AG2-424 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:48

Summersville - Magnolia 69 kV

34.95 MW Capacity / 63.25 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Magnolia Solar and Grazing Farm LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is East Kentucky Power Cooperative, Inc..

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $14,069,372 $15,450,810 = 0.91 AND ( $14,069,372 - $15,450,810 ) 63.2 = $-21,841 per MW

General

The Project Developer has proposed a Solar/Storage generating facility located in the East Kentucky Power Cooperative, Inc. zone — Larue County, Kentucky. The installed facilities will have a total capability of 63.25 MW with 34.95 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-424
Project Name:
Summersville - Magnolia 69 kV
Project Developer Name:
Magnolia Solar and Grazing Farm LLC
State:
Kentucky
County:
Larue
Transmission Owner:
East Kentucky Power Cooperative, Inc.
MFO:
63.25
MWE:
63.25
MWC:
34.95
Battery Storage Specification:
60.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Solar/Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-424 will interconnect on the East Kentucky Power Cooperative, Inc. transmission system tapping the Magnolia - Summersville 69 kV line .

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-424 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-424Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$1,989,000$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$8,316,000$8,316,000$8,316,000
Network Upgrades$948,000$948,000$948,000
System Reliability Network Upgrades
Steady State Thermal & Voltage$4,805,372$4,805,372$4,805,372
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$16,058,372$14,069,372$14,069,372

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-424

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-424
Project ID: AG2-424
20% of cost allocation for Phase II Network Upgrades:(A) $2,813,874
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $1,355,926
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $1,457,948
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Revise relay settings/relays at the existing Hodgenville substation.

$85,000$5,000$14,000$2,000$106,000$106,000
(Pending)

Revise relay settings/relays at the existing Green County substation.

$85,000$5,000$14,000$2,000$106,000$106,000
(Pending)

Loop the existing Magnolia-Summersville 69 kV line into the new South Larue County interconnection switching station.

$425,000$205,000$95,000$11,000$736,000$736,000
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

South Larue County 69 Switching Station: Construct a new 69 kV switching station along the Magnolia-Summersville 69 kV line.

$3,420,000$3,706,000$1,071,000$119,000$8,316,000$8,316,000
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

One (1) 69 kV generator lead line to include, but not limited to, installation of one 69 kV breaker, a 69 kV line monopole dead-end structure and foundation, a 3-pole disconnect switch mounted to the monopole, line conductor from the dead-end structure to the bus position in the switchyard, two (2) 48-strand fiber optic cables, and 69 kV metering equipment.

$1,051,000$654,000$256,000$28,000$1,989,000$1,989,000
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Revise relay settings/relays at the existing Hodgenville substation.

$85,000$5,000$14,000$2,000$106,000$106,000
(Pending)

Revise relay settings/relays at the existing Green County substation.

$85,000$5,000$14,000$2,000$106,000$106,000
(Pending)

Loop the existing Magnolia-Summersville 69 kV line into the new South Larue County interconnection switching station.

$425,000$205,000$95,000$11,000$736,000$736,000
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

EKPC Oversight for New Interconnection Substation (South Larue County 69 kV) for Developer Build (AG2-424)

$1,129,000$216,000$146,000$146,000$1,637,000$1,637,000
(Pending)

EKPC Oversight for Transmission Owner Interconnection Facilities for Developer Build for AG2-424

$277,000$45,000$35,000$35,000$392,000$392,000
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$11,253,000$11,253,000
Developer Build Option$2,977,000$2,977,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 18 to 33 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. EKPC interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-424 was evaluated as a 63.25 MW (34.95 MW Capacity) injection in the EKPC area.

AG2-424 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 63.25 MW (63.25 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
6.24
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
6.24
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
6.24
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
6.24
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.16
6.24
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC102.09 %5523.0B5638.63
4.59
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC102.08 %5523.0B5637.94
4.59
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
6.24
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
6.24
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
6.24
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
6.24
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.16
6.24
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC123.36 %4571.0B5638.63
4.59
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC123.34 %4571.0B5637.94
4.59
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#3149_05HANG R 765_B_SRT-A
BreakerAC143.94 %1540.0B2216.66
3.76
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC123.49 %1540.0B1901.76
3.56
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1558_05BAKER 765_Q_SRT-A
BreakerAC121.58 %1540.0B1872.34
3.21
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#309_05HANG R 765_B2_SRT-A
BreakerAC121.32 %1540.0B1868.38
3.23
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
BreakerAC121.04 %1540.0B1864.08
3.23
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#6156_05MARQUI 765_2_SRT-A
BusAC120.75 %1540.0B1859.53
3.73
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC108.24 %1540.0B1666.97
3.1
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC107.72 %1189.0A1280.85
2.23
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
BusAC106.64 %1540.0B1642.31
3.15
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
BusAC106.58 %1540.0B1641.32
3.2
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P7-1_#11019___SRT-A-2
TowerAC106.15 %1540.0B1634.72
3.15
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC105.24 %1540.0B1620.65
3.17
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC104.94 %1540.0B1616.13
3.02
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT5_SRT-SL
BusAC103.91 %1540.0B1600.21
3.02
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#316_05AMOS 765_2_SRT-A
BusAC101.35 %1540.0B1560.82
3.03
GD2EKPC/LGEE
2GREEN CO-2GRENSBRG KU 69.0 kV Ckt 1 line
EKPC_P1-2_GRE-AF1-083161_SRT-A
SingleAC101.58 %66.0B67.04
2.72
GD2EKPC/LGEE
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
EKPC_P2-2_KU HODG 69_SRT-A
BusAC106.61 %50.0B53.3
3.12
IPDEKPC
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
EKPC_P1-2_AG2-424 TP-2MAGNOLIA-69_SRT-A
SingleAC157.14 %39.0B61.28
63.25
IPDEKPC
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
EKPC_P2-2_KU HODG 69_SRT-A
BusAC144.51 %39.0B56.36
63.25
GD2EKPC
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
EKPC_P2-3_GREEN W45-1014_SRT-A
BreakerAC112.88 %39.0B44.02
15.5
IPDEKPC
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
EKPC_P2-3_GREEN W45-1014_SRT-A
BreakerAC104.24 %39.0B40.66
20.64
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC196.67 %277.0B544.77
2.65

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
6.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
6.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
6.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
6.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
6.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
4.59
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
4.59
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
6.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
6.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
6.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
6.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
6.24
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
971067AG2-660 GEN
Solar/Wind Harmer
0.672
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.36 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
4.59
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
4.59
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#3149_05HANG R 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3149_05HANG R 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2216.66
MW Contribution:
3.76
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.637
24803306KYGER 4LP
50/50
2.583
971191AH1-055 GEN
Solar/Wind Harmer
85.223
252507AC2-088 GEN
Solar/Wind Harmer
2.672
253317AC1-085 GEN4
Solar/Wind Harmer
11.681
946181AF1-283 GEN
Solar/Wind Harmer
18.138
252519AF1-045_GEN
Solar/Wind Harmer
5.073
25194608D.CRK4
Adder
2.171
252524AE2-267 GEN
Solar/Wind Harmer
2.074
25196608WSDLE5
Adder
11.291
958171AF2-111 GEN
Solar/Wind Harmer
32.8
253394AE2-221_GEN
Solar/Wind Harmer
5.919
270367AC2-061_GEN
Solar/Wind Harmer
3.968
270186AC1-089 GEN
Solar/Wind Harmer
7.496
972167AH1-666 GEN
Solar/Wind Harmer
9.813
25196008MFTGT1
Adder
1.652
339243AC2-075 GEN1
Solar/Wind Harmer
0.505
253303V4-073 C
Solar/Wind Harmer
0.125
253370AE2-315 SEC1
Adder
2.154
253371AE2-315 SEC2
Adder
2.037
960071AF2-298 GEN
Solar/Wind Harmer
1.548
3429391JKCT 9G
Adder
8.012
253325AC1-069 GEN
Solar/Wind Harmer
0.911
970093AG2-073 GEN
Solar/Wind Harmer
4.533
24379505HDWTR1G C
Solar/Wind Harmer
6.491
270240V3-007_GEN2
Solar/Wind Harmer
5.079
270518AE2-148 GEN
Solar/Wind Harmer
9.286
270004AE1-209 GEN
Solar/Wind Harmer
4.08
970455AG2-298 GEN
Solar/Wind Harmer
2.601
946031AF1-268 GEN
Solar/Wind Harmer
6.158
24728505AND G1
Adder
2.824
970825AG2-519 GEN
Solar/Wind Harmer
4.143
962031AG1-047 GEN
Solar/Wind Harmer
2.182
957741AF2-068 GEN
Solar/Wind Harmer
10.823
970879AG2-548 GEN
Solar/Wind Harmer
5.557
276820AF1-078_GEN
Solar/Wind Harmer
1.094
970653AG2-424 GEN
Solar/Wind Harmer
0.476
339206AE1-143 GEN
Solar/Wind Harmer
1.407
965461AG1-414 GEN
Solar/Wind Harmer
1.435
970289AG2-191 GEN
Solar/Wind Harmer
0.486
247642Z2-115 C
Solar/Wind Harmer
0.039
942051AE2-217 GEN
Solar/Wind Harmer
10.751
944531AF1-118 GEN
Solar/Wind Harmer
20.719
960801AF2-371 GEN
Solar/Wind Harmer
1.503
964871AG1-351 GEN
Solar/Wind Harmer
1.038
972273AH1-721 GEN
Adder
48.281
970193AG2-126 GEN
Solar/Wind Harmer
8.371
957541AF2-048 GEN
Solar/Wind Harmer
0.86
339255AE2-071 GEN
Solar/Wind Harmer
0.625
339250AF1-203 GEN
Solar/Wind Harmer
0.322
24386205FR-12G C
Solar/Wind Harmer
2.102
942481AE2-261 GEN
Solar/Wind Harmer
14.45
957381AF2-032 GEN
Solar/Wind Harmer
0.966
276785W4-005 GEN1
Solar/Wind Harmer
1.451
971993AH1-541 GEN
Solar/Wind Harmer
4.434
24690905MDL-1G C
Solar/Wind Harmer
3.811
274729ELWOOD EC;1P
Adder
7.239
274730ELWOOD EC;6P
Adder
7.239
274734ELWOOD EC;8P
Adder
7.239
274736ELWOOD EC;9P
Adder
7.239
972259AH1-714 GEN
Adder
8.385
972038AH1-567 GEN2
Adder
0.16
274676JOLIET 29;8U
Adder
12.994
274803UNIV PARK;6U
Adder
2.56
274826FISK ;BP
Adder
4.804
274814UNIV PK N;0U
Adder
2.215
274807UNIV PK N;3U
Adder
2.21
274811UNIV PK N;7U
Adder
2.195
274682WAUKEGAN ;7U
Adder
7.875
274760LEE CO EC;1U
Adder
4.074
274767LEE CO EC;8U
Adder
4.026
274724RIVER EC ;11
Adder
5.289
270330AC1-082 GEN2
Solar/Wind Helper
0.17
270329AC1-082 GEN1
Solar/Wind Helper
0.17
970781AG2-491 GEN
Solar/Wind Harmer
2.151
24802606KYGER 1HP
50/50
4.51
24802706KYGER 1LP
50/50
2.645
24803506KYGER 5LP
50/50
2.583
971985AH1-537 GEN
Solar/Wind Harmer
56.698
253433AC1-085 GEN1
Solar/Wind Harmer
7.414
253432AC1-085 GEN2
Solar/Wind Harmer
0.373
270263AC1-001 GEN
Solar/Wind Harmer
1.45
25196408WSDLE3
Adder
11.623
270340AC2-060 GEN
Solar/Wind Harmer
3.884
253406AD2-031_GEN
Solar/Wind Harmer
1.593
25196108MFTGT2
Adder
1.88
25196108MFTGT2
Adder
1.746
972163AH1-664 GEN
Solar/Wind Harmer
12.044
972165AH1-665 GEN
Solar/Wind Harmer
9.636
339216AC1-074 GEN
Solar/Wind Harmer
1.864
270432AC2-029 GEN
Solar/Wind Harmer
7.644
253372AE2-315 SEC3
Adder
2.037
253372AE2-315 SEC3
Adder
2.037
25306009OHH W.
Adder
3.033
3429211JKCT 2G
Adder
10.852
241972AD1-140 GEN
Solar/Wind Harmer
4.019
253338AC1-165 GEN
Solar/Wind Harmer
0.945
253343AC1-166 GEN
Solar/Wind Harmer
0.945
270356AE2-297 GEN
Solar/Wind Harmer
3.987
971029AG2-637 GEN
Solar/Wind Harmer
12.539
270543AE2-219 C
Solar/Wind Harmer
7.986
247536S-71 GEN
Solar/Wind Harmer
3.092
964611AG1-324 GEN
Solar/Wind Harmer
2.831
961761AG1-017 GEN
Solar/Wind Harmer
0.309
945581AF1-223 GEN
Solar/Wind Harmer
3.114
945631AF1-228 GEN
Solar/Wind Harmer
3.07
958711AF2-162 GEN
Solar/Wind Harmer
0.655
943861AF1-054 GEN
Solar/Wind Harmer
2.451
943851AF1-053 GEN
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
1.202
24729505KEY G4
Adder
3.936
270291AC1-194 GEN
Solar/Wind Harmer
2.922
270444AC2-157 GEN1
Solar/Wind Harmer
3.091
270445AC2-157 GEN2
Solar/Wind Harmer
3.091
963791AG1-232 GEN
Solar/Wind Harmer
7.435
241955AC1-078 GEN
Solar/Wind Harmer
4.102
241973AD2-163_GEN1
Solar/Wind Harmer
1.085
241974AD2-163_GEN2
Solar/Wind Harmer
1.085
963841AG1-237 GEN
Solar/Wind Harmer
5.506
24386405FR-21G C
Solar/Wind Harmer
2.11
24387005FR-3G C
Solar/Wind Harmer
1.94
270071AF1-092 GEN
Solar/Wind Harmer
7.35
944221AF1-090 GEN
Solar/Wind Harmer
5.351
276763AC1-053 GEN1
Solar/Wind Harmer
1.897
276764AC1-053 GEN2
Solar/Wind Harmer
1.897
276668AB2-070 GEN1
Solar/Wind Harmer
1.062
276848AB2-070 GEN3
Solar/Wind Harmer
1.062
276849AB2-070 GEN2
Solar/Wind Harmer
1.062
946581AF1-322 GEN
Solar/Wind Harmer
4.858
24691005MDL-2G C
Solar/Wind Harmer
1.756
274731ELWOOD EC;2P
Adder
7.239
274733ELWOOD EC;3P
Adder
7.239
274735ELWOOD EC;4P
Adder
7.239
274728ELWOOD EC;5P
Adder
7.239
972228AH1-698 GEN2
Adder
1.631
972227AH1-698 GEN1
Adder
1.148
274800UNIV PARK;3U
Adder
2.561
274801UNIV PARK;4U
Adder
2.561
274675JOLIET 29;7U
Adder
13.475
274675JOLIET 29;7U
Adder
12.994
274687WILL CNTY;4U
Adder
12.271
274687WILL CNTY;4U
Adder
12.271
972037AH1-567 GEN1
Adder
0.08
274744AC1-111 GEN8
Adder
2.453
274746AC1-111 G10
Adder
2.453
274827FISK ;RP
Adder
3.404
972267AH1-718 GEN
Adder
1.824
24803006KYGER 3HP
50/50
4.478
24802806KYGER 2HP
50/50
4.462
24802906KYGER 2LP
50/50
2.619
25183008BIOENL
50/50
0.04
252509AD1-136 GEN
Solar/Wind Harmer
0.382
25183208HLCRTG
Solar/Wind Harmer
8.726
270269AC2-059
Solar/Wind Harmer
12.725
25194408D.CRK1
Adder
9.987
25194508D.CRK3
Adder
1.867
253415AE1-040 GEN
Solar/Wind Harmer
1.391
962581AG1-107 GEN
Solar/Wind Harmer
6.139
961491AF2-440 GEN
Solar/Wind Harmer
2.552
253370AE2-315 SEC1
Adder
2.154
972043AH1-570 GEN
Solar/Wind Harmer
2.668
972045AH1-571 GEN
Solar/Wind Harmer
2.134
25322209TAIT E
Adder
10.12
25322209TAIT E
Adder
9.892
253349AC2-067 GEN
Solar/Wind Harmer
2.068
253400AC2-068 GEN
Solar/Wind Harmer
0.832
25326109MON D
Adder
1.335
971125AH1-004 GEN
Solar/Wind Harmer
4.054
970107AG2-081 GEN
Solar/Wind Harmer
3.041
942891AE2-308 GEN
Solar/Wind Harmer
9.049
926881AC1-175 GEN
Solar/Wind Harmer
4.582
270383AD1-128 GEN
Solar/Wind Harmer
4.96
970883AG2-550 GEN
Solar/Wind Harmer
7.986
970885AG2-551 GEN
Solar/Wind Harmer
1.857
247621Y3-024
Adder
0.179
25326509SID D
Adder
0.961
964611AG1-324 GEN
Solar/Wind Harmer
0.38
270201AC2-176 GEN
Solar/Wind Harmer
3.708
964571AG1-320 GEN
Solar/Wind Harmer
5.837
971073AG2-665 GEN
Solar/Wind Harmer
5.557
970879AG2-548 GEN
Solar/Wind Harmer
0.808
24725505WLD G2 C
Solar/Wind Harmer
2.754
24699105WLD G1 C
Solar/Wind Harmer
2.722
253378AE2-206_GEN
Solar/Wind Harmer
2.463
270031AE2-169
Solar/Wind Harmer
5.579
270599AE1-208 GEN
Solar/Wind Harmer
5.579
944541AF1-119 GEN
Solar/Wind Harmer
2.712
960971AF2-388 GEN
Solar/Wind Harmer
7.079
942861AE2-305 GEN
Solar/Wind Harmer
4.965
970291AG2-192 GEN
Solar/Wind Harmer
0.823
970291AG2-192 GEN
Solar/Wind Harmer
0.265
942221AE2-234 GEN
Solar/Wind Harmer
2.13
339236AF1-050_GEN
Solar/Wind Harmer
1.062
945391AF1-204 GEN
Solar/Wind Harmer
7.777
339231AF1-038_GEN
Solar/Wind Harmer
1.01
927014AC1-188 GEN
Solar/Wind Harmer
0.86
964781AG1-341 GEN
Solar/Wind Harmer
5.607
253383AE2-342_GEN
Solar/Wind Harmer
0.463
970241AG2-163 GEN
Solar/Wind Harmer
12.901
971485AH1-239 GEN
Solar/Wind Harmer
3.962
24387305FR-4G C
Solar/Wind Harmer
2.492
966841AG1-555 GEN
Solar/Wind Harmer
1.232
966021AG1-471 GEN
Solar/Wind Harmer
2.631
276916AD2-100_GEN
Solar/Wind Harmer
10.179
276911AD2-131_GEN
Solar/Wind Harmer
2.057
276615X2-022 GEN
Solar/Wind Harmer
0.941
276838X2-022 GEN2
Solar/Wind Harmer
0.112
274880W4-005 GEN4
Solar/Wind Harmer
1.451
276174W4-005 GEN2
Solar/Wind Harmer
1.451
270180AB1-006 GEN1
Solar/Wind Harmer
3.414
24697605MDL-3G C
Solar/Wind Harmer
1.75
24755605MDL-5G
Solar/Wind Harmer
1.145
24697905MDL-4G C
Solar/Wind Harmer
1.089
270181AB1-006 GEN2
Solar/Wind Harmer
0.34
274674JOLIET 9 ;6U
Adder
6.773
274696ROCKY RD ;4P
Adder
4.997
274695ROCKY RD ;2P
Adder
4.881
274693ROCKY RD ;1P
Adder
4.833
274697ROCKY RD ;3P
Adder
1.326
274805UNIV PK N;1U
Adder
2.2
274808UNIV PK N;4U
Adder
2.186
274683WAUKEGAN ;8U
Adder
9.232
274683WAUKEGAN ;8U
Adder
7.782
274764LEE CO EC;5U
Adder
4.084
274765LEE CO EC;6U
Adder
4.084
274762LEE CO EC;3U
Adder
4.074
274763LEE CO EC;4U
Adder
4.036
237033AB1-150 GEN
Solar/Wind Helper
0.429
24803406KYGER 5HP
50/50
4.427
24803206KYGER 4HP
50/50
4.417
253316AC1-085 GEN3
Solar/Wind Harmer
11.681
946171AF1-282 GEN
Solar/Wind Harmer
13.952
252516AE2-318_GEN
Solar/Wind Harmer
13.939
25196808ZIMRHP
Adder
103.883
270273AD2-016 GEN
Solar/Wind Harmer
3.628
252510AF1-249 C
Solar/Wind Harmer
0.552
25194608D.CRK4
Adder
2.171
253398AE2-221_GEN2
Solar/Wind Harmer
5.919
25196008MFTGT1
Adder
1.705
945681AF1-233 GEN
Solar/Wind Harmer
23.016
339221AD2-048_GEN
Solar/Wind Harmer
1.678
253370AE2-315 SEC1
Adder
2.154
253371AE2-315 SEC2
Adder
2.037
25326309TAIT D
Adder
1.136
270222AC2-111 GEN
Solar/Wind Harmer
4.57
944031AF1-071 GEN
Solar/Wind Harmer
1.028
943111AE2-339 GEN
Solar/Wind Harmer
0.888
3429421JKCT 10G
Adder
8.012
3429241JKCT 3G
Adder
10.994
253333AC1-068 GEN
Solar/Wind Harmer
0.911
942081AE2-220 GEN
Solar/Wind Harmer
5.25
270209AC1-174_GEN
Solar/Wind Harmer
3.341
270437AC2-090 C
Solar/Wind Harmer
4.582
270239V3-007_GEN1
Solar/Wind Harmer
1.413
339211AE2-254 GEN
Solar/Wind Harmer
1.157
270005AE1-210 C O1
Solar/Wind Harmer
4.08
24728605AND G2
Adder
2.824
970825AG2-519 GEN
Solar/Wind Harmer
1.543
971073AG2-665 GEN
Solar/Wind Harmer
0.808
945371AF1-202 GEN
Solar/Wind Harmer
4.791
970653AG2-424 GEN
Solar/Wind Harmer
3.289
276903AD2-071 C
Solar/Wind Harmer
6.734
958861AF2-177 GEN
Solar/Wind Harmer
7.226
270594AE1-207 GEN
Solar/Wind Harmer
8.954
270032AE2-172
Solar/Wind Harmer
3.066
270024AE2-089 GEN
Solar/Wind Harmer
3.071
965651AG1-433 GEN
Solar/Wind Harmer
3.54
339241AF1-083 GEN
Solar/Wind Harmer
1.047
964901AG1-354 GEN
Solar/Wind Harmer
8.68
970091AG2-072 GEN
Adder
41.08
963741AG1-226 GEN
Solar/Wind Harmer
23.222
24385905FR-11G C
Solar/Wind Harmer
4.077
24386605FR-22G C
Solar/Wind Harmer
2.11
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
2.997
276686W4-005 GEN3
Solar/Wind Harmer
1.451
24791305MDL-5G
Solar/Wind Harmer
1.145
274732ELWOOD EC;7P
Adder
7.239
274674JOLIET 9 ;6U
Adder
6.773
274676JOLIET 29;8U
Adder
13.475
274802UNIV PARK;5U
Adder
2.56
274745AC1-111 GEN9
Adder
2.453
274812UNIV PK N;8U
Adder
2.195
274682WAUKEGAN ;7U
Adder
7.875
274828WAUKEGAN ;BP
Adder
4.839
274761LEE CO EC;2U
Adder
4.074
274766LEE CO EC;7U
Adder
4.026
274723RIVER EC ;12
Adder
7.842
960001AF2-291 GEN
Solar/Wind Helper
1.495
270331AC1-082 GEN3
Solar/Wind Helper
0.169
235780M24_1
Solar/Wind Helper
0.532
LAGNLTFEXP_LAGN->PJM
CLTF
5.53
TVALTFEXP_TVA->PJM
CLTF
2.623
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.436
CBM West 1LTFEXP_CBM-W1->PJM
CBM
67.865
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.827
MECLTFEXP_MEC->PJM
CLTF
7.138
SIGELTFEXP_SIGE->PJM
CLTF
0.35
NYPJM->LTFIMP_NY
CLTF
1.649
LGEELTFEXP_LGEE->PJM
CLTF
5.838
WECLTFEXP_WEC->PJM
CLTF
1.668
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.901
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.263

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.49 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1901.76
MW Contribution:
3.56
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.165
24802706KYGER 1LP
50/50
2.442
24803506KYGER 5LP
50/50
2.385
971985AH1-537 GEN
Solar/Wind Harmer
50.232
25196408WSDLE3
Adder
9.326
25196108MFTGT2
Adder
1.564
25196108MFTGT2
Adder
1.452
253433AC1-085 GEN1
Solar/Wind Harmer
5.406
253432AC1-085 GEN2
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
9.279
972165AH1-665 GEN
Solar/Wind Harmer
7.424
339216AC1-074 GEN
Solar/Wind Harmer
1.517
253406AD2-031_GEN
Solar/Wind Harmer
1.147
270340AC2-060 GEN
Solar/Wind Harmer
2.587
270263AC1-001 GEN
Solar/Wind Harmer
0.87
253372AE2-315 SEC3
Adder
1.541
253372AE2-315 SEC3
Adder
1.541
25306009OHH W.
Adder
2.304
3429211JKCT 2G
Adder
9.05
270356AE2-297 GEN
Solar/Wind Harmer
3.35
971029AG2-637 GEN
Solar/Wind Harmer
10.129
241972AD1-140 GEN
Solar/Wind Harmer
2.94
270432AC2-029 GEN
Solar/Wind Harmer
4.54
270543AE2-219 C
Solar/Wind Harmer
6.457
270444AC2-157 GEN1
Solar/Wind Harmer
3.536
270445AC2-157 GEN2
Solar/Wind Harmer
3.536
247536S-71 GEN
Solar/Wind Harmer
2.502
964611AG1-324 GEN
Solar/Wind Harmer
2.301
961761AG1-017 GEN
Solar/Wind Harmer
0.25
253338AC1-165 GEN
Solar/Wind Harmer
0.633
253343AC1-166 GEN
Solar/Wind Harmer
0.633
945581AF1-223 GEN
Solar/Wind Harmer
2.541
958711AF2-162 GEN
Solar/Wind Harmer
0.529
970289AG2-191 GEN
Solar/Wind Harmer
0.966
24729505KEY G4
Adder
3.139
944221AF1-090 GEN
Solar/Wind Harmer
5.121
963841AG1-237 GEN
Solar/Wind Harmer
4.848
276763AC1-053 GEN1
Solar/Wind Harmer
1.744
276764AC1-053 GEN2
Solar/Wind Harmer
1.744
276668AB2-070 GEN1
Solar/Wind Harmer
0.974
276848AB2-070 GEN3
Solar/Wind Harmer
0.974
276849AB2-070 GEN2
Solar/Wind Harmer
0.974
943861AF1-054 GEN
Solar/Wind Harmer
1.665
943851AF1-053 GEN
Solar/Wind Harmer
0.805
24803006KYGER 3HP
50/50
4.136
24802806KYGER 2HP
50/50
4.121
24802906KYGER 2LP
50/50
2.418
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.299
25183208HLCRTG
Solar/Wind Harmer
6.647
25194408D.CRK1
Adder
7.991
25194508D.CRK3
Adder
1.494
962581AG1-107 GEN
Solar/Wind Harmer
4.435
961491AF2-440 GEN
Solar/Wind Harmer
1.844
972043AH1-570 GEN
Solar/Wind Harmer
2.164
972045AH1-571 GEN
Solar/Wind Harmer
1.731
971125AH1-004 GEN
Solar/Wind Harmer
3.34
970107AG2-081 GEN
Solar/Wind Harmer
2.505
270269AC2-059
Solar/Wind Harmer
7.76
253415AE1-040 GEN
Solar/Wind Harmer
0.936
253370AE2-315 SEC1
Adder
1.629
25322209TAIT E
Adder
7.66
25322209TAIT E
Adder
7.488
253349AC2-067 GEN
Solar/Wind Harmer
1.584
253400AC2-068 GEN
Solar/Wind Harmer
0.637
25326109MON D
Adder
1.005
942891AE2-308 GEN
Solar/Wind Harmer
7.614
926881AC1-175 GEN
Solar/Wind Harmer
3.8
964571AG1-320 GEN
Solar/Wind Harmer
5.537
270383AD1-128 GEN
Solar/Wind Harmer
4.066
970883AG2-550 GEN
Solar/Wind Harmer
6.457
970885AG2-551 GEN
Solar/Wind Harmer
1.502
247621Y3-024
Adder
0.145
964611AG1-324 GEN
Solar/Wind Harmer
0.309
270201AC2-176 GEN
Solar/Wind Harmer
3.006
24725505WLD G2 C
Solar/Wind Harmer
2.27
24699105WLD G1 C
Solar/Wind Harmer
2.244
339236AF1-050_GEN
Solar/Wind Harmer
1.02
270031AE2-169
Solar/Wind Harmer
4.558
270599AE1-208 GEN
Solar/Wind Harmer
4.558
25326509SID D
Adder
0.702
339231AF1-038_GEN
Solar/Wind Harmer
0.965
945391AF1-204 GEN
Solar/Wind Harmer
7.373
944541AF1-119 GEN
Solar/Wind Harmer
2.19
960971AF2-388 GEN
Solar/Wind Harmer
5.716
964781AG1-341 GEN
Solar/Wind Harmer
5.52
970291AG2-192 GEN
Solar/Wind Harmer
0.661
970291AG2-192 GEN
Solar/Wind Harmer
0.213
253378AE2-206_GEN
Solar/Wind Harmer
1.774
971485AH1-239 GEN
Solar/Wind Harmer
3.886
942221AE2-234 GEN
Solar/Wind Harmer
1.69
966021AG1-471 GEN
Solar/Wind Harmer
2.588
970241AG2-163 GEN
Solar/Wind Harmer
11.574
276916AD2-100_GEN
Solar/Wind Harmer
9.604
276911AD2-131_GEN
Solar/Wind Harmer
1.941
276615X2-022 GEN
Solar/Wind Harmer
0.87
276838X2-022 GEN2
Solar/Wind Harmer
0.103
274880W4-005 GEN4
Solar/Wind Harmer
1.331
276174W4-005 GEN2
Solar/Wind Harmer
1.331
942861AE2-305 GEN
Solar/Wind Harmer
3.374
237033AB1-150 GEN
Solar/Wind Helper
0.386
24803406KYGER 5HP
50/50
4.088
24803206KYGER 4HP
50/50
4.079
252516AE2-318_GEN
Solar/Wind Harmer
10.884
25196808ZIMRHP
Adder
81.628
25194608D.CRK4
Adder
1.737
252510AF1-249 C
Solar/Wind Harmer
0.44
25196008MFTGT1
Adder
1.418
253316AC1-085 GEN3
Solar/Wind Harmer
8.517
946171AF1-282 GEN
Solar/Wind Harmer
10.173
253398AE2-221_GEN2
Solar/Wind Harmer
4.342
945681AF1-233 GEN
Solar/Wind Harmer
17.68
339221AD2-048_GEN
Solar/Wind Harmer
1.364
270273AD2-016 GEN
Solar/Wind Harmer
2.213
943111AE2-339 GEN
Solar/Wind Harmer
0.732
270222AC2-111 GEN
Solar/Wind Harmer
3.698
944031AF1-071 GEN
Solar/Wind Harmer
0.832
253370AE2-315 SEC1
Adder
1.629
253371AE2-315 SEC2
Adder
1.541
3429421JKCT 10G
Adder
6.632
970091AG2-072 GEN
Adder
60.833
25326309TAIT D
Adder
0.86
3429241JKCT 3G
Adder
9.168
339211AE2-254 GEN
Solar/Wind Harmer
1.029
942081AE2-220 GEN
Solar/Wind Harmer
4.355
270209AC1-174_GEN
Solar/Wind Harmer
2.771
270437AC2-090 C
Solar/Wind Harmer
3.8
270239V3-007_GEN1
Solar/Wind Harmer
1.172
970653AG2-424 GEN
Solar/Wind Harmer
3.113
24728605AND G2
Adder
2.452
270005AE1-210 C O1
Solar/Wind Harmer
3.373
970825AG2-519 GEN
Solar/Wind Harmer
1.27
339241AF1-083 GEN
Solar/Wind Harmer
0.988
253333AC1-068 GEN
Solar/Wind Harmer
0.611
945371AF1-202 GEN
Solar/Wind Harmer
3.908
964901AG1-354 GEN
Solar/Wind Harmer
8.361
276903AD2-071 C
Solar/Wind Harmer
5.516
958861AF2-177 GEN
Solar/Wind Harmer
5.856
270594AE1-207 GEN
Solar/Wind Harmer
7.241
270032AE2-172
Solar/Wind Harmer
2.48
270024AE2-089 GEN
Solar/Wind Harmer
2.452
965651AG1-433 GEN
Solar/Wind Harmer
2.858
963741AG1-226 GEN
Solar/Wind Harmer
20.834
965911AG1-460 GEN
Solar/Wind Harmer
0.634
276621W2-048 GEN
Solar/Wind Harmer
2.771
276686W4-005 GEN3
Solar/Wind Harmer
1.331
960001AF2-291 GEN
Solar/Wind Helper
1.708
270331AC1-082 GEN3
Solar/Wind Helper
0.192
235780M24_1
Solar/Wind Helper
0.478
24803106KYGER 3LP
50/50
2.435
24803306KYGER 4LP
50/50
2.385
971191AH1-055 GEN
Solar/Wind Harmer
71.732
252507AC2-088 GEN
Solar/Wind Harmer
2.093
252519AF1-045_GEN
Solar/Wind Harmer
3.961
252524AE2-267 GEN
Solar/Wind Harmer
1.664
25196608WSDLE5
Adder
9.059
25194608D.CRK4
Adder
1.737
25196008MFTGT1
Adder
1.374
253317AC1-085 GEN4
Solar/Wind Harmer
8.517
946181AF1-283 GEN
Solar/Wind Harmer
13.225
958171AF2-111 GEN
Solar/Wind Harmer
24.984
253394AE2-221_GEN
Solar/Wind Harmer
4.342
972167AH1-666 GEN
Solar/Wind Harmer
7.533
270367AC2-061_GEN
Solar/Wind Harmer
2.88
339243AC2-075 GEN1
Solar/Wind Harmer
0.411
270186AC1-089 GEN
Solar/Wind Harmer
5.474
253303V4-073 C
Solar/Wind Harmer
0.094
253370AE2-315 SEC1
Adder
1.629
253371AE2-315 SEC2
Adder
1.541
3429391JKCT 9G
Adder
6.632
960071AF2-298 GEN
Solar/Wind Harmer
1.175
970093AG2-073 GEN
Solar/Wind Harmer
3.861
970455AG2-298 GEN
Solar/Wind Harmer
2.419
24379505HDWTR1G C
Solar/Wind Harmer
5.384
270240V3-007_GEN2
Solar/Wind Harmer
4.212
970653AG2-424 GEN
Solar/Wind Harmer
0.45
24728505AND G1
Adder
2.452
270004AE1-209 GEN
Solar/Wind Harmer
3.373
339206AE1-143 GEN
Solar/Wind Harmer
1.311
946031AF1-268 GEN
Solar/Wind Harmer
5.055
970825AG2-519 GEN
Solar/Wind Harmer
3.411
962031AG1-047 GEN
Solar/Wind Harmer
1.769
957741AF2-068 GEN
Solar/Wind Harmer
8.774
253325AC1-069 GEN
Solar/Wind Harmer
0.611
972273AH1-721 GEN
Adder
45.289
970193AG2-126 GEN
Solar/Wind Harmer
7.936
270518AE2-148 GEN
Solar/Wind Harmer
6.377
339255AE2-071 GEN
Solar/Wind Harmer
0.613
339250AF1-203 GEN
Solar/Wind Harmer
0.316
965461AG1-414 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
0.39
276820AF1-078_GEN
Solar/Wind Harmer
0.788
247642Z2-115 C
Solar/Wind Harmer
0.031
944531AF1-118 GEN
Solar/Wind Harmer
16.445
942481AE2-261 GEN
Solar/Wind Harmer
13.577
957381AF2-032 GEN
Solar/Wind Harmer
0.906
276785W4-005 GEN1
Solar/Wind Harmer
1.331
971993AH1-541 GEN
Solar/Wind Harmer
4.067
270330AC1-082 GEN2
Solar/Wind Helper
0.193
270329AC1-082 GEN1
Solar/Wind Helper
0.193
LAGNLTFEXP_LAGN->PJM
CLTF
6.101
TVALTFEXP_TVA->PJM
CLTF
3.013
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
CBM West 1LTFEXP_CBM-W1->PJM
CBM
57.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.776
MECLTFEXP_MEC->PJM
CLTF
6.502
SIGELTFEXP_SIGE->PJM
CLTF
0.338
NYPJM->LTFIMP_NY
CLTF
1.477
LGEELTFEXP_LGEE->PJM
CLTF
5.581
WECLTFEXP_WEC->PJM
CLTF
1.413
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.272
AG2-052LTFEXP_AG2-052->PJM
LTF
0.09
AH1-155LTFEXP_AH1-155->PJM
LTF
0.135
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.85

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1558_05BAKER 765_Q_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1558_05BAKER 765_Q_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.58 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1872.34
MW Contribution:
3.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1558_05BAKER 765_Q_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.08 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2295.78
MW Contribution:
3.38
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.206
24802706KYGER 1LP
50/50
2.466
24803506KYGER 5LP
50/50
2.408
971985AH1-537 GEN
Solar/Wind Harmer
50.38
25196408WSDLE3
Adder
9.236
253433AC1-085 GEN1
Solar/Wind Harmer
5.516
253432AC1-085 GEN2
Solar/Wind Harmer
0.278
25196108MFTGT2
Adder
1.524
25196108MFTGT2
Adder
1.415
253406AD2-031_GEN
Solar/Wind Harmer
1.174
972163AH1-664 GEN
Solar/Wind Harmer
9.177
972165AH1-665 GEN
Solar/Wind Harmer
7.342
270263AC1-001 GEN
Solar/Wind Harmer
0.943
270340AC2-060 GEN
Solar/Wind Harmer
2.713
339216AC1-074 GEN
Solar/Wind Harmer
1.469
253372AE2-315 SEC3
Adder
1.56
253372AE2-315 SEC3
Adder
1.56
25306009OHH W.
Adder
2.331
3429211JKCT 2G
Adder
8.597
270356AE2-297 GEN
Solar/Wind Harmer
3.32
270432AC2-029 GEN
Solar/Wind Harmer
4.963
971029AG2-637 GEN
Solar/Wind Harmer
10.225
241972AD1-140 GEN
Solar/Wind Harmer
3.018
270543AE2-219 C
Solar/Wind Harmer
6.542
247536S-71 GEN
Solar/Wind Harmer
2.544
253338AC1-165 GEN
Solar/Wind Harmer
0.67
253343AC1-166 GEN
Solar/Wind Harmer
0.67
964611AG1-324 GEN
Solar/Wind Harmer
2.347
961761AG1-017 GEN
Solar/Wind Harmer
0.256
945581AF1-223 GEN
Solar/Wind Harmer
2.597
270444AC2-157 GEN1
Solar/Wind Harmer
3.034
270445AC2-157 GEN2
Solar/Wind Harmer
3.034
970289AG2-191 GEN
Solar/Wind Harmer
1.032
958711AF2-162 GEN
Solar/Wind Harmer
0.546
24729505KEY G4
Adder
3.282
963841AG1-237 GEN
Solar/Wind Harmer
5.056
945631AF1-228 GEN
Solar/Wind Harmer
2.147
943861AF1-054 GEN
Solar/Wind Harmer
1.763
943851AF1-053 GEN
Solar/Wind Harmer
0.852
963791AG1-232 GEN
Solar/Wind Harmer
6.128
24386405FR-21G C
Solar/Wind Harmer
1.939
24387005FR-3G C
Solar/Wind Harmer
1.783
944221AF1-090 GEN
Solar/Wind Harmer
4.903
276763AC1-053 GEN1
Solar/Wind Harmer
1.725
276764AC1-053 GEN2
Solar/Wind Harmer
1.725
276668AB2-070 GEN1
Solar/Wind Harmer
0.965
276848AB2-070 GEN3
Solar/Wind Harmer
0.965
276849AB2-070 GEN2
Solar/Wind Harmer
0.965
946581AF1-322 GEN
Solar/Wind Harmer
4.451
24691005MDL-2G C
Solar/Wind Harmer
1.609
24803406KYGER 5HP
50/50
4.128
24803206KYGER 4HP
50/50
4.118
252516AE2-318_GEN
Solar/Wind Harmer
10.869
25196808ZIMRHP
Adder
81.158
25194608D.CRK4
Adder
1.722
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.691
946171AF1-282 GEN
Solar/Wind Harmer
10.381
25196008MFTGT1
Adder
1.383
253398AE2-221_GEN2
Solar/Wind Harmer
4.427
945681AF1-233 GEN
Solar/Wind Harmer
17.516
270273AD2-016 GEN
Solar/Wind Harmer
2.397
339221AD2-048_GEN
Solar/Wind Harmer
1.32
270222AC2-111 GEN
Solar/Wind Harmer
3.68
944031AF1-071 GEN
Solar/Wind Harmer
0.828
253370AE2-315 SEC1
Adder
1.65
253371AE2-315 SEC2
Adder
1.56
25326309TAIT D
Adder
0.871
943111AE2-339 GEN
Solar/Wind Harmer
0.702
3429421JKCT 10G
Adder
6.331
3429241JKCT 3G
Adder
8.71
942081AE2-220 GEN
Solar/Wind Harmer
4.357
270209AC1-174_GEN
Solar/Wind Harmer
2.772
270437AC2-090 C
Solar/Wind Harmer
3.802
270239V3-007_GEN1
Solar/Wind Harmer
1.172
24728605AND G2
Adder
2.416
339211AE2-254 GEN
Solar/Wind Harmer
0.948
270005AE1-210 C O1
Solar/Wind Harmer
3.403
253333AC1-068 GEN
Solar/Wind Harmer
0.646
970825AG2-519 GEN
Solar/Wind Harmer
1.289
970091AG2-072 GEN
Adder
45.609
970653AG2-424 GEN
Solar/Wind Harmer
2.807
276903AD2-071 C
Solar/Wind Harmer
5.743
945371AF1-202 GEN
Solar/Wind Harmer
3.996
270594AE1-207 GEN
Solar/Wind Harmer
7.628
270032AE2-172
Solar/Wind Harmer
2.612
958861AF2-177 GEN
Solar/Wind Harmer
6.026
270024AE2-089 GEN
Solar/Wind Harmer
2.54
965651AG1-433 GEN
Solar/Wind Harmer
2.952
339241AF1-083 GEN
Solar/Wind Harmer
0.886
972203AH1-686 GEN
Adder
1.224
964901AG1-354 GEN
Solar/Wind Harmer
7.42
963741AG1-226 GEN
Solar/Wind Harmer
21.31
24385905FR-11G C
Solar/Wind Harmer
3.747
24386605FR-22G C
Solar/Wind Harmer
1.939
965911AG1-460 GEN
Solar/Wind Harmer
0.616
276621W2-048 GEN
Solar/Wind Harmer
2.728
276686W4-005 GEN3
Solar/Wind Harmer
1.319
24791305MDL-5G
Solar/Wind Harmer
1.049
960001AF2-291 GEN
Solar/Wind Helper
1.672
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.482
24803006KYGER 3HP
50/50
4.176
24802806KYGER 2HP
50/50
4.16
24802906KYGER 2LP
50/50
2.442
25183008BIOENL
50/50
0.031
252509AD1-136 GEN
Solar/Wind Harmer
0.298
25183208HLCRTG
Solar/Wind Harmer
6.689
25194408D.CRK1
Adder
7.92
25194508D.CRK3
Adder
1.481
270269AC2-059
Solar/Wind Harmer
8.406
962581AG1-107 GEN
Solar/Wind Harmer
4.506
961491AF2-440 GEN
Solar/Wind Harmer
1.873
253415AE1-040 GEN
Solar/Wind Harmer
0.979
972043AH1-570 GEN
Solar/Wind Harmer
2.092
972045AH1-571 GEN
Solar/Wind Harmer
1.674
253370AE2-315 SEC1
Adder
1.65
971125AH1-004 GEN
Solar/Wind Harmer
3.204
970107AG2-081 GEN
Solar/Wind Harmer
2.403
25322209TAIT E
Adder
7.761
25322209TAIT E
Adder
7.587
253349AC2-067 GEN
Solar/Wind Harmer
1.601
253400AC2-068 GEN
Solar/Wind Harmer
0.644
25326109MON D
Adder
1.02
942891AE2-308 GEN
Solar/Wind Harmer
7.202
926881AC1-175 GEN
Solar/Wind Harmer
3.802
270383AD1-128 GEN
Solar/Wind Harmer
4.093
970883AG2-550 GEN
Solar/Wind Harmer
6.542
970885AG2-551 GEN
Solar/Wind Harmer
1.521
247621Y3-024
Adder
0.148
964571AG1-320 GEN
Solar/Wind Harmer
5.012
964611AG1-324 GEN
Solar/Wind Harmer
0.315
270201AC2-176 GEN
Solar/Wind Harmer
3.071
24725505WLD G2 C
Solar/Wind Harmer
2.34
24699105WLD G1 C
Solar/Wind Harmer
2.313
270031AE2-169
Solar/Wind Harmer
4.672
270599AE1-208 GEN
Solar/Wind Harmer
4.672
25326509SID D
Adder
0.727
970291AG2-192 GEN
Solar/Wind Harmer
0.706
970291AG2-192 GEN
Solar/Wind Harmer
0.227
944541AF1-119 GEN
Solar/Wind Harmer
2.261
960971AF2-388 GEN
Solar/Wind Harmer
5.903
253378AE2-206_GEN
Solar/Wind Harmer
1.848
945391AF1-204 GEN
Solar/Wind Harmer
7.122
942221AE2-234 GEN
Solar/Wind Harmer
1.774
339236AF1-050_GEN
Solar/Wind Harmer
0.907
970241AG2-163 GEN
Solar/Wind Harmer
11.839
339231AF1-038_GEN
Solar/Wind Harmer
0.852
942861AE2-305 GEN
Solar/Wind Harmer
3.571
964781AG1-341 GEN
Solar/Wind Harmer
4.844
24387305FR-4G C
Solar/Wind Harmer
2.29
966841AG1-555 GEN
Solar/Wind Harmer
1.132
276916AD2-100_GEN
Solar/Wind Harmer
9.299
276911AD2-131_GEN
Solar/Wind Harmer
1.879
276615X2-022 GEN
Solar/Wind Harmer
0.857
276838X2-022 GEN2
Solar/Wind Harmer
0.102
274880W4-005 GEN4
Solar/Wind Harmer
1.319
276174W4-005 GEN2
Solar/Wind Harmer
1.319
270180AB1-006 GEN1
Solar/Wind Harmer
3.129
24697605MDL-3G C
Solar/Wind Harmer
1.604
24755605MDL-5G
Solar/Wind Harmer
1.049
24697905MDL-4G C
Solar/Wind Harmer
0.998
270181AB1-006 GEN2
Solar/Wind Harmer
0.311
237033AB1-150 GEN
Solar/Wind Helper
0.389
24803106KYGER 3LP
50/50
2.459
24803306KYGER 4LP
50/50
2.408
971191AH1-055 GEN
Solar/Wind Harmer
73.297
252507AC2-088 GEN
Solar/Wind Harmer
2.088
252519AF1-045_GEN
Solar/Wind Harmer
3.956
25194608D.CRK4
Adder
1.722
252524AE2-267 GEN
Solar/Wind Harmer
1.648
25196608WSDLE5
Adder
8.972
253317AC1-085 GEN4
Solar/Wind Harmer
8.691
946181AF1-283 GEN
Solar/Wind Harmer
13.495
958171AF2-111 GEN
Solar/Wind Harmer
24.929
25196008MFTGT1
Adder
1.339
253394AE2-221_GEN
Solar/Wind Harmer
4.427
972167AH1-666 GEN
Solar/Wind Harmer
7.467
270367AC2-061_GEN
Solar/Wind Harmer
2.92
270186AC1-089 GEN
Solar/Wind Harmer
5.527
339243AC2-075 GEN1
Solar/Wind Harmer
0.398
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.65
253371AE2-315 SEC2
Adder
1.56
960071AF2-298 GEN
Solar/Wind Harmer
1.19
3429391JKCT 9G
Adder
6.331
970093AG2-073 GEN
Solar/Wind Harmer
3.624
24379505HDWTR1G C
Solar/Wind Harmer
5.386
270240V3-007_GEN2
Solar/Wind Harmer
4.214
24728505AND G1
Adder
2.416
970455AG2-298 GEN
Solar/Wind Harmer
2.202
270004AE1-209 GEN
Solar/Wind Harmer
3.403
253325AC1-069 GEN
Solar/Wind Harmer
0.646
946031AF1-268 GEN
Solar/Wind Harmer
5.127
970825AG2-519 GEN
Solar/Wind Harmer
3.46
962031AG1-047 GEN
Solar/Wind Harmer
1.807
957741AF2-068 GEN
Solar/Wind Harmer
8.963
970653AG2-424 GEN
Solar/Wind Harmer
0.406
270518AE2-148 GEN
Solar/Wind Harmer
6.717
339206AE1-143 GEN
Solar/Wind Harmer
1.183
965461AG1-414 GEN
Solar/Wind Harmer
1.232
970289AG2-191 GEN
Solar/Wind Harmer
0.417
247642Z2-115 C
Solar/Wind Harmer
0.034
276820AF1-078_GEN
Solar/Wind Harmer
0.821
970193AG2-126 GEN
Solar/Wind Harmer
7.665
944531AF1-118 GEN
Solar/Wind Harmer
17.273
972273AH1-721 GEN
Adder
40.144
339255AE2-071 GEN
Solar/Wind Harmer
0.539
339250AF1-203 GEN
Solar/Wind Harmer
0.277
24386205FR-12G C
Solar/Wind Harmer
1.932
942481AE2-261 GEN
Solar/Wind Harmer
13.191
957381AF2-032 GEN
Solar/Wind Harmer
0.881
276785W4-005 GEN1
Solar/Wind Harmer
1.319
971993AH1-541 GEN
Solar/Wind Harmer
4.03
24690905MDL-1G C
Solar/Wind Harmer
3.492
970781AG2-491 GEN
Solar/Wind Harmer
4.35
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
5.106
TVALTFEXP_TVA->PJM
CLTF
2.41
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.296
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.717
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.398
MECLTFEXP_MEC->PJM
CLTF
6.442
SIGELTFEXP_SIGE->PJM
CLTF
0.309
NYPJM->LTFIMP_NY
CLTF
1.475
LGEELTFEXP_LGEE->PJM
CLTF
5.052
WECLTFEXP_WEC->PJM
CLTF
1.492
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.65
AG2-052LTFEXP_AG2-052->PJM
LTF
0.097
AH1-155LTFEXP_AH1-155->PJM
LTF
0.146
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.237

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#309_05HANG R 765_B2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#309_05HANG R 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.32 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1868.38
MW Contribution:
3.23
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#309_05HANG R 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.69 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2289.82
MW Contribution:
3.39
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.465
24803506KYGER 5LP
50/50
2.408
971985AH1-537 GEN
Solar/Wind Harmer
50.362
25196408WSDLE3
Adder
9.229
253433AC1-085 GEN1
Solar/Wind Harmer
5.512
253432AC1-085 GEN2
Solar/Wind Harmer
0.277
25196108MFTGT2
Adder
1.523
25196108MFTGT2
Adder
1.414
972163AH1-664 GEN
Solar/Wind Harmer
9.198
972165AH1-665 GEN
Solar/Wind Harmer
7.358
253406AD2-031_GEN
Solar/Wind Harmer
1.174
270263AC1-001 GEN
Solar/Wind Harmer
0.941
24803406KYGER 5HP
50/50
4.127
24803206KYGER 4HP
50/50
4.117
252516AE2-318_GEN
Solar/Wind Harmer
10.863
25196808ZIMRHP
Adder
81.128
25194608D.CRK4
Adder
1.721
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.685
946171AF1-282 GEN
Solar/Wind Harmer
10.373
25196008MFTGT1
Adder
1.382
253398AE2-221_GEN2
Solar/Wind Harmer
4.423
945681AF1-233 GEN
Solar/Wind Harmer
17.553
270273AD2-016 GEN
Solar/Wind Harmer
2.392
339221AD2-048_GEN
Solar/Wind Harmer
1.323
270222AC2-111 GEN
Solar/Wind Harmer
3.676
944031AF1-071 GEN
Solar/Wind Harmer
0.827
253370AE2-315 SEC1
Adder
1.648
253371AE2-315 SEC2
Adder
1.558
943111AE2-339 GEN
Solar/Wind Harmer
0.704
25326309TAIT D
Adder
0.87
3429421JKCT 10G
Adder
6.355
3429241JKCT 3G
Adder
8.749
942081AE2-220 GEN
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
2.768
270437AC2-090 C
Solar/Wind Harmer
3.796
270239V3-007_GEN1
Solar/Wind Harmer
1.17
339211AE2-254 GEN
Solar/Wind Harmer
0.954
24728605AND G2
Adder
2.415
270005AE1-210 C O1
Solar/Wind Harmer
3.398
253333AC1-068 GEN
Solar/Wind Harmer
0.644
970825AG2-519 GEN
Solar/Wind Harmer
1.287
970091AG2-072 GEN
Adder
45.51
970653AG2-424 GEN
Solar/Wind Harmer
2.823
276903AD2-071 C
Solar/Wind Harmer
5.733
945371AF1-202 GEN
Solar/Wind Harmer
3.988
270594AE1-207 GEN
Solar/Wind Harmer
7.612
270032AE2-172
Solar/Wind Harmer
2.607
958861AF2-177 GEN
Solar/Wind Harmer
6.012
270024AE2-089 GEN
Solar/Wind Harmer
2.534
965651AG1-433 GEN
Solar/Wind Harmer
2.945
339241AF1-083 GEN
Solar/Wind Harmer
0.893
972203AH1-686 GEN
Adder
1.213
964901AG1-354 GEN
Solar/Wind Harmer
7.489
963741AG1-226 GEN
Solar/Wind Harmer
21.272
24385905FR-11G C
Solar/Wind Harmer
3.737
24386605FR-22G C
Solar/Wind Harmer
1.934
965911AG1-460 GEN
Solar/Wind Harmer
0.616
276621W2-048 GEN
Solar/Wind Harmer
2.728
276686W4-005 GEN3
Solar/Wind Harmer
1.319
24791305MDL-5G
Solar/Wind Harmer
1.046
960001AF2-291 GEN
Solar/Wind Helper
1.673
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.482
270340AC2-060 GEN
Solar/Wind Harmer
2.71
339216AC1-074 GEN
Solar/Wind Harmer
1.472
253372AE2-315 SEC3
Adder
1.558
253372AE2-315 SEC3
Adder
1.558
25306009OHH W.
Adder
2.328
3429211JKCT 2G
Adder
8.636
270356AE2-297 GEN
Solar/Wind Harmer
3.317
270432AC2-029 GEN
Solar/Wind Harmer
4.949
971029AG2-637 GEN
Solar/Wind Harmer
10.209
241972AD1-140 GEN
Solar/Wind Harmer
3.011
270543AE2-219 C
Solar/Wind Harmer
6.531
247536S-71 GEN
Solar/Wind Harmer
2.539
253338AC1-165 GEN
Solar/Wind Harmer
0.668
253343AC1-166 GEN
Solar/Wind Harmer
0.668
964611AG1-324 GEN
Solar/Wind Harmer
2.343
961761AG1-017 GEN
Solar/Wind Harmer
0.255
945581AF1-223 GEN
Solar/Wind Harmer
2.592
270444AC2-157 GEN1
Solar/Wind Harmer
3.031
270445AC2-157 GEN2
Solar/Wind Harmer
3.031
970289AG2-191 GEN
Solar/Wind Harmer
1.03
958711AF2-162 GEN
Solar/Wind Harmer
0.545
24729505KEY G4
Adder
3.273
963841AG1-237 GEN
Solar/Wind Harmer
5.045
945631AF1-228 GEN
Solar/Wind Harmer
2.136
943861AF1-054 GEN
Solar/Wind Harmer
1.755
943851AF1-053 GEN
Solar/Wind Harmer
0.848
963791AG1-232 GEN
Solar/Wind Harmer
6.108
24386405FR-21G C
Solar/Wind Harmer
1.934
24387005FR-3G C
Solar/Wind Harmer
1.779
944221AF1-090 GEN
Solar/Wind Harmer
4.906
276763AC1-053 GEN1
Solar/Wind Harmer
1.725
276764AC1-053 GEN2
Solar/Wind Harmer
1.725
276668AB2-070 GEN1
Solar/Wind Harmer
0.965
276848AB2-070 GEN3
Solar/Wind Harmer
0.965
276849AB2-070 GEN2
Solar/Wind Harmer
0.965
946581AF1-322 GEN
Solar/Wind Harmer
4.438
24691005MDL-2G C
Solar/Wind Harmer
1.604
24803006KYGER 3HP
50/50
4.175
24802806KYGER 2HP
50/50
4.16
24802906KYGER 2LP
50/50
2.441
25183008BIOENL
50/50
0.031
252509AD1-136 GEN
Solar/Wind Harmer
0.298
25183208HLCRTG
Solar/Wind Harmer
6.685
25194408D.CRK1
Adder
7.915
25194508D.CRK3
Adder
1.48
270269AC2-059
Solar/Wind Harmer
8.388
962581AG1-107 GEN
Solar/Wind Harmer
4.512
961491AF2-440 GEN
Solar/Wind Harmer
1.875
253415AE1-040 GEN
Solar/Wind Harmer
0.978
972043AH1-570 GEN
Solar/Wind Harmer
2.098
972045AH1-571 GEN
Solar/Wind Harmer
1.678
253370AE2-315 SEC1
Adder
1.648
971125AH1-004 GEN
Solar/Wind Harmer
3.214
970107AG2-081 GEN
Solar/Wind Harmer
2.411
25322209TAIT E
Adder
7.75
25322209TAIT E
Adder
7.575
253349AC2-067 GEN
Solar/Wind Harmer
1.598
253400AC2-068 GEN
Solar/Wind Harmer
0.643
25326109MON D
Adder
1.019
942891AE2-308 GEN
Solar/Wind Harmer
7.237
926881AC1-175 GEN
Solar/Wind Harmer
3.796
270383AD1-128 GEN
Solar/Wind Harmer
4.087
970883AG2-550 GEN
Solar/Wind Harmer
6.531
970885AG2-551 GEN
Solar/Wind Harmer
1.519
964571AG1-320 GEN
Solar/Wind Harmer
5.034
247621Y3-024
Adder
0.147
964611AG1-324 GEN
Solar/Wind Harmer
0.314
270201AC2-176 GEN
Solar/Wind Harmer
3.065
24725505WLD G2 C
Solar/Wind Harmer
2.336
24699105WLD G1 C
Solar/Wind Harmer
2.309
270031AE2-169
Solar/Wind Harmer
4.663
270599AE1-208 GEN
Solar/Wind Harmer
4.663
25326509SID D
Adder
0.725
970291AG2-192 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.227
944541AF1-119 GEN
Solar/Wind Harmer
2.256
960971AF2-388 GEN
Solar/Wind Harmer
5.889
253378AE2-206_GEN
Solar/Wind Harmer
1.841
945391AF1-204 GEN
Solar/Wind Harmer
7.115
942221AE2-234 GEN
Solar/Wind Harmer
1.77
339236AF1-050_GEN
Solar/Wind Harmer
0.915
339231AF1-038_GEN
Solar/Wind Harmer
0.862
970241AG2-163 GEN
Solar/Wind Harmer
11.818
964781AG1-341 GEN
Solar/Wind Harmer
4.895
942861AE2-305 GEN
Solar/Wind Harmer
3.555
24387305FR-4G C
Solar/Wind Harmer
2.284
966841AG1-555 GEN
Solar/Wind Harmer
1.129
276916AD2-100_GEN
Solar/Wind Harmer
9.304
276911AD2-131_GEN
Solar/Wind Harmer
1.88
276615X2-022 GEN
Solar/Wind Harmer
0.857
276838X2-022 GEN2
Solar/Wind Harmer
0.102
274880W4-005 GEN4
Solar/Wind Harmer
1.319
276174W4-005 GEN2
Solar/Wind Harmer
1.319
270180AB1-006 GEN1
Solar/Wind Harmer
3.12
24697605MDL-3G C
Solar/Wind Harmer
1.599
24755605MDL-5G
Solar/Wind Harmer
1.046
24697905MDL-4G C
Solar/Wind Harmer
0.995
270181AB1-006 GEN2
Solar/Wind Harmer
0.31
237033AB1-150 GEN
Solar/Wind Helper
0.389
24803106KYGER 3LP
50/50
2.459
24803306KYGER 4LP
50/50
2.408
971191AH1-055 GEN
Solar/Wind Harmer
73.271
252507AC2-088 GEN
Solar/Wind Harmer
2.087
252519AF1-045_GEN
Solar/Wind Harmer
3.954
25194608D.CRK4
Adder
1.721
252524AE2-267 GEN
Solar/Wind Harmer
1.647
25196608WSDLE5
Adder
8.965
253317AC1-085 GEN4
Solar/Wind Harmer
8.685
946181AF1-283 GEN
Solar/Wind Harmer
13.485
958171AF2-111 GEN
Solar/Wind Harmer
24.946
25196008MFTGT1
Adder
1.338
253394AE2-221_GEN
Solar/Wind Harmer
4.423
972167AH1-666 GEN
Solar/Wind Harmer
7.482
270367AC2-061_GEN
Solar/Wind Harmer
2.924
270186AC1-089 GEN
Solar/Wind Harmer
5.537
339243AC2-075 GEN1
Solar/Wind Harmer
0.399
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.648
253371AE2-315 SEC2
Adder
1.558
960071AF2-298 GEN
Solar/Wind Harmer
1.188
3429391JKCT 9G
Adder
6.355
970093AG2-073 GEN
Solar/Wind Harmer
3.645
24379505HDWTR1G C
Solar/Wind Harmer
5.379
270240V3-007_GEN2
Solar/Wind Harmer
4.208
970455AG2-298 GEN
Solar/Wind Harmer
2.212
24728505AND G1
Adder
2.415
270004AE1-209 GEN
Solar/Wind Harmer
3.398
253325AC1-069 GEN
Solar/Wind Harmer
0.644
946031AF1-268 GEN
Solar/Wind Harmer
5.118
970825AG2-519 GEN
Solar/Wind Harmer
3.455
962031AG1-047 GEN
Solar/Wind Harmer
1.803
957741AF2-068 GEN
Solar/Wind Harmer
8.946
970653AG2-424 GEN
Solar/Wind Harmer
0.408
339206AE1-143 GEN
Solar/Wind Harmer
1.192
270518AE2-148 GEN
Solar/Wind Harmer
6.693
965461AG1-414 GEN
Solar/Wind Harmer
1.229
970289AG2-191 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.034
276820AF1-078_GEN
Solar/Wind Harmer
0.818
970193AG2-126 GEN
Solar/Wind Harmer
7.659
944531AF1-118 GEN
Solar/Wind Harmer
17.224
972273AH1-721 GEN
Adder
40.637
339255AE2-071 GEN
Solar/Wind Harmer
0.544
339250AF1-203 GEN
Solar/Wind Harmer
0.28
24386205FR-12G C
Solar/Wind Harmer
1.927
942481AE2-261 GEN
Solar/Wind Harmer
13.196
957381AF2-032 GEN
Solar/Wind Harmer
0.881
276785W4-005 GEN1
Solar/Wind Harmer
1.319
971993AH1-541 GEN
Solar/Wind Harmer
4.029
24690905MDL-1G C
Solar/Wind Harmer
3.482
970781AG2-491 GEN
Solar/Wind Harmer
4.338
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
5.217
TVALTFEXP_TVA->PJM
CLTF
2.479
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.262
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.663
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.617
MECLTFEXP_MEC->PJM
CLTF
6.459
SIGELTFEXP_SIGE->PJM
CLTF
0.31
NYPJM->LTFIMP_NY
CLTF
1.479
LGEELTFEXP_LGEE->PJM
CLTF
5.06
WECLTFEXP_WEC->PJM
CLTF
1.491
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.097
AH1-155LTFEXP_AH1-155->PJM
LTF
0.145
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.694

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1560_05BAKER 765_Q2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.04 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1864.08
MW Contribution:
3.23
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.55 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2287.64
MW Contribution:
3.39
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.125
24803206KYGER 4HP
50/50
4.116
252516AE2-318_GEN
Solar/Wind Harmer
10.852
25196808ZIMRHP
Adder
81.048
25194608D.CRK4
Adder
1.719
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.675
946171AF1-282 GEN
Solar/Wind Harmer
10.363
25196008MFTGT1
Adder
1.381
253398AE2-221_GEN2
Solar/Wind Harmer
4.418
945681AF1-233 GEN
Solar/Wind Harmer
17.515
270273AD2-016 GEN
Solar/Wind Harmer
2.389
339221AD2-048_GEN
Solar/Wind Harmer
1.321
270222AC2-111 GEN
Solar/Wind Harmer
3.672
944031AF1-071 GEN
Solar/Wind Harmer
0.826
253370AE2-315 SEC1
Adder
1.646
253371AE2-315 SEC2
Adder
1.557
943111AE2-339 GEN
Solar/Wind Harmer
0.703
25326309TAIT D
Adder
0.869
3429421JKCT 10G
Adder
6.347
3429241JKCT 3G
Adder
8.736
942081AE2-220 GEN
Solar/Wind Harmer
4.346
270209AC1-174_GEN
Solar/Wind Harmer
2.766
270437AC2-090 C
Solar/Wind Harmer
3.793
270239V3-007_GEN1
Solar/Wind Harmer
1.169
339211AE2-254 GEN
Solar/Wind Harmer
0.953
24728605AND G2
Adder
2.412
270005AE1-210 C O1
Solar/Wind Harmer
3.395
253333AC1-068 GEN
Solar/Wind Harmer
0.643
970825AG2-519 GEN
Solar/Wind Harmer
1.285
970091AG2-072 GEN
Adder
45.472
970653AG2-424 GEN
Solar/Wind Harmer
2.821
276903AD2-071 C
Solar/Wind Harmer
5.727
945371AF1-202 GEN
Solar/Wind Harmer
3.984
270594AE1-207 GEN
Solar/Wind Harmer
7.604
270032AE2-172
Solar/Wind Harmer
2.604
958861AF2-177 GEN
Solar/Wind Harmer
6.007
270024AE2-089 GEN
Solar/Wind Harmer
2.531
965651AG1-433 GEN
Solar/Wind Harmer
2.942
339241AF1-083 GEN
Solar/Wind Harmer
0.892
972203AH1-686 GEN
Adder
1.212
964901AG1-354 GEN
Solar/Wind Harmer
7.485
963741AG1-226 GEN
Solar/Wind Harmer
21.254
24385905FR-11G C
Solar/Wind Harmer
3.734
24386605FR-22G C
Solar/Wind Harmer
1.932
965911AG1-460 GEN
Solar/Wind Harmer
0.615
276621W2-048 GEN
Solar/Wind Harmer
2.726
276686W4-005 GEN3
Solar/Wind Harmer
1.318
24791305MDL-5G
Solar/Wind Harmer
1.045
960001AF2-291 GEN
Solar/Wind Helper
1.677
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.483
24802606KYGER 1HP
50/50
4.203
24802706KYGER 1LP
50/50
2.464
24803506KYGER 5LP
50/50
2.407
971985AH1-537 GEN
Solar/Wind Harmer
50.336
25196408WSDLE3
Adder
9.22
253433AC1-085 GEN1
Solar/Wind Harmer
5.507
253432AC1-085 GEN2
Solar/Wind Harmer
0.277
25196108MFTGT2
Adder
1.522
25196108MFTGT2
Adder
1.413
253406AD2-031_GEN
Solar/Wind Harmer
1.172
972163AH1-664 GEN
Solar/Wind Harmer
9.178
972165AH1-665 GEN
Solar/Wind Harmer
7.342
270263AC1-001 GEN
Solar/Wind Harmer
0.94
270340AC2-060 GEN
Solar/Wind Harmer
2.706
339216AC1-074 GEN
Solar/Wind Harmer
1.47
253372AE2-315 SEC3
Adder
1.557
253372AE2-315 SEC3
Adder
1.557
25306009OHH W.
Adder
2.325
3429211JKCT 2G
Adder
8.623
270356AE2-297 GEN
Solar/Wind Harmer
3.314
270432AC2-029 GEN
Solar/Wind Harmer
4.942
971029AG2-637 GEN
Solar/Wind Harmer
10.199
241972AD1-140 GEN
Solar/Wind Harmer
3.007
270543AE2-219 C
Solar/Wind Harmer
6.525
247536S-71 GEN
Solar/Wind Harmer
2.537
253338AC1-165 GEN
Solar/Wind Harmer
0.667
253343AC1-166 GEN
Solar/Wind Harmer
0.667
964611AG1-324 GEN
Solar/Wind Harmer
2.341
961761AG1-017 GEN
Solar/Wind Harmer
0.255
945581AF1-223 GEN
Solar/Wind Harmer
2.59
270444AC2-157 GEN1
Solar/Wind Harmer
3.029
270445AC2-157 GEN2
Solar/Wind Harmer
3.029
970289AG2-191 GEN
Solar/Wind Harmer
1.029
958711AF2-162 GEN
Solar/Wind Harmer
0.545
24729505KEY G4
Adder
3.27
963841AG1-237 GEN
Solar/Wind Harmer
5.041
945631AF1-228 GEN
Solar/Wind Harmer
2.133
943861AF1-054 GEN
Solar/Wind Harmer
1.752
943851AF1-053 GEN
Solar/Wind Harmer
0.847
963791AG1-232 GEN
Solar/Wind Harmer
6.102
24386405FR-21G C
Solar/Wind Harmer
1.932
24387005FR-3G C
Solar/Wind Harmer
1.777
944221AF1-090 GEN
Solar/Wind Harmer
4.903
276763AC1-053 GEN1
Solar/Wind Harmer
1.724
276764AC1-053 GEN2
Solar/Wind Harmer
1.724
276668AB2-070 GEN1
Solar/Wind Harmer
0.964
276848AB2-070 GEN3
Solar/Wind Harmer
0.964
276849AB2-070 GEN2
Solar/Wind Harmer
0.964
946581AF1-322 GEN
Solar/Wind Harmer
4.434
24691005MDL-2G C
Solar/Wind Harmer
1.603
24803006KYGER 3HP
50/50
4.173
24802806KYGER 2HP
50/50
4.158
24802906KYGER 2LP
50/50
2.44
25183008BIOENL
50/50
0.031
252509AD1-136 GEN
Solar/Wind Harmer
0.298
25183208HLCRTG
Solar/Wind Harmer
6.678
25194408D.CRK1
Adder
7.907
25194508D.CRK3
Adder
1.478
270269AC2-059
Solar/Wind Harmer
8.376
962581AG1-107 GEN
Solar/Wind Harmer
4.499
961491AF2-440 GEN
Solar/Wind Harmer
1.87
253415AE1-040 GEN
Solar/Wind Harmer
0.977
972043AH1-570 GEN
Solar/Wind Harmer
2.094
972045AH1-571 GEN
Solar/Wind Harmer
1.675
253370AE2-315 SEC1
Adder
1.646
971125AH1-004 GEN
Solar/Wind Harmer
3.21
970107AG2-081 GEN
Solar/Wind Harmer
2.407
25322209TAIT E
Adder
7.741
25322209TAIT E
Adder
7.567
253349AC2-067 GEN
Solar/Wind Harmer
1.597
253400AC2-068 GEN
Solar/Wind Harmer
0.642
25326109MON D
Adder
1.017
942891AE2-308 GEN
Solar/Wind Harmer
7.225
926881AC1-175 GEN
Solar/Wind Harmer
3.793
270383AD1-128 GEN
Solar/Wind Harmer
4.083
970883AG2-550 GEN
Solar/Wind Harmer
6.525
970885AG2-551 GEN
Solar/Wind Harmer
1.517
964571AG1-320 GEN
Solar/Wind Harmer
5.03
247621Y3-024
Adder
0.147
964611AG1-324 GEN
Solar/Wind Harmer
0.314
270201AC2-176 GEN
Solar/Wind Harmer
3.062
24725505WLD G2 C
Solar/Wind Harmer
2.334
24699105WLD G1 C
Solar/Wind Harmer
2.307
270031AE2-169
Solar/Wind Harmer
4.658
270599AE1-208 GEN
Solar/Wind Harmer
4.658
25326509SID D
Adder
0.724
970291AG2-192 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.227
944541AF1-119 GEN
Solar/Wind Harmer
2.254
960971AF2-388 GEN
Solar/Wind Harmer
5.884
253378AE2-206_GEN
Solar/Wind Harmer
1.839
945391AF1-204 GEN
Solar/Wind Harmer
7.11
942221AE2-234 GEN
Solar/Wind Harmer
1.768
339236AF1-050_GEN
Solar/Wind Harmer
0.914
339231AF1-038_GEN
Solar/Wind Harmer
0.862
970241AG2-163 GEN
Solar/Wind Harmer
11.808
964781AG1-341 GEN
Solar/Wind Harmer
4.893
942861AE2-305 GEN
Solar/Wind Harmer
3.55
24387305FR-4G C
Solar/Wind Harmer
2.282
966841AG1-555 GEN
Solar/Wind Harmer
1.128
276916AD2-100_GEN
Solar/Wind Harmer
9.298
276911AD2-131_GEN
Solar/Wind Harmer
1.879
276615X2-022 GEN
Solar/Wind Harmer
0.856
276838X2-022 GEN2
Solar/Wind Harmer
0.102
274880W4-005 GEN4
Solar/Wind Harmer
1.318
276174W4-005 GEN2
Solar/Wind Harmer
1.318
270180AB1-006 GEN1
Solar/Wind Harmer
3.117
24697605MDL-3G C
Solar/Wind Harmer
1.598
24755605MDL-5G
Solar/Wind Harmer
1.045
24697905MDL-4G C
Solar/Wind Harmer
0.994
270181AB1-006 GEN2
Solar/Wind Harmer
0.31
237033AB1-150 GEN
Solar/Wind Helper
0.389
24803106KYGER 3LP
50/50
2.458
24803306KYGER 4LP
50/50
2.407
971191AH1-055 GEN
Solar/Wind Harmer
73.235
252507AC2-088 GEN
Solar/Wind Harmer
2.085
252519AF1-045_GEN
Solar/Wind Harmer
3.95
25194608D.CRK4
Adder
1.719
252524AE2-267 GEN
Solar/Wind Harmer
1.646
25196608WSDLE5
Adder
8.957
253317AC1-085 GEN4
Solar/Wind Harmer
8.675
946181AF1-283 GEN
Solar/Wind Harmer
13.471
958171AF2-111 GEN
Solar/Wind Harmer
24.917
25196008MFTGT1
Adder
1.337
253394AE2-221_GEN
Solar/Wind Harmer
4.418
972167AH1-666 GEN
Solar/Wind Harmer
7.466
270367AC2-061_GEN
Solar/Wind Harmer
2.916
270186AC1-089 GEN
Solar/Wind Harmer
5.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.398
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.646
253371AE2-315 SEC2
Adder
1.557
960071AF2-298 GEN
Solar/Wind Harmer
1.187
3429391JKCT 9G
Adder
6.347
970093AG2-073 GEN
Solar/Wind Harmer
3.638
24379505HDWTR1G C
Solar/Wind Harmer
5.374
270240V3-007_GEN2
Solar/Wind Harmer
4.204
970455AG2-298 GEN
Solar/Wind Harmer
2.21
24728505AND G1
Adder
2.412
270004AE1-209 GEN
Solar/Wind Harmer
3.395
253325AC1-069 GEN
Solar/Wind Harmer
0.643
946031AF1-268 GEN
Solar/Wind Harmer
5.113
970825AG2-519 GEN
Solar/Wind Harmer
3.451
962031AG1-047 GEN
Solar/Wind Harmer
1.802
957741AF2-068 GEN
Solar/Wind Harmer
8.938
970653AG2-424 GEN
Solar/Wind Harmer
0.408
339206AE1-143 GEN
Solar/Wind Harmer
1.191
270518AE2-148 GEN
Solar/Wind Harmer
6.685
965461AG1-414 GEN
Solar/Wind Harmer
1.228
970289AG2-191 GEN
Solar/Wind Harmer
0.415
247642Z2-115 C
Solar/Wind Harmer
0.034
276820AF1-078_GEN
Solar/Wind Harmer
0.817
970193AG2-126 GEN
Solar/Wind Harmer
7.653
944531AF1-118 GEN
Solar/Wind Harmer
17.208
972273AH1-721 GEN
Adder
40.6
339255AE2-071 GEN
Solar/Wind Harmer
0.544
339250AF1-203 GEN
Solar/Wind Harmer
0.28
24386205FR-12G C
Solar/Wind Harmer
1.925
942481AE2-261 GEN
Solar/Wind Harmer
13.188
957381AF2-032 GEN
Solar/Wind Harmer
0.881
276785W4-005 GEN1
Solar/Wind Harmer
1.318
971993AH1-541 GEN
Solar/Wind Harmer
4.027
24690905MDL-1G C
Solar/Wind Harmer
3.479
970781AG2-491 GEN
Solar/Wind Harmer
4.334
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
5.225
TVALTFEXP_TVA->PJM
CLTF
2.484
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.256
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.621
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.627
MECLTFEXP_MEC->PJM
CLTF
6.456
SIGELTFEXP_SIGE->PJM
CLTF
0.31
NYPJM->LTFIMP_NY
CLTF
1.475
LGEELTFEXP_LGEE->PJM
CLTF
5.055
WECLTFEXP_WEC->PJM
CLTF
1.49
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.592
AG2-052LTFEXP_AG2-052->PJM
LTF
0.097
AH1-155LTFEXP_AH1-155->PJM
LTF
0.145
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.702

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#6156_05MARQUI 765_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6156_05MARQUI 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.75 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1859.53
MW Contribution:
3.73
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.511
24802706KYGER 1LP
50/50
2.645
24803506KYGER 5LP
50/50
2.583
971985AH1-537 GEN
Solar/Wind Harmer
56.568
253433AC1-085 GEN1
Solar/Wind Harmer
7.375
253432AC1-085 GEN2
Solar/Wind Harmer
0.371
270263AC1-001 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
11.529
270340AC2-060 GEN
Solar/Wind Harmer
3.869
253406AD2-031_GEN
Solar/Wind Harmer
1.584
25196108MFTGT2
Adder
1.862
25196108MFTGT2
Adder
1.729
972163AH1-664 GEN
Solar/Wind Harmer
11.991
972165AH1-665 GEN
Solar/Wind Harmer
9.592
339216AC1-074 GEN
Solar/Wind Harmer
1.851
270432AC2-029 GEN
Solar/Wind Harmer
7.618
253372AE2-315 SEC3
Adder
2.021
253372AE2-315 SEC3
Adder
2.021
24803006KYGER 3HP
50/50
4.479
24802806KYGER 2HP
50/50
4.462
24802906KYGER 2LP
50/50
2.619
25183008BIOENL
50/50
0.04
252509AD1-136 GEN
Solar/Wind Harmer
0.379
25183208HLCRTG
Solar/Wind Harmer
8.672
270269AC2-059
Solar/Wind Harmer
12.691
25194408D.CRK1
Adder
9.908
25194508D.CRK3
Adder
1.852
253415AE1-040 GEN
Solar/Wind Harmer
1.385
962581AG1-107 GEN
Solar/Wind Harmer
6.11
961491AF2-440 GEN
Solar/Wind Harmer
2.54
253370AE2-315 SEC1
Adder
2.137
972043AH1-570 GEN
Solar/Wind Harmer
2.652
972045AH1-571 GEN
Solar/Wind Harmer
2.122
25322209TAIT E
Adder
10.038
25322209TAIT E
Adder
9.812
253349AC2-067 GEN
Solar/Wind Harmer
2.05
253400AC2-068 GEN
Solar/Wind Harmer
0.824
971125AH1-004 GEN
Solar/Wind Harmer
4.03
970107AG2-081 GEN
Solar/Wind Harmer
3.023
25326109MON D
Adder
1.324
942891AE2-308 GEN
Solar/Wind Harmer
9.002
926881AC1-175 GEN
Solar/Wind Harmer
4.513
270383AD1-128 GEN
Solar/Wind Harmer
4.887
970883AG2-550 GEN
Solar/Wind Harmer
7.87
970885AG2-551 GEN
Solar/Wind Harmer
1.83
247621Y3-024
Adder
0.176
25326509SID D
Adder
0.951
964611AG1-324 GEN
Solar/Wind Harmer
0.374
270201AC2-176 GEN
Solar/Wind Harmer
3.648
964571AG1-320 GEN
Solar/Wind Harmer
5.767
971073AG2-665 GEN
Solar/Wind Harmer
5.548
970879AG2-548 GEN
Solar/Wind Harmer
0.806
24725505WLD G2 C
Solar/Wind Harmer
2.701
24699105WLD G1 C
Solar/Wind Harmer
2.67
253378AE2-206_GEN
Solar/Wind Harmer
2.436
270031AE2-169
Solar/Wind Harmer
5.48
270599AE1-208 GEN
Solar/Wind Harmer
5.48
944541AF1-119 GEN
Solar/Wind Harmer
2.663
960971AF2-388 GEN
Solar/Wind Harmer
6.95
942861AE2-305 GEN
Solar/Wind Harmer
4.917
970291AG2-192 GEN
Solar/Wind Harmer
0.805
970291AG2-192 GEN
Solar/Wind Harmer
0.259
942221AE2-234 GEN
Solar/Wind Harmer
2.089
339236AF1-050_GEN
Solar/Wind Harmer
1.055
339231AF1-038_GEN
Solar/Wind Harmer
1.008
927014AC1-188 GEN
Solar/Wind Harmer
0.859
945391AF1-204 GEN
Solar/Wind Harmer
7.563
964781AG1-341 GEN
Solar/Wind Harmer
5.576
253383AE2-342_GEN
Solar/Wind Harmer
0.458
970241AG2-163 GEN
Solar/Wind Harmer
12.517
971485AH1-239 GEN
Solar/Wind Harmer
3.96
966021AG1-471 GEN
Solar/Wind Harmer
2.631
24387305FR-4G C
Solar/Wind Harmer
2.413
966841AG1-555 GEN
Solar/Wind Harmer
1.193
276916AD2-100_GEN
Solar/Wind Harmer
9.913
276911AD2-131_GEN
Solar/Wind Harmer
2.003
276615X2-022 GEN
Solar/Wind Harmer
0.916
276838X2-022 GEN2
Solar/Wind Harmer
0.109
274880W4-005 GEN4
Solar/Wind Harmer
1.412
276174W4-005 GEN2
Solar/Wind Harmer
1.412
270180AB1-006 GEN1
Solar/Wind Harmer
3.305
24697605MDL-3G C
Solar/Wind Harmer
1.694
24755605MDL-5G
Solar/Wind Harmer
1.108
24697905MDL-4G C
Solar/Wind Harmer
1.055
270181AB1-006 GEN2
Solar/Wind Harmer
0.329
237033AB1-150 GEN
Solar/Wind Helper
0.424
25306009OHH W.
Adder
3.008
3429211JKCT 2G
Adder
10.797
241972AD1-140 GEN
Solar/Wind Harmer
3.986
253338AC1-165 GEN
Solar/Wind Harmer
0.939
253343AC1-166 GEN
Solar/Wind Harmer
0.939
270356AE2-297 GEN
Solar/Wind Harmer
3.929
971029AG2-637 GEN
Solar/Wind Harmer
12.368
270543AE2-219 C
Solar/Wind Harmer
7.87
247536S-71 GEN
Solar/Wind Harmer
3.045
964611AG1-324 GEN
Solar/Wind Harmer
2.784
961761AG1-017 GEN
Solar/Wind Harmer
0.304
945581AF1-223 GEN
Solar/Wind Harmer
3.06
945631AF1-228 GEN
Solar/Wind Harmer
3.043
958711AF2-162 GEN
Solar/Wind Harmer
0.643
943861AF1-054 GEN
Solar/Wind Harmer
2.427
943851AF1-053 GEN
Solar/Wind Harmer
1.173
970289AG2-191 GEN
Solar/Wind Harmer
1.176
24729505KEY G4
Adder
3.861
270291AC1-194 GEN
Solar/Wind Harmer
2.916
241955AC1-078 GEN
Solar/Wind Harmer
4.064
241973AD2-163_GEN1
Solar/Wind Harmer
1.073
241974AD2-163_GEN2
Solar/Wind Harmer
1.073
963791AG1-232 GEN
Solar/Wind Harmer
7.287
270444AC2-157 GEN1
Solar/Wind Harmer
2.98
270445AC2-157 GEN2
Solar/Wind Harmer
2.98
963841AG1-237 GEN
Solar/Wind Harmer
5.337
270071AF1-092 GEN
Solar/Wind Harmer
7.165
944221AF1-090 GEN
Solar/Wind Harmer
5.212
24386405FR-21G C
Solar/Wind Harmer
2.043
24387005FR-3G C
Solar/Wind Harmer
1.879
276763AC1-053 GEN1
Solar/Wind Harmer
1.847
276764AC1-053 GEN2
Solar/Wind Harmer
1.847
276668AB2-070 GEN1
Solar/Wind Harmer
1.034
276848AB2-070 GEN3
Solar/Wind Harmer
1.034
276849AB2-070 GEN2
Solar/Wind Harmer
1.034
946581AF1-322 GEN
Solar/Wind Harmer
4.702
24691005MDL-2G C
Solar/Wind Harmer
1.699
24803106KYGER 3LP
50/50
2.637
24803306KYGER 4LP
50/50
2.583
971191AH1-055 GEN
Solar/Wind Harmer
85.195
252507AC2-088 GEN
Solar/Wind Harmer
2.655
253317AC1-085 GEN4
Solar/Wind Harmer
11.619
946181AF1-283 GEN
Solar/Wind Harmer
18.042
252519AF1-045_GEN
Solar/Wind Harmer
5.038
25194608D.CRK4
Adder
2.154
252524AE2-267 GEN
Solar/Wind Harmer
2.058
25196608WSDLE5
Adder
11.2
958171AF2-111 GEN
Solar/Wind Harmer
32.628
253394AE2-221_GEN
Solar/Wind Harmer
5.885
270367AC2-061_GEN
Solar/Wind Harmer
3.949
270186AC1-089 GEN
Solar/Wind Harmer
7.462
972167AH1-666 GEN
Solar/Wind Harmer
9.768
25196008MFTGT1
Adder
1.636
339243AC2-075 GEN1
Solar/Wind Harmer
0.501
253303V4-073 C
Solar/Wind Harmer
0.124
253370AE2-315 SEC1
Adder
2.137
253371AE2-315 SEC2
Adder
2.021
960071AF2-298 GEN
Solar/Wind Harmer
1.535
3429391JKCT 9G
Adder
7.969
253325AC1-069 GEN
Solar/Wind Harmer
0.905
970093AG2-073 GEN
Solar/Wind Harmer
4.511
24379505HDWTR1G C
Solar/Wind Harmer
6.394
270240V3-007_GEN2
Solar/Wind Harmer
5.003
270518AE2-148 GEN
Solar/Wind Harmer
9.208
970455AG2-298 GEN
Solar/Wind Harmer
2.574
270004AE1-209 GEN
Solar/Wind Harmer
4.013
946031AF1-268 GEN
Solar/Wind Harmer
6.057
970825AG2-519 GEN
Solar/Wind Harmer
4.074
24728505AND G1
Adder
2.773
962031AG1-047 GEN
Solar/Wind Harmer
2.146
957741AF2-068 GEN
Solar/Wind Harmer
10.645
970879AG2-548 GEN
Solar/Wind Harmer
5.548
276820AF1-078_GEN
Solar/Wind Harmer
1.082
970653AG2-424 GEN
Solar/Wind Harmer
0.471
339206AE1-143 GEN
Solar/Wind Harmer
1.398
965461AG1-414 GEN
Solar/Wind Harmer
1.404
970289AG2-191 GEN
Solar/Wind Harmer
0.475
247642Z2-115 C
Solar/Wind Harmer
0.038
942051AE2-217 GEN
Solar/Wind Harmer
10.648
960801AF2-371 GEN
Solar/Wind Harmer
1.494
964871AG1-351 GEN
Solar/Wind Harmer
1.032
944531AF1-118 GEN
Solar/Wind Harmer
20.315
972273AH1-721 GEN
Adder
48.249
957541AF2-048 GEN
Solar/Wind Harmer
0.859
970193AG2-126 GEN
Solar/Wind Harmer
8.141
339255AE2-071 GEN
Solar/Wind Harmer
0.622
339250AF1-203 GEN
Solar/Wind Harmer
0.32
24386205FR-12G C
Solar/Wind Harmer
2.036
942481AE2-261 GEN
Solar/Wind Harmer
14.072
957381AF2-032 GEN
Solar/Wind Harmer
0.94
276785W4-005 GEN1
Solar/Wind Harmer
1.412
971993AH1-541 GEN
Solar/Wind Harmer
4.315
24690905MDL-1G C
Solar/Wind Harmer
3.689
270330AC1-082 GEN2
Solar/Wind Helper
0.169
270329AC1-082 GEN1
Solar/Wind Helper
0.169
970781AG2-491 GEN
Solar/Wind Harmer
2.082
24803406KYGER 5HP
50/50
4.427
24803206KYGER 4HP
50/50
4.417
253316AC1-085 GEN3
Solar/Wind Harmer
11.619
946171AF1-282 GEN
Solar/Wind Harmer
13.878
252516AE2-318_GEN
Solar/Wind Harmer
13.842
270273AD2-016 GEN
Solar/Wind Harmer
3.619
25196808ZIMRHP
Adder
103.16
252510AF1-249 C
Solar/Wind Harmer
0.548
25194608D.CRK4
Adder
2.154
253398AE2-221_GEN2
Solar/Wind Harmer
5.885
945681AF1-233 GEN
Solar/Wind Harmer
22.912
25196008MFTGT1
Adder
1.689
339221AD2-048_GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.137
253371AE2-315 SEC2
Adder
2.021
25326309TAIT D
Adder
1.127
270222AC2-111 GEN
Solar/Wind Harmer
4.52
944031AF1-071 GEN
Solar/Wind Harmer
1.017
943111AE2-339 GEN
Solar/Wind Harmer
0.883
3429421JKCT 10G
Adder
7.969
3429241JKCT 3G
Adder
10.939
253333AC1-068 GEN
Solar/Wind Harmer
0.905
942081AE2-220 GEN
Solar/Wind Harmer
5.172
270209AC1-174_GEN
Solar/Wind Harmer
3.291
270437AC2-090 C
Solar/Wind Harmer
4.513
270239V3-007_GEN1
Solar/Wind Harmer
1.391
339211AE2-254 GEN
Solar/Wind Harmer
1.15
270005AE1-210 C O1
Solar/Wind Harmer
4.013
970825AG2-519 GEN
Solar/Wind Harmer
1.517
24728605AND G2
Adder
2.773
971073AG2-665 GEN
Solar/Wind Harmer
0.806
970653AG2-424 GEN
Solar/Wind Harmer
3.256
945371AF1-202 GEN
Solar/Wind Harmer
4.707
276903AD2-071 C
Solar/Wind Harmer
6.601
958861AF2-177 GEN
Solar/Wind Harmer
7.096
270594AE1-207 GEN
Solar/Wind Harmer
8.773
270032AE2-172
Solar/Wind Harmer
3.005
270024AE2-089 GEN
Solar/Wind Harmer
3.017
965651AG1-433 GEN
Solar/Wind Harmer
3.475
339241AF1-083 GEN
Solar/Wind Harmer
1.04
964901AG1-354 GEN
Solar/Wind Harmer
8.626
970091AG2-072 GEN
Adder
38.834
963741AG1-226 GEN
Solar/Wind Harmer
22.53
24385905FR-11G C
Solar/Wind Harmer
3.949
24386605FR-22G C
Solar/Wind Harmer
2.043
965911AG1-460 GEN
Solar/Wind Harmer
0.657
276621W2-048 GEN
Solar/Wind Harmer
2.918
276686W4-005 GEN3
Solar/Wind Harmer
1.412
24791305MDL-5G
Solar/Wind Harmer
1.108
960001AF2-291 GEN
Solar/Wind Helper
1.492
270331AC1-082 GEN3
Solar/Wind Helper
0.168
235780M24_1
Solar/Wind Helper
0.525
LAGNLTFEXP_LAGN->PJM
CLTF
5.54
TVALTFEXP_TVA->PJM
CLTF
2.651
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.383
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.406
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.825
MECLTFEXP_MEC->PJM
CLTF
6.978
SIGELTFEXP_SIGE->PJM
CLTF
0.344
NYPJM->LTFIMP_NY
CLTF
1.62
LGEELTFEXP_LGEE->PJM
CLTF
5.749
WECLTFEXP_WEC->PJM
CLTF
1.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.817
AG2-052LTFEXP_AG2-052->PJM
LTF
0.106
AH1-155LTFEXP_AH1-155->PJM
LTF
0.159
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.569

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.24 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1666.97
MW Contribution:
3.1
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.1 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2342.28
MW Contribution:
3.38
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.162
24802706KYGER 1LP
50/50
2.441
24803506KYGER 5LP
50/50
2.384
971985AH1-537 GEN
Solar/Wind Harmer
49.14
25196408WSDLE3
Adder
8.658
253433AC1-085 GEN1
Solar/Wind Harmer
5.134
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
8.69
972165AH1-665 GEN
Solar/Wind Harmer
6.952
253406AD2-031_GEN
Solar/Wind Harmer
1.088
339216AC1-074 GEN
Solar/Wind Harmer
1.391
270340AC2-060 GEN
Solar/Wind Harmer
2.489
270263AC1-001 GEN
Solar/Wind Harmer
0.854
253372AE2-315 SEC3
Adder
1.443
253372AE2-315 SEC3
Adder
1.443
25306009OHH W.
Adder
2.158
3429211JKCT 2G
Adder
8.249
270356AE2-297 GEN
Solar/Wind Harmer
3.158
971029AG2-637 GEN
Solar/Wind Harmer
9.766
270432AC2-029 GEN
Solar/Wind Harmer
4.409
24803006KYGER 3HP
50/50
4.133
24802806KYGER 2HP
50/50
4.118
24802906KYGER 2LP
50/50
2.417
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.28
25183208HLCRTG
Solar/Wind Harmer
6.261
25194408D.CRK1
Adder
7.428
25194508D.CRK3
Adder
1.389
962581AG1-107 GEN
Solar/Wind Harmer
4.213
961491AF2-440 GEN
Solar/Wind Harmer
1.751
270269AC2-059
Solar/Wind Harmer
7.604
253415AE1-040 GEN
Solar/Wind Harmer
0.897
972043AH1-570 GEN
Solar/Wind Harmer
1.988
972045AH1-571 GEN
Solar/Wind Harmer
1.59
971125AH1-004 GEN
Solar/Wind Harmer
3.051
24803106KYGER 3LP
50/50
2.434
24803306KYGER 4LP
50/50
2.384
971191AH1-055 GEN
Solar/Wind Harmer
71.644
252507AC2-088 GEN
Solar/Wind Harmer
1.961
252519AF1-045_GEN
Solar/Wind Harmer
3.707
25194608D.CRK4
Adder
1.615
252524AE2-267 GEN
Solar/Wind Harmer
1.545
25196608WSDLE5
Adder
8.411
253317AC1-085 GEN4
Solar/Wind Harmer
8.089
946181AF1-283 GEN
Solar/Wind Harmer
12.561
958171AF2-111 GEN
Solar/Wind Harmer
23.452
25196008MFTGT1
Adder
1.257
253394AE2-221_GEN
Solar/Wind Harmer
4.109
972167AH1-666 GEN
Solar/Wind Harmer
7.062
270367AC2-061_GEN
Solar/Wind Harmer
2.733
270543AE2-219 C
Solar/Wind Harmer
6.274
241972AD1-140 GEN
Solar/Wind Harmer
2.733
247536S-71 GEN
Solar/Wind Harmer
2.45
964611AG1-324 GEN
Solar/Wind Harmer
2.272
961761AG1-017 GEN
Solar/Wind Harmer
0.248
945581AF1-223 GEN
Solar/Wind Harmer
2.557
253338AC1-165 GEN
Solar/Wind Harmer
0.595
253343AC1-166 GEN
Solar/Wind Harmer
0.595
958711AF2-162 GEN
Solar/Wind Harmer
0.544
970289AG2-191 GEN
Solar/Wind Harmer
0.989
24729505KEY G4
Adder
3.305
270444AC2-157 GEN1
Solar/Wind Harmer
2.758
270445AC2-157 GEN2
Solar/Wind Harmer
2.758
963791AG1-232 GEN
Solar/Wind Harmer
6.09
963841AG1-237 GEN
Solar/Wind Harmer
4.776
944221AF1-090 GEN
Solar/Wind Harmer
4.74
24803406KYGER 5HP
50/50
4.085
24803206KYGER 4HP
50/50
4.076
252516AE2-318_GEN
Solar/Wind Harmer
10.186
25196808ZIMRHP
Adder
76.155
25194608D.CRK4
Adder
1.615
252510AF1-249 C
Solar/Wind Harmer
0.409
253316AC1-085 GEN3
Solar/Wind Harmer
8.089
946171AF1-282 GEN
Solar/Wind Harmer
9.662
25196008MFTGT1
Adder
1.298
253398AE2-221_GEN2
Solar/Wind Harmer
4.109
945681AF1-233 GEN
Solar/Wind Harmer
16.573
270273AD2-016 GEN
Solar/Wind Harmer
2.168
339221AD2-048_GEN
Solar/Wind Harmer
1.251
270222AC2-111 GEN
Solar/Wind Harmer
3.47
944031AF1-071 GEN
Solar/Wind Harmer
0.781
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.443
943111AE2-339 GEN
Solar/Wind Harmer
0.669
25326309TAIT D
Adder
0.804
3429421JKCT 10G
Adder
6.056
3429241JKCT 3G
Adder
8.358
942081AE2-220 GEN
Solar/Wind Harmer
4.197
270209AC1-174_GEN
Solar/Wind Harmer
2.67
270437AC2-090 C
Solar/Wind Harmer
3.662
270239V3-007_GEN1
Solar/Wind Harmer
1.129
339211AE2-254 GEN
Solar/Wind Harmer
0.919
270005AE1-210 C O1
Solar/Wind Harmer
3.304
24728605AND G2
Adder
2.296
970825AG2-519 GEN
Solar/Wind Harmer
1.247
945371AF1-202 GEN
Solar/Wind Harmer
3.934
970653AG2-424 GEN
Solar/Wind Harmer
2.709
276903AD2-071 C
Solar/Wind Harmer
5.501
253333AC1-068 GEN
Solar/Wind Harmer
0.574
958861AF2-177 GEN
Solar/Wind Harmer
5.973
270594AE1-207 GEN
Solar/Wind Harmer
7.326
270032AE2-172
Solar/Wind Harmer
2.509
965651AG1-433 GEN
Solar/Wind Harmer
2.937
270024AE2-089 GEN
Solar/Wind Harmer
2.481
339241AF1-083 GEN
Solar/Wind Harmer
0.868
970091AG2-072 GEN
Adder
38.983
964901AG1-354 GEN
Solar/Wind Harmer
7.327
963741AG1-226 GEN
Solar/Wind Harmer
20.113
960001AF2-291 GEN
Solar/Wind Helper
1.7
270331AC1-082 GEN3
Solar/Wind Helper
0.189
235780M24_1
Solar/Wind Helper
0.465
970107AG2-081 GEN
Solar/Wind Harmer
2.288
253370AE2-315 SEC1
Adder
1.526
25322209TAIT E
Adder
7.164
25322209TAIT E
Adder
7.003
253349AC2-067 GEN
Solar/Wind Harmer
1.485
253400AC2-068 GEN
Solar/Wind Harmer
0.597
25326109MON D
Adder
0.938
942891AE2-308 GEN
Solar/Wind Harmer
6.919
926881AC1-175 GEN
Solar/Wind Harmer
3.662
270383AD1-128 GEN
Solar/Wind Harmer
3.929
970883AG2-550 GEN
Solar/Wind Harmer
6.274
970885AG2-551 GEN
Solar/Wind Harmer
1.459
247621Y3-024
Adder
0.142
964571AG1-320 GEN
Solar/Wind Harmer
4.793
964611AG1-324 GEN
Solar/Wind Harmer
0.305
270201AC2-176 GEN
Solar/Wind Harmer
2.974
24725505WLD G2 C
Solar/Wind Harmer
2.243
24699105WLD G1 C
Solar/Wind Harmer
2.217
270031AE2-169
Solar/Wind Harmer
4.555
270599AE1-208 GEN
Solar/Wind Harmer
4.555
944541AF1-119 GEN
Solar/Wind Harmer
2.25
960971AF2-388 GEN
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
0.676
970291AG2-192 GEN
Solar/Wind Harmer
0.218
942221AE2-234 GEN
Solar/Wind Harmer
1.752
25326509SID D
Adder
0.658
339236AF1-050_GEN
Solar/Wind Harmer
0.894
945391AF1-204 GEN
Solar/Wind Harmer
6.702
339231AF1-038_GEN
Solar/Wind Harmer
0.854
253378AE2-206_GEN
Solar/Wind Harmer
1.655
964781AG1-341 GEN
Solar/Wind Harmer
4.826
970241AG2-163 GEN
Solar/Wind Harmer
11.174
237033AB1-150 GEN
Solar/Wind Helper
0.375
270186AC1-089 GEN
Solar/Wind Harmer
5.183
339243AC2-075 GEN1
Solar/Wind Harmer
0.377
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.443
3429391JKCT 9G
Adder
6.056
960071AF2-298 GEN
Solar/Wind Harmer
1.1
970093AG2-073 GEN
Solar/Wind Harmer
3.499
24379505HDWTR1G C
Solar/Wind Harmer
5.189
270240V3-007_GEN2
Solar/Wind Harmer
4.06
270004AE1-209 GEN
Solar/Wind Harmer
3.304
970455AG2-298 GEN
Solar/Wind Harmer
2.109
24728505AND G1
Adder
2.296
946031AF1-268 GEN
Solar/Wind Harmer
4.96
970825AG2-519 GEN
Solar/Wind Harmer
3.347
962031AG1-047 GEN
Solar/Wind Harmer
1.75
957741AF2-068 GEN
Solar/Wind Harmer
8.68
970653AG2-424 GEN
Solar/Wind Harmer
0.392
253325AC1-069 GEN
Solar/Wind Harmer
0.574
339206AE1-143 GEN
Solar/Wind Harmer
1.156
965461AG1-414 GEN
Solar/Wind Harmer
1.18
970289AG2-191 GEN
Solar/Wind Harmer
0.399
247642Z2-115 C
Solar/Wind Harmer
0.032
944531AF1-118 GEN
Solar/Wind Harmer
17.479
270518AE2-148 GEN
Solar/Wind Harmer
5.914
972273AH1-721 GEN
Adder
40.32
970193AG2-126 GEN
Solar/Wind Harmer
7.214
276820AF1-078_GEN
Solar/Wind Harmer
0.735
339255AE2-071 GEN
Solar/Wind Harmer
0.537
339250AF1-203 GEN
Solar/Wind Harmer
0.276
270330AC1-082 GEN2
Solar/Wind Helper
0.19
270329AC1-082 GEN1
Solar/Wind Helper
0.19
LAGNLTFEXP_LAGN->PJM
CLTF
5.572
TVALTFEXP_TVA->PJM
CLTF
2.7
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.049
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.972
MECLTFEXP_MEC->PJM
CLTF
6.466
SIGELTFEXP_SIGE->PJM
CLTF
0.293
NYPJM->LTFIMP_NY
CLTF
1.435
LGEELTFEXP_LGEE->PJM
CLTF
4.729
WECLTFEXP_WEC->PJM
CLTF
1.499
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.271
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.144
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.696

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1280.85
MW Contribution:
2.23
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.63 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1362.91
MW Contribution:
2.34
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.142
24802806KYGER 2HP
50/50
4.127
24802906KYGER 2LP
50/50
2.422
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.038
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.38
25194508D.CRK3
Adder
1.38
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.433
972045AH1-571 GEN
Solar/Wind Harmer
1.148
253370AE2-315 SEC1
Adder
1.526
971125AH1-004 GEN
Solar/Wind Harmer
2.112
970107AG2-081 GEN
Solar/Wind Harmer
1.584
25322209TAIT E
Adder
7.169
25322209TAIT E
Adder
7.008
25326109MON D
Adder
0.942
942891AE2-308 GEN
Solar/Wind Harmer
4.783
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.132
970885AG2-551 GEN
Solar/Wind Harmer
1.377
964571AG1-320 GEN
Solar/Wind Harmer
3.631
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.967
270599AE1-208 GEN
Solar/Wind Harmer
3.278
25326509SID D
Adder
0.66
971613AH1-306 GEN
Solar/Wind Harmer
1.669
944541AF1-119 GEN
Solar/Wind Harmer
0.224
960971AF2-388 GEN
Solar/Wind Harmer
1.97
970291AG2-192 GEN
Solar/Wind Harmer
0.435
970291AG2-192 GEN
Solar/Wind Harmer
0.201
971587AH1-292 GEN
Solar/Wind Harmer
2.382
970329AG2-216 GEN
Solar/Wind Harmer
1.4
942221AE2-234 GEN
Solar/Wind Harmer
1.259
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.389
971191AH1-055 GEN
Solar/Wind Harmer
68.884
252507AC2-088 GEN
Solar/Wind Harmer
0.343
252519AF1-045_GEN
Solar/Wind Harmer
3.694
25194608D.CRK4
Adder
1.604
25196608WSDLE5
Adder
8.356
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.789
958171AF2-111 GEN
Solar/Wind Harmer
16.332
25196008MFTGT1
Adder
1.242
253394AE2-221_GEN
Solar/Wind Harmer
0.001
972167AH1-666 GEN
Solar/Wind Harmer
4.919
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
970191AG2-125 GEN
Solar/Wind Harmer
1.303
3429391JKCT 9G
Adder
6.006
970093AG2-073 GEN
Solar/Wind Harmer
3.867
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970455AG2-298 GEN
Solar/Wind Harmer
1.6
24728505AND G1
Adder
2.173
253325AC1-069 GEN
Solar/Wind Harmer
0.004
270004AE1-209 GEN
Solar/Wind Harmer
0.848
946031AF1-268 GEN
Solar/Wind Harmer
3.69
970825AG2-519 GEN
Solar/Wind Harmer
2.902
970653AG2-424 GEN
Solar/Wind Harmer
0.382
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.618
270518AE2-148 GEN
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
0.368
972273AH1-721 GEN
Adder
39.663
247642Z2-115 C
Solar/Wind Harmer
0.001
970193AG2-126 GEN
Solar/Wind Harmer
4.669
944531AF1-118 GEN
Solar/Wind Harmer
13.648
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24803406KYGER 5HP
50/50
4.094
24803206KYGER 4HP
50/50
4.085
252516AE2-318_GEN
Solar/Wind Harmer
7.932
25196808ZIMRHP
Adder
75.812
25194608D.CRK4
Adder
1.604
252510AF1-249 C
Solar/Wind Harmer
0.051
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.761
25196008MFTGT1
Adder
1.283
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
11.543
270273AD2-016 GEN
Solar/Wind Harmer
0.596
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
25326309TAIT D
Adder
0.805
3429421JKCT 10G
Adder
6.006
3429241JKCT 3G
Adder
8.287
970773AG2-487 GEN
Solar/Wind Harmer
0.807
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.158
24728605AND G2
Adder
2.173
253333AC1-068 GEN
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
0.848
970825AG2-519 GEN
Solar/Wind Harmer
1.367
970653AG2-424 GEN
Solar/Wind Harmer
1.845
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
3.979
270594AE1-207 GEN
Solar/Wind Harmer
3.893
270032AE2-172
Solar/Wind Harmer
2.318
958861AF2-177 GEN
Solar/Wind Harmer
1.487
970091AG2-072 GEN
Adder
37.335
270024AE2-089 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.985
964901AG1-354 GEN
Solar/Wind Harmer
4.987
960001AF2-291 GEN
Solar/Wind Helper
1.682
270331AC1-082 GEN3
Solar/Wind Helper
0.187
945391AF1-204 GEN
Solar/Wind Harmer
3.307
964781AG1-341 GEN
Solar/Wind Harmer
3.276
24802606KYGER 1HP
50/50
4.172
24802706KYGER 1LP
50/50
2.446
24803506KYGER 5LP
50/50
2.389
971985AH1-537 GEN
Solar/Wind Harmer
5.716
25196408WSDLE3
Adder
8.602
25196108MFTGT2
Adder
1.414
25196108MFTGT2
Adder
1.313
972163AH1-664 GEN
Solar/Wind Harmer
6.737
972165AH1-665 GEN
Solar/Wind Harmer
5.396
253406AD2-031_GEN
Solar/Wind Harmer
0.443
270263AC1-001 GEN
Solar/Wind Harmer
0.582
270340AC2-060 GEN
Solar/Wind Harmer
0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.154
253372AE2-315 SEC3
Adder
1.444
253372AE2-315 SEC3
Adder
1.444
25306009OHH W.
Adder
2.154
3429211JKCT 2G
Adder
8.179
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.01
971029AG2-637 GEN
Solar/Wind Harmer
6.48
241972AD1-140 GEN
Solar/Wind Harmer
0.472
270543AE2-219 C
Solar/Wind Harmer
2.892
247536S-71 GEN
Solar/Wind Harmer
0.158
964611AG1-324 GEN
Solar/Wind Harmer
1.472
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.584
970289AG2-191 GEN
Solar/Wind Harmer
0.636
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
2.909
LAGNLTFEXP_LAGN->PJM
CLTF
5.22
TVALTFEXP_TVA->PJM
CLTF
2.571
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.475
MECLTFEXP_MEC->PJM
CLTF
5.763
SIGELTFEXP_SIGE->PJM
CLTF
0.281
NYPJM->LTFIMP_NY
CLTF
1.348
LGEELTFEXP_LGEE->PJM
CLTF
4.627
WECLTFEXP_WEC->PJM
CLTF
1.3
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.242
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.509

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#6763_05BIERSR 345_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.64 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1642.31
MW Contribution:
3.15
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:124.15 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1911.95
MW Contribution:
3.33
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.233
24802706KYGER 1LP
50/50
2.482
24803506KYGER 5LP
50/50
2.424
971985AH1-537 GEN
Solar/Wind Harmer
50.257
270263AC1-001 GEN
Solar/Wind Harmer
1.208
270340AC2-060 GEN
Solar/Wind Harmer
3.062
25196408WSDLE3
Adder
8.855
253433AC1-085 GEN1
Solar/Wind Harmer
5.315
253432AC1-085 GEN2
Solar/Wind Harmer
0.268
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
972163AH1-664 GEN
Solar/Wind Harmer
9.072
972165AH1-665 GEN
Solar/Wind Harmer
7.258
253406AD2-031_GEN
Solar/Wind Harmer
1.155
270432AC2-029 GEN
Solar/Wind Harmer
6.034
339216AC1-074 GEN
Solar/Wind Harmer
1.44
253372AE2-315 SEC3
Adder
1.457
253372AE2-315 SEC3
Adder
1.457
25306009OHH W.
Adder
2.176
3429211JKCT 2G
Adder
8.545
270356AE2-297 GEN
Solar/Wind Harmer
3.063
971029AG2-637 GEN
Solar/Wind Harmer
9.355
241972AD1-140 GEN
Solar/Wind Harmer
2.699
270543AE2-219 C
Solar/Wind Harmer
5.951
247536S-71 GEN
Solar/Wind Harmer
2.301
964611AG1-324 GEN
Solar/Wind Harmer
2.109
961761AG1-017 GEN
Solar/Wind Harmer
0.229
253338AC1-165 GEN
Solar/Wind Harmer
0.575
253343AC1-166 GEN
Solar/Wind Harmer
0.575
945581AF1-223 GEN
Solar/Wind Harmer
2.315
958711AF2-162 GEN
Solar/Wind Harmer
0.482
970289AG2-191 GEN
Solar/Wind Harmer
0.904
270444AC2-157 GEN1
Solar/Wind Harmer
2.638
270445AC2-157 GEN2
Solar/Wind Harmer
2.638
24729505KEY G4
Adder
2.858
24803006KYGER 3HP
50/50
4.203
24802806KYGER 2HP
50/50
4.187
24802906KYGER 2LP
50/50
2.458
25183008BIOENL
50/50
0.03
270269AC2-059
Solar/Wind Harmer
11.217
252509AD1-136 GEN
Solar/Wind Harmer
0.29
25183208HLCRTG
Solar/Wind Harmer
6.476
25194408D.CRK1
Adder
7.607
25194508D.CRK3
Adder
1.422
253415AE1-040 GEN
Solar/Wind Harmer
1.072
962581AG1-107 GEN
Solar/Wind Harmer
4.523
961491AF2-440 GEN
Solar/Wind Harmer
1.88
972043AH1-570 GEN
Solar/Wind Harmer
2.063
972045AH1-571 GEN
Solar/Wind Harmer
1.65
971125AH1-004 GEN
Solar/Wind Harmer
3.156
970107AG2-081 GEN
Solar/Wind Harmer
2.367
253370AE2-315 SEC1
Adder
1.54
25322209TAIT E
Adder
7.197
25322209TAIT E
Adder
7.035
253349AC2-067 GEN
Solar/Wind Harmer
1.487
253400AC2-068 GEN
Solar/Wind Harmer
0.598
942891AE2-308 GEN
Solar/Wind Harmer
7.164
25326109MON D
Adder
0.939
926881AC1-175 GEN
Solar/Wind Harmer
3.478
270383AD1-128 GEN
Solar/Wind Harmer
3.738
970883AG2-550 GEN
Solar/Wind Harmer
5.951
970885AG2-551 GEN
Solar/Wind Harmer
1.384
964571AG1-320 GEN
Solar/Wind Harmer
4.845
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
2.756
24725505WLD G2 C
Solar/Wind Harmer
2.089
24699105WLD G1 C
Solar/Wind Harmer
2.065
270031AE2-169
Solar/Wind Harmer
4.163
270599AE1-208 GEN
Solar/Wind Harmer
4.163
339236AF1-050_GEN
Solar/Wind Harmer
0.911
25326509SID D
Adder
0.639
339231AF1-038_GEN
Solar/Wind Harmer
0.877
944541AF1-119 GEN
Solar/Wind Harmer
1.995
960971AF2-388 GEN
Solar/Wind Harmer
5.207
970291AG2-192 GEN
Solar/Wind Harmer
0.618
970291AG2-192 GEN
Solar/Wind Harmer
0.199
964781AG1-341 GEN
Solar/Wind Harmer
4.908
945391AF1-204 GEN
Solar/Wind Harmer
6.233
253378AE2-206_GEN
Solar/Wind Harmer
1.598
942221AE2-234 GEN
Solar/Wind Harmer
1.546
971485AH1-239 GEN
Solar/Wind Harmer
3.529
966021AG1-471 GEN
Solar/Wind Harmer
2.352
24803106KYGER 3LP
50/50
2.475
24803306KYGER 4LP
50/50
2.424
971191AH1-055 GEN
Solar/Wind Harmer
74.07
252507AC2-088 GEN
Solar/Wind Harmer
2.029
252519AF1-045_GEN
Solar/Wind Harmer
3.821
25194608D.CRK4
Adder
1.654
252524AE2-267 GEN
Solar/Wind Harmer
1.581
25196608WSDLE5
Adder
8.602
253317AC1-085 GEN4
Solar/Wind Harmer
8.374
946181AF1-283 GEN
Solar/Wind Harmer
13.003
958171AF2-111 GEN
Solar/Wind Harmer
24.384
25196008MFTGT1
Adder
1.281
253394AE2-221_GEN
Solar/Wind Harmer
4.227
270367AC2-061_GEN
Solar/Wind Harmer
2.94
972167AH1-666 GEN
Solar/Wind Harmer
7.371
270186AC1-089 GEN
Solar/Wind Harmer
5.567
339243AC2-075 GEN1
Solar/Wind Harmer
0.39
253303V4-073 C
Solar/Wind Harmer
0.089
253370AE2-315 SEC1
Adder
1.54
253371AE2-315 SEC2
Adder
1.457
3429391JKCT 9G
Adder
6.269
960071AF2-298 GEN
Solar/Wind Harmer
1.104
970093AG2-073 GEN
Solar/Wind Harmer
3.624
24379505HDWTR1G C
Solar/Wind Harmer
4.928
270240V3-007_GEN2
Solar/Wind Harmer
3.856
970455AG2-298 GEN
Solar/Wind Harmer
2.145
24728505AND G1
Adder
2.198
970653AG2-424 GEN
Solar/Wind Harmer
0.398
270004AE1-209 GEN
Solar/Wind Harmer
3.075
946031AF1-268 GEN
Solar/Wind Harmer
4.625
339206AE1-143 GEN
Solar/Wind Harmer
1.182
970825AG2-519 GEN
Solar/Wind Harmer
3.119
962031AG1-047 GEN
Solar/Wind Harmer
1.621
957741AF2-068 GEN
Solar/Wind Harmer
8.043
253325AC1-069 GEN
Solar/Wind Harmer
0.554
972273AH1-721 GEN
Adder
41.705
965461AG1-414 GEN
Solar/Wind Harmer
1.079
970289AG2-191 GEN
Solar/Wind Harmer
0.365
339255AE2-071 GEN
Solar/Wind Harmer
0.546
339250AF1-203 GEN
Solar/Wind Harmer
0.281
247642Z2-115 C
Solar/Wind Harmer
0.029
270518AE2-148 GEN
Solar/Wind Harmer
5.413
970193AG2-126 GEN
Solar/Wind Harmer
6.708
276820AF1-078_GEN
Solar/Wind Harmer
0.71
270330AC1-082 GEN2
Solar/Wind Helper
0.177
270329AC1-082 GEN1
Solar/Wind Helper
0.177
24803406KYGER 5HP
50/50
4.154
24803206KYGER 4HP
50/50
4.145
270273AD2-016 GEN
Solar/Wind Harmer
3.199
252516AE2-318_GEN
Solar/Wind Harmer
10.498
25196808ZIMRHP
Adder
78.483
252510AF1-249 C
Solar/Wind Harmer
0.42
25194608D.CRK4
Adder
1.654
253316AC1-085 GEN3
Solar/Wind Harmer
8.374
946171AF1-282 GEN
Solar/Wind Harmer
10.003
25196008MFTGT1
Adder
1.323
253398AE2-221_GEN2
Solar/Wind Harmer
4.227
945681AF1-233 GEN
Solar/Wind Harmer
17.298
339221AD2-048_GEN
Solar/Wind Harmer
1.297
943111AE2-339 GEN
Solar/Wind Harmer
0.692
270222AC2-111 GEN
Solar/Wind Harmer
3.448
944031AF1-071 GEN
Solar/Wind Harmer
0.776
253370AE2-315 SEC1
Adder
1.54
253371AE2-315 SEC2
Adder
1.457
3429421JKCT 10G
Adder
6.269
25326309TAIT D
Adder
0.808
3429241JKCT 3G
Adder
8.658
339211AE2-254 GEN
Solar/Wind Harmer
0.946
942081AE2-220 GEN
Solar/Wind Harmer
3.986
270209AC1-174_GEN
Solar/Wind Harmer
2.536
270437AC2-090 C
Solar/Wind Harmer
3.478
270239V3-007_GEN1
Solar/Wind Harmer
1.072
24728605AND G2
Adder
2.198
970653AG2-424 GEN
Solar/Wind Harmer
2.75
270005AE1-210 C O1
Solar/Wind Harmer
3.075
970825AG2-519 GEN
Solar/Wind Harmer
1.162
339241AF1-083 GEN
Solar/Wind Harmer
0.887
253333AC1-068 GEN
Solar/Wind Harmer
0.554
945371AF1-202 GEN
Solar/Wind Harmer
3.561
276903AD2-071 C
Solar/Wind Harmer
5.099
970091AG2-072 GEN
Adder
38.38
964901AG1-354 GEN
Solar/Wind Harmer
7.465
270594AE1-207 GEN
Solar/Wind Harmer
6.734
270032AE2-172
Solar/Wind Harmer
2.306
958861AF2-177 GEN
Solar/Wind Harmer
5.335
270024AE2-089 GEN
Solar/Wind Harmer
2.242
965651AG1-433 GEN
Solar/Wind Harmer
2.603
960001AF2-291 GEN
Solar/Wind Helper
1.623
270331AC1-082 GEN3
Solar/Wind Helper
0.176
LAGNLTFEXP_LAGN->PJM
CLTF
5.453
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.294
TVALTFEXP_TVA->PJM
CLTF
2.722
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.877
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.097
MECLTFEXP_MEC->PJM
CLTF
5.729
SIGELTFEXP_SIGE->PJM
CLTF
0.289
NYPJM->LTFIMP_NY
CLTF
1.367
LGEELTFEXP_LGEE->PJM
CLTF
4.789
WECLTFEXP_WEC->PJM
CLTF
1.269
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.139
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.122
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.722

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#308_05CULLOD 765_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.58 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1641.32
MW Contribution:
3.2
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.05 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1848.71
MW Contribution:
3.36
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.181
24802706KYGER 1LP
50/50
2.452
24803506KYGER 5LP
50/50
2.394
971985AH1-537 GEN
Solar/Wind Harmer
49.573
25196408WSDLE3
Adder
8.83
253433AC1-085 GEN1
Solar/Wind Harmer
5.281
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
1.456
25196108MFTGT2
Adder
1.352
972163AH1-664 GEN
Solar/Wind Harmer
8.997
972165AH1-665 GEN
Solar/Wind Harmer
7.198
253406AD2-031_GEN
Solar/Wind Harmer
1.124
339216AC1-074 GEN
Solar/Wind Harmer
1.434
270340AC2-060 GEN
Solar/Wind Harmer
2.588
270263AC1-001 GEN
Solar/Wind Harmer
0.893
253372AE2-315 SEC3
Adder
1.482
253372AE2-315 SEC3
Adder
1.482
25306009OHH W.
Adder
2.212
3429211JKCT 2G
Adder
8.562
270356AE2-297 GEN
Solar/Wind Harmer
3.125
270432AC2-029 GEN
Solar/Wind Harmer
4.647
971029AG2-637 GEN
Solar/Wind Harmer
9.596
241972AD1-140 GEN
Solar/Wind Harmer
2.835
270543AE2-219 C
Solar/Wind Harmer
6.124
247536S-71 GEN
Solar/Wind Harmer
2.375
253338AC1-165 GEN
Solar/Wind Harmer
0.626
253343AC1-166 GEN
Solar/Wind Harmer
0.626
964611AG1-324 GEN
Solar/Wind Harmer
2.185
961761AG1-017 GEN
Solar/Wind Harmer
0.238
945581AF1-223 GEN
Solar/Wind Harmer
2.41
970289AG2-191 GEN
Solar/Wind Harmer
0.949
958711AF2-162 GEN
Solar/Wind Harmer
0.505
270444AC2-157 GEN1
Solar/Wind Harmer
2.766
270445AC2-157 GEN2
Solar/Wind Harmer
2.766
24729505KEY G4
Adder
3.017
24803006KYGER 3HP
50/50
4.152
24802806KYGER 2HP
50/50
4.136
24802906KYGER 2LP
50/50
2.428
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.286
25183208HLCRTG
Solar/Wind Harmer
6.412
25194408D.CRK1
Adder
7.577
25194508D.CRK3
Adder
1.417
962581AG1-107 GEN
Solar/Wind Harmer
4.372
961491AF2-440 GEN
Solar/Wind Harmer
1.817
270269AC2-059
Solar/Wind Harmer
7.941
253415AE1-040 GEN
Solar/Wind Harmer
0.933
972043AH1-570 GEN
Solar/Wind Harmer
2.055
972045AH1-571 GEN
Solar/Wind Harmer
1.644
971125AH1-004 GEN
Solar/Wind Harmer
3.154
970107AG2-081 GEN
Solar/Wind Harmer
2.365
253370AE2-315 SEC1
Adder
1.567
25322209TAIT E
Adder
7.355
25322209TAIT E
Adder
7.19
253349AC2-067 GEN
Solar/Wind Harmer
1.516
253400AC2-068 GEN
Solar/Wind Harmer
0.61
25326109MON D
Adder
0.965
942891AE2-308 GEN
Solar/Wind Harmer
7.186
926881AC1-175 GEN
Solar/Wind Harmer
3.565
270383AD1-128 GEN
Solar/Wind Harmer
3.837
970883AG2-550 GEN
Solar/Wind Harmer
6.124
970885AG2-551 GEN
Solar/Wind Harmer
1.424
964571AG1-320 GEN
Solar/Wind Harmer
4.93
247621Y3-024
Adder
0.138
964611AG1-324 GEN
Solar/Wind Harmer
0.293
270201AC2-176 GEN
Solar/Wind Harmer
2.858
24725505WLD G2 C
Solar/Wind Harmer
2.172
24699105WLD G1 C
Solar/Wind Harmer
2.146
270031AE2-169
Solar/Wind Harmer
4.335
270599AE1-208 GEN
Solar/Wind Harmer
4.335
25326509SID D
Adder
0.676
339236AF1-050_GEN
Solar/Wind Harmer
0.931
970291AG2-192 GEN
Solar/Wind Harmer
0.649
970291AG2-192 GEN
Solar/Wind Harmer
0.209
944541AF1-119 GEN
Solar/Wind Harmer
2.09
960971AF2-388 GEN
Solar/Wind Harmer
5.455
339231AF1-038_GEN
Solar/Wind Harmer
0.897
253378AE2-206_GEN
Solar/Wind Harmer
1.709
964781AG1-341 GEN
Solar/Wind Harmer
5.034
945391AF1-204 GEN
Solar/Wind Harmer
6.561
942221AE2-234 GEN
Solar/Wind Harmer
1.631
971485AH1-239 GEN
Solar/Wind Harmer
3.621
966021AG1-471 GEN
Solar/Wind Harmer
2.415
970241AG2-163 GEN
Solar/Wind Harmer
10.778
237033AB1-150 GEN
Solar/Wind Helper
0.376
24803106KYGER 3LP
50/50
2.445
24803306KYGER 4LP
50/50
2.394
971191AH1-055 GEN
Solar/Wind Harmer
72.303
252507AC2-088 GEN
Solar/Wind Harmer
2.004
252519AF1-045_GEN
Solar/Wind Harmer
3.791
25194608D.CRK4
Adder
1.647
252524AE2-267 GEN
Solar/Wind Harmer
1.576
25196608WSDLE5
Adder
8.577
253317AC1-085 GEN4
Solar/Wind Harmer
8.32
946181AF1-283 GEN
Solar/Wind Harmer
12.919
958171AF2-111 GEN
Solar/Wind Harmer
24.139
25196008MFTGT1
Adder
1.279
253394AE2-221_GEN
Solar/Wind Harmer
4.228
972167AH1-666 GEN
Solar/Wind Harmer
7.307
270367AC2-061_GEN
Solar/Wind Harmer
2.836
270186AC1-089 GEN
Solar/Wind Harmer
5.382
339243AC2-075 GEN1
Solar/Wind Harmer
0.388
253303V4-073 C
Solar/Wind Harmer
0.091
253370AE2-315 SEC1
Adder
1.567
253371AE2-315 SEC2
Adder
1.482
3429391JKCT 9G
Adder
6.274
960071AF2-298 GEN
Solar/Wind Harmer
1.127
970093AG2-073 GEN
Solar/Wind Harmer
3.641
24379505HDWTR1G C
Solar/Wind Harmer
5.05
270240V3-007_GEN2
Solar/Wind Harmer
3.951
970455AG2-298 GEN
Solar/Wind Harmer
2.176
24728505AND G1
Adder
2.264
270004AE1-209 GEN
Solar/Wind Harmer
3.176
970653AG2-424 GEN
Solar/Wind Harmer
0.405
253325AC1-069 GEN
Solar/Wind Harmer
0.604
946031AF1-268 GEN
Solar/Wind Harmer
4.781
970825AG2-519 GEN
Solar/Wind Harmer
3.226
339206AE1-143 GEN
Solar/Wind Harmer
1.202
962031AG1-047 GEN
Solar/Wind Harmer
1.681
957741AF2-068 GEN
Solar/Wind Harmer
8.342
270518AE2-148 GEN
Solar/Wind Harmer
6.232
972273AH1-721 GEN
Adder
42.523
965461AG1-414 GEN
Solar/Wind Harmer
1.132
970289AG2-191 GEN
Solar/Wind Harmer
0.383
247642Z2-115 C
Solar/Wind Harmer
0.031
339255AE2-071 GEN
Solar/Wind Harmer
0.56
339250AF1-203 GEN
Solar/Wind Harmer
0.288
276820AF1-078_GEN
Solar/Wind Harmer
0.759
970193AG2-126 GEN
Solar/Wind Harmer
7.062
944531AF1-118 GEN
Solar/Wind Harmer
15.85
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
24803406KYGER 5HP
50/50
4.104
24803206KYGER 4HP
50/50
4.094
252516AE2-318_GEN
Solar/Wind Harmer
10.415
25196808ZIMRHP
Adder
77.888
25194608D.CRK4
Adder
1.647
252510AF1-249 C
Solar/Wind Harmer
0.418
253316AC1-085 GEN3
Solar/Wind Harmer
8.32
946171AF1-282 GEN
Solar/Wind Harmer
9.938
25196008MFTGT1
Adder
1.321
253398AE2-221_GEN2
Solar/Wind Harmer
4.228
945681AF1-233 GEN
Solar/Wind Harmer
17.15
270273AD2-016 GEN
Solar/Wind Harmer
2.264
339221AD2-048_GEN
Solar/Wind Harmer
1.291
943111AE2-339 GEN
Solar/Wind Harmer
0.692
253370AE2-315 SEC1
Adder
1.567
253371AE2-315 SEC2
Adder
1.482
270222AC2-111 GEN
Solar/Wind Harmer
3.487
944031AF1-071 GEN
Solar/Wind Harmer
0.785
25326309TAIT D
Adder
0.826
3429421JKCT 10G
Adder
6.274
3429241JKCT 3G
Adder
8.674
942081AE2-220 GEN
Solar/Wind Harmer
4.085
270209AC1-174_GEN
Solar/Wind Harmer
2.599
270437AC2-090 C
Solar/Wind Harmer
3.565
270239V3-007_GEN1
Solar/Wind Harmer
1.099
339211AE2-254 GEN
Solar/Wind Harmer
0.956
24728605AND G2
Adder
2.264
270005AE1-210 C O1
Solar/Wind Harmer
3.176
970653AG2-424 GEN
Solar/Wind Harmer
2.799
253333AC1-068 GEN
Solar/Wind Harmer
0.604
970825AG2-519 GEN
Solar/Wind Harmer
1.201
339241AF1-083 GEN
Solar/Wind Harmer
0.903
276903AD2-071 C
Solar/Wind Harmer
5.316
945371AF1-202 GEN
Solar/Wind Harmer
3.708
970091AG2-072 GEN
Adder
40.26
270594AE1-207 GEN
Solar/Wind Harmer
7.041
270032AE2-172
Solar/Wind Harmer
2.411
958861AF2-177 GEN
Solar/Wind Harmer
5.577
964901AG1-354 GEN
Solar/Wind Harmer
7.63
270024AE2-089 GEN
Solar/Wind Harmer
2.348
965651AG1-433 GEN
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
19.4
960001AF2-291 GEN
Solar/Wind Helper
1.679
270331AC1-082 GEN3
Solar/Wind Helper
0.185
235780M24_1
Solar/Wind Helper
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
5.772
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.344
TVALTFEXP_TVA->PJM
CLTF
2.874
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.588
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.625
MECLTFEXP_MEC->PJM
CLTF
6.138
SIGELTFEXP_SIGE->PJM
CLTF
0.297
NYPJM->LTFIMP_NY
CLTF
1.419
LGEELTFEXP_LGEE->PJM
CLTF
4.847
WECLTFEXP_WEC->PJM
CLTF
1.374
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.143
AG2-052LTFEXP_AG2-052->PJM
LTF
0.088
AH1-155LTFEXP_AH1-155->PJM
LTF
0.132
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.11

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P7-1_#11019___SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11019___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.15 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1634.72
MW Contribution:
3.15
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.147
24802806KYGER 2HP
50/50
4.132
24802906KYGER 2LP
50/50
2.425
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.286
25183208HLCRTG
Solar/Wind Harmer
6.401
25194408D.CRK1
Adder
7.63
25194508D.CRK3
Adder
1.427
962581AG1-107 GEN
Solar/Wind Harmer
4.324
961491AF2-440 GEN
Solar/Wind Harmer
1.797
270269AC2-059
Solar/Wind Harmer
7.807
253415AE1-040 GEN
Solar/Wind Harmer
0.922
972043AH1-570 GEN
Solar/Wind Harmer
2.031
972045AH1-571 GEN
Solar/Wind Harmer
1.625
253370AE2-315 SEC1
Adder
1.572
971125AH1-004 GEN
Solar/Wind Harmer
3.116
970107AG2-081 GEN
Solar/Wind Harmer
2.337
926881AC1-175 GEN
Solar/Wind Harmer
4.256
25322209TAIT E
Adder
7.38
25322209TAIT E
Adder
7.214
253349AC2-067 GEN
Solar/Wind Harmer
1.537
253400AC2-068 GEN
Solar/Wind Harmer
0.618
25326109MON D
Adder
0.965
944541AF1-119 GEN
Solar/Wind Harmer
3.039
960971AF2-388 GEN
Solar/Wind Harmer
7.934
270383AD1-128 GEN
Solar/Wind Harmer
4.402
942891AE2-308 GEN
Solar/Wind Harmer
7.07
970883AG2-550 GEN
Solar/Wind Harmer
6.73
970885AG2-551 GEN
Solar/Wind Harmer
1.565
964611AG1-324 GEN
Solar/Wind Harmer
0.333
247621Y3-024
Adder
0.152
270201AC2-176 GEN
Solar/Wind Harmer
3.215
24725505WLD G2 C
Solar/Wind Harmer
2.387
24699105WLD G1 C
Solar/Wind Harmer
2.359
964571AG1-320 GEN
Solar/Wind Harmer
4.862
270031AE2-169
Solar/Wind Harmer
4.804
270599AE1-208 GEN
Solar/Wind Harmer
4.804
970291AG2-192 GEN
Solar/Wind Harmer
0.705
970291AG2-192 GEN
Solar/Wind Harmer
0.227
25326509SID D
Adder
0.666
339236AF1-050_GEN
Solar/Wind Harmer
0.907
339231AF1-038_GEN
Solar/Wind Harmer
0.869
942221AE2-234 GEN
Solar/Wind Harmer
1.672
253378AE2-206_GEN
Solar/Wind Harmer
1.682
945391AF1-204 GEN
Solar/Wind Harmer
6.43
964781AG1-341 GEN
Solar/Wind Harmer
4.886
971485AH1-239 GEN
Solar/Wind Harmer
3.491
966021AG1-471 GEN
Solar/Wind Harmer
2.326
24802606KYGER 1HP
50/50
4.177
24802706KYGER 1LP
50/50
2.449
24803506KYGER 5LP
50/50
2.392
971985AH1-537 GEN
Solar/Wind Harmer
49.507
25196408WSDLE3
Adder
8.895
253433AC1-085 GEN1
Solar/Wind Harmer
5.248
253432AC1-085 GEN2
Solar/Wind Harmer
0.264
25196108MFTGT2
Adder
1.472
25196108MFTGT2
Adder
1.367
972163AH1-664 GEN
Solar/Wind Harmer
8.886
972165AH1-665 GEN
Solar/Wind Harmer
7.109
253406AD2-031_GEN
Solar/Wind Harmer
1.116
339216AC1-074 GEN
Solar/Wind Harmer
1.421
270340AC2-060 GEN
Solar/Wind Harmer
2.555
270263AC1-001 GEN
Solar/Wind Harmer
0.877
253372AE2-315 SEC3
Adder
1.486
253372AE2-315 SEC3
Adder
1.486
25306009OHH W.
Adder
2.227
270356AE2-297 GEN
Solar/Wind Harmer
3.397
24729505KEY G4
Adder
4.712
958711AF2-162 GEN
Solar/Wind Harmer
0.734
945581AF1-223 GEN
Solar/Wind Harmer
3.291
3429211JKCT 2G
Adder
8.429
971029AG2-637 GEN
Solar/Wind Harmer
10.454
270543AE2-219 C
Solar/Wind Harmer
6.73
270432AC2-029 GEN
Solar/Wind Harmer
4.565
247536S-71 GEN
Solar/Wind Harmer
2.631
964611AG1-324 GEN
Solar/Wind Harmer
2.484
241972AD1-140 GEN
Solar/Wind Harmer
2.83
961761AG1-017 GEN
Solar/Wind Harmer
0.268
253338AC1-165 GEN
Solar/Wind Harmer
0.62
253343AC1-166 GEN
Solar/Wind Harmer
0.62
970289AG2-191 GEN
Solar/Wind Harmer
1.03
270444AC2-157 GEN1
Solar/Wind Harmer
2.679
270445AC2-157 GEN2
Solar/Wind Harmer
2.679
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.392
971191AH1-055 GEN
Solar/Wind Harmer
71.988
252507AC2-088 GEN
Solar/Wind Harmer
2.003
252519AF1-045_GEN
Solar/Wind Harmer
3.797
25194608D.CRK4
Adder
1.659
252524AE2-267 GEN
Solar/Wind Harmer
1.588
25196608WSDLE5
Adder
8.641
253317AC1-085 GEN4
Solar/Wind Harmer
8.268
946181AF1-283 GEN
Solar/Wind Harmer
12.839
25196008MFTGT1
Adder
1.293
958171AF2-111 GEN
Solar/Wind Harmer
23.953
253394AE2-221_GEN
Solar/Wind Harmer
4.207
972167AH1-666 GEN
Solar/Wind Harmer
7.221
270367AC2-061_GEN
Solar/Wind Harmer
2.804
270186AC1-089 GEN
Solar/Wind Harmer
5.313
339243AC2-075 GEN1
Solar/Wind Harmer
0.385
253303V4-073 C
Solar/Wind Harmer
0.091
253370AE2-315 SEC1
Adder
1.572
253371AE2-315 SEC2
Adder
1.486
24379505HDWTR1G C
Solar/Wind Harmer
6.03
270240V3-007_GEN2
Solar/Wind Harmer
4.718
960071AF2-298 GEN
Solar/Wind Harmer
1.133
3429391JKCT 9G
Adder
6.186
944531AF1-118 GEN
Solar/Wind Harmer
25.425
270004AE1-209 GEN
Solar/Wind Harmer
3.962
946031AF1-268 GEN
Solar/Wind Harmer
5.635
970093AG2-073 GEN
Solar/Wind Harmer
3.576
970825AG2-519 GEN
Solar/Wind Harmer
3.78
24728505AND G1
Adder
2.43
962031AG1-047 GEN
Solar/Wind Harmer
1.892
957741AF2-068 GEN
Solar/Wind Harmer
9.384
970455AG2-298 GEN
Solar/Wind Harmer
2.144
253325AC1-069 GEN
Solar/Wind Harmer
0.598
970653AG2-424 GEN
Solar/Wind Harmer
0.398
339206AE1-143 GEN
Solar/Wind Harmer
1.176
965461AG1-414 GEN
Solar/Wind Harmer
1.229
970289AG2-191 GEN
Solar/Wind Harmer
0.416
270518AE2-148 GEN
Solar/Wind Harmer
6.193
247642Z2-115 C
Solar/Wind Harmer
0.033
972273AH1-721 GEN
Adder
41.179
276820AF1-078_GEN
Solar/Wind Harmer
0.747
339255AE2-071 GEN
Solar/Wind Harmer
0.544
339250AF1-203 GEN
Solar/Wind Harmer
0.28
970193AG2-126 GEN
Solar/Wind Harmer
6.921
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
24803406KYGER 5HP
50/50
4.099
24803206KYGER 4HP
50/50
4.09
252516AE2-318_GEN
Solar/Wind Harmer
10.431
25196808ZIMRHP
Adder
78.006
25194608D.CRK4
Adder
1.659
252510AF1-249 C
Solar/Wind Harmer
0.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.268
946171AF1-282 GEN
Solar/Wind Harmer
9.876
25196008MFTGT1
Adder
1.335
253398AE2-221_GEN2
Solar/Wind Harmer
4.207
945681AF1-233 GEN
Solar/Wind Harmer
16.945
270273AD2-016 GEN
Solar/Wind Harmer
2.226
339221AD2-048_GEN
Solar/Wind Harmer
1.278
270222AC2-111 GEN
Solar/Wind Harmer
3.666
944031AF1-071 GEN
Solar/Wind Harmer
0.825
253370AE2-315 SEC1
Adder
1.572
253371AE2-315 SEC2
Adder
1.486
943111AE2-339 GEN
Solar/Wind Harmer
0.683
942081AE2-220 GEN
Solar/Wind Harmer
4.877
270209AC1-174_GEN
Solar/Wind Harmer
3.103
270437AC2-090 C
Solar/Wind Harmer
4.256
270239V3-007_GEN1
Solar/Wind Harmer
1.312
25326309TAIT D
Adder
0.828
3429421JKCT 10G
Adder
6.186
965651AG1-433 GEN
Solar/Wind Harmer
3.967
958861AF2-177 GEN
Solar/Wind Harmer
7.933
945371AF1-202 GEN
Solar/Wind Harmer
5.062
270005AE1-210 C O1
Solar/Wind Harmer
3.962
3429241JKCT 3G
Adder
8.54
970825AG2-519 GEN
Solar/Wind Harmer
1.408
24728605AND G2
Adder
2.43
339211AE2-254 GEN
Solar/Wind Harmer
0.938
276903AD2-071 C
Solar/Wind Harmer
5.798
270594AE1-207 GEN
Solar/Wind Harmer
7.838
270032AE2-172
Solar/Wind Harmer
2.684
253333AC1-068 GEN
Solar/Wind Harmer
0.598
970653AG2-424 GEN
Solar/Wind Harmer
2.75
270024AE2-089 GEN
Solar/Wind Harmer
2.518
339241AF1-083 GEN
Solar/Wind Harmer
0.882
970091AG2-072 GEN
Adder
38.234
964901AG1-354 GEN
Solar/Wind Harmer
7.432
960001AF2-291 GEN
Solar/Wind Helper
1.677
270331AC1-082 GEN3
Solar/Wind Helper
0.186
LAGNLTFEXP_LAGN->PJM
CLTF
5.383
TVALTFEXP_TVA->PJM
CLTF
2.678
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.356
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.982
MECLTFEXP_MEC->PJM
CLTF
5.697
SIGELTFEXP_SIGE->PJM
CLTF
0.296
NYPJM->LTFIMP_NY
CLTF
1.353
LGEELTFEXP_LGEE->PJM
CLTF
4.807
WECLTFEXP_WEC->PJM
CLTF
1.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.209
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.183

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.24 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1620.65
MW Contribution:
3.17
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.92 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1862.17
MW Contribution:
3.34
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.151
24802806KYGER 2HP
50/50
4.136
24802906KYGER 2LP
50/50
2.427
252509AD1-136 GEN
Solar/Wind Harmer
0.296
25194408D.CRK1
Adder
8.3
25194508D.CRK3
Adder
1.552
25183208HLCRTG
Solar/Wind Harmer
6.57
962581AG1-107 GEN
Solar/Wind Harmer
4.143
961491AF2-440 GEN
Solar/Wind Harmer
1.722
270269AC2-059
Solar/Wind Harmer
7.653
972043AH1-570 GEN
Solar/Wind Harmer
2.049
972045AH1-571 GEN
Solar/Wind Harmer
1.639
971125AH1-004 GEN
Solar/Wind Harmer
3.142
970107AG2-081 GEN
Solar/Wind Harmer
2.356
253415AE1-040 GEN
Solar/Wind Harmer
0.85
942891AE2-308 GEN
Solar/Wind Harmer
7.124
926881AC1-175 GEN
Solar/Wind Harmer
3.612
270383AD1-128 GEN
Solar/Wind Harmer
3.829
253349AC2-067 GEN
Solar/Wind Harmer
1.237
253400AC2-068 GEN
Solar/Wind Harmer
0.497
970883AG2-550 GEN
Solar/Wind Harmer
6.014
970885AG2-551 GEN
Solar/Wind Harmer
1.399
964571AG1-320 GEN
Solar/Wind Harmer
4.901
253370AE2-315 SEC1
Adder
1.193
25322209TAIT E
Adder
5.625
25322209TAIT E
Adder
5.499
247621Y3-024
Adder
0.136
964611AG1-324 GEN
Solar/Wind Harmer
0.291
270201AC2-176 GEN
Solar/Wind Harmer
2.828
25326109MON D
Adder
0.721
24725505WLD G2 C
Solar/Wind Harmer
2.164
24699105WLD G1 C
Solar/Wind Harmer
2.139
270031AE2-169
Solar/Wind Harmer
4.312
270599AE1-208 GEN
Solar/Wind Harmer
4.312
339236AF1-050_GEN
Solar/Wind Harmer
0.916
944541AF1-119 GEN
Solar/Wind Harmer
2.077
960971AF2-388 GEN
Solar/Wind Harmer
5.423
970291AG2-192 GEN
Solar/Wind Harmer
0.642
970291AG2-192 GEN
Solar/Wind Harmer
0.207
339231AF1-038_GEN
Solar/Wind Harmer
0.877
964781AG1-341 GEN
Solar/Wind Harmer
4.932
945391AF1-204 GEN
Solar/Wind Harmer
6.434
942221AE2-234 GEN
Solar/Wind Harmer
1.6
971485AH1-239 GEN
Solar/Wind Harmer
3.524
966021AG1-471 GEN
Solar/Wind Harmer
2.348
24802606KYGER 1HP
50/50
4.18
24802706KYGER 1LP
50/50
2.451
24803506KYGER 5LP
50/50
2.394
25250008NTE_CT
50/50
1.874
25250108NTE_ST
50/50
1.428
971985AH1-537 GEN
Solar/Wind Harmer
50.178
25196408WSDLE3
Adder
9.751
25196108MFTGT2
Adder
1.528
25196108MFTGT2
Adder
1.418
253433AC1-085 GEN1
Solar/Wind Harmer
4.843
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
972163AH1-664 GEN
Solar/Wind Harmer
8.928
972165AH1-665 GEN
Solar/Wind Harmer
7.142
339216AC1-074 GEN
Solar/Wind Harmer
1.438
270263AC1-001 GEN
Solar/Wind Harmer
0.863
270340AC2-060 GEN
Solar/Wind Harmer
2.393
253406AD2-031_GEN
Solar/Wind Harmer
0.982
3429211JKCT 2G
Adder
8.489
270356AE2-297 GEN
Solar/Wind Harmer
3.167
270432AC2-029 GEN
Solar/Wind Harmer
4.421
971029AG2-637 GEN
Solar/Wind Harmer
9.394
25306009OHH W.
Adder
1.747
270543AE2-219 C
Solar/Wind Harmer
6.014
253372AE2-315 SEC3
Adder
1.129
253372AE2-315 SEC3
Adder
1.129
247536S-71 GEN
Solar/Wind Harmer
2.339
964611AG1-324 GEN
Solar/Wind Harmer
2.166
961761AG1-017 GEN
Solar/Wind Harmer
0.235
945581AF1-223 GEN
Solar/Wind Harmer
2.407
253338AC1-165 GEN
Solar/Wind Harmer
0.566
253343AC1-166 GEN
Solar/Wind Harmer
0.566
958711AF2-162 GEN
Solar/Wind Harmer
0.502
970289AG2-191 GEN
Solar/Wind Harmer
0.938
270444AC2-157 GEN1
Solar/Wind Harmer
2.7
270445AC2-157 GEN2
Solar/Wind Harmer
2.7
241972AD1-140 GEN
Solar/Wind Harmer
2.089
24729505KEY G4
Adder
2.983
24803106KYGER 3LP
50/50
2.444
24803306KYGER 4LP
50/50
2.394
971191AH1-055 GEN
Solar/Wind Harmer
72.075
252507AC2-088 GEN
Solar/Wind Harmer
2.075
252519AF1-045_GEN
Solar/Wind Harmer
4.054
252524AE2-267 GEN
Solar/Wind Harmer
1.74
25196608WSDLE5
Adder
9.473
25194608D.CRK4
Adder
1.804
25196008MFTGT1
Adder
1.342
958171AF2-111 GEN
Solar/Wind Harmer
24.038
253317AC1-085 GEN4
Solar/Wind Harmer
7.629
946181AF1-283 GEN
Solar/Wind Harmer
11.847
972167AH1-666 GEN
Solar/Wind Harmer
7.254
270367AC2-061_GEN
Solar/Wind Harmer
2.783
339243AC2-075 GEN1
Solar/Wind Harmer
0.389
270186AC1-089 GEN
Solar/Wind Harmer
5.237
253394AE2-221_GEN
Solar/Wind Harmer
3.688
3429391JKCT 9G
Adder
6.228
970093AG2-073 GEN
Solar/Wind Harmer
3.604
24379505HDWTR1G C
Solar/Wind Harmer
5.117
270240V3-007_GEN2
Solar/Wind Harmer
4.003
970455AG2-298 GEN
Solar/Wind Harmer
2.164
253303V4-073 C
Solar/Wind Harmer
0.069
253370AE2-315 SEC1
Adder
1.193
253371AE2-315 SEC2
Adder
1.129
24728505AND G1
Adder
2.269
960071AF2-298 GEN
Solar/Wind Harmer
0.884
270004AE1-209 GEN
Solar/Wind Harmer
3.191
946031AF1-268 GEN
Solar/Wind Harmer
4.773
970653AG2-424 GEN
Solar/Wind Harmer
0.401
970825AG2-519 GEN
Solar/Wind Harmer
3.224
339206AE1-143 GEN
Solar/Wind Harmer
1.186
962031AG1-047 GEN
Solar/Wind Harmer
1.663
957741AF2-068 GEN
Solar/Wind Harmer
8.252
253325AC1-069 GEN
Solar/Wind Harmer
0.546
972273AH1-721 GEN
Adder
41.552
965461AG1-414 GEN
Solar/Wind Harmer
1.12
970289AG2-191 GEN
Solar/Wind Harmer
0.379
247642Z2-115 C
Solar/Wind Harmer
0.03
339255AE2-071 GEN
Solar/Wind Harmer
0.549
339250AF1-203 GEN
Solar/Wind Harmer
0.283
970193AG2-126 GEN
Solar/Wind Harmer
6.925
944531AF1-118 GEN
Solar/Wind Harmer
15.636
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
24803406KYGER 5HP
50/50
4.103
24803206KYGER 4HP
50/50
4.094
252516AE2-318_GEN
Solar/Wind Harmer
11.138
25194608D.CRK4
Adder
1.804
252510AF1-249 C
Solar/Wind Harmer
0.456
25196808ZIMRHP
Adder
81.595
25196008MFTGT1
Adder
1.386
253316AC1-085 GEN3
Solar/Wind Harmer
7.629
946171AF1-282 GEN
Solar/Wind Harmer
9.113
945681AF1-233 GEN
Solar/Wind Harmer
17.022
339221AD2-048_GEN
Solar/Wind Harmer
1.291
270273AD2-016 GEN
Solar/Wind Harmer
2.182
253398AE2-221_GEN2
Solar/Wind Harmer
3.688
943111AE2-339 GEN
Solar/Wind Harmer
0.688
270222AC2-111 GEN
Solar/Wind Harmer
3.467
944031AF1-071 GEN
Solar/Wind Harmer
0.78
3429421JKCT 10G
Adder
6.228
3429241JKCT 3G
Adder
8.601
942081AE2-220 GEN
Solar/Wind Harmer
4.139
270209AC1-174_GEN
Solar/Wind Harmer
2.633
270437AC2-090 C
Solar/Wind Harmer
3.612
270239V3-007_GEN1
Solar/Wind Harmer
1.113
339211AE2-254 GEN
Solar/Wind Harmer
0.946
253370AE2-315 SEC1
Adder
1.193
253371AE2-315 SEC2
Adder
1.129
24728605AND G2
Adder
2.269
270005AE1-210 C O1
Solar/Wind Harmer
3.191
25326309TAIT D
Adder
0.632
970653AG2-424 GEN
Solar/Wind Harmer
2.774
970825AG2-519 GEN
Solar/Wind Harmer
1.201
339241AF1-083 GEN
Solar/Wind Harmer
0.89
945371AF1-202 GEN
Solar/Wind Harmer
3.703
276903AD2-071 C
Solar/Wind Harmer
5.286
253333AC1-068 GEN
Solar/Wind Harmer
0.546
270594AE1-207 GEN
Solar/Wind Harmer
6.982
270032AE2-172
Solar/Wind Harmer
2.391
958861AF2-177 GEN
Solar/Wind Harmer
5.553
970091AG2-072 GEN
Adder
38.889
964901AG1-354 GEN
Solar/Wind Harmer
7.5
965651AG1-433 GEN
Solar/Wind Harmer
2.711
270024AE2-089 GEN
Solar/Wind Harmer
2.306
960001AF2-291 GEN
Solar/Wind Helper
1.678
270331AC1-082 GEN3
Solar/Wind Helper
0.186
LAGNLTFEXP_LAGN->PJM
CLTF
5.472
TVALTFEXP_TVA->PJM
CLTF
2.709
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.578
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.139
MECLTFEXP_MEC->PJM
CLTF
5.918
SIGELTFEXP_SIGE->PJM
CLTF
0.295
NYPJM->LTFIMP_NY
CLTF
1.375
LGEELTFEXP_LGEE->PJM
CLTF
4.87
WECLTFEXP_WEC->PJM
CLTF
1.323
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.209
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.539

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1616.13
MW Contribution:
3.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.49 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1763.1
MW Contribution:
3.17
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.171
24802706KYGER 1LP
50/50
2.446
24803506KYGER 5LP
50/50
2.388
971985AH1-537 GEN
Solar/Wind Harmer
49.138
25196408WSDLE3
Adder
8.592
253433AC1-085 GEN1
Solar/Wind Harmer
5.144
253432AC1-085 GEN2
Solar/Wind Harmer
0.259
25196108MFTGT2
Adder
1.412
25196108MFTGT2
Adder
1.312
972163AH1-664 GEN
Solar/Wind Harmer
8.663
972165AH1-665 GEN
Solar/Wind Harmer
6.93
253406AD2-031_GEN
Solar/Wind Harmer
1.092
270263AC1-001 GEN
Solar/Wind Harmer
0.871
270340AC2-060 GEN
Solar/Wind Harmer
2.516
339216AC1-074 GEN
Solar/Wind Harmer
1.38
253372AE2-315 SEC3
Adder
1.442
253372AE2-315 SEC3
Adder
1.442
25306009OHH W.
Adder
2.151
3429211JKCT 2G
Adder
8.167
270356AE2-297 GEN
Solar/Wind Harmer
3.013
270432AC2-029 GEN
Solar/Wind Harmer
4.541
971029AG2-637 GEN
Solar/Wind Harmer
9.271
241972AD1-140 GEN
Solar/Wind Harmer
2.765
270543AE2-219 C
Solar/Wind Harmer
5.912
247536S-71 GEN
Solar/Wind Harmer
2.291
253338AC1-165 GEN
Solar/Wind Harmer
0.612
253343AC1-166 GEN
Solar/Wind Harmer
0.612
964611AG1-324 GEN
Solar/Wind Harmer
2.105
961761AG1-017 GEN
Solar/Wind Harmer
0.229
945581AF1-223 GEN
Solar/Wind Harmer
2.32
958711AF2-162 GEN
Solar/Wind Harmer
0.486
970289AG2-191 GEN
Solar/Wind Harmer
0.909
270444AC2-157 GEN1
Solar/Wind Harmer
2.592
270445AC2-157 GEN2
Solar/Wind Harmer
2.592
24729505KEY G4
Adder
2.902
24803006KYGER 3HP
50/50
4.141
24802806KYGER 2HP
50/50
4.126
24802906KYGER 2LP
50/50
2.422
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.279
25183208HLCRTG
Solar/Wind Harmer
6.246
25194408D.CRK1
Adder
7.371
25194508D.CRK3
Adder
1.378
962581AG1-107 GEN
Solar/Wind Harmer
4.214
961491AF2-440 GEN
Solar/Wind Harmer
1.751
270269AC2-059
Solar/Wind Harmer
7.764
253415AE1-040 GEN
Solar/Wind Harmer
0.907
972043AH1-570 GEN
Solar/Wind Harmer
1.972
972045AH1-571 GEN
Solar/Wind Harmer
1.578
253370AE2-315 SEC1
Adder
1.524
971125AH1-004 GEN
Solar/Wind Harmer
3.022
970107AG2-081 GEN
Solar/Wind Harmer
2.267
25322209TAIT E
Adder
7.158
25322209TAIT E
Adder
6.998
253349AC2-067 GEN
Solar/Wind Harmer
1.474
253400AC2-068 GEN
Solar/Wind Harmer
0.593
25326109MON D
Adder
0.94
942891AE2-308 GEN
Solar/Wind Harmer
6.845
926881AC1-175 GEN
Solar/Wind Harmer
3.439
270383AD1-128 GEN
Solar/Wind Harmer
3.701
970883AG2-550 GEN
Solar/Wind Harmer
5.912
970885AG2-551 GEN
Solar/Wind Harmer
1.375
964571AG1-320 GEN
Solar/Wind Harmer
4.664
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.282
270201AC2-176 GEN
Solar/Wind Harmer
2.754
24725505WLD G2 C
Solar/Wind Harmer
2.084
24699105WLD G1 C
Solar/Wind Harmer
2.059
270031AE2-169
Solar/Wind Harmer
4.168
270599AE1-208 GEN
Solar/Wind Harmer
4.168
25326509SID D
Adder
0.658
944541AF1-119 GEN
Solar/Wind Harmer
2.011
960971AF2-388 GEN
Solar/Wind Harmer
5.248
339236AF1-050_GEN
Solar/Wind Harmer
0.871
970291AG2-192 GEN
Solar/Wind Harmer
0.622
970291AG2-192 GEN
Solar/Wind Harmer
0.2
253378AE2-206_GEN
Solar/Wind Harmer
1.666
339231AF1-038_GEN
Solar/Wind Harmer
0.834
942221AE2-234 GEN
Solar/Wind Harmer
1.568
945391AF1-204 GEN
Solar/Wind Harmer
6.202
964781AG1-341 GEN
Solar/Wind Harmer
4.685
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.388
971191AH1-055 GEN
Solar/Wind Harmer
71.816
252507AC2-088 GEN
Solar/Wind Harmer
1.953
252519AF1-045_GEN
Solar/Wind Harmer
3.69
25194608D.CRK4
Adder
1.602
252524AE2-267 GEN
Solar/Wind Harmer
1.534
25196608WSDLE5
Adder
8.347
253317AC1-085 GEN4
Solar/Wind Harmer
8.104
946181AF1-283 GEN
Solar/Wind Harmer
12.584
958171AF2-111 GEN
Solar/Wind Harmer
23.383
25196008MFTGT1
Adder
1.241
253394AE2-221_GEN
Solar/Wind Harmer
4.119
972167AH1-666 GEN
Solar/Wind Harmer
7.042
270367AC2-061_GEN
Solar/Wind Harmer
2.733
270186AC1-089 GEN
Solar/Wind Harmer
5.181
339243AC2-075 GEN1
Solar/Wind Harmer
0.374
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.524
253371AE2-315 SEC2
Adder
1.442
960071AF2-298 GEN
Solar/Wind Harmer
1.097
3429391JKCT 9G
Adder
5.997
970093AG2-073 GEN
Solar/Wind Harmer
3.458
24379505HDWTR1G C
Solar/Wind Harmer
4.872
270240V3-007_GEN2
Solar/Wind Harmer
3.812
970455AG2-298 GEN
Solar/Wind Harmer
2.061
24728505AND G1
Adder
2.168
253325AC1-069 GEN
Solar/Wind Harmer
0.59
270004AE1-209 GEN
Solar/Wind Harmer
3.058
946031AF1-268 GEN
Solar/Wind Harmer
4.604
970825AG2-519 GEN
Solar/Wind Harmer
3.105
970653AG2-424 GEN
Solar/Wind Harmer
0.382
962031AG1-047 GEN
Solar/Wind Harmer
1.62
957741AF2-068 GEN
Solar/Wind Harmer
8.036
339206AE1-143 GEN
Solar/Wind Harmer
1.13
270518AE2-148 GEN
Solar/Wind Harmer
6.093
965461AG1-414 GEN
Solar/Wind Harmer
1.085
970289AG2-191 GEN
Solar/Wind Harmer
0.367
972273AH1-721 GEN
Adder
39.573
276820AF1-078_GEN
Solar/Wind Harmer
0.74
247642Z2-115 C
Solar/Wind Harmer
0.029
970193AG2-126 GEN
Solar/Wind Harmer
6.675
339255AE2-071 GEN
Solar/Wind Harmer
0.521
339250AF1-203 GEN
Solar/Wind Harmer
0.268
944531AF1-118 GEN
Solar/Wind Harmer
15.239
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24803406KYGER 5HP
50/50
4.093
24803206KYGER 4HP
50/50
4.084
252516AE2-318_GEN
Solar/Wind Harmer
10.14
25196808ZIMRHP
Adder
75.73
25194608D.CRK4
Adder
1.602
252510AF1-249 C
Solar/Wind Harmer
0.406
253316AC1-085 GEN3
Solar/Wind Harmer
8.104
946171AF1-282 GEN
Solar/Wind Harmer
9.68
25196008MFTGT1
Adder
1.281
253398AE2-221_GEN2
Solar/Wind Harmer
4.119
945681AF1-233 GEN
Solar/Wind Harmer
16.525
270273AD2-016 GEN
Solar/Wind Harmer
2.214
339221AD2-048_GEN
Solar/Wind Harmer
1.241
253370AE2-315 SEC1
Adder
1.524
253371AE2-315 SEC2
Adder
1.442
270222AC2-111 GEN
Solar/Wind Harmer
3.38
944031AF1-071 GEN
Solar/Wind Harmer
0.76
943111AE2-339 GEN
Solar/Wind Harmer
0.662
25326309TAIT D
Adder
0.804
3429421JKCT 10G
Adder
5.997
3429241JKCT 3G
Adder
8.274
942081AE2-220 GEN
Solar/Wind Harmer
3.941
270209AC1-174_GEN
Solar/Wind Harmer
2.508
270437AC2-090 C
Solar/Wind Harmer
3.439
270239V3-007_GEN1
Solar/Wind Harmer
1.06
339211AE2-254 GEN
Solar/Wind Harmer
0.904
24728605AND G2
Adder
2.168
253333AC1-068 GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
3.058
970825AG2-519 GEN
Solar/Wind Harmer
1.156
970653AG2-424 GEN
Solar/Wind Harmer
2.64
945371AF1-202 GEN
Solar/Wind Harmer
3.569
339241AF1-083 GEN
Solar/Wind Harmer
0.848
276903AD2-071 C
Solar/Wind Harmer
5.097
270594AE1-207 GEN
Solar/Wind Harmer
6.753
270032AE2-172
Solar/Wind Harmer
2.313
958861AF2-177 GEN
Solar/Wind Harmer
5.366
970091AG2-072 GEN
Adder
37.252
270024AE2-089 GEN
Solar/Wind Harmer
2.261
965651AG1-433 GEN
Solar/Wind Harmer
2.624
964901AG1-354 GEN
Solar/Wind Harmer
7.132
960001AF2-291 GEN
Solar/Wind Helper
1.683
270331AC1-082 GEN3
Solar/Wind Helper
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
5.198
TVALTFEXP_TVA->PJM
CLTF
2.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.966
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.434
MECLTFEXP_MEC->PJM
CLTF
5.745
SIGELTFEXP_SIGE->PJM
CLTF
0.281
NYPJM->LTFIMP_NY
CLTF
1.355
LGEELTFEXP_LGEE->PJM
CLTF
4.619
WECLTFEXP_WEC->PJM
CLTF
1.296
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.249
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.364

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT5_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT5_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.91 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1600.21
MW Contribution:
3.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT5_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.35 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1745.55
MW Contribution:
3.17
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.171
24802706KYGER 1LP
50/50
2.446
24803506KYGER 5LP
50/50
2.389
971985AH1-537 GEN
Solar/Wind Harmer
49.142
25196408WSDLE3
Adder
8.594
253433AC1-085 GEN1
Solar/Wind Harmer
5.145
253432AC1-085 GEN2
Solar/Wind Harmer
0.259
25196108MFTGT2
Adder
1.413
25196108MFTGT2
Adder
1.312
972163AH1-664 GEN
Solar/Wind Harmer
8.665
972165AH1-665 GEN
Solar/Wind Harmer
6.932
253406AD2-031_GEN
Solar/Wind Harmer
1.092
270263AC1-001 GEN
Solar/Wind Harmer
0.871
270340AC2-060 GEN
Solar/Wind Harmer
2.517
339216AC1-074 GEN
Solar/Wind Harmer
1.38
253372AE2-315 SEC3
Adder
1.442
253372AE2-315 SEC3
Adder
1.442
25306009OHH W.
Adder
2.152
3429211JKCT 2G
Adder
8.17
270356AE2-297 GEN
Solar/Wind Harmer
3.014
270432AC2-029 GEN
Solar/Wind Harmer
4.543
971029AG2-637 GEN
Solar/Wind Harmer
9.275
241972AD1-140 GEN
Solar/Wind Harmer
2.767
270543AE2-219 C
Solar/Wind Harmer
5.914
247536S-71 GEN
Solar/Wind Harmer
2.292
253338AC1-165 GEN
Solar/Wind Harmer
0.612
253343AC1-166 GEN
Solar/Wind Harmer
0.612
964611AG1-324 GEN
Solar/Wind Harmer
2.106
961761AG1-017 GEN
Solar/Wind Harmer
0.229
945581AF1-223 GEN
Solar/Wind Harmer
2.321
958711AF2-162 GEN
Solar/Wind Harmer
0.486
970289AG2-191 GEN
Solar/Wind Harmer
0.909
270444AC2-157 GEN1
Solar/Wind Harmer
2.593
270445AC2-157 GEN2
Solar/Wind Harmer
2.593
24729505KEY G4
Adder
2.903
24803006KYGER 3HP
50/50
4.142
24802806KYGER 2HP
50/50
4.126
24802906KYGER 2LP
50/50
2.422
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.279
25183208HLCRTG
Solar/Wind Harmer
6.247
25194408D.CRK1
Adder
7.373
25194508D.CRK3
Adder
1.378
962581AG1-107 GEN
Solar/Wind Harmer
4.215
961491AF2-440 GEN
Solar/Wind Harmer
1.752
270269AC2-059
Solar/Wind Harmer
7.766
253415AE1-040 GEN
Solar/Wind Harmer
0.908
972043AH1-570 GEN
Solar/Wind Harmer
1.973
972045AH1-571 GEN
Solar/Wind Harmer
1.578
253370AE2-315 SEC1
Adder
1.525
971125AH1-004 GEN
Solar/Wind Harmer
3.023
970107AG2-081 GEN
Solar/Wind Harmer
2.267
25322209TAIT E
Adder
7.161
25322209TAIT E
Adder
7
253349AC2-067 GEN
Solar/Wind Harmer
1.474
253400AC2-068 GEN
Solar/Wind Harmer
0.593
25326109MON D
Adder
0.94
942891AE2-308 GEN
Solar/Wind Harmer
6.847
926881AC1-175 GEN
Solar/Wind Harmer
3.44
270383AD1-128 GEN
Solar/Wind Harmer
3.703
970883AG2-550 GEN
Solar/Wind Harmer
5.914
970885AG2-551 GEN
Solar/Wind Harmer
1.375
964571AG1-320 GEN
Solar/Wind Harmer
4.665
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
2.755
24725505WLD G2 C
Solar/Wind Harmer
2.085
24699105WLD G1 C
Solar/Wind Harmer
2.06
270031AE2-169
Solar/Wind Harmer
4.17
270599AE1-208 GEN
Solar/Wind Harmer
4.17
25326509SID D
Adder
0.658
944541AF1-119 GEN
Solar/Wind Harmer
2.012
960971AF2-388 GEN
Solar/Wind Harmer
5.251
339236AF1-050_GEN
Solar/Wind Harmer
0.871
970291AG2-192 GEN
Solar/Wind Harmer
0.622
970291AG2-192 GEN
Solar/Wind Harmer
0.2
253378AE2-206_GEN
Solar/Wind Harmer
1.667
339231AF1-038_GEN
Solar/Wind Harmer
0.835
942221AE2-234 GEN
Solar/Wind Harmer
1.569
945391AF1-204 GEN
Solar/Wind Harmer
6.205
964781AG1-341 GEN
Solar/Wind Harmer
4.687
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.389
971191AH1-055 GEN
Solar/Wind Harmer
71.821
252507AC2-088 GEN
Solar/Wind Harmer
1.953
252519AF1-045_GEN
Solar/Wind Harmer
3.691
25194608D.CRK4
Adder
1.603
252524AE2-267 GEN
Solar/Wind Harmer
1.534
25196608WSDLE5
Adder
8.349
253317AC1-085 GEN4
Solar/Wind Harmer
8.106
946181AF1-283 GEN
Solar/Wind Harmer
12.587
958171AF2-111 GEN
Solar/Wind Harmer
23.388
25196008MFTGT1
Adder
1.241
253394AE2-221_GEN
Solar/Wind Harmer
4.12
972167AH1-666 GEN
Solar/Wind Harmer
7.044
270367AC2-061_GEN
Solar/Wind Harmer
2.734
270186AC1-089 GEN
Solar/Wind Harmer
5.183
339243AC2-075 GEN1
Solar/Wind Harmer
0.374
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.525
253371AE2-315 SEC2
Adder
1.442
960071AF2-298 GEN
Solar/Wind Harmer
1.097
3429391JKCT 9G
Adder
5.999
970093AG2-073 GEN
Solar/Wind Harmer
3.46
24379505HDWTR1G C
Solar/Wind Harmer
4.874
270240V3-007_GEN2
Solar/Wind Harmer
3.813
970455AG2-298 GEN
Solar/Wind Harmer
2.061
24728505AND G1
Adder
2.169
253325AC1-069 GEN
Solar/Wind Harmer
0.59
270004AE1-209 GEN
Solar/Wind Harmer
3.06
946031AF1-268 GEN
Solar/Wind Harmer
4.606
970825AG2-519 GEN
Solar/Wind Harmer
3.106
970653AG2-424 GEN
Solar/Wind Harmer
0.382
962031AG1-047 GEN
Solar/Wind Harmer
1.621
957741AF2-068 GEN
Solar/Wind Harmer
8.04
339206AE1-143 GEN
Solar/Wind Harmer
1.131
270518AE2-148 GEN
Solar/Wind Harmer
6.095
965461AG1-414 GEN
Solar/Wind Harmer
1.085
970289AG2-191 GEN
Solar/Wind Harmer
0.367
972273AH1-721 GEN
Adder
39.592
276820AF1-078_GEN
Solar/Wind Harmer
0.741
247642Z2-115 C
Solar/Wind Harmer
0.029
970193AG2-126 GEN
Solar/Wind Harmer
6.679
339255AE2-071 GEN
Solar/Wind Harmer
0.522
339250AF1-203 GEN
Solar/Wind Harmer
0.269
944531AF1-118 GEN
Solar/Wind Harmer
15.247
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24803406KYGER 5HP
50/50
4.094
24803206KYGER 4HP
50/50
4.085
252516AE2-318_GEN
Solar/Wind Harmer
10.142
25196808ZIMRHP
Adder
75.748
25194608D.CRK4
Adder
1.603
252510AF1-249 C
Solar/Wind Harmer
0.406
253316AC1-085 GEN3
Solar/Wind Harmer
8.106
946171AF1-282 GEN
Solar/Wind Harmer
9.682
25196008MFTGT1
Adder
1.282
253398AE2-221_GEN2
Solar/Wind Harmer
4.12
945681AF1-233 GEN
Solar/Wind Harmer
16.529
270273AD2-016 GEN
Solar/Wind Harmer
2.214
339221AD2-048_GEN
Solar/Wind Harmer
1.241
253370AE2-315 SEC1
Adder
1.525
253371AE2-315 SEC2
Adder
1.442
270222AC2-111 GEN
Solar/Wind Harmer
3.381
944031AF1-071 GEN
Solar/Wind Harmer
0.761
943111AE2-339 GEN
Solar/Wind Harmer
0.663
25326309TAIT D
Adder
0.804
3429421JKCT 10G
Adder
5.999
3429241JKCT 3G
Adder
8.277
942081AE2-220 GEN
Solar/Wind Harmer
3.942
270209AC1-174_GEN
Solar/Wind Harmer
2.508
270437AC2-090 C
Solar/Wind Harmer
3.44
270239V3-007_GEN1
Solar/Wind Harmer
1.061
339211AE2-254 GEN
Solar/Wind Harmer
0.905
24728605AND G2
Adder
2.169
253333AC1-068 GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
3.06
970825AG2-519 GEN
Solar/Wind Harmer
1.157
970653AG2-424 GEN
Solar/Wind Harmer
2.641
945371AF1-202 GEN
Solar/Wind Harmer
3.57
339241AF1-083 GEN
Solar/Wind Harmer
0.848
276903AD2-071 C
Solar/Wind Harmer
5.099
270594AE1-207 GEN
Solar/Wind Harmer
6.756
270032AE2-172
Solar/Wind Harmer
2.314
958861AF2-177 GEN
Solar/Wind Harmer
5.369
970091AG2-072 GEN
Adder
37.27
270024AE2-089 GEN
Solar/Wind Harmer
2.262
965651AG1-433 GEN
Solar/Wind Harmer
2.625
964901AG1-354 GEN
Solar/Wind Harmer
7.136
960001AF2-291 GEN
Solar/Wind Helper
1.683
270331AC1-082 GEN3
Solar/Wind Helper
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
5.203
TVALTFEXP_TVA->PJM
CLTF
2.563
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.443
MECLTFEXP_MEC->PJM
CLTF
5.749
SIGELTFEXP_SIGE->PJM
CLTF
0.281
NYPJM->LTFIMP_NY
CLTF
1.353
LGEELTFEXP_LGEE->PJM
CLTF
4.621
WECLTFEXP_WEC->PJM
CLTF
1.297
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.248
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.395

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#316_05AMOS 765_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#316_05AMOS 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1560.82
MW Contribution:
3.03
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#316_05AMOS 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.21 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1789.67
MW Contribution:
3.21
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.141
24802706KYGER 1LP
50/50
2.428
24803506KYGER 5LP
50/50
2.371
971985AH1-537 GEN
Solar/Wind Harmer
48.849
25196408WSDLE3
Adder
8.575
253433AC1-085 GEN1
Solar/Wind Harmer
5.13
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
25196108MFTGT2
Adder
1.411
25196108MFTGT2
Adder
1.31
972163AH1-664 GEN
Solar/Wind Harmer
8.638
972165AH1-665 GEN
Solar/Wind Harmer
6.911
253406AD2-031_GEN
Solar/Wind Harmer
1.088
270340AC2-060 GEN
Solar/Wind Harmer
2.501
270263AC1-001 GEN
Solar/Wind Harmer
0.862
339216AC1-074 GEN
Solar/Wind Harmer
1.378
253372AE2-315 SEC3
Adder
1.438
253372AE2-315 SEC3
Adder
1.438
25306009OHH W.
Adder
2.146
3429211JKCT 2G
Adder
8.16
270356AE2-297 GEN
Solar/Wind Harmer
3.016
270432AC2-029 GEN
Solar/Wind Harmer
4.502
971029AG2-637 GEN
Solar/Wind Harmer
9.279
241972AD1-140 GEN
Solar/Wind Harmer
2.76
270543AE2-219 C
Solar/Wind Harmer
5.919
247536S-71 GEN
Solar/Wind Harmer
2.295
253338AC1-165 GEN
Solar/Wind Harmer
0.61
253343AC1-166 GEN
Solar/Wind Harmer
0.61
964611AG1-324 GEN
Solar/Wind Harmer
2.11
961761AG1-017 GEN
Solar/Wind Harmer
0.23
945581AF1-223 GEN
Solar/Wind Harmer
2.326
958711AF2-162 GEN
Solar/Wind Harmer
0.487
970289AG2-191 GEN
Solar/Wind Harmer
0.913
270444AC2-157 GEN1
Solar/Wind Harmer
2.615
270445AC2-157 GEN2
Solar/Wind Harmer
2.615
24729505KEY G4
Adder
2.912
24803006KYGER 3HP
50/50
4.111
24802806KYGER 2HP
50/50
4.096
24802906KYGER 2LP
50/50
2.404
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.278
25183208HLCRTG
Solar/Wind Harmer
6.23
25194408D.CRK1
Adder
7.356
25194508D.CRK3
Adder
1.375
962581AG1-107 GEN
Solar/Wind Harmer
4.188
961491AF2-440 GEN
Solar/Wind Harmer
1.741
270269AC2-059
Solar/Wind Harmer
7.708
253415AE1-040 GEN
Solar/Wind Harmer
0.902
972043AH1-570 GEN
Solar/Wind Harmer
1.969
972045AH1-571 GEN
Solar/Wind Harmer
1.575
253370AE2-315 SEC1
Adder
1.521
971125AH1-004 GEN
Solar/Wind Harmer
3.019
970107AG2-081 GEN
Solar/Wind Harmer
2.264
25322209TAIT E
Adder
7.143
25322209TAIT E
Adder
6.983
253349AC2-067 GEN
Solar/Wind Harmer
1.471
253400AC2-068 GEN
Solar/Wind Harmer
0.592
25326109MON D
Adder
0.938
942891AE2-308 GEN
Solar/Wind Harmer
6.839
926881AC1-175 GEN
Solar/Wind Harmer
3.444
270383AD1-128 GEN
Solar/Wind Harmer
3.706
970883AG2-550 GEN
Solar/Wind Harmer
5.919
970885AG2-551 GEN
Solar/Wind Harmer
1.376
964571AG1-320 GEN
Solar/Wind Harmer
4.676
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
2.759
24725505WLD G2 C
Solar/Wind Harmer
2.091
24699105WLD G1 C
Solar/Wind Harmer
2.066
270031AE2-169
Solar/Wind Harmer
4.18
270599AE1-208 GEN
Solar/Wind Harmer
4.18
25326509SID D
Adder
0.657
944541AF1-119 GEN
Solar/Wind Harmer
2.017
960971AF2-388 GEN
Solar/Wind Harmer
5.265
339236AF1-050_GEN
Solar/Wind Harmer
0.874
970291AG2-192 GEN
Solar/Wind Harmer
0.625
970291AG2-192 GEN
Solar/Wind Harmer
0.201
253378AE2-206_GEN
Solar/Wind Harmer
1.665
339231AF1-038_GEN
Solar/Wind Harmer
0.837
942221AE2-234 GEN
Solar/Wind Harmer
1.574
945391AF1-204 GEN
Solar/Wind Harmer
6.245
964781AG1-341 GEN
Solar/Wind Harmer
4.704
237033AB1-150 GEN
Solar/Wind Helper
0.445
24803106KYGER 3LP
50/50
2.421
24803306KYGER 4LP
50/50
2.371
971191AH1-055 GEN
Solar/Wind Harmer
71.356
252507AC2-088 GEN
Solar/Wind Harmer
1.948
252519AF1-045_GEN
Solar/Wind Harmer
3.681
25194608D.CRK4
Adder
1.599
252524AE2-267 GEN
Solar/Wind Harmer
1.53
25196608WSDLE5
Adder
8.33
253317AC1-085 GEN4
Solar/Wind Harmer
8.083
946181AF1-283 GEN
Solar/Wind Harmer
12.551
958171AF2-111 GEN
Solar/Wind Harmer
23.332
25196008MFTGT1
Adder
1.239
253394AE2-221_GEN
Solar/Wind Harmer
4.108
972167AH1-666 GEN
Solar/Wind Harmer
7.022
270367AC2-061_GEN
Solar/Wind Harmer
2.716
270186AC1-089 GEN
Solar/Wind Harmer
5.151
339243AC2-075 GEN1
Solar/Wind Harmer
0.373
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.521
253371AE2-315 SEC2
Adder
1.438
960071AF2-298 GEN
Solar/Wind Harmer
1.095
3429391JKCT 9G
Adder
5.993
970093AG2-073 GEN
Solar/Wind Harmer
3.456
24379505HDWTR1G C
Solar/Wind Harmer
4.879
270240V3-007_GEN2
Solar/Wind Harmer
3.817
970455AG2-298 GEN
Solar/Wind Harmer
2.065
24728505AND G1
Adder
2.175
253325AC1-069 GEN
Solar/Wind Harmer
0.588
270004AE1-209 GEN
Solar/Wind Harmer
3.065
946031AF1-268 GEN
Solar/Wind Harmer
4.614
970825AG2-519 GEN
Solar/Wind Harmer
3.112
970653AG2-424 GEN
Solar/Wind Harmer
0.383
962031AG1-047 GEN
Solar/Wind Harmer
1.623
957741AF2-068 GEN
Solar/Wind Harmer
8.053
339206AE1-143 GEN
Solar/Wind Harmer
1.133
270518AE2-148 GEN
Solar/Wind Harmer
6.079
965461AG1-414 GEN
Solar/Wind Harmer
1.089
970289AG2-191 GEN
Solar/Wind Harmer
0.369
972273AH1-721 GEN
Adder
39.657
276820AF1-078_GEN
Solar/Wind Harmer
0.74
247642Z2-115 C
Solar/Wind Harmer
0.03
970193AG2-126 GEN
Solar/Wind Harmer
6.722
339255AE2-071 GEN
Solar/Wind Harmer
0.524
339250AF1-203 GEN
Solar/Wind Harmer
0.27
944531AF1-118 GEN
Solar/Wind Harmer
15.299
270330AC1-082 GEN2
Solar/Wind Helper
0.209
270329AC1-082 GEN1
Solar/Wind Helper
0.209
24803406KYGER 5HP
50/50
4.064
24803206KYGER 4HP
50/50
4.055
252516AE2-318_GEN
Solar/Wind Harmer
10.115
25196808ZIMRHP
Adder
75.568
25194608D.CRK4
Adder
1.599
252510AF1-249 C
Solar/Wind Harmer
0.405
253316AC1-085 GEN3
Solar/Wind Harmer
8.083
946171AF1-282 GEN
Solar/Wind Harmer
9.655
25196008MFTGT1
Adder
1.28
253398AE2-221_GEN2
Solar/Wind Harmer
4.108
945681AF1-233 GEN
Solar/Wind Harmer
16.478
270273AD2-016 GEN
Solar/Wind Harmer
2.198
339221AD2-048_GEN
Solar/Wind Harmer
1.239
253370AE2-315 SEC1
Adder
1.521
253371AE2-315 SEC2
Adder
1.438
270222AC2-111 GEN
Solar/Wind Harmer
3.377
944031AF1-071 GEN
Solar/Wind Harmer
0.76
943111AE2-339 GEN
Solar/Wind Harmer
0.662
25326309TAIT D
Adder
0.802
3429421JKCT 10G
Adder
5.993
3429241JKCT 3G
Adder
8.267
942081AE2-220 GEN
Solar/Wind Harmer
3.946
270209AC1-174_GEN
Solar/Wind Harmer
2.511
270437AC2-090 C
Solar/Wind Harmer
3.444
270239V3-007_GEN1
Solar/Wind Harmer
1.062
339211AE2-254 GEN
Solar/Wind Harmer
0.905
24728605AND G2
Adder
2.175
253333AC1-068 GEN
Solar/Wind Harmer
0.588
270005AE1-210 C O1
Solar/Wind Harmer
3.065
970825AG2-519 GEN
Solar/Wind Harmer
1.159
970653AG2-424 GEN
Solar/Wind Harmer
2.647
945371AF1-202 GEN
Solar/Wind Harmer
3.579
276903AD2-071 C
Solar/Wind Harmer
5.115
339241AF1-083 GEN
Solar/Wind Harmer
0.85
270594AE1-207 GEN
Solar/Wind Harmer
6.778
270032AE2-172
Solar/Wind Harmer
2.321
958861AF2-177 GEN
Solar/Wind Harmer
5.382
970091AG2-072 GEN
Adder
37.724
270024AE2-089 GEN
Solar/Wind Harmer
2.267
965651AG1-433 GEN
Solar/Wind Harmer
2.633
964901AG1-354 GEN
Solar/Wind Harmer
7.156
960001AF2-291 GEN
Solar/Wind Helper
1.773
270331AC1-082 GEN3
Solar/Wind Helper
0.208
235780M24_1
Solar/Wind Helper
0.552
LAGNLTFEXP_LAGN->PJM
CLTF
5.253
TVALTFEXP_TVA->PJM
CLTF
2.588
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.217
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.528
MECLTFEXP_MEC->PJM
CLTF
5.794
SIGELTFEXP_SIGE->PJM
CLTF
0.282
NYPJM->LTFIMP_NY
CLTF
1.332
LGEELTFEXP_LGEE->PJM
CLTF
4.629
WECLTFEXP_WEC->PJM
CLTF
1.307
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.235
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.728

Details for 2GREEN CO-2GRENSBRG KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_GRE-AF1-083161_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2GREEN CO-2GRENSBRG KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_GRE-AF1-083161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.58 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:67.04
MW Contribution:
2.72
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2GREEN CO-2GRENSBRG KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_GRE-AF1-083161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.34 %
Rating:66.0 MVA
Rating Type:B
MVA to Mitigate:68.2
MW Contribution:
2.72
Bus #Bus NameTypeMW Contribution
970653AG2-424 GEN
Solar/Wind Harmer
0.467
339206AE1-143 GEN
Solar/Wind Helper
0.862
970653AG2-424 GEN
Solar/Wind Harmer
2.252
964901AG1-354 GEN
Solar/Wind Harmer
6.63
339241AF1-083 GEN
Solar/Wind Helper
0.304
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.025
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.051
LAGNLTFEXP_LAGN->PJM
CLTF
0.399
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.28
TVALTFEXP_TVA->PJM
CLTF
0.271
VTFLTFEXP_VFT->PJM
CMTX
0.032
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.758
MECLTFEXP_MEC->PJM
CLTF
0.127
SIGELTFEXP_SIGE->PJM
CLTF
0.001
WECLTFEXP_WEC->PJM
CLTF
0.013
G-007ALTFEXP_G-007A->PJM
CMTX
0.012
CPLELTFEXP_CPLE->PJM
CLTF
0.076
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.014
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.795

Details for 2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line l/o EKPC_P2-2_KU HODG 69_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_KU HODG 69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.61 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:53.3
MW Contribution:
3.12
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_KU HODG 69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.98 %
Rating:50.0 MVA
Rating Type:B
MVA to Mitigate:56.99
MW Contribution:
3.15
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Harmer
1.435
970653AG2-424 GEN
Solar/Wind Harmer
0.394
972273AH1-721 GEN
Adder
8.927
339241AF1-083 GEN
Solar/Wind Harmer
1.026
970653AG2-424 GEN
Solar/Wind Harmer
2.725
964901AG1-354 GEN
Solar/Wind Harmer
5.9
950011AG9-010
External Queue
10.121600151062012
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
0.397
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.36
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.277
VTFLTFEXP_VFT->PJM
CMTX
0.039
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.693
MECLTFEXP_MEC->PJM
CLTF
0.078
WECLTFEXP_WEC->PJM
CLTF
0.001
G-007ALTFEXP_G-007A->PJM
CMTX
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.099
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.516

Details for [AG2-424] 2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG2-424 TP-2MAGNOLIA-69_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG2-424 TP-2MAGNOLIA-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:157.14 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:61.28
MW Contribution:
63.25
IPD Plant:AG2-424
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG2-424 TP-2MAGNOLIA-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.98 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:61.22
MW Contribution:
63.25
IPD Plant:AG2-424
Bus #Bus NameTypeMW Contribution
970653AG2-424 GEN
PJM_IPD_GROUP
48.25
970653AG2-424 GEN
PJM_IPD_GROUP
15

Details for [AG2-424] 2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line l/o EKPC_P2-2_KU HODG 69_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_KU HODG 69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:144.51 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:56.36
MW Contribution:
63.25
IPD Plant:AG2-424
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_KU HODG 69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:143.8 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:56.08
MW Contribution:
63.25
IPD Plant:AG2-424
Bus #Bus NameTypeMW Contribution
970653AG2-424 GEN
PJM_IPD_GROUP
48.25
970653AG2-424 GEN
PJM_IPD_GROUP
15

Details for 2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line l/o EKPC_P2-3_GREEN W45-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_GREEN W45-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.88 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:44.02
MW Contribution:
15.5
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_GREEN W45-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.78 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:43.2
MW Contribution:
15.49
Bus #Bus NameTypeMW Contribution
970653AG2-424 GEN
Solar/Wind Harmer
1.958
970455AG2-298 GEN
Solar/Wind Harmer
1.729
964571AG1-320 GEN
Solar/Wind Harmer
4.406
970653AG2-424 GEN
Solar/Wind Harmer
13.538
950031AG9-013
External Queue
2.0728914737701416
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.201
SIGELTFEXP_SIGE->PJM
CLTF
0.01
NYPJM->LTFIMP_NY
CLTF
0.003
LGEELTFEXP_LGEE->PJM
CLTF
0.114
WECLTFEXP_WEC->PJM
CLTF
0.007
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.045
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for [AG2-424] 2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line l/o EKPC_P2-3_GREEN W45-1014_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_GREEN W45-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.24 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:40.66
MW Contribution:
20.64
IPD Plant:AG2-424
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_GREEN W45-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.15 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:39.84
MW Contribution:
20.63
IPD Plant:AG2-424
Bus #Bus NameTypeMW Contribution
970653AG2-424 GEN
PJM_IPD_GROUP
15.742
970653AG2-424 GEN
PJM_IPD_GROUP
4.894

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:196.67 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:544.77
MW Contribution:
2.65
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.17
971485AH1-239 GEN
Solar/Wind Harmer
12.338
966021AG1-471 GEN
Solar/Wind Harmer
8.255
339231AF1-038_GEN
Solar/Wind Harmer
2.312
339236AF1-050_GEN
Solar/Wind Harmer
1.637
964781AG1-341 GEN
Solar/Wind Harmer
8.957
3429031COOPER2 G
50/50
5.924
972273AH1-721 GEN
50/50
363.261
339206AE1-143 GEN
Solar/Wind Harmer
2.391
339255AE2-071 GEN
Solar/Wind Harmer
1.036
339250AF1-203 GEN
Solar/Wind Harmer
0.533
970653AG2-424 GEN
Solar/Wind Harmer
0.335
339241AF1-083 GEN
Solar/Wind Harmer
1.642
964901AG1-354 GEN
Solar/Wind Harmer
13.431
339211AE2-254 GEN
Solar/Wind Harmer
0.738
970653AG2-424 GEN
Solar/Wind Harmer
2.314
950011AG9-010
External Queue
9.896462440490723
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
1.46
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.515
TVALTFEXP_TVA->PJM
CLTF
1.072
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.927
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.18
MECLTFEXP_MEC->PJM
CLTF
0.521
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.067
WECLTFEXP_WEC->PJM
CLTF
0.058
CPLELTFEXP_CPLE->PJM
CLTF
0.097
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.21
CONTINGENCY 'AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 1           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 2           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AEP_P4_#3149_05HANG R 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242924 TO BUS 242927 CKT 1   /*05HANG R     765.0 - 05MARQUI     765.0
 OPEN BRANCH FROM BUS 242927 TO BUS 242938 CKT 1   /*05MARQUI     765.0 - 05MARQUI     345.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#1558_05BAKER 765_Q_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#309_05HANG R 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#1560_05BAKER 765_Q2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242523 CKT 1   /*05BAKER      765.0 - 05BAKER      345.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P2-2_#6156_05MARQUI 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 242927 CKT 1   /*05HANG R     765.0 - 05MARQUI     765.0
 OPEN BRANCH FROM BUS 242927 TO BUS 242938 CKT 1   /*05MARQUI     765.0 - 05MARQUI     345.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P2-2_#6763_05BIERSR 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243454 TO BUS 246888 CKT 1   /*05BIXBY      345.0 - 05BIERSR     345.0
END
CONTINGENCY 'AEP_P2-2_#308_05CULLOD 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
END
CONTINGENCY 'AEP_P7-1_#11019___SRT-A-2'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 944530 TO BUS 243232 CKT 2   /*AF1-118 TP   345.0 - 05SORENS     345.0
END
CONTINGENCY '34569 34598 34524_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 249578 CKT 1   /*08FOSTER     345.0 - 08HILCRT     345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT5_SRT-SL'
 OPEN BRANCH FROM BUS 235851 TO BUS 235850 CKT 1                /*01NTHLNV     500.0 - 01LONGVIEW   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235111 TO BUS 235851 CKT 1 /*01 502 J     500.0 - 01NTHLNV     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235851 TO BUS 235106 CKT 1 /*01NTHLNV     500.0 - 01FMARTN     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235111 TO BUS 235851 CKT 1 /*01 502 J     500.0 - 01NTHLNV     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235851 TO BUS 235106 CKT 1 /*01NTHLNV     500.0 - 01FMARTN     500.0
END
CONTINGENCY 'AEP_P2-2_#316_05AMOS 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242508 TO BUS 290927 CKT 5    /*05AMOS       765.0 - 05AMOS 5EQ     1.0
 OPEN BRANCH FROM BUS 242522 TO BUS 247504 CKT Z5   /*05AMOS       345.0 - 05AMOS_5_XFL 345.0
 OPEN BRANCH FROM BUS 247504 TO BUS 290927 CKT 5    /*05AMOS_5_XFL 345.0 - 05AMOS 5EQ     1.0
 OPEN BRANCH FROM BUS 290927 TO BUS 290928 CKT 5    /*05AMOS 5EQ     1.0 - 05AMOS T5     34.5
END
CONTINGENCY 'EKPC_P1-2_GRE-AF1-083161_SRT-A'
 OPEN BRANCH FROM BUS 342733 TO BUS 342817 CKT 1   /*5GREEN CO    161.0 - 5TAYLOR CO J 161.0
 OPEN BUS 325921                                   /*5TAYLOR CO   161.0
 OPEN BUS 342817                                   /*5TAYLOR CO J 161.0
END
CONTINGENCY 'EKPC_P2-2_KU HODG 69_SRT-A'
 OPEN BUS 341632   /*2HODGENVILLE  69.0
END
CONTINGENCY 'EKPC_P1-2_AG2-424 TP-2MAGNOLIA-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 970652 TO BUS 341800 CKT 1   /*AG2-424 TP    69.0 - 2MAGNOLIA     69.0
END
CONTINGENCY 'EKPC_P2-3_GREEN W45-1014_SRT-A'
 OPEN BUS 325921   /*5TAYLOR CO   161.0
 OPEN BUS 342733   /*5GREEN CO    161.0
 OPEN BUS 342817   /*5TAYLOR CO J 161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS'
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 1   /*5ALCALDE     161.0 - AH1-721 TP   161.0
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 2   /*5ALCALDE     161.0 - AH1-721 TP   161.0
END
290610 to 242512 ckt Z1
242514 to 290610 ckt 1
248005 to 242528 ckt 1
341563 to 324554 ckt 1
324736 to 341935 ckt 1
342325 to 341563 ckt 1
342718 to 324141 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.18 %2320.0B2486.65
3.06
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC104.78 %2320.0B2430.97
2.25
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
4.11
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC115.66 %3610.0B4175.28
5.61
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC115.4 %3610.0B4165.98
5.59
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC115.26 %3610.0B4160.96
5.58
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC114.94 %3610.0B4149.41
5.59
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC117.27 %5523.0B6477.04
7.6
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC116.4 %5523.0B6428.58
5.59
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.72 %5523.0B6225.55
7.67
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC111.96 %5523.0B6183.32
6.1
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC109.18 %4558.0A4976.63
4.34
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.41 %5523.0B5987.66
7.14
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.46 %5523.0B5935.05
6.54
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.76 %5523.0B5896.19
5.25
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC105.86 %5523.0B5846.6
6.47
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC101.88 %5523.0B5626.94
6.54
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC153.59 %1540.0B2365.35
3.44
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC141.94 %1540.0B2185.8
2.49
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC133.27 %1540.0B2052.4
2.5
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC107.31 %1540.0B1652.5
2.98
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC102.96 %1540.0B1585.6
3.01
GD2EKPC/LGEE
4MARION CO-4LEBANON 138.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC106.8 %220.0B234.95
3.2
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC250.49 %277.0B693.86
3.12
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC250.48 %277.0B693.83
3.12
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC250.47 %277.0B693.79
3.12
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC250.35 %277.0B693.48
3.13
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC250.29 %277.0B693.3
3.12
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC240.63 %277.0B666.55
2.3
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC238.58 %219.0A522.49
1.94
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-2
SingleAC225.99 %277.0B626.0
2.31
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_BULL 161 DBL_SRT-A
TowerAC198.95 %277.0B551.09
2.75
GD2EKPC
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC106.57 %220.0B234.46
3.2
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1445_ZIMMER_SRT-A
BreakerAC107.55 %1532.0B1647.65
5.31
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1449_ZIMMER_SRT-A
BreakerAC107.43 %1532.0B1645.79
5.31
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC106.98 %1532.0B1638.99
5.06
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1373_PORTUNION_SRT-A
BreakerAC106.14 %1532.0B1626.02
4.97
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1493_RED BANK_SRT-A
BreakerAC105.1 %1532.0B1610.06
4.83
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1487_RED BANK_SRT-A
BreakerAC105.05 %1532.0B1609.33
4.83
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
TowerAC104.96 %1532.0B1608.02
4.83
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
BusAC104.95 %1532.0B1607.79
4.83
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Base Case
SingleAC104.93 %1240.0A1301.17
3.47
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
EKPC_P2-2_MELD-SPUR 345_SRT-A
BusAC103.1 %1532.0B1579.46
5.33
GD2EKPC
AG2-298 TP-2LORETTO 69.0 kV Ckt 1 line
EKPC_P2-2_BARDIT-EBARD69_SRT-A
BusAC100.08 %46.0B46.04
3.31

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.18 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2486.65
MW Contribution:
3.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971277AH1-098 GEN
Solar/Wind Harmer
3.312
24728205BUCHG1
Adder
3.63
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
966021AG1-471 GEN
Solar/Wind Harmer
3.282
971485AH1-239 GEN
Solar/Wind Harmer
4.84
339231AF1-038_GEN
Solar/Wind Harmer
1.081
964781AG1-341 GEN
Solar/Wind Harmer
6.17
339236AF1-050_GEN
Solar/Wind Harmer
1.045
970563AG2-360 GEN
50/50
26.903
943031AE2-326 GEN
Solar/Wind Harmer
3.912
962751AG1-124 GEN
Solar/Wind Harmer
9.059
960911AF2-382 GEN
Solar/Wind Harmer
5.846
971461AH1-227 GEN
Solar/Wind Harmer
3.852
972103AH1-617 GEN
Solar/Wind Harmer
13.916
972273AH1-721 GEN
Adder
50.356
339255AE2-071 GEN
Solar/Wind Harmer
0.685
339250AF1-203 GEN
Solar/Wind Harmer
0.353
339206AE1-143 GEN
Solar/Wind Harmer
1.218
24686405CER G5
Adder
4.71
970093AG2-073 GEN
Solar/Wind Harmer
2.932
970653AG2-424 GEN
Solar/Wind Harmer
0.386
270030AE2-140 GEN
Solar/Wind Harmer
10.987
970455AG2-298 GEN
Solar/Wind Harmer
1.905
3429391JKCT 9G
Adder
4.482
339243AC2-075 GEN1
Solar/Wind Harmer
0.232
972167AH1-666 GEN
Solar/Wind Harmer
3.959
958171AF2-111 GEN
Solar/Wind Harmer
12.218
942481AE2-261 GEN
Solar/Wind Harmer
14.451
957381AF2-032 GEN
Solar/Wind Harmer
0.966
970193AG2-126 GEN
Solar/Wind Harmer
7.158
276785W4-005 GEN1
Solar/Wind Harmer
1.44
971993AH1-541 GEN
Solar/Wind Harmer
4.402
965931AG1-462 GEN
Solar/Wind Harmer
12.097
971087AG2-675 GEN
Solar/Wind Harmer
1.765
270186AC1-089 GEN
Solar/Wind Harmer
2.883
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.771
24728505AND G1
Adder
1.803
965091AG1-374 GEN
Solar/Wind Harmer
14.092
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
1.869
274878BISHOP HL;2U
Solar/Wind Harmer
1.582
24735105WLF2G1
Adder
4.907
24734705WLF1G3
Adder
4.896
24734805WLF1G4
Adder
4.896
24734905WLF1G5
Adder
4.896
966391AG1-508 GEN
Solar/Wind Harmer
2.783
971981AH1-535 GEN
Solar/Wind Harmer
7.894
971313AH1-133 GEN
Solar/Wind Harmer
4.584
970281AG2-184 GEN
Solar/Wind Harmer
14.612
962211AG1-066 GEN
Solar/Wind Harmer
1.641
270399AC1-101 GEN
Solar/Wind Harmer
2.774
270400AC1-102 GEN
Solar/Wind Harmer
2.774
957241AF2-018 GEN
Solar/Wind Harmer
2.859
270053AF1-130 C
Solar/Wind Harmer
11.424
3429211JKCT 2G
Adder
6.347
339216AC1-074 GEN
Solar/Wind Harmer
0.857
972163AH1-664 GEN
Solar/Wind Harmer
4.973
972165AH1-665 GEN
Solar/Wind Harmer
3.979
270444AC2-157 GEN1
Solar/Wind Harmer
2.733
270445AC2-157 GEN2
Solar/Wind Harmer
2.733
944221AF1-090 GEN
Solar/Wind Harmer
5.329
276763AC1-053 GEN1
Solar/Wind Harmer
1.887
276764AC1-053 GEN2
Solar/Wind Harmer
1.887
276668AB2-070 GEN1
Solar/Wind Harmer
1.055
276848AB2-070 GEN3
Solar/Wind Harmer
1.055
276849AB2-070 GEN2
Solar/Wind Harmer
1.055
946321AF1-296 GEN
Solar/Wind Harmer
4.94
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
274853TWINGROVE;U1
Solar/Wind Harmer
3.384
274854TWINGROVE;U2
Solar/Wind Harmer
3.313
274877BISHOP HL;1U
Solar/Wind Harmer
1.582
276741O09 GEN1
Solar/Wind Harmer
1.676
972267AH1-718 GEN
Adder
1.953
276726Z2-087_GEN
Solar/Wind Harmer
3.696
959341AF2-225 GEN
Solar/Wind Harmer
7.012
971681AH1-341 GEN
Solar/Wind Harmer
7
274856ECOGROVE ;U1
Solar/Wind Harmer
1.571
276611AD2-172 GEN
Solar/Wind Harmer
1.192
276612AE2-035 GEN
Solar/Wind Harmer
1.192
274823ROCKFORD ;21
Adder
9.053
926823AC1-168 GEN
Solar/Wind Harmer
1.997
963841AG1-237 GEN
Solar/Wind Harmer
5.074
971171AH1-044 GEN
Solar/Wind Harmer
9.281
970169AG2-114 GEN
Solar/Wind Harmer
4.633
276861AD2-134 GEN
Solar/Wind Harmer
0.827
276863AD2-134 GEN
Solar/Wind Harmer
0.827
971675AH1-338 GEN
Solar/Wind Harmer
8.334
971411AH1-196 GEN
Solar/Wind Harmer
6.945
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
24735205WLF2G2
Adder
4.907
24728305BUCHG2
Adder
3.63
971687AH1-348 GEN
Solar/Wind Harmer
0.746
971403AH1-188 GEN
Solar/Wind Harmer
9.183
944971AF1-162 GEN
Solar/Wind Harmer
4.503
24723205RIVRG3
Adder
11.612
270336AE1-100 GEN
Solar/Wind Harmer
1.01
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
8.649
339241AF1-083 GEN
Solar/Wind Harmer
0.951
24686505CER G6
Adder
4.748
339211AE2-254 GEN
Solar/Wind Harmer
0.852
970653AG2-424 GEN
Solar/Wind Harmer
2.669
3429241JKCT 3G
Adder
6.43
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.667
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
339221AD2-048_GEN
Solar/Wind Harmer
0.786
970091AG2-072 GEN
Adder
38.065
945681AF1-233 GEN
Solar/Wind Harmer
9.341
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
2.987
276686W4-005 GEN3
Solar/Wind Harmer
1.44
25196008MFTGT1
Adder
0.654
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
3.029
276708O09 GEN2
Solar/Wind Harmer
1.676
276646AC1-214 GEN2
Solar/Wind Harmer
0.626
25196808ZIMRHP
Adder
35.505
276655WTG1_EQ
Solar/Wind Harmer
4.08
276656WTG2_EQ
Solar/Wind Harmer
0.54
939741AE1-205 GEN
Solar/Wind Harmer
9.349
274858EASY ROAD;U2
Solar/Wind Harmer
2.239
274761LEE CO EC;2U
Adder
4.348
274766LEE CO EC;7U
Adder
4.297
963741AG1-226 GEN
Solar/Wind Harmer
21.023
970819AG2-516 GEN
Solar/Wind Harmer
5.587
274822ROCKFORD ;11
Adder
9.119
970569AG2-363 GEN
Solar/Wind Harmer
13.937
957471AF2-041 GEN
Solar/Wind Harmer
13.921
959081AF2-199 GEN
Solar/Wind Harmer
4.64
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274828WAUKEGAN ;BP
Adder
5.078
25196508WSDLE4
Adder
3.893
274744AC1-111 GEN8
Adder
2.557
274746AC1-111 G10
Adder
2.557
274728ELWOOD EC;5P
Adder
7.484
942891AE2-308 GEN
Solar/Wind Harmer
5.443
964571AG1-320 GEN
Solar/Wind Harmer
4.43
971125AH1-004 GEN
Solar/Wind Harmer
2.108
970107AG2-081 GEN
Solar/Wind Harmer
1.581
972043AH1-570 GEN
Solar/Wind Harmer
1.293
972045AH1-571 GEN
Solar/Wind Harmer
1.034
276916AD2-100_GEN
Solar/Wind Harmer
10.169
276911AD2-131_GEN
Solar/Wind Harmer
2.055
276615X2-022 GEN
Solar/Wind Harmer
0.938
276838X2-022 GEN2
Solar/Wind Harmer
0.111
945391AF1-204 GEN
Solar/Wind Harmer
6.651
274880W4-005 GEN4
Solar/Wind Harmer
1.44
276174W4-005 GEN2
Solar/Wind Harmer
1.44
960611AF2-352 GEN
Solar/Wind Harmer
1.092
276158O29GEN2
Solar/Wind Harmer
2.347
276157O29GEN1
Solar/Wind Harmer
1.785
276645AC1-214 GEN1
Solar/Wind Harmer
0.626
942111AE2-223 GEN
Solar/Wind Harmer
3.832
274764LEE CO EC;5U
Adder
4.358
274765LEE CO EC;6U
Adder
4.358
274762LEE CO EC;3U
Adder
4.348
274763LEE CO EC;4U
Adder
4.307
970241AG2-163 GEN
Solar/Wind Harmer
11.68
938861AE1-114 GEN
Solar/Wind Harmer
3.826
972235AH1-702 GEN1
Adder
1.172
972236AH1-702 GEN2
Adder
1.019
971341AH1-150 GEN
Solar/Wind Harmer
9.281
971343AH1-151 GEN
Solar/Wind Harmer
9.281
252509AD1-136 GEN
Solar/Wind Harmer
0.119
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
25194508D.CRK3
Adder
0.65
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.064
274697ROCKY RD ;3P
Adder
1.389
24728805RICHG1
Adder
1.729
24728905RICHG2
Adder
1.729
274674JOLIET 9 ;6U
Adder
7.01
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
237061AD1-155 GEN
Solar/Wind Helper
0.84
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238147AE2-230_GEN1
Solar/Wind Helper
0.214
238148AE2-230_GEN2
Solar/Wind Helper
0.214
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316312AB1-027
Solar/Wind Helper
0.234
316097T157 G90
Solar/Wind Helper
0.557
316045AC1-158 PL2
Solar/Wind Helper
2.117
316450AC1-158 RIC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.609
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
276872AE1-163_GEN1
Solar/Wind Harmer
0.072
276876AE1-163_GEN2
Solar/Wind Harmer
0.072
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
274735ELWOOD EC;4P
Adder
7.484
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
315616AA1-038_C
Solar/Wind Helper
1.809
3148463FAIRFLD
Solar/Wind Helper
0.399
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316258AE1-075 C
Solar/Wind Helper
0.181
316405AF2-144 C
Solar/Wind Helper
0.151
316164AC1-076 GEN
Solar/Wind Helper
0.62
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.113
276889AE2-281 GEN
Solar/Wind Harmer
0.021
274851PROVIDENC;RU
Solar/Wind Harmer
1.332
274849CRESCENT ;1U
Solar/Wind Harmer
0.865
276603SUBLETTE C
Solar/Wind Harmer
0.49
274857EASY ROAD;U1
Solar/Wind Harmer
2.239
274760LEE CO EC;1U
Adder
4.348
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
270367AC2-061_GEN
Solar/Wind Harmer
1.479
970571AG2-364 GEN
Solar/Wind Harmer
9.291
959091AF2-200 GEN
Solar/Wind Harmer
9.281
252507AC2-088 GEN
Solar/Wind Harmer
0.831
274855GSG-6 ;RU
Solar/Wind Harmer
1.71
274850MENDOTA H;RU
Solar/Wind Harmer
1.189
276602WESTBROOK C
Solar/Wind Harmer
0.984
276799AD1-013 GEN
Solar/Wind Harmer
1.023
946671AF1-331 GEN
Solar/Wind Harmer
0.194
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
25196608WSDLE5
Adder
3.933
274729ELWOOD EC;1P
Adder
7.484
274730ELWOOD EC;6P
Adder
7.484
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
5.57
3147983MERCK5
Solar/Wind Helper
0.108
316192AB2-158 GEN
Solar/Wind Helper
0.989
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
3146776BUCKING
Solar/Wind Helper
0.05
238152AF2-075_GEN
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.173
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.959
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
274745AC1-111 GEN9
Adder
2.557
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
274676JOLIET 29;8U
Adder
13.963
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
23583801GRNGAP
Solar/Wind Helper
2.128
316095T157 G97
Solar/Wind Helper
0.557
316075AC2-137 C
Solar/Wind Helper
0.18
316223AC1-118
Solar/Wind Helper
0.174
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2430.97
MW Contribution:
2.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24735105WLF2G1
50/50
5.207
24734705WLF1G3
50/50
5.196
24734805WLF1G4
50/50
5.196
24734905WLF1G5
50/50
5.196
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.671
971313AH1-133 GEN
Solar/Wind Harmer
2.637
970281AG2-184 GEN
Solar/Wind Harmer
10.194
270399AC1-101 GEN
Solar/Wind Harmer
1.444
270400AC1-102 GEN
Solar/Wind Harmer
1.444
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
10.049
3429211JKCT 2G
Adder
6.347
339216AC1-074 GEN
Solar/Wind Harmer
0.095
972163AH1-664 GEN
Solar/Wind Harmer
3.863
972165AH1-665 GEN
Solar/Wind Harmer
3.094
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.131
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.131
946321AF1-296 GEN
Solar/Wind Harmer
1.85
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
274854TWINGROVE;U2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.109
276741O09 GEN1
Solar/Wind Harmer
0.116
972267AH1-718 GEN
Adder
1.953
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.424
971681AH1-341 GEN
Solar/Wind Harmer
5.242
274856ECOGROVE ;U1
Solar/Wind Harmer
0.076
274823ROCKFORD ;21
Adder
9.053
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.475
970169AG2-114 GEN
Solar/Wind Harmer
3.232
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276863AD2-134 GEN
Solar/Wind Harmer
0.058
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
25196508WSDLE4
Adder
3.893
274744AC1-111 GEN8
Adder
2.557
274746AC1-111 G10
Adder
2.557
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.499
970833AG2-524 GEN
Solar/Wind Harmer
2.333
274728ELWOOD EC;5P
Adder
7.484
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
274735ELWOOD EC;4P
Adder
7.484
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
960591AF2-350 GEN
Solar/Wind Harmer
3.162
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971611AH1-305 GEN
Solar/Wind Harmer
1.876
971985AH1-537 GEN
Solar/Wind Harmer
0.936
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
4.672
971609AH1-304 GEN
Solar/Wind Harmer
0.508
270543AE2-219 C
Solar/Wind Harmer
2.176
253406AD2-031_GEN
Solar/Wind Harmer
0.23
964611AG1-324 GEN
Solar/Wind Harmer
1.21
247536S-71 GEN
Solar/Wind Harmer
0.124
945581AF1-223 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
5.772
315616AA1-038_C
Solar/Wind Helper
1.809
3148463FAIRFLD
Solar/Wind Helper
0.399
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316258AE1-075 C
Solar/Wind Helper
0.181
316405AF2-144 C
Solar/Wind Helper
0.151
316164AC1-076 GEN
Solar/Wind Helper
0.62
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.113
24735205WLF2G2
50/50
5.207
24728305BUCHG2
Adder
3.63
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.407
944971AF1-162 GEN
Solar/Wind Harmer
4.503
24723205RIVRG3
Adder
11.612
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
6.034
24686505CER G6
Adder
4.748
970653AG2-424 GEN
Solar/Wind Harmer
1.862
3429241JKCT 3G
Adder
6.43
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.003
943811AF1-049 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
38.065
945681AF1-233 GEN
Solar/Wind Harmer
6.517
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
0.167
25196008MFTGT1
Adder
0.654
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.116
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
25196808ZIMRHP
Adder
35.505
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.566
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.348
274766LEE CO EC;7U
Adder
4.297
963741AG1-226 GEN
Solar/Wind Harmer
7.714
970819AG2-516 GEN
Solar/Wind Harmer
3.898
274822ROCKFORD ;11
Adder
9.119
970569AG2-363 GEN
Solar/Wind Harmer
9.723
957471AF2-041 GEN
Solar/Wind Harmer
9.712
959081AF2-199 GEN
Solar/Wind Harmer
3.237
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.689
276882AE2-255 GEN
Solar/Wind Harmer
0.375
962781AG1-127 GEN
Solar/Wind Harmer
3.062
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
0.568
276805AD2-038 GEN
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.024
252516AE2-318_GEN
Solar/Wind Harmer
3.594
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
939401AE1-172 GEN
Solar/Wind Harmer
2.397
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
274745AC1-111 GEN9
Adder
2.557
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
274676JOLIET 29;8U
Adder
13.963
276903AD2-071 C
Solar/Wind Harmer
3.542
941551AE2-152 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.159
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.314
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.938
270594AE1-207 GEN
Solar/Wind Harmer
3.528
270032AE2-172
Solar/Wind Harmer
2.1
970825AG2-519 GEN
Solar/Wind Harmer
1.115
270005AE1-210 C O1
Solar/Wind Harmer
0.68
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.068
958381AF2-132 GEN
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.5
958861AF2-177 GEN
Solar/Wind Harmer
1.334
965651AG1-433 GEN
Solar/Wind Harmer
0.9
270024AE2-089 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
23583801GRNGAP
Solar/Wind Helper
2.128
316095T157 G97
Solar/Wind Helper
0.557
970563AG2-360 GEN
50/50
26.903
24689505VACITY
50/50
3.164
943031AE2-326 GEN
Solar/Wind Harmer
3.912
962751AG1-124 GEN
Solar/Wind Harmer
6.205
960911AF2-382 GEN
Solar/Wind Harmer
4.078
971461AH1-227 GEN
Solar/Wind Harmer
2.687
972103AH1-617 GEN
Solar/Wind Harmer
9.709
972273AH1-721 GEN
Adder
50.356
24686405CER G5
Adder
4.71
970093AG2-073 GEN
Solar/Wind Harmer
3.273
970653AG2-424 GEN
Solar/Wind Harmer
0.386
270030AE2-140 GEN
Solar/Wind Harmer
7.666
970455AG2-298 GEN
Solar/Wind Harmer
1.477
3429391JKCT 9G
Adder
4.482
972167AH1-666 GEN
Solar/Wind Harmer
2.762
958171AF2-111 GEN
Solar/Wind Harmer
8.524
942481AE2-261 GEN
Solar/Wind Harmer
10.082
957381AF2-032 GEN
Solar/Wind Harmer
0.764
970193AG2-126 GEN
Solar/Wind Harmer
4.994
971993AH1-541 GEN
Solar/Wind Harmer
1.535
965931AG1-462 GEN
Solar/Wind Harmer
8.44
971087AG2-675 GEN
Solar/Wind Harmer
1.765
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.771
24728505AND G1
Adder
1.803
965091AG1-374 GEN
Solar/Wind Harmer
9.832
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.109
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.348
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
270367AC2-061_GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.482
959091AF2-200 GEN
Solar/Wind Harmer
6.475
252507AC2-088 GEN
Solar/Wind Harmer
0.146
274855GSG-6 ;RU
Solar/Wind Harmer
0.118
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276868AE1-113 GEN
Solar/Wind Harmer
0.643
274879MINONK ;1U
Solar/Wind Harmer
0.134
24386205FR-12G C
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
1.674
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
25196608WSDLE5
Adder
3.933
274862TOP CROP ;2U
Solar/Wind Harmer
0.432
943121AE2-341 GEN
Solar/Wind Harmer
5.351
943591AF1-030 GEN
Solar/Wind Harmer
3.559
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.187
274729ELWOOD EC;1P
Adder
7.484
274730ELWOOD EC;6P
Adder
7.484
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
3.003
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.354
274887GEN-1.85
Solar/Wind Harmer
0.082
276843GEN-1.7
Solar/Wind Harmer
0.102
276806AD2-047 C O1
Solar/Wind Harmer
1.792
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
4.107
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970825AG2-519 GEN
Solar/Wind Harmer
2.365
270004AE1-209 GEN
Solar/Wind Harmer
0.68
946031AF1-268 GEN
Solar/Wind Harmer
2.979
964401AG1-302 GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
7.973
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.643
970191AG2-125 GEN
Solar/Wind Harmer
0.781
944531AF1-118 GEN
Solar/Wind Harmer
13.572
971347AH1-153 GEN
Solar/Wind Harmer
1.512
3147983MERCK5
Solar/Wind Helper
0.108
316192AB2-158 GEN
Solar/Wind Helper
0.989
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
3146776BUCKING
Solar/Wind Helper
0.05
238152AF2-075_GEN
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.18
316223AC1-118
Solar/Wind Helper
0.174
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.173
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.959
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
971277AH1-098 GEN
Solar/Wind Harmer
2.311
24728205BUCHG1
Adder
3.63
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
966021AG1-471 GEN
Solar/Wind Harmer
2.29
971485AH1-239 GEN
Solar/Wind Harmer
3.377
964781AG1-341 GEN
Solar/Wind Harmer
4.305
942891AE2-308 GEN
Solar/Wind Harmer
3.798
964571AG1-320 GEN
Solar/Wind Harmer
3.443
971125AH1-004 GEN
Solar/Wind Harmer
1.471
970107AG2-081 GEN
Solar/Wind Harmer
1.103
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.751
971587AH1-292 GEN
Solar/Wind Harmer
2.505
276916AD2-100_GEN
Solar/Wind Harmer
7.095
276911AD2-131_GEN
Solar/Wind Harmer
0.467
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.188
945391AF1-204 GEN
Solar/Wind Harmer
3.538
960611AF2-352 GEN
Solar/Wind Harmer
1.092
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.528
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274764LEE CO EC;5U
Adder
4.358
274765LEE CO EC;6U
Adder
4.358
274762LEE CO EC;3U
Adder
4.348
274763LEE CO EC;4U
Adder
4.307
970241AG2-163 GEN
Solar/Wind Harmer
1.901
938861AE1-114 GEN
Solar/Wind Harmer
1.845
972235AH1-702 GEN1
Adder
1.172
972236AH1-702 GEN2
Adder
1.019
971341AH1-150 GEN
Solar/Wind Harmer
6.475
971343AH1-151 GEN
Solar/Wind Harmer
6.475
252509AD1-136 GEN
Solar/Wind Harmer
0.016
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.643
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.815
25183208HLCRTG
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
25194508D.CRK3
Adder
0.65
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.064
274697ROCKY RD ;3P
Adder
1.389
958481AF2-142 GEN
Solar/Wind Harmer
4.795
24728805RICHG1
Adder
1.729
24728905RICHG2
Adder
1.729
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.01
276893AG1-478 C
Solar/Wind Harmer
0.212
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
0.184
276776AD2-060 GEN
Solar/Wind Harmer
0.337
958011AF2-095 GEN
Solar/Wind Harmer
4.553
970941AG2-585 GEN
Solar/Wind Harmer
1.739
926881AC1-175 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.41
970291AG2-192 GEN
Solar/Wind Harmer
0.189
971613AH1-306 GEN
Solar/Wind Harmer
1.512
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.712
270599AE1-208 GEN
Solar/Wind Harmer
2.854
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
3.108
970885AG2-551 GEN
Solar/Wind Harmer
1.036
964611AG1-324 GEN
Solar/Wind Harmer
0.233
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.205
960971AF2-388 GEN
Solar/Wind Harmer
1.8
965681AG1-436 GEN
Solar/Wind Harmer
3.818
965791AG1-447 GEN
Solar/Wind Harmer
2.8
942221AE2-234 GEN
Solar/Wind Harmer
1.218
970349AG2-230 GEN
Solar/Wind Harmer
4.536
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
237061AD1-155 GEN
Solar/Wind Helper
0.84
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238147AE2-230_GEN1
Solar/Wind Helper
0.214
238148AE2-230_GEN2
Solar/Wind Helper
0.214
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316312AB1-027
Solar/Wind Helper
0.234
316097T157 G90
Solar/Wind Helper
0.557
316045AC1-158 PL2
Solar/Wind Helper
2.117
316450AC1-158 RIC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.609
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
4.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971277AH1-098 GEN
Solar/Wind Harmer
5.174
942671AE2-283 GEN
Solar/Wind Harmer
5.792
970913AG2-568 GEN
Solar/Wind Harmer
7.67
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
12.886
958121AF2-106 GEN
Solar/Wind Harmer
0.001
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
941801AE2-185 GEN
Solar/Wind Harmer
7.447
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.535
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24686405CER G5
Adder
9.787
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
970093AG2-073 GEN
Solar/Wind Harmer
6.071
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.034
970455AG2-298 GEN
Solar/Wind Harmer
2.725
972167AH1-666 GEN
Solar/Wind Harmer
5.413
958171AF2-111 GEN
Solar/Wind Harmer
16.661
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
4.688
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
942481AE2-261 GEN
Solar/Wind Harmer
18.979
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
15.863
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
18.636
959611AF2-252 GEN
Solar/Wind Harmer
2.071
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
970571AG2-364 GEN
Solar/Wind Harmer
12.283
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946671AF1-331 GEN
Solar/Wind Harmer
0.653
270004AE1-209 GEN
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
4.603
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
276843GEN-1.7
Solar/Wind Harmer
0.195
276806AD2-047 C O1
Solar/Wind Harmer
3.42
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
6.744
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
270069AE2-166 C O1
Solar/Wind Harmer
10.375
971313AH1-133 GEN
Solar/Wind Harmer
5.363
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
2.889
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
970281AG2-184 GEN
Solar/Wind Harmer
18.909
971981AH1-535 GEN
Solar/Wind Harmer
5.838
971061AG2-657 GEN
Solar/Wind Harmer
5.362
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972163AH1-664 GEN
Solar/Wind Harmer
7.559
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
270356AE2-297 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.464
963841AG1-237 GEN
Solar/Wind Harmer
2.696
946321AF1-296 GEN
Solar/Wind Harmer
3.479
274854TWINGROVE;U2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.498
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
972267AH1-718 GEN
Adder
3.684
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
926823AC1-168 GEN
Solar/Wind Harmer
1.044
970169AG2-114 GEN
Solar/Wind Harmer
6.143
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
270263AC1-001 GEN
Solar/Wind Harmer
0.61
970073AG2-061 GEN
Solar/Wind Harmer
2.033
971029AG2-637 GEN
Solar/Wind Harmer
9.145
270543AE2-219 C
Solar/Wind Harmer
4.252
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
247536S-71 GEN
Solar/Wind Harmer
0.242
25306009OHH W.
Adder
2.5
971609AH1-304 GEN
Solar/Wind Harmer
0.988
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
964611AG1-324 GEN
Solar/Wind Harmer
2.357
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
3147312GRETNA
Solar/Wind Harmer
0.047
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
5.335
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
0.947
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
960001AF2-291 GEN
Solar/Wind Harmer
0
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
945681AF1-233 GEN
Solar/Wind Harmer
12.766
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
7.186
252510AF1-249 C
Solar/Wind Harmer
0.048
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
276621W2-048 GEN
Solar/Wind Harmer
0.315
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
253398AE2-221_GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24385905FR-11G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
970819AG2-516 GEN
Solar/Wind Harmer
7.371
970569AG2-363 GEN
Solar/Wind Harmer
18.425
274822ROCKFORD ;11
Adder
17.258
957471AF2-041 GEN
Solar/Wind Harmer
18.391
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
274745AC1-111 GEN9
Adder
4.865
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
941551AE2-152 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
7.838
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
964571AG1-320 GEN
Solar/Wind Harmer
6.355
971125AH1-004 GEN
Solar/Wind Harmer
2.78
970107AG2-081 GEN
Solar/Wind Harmer
2.085
972043AH1-570 GEN
Solar/Wind Harmer
1.794
972045AH1-571 GEN
Solar/Wind Harmer
1.437
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
4.796
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276916AD2-100_GEN
Solar/Wind Harmer
13.351
276911AD2-131_GEN
Solar/Wind Harmer
0.879
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960201AF2-311 GEN
Solar/Wind Harmer
5.7
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
938861AE1-114 GEN
Solar/Wind Harmer
3.487
270383AD1-128 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
970885AG2-551 GEN
Solar/Wind Harmer
2.025
276893AG1-478 C
Solar/Wind Harmer
0.404
274674JOLIET 9 ;6U
Adder
13.36
270031AE2-169
Solar/Wind Harmer
3.328
270599AE1-208 GEN
Solar/Wind Harmer
5.547
276897AD1-100 C
Solar/Wind Harmer
15.124
964611AG1-324 GEN
Solar/Wind Harmer
0.453
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
276776AD2-060 GEN
Solar/Wind Harmer
0.644
958011AF2-095 GEN
Solar/Wind Harmer
8.691
970941AG2-585 GEN
Solar/Wind Harmer
3.319
270201AC2-176 GEN
Solar/Wind Harmer
0
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.66 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4175.28
MW Contribution:
5.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.26
24684705SMG5
50/50
0.846
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.387
971329AH1-144 GEN
Solar/Wind Harmer
11.745
966391AG1-508 GEN
Solar/Wind Harmer
6.384
270197AD1-017 GEN1
Solar/Wind Harmer
2.542
270069AE2-166 C O1
Solar/Wind Harmer
14.894
971313AH1-133 GEN
Solar/Wind Harmer
9.348
24734705WLF1G3
Adder
8.213
24734805WLF1G4
Adder
8.213
24734905WLF1G5
Adder
8.213
24735105WLF2G1
Adder
8.042
270399AC1-101 GEN
Solar/Wind Harmer
5.575
270400AC1-102 GEN
Solar/Wind Harmer
5.575
941621AE2-160 GEN
Adder
4.304
957241AF2-018 GEN
Solar/Wind Harmer
5.778
270053AF1-130 C
Solar/Wind Harmer
23.086
970281AG2-184 GEN
Solar/Wind Harmer
27.213
971981AH1-535 GEN
Solar/Wind Harmer
12.593
962211AG1-066 GEN
Solar/Wind Harmer
3.011
971061AG2-657 GEN
Solar/Wind Harmer
11.048
3429211JKCT 2G
Adder
11.928
339216AC1-074 GEN
Solar/Wind Harmer
1.652
972163AH1-664 GEN
Solar/Wind Harmer
9.793
972165AH1-665 GEN
Solar/Wind Harmer
7.834
971985AH1-537 GEN
Solar/Wind Harmer
17.394
270444AC2-157 GEN1
Solar/Wind Harmer
5.263
270445AC2-157 GEN2
Solar/Wind Harmer
5.263
25196108MFTGT2
Adder
1.433
25196108MFTGT2
Adder
1.331
944221AF1-090 GEN
Solar/Wind Harmer
10.074
25196408WSDLE3
Adder
8.125
25196308WSDLE2
Adder
8.054
25196208WSDLE1
Adder
8.034
25196708WSDLE6
Adder
8.014
25196508WSDLE4
Adder
7.812
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.18
270583AD2-179 GEN
Solar/Wind Harmer
20.746
270214AC2-123 GEN
Solar/Wind Harmer
4.317
971277AH1-098 GEN
Solar/Wind Harmer
7.43
942671AE2-283 GEN
Solar/Wind Harmer
8.669
270013AE1-250 PV
Solar/Wind Harmer
3.251
970913AG2-568 GEN
Solar/Wind Harmer
9.375
971225AH1-072 GEN
Solar/Wind Harmer
2.738
971227AH1-073 GEN
Solar/Wind Harmer
2.738
24723005RIVRG1
Adder
23.046
24723105RIVRG2
Adder
23.046
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.774
971485AH1-239 GEN
Solar/Wind Harmer
8.528
339231AF1-038_GEN
Solar/Wind Harmer
1.925
964781AG1-341 GEN
Solar/Wind Harmer
11.012
339236AF1-050_GEN
Solar/Wind Harmer
1.88
942891AE2-308 GEN
Solar/Wind Harmer
10.222
964571AG1-320 GEN
Solar/Wind Harmer
8.222
971125AH1-004 GEN
Solar/Wind Harmer
4.008
970107AG2-081 GEN
Solar/Wind Harmer
3.006
253433AC1-085 GEN1
Solar/Wind Harmer
4.849
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
276763AC1-053 GEN1
Solar/Wind Harmer
3.586
276764AC1-053 GEN2
Solar/Wind Harmer
3.586
276668AB2-070 GEN1
Solar/Wind Harmer
2.006
276848AB2-070 GEN3
Solar/Wind Harmer
2.006
276849AB2-070 GEN2
Solar/Wind Harmer
2.006
270356AE2-297 GEN
Solar/Wind Harmer
4.168
253406AD2-031_GEN
Solar/Wind Harmer
1.153
270291AC1-194 GEN
Solar/Wind Harmer
4.567
963841AG1-237 GEN
Solar/Wind Harmer
9.807
946321AF1-296 GEN
Solar/Wind Harmer
9.347
274853TWINGROVE;U1
Solar/Wind Harmer
6.454
274854TWINGROVE;U2
Solar/Wind Harmer
6.319
270340AC2-060 GEN
Solar/Wind Harmer
2.703
276726Z2-087_GEN
Solar/Wind Harmer
7.058
959341AF2-225 GEN
Solar/Wind Harmer
13.389
972267AH1-718 GEN
Adder
3.707
274823ROCKFORD ;21
Adder
17.239
274744AC1-111 GEN8
Adder
4.896
274746AC1-111 G10
Adder
4.896
25306009OHH W.
Adder
2.518
274728ELWOOD EC;5P
Adder
14.355
274731ELWOOD EC;2P
Adder
14.355
274733ELWOOD EC;3P
Adder
14.355
274735ELWOOD EC;4P
Adder
14.355
253372AE2-315 SEC3
Adder
1.655
253372AE2-315 SEC3
Adder
1.655
274675JOLIET 29;7U
Adder
26.781
315616AA1-038_C
Solar/Wind Helper
3.299
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.846
316164AC1-076 GEN
Solar/Wind Helper
1.182
316258AE1-075 C
Solar/Wind Helper
0.321
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.093
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
3141426STAFORD
Solar/Wind Helper
0.049
24386405FR-21G C
Solar/Wind Harmer
2.921
24387005FR-3G C
Solar/Wind Harmer
2.686
972043AH1-570 GEN
Solar/Wind Harmer
2.487
972045AH1-571 GEN
Solar/Wind Harmer
1.989
927014AC1-188 GEN
Solar/Wind Harmer
1.537
962581AG1-107 GEN
Solar/Wind Harmer
4.757
961491AF2-440 GEN
Solar/Wind Harmer
1.977
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.603
971073AG2-665 GEN
Solar/Wind Harmer
7.39
970879AG2-548 GEN
Solar/Wind Harmer
1.074
25194408D.CRK1
Adder
6.977
25194508D.CRK3
Adder
1.304
945391AF1-204 GEN
Solar/Wind Harmer
12.785
276916AD2-100_GEN
Solar/Wind Harmer
19.251
276911AD2-131_GEN
Solar/Wind Harmer
3.891
276615X2-022 GEN
Solar/Wind Harmer
1.781
276838X2-022 GEN2
Solar/Wind Harmer
0.212
274880W4-005 GEN4
Solar/Wind Harmer
2.739
276174W4-005 GEN2
Solar/Wind Harmer
2.739
970241AG2-163 GEN
Solar/Wind Harmer
22.546
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
960251AF2-316 GEN
Solar/Wind Harmer
13.508
960201AF2-311 GEN
Solar/Wind Harmer
9.005
960611AF2-352 GEN
Solar/Wind Harmer
2.083
942111AE2-223 GEN
Solar/Wind Harmer
7.317
274764LEE CO EC;5U
Adder
8.284
274765LEE CO EC;6U
Adder
8.284
274762LEE CO EC;3U
Adder
8.264
274763LEE CO EC;4U
Adder
8.186
972235AH1-702 GEN1
Adder
2.231
972236AH1-702 GEN2
Adder
1.94
274683WAUKEGAN ;8U
Adder
18.516
274683WAUKEGAN ;8U
Adder
15.608
274696ROCKY RD ;4P
Adder
10.01
274695ROCKY RD ;2P
Adder
9.779
274693ROCKY RD ;1P
Adder
9.683
274697ROCKY RD ;3P
Adder
2.656
253370AE2-315 SEC1
Adder
1.749
274674JOLIET 9 ;6U
Adder
13.445
3132123MT JACKSON
Solar/Wind Helper
1.393
966001AG1-469 GEN
Solar/Wind Helper
0.321
237061AD1-155 GEN
Solar/Wind Helper
1.655
316097T157 G90
Solar/Wind Helper
1.135
238147AE2-230_GEN1
Solar/Wind Helper
0.426
238148AE2-230_GEN2
Solar/Wind Helper
0.426
238149AF1-291A_GEN
Solar/Wind Helper
0.122
316006AB2-029 C
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.356
316045AC1-158 PL2
Solar/Wind Helper
4.058
316450AC1-158 RIC
Solar/Wind Helper
0.338
966871AG1-558 GEN
Solar/Wind Helper
0.307
316312AB1-027
Solar/Wind Helper
0.426
24387305FR-4G C
Solar/Wind Harmer
3.45
970823AG2-518 GEN
50/50
8.391
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.212
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
15.01
970563AG2-360 GEN
50/50
45.925
970417AG2-272 GEN
50/50
3.737
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.417
943031AE2-326 GEN
Solar/Wind Harmer
6.794
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.813
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.976
270030AE2-140 GEN
Solar/Wind Harmer
30.957
270018AE2-047 C O1
Solar/Wind Harmer
1.823
960911AF2-382 GEN
Solar/Wind Harmer
10.976
270016AE1-250 BESS
Solar/Wind Harmer
3.251
971461AH1-227 GEN
Solar/Wind Harmer
7.023
970223AG2-152 GEN
Solar/Wind Harmer
17.677
972103AH1-617 GEN
Solar/Wind Harmer
25.917
24686405CER G5
Adder
9.839
270330AC1-082 GEN2
Solar/Wind Harmer
0.514
270329AC1-082 GEN1
Solar/Wind Harmer
0.514
972273AH1-721 GEN
Adder
89.66
24721905FLATG4
Adder
21.789
339255AE2-071 GEN
Solar/Wind Harmer
1.222
339250AF1-203 GEN
Solar/Wind Harmer
0.629
339206AE1-143 GEN
Solar/Wind Harmer
2.213
970093AG2-073 GEN
Solar/Wind Harmer
5.468
970653AG2-424 GEN
Solar/Wind Harmer
0.709
971191AH1-055 GEN
Solar/Wind Harmer
18.939
3429391JKCT 9G
Adder
8.441
970455AG2-298 GEN
Solar/Wind Harmer
3.536
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972167AH1-666 GEN
Solar/Wind Harmer
7.807
957541AF2-048 GEN
Solar/Wind Harmer
1.537
958171AF2-111 GEN
Solar/Wind Harmer
24.034
270186AC1-089 GEN
Solar/Wind Harmer
5.851
270367AC2-061_GEN
Solar/Wind Harmer
3.02
252507AC2-088 GEN
Solar/Wind Harmer
1.676
25196008MFTGT1
Adder
1.259
252519AF1-045_GEN
Solar/Wind Harmer
3.37
970879AG2-548 GEN
Solar/Wind Harmer
7.39
25194608D.CRK4
Adder
1.517
252524AE2-267 GEN
Solar/Wind Harmer
1.45
25196608WSDLE5
Adder
7.893
970193AG2-126 GEN
Solar/Wind Harmer
13.761
942481AE2-261 GEN
Solar/Wind Harmer
27.366
957381AF2-032 GEN
Solar/Wind Harmer
1.829
253317AC1-085 GEN4
Solar/Wind Harmer
7.64
946181AF1-283 GEN
Solar/Wind Harmer
11.863
24728705AND G3
Adder
7.32
24728505AND G1
Adder
3.5
276785W4-005 GEN1
Solar/Wind Harmer
2.739
971993AH1-541 GEN
Solar/Wind Harmer
8.371
253394AE2-221_GEN
Solar/Wind Harmer
4.079
965931AG1-462 GEN
Solar/Wind Harmer
22.875
971087AG2-675 GEN
Solar/Wind Harmer
3.338
965091AG1-374 GEN
Solar/Wind Harmer
26.876
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274760LEE CO EC;1U
Adder
8.264
274767LEE CO EC;8U
Adder
8.167
274682WAUKEGAN ;7U
Adder
15.786
274729ELWOOD EC;1P
Adder
14.355
274730ELWOOD EC;6P
Adder
14.355
274734ELWOOD EC;8P
Adder
14.355
274736ELWOOD EC;9P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.852
3147666LOUISA
Solar/Wind Helper
1.093
238152AF2-075_GEN
Solar/Wind Helper
0.608
316447AC1-158 HLD
Solar/Wind Helper
2.79
316044AC1-158 PL1
Solar/Wind Helper
1.268
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.222
24386205FR-12G C
Solar/Wind Harmer
2.911
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.197
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24728305BUCHG2
50/50
7.18
270173AC1-122 GEN
Solar/Wind Harmer
3.446
316217AC1-145 GEN
Solar/Wind Harmer
4.244
316197AC1-042 GEN
Solar/Wind Harmer
3.217
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.474
270336AE1-100 GEN
Solar/Wind Harmer
2.754
943811AF1-049 GEN
Solar/Wind Harmer
5.701
958131AF2-107 GEN
Solar/Wind Harmer
7.107
24735205WLF2G2
Adder
8.042
971687AH1-348 GEN
Solar/Wind Harmer
1.363
971403AH1-188 GEN
Solar/Wind Harmer
18.915
944971AF1-162 GEN
Solar/Wind Harmer
9.1
24723205RIVRG3
Adder
23.046
24686505CER G6
Adder
9.917
972203AH1-686 GEN
Adder
2.716
270331AC1-082 GEN3
Solar/Wind Harmer
0.515
339211AE2-254 GEN
Solar/Wind Harmer
1.567
964901AG1-354 GEN
Solar/Wind Harmer
15.55
960001AF2-291 GEN
Solar/Wind Harmer
3.133
339241AF1-083 GEN
Solar/Wind Harmer
1.722
3429241JKCT 3G
Adder
12.084
970653AG2-424 GEN
Solar/Wind Harmer
4.903
3429421JKCT 10G
Adder
8.441
943111AE2-339 GEN
Solar/Wind Harmer
0.887
339221AD2-048_GEN
Solar/Wind Harmer
1.518
945681AF1-233 GEN
Solar/Wind Harmer
18.414
970091AG2-072 GEN
Adder
74.384
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
71.001
25196008MFTGT1
Adder
1.3
252516AE2-318_GEN
Solar/Wind Harmer
9.259
252510AF1-249 C
Solar/Wind Harmer
0.385
971073AG2-665 GEN
Solar/Wind Harmer
1.074
25194608D.CRK4
Adder
1.517
965911AG1-460 GEN
Solar/Wind Harmer
1.277
253316AC1-085 GEN3
Solar/Wind Harmer
7.64
946171AF1-282 GEN
Solar/Wind Harmer
9.125
24728605AND G2
Adder
3.5
276621W2-048 GEN
Solar/Wind Harmer
5.671
276686W4-005 GEN3
Solar/Wind Harmer
2.739
963741AG1-226 GEN
Solar/Wind Harmer
40.583
253398AE2-221_GEN2
Solar/Wind Harmer
4.079
270222AC2-111 GEN
Solar/Wind Harmer
4.015
944031AF1-071 GEN
Solar/Wind Harmer
0.903
276655WTG1_EQ
Solar/Wind Harmer
7.791
276656WTG2_EQ
Solar/Wind Harmer
1.032
939741AE1-205 GEN
Solar/Wind Harmer
17.852
274761LEE CO EC;2U
Adder
8.264
274766LEE CO EC;7U
Adder
8.167
274822ROCKFORD ;11
Adder
17.365
274828WAUKEGAN ;BP
Adder
9.706
274682WAUKEGAN ;7U
Adder
15.786
274745AC1-111 GEN9
Adder
4.896
274732ELWOOD EC;7P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
274674JOLIET 9 ;6U
Adder
13.445
274676JOLIET 29;8U
Adder
22.605
3148013FISHERV
Solar/Wind Helper
0.524
316499AE2-029_GEN
Solar/Wind Helper
1.728
315821AE2-092 GEN
Solar/Wind Helper
3.236
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.324
316095T157 G97
Solar/Wind Helper
1.135
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.393
24385905FR-11G C
Solar/Wind Harmer
5.645
24386605FR-22G C
Solar/Wind Harmer
2.921
LAGNLTFEXP_LAGN->PJM
CLTF
20.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.582
TVALTFEXP_TVA->PJM
CLTF
10.64
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.053
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.452
MECLTFEXP_MEC->PJM
CLTF
15.488
SIGELTFEXP_SIGE->PJM
CLTF
0.51
NYPJM->LTFIMP_NY
CLTF
3.28
LGEELTFEXP_LGEE->PJM
CLTF
6.795
WECLTFEXP_WEC->PJM
CLTF
3.389
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
CPLELTFEXP_CPLE->PJM
CLTF
6.224
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.642

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4165.98
MW Contribution:
5.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.246
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.362
971329AH1-144 GEN
Solar/Wind Harmer
11.729
966391AG1-508 GEN
Solar/Wind Harmer
6.375
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270069AE2-166 C O1
Solar/Wind Harmer
14.878
971313AH1-133 GEN
Solar/Wind Harmer
9.329
24734705WLF1G3
Adder
8.195
24734805WLF1G4
Adder
8.195
24734905WLF1G5
Adder
8.195
24735105WLF2G1
Adder
8.025
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.288
957241AF2-018 GEN
Solar/Wind Harmer
5.76
270053AF1-130 C
Solar/Wind Harmer
23.016
970281AG2-184 GEN
Solar/Wind Harmer
27.137
971981AH1-535 GEN
Solar/Wind Harmer
12.564
962211AG1-066 GEN
Solar/Wind Harmer
3.002
971061AG2-657 GEN
Solar/Wind Harmer
11.001
3429211JKCT 2G
Adder
11.881
339216AC1-074 GEN
Solar/Wind Harmer
1.645
972163AH1-664 GEN
Solar/Wind Harmer
9.75
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.311
270444AC2-157 GEN1
Solar/Wind Harmer
5.241
270445AC2-157 GEN2
Solar/Wind Harmer
5.241
25196108MFTGT2
Adder
1.427
25196108MFTGT2
Adder
1.325
944221AF1-090 GEN
Solar/Wind Harmer
10.032
25196408WSDLE3
Adder
8.087
25196308WSDLE2
Adder
8.016
25196208WSDLE1
Adder
7.996
25196708WSDLE6
Adder
7.976
25196508WSDLE4
Adder
7.775
253433AC1-085 GEN1
Solar/Wind Harmer
4.826
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
276668AB2-070 GEN1
Solar/Wind Harmer
1.998
276848AB2-070 GEN3
Solar/Wind Harmer
1.998
276849AB2-070 GEN2
Solar/Wind Harmer
1.998
270356AE2-297 GEN
Solar/Wind Harmer
4.149
253406AD2-031_GEN
Solar/Wind Harmer
1.147
963841AG1-237 GEN
Solar/Wind Harmer
9.765
270291AC1-194 GEN
Solar/Wind Harmer
4.541
946321AF1-296 GEN
Solar/Wind Harmer
9.308
274853TWINGROVE;U1
Solar/Wind Harmer
6.427
274854TWINGROVE;U2
Solar/Wind Harmer
6.292
270340AC2-060 GEN
Solar/Wind Harmer
2.689
276726Z2-087_GEN
Solar/Wind Harmer
7.027
959341AF2-225 GEN
Solar/Wind Harmer
13.331
972267AH1-718 GEN
Adder
3.691
274823ROCKFORD ;21
Adder
17.165
274744AC1-111 GEN8
Adder
4.874
274746AC1-111 G10
Adder
4.874
274728ELWOOD EC;5P
Adder
14.292
274731ELWOOD EC;2P
Adder
14.292
274733ELWOOD EC;3P
Adder
14.292
274735ELWOOD EC;4P
Adder
14.292
25306009OHH W.
Adder
2.505
274675JOLIET 29;7U
Adder
26.663
274675JOLIET 29;7U
Adder
7.65
315616AA1-038_C
Solar/Wind Helper
3.298
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.844
316164AC1-076 GEN
Solar/Wind Helper
1.178
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.09
24386405FR-21G C
Solar/Wind Harmer
2.093
24387005FR-3G C
Solar/Wind Harmer
1.925
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.164
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
942671AE2-283 GEN
Solar/Wind Harmer
8.664
270013AE1-250 PV
Solar/Wind Harmer
3.249
970913AG2-568 GEN
Solar/Wind Harmer
9.345
971225AH1-072 GEN
Solar/Wind Harmer
2.731
971227AH1-073 GEN
Solar/Wind Harmer
2.731
24723005RIVRG1
Adder
22.967
24723105RIVRG2
Adder
22.967
942751AE2-291 GEN
Solar/Wind Harmer
10.376
966021AG1-471 GEN
Solar/Wind Harmer
5.755
971485AH1-239 GEN
Solar/Wind Harmer
8.501
339231AF1-038_GEN
Solar/Wind Harmer
1.919
964781AG1-341 GEN
Solar/Wind Harmer
10.975
339236AF1-050_GEN
Solar/Wind Harmer
1.873
942891AE2-308 GEN
Solar/Wind Harmer
10.182
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
972043AH1-570 GEN
Solar/Wind Harmer
2.477
972045AH1-571 GEN
Solar/Wind Harmer
1.981
927014AC1-188 GEN
Solar/Wind Harmer
1.529
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.577
971073AG2-665 GEN
Solar/Wind Harmer
7.349
970879AG2-548 GEN
Solar/Wind Harmer
1.068
25194408D.CRK1
Adder
6.944
25194508D.CRK3
Adder
1.298
945391AF1-204 GEN
Solar/Wind Harmer
12.73
276916AD2-100_GEN
Solar/Wind Harmer
19.171
276911AD2-131_GEN
Solar/Wind Harmer
3.875
276615X2-022 GEN
Solar/Wind Harmer
1.774
276838X2-022 GEN2
Solar/Wind Harmer
0.211
274880W4-005 GEN4
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
970241AG2-163 GEN
Solar/Wind Harmer
22.448
24728805RICHG1
Adder
3.39
24728905RICHG2
Adder
3.39
960251AF2-316 GEN
Solar/Wind Harmer
13.412
960201AF2-311 GEN
Solar/Wind Harmer
8.941
960611AF2-352 GEN
Solar/Wind Harmer
2.075
942111AE2-223 GEN
Solar/Wind Harmer
7.286
274764LEE CO EC;5U
Adder
8.248
274765LEE CO EC;6U
Adder
8.248
274762LEE CO EC;3U
Adder
8.229
274763LEE CO EC;4U
Adder
8.151
972235AH1-702 GEN1
Adder
2.222
972236AH1-702 GEN2
Adder
1.932
274683WAUKEGAN ;8U
Adder
18.436
274683WAUKEGAN ;8U
Adder
15.54
274696ROCKY RD ;4P
Adder
9.966
274695ROCKY RD ;2P
Adder
9.736
274693ROCKY RD ;1P
Adder
9.64
274697ROCKY RD ;3P
Adder
2.645
274674JOLIET 9 ;6U
Adder
13.386
3132123MT JACKSON
Solar/Wind Helper
1.391
966001AG1-469 GEN
Solar/Wind Helper
0.321
237061AD1-155 GEN
Solar/Wind Helper
1.65
316097T157 G90
Solar/Wind Helper
1.13
238147AE2-230_GEN1
Solar/Wind Helper
0.424
238148AE2-230_GEN2
Solar/Wind Helper
0.424
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.356
966871AG1-558 GEN
Solar/Wind Helper
0.307
316045AC1-158 PL2
Solar/Wind Helper
4.045
316450AC1-158 RIC
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.425
24387305FR-4G C
Solar/Wind Harmer
2.471
970823AG2-518 GEN
50/50
8.383
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.211
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.98
970563AG2-360 GEN
50/50
45.836
970417AG2-272 GEN
50/50
3.733
962751AG1-124 GEN
Solar/Wind Harmer
18.819
958121AF2-106 GEN
Solar/Wind Harmer
9.406
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.808
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.922
270018AE2-047 C O1
Solar/Wind Harmer
1.821
960911AF2-382 GEN
Solar/Wind Harmer
10.95
270016AE1-250 BESS
Solar/Wind Harmer
3.249
971461AH1-227 GEN
Solar/Wind Harmer
7.006
970223AG2-152 GEN
Solar/Wind Harmer
17.663
972103AH1-617 GEN
Solar/Wind Harmer
25.844
24686405CER G5
Adder
9.803
270330AC1-082 GEN2
Solar/Wind Harmer
0.512
270329AC1-082 GEN1
Solar/Wind Harmer
0.512
972273AH1-721 GEN
Adder
89.361
24721905FLATG4
Adder
21.701
339255AE2-071 GEN
Solar/Wind Harmer
1.218
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.205
970093AG2-073 GEN
Solar/Wind Harmer
5.447
970653AG2-424 GEN
Solar/Wind Harmer
0.706
3429391JKCT 9G
Adder
8.408
971191AH1-055 GEN
Solar/Wind Harmer
18.847
970455AG2-298 GEN
Solar/Wind Harmer
3.522
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.928
270186AC1-089 GEN
Solar/Wind Harmer
5.824
270367AC2-061_GEN
Solar/Wind Harmer
3.006
252507AC2-088 GEN
Solar/Wind Harmer
1.668
25196008MFTGT1
Adder
1.253
252519AF1-045_GEN
Solar/Wind Harmer
3.354
970879AG2-548 GEN
Solar/Wind Harmer
7.349
25194608D.CRK4
Adder
1.51
252524AE2-267 GEN
Solar/Wind Harmer
1.443
25196608WSDLE5
Adder
7.856
970193AG2-126 GEN
Solar/Wind Harmer
13.702
942481AE2-261 GEN
Solar/Wind Harmer
27.253
957381AF2-032 GEN
Solar/Wind Harmer
1.822
24728705AND G3
Adder
7.288
24728505AND G1
Adder
3.485
253317AC1-085 GEN4
Solar/Wind Harmer
7.603
946181AF1-283 GEN
Solar/Wind Harmer
11.806
276785W4-005 GEN1
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.336
253394AE2-221_GEN
Solar/Wind Harmer
4.059
965931AG1-462 GEN
Solar/Wind Harmer
22.779
971087AG2-675 GEN
Solar/Wind Harmer
3.324
965091AG1-374 GEN
Solar/Wind Harmer
26.762
959611AF2-252 GEN
Solar/Wind Harmer
2.075
274760LEE CO EC;1U
Adder
8.229
274767LEE CO EC;8U
Adder
8.132
274682WAUKEGAN ;7U
Adder
15.718
274729ELWOOD EC;1P
Adder
14.292
274730ELWOOD EC;6P
Adder
14.292
274734ELWOOD EC;8P
Adder
14.292
274736ELWOOD EC;9P
Adder
14.292
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.847
3147666LOUISA
Solar/Wind Helper
1.09
238152AF2-075_GEN
Solar/Wind Helper
0.606
316447AC1-158 HLD
Solar/Wind Helper
2.781
316044AC1-158 PL1
Solar/Wind Helper
1.264
3142416OLDCHRC
Solar/Wind Helper
0.579
3142416OLDCHRC
Solar/Wind Helper
0.222
24386205FR-12G C
Solar/Wind Harmer
2.085
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.164
270173AC1-122 GEN
Solar/Wind Harmer
3.444
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
958131AF2-107 GEN
Solar/Wind Harmer
7.104
24735205WLF2G2
Adder
8.025
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.86
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723205RIVRG3
Adder
22.967
24686505CER G6
Adder
9.881
972203AH1-686 GEN
Adder
2.706
270331AC1-082 GEN3
Solar/Wind Harmer
0.513
964901AG1-354 GEN
Solar/Wind Harmer
15.496
339211AE2-254 GEN
Solar/Wind Harmer
1.561
339241AF1-083 GEN
Solar/Wind Harmer
1.716
960001AF2-291 GEN
Solar/Wind Harmer
3.117
3429241JKCT 3G
Adder
12.037
970653AG2-424 GEN
Solar/Wind Harmer
4.885
3429421JKCT 10G
Adder
8.408
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339221AD2-048_GEN
Solar/Wind Harmer
1.511
945681AF1-233 GEN
Solar/Wind Harmer
18.334
970091AG2-072 GEN
Adder
74.077
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.673
25196008MFTGT1
Adder
1.294
252516AE2-318_GEN
Solar/Wind Harmer
9.216
252510AF1-249 C
Solar/Wind Harmer
0.384
971073AG2-665 GEN
Solar/Wind Harmer
1.068
25194608D.CRK4
Adder
1.51
965911AG1-460 GEN
Solar/Wind Harmer
1.272
24728605AND G2
Adder
3.485
253316AC1-085 GEN3
Solar/Wind Harmer
7.603
946171AF1-282 GEN
Solar/Wind Harmer
9.081
276621W2-048 GEN
Solar/Wind Harmer
5.648
276686W4-005 GEN3
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.407
270222AC2-111 GEN
Solar/Wind Harmer
3.996
944031AF1-071 GEN
Solar/Wind Harmer
0.899
253398AE2-221_GEN2
Solar/Wind Harmer
4.059
276655WTG1_EQ
Solar/Wind Harmer
7.757
276656WTG2_EQ
Solar/Wind Harmer
1.027
939741AE1-205 GEN
Solar/Wind Harmer
17.775
274848CAMPGROVE;RU
Solar/Wind Harmer
5.733
274761LEE CO EC;2U
Adder
8.229
274766LEE CO EC;7U
Adder
8.132
274822ROCKFORD ;11
Adder
17.29
274828WAUKEGAN ;BP
Adder
9.664
274682WAUKEGAN ;7U
Adder
15.718
274745AC1-111 GEN9
Adder
4.874
274732ELWOOD EC;7P
Adder
14.292
274674JOLIET 9 ;6U
Adder
13.386
274676JOLIET 29;8U
Adder
26.663
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.232
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.627
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.304
316095T157 G97
Solar/Wind Helper
1.13
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.39
24385905FR-11G C
Solar/Wind Harmer
4.044
24386605FR-22G C
Solar/Wind Harmer
2.093
LAGNLTFEXP_LAGN->PJM
CLTF
20.287
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.539
TVALTFEXP_TVA->PJM
CLTF
10.609
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.331
MECLTFEXP_MEC->PJM
CLTF
15.426
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.263
LGEELTFEXP_LGEE->PJM
CLTF
6.768
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CPLELTFEXP_CPLE->PJM
CLTF
6.216
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.186

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.26 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4160.96
MW Contribution:
5.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
11.722
966391AG1-508 GEN
Solar/Wind Harmer
6.371
270197AD1-017 GEN1
Solar/Wind Harmer
2.54
270069AE2-166 C O1
Solar/Wind Harmer
14.87
971313AH1-133 GEN
Solar/Wind Harmer
9.321
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
5.551
270400AC1-102 GEN
Solar/Wind Harmer
5.551
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
5.752
270053AF1-130 C
Solar/Wind Harmer
22.985
970281AG2-184 GEN
Solar/Wind Harmer
27.103
971981AH1-535 GEN
Solar/Wind Harmer
12.552
962211AG1-066 GEN
Solar/Wind Harmer
2.998
971061AG2-657 GEN
Solar/Wind Harmer
10.98
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
1.642
972163AH1-664 GEN
Solar/Wind Harmer
9.732
972165AH1-665 GEN
Solar/Wind Harmer
7.785
971985AH1-537 GEN
Solar/Wind Harmer
17.275
270444AC2-157 GEN1
Solar/Wind Harmer
5.231
270445AC2-157 GEN2
Solar/Wind Harmer
5.231
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
10.014
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
253433AC1-085 GEN1
Solar/Wind Harmer
4.815
253432AC1-085 GEN2
Solar/Wind Harmer
0.242
276763AC1-053 GEN1
Solar/Wind Harmer
3.564
276764AC1-053 GEN2
Solar/Wind Harmer
3.564
276668AB2-070 GEN1
Solar/Wind Harmer
1.994
276848AB2-070 GEN3
Solar/Wind Harmer
1.994
276849AB2-070 GEN2
Solar/Wind Harmer
1.994
270356AE2-297 GEN
Solar/Wind Harmer
4.141
253406AD2-031_GEN
Solar/Wind Harmer
1.145
963841AG1-237 GEN
Solar/Wind Harmer
9.746
946321AF1-296 GEN
Solar/Wind Harmer
9.291
274853TWINGROVE;U1
Solar/Wind Harmer
6.415
274854TWINGROVE;U2
Solar/Wind Harmer
6.28
270291AC1-194 GEN
Solar/Wind Harmer
4.529
270340AC2-060 GEN
Solar/Wind Harmer
2.683
276726Z2-087_GEN
Solar/Wind Harmer
7.014
959341AF2-225 GEN
Solar/Wind Harmer
13.306
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
24386405FR-21G C
Solar/Wind Harmer
2.088
24387005FR-3G C
Solar/Wind Harmer
1.921
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
20.71
270214AC2-123 GEN
Solar/Wind Harmer
4.308
971277AH1-098 GEN
Solar/Wind Harmer
7.416
942671AE2-283 GEN
Solar/Wind Harmer
8.662
270013AE1-250 PV
Solar/Wind Harmer
3.247
970913AG2-568 GEN
Solar/Wind Harmer
9.332
971225AH1-072 GEN
Solar/Wind Harmer
2.728
971227AH1-073 GEN
Solar/Wind Harmer
2.728
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
10.374
966021AG1-471 GEN
Solar/Wind Harmer
5.747
971485AH1-239 GEN
Solar/Wind Harmer
8.488
339231AF1-038_GEN
Solar/Wind Harmer
1.916
964781AG1-341 GEN
Solar/Wind Harmer
10.959
339236AF1-050_GEN
Solar/Wind Harmer
1.871
942891AE2-308 GEN
Solar/Wind Harmer
10.165
964571AG1-320 GEN
Solar/Wind Harmer
8.178
971125AH1-004 GEN
Solar/Wind Harmer
3.985
970107AG2-081 GEN
Solar/Wind Harmer
2.988
972043AH1-570 GEN
Solar/Wind Harmer
2.472
972045AH1-571 GEN
Solar/Wind Harmer
1.978
927014AC1-188 GEN
Solar/Wind Harmer
1.526
962581AG1-107 GEN
Solar/Wind Harmer
4.724
961491AF2-440 GEN
Solar/Wind Harmer
1.963
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.565
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.33
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
12.706
276916AD2-100_GEN
Solar/Wind Harmer
19.136
276911AD2-131_GEN
Solar/Wind Harmer
3.867
276615X2-022 GEN
Solar/Wind Harmer
1.77
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.723
276174W4-005 GEN2
Solar/Wind Harmer
2.723
970241AG2-163 GEN
Solar/Wind Harmer
22.405
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
13.37
960201AF2-311 GEN
Solar/Wind Harmer
8.913
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
7.272
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
274674JOLIET 9 ;6U
Adder
13.36
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
24387305FR-4G C
Solar/Wind Harmer
2.467
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
18.814
958121AF2-106 GEN
Solar/Wind Harmer
9.401
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.805
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.925
270030AE2-140 GEN
Solar/Wind Harmer
30.906
270018AE2-047 C O1
Solar/Wind Harmer
1.82
960911AF2-382 GEN
Solar/Wind Harmer
10.939
270016AE1-250 BESS
Solar/Wind Harmer
3.247
971461AH1-227 GEN
Solar/Wind Harmer
6.998
970223AG2-152 GEN
Solar/Wind Harmer
17.657
972103AH1-617 GEN
Solar/Wind Harmer
25.812
24686405CER G5
Adder
9.787
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
339255AE2-071 GEN
Solar/Wind Harmer
1.216
339250AF1-203 GEN
Solar/Wind Harmer
0.626
339206AE1-143 GEN
Solar/Wind Harmer
2.202
970093AG2-073 GEN
Solar/Wind Harmer
5.438
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.807
970455AG2-298 GEN
Solar/Wind Harmer
3.516
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
972167AH1-666 GEN
Solar/Wind Harmer
7.758
957541AF2-048 GEN
Solar/Wind Harmer
1.526
958171AF2-111 GEN
Solar/Wind Harmer
23.881
270186AC1-089 GEN
Solar/Wind Harmer
5.812
270367AC2-061_GEN
Solar/Wind Harmer
3
252507AC2-088 GEN
Solar/Wind Harmer
1.664
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
7.33
252524AE2-267 GEN
Solar/Wind Harmer
1.44
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
13.676
942481AE2-261 GEN
Solar/Wind Harmer
27.203
957381AF2-032 GEN
Solar/Wind Harmer
1.819
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
7.586
946181AF1-283 GEN
Solar/Wind Harmer
11.78
276785W4-005 GEN1
Solar/Wind Harmer
2.723
971993AH1-541 GEN
Solar/Wind Harmer
8.32
253394AE2-221_GEN
Solar/Wind Harmer
4.05
965931AG1-462 GEN
Solar/Wind Harmer
22.737
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
26.711
959611AF2-252 GEN
Solar/Wind Harmer
2.071
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
274682WAUKEGAN ;7U
Adder
15.687
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
24386205FR-12G C
Solar/Wind Harmer
2.081
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
270173AC1-122 GEN
Solar/Wind Harmer
3.443
316217AC1-145 GEN
Solar/Wind Harmer
4.241
316197AC1-042 GEN
Solar/Wind Harmer
3.215
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.466
270336AE1-100 GEN
Solar/Wind Harmer
2.749
943811AF1-049 GEN
Solar/Wind Harmer
5.692
958131AF2-107 GEN
Solar/Wind Harmer
7.102
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
1.358
971403AH1-188 GEN
Solar/Wind Harmer
18.836
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
964901AG1-354 GEN
Solar/Wind Harmer
15.473
339211AE2-254 GEN
Solar/Wind Harmer
1.559
339241AF1-083 GEN
Solar/Wind Harmer
1.713
960001AF2-291 GEN
Solar/Wind Harmer
3.11
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
4.877
3429421JKCT 10G
Adder
8.393
943111AE2-339 GEN
Solar/Wind Harmer
0.882
339221AD2-048_GEN
Solar/Wind Harmer
1.508
945681AF1-233 GEN
Solar/Wind Harmer
18.298
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
9.197
252510AF1-249 C
Solar/Wind Harmer
0.383
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
7.586
946171AF1-282 GEN
Solar/Wind Harmer
9.062
276621W2-048 GEN
Solar/Wind Harmer
5.637
276686W4-005 GEN3
Solar/Wind Harmer
2.723
963741AG1-226 GEN
Solar/Wind Harmer
40.329
270222AC2-111 GEN
Solar/Wind Harmer
3.988
944031AF1-071 GEN
Solar/Wind Harmer
0.897
253398AE2-221_GEN2
Solar/Wind Harmer
4.05
276655WTG1_EQ
Solar/Wind Harmer
7.743
276656WTG2_EQ
Solar/Wind Harmer
1.025
939741AE1-205 GEN
Solar/Wind Harmer
17.741
274848CAMPGROVE;RU
Solar/Wind Harmer
5.723
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
274822ROCKFORD ;11
Adder
17.258
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274745AC1-111 GEN9
Adder
4.865
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
24385905FR-11G C
Solar/Wind Harmer
4.036
24386605FR-22G C
Solar/Wind Harmer
2.088
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4149.41
MW Contribution:
5.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.244
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.357
971329AH1-144 GEN
Solar/Wind Harmer
11.725
966391AG1-508 GEN
Solar/Wind Harmer
6.373
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270069AE2-166 C O1
Solar/Wind Harmer
14.876
971313AH1-133 GEN
Solar/Wind Harmer
9.325
24734705WLF1G3
Adder
8.191
24734805WLF1G4
Adder
8.191
24734905WLF1G5
Adder
8.191
24735105WLF2G1
Adder
8.021
270399AC1-101 GEN
Solar/Wind Harmer
5.554
270400AC1-102 GEN
Solar/Wind Harmer
5.554
941621AE2-160 GEN
Adder
4.283
957241AF2-018 GEN
Solar/Wind Harmer
5.755
270053AF1-130 C
Solar/Wind Harmer
22.996
970281AG2-184 GEN
Solar/Wind Harmer
27.117
971981AH1-535 GEN
Solar/Wind Harmer
12.558
962211AG1-066 GEN
Solar/Wind Harmer
3
971061AG2-657 GEN
Solar/Wind Harmer
10.986
3429211JKCT 2G
Adder
11.868
339216AC1-074 GEN
Solar/Wind Harmer
1.643
972163AH1-664 GEN
Solar/Wind Harmer
9.738
972165AH1-665 GEN
Solar/Wind Harmer
7.79
971985AH1-537 GEN
Solar/Wind Harmer
17.286
270444AC2-157 GEN1
Solar/Wind Harmer
5.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.235
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.323
944221AF1-090 GEN
Solar/Wind Harmer
10.021
25196408WSDLE3
Adder
8.076
25196308WSDLE2
Adder
8.005
25196208WSDLE1
Adder
7.985
25196708WSDLE6
Adder
7.965
25196508WSDLE4
Adder
7.765
253433AC1-085 GEN1
Solar/Wind Harmer
4.819
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.567
276764AC1-053 GEN2
Solar/Wind Harmer
3.567
276668AB2-070 GEN1
Solar/Wind Harmer
1.995
276848AB2-070 GEN3
Solar/Wind Harmer
1.995
276849AB2-070 GEN2
Solar/Wind Harmer
1.995
270356AE2-297 GEN
Solar/Wind Harmer
4.144
253406AD2-031_GEN
Solar/Wind Harmer
1.146
963841AG1-237 GEN
Solar/Wind Harmer
9.753
946321AF1-296 GEN
Solar/Wind Harmer
9.297
274853TWINGROVE;U1
Solar/Wind Harmer
6.419
274854TWINGROVE;U2
Solar/Wind Harmer
6.285
270291AC1-194 GEN
Solar/Wind Harmer
4.532
270340AC2-060 GEN
Solar/Wind Harmer
2.685
276726Z2-087_GEN
Solar/Wind Harmer
7.019
959341AF2-225 GEN
Solar/Wind Harmer
13.316
972267AH1-718 GEN
Adder
3.687
274823ROCKFORD ;21
Adder
17.145
274744AC1-111 GEN8
Adder
4.868
274746AC1-111 G10
Adder
4.868
274728ELWOOD EC;5P
Adder
14.275
274731ELWOOD EC;2P
Adder
14.275
274733ELWOOD EC;3P
Adder
14.275
274735ELWOOD EC;4P
Adder
14.275
25306009OHH W.
Adder
2.502
274675JOLIET 29;7U
Adder
26.631
274675JOLIET 29;7U
Adder
7.641
315616AA1-038_C
Solar/Wind Helper
3.296
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.842
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.266
316468AD1-105 GEN
Solar/Wind Helper
1.088
24386405FR-21G C
Solar/Wind Harmer
2.09
24387005FR-3G C
Solar/Wind Harmer
1.922
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.16
270173AC1-122 GEN
Solar/Wind Harmer
3.444
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
958131AF2-107 GEN
Solar/Wind Harmer
7.106
24735205WLF2G2
Adder
8.021
971687AH1-348 GEN
Solar/Wind Harmer
1.358
971403AH1-188 GEN
Solar/Wind Harmer
18.845
944971AF1-162 GEN
Solar/Wind Harmer
9.064
24723205RIVRG3
Adder
22.944
24686505CER G6
Adder
9.87
972203AH1-686 GEN
Adder
2.703
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
964901AG1-354 GEN
Solar/Wind Harmer
15.482
339211AE2-254 GEN
Solar/Wind Harmer
1.56
339241AF1-083 GEN
Solar/Wind Harmer
1.714
960001AF2-291 GEN
Solar/Wind Harmer
3.112
3429241JKCT 3G
Adder
12.024
970653AG2-424 GEN
Solar/Wind Harmer
4.88
3429421JKCT 10G
Adder
8.399
943111AE2-339 GEN
Solar/Wind Harmer
0.882
339221AD2-048_GEN
Solar/Wind Harmer
1.509
945681AF1-233 GEN
Solar/Wind Harmer
18.311
970091AG2-072 GEN
Adder
73.991
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
70.578
25196008MFTGT1
Adder
1.293
252516AE2-318_GEN
Solar/Wind Harmer
9.203
252510AF1-249 C
Solar/Wind Harmer
0.383
25194608D.CRK4
Adder
1.508
971073AG2-665 GEN
Solar/Wind Harmer
1.066
965911AG1-460 GEN
Solar/Wind Harmer
1.27
24728605AND G2
Adder
3.48
253316AC1-085 GEN3
Solar/Wind Harmer
7.592
946171AF1-282 GEN
Solar/Wind Harmer
9.068
276621W2-048 GEN
Solar/Wind Harmer
5.641
276686W4-005 GEN3
Solar/Wind Harmer
2.725
963741AG1-226 GEN
Solar/Wind Harmer
40.358
270222AC2-111 GEN
Solar/Wind Harmer
3.991
944031AF1-071 GEN
Solar/Wind Harmer
0.898
253398AE2-221_GEN2
Solar/Wind Harmer
4.053
276655WTG1_EQ
Solar/Wind Harmer
7.748
276656WTG2_EQ
Solar/Wind Harmer
1.026
939741AE1-205 GEN
Solar/Wind Harmer
17.754
274848CAMPGROVE;RU
Solar/Wind Harmer
5.727
274761LEE CO EC;2U
Adder
8.219
274766LEE CO EC;7U
Adder
8.123
274822ROCKFORD ;11
Adder
17.27
274828WAUKEGAN ;BP
Adder
9.652
274682WAUKEGAN ;7U
Adder
15.699
274745AC1-111 GEN9
Adder
4.868
274732ELWOOD EC;7P
Adder
14.275
274674JOLIET 9 ;6U
Adder
13.37
274676JOLIET 29;8U
Adder
26.631
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
315821AE2-092 GEN
Solar/Wind Helper
3.228
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.293
316095T157 G97
Solar/Wind Helper
1.127
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
24385905FR-11G C
Solar/Wind Harmer
4.039
24386605FR-22G C
Solar/Wind Harmer
2.09
970823AG2-518 GEN
50/50
8.382
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.211
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.973
970563AG2-360 GEN
50/50
45.815
970417AG2-272 GEN
50/50
3.733
962751AG1-124 GEN
Solar/Wind Harmer
18.82
958121AF2-106 GEN
Solar/Wind Harmer
9.404
943031AE2-326 GEN
Solar/Wind Harmer
6.783
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.809
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.931
270030AE2-140 GEN
Solar/Wind Harmer
30.919
270018AE2-047 C O1
Solar/Wind Harmer
1.821
960911AF2-382 GEN
Solar/Wind Harmer
10.944
270016AE1-250 BESS
Solar/Wind Harmer
3.249
971461AH1-227 GEN
Solar/Wind Harmer
7.001
970223AG2-152 GEN
Solar/Wind Harmer
17.666
972103AH1-617 GEN
Solar/Wind Harmer
25.825
24686405CER G5
Adder
9.792
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
972273AH1-721 GEN
Adder
89.284
24721905FLATG4
Adder
21.675
339255AE2-071 GEN
Solar/Wind Harmer
1.217
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.203
970093AG2-073 GEN
Solar/Wind Harmer
5.442
970653AG2-424 GEN
Solar/Wind Harmer
0.706
3429391JKCT 9G
Adder
8.399
971191AH1-055 GEN
Solar/Wind Harmer
18.819
970455AG2-298 GEN
Solar/Wind Harmer
3.519
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
972167AH1-666 GEN
Solar/Wind Harmer
7.764
957541AF2-048 GEN
Solar/Wind Harmer
1.527
958171AF2-111 GEN
Solar/Wind Harmer
23.897
270186AC1-089 GEN
Solar/Wind Harmer
5.816
270367AC2-061_GEN
Solar/Wind Harmer
3.002
252507AC2-088 GEN
Solar/Wind Harmer
1.666
25196008MFTGT1
Adder
1.252
252519AF1-045_GEN
Solar/Wind Harmer
3.349
25194608D.CRK4
Adder
1.508
970879AG2-548 GEN
Solar/Wind Harmer
7.336
252524AE2-267 GEN
Solar/Wind Harmer
1.441
25196608WSDLE5
Adder
7.845
970193AG2-126 GEN
Solar/Wind Harmer
13.686
942481AE2-261 GEN
Solar/Wind Harmer
27.222
957381AF2-032 GEN
Solar/Wind Harmer
1.82
24728705AND G3
Adder
7.279
24728505AND G1
Adder
3.48
253317AC1-085 GEN4
Solar/Wind Harmer
7.592
946181AF1-283 GEN
Solar/Wind Harmer
11.789
276785W4-005 GEN1
Solar/Wind Harmer
2.725
971993AH1-541 GEN
Solar/Wind Harmer
8.326
253394AE2-221_GEN
Solar/Wind Harmer
4.053
965931AG1-462 GEN
Solar/Wind Harmer
22.754
971087AG2-675 GEN
Solar/Wind Harmer
3.32
965091AG1-374 GEN
Solar/Wind Harmer
26.73
959611AF2-252 GEN
Solar/Wind Harmer
2.072
274760LEE CO EC;1U
Adder
8.219
274767LEE CO EC;8U
Adder
8.123
274682WAUKEGAN ;7U
Adder
15.699
274729ELWOOD EC;1P
Adder
14.275
274730ELWOOD EC;6P
Adder
14.275
274734ELWOOD EC;8P
Adder
14.275
274736ELWOOD EC;9P
Adder
14.275
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.844
3147666LOUISA
Solar/Wind Helper
1.088
238152AF2-075_GEN
Solar/Wind Helper
0.604
316447AC1-158 HLD
Solar/Wind Helper
2.775
316044AC1-158 PL1
Solar/Wind Helper
1.261
24386205FR-12G C
Solar/Wind Harmer
2.082
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.16
270583AD2-179 GEN
Solar/Wind Harmer
20.716
270214AC2-123 GEN
Solar/Wind Harmer
4.31
971277AH1-098 GEN
Solar/Wind Harmer
7.418
942671AE2-283 GEN
Solar/Wind Harmer
8.665
270013AE1-250 PV
Solar/Wind Harmer
3.249
970913AG2-568 GEN
Solar/Wind Harmer
9.337
971225AH1-072 GEN
Solar/Wind Harmer
2.729
971227AH1-073 GEN
Solar/Wind Harmer
2.729
24723005RIVRG1
Adder
22.944
24723105RIVRG2
Adder
22.944
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.751
971485AH1-239 GEN
Solar/Wind Harmer
8.494
339231AF1-038_GEN
Solar/Wind Harmer
1.917
964781AG1-341 GEN
Solar/Wind Harmer
10.966
339236AF1-050_GEN
Solar/Wind Harmer
1.872
942891AE2-308 GEN
Solar/Wind Harmer
10.171
964571AG1-320 GEN
Solar/Wind Harmer
8.183
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.474
972045AH1-571 GEN
Solar/Wind Harmer
1.979
927014AC1-188 GEN
Solar/Wind Harmer
1.527
962581AG1-107 GEN
Solar/Wind Harmer
4.728
961491AF2-440 GEN
Solar/Wind Harmer
1.965
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.569
25194408D.CRK1
Adder
6.935
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.336
970879AG2-548 GEN
Solar/Wind Harmer
1.066
945391AF1-204 GEN
Solar/Wind Harmer
12.715
276916AD2-100_GEN
Solar/Wind Harmer
19.15
276911AD2-131_GEN
Solar/Wind Harmer
3.87
276615X2-022 GEN
Solar/Wind Harmer
1.772
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276174W4-005 GEN2
Solar/Wind Harmer
2.725
970241AG2-163 GEN
Solar/Wind Harmer
22.421
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
960251AF2-316 GEN
Solar/Wind Harmer
13.38
960201AF2-311 GEN
Solar/Wind Harmer
8.92
960611AF2-352 GEN
Solar/Wind Harmer
2.072
942111AE2-223 GEN
Solar/Wind Harmer
7.277
274764LEE CO EC;5U
Adder
8.239
274765LEE CO EC;6U
Adder
8.239
274762LEE CO EC;3U
Adder
8.219
274763LEE CO EC;4U
Adder
8.142
972235AH1-702 GEN1
Adder
2.219
972236AH1-702 GEN2
Adder
1.93
274683WAUKEGAN ;8U
Adder
18.414
274683WAUKEGAN ;8U
Adder
15.522
274696ROCKY RD ;4P
Adder
9.954
274695ROCKY RD ;2P
Adder
9.725
274693ROCKY RD ;1P
Adder
9.629
274697ROCKY RD ;3P
Adder
2.642
274674JOLIET 9 ;6U
Adder
13.37
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.646
316097T157 G90
Solar/Wind Helper
1.127
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.036
316450AC1-158 RIC
Solar/Wind Helper
0.336
24387305FR-4G C
Solar/Wind Harmer
2.468
LAGNLTFEXP_LAGN->PJM
CLTF
20.273
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.54
TVALTFEXP_TVA->PJM
CLTF
10.603
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.302
MECLTFEXP_MEC->PJM
CLTF
15.41
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.251
LGEELTFEXP_LGEE->PJM
CLTF
6.761
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CPLELTFEXP_CPLE->PJM
CLTF
6.22
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.073

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.27 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6477.04
MW Contribution:
7.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
270331AC1-082 GEN3
Solar/Wind Harmer
0.844
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
5.223
971403AH1-188 GEN
Solar/Wind Harmer
23.963
962761AG1-125 GEN
Solar/Wind Harmer
54.553
970149AG2-104 GEN
Solar/Wind Harmer
33.686
970155AG2-107 GEN
Solar/Wind Harmer
23.787
971687AH1-348 GEN
Solar/Wind Harmer
1.522
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
27.387
339221AD2-048_GEN
Solar/Wind Harmer
2.202
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
14.288
252510AF1-249 C
Solar/Wind Harmer
0.594
25196008MFTGT1
Adder
1.98
943111AE2-339 GEN
Solar/Wind Harmer
1.257
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
11.825
946171AF1-282 GEN
Solar/Wind Harmer
14.124
339211AE2-254 GEN
Solar/Wind Harmer
2.115
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
6.325
270222AC2-111 GEN
Solar/Wind Harmer
6.156
944031AF1-071 GEN
Solar/Wind Harmer
1.385
970653AG2-424 GEN
Solar/Wind Harmer
6.638
270273AD2-016 GEN
Solar/Wind Harmer
3.648
24728605AND G2
Adder
5.248
339241AF1-083 GEN
Solar/Wind Harmer
2.268
942081AE2-220 GEN
Solar/Wind Harmer
8.696
270209AC1-174_GEN
Solar/Wind Harmer
5.534
270437AC2-090 C
Solar/Wind Harmer
7.589
270239V3-007_GEN1
Solar/Wind Harmer
2.34
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
13.523
963741AG1-226 GEN
Solar/Wind Harmer
60.722
964901AG1-354 GEN
Solar/Wind Harmer
20.24
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
7.699
270053AF1-130 C
Solar/Wind Harmer
30.765
270399AC1-101 GEN
Solar/Wind Harmer
7.281
270400AC1-102 GEN
Solar/Wind Harmer
7.281
970281AG2-184 GEN
Solar/Wind Harmer
32.719
971985AH1-537 GEN
Solar/Wind Harmer
27.788
941621AE2-160 GEN
Adder
5.034
962211AG1-066 GEN
Solar/Wind Harmer
3.649
971313AH1-133 GEN
Solar/Wind Harmer
8.798
972163AH1-664 GEN
Solar/Wind Harmer
14.536
972165AH1-665 GEN
Solar/Wind Harmer
11.629
339216AC1-074 GEN
Solar/Wind Harmer
2.394
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
253433AC1-085 GEN1
Solar/Wind Harmer
7.506
253432AC1-085 GEN2
Solar/Wind Harmer
0.378
270340AC2-060 GEN
Solar/Wind Harmer
4.256
253406AD2-031_GEN
Solar/Wind Harmer
1.796
270263AC1-001 GEN
Solar/Wind Harmer
1.464
270444AC2-157 GEN1
Solar/Wind Harmer
7.815
270445AC2-157 GEN2
Solar/Wind Harmer
7.815
270291AC1-194 GEN
Solar/Wind Harmer
7.123
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
6.333
971061AG2-657 GEN
Solar/Wind Harmer
12.288
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
2.562
963841AG1-237 GEN
Solar/Wind Harmer
14.713
971029AG2-637 GEN
Solar/Wind Harmer
20.191
24386405FR-21G C
Solar/Wind Harmer
5.776
24387005FR-3G C
Solar/Wind Harmer
5.313
270543AE2-219 C
Solar/Wind Harmer
13.404
946581AF1-322 GEN
Solar/Wind Harmer
13.675
24691005MDL-2G C
Solar/Wind Harmer
4.942
945581AF1-223 GEN
Solar/Wind Harmer
6.056
247536S-71 GEN
Solar/Wind Harmer
5.402
964611AG1-324 GEN
Solar/Wind Harmer
5.196
270432AC2-029 GEN
Solar/Wind Harmer
9.322
944221AF1-090 GEN
Solar/Wind Harmer
14.552
961761AG1-017 GEN
Solar/Wind Harmer
0.569
24729505KEY G4
Adder
8.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
972267AH1-718 GEN
Adder
5.423
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274823ROCKFORD ;21
Adder
25.367
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
927014AC1-188 GEN
Solar/Wind Harmer
2.477
970913AG2-568 GEN
Solar/Wind Harmer
10.623
971225AH1-072 GEN
Solar/Wind Harmer
3.04
971227AH1-073 GEN
Solar/Wind Harmer
3.04
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
7.389
961491AF2-440 GEN
Solar/Wind Harmer
3.071
971073AG2-665 GEN
Solar/Wind Harmer
11.654
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.369
972043AH1-570 GEN
Solar/Wind Harmer
3.585
972045AH1-571 GEN
Solar/Wind Harmer
2.868
25183208HLCRTG
Solar/Wind Harmer
8.652
971125AH1-004 GEN
Solar/Wind Harmer
5.691
970107AG2-081 GEN
Solar/Wind Harmer
4.268
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
14.201
253415AE1-040 GEN
Solar/Wind Harmer
1.57
964571AG1-320 GEN
Solar/Wind Harmer
11.341
270269AC2-059
Solar/Wind Harmer
12.798
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
18.959
926881AC1-175 GEN
Solar/Wind Harmer
7.589
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
8.27
339231AF1-038_GEN
Solar/Wind Harmer
2.457
24725505WLD G2 C
Solar/Wind Harmer
5.381
24699105WLD G1 C
Solar/Wind Harmer
5.319
339236AF1-050_GEN
Solar/Wind Harmer
2.451
970241AG2-163 GEN
Solar/Wind Harmer
33.734
970291AG2-192 GEN
Solar/Wind Harmer
1.753
970291AG2-192 GEN
Solar/Wind Harmer
0.565
253349AC2-067 GEN
Solar/Wind Harmer
2.741
253400AC2-068 GEN
Solar/Wind Harmer
1.102
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
6.822
966841AG1-555 GEN
Solar/Wind Harmer
3.372
970883AG2-550 GEN
Solar/Wind Harmer
13.404
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
4.927
24755605MDL-5G
Solar/Wind Harmer
3.222
24697905MDL-4G C
Solar/Wind Harmer
3.067
270181AB1-006 GEN2
Solar/Wind Harmer
0.956
971485AH1-239 GEN
Solar/Wind Harmer
10.681
964781AG1-341 GEN
Solar/Wind Harmer
14.151
966021AG1-471 GEN
Solar/Wind Harmer
7.208
270031AE2-169
Solar/Wind Harmer
10.876
270599AE1-208 GEN
Solar/Wind Harmer
10.876
945421AF1-207 GEN
Solar/Wind Harmer
18.73
957841AF2-078 GEN
Solar/Wind Harmer
8.063
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
6.831
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
274674JOLIET 9 ;6U
Adder
20.046
274683WAUKEGAN ;8U
Adder
27.432
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
270330AC1-082 GEN2
Solar/Wind Harmer
0.842
270329AC1-082 GEN1
Solar/Wind Harmer
0.842
962771AG1-126 GEN
Solar/Wind Harmer
54.553
970153AG2-106 GEN
Solar/Wind Harmer
23.787
971191AH1-055 GEN
Solar/Wind Harmer
31.162
957541AF2-048 GEN
Solar/Wind Harmer
2.477
972103AH1-617 GEN
Solar/Wind Harmer
31.161
960911AF2-382 GEN
Solar/Wind Harmer
11.466
971461AH1-227 GEN
Solar/Wind Harmer
7.797
270367AC2-061_GEN
Solar/Wind Harmer
4.689
270186AC1-089 GEN
Solar/Wind Harmer
9.011
970879AG2-548 GEN
Solar/Wind Harmer
11.654
972167AH1-666 GEN
Solar/Wind Harmer
11.619
252507AC2-088 GEN
Solar/Wind Harmer
2.586
958171AF2-111 GEN
Solar/Wind Harmer
35.846
339243AC2-075 GEN1
Solar/Wind Harmer
0.648
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
252524AE2-267 GEN
Solar/Wind Harmer
2.234
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
7.507
253317AC1-085 GEN4
Solar/Wind Harmer
11.825
946181AF1-283 GEN
Solar/Wind Harmer
18.362
253394AE2-221_GEN
Solar/Wind Harmer
6.325
970455AG2-298 GEN
Solar/Wind Harmer
4.865
970653AG2-424 GEN
Solar/Wind Harmer
0.96
339206AE1-143 GEN
Solar/Wind Harmer
2.932
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
20.406
24379505HDWTR1G C
Solar/Wind Harmer
10.752
270240V3-007_GEN2
Solar/Wind Harmer
8.412
253303V4-073 C
Solar/Wind Harmer
0.157
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
12.206
247642Z2-115 C
Solar/Wind Harmer
0.086
965461AG1-414 GEN
Solar/Wind Harmer
3.058
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
7.583
946031AF1-268 GEN
Solar/Wind Harmer
11.153
24386205FR-12G C
Solar/Wind Harmer
5.756
960071AF2-298 GEN
Solar/Wind Harmer
2.031
339255AE2-071 GEN
Solar/Wind Harmer
1.57
339250AF1-203 GEN
Solar/Wind Harmer
0.808
24690905MDL-1G C
Solar/Wind Harmer
10.73
970781AG2-491 GEN
Solar/Wind Harmer
13.365
962031AG1-047 GEN
Solar/Wind Harmer
4.019
274772LINCOLN ;3U
Adder
11.001
972259AH1-714 GEN
Adder
24.853
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
274682WAUKEGAN ;7U
Adder
7.239
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
957741AF2-068 GEN
Solar/Wind Harmer
8.281
270594AE1-207 GEN
Solar/Wind Harmer
18.313
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
2.824
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
11.163
24386605FR-22G C
Solar/Wind Harmer
5.776
24791305MDL-5G
Solar/Wind Harmer
3.222
945371AF1-202 GEN
Solar/Wind Harmer
9.316
958861AF2-177 GEN
Solar/Wind Harmer
14.534
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
274745AC1-111 GEN9
Adder
7.28
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6428.58
MW Contribution:
5.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
962771AG1-126 GEN
Solar/Wind Harmer
46.005
970153AG2-106 GEN
Solar/Wind Harmer
29.378
971191AH1-055 GEN
Solar/Wind Harmer
29.882
972103AH1-617 GEN
Solar/Wind Harmer
21.74
960911AF2-382 GEN
Solar/Wind Harmer
7.999
971461AH1-227 GEN
Solar/Wind Harmer
5.44
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
7.453
972167AH1-666 GEN
Solar/Wind Harmer
8.106
252507AC2-088 GEN
Solar/Wind Harmer
0.453
958171AF2-111 GEN
Solar/Wind Harmer
25.009
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
8.38
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
12.81
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.77
970653AG2-424 GEN
Solar/Wind Harmer
0.96
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
14.237
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
8.358
247642Z2-115 C
Solar/Wind Harmer
0.004
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
27.062
270399AC1-101 GEN
Solar/Wind Harmer
3.79
270400AC1-102 GEN
Solar/Wind Harmer
3.79
970281AG2-184 GEN
Solar/Wind Harmer
22.827
971985AH1-537 GEN
Solar/Wind Harmer
3.231
941621AE2-160 GEN
Adder
5.034
971313AH1-133 GEN
Solar/Wind Harmer
5.062
972163AH1-664 GEN
Solar/Wind Harmer
11.291
972165AH1-665 GEN
Solar/Wind Harmer
9.043
339216AC1-074 GEN
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.728
270263AC1-001 GEN
Solar/Wind Harmer
0.978
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971061AG2-657 GEN
Solar/Wind Harmer
6.001
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
1.788
963841AG1-237 GEN
Solar/Wind Harmer
4.07
971029AG2-637 GEN
Solar/Wind Harmer
14.087
24386405FR-21G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.546
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.372
971609AH1-304 GEN
Solar/Wind Harmer
1.521
964611AG1-324 GEN
Solar/Wind Harmer
3.625
270432AC2-029 GEN
Solar/Wind Harmer
4.119
944221AF1-090 GEN
Solar/Wind Harmer
5.449
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.362
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
971611AH1-305 GEN
Solar/Wind Harmer
5.499
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.649
966391AG1-508 GEN
Solar/Wind Harmer
1.42
970169AG2-114 GEN
Solar/Wind Harmer
9.156
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
0.996
274877BISHOP HL;1U
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
1.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
970073AG2-061 GEN
Solar/Wind Harmer
3.032
276741O09 GEN1
Solar/Wind Harmer
0.321
970833AG2-524 GEN
Solar/Wind Harmer
10.003
970833AG2-524 GEN
Solar/Wind Harmer
6.669
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
276861AD2-134 GEN
Solar/Wind Harmer
0.162
276863AD2-134 GEN
Solar/Wind Harmer
0.162
971675AH1-338 GEN
Solar/Wind Harmer
3.544
971171AH1-044 GEN
Solar/Wind Harmer
18.173
971681AH1-341 GEN
Solar/Wind Harmer
14.63
972267AH1-718 GEN
Adder
5.423
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
274823ROCKFORD ;21
Adder
25.367
971411AH1-196 GEN
Solar/Wind Harmer
13.626
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
960591AF2-350 GEN
Solar/Wind Harmer
9.078
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
16.719
962761AG1-125 GEN
Solar/Wind Harmer
46.005
970149AG2-104 GEN
Solar/Wind Harmer
24.844
970155AG2-107 GEN
Solar/Wind Harmer
29.378
971687AH1-348 GEN
Solar/Wind Harmer
1.062
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
19.107
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
11.165
252510AF1-249 C
Solar/Wind Harmer
0.075
25196008MFTGT1
Adder
1.98
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.854
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
4.631
970773AG2-487 GEN
Solar/Wind Harmer
1.693
270273AD2-016 GEN
Solar/Wind Harmer
0.98
24728605AND G2
Adder
5.248
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.957
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
10.535
963741AG1-226 GEN
Solar/Wind Harmer
22.28
964901AG1-354 GEN
Solar/Wind Harmer
14.121
270594AE1-207 GEN
Solar/Wind Harmer
10.536
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
2.038
970825AG2-519 GEN
Solar/Wind Harmer
3.334
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.02
965911AG1-460 GEN
Solar/Wind Harmer
1.852
965651AG1-433 GEN
Solar/Wind Harmer
2.715
276621W2-048 GEN
Solar/Wind Harmer
0.463
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.546
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.866
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.925
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.831
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.358
270055AF2-134 C O1
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
27.326
971997AH1-543 GEN
Solar/Wind Harmer
4.779
253333AC1-068 GEN
Solar/Wind Harmer
0.01
276882AE2-255 GEN
Solar/Wind Harmer
1.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
276805AD2-038 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.321
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.477
274861TOP CROP ;1U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.28
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
27.26
959081AF2-199 GEN
Solar/Wind Harmer
9.087
962781AG1-127 GEN
Solar/Wind Harmer
8.648
971067AG2-660 GEN
Solar/Wind Harmer
3.029
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
970819AG2-516 GEN
Solar/Wind Harmer
10.9
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
2.038
970191AG2-125 GEN
Solar/Wind Harmer
2.419
970825AG2-519 GEN
Solar/Wind Harmer
7.074
946031AF1-268 GEN
Solar/Wind Harmer
8.922
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.325
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.91
942481AE2-261 GEN
Solar/Wind Harmer
27.692
957381AF2-032 GEN
Solar/Wind Harmer
2.099
971993AH1-541 GEN
Solar/Wind Harmer
4.271
943031AE2-326 GEN
Solar/Wind Harmer
4.803
965091AG1-374 GEN
Solar/Wind Harmer
27.602
959611AF2-252 GEN
Solar/Wind Harmer
3.067
944531AF1-118 GEN
Solar/Wind Harmer
41.107
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.304
970571AG2-364 GEN
Solar/Wind Harmer
18.217
253325AC1-069 GEN
Solar/Wind Harmer
0.01
276868AE1-113 GEN
Solar/Wind Harmer
1.82
274879MINONK ;1U
Solar/Wind Harmer
0.38
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.001
970707AG2-453 GEN
Solar/Wind Harmer
29.702
943121AE2-341 GEN
Solar/Wind Harmer
15.239
943591AF1-030 GEN
Solar/Wind Harmer
10.134
274862TOP CROP ;2U
Solar/Wind Harmer
1.227
972259AH1-714 GEN
Adder
24.853
274855GSG-6 ;RU
Solar/Wind Harmer
0.332
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
946671AF1-331 GEN
Solar/Wind Harmer
0.969
959091AF2-200 GEN
Solar/Wind Harmer
18.173
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
965931AG1-462 GEN
Solar/Wind Harmer
23.167
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
971087AG2-675 GEN
Solar/Wind Harmer
4.845
274682WAUKEGAN ;7U
Adder
7.239
274887GEN-1.85
Solar/Wind Harmer
0.236
276843GEN-1.7
Solar/Wind Harmer
0.294
276806AD2-047 C O1
Solar/Wind Harmer
5.144
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
970373AG2-245 GEN
Solar/Wind Harmer
16.807
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
970913AG2-568 GEN
Solar/Wind Harmer
8.731
971225AH1-072 GEN
Solar/Wind Harmer
2.121
971227AH1-073 GEN
Solar/Wind Harmer
2.121
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971073AG2-665 GEN
Solar/Wind Harmer
7.453
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.05
972043AH1-570 GEN
Solar/Wind Harmer
2.601
972045AH1-571 GEN
Solar/Wind Harmer
2.084
25183208HLCRTG
Solar/Wind Harmer
0.001
971125AH1-004 GEN
Solar/Wind Harmer
3.97
970107AG2-081 GEN
Solar/Wind Harmer
2.978
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
9.908
971587AH1-292 GEN
Solar/Wind Harmer
7.164
964571AG1-320 GEN
Solar/Wind Harmer
8.813
270269AC2-059
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
10.085
926881AC1-175 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.492
970291AG2-192 GEN
Solar/Wind Harmer
1.223
970291AG2-192 GEN
Solar/Wind Harmer
0.565
971613AH1-306 GEN
Solar/Wind Harmer
4.515
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.061
970883AG2-550 GEN
Solar/Wind Harmer
9.352
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971485AH1-239 GEN
Solar/Wind Harmer
7.452
964781AG1-341 GEN
Solar/Wind Harmer
9.873
966021AG1-471 GEN
Solar/Wind Harmer
5.029
270031AE2-169
Solar/Wind Harmer
5.121
270599AE1-208 GEN
Solar/Wind Harmer
8.535
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
19.462
276911AD2-131_GEN
Solar/Wind Harmer
1.282
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.431
276615X2-022 GEN
Solar/Wind Harmer
0.096
276838X2-022 GEN2
Solar/Wind Harmer
0.521
960611AF2-352 GEN
Solar/Wind Harmer
3.067
942111AE2-223 GEN
Solar/Wind Harmer
2.987
276645AC1-214 GEN1
Solar/Wind Harmer
0.358
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
22.743
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
958491AF2-143 GEN
Solar/Wind Harmer
13.642
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.467
958481AF2-142 GEN
Solar/Wind Harmer
13.633
962691AG1-118 GEN
Solar/Wind Harmer
27.261
971341AH1-150 GEN
Solar/Wind Harmer
18.173
971343AH1-151 GEN
Solar/Wind Harmer
18.173
938861AE1-114 GEN
Solar/Wind Harmer
5.149
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
276893AG1-478 C
Solar/Wind Harmer
0.606
274674JOLIET 9 ;6U
Adder
20.046
942221AE2-234 GEN
Solar/Wind Harmer
3.648
274683WAUKEGAN ;8U
Adder
27.432
971277AH1-098 GEN
Solar/Wind Harmer
3.633
274888KELLY CRK;1U
Solar/Wind Harmer
0.529
276776AD2-060 GEN
Solar/Wind Harmer
0.968
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.72 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6225.55
MW Contribution:
7.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.774
957241AF2-018 GEN
Solar/Wind Harmer
7.761
270053AF1-130 C
Solar/Wind Harmer
31.012
270399AC1-101 GEN
Solar/Wind Harmer
7.341
270400AC1-102 GEN
Solar/Wind Harmer
7.341
970281AG2-184 GEN
Solar/Wind Harmer
33.013
971985AH1-537 GEN
Solar/Wind Harmer
28.037
941621AE2-160 GEN
Adder
5.08
962211AG1-066 GEN
Solar/Wind Harmer
3.683
971313AH1-133 GEN
Solar/Wind Harmer
8.881
972163AH1-664 GEN
Solar/Wind Harmer
14.676
972165AH1-665 GEN
Solar/Wind Harmer
11.741
339216AC1-074 GEN
Solar/Wind Harmer
2.418
25196108MFTGT2
Adder
2.204
25196108MFTGT2
Adder
2.047
3429211JKCT 2G
Adder
16.761
25196408WSDLE3
Adder
12.643
25196308WSDLE2
Adder
12.533
25196208WSDLE1
Adder
12.501
25196708WSDLE6
Adder
12.47
25196508WSDLE4
Adder
12.156
24734705WLF1G3
Adder
8.239
24734805WLF1G4
Adder
8.239
24734905WLF1G5
Adder
8.239
253433AC1-085 GEN1
Solar/Wind Harmer
7.58
253432AC1-085 GEN2
Solar/Wind Harmer
0.381
270340AC2-060 GEN
Solar/Wind Harmer
4.299
253406AD2-031_GEN
Solar/Wind Harmer
1.814
270263AC1-001 GEN
Solar/Wind Harmer
1.479
270444AC2-157 GEN1
Solar/Wind Harmer
7.893
270445AC2-157 GEN2
Solar/Wind Harmer
7.893
270291AC1-194 GEN
Solar/Wind Harmer
7.194
24735105WLF2G1
Adder
8.122
270356AE2-297 GEN
Solar/Wind Harmer
6.397
971061AG2-657 GEN
Solar/Wind Harmer
12.414
253372AE2-315 SEC3
Adder
2.597
253372AE2-315 SEC3
Adder
2.597
25306009OHH W.
Adder
3.946
970289AG2-191 GEN
Solar/Wind Harmer
2.589
963841AG1-237 GEN
Solar/Wind Harmer
14.866
971029AG2-637 GEN
Solar/Wind Harmer
20.401
24386405FR-21G C
Solar/Wind Harmer
5.837
24387005FR-3G C
Solar/Wind Harmer
5.368
270543AE2-219 C
Solar/Wind Harmer
13.544
946581AF1-322 GEN
Solar/Wind Harmer
13.818
24691005MDL-2G C
Solar/Wind Harmer
4.994
945581AF1-223 GEN
Solar/Wind Harmer
6.119
247536S-71 GEN
Solar/Wind Harmer
5.458
964611AG1-324 GEN
Solar/Wind Harmer
5.25
270432AC2-029 GEN
Solar/Wind Harmer
9.42
944221AF1-090 GEN
Solar/Wind Harmer
14.705
961761AG1-017 GEN
Solar/Wind Harmer
0.575
24729505KEY G4
Adder
8.64
274775LINCOLN ;6U
Adder
11.119
274776LINCOLN ;7U
Adder
11.119
274777LINCOLN ;8U
Adder
11.119
274744AC1-111 GEN8
Adder
7.358
24289405MTG1
50/50
11.396
243186AF1-051 GEN
50/50
12.548
24318705GVG2
50/50
11.631
24721805FLATG3
50/50
2.774
972203AH1-686 GEN
Adder
4.442
24723205RIVRG3
Adder
36.155
24686505CER G6
Adder
15.668
270331AC1-082 GEN3
Solar/Wind Harmer
0.851
944971AF1-162 GEN
Solar/Wind Harmer
12.224
960001AF2-291 GEN
Solar/Wind Harmer
5.265
971403AH1-188 GEN
Solar/Wind Harmer
24.159
962761AG1-125 GEN
Solar/Wind Harmer
55.006
970149AG2-104 GEN
Solar/Wind Harmer
33.966
970155AG2-107 GEN
Solar/Wind Harmer
23.985
971687AH1-348 GEN
Solar/Wind Harmer
1.536
24728305BUCHG2
Adder
6.863
970091AG2-072 GEN
Adder
114.157
971073AG2-665 GEN
Solar/Wind Harmer
1.71
945681AF1-233 GEN
Solar/Wind Harmer
27.651
339221AD2-048_GEN
Solar/Wind Harmer
2.223
25196808ZIMRHP
Adder
109.659
252516AE2-318_GEN
Solar/Wind Harmer
14.428
252510AF1-249 C
Solar/Wind Harmer
0.6
25196008MFTGT1
Adder
1.999
943111AE2-339 GEN
Solar/Wind Harmer
1.269
25194608D.CRK4
Adder
2.359
3429241JKCT 3G
Adder
16.981
3429421JKCT 10G
Adder
11.925
253316AC1-085 GEN3
Solar/Wind Harmer
11.942
946171AF1-282 GEN
Solar/Wind Harmer
14.264
339211AE2-254 GEN
Solar/Wind Harmer
2.136
24735205WLF2G2
Adder
8.122
253398AE2-221_GEN2
Solar/Wind Harmer
6.388
270222AC2-111 GEN
Solar/Wind Harmer
6.219
944031AF1-071 GEN
Solar/Wind Harmer
1.399
970653AG2-424 GEN
Solar/Wind Harmer
6.706
270273AD2-016 GEN
Solar/Wind Harmer
3.685
24728605AND G2
Adder
5.301
339241AF1-083 GEN
Solar/Wind Harmer
2.292
942081AE2-220 GEN
Solar/Wind Harmer
8.785
270209AC1-174_GEN
Solar/Wind Harmer
5.591
270437AC2-090 C
Solar/Wind Harmer
7.667
270239V3-007_GEN1
Solar/Wind Harmer
2.364
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
276903AD2-071 C
Solar/Wind Harmer
13.662
963741AG1-226 GEN
Solar/Wind Harmer
61.351
964901AG1-354 GEN
Solar/Wind Harmer
20.45
270594AE1-207 GEN
Solar/Wind Harmer
18.503
270032AE2-172
Solar/Wind Harmer
6.337
270005AE1-210 C O1
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
2.854
25326309TAIT D
Adder
1.488
24385905FR-11G C
Solar/Wind Harmer
11.279
24386605FR-22G C
Solar/Wind Harmer
5.837
24791305MDL-5G
Solar/Wind Harmer
3.256
945371AF1-202 GEN
Solar/Wind Harmer
9.414
958861AF2-177 GEN
Solar/Wind Harmer
14.687
274773LINCOLN ;4U
Adder
11.119
24289405MTG1
50/50
11.396
24318705GVG2
50/50
11.631
24722005FLATG5
50/50
2.774
24721905FLATG4
50/50
50.672
24686405CER G5
Adder
15.544
270330AC1-082 GEN2
Solar/Wind Harmer
0.849
270329AC1-082 GEN1
Solar/Wind Harmer
0.849
962771AG1-126 GEN
Solar/Wind Harmer
55.006
970153AG2-106 GEN
Solar/Wind Harmer
23.985
971191AH1-055 GEN
Solar/Wind Harmer
31.424
957541AF2-048 GEN
Solar/Wind Harmer
2.499
972103AH1-617 GEN
Solar/Wind Harmer
31.441
960911AF2-382 GEN
Solar/Wind Harmer
11.571
971461AH1-227 GEN
Solar/Wind Harmer
7.869
270367AC2-061_GEN
Solar/Wind Harmer
4.734
270186AC1-089 GEN
Solar/Wind Harmer
9.096
970879AG2-548 GEN
Solar/Wind Harmer
11.766
972167AH1-666 GEN
Solar/Wind Harmer
11.731
252507AC2-088 GEN
Solar/Wind Harmer
2.611
958171AF2-111 GEN
Solar/Wind Harmer
36.196
339243AC2-075 GEN1
Solar/Wind Harmer
0.655
252519AF1-045_GEN
Solar/Wind Harmer
5.251
25196008MFTGT1
Adder
1.936
25194608D.CRK4
Adder
2.359
252524AE2-267 GEN
Solar/Wind Harmer
2.256
25196608WSDLE5
Adder
12.281
3429391JKCT 9G
Adder
11.925
970093AG2-073 GEN
Solar/Wind Harmer
7.582
253317AC1-085 GEN4
Solar/Wind Harmer
11.942
946181AF1-283 GEN
Solar/Wind Harmer
18.543
253394AE2-221_GEN
Solar/Wind Harmer
6.388
970455AG2-298 GEN
Solar/Wind Harmer
4.914
970653AG2-424 GEN
Solar/Wind Harmer
0.97
339206AE1-143 GEN
Solar/Wind Harmer
2.962
972273AH1-721 GEN
Adder
115.342
24728705AND G3
Adder
11.088
24728505AND G1
Adder
5.301
970193AG2-126 GEN
Solar/Wind Harmer
20.616
24379505HDWTR1G C
Solar/Wind Harmer
10.862
270240V3-007_GEN2
Solar/Wind Harmer
8.498
253303V4-073 C
Solar/Wind Harmer
0.159
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
270346AE1-212 GEN
Solar/Wind Harmer
12.332
247642Z2-115 C
Solar/Wind Harmer
0.087
965461AG1-414 GEN
Solar/Wind Harmer
3.09
970289AG2-191 GEN
Solar/Wind Harmer
1.046
270004AE1-209 GEN
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
7.662
946031AF1-268 GEN
Solar/Wind Harmer
11.269
24386205FR-12G C
Solar/Wind Harmer
5.816
960071AF2-298 GEN
Solar/Wind Harmer
2.052
339255AE2-071 GEN
Solar/Wind Harmer
1.586
339250AF1-203 GEN
Solar/Wind Harmer
0.817
24690905MDL-1G C
Solar/Wind Harmer
10.842
970781AG2-491 GEN
Solar/Wind Harmer
13.505
962031AG1-047 GEN
Solar/Wind Harmer
4.061
274772LINCOLN ;3U
Adder
11.119
972259AH1-714 GEN
Adder
25.12
274760LEE CO EC;1U
Adder
12.246
274767LEE CO EC;8U
Adder
12.101
274729ELWOOD EC;1P
Adder
21.634
274730ELWOOD EC;6P
Adder
21.634
274734ELWOOD EC;8P
Adder
21.634
274736ELWOOD EC;9P
Adder
21.634
274682WAUKEGAN ;7U
Adder
23.647
237048AF1-022 C
Solar/Wind Helper
0.229
237046AF1-021 C
Solar/Wind Helper
0.396
235058AG1-386 C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
1.065
964991AG1-363 GEN
Solar/Wind Helper
4.388
202652Y1-033 WT C
Solar/Wind Helper
0.652
238127S14_GEN_2
Solar/Wind Helper
0.805
20092526R32
Solar/Wind Helper
1.303
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20303426NA_O38_P22
Solar/Wind Helper
1.11
203993AD2-133_GEN1
Solar/Wind Helper
1.142
203854AF2-039 C
Solar/Wind Helper
0.352
20398826ARMNA MT
Solar/Wind Helper
1.645
941421AE2-139 GEN
Solar/Wind Helper
2.555
209137AF2-361 C
Solar/Wind Helper
1.523
946731AF1-337 GEN
Solar/Wind Helper
0.496
212507AE2-042_GEN
Solar/Wind Helper
1.759
961341AF2-425 GEN
Solar/Wind Helper
0.495
961301AF2-421 GEN
Solar/Wind Helper
0.492
963151AG1-164 GEN
Solar/Wind Helper
0.492
211065PSPA IPP
Solar/Wind Helper
0.167
207518AF1-320_GEN
Solar/Wind Helper
1.705
20675728RH_W2-091
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.032
203975AE1-071-GEN
Solar/Wind Helper
2.659
207484AF2-139 C O1
Solar/Wind Helper
0.091
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
20674628WNG_W3-110
Solar/Wind Helper
0.097
20676328BVR_Y1-020
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.072
207439AE1-081 C O1
Solar/Wind Helper
0.02
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.485
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.172
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.083
20720528MAN_W1-024
Solar/Wind Helper
0.03
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219276PARKLANDSO C
Solar/Wind Helper
0.095
20715828PEM_W1-120
Solar/Wind Helper
0.101
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.12
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.057
228729W2-030 C
Solar/Wind Helper
0.116
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.52
232408W1-005 C
Solar/Wind Helper
0.52
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.52
233944AB2-135 GEN
Solar/Wind Helper
0.605
233918AB1-142 GEN
Solar/Wind Helper
0.515
235063AE1-101 C2
Solar/Wind Helper
1.456
205916AD1-020 GEN
Solar/Wind Helper
1.701
237001AB1-127_GEN
Solar/Wind Helper
0.386
23777901MDS_W4-102
Solar/Wind Helper
0.149
208835TUHI V3-051
Solar/Wind Helper
0.021
238175AF1-290_GEN
Solar/Wind Helper
0.125
957741AF2-068 GEN
Solar/Wind Harmer
8.369
243186AF1-051 GEN
50/50
12.548
24721705FLATG2
50/50
41.198
24723005RIVRG1
Adder
36.155
24723105RIVRG2
Adder
36.155
927014AC1-188 GEN
Solar/Wind Harmer
2.499
970913AG2-568 GEN
Solar/Wind Harmer
10.718
971225AH1-072 GEN
Solar/Wind Harmer
3.068
971227AH1-073 GEN
Solar/Wind Harmer
3.068
24728205BUCHG1
Adder
6.863
962581AG1-107 GEN
Solar/Wind Harmer
7.459
961491AF2-440 GEN
Solar/Wind Harmer
3.1
971073AG2-665 GEN
Solar/Wind Harmer
11.766
970879AG2-548 GEN
Solar/Wind Harmer
1.71
252509AD1-136 GEN
Solar/Wind Harmer
0.373
972043AH1-570 GEN
Solar/Wind Harmer
3.62
972045AH1-571 GEN
Solar/Wind Harmer
2.896
25183208HLCRTG
Solar/Wind Harmer
8.737
971125AH1-004 GEN
Solar/Wind Harmer
5.746
970107AG2-081 GEN
Solar/Wind Harmer
4.31
25194408D.CRK1
Adder
10.853
25194508D.CRK3
Adder
2.029
942891AE2-308 GEN
Solar/Wind Harmer
14.341
253415AE1-040 GEN
Solar/Wind Harmer
1.586
964571AG1-320 GEN
Solar/Wind Harmer
11.455
270269AC2-059
Solar/Wind Harmer
12.928
24728805RICHG1
Adder
5.238
24728905RICHG2
Adder
5.238
945391AF1-204 GEN
Solar/Wind Harmer
19.154
926881AC1-175 GEN
Solar/Wind Harmer
7.667
253370AE2-315 SEC1
Adder
2.746
270383AD1-128 GEN
Solar/Wind Harmer
8.356
339231AF1-038_GEN
Solar/Wind Harmer
2.483
24725505WLD G2 C
Solar/Wind Harmer
5.437
24699105WLD G1 C
Solar/Wind Harmer
5.374
339236AF1-050_GEN
Solar/Wind Harmer
2.477
970241AG2-163 GEN
Solar/Wind Harmer
34.084
970291AG2-192 GEN
Solar/Wind Harmer
1.771
970291AG2-192 GEN
Solar/Wind Harmer
0.57
253349AC2-067 GEN
Solar/Wind Harmer
2.769
253400AC2-068 GEN
Solar/Wind Harmer
1.114
25322209TAIT E
Adder
13.248
25322209TAIT E
Adder
12.95
24387305FR-4G C
Solar/Wind Harmer
6.894
966841AG1-555 GEN
Solar/Wind Harmer
3.407
970883AG2-550 GEN
Solar/Wind Harmer
13.544
970885AG2-551 GEN
Solar/Wind Harmer
3.15
270180AB1-006 GEN1
Solar/Wind Harmer
9.713
24697605MDL-3G C
Solar/Wind Harmer
4.978
24755605MDL-5G
Solar/Wind Harmer
3.256
24697905MDL-4G C
Solar/Wind Harmer
3.099
270181AB1-006 GEN2
Solar/Wind Harmer
0.966
971485AH1-239 GEN
Solar/Wind Harmer
10.793
964781AG1-341 GEN
Solar/Wind Harmer
14.3
966021AG1-471 GEN
Solar/Wind Harmer
7.284
270031AE2-169
Solar/Wind Harmer
10.99
270599AE1-208 GEN
Solar/Wind Harmer
10.99
945421AF1-207 GEN
Solar/Wind Harmer
18.926
957841AF2-078 GEN
Solar/Wind Harmer
8.147
25326109MON D
Adder
1.772
964611AG1-324 GEN
Solar/Wind Harmer
0.704
247621Y3-024
Adder
0.324
270201AC2-176 GEN
Solar/Wind Harmer
6.903
274770LINCOLN ;1U
Adder
11.119
274771LINCOLN ;2U
Adder
11.119
274696ROCKY RD ;4P
Adder
15.001
274695ROCKY RD ;2P
Adder
14.655
274693ROCKY RD ;1P
Adder
14.51
274764LEE CO EC;5U
Adder
12.274
274765LEE CO EC;6U
Adder
12.274
274762LEE CO EC;3U
Adder
12.246
274763LEE CO EC;4U
Adder
12.13
274697ROCKY RD ;3P
Adder
3.981
274674JOLIET 9 ;6U
Adder
20.261
972235AH1-702 GEN1
Adder
3.317
972236AH1-702 GEN2
Adder
2.884
23585401KL_K28_T16
Solar/Wind Helper
1.522
237043AE2-125 C
Solar/Wind Helper
0.207
23751201ROTHROCK
Solar/Wind Helper
0.874
235054AD2-180 GEN
Solar/Wind Helper
2.021
238117U2-030
Solar/Wind Helper
0.341
235531U2-073 GEN
Solar/Wind Helper
3.241
962101AG1-054 GEN
Solar/Wind Helper
0.711
254304AE2-114 C
Solar/Wind Helper
0.238
254305AE2-115 C
Solar/Wind Helper
0.238
20083426SW_E13_K22
Solar/Wind Helper
0.063
241967AE2-285_GEN
Solar/Wind Helper
0.691
241801AE1-079 GEN
Solar/Wind Helper
0.27
946071AF1-272 GEN
Solar/Wind Helper
3.032
20088826HIGHLAND
Solar/Wind Helper
1.005
203961AE2-224 GEN
Solar/Wind Helper
2.695
203818AF1-086 GEN
Solar/Wind Helper
1.876
203853AF1-134 C O1
Solar/Wind Helper
0.53
946381AF1-302 GEN
Solar/Wind Helper
0.245
203946AE2-131 C
Solar/Wind Helper
0.526
203954AE2-126 C
Solar/Wind Helper
0.519
940863AE2-074 GEN
Solar/Wind Helper
0.501
203804AE2-113_GEN
Solar/Wind Helper
1.916
946751AF1-339 GEN
Solar/Wind Helper
0.496
961431AF2-434 GEN
Solar/Wind Helper
0.495
316097T157 G90
Solar/Wind Helper
1.146
203835AF1-098 GEN
Solar/Wind Helper
1.948
207471AF2-354 C
Solar/Wind Helper
0.183
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.054
20674328GAR_V4-001
Solar/Wind Helper
0.024
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.15
20714828MDF_W3-079
Solar/Wind Helper
0.138
207459AE1-142 C O1
Solar/Wind Helper
0.307
20720828JCB_W4-025
Solar/Wind Helper
0.067
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.084
219304NAMERICA C
Solar/Wind Helper
0.138
219906AC1-017 C
Solar/Wind Helper
0.044
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.157
219904AC1-010 C
Solar/Wind Helper
0.063
228754AB1-001 C
Solar/Wind Helper
0.027
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.015
233952AC2-187 GEN
Solar/Wind Helper
0.239
233954AC2-188 GEN
Solar/Wind Helper
0.239
233994AC2-023 GEN
Solar/Wind Helper
0.986
232410W1-006 C
Solar/Wind Helper
0.52
232428Y3-058 C
Solar/Wind Helper
0.347
234015AF2-250 C
Solar/Wind Helper
0.039
233946AB2-136 GEN
Solar/Wind Helper
0.583
234036AF2-325 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.368
233930AB2-032 GEN
Solar/Wind Helper
0.39
232436AB1-176 C
Solar/Wind Helper
0.046
235062AE1-101 C1
Solar/Wind Helper
1.456
237080AD1-060 GEN
Solar/Wind Helper
0.295
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.235
237006AB1-125 GEN
Solar/Wind Helper
0.109
223401AF1-299 GEN
Solar/Wind Helper
0.336
223402AF1-300 C
Solar/Wind Helper
0.336
274746AC1-111 G10
Adder
7.358
972267AH1-718 GEN
Adder
5.481
274731ELWOOD EC;2P
Adder
21.634
274733ELWOOD EC;3P
Adder
21.634
274735ELWOOD EC;4P
Adder
21.634
274728ELWOOD EC;5P
Adder
21.634
274823ROCKFORD ;21
Adder
25.64
972228AH1-698 GEN2
Adder
4.874
972227AH1-698 GEN1
Adder
3.432
23750501ELLIOTTS
Solar/Wind Helper
0.784
23652301WDPWR_K20
Solar/Wind Helper
0.167
23750701CROSSCHOOL
Solar/Wind Helper
1.42
238118U2-030_1
Solar/Wind Helper
0.341
203955AF1-039 C O1
Solar/Wind Helper
0.43
20089126CSLMN_L13
Solar/Wind Helper
0.68
20089226LOOKOUT
Solar/Wind Helper
0.678
241997AF1-093 GEN
Solar/Wind Helper
0.278
241985AE1-237 GEN
Solar/Wind Helper
0.27
241982AE2-343 S C
Solar/Wind Helper
0.243
20088926STNY CRK
Solar/Wind Helper
0.922
203940AF1-140 C
Solar/Wind Helper
0.444
20094526CT_V3-030
Solar/Wind Helper
0.527
20088626ARWF_N39
Solar/Wind Helper
1.354
203846AF2-130 C
Solar/Wind Helper
0.494
20334926Z1-069 C
Solar/Wind Helper
1.481
200917MEHOOPANY_G
Solar/Wind Helper
2.413
209067AE2-060 GEN
Solar/Wind Helper
0.091
959431AF2-234 GEN
Solar/Wind Helper
0.993
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
959421AF2-233 GEN
Solar/Wind Helper
0.497
209054AE2-059 GEN
Solar/Wind Helper
0.09
209027LOR2_Q27
Solar/Wind Helper
1.157
212266LOR1
Solar/Wind Helper
0.337
209029WAYMART-WD
Solar/Wind Helper
0.93
961261AF2-417 GEN
Solar/Wind Helper
0.492
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.068
20676428JCR_X2-075
Solar/Wind Helper
0.073
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.172
20675528CPH_W2-050
Solar/Wind Helper
0.121
20720628TIN_W1-124
Solar/Wind Helper
0.202
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.111
20715028HAN_X4-015
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.06
959381AF2-229 GEN
Solar/Wind Helper
0.361
20390526W1-045 C
Solar/Wind Helper
0.355
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.08
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.042
228728W1-130C
Solar/Wind Helper
0.056
230434AG1-499 GEN
Solar/Wind Helper
0.24
232432Z2-076 GEN
Solar/Wind Helper
0.069
233901CHERRYDALE C
Solar/Wind Helper
0.239
233940AF2-379 C
Solar/Wind Helper
0.064
205956AE1-196_GEN
Solar/Wind Helper
0.52
205943AE1-185 GEN
Solar/Wind Helper
0.52
233915AB1-141 GEN
Solar/Wind Helper
0.515
205917AD1-020 ES
Solar/Wind Helper
0.366
237025AB1-124 C
Solar/Wind Helper
0.145
237030AB1-096 C
Solar/Wind Helper
0.059
23779801AA1-109
Solar/Wind Helper
0.167
238169AE2-226 GEN1
Solar/Wind Helper
0.55
238170AE2-226 GEN2
Solar/Wind Helper
0.55
274774LINCOLN ;5U
Adder
11.119
274745AC1-111 GEN9
Adder
7.358
274761LEE CO EC;2U
Adder
12.246
274766LEE CO EC;7U
Adder
12.101
274732ELWOOD EC;7P
Adder
21.634
274822ROCKFORD ;11
Adder
25.827
274674JOLIET 9 ;6U
Adder
20.261
274682WAUKEGAN ;7U
Adder
11.397
238185AF2-356 C
Solar/Wind Helper
2.609
20089026BF_G21_K23
Solar/Wind Helper
0.538
238120AE2-309 GEN
Solar/Wind Helper
0.508
238126S14_GEN_1
Solar/Wind Helper
0.805
254303AC2-168 GEN
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.278
23751101LEADS_P59
Solar/Wind Helper
2.213
20084626FORWARD
Solar/Wind Helper
0.4
964201AG1-281 GEN
Solar/Wind Helper
0.541
20091526CHSTN_FL
Solar/Wind Helper
0.651
238109AE1-109 GEN2
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.142
203952AE2-129 C
Solar/Wind Helper
0.526
203855AF2-088 C
Solar/Wind Helper
0.169
209071AE2-133 GEN
Solar/Wind Helper
0.09
946691AF1-333 GEN
Solar/Wind Helper
0.496
946741AF1-338 GEN
Solar/Wind Helper
0.496
961421AF2-433 GEN
Solar/Wind Helper
0.495
957921AF2-086 GEN
Solar/Wind Helper
0.49
961331AF2-424 GEN
Solar/Wind Helper
0.495
208972BECR K09
Solar/Wind Helper
0.37
963161AG1-165 GEN
Solar/Wind Helper
0.492
203830AF1-094 GEN
Solar/Wind Helper
0.492
203979AG1-198 GEN
Solar/Wind Helper
0.295
316095T157 G97
Solar/Wind Helper
1.146
23583801GRNGAP
Solar/Wind Helper
4.253
211065PSPA IPP
Solar/Wind Helper
0.167
209116AE2-175 GEN
Solar/Wind Helper
1.956
961971AG1-040 GEN
Solar/Wind Helper
0.488
20674128FR_U2-059
Solar/Wind Helper
0.004
20671928W4-073
Solar/Wind Helper
0.097
207437AD2-070 GEN
Solar/Wind Helper
0.149
207511W3-106 GEN
Solar/Wind Helper
0.029
207510AF2-138 C
Solar/Wind Helper
0.088
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.349
20673728F2S_V4-070
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
219249CENTRALDIV C
Solar/Wind Helper
0.011
205941AD2-115 GEN
Solar/Wind Helper
0.528
20716928W4-060COL
Solar/Wind Helper
0.055
219612MATRIX C
Solar/Wind Helper
0.025
207454AA2-184 E
Solar/Wind Helper
0.33
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.005
20715728PEM_W1-119
Solar/Wind Helper
0.101
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.12
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.524
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233950AC2-186 GEN
Solar/Wind Helper
0.119
232434Z2-077 GEN
Solar/Wind Helper
0.13
233923SMA
Solar/Wind Helper
0.772
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.52
232417X3-008 C
Solar/Wind Helper
0.239
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.442
233987AB2-037 GEN
Solar/Wind Helper
2.403
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
233935AB2-179 C
Solar/Wind Helper
1.3
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
208835TUHI V3-051
Solar/Wind Helper
0.021
23777801MSM_W1-116
Solar/Wind Helper
0.099
LAGNLTFEXP_LAGN->PJM
CLTF
25.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.459
TVALTFEXP_TVA->PJM
CLTF
12.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
171.353
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.863
MECLTFEXP_MEC->PJM
CLTF
22.066
SIGELTFEXP_SIGE->PJM
CLTF
0.733
NYPJM->LTFIMP_NY
CLTF
6.23
LGEELTFEXP_LGEE->PJM
CLTF
9.895
WECLTFEXP_WEC->PJM
CLTF
5.031
AG2-052LTFEXP_AG2-052->PJM
LTF
0.308
AH1-155LTFEXP_AH1-155->PJM
LTF
0.462
CPLELTFEXP_CPLE->PJM
CLTF
6.636
CBM West 2LTFEXP_CBM-W2->PJM
CBM
174.171

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.96 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6183.32
MW Contribution:
6.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
12.684
24722005FLATG5
50/50
3.326
24721905FLATG4
50/50
60.751
24318705GVG2
50/50
13.247
962771AG1-126 GEN
Solar/Wind Harmer
91.718
970153AG2-106 GEN
Solar/Wind Harmer
39.993
24686405CER G5
Adder
15.983
270330AC1-082 GEN2
Solar/Wind Harmer
0.845
270329AC1-082 GEN1
Solar/Wind Harmer
0.845
960911AF2-382 GEN
Solar/Wind Harmer
12.012
972103AH1-617 GEN
Solar/Wind Harmer
30.905
971461AH1-227 GEN
Solar/Wind Harmer
7.89
971191AH1-055 GEN
Solar/Wind Harmer
28.586
270346AE1-212 GEN
Solar/Wind Harmer
13.435
943031AE2-326 GEN
Solar/Wind Harmer
5.264
958121AF2-106 GEN
Solar/Wind Harmer
6.036
957541AF2-048 GEN
Solar/Wind Harmer
2.104
972273AH1-721 GEN
Adder
96.087
270030AE2-140 GEN
Solar/Wind Harmer
23
970093AG2-073 GEN
Solar/Wind Harmer
5.967
339206AE1-143 GEN
Solar/Wind Harmer
2.39
970879AG2-548 GEN
Solar/Wind Harmer
8.927
339255AE2-071 GEN
Solar/Wind Harmer
1.308
339250AF1-203 GEN
Solar/Wind Harmer
0.673
970653AG2-424 GEN
Solar/Wind Harmer
0.771
970455AG2-298 GEN
Solar/Wind Harmer
3.861
3429391JKCT 9G
Adder
9.153
270186AC1-089 GEN
Solar/Wind Harmer
6.641
339243AC2-075 GEN1
Solar/Wind Harmer
0.489
270367AC2-061_GEN
Solar/Wind Harmer
3.424
972167AH1-666 GEN
Solar/Wind Harmer
8.599
958171AF2-111 GEN
Solar/Wind Harmer
25.759
270018AE2-047 C O1
Solar/Wind Harmer
1.267
252507AC2-088 GEN
Solar/Wind Harmer
1.823
25196008MFTGT1
Adder
1.357
970193AG2-126 GEN
Solar/Wind Harmer
14.771
252519AF1-045_GEN
Solar/Wind Harmer
3.559
25194608D.CRK4
Adder
1.596
252524AE2-267 GEN
Solar/Wind Harmer
1.519
25196608WSDLE5
Adder
8.266
942481AE2-261 GEN
Solar/Wind Harmer
28.724
24728705AND G3
Adder
7.705
24728505AND G1
Adder
3.684
957381AF2-032 GEN
Solar/Wind Harmer
1.919
962751AG1-124 GEN
Solar/Wind Harmer
8.593
276785W4-005 GEN1
Solar/Wind Harmer
2.856
971993AH1-541 GEN
Solar/Wind Harmer
8.726
24386205FR-12G C
Solar/Wind Harmer
4.023
24721705FLATG2
50/50
49.394
243186AF1-051 GEN
50/50
14.291
24723005RIVRG1
Adder
37.759
24723105RIVRG2
Adder
37.759
970913AG2-568 GEN
Solar/Wind Harmer
11.514
24728205BUCHG1
Adder
7.18
971225AH1-072 GEN
Solar/Wind Harmer
3.076
971227AH1-073 GEN
Solar/Wind Harmer
3.076
270214AC2-123 GEN
Solar/Wind Harmer
3.345
971277AH1-098 GEN
Solar/Wind Harmer
5.707
270583AD2-179 GEN
Solar/Wind Harmer
13.318
927014AC1-188 GEN
Solar/Wind Harmer
2.104
966021AG1-471 GEN
Solar/Wind Harmer
6.141
339231AF1-038_GEN
Solar/Wind Harmer
2.061
971485AH1-239 GEN
Solar/Wind Harmer
9.077
942891AE2-308 GEN
Solar/Wind Harmer
11.161
971073AG2-665 GEN
Solar/Wind Harmer
8.927
970879AG2-548 GEN
Solar/Wind Harmer
1.298
339236AF1-050_GEN
Solar/Wind Harmer
2.021
964781AG1-341 GEN
Solar/Wind Harmer
11.789
964571AG1-320 GEN
Solar/Wind Harmer
8.983
972043AH1-570 GEN
Solar/Wind Harmer
2.731
972045AH1-571 GEN
Solar/Wind Harmer
2.185
971125AH1-004 GEN
Solar/Wind Harmer
4.363
970107AG2-081 GEN
Solar/Wind Harmer
3.272
962581AG1-107 GEN
Solar/Wind Harmer
5.294
961491AF2-440 GEN
Solar/Wind Harmer
2.2
252509AD1-136 GEN
Solar/Wind Harmer
0.26
945391AF1-204 GEN
Solar/Wind Harmer
13.723
25183208HLCRTG
Solar/Wind Harmer
5.886
25194408D.CRK1
Adder
7.34
25194508D.CRK3
Adder
1.372
276916AD2-100_GEN
Solar/Wind Harmer
20.233
276911AD2-131_GEN
Solar/Wind Harmer
4.089
970241AG2-163 GEN
Solar/Wind Harmer
23.902
276615X2-022 GEN
Solar/Wind Harmer
1.861
276838X2-022 GEN2
Solar/Wind Harmer
0.221
274880W4-005 GEN4
Solar/Wind Harmer
2.856
276174W4-005 GEN2
Solar/Wind Harmer
2.856
24387305FR-4G C
Solar/Wind Harmer
4.769
966841AG1-555 GEN
Solar/Wind Harmer
2.357
960611AF2-352 GEN
Solar/Wind Harmer
2.15
270180AB1-006 GEN1
Solar/Wind Harmer
6.648
24697605MDL-3G C
Solar/Wind Harmer
3.407
24755605MDL-5G
Solar/Wind Harmer
2.228
24697905MDL-4G C
Solar/Wind Harmer
2.121
24721605FLATG1
50/50
3.326
957241AF2-018 GEN
Solar/Wind Harmer
8.033
270053AF1-130 C
Solar/Wind Harmer
32.096
270399AC1-101 GEN
Solar/Wind Harmer
7.582
270400AC1-102 GEN
Solar/Wind Harmer
7.582
941621AE2-160 GEN
Adder
5.453
971313AH1-133 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
32.451
971061AG2-657 GEN
Solar/Wind Harmer
13.518
24734705WLF1G3
Adder
8.32
24734805WLF1G4
Adder
8.32
24734905WLF1G5
Adder
8.32
962211AG1-066 GEN
Solar/Wind Harmer
3.487
966391AG1-508 GEN
Solar/Wind Harmer
4.969
24735105WLF2G1
Adder
8.13
971331AH1-145 GEN
Solar/Wind Harmer
12.844
971329AH1-144 GEN
Solar/Wind Harmer
8.204
971985AH1-537 GEN
Solar/Wind Harmer
23.127
971981AH1-535 GEN
Solar/Wind Harmer
12.746
270069AE2-166 C O1
Solar/Wind Harmer
10.572
3429211JKCT 2G
Adder
12.98
972163AH1-664 GEN
Solar/Wind Harmer
10.818
972165AH1-665 GEN
Solar/Wind Harmer
8.654
339216AC1-074 GEN
Solar/Wind Harmer
1.805
270444AC2-157 GEN1
Solar/Wind Harmer
5.93
270445AC2-157 GEN2
Solar/Wind Harmer
5.93
270291AC1-194 GEN
Solar/Wind Harmer
5.169
25196108MFTGT2
Adder
1.544
25196108MFTGT2
Adder
1.434
944221AF1-090 GEN
Solar/Wind Harmer
10.637
25196408WSDLE3
Adder
8.509
25196308WSDLE2
Adder
8.435
25196208WSDLE1
Adder
8.414
25196708WSDLE6
Adder
8.393
25196508WSDLE4
Adder
8.182
963841AG1-237 GEN
Solar/Wind Harmer
10.358
276763AC1-053 GEN1
Solar/Wind Harmer
3.74
276764AC1-053 GEN2
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
2.091
276848AB2-070 GEN3
Solar/Wind Harmer
2.091
276849AB2-070 GEN2
Solar/Wind Harmer
2.091
270356AE2-297 GEN
Solar/Wind Harmer
4.331
24386405FR-21G C
Solar/Wind Harmer
4.038
24387005FR-3G C
Solar/Wind Harmer
3.714
274853TWINGROVE;U1
Solar/Wind Harmer
6.662
274854TWINGROVE;U2
Solar/Wind Harmer
6.522
946581AF1-322 GEN
Solar/Wind Harmer
9.458
24691005MDL-2G C
Solar/Wind Harmer
3.418
270197AD1-017 GEN1
Solar/Wind Harmer
1.417
276726Z2-087_GEN
Solar/Wind Harmer
7.262
959341AF2-225 GEN
Solar/Wind Harmer
13.777
972267AH1-718 GEN
Adder
3.77
274823ROCKFORD ;21
Adder
17.467
274744AC1-111 GEN8
Adder
4.935
274746AC1-111 G10
Adder
4.935
274728ELWOOD EC;5P
Adder
14.442
274731ELWOOD EC;2P
Adder
14.442
274733ELWOOD EC;3P
Adder
14.442
274735ELWOOD EC;4P
Adder
14.442
274675JOLIET 29;7U
Adder
26.921
274675JOLIET 29;7U
Adder
15.118
23750501ELLIOTTS
Solar/Wind Helper
0.617
23652301WDPWR_K20
Solar/Wind Helper
0.134
241997AF1-093 GEN
Solar/Wind Helper
0.235
24289405MTG1
50/50
12.684
24721805FLATG3
50/50
3.326
243186AF1-051 GEN
50/50
14.291
24318705GVG2
50/50
13.247
962761AG1-125 GEN
Solar/Wind Harmer
91.718
970149AG2-104 GEN
Solar/Wind Harmer
56.636
970155AG2-107 GEN
Solar/Wind Harmer
39.993
24723205RIVRG3
Adder
37.759
972203AH1-686 GEN
Adder
4.539
24686505CER G6
Adder
16.11
944971AF1-162 GEN
Solar/Wind Harmer
12.651
971403AH1-188 GEN
Solar/Wind Harmer
25.286
270331AC1-082 GEN3
Solar/Wind Harmer
0.847
960001AF2-291 GEN
Solar/Wind Harmer
5.171
24728305BUCHG2
Adder
7.18
971687AH1-348 GEN
Solar/Wind Harmer
1.537
24735205WLF2G2
Adder
8.13
270336AE1-100 GEN
Solar/Wind Harmer
2.029
970091AG2-072 GEN
Adder
90.254
943811AF1-049 GEN
Solar/Wind Harmer
4.254
339211AE2-254 GEN
Solar/Wind Harmer
1.701
339241AF1-083 GEN
Solar/Wind Harmer
1.857
971073AG2-665 GEN
Solar/Wind Harmer
1.298
964901AG1-354 GEN
Solar/Wind Harmer
16.708
3429241JKCT 3G
Adder
13.15
970653AG2-424 GEN
Solar/Wind Harmer
5.33
3429421JKCT 10G
Adder
9.153
943111AE2-339 GEN
Solar/Wind Harmer
0.965
339221AD2-048_GEN
Solar/Wind Harmer
1.667
945681AF1-233 GEN
Solar/Wind Harmer
20.299
25196008MFTGT1
Adder
1.401
25196808ZIMRHP
Adder
75.86
252516AE2-318_GEN
Solar/Wind Harmer
9.778
252510AF1-249 C
Solar/Wind Harmer
0.407
270173AC1-122 GEN
Solar/Wind Harmer
1.632
25194608D.CRK4
Adder
1.596
965911AG1-460 GEN
Solar/Wind Harmer
1.34
24728605AND G2
Adder
3.684
963741AG1-226 GEN
Solar/Wind Harmer
43.023
276621W2-048 GEN
Solar/Wind Harmer
5.925
276686W4-005 GEN3
Solar/Wind Harmer
2.856
24385905FR-11G C
Solar/Wind Harmer
7.803
24386605FR-22G C
Solar/Wind Harmer
4.038
24791305MDL-5G
Solar/Wind Harmer
2.228
270574AD1-017 GEN2
Solar/Wind Harmer
4.722
276655WTG1_EQ
Solar/Wind Harmer
8.017
276656WTG2_EQ
Solar/Wind Harmer
1.061
939741AE1-205 GEN
Solar/Wind Harmer
18.37
274761LEE CO EC;2U
Adder
8.393
274766LEE CO EC;7U
Adder
8.294
965091AG1-374 GEN
Solar/Wind Harmer
27.739
959611AF2-252 GEN
Solar/Wind Harmer
2.15
24690905MDL-1G C
Solar/Wind Harmer
7.42
970781AG2-491 GEN
Solar/Wind Harmer
9.243
274760LEE CO EC;1U
Adder
8.393
274767LEE CO EC;8U
Adder
8.294
274682WAUKEGAN ;7U
Adder
15.93
274729ELWOOD EC;1P
Adder
14.442
274730ELWOOD EC;6P
Adder
14.442
274734ELWOOD EC;8P
Adder
14.442
274736ELWOOD EC;9P
Adder
14.442
237048AF1-022 C
Solar/Wind Helper
0.181
237046AF1-021 C
Solar/Wind Helper
0.315
235058AG1-386 C
Solar/Wind Helper
0.425
202652Y1-033 WT C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
0.816
964991AG1-363 GEN
Solar/Wind Helper
3.339
241985AE1-237 GEN
Solar/Wind Helper
0.229
241982AE2-343 S C
Solar/Wind Helper
0.206
203955AF1-039 C O1
Solar/Wind Helper
0.338
23750701CROSSCHOOL
Solar/Wind Helper
1.086
20089126CSLMN_L13
Solar/Wind Helper
0.537
20089226LOOKOUT
Solar/Wind Helper
0.536
238118U2-030_1
Solar/Wind Helper
0.261
270181AB1-006 GEN2
Solar/Wind Harmer
0.661
942111AE2-223 GEN
Solar/Wind Harmer
7.529
24728805RICHG1
Adder
3.447
24728905RICHG2
Adder
3.447
274764LEE CO EC;5U
Adder
8.413
274765LEE CO EC;6U
Adder
8.413
274762LEE CO EC;3U
Adder
8.393
274763LEE CO EC;4U
Adder
8.314
972235AH1-702 GEN1
Adder
2.262
972236AH1-702 GEN2
Adder
1.967
274683WAUKEGAN ;8U
Adder
18.687
274683WAUKEGAN ;8U
Adder
15.753
274696ROCKY RD ;4P
Adder
10.103
274695ROCKY RD ;2P
Adder
9.87
274693ROCKY RD ;1P
Adder
9.773
274697ROCKY RD ;3P
Adder
2.681
274674JOLIET 9 ;6U
Adder
13.524
237043AE2-125 C
Solar/Wind Helper
0.166
254304AE2-114 C
Solar/Wind Helper
0.201
254305AE2-115 C
Solar/Wind Helper
0.201
962101AG1-054 GEN
Solar/Wind Helper
0.598
241967AE2-285_GEN
Solar/Wind Helper
0.586
241801AE1-079 GEN
Solar/Wind Helper
0.229
23585401KL_K28_T16
Solar/Wind Helper
1.176
23751201ROTHROCK
Solar/Wind Helper
0.671
235054AD2-180 GEN
Solar/Wind Helper
1.553
238117U2-030
Solar/Wind Helper
0.261
946071AF1-272 GEN
Solar/Wind Helper
2.433
20083426SW_E13_K22
Solar/Wind Helper
0.05
945421AF1-207 GEN
Solar/Wind Harmer
3.217
274822ROCKFORD ;11
Adder
17.595
274828WAUKEGAN ;BP
Adder
9.796
274682WAUKEGAN ;7U
Adder
15.93
274745AC1-111 GEN9
Adder
4.935
274732ELWOOD EC;7P
Adder
14.442
274674JOLIET 9 ;6U
Adder
13.524
274676JOLIET 29;8U
Adder
26.921
254303AC2-168 GEN
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.235
238185AF2-356 C
Solar/Wind Helper
2.008
20089026BF_G21_K23
Solar/Wind Helper
0.425
LAGNLTFEXP_LAGN->PJM
CLTF
21.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.819
TVALTFEXP_TVA->PJM
CLTF
11.07
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.561
MECLTFEXP_MEC->PJM
CLTF
15.956
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
4.806
LGEELTFEXP_LGEE->PJM
CLTF
7.592
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.205
AH1-155LTFEXP_AH1-155->PJM
LTF
0.307
CPLELTFEXP_CPLE->PJM
CLTF
7.6
CBM West 2LTFEXP_CBM-W2->PJM
CBM
138.522

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4976.63
MW Contribution:
4.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.475
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
24.531
270399AC1-101 GEN
Solar/Wind Harmer
3.431
270400AC1-102 GEN
Solar/Wind Harmer
3.431
941621AE2-160 GEN
Adder
4.685
970281AG2-184 GEN
Solar/Wind Harmer
20.069
971313AH1-133 GEN
Solar/Wind Harmer
4.633
971061AG2-657 GEN
Solar/Wind Harmer
5.63
24734705WLF1G3
Adder
7.275
24734805WLF1G4
Adder
7.275
24734905WLF1G5
Adder
7.275
971985AH1-537 GEN
Solar/Wind Harmer
2.606
24735105WLF2G1
Adder
7.131
966391AG1-508 GEN
Solar/Wind Harmer
1.323
971331AH1-145 GEN
Solar/Wind Harmer
10.902
971329AH1-144 GEN
Solar/Wind Harmer
4.007
971981AH1-535 GEN
Solar/Wind Harmer
5.247
972163AH1-664 GEN
Solar/Wind Harmer
8.578
972165AH1-665 GEN
Solar/Wind Harmer
6.87
3429211JKCT 2G
Adder
12.836
339216AC1-074 GEN
Solar/Wind Harmer
0.202
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.606
25196108MFTGT2
Adder
1.492
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
9.098
25196308WSDLE2
Adder
9.019
25196208WSDLE1
Adder
8.997
25196708WSDLE6
Adder
8.974
25196508WSDLE4
Adder
8.748
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.692
270069AE2-166 C O1
Solar/Wind Harmer
6.22
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.926
963841AG1-237 GEN
Solar/Wind Harmer
2.866
24386405FR-21G C
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.257
276848AB2-070 GEN3
Solar/Wind Harmer
0.256
276849AB2-070 GEN2
Solar/Wind Harmer
0.257
970289AG2-191 GEN
Solar/Wind Harmer
1.233
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.69
274854TWINGROVE;U2
Solar/Wind Harmer
0
25306009OHH W.
Adder
2.654
253372AE2-315 SEC3
Adder
1.743
253372AE2-315 SEC3
Adder
1.743
270543AE2-219 C
Solar/Wind Harmer
4.484
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.721
247536S-71 GEN
Solar/Wind Harmer
0.254
971611AH1-305 GEN
Solar/Wind Harmer
3.778
946321AF1-296 GEN
Solar/Wind Harmer
3.554
274877BISHOP HL;1U
Solar/Wind Harmer
0.211
971609AH1-304 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
2.468
970169AG2-114 GEN
Solar/Wind Harmer
6.325
276741O09 GEN1
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.763
926823AC1-168 GEN
Solar/Wind Harmer
1.07
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.116
274856ECOGROVE ;U1
Solar/Wind Harmer
0.147
274823ROCKFORD ;21
Adder
17.485
971171AH1-044 GEN
Solar/Wind Harmer
12.516
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971675AH1-338 GEN
Solar/Wind Harmer
2.437
971411AH1-196 GEN
Solar/Wind Harmer
9.369
970073AG2-061 GEN
Solar/Wind Harmer
2.078
274744AC1-111 GEN8
Adder
4.965
274746AC1-111 G10
Adder
4.965
970833AG2-524 GEN
Solar/Wind Harmer
6.809
970833AG2-524 GEN
Solar/Wind Harmer
4.54
274728ELWOOD EC;5P
Adder
14.558
274731ELWOOD EC;2P
Adder
14.558
274733ELWOOD EC;3P
Adder
14.558
274735ELWOOD EC;4P
Adder
14.558
274675JOLIET 29;7U
Adder
27.142
960591AF2-350 GEN
Solar/Wind Harmer
6.155
24289405MTG1
50/50
10.896
243186AF1-051 GEN
50/50
11.683
24318705GVG2
50/50
10.829
24721805FLATG3
50/50
2.475
24723205RIVRG3
Adder
32.69
972203AH1-686 GEN
Adder
3.965
24686505CER G6
Adder
14.074
944971AF1-162 GEN
Solar/Wind Harmer
10.992
971403AH1-188 GEN
Solar/Wind Harmer
15.251
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
6.196
971687AH1-348 GEN
Solar/Wind Harmer
0.943
24735205WLF2G2
Adder
7.131
971073AG2-665 GEN
Solar/Wind Harmer
1.329
970091AG2-072 GEN
Adder
86.562
945681AF1-233 GEN
Solar/Wind Harmer
14.491
3429241JKCT 3G
Adder
13.004
3429421JKCT 10G
Adder
9.095
970653AG2-424 GEN
Solar/Wind Harmer
3.596
964901AG1-354 GEN
Solar/Wind Harmer
11.126
25196808ZIMRHP
Adder
79.991
25196008MFTGT1
Adder
1.457
252516AE2-318_GEN
Solar/Wind Harmer
8.161
252510AF1-249 C
Solar/Wind Harmer
0.055
25194608D.CRK4
Adder
1.702
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.045
962761AG1-125 GEN
Solar/Wind Harmer
27.311
970149AG2-104 GEN
Solar/Wind Harmer
14.748
970155AG2-107 GEN
Solar/Wind Harmer
17.44
253398AE2-221_GEN2
Solar/Wind Harmer
0
24728605AND G2
Adder
3.745
970773AG2-487 GEN
Solar/Wind Harmer
1.199
963741AG1-226 GEN
Solar/Wind Harmer
15.765
965911AG1-460 GEN
Solar/Wind Harmer
1.325
943811AF1-049 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.832
276621W2-048 GEN
Solar/Wind Harmer
0.329
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.31
270594AE1-207 GEN
Solar/Wind Harmer
7.264
270032AE2-172
Solar/Wind Harmer
4.324
270273AD2-016 GEN
Solar/Wind Harmer
0.662
270005AE1-210 C O1
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
2.292
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.961
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.933
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.248
276708O09 GEN2
Solar/Wind Harmer
0.223
970569AG2-363 GEN
Solar/Wind Harmer
18.869
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.386
274766LEE CO EC;7U
Adder
8.287
25326309TAIT D
Adder
0.988
945371AF1-202 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
7.523
939401AE1-172 GEN
Solar/Wind Harmer
4.684
274822ROCKFORD ;11
Adder
17.613
957471AF2-041 GEN
Solar/Wind Harmer
18.774
959081AF2-199 GEN
Solar/Wind Harmer
6.258
971067AG2-660 GEN
Solar/Wind Harmer
2.086
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.135
971997AH1-543 GEN
Solar/Wind Harmer
3.283
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.729
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.929
274828WAUKEGAN ;BP
Adder
9.84
274682WAUKEGAN ;7U
Adder
16.004
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.692
24289405MTG1
50/50
10.896
24318705GVG2
50/50
10.829
24722005FLATG5
50/50
2.475
24721905FLATG4
50/50
45.211
24686405CER G5
Adder
13.963
971191AH1-055 GEN
Solar/Wind Harmer
25.524
960911AF2-382 GEN
Solar/Wind Harmer
7.256
972103AH1-617 GEN
Solar/Wind Harmer
19.113
971461AH1-227 GEN
Solar/Wind Harmer
4.836
270346AE1-212 GEN
Solar/Wind Harmer
7.826
943031AE2-326 GEN
Solar/Wind Harmer
4.478
970879AG2-548 GEN
Solar/Wind Harmer
5.846
958121AF2-106 GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
6.527
972167AH1-666 GEN
Solar/Wind Harmer
6.143
972273AH1-721 GEN
Adder
91.222
3429391JKCT 9G
Adder
9.095
970455AG2-298 GEN
Solar/Wind Harmer
2.913
958171AF2-111 GEN
Solar/Wind Harmer
18.695
252507AC2-088 GEN
Solar/Wind Harmer
0.336
970653AG2-424 GEN
Solar/Wind Harmer
0.745
25196008MFTGT1
Adder
1.411
252519AF1-045_GEN
Solar/Wind Harmer
3.801
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.838
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.158
962771AG1-126 GEN
Solar/Wind Harmer
27.311
970153AG2-106 GEN
Solar/Wind Harmer
17.44
253394AE2-221_GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.239
24728705AND G3
Adder
7.833
24728505AND G1
Adder
3.745
270030AE2-140 GEN
Solar/Wind Harmer
13.518
942481AE2-261 GEN
Solar/Wind Harmer
19.808
957381AF2-032 GEN
Solar/Wind Harmer
1.5
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.022
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.714
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.48
270004AE1-209 GEN
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
4.865
965091AG1-374 GEN
Solar/Wind Harmer
19.301
946031AF1-268 GEN
Solar/Wind Harmer
6.123
959611AF2-252 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
970191AG2-125 GEN
Solar/Wind Harmer
1.638
965931AG1-462 GEN
Solar/Wind Harmer
16.203
971087AG2-675 GEN
Solar/Wind Harmer
3.389
274878BISHOP HL;2U
Solar/Wind Harmer
0.211
276782AC1-033 GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.45
970571AG2-364 GEN
Solar/Wind Harmer
12.579
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.386
274767LEE CO EC;8U
Adder
8.287
959091AF2-200 GEN
Solar/Wind Harmer
12.516
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
946671AF1-331 GEN
Solar/Wind Harmer
0.666
276868AE1-113 GEN
Solar/Wind Harmer
1.25
274879MINONK ;1U
Solar/Wind Harmer
0.261
274682WAUKEGAN ;7U
Adder
16.004
274862TOP CROP ;2U
Solar/Wind Harmer
0.839
943121AE2-341 GEN
Solar/Wind Harmer
10.39
943591AF1-030 GEN
Solar/Wind Harmer
6.91
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
14.558
274730ELWOOD EC;6P
Adder
14.558
274734ELWOOD EC;8P
Adder
14.558
274736ELWOOD EC;9P
Adder
14.558
970707AG2-453 GEN
Solar/Wind Harmer
20.15
274887GEN-1.85
Solar/Wind Harmer
0.16
276843GEN-1.7
Solar/Wind Harmer
0.199
276806AD2-047 C O1
Solar/Wind Harmer
3.488
237048AF1-022 C
Solar/Wind Helper
0.175
237046AF1-021 C
Solar/Wind Helper
0.301
235058AG1-386 C
Solar/Wind Helper
0.387
23562501BACKB
Solar/Wind Helper
0.811
23750501ELLIOTTS
Solar/Wind Helper
0.598
23652301WDPWR_K20
Solar/Wind Helper
0.127
243186AF1-051 GEN
50/50
11.683
24721705FLATG2
50/50
36.759
24723005RIVRG1
Adder
32.69
24723105RIVRG2
Adder
32.69
970913AG2-568 GEN
Solar/Wind Harmer
8.105
24728205BUCHG1
Adder
6.196
971225AH1-072 GEN
Solar/Wind Harmer
1.885
971227AH1-073 GEN
Solar/Wind Harmer
1.885
971277AH1-098 GEN
Solar/Wind Harmer
3.388
971073AG2-665 GEN
Solar/Wind Harmer
5.846
970879AG2-548 GEN
Solar/Wind Harmer
1.329
270583AD2-179 GEN
Solar/Wind Harmer
7.872
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942891AE2-308 GEN
Solar/Wind Harmer
7.677
972043AH1-570 GEN
Solar/Wind Harmer
1.99
972045AH1-571 GEN
Solar/Wind Harmer
1.594
971125AH1-004 GEN
Solar/Wind Harmer
3.042
970107AG2-081 GEN
Solar/Wind Harmer
2.281
966021AG1-471 GEN
Solar/Wind Harmer
4.034
252509AD1-136 GEN
Solar/Wind Harmer
0.037
971485AH1-239 GEN
Solar/Wind Harmer
5.968
964571AG1-320 GEN
Solar/Wind Harmer
6.787
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25183208HLCRTG
Solar/Wind Harmer
0
971587AH1-292 GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
7.827
25194508D.CRK3
Adder
1.463
945391AF1-204 GEN
Solar/Wind Harmer
7.253
24728805RICHG1
Adder
3.656
24728905RICHG2
Adder
3.656
970241AG2-163 GEN
Solar/Wind Harmer
3.886
276916AD2-100_GEN
Solar/Wind Harmer
13.944
276911AD2-131_GEN
Solar/Wind Harmer
0.919
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.068
276838X2-022 GEN2
Solar/Wind Harmer
0.37
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.743
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.844
970291AG2-192 GEN
Solar/Wind Harmer
0.389
971613AH1-306 GEN
Solar/Wind Harmer
3.113
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
970883AG2-550 GEN
Solar/Wind Harmer
6.406
970885AG2-551 GEN
Solar/Wind Harmer
2.135
942111AE2-223 GEN
Solar/Wind Harmer
2.08
270031AE2-169
Solar/Wind Harmer
3.483
270599AE1-208 GEN
Solar/Wind Harmer
5.804
276645AC1-214 GEN1
Solar/Wind Harmer
0.248
276691AA1-018 GEN1
Solar/Wind Harmer
1.009
274745AC1-111 GEN9
Adder
4.965
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.558
274674JOLIET 9 ;6U
Adder
13.632
965651AG1-433 GEN
Solar/Wind Harmer
1.811
274676JOLIET 29;8U
Adder
9.572
238185AF2-356 C
Solar/Wind Helper
1.975
970373AG2-245 GEN
Solar/Wind Harmer
5.443
964611AG1-324 GEN
Solar/Wind Harmer
0.475
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.019
247621Y3-024
Adder
0.218
270201AC2-176 GEN
Solar/Wind Harmer
0
25322209TAIT E
Adder
8.794
25322209TAIT E
Adder
8.596
274764LEE CO EC;5U
Adder
8.405
274765LEE CO EC;6U
Adder
8.405
274762LEE CO EC;3U
Adder
8.386
274763LEE CO EC;4U
Adder
8.307
938861AE1-114 GEN
Solar/Wind Harmer
3.56
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.263
972236AH1-702 GEN2
Adder
1.968
971341AH1-150 GEN
Solar/Wind Harmer
12.516
971343AH1-151 GEN
Solar/Wind Harmer
12.516
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.353
962691AG1-118 GEN
Solar/Wind Harmer
18.68
274683WAUKEGAN ;8U
Adder
18.772
274683WAUKEGAN ;8U
Adder
15.824
274696ROCKY RD ;4P
Adder
10.15
274695ROCKY RD ;2P
Adder
9.916
274693ROCKY RD ;1P
Adder
9.818
274697ROCKY RD ;3P
Adder
2.694
958481AF2-142 GEN
Solar/Wind Harmer
9.318
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
15.453
276893AG1-478 C
Solar/Wind Harmer
0.412
274674JOLIET 9 ;6U
Adder
13.632
944541AF1-119 GEN
Solar/Wind Harmer
0.412
960971AF2-388 GEN
Solar/Wind Harmer
3.621
274888KELLY CRK;1U
Solar/Wind Harmer
0.359
276776AD2-060 GEN
Solar/Wind Harmer
0.657
958011AF2-095 GEN
Solar/Wind Harmer
8.864
970941AG2-585 GEN
Solar/Wind Harmer
3.385
23585401KL_K28_T16
Solar/Wind Helper
1.157
237043AE2-125 C
Solar/Wind Helper
0.157
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.531
LAGNLTFEXP_LAGN->PJM
CLTF
19.698
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23
TVALTFEXP_TVA->PJM
CLTF
10.208
CBM West 1LTFEXP_CBM-W1->PJM
CBM
115.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.783
MECLTFEXP_MEC->PJM
CLTF
15.666
SIGELTFEXP_SIGE->PJM
CLTF
0.545
NYPJM->LTFIMP_NY
CLTF
4.626
LGEELTFEXP_LGEE->PJM
CLTF
7.468
WECLTFEXP_WEC->PJM
CLTF
3.435
AG2-052LTFEXP_AG2-052->PJM
LTF
0.207
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
CPLELTFEXP_CPLE->PJM
CLTF
6.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.098

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.41 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5987.66
MW Contribution:
7.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
11.956
24728205BUCHG1
Adder
7.739
270214AC2-123 GEN
Solar/Wind Harmer
3.869
971225AH1-072 GEN
Solar/Wind Harmer
3.319
971227AH1-073 GEN
Solar/Wind Harmer
3.319
971277AH1-098 GEN
Solar/Wind Harmer
6.62
270583AD2-179 GEN
Solar/Wind Harmer
16.289
927014AC1-188 GEN
Solar/Wind Harmer
2.364
971073AG2-665 GEN
Solar/Wind Harmer
10.717
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
13.25
339231AF1-038_GEN
Solar/Wind Harmer
2.384
972043AH1-570 GEN
Solar/Wind Harmer
3.285
972045AH1-571 GEN
Solar/Wind Harmer
2.628
971125AH1-004 GEN
Solar/Wind Harmer
5.238
970107AG2-081 GEN
Solar/Wind Harmer
3.929
966021AG1-471 GEN
Solar/Wind Harmer
7.071
971485AH1-239 GEN
Solar/Wind Harmer
10.457
962581AG1-107 GEN
Solar/Wind Harmer
6.569
961491AF2-440 GEN
Solar/Wind Harmer
2.73
339236AF1-050_GEN
Solar/Wind Harmer
2.347
964781AG1-341 GEN
Solar/Wind Harmer
13.643
964571AG1-320 GEN
Solar/Wind Harmer
10.544
252509AD1-136 GEN
Solar/Wind Harmer
0.325
25183208HLCRTG
Solar/Wind Harmer
7.535
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
16.433
942671AE2-283 GEN
Solar/Wind Harmer
5.701
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
253415AE1-040 GEN
Solar/Wind Harmer
1.308
276916AD2-100_GEN
Solar/Wind Harmer
24.22
276911AD2-131_GEN
Solar/Wind Harmer
4.895
970241AG2-163 GEN
Solar/Wind Harmer
28.803
276615X2-022 GEN
Solar/Wind Harmer
2.236
276838X2-022 GEN2
Solar/Wind Harmer
0.266
926881AC1-175 GEN
Solar/Wind Harmer
6.354
274880W4-005 GEN4
Solar/Wind Harmer
3.438
276174W4-005 GEN2
Solar/Wind Harmer
3.438
24387305FR-4G C
Solar/Wind Harmer
5.77
966841AG1-555 GEN
Solar/Wind Harmer
2.852
24725505WLD G2 C
Solar/Wind Harmer
4.513
24699105WLD G1 C
Solar/Wind Harmer
4.461
270383AD1-128 GEN
Solar/Wind Harmer
6.909
970291AG2-192 GEN
Solar/Wind Harmer
1.461
970291AG2-192 GEN
Solar/Wind Harmer
0.47
253370AE2-315 SEC1
Adder
2.225
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
247621Y3-024
Adder
0.264
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
274674JOLIET 9 ;6U
Adder
16.589
23585401KL_K28_T16
Solar/Wind Helper
1.275
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
8.236
270053AF1-130 C
Solar/Wind Harmer
32.909
270399AC1-101 GEN
Solar/Wind Harmer
7.81
270400AC1-102 GEN
Solar/Wind Harmer
7.81
971313AH1-133 GEN
Solar/Wind Harmer
10.201
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
5.744
970281AG2-184 GEN
Solar/Wind Harmer
34.819
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
9.777
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
962211AG1-066 GEN
Solar/Wind Harmer
3.81
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
14.005
971985AH1-537 GEN
Solar/Wind Harmer
26.103
971981AH1-535 GEN
Solar/Wind Harmer
14.155
270069AE2-166 C O1
Solar/Wind Harmer
12.483
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
13.172
972165AH1-665 GEN
Solar/Wind Harmer
10.538
339216AC1-074 GEN
Solar/Wind Harmer
2.182
270291AC1-194 GEN
Solar/Wind Harmer
6.437
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
6.941
270445AC2-157 GEN2
Solar/Wind Harmer
6.941
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253433AC1-085 GEN1
Solar/Wind Harmer
6.419
253432AC1-085 GEN2
Solar/Wind Harmer
0.323
253406AD2-031_GEN
Solar/Wind Harmer
1.524
270340AC2-060 GEN
Solar/Wind Harmer
3.588
270263AC1-001 GEN
Solar/Wind Harmer
1.236
270197AD1-017 GEN1
Solar/Wind Harmer
1.798
270356AE2-297 GEN
Solar/Wind Harmer
5.395
944221AF1-090 GEN
Solar/Wind Harmer
12.7
963841AG1-237 GEN
Solar/Wind Harmer
12.506
276763AC1-053 GEN1
Solar/Wind Harmer
4.5
276764AC1-053 GEN2
Solar/Wind Harmer
4.5
276668AB2-070 GEN1
Solar/Wind Harmer
2.517
276848AB2-070 GEN3
Solar/Wind Harmer
2.517
276849AB2-070 GEN2
Solar/Wind Harmer
2.517
24386405FR-21G C
Solar/Wind Harmer
4.886
24387005FR-3G C
Solar/Wind Harmer
4.493
970289AG2-191 GEN
Solar/Wind Harmer
2.135
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
270330AC1-082 GEN2
Solar/Wind Harmer
0.862
270329AC1-082 GEN1
Solar/Wind Harmer
0.862
960911AF2-382 GEN
Solar/Wind Harmer
12.889
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
8.512
972103AH1-617 GEN
Solar/Wind Harmer
33.161
971191AH1-055 GEN
Solar/Wind Harmer
30.574
270346AE1-212 GEN
Solar/Wind Harmer
14.67
958121AF2-106 GEN
Solar/Wind Harmer
7.386
957541AF2-048 GEN
Solar/Wind Harmer
2.364
970879AG2-548 GEN
Solar/Wind Harmer
10.717
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
26.764
970093AG2-073 GEN
Solar/Wind Harmer
7.05
270186AC1-089 GEN
Solar/Wind Harmer
8.102
270367AC2-061_GEN
Solar/Wind Harmer
4.197
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
10.503
962751AG1-124 GEN
Solar/Wind Harmer
11.766
339206AE1-143 GEN
Solar/Wind Harmer
2.789
339243AC2-075 GEN1
Solar/Wind Harmer
0.591
970455AG2-298 GEN
Solar/Wind Harmer
4.537
970653AG2-424 GEN
Solar/Wind Harmer
0.902
339255AE2-071 GEN
Solar/Wind Harmer
1.514
339250AF1-203 GEN
Solar/Wind Harmer
0.779
958171AF2-111 GEN
Solar/Wind Harmer
32.027
252507AC2-088 GEN
Solar/Wind Harmer
2.278
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
252524AE2-267 GEN
Solar/Wind Harmer
1.938
25196608WSDLE5
Adder
10.55
270018AE2-047 C O1
Solar/Wind Harmer
1.501
253317AC1-085 GEN4
Solar/Wind Harmer
10.112
946181AF1-283 GEN
Solar/Wind Harmer
15.702
970193AG2-126 GEN
Solar/Wind Harmer
17.687
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
5.329
962771AG1-126 GEN
Solar/Wind Harmer
38.013
970153AG2-106 GEN
Solar/Wind Harmer
16.575
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.453
942481AE2-261 GEN
Solar/Wind Harmer
34.409
957381AF2-032 GEN
Solar/Wind Harmer
2.3
24379505HDWTR1G C
Solar/Wind Harmer
9.002
270240V3-007_GEN2
Solar/Wind Harmer
7.043
276785W4-005 GEN1
Solar/Wind Harmer
3.438
971993AH1-541 GEN
Solar/Wind Harmer
10.504
24386205FR-12G C
Solar/Wind Harmer
4.868
247642Z2-115 C
Solar/Wind Harmer
0.072
965461AG1-414 GEN
Solar/Wind Harmer
2.547
970289AG2-191 GEN
Solar/Wind Harmer
0.862
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
274682WAUKEGAN ;7U
Adder
19.478
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
26.012
270331AC1-082 GEN3
Solar/Wind Harmer
0.864
960001AF2-291 GEN
Solar/Wind Harmer
5.313
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.658
24735205WLF2G2
Adder
8.97
270336AE1-100 GEN
Solar/Wind Harmer
2.369
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
339211AE2-254 GEN
Solar/Wind Harmer
1.998
3429241JKCT 3G
Adder
15.659
270173AC1-122 GEN
Solar/Wind Harmer
2.206
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
24.773
943111AE2-339 GEN
Solar/Wind Harmer
1.158
339221AD2-048_GEN
Solar/Wind Harmer
2.01
943811AF1-049 GEN
Solar/Wind Harmer
4.941
339241AF1-083 GEN
Solar/Wind Harmer
2.163
964901AG1-354 GEN
Solar/Wind Harmer
19.398
970653AG2-424 GEN
Solar/Wind Harmer
6.236
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
12.45
252510AF1-249 C
Solar/Wind Harmer
0.517
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
10.112
946171AF1-282 GEN
Solar/Wind Harmer
12.079
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
5.329
962761AG1-125 GEN
Solar/Wind Harmer
38.013
970149AG2-104 GEN
Solar/Wind Harmer
23.473
970155AG2-107 GEN
Solar/Wind Harmer
16.575
270574AD1-017 GEN2
Solar/Wind Harmer
5.994
316217AC1-145 GEN
Solar/Wind Harmer
2.791
316197AC1-042 GEN
Solar/Wind Harmer
2.116
3147312GRETNA
Solar/Wind Harmer
-0.003
270222AC2-111 GEN
Solar/Wind Harmer
5.217
944031AF1-071 GEN
Solar/Wind Harmer
1.174
963741AG1-226 GEN
Solar/Wind Harmer
51.846
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
7.12
942081AE2-220 GEN
Solar/Wind Harmer
7.281
270209AC1-174_GEN
Solar/Wind Harmer
4.633
270437AC2-090 C
Solar/Wind Harmer
6.354
270239V3-007_GEN1
Solar/Wind Harmer
1.959
276686W4-005 GEN3
Solar/Wind Harmer
3.438
24385905FR-11G C
Solar/Wind Harmer
9.442
24386605FR-22G C
Solar/Wind Harmer
4.886
276903AD2-071 C
Solar/Wind Harmer
11.325
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
274822ROCKFORD ;11
Adder
21.436
25326309TAIT D
Adder
1.195
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274745AC1-111 GEN9
Adder
6.042
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
270594AE1-207 GEN
Solar/Wind Harmer
12.561
270032AE2-172
Solar/Wind Harmer
4.302
972267AH1-718 GEN
Adder
4.579
274823ROCKFORD ;21
Adder
21.28
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.46 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5935.05
MW Contribution:
6.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.718
957241AF2-018 GEN
Solar/Wind Harmer
7.332
270053AF1-130 C
Solar/Wind Harmer
29.298
270399AC1-101 GEN
Solar/Wind Harmer
6.93
270400AC1-102 GEN
Solar/Wind Harmer
6.93
941621AE2-160 GEN
Adder
4.867
970281AG2-184 GEN
Solar/Wind Harmer
30.484
971313AH1-133 GEN
Solar/Wind Harmer
8.48
962211AG1-066 GEN
Solar/Wind Harmer
3.344
24734705WLF1G3
Adder
7.73
24734805WLF1G4
Adder
7.73
24734905WLF1G5
Adder
7.73
971061AG2-657 GEN
Solar/Wind Harmer
11.954
971985AH1-537 GEN
Solar/Wind Harmer
23.681
24735105WLF2G1
Adder
7.594
966391AG1-508 GEN
Solar/Wind Harmer
4.439
971331AH1-145 GEN
Solar/Wind Harmer
11.397
971329AH1-144 GEN
Solar/Wind Harmer
7.28
971981AH1-535 GEN
Solar/Wind Harmer
12.094
270444AC2-157 GEN1
Solar/Wind Harmer
6.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.747
3429211JKCT 2G
Adder
13.893
972163AH1-664 GEN
Solar/Wind Harmer
11.763
972165AH1-665 GEN
Solar/Wind Harmer
9.41
339216AC1-074 GEN
Solar/Wind Harmer
1.968
963841AG1-237 GEN
Solar/Wind Harmer
12.582
25196108MFTGT2
Adder
1.764
25196108MFTGT2
Adder
1.638
24386405FR-21G C
Solar/Wind Harmer
4.939
24387005FR-3G C
Solar/Wind Harmer
4.542
944221AF1-090 GEN
Solar/Wind Harmer
12.541
946581AF1-322 GEN
Solar/Wind Harmer
11.687
24691005MDL-2G C
Solar/Wind Harmer
4.223
276763AC1-053 GEN1
Solar/Wind Harmer
4.503
276764AC1-053 GEN2
Solar/Wind Harmer
4.503
276668AB2-070 GEN1
Solar/Wind Harmer
2.521
276848AB2-070 GEN3
Solar/Wind Harmer
2.521
276849AB2-070 GEN2
Solar/Wind Harmer
2.521
270356AE2-297 GEN
Solar/Wind Harmer
5.225
274853TWINGROVE;U1
Solar/Wind Harmer
8.154
274854TWINGROVE;U2
Solar/Wind Harmer
7.983
970289AG2-191 GEN
Solar/Wind Harmer
2.148
276726Z2-087_GEN
Solar/Wind Harmer
8.934
959341AF2-225 GEN
Solar/Wind Harmer
16.948
972267AH1-718 GEN
Adder
4.661
274823ROCKFORD ;21
Adder
21.773
25196408WSDLE3
Adder
9.858
25196308WSDLE2
Adder
9.772
25196208WSDLE1
Adder
9.747
25196708WSDLE6
Adder
9.723
25196508WSDLE4
Adder
9.478
274744AC1-111 GEN8
Adder
6.235
274746AC1-111 G10
Adder
6.235
274775LINCOLN ;6U
Adder
9.41
274776LINCOLN ;7U
Adder
9.41
274777LINCOLN ;8U
Adder
9.41
274728ELWOOD EC;5P
Adder
18.315
274731ELWOOD EC;2P
Adder
18.315
274733ELWOOD EC;3P
Adder
18.315
274735ELWOOD EC;4P
Adder
18.315
23750501ELLIOTTS
Solar/Wind Helper
0.664
23652301WDPWR_K20
Solar/Wind Helper
0.142
23750701CROSSCHOOL
Solar/Wind Helper
1.189
203955AF1-039 C O1
Solar/Wind Helper
0.363
238118U2-030_1
Solar/Wind Helper
0.286
241997AF1-093 GEN
Solar/Wind Helper
0.24
241985AE1-237 GEN
Solar/Wind Helper
0.233
241982AE2-343 S C
Solar/Wind Helper
0.209
20089126CSLMN_L13
Solar/Wind Helper
0.575
20089226LOOKOUT
Solar/Wind Helper
0.573
20088926STNY CRK
Solar/Wind Helper
0.78
203940AF1-140 C
Solar/Wind Helper
0.376
20094526CT_V3-030
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.144
203846AF2-130 C
Solar/Wind Helper
0.423
959141AF2-205 GEN
Solar/Wind Harmer
1.763
243186AF1-051 GEN
50/50
12.373
24721705FLATG2
50/50
40.36
24723005RIVRG1
Adder
34.305
24723105RIVRG2
Adder
34.305
970913AG2-568 GEN
Solar/Wind Harmer
10.293
24728205BUCHG1
Adder
6.531
971225AH1-072 GEN
Solar/Wind Harmer
2.862
971227AH1-073 GEN
Solar/Wind Harmer
2.862
927014AC1-188 GEN
Solar/Wind Harmer
2.06
270214AC2-123 GEN
Solar/Wind Harmer
2.985
971277AH1-098 GEN
Solar/Wind Harmer
5.094
942891AE2-308 GEN
Solar/Wind Harmer
11.926
964571AG1-320 GEN
Solar/Wind Harmer
9.728
339231AF1-038_GEN
Solar/Wind Harmer
2.148
972043AH1-570 GEN
Solar/Wind Harmer
2.957
972045AH1-571 GEN
Solar/Wind Harmer
2.366
971125AH1-004 GEN
Solar/Wind Harmer
4.718
970107AG2-081 GEN
Solar/Wind Harmer
3.539
270583AD2-179 GEN
Solar/Wind Harmer
11.79
966021AG1-471 GEN
Solar/Wind Harmer
6.353
339236AF1-050_GEN
Solar/Wind Harmer
2.134
971485AH1-239 GEN
Solar/Wind Harmer
9.407
964781AG1-341 GEN
Solar/Wind Harmer
12.396
945391AF1-204 GEN
Solar/Wind Harmer
16.22
962581AG1-107 GEN
Solar/Wind Harmer
5.847
961491AF2-440 GEN
Solar/Wind Harmer
2.43
970241AG2-163 GEN
Solar/Wind Harmer
28.851
24387305FR-4G C
Solar/Wind Harmer
5.833
966841AG1-555 GEN
Solar/Wind Harmer
2.883
252509AD1-136 GEN
Solar/Wind Harmer
0.293
276916AD2-100_GEN
Solar/Wind Harmer
24.022
276911AD2-131_GEN
Solar/Wind Harmer
4.855
270180AB1-006 GEN1
Solar/Wind Harmer
8.215
24697605MDL-3G C
Solar/Wind Harmer
4.21
24755605MDL-5G
Solar/Wind Harmer
2.754
24697905MDL-4G C
Solar/Wind Harmer
2.621
270181AB1-006 GEN2
Solar/Wind Harmer
0.817
276615X2-022 GEN
Solar/Wind Harmer
2.233
276838X2-022 GEN2
Solar/Wind Harmer
0.265
945421AF1-207 GEN
Solar/Wind Harmer
16.001
957841AF2-078 GEN
Solar/Wind Harmer
6.888
274880W4-005 GEN4
Solar/Wind Harmer
3.443
276174W4-005 GEN2
Solar/Wind Harmer
3.443
971073AG2-665 GEN
Solar/Wind Harmer
9.054
960611AF2-352 GEN
Solar/Wind Harmer
2.632
970879AG2-548 GEN
Solar/Wind Harmer
1.316
970291AG2-192 GEN
Solar/Wind Harmer
1.47
970291AG2-192 GEN
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
4.494
24699105WLD G1 C
Solar/Wind Harmer
4.441
942111AE2-223 GEN
Solar/Wind Harmer
9.262
25194408D.CRK1
Adder
8.477
25194508D.CRK3
Adder
1.585
274764LEE CO EC;5U
Adder
10.431
274765LEE CO EC;6U
Adder
10.431
274762LEE CO EC;3U
Adder
10.407
274763LEE CO EC;4U
Adder
10.309
972235AH1-702 GEN1
Adder
2.817
972236AH1-702 GEN2
Adder
2.45
274696ROCKY RD ;4P
Adder
12.719
274695ROCKY RD ;2P
Adder
12.425
274693ROCKY RD ;1P
Adder
12.303
274697ROCKY RD ;3P
Adder
3.375
274683WAUKEGAN ;8U
Adder
23.51
274683WAUKEGAN ;8U
Adder
19.818
274770LINCOLN ;1U
Adder
9.41
274771LINCOLN ;2U
Adder
9.41
274674JOLIET 9 ;6U
Adder
16.682
237043AE2-125 C
Solar/Wind Helper
0.176
23585401KL_K28_T16
Solar/Wind Helper
1.282
23751201ROTHROCK
Solar/Wind Helper
0.737
235054AD2-180 GEN
Solar/Wind Helper
1.698
238117U2-030
Solar/Wind Helper
0.286
962101AG1-054 GEN
Solar/Wind Helper
0.612
254304AE2-114 C
Solar/Wind Helper
0.205
254305AE2-115 C
Solar/Wind Helper
0.205
241967AE2-285_GEN
Solar/Wind Helper
0.597
241801AE1-079 GEN
Solar/Wind Helper
0.233
235531U2-073 GEN
Solar/Wind Helper
2.712
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.571
20088826HIGHLAND
Solar/Wind Helper
0.851
203961AE2-224 GEN
Solar/Wind Helper
2.277
203818AF1-086 GEN
Solar/Wind Helper
1.591
203853AF1-134 C O1
Solar/Wind Helper
0.449
946381AF1-302 GEN
Solar/Wind Helper
0.208
203946AE2-131 C
Solar/Wind Helper
0.445
203954AE2-126 C
Solar/Wind Helper
0.44
203804AE2-113_GEN
Solar/Wind Helper
1.631
940863AE2-074 GEN
Solar/Wind Helper
0.426
24289405MTG1
50/50
11.32
24318705GVG2
50/50
11.469
24722005FLATG5
50/50
2.718
24721905FLATG4
50/50
49.64
24686405CER G5
Adder
14.607
270330AC1-082 GEN2
Solar/Wind Harmer
0.779
270329AC1-082 GEN1
Solar/Wind Harmer
0.779
962771AG1-126 GEN
Solar/Wind Harmer
51.105
970153AG2-106 GEN
Solar/Wind Harmer
22.284
971191AH1-055 GEN
Solar/Wind Harmer
27.435
960911AF2-382 GEN
Solar/Wind Harmer
10.97
972103AH1-617 GEN
Solar/Wind Harmer
29.032
971461AH1-227 GEN
Solar/Wind Harmer
7.34
270346AE1-212 GEN
Solar/Wind Harmer
11.918
957541AF2-048 GEN
Solar/Wind Harmer
2.06
943031AE2-326 GEN
Solar/Wind Harmer
4.698
972273AH1-721 GEN
Adder
99.65
970093AG2-073 GEN
Solar/Wind Harmer
6.342
970455AG2-298 GEN
Solar/Wind Harmer
4.162
339206AE1-143 GEN
Solar/Wind Harmer
2.532
970653AG2-424 GEN
Solar/Wind Harmer
0.827
270186AC1-089 GEN
Solar/Wind Harmer
7.225
3429391JKCT 9G
Adder
9.84
270367AC2-061_GEN
Solar/Wind Harmer
3.742
958121AF2-106 GEN
Solar/Wind Harmer
5.343
339243AC2-075 GEN1
Solar/Wind Harmer
0.533
972167AH1-666 GEN
Solar/Wind Harmer
9.374
339255AE2-071 GEN
Solar/Wind Harmer
1.375
339250AF1-203 GEN
Solar/Wind Harmer
0.708
970193AG2-126 GEN
Solar/Wind Harmer
17.459
25196008MFTGT1
Adder
1.55
24386205FR-12G C
Solar/Wind Harmer
4.921
24728705AND G3
Adder
9.201
24728505AND G1
Adder
4.399
252507AC2-088 GEN
Solar/Wind Harmer
2.051
942481AE2-261 GEN
Solar/Wind Harmer
34.173
957381AF2-032 GEN
Solar/Wind Harmer
2.285
24690905MDL-1G C
Solar/Wind Harmer
9.169
970781AG2-491 GEN
Solar/Wind Harmer
11.422
958171AF2-111 GEN
Solar/Wind Harmer
28.524
276785W4-005 GEN1
Solar/Wind Harmer
3.443
971993AH1-541 GEN
Solar/Wind Harmer
10.521
247642Z2-115 C
Solar/Wind Harmer
0.073
965091AG1-374 GEN
Solar/Wind Harmer
33.954
970879AG2-548 GEN
Solar/Wind Harmer
9.054
959611AF2-252 GEN
Solar/Wind Harmer
2.632
965461AG1-414 GEN
Solar/Wind Harmer
2.564
970289AG2-191 GEN
Solar/Wind Harmer
0.868
25194608D.CRK4
Adder
1.843
274760LEE CO EC;1U
Adder
10.407
274767LEE CO EC;8U
Adder
10.284
25196608WSDLE5
Adder
9.576
274682WAUKEGAN ;7U
Adder
20.049
274772LINCOLN ;3U
Adder
9.41
972259AH1-714 GEN
Adder
21.265
274729ELWOOD EC;1P
Adder
18.315
274730ELWOOD EC;6P
Adder
18.315
274734ELWOOD EC;8P
Adder
18.315
274736ELWOOD EC;9P
Adder
18.315
237048AF1-022 C
Solar/Wind Helper
0.194
237046AF1-021 C
Solar/Wind Helper
0.336
235058AG1-386 C
Solar/Wind Helper
0.44
23562501BACKB
Solar/Wind Helper
0.897
964991AG1-363 GEN
Solar/Wind Helper
3.654
202652Y1-033 WT C
Solar/Wind Helper
0.551
238127S14_GEN_2
Solar/Wind Helper
0.674
20092526R32
Solar/Wind Helper
1.103
20303426NA_O38_P22
Solar/Wind Helper
0.938
203993AD2-133_GEN1
Solar/Wind Helper
0.966
238108AE1-109 GEN1
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
203854AF2-039 C
Solar/Wind Helper
0.298
24289405MTG1
50/50
11.32
243186AF1-051 GEN
50/50
12.373
24318705GVG2
50/50
11.469
24721805FLATG3
50/50
2.718
24723205RIVRG3
Adder
34.305
972203AH1-686 GEN
Adder
4.176
24686505CER G6
Adder
14.723
944971AF1-162 GEN
Solar/Wind Harmer
11.548
971403AH1-188 GEN
Solar/Wind Harmer
22.954
270331AC1-082 GEN3
Solar/Wind Harmer
0.78
960001AF2-291 GEN
Solar/Wind Harmer
4.782
962761AG1-125 GEN
Solar/Wind Harmer
51.105
970149AG2-104 GEN
Solar/Wind Harmer
31.557
970155AG2-107 GEN
Solar/Wind Harmer
22.284
24728305BUCHG2
Adder
6.531
971687AH1-348 GEN
Solar/Wind Harmer
1.432
24735205WLF2G2
Adder
7.594
970091AG2-072 GEN
Adder
98.735
339211AE2-254 GEN
Solar/Wind Harmer
1.806
3429241JKCT 3G
Adder
14.075
970653AG2-424 GEN
Solar/Wind Harmer
5.716
339241AF1-083 GEN
Solar/Wind Harmer
1.965
3429421JKCT 10G
Adder
9.84
339221AD2-048_GEN
Solar/Wind Harmer
1.812
943111AE2-339 GEN
Solar/Wind Harmer
1.043
964901AG1-354 GEN
Solar/Wind Harmer
17.632
945681AF1-233 GEN
Solar/Wind Harmer
22.112
963741AG1-226 GEN
Solar/Wind Harmer
51.931
25196008MFTGT1
Adder
1.6
24385905FR-11G C
Solar/Wind Harmer
9.545
24386605FR-22G C
Solar/Wind Harmer
4.939
24728605AND G2
Adder
4.399
965911AG1-460 GEN
Solar/Wind Harmer
1.595
24791305MDL-5G
Solar/Wind Harmer
2.754
276621W2-048 GEN
Solar/Wind Harmer
7.111
276686W4-005 GEN3
Solar/Wind Harmer
3.443
25196808ZIMRHP
Adder
86.01
971073AG2-665 GEN
Solar/Wind Harmer
1.316
276903AD2-071 C
Solar/Wind Harmer
11.309
940581AE2-045 GEN
Solar/Wind Harmer
11.524
971605AH1-302 GEN
Solar/Wind Harmer
9.854
276655WTG1_EQ
Solar/Wind Harmer
9.862
276656WTG2_EQ
Solar/Wind Harmer
1.306
939741AE1-205 GEN
Solar/Wind Harmer
22.597
270594AE1-207 GEN
Solar/Wind Harmer
15.305
270032AE2-172
Solar/Wind Harmer
5.241
25194608D.CRK4
Adder
1.843
274761LEE CO EC;2U
Adder
10.407
274766LEE CO EC;7U
Adder
10.284
274822ROCKFORD ;11
Adder
21.932
274828WAUKEGAN ;BP
Adder
12.324
274745AC1-111 GEN9
Adder
6.235
274682WAUKEGAN ;7U
Adder
20.049
274773LINCOLN ;4U
Adder
9.41
274774LINCOLN ;5U
Adder
9.41
274732ELWOOD EC;7P
Adder
18.315
274674JOLIET 9 ;6U
Adder
17.154
238185AF2-356 C
Solar/Wind Helper
2.191
254303AC2-168 GEN
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.24
20089026BF_G21_K23
Solar/Wind Helper
0.455
238120AE2-309 GEN
Solar/Wind Helper
0.424
238126S14_GEN_1
Solar/Wind Helper
0.674
23751101LEADS_P59
Solar/Wind Helper
1.865
20084626FORWARD
Solar/Wind Helper
0.338
964201AG1-281 GEN
Solar/Wind Helper
0.457
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.966
238109AE1-109 GEN2
Solar/Wind Helper
0.084
203952AE2-129 C
Solar/Wind Helper
0.445
203855AF2-088 C
Solar/Wind Helper
0.143
LAGNLTFEXP_LAGN->PJM
CLTF
22.209
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.481
TVALTFEXP_TVA->PJM
CLTF
11.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.12
MECLTFEXP_MEC->PJM
CLTF
18.91
SIGELTFEXP_SIGE->PJM
CLTF
0.622
NYPJM->LTFIMP_NY
CLTF
5.206
LGEELTFEXP_LGEE->PJM
CLTF
8.318
WECLTFEXP_WEC->PJM
CLTF
4.274
AG2-052LTFEXP_AG2-052->PJM
LTF
0.26
AH1-155LTFEXP_AH1-155->PJM
LTF
0.389
CPLELTFEXP_CPLE->PJM
CLTF
6.634
CBM West 2LTFEXP_CBM-W2->PJM
CBM
151.558

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5896.19
MW Contribution:
5.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
28.948
270399AC1-101 GEN
Solar/Wind Harmer
4.065
270400AC1-102 GEN
Solar/Wind Harmer
4.065
971313AH1-133 GEN
Solar/Wind Harmer
5.869
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
1.796
970281AG2-184 GEN
Solar/Wind Harmer
24.292
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
5.625
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
6.84
971985AH1-537 GEN
Solar/Wind Harmer
3.035
971981AH1-535 GEN
Solar/Wind Harmer
6.584
270069AE2-166 C O1
Solar/Wind Harmer
8.709
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
10.231
972165AH1-665 GEN
Solar/Wind Harmer
8.194
339216AC1-074 GEN
Solar/Wind Harmer
0.242
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253406AD2-031_GEN
Solar/Wind Harmer
0.618
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.825
270197AD1-017 GEN1
Solar/Wind Harmer
1.008
270356AE2-297 GEN
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.756
963841AG1-237 GEN
Solar/Wind Harmer
3.459
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.489
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
18.148
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.157
24735205WLF2G2
Adder
8.97
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
3429241JKCT 3G
Adder
15.659
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
17.283
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
964901AG1-354 GEN
Solar/Wind Harmer
13.534
970653AG2-424 GEN
Solar/Wind Harmer
4.351
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
9.728
252510AF1-249 C
Solar/Wind Harmer
0.065
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.427
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
32.057
970149AG2-104 GEN
Solar/Wind Harmer
17.311
970155AG2-107 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.031
970773AG2-487 GEN
Solar/Wind Harmer
1.442
963741AG1-226 GEN
Solar/Wind Harmer
19.023
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
0.398
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.825
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.823
270594AE1-207 GEN
Solar/Wind Harmer
8.772
270032AE2-172
Solar/Wind Harmer
5.222
270005AE1-210 C O1
Solar/Wind Harmer
1.692
970825AG2-519 GEN
Solar/Wind Harmer
2.77
270273AD2-016 GEN
Solar/Wind Harmer
0.795
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
10.877
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.302
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.607
276708O09 GEN2
Solar/Wind Harmer
0.271
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
970569AG2-363 GEN
Solar/Wind Harmer
22.948
970819AG2-516 GEN
Solar/Wind Harmer
9.157
274822ROCKFORD ;11
Adder
21.436
957471AF2-041 GEN
Solar/Wind Harmer
22.848
959081AF2-199 GEN
Solar/Wind Harmer
7.616
971067AG2-660 GEN
Solar/Wind Harmer
2.539
945371AF1-202 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.694
971997AH1-543 GEN
Solar/Wind Harmer
3.993
25326309TAIT D
Adder
1.195
276882AE2-255 GEN
Solar/Wind Harmer
0.887
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.865
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.216
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.228
274745AC1-111 GEN9
Adder
6.042
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
3.264
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
270055AF2-134 C O1
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
960911AF2-382 GEN
Solar/Wind Harmer
8.992
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
5.939
972103AH1-617 GEN
Solar/Wind Harmer
23.135
971191AH1-055 GEN
Solar/Wind Harmer
29.317
270346AE1-212 GEN
Solar/Wind Harmer
10.045
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
6.854
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
18.672
970093AG2-073 GEN
Solar/Wind Harmer
7.87
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
8.058
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970653AG2-424 GEN
Solar/Wind Harmer
0.902
958171AF2-111 GEN
Solar/Wind Harmer
22.344
252507AC2-088 GEN
Solar/Wind Harmer
0.399
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
25196608WSDLE5
Adder
10.55
274854TWINGROVE;U2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.702
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.158
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
270543AE2-219 C
Solar/Wind Harmer
5.421
946321AF1-296 GEN
Solar/Wind Harmer
4.325
274877BISHOP HL;1U
Solar/Wind Harmer
0.257
247536S-71 GEN
Solar/Wind Harmer
0.307
971611AH1-305 GEN
Solar/Wind Harmer
4.575
970169AG2-114 GEN
Solar/Wind Harmer
7.684
276741O09 GEN1
Solar/Wind Harmer
0.271
972267AH1-718 GEN
Adder
4.579
971609AH1-304 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
2.987
926823AC1-168 GEN
Solar/Wind Harmer
1.302
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
12.311
274856ECOGROVE ;U1
Solar/Wind Harmer
0.178
274823ROCKFORD ;21
Adder
21.28
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.232
945581AF1-223 GEN
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.136
276863AD2-134 GEN
Solar/Wind Harmer
0.136
971675AH1-338 GEN
Solar/Wind Harmer
2.966
971411AH1-196 GEN
Solar/Wind Harmer
11.402
970073AG2-061 GEN
Solar/Wind Harmer
2.528
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
970833AG2-524 GEN
Solar/Wind Harmer
8.285
970833AG2-524 GEN
Solar/Wind Harmer
5.523
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
960591AF2-350 GEN
Solar/Wind Harmer
7.491
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
9.827
24728205BUCHG1
Adder
7.739
971225AH1-072 GEN
Solar/Wind Harmer
2.315
971227AH1-073 GEN
Solar/Wind Harmer
2.315
971277AH1-098 GEN
Solar/Wind Harmer
4.618
270583AD2-179 GEN
Solar/Wind Harmer
11.364
971073AG2-665 GEN
Solar/Wind Harmer
6.854
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
9.244
972043AH1-570 GEN
Solar/Wind Harmer
2.384
972045AH1-571 GEN
Solar/Wind Harmer
1.91
971125AH1-004 GEN
Solar/Wind Harmer
3.655
970107AG2-081 GEN
Solar/Wind Harmer
2.741
966021AG1-471 GEN
Solar/Wind Harmer
4.933
971485AH1-239 GEN
Solar/Wind Harmer
7.296
962581AG1-107 GEN
Solar/Wind Harmer
0.002
964781AG1-341 GEN
Solar/Wind Harmer
9.518
964571AG1-320 GEN
Solar/Wind Harmer
8.194
252509AD1-136 GEN
Solar/Wind Harmer
0.044
25183208HLCRTG
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.363
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
8.741
942671AE2-283 GEN
Solar/Wind Harmer
3.812
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
276916AD2-100_GEN
Solar/Wind Harmer
16.897
276911AD2-131_GEN
Solar/Wind Harmer
1.113
970241AG2-163 GEN
Solar/Wind Harmer
4.689
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.448
926881AC1-175 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.897
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
1.019
970291AG2-192 GEN
Solar/Wind Harmer
0.47
971613AH1-306 GEN
Solar/Wind Harmer
3.76
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.602
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
2.525
253370AE2-315 SEC1
Adder
2.225
970883AG2-550 GEN
Solar/Wind Harmer
7.744
970885AG2-551 GEN
Solar/Wind Harmer
2.581
276645AC1-214 GEN1
Solar/Wind Harmer
0.302
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.239
270031AE2-169
Solar/Wind Harmer
4.216
270599AE1-208 GEN
Solar/Wind Harmer
7.027
964611AG1-324 GEN
Solar/Wind Harmer
0.575
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
938861AE1-114 GEN
Solar/Wind Harmer
4.333
247621Y3-024
Adder
0.264
270201AC2-176 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
15.232
971343AH1-151 GEN
Solar/Wind Harmer
15.232
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.378
962691AG1-118 GEN
Solar/Wind Harmer
22.733
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
958481AF2-142 GEN
Solar/Wind Harmer
11.337
276897AD1-100 C
Solar/Wind Harmer
18.8
276893AG1-478 C
Solar/Wind Harmer
0.501
274674JOLIET 9 ;6U
Adder
16.589
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.437
276776AD2-060 GEN
Solar/Wind Harmer
0.799
958011AF2-095 GEN
Solar/Wind Harmer
10.787
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
970941AG2-585 GEN
Solar/Wind Harmer
2.017
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
10.955
970193AG2-126 GEN
Solar/Wind Harmer
12.34
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
0
962771AG1-126 GEN
Solar/Wind Harmer
32.057
970153AG2-106 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.122
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.901
942481AE2-261 GEN
Solar/Wind Harmer
24.006
957381AF2-032 GEN
Solar/Wind Harmer
1.818
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.664
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.862
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.832
270004AE1-209 GEN
Solar/Wind Harmer
1.692
965091AG1-374 GEN
Solar/Wind Harmer
23.422
959611AF2-252 GEN
Solar/Wind Harmer
2.602
970825AG2-519 GEN
Solar/Wind Harmer
5.878
946031AF1-268 GEN
Solar/Wind Harmer
7.4
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
965931AG1-462 GEN
Solar/Wind Harmer
19.72
971087AG2-675 GEN
Solar/Wind Harmer
4.124
3147123OTTER R
Solar/Wind Harmer
0.087
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.257
970191AG2-125 GEN
Solar/Wind Harmer
1.979
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
970571AG2-364 GEN
Solar/Wind Harmer
15.299
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.443
959091AF2-200 GEN
Solar/Wind Harmer
15.232
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
274850MENDOTA H;RU
Solar/Wind Harmer
0.088
946671AF1-331 GEN
Solar/Wind Harmer
0.811
276868AE1-113 GEN
Solar/Wind Harmer
1.52
274879MINONK ;1U
Solar/Wind Harmer
0.317
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
19.478
274862TOP CROP ;2U
Solar/Wind Harmer
1.021
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.409
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
970707AG2-453 GEN
Solar/Wind Harmer
24.521
274887GEN-1.85
Solar/Wind Harmer
0.195
276843GEN-1.7
Solar/Wind Harmer
0.242
276806AD2-047 C O1
Solar/Wind Harmer
4.245
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.86 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5846.6
MW Contribution:
6.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.66
957241AF2-018 GEN
Solar/Wind Harmer
7.904
270053AF1-130 C
Solar/Wind Harmer
31.582
270399AC1-101 GEN
Solar/Wind Harmer
7.458
270400AC1-102 GEN
Solar/Wind Harmer
7.458
941621AE2-160 GEN
Adder
5.547
970281AG2-184 GEN
Solar/Wind Harmer
32.31
971313AH1-133 GEN
Solar/Wind Harmer
9.046
971061AG2-657 GEN
Solar/Wind Harmer
13.699
971985AH1-537 GEN
Solar/Wind Harmer
26.806
962211AG1-066 GEN
Solar/Wind Harmer
3.513
24734705WLF1G3
Adder
8.136
24734805WLF1G4
Adder
8.136
24734905WLF1G5
Adder
8.136
24735105WLF2G1
Adder
7.967
966391AG1-508 GEN
Solar/Wind Harmer
4.767
971331AH1-145 GEN
Solar/Wind Harmer
12.423
971329AH1-144 GEN
Solar/Wind Harmer
7.935
971981AH1-535 GEN
Solar/Wind Harmer
12.575
972163AH1-664 GEN
Solar/Wind Harmer
12.156
972165AH1-665 GEN
Solar/Wind Harmer
9.725
3429211JKCT 2G
Adder
14.123
270291AC1-194 GEN
Solar/Wind Harmer
6.12
339216AC1-074 GEN
Solar/Wind Harmer
2.003
25196108MFTGT2
Adder
1.756
25196108MFTGT2
Adder
1.631
25196408WSDLE3
Adder
9.915
25196308WSDLE2
Adder
9.829
25196208WSDLE1
Adder
9.804
25196708WSDLE6
Adder
9.779
25196508WSDLE4
Adder
9.533
270444AC2-157 GEN1
Solar/Wind Harmer
6.262
270445AC2-157 GEN2
Solar/Wind Harmer
6.262
270069AE2-166 C O1
Solar/Wind Harmer
10.085
253433AC1-085 GEN1
Solar/Wind Harmer
5.787
253432AC1-085 GEN2
Solar/Wind Harmer
0.291
253406AD2-031_GEN
Solar/Wind Harmer
1.368
270340AC2-060 GEN
Solar/Wind Harmer
3.206
270263AC1-001 GEN
Solar/Wind Harmer
1.104
270356AE2-297 GEN
Solar/Wind Harmer
4.818
944221AF1-090 GEN
Solar/Wind Harmer
11.234
963841AG1-237 GEN
Solar/Wind Harmer
11.024
276763AC1-053 GEN1
Solar/Wind Harmer
3.957
276764AC1-053 GEN2
Solar/Wind Harmer
3.957
276668AB2-070 GEN1
Solar/Wind Harmer
2.213
276848AB2-070 GEN3
Solar/Wind Harmer
2.213
276849AB2-070 GEN2
Solar/Wind Harmer
2.213
24386405FR-21G C
Solar/Wind Harmer
4.297
24387005FR-3G C
Solar/Wind Harmer
3.952
970289AG2-191 GEN
Solar/Wind Harmer
1.875
25306009OHH W.
Adder
2.793
253372AE2-315 SEC3
Adder
1.832
253372AE2-315 SEC3
Adder
1.832
972267AH1-718 GEN
Adder
3.983
274823ROCKFORD ;21
Adder
18.472
274744AC1-111 GEN8
Adder
5.228
274746AC1-111 G10
Adder
5.228
274728ELWOOD EC;5P
Adder
15.317
274731ELWOOD EC;2P
Adder
15.317
274733ELWOOD EC;3P
Adder
15.317
274735ELWOOD EC;4P
Adder
15.317
274675JOLIET 29;7U
Adder
28.551
23750501ELLIOTTS
Solar/Wind Helper
0.647
23652301WDPWR_K20
Solar/Wind Helper
0.14
241997AF1-093 GEN
Solar/Wind Helper
0.247
241985AE1-237 GEN
Solar/Wind Helper
0.241
241982AE2-343 S C
Solar/Wind Helper
0.216
203955AF1-039 C O1
Solar/Wind Helper
0.355
23750701CROSSCHOOL
Solar/Wind Helper
1.137
20089126CSLMN_L13
Solar/Wind Helper
0.564
20089226LOOKOUT
Solar/Wind Helper
0.562
238118U2-030_1
Solar/Wind Helper
0.274
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.371
20094526CT_V3-030
Solar/Wind Helper
0.443
203846AF2-130 C
Solar/Wind Helper
0.428
20088626ARWF_N39
Solar/Wind Helper
1.129
946581AF1-322 GEN
Solar/Wind Harmer
3.68
243186AF1-051 GEN
50/50
12.616
24721705FLATG2
50/50
39.51
24723005RIVRG1
Adder
36.981
24723105RIVRG2
Adder
36.981
970913AG2-568 GEN
Solar/Wind Harmer
11.393
24728205BUCHG1
Adder
6.959
927014AC1-188 GEN
Solar/Wind Harmer
2.439
971225AH1-072 GEN
Solar/Wind Harmer
3.033
971227AH1-073 GEN
Solar/Wind Harmer
3.033
270214AC2-123 GEN
Solar/Wind Harmer
3.2
971277AH1-098 GEN
Solar/Wind Harmer
5.471
971073AG2-665 GEN
Solar/Wind Harmer
10.456
970879AG2-548 GEN
Solar/Wind Harmer
1.52
270583AD2-179 GEN
Solar/Wind Harmer
12.855
962581AG1-107 GEN
Solar/Wind Harmer
6.12
961491AF2-440 GEN
Solar/Wind Harmer
2.543
942891AE2-308 GEN
Solar/Wind Harmer
12.112
972043AH1-570 GEN
Solar/Wind Harmer
3.018
972045AH1-571 GEN
Solar/Wind Harmer
2.414
971125AH1-004 GEN
Solar/Wind Harmer
4.793
970107AG2-081 GEN
Solar/Wind Harmer
3.595
339231AF1-038_GEN
Solar/Wind Harmer
2.155
966021AG1-471 GEN
Solar/Wind Harmer
6.374
971485AH1-239 GEN
Solar/Wind Harmer
9.429
252509AD1-136 GEN
Solar/Wind Harmer
0.301
339236AF1-050_GEN
Solar/Wind Harmer
2.122
964571AG1-320 GEN
Solar/Wind Harmer
9.57
964781AG1-341 GEN
Solar/Wind Harmer
12.309
25183208HLCRTG
Solar/Wind Harmer
6.902
25194408D.CRK1
Adder
8.538
25194508D.CRK3
Adder
1.596
945391AF1-204 GEN
Solar/Wind Harmer
14.618
24728805RICHG1
Adder
3.92
24728905RICHG2
Adder
3.92
253415AE1-040 GEN
Solar/Wind Harmer
1.157
276916AD2-100_GEN
Solar/Wind Harmer
21.377
276911AD2-131_GEN
Solar/Wind Harmer
4.32
970241AG2-163 GEN
Solar/Wind Harmer
25.444
926881AC1-175 GEN
Solar/Wind Harmer
5.627
276615X2-022 GEN
Solar/Wind Harmer
1.968
276838X2-022 GEN2
Solar/Wind Harmer
0.234
24725505WLD G2 C
Solar/Wind Harmer
3.981
24699105WLD G1 C
Solar/Wind Harmer
3.935
274880W4-005 GEN4
Solar/Wind Harmer
3.022
276174W4-005 GEN2
Solar/Wind Harmer
3.022
270383AD1-128 GEN
Solar/Wind Harmer
6.1
24387305FR-4G C
Solar/Wind Harmer
5.075
966841AG1-555 GEN
Solar/Wind Harmer
2.508
970291AG2-192 GEN
Solar/Wind Harmer
1.283
970291AG2-192 GEN
Solar/Wind Harmer
0.413
270180AB1-006 GEN1
Solar/Wind Harmer
7.075
253370AE2-315 SEC1
Adder
1.937
247621Y3-024
Adder
0.23
274764LEE CO EC;5U
Adder
8.891
274765LEE CO EC;6U
Adder
8.891
274762LEE CO EC;3U
Adder
8.871
274763LEE CO EC;4U
Adder
8.787
972235AH1-702 GEN1
Adder
2.391
972236AH1-702 GEN2
Adder
2.08
25322209TAIT E
Adder
9.19
25322209TAIT E
Adder
8.984
274683WAUKEGAN ;8U
Adder
19.789
274683WAUKEGAN ;8U
Adder
16.681
274696ROCKY RD ;4P
Adder
10.699
274695ROCKY RD ;2P
Adder
10.452
274693ROCKY RD ;1P
Adder
10.349
274697ROCKY RD ;3P
Adder
2.839
274674JOLIET 9 ;6U
Adder
14.342
237043AE2-125 C
Solar/Wind Helper
0.175
254304AE2-114 C
Solar/Wind Helper
0.213
254305AE2-115 C
Solar/Wind Helper
0.213
962101AG1-054 GEN
Solar/Wind Helper
0.63
241967AE2-285_GEN
Solar/Wind Helper
0.617
241801AE1-079 GEN
Solar/Wind Helper
0.241
23585401KL_K28_T16
Solar/Wind Helper
1.231
23751201ROTHROCK
Solar/Wind Helper
0.704
235054AD2-180 GEN
Solar/Wind Helper
1.627
946071AF1-272 GEN
Solar/Wind Helper
2.555
238117U2-030
Solar/Wind Helper
0.274
20083426SW_E13_K22
Solar/Wind Helper
0.053
20088826HIGHLAND
Solar/Wind Helper
0.842
235531U2-073 GEN
Solar/Wind Helper
2.597
203818AF1-086 GEN
Solar/Wind Helper
1.582
203961AE2-224 GEN
Solar/Wind Helper
2.25
946381AF1-302 GEN
Solar/Wind Helper
0.208
203853AF1-134 C O1
Solar/Wind Helper
0.446
203946AE2-131 C
Solar/Wind Helper
0.441
203804AE2-113_GEN
Solar/Wind Helper
1.63
24289405MTG1
50/50
11.749
24318705GVG2
50/50
11.694
24722005FLATG5
50/50
2.66
24721905FLATG4
50/50
48.595
270330AC1-082 GEN2
Solar/Wind Harmer
0.934
270329AC1-082 GEN1
Solar/Wind Harmer
0.934
24686405CER G5
Adder
16.065
971191AH1-055 GEN
Solar/Wind Harmer
33.049
960911AF2-382 GEN
Solar/Wind Harmer
11.685
957541AF2-048 GEN
Solar/Wind Harmer
2.439
972103AH1-617 GEN
Solar/Wind Harmer
30.771
971461AH1-227 GEN
Solar/Wind Harmer
7.779
270346AE1-212 GEN
Solar/Wind Harmer
13.204
943031AE2-326 GEN
Solar/Wind Harmer
5.037
970879AG2-548 GEN
Solar/Wind Harmer
10.456
958121AF2-106 GEN
Solar/Wind Harmer
5.826
270186AC1-089 GEN
Solar/Wind Harmer
7.579
270367AC2-061_GEN
Solar/Wind Harmer
3.93
970093AG2-073 GEN
Solar/Wind Harmer
6.439
972167AH1-666 GEN
Solar/Wind Harmer
9.688
972273AH1-721 GEN
Adder
100.618
3429391JKCT 9G
Adder
9.999
339243AC2-075 GEN1
Solar/Wind Harmer
0.542
339206AE1-143 GEN
Solar/Wind Harmer
2.528
970455AG2-298 GEN
Solar/Wind Harmer
4.124
252507AC2-088 GEN
Solar/Wind Harmer
2.108
958171AF2-111 GEN
Solar/Wind Harmer
29.368
970653AG2-424 GEN
Solar/Wind Harmer
0.818
339255AE2-071 GEN
Solar/Wind Harmer
1.366
339250AF1-203 GEN
Solar/Wind Harmer
0.703
25196008MFTGT1
Adder
1.543
252519AF1-045_GEN
Solar/Wind Harmer
4.153
25194608D.CRK4
Adder
1.856
252524AE2-267 GEN
Solar/Wind Harmer
1.77
25196608WSDLE5
Adder
9.632
270030AE2-140 GEN
Solar/Wind Harmer
21.915
253317AC1-085 GEN4
Solar/Wind Harmer
9.117
946181AF1-283 GEN
Solar/Wind Harmer
14.157
970193AG2-126 GEN
Solar/Wind Harmer
15.734
24728705AND G3
Adder
8.411
24728505AND G1
Adder
4.021
253394AE2-221_GEN
Solar/Wind Harmer
4.748
942481AE2-261 GEN
Solar/Wind Harmer
30.351
957381AF2-032 GEN
Solar/Wind Harmer
2.028
962771AG1-126 GEN
Solar/Wind Harmer
32.808
970153AG2-106 GEN
Solar/Wind Harmer
14.306
24379505HDWTR1G C
Solar/Wind Harmer
7.972
270240V3-007_GEN2
Solar/Wind Harmer
6.237
276785W4-005 GEN1
Solar/Wind Harmer
3.022
971993AH1-541 GEN
Solar/Wind Harmer
9.233
24386205FR-12G C
Solar/Wind Harmer
4.281
247642Z2-115 C
Solar/Wind Harmer
0.063
965461AG1-414 GEN
Solar/Wind Harmer
2.238
970289AG2-191 GEN
Solar/Wind Harmer
0.757
270004AE1-209 GEN
Solar/Wind Harmer
5.379
24690905MDL-1G C
Solar/Wind Harmer
7.897
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274760LEE CO EC;1U
Adder
8.871
274767LEE CO EC;8U
Adder
8.766
274682WAUKEGAN ;7U
Adder
16.869
274729ELWOOD EC;1P
Adder
15.317
274730ELWOOD EC;6P
Adder
15.317
274734ELWOOD EC;8P
Adder
15.317
274736ELWOOD EC;9P
Adder
15.317
237048AF1-022 C
Solar/Wind Helper
0.19
235058AG1-386 C
Solar/Wind Helper
0.455
237046AF1-021 C
Solar/Wind Helper
0.331
202652Y1-033 WT C
Solar/Wind Helper
0.537
23562501BACKB
Solar/Wind Helper
0.856
964991AG1-363 GEN
Solar/Wind Helper
3.486
20092526R32
Solar/Wind Helper
1.091
238127S14_GEN_2
Solar/Wind Helper
0.645
20303426NA_O38_P22
Solar/Wind Helper
0.926
203993AD2-133_GEN1
Solar/Wind Helper
0.956
24289405MTG1
50/50
11.749
243186AF1-051 GEN
50/50
12.616
24318705GVG2
50/50
11.694
24721805FLATG3
50/50
2.66
960001AF2-291 GEN
Solar/Wind Harmer
6.049
24723205RIVRG3
Adder
36.981
270331AC1-082 GEN3
Solar/Wind Harmer
0.937
24686505CER G6
Adder
16.193
972203AH1-686 GEN
Adder
4.427
944971AF1-162 GEN
Solar/Wind Harmer
12.449
971403AH1-188 GEN
Solar/Wind Harmer
24.722
24728305BUCHG2
Adder
6.959
971687AH1-348 GEN
Solar/Wind Harmer
1.517
24735205WLF2G2
Adder
7.967
971073AG2-665 GEN
Solar/Wind Harmer
1.52
970091AG2-072 GEN
Adder
94.28
945681AF1-233 GEN
Solar/Wind Harmer
22.855
3429241JKCT 3G
Adder
14.309
339221AD2-048_GEN
Solar/Wind Harmer
1.847
339211AE2-254 GEN
Solar/Wind Harmer
1.818
3429421JKCT 10G
Adder
9.999
943111AE2-339 GEN
Solar/Wind Harmer
1.059
339241AF1-083 GEN
Solar/Wind Harmer
1.958
970653AG2-424 GEN
Solar/Wind Harmer
5.656
964901AG1-354 GEN
Solar/Wind Harmer
17.533
25196808ZIMRHP
Adder
87.559
25196008MFTGT1
Adder
1.593
252516AE2-318_GEN
Solar/Wind Harmer
11.412
252510AF1-249 C
Solar/Wind Harmer
0.473
25194608D.CRK4
Adder
1.856
270336AE1-100 GEN
Solar/Wind Harmer
1.934
253316AC1-085 GEN3
Solar/Wind Harmer
9.117
946171AF1-282 GEN
Solar/Wind Harmer
10.89
943811AF1-049 GEN
Solar/Wind Harmer
4.052
24728605AND G2
Adder
4.021
253398AE2-221_GEN2
Solar/Wind Harmer
4.748
270222AC2-111 GEN
Solar/Wind Harmer
4.662
944031AF1-071 GEN
Solar/Wind Harmer
1.049
963741AG1-226 GEN
Solar/Wind Harmer
45.799
965911AG1-460 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
32.808
970149AG2-104 GEN
Solar/Wind Harmer
20.259
970155AG2-107 GEN
Solar/Wind Harmer
14.306
942081AE2-220 GEN
Solar/Wind Harmer
6.447
270209AC1-174_GEN
Solar/Wind Harmer
4.103
270437AC2-090 C
Solar/Wind Harmer
5.627
270239V3-007_GEN1
Solar/Wind Harmer
1.735
276621W2-048 GEN
Solar/Wind Harmer
6.266
276686W4-005 GEN3
Solar/Wind Harmer
3.022
24385905FR-11G C
Solar/Wind Harmer
8.303
24386605FR-22G C
Solar/Wind Harmer
4.297
276903AD2-071 C
Solar/Wind Harmer
9.98
270594AE1-207 GEN
Solar/Wind Harmer
13.398
270032AE2-172
Solar/Wind Harmer
4.588
270005AE1-210 C O1
Solar/Wind Harmer
5.379
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274761LEE CO EC;2U
Adder
8.871
274766LEE CO EC;7U
Adder
8.766
274822ROCKFORD ;11
Adder
18.607
25326309TAIT D
Adder
1.032
274828WAUKEGAN ;BP
Adder
10.373
274682WAUKEGAN ;7U
Adder
16.869
274745AC1-111 GEN9
Adder
5.228
274732ELWOOD EC;7P
Adder
15.317
274674JOLIET 9 ;6U
Adder
14.342
274676JOLIET 29;8U
Adder
10.069
254303AC2-168 GEN
Solar/Wind Helper
0.154
241966AE1-183 GEN
Solar/Wind Helper
0.247
238185AF2-356 C
Solar/Wind Helper
2.102
20089026BF_G21_K23
Solar/Wind Helper
0.446
20084626FORWARD
Solar/Wind Helper
0.335
964201AG1-281 GEN
Solar/Wind Helper
0.452
238126S14_GEN_1
Solar/Wind Helper
0.645
20091526CHSTN_FL
Solar/Wind Helper
0.544
238120AE2-309 GEN
Solar/Wind Helper
0.406
20090526Q36
Solar/Wind Helper
0.956
203952AE2-129 C
Solar/Wind Helper
0.441
LAGNLTFEXP_LAGN->PJM
CLTF
21.601
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.934
TVALTFEXP_TVA->PJM
CLTF
11.244
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.677
MECLTFEXP_MEC->PJM
CLTF
16.745
SIGELTFEXP_SIGE->PJM
CLTF
0.592
NYPJM->LTFIMP_NY
CLTF
5.068
LGEELTFEXP_LGEE->PJM
CLTF
8.183
WECLTFEXP_WEC->PJM
CLTF
3.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.218
AH1-155LTFEXP_AH1-155->PJM
LTF
0.328
CPLELTFEXP_CPLE->PJM
CLTF
7.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
143.77

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.88 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5626.94
MW Contribution:
6.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.678
24721705FLATG2
50/50
39.728
24723005RIVRG1
Adder
37.214
24723105RIVRG2
Adder
37.214
970913AG2-568 GEN
Solar/Wind Harmer
11.477
24728205BUCHG1
Adder
7.015
927014AC1-188 GEN
Solar/Wind Harmer
2.459
971225AH1-072 GEN
Solar/Wind Harmer
3.058
971227AH1-073 GEN
Solar/Wind Harmer
3.058
270214AC2-123 GEN
Solar/Wind Harmer
3.229
971277AH1-098 GEN
Solar/Wind Harmer
5.52
971073AG2-665 GEN
Solar/Wind Harmer
10.556
970879AG2-548 GEN
Solar/Wind Harmer
1.534
270583AD2-179 GEN
Solar/Wind Harmer
12.98
24289405MTG1
50/50
11.803
24318705GVG2
50/50
11.752
24722005FLATG5
50/50
2.675
24721905FLATG4
50/50
48.862
270330AC1-082 GEN2
Solar/Wind Harmer
0.94
270329AC1-082 GEN1
Solar/Wind Harmer
0.94
24686405CER G5
Adder
16.168
971191AH1-055 GEN
Solar/Wind Harmer
33.281
960911AF2-382 GEN
Solar/Wind Harmer
11.778
957541AF2-048 GEN
Solar/Wind Harmer
2.459
972103AH1-617 GEN
Solar/Wind Harmer
31.019
971461AH1-227 GEN
Solar/Wind Harmer
7.843
270346AE1-212 GEN
Solar/Wind Harmer
13.316
943031AE2-326 GEN
Solar/Wind Harmer
5.082
970879AG2-548 GEN
Solar/Wind Harmer
10.556
958121AF2-106 GEN
Solar/Wind Harmer
5.883
270186AC1-089 GEN
Solar/Wind Harmer
7.655
270367AC2-061_GEN
Solar/Wind Harmer
3.969
970093AG2-073 GEN
Solar/Wind Harmer
6.505
972167AH1-666 GEN
Solar/Wind Harmer
9.788
972273AH1-721 GEN
Adder
101.651
3429391JKCT 9G
Adder
10.103
339243AC2-075 GEN1
Solar/Wind Harmer
0.548
339206AE1-143 GEN
Solar/Wind Harmer
2.555
970455AG2-298 GEN
Solar/Wind Harmer
4.167
252507AC2-088 GEN
Solar/Wind Harmer
2.13
958171AF2-111 GEN
Solar/Wind Harmer
29.678
970653AG2-424 GEN
Solar/Wind Harmer
0.827
339255AE2-071 GEN
Solar/Wind Harmer
1.381
339250AF1-203 GEN
Solar/Wind Harmer
0.711
25196008MFTGT1
Adder
1.56
252519AF1-045_GEN
Solar/Wind Harmer
4.199
25194608D.CRK4
Adder
1.876
252524AE2-267 GEN
Solar/Wind Harmer
1.789
25196608WSDLE5
Adder
9.738
270030AE2-140 GEN
Solar/Wind Harmer
22.165
253317AC1-085 GEN4
Solar/Wind Harmer
9.221
946181AF1-283 GEN
Solar/Wind Harmer
14.318
970193AG2-126 GEN
Solar/Wind Harmer
15.92
24728705AND G3
Adder
8.51
24728505AND G1
Adder
4.069
253394AE2-221_GEN
Solar/Wind Harmer
4.804
942481AE2-261 GEN
Solar/Wind Harmer
30.722
957381AF2-032 GEN
Solar/Wind Harmer
2.053
962771AG1-126 GEN
Solar/Wind Harmer
33.21
970153AG2-106 GEN
Solar/Wind Harmer
14.481
24379505HDWTR1G C
Solar/Wind Harmer
8.07
270240V3-007_GEN2
Solar/Wind Harmer
6.314
276785W4-005 GEN1
Solar/Wind Harmer
3.059
971993AH1-541 GEN
Solar/Wind Harmer
9.348
24386205FR-12G C
Solar/Wind Harmer
4.335
247642Z2-115 C
Solar/Wind Harmer
0.064
965461AG1-414 GEN
Solar/Wind Harmer
2.266
970289AG2-191 GEN
Solar/Wind Harmer
0.767
270004AE1-209 GEN
Solar/Wind Harmer
5.447
24690905MDL-1G C
Solar/Wind Harmer
7.997
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274760LEE CO EC;1U
Adder
8.986
274767LEE CO EC;8U
Adder
8.88
274682WAUKEGAN ;7U
Adder
17.092
274729ELWOOD EC;1P
Adder
15.521
274730ELWOOD EC;6P
Adder
15.521
274734ELWOOD EC;8P
Adder
15.521
274736ELWOOD EC;9P
Adder
15.521
237048AF1-022 C
Solar/Wind Helper
0.188
235058AG1-386 C
Solar/Wind Helper
0.45
237046AF1-021 C
Solar/Wind Helper
0.327
202652Y1-033 WT C
Solar/Wind Helper
0.53
24721605FLATG1
50/50
2.675
957241AF2-018 GEN
Solar/Wind Harmer
7.959
270053AF1-130 C
Solar/Wind Harmer
31.802
270399AC1-101 GEN
Solar/Wind Harmer
7.511
270400AC1-102 GEN
Solar/Wind Harmer
7.511
941621AE2-160 GEN
Adder
5.587
970281AG2-184 GEN
Solar/Wind Harmer
32.57
971313AH1-133 GEN
Solar/Wind Harmer
9.12
971061AG2-657 GEN
Solar/Wind Harmer
13.811
971985AH1-537 GEN
Solar/Wind Harmer
27.028
962211AG1-066 GEN
Solar/Wind Harmer
3.543
24734705WLF1G3
Adder
8.207
24734805WLF1G4
Adder
8.207
24734905WLF1G5
Adder
8.207
24735105WLF2G1
Adder
8.038
966391AG1-508 GEN
Solar/Wind Harmer
4.81
971331AH1-145 GEN
Solar/Wind Harmer
12.539
971329AH1-144 GEN
Solar/Wind Harmer
8.009
971981AH1-535 GEN
Solar/Wind Harmer
12.699
972163AH1-664 GEN
Solar/Wind Harmer
12.28
972165AH1-665 GEN
Solar/Wind Harmer
9.824
3429211JKCT 2G
Adder
14.268
270291AC1-194 GEN
Solar/Wind Harmer
6.183
339216AC1-074 GEN
Solar/Wind Harmer
2.024
25196108MFTGT2
Adder
1.775
25196108MFTGT2
Adder
1.648
25196408WSDLE3
Adder
10.024
25196308WSDLE2
Adder
9.937
25196208WSDLE1
Adder
9.912
25196708WSDLE6
Adder
9.887
25196508WSDLE4
Adder
9.638
270444AC2-157 GEN1
Solar/Wind Harmer
6.331
270445AC2-157 GEN2
Solar/Wind Harmer
6.331
270069AE2-166 C O1
Solar/Wind Harmer
10.196
253433AC1-085 GEN1
Solar/Wind Harmer
5.853
253432AC1-085 GEN2
Solar/Wind Harmer
0.295
253406AD2-031_GEN
Solar/Wind Harmer
1.384
270340AC2-060 GEN
Solar/Wind Harmer
3.244
270263AC1-001 GEN
Solar/Wind Harmer
1.117
270356AE2-297 GEN
Solar/Wind Harmer
4.876
944221AF1-090 GEN
Solar/Wind Harmer
11.369
963841AG1-237 GEN
Solar/Wind Harmer
11.16
276763AC1-053 GEN1
Solar/Wind Harmer
4.006
276764AC1-053 GEN2
Solar/Wind Harmer
4.006
276668AB2-070 GEN1
Solar/Wind Harmer
2.24
276848AB2-070 GEN3
Solar/Wind Harmer
2.24
276849AB2-070 GEN2
Solar/Wind Harmer
2.24
24386405FR-21G C
Solar/Wind Harmer
4.35
24387005FR-3G C
Solar/Wind Harmer
4.001
970289AG2-191 GEN
Solar/Wind Harmer
1.899
25306009OHH W.
Adder
2.828
253372AE2-315 SEC3
Adder
1.855
253372AE2-315 SEC3
Adder
1.855
972267AH1-718 GEN
Adder
4.035
274823ROCKFORD ;21
Adder
18.714
274744AC1-111 GEN8
Adder
5.298
274746AC1-111 G10
Adder
5.298
274728ELWOOD EC;5P
Adder
15.521
274731ELWOOD EC;2P
Adder
15.521
274733ELWOOD EC;3P
Adder
15.521
274735ELWOOD EC;4P
Adder
15.521
274675JOLIET 29;7U
Adder
28.931
23750501ELLIOTTS
Solar/Wind Helper
0.639
23652301WDPWR_K20
Solar/Wind Helper
0.139
241997AF1-093 GEN
Solar/Wind Helper
0.244
241985AE1-237 GEN
Solar/Wind Helper
0.238
241982AE2-343 S C
Solar/Wind Helper
0.214
203955AF1-039 C O1
Solar/Wind Helper
0.35
23750701CROSSCHOOL
Solar/Wind Helper
1.122
20089126CSLMN_L13
Solar/Wind Helper
0.556
20089226LOOKOUT
Solar/Wind Helper
0.555
238118U2-030_1
Solar/Wind Helper
0.27
20088926STNY CRK
Solar/Wind Helper
0.759
203940AF1-140 C
Solar/Wind Helper
0.366
20094526CT_V3-030
Solar/Wind Helper
0.437
203846AF2-130 C
Solar/Wind Helper
0.422
23562501BACKB
Solar/Wind Helper
0.844
964991AG1-363 GEN
Solar/Wind Helper
3.438
20092526R32
Solar/Wind Helper
1.076
238127S14_GEN_2
Solar/Wind Helper
0.636
20303426NA_O38_P22
Solar/Wind Helper
0.913
20088626ARWF_N39
Solar/Wind Helper
1.113
946581AF1-322 GEN
Solar/Wind Harmer
3.726
24289405MTG1
50/50
11.803
243186AF1-051 GEN
50/50
12.678
24318705GVG2
50/50
11.752
24721805FLATG3
50/50
2.675
960001AF2-291 GEN
Solar/Wind Harmer
6.087
24723205RIVRG3
Adder
37.214
270331AC1-082 GEN3
Solar/Wind Harmer
0.942
24686505CER G6
Adder
16.296
972203AH1-686 GEN
Adder
4.456
944971AF1-162 GEN
Solar/Wind Harmer
12.535
971403AH1-188 GEN
Solar/Wind Harmer
24.896
24728305BUCHG2
Adder
7.015
971687AH1-348 GEN
Solar/Wind Harmer
1.53
24735205WLF2G2
Adder
8.038
971073AG2-665 GEN
Solar/Wind Harmer
1.534
970091AG2-072 GEN
Adder
95.233
945681AF1-233 GEN
Solar/Wind Harmer
23.089
3429241JKCT 3G
Adder
14.456
339221AD2-048_GEN
Solar/Wind Harmer
1.866
339211AE2-254 GEN
Solar/Wind Harmer
1.837
3429421JKCT 10G
Adder
10.103
943111AE2-339 GEN
Solar/Wind Harmer
1.07
339241AF1-083 GEN
Solar/Wind Harmer
1.979
970653AG2-424 GEN
Solar/Wind Harmer
5.716
964901AG1-354 GEN
Solar/Wind Harmer
17.72
25196808ZIMRHP
Adder
88.501
25196008MFTGT1
Adder
1.61
252516AE2-318_GEN
Solar/Wind Harmer
11.536
252510AF1-249 C
Solar/Wind Harmer
0.479
25194608D.CRK4
Adder
1.876
270336AE1-100 GEN
Solar/Wind Harmer
1.956
253316AC1-085 GEN3
Solar/Wind Harmer
9.221
946171AF1-282 GEN
Solar/Wind Harmer
11.014
943811AF1-049 GEN
Solar/Wind Harmer
4.099
24728605AND G2
Adder
4.069
253398AE2-221_GEN2
Solar/Wind Harmer
4.804
270222AC2-111 GEN
Solar/Wind Harmer
4.717
944031AF1-071 GEN
Solar/Wind Harmer
1.061
963741AG1-226 GEN
Solar/Wind Harmer
46.357
965911AG1-460 GEN
Solar/Wind Harmer
1.434
962761AG1-125 GEN
Solar/Wind Harmer
33.21
970149AG2-104 GEN
Solar/Wind Harmer
20.507
970155AG2-107 GEN
Solar/Wind Harmer
14.481
942081AE2-220 GEN
Solar/Wind Harmer
6.527
270209AC1-174_GEN
Solar/Wind Harmer
4.153
270437AC2-090 C
Solar/Wind Harmer
5.696
270239V3-007_GEN1
Solar/Wind Harmer
1.756
276621W2-048 GEN
Solar/Wind Harmer
6.343
276686W4-005 GEN3
Solar/Wind Harmer
3.059
24385905FR-11G C
Solar/Wind Harmer
8.406
24386605FR-22G C
Solar/Wind Harmer
4.35
276903AD2-071 C
Solar/Wind Harmer
10.104
270594AE1-207 GEN
Solar/Wind Harmer
13.567
270032AE2-172
Solar/Wind Harmer
4.646
270005AE1-210 C O1
Solar/Wind Harmer
5.447
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274761LEE CO EC;2U
Adder
8.986
274766LEE CO EC;7U
Adder
8.88
274822ROCKFORD ;11
Adder
18.851
25326309TAIT D
Adder
1.046
274828WAUKEGAN ;BP
Adder
10.51
274682WAUKEGAN ;7U
Adder
17.092
274745AC1-111 GEN9
Adder
5.298
274732ELWOOD EC;7P
Adder
15.521
274674JOLIET 9 ;6U
Adder
14.533
274676JOLIET 29;8U
Adder
10.203
254303AC2-168 GEN
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.244
238185AF2-356 C
Solar/Wind Helper
2.074
20089026BF_G21_K23
Solar/Wind Helper
0.44
20084626FORWARD
Solar/Wind Helper
0.33
964201AG1-281 GEN
Solar/Wind Helper
0.445
238126S14_GEN_1
Solar/Wind Helper
0.636
20091526CHSTN_FL
Solar/Wind Helper
0.536
238120AE2-309 GEN
Solar/Wind Helper
0.4
962581AG1-107 GEN
Solar/Wind Harmer
6.183
961491AF2-440 GEN
Solar/Wind Harmer
2.569
942891AE2-308 GEN
Solar/Wind Harmer
12.236
972043AH1-570 GEN
Solar/Wind Harmer
3.049
972045AH1-571 GEN
Solar/Wind Harmer
2.439
971125AH1-004 GEN
Solar/Wind Harmer
4.843
970107AG2-081 GEN
Solar/Wind Harmer
3.632
339231AF1-038_GEN
Solar/Wind Harmer
2.178
966021AG1-471 GEN
Solar/Wind Harmer
6.442
971485AH1-239 GEN
Solar/Wind Harmer
9.528
252509AD1-136 GEN
Solar/Wind Harmer
0.304
339236AF1-050_GEN
Solar/Wind Harmer
2.145
964571AG1-320 GEN
Solar/Wind Harmer
9.672
964781AG1-341 GEN
Solar/Wind Harmer
12.441
25183208HLCRTG
Solar/Wind Harmer
6.977
25194408D.CRK1
Adder
8.632
25194508D.CRK3
Adder
1.614
945391AF1-204 GEN
Solar/Wind Harmer
14.791
24728805RICHG1
Adder
3.967
24728905RICHG2
Adder
3.967
253415AE1-040 GEN
Solar/Wind Harmer
1.171
276916AD2-100_GEN
Solar/Wind Harmer
21.637
276911AD2-131_GEN
Solar/Wind Harmer
4.373
970241AG2-163 GEN
Solar/Wind Harmer
25.754
926881AC1-175 GEN
Solar/Wind Harmer
5.696
276615X2-022 GEN
Solar/Wind Harmer
1.992
276838X2-022 GEN2
Solar/Wind Harmer
0.237
24725505WLD G2 C
Solar/Wind Harmer
4.03
24699105WLD G1 C
Solar/Wind Harmer
3.983
274880W4-005 GEN4
Solar/Wind Harmer
3.059
276174W4-005 GEN2
Solar/Wind Harmer
3.059
270383AD1-128 GEN
Solar/Wind Harmer
6.175
24387305FR-4G C
Solar/Wind Harmer
5.138
966841AG1-555 GEN
Solar/Wind Harmer
2.539
970291AG2-192 GEN
Solar/Wind Harmer
1.299
970291AG2-192 GEN
Solar/Wind Harmer
0.418
270180AB1-006 GEN1
Solar/Wind Harmer
7.164
253370AE2-315 SEC1
Adder
1.962
247621Y3-024
Adder
0.233
274764LEE CO EC;5U
Adder
9.007
274765LEE CO EC;6U
Adder
9.007
274762LEE CO EC;3U
Adder
8.986
274763LEE CO EC;4U
Adder
8.901
972235AH1-702 GEN1
Adder
2.423
972236AH1-702 GEN2
Adder
2.107
25322209TAIT E
Adder
9.312
25322209TAIT E
Adder
9.102
274683WAUKEGAN ;8U
Adder
20.05
274683WAUKEGAN ;8U
Adder
16.901
274696ROCKY RD ;4P
Adder
10.84
274695ROCKY RD ;2P
Adder
10.59
274693ROCKY RD ;1P
Adder
10.485
274697ROCKY RD ;3P
Adder
2.877
274674JOLIET 9 ;6U
Adder
14.533
237043AE2-125 C
Solar/Wind Helper
0.172
254304AE2-114 C
Solar/Wind Helper
0.21
254305AE2-115 C
Solar/Wind Helper
0.21
962101AG1-054 GEN
Solar/Wind Helper
0.622
241967AE2-285_GEN
Solar/Wind Helper
0.609
241801AE1-079 GEN
Solar/Wind Helper
0.238
23585401KL_K28_T16
Solar/Wind Helper
1.215
23751201ROTHROCK
Solar/Wind Helper
0.695
235054AD2-180 GEN
Solar/Wind Helper
1.606
946071AF1-272 GEN
Solar/Wind Helper
2.52
238117U2-030
Solar/Wind Helper
0.27
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.83
235531U2-073 GEN
Solar/Wind Helper
2.561
203818AF1-086 GEN
Solar/Wind Helper
1.56
203961AE2-224 GEN
Solar/Wind Helper
2.218
946381AF1-302 GEN
Solar/Wind Helper
0.205
LAGNLTFEXP_LAGN->PJM
CLTF
21.853
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
11.37
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.565
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.151
MECLTFEXP_MEC->PJM
CLTF
16.954
SIGELTFEXP_SIGE->PJM
CLTF
0.599
NYPJM->LTFIMP_NY
CLTF
4.988
LGEELTFEXP_LGEE->PJM
CLTF
8.269
WECLTFEXP_WEC->PJM
CLTF
3.678
AG2-052LTFEXP_AG2-052->PJM
LTF
0.221
AH1-155LTFEXP_AH1-155->PJM
LTF
0.332
CPLELTFEXP_CPLE->PJM
CLTF
7.358
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.448

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.59 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2365.35
MW Contribution:
3.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.153
24802706KYGER 1LP
50/50
2.435
24803506KYGER 5LP
50/50
2.378
971985AH1-537 GEN
Solar/Wind Harmer
49.684
25196408WSDLE3
Adder
9.213
25196308WSDLE2
Adder
9.133
25196208WSDLE1
Adder
9.11
25196708WSDLE6
Adder
9.087
25196508WSDLE4
Adder
8.858
253433AC1-085 GEN1
Solar/Wind Harmer
5.417
253432AC1-085 GEN2
Solar/Wind Harmer
0.273
25196108MFTGT2
Adder
1.534
25196108MFTGT2
Adder
1.424
972163AH1-664 GEN
Solar/Wind Harmer
9.168
972165AH1-665 GEN
Solar/Wind Harmer
7.335
253406AD2-031_GEN
Solar/Wind Harmer
1.154
339216AC1-074 GEN
Solar/Wind Harmer
1.482
270340AC2-060 GEN
Solar/Wind Harmer
2.616
270263AC1-001 GEN
Solar/Wind Harmer
0.88
253372AE2-315 SEC3
Adder
1.561
253372AE2-315 SEC3
Adder
1.561
25306009OHH W.
Adder
2.343
24803406KYGER 5HP
50/50
4.081
24803206KYGER 4HP
50/50
4.076
252516AE2-318_GEN
Solar/Wind Harmer
10.768
25196808ZIMRHP
Adder
80.577
25194608D.CRK4
Adder
1.717
252510AF1-249 C
Solar/Wind Harmer
0.435
253316AC1-085 GEN3
Solar/Wind Harmer
8.534
946171AF1-282 GEN
Solar/Wind Harmer
10.193
25196008MFTGT1
Adder
1.391
253398AE2-221_GEN2
Solar/Wind Harmer
4.361
945681AF1-233 GEN
Solar/Wind Harmer
17.478
339221AD2-048_GEN
Solar/Wind Harmer
1.333
270222AC2-111 GEN
Solar/Wind Harmer
3.827
944031AF1-071 GEN
Solar/Wind Harmer
0.861
270273AD2-016 GEN
Solar/Wind Harmer
2.247
253370AE2-315 SEC1
Adder
1.651
253371AE2-315 SEC2
Adder
1.561
943111AE2-339 GEN
Solar/Wind Harmer
0.715
25326309TAIT D
Adder
0.874
3429421JKCT 10G
Adder
6.485
24803106KYGER 3LP
50/50
2.429
24803306KYGER 4LP
50/50
2.378
971191AH1-055 GEN
Solar/Wind Harmer
71.613
252507AC2-088 GEN
Solar/Wind Harmer
2.061
252519AF1-045_GEN
Solar/Wind Harmer
3.919
25194608D.CRK4
Adder
1.717
252524AE2-267 GEN
Solar/Wind Harmer
1.644
25196608WSDLE5
Adder
8.95
253317AC1-085 GEN4
Solar/Wind Harmer
8.534
946181AF1-283 GEN
Solar/Wind Harmer
13.251
25196008MFTGT1
Adder
1.348
958171AF2-111 GEN
Solar/Wind Harmer
24.74
253394AE2-221_GEN
Solar/Wind Harmer
4.361
972167AH1-666 GEN
Solar/Wind Harmer
7.448
270367AC2-061_GEN
Solar/Wind Harmer
2.87
270186AC1-089 GEN
Solar/Wind Harmer
5.445
24803006KYGER 3HP
50/50
4.125
24802806KYGER 2HP
50/50
4.108
24802906KYGER 2LP
50/50
2.412
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.294
25183208HLCRTG
Solar/Wind Harmer
6.595
25194408D.CRK1
Adder
7.9
25194508D.CRK3
Adder
1.477
962581AG1-107 GEN
Solar/Wind Harmer
4.434
961491AF2-440 GEN
Solar/Wind Harmer
1.843
972043AH1-570 GEN
Solar/Wind Harmer
2.117
972045AH1-571 GEN
Solar/Wind Harmer
1.694
270269AC2-059
Solar/Wind Harmer
7.883
253415AE1-040 GEN
Solar/Wind Harmer
0.948
253370AE2-315 SEC1
Adder
1.651
971125AH1-004 GEN
Solar/Wind Harmer
3.263
970107AG2-081 GEN
Solar/Wind Harmer
2.447
24728805RICHG1
Adder
3.029
24728905RICHG2
Adder
3.029
25322209TAIT E
Adder
7.785
25322209TAIT E
Adder
7.61
253349AC2-067 GEN
Solar/Wind Harmer
1.622
253400AC2-068 GEN
Solar/Wind Harmer
0.652
25326109MON D
Adder
1.021
926881AC1-175 GEN
Solar/Wind Harmer
4.212
942891AE2-308 GEN
Solar/Wind Harmer
7.426
270383AD1-128 GEN
Solar/Wind Harmer
4.53
970883AG2-550 GEN
Solar/Wind Harmer
7.251
970885AG2-551 GEN
Solar/Wind Harmer
1.686
247621Y3-024
Adder
0.167
964611AG1-324 GEN
Solar/Wind Harmer
0.36
270201AC2-176 GEN
Solar/Wind Harmer
3.513
24725505WLD G2 C
Solar/Wind Harmer
2.705
24699105WLD G1 C
Solar/Wind Harmer
2.673
270031AE2-169
Solar/Wind Harmer
5.45
270599AE1-208 GEN
Solar/Wind Harmer
5.45
964571AG1-320 GEN
Solar/Wind Harmer
5.334
970291AG2-192 GEN
Solar/Wind Harmer
0.843
970291AG2-192 GEN
Solar/Wind Harmer
0.272
944541AF1-119 GEN
Solar/Wind Harmer
2.715
960971AF2-388 GEN
Solar/Wind Harmer
7.089
942221AE2-234 GEN
Solar/Wind Harmer
2.151
945391AF1-204 GEN
Solar/Wind Harmer
8.333
970241AG2-163 GEN
Solar/Wind Harmer
14.459
25326509SID D
Adder
0.751
24387305FR-4G C
Solar/Wind Harmer
2.878
966841AG1-555 GEN
Solar/Wind Harmer
1.422
270180AB1-006 GEN1
Solar/Wind Harmer
4.02
24697605MDL-3G C
Solar/Wind Harmer
2.06
24755605MDL-5G
Solar/Wind Harmer
1.347
24697905MDL-4G C
Solar/Wind Harmer
1.282
270181AB1-006 GEN2
Solar/Wind Harmer
0.4
945421AF1-207 GEN
Solar/Wind Harmer
7.8
957841AF2-078 GEN
Solar/Wind Harmer
3.358
339236AF1-050_GEN
Solar/Wind Harmer
0.993
274880W4-005 GEN4
Solar/Wind Harmer
1.638
276174W4-005 GEN2
Solar/Wind Harmer
1.638
276615X2-022 GEN
Solar/Wind Harmer
1.059
276838X2-022 GEN2
Solar/Wind Harmer
0.126
276916AD2-100_GEN
Solar/Wind Harmer
11.356
276911AD2-131_GEN
Solar/Wind Harmer
2.295
270535AF1-215 GEN1
Solar/Wind Harmer
2.441
270536AF1-215 GEN2
Solar/Wind Harmer
2.441
274770LINCOLN ;1U
Adder
4.436
274771LINCOLN ;2U
Adder
4.436
274674JOLIET 9 ;6U
Adder
8.063
274805UNIV PK N;1U
Adder
2.628
274808UNIV PK N;4U
Adder
2.611
274696ROCKY RD ;4P
Adder
5.933
274695ROCKY RD ;2P
Adder
5.796
274693ROCKY RD ;1P
Adder
5.739
274697ROCKY RD ;3P
Adder
1.575
237033AB1-150 GEN
Solar/Wind Helper
0.409
960611AF2-352 GEN
Solar/Wind Harmer
0.12
270356AE2-297 GEN
Solar/Wind Harmer
3.599
3429211JKCT 2G
Adder
8.841
971029AG2-637 GEN
Solar/Wind Harmer
11.181
270543AE2-219 C
Solar/Wind Harmer
7.251
247536S-71 GEN
Solar/Wind Harmer
2.858
964611AG1-324 GEN
Solar/Wind Harmer
2.681
961761AG1-017 GEN
Solar/Wind Harmer
0.293
945581AF1-223 GEN
Solar/Wind Harmer
3.049
241972AD1-140 GEN
Solar/Wind Harmer
2.984
270432AC2-029 GEN
Solar/Wind Harmer
4.634
970289AG2-191 GEN
Solar/Wind Harmer
1.232
958711AF2-162 GEN
Solar/Wind Harmer
0.656
24729505KEY G4
Adder
4.046
253338AC1-165 GEN
Solar/Wind Harmer
0.663
253343AC1-166 GEN
Solar/Wind Harmer
0.663
270444AC2-157 GEN1
Solar/Wind Harmer
3.34
270445AC2-157 GEN2
Solar/Wind Harmer
3.34
963841AG1-237 GEN
Solar/Wind Harmer
6.259
24386405FR-21G C
Solar/Wind Harmer
2.437
24387005FR-3G C
Solar/Wind Harmer
2.241
963791AG1-232 GEN
Solar/Wind Harmer
7.617
946581AF1-322 GEN
Solar/Wind Harmer
5.719
24691005MDL-2G C
Solar/Wind Harmer
2.067
270071AF1-092 GEN
Solar/Wind Harmer
8.327
959141AF2-205 GEN
Solar/Wind Harmer
3.307
958391AF2-133 GEN
Solar/Wind Harmer
4.945
944221AF1-090 GEN
Solar/Wind Harmer
5.93
276668AB2-070 GEN1
Solar/Wind Harmer
1.199
276848AB2-070 GEN3
Solar/Wind Harmer
1.199
276849AB2-070 GEN2
Solar/Wind Harmer
1.199
276763AC1-053 GEN1
Solar/Wind Harmer
2.139
276764AC1-053 GEN2
Solar/Wind Harmer
2.139
274853TWINGROVE;U1
Solar/Wind Harmer
3.87
274775LINCOLN ;6U
Adder
4.436
274776LINCOLN ;7U
Adder
4.436
274777LINCOLN ;8U
Adder
4.436
972227AH1-698 GEN1
Adder
1.369
972228AH1-698 GEN2
Adder
1.944
274728ELWOOD EC;5P
Adder
8.613
274731ELWOOD EC;2P
Adder
8.614
274733ELWOOD EC;3P
Adder
8.614
274735ELWOOD EC;4P
Adder
8.614
274800UNIV PARK;3U
Adder
3.055
274801UNIV PARK;4U
Adder
3.055
972037AH1-567 GEN1
Adder
0.096
274827FISK ;RP
Adder
4.063
274687WILL CNTY;4U
Adder
14.622
274687WILL CNTY;4U
Adder
14.622
274675JOLIET 29;7U
Adder
16.054
274675JOLIET 29;7U
Adder
15.48
274744AC1-111 GEN8
Adder
2.918
274746AC1-111 G10
Adder
2.918
274854TWINGROVE;U2
Solar/Wind Harmer
0.363
339243AC2-075 GEN1
Solar/Wind Harmer
0.401
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.651
253371AE2-315 SEC2
Adder
1.561
960071AF2-298 GEN
Solar/Wind Harmer
1.198
3429391JKCT 9G
Adder
6.485
24379505HDWTR1G C
Solar/Wind Harmer
5.968
270240V3-007_GEN2
Solar/Wind Harmer
4.669
970093AG2-073 GEN
Solar/Wind Harmer
3.762
270004AE1-209 GEN
Solar/Wind Harmer
3.872
24728705AND G3
Adder
5.634
24728505AND G1
Adder
2.694
946031AF1-268 GEN
Solar/Wind Harmer
5.828
970825AG2-519 GEN
Solar/Wind Harmer
3.944
962031AG1-047 GEN
Solar/Wind Harmer
2.067
957741AF2-068 GEN
Solar/Wind Harmer
10.253
970455AG2-298 GEN
Solar/Wind Harmer
2.327
965461AG1-414 GEN
Solar/Wind Harmer
1.471
970289AG2-191 GEN
Solar/Wind Harmer
0.498
247642Z2-115 C
Solar/Wind Harmer
0.041
970653AG2-424 GEN
Solar/Wind Harmer
0.434
944531AF1-118 GEN
Solar/Wind Harmer
21.518
253325AC1-069 GEN
Solar/Wind Harmer
0.639
970193AG2-126 GEN
Solar/Wind Harmer
8.969
339206AE1-143 GEN
Solar/Wind Harmer
1.271
24386205FR-12G C
Solar/Wind Harmer
2.428
24690905MDL-1G C
Solar/Wind Harmer
4.487
970781AG2-491 GEN
Solar/Wind Harmer
5.589
270518AE2-148 GEN
Solar/Wind Harmer
6.728
964401AG1-302 GEN
Solar/Wind Harmer
4.923
276785W4-005 GEN1
Solar/Wind Harmer
1.638
971993AH1-541 GEN
Solar/Wind Harmer
5.005
942481AE2-261 GEN
Solar/Wind Harmer
16.153
957381AF2-032 GEN
Solar/Wind Harmer
1.08
972273AH1-721 GEN
Adder
43.936
274772LINCOLN ;3U
Adder
4.436
972259AH1-714 GEN
Adder
10.006
274729ELWOOD EC;1P
Adder
8.614
274730ELWOOD EC;6P
Adder
8.613
274734ELWOOD EC;8P
Adder
8.613
274736ELWOOD EC;9P
Adder
8.613
274803UNIV PARK;6U
Adder
3.054
972038AH1-567 GEN2
Adder
0.191
274826FISK ;BP
Adder
5.733
274814UNIV PK N;0U
Adder
2.645
274807UNIV PK N;3U
Adder
2.64
274811UNIV PK N;7U
Adder
2.622
274724RIVER EC ;11
Adder
9.272
274752CRETE EC ;2U
Adder
4.313
274753CRETE EC ;3U
Adder
4.313
274676JOLIET 29;8U
Adder
15.48
274682WAUKEGAN ;7U
Adder
5.491
270330AC1-082 GEN2
Solar/Wind Helper
0.195
270329AC1-082 GEN1
Solar/Wind Helper
0.195
3429241JKCT 3G
Adder
8.957
942081AE2-220 GEN
Solar/Wind Harmer
4.827
270209AC1-174_GEN
Solar/Wind Harmer
3.072
270437AC2-090 C
Solar/Wind Harmer
4.212
270239V3-007_GEN1
Solar/Wind Harmer
1.299
270005AE1-210 C O1
Solar/Wind Harmer
3.872
24728605AND G2
Adder
2.694
970825AG2-519 GEN
Solar/Wind Harmer
1.469
945371AF1-202 GEN
Solar/Wind Harmer
4.69
276903AD2-071 C
Solar/Wind Harmer
6.702
270594AE1-207 GEN
Solar/Wind Harmer
8.993
270032AE2-172
Solar/Wind Harmer
3.08
339211AE2-254 GEN
Solar/Wind Harmer
0.998
958861AF2-177 GEN
Solar/Wind Harmer
7.178
965651AG1-433 GEN
Solar/Wind Harmer
3.544
270024AE2-089 GEN
Solar/Wind Harmer
2.988
970653AG2-424 GEN
Solar/Wind Harmer
3.003
253333AC1-068 GEN
Solar/Wind Harmer
0.639
970091AG2-072 GEN
Adder
46.355
963741AG1-226 GEN
Solar/Wind Harmer
26.027
339241AF1-083 GEN
Solar/Wind Harmer
0.959
24385905FR-11G C
Solar/Wind Harmer
4.709
24386605FR-22G C
Solar/Wind Harmer
2.437
24791305MDL-5G
Solar/Wind Harmer
1.347
940581AE2-045 GEN
Solar/Wind Harmer
5.601
971605AH1-302 GEN
Solar/Wind Harmer
4.789
964861AG1-349 GEN
Solar/Wind Harmer
4.271
971917AH1-482 GEN
Solar/Wind Harmer
4.927
958381AF2-132 GEN
Solar/Wind Harmer
4.923
964901AG1-354 GEN
Solar/Wind Harmer
8.138
276686W4-005 GEN3
Solar/Wind Harmer
1.638
276621W2-048 GEN
Solar/Wind Harmer
3.373
965911AG1-460 GEN
Solar/Wind Harmer
0.754
270055AF2-134 C O1
Solar/Wind Harmer
1.627
274773LINCOLN ;4U
Adder
4.436
274774LINCOLN ;5U
Adder
4.436
274732ELWOOD EC;7P
Adder
8.613
274802UNIV PARK;5U
Adder
3.054
274674JOLIET 9 ;6U
Adder
8.063
274812UNIV PK N;8U
Adder
2.622
274723RIVER EC ;12
Adder
9.381
274751CRETE EC ;1U
Adder
4.313
274754CRETE EC ;4U
Adder
4.313
274676JOLIET 29;8U
Adder
16.054
274745AC1-111 GEN9
Adder
2.918
960001AF2-291 GEN
Solar/Wind Helper
1.729
270331AC1-082 GEN3
Solar/Wind Helper
0.194
235780M24_1
Solar/Wind Helper
0.507
LAGNLTFEXP_LAGN->PJM
CLTF
6.674
TVALTFEXP_TVA->PJM
CLTF
3.152
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.061
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.047
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.848
MECLTFEXP_MEC->PJM
CLTF
8.254
SIGELTFEXP_SIGE->PJM
CLTF
0.338
NYPJM->LTFIMP_NY
CLTF
1.71
LGEELTFEXP_LGEE->PJM
CLTF
5.221
WECLTFEXP_WEC->PJM
CLTF
1.971
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.322
AG2-052LTFEXP_AG2-052->PJM
LTF
0.126
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.683

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2185.8
MW Contribution:
2.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.079
252516AE2-318_GEN
Solar/Wind Harmer
8.283
25196808ZIMRHP
Adder
79.38
25194608D.CRK4
Adder
1.689
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.986
25196008MFTGT1
Adder
1.369
253398AE2-221_GEN2
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.031
270273AD2-016 GEN
Solar/Wind Harmer
0.594
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
25326309TAIT D
Adder
0.844
3429421JKCT 10G
Adder
6.396
970773AG2-487 GEN
Solar/Wind Harmer
0.939
3429241JKCT 3G
Adder
8.835
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.76
270005AE1-210 C O1
Solar/Wind Harmer
1.04
24728605AND G2
Adder
2.628
970825AG2-519 GEN
Solar/Wind Harmer
1.683
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.07
270594AE1-207 GEN
Solar/Wind Harmer
5.019
270032AE2-172
Solar/Wind Harmer
2.988
958861AF2-177 GEN
Solar/Wind Harmer
1.919
965651AG1-433 GEN
Solar/Wind Harmer
1.282
270024AE2-089 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.063
970091AG2-072 GEN
Adder
45.503
253333AC1-068 GEN
Solar/Wind Harmer
0.005
963741AG1-226 GEN
Solar/Wind Harmer
9.274
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
964901AG1-354 GEN
Solar/Wind Harmer
5.594
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.628
276621W2-048 GEN
Solar/Wind Harmer
0.183
965911AG1-460 GEN
Solar/Wind Harmer
0.732
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.756
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
5.074
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.536
939401AE1-172 GEN
Solar/Wind Harmer
2.672
941551AE2-152 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
4.277
274774LINCOLN ;5U
Adder
4.277
971997AH1-543 GEN
Solar/Wind Harmer
1.853
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.311
274674JOLIET 9 ;6U
Adder
7.779
276694AA1-018 GEN2
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
10.575
274802UNIV PARK;5U
Adder
2.945
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.411
276646AC1-214 GEN2
Solar/Wind Harmer
0.138
274848CAMPGROVE;RU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.488
274812UNIV PK N;8U
Adder
2.528
274723RIVER EC ;12
Adder
9.04
274751CRETE EC ;1U
Adder
4.155
274754CRETE EC ;4U
Adder
4.155
274745AC1-111 GEN9
Adder
2.817
962781AG1-127 GEN
Solar/Wind Harmer
3.332
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
10.473
959081AF2-199 GEN
Solar/Wind Harmer
3.491
971067AG2-660 GEN
Solar/Wind Harmer
1.164
276708O09 GEN2
Solar/Wind Harmer
0.123
970819AG2-516 GEN
Solar/Wind Harmer
4.177
274858EASY ROAD;U2
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
5.58
945111AF1-176 GEN
Solar/Wind Harmer
5.962
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.73
965011AG1-365 GEN
Solar/Wind Harmer
3.232
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.193
235780M24_1
Solar/Wind Helper
0.496
24803006KYGER 3HP
50/50
4.127
24802806KYGER 2HP
50/50
4.111
24802906KYGER 2LP
50/50
2.413
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.768
25194508D.CRK3
Adder
1.452
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.516
972045AH1-571 GEN
Solar/Wind Harmer
1.214
270269AC2-059
Solar/Wind Harmer
0
971125AH1-004 GEN
Solar/Wind Harmer
2.245
970107AG2-081 GEN
Solar/Wind Harmer
1.684
253370AE2-315 SEC1
Adder
1.601
24728805RICHG1
Adder
2.955
24728905RICHG2
Adder
2.955
25322209TAIT E
Adder
7.522
25322209TAIT E
Adder
7.353
25326109MON D
Adder
0.984
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.111
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.905
970885AG2-551 GEN
Solar/Wind Harmer
1.635
247621Y3-024
Adder
0.162
964611AG1-324 GEN
Solar/Wind Harmer
0.348
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
2.485
270599AE1-208 GEN
Solar/Wind Harmer
4.141
971613AH1-306 GEN
Solar/Wind Harmer
2.151
964571AG1-320 GEN
Solar/Wind Harmer
4.079
970291AG2-192 GEN
Solar/Wind Harmer
0.57
970291AG2-192 GEN
Solar/Wind Harmer
0.263
944541AF1-119 GEN
Solar/Wind Harmer
0.292
960971AF2-388 GEN
Solar/Wind Harmer
2.564
942221AE2-234 GEN
Solar/Wind Harmer
1.655
971587AH1-292 GEN
Solar/Wind Harmer
2.993
945391AF1-204 GEN
Solar/Wind Harmer
4.316
970241AG2-163 GEN
Solar/Wind Harmer
2.286
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.434
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.7
276911AD2-131_GEN
Solar/Wind Harmer
0.507
276615X2-022 GEN
Solar/Wind Harmer
0.038
276838X2-022 GEN2
Solar/Wind Harmer
0.206
25326509SID D
Adder
0.689
960611AF2-352 GEN
Solar/Wind Harmer
1.21
942111AE2-223 GEN
Solar/Wind Harmer
1.178
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
8.857
274770LINCOLN ;1U
Adder
4.277
274771LINCOLN ;2U
Adder
4.277
276901AD2-066 C O1
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.206
276776AD2-060 GEN
Solar/Wind Harmer
0.377
958011AF2-095 GEN
Solar/Wind Harmer
5.084
970941AG2-585 GEN
Solar/Wind Harmer
1.942
276893AG1-478 C
Solar/Wind Harmer
0.235
274674JOLIET 9 ;6U
Adder
7.779
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.287
958491AF2-143 GEN
Solar/Wind Harmer
5.287
276645AC1-214 GEN1
Solar/Wind Harmer
0.138
274805UNIV PK N;1U
Adder
2.533
274808UNIV PK N;4U
Adder
2.517
274696ROCKY RD ;4P
Adder
5.728
274695ROCKY RD ;2P
Adder
5.596
274693ROCKY RD ;1P
Adder
5.541
274697ROCKY RD ;3P
Adder
1.52
962691AG1-118 GEN
Solar/Wind Harmer
10.508
964781AG1-341 GEN
Solar/Wind Harmer
3.705
971341AH1-150 GEN
Solar/Wind Harmer
6.982
971343AH1-151 GEN
Solar/Wind Harmer
6.982
970349AG2-230 GEN
Solar/Wind Harmer
5.234
965681AG1-436 GEN
Solar/Wind Harmer
4.361
965791AG1-447 GEN
Solar/Wind Harmer
3.198
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.562
938861AE1-114 GEN
Solar/Wind Harmer
1.972
970329AG2-216 GEN
Solar/Wind Harmer
1.444
961051AF2-396 GEN
Solar/Wind Harmer
6.65
961051AF2-396 GEN
Solar/Wind Harmer
4.433
971485AH1-239 GEN
Solar/Wind Harmer
2.603
966021AG1-471 GEN
Solar/Wind Harmer
1.739
270246TR4_N_V150
Solar/Wind Harmer
0.019
270247TR4_N_V136
Solar/Wind Harmer
0.019
237033AB1-150 GEN
Solar/Wind Helper
0.401
24803106KYGER 3LP
50/50
2.43
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
68.684
252507AC2-088 GEN
Solar/Wind Harmer
0.357
252519AF1-045_GEN
Solar/Wind Harmer
3.858
25194608D.CRK4
Adder
1.689
25196608WSDLE5
Adder
8.798
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.081
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
17.024
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.127
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
970191AG2-125 GEN
Solar/Wind Harmer
1.385
3429391JKCT 9G
Adder
6.396
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.143
270004AE1-209 GEN
Solar/Wind Harmer
1.04
24728705AND G3
Adder
5.496
24728505AND G1
Adder
2.628
946031AF1-268 GEN
Solar/Wind Harmer
4.524
970825AG2-519 GEN
Solar/Wind Harmer
3.571
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.92
970455AG2-298 GEN
Solar/Wind Harmer
1.776
970289AG2-191 GEN
Solar/Wind Harmer
0.483
247642Z2-115 C
Solar/Wind Harmer
0.002
970653AG2-424 GEN
Solar/Wind Harmer
0.428
944531AF1-118 GEN
Solar/Wind Harmer
18.504
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970193AG2-126 GEN
Solar/Wind Harmer
6.094
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.775
270518AE2-148 GEN
Solar/Wind Harmer
0.304
971993AH1-541 GEN
Solar/Wind Harmer
1.694
942481AE2-261 GEN
Solar/Wind Harmer
10.95
957381AF2-032 GEN
Solar/Wind Harmer
0.83
964401AG1-302 GEN
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
43.369
965091AG1-374 GEN
Solar/Wind Harmer
10.891
959611AF2-252 GEN
Solar/Wind Harmer
1.21
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
4.277
274887GEN-1.85
Solar/Wind Harmer
0.092
276843GEN-1.7
Solar/Wind Harmer
0.114
276806AD2-047 C O1
Solar/Wind Harmer
2.001
972259AH1-714 GEN
Adder
9.653
274729ELWOOD EC;1P
Adder
8.311
274730ELWOOD EC;6P
Adder
8.311
274734ELWOOD EC;8P
Adder
8.311
274736ELWOOD EC;9P
Adder
8.311
970707AG2-453 GEN
Solar/Wind Harmer
11.521
270043AE2-236 GEN
Solar/Wind Harmer
2.263
972038AH1-567 GEN2
Adder
0.184
970571AG2-364 GEN
Solar/Wind Harmer
7.05
274803UNIV PARK;6U
Adder
2.945
276868AE1-113 GEN
Solar/Wind Harmer
0.705
274879MINONK ;1U
Solar/Wind Harmer
0.147
274862TOP CROP ;2U
Solar/Wind Harmer
0.476
274826FISK ;BP
Adder
5.528
274676JOLIET 29;8U
Adder
14.935
274814UNIV PK N;0U
Adder
2.55
274807UNIV PK N;3U
Adder
2.544
274811UNIV PK N;7U
Adder
2.528
274724RIVER EC ;11
Adder
8.935
274752CRETE EC ;2U
Adder
4.155
274753CRETE EC ;3U
Adder
4.155
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
943121AE2-341 GEN
Solar/Wind Harmer
5.893
943591AF1-030 GEN
Solar/Wind Harmer
3.919
274682WAUKEGAN ;7U
Adder
5.301
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
959091AF2-200 GEN
Solar/Wind Harmer
6.982
971347AH1-153 GEN
Solar/Wind Harmer
1.745
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
8.801
971087AG2-675 GEN
Solar/Wind Harmer
1.841
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
3.511
945111AF1-176 GEN
Solar/Wind Harmer
2.708
965021AG1-366 GEN
Solar/Wind Harmer
1.077
270330AC1-082 GEN2
Solar/Wind Helper
0.194
270329AC1-082 GEN1
Solar/Wind Helper
0.194
24802606KYGER 1HP
50/50
4.156
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
971985AH1-537 GEN
Solar/Wind Harmer
5.763
25196408WSDLE3
Adder
9.057
25196308WSDLE2
Adder
8.978
25196208WSDLE1
Adder
8.956
25196708WSDLE6
Adder
8.933
25196508WSDLE4
Adder
8.708
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.401
972163AH1-664 GEN
Solar/Wind Harmer
7.027
972165AH1-665 GEN
Solar/Wind Harmer
5.628
253406AD2-031_GEN
Solar/Wind Harmer
0.458
339216AC1-074 GEN
Solar/Wind Harmer
0.162
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.58
253372AE2-315 SEC3
Adder
1.514
253372AE2-315 SEC3
Adder
1.514
25306009OHH W.
Adder
2.27
270356AE2-297 GEN
Solar/Wind Harmer
0
3429211JKCT 2G
Adder
8.721
971029AG2-637 GEN
Solar/Wind Harmer
7.57
270543AE2-219 C
Solar/Wind Harmer
3.433
247536S-71 GEN
Solar/Wind Harmer
0.191
964611AG1-324 GEN
Solar/Wind Harmer
1.811
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.738
270432AC2-029 GEN
Solar/Wind Harmer
2.001
241972AD1-140 GEN
Solar/Wind Harmer
0.484
970289AG2-191 GEN
Solar/Wind Harmer
0.834
24729505KEY G4
Adder
3.899
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.68
24386405FR-21G C
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.053
270071AF1-092 GEN
Solar/Wind Harmer
7.11
971611AH1-305 GEN
Solar/Wind Harmer
2.204
959141AF2-205 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.16
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.144
276848AB2-070 GEN3
Solar/Wind Harmer
0.143
276849AB2-070 GEN2
Solar/Wind Harmer
0.144
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.806
970169AG2-114 GEN
Solar/Wind Harmer
3.591
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
4.277
274776LINCOLN ;7U
Adder
4.277
274777LINCOLN ;8U
Adder
4.277
926823AC1-168 GEN
Solar/Wind Harmer
0.6
972228AH1-698 GEN2
Adder
1.875
972227AH1-698 GEN1
Adder
1.321
970833AG2-524 GEN
Solar/Wind Harmer
3.884
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.53
274728ELWOOD EC;5P
Adder
8.311
274731ELWOOD EC;2P
Adder
8.311
274733ELWOOD EC;3P
Adder
8.311
274735ELWOOD EC;4P
Adder
8.311
274800UNIV PARK;3U
Adder
2.946
274801UNIV PARK;4U
Adder
2.946
970073AG2-061 GEN
Solar/Wind Harmer
1.175
972037AH1-567 GEN1
Adder
0.092
274827FISK ;RP
Adder
3.918
274675JOLIET 29;7U
Adder
15.488
274675JOLIET 29;7U
Adder
14.935
274687WILL CNTY;4U
Adder
14.106
274687WILL CNTY;4U
Adder
14.106
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
274744AC1-111 GEN8
Adder
2.817
274746AC1-111 G10
Adder
2.817
276861AD2-134 GEN
Solar/Wind Harmer
0.062
276863AD2-134 GEN
Solar/Wind Harmer
0.062
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.237
971171AH1-044 GEN
Solar/Wind Harmer
6.982
960681AF2-359 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.123
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
971681AH1-341 GEN
Solar/Wind Harmer
5.605
946321AF1-296 GEN
Solar/Wind Harmer
1.935
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.411
970031AG2-029 GEN
Solar/Wind Harmer
1.822
959331AF2-224 GEN
Solar/Wind Harmer
2.262
965041AG1-368 GEN
Solar/Wind Harmer
3.099
247521TR3_G114
Solar/Wind Harmer
0.11
965051AG1-369 GEN
Solar/Wind Harmer
1.514
945631AF1-228 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
6.245
LAGNLTFEXP_LAGN->PJM
CLTF
6.552
TVALTFEXP_TVA->PJM
CLTF
3.106
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.044
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.317
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.627
MECLTFEXP_MEC->PJM
CLTF
8.009
SIGELTFEXP_SIGE->PJM
CLTF
0.331
NYPJM->LTFIMP_NY
CLTF
1.666
LGEELTFEXP_LGEE->PJM
CLTF
5.14
WECLTFEXP_WEC->PJM
CLTF
1.904
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.289
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.393

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.27 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2052.4
MW Contribution:
2.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252516AE2-318_GEN
Solar/Wind Harmer
8.746
25196808ZIMRHP
Adder
83.622
25194608D.CRK4
Adder
1.776
252510AF1-249 C
Solar/Wind Harmer
0.057
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.475
25196008MFTGT1
Adder
1.43
253398AE2-221_GEN2
Solar/Wind Harmer
0
24803006KYGER 3HP
50/50
4.179
24802806KYGER 2HP
50/50
4.162
24802906KYGER 2LP
50/50
2.443
25183008BIOENL
50/50
0.032
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
8.168
25194508D.CRK3
Adder
1.527
270269AC2-059
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.575
972045AH1-571 GEN
Solar/Wind Harmer
1.262
253370AE2-315 SEC1
Adder
1.716
971125AH1-004 GEN
Solar/Wind Harmer
2.323
970107AG2-081 GEN
Solar/Wind Harmer
1.743
25322209TAIT E
Adder
8.074
25322209TAIT E
Adder
7.893
25326109MON D
Adder
1.062
24728805RICHG1
Adder
2.987
24728905RICHG2
Adder
2.987
942891AE2-308 GEN
Solar/Wind Harmer
5.239
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.803
970885AG2-551 GEN
Solar/Wind Harmer
1.601
247621Y3-024
Adder
0.156
964571AG1-320 GEN
Solar/Wind Harmer
4.114
964611AG1-324 GEN
Solar/Wind Harmer
0.333
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
2.045
270031AE2-169
Solar/Wind Harmer
2.337
270599AE1-208 GEN
Solar/Wind Harmer
3.895
970291AG2-192 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.25
971587AH1-292 GEN
Solar/Wind Harmer
3.03
25326509SID D
Adder
0.755
944541AF1-119 GEN
Solar/Wind Harmer
0.265
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.175
942221AE2-234 GEN
Solar/Wind Harmer
1.514
970329AG2-216 GEN
Solar/Wind Harmer
1.606
970241AG2-163 GEN
Solar/Wind Harmer
2.168
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.406
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.149
276911AD2-131_GEN
Solar/Wind Harmer
0.471
964781AG1-341 GEN
Solar/Wind Harmer
3.596
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.19
942861AE2-305 GEN
Solar/Wind Harmer
2.579
960611AF2-352 GEN
Solar/Wind Harmer
1.092
942111AE2-223 GEN
Solar/Wind Harmer
1.058
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.122
971485AH1-239 GEN
Solar/Wind Harmer
2.492
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.619
966021AG1-471 GEN
Solar/Wind Harmer
1.662
276897AD1-100 C
Solar/Wind Harmer
7.68
958481AF2-142 GEN
Solar/Wind Harmer
4.605
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.494
276893AG1-478 C
Solar/Wind Harmer
0.204
274888KELLY CRK;1U
Solar/Wind Harmer
0.178
276776AD2-060 GEN
Solar/Wind Harmer
0.326
958011AF2-095 GEN
Solar/Wind Harmer
4.397
274674JOLIET 9 ;6U
Adder
6.739
970941AG2-585 GEN
Solar/Wind Harmer
1.679
971341AH1-150 GEN
Solar/Wind Harmer
6.093
971343AH1-151 GEN
Solar/Wind Harmer
6.093
938861AE1-114 GEN
Solar/Wind Harmer
1.726
962691AG1-118 GEN
Solar/Wind Harmer
9.136
274764LEE CO EC;5U
Adder
4.07
274765LEE CO EC;6U
Adder
4.07
274762LEE CO EC;3U
Adder
4.061
274763LEE CO EC;4U
Adder
4.023
274696ROCKY RD ;4P
Adder
4.974
274695ROCKY RD ;2P
Adder
4.859
274693ROCKY RD ;1P
Adder
4.811
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.19
274683WAUKEGAN ;8U
Adder
7.747
972235AH1-702 GEN1
Adder
1.099
972236AH1-702 GEN2
Adder
0.956
237033AB1-150 GEN
Solar/Wind Helper
0.404
24803106KYGER 3LP
50/50
2.46
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
70.432
252507AC2-088 GEN
Solar/Wind Harmer
0.376
252519AF1-045_GEN
Solar/Wind Harmer
4.074
25194608D.CRK4
Adder
1.776
25196608WSDLE5
Adder
9.253
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.717
958171AF2-111 GEN
Solar/Wind Harmer
17.947
25196008MFTGT1
Adder
1.385
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.382
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
970191AG2-125 GEN
Solar/Wind Harmer
1.47
3429391JKCT 9G
Adder
6.589
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.224
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970455AG2-298 GEN
Solar/Wind Harmer
1.797
270004AE1-209 GEN
Solar/Wind Harmer
0.992
946031AF1-268 GEN
Solar/Wind Harmer
4.337
970825AG2-519 GEN
Solar/Wind Harmer
3.419
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.615
970653AG2-424 GEN
Solar/Wind Harmer
0.429
270518AE2-148 GEN
Solar/Wind Harmer
0.348
970289AG2-191 GEN
Solar/Wind Harmer
0.457
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
5.894
944531AF1-118 GEN
Solar/Wind Harmer
16.286
24386205FR-12G C
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
42.335
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.495
942481AE2-261 GEN
Solar/Wind Harmer
10.146
957381AF2-032 GEN
Solar/Wind Harmer
0.768
971993AH1-541 GEN
Solar/Wind Harmer
1.554
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
9.828
959611AF2-252 GEN
Solar/Wind Harmer
1.092
274878BISHOP HL;2U
Solar/Wind Harmer
0.104
276782AC1-033 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.202
942051AE2-217 GEN
Solar/Wind Harmer
5.57
276868AE1-113 GEN
Solar/Wind Harmer
0.616
274879MINONK ;1U
Solar/Wind Harmer
0.129
939351AE1-166 GEN
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.415
274729ELWOOD EC;1P
Adder
7.204
274730ELWOOD EC;6P
Adder
7.204
274734ELWOOD EC;8P
Adder
7.204
274736ELWOOD EC;9P
Adder
7.204
274887GEN-1.85
Solar/Wind Harmer
0.079
276843GEN-1.7
Solar/Wind Harmer
0.099
276806AD2-047 C O1
Solar/Wind Harmer
1.73
972259AH1-714 GEN
Adder
8.342
274676JOLIET 29;8U
Adder
12.928
972038AH1-567 GEN2
Adder
0.159
274803UNIV PARK;6U
Adder
2.546
274855GSG-6 ;RU
Solar/Wind Harmer
0.111
274850MENDOTA H;RU
Solar/Wind Harmer
0.035
946671AF1-331 GEN
Solar/Wind Harmer
0.325
959091AF2-200 GEN
Solar/Wind Harmer
6.093
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
7.765
274760LEE CO EC;1U
Adder
4.061
274767LEE CO EC;8U
Adder
4.013
971087AG2-675 GEN
Solar/Wind Harmer
1.624
274826FISK ;BP
Adder
4.777
943121AE2-341 GEN
Solar/Wind Harmer
5.104
943591AF1-030 GEN
Solar/Wind Harmer
3.394
274682WAUKEGAN ;7U
Adder
7.839
970707AG2-453 GEN
Solar/Wind Harmer
9.937
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24802606KYGER 1HP
50/50
4.207
24802706KYGER 1LP
50/50
2.467
24803506KYGER 5LP
50/50
2.41
971985AH1-537 GEN
Solar/Wind Harmer
5.9
25196408WSDLE3
Adder
9.526
25196308WSDLE2
Adder
9.443
25196208WSDLE1
Adder
9.419
25196708WSDLE6
Adder
9.395
25196508WSDLE4
Adder
9.159
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
253406AD2-031_GEN
Solar/Wind Harmer
0.493
972163AH1-664 GEN
Solar/Wind Harmer
7.368
972165AH1-665 GEN
Solar/Wind Harmer
5.901
270263AC1-001 GEN
Solar/Wind Harmer
0.65
270340AC2-060 GEN
Solar/Wind Harmer
0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.169
253372AE2-315 SEC3
Adder
1.623
253372AE2-315 SEC3
Adder
1.623
25306009OHH W.
Adder
2.424
3429211JKCT 2G
Adder
8.956
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.299
971029AG2-637 GEN
Solar/Wind Harmer
7.492
241972AD1-140 GEN
Solar/Wind Harmer
0.535
270543AE2-219 C
Solar/Wind Harmer
3.362
247536S-71 GEN
Solar/Wind Harmer
0.185
964611AG1-324 GEN
Solar/Wind Harmer
1.732
971609AH1-304 GEN
Solar/Wind Harmer
0.694
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.79
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.463
963841AG1-237 GEN
Solar/Wind Harmer
1.583
945631AF1-228 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.02
963791AG1-232 GEN
Solar/Wind Harmer
4.554
971611AH1-305 GEN
Solar/Wind Harmer
2.005
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.132
276848AB2-070 GEN3
Solar/Wind Harmer
0.132
276849AB2-070 GEN2
Solar/Wind Harmer
0.132
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.273
943851AF1-053 GEN
Solar/Wind Harmer
0.882
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.418
270071AF1-092 GEN
Solar/Wind Harmer
6.13
970169AG2-114 GEN
Solar/Wind Harmer
3.185
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.104
926823AC1-168 GEN
Solar/Wind Harmer
0.529
970073AG2-061 GEN
Solar/Wind Harmer
1.026
276741O09 GEN1
Solar/Wind Harmer
0.108
970833AG2-524 GEN
Solar/Wind Harmer
3.368
970833AG2-524 GEN
Solar/Wind Harmer
2.246
274728ELWOOD EC;5P
Adder
7.204
274731ELWOOD EC;2P
Adder
7.204
274733ELWOOD EC;3P
Adder
7.204
274735ELWOOD EC;4P
Adder
7.204
972227AH1-698 GEN1
Adder
1.143
972228AH1-698 GEN2
Adder
1.623
960591AF2-350 GEN
Solar/Wind Harmer
3.054
274675JOLIET 29;7U
Adder
13.407
274675JOLIET 29;7U
Adder
12.928
274687WILL CNTY;4U
Adder
12.208
274687WILL CNTY;4U
Adder
12.208
274800UNIV PARK;3U
Adder
2.547
274801UNIV PARK;4U
Adder
2.547
971681AH1-341 GEN
Solar/Wind Harmer
4.906
274744AC1-111 GEN8
Adder
2.441
274746AC1-111 G10
Adder
2.441
972267AH1-718 GEN
Adder
1.819
972037AH1-567 GEN1
Adder
0.08
276861AD2-134 GEN
Solar/Wind Harmer
0.054
276863AD2-134 GEN
Solar/Wind Harmer
0.054
971171AH1-044 GEN
Solar/Wind Harmer
6.093
971675AH1-338 GEN
Solar/Wind Harmer
1.188
946321AF1-296 GEN
Solar/Wind Harmer
1.706
274827FISK ;RP
Adder
3.386
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971411AH1-196 GEN
Solar/Wind Harmer
4.564
945681AF1-233 GEN
Solar/Wind Harmer
12.627
270273AD2-016 GEN
Solar/Wind Harmer
0.667
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
25326309TAIT D
Adder
0.906
3429421JKCT 10G
Adder
6.589
3429241JKCT 3G
Adder
9.074
970773AG2-487 GEN
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.658
24728605AND G2
Adder
2.584
253333AC1-068 GEN
Solar/Wind Harmer
0.005
270005AE1-210 C O1
Solar/Wind Harmer
0.992
970825AG2-519 GEN
Solar/Wind Harmer
1.611
970091AG2-072 GEN
Adder
49.338
276903AD2-071 C
Solar/Wind Harmer
4.853
970653AG2-424 GEN
Solar/Wind Harmer
2.069
270594AE1-207 GEN
Solar/Wind Harmer
4.771
270032AE2-172
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.758
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.166
963741AG1-226 GEN
Solar/Wind Harmer
8.794
972203AH1-686 GEN
Adder
1.223
964901AG1-354 GEN
Solar/Wind Harmer
5.49
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276621W2-048 GEN
Solar/Wind Harmer
0.169
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.21
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.274
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.558
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.636
939401AE1-172 GEN
Solar/Wind Harmer
2.347
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.122
970569AG2-363 GEN
Solar/Wind Harmer
9.303
971997AH1-543 GEN
Solar/Wind Harmer
1.622
276882AE2-255 GEN
Solar/Wind Harmer
0.36
276805AD2-038 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.499
276708O09 GEN2
Solar/Wind Harmer
0.108
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.204
274674JOLIET 9 ;6U
Adder
6.739
274676JOLIET 29;8U
Adder
13.407
274802UNIV PARK;5U
Adder
2.546
274745AC1-111 GEN9
Adder
2.441
957471AF2-041 GEN
Solar/Wind Harmer
9.139
959081AF2-199 GEN
Solar/Wind Harmer
3.046
971067AG2-660 GEN
Solar/Wind Harmer
1.015
274872LEEDK;1U
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.061
274766LEE CO EC;7U
Adder
4.013
962781AG1-127 GEN
Solar/Wind Harmer
2.898
274682WAUKEGAN ;7U
Adder
7.839
274828WAUKEGAN ;BP
Adder
4.817
274822ROCKFORD ;11
Adder
2.437
970819AG2-516 GEN
Solar/Wind Harmer
3.649
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.501
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
TVALTFEXP_TVA->PJM
CLTF
2.665
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.274
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.431
MECLTFEXP_MEC->PJM
CLTF
7.137
SIGELTFEXP_SIGE->PJM
CLTF
0.33
NYPJM->LTFIMP_NY
CLTF
1.597
LGEELTFEXP_LGEE->PJM
CLTF
5.305
WECLTFEXP_WEC->PJM
CLTF
1.662
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.865

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.31 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1652.5
MW Contribution:
2.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
25194408D.CRK1
Adder
7.451
25194508D.CRK3
Adder
1.393
252509AD1-136 GEN
Solar/Wind Harmer
0.247
24728805RICHG1
Adder
2.815
24728905RICHG2
Adder
2.815
926881AC1-175 GEN
Solar/Wind Harmer
4.028
25183208HLCRTG
Solar/Wind Harmer
4.167
270383AD1-128 GEN
Solar/Wind Harmer
4.197
970883AG2-550 GEN
Solar/Wind Harmer
6.559
970885AG2-551 GEN
Solar/Wind Harmer
1.525
24725505WLD G2 C
Solar/Wind Harmer
2.554
24699105WLD G1 C
Solar/Wind Harmer
2.524
247621Y3-024
Adder
0.151
964611AG1-324 GEN
Solar/Wind Harmer
0.327
270201AC2-176 GEN
Solar/Wind Harmer
3.18
270031AE2-169
Solar/Wind Harmer
4.953
270599AE1-208 GEN
Solar/Wind Harmer
4.953
970291AG2-192 GEN
Solar/Wind Harmer
0.79
970291AG2-192 GEN
Solar/Wind Harmer
0.254
253349AC2-067 GEN
Solar/Wind Harmer
1.23
253400AC2-068 GEN
Solar/Wind Harmer
0.495
945391AF1-204 GEN
Solar/Wind Harmer
8.204
964571AG1-320 GEN
Solar/Wind Harmer
4.812
253370AE2-315 SEC1
Adder
1.168
25322209TAIT E
Adder
5.648
25322209TAIT E
Adder
5.521
944541AF1-119 GEN
Solar/Wind Harmer
2.383
960971AF2-388 GEN
Solar/Wind Harmer
6.222
970241AG2-163 GEN
Solar/Wind Harmer
14.001
25326109MON D
Adder
0.735
24387305FR-4G C
Solar/Wind Harmer
2.757
966841AG1-555 GEN
Solar/Wind Harmer
1.362
942221AE2-234 GEN
Solar/Wind Harmer
1.865
270180AB1-006 GEN1
Solar/Wind Harmer
3.807
24697605MDL-3G C
Solar/Wind Harmer
1.951
24755605MDL-5G
Solar/Wind Harmer
1.276
24697905MDL-4G C
Solar/Wind Harmer
1.214
270181AB1-006 GEN2
Solar/Wind Harmer
0.378
945421AF1-207 GEN
Solar/Wind Harmer
7.341
957841AF2-078 GEN
Solar/Wind Harmer
3.16
972043AH1-570 GEN
Solar/Wind Harmer
1.299
972045AH1-571 GEN
Solar/Wind Harmer
1.039
971125AH1-004 GEN
Solar/Wind Harmer
2.039
970107AG2-081 GEN
Solar/Wind Harmer
1.529
276916AD2-100_GEN
Solar/Wind Harmer
10.576
276911AD2-131_GEN
Solar/Wind Harmer
2.137
276615X2-022 GEN
Solar/Wind Harmer
0.977
276838X2-022 GEN2
Solar/Wind Harmer
0.116
274880W4-005 GEN4
Solar/Wind Harmer
1.506
276174W4-005 GEN2
Solar/Wind Harmer
1.506
960611AF2-352 GEN
Solar/Wind Harmer
1.127
270535AF1-215 GEN1
Solar/Wind Harmer
2.188
270536AF1-215 GEN2
Solar/Wind Harmer
2.188
942111AE2-223 GEN
Solar/Wind Harmer
3.947
942891AE2-308 GEN
Solar/Wind Harmer
4.665
276645AC1-214 GEN1
Solar/Wind Harmer
0.614
274674JOLIET 9 ;6U
Adder
6.933
274805UNIV PK N;1U
Adder
2.252
274808UNIV PK N;4U
Adder
2.237
274696ROCKY RD ;4P
Adder
5.109
274695ROCKY RD ;2P
Adder
4.991
274693ROCKY RD ;1P
Adder
4.942
274697ROCKY RD ;3P
Adder
1.356
274770LINCOLN ;1U
Adder
3.782
274771LINCOLN ;2U
Adder
3.782
274683WAUKEGAN ;8U
Adder
9.438
274683WAUKEGAN ;8U
Adder
7.956
274764LEE CO EC;5U
Adder
4.17
274765LEE CO EC;6U
Adder
0.868
927014AC1-188 GEN
Solar/Wind Helper
0.884
25196008MFTGT1
Adder
1.366
252524AE2-267 GEN
Solar/Wind Harmer
1.575
25196608WSDLE5
Adder
8.573
25194608D.CRK4
Adder
1.62
252507AC2-088 GEN
Solar/Wind Harmer
1.729
252519AF1-045_GEN
Solar/Wind Harmer
3.15
24379505HDWTR1G C
Solar/Wind Harmer
5.707
270240V3-007_GEN2
Solar/Wind Harmer
4.465
24728705AND G3
Adder
5.457
24728505AND G1
Adder
2.609
270004AE1-209 GEN
Solar/Wind Harmer
3.603
970825AG2-519 GEN
Solar/Wind Harmer
3.655
946031AF1-268 GEN
Solar/Wind Harmer
5.382
962031AG1-047 GEN
Solar/Wind Harmer
1.871
957741AF2-068 GEN
Solar/Wind Harmer
9.281
965461AG1-414 GEN
Solar/Wind Harmer
1.378
970289AG2-191 GEN
Solar/Wind Harmer
0.466
247642Z2-115 C
Solar/Wind Harmer
0.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.268
970193AG2-126 GEN
Solar/Wind Harmer
8.831
253303V4-073 C
Solar/Wind Harmer
0.068
253370AE2-315 SEC1
Adder
1.168
253371AE2-315 SEC2
Adder
1.104
960071AF2-298 GEN
Solar/Wind Harmer
0.881
970455AG2-298 GEN
Solar/Wind Harmer
2.002
24386205FR-12G C
Solar/Wind Harmer
2.326
970653AG2-424 GEN
Solar/Wind Harmer
0.377
24690905MDL-1G C
Solar/Wind Harmer
4.249
970781AG2-491 GEN
Solar/Wind Harmer
5.293
944531AF1-118 GEN
Solar/Wind Harmer
18.147
942481AE2-261 GEN
Solar/Wind Harmer
15.006
957381AF2-032 GEN
Solar/Wind Harmer
1.003
276785W4-005 GEN1
Solar/Wind Harmer
1.506
971993AH1-541 GEN
Solar/Wind Harmer
4.6
964401AG1-302 GEN
Solar/Wind Harmer
4.474
965091AG1-374 GEN
Solar/Wind Harmer
14.538
959611AF2-252 GEN
Solar/Wind Harmer
1.127
339206AE1-143 GEN
Solar/Wind Harmer
1.012
3429391JKCT 9G
Adder
3.875
274851PROVIDENC;RU
Solar/Wind Harmer
1.306
274849CRESCENT ;1U
Solar/Wind Harmer
0.848
276782AC1-033 GEN
Solar/Wind Harmer
1.823
274878BISHOP HL;2U
Solar/Wind Harmer
1.543
274729ELWOOD EC;1P
Adder
7.412
274730ELWOOD EC;6P
Adder
7.412
274734ELWOOD EC;8P
Adder
7.412
274736ELWOOD EC;9P
Adder
7.412
972259AH1-714 GEN
Adder
8.585
972038AH1-567 GEN2
Adder
0.164
274676JOLIET 29;8U
Adder
13.298
274803UNIV PARK;6U
Adder
2.62
274826FISK ;BP
Adder
4.915
274814UNIV PK N;0U
Adder
2.267
274807UNIV PK N;3U
Adder
2.262
274811UNIV PK N;7U
Adder
2.247
274772LINCOLN ;3U
Adder
3.782
274682WAUKEGAN ;7U
Adder
8.051
274752CRETE EC ;2U
Adder
3.69
274753CRETE EC ;3U
Adder
3.69
274724RIVER EC ;11
Adder
7.922
957541AF2-048 GEN
Solar/Wind Helper
0.884
270330AC1-082 GEN2
Solar/Wind Helper
0.094
270329AC1-082 GEN1
Solar/Wind Helper
0.094
970571AG2-364 GEN
Solar/Wind Harmer
7.481
25196008MFTGT1
Adder
1.41
25194608D.CRK4
Adder
1.62
252510AF1-249 C
Solar/Wind Harmer
0.398
252516AE2-318_GEN
Solar/Wind Harmer
8.654
25196808ZIMRHP
Adder
62.026
270222AC2-111 GEN
Solar/Wind Harmer
3.535
944031AF1-071 GEN
Solar/Wind Harmer
0.795
970091AG2-072 GEN
Adder
56.358
942081AE2-220 GEN
Solar/Wind Harmer
4.616
270209AC1-174_GEN
Solar/Wind Harmer
2.937
270437AC2-090 C
Solar/Wind Harmer
4.028
270239V3-007_GEN1
Solar/Wind Harmer
1.242
24728605AND G2
Adder
2.609
270005AE1-210 C O1
Solar/Wind Harmer
3.603
970825AG2-519 GEN
Solar/Wind Harmer
1.361
276903AD2-071 C
Solar/Wind Harmer
6.32
270594AE1-207 GEN
Solar/Wind Harmer
8.405
270032AE2-172
Solar/Wind Harmer
2.878
945371AF1-202 GEN
Solar/Wind Harmer
4.219
253370AE2-315 SEC1
Adder
1.168
253371AE2-315 SEC2
Adder
1.104
958861AF2-177 GEN
Solar/Wind Harmer
6.355
25326309TAIT D
Adder
0.634
965651AG1-433 GEN
Solar/Wind Harmer
3.111
270024AE2-089 GEN
Solar/Wind Harmer
2.629
963741AG1-226 GEN
Solar/Wind Harmer
25.203
339221AD2-048_GEN
Solar/Wind Harmer
0.859
24385905FR-11G C
Solar/Wind Harmer
4.511
24386605FR-22G C
Solar/Wind Harmer
2.334
970653AG2-424 GEN
Solar/Wind Harmer
2.607
24791305MDL-5G
Solar/Wind Harmer
1.276
940581AE2-045 GEN
Solar/Wind Harmer
5.184
971605AH1-302 GEN
Solar/Wind Harmer
4.432
965911AG1-460 GEN
Solar/Wind Harmer
0.7
943111AE2-339 GEN
Solar/Wind Harmer
0.443
276621W2-048 GEN
Solar/Wind Harmer
3.11
276686W4-005 GEN3
Solar/Wind Harmer
1.506
964861AG1-349 GEN
Solar/Wind Harmer
3.886
971917AH1-482 GEN
Solar/Wind Harmer
4.484
958381AF2-132 GEN
Solar/Wind Harmer
4.474
270055AF2-134 C O1
Solar/Wind Harmer
1.459
276655WTG1_EQ
Solar/Wind Harmer
4.203
276656WTG2_EQ
Solar/Wind Harmer
0.556
939741AE1-205 GEN
Solar/Wind Harmer
9.631
339211AE2-254 GEN
Solar/Wind Harmer
0.727
970373AG2-245 GEN
Solar/Wind Harmer
9.915
339241AF1-083 GEN
Solar/Wind Harmer
0.777
3429421JKCT 10G
Adder
3.875
939401AE1-172 GEN
Solar/Wind Harmer
6.459
274848CAMPGROVE;RU
Solar/Wind Harmer
2.964
276646AC1-214 GEN2
Solar/Wind Harmer
0.614
3429241JKCT 3G
Adder
5.431
274732ELWOOD EC;7P
Adder
7.412
274674JOLIET 9 ;6U
Adder
6.933
274676JOLIET 29;8U
Adder
13.79
274802UNIV PARK;5U
Adder
2.62
274745AC1-111 GEN9
Adder
2.509
274812UNIV PK N;8U
Adder
2.247
274773LINCOLN ;4U
Adder
3.782
274774LINCOLN ;5U
Adder
3.782
274682WAUKEGAN ;7U
Adder
8.051
274828WAUKEGAN ;BP
Adder
4.947
25196108MFTGT2
Adder
1.554
25196108MFTGT2
Adder
1.443
25196408WSDLE3
Adder
8.826
25196308WSDLE2
Adder
8.749
25196208WSDLE1
Adder
8.727
25196708WSDLE6
Adder
8.705
25196508WSDLE4
Adder
8.486
971985AH1-537 GEN
Solar/Wind Harmer
17.68
270356AE2-297 GEN
Solar/Wind Harmer
3.518
971029AG2-637 GEN
Solar/Wind Harmer
10.113
270543AE2-219 C
Solar/Wind Harmer
6.559
270444AC2-157 GEN1
Solar/Wind Harmer
3.564
270445AC2-157 GEN2
Solar/Wind Harmer
3.564
247536S-71 GEN
Solar/Wind Harmer
2.584
964611AG1-324 GEN
Solar/Wind Harmer
2.438
961761AG1-017 GEN
Solar/Wind Harmer
0.265
970289AG2-191 GEN
Solar/Wind Harmer
1.154
945581AF1-223 GEN
Solar/Wind Harmer
2.743
339216AC1-074 GEN
Solar/Wind Harmer
0.988
25306009OHH W.
Adder
1.692
253372AE2-315 SEC3
Adder
1.104
253372AE2-315 SEC3
Adder
1.104
958711AF2-162 GEN
Solar/Wind Harmer
0.576
963841AG1-237 GEN
Solar/Wind Harmer
6.03
24386405FR-21G C
Solar/Wind Harmer
2.334
24387005FR-3G C
Solar/Wind Harmer
2.147
24729505KEY G4
Adder
3.451
946581AF1-322 GEN
Solar/Wind Harmer
5.415
24691005MDL-2G C
Solar/Wind Harmer
1.957
944221AF1-090 GEN
Solar/Wind Harmer
5.569
959141AF2-205 GEN
Solar/Wind Harmer
3.042
958391AF2-133 GEN
Solar/Wind Harmer
4.525
276763AC1-053 GEN1
Solar/Wind Harmer
1.968
276764AC1-053 GEN2
Solar/Wind Harmer
1.968
276668AB2-070 GEN1
Solar/Wind Harmer
1.102
276848AB2-070 GEN3
Solar/Wind Harmer
1.102
276849AB2-070 GEN2
Solar/Wind Harmer
1.102
274853TWINGROVE;U1
Solar/Wind Harmer
3.491
274854TWINGROVE;U2
Solar/Wind Harmer
3.418
276726Z2-087_GEN
Solar/Wind Harmer
3.807
959341AF2-225 GEN
Solar/Wind Harmer
7.223
970169AG2-114 GEN
Solar/Wind Harmer
4.707
963791AG1-232 GEN
Solar/Wind Harmer
6.325
274863CRW1-WTG
Solar/Wind Harmer
2.609
274864CRW2-WTG
Solar/Wind Harmer
2.609
270071AF1-092 GEN
Solar/Wind Harmer
6.933
3429211JKCT 2G
Adder
5.361
926823AC1-168 GEN
Solar/Wind Harmer
1.969
274877BISHOP HL;1U
Solar/Wind Harmer
1.543
274728ELWOOD EC;5P
Adder
7.412
274731ELWOOD EC;2P
Adder
7.412
274733ELWOOD EC;3P
Adder
7.412
274735ELWOOD EC;4P
Adder
7.412
972228AH1-698 GEN2
Adder
1.67
972227AH1-698 GEN1
Adder
1.176
274800UNIV PARK;3U
Adder
2.621
274801UNIV PARK;4U
Adder
2.621
274675JOLIET 29;7U
Adder
13.79
274675JOLIET 29;7U
Adder
13.298
972037AH1-567 GEN1
Adder
0.082
274687WILL CNTY;4U
Adder
12.558
274687WILL CNTY;4U
Adder
12.558
274827FISK ;RP
Adder
3.484
274744AC1-111 GEN8
Adder
2.509
274746AC1-111 G10
Adder
2.509
274775LINCOLN ;6U
Adder
3.782
274776LINCOLN ;7U
Adder
3.782
274777LINCOLN ;8U
Adder
3.782
972267AH1-718 GEN
Adder
1.863
270263AC1-001 GEN
Solar/Wind Helper
0.628
270291AC1-194 GEN
Solar/Wind Helper
0.524
274751CRETE EC ;1U
Adder
3.69
274754CRETE EC ;4U
Adder
3.69
274723RIVER EC ;12
Adder
8.017
270273AD2-016 GEN
Solar/Wind Helper
1.464
270331AC1-082 GEN3
Solar/Wind Helper
0.094
960001AF2-291 GEN
Solar/Wind Helper
0.555
970569AG2-363 GEN
Solar/Wind Harmer
11.221
LAGNLTFEXP_LAGN->PJM
CLTF
5.26
TVALTFEXP_TVA->PJM
CLTF
2.352
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.345
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.476
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.36
MECLTFEXP_MEC->PJM
CLTF
7.227
SIGELTFEXP_SIGE->PJM
CLTF
0.329
NYPJM->LTFIMP_NY
CLTF
1.096
LGEELTFEXP_LGEE->PJM
CLTF
5.198
WECLTFEXP_WEC->PJM
CLTF
1.703
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.674
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.922

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1585.6
MW Contribution:
3.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
25194408D.CRK1
Adder
7.483
25194508D.CRK3
Adder
1.399
252509AD1-136 GEN
Solar/Wind Harmer
0.248
24728805RICHG1
Adder
2.831
24728905RICHG2
Adder
2.831
926881AC1-175 GEN
Solar/Wind Harmer
4.052
25183208HLCRTG
Solar/Wind Harmer
4.193
270383AD1-128 GEN
Solar/Wind Harmer
4.223
970883AG2-550 GEN
Solar/Wind Harmer
6.601
970885AG2-551 GEN
Solar/Wind Harmer
1.535
24725505WLD G2 C
Solar/Wind Harmer
2.571
24699105WLD G1 C
Solar/Wind Harmer
2.541
247621Y3-024
Adder
0.152
964611AG1-324 GEN
Solar/Wind Harmer
0.329
270201AC2-176 GEN
Solar/Wind Harmer
3.202
270031AE2-169
Solar/Wind Harmer
4.988
270599AE1-208 GEN
Solar/Wind Harmer
4.988
970291AG2-192 GEN
Solar/Wind Harmer
0.795
970291AG2-192 GEN
Solar/Wind Harmer
0.256
253349AC2-067 GEN
Solar/Wind Harmer
1.239
253400AC2-068 GEN
Solar/Wind Harmer
0.498
945391AF1-204 GEN
Solar/Wind Harmer
8.264
964571AG1-320 GEN
Solar/Wind Harmer
4.847
253370AE2-315 SEC1
Adder
1.176
25322209TAIT E
Adder
5.689
25322209TAIT E
Adder
5.561
944541AF1-119 GEN
Solar/Wind Harmer
2.401
960971AF2-388 GEN
Solar/Wind Harmer
6.268
970241AG2-163 GEN
Solar/Wind Harmer
14.108
25326109MON D
Adder
0.741
24387305FR-4G C
Solar/Wind Harmer
2.778
966841AG1-555 GEN
Solar/Wind Harmer
1.373
942221AE2-234 GEN
Solar/Wind Harmer
1.88
270180AB1-006 GEN1
Solar/Wind Harmer
3.837
24697605MDL-3G C
Solar/Wind Harmer
1.967
24755605MDL-5G
Solar/Wind Harmer
1.286
24697905MDL-4G C
Solar/Wind Harmer
1.224
270181AB1-006 GEN2
Solar/Wind Harmer
0.382
945421AF1-207 GEN
Solar/Wind Harmer
7.401
957841AF2-078 GEN
Solar/Wind Harmer
3.186
972043AH1-570 GEN
Solar/Wind Harmer
1.31
972045AH1-571 GEN
Solar/Wind Harmer
1.048
971125AH1-004 GEN
Solar/Wind Harmer
2.056
970107AG2-081 GEN
Solar/Wind Harmer
1.542
276916AD2-100_GEN
Solar/Wind Harmer
10.665
276911AD2-131_GEN
Solar/Wind Harmer
2.155
276615X2-022 GEN
Solar/Wind Harmer
0.985
276838X2-022 GEN2
Solar/Wind Harmer
0.117
274880W4-005 GEN4
Solar/Wind Harmer
1.518
276174W4-005 GEN2
Solar/Wind Harmer
1.518
960611AF2-352 GEN
Solar/Wind Harmer
1.137
270535AF1-215 GEN1
Solar/Wind Harmer
2.208
270536AF1-215 GEN2
Solar/Wind Harmer
2.208
942111AE2-223 GEN
Solar/Wind Harmer
3.982
942891AE2-308 GEN
Solar/Wind Harmer
4.707
276645AC1-214 GEN1
Solar/Wind Harmer
0.62
274674JOLIET 9 ;6U
Adder
6.998
274805UNIV PK N;1U
Adder
2.273
274808UNIV PK N;4U
Adder
2.258
274696ROCKY RD ;4P
Adder
5.158
274695ROCKY RD ;2P
Adder
5.039
274693ROCKY RD ;1P
Adder
4.989
274697ROCKY RD ;3P
Adder
1.369
274770LINCOLN ;1U
Adder
3.818
274771LINCOLN ;2U
Adder
3.818
274683WAUKEGAN ;8U
Adder
9.528
274683WAUKEGAN ;8U
Adder
8.032
274764LEE CO EC;5U
Adder
4.21
274765LEE CO EC;6U
Adder
0.877
927014AC1-188 GEN
Solar/Wind Helper
0.878
25196008MFTGT1
Adder
1.371
252524AE2-267 GEN
Solar/Wind Harmer
1.582
25196608WSDLE5
Adder
8.61
25194608D.CRK4
Adder
1.627
252507AC2-088 GEN
Solar/Wind Harmer
1.737
252519AF1-045_GEN
Solar/Wind Harmer
3.165
24379505HDWTR1G C
Solar/Wind Harmer
5.74
270240V3-007_GEN2
Solar/Wind Harmer
4.491
24728705AND G3
Adder
5.491
24728505AND G1
Adder
2.625
270004AE1-209 GEN
Solar/Wind Harmer
3.626
970825AG2-519 GEN
Solar/Wind Harmer
3.679
946031AF1-268 GEN
Solar/Wind Harmer
5.417
962031AG1-047 GEN
Solar/Wind Harmer
1.884
957741AF2-068 GEN
Solar/Wind Harmer
9.345
965461AG1-414 GEN
Solar/Wind Harmer
1.387
970289AG2-191 GEN
Solar/Wind Harmer
0.47
247642Z2-115 C
Solar/Wind Harmer
0.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.269
970193AG2-126 GEN
Solar/Wind Harmer
8.895
253303V4-073 C
Solar/Wind Harmer
0.068
253370AE2-315 SEC1
Adder
1.176
253371AE2-315 SEC2
Adder
1.112
960071AF2-298 GEN
Solar/Wind Harmer
0.887
970455AG2-298 GEN
Solar/Wind Harmer
2.017
24386205FR-12G C
Solar/Wind Harmer
2.344
970653AG2-424 GEN
Solar/Wind Harmer
0.38
24690905MDL-1G C
Solar/Wind Harmer
4.283
970781AG2-491 GEN
Solar/Wind Harmer
5.335
944531AF1-118 GEN
Solar/Wind Harmer
18.296
942481AE2-261 GEN
Solar/Wind Harmer
15.134
957381AF2-032 GEN
Solar/Wind Harmer
1.011
276785W4-005 GEN1
Solar/Wind Harmer
1.518
971993AH1-541 GEN
Solar/Wind Harmer
4.64
964401AG1-302 GEN
Solar/Wind Harmer
4.513
965091AG1-374 GEN
Solar/Wind Harmer
14.666
959611AF2-252 GEN
Solar/Wind Harmer
1.137
339206AE1-143 GEN
Solar/Wind Harmer
1.021
3429391JKCT 9G
Adder
3.91
274851PROVIDENC;RU
Solar/Wind Harmer
1.318
274849CRESCENT ;1U
Solar/Wind Harmer
0.856
276782AC1-033 GEN
Solar/Wind Harmer
1.84
274878BISHOP HL;2U
Solar/Wind Harmer
1.557
274729ELWOOD EC;1P
Adder
7.482
274730ELWOOD EC;6P
Adder
7.482
274734ELWOOD EC;8P
Adder
7.482
274736ELWOOD EC;9P
Adder
7.482
972259AH1-714 GEN
Adder
8.666
972038AH1-567 GEN2
Adder
0.166
274676JOLIET 29;8U
Adder
13.424
274803UNIV PARK;6U
Adder
2.645
274826FISK ;BP
Adder
4.962
274814UNIV PK N;0U
Adder
2.288
274807UNIV PK N;3U
Adder
2.283
274811UNIV PK N;7U
Adder
2.268
274772LINCOLN ;3U
Adder
3.818
274682WAUKEGAN ;7U
Adder
8.127
274752CRETE EC ;2U
Adder
3.725
274753CRETE EC ;3U
Adder
3.725
274724RIVER EC ;11
Adder
7.998
957541AF2-048 GEN
Solar/Wind Helper
0.878
270330AC1-082 GEN2
Solar/Wind Helper
0.093
270329AC1-082 GEN1
Solar/Wind Helper
0.093
970571AG2-364 GEN
Solar/Wind Harmer
7.551
25196008MFTGT1
Adder
1.416
25194608D.CRK4
Adder
1.627
252510AF1-249 C
Solar/Wind Harmer
0.4
252516AE2-318_GEN
Solar/Wind Harmer
8.697
25196808ZIMRHP
Adder
62.349
270222AC2-111 GEN
Solar/Wind Harmer
3.554
944031AF1-071 GEN
Solar/Wind Harmer
0.8
970091AG2-072 GEN
Adder
56.685
942081AE2-220 GEN
Solar/Wind Harmer
4.643
270209AC1-174_GEN
Solar/Wind Harmer
2.954
270437AC2-090 C
Solar/Wind Harmer
4.052
270239V3-007_GEN1
Solar/Wind Harmer
1.249
24728605AND G2
Adder
2.625
270005AE1-210 C O1
Solar/Wind Harmer
3.626
970825AG2-519 GEN
Solar/Wind Harmer
1.37
276903AD2-071 C
Solar/Wind Harmer
6.363
270594AE1-207 GEN
Solar/Wind Harmer
8.462
270032AE2-172
Solar/Wind Harmer
2.898
945371AF1-202 GEN
Solar/Wind Harmer
4.249
253370AE2-315 SEC1
Adder
1.176
253371AE2-315 SEC2
Adder
1.112
958861AF2-177 GEN
Solar/Wind Harmer
6.402
25326309TAIT D
Adder
0.639
965651AG1-433 GEN
Solar/Wind Harmer
3.134
270024AE2-089 GEN
Solar/Wind Harmer
2.649
963741AG1-226 GEN
Solar/Wind Harmer
25.394
339221AD2-048_GEN
Solar/Wind Harmer
0.866
24385905FR-11G C
Solar/Wind Harmer
4.546
24386605FR-22G C
Solar/Wind Harmer
2.352
970653AG2-424 GEN
Solar/Wind Harmer
2.628
24791305MDL-5G
Solar/Wind Harmer
1.286
940581AE2-045 GEN
Solar/Wind Harmer
5.227
971605AH1-302 GEN
Solar/Wind Harmer
4.47
965911AG1-460 GEN
Solar/Wind Harmer
0.706
943111AE2-339 GEN
Solar/Wind Harmer
0.446
276621W2-048 GEN
Solar/Wind Harmer
3.137
276686W4-005 GEN3
Solar/Wind Harmer
1.518
964861AG1-349 GEN
Solar/Wind Harmer
3.92
971917AH1-482 GEN
Solar/Wind Harmer
4.523
958381AF2-132 GEN
Solar/Wind Harmer
4.513
270055AF2-134 C O1
Solar/Wind Harmer
1.472
276655WTG1_EQ
Solar/Wind Harmer
4.24
276656WTG2_EQ
Solar/Wind Harmer
0.561
939741AE1-205 GEN
Solar/Wind Harmer
9.716
339211AE2-254 GEN
Solar/Wind Harmer
0.733
970373AG2-245 GEN
Solar/Wind Harmer
10.005
339241AF1-083 GEN
Solar/Wind Harmer
0.784
3429421JKCT 10G
Adder
3.91
939401AE1-172 GEN
Solar/Wind Harmer
6.518
274848CAMPGROVE;RU
Solar/Wind Harmer
2.991
276646AC1-214 GEN2
Solar/Wind Harmer
0.62
3429241JKCT 3G
Adder
5.482
274732ELWOOD EC;7P
Adder
7.482
274674JOLIET 9 ;6U
Adder
6.998
274676JOLIET 29;8U
Adder
13.921
274802UNIV PARK;5U
Adder
2.645
274745AC1-111 GEN9
Adder
2.533
274812UNIV PK N;8U
Adder
2.268
274773LINCOLN ;4U
Adder
3.818
274774LINCOLN ;5U
Adder
3.818
274682WAUKEGAN ;7U
Adder
8.127
274828WAUKEGAN ;BP
Adder
4.994
274751CRETE EC ;1U
Adder
3.725
274754CRETE EC ;4U
Adder
3.725
274723RIVER EC ;12
Adder
8.094
270273AD2-016 GEN
Solar/Wind Helper
1.452
270331AC1-082 GEN3
Solar/Wind Helper
0.093
970569AG2-363 GEN
Solar/Wind Harmer
11.326
25196108MFTGT2
Adder
1.561
25196108MFTGT2
Adder
1.449
25196408WSDLE3
Adder
8.863
25196308WSDLE2
Adder
8.786
25196208WSDLE1
Adder
8.764
25196708WSDLE6
Adder
8.742
25196508WSDLE4
Adder
8.522
971985AH1-537 GEN
Solar/Wind Harmer
17.756
270356AE2-297 GEN
Solar/Wind Harmer
3.537
971029AG2-637 GEN
Solar/Wind Harmer
10.176
270543AE2-219 C
Solar/Wind Harmer
6.601
270444AC2-157 GEN1
Solar/Wind Harmer
3.588
270445AC2-157 GEN2
Solar/Wind Harmer
3.588
247536S-71 GEN
Solar/Wind Harmer
2.601
964611AG1-324 GEN
Solar/Wind Harmer
2.454
961761AG1-017 GEN
Solar/Wind Harmer
0.267
970289AG2-191 GEN
Solar/Wind Harmer
1.163
945581AF1-223 GEN
Solar/Wind Harmer
2.762
339216AC1-074 GEN
Solar/Wind Harmer
0.995
25306009OHH W.
Adder
1.704
253372AE2-315 SEC3
Adder
1.112
253372AE2-315 SEC3
Adder
1.112
958711AF2-162 GEN
Solar/Wind Harmer
0.58
963841AG1-237 GEN
Solar/Wind Harmer
6.076
24386405FR-21G C
Solar/Wind Harmer
2.352
24387005FR-3G C
Solar/Wind Harmer
2.164
24729505KEY G4
Adder
3.478
946581AF1-322 GEN
Solar/Wind Harmer
5.459
24691005MDL-2G C
Solar/Wind Harmer
1.973
944221AF1-090 GEN
Solar/Wind Harmer
5.616
959141AF2-205 GEN
Solar/Wind Harmer
3.067
958391AF2-133 GEN
Solar/Wind Harmer
4.563
276763AC1-053 GEN1
Solar/Wind Harmer
1.985
276764AC1-053 GEN2
Solar/Wind Harmer
1.985
276668AB2-070 GEN1
Solar/Wind Harmer
1.111
276848AB2-070 GEN3
Solar/Wind Harmer
1.111
276849AB2-070 GEN2
Solar/Wind Harmer
1.111
274853TWINGROVE;U1
Solar/Wind Harmer
3.522
274854TWINGROVE;U2
Solar/Wind Harmer
3.448
276726Z2-087_GEN
Solar/Wind Harmer
3.841
959341AF2-225 GEN
Solar/Wind Harmer
7.287
970169AG2-114 GEN
Solar/Wind Harmer
4.75
963791AG1-232 GEN
Solar/Wind Harmer
6.383
274863CRW1-WTG
Solar/Wind Harmer
2.632
274864CRW2-WTG
Solar/Wind Harmer
2.632
270071AF1-092 GEN
Solar/Wind Harmer
6.997
3429211JKCT 2G
Adder
5.411
926823AC1-168 GEN
Solar/Wind Harmer
1.987
274877BISHOP HL;1U
Solar/Wind Harmer
1.557
274731ELWOOD EC;2P
Adder
7.482
274733ELWOOD EC;3P
Adder
7.482
274735ELWOOD EC;4P
Adder
7.482
972228AH1-698 GEN2
Adder
1.686
972227AH1-698 GEN1
Adder
1.187
274728ELWOOD EC;5P
Adder
7.482
274800UNIV PARK;3U
Adder
2.646
274801UNIV PARK;4U
Adder
2.646
274675JOLIET 29;7U
Adder
13.921
274675JOLIET 29;7U
Adder
13.424
274687WILL CNTY;4U
Adder
12.677
274687WILL CNTY;4U
Adder
12.677
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.517
274744AC1-111 GEN8
Adder
2.533
274746AC1-111 G10
Adder
2.533
274775LINCOLN ;6U
Adder
3.818
274776LINCOLN ;7U
Adder
3.818
274777LINCOLN ;8U
Adder
3.818
972267AH1-718 GEN
Adder
1.88
270263AC1-001 GEN
Solar/Wind Helper
0.624
270291AC1-194 GEN
Solar/Wind Helper
0.52
LAGNLTFEXP_LAGN->PJM
CLTF
5.346
TVALTFEXP_TVA->PJM
CLTF
2.395
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.328
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.099
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.523
MECLTFEXP_MEC->PJM
CLTF
7.298
SIGELTFEXP_SIGE->PJM
CLTF
0.331
NYPJM->LTFIMP_NY
CLTF
1.069
LGEELTFEXP_LGEE->PJM
CLTF
5.227
WECLTFEXP_WEC->PJM
CLTF
1.719
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.646
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
AH1-155LTFEXP_AH1-155->PJM
LTF
0.17
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.498

Details for 4MARION CO-4LEBANON 138.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
4MARION CO-4LEBANON 138.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.8 %
Rating:220.0 MVA
Rating Type:B
MVA to Mitigate:234.95
MW Contribution:
3.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339236AF1-050_GEN
Solar/Wind Harmer
2.932
339231AF1-038_GEN
Solar/Wind Harmer
1.786
971485AH1-239 GEN
Solar/Wind Harmer
5.85
966021AG1-471 GEN
Solar/Wind Harmer
3.94
964781AG1-341 GEN
Solar/Wind Harmer
7.499
3429031COOPER2 G
50/50
1.767
972273AH1-721 GEN
50/50
108.965
339206AE1-143 GEN
Solar/Wind Harmer
8.636
339255AE2-071 GEN
Solar/Wind Harmer
0.855
339250AF1-203 GEN
Solar/Wind Harmer
0.44
970653AG2-424 GEN
Solar/Wind Harmer
0.404
339241AF1-083 GEN
Solar/Wind Harmer
4.334
964901AG1-354 GEN
Solar/Wind Harmer
22.606
970653AG2-424 GEN
Solar/Wind Harmer
2.794
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.292
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.886
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.121
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.251
MECLTFEXP_MEC->PJM
CLTF
0.173
NYPJM->LTFIMP_NY
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.988

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:250.49 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:693.86
MW Contribution:
3.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.113
966021AG1-471 GEN
Solar/Wind Harmer
9.329
971485AH1-239 GEN
Solar/Wind Harmer
13.192
339231AF1-038_GEN
Solar/Wind Harmer
2.843
339236AF1-050_GEN
Solar/Wind Harmer
1.903
964781AG1-341 GEN
Solar/Wind Harmer
10.425
3429031COOPER2 G
50/50
6.798
972273AH1-721 GEN
50/50
418.865
339206AE1-143 GEN
Solar/Wind Harmer
2.773
339255AE2-071 GEN
Solar/Wind Harmer
1.202
339250AF1-203 GEN
Solar/Wind Harmer
0.619
970653AG2-424 GEN
Solar/Wind Harmer
0.394
339241AF1-083 GEN
Solar/Wind Harmer
1.907
964901AG1-354 GEN
Solar/Wind Harmer
15.617
970653AG2-424 GEN
Solar/Wind Harmer
2.723
950011AG9-010
External Queue
11.361714363098145
LAGNLTFEXP_LAGN->PJM
CLTF
1.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.646
TVALTFEXP_TVA->PJM
CLTF
1.295
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.562
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.923
MECLTFEXP_MEC->PJM
CLTF
0.666
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.013

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:250.48 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:693.83
MW Contribution:
3.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.113
966021AG1-471 GEN
Solar/Wind Harmer
9.329
971485AH1-239 GEN
Solar/Wind Harmer
13.192
339231AF1-038_GEN
Solar/Wind Harmer
2.843
339236AF1-050_GEN
Solar/Wind Harmer
1.903
964781AG1-341 GEN
Solar/Wind Harmer
10.425
3429031COOPER2 G
50/50
6.798
972273AH1-721 GEN
50/50
418.865
339206AE1-143 GEN
Solar/Wind Harmer
2.773
339255AE2-071 GEN
Solar/Wind Harmer
1.202
339250AF1-203 GEN
Solar/Wind Harmer
0.619
970653AG2-424 GEN
Solar/Wind Harmer
0.394
339241AF1-083 GEN
Solar/Wind Harmer
1.907
964901AG1-354 GEN
Solar/Wind Harmer
15.617
970653AG2-424 GEN
Solar/Wind Harmer
2.723
950011AG9-010
External Queue
11.361714363098145
LAGNLTFEXP_LAGN->PJM
CLTF
1.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.646
TVALTFEXP_TVA->PJM
CLTF
1.295
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.562
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.923
MECLTFEXP_MEC->PJM
CLTF
0.666
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.013

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:250.47 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:693.79
MW Contribution:
3.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.113
966021AG1-471 GEN
Solar/Wind Harmer
9.329
971485AH1-239 GEN
Solar/Wind Harmer
13.192
339231AF1-038_GEN
Solar/Wind Harmer
2.843
339236AF1-050_GEN
Solar/Wind Harmer
1.903
964781AG1-341 GEN
Solar/Wind Harmer
10.425
3429031COOPER2 G
50/50
6.798
972273AH1-721 GEN
50/50
418.865
339206AE1-143 GEN
Solar/Wind Harmer
2.773
339255AE2-071 GEN
Solar/Wind Harmer
1.202
339250AF1-203 GEN
Solar/Wind Harmer
0.619
970653AG2-424 GEN
Solar/Wind Harmer
0.394
339241AF1-083 GEN
Solar/Wind Harmer
1.907
964901AG1-354 GEN
Solar/Wind Harmer
15.617
970653AG2-424 GEN
Solar/Wind Harmer
2.723
950011AG9-010
External Queue
11.361714363098145
LAGNLTFEXP_LAGN->PJM
CLTF
1.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.646
TVALTFEXP_TVA->PJM
CLTF
1.295
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.562
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.923
MECLTFEXP_MEC->PJM
CLTF
0.666
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.013

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:250.35 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:693.48
MW Contribution:
3.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.116
966021AG1-471 GEN
Solar/Wind Harmer
9.361
971485AH1-239 GEN
Solar/Wind Harmer
13.237
339231AF1-038_GEN
Solar/Wind Harmer
2.854
339236AF1-050_GEN
Solar/Wind Harmer
1.908
964781AG1-341 GEN
Solar/Wind Harmer
10.458
3429031COOPER2 G
50/50
6.81
972273AH1-721 GEN
50/50
419.599
339206AE1-143 GEN
Solar/Wind Harmer
2.78
339255AE2-071 GEN
Solar/Wind Harmer
1.206
339250AF1-203 GEN
Solar/Wind Harmer
0.621
970653AG2-424 GEN
Solar/Wind Harmer
0.395
339241AF1-083 GEN
Solar/Wind Harmer
1.912
964901AG1-354 GEN
Solar/Wind Harmer
15.662
970653AG2-424 GEN
Solar/Wind Harmer
2.731
950011AG9-010
External Queue
11.39061164855957
LAGNLTFEXP_LAGN->PJM
CLTF
1.806
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.669
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.582
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.967
MECLTFEXP_MEC->PJM
CLTF
0.672
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.11

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:250.29 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:693.3
MW Contribution:
3.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.114
966021AG1-471 GEN
Solar/Wind Harmer
9.345
971485AH1-239 GEN
Solar/Wind Harmer
13.214
339231AF1-038_GEN
Solar/Wind Harmer
2.849
339236AF1-050_GEN
Solar/Wind Harmer
1.906
964781AG1-341 GEN
Solar/Wind Harmer
10.442
3429031COOPER2 G
50/50
6.804
972273AH1-721 GEN
50/50
419.224
339206AE1-143 GEN
Solar/Wind Harmer
2.777
339255AE2-071 GEN
Solar/Wind Harmer
1.204
339250AF1-203 GEN
Solar/Wind Harmer
0.62
970653AG2-424 GEN
Solar/Wind Harmer
0.394
339241AF1-083 GEN
Solar/Wind Harmer
1.91
964901AG1-354 GEN
Solar/Wind Harmer
15.642
970653AG2-424 GEN
Solar/Wind Harmer
2.728
950011AG9-010
External Queue
11.37878131866455
LAGNLTFEXP_LAGN->PJM
CLTF
1.796
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.657
TVALTFEXP_TVA->PJM
CLTF
1.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.946
MECLTFEXP_MEC->PJM
CLTF
0.669
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.065

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:240.63 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:666.55
MW Contribution:
2.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
964901AG1-354 GEN
Solar/Wind Harmer
10.927
970653AG2-424 GEN
Solar/Wind Harmer
1.905
3429451LAUREL 1G
50/50
2.116
966021AG1-471 GEN
Solar/Wind Harmer
6.531
971485AH1-239 GEN
Solar/Wind Harmer
9.235
964781AG1-341 GEN
Solar/Wind Harmer
7.296
3429031COOPER2 G
50/50
6.81
972273AH1-721 GEN
50/50
419.599
970653AG2-424 GEN
Solar/Wind Harmer
0.395
950011AG9-010
External Queue
11.39061164855957
LAGNLTFEXP_LAGN->PJM
CLTF
1.806
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.669
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.582
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.967
MECLTFEXP_MEC->PJM
CLTF
0.672
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.11

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:238.58 %
Rating:219.0 MVA
Rating Type:A
MVA to Mitigate:522.49
MW Contribution:
1.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
964901AG1-354 GEN
Solar/Wind Harmer
9.324
970653AG2-424 GEN
Solar/Wind Harmer
1.606
3429451LAUREL 1G
50/50
1.172
966021AG1-471 GEN
Solar/Wind Harmer
5.566
971485AH1-239 GEN
Solar/Wind Harmer
7.867
964781AG1-341 GEN
Solar/Wind Harmer
6.207
3429031COOPER2 G
50/50
5.929
972273AH1-721 GEN
50/50
363.691
970653AG2-424 GEN
Solar/Wind Harmer
0.333
950011AG9-010
External Queue
9.8912935256958
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.03
LAGNLTFEXP_LAGN->PJM
CLTF
1.443
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
1.061
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.912
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.14
MECLTFEXP_MEC->PJM
CLTF
0.52
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.066
WECLTFEXP_WEC->PJM
CLTF
0.059
CPLELTFEXP_CPLE->PJM
CLTF
0.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.133

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:225.99 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:626.0
MW Contribution:
2.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
964901AG1-354 GEN
Solar/Wind Harmer
10.948
970653AG2-424 GEN
Solar/Wind Harmer
1.912
966021AG1-471 GEN
Solar/Wind Harmer
6.539
971485AH1-239 GEN
Solar/Wind Harmer
9.246
964781AG1-341 GEN
Solar/Wind Harmer
7.311
3429031COOPER2 G
50/50
6.813
972273AH1-721 GEN
50/50
419.775
970653AG2-424 GEN
Solar/Wind Harmer
0.396
950011AG9-010
External Queue
11.39061164855957
LAGNLTFEXP_LAGN->PJM
CLTF
1.847
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.729
TVALTFEXP_TVA->PJM
CLTF
1.329
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.874
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.043
MECLTFEXP_MEC->PJM
CLTF
0.706
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.087
CPLELTFEXP_CPLE->PJM
CLTF
0.152
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.38

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_BULL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_BULL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:198.95 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:551.09
MW Contribution:
2.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.179
966021AG1-471 GEN
Solar/Wind Harmer
8.246
971485AH1-239 GEN
Solar/Wind Harmer
11.698
339231AF1-038_GEN
Solar/Wind Harmer
2.389
339236AF1-050_GEN
Solar/Wind Harmer
1.749
964781AG1-341 GEN
Solar/Wind Harmer
9.882
3429031COOPER2 G
50/50
5.962
972273AH1-721 GEN
50/50
365.691
339206AE1-143 GEN
Solar/Wind Harmer
2.453
339255AE2-071 GEN
Solar/Wind Harmer
1.112
339250AF1-203 GEN
Solar/Wind Harmer
0.573
970653AG2-424 GEN
Solar/Wind Harmer
0.347
339241AF1-083 GEN
Solar/Wind Harmer
1.712
964901AG1-354 GEN
Solar/Wind Harmer
14.402
970653AG2-424 GEN
Solar/Wind Harmer
2.401
339211AE2-254 GEN
Solar/Wind Harmer
0.75
950011AG9-010
External Queue
10.310691833496094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.12
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.291
LAGNLTFEXP_LAGN->PJM
CLTF
1.601
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.641
TVALTFEXP_TVA->PJM
CLTF
1.174
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.881
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.407
MECLTFEXP_MEC->PJM
CLTF
0.544
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.064
WECLTFEXP_WEC->PJM
CLTF
0.058
CPLELTFEXP_CPLE->PJM
CLTF
0.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.673

Details for 5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.57 %
Rating:220.0 MVA
Rating Type:B
MVA to Mitigate:234.46
MW Contribution:
3.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
339236AF1-050_GEN
Solar/Wind Harmer
2.932
339231AF1-038_GEN
Solar/Wind Harmer
1.786
971485AH1-239 GEN
Solar/Wind Harmer
5.85
966021AG1-471 GEN
Solar/Wind Harmer
3.94
964781AG1-341 GEN
Solar/Wind Harmer
7.499
3429031COOPER2 G
50/50
1.767
972273AH1-721 GEN
50/50
108.965
339206AE1-143 GEN
Solar/Wind Harmer
8.636
339255AE2-071 GEN
Solar/Wind Harmer
0.855
339250AF1-203 GEN
Solar/Wind Harmer
0.44
970653AG2-424 GEN
Solar/Wind Harmer
0.404
339241AF1-083 GEN
Solar/Wind Harmer
4.334
964901AG1-354 GEN
Solar/Wind Harmer
22.606
970653AG2-424 GEN
Solar/Wind Harmer
2.794
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.292
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.886
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.121
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.251
MECLTFEXP_MEC->PJM
CLTF
0.173
NYPJM->LTFIMP_NY
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.988

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1445_ZIMMER_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1445_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.55 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1647.65
MW Contribution:
5.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
18.648
25197108MELDL2
50/50
1.268
971125AH1-004 GEN
Solar/Wind Harmer
11.529
970107AG2-081 GEN
Solar/Wind Harmer
8.647
972043AH1-570 GEN
Solar/Wind Harmer
7.199
972045AH1-571 GEN
Solar/Wind Harmer
5.759
942891AE2-308 GEN
Solar/Wind Harmer
25.15
339231AF1-038_GEN
Solar/Wind Harmer
1.929
339236AF1-050_GEN
Solar/Wind Harmer
1.676
966021AG1-471 GEN
Solar/Wind Harmer
4.849
971485AH1-239 GEN
Solar/Wind Harmer
7.098
964571AG1-320 GEN
Solar/Wind Harmer
7.24
964781AG1-341 GEN
Solar/Wind Harmer
8.124
971225AH1-072 GEN
Solar/Wind Harmer
0.883
971227AH1-073 GEN
Solar/Wind Harmer
0.883
25183208HLCRTG
Solar/Wind Helper
2.43
252509AD1-136 GEN
Solar/Wind Helper
0.142
253415AE1-040 GEN
Solar/Wind Helper
0.408
3429631SPURLK3G
50/50
9.786
25197208MELDL3
50/50
1.258
958171AF2-111 GEN
Solar/Wind Harmer
128.735
972167AH1-666 GEN
Solar/Wind Harmer
35.72
339243AC2-075 GEN1
Solar/Wind Harmer
1.315
3429391JKCT 9G
Adder
24.087
970093AG2-073 GEN
Solar/Wind Harmer
12.282
972273AH1-721 GEN
Adder
104.619
339206AE1-143 GEN
Solar/Wind Harmer
2.513
970455AG2-298 GEN
Solar/Wind Harmer
3.9
970653AG2-424 GEN
Solar/Wind Harmer
0.671
270186AC1-089 GEN
Solar/Wind Harmer
5.472
339255AE2-071 GEN
Solar/Wind Harmer
0.94
339250AF1-203 GEN
Solar/Wind Harmer
0.484
972103AH1-617 GEN
Solar/Wind Harmer
12.419
971461AH1-227 GEN
Solar/Wind Harmer
2.266
253394AE2-221_GEN
Solar/Wind Helper
2.196
253325AC1-069 GEN
Solar/Wind Helper
0.827
252507AC2-088 GEN
Solar/Wind Helper
0.993
270518AE2-148 GEN
Solar/Wind Helper
6.125
3429661SPURLK4G
50/50
9.786
25197008MELDL1
50/50
1.25
3429571SPURLK1G
50/50
9.78
945681AF1-233 GEN
Solar/Wind Harmer
83.584
943111AE2-339 GEN
Solar/Wind Harmer
2.559
3429421JKCT 10G
Adder
24.087
339221AD2-048_GEN
Solar/Wind Harmer
4.286
3429241JKCT 3G
Adder
32.179
339211AE2-254 GEN
Solar/Wind Harmer
2.559
339241AF1-083 GEN
Solar/Wind Harmer
1.767
970653AG2-424 GEN
Solar/Wind Harmer
4.64
964901AG1-354 GEN
Solar/Wind Harmer
13.573
971687AH1-348 GEN
Solar/Wind Harmer
0.458
253398AE2-221_GEN2
Solar/Wind Helper
2.196
253333AC1-068 GEN
Solar/Wind Helper
0.827
972163AH1-664 GEN
Solar/Wind Harmer
43.025
972165AH1-665 GEN
Solar/Wind Harmer
34.42
339216AC1-074 GEN
Solar/Wind Harmer
4.856
3429211JKCT 2G
Adder
31.762
962211AG1-066 GEN
Solar/Wind Harmer
2.194
970281AG2-184 GEN
Solar/Wind Harmer
13.04
253338AC1-165 GEN
Solar/Wind Helper
0.798
253343AC1-166 GEN
Solar/Wind Helper
0.798
253406AD2-031_GEN
Solar/Wind Helper
0.685
945631AF1-228 GEN
Solar/Wind Helper
0.92
241972AD1-140 GEN
Solar/Wind Helper
1.755
950011AG9-010
External Queue
6.1081342697143555
950041AG9-017
External Queue
23.31861114501953
950051AG9-018
External Queue
23.236736297607422
LAGNLTFEXP_LAGN->PJM
CLTF
6.1
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.899
TVALTFEXP_TVA->PJM
CLTF
3.738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.881
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.374
MECLTFEXP_MEC->PJM
CLTF
2.567
SIGELTFEXP_SIGE->PJM
CLTF
0.219
NYPJM->LTFIMP_NY
CLTF
0.555
LGEELTFEXP_LGEE->PJM
CLTF
4.938
WECLTFEXP_WEC->PJM
CLTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
1.184
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.757

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1449_ZIMMER_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1449_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.43 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1645.79
MW Contribution:
5.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
18.65
25197108MELDL2
50/50
1.268
971125AH1-004 GEN
Solar/Wind Harmer
11.528
970107AG2-081 GEN
Solar/Wind Harmer
8.646
972043AH1-570 GEN
Solar/Wind Harmer
7.198
972045AH1-571 GEN
Solar/Wind Harmer
5.758
942891AE2-308 GEN
Solar/Wind Harmer
25.149
339231AF1-038_GEN
Solar/Wind Harmer
1.929
339236AF1-050_GEN
Solar/Wind Harmer
1.675
966021AG1-471 GEN
Solar/Wind Harmer
4.847
971485AH1-239 GEN
Solar/Wind Harmer
7.096
964571AG1-320 GEN
Solar/Wind Harmer
7.237
964781AG1-341 GEN
Solar/Wind Harmer
8.121
971225AH1-072 GEN
Solar/Wind Harmer
0.883
971227AH1-073 GEN
Solar/Wind Harmer
0.883
25183208HLCRTG
Solar/Wind Helper
2.425
252509AD1-136 GEN
Solar/Wind Helper
0.142
253415AE1-040 GEN
Solar/Wind Helper
0.407
3429631SPURLK3G
50/50
9.787
25197208MELDL3
50/50
1.258
958171AF2-111 GEN
Solar/Wind Harmer
128.745
972167AH1-666 GEN
Solar/Wind Harmer
35.722
339243AC2-075 GEN1
Solar/Wind Harmer
1.315
3429391JKCT 9G
Adder
24.086
970093AG2-073 GEN
Solar/Wind Harmer
12.281
972273AH1-721 GEN
Adder
104.598
339206AE1-143 GEN
Solar/Wind Harmer
2.513
970455AG2-298 GEN
Solar/Wind Harmer
3.899
970653AG2-424 GEN
Solar/Wind Harmer
0.671
270186AC1-089 GEN
Solar/Wind Harmer
5.475
339255AE2-071 GEN
Solar/Wind Harmer
0.939
339250AF1-203 GEN
Solar/Wind Harmer
0.484
972103AH1-617 GEN
Solar/Wind Harmer
12.418
971461AH1-227 GEN
Solar/Wind Harmer
2.266
253394AE2-221_GEN
Solar/Wind Helper
2.194
253325AC1-069 GEN
Solar/Wind Helper
0.826
252507AC2-088 GEN
Solar/Wind Helper
0.996
270518AE2-148 GEN
Solar/Wind Helper
6.113
3429661SPURLK4G
50/50
9.787
25197008MELDL1
50/50
1.25
3429571SPURLK1G
50/50
9.78
945681AF1-233 GEN
Solar/Wind Harmer
83.589
943111AE2-339 GEN
Solar/Wind Harmer
2.559
3429421JKCT 10G
Adder
24.086
339221AD2-048_GEN
Solar/Wind Harmer
4.286
3429241JKCT 3G
Adder
32.178
339211AE2-254 GEN
Solar/Wind Harmer
2.559
339241AF1-083 GEN
Solar/Wind Harmer
1.767
970653AG2-424 GEN
Solar/Wind Harmer
4.638
964901AG1-354 GEN
Solar/Wind Harmer
13.568
971687AH1-348 GEN
Solar/Wind Harmer
0.458
253398AE2-221_GEN2
Solar/Wind Helper
2.194
253333AC1-068 GEN
Solar/Wind Helper
0.826
972163AH1-664 GEN
Solar/Wind Harmer
43.027
972165AH1-665 GEN
Solar/Wind Harmer
34.422
339216AC1-074 GEN
Solar/Wind Harmer
4.855
3429211JKCT 2G
Adder
31.761
962211AG1-066 GEN
Solar/Wind Harmer
2.194
970281AG2-184 GEN
Solar/Wind Harmer
13.039
253338AC1-165 GEN
Solar/Wind Helper
0.797
253343AC1-166 GEN
Solar/Wind Helper
0.797
253406AD2-031_GEN
Solar/Wind Helper
0.683
945631AF1-228 GEN
Solar/Wind Helper
0.919
950011AG9-010
External Queue
6.111148357391357
950041AG9-017
External Queue
23.32491683959961
950051AG9-018
External Queue
23.243040084838867
LAGNLTFEXP_LAGN->PJM
CLTF
6.095
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.896
TVALTFEXP_TVA->PJM
CLTF
3.736
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.363
MECLTFEXP_MEC->PJM
CLTF
2.563
SIGELTFEXP_SIGE->PJM
CLTF
0.219
NYPJM->LTFIMP_NY
CLTF
0.554
LGEELTFEXP_LGEE->PJM
CLTF
4.934
WECLTFEXP_WEC->PJM
CLTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
1.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.719

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.98 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1638.99
MW Contribution:
5.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
31.649
972165AH1-665 GEN
Solar/Wind Harmer
25.319
339216AC1-074 GEN
Solar/Wind Harmer
3.834
3429211JKCT 2G
Adder
24.533
25196108MFTGT2
Adder
1.166
25196108MFTGT2
Adder
1.082
962211AG1-066 GEN
Solar/Wind Harmer
1.711
25196408WSDLE3
Adder
6.108
25196308WSDLE2
Adder
6.055
25196208WSDLE1
Adder
6.04
25196708WSDLE6
Adder
6.025
25196508WSDLE4
Adder
5.873
970281AG2-184 GEN
Solar/Wind Harmer
9.952
253338AC1-165 GEN
Solar/Wind Helper
1.292
253343AC1-166 GEN
Solar/Wind Helper
1.292
253406AD2-031_GEN
Solar/Wind Helper
1.192
945631AF1-228 GEN
Solar/Wind Helper
1.431
241972AD1-140 GEN
Solar/Wind Helper
2.736
270340AC2-060 GEN
Solar/Wind Helper
1.34
241955AC1-078 GEN
Solar/Wind Helper
1.212
241973AD2-163_GEN1
Solar/Wind Helper
0.942
241974AD2-163_GEN2
Solar/Wind Helper
0.942
270263AC1-001 GEN
Solar/Wind Helper
0.509
3429601SPURLK2G
50/50
13.454
25197108MELDL2
50/50
0.567
972043AH1-570 GEN
Solar/Wind Harmer
5.598
972045AH1-571 GEN
Solar/Wind Harmer
4.479
971125AH1-004 GEN
Solar/Wind Harmer
8.94
970107AG2-081 GEN
Solar/Wind Harmer
6.705
942891AE2-308 GEN
Solar/Wind Harmer
19.644
339231AF1-038_GEN
Solar/Wind Harmer
1.696
964571AG1-320 GEN
Solar/Wind Harmer
7.187
339236AF1-050_GEN
Solar/Wind Harmer
1.554
966021AG1-471 GEN
Solar/Wind Harmer
4.35
971485AH1-239 GEN
Solar/Wind Harmer
6.405
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25194408D.CRK1
Adder
5.134
25194508D.CRK3
Adder
0.96
25183208HLCRTG
Solar/Wind Helper
5.698
253415AE1-040 GEN
Solar/Wind Helper
0.679
252509AD1-136 GEN
Solar/Wind Helper
0.14
946101AF1-275 GEN
Solar/Wind Helper
0.373
253383AE2-342_GEN
Solar/Wind Helper
0.369
3429631SPURLK3G
50/50
7.061
25197208MELDL3
50/50
0.562
958171AF2-111 GEN
Solar/Wind Harmer
93.601
972167AH1-666 GEN
Solar/Wind Harmer
26.206
339243AC2-075 GEN1
Solar/Wind Harmer
1.039
3429391JKCT 9G
Adder
18.489
970093AG2-073 GEN
Solar/Wind Harmer
9.666
972273AH1-721 GEN
Adder
88.699
339206AE1-143 GEN
Solar/Wind Harmer
2.228
970455AG2-298 GEN
Solar/Wind Harmer
3.621
970653AG2-424 GEN
Solar/Wind Harmer
0.639
25196008MFTGT1
Adder
1.024
339255AE2-071 GEN
Solar/Wind Harmer
0.892
339250AF1-203 GEN
Solar/Wind Harmer
0.459
270186AC1-089 GEN
Solar/Wind Harmer
4.247
252524AE2-267 GEN
Solar/Wind Harmer
1.09
25196608WSDLE5
Adder
5.933
25194608D.CRK4
Adder
1.116
972103AH1-617 GEN
Solar/Wind Harmer
9.479
253394AE2-221_GEN
Solar/Wind Helper
3.664
253325AC1-069 GEN
Solar/Wind Helper
1.339
270518AE2-148 GEN
Solar/Wind Helper
9.686
252507AC2-088 GEN
Solar/Wind Helper
0.978
960071AF2-298 GEN
Solar/Wind Helper
0.314
960801AF2-371 GEN
Solar/Wind Helper
0.52
964871AG1-351 GEN
Solar/Wind Helper
0.359
3429661SPURLK4G
50/50
7.061
3429571SPURLK1G
50/50
7.129
25197008MELDL1
50/50
0.559
945681AF1-233 GEN
Solar/Wind Harmer
61.342
943111AE2-339 GEN
Solar/Wind Harmer
1.979
3429421JKCT 10G
Adder
18.489
339221AD2-048_GEN
Solar/Wind Harmer
3.377
25196808ZIMRHP
Adder
160.518
3429241JKCT 3G
Adder
24.855
339211AE2-254 GEN
Solar/Wind Harmer
2.125
339241AF1-083 GEN
Solar/Wind Harmer
1.597
970653AG2-424 GEN
Solar/Wind Harmer
4.417
964901AG1-354 GEN
Solar/Wind Harmer
12.634
25196008MFTGT1
Adder
1.057
25194608D.CRK4
Adder
1.116
252510AF1-249 C
Solar/Wind Harmer
0.264
253398AE2-221_GEN2
Solar/Wind Helper
3.664
253333AC1-068 GEN
Solar/Wind Helper
1.339
270520AE2-214 GEN
Solar/Wind Helper
1.493
270273AD2-016 GEN
Solar/Wind Helper
1.381
950041AG9-017
External Queue
14.800519943237305
950051AG9-018
External Queue
14.513641357421875
LAGNLTFEXP_LAGN->PJM
CLTF
6.902
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.204
TVALTFEXP_TVA->PJM
CLTF
3.913
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.766
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.666
MECLTFEXP_MEC->PJM
CLTF
4.442
SIGELTFEXP_SIGE->PJM
CLTF
0.296
NYPJM->LTFIMP_NY
CLTF
0.774
LGEELTFEXP_LGEE->PJM
CLTF
5.705
WECLTFEXP_WEC->PJM
CLTF
0.798
CPLELTFEXP_CPLE->PJM
CLTF
0.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.135

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1373_PORTUNION_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1373_PORTUNION_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.14 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1626.02
MW Contribution:
4.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
15.051
25197108MELDL2
50/50
0.689
972043AH1-570 GEN
Solar/Wind Harmer
6.04
972045AH1-571 GEN
Solar/Wind Harmer
4.832
971125AH1-004 GEN
Solar/Wind Harmer
9.66
970107AG2-081 GEN
Solar/Wind Harmer
7.245
942891AE2-308 GEN
Solar/Wind Harmer
21.138
339231AF1-038_GEN
Solar/Wind Harmer
1.725
339236AF1-050_GEN
Solar/Wind Harmer
1.543
964571AG1-320 GEN
Solar/Wind Harmer
6.934
966021AG1-471 GEN
Solar/Wind Harmer
4.381
971485AH1-239 GEN
Solar/Wind Harmer
6.435
964781AG1-341 GEN
Solar/Wind Harmer
7.632
25183208HLCRTG
Solar/Wind Helper
2.949
253415AE1-040 GEN
Solar/Wind Helper
0.531
946101AF1-275 GEN
Solar/Wind Helper
0.294
252509AD1-136 GEN
Solar/Wind Helper
0.105
972163AH1-664 GEN
Solar/Wind Harmer
35.056
972165AH1-665 GEN
Solar/Wind Harmer
28.045
339216AC1-074 GEN
Solar/Wind Harmer
4.116
3429211JKCT 2G
Adder
26.54
962211AG1-066 GEN
Solar/Wind Harmer
1.83
970281AG2-184 GEN
Solar/Wind Harmer
10.689
25196108MFTGT2
Adder
0.729
25196108MFTGT2
Adder
0.677
253338AC1-165 GEN
Solar/Wind Helper
1.023
253343AC1-166 GEN
Solar/Wind Helper
1.023
253406AD2-031_GEN
Solar/Wind Helper
0.903
945631AF1-228 GEN
Solar/Wind Helper
1.078
270340AC2-060 GEN
Solar/Wind Helper
1.06
241972AD1-140 GEN
Solar/Wind Helper
1.838
241955AC1-078 GEN
Solar/Wind Helper
0.93
3429631SPURLK3G
50/50
7.899
25197208MELDL3
50/50
0.684
958171AF2-111 GEN
Solar/Wind Harmer
104.309
972167AH1-666 GEN
Solar/Wind Harmer
29.068
339243AC2-075 GEN1
Solar/Wind Harmer
1.115
3429391JKCT 9G
Adder
20.063
970093AG2-073 GEN
Solar/Wind Harmer
10.362
972273AH1-721 GEN
Adder
91.729
339206AE1-143 GEN
Solar/Wind Harmer
2.259
970455AG2-298 GEN
Solar/Wind Harmer
3.596
970653AG2-424 GEN
Solar/Wind Harmer
0.627
339255AE2-071 GEN
Solar/Wind Harmer
0.876
339250AF1-203 GEN
Solar/Wind Harmer
0.451
270186AC1-089 GEN
Solar/Wind Harmer
4.264
972103AH1-617 GEN
Solar/Wind Harmer
10.18
25196008MFTGT1
Adder
0.64
253394AE2-221_GEN
Solar/Wind Helper
2.845
253325AC1-069 GEN
Solar/Wind Helper
1.06
270518AE2-148 GEN
Solar/Wind Helper
7.005
252507AC2-088 GEN
Solar/Wind Helper
0.736
3429661SPURLK4G
50/50
7.899
3429571SPURLK1G
50/50
7.935
25197008MELDL1
50/50
0.68
25196808ZIMRHP
50/50
216.614
945681AF1-233 GEN
Solar/Wind Harmer
68.028
943111AE2-339 GEN
Solar/Wind Harmer
2.141
3429421JKCT 10G
Adder
20.063
339221AD2-048_GEN
Solar/Wind Harmer
3.624
3429241JKCT 3G
Adder
26.889
339211AE2-254 GEN
Solar/Wind Harmer
2.221
339241AF1-083 GEN
Solar/Wind Harmer
1.605
970653AG2-424 GEN
Solar/Wind Harmer
4.338
964901AG1-354 GEN
Solar/Wind Harmer
12.527
25196008MFTGT1
Adder
0.661
253398AE2-221_GEN2
Solar/Wind Helper
2.845
253333AC1-068 GEN
Solar/Wind Helper
1.06
270520AE2-214 GEN
Solar/Wind Helper
1.175
950041AG9-017
External Queue
17.633872985839844
950051AG9-018
External Queue
17.4936466217041
LAGNLTFEXP_LAGN->PJM
CLTF
6.318
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.215
TVALTFEXP_TVA->PJM
CLTF
3.686
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.436
MECLTFEXP_MEC->PJM
CLTF
3.587
SIGELTFEXP_SIGE->PJM
CLTF
0.255
NYPJM->LTFIMP_NY
CLTF
0.654
LGEELTFEXP_LGEE->PJM
CLTF
5.166
WECLTFEXP_WEC->PJM
CLTF
0.598
CPLELTFEXP_CPLE->PJM
CLTF
0.943
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.569

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1493_RED BANK_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1493_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.1 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1610.06
MW Contribution:
4.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
15.451
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.765
970107AG2-081 GEN
Solar/Wind Harmer
7.323
972043AH1-570 GEN
Solar/Wind Harmer
6.102
972045AH1-571 GEN
Solar/Wind Harmer
4.881
942891AE2-308 GEN
Solar/Wind Harmer
21.351
339231AF1-038_GEN
Solar/Wind Harmer
1.702
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.69
966021AG1-471 GEN
Solar/Wind Harmer
4.307
971485AH1-239 GEN
Solar/Wind Harmer
6.318
964781AG1-341 GEN
Solar/Wind Harmer
7.405
25183208HLCRTG
Solar/Wind Helper
2.518
252509AD1-136 GEN
Solar/Wind Helper
0.126
253415AE1-040 GEN
Solar/Wind Helper
0.462
972163AH1-664 GEN
Solar/Wind Harmer
35.849
972165AH1-665 GEN
Solar/Wind Harmer
28.679
339216AC1-074 GEN
Solar/Wind Harmer
4.134
3429211JKCT 2G
Adder
26.87
962211AG1-066 GEN
Solar/Wind Harmer
1.846
970281AG2-184 GEN
Solar/Wind Harmer
10.819
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.945
3429631SPURLK3G
50/50
8.108
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.911
972167AH1-666 GEN
Solar/Wind Harmer
29.739
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.338
970093AG2-073 GEN
Solar/Wind Harmer
10.451
972273AH1-721 GEN
Adder
91.159
339206AE1-143 GEN
Solar/Wind Harmer
2.226
970455AG2-298 GEN
Solar/Wind Harmer
3.514
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.706
339255AE2-071 GEN
Solar/Wind Harmer
0.852
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.304
253394AE2-221_GEN
Solar/Wind Helper
2.61
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.879
270518AE2-148 GEN
Solar/Wind Helper
5.932
3429661SPURLK4G
50/50
8.108
3429571SPURLK1G
50/50
8.127
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.792
945681AF1-233 GEN
Solar/Wind Harmer
69.595
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.338
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.222
339211AE2-254 GEN
Solar/Wind Harmer
2.216
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.218
964901AG1-354 GEN
Solar/Wind Harmer
12.23
253398AE2-221_GEN2
Solar/Wind Helper
2.61
253333AC1-068 GEN
Solar/Wind Helper
0.979
950041AG9-017
External Queue
18.613412857055664
950051AG9-018
External Queue
18.441604614257812
LAGNLTFEXP_LAGN->PJM
CLTF
5.925
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.129
TVALTFEXP_TVA->PJM
CLTF
3.509
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.619
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.574
MECLTFEXP_MEC->PJM
CLTF
3.122
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.842
WECLTFEXP_WEC->PJM
CLTF
0.494
CPLELTFEXP_CPLE->PJM
CLTF
0.937
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.691

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1487_RED BANK_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1487_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1609.33
MW Contribution:
4.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
15.451
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.765
970107AG2-081 GEN
Solar/Wind Harmer
7.323
972043AH1-570 GEN
Solar/Wind Harmer
6.102
972045AH1-571 GEN
Solar/Wind Harmer
4.881
942891AE2-308 GEN
Solar/Wind Harmer
21.351
339231AF1-038_GEN
Solar/Wind Harmer
1.702
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.69
966021AG1-471 GEN
Solar/Wind Harmer
4.307
971485AH1-239 GEN
Solar/Wind Harmer
6.318
964781AG1-341 GEN
Solar/Wind Harmer
7.405
25183208HLCRTG
Solar/Wind Helper
2.518
252509AD1-136 GEN
Solar/Wind Helper
0.125
253415AE1-040 GEN
Solar/Wind Helper
0.462
972163AH1-664 GEN
Solar/Wind Harmer
35.849
972165AH1-665 GEN
Solar/Wind Harmer
28.679
339216AC1-074 GEN
Solar/Wind Harmer
4.134
3429211JKCT 2G
Adder
26.87
962211AG1-066 GEN
Solar/Wind Harmer
1.846
970281AG2-184 GEN
Solar/Wind Harmer
10.819
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.945
3429631SPURLK3G
50/50
8.108
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.91
972167AH1-666 GEN
Solar/Wind Harmer
29.739
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.338
970093AG2-073 GEN
Solar/Wind Harmer
10.451
972273AH1-721 GEN
Adder
91.159
339206AE1-143 GEN
Solar/Wind Harmer
2.226
970455AG2-298 GEN
Solar/Wind Harmer
3.514
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.707
339255AE2-071 GEN
Solar/Wind Harmer
0.852
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.304
253394AE2-221_GEN
Solar/Wind Helper
2.61
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.878
270518AE2-148 GEN
Solar/Wind Helper
5.933
3429661SPURLK4G
50/50
8.108
3429571SPURLK1G
50/50
8.127
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.774
945681AF1-233 GEN
Solar/Wind Harmer
69.594
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.338
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.222
339211AE2-254 GEN
Solar/Wind Harmer
2.216
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.218
964901AG1-354 GEN
Solar/Wind Harmer
12.23
253398AE2-221_GEN2
Solar/Wind Helper
2.61
253333AC1-068 GEN
Solar/Wind Helper
0.979
950041AG9-017
External Queue
18.61345100402832
950051AG9-018
External Queue
18.441471099853516
LAGNLTFEXP_LAGN->PJM
CLTF
5.925
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.129
TVALTFEXP_TVA->PJM
CLTF
3.509
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.573
MECLTFEXP_MEC->PJM
CLTF
3.121
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.842
WECLTFEXP_WEC->PJM
CLTF
0.494
CPLELTFEXP_CPLE->PJM
CLTF
0.937
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.689

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.96 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1608.02
MW Contribution:
4.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
35.852
972165AH1-665 GEN
Solar/Wind Harmer
28.681
339216AC1-074 GEN
Solar/Wind Harmer
4.135
3429211JKCT 2G
Adder
26.873
962211AG1-066 GEN
Solar/Wind Harmer
1.847
970281AG2-184 GEN
Solar/Wind Harmer
10.819
3429601SPURLK2G
50/50
15.452
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.766
970107AG2-081 GEN
Solar/Wind Harmer
7.324
972043AH1-570 GEN
Solar/Wind Harmer
6.103
972045AH1-571 GEN
Solar/Wind Harmer
4.882
942891AE2-308 GEN
Solar/Wind Harmer
21.354
339231AF1-038_GEN
Solar/Wind Harmer
1.703
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.692
966021AG1-471 GEN
Solar/Wind Harmer
4.308
971485AH1-239 GEN
Solar/Wind Harmer
6.32
964781AG1-341 GEN
Solar/Wind Harmer
7.407
25183208HLCRTG
Solar/Wind Helper
2.519
252509AD1-136 GEN
Solar/Wind Helper
0.127
253415AE1-040 GEN
Solar/Wind Helper
0.462
253338AC1-165 GEN
Solar/Wind Helper
0.945
3429631SPURLK3G
50/50
8.109
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.917
972167AH1-666 GEN
Solar/Wind Harmer
29.741
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.341
970093AG2-073 GEN
Solar/Wind Harmer
10.453
972273AH1-721 GEN
Adder
91.178
339206AE1-143 GEN
Solar/Wind Harmer
2.227
970455AG2-298 GEN
Solar/Wind Harmer
3.515
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.707
339255AE2-071 GEN
Solar/Wind Harmer
0.853
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.304
253394AE2-221_GEN
Solar/Wind Helper
2.61
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.886
270518AE2-148 GEN
Solar/Wind Helper
5.931
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.944
3429661SPURLK4G
50/50
8.109
3429571SPURLK1G
50/50
8.128
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.827
945681AF1-233 GEN
Solar/Wind Harmer
69.6
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.341
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.226
339211AE2-254 GEN
Solar/Wind Harmer
2.217
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.22
964901AG1-354 GEN
Solar/Wind Harmer
12.233
253398AE2-221_GEN2
Solar/Wind Helper
2.61
253333AC1-068 GEN
Solar/Wind Helper
0.979
950041AG9-017
External Queue
18.613161087036133
950051AG9-018
External Queue
18.440826416015625
LAGNLTFEXP_LAGN->PJM
CLTF
5.927
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.129
TVALTFEXP_TVA->PJM
CLTF
3.51
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.634
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.579
MECLTFEXP_MEC->PJM
CLTF
3.124
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.844
WECLTFEXP_WEC->PJM
CLTF
0.494
CPLELTFEXP_CPLE->PJM
CLTF
0.937
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.712

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.95 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1607.79
MW Contribution:
4.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
35.848
972165AH1-665 GEN
Solar/Wind Harmer
28.679
339216AC1-074 GEN
Solar/Wind Harmer
4.134
3429211JKCT 2G
Adder
26.87
962211AG1-066 GEN
Solar/Wind Harmer
1.847
970281AG2-184 GEN
Solar/Wind Harmer
10.82
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.945
3429601SPURLK2G
50/50
15.45
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.765
970107AG2-081 GEN
Solar/Wind Harmer
7.324
972043AH1-570 GEN
Solar/Wind Harmer
6.102
972045AH1-571 GEN
Solar/Wind Harmer
4.882
942891AE2-308 GEN
Solar/Wind Harmer
21.351
339231AF1-038_GEN
Solar/Wind Harmer
1.702
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.691
966021AG1-471 GEN
Solar/Wind Harmer
4.307
971485AH1-239 GEN
Solar/Wind Harmer
6.319
964781AG1-341 GEN
Solar/Wind Harmer
7.406
25183208HLCRTG
Solar/Wind Helper
2.518
252509AD1-136 GEN
Solar/Wind Helper
0.125
253415AE1-040 GEN
Solar/Wind Helper
0.462
3429631SPURLK3G
50/50
8.108
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.907
972167AH1-666 GEN
Solar/Wind Harmer
29.739
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.338
970093AG2-073 GEN
Solar/Wind Harmer
10.451
972273AH1-721 GEN
Adder
91.166
339206AE1-143 GEN
Solar/Wind Harmer
2.226
970455AG2-298 GEN
Solar/Wind Harmer
3.514
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.707
339255AE2-071 GEN
Solar/Wind Harmer
0.852
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.305
253394AE2-221_GEN
Solar/Wind Helper
2.611
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.876
270518AE2-148 GEN
Solar/Wind Helper
5.934
3429661SPURLK4G
50/50
8.108
3429571SPURLK1G
50/50
8.127
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.731
945681AF1-233 GEN
Solar/Wind Harmer
69.594
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.338
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.223
339211AE2-254 GEN
Solar/Wind Harmer
2.216
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.219
964901AG1-354 GEN
Solar/Wind Harmer
12.231
253398AE2-221_GEN2
Solar/Wind Helper
2.611
253333AC1-068 GEN
Solar/Wind Helper
0.979
950041AG9-017
External Queue
18.612449645996094
950051AG9-018
External Queue
18.440135955810547
LAGNLTFEXP_LAGN->PJM
CLTF
5.926
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.131
TVALTFEXP_TVA->PJM
CLTF
3.509
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.615
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.576
MECLTFEXP_MEC->PJM
CLTF
3.121
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.843
WECLTFEXP_WEC->PJM
CLTF
0.494
CPLELTFEXP_CPLE->PJM
CLTF
0.938
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.692

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.93 %
Rating:1240.0 MVA
Rating Type:A
MVA to Mitigate:1301.17
MW Contribution:
3.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
25.864
972165AH1-665 GEN
Solar/Wind Harmer
20.714
339216AC1-074 GEN
Solar/Wind Harmer
0.434
3429211JKCT 2G
Adder
25.2
970281AG2-184 GEN
Solar/Wind Harmer
7.039
25196108MFTGT2
Adder
0.689
25196108MFTGT2
Adder
0.64
253338AC1-165 GEN
Solar/Wind Helper
1.016
253343AC1-166 GEN
Solar/Wind Helper
1.016
253406AD2-031_GEN
Solar/Wind Helper
0.85
945631AF1-228 GEN
Solar/Wind Helper
0.992
270340AC2-060 GEN
Solar/Wind Helper
0.994
3429661SPURLK4G
50/50
7.499
3429571SPURLK1G
50/50
7.535
25197008MELDL1
50/50
0.54
945681AF1-233 GEN
Solar/Wind Harmer
45.077
3429421JKCT 10G
Adder
19.05
3429241JKCT 3G
Adder
25.531
25196808ZIMRHP
Adder
146.641
970653AG2-424 GEN
Solar/Wind Harmer
2.876
964901AG1-354 GEN
Solar/Wind Harmer
8.3
25196008MFTGT1
Adder
0.625
253398AE2-221_GEN2
Solar/Wind Helper
2.816
253333AC1-068 GEN
Solar/Wind Helper
1.053
270520AE2-214 GEN
Solar/Wind Helper
1.117
3429631SPURLK3G
50/50
7.499
25197208MELDL3
50/50
0.543
958171AF2-111 GEN
Solar/Wind Harmer
69.096
972167AH1-666 GEN
Solar/Wind Harmer
19.261
3429391JKCT 9G
Adder
19.05
970093AG2-073 GEN
Solar/Wind Harmer
10.983
972273AH1-721 GEN
Adder
87.068
970455AG2-298 GEN
Solar/Wind Harmer
2.649
970653AG2-424 GEN
Solar/Wind Harmer
0.596
270186AC1-089 GEN
Solar/Wind Harmer
0
972103AH1-617 GEN
Solar/Wind Harmer
6.704
25196008MFTGT1
Adder
0.605
253394AE2-221_GEN
Solar/Wind Helper
2.816
253325AC1-069 GEN
Solar/Wind Helper
1.053
270518AE2-148 GEN
Solar/Wind Helper
6.196
252507AC2-088 GEN
Solar/Wind Helper
0.745
3429601SPURLK2G
50/50
14.29
25197108MELDL2
50/50
0.548
972043AH1-570 GEN
Solar/Wind Harmer
4.163
972045AH1-571 GEN
Solar/Wind Harmer
3.336
971125AH1-004 GEN
Solar/Wind Harmer
6.399
970107AG2-081 GEN
Solar/Wind Harmer
4.799
942891AE2-308 GEN
Solar/Wind Harmer
14.003
964571AG1-320 GEN
Solar/Wind Harmer
5.122
966021AG1-471 GEN
Solar/Wind Harmer
2.901
971485AH1-239 GEN
Solar/Wind Harmer
4.261
964781AG1-341 GEN
Solar/Wind Harmer
5.057
25183208HLCRTG
Solar/Wind Helper
2.669
253415AE1-040 GEN
Solar/Wind Helper
0.5
252509AD1-136 GEN
Solar/Wind Helper
0.106
946101AF1-275 GEN
Solar/Wind Helper
0.279
950041AG9-017
External Queue
16.80695915222168
950051AG9-018
External Queue
16.602676391601562
LAGNLTFEXP_LAGN->PJM
CLTF
5.986
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.932
TVALTFEXP_TVA->PJM
CLTF
3.49
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.28
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.592
MECLTFEXP_MEC->PJM
CLTF
3.424
SIGELTFEXP_SIGE->PJM
CLTF
0.243
NYPJM->LTFIMP_NY
CLTF
0.629
LGEELTFEXP_LGEE->PJM
CLTF
4.921
WECLTFEXP_WEC->PJM
CLTF
0.575
CPLELTFEXP_CPLE->PJM
CLTF
0.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.388

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o EKPC_P2-2_MELD-SPUR 345_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_MELD-SPUR 345_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.1 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1579.46
MW Contribution:
5.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
43.062
972165AH1-665 GEN
Solar/Wind Harmer
34.449
339216AC1-074 GEN
Solar/Wind Harmer
4.861
3429211JKCT 2G
Adder
31.801
962211AG1-066 GEN
Solar/Wind Harmer
2.202
970281AG2-184 GEN
Solar/Wind Harmer
13.111
253338AC1-165 GEN
Solar/Wind Helper
0.794
253343AC1-166 GEN
Solar/Wind Helper
0.794
253406AD2-031_GEN
Solar/Wind Helper
0.679
945631AF1-228 GEN
Solar/Wind Helper
0.912
3429601SPURLK2G
50/50
18.661
971125AH1-004 GEN
Solar/Wind Harmer
11.542
970107AG2-081 GEN
Solar/Wind Harmer
8.656
972043AH1-570 GEN
Solar/Wind Harmer
7.207
972045AH1-571 GEN
Solar/Wind Harmer
5.765
942891AE2-308 GEN
Solar/Wind Harmer
25.183
339231AF1-038_GEN
Solar/Wind Harmer
1.935
339236AF1-050_GEN
Solar/Wind Harmer
1.681
966021AG1-471 GEN
Solar/Wind Harmer
4.866
971485AH1-239 GEN
Solar/Wind Harmer
7.124
964571AG1-320 GEN
Solar/Wind Harmer
7.265
964781AG1-341 GEN
Solar/Wind Harmer
8.157
971225AH1-072 GEN
Solar/Wind Harmer
0.89
971227AH1-073 GEN
Solar/Wind Harmer
0.89
25183208HLCRTG
Solar/Wind Helper
2.416
252509AD1-136 GEN
Solar/Wind Helper
0.141
3429631SPURLK3G
50/50
9.793
958171AF2-111 GEN
Solar/Wind Harmer
128.831
972167AH1-666 GEN
Solar/Wind Harmer
35.75
339243AC2-075 GEN1
Solar/Wind Harmer
1.316
3429391JKCT 9G
Adder
24.115
970093AG2-073 GEN
Solar/Wind Harmer
12.299
972273AH1-721 GEN
Adder
104.883
339206AE1-143 GEN
Solar/Wind Harmer
2.52
970455AG2-298 GEN
Solar/Wind Harmer
3.911
970653AG2-424 GEN
Solar/Wind Harmer
0.673
270186AC1-089 GEN
Solar/Wind Harmer
5.496
339255AE2-071 GEN
Solar/Wind Harmer
0.943
339250AF1-203 GEN
Solar/Wind Harmer
0.486
972103AH1-617 GEN
Solar/Wind Harmer
12.486
971461AH1-227 GEN
Solar/Wind Harmer
2.283
253394AE2-221_GEN
Solar/Wind Helper
2.188
253325AC1-069 GEN
Solar/Wind Helper
0.822
252507AC2-088 GEN
Solar/Wind Helper
0.99
270518AE2-148 GEN
Solar/Wind Helper
6.07
3429661SPURLK4G
50/50
9.793
3429571SPURLK1G
50/50
9.787
945681AF1-233 GEN
Solar/Wind Harmer
83.653
943111AE2-339 GEN
Solar/Wind Harmer
2.562
3429421JKCT 10G
Adder
24.115
339221AD2-048_GEN
Solar/Wind Harmer
4.291
3429241JKCT 3G
Adder
32.219
339211AE2-254 GEN
Solar/Wind Harmer
2.564
339241AF1-083 GEN
Solar/Wind Harmer
1.773
970653AG2-424 GEN
Solar/Wind Harmer
4.655
964901AG1-354 GEN
Solar/Wind Harmer
13.62
971687AH1-348 GEN
Solar/Wind Harmer
0.461
253398AE2-221_GEN2
Solar/Wind Helper
2.188
253333AC1-068 GEN
Solar/Wind Helper
0.822
950011AG9-010
External Queue
6.111148357391357
950041AG9-017
External Queue
23.32491683959961
950051AG9-018
External Queue
23.243040084838867
LAGNLTFEXP_LAGN->PJM
CLTF
6.165
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5
TVALTFEXP_TVA->PJM
CLTF
3.771
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.357
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.494
MECLTFEXP_MEC->PJM
CLTF
2.621
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
0.532
LGEELTFEXP_LGEE->PJM
CLTF
4.958
WECLTFEXP_WEC->PJM
CLTF
0.339
CPLELTFEXP_CPLE->PJM
CLTF
1.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.182

Details for AG2-298 TP-2LORETTO 69.0 kV Ckt 1 line l/o EKPC_P2-2_BARDIT-EBARD69_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC
Facility Description:
AG2-298 TP-2LORETTO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_BARDIT-EBARD69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.08 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:46.04
MW Contribution:
3.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
964571AG1-320 GEN
Solar/Wind Harmer
4.155
970455AG2-298 GEN
Solar/Wind Harmer
14.635
970653AG2-424 GEN
Solar/Wind Harmer
0.418
970653AG2-424 GEN
Solar/Wind Harmer
2.893
LAGNLTFEXP_LAGN->PJM
CLTF
0.067
TVALTFEXP_TVA->PJM
CLTF
0.028
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.493
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.134
MECLTFEXP_MEC->PJM
CLTF
0.077
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.003
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-2'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
 OPEN BUS 342754                                   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P7-1_LAURL 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P2-2_LAUR-LAURD161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_LAUREL CO 161_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-L DAM161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-2'
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P7-1_BULL 161 DBL_SRT-A'
 OPEN BUS 326975   /*5CEDAR GRV   161.0
 OPEN BUS 361788   /*5SUM SHAD TP 161.0
END
CONTINGENCY 'DEOK_P4_1445_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1449_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY '34569 34598 34524_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 249578 CKT 1   /*08FOSTER     345.0 - 08HILCRT     345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'DEOK_P4_1373_PORTUNION_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249575 CKT 1   /*08P.UNON     345.0 - 08TERMNL     345.0
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1493_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250092 CKT 1   /*08REDBK1     345.0 - 08REDBK1     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P4_1487_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250093 CKT 1   /*08REDBK1     345.0 - 08REDBK2     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
 OPEN BUS 250079   /*08NWTWN1     138.0
END
CONTINGENCY 'DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
END
CONTINGENCY 'EKPC_P2-2_MELD-SPUR 345_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1   /*08MELDAL     345.0 - 7SPURLOCK    345.0
END
CONTINGENCY 'EKPC_P2-2_BARDIT-EBARD69_SRT-A'
 OPEN BUS 341407   /*2E BARDSTOWN  69.0
END
247977 to 242524 ckt 17
242519 to 314912 ckt 1
242516 to 242920 ckt 1
248005 to 242528 ckt 1
248013 to 242938 ckt 1
342770 to 324271 ckt 1
342718 to 324141 ckt 1
342769 to 342770 ckt 1
342838 to 253077 ckt 1
970454 to 341776 ckt 1

Winter Peak Analysis

The New Service Request AG2-424 was evaluated as a 63.25 MW (34.95 MW Capacity) injection in the EKPC area.

AG2-424 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 63.25 MW (63.25 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC135.36 %305.0B412.85
0.47

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:135.36 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:412.85
MW Contribution:
0.47
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
108.527
3429451LAUREL 1G
50/50
1.173
970653AG2-424 GEN
Solar/Wind Harmer
0.136
970653AG2-424 GEN
Solar/Wind Harmer
0.339
971485AH1-239 GEN
Solar/Wind Harmer
0.72
964781AG1-341 GEN
Solar/Wind Harmer
0.524
964901AG1-354 GEN
Solar/Wind Harmer
0.786
966021AG1-471 GEN
Solar/Wind Harmer
0.482
972273AH1-721 GEN
50/50
376.735
950011AG9-010
External Queue
0.5764614939689636
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.054
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.187
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.684
NYPJM->LTFIMP_NY
CLTF
0.03
WECLTFEXP_WEC->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.158
TVALTFEXP_TVA->PJM
CLTF
1.063
MECLTFEXP_MEC->PJM
CLTF
0.626
LAGNLTFEXP_LAGN->PJM
CLTF
1.577
SIGELTFEXP_SIGE->PJM
CLTF
0.02
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.024
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS'
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 1   /*5ALCALDE     161.0 - AH1-721 TP   161.0
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 2   /*5ALCALDE     161.0 - AH1-721 TP   161.0
END
342718 to 324141 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC184.26 %305.0B561.98
0.56
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC184.25 %305.0B561.97
0.56
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC184.25 %305.0B561.96
0.56
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC183.81 %305.0B560.61
0.56
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC183.8 %305.0B560.6
0.56
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC183.79 %305.0B560.55
0.56
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-2
SingleAC170.9 %305.0B521.25
0.56
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC149.52 %279.0A417.15
0.47
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_SPUR 345&138_SRT-A
TowerAC137.8 %305.0B420.28
0.46

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:184.26 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:561.98
MW Contribution:
0.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
124.571
3429451LAUREL 1G
50/50
2.116
970653AG2-424 GEN
Solar/Wind Harmer
0.16
970653AG2-424 GEN
Solar/Wind Harmer
0.398
971485AH1-239 GEN
Solar/Wind Harmer
0.77
964781AG1-341 GEN
Solar/Wind Harmer
0.61
964901AG1-354 GEN
Solar/Wind Harmer
0.914
966021AG1-471 GEN
Solar/Wind Harmer
0.544
972273AH1-721 GEN
50/50
434.378
950011AG9-010
External Queue
0.6617914438247681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.868
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.761
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.833
NYPJM->LTFIMP_NY
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.191
TVALTFEXP_TVA->PJM
CLTF
1.281
MECLTFEXP_MEC->PJM
CLTF
0.784
LAGNLTFEXP_LAGN->PJM
CLTF
1.914
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.093

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.25 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:561.97
MW Contribution:
0.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
124.571
3429451LAUREL 1G
50/50
2.116
970653AG2-424 GEN
Solar/Wind Harmer
0.16
970653AG2-424 GEN
Solar/Wind Harmer
0.398
971485AH1-239 GEN
Solar/Wind Harmer
0.77
964781AG1-341 GEN
Solar/Wind Harmer
0.61
964901AG1-354 GEN
Solar/Wind Harmer
0.914
966021AG1-471 GEN
Solar/Wind Harmer
0.544
972273AH1-721 GEN
50/50
434.378
950011AG9-010
External Queue
0.6617914438247681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.868
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.761
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.833
NYPJM->LTFIMP_NY
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.191
TVALTFEXP_TVA->PJM
CLTF
1.281
MECLTFEXP_MEC->PJM
CLTF
0.784
LAGNLTFEXP_LAGN->PJM
CLTF
1.914
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.093

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.25 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:561.96
MW Contribution:
0.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
124.571
3429451LAUREL 1G
50/50
2.116
970653AG2-424 GEN
Solar/Wind Harmer
0.16
970653AG2-424 GEN
Solar/Wind Harmer
0.398
971485AH1-239 GEN
Solar/Wind Harmer
0.77
964781AG1-341 GEN
Solar/Wind Harmer
0.61
964901AG1-354 GEN
Solar/Wind Harmer
0.914
966021AG1-471 GEN
Solar/Wind Harmer
0.544
972273AH1-721 GEN
50/50
434.378
950011AG9-010
External Queue
0.6617914438247681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.868
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.761
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.833
NYPJM->LTFIMP_NY
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.191
TVALTFEXP_TVA->PJM
CLTF
1.281
MECLTFEXP_MEC->PJM
CLTF
0.784
LAGNLTFEXP_LAGN->PJM
CLTF
1.914
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.093

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:183.81 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:560.61
MW Contribution:
0.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
124.788
3429451LAUREL 1G
50/50
2.119
970653AG2-424 GEN
Solar/Wind Harmer
0.161
970653AG2-424 GEN
Solar/Wind Harmer
0.399
971485AH1-239 GEN
Solar/Wind Harmer
0.773
964781AG1-341 GEN
Solar/Wind Harmer
0.612
964901AG1-354 GEN
Solar/Wind Harmer
0.916
966021AG1-471 GEN
Solar/Wind Harmer
0.546
972273AH1-721 GEN
50/50
435.138
950011AG9-010
External Queue
0.6634839773178101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.891
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.964
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.856
NYPJM->LTFIMP_NY
CLTF
0.04
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.198
TVALTFEXP_TVA->PJM
CLTF
1.295
MECLTFEXP_MEC->PJM
CLTF
0.79
LAGNLTFEXP_LAGN->PJM
CLTF
1.936
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.112

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:183.8 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:560.6
MW Contribution:
0.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
124.788
3429451LAUREL 1G
50/50
2.119
970653AG2-424 GEN
Solar/Wind Harmer
0.161
970653AG2-424 GEN
Solar/Wind Harmer
0.399
971485AH1-239 GEN
Solar/Wind Harmer
0.773
964781AG1-341 GEN
Solar/Wind Harmer
0.612
964901AG1-354 GEN
Solar/Wind Harmer
0.916
966021AG1-471 GEN
Solar/Wind Harmer
0.546
972273AH1-721 GEN
50/50
435.138
950011AG9-010
External Queue
0.6634839773178101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.891
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.964
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.856
NYPJM->LTFIMP_NY
CLTF
0.04
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.198
TVALTFEXP_TVA->PJM
CLTF
1.295
MECLTFEXP_MEC->PJM
CLTF
0.79
LAGNLTFEXP_LAGN->PJM
CLTF
1.936
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.112

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:183.79 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:560.55
MW Contribution:
0.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
124.677
3429451LAUREL 1G
50/50
2.117
970653AG2-424 GEN
Solar/Wind Harmer
0.16
970653AG2-424 GEN
Solar/Wind Harmer
0.399
971485AH1-239 GEN
Solar/Wind Harmer
0.771
964781AG1-341 GEN
Solar/Wind Harmer
0.611
964901AG1-354 GEN
Solar/Wind Harmer
0.915
966021AG1-471 GEN
Solar/Wind Harmer
0.545
972273AH1-721 GEN
50/50
434.751
950011AG9-010
External Queue
0.6627915501594543
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.813
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.943
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.845
NYPJM->LTFIMP_NY
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.195
TVALTFEXP_TVA->PJM
CLTF
1.288
MECLTFEXP_MEC->PJM
CLTF
0.787
LAGNLTFEXP_LAGN->PJM
CLTF
1.925
SIGELTFEXP_SIGE->PJM
CLTF
0.027
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.102

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:170.9 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:521.25
MW Contribution:
0.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
124.848
970653AG2-424 GEN
Solar/Wind Harmer
0.161
970653AG2-424 GEN
Solar/Wind Harmer
0.401
971485AH1-239 GEN
Solar/Wind Harmer
0.774
964781AG1-341 GEN
Solar/Wind Harmer
0.613
964901AG1-354 GEN
Solar/Wind Harmer
0.918
966021AG1-471 GEN
Solar/Wind Harmer
0.547
972273AH1-721 GEN
50/50
435.348
950011AG9-010
External Queue
0.6634839773178101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.051
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.926
NYPJM->LTFIMP_NY
CLTF
0.026
WECLTFEXP_WEC->PJM
CLTF
0.112
CPLELTFEXP_CPLE->PJM
CLTF
0.223
TVALTFEXP_TVA->PJM
CLTF
1.318
MECLTFEXP_MEC->PJM
CLTF
0.828
LAGNLTFEXP_LAGN->PJM
CLTF
1.982
SIGELTFEXP_SIGE->PJM
CLTF
0.029
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.112

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:149.52 %
Rating:279.0 MVA
Rating Type:A
MVA to Mitigate:417.15
MW Contribution:
0.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
108.652
3429451LAUREL 1G
50/50
1.174
970653AG2-424 GEN
Solar/Wind Harmer
0.135
970653AG2-424 GEN
Solar/Wind Harmer
0.337
971485AH1-239 GEN
Solar/Wind Harmer
0.658
964781AG1-341 GEN
Solar/Wind Harmer
0.521
964901AG1-354 GEN
Solar/Wind Harmer
0.782
966021AG1-471 GEN
Solar/Wind Harmer
0.466
972273AH1-721 GEN
50/50
377.185
950011AG9-010
External Queue
0.57616126537323
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.058
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.825
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.149
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.665
NYPJM->LTFIMP_NY
CLTF
0.029
WECLTFEXP_WEC->PJM
CLTF
0.081
CPLELTFEXP_CPLE->PJM
CLTF
0.154
TVALTFEXP_TVA->PJM
CLTF
1.052
MECLTFEXP_MEC->PJM
CLTF
0.625
LAGNLTFEXP_LAGN->PJM
CLTF
1.561
SIGELTFEXP_SIGE->PJM
CLTF
0.019
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.069

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_SPUR 345&138_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_SPUR 345&138_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:137.8 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:420.28
MW Contribution:
0.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
108.189
3429451LAUREL 1G
50/50
1.166
970653AG2-424 GEN
Solar/Wind Harmer
0.132
970653AG2-424 GEN
Solar/Wind Harmer
0.328
971485AH1-239 GEN
Solar/Wind Harmer
0.653
964781AG1-341 GEN
Solar/Wind Harmer
0.514
964901AG1-354 GEN
Solar/Wind Harmer
0.771
966021AG1-471 GEN
Solar/Wind Harmer
0.462
972273AH1-721 GEN
50/50
375.566
950011AG9-010
External Queue
0.5702452063560486
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.315
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.926
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.578
NYPJM->LTFIMP_NY
CLTF
0.028
WECLTFEXP_WEC->PJM
CLTF
0.075
CPLELTFEXP_CPLE->PJM
CLTF
0.13
TVALTFEXP_TVA->PJM
CLTF
0.998
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.028
MECLTFEXP_MEC->PJM
CLTF
0.587
LAGNLTFEXP_LAGN->PJM
CLTF
1.471
SIGELTFEXP_SIGE->PJM
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.117
CONTINGENCY 'EKPC_P7-1_LAURL 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
 OPEN BUS 342754                                   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P2-2_LAUR-LAURD161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-L DAM161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_LAUREL CO 161_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-2'
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P7-1_SPUR 345&138_SRT-A'
 OPEN BRANCH FROM BUS 958170 TO BUS 342838 CKT 1   /*AF2-111 TP   345.0 - 7SPURLOCK    345.0
 OPEN BRANCH FROM BUS 972166 TO BUS 342664 CKT 1   /*AH1-666 TP   138.0 - 4SPURLOCK    138.0
END
342718 to 324141 ckt 1

Light Load Analysis

The New Service Request AG2-424 was evaluated as a 63.25 MW injection and 15.0 MW withdrawal in the EKPC area.

AG2-424 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 63.25 MW (63.25 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
IPDEKPC
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
EKPC_P1-2_AG2-424 TP-2MAGNOLIA-69_SRT-A
SingleAC162.23 %39.0B63.27
63.25
IPDEKPC
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
EKPC_P2-2_KU HODG 69_SRT-A
BusAC155.72 %39.0B60.73
63.25
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
TowerAC153.06 %298.0B456.13
2.32
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-DEN161_SRT-A-1
SingleAC108.39 %298.0B323.01
0.95
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
SingleAC153.07 %210.0B321.45
0.95

Details for [AG2-424] 2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG2-424 TP-2MAGNOLIA-69_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG2-424 TP-2MAGNOLIA-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:162.23 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:63.27
MW Contribution:
63.25
IPD Plant:AG2-424
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG2-424 TP-2MAGNOLIA-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:161.89 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:63.14
MW Contribution:
63.25
IPD Plant:AG2-424
Bus #Bus NameTypeMW Contribution
970653AG2-424 GEN
PJM_IPD_GROUP
48.25
970653AG2-424 GEN
PJM_IPD_GROUP
15

Details for [AG2-424] 2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line l/o EKPC_P2-2_KU HODG 69_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_KU HODG 69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:155.72 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:60.73
MW Contribution:
63.25
IPD Plant:AG2-424
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:EKPC
Facility Description:
2SUMMERSVIL-2GREEN CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_KU HODG 69_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:155.37 %
Rating:39.0 MVA
Rating Type:B
MVA to Mitigate:60.59
MW Contribution:
63.25
IPD Plant:AG2-424
Bus #Bus NameTypeMW Contribution
970653AG2-424 GEN
PJM_IPD_GROUP
48.25
970653AG2-424 GEN
PJM_IPD_GROUP
15

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:153.06 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:456.13
MW Contribution:
2.32
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.284
970653AG2-424 GEN
Solar/Wind Harmer
1.484
970653AG2-424 GEN
Solar/Wind Harmer
0.839
972273AH1-721 GEN
50/50
363.396
971485AH1-239 GEN
Solar/Wind Harmer
7.898
964781AG1-341 GEN
Solar/Wind Harmer
6.731
964781AG1-341 GEN
Solar/Wind Harmer
3.702
964901AG1-354 GEN
Solar/Wind Harmer
8.603
950011AG9-010
External Queue
6.191452503204346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.887
WECLTFEXP_WEC->PJM
CLTF
0.064
MECLTFEXP_MEC->PJM
CLTF
0.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.67
CPLELTFEXP_CPLE->PJM
CLTF
0.144
LAGNLTFEXP_LAGN->PJM
CLTF
1.49
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.527
LGEELTFEXP_LGEE->PJM
CLTF
0.011
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.372
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.363
NYPJM->LTFIMP_NY
CLTF
0.058
TVALTFEXP_TVA->PJM
CLTF
0.929
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-DEN161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.39 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:323.01
MW Contribution:
0.95
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.14 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:641.11
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Helper
3.873
339231AF1-038_GEN
Solar/Wind Helper
3.388
339255AE2-071 GEN
Solar/Wind Helper
0.963
339250AF1-203 GEN
Solar/Wind Helper
0.55
970653AG2-424 GEN
50/50
Charging
0.95
339236AF1-050_GEN
Solar/Wind Helper
1.828
972273AH1-721 GEN
50/50
310.417
339241AF1-083 GEN
Solar/Wind Helper
1.908
VFTLTFEXP_VFT->PJM
CMTX
0.538
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.711
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.2
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.064
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.402
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.089
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.07 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:321.45
MW Contribution:
0.95
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:305.0 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:640.49
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
339206AE1-143 GEN
Solar/Wind Helper
3.854
339231AF1-038_GEN
Solar/Wind Helper
3.372
339255AE2-071 GEN
Solar/Wind Helper
0.958
339250AF1-203 GEN
Solar/Wind Helper
0.548
970653AG2-424 GEN
50/50
Charging
0.946
339236AF1-050_GEN
Solar/Wind Helper
1.819
972273AH1-721 GEN
50/50
308.935
339241AF1-083 GEN
Solar/Wind Helper
1.899
VFTLTFEXP_VFT->PJM
CMTX
0.535
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.703
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.631
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.199
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.064
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.4
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.088
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CONTINGENCY 'EKPC_P1-2_AG2-424 TP-2MAGNOLIA-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 970652 TO BUS 341800 CKT 1   /*AG2-424 TP    69.0 - 2MAGNOLIA     69.0
END
CONTINGENCY 'EKPC_P2-2_KU HODG 69_SRT-A'
 OPEN BUS 341632   /*2HODGENVILLE  69.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 3_SRT-A_SENS'
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 1   /*5ALCALDE     161.0 - AH1-721 TP   161.0
 OPEN BRANCH FROM BUS 324130 TO BUS 972272 CKT 2   /*5ALCALDE     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-DEN161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 2   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
342325 to 341563 ckt 1
342718 to 324141 ckt 1
972272 to 342718 ckt 1
972272 to 342718 ckt 2

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC188.48 %298.0B561.68
2.73
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC188.47 %298.0B561.64
2.73
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC188.47 %298.0B561.64
2.73
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC188.46 %298.0B561.62
2.73
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC188.26 %298.0B561.0
2.73
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC184.41 %298.0B549.53
2.73
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC179.86 %249.0A447.86
2.31
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOP-LAURD 161_SRT-A
BusAC176.44 %298.0B525.79
2.75
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-2
SingleAC172.34 %298.0B513.59
2.75
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_BULL 161 DBL_SRT-A
TowerAC155.49 %298.0B463.35
2.41

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:188.48 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:561.68
MW Contribution:
2.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.987
970653AG2-424 GEN
Solar/Wind Harmer
1.747
970653AG2-424 GEN
Solar/Wind Harmer
0.987
972273AH1-721 GEN
50/50
419.607
971485AH1-239 GEN
Solar/Wind Harmer
8.466
964781AG1-341 GEN
Solar/Wind Harmer
7.846
964781AG1-341 GEN
Solar/Wind Harmer
4.315
964901AG1-354 GEN
Solar/Wind Harmer
10.018
950011AG9-010
External Queue
7.131826877593994
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.885
NYPJM->LTFIMP_NY
CLTF
0.081
TVALTFEXP_TVA->PJM
CLTF
1.127
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.985
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.294
LGEELTFEXP_LGEE->PJM
CLTF
0.075
MECLTFEXP_MEC->PJM
CLTF
0.686
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.811
CPLELTFEXP_CPLE->PJM
CLTF
0.171
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.563
WECLTFEXP_WEC->PJM
CLTF
0.081
LAGNLTFEXP_LAGN->PJM
CLTF
1.809

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:188.47 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:561.64
MW Contribution:
2.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.967
970653AG2-424 GEN
Solar/Wind Harmer
1.742
970653AG2-424 GEN
Solar/Wind Harmer
0.985
972273AH1-721 GEN
50/50
418.878
971485AH1-239 GEN
Solar/Wind Harmer
8.437
964781AG1-341 GEN
Solar/Wind Harmer
7.822
964781AG1-341 GEN
Solar/Wind Harmer
4.302
964901AG1-354 GEN
Solar/Wind Harmer
9.989
950011AG9-010
External Queue
7.1139235496521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.521
WECLTFEXP_WEC->PJM
CLTF
0.081
LAGNLTFEXP_LAGN->PJM
CLTF
1.789
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.788
CPLELTFEXP_CPLE->PJM
CLTF
0.165
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.201
LGEELTFEXP_LGEE->PJM
CLTF
0.075
MECLTFEXP_MEC->PJM
CLTF
0.681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.868
NYPJM->LTFIMP_NY
CLTF
0.081
TVALTFEXP_TVA->PJM
CLTF
1.113
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.888

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:188.47 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:561.64
MW Contribution:
2.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.967
970653AG2-424 GEN
Solar/Wind Harmer
1.742
970653AG2-424 GEN
Solar/Wind Harmer
0.985
972273AH1-721 GEN
50/50
418.878
971485AH1-239 GEN
Solar/Wind Harmer
8.437
964781AG1-341 GEN
Solar/Wind Harmer
7.822
964781AG1-341 GEN
Solar/Wind Harmer
4.302
964901AG1-354 GEN
Solar/Wind Harmer
9.989
950011AG9-010
External Queue
7.1139235496521
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.201
LGEELTFEXP_LGEE->PJM
CLTF
0.075
MECLTFEXP_MEC->PJM
CLTF
0.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.521
WECLTFEXP_WEC->PJM
CLTF
0.081
LAGNLTFEXP_LAGN->PJM
CLTF
1.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.868
NYPJM->LTFIMP_NY
CLTF
0.081
TVALTFEXP_TVA->PJM
CLTF
1.113
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.888
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.788
CPLELTFEXP_CPLE->PJM
CLTF
0.165
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:188.46 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:561.62
MW Contribution:
2.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.967
970653AG2-424 GEN
Solar/Wind Harmer
1.742
970653AG2-424 GEN
Solar/Wind Harmer
0.985
972273AH1-721 GEN
50/50
418.878
971485AH1-239 GEN
Solar/Wind Harmer
8.437
964781AG1-341 GEN
Solar/Wind Harmer
7.822
964781AG1-341 GEN
Solar/Wind Harmer
4.302
964901AG1-354 GEN
Solar/Wind Harmer
9.989
950011AG9-010
External Queue
7.1139235496521
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.201
LGEELTFEXP_LGEE->PJM
CLTF
0.075
MECLTFEXP_MEC->PJM
CLTF
0.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.521
WECLTFEXP_WEC->PJM
CLTF
0.081
LAGNLTFEXP_LAGN->PJM
CLTF
1.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.868
NYPJM->LTFIMP_NY
CLTF
0.081
TVALTFEXP_TVA->PJM
CLTF
1.113
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.888
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.788
CPLELTFEXP_CPLE->PJM
CLTF
0.165
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:188.26 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:561.0
MW Contribution:
2.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.977
970653AG2-424 GEN
Solar/Wind Harmer
1.745
970653AG2-424 GEN
Solar/Wind Harmer
0.986
972273AH1-721 GEN
50/50
419.235
971485AH1-239 GEN
Solar/Wind Harmer
8.452
964781AG1-341 GEN
Solar/Wind Harmer
7.834
964781AG1-341 GEN
Solar/Wind Harmer
4.309
964901AG1-354 GEN
Solar/Wind Harmer
10.005
950011AG9-010
External Queue
7.124643802642822
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.8
CPLELTFEXP_CPLE->PJM
CLTF
0.168
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.878
NYPJM->LTFIMP_NY
CLTF
0.081
TVALTFEXP_TVA->PJM
CLTF
1.12
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.935
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.543
WECLTFEXP_WEC->PJM
CLTF
0.081
LAGNLTFEXP_LAGN->PJM
CLTF
1.799
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.25
LGEELTFEXP_LGEE->PJM
CLTF
0.075
MECLTFEXP_MEC->PJM
CLTF
0.684

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:184.41 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:549.53
MW Contribution:
2.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.987
970653AG2-424 GEN
Solar/Wind Harmer
1.747
970653AG2-424 GEN
Solar/Wind Harmer
0.987
972273AH1-721 GEN
50/50
419.607
971485AH1-239 GEN
Solar/Wind Harmer
8.466
964901AG1-354 GEN
Solar/Wind Harmer
10.018
950011AG9-010
External Queue
7.131826877593994
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.563
WECLTFEXP_WEC->PJM
CLTF
0.081
LAGNLTFEXP_LAGN->PJM
CLTF
1.809
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.811
CPLELTFEXP_CPLE->PJM
CLTF
0.171
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.294
LGEELTFEXP_LGEE->PJM
CLTF
0.075
MECLTFEXP_MEC->PJM
CLTF
0.686
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.885
NYPJM->LTFIMP_NY
CLTF
0.081
TVALTFEXP_TVA->PJM
CLTF
1.127
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.985

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.86 %
Rating:249.0 MVA
Rating Type:A
MVA to Mitigate:447.86
MW Contribution:
2.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.107
970653AG2-424 GEN
Solar/Wind Harmer
1.476
970653AG2-424 GEN
Solar/Wind Harmer
0.834
972273AH1-721 GEN
50/50
363.804
971485AH1-239 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
8.559
950011AG9-010
External Queue
6.188554286956787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.413
LGEELTFEXP_LGEE->PJM
CLTF
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.022
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.637
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.841
WECLTFEXP_WEC->PJM
CLTF
0.064
MECLTFEXP_MEC->PJM
CLTF
0.549
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.314
NYPJM->LTFIMP_NY
CLTF
0.059
TVALTFEXP_TVA->PJM
CLTF
0.915
SIGELTFEXP_SIGE->PJM
CLTF
0.017
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.64
CPLELTFEXP_CPLE->PJM
CLTF
0.137
LAGNLTFEXP_LAGN->PJM
CLTF
1.468

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOP-LAURD 161_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOP-LAURD 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:176.44 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:525.79
MW Contribution:
2.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
6
970653AG2-424 GEN
Solar/Wind Harmer
1.759
970653AG2-424 GEN
Solar/Wind Harmer
0.994
972273AH1-721 GEN
50/50
419.944
971485AH1-239 GEN
Solar/Wind Harmer
8.485
964781AG1-341 GEN
Solar/Wind Harmer
7.877
964781AG1-341 GEN
Solar/Wind Harmer
4.332
964901AG1-354 GEN
Solar/Wind Harmer
10.054
950011AG9-010
External Queue
7.131826877593994
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.709
WECLTFEXP_WEC->PJM
CLTF
0.096
LAGNLTFEXP_LAGN->PJM
CLTF
1.887
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.927
CPLELTFEXP_CPLE->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.81
LGEELTFEXP_LGEE->PJM
CLTF
0.102
MECLTFEXP_MEC->PJM
CLTF
0.751
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.445
NYPJM->LTFIMP_NY
CLTF
0.057
TVALTFEXP_TVA->PJM
CLTF
1.165
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.985

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.34 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:513.59
MW Contribution:
2.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
6
970653AG2-424 GEN
Solar/Wind Harmer
1.759
970653AG2-424 GEN
Solar/Wind Harmer
0.994
972273AH1-721 GEN
50/50
419.944
971485AH1-239 GEN
Solar/Wind Harmer
8.485
964901AG1-354 GEN
Solar/Wind Harmer
10.054
950011AG9-010
External Queue
7.131826877593994
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.927
CPLELTFEXP_CPLE->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.445
NYPJM->LTFIMP_NY
CLTF
0.057
TVALTFEXP_TVA->PJM
CLTF
1.165
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.985
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.709
WECLTFEXP_WEC->PJM
CLTF
0.096
LAGNLTFEXP_LAGN->PJM
CLTF
1.887
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.81
LGEELTFEXP_LGEE->PJM
CLTF
0.102
MECLTFEXP_MEC->PJM
CLTF
0.751

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_BULL 161 DBL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_BULL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:155.49 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:463.35
MW Contribution:
2.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.277
970653AG2-424 GEN
Solar/Wind Harmer
1.539
970653AG2-424 GEN
Solar/Wind Harmer
0.87
972273AH1-721 GEN
50/50
365.799
971485AH1-239 GEN
Solar/Wind Harmer
7.487
964781AG1-341 GEN
Solar/Wind Harmer
7.423
964781AG1-341 GEN
Solar/Wind Harmer
4.082
964901AG1-354 GEN
Solar/Wind Harmer
9.221
950011AG9-010
External Queue
6.476762294769287
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.301
NYPJM->LTFIMP_NY
CLTF
0.057
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.113
SIGELTFEXP_SIGE->PJM
CLTF
0.015
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.941
WECLTFEXP_WEC->PJM
CLTF
0.063
MECLTFEXP_MEC->PJM
CLTF
0.574
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.311
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.797
TVALTFEXP_TVA->PJM
CLTF
1.021
LAGNLTFEXP_LAGN->PJM
CLTF
1.625
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.073
CPLELTFEXP_CPLE->PJM
CLTF
0.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.269
CONTINGENCY 'EKPC_P2-2_LAUR-LAURD161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
 OPEN BUS 342754                                   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P7-1_LAURL 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P2-2_LAUREL CO 161_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-L DAM161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_COOP-LAURD 161_SRT-A'
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-2'
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P7-1_BULL 161 DBL_SRT-A'
 OPEN BUS 326975   /*5CEDAR GRV   161.0
 OPEN BUS 361788   /*5SUM SHAD TP 161.0
END
342718 to 324141 ckt 1

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests (projects) in PJM Transition Cycle 2, Cluster 79 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 79 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 79 projects will meet the dynamics requirements of the NERC, EKPC and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2028 summer peak load and light load cases, modified to include applicable projects. Cluster 79 projects have been dispatched online at maximum power output and the voltage schedule set to achieve near unity power factor at the high side of the main transformer.

Cluster 79 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 245 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

       a)       Steady-state operation;

       b)       Three-phase faults with normal clearing time;

       c)       Single-phase to ground bus faults with normal clearing time;

       d)       Single-phase to ground faults with delayed clearing due to a stuck breaker;

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure;

       f)       Single-phase faults with loss of multiple-circuit tower line.

       g)       Three-phase faults with normal clearing time and a failed high speed reclose attempt.

 

For all simulations, the Cluster 79 projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all of the fault contingencies tested on the 2028 summer peak load and light load cases:

       a)       Cluster 79 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 79 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

AG2-424 meets the 0.95 leading and lagging PF requirement.

 

AH1-721 meets the 0.95 leading and 0.90 lagging PF requirement.

 

No mitigations were found to be required.

 

Table 1: TC2 Cluster 79 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

79

AG2-424

Solar

Storage

EKPC

63.25

63.25

34.95

Mognolia – Summersville Tap 69 kV

AH1-721

Natural Gas

EKPC

786

786

758.9507

Laurel River Dam – Cooper 161 kV

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AG2-424 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-150Grassy Falls 138kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVEngineering & Procurement
AC1-214Crescent RidgeIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-029Circleville 138kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-176Jay 138 kVIn Service
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-143Marion County 161 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-089Pennville-Adams 138 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVUnder Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-342Woodstock 69 kVSuspended
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-038Sewellton Jct-Webbs Crossroads 69 kVUnder Construction
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-090Kincaid-PanaEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVWithdrawn
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVUnder Construction
AG1-017Jay 138 kVIn Service
AG1-047Jay 138 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-471Up Church-Wayne County 69 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-508Point Lookout 69 kVWithdrawn
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-348Pound 34.5 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-073Yankee 12.5kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15526
Title
Invalid - P2 contingency 69kV not monitored
Description
Per the LG&E/KU Planning Guidelines, 69kV is not monitored for P2 contingencies.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0004
Title
Reconductor of line & replacement of terminal equipment
Description
Reconductor of line & replacement of terminal equipment LG&E/KU ratings 104/132 MVA SP & 161/178 MVA WP
Total Cost ($USD)
$4,000,000
Allocated Cost ($USD)
$0
Time Estimate
0 to 36 Months

Info

Note: AG2-424 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
2GRENSBRG KU-2GREEN CO 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0013
Title
Invalid - common mode contingency over 69 kV addressed by load shedding or generation redispatch
Description
LG&E/KU planning guidelines permit redispatch of generation or 5% load shedding to resolve overload for the contingency category
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
4LEBANON-4MARION CO 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15524
Title
Load shedding of 10% PC load is allowed for P7 contingency
Description
Load shedding of 10% PC load is allowed for P7 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15525
Title
Load shedding of 10% PC load is allowed for P4 contingency
Description
Load shedding of 10% PC load is allowed for P4 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending)
Title
Load shedding of 10% PC load is allowed for P2 contingency
Description
Load shedding of 10% PC load is allowed for P2 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0003
Title
Replacing all terminal equipment at Elihu
Description
Replacing all terminal equipment at Elihu LG&E/KU rating is 219/277 MVA SP & 335/368 MVA WP, flow would require replacement of all terminal equipment at Elihu. $1,000,000 24months
Total Cost ($USD)
$1,000,000
Allocated Cost ($USD)
$0
Time Estimate
0 to 24 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 may need this upgrade in-service to be deliverable to the PJM system. If AG2-424 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending)
Title
LGEE Summer 219/277 MVA & winter 335/335 MVA Rate A/Rate B
Description
LGEE Summer 219/277 MVA & winter 335/335 MVA Rate A/Rate B
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Louisville Gas & Electric (LG&E)Study Pending
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-424 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
EKPCn6834.1Rebuild the 4/0 ACSR Green County-Summersville 69 kV line section (4.2 miles) using 556 MCM ACSR.Cost Allocated$4,678,715N/A
EKPCn9745.0Green County-Summersville 69 kV Line Section Rebuild #2 (266.8 MCM ACSR section)Cost Allocated$120,000N/A
EKPCn9743.0Cooper CCGT-Alcalde 161 kV Double-Circuit Line AdditionCost Allocated$6,656N/A
AEPb4068.1b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570Contingent$0N/A
AEPb3919.1Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yardContingent$0N/A
EKPCn8368.3Change the Zone 3 relay setting at Elihu substation associated with the line protection to at least 545 MVA LTE rating.Contingent$0N/A
EKPCn8368.2Rebuild the Cooper-Elihu 161 kV line section using 1272 MCM ACSS conductor (4.2 miles)Contingent$0N/A
EKPCn8368.4Upgrade the existing 795 MCM ACSR jumpers at the Cooper substation associated with the Cooper-Elihu 161 kV line using bundled 500 MCM CU or equivalentContingent$0N/A
EKPCn8368.5Cooper-Elihu 161 kV Current Transformer UpgradeContingent$0N/A
EKPCn9780.0Cooper-Elihu 161 kV Relay UpgradeContingent$0N/A
EKPCn9781.0Cooper-Elihu 161 kV Bus Conductor UpgradeContingent$0N/A
EKPCn9687.10Cooper 161kV breaker replacements - Breaker 1044 ELIHUContingent$0N/A
Grand Total:$4,805,371

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n6834.1
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n6834.1 / EKPC-tc1-r0001a
Title
Rebuild the 4/0 ACSR Green County-Summersville 69 kV line section (4.2 miles) using 556 MCM ACSR.
Description
Rebuild the 4/0 ACSR Green County-Summersville 69 kV line section (4.2 miles) using 556 MCM ACSR.
Total Cost ($USD)
$5,705,000
Discounted Total Cost ($USD)
$5,705,000
Allocated Cost ($USD)
$4,678,715
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A57.0 MVA
(All)B63.0 MVA
(All)C63.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-2981.7 MW2.2%$127,897
AG2-42463.2 MW82.0%$4,678,715
AH1-72112.1 MW15.7%$898,387

System Reinforcement: n9745.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9745.0 / EKPC-tc2-nu014
Title
Green County-Summersville 69 kV Line Section Rebuild #2 (266.8 MCM ACSR section)
Description
Rebuild the 266.8 MCM ACSR Green County-Summersville 69 kV line section (0.1 miles) using 556 MCM ACSR.
Total Cost ($USD)
$120,000
Discounted Total Cost ($USD)
$120,000
Allocated Cost ($USD)
$120,000
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
2GREEN CO-2SUMMERSVIL 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A58.0 MVA
(All)B68.0 MVA
(All)C71.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-42463.2 MW100.0%$120,000

System Reinforcement: n9743.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9743.0 / EKPC-tc2-nu003
Title
Cooper CCGT-Alcalde 161 kV Double-Circuit Line Addition
Description
Construct a new double-circuit 161 kV line between EKPC's new Cooper CCGT substation and the LG&E/KU Alcalde substation (approximate length of 5 miles) using 1272 MCM ACSS conductor.
Total Cost ($USD)
$20,130,000
Discounted Total Cost ($USD)
$20,130,000
Allocated Cost ($USD)
$6,656
Time Estimate
22 to 36 Months

ContributorTopology Changing

Note: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement. Hence, this project is receiving a cost allocation based on its MW contribution to the need for this topology changing reinforcement but at a reduced amount considering the other reinforcements that were able to be eliminated. This project's cost allocation is based on the pro rata share of the MW impacts from all cost allocated contributors multiplied by the relevant regional discount factor listed in the executive summary report.

FacilityContingency
(Any)EKPC_P1-2_COOP-LAUREL161_SRT-A-1
No new ratings for this Flowgate.
(Any)EKPC_P1-2_COOP-LAUREL161_SRT-A-2
No new ratings for this Flowgate.
(Any)EKPC_P1-2_COOP-DEN161_SRT-A-1
No new ratings for this Flowgate.
(Any)EKPC_P2-2_COOP-LAURD 161_SRT-A
No new ratings for this Flowgate.
(Any)EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
No new ratings for this Flowgate.
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 lineEKPC_P2-3_SSHAD S11-1044_SRT-A
No new ratings for this Flowgate.
5COOPER2-AH1-721 TP 161.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
5COOPER2-AH1-721 TP 161.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-4243.1 MW0.0%$6,656
AH1-239260.5 MW2.8%$555,851
AH1-7219169.1 MW97.2%$19,567,493

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 may need this upgrade in-service to be deliverable to the PJM system. If AG2-424 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
2LORETTO-AG2-298 TP 69.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 may need this upgrade in-service to be deliverable to the PJM system. If AG2-424 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
2LORETTO-AG2-298 TP 69.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9769.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9769.0 / AEP-TC2-19070
Title
05CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBs
Description
Upgrade/replace Cloverdale 765 kV, 4000 A CBs "CC" and "CC2" to 5000 A
Total Cost ($USD)
$25,000,000
Discounted Total Cost ($USD)
$25,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 is a potential Aggregate Pool Contributor.

FacilityContingency
05CLOVRD-05CLOVRD_RJA 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: n9763.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9763.0 / AEP-TC2-19060
Title
05J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace Wavetraps
Description
Replace wave trap on 765 kV Cloverdale line. Replace/upgrade CB's B and B2 with 5000A CBs.
Total Cost ($USD)
$3,300,000
Discounted Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 is a potential Aggregate Pool Contributor.

FacilityContingency
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: n9759.0
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
n9759.0 / OVEC-TC2-19030
Title
06KYGER 345.0 kV to 05SPORN 345.0 kV ckt 1 - Replace Equipment
Description
Sag study Sporn - Kyger Creek line and replace section #25 OVEC element conductor 12.51 Miles At Sporn replace the following equipment: 2 - 2000 KCM AAC, 91-Str., AA1S1, AA1S2, AAS1, AAS2, KYGER CREEK #1 - PH A, KYGER CREEK #1 - PH B At Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB
Total Cost ($USD)
$38,180,000
Discounted Total Cost ($USD)
$38,180,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1942.0 MVA
(All)B2837.0 MVA
LLA1942.0 MVA
LLB2837.0 MVA

System Reinforcement: n9753.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9753.0 / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Discounted Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1944.0 MVA
(All)B2825.0 MVA
(All)C2468.0 MVA

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Apr 03 2028

Not Contingent

Note: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-424 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-424 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu901
Title
Green County-Greensburg KU 69 kV Line Section EKPC Limit
Description
No EKPC upgrade required. EKPC summer Rate B is 114 MVA.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
1 Months

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2GRENSBRG KU-2GREEN CO 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A109.0 MVA
(All)B114.0 MVA
(All)C115.0 MVA

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0005a
Title
LGEE violation (non PJM area). EKPC emergency rating at 54 MVA The externa [...] Owner, LGEE, will not evaluate this violation until the impact study phase.
Description
LGEE violation (non PJM area). EKPC emergency rating at 54 MVA The external (i.e. Non-PJM) Transmission Owner, LGEE, will not evaluate this violation until the impact study phase.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2SPRINGFL KU-2N SPRINGFLD 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A49.0 MVA
(All)B54.0 MVA
(All)C54.0 MVA

System Reinforcement: n9777.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9777.0 / EKPC-tc2-nu055
Title
Cooper-AH1-721 (East Cooper) Circuit #2 161 kV Zone 3 Setting Upgrade
Description
Increase the Zone 3 relay setting at Cooper substation associated with the Cooper-AH1-721 (East Cooper) 161 kV Circuit #2 (formerly the Cooper-Denny line) to at least 387 MVA.
Total Cost ($USD)
$10,000
Discounted Total Cost ($USD)
$10,000
Allocated Cost ($USD)
$0
Time Estimate
9 to 12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 is a potential Aggregate Pool Contributor.

FacilityContingency
5COOPER2-AH1-721 TP 161.0 kV Ckt 2 line(Any)
Rating SetRating TypeRating Value
LLA186.0 MVA
LLB210.0 MVA
LLC210.0 MVA
SUMA186.0 MVA
SUMB210.0 MVA
SUMC210.0 MVA
WINA343.0 MVA
WINB355.0 MVA
WINC355.0 MVA

System Reinforcement: n9775.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9775.0 / EKPC-tc2-nu056
Title
Cooper-AH1-721 Tap (East Cooper) 161 kV Circuit #2 Rebuild (0.5 miles)
Description
Rebuild the Cooper-AH1-721 Tap (East Cooper) 161 kV Circuit #2 (formerly the Cooper-Denny line) line section (0.5 miles) using 954 ACSR conductor.
Total Cost ($USD)
$1,215,000
Discounted Total Cost ($USD)
$1,215,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 is a potential Aggregate Pool Contributor.

FacilityContingency
5COOPER2-AH1-721 TP 161.0 kV Ckt 2 line(Any)
Rating SetRating TypeRating Value
LLA268.0 MVA
LLB345.0 MVA
LLC390.0 MVA
SUMA268.0 MVA
SUMB345.0 MVA
SUMC390.0 MVA
WINA387.0 MVA
WINB399.0 MVA
WINC399.0 MVA

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0012a
Title
LGE/KU is limiting this facility. EKPC emergency rating is 298 MVA.
Description
LGE/KU is limiting this facility (LGEE Summer 219/277 MVA & winter 335/335 MVA Rate A/Rate B). EKPC emergency rating is 298 MVA. LGEE AFS for TC1 has determined they will not require an reinforcement and thus EKPC existing 298 MVA Rate B is adequate as LGEE is the limiting element of the line.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA267.0 MVA
SUMB298.0 MVA
SUMC298.0 MVA

System Reinforcement: n8368.3
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.3 / EKPC-tc1-r0012c
Title
Change the Zone 3 relay setting at Elihu substation associated with the line protection to at least 545 MVA LTE rating.
Description
Change the Zone 3 relay setting at Elihu substation associated with the line protection to at least 545 MVA LTE rating.
Total Cost ($USD)
$10,000
Discounted Total Cost ($USD)
$10,000
Allocated Cost ($USD)
$0
Time Estimate
9 to 12 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 may need this upgrade in-service to be deliverable to the PJM system. If AG2-424 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A325.0 MVA
(All)B381.0 MVA
(All)C390.0 MVA

System Reinforcement: n8368.2
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.2 / EKPC-tc1-r0012b
Title
Rebuild the Cooper-Elihu 161 kV line section using 1272 MCM ACSS conductor (4.2 miles)
Description
Rebuild the Cooper-Elihu 161 kV line section using 1272 MCM ACSS conductor (4.2 miles).
Total Cost ($USD)
$10,335,000
Discounted Total Cost ($USD)
$10,335,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 27 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 may need this upgrade in-service to be deliverable to the PJM system. If AG2-424 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A362.0 MVA
(All)B373.0 MVA
(All)C373.0 MVA

System Reinforcement: n8368.4
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.4 / EKPC-tc1-r0012d
Title
Upgrade the existing 795 MCM ACSR jumpers at the Cooper substation associated with the Cooper-Elihu 161 kV line using bundled 500 MCM CU or equivalent
Description
Upgrade the existing 795 MCM ACSR jumpers at the Cooper substation associated with the Cooper-Elihu 161 kV line using bundled 500 MCM CU or equivalent
Total Cost ($USD)
$35,000
Discounted Total Cost ($USD)
$35,000
Allocated Cost ($USD)
$0
Time Estimate
9 to 12 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 may need this upgrade in-service to be deliverable to the PJM system. If AG2-424 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A344.0 MVA
(All)B383.0 MVA
(All)C390.0 MVA

System Reinforcement: n8368.5
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.5 / EKPC-r0117d
Title
Cooper-Elihu 161 kV Current Transformer Upgrade
Description
Upgrade the 1200A current transformer at the Cooper substation associated with the Cooper-Elihu 161 kV line with a 2000A current transformer.
Total Cost ($USD)
$135,000
Discounted Total Cost ($USD)
$135,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 15 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 may need this upgrade in-service to be deliverable to the PJM system. If AG2-424 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA359.0 MVA
LLB437.0 MVA
LLC476.0 MVA
SUMA359.0 MVA
SUMB437.0 MVA
SUMC476.0 MVA
WINA468.0 MVA
WINB501.0 MVA
WINC501.0 MVA

System Reinforcement: n9780.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9780.0 / EKPC-tc2-nu052
Title
Cooper-Elihu 161 kV Relay Upgrade
Description
Upgrade the relays at Cooper Station associated with the Cooper-Elihu 161 kV line to provide thermal capability of at least 2000A capability
Total Cost ($USD)
$55,000
Discounted Total Cost ($USD)
$55,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 15 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 may need this upgrade in-service to be deliverable to the PJM system. If AG2-424 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA408.0 MVA
LLB517.0 MVA
LLC525.0 MVA
SUMA408.0 MVA
SUMB517.0 MVA
SUMC525.0 MVA
WINA544.0 MVA
WINB654.0 MVA
WINC660.0 MVA

System Reinforcement: n9781.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9781.0 / EKPC-tc2-nu051
Title
Cooper-Elihu 161 kV Bus Conductor Upgrade
Description
Upgrade the 1.5" IPS aluminum bus conductor at Cooper Station associated with the Cooper-Elihu 161 kV line with at least 2" IPS aluminum bus conductor.
Total Cost ($USD)
$990,000
Discounted Total Cost ($USD)
$990,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 15 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 may need this upgrade in-service to be deliverable to the PJM system. If AG2-424 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA408.0 MVA
LLB501.0 MVA
LLC501.0 MVA
SUMA408.0 MVA
SUMB501.0 MVA
SUMC501.0 MVA
WINA468.0 MVA
WINB501.0 MVA
WINC501.0 MVA

System Reinforcement: n9687.10
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9687.10 / EKPC-tc2-nu053
Title
Cooper 161kV breaker replacements - Breaker 1044 ELIHU
Description
Cooper 161kV breaker replacements - Breaker 1044 ELIHU - replace with 63kA breaker
Total Cost ($USD)
$335,000
Discounted Total Cost ($USD)
$335,000
Allocated Cost ($USD)
$0
Time Estimate
Dec 01 2029

Contingent

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 may need this upgrade in-service to be deliverable to the PJM system. If AG2-424 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA408.0 MVA
LLB545.0 MVA
LLC545.0 MVA
SUMA408.0 MVA
SUMB545.0 MVA
SUMC545.0 MVA
WINA529.0 MVA
WINB545.0 MVA
WINC545.0 MVA

System Reinforcement: n9776.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9776.0 / EKPC-tc2-nu054
Title
Cooper-AH1-721 Tap (East Cooper) 161 kV Circuit #1 Rebuild (0.5 miles)
Description
Rebuild the Cooper-AH1-721 Tap (East Cooper) 161 kV Circuit #1 (formerly the Cooper-Laurel Dam line) line section (0.5 miles) using 954 ACSR conductor.
Total Cost ($USD)
$1,215,000
Discounted Total Cost ($USD)
$1,215,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-424 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-424 could receive cost allocation. Although AG2-424 may not presently have cost responsibility for this upgrade, AG2-424 is a potential Aggregate Pool Contributor.

FacilityContingency
5COOPER2-AH1-721 TP 161.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA268.0 MVA
LLB345.0 MVA
LLC391.0 MVA
SUMA268.0 MVA
SUMB345.0 MVA
SUMC391.0 MVA
WINA417.0 MVA
WINB448.0 MVA
WINC448.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-424


AG2-424 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowEKPCn9743.0 / EKPC-tc2-nu003Cooper CCGT-Alcalde 161 kV Double-Circuit Line AdditionTopology3.1 MW0.0%Cost Allocated$6,656
Load FlowAEPb4068.1 / AEP-TC2-18693b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570Topology-0.0%Contingent$0
Load FlowAEPb3919.1Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yardTopology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$6,656
AG2-424 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-424 One Line Diagram

AG2-424 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.