AG2-448 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:22

Cross School - Westvaco 138 kV

30.0 MW Capacity / 50.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Potomac Hills Energy, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is The Potomac Edison Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $23,074,066 $40,642,387 = 0.57 AND ( $23,074,066 - $40,642,387 ) 50.0 = $-351,366 per MW

General

The Project Developer has proposed a Solar generating facility located in the The Potomac Edison Company zone — Mineral County, West Virginia. The installed facilities will have a total capability of 50.0 MW with 30.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-448
Project Name:
Cross School - Westvaco 138 kV
Project Developer Name:
Potomac Hills Energy, LLC
State:
West Virginia
County:
Mineral
Transmission Owner:
The Potomac Edison Company
MFO:
50.0
MWE:
50.0
MWC:
30.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-448 will interconnect on the The Potomac Edison Company transmission system by tapping the Cross School - Westvaco 138 kV line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-448 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-448Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$1,587,454$0$0
Other Scope$517,528$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$14,774,786$14,774,786$14,774,786
Network Upgrades$8,299,280$8,299,280$8,299,280
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$25,179,048$23,074,066$23,074,066

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-448

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-448
Project ID: AG2-448
20% of cost allocation for Phase II Network Upgrades:(A) $4,614,813
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $4,064,239
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $550,574
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Revise relay settings at Westvaco Substation.

$48,297$0$2,571$0$50,868$50,868
(Pending)

Decommission Beryl asset by removing disconnect switches, PTs, relays, structures, foundations, and fence to facilitate new cut/loop of the Kitzmiller-Cross School 138 kV Line.

$402,215$0$21,408$0$423,623$423,623
(Pending)

Cut the Kitzmiller - Cross School 138kV Line between structures 13 and 14. The line coming from Westvaco to enter the new AG2-448 four (4) breaker ring bus interconnection substation as a new line exit and will become the Westvaco - AG2-448 138kV Line. Cut the Kitzmiller - Cross School 138kV Line at the Beryl switchyard. After Beryl is decommissioned, the transmission group will cut and loop the existing Kitzmiller - Cross School 138kV Line between structures 270 and 271 to create two new circuits: Kitzmiller - AG2-448 138kV Line and the AG2-448 - Cross School 138kV Line. Rebuild the two (2) new circuits (Kitzmiller - AG2-448 138kV Line and the AG2-448 - Cross School 138kV Line) in the existing Beryl-Westvaco 138kV Line corridor and replace structures 1 through 12 with new double circuit structures. Both the new Kitzmiller - AG2-448 138kV Line and the new AG2-448 - Cross School 138kV Line to have their own line exit terminals in the new AG2-448 four (4) breaker ring bus interconnection substation. The approximate distance of the new rebuild is 1.4 miles.

$5,393,869$1,408,740$287,089$117,295$7,206,993$7,206,993
(Pending)

Install new relays and revise relay settings at Cross School Substation.

$441,922$49,421$23,521$1,196$516,060$516,060
(Pending)

Revise relay settings at Mt. Zion Substation.

$48,297$0$2,571$0$50,868$50,868
(Pending)

Revise relay settings at Kitzmiller Substation.

$48,297$0$2,571$0$50,868$50,868
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Provide revenue metering panel within new AG2-448 Control House. Install and integrate revenue metering to interconnection substation. Provide new 3-phase 138kV free-standing CT/VT combo units.

$311,540$184,931$16,582$4,475$517,528$517,528
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install and test new 96F/SM and 48F/SM ADSS cables to accommodate AG2-448 generator interconnection.

$1,736,418$217,526$92,421$5,264$2,051,629$2,051,629
(Pending)

Construct a new 138 kV four (4) breaker ring bus interconnection substation.

$7,825,002$3,804,945$416,486$96,459$12,142,892$12,142,892
(Pending)

Design, install, and test/commission MPLS equipment for SCADA transport at AG2-448 interconnection substation.

$370,747$128,649$19,733$3,113$522,242$522,242
(Pending)

Install fiber run from AG2-448 interconnection substation control house to Project Developer-built fiber run to support communications and control to generator site.

$52,543$2,620$2,797$63$58,023$58,023
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Integrate Interconnection Facilities protection and controls to the Transmission Owner system.

$48,297$0$2,571$0$50,868$50,868
(Pending)

Install line terminal equipment within the AG2-448 interconnection substation. Install one (1) span from AG2-448 interconnection substation to the Project Developer-owned dead-end structure outside of substation fence.

$1,037,392$431,743$55,215$12,236$1,536,586$1,536,586
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Revise relay settings at Westvaco Substation.

$48,297$0$2,571$0$50,868$50,868
(Pending)

Decommission Beryl asset by removing disconnect switches, PTs, relays, structures, foundations, and fence to facilitate new cut/loop of the Kitzmiller-Cross School 138 kV Line.

$402,215$0$21,408$0$423,623$423,623
(Pending)

Cut the Kitzmiller - Cross School 138kV Line between structures 13 and 14. The line coming from Westvaco to enter the new AG2-448 four (4) breaker ring bus interconnection substation as a new line exit and will become the Westvaco - AG2-448 138kV Line. Cut the Kitzmiller - Cross School 138kV Line at the Beryl switchyard. After Beryl is decommissioned, the transmission group will cut and loop the existing Kitzmiller - Cross School 138kV Line between structures 270 and 271 to create two new circuits: Kitzmiller - AG2-448 138kV Line and the AG2-448 - Cross School 138kV Line. Rebuild the two (2) new circuits (Kitzmiller - AG2-448 138kV Line and the AG2-448 - Cross School 138kV Line) in the existing Beryl-Westvaco 138kV Line corridor and replace structures 1 through 12 with new double circuit structures. Both the new Kitzmiller - AG2-448 138kV Line and the new AG2-448 - Cross School 138kV Line to have their own line exit terminals in the new AG2-448 four (4) breaker ring bus interconnection substation. The approximate distance of the new rebuild is 1.4 miles.

$5,393,869$1,408,740$287,089$117,295$7,206,993$7,206,993
(Pending)

Install new relays and revise relay settings at Cross School Substation.

$441,922$49,421$23,521$1,196$516,060$516,060
(Pending)

Revise relay settings at Mt. Zion Substation.

$48,297$0$2,571$0$50,868$50,868
(Pending)

Revise relay settings at Kitzmiller Substation.

$48,297$0$2,571$0$50,868$50,868
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight of Project Developer design and construction of new interconnection substation.

$1,281,840$0$68,279$0$1,350,119$1,350,119
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Provide revenue metering panel within new AG2-448 Control House. Install and integrate revenue metering to interconnection substation. Provide new 3-phase 138kV free-standing CT/VT combo units.

$311,540$184,931$16,582$4,475$517,528$517,528
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install and test new 96F/SM and 48F/SM ADSS cables to accommodate AG2-448 generator interconnection.

$1,736,418$217,526$92,421$5,264$2,051,629$2,051,629
(Pending)

Design, install, and test/commission MPLS equipment for SCADA transport at AG2-448 interconnection substation.

$370,747$128,649$19,733$3,113$522,242$522,242
(Pending)

Install one (1) security system and camera system. Install one (1) indoor security AC cabinet. Install one (1) network fiber termination rack.

$1,673,828$262,676$89,089$6,357$2,031,950$2,031,950
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Integrate Interconnection Facilities protection and controls to the Transmission Owner system.

$48,297$0$2,571$0$50,868$50,868
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$25,179,048$25,179,048
Developer Build Option$14,823,616$14,823,616

Based on the scope of work for the Interconnection Facilities, it is expected to take 38 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV. New Service Request Project AG2-448 did not contribute to any overloads on the FE transmission <100 kV system.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-448 was evaluated as a 50.0 MW (30.0 MW Capacity) injection in the APS area.

AG2-448 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 50.0 MW (50.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC155.12 %206.0B319.54
25.38
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC151.46 %206.0B312.0
25.38
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-2
SingleAC140.5 %206.0B289.42
20.86
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-1
SingleAC136.99 %206.0B282.21
20.86
IPDAP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC135.62 %206.0B279.37
34.77
IPDAP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-2
SingleAC135.52 %206.0B279.18
34.77
IPDAP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-1
SingleAC131.1 %206.0B270.06
34.77
IPDAP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC131.1 %206.0B270.06
34.77
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P7-1_PE-138-012A_SRT-A
TowerAC113.83 %206.0B234.49
25.61
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT9_SRT-SL
BusAC110.26 %206.0B227.14
25.79
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT22_SRT-SL
BreakerAC110.26 %206.0B227.13
25.79
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_MP-138-206_SRT-A
BreakerAC108.81 %206.0B224.14
25.79
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT11_SRT-SL
BusAC104.91 %206.0B216.12
25.79
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-4_MP-138-162_SRT-A
BreakerAC103.66 %206.0B213.54
25.75
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P7-1_MP-138-058_SRT-A
TowerAC103.66 %206.0B213.54
25.75
IPDAP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Base Case
SingleAC101.75 %164.0A166.86
35.47
GD2AP
01BLACKO-01BLACKO 138.0/500.0 kV Ckt 3 transformer
AP_P2-3_PE-500-014_SRT-SL
BreakerAC100.96 %558.0B563.37
14.45
GD2AP
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC124.46 %268.0B333.56
25.38
GD2AP
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC121.67 %268.0B326.07
25.38
IPDAP
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC107.71 %268.0B288.66
34.76
IPDAP
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-2
SingleAC107.59 %268.0B288.35
34.76
GD2AP
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-2
SingleAC105.55 %268.0B282.88
20.86
IPDAP
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-1
SingleAC104.18 %268.0B279.19
34.77
IPDAP
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC104.18 %268.0B279.19
34.77
GD2AP
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-1
SingleAC102.75 %268.0B275.38
20.86

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.12 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:319.54
MW Contribution:
25.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.971
23750701CROSSCHOOL
Solar/Wind Helper
3.116
970697AG2-448 GEN
Solar/Wind Harmer
25.379
238185AF2-356 C
Solar/Wind Harmer
24.308
970935AG2-582 GEN
Adder
11.589
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.968
LGEELTFEXP_LGEE->PJM
CLTF
0.173
TVALTFEXP_TVA->PJM
CLTF
0.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.649
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.664
WECLTFEXP_WEC->PJM
CLTF
0.1
MECLTFEXP_MEC->PJM
CLTF
0.403
NYPJM->LTFIMP_NY
CLTF
0.148
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.46 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:312.0
MW Contribution:
25.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.973
23750701CROSSCHOOL
Solar/Wind Helper
3.116
970697AG2-448 GEN
Solar/Wind Harmer
25.381
238185AF2-356 C
Solar/Wind Harmer
24.311
964991AG1-363 GEN
Solar/Wind Helper
1.775
970935AG2-582 GEN
Adder
11.711
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.047
LGEELTFEXP_LGEE->PJM
CLTF
0.176
TVALTFEXP_TVA->PJM
CLTF
0.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.669
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.736
WECLTFEXP_WEC->PJM
CLTF
0.102
MECLTFEXP_MEC->PJM
CLTF
0.413
NYPJM->LTFIMP_NY
CLTF
0.145
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.5 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:289.42
MW Contribution:
20.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750701CROSSCHOOL
Solar/Wind Helper
3.116
970697AG2-448 GEN
Solar/Wind Harmer
20.86
238185AF2-356 C
Solar/Wind Harmer
0
970935AG2-582 GEN
Adder
11.589
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.968
LGEELTFEXP_LGEE->PJM
CLTF
0.173
TVALTFEXP_TVA->PJM
CLTF
0.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.649
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.664
WECLTFEXP_WEC->PJM
CLTF
0.1
MECLTFEXP_MEC->PJM
CLTF
0.403
NYPJM->LTFIMP_NY
CLTF
0.148
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.99 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:282.21
MW Contribution:
20.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750701CROSSCHOOL
Solar/Wind Helper
3.116
970697AG2-448 GEN
Solar/Wind Harmer
20.861
238185AF2-356 C
Solar/Wind Harmer
0
964991AG1-363 GEN
Solar/Wind Helper
1.775
970935AG2-582 GEN
Adder
11.711
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.047
LGEELTFEXP_LGEE->PJM
CLTF
0.176
TVALTFEXP_TVA->PJM
CLTF
0.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.669
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.736
WECLTFEXP_WEC->PJM
CLTF
0.102
MECLTFEXP_MEC->PJM
CLTF
0.413
NYPJM->LTFIMP_NY
CLTF
0.145
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for [AG2-448] 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.62 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:279.37
MW Contribution:
34.77
IPD Plant:AG2-448
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
PJM_IPD
34.766

Details for [AG2-448] 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.52 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:279.18
MW Contribution:
34.77
IPD Plant:AG2-448
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
PJM_IPD
34.766

Details for [AG2-448] 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.1 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:270.06
MW Contribution:
34.77
IPD Plant:AG2-448
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
PJM_IPD
34.769

Details for [AG2-448] 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.1 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:270.06
MW Contribution:
34.77
IPD Plant:AG2-448
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
PJM_IPD
34.769

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P7-1_PE-138-012A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_PE-138-012A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.83 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:234.49
MW Contribution:
25.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23562501BACKB
Solar/Wind Harmer
1.263
238118U2-030_1
Solar/Wind Harmer
0.479
23750501ELLIOTTS
Solar/Wind Harmer
1.152
238126S14_GEN_1
Solar/Wind Helper
0.523
23751201ROTHROCK
Solar/Wind Harmer
1.038
238127S14_GEN_2
Solar/Wind Helper
0.523
970075AG2-062 GEN
Solar/Wind Harmer
3.791
23750701CROSSCHOOL
Solar/Wind Helper
3.05
238117U2-030
Solar/Wind Harmer
1.14
970697AG2-448 GEN
Solar/Wind Harmer
25.614
238185AF2-356 C
Solar/Wind Harmer
24.72
238193AE1-106 GEN
Solar/Wind Harmer
5.342
238120AE2-309 GEN
Solar/Wind Helper
0.283
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.907
LGEELTFEXP_LGEE->PJM
CLTF
0.126
TVALTFEXP_TVA->PJM
CLTF
0.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.465
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
LAGNLTFEXP_LAGN->PJM
CLTF
0.228
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.922
WECLTFEXP_WEC->PJM
CLTF
0.073
MECLTFEXP_MEC->PJM
CLTF
0.293
NYPJM->LTFIMP_NY
CLTF
0.09
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.007
SIGELTFEXP_SIGE->PJM
CLTF
0.009

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT9_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT9_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.26 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:227.14
MW Contribution:
25.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.95
23751201ROTHROCK
Solar/Wind Harmer
0.889
23750701CROSSCHOOL
Solar/Wind Helper
2.995
970697AG2-448 GEN
Solar/Wind Harmer
25.785
238185AF2-356 C
Solar/Wind Harmer
24.708
970935AG2-582 GEN
Adder
11.874
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.604
NYPJM->LTFIMP_NY
CLTF
0.189
TVALTFEXP_TVA->PJM
CLTF
0.186
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.74
WECLTFEXP_WEC->PJM
CLTF
0.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.376
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.828
LGEELTFEXP_LGEE->PJM
CLTF
0.169
MECLTFEXP_MEC->PJM
CLTF
0.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.198
CPLELTFEXP_CPLE->PJM
CLTF
0.009
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT22_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT22_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.26 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:227.13
MW Contribution:
25.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.95
23751201ROTHROCK
Solar/Wind Harmer
0.889
23750701CROSSCHOOL
Solar/Wind Helper
2.995
970697AG2-448 GEN
Solar/Wind Harmer
25.785
238185AF2-356 C
Solar/Wind Harmer
24.708
970935AG2-582 GEN
Adder
11.874
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.604
NYPJM->LTFIMP_NY
CLTF
0.189
TVALTFEXP_TVA->PJM
CLTF
0.186
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.74
WECLTFEXP_WEC->PJM
CLTF
0.094
LAGNLTFEXP_LAGN->PJM
CLTF
0.376
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.828
LGEELTFEXP_LGEE->PJM
CLTF
0.169
MECLTFEXP_MEC->PJM
CLTF
0.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.198
CPLELTFEXP_CPLE->PJM
CLTF
0.009
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_MP-138-206_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-138-206_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.81 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:224.14
MW Contribution:
25.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.951
23751201ROTHROCK
Solar/Wind Harmer
0.889
23750701CROSSCHOOL
Solar/Wind Helper
2.995
970697AG2-448 GEN
Solar/Wind Harmer
25.786
238185AF2-356 C
Solar/Wind Harmer
24.709
970935AG2-582 GEN
Adder
11.913
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.629
NYPJM->LTFIMP_NY
CLTF
0.188
TVALTFEXP_TVA->PJM
CLTF
0.188
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.747
WECLTFEXP_WEC->PJM
CLTF
0.095
LAGNLTFEXP_LAGN->PJM
CLTF
0.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.851
LGEELTFEXP_LGEE->PJM
CLTF
0.17
MECLTFEXP_MEC->PJM
CLTF
0.397
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.203
CPLELTFEXP_CPLE->PJM
CLTF
0.011
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT11_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT11_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.91 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:216.12
MW Contribution:
25.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.952
23751201ROTHROCK
Solar/Wind Harmer
0.89
23750701CROSSCHOOL
Solar/Wind Helper
2.994
970697AG2-448 GEN
Solar/Wind Harmer
25.788
238185AF2-356 C
Solar/Wind Harmer
24.712
970935AG2-582 GEN
Adder
12.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.7
NYPJM->LTFIMP_NY
CLTF
0.185
TVALTFEXP_TVA->PJM
CLTF
0.193
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.765
WECLTFEXP_WEC->PJM
CLTF
0.097
LAGNLTFEXP_LAGN->PJM
CLTF
0.389
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.916
LGEELTFEXP_LGEE->PJM
CLTF
0.173
MECLTFEXP_MEC->PJM
CLTF
0.405
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
CPLELTFEXP_CPLE->PJM
CLTF
0.016
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-4_MP-138-162_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-4_MP-138-162_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.66 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:213.54
MW Contribution:
25.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
238108AE1-109 GEN1
Solar/Wind Helper
0.049
23750501ELLIOTTS
Solar/Wind Harmer
1.09
235054AD2-180 GEN
Solar/Wind Harmer
3.42
23751201ROTHROCK
Solar/Wind Harmer
0.955
23750701CROSSCHOOL
Solar/Wind Helper
3.007
23585401KL_K28_T16
Solar/Wind Harmer
3.349
970697AG2-448 GEN
Solar/Wind Harmer
25.754
238185AF2-356 C
Solar/Wind Harmer
24.801
238109AE1-109 GEN2
Solar/Wind Helper
0.049
238110AE1-109 GEN3
Solar/Wind Helper
0.049
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.579
LGEELTFEXP_LGEE->PJM
CLTF
0.113
TVALTFEXP_TVA->PJM
CLTF
0.104
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.43
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.031
LAGNLTFEXP_LAGN->PJM
CLTF
0.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.752
WECLTFEXP_WEC->PJM
CLTF
0.065
MECLTFEXP_MEC->PJM
CLTF
0.263
NYPJM->LTFIMP_NY
CLTF
0.099
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.002
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P7-1_MP-138-058_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_MP-138-058_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.66 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:213.54
MW Contribution:
25.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
238108AE1-109 GEN1
Solar/Wind Helper
0.049
23750501ELLIOTTS
Solar/Wind Harmer
1.09
235054AD2-180 GEN
Solar/Wind Harmer
3.42
23751201ROTHROCK
Solar/Wind Harmer
0.955
23750701CROSSCHOOL
Solar/Wind Helper
3.007
23585401KL_K28_T16
Solar/Wind Harmer
3.349
970697AG2-448 GEN
Solar/Wind Harmer
25.754
238185AF2-356 C
Solar/Wind Harmer
24.801
238109AE1-109 GEN2
Solar/Wind Helper
0.049
238110AE1-109 GEN3
Solar/Wind Helper
0.049
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.579
LGEELTFEXP_LGEE->PJM
CLTF
0.113
TVALTFEXP_TVA->PJM
CLTF
0.104
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.43
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.031
LAGNLTFEXP_LAGN->PJM
CLTF
0.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.752
WECLTFEXP_WEC->PJM
CLTF
0.065
MECLTFEXP_MEC->PJM
CLTF
0.263
NYPJM->LTFIMP_NY
CLTF
0.099
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.002
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for [AG2-448] 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.75 %
Rating:164.0 MVA
Rating Type:A
MVA to Mitigate:166.86
MW Contribution:
35.47
IPD Plant:AG2-448
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
PJM_IPD
35.467

Details for 01BLACKO-01BLACKO 138.0/500.0 kV Ckt 3 transformer l/o AP_P2-3_PE-500-014_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BLACKO-01BLACKO 138.0/500.0 kV Ckt 3 transformer
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.96 %
Rating:558.0 MVA
Rating Type:B
MVA to Mitigate:563.37
MW Contribution:
14.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20084126DEEPCRK2
50/50
0.068
238108AE1-109 GEN1
Solar/Wind Harmer
0.394
23562501BACKB
Solar/Wind Harmer
2.614
235049AD1-125 C2
Solar/Wind Harmer
4.413
238118U2-030_1
Solar/Wind Harmer
1.267
23750501ELLIOTTS
Solar/Wind Harmer
1.439
20089126CSLMN_L13
Solar/Wind Harmer
0.402
23600101WARRIOR RN
50/50
39.983
235054AD2-180 GEN
Solar/Wind Harmer
7.425
235531U2-073 GEN
Solar/Wind Harmer
8.085
20084026DEEPCRK1
50/50
0.067
238126S14_GEN_1
Solar/Wind Harmer
2.086
20089226LOOKOUT
Solar/Wind Harmer
0.401
942731AE2-289 GEN
Solar/Wind Harmer
7.52
23751201ROTHROCK
Solar/Wind Harmer
1.942
944781AF1-143 GEN
Solar/Wind Harmer
4.565
20089026BF_G21_K23
Solar/Wind Harmer
0.318
238127S14_GEN_2
Solar/Wind Harmer
2.086
202652Y1-033 WT C
Solar/Wind Harmer
0.623
23750701CROSSCHOOL
Solar/Wind Harmer
11.756
235048AD1-125 C1
Solar/Wind Harmer
4.413
970075AG2-062 GEN
Solar/Wind Harmer
7.844
203955AF1-039 C O1
Solar/Wind Harmer
0.303
238117U2-030
Solar/Wind Harmer
3.02
23585401KL_K28_T16
Solar/Wind Harmer
6.183
970697AG2-448 GEN
Solar/Wind Harmer
14.447
238185AF2-356 C
Solar/Wind Harmer
14.691
238120AE2-309 GEN
Solar/Wind Harmer
1.003
238109AE1-109 GEN2
Solar/Wind Harmer
0.394
238193AE1-106 GEN
Solar/Wind Harmer
8.104
238110AE1-109 GEN3
Solar/Wind Harmer
0.394
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.309
NYPJM->LTFIMP_NY
CLTF
0.302
TVALTFEXP_TVA->PJM
CLTF
0.364
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.481
WECLTFEXP_WEC->PJM
CLTF
0.211
LAGNLTFEXP_LAGN->PJM
CLTF
0.74
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.893
LGEELTFEXP_LGEE->PJM
CLTF
0.367
MECLTFEXP_MEC->PJM
CLTF
0.862
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.059
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.045
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.46 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:333.56
MW Contribution:
25.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.97
23750701CROSSCHOOL
Solar/Wind Harmer
20.729
970697AG2-448 GEN
Solar/Wind Harmer
25.377
238185AF2-356 C
Solar/Wind Harmer
24.305
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.888
LGEELTFEXP_LGEE->PJM
CLTF
0.169
TVALTFEXP_TVA->PJM
CLTF
0.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.628
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
LAGNLTFEXP_LAGN->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.59
WECLTFEXP_WEC->PJM
CLTF
0.098
MECLTFEXP_MEC->PJM
CLTF
0.394
NYPJM->LTFIMP_NY
CLTF
0.152
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.67 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:326.07
MW Contribution:
25.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23750501ELLIOTTS
Solar/Wind Harmer
0.971
23750701CROSSCHOOL
Solar/Wind Harmer
20.731
970697AG2-448 GEN
Solar/Wind Harmer
25.379
238185AF2-356 C
Solar/Wind Harmer
24.308
964991AG1-363 GEN
Solar/Wind Helper
1.777
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.967
LGEELTFEXP_LGEE->PJM
CLTF
0.173
TVALTFEXP_TVA->PJM
CLTF
0.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.649
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.663
WECLTFEXP_WEC->PJM
CLTF
0.1
MECLTFEXP_MEC->PJM
CLTF
0.403
NYPJM->LTFIMP_NY
CLTF
0.148
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for [AG2-448] 01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.71 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:288.66
MW Contribution:
34.76
IPD Plant:AG2-448
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
PJM_IPD
34.763

Details for [AG2-448] 01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.59 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:288.35
MW Contribution:
34.76
IPD Plant:AG2-448
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
PJM_IPD
34.763

Details for 01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.55 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:282.88
MW Contribution:
20.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
Solar/Wind Harmer
20.858
238185AF2-356 C
Solar/Wind Harmer
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.888
LGEELTFEXP_LGEE->PJM
CLTF
0.169
TVALTFEXP_TVA->PJM
CLTF
0.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.628
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
LAGNLTFEXP_LAGN->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.59
WECLTFEXP_WEC->PJM
CLTF
0.098
MECLTFEXP_MEC->PJM
CLTF
0.394
NYPJM->LTFIMP_NY
CLTF
0.152
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for [AG2-448] 01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.18 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:279.19
MW Contribution:
34.77
IPD Plant:AG2-448
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
PJM_IPD
34.766

Details for [AG2-448] 01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.18 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:279.19
MW Contribution:
34.77
IPD Plant:AG2-448
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
PJM_IPD
34.766

Details for 01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01CROSSCHOOL-01BLACKO 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.75 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:275.38
MW Contribution:
20.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970697AG2-448 GEN
Solar/Wind Harmer
20.86
238185AF2-356 C
Solar/Wind Harmer
0
964991AG1-363 GEN
Solar/Wind Helper
1.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.967
LGEELTFEXP_LGEE->PJM
CLTF
0.173
TVALTFEXP_TVA->PJM
CLTF
0.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.649
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.663
WECLTFEXP_WEC->PJM
CLTF
0.1
MECLTFEXP_MEC->PJM
CLTF
0.403
NYPJM->LTFIMP_NY
CLTF
0.148
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
SIGELTFEXP_SIGE->PJM
CLTF
0.013
CONTINGENCY 'AP_P2-3_PE-500-014_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235103 TO BUS 964990 CKT 1          /*01BLACKO     500.0 - AG1-363 TP   500.0
 REDUCE BUS 235103 SHUNT BY 50 PERCENT                          /*01BLACKO     500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 235101 TO BUS 235103 CKT 1 /*01BEDNGT     500.0 - 01BLACKO     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235101 TO BUS 235103 CKT 1 /*01BEDNGT     500.0 - 01BLACKO     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT19_SRT-SL'
 OPEN BRANCH FROM BUS 235108 TO BUS 964990 CKT 1                /*01HATFLD     500.0 - AG1-363 TP   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P1-2_PE-500-004_SRT-SL-2'
 DISCONNECT BRANCH FROM BUS 964990 TO BUS 235103 CKT 1   /*AG1-363 TP   500.0 - 01BLACKO     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-004_SRT-SL-1'
 DISCONNECT BRANCH FROM BUS 235108 TO BUS 964990 CKT 1   /*01HATFLD     500.0 - AG1-363 TP   500.0
END
CONTINGENCY 'AP_P7-1_PE-138-012A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235468 TO BUS 235504 CKT 1   /*01FROSTB     138.0 - 01RIDGLY     138.0
 DISCONNECT BRANCH FROM BUS 235468 TO BUS 237317 CKT 1   /*01FROSTB     138.0 - 01FINZEL     138.0
 DISCONNECT BUS 235449                                   /*01CARLOS     138.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT9_SRT-SL'
 OPEN BRANCH FROM BUS 235774 TO BUS 235108 CKT 1                /*01RONCO      500.0 - 01HATFLD     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235106 TO BUS 235774 CKT 1 /*01FMARTN     500.0 - 01RONCO      500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235106 TO BUS 235774 CKT 1 /*01FMARTN     500.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT22_SRT-SL'
 OPEN BRANCH FROM BUS 235108 TO BUS 235774 CKT 1                /*01HATFLD     500.0 - 01RONCO      500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 964990 CKT 1 /*01HATFLD     500.0 - AG1-363 TP   500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 964990 CKT 1 /*01HATFLD     500.0 - AG1-363 TP   500.0
END
CONTINGENCY 'AP_P2-3_MP-138-206_SRT-A'
 DISCONNECT BRANCH FROM BUS 235106 TO BUS 235774 CKT 1   /*01FMARTN     500.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235108 TO BUS 235774 CKT 1   /*01HATFLD     500.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235755 TO BUS 235774 CKT 1   /*01RONCO1      18.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235756 TO BUS 235774 CKT 1   /*01RONCO2      18.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235757 TO BUS 235774 CKT 1   /*01RONCO3      18.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT11_SRT-SL'
 OPEN BRANCH FROM BUS 235774 TO BUS 235106 CKT 1                /*01RONCO      500.0 - 01FMARTN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235774 TO BUS 235108 CKT 1 /*01RONCO      500.0 - 01HATFLD     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235774 TO BUS 235108 CKT 1 /*01RONCO      500.0 - 01HATFLD     500.0
END
CONTINGENCY 'AP_P2-4_MP-138-162_SRT-A'
 DISCONNECT BRANCH FROM BUS 235050 TO BUS 235501 CKT 1   /*01SULPHURCTY 138.0 - 01PARRN      138.0
 DISCONNECT BRANCH FROM BUS 235479 TO BUS 235501 CKT 1   /*01JUNCTN     138.0 - 01PARRN      138.0
 DISCONNECT BRANCH FROM BUS 237483 TO BUS 235501 CKT 2   /*01PARR RUN    34.5 - 01PARRN      138.0
END
CONTINGENCY 'AP_P7-1_MP-138-058_SRT-A'
 DISCONNECT BRANCH FROM BUS 235050 TO BUS 235501 CKT 1   /*01SULPHURCTY 138.0 - 01PARRN      138.0
 DISCONNECT BRANCH FROM BUS 235479 TO BUS 235501 CKT 1   /*01JUNCTN     138.0 - 01PARRN      138.0
 DISCONNECT BRANCH FROM BUS 237483 TO BUS 235501 CKT 2   /*01PARR RUN    34.5 - 01PARRN      138.0
END
235550 to 237506 ckt 1
235446 to 235103 ckt 3
237506 to 235446 ckt 1

Winter Peak Analysis

The New Service Request AG2-448 was evaluated as a 50.0 MW (30.0 MW Capacity) injection in the APS area.

AG2-448 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 50.0 MW (50.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-448 was evaluated as a 50.0 MW injection

AG2-448 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 50.0 MW (50.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 2, Cluster 64 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 64 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 64 projects will meet the dynamics requirements of the NERC, FirstEnergy (FE), and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2028 summer peak load case, modified to include applicable projects. Cluster 64 projects have been dispatched online at maximum power output, with approximately unity power factor at the high side of the GSUs, 1.0 pu voltage at the generator terminals, and 1.0 pu voltage at the POI buses.

Cluster 64 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 254 contingencies were studied, each with a 20 second simulation time period (with 1.0 second initial run prior to any events). Studied faults included:

  1. Steady-state operation (Category P0);
  2. Three phase faults with normal clearing time on the intact network (Category P1);
  3. Single phase to ground faults with delayed clearing due to a stuck breaker (Category P4);
  4. Single phase to ground faults with delayed clearing as a result of protection failure (Category P5);
  5. Single phase to ground faults with normal clearing for common structure (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 64 projects.

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2028 peak load case:

  1. Cluster 64 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 64 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

No mitigations were found to be required for TC2 Cluster 64.

 

Table 1: TC2 Cluster 64 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

64

AG2-062

Wind

FirstEnergy (FE) transmission system, Allegheny Power System (APS) zone

147.0 MW

147.0 MW

21.609 MW

William 138 kV

AG2-448

Solar

FirstEnergy (FE) transmission system, Allegheny Power System (APS) zone

50.0 MW

50.0 MW

30.0 MW

Cross School - Kitzmiller

138 kV

AH1-206

Storage

FirstEnergy (FE) transmission system, Allegheny Power System (APS) zone

60.0 MW

60.0 MW

60.0 MW

Bethelboro 138 kV

AH1-247

Solar

FirstEnergy (FE) transmission system, Allegheny Power System (APS) zone

40.0 MW

40.0 MW

24.0 MW

Lardin - Lake Lynn 138kV

AH1-248

Solar

FirstEnergy (FE) transmission system, Allegheny Power System (APS) zone

65.0 MW

25.0 MW

15.0 MW

Lardin - Lake Lynn 138kV

AH1-249

Storage

FirstEnergy (FE) transmission system, Allegheny Power System (APS) zone

145.0 MW

80.0 MW

80.0 MW

Lardin – Lake Lynn 138kV

 

Reactive Power Analysis

AG2-448 meets the 0.95 lagging and leading PF requirement at the high side of the main transformer.

 

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

(No dependencies were identified)

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-448 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
APSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationContingent$0N/A
APSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Contingent$0N/A
APSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Contingent$0N/A
APSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardContingent$0N/A
Grand Total:$0

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BLACKO-01BLACKO 500.0/138.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-448 may not presently have cost responsibility for this upgrade, AG2-448 may need this upgrade in-service to be deliverable to the PJM system. If AG2-448 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BLACKO-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-448


AG2-448 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowAPSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationTopology-0.0%Contingent$0
Load FlowAPSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Topology-0.0%Contingent$0
Load FlowAPSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Topology-0.0%Contingent$0
Load FlowAPSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardTopology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-448 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-448 One Line Diagram

AG2-448 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.