AG2-518 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:41

Tech Drive 138 kV

32.0 MW Capacity / 80.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Delorean Power LLC dba Lightshift Energy, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request meets the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposits refunded. See Readiness Deposit calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $10,438,492 $7,540,496 = 1.38 AND ( $10,438,492 - $7,540,496 ) 80.0 = $36,225 per MW

General

The Project Developer has proposed a Storage facility located in the American Electric Power zone — Montgomery County, Virginia. The installed facilities will have a total capability of 80.0 MW with 32.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-518
Project Name:
Tech Drive 138 kV
Project Developer Name:
Delorean Power LLC dba Lightshift Energy
State:
Virginia
County:
Montgomery
Transmission Owner:
American Electric Power
MFO:
80.0
MWE:
80.0
MWC:
32.0
Battery Storage Specification:
320.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-518 will interconnect on the American Electric Power transmission system at the Tech Drive 138 kV Station.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-518 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-518Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$986,167$0$0
Other Scope$750,157$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$10,229,132$10,229,132$10,229,132
System Reliability Network Upgrades
Steady State Thermal & Voltage$184,360$184,360$184,360
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$25,000$25,000$25,000
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$12,174,816$10,438,492$10,438,492

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-518

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-518
Project ID: AG2-518
20% of cost allocation for Phase II Network Upgrades:(A) $2,087,698
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $754,050
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $1,333,649
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

APCO will tie the proposed AG2-518 138 kV project into the existing Tech Drive 138 kV station by completing the following construction tasks: Major Equipment Installation of (3) 138KV RCVTs with (1) three-phase 138KV RCVT structures & foundations. 1 mile of gravel access road. Installation of two 2 breaker control at the TECH DRIVE 138 kV Station. Installation of Bus Differential Protection at the TECH DRIVE 138 kV Station. Installation of Direct Fiber at the TECH DRIVE 138 kV Station. Installation of DCB Line Protection at the CLAYTOR HILLTOP 138 kV Station. Replacement of the existing control house with a new 16 by 27 foot control house. Installation of one 1 RTU at the TECH DRIVE 138 kV Station. Installation of DCB Line Protection at the CLAYTOR HILLTOP 138 kV Station. Appalachian Power Company will transition existing OPGW fiber-optic shield wire from the cut-in dead ends into the TECH DRIVE 138 kV Station. Appalachian Power Company will install 1 mile of 144 count all dielectric self supporting (ADSS) fiber-optic cable. Appalachian Power Company will install 1 mile of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable. Appalachian Power Company will install one (1) new 8340 router at the TECH DRIVE 138 kV Station. Appalachian Power Company will install one (1) CES relaying package at the TECH DRIVE 138 kV Station.

$5,149,633$2,759,462$1,457,579$862,458$10,229,132$10,229,132
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the TECH DRIVE 138 kV Station.

$372,255$211,684$106,855$59,363$750,157$750,157
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

A 138 kV dead-end structure and foundation outside the fence of the Interconnection Substation, to terminate the Project Developer’s generator lead line. Line conductor from the dead-end structure to the bus position in the switchyard of the interconnection substation. The APCO Interconnection Facilities will include but are not limited to the following: • Installation of one (1) new steel, single circuit, single pole dead end structure and one span of ACSR 556 (Dove) transmission line conductor with 7#8 Alumoweld shield wire for the generation lead circuit extending from the TECH DRIVE 138 kV Station.

$501,438$273,318$136,830$74,581$986,167$986,167
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$11,965,456$11,965,456
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

Transmission Owner Identified Network Impacts to Distribution Facilities

None


Transmission Owner Identified Network Impacts to Sub-Regional Facilities

The Transmission Owner identified network impacts to Sub-Regional facilities as follows:

Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
244110 05MERRIMAC 69.0 - 244111 05MIDWAY 69.0 CKT 1 AEP_P7-1_#10876___SRT-A
CONTINGENCY 'AEP_P7-1_#10876___SRT-A'  

  OPEN BRANCH FROM BUS 242608 TO BUS 242791 CKT 1                  / 242608 05CLYTR1 138 242791 05SCHRIS 138 1

  OPEN BRANCH FROM BUS 242791 TO BUS 243874 CKT 1                  / 242791 05SCHRIS 138 243874 05TECHDR 138 1

  OPEN BRANCH FROM BUS 242634 TO BUS 247507 CKT 1                  / 242634 05EDGEMO 138 247507 05S.CHRIS_BP 138 1

  OPEN BRANCH FROM BUS 242636 TO BUS 247507 CKT 1                  / 242636 05FALLBR 138 247507 05S.CHRIS_BP 138 1

END
44.0102.66 %21.72

Transmission Owner Identified System Reinforcements on Distribution Facilities

None


Transmission Owner Identified System Reinforcements on Sub-Regional Facilities
AG2-518 Transmission Owner Identified System Reinforcements Cost Breakdown:
TORTEP ID / TO IDTitleMW ImpactPercent AllocationAllocated Cost ($USD)
AEPn9803.0 / AEP-TC2-243Merrimac - Midway: Sag study Merrimac-Midway 69 kV line from Merrimac to Str. 464-121.7 MW100.0%$25,000
Grand Total:$25,000
System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEPn9803.0 / AEP-TC2-243Merrimac - Midway: Sag study Merrimac-Midway 69 kV line from Merrimac to Str. 464-1$25,000

Contributor

Description: Sag study Merrimac-Midway 69 kV line from Merrimac to Str. 464-1

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-51821.7 MW100.0%$25,000

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-518 was evaluated as a 80.0 MW (32.0 MW Capacity) injection in the AEP area.

AG2-518 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 80.0 MW (80.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC300.71 %1180.0B3548.35
5.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC300.71 %1180.0B3548.35
5.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.19
5.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.19
5.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.09
5.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC286.57 %1180.0B3381.47
5.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC286.54 %1180.0B3381.22
5.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC253.24 %1180.0B2988.23
5.48
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17030___SRT-A
TowerAC241.49 %1180.0B2849.63
5.72
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
BusAC237.35 %1180.0B2800.7
5.13
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
BusAC236.49 %1180.0B2790.61
5.2
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC222.44 %1180.0A2624.74
5.13
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC215.58 %1180.0B2543.84
13.42
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC215.58 %1180.0B2543.84
13.42
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC215.58 %1180.0B2543.84
13.42
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC215.56 %1180.0B2543.58
13.42
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC187.71 %1180.0B2214.98
13.69
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC184.07 %1180.0B2171.99
12.76
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC180.07 %1180.0B2124.82
12.85
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 138KV_SRT-A
BusAC179.73 %1180.0B2120.8
12.92
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC176.02 %1180.0A2077.06
12.84

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.35
MW Contribution:
5.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.35
MW Contribution:
5.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
24290005CRG1L
50/50
0.717
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.19
MW Contribution:
5.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.19
MW Contribution:
5.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316192AB2-158 GEN
Solar/Wind Helper
1.54
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
3143873LANEXA
Solar/Wind Helper
0.14
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.09
MW Contribution:
5.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:286.57 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3381.47
MW Contribution:
5.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
5.833
972103AH1-617 GEN
Solar/Wind Harmer
13.552
270030AE2-140 GEN
Solar/Wind Harmer
13.376
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270583AD2-179 GEN
Solar/Wind Harmer
9.711
971225AH1-072 GEN
Solar/Wind Harmer
1.446
971227AH1-073 GEN
Solar/Wind Harmer
1.446
24723105RIVRG2
Adder
16.666
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
1.529
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
6.442
270399AC1-101 GEN
Solar/Wind Harmer
2.148
971981AH1-535 GEN
Solar/Wind Harmer
4.373
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
9.797
944971AF1-162 GEN
Solar/Wind Harmer
6.718
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
4.106
971061AG2-657 GEN
Solar/Wind Harmer
3.871
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
0.719
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
970281AG2-184 GEN
Solar/Wind Harmer
14.229
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
3.974
970913AG2-568 GEN
Solar/Wind Harmer
5.608
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
971329AH1-144 GEN
Solar/Wind Harmer
4.594
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
2.148
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
14.993
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
6.792
971461AH1-227 GEN
Solar/Wind Harmer
3.708
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:286.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3381.22
MW Contribution:
5.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
5.833
972103AH1-617 GEN
Solar/Wind Harmer
13.552
270030AE2-140 GEN
Solar/Wind Harmer
13.376
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270583AD2-179 GEN
Solar/Wind Harmer
9.711
971225AH1-072 GEN
Solar/Wind Harmer
1.446
971227AH1-073 GEN
Solar/Wind Harmer
1.446
24723105RIVRG2
Adder
16.666
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
1.529
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
6.442
270399AC1-101 GEN
Solar/Wind Harmer
2.148
971981AH1-535 GEN
Solar/Wind Harmer
4.373
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
9.797
944971AF1-162 GEN
Solar/Wind Harmer
6.718
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
4.106
971061AG2-657 GEN
Solar/Wind Harmer
3.871
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
0.719
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
970281AG2-184 GEN
Solar/Wind Harmer
14.229
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
3.974
970913AG2-568 GEN
Solar/Wind Harmer
5.608
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
971329AH1-144 GEN
Solar/Wind Harmer
4.594
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
2.148
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
14.993
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
6.792
971461AH1-227 GEN
Solar/Wind Harmer
3.708
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:253.24 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2988.23
MW Contribution:
5.48
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270214AC2-123 GEN
Solar/Wind Harmer
3.383
270583AD2-179 GEN
Solar/Wind Harmer
13.976
971225AH1-072 GEN
Solar/Wind Harmer
1.896
971227AH1-073 GEN
Solar/Wind Harmer
1.896
971341AH1-150 GEN
Solar/Wind Harmer
10.981
971343AH1-151 GEN
Solar/Wind Harmer
10.981
315976AC1-164 GENA
Solar/Wind Helper
2.937
316169AC1-164_GENC
Solar/Wind Helper
2.537
3142946ENON
Solar/Wind Helper
0.022
316312AB1-027
Solar/Wind Helper
0.45
3143526WINTERP
Solar/Wind Helper
1.209
970563AG2-360 GEN
50/50
33.924
24689505VACITY
50/50
3.969
274729ELWOOD EC;1P
Adder
8.897
3143526WINTERP
Solar/Wind Helper
1.209
964211AG1-282 GEN
Solar/Wind Helper
0.301
971543AH1-269 GEN
50/50
8.242
971313AH1-133 GEN
Solar/Wind Harmer
6.737
274728ELWOOD EC;5P
Adder
8.897
316468AD1-105 GEN
Solar/Wind Helper
1.134
971687AH1-348 GEN
Solar/Wind Harmer
0.942
316075AC2-137 C
Solar/Wind Helper
0.351
316077AC2-138 C
Solar/Wind Helper
0.211
971881AH1-461 GEN
50/50
10.678
943031AE2-326 GEN
Solar/Wind Harmer
5.324
960911AF2-382 GEN
Solar/Wind Harmer
7.746
270030AE2-140 GEN
Solar/Wind Harmer
19.126
972103AH1-617 GEN
Solar/Wind Harmer
17.445
959091AF2-200 GEN
Solar/Wind Harmer
10.981
274734ELWOOD EC;8P
Adder
8.897
274736ELWOOD EC;9P
Adder
8.897
274676JOLIET 29;8U
Adder
16.007
316447AC1-158 HLD
Solar/Wind Helper
3.012
3142416OLDCHRC
Solar/Wind Helper
0.613
3142416OLDCHRC
Solar/Wind Helper
0.235
315975AC1-164 GENB
Solar/Wind Helper
0.087
3142433PROV 92
Solar/Wind Helper
0.892
3148463FAIRFLD
Solar/Wind Harmer
-0.014
970281AG2-184 GEN
Solar/Wind Harmer
18.318
274735ELWOOD EC;4P
Adder
8.897
315651AD1-115 GEN
Solar/Wind Helper
0.755
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
6.118
270336AE1-100 GEN
Solar/Wind Harmer
1.761
943811AF1-049 GEN
Solar/Wind Harmer
3.46
957471AF2-041 GEN
Solar/Wind Harmer
16.472
274676JOLIET 29;8U
Adder
16.6
966881AG1-559 GEN
Solar/Wind Helper
0.328
316473AC1-191 GEN
Solar/Wind Helper
1.456
3142946ENON
Solar/Wind Helper
0.075
24728205BUCHG1
50/50
5.133
971277AH1-098 GEN
Solar/Wind Harmer
5.61
970913AG2-568 GEN
Solar/Wind Harmer
6.125
316045AC1-158 PL2
Solar/Wind Helper
4.379
966871AG1-558 GEN
Solar/Wind Helper
0.321
316006AB2-029 C
Solar/Wind Helper
0.107
24290705CLAY-2
50/50
0.169
24415905BUCK
50/50
0.025
316337AD2-073 GEN
Solar/Wind Helper
0.341
3141726DUNNSVL
Solar/Wind Helper
0.895
24734805WLF1G4
50/50
6.262
24735105WLF2G1
50/50
6.118
971329AH1-144 GEN
Solar/Wind Harmer
7.928
3151861LOWMORA
Adder
1.244
274731ELWOOD EC;2P
Adder
8.897
274733ELWOOD EC;3P
Adder
8.897
316164AC1-076 GEN
Solar/Wind Helper
1.11
316233AE1-074 FULL
Solar/Wind Helper
0.355
3141813NORNECK
Solar/Wind Helper
0.223
24290705CLAY-2
50/50
0.169
3151861LOWMORA
Adder
1.295
971403AH1-188 GEN
Solar/Wind Harmer
12.423
959081AF2-199 GEN
Solar/Wind Harmer
5.491
971067AG2-660 GEN
Solar/Wind Harmer
1.277
270494AE1-108_GEN
Solar/Wind Helper
3.531
316223AC1-118
Solar/Wind Helper
0.343
247619Y1-049
50/50
0.036
316450AC1-158 RIC
Solar/Wind Helper
0.365
970823AG2-518 GEN
50/50
5.477
24290605CLAY-1
50/50
0.169
958121AF2-106 GEN
Solar/Wind Harmer
6.343
270346AE1-212 GEN
Solar/Wind Harmer
9.332
971461AH1-227 GEN
Solar/Wind Harmer
4.864
274730ELWOOD EC;6P
Adder
8.897
316044AC1-158 PL1
Solar/Wind Helper
1.369
3143226MDLTHAN
Solar/Wind Helper
0.233
3142543TWELFTH
Solar/Wind Helper
0.022
316404AE1-155 C
Solar/Wind Helper
1.907
24416005BYLLESBY
50/50
0.023
24734705WLF1G3
50/50
6.262
24734905WLF1G5
50/50
6.262
966391AG1-508 GEN
Solar/Wind Harmer
4.809
971331AH1-145 GEN
Solar/Wind Harmer
12.412
270069AE2-166 C O1
Solar/Wind Harmer
9.245
315616AA1-038_C
Solar/Wind Harmer
2.777
3151881LOWMORC
Adder
1.285
3151881LOWMORC
Adder
1.264
971981AH1-535 GEN
Solar/Wind Harmer
8.769
971171AH1-044 GEN
Solar/Wind Harmer
10.981
274675JOLIET 29;7U
Adder
16.6
274675JOLIET 29;7U
Adder
16.007
3143873LANEXA
Solar/Wind Helper
0.134
24290605CLAY-1
50/50
0.169
24728305BUCHG2
50/50
5.133
274732ELWOOD EC;7P
Adder
8.897
3141906WESTMOR
Solar/Wind Helper
0.09
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.396
WECLTFEXP_WEC->PJM
CLTF
2.106
LAGNLTFEXP_LAGN->PJM
CLTF
12.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.088
CPLELTFEXP_CPLE->PJM
CLTF
2.02
SIGELTFEXP_SIGE->PJM
CLTF
0.319
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.014
NYPJM->LTFIMP_NY
CLTF
2.107
TVALTFEXP_TVA->PJM
CLTF
6.888
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
83.049
LGEELTFEXP_LGEE->PJM
CLTF
4.253
MECLTFEXP_MEC->PJM
CLTF
9.684
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17030___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17030___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:241.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2849.63
MW Contribution:
5.72
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
5.054
971277AH1-098 GEN
Solar/Wind Harmer
5.569
970913AG2-568 GEN
Solar/Wind Harmer
6.098
316045AC1-158 PL2
Solar/Wind Helper
4.285
966871AG1-558 GEN
Solar/Wind Helper
0.314
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.774
971331AH1-145 GEN
Solar/Wind Harmer
12.745
270069AE2-166 C O1
Solar/Wind Harmer
9.341
24734705WLF1G3
Adder
5.791
24734905WLF1G5
Adder
5.791
971171AH1-044 GEN
Solar/Wind Harmer
10.834
274675JOLIET 29;7U
Adder
16.387
274675JOLIET 29;7U
Adder
15.801
970563AG2-360 GEN
50/50
33.343
24689505VACITY
50/50
3.901
274729ELWOOD EC;1P
Adder
8.783
3147312GRETNA
Solar/Wind Helper
0.273
3146802CHATHAM
Solar/Wind Helper
0.256
3143526WINTERP
Solar/Wind Helper
1.177
24290705CLAY-2
50/50
0.175
971403AH1-188 GEN
Solar/Wind Harmer
12.255
959081AF2-199 GEN
Solar/Wind Harmer
5.417
971067AG2-660 GEN
Solar/Wind Harmer
1.26
270494AE1-108_GEN
Solar/Wind Helper
4.186
270173AC1-122 GEN
Solar/Wind Helper
2.053
270205AE1-176
50/50
0.004
270336AE1-100 GEN
Solar/Wind Harmer
1.752
24735205WLF2G2
Adder
5.652
943811AF1-049 GEN
Solar/Wind Harmer
3.421
957471AF2-041 GEN
Solar/Wind Harmer
16.25
274676JOLIET 29;8U
Adder
16.387
966881AG1-559 GEN
Solar/Wind Helper
0.321
316473AC1-191 GEN
Solar/Wind Helper
1.424
971881AH1-461 GEN
50/50
10.6
24290105CRG2H
50/50
0.806
943031AE2-326 GEN
Solar/Wind Harmer
5.244
960911AF2-382 GEN
Solar/Wind Harmer
7.628
270030AE2-140 GEN
Solar/Wind Harmer
18.948
959091AF2-200 GEN
Solar/Wind Harmer
10.834
274734ELWOOD EC;8P
Adder
8.783
274736ELWOOD EC;9P
Adder
8.783
274676JOLIET 29;8U
Adder
15.802
3147123OTTER R
Solar/Wind Helper
0.199
316447AC1-158 HLD
Solar/Wind Helper
2.947
3142416OLDCHRC
Solar/Wind Helper
0.599
3142416OLDCHRC
Solar/Wind Helper
0.23
315975AC1-164 GENB
Solar/Wind Helper
0.085
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.785
316450AC1-158 RIC
Solar/Wind Helper
0.357
270583AD2-179 GEN
Solar/Wind Harmer
14.401
270214AC2-123 GEN
Solar/Wind Harmer
3.332
971225AH1-072 GEN
Solar/Wind Harmer
1.865
971227AH1-073 GEN
Solar/Wind Harmer
1.865
971341AH1-150 GEN
Solar/Wind Harmer
10.834
971343AH1-151 GEN
Solar/Wind Harmer
10.834
315976AC1-164 GENA
Solar/Wind Helper
2.875
316169AC1-164_GENC
Solar/Wind Helper
2.483
274735ELWOOD EC;4P
Adder
8.783
970823AG2-518 GEN
50/50
5.724
24290605CLAY-1
50/50
0.175
958121AF2-106 GEN
Solar/Wind Harmer
6.537
270346AE1-212 GEN
Solar/Wind Harmer
9.433
971461AH1-227 GEN
Solar/Wind Harmer
4.785
274730ELWOOD EC;6P
Adder
8.783
316044AC1-158 PL1
Solar/Wind Helper
1.339
3143226MDLTHAN
Solar/Wind Helper
0.227
971329AH1-144 GEN
Solar/Wind Harmer
8.141
24734805WLF1G4
Adder
5.791
24735105WLF2G1
Adder
5.652
274731ELWOOD EC;2P
Adder
8.783
274733ELWOOD EC;3P
Adder
8.783
316233AE1-074 FULL
Solar/Wind Helper
0.346
316164AC1-076 GEN
Solar/Wind Helper
1.072
971543AH1-269 GEN
50/50
8.505
24290205CRG2L
50/50
0.675
971313AH1-133 GEN
Solar/Wind Harmer
6.653
274728ELWOOD EC;5P
Adder
8.783
316468AD1-105 GEN
Solar/Wind Helper
1.109
24290005CRG1L
50/50
0.657
971687AH1-348 GEN
Solar/Wind Harmer
0.926
3147312GRETNA
Solar/Wind Helper
0.068
316075AC2-137 C
Solar/Wind Helper
0.344
316312AB1-027
Solar/Wind Helper
0.44
3143526WINTERP
Solar/Wind Helper
1.177
24290605CLAY-1
50/50
0.175
24728305BUCHG2
50/50
5.054
274732ELWOOD EC;7P
Adder
8.783
316197AC1-042 GEN
Solar/Wind Helper
0.322
24290705CLAY-2
50/50
0.175
24415905BUCK
50/50
0.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.022
NYPJM->LTFIMP_NY
CLTF
2.036
TVALTFEXP_TVA->PJM
CLTF
6.738
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.488
LGEELTFEXP_LGEE->PJM
CLTF
4.19
MECLTFEXP_MEC->PJM
CLTF
9.533
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.871
WECLTFEXP_WEC->PJM
CLTF
2.077
LAGNLTFEXP_LAGN->PJM
CLTF
12.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.507
CPLELTFEXP_CPLE->PJM
CLTF
1.827
SIGELTFEXP_SIGE->PJM
CLTF
0.315

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:237.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2800.7
MW Contribution:
5.13
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270214AC2-123 GEN
Solar/Wind Harmer
3.229
270583AD2-179 GEN
Solar/Wind Harmer
13.158
971225AH1-072 GEN
Solar/Wind Harmer
1.812
971227AH1-073 GEN
Solar/Wind Harmer
1.812
971341AH1-150 GEN
Solar/Wind Harmer
10.521
971343AH1-151 GEN
Solar/Wind Harmer
10.521
971881AH1-461 GEN
50/50
10.173
943031AE2-326 GEN
Solar/Wind Harmer
5.082
960911AF2-382 GEN
Solar/Wind Harmer
7.399
270030AE2-140 GEN
Solar/Wind Harmer
18.085
959091AF2-200 GEN
Solar/Wind Harmer
10.521
274734ELWOOD EC;8P
Adder
8.525
274736ELWOOD EC;9P
Adder
8.525
274676JOLIET 29;8U
Adder
15.337
316447AC1-158 HLD
Solar/Wind Helper
2.88
3147123OTTER R
Solar/Wind Helper
0.137
3142416OLDCHRC
Solar/Wind Helper
0.582
3142416OLDCHRC
Solar/Wind Helper
0.223
316312AB1-027
Solar/Wind Helper
0.427
970563AG2-360 GEN
50/50
32.411
24689505VACITY
50/50
3.793
274729ELWOOD EC;1P
Adder
8.525
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
971543AH1-269 GEN
50/50
7.755
971313AH1-133 GEN
Solar/Wind Harmer
6.428
274728ELWOOD EC;5P
Adder
8.525
316468AD1-105 GEN
Solar/Wind Helper
1.079
971687AH1-348 GEN
Solar/Wind Harmer
0.9
3147312GRETNA
Solar/Wind Helper
0.046
274735ELWOOD EC;4P
Adder
8.525
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
5.85
270336AE1-100 GEN
Solar/Wind Harmer
1.667
943811AF1-049 GEN
Solar/Wind Harmer
3.27
957471AF2-041 GEN
Solar/Wind Harmer
15.782
274676JOLIET 29;8U
Adder
15.905
966881AG1-559 GEN
Solar/Wind Helper
0.312
316473AC1-191 GEN
Solar/Wind Helper
1.383
24728205BUCHG1
50/50
4.902
971277AH1-098 GEN
Solar/Wind Harmer
5.342
316045AC1-158 PL2
Solar/Wind Helper
4.187
966871AG1-558 GEN
Solar/Wind Helper
0.305
24290705CLAY-2
50/50
0.159
24415905BUCK
50/50
0.024
24734805WLF1G4
50/50
5.986
24735105WLF2G1
50/50
5.85
971329AH1-144 GEN
Solar/Wind Harmer
7.474
274731ELWOOD EC;2P
Adder
8.525
274733ELWOOD EC;3P
Adder
8.525
24290705CLAY-2
50/50
0.159
959081AF2-199 GEN
Solar/Wind Harmer
5.261
971067AG2-660 GEN
Solar/Wind Harmer
1.223
270494AE1-108_GEN
Solar/Wind Helper
3.291
970823AG2-518 GEN
50/50
5.131
24290605CLAY-1
50/50
0.159
958121AF2-106 GEN
Solar/Wind Harmer
5.971
270346AE1-212 GEN
Solar/Wind Harmer
8.843
971461AH1-227 GEN
Solar/Wind Harmer
4.649
274730ELWOOD EC;6P
Adder
8.525
316044AC1-158 PL1
Solar/Wind Helper
1.309
247619Y1-049
50/50
0.034
316450AC1-158 RIC
Solar/Wind Helper
0.349
24416005BYLLESBY
50/50
0.022
24734705WLF1G3
50/50
5.986
24734905WLF1G5
50/50
5.986
966391AG1-508 GEN
Solar/Wind Harmer
4.579
971331AH1-145 GEN
Solar/Wind Harmer
11.701
270069AE2-166 C O1
Solar/Wind Harmer
8.726
971171AH1-044 GEN
Solar/Wind Harmer
10.521
274675JOLIET 29;7U
Adder
15.905
274675JOLIET 29;7U
Adder
15.337
24290605CLAY-1
50/50
0.159
24728305BUCHG2
50/50
4.902
274732ELWOOD EC;7P
Adder
8.525
316197AC1-042 GEN
Solar/Wind Helper
0.219
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.311
WECLTFEXP_WEC->PJM
CLTF
2.017
LAGNLTFEXP_LAGN->PJM
CLTF
12.384
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.49
CPLELTFEXP_CPLE->PJM
CLTF
1.94
SIGELTFEXP_SIGE->PJM
CLTF
0.306
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.805
NYPJM->LTFIMP_NY
CLTF
2.006
TVALTFEXP_TVA->PJM
CLTF
6.594
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
CBM West 2LTFEXP_CBM-W2->PJM
CBM
79.525
LGEELTFEXP_LGEE->PJM
CLTF
4.072
MECLTFEXP_MEC->PJM
CLTF
9.276
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10265_05LEESVI 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:236.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2790.61
MW Contribution:
5.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270214AC2-123 GEN
Solar/Wind Harmer
3.25
270583AD2-179 GEN
Solar/Wind Harmer
13.324
971225AH1-072 GEN
Solar/Wind Harmer
1.824
971227AH1-073 GEN
Solar/Wind Harmer
1.824
971341AH1-150 GEN
Solar/Wind Harmer
10.59
971343AH1-151 GEN
Solar/Wind Harmer
10.59
971881AH1-461 GEN
50/50
10.248
943031AE2-326 GEN
Solar/Wind Harmer
5.116
960911AF2-382 GEN
Solar/Wind Harmer
7.446
270030AE2-140 GEN
Solar/Wind Harmer
18.83
959091AF2-200 GEN
Solar/Wind Harmer
10.59
274734ELWOOD EC;8P
Adder
8.58
274736ELWOOD EC;9P
Adder
8.58
274676JOLIET 29;8U
Adder
15.437
316312AB1-027
Solar/Wind Helper
0.431
970563AG2-360 GEN
50/50
32.611
24689505VACITY
50/50
3.816
274729ELWOOD EC;1P
Adder
8.581
3147312GRETNA
Solar/Wind Helper
0.331
3146802CHATHAM
Solar/Wind Helper
0.31
971543AH1-269 GEN
50/50
7.854
971313AH1-133 GEN
Solar/Wind Harmer
6.472
274728ELWOOD EC;5P
Adder
8.58
316468AD1-105 GEN
Solar/Wind Helper
1.087
971687AH1-348 GEN
Solar/Wind Harmer
0.906
3147312GRETNA
Solar/Wind Helper
0.083
316123AC1-075 GEN
Solar/Wind Helper
1.523
3147123OTTER R
Solar/Wind Helper
0.234
316447AC1-158 HLD
Solar/Wind Helper
2.895
3142416OLDCHRC
Solar/Wind Helper
0.587
3142416OLDCHRC
Solar/Wind Helper
0.225
274735ELWOOD EC;4P
Adder
8.581
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
5.886
270336AE1-100 GEN
Solar/Wind Harmer
1.727
943811AF1-049 GEN
Solar/Wind Harmer
3.415
957471AF2-041 GEN
Solar/Wind Harmer
15.885
274676JOLIET 29;8U
Adder
16.009
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.394
24728205BUCHG1
50/50
4.933
971277AH1-098 GEN
Solar/Wind Harmer
5.391
970913AG2-568 GEN
Solar/Wind Harmer
5.873
316045AC1-158 PL2
Solar/Wind Helper
4.21
966871AG1-558 GEN
Solar/Wind Helper
0.308
24290705CLAY-2
50/50
0.161
24415905BUCK
50/50
0.024
24734805WLF1G4
50/50
6.023
24735105WLF2G1
50/50
5.886
971329AH1-144 GEN
Solar/Wind Harmer
7.561
274731ELWOOD EC;2P
Adder
8.581
274733ELWOOD EC;3P
Adder
8.581
24290705CLAY-2
50/50
0.161
959081AF2-199 GEN
Solar/Wind Harmer
5.295
971067AG2-660 GEN
Solar/Wind Harmer
1.231
270494AE1-108_GEN
Solar/Wind Helper
3.421
247619Y1-049
50/50
0.034
316450AC1-158 RIC
Solar/Wind Helper
0.351
970823AG2-518 GEN
50/50
5.201
24290605CLAY-1
50/50
0.161
958121AF2-106 GEN
Solar/Wind Harmer
6.047
270346AE1-212 GEN
Solar/Wind Harmer
8.928
971461AH1-227 GEN
Solar/Wind Harmer
4.678
274730ELWOOD EC;6P
Adder
8.58
316044AC1-158 PL1
Solar/Wind Helper
1.316
24416005BYLLESBY
50/50
0.022
24734705WLF1G3
50/50
6.023
24734905WLF1G5
50/50
6.023
966391AG1-508 GEN
Solar/Wind Harmer
4.619
971331AH1-145 GEN
Solar/Wind Harmer
11.838
270069AE2-166 C O1
Solar/Wind Harmer
9.063
971171AH1-044 GEN
Solar/Wind Harmer
10.59
274675JOLIET 29;7U
Adder
16.009
274675JOLIET 29;7U
Adder
15.437
24290605CLAY-1
50/50
0.161
24728305BUCHG2
50/50
4.933
274732ELWOOD EC;7P
Adder
8.58
316197AC1-042 GEN
Solar/Wind Helper
0.39
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.288
NYPJM->LTFIMP_NY
CLTF
2.015
TVALTFEXP_TVA->PJM
CLTF
6.637
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.048
LGEELTFEXP_LGEE->PJM
CLTF
4.098
MECLTFEXP_MEC->PJM
CLTF
9.336
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.47
WECLTFEXP_WEC->PJM
CLTF
2.031
LAGNLTFEXP_LAGN->PJM
CLTF
12.467
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.609
CPLELTFEXP_CPLE->PJM
CLTF
1.968
SIGELTFEXP_SIGE->PJM
CLTF
0.308

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:222.44 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:2624.74
MW Contribution:
5.13
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
10.18
943031AE2-326 GEN
Solar/Wind Harmer
5.085
960911AF2-382 GEN
Solar/Wind Harmer
5.166
270030AE2-140 GEN
Solar/Wind Harmer
12.629
274734ELWOOD EC;8P
Adder
8.538
274736ELWOOD EC;9P
Adder
8.538
274676JOLIET 29;8U
Adder
15.361
316447AC1-158 HLD
Solar/Wind Helper
2.877
3147123OTTER R
Solar/Wind Helper
0.137
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.223
270583AD2-179 GEN
Solar/Wind Harmer
9.185
971225AH1-072 GEN
Solar/Wind Harmer
1.266
971227AH1-073 GEN
Solar/Wind Harmer
1.266
24416005BYLLESBY
50/50
0.022
24734705WLF1G3
50/50
5.991
24734905WLF1G5
50/50
5.991
966391AG1-508 GEN
Solar/Wind Harmer
1.432
971331AH1-145 GEN
Solar/Wind Harmer
11.709
270069AE2-166 C O1
Solar/Wind Harmer
6.093
274675JOLIET 29;7U
Adder
15.93
274675JOLIET 29;7U
Adder
15.361
971543AH1-269 GEN
50/50
7.759
971313AH1-133 GEN
Solar/Wind Harmer
3.701
274728ELWOOD EC;5P
Adder
8.538
316468AD1-105 GEN
Solar/Wind Helper
1.078
971687AH1-348 GEN
Solar/Wind Harmer
0.628
3147312GRETNA
Solar/Wind Helper
0.046
316312AB1-027
Solar/Wind Helper
0.427
970563AG2-360 GEN
50/50
32.435
24689505VACITY
50/50
3.796
274729ELWOOD EC;1P
Adder
8.538
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
274735ELWOOD EC;4P
Adder
8.538
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
5.855
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
15.93
966881AG1-559 GEN
Solar/Wind Helper
0.312
316473AC1-191 GEN
Solar/Wind Helper
1.382
24728205BUCHG1
50/50
4.906
971277AH1-098 GEN
Solar/Wind Harmer
3.729
316045AC1-158 PL2
Solar/Wind Helper
4.183
966871AG1-558 GEN
Solar/Wind Helper
0.305
24290705CLAY-2
50/50
0.16
24415905BUCK
50/50
0.024
24734805WLF1G4
50/50
5.991
24735105WLF2G1
50/50
5.855
971329AH1-144 GEN
Solar/Wind Harmer
4.303
274731ELWOOD EC;2P
Adder
8.538
274733ELWOOD EC;3P
Adder
8.538
24290705CLAY-2
50/50
0.16
270494AE1-108_GEN
Solar/Wind Helper
3.288
24290605CLAY-1
50/50
0.16
24728305BUCHG2
50/50
4.906
274732ELWOOD EC;7P
Adder
8.538
316197AC1-042 GEN
Solar/Wind Helper
0.219
970823AG2-518 GEN
50/50
5.134
24290605CLAY-1
50/50
0.16
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
6.06
971461AH1-227 GEN
Solar/Wind Harmer
3.246
274730ELWOOD EC;6P
Adder
8.538
316044AC1-158 PL1
Solar/Wind Helper
1.308
247619Y1-049
50/50
0.034
316450AC1-158 RIC
Solar/Wind Helper
0.349
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.342
WECLTFEXP_WEC->PJM
CLTF
2.02
LAGNLTFEXP_LAGN->PJM
CLTF
12.4
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.515
CPLELTFEXP_CPLE->PJM
CLTF
1.948
SIGELTFEXP_SIGE->PJM
CLTF
0.306
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.921
NYPJM->LTFIMP_NY
CLTF
2.001
TVALTFEXP_TVA->PJM
CLTF
6.602
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
CBM West 2LTFEXP_CBM-W2->PJM
CBM
79.632
LGEELTFEXP_LGEE->PJM
CLTF
4.077
MECLTFEXP_MEC->PJM
CLTF
9.289
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:215.58 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.84
MW Contribution:
13.42
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.418

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:215.58 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.84
MW Contribution:
13.42
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.418

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.58 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.84
MW Contribution:
13.42
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.418

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.56 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.58
MW Contribution:
13.42
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.418

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:187.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2214.98
MW Contribution:
13.69
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.693

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:184.07 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2171.99
MW Contribution:
12.76
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
12.758

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:180.07 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2124.82
MW Contribution:
12.85
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
12.849

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 138KV_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 138KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:179.73 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2120.8
MW Contribution:
12.92
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
12.918

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:176.02 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:2077.06
MW Contribution:
12.84
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
12.836
CONTINGENCY 'AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 2           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 1           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#17030___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
END
CONTINGENCY 'PECO_P2-2_PHILLIPS-BUS_SRT-A
 DISCONNECT BUS 213888   /*PHLISCT1      18.0
 DISCONNECT BUS 213889   /*PHLISCT2      18.0
 DISCONNECT BUS 213892   /*PHLISL87     230.0
END
CONTINGENCY 'AEP_P2-2_#10265_05LEESVI 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242701 TO BUS 242802 CKT 1   /*05LEESVI     138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 247284 CKT 1   /*05LEESVI     138.0 - 05LEESVG      13.8
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'DVP_P7-1: LN 2114-535_SRT-A_SENS'
 OPEN BRANCH FROM BUS 235110 TO BUS 289543 CKT 1   /*01MDWBRK     500.0 - 05YEAT       500.0
 OPEN BRANCH FROM BUS 314085 TO BUS 314110 CKT 1   /*6REMNGCT     230.0 - 6ELK RUN     230.0
 OPEN BRANCH FROM BUS 314110 TO BUS 314125 CKT 1   /*6ELK RUN     230.0 - 6VINTHIL     230.0
 OPEN BUS 314110                                   /*6ELK RUN     230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 138KV_SRT-A'
 OPEN BUS 314348   /*2GRETN_1      69.0
 OPEN BUS 314667   /*4ALTVSTA     138.0
 OPEN BUS 314670   /*2ALTVSTA      69.0
 OPEN BUS 314680   /*2CHATHAM      69.0
 OPEN BUS 314685   /*2CHTM TP      69.0
 OPEN BUS 314698   /*2TAYLORS MIL  69.0
 OPEN BUS 314709   /*2GLADYS TAP   69.0
 OPEN BUS 314727   /*2CLIMAX DP    69.0
 OPEN BUS 314728   /*2CLMX TP      69.0
 OPEN BUS 314729   /*2GLADYS       69.0
 OPEN BUS 314730   /*3STONE MILL   69.0
 OPEN BUS 314731   /*2GRETNA       69.0
 OPEN BUS 314733   /*2GRNA DP      69.0
 OPEN BUS 314735   /*2ALTAVISTADP  69.0
 OPEN BUS 314736   /*2SHKO DP      69.0
 OPEN BUS 314738   /*2MT AIRY      69.0
 OPEN BUS 314739   /*2MT A TP      69.0
 OPEN BUS 316193   /*RENANTP       69.0
 OPEN BUS 316194   /*AC1-042 MAIN  69.0
 OPEN BUS 316195   /*AC1-042 COL   34.0
 OPEN BUS 316196   /*AC1-042 TERT  13.0
 OPEN BUS 316197   /*AC1-042 GEN    0.4
 OPEN BUS 316214   /*AC1-145 MAIN  69.0
 OPEN BUS 316215   /*AC1-145 COL2  34.5
 OPEN BUS 316216   /*AC1-145 COL1  34.5
 OPEN BUS 316217   /*AC1-145 GEN    0.6
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
8.38
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC115.66 %3610.0B4175.28
8.39
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC115.4 %3610.0B4165.98
8.38
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC115.26 %3610.0B4160.96
8.38
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC114.94 %3610.0B4149.41
8.38
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P1-2: LN 555_SRT-A
SingleAC112.06 %3220.44B3608.77
5.73
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC104.87 %3940.0C4131.96
6.45
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P1-2: LN 555_SRT-A
SingleAC111.74 %3220.44B3598.36
5.73
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC104.6 %3940.0C4121.29
6.45

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
8.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
7.157
971277AH1-098 GEN
Solar/Wind Harmer
5.174
970913AG2-568 GEN
Solar/Wind Harmer
7.67
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
964571AG1-320 GEN
Solar/Wind Harmer
6.355
972045AH1-571 GEN
Solar/Wind Harmer
1.437
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
276911AD2-131_GEN
Solar/Wind Harmer
0.879
24728805RICHG1
Adder
3.383
24699105WLD G1 C
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
8.233
274763LEE CO EC;4U
Adder
8.136
270383AD1-128 GEN
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274695ROCKY RD ;2P
Adder
9.717
970885AG2-551 GEN
Solar/Wind Harmer
2.025
270031AE2-169
Solar/Wind Harmer
3.328
964611AG1-324 GEN
Solar/Wind Harmer
0.453
958011AF2-095 GEN
Solar/Wind Harmer
8.691
270201AC2-176 GEN
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270069AE2-166 C O1
Solar/Wind Harmer
10.375
24734705WLF1G3
Adder
8.187
24734905WLF1G5
Adder
8.187
270399AC1-101 GEN
Solar/Wind Harmer
2.889
971981AH1-535 GEN
Solar/Wind Harmer
5.838
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
253406AD2-031_GEN
Solar/Wind Harmer
0.464
946321AF1-296 GEN
Solar/Wind Harmer
3.479
270291AC1-194 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
971029AG2-637 GEN
Solar/Wind Harmer
9.145
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.242
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148013FISHERV
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.267
24684605SMG4
50/50
2.21
970563AG2-360 GEN
50/50
45.796
962751AG1-124 GEN
Solar/Wind Harmer
12.886
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
972273AH1-721 GEN
Adder
89.23
970093AG2-073 GEN
Solar/Wind Harmer
6.071
971191AH1-055 GEN
Solar/Wind Harmer
18.034
972167AH1-666 GEN
Solar/Wind Harmer
5.413
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.251
970879AG2-548 GEN
Solar/Wind Harmer
4.688
942481AE2-261 GEN
Solar/Wind Harmer
18.979
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
12.283
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
946671AF1-331 GEN
Solar/Wind Harmer
0.653
970825AG2-519 GEN
Solar/Wind Harmer
4.603
274729ELWOOD EC;1P
Adder
14.264
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
3147983MERCK5
Solar/Wind Helper
0.198
24290705CLAY-2
50/50
0.252
958131AF2-107 GEN
Solar/Wind Harmer
5.335
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
960001AF2-291 GEN
Solar/Wind Harmer
0
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
970091AG2-072 GEN
Adder
73.941
971073AG2-665 GEN
Solar/Wind Harmer
1.065
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
970819AG2-516 GEN
Solar/Wind Harmer
7.371
274822ROCKFORD ;11
Adder
17.258
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
941551AE2-152 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
7.838
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
24735205WLF2G2
Adder
8.017
24723205RIVRG3
Adder
22.932
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
945681AF1-233 GEN
Solar/Wind Harmer
12.766
252516AE2-318_GEN
Solar/Wind Harmer
7.186
25194608D.CRK4
Adder
1.506
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
957471AF2-041 GEN
Solar/Wind Harmer
18.391
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.865
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
26.611
316499AE2-029_GEN
Solar/Wind Helper
1.726
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
971881AH1-461 GEN
50/50
14.967
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147123OTTER R
Solar/Wind Harmer
0.13
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24721905FLATG4
Adder
21.662
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971087AG2-675 GEN
Solar/Wind Harmer
3.318
274767LEE CO EC;8U
Adder
8.117
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
276806AD2-047 C O1
Solar/Wind Harmer
3.42
316192AB2-158 GEN
Solar/Wind Helper
1.845
316447AC1-158 HLD
Solar/Wind Helper
2.777
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
971125AH1-004 GEN
Solar/Wind Harmer
2.78
971587AH1-292 GEN
Solar/Wind Harmer
4.796
276916AD2-100_GEN
Solar/Wind Harmer
13.351
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.644
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
5.792
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
972043AH1-570 GEN
Solar/Wind Harmer
1.794
25194408D.CRK1
Adder
6.93
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276615X2-022 GEN
Solar/Wind Harmer
0.065
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960611AF2-352 GEN
Solar/Wind Harmer
2.071
966841AG1-555 GEN
Solar/Wind Harmer
0.701
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
972235AH1-702 GEN1
Adder
2.217
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274693ROCKY RD ;1P
Adder
9.622
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
274674JOLIET 9 ;6U
Adder
13.36
270599AE1-208 GEN
Solar/Wind Harmer
5.547
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316450AC1-158 RIC
Solar/Wind Helper
0.337
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
970281AG2-184 GEN
Solar/Wind Harmer
18.909
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
959341AF2-225 GEN
Solar/Wind Harmer
6.498
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
970169AG2-114 GEN
Solar/Wind Harmer
6.143
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274744AC1-111 GEN8
Adder
4.865
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
958391AF2-133 GEN
Solar/Wind Harmer
0.001
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.731
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
9.535
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
3429391JKCT 9G
Adder
8.393
958171AF2-111 GEN
Solar/Wind Harmer
16.661
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
24728705AND G3
Adder
7.274
959611AF2-252 GEN
Solar/Wind Harmer
2.071
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
274730ELWOOD EC;6P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316044AC1-158 PL1
Solar/Wind Helper
1.262
24684305SMG1
50/50
0.795
971329AH1-144 GEN
Solar/Wind Harmer
6.744
24734805WLF1G4
Adder
8.187
24735105WLF2G1
Adder
8.017
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
3429211JKCT 2G
Adder
11.861
972163AH1-664 GEN
Solar/Wind Harmer
7.559
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196508WSDLE4
Adder
7.759
270356AE2-297 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.696
274854TWINGROVE;U2
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.044
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.61
274746AC1-111 G10
Adder
4.865
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
971609AH1-304 GEN
Solar/Wind Harmer
0.988
964611AG1-324 GEN
Solar/Wind Harmer
2.357
316164AC1-076 GEN
Solar/Wind Helper
1.176
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
5.363
971061AG2-657 GEN
Solar/Wind Harmer
5.362
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
24691005MDL-2G C
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.033
270543AE2-219 C
Solar/Wind Harmer
4.252
274728ELWOOD EC;5P
Adder
14.264
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.089
24684505SMG3
50/50
1.341
3147312GRETNA
Solar/Wind Harmer
0.047
971687AH1-348 GEN
Solar/Wind Harmer
0.947
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252510AF1-249 C
Solar/Wind Harmer
0.048
276621W2-048 GEN
Solar/Wind Harmer
0.315
253398AE2-221_GEN2
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24386605FR-22G C
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
970569AG2-363 GEN
Solar/Wind Harmer
18.425
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276805AD2-038 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
964861AG1-349 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
315821AE2-092 GEN
Solar/Wind Helper
3.23
23583801GRNGAP
Solar/Wind Helper
4.295
970107AG2-081 GEN
Solar/Wind Harmer
2.085
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
1.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
960201AF2-311 GEN
Solar/Wind Harmer
5.7
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
274762LEE CO EC;3U
Adder
8.213
938861AE1-114 GEN
Solar/Wind Harmer
3.487
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
274696ROCKY RD ;4P
Adder
9.947
274697ROCKY RD ;3P
Adder
2.64
276893AG1-478 C
Solar/Wind Harmer
0.404
276897AD1-100 C
Solar/Wind Harmer
15.124
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
970941AG2-585 GEN
Solar/Wind Harmer
3.319
237061AD1-155 GEN
Solar/Wind Helper
1.647
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.195
24728305BUCHG2
50/50
7.157
24686505CER G6
Adder
9.865
3429241JKCT 3G
Adder
12.016
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
270437AC2-090 C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
7.447
24686405CER G5
Adder
9.787
970653AG2-424 GEN
Solar/Wind Harmer
0.705
970455AG2-298 GEN
Solar/Wind Harmer
2.725
965931AG1-462 GEN
Solar/Wind Harmer
15.863
965091AG1-374 GEN
Solar/Wind Harmer
18.636
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
24690905MDL-1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276843GEN-1.7
Solar/Wind Harmer
0.195
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
NYPJM->LTFIMP_NY
CLTF
3.255
TVALTFEXP_TVA->PJM
CLTF
10.596
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
LGEELTFEXP_LGEE->PJM
CLTF
6.756
MECLTFEXP_MEC->PJM
CLTF
15.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
WECLTFEXP_WEC->PJM
CLTF
3.368
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
CPLELTFEXP_CPLE->PJM
CLTF
6.213
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.66 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4175.28
MW Contribution:
8.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
7.18
971277AH1-098 GEN
Solar/Wind Harmer
7.43
970913AG2-568 GEN
Solar/Wind Harmer
9.375
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.774
339231AF1-038_GEN
Solar/Wind Harmer
1.925
964571AG1-320 GEN
Solar/Wind Harmer
8.222
972045AH1-571 GEN
Solar/Wind Harmer
1.989
927014AC1-188 GEN
Solar/Wind Harmer
1.537
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.603
971073AG2-665 GEN
Solar/Wind Harmer
7.39
25194508D.CRK3
Adder
1.304
276911AD2-131_GEN
Solar/Wind Harmer
3.891
24728805RICHG1
Adder
3.406
274765LEE CO EC;6U
Adder
8.284
274763LEE CO EC;4U
Adder
8.186
972236AH1-702 GEN2
Adder
1.94
274695ROCKY RD ;2P
Adder
9.779
238149AF1-291A_GEN
Solar/Wind Helper
0.122
316006AB2-029 C
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.356
316045AC1-158 PL2
Solar/Wind Helper
4.058
966871AG1-558 GEN
Solar/Wind Helper
0.307
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.387
966391AG1-508 GEN
Solar/Wind Harmer
6.384
270069AE2-166 C O1
Solar/Wind Harmer
14.894
24734705WLF1G3
Adder
8.213
24734905WLF1G5
Adder
8.213
270399AC1-101 GEN
Solar/Wind Harmer
5.575
971981AH1-535 GEN
Solar/Wind Harmer
12.593
339216AC1-074 GEN
Solar/Wind Harmer
1.652
972165AH1-665 GEN
Solar/Wind Harmer
7.834
971985AH1-537 GEN
Solar/Wind Harmer
17.394
253406AD2-031_GEN
Solar/Wind Harmer
1.153
270291AC1-194 GEN
Solar/Wind Harmer
4.567
946321AF1-296 GEN
Solar/Wind Harmer
9.347
274853TWINGROVE;U1
Solar/Wind Harmer
6.454
972267AH1-718 GEN
Adder
3.707
274823ROCKFORD ;21
Adder
17.239
274675JOLIET 29;7U
Adder
26.781
315616AA1-038_C
Solar/Wind Helper
3.299
3148013FISHERV
Solar/Wind Helper
0.301
316405AF2-144 C
Solar/Wind Helper
0.267
24386405FR-21G C
Solar/Wind Harmer
2.921
24684605SMG4
50/50
2.212
970563AG2-360 GEN
50/50
45.925
962751AG1-124 GEN
Solar/Wind Harmer
18.829
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.251
972273AH1-721 GEN
Adder
89.66
970093AG2-073 GEN
Solar/Wind Harmer
5.468
971191AH1-055 GEN
Solar/Wind Harmer
18.939
972167AH1-666 GEN
Solar/Wind Harmer
7.807
270186AC1-089 GEN
Solar/Wind Harmer
5.851
270367AC2-061_GEN
Solar/Wind Harmer
3.02
25196008MFTGT1
Adder
1.259
970879AG2-548 GEN
Solar/Wind Harmer
7.39
942481AE2-261 GEN
Solar/Wind Harmer
27.366
971993AH1-541 GEN
Solar/Wind Harmer
8.371
253394AE2-221_GEN
Solar/Wind Harmer
4.079
274729ELWOOD EC;1P
Adder
14.355
3147983MERCK5
Solar/Wind Helper
0.199
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.446
958131AF2-107 GEN
Solar/Wind Harmer
7.107
971403AH1-188 GEN
Solar/Wind Harmer
18.915
944971AF1-162 GEN
Solar/Wind Harmer
9.1
960001AF2-291 GEN
Solar/Wind Harmer
3.133
970653AG2-424 GEN
Solar/Wind Harmer
4.903
3429421JKCT 10G
Adder
8.441
339221AD2-048_GEN
Solar/Wind Harmer
1.518
970091AG2-072 GEN
Adder
74.384
971073AG2-665 GEN
Solar/Wind Harmer
1.074
276686W4-005 GEN3
Solar/Wind Harmer
2.739
963741AG1-226 GEN
Solar/Wind Harmer
40.583
270222AC2-111 GEN
Solar/Wind Harmer
4.015
276655WTG1_EQ
Solar/Wind Harmer
7.791
274822ROCKFORD ;11
Adder
17.365
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
270574AD1-017 GEN2
Solar/Wind Harmer
8.474
270336AE1-100 GEN
Solar/Wind Harmer
2.754
943811AF1-049 GEN
Solar/Wind Harmer
5.701
24735205WLF2G2
Adder
8.042
24723205RIVRG3
Adder
23.046
972203AH1-686 GEN
Adder
2.716
964901AG1-354 GEN
Solar/Wind Harmer
15.55
339241AF1-083 GEN
Solar/Wind Harmer
1.722
943111AE2-339 GEN
Solar/Wind Harmer
0.887
945681AF1-233 GEN
Solar/Wind Harmer
18.414
252516AE2-318_GEN
Solar/Wind Harmer
9.259
25194608D.CRK4
Adder
1.517
253316AC1-085 GEN3
Solar/Wind Harmer
7.64
946171AF1-282 GEN
Solar/Wind Harmer
9.125
24728605AND G2
Adder
3.5
274828WAUKEGAN ;BP
Adder
9.706
274682WAUKEGAN ;7U
Adder
15.786
274745AC1-111 GEN9
Adder
4.896
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
274676JOLIET 29;8U
Adder
22.605
316499AE2-029_GEN
Solar/Wind Helper
1.728
316095T157 G97
Solar/Wind Helper
1.135
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.393
971881AH1-461 GEN
50/50
15.01
943031AE2-326 GEN
Solar/Wind Harmer
6.794
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.957
960911AF2-382 GEN
Solar/Wind Harmer
10.976
972103AH1-617 GEN
Solar/Wind Harmer
25.917
24721905FLATG4
Adder
21.789
252519AF1-045_GEN
Solar/Wind Harmer
3.37
25194608D.CRK4
Adder
1.517
252524AE2-267 GEN
Solar/Wind Harmer
1.45
957381AF2-032 GEN
Solar/Wind Harmer
1.829
253317AC1-085 GEN4
Solar/Wind Harmer
7.64
946181AF1-283 GEN
Solar/Wind Harmer
11.863
24728505AND G1
Adder
3.5
276785W4-005 GEN1
Solar/Wind Harmer
2.739
971087AG2-675 GEN
Solar/Wind Harmer
3.338
274767LEE CO EC;8U
Adder
8.167
274682WAUKEGAN ;7U
Adder
15.786
274734ELWOOD EC;8P
Adder
14.355
274736ELWOOD EC;9P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
316192AB2-158 GEN
Solar/Wind Helper
1.852
316447AC1-158 HLD
Solar/Wind Helper
2.79
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.222
270583AD2-179 GEN
Solar/Wind Harmer
20.746
270214AC2-123 GEN
Solar/Wind Harmer
4.317
971225AH1-072 GEN
Solar/Wind Harmer
2.738
971227AH1-073 GEN
Solar/Wind Harmer
2.738
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.669
971485AH1-239 GEN
Solar/Wind Harmer
8.528
964781AG1-341 GEN
Solar/Wind Harmer
11.012
942891AE2-308 GEN
Solar/Wind Harmer
10.222
972043AH1-570 GEN
Solar/Wind Harmer
2.487
25194408D.CRK1
Adder
6.977
945391AF1-204 GEN
Solar/Wind Harmer
12.785
276615X2-022 GEN
Solar/Wind Harmer
1.781
24728905RICHG2
Adder
3.406
960251AF2-316 GEN
Solar/Wind Harmer
13.508
960611AF2-352 GEN
Solar/Wind Harmer
2.083
274764LEE CO EC;5U
Adder
8.284
972235AH1-702 GEN1
Adder
2.231
274683WAUKEGAN ;8U
Adder
18.516
274683WAUKEGAN ;8U
Adder
15.608
274693ROCKY RD ;1P
Adder
9.683
274674JOLIET 9 ;6U
Adder
13.445
3132123MT JACKSON
Solar/Wind Helper
1.393
966001AG1-469 GEN
Solar/Wind Helper
0.321
238148AE2-230_GEN2
Solar/Wind Helper
0.426
316450AC1-158 RIC
Solar/Wind Helper
0.338
24723005RIVRG1
Adder
23.046
24723105RIVRG2
Adder
23.046
971125AH1-004 GEN
Solar/Wind Harmer
4.008
276916AD2-100_GEN
Solar/Wind Harmer
19.251
253370AE2-315 SEC1
Adder
1.749
316097T157 G90
Solar/Wind Helper
1.135
238147AE2-230_GEN1
Solar/Wind Helper
0.426
270197AD1-017 GEN1
Solar/Wind Harmer
2.542
970281AG2-184 GEN
Solar/Wind Harmer
27.213
962211AG1-066 GEN
Solar/Wind Harmer
3.011
270444AC2-157 GEN1
Solar/Wind Harmer
5.263
270445AC2-157 GEN2
Solar/Wind Harmer
5.263
253433AC1-085 GEN1
Solar/Wind Harmer
4.849
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
276763AC1-053 GEN1
Solar/Wind Harmer
3.586
276764AC1-053 GEN2
Solar/Wind Harmer
3.586
276668AB2-070 GEN1
Solar/Wind Harmer
2.006
276848AB2-070 GEN3
Solar/Wind Harmer
2.006
276849AB2-070 GEN2
Solar/Wind Harmer
2.006
959341AF2-225 GEN
Solar/Wind Harmer
13.389
274744AC1-111 GEN8
Adder
4.896
25306009OHH W.
Adder
2.518
274735ELWOOD EC;4P
Adder
14.355
253372AE2-315 SEC3
Adder
1.655
253372AE2-315 SEC3
Adder
1.655
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.846
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
970823AG2-518 GEN
50/50
8.391
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.737
958121AF2-106 GEN
Solar/Wind Harmer
9.417
270346AE1-212 GEN
Solar/Wind Harmer
13.976
270018AE2-047 C O1
Solar/Wind Harmer
1.823
971461AH1-227 GEN
Solar/Wind Harmer
7.023
970223AG2-152 GEN
Solar/Wind Harmer
17.677
270330AC1-082 GEN2
Solar/Wind Harmer
0.514
3429391JKCT 9G
Adder
8.441
957541AF2-048 GEN
Solar/Wind Harmer
1.537
958171AF2-111 GEN
Solar/Wind Harmer
24.034
252507AC2-088 GEN
Solar/Wind Harmer
1.676
25196608WSDLE5
Adder
7.893
970193AG2-126 GEN
Solar/Wind Harmer
13.761
24728705AND G3
Adder
7.32
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274730ELWOOD EC;6P
Adder
14.355
3147666LOUISA
Solar/Wind Helper
1.093
238152AF2-075_GEN
Solar/Wind Helper
0.608
316044AC1-158 PL1
Solar/Wind Helper
1.268
24684305SMG1
50/50
0.796
971329AH1-144 GEN
Solar/Wind Harmer
11.745
24734805WLF1G4
Adder
8.213
24735105WLF2G1
Adder
8.042
270400AC1-102 GEN
Solar/Wind Harmer
5.575
941621AE2-160 GEN
Adder
4.304
957241AF2-018 GEN
Solar/Wind Harmer
5.778
270053AF1-130 C
Solar/Wind Harmer
23.086
3429211JKCT 2G
Adder
11.928
972163AH1-664 GEN
Solar/Wind Harmer
9.793
944221AF1-090 GEN
Solar/Wind Harmer
10.074
25196508WSDLE4
Adder
7.812
971543AH1-269 GEN
50/50
12.26
24684705SMG5
50/50
0.846
971313AH1-133 GEN
Solar/Wind Harmer
9.348
971061AG2-657 GEN
Solar/Wind Harmer
11.048
25196108MFTGT2
Adder
1.433
25196108MFTGT2
Adder
1.331
25196408WSDLE3
Adder
8.125
25196308WSDLE2
Adder
8.054
25196208WSDLE1
Adder
8.034
25196708WSDLE6
Adder
8.014
274728ELWOOD EC;5P
Adder
14.355
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.321
316468AD1-105 GEN
Solar/Wind Helper
1.093
3141426STAFORD
Solar/Wind Helper
0.049
24387005FR-3G C
Solar/Wind Harmer
2.686
24684505SMG3
50/50
1.342
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.363
270331AC1-082 GEN3
Solar/Wind Harmer
0.515
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
71.001
25196008MFTGT1
Adder
1.3
252510AF1-249 C
Solar/Wind Harmer
0.385
276621W2-048 GEN
Solar/Wind Harmer
5.671
253398AE2-221_GEN2
Solar/Wind Harmer
4.079
939741AE1-205 GEN
Solar/Wind Harmer
17.852
274761LEE CO EC;2U
Adder
8.264
315821AE2-092 GEN
Solar/Wind Helper
3.236
23583801GRNGAP
Solar/Wind Helper
4.324
24386605FR-22G C
Solar/Wind Harmer
2.921
270013AE1-250 PV
Solar/Wind Harmer
3.251
339236AF1-050_GEN
Solar/Wind Harmer
1.88
970107AG2-081 GEN
Solar/Wind Harmer
3.006
962581AG1-107 GEN
Solar/Wind Harmer
4.757
961491AF2-440 GEN
Solar/Wind Harmer
1.977
970879AG2-548 GEN
Solar/Wind Harmer
1.074
276838X2-022 GEN2
Solar/Wind Harmer
0.212
274880W4-005 GEN4
Solar/Wind Harmer
2.739
276174W4-005 GEN2
Solar/Wind Harmer
2.739
970241AG2-163 GEN
Solar/Wind Harmer
22.546
960201AF2-311 GEN
Solar/Wind Harmer
9.005
942111AE2-223 GEN
Solar/Wind Harmer
7.317
274762LEE CO EC;3U
Adder
8.264
274696ROCKY RD ;4P
Adder
10.01
274697ROCKY RD ;3P
Adder
2.656
237061AD1-155 GEN
Solar/Wind Helper
1.655
316312AB1-027
Solar/Wind Helper
0.426
24387305FR-4G C
Solar/Wind Harmer
3.45
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.197
24728305BUCHG2
50/50
7.18
316217AC1-145 GEN
Solar/Wind Harmer
4.244
316197AC1-042 GEN
Solar/Wind Harmer
3.217
24686505CER G6
Adder
9.917
339211AE2-254 GEN
Solar/Wind Harmer
1.567
3429241JKCT 3G
Adder
12.084
965911AG1-460 GEN
Solar/Wind Harmer
1.277
944031AF1-071 GEN
Solar/Wind Harmer
0.903
276656WTG2_EQ
Solar/Wind Harmer
1.032
274766LEE CO EC;7U
Adder
8.167
274732ELWOOD EC;7P
Adder
14.355
274674JOLIET 9 ;6U
Adder
13.445
3148013FISHERV
Solar/Wind Helper
0.524
3147666LOUISA
Solar/Wind Helper
0.628
24385905FR-11G C
Solar/Wind Harmer
5.645
270356AE2-297 GEN
Solar/Wind Harmer
4.168
963841AG1-237 GEN
Solar/Wind Harmer
9.807
274854TWINGROVE;U2
Solar/Wind Harmer
6.319
270340AC2-060 GEN
Solar/Wind Harmer
2.703
276726Z2-087_GEN
Solar/Wind Harmer
7.058
274746AC1-111 G10
Adder
4.896
274731ELWOOD EC;2P
Adder
14.355
274733ELWOOD EC;3P
Adder
14.355
316164AC1-076 GEN
Solar/Wind Helper
1.182
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.813
24686405CER G5
Adder
9.839
270329AC1-082 GEN1
Solar/Wind Harmer
0.514
339255AE2-071 GEN
Solar/Wind Harmer
1.222
339250AF1-203 GEN
Solar/Wind Harmer
0.629
339206AE1-143 GEN
Solar/Wind Harmer
2.213
970653AG2-424 GEN
Solar/Wind Harmer
0.709
970455AG2-298 GEN
Solar/Wind Harmer
3.536
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
965931AG1-462 GEN
Solar/Wind Harmer
22.875
965091AG1-374 GEN
Solar/Wind Harmer
26.876
274760LEE CO EC;1U
Adder
8.264
24386205FR-12G C
Solar/Wind Harmer
2.911
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.452
WECLTFEXP_WEC->PJM
CLTF
3.389
LAGNLTFEXP_LAGN->PJM
CLTF
20.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.582
CPLELTFEXP_CPLE->PJM
CLTF
6.224
SIGELTFEXP_SIGE->PJM
CLTF
0.51
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.053
NYPJM->LTFIMP_NY
CLTF
3.28
TVALTFEXP_TVA->PJM
CLTF
10.64
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.642
LGEELTFEXP_LGEE->PJM
CLTF
6.795
MECLTFEXP_MEC->PJM
CLTF
15.488
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4165.98
MW Contribution:
8.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
7.164
971277AH1-098 GEN
Solar/Wind Harmer
7.42
970913AG2-568 GEN
Solar/Wind Harmer
9.345
942751AE2-291 GEN
Solar/Wind Harmer
10.376
966021AG1-471 GEN
Solar/Wind Harmer
5.755
339231AF1-038_GEN
Solar/Wind Harmer
1.919
964571AG1-320 GEN
Solar/Wind Harmer
8.191
972045AH1-571 GEN
Solar/Wind Harmer
1.981
927014AC1-188 GEN
Solar/Wind Harmer
1.529
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.577
971073AG2-665 GEN
Solar/Wind Harmer
7.349
25194508D.CRK3
Adder
1.298
276911AD2-131_GEN
Solar/Wind Harmer
3.875
24728805RICHG1
Adder
3.39
274765LEE CO EC;6U
Adder
8.248
274763LEE CO EC;4U
Adder
8.151
972236AH1-702 GEN2
Adder
1.932
274695ROCKY RD ;2P
Adder
9.736
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.356
966871AG1-558 GEN
Solar/Wind Helper
0.307
316045AC1-158 PL2
Solar/Wind Helper
4.045
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.362
966391AG1-508 GEN
Solar/Wind Harmer
6.375
270069AE2-166 C O1
Solar/Wind Harmer
14.878
24734705WLF1G3
Adder
8.195
24734905WLF1G5
Adder
8.195
270399AC1-101 GEN
Solar/Wind Harmer
5.558
971981AH1-535 GEN
Solar/Wind Harmer
12.564
339216AC1-074 GEN
Solar/Wind Harmer
1.645
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.311
253406AD2-031_GEN
Solar/Wind Harmer
1.147
270291AC1-194 GEN
Solar/Wind Harmer
4.541
946321AF1-296 GEN
Solar/Wind Harmer
9.308
274853TWINGROVE;U1
Solar/Wind Harmer
6.427
972267AH1-718 GEN
Adder
3.691
274823ROCKFORD ;21
Adder
17.165
274675JOLIET 29;7U
Adder
26.663
274675JOLIET 29;7U
Adder
7.65
315616AA1-038_C
Solar/Wind Helper
3.298
3148013FISHERV
Solar/Wind Helper
0.301
316405AF2-144 C
Solar/Wind Helper
0.267
24386405FR-21G C
Solar/Wind Harmer
2.093
24684605SMG4
50/50
2.211
970563AG2-360 GEN
50/50
45.836
962751AG1-124 GEN
Solar/Wind Harmer
18.819
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.249
972273AH1-721 GEN
Adder
89.361
970093AG2-073 GEN
Solar/Wind Harmer
5.447
971191AH1-055 GEN
Solar/Wind Harmer
18.847
972167AH1-666 GEN
Solar/Wind Harmer
7.773
270186AC1-089 GEN
Solar/Wind Harmer
5.824
270367AC2-061_GEN
Solar/Wind Harmer
3.006
25196008MFTGT1
Adder
1.253
970879AG2-548 GEN
Solar/Wind Harmer
7.349
942481AE2-261 GEN
Solar/Wind Harmer
27.253
971993AH1-541 GEN
Solar/Wind Harmer
8.336
253394AE2-221_GEN
Solar/Wind Harmer
4.059
274729ELWOOD EC;1P
Adder
14.292
3147983MERCK5
Solar/Wind Helper
0.199
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.444
958131AF2-107 GEN
Solar/Wind Harmer
7.104
971403AH1-188 GEN
Solar/Wind Harmer
18.86
944971AF1-162 GEN
Solar/Wind Harmer
9.072
960001AF2-291 GEN
Solar/Wind Harmer
3.117
970653AG2-424 GEN
Solar/Wind Harmer
4.885
3429421JKCT 10G
Adder
8.408
339221AD2-048_GEN
Solar/Wind Harmer
1.511
970091AG2-072 GEN
Adder
74.077
971073AG2-665 GEN
Solar/Wind Harmer
1.068
276686W4-005 GEN3
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.407
270222AC2-111 GEN
Solar/Wind Harmer
3.996
276655WTG1_EQ
Solar/Wind Harmer
7.757
274822ROCKFORD ;11
Adder
17.29
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24735205WLF2G2
Adder
8.025
24723205RIVRG3
Adder
22.967
972203AH1-686 GEN
Adder
2.706
964901AG1-354 GEN
Solar/Wind Harmer
15.496
339241AF1-083 GEN
Solar/Wind Harmer
1.716
943111AE2-339 GEN
Solar/Wind Harmer
0.883
945681AF1-233 GEN
Solar/Wind Harmer
18.334
252516AE2-318_GEN
Solar/Wind Harmer
9.216
25194608D.CRK4
Adder
1.51
24728605AND G2
Adder
3.485
253316AC1-085 GEN3
Solar/Wind Harmer
7.603
946171AF1-282 GEN
Solar/Wind Harmer
9.081
274848CAMPGROVE;RU
Solar/Wind Harmer
5.733
274828WAUKEGAN ;BP
Adder
9.664
274682WAUKEGAN ;7U
Adder
15.718
274745AC1-111 GEN9
Adder
4.874
274676JOLIET 29;8U
Adder
26.663
316499AE2-029_GEN
Solar/Wind Helper
1.726
316095T157 G97
Solar/Wind Helper
1.13
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.39
971881AH1-461 GEN
50/50
14.98
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.922
960911AF2-382 GEN
Solar/Wind Harmer
10.95
972103AH1-617 GEN
Solar/Wind Harmer
25.844
24721905FLATG4
Adder
21.701
252519AF1-045_GEN
Solar/Wind Harmer
3.354
25194608D.CRK4
Adder
1.51
252524AE2-267 GEN
Solar/Wind Harmer
1.443
957381AF2-032 GEN
Solar/Wind Harmer
1.822
24728505AND G1
Adder
3.485
253317AC1-085 GEN4
Solar/Wind Harmer
7.603
946181AF1-283 GEN
Solar/Wind Harmer
11.806
276785W4-005 GEN1
Solar/Wind Harmer
2.728
971087AG2-675 GEN
Solar/Wind Harmer
3.324
274767LEE CO EC;8U
Adder
8.132
274682WAUKEGAN ;7U
Adder
15.718
274734ELWOOD EC;8P
Adder
14.292
274736ELWOOD EC;9P
Adder
14.292
316192AB2-158 GEN
Solar/Wind Helper
1.847
316447AC1-158 HLD
Solar/Wind Helper
2.781
3142416OLDCHRC
Solar/Wind Helper
0.579
3142416OLDCHRC
Solar/Wind Helper
0.222
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.664
971485AH1-239 GEN
Solar/Wind Harmer
8.501
964781AG1-341 GEN
Solar/Wind Harmer
10.975
942891AE2-308 GEN
Solar/Wind Harmer
10.182
972043AH1-570 GEN
Solar/Wind Harmer
2.477
25194408D.CRK1
Adder
6.944
945391AF1-204 GEN
Solar/Wind Harmer
12.73
276615X2-022 GEN
Solar/Wind Harmer
1.774
24728905RICHG2
Adder
3.39
960251AF2-316 GEN
Solar/Wind Harmer
13.412
960611AF2-352 GEN
Solar/Wind Harmer
2.075
274764LEE CO EC;5U
Adder
8.248
972235AH1-702 GEN1
Adder
2.222
274683WAUKEGAN ;8U
Adder
18.436
274683WAUKEGAN ;8U
Adder
15.54
274693ROCKY RD ;1P
Adder
9.64
274674JOLIET 9 ;6U
Adder
13.386
3132123MT JACKSON
Solar/Wind Helper
1.391
966001AG1-469 GEN
Solar/Wind Helper
0.321
238148AE2-230_GEN2
Solar/Wind Helper
0.424
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971225AH1-072 GEN
Solar/Wind Harmer
2.731
971227AH1-073 GEN
Solar/Wind Harmer
2.731
24723005RIVRG1
Adder
22.967
24723105RIVRG2
Adder
22.967
971125AH1-004 GEN
Solar/Wind Harmer
3.992
276916AD2-100_GEN
Solar/Wind Harmer
19.171
316097T157 G90
Solar/Wind Helper
1.13
238147AE2-230_GEN1
Solar/Wind Helper
0.424
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
970281AG2-184 GEN
Solar/Wind Harmer
27.137
962211AG1-066 GEN
Solar/Wind Harmer
3.002
270444AC2-157 GEN1
Solar/Wind Harmer
5.241
270445AC2-157 GEN2
Solar/Wind Harmer
5.241
253433AC1-085 GEN1
Solar/Wind Harmer
4.826
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
276668AB2-070 GEN1
Solar/Wind Harmer
1.998
276848AB2-070 GEN3
Solar/Wind Harmer
1.998
276849AB2-070 GEN2
Solar/Wind Harmer
1.998
959341AF2-225 GEN
Solar/Wind Harmer
13.331
274744AC1-111 GEN8
Adder
4.874
274735ELWOOD EC;4P
Adder
14.292
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.844
316450AC1-158 RIC
Solar/Wind Helper
0.337
970823AG2-518 GEN
50/50
8.383
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.733
958121AF2-106 GEN
Solar/Wind Harmer
9.406
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270018AE2-047 C O1
Solar/Wind Harmer
1.821
971461AH1-227 GEN
Solar/Wind Harmer
7.006
970223AG2-152 GEN
Solar/Wind Harmer
17.663
270330AC1-082 GEN2
Solar/Wind Harmer
0.512
3429391JKCT 9G
Adder
8.408
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.928
252507AC2-088 GEN
Solar/Wind Harmer
1.668
25196608WSDLE5
Adder
7.856
970193AG2-126 GEN
Solar/Wind Harmer
13.702
24728705AND G3
Adder
7.288
959611AF2-252 GEN
Solar/Wind Harmer
2.075
274730ELWOOD EC;6P
Adder
14.292
3147666LOUISA
Solar/Wind Helper
1.09
238152AF2-075_GEN
Solar/Wind Helper
0.606
316044AC1-158 PL1
Solar/Wind Helper
1.264
971543AH1-269 GEN
50/50
12.246
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
9.329
971061AG2-657 GEN
Solar/Wind Harmer
11.001
25196108MFTGT2
Adder
1.427
25196108MFTGT2
Adder
1.325
25196408WSDLE3
Adder
8.087
25196308WSDLE2
Adder
8.016
25196208WSDLE1
Adder
7.996
25196708WSDLE6
Adder
7.976
274728ELWOOD EC;5P
Adder
14.292
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.09
24387005FR-3G C
Solar/Wind Harmer
1.925
24684505SMG3
50/50
1.342
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.359
270331AC1-082 GEN3
Solar/Wind Harmer
0.513
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.673
25196008MFTGT1
Adder
1.294
252510AF1-249 C
Solar/Wind Harmer
0.384
276621W2-048 GEN
Solar/Wind Harmer
5.648
253398AE2-221_GEN2
Solar/Wind Harmer
4.059
939741AE1-205 GEN
Solar/Wind Harmer
17.775
274761LEE CO EC;2U
Adder
8.229
315821AE2-092 GEN
Solar/Wind Helper
3.232
23583801GRNGAP
Solar/Wind Helper
4.304
24386605FR-22G C
Solar/Wind Harmer
2.093
270013AE1-250 PV
Solar/Wind Harmer
3.249
339236AF1-050_GEN
Solar/Wind Harmer
1.873
970107AG2-081 GEN
Solar/Wind Harmer
2.994
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
970879AG2-548 GEN
Solar/Wind Harmer
1.068
276838X2-022 GEN2
Solar/Wind Harmer
0.211
274880W4-005 GEN4
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
970241AG2-163 GEN
Solar/Wind Harmer
22.448
960201AF2-311 GEN
Solar/Wind Harmer
8.941
942111AE2-223 GEN
Solar/Wind Harmer
7.286
274762LEE CO EC;3U
Adder
8.229
274696ROCKY RD ;4P
Adder
9.966
274697ROCKY RD ;3P
Adder
2.645
237061AD1-155 GEN
Solar/Wind Helper
1.65
316312AB1-027
Solar/Wind Helper
0.425
24387305FR-4G C
Solar/Wind Harmer
2.471
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.196
24728305BUCHG2
50/50
7.164
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
24686505CER G6
Adder
9.881
339211AE2-254 GEN
Solar/Wind Harmer
1.561
3429241JKCT 3G
Adder
12.037
965911AG1-460 GEN
Solar/Wind Harmer
1.272
944031AF1-071 GEN
Solar/Wind Harmer
0.899
276656WTG2_EQ
Solar/Wind Harmer
1.027
274766LEE CO EC;7U
Adder
8.132
274732ELWOOD EC;7P
Adder
14.292
274674JOLIET 9 ;6U
Adder
13.386
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.627
24385905FR-11G C
Solar/Wind Harmer
4.044
24684305SMG1
50/50
0.796
971329AH1-144 GEN
Solar/Wind Harmer
11.729
24734805WLF1G4
Adder
8.195
24735105WLF2G1
Adder
8.025
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.288
957241AF2-018 GEN
Solar/Wind Harmer
5.76
270053AF1-130 C
Solar/Wind Harmer
23.016
3429211JKCT 2G
Adder
11.881
972163AH1-664 GEN
Solar/Wind Harmer
9.75
944221AF1-090 GEN
Solar/Wind Harmer
10.032
25196508WSDLE4
Adder
7.775
270356AE2-297 GEN
Solar/Wind Harmer
4.149
963841AG1-237 GEN
Solar/Wind Harmer
9.765
274854TWINGROVE;U2
Solar/Wind Harmer
6.292
270340AC2-060 GEN
Solar/Wind Harmer
2.689
276726Z2-087_GEN
Solar/Wind Harmer
7.027
274746AC1-111 G10
Adder
4.874
274731ELWOOD EC;2P
Adder
14.292
274733ELWOOD EC;3P
Adder
14.292
316164AC1-076 GEN
Solar/Wind Helper
1.178
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.808
24686405CER G5
Adder
9.803
270329AC1-082 GEN1
Solar/Wind Harmer
0.512
339255AE2-071 GEN
Solar/Wind Harmer
1.218
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.205
970653AG2-424 GEN
Solar/Wind Harmer
0.706
970455AG2-298 GEN
Solar/Wind Harmer
3.522
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
965931AG1-462 GEN
Solar/Wind Harmer
22.779
965091AG1-374 GEN
Solar/Wind Harmer
26.762
274760LEE CO EC;1U
Adder
8.229
24386205FR-12G C
Solar/Wind Harmer
2.085
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.511
NYPJM->LTFIMP_NY
CLTF
3.263
TVALTFEXP_TVA->PJM
CLTF
10.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.186
LGEELTFEXP_LGEE->PJM
CLTF
6.768
MECLTFEXP_MEC->PJM
CLTF
15.426
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.331
WECLTFEXP_WEC->PJM
CLTF
3.374
LAGNLTFEXP_LAGN->PJM
CLTF
20.287
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.539
CPLELTFEXP_CPLE->PJM
CLTF
6.216
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.26 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4160.96
MW Contribution:
8.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
7.157
971277AH1-098 GEN
Solar/Wind Harmer
7.416
970913AG2-568 GEN
Solar/Wind Harmer
9.332
942751AE2-291 GEN
Solar/Wind Harmer
10.374
966021AG1-471 GEN
Solar/Wind Harmer
5.747
339231AF1-038_GEN
Solar/Wind Harmer
1.916
964571AG1-320 GEN
Solar/Wind Harmer
8.178
972045AH1-571 GEN
Solar/Wind Harmer
1.978
927014AC1-188 GEN
Solar/Wind Harmer
1.526
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.565
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.33
276911AD2-131_GEN
Solar/Wind Harmer
3.867
24728805RICHG1
Adder
3.383
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
24684605SMG4
50/50
2.21
970563AG2-360 GEN
50/50
45.796
962751AG1-124 GEN
Solar/Wind Harmer
18.814
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.247
972273AH1-721 GEN
Adder
89.23
970093AG2-073 GEN
Solar/Wind Harmer
5.438
971191AH1-055 GEN
Solar/Wind Harmer
18.807
972167AH1-666 GEN
Solar/Wind Harmer
7.758
270186AC1-089 GEN
Solar/Wind Harmer
5.812
270367AC2-061_GEN
Solar/Wind Harmer
3
25196008MFTGT1
Adder
1.251
970879AG2-548 GEN
Solar/Wind Harmer
7.33
942481AE2-261 GEN
Solar/Wind Harmer
27.203
971993AH1-541 GEN
Solar/Wind Harmer
8.32
253394AE2-221_GEN
Solar/Wind Harmer
4.05
274729ELWOOD EC;1P
Adder
14.264
3147983MERCK5
Solar/Wind Helper
0.198
274765LEE CO EC;6U
Adder
8.233
274763LEE CO EC;4U
Adder
8.136
972236AH1-702 GEN2
Adder
1.928
274695ROCKY RD ;2P
Adder
9.717
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.443
958131AF2-107 GEN
Solar/Wind Harmer
7.102
971403AH1-188 GEN
Solar/Wind Harmer
18.836
944971AF1-162 GEN
Solar/Wind Harmer
9.06
960001AF2-291 GEN
Solar/Wind Harmer
3.11
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
270574AD1-017 GEN2
Solar/Wind Harmer
8.466
270336AE1-100 GEN
Solar/Wind Harmer
2.749
943811AF1-049 GEN
Solar/Wind Harmer
5.692
24735205WLF2G2
Adder
8.017
24723205RIVRG3
Adder
22.932
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
15.473
339241AF1-083 GEN
Solar/Wind Harmer
1.713
943111AE2-339 GEN
Solar/Wind Harmer
0.882
945681AF1-233 GEN
Solar/Wind Harmer
18.298
252516AE2-318_GEN
Solar/Wind Harmer
9.197
25194608D.CRK4
Adder
1.506
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
7.586
946171AF1-282 GEN
Solar/Wind Harmer
9.062
274848CAMPGROVE;RU
Solar/Wind Harmer
5.723
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274745AC1-111 GEN9
Adder
4.865
274676JOLIET 29;8U
Adder
26.611
316499AE2-029_GEN
Solar/Wind Helper
1.726
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
971881AH1-461 GEN
50/50
14.967
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.906
960911AF2-382 GEN
Solar/Wind Harmer
10.939
972103AH1-617 GEN
Solar/Wind Harmer
25.812
24721905FLATG4
Adder
21.662
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
252524AE2-267 GEN
Solar/Wind Harmer
1.44
957381AF2-032 GEN
Solar/Wind Harmer
1.819
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
7.586
946181AF1-283 GEN
Solar/Wind Harmer
11.78
276785W4-005 GEN1
Solar/Wind Harmer
2.723
971087AG2-675 GEN
Solar/Wind Harmer
3.318
274767LEE CO EC;8U
Adder
8.117
274682WAUKEGAN ;7U
Adder
15.687
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
316192AB2-158 GEN
Solar/Wind Helper
1.845
316447AC1-158 HLD
Solar/Wind Helper
2.777
966391AG1-508 GEN
Solar/Wind Harmer
6.371
270069AE2-166 C O1
Solar/Wind Harmer
14.87
24734705WLF1G3
Adder
8.187
24734905WLF1G5
Adder
8.187
270399AC1-101 GEN
Solar/Wind Harmer
5.551
971981AH1-535 GEN
Solar/Wind Harmer
12.552
339216AC1-074 GEN
Solar/Wind Harmer
1.642
972165AH1-665 GEN
Solar/Wind Harmer
7.785
971985AH1-537 GEN
Solar/Wind Harmer
17.275
253406AD2-031_GEN
Solar/Wind Harmer
1.145
946321AF1-296 GEN
Solar/Wind Harmer
9.291
274853TWINGROVE;U1
Solar/Wind Harmer
6.415
270291AC1-194 GEN
Solar/Wind Harmer
4.529
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
315616AA1-038_C
Solar/Wind Helper
3.297
3148013FISHERV
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.267
24386405FR-21G C
Solar/Wind Harmer
2.088
270583AD2-179 GEN
Solar/Wind Harmer
20.71
270214AC2-123 GEN
Solar/Wind Harmer
4.308
971225AH1-072 GEN
Solar/Wind Harmer
2.728
971227AH1-073 GEN
Solar/Wind Harmer
2.728
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
971125AH1-004 GEN
Solar/Wind Harmer
3.985
276916AD2-100_GEN
Solar/Wind Harmer
19.136
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
270197AD1-017 GEN1
Solar/Wind Harmer
2.54
970281AG2-184 GEN
Solar/Wind Harmer
27.103
962211AG1-066 GEN
Solar/Wind Harmer
2.998
270444AC2-157 GEN1
Solar/Wind Harmer
5.231
270445AC2-157 GEN2
Solar/Wind Harmer
5.231
253433AC1-085 GEN1
Solar/Wind Harmer
4.815
253432AC1-085 GEN2
Solar/Wind Harmer
0.242
276763AC1-053 GEN1
Solar/Wind Harmer
3.564
276764AC1-053 GEN2
Solar/Wind Harmer
3.564
276668AB2-070 GEN1
Solar/Wind Harmer
1.994
276848AB2-070 GEN3
Solar/Wind Harmer
1.994
276849AB2-070 GEN2
Solar/Wind Harmer
1.994
959341AF2-225 GEN
Solar/Wind Harmer
13.306
274744AC1-111 GEN8
Adder
4.865
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.662
971485AH1-239 GEN
Solar/Wind Harmer
8.488
964781AG1-341 GEN
Solar/Wind Harmer
10.959
942891AE2-308 GEN
Solar/Wind Harmer
10.165
972043AH1-570 GEN
Solar/Wind Harmer
2.472
25194408D.CRK1
Adder
6.93
945391AF1-204 GEN
Solar/Wind Harmer
12.706
276615X2-022 GEN
Solar/Wind Harmer
1.77
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
13.37
960611AF2-352 GEN
Solar/Wind Harmer
2.071
274764LEE CO EC;5U
Adder
8.233
972235AH1-702 GEN1
Adder
2.217
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274693ROCKY RD ;1P
Adder
9.622
274674JOLIET 9 ;6U
Adder
13.36
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316450AC1-158 RIC
Solar/Wind Helper
0.337
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.731
958121AF2-106 GEN
Solar/Wind Harmer
9.401
270346AE1-212 GEN
Solar/Wind Harmer
13.925
270018AE2-047 C O1
Solar/Wind Harmer
1.82
971461AH1-227 GEN
Solar/Wind Harmer
6.998
970223AG2-152 GEN
Solar/Wind Harmer
17.657
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
3429391JKCT 9G
Adder
8.393
957541AF2-048 GEN
Solar/Wind Harmer
1.526
958171AF2-111 GEN
Solar/Wind Harmer
23.881
252507AC2-088 GEN
Solar/Wind Harmer
1.664
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
13.676
24728705AND G3
Adder
7.274
959611AF2-252 GEN
Solar/Wind Harmer
2.071
274730ELWOOD EC;6P
Adder
14.264
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316044AC1-158 PL1
Solar/Wind Helper
1.262
970653AG2-424 GEN
Solar/Wind Harmer
4.877
3429421JKCT 10G
Adder
8.393
339221AD2-048_GEN
Solar/Wind Harmer
1.508
970091AG2-072 GEN
Adder
73.941
971073AG2-665 GEN
Solar/Wind Harmer
1.065
276686W4-005 GEN3
Solar/Wind Harmer
2.723
963741AG1-226 GEN
Solar/Wind Harmer
40.329
270222AC2-111 GEN
Solar/Wind Harmer
3.988
276655WTG1_EQ
Solar/Wind Harmer
7.743
274822ROCKFORD ;11
Adder
17.258
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
9.321
971061AG2-657 GEN
Solar/Wind Harmer
10.98
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
274728ELWOOD EC;5P
Adder
14.264
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.089
24387005FR-3G C
Solar/Wind Harmer
1.921
24684505SMG3
50/50
1.341
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.358
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252510AF1-249 C
Solar/Wind Harmer
0.383
276621W2-048 GEN
Solar/Wind Harmer
5.637
253398AE2-221_GEN2
Solar/Wind Harmer
4.05
939741AE1-205 GEN
Solar/Wind Harmer
17.741
274761LEE CO EC;2U
Adder
8.213
315821AE2-092 GEN
Solar/Wind Helper
3.23
23583801GRNGAP
Solar/Wind Helper
4.295
24386605FR-22G C
Solar/Wind Harmer
2.088
270013AE1-250 PV
Solar/Wind Harmer
3.247
339236AF1-050_GEN
Solar/Wind Harmer
1.871
970107AG2-081 GEN
Solar/Wind Harmer
2.988
962581AG1-107 GEN
Solar/Wind Harmer
4.724
961491AF2-440 GEN
Solar/Wind Harmer
1.963
970879AG2-548 GEN
Solar/Wind Harmer
1.065
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.723
276174W4-005 GEN2
Solar/Wind Harmer
2.723
970241AG2-163 GEN
Solar/Wind Harmer
22.405
960201AF2-311 GEN
Solar/Wind Harmer
8.913
942111AE2-223 GEN
Solar/Wind Harmer
7.272
274762LEE CO EC;3U
Adder
8.213
274696ROCKY RD ;4P
Adder
9.947
274697ROCKY RD ;3P
Adder
2.64
237061AD1-155 GEN
Solar/Wind Helper
1.647
24387305FR-4G C
Solar/Wind Harmer
2.467
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.195
24728305BUCHG2
50/50
7.157
316217AC1-145 GEN
Solar/Wind Harmer
4.241
316197AC1-042 GEN
Solar/Wind Harmer
3.215
24686505CER G6
Adder
9.865
339211AE2-254 GEN
Solar/Wind Harmer
1.559
3429241JKCT 3G
Adder
12.016
965911AG1-460 GEN
Solar/Wind Harmer
1.269
944031AF1-071 GEN
Solar/Wind Harmer
0.897
276656WTG2_EQ
Solar/Wind Harmer
1.025
274766LEE CO EC;7U
Adder
8.117
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
24385905FR-11G C
Solar/Wind Harmer
4.036
24684305SMG1
50/50
0.795
971329AH1-144 GEN
Solar/Wind Harmer
11.722
24734805WLF1G4
Adder
8.187
24735105WLF2G1
Adder
8.017
270400AC1-102 GEN
Solar/Wind Harmer
5.551
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
5.752
270053AF1-130 C
Solar/Wind Harmer
22.985
3429211JKCT 2G
Adder
11.861
972163AH1-664 GEN
Solar/Wind Harmer
9.732
944221AF1-090 GEN
Solar/Wind Harmer
10.014
25196508WSDLE4
Adder
7.759
270356AE2-297 GEN
Solar/Wind Harmer
4.141
963841AG1-237 GEN
Solar/Wind Harmer
9.746
274854TWINGROVE;U2
Solar/Wind Harmer
6.28
270340AC2-060 GEN
Solar/Wind Harmer
2.683
276726Z2-087_GEN
Solar/Wind Harmer
7.014
274746AC1-111 G10
Adder
4.865
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
316164AC1-076 GEN
Solar/Wind Helper
1.176
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.805
24686405CER G5
Adder
9.787
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
339255AE2-071 GEN
Solar/Wind Harmer
1.216
339250AF1-203 GEN
Solar/Wind Harmer
0.626
339206AE1-143 GEN
Solar/Wind Harmer
2.202
970653AG2-424 GEN
Solar/Wind Harmer
0.705
970455AG2-298 GEN
Solar/Wind Harmer
3.516
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
965931AG1-462 GEN
Solar/Wind Harmer
22.737
965091AG1-374 GEN
Solar/Wind Harmer
26.711
274760LEE CO EC;1U
Adder
8.213
24386205FR-12G C
Solar/Wind Harmer
2.081
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
WECLTFEXP_WEC->PJM
CLTF
3.368
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
CPLELTFEXP_CPLE->PJM
CLTF
6.213
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
NYPJM->LTFIMP_NY
CLTF
3.255
TVALTFEXP_TVA->PJM
CLTF
10.596
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
LGEELTFEXP_LGEE->PJM
CLTF
6.756
MECLTFEXP_MEC->PJM
CLTF
15.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4149.41
MW Contribution:
8.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.211
970563AG2-360 GEN
50/50
45.815
962751AG1-124 GEN
Solar/Wind Harmer
18.82
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.249
972273AH1-721 GEN
Adder
89.284
970093AG2-073 GEN
Solar/Wind Harmer
5.442
971191AH1-055 GEN
Solar/Wind Harmer
18.819
24728205BUCHG1
50/50
7.16
971277AH1-098 GEN
Solar/Wind Harmer
7.418
970913AG2-568 GEN
Solar/Wind Harmer
9.337
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.751
339231AF1-038_GEN
Solar/Wind Harmer
1.917
964571AG1-320 GEN
Solar/Wind Harmer
8.183
972045AH1-571 GEN
Solar/Wind Harmer
1.979
927014AC1-188 GEN
Solar/Wind Harmer
1.527
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.569
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.336
276911AD2-131_GEN
Solar/Wind Harmer
3.87
24728805RICHG1
Adder
3.386
274765LEE CO EC;6U
Adder
8.239
274763LEE CO EC;4U
Adder
8.142
972236AH1-702 GEN2
Adder
1.93
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24735205WLF2G2
Adder
8.021
24723205RIVRG3
Adder
22.944
972203AH1-686 GEN
Adder
2.703
964901AG1-354 GEN
Solar/Wind Harmer
15.482
971881AH1-461 GEN
50/50
14.973
943031AE2-326 GEN
Solar/Wind Harmer
6.783
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.919
960911AF2-382 GEN
Solar/Wind Harmer
10.944
972103AH1-617 GEN
Solar/Wind Harmer
25.825
24721905FLATG4
Adder
21.675
252519AF1-045_GEN
Solar/Wind Harmer
3.349
25194608D.CRK4
Adder
1.508
252524AE2-267 GEN
Solar/Wind Harmer
1.441
957381AF2-032 GEN
Solar/Wind Harmer
1.82
24728505AND G1
Adder
3.48
253317AC1-085 GEN4
Solar/Wind Harmer
7.592
946181AF1-283 GEN
Solar/Wind Harmer
11.789
276785W4-005 GEN1
Solar/Wind Harmer
2.725
971087AG2-675 GEN
Solar/Wind Harmer
3.32
274767LEE CO EC;8U
Adder
8.123
274682WAUKEGAN ;7U
Adder
15.699
274734ELWOOD EC;8P
Adder
14.275
274736ELWOOD EC;9P
Adder
14.275
316192AB2-158 GEN
Solar/Wind Helper
1.844
316447AC1-158 HLD
Solar/Wind Helper
2.775
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.357
966391AG1-508 GEN
Solar/Wind Harmer
6.373
270069AE2-166 C O1
Solar/Wind Harmer
14.876
24734705WLF1G3
Adder
8.191
24734905WLF1G5
Adder
8.191
270583AD2-179 GEN
Solar/Wind Harmer
20.716
270214AC2-123 GEN
Solar/Wind Harmer
4.31
971225AH1-072 GEN
Solar/Wind Harmer
2.729
971227AH1-073 GEN
Solar/Wind Harmer
2.729
24723005RIVRG1
Adder
22.944
24723105RIVRG2
Adder
22.944
971125AH1-004 GEN
Solar/Wind Harmer
3.987
276916AD2-100_GEN
Solar/Wind Harmer
19.15
316097T157 G90
Solar/Wind Helper
1.127
238147AE2-230_GEN1
Solar/Wind Helper
0.423
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
970281AG2-184 GEN
Solar/Wind Harmer
27.117
962211AG1-066 GEN
Solar/Wind Harmer
3
270444AC2-157 GEN1
Solar/Wind Harmer
5.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.235
253433AC1-085 GEN1
Solar/Wind Harmer
4.819
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.567
276764AC1-053 GEN2
Solar/Wind Harmer
3.567
276668AB2-070 GEN1
Solar/Wind Harmer
1.995
276848AB2-070 GEN3
Solar/Wind Harmer
1.995
276849AB2-070 GEN2
Solar/Wind Harmer
1.995
959341AF2-225 GEN
Solar/Wind Harmer
13.316
274744AC1-111 GEN8
Adder
4.868
274735ELWOOD EC;4P
Adder
14.275
25306009OHH W.
Adder
2.502
3148463FAIRFLD
Solar/Wind Helper
0.726
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.842
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.665
971485AH1-239 GEN
Solar/Wind Harmer
8.494
964781AG1-341 GEN
Solar/Wind Harmer
10.966
942891AE2-308 GEN
Solar/Wind Harmer
10.171
972043AH1-570 GEN
Solar/Wind Harmer
2.474
25194408D.CRK1
Adder
6.935
945391AF1-204 GEN
Solar/Wind Harmer
12.715
276615X2-022 GEN
Solar/Wind Harmer
1.772
24728905RICHG2
Adder
3.386
960251AF2-316 GEN
Solar/Wind Harmer
13.38
960611AF2-352 GEN
Solar/Wind Harmer
2.072
274764LEE CO EC;5U
Adder
8.239
972235AH1-702 GEN1
Adder
2.219
274683WAUKEGAN ;8U
Adder
18.414
274683WAUKEGAN ;8U
Adder
15.522
274693ROCKY RD ;1P
Adder
9.629
274674JOLIET 9 ;6U
Adder
13.37
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316450AC1-158 RIC
Solar/Wind Helper
0.336
970823AG2-518 GEN
50/50
8.382
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.733
958121AF2-106 GEN
Solar/Wind Harmer
9.404
270346AE1-212 GEN
Solar/Wind Harmer
13.931
270018AE2-047 C O1
Solar/Wind Harmer
1.821
971461AH1-227 GEN
Solar/Wind Harmer
7.001
970223AG2-152 GEN
Solar/Wind Harmer
17.666
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
3429391JKCT 9G
Adder
8.399
957541AF2-048 GEN
Solar/Wind Harmer
1.527
958171AF2-111 GEN
Solar/Wind Harmer
23.897
252507AC2-088 GEN
Solar/Wind Harmer
1.666
25196608WSDLE5
Adder
7.845
970193AG2-126 GEN
Solar/Wind Harmer
13.686
24728705AND G3
Adder
7.279
959611AF2-252 GEN
Solar/Wind Harmer
2.072
274730ELWOOD EC;6P
Adder
14.275
3147666LOUISA
Solar/Wind Helper
1.088
238152AF2-075_GEN
Solar/Wind Helper
0.604
270399AC1-101 GEN
Solar/Wind Harmer
5.554
971981AH1-535 GEN
Solar/Wind Harmer
12.558
339216AC1-074 GEN
Solar/Wind Harmer
1.643
972165AH1-665 GEN
Solar/Wind Harmer
7.79
971985AH1-537 GEN
Solar/Wind Harmer
17.286
253406AD2-031_GEN
Solar/Wind Harmer
1.146
946321AF1-296 GEN
Solar/Wind Harmer
9.297
274853TWINGROVE;U1
Solar/Wind Harmer
6.419
270291AC1-194 GEN
Solar/Wind Harmer
4.532
972267AH1-718 GEN
Adder
3.687
274823ROCKFORD ;21
Adder
17.145
274675JOLIET 29;7U
Adder
26.631
274675JOLIET 29;7U
Adder
7.641
315616AA1-038_C
Solar/Wind Helper
3.296
3148013FISHERV
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.266
24386405FR-21G C
Solar/Wind Harmer
2.09
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.444
958131AF2-107 GEN
Solar/Wind Harmer
7.106
971403AH1-188 GEN
Solar/Wind Harmer
18.845
944971AF1-162 GEN
Solar/Wind Harmer
9.064
960001AF2-291 GEN
Solar/Wind Harmer
3.112
970653AG2-424 GEN
Solar/Wind Harmer
4.88
3429421JKCT 10G
Adder
8.399
339221AD2-048_GEN
Solar/Wind Harmer
1.509
970091AG2-072 GEN
Adder
73.991
971073AG2-665 GEN
Solar/Wind Harmer
1.066
276686W4-005 GEN3
Solar/Wind Harmer
2.725
963741AG1-226 GEN
Solar/Wind Harmer
40.358
270222AC2-111 GEN
Solar/Wind Harmer
3.991
276655WTG1_EQ
Solar/Wind Harmer
7.748
274822ROCKFORD ;11
Adder
17.27
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
972167AH1-666 GEN
Solar/Wind Harmer
7.764
270186AC1-089 GEN
Solar/Wind Harmer
5.816
270367AC2-061_GEN
Solar/Wind Harmer
3.002
25196008MFTGT1
Adder
1.252
970879AG2-548 GEN
Solar/Wind Harmer
7.336
942481AE2-261 GEN
Solar/Wind Harmer
27.222
971993AH1-541 GEN
Solar/Wind Harmer
8.326
253394AE2-221_GEN
Solar/Wind Harmer
4.053
274729ELWOOD EC;1P
Adder
14.275
3147983MERCK5
Solar/Wind Helper
0.198
971543AH1-269 GEN
50/50
12.244
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
9.325
971061AG2-657 GEN
Solar/Wind Harmer
10.986
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.323
25196408WSDLE3
Adder
8.076
25196308WSDLE2
Adder
8.005
25196208WSDLE1
Adder
7.985
25196708WSDLE6
Adder
7.965
274728ELWOOD EC;5P
Adder
14.275
3148133STUARTS
Solar/Wind Helper
0.313
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.088
24387005FR-3G C
Solar/Wind Harmer
1.922
24684505SMG3
50/50
1.342
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.358
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
70.578
25196008MFTGT1
Adder
1.293
252510AF1-249 C
Solar/Wind Harmer
0.383
276621W2-048 GEN
Solar/Wind Harmer
5.641
253398AE2-221_GEN2
Solar/Wind Harmer
4.053
939741AE1-205 GEN
Solar/Wind Harmer
17.754
274761LEE CO EC;2U
Adder
8.219
315821AE2-092 GEN
Solar/Wind Helper
3.228
23583801GRNGAP
Solar/Wind Helper
4.293
24386605FR-22G C
Solar/Wind Harmer
2.09
270013AE1-250 PV
Solar/Wind Harmer
3.249
339236AF1-050_GEN
Solar/Wind Harmer
1.872
970107AG2-081 GEN
Solar/Wind Harmer
2.99
962581AG1-107 GEN
Solar/Wind Harmer
4.728
961491AF2-440 GEN
Solar/Wind Harmer
1.965
970879AG2-548 GEN
Solar/Wind Harmer
1.066
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276174W4-005 GEN2
Solar/Wind Harmer
2.725
970241AG2-163 GEN
Solar/Wind Harmer
22.421
960201AF2-311 GEN
Solar/Wind Harmer
8.92
942111AE2-223 GEN
Solar/Wind Harmer
7.277
274762LEE CO EC;3U
Adder
8.219
274696ROCKY RD ;4P
Adder
9.954
274697ROCKY RD ;3P
Adder
2.642
237061AD1-155 GEN
Solar/Wind Helper
1.646
24387305FR-4G C
Solar/Wind Harmer
2.468
339241AF1-083 GEN
Solar/Wind Harmer
1.714
943111AE2-339 GEN
Solar/Wind Harmer
0.882
945681AF1-233 GEN
Solar/Wind Harmer
18.311
252516AE2-318_GEN
Solar/Wind Harmer
9.203
25194608D.CRK4
Adder
1.508
24728605AND G2
Adder
3.48
253316AC1-085 GEN3
Solar/Wind Harmer
7.592
946171AF1-282 GEN
Solar/Wind Harmer
9.068
274848CAMPGROVE;RU
Solar/Wind Harmer
5.727
274828WAUKEGAN ;BP
Adder
9.652
274682WAUKEGAN ;7U
Adder
15.699
274745AC1-111 GEN9
Adder
4.868
274676JOLIET 29;8U
Adder
26.631
316499AE2-029_GEN
Solar/Wind Helper
1.725
316095T157 G97
Solar/Wind Helper
1.127
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.196
24728305BUCHG2
50/50
7.16
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
24686505CER G6
Adder
9.87
339211AE2-254 GEN
Solar/Wind Harmer
1.56
3429241JKCT 3G
Adder
12.024
965911AG1-460 GEN
Solar/Wind Harmer
1.27
944031AF1-071 GEN
Solar/Wind Harmer
0.898
276656WTG2_EQ
Solar/Wind Harmer
1.026
274766LEE CO EC;7U
Adder
8.123
274732ELWOOD EC;7P
Adder
14.275
274674JOLIET 9 ;6U
Adder
13.37
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
24385905FR-11G C
Solar/Wind Harmer
4.039
24684305SMG1
50/50
0.796
971329AH1-144 GEN
Solar/Wind Harmer
11.725
24734805WLF1G4
Adder
8.191
24735105WLF2G1
Adder
8.021
270400AC1-102 GEN
Solar/Wind Harmer
5.554
941621AE2-160 GEN
Adder
4.283
957241AF2-018 GEN
Solar/Wind Harmer
5.755
270053AF1-130 C
Solar/Wind Harmer
22.996
3429211JKCT 2G
Adder
11.868
972163AH1-664 GEN
Solar/Wind Harmer
9.738
944221AF1-090 GEN
Solar/Wind Harmer
10.021
25196508WSDLE4
Adder
7.765
270356AE2-297 GEN
Solar/Wind Harmer
4.144
963841AG1-237 GEN
Solar/Wind Harmer
9.753
274854TWINGROVE;U2
Solar/Wind Harmer
6.285
270340AC2-060 GEN
Solar/Wind Harmer
2.685
276726Z2-087_GEN
Solar/Wind Harmer
7.019
274746AC1-111 G10
Adder
4.868
274731ELWOOD EC;2P
Adder
14.275
274733ELWOOD EC;3P
Adder
14.275
316164AC1-076 GEN
Solar/Wind Helper
1.176
274695ROCKY RD ;2P
Adder
9.725
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.036
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.809
24686405CER G5
Adder
9.792
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
339255AE2-071 GEN
Solar/Wind Harmer
1.217
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.203
970653AG2-424 GEN
Solar/Wind Harmer
0.706
970455AG2-298 GEN
Solar/Wind Harmer
3.519
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
965931AG1-462 GEN
Solar/Wind Harmer
22.754
965091AG1-374 GEN
Solar/Wind Harmer
26.73
274760LEE CO EC;1U
Adder
8.219
24386205FR-12G C
Solar/Wind Harmer
2.082
316044AC1-158 PL1
Solar/Wind Helper
1.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.367
NYPJM->LTFIMP_NY
CLTF
3.251
TVALTFEXP_TVA->PJM
CLTF
10.603
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.073
LGEELTFEXP_LGEE->PJM
CLTF
6.761
MECLTFEXP_MEC->PJM
CLTF
15.41
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.302
WECLTFEXP_WEC->PJM
CLTF
3.371
LAGNLTFEXP_LAGN->PJM
CLTF
20.273
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.54
CPLELTFEXP_CPLE->PJM
CLTF
6.22
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 555_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.06 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3608.77
MW Contribution:
5.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3137383CUSHAW
50/50
0.077
971277AH1-098 GEN
Solar/Wind Harmer
3.382
24728205BUCHG1
Adder
4.099
3152041BATH 4D
50/50
16.147
3151881LOWMORC
50/50
4.045
3151881LOWMORC
50/50
3.981
24416005BYLLESBY
50/50
0.02
971331AH1-145 GEN
Solar/Wind Harmer
12.166
966391AG1-508 GEN
Solar/Wind Harmer
1.298
270069AE2-166 C O1
Solar/Wind Harmer
6.845
24734705WLF1G3
Adder
4.973
24734905WLF1G5
Adder
4.973
3148013FISHERV
Solar/Wind Helper
0.175
24684605SMG4
50/50
1.533
962751AG1-124 GEN
Solar/Wind Harmer
9.113
3147312GRETNA
Solar/Wind Harmer
0.129
3146802CHATHAM
Solar/Wind Harmer
0.121
3147983MERCK5
Solar/Wind Helper
0.146
3151861LOWMORA
50/50
4.077
24290705CLAY-2
50/50
0.17
958131AF2-107 GEN
Solar/Wind Harmer
3.841
3152021BATH 2B
50/50
16.153
270205AE1-176
50/50
0.004
24728405LEESVG
50/50
0.203
24728405LEESVG
50/50
0.202
943811AF1-049 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.226
943031AE2-326 GEN
Solar/Wind Harmer
4.428
3147123OTTER R
Solar/Wind Harmer
0.09
270030AE2-140 GEN
Solar/Wind Harmer
14.101
960911AF2-382 GEN
Solar/Wind Harmer
4.591
270583AD2-179 GEN
Solar/Wind Harmer
9.704
247619Y1-049
50/50
0.033
942671AE2-283 GEN
Solar/Wind Harmer
4.019
3132123MT JACKSON
Solar/Wind Helper
1.116
3152031BATH 3C
50/50
16.174
3152011BATH 1A
50/50
16.153
3148463FAIRFLD
Solar/Wind Harmer
0.358
270197AD1-017 GEN1
Solar/Wind Harmer
0.971
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
24288905REUSENS
50/50
0.04
970823AG2-518 GEN
50/50
5.732
24290605CLAY-1
50/50
0.17
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
5.912
970223AG2-152 GEN
Solar/Wind Harmer
8.217
3152051BATH 5E
50/50
16.17
3151861LOWMORA
50/50
3.918
24684305SMG1
50/50
0.552
971329AH1-144 GEN
Solar/Wind Harmer
4.471
24734805WLF1G4
Adder
4.973
971543AH1-269 GEN
50/50
8.255
24684705SMG5
50/50
0.586
971313AH1-133 GEN
Solar/Wind Harmer
3.311
3148133STUARTS
Solar/Wind Helper
0.183
24684505SMG3
50/50
0.93
3147312GRETNA
Solar/Wind Harmer
0.032
23583801GRNGAP
Solar/Wind Helper
3.89
237061AD1-155 GEN
Solar/Wind Helper
1.4
3152061BATH 6F
50/50
16.198
24290605CLAY-1
50/50
0.17
24684405SMG2
50/50
1.523
24728305BUCHG2
Adder
4.099
3148013FISHERV
Solar/Wind Helper
0.304
24290705CLAY-2
50/50
0.17
24415905BUCK
50/50
0.022
941801AE2-185 GEN
Solar/Wind Harmer
5.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.084
WECLTFEXP_WEC->PJM
CLTF
1.751
LAGNLTFEXP_LAGN->PJM
CLTF
11.379
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.897
CPLELTFEXP_CPLE->PJM
CLTF
3.388
SIGELTFEXP_SIGE->PJM
CLTF
0.27
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.449
NYPJM->LTFIMP_NY
CLTF
2.913
TVALTFEXP_TVA->PJM
CLTF
6.026
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.738
LGEELTFEXP_LGEE->PJM
CLTF
3.585
MECLTFEXP_MEC->PJM
CLTF
8.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.87 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4131.96
MW Contribution:
6.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
4.988
3147123OTTER R
Solar/Wind Harmer
-0.011
270030AE2-140 GEN
Solar/Wind Harmer
22.56
960911AF2-382 GEN
Solar/Wind Harmer
7.439
316192AB2-158 GEN
Solar/Wind Helper
1.701
270583AD2-179 GEN
Solar/Wind Harmer
15.666
270214AC2-123 GEN
Solar/Wind Harmer
3.169
971225AH1-072 GEN
Solar/Wind Harmer
1.823
971227AH1-073 GEN
Solar/Wind Harmer
1.823
316097T157 G90
Solar/Wind Helper
1.083
238147AE2-230_GEN1
Solar/Wind Helper
0.403
3152031BATH 3C
50/50
17.148
3152011BATH 1A
50/50
17.126
3148463FAIRFLD
Solar/Wind Harmer
-0.069
270197AD1-017 GEN1
Solar/Wind Harmer
1.923
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
315651AD1-115 GEN
Solar/Wind Helper
0.785
247619Y1-049
50/50
0.037
942671AE2-283 GEN
Solar/Wind Harmer
6.661
3132123MT JACKSON
Solar/Wind Helper
1.31
966001AG1-469 GEN
Solar/Wind Helper
0.292
238148AE2-230_GEN2
Solar/Wind Helper
0.403
3152041BATH 4D
50/50
17.119
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.874
24416005BYLLESBY
50/50
0.022
315616AA1-038_C
Solar/Wind Harmer
14.227
971331AH1-145 GEN
Solar/Wind Harmer
13.713
966391AG1-508 GEN
Solar/Wind Harmer
4.679
270069AE2-166 C O1
Solar/Wind Harmer
10.973
24734705WLF1G3
Adder
5.611
24734905WLF1G5
Adder
5.611
3148013FISHERV
Solar/Wind Helper
0.263
3151861LOWMORA
50/50
7.039
24290705CLAY-2
50/50
0.191
270173AC1-122 GEN
Solar/Wind Harmer
2.679
958131AF2-107 GEN
Solar/Wind Harmer
5.401
971403AH1-188 GEN
Solar/Wind Harmer
12.18
3132273ORANGE
Solar/Wind Helper
0.051
23546401DTGZ2-030
Solar/Wind Helper
0.075
24684605SMG4
50/50
1.709
962751AG1-124 GEN
Solar/Wind Harmer
14.722
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
270016AE1-250 BESS
Solar/Wind Harmer
2.406
3147983MERCK5
Solar/Wind Helper
0.183
971543AH1-269 GEN
50/50
9.295
24684705SMG5
50/50
0.653
971313AH1-133 GEN
Solar/Wind Harmer
6.499
3148133STUARTS
Solar/Wind Helper
0.274
24684505SMG3
50/50
1.037
3147312GRETNA
Solar/Wind Harmer
-0.004
971687AH1-348 GEN
Solar/Wind Harmer
0.905
315821AE2-092 GEN
Solar/Wind Helper
2.905
23583801GRNGAP
Solar/Wind Helper
4.13
270013AE1-250 PV
Solar/Wind Harmer
2.406
237061AD1-155 GEN
Solar/Wind Helper
1.565
3152021BATH 2B
50/50
17.126
270205AE1-176
50/50
0.005
24728405LEESVG
50/50
0.226
24728405LEESVG
50/50
0.225
270574AD1-017 GEN2
Solar/Wind Harmer
6.411
270336AE1-100 GEN
Solar/Wind Harmer
2.015
943811AF1-049 GEN
Solar/Wind Harmer
4.146
24735205WLF2G2
Adder
5.477
316499AE2-029_GEN
Solar/Wind Helper
1.577
316095T157 G97
Solar/Wind Helper
1.083
3152061BATH 6F
50/50
17.174
24290605CLAY-1
50/50
0.191
24684405SMG2
50/50
1.698
316217AC1-145 GEN
Solar/Wind Harmer
3.261
316197AC1-042 GEN
Solar/Wind Harmer
2.472
24728305BUCHG2
Adder
4.632
3148013FISHERV
Solar/Wind Helper
0.457
3147666LOUISA
Solar/Wind Helper
0.578
3152051BATH 5E
50/50
17.143
3151861LOWMORA
50/50
6.764
24684305SMG1
50/50
0.615
971329AH1-144 GEN
Solar/Wind Harmer
8.759
24734805WLF1G4
Adder
5.611
24735105WLF2G1
Adder
5.477
316164AC1-076 GEN
Solar/Wind Helper
1.099
3137383CUSHAW
50/50
0.133
971277AH1-098 GEN
Solar/Wind Harmer
5.459
24728205BUCHG1
Adder
4.632
970913AG2-568 GEN
Solar/Wind Harmer
6.181
238149AF1-291A_GEN
Solar/Wind Helper
0.115
24290705CLAY-2
50/50
0.191
24415905BUCK
50/50
0.024
941801AE2-185 GEN
Solar/Wind Harmer
7.541
970823AG2-518 GEN
50/50
6.453
24288905REUSENS
50/50
0.044
24290605CLAY-1
50/50
0.191
958121AF2-106 GEN
Solar/Wind Harmer
7.113
270346AE1-212 GEN
Solar/Wind Harmer
9.774
270018AE2-047 C O1
Solar/Wind Harmer
1.335
970223AG2-152 GEN
Solar/Wind Harmer
12.946
971461AH1-227 GEN
Solar/Wind Harmer
4.675
3147666LOUISA
Solar/Wind Helper
1.004
238152AF2-075_GEN
Solar/Wind Helper
0.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.926
WECLTFEXP_WEC->PJM
CLTF
2.006
LAGNLTFEXP_LAGN->PJM
CLTF
12.819
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.276
CPLELTFEXP_CPLE->PJM
CLTF
3.542
SIGELTFEXP_SIGE->PJM
CLTF
0.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.709
NYPJM->LTFIMP_NY
CLTF
3.203
TVALTFEXP_TVA->PJM
CLTF
6.787
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.271
LGEELTFEXP_LGEE->PJM
CLTF
4.093
MECLTFEXP_MEC->PJM
CLTF
9.317
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 555_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.74 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3598.36
MW Contribution:
5.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3137383CUSHAW
50/50
0.077
971277AH1-098 GEN
Solar/Wind Harmer
3.382
24728205BUCHG1
Adder
4.099
3152041BATH 4D
50/50
16.147
3151881LOWMORC
50/50
4.045
3151881LOWMORC
50/50
3.981
24416005BYLLESBY
50/50
0.02
971331AH1-145 GEN
Solar/Wind Harmer
12.166
966391AG1-508 GEN
Solar/Wind Harmer
1.298
270069AE2-166 C O1
Solar/Wind Harmer
6.845
24734705WLF1G3
Adder
4.973
24734905WLF1G5
Adder
4.973
3148013FISHERV
Solar/Wind Helper
0.175
24684605SMG4
50/50
1.533
962751AG1-124 GEN
Solar/Wind Harmer
9.113
3147312GRETNA
Solar/Wind Harmer
0.129
3146802CHATHAM
Solar/Wind Harmer
0.121
3147983MERCK5
Solar/Wind Helper
0.146
3151861LOWMORA
50/50
4.077
24290705CLAY-2
50/50
0.17
958131AF2-107 GEN
Solar/Wind Harmer
3.841
3152021BATH 2B
50/50
16.153
270205AE1-176
50/50
0.004
24728405LEESVG
50/50
0.203
24728405LEESVG
50/50
0.202
943811AF1-049 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.226
943031AE2-326 GEN
Solar/Wind Harmer
4.428
3147123OTTER R
Solar/Wind Harmer
0.09
270030AE2-140 GEN
Solar/Wind Harmer
14.101
960911AF2-382 GEN
Solar/Wind Harmer
4.591
270583AD2-179 GEN
Solar/Wind Harmer
9.704
247619Y1-049
50/50
0.033
942671AE2-283 GEN
Solar/Wind Harmer
4.019
3132123MT JACKSON
Solar/Wind Helper
1.116
3152031BATH 3C
50/50
16.174
3152011BATH 1A
50/50
16.153
3148463FAIRFLD
Solar/Wind Harmer
0.358
270197AD1-017 GEN1
Solar/Wind Harmer
0.971
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
24288905REUSENS
50/50
0.04
970823AG2-518 GEN
50/50
5.732
24290605CLAY-1
50/50
0.17
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
5.912
970223AG2-152 GEN
Solar/Wind Harmer
8.217
3152051BATH 5E
50/50
16.17
3151861LOWMORA
50/50
3.918
24684305SMG1
50/50
0.552
971329AH1-144 GEN
Solar/Wind Harmer
4.471
24734805WLF1G4
Adder
4.973
971543AH1-269 GEN
50/50
8.255
24684705SMG5
50/50
0.586
971313AH1-133 GEN
Solar/Wind Harmer
3.311
3148133STUARTS
Solar/Wind Helper
0.183
24684505SMG3
50/50
0.93
3147312GRETNA
Solar/Wind Harmer
0.032
23583801GRNGAP
Solar/Wind Helper
3.89
237061AD1-155 GEN
Solar/Wind Helper
1.4
3152061BATH 6F
50/50
16.198
24290605CLAY-1
50/50
0.17
24684405SMG2
50/50
1.523
24728305BUCHG2
Adder
4.099
3148013FISHERV
Solar/Wind Helper
0.304
24290705CLAY-2
50/50
0.17
24415905BUCK
50/50
0.022
941801AE2-185 GEN
Solar/Wind Harmer
5.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.449
NYPJM->LTFIMP_NY
CLTF
2.913
TVALTFEXP_TVA->PJM
CLTF
6.026
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.738
LGEELTFEXP_LGEE->PJM
CLTF
3.585
MECLTFEXP_MEC->PJM
CLTF
8.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.084
WECLTFEXP_WEC->PJM
CLTF
1.751
LAGNLTFEXP_LAGN->PJM
CLTF
11.379
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.897
CPLELTFEXP_CPLE->PJM
CLTF
3.388
SIGELTFEXP_SIGE->PJM
CLTF
0.27

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.6 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4121.29
MW Contribution:
6.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
4.988
3147123OTTER R
Solar/Wind Harmer
-0.011
270030AE2-140 GEN
Solar/Wind Harmer
22.56
960911AF2-382 GEN
Solar/Wind Harmer
7.439
316192AB2-158 GEN
Solar/Wind Helper
1.701
270583AD2-179 GEN
Solar/Wind Harmer
15.666
270214AC2-123 GEN
Solar/Wind Harmer
3.169
971225AH1-072 GEN
Solar/Wind Harmer
1.823
971227AH1-073 GEN
Solar/Wind Harmer
1.823
316097T157 G90
Solar/Wind Helper
1.083
238147AE2-230_GEN1
Solar/Wind Helper
0.403
3152031BATH 3C
50/50
17.148
3152011BATH 1A
50/50
17.126
3148463FAIRFLD
Solar/Wind Harmer
-0.069
270197AD1-017 GEN1
Solar/Wind Harmer
1.923
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
247619Y1-049
50/50
0.037
942671AE2-283 GEN
Solar/Wind Harmer
6.661
3132123MT JACKSON
Solar/Wind Helper
1.31
966001AG1-469 GEN
Solar/Wind Helper
0.292
238148AE2-230_GEN2
Solar/Wind Helper
0.403
3152041BATH 4D
50/50
17.119
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.874
24416005BYLLESBY
50/50
0.022
315616AA1-038_C
Solar/Wind Harmer
14.227
971331AH1-145 GEN
Solar/Wind Harmer
13.713
966391AG1-508 GEN
Solar/Wind Harmer
4.679
270069AE2-166 C O1
Solar/Wind Harmer
10.973
24734705WLF1G3
Adder
5.611
24734905WLF1G5
Adder
5.611
3148013FISHERV
Solar/Wind Helper
0.263
3151861LOWMORA
50/50
7.039
24290705CLAY-2
50/50
0.191
270173AC1-122 GEN
Solar/Wind Harmer
2.679
958131AF2-107 GEN
Solar/Wind Harmer
5.401
971403AH1-188 GEN
Solar/Wind Harmer
12.18
3132273ORANGE
Solar/Wind Helper
0.051
23546401DTGZ2-030
Solar/Wind Helper
0.075
24684605SMG4
50/50
1.709
962751AG1-124 GEN
Solar/Wind Harmer
14.722
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
270016AE1-250 BESS
Solar/Wind Harmer
2.406
3147983MERCK5
Solar/Wind Helper
0.183
971543AH1-269 GEN
50/50
9.295
24684705SMG5
50/50
0.653
971313AH1-133 GEN
Solar/Wind Harmer
6.499
3148133STUARTS
Solar/Wind Helper
0.274
24684505SMG3
50/50
1.037
3147312GRETNA
Solar/Wind Harmer
-0.004
971687AH1-348 GEN
Solar/Wind Harmer
0.905
315821AE2-092 GEN
Solar/Wind Helper
2.905
23583801GRNGAP
Solar/Wind Helper
4.13
270013AE1-250 PV
Solar/Wind Harmer
2.406
237061AD1-155 GEN
Solar/Wind Helper
1.565
315651AD1-115 GEN
Solar/Wind Helper
0.785
3152021BATH 2B
50/50
17.126
270205AE1-176
50/50
0.005
24728405LEESVG
50/50
0.226
24728405LEESVG
50/50
0.225
270574AD1-017 GEN2
Solar/Wind Harmer
6.411
270336AE1-100 GEN
Solar/Wind Harmer
2.015
943811AF1-049 GEN
Solar/Wind Harmer
4.146
24735205WLF2G2
Adder
5.477
316499AE2-029_GEN
Solar/Wind Helper
1.577
316095T157 G97
Solar/Wind Helper
1.083
3152061BATH 6F
50/50
17.174
24290605CLAY-1
50/50
0.191
24684405SMG2
50/50
1.698
316217AC1-145 GEN
Solar/Wind Harmer
3.261
316197AC1-042 GEN
Solar/Wind Harmer
2.472
3152051BATH 5E
50/50
17.143
3151861LOWMORA
50/50
6.764
24684305SMG1
50/50
0.615
971329AH1-144 GEN
Solar/Wind Harmer
8.759
24734805WLF1G4
Adder
5.611
3137383CUSHAW
50/50
0.133
971277AH1-098 GEN
Solar/Wind Harmer
5.459
24728205BUCHG1
Adder
4.632
970913AG2-568 GEN
Solar/Wind Harmer
6.181
238149AF1-291A_GEN
Solar/Wind Helper
0.115
24290705CLAY-2
50/50
0.191
24415905BUCK
50/50
0.024
941801AE2-185 GEN
Solar/Wind Harmer
7.541
24735105WLF2G1
Adder
5.477
316164AC1-076 GEN
Solar/Wind Helper
1.099
24728305BUCHG2
Adder
4.632
3148013FISHERV
Solar/Wind Helper
0.457
3147666LOUISA
Solar/Wind Helper
0.578
970823AG2-518 GEN
50/50
6.453
24288905REUSENS
50/50
0.044
24290605CLAY-1
50/50
0.191
958121AF2-106 GEN
Solar/Wind Harmer
7.113
270346AE1-212 GEN
Solar/Wind Harmer
9.774
270018AE2-047 C O1
Solar/Wind Harmer
1.335
970223AG2-152 GEN
Solar/Wind Harmer
12.946
971461AH1-227 GEN
Solar/Wind Harmer
4.675
3147666LOUISA
Solar/Wind Helper
1.004
238152AF2-075_GEN
Solar/Wind Helper
0.575
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.709
NYPJM->LTFIMP_NY
CLTF
3.203
TVALTFEXP_TVA->PJM
CLTF
6.787
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.271
LGEELTFEXP_LGEE->PJM
CLTF
4.093
MECLTFEXP_MEC->PJM
CLTF
9.317
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.926
WECLTFEXP_WEC->PJM
CLTF
2.006
LAGNLTFEXP_LAGN->PJM
CLTF
12.819
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.276
CPLELTFEXP_CPLE->PJM
CLTF
3.542
SIGELTFEXP_SIGE->PJM
CLTF
0.308
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'DVP_P1-2: LN 555_SRT-A'
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
242519 to 314912 ckt 1
314901 to 314991 ckt 1
314991 to 314926 ckt 1

Winter Peak Analysis

The New Service Request AG2-518 was evaluated as a 80.0 MW (32.0 MW Capacity) injection in the AEP area.

AG2-518 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 80.0 MW (80.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-A_SENS
SingleAC220.41 %1180.0B2600.84
5.46
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 542T553_SRT-W_SENS
BreakerAC218.08 %1180.0B2573.38
5.46
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 553T564_SRT-W_SENS
BreakerAC217.06 %1180.0B2561.3
5.46
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC215.66 %1180.0B2544.77
5.45
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC194.03 %1180.0B2289.58
5.55
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC190.04 %1180.0B2242.41
5.17
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-A_SENS
SingleAC188.91 %1180.0B2229.09
13.64
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
BusAC186.82 %1180.0B2204.47
5.2
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 542T553_SRT-W_SENS
BreakerAC186.53 %1180.0B2201.01
13.65
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC186.02 %1180.0B2194.98
5.21
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 553T564_SRT-W_SENS
BreakerAC185.48 %1180.0B2188.66
13.66
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC180.89 %1180.0A2134.53
5.2
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC179.85 %1180.0B2122.24
13.63
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC161.03 %1180.0B1900.15
13.87
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC159.03 %1180.0B1876.56
12.92
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC155.04 %1180.0B1829.46
13.02
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
BusAC154.66 %1180.0B1824.96
13.17
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC150.34 %1180.0A1774.07
13.01

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:220.41 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2600.84
MW Contribution:
5.46
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.996
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.684
24728305BUCHG2
50/50
5.51
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.141
3142416OLDCHRC
Solar/Wind Helper
0.97
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.414
3142956BIRDNECK
Solar/Wind Helper
0.519
3143316POE
Solar/Wind Helper
1.304
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.352
3141913WHIT STONE
Solar/Wind Helper
0.35
3143226MDLTHAN
Solar/Wind Helper
0.36
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.189
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.255
3141726DUNNSVL
Solar/Wind Helper
1.412
24289905CRG1H
50/50
0.807
24290105CRG2H
50/50
0.813
24290005CRG1L
50/50
0.807
24290205CRG2L
50/50
0.807
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.11
316314AB2-024 C
Solar/Wind Helper
0.114
316316AC1-027 C
Solar/Wind Helper
0.089
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.284
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.239
3141196NOKESVL
Solar/Wind Helper
1.295
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.88
3143526WINTERP
Solar/Wind Helper
1.88
316404AE1-155 C
Solar/Wind Helper
0.718
316033AB2-134 GEN
Solar/Wind Helper
0.757
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.734
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.15
316369SG1_INVT
Solar/Wind Helper
0.52
315651AD1-115 GEN
Solar/Wind Helper
0.758
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.653
315662AE1-191 GEN
Solar/Wind Helper
0.451
315666AE1-190 GEN
Solar/Wind Helper
0.113
315697AD1-025 GEN
Solar/Wind Helper
0.797
316185AD1-033 GEN
Solar/Wind Helper
0.352
316280AD1-041 GEN
Solar/Wind Helper
0.282
316447AC1-158 HLD
Solar/Wind Helper
0.966
316044AC1-158 PL1
Solar/Wind Helper
0.439
316045AC1-158 PL2
Solar/Wind Helper
1.405
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.439
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.113
270583AD2-179 GEN
Solar/Wind Harmer
0.811
270346AE1-212 GEN
Solar/Wind Harmer
0.545
270030AE2-140 GEN
Solar/Wind Harmer
1.083
270069AE2-166 C O1
Solar/Wind Harmer
0.526
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
0.403
316375AC2-012 GEN
Solar/Wind Helper
0.596
316197AC1-042 GEN
Solar/Wind Helper
0.215
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.981
316169AC1-164_GENC
Solar/Wind Helper
0.847
316381AD1-082 GEN
Solar/Wind Helper
0.344
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.036
3142946ENON
Solar/Wind Helper
0.119
3144536CHRHLND
Solar/Wind Helper
0.048
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.281
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.563
961611AG1-000B GEN
Solar/Wind Helper
0.468
961951AG1-038 GEN
Solar/Wind Helper
0.254
966871AG1-558 GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.062
970563AG2-360 GEN
50/50
33.666
970823AG2-518 GEN
50/50
5.456
970913AG2-568 GEN
Solar/Wind Harmer
0.421
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.457
971329AH1-144 GEN
Solar/Wind Harmer
0.545
971331AH1-145 GEN
Solar/Wind Harmer
12.45
971403AH1-188 GEN
Solar/Wind Harmer
0.722
971461AH1-227 GEN
Solar/Wind Harmer
0.281
971543AH1-269 GEN
50/50
8.214
971687AH1-348 GEN
Solar/Wind Harmer
0.054
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.192
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.959
971981AH1-535 GEN
Solar/Wind Harmer
0.503
972103AH1-617 GEN
Solar/Wind Harmer
1.012
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.044
971881AH1-461 GEN
50/50
10.558
315773AC2-141 GEN
Solar/Wind Helper
1.246
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.256
316294AC1-161 GEN
Solar/Wind Helper
1.246
316473AC1-191 GEN
Solar/Wind Helper
0.483
316487AF1-042 GEN
Solar/Wind Helper
0.254
316484AD2-074 GEN
Solar/Wind Helper
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.356
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.618
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.657
NYPJM->LTFIMP_NY
CLTF
2.067
LGEELTFEXP_LGEE->PJM
CLTF
4.281
WECLTFEXP_WEC->PJM
CLTF
2.133
CPLELTFEXP_CPLE->PJM
CLTF
1.528
TVALTFEXP_TVA->PJM
CLTF
6.811
MECLTFEXP_MEC->PJM
CLTF
9.763
LAGNLTFEXP_LAGN->PJM
CLTF
12.763
SIGELTFEXP_SIGE->PJM
CLTF
0.322
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.192

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 542T553_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 542T553_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.08 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2573.38
MW Contribution:
5.46
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.997
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.693
24728305BUCHG2
50/50
5.518
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.141
3142416OLDCHRC
Solar/Wind Helper
0.968
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.412
3142956BIRDNECK
Solar/Wind Helper
0.518
3143316POE
Solar/Wind Helper
1.302
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.352
3141913WHIT STONE
Solar/Wind Helper
0.35
3143226MDLTHAN
Solar/Wind Helper
0.359
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.254
3141726DUNNSVL
Solar/Wind Helper
1.409
24289905CRG1H
50/50
0.808
24290105CRG2H
50/50
0.815
24290005CRG1L
50/50
0.808
24290205CRG2L
50/50
0.808
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.11
316314AB2-024 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.088
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.282
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.293
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.877
3143526WINTERP
Solar/Wind Helper
1.877
316404AE1-155 C
Solar/Wind Helper
0.716
316033AB2-134 GEN
Solar/Wind Helper
0.755
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.733
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.15
316369SG1_INVT
Solar/Wind Helper
0.519
315651AD1-115 GEN
Solar/Wind Helper
0.757
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.652
315662AE1-191 GEN
Solar/Wind Helper
0.45
315666AE1-190 GEN
Solar/Wind Helper
0.112
315697AD1-025 GEN
Solar/Wind Helper
0.796
316185AD1-033 GEN
Solar/Wind Helper
0.351
316280AD1-041 GEN
Solar/Wind Helper
0.281
316447AC1-158 HLD
Solar/Wind Helper
0.965
316044AC1-158 PL1
Solar/Wind Helper
0.439
316045AC1-158 PL2
Solar/Wind Helper
1.403
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.438
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.113
270583AD2-179 GEN
Solar/Wind Harmer
0.812
270346AE1-212 GEN
Solar/Wind Harmer
0.546
270030AE2-140 GEN
Solar/Wind Harmer
1.085
270069AE2-166 C O1
Solar/Wind Harmer
0.527
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.402
316458AB2-190 GEN2
Solar/Wind Helper
0.402
316375AC2-012 GEN
Solar/Wind Helper
0.595
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.979
316169AC1-164_GENC
Solar/Wind Helper
0.846
316381AD1-082 GEN
Solar/Wind Helper
0.344
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.035
3142946ENON
Solar/Wind Helper
0.119
3144536CHRHLND
Solar/Wind Helper
0.047
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.287
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.563
961611AG1-000B GEN
Solar/Wind Helper
0.467
961951AG1-038 GEN
Solar/Wind Helper
0.254
966871AG1-558 GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.064
970563AG2-360 GEN
50/50
33.712
970823AG2-518 GEN
50/50
5.462
970913AG2-568 GEN
Solar/Wind Harmer
0.421
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.458
971329AH1-144 GEN
Solar/Wind Harmer
0.545
971331AH1-145 GEN
Solar/Wind Harmer
12.465
971403AH1-188 GEN
Solar/Wind Harmer
0.724
971461AH1-227 GEN
Solar/Wind Harmer
0.282
971543AH1-269 GEN
50/50
8.223
971687AH1-348 GEN
Solar/Wind Harmer
0.055
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.191
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.963
971981AH1-535 GEN
Solar/Wind Harmer
0.504
972103AH1-617 GEN
Solar/Wind Harmer
1.014
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.051
971881AH1-461 GEN
50/50
10.572
315773AC2-141 GEN
Solar/Wind Helper
1.244
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.255
316294AC1-161 GEN
Solar/Wind Helper
1.244
316473AC1-191 GEN
Solar/Wind Helper
0.482
316487AF1-042 GEN
Solar/Wind Helper
0.254
316484AD2-074 GEN
Solar/Wind Helper
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.588
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.833
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.705
NYPJM->LTFIMP_NY
CLTF
2.056
LGEELTFEXP_LGEE->PJM
CLTF
4.292
WECLTFEXP_WEC->PJM
CLTF
2.14
CPLELTFEXP_CPLE->PJM
CLTF
1.545
TVALTFEXP_TVA->PJM
CLTF
6.827
MECLTFEXP_MEC->PJM
CLTF
9.79
LAGNLTFEXP_LAGN->PJM
CLTF
12.796
SIGELTFEXP_SIGE->PJM
CLTF
0.323
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 553T564_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 553T564_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:217.06 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2561.3
MW Contribution:
5.46
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.997
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.696
24728305BUCHG2
50/50
5.522
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.14
3142416OLDCHRC
Solar/Wind Helper
0.968
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.411
3142956BIRDNECK
Solar/Wind Helper
0.518
3143316POE
Solar/Wind Helper
1.301
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.351
3141913WHIT STONE
Solar/Wind Helper
0.349
3143226MDLTHAN
Solar/Wind Helper
0.359
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.063
3147312GRETNA
Solar/Wind Helper
0.254
3141726DUNNSVL
Solar/Wind Helper
1.408
24289905CRG1H
50/50
0.809
24290105CRG2H
50/50
0.815
24290005CRG1L
50/50
0.809
24290205CRG2L
50/50
0.809
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.109
316314AB2-024 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.088
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.281
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.292
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.876
3143526WINTERP
Solar/Wind Helper
1.876
316404AE1-155 C
Solar/Wind Helper
0.716
316033AB2-134 GEN
Solar/Wind Helper
0.755
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.732
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.149
316369SG1_INVT
Solar/Wind Helper
0.519
315651AD1-115 GEN
Solar/Wind Helper
0.756
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.652
315662AE1-191 GEN
Solar/Wind Helper
0.45
315666AE1-190 GEN
Solar/Wind Helper
0.112
315697AD1-025 GEN
Solar/Wind Helper
0.795
316185AD1-033 GEN
Solar/Wind Helper
0.351
316280AD1-041 GEN
Solar/Wind Helper
0.281
316447AC1-158 HLD
Solar/Wind Helper
0.964
316044AC1-158 PL1
Solar/Wind Helper
0.438
316045AC1-158 PL2
Solar/Wind Helper
1.402
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.438
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.112
270583AD2-179 GEN
Solar/Wind Harmer
0.812
270346AE1-212 GEN
Solar/Wind Harmer
0.546
270030AE2-140 GEN
Solar/Wind Harmer
1.086
270069AE2-166 C O1
Solar/Wind Harmer
0.527
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.402
316458AB2-190 GEN2
Solar/Wind Helper
0.402
316375AC2-012 GEN
Solar/Wind Helper
0.595
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.979
316169AC1-164_GENC
Solar/Wind Helper
0.845
316381AD1-082 GEN
Solar/Wind Helper
0.343
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.035
3142946ENON
Solar/Wind Helper
0.118
3144536CHRHLND
Solar/Wind Helper
0.047
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.29
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.562
961611AG1-000B GEN
Solar/Wind Helper
0.467
961951AG1-038 GEN
Solar/Wind Helper
0.253
966871AG1-558 GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.065
970563AG2-360 GEN
50/50
33.733
970823AG2-518 GEN
50/50
5.464
970913AG2-568 GEN
Solar/Wind Harmer
0.422
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.458
971329AH1-144 GEN
Solar/Wind Harmer
0.546
971331AH1-145 GEN
Solar/Wind Harmer
12.472
971403AH1-188 GEN
Solar/Wind Harmer
0.724
971461AH1-227 GEN
Solar/Wind Harmer
0.282
971543AH1-269 GEN
50/50
8.227
971687AH1-348 GEN
Solar/Wind Harmer
0.055
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.191
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.965
971981AH1-535 GEN
Solar/Wind Harmer
0.504
972103AH1-617 GEN
Solar/Wind Harmer
1.014
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.053
971881AH1-461 GEN
50/50
10.579
315773AC2-141 GEN
Solar/Wind Helper
1.243
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.255
316294AC1-161 GEN
Solar/Wind Helper
1.243
316473AC1-191 GEN
Solar/Wind Helper
0.482
316487AF1-042 GEN
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.484
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.927
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.726
NYPJM->LTFIMP_NY
CLTF
2.052
LGEELTFEXP_LGEE->PJM
CLTF
4.297
WECLTFEXP_WEC->PJM
CLTF
2.142
CPLELTFEXP_CPLE->PJM
CLTF
1.553
TVALTFEXP_TVA->PJM
CLTF
6.834
MECLTFEXP_MEC->PJM
CLTF
9.802
LAGNLTFEXP_LAGN->PJM
CLTF
12.81
SIGELTFEXP_SIGE->PJM
CLTF
0.323
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.66 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2544.77
MW Contribution:
5.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
1.018
24290605CLAY-1
50/50
0.171
24290605CLAY-1
50/50
0.171
24290705CLAY-2
50/50
0.171
24290705CLAY-2
50/50
0.171
24728205BUCHG1
50/50
6.231
24728305BUCHG2
50/50
6.04
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.13
3142416OLDCHRC
Solar/Wind Helper
0.878
3142416OLDCHRC
Solar/Wind Helper
0.336
3142433PROV 92
Solar/Wind Helper
1.276
316075AC2-137 C
Solar/Wind Helper
0.106
316077AC2-138 C
Solar/Wind Helper
0.072
3138133OCRAN
Solar/Wind Helper
0.095
3138133OCRAN
Solar/Wind Helper
0.19
3141766HARMONY
Solar/Wind Helper
0.064
3141783LANCAST
Solar/Wind Helper
0.191
3141783LANCAST
Solar/Wind Helper
0.127
3141813NORNECK
Solar/Wind Helper
0.322
3141913WHIT STONE
Solar/Wind Helper
0.317
3143226MDLTHAN
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.191
3147123OTTER R
Solar/Wind Helper
0.187
3147312GRETNA
Solar/Wind Helper
0.063
3147312GRETNA
Solar/Wind Helper
0.254
3147666LOUISA
Solar/Wind Helper
1.258
3147666LOUISA
Solar/Wind Helper
0.723
3141726DUNNSVL
Solar/Wind Helper
1.29
24289905CRG1H
50/50
0.888
24290105CRG2H
50/50
0.895
24290005CRG1L
50/50
0.888
24290205CRG2L
50/50
0.888
316059AD1-063 C
Solar/Wind Helper
0.077
316314AB2-024 C
Solar/Wind Helper
0.103
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.355
3141873WAN 176
Solar/Wind Helper
0.063
3143526WINTERP
Solar/Wind Helper
1.709
3143526WINTERP
Solar/Wind Helper
1.709
316404AE1-155 C
Solar/Wind Helper
0.655
3142543TWELFTH
Solar/Wind Helper
0.031
316203AE2-005 GEN
Solar/Wind Helper
0.662
316441AF1-014 GEN
Solar/Wind Helper
0.101
316312AB1-027
Solar/Wind Helper
0.136
315651AD1-115 GEN
Solar/Wind Helper
0.792
315662AE1-191 GEN
Solar/Wind Helper
0.407
315666AE1-190 GEN
Solar/Wind Helper
0.102
316280AD1-041 GEN
Solar/Wind Helper
0.254
316447AC1-158 HLD
Solar/Wind Helper
0.936
316044AC1-158 PL1
Solar/Wind Helper
0.425
316045AC1-158 PL2
Solar/Wind Helper
1.361
316450AC1-158 RIC
Solar/Wind Helper
0.113
316468AD1-105 GEN
Solar/Wind Helper
0.407
316156AD2-030 GEN
Solar/Wind Helper
0.1
316337AD2-073 GEN
Solar/Wind Helper
0.104
270399AC1-101 GEN
Solar/Wind Harmer
0.288
270583AD2-179 GEN
Solar/Wind Harmer
0.823
270494AE1-108_GEN
Solar/Wind Helper
0.847
270346AE1-212 GEN
Solar/Wind Harmer
0.589
270030AE2-140 GEN
Solar/Wind Harmer
1.139
270069AE2-166 C O1
Solar/Wind Harmer
0.548
270053AF1-130 C
Solar/Wind Harmer
1.012
316006AB2-029 C
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.442
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.105
315975AC1-164 GENB
Solar/Wind Helper
0.026
315976AC1-164 GENA
Solar/Wind Helper
0.883
316169AC1-164_GENC
Solar/Wind Helper
0.763
316233AE1-074 FULL
Solar/Wind Helper
0.106
3142946ENON
Solar/Wind Helper
0.032
3142946ENON
Solar/Wind Helper
0.107
943031AE2-326 GEN
Solar/Wind Harmer
5.484
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.53
944971AF1-162 GEN
Solar/Wind Harmer
6.858
961951AG1-038 GEN
Solar/Wind Helper
0.231
966871AG1-558 GEN
Solar/Wind Helper
0.11
966881AG1-559 GEN
Solar/Wind Helper
0.114
970281AG2-184 GEN
Solar/Wind Harmer
1.21
970563AG2-360 GEN
50/50
36.34
970823AG2-518 GEN
50/50
5.453
970913AG2-568 GEN
Solar/Wind Harmer
0.477
971061AG2-657 GEN
Solar/Wind Harmer
0.472
971225AH1-072 GEN
Solar/Wind Harmer
0.123
971227AH1-073 GEN
Solar/Wind Harmer
0.123
971277AH1-098 GEN
Solar/Wind Harmer
0.336
971313AH1-133 GEN
Solar/Wind Harmer
0.496
971329AH1-144 GEN
Solar/Wind Harmer
0.558
971331AH1-145 GEN
Solar/Wind Harmer
12.762
971403AH1-188 GEN
Solar/Wind Harmer
0.833
971461AH1-227 GEN
Solar/Wind Harmer
0.315
971543AH1-269 GEN
50/50
8.316
971687AH1-348 GEN
Solar/Wind Harmer
0.061
24415905BUCK
50/50
0.026
24416005BYLLESBY
50/50
0.049
957601AF2-054 GEN
Solar/Wind Helper
0.101
957971AF2-091 GEN
Solar/Wind Helper
0.18
964211AG1-282 GEN
Solar/Wind Helper
0.104
966391AG1-508 GEN
Solar/Wind Harmer
4.12
971981AH1-535 GEN
Solar/Wind Harmer
0.558
972103AH1-617 GEN
Solar/Wind Harmer
1.152
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.448
971881AH1-461 GEN
50/50
11.424
316164AC1-076 GEN
Solar/Wind Helper
0.342
316217AC1-145 GEN
Solar/Wind Helper
0.255
316473AC1-191 GEN
Solar/Wind Helper
0.44
270400AC1-102 GEN
Solar/Wind Harmer
0.288
316487AF1-042 GEN
Solar/Wind Helper
0.231
316484AD2-074 GEN
Solar/Wind Helper
0.442
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.464
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.422
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.119
NYPJM->LTFIMP_NY
CLTF
2.528
LGEELTFEXP_LGEE->PJM
CLTF
5.132
WECLTFEXP_WEC->PJM
CLTF
2.57
CPLELTFEXP_CPLE->PJM
CLTF
2.392
TVALTFEXP_TVA->PJM
CLTF
7.856
MECLTFEXP_MEC->PJM
CLTF
11.663
LAGNLTFEXP_LAGN->PJM
CLTF
14.865
SIGELTFEXP_SIGE->PJM
CLTF
0.385
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.446
AG2-052LTFEXP_AG2-052->PJM
LTF
0.155
AH1-155LTFEXP_AH1-155->PJM
LTF
0.233

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:194.03 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2289.58
MW Contribution:
5.55
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
1.014
24290605CLAY-1
50/50
0.172
24290605CLAY-1
50/50
0.172
24290705CLAY-2
50/50
0.172
24290705CLAY-2
50/50
0.172
24728205BUCHG1
50/50
5.791
24728305BUCHG2
50/50
5.614
3142416OLDCHRC
Solar/Wind Helper
0.842
3142416OLDCHRC
Solar/Wind Helper
0.323
316075AC2-137 C
Solar/Wind Helper
0.101
3143226MDLTHAN
Solar/Wind Helper
0.32
270205AE1-176
50/50
0.013
3143526WINTERP
Solar/Wind Helper
1.661
3143526WINTERP
Solar/Wind Helper
1.661
3148463FAIRFLD
Solar/Wind Harmer
-0.312
315616AA1-038_C
Solar/Wind Harmer
3.158
316312AB1-027
Solar/Wind Helper
0.13
316447AC1-158 HLD
Solar/Wind Helper
0.871
316044AC1-158 PL1
Solar/Wind Helper
0.396
316045AC1-158 PL2
Solar/Wind Helper
1.267
316450AC1-158 RIC
Solar/Wind Helper
0.106
316468AD1-105 GEN
Solar/Wind Helper
0.386
270399AC1-101 GEN
Solar/Wind Harmer
0.252
270583AD2-179 GEN
Solar/Wind Harmer
0.825
270494AE1-108_GEN
Solar/Wind Helper
0.869
270346AE1-212 GEN
Solar/Wind Harmer
0.553
270030AE2-140 GEN
Solar/Wind Harmer
1.13
270069AE2-166 C O1
Solar/Wind Harmer
0.546
24734705WLF1G3
50/50
7.099
24734805WLF1G4
50/50
7.099
24734905WLF1G5
50/50
7.099
24735105WLF2G1
50/50
6.939
24735205WLF2G2
50/50
6.939
315975AC1-164 GENB
Solar/Wind Helper
0.025
315976AC1-164 GENA
Solar/Wind Helper
0.849
316169AC1-164_GENC
Solar/Wind Helper
0.733
316233AE1-074 FULL
Solar/Wind Helper
0.103
943031AE2-326 GEN
Solar/Wind Harmer
5.381
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.105
966881AG1-559 GEN
Solar/Wind Helper
0.108
970281AG2-184 GEN
Solar/Wind Harmer
1.082
970563AG2-360 GEN
50/50
34.318
970823AG2-518 GEN
50/50
5.548
970913AG2-568 GEN
Solar/Wind Harmer
0.426
971225AH1-072 GEN
Solar/Wind Harmer
0.112
971227AH1-073 GEN
Solar/Wind Harmer
0.112
971277AH1-098 GEN
Solar/Wind Harmer
0.33
971313AH1-133 GEN
Solar/Wind Harmer
0.466
971329AH1-144 GEN
Solar/Wind Harmer
0.554
971331AH1-145 GEN
Solar/Wind Harmer
12.663
971403AH1-188 GEN
Solar/Wind Harmer
0.734
971461AH1-227 GEN
Solar/Wind Harmer
0.287
971543AH1-269 GEN
50/50
8.359
971687AH1-348 GEN
Solar/Wind Harmer
0.056
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.048
966391AG1-508 GEN
Solar/Wind Harmer
4.035
971981AH1-535 GEN
Solar/Wind Harmer
0.518
972103AH1-617 GEN
Solar/Wind Harmer
1.031
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.128
971881AH1-461 GEN
50/50
10.749
316164AC1-076 GEN
Solar/Wind Helper
0.321
316473AC1-191 GEN
Solar/Wind Helper
0.421
270400AC1-102 GEN
Solar/Wind Harmer
0.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
84.953
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.009
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.24
NYPJM->LTFIMP_NY
CLTF
2.009
LGEELTFEXP_LGEE->PJM
CLTF
4.347
WECLTFEXP_WEC->PJM
CLTF
2.162
CPLELTFEXP_CPLE->PJM
CLTF
2.241
TVALTFEXP_TVA->PJM
CLTF
7.056
MECLTFEXP_MEC->PJM
CLTF
9.948
LAGNLTFEXP_LAGN->PJM
CLTF
13.244
SIGELTFEXP_SIGE->PJM
CLTF
0.327
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.194

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:190.04 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2242.41
MW Contribution:
5.17
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.954
24290605CLAY-1
50/50
0.161
24290605CLAY-1
50/50
0.161
24290705CLAY-2
50/50
0.161
24290705CLAY-2
50/50
0.161
24728205BUCHG1
50/50
5.518
24728305BUCHG2
50/50
5.349
3142416OLDCHRC
Solar/Wind Helper
0.834
3142416OLDCHRC
Solar/Wind Helper
0.319
316075AC2-137 C
Solar/Wind Helper
0.1
3143226MDLTHAN
Solar/Wind Helper
0.312
3147123OTTER R
Solar/Wind Helper
0.192
3147312GRETNA
Solar/Wind Helper
0.065
3147312GRETNA
Solar/Wind Helper
0.261
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.245
3143526WINTERP
Solar/Wind Helper
1.627
3143526WINTERP
Solar/Wind Helper
1.627
316312AB1-027
Solar/Wind Helper
0.129
316447AC1-158 HLD
Solar/Wind Helper
0.869
316044AC1-158 PL1
Solar/Wind Helper
0.395
316045AC1-158 PL2
Solar/Wind Helper
1.264
316450AC1-158 RIC
Solar/Wind Helper
0.105
316468AD1-105 GEN
Solar/Wind Helper
0.383
270583AD2-179 GEN
Solar/Wind Harmer
0.773
270494AE1-108_GEN
Solar/Wind Helper
0.825
270346AE1-212 GEN
Solar/Wind Harmer
0.523
270030AE2-140 GEN
Solar/Wind Harmer
1.055
270069AE2-166 C O1
Solar/Wind Harmer
0.509
24734705WLF1G3
50/50
6.764
24734805WLF1G4
50/50
6.764
24734905WLF1G5
50/50
6.764
24735105WLF2G1
50/50
6.612
24735205WLF2G2
50/50
6.612
316197AC1-042 GEN
Solar/Wind Helper
0.22
316233AE1-074 FULL
Solar/Wind Helper
0.101
943031AE2-326 GEN
Solar/Wind Harmer
5.111
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.104
966881AG1-559 GEN
Solar/Wind Helper
0.107
970563AG2-360 GEN
50/50
32.682
970823AG2-518 GEN
50/50
5.169
970913AG2-568 GEN
Solar/Wind Harmer
0.406
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.313
971313AH1-133 GEN
Solar/Wind Harmer
0.443
971329AH1-144 GEN
Solar/Wind Harmer
0.52
971331AH1-145 GEN
Solar/Wind Harmer
11.877
971403AH1-188 GEN
Solar/Wind Harmer
0.701
971461AH1-227 GEN
Solar/Wind Harmer
0.274
971543AH1-269 GEN
50/50
7.822
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.825
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.934
971881AH1-461 GEN
50/50
10.218
316164AC1-076 GEN
Solar/Wind Helper
0.317
316217AC1-145 GEN
Solar/Wind Helper
0.262
316473AC1-191 GEN
Solar/Wind Helper
0.417
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.376
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.835
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.235
NYPJM->LTFIMP_NY
CLTF
1.913
LGEELTFEXP_LGEE->PJM
CLTF
4.185
WECLTFEXP_WEC->PJM
CLTF
2.088
CPLELTFEXP_CPLE->PJM
CLTF
1.958
TVALTFEXP_TVA->PJM
CLTF
6.727
MECLTFEXP_MEC->PJM
CLTF
9.577
LAGNLTFEXP_LAGN->PJM
CLTF
12.632
SIGELTFEXP_SIGE->PJM
CLTF
0.315
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.536
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:188.91 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2229.09
MW Contribution:
13.64
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.639

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:186.82 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2204.47
MW Contribution:
5.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.959
24290605CLAY-1
50/50
0.162
24290605CLAY-1
50/50
0.162
24290705CLAY-2
50/50
0.162
24290705CLAY-2
50/50
0.162
24728205BUCHG1
50/50
5.533
24728305BUCHG2
50/50
5.364
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.256
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.24
316447AC1-158 HLD
Solar/Wind Helper
0.833
316044AC1-158 PL1
Solar/Wind Helper
0.379
316045AC1-158 PL2
Solar/Wind Helper
1.211
316450AC1-158 RIC
Solar/Wind Helper
0.101
270583AD2-179 GEN
Solar/Wind Harmer
0.777
270494AE1-108_GEN
Solar/Wind Helper
0.809
270346AE1-212 GEN
Solar/Wind Harmer
0.524
270030AE2-140 GEN
Solar/Wind Harmer
1.069
270069AE2-166 C O1
Solar/Wind Harmer
0.515
24734705WLF1G3
50/50
6.789
24734805WLF1G4
50/50
6.789
24734905WLF1G5
50/50
6.789
24735105WLF2G1
50/50
6.638
24735205WLF2G2
50/50
6.638
316197AC1-042 GEN
Solar/Wind Helper
0.216
943031AE2-326 GEN
Solar/Wind Harmer
5.137
943811AF1-049 GEN
Solar/Wind Harmer
0
966881AG1-559 GEN
Solar/Wind Helper
0.102
970563AG2-360 GEN
50/50
32.8
970823AG2-518 GEN
50/50
5.199
970913AG2-568 GEN
Solar/Wind Harmer
0.406
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.314
971313AH1-133 GEN
Solar/Wind Harmer
0.445
971329AH1-144 GEN
Solar/Wind Harmer
0.522
971331AH1-145 GEN
Solar/Wind Harmer
11.934
971403AH1-188 GEN
Solar/Wind Harmer
0.701
971461AH1-227 GEN
Solar/Wind Harmer
0.274
971543AH1-269 GEN
50/50
7.866
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.844
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.947
971881AH1-461 GEN
50/50
10.25
316217AC1-145 GEN
Solar/Wind Helper
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.062
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.386
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.91
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.644
NYPJM->LTFIMP_NY
CLTF
1.911
LGEELTFEXP_LGEE->PJM
CLTF
4.164
WECLTFEXP_WEC->PJM
CLTF
2.073
CPLELTFEXP_CPLE->PJM
CLTF
2.153
TVALTFEXP_TVA->PJM
CLTF
6.757
MECLTFEXP_MEC->PJM
CLTF
9.533
LAGNLTFEXP_LAGN->PJM
CLTF
12.686
SIGELTFEXP_SIGE->PJM
CLTF
0.314
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.662
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 542T553_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 542T553_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:186.53 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2201.01
MW Contribution:
13.65
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.654

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:186.02 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2194.98
MW Contribution:
5.21
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.96
24290605CLAY-1
50/50
0.162
24290605CLAY-1
50/50
0.162
24290705CLAY-2
50/50
0.162
24290705CLAY-2
50/50
0.162
24728205BUCHG1
50/50
5.534
24728305BUCHG2
50/50
5.365
3142416OLDCHRC
Solar/Wind Helper
0.819
3142416OLDCHRC
Solar/Wind Helper
0.314
3143226MDLTHAN
Solar/Wind Helper
0.324
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.255
316258AE1-075 C
Solar/Wind Helper
0.094
316405AF2-144 C
Solar/Wind Helper
0.088
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.239
3143526WINTERP
Solar/Wind Helper
1.661
3143526WINTERP
Solar/Wind Helper
1.661
316312AB1-027
Solar/Wind Helper
0.126
316447AC1-158 HLD
Solar/Wind Helper
0.837
316044AC1-158 PL1
Solar/Wind Helper
0.381
316045AC1-158 PL2
Solar/Wind Helper
1.218
316450AC1-158 RIC
Solar/Wind Helper
0.101
316468AD1-105 GEN
Solar/Wind Helper
0.374
316313AB2-026
Solar/Wind Helper
0.104
270583AD2-179 GEN
Solar/Wind Harmer
0.778
270494AE1-108_GEN
Solar/Wind Helper
0.764
270346AE1-212 GEN
Solar/Wind Harmer
0.524
270030AE2-140 GEN
Solar/Wind Harmer
1.068
270069AE2-166 C O1
Solar/Wind Harmer
0.515
24734705WLF1G3
50/50
6.788
24734805WLF1G4
50/50
6.788
24734905WLF1G5
50/50
6.788
24735105WLF2G1
50/50
6.636
24735205WLF2G2
50/50
6.636
316197AC1-042 GEN
Solar/Wind Helper
0.215
316233AE1-074 FULL
Solar/Wind Helper
0.103
943031AE2-326 GEN
Solar/Wind Harmer
5.139
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.102
966881AG1-559 GEN
Solar/Wind Helper
0.104
970563AG2-360 GEN
50/50
32.806
970823AG2-518 GEN
50/50
5.206
970913AG2-568 GEN
Solar/Wind Harmer
0.406
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.314
971313AH1-133 GEN
Solar/Wind Harmer
0.445
971329AH1-144 GEN
Solar/Wind Harmer
0.523
971331AH1-145 GEN
Solar/Wind Harmer
11.946
971403AH1-188 GEN
Solar/Wind Harmer
0.701
971461AH1-227 GEN
Solar/Wind Harmer
0.274
971543AH1-269 GEN
50/50
7.875
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.846
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.947
971881AH1-461 GEN
50/50
10.253
316217AC1-145 GEN
Solar/Wind Helper
0.256
316473AC1-191 GEN
Solar/Wind Helper
0.41
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.009
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.274
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.872
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.539
NYPJM->LTFIMP_NY
CLTF
1.92
LGEELTFEXP_LGEE->PJM
CLTF
4.162
WECLTFEXP_WEC->PJM
CLTF
2.071
CPLELTFEXP_CPLE->PJM
CLTF
2.099
TVALTFEXP_TVA->PJM
CLTF
6.746
MECLTFEXP_MEC->PJM
CLTF
9.525
LAGNLTFEXP_LAGN->PJM
CLTF
12.662
SIGELTFEXP_SIGE->PJM
CLTF
0.313
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.646
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 553T564_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 553T564_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.48 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2188.66
MW Contribution:
13.66
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.66

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:180.89 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:2134.53
MW Contribution:
5.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.96
24290605CLAY-1
50/50
0.162
24290605CLAY-1
50/50
0.162
24290705CLAY-2
50/50
0.162
24290705CLAY-2
50/50
0.162
24728205BUCHG1
50/50
5.538
24728305BUCHG2
50/50
5.369
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.255
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.239
316447AC1-158 HLD
Solar/Wind Helper
0.832
316044AC1-158 PL1
Solar/Wind Helper
0.378
316045AC1-158 PL2
Solar/Wind Helper
1.21
316450AC1-158 RIC
Solar/Wind Helper
0.101
270583AD2-179 GEN
Solar/Wind Harmer
0.777
270494AE1-108_GEN
Solar/Wind Helper
0.809
270346AE1-212 GEN
Solar/Wind Harmer
0.524
270030AE2-140 GEN
Solar/Wind Harmer
1.07
270069AE2-166 C O1
Solar/Wind Harmer
0.516
24734705WLF1G3
50/50
6.796
24734805WLF1G4
50/50
6.796
24734905WLF1G5
50/50
6.796
24735105WLF2G1
50/50
6.645
24735205WLF2G2
50/50
6.645
316197AC1-042 GEN
Solar/Wind Helper
0.215
943031AE2-326 GEN
Solar/Wind Harmer
5.14
943811AF1-049 GEN
Solar/Wind Harmer
0
966881AG1-559 GEN
Solar/Wind Helper
0.102
970563AG2-360 GEN
50/50
32.828
970823AG2-518 GEN
50/50
5.203
970913AG2-568 GEN
Solar/Wind Harmer
0.407
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.314
971313AH1-133 GEN
Solar/Wind Harmer
0.445
971329AH1-144 GEN
Solar/Wind Harmer
0.522
971331AH1-145 GEN
Solar/Wind Harmer
11.943
971403AH1-188 GEN
Solar/Wind Harmer
0.702
971461AH1-227 GEN
Solar/Wind Harmer
0.275
971543AH1-269 GEN
50/50
7.871
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.846
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.951
971881AH1-461 GEN
50/50
10.259
316217AC1-145 GEN
Solar/Wind Helper
0.256
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.515
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.946
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.673
NYPJM->LTFIMP_NY
CLTF
1.904
LGEELTFEXP_LGEE->PJM
CLTF
4.171
WECLTFEXP_WEC->PJM
CLTF
2.076
CPLELTFEXP_CPLE->PJM
CLTF
2.163
TVALTFEXP_TVA->PJM
CLTF
6.767
MECLTFEXP_MEC->PJM
CLTF
9.549
LAGNLTFEXP_LAGN->PJM
CLTF
12.705
SIGELTFEXP_SIGE->PJM
CLTF
0.314
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.662
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.85 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2122.24
MW Contribution:
13.63
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.633

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:161.03 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1900.15
MW Contribution:
13.87
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.871

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:159.03 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1876.56
MW Contribution:
12.92
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
12.923

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:155.04 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1829.46
MW Contribution:
13.02
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.016

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10265_05LEESVI 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:154.66 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1824.96
MW Contribution:
13.17
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.172

Details for [AG2-518] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:150.34 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:1774.07
MW Contribution:
13.01
IPD Plant:AG2-518
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
PJM_IPD
13.007
CONTINGENCY 'DVP_P1-2: LN 553_SRT-A_SENS'
 OPEN BRANCH FROM BUS 314910 TO BUS 313378 CKT 1   /*8CUNINGHAM   500.0 - 8VONTAY      500.0
END
CONTINGENCY 'DVP_P4-2: 542T553_SRT-W_SENS'
 OPEN BRANCH FROM BUS 313378 TO BUS 314910 CKT 1                /*8VONTAY      500.0 - 8CUNINGHAM   500.0
 OPEN BUS 315217                                                /*1CUNINGB      18.0
 OPEN BUS 315218                                                /*1CUNINGC      18.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'DVP_P4-2: 553T564_SRT-W_SENS'
 OPEN BRANCH FROM BUS 313378 TO BUS 314910 CKT 1                /*8VONTAY      500.0 - 8CUNINGHAM   500.0
 OPEN BUS 315216                                                /*1CUNINGA      18.0
 OPEN BUS 315219                                                /*1CUNINGD      22.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2114-535_SRT-A_SENS'
 OPEN BRANCH FROM BUS 235110 TO BUS 289543 CKT 1   /*01MDWBRK     500.0 - 05YEAT       500.0
 OPEN BRANCH FROM BUS 314085 TO BUS 314110 CKT 1   /*6REMNGCT     230.0 - 6ELK RUN     230.0
 OPEN BRANCH FROM BUS 314110 TO BUS 314125 CKT 1   /*6ELK RUN     230.0 - 6VINTHIL     230.0
 OPEN BUS 314110                                   /*6ELK RUN     230.0
END
CONTINGENCY 'PECO_P2-2_PHILLIPS-BUS_SRT-A
 DISCONNECT BUS 213888   /*PHLISCT1      18.0
 DISCONNECT BUS 213889   /*PHLISCT2      18.0
 DISCONNECT BUS 213892   /*PHLISL87     230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'AEP_P2-2_#10265_05LEESVI 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242701 TO BUS 242802 CKT 1   /*05LEESVI     138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 247284 CKT 1   /*05LEESVI     138.0 - 05LEESVG      13.8
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-518 was evaluated as a 80.0 MW injection and 80.0 MW withdrawal in the AEP area.

AG2-518 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 80.0 MW (80.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC173.68 %1180.0B2049.45
19.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC173.67 %1180.0B2049.35
19.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-L
BreakerAC173.35 %1180.0B2045.56
19.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC171.54 %1180.0B2024.13
19.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
14.08
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
14.08
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC136.83 %1180.0B1614.63
14.08
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
BusAC110.97 %1180.0B1309.48
14.96
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17030___SRT-A
TowerAC110.49 %1180.0B1303.74
14.89
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17029___SRT-A
TowerAC110.3 %1180.0B1301.52
14.89
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
BusAC109.1 %1180.0B1287.39
14.38
GD2AEP
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
AEP_P1-2_#311_5_SRT-A
SingleAC104.41 %167.0B174.36
36.06
GD2AEP
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
AEP_P4_#311_05CLOVRD 765_CC2_SRT-A
BreakerAC104.41 %167.0B174.36
36.06
GD2AEP
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
BreakerAC104.37 %167.0B174.3
36.06
GD2AEP
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
AEP_P4_#7587_05J.FERR 765_B_SRT-A
BreakerAC103.04 %167.0B172.07
35.88

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.68 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.45
MW Contribution:
19.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
19.371
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.174
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971461AH1-227 GEN
Solar/Wind Harmer
4.169
316405AF2-144 C
Solar/Wind Helper
0.49
316404AE1-155 C
Solar/Wind Helper
3.563
315662AE1-191 GEN
Solar/Wind Helper
2.22
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
270346AE1-212 GEN
Solar/Wind Harmer
8.186
971981AH1-535 GEN
Solar/Wind Harmer
6.611
316044AC1-158 PL1
Solar/Wind Helper
2.309
944491AF1-114 GEN
Solar/Wind Helper
2.856
316487AF1-042 GEN
Solar/Wind Helper
1.165
316280AD1-041 GEN
Solar/Wind Helper
1.388
270399AC1-101 GEN
Solar/Wind Harmer
1.686
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971981AH1-535 GEN
Solar/Wind Harmer
7.212
316450AC1-158 RIC
Solar/Wind Helper
0.616
957971AF2-091 GEN
Solar/Wind Helper
0.971
316159AE1-175 C
Solar/Wind Helper
0.538
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
316045AC1-158 PL2
Solar/Wind Helper
7.388
316233AE1-074 FULL
Solar/Wind Helper
0.6
270400AC1-102 GEN
Solar/Wind Harmer
1.686
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.553
971543AH1-269 GEN
50/50
11.498
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
315821AE2-092 GEN
Solar/Wind Helper
3.827
970563AG2-360 GEN
50/50
45.019
972273AH1-721 GEN
50/50
85.07
316468AD1-105 GEN
Solar/Wind Helper
2.225
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.581
316258AE1-075 C
Solar/Wind Helper
0.519
970119AG2-088 GEN
50/50
Charging
16.823
971277AH1-098 GEN
Solar/Wind Harmer
4.144
270494AE1-108_GEN
Solar/Wind Helper
5.579
316164AC1-076 GEN
Solar/Wind Helper
1.94
316313AB2-026
Solar/Wind Helper
0.577
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
966871AG1-558 GEN
Solar/Wind Helper
0.436
316337AD2-073 GEN
Solar/Wind Helper
0.563
315666AE1-190 GEN
Solar/Wind Helper
0.555
970417AG2-272 GEN
50/50
8.428
270069AE2-166 C O1
Solar/Wind Harmer
8.427
966001AG1-469 GEN
Solar/Wind Helper
0.423
316382AG1-145 C
Solar/Wind Helper
0.541
315616AA1-038_C
Solar/Wind Helper
1.957
316303AF2-085
50/50
Charging
2.243
270583AD2-179 GEN
Solar/Wind Harmer
12.447
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316447AC1-158 HLD
Solar/Wind Helper
5.08
316192AB2-158 GEN
Solar/Wind Helper
2.765
963031AG1-152 GEN
50/50
Charging
10.85
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
316059AD1-063 C
Solar/Wind Helper
0.418
971881AH1-461 GEN
50/50
14.324
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.427
315651AD1-115 GEN
Solar/Wind Helper
4.201
315975AC1-164 GENB
Solar/Wind Helper
0.061
961951AG1-038 GEN
Solar/Wind Helper
1.258
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
CPLELTFEXP_CPLE->PJM
CLTF
4.752
SIGELTFEXP_SIGE->PJM
CLTF
0.438
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
NYPJM->LTFIMP_NY
CLTF
2.179
TVALTFEXP_TVA->PJM
CLTF
9.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
LGEELTFEXP_LGEE->PJM
CLTF
5.763
MECLTFEXP_MEC->PJM
CLTF
13.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
WECLTFEXP_WEC->PJM
CLTF
2.894
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.67 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.35
MW Contribution:
19.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
19.371
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.175
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971461AH1-227 GEN
Solar/Wind Harmer
4.169
316405AF2-144 C
Solar/Wind Helper
0.49
316404AE1-155 C
Solar/Wind Helper
3.563
315662AE1-191 GEN
Solar/Wind Helper
2.22
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
270346AE1-212 GEN
Solar/Wind Harmer
8.186
971981AH1-535 GEN
Solar/Wind Harmer
6.611
316044AC1-158 PL1
Solar/Wind Helper
2.309
944491AF1-114 GEN
Solar/Wind Helper
2.856
316487AF1-042 GEN
Solar/Wind Helper
1.165
316280AD1-041 GEN
Solar/Wind Helper
1.388
270399AC1-101 GEN
Solar/Wind Harmer
1.686
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971981AH1-535 GEN
Solar/Wind Harmer
7.212
316450AC1-158 RIC
Solar/Wind Helper
0.616
957971AF2-091 GEN
Solar/Wind Helper
0.971
316159AE1-175 C
Solar/Wind Helper
0.538
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
316045AC1-158 PL2
Solar/Wind Helper
7.388
316233AE1-074 FULL
Solar/Wind Helper
0.6
270400AC1-102 GEN
Solar/Wind Harmer
1.686
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.554
971543AH1-269 GEN
50/50
11.498
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
315821AE2-092 GEN
Solar/Wind Helper
3.827
970563AG2-360 GEN
50/50
45.019
972273AH1-721 GEN
50/50
85.07
316468AD1-105 GEN
Solar/Wind Helper
2.225
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.581
316258AE1-075 C
Solar/Wind Helper
0.519
970119AG2-088 GEN
50/50
Charging
16.824
971277AH1-098 GEN
Solar/Wind Harmer
4.144
270494AE1-108_GEN
Solar/Wind Helper
5.58
316164AC1-076 GEN
Solar/Wind Helper
1.94
316313AB2-026
Solar/Wind Helper
0.577
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
966871AG1-558 GEN
Solar/Wind Helper
0.436
316337AD2-073 GEN
Solar/Wind Helper
0.563
315666AE1-190 GEN
Solar/Wind Helper
0.555
970417AG2-272 GEN
50/50
8.428
270069AE2-166 C O1
Solar/Wind Harmer
8.427
966001AG1-469 GEN
Solar/Wind Helper
0.423
315616AA1-038_C
Solar/Wind Helper
1.962
316382AG1-145 C
Solar/Wind Helper
0.541
316303AF2-085
50/50
Charging
2.243
270583AD2-179 GEN
Solar/Wind Harmer
12.447
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316447AC1-158 HLD
Solar/Wind Helper
5.08
316192AB2-158 GEN
Solar/Wind Helper
2.765
963031AG1-152 GEN
50/50
Charging
10.85
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
316059AD1-063 C
Solar/Wind Helper
0.418
971881AH1-461 GEN
50/50
14.324
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.427
315651AD1-115 GEN
Solar/Wind Helper
4.201
315975AC1-164 GENB
Solar/Wind Helper
0.061
961951AG1-038 GEN
Solar/Wind Helper
1.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
NYPJM->LTFIMP_NY
CLTF
2.178
TVALTFEXP_TVA->PJM
CLTF
9.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
LGEELTFEXP_LGEE->PJM
CLTF
5.763
MECLTFEXP_MEC->PJM
CLTF
13.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
WECLTFEXP_WEC->PJM
CLTF
2.894
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
CPLELTFEXP_CPLE->PJM
CLTF
4.752
SIGELTFEXP_SIGE->PJM
CLTF
0.438

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2045.56
MW Contribution:
19.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
19.368
970365AG2-240 GEN
50/50
Charging
1.247
316405AF2-144 C
50/50
Charging
1.177
966391AG1-508 GEN
Solar/Wind Harmer
10.237
971461AH1-227 GEN
Solar/Wind Harmer
4.168
316405AF2-144 C
Solar/Wind Helper
0.491
316404AE1-155 C
Solar/Wind Helper
3.567
315662AE1-191 GEN
Solar/Wind Helper
2.223
971531AH1-263 GEN
50/50
Charging
23.682
972293SS25-0014
50/50
Charging
57.048
270346AE1-212 GEN
Solar/Wind Harmer
8.185
971981AH1-535 GEN
Solar/Wind Harmer
6.61
316044AC1-158 PL1
Solar/Wind Helper
2.31
944491AF1-114 GEN
Solar/Wind Helper
2.859
316487AF1-042 GEN
Solar/Wind Helper
1.167
316280AD1-041 GEN
Solar/Wind Helper
1.389
270399AC1-101 GEN
Solar/Wind Harmer
1.686
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.214
971981AH1-535 GEN
Solar/Wind Harmer
7.211
316450AC1-158 RIC
Solar/Wind Helper
0.616
957971AF2-091 GEN
Solar/Wind Helper
0.972
316159AE1-175 C
Solar/Wind Helper
0.538
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971329AH1-144 GEN
Solar/Wind Harmer
7.832
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
316045AC1-158 PL2
Solar/Wind Helper
7.393
316233AE1-074 FULL
Solar/Wind Helper
0.6
270400AC1-102 GEN
Solar/Wind Harmer
1.686
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.554
971543AH1-269 GEN
50/50
11.496
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.229
315821AE2-092 GEN
Solar/Wind Helper
3.841
970563AG2-360 GEN
50/50
45.014
972273AH1-721 GEN
50/50
85.068
316468AD1-105 GEN
Solar/Wind Helper
2.227
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.582
316258AE1-075 C
Solar/Wind Helper
0.52
970119AG2-088 GEN
50/50
Charging
16.846
971277AH1-098 GEN
Solar/Wind Harmer
4.143
270494AE1-108_GEN
Solar/Wind Helper
5.59
316164AC1-076 GEN
Solar/Wind Helper
1.941
316313AB2-026
Solar/Wind Helper
0.578
316223AC1-118
Solar/Wind Helper
0.568
316203AE2-005 GEN
Solar/Wind Helper
3.62
316156AD2-030 GEN
Solar/Wind Helper
0.548
966871AG1-558 GEN
Solar/Wind Helper
0.437
316337AD2-073 GEN
Solar/Wind Helper
0.564
315666AE1-190 GEN
Solar/Wind Helper
0.556
970417AG2-272 GEN
50/50
8.425
270069AE2-166 C O1
Solar/Wind Harmer
8.425
966001AG1-469 GEN
Solar/Wind Helper
0.424
315616AA1-038_C
Solar/Wind Helper
2.018
316382AG1-145 C
Solar/Wind Helper
0.541
316303AF2-085
50/50
Charging
2.246
270583AD2-179 GEN
Solar/Wind Harmer
12.446
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.746
972103AH1-617 GEN
Solar/Wind Harmer
14.996
316447AC1-158 HLD
Solar/Wind Helper
5.083
316192AB2-158 GEN
Solar/Wind Helper
2.769
963031AG1-152 GEN
50/50
Charging
10.856
960911AF2-382 GEN
Solar/Wind Harmer
6.616
270030AE2-140 GEN
Solar/Wind Harmer
17.478
316059AD1-063 C
Solar/Wind Helper
0.419
971881AH1-461 GEN
50/50
14.323
315976AC1-164 GENA
Solar/Wind Helper
2.057
316169AC1-164_GENC
Solar/Wind Helper
1.777
971507AH1-251 GEN
50/50
Charging
5.867
957191AF2-013 GEN
50/50
Charging
10.663
943031AE2-326 GEN
Solar/Wind Harmer
11.708
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.43
315651AD1-115 GEN
Solar/Wind Helper
4.205
315975AC1-164 GENB
Solar/Wind Helper
0.061
961951AG1-038 GEN
Solar/Wind Helper
1.26
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.999
LGEELTFEXP_LGEE->PJM
CLTF
5.764
MECLTFEXP_MEC->PJM
CLTF
13.347
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.017
WECLTFEXP_WEC->PJM
CLTF
2.895
LAGNLTFEXP_LAGN->PJM
CLTF
17.991
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.652
CPLELTFEXP_CPLE->PJM
CLTF
4.745
SIGELTFEXP_SIGE->PJM
CLTF
0.438
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.9
NYPJM->LTFIMP_NY
CLTF
2.177
TVALTFEXP_TVA->PJM
CLTF
9.524
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.478

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2024.13
MW Contribution:
19.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
19.371
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.174
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971461AH1-227 GEN
Solar/Wind Harmer
4.169
316404AE1-155 C
Solar/Wind Helper
3.563
315662AE1-191 GEN
Solar/Wind Helper
2.22
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270399AC1-101 GEN
Solar/Wind Harmer
3.469
944491AF1-114 GEN
Solar/Wind Helper
2.856
316487AF1-042 GEN
Solar/Wind Helper
1.165
316280AD1-041 GEN
Solar/Wind Helper
1.388
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.216
957971AF2-091 GEN
Solar/Wind Helper
0.971
316159AE1-175 C
Solar/Wind Helper
0.538
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
270400AC1-102 GEN
Solar/Wind Harmer
3.469
270053AF1-130 C
Solar/Wind Harmer
12.797
316233AE1-074 FULL
Solar/Wind Helper
0.6
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.553
971543AH1-269 GEN
50/50
11.498
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
315821AE2-092 GEN
Solar/Wind Helper
3.827
970563AG2-360 GEN
50/50
45.019
972273AH1-721 GEN
50/50
85.07
316468AD1-105 GEN
Solar/Wind Helper
2.225
316075AC2-137 C
Solar/Wind Helper
0.581
316258AE1-075 C
Solar/Wind Helper
0.519
970119AG2-088 GEN
50/50
Charging
16.823
270494AE1-108_GEN
Solar/Wind Helper
5.579
316164AC1-076 GEN
Solar/Wind Helper
1.94
316313AB2-026
Solar/Wind Helper
0.577
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
944971AF1-162 GEN
Solar/Wind Harmer
2.093
957241AF2-018 GEN
Solar/Wind Harmer
0
316337AD2-073 GEN
Solar/Wind Helper
0.563
315666AE1-190 GEN
Solar/Wind Helper
0.555
970417AG2-272 GEN
50/50
8.428
270069AE2-166 C O1
Solar/Wind Harmer
8.427
966001AG1-469 GEN
Solar/Wind Helper
0.423
316382AG1-145 C
Solar/Wind Helper
0.541
315616AA1-038_C
Solar/Wind Helper
1.957
316303AF2-085
50/50
Charging
2.243
270583AD2-179 GEN
Solar/Wind Harmer
12.447
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316192AB2-158 GEN
Solar/Wind Helper
2.765
963031AG1-152 GEN
50/50
Charging
10.85
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
316059AD1-063 C
Solar/Wind Helper
0.418
971881AH1-461 GEN
50/50
14.324
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
316473AC1-191 GEN
Solar/Wind Helper
2.427
315651AD1-115 GEN
Solar/Wind Helper
4.201
961951AG1-038 GEN
Solar/Wind Helper
1.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
NYPJM->LTFIMP_NY
CLTF
2.179
TVALTFEXP_TVA->PJM
CLTF
9.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
LGEELTFEXP_LGEE->PJM
CLTF
5.763
MECLTFEXP_MEC->PJM
CLTF
13.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
WECLTFEXP_WEC->PJM
CLTF
2.894
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
CPLELTFEXP_CPLE->PJM
CLTF
4.752
SIGELTFEXP_SIGE->PJM
CLTF
0.438

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
14.08
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
966391AG1-508 GEN
Solar/Wind Harmer
8.202
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270399AC1-101 GEN
Solar/Wind Harmer
3.156
316044AC1-158 PL1
Solar/Wind Helper
2.181
944491AF1-114 GEN
Solar/Wind Helper
2.702
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
316450AC1-158 RIC
Solar/Wind Helper
0.582
957971AF2-091 GEN
Solar/Wind Helper
0.919
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971403AH1-188 GEN
Solar/Wind Harmer
9.621
316006AB2-029 C
Solar/Wind Helper
0.504
941621AE2-160 GEN
50/50
5.904
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
316045AC1-158 PL2
Solar/Wind Helper
6.979
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971543AH1-269 GEN
50/50
8.594
971313AH1-133 GEN
Solar/Wind Harmer
5.386
970563AG2-360 GEN
50/50
37.854
972273AH1-721 GEN
50/50
76.948
316468AD1-105 GEN
Solar/Wind Helper
2.079
316312AB1-027
Solar/Wind Helper
0.693
971277AH1-098 GEN
Solar/Wind Harmer
3.312
270494AE1-108_GEN
Solar/Wind Helper
4.816
316164AC1-076 GEN
Solar/Wind Helper
1.745
944971AF1-162 GEN
Solar/Wind Harmer
10.409
957241AF2-018 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.404
970417AG2-272 GEN
50/50
6.326
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270583AD2-179 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
316447AC1-158 HLD
Solar/Wind Helper
4.798
963031AG1-152 GEN
50/50
Charging
10.244
960911AF2-382 GEN
Solar/Wind Harmer
5.69
971881AH1-461 GEN
50/50
11.944
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
966881AG1-559 GEN
Solar/Wind Helper
0.418
316473AC1-191 GEN
Solar/Wind Helper
2.25
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
WECLTFEXP_WEC->PJM
CLTF
2.768
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
CPLELTFEXP_CPLE->PJM
CLTF
3.423
SIGELTFEXP_SIGE->PJM
CLTF
0.412
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
NYPJM->LTFIMP_NY
CLTF
2.2
TVALTFEXP_TVA->PJM
CLTF
8.341
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
LGEELTFEXP_LGEE->PJM
CLTF
5.464
MECLTFEXP_MEC->PJM
CLTF
12.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
14.08
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
966391AG1-508 GEN
Solar/Wind Harmer
8.202
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270399AC1-101 GEN
Solar/Wind Harmer
3.156
316044AC1-158 PL1
Solar/Wind Helper
2.181
944491AF1-114 GEN
Solar/Wind Helper
2.702
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
316450AC1-158 RIC
Solar/Wind Helper
0.582
957971AF2-091 GEN
Solar/Wind Helper
0.919
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971403AH1-188 GEN
Solar/Wind Harmer
9.621
316006AB2-029 C
Solar/Wind Helper
0.504
941621AE2-160 GEN
50/50
5.904
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
316045AC1-158 PL2
Solar/Wind Helper
6.979
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971543AH1-269 GEN
50/50
8.594
971313AH1-133 GEN
Solar/Wind Harmer
5.386
970563AG2-360 GEN
50/50
37.854
972273AH1-721 GEN
50/50
76.948
316468AD1-105 GEN
Solar/Wind Helper
2.079
316312AB1-027
Solar/Wind Helper
0.693
971277AH1-098 GEN
Solar/Wind Harmer
3.312
270494AE1-108_GEN
Solar/Wind Helper
4.816
316164AC1-076 GEN
Solar/Wind Helper
1.745
944971AF1-162 GEN
Solar/Wind Harmer
10.409
957241AF2-018 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.404
970417AG2-272 GEN
50/50
6.326
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270583AD2-179 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
316447AC1-158 HLD
Solar/Wind Helper
4.798
963031AG1-152 GEN
50/50
Charging
10.244
960911AF2-382 GEN
Solar/Wind Harmer
5.69
971881AH1-461 GEN
50/50
11.944
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
966881AG1-559 GEN
Solar/Wind Helper
0.418
316473AC1-191 GEN
Solar/Wind Helper
2.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
CPLELTFEXP_CPLE->PJM
CLTF
3.423
SIGELTFEXP_SIGE->PJM
CLTF
0.412
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
NYPJM->LTFIMP_NY
CLTF
2.2
TVALTFEXP_TVA->PJM
CLTF
8.341
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
LGEELTFEXP_LGEE->PJM
CLTF
5.464
MECLTFEXP_MEC->PJM
CLTF
12.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
WECLTFEXP_WEC->PJM
CLTF
2.768
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.83 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1614.63
MW Contribution:
14.08
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
966391AG1-508 GEN
Solar/Wind Harmer
8.202
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270399AC1-101 GEN
Solar/Wind Harmer
3.156
944491AF1-114 GEN
Solar/Wind Helper
2.702
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
957971AF2-091 GEN
Solar/Wind Helper
0.919
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971403AH1-188 GEN
Solar/Wind Harmer
9.621
316006AB2-029 C
Solar/Wind Helper
0.504
941621AE2-160 GEN
50/50
5.904
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971543AH1-269 GEN
50/50
8.594
971313AH1-133 GEN
Solar/Wind Harmer
5.386
970563AG2-360 GEN
50/50
37.854
972273AH1-721 GEN
50/50
76.948
316468AD1-105 GEN
Solar/Wind Helper
2.079
944971AF1-162 GEN
Solar/Wind Harmer
12.03
270494AE1-108_GEN
Solar/Wind Helper
4.816
316164AC1-076 GEN
Solar/Wind Helper
1.745
957241AF2-018 GEN
Solar/Wind Harmer
0
970417AG2-272 GEN
50/50
6.326
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270583AD2-179 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
963031AG1-152 GEN
50/50
Charging
10.244
960911AF2-382 GEN
Solar/Wind Harmer
5.69
270030AE2-140 GEN
Solar/Wind Harmer
3.161
971881AH1-461 GEN
50/50
11.944
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
316473AC1-191 GEN
Solar/Wind Helper
2.25
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
LGEELTFEXP_LGEE->PJM
CLTF
5.464
MECLTFEXP_MEC->PJM
CLTF
12.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
WECLTFEXP_WEC->PJM
CLTF
2.768
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
CPLELTFEXP_CPLE->PJM
CLTF
3.423
SIGELTFEXP_SIGE->PJM
CLTF
0.412
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
NYPJM->LTFIMP_NY
CLTF
2.2
TVALTFEXP_TVA->PJM
CLTF
8.341
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.97 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1309.48
MW Contribution:
14.96
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
14.96
966391AG1-508 GEN
Solar/Wind Harmer
7.933
942671AE2-283 GEN
Solar/Wind Harmer
3.623
971461AH1-227 GEN
Solar/Wind Harmer
3.235
971531AH1-263 GEN
50/50
Charging
20.999
972293SS25-0014
50/50
Charging
50.508
270346AE1-212 GEN
Solar/Wind Harmer
6.338
971981AH1-535 GEN
Solar/Wind Harmer
5.175
316044AC1-158 PL1
Solar/Wind Helper
2.046
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.329
971981AH1-535 GEN
Solar/Wind Harmer
5.645
316450AC1-158 RIC
Solar/Wind Helper
0.545
971277AH1-098 GEN
Solar/Wind Harmer
3.537
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
8.261
941621AE2-160 GEN
50/50
5.119
970913AG2-568 GEN
Solar/Wind Harmer
4.573
316045AC1-158 PL2
Solar/Wind Helper
6.545
971687AH1-348 GEN
Solar/Wind Harmer
0.626
971543AH1-269 GEN
50/50
8.911
971313AH1-133 GEN
Solar/Wind Harmer
4.952
3146802CHATHAM
Solar/Wind Harmer
0.256
970563AG2-360 GEN
50/50
34.767
962751AG1-124 GEN
Solar/Wind Harmer
6.233
3147312GRETNA
Solar/Wind Harmer
0.273
3147312GRETNA
Solar/Wind Harmer
0.068
971277AH1-098 GEN
Solar/Wind Harmer
3.215
941801AE2-185 GEN
Solar/Wind Harmer
4.102
961131AF2-404 GEN
Solar/Wind Harmer
2.357
970417AG2-272 GEN
50/50
7.231
270069AE2-166 C O1
Solar/Wind Harmer
7.142
270583AD2-179 GEN
Solar/Wind Harmer
9.646
943811AF1-049 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.188
316447AC1-158 HLD
Solar/Wind Helper
4.5
970281AG2-184 GEN
Solar/Wind Harmer
11.543
270030AE2-140 GEN
Solar/Wind Harmer
14.894
960911AF2-382 GEN
Solar/Wind Harmer
5.121
971881AH1-461 GEN
50/50
11.072
971507AH1-251 GEN
50/50
Charging
5.111
943031AE2-326 GEN
Solar/Wind Harmer
9.019
971225AH1-072 GEN
Solar/Wind Harmer
1.261
971227AH1-073 GEN
Solar/Wind Harmer
1.261
966881AG1-559 GEN
Solar/Wind Helper
0.39
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.09
NYPJM->LTFIMP_NY
CLTF
1.786
TVALTFEXP_TVA->PJM
CLTF
7.544
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
19.204
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.13
LGEELTFEXP_LGEE->PJM
CLTF
4.54
MECLTFEXP_MEC->PJM
CLTF
10.573
AG2-052LTFEXP_AG2-052->PJM
LTF
0.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.713
WECLTFEXP_WEC->PJM
CLTF
2.293
LAGNLTFEXP_LAGN->PJM
CLTF
14.289
AH1-155LTFEXP_AH1-155->PJM
LTF
0.206
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.61
CPLELTFEXP_CPLE->PJM
CLTF
4.184
SIGELTFEXP_SIGE->PJM
CLTF
0.346

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17030___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17030___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1303.74
MW Contribution:
14.89
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
14.895
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971531AH1-263 GEN
50/50
Charging
20.391
972293SS25-0014
50/50
Charging
48.973
270346AE1-212 GEN
Solar/Wind Harmer
6.395
971981AH1-535 GEN
Solar/Wind Harmer
5.117
316217AC1-145 GEN
Solar/Wind Helper
1.974
316044AC1-158 PL1
Solar/Wind Helper
1.983
270399AC1-101 GEN
Solar/Wind Harmer
1.329
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971981AH1-535 GEN
Solar/Wind Harmer
5.582
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
8.401
270173AC1-122 GEN
Solar/Wind Helper
2.76
941621AE2-160 GEN
50/50
5.212
970913AG2-568 GEN
Solar/Wind Harmer
4.649
316045AC1-158 PL2
Solar/Wind Helper
6.347
270400AC1-102 GEN
Solar/Wind Harmer
1.329
971687AH1-348 GEN
Solar/Wind Harmer
0.633
971543AH1-269 GEN
50/50
8.871
971313AH1-133 GEN
Solar/Wind Harmer
5.006
970563AG2-360 GEN
50/50
35.173
971277AH1-098 GEN
Solar/Wind Harmer
3.223
270494AE1-108_GEN
Solar/Wind Helper
5.948
961131AF2-404 GEN
50/50
Charging
2.924
316450AC1-158 RIC
Solar/Wind Helper
0.529
970417AG2-272 GEN
50/50
6.193
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
270583AD2-179 GEN
Solar/Wind Harmer
9.612
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
12.374
972103AH1-617 GEN
Solar/Wind Harmer
11.785
316447AC1-158 HLD
Solar/Wind Helper
4.364
960911AF2-382 GEN
Solar/Wind Harmer
5.18
270030AE2-140 GEN
Solar/Wind Harmer
12.927
971881AH1-461 GEN
50/50
11.185
943031AE2-326 GEN
Solar/Wind Harmer
9.122
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
WECLTFEXP_WEC->PJM
CLTF
2.32
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
CPLELTFEXP_CPLE->PJM
CLTF
3.013
SIGELTFEXP_SIGE->PJM
CLTF
0.348
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
NYPJM->LTFIMP_NY
CLTF
1.631
TVALTFEXP_TVA->PJM
CLTF
7.367
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
LGEELTFEXP_LGEE->PJM
CLTF
4.594
MECLTFEXP_MEC->PJM
CLTF
10.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17029___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17029___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.3 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1301.52
MW Contribution:
14.89
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
14.895
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971531AH1-263 GEN
50/50
Charging
20.391
972293SS25-0014
50/50
Charging
48.973
270346AE1-212 GEN
Solar/Wind Harmer
6.395
971981AH1-535 GEN
Solar/Wind Harmer
5.117
316217AC1-145 GEN
Solar/Wind Helper
1.974
316044AC1-158 PL1
Solar/Wind Helper
1.983
270399AC1-101 GEN
Solar/Wind Harmer
1.329
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
8.401
270173AC1-122 GEN
Solar/Wind Helper
2.76
941621AE2-160 GEN
50/50
5.212
971687AH1-348 GEN
Solar/Wind Harmer
0.633
971543AH1-269 GEN
50/50
8.871
971313AH1-133 GEN
Solar/Wind Harmer
5.006
970563AG2-360 GEN
50/50
35.173
970913AG2-568 GEN
Solar/Wind Harmer
4.649
316045AC1-158 PL2
Solar/Wind Helper
6.347
270400AC1-102 GEN
Solar/Wind Harmer
1.329
971277AH1-098 GEN
Solar/Wind Harmer
3.223
270494AE1-108_GEN
Solar/Wind Helper
5.948
961131AF2-404 GEN
50/50
Charging
2.924
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971981AH1-535 GEN
Solar/Wind Harmer
5.582
316450AC1-158 RIC
Solar/Wind Helper
0.529
970417AG2-272 GEN
50/50
6.193
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
270583AD2-179 GEN
Solar/Wind Harmer
9.612
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
12.374
972103AH1-617 GEN
Solar/Wind Harmer
11.785
316447AC1-158 HLD
Solar/Wind Helper
4.364
960911AF2-382 GEN
Solar/Wind Harmer
5.18
270030AE2-140 GEN
Solar/Wind Harmer
12.927
971881AH1-461 GEN
50/50
11.185
943031AE2-326 GEN
Solar/Wind Harmer
9.122
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
CPLELTFEXP_CPLE->PJM
CLTF
3.013
SIGELTFEXP_SIGE->PJM
CLTF
0.348
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
NYPJM->LTFIMP_NY
CLTF
1.631
TVALTFEXP_TVA->PJM
CLTF
7.367
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
LGEELTFEXP_LGEE->PJM
CLTF
4.594
MECLTFEXP_MEC->PJM
CLTF
10.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
WECLTFEXP_WEC->PJM
CLTF
2.32
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1287.39
MW Contribution:
14.38
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
14.377
966391AG1-508 GEN
Solar/Wind Harmer
7.844
971461AH1-227 GEN
Solar/Wind Harmer
3.227
971531AH1-263 GEN
50/50
Charging
20.247
972293SS25-0014
50/50
Charging
48.638
270346AE1-212 GEN
Solar/Wind Harmer
6.24
971981AH1-535 GEN
Solar/Wind Harmer
5.078
316044AC1-158 PL1
Solar/Wind Helper
1.97
270399AC1-101 GEN
Solar/Wind Harmer
1.311
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
12.93
971981AH1-535 GEN
Solar/Wind Harmer
5.54
316450AC1-158 RIC
Solar/Wind Helper
0.525
971277AH1-098 GEN
Solar/Wind Harmer
3.493
971329AH1-144 GEN
Solar/Wind Harmer
5.883
971403AH1-188 GEN
Solar/Wind Harmer
8.284
270173AC1-122 GEN
Solar/Wind Helper
2.227
941621AE2-160 GEN
50/50
5.101
970913AG2-568 GEN
Solar/Wind Harmer
4.564
316045AC1-158 PL2
Solar/Wind Helper
6.303
270400AC1-102 GEN
Solar/Wind Harmer
1.311
971687AH1-348 GEN
Solar/Wind Harmer
0.625
971543AH1-269 GEN
50/50
8.605
971313AH1-133 GEN
Solar/Wind Harmer
4.935
970563AG2-360 GEN
50/50
34.746
971277AH1-098 GEN
Solar/Wind Harmer
3.175
270494AE1-108_GEN
Solar/Wind Helper
4.907
970417AG2-272 GEN
50/50
6.208
270069AE2-166 C O1
Solar/Wind Harmer
6.298
270583AD2-179 GEN
Solar/Wind Harmer
9.325
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
12.222
972103AH1-617 GEN
Solar/Wind Harmer
11.64
316447AC1-158 HLD
Solar/Wind Helper
4.334
960911AF2-382 GEN
Solar/Wind Harmer
5.113
270030AE2-140 GEN
Solar/Wind Harmer
12.937
971881AH1-461 GEN
50/50
11.002
943031AE2-326 GEN
Solar/Wind Harmer
9.004
971225AH1-072 GEN
Solar/Wind Harmer
1.258
971227AH1-073 GEN
Solar/Wind Harmer
1.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.36
LGEELTFEXP_LGEE->PJM
CLTF
4.537
MECLTFEXP_MEC->PJM
CLTF
10.492
AG2-052LTFEXP_AG2-052->PJM
LTF
0.138
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.018
WECLTFEXP_WEC->PJM
CLTF
2.291
LAGNLTFEXP_LAGN->PJM
CLTF
13.848
AH1-155LTFEXP_AH1-155->PJM
LTF
0.207
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.535
CPLELTFEXP_CPLE->PJM
CLTF
3.149
SIGELTFEXP_SIGE->PJM
CLTF
0.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.092
NYPJM->LTFIMP_NY
CLTF
1.636
TVALTFEXP_TVA->PJM
CLTF
7.32
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.744

Details for 05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line l/o AEP_P1-2_#311_5_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#311_5_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.41 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:174.36
MW Contribution:
36.06
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#311_5_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.35 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:199.31
MW Contribution:
36.49
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
Charging
36.058
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.378
971329AH1-144 GEN
Solar/Wind Harmer
1.992
971543AH1-269 GEN
50/50
9.577
270583AD2-179 GEN
Solar/Wind Harmer
9.101
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.16
LGEELTFEXP_LGEE->PJM
CLTF
0.299
MECLTFEXP_MEC->PJM
CLTF
0.691
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.942
WECLTFEXP_WEC->PJM
CLTF
0.146
LAGNLTFEXP_LAGN->PJM
CLTF
0.987
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.202
CPLELTFEXP_CPLE->PJM
CLTF
0.222
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.318
NYPJM->LTFIMP_NY
CLTF
0.129
TVALTFEXP_TVA->PJM
CLTF
0.535
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.642

Details for 05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line l/o AEP_P4_#311_05CLOVRD 765_CC2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#311_05CLOVRD 765_CC2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.41 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:174.36
MW Contribution:
36.06
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#311_05CLOVRD 765_CC2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.35 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:199.31
MW Contribution:
36.49
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
Charging
36.058
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.378
971329AH1-144 GEN
Solar/Wind Harmer
1.992
971543AH1-269 GEN
50/50
9.577
270583AD2-179 GEN
Solar/Wind Harmer
9.101
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.16
LGEELTFEXP_LGEE->PJM
CLTF
0.299
MECLTFEXP_MEC->PJM
CLTF
0.691
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.942
WECLTFEXP_WEC->PJM
CLTF
0.146
LAGNLTFEXP_LAGN->PJM
CLTF
0.987
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.202
CPLELTFEXP_CPLE->PJM
CLTF
0.222
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.318
NYPJM->LTFIMP_NY
CLTF
0.129
TVALTFEXP_TVA->PJM
CLTF
0.535
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.642

Details for 05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line l/o AEP_P4_#2914_05J.FERR 765_B2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.37 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:174.3
MW Contribution:
36.06
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.36 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:199.32
MW Contribution:
36.49
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
Charging
36.058
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.378
971329AH1-144 GEN
Solar/Wind Harmer
1.992
971543AH1-269 GEN
50/50
9.577
270583AD2-179 GEN
Solar/Wind Harmer
9.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.942
WECLTFEXP_WEC->PJM
CLTF
0.146
LAGNLTFEXP_LAGN->PJM
CLTF
0.987
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.202
CPLELTFEXP_CPLE->PJM
CLTF
0.222
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.318
NYPJM->LTFIMP_NY
CLTF
0.129
TVALTFEXP_TVA->PJM
CLTF
0.535
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.642
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.16
LGEELTFEXP_LGEE->PJM
CLTF
0.299
MECLTFEXP_MEC->PJM
CLTF
0.691

Details for 05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line l/o AEP_P4_#7587_05J.FERR 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7587_05J.FERR 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.04 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:172.07
MW Contribution:
35.88
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7587_05J.FERR 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.54 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:196.28
MW Contribution:
36.31
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
Charging
35.885
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.595
971329AH1-144 GEN
Solar/Wind Harmer
2.091
971543AH1-269 GEN
50/50
9.722
270583AD2-179 GEN
Solar/Wind Harmer
9.26
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.166
NYPJM->LTFIMP_NY
CLTF
0.126
TVALTFEXP_TVA->PJM
CLTF
0.519
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.981
LGEELTFEXP_LGEE->PJM
CLTF
0.291
MECLTFEXP_MEC->PJM
CLTF
0.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.886
WECLTFEXP_WEC->PJM
CLTF
0.142
LAGNLTFEXP_LAGN->PJM
CLTF
0.957
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.145
CPLELTFEXP_CPLE->PJM
CLTF
0.209
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 547T566_SRT-L'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1                /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1                /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1                /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                                /*8LEXINGTN SC 500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 247669 CKT 1   /*05JOSHUA     765.0 - 05JOSHUA 1EQ   1.0
 OPEN BRANCH FROM BUS 242688 TO BUS 247670 CKT 1   /*05JOSHUA     138.0 - 05JOSHUA_XFL 138.0
 OPEN BRANCH FROM BUS 247669 TO BUS 247670 CKT 1   /*05JOSHUA 1EQ   1.0 - 05JOSHUA_XFL 138.0
END
CONTINGENCY 'AEP_P7-1_#17030___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
END
CONTINGENCY 'AEP_P7-1_#17029___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1   /*05MOSELEY    138.0 - 05REUSENS1   138.0
END
CONTINGENCY 'AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242561 TO BUS 242765 CKT 1    /*05BOONSBORO  138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242719 TO BUS 242765 CKT 1    /*05MONEL      138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1    /*05MOSELEY    138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242882 CKT 4    /*05REUSENS1   138.0 - 05REUSENS     69.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242889 CKT 1    /*05REUSENS1   138.0 - 05REUSENS     34.5
 OPEN BRANCH FROM BUS 242765 TO BUS 246229 CKT Z1   /*05REUSENS1   138.0 - 05REUSENS2   138.0
 REMOVE SWSHUNT FROM BUS 242765                     /*05REUSENS1   138.0
END
CONTINGENCY 'AEP_P1-2_#311_5_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
CONTINGENCY 'AEP_P4_#311_05CLOVRD 765_CC2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
CONTINGENCY 'AEP_P4_#2914_05J.FERR 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 245993 CKT 4    /*05J.FERR     765.0 - 05J.FERR SVS  20.6
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
 REMOVE SWSHUNT FROM BUS 242514                     /*05J.FERR     765.0
END
CONTINGENCY 'AEP_P4_#7587_05J.FERR 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 242684 CKT 2    /*05J.FERR     765.0 - 05J.FERR     138.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
290614 to 242515 ckt 1
242608 to 242791 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
BreakerAC110.16 %180.0B198.29
36.49
GD2AEP
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line
AEP_P1-2_#311_5_SRT-A
SingleAC110.16 %180.0B198.28
36.49
GD2AEP
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line
AEP_P4_#311_05CLOVRD 765_CC2_SRT-A
BreakerAC110.16 %180.0B198.28
36.49
GD2AEP
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line
AEP_P4_#7587_05J.FERR 765_B_SRT-A
BreakerAC108.47 %180.0B195.25
36.31
GD2AEP
05TECHDR-05M FUNK 138.0 kV Ckt 1 line
AEP_P1-2_#311_5_SRT-A
SingleAC112.65 %167.0B188.13
33.36
GD2AEP
05TECHDR-05M FUNK 138.0 kV Ckt 1 line
AEP_P4_#311_05CLOVRD 765_CC2_SRT-A
BreakerAC112.65 %167.0B188.13
33.36
GD2AEP
05TECHDR-05M FUNK 138.0 kV Ckt 1 line
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
BreakerAC112.63 %167.0B188.1
33.36
GD2AEP
05TECHDR-05M FUNK 138.0 kV Ckt 1 line
AEP_P4_#7587_05J.FERR 765_B_SRT-A
BreakerAC111.27 %167.0B185.82
33.53

Details for 05SCHRIS-05TECHDR 138.0 kV Ckt 1 line l/o AEP_P4_#2914_05J.FERR 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.16 %
Rating:180.0 MVA
Rating Type:B
MVA to Mitigate:198.29
MW Contribution:
36.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
Charging
36.486
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.106
971329AH1-144 GEN
Solar/Wind Harmer
1.868
971543AH1-269 GEN
50/50
9.362
270583AD2-179 GEN
Solar/Wind Harmer
8.877
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.564
NYPJM->LTFIMP_NY
CLTF
0.15
TVALTFEXP_TVA->PJM
CLTF
0.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.696
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.223
LGEELTFEXP_LGEE->PJM
CLTF
0.311
MECLTFEXP_MEC->PJM
CLTF
0.716
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.926
WECLTFEXP_WEC->PJM
CLTF
0.154
LAGNLTFEXP_LAGN->PJM
CLTF
0.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.073
CPLELTFEXP_CPLE->PJM
CLTF
0.165
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 05SCHRIS-05TECHDR 138.0 kV Ckt 1 line l/o AEP_P1-2_#311_5_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#311_5_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.16 %
Rating:180.0 MVA
Rating Type:B
MVA to Mitigate:198.28
MW Contribution:
36.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
Charging
36.486
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.106
971329AH1-144 GEN
Solar/Wind Harmer
1.868
971543AH1-269 GEN
50/50
9.362
270583AD2-179 GEN
Solar/Wind Harmer
8.877
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.564
NYPJM->LTFIMP_NY
CLTF
0.15
TVALTFEXP_TVA->PJM
CLTF
0.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.696
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.223
LGEELTFEXP_LGEE->PJM
CLTF
0.311
MECLTFEXP_MEC->PJM
CLTF
0.716
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.926
WECLTFEXP_WEC->PJM
CLTF
0.154
LAGNLTFEXP_LAGN->PJM
CLTF
0.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.073
CPLELTFEXP_CPLE->PJM
CLTF
0.165
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 05SCHRIS-05TECHDR 138.0 kV Ckt 1 line l/o AEP_P4_#311_05CLOVRD 765_CC2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#311_05CLOVRD 765_CC2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.16 %
Rating:180.0 MVA
Rating Type:B
MVA to Mitigate:198.28
MW Contribution:
36.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
Charging
36.486
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.106
971329AH1-144 GEN
Solar/Wind Harmer
1.868
971543AH1-269 GEN
50/50
9.362
270583AD2-179 GEN
Solar/Wind Harmer
8.877
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.073
CPLELTFEXP_CPLE->PJM
CLTF
0.165
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.564
NYPJM->LTFIMP_NY
CLTF
0.15
TVALTFEXP_TVA->PJM
CLTF
0.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.696
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.223
LGEELTFEXP_LGEE->PJM
CLTF
0.311
MECLTFEXP_MEC->PJM
CLTF
0.716
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.926
WECLTFEXP_WEC->PJM
CLTF
0.154
LAGNLTFEXP_LAGN->PJM
CLTF
0.976

Details for 05SCHRIS-05TECHDR 138.0 kV Ckt 1 line l/o AEP_P4_#7587_05J.FERR 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7587_05J.FERR 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:180.0 MVA
Rating Type:B
MVA to Mitigate:195.25
MW Contribution:
36.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
Charging
36.308
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.321
971329AH1-144 GEN
Solar/Wind Harmer
1.966
971543AH1-269 GEN
50/50
9.506
270583AD2-179 GEN
Solar/Wind Harmer
9.035
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.872
WECLTFEXP_WEC->PJM
CLTF
0.15
LAGNLTFEXP_LAGN->PJM
CLTF
0.947
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.021
CPLELTFEXP_CPLE->PJM
CLTF
0.153
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.409
NYPJM->LTFIMP_NY
CLTF
0.147
TVALTFEXP_TVA->PJM
CLTF
0.511
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.046
LGEELTFEXP_LGEE->PJM
CLTF
0.303
MECLTFEXP_MEC->PJM
CLTF
0.696

Details for 05TECHDR-05M FUNK 138.0 kV Ckt 1 line l/o AEP_P1-2_#311_5_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05TECHDR-05M FUNK 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#311_5_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.65 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:188.13
MW Contribution:
33.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
33.361
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.601
971329AH1-144 GEN
Solar/Wind Harmer
2.093
971543AH1-269 GEN
50/50
8.748
270583AD2-179 GEN
Solar/Wind Harmer
8.376
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.146
LGEELTFEXP_LGEE->PJM
CLTF
0.308
MECLTFEXP_MEC->PJM
CLTF
0.709
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.9
WECLTFEXP_WEC->PJM
CLTF
0.153
LAGNLTFEXP_LAGN->PJM
CLTF
0.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.044
CPLELTFEXP_CPLE->PJM
CLTF
0.157
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.516
NYPJM->LTFIMP_NY
CLTF
0.147
TVALTFEXP_TVA->PJM
CLTF
0.518
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.647

Details for 05TECHDR-05M FUNK 138.0 kV Ckt 1 line l/o AEP_P4_#311_05CLOVRD 765_CC2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05TECHDR-05M FUNK 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#311_05CLOVRD 765_CC2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.65 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:188.13
MW Contribution:
33.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
33.361
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.601
971329AH1-144 GEN
Solar/Wind Harmer
2.093
971543AH1-269 GEN
50/50
8.748
270583AD2-179 GEN
Solar/Wind Harmer
8.376
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.044
CPLELTFEXP_CPLE->PJM
CLTF
0.157
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.516
NYPJM->LTFIMP_NY
CLTF
0.147
TVALTFEXP_TVA->PJM
CLTF
0.518
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.146
LGEELTFEXP_LGEE->PJM
CLTF
0.308
MECLTFEXP_MEC->PJM
CLTF
0.709
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.9
WECLTFEXP_WEC->PJM
CLTF
0.153
LAGNLTFEXP_LAGN->PJM
CLTF
0.962

Details for 05TECHDR-05M FUNK 138.0 kV Ckt 1 line l/o AEP_P4_#2914_05J.FERR 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05TECHDR-05M FUNK 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.63 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:188.1
MW Contribution:
33.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
33.361
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.601
971329AH1-144 GEN
Solar/Wind Harmer
2.093
971543AH1-269 GEN
50/50
8.748
270583AD2-179 GEN
Solar/Wind Harmer
8.376
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.9
WECLTFEXP_WEC->PJM
CLTF
0.153
LAGNLTFEXP_LAGN->PJM
CLTF
0.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.044
CPLELTFEXP_CPLE->PJM
CLTF
0.157
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.516
NYPJM->LTFIMP_NY
CLTF
0.147
TVALTFEXP_TVA->PJM
CLTF
0.518
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.146
LGEELTFEXP_LGEE->PJM
CLTF
0.308
MECLTFEXP_MEC->PJM
CLTF
0.709

Details for 05TECHDR-05M FUNK 138.0 kV Ckt 1 line l/o AEP_P4_#7587_05J.FERR 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05TECHDR-05M FUNK 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7587_05J.FERR 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.27 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:185.82
MW Contribution:
33.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
33.533
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
4.809
971329AH1-144 GEN
Solar/Wind Harmer
2.188
971543AH1-269 GEN
50/50
8.887
270583AD2-179 GEN
Solar/Wind Harmer
8.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.975
LGEELTFEXP_LGEE->PJM
CLTF
0.3
MECLTFEXP_MEC->PJM
CLTF
0.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.848
WECLTFEXP_WEC->PJM
CLTF
0.149
LAGNLTFEXP_LAGN->PJM
CLTF
0.934
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.994
CPLELTFEXP_CPLE->PJM
CLTF
0.145
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.366
NYPJM->LTFIMP_NY
CLTF
0.145
TVALTFEXP_TVA->PJM
CLTF
0.504
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.585
CONTINGENCY 'AEP_P4_#2914_05J.FERR 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 245993 CKT 4    /*05J.FERR     765.0 - 05J.FERR SVS  20.6
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
 REMOVE SWSHUNT FROM BUS 242514                     /*05J.FERR     765.0
END
CONTINGENCY 'AEP_P1-2_#311_5_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
CONTINGENCY 'AEP_P4_#311_05CLOVRD 765_CC2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
CONTINGENCY 'AEP_P4_#7587_05J.FERR 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 242684 CKT 2    /*05J.FERR     765.0 - 05J.FERR     138.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
242791 to 243874 ckt 1
243874 to 242708 ckt 1

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-152, AG2-272, AG2-518, AH1-098, AH1-144, AH1-145, AH1-269 and AH1-314 in PJM Transition Cycle 2, Cluster 24 are listed in Table 1. below. This report will cover the dynamic analysis of Cluster 24 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 24 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

Cluster 24 projects were dispatched for stability analysis according to the following scenarios:

       a)       Scenario 1: AH1-098 dispatched at full MFO injection at the POI with PV MW contribution maxed out and no/reduced MW contribution from BESS.

       b)       Scenario 2: AH1-098 dispatched at full MFO injection at the POI with BESS MW contribution maxed out, and no/reduced PV MW injection.

       c)       Scenario 3: AH1-098 dispatched at full MFO injection at the POI with PV and BESS MW contribution proportional to their capacity.

       d)       Scenario 4: AH1-098 dispatched to full capacity with PV and BESS MW injection maxed out.

 

This report describes a dynamic simulation analysis of TC2 Cluster 24 for dispatch Scenario 3 as part of the overall system impact study.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 24 projects have been dispatched online at maximum power output, with 1.01 pu voltage at the terminal bus.

 

Transition Cycle 2 Cluster 24 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);

       f)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 24 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 peak load case:

       a)       Cluster 24 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 24 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

The IPCMD and IQCMD states in the REGCA1 models of all units of Cluster 24 showed erratic behavior for some contingencies in which queue project has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

Tripping was observed for several contingencies (P4.081, P4.082, P5.39, and P5.48) under the initial study conditions. Upon updating the fault impedance values based on Aspen short circuit case, the tripping issues were resolved, and the system remained stable for these contingencies.

 

AH1-098 both Solar and BESS units tripped under several contingencies. Upon updating Vdip to 0.8 (Original value was 0.9) and Vup to 1.2 (Original value was 1.1) for both units resolved all tripping issue.

 

Fictitious frequency response at AH1-145 generator bus tripped the queue project for several contingencies (P1.073, P1.075 and P1.076). Therefore, the frequency relay pickup times for were set to 20 seconds to avoid fictitious frequency tripping of the unit.

 

AG2-272 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.15 (original value was 0) which resolved the slow reactive power response.

 

AH1-269 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.1 (original value was 0) which resolved the slow reactive power response.

 

AH1-314 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.1 (original value was 0) which resolved the slow reactive power response.

 

The active power for AG2-152 did not recover to the pre fault value for contingency P7.21 due inadequate reactive power response. The reactive power droop compensation gain Kc parameter was updated to 0.1 which resolved the active power recovery issue.

 

Smith Mountain generators showed positively damped oscillations which did not settle during the 20 second simulation window. The selected contingencies were run for 30 seconds, and the oscillatory signals achieved a flat response at the end of the 30 second simulation time period.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 24 Queues

Table 1: Transition Cycle 2 Cluster 24 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-152

Solar

AEP

131

Banister – Bearskin 138 kV

AG2-272

Battery

AEP

55

Berry Hill substation 138 kV

AG2-518

Battery

AEP

80

Tech Drive substation 138 kV

AH1-098

Solar/Battery

AEP

40

West Carroll – Wolf Glade 138 kV

AH1-144

Solar

AEP

70

Peter’s Mountain Substation 138 kV

AH1-145

Battery

AEP

80

Peter’s Mountain Substation 138 kV

AH1-269

Battery

AEP

50

Claytor substation 138 kV

AH1-314

Battery

AEP

100

East Danville substation 138 kV

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AG2-518 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-027Old Church 34.5 KVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-191Elmont 115kVEngineering & Procurement
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD2-030Wan 34.5 kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-179Morgans Cut-Glen Lyn 138kVWithdrawn
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-175Light Foot 34.5 kVIn Service
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-212Grandview-Clifftop 138 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVSuspended
AE2-027Harrowgate-Locks 115kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AF1-014Harmony Village-Shackleford 115 kVSuspended
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-162Inez 138 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-404Gladys DP-Stonemill 69 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-124Riverville - Gladstone 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-152Remington CT 230 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-508Point Lookout 69 kVWithdrawn
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-088Midlothian 230 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-240Old Church 34.5 kVActive
AG2-272Berry Hill 138 kVActive
AG2-360Broadford 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-269Claytor 138 kVActive
AH1-348Pound 34.5 kVActive
AH1-461Buckhorn 138 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-721Laurel-Cooper 161 kVActive
Y1-049Wurno 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-518 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
AEPn9772.005CLYTR1 138.0 kV to 05SCHRIS 138.0 kV ckt 1 - Replace StructuresCost Allocated$184,360N/A
APSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationContingent$0N/A
APSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Contingent$0N/A
APSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Contingent$0N/A
APSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardContingent$0N/A
AEPb4000.251Replace the wave trap and upgrade the relay at Cloverdale 765kV substationContingent$0N/A
AEPb4000.252Replace the wave trap and upgrade the relay at Joshua Falls 765kV substationContingent$0N/A
Grand Total:$184,360

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9772.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9772.0 / AEP-TC2-19074
Title
05CLYTR1 138.0 kV to 05SCHRIS 138.0 kV ckt 1 - Replace Structures
Description
Replace two 250 KCM CU 12-Str bus risers. Sg study Claytor - S. Christiansburg 138 kV line from Claytor to Str. 45-162 and from Str. 45-131 - 45-162.
Total Cost ($USD)
$270,000
Discounted Total Cost ($USD)
$270,000
Allocated Cost ($USD)
$184,360
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05CLYTR1-05SCHRIS 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A164.0 MVA
(All)B180.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-51836.1 MW68.3%$184,360
AH1-144 ⧉ Peter's Mountain 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-144, AH1-145
2.8 MW5.3%$14,290
AH1-145 ⧉ Peter's Mountain 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-144, AH1-145
4.4 MW8.3%$22,384
AH1-2699.6 MW18.1%$48,966

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 lineAEP_P4_#2914_05J.FERR 765_B2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 lineAEP_P4_#2914_05J.FERR 765_B2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 lineAEP_P4_#2914_05J.FERR 765_B2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 lineAEP_P4_#2914_05J.FERR 765_B2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 lineAEP_P4_#2914_05J.FERR 765_B2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 lineAEP_P4_#2914_05J.FERR 765_B2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 lineAEP_P4_#2914_05J.FERR 765_B2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 lineAEP_P4_#2914_05J.FERR 765_B2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 lineAEP_P4_#2914_05J.FERR 765_B2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 lineAEP_P4_#2914_05J.FERR 765_B2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05M FUNK-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SCHRIS-05TECHDR 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-518 may not presently have cost responsibility for this upgrade, AG2-518 may need this upgrade in-service to be deliverable to the PJM system. If AG2-518 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-518 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-518 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-518


AG2-518 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowAPSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationTopology-0.0%Contingent$0
Load FlowAPSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Topology-0.0%Contingent$0
Load FlowAPSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Topology-0.0%Contingent$0
Load FlowAPSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardTopology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-518 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-518 One Line Diagram

AG2-518 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.