AG2-550 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:53

Bluff Point - Randolph 138 kV

60.0 MW Capacity / 100.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Riverstart Solar Park VI LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $9,605,325 $22,991,797 = 0.42 AND ( $9,605,325 - $22,991,797 ) 100.0 = $-133,865 per MW

General

The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Randolph County, Indiana. The installed facilities will have a total capability of 100.0 MW with 60.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-550
Project Name:
Bluff Point - Randolph 138 kV
Project Developer Name:
Riverstart Solar Park VI LLC
State:
Indiana
County:
Randolph
Transmission Owner:
American Electric Power
MFO:
100.0
MWE:
100.0
MWC:
60.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-550 will interconnect on the American Electric Power transmission system by tapping the Bluff Point - Randolph 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-550 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-550Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$0$0$0
Other Scope$603,891$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$1,225,275$1,225,275$1,225,275
System Reliability Network Upgrades
Steady State Thermal & Voltage$70,097$70,097$70,097
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$8,309,953$8,309,953$8,309,953
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$10,209,216$9,605,325$9,605,325

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-550

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-550
Project ID: AG2-550
20% of cost allocation for Phase II Network Upgrades:(A) $1,921,065
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $2,299,180
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of (3) 138KV RCVTs with (1) three-phase 138KV RCVT structures & foundations. AEP Indiana Michigan Transmission Company Inc. will review and revise (as needed) the protective relay settings at the 138 kV Station. AEP Indiana Michigan Transmission Company Inc. will install one (1) new 1101 router at the 138 kV Station. AEP Indiana Michigan Transmission Company Inc. will install one (1) CES relaying package at the New 138 kV Station.

$590,315$325,967$191,431$117,562$1,225,275$1,225,275
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

AEP Indiana Michigan Transmission Company Inc. will install one (1) metering panel with two (2) primary meters and one (1) ethernet switch in the AG2-550 Project Developer's collector Station.

$310,265$139,608$106,222$47,796$603,891$603,891
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$1,829,166$1,829,166
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 15 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

Transmission Owner Identified Network Impacts to Distribution Facilities

None


Transmission Owner Identified Network Impacts to Sub-Regional Facilities

The Transmission Owner identified network impacts to Sub-Regional facilities as follows:

Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P4_#14047_05DESOTO 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A'  

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 138 1

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1                  / 243278 05DESOTO 138 243340 05MEDFOR 138 1

END
71.0152.44 %11.64
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
71.0152.42 %11.64
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-1
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
71.0149.34 %7.44
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P4_#15019_05DESOTO 138_F1_SRT-A
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
71.0149.34 %7.44
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-2
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2'  

  OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1                  / 946030 AF1-268 TP 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1                  / 964610 AG1-324 TP 138 247837 05PERCH 138 1

END
71.0137.08 %7.44
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-3
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-3'  

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

END
71.0128.07 %7.44
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P4_#15176_05JAY 138_E2_SRT-A
CONTINGENCY 'AEP_P4_#15176_05JAY 138_E2_SRT-A'  

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2                  / 243319 05JAY 138 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2                  / 246016 05JAY 69.0 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2                  / 290130 05JAY 2EQ 1.00 290132 05JAY T2 13.0 2

  REMOVE SWSHUNT FROM BUS 243319                                   / 243319 05JAY 138

END
71.0120.19 %7.14
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P4_#15023_05JAY 138_E_SRT-A
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'  

  OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4                  / 243319 05JAY 138 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4                  / 246016 05JAY 69.0 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4                  / 246015 05JAY 34.5 246018 05JAY 4EQ 1.00 4

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

END
71.0115.17 %6.91
246014 05BLUFFPNT 69.0 - 246022 05PORTLAND 69.0 CKT 1 AEP_P4_#10531_05JAY 138_D_SRT-A
CONTINGENCY 'AEP_P4_#10531_05JAY 138_D_SRT-A'  

  OPEN BRANCH FROM BUS 243237 TO BUS 270019 CKT 1                  / 243237 05ADAM 138 270019 AE2-089 TAP 138 1

  OPEN BRANCH FROM BUS 270019 TO BUS 243358 CKT 1                  / 270019 AE2-089 TAP 138 243358 05PENNVI 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 243358 CKT 1                  / 243319 05JAY 138 243358 05PENNVI 138 1

  OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1                  / 243253 05BLUFFP 138 243319 05JAY 138 1

END
86.0129.01 %24.5
246014 05BLUFFPNT 69.0 - 246022 05PORTLAND 69.0 CKT 1 AEP_P4_#15175_05JAY 138_D2_SRT-A
CONTINGENCY 'AEP_P4_#15175_05JAY 138_D2_SRT-A'  

  OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1                  / 243253 05BLUFFP 138 243319 05JAY 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2                  / 243319 05JAY 138 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2                  / 246016 05JAY 69.0 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2                  / 290130 05JAY 2EQ 1.00 290132 05JAY T2 13.0 2

  REMOVE SWSHUNT FROM BUS 243319                                   / 243319 05JAY 138

END
86.0128.18 %24.14
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P1-2_#17621_SRT-A-3
CONTINGENCY 'AEP_P1-2_#17621_SRT-A-3'  

  OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1                  / 971672 AH1-337 TP 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1                  / 290084 05HAYES 138 290085 05HODGIN_BP 138 1

END
50.0144.32 %8.79
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P4_#17624_05HAYES 138_A_SRT-A
CONTINGENCY 'AEP_P4_#17624_05HAYES 138_A_SRT-A'  

/  OPEN BRANCH FROM BUS 244587 TO BUS 290085 CKT 1                  / 244587 05RANDOLPH2 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1                  / 971672 AH1-337 TP(05RANDOLPH2) 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1                  / 290084 05HAYES 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 243310 TO BUS 290084 CKT 1                  / 243310 05HODGIN 138 290084 05HAYES 138 1

  OPEN BRANCH FROM BUS 243310 TO BUS 243400 CKT 1                  / 243310 05HODGIN 138 243400 05HODGIN 69.0 1

END
50.0144.24 %8.79
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P4_#17625_05HAYES 138_B_SRT-A-1
CONTINGENCY 'AEP_P4_#17625_05HAYES 138_B_SRT-A-1'  

  OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1                  / 971672 AH1-337 TP 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1                  / 290084 05HAYES 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 253290 TO BUS 290084 CKT 1                  / 253290 09BLAZER 138 290084 05HAYES 138 1

END
50.0142.88 %8.78
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-1
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
50.0120.84 %7.02
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
50.0120.84 %7.02
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P4_#14047_05DESOTO 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A'  

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 138 1

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1                  / 243278 05DESOTO 138 243340 05MEDFOR 138 1

END
50.0120.32 %7.02
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-2
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2'  

  OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1                  / 946030 AF1-268 TP 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1                  / 964610 AG1-324 TP 138 247837 05PERCH 138 1

END
50.0113.85 %7.02
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P1-2_#17621_SRT-A-1
CONTINGENCY 'AEP_P1-2_#17621_SRT-A-1'  

  OPEN BRANCH FROM BUS 244587 TO BUS 971028 CKT 1                  / 244587 05RANDOLPH2 138 971028 AG2-637 TP 138 1

END
50.0112.63 %8.79
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P4_#15023_05JAY 138_E_SRT-A
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'  

  OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4                  / 243319 05JAY 138 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4                  / 246016 05JAY 69.0 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4                  / 246015 05JAY 34.5 246018 05JAY 4EQ 1.00 4

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

END
50.0110.82 %7.08
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-3
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-3'  

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

END
50.0108.7 %7.02
246087 05RANDOLPH 69.0 - 246079 05PRICE 69.0 CKT 1 AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
CONTINGENCY 'AEP_P4_#10527_05BLUFFP 138_E2_SRT-A'  

  OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1                  / 243253 05BLUFFP 138 243319 05JAY 138 1

  OPEN BRANCH FROM BUS 243253 TO BUS 246014 CKT 1                  / 243253 05BLUFFP 138 246014 05BLUFFPNT 69.0 1

END
86.0109.8 %20.35
246087 05RANDOLPH 69.0 - 246079 05PRICE 69.0 CKT 1 AEP_P4_#17624_05HAYES 138_A_SRT-A
CONTINGENCY 'AEP_P4_#17624_05HAYES 138_A_SRT-A'  

/  OPEN BRANCH FROM BUS 244587 TO BUS 290085 CKT 1                  / 244587 05RANDOLPH2 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1                  / 971672 AH1-337 TP(05RANDOLPH2) 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1                  / 290084 05HAYES 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 243310 TO BUS 290084 CKT 1                  / 243310 05HODGIN 138 290084 05HAYES 138 1

  OPEN BRANCH FROM BUS 243310 TO BUS 243400 CKT 1                  / 243310 05HODGIN 138 243400 05HODGIN 69.0 1

END
86.0104.53 %13.85
246087 05RANDOLPH 69.0 - 246079 05PRICE 69.0 CKT 1 AEP_P4_#17625_05HAYES 138_B_SRT-A-1
CONTINGENCY 'AEP_P4_#17625_05HAYES 138_B_SRT-A-1'  

  OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1                  / 971672 AH1-337 TP 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1                  / 290084 05HAYES 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 253290 TO BUS 290084 CKT 1                  / 253290 09BLAZER 138 290084 05HAYES 138 1

END
86.0103.71 %13.84
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P4_#14047_05DESOTO 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A'  

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 138 1

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1                  / 243278 05DESOTO 138 243340 05MEDFOR 138 1

END
71.0174.69 %11.64
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
71.0174.67 %11.64
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-1
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
71.0155.86 %7.44
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P4_#15019_05DESOTO 138_F1_SRT-A
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
71.0155.86 %7.44
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-2
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2'  

  OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1                  / 946030 AF1-268 TP 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1                  / 964610 AG1-324 TP 138 247837 05PERCH 138 1

END
71.0143.6 %7.44
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P4_#15176_05JAY 138_E2_SRT-A
CONTINGENCY 'AEP_P4_#15176_05JAY 138_E2_SRT-A'  

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2                  / 243319 05JAY 138 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2                  / 246016 05JAY 69.0 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2                  / 290130 05JAY 2EQ 1.00 290132 05JAY T2 13.0 2

  REMOVE SWSHUNT FROM BUS 243319                                   / 243319 05JAY 138

END
71.0136.59 %11.17
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-3
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-3'  

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

END
71.0134.56 %7.44
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P4_#15023_05JAY 138_E_SRT-A
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'  

  OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4                  / 243319 05JAY 138 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4                  / 246016 05JAY 69.0 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4                  / 246015 05JAY 34.5 246018 05JAY 4EQ 1.00 4

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

END
71.0120.56 %10.8
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P4_#15449_05ADAM 138_C_SRT-A
CONTINGENCY 'AEP_P4_#15449_05ADAM 138_C_SRT-A'
 OPEN BRANCH FROM BUS 243237 TO BUS 243334 CKT 1   /*05ADAM       138.0 - 05MAGLEY     138.0
 OPEN BRANCH FROM BUS 243237 TO BUS 246232 CKT 1   /*05ADAM       138.0 - 05ADAMS1EQ   999.0
 OPEN BRANCH FROM BUS 246231 TO BUS 246232 CKT 1   /*05ADAMS-      69.0 - 05ADAMS1EQ   999.0
 REMOVE LOAD D2 FROM BUS 243237                    /*05ADAM       138.0
END
71.0109.03 %6.09
290130 05JAY 2EQ 1.0 - 246016 05JAY 69.0 CKT 2 AEP_P4_#15023_05JAY 138_E_SRT-A
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'  

  OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4                  / 243319 05JAY 138 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4                  / 246016 05JAY 69.0 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4                  / 246015 05JAY 34.5 246018 05JAY 4EQ 1.00 4

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

END
113.0104.97 %7.51

Transmission Owner Identified System Reinforcements on Distribution Facilities

None


Transmission Owner Identified System Reinforcements on Sub-Regional Facilities
AG2-550 Transmission Owner Identified System Reinforcements Cost Breakdown:
TORTEP ID / TO IDTitleMW ImpactPercent AllocationAllocated Cost ($USD)
AEPn9798.0 / TC2-AEP-191Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.23.3 MW36.0%$35,959
AEPn9799.0 / TC2-AEP-192Upgrade Bluff Point 69 kV 300 MCM Cu 37, Upgrade Portland 69 kV 600 A and rebuild the Bluff Point - Portland 69 kV ~ 7.48 miles24.5 MW41.0%$7,682,655
AEP(Pending) / TC2-AEP-203Randolph - Price: Summer emergency rating is 142 MVA.20.4 MW38.0%$0
AEPn9802.0 / AEP-TC2-237Jay 138/69 kV TR 2: Replace with a 138/69/13 kV 115 MVA transformer7.5 MW45.5%$591,339
Grand Total:$8,309,953
System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEPn9798.0 / TC2-AEP-191Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.$100,000

Contributor

Description: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-63727.9 MW43.1%$43,126
AG2-55023.3 MW36.0%$35,959
AG2-55113.5 MW20.9%$20,914
System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEPn9799.0 / TC2-AEP-192Upgrade Bluff Point 69 kV 300 MCM Cu 37, Upgrade Portland 69 kV 600 A and rebuild the Bluff Point - Portland 69 kV ~ 7.48 miles$18,730,000

Contributor

Description: Upgrade Bluff Point 69 kV 300 MCM Cu 37, Upgrade Portland 69 kV 600 A and rebuild the Bluff Point - Portland 69 kV ~ 7.48 miles

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-55024.5 MW41.0%$7,682,655
AG2-5515.7 MW9.5%$1,787,393
AG2-63729.5 MW49.4%$9,259,951
System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEPs1508s1508 (In service)$0

Contingent

Note: Although Queue Project AG2-550 may not have cost responsibility for this upgrade, Queue Project AG2-550 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AG2-550 comes into service prior to completion of the upgrade, Queue Project AG2-550 will need an interim study.

Description: Rebuild from Structure 1 near Anchor Hocking Station to structure 139A near Price station (~6.5 miles) using 556.5 ACSR 26/7 (SN:102 SE:141 WN:129 WE:159)

System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEP(Pending) / TC2-AEP-203Randolph - Price: Summer emergency rating is 142 MVA.$0

Contributor

Description: Randolph - Price: Summer emergency rating is 142 MVA.

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-55020.4 MW38.0%$0
AG2-5514.7 MW8.8%$0
AG2-63728.4 MW53.1%$0
System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEPn9802.0 / AEP-TC2-237Jay 138/69 kV TR 2: Replace with a 138/69/13 kV 115 MVA transformer$1,300,000

Contributor

Description: Replace with a 138/69/13 kV 115 MVA transformer

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-5507.5 MW45.5%$591,339
AG2-6379.0 MW54.5%$708,661

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-550 was evaluated as a 100.0 MW (60.0 MW Capacity) injection in the AEP area.

AG2-550 was evaluated as part of a plant. The plant consists of AG2-550, AG2-551. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (120.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC102.09 %5523.0B5638.63
6.56
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC102.08 %5523.0B5637.94
6.56
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
DEOK_P4_1403_MIAMI FORT_SRT-A
BreakerAC101.61 %178.0B180.87
7.07
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
BreakerAC109.45 %255.0B279.09
65.63
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#14047_05DESOTO 138_F_SRT-A
BreakerAC108.89 %255.0B277.66
36.31
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
BreakerAC108.85 %255.0B277.57
36.31
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC123.36 %4571.0B5638.63
6.56
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC123.34 %4571.0B5637.94
6.56
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC111.73 %4142.0B4627.93
12.68
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC106.82 %4142.0B4424.53
12.86
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC106.7 %4142.0B4419.47
12.83
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC106.67 %4142.0B4418.17
12.82
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC104.85 %4142.0B4342.78
8.95
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC104.04 %4142.0B4309.27
9.92
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.48 %4571.0B4638.62
7.4
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.94 %4571.0B4659.48
7.4
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS
SingleAC120.92 %4142.0B5008.41
7.42
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#9287_1679_SRT-A
SingleAC103.12 %4142.0B4271.28
6.2
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#3149_05HANG R 765_B_SRT-A
BreakerAC143.94 %1540.0B2216.66
7.99
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC123.49 %1540.0B1901.76
6.46
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1558_05BAKER 765_Q_SRT-A
BreakerAC121.58 %1540.0B1872.34
6.54
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#309_05HANG R 765_B2_SRT-A
BreakerAC121.32 %1540.0B1868.38
6.53
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
BreakerAC121.04 %1540.0B1864.08
6.53
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#6156_05MARQUI 765_2_SRT-A
BusAC120.75 %1540.0B1859.53
7.87
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC108.24 %1540.0B1666.97
6.27
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC107.72 %1189.0A1280.85
4.13
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
BusAC106.64 %1540.0B1642.31
5.95
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
BusAC106.58 %1540.0B1641.32
6.12
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P7-1_#11019___SRT-A-2
TowerAC106.15 %1540.0B1634.72
6.73
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC105.24 %1540.0B1620.65
6.01
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC104.94 %1540.0B1616.13
5.91
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT5_SRT-SL
BusAC103.91 %1540.0B1600.21
5.91
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#316_05AMOS 765_2_SRT-A
BusAC101.35 %1540.0B1560.82
5.92
GD2DEO&K
08MCGFY1-08LOCST1 69.0 kV Ckt 1 line
DEOK_P_CIRCUIT3281&13803_SRT-A
TowerAC119.84 %54.0B64.71
2.49
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_05MARYSV 765_A_SRT-A_SENS
BreakerAC103.61 %1868.0B1935.5
5.43
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A_SENS
BreakerAC103.47 %1868.0B1932.9
5.38
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC103.36 %1868.0B1930.81
5.42
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
BreakerAC109.45 %255.0B279.09
65.63
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#14047_05DESOTO 138_F_SRT-A
BreakerAC108.88 %255.0B277.66
36.31
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
BreakerAC108.85 %255.0B277.57
36.31

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
6.56
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
6.56
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o DEOK_P4_1403_MIAMI FORT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1403_MIAMI FORT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.61 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:180.87
MW Contribution:
7.07
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1403_MIAMI FORT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.36 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:201.78
MW Contribution:
7.09
Bus #Bus NameTypeMW Contribution
24728905RICHG2
50/50
0.247
971029AG2-637 GEN
Solar/Wind Harmer
12.801
270543AE2-219 C
Solar/Wind Harmer
7.071
247536S-71 GEN
Solar/Wind Harmer
2.324
24728805RICHG1
50/50
0.247
270222AC2-111 GEN
Solar/Wind Harmer
8.488
944031AF1-071 GEN
Solar/Wind Harmer
1.91
252510AF1-249 C
Solar/Wind Helper
0.213
970883AG2-550 GEN
Solar/Wind Harmer
7.071
970885AG2-551 GEN
Solar/Wind Harmer
1.644
270383AD1-128 GEN
Solar/Wind Harmer
4.072
247621Y3-024
Adder
0.124
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.036
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
0.258
TVALTFEXP_TVA->PJM
CLTF
0.072
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.024
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.16
MECLTFEXP_MEC->PJM
CLTF
0.578
SIGELTFEXP_SIGE->PJM
CLTF
0.015
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.432
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.046
WECLTFEXP_WEC->PJM
CLTF
0.154
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#10527_05BLUFFP 138_E2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.45 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:279.09
MW Contribution:
65.63
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.07 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:283.22
MW Contribution:
65.63
Bus #Bus NameTypeMW Contribution
970883AG2-550 GEN
Solar/Wind Harmer
65.634
970885AG2-551 GEN
Solar/Wind Harmer
15.264
971029AG2-637 GEN
Solar/Wind Harmer
100.53
247536S-71 GEN
Solar/Wind Harmer
26.558
270543AE2-219 C
Solar/Wind Harmer
65.634
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.013
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
0.044
TVALTFEXP_TVA->PJM
CLTF
0.012
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.906
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.023
MECLTFEXP_MEC->PJM
CLTF
0.107
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.556
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.012
WECLTFEXP_WEC->PJM
CLTF
0.029
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.009

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#14047_05DESOTO 138_F_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.89 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:277.66
MW Contribution:
36.31
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.88 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:290.39
MW Contribution:
36.31
Bus #Bus NameTypeMW Contribution
270024AE2-089 GEN
Solar/Wind Harmer
8.101
247621Y3-024
50/50
0.702
970883AG2-550 GEN
Solar/Wind Harmer
36.314
970885AG2-551 GEN
Solar/Wind Harmer
8.445
270201AC2-176 GEN
Solar/Wind Harmer
11.883
964611AG1-324 GEN
Solar/Wind Harmer
1.21
942221AE2-234 GEN
Solar/Wind Harmer
2.447
971029AG2-637 GEN
Solar/Wind Harmer
65.061
270543AE2-219 C
Solar/Wind Harmer
36.314
247536S-71 GEN
Solar/Wind Harmer
12.36
961761AG1-017 GEN
Solar/Wind Harmer
0.99
964611AG1-324 GEN
Solar/Wind Harmer
9.017
963791AG1-232 GEN
Solar/Wind Harmer
11.525
962031AG1-047 GEN
Solar/Wind Harmer
6.99
957741AF2-068 GEN
Solar/Wind Harmer
34.679
946031AF1-268 GEN
Solar/Wind Harmer
19.189
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.148
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.443
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.258
MECLTFEXP_MEC->PJM
CLTF
0.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.148
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.027
WECLTFEXP_WEC->PJM
CLTF
0.093
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.85 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:277.57
MW Contribution:
36.31
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.85 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:290.32
MW Contribution:
36.31
Bus #Bus NameTypeMW Contribution
270024AE2-089 GEN
Solar/Wind Harmer
8.1
247621Y3-024
50/50
0.702
970883AG2-550 GEN
Solar/Wind Harmer
36.31
970885AG2-551 GEN
Solar/Wind Harmer
8.444
270201AC2-176 GEN
Solar/Wind Harmer
11.881
964611AG1-324 GEN
Solar/Wind Harmer
1.21
942221AE2-234 GEN
Solar/Wind Harmer
2.446
971029AG2-637 GEN
Solar/Wind Harmer
65.055
270543AE2-219 C
Solar/Wind Harmer
36.31
247536S-71 GEN
Solar/Wind Harmer
12.359
961761AG1-017 GEN
Solar/Wind Harmer
0.989
964611AG1-324 GEN
Solar/Wind Harmer
9.015
963791AG1-232 GEN
Solar/Wind Harmer
11.522
962031AG1-047 GEN
Solar/Wind Harmer
6.989
957741AF2-068 GEN
Solar/Wind Harmer
34.675
946031AF1-268 GEN
Solar/Wind Harmer
19.186
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.147
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.441
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.259
MECLTFEXP_MEC->PJM
CLTF
0.271
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.161
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.027
WECLTFEXP_WEC->PJM
CLTF
0.093
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.36 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
6.56
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
6.56
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.73 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4627.93
MW Contribution:
12.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.68 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5205.7
MW Contribution:
12.22
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
0.834
270157DARBY CT2
50/50
0.831
270159DARBY CT4
50/50
0.82
270158DARBY CT3
50/50
0.818
270036AE2-216 BAT
50/50
9.171
270459AD2-067 GEN
Solar/Wind Harmer
14.991
961821AG1-024 GEN
Solar/Wind Harmer
15.221
241955AC1-078 GEN
Solar/Wind Harmer
12.28
945631AF1-228 GEN
Solar/Wind Harmer
7.537
241973AD2-163_GEN1
Solar/Wind Harmer
3.183
241974AD2-163_GEN2
Solar/Wind Harmer
3.183
943861AF1-054 GEN
Solar/Wind Harmer
6.081
943851AF1-053 GEN
Solar/Wind Harmer
2.938
253338AC1-165 GEN
Solar/Wind Harmer
1.644
253343AC1-166 GEN
Solar/Wind Harmer
1.644
270223U2-072_GEN1
Solar/Wind Harmer
2.95
270224U2-072_GEN2
Solar/Wind Harmer
2.95
270227U2-072_GEN3
Solar/Wind Harmer
2.95
270228U2-072_GEN4
Solar/Wind Harmer
2.95
270231U2-072_GEN5
Solar/Wind Harmer
2.95
270578AF1-285 GEN2
Solar/Wind Harmer
0.695
270432AC2-029 GEN
Solar/Wind Harmer
10.129
270166AC1-044 GEN3
50/50
13.634
962761AG1-125 GEN
Solar/Wind Harmer
60.25
970149AG2-104 GEN
Solar/Wind Harmer
37.205
970155AG2-107 GEN
Solar/Wind Harmer
26.272
270520AE2-214 GEN
Solar/Wind Harmer
10.552
270286AF1-227 GEN2
Solar/Wind Harmer
3.521
253333AC1-068 GEN
Solar/Wind Harmer
1.586
270391AF1-285 GEN3
Solar/Wind Harmer
1.806
270578AF1-285 GEN2
Solar/Wind Harmer
1.806
270317AD1-130_GEN
Solar/Wind Harmer
4.589
270485AE1-090_GEN
Solar/Wind Harmer
0.867
270273AD2-016 GEN
Solar/Wind Harmer
3.685
25326309TAIT D
Adder
1.458
253370AE2-315 SEC1
Adder
2.649
253371AE2-315 SEC2
Adder
2.506
253398AE2-221_GEN2
Solar/Wind Harmer
5.86
965651AG1-433 GEN
Solar/Wind Harmer
7.057
940581AE2-045 GEN
Solar/Wind Harmer
13.168
971605AH1-302 GEN
Solar/Wind Harmer
11.259
971995AH1-542 GEN
Solar/Wind Harmer
14.188
964861AG1-349 GEN
Solar/Wind Harmer
10.135
971917AH1-482 GEN
Solar/Wind Harmer
11.693
958381AF2-132 GEN
Solar/Wind Harmer
11.693
958861AF2-177 GEN
Solar/Wind Harmer
14.078
965011AG1-365 GEN
Solar/Wind Harmer
12.88
270055AF2-134 C O1
Solar/Wind Harmer
3.893
24791305MDL-5G
Solar/Wind Harmer
3.102
270594AE1-207 GEN
Solar/Wind Harmer
17.476
270032AE2-172
Solar/Wind Harmer
5.985
970373AG2-245 GEN
Solar/Wind Harmer
27.014
945371AF1-202 GEN
Solar/Wind Harmer
8.941
270051AF1-062 GEN
50/50
17.906
270475AD2-096_GEN
50/50
10.496
962771AG1-126 GEN
Solar/Wind Harmer
60.25
970153AG2-106 GEN
Solar/Wind Harmer
26.272
961921AG1-034 GEN
Solar/Wind Harmer
22.831
270284AF1-227 GEN1
Solar/Wind Harmer
9.52
270287AF1-227 GEN3
Solar/Wind Harmer
3.521
942051AE2-217 GEN
Solar/Wind Harmer
28.777
270518AE2-148 GEN
Solar/Wind Harmer
18.58
253325AC1-069 GEN
Solar/Wind Harmer
1.586
942871AE2-306 GEN
Solar/Wind Harmer
1.355
270391AF1-285 GEN3
Solar/Wind Harmer
0.695
960801AF2-371 GEN
Solar/Wind Harmer
3.703
964871AG1-351 GEN
Solar/Wind Harmer
2.557
276820AF1-078_GEN
Solar/Wind Harmer
2.191
960071AF2-298 GEN
Solar/Wind Harmer
2.003
253303V4-073 C
Solar/Wind Harmer
0.153
253370AE2-315 SEC1
Adder
2.649
253371AE2-315 SEC2
Adder
2.506
944531AF1-118 GEN
Solar/Wind Harmer
45.692
270043AE2-236 GEN
Solar/Wind Harmer
7.15
247642Z2-115 C
Solar/Wind Harmer
0.083
971347AH1-153 GEN
Solar/Wind Harmer
6.489
965461AG1-414 GEN
Solar/Wind Harmer
2.931
970289AG2-191 GEN
Solar/Wind Harmer
0.992
253394AE2-221_GEN
Solar/Wind Harmer
5.86
964401AG1-302 GEN
Solar/Wind Harmer
11.693
965021AG1-366 GEN
Solar/Wind Harmer
2.995
24690905MDL-1G C
Solar/Wind Harmer
10.33
970781AG2-491 GEN
Solar/Wind Harmer
12.867
24386205FR-12G C
Solar/Wind Harmer
5.457
274772LINCOLN ;3U
Adder
7.887
24441505OLIV SLR
Solar/Wind Harmer
0.17
962031AG1-047 GEN
Solar/Wind Harmer
3.839
957741AF2-068 GEN
Solar/Wind Harmer
19.045
253317AC1-085 GEN4
Solar/Wind Harmer
10.624
946181AF1-283 GEN
Solar/Wind Harmer
16.496
946031AF1-268 GEN
Solar/Wind Harmer
10.518
970825AG2-519 GEN
Solar/Wind Harmer
7.139
270004AE1-209 GEN
Solar/Wind Harmer
6.921
270063AE2-323 C
Solar/Wind Harmer
2.782
274724RIVER EC ;11
Adder
22.402
972231SS25-0005
Solar/Wind Harmer
12.006
972181SS23-001
Solar/Wind Harmer
7.504
274752CRETE EC ;2U
Adder
6.184
274753CRETE EC ;3U
Adder
6.184
247643Z2-116 C
Solar/Wind Harmer
0.088
276164X3-005 C
Solar/Wind Harmer
0.887
274814UNIV PK N;0U
Adder
6.378
274807UNIV PK N;3U
Adder
6.364
274811UNIV PK N;7U
Adder
6.323
274803UNIV PARK;6U
Adder
7.347
274826FISK ;BP
Adder
13.792
972259AH1-714 GEN
Adder
24.031
972038AH1-567 GEN2
Adder
0.46
274676JOLIET 29;8U
Adder
37.145
274729ELWOOD EC;1P
Adder
20.631
274730ELWOOD EC;6P
Adder
20.631
274734ELWOOD EC;8P
Adder
20.631
274736ELWOOD EC;9P
Adder
20.631
274682WAUKEGAN ;7U
Adder
22.344
25196608WSDLE5
Adder
10.548
24728505AND G1
Adder
4.712
25194608D.CRK4
Adder
2.018
274760LEE CO EC;1U
Adder
11.36
274767LEE CO EC;8U
Adder
11.226
25196008MFTGT1
Adder
1.623
235058AG1-386 C
Solar/Wind Helper
0.581
237048AF1-022 C
Solar/Wind Helper
0.208
237046AF1-021 C
Solar/Wind Helper
0.376
962511AG1-100 GEN
Solar/Wind Helper
0.525
20092526R32
Solar/Wind Helper
1.228
202652Y1-033 WT C
Solar/Wind Helper
0.585
964991AG1-363 GEN
Solar/Wind Helper
3.784
20303426NA_O38_P22
Solar/Wind Helper
1.032
23562501BACKB
Solar/Wind Helper
0.906
203993AD2-133_GEN1
Solar/Wind Helper
1.071
203854AF2-039 C
Solar/Wind Helper
0.332
20398826ARMNA MT
Solar/Wind Helper
1.535
238127S14_GEN_2
Solar/Wind Helper
0.672
941421AE2-139 GEN
Solar/Wind Helper
2.297
274887GEN-1.85
Solar/Wind Harmer
0.443
276843GEN-1.7
Solar/Wind Harmer
0.048
270119AB2-067 GEN1
50/50
13.634
270120AB2-067 GEN2
50/50
13.634
270160DARBY CT5
50/50
0.817
270161DARBY CT6
50/50
0.806
270466AD2-091
50/50
8.337
25326109MON D
50/50
1.882
25326509SID D
50/50
1.875
270349AD2-093_GEN
Solar/Wind Harmer
6.551
270471AD2-092_GEN
Solar/Wind Harmer
6.551
946101AF1-275 GEN
Solar/Wind Harmer
2.638
270054AF2-122 C O1
Solar/Wind Harmer
5.579
253383AE2-342_GEN
Solar/Wind Harmer
1.432
942861AE2-305 GEN
Solar/Wind Harmer
12.319
938701AE1-092 GEN
Solar/Wind Harmer
29.745
270462AD2-086
Solar/Wind Harmer
9.973
270269AC2-059
Solar/Wind Harmer
12.923
253378AE2-206_GEN
Solar/Wind Harmer
4.933
25322209TAIT E
Adder
12.972
25322209TAIT E
Adder
12.68
253415AE1-040 GEN
Solar/Wind Harmer
1.495
253370AE2-315 SEC1
Adder
2.649
253349AC2-067 GEN
Solar/Wind Harmer
2.665
276903AD2-071 C
Solar/Wind Harmer
12.774
24385905FR-11G C
Solar/Wind Harmer
10.583
24386605FR-22G C
Solar/Wind Harmer
5.476
270024AE2-089 GEN
Solar/Wind Harmer
5.963
972207SS24-0001
Solar/Wind Harmer
28.043
274773LINCOLN ;4U
Adder
7.887
274774LINCOLN ;5U
Adder
7.887
253316AC1-085 GEN3
Solar/Wind Harmer
10.624
946171AF1-282 GEN
Solar/Wind Harmer
12.689
970825AG2-519 GEN
Solar/Wind Harmer
2.659
270005AE1-210 C O1
Solar/Wind Harmer
6.921
274723RIVER EC ;12
Adder
22.667
274751CRETE EC ;1U
Adder
6.184
274754CRETE EC ;4U
Adder
6.184
270216AD2-079_GEN
Solar/Wind Harmer
0.764
274812UNIV PK N;8U
Adder
6.323
24639705ELKHART HY
Adder
0.193
274802UNIV PARK;5U
Adder
7.347
274676JOLIET 29;8U
Adder
38.521
274732ELWOOD EC;7P
Adder
20.631
274674JOLIET 9 ;6U
Adder
19.323
274745AC1-111 GEN9
Adder
6.986
274682WAUKEGAN ;7U
Adder
22.344
274828WAUKEGAN ;BP
Adder
13.726
274822ROCKFORD ;11
Adder
24.117
24728605AND G2
Adder
4.712
25194608D.CRK4
Adder
2.018
274761LEE CO EC;2U
Adder
11.36
274766LEE CO EC;7U
Adder
11.226
25196808ZIMRHP
Adder
91.918
25196008MFTGT1
Adder
1.676
970091AG2-072 GEN
Adder
52.601
254303AC2-168 GEN
Solar/Wind Helper
0.2
241966AE1-183 GEN
Solar/Wind Helper
0.316
961971AG1-040 GEN
Solar/Wind Helper
0.526
203830AF1-094 GEN
Solar/Wind Helper
0.526
203979AG1-198 GEN
Solar/Wind Helper
0.315
203947AF1-006 C
Solar/Wind Helper
0.571
20084626FORWARD
Solar/Wind Helper
0.376
20089026BF_G21_K23
Solar/Wind Helper
0.492
964201AG1-281 GEN
Solar/Wind Helper
0.505
238185AF2-356 C
Solar/Wind Helper
2.211
20091526CHSTN_FL
Solar/Wind Helper
0.61
20090526Q36
Solar/Wind Helper
1.071
203952AE2-129 C
Solar/Wind Helper
0.495
203855AF2-088 C
Solar/Wind Helper
0.16
238126S14_GEN_1
Solar/Wind Helper
0.672
238120AE2-309 GEN
Solar/Wind Helper
0.423
23751101LEADS_P59
Solar/Wind Helper
1.861
270302AB2-170 GEN
Solar/Wind Harmer
12.005
241972AD1-140 GEN
Solar/Wind Harmer
6.404
253372AE2-315 SEC3
Adder
2.506
253372AE2-315 SEC3
Adder
2.506
270071AF1-092 GEN
Solar/Wind Harmer
19.771
25306009OHH W.
Adder
3.787
270340AC2-060 GEN
Solar/Wind Harmer
3.955
270263AC1-001 GEN
Solar/Wind Harmer
1.363
24729505KEY G4
Adder
8.445
970289AG2-191 GEN
Solar/Wind Harmer
2.456
958711AF2-162 GEN
Solar/Wind Harmer
1.306
959141AF2-205 GEN
Solar/Wind Harmer
7.803
958391AF2-133 GEN
Solar/Wind Harmer
11.7
959331AF2-224 GEN
Solar/Wind Harmer
12.88
946581AF1-322 GEN
Solar/Wind Harmer
13.166
24691005MDL-2G C
Solar/Wind Harmer
4.758
253406AD2-031_GEN
Solar/Wind Harmer
1.637
945581AF1-223 GEN
Solar/Wind Harmer
5.812
960681AF2-359 GEN
Solar/Wind Harmer
4.837
963791AG1-232 GEN
Solar/Wind Harmer
17.234
24386405FR-21G C
Solar/Wind Harmer
5.476
24387005FR-3G C
Solar/Wind Harmer
5.037
274775LINCOLN ;6U
Adder
7.887
274776LINCOLN ;7U
Adder
7.887
274777LINCOLN ;8U
Adder
7.887
961761AG1-017 GEN
Solar/Wind Harmer
0.543
270526AF1-158 GEN
Solar/Wind Harmer
5.757
964611AG1-324 GEN
Solar/Wind Harmer
4.95
253433AC1-085 GEN1
Solar/Wind Harmer
6.743
253432AC1-085 GEN2
Solar/Wind Harmer
0.339
247536S-71 GEN
Solar/Wind Harmer
5.133
247521TR3_G114
Solar/Wind Harmer
4.26
270191TR4_S_V150
Solar/Wind Harmer
3.801
965051AG1-369 GEN
Solar/Wind Harmer
6.329
270543AE2-219 C
Solar/Wind Harmer
12.676
970031AG2-029 GEN
Solar/Wind Harmer
31.677
971771AH1-392 GEN
Solar/Wind Harmer
11.401
971029AG2-637 GEN
Solar/Wind Harmer
18.999
965041AG1-368 GEN
Solar/Wind Harmer
12.63
963841AG1-237 GEN
Solar/Wind Harmer
13.795
972037AH1-567 GEN1
Adder
0.231
972228AH1-698 GEN2
Adder
4.668
972227AH1-698 GEN1
Adder
3.287
274827FISK ;RP
Adder
9.775
274800UNIV PARK;3U
Adder
7.343
274801UNIV PARK;4U
Adder
7.343
274687WILL CNTY;4U
Adder
35.099
274687WILL CNTY;4U
Adder
35.099
274675JOLIET 29;7U
Adder
38.521
274675JOLIET 29;7U
Adder
37.145
274728ELWOOD EC;5P
Adder
20.631
274731ELWOOD EC;2P
Adder
20.631
274733ELWOOD EC;3P
Adder
20.631
274735ELWOOD EC;4P
Adder
20.631
274744AC1-111 GEN8
Adder
6.986
274746AC1-111 G10
Adder
6.986
25196408WSDLE3
Adder
10.858
274823ROCKFORD ;21
Adder
23.942
972267AH1-718 GEN
Adder
5.066
25196108MFTGT2
Adder
1.847
25196108MFTGT2
Adder
1.715
241985AE1-237 GEN
Solar/Wind Helper
0.312
241982AE2-343 S C
Solar/Wind Helper
0.28
241997AF1-093 GEN
Solar/Wind Helper
0.316
23652301WDPWR_K20
Solar/Wind Helper
0.162
23750501ELLIOTTS
Solar/Wind Helper
0.704
203846AF2-130 C
Solar/Wind Helper
0.505
20089126CSLMN_L13
Solar/Wind Helper
0.622
20089226LOOKOUT
Solar/Wind Helper
0.62
20088926STNY CRK
Solar/Wind Helper
0.862
20094526CT_V3-030
Solar/Wind Helper
0.502
203955AF1-039 C O1
Solar/Wind Helper
0.386
203940AF1-140 C
Solar/Wind Helper
0.417
20088626ARWF_N39
Solar/Wind Helper
1.259
20334926Z1-069 C
Solar/Wind Helper
1.425
23750701CROSSCHOOL
Solar/Wind Helper
1.2
238118U2-030_1
Solar/Wind Helper
0.287
200917MEHOOPANY_G
Solar/Wind Helper
2.134
253400AC2-068 GEN
Solar/Wind Harmer
1.072
970349AG2-230 GEN
Solar/Wind Harmer
19.467
945421AF1-207 GEN
Solar/Wind Harmer
18.162
957841AF2-078 GEN
Solar/Wind Harmer
7.818
970291AG2-192 GEN
Solar/Wind Harmer
1.681
970291AG2-192 GEN
Solar/Wind Harmer
0.541
944541AF1-119 GEN
Solar/Wind Harmer
5.407
960971AF2-388 GEN
Solar/Wind Harmer
14.115
270535AF1-215 GEN1
Solar/Wind Harmer
5.84
270536AF1-215 GEN2
Solar/Wind Harmer
5.84
270180AB1-006 GEN1
Solar/Wind Harmer
9.254
24697605MDL-3G C
Solar/Wind Harmer
4.743
24755605MDL-5G
Solar/Wind Harmer
3.102
24697905MDL-4G C
Solar/Wind Harmer
2.953
270181AB1-006 GEN2
Solar/Wind Harmer
0.92
942221AE2-234 GEN
Solar/Wind Harmer
4.491
965681AG1-436 GEN
Solar/Wind Harmer
16.003
965791AG1-447 GEN
Solar/Wind Harmer
8.187
270031AE2-169
Solar/Wind Harmer
10.386
270599AE1-208 GEN
Solar/Wind Harmer
10.386
24387305FR-4G C
Solar/Wind Harmer
6.468
966841AG1-555 GEN
Solar/Wind Harmer
3.198
274770LINCOLN ;1U
Adder
7.887
274771LINCOLN ;2U
Adder
7.887
24725505WLD G2 C
Solar/Wind Harmer
5.055
24699105WLD G1 C
Solar/Wind Harmer
4.996
270201AC2-176 GEN
Solar/Wind Harmer
6.526
247621Y3-024
Adder
0.306
964611AG1-324 GEN
Solar/Wind Harmer
0.664
270246TR4_N_V150
Solar/Wind Harmer
1.078
270247TR4_N_V136
Solar/Wind Harmer
1.078
970883AG2-550 GEN
Solar/Wind Harmer
12.676
970885AG2-551 GEN
Solar/Wind Harmer
2.948
270383AD1-128 GEN
Solar/Wind Harmer
7.709
274805UNIV PK N;1U
Adder
6.337
274808UNIV PK N;4U
Adder
6.295
274888KELLY CRK;1U
Solar/Wind Harmer
7.437
247620Y3-023
Adder
0.579
274674JOLIET 9 ;6U
Adder
19.323
274696ROCKY RD ;4P
Adder
14.179
274695ROCKY RD ;2P
Adder
13.852
274693ROCKY RD ;1P
Adder
13.715
274697ROCKY RD ;3P
Adder
3.763
274683WAUKEGAN ;8U
Adder
26.185
274683WAUKEGAN ;8U
Adder
22.073
25194408D.CRK1
Adder
9.285
25194508D.CRK3
Adder
1.736
972235AH1-702 GEN1
Adder
3.095
972236AH1-702 GEN2
Adder
2.691
274764LEE CO EC;5U
Adder
11.387
274765LEE CO EC;6U
Adder
11.387
274762LEE CO EC;3U
Adder
11.36
274763LEE CO EC;4U
Adder
11.253
254304AE2-114 C
Solar/Wind Helper
0.277
254305AE2-115 C
Solar/Wind Helper
0.277
241967AE2-285_GEN
Solar/Wind Helper
0.8
241801AE1-079 GEN
Solar/Wind Helper
0.313
962101AG1-054 GEN
Solar/Wind Helper
0.804
237043AE2-125 C
Solar/Wind Helper
0.204
946071AF1-272 GEN
Solar/Wind Helper
2.92
203835AF1-098 GEN
Solar/Wind Helper
2.083
946381AF1-302 GEN
Solar/Wind Helper
0.24
20083426SW_E13_K22
Solar/Wind Helper
0.059
20088826HIGHLAND
Solar/Wind Helper
0.947
203818AF1-086 GEN
Solar/Wind Helper
1.799
23585401KL_K28_T16
Solar/Wind Helper
1.286
203853AF1-134 C O1
Solar/Wind Helper
0.505
203804AE2-113_GEN
Solar/Wind Helper
1.868
23751201ROTHROCK
Solar/Wind Helper
0.744
203961AE2-224 GEN
Solar/Wind Helper
2.516
940863AE2-074 GEN
Solar/Wind Helper
0.487
203954AE2-126 C
Solar/Wind Helper
0.496
235054AD2-180 GEN
Solar/Wind Helper
1.697
203946AE2-131 C
Solar/Wind Helper
0.495
238117U2-030
Solar/Wind Helper
0.287
235531U2-073 GEN
Solar/Wind Helper
2.713
LAGNLTFEXP_LAGN->PJM
CLTF
17.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.667
TVALTFEXP_TVA->PJM
CLTF
8.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
156.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.206
MECLTFEXP_MEC->PJM
CLTF
19.244
SIGELTFEXP_SIGE->PJM
CLTF
0.591
CPLELTFEXP_CPLE->PJM
CLTF
2.158
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.077
NYPJM->LTFIMP_NY
CLTF
5.256
LGEELTFEXP_LGEE->PJM
CLTF
7.735
WECLTFEXP_WEC->PJM
CLTF
4.687
AG2-052LTFEXP_AG2-052->PJM
LTF
0.294
AH1-155LTFEXP_AH1-155->PJM
LTF
0.441

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.82 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4424.53
MW Contribution:
12.86
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5024.36
MW Contribution:
12.39
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
18.085
270475AD2-096_GEN
50/50
10.605
962771AG1-126 GEN
Solar/Wind Harmer
60.856
970153AG2-106 GEN
Solar/Wind Harmer
26.536
961921AG1-034 GEN
Solar/Wind Harmer
23.077
270284AF1-227 GEN1
Solar/Wind Harmer
9.626
270287AF1-227 GEN3
Solar/Wind Harmer
3.56
942051AE2-217 GEN
Solar/Wind Harmer
29.118
270518AE2-148 GEN
Solar/Wind Harmer
18.808
253325AC1-069 GEN
Solar/Wind Harmer
1.605
942871AE2-306 GEN
Solar/Wind Harmer
1.372
270391AF1-285 GEN3
Solar/Wind Harmer
0.703
960801AF2-371 GEN
Solar/Wind Harmer
3.753
964871AG1-351 GEN
Solar/Wind Harmer
2.591
276820AF1-078_GEN
Solar/Wind Harmer
2.221
960071AF2-298 GEN
Solar/Wind Harmer
2.031
253303V4-073 C
Solar/Wind Harmer
0.155
253370AE2-315 SEC1
Adder
2.687
253371AE2-315 SEC2
Adder
2.541
944531AF1-118 GEN
Solar/Wind Harmer
46.338
270043AE2-236 GEN
Solar/Wind Harmer
7.251
247642Z2-115 C
Solar/Wind Harmer
0.084
971347AH1-153 GEN
Solar/Wind Harmer
6.581
965461AG1-414 GEN
Solar/Wind Harmer
2.973
970289AG2-191 GEN
Solar/Wind Harmer
1.006
253394AE2-221_GEN
Solar/Wind Harmer
5.944
964401AG1-302 GEN
Solar/Wind Harmer
11.86
965021AG1-366 GEN
Solar/Wind Harmer
3.038
24690905MDL-1G C
Solar/Wind Harmer
10.477
970781AG2-491 GEN
Solar/Wind Harmer
13.051
24386205FR-12G C
Solar/Wind Harmer
5.536
274772LINCOLN ;3U
Adder
8.001
24441505OLIV SLR
Solar/Wind Harmer
0.172
962031AG1-047 GEN
Solar/Wind Harmer
3.895
957741AF2-068 GEN
Solar/Wind Harmer
19.322
253317AC1-085 GEN4
Solar/Wind Harmer
10.78
946181AF1-283 GEN
Solar/Wind Harmer
16.739
946031AF1-268 GEN
Solar/Wind Harmer
10.671
970825AG2-519 GEN
Solar/Wind Harmer
7.243
270004AE1-209 GEN
Solar/Wind Harmer
7.022
270063AE2-323 C
Solar/Wind Harmer
2.823
274724RIVER EC ;11
Adder
22.726
972231SS25-0005
Solar/Wind Harmer
12.18
972181SS23-001
Solar/Wind Harmer
7.613
274752CRETE EC ;2U
Adder
6.273
274753CRETE EC ;3U
Adder
6.273
247643Z2-116 C
Solar/Wind Harmer
0.089
276164X3-005 C
Solar/Wind Harmer
0.9
274814UNIV PK N;0U
Adder
6.471
274807UNIV PK N;3U
Adder
6.457
274811UNIV PK N;7U
Adder
6.415
274803UNIV PARK;6U
Adder
7.454
274826FISK ;BP
Adder
13.992
972259AH1-714 GEN
Adder
24.38
972038AH1-567 GEN2
Adder
0.466
274676JOLIET 29;8U
Adder
37.686
274729ELWOOD EC;1P
Adder
20.931
274730ELWOOD EC;6P
Adder
20.931
274734ELWOOD EC;8P
Adder
20.931
274736ELWOOD EC;9P
Adder
20.931
274682WAUKEGAN ;7U
Adder
22.672
25196608WSDLE5
Adder
10.708
24728505AND G1
Adder
4.783
25194608D.CRK4
Adder
2.049
274760LEE CO EC;1U
Adder
11.529
274767LEE CO EC;8U
Adder
11.394
25196008MFTGT1
Adder
1.648
235058AG1-386 C
Solar/Wind Helper
0.575
237048AF1-022 C
Solar/Wind Helper
0.206
237046AF1-021 C
Solar/Wind Helper
0.372
962511AG1-100 GEN
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Helper
0.578
20092526R32
Solar/Wind Helper
1.213
964991AG1-363 GEN
Solar/Wind Helper
3.745
20303426NA_O38_P22
Solar/Wind Helper
1.019
23562501BACKB
Solar/Wind Helper
0.896
203993AD2-133_GEN1
Solar/Wind Helper
1.057
203854AF2-039 C
Solar/Wind Helper
0.328
20398826ARMNA MT
Solar/Wind Helper
1.514
238127S14_GEN_2
Solar/Wind Helper
0.664
941421AE2-139 GEN
Solar/Wind Helper
2.265
965431AG1-411 GEN
Solar/Wind Harmer
0
270166AC1-044 GEN3
50/50
13.704
962761AG1-125 GEN
Solar/Wind Harmer
60.856
970149AG2-104 GEN
Solar/Wind Harmer
37.579
970155AG2-107 GEN
Solar/Wind Harmer
26.536
270520AE2-214 GEN
Solar/Wind Harmer
10.667
270286AF1-227 GEN2
Solar/Wind Harmer
3.56
253333AC1-068 GEN
Solar/Wind Harmer
1.605
270391AF1-285 GEN3
Solar/Wind Harmer
1.829
270578AF1-285 GEN2
Solar/Wind Harmer
1.829
270317AD1-130_GEN
Solar/Wind Harmer
4.649
270485AE1-090_GEN
Solar/Wind Harmer
0.878
270273AD2-016 GEN
Solar/Wind Harmer
3.736
25326309TAIT D
Adder
1.478
253370AE2-315 SEC1
Adder
2.687
253371AE2-315 SEC2
Adder
2.541
253398AE2-221_GEN2
Solar/Wind Harmer
5.944
965651AG1-433 GEN
Solar/Wind Harmer
7.158
940581AE2-045 GEN
Solar/Wind Harmer
13.356
971605AH1-302 GEN
Solar/Wind Harmer
11.42
971995AH1-542 GEN
Solar/Wind Harmer
14.398
964861AG1-349 GEN
Solar/Wind Harmer
10.279
971917AH1-482 GEN
Solar/Wind Harmer
11.86
958381AF2-132 GEN
Solar/Wind Harmer
11.86
958861AF2-177 GEN
Solar/Wind Harmer
14.28
965011AG1-365 GEN
Solar/Wind Harmer
13.064
270055AF2-134 C O1
Solar/Wind Harmer
3.949
270594AE1-207 GEN
Solar/Wind Harmer
17.727
270032AE2-172
Solar/Wind Harmer
6.071
24791305MDL-5G
Solar/Wind Harmer
3.146
970373AG2-245 GEN
Solar/Wind Harmer
27.399
945371AF1-202 GEN
Solar/Wind Harmer
9.07
276903AD2-071 C
Solar/Wind Harmer
12.959
24385905FR-11G C
Solar/Wind Harmer
10.735
24386605FR-22G C
Solar/Wind Harmer
5.555
270024AE2-089 GEN
Solar/Wind Harmer
6.05
972207SS24-0001
Solar/Wind Harmer
28.446
274773LINCOLN ;4U
Adder
8.001
274774LINCOLN ;5U
Adder
8.001
253316AC1-085 GEN3
Solar/Wind Harmer
10.78
946171AF1-282 GEN
Solar/Wind Harmer
12.876
970825AG2-519 GEN
Solar/Wind Harmer
2.698
270005AE1-210 C O1
Solar/Wind Harmer
7.022
274723RIVER EC ;12
Adder
22.995
274751CRETE EC ;1U
Adder
6.273
274754CRETE EC ;4U
Adder
6.273
270216AD2-079_GEN
Solar/Wind Harmer
0.776
274812UNIV PK N;8U
Adder
6.415
24639705ELKHART HY
Adder
0.196
274802UNIV PARK;5U
Adder
7.454
274676JOLIET 29;8U
Adder
39.082
274732ELWOOD EC;7P
Adder
20.931
274674JOLIET 9 ;6U
Adder
19.605
274745AC1-111 GEN9
Adder
7.088
274682WAUKEGAN ;7U
Adder
22.672
274828WAUKEGAN ;BP
Adder
13.928
274822ROCKFORD ;11
Adder
24.475
24728605AND G2
Adder
4.783
25194608D.CRK4
Adder
2.049
274761LEE CO EC;2U
Adder
11.529
274766LEE CO EC;7U
Adder
11.394
25196808ZIMRHP
Adder
93.328
25196008MFTGT1
Adder
1.701
970091AG2-072 GEN
Adder
53.422
254303AC2-168 GEN
Solar/Wind Helper
0.198
241966AE1-183 GEN
Solar/Wind Helper
0.312
961971AG1-040 GEN
Solar/Wind Helper
0.519
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.372
20089026BF_G21_K23
Solar/Wind Helper
0.487
238185AF2-356 C
Solar/Wind Helper
2.187
964201AG1-281 GEN
Solar/Wind Helper
0.499
20091526CHSTN_FL
Solar/Wind Helper
0.602
20090526Q36
Solar/Wind Helper
1.057
203952AE2-129 C
Solar/Wind Helper
0.489
203855AF2-088 C
Solar/Wind Helper
0.158
238126S14_GEN_1
Solar/Wind Helper
0.664
238120AE2-309 GEN
Solar/Wind Helper
0.418
23751101LEADS_P59
Solar/Wind Helper
1.838
965421AG1-410 GEN
Solar/Wind Harmer
8.043
270156DARBY CT1
50/50
0.843
270157DARBY CT2
50/50
0.841
270159DARBY CT4
50/50
0.83
270158DARBY CT3
50/50
0.828
270036AE2-216 BAT
50/50
9.29
270459AD2-067 GEN
Solar/Wind Harmer
15.153
961821AG1-024 GEN
Solar/Wind Harmer
15.385
241955AC1-078 GEN
Solar/Wind Harmer
12.422
945631AF1-228 GEN
Solar/Wind Harmer
7.626
241973AD2-163_GEN1
Solar/Wind Harmer
3.221
241974AD2-163_GEN2
Solar/Wind Harmer
3.221
943861AF1-054 GEN
Solar/Wind Harmer
6.153
943851AF1-053 GEN
Solar/Wind Harmer
2.973
253338AC1-165 GEN
Solar/Wind Harmer
1.665
253343AC1-166 GEN
Solar/Wind Harmer
1.665
270223U2-072_GEN1
Solar/Wind Harmer
2.986
270224U2-072_GEN2
Solar/Wind Harmer
2.986
270227U2-072_GEN3
Solar/Wind Harmer
2.986
270228U2-072_GEN4
Solar/Wind Harmer
2.986
270231U2-072_GEN5
Solar/Wind Harmer
2.986
270578AF1-285 GEN2
Solar/Wind Harmer
0.703
270432AC2-029 GEN
Solar/Wind Harmer
10.263
270302AB2-170 GEN
Solar/Wind Harmer
12.161
241972AD1-140 GEN
Solar/Wind Harmer
6.488
253372AE2-315 SEC3
Adder
2.541
253372AE2-315 SEC3
Adder
2.541
270071AF1-092 GEN
Solar/Wind Harmer
20.047
25306009OHH W.
Adder
3.841
270340AC2-060 GEN
Solar/Wind Harmer
4.012
270263AC1-001 GEN
Solar/Wind Harmer
1.383
24729505KEY G4
Adder
8.564
970289AG2-191 GEN
Solar/Wind Harmer
2.491
958711AF2-162 GEN
Solar/Wind Harmer
1.325
959141AF2-205 GEN
Solar/Wind Harmer
7.914
958391AF2-133 GEN
Solar/Wind Harmer
11.867
959331AF2-224 GEN
Solar/Wind Harmer
13.064
946581AF1-322 GEN
Solar/Wind Harmer
13.354
24691005MDL-2G C
Solar/Wind Harmer
4.826
253406AD2-031_GEN
Solar/Wind Harmer
1.661
945581AF1-223 GEN
Solar/Wind Harmer
5.896
960681AF2-359 GEN
Solar/Wind Harmer
4.907
963791AG1-232 GEN
Solar/Wind Harmer
17.483
24386405FR-21G C
Solar/Wind Harmer
5.555
24387005FR-3G C
Solar/Wind Harmer
5.109
274775LINCOLN ;6U
Adder
8.001
274776LINCOLN ;7U
Adder
8.001
274777LINCOLN ;8U
Adder
8.001
961761AG1-017 GEN
Solar/Wind Harmer
0.551
270526AF1-158 GEN
Solar/Wind Harmer
5.84
253433AC1-085 GEN1
Solar/Wind Harmer
6.842
253432AC1-085 GEN2
Solar/Wind Harmer
0.344
964611AG1-324 GEN
Solar/Wind Harmer
5.022
247536S-71 GEN
Solar/Wind Harmer
5.208
247521TR3_G114
Solar/Wind Harmer
4.322
270191TR4_S_V150
Solar/Wind Harmer
3.856
965051AG1-369 GEN
Solar/Wind Harmer
6.421
270543AE2-219 C
Solar/Wind Harmer
12.861
970031AG2-029 GEN
Solar/Wind Harmer
32.137
971771AH1-392 GEN
Solar/Wind Harmer
11.566
971029AG2-637 GEN
Solar/Wind Harmer
19.276
965041AG1-368 GEN
Solar/Wind Harmer
12.814
963841AG1-237 GEN
Solar/Wind Harmer
13.995
972037AH1-567 GEN1
Adder
0.234
972228AH1-698 GEN2
Adder
4.735
972227AH1-698 GEN1
Adder
3.334
274827FISK ;RP
Adder
9.917
274800UNIV PARK;3U
Adder
7.45
274801UNIV PARK;4U
Adder
7.45
274687WILL CNTY;4U
Adder
35.61
274687WILL CNTY;4U
Adder
35.61
274675JOLIET 29;7U
Adder
39.082
274675JOLIET 29;7U
Adder
37.686
274728ELWOOD EC;5P
Adder
20.931
274731ELWOOD EC;2P
Adder
20.931
274733ELWOOD EC;3P
Adder
20.931
274735ELWOOD EC;4P
Adder
20.931
274744AC1-111 GEN8
Adder
7.088
274746AC1-111 G10
Adder
7.088
25196408WSDLE3
Adder
11.023
274823ROCKFORD ;21
Adder
24.297
972267AH1-718 GEN
Adder
5.142
25196108MFTGT2
Adder
1.876
25196108MFTGT2
Adder
1.742
241985AE1-237 GEN
Solar/Wind Helper
0.309
241982AE2-343 S C
Solar/Wind Helper
0.277
241997AF1-093 GEN
Solar/Wind Helper
0.312
23652301WDPWR_K20
Solar/Wind Helper
0.16
23750501ELLIOTTS
Solar/Wind Helper
0.697
203846AF2-130 C
Solar/Wind Helper
0.499
20089126CSLMN_L13
Solar/Wind Helper
0.615
20089226LOOKOUT
Solar/Wind Helper
0.613
20088926STNY CRK
Solar/Wind Helper
0.851
203955AF1-039 C O1
Solar/Wind Helper
0.382
20094526CT_V3-030
Solar/Wind Helper
0.495
203940AF1-140 C
Solar/Wind Helper
0.412
20088626ARWF_N39
Solar/Wind Helper
1.243
20334926Z1-069 C
Solar/Wind Helper
1.406
23750701CROSSCHOOL
Solar/Wind Helper
1.187
238118U2-030_1
Solar/Wind Helper
0.284
200917MEHOOPANY_G
Solar/Wind Helper
2.104
270119AB2-067 GEN1
50/50
13.704
270120AB2-067 GEN2
50/50
13.704
270160DARBY CT5
50/50
0.827
270161DARBY CT6
50/50
0.815
270466AD2-091
50/50
8.446
25326109MON D
50/50
1.908
25326509SID D
50/50
1.901
270349AD2-093_GEN
Solar/Wind Harmer
6.619
270471AD2-092_GEN
Solar/Wind Harmer
6.619
946101AF1-275 GEN
Solar/Wind Harmer
2.667
270054AF2-122 C O1
Solar/Wind Harmer
5.642
253383AE2-342_GEN
Solar/Wind Harmer
1.448
942861AE2-305 GEN
Solar/Wind Harmer
12.466
938701AE1-092 GEN
Solar/Wind Harmer
30.136
270462AD2-086
Solar/Wind Harmer
10.102
270269AC2-059
Solar/Wind Harmer
13.102
253378AE2-206_GEN
Solar/Wind Harmer
5
25322209TAIT E
Adder
13.154
25322209TAIT E
Adder
12.859
253415AE1-040 GEN
Solar/Wind Harmer
1.516
253370AE2-315 SEC1
Adder
2.687
253349AC2-067 GEN
Solar/Wind Harmer
2.703
253400AC2-068 GEN
Solar/Wind Harmer
1.087
970349AG2-230 GEN
Solar/Wind Harmer
19.743
945421AF1-207 GEN
Solar/Wind Harmer
18.42
957841AF2-078 GEN
Solar/Wind Harmer
7.93
970291AG2-192 GEN
Solar/Wind Harmer
1.705
970291AG2-192 GEN
Solar/Wind Harmer
0.549
944541AF1-119 GEN
Solar/Wind Harmer
5.484
960971AF2-388 GEN
Solar/Wind Harmer
14.317
270535AF1-215 GEN1
Solar/Wind Harmer
5.924
270536AF1-215 GEN2
Solar/Wind Harmer
5.924
270180AB1-006 GEN1
Solar/Wind Harmer
9.386
24697605MDL-3G C
Solar/Wind Harmer
4.811
24755605MDL-5G
Solar/Wind Harmer
3.146
24697905MDL-4G C
Solar/Wind Harmer
2.995
270181AB1-006 GEN2
Solar/Wind Harmer
0.933
942221AE2-234 GEN
Solar/Wind Harmer
4.556
965681AG1-436 GEN
Solar/Wind Harmer
16.232
965791AG1-447 GEN
Solar/Wind Harmer
8.305
270031AE2-169
Solar/Wind Harmer
10.536
270599AE1-208 GEN
Solar/Wind Harmer
10.536
24387305FR-4G C
Solar/Wind Harmer
6.561
966841AG1-555 GEN
Solar/Wind Harmer
3.244
274770LINCOLN ;1U
Adder
8.001
274771LINCOLN ;2U
Adder
8.001
24725505WLD G2 C
Solar/Wind Harmer
5.129
24699105WLD G1 C
Solar/Wind Harmer
5.069
270201AC2-176 GEN
Solar/Wind Harmer
6.621
247621Y3-024
Adder
0.311
964611AG1-324 GEN
Solar/Wind Harmer
0.674
270246TR4_N_V150
Solar/Wind Harmer
1.093
270247TR4_N_V136
Solar/Wind Harmer
1.093
970883AG2-550 GEN
Solar/Wind Harmer
12.861
970885AG2-551 GEN
Solar/Wind Harmer
2.991
270383AD1-128 GEN
Solar/Wind Harmer
7.821
274805UNIV PK N;1U
Adder
6.429
274808UNIV PK N;4U
Adder
6.386
247620Y3-023
Adder
0.588
274674JOLIET 9 ;6U
Adder
19.605
274695ROCKY RD ;2P
Adder
14.055
274693ROCKY RD ;1P
Adder
13.917
274697ROCKY RD ;3P
Adder
3.818
274696ROCKY RD ;4P
Adder
14.387
274683WAUKEGAN ;8U
Adder
26.57
274683WAUKEGAN ;8U
Adder
22.397
25194408D.CRK1
Adder
9.426
25194508D.CRK3
Adder
1.762
972235AH1-702 GEN1
Adder
3.14
972236AH1-702 GEN2
Adder
2.731
274764LEE CO EC;5U
Adder
11.556
274765LEE CO EC;6U
Adder
11.556
274762LEE CO EC;3U
Adder
11.529
274763LEE CO EC;4U
Adder
11.421
254304AE2-114 C
Solar/Wind Helper
0.274
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
241801AE1-079 GEN
Solar/Wind Helper
0.309
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
946071AF1-272 GEN
Solar/Wind Helper
2.885
203835AF1-098 GEN
Solar/Wind Helper
2.054
946381AF1-302 GEN
Solar/Wind Helper
0.237
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.936
203818AF1-086 GEN
Solar/Wind Helper
1.776
23585401KL_K28_T16
Solar/Wind Helper
1.272
203853AF1-134 C O1
Solar/Wind Helper
0.498
23751201ROTHROCK
Solar/Wind Helper
0.736
203804AE2-113_GEN
Solar/Wind Helper
1.843
203961AE2-224 GEN
Solar/Wind Helper
2.485
940863AE2-074 GEN
Solar/Wind Helper
0.48
235054AD2-180 GEN
Solar/Wind Helper
1.679
203954AE2-126 C
Solar/Wind Helper
0.49
203946AE2-131 C
Solar/Wind Helper
0.489
238117U2-030
Solar/Wind Helper
0.284
235531U2-073 GEN
Solar/Wind Helper
2.681
LAGNLTFEXP_LAGN->PJM
CLTF
17.663
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.14
TVALTFEXP_TVA->PJM
CLTF
8.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.09
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.869
MECLTFEXP_MEC->PJM
CLTF
19.548
SIGELTFEXP_SIGE->PJM
CLTF
0.601
CPLELTFEXP_CPLE->PJM
CLTF
2.322
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.459
NYPJM->LTFIMP_NY
CLTF
5.177
LGEELTFEXP_LGEE->PJM
CLTF
7.861
WECLTFEXP_WEC->PJM
CLTF
4.757
AG2-052LTFEXP_AG2-052->PJM
LTF
0.298
AH1-155LTFEXP_AH1-155->PJM
LTF
0.447

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4419.47
MW Contribution:
12.83
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.09 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5015.35
MW Contribution:
12.35
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
13.695
962761AG1-125 GEN
Solar/Wind Harmer
60.765
970149AG2-104 GEN
Solar/Wind Harmer
37.522
970155AG2-107 GEN
Solar/Wind Harmer
26.496
270520AE2-214 GEN
Solar/Wind Harmer
10.649
270286AF1-227 GEN2
Solar/Wind Harmer
3.554
253333AC1-068 GEN
Solar/Wind Harmer
1.602
270391AF1-285 GEN3
Solar/Wind Harmer
1.826
270578AF1-285 GEN2
Solar/Wind Harmer
1.826
270317AD1-130_GEN
Solar/Wind Harmer
4.64
270485AE1-090_GEN
Solar/Wind Harmer
0.877
270273AD2-016 GEN
Solar/Wind Harmer
3.727
25326309TAIT D
Adder
1.475
253370AE2-315 SEC1
Adder
2.681
253371AE2-315 SEC2
Adder
2.536
253398AE2-221_GEN2
Solar/Wind Harmer
5.932
965651AG1-433 GEN
Solar/Wind Harmer
7.144
940581AE2-045 GEN
Solar/Wind Harmer
13.329
971605AH1-302 GEN
Solar/Wind Harmer
11.397
971995AH1-542 GEN
Solar/Wind Harmer
14.364
964861AG1-349 GEN
Solar/Wind Harmer
10.259
971917AH1-482 GEN
Solar/Wind Harmer
11.837
958381AF2-132 GEN
Solar/Wind Harmer
11.837
958861AF2-177 GEN
Solar/Wind Harmer
14.251
965011AG1-365 GEN
Solar/Wind Harmer
13.038
270055AF2-134 C O1
Solar/Wind Harmer
3.941
270594AE1-207 GEN
Solar/Wind Harmer
17.691
270032AE2-172
Solar/Wind Harmer
6.059
24791305MDL-5G
Solar/Wind Harmer
3.14
970373AG2-245 GEN
Solar/Wind Harmer
27.345
945371AF1-202 GEN
Solar/Wind Harmer
9.051
276903AD2-071 C
Solar/Wind Harmer
12.933
24385905FR-11G C
Solar/Wind Harmer
10.714
24386605FR-22G C
Solar/Wind Harmer
5.544
270024AE2-089 GEN
Solar/Wind Harmer
6.037
972207SS24-0001
Solar/Wind Harmer
28.39
274773LINCOLN ;4U
Adder
7.985
274774LINCOLN ;5U
Adder
7.985
253316AC1-085 GEN3
Solar/Wind Harmer
10.757
946171AF1-282 GEN
Solar/Wind Harmer
12.848
970825AG2-519 GEN
Solar/Wind Harmer
2.692
270005AE1-210 C O1
Solar/Wind Harmer
7.007
274723RIVER EC ;12
Adder
22.949
274751CRETE EC ;1U
Adder
6.261
274754CRETE EC ;4U
Adder
6.261
270216AD2-079_GEN
Solar/Wind Harmer
0.774
274812UNIV PK N;8U
Adder
6.402
24639705ELKHART HY
Adder
0.196
274802UNIV PARK;5U
Adder
7.439
274676JOLIET 29;8U
Adder
39.004
274732ELWOOD EC;7P
Adder
20.89
274674JOLIET 9 ;6U
Adder
19.566
274745AC1-111 GEN9
Adder
7.074
274682WAUKEGAN ;7U
Adder
22.627
274828WAUKEGAN ;BP
Adder
13.9
274822ROCKFORD ;11
Adder
24.426
24728605AND G2
Adder
4.773
25194608D.CRK4
Adder
2.045
274761LEE CO EC;2U
Adder
11.506
274766LEE CO EC;7U
Adder
11.371
25196808ZIMRHP
Adder
93.121
25196008MFTGT1
Adder
1.698
970091AG2-072 GEN
Adder
53.308
254303AC2-168 GEN
Solar/Wind Helper
0.198
241966AE1-183 GEN
Solar/Wind Helper
0.312
961971AG1-040 GEN
Solar/Wind Helper
0.519
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
270156DARBY CT1
50/50
0.842
270157DARBY CT2
50/50
0.84
270159DARBY CT4
50/50
0.828
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.272
270459AD2-067 GEN
Solar/Wind Harmer
15.126
961821AG1-024 GEN
Solar/Wind Harmer
15.357
241955AC1-078 GEN
Solar/Wind Harmer
12.399
945631AF1-228 GEN
Solar/Wind Harmer
7.612
241973AD2-163_GEN1
Solar/Wind Harmer
3.215
241974AD2-163_GEN2
Solar/Wind Harmer
3.215
943861AF1-054 GEN
Solar/Wind Harmer
6.142
943851AF1-053 GEN
Solar/Wind Harmer
2.968
253338AC1-165 GEN
Solar/Wind Harmer
1.661
253343AC1-166 GEN
Solar/Wind Harmer
1.661
270223U2-072_GEN1
Solar/Wind Harmer
2.981
270224U2-072_GEN2
Solar/Wind Harmer
2.981
270227U2-072_GEN3
Solar/Wind Harmer
2.981
270228U2-072_GEN4
Solar/Wind Harmer
2.981
270231U2-072_GEN5
Solar/Wind Harmer
2.981
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
10.241
270302AB2-170 GEN
Solar/Wind Harmer
12.138
241972AD1-140 GEN
Solar/Wind Harmer
6.475
253372AE2-315 SEC3
Adder
2.536
253372AE2-315 SEC3
Adder
2.536
270071AF1-092 GEN
Solar/Wind Harmer
20.008
25306009OHH W.
Adder
3.833
270340AC2-060 GEN
Solar/Wind Harmer
4.004
270263AC1-001 GEN
Solar/Wind Harmer
1.38
24729505KEY G4
Adder
8.547
970289AG2-191 GEN
Solar/Wind Harmer
2.486
958711AF2-162 GEN
Solar/Wind Harmer
1.322
959141AF2-205 GEN
Solar/Wind Harmer
7.898
958391AF2-133 GEN
Solar/Wind Harmer
11.843
959331AF2-224 GEN
Solar/Wind Harmer
13.038
946581AF1-322 GEN
Solar/Wind Harmer
13.327
24691005MDL-2G C
Solar/Wind Harmer
4.816
253406AD2-031_GEN
Solar/Wind Harmer
1.657
945581AF1-223 GEN
Solar/Wind Harmer
5.884
960681AF2-359 GEN
Solar/Wind Harmer
4.897
963791AG1-232 GEN
Solar/Wind Harmer
17.447
24386405FR-21G C
Solar/Wind Harmer
5.544
24387005FR-3G C
Solar/Wind Harmer
5.099
274775LINCOLN ;6U
Adder
7.985
274776LINCOLN ;7U
Adder
7.985
274777LINCOLN ;8U
Adder
7.985
961761AG1-017 GEN
Solar/Wind Harmer
0.55
270526AF1-158 GEN
Solar/Wind Harmer
5.829
964611AG1-324 GEN
Solar/Wind Harmer
5.011
253433AC1-085 GEN1
Solar/Wind Harmer
6.828
253432AC1-085 GEN2
Solar/Wind Harmer
0.344
247536S-71 GEN
Solar/Wind Harmer
5.197
247521TR3_G114
Solar/Wind Harmer
4.313
270191TR4_S_V150
Solar/Wind Harmer
3.848
965051AG1-369 GEN
Solar/Wind Harmer
6.408
270543AE2-219 C
Solar/Wind Harmer
12.834
970031AG2-029 GEN
Solar/Wind Harmer
32.072
971771AH1-392 GEN
Solar/Wind Harmer
11.543
971029AG2-637 GEN
Solar/Wind Harmer
19.236
965041AG1-368 GEN
Solar/Wind Harmer
12.788
963841AG1-237 GEN
Solar/Wind Harmer
13.967
972228AH1-698 GEN2
Adder
4.726
972227AH1-698 GEN1
Adder
3.328
972037AH1-567 GEN1
Adder
0.234
274827FISK ;RP
Adder
9.897
274800UNIV PARK;3U
Adder
7.435
274801UNIV PARK;4U
Adder
7.435
274687WILL CNTY;4U
Adder
35.54
274687WILL CNTY;4U
Adder
35.54
274675JOLIET 29;7U
Adder
39.004
274675JOLIET 29;7U
Adder
37.611
274728ELWOOD EC;5P
Adder
20.89
274731ELWOOD EC;2P
Adder
20.89
274733ELWOOD EC;3P
Adder
20.89
274735ELWOOD EC;4P
Adder
20.89
274744AC1-111 GEN8
Adder
7.074
274746AC1-111 G10
Adder
7.074
25196408WSDLE3
Adder
10.998
274823ROCKFORD ;21
Adder
24.249
972267AH1-718 GEN
Adder
5.132
25196108MFTGT2
Adder
1.871
25196108MFTGT2
Adder
1.738
241985AE1-237 GEN
Solar/Wind Helper
0.309
241982AE2-343 S C
Solar/Wind Helper
0.277
241997AF1-093 GEN
Solar/Wind Helper
0.312
23652301WDPWR_K20
Solar/Wind Helper
0.16
23750501ELLIOTTS
Solar/Wind Helper
0.695
203846AF2-130 C
Solar/Wind Helper
0.499
20089126CSLMN_L13
Solar/Wind Helper
0.614
20089226LOOKOUT
Solar/Wind Helper
0.612
20088926STNY CRK
Solar/Wind Helper
0.85
20094526CT_V3-030
Solar/Wind Helper
0.495
203955AF1-039 C O1
Solar/Wind Helper
0.381
203940AF1-140 C
Solar/Wind Helper
0.411
20088626ARWF_N39
Solar/Wind Helper
1.241
20334926Z1-069 C
Solar/Wind Helper
1.404
23750701CROSSCHOOL
Solar/Wind Helper
1.183
238118U2-030_1
Solar/Wind Helper
0.283
270051AF1-062 GEN
50/50
18.055
270475AD2-096_GEN
50/50
10.588
962771AG1-126 GEN
Solar/Wind Harmer
60.765
970153AG2-106 GEN
Solar/Wind Harmer
26.496
961921AG1-034 GEN
Solar/Wind Harmer
23.036
270284AF1-227 GEN1
Solar/Wind Harmer
9.61
270287AF1-227 GEN3
Solar/Wind Harmer
3.554
942051AE2-217 GEN
Solar/Wind Harmer
29.065
270518AE2-148 GEN
Solar/Wind Harmer
18.772
253325AC1-069 GEN
Solar/Wind Harmer
1.602
942871AE2-306 GEN
Solar/Wind Harmer
1.369
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
960801AF2-371 GEN
Solar/Wind Harmer
3.744
964871AG1-351 GEN
Solar/Wind Harmer
2.585
276820AF1-078_GEN
Solar/Wind Harmer
2.217
960071AF2-298 GEN
Solar/Wind Harmer
2.027
253303V4-073 C
Solar/Wind Harmer
0.155
253370AE2-315 SEC1
Adder
2.681
253371AE2-315 SEC2
Adder
2.536
944531AF1-118 GEN
Solar/Wind Harmer
46.245
270043AE2-236 GEN
Solar/Wind Harmer
7.237
247642Z2-115 C
Solar/Wind Harmer
0.084
971347AH1-153 GEN
Solar/Wind Harmer
6.568
965461AG1-414 GEN
Solar/Wind Harmer
2.967
970289AG2-191 GEN
Solar/Wind Harmer
1.004
253394AE2-221_GEN
Solar/Wind Harmer
5.932
964401AG1-302 GEN
Solar/Wind Harmer
11.837
965021AG1-366 GEN
Solar/Wind Harmer
3.032
24690905MDL-1G C
Solar/Wind Harmer
10.457
970781AG2-491 GEN
Solar/Wind Harmer
13.025
24386205FR-12G C
Solar/Wind Harmer
5.525
274772LINCOLN ;3U
Adder
7.985
24441505OLIV SLR
Solar/Wind Harmer
0.172
962031AG1-047 GEN
Solar/Wind Harmer
3.887
957741AF2-068 GEN
Solar/Wind Harmer
19.282
253317AC1-085 GEN4
Solar/Wind Harmer
10.757
946181AF1-283 GEN
Solar/Wind Harmer
16.703
946031AF1-268 GEN
Solar/Wind Harmer
10.649
970825AG2-519 GEN
Solar/Wind Harmer
7.228
270004AE1-209 GEN
Solar/Wind Harmer
7.007
270063AE2-323 C
Solar/Wind Harmer
2.817
274724RIVER EC ;11
Adder
22.681
972231SS25-0005
Solar/Wind Harmer
12.156
972181SS23-001
Solar/Wind Harmer
7.597
274752CRETE EC ;2U
Adder
6.261
274753CRETE EC ;3U
Adder
6.261
247643Z2-116 C
Solar/Wind Harmer
0.089
276164X3-005 C
Solar/Wind Harmer
0.899
274814UNIV PK N;0U
Adder
6.458
274807UNIV PK N;3U
Adder
6.444
274811UNIV PK N;7U
Adder
6.402
274803UNIV PARK;6U
Adder
7.439
274826FISK ;BP
Adder
13.965
972259AH1-714 GEN
Adder
24.332
972038AH1-567 GEN2
Adder
0.465
274676JOLIET 29;8U
Adder
37.611
274729ELWOOD EC;1P
Adder
20.89
274730ELWOOD EC;6P
Adder
20.89
274734ELWOOD EC;8P
Adder
20.89
274736ELWOOD EC;9P
Adder
20.89
274682WAUKEGAN ;7U
Adder
22.627
25196608WSDLE5
Adder
10.684
24728505AND G1
Adder
4.773
25194608D.CRK4
Adder
2.045
274760LEE CO EC;1U
Adder
11.506
274767LEE CO EC;8U
Adder
11.371
25196008MFTGT1
Adder
1.644
235058AG1-386 C
Solar/Wind Helper
0.575
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
962511AG1-100 GEN
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Helper
0.577
20092526R32
Solar/Wind Helper
1.211
964991AG1-363 GEN
Solar/Wind Helper
3.733
20303426NA_O38_P22
Solar/Wind Helper
1.018
23562501BACKB
Solar/Wind Helper
0.894
203993AD2-133_GEN1
Solar/Wind Helper
1.056
203854AF2-039 C
Solar/Wind Helper
0.327
20398826ARMNA MT
Solar/Wind Helper
1.512
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.261
274887GEN-1.85
Solar/Wind Harmer
0.448
276843GEN-1.7
Solar/Wind Harmer
0.048
20089026BF_G21_K23
Solar/Wind Helper
0.486
238185AF2-356 C
Solar/Wind Helper
2.181
964201AG1-281 GEN
Solar/Wind Helper
0.498
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.056
203952AE2-129 C
Solar/Wind Helper
0.488
203855AF2-088 C
Solar/Wind Helper
0.158
238126S14_GEN_1
Solar/Wind Helper
0.662
238120AE2-309 GEN
Solar/Wind Helper
0.417
23751101LEADS_P59
Solar/Wind Helper
1.833
270119AB2-067 GEN1
50/50
13.695
270120AB2-067 GEN2
50/50
13.695
270160DARBY CT5
50/50
0.825
270161DARBY CT6
50/50
0.814
270466AD2-091
50/50
8.429
25326109MON D
50/50
1.904
25326509SID D
50/50
1.897
270349AD2-093_GEN
Solar/Wind Harmer
6.609
270471AD2-092_GEN
Solar/Wind Harmer
6.609
946101AF1-275 GEN
Solar/Wind Harmer
2.662
270054AF2-122 C O1
Solar/Wind Harmer
5.631
253383AE2-342_GEN
Solar/Wind Harmer
1.446
942861AE2-305 GEN
Solar/Wind Harmer
12.443
938701AE1-092 GEN
Solar/Wind Harmer
30.075
270462AD2-086
Solar/Wind Harmer
10.083
270269AC2-059
Solar/Wind Harmer
13.072
253378AE2-206_GEN
Solar/Wind Harmer
4.99
25322209TAIT E
Adder
13.127
25322209TAIT E
Adder
12.832
253415AE1-040 GEN
Solar/Wind Harmer
1.513
253370AE2-315 SEC1
Adder
2.681
253349AC2-067 GEN
Solar/Wind Harmer
2.698
253400AC2-068 GEN
Solar/Wind Harmer
1.085
970349AG2-230 GEN
Solar/Wind Harmer
19.704
945421AF1-207 GEN
Solar/Wind Harmer
18.384
957841AF2-078 GEN
Solar/Wind Harmer
7.914
970291AG2-192 GEN
Solar/Wind Harmer
1.701
970291AG2-192 GEN
Solar/Wind Harmer
0.548
944541AF1-119 GEN
Solar/Wind Harmer
5.473
960971AF2-388 GEN
Solar/Wind Harmer
14.288
270535AF1-215 GEN1
Solar/Wind Harmer
5.912
270536AF1-215 GEN2
Solar/Wind Harmer
5.912
270180AB1-006 GEN1
Solar/Wind Harmer
9.367
24697605MDL-3G C
Solar/Wind Harmer
4.801
24755605MDL-5G
Solar/Wind Harmer
3.14
24697905MDL-4G C
Solar/Wind Harmer
2.989
270181AB1-006 GEN2
Solar/Wind Harmer
0.931
942221AE2-234 GEN
Solar/Wind Harmer
4.547
965681AG1-436 GEN
Solar/Wind Harmer
16.2
965791AG1-447 GEN
Solar/Wind Harmer
8.288
270031AE2-169
Solar/Wind Harmer
10.515
270599AE1-208 GEN
Solar/Wind Harmer
10.515
24387305FR-4G C
Solar/Wind Harmer
6.548
966841AG1-555 GEN
Solar/Wind Harmer
3.237
274770LINCOLN ;1U
Adder
7.985
274771LINCOLN ;2U
Adder
7.985
24725505WLD G2 C
Solar/Wind Harmer
5.118
24699105WLD G1 C
Solar/Wind Harmer
5.058
270201AC2-176 GEN
Solar/Wind Harmer
6.607
247621Y3-024
Adder
0.31
964611AG1-324 GEN
Solar/Wind Harmer
0.672
270246TR4_N_V150
Solar/Wind Harmer
1.091
270247TR4_N_V136
Solar/Wind Harmer
1.091
970883AG2-550 GEN
Solar/Wind Harmer
12.834
970885AG2-551 GEN
Solar/Wind Harmer
2.985
270383AD1-128 GEN
Solar/Wind Harmer
7.805
274805UNIV PK N;1U
Adder
6.416
274808UNIV PK N;4U
Adder
6.374
274888KELLY CRK;1U
Solar/Wind Harmer
7.53
247620Y3-023
Adder
0.587
274674JOLIET 9 ;6U
Adder
19.566
274695ROCKY RD ;2P
Adder
14.027
274693ROCKY RD ;1P
Adder
13.889
274697ROCKY RD ;3P
Adder
3.811
274696ROCKY RD ;4P
Adder
14.358
274683WAUKEGAN ;8U
Adder
26.517
274683WAUKEGAN ;8U
Adder
22.353
25194408D.CRK1
Adder
9.405
25194508D.CRK3
Adder
1.758
972235AH1-702 GEN1
Adder
3.134
972236AH1-702 GEN2
Adder
2.725
274764LEE CO EC;5U
Adder
11.533
274765LEE CO EC;6U
Adder
11.533
274762LEE CO EC;3U
Adder
11.506
274763LEE CO EC;4U
Adder
11.398
254304AE2-114 C
Solar/Wind Helper
0.274
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
241801AE1-079 GEN
Solar/Wind Helper
0.309
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
946071AF1-272 GEN
Solar/Wind Helper
2.881
203835AF1-098 GEN
Solar/Wind Helper
2.053
946381AF1-302 GEN
Solar/Wind Helper
0.237
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
203818AF1-086 GEN
Solar/Wind Helper
1.773
23585401KL_K28_T16
Solar/Wind Helper
1.269
203853AF1-134 C O1
Solar/Wind Helper
0.498
203804AE2-113_GEN
Solar/Wind Helper
1.841
23751201ROTHROCK
Solar/Wind Helper
0.734
203961AE2-224 GEN
Solar/Wind Helper
2.481
940863AE2-074 GEN
Solar/Wind Helper
0.48
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.674
203946AE2-131 C
Solar/Wind Helper
0.488
238117U2-030
Solar/Wind Helper
0.283
235531U2-073 GEN
Solar/Wind Helper
2.674
LAGNLTFEXP_LAGN->PJM
CLTF
17.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.12
TVALTFEXP_TVA->PJM
CLTF
8.468
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.733
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.797
MECLTFEXP_MEC->PJM
CLTF
19.508
SIGELTFEXP_SIGE->PJM
CLTF
0.599
CPLELTFEXP_CPLE->PJM
CLTF
2.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.179
NYPJM->LTFIMP_NY
CLTF
5.166
LGEELTFEXP_LGEE->PJM
CLTF
7.844
WECLTFEXP_WEC->PJM
CLTF
4.747
AG2-052LTFEXP_AG2-052->PJM
LTF
0.298
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.67 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4418.17
MW Contribution:
12.82
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5011.7
MW Contribution:
12.33
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
0.841
270157DARBY CT2
50/50
0.839
270159DARBY CT4
50/50
0.828
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.265
270459AD2-067 GEN
Solar/Wind Harmer
15.114
961821AG1-024 GEN
Solar/Wind Harmer
15.345
241955AC1-078 GEN
Solar/Wind Harmer
12.389
945631AF1-228 GEN
Solar/Wind Harmer
7.606
241973AD2-163_GEN1
Solar/Wind Harmer
3.212
241974AD2-163_GEN2
Solar/Wind Harmer
3.212
943861AF1-054 GEN
Solar/Wind Harmer
6.137
943851AF1-053 GEN
Solar/Wind Harmer
2.966
253338AC1-165 GEN
Solar/Wind Harmer
1.66
253343AC1-166 GEN
Solar/Wind Harmer
1.66
270223U2-072_GEN1
Solar/Wind Harmer
2.978
270224U2-072_GEN2
Solar/Wind Harmer
2.978
270227U2-072_GEN3
Solar/Wind Harmer
2.978
270228U2-072_GEN4
Solar/Wind Harmer
2.978
270231U2-072_GEN5
Solar/Wind Harmer
2.978
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
10.231
270302AB2-170 GEN
Solar/Wind Harmer
12.128
241972AD1-140 GEN
Solar/Wind Harmer
6.47
253372AE2-315 SEC3
Adder
2.534
253372AE2-315 SEC3
Adder
2.534
270071AF1-092 GEN
Solar/Wind Harmer
19.99
25306009OHH W.
Adder
3.829
270340AC2-060 GEN
Solar/Wind Harmer
4
270263AC1-001 GEN
Solar/Wind Harmer
1.378
24729505KEY G4
Adder
8.54
970289AG2-191 GEN
Solar/Wind Harmer
2.484
958711AF2-162 GEN
Solar/Wind Harmer
1.321
959141AF2-205 GEN
Solar/Wind Harmer
7.891
958391AF2-133 GEN
Solar/Wind Harmer
11.833
959331AF2-224 GEN
Solar/Wind Harmer
13.026
946581AF1-322 GEN
Solar/Wind Harmer
13.316
24691005MDL-2G C
Solar/Wind Harmer
4.812
253406AD2-031_GEN
Solar/Wind Harmer
1.656
945581AF1-223 GEN
Solar/Wind Harmer
5.879
960681AF2-359 GEN
Solar/Wind Harmer
4.892
963791AG1-232 GEN
Solar/Wind Harmer
17.431
24386405FR-21G C
Solar/Wind Harmer
5.54
24387005FR-3G C
Solar/Wind Harmer
5.095
274775LINCOLN ;6U
Adder
7.978
274776LINCOLN ;7U
Adder
7.978
274777LINCOLN ;8U
Adder
7.978
961761AG1-017 GEN
Solar/Wind Harmer
0.55
270526AF1-158 GEN
Solar/Wind Harmer
5.824
964611AG1-324 GEN
Solar/Wind Harmer
5.007
253433AC1-085 GEN1
Solar/Wind Harmer
6.821
253432AC1-085 GEN2
Solar/Wind Harmer
0.343
247536S-71 GEN
Solar/Wind Harmer
5.193
247521TR3_G114
Solar/Wind Harmer
4.309
270191TR4_S_V150
Solar/Wind Harmer
3.845
965051AG1-369 GEN
Solar/Wind Harmer
6.402
270543AE2-219 C
Solar/Wind Harmer
12.822
970031AG2-029 GEN
Solar/Wind Harmer
32.043
971771AH1-392 GEN
Solar/Wind Harmer
11.533
971029AG2-637 GEN
Solar/Wind Harmer
19.218
965041AG1-368 GEN
Solar/Wind Harmer
12.776
963841AG1-237 GEN
Solar/Wind Harmer
13.955
972228AH1-698 GEN2
Adder
4.722
972227AH1-698 GEN1
Adder
3.325
972037AH1-567 GEN1
Adder
0.233
274827FISK ;RP
Adder
9.888
274800UNIV PARK;3U
Adder
7.429
274801UNIV PARK;4U
Adder
7.429
274687WILL CNTY;4U
Adder
35.509
274687WILL CNTY;4U
Adder
35.509
274675JOLIET 29;7U
Adder
38.97
274675JOLIET 29;7U
Adder
37.578
274728ELWOOD EC;5P
Adder
20.872
274731ELWOOD EC;2P
Adder
20.872
274733ELWOOD EC;3P
Adder
20.872
274735ELWOOD EC;4P
Adder
20.872
274744AC1-111 GEN8
Adder
7.068
274746AC1-111 G10
Adder
7.068
25196408WSDLE3
Adder
10.988
274823ROCKFORD ;21
Adder
24.227
972267AH1-718 GEN
Adder
5.127
25196108MFTGT2
Adder
1.87
25196108MFTGT2
Adder
1.736
241985AE1-237 GEN
Solar/Wind Helper
0.309
241982AE2-343 S C
Solar/Wind Helper
0.277
241997AF1-093 GEN
Solar/Wind Helper
0.312
23652301WDPWR_K20
Solar/Wind Helper
0.16
270051AF1-062 GEN
50/50
18.043
270475AD2-096_GEN
50/50
10.581
962771AG1-126 GEN
Solar/Wind Harmer
60.725
970153AG2-106 GEN
Solar/Wind Harmer
26.479
961921AG1-034 GEN
Solar/Wind Harmer
23.018
270284AF1-227 GEN1
Solar/Wind Harmer
9.603
270287AF1-227 GEN3
Solar/Wind Harmer
3.552
942051AE2-217 GEN
Solar/Wind Harmer
29.041
270518AE2-148 GEN
Solar/Wind Harmer
18.756
253325AC1-069 GEN
Solar/Wind Harmer
1.601
942871AE2-306 GEN
Solar/Wind Harmer
1.368
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
960801AF2-371 GEN
Solar/Wind Harmer
3.74
964871AG1-351 GEN
Solar/Wind Harmer
2.583
276820AF1-078_GEN
Solar/Wind Harmer
2.215
960071AF2-298 GEN
Solar/Wind Harmer
2.025
253303V4-073 C
Solar/Wind Harmer
0.155
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
944531AF1-118 GEN
Solar/Wind Harmer
46.204
270043AE2-236 GEN
Solar/Wind Harmer
7.23
247642Z2-115 C
Solar/Wind Harmer
0.084
971347AH1-153 GEN
Solar/Wind Harmer
6.562
965461AG1-414 GEN
Solar/Wind Harmer
2.965
970289AG2-191 GEN
Solar/Wind Harmer
1.003
253394AE2-221_GEN
Solar/Wind Harmer
5.926
964401AG1-302 GEN
Solar/Wind Harmer
11.826
965021AG1-366 GEN
Solar/Wind Harmer
3.029
24690905MDL-1G C
Solar/Wind Harmer
10.447
970781AG2-491 GEN
Solar/Wind Harmer
13.014
24386205FR-12G C
Solar/Wind Harmer
5.52
274772LINCOLN ;3U
Adder
7.978
24441505OLIV SLR
Solar/Wind Harmer
0.172
962031AG1-047 GEN
Solar/Wind Harmer
3.883
957741AF2-068 GEN
Solar/Wind Harmer
19.265
253317AC1-085 GEN4
Solar/Wind Harmer
10.746
946181AF1-283 GEN
Solar/Wind Harmer
16.687
270166AC1-044 GEN3
50/50
13.691
962761AG1-125 GEN
Solar/Wind Harmer
60.725
970149AG2-104 GEN
Solar/Wind Harmer
37.498
970155AG2-107 GEN
Solar/Wind Harmer
26.479
270520AE2-214 GEN
Solar/Wind Harmer
10.641
270286AF1-227 GEN2
Solar/Wind Harmer
3.552
253333AC1-068 GEN
Solar/Wind Harmer
1.601
270391AF1-285 GEN3
Solar/Wind Harmer
1.824
270578AF1-285 GEN2
Solar/Wind Harmer
1.824
270317AD1-130_GEN
Solar/Wind Harmer
4.636
270485AE1-090_GEN
Solar/Wind Harmer
0.876
270273AD2-016 GEN
Solar/Wind Harmer
3.724
25326309TAIT D
Adder
1.474
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
253398AE2-221_GEN2
Solar/Wind Harmer
5.926
965651AG1-433 GEN
Solar/Wind Harmer
7.138
940581AE2-045 GEN
Solar/Wind Harmer
13.318
971605AH1-302 GEN
Solar/Wind Harmer
11.387
971995AH1-542 GEN
Solar/Wind Harmer
14.349
964861AG1-349 GEN
Solar/Wind Harmer
10.25
971917AH1-482 GEN
Solar/Wind Harmer
11.826
958381AF2-132 GEN
Solar/Wind Harmer
11.826
958861AF2-177 GEN
Solar/Wind Harmer
14.238
965011AG1-365 GEN
Solar/Wind Harmer
13.026
270055AF2-134 C O1
Solar/Wind Harmer
3.938
24791305MDL-5G
Solar/Wind Harmer
3.137
270594AE1-207 GEN
Solar/Wind Harmer
17.675
270032AE2-172
Solar/Wind Harmer
6.053
970373AG2-245 GEN
Solar/Wind Harmer
27.321
945371AF1-202 GEN
Solar/Wind Harmer
9.043
276903AD2-071 C
Solar/Wind Harmer
12.921
24385905FR-11G C
Solar/Wind Harmer
10.705
24386605FR-22G C
Solar/Wind Harmer
5.54
270024AE2-089 GEN
Solar/Wind Harmer
6.032
972207SS24-0001
Solar/Wind Harmer
28.366
274773LINCOLN ;4U
Adder
7.978
274774LINCOLN ;5U
Adder
7.978
253316AC1-085 GEN3
Solar/Wind Harmer
10.746
946171AF1-282 GEN
Solar/Wind Harmer
12.836
970825AG2-519 GEN
Solar/Wind Harmer
2.69
270005AE1-210 C O1
Solar/Wind Harmer
7.001
274723RIVER EC ;12
Adder
22.929
274751CRETE EC ;1U
Adder
6.255
274754CRETE EC ;4U
Adder
6.255
270216AD2-079_GEN
Solar/Wind Harmer
0.773
274812UNIV PK N;8U
Adder
6.396
24639705ELKHART HY
Adder
0.196
274802UNIV PARK;5U
Adder
7.433
274676JOLIET 29;8U
Adder
38.97
274732ELWOOD EC;7P
Adder
20.872
274674JOLIET 9 ;6U
Adder
19.549
274745AC1-111 GEN9
Adder
7.068
274682WAUKEGAN ;7U
Adder
22.607
274828WAUKEGAN ;BP
Adder
13.888
274822ROCKFORD ;11
Adder
24.404
24728605AND G2
Adder
4.768
25194608D.CRK4
Adder
2.043
274761LEE CO EC;2U
Adder
11.496
274766LEE CO EC;7U
Adder
11.361
25196808ZIMRHP
Adder
93.029
25196008MFTGT1
Adder
1.696
970091AG2-072 GEN
Adder
53.258
254303AC2-168 GEN
Solar/Wind Helper
0.198
241966AE1-183 GEN
Solar/Wind Helper
0.312
961971AG1-040 GEN
Solar/Wind Helper
0.519
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.485
964201AG1-281 GEN
Solar/Wind Helper
0.498
238185AF2-356 C
Solar/Wind Helper
2.178
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.055
946031AF1-268 GEN
Solar/Wind Harmer
10.639
970825AG2-519 GEN
Solar/Wind Harmer
7.221
270004AE1-209 GEN
Solar/Wind Harmer
7.001
270063AE2-323 C
Solar/Wind Harmer
2.815
274724RIVER EC ;11
Adder
22.661
972231SS25-0005
Solar/Wind Harmer
12.145
972181SS23-001
Solar/Wind Harmer
7.591
274752CRETE EC ;2U
Adder
6.255
274753CRETE EC ;3U
Adder
6.255
247643Z2-116 C
Solar/Wind Harmer
0.089
276164X3-005 C
Solar/Wind Harmer
0.898
274814UNIV PK N;0U
Adder
6.452
274807UNIV PK N;3U
Adder
6.438
274811UNIV PK N;7U
Adder
6.396
274803UNIV PARK;6U
Adder
7.433
274826FISK ;BP
Adder
13.952
972259AH1-714 GEN
Adder
24.311
972038AH1-567 GEN2
Adder
0.465
23750501ELLIOTTS
Solar/Wind Helper
0.695
203846AF2-130 C
Solar/Wind Helper
0.498
20089126CSLMN_L13
Solar/Wind Helper
0.613
20089226LOOKOUT
Solar/Wind Helper
0.611
20088926STNY CRK
Solar/Wind Helper
0.849
20094526CT_V3-030
Solar/Wind Helper
0.494
203955AF1-039 C O1
Solar/Wind Helper
0.38
203940AF1-140 C
Solar/Wind Helper
0.411
20088626ARWF_N39
Solar/Wind Helper
1.24
20334926Z1-069 C
Solar/Wind Helper
1.403
23750701CROSSCHOOL
Solar/Wind Helper
1.182
238118U2-030_1
Solar/Wind Helper
0.283
203952AE2-129 C
Solar/Wind Helper
0.488
203855AF2-088 C
Solar/Wind Helper
0.158
238126S14_GEN_1
Solar/Wind Helper
0.662
238120AE2-309 GEN
Solar/Wind Helper
0.416
23751101LEADS_P59
Solar/Wind Helper
1.832
274676JOLIET 29;8U
Adder
37.578
274729ELWOOD EC;1P
Adder
20.872
274730ELWOOD EC;6P
Adder
20.872
274734ELWOOD EC;8P
Adder
20.872
274736ELWOOD EC;9P
Adder
20.872
274682WAUKEGAN ;7U
Adder
22.607
25196608WSDLE5
Adder
10.674
24728505AND G1
Adder
4.768
25194608D.CRK4
Adder
2.043
274760LEE CO EC;1U
Adder
11.496
274767LEE CO EC;8U
Adder
11.361
25196008MFTGT1
Adder
1.643
235058AG1-386 C
Solar/Wind Helper
0.575
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
962511AG1-100 GEN
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Helper
0.576
20092526R32
Solar/Wind Helper
1.21
964991AG1-363 GEN
Solar/Wind Helper
3.728
20303426NA_O38_P22
Solar/Wind Helper
1.017
23562501BACKB
Solar/Wind Helper
0.893
203993AD2-133_GEN1
Solar/Wind Helper
1.055
203854AF2-039 C
Solar/Wind Helper
0.327
20398826ARMNA MT
Solar/Wind Helper
1.511
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.259
274887GEN-1.85
Solar/Wind Harmer
0.448
276843GEN-1.7
Solar/Wind Harmer
0.048
270119AB2-067 GEN1
50/50
13.691
270120AB2-067 GEN2
50/50
13.691
270160DARBY CT5
50/50
0.825
270161DARBY CT6
50/50
0.813
270466AD2-091
50/50
8.422
25326109MON D
50/50
1.903
25326509SID D
50/50
1.895
270349AD2-093_GEN
Solar/Wind Harmer
6.604
270471AD2-092_GEN
Solar/Wind Harmer
6.604
946101AF1-275 GEN
Solar/Wind Harmer
2.66
270054AF2-122 C O1
Solar/Wind Harmer
5.626
253383AE2-342_GEN
Solar/Wind Harmer
1.445
942861AE2-305 GEN
Solar/Wind Harmer
12.433
938701AE1-092 GEN
Solar/Wind Harmer
30.048
270462AD2-086
Solar/Wind Harmer
10.074
270269AC2-059
Solar/Wind Harmer
13.059
253378AE2-206_GEN
Solar/Wind Harmer
4.985
25322209TAIT E
Adder
13.115
25322209TAIT E
Adder
12.82
253415AE1-040 GEN
Solar/Wind Harmer
1.511
253370AE2-315 SEC1
Adder
2.679
253349AC2-067 GEN
Solar/Wind Harmer
2.695
253400AC2-068 GEN
Solar/Wind Harmer
1.084
970349AG2-230 GEN
Solar/Wind Harmer
19.687
945421AF1-207 GEN
Solar/Wind Harmer
18.368
957841AF2-078 GEN
Solar/Wind Harmer
7.907
970291AG2-192 GEN
Solar/Wind Harmer
1.7
970291AG2-192 GEN
Solar/Wind Harmer
0.547
944541AF1-119 GEN
Solar/Wind Harmer
5.469
960971AF2-388 GEN
Solar/Wind Harmer
14.275
270535AF1-215 GEN1
Solar/Wind Harmer
5.907
270536AF1-215 GEN2
Solar/Wind Harmer
5.907
270180AB1-006 GEN1
Solar/Wind Harmer
9.359
24697605MDL-3G C
Solar/Wind Harmer
4.797
24755605MDL-5G
Solar/Wind Harmer
3.137
24697905MDL-4G C
Solar/Wind Harmer
2.986
270181AB1-006 GEN2
Solar/Wind Harmer
0.931
942221AE2-234 GEN
Solar/Wind Harmer
4.543
965681AG1-436 GEN
Solar/Wind Harmer
16.186
965791AG1-447 GEN
Solar/Wind Harmer
8.281
270031AE2-169
Solar/Wind Harmer
10.505
270599AE1-208 GEN
Solar/Wind Harmer
10.505
24387305FR-4G C
Solar/Wind Harmer
6.542
966841AG1-555 GEN
Solar/Wind Harmer
3.234
274770LINCOLN ;1U
Adder
7.978
274771LINCOLN ;2U
Adder
7.978
24725505WLD G2 C
Solar/Wind Harmer
5.114
24699105WLD G1 C
Solar/Wind Harmer
5.054
270201AC2-176 GEN
Solar/Wind Harmer
6.601
247621Y3-024
Adder
0.31
964611AG1-324 GEN
Solar/Wind Harmer
0.672
270246TR4_N_V150
Solar/Wind Harmer
1.09
270247TR4_N_V136
Solar/Wind Harmer
1.09
970883AG2-550 GEN
Solar/Wind Harmer
12.822
970885AG2-551 GEN
Solar/Wind Harmer
2.982
270383AD1-128 GEN
Solar/Wind Harmer
7.798
274805UNIV PK N;1U
Adder
6.41
274808UNIV PK N;4U
Adder
6.368
274888KELLY CRK;1U
Solar/Wind Harmer
7.524
247620Y3-023
Adder
0.586
274674JOLIET 9 ;6U
Adder
19.549
274695ROCKY RD ;2P
Adder
14.015
274693ROCKY RD ;1P
Adder
13.877
274697ROCKY RD ;3P
Adder
3.807
274696ROCKY RD ;4P
Adder
14.346
274683WAUKEGAN ;8U
Adder
26.494
274683WAUKEGAN ;8U
Adder
22.333
25194408D.CRK1
Adder
9.396
25194508D.CRK3
Adder
1.757
972235AH1-702 GEN1
Adder
3.131
972236AH1-702 GEN2
Adder
2.723
274764LEE CO EC;5U
Adder
11.523
274765LEE CO EC;6U
Adder
11.523
274762LEE CO EC;3U
Adder
11.496
274763LEE CO EC;4U
Adder
11.388
254304AE2-114 C
Solar/Wind Helper
0.274
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
241801AE1-079 GEN
Solar/Wind Helper
0.309
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
946071AF1-272 GEN
Solar/Wind Helper
2.879
203835AF1-098 GEN
Solar/Wind Helper
2.053
946381AF1-302 GEN
Solar/Wind Helper
0.237
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
203818AF1-086 GEN
Solar/Wind Helper
1.772
23585401KL_K28_T16
Solar/Wind Helper
1.267
203853AF1-134 C O1
Solar/Wind Helper
0.497
203804AE2-113_GEN
Solar/Wind Helper
1.84
23751201ROTHROCK
Solar/Wind Helper
0.733
203961AE2-224 GEN
Solar/Wind Helper
2.479
940863AE2-074 GEN
Solar/Wind Helper
0.479
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.672
203946AE2-131 C
Solar/Wind Helper
0.488
238117U2-030
Solar/Wind Helper
0.283
235531U2-073 GEN
Solar/Wind Helper
2.67
LAGNLTFEXP_LAGN->PJM
CLTF
17.61
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.111
TVALTFEXP_TVA->PJM
CLTF
8.46
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.765
MECLTFEXP_MEC->PJM
CLTF
19.491
SIGELTFEXP_SIGE->PJM
CLTF
0.599
CPLELTFEXP_CPLE->PJM
CLTF
2.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.056
NYPJM->LTFIMP_NY
CLTF
5.162
LGEELTFEXP_LGEE->PJM
CLTF
7.836
WECLTFEXP_WEC->PJM
CLTF
4.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.297
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4342.78
MW Contribution:
8.95
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.43 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4946.71
MW Contribution:
8.6
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
0.841
270157DARBY CT2
50/50
0.839
270159DARBY CT4
50/50
0.828
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.265
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
7.494
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
4.282
943851AF1-053 GEN
Solar/Wind Harmer
2.966
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
4.521
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.422
241972AD1-140 GEN
Solar/Wind Harmer
1.102
253372AE2-315 SEC3
Adder
2.534
253372AE2-315 SEC3
Adder
2.534
270071AF1-092 GEN
Solar/Wind Harmer
17.821
25306009OHH W.
Adder
3.829
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.92
24729505KEY G4
Adder
8.54
270166AC1-044 GEN3
50/50
13.691
962761AG1-125 GEN
Solar/Wind Harmer
51.21
970149AG2-104 GEN
Solar/Wind Harmer
27.654
970155AG2-107 GEN
Solar/Wind Harmer
32.701
270520AE2-214 GEN
Solar/Wind Harmer
0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
270273AD2-016 GEN
Solar/Wind Harmer
1.001
25326309TAIT D
Adder
1.474
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.673
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.387
971995AH1-542 GEN
Solar/Wind Harmer
3.337
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.826
958381AF2-132 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
9.088
270055AF2-134 C O1
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
10.169
270032AE2-172
Solar/Wind Harmer
6.053
970373AG2-245 GEN
Solar/Wind Harmer
19.061
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
10.066
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
10.86
274774LINCOLN ;5U
Adder
10.86
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.955
970825AG2-519 GEN
Solar/Wind Harmer
3.175
270005AE1-210 C O1
Solar/Wind Harmer
1.936
274723RIVER EC ;12
Adder
22.929
274751CRETE EC ;1U
Adder
10.545
274754CRETE EC ;4U
Adder
10.545
274812UNIV PK N;8U
Adder
6.396
24639705ELKHART HY
Adder
0.196
965421AG1-410 GEN
Solar/Wind Harmer
26.684
274802UNIV PARK;5U
Adder
7.433
941551AE2-152 GEN
Solar/Wind Harmer
0.001
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.512
246936BC-WTG1
Solar/Wind Harmer
0.358
270489AE1-102 GEN1
Solar/Wind Harmer
1.154
274676JOLIET 29;8U
Adder
38.97
274732ELWOOD EC;7P
Adder
20.872
274674JOLIET 9 ;6U
Adder
19.549
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
20.916
957891AF2-083 GEN
Solar/Wind Harmer
14.717
274745AC1-111 GEN9
Adder
7.068
945111AF1-176 GEN
Solar/Wind Harmer
15.739
939401AE1-172 GEN
Solar/Wind Harmer
6.59
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.43
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.607
274828WAUKEGAN ;BP
Adder
13.888
276805AD2-038 GEN
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
1.548
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.573
971997AH1-543 GEN
Solar/Wind Harmer
4.591
276882AE2-255 GEN
Solar/Wind Harmer
1.021
962781AG1-127 GEN
Solar/Wind Harmer
8.326
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
26.068
959081AF2-199 GEN
Solar/Wind Harmer
8.689
971067AG2-660 GEN
Solar/Wind Harmer
2.896
970569AG2-363 GEN
Solar/Wind Harmer
26.052
274822ROCKFORD ;11
Adder
24.404
24728605AND G2
Adder
4.768
25194608D.CRK4
Adder
2.043
252516AE2-318_GEN
Solar/Wind Harmer
9.707
276655WTG1_EQ
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.733
971611AH1-305 GEN
Solar/Wind Harmer
5.423
959141AF2-205 GEN
Solar/Wind Harmer
0.001
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
6.362
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.671
945581AF1-223 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963791AG1-232 GEN
Solar/Wind Harmer
12.161
971609AH1-304 GEN
Solar/Wind Harmer
1.469
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
10.86
274776LINCOLN ;7U
Adder
10.86
274777LINCOLN ;8U
Adder
10.86
270526AF1-158 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
3.493
247536S-71 GEN
Solar/Wind Harmer
0.358
247521TR3_G114
Solar/Wind Harmer
0.324
965051AG1-369 GEN
Solar/Wind Harmer
4.466
270543AE2-219 C
Solar/Wind Harmer
6.262
970031AG2-029 GEN
Solar/Wind Harmer
4.844
971771AH1-392 GEN
Solar/Wind Harmer
8.94
971029AG2-637 GEN
Solar/Wind Harmer
13.408
965041AG1-368 GEN
Solar/Wind Harmer
8.914
963841AG1-237 GEN
Solar/Wind Harmer
3.86
960591AF2-350 GEN
Solar/Wind Harmer
8.895
972228AH1-698 GEN2
Adder
4.722
972227AH1-698 GEN1
Adder
3.325
972037AH1-567 GEN1
Adder
0.233
274827FISK ;RP
Adder
9.888
274800UNIV PARK;3U
Adder
7.429
274801UNIV PARK;4U
Adder
7.429
270051AF1-062 GEN
50/50
18.043
270475AD2-096_GEN
50/50
10.581
962771AG1-126 GEN
Solar/Wind Harmer
51.21
970153AG2-106 GEN
Solar/Wind Harmer
32.701
961921AG1-034 GEN
Solar/Wind Harmer
11.241
270284AF1-227 GEN1
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Harmer
20.261
270518AE2-148 GEN
Solar/Wind Harmer
0.888
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
970191AG2-125 GEN
Solar/Wind Harmer
2.379
944531AF1-118 GEN
Solar/Wind Harmer
41.277
270043AE2-236 GEN
Solar/Wind Harmer
5.885
247642Z2-115 C
Solar/Wind Harmer
0.004
971347AH1-153 GEN
Solar/Wind Harmer
4.578
970289AG2-191 GEN
Solar/Wind Harmer
1.003
253394AE2-221_GEN
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
3.029
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.079
24386205FR-12G C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
10.86
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.124
274687WILL CNTY;4U
Adder
35.509
274687WILL CNTY;4U
Adder
35.509
274675JOLIET 29;7U
Adder
38.97
274675JOLIET 29;7U
Adder
37.578
274728ELWOOD EC;5P
Adder
20.872
274731ELWOOD EC;2P
Adder
20.872
274733ELWOOD EC;3P
Adder
20.872
274735ELWOOD EC;4P
Adder
20.872
970833AG2-524 GEN
Solar/Wind Harmer
9.741
970833AG2-524 GEN
Solar/Wind Harmer
6.494
274744AC1-111 GEN8
Adder
7.068
274746AC1-111 G10
Adder
7.068
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.922
270356AE2-297 GEN
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
8.736
971675AH1-338 GEN
Solar/Wind Harmer
3.397
276861AD2-134 GEN
Solar/Wind Harmer
0.155
276863AD2-134 GEN
Solar/Wind Harmer
0.155
971411AH1-196 GEN
Solar/Wind Harmer
13.063
25196408WSDLE3
Adder
10.988
971171AH1-044 GEN
Solar/Wind Harmer
17.379
926823AC1-168 GEN
Solar/Wind Harmer
1.477
270007AE1-245 C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
24.227
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.098
274856ECOGROVE ;U1
Solar/Wind Harmer
0.202
971681AH1-341 GEN
Solar/Wind Harmer
13.904
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276741O09 GEN1
Solar/Wind Harmer
0.303
972267AH1-718 GEN
Adder
5.127
276668AB2-070 GEN1
Solar/Wind Harmer
0.334
276848AB2-070 GEN3
Solar/Wind Harmer
0.333
276849AB2-070 GEN2
Solar/Wind Harmer
0.334
25196108MFTGT2
Adder
1.87
25196108MFTGT2
Adder
1.736
946321AF1-296 GEN
Solar/Wind Harmer
4.758
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
241985AE1-237 GEN
Solar/Wind Helper
0.309
241982AE2-343 S C
Solar/Wind Helper
0.277
241997AF1-093 GEN
Solar/Wind Helper
0.312
23652301WDPWR_K20
Solar/Wind Helper
0.16
23750501ELLIOTTS
Solar/Wind Helper
0.695
203846AF2-130 C
Solar/Wind Helper
0.498
20089126CSLMN_L13
Solar/Wind Helper
0.613
20089226LOOKOUT
Solar/Wind Helper
0.611
20088926STNY CRK
Solar/Wind Helper
0.849
20094526CT_V3-030
Solar/Wind Helper
0.494
203955AF1-039 C O1
Solar/Wind Helper
0.38
203940AF1-140 C
Solar/Wind Helper
0.411
20088626ARWF_N39
Solar/Wind Helper
1.24
20334926Z1-069 C
Solar/Wind Helper
1.403
23750701CROSSCHOOL
Solar/Wind Helper
1.182
238118U2-030_1
Solar/Wind Helper
0.283
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.441
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.642
946031AF1-268 GEN
Solar/Wind Harmer
8.511
970825AG2-519 GEN
Solar/Wind Harmer
6.737
270004AE1-209 GEN
Solar/Wind Harmer
1.936
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
22.661
274752CRETE EC ;2U
Adder
10.545
274753CRETE EC ;3U
Adder
10.545
274814UNIV PK N;0U
Adder
6.452
274807UNIV PK N;3U
Adder
6.438
274811UNIV PK N;7U
Adder
6.396
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.288
276806AD2-047 C O1
Solar/Wind Harmer
5.041
970707AG2-453 GEN
Solar/Wind Harmer
29.056
274803UNIV PARK;6U
Adder
7.433
274826FISK ;BP
Adder
13.952
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
24.311
972038AH1-567 GEN2
Adder
0.465
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.319
270491AE1-102 GEN2
Solar/Wind Harmer
1.154
274676JOLIET 29;8U
Adder
37.578
274729ELWOOD EC;1P
Adder
20.872
274730ELWOOD EC;6P
Adder
20.872
274734ELWOOD EC;8P
Adder
20.872
274736ELWOOD EC;9P
Adder
20.872
270505AE1-170 C O1
Solar/Wind Harmer
9.267
943121AE2-341 GEN
Solar/Wind Harmer
14.798
943591AF1-030 GEN
Solar/Wind Harmer
9.841
945111AF1-176 GEN
Solar/Wind Harmer
7.15
24695305TIMB G C
Solar/Wind Harmer
0.747
274862TOP CROP ;2U
Solar/Wind Harmer
1.188
274682WAUKEGAN ;7U
Adder
22.607
276868AE1-113 GEN
Solar/Wind Harmer
1.751
274879MINONK ;1U
Solar/Wind Harmer
0.365
946671AF1-331 GEN
Solar/Wind Harmer
0.929
274855GSG-6 ;RU
Solar/Wind Harmer
0.318
274850MENDOTA H;RU
Solar/Wind Harmer
0.101
25196608WSDLE5
Adder
10.674
959091AF2-200 GEN
Solar/Wind Harmer
17.379
970571AG2-364 GEN
Solar/Wind Harmer
17.368
24728505AND G1
Adder
4.768
25194608D.CRK4
Adder
2.043
252519AF1-045_GEN
Solar/Wind Harmer
4.521
965091AG1-374 GEN
Solar/Wind Harmer
25.867
959611AF2-252 GEN
Solar/Wind Harmer
2.874
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.496
274767LEE CO EC;8U
Adder
11.361
970193AG2-126 GEN
Solar/Wind Harmer
12.901
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
252507AC2-088 GEN
Solar/Wind Harmer
0.384
971993AH1-541 GEN
Solar/Wind Harmer
3.929
25196008MFTGT1
Adder
1.643
965931AG1-462 GEN
Solar/Wind Harmer
21.621
971087AG2-675 GEN
Solar/Wind Harmer
4.522
957381AF2-032 GEN
Solar/Wind Harmer
1.898
942481AE2-261 GEN
Solar/Wind Harmer
25.023
270367AC2-061_GEN
Solar/Wind Harmer
-0.001
235058AG1-386 C
Solar/Wind Helper
0.575
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
962511AG1-100 GEN
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Helper
0.576
20092526R32
Solar/Wind Helper
1.21
964991AG1-363 GEN
Solar/Wind Helper
3.728
20303426NA_O38_P22
Solar/Wind Helper
1.017
23562501BACKB
Solar/Wind Helper
0.893
203993AD2-133_GEN1
Solar/Wind Helper
1.055
203854AF2-039 C
Solar/Wind Helper
0.327
20398826ARMNA MT
Solar/Wind Helper
1.511
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.259
958171AF2-111 GEN
Solar/Wind Harmer
13.887
270119AB2-067 GEN1
50/50
13.691
270120AB2-067 GEN2
50/50
13.691
270160DARBY CT5
50/50
0.825
270161DARBY CT6
50/50
0.813
270466AD2-091
50/50
8.422
25326109MON D
50/50
1.903
25326509SID D
50/50
1.895
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
8.674
938701AE1-092 GEN
Solar/Wind Harmer
16.303
971655AH1-328 GEN
Solar/Wind Harmer
3.602
270462AD2-086
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
4.181
25322209TAIT E
Adder
13.115
25322209TAIT E
Adder
12.82
253370AE2-315 SEC1
Adder
2.679
970349AG2-230 GEN
Solar/Wind Harmer
13.735
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.186
970291AG2-192 GEN
Solar/Wind Harmer
0.547
944541AF1-119 GEN
Solar/Wind Harmer
0.609
960971AF2-388 GEN
Solar/Wind Harmer
5.346
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
4.358
942221AE2-234 GEN
Solar/Wind Harmer
3.637
965681AG1-436 GEN
Solar/Wind Harmer
11.293
965791AG1-447 GEN
Solar/Wind Harmer
8.281
270031AE2-169
Solar/Wind Harmer
4.946
270599AE1-208 GEN
Solar/Wind Harmer
8.243
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.019
274770LINCOLN ;1U
Adder
10.86
274771LINCOLN ;2U
Adder
10.86
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.31
964611AG1-324 GEN
Solar/Wind Harmer
0.672
270246TR4_N_V150
Solar/Wind Harmer
0.057
270247TR4_N_V136
Solar/Wind Harmer
0.057
970883AG2-550 GEN
Solar/Wind Harmer
8.946
970885AG2-551 GEN
Solar/Wind Harmer
2.982
270383AD1-128 GEN
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
6.41
274808UNIV PK N;4U
Adder
6.368
274888KELLY CRK;1U
Solar/Wind Harmer
0.519
276776AD2-060 GEN
Solar/Wind Harmer
0.949
958011AF2-095 GEN
Solar/Wind Harmer
12.809
970941AG2-585 GEN
Solar/Wind Harmer
4.892
276897AD1-100 C
Solar/Wind Harmer
22.228
247620Y3-023
Adder
0.586
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.358
274674JOLIET 9 ;6U
Adder
19.549
276893AG1-478 C
Solar/Wind Harmer
0.591
970241AG2-163 GEN
Solar/Wind Harmer
5.155
958481AF2-142 GEN
Solar/Wind Harmer
13.2
961051AF2-396 GEN
Solar/Wind Harmer
17.567
961051AF2-396 GEN
Solar/Wind Harmer
11.711
274695ROCKY RD ;2P
Adder
14.015
274693ROCKY RD ;1P
Adder
13.877
274697ROCKY RD ;3P
Adder
3.807
274696ROCKY RD ;4P
Adder
14.346
274683WAUKEGAN ;8U
Adder
26.494
274683WAUKEGAN ;8U
Adder
22.333
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.148
962691AG1-118 GEN
Solar/Wind Harmer
26.273
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
17.379
971343AH1-151 GEN
Solar/Wind Harmer
17.379
247607V1-011 GEN
Solar/Wind Harmer
0
25194408D.CRK1
Adder
9.396
25194508D.CRK3
Adder
1.757
972235AH1-702 GEN1
Adder
3.131
972236AH1-702 GEN2
Adder
2.723
942111AE2-223 GEN
Solar/Wind Harmer
2.816
938861AE1-114 GEN
Solar/Wind Harmer
4.893
960611AF2-352 GEN
Solar/Wind Harmer
2.874
276645AC1-214 GEN1
Solar/Wind Harmer
0.338
274764LEE CO EC;5U
Adder
11.523
274765LEE CO EC;6U
Adder
11.523
274762LEE CO EC;3U
Adder
11.496
274763LEE CO EC;4U
Adder
11.388
945391AF1-204 GEN
Solar/Wind Harmer
9.138
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.387
252509AD1-136 GEN
Solar/Wind Harmer
0.043
276615X2-022 GEN
Solar/Wind Harmer
0.088
276838X2-022 GEN2
Solar/Wind Harmer
0.476
970623AG2-406 GEN
Solar/Wind Harmer
1.547
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.129
276916AD2-100_GEN
Solar/Wind Harmer
17.538
276911AD2-131_GEN
Solar/Wind Harmer
1.155
254304AE2-114 C
Solar/Wind Helper
0.274
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
241801AE1-079 GEN
Solar/Wind Helper
0.309
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
946071AF1-272 GEN
Solar/Wind Helper
2.879
203835AF1-098 GEN
Solar/Wind Helper
2.053
946381AF1-302 GEN
Solar/Wind Helper
0.237
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
203818AF1-086 GEN
Solar/Wind Helper
1.772
23585401KL_K28_T16
Solar/Wind Helper
1.267
203853AF1-134 C O1
Solar/Wind Helper
0.497
203804AE2-113_GEN
Solar/Wind Helper
1.84
23751201ROTHROCK
Solar/Wind Helper
0.733
203961AE2-224 GEN
Solar/Wind Helper
2.479
940863AE2-074 GEN
Solar/Wind Helper
0.479
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.672
203946AE2-131 C
Solar/Wind Helper
0.488
238117U2-030
Solar/Wind Helper
0.283
235531U2-073 GEN
Solar/Wind Helper
2.67
939741AE1-205 GEN
Solar/Wind Harmer
12.131
970819AG2-516 GEN
Solar/Wind Harmer
10.388
252510AF1-249 C
Solar/Wind Harmer
0.065
276646AC1-214 GEN2
Solar/Wind Harmer
0.338
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.496
274766LEE CO EC;7U
Adder
11.361
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.303
25196808ZIMRHP
Adder
93.029
25196008MFTGT1
Adder
1.696
276621W2-048 GEN
Solar/Wind Harmer
0.423
965911AG1-460 GEN
Solar/Wind Harmer
1.674
970091AG2-072 GEN
Adder
16.07
254303AC2-168 GEN
Solar/Wind Helper
0.198
241966AE1-183 GEN
Solar/Wind Helper
0.312
961971AG1-040 GEN
Solar/Wind Helper
0.519
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.485
964201AG1-281 GEN
Solar/Wind Helper
0.498
238185AF2-356 C
Solar/Wind Helper
2.178
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.055
203952AE2-129 C
Solar/Wind Helper
0.488
203855AF2-088 C
Solar/Wind Helper
0.158
238126S14_GEN_1
Solar/Wind Helper
0.662
238120AE2-309 GEN
Solar/Wind Helper
0.416
23751101LEADS_P59
Solar/Wind Helper
1.832
LAGNLTFEXP_LAGN->PJM
CLTF
17.61
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.111
TVALTFEXP_TVA->PJM
CLTF
8.46
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.765
MECLTFEXP_MEC->PJM
CLTF
19.491
SIGELTFEXP_SIGE->PJM
CLTF
0.599
CPLELTFEXP_CPLE->PJM
CLTF
2.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.056
NYPJM->LTFIMP_NY
CLTF
5.162
LGEELTFEXP_LGEE->PJM
CLTF
7.836
WECLTFEXP_WEC->PJM
CLTF
4.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.297
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4309.27
MW Contribution:
9.92
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:92.06 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3813.12
MW Contribution:
8.04
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
17.244
24721705FLATG2
50/50
3.319
24721805FLATG3
50/50
3.319
962761AG1-125 GEN
Solar/Wind Harmer
73.48
970149AG2-104 GEN
Solar/Wind Harmer
39.681
970155AG2-107 GEN
Solar/Wind Harmer
46.922
270520AE2-214 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.014
971995AH1-542 GEN
Solar/Wind Harmer
4.575
246936BC-WTG1
Solar/Wind Harmer
0.455
270489AE1-102 GEN1
Solar/Wind Harmer
1.468
965421AG1-410 GEN
Solar/Wind Harmer
33.842
965011AG1-365 GEN
Solar/Wind Harmer
11.206
24639705ELKHART HY
Adder
0.237
957891AF2-083 GEN
Solar/Wind Harmer
17.821
945111AF1-176 GEN
Solar/Wind Harmer
19.076
970373AG2-245 GEN
Solar/Wind Harmer
22.382
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.553
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.746
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
13.152
965651AG1-433 GEN
Solar/Wind Harmer
3.072
274773LINCOLN ;4U
Adder
12.619
274774LINCOLN ;5U
Adder
12.619
958861AF2-177 GEN
Solar/Wind Harmer
4.506
274751CRETE EC ;1U
Adder
12.279
274754CRETE EC ;4U
Adder
12.279
270273AD2-016 GEN
Solar/Wind Harmer
1.064
274723RIVER EC ;12
Adder
26.668
270024AE2-089 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.423
25326309TAIT D
Adder
1.618
274802UNIV PARK;5U
Adder
8.599
945371AF1-202 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
44.89
270594AE1-207 GEN
Solar/Wind Harmer
11.433
270032AE2-172
Solar/Wind Harmer
6.805
274674JOLIET 9 ;6U
Adder
22.504
274732ELWOOD EC;7P
Adder
24.024
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270119AB2-067 GEN1
50/50
17.244
270120AB2-067 GEN2
50/50
17.244
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
10.655
270462AD2-086
Solar/Wind Harmer
0.002
938701AE1-092 GEN
Solar/Wind Harmer
21.46
971655AH1-328 GEN
Solar/Wind Harmer
4.742
970329AG2-216 GEN
Solar/Wind Harmer
5.083
25326509SID D
Adder
2.143
246937BC-WTG2
Solar/Wind Harmer
0.455
270246TR4_N_V150
Solar/Wind Harmer
0.071
270247TR4_N_V136
Solar/Wind Harmer
0.071
247607V1-011 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
16.464
247620Y3-023
Adder
0.71
965681AG1-436 GEN
Solar/Wind Harmer
13.426
965791AG1-447 GEN
Solar/Wind Harmer
9.845
970623AG2-406 GEN
Solar/Wind Harmer
1.96
961051AF2-396 GEN
Solar/Wind Harmer
21.315
961051AF2-396 GEN
Solar/Wind Harmer
14.21
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.994
942221AE2-234 GEN
Solar/Wind Harmer
4.232
944541AF1-119 GEN
Solar/Wind Harmer
0.7
960971AF2-388 GEN
Solar/Wind Harmer
6.145
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.914
944231AF1-091 GEN
Solar/Wind Harmer
24.097
274770LINCOLN ;1U
Adder
12.619
274771LINCOLN ;2U
Adder
12.619
270269AC2-059
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
7.439
274808UNIV PK N;4U
Adder
7.391
25322209TAIT E
Adder
14.396
25322209TAIT E
Adder
14.072
970291AG2-192 GEN
Solar/Wind Harmer
1.338
970291AG2-192 GEN
Solar/Wind Harmer
0.618
274888KELLY CRK;1U
Solar/Wind Harmer
0.6
276776AD2-060 GEN
Solar/Wind Harmer
1.097
958011AF2-095 GEN
Solar/Wind Harmer
14.803
970941AG2-585 GEN
Solar/Wind Harmer
5.654
276897AD1-100 C
Solar/Wind Harmer
25.624
971613AH1-306 GEN
Solar/Wind Harmer
4.9
274674JOLIET 9 ;6U
Adder
22.504
276893AG1-478 C
Solar/Wind Harmer
0.68
270031AE2-169
Solar/Wind Harmer
5.58
270599AE1-208 GEN
Solar/Wind Harmer
9.3
253370AE2-315 SEC1
Adder
2.904
24721605FLATG1
50/50
3.319
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
9.821
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.932
945631AF1-228 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
5.259
943851AF1-053 GEN
Solar/Wind Harmer
3.643
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.888
241972AD1-140 GEN
Solar/Wind Harmer
1.272
270432AC2-029 GEN
Solar/Wind Harmer
5.04
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.43
959331AF2-224 GEN
Solar/Wind Harmer
7.844
247521TR3_G114
Solar/Wind Harmer
0.403
965051AG1-369 GEN
Solar/Wind Harmer
5.558
270071AF1-092 GEN
Solar/Wind Harmer
21.261
965041AG1-368 GEN
Solar/Wind Harmer
11.063
270007AE1-245 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
5.889
970179AG2-119 GEN
Solar/Wind Harmer
9.709
971771AH1-392 GEN
Solar/Wind Harmer
10.756
963791AG1-232 GEN
Solar/Wind Harmer
14.514
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
9.953
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24721905FLATG4
50/50
3.319
24722005FLATG5
50/50
3.319
270051AF1-062 GEN
50/50
23.559
270475AD2-096_GEN
50/50
14.072
962771AG1-126 GEN
Solar/Wind Harmer
73.48
970153AG2-106 GEN
Solar/Wind Harmer
46.922
961921AG1-034 GEN
Solar/Wind Harmer
14.732
270284AF1-227 GEN1
Solar/Wind Harmer
0
270391AF1-285 GEN3
Solar/Wind Harmer
0.932
942051AE2-217 GEN
Solar/Wind Harmer
25.116
270518AE2-148 GEN
Solar/Wind Harmer
1.063
253325AC1-069 GEN
Solar/Wind Harmer
0.014
246938BC-WTG3
Solar/Wind Harmer
0.406
270491AE1-102 GEN2
Solar/Wind Harmer
1.468
965021AG1-366 GEN
Solar/Wind Harmer
3.735
270043AE2-236 GEN
Solar/Wind Harmer
7.125
24695305TIMB G C
Solar/Wind Harmer
0.934
971347AH1-153 GEN
Solar/Wind Harmer
5.488
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
48.343
971199AH1-059 GEN
Solar/Wind Harmer
2.255
270505AE1-170 C O1
Solar/Wind Harmer
11.228
945111AF1-176 GEN
Solar/Wind Harmer
8.665
964401AG1-302 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
8.236
274772LINCOLN ;3U
Adder
12.619
274752CRETE EC ;2U
Adder
12.279
274753CRETE EC ;3U
Adder
12.279
274724RIVER EC ;11
Adder
26.355
247642Z2-115 C
Solar/Wind Harmer
0.004
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.354
274814UNIV PK N;0U
Adder
7.488
274807UNIV PK N;3U
Adder
7.472
241813AF1-122_GEN
Solar/Wind Harmer
4.544
971201AH1-060 GEN
Solar/Wind Harmer
2.029
274745AC1-111 GEN9
Adder
8.105
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.636
274861TOP CROP ;1U
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
11.216
939401AE1-172 GEN
Solar/Wind Harmer
7.51
274682WAUKEGAN ;7U
Adder
25.826
274828WAUKEGAN ;BP
Adder
15.858
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.482
276882AE2-255 GEN
Solar/Wind Harmer
1.162
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.217
970825AG2-519 GEN
Solar/Wind Harmer
3.528
270005AE1-210 C O1
Solar/Wind Harmer
2.149
957471AF2-041 GEN
Solar/Wind Harmer
29.515
959081AF2-199 GEN
Solar/Wind Harmer
9.838
971067AG2-660 GEN
Solar/Wind Harmer
3.279
274822ROCKFORD ;11
Adder
27.602
970569AG2-363 GEN
Solar/Wind Harmer
29.408
970819AG2-516 GEN
Solar/Wind Harmer
11.727
963741AG1-226 GEN
Solar/Wind Harmer
23.101
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.93
274766LEE CO EC;7U
Adder
12.777
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.109
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
13.541
276646AC1-214 GEN2
Solar/Wind Harmer
0.379
276708O09 GEN2
Solar/Wind Harmer
0.34
274848CAMPGROVE;RU
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.647
24728605AND G2
Adder
5.071
276621W2-048 GEN
Solar/Wind Harmer
0.459
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.029
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.662
23906502RICHG2&3
Adder
1.439
25196808ZIMRHP
Adder
90.149
970091AG2-072 GEN
Adder
20.654
238185AF2-356 C
Solar/Wind Helper
2.037
23751101LEADS_P59
Solar/Wind Helper
1.839
238120AE2-309 GEN
Solar/Wind Helper
0.401
238126S14_GEN_1
Solar/Wind Helper
0.635
965911AG1-460 GEN
Solar/Wind Harmer
1.103
274811UNIV PK N;7U
Adder
7.423
970289AG2-191 GEN
Solar/Wind Harmer
1.133
274803UNIV PARK;6U
Adder
8.599
274826FISK ;BP
Adder
16.137
274887GEN-1.85
Solar/Wind Harmer
0.267
276843GEN-1.7
Solar/Wind Harmer
0.332
276806AD2-047 C O1
Solar/Wind Harmer
5.825
972038AH1-567 GEN2
Adder
0.538
970707AG2-453 GEN
Solar/Wind Harmer
33.528
972259AH1-714 GEN
Adder
28.051
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
43.287
274730ELWOOD EC;6P
Adder
24.024
274734ELWOOD EC;8P
Adder
24.024
274736ELWOOD EC;9P
Adder
24.024
274729ELWOOD EC;1P
Adder
24.024
970065AG2-057 GEN
Solar/Wind Harmer
1.014
943121AE2-341 GEN
Solar/Wind Harmer
16.972
943591AF1-030 GEN
Solar/Wind Harmer
11.286
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
24386205FR-12G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
2.597
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.132
274862TOP CROP ;2U
Solar/Wind Harmer
1.359
274682WAUKEGAN ;7U
Adder
25.826
276868AE1-113 GEN
Solar/Wind Harmer
1.991
274879MINONK ;1U
Solar/Wind Harmer
0.415
946031AF1-268 GEN
Solar/Wind Harmer
9.47
970825AG2-519 GEN
Solar/Wind Harmer
7.486
270004AE1-209 GEN
Solar/Wind Harmer
2.149
946671AF1-331 GEN
Solar/Wind Harmer
1.054
274855GSG-6 ;RU
Solar/Wind Harmer
0.361
274850MENDOTA H;RU
Solar/Wind Harmer
0.115
959091AF2-200 GEN
Solar/Wind Harmer
19.677
970571AG2-364 GEN
Solar/Wind Harmer
19.606
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.93
274767LEE CO EC;8U
Adder
12.777
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.321
965091AG1-374 GEN
Solar/Wind Harmer
28.713
959611AF2-252 GEN
Solar/Wind Harmer
3.19
253394AE2-221_GEN
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
23.963
971087AG2-675 GEN
Solar/Wind Harmer
5.012
971993AH1-541 GEN
Solar/Wind Harmer
4.285
24728505AND G1
Adder
5.071
970193AG2-126 GEN
Solar/Wind Harmer
13.784
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.737
270541AE2-072 C
Solar/Wind Harmer
0.001
957381AF2-032 GEN
Solar/Wind Harmer
2.038
25196608WSDLE5
Adder
10.619
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.61
23906502RICHG2&3
Adder
1.439
23906402RICHG1
Adder
1.437
237048AF1-022 C
Solar/Wind Helper
0.174
237046AF1-021 C
Solar/Wind Helper
0.304
964991AG1-363 GEN
Solar/Wind Helper
3.522
23562501BACKB
Solar/Wind Helper
0.847
235058AG1-386 C
Solar/Wind Helper
0.4
238127S14_GEN_2
Solar/Wind Helper
0.635
202652Y1-033 WT C
Solar/Wind Helper
0.501
942481AE2-261 GEN
Solar/Wind Harmer
16.491
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.264
274775LINCOLN ;6U
Adder
12.619
274776LINCOLN ;7U
Adder
12.619
274777LINCOLN ;8U
Adder
12.619
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.956
972037AH1-567 GEN1
Adder
0.27
274827FISK ;RP
Adder
11.436
960591AF2-350 GEN
Solar/Wind Harmer
10.28
274800UNIV PARK;3U
Adder
8.587
274801UNIV PARK;4U
Adder
8.587
972228AH1-698 GEN2
Adder
5.454
972227AH1-698 GEN1
Adder
3.84
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
40.93
274687WILL CNTY;4U
Adder
40.93
274675JOLIET 29;7U
Adder
44.89
274675JOLIET 29;7U
Adder
43.287
274728ELWOOD EC;5P
Adder
24.024
274731ELWOOD EC;2P
Adder
24.024
274733ELWOOD EC;3P
Adder
24.024
274735ELWOOD EC;4P
Adder
24.024
970833AG2-524 GEN
Solar/Wind Harmer
11.198
970833AG2-524 GEN
Solar/Wind Harmer
7.465
270377AD1-106 GEN
Solar/Wind Harmer
3.864
971609AH1-304 GEN
Solar/Wind Harmer
1.657
971549AH1-272 GEN
Solar/Wind Harmer
20.903
274744AC1-111 GEN8
Adder
8.105
274746AC1-111 G10
Adder
8.105
253372AE2-315 SEC3
Adder
2.747
253372AE2-315 SEC3
Adder
2.747
24386405FR-21G C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.923
25306009OHH W.
Adder
4.15
247536S-71 GEN
Solar/Wind Harmer
0.4
970073AG2-061 GEN
Solar/Wind Harmer
3.33
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.303
270543AE2-219 C
Solar/Wind Harmer
6.944
971675AH1-338 GEN
Solar/Wind Harmer
3.854
971411AH1-196 GEN
Solar/Wind Harmer
14.823
276861AD2-134 GEN
Solar/Wind Harmer
0.176
276863AD2-134 GEN
Solar/Wind Harmer
0.176
970169AG2-114 GEN
Solar/Wind Harmer
9.859
971171AH1-044 GEN
Solar/Wind Harmer
19.677
971029AG2-637 GEN
Solar/Wind Harmer
14.756
274823ROCKFORD ;21
Adder
27.402
926823AC1-168 GEN
Solar/Wind Harmer
1.667
274856ECOGROVE ;U1
Solar/Wind Harmer
0.228
971681AH1-341 GEN
Solar/Wind Harmer
15.659
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.156
972267AH1-718 GEN
Adder
5.748
276741O09 GEN1
Solar/Wind Harmer
0.34
274877BISHOP HL;1U
Solar/Wind Harmer
0.321
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.283
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.365
276848AB2-070 GEN3
Solar/Wind Harmer
0.363
276849AB2-070 GEN2
Solar/Wind Harmer
0.365
270263AC1-001 GEN
Solar/Wind Harmer
0.924
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.684
25196408WSDLE3
Adder
10.931
25196108MFTGT2
Adder
1.832
25196108MFTGT2
Adder
1.701
23750501ELLIOTTS
Solar/Wind Helper
0.6
23652301WDPWR_K20
Solar/Wind Helper
0.129
23750701CROSSCHOOL
Solar/Wind Helper
1.119
238118U2-030_1
Solar/Wind Helper
0.267
203955AF1-039 C O1
Solar/Wind Helper
0.331
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.147
270201AC2-176 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
15.103
247621Y3-024
Adder
0.348
964611AG1-324 GEN
Solar/Wind Harmer
0.754
274696ROCKY RD ;4P
Adder
16.391
274695ROCKY RD ;2P
Adder
16.014
274693ROCKY RD ;1P
Adder
15.856
274697ROCKY RD ;3P
Adder
4.35
274683WAUKEGAN ;8U
Adder
30.253
274683WAUKEGAN ;8U
Adder
25.502
958491AF2-143 GEN
Solar/Wind Harmer
14.984
962691AG1-118 GEN
Solar/Wind Harmer
29.945
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
9.92
970885AG2-551 GEN
Solar/Wind Harmer
3.307
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
19.677
971343AH1-151 GEN
Solar/Wind Harmer
19.677
972235AH1-702 GEN1
Adder
3.539
972236AH1-702 GEN2
Adder
3.077
270383AD1-128 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.694
938861AE1-114 GEN
Solar/Wind Harmer
5.51
274764LEE CO EC;5U
Adder
12.96
274765LEE CO EC;6U
Adder
12.96
274762LEE CO EC;3U
Adder
12.93
274763LEE CO EC;4U
Adder
12.808
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
3.143
276645AC1-214 GEN1
Solar/Wind Harmer
0.379
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.554
960611AF2-352 GEN
Solar/Wind Harmer
3.19
945391AF1-204 GEN
Solar/Wind Harmer
9.764
276615X2-022 GEN
Solar/Wind Harmer
0.095
276838X2-022 GEN2
Solar/Wind Harmer
0.516
25194408D.CRK1
Adder
9.313
25194508D.CRK3
Adder
1.741
972159AH1-661 GEN
Adder
1.225
23751201ROTHROCK
Solar/Wind Helper
0.691
23585401KL_K28_T16
Solar/Wind Helper
1.178
237043AE2-125 C
Solar/Wind Helper
0.16
235054AD2-180 GEN
Solar/Wind Helper
1.576
238117U2-030
Solar/Wind Helper
0.267
235531U2-073 GEN
Solar/Wind Helper
2.548
LAGNLTFEXP_LAGN->PJM
CLTF
14.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
TVALTFEXP_TVA->PJM
CLTF
6.29
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.5
MECLTFEXP_MEC->PJM
CLTF
20.741
SIGELTFEXP_SIGE->PJM
CLTF
0.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
124.415
NYPJM->LTFIMP_NY
CLTF
4.821
LGEELTFEXP_LGEE->PJM
CLTF
7.242
WECLTFEXP_WEC->PJM
CLTF
5.355
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.468
AG2-052LTFEXP_AG2-052->PJM
LTF
0.342
AH1-155LTFEXP_AH1-155->PJM
LTF
0.513

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.48 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4638.62
MW Contribution:
7.4
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.401
965681AG1-436 GEN
Solar/Wind Harmer
13.215
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
93.339
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970155AG2-107 GEN
Solar/Wind Harmer
59.604
957891AF2-083 GEN
Solar/Wind Harmer
17.358
970373AG2-245 GEN
Solar/Wind Harmer
21.825
945111AF1-176 GEN
Solar/Wind Harmer
18.541
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
274754CRETE EC ;4U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.154
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
28.375
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276708O09 GEN2
Solar/Wind Harmer
0.324
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.763
274848CAMPGROVE;RU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
963741AG1-226 GEN
Solar/Wind Harmer
21.176
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.571
276621W2-048 GEN
Solar/Wind Harmer
0.421
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
276776AD2-060 GEN
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
14.407
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.66
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
28.923
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.429
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
10.525
270526AF1-158 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274776LINCOLN ;7U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959331AF2-224 GEN
Solar/Wind Harmer
7.14
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
10.005
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
965041AG1-368 GEN
Solar/Wind Harmer
9.581
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
965051AG1-369 GEN
Solar/Wind Harmer
4.689
963791AG1-232 GEN
Solar/Wind Harmer
12.673
926823AC1-168 GEN
Solar/Wind Harmer
1.594
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
963841AG1-237 GEN
Solar/Wind Harmer
3.99
972267AH1-718 GEN
Adder
5.487
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
1.719
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274752CRETE EC ;2U
Adder
11.974
274753CRETE EC ;3U
Adder
11.974
274724RIVER EC ;11
Adder
25.717
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
276843GEN-1.7
Solar/Wind Harmer
0.323
276806AD2-047 C O1
Solar/Wind Harmer
5.669
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
44.295
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.86
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
24386205FR-12G C
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
18.917
970571AG2-364 GEN
Solar/Wind Harmer
18.75
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
246938BC-WTG3
Solar/Wind Harmer
0.328
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
0.995
965091AG1-374 GEN
Solar/Wind Harmer
26.927
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
960611AF2-352 GEN
Solar/Wind Harmer
2.992
970241AG2-163 GEN
Solar/Wind Harmer
5.219
971613AH1-306 GEN
Solar/Wind Harmer
4.231
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
270031AE2-169
Solar/Wind Harmer
4.725
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
276838X2-022 GEN2
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276916AD2-100_GEN
Solar/Wind Harmer
16.976
276911AD2-131_GEN
Solar/Wind Harmer
1.118
945391AF1-204 GEN
Solar/Wind Harmer
8.566
247621Y3-024
Adder
0.274
926881AC1-175 GEN
Solar/Wind Harmer
0
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
970885AG2-551 GEN
Solar/Wind Harmer
2.468
971587AH1-292 GEN
Solar/Wind Harmer
5.199
270054AF2-122 C O1
Solar/Wind Helper
1.203
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
247536S-71 GEN
Solar/Wind Harmer
0.309
270543AE2-219 C
Solar/Wind Harmer
5.183
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270356AE2-297 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.992
965931AG1-462 GEN
Solar/Wind Harmer
22.694
971087AG2-675 GEN
Solar/Wind Harmer
4.746
971993AH1-541 GEN
Solar/Wind Harmer
3.947
957381AF2-032 GEN
Solar/Wind Harmer
1.851
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
270004AE1-209 GEN
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
6.118
946031AF1-268 GEN
Solar/Wind Harmer
7.675
970193AG2-126 GEN
Solar/Wind Harmer
12.093
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270541AE2-072 C
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4659.48
MW Contribution:
7.4
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
93.339
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970155AG2-107 GEN
Solar/Wind Harmer
59.604
957891AF2-083 GEN
Solar/Wind Harmer
17.358
970373AG2-245 GEN
Solar/Wind Harmer
21.825
945111AF1-176 GEN
Solar/Wind Harmer
18.541
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
274754CRETE EC ;4U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274752CRETE EC ;2U
Adder
11.974
274753CRETE EC ;3U
Adder
11.974
274724RIVER EC ;11
Adder
25.717
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
276843GEN-1.7
Solar/Wind Harmer
0.323
276806AD2-047 C O1
Solar/Wind Harmer
5.669
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
44.295
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.86
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
7.225
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.401
965681AG1-436 GEN
Solar/Wind Harmer
13.215
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
276776AD2-060 GEN
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
14.407
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.66
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
28.923
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.429
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
960611AF2-352 GEN
Solar/Wind Harmer
2.992
970241AG2-163 GEN
Solar/Wind Harmer
5.219
971613AH1-306 GEN
Solar/Wind Harmer
4.231
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
270031AE2-169
Solar/Wind Harmer
4.725
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
276838X2-022 GEN2
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
10.525
270526AF1-158 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274776LINCOLN ;7U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959331AF2-224 GEN
Solar/Wind Harmer
7.14
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
10.005
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
965041AG1-368 GEN
Solar/Wind Harmer
9.581
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
965051AG1-369 GEN
Solar/Wind Harmer
4.689
963791AG1-232 GEN
Solar/Wind Harmer
12.673
926823AC1-168 GEN
Solar/Wind Harmer
1.594
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
963841AG1-237 GEN
Solar/Wind Harmer
3.99
972267AH1-718 GEN
Adder
5.487
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
1.719
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
247536S-71 GEN
Solar/Wind Harmer
0.309
270543AE2-219 C
Solar/Wind Harmer
5.183
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270356AE2-297 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.154
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
28.375
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276708O09 GEN2
Solar/Wind Harmer
0.324
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.763
274848CAMPGROVE;RU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
963741AG1-226 GEN
Solar/Wind Harmer
21.176
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.571
276621W2-048 GEN
Solar/Wind Harmer
0.421
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
24386205FR-12G C
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
18.917
970571AG2-364 GEN
Solar/Wind Harmer
18.75
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
246938BC-WTG3
Solar/Wind Harmer
0.328
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
0.995
965091AG1-374 GEN
Solar/Wind Harmer
26.927
959611AF2-252 GEN
Solar/Wind Harmer
2.992
965931AG1-462 GEN
Solar/Wind Harmer
22.694
971087AG2-675 GEN
Solar/Wind Harmer
4.746
971993AH1-541 GEN
Solar/Wind Harmer
3.947
957381AF2-032 GEN
Solar/Wind Harmer
1.851
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
270004AE1-209 GEN
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
6.118
946031AF1-268 GEN
Solar/Wind Harmer
7.675
970193AG2-126 GEN
Solar/Wind Harmer
12.093
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270541AE2-072 C
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
16.976
276911AD2-131_GEN
Solar/Wind Harmer
1.118
945391AF1-204 GEN
Solar/Wind Harmer
8.566
247621Y3-024
Adder
0.274
926881AC1-175 GEN
Solar/Wind Harmer
0
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
970885AG2-551 GEN
Solar/Wind Harmer
2.468
971587AH1-292 GEN
Solar/Wind Harmer
5.199
270054AF2-122 C O1
Solar/Wind Helper
1.203
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.92 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5008.41
MW Contribution:
7.42
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
12.247
270144AC1-141 ST1_
50/50
4.015
24641605TWIN BRNCH
50/50
0.032
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
16.554
274776LINCOLN ;7U
50/50
16.554
274777LINCOLN ;8U
50/50
16.554
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
13.194
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
24.953
970031AG2-029 GEN
Solar/Wind Harmer
6.772
972037AH1-567 GEN1
Adder
0.327
274827FISK ;RP
Adder
13.882
960591AF2-350 GEN
Solar/Wind Harmer
12.474
274800UNIV PARK;3U
Adder
10.418
274801UNIV PARK;4U
Adder
10.418
972228AH1-698 GEN2
Adder
6.619
972227AH1-698 GEN1
Adder
4.661
274687WILL CNTY;4U
Adder
49.553
274687WILL CNTY;4U
Adder
49.553
274675JOLIET 29;7U
Adder
54.333
274675JOLIET 29;7U
Adder
52.393
274728ELWOOD EC;5P
Adder
29.026
274731ELWOOD EC;2P
Adder
29.025
274733ELWOOD EC;3P
Adder
29.025
274735ELWOOD EC;4P
Adder
29.025
970833AG2-524 GEN
Solar/Wind Harmer
13.528
970833AG2-524 GEN
Solar/Wind Harmer
9.019
24729505KEY G4
Adder
11.373
274744AC1-111 GEN8
Adder
9.782
274746AC1-111 G10
Adder
9.782
970073AG2-061 GEN
Solar/Wind Harmer
3.962
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971411AH1-196 GEN
Solar/Wind Harmer
17.649
971675AH1-338 GEN
Solar/Wind Harmer
4.588
276861AD2-134 GEN
Solar/Wind Harmer
0.21
276863AD2-134 GEN
Solar/Wind Harmer
0.21
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
23.357
971549AH1-272 GEN
Solar/Wind Harmer
24.093
274823ROCKFORD ;21
Adder
32.492
959331AF2-224 GEN
Solar/Wind Harmer
8.133
971611AH1-305 GEN
Solar/Wind Harmer
6.874
274856ECOGROVE ;U1
Solar/Wind Harmer
0.27
926823AC1-168 GEN
Solar/Wind Harmer
1.955
970169AG2-114 GEN
Solar/Wind Harmer
11.475
971681AH1-341 GEN
Solar/Wind Harmer
18.454
972267AH1-718 GEN
Adder
6.732
276741O09 GEN1
Solar/Wind Harmer
0.397
274877BISHOP HL;1U
Solar/Wind Harmer
0.372
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
11.542
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.109
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
14.195
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.388
276668AB2-070 GEN1
Solar/Wind Harmer
0.395
276848AB2-070 GEN3
Solar/Wind Harmer
0.393
276849AB2-070 GEN2
Solar/Wind Harmer
0.395
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
9.911
970289AG2-191 GEN
Solar/Wind Harmer
1.868
971609AH1-304 GEN
Solar/Wind Harmer
1.601
247521TR3_G114
Solar/Wind Harmer
0.327
965051AG1-369 GEN
Solar/Wind Harmer
4.503
944221AF1-090 GEN
Solar/Wind Harmer
5.281
964611AG1-324 GEN
Solar/Wind Harmer
3.439
247536S-71 GEN
Solar/Wind Harmer
0.321
270543AE2-219 C
Solar/Wind Harmer
5.19
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.88
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.12
24344105CKG2
50/50
15.733
270143AC1-141 CT2_
50/50
4.53
24639705ELKHART HY
50/50
0.302
274773LINCOLN ;4U
50/50
16.554
274774LINCOLN ;5U
50/50
16.554
970521AG2-332 GEN
50/50
21.475
24307105BERRINSP G
50/50
0.04
957891AF2-083 GEN
Solar/Wind Harmer
21.685
945111AF1-176 GEN
Solar/Wind Harmer
23.109
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.729
274723RIVER EC ;12
Adder
32.481
274751CRETE EC ;1U
Adder
14.913
274754CRETE EC ;4U
Adder
14.913
274812UNIV PK N;8U
Adder
9.011
274802UNIV PARK;5U
Adder
10.432
970373AG2-245 GEN
Solar/Wind Harmer
26.204
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
54.332
274674JOLIET 9 ;6U
Adder
27.209
274732ELWOOD EC;7P
Adder
29.026
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.782
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.958
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
30.998
274828WAUKEGAN ;BP
Adder
19.024
958381AF2-132 GEN
Solar/Wind Harmer
0.002
962781AG1-127 GEN
Solar/Wind Harmer
11.346
939401AE1-172 GEN
Solar/Wind Harmer
8.909
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
15.475
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.379
971997AH1-543 GEN
Solar/Wind Harmer
6.189
957471AF2-041 GEN
Solar/Wind Harmer
35.035
959081AF2-199 GEN
Solar/Wind Harmer
11.678
971067AG2-660 GEN
Solar/Wind Harmer
3.893
274822ROCKFORD ;11
Adder
32.73
965011AG1-365 GEN
Solar/Wind Harmer
11.618
970819AG2-516 GEN
Solar/Wind Harmer
13.872
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
14.433
970569AG2-363 GEN
Solar/Wind Harmer
34.504
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
15.212
274766LEE CO EC;7U
Adder
15.033
965651AG1-433 GEN
Solar/Wind Harmer
3.328
276708O09 GEN2
Solar/Wind Harmer
0.397
276646AC1-214 GEN2
Solar/Wind Harmer
0.44
274848CAMPGROVE;RU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.79
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
15.389
945371AF1-202 GEN
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.492
963741AG1-226 GEN
Solar/Wind Harmer
23.2
270594AE1-207 GEN
Solar/Wind Harmer
10.763
270032AE2-172
Solar/Wind Harmer
6.407
270024AE2-089 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.887
276903AD2-071 C
Solar/Wind Harmer
10.328
270005AE1-210 C O1
Solar/Wind Harmer
1.995
970825AG2-519 GEN
Solar/Wind Harmer
3.188
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.023
24728605AND G2
Adder
4.166
965421AG1-410 GEN
Solar/Wind Harmer
22.186
246936BC-WTG1
Solar/Wind Harmer
0.28
270489AE1-102 GEN1
Solar/Wind Harmer
0.903
970773AG2-487 GEN
Solar/Wind Harmer
1.206
970091AG2-072 GEN
Adder
67.129
270520AE2-214 GEN
Solar/Wind Helper
2.6
270286AF1-227 GEN2
Solar/Wind Helper
0.817
270142AC1-141 CT1_
50/50
4.53
24642205MAYFLWER
50/50
0.069
274772LINCOLN ;3U
50/50
16.554
944961AF1-161 GEN
50/50
5.371
962601AG1-109 GEN
50/50
5.371
971347AH1-153 GEN
Solar/Wind Harmer
7.007
270043AE2-236 GEN
Solar/Wind Harmer
8.609
270505AE1-170 C O1
Solar/Wind Harmer
13.688
945111AF1-176 GEN
Solar/Wind Harmer
10.497
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
32.107
274752CRETE EC ;2U
Adder
14.913
274753CRETE EC ;3U
Adder
14.913
274814UNIV PK N;0U
Adder
9.09
274807UNIV PK N;3U
Adder
9.07
274811UNIV PK N;7U
Adder
9.011
944531AF1-118 GEN
Solar/Wind Harmer
56.246
970707AG2-453 GEN
Solar/Wind Harmer
40.893
274803UNIV PARK;6U
Adder
10.432
274826FISK ;BP
Adder
19.587
274887GEN-1.85
Solar/Wind Harmer
0.324
276843GEN-1.7
Solar/Wind Harmer
0.403
276806AD2-047 C O1
Solar/Wind Harmer
7.069
972259AH1-714 GEN
Adder
34.103
972038AH1-567 GEN2
Adder
0.652
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
52.392
274730ELWOOD EC;6P
Adder
29.026
274734ELWOOD EC;8P
Adder
29.026
274736ELWOOD EC;9P
Adder
29.026
274729ELWOOD EC;1P
Adder
29.025
943121AE2-341 GEN
Solar/Wind Harmer
20.51
943591AF1-030 GEN
Solar/Wind Harmer
13.64
274862TOP CROP ;2U
Solar/Wind Harmer
1.626
274682WAUKEGAN ;7U
Adder
30.998
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
2.364
274879MINONK ;1U
Solar/Wind Harmer
0.493
946671AF1-331 GEN
Solar/Wind Harmer
1.255
274855GSG-6 ;RU
Solar/Wind Harmer
0.429
274850MENDOTA H;RU
Solar/Wind Harmer
0.137
959091AF2-200 GEN
Solar/Wind Harmer
23.357
965021AG1-366 GEN
Solar/Wind Harmer
3.873
970571AG2-364 GEN
Solar/Wind Harmer
23.003
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
15.212
274767LEE CO EC;8U
Adder
15.033
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.946
965931AG1-462 GEN
Solar/Wind Harmer
27.64
971087AG2-675 GEN
Solar/Wind Harmer
5.781
965091AG1-374 GEN
Solar/Wind Harmer
32.301
959611AF2-252 GEN
Solar/Wind Harmer
3.589
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
4.642
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.081
957381AF2-032 GEN
Solar/Wind Harmer
2.147
942481AE2-261 GEN
Solar/Wind Harmer
28.217
270004AE1-209 GEN
Solar/Wind Harmer
1.995
970825AG2-519 GEN
Solar/Wind Harmer
6.765
946031AF1-268 GEN
Solar/Wind Harmer
8.435
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.208
24695305TIMB G C
Solar/Wind Harmer
0.74
970193AG2-126 GEN
Solar/Wind Harmer
13.057
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.166
246938BC-WTG3
Solar/Wind Harmer
0.25
270491AE1-102 GEN2
Solar/Wind Harmer
0.903
270284AF1-227 GEN1
Solar/Wind Helper
2.228
270287AF1-227 GEN3
Solar/Wind Helper
0.817
270102X2-052 ST
50/50
3.058
270100X2-052 CT1
50/50
2.825
270101X2-052 CT2
50/50
2.825
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
16.554
274771LINCOLN ;2U
50/50
16.554
247620Y3-023
50/50
0.898
970349AG2-230 GEN
Solar/Wind Harmer
21.02
965681AG1-436 GEN
Solar/Wind Harmer
16.554
965791AG1-447 GEN
Solar/Wind Harmer
12.14
961051AF2-396 GEN
Solar/Wind Harmer
25.827
961051AF2-396 GEN
Solar/Wind Harmer
17.218
274805UNIV PK N;1U
Adder
9.031
274808UNIV PK N;4U
Adder
8.972
274888KELLY CRK;1U
Solar/Wind Harmer
0.727
276776AD2-060 GEN
Solar/Wind Harmer
1.331
958011AF2-095 GEN
Solar/Wind Harmer
17.963
970941AG2-585 GEN
Solar/Wind Harmer
6.861
276897AD1-100 C
Solar/Wind Harmer
31.049
274674JOLIET 9 ;6U
Adder
27.209
276893AG1-478 C
Solar/Wind Harmer
0.821
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274695ROCKY RD ;2P
Adder
19.235
274693ROCKY RD ;1P
Adder
19.046
274697ROCKY RD ;3P
Adder
5.225
274696ROCKY RD ;4P
Adder
19.689
958481AF2-142 GEN
Solar/Wind Harmer
18.073
274683WAUKEGAN ;8U
Adder
36.293
274683WAUKEGAN ;8U
Adder
30.593
962691AG1-118 GEN
Solar/Wind Harmer
35.867
958491AF2-143 GEN
Solar/Wind Harmer
17.827
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
23.357
971343AH1-151 GEN
Solar/Wind Harmer
23.357
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.192
972236AH1-702 GEN2
Adder
3.645
938861AE1-114 GEN
Solar/Wind Harmer
6.492
274764LEE CO EC;5U
Adder
15.248
274765LEE CO EC;6U
Adder
15.248
274762LEE CO EC;3U
Adder
15.212
274763LEE CO EC;4U
Adder
15.069
944541AF1-119 GEN
Solar/Wind Harmer
0.758
960971AF2-388 GEN
Solar/Wind Harmer
6.656
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.814
276645AC1-214 GEN1
Solar/Wind Harmer
0.44
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
3.572
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
3.589
942221AE2-234 GEN
Solar/Wind Harmer
4.268
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.188
944231AF1-091 GEN
Solar/Wind Harmer
23.789
276615X2-022 GEN
Solar/Wind Harmer
0.102
276838X2-022 GEN2
Solar/Wind Harmer
0.554
970291AG2-192 GEN
Solar/Wind Harmer
1.278
970291AG2-192 GEN
Solar/Wind Harmer
0.59
970241AG2-163 GEN
Solar/Wind Harmer
5.718
270031AE2-169
Solar/Wind Harmer
5.389
270599AE1-208 GEN
Solar/Wind Harmer
8.982
971613AH1-306 GEN
Solar/Wind Harmer
4.613
276916AD2-100_GEN
Solar/Wind Harmer
19.611
276911AD2-131_GEN
Solar/Wind Harmer
1.292
270246TR4_N_V150
Solar/Wind Harmer
0.058
270247TR4_N_V136
Solar/Wind Harmer
0.058
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.661
270201AC2-176 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
9.248
247621Y3-024
Adder
0.288
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.371
970883AG2-550 GEN
Solar/Wind Harmer
7.415
970885AG2-551 GEN
Solar/Wind Harmer
2.472
971587AH1-292 GEN
Solar/Wind Harmer
5.408
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.28
270349AD2-093_GEN
Solar/Wind Helper
1.835
270471AD2-092_GEN
Solar/Wind Helper
1.835
946101AF1-275 GEN
Solar/Wind Helper
0.65
270054AF2-122 C O1
Solar/Wind Helper
1.32
LAGNLTFEXP_LAGN->PJM
CLTF
12.121
TVALTFEXP_TVA->PJM
CLTF
4.571
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.577
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.817
MECLTFEXP_MEC->PJM
CLTF
22.833
SIGELTFEXP_SIGE->PJM
CLTF
0.424
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.518
NYPJM->LTFIMP_NY
CLTF
2.831
LGEELTFEXP_LGEE->PJM
CLTF
3.802
WECLTFEXP_WEC->PJM
CLTF
6.34
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.778
AG2-052LTFEXP_AG2-052->PJM
LTF
0.395
AH1-155LTFEXP_AH1-155->PJM
LTF
0.593

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#9287_1679_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#9287_1679_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.12 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4271.28
MW Contribution:
6.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
17.101
270143AC1-141 CT2_
50/50
4.628
274773LINCOLN ;4U
50/50
16.742
274774LINCOLN ;5U
50/50
16.742
24307105BERRINSP G
50/50
0.04
24639705ELKHART HY
50/50
0.302
247604X1-042
50/50
0.044
970521AG2-332 GEN
50/50
21.337
957891AF2-083 GEN
Solar/Wind Harmer
21.973
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.836
945111AF1-176 GEN
Solar/Wind Harmer
23.345
274723RIVER EC ;12
Adder
32.119
274751CRETE EC ;1U
Adder
14.651
274754CRETE EC ;4U
Adder
14.651
274812UNIV PK N;8U
Adder
8.876
274802UNIV PARK;5U
Adder
10.298
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.66
274674JOLIET 9 ;6U
Adder
26.849
274732ELWOOD EC;7P
Adder
28.611
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.659
274682WAUKEGAN ;7U
Adder
30.457
274828WAUKEGAN ;BP
Adder
18.685
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.913
274861TOP CROP ;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
11.128
274872LEEDK;1U
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
11.556
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
8.623
276882AE2-255 GEN
Solar/Wind Harmer
1.339
971997AH1-543 GEN
Solar/Wind Harmer
6.007
957471AF2-041 GEN
Solar/Wind Harmer
34.131
959081AF2-199 GEN
Solar/Wind Harmer
11.377
971067AG2-660 GEN
Solar/Wind Harmer
3.792
274822ROCKFORD ;11
Adder
31.861
970819AG2-516 GEN
Solar/Wind Harmer
13.478
970569AG2-363 GEN
Solar/Wind Harmer
33.131
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
14.712
274766LEE CO EC;7U
Adder
14.538
276708O09 GEN2
Solar/Wind Harmer
0.381
970373AG2-245 GEN
Solar/Wind Harmer
22.393
276646AC1-214 GEN2
Solar/Wind Harmer
0.418
965651AG1-433 GEN
Solar/Wind Harmer
3.089
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270142AC1-141 CT1_
50/50
4.628
24642205MAYFLWER
50/50
0.07
944961AF1-161 GEN
50/50
5.457
962601AG1-109 GEN
50/50
5.457
274772LINCOLN ;3U
50/50
16.742
971347AH1-153 GEN
Solar/Wind Harmer
7.293
270505AE1-170 C O1
Solar/Wind Harmer
13.912
945111AF1-176 GEN
Solar/Wind Harmer
10.605
270043AE2-236 GEN
Solar/Wind Harmer
8.283
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
31.767
970707AG2-453 GEN
Solar/Wind Harmer
40.791
274752CRETE EC ;2U
Adder
14.651
274753CRETE EC ;3U
Adder
14.651
972259AH1-714 GEN
Adder
33.857
274814UNIV PK N;0U
Adder
8.953
274807UNIV PK N;3U
Adder
8.934
274811UNIV PK N;7U
Adder
8.876
274826FISK ;BP
Adder
19.361
274887GEN-1.85
Solar/Wind Harmer
0.321
276843GEN-1.7
Solar/Wind Harmer
0.399
276806AD2-047 C O1
Solar/Wind Harmer
6.988
274803UNIV PARK;6U
Adder
10.298
972038AH1-567 GEN2
Adder
0.644
939351AE1-166 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.409
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
14.202
270055AF2-134 C O1
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.626
276621W2-048 GEN
Solar/Wind Harmer
0.426
270024AE2-089 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.598
270005AE1-210 C O1
Solar/Wind Harmer
1.716
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
9.838
965421AG1-410 GEN
Solar/Wind Harmer
22.84
970825AG2-519 GEN
Solar/Wind Harmer
2.631
246936BC-WTG1
Solar/Wind Harmer
0.29
270489AE1-102 GEN1
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.078
270594AE1-207 GEN
Solar/Wind Harmer
7.228
270032AE2-172
Solar/Wind Harmer
4.303
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
6.868
963741AG1-226 GEN
Solar/Wind Harmer
14.404
24344005CKG1
50/50
12.668
270144AC1-141 ST1_
50/50
4.102
24641605TWIN BRNCH
50/50
0.033
274775LINCOLN ;6U
50/50
16.742
274776LINCOLN ;7U
50/50
16.742
274777LINCOLN ;8U
50/50
16.742
24653605MOTTVILLE
50/50
0.007
971771AH1-392 GEN
Solar/Wind Harmer
13.283
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274827FISK ;RP
Adder
13.721
972228AH1-698 GEN2
Adder
6.549
972227AH1-698 GEN1
Adder
4.611
960591AF2-350 GEN
Solar/Wind Harmer
12.332
972037AH1-567 GEN1
Adder
0.323
274800UNIV PARK;3U
Adder
10.294
274801UNIV PARK;4U
Adder
10.294
274687WILL CNTY;4U
Adder
48.934
274687WILL CNTY;4U
Adder
48.934
274675JOLIET 29;7U
Adder
53.662
274675JOLIET 29;7U
Adder
51.745
274728ELWOOD EC;5P
Adder
28.611
274731ELWOOD EC;2P
Adder
28.61
274733ELWOOD EC;3P
Adder
28.61
274735ELWOOD EC;4P
Adder
28.61
970833AG2-524 GEN
Solar/Wind Harmer
13.35
970833AG2-524 GEN
Solar/Wind Harmer
8.9
274744AC1-111 GEN8
Adder
9.659
274746AC1-111 G10
Adder
9.659
970031AG2-029 GEN
Solar/Wind Harmer
6.498
971549AH1-272 GEN
Solar/Wind Harmer
24.686
24729505KEY G4
Adder
10.795
959331AF2-224 GEN
Solar/Wind Harmer
8.089
970073AG2-061 GEN
Solar/Wind Harmer
3.851
971411AH1-196 GEN
Solar/Wind Harmer
17.237
971675AH1-338 GEN
Solar/Wind Harmer
4.48
276861AD2-134 GEN
Solar/Wind Harmer
0.205
276863AD2-134 GEN
Solar/Wind Harmer
0.205
971171AH1-044 GEN
Solar/Wind Harmer
22.754
274823ROCKFORD ;21
Adder
31.63
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.262
971681AH1-341 GEN
Solar/Wind Harmer
17.867
926823AC1-168 GEN
Solar/Wind Harmer
1.875
270071AF1-092 GEN
Solar/Wind Harmer
21.116
970169AG2-114 GEN
Solar/Wind Harmer
10.885
972267AH1-718 GEN
Adder
6.485
276741O09 GEN1
Solar/Wind Harmer
0.381
274877BISHOP HL;1U
Solar/Wind Harmer
0.353
946321AF1-296 GEN
Solar/Wind Harmer
5.822
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.652
963791AG1-232 GEN
Solar/Wind Harmer
13.422
965041AG1-368 GEN
Solar/Wind Harmer
9.865
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.327
274676JOLIET 29;8U
Adder
51.744
274729ELWOOD EC;1P
Adder
28.61
274730ELWOOD EC;6P
Adder
28.611
274734ELWOOD EC;8P
Adder
28.611
274736ELWOOD EC;9P
Adder
28.611
943121AE2-341 GEN
Solar/Wind Harmer
20.29
943591AF1-030 GEN
Solar/Wind Harmer
13.493
944531AF1-118 GEN
Solar/Wind Harmer
53.775
274682WAUKEGAN ;7U
Adder
30.457
274862TOP CROP ;2U
Solar/Wind Harmer
1.588
965021AG1-366 GEN
Solar/Wind Harmer
3.852
946671AF1-331 GEN
Solar/Wind Harmer
1.226
274855GSG-6 ;RU
Solar/Wind Harmer
0.419
274850MENDOTA H;RU
Solar/Wind Harmer
0.133
276868AE1-113 GEN
Solar/Wind Harmer
2.296
274879MINONK ;1U
Solar/Wind Harmer
0.479
959091AF2-200 GEN
Solar/Wind Harmer
22.754
970571AG2-364 GEN
Solar/Wind Harmer
22.087
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
14.712
274767LEE CO EC;8U
Adder
14.538
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.353
965931AG1-462 GEN
Solar/Wind Harmer
26.286
971087AG2-675 GEN
Solar/Wind Harmer
5.498
965091AG1-374 GEN
Solar/Wind Harmer
29.5
959611AF2-252 GEN
Solar/Wind Harmer
3.278
964401AG1-302 GEN
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.055
24695305TIMB G C
Solar/Wind Harmer
0.742
957381AF2-032 GEN
Solar/Wind Harmer
1.822
942481AE2-261 GEN
Solar/Wind Harmer
23.884
270004AE1-209 GEN
Solar/Wind Harmer
1.716
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.272
946031AF1-268 GEN
Solar/Wind Harmer
7.057
970825AG2-519 GEN
Solar/Wind Harmer
5.584
246938BC-WTG3
Solar/Wind Harmer
0.259
270491AE1-102 GEN2
Solar/Wind Harmer
0.935
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.599
24386205FR-12G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.679
270102X2-052 ST
50/50
3.04
270100X2-052 CT1
50/50
2.808
270101X2-052 CT2
50/50
2.808
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
16.742
274771LINCOLN ;2U
50/50
16.742
247620Y3-023
50/50
0.894
970349AG2-230 GEN
Solar/Wind Harmer
21.879
965681AG1-436 GEN
Solar/Wind Harmer
16.375
965791AG1-447 GEN
Solar/Wind Harmer
12.008
961051AF2-396 GEN
Solar/Wind Harmer
26.182
961051AF2-396 GEN
Solar/Wind Harmer
17.455
274805UNIV PK N;1U
Adder
8.895
274808UNIV PK N;4U
Adder
8.837
274888KELLY CRK;1U
Solar/Wind Harmer
0.719
276776AD2-060 GEN
Solar/Wind Harmer
1.315
958011AF2-095 GEN
Solar/Wind Harmer
17.758
970941AG2-585 GEN
Solar/Wind Harmer
6.782
276897AD1-100 C
Solar/Wind Harmer
30.703
274674JOLIET 9 ;6U
Adder
26.849
276893AG1-478 C
Solar/Wind Harmer
0.809
274695ROCKY RD ;2P
Adder
18.919
274693ROCKY RD ;1P
Adder
18.733
274697ROCKY RD ;3P
Adder
5.139
274696ROCKY RD ;4P
Adder
19.364
274683WAUKEGAN ;8U
Adder
35.646
274683WAUKEGAN ;8U
Adder
30.048
958481AF2-142 GEN
Solar/Wind Harmer
17.657
962691AG1-118 GEN
Solar/Wind Harmer
35.208
958491AF2-143 GEN
Solar/Wind Harmer
17.33
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
22.754
971343AH1-151 GEN
Solar/Wind Harmer
22.754
972235AH1-702 GEN1
Adder
4.077
972236AH1-702 GEN2
Adder
3.545
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
6.286
274764LEE CO EC;5U
Adder
14.746
274765LEE CO EC;6U
Adder
14.746
274762LEE CO EC;3U
Adder
14.712
274763LEE CO EC;4U
Adder
14.573
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.741
276645AC1-214 GEN1
Solar/Wind Harmer
0.418
944541AF1-119 GEN
Solar/Wind Harmer
0.704
960971AF2-388 GEN
Solar/Wind Harmer
6.177
944231AF1-091 GEN
Solar/Wind Harmer
23.61
942111AE2-223 GEN
Solar/Wind Harmer
3.297
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
3.278
942221AE2-234 GEN
Solar/Wind Harmer
3.817
270246TR4_N_V150
Solar/Wind Harmer
0.058
270247TR4_N_V136
Solar/Wind Harmer
0.058
276615X2-022 GEN
Solar/Wind Harmer
0.088
276838X2-022 GEN2
Solar/Wind Harmer
0.479
270031AE2-169
Solar/Wind Harmer
4.571
270599AE1-208 GEN
Solar/Wind Harmer
7.618
276916AD2-100_GEN
Solar/Wind Harmer
16.489
276911AD2-131_GEN
Solar/Wind Harmer
1.086
970623AG2-406 GEN
Solar/Wind Harmer
1.389
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.562
246937BC-WTG2
Solar/Wind Harmer
0.29
247607V1-011 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.098
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.721
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
6.198
970885AG2-551 GEN
Solar/Wind Harmer
2.066
970291AG2-192 GEN
Solar/Wind Harmer
0.802
970291AG2-192 GEN
Solar/Wind Harmer
0.37
970241AG2-163 GEN
Solar/Wind Harmer
3.55
270349AD2-093_GEN
Solar/Wind Helper
1.46
965051AG1-369 GEN
Solar/Wind Harmer
4.508
276668AB2-070 GEN1
Solar/Wind Harmer
0.345
276848AB2-070 GEN3
Solar/Wind Harmer
0.343
276849AB2-070 GEN2
Solar/Wind Harmer
0.345
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.357
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.686
964611AG1-324 GEN
Solar/Wind Harmer
2.923
944221AF1-090 GEN
Solar/Wind Harmer
4.332
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.911
270007AE1-245 C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.271
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.694
270543AE2-219 C
Solar/Wind Harmer
4.339
970289AG2-191 GEN
Solar/Wind Harmer
1.173
270471AD2-092_GEN
Solar/Wind Helper
1.46
LAGNLTFEXP_LAGN->PJM
CLTF
9.08
TVALTFEXP_TVA->PJM
CLTF
3.004
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
184.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.09
MECLTFEXP_MEC->PJM
CLTF
20.956
SIGELTFEXP_SIGE->PJM
CLTF
0.265
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.536
NYPJM->LTFIMP_NY
CLTF
2.551
LGEELTFEXP_LGEE->PJM
CLTF
1.869
WECLTFEXP_WEC->PJM
CLTF
6.165
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.118
AG2-052LTFEXP_AG2-052->PJM
LTF
0.357
AH1-155LTFEXP_AH1-155->PJM
LTF
0.535

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#3149_05HANG R 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3149_05HANG R 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2216.66
MW Contribution:
7.99
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.427
24803206KYGER 4HP
50/50
4.417
253316AC1-085 GEN3
Solar/Wind Harmer
11.681
946171AF1-282 GEN
Solar/Wind Harmer
13.952
252516AE2-318_GEN
Solar/Wind Harmer
13.939
25196808ZIMRHP
Adder
103.883
270273AD2-016 GEN
Solar/Wind Harmer
3.628
252510AF1-249 C
Solar/Wind Harmer
0.552
25194608D.CRK4
Adder
2.171
253398AE2-221_GEN2
Solar/Wind Harmer
5.919
25196008MFTGT1
Adder
1.705
945681AF1-233 GEN
Solar/Wind Harmer
23.016
339221AD2-048_GEN
Solar/Wind Harmer
1.678
253370AE2-315 SEC1
Adder
2.154
253371AE2-315 SEC2
Adder
2.037
25326309TAIT D
Adder
1.136
270222AC2-111 GEN
Solar/Wind Harmer
4.57
944031AF1-071 GEN
Solar/Wind Harmer
1.028
943111AE2-339 GEN
Solar/Wind Harmer
0.888
3429421JKCT 10G
Adder
8.012
3429241JKCT 3G
Adder
10.994
253333AC1-068 GEN
Solar/Wind Harmer
0.911
942081AE2-220 GEN
Solar/Wind Harmer
5.25
270209AC1-174_GEN
Solar/Wind Harmer
3.341
270437AC2-090 C
Solar/Wind Harmer
4.582
270239V3-007_GEN1
Solar/Wind Harmer
1.413
339211AE2-254 GEN
Solar/Wind Harmer
1.157
24803006KYGER 3HP
50/50
4.478
24802806KYGER 2HP
50/50
4.462
24802906KYGER 2LP
50/50
2.619
25183008BIOENL
50/50
0.04
252509AD1-136 GEN
Solar/Wind Harmer
0.382
25183208HLCRTG
Solar/Wind Harmer
8.726
270269AC2-059
Solar/Wind Harmer
12.725
25194408D.CRK1
Adder
9.987
25194508D.CRK3
Adder
1.867
253415AE1-040 GEN
Solar/Wind Harmer
1.391
962581AG1-107 GEN
Solar/Wind Harmer
6.139
961491AF2-440 GEN
Solar/Wind Harmer
2.552
253370AE2-315 SEC1
Adder
2.154
972043AH1-570 GEN
Solar/Wind Harmer
2.668
972045AH1-571 GEN
Solar/Wind Harmer
2.134
25322209TAIT E
Adder
10.12
25322209TAIT E
Adder
9.892
253349AC2-067 GEN
Solar/Wind Harmer
2.068
253400AC2-068 GEN
Solar/Wind Harmer
0.832
25326109MON D
Adder
1.335
971125AH1-004 GEN
Solar/Wind Harmer
4.054
970107AG2-081 GEN
Solar/Wind Harmer
3.041
942891AE2-308 GEN
Solar/Wind Harmer
9.049
926881AC1-175 GEN
Solar/Wind Harmer
4.582
270383AD1-128 GEN
Solar/Wind Harmer
4.96
970883AG2-550 GEN
Solar/Wind Harmer
7.986
970885AG2-551 GEN
Solar/Wind Harmer
1.857
247621Y3-024
Adder
0.179
25326509SID D
Adder
0.961
964611AG1-324 GEN
Solar/Wind Harmer
0.38
270201AC2-176 GEN
Solar/Wind Harmer
3.708
964571AG1-320 GEN
Solar/Wind Harmer
5.837
971073AG2-665 GEN
Solar/Wind Harmer
5.557
970879AG2-548 GEN
Solar/Wind Harmer
0.808
24725505WLD G2 C
Solar/Wind Harmer
2.754
24699105WLD G1 C
Solar/Wind Harmer
2.722
253378AE2-206_GEN
Solar/Wind Harmer
2.463
270031AE2-169
Solar/Wind Harmer
5.579
270599AE1-208 GEN
Solar/Wind Harmer
5.579
944541AF1-119 GEN
Solar/Wind Harmer
2.712
960971AF2-388 GEN
Solar/Wind Harmer
7.079
942861AE2-305 GEN
Solar/Wind Harmer
4.965
970291AG2-192 GEN
Solar/Wind Harmer
0.823
970291AG2-192 GEN
Solar/Wind Harmer
0.265
942221AE2-234 GEN
Solar/Wind Harmer
2.13
339236AF1-050_GEN
Solar/Wind Harmer
1.062
945391AF1-204 GEN
Solar/Wind Harmer
7.777
339231AF1-038_GEN
Solar/Wind Harmer
1.01
927014AC1-188 GEN
Solar/Wind Harmer
0.86
964781AG1-341 GEN
Solar/Wind Harmer
5.607
253383AE2-342_GEN
Solar/Wind Harmer
0.463
970241AG2-163 GEN
Solar/Wind Harmer
12.901
270005AE1-210 C O1
Solar/Wind Harmer
4.08
24728605AND G2
Adder
2.824
970825AG2-519 GEN
Solar/Wind Harmer
1.543
971073AG2-665 GEN
Solar/Wind Harmer
0.808
945371AF1-202 GEN
Solar/Wind Harmer
4.791
970653AG2-424 GEN
Solar/Wind Harmer
3.289
276903AD2-071 C
Solar/Wind Harmer
6.734
958861AF2-177 GEN
Solar/Wind Harmer
7.226
270594AE1-207 GEN
Solar/Wind Harmer
8.954
270032AE2-172
Solar/Wind Harmer
3.066
270024AE2-089 GEN
Solar/Wind Harmer
3.071
965651AG1-433 GEN
Solar/Wind Harmer
3.54
339241AF1-083 GEN
Solar/Wind Harmer
1.047
964901AG1-354 GEN
Solar/Wind Harmer
8.68
970091AG2-072 GEN
Adder
41.08
963741AG1-226 GEN
Solar/Wind Harmer
23.222
24385905FR-11G C
Solar/Wind Harmer
4.077
24386605FR-22G C
Solar/Wind Harmer
2.11
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
2.997
276686W4-005 GEN3
Solar/Wind Harmer
1.451
24791305MDL-5G
Solar/Wind Harmer
1.145
274732ELWOOD EC;7P
Adder
7.239
274674JOLIET 9 ;6U
Adder
6.773
274676JOLIET 29;8U
Adder
13.475
274802UNIV PARK;5U
Adder
2.56
274745AC1-111 GEN9
Adder
2.453
274812UNIV PK N;8U
Adder
2.195
274682WAUKEGAN ;7U
Adder
7.875
274828WAUKEGAN ;BP
Adder
4.839
274761LEE CO EC;2U
Adder
4.074
274766LEE CO EC;7U
Adder
4.026
274723RIVER EC ;12
Adder
7.842
960001AF2-291 GEN
Solar/Wind Helper
1.495
270331AC1-082 GEN3
Solar/Wind Helper
0.169
235780M24_1
Solar/Wind Helper
0.532
24802606KYGER 1HP
50/50
4.51
24802706KYGER 1LP
50/50
2.645
24803506KYGER 5LP
50/50
2.583
971985AH1-537 GEN
Solar/Wind Harmer
56.698
253433AC1-085 GEN1
Solar/Wind Harmer
7.414
253432AC1-085 GEN2
Solar/Wind Harmer
0.373
270263AC1-001 GEN
Solar/Wind Harmer
1.45
25196408WSDLE3
Adder
11.623
270340AC2-060 GEN
Solar/Wind Harmer
3.884
253406AD2-031_GEN
Solar/Wind Harmer
1.593
25196108MFTGT2
Adder
1.88
25196108MFTGT2
Adder
1.746
972163AH1-664 GEN
Solar/Wind Harmer
12.044
972165AH1-665 GEN
Solar/Wind Harmer
9.636
339216AC1-074 GEN
Solar/Wind Harmer
1.864
270432AC2-029 GEN
Solar/Wind Harmer
7.644
253372AE2-315 SEC3
Adder
2.037
253372AE2-315 SEC3
Adder
2.037
25306009OHH W.
Adder
3.033
3429211JKCT 2G
Adder
10.852
241972AD1-140 GEN
Solar/Wind Harmer
4.019
253338AC1-165 GEN
Solar/Wind Harmer
0.945
253343AC1-166 GEN
Solar/Wind Harmer
0.945
270356AE2-297 GEN
Solar/Wind Harmer
3.987
971029AG2-637 GEN
Solar/Wind Harmer
12.539
270543AE2-219 C
Solar/Wind Harmer
7.986
247536S-71 GEN
Solar/Wind Harmer
3.092
964611AG1-324 GEN
Solar/Wind Harmer
2.831
961761AG1-017 GEN
Solar/Wind Harmer
0.309
945581AF1-223 GEN
Solar/Wind Harmer
3.114
945631AF1-228 GEN
Solar/Wind Harmer
3.07
958711AF2-162 GEN
Solar/Wind Harmer
0.655
943861AF1-054 GEN
Solar/Wind Harmer
2.451
943851AF1-053 GEN
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
1.202
24729505KEY G4
Adder
3.936
270291AC1-194 GEN
Solar/Wind Harmer
2.922
270444AC2-157 GEN1
Solar/Wind Harmer
3.091
270445AC2-157 GEN2
Solar/Wind Harmer
3.091
963791AG1-232 GEN
Solar/Wind Harmer
7.435
241955AC1-078 GEN
Solar/Wind Harmer
4.102
241973AD2-163_GEN1
Solar/Wind Harmer
1.085
241974AD2-163_GEN2
Solar/Wind Harmer
1.085
963841AG1-237 GEN
Solar/Wind Harmer
5.506
24386405FR-21G C
Solar/Wind Harmer
2.11
24387005FR-3G C
Solar/Wind Harmer
1.94
270071AF1-092 GEN
Solar/Wind Harmer
7.35
944221AF1-090 GEN
Solar/Wind Harmer
5.351
276763AC1-053 GEN1
Solar/Wind Harmer
1.897
276764AC1-053 GEN2
Solar/Wind Harmer
1.897
276668AB2-070 GEN1
Solar/Wind Harmer
1.062
276848AB2-070 GEN3
Solar/Wind Harmer
1.062
276849AB2-070 GEN2
Solar/Wind Harmer
1.062
946581AF1-322 GEN
Solar/Wind Harmer
4.858
24691005MDL-2G C
Solar/Wind Harmer
1.756
274731ELWOOD EC;2P
Adder
7.239
274733ELWOOD EC;3P
Adder
7.239
274735ELWOOD EC;4P
Adder
7.239
274728ELWOOD EC;5P
Adder
7.239
972228AH1-698 GEN2
Adder
1.631
972227AH1-698 GEN1
Adder
1.148
274800UNIV PARK;3U
Adder
2.561
274801UNIV PARK;4U
Adder
2.561
274675JOLIET 29;7U
Adder
13.475
274675JOLIET 29;7U
Adder
12.994
274687WILL CNTY;4U
Adder
12.271
274687WILL CNTY;4U
Adder
12.271
972037AH1-567 GEN1
Adder
0.08
274744AC1-111 GEN8
Adder
2.453
274746AC1-111 G10
Adder
2.453
274827FISK ;RP
Adder
3.404
972267AH1-718 GEN
Adder
1.824
24803106KYGER 3LP
50/50
2.637
24803306KYGER 4LP
50/50
2.583
971191AH1-055 GEN
Solar/Wind Harmer
85.223
252507AC2-088 GEN
Solar/Wind Harmer
2.672
253317AC1-085 GEN4
Solar/Wind Harmer
11.681
946181AF1-283 GEN
Solar/Wind Harmer
18.138
252519AF1-045_GEN
Solar/Wind Harmer
5.073
25194608D.CRK4
Adder
2.171
252524AE2-267 GEN
Solar/Wind Harmer
2.074
25196608WSDLE5
Adder
11.291
958171AF2-111 GEN
Solar/Wind Harmer
32.8
253394AE2-221_GEN
Solar/Wind Harmer
5.919
270367AC2-061_GEN
Solar/Wind Harmer
3.968
270186AC1-089 GEN
Solar/Wind Harmer
7.496
972167AH1-666 GEN
Solar/Wind Harmer
9.813
25196008MFTGT1
Adder
1.652
339243AC2-075 GEN1
Solar/Wind Harmer
0.505
253303V4-073 C
Solar/Wind Harmer
0.125
253370AE2-315 SEC1
Adder
2.154
253371AE2-315 SEC2
Adder
2.037
960071AF2-298 GEN
Solar/Wind Harmer
1.548
3429391JKCT 9G
Adder
8.012
253325AC1-069 GEN
Solar/Wind Harmer
0.911
970093AG2-073 GEN
Solar/Wind Harmer
4.533
24379505HDWTR1G C
Solar/Wind Harmer
6.491
270240V3-007_GEN2
Solar/Wind Harmer
5.079
270518AE2-148 GEN
Solar/Wind Harmer
9.286
270004AE1-209 GEN
Solar/Wind Harmer
4.08
970455AG2-298 GEN
Solar/Wind Harmer
2.601
946031AF1-268 GEN
Solar/Wind Harmer
6.158
24728505AND G1
Adder
2.824
970825AG2-519 GEN
Solar/Wind Harmer
4.143
962031AG1-047 GEN
Solar/Wind Harmer
2.182
957741AF2-068 GEN
Solar/Wind Harmer
10.823
970879AG2-548 GEN
Solar/Wind Harmer
5.557
276820AF1-078_GEN
Solar/Wind Harmer
1.094
970653AG2-424 GEN
Solar/Wind Harmer
0.476
339206AE1-143 GEN
Solar/Wind Harmer
1.407
965461AG1-414 GEN
Solar/Wind Harmer
1.435
970289AG2-191 GEN
Solar/Wind Harmer
0.486
247642Z2-115 C
Solar/Wind Harmer
0.039
942051AE2-217 GEN
Solar/Wind Harmer
10.751
944531AF1-118 GEN
Solar/Wind Harmer
20.719
960801AF2-371 GEN
Solar/Wind Harmer
1.503
964871AG1-351 GEN
Solar/Wind Harmer
1.038
972273AH1-721 GEN
Adder
48.281
970193AG2-126 GEN
Solar/Wind Harmer
8.371
957541AF2-048 GEN
Solar/Wind Harmer
0.86
339255AE2-071 GEN
Solar/Wind Harmer
0.625
339250AF1-203 GEN
Solar/Wind Harmer
0.322
24386205FR-12G C
Solar/Wind Harmer
2.102
942481AE2-261 GEN
Solar/Wind Harmer
14.45
957381AF2-032 GEN
Solar/Wind Harmer
0.966
276785W4-005 GEN1
Solar/Wind Harmer
1.451
971993AH1-541 GEN
Solar/Wind Harmer
4.434
24690905MDL-1G C
Solar/Wind Harmer
3.811
274729ELWOOD EC;1P
Adder
7.239
274730ELWOOD EC;6P
Adder
7.239
274734ELWOOD EC;8P
Adder
7.239
274736ELWOOD EC;9P
Adder
7.239
972259AH1-714 GEN
Adder
8.385
972038AH1-567 GEN2
Adder
0.16
274676JOLIET 29;8U
Adder
12.994
274803UNIV PARK;6U
Adder
2.56
274826FISK ;BP
Adder
4.804
274814UNIV PK N;0U
Adder
2.215
274807UNIV PK N;3U
Adder
2.21
274811UNIV PK N;7U
Adder
2.195
274682WAUKEGAN ;7U
Adder
7.875
274760LEE CO EC;1U
Adder
4.074
274767LEE CO EC;8U
Adder
4.026
274724RIVER EC ;11
Adder
5.289
270330AC1-082 GEN2
Solar/Wind Helper
0.17
270329AC1-082 GEN1
Solar/Wind Helper
0.17
970781AG2-491 GEN
Solar/Wind Harmer
2.151
971485AH1-239 GEN
Solar/Wind Harmer
3.962
24387305FR-4G C
Solar/Wind Harmer
2.492
966841AG1-555 GEN
Solar/Wind Harmer
1.232
966021AG1-471 GEN
Solar/Wind Harmer
2.631
276916AD2-100_GEN
Solar/Wind Harmer
10.179
276911AD2-131_GEN
Solar/Wind Harmer
2.057
276615X2-022 GEN
Solar/Wind Harmer
0.941
276838X2-022 GEN2
Solar/Wind Harmer
0.112
274880W4-005 GEN4
Solar/Wind Harmer
1.451
276174W4-005 GEN2
Solar/Wind Harmer
1.451
270180AB1-006 GEN1
Solar/Wind Harmer
3.414
24697605MDL-3G C
Solar/Wind Harmer
1.75
24755605MDL-5G
Solar/Wind Harmer
1.145
24697905MDL-4G C
Solar/Wind Harmer
1.089
270181AB1-006 GEN2
Solar/Wind Harmer
0.34
274674JOLIET 9 ;6U
Adder
6.773
274696ROCKY RD ;4P
Adder
4.997
274695ROCKY RD ;2P
Adder
4.881
274693ROCKY RD ;1P
Adder
4.833
274697ROCKY RD ;3P
Adder
1.326
274805UNIV PK N;1U
Adder
2.2
274808UNIV PK N;4U
Adder
2.186
274683WAUKEGAN ;8U
Adder
9.232
274683WAUKEGAN ;8U
Adder
7.782
274764LEE CO EC;5U
Adder
4.084
274765LEE CO EC;6U
Adder
4.084
274762LEE CO EC;3U
Adder
4.074
274763LEE CO EC;4U
Adder
4.036
237033AB1-150 GEN
Solar/Wind Helper
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
5.53
TVALTFEXP_TVA->PJM
CLTF
2.623
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.436
CBM West 1LTFEXP_CBM-W1->PJM
CBM
67.865
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.827
MECLTFEXP_MEC->PJM
CLTF
7.138
SIGELTFEXP_SIGE->PJM
CLTF
0.35
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.263
NYPJM->LTFIMP_NY
CLTF
1.649
LGEELTFEXP_LGEE->PJM
CLTF
5.838
WECLTFEXP_WEC->PJM
CLTF
1.668
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.901
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.49 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1901.76
MW Contribution:
6.46
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.088
24803206KYGER 4HP
50/50
4.079
252516AE2-318_GEN
Solar/Wind Harmer
10.884
25196808ZIMRHP
Adder
81.628
25194608D.CRK4
Adder
1.737
252510AF1-249 C
Solar/Wind Harmer
0.44
25196008MFTGT1
Adder
1.418
253316AC1-085 GEN3
Solar/Wind Harmer
8.517
946171AF1-282 GEN
Solar/Wind Harmer
10.173
253398AE2-221_GEN2
Solar/Wind Harmer
4.342
945681AF1-233 GEN
Solar/Wind Harmer
17.68
339221AD2-048_GEN
Solar/Wind Harmer
1.364
24802606KYGER 1HP
50/50
4.165
24802706KYGER 1LP
50/50
2.442
24803506KYGER 5LP
50/50
2.385
971985AH1-537 GEN
Solar/Wind Harmer
50.232
25196408WSDLE3
Adder
9.326
25196108MFTGT2
Adder
1.564
25196108MFTGT2
Adder
1.452
253433AC1-085 GEN1
Solar/Wind Harmer
5.406
253432AC1-085 GEN2
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
9.279
972165AH1-665 GEN
Solar/Wind Harmer
7.424
339216AC1-074 GEN
Solar/Wind Harmer
1.517
253406AD2-031_GEN
Solar/Wind Harmer
1.147
270340AC2-060 GEN
Solar/Wind Harmer
2.587
270263AC1-001 GEN
Solar/Wind Harmer
0.87
253372AE2-315 SEC3
Adder
1.541
253372AE2-315 SEC3
Adder
1.541
25306009OHH W.
Adder
2.304
3429211JKCT 2G
Adder
9.05
24803106KYGER 3LP
50/50
2.435
24803306KYGER 4LP
50/50
2.385
971191AH1-055 GEN
Solar/Wind Harmer
71.732
252507AC2-088 GEN
Solar/Wind Harmer
2.093
252519AF1-045_GEN
Solar/Wind Harmer
3.961
252524AE2-267 GEN
Solar/Wind Harmer
1.664
25196608WSDLE5
Adder
9.059
25194608D.CRK4
Adder
1.737
25196008MFTGT1
Adder
1.374
270273AD2-016 GEN
Solar/Wind Harmer
2.213
943111AE2-339 GEN
Solar/Wind Harmer
0.732
270222AC2-111 GEN
Solar/Wind Harmer
3.698
944031AF1-071 GEN
Solar/Wind Harmer
0.832
253370AE2-315 SEC1
Adder
1.629
253371AE2-315 SEC2
Adder
1.541
3429421JKCT 10G
Adder
6.632
970091AG2-072 GEN
Adder
60.833
25326309TAIT D
Adder
0.86
3429241JKCT 3G
Adder
9.168
339211AE2-254 GEN
Solar/Wind Harmer
1.029
942081AE2-220 GEN
Solar/Wind Harmer
4.355
270209AC1-174_GEN
Solar/Wind Harmer
2.771
270437AC2-090 C
Solar/Wind Harmer
3.8
270239V3-007_GEN1
Solar/Wind Harmer
1.172
970653AG2-424 GEN
Solar/Wind Harmer
3.113
24728605AND G2
Adder
2.452
270005AE1-210 C O1
Solar/Wind Harmer
3.373
970825AG2-519 GEN
Solar/Wind Harmer
1.27
339241AF1-083 GEN
Solar/Wind Harmer
0.988
253333AC1-068 GEN
Solar/Wind Harmer
0.611
945371AF1-202 GEN
Solar/Wind Harmer
3.908
964901AG1-354 GEN
Solar/Wind Harmer
8.361
276903AD2-071 C
Solar/Wind Harmer
5.516
958861AF2-177 GEN
Solar/Wind Harmer
5.856
270594AE1-207 GEN
Solar/Wind Harmer
7.241
270032AE2-172
Solar/Wind Harmer
2.48
270024AE2-089 GEN
Solar/Wind Harmer
2.452
965651AG1-433 GEN
Solar/Wind Harmer
2.858
963741AG1-226 GEN
Solar/Wind Harmer
20.834
965911AG1-460 GEN
Solar/Wind Harmer
0.634
276621W2-048 GEN
Solar/Wind Harmer
2.771
276686W4-005 GEN3
Solar/Wind Harmer
1.331
960001AF2-291 GEN
Solar/Wind Helper
1.708
270331AC1-082 GEN3
Solar/Wind Helper
0.192
235780M24_1
Solar/Wind Helper
0.478
253317AC1-085 GEN4
Solar/Wind Harmer
8.517
946181AF1-283 GEN
Solar/Wind Harmer
13.225
958171AF2-111 GEN
Solar/Wind Harmer
24.984
253394AE2-221_GEN
Solar/Wind Harmer
4.342
972167AH1-666 GEN
Solar/Wind Harmer
7.533
270367AC2-061_GEN
Solar/Wind Harmer
2.88
339243AC2-075 GEN1
Solar/Wind Harmer
0.411
270186AC1-089 GEN
Solar/Wind Harmer
5.474
253303V4-073 C
Solar/Wind Harmer
0.094
253370AE2-315 SEC1
Adder
1.629
253371AE2-315 SEC2
Adder
1.541
3429391JKCT 9G
Adder
6.632
960071AF2-298 GEN
Solar/Wind Harmer
1.175
970093AG2-073 GEN
Solar/Wind Harmer
3.861
970455AG2-298 GEN
Solar/Wind Harmer
2.419
24379505HDWTR1G C
Solar/Wind Harmer
5.384
270240V3-007_GEN2
Solar/Wind Harmer
4.212
970653AG2-424 GEN
Solar/Wind Harmer
0.45
24728505AND G1
Adder
2.452
270004AE1-209 GEN
Solar/Wind Harmer
3.373
339206AE1-143 GEN
Solar/Wind Harmer
1.311
946031AF1-268 GEN
Solar/Wind Harmer
5.055
970825AG2-519 GEN
Solar/Wind Harmer
3.411
962031AG1-047 GEN
Solar/Wind Harmer
1.769
957741AF2-068 GEN
Solar/Wind Harmer
8.774
253325AC1-069 GEN
Solar/Wind Harmer
0.611
972273AH1-721 GEN
Adder
45.289
970193AG2-126 GEN
Solar/Wind Harmer
7.936
270518AE2-148 GEN
Solar/Wind Harmer
6.377
339255AE2-071 GEN
Solar/Wind Harmer
0.613
339250AF1-203 GEN
Solar/Wind Harmer
0.316
965461AG1-414 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
0.39
276820AF1-078_GEN
Solar/Wind Harmer
0.788
247642Z2-115 C
Solar/Wind Harmer
0.031
944531AF1-118 GEN
Solar/Wind Harmer
16.445
942481AE2-261 GEN
Solar/Wind Harmer
13.577
957381AF2-032 GEN
Solar/Wind Harmer
0.906
276785W4-005 GEN1
Solar/Wind Harmer
1.331
971993AH1-541 GEN
Solar/Wind Harmer
4.067
270330AC1-082 GEN2
Solar/Wind Helper
0.193
270329AC1-082 GEN1
Solar/Wind Helper
0.193
24803006KYGER 3HP
50/50
4.136
24802806KYGER 2HP
50/50
4.121
24802906KYGER 2LP
50/50
2.418
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.299
25183208HLCRTG
Solar/Wind Harmer
6.647
25194408D.CRK1
Adder
7.991
25194508D.CRK3
Adder
1.494
962581AG1-107 GEN
Solar/Wind Harmer
4.435
961491AF2-440 GEN
Solar/Wind Harmer
1.844
972043AH1-570 GEN
Solar/Wind Harmer
2.164
972045AH1-571 GEN
Solar/Wind Harmer
1.731
971125AH1-004 GEN
Solar/Wind Harmer
3.34
970107AG2-081 GEN
Solar/Wind Harmer
2.505
270269AC2-059
Solar/Wind Harmer
7.76
253415AE1-040 GEN
Solar/Wind Harmer
0.936
253370AE2-315 SEC1
Adder
1.629
25322209TAIT E
Adder
7.66
25322209TAIT E
Adder
7.488
253349AC2-067 GEN
Solar/Wind Harmer
1.584
253400AC2-068 GEN
Solar/Wind Harmer
0.637
25326109MON D
Adder
1.005
942891AE2-308 GEN
Solar/Wind Harmer
7.614
926881AC1-175 GEN
Solar/Wind Harmer
3.8
964571AG1-320 GEN
Solar/Wind Harmer
5.537
270383AD1-128 GEN
Solar/Wind Harmer
4.066
970883AG2-550 GEN
Solar/Wind Harmer
6.457
970885AG2-551 GEN
Solar/Wind Harmer
1.502
247621Y3-024
Adder
0.145
964611AG1-324 GEN
Solar/Wind Harmer
0.309
270201AC2-176 GEN
Solar/Wind Harmer
3.006
24725505WLD G2 C
Solar/Wind Harmer
2.27
24699105WLD G1 C
Solar/Wind Harmer
2.244
339236AF1-050_GEN
Solar/Wind Harmer
1.02
270031AE2-169
Solar/Wind Harmer
4.558
270599AE1-208 GEN
Solar/Wind Harmer
4.558
25326509SID D
Adder
0.702
339231AF1-038_GEN
Solar/Wind Harmer
0.965
945391AF1-204 GEN
Solar/Wind Harmer
7.373
944541AF1-119 GEN
Solar/Wind Harmer
2.19
960971AF2-388 GEN
Solar/Wind Harmer
5.716
964781AG1-341 GEN
Solar/Wind Harmer
5.52
970291AG2-192 GEN
Solar/Wind Harmer
0.661
970291AG2-192 GEN
Solar/Wind Harmer
0.213
253378AE2-206_GEN
Solar/Wind Harmer
1.774
971485AH1-239 GEN
Solar/Wind Harmer
3.886
942221AE2-234 GEN
Solar/Wind Harmer
1.69
966021AG1-471 GEN
Solar/Wind Harmer
2.588
970241AG2-163 GEN
Solar/Wind Harmer
11.574
276916AD2-100_GEN
Solar/Wind Harmer
9.604
276911AD2-131_GEN
Solar/Wind Harmer
1.941
276615X2-022 GEN
Solar/Wind Harmer
0.87
276838X2-022 GEN2
Solar/Wind Harmer
0.103
274880W4-005 GEN4
Solar/Wind Harmer
1.331
276174W4-005 GEN2
Solar/Wind Harmer
1.331
942861AE2-305 GEN
Solar/Wind Harmer
3.374
237033AB1-150 GEN
Solar/Wind Helper
0.386
270356AE2-297 GEN
Solar/Wind Harmer
3.35
971029AG2-637 GEN
Solar/Wind Harmer
10.129
241972AD1-140 GEN
Solar/Wind Harmer
2.94
270432AC2-029 GEN
Solar/Wind Harmer
4.54
270543AE2-219 C
Solar/Wind Harmer
6.457
270444AC2-157 GEN1
Solar/Wind Harmer
3.536
270445AC2-157 GEN2
Solar/Wind Harmer
3.536
247536S-71 GEN
Solar/Wind Harmer
2.502
964611AG1-324 GEN
Solar/Wind Harmer
2.301
961761AG1-017 GEN
Solar/Wind Harmer
0.25
253338AC1-165 GEN
Solar/Wind Harmer
0.633
253343AC1-166 GEN
Solar/Wind Harmer
0.633
945581AF1-223 GEN
Solar/Wind Harmer
2.541
958711AF2-162 GEN
Solar/Wind Harmer
0.529
970289AG2-191 GEN
Solar/Wind Harmer
0.966
24729505KEY G4
Adder
3.139
944221AF1-090 GEN
Solar/Wind Harmer
5.121
963841AG1-237 GEN
Solar/Wind Harmer
4.848
276763AC1-053 GEN1
Solar/Wind Harmer
1.744
276764AC1-053 GEN2
Solar/Wind Harmer
1.744
276668AB2-070 GEN1
Solar/Wind Harmer
0.974
276848AB2-070 GEN3
Solar/Wind Harmer
0.974
276849AB2-070 GEN2
Solar/Wind Harmer
0.974
943861AF1-054 GEN
Solar/Wind Harmer
1.665
943851AF1-053 GEN
Solar/Wind Harmer
0.805
LAGNLTFEXP_LAGN->PJM
CLTF
6.101
TVALTFEXP_TVA->PJM
CLTF
3.013
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
CBM West 1LTFEXP_CBM-W1->PJM
CBM
57.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.776
MECLTFEXP_MEC->PJM
CLTF
6.502
SIGELTFEXP_SIGE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.85
NYPJM->LTFIMP_NY
CLTF
1.477
LGEELTFEXP_LGEE->PJM
CLTF
5.581
WECLTFEXP_WEC->PJM
CLTF
1.413
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.272
AG2-052LTFEXP_AG2-052->PJM
LTF
0.09
AH1-155LTFEXP_AH1-155->PJM
LTF
0.135

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1558_05BAKER 765_Q_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1558_05BAKER 765_Q_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.58 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1872.34
MW Contribution:
6.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1558_05BAKER 765_Q_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.08 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2295.78
MW Contribution:
6.9
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.459
24803306KYGER 4LP
50/50
2.408
971191AH1-055 GEN
Solar/Wind Harmer
73.297
252507AC2-088 GEN
Solar/Wind Harmer
2.088
252519AF1-045_GEN
Solar/Wind Harmer
3.956
25194608D.CRK4
Adder
1.722
252524AE2-267 GEN
Solar/Wind Harmer
1.648
25196608WSDLE5
Adder
8.972
253317AC1-085 GEN4
Solar/Wind Harmer
8.691
946181AF1-283 GEN
Solar/Wind Harmer
13.495
958171AF2-111 GEN
Solar/Wind Harmer
24.929
25196008MFTGT1
Adder
1.339
253394AE2-221_GEN
Solar/Wind Harmer
4.427
972167AH1-666 GEN
Solar/Wind Harmer
7.467
270367AC2-061_GEN
Solar/Wind Harmer
2.92
270186AC1-089 GEN
Solar/Wind Harmer
5.527
339243AC2-075 GEN1
Solar/Wind Harmer
0.398
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.65
253371AE2-315 SEC2
Adder
1.56
960071AF2-298 GEN
Solar/Wind Harmer
1.19
3429391JKCT 9G
Adder
6.331
970093AG2-073 GEN
Solar/Wind Harmer
3.624
24379505HDWTR1G C
Solar/Wind Harmer
5.386
270240V3-007_GEN2
Solar/Wind Harmer
4.214
24728505AND G1
Adder
2.416
970455AG2-298 GEN
Solar/Wind Harmer
2.202
270004AE1-209 GEN
Solar/Wind Harmer
3.403
253325AC1-069 GEN
Solar/Wind Harmer
0.646
946031AF1-268 GEN
Solar/Wind Harmer
5.127
970825AG2-519 GEN
Solar/Wind Harmer
3.46
962031AG1-047 GEN
Solar/Wind Harmer
1.807
957741AF2-068 GEN
Solar/Wind Harmer
8.963
970653AG2-424 GEN
Solar/Wind Harmer
0.406
270518AE2-148 GEN
Solar/Wind Harmer
6.717
339206AE1-143 GEN
Solar/Wind Harmer
1.183
965461AG1-414 GEN
Solar/Wind Harmer
1.232
970289AG2-191 GEN
Solar/Wind Harmer
0.417
247642Z2-115 C
Solar/Wind Harmer
0.034
276820AF1-078_GEN
Solar/Wind Harmer
0.821
24802606KYGER 1HP
50/50
4.206
24802706KYGER 1LP
50/50
2.466
24803506KYGER 5LP
50/50
2.408
971985AH1-537 GEN
Solar/Wind Harmer
50.38
25196408WSDLE3
Adder
9.236
253433AC1-085 GEN1
Solar/Wind Harmer
5.516
253432AC1-085 GEN2
Solar/Wind Harmer
0.278
25196108MFTGT2
Adder
1.524
25196108MFTGT2
Adder
1.415
253406AD2-031_GEN
Solar/Wind Harmer
1.174
972163AH1-664 GEN
Solar/Wind Harmer
9.177
972165AH1-665 GEN
Solar/Wind Harmer
7.342
270263AC1-001 GEN
Solar/Wind Harmer
0.943
270340AC2-060 GEN
Solar/Wind Harmer
2.713
339216AC1-074 GEN
Solar/Wind Harmer
1.469
253372AE2-315 SEC3
Adder
1.56
253372AE2-315 SEC3
Adder
1.56
25306009OHH W.
Adder
2.331
3429211JKCT 2G
Adder
8.597
270356AE2-297 GEN
Solar/Wind Harmer
3.32
270432AC2-029 GEN
Solar/Wind Harmer
4.963
971029AG2-637 GEN
Solar/Wind Harmer
10.225
241972AD1-140 GEN
Solar/Wind Harmer
3.018
270543AE2-219 C
Solar/Wind Harmer
6.542
247536S-71 GEN
Solar/Wind Harmer
2.544
253338AC1-165 GEN
Solar/Wind Harmer
0.67
253343AC1-166 GEN
Solar/Wind Harmer
0.67
964611AG1-324 GEN
Solar/Wind Harmer
2.347
961761AG1-017 GEN
Solar/Wind Harmer
0.256
945581AF1-223 GEN
Solar/Wind Harmer
2.597
270444AC2-157 GEN1
Solar/Wind Harmer
3.034
270445AC2-157 GEN2
Solar/Wind Harmer
3.034
970289AG2-191 GEN
Solar/Wind Harmer
1.032
958711AF2-162 GEN
Solar/Wind Harmer
0.546
24729505KEY G4
Adder
3.282
963841AG1-237 GEN
Solar/Wind Harmer
5.056
945631AF1-228 GEN
Solar/Wind Harmer
2.147
943861AF1-054 GEN
Solar/Wind Harmer
1.763
943851AF1-053 GEN
Solar/Wind Harmer
0.852
963791AG1-232 GEN
Solar/Wind Harmer
6.128
24386405FR-21G C
Solar/Wind Harmer
1.939
24387005FR-3G C
Solar/Wind Harmer
1.783
944221AF1-090 GEN
Solar/Wind Harmer
4.903
276763AC1-053 GEN1
Solar/Wind Harmer
1.725
276764AC1-053 GEN2
Solar/Wind Harmer
1.725
276668AB2-070 GEN1
Solar/Wind Harmer
0.965
276848AB2-070 GEN3
Solar/Wind Harmer
0.965
276849AB2-070 GEN2
Solar/Wind Harmer
0.965
946581AF1-322 GEN
Solar/Wind Harmer
4.451
24691005MDL-2G C
Solar/Wind Harmer
1.609
24803406KYGER 5HP
50/50
4.128
24803206KYGER 4HP
50/50
4.118
252516AE2-318_GEN
Solar/Wind Harmer
10.869
25196808ZIMRHP
Adder
81.158
25194608D.CRK4
Adder
1.722
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.691
946171AF1-282 GEN
Solar/Wind Harmer
10.381
25196008MFTGT1
Adder
1.383
253398AE2-221_GEN2
Solar/Wind Harmer
4.427
945681AF1-233 GEN
Solar/Wind Harmer
17.516
270273AD2-016 GEN
Solar/Wind Harmer
2.397
339221AD2-048_GEN
Solar/Wind Harmer
1.32
270222AC2-111 GEN
Solar/Wind Harmer
3.68
944031AF1-071 GEN
Solar/Wind Harmer
0.828
253370AE2-315 SEC1
Adder
1.65
253371AE2-315 SEC2
Adder
1.56
25326309TAIT D
Adder
0.871
943111AE2-339 GEN
Solar/Wind Harmer
0.702
3429421JKCT 10G
Adder
6.331
3429241JKCT 3G
Adder
8.71
942081AE2-220 GEN
Solar/Wind Harmer
4.357
270209AC1-174_GEN
Solar/Wind Harmer
2.772
270437AC2-090 C
Solar/Wind Harmer
3.802
270239V3-007_GEN1
Solar/Wind Harmer
1.172
24728605AND G2
Adder
2.416
339211AE2-254 GEN
Solar/Wind Harmer
0.948
270005AE1-210 C O1
Solar/Wind Harmer
3.403
253333AC1-068 GEN
Solar/Wind Harmer
0.646
970825AG2-519 GEN
Solar/Wind Harmer
1.289
970091AG2-072 GEN
Adder
45.609
970653AG2-424 GEN
Solar/Wind Harmer
2.807
276903AD2-071 C
Solar/Wind Harmer
5.743
945371AF1-202 GEN
Solar/Wind Harmer
3.996
270594AE1-207 GEN
Solar/Wind Harmer
7.628
270032AE2-172
Solar/Wind Harmer
2.612
958861AF2-177 GEN
Solar/Wind Harmer
6.026
270024AE2-089 GEN
Solar/Wind Harmer
2.54
965651AG1-433 GEN
Solar/Wind Harmer
2.952
339241AF1-083 GEN
Solar/Wind Harmer
0.886
972203AH1-686 GEN
Adder
1.224
964901AG1-354 GEN
Solar/Wind Harmer
7.42
963741AG1-226 GEN
Solar/Wind Harmer
21.31
24385905FR-11G C
Solar/Wind Harmer
3.747
24386605FR-22G C
Solar/Wind Harmer
1.939
965911AG1-460 GEN
Solar/Wind Harmer
0.616
276621W2-048 GEN
Solar/Wind Harmer
2.728
276686W4-005 GEN3
Solar/Wind Harmer
1.319
24791305MDL-5G
Solar/Wind Harmer
1.049
960001AF2-291 GEN
Solar/Wind Helper
1.672
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.482
970193AG2-126 GEN
Solar/Wind Harmer
7.665
944531AF1-118 GEN
Solar/Wind Harmer
17.273
972273AH1-721 GEN
Adder
40.144
339255AE2-071 GEN
Solar/Wind Harmer
0.539
339250AF1-203 GEN
Solar/Wind Harmer
0.277
24386205FR-12G C
Solar/Wind Harmer
1.932
942481AE2-261 GEN
Solar/Wind Harmer
13.191
957381AF2-032 GEN
Solar/Wind Harmer
0.881
276785W4-005 GEN1
Solar/Wind Harmer
1.319
971993AH1-541 GEN
Solar/Wind Harmer
4.03
24690905MDL-1G C
Solar/Wind Harmer
3.492
970781AG2-491 GEN
Solar/Wind Harmer
4.35
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
24803006KYGER 3HP
50/50
4.176
24802806KYGER 2HP
50/50
4.16
24802906KYGER 2LP
50/50
2.442
25183008BIOENL
50/50
0.031
252509AD1-136 GEN
Solar/Wind Harmer
0.298
25183208HLCRTG
Solar/Wind Harmer
6.689
25194408D.CRK1
Adder
7.92
25194508D.CRK3
Adder
1.481
270269AC2-059
Solar/Wind Harmer
8.406
962581AG1-107 GEN
Solar/Wind Harmer
4.506
961491AF2-440 GEN
Solar/Wind Harmer
1.873
253415AE1-040 GEN
Solar/Wind Harmer
0.979
972043AH1-570 GEN
Solar/Wind Harmer
2.092
972045AH1-571 GEN
Solar/Wind Harmer
1.674
253370AE2-315 SEC1
Adder
1.65
971125AH1-004 GEN
Solar/Wind Harmer
3.204
970107AG2-081 GEN
Solar/Wind Harmer
2.403
25322209TAIT E
Adder
7.761
25322209TAIT E
Adder
7.587
253349AC2-067 GEN
Solar/Wind Harmer
1.601
253400AC2-068 GEN
Solar/Wind Harmer
0.644
25326109MON D
Adder
1.02
942891AE2-308 GEN
Solar/Wind Harmer
7.202
926881AC1-175 GEN
Solar/Wind Harmer
3.802
270383AD1-128 GEN
Solar/Wind Harmer
4.093
970883AG2-550 GEN
Solar/Wind Harmer
6.542
970885AG2-551 GEN
Solar/Wind Harmer
1.521
247621Y3-024
Adder
0.148
964571AG1-320 GEN
Solar/Wind Harmer
5.012
964611AG1-324 GEN
Solar/Wind Harmer
0.315
270201AC2-176 GEN
Solar/Wind Harmer
3.071
24725505WLD G2 C
Solar/Wind Harmer
2.34
24699105WLD G1 C
Solar/Wind Harmer
2.313
270031AE2-169
Solar/Wind Harmer
4.672
270599AE1-208 GEN
Solar/Wind Harmer
4.672
25326509SID D
Adder
0.727
970291AG2-192 GEN
Solar/Wind Harmer
0.706
970291AG2-192 GEN
Solar/Wind Harmer
0.227
944541AF1-119 GEN
Solar/Wind Harmer
2.261
960971AF2-388 GEN
Solar/Wind Harmer
5.903
253378AE2-206_GEN
Solar/Wind Harmer
1.848
945391AF1-204 GEN
Solar/Wind Harmer
7.122
942221AE2-234 GEN
Solar/Wind Harmer
1.774
339236AF1-050_GEN
Solar/Wind Harmer
0.907
970241AG2-163 GEN
Solar/Wind Harmer
11.839
339231AF1-038_GEN
Solar/Wind Harmer
0.852
942861AE2-305 GEN
Solar/Wind Harmer
3.571
964781AG1-341 GEN
Solar/Wind Harmer
4.844
24387305FR-4G C
Solar/Wind Harmer
2.29
966841AG1-555 GEN
Solar/Wind Harmer
1.132
276916AD2-100_GEN
Solar/Wind Harmer
9.299
276911AD2-131_GEN
Solar/Wind Harmer
1.879
276615X2-022 GEN
Solar/Wind Harmer
0.857
276838X2-022 GEN2
Solar/Wind Harmer
0.102
274880W4-005 GEN4
Solar/Wind Harmer
1.319
276174W4-005 GEN2
Solar/Wind Harmer
1.319
270180AB1-006 GEN1
Solar/Wind Harmer
3.129
24697605MDL-3G C
Solar/Wind Harmer
1.604
24755605MDL-5G
Solar/Wind Harmer
1.049
24697905MDL-4G C
Solar/Wind Harmer
0.998
270181AB1-006 GEN2
Solar/Wind Harmer
0.311
237033AB1-150 GEN
Solar/Wind Helper
0.389
LAGNLTFEXP_LAGN->PJM
CLTF
5.106
TVALTFEXP_TVA->PJM
CLTF
2.41
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.296
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.717
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.398
MECLTFEXP_MEC->PJM
CLTF
6.442
SIGELTFEXP_SIGE->PJM
CLTF
0.309
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.237
NYPJM->LTFIMP_NY
CLTF
1.475
LGEELTFEXP_LGEE->PJM
CLTF
5.052
WECLTFEXP_WEC->PJM
CLTF
1.492
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.65
AG2-052LTFEXP_AG2-052->PJM
LTF
0.097
AH1-155LTFEXP_AH1-155->PJM
LTF
0.146

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#309_05HANG R 765_B2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#309_05HANG R 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.32 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1868.38
MW Contribution:
6.53
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#309_05HANG R 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.69 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2289.82
MW Contribution:
6.88
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.127
24803206KYGER 4HP
50/50
4.117
252516AE2-318_GEN
Solar/Wind Harmer
10.863
24803006KYGER 3HP
50/50
4.175
24802806KYGER 2HP
50/50
4.16
24802906KYGER 2LP
50/50
2.441
25183008BIOENL
50/50
0.031
252509AD1-136 GEN
Solar/Wind Harmer
0.298
25183208HLCRTG
Solar/Wind Harmer
6.685
25194408D.CRK1
Adder
7.915
25194508D.CRK3
Adder
1.48
270269AC2-059
Solar/Wind Harmer
8.388
962581AG1-107 GEN
Solar/Wind Harmer
4.512
961491AF2-440 GEN
Solar/Wind Harmer
1.875
253415AE1-040 GEN
Solar/Wind Harmer
0.978
972043AH1-570 GEN
Solar/Wind Harmer
2.098
972045AH1-571 GEN
Solar/Wind Harmer
1.678
253370AE2-315 SEC1
Adder
1.648
971125AH1-004 GEN
Solar/Wind Harmer
3.214
970107AG2-081 GEN
Solar/Wind Harmer
2.411
25322209TAIT E
Adder
7.75
25322209TAIT E
Adder
7.575
253349AC2-067 GEN
Solar/Wind Harmer
1.598
253400AC2-068 GEN
Solar/Wind Harmer
0.643
25326109MON D
Adder
1.019
942891AE2-308 GEN
Solar/Wind Harmer
7.237
926881AC1-175 GEN
Solar/Wind Harmer
3.796
270383AD1-128 GEN
Solar/Wind Harmer
4.087
970883AG2-550 GEN
Solar/Wind Harmer
6.531
970885AG2-551 GEN
Solar/Wind Harmer
1.519
964571AG1-320 GEN
Solar/Wind Harmer
5.034
247621Y3-024
Adder
0.147
964611AG1-324 GEN
Solar/Wind Harmer
0.314
270201AC2-176 GEN
Solar/Wind Harmer
3.065
24725505WLD G2 C
Solar/Wind Harmer
2.336
24699105WLD G1 C
Solar/Wind Harmer
2.309
270031AE2-169
Solar/Wind Harmer
4.663
270599AE1-208 GEN
Solar/Wind Harmer
4.663
25326509SID D
Adder
0.725
970291AG2-192 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.227
944541AF1-119 GEN
Solar/Wind Harmer
2.256
960971AF2-388 GEN
Solar/Wind Harmer
5.889
253378AE2-206_GEN
Solar/Wind Harmer
1.841
945391AF1-204 GEN
Solar/Wind Harmer
7.115
942221AE2-234 GEN
Solar/Wind Harmer
1.77
339236AF1-050_GEN
Solar/Wind Harmer
0.915
25196808ZIMRHP
Adder
81.128
25194608D.CRK4
Adder
1.721
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.685
946171AF1-282 GEN
Solar/Wind Harmer
10.373
25196008MFTGT1
Adder
1.382
253398AE2-221_GEN2
Solar/Wind Harmer
4.423
945681AF1-233 GEN
Solar/Wind Harmer
17.553
270273AD2-016 GEN
Solar/Wind Harmer
2.392
339221AD2-048_GEN
Solar/Wind Harmer
1.323
270222AC2-111 GEN
Solar/Wind Harmer
3.676
944031AF1-071 GEN
Solar/Wind Harmer
0.827
253370AE2-315 SEC1
Adder
1.648
253371AE2-315 SEC2
Adder
1.558
943111AE2-339 GEN
Solar/Wind Harmer
0.704
25326309TAIT D
Adder
0.87
3429421JKCT 10G
Adder
6.355
3429241JKCT 3G
Adder
8.749
942081AE2-220 GEN
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
2.768
270437AC2-090 C
Solar/Wind Harmer
3.796
270239V3-007_GEN1
Solar/Wind Harmer
1.17
339211AE2-254 GEN
Solar/Wind Harmer
0.954
24728605AND G2
Adder
2.415
270005AE1-210 C O1
Solar/Wind Harmer
3.398
253333AC1-068 GEN
Solar/Wind Harmer
0.644
970825AG2-519 GEN
Solar/Wind Harmer
1.287
970091AG2-072 GEN
Adder
45.51
970653AG2-424 GEN
Solar/Wind Harmer
2.823
276903AD2-071 C
Solar/Wind Harmer
5.733
945371AF1-202 GEN
Solar/Wind Harmer
3.988
270594AE1-207 GEN
Solar/Wind Harmer
7.612
270032AE2-172
Solar/Wind Harmer
2.607
958861AF2-177 GEN
Solar/Wind Harmer
6.012
270024AE2-089 GEN
Solar/Wind Harmer
2.534
965651AG1-433 GEN
Solar/Wind Harmer
2.945
339241AF1-083 GEN
Solar/Wind Harmer
0.893
972203AH1-686 GEN
Adder
1.213
964901AG1-354 GEN
Solar/Wind Harmer
7.489
963741AG1-226 GEN
Solar/Wind Harmer
21.272
24385905FR-11G C
Solar/Wind Harmer
3.737
24386605FR-22G C
Solar/Wind Harmer
1.934
965911AG1-460 GEN
Solar/Wind Harmer
0.616
276621W2-048 GEN
Solar/Wind Harmer
2.728
276686W4-005 GEN3
Solar/Wind Harmer
1.319
24791305MDL-5G
Solar/Wind Harmer
1.046
960001AF2-291 GEN
Solar/Wind Helper
1.673
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.482
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.465
24803506KYGER 5LP
50/50
2.408
971985AH1-537 GEN
Solar/Wind Harmer
50.362
25196408WSDLE3
Adder
9.229
253433AC1-085 GEN1
Solar/Wind Harmer
5.512
253432AC1-085 GEN2
Solar/Wind Harmer
0.277
25196108MFTGT2
Adder
1.523
25196108MFTGT2
Adder
1.414
972163AH1-664 GEN
Solar/Wind Harmer
9.198
972165AH1-665 GEN
Solar/Wind Harmer
7.358
253406AD2-031_GEN
Solar/Wind Harmer
1.174
270263AC1-001 GEN
Solar/Wind Harmer
0.941
270340AC2-060 GEN
Solar/Wind Harmer
2.71
339216AC1-074 GEN
Solar/Wind Harmer
1.472
253372AE2-315 SEC3
Adder
1.558
253372AE2-315 SEC3
Adder
1.558
25306009OHH W.
Adder
2.328
3429211JKCT 2G
Adder
8.636
270356AE2-297 GEN
Solar/Wind Harmer
3.317
270432AC2-029 GEN
Solar/Wind Harmer
4.949
971029AG2-637 GEN
Solar/Wind Harmer
10.209
241972AD1-140 GEN
Solar/Wind Harmer
3.011
270543AE2-219 C
Solar/Wind Harmer
6.531
247536S-71 GEN
Solar/Wind Harmer
2.539
253338AC1-165 GEN
Solar/Wind Harmer
0.668
253343AC1-166 GEN
Solar/Wind Harmer
0.668
964611AG1-324 GEN
Solar/Wind Harmer
2.343
961761AG1-017 GEN
Solar/Wind Harmer
0.255
945581AF1-223 GEN
Solar/Wind Harmer
2.592
270444AC2-157 GEN1
Solar/Wind Harmer
3.031
270445AC2-157 GEN2
Solar/Wind Harmer
3.031
970289AG2-191 GEN
Solar/Wind Harmer
1.03
958711AF2-162 GEN
Solar/Wind Harmer
0.545
24729505KEY G4
Adder
3.273
963841AG1-237 GEN
Solar/Wind Harmer
5.045
945631AF1-228 GEN
Solar/Wind Harmer
2.136
943861AF1-054 GEN
Solar/Wind Harmer
1.755
943851AF1-053 GEN
Solar/Wind Harmer
0.848
963791AG1-232 GEN
Solar/Wind Harmer
6.108
24386405FR-21G C
Solar/Wind Harmer
1.934
24387005FR-3G C
Solar/Wind Harmer
1.779
944221AF1-090 GEN
Solar/Wind Harmer
4.906
276763AC1-053 GEN1
Solar/Wind Harmer
1.725
276764AC1-053 GEN2
Solar/Wind Harmer
1.725
276668AB2-070 GEN1
Solar/Wind Harmer
0.965
276848AB2-070 GEN3
Solar/Wind Harmer
0.965
276849AB2-070 GEN2
Solar/Wind Harmer
0.965
946581AF1-322 GEN
Solar/Wind Harmer
4.438
24691005MDL-2G C
Solar/Wind Harmer
1.604
24803106KYGER 3LP
50/50
2.459
24803306KYGER 4LP
50/50
2.408
971191AH1-055 GEN
Solar/Wind Harmer
73.271
252507AC2-088 GEN
Solar/Wind Harmer
2.087
252519AF1-045_GEN
Solar/Wind Harmer
3.954
25194608D.CRK4
Adder
1.721
252524AE2-267 GEN
Solar/Wind Harmer
1.647
25196608WSDLE5
Adder
8.965
253317AC1-085 GEN4
Solar/Wind Harmer
8.685
946181AF1-283 GEN
Solar/Wind Harmer
13.485
958171AF2-111 GEN
Solar/Wind Harmer
24.946
25196008MFTGT1
Adder
1.338
253394AE2-221_GEN
Solar/Wind Harmer
4.423
972167AH1-666 GEN
Solar/Wind Harmer
7.482
270367AC2-061_GEN
Solar/Wind Harmer
2.924
270186AC1-089 GEN
Solar/Wind Harmer
5.537
339243AC2-075 GEN1
Solar/Wind Harmer
0.399
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.648
253371AE2-315 SEC2
Adder
1.558
960071AF2-298 GEN
Solar/Wind Harmer
1.188
3429391JKCT 9G
Adder
6.355
970093AG2-073 GEN
Solar/Wind Harmer
3.645
24379505HDWTR1G C
Solar/Wind Harmer
5.379
270240V3-007_GEN2
Solar/Wind Harmer
4.208
970455AG2-298 GEN
Solar/Wind Harmer
2.212
24728505AND G1
Adder
2.415
270004AE1-209 GEN
Solar/Wind Harmer
3.398
253325AC1-069 GEN
Solar/Wind Harmer
0.644
946031AF1-268 GEN
Solar/Wind Harmer
5.118
970825AG2-519 GEN
Solar/Wind Harmer
3.455
962031AG1-047 GEN
Solar/Wind Harmer
1.803
957741AF2-068 GEN
Solar/Wind Harmer
8.946
970653AG2-424 GEN
Solar/Wind Harmer
0.408
339206AE1-143 GEN
Solar/Wind Harmer
1.192
270518AE2-148 GEN
Solar/Wind Harmer
6.693
965461AG1-414 GEN
Solar/Wind Harmer
1.229
970289AG2-191 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.034
276820AF1-078_GEN
Solar/Wind Harmer
0.818
970193AG2-126 GEN
Solar/Wind Harmer
7.659
944531AF1-118 GEN
Solar/Wind Harmer
17.224
972273AH1-721 GEN
Adder
40.637
339255AE2-071 GEN
Solar/Wind Harmer
0.544
339250AF1-203 GEN
Solar/Wind Harmer
0.28
24386205FR-12G C
Solar/Wind Harmer
1.927
942481AE2-261 GEN
Solar/Wind Harmer
13.196
957381AF2-032 GEN
Solar/Wind Harmer
0.881
276785W4-005 GEN1
Solar/Wind Harmer
1.319
971993AH1-541 GEN
Solar/Wind Harmer
4.029
24690905MDL-1G C
Solar/Wind Harmer
3.482
970781AG2-491 GEN
Solar/Wind Harmer
4.338
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
339231AF1-038_GEN
Solar/Wind Harmer
0.862
970241AG2-163 GEN
Solar/Wind Harmer
11.818
964781AG1-341 GEN
Solar/Wind Harmer
4.895
942861AE2-305 GEN
Solar/Wind Harmer
3.555
24387305FR-4G C
Solar/Wind Harmer
2.284
966841AG1-555 GEN
Solar/Wind Harmer
1.129
276916AD2-100_GEN
Solar/Wind Harmer
9.304
276911AD2-131_GEN
Solar/Wind Harmer
1.88
276615X2-022 GEN
Solar/Wind Harmer
0.857
276838X2-022 GEN2
Solar/Wind Harmer
0.102
274880W4-005 GEN4
Solar/Wind Harmer
1.319
276174W4-005 GEN2
Solar/Wind Harmer
1.319
270180AB1-006 GEN1
Solar/Wind Harmer
3.12
24697605MDL-3G C
Solar/Wind Harmer
1.599
24755605MDL-5G
Solar/Wind Harmer
1.046
24697905MDL-4G C
Solar/Wind Harmer
0.995
270181AB1-006 GEN2
Solar/Wind Harmer
0.31
237033AB1-150 GEN
Solar/Wind Helper
0.389
LAGNLTFEXP_LAGN->PJM
CLTF
5.217
TVALTFEXP_TVA->PJM
CLTF
2.479
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.262
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.663
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.617
MECLTFEXP_MEC->PJM
CLTF
6.459
SIGELTFEXP_SIGE->PJM
CLTF
0.31
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.694
NYPJM->LTFIMP_NY
CLTF
1.479
LGEELTFEXP_LGEE->PJM
CLTF
5.06
WECLTFEXP_WEC->PJM
CLTF
1.491
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.097
AH1-155LTFEXP_AH1-155->PJM
LTF
0.145

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1560_05BAKER 765_Q2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.04 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1864.08
MW Contribution:
6.53
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.55 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2287.64
MW Contribution:
6.88
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.203
24802706KYGER 1LP
50/50
2.464
24803506KYGER 5LP
50/50
2.407
971985AH1-537 GEN
Solar/Wind Harmer
50.336
25196408WSDLE3
Adder
9.22
253433AC1-085 GEN1
Solar/Wind Harmer
5.507
253432AC1-085 GEN2
Solar/Wind Harmer
0.277
25196108MFTGT2
Adder
1.522
25196108MFTGT2
Adder
1.413
253406AD2-031_GEN
Solar/Wind Harmer
1.172
972163AH1-664 GEN
Solar/Wind Harmer
9.178
972165AH1-665 GEN
Solar/Wind Harmer
7.342
270263AC1-001 GEN
Solar/Wind Harmer
0.94
270340AC2-060 GEN
Solar/Wind Harmer
2.706
339216AC1-074 GEN
Solar/Wind Harmer
1.47
253372AE2-315 SEC3
Adder
1.557
253372AE2-315 SEC3
Adder
1.557
25306009OHH W.
Adder
2.325
3429211JKCT 2G
Adder
8.623
270356AE2-297 GEN
Solar/Wind Harmer
3.314
270432AC2-029 GEN
Solar/Wind Harmer
4.942
971029AG2-637 GEN
Solar/Wind Harmer
10.199
241972AD1-140 GEN
Solar/Wind Harmer
3.007
270543AE2-219 C
Solar/Wind Harmer
6.525
247536S-71 GEN
Solar/Wind Harmer
2.537
253338AC1-165 GEN
Solar/Wind Harmer
0.667
253343AC1-166 GEN
Solar/Wind Harmer
0.667
964611AG1-324 GEN
Solar/Wind Harmer
2.341
961761AG1-017 GEN
Solar/Wind Harmer
0.255
945581AF1-223 GEN
Solar/Wind Harmer
2.59
270444AC2-157 GEN1
Solar/Wind Harmer
3.029
270445AC2-157 GEN2
Solar/Wind Harmer
3.029
970289AG2-191 GEN
Solar/Wind Harmer
1.029
958711AF2-162 GEN
Solar/Wind Harmer
0.545
24729505KEY G4
Adder
3.27
963841AG1-237 GEN
Solar/Wind Harmer
5.041
945631AF1-228 GEN
Solar/Wind Harmer
2.133
943861AF1-054 GEN
Solar/Wind Harmer
1.752
943851AF1-053 GEN
Solar/Wind Harmer
0.847
963791AG1-232 GEN
Solar/Wind Harmer
6.102
24386405FR-21G C
Solar/Wind Harmer
1.932
24387005FR-3G C
Solar/Wind Harmer
1.777
944221AF1-090 GEN
Solar/Wind Harmer
4.903
24803406KYGER 5HP
50/50
4.125
24803206KYGER 4HP
50/50
4.116
252516AE2-318_GEN
Solar/Wind Harmer
10.852
25196808ZIMRHP
Adder
81.048
25194608D.CRK4
Adder
1.719
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.675
946171AF1-282 GEN
Solar/Wind Harmer
10.363
25196008MFTGT1
Adder
1.381
253398AE2-221_GEN2
Solar/Wind Harmer
4.418
945681AF1-233 GEN
Solar/Wind Harmer
17.515
270273AD2-016 GEN
Solar/Wind Harmer
2.389
339221AD2-048_GEN
Solar/Wind Harmer
1.321
270222AC2-111 GEN
Solar/Wind Harmer
3.672
944031AF1-071 GEN
Solar/Wind Harmer
0.826
253370AE2-315 SEC1
Adder
1.646
253371AE2-315 SEC2
Adder
1.557
943111AE2-339 GEN
Solar/Wind Harmer
0.703
25326309TAIT D
Adder
0.869
3429421JKCT 10G
Adder
6.347
3429241JKCT 3G
Adder
8.736
942081AE2-220 GEN
Solar/Wind Harmer
4.346
270209AC1-174_GEN
Solar/Wind Harmer
2.766
270437AC2-090 C
Solar/Wind Harmer
3.793
270239V3-007_GEN1
Solar/Wind Harmer
1.169
339211AE2-254 GEN
Solar/Wind Harmer
0.953
24728605AND G2
Adder
2.412
270005AE1-210 C O1
Solar/Wind Harmer
3.395
253333AC1-068 GEN
Solar/Wind Harmer
0.643
970825AG2-519 GEN
Solar/Wind Harmer
1.285
970091AG2-072 GEN
Adder
45.472
970653AG2-424 GEN
Solar/Wind Harmer
2.821
276903AD2-071 C
Solar/Wind Harmer
5.727
945371AF1-202 GEN
Solar/Wind Harmer
3.984
270594AE1-207 GEN
Solar/Wind Harmer
7.604
270032AE2-172
Solar/Wind Harmer
2.604
958861AF2-177 GEN
Solar/Wind Harmer
6.007
270024AE2-089 GEN
Solar/Wind Harmer
2.531
965651AG1-433 GEN
Solar/Wind Harmer
2.942
339241AF1-083 GEN
Solar/Wind Harmer
0.892
972203AH1-686 GEN
Adder
1.212
964901AG1-354 GEN
Solar/Wind Harmer
7.485
963741AG1-226 GEN
Solar/Wind Harmer
21.254
24385905FR-11G C
Solar/Wind Harmer
3.734
24386605FR-22G C
Solar/Wind Harmer
1.932
965911AG1-460 GEN
Solar/Wind Harmer
0.615
276621W2-048 GEN
Solar/Wind Harmer
2.726
276686W4-005 GEN3
Solar/Wind Harmer
1.318
24791305MDL-5G
Solar/Wind Harmer
1.045
960001AF2-291 GEN
Solar/Wind Helper
1.677
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.483
276763AC1-053 GEN1
Solar/Wind Harmer
1.724
276764AC1-053 GEN2
Solar/Wind Harmer
1.724
276668AB2-070 GEN1
Solar/Wind Harmer
0.964
276848AB2-070 GEN3
Solar/Wind Harmer
0.964
276849AB2-070 GEN2
Solar/Wind Harmer
0.964
946581AF1-322 GEN
Solar/Wind Harmer
4.434
24691005MDL-2G C
Solar/Wind Harmer
1.603
24803106KYGER 3LP
50/50
2.458
24803306KYGER 4LP
50/50
2.407
971191AH1-055 GEN
Solar/Wind Harmer
73.235
252507AC2-088 GEN
Solar/Wind Harmer
2.085
252519AF1-045_GEN
Solar/Wind Harmer
3.95
25194608D.CRK4
Adder
1.719
252524AE2-267 GEN
Solar/Wind Harmer
1.646
25196608WSDLE5
Adder
8.957
253317AC1-085 GEN4
Solar/Wind Harmer
8.675
946181AF1-283 GEN
Solar/Wind Harmer
13.471
958171AF2-111 GEN
Solar/Wind Harmer
24.917
25196008MFTGT1
Adder
1.337
253394AE2-221_GEN
Solar/Wind Harmer
4.418
972167AH1-666 GEN
Solar/Wind Harmer
7.466
270367AC2-061_GEN
Solar/Wind Harmer
2.916
270186AC1-089 GEN
Solar/Wind Harmer
5.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.398
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.646
253371AE2-315 SEC2
Adder
1.557
960071AF2-298 GEN
Solar/Wind Harmer
1.187
3429391JKCT 9G
Adder
6.347
970093AG2-073 GEN
Solar/Wind Harmer
3.638
24379505HDWTR1G C
Solar/Wind Harmer
5.374
270240V3-007_GEN2
Solar/Wind Harmer
4.204
970455AG2-298 GEN
Solar/Wind Harmer
2.21
24803006KYGER 3HP
50/50
4.173
24802806KYGER 2HP
50/50
4.158
24802906KYGER 2LP
50/50
2.44
25183008BIOENL
50/50
0.031
252509AD1-136 GEN
Solar/Wind Harmer
0.298
25183208HLCRTG
Solar/Wind Harmer
6.678
25194408D.CRK1
Adder
7.907
24728505AND G1
Adder
2.412
270004AE1-209 GEN
Solar/Wind Harmer
3.395
253325AC1-069 GEN
Solar/Wind Harmer
0.643
946031AF1-268 GEN
Solar/Wind Harmer
5.113
970825AG2-519 GEN
Solar/Wind Harmer
3.451
962031AG1-047 GEN
Solar/Wind Harmer
1.802
957741AF2-068 GEN
Solar/Wind Harmer
8.938
970653AG2-424 GEN
Solar/Wind Harmer
0.408
339206AE1-143 GEN
Solar/Wind Harmer
1.191
270518AE2-148 GEN
Solar/Wind Harmer
6.685
965461AG1-414 GEN
Solar/Wind Harmer
1.228
970289AG2-191 GEN
Solar/Wind Harmer
0.415
247642Z2-115 C
Solar/Wind Harmer
0.034
276820AF1-078_GEN
Solar/Wind Harmer
0.817
970193AG2-126 GEN
Solar/Wind Harmer
7.653
944531AF1-118 GEN
Solar/Wind Harmer
17.208
972273AH1-721 GEN
Adder
40.6
339255AE2-071 GEN
Solar/Wind Harmer
0.544
339250AF1-203 GEN
Solar/Wind Harmer
0.28
24386205FR-12G C
Solar/Wind Harmer
1.925
942481AE2-261 GEN
Solar/Wind Harmer
13.188
957381AF2-032 GEN
Solar/Wind Harmer
0.881
276785W4-005 GEN1
Solar/Wind Harmer
1.318
971993AH1-541 GEN
Solar/Wind Harmer
4.027
24690905MDL-1G C
Solar/Wind Harmer
3.479
970781AG2-491 GEN
Solar/Wind Harmer
4.334
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
25194508D.CRK3
Adder
1.478
270269AC2-059
Solar/Wind Harmer
8.376
962581AG1-107 GEN
Solar/Wind Harmer
4.499
961491AF2-440 GEN
Solar/Wind Harmer
1.87
253415AE1-040 GEN
Solar/Wind Harmer
0.977
972043AH1-570 GEN
Solar/Wind Harmer
2.094
972045AH1-571 GEN
Solar/Wind Harmer
1.675
253370AE2-315 SEC1
Adder
1.646
971125AH1-004 GEN
Solar/Wind Harmer
3.21
970107AG2-081 GEN
Solar/Wind Harmer
2.407
25322209TAIT E
Adder
7.741
25322209TAIT E
Adder
7.567
253349AC2-067 GEN
Solar/Wind Harmer
1.597
253400AC2-068 GEN
Solar/Wind Harmer
0.642
25326109MON D
Adder
1.017
942891AE2-308 GEN
Solar/Wind Harmer
7.225
926881AC1-175 GEN
Solar/Wind Harmer
3.793
270383AD1-128 GEN
Solar/Wind Harmer
4.083
970883AG2-550 GEN
Solar/Wind Harmer
6.525
970885AG2-551 GEN
Solar/Wind Harmer
1.517
964571AG1-320 GEN
Solar/Wind Harmer
5.03
247621Y3-024
Adder
0.147
964611AG1-324 GEN
Solar/Wind Harmer
0.314
270201AC2-176 GEN
Solar/Wind Harmer
3.062
24725505WLD G2 C
Solar/Wind Harmer
2.334
24699105WLD G1 C
Solar/Wind Harmer
2.307
270031AE2-169
Solar/Wind Harmer
4.658
270599AE1-208 GEN
Solar/Wind Harmer
4.658
25326509SID D
Adder
0.724
970291AG2-192 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.227
944541AF1-119 GEN
Solar/Wind Harmer
2.254
960971AF2-388 GEN
Solar/Wind Harmer
5.884
253378AE2-206_GEN
Solar/Wind Harmer
1.839
945391AF1-204 GEN
Solar/Wind Harmer
7.11
942221AE2-234 GEN
Solar/Wind Harmer
1.768
339236AF1-050_GEN
Solar/Wind Harmer
0.914
339231AF1-038_GEN
Solar/Wind Harmer
0.862
970241AG2-163 GEN
Solar/Wind Harmer
11.808
964781AG1-341 GEN
Solar/Wind Harmer
4.893
942861AE2-305 GEN
Solar/Wind Harmer
3.55
24387305FR-4G C
Solar/Wind Harmer
2.282
966841AG1-555 GEN
Solar/Wind Harmer
1.128
276916AD2-100_GEN
Solar/Wind Harmer
9.298
276911AD2-131_GEN
Solar/Wind Harmer
1.879
276615X2-022 GEN
Solar/Wind Harmer
0.856
276838X2-022 GEN2
Solar/Wind Harmer
0.102
274880W4-005 GEN4
Solar/Wind Harmer
1.318
276174W4-005 GEN2
Solar/Wind Harmer
1.318
270180AB1-006 GEN1
Solar/Wind Harmer
3.117
24697605MDL-3G C
Solar/Wind Harmer
1.598
24755605MDL-5G
Solar/Wind Harmer
1.045
24697905MDL-4G C
Solar/Wind Harmer
0.994
270181AB1-006 GEN2
Solar/Wind Harmer
0.31
237033AB1-150 GEN
Solar/Wind Helper
0.389
LAGNLTFEXP_LAGN->PJM
CLTF
5.225
TVALTFEXP_TVA->PJM
CLTF
2.484
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.256
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.621
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.627
MECLTFEXP_MEC->PJM
CLTF
6.456
SIGELTFEXP_SIGE->PJM
CLTF
0.31
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.702
NYPJM->LTFIMP_NY
CLTF
1.475
LGEELTFEXP_LGEE->PJM
CLTF
5.055
WECLTFEXP_WEC->PJM
CLTF
1.49
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.592
AG2-052LTFEXP_AG2-052->PJM
LTF
0.097
AH1-155LTFEXP_AH1-155->PJM
LTF
0.145

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#6156_05MARQUI 765_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6156_05MARQUI 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.75 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1859.53
MW Contribution:
7.87
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.427
24803206KYGER 4HP
50/50
4.417
253316AC1-085 GEN3
Solar/Wind Harmer
11.619
946171AF1-282 GEN
Solar/Wind Harmer
13.878
252516AE2-318_GEN
Solar/Wind Harmer
13.842
270273AD2-016 GEN
Solar/Wind Harmer
3.619
25196808ZIMRHP
Adder
103.16
252510AF1-249 C
Solar/Wind Harmer
0.548
25194608D.CRK4
Adder
2.154
253398AE2-221_GEN2
Solar/Wind Harmer
5.885
945681AF1-233 GEN
Solar/Wind Harmer
22.912
25196008MFTGT1
Adder
1.689
339221AD2-048_GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.137
253371AE2-315 SEC2
Adder
2.021
25326309TAIT D
Adder
1.127
270222AC2-111 GEN
Solar/Wind Harmer
4.52
944031AF1-071 GEN
Solar/Wind Harmer
1.017
943111AE2-339 GEN
Solar/Wind Harmer
0.883
3429421JKCT 10G
Adder
7.969
3429241JKCT 3G
Adder
10.939
253333AC1-068 GEN
Solar/Wind Harmer
0.905
942081AE2-220 GEN
Solar/Wind Harmer
5.172
270209AC1-174_GEN
Solar/Wind Harmer
3.291
270437AC2-090 C
Solar/Wind Harmer
4.513
270239V3-007_GEN1
Solar/Wind Harmer
1.391
339211AE2-254 GEN
Solar/Wind Harmer
1.15
270005AE1-210 C O1
Solar/Wind Harmer
4.013
970825AG2-519 GEN
Solar/Wind Harmer
1.517
24728605AND G2
Adder
2.773
971073AG2-665 GEN
Solar/Wind Harmer
0.806
970653AG2-424 GEN
Solar/Wind Harmer
3.256
945371AF1-202 GEN
Solar/Wind Harmer
4.707
276903AD2-071 C
Solar/Wind Harmer
6.601
958861AF2-177 GEN
Solar/Wind Harmer
7.096
270594AE1-207 GEN
Solar/Wind Harmer
8.773
270032AE2-172
Solar/Wind Harmer
3.005
270024AE2-089 GEN
Solar/Wind Harmer
3.017
965651AG1-433 GEN
Solar/Wind Harmer
3.475
339241AF1-083 GEN
Solar/Wind Harmer
1.04
964901AG1-354 GEN
Solar/Wind Harmer
8.626
970091AG2-072 GEN
Adder
38.834
963741AG1-226 GEN
Solar/Wind Harmer
22.53
24385905FR-11G C
Solar/Wind Harmer
3.949
24386605FR-22G C
Solar/Wind Harmer
2.043
965911AG1-460 GEN
Solar/Wind Harmer
0.657
276621W2-048 GEN
Solar/Wind Harmer
2.918
276686W4-005 GEN3
Solar/Wind Harmer
1.412
24791305MDL-5G
Solar/Wind Harmer
1.108
960001AF2-291 GEN
Solar/Wind Helper
1.492
24803106KYGER 3LP
50/50
2.637
24803306KYGER 4LP
50/50
2.583
971191AH1-055 GEN
Solar/Wind Harmer
85.195
252507AC2-088 GEN
Solar/Wind Harmer
2.655
253317AC1-085 GEN4
Solar/Wind Harmer
11.619
946181AF1-283 GEN
Solar/Wind Harmer
18.042
252519AF1-045_GEN
Solar/Wind Harmer
5.038
25194608D.CRK4
Adder
2.154
252524AE2-267 GEN
Solar/Wind Harmer
2.058
25196608WSDLE5
Adder
11.2
958171AF2-111 GEN
Solar/Wind Harmer
32.628
253394AE2-221_GEN
Solar/Wind Harmer
5.885
270367AC2-061_GEN
Solar/Wind Harmer
3.949
270186AC1-089 GEN
Solar/Wind Harmer
7.462
972167AH1-666 GEN
Solar/Wind Harmer
9.768
25196008MFTGT1
Adder
1.636
339243AC2-075 GEN1
Solar/Wind Harmer
0.501
253303V4-073 C
Solar/Wind Harmer
0.124
253370AE2-315 SEC1
Adder
2.137
253371AE2-315 SEC2
Adder
2.021
960071AF2-298 GEN
Solar/Wind Harmer
1.535
3429391JKCT 9G
Adder
7.969
253325AC1-069 GEN
Solar/Wind Harmer
0.905
970093AG2-073 GEN
Solar/Wind Harmer
4.511
24379505HDWTR1G C
Solar/Wind Harmer
6.394
270240V3-007_GEN2
Solar/Wind Harmer
5.003
270518AE2-148 GEN
Solar/Wind Harmer
9.208
970455AG2-298 GEN
Solar/Wind Harmer
2.574
270004AE1-209 GEN
Solar/Wind Harmer
4.013
946031AF1-268 GEN
Solar/Wind Harmer
6.057
970825AG2-519 GEN
Solar/Wind Harmer
4.074
24728505AND G1
Adder
2.773
962031AG1-047 GEN
Solar/Wind Harmer
2.146
957741AF2-068 GEN
Solar/Wind Harmer
10.645
970879AG2-548 GEN
Solar/Wind Harmer
5.548
276820AF1-078_GEN
Solar/Wind Harmer
1.082
24803006KYGER 3HP
50/50
4.479
24802806KYGER 2HP
50/50
4.462
24802906KYGER 2LP
50/50
2.619
25183008BIOENL
50/50
0.04
252509AD1-136 GEN
Solar/Wind Harmer
0.379
25183208HLCRTG
Solar/Wind Harmer
8.672
270269AC2-059
Solar/Wind Harmer
12.691
25194408D.CRK1
Adder
9.908
25194508D.CRK3
Adder
1.852
253415AE1-040 GEN
Solar/Wind Harmer
1.385
962581AG1-107 GEN
Solar/Wind Harmer
6.11
961491AF2-440 GEN
Solar/Wind Harmer
2.54
253370AE2-315 SEC1
Adder
2.137
972043AH1-570 GEN
Solar/Wind Harmer
2.652
972045AH1-571 GEN
Solar/Wind Harmer
2.122
25322209TAIT E
Adder
10.038
25322209TAIT E
Adder
9.812
253349AC2-067 GEN
Solar/Wind Harmer
2.05
253400AC2-068 GEN
Solar/Wind Harmer
0.824
971125AH1-004 GEN
Solar/Wind Harmer
4.03
970107AG2-081 GEN
Solar/Wind Harmer
3.023
25326109MON D
Adder
1.324
942891AE2-308 GEN
Solar/Wind Harmer
9.002
926881AC1-175 GEN
Solar/Wind Harmer
4.513
270383AD1-128 GEN
Solar/Wind Harmer
4.887
970883AG2-550 GEN
Solar/Wind Harmer
7.87
970885AG2-551 GEN
Solar/Wind Harmer
1.83
247621Y3-024
Adder
0.176
25326509SID D
Adder
0.951
964611AG1-324 GEN
Solar/Wind Harmer
0.374
270201AC2-176 GEN
Solar/Wind Harmer
3.648
964571AG1-320 GEN
Solar/Wind Harmer
5.767
971073AG2-665 GEN
Solar/Wind Harmer
5.548
970879AG2-548 GEN
Solar/Wind Harmer
0.806
24725505WLD G2 C
Solar/Wind Harmer
2.701
24699105WLD G1 C
Solar/Wind Harmer
2.67
253378AE2-206_GEN
Solar/Wind Harmer
2.436
270031AE2-169
Solar/Wind Harmer
5.48
270599AE1-208 GEN
Solar/Wind Harmer
5.48
944541AF1-119 GEN
Solar/Wind Harmer
2.663
960971AF2-388 GEN
Solar/Wind Harmer
6.95
942861AE2-305 GEN
Solar/Wind Harmer
4.917
970291AG2-192 GEN
Solar/Wind Harmer
0.805
970291AG2-192 GEN
Solar/Wind Harmer
0.259
942221AE2-234 GEN
Solar/Wind Harmer
2.089
339236AF1-050_GEN
Solar/Wind Harmer
1.055
339231AF1-038_GEN
Solar/Wind Harmer
1.008
927014AC1-188 GEN
Solar/Wind Harmer
0.859
945391AF1-204 GEN
Solar/Wind Harmer
7.563
964781AG1-341 GEN
Solar/Wind Harmer
5.576
253383AE2-342_GEN
Solar/Wind Harmer
0.458
970241AG2-163 GEN
Solar/Wind Harmer
12.517
971485AH1-239 GEN
Solar/Wind Harmer
3.96
966021AG1-471 GEN
Solar/Wind Harmer
2.631
24387305FR-4G C
Solar/Wind Harmer
2.413
966841AG1-555 GEN
Solar/Wind Harmer
1.193
276916AD2-100_GEN
Solar/Wind Harmer
9.913
276911AD2-131_GEN
Solar/Wind Harmer
2.003
276615X2-022 GEN
Solar/Wind Harmer
0.916
276838X2-022 GEN2
Solar/Wind Harmer
0.109
274880W4-005 GEN4
Solar/Wind Harmer
1.412
276174W4-005 GEN2
Solar/Wind Harmer
1.412
270180AB1-006 GEN1
Solar/Wind Harmer
3.305
24697605MDL-3G C
Solar/Wind Harmer
1.694
24755605MDL-5G
Solar/Wind Harmer
1.108
24697905MDL-4G C
Solar/Wind Harmer
1.055
270181AB1-006 GEN2
Solar/Wind Harmer
0.329
237033AB1-150 GEN
Solar/Wind Helper
0.424
970653AG2-424 GEN
Solar/Wind Harmer
0.471
339206AE1-143 GEN
Solar/Wind Harmer
1.398
965461AG1-414 GEN
Solar/Wind Harmer
1.404
970289AG2-191 GEN
Solar/Wind Harmer
0.475
247642Z2-115 C
Solar/Wind Harmer
0.038
942051AE2-217 GEN
Solar/Wind Harmer
10.648
960801AF2-371 GEN
Solar/Wind Harmer
1.494
964871AG1-351 GEN
Solar/Wind Harmer
1.032
944531AF1-118 GEN
Solar/Wind Harmer
20.315
972273AH1-721 GEN
Adder
48.249
957541AF2-048 GEN
Solar/Wind Harmer
0.859
970193AG2-126 GEN
Solar/Wind Harmer
8.141
339255AE2-071 GEN
Solar/Wind Harmer
0.622
339250AF1-203 GEN
Solar/Wind Harmer
0.32
24386205FR-12G C
Solar/Wind Harmer
2.036
942481AE2-261 GEN
Solar/Wind Harmer
14.072
957381AF2-032 GEN
Solar/Wind Harmer
0.94
276785W4-005 GEN1
Solar/Wind Harmer
1.412
971993AH1-541 GEN
Solar/Wind Harmer
4.315
24690905MDL-1G C
Solar/Wind Harmer
3.689
270330AC1-082 GEN2
Solar/Wind Helper
0.169
270329AC1-082 GEN1
Solar/Wind Helper
0.169
970781AG2-491 GEN
Solar/Wind Harmer
2.082
24802606KYGER 1HP
50/50
4.511
24802706KYGER 1LP
50/50
2.645
24803506KYGER 5LP
50/50
2.583
971985AH1-537 GEN
Solar/Wind Harmer
56.568
253433AC1-085 GEN1
Solar/Wind Harmer
7.375
253432AC1-085 GEN2
Solar/Wind Harmer
0.371
270263AC1-001 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
11.529
270340AC2-060 GEN
Solar/Wind Harmer
3.869
253406AD2-031_GEN
Solar/Wind Harmer
1.584
25196108MFTGT2
Adder
1.862
25196108MFTGT2
Adder
1.729
972163AH1-664 GEN
Solar/Wind Harmer
11.991
972165AH1-665 GEN
Solar/Wind Harmer
9.592
339216AC1-074 GEN
Solar/Wind Harmer
1.851
270432AC2-029 GEN
Solar/Wind Harmer
7.618
253372AE2-315 SEC3
Adder
2.021
253372AE2-315 SEC3
Adder
2.021
25306009OHH W.
Adder
3.008
3429211JKCT 2G
Adder
10.797
241972AD1-140 GEN
Solar/Wind Harmer
3.986
253338AC1-165 GEN
Solar/Wind Harmer
0.939
253343AC1-166 GEN
Solar/Wind Harmer
0.939
270356AE2-297 GEN
Solar/Wind Harmer
3.929
971029AG2-637 GEN
Solar/Wind Harmer
12.368
270543AE2-219 C
Solar/Wind Harmer
7.87
247536S-71 GEN
Solar/Wind Harmer
3.045
964611AG1-324 GEN
Solar/Wind Harmer
2.784
961761AG1-017 GEN
Solar/Wind Harmer
0.304
945581AF1-223 GEN
Solar/Wind Harmer
3.06
945631AF1-228 GEN
Solar/Wind Harmer
3.043
958711AF2-162 GEN
Solar/Wind Harmer
0.643
943861AF1-054 GEN
Solar/Wind Harmer
2.427
943851AF1-053 GEN
Solar/Wind Harmer
1.173
970289AG2-191 GEN
Solar/Wind Harmer
1.176
24729505KEY G4
Adder
3.861
270291AC1-194 GEN
Solar/Wind Harmer
2.916
241955AC1-078 GEN
Solar/Wind Harmer
4.064
241973AD2-163_GEN1
Solar/Wind Harmer
1.073
241974AD2-163_GEN2
Solar/Wind Harmer
1.073
963791AG1-232 GEN
Solar/Wind Harmer
7.287
270444AC2-157 GEN1
Solar/Wind Harmer
2.98
270445AC2-157 GEN2
Solar/Wind Harmer
2.98
963841AG1-237 GEN
Solar/Wind Harmer
5.337
270071AF1-092 GEN
Solar/Wind Harmer
7.165
944221AF1-090 GEN
Solar/Wind Harmer
5.212
24386405FR-21G C
Solar/Wind Harmer
2.043
24387005FR-3G C
Solar/Wind Harmer
1.879
276763AC1-053 GEN1
Solar/Wind Harmer
1.847
276764AC1-053 GEN2
Solar/Wind Harmer
1.847
276668AB2-070 GEN1
Solar/Wind Harmer
1.034
276848AB2-070 GEN3
Solar/Wind Harmer
1.034
276849AB2-070 GEN2
Solar/Wind Harmer
1.034
946581AF1-322 GEN
Solar/Wind Harmer
4.702
24691005MDL-2G C
Solar/Wind Harmer
1.699
270331AC1-082 GEN3
Solar/Wind Helper
0.168
235780M24_1
Solar/Wind Helper
0.525
LAGNLTFEXP_LAGN->PJM
CLTF
5.54
TVALTFEXP_TVA->PJM
CLTF
2.651
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.383
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.406
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.825
MECLTFEXP_MEC->PJM
CLTF
6.978
SIGELTFEXP_SIGE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.569
NYPJM->LTFIMP_NY
CLTF
1.62
LGEELTFEXP_LGEE->PJM
CLTF
5.749
WECLTFEXP_WEC->PJM
CLTF
1.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.817
AG2-052LTFEXP_AG2-052->PJM
LTF
0.106
AH1-155LTFEXP_AH1-155->PJM
LTF
0.159

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.24 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1666.97
MW Contribution:
6.27
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.1 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2342.28
MW Contribution:
7.03
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.434
24803306KYGER 4LP
50/50
2.384
971191AH1-055 GEN
Solar/Wind Harmer
71.644
252507AC2-088 GEN
Solar/Wind Harmer
1.961
252519AF1-045_GEN
Solar/Wind Harmer
3.707
25194608D.CRK4
Adder
1.615
252524AE2-267 GEN
Solar/Wind Harmer
1.545
25196608WSDLE5
Adder
8.411
253317AC1-085 GEN4
Solar/Wind Harmer
8.089
946181AF1-283 GEN
Solar/Wind Harmer
12.561
958171AF2-111 GEN
Solar/Wind Harmer
23.452
25196008MFTGT1
Adder
1.257
253394AE2-221_GEN
Solar/Wind Harmer
4.109
972167AH1-666 GEN
Solar/Wind Harmer
7.062
270367AC2-061_GEN
Solar/Wind Harmer
2.733
270186AC1-089 GEN
Solar/Wind Harmer
5.183
339243AC2-075 GEN1
Solar/Wind Harmer
0.377
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.443
3429391JKCT 9G
Adder
6.056
960071AF2-298 GEN
Solar/Wind Harmer
1.1
970093AG2-073 GEN
Solar/Wind Harmer
3.499
24379505HDWTR1G C
Solar/Wind Harmer
5.189
270240V3-007_GEN2
Solar/Wind Harmer
4.06
270004AE1-209 GEN
Solar/Wind Harmer
3.304
970455AG2-298 GEN
Solar/Wind Harmer
2.109
24728505AND G1
Adder
2.296
946031AF1-268 GEN
Solar/Wind Harmer
4.96
970825AG2-519 GEN
Solar/Wind Harmer
3.347
962031AG1-047 GEN
Solar/Wind Harmer
1.75
957741AF2-068 GEN
Solar/Wind Harmer
8.68
970653AG2-424 GEN
Solar/Wind Harmer
0.392
253325AC1-069 GEN
Solar/Wind Harmer
0.574
339206AE1-143 GEN
Solar/Wind Harmer
1.156
965461AG1-414 GEN
Solar/Wind Harmer
1.18
970289AG2-191 GEN
Solar/Wind Harmer
0.399
247642Z2-115 C
Solar/Wind Harmer
0.032
944531AF1-118 GEN
Solar/Wind Harmer
17.479
270518AE2-148 GEN
Solar/Wind Harmer
5.914
972273AH1-721 GEN
Adder
40.32
970193AG2-126 GEN
Solar/Wind Harmer
7.214
276820AF1-078_GEN
Solar/Wind Harmer
0.735
339255AE2-071 GEN
Solar/Wind Harmer
0.537
339250AF1-203 GEN
Solar/Wind Harmer
0.276
270330AC1-082 GEN2
Solar/Wind Helper
0.19
270329AC1-082 GEN1
Solar/Wind Helper
0.19
24802606KYGER 1HP
50/50
4.162
24802706KYGER 1LP
50/50
2.441
24803506KYGER 5LP
50/50
2.384
971985AH1-537 GEN
Solar/Wind Harmer
49.14
25196408WSDLE3
Adder
8.658
253433AC1-085 GEN1
Solar/Wind Harmer
5.134
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
8.69
972165AH1-665 GEN
Solar/Wind Harmer
6.952
253406AD2-031_GEN
Solar/Wind Harmer
1.088
339216AC1-074 GEN
Solar/Wind Harmer
1.391
270340AC2-060 GEN
Solar/Wind Harmer
2.489
270263AC1-001 GEN
Solar/Wind Harmer
0.854
253372AE2-315 SEC3
Adder
1.443
253372AE2-315 SEC3
Adder
1.443
25306009OHH W.
Adder
2.158
3429211JKCT 2G
Adder
8.249
270356AE2-297 GEN
Solar/Wind Harmer
3.158
971029AG2-637 GEN
Solar/Wind Harmer
9.766
270432AC2-029 GEN
Solar/Wind Harmer
4.409
270543AE2-219 C
Solar/Wind Harmer
6.274
241972AD1-140 GEN
Solar/Wind Harmer
2.733
247536S-71 GEN
Solar/Wind Harmer
2.45
964611AG1-324 GEN
Solar/Wind Harmer
2.272
961761AG1-017 GEN
Solar/Wind Harmer
0.248
945581AF1-223 GEN
Solar/Wind Harmer
2.557
253338AC1-165 GEN
Solar/Wind Harmer
0.595
253343AC1-166 GEN
Solar/Wind Harmer
0.595
958711AF2-162 GEN
Solar/Wind Harmer
0.544
970289AG2-191 GEN
Solar/Wind Harmer
0.989
24729505KEY G4
Adder
3.305
270444AC2-157 GEN1
Solar/Wind Harmer
2.758
270445AC2-157 GEN2
Solar/Wind Harmer
2.758
963791AG1-232 GEN
Solar/Wind Harmer
6.09
963841AG1-237 GEN
Solar/Wind Harmer
4.776
944221AF1-090 GEN
Solar/Wind Harmer
4.74
24803006KYGER 3HP
50/50
4.133
24802806KYGER 2HP
50/50
4.118
24802906KYGER 2LP
50/50
2.417
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.28
25183208HLCRTG
Solar/Wind Harmer
6.261
25194408D.CRK1
Adder
7.428
25194508D.CRK3
Adder
1.389
962581AG1-107 GEN
Solar/Wind Harmer
4.213
961491AF2-440 GEN
Solar/Wind Harmer
1.751
270269AC2-059
Solar/Wind Harmer
7.604
253415AE1-040 GEN
Solar/Wind Harmer
0.897
972043AH1-570 GEN
Solar/Wind Harmer
1.988
972045AH1-571 GEN
Solar/Wind Harmer
1.59
971125AH1-004 GEN
Solar/Wind Harmer
3.051
970107AG2-081 GEN
Solar/Wind Harmer
2.288
253370AE2-315 SEC1
Adder
1.526
25322209TAIT E
Adder
7.164
25322209TAIT E
Adder
7.003
253349AC2-067 GEN
Solar/Wind Harmer
1.485
253400AC2-068 GEN
Solar/Wind Harmer
0.597
25326109MON D
Adder
0.938
942891AE2-308 GEN
Solar/Wind Harmer
6.919
926881AC1-175 GEN
Solar/Wind Harmer
3.662
270383AD1-128 GEN
Solar/Wind Harmer
3.929
970883AG2-550 GEN
Solar/Wind Harmer
6.274
970885AG2-551 GEN
Solar/Wind Harmer
1.459
247621Y3-024
Adder
0.142
964571AG1-320 GEN
Solar/Wind Harmer
4.793
24803406KYGER 5HP
50/50
4.085
24803206KYGER 4HP
50/50
4.076
252516AE2-318_GEN
Solar/Wind Harmer
10.186
25196808ZIMRHP
Adder
76.155
25194608D.CRK4
Adder
1.615
252510AF1-249 C
Solar/Wind Harmer
0.409
253316AC1-085 GEN3
Solar/Wind Harmer
8.089
946171AF1-282 GEN
Solar/Wind Harmer
9.662
25196008MFTGT1
Adder
1.298
253398AE2-221_GEN2
Solar/Wind Harmer
4.109
945681AF1-233 GEN
Solar/Wind Harmer
16.573
270273AD2-016 GEN
Solar/Wind Harmer
2.168
339221AD2-048_GEN
Solar/Wind Harmer
1.251
270222AC2-111 GEN
Solar/Wind Harmer
3.47
944031AF1-071 GEN
Solar/Wind Harmer
0.781
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.443
943111AE2-339 GEN
Solar/Wind Harmer
0.669
25326309TAIT D
Adder
0.804
3429421JKCT 10G
Adder
6.056
3429241JKCT 3G
Adder
8.358
942081AE2-220 GEN
Solar/Wind Harmer
4.197
270209AC1-174_GEN
Solar/Wind Harmer
2.67
270437AC2-090 C
Solar/Wind Harmer
3.662
270239V3-007_GEN1
Solar/Wind Harmer
1.129
339211AE2-254 GEN
Solar/Wind Harmer
0.919
270005AE1-210 C O1
Solar/Wind Harmer
3.304
24728605AND G2
Adder
2.296
970825AG2-519 GEN
Solar/Wind Harmer
1.247
945371AF1-202 GEN
Solar/Wind Harmer
3.934
970653AG2-424 GEN
Solar/Wind Harmer
2.709
276903AD2-071 C
Solar/Wind Harmer
5.501
253333AC1-068 GEN
Solar/Wind Harmer
0.574
958861AF2-177 GEN
Solar/Wind Harmer
5.973
270594AE1-207 GEN
Solar/Wind Harmer
7.326
270032AE2-172
Solar/Wind Harmer
2.509
965651AG1-433 GEN
Solar/Wind Harmer
2.937
270024AE2-089 GEN
Solar/Wind Harmer
2.481
339241AF1-083 GEN
Solar/Wind Harmer
0.868
970091AG2-072 GEN
Adder
38.983
964901AG1-354 GEN
Solar/Wind Harmer
7.327
963741AG1-226 GEN
Solar/Wind Harmer
20.113
960001AF2-291 GEN
Solar/Wind Helper
1.7
270331AC1-082 GEN3
Solar/Wind Helper
0.189
235780M24_1
Solar/Wind Helper
0.465
964611AG1-324 GEN
Solar/Wind Harmer
0.305
270201AC2-176 GEN
Solar/Wind Harmer
2.974
24725505WLD G2 C
Solar/Wind Harmer
2.243
24699105WLD G1 C
Solar/Wind Harmer
2.217
270031AE2-169
Solar/Wind Harmer
4.555
270599AE1-208 GEN
Solar/Wind Harmer
4.555
944541AF1-119 GEN
Solar/Wind Harmer
2.25
960971AF2-388 GEN
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
0.676
970291AG2-192 GEN
Solar/Wind Harmer
0.218
942221AE2-234 GEN
Solar/Wind Harmer
1.752
25326509SID D
Adder
0.658
339236AF1-050_GEN
Solar/Wind Harmer
0.894
945391AF1-204 GEN
Solar/Wind Harmer
6.702
339231AF1-038_GEN
Solar/Wind Harmer
0.854
253378AE2-206_GEN
Solar/Wind Harmer
1.655
964781AG1-341 GEN
Solar/Wind Harmer
4.826
970241AG2-163 GEN
Solar/Wind Harmer
11.174
237033AB1-150 GEN
Solar/Wind Helper
0.375
LAGNLTFEXP_LAGN->PJM
CLTF
5.572
TVALTFEXP_TVA->PJM
CLTF
2.7
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.049
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.972
MECLTFEXP_MEC->PJM
CLTF
6.466
SIGELTFEXP_SIGE->PJM
CLTF
0.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.696
NYPJM->LTFIMP_NY
CLTF
1.435
LGEELTFEXP_LGEE->PJM
CLTF
4.729
WECLTFEXP_WEC->PJM
CLTF
1.499
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.271
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.144

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1280.85
MW Contribution:
4.13
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.63 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1362.91
MW Contribution:
4.35
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.094
24803206KYGER 4HP
50/50
4.085
252516AE2-318_GEN
Solar/Wind Harmer
7.932
25196808ZIMRHP
Adder
75.812
25194608D.CRK4
Adder
1.604
252510AF1-249 C
Solar/Wind Harmer
0.051
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.761
25196008MFTGT1
Adder
1.283
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
11.543
270273AD2-016 GEN
Solar/Wind Harmer
0.596
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
25326309TAIT D
Adder
0.805
3429421JKCT 10G
Adder
6.006
3429241JKCT 3G
Adder
8.287
970773AG2-487 GEN
Solar/Wind Harmer
0.807
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.158
24728605AND G2
Adder
2.173
253333AC1-068 GEN
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
0.848
970825AG2-519 GEN
Solar/Wind Harmer
1.367
970653AG2-424 GEN
Solar/Wind Harmer
1.845
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
3.979
270594AE1-207 GEN
Solar/Wind Harmer
3.893
270032AE2-172
Solar/Wind Harmer
2.318
958861AF2-177 GEN
Solar/Wind Harmer
1.487
970091AG2-072 GEN
Adder
37.335
270024AE2-089 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.985
964901AG1-354 GEN
Solar/Wind Harmer
4.987
960001AF2-291 GEN
Solar/Wind Helper
1.682
270331AC1-082 GEN3
Solar/Wind Helper
0.187
24803006KYGER 3HP
50/50
4.142
24802806KYGER 2HP
50/50
4.127
24802906KYGER 2LP
50/50
2.422
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.038
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.38
25194508D.CRK3
Adder
1.38
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.433
972045AH1-571 GEN
Solar/Wind Harmer
1.148
253370AE2-315 SEC1
Adder
1.526
971125AH1-004 GEN
Solar/Wind Harmer
2.112
970107AG2-081 GEN
Solar/Wind Harmer
1.584
25322209TAIT E
Adder
7.169
25322209TAIT E
Adder
7.008
25326109MON D
Adder
0.942
942891AE2-308 GEN
Solar/Wind Harmer
4.783
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.132
970885AG2-551 GEN
Solar/Wind Harmer
1.377
964571AG1-320 GEN
Solar/Wind Harmer
3.631
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.967
270599AE1-208 GEN
Solar/Wind Harmer
3.278
25326509SID D
Adder
0.66
971613AH1-306 GEN
Solar/Wind Harmer
1.669
944541AF1-119 GEN
Solar/Wind Harmer
0.224
960971AF2-388 GEN
Solar/Wind Harmer
1.97
970291AG2-192 GEN
Solar/Wind Harmer
0.435
970291AG2-192 GEN
Solar/Wind Harmer
0.201
971587AH1-292 GEN
Solar/Wind Harmer
2.382
970329AG2-216 GEN
Solar/Wind Harmer
1.4
942221AE2-234 GEN
Solar/Wind Harmer
1.259
945391AF1-204 GEN
Solar/Wind Harmer
3.307
964781AG1-341 GEN
Solar/Wind Harmer
3.276
24802606KYGER 1HP
50/50
4.172
24802706KYGER 1LP
50/50
2.446
24803506KYGER 5LP
50/50
2.389
971985AH1-537 GEN
Solar/Wind Harmer
5.716
25196408WSDLE3
Adder
8.602
25196108MFTGT2
Adder
1.414
25196108MFTGT2
Adder
1.313
972163AH1-664 GEN
Solar/Wind Harmer
6.737
972165AH1-665 GEN
Solar/Wind Harmer
5.396
253406AD2-031_GEN
Solar/Wind Harmer
0.443
270263AC1-001 GEN
Solar/Wind Harmer
0.582
270340AC2-060 GEN
Solar/Wind Harmer
0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.154
253372AE2-315 SEC3
Adder
1.444
253372AE2-315 SEC3
Adder
1.444
25306009OHH W.
Adder
2.154
3429211JKCT 2G
Adder
8.179
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.01
971029AG2-637 GEN
Solar/Wind Harmer
6.48
241972AD1-140 GEN
Solar/Wind Harmer
0.472
270543AE2-219 C
Solar/Wind Harmer
2.892
247536S-71 GEN
Solar/Wind Harmer
0.158
964611AG1-324 GEN
Solar/Wind Harmer
1.472
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.584
970289AG2-191 GEN
Solar/Wind Harmer
0.636
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
2.909
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.389
971191AH1-055 GEN
Solar/Wind Harmer
68.884
252507AC2-088 GEN
Solar/Wind Harmer
0.343
252519AF1-045_GEN
Solar/Wind Harmer
3.694
25194608D.CRK4
Adder
1.604
25196608WSDLE5
Adder
8.356
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.789
958171AF2-111 GEN
Solar/Wind Harmer
16.332
25196008MFTGT1
Adder
1.242
253394AE2-221_GEN
Solar/Wind Harmer
0.001
972167AH1-666 GEN
Solar/Wind Harmer
4.919
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
970191AG2-125 GEN
Solar/Wind Harmer
1.303
3429391JKCT 9G
Adder
6.006
970093AG2-073 GEN
Solar/Wind Harmer
3.867
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970455AG2-298 GEN
Solar/Wind Harmer
1.6
24728505AND G1
Adder
2.173
253325AC1-069 GEN
Solar/Wind Harmer
0.004
270004AE1-209 GEN
Solar/Wind Harmer
0.848
946031AF1-268 GEN
Solar/Wind Harmer
3.69
970825AG2-519 GEN
Solar/Wind Harmer
2.902
970653AG2-424 GEN
Solar/Wind Harmer
0.382
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.618
270518AE2-148 GEN
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
0.368
972273AH1-721 GEN
Adder
39.663
247642Z2-115 C
Solar/Wind Harmer
0.001
970193AG2-126 GEN
Solar/Wind Harmer
4.669
944531AF1-118 GEN
Solar/Wind Harmer
13.648
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
LAGNLTFEXP_LAGN->PJM
CLTF
5.22
TVALTFEXP_TVA->PJM
CLTF
2.571
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.475
MECLTFEXP_MEC->PJM
CLTF
5.763
SIGELTFEXP_SIGE->PJM
CLTF
0.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.509
NYPJM->LTFIMP_NY
CLTF
1.348
LGEELTFEXP_LGEE->PJM
CLTF
4.627
WECLTFEXP_WEC->PJM
CLTF
1.3
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.242
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#6763_05BIERSR 345_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.64 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1642.31
MW Contribution:
5.95
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:124.15 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1911.95
MW Contribution:
6.31
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.233
24802706KYGER 1LP
50/50
2.482
24803506KYGER 5LP
50/50
2.424
971985AH1-537 GEN
Solar/Wind Harmer
50.257
270263AC1-001 GEN
Solar/Wind Harmer
1.208
270340AC2-060 GEN
Solar/Wind Harmer
3.062
25196408WSDLE3
Adder
8.855
253433AC1-085 GEN1
Solar/Wind Harmer
5.315
253432AC1-085 GEN2
Solar/Wind Harmer
0.268
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
972163AH1-664 GEN
Solar/Wind Harmer
9.072
972165AH1-665 GEN
Solar/Wind Harmer
7.258
253406AD2-031_GEN
Solar/Wind Harmer
1.155
270432AC2-029 GEN
Solar/Wind Harmer
6.034
339216AC1-074 GEN
Solar/Wind Harmer
1.44
253372AE2-315 SEC3
Adder
1.457
253372AE2-315 SEC3
Adder
1.457
25306009OHH W.
Adder
2.176
3429211JKCT 2G
Adder
8.545
270356AE2-297 GEN
Solar/Wind Harmer
3.063
971029AG2-637 GEN
Solar/Wind Harmer
9.355
241972AD1-140 GEN
Solar/Wind Harmer
2.699
270543AE2-219 C
Solar/Wind Harmer
5.951
247536S-71 GEN
Solar/Wind Harmer
2.301
964611AG1-324 GEN
Solar/Wind Harmer
2.109
961761AG1-017 GEN
Solar/Wind Harmer
0.229
253338AC1-165 GEN
Solar/Wind Harmer
0.575
253343AC1-166 GEN
Solar/Wind Harmer
0.575
945581AF1-223 GEN
Solar/Wind Harmer
2.315
24803406KYGER 5HP
50/50
4.154
24803206KYGER 4HP
50/50
4.145
270273AD2-016 GEN
Solar/Wind Harmer
3.199
252516AE2-318_GEN
Solar/Wind Harmer
10.498
25196808ZIMRHP
Adder
78.483
252510AF1-249 C
Solar/Wind Harmer
0.42
25194608D.CRK4
Adder
1.654
253316AC1-085 GEN3
Solar/Wind Harmer
8.374
946171AF1-282 GEN
Solar/Wind Harmer
10.003
25196008MFTGT1
Adder
1.323
253398AE2-221_GEN2
Solar/Wind Harmer
4.227
945681AF1-233 GEN
Solar/Wind Harmer
17.298
339221AD2-048_GEN
Solar/Wind Harmer
1.297
943111AE2-339 GEN
Solar/Wind Harmer
0.692
270222AC2-111 GEN
Solar/Wind Harmer
3.448
944031AF1-071 GEN
Solar/Wind Harmer
0.776
253370AE2-315 SEC1
Adder
1.54
253371AE2-315 SEC2
Adder
1.457
3429421JKCT 10G
Adder
6.269
25326309TAIT D
Adder
0.808
3429241JKCT 3G
Adder
8.658
339211AE2-254 GEN
Solar/Wind Harmer
0.946
942081AE2-220 GEN
Solar/Wind Harmer
3.986
270209AC1-174_GEN
Solar/Wind Harmer
2.536
270437AC2-090 C
Solar/Wind Harmer
3.478
270239V3-007_GEN1
Solar/Wind Harmer
1.072
24728605AND G2
Adder
2.198
970653AG2-424 GEN
Solar/Wind Harmer
2.75
270005AE1-210 C O1
Solar/Wind Harmer
3.075
970825AG2-519 GEN
Solar/Wind Harmer
1.162
339241AF1-083 GEN
Solar/Wind Harmer
0.887
253333AC1-068 GEN
Solar/Wind Harmer
0.554
945371AF1-202 GEN
Solar/Wind Harmer
3.561
276903AD2-071 C
Solar/Wind Harmer
5.099
970091AG2-072 GEN
Adder
38.38
964901AG1-354 GEN
Solar/Wind Harmer
7.465
270594AE1-207 GEN
Solar/Wind Harmer
6.734
270032AE2-172
Solar/Wind Harmer
2.306
958861AF2-177 GEN
Solar/Wind Harmer
5.335
270024AE2-089 GEN
Solar/Wind Harmer
2.242
965651AG1-433 GEN
Solar/Wind Harmer
2.603
960001AF2-291 GEN
Solar/Wind Helper
1.623
270331AC1-082 GEN3
Solar/Wind Helper
0.176
24803106KYGER 3LP
50/50
2.475
24803306KYGER 4LP
50/50
2.424
971191AH1-055 GEN
Solar/Wind Harmer
74.07
252507AC2-088 GEN
Solar/Wind Harmer
2.029
252519AF1-045_GEN
Solar/Wind Harmer
3.821
25194608D.CRK4
Adder
1.654
252524AE2-267 GEN
Solar/Wind Harmer
1.581
25196608WSDLE5
Adder
8.602
253317AC1-085 GEN4
Solar/Wind Harmer
8.374
946181AF1-283 GEN
Solar/Wind Harmer
13.003
958171AF2-111 GEN
Solar/Wind Harmer
24.384
25196008MFTGT1
Adder
1.281
253394AE2-221_GEN
Solar/Wind Harmer
4.227
270367AC2-061_GEN
Solar/Wind Harmer
2.94
972167AH1-666 GEN
Solar/Wind Harmer
7.371
270186AC1-089 GEN
Solar/Wind Harmer
5.567
339243AC2-075 GEN1
Solar/Wind Harmer
0.39
253303V4-073 C
Solar/Wind Harmer
0.089
253370AE2-315 SEC1
Adder
1.54
253371AE2-315 SEC2
Adder
1.457
3429391JKCT 9G
Adder
6.269
960071AF2-298 GEN
Solar/Wind Harmer
1.104
970093AG2-073 GEN
Solar/Wind Harmer
3.624
24379505HDWTR1G C
Solar/Wind Harmer
4.928
270240V3-007_GEN2
Solar/Wind Harmer
3.856
970455AG2-298 GEN
Solar/Wind Harmer
2.145
24728505AND G1
Adder
2.198
970653AG2-424 GEN
Solar/Wind Harmer
0.398
270004AE1-209 GEN
Solar/Wind Harmer
3.075
946031AF1-268 GEN
Solar/Wind Harmer
4.625
339206AE1-143 GEN
Solar/Wind Harmer
1.182
970825AG2-519 GEN
Solar/Wind Harmer
3.119
962031AG1-047 GEN
Solar/Wind Harmer
1.621
957741AF2-068 GEN
Solar/Wind Harmer
8.043
253325AC1-069 GEN
Solar/Wind Harmer
0.554
972273AH1-721 GEN
Adder
41.705
965461AG1-414 GEN
Solar/Wind Harmer
1.079
970289AG2-191 GEN
Solar/Wind Harmer
0.365
339255AE2-071 GEN
Solar/Wind Harmer
0.546
339250AF1-203 GEN
Solar/Wind Harmer
0.281
247642Z2-115 C
Solar/Wind Harmer
0.029
270518AE2-148 GEN
Solar/Wind Harmer
5.413
970193AG2-126 GEN
Solar/Wind Harmer
6.708
276820AF1-078_GEN
Solar/Wind Harmer
0.71
270330AC1-082 GEN2
Solar/Wind Helper
0.177
270329AC1-082 GEN1
Solar/Wind Helper
0.177
24803006KYGER 3HP
50/50
4.203
24802806KYGER 2HP
50/50
4.187
24802906KYGER 2LP
50/50
2.458
25183008BIOENL
50/50
0.03
270269AC2-059
Solar/Wind Harmer
11.217
252509AD1-136 GEN
Solar/Wind Harmer
0.29
25183208HLCRTG
Solar/Wind Harmer
6.476
25194408D.CRK1
Adder
7.607
25194508D.CRK3
Adder
1.422
253415AE1-040 GEN
Solar/Wind Harmer
1.072
962581AG1-107 GEN
Solar/Wind Harmer
4.523
961491AF2-440 GEN
Solar/Wind Harmer
1.88
972043AH1-570 GEN
Solar/Wind Harmer
2.063
972045AH1-571 GEN
Solar/Wind Harmer
1.65
971125AH1-004 GEN
Solar/Wind Harmer
3.156
970107AG2-081 GEN
Solar/Wind Harmer
2.367
253370AE2-315 SEC1
Adder
1.54
25322209TAIT E
Adder
7.197
25322209TAIT E
Adder
7.035
253349AC2-067 GEN
Solar/Wind Harmer
1.487
253400AC2-068 GEN
Solar/Wind Harmer
0.598
942891AE2-308 GEN
Solar/Wind Harmer
7.164
25326109MON D
Adder
0.939
926881AC1-175 GEN
Solar/Wind Harmer
3.478
270383AD1-128 GEN
Solar/Wind Harmer
3.738
970883AG2-550 GEN
Solar/Wind Harmer
5.951
970885AG2-551 GEN
Solar/Wind Harmer
1.384
964571AG1-320 GEN
Solar/Wind Harmer
4.845
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
2.756
24725505WLD G2 C
Solar/Wind Harmer
2.089
24699105WLD G1 C
Solar/Wind Harmer
2.065
270031AE2-169
Solar/Wind Harmer
4.163
270599AE1-208 GEN
Solar/Wind Harmer
4.163
339236AF1-050_GEN
Solar/Wind Harmer
0.911
25326509SID D
Adder
0.639
339231AF1-038_GEN
Solar/Wind Harmer
0.877
944541AF1-119 GEN
Solar/Wind Harmer
1.995
960971AF2-388 GEN
Solar/Wind Harmer
5.207
970291AG2-192 GEN
Solar/Wind Harmer
0.618
970291AG2-192 GEN
Solar/Wind Harmer
0.199
964781AG1-341 GEN
Solar/Wind Harmer
4.908
945391AF1-204 GEN
Solar/Wind Harmer
6.233
253378AE2-206_GEN
Solar/Wind Harmer
1.598
942221AE2-234 GEN
Solar/Wind Harmer
1.546
971485AH1-239 GEN
Solar/Wind Harmer
3.529
966021AG1-471 GEN
Solar/Wind Harmer
2.352
958711AF2-162 GEN
Solar/Wind Harmer
0.482
970289AG2-191 GEN
Solar/Wind Harmer
0.904
270444AC2-157 GEN1
Solar/Wind Harmer
2.638
270445AC2-157 GEN2
Solar/Wind Harmer
2.638
24729505KEY G4
Adder
2.858
LAGNLTFEXP_LAGN->PJM
CLTF
5.453
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.294
TVALTFEXP_TVA->PJM
CLTF
2.722
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.877
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.097
MECLTFEXP_MEC->PJM
CLTF
5.729
SIGELTFEXP_SIGE->PJM
CLTF
0.289
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.722
NYPJM->LTFIMP_NY
CLTF
1.367
LGEELTFEXP_LGEE->PJM
CLTF
4.789
WECLTFEXP_WEC->PJM
CLTF
1.269
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.139
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.122

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#308_05CULLOD 765_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.58 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1641.32
MW Contribution:
6.12
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.05 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1848.71
MW Contribution:
6.44
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.104
24803206KYGER 4HP
50/50
4.094
252516AE2-318_GEN
Solar/Wind Harmer
10.415
25196808ZIMRHP
Adder
77.888
25194608D.CRK4
Adder
1.647
252510AF1-249 C
Solar/Wind Harmer
0.418
253316AC1-085 GEN3
Solar/Wind Harmer
8.32
946171AF1-282 GEN
Solar/Wind Harmer
9.938
25196008MFTGT1
Adder
1.321
253398AE2-221_GEN2
Solar/Wind Harmer
4.228
945681AF1-233 GEN
Solar/Wind Harmer
17.15
270273AD2-016 GEN
Solar/Wind Harmer
2.264
339221AD2-048_GEN
Solar/Wind Harmer
1.291
943111AE2-339 GEN
Solar/Wind Harmer
0.692
253370AE2-315 SEC1
Adder
1.567
253371AE2-315 SEC2
Adder
1.482
270222AC2-111 GEN
Solar/Wind Harmer
3.487
944031AF1-071 GEN
Solar/Wind Harmer
0.785
25326309TAIT D
Adder
0.826
3429421JKCT 10G
Adder
6.274
3429241JKCT 3G
Adder
8.674
942081AE2-220 GEN
Solar/Wind Harmer
4.085
270209AC1-174_GEN
Solar/Wind Harmer
2.599
270437AC2-090 C
Solar/Wind Harmer
3.565
270239V3-007_GEN1
Solar/Wind Harmer
1.099
339211AE2-254 GEN
Solar/Wind Harmer
0.956
24728605AND G2
Adder
2.264
270005AE1-210 C O1
Solar/Wind Harmer
3.176
970653AG2-424 GEN
Solar/Wind Harmer
2.799
253333AC1-068 GEN
Solar/Wind Harmer
0.604
970825AG2-519 GEN
Solar/Wind Harmer
1.201
339241AF1-083 GEN
Solar/Wind Harmer
0.903
276903AD2-071 C
Solar/Wind Harmer
5.316
945371AF1-202 GEN
Solar/Wind Harmer
3.708
970091AG2-072 GEN
Adder
40.26
270594AE1-207 GEN
Solar/Wind Harmer
7.041
270032AE2-172
Solar/Wind Harmer
2.411
958861AF2-177 GEN
Solar/Wind Harmer
5.577
964901AG1-354 GEN
Solar/Wind Harmer
7.63
270024AE2-089 GEN
Solar/Wind Harmer
2.348
965651AG1-433 GEN
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
19.4
960001AF2-291 GEN
Solar/Wind Helper
1.679
270331AC1-082 GEN3
Solar/Wind Helper
0.185
235780M24_1
Solar/Wind Helper
0.466
24803106KYGER 3LP
50/50
2.445
24803306KYGER 4LP
50/50
2.394
971191AH1-055 GEN
Solar/Wind Harmer
72.303
252507AC2-088 GEN
Solar/Wind Harmer
2.004
252519AF1-045_GEN
Solar/Wind Harmer
3.791
25194608D.CRK4
Adder
1.647
252524AE2-267 GEN
Solar/Wind Harmer
1.576
25196608WSDLE5
Adder
8.577
253317AC1-085 GEN4
Solar/Wind Harmer
8.32
946181AF1-283 GEN
Solar/Wind Harmer
12.919
958171AF2-111 GEN
Solar/Wind Harmer
24.139
25196008MFTGT1
Adder
1.279
253394AE2-221_GEN
Solar/Wind Harmer
4.228
972167AH1-666 GEN
Solar/Wind Harmer
7.307
270367AC2-061_GEN
Solar/Wind Harmer
2.836
270186AC1-089 GEN
Solar/Wind Harmer
5.382
339243AC2-075 GEN1
Solar/Wind Harmer
0.388
253303V4-073 C
Solar/Wind Harmer
0.091
253370AE2-315 SEC1
Adder
1.567
253371AE2-315 SEC2
Adder
1.482
3429391JKCT 9G
Adder
6.274
960071AF2-298 GEN
Solar/Wind Harmer
1.127
970093AG2-073 GEN
Solar/Wind Harmer
3.641
24379505HDWTR1G C
Solar/Wind Harmer
5.05
270240V3-007_GEN2
Solar/Wind Harmer
3.951
970455AG2-298 GEN
Solar/Wind Harmer
2.176
24728505AND G1
Adder
2.264
270004AE1-209 GEN
Solar/Wind Harmer
3.176
970653AG2-424 GEN
Solar/Wind Harmer
0.405
253325AC1-069 GEN
Solar/Wind Harmer
0.604
946031AF1-268 GEN
Solar/Wind Harmer
4.781
970825AG2-519 GEN
Solar/Wind Harmer
3.226
339206AE1-143 GEN
Solar/Wind Harmer
1.202
962031AG1-047 GEN
Solar/Wind Harmer
1.681
957741AF2-068 GEN
Solar/Wind Harmer
8.342
270518AE2-148 GEN
Solar/Wind Harmer
6.232
972273AH1-721 GEN
Adder
42.523
965461AG1-414 GEN
Solar/Wind Harmer
1.132
970289AG2-191 GEN
Solar/Wind Harmer
0.383
247642Z2-115 C
Solar/Wind Harmer
0.031
339255AE2-071 GEN
Solar/Wind Harmer
0.56
339250AF1-203 GEN
Solar/Wind Harmer
0.288
276820AF1-078_GEN
Solar/Wind Harmer
0.759
970193AG2-126 GEN
Solar/Wind Harmer
7.062
944531AF1-118 GEN
Solar/Wind Harmer
15.85
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
24803006KYGER 3HP
50/50
4.152
24802806KYGER 2HP
50/50
4.136
24802906KYGER 2LP
50/50
2.428
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.286
25183208HLCRTG
Solar/Wind Harmer
6.412
25194408D.CRK1
Adder
7.577
25194508D.CRK3
Adder
1.417
962581AG1-107 GEN
Solar/Wind Harmer
4.372
961491AF2-440 GEN
Solar/Wind Harmer
1.817
270269AC2-059
Solar/Wind Harmer
7.941
253415AE1-040 GEN
Solar/Wind Harmer
0.933
972043AH1-570 GEN
Solar/Wind Harmer
2.055
972045AH1-571 GEN
Solar/Wind Harmer
1.644
971125AH1-004 GEN
Solar/Wind Harmer
3.154
970107AG2-081 GEN
Solar/Wind Harmer
2.365
253370AE2-315 SEC1
Adder
1.567
25322209TAIT E
Adder
7.355
25322209TAIT E
Adder
7.19
253349AC2-067 GEN
Solar/Wind Harmer
1.516
253400AC2-068 GEN
Solar/Wind Harmer
0.61
25326109MON D
Adder
0.965
942891AE2-308 GEN
Solar/Wind Harmer
7.186
926881AC1-175 GEN
Solar/Wind Harmer
3.565
270383AD1-128 GEN
Solar/Wind Harmer
3.837
970883AG2-550 GEN
Solar/Wind Harmer
6.124
970885AG2-551 GEN
Solar/Wind Harmer
1.424
964571AG1-320 GEN
Solar/Wind Harmer
4.93
247621Y3-024
Adder
0.138
964611AG1-324 GEN
Solar/Wind Harmer
0.293
270201AC2-176 GEN
Solar/Wind Harmer
2.858
24725505WLD G2 C
Solar/Wind Harmer
2.172
24699105WLD G1 C
Solar/Wind Harmer
2.146
270031AE2-169
Solar/Wind Harmer
4.335
270599AE1-208 GEN
Solar/Wind Harmer
4.335
25326509SID D
Adder
0.676
339236AF1-050_GEN
Solar/Wind Harmer
0.931
970291AG2-192 GEN
Solar/Wind Harmer
0.649
970291AG2-192 GEN
Solar/Wind Harmer
0.209
944541AF1-119 GEN
Solar/Wind Harmer
2.09
960971AF2-388 GEN
Solar/Wind Harmer
5.455
339231AF1-038_GEN
Solar/Wind Harmer
0.897
253378AE2-206_GEN
Solar/Wind Harmer
1.709
964781AG1-341 GEN
Solar/Wind Harmer
5.034
945391AF1-204 GEN
Solar/Wind Harmer
6.561
942221AE2-234 GEN
Solar/Wind Harmer
1.631
971485AH1-239 GEN
Solar/Wind Harmer
3.621
966021AG1-471 GEN
Solar/Wind Harmer
2.415
970241AG2-163 GEN
Solar/Wind Harmer
10.778
237033AB1-150 GEN
Solar/Wind Helper
0.376
24802606KYGER 1HP
50/50
4.181
24802706KYGER 1LP
50/50
2.452
24803506KYGER 5LP
50/50
2.394
971985AH1-537 GEN
Solar/Wind Harmer
49.573
25196408WSDLE3
Adder
8.83
253433AC1-085 GEN1
Solar/Wind Harmer
5.281
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
1.456
25196108MFTGT2
Adder
1.352
972163AH1-664 GEN
Solar/Wind Harmer
8.997
972165AH1-665 GEN
Solar/Wind Harmer
7.198
253406AD2-031_GEN
Solar/Wind Harmer
1.124
339216AC1-074 GEN
Solar/Wind Harmer
1.434
270340AC2-060 GEN
Solar/Wind Harmer
2.588
270263AC1-001 GEN
Solar/Wind Harmer
0.893
253372AE2-315 SEC3
Adder
1.482
253372AE2-315 SEC3
Adder
1.482
25306009OHH W.
Adder
2.212
3429211JKCT 2G
Adder
8.562
270356AE2-297 GEN
Solar/Wind Harmer
3.125
270432AC2-029 GEN
Solar/Wind Harmer
4.647
971029AG2-637 GEN
Solar/Wind Harmer
9.596
241972AD1-140 GEN
Solar/Wind Harmer
2.835
270543AE2-219 C
Solar/Wind Harmer
6.124
247536S-71 GEN
Solar/Wind Harmer
2.375
253338AC1-165 GEN
Solar/Wind Harmer
0.626
253343AC1-166 GEN
Solar/Wind Harmer
0.626
964611AG1-324 GEN
Solar/Wind Harmer
2.185
961761AG1-017 GEN
Solar/Wind Harmer
0.238
945581AF1-223 GEN
Solar/Wind Harmer
2.41
970289AG2-191 GEN
Solar/Wind Harmer
0.949
958711AF2-162 GEN
Solar/Wind Harmer
0.505
270444AC2-157 GEN1
Solar/Wind Harmer
2.766
270445AC2-157 GEN2
Solar/Wind Harmer
2.766
24729505KEY G4
Adder
3.017
LAGNLTFEXP_LAGN->PJM
CLTF
5.772
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.344
TVALTFEXP_TVA->PJM
CLTF
2.874
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.588
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.625
MECLTFEXP_MEC->PJM
CLTF
6.138
SIGELTFEXP_SIGE->PJM
CLTF
0.297
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.11
NYPJM->LTFIMP_NY
CLTF
1.419
LGEELTFEXP_LGEE->PJM
CLTF
4.847
WECLTFEXP_WEC->PJM
CLTF
1.374
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.143
AG2-052LTFEXP_AG2-052->PJM
LTF
0.088
AH1-155LTFEXP_AH1-155->PJM
LTF
0.132

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P7-1_#11019___SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11019___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.15 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1634.72
MW Contribution:
6.73
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.392
971191AH1-055 GEN
Solar/Wind Harmer
71.988
252507AC2-088 GEN
Solar/Wind Harmer
2.003
252519AF1-045_GEN
Solar/Wind Harmer
3.797
25194608D.CRK4
Adder
1.659
252524AE2-267 GEN
Solar/Wind Harmer
1.588
25196608WSDLE5
Adder
8.641
253317AC1-085 GEN4
Solar/Wind Harmer
8.268
946181AF1-283 GEN
Solar/Wind Harmer
12.839
25196008MFTGT1
Adder
1.293
958171AF2-111 GEN
Solar/Wind Harmer
23.953
253394AE2-221_GEN
Solar/Wind Harmer
4.207
972167AH1-666 GEN
Solar/Wind Harmer
7.221
270367AC2-061_GEN
Solar/Wind Harmer
2.804
270186AC1-089 GEN
Solar/Wind Harmer
5.313
339243AC2-075 GEN1
Solar/Wind Harmer
0.385
253303V4-073 C
Solar/Wind Harmer
0.091
253370AE2-315 SEC1
Adder
1.572
253371AE2-315 SEC2
Adder
1.486
24379505HDWTR1G C
Solar/Wind Harmer
6.03
270240V3-007_GEN2
Solar/Wind Harmer
4.718
960071AF2-298 GEN
Solar/Wind Harmer
1.133
3429391JKCT 9G
Adder
6.186
944531AF1-118 GEN
Solar/Wind Harmer
25.425
270004AE1-209 GEN
Solar/Wind Harmer
3.962
946031AF1-268 GEN
Solar/Wind Harmer
5.635
970093AG2-073 GEN
Solar/Wind Harmer
3.576
970825AG2-519 GEN
Solar/Wind Harmer
3.78
24728505AND G1
Adder
2.43
962031AG1-047 GEN
Solar/Wind Harmer
1.892
957741AF2-068 GEN
Solar/Wind Harmer
9.384
970455AG2-298 GEN
Solar/Wind Harmer
2.144
253325AC1-069 GEN
Solar/Wind Harmer
0.598
970653AG2-424 GEN
Solar/Wind Harmer
0.398
339206AE1-143 GEN
Solar/Wind Harmer
1.176
965461AG1-414 GEN
Solar/Wind Harmer
1.229
24802606KYGER 1HP
50/50
4.177
24802706KYGER 1LP
50/50
2.449
24803506KYGER 5LP
50/50
2.392
971985AH1-537 GEN
Solar/Wind Harmer
49.507
25196408WSDLE3
Adder
8.895
253433AC1-085 GEN1
Solar/Wind Harmer
5.248
253432AC1-085 GEN2
Solar/Wind Harmer
0.264
25196108MFTGT2
Adder
1.472
25196108MFTGT2
Adder
1.367
972163AH1-664 GEN
Solar/Wind Harmer
8.886
972165AH1-665 GEN
Solar/Wind Harmer
7.109
253406AD2-031_GEN
Solar/Wind Harmer
1.116
339216AC1-074 GEN
Solar/Wind Harmer
1.421
270340AC2-060 GEN
Solar/Wind Harmer
2.555
270263AC1-001 GEN
Solar/Wind Harmer
0.877
253372AE2-315 SEC3
Adder
1.486
253372AE2-315 SEC3
Adder
1.486
25306009OHH W.
Adder
2.227
270356AE2-297 GEN
Solar/Wind Harmer
3.397
24729505KEY G4
Adder
4.712
958711AF2-162 GEN
Solar/Wind Harmer
0.734
945581AF1-223 GEN
Solar/Wind Harmer
3.291
3429211JKCT 2G
Adder
8.429
971029AG2-637 GEN
Solar/Wind Harmer
10.454
270543AE2-219 C
Solar/Wind Harmer
6.73
270432AC2-029 GEN
Solar/Wind Harmer
4.565
247536S-71 GEN
Solar/Wind Harmer
2.631
964611AG1-324 GEN
Solar/Wind Harmer
2.484
241972AD1-140 GEN
Solar/Wind Harmer
2.83
961761AG1-017 GEN
Solar/Wind Harmer
0.268
253338AC1-165 GEN
Solar/Wind Harmer
0.62
253343AC1-166 GEN
Solar/Wind Harmer
0.62
970289AG2-191 GEN
Solar/Wind Harmer
1.03
270444AC2-157 GEN1
Solar/Wind Harmer
2.679
270445AC2-157 GEN2
Solar/Wind Harmer
2.679
24803406KYGER 5HP
50/50
4.099
24803206KYGER 4HP
50/50
4.09
252516AE2-318_GEN
Solar/Wind Harmer
10.431
25196808ZIMRHP
Adder
78.006
25194608D.CRK4
Adder
1.659
252510AF1-249 C
Solar/Wind Harmer
0.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.268
946171AF1-282 GEN
Solar/Wind Harmer
9.876
25196008MFTGT1
Adder
1.335
253398AE2-221_GEN2
Solar/Wind Harmer
4.207
945681AF1-233 GEN
Solar/Wind Harmer
16.945
270273AD2-016 GEN
Solar/Wind Harmer
2.226
339221AD2-048_GEN
Solar/Wind Harmer
1.278
270222AC2-111 GEN
Solar/Wind Harmer
3.666
944031AF1-071 GEN
Solar/Wind Harmer
0.825
253370AE2-315 SEC1
Adder
1.572
253371AE2-315 SEC2
Adder
1.486
943111AE2-339 GEN
Solar/Wind Harmer
0.683
942081AE2-220 GEN
Solar/Wind Harmer
4.877
270209AC1-174_GEN
Solar/Wind Harmer
3.103
270437AC2-090 C
Solar/Wind Harmer
4.256
270239V3-007_GEN1
Solar/Wind Harmer
1.312
25326309TAIT D
Adder
0.828
3429421JKCT 10G
Adder
6.186
965651AG1-433 GEN
Solar/Wind Harmer
3.967
958861AF2-177 GEN
Solar/Wind Harmer
7.933
945371AF1-202 GEN
Solar/Wind Harmer
5.062
270005AE1-210 C O1
Solar/Wind Harmer
3.962
3429241JKCT 3G
Adder
8.54
970825AG2-519 GEN
Solar/Wind Harmer
1.408
24728605AND G2
Adder
2.43
339211AE2-254 GEN
Solar/Wind Harmer
0.938
276903AD2-071 C
Solar/Wind Harmer
5.798
270594AE1-207 GEN
Solar/Wind Harmer
7.838
270032AE2-172
Solar/Wind Harmer
2.684
253333AC1-068 GEN
Solar/Wind Harmer
0.598
970653AG2-424 GEN
Solar/Wind Harmer
2.75
270024AE2-089 GEN
Solar/Wind Harmer
2.518
339241AF1-083 GEN
Solar/Wind Harmer
0.882
970091AG2-072 GEN
Adder
38.234
964901AG1-354 GEN
Solar/Wind Harmer
7.432
960001AF2-291 GEN
Solar/Wind Helper
1.677
270331AC1-082 GEN3
Solar/Wind Helper
0.186
970289AG2-191 GEN
Solar/Wind Harmer
0.416
270518AE2-148 GEN
Solar/Wind Harmer
6.193
247642Z2-115 C
Solar/Wind Harmer
0.033
972273AH1-721 GEN
Adder
41.179
276820AF1-078_GEN
Solar/Wind Harmer
0.747
339255AE2-071 GEN
Solar/Wind Harmer
0.544
339250AF1-203 GEN
Solar/Wind Harmer
0.28
970193AG2-126 GEN
Solar/Wind Harmer
6.921
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
24803006KYGER 3HP
50/50
4.147
24802806KYGER 2HP
50/50
4.132
24802906KYGER 2LP
50/50
2.425
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.286
25183208HLCRTG
Solar/Wind Harmer
6.401
25194408D.CRK1
Adder
7.63
25194508D.CRK3
Adder
1.427
962581AG1-107 GEN
Solar/Wind Harmer
4.324
961491AF2-440 GEN
Solar/Wind Harmer
1.797
270269AC2-059
Solar/Wind Harmer
7.807
253415AE1-040 GEN
Solar/Wind Harmer
0.922
972043AH1-570 GEN
Solar/Wind Harmer
2.031
972045AH1-571 GEN
Solar/Wind Harmer
1.625
253370AE2-315 SEC1
Adder
1.572
971125AH1-004 GEN
Solar/Wind Harmer
3.116
970107AG2-081 GEN
Solar/Wind Harmer
2.337
926881AC1-175 GEN
Solar/Wind Harmer
4.256
25322209TAIT E
Adder
7.38
25322209TAIT E
Adder
7.214
253349AC2-067 GEN
Solar/Wind Harmer
1.537
253400AC2-068 GEN
Solar/Wind Harmer
0.618
25326109MON D
Adder
0.965
944541AF1-119 GEN
Solar/Wind Harmer
3.039
960971AF2-388 GEN
Solar/Wind Harmer
7.934
270383AD1-128 GEN
Solar/Wind Harmer
4.402
942891AE2-308 GEN
Solar/Wind Harmer
7.07
970883AG2-550 GEN
Solar/Wind Harmer
6.73
970885AG2-551 GEN
Solar/Wind Harmer
1.565
964611AG1-324 GEN
Solar/Wind Harmer
0.333
247621Y3-024
Adder
0.152
270201AC2-176 GEN
Solar/Wind Harmer
3.215
24725505WLD G2 C
Solar/Wind Harmer
2.387
24699105WLD G1 C
Solar/Wind Harmer
2.359
964571AG1-320 GEN
Solar/Wind Harmer
4.862
270031AE2-169
Solar/Wind Harmer
4.804
270599AE1-208 GEN
Solar/Wind Harmer
4.804
970291AG2-192 GEN
Solar/Wind Harmer
0.705
970291AG2-192 GEN
Solar/Wind Harmer
0.227
25326509SID D
Adder
0.666
339236AF1-050_GEN
Solar/Wind Harmer
0.907
339231AF1-038_GEN
Solar/Wind Harmer
0.869
942221AE2-234 GEN
Solar/Wind Harmer
1.672
253378AE2-206_GEN
Solar/Wind Harmer
1.682
945391AF1-204 GEN
Solar/Wind Harmer
6.43
964781AG1-341 GEN
Solar/Wind Harmer
4.886
971485AH1-239 GEN
Solar/Wind Harmer
3.491
966021AG1-471 GEN
Solar/Wind Harmer
2.326
LAGNLTFEXP_LAGN->PJM
CLTF
5.383
TVALTFEXP_TVA->PJM
CLTF
2.678
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.356
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.982
MECLTFEXP_MEC->PJM
CLTF
5.697
SIGELTFEXP_SIGE->PJM
CLTF
0.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.183
NYPJM->LTFIMP_NY
CLTF
1.353
LGEELTFEXP_LGEE->PJM
CLTF
4.807
WECLTFEXP_WEC->PJM
CLTF
1.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.209
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.24 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1620.65
MW Contribution:
6.01
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.92 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1862.17
MW Contribution:
6.35
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.103
24803206KYGER 4HP
50/50
4.094
252516AE2-318_GEN
Solar/Wind Harmer
11.138
25194608D.CRK4
Adder
1.804
252510AF1-249 C
Solar/Wind Harmer
0.456
25196808ZIMRHP
Adder
81.595
25196008MFTGT1
Adder
1.386
253316AC1-085 GEN3
Solar/Wind Harmer
7.629
946171AF1-282 GEN
Solar/Wind Harmer
9.113
945681AF1-233 GEN
Solar/Wind Harmer
17.022
339221AD2-048_GEN
Solar/Wind Harmer
1.291
270273AD2-016 GEN
Solar/Wind Harmer
2.182
253398AE2-221_GEN2
Solar/Wind Harmer
3.688
943111AE2-339 GEN
Solar/Wind Harmer
0.688
270222AC2-111 GEN
Solar/Wind Harmer
3.467
944031AF1-071 GEN
Solar/Wind Harmer
0.78
3429421JKCT 10G
Adder
6.228
3429241JKCT 3G
Adder
8.601
942081AE2-220 GEN
Solar/Wind Harmer
4.139
270209AC1-174_GEN
Solar/Wind Harmer
2.633
270437AC2-090 C
Solar/Wind Harmer
3.612
270239V3-007_GEN1
Solar/Wind Harmer
1.113
339211AE2-254 GEN
Solar/Wind Harmer
0.946
253370AE2-315 SEC1
Adder
1.193
253371AE2-315 SEC2
Adder
1.129
24728605AND G2
Adder
2.269
270005AE1-210 C O1
Solar/Wind Harmer
3.191
25326309TAIT D
Adder
0.632
24803006KYGER 3HP
50/50
4.151
24802806KYGER 2HP
50/50
4.136
24802906KYGER 2LP
50/50
2.427
252509AD1-136 GEN
Solar/Wind Harmer
0.296
25194408D.CRK1
Adder
8.3
25194508D.CRK3
Adder
1.552
25183208HLCRTG
Solar/Wind Harmer
6.57
962581AG1-107 GEN
Solar/Wind Harmer
4.143
961491AF2-440 GEN
Solar/Wind Harmer
1.722
270269AC2-059
Solar/Wind Harmer
7.653
972043AH1-570 GEN
Solar/Wind Harmer
2.049
972045AH1-571 GEN
Solar/Wind Harmer
1.639
971125AH1-004 GEN
Solar/Wind Harmer
3.142
970107AG2-081 GEN
Solar/Wind Harmer
2.356
253415AE1-040 GEN
Solar/Wind Harmer
0.85
942891AE2-308 GEN
Solar/Wind Harmer
7.124
926881AC1-175 GEN
Solar/Wind Harmer
3.612
270383AD1-128 GEN
Solar/Wind Harmer
3.829
253349AC2-067 GEN
Solar/Wind Harmer
1.237
253400AC2-068 GEN
Solar/Wind Harmer
0.497
970883AG2-550 GEN
Solar/Wind Harmer
6.014
970885AG2-551 GEN
Solar/Wind Harmer
1.399
24803106KYGER 3LP
50/50
2.444
24803306KYGER 4LP
50/50
2.394
971191AH1-055 GEN
Solar/Wind Harmer
72.075
252507AC2-088 GEN
Solar/Wind Harmer
2.075
252519AF1-045_GEN
Solar/Wind Harmer
4.054
252524AE2-267 GEN
Solar/Wind Harmer
1.74
25196608WSDLE5
Adder
9.473
25194608D.CRK4
Adder
1.804
25196008MFTGT1
Adder
1.342
958171AF2-111 GEN
Solar/Wind Harmer
24.038
253317AC1-085 GEN4
Solar/Wind Harmer
7.629
946181AF1-283 GEN
Solar/Wind Harmer
11.847
972167AH1-666 GEN
Solar/Wind Harmer
7.254
270367AC2-061_GEN
Solar/Wind Harmer
2.783
339243AC2-075 GEN1
Solar/Wind Harmer
0.389
270186AC1-089 GEN
Solar/Wind Harmer
5.237
253394AE2-221_GEN
Solar/Wind Harmer
3.688
3429391JKCT 9G
Adder
6.228
970093AG2-073 GEN
Solar/Wind Harmer
3.604
24379505HDWTR1G C
Solar/Wind Harmer
5.117
270240V3-007_GEN2
Solar/Wind Harmer
4.003
970455AG2-298 GEN
Solar/Wind Harmer
2.164
253303V4-073 C
Solar/Wind Harmer
0.069
253370AE2-315 SEC1
Adder
1.193
253371AE2-315 SEC2
Adder
1.129
24728505AND G1
Adder
2.269
960071AF2-298 GEN
Solar/Wind Harmer
0.884
270004AE1-209 GEN
Solar/Wind Harmer
3.191
946031AF1-268 GEN
Solar/Wind Harmer
4.773
970653AG2-424 GEN
Solar/Wind Harmer
0.401
970825AG2-519 GEN
Solar/Wind Harmer
3.224
339206AE1-143 GEN
Solar/Wind Harmer
1.186
962031AG1-047 GEN
Solar/Wind Harmer
1.663
957741AF2-068 GEN
Solar/Wind Harmer
8.252
253325AC1-069 GEN
Solar/Wind Harmer
0.546
972273AH1-721 GEN
Adder
41.552
965461AG1-414 GEN
Solar/Wind Harmer
1.12
970289AG2-191 GEN
Solar/Wind Harmer
0.379
247642Z2-115 C
Solar/Wind Harmer
0.03
339255AE2-071 GEN
Solar/Wind Harmer
0.549
339250AF1-203 GEN
Solar/Wind Harmer
0.283
970193AG2-126 GEN
Solar/Wind Harmer
6.925
944531AF1-118 GEN
Solar/Wind Harmer
15.636
270330AC1-082 GEN2
Solar/Wind Helper
0.187
270329AC1-082 GEN1
Solar/Wind Helper
0.187
24802606KYGER 1HP
50/50
4.18
24802706KYGER 1LP
50/50
2.451
24803506KYGER 5LP
50/50
2.394
25250008NTE_CT
50/50
1.874
25250108NTE_ST
50/50
1.428
971985AH1-537 GEN
Solar/Wind Harmer
50.178
25196408WSDLE3
Adder
9.751
25196108MFTGT2
Adder
1.528
25196108MFTGT2
Adder
1.418
253433AC1-085 GEN1
Solar/Wind Harmer
4.843
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
972163AH1-664 GEN
Solar/Wind Harmer
8.928
972165AH1-665 GEN
Solar/Wind Harmer
7.142
339216AC1-074 GEN
Solar/Wind Harmer
1.438
270263AC1-001 GEN
Solar/Wind Harmer
0.863
270340AC2-060 GEN
Solar/Wind Harmer
2.393
253406AD2-031_GEN
Solar/Wind Harmer
0.982
3429211JKCT 2G
Adder
8.489
270356AE2-297 GEN
Solar/Wind Harmer
3.167
270432AC2-029 GEN
Solar/Wind Harmer
4.421
971029AG2-637 GEN
Solar/Wind Harmer
9.394
25306009OHH W.
Adder
1.747
270543AE2-219 C
Solar/Wind Harmer
6.014
253372AE2-315 SEC3
Adder
1.129
253372AE2-315 SEC3
Adder
1.129
247536S-71 GEN
Solar/Wind Harmer
2.339
964611AG1-324 GEN
Solar/Wind Harmer
2.166
961761AG1-017 GEN
Solar/Wind Harmer
0.235
945581AF1-223 GEN
Solar/Wind Harmer
2.407
253338AC1-165 GEN
Solar/Wind Harmer
0.566
253343AC1-166 GEN
Solar/Wind Harmer
0.566
958711AF2-162 GEN
Solar/Wind Harmer
0.502
970289AG2-191 GEN
Solar/Wind Harmer
0.938
270444AC2-157 GEN1
Solar/Wind Harmer
2.7
270445AC2-157 GEN2
Solar/Wind Harmer
2.7
241972AD1-140 GEN
Solar/Wind Harmer
2.089
24729505KEY G4
Adder
2.983
970653AG2-424 GEN
Solar/Wind Harmer
2.774
970825AG2-519 GEN
Solar/Wind Harmer
1.201
339241AF1-083 GEN
Solar/Wind Harmer
0.89
945371AF1-202 GEN
Solar/Wind Harmer
3.703
276903AD2-071 C
Solar/Wind Harmer
5.286
253333AC1-068 GEN
Solar/Wind Harmer
0.546
270594AE1-207 GEN
Solar/Wind Harmer
6.982
270032AE2-172
Solar/Wind Harmer
2.391
958861AF2-177 GEN
Solar/Wind Harmer
5.553
970091AG2-072 GEN
Adder
38.889
964901AG1-354 GEN
Solar/Wind Harmer
7.5
965651AG1-433 GEN
Solar/Wind Harmer
2.711
270024AE2-089 GEN
Solar/Wind Harmer
2.306
960001AF2-291 GEN
Solar/Wind Helper
1.678
270331AC1-082 GEN3
Solar/Wind Helper
0.186
964571AG1-320 GEN
Solar/Wind Harmer
4.901
253370AE2-315 SEC1
Adder
1.193
25322209TAIT E
Adder
5.625
25322209TAIT E
Adder
5.499
247621Y3-024
Adder
0.136
964611AG1-324 GEN
Solar/Wind Harmer
0.291
270201AC2-176 GEN
Solar/Wind Harmer
2.828
25326109MON D
Adder
0.721
24725505WLD G2 C
Solar/Wind Harmer
2.164
24699105WLD G1 C
Solar/Wind Harmer
2.139
270031AE2-169
Solar/Wind Harmer
4.312
270599AE1-208 GEN
Solar/Wind Harmer
4.312
339236AF1-050_GEN
Solar/Wind Harmer
0.916
944541AF1-119 GEN
Solar/Wind Harmer
2.077
960971AF2-388 GEN
Solar/Wind Harmer
5.423
970291AG2-192 GEN
Solar/Wind Harmer
0.642
970291AG2-192 GEN
Solar/Wind Harmer
0.207
339231AF1-038_GEN
Solar/Wind Harmer
0.877
964781AG1-341 GEN
Solar/Wind Harmer
4.932
945391AF1-204 GEN
Solar/Wind Harmer
6.434
942221AE2-234 GEN
Solar/Wind Harmer
1.6
971485AH1-239 GEN
Solar/Wind Harmer
3.524
966021AG1-471 GEN
Solar/Wind Harmer
2.348
LAGNLTFEXP_LAGN->PJM
CLTF
5.472
TVALTFEXP_TVA->PJM
CLTF
2.709
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.578
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.139
MECLTFEXP_MEC->PJM
CLTF
5.918
SIGELTFEXP_SIGE->PJM
CLTF
0.295
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.539
NYPJM->LTFIMP_NY
CLTF
1.375
LGEELTFEXP_LGEE->PJM
CLTF
4.87
WECLTFEXP_WEC->PJM
CLTF
1.323
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.209
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.127

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1616.13
MW Contribution:
5.91
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.49 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1763.1
MW Contribution:
6.22
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.093
24803206KYGER 4HP
50/50
4.084
252516AE2-318_GEN
Solar/Wind Harmer
10.14
25196808ZIMRHP
Adder
75.73
25194608D.CRK4
Adder
1.602
252510AF1-249 C
Solar/Wind Harmer
0.406
253316AC1-085 GEN3
Solar/Wind Harmer
8.104
946171AF1-282 GEN
Solar/Wind Harmer
9.68
25196008MFTGT1
Adder
1.281
253398AE2-221_GEN2
Solar/Wind Harmer
4.119
945681AF1-233 GEN
Solar/Wind Harmer
16.525
270273AD2-016 GEN
Solar/Wind Harmer
2.214
339221AD2-048_GEN
Solar/Wind Harmer
1.241
253370AE2-315 SEC1
Adder
1.524
253371AE2-315 SEC2
Adder
1.442
270222AC2-111 GEN
Solar/Wind Harmer
3.38
944031AF1-071 GEN
Solar/Wind Harmer
0.76
943111AE2-339 GEN
Solar/Wind Harmer
0.662
25326309TAIT D
Adder
0.804
3429421JKCT 10G
Adder
5.997
3429241JKCT 3G
Adder
8.274
942081AE2-220 GEN
Solar/Wind Harmer
3.941
270209AC1-174_GEN
Solar/Wind Harmer
2.508
270437AC2-090 C
Solar/Wind Harmer
3.439
270239V3-007_GEN1
Solar/Wind Harmer
1.06
339211AE2-254 GEN
Solar/Wind Harmer
0.904
24728605AND G2
Adder
2.168
253333AC1-068 GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
3.058
970825AG2-519 GEN
Solar/Wind Harmer
1.156
970653AG2-424 GEN
Solar/Wind Harmer
2.64
945371AF1-202 GEN
Solar/Wind Harmer
3.569
339241AF1-083 GEN
Solar/Wind Harmer
0.848
276903AD2-071 C
Solar/Wind Harmer
5.097
270594AE1-207 GEN
Solar/Wind Harmer
6.753
270032AE2-172
Solar/Wind Harmer
2.313
958861AF2-177 GEN
Solar/Wind Harmer
5.366
970091AG2-072 GEN
Adder
37.252
270024AE2-089 GEN
Solar/Wind Harmer
2.261
965651AG1-433 GEN
Solar/Wind Harmer
2.624
964901AG1-354 GEN
Solar/Wind Harmer
7.132
960001AF2-291 GEN
Solar/Wind Helper
1.683
270331AC1-082 GEN3
Solar/Wind Helper
0.187
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.388
971191AH1-055 GEN
Solar/Wind Harmer
71.816
252507AC2-088 GEN
Solar/Wind Harmer
1.953
252519AF1-045_GEN
Solar/Wind Harmer
3.69
25194608D.CRK4
Adder
1.602
252524AE2-267 GEN
Solar/Wind Harmer
1.534
25196608WSDLE5
Adder
8.347
253317AC1-085 GEN4
Solar/Wind Harmer
8.104
946181AF1-283 GEN
Solar/Wind Harmer
12.584
958171AF2-111 GEN
Solar/Wind Harmer
23.383
25196008MFTGT1
Adder
1.241
253394AE2-221_GEN
Solar/Wind Harmer
4.119
972167AH1-666 GEN
Solar/Wind Harmer
7.042
270367AC2-061_GEN
Solar/Wind Harmer
2.733
270186AC1-089 GEN
Solar/Wind Harmer
5.181
339243AC2-075 GEN1
Solar/Wind Harmer
0.374
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.524
253371AE2-315 SEC2
Adder
1.442
960071AF2-298 GEN
Solar/Wind Harmer
1.097
3429391JKCT 9G
Adder
5.997
970093AG2-073 GEN
Solar/Wind Harmer
3.458
24379505HDWTR1G C
Solar/Wind Harmer
4.872
270240V3-007_GEN2
Solar/Wind Harmer
3.812
970455AG2-298 GEN
Solar/Wind Harmer
2.061
24728505AND G1
Adder
2.168
253325AC1-069 GEN
Solar/Wind Harmer
0.59
270004AE1-209 GEN
Solar/Wind Harmer
3.058
946031AF1-268 GEN
Solar/Wind Harmer
4.604
970825AG2-519 GEN
Solar/Wind Harmer
3.105
970653AG2-424 GEN
Solar/Wind Harmer
0.382
962031AG1-047 GEN
Solar/Wind Harmer
1.62
957741AF2-068 GEN
Solar/Wind Harmer
8.036
339206AE1-143 GEN
Solar/Wind Harmer
1.13
270518AE2-148 GEN
Solar/Wind Harmer
6.093
965461AG1-414 GEN
Solar/Wind Harmer
1.085
970289AG2-191 GEN
Solar/Wind Harmer
0.367
972273AH1-721 GEN
Adder
39.573
276820AF1-078_GEN
Solar/Wind Harmer
0.74
247642Z2-115 C
Solar/Wind Harmer
0.029
970193AG2-126 GEN
Solar/Wind Harmer
6.675
339255AE2-071 GEN
Solar/Wind Harmer
0.521
339250AF1-203 GEN
Solar/Wind Harmer
0.268
944531AF1-118 GEN
Solar/Wind Harmer
15.239
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24803006KYGER 3HP
50/50
4.141
24802806KYGER 2HP
50/50
4.126
24802906KYGER 2LP
50/50
2.422
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.279
25183208HLCRTG
Solar/Wind Harmer
6.246
25194408D.CRK1
Adder
7.371
25194508D.CRK3
Adder
1.378
962581AG1-107 GEN
Solar/Wind Harmer
4.214
961491AF2-440 GEN
Solar/Wind Harmer
1.751
270269AC2-059
Solar/Wind Harmer
7.764
253415AE1-040 GEN
Solar/Wind Harmer
0.907
972043AH1-570 GEN
Solar/Wind Harmer
1.972
972045AH1-571 GEN
Solar/Wind Harmer
1.578
253370AE2-315 SEC1
Adder
1.524
971125AH1-004 GEN
Solar/Wind Harmer
3.022
970107AG2-081 GEN
Solar/Wind Harmer
2.267
25322209TAIT E
Adder
7.158
25322209TAIT E
Adder
6.998
253349AC2-067 GEN
Solar/Wind Harmer
1.474
253400AC2-068 GEN
Solar/Wind Harmer
0.593
25326109MON D
Adder
0.94
942891AE2-308 GEN
Solar/Wind Harmer
6.845
926881AC1-175 GEN
Solar/Wind Harmer
3.439
270383AD1-128 GEN
Solar/Wind Harmer
3.701
970883AG2-550 GEN
Solar/Wind Harmer
5.912
970885AG2-551 GEN
Solar/Wind Harmer
1.375
964571AG1-320 GEN
Solar/Wind Harmer
4.664
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.282
270201AC2-176 GEN
Solar/Wind Harmer
2.754
24725505WLD G2 C
Solar/Wind Harmer
2.084
24699105WLD G1 C
Solar/Wind Harmer
2.059
270031AE2-169
Solar/Wind Harmer
4.168
270599AE1-208 GEN
Solar/Wind Harmer
4.168
25326509SID D
Adder
0.658
944541AF1-119 GEN
Solar/Wind Harmer
2.011
960971AF2-388 GEN
Solar/Wind Harmer
5.248
339236AF1-050_GEN
Solar/Wind Harmer
0.871
970291AG2-192 GEN
Solar/Wind Harmer
0.622
970291AG2-192 GEN
Solar/Wind Harmer
0.2
253378AE2-206_GEN
Solar/Wind Harmer
1.666
339231AF1-038_GEN
Solar/Wind Harmer
0.834
942221AE2-234 GEN
Solar/Wind Harmer
1.568
945391AF1-204 GEN
Solar/Wind Harmer
6.202
964781AG1-341 GEN
Solar/Wind Harmer
4.685
24802606KYGER 1HP
50/50
4.171
24802706KYGER 1LP
50/50
2.446
24803506KYGER 5LP
50/50
2.388
971985AH1-537 GEN
Solar/Wind Harmer
49.138
25196408WSDLE3
Adder
8.592
253433AC1-085 GEN1
Solar/Wind Harmer
5.144
253432AC1-085 GEN2
Solar/Wind Harmer
0.259
25196108MFTGT2
Adder
1.412
25196108MFTGT2
Adder
1.312
972163AH1-664 GEN
Solar/Wind Harmer
8.663
972165AH1-665 GEN
Solar/Wind Harmer
6.93
253406AD2-031_GEN
Solar/Wind Harmer
1.092
270263AC1-001 GEN
Solar/Wind Harmer
0.871
270340AC2-060 GEN
Solar/Wind Harmer
2.516
339216AC1-074 GEN
Solar/Wind Harmer
1.38
253372AE2-315 SEC3
Adder
1.442
253372AE2-315 SEC3
Adder
1.442
25306009OHH W.
Adder
2.151
3429211JKCT 2G
Adder
8.167
270356AE2-297 GEN
Solar/Wind Harmer
3.013
270432AC2-029 GEN
Solar/Wind Harmer
4.541
971029AG2-637 GEN
Solar/Wind Harmer
9.271
241972AD1-140 GEN
Solar/Wind Harmer
2.765
270543AE2-219 C
Solar/Wind Harmer
5.912
247536S-71 GEN
Solar/Wind Harmer
2.291
253338AC1-165 GEN
Solar/Wind Harmer
0.612
253343AC1-166 GEN
Solar/Wind Harmer
0.612
964611AG1-324 GEN
Solar/Wind Harmer
2.105
961761AG1-017 GEN
Solar/Wind Harmer
0.229
945581AF1-223 GEN
Solar/Wind Harmer
2.32
958711AF2-162 GEN
Solar/Wind Harmer
0.486
970289AG2-191 GEN
Solar/Wind Harmer
0.909
270444AC2-157 GEN1
Solar/Wind Harmer
2.592
270445AC2-157 GEN2
Solar/Wind Harmer
2.592
24729505KEY G4
Adder
2.902
LAGNLTFEXP_LAGN->PJM
CLTF
5.198
TVALTFEXP_TVA->PJM
CLTF
2.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.966
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.434
MECLTFEXP_MEC->PJM
CLTF
5.745
SIGELTFEXP_SIGE->PJM
CLTF
0.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.364
NYPJM->LTFIMP_NY
CLTF
1.355
LGEELTFEXP_LGEE->PJM
CLTF
4.619
WECLTFEXP_WEC->PJM
CLTF
1.296
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.249
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT5_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT5_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.91 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1600.21
MW Contribution:
5.91
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT5_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.35 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1745.55
MW Contribution:
6.22
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.094
24803206KYGER 4HP
50/50
4.085
252516AE2-318_GEN
Solar/Wind Harmer
10.142
25196808ZIMRHP
Adder
75.748
25194608D.CRK4
Adder
1.603
252510AF1-249 C
Solar/Wind Harmer
0.406
253316AC1-085 GEN3
Solar/Wind Harmer
8.106
946171AF1-282 GEN
Solar/Wind Harmer
9.682
25196008MFTGT1
Adder
1.282
253398AE2-221_GEN2
Solar/Wind Harmer
4.12
945681AF1-233 GEN
Solar/Wind Harmer
16.529
270273AD2-016 GEN
Solar/Wind Harmer
2.214
339221AD2-048_GEN
Solar/Wind Harmer
1.241
253370AE2-315 SEC1
Adder
1.525
253371AE2-315 SEC2
Adder
1.442
270222AC2-111 GEN
Solar/Wind Harmer
3.381
944031AF1-071 GEN
Solar/Wind Harmer
0.761
943111AE2-339 GEN
Solar/Wind Harmer
0.663
25326309TAIT D
Adder
0.804
3429421JKCT 10G
Adder
5.999
3429241JKCT 3G
Adder
8.277
942081AE2-220 GEN
Solar/Wind Harmer
3.942
270209AC1-174_GEN
Solar/Wind Harmer
2.508
270437AC2-090 C
Solar/Wind Harmer
3.44
270239V3-007_GEN1
Solar/Wind Harmer
1.061
339211AE2-254 GEN
Solar/Wind Harmer
0.905
24728605AND G2
Adder
2.169
253333AC1-068 GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
3.06
970825AG2-519 GEN
Solar/Wind Harmer
1.157
970653AG2-424 GEN
Solar/Wind Harmer
2.641
945371AF1-202 GEN
Solar/Wind Harmer
3.57
339241AF1-083 GEN
Solar/Wind Harmer
0.848
276903AD2-071 C
Solar/Wind Harmer
5.099
270594AE1-207 GEN
Solar/Wind Harmer
6.756
270032AE2-172
Solar/Wind Harmer
2.314
958861AF2-177 GEN
Solar/Wind Harmer
5.369
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.389
971191AH1-055 GEN
Solar/Wind Harmer
71.821
252507AC2-088 GEN
Solar/Wind Harmer
1.953
252519AF1-045_GEN
Solar/Wind Harmer
3.691
25194608D.CRK4
Adder
1.603
252524AE2-267 GEN
Solar/Wind Harmer
1.534
25196608WSDLE5
Adder
8.349
253317AC1-085 GEN4
Solar/Wind Harmer
8.106
946181AF1-283 GEN
Solar/Wind Harmer
12.587
958171AF2-111 GEN
Solar/Wind Harmer
23.388
25196008MFTGT1
Adder
1.241
253394AE2-221_GEN
Solar/Wind Harmer
4.12
24803006KYGER 3HP
50/50
4.142
24802806KYGER 2HP
50/50
4.126
24802906KYGER 2LP
50/50
2.422
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.279
25183208HLCRTG
Solar/Wind Harmer
6.247
25194408D.CRK1
Adder
7.373
25194508D.CRK3
Adder
1.378
962581AG1-107 GEN
Solar/Wind Harmer
4.215
961491AF2-440 GEN
Solar/Wind Harmer
1.752
270269AC2-059
Solar/Wind Harmer
7.766
253415AE1-040 GEN
Solar/Wind Harmer
0.908
972043AH1-570 GEN
Solar/Wind Harmer
1.973
972045AH1-571 GEN
Solar/Wind Harmer
1.578
253370AE2-315 SEC1
Adder
1.525
971125AH1-004 GEN
Solar/Wind Harmer
3.023
970107AG2-081 GEN
Solar/Wind Harmer
2.267
25322209TAIT E
Adder
7.161
25322209TAIT E
Adder
7
253349AC2-067 GEN
Solar/Wind Harmer
1.474
253400AC2-068 GEN
Solar/Wind Harmer
0.593
25326109MON D
Adder
0.94
942891AE2-308 GEN
Solar/Wind Harmer
6.847
926881AC1-175 GEN
Solar/Wind Harmer
3.44
270383AD1-128 GEN
Solar/Wind Harmer
3.703
970883AG2-550 GEN
Solar/Wind Harmer
5.914
970885AG2-551 GEN
Solar/Wind Harmer
1.375
964571AG1-320 GEN
Solar/Wind Harmer
4.665
247621Y3-024
Adder
0.133
970091AG2-072 GEN
Adder
37.27
270024AE2-089 GEN
Solar/Wind Harmer
2.262
965651AG1-433 GEN
Solar/Wind Harmer
2.625
964901AG1-354 GEN
Solar/Wind Harmer
7.136
960001AF2-291 GEN
Solar/Wind Helper
1.683
270331AC1-082 GEN3
Solar/Wind Helper
0.187
24802606KYGER 1HP
50/50
4.171
24802706KYGER 1LP
50/50
2.446
24803506KYGER 5LP
50/50
2.389
971985AH1-537 GEN
Solar/Wind Harmer
49.142
25196408WSDLE3
Adder
8.594
253433AC1-085 GEN1
Solar/Wind Harmer
5.145
253432AC1-085 GEN2
Solar/Wind Harmer
0.259
25196108MFTGT2
Adder
1.413
25196108MFTGT2
Adder
1.312
972163AH1-664 GEN
Solar/Wind Harmer
8.665
972165AH1-665 GEN
Solar/Wind Harmer
6.932
253406AD2-031_GEN
Solar/Wind Harmer
1.092
270263AC1-001 GEN
Solar/Wind Harmer
0.871
270340AC2-060 GEN
Solar/Wind Harmer
2.517
339216AC1-074 GEN
Solar/Wind Harmer
1.38
253372AE2-315 SEC3
Adder
1.442
253372AE2-315 SEC3
Adder
1.442
25306009OHH W.
Adder
2.152
3429211JKCT 2G
Adder
8.17
270356AE2-297 GEN
Solar/Wind Harmer
3.014
270432AC2-029 GEN
Solar/Wind Harmer
4.543
971029AG2-637 GEN
Solar/Wind Harmer
9.275
241972AD1-140 GEN
Solar/Wind Harmer
2.767
270543AE2-219 C
Solar/Wind Harmer
5.914
247536S-71 GEN
Solar/Wind Harmer
2.292
253338AC1-165 GEN
Solar/Wind Harmer
0.612
253343AC1-166 GEN
Solar/Wind Harmer
0.612
964611AG1-324 GEN
Solar/Wind Harmer
2.106
961761AG1-017 GEN
Solar/Wind Harmer
0.229
945581AF1-223 GEN
Solar/Wind Harmer
2.321
958711AF2-162 GEN
Solar/Wind Harmer
0.486
970289AG2-191 GEN
Solar/Wind Harmer
0.909
270444AC2-157 GEN1
Solar/Wind Harmer
2.593
270445AC2-157 GEN2
Solar/Wind Harmer
2.593
24729505KEY G4
Adder
2.903
972167AH1-666 GEN
Solar/Wind Harmer
7.044
270367AC2-061_GEN
Solar/Wind Harmer
2.734
270186AC1-089 GEN
Solar/Wind Harmer
5.183
339243AC2-075 GEN1
Solar/Wind Harmer
0.374
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.525
253371AE2-315 SEC2
Adder
1.442
960071AF2-298 GEN
Solar/Wind Harmer
1.097
3429391JKCT 9G
Adder
5.999
970093AG2-073 GEN
Solar/Wind Harmer
3.46
24379505HDWTR1G C
Solar/Wind Harmer
4.874
270240V3-007_GEN2
Solar/Wind Harmer
3.813
970455AG2-298 GEN
Solar/Wind Harmer
2.061
24728505AND G1
Adder
2.169
253325AC1-069 GEN
Solar/Wind Harmer
0.59
270004AE1-209 GEN
Solar/Wind Harmer
3.06
946031AF1-268 GEN
Solar/Wind Harmer
4.606
970825AG2-519 GEN
Solar/Wind Harmer
3.106
970653AG2-424 GEN
Solar/Wind Harmer
0.382
962031AG1-047 GEN
Solar/Wind Harmer
1.621
957741AF2-068 GEN
Solar/Wind Harmer
8.04
339206AE1-143 GEN
Solar/Wind Harmer
1.131
270518AE2-148 GEN
Solar/Wind Harmer
6.095
965461AG1-414 GEN
Solar/Wind Harmer
1.085
970289AG2-191 GEN
Solar/Wind Harmer
0.367
972273AH1-721 GEN
Adder
39.592
276820AF1-078_GEN
Solar/Wind Harmer
0.741
247642Z2-115 C
Solar/Wind Harmer
0.029
970193AG2-126 GEN
Solar/Wind Harmer
6.679
339255AE2-071 GEN
Solar/Wind Harmer
0.522
339250AF1-203 GEN
Solar/Wind Harmer
0.269
944531AF1-118 GEN
Solar/Wind Harmer
15.247
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
2.755
24725505WLD G2 C
Solar/Wind Harmer
2.085
24699105WLD G1 C
Solar/Wind Harmer
2.06
270031AE2-169
Solar/Wind Harmer
4.17
270599AE1-208 GEN
Solar/Wind Harmer
4.17
25326509SID D
Adder
0.658
944541AF1-119 GEN
Solar/Wind Harmer
2.012
960971AF2-388 GEN
Solar/Wind Harmer
5.251
339236AF1-050_GEN
Solar/Wind Harmer
0.871
970291AG2-192 GEN
Solar/Wind Harmer
0.622
970291AG2-192 GEN
Solar/Wind Harmer
0.2
253378AE2-206_GEN
Solar/Wind Harmer
1.667
339231AF1-038_GEN
Solar/Wind Harmer
0.835
942221AE2-234 GEN
Solar/Wind Harmer
1.569
945391AF1-204 GEN
Solar/Wind Harmer
6.205
964781AG1-341 GEN
Solar/Wind Harmer
4.687
LAGNLTFEXP_LAGN->PJM
CLTF
5.203
TVALTFEXP_TVA->PJM
CLTF
2.563
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.443
MECLTFEXP_MEC->PJM
CLTF
5.749
SIGELTFEXP_SIGE->PJM
CLTF
0.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.395
NYPJM->LTFIMP_NY
CLTF
1.353
LGEELTFEXP_LGEE->PJM
CLTF
4.621
WECLTFEXP_WEC->PJM
CLTF
1.297
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.248
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#316_05AMOS 765_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#316_05AMOS 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1560.82
MW Contribution:
5.92
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#316_05AMOS 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.21 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1789.67
MW Contribution:
6.28
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.421
24803306KYGER 4LP
50/50
2.371
971191AH1-055 GEN
Solar/Wind Harmer
71.356
252507AC2-088 GEN
Solar/Wind Harmer
1.948
252519AF1-045_GEN
Solar/Wind Harmer
3.681
25194608D.CRK4
Adder
1.599
252524AE2-267 GEN
Solar/Wind Harmer
1.53
25196608WSDLE5
Adder
8.33
253317AC1-085 GEN4
Solar/Wind Harmer
8.083
946181AF1-283 GEN
Solar/Wind Harmer
12.551
958171AF2-111 GEN
Solar/Wind Harmer
23.332
25196008MFTGT1
Adder
1.239
253394AE2-221_GEN
Solar/Wind Harmer
4.108
972167AH1-666 GEN
Solar/Wind Harmer
7.022
270367AC2-061_GEN
Solar/Wind Harmer
2.716
270186AC1-089 GEN
Solar/Wind Harmer
5.151
339243AC2-075 GEN1
Solar/Wind Harmer
0.373
253303V4-073 C
Solar/Wind Harmer
0.088
253370AE2-315 SEC1
Adder
1.521
253371AE2-315 SEC2
Adder
1.438
960071AF2-298 GEN
Solar/Wind Harmer
1.095
3429391JKCT 9G
Adder
5.993
970093AG2-073 GEN
Solar/Wind Harmer
3.456
24379505HDWTR1G C
Solar/Wind Harmer
4.879
270240V3-007_GEN2
Solar/Wind Harmer
3.817
970455AG2-298 GEN
Solar/Wind Harmer
2.065
24728505AND G1
Adder
2.175
253325AC1-069 GEN
Solar/Wind Harmer
0.588
270004AE1-209 GEN
Solar/Wind Harmer
3.065
946031AF1-268 GEN
Solar/Wind Harmer
4.614
970825AG2-519 GEN
Solar/Wind Harmer
3.112
970653AG2-424 GEN
Solar/Wind Harmer
0.383
962031AG1-047 GEN
Solar/Wind Harmer
1.623
957741AF2-068 GEN
Solar/Wind Harmer
8.053
339206AE1-143 GEN
Solar/Wind Harmer
1.133
270518AE2-148 GEN
Solar/Wind Harmer
6.079
965461AG1-414 GEN
Solar/Wind Harmer
1.089
970289AG2-191 GEN
Solar/Wind Harmer
0.369
972273AH1-721 GEN
Adder
39.657
276820AF1-078_GEN
Solar/Wind Harmer
0.74
247642Z2-115 C
Solar/Wind Harmer
0.03
970193AG2-126 GEN
Solar/Wind Harmer
6.722
339255AE2-071 GEN
Solar/Wind Harmer
0.524
339250AF1-203 GEN
Solar/Wind Harmer
0.27
944531AF1-118 GEN
Solar/Wind Harmer
15.299
270330AC1-082 GEN2
Solar/Wind Helper
0.209
270329AC1-082 GEN1
Solar/Wind Helper
0.209
24802606KYGER 1HP
50/50
4.141
24802706KYGER 1LP
50/50
2.428
24803506KYGER 5LP
50/50
2.371
971985AH1-537 GEN
Solar/Wind Harmer
48.849
25196408WSDLE3
Adder
8.575
253433AC1-085 GEN1
Solar/Wind Harmer
5.13
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
25196108MFTGT2
Adder
1.411
25196108MFTGT2
Adder
1.31
972163AH1-664 GEN
Solar/Wind Harmer
8.638
972165AH1-665 GEN
Solar/Wind Harmer
6.911
253406AD2-031_GEN
Solar/Wind Harmer
1.088
270340AC2-060 GEN
Solar/Wind Harmer
2.501
270263AC1-001 GEN
Solar/Wind Harmer
0.862
339216AC1-074 GEN
Solar/Wind Harmer
1.378
253372AE2-315 SEC3
Adder
1.438
253372AE2-315 SEC3
Adder
1.438
25306009OHH W.
Adder
2.146
3429211JKCT 2G
Adder
8.16
270356AE2-297 GEN
Solar/Wind Harmer
3.016
270432AC2-029 GEN
Solar/Wind Harmer
4.502
971029AG2-637 GEN
Solar/Wind Harmer
9.279
241972AD1-140 GEN
Solar/Wind Harmer
2.76
270543AE2-219 C
Solar/Wind Harmer
5.919
247536S-71 GEN
Solar/Wind Harmer
2.295
253338AC1-165 GEN
Solar/Wind Harmer
0.61
253343AC1-166 GEN
Solar/Wind Harmer
0.61
964611AG1-324 GEN
Solar/Wind Harmer
2.11
961761AG1-017 GEN
Solar/Wind Harmer
0.23
945581AF1-223 GEN
Solar/Wind Harmer
2.326
958711AF2-162 GEN
Solar/Wind Harmer
0.487
970289AG2-191 GEN
Solar/Wind Harmer
0.913
270444AC2-157 GEN1
Solar/Wind Harmer
2.615
24803406KYGER 5HP
50/50
4.064
24803206KYGER 4HP
50/50
4.055
252516AE2-318_GEN
Solar/Wind Harmer
10.115
25196808ZIMRHP
Adder
75.568
25194608D.CRK4
Adder
1.599
252510AF1-249 C
Solar/Wind Harmer
0.405
253316AC1-085 GEN3
Solar/Wind Harmer
8.083
946171AF1-282 GEN
Solar/Wind Harmer
9.655
25196008MFTGT1
Adder
1.28
253398AE2-221_GEN2
Solar/Wind Harmer
4.108
945681AF1-233 GEN
Solar/Wind Harmer
16.478
270273AD2-016 GEN
Solar/Wind Harmer
2.198
339221AD2-048_GEN
Solar/Wind Harmer
1.239
253370AE2-315 SEC1
Adder
1.521
253371AE2-315 SEC2
Adder
1.438
270222AC2-111 GEN
Solar/Wind Harmer
3.377
944031AF1-071 GEN
Solar/Wind Harmer
0.76
943111AE2-339 GEN
Solar/Wind Harmer
0.662
25326309TAIT D
Adder
0.802
3429421JKCT 10G
Adder
5.993
3429241JKCT 3G
Adder
8.267
942081AE2-220 GEN
Solar/Wind Harmer
3.946
270209AC1-174_GEN
Solar/Wind Harmer
2.511
270437AC2-090 C
Solar/Wind Harmer
3.444
270239V3-007_GEN1
Solar/Wind Harmer
1.062
339211AE2-254 GEN
Solar/Wind Harmer
0.905
24728605AND G2
Adder
2.175
253333AC1-068 GEN
Solar/Wind Harmer
0.588
270005AE1-210 C O1
Solar/Wind Harmer
3.065
970825AG2-519 GEN
Solar/Wind Harmer
1.159
970653AG2-424 GEN
Solar/Wind Harmer
2.647
945371AF1-202 GEN
Solar/Wind Harmer
3.579
276903AD2-071 C
Solar/Wind Harmer
5.115
339241AF1-083 GEN
Solar/Wind Harmer
0.85
270594AE1-207 GEN
Solar/Wind Harmer
6.778
270032AE2-172
Solar/Wind Harmer
2.321
958861AF2-177 GEN
Solar/Wind Harmer
5.382
970091AG2-072 GEN
Adder
37.724
270024AE2-089 GEN
Solar/Wind Harmer
2.267
965651AG1-433 GEN
Solar/Wind Harmer
2.633
964901AG1-354 GEN
Solar/Wind Harmer
7.156
960001AF2-291 GEN
Solar/Wind Helper
1.773
270331AC1-082 GEN3
Solar/Wind Helper
0.208
235780M24_1
Solar/Wind Helper
0.552
24803006KYGER 3HP
50/50
4.111
24802806KYGER 2HP
50/50
4.096
24802906KYGER 2LP
50/50
2.404
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.278
25183208HLCRTG
Solar/Wind Harmer
6.23
25194408D.CRK1
Adder
7.356
25194508D.CRK3
Adder
1.375
962581AG1-107 GEN
Solar/Wind Harmer
4.188
961491AF2-440 GEN
Solar/Wind Harmer
1.741
270269AC2-059
Solar/Wind Harmer
7.708
253415AE1-040 GEN
Solar/Wind Harmer
0.902
972043AH1-570 GEN
Solar/Wind Harmer
1.969
972045AH1-571 GEN
Solar/Wind Harmer
1.575
253370AE2-315 SEC1
Adder
1.521
971125AH1-004 GEN
Solar/Wind Harmer
3.019
970107AG2-081 GEN
Solar/Wind Harmer
2.264
25322209TAIT E
Adder
7.143
25322209TAIT E
Adder
6.983
253349AC2-067 GEN
Solar/Wind Harmer
1.471
253400AC2-068 GEN
Solar/Wind Harmer
0.592
25326109MON D
Adder
0.938
942891AE2-308 GEN
Solar/Wind Harmer
6.839
926881AC1-175 GEN
Solar/Wind Harmer
3.444
270383AD1-128 GEN
Solar/Wind Harmer
3.706
970883AG2-550 GEN
Solar/Wind Harmer
5.919
970885AG2-551 GEN
Solar/Wind Harmer
1.376
964571AG1-320 GEN
Solar/Wind Harmer
4.676
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
2.759
24725505WLD G2 C
Solar/Wind Harmer
2.091
24699105WLD G1 C
Solar/Wind Harmer
2.066
270031AE2-169
Solar/Wind Harmer
4.18
270599AE1-208 GEN
Solar/Wind Harmer
4.18
25326509SID D
Adder
0.657
944541AF1-119 GEN
Solar/Wind Harmer
2.017
960971AF2-388 GEN
Solar/Wind Harmer
5.265
339236AF1-050_GEN
Solar/Wind Harmer
0.874
970291AG2-192 GEN
Solar/Wind Harmer
0.625
970291AG2-192 GEN
Solar/Wind Harmer
0.201
253378AE2-206_GEN
Solar/Wind Harmer
1.665
339231AF1-038_GEN
Solar/Wind Harmer
0.837
942221AE2-234 GEN
Solar/Wind Harmer
1.574
945391AF1-204 GEN
Solar/Wind Harmer
6.245
964781AG1-341 GEN
Solar/Wind Harmer
4.704
237033AB1-150 GEN
Solar/Wind Helper
0.445
270445AC2-157 GEN2
Solar/Wind Harmer
2.615
24729505KEY G4
Adder
2.912
LAGNLTFEXP_LAGN->PJM
CLTF
5.253
TVALTFEXP_TVA->PJM
CLTF
2.588
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.217
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.528
MECLTFEXP_MEC->PJM
CLTF
5.794
SIGELTFEXP_SIGE->PJM
CLTF
0.282
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.728
NYPJM->LTFIMP_NY
CLTF
1.332
LGEELTFEXP_LGEE->PJM
CLTF
4.629
WECLTFEXP_WEC->PJM
CLTF
1.307
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.235
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126

Details for 08MCGFY1-08LOCST1 69.0 kV Ckt 1 line l/o DEOK_P_CIRCUIT3281&13803_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DEO&K
Facility Description:
08MCGFY1-08LOCST1 69.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT3281&13803_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.84 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:64.71
MW Contribution:
2.49
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DEO&K
Facility Description:
08MCGFY1-08LOCST1 69.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT3281&13803_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:127.39 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:68.79
MW Contribution:
2.5
Bus #Bus NameTypeMW Contribution
270222AC2-111 GEN
Solar/Wind Harmer
3.07
944031AF1-071 GEN
Solar/Wind Harmer
0.691
971029AG2-637 GEN
Solar/Wind Harmer
4.542
970883AG2-550 GEN
Solar/Wind Harmer
2.494
970885AG2-551 GEN
Solar/Wind Harmer
0.58
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
0.061
TVALTFEXP_TVA->PJM
CLTF
0.013
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.01
MECLTFEXP_MEC->PJM
CLTF
0.162
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.883
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.015
WECLTFEXP_WEC->PJM
CLTF
0.044
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_05MARYSV 765_A_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_05MARYSV 765_A_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.61 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1935.5
MW Contribution:
5.43
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
44.712
24727105RPMNG2
50/50
3.25
970583AG2-370 GEN
50/50
2.58
965021AG1-366 GEN
Solar/Wind Harmer
4.327
270043AE2-236 GEN
Solar/Wind Harmer
5.578
270063AE2-323 C
Solar/Wind Harmer
2.004
944531AF1-118 GEN
Solar/Wind Harmer
30.953
24695305TIMB G C
Solar/Wind Harmer
2.723
247643Z2-116 C
Solar/Wind Harmer
0.049
962031AG1-047 GEN
Solar/Wind Harmer
2.06
957741AF2-068 GEN
Solar/Wind Harmer
10.222
945111AF1-176 GEN
Solar/Wind Harmer
3.848
270505AE1-170 C O1
Solar/Wind Harmer
9.863
971347AH1-153 GEN
Solar/Wind Harmer
3.198
24441505OLIV SLR
Solar/Wind Harmer
0.084
946031AF1-268 GEN
Solar/Wind Harmer
5.053
270004AE1-209 GEN
Solar/Wind Harmer
3.321
970825AG2-519 GEN
Solar/Wind Harmer
3.37
24727005RPMNG1
50/50
3.25
960861AF2-377 GEN
50/50
2.2
965421AG1-410 GEN
Solar/Wind Harmer
115.358
965011AG1-365 GEN
Solar/Wind Harmer
18.606
270024AE2-089 GEN
Solar/Wind Harmer
4.038
965651AG1-433 GEN
Solar/Wind Harmer
4.288
958861AF2-177 GEN
Solar/Wind Harmer
8.314
24639705ELKHART HY
Adder
0.115
945371AF1-202 GEN
Solar/Wind Harmer
4.987
270216AD2-079_GEN
Solar/Wind Harmer
0.431
945111AF1-176 GEN
Solar/Wind Harmer
12.142
24727205RPMNG3
50/50
3.231
959331AF2-224 GEN
Solar/Wind Harmer
18.606
963791AG1-232 GEN
Solar/Wind Harmer
15.633
965041AG1-368 GEN
Solar/Wind Harmer
11.094
970031AG2-029 GEN
Solar/Wind Harmer
26.426
247521TR3_G114
Solar/Wind Harmer
3.178
270191TR4_S_V150
Solar/Wind Harmer
2.836
965051AG1-369 GEN
Solar/Wind Harmer
4.721
270071AF1-092 GEN
Solar/Wind Harmer
13.726
24729505KEY G4
Adder
5.566
958711AF2-162 GEN
Solar/Wind Harmer
0.794
945581AF1-223 GEN
Solar/Wind Harmer
3.242
961761AG1-017 GEN
Solar/Wind Harmer
0.292
964611AG1-324 GEN
Solar/Wind Harmer
2.597
971771AH1-392 GEN
Solar/Wind Harmer
5.97
270526AF1-158 GEN
Solar/Wind Harmer
2.886
944161AF1-084 GEN
Solar/Wind Harmer
1.403
960681AF2-359 GEN
Solar/Wind Harmer
2.307
247536S-71 GEN
Solar/Wind Harmer
2.452
274775LINCOLN ;6U
Adder
3.521
274776LINCOLN ;7U
Adder
3.521
274777LINCOLN ;8U
Adder
3.521
972037AH1-567 GEN1
Adder
0.103
274827FISK ;RP
Adder
4.38
274800UNIV PARK;3U
Adder
3.284
274801UNIV PARK;4U
Adder
3.284
960591AF2-350 GEN
Solar/Wind Harmer
5.623
970289AG2-191 GEN
Solar/Wind Harmer
1.065
972228AH1-698 GEN2
Adder
2.075
972227AH1-698 GEN1
Adder
1.461
274687WILL CNTY;4U
Adder
15.572
274687WILL CNTY;4U
Adder
15.572
274675JOLIET 29;7U
Adder
17.053
274675JOLIET 29;7U
Adder
16.444
276893AG1-478 C
Solar/Wind Harmer
0.305
274728ELWOOD EC;5P
Adder
9.109
274731ELWOOD EC;2P
Adder
9.108
274733ELWOOD EC;3P
Adder
9.108
274735ELWOOD EC;4P
Adder
9.108
970833AG2-524 GEN
Solar/Wind Harmer
4.808
970833AG2-524 GEN
Solar/Wind Harmer
2.236
274744AC1-111 GEN8
Adder
3.054
274746AC1-111 G10
Adder
3.054
270543AE2-219 C
Solar/Wind Harmer
5.431
970073AG2-061 GEN
Solar/Wind Harmer
1.247
971549AH1-272 GEN
Solar/Wind Harmer
9.777
971411AH1-196 GEN
Solar/Wind Harmer
7.924
274823ROCKFORD ;21
Adder
10.183
972267AH1-718 GEN
Adder
2.114
957201AF2-014 GEN
Solar/Wind Helper
8.717
270223U2-072_GEN1
Solar/Wind Helper
0.799
270224U2-072_GEN2
Solar/Wind Helper
0.799
270227U2-072_GEN3
Solar/Wind Helper
0.799
270228U2-072_GEN4
Solar/Wind Helper
0.799
270231U2-072_GEN5
Solar/Wind Helper
0.799
966831AG1-554 GEN
Solar/Wind Helper
0.85
270499AE1-146 GEN
Solar/Wind Helper
1.939
945641AF1-229 GEN
Solar/Wind Helper
0.909
971675AH1-338 GEN
Solar/Wind Harmer
1.226
972231SS25-0005
Solar/Wind Harmer
5.51
972181SS23-001
Solar/Wind Harmer
3.444
274752CRETE EC ;2U
Adder
2.838
274753CRETE EC ;3U
Adder
2.838
274724RIVER EC ;11
Adder
10.229
274814UNIV PK N;0U
Adder
2.893
274807UNIV PK N;3U
Adder
2.886
274811UNIV PK N;7U
Adder
2.868
276164X3-005 C
Solar/Wind Harmer
0.402
274772LINCOLN ;3U
Adder
3.521
274803UNIV PARK;6U
Adder
3.296
274826FISK ;BP
Adder
6.181
972038AH1-567 GEN2
Adder
0.206
274887GEN-1.85
Solar/Wind Harmer
2.996
276772AC2-154 GEN
Solar/Wind Harmer
1.569
276843GEN-1.7
Solar/Wind Harmer
0.322
276806AD2-047 C O1
Solar/Wind Harmer
6.016
965461AG1-414 GEN
Solar/Wind Harmer
1.271
970289AG2-191 GEN
Solar/Wind Harmer
0.43
972259AH1-714 GEN
Adder
10.637
970707AG2-453 GEN
Solar/Wind Harmer
15.585
274676JOLIET 29;8U
Adder
16.443
939351AE1-166 GEN
Solar/Wind Harmer
3.295
247642Z2-115 C
Solar/Wind Harmer
0.035
274729ELWOOD EC;1P
Adder
9.108
274730ELWOOD EC;6P
Adder
9.109
274734ELWOOD EC;8P
Adder
9.109
274736ELWOOD EC;9P
Adder
9.109
943121AE2-341 GEN
Solar/Wind Harmer
8.195
943591AF1-030 GEN
Solar/Wind Harmer
5.463
274862TOP CROP ;2U
Solar/Wind Harmer
2.748
274682WAUKEGAN ;7U
Adder
9.708
964401AG1-302 GEN
Solar/Wind Harmer
4.858
24379505HDWTR1G C
Solar/Wind Harmer
4.211
270240V3-007_GEN2
Solar/Wind Harmer
3.294
276868AE1-113 GEN
Solar/Wind Harmer
5.385
274879MINONK ;1U
Solar/Wind Harmer
3.59
276799AD1-013 GEN
Solar/Wind Harmer
1.166
946671AF1-331 GEN
Solar/Wind Harmer
0.221
274760LEE CO EC;1U
Adder
4.773
274767LEE CO EC;8U
Adder
4.717
246938BC-WTG3
Solar/Wind Helper
11.224
942871AE2-306 GEN
Solar/Wind Helper
0.405
270284AF1-227 GEN1
Solar/Wind Helper
1.524
270287AF1-227 GEN3
Solar/Wind Helper
0.559
276820AF1-078_GEN
Solar/Wind Helper
0.309
270541AE2-072 C
Solar/Wind Helper
0.973
270246TR4_N_V150
Solar/Wind Harmer
0.804
270247TR4_N_V136
Solar/Wind Harmer
0.804
944231AF1-091 GEN
Solar/Wind Harmer
16.021
942221AE2-234 GEN
Solar/Wind Harmer
3.104
247620Y3-023
Adder
0.361
944541AF1-119 GEN
Solar/Wind Harmer
3.285
960971AF2-388 GEN
Solar/Wind Harmer
8.576
270201AC2-176 GEN
Solar/Wind Harmer
3.503
270031AE2-169
Solar/Wind Harmer
5.526
270599AE1-208 GEN
Solar/Wind Harmer
5.526
964611AG1-324 GEN
Solar/Wind Harmer
0.349
961051AF2-396 GEN
Solar/Wind Harmer
10.462
961051AF2-396 GEN
Solar/Wind Harmer
4.866
247621Y3-024
Adder
0.156
970349AG2-230 GEN
Solar/Wind Harmer
9.594
965681AG1-436 GEN
Solar/Wind Harmer
7.631
965791AG1-447 GEN
Solar/Wind Harmer
3.904
274805UNIV PK N;1U
Adder
2.874
274808UNIV PK N;4U
Adder
2.855
274770LINCOLN ;1U
Adder
3.521
274771LINCOLN ;2U
Adder
3.521
274888KELLY CRK;1U
Solar/Wind Harmer
3.318
276776AD2-060 GEN
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
8.098
970941AG2-585 GEN
Solar/Wind Harmer
3.093
970291AG2-192 GEN
Solar/Wind Harmer
0.729
970291AG2-192 GEN
Solar/Wind Harmer
0.235
276897AD1-100 C
Solar/Wind Harmer
25.808
274674JOLIET 9 ;6U
Adder
8.535
276893AG1-478 C
Solar/Wind Harmer
0.243
270535AF1-215 GEN1
Solar/Wind Harmer
2.5
270536AF1-215 GEN2
Solar/Wind Harmer
2.5
958481AF2-142 GEN
Solar/Wind Harmer
8.153
970883AG2-550 GEN
Solar/Wind Harmer
5.431
970885AG2-551 GEN
Solar/Wind Harmer
1.263
274696ROCKY RD ;4P
Adder
6.156
274695ROCKY RD ;2P
Adder
6.014
274693ROCKY RD ;1P
Adder
5.955
274697ROCKY RD ;3P
Adder
1.634
274683WAUKEGAN ;8U
Adder
11.367
274683WAUKEGAN ;8U
Adder
9.582
958491AF2-143 GEN
Solar/Wind Harmer
8.042
962691AG1-118 GEN
Solar/Wind Harmer
16.067
24725505WLD G2 C
Solar/Wind Harmer
2.125
24699105WLD G1 C
Solar/Wind Harmer
2.1
960751AF2-366 GEN
Solar/Wind Harmer
1.533
276901AD2-066 C O1
Solar/Wind Harmer
1.871
926881AC1-175 GEN
Solar/Wind Harmer
2.972
972235AH1-702 GEN1
Adder
1.314
972236AH1-702 GEN2
Adder
1.143
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.773
274763LEE CO EC;4U
Adder
4.728
246937BC-WTG2
Solar/Wind Helper
11.034
270462AD2-086
Solar/Wind Helper
3.494
247522W1-056 GEN
Solar/Wind Helper
1.143
253378AE2-206_GEN
Solar/Wind Helper
0.662
957891AF2-083 GEN
Solar/Wind Harmer
9.957
270449AD2-020 GEN
Solar/Wind Harmer
1.811
943021AE2-325 GEN
Solar/Wind Harmer
2.354
270005AE1-210 C O1
Solar/Wind Harmer
3.321
24441205WTRV SLR C
Solar/Wind Harmer
0.082
970825AG2-519 GEN
Solar/Wind Harmer
1.255
274751CRETE EC ;1U
Adder
2.838
274754CRETE EC ;4U
Adder
2.838
274723RIVER EC ;12
Adder
10.355
274812UNIV PK N;8U
Adder
2.868
972207SS24-0001
Solar/Wind Harmer
12.518
274773LINCOLN ;4U
Adder
3.521
274774LINCOLN ;5U
Adder
3.521
270594AE1-207 GEN
Solar/Wind Harmer
7.706
270032AE2-172
Solar/Wind Harmer
2.639
970373AG2-245 GEN
Solar/Wind Harmer
11.888
274802UNIV PARK;5U
Adder
3.296
274676JOLIET 29;8U
Adder
17.052
941551AE2-152 GEN
Solar/Wind Harmer
2.52
274674JOLIET 9 ;6U
Adder
8.535
274732ELWOOD EC;7P
Adder
9.109
270055AF2-134 C O1
Solar/Wind Harmer
1.666
274871GR RIDGE ;2U
Solar/Wind Harmer
4.231
274847GR RIDGE ;BU
Solar/Wind Harmer
2.782
274745AC1-111 GEN9
Adder
3.054
276694AA1-018 GEN2
Solar/Wind Harmer
3.43
276691AA1-018 GEN1
Solar/Wind Harmer
0.41
274861TOP CROP ;1U
Solar/Wind Harmer
3.292
274682WAUKEGAN ;7U
Adder
9.708
274828WAUKEGAN ;BP
Adder
5.958
276903AD2-071 C
Solar/Wind Harmer
5.388
276805AD2-038 GEN
Solar/Wind Harmer
2.749
958381AF2-132 GEN
Solar/Wind Harmer
4.858
962781AG1-127 GEN
Solar/Wind Harmer
5.08
964861AG1-349 GEN
Solar/Wind Harmer
4.197
971917AH1-482 GEN
Solar/Wind Harmer
4.843
939401AE1-172 GEN
Solar/Wind Harmer
7.431
274872LEEDK;1U
Solar/Wind Harmer
4.374
942081AE2-220 GEN
Solar/Wind Harmer
3.406
270209AC1-174_GEN
Solar/Wind Harmer
2.167
270437AC2-090 C
Solar/Wind Harmer
2.972
270239V3-007_GEN1
Solar/Wind Harmer
0.916
276882AE2-255 GEN
Solar/Wind Harmer
1.795
971997AH1-543 GEN
Solar/Wind Harmer
8.338
274822ROCKFORD ;11
Adder
10.257
274761LEE CO EC;2U
Adder
4.773
274766LEE CO EC;7U
Adder
4.717
246936BC-WTG1
Solar/Wind Helper
11.034
270317AD1-130_GEN
Solar/Wind Helper
3.865
270485AE1-090_GEN
Solar/Wind Helper
0.304
270391AF1-285 GEN3
Solar/Wind Helper
0.541
270578AF1-285 GEN2
Solar/Wind Helper
0.541
960841AF2-375 GEN
Solar/Wind Helper
1.161
270286AF1-227 GEN2
Solar/Wind Helper
0.559
990497J1323
External Queue
1.5409908294677734
990792J1392
External Queue
5.301008224487305
LAGNLTFEXP_LAGN->PJM
CLTF
4.175
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.241
TVALTFEXP_TVA->PJM
CLTF
1.645
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.209
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.297
MECLTFEXP_MEC->PJM
CLTF
7.255
SIGELTFEXP_SIGE->PJM
CLTF
0.143
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.738
NYPJM->LTFIMP_NY
CLTF
0.909
LGEELTFEXP_LGEE->PJM
CLTF
1.252
WECLTFEXP_WEC->PJM
CLTF
1.989
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.47 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1932.9
MW Contribution:
5.38
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.217
959331AF2-224 GEN
Solar/Wind Harmer
18.515
963791AG1-232 GEN
Solar/Wind Harmer
15.532
965041AG1-368 GEN
Solar/Wind Harmer
10.987
970031AG2-029 GEN
Solar/Wind Harmer
26.279
247521TR3_G114
Solar/Wind Harmer
3.138
270191TR4_S_V150
Solar/Wind Harmer
2.8
965051AG1-369 GEN
Solar/Wind Harmer
4.662
270071AF1-092 GEN
Solar/Wind Harmer
13.655
24729505KEY G4
Adder
5.533
958711AF2-162 GEN
Solar/Wind Harmer
0.789
945581AF1-223 GEN
Solar/Wind Harmer
3.221
961761AG1-017 GEN
Solar/Wind Harmer
0.289
964611AG1-324 GEN
Solar/Wind Harmer
2.578
971771AH1-392 GEN
Solar/Wind Harmer
5.936
270526AF1-158 GEN
Solar/Wind Harmer
2.87
944161AF1-084 GEN
Solar/Wind Harmer
1.394
960681AF2-359 GEN
Solar/Wind Harmer
2.295
247536S-71 GEN
Solar/Wind Harmer
2.431
274775LINCOLN ;6U
Adder
3.504
274776LINCOLN ;7U
Adder
3.504
274777LINCOLN ;8U
Adder
3.504
972037AH1-567 GEN1
Adder
0.103
274827FISK ;RP
Adder
4.359
274800UNIV PARK;3U
Adder
3.268
274801UNIV PARK;4U
Adder
3.268
960591AF2-350 GEN
Solar/Wind Harmer
5.596
970289AG2-191 GEN
Solar/Wind Harmer
1.059
972228AH1-698 GEN2
Adder
2.065
972227AH1-698 GEN1
Adder
1.454
274687WILL CNTY;4U
Adder
15.497
274687WILL CNTY;4U
Adder
15.497
274675JOLIET 29;7U
Adder
16.97
274675JOLIET 29;7U
Adder
16.364
276893AG1-478 C
Solar/Wind Harmer
0.303
965431AG1-411 GEN
50/50
44.533
24727105RPMNG2
50/50
3.236
970583AG2-370 GEN
50/50
2.555
965021AG1-366 GEN
Solar/Wind Harmer
4.306
270043AE2-236 GEN
Solar/Wind Harmer
5.547
270063AE2-323 C
Solar/Wind Harmer
1.992
944531AF1-118 GEN
Solar/Wind Harmer
30.771
24695305TIMB G C
Solar/Wind Harmer
2.683
247643Z2-116 C
Solar/Wind Harmer
0.049
962031AG1-047 GEN
Solar/Wind Harmer
2.045
957741AF2-068 GEN
Solar/Wind Harmer
10.146
945111AF1-176 GEN
Solar/Wind Harmer
3.824
270505AE1-170 C O1
Solar/Wind Harmer
9.801
971347AH1-153 GEN
Solar/Wind Harmer
3.182
24441505OLIV SLR
Solar/Wind Harmer
0.084
946031AF1-268 GEN
Solar/Wind Harmer
5.016
270004AE1-209 GEN
Solar/Wind Harmer
3.298
970825AG2-519 GEN
Solar/Wind Harmer
3.346
972231SS25-0005
Solar/Wind Harmer
5.483
972181SS23-001
Solar/Wind Harmer
3.427
274752CRETE EC ;2U
Adder
2.824
274753CRETE EC ;3U
Adder
2.824
274724RIVER EC ;11
Adder
10.179
274814UNIV PK N;0U
Adder
2.878
274807UNIV PK N;3U
Adder
2.872
274811UNIV PK N;7U
Adder
2.854
270246TR4_N_V150
Solar/Wind Harmer
0.794
270247TR4_N_V136
Solar/Wind Harmer
0.794
944231AF1-091 GEN
Solar/Wind Harmer
15.867
942221AE2-234 GEN
Solar/Wind Harmer
3.085
247620Y3-023
Adder
0.359
944541AF1-119 GEN
Solar/Wind Harmer
3.265
960971AF2-388 GEN
Solar/Wind Harmer
8.523
270201AC2-176 GEN
Solar/Wind Harmer
3.476
270031AE2-169
Solar/Wind Harmer
5.49
270599AE1-208 GEN
Solar/Wind Harmer
5.49
964611AG1-324 GEN
Solar/Wind Harmer
0.346
961051AF2-396 GEN
Solar/Wind Harmer
10.396
961051AF2-396 GEN
Solar/Wind Harmer
4.835
247621Y3-024
Adder
0.155
970349AG2-230 GEN
Solar/Wind Harmer
9.545
965681AG1-436 GEN
Solar/Wind Harmer
7.591
965791AG1-447 GEN
Solar/Wind Harmer
3.884
274805UNIV PK N;1U
Adder
2.86
274808UNIV PK N;4U
Adder
2.841
274770LINCOLN ;1U
Adder
3.504
274771LINCOLN ;2U
Adder
3.504
274888KELLY CRK;1U
Solar/Wind Harmer
3.302
276776AD2-060 GEN
Solar/Wind Harmer
0.234
958011AF2-095 GEN
Solar/Wind Harmer
8.059
970941AG2-585 GEN
Solar/Wind Harmer
3.078
970291AG2-192 GEN
Solar/Wind Harmer
0.725
970291AG2-192 GEN
Solar/Wind Harmer
0.233
276897AD1-100 C
Solar/Wind Harmer
25.684
274674JOLIET 9 ;6U
Adder
8.494
276893AG1-478 C
Solar/Wind Harmer
0.242
270535AF1-215 GEN1
Solar/Wind Harmer
2.489
270536AF1-215 GEN2
Solar/Wind Harmer
2.489
958481AF2-142 GEN
Solar/Wind Harmer
8.114
970883AG2-550 GEN
Solar/Wind Harmer
5.379
970885AG2-551 GEN
Solar/Wind Harmer
1.251
274696ROCKY RD ;4P
Adder
6.127
274695ROCKY RD ;2P
Adder
5.986
274693ROCKY RD ;1P
Adder
5.927
276164X3-005 C
Solar/Wind Harmer
0.4
274772LINCOLN ;3U
Adder
3.504
274803UNIV PARK;6U
Adder
3.28
274826FISK ;BP
Adder
6.151
972038AH1-567 GEN2
Adder
0.205
274887GEN-1.85
Solar/Wind Harmer
2.982
276772AC2-154 GEN
Solar/Wind Harmer
1.562
276843GEN-1.7
Solar/Wind Harmer
0.321
276806AD2-047 C O1
Solar/Wind Harmer
5.987
965461AG1-414 GEN
Solar/Wind Harmer
1.264
970289AG2-191 GEN
Solar/Wind Harmer
0.428
972259AH1-714 GEN
Adder
10.586
970707AG2-453 GEN
Solar/Wind Harmer
15.511
274676JOLIET 29;8U
Adder
16.364
939351AE1-166 GEN
Solar/Wind Harmer
3.279
247642Z2-115 C
Solar/Wind Harmer
0.035
274729ELWOOD EC;1P
Adder
9.065
274730ELWOOD EC;6P
Adder
9.065
274734ELWOOD EC;8P
Adder
9.065
274736ELWOOD EC;9P
Adder
9.065
943121AE2-341 GEN
Solar/Wind Harmer
8.156
943591AF1-030 GEN
Solar/Wind Harmer
5.437
274862TOP CROP ;2U
Solar/Wind Harmer
2.735
274682WAUKEGAN ;7U
Adder
9.661
964401AG1-302 GEN
Solar/Wind Harmer
4.838
276868AE1-113 GEN
Solar/Wind Harmer
5.359
274879MINONK ;1U
Solar/Wind Harmer
3.573
24379505HDWTR1G C
Solar/Wind Harmer
4.177
270240V3-007_GEN2
Solar/Wind Harmer
3.268
276799AD1-013 GEN
Solar/Wind Harmer
1.161
946671AF1-331 GEN
Solar/Wind Harmer
0.22
274760LEE CO EC;1U
Adder
4.75
274767LEE CO EC;8U
Adder
4.695
246938BC-WTG3
Solar/Wind Helper
11.264
942871AE2-306 GEN
Solar/Wind Helper
0.422
270284AF1-227 GEN1
Solar/Wind Helper
1.655
270287AF1-227 GEN3
Solar/Wind Helper
0.607
276820AF1-078_GEN
Solar/Wind Helper
0.32
270541AE2-072 C
Solar/Wind Helper
1.001
274728ELWOOD EC;5P
Adder
9.065
274731ELWOOD EC;2P
Adder
9.065
274733ELWOOD EC;3P
Adder
9.065
274735ELWOOD EC;4P
Adder
9.065
970833AG2-524 GEN
Solar/Wind Harmer
4.785
970833AG2-524 GEN
Solar/Wind Harmer
2.225
274744AC1-111 GEN8
Adder
3.039
274746AC1-111 G10
Adder
3.039
270543AE2-219 C
Solar/Wind Harmer
5.379
970073AG2-061 GEN
Solar/Wind Harmer
1.241
971411AH1-196 GEN
Solar/Wind Harmer
7.886
958391AF2-133 GEN
Solar/Wind Harmer
4.766
274823ROCKFORD ;21
Adder
10.134
972267AH1-718 GEN
Adder
2.104
957201AF2-014 GEN
Solar/Wind Helper
8.747
270223U2-072_GEN1
Solar/Wind Helper
0.831
270224U2-072_GEN2
Solar/Wind Helper
0.831
270227U2-072_GEN3
Solar/Wind Helper
0.831
270228U2-072_GEN4
Solar/Wind Helper
0.831
270231U2-072_GEN5
Solar/Wind Helper
0.831
966831AG1-554 GEN
Solar/Wind Helper
0.865
270499AE1-146 GEN
Solar/Wind Helper
1.978
945641AF1-229 GEN
Solar/Wind Helper
0.926
971675AH1-338 GEN
Solar/Wind Harmer
6.172
24727005RPMNG1
50/50
3.237
960861AF2-377 GEN
50/50
2.173
965421AG1-410 GEN
Solar/Wind Harmer
114.896
965011AG1-365 GEN
Solar/Wind Harmer
18.515
270024AE2-089 GEN
Solar/Wind Harmer
4.01
965651AG1-433 GEN
Solar/Wind Harmer
4.262
958861AF2-177 GEN
Solar/Wind Harmer
8.262
24639705ELKHART HY
Adder
0.114
945371AF1-202 GEN
Solar/Wind Harmer
4.955
270216AD2-079_GEN
Solar/Wind Harmer
0.428
945111AF1-176 GEN
Solar/Wind Harmer
12.067
957891AF2-083 GEN
Solar/Wind Harmer
9.896
270449AD2-020 GEN
Solar/Wind Harmer
1.8
943021AE2-325 GEN
Solar/Wind Harmer
2.339
270005AE1-210 C O1
Solar/Wind Harmer
3.298
24441205WTRV SLR C
Solar/Wind Harmer
0.081
970825AG2-519 GEN
Solar/Wind Harmer
1.246
274751CRETE EC ;1U
Adder
2.824
274754CRETE EC ;4U
Adder
2.824
274723RIVER EC ;12
Adder
10.305
274812UNIV PK N;8U
Adder
2.854
972207SS24-0001
Solar/Wind Harmer
12.459
274773LINCOLN ;4U
Adder
3.504
274774LINCOLN ;5U
Adder
3.504
270594AE1-207 GEN
Solar/Wind Harmer
7.661
270032AE2-172
Solar/Wind Harmer
2.624
970373AG2-245 GEN
Solar/Wind Harmer
11.833
274802UNIV PARK;5U
Adder
3.28
274676JOLIET 29;8U
Adder
16.97
941551AE2-152 GEN
Solar/Wind Harmer
2.508
274674JOLIET 9 ;6U
Adder
8.494
274732ELWOOD EC;7P
Adder
9.065
270055AF2-134 C O1
Solar/Wind Harmer
1.659
274871GR RIDGE ;2U
Solar/Wind Harmer
4.211
274847GR RIDGE ;BU
Solar/Wind Harmer
2.769
274745AC1-111 GEN9
Adder
3.039
276694AA1-018 GEN2
Solar/Wind Harmer
3.413
276691AA1-018 GEN1
Solar/Wind Harmer
0.408
274861TOP CROP ;1U
Solar/Wind Harmer
3.276
274682WAUKEGAN ;7U
Adder
9.661
274828WAUKEGAN ;BP
Adder
5.93
276903AD2-071 C
Solar/Wind Harmer
5.356
276805AD2-038 GEN
Solar/Wind Harmer
2.736
958381AF2-132 GEN
Solar/Wind Harmer
4.838
964861AG1-349 GEN
Solar/Wind Harmer
4.18
971917AH1-482 GEN
Solar/Wind Harmer
4.823
962781AG1-127 GEN
Solar/Wind Harmer
5.056
939401AE1-172 GEN
Solar/Wind Harmer
7.395
274872LEEDK;1U
Solar/Wind Harmer
4.354
276882AE2-255 GEN
Solar/Wind Harmer
1.787
942081AE2-220 GEN
Solar/Wind Harmer
3.379
270209AC1-174_GEN
Solar/Wind Harmer
2.15
270437AC2-090 C
Solar/Wind Harmer
2.949
270239V3-007_GEN1
Solar/Wind Harmer
0.909
971997AH1-543 GEN
Solar/Wind Harmer
8.298
274822ROCKFORD ;11
Adder
10.209
274761LEE CO EC;2U
Adder
4.75
274766LEE CO EC;7U
Adder
4.695
246936BC-WTG1
Solar/Wind Helper
11.073
270317AD1-130_GEN
Solar/Wind Helper
3.991
270485AE1-090_GEN
Solar/Wind Helper
0.314
270391AF1-285 GEN3
Solar/Wind Helper
0.562
270578AF1-285 GEN2
Solar/Wind Helper
0.562
960841AF2-375 GEN
Solar/Wind Helper
1.184
270286AF1-227 GEN2
Solar/Wind Helper
0.607
274697ROCKY RD ;3P
Adder
1.626
274683WAUKEGAN ;8U
Adder
11.313
274683WAUKEGAN ;8U
Adder
9.536
958491AF2-143 GEN
Solar/Wind Harmer
8.003
962691AG1-118 GEN
Solar/Wind Harmer
15.99
960751AF2-366 GEN
Solar/Wind Harmer
1.525
24725505WLD G2 C
Solar/Wind Harmer
2.112
24699105WLD G1 C
Solar/Wind Harmer
2.087
276901AD2-066 C O1
Solar/Wind Harmer
1.862
926881AC1-175 GEN
Solar/Wind Harmer
2.949
972235AH1-702 GEN1
Adder
1.308
972236AH1-702 GEN2
Adder
1.137
274764LEE CO EC;5U
Adder
4.762
274765LEE CO EC;6U
Adder
4.762
274762LEE CO EC;3U
Adder
4.75
274763LEE CO EC;4U
Adder
4.706
246937BC-WTG2
Solar/Wind Helper
11.073
270462AD2-086
Solar/Wind Helper
3.608
247522W1-056 GEN
Solar/Wind Helper
1.164
253378AE2-206_GEN
Solar/Wind Helper
0.686
270349AD2-093_GEN
Solar/Wind Helper
0.668
270471AD2-092_GEN
Solar/Wind Helper
0.668
990497J1323
External Queue
1.5336281061172485
990792J1392
External Queue
5.2756805419921875
LAGNLTFEXP_LAGN->PJM
CLTF
4.163
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.274
TVALTFEXP_TVA->PJM
CLTF
1.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.654
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.273
MECLTFEXP_MEC->PJM
CLTF
7.221
SIGELTFEXP_SIGE->PJM
CLTF
0.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.578
NYPJM->LTFIMP_NY
CLTF
0.9
LGEELTFEXP_LGEE->PJM
CLTF
1.239
WECLTFEXP_WEC->PJM
CLTF
1.98
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.047
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.192

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.36 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1930.81
MW Contribution:
5.42
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.2 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2600.32
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.249
960861AF2-377 GEN
50/50
2.199
965421AG1-410 GEN
Solar/Wind Harmer
115.334
965011AG1-365 GEN
Solar/Wind Harmer
18.598
270024AE2-089 GEN
Solar/Wind Harmer
4.034
965651AG1-433 GEN
Solar/Wind Harmer
4.284
958861AF2-177 GEN
Solar/Wind Harmer
8.306
24639705ELKHART HY
Adder
0.115
945371AF1-202 GEN
Solar/Wind Harmer
4.982
270216AD2-079_GEN
Solar/Wind Harmer
0.43
945111AF1-176 GEN
Solar/Wind Harmer
12.127
957891AF2-083 GEN
Solar/Wind Harmer
9.944
270449AD2-020 GEN
Solar/Wind Harmer
1.809
943021AE2-325 GEN
Solar/Wind Harmer
2.351
270005AE1-210 C O1
Solar/Wind Harmer
3.317
24441205WTRV SLR C
Solar/Wind Harmer
0.082
970825AG2-519 GEN
Solar/Wind Harmer
1.254
274751CRETE EC ;1U
Adder
2.834
274754CRETE EC ;4U
Adder
2.834
274723RIVER EC ;12
Adder
10.339
274812UNIV PK N;8U
Adder
2.863
972207SS24-0001
Solar/Wind Harmer
12.498
274773LINCOLN ;4U
Adder
3.515
274774LINCOLN ;5U
Adder
3.515
270594AE1-207 GEN
Solar/Wind Harmer
7.695
270032AE2-172
Solar/Wind Harmer
2.635
970373AG2-245 GEN
Solar/Wind Harmer
11.868
274802UNIV PARK;5U
Adder
3.291
274676JOLIET 29;8U
Adder
17.025
941551AE2-152 GEN
Solar/Wind Harmer
2.516
274674JOLIET 9 ;6U
Adder
8.521
274732ELWOOD EC;7P
Adder
9.094
270055AF2-134 C O1
Solar/Wind Harmer
1.663
274871GR RIDGE ;2U
Solar/Wind Harmer
4.224
274847GR RIDGE ;BU
Solar/Wind Harmer
2.778
274745AC1-111 GEN9
Adder
3.049
276694AA1-018 GEN2
Solar/Wind Harmer
3.424
276691AA1-018 GEN1
Solar/Wind Harmer
0.409
274861TOP CROP ;1U
Solar/Wind Harmer
3.286
274682WAUKEGAN ;7U
Adder
9.692
274828WAUKEGAN ;BP
Adder
5.949
276903AD2-071 C
Solar/Wind Harmer
5.38
276805AD2-038 GEN
Solar/Wind Harmer
2.745
958381AF2-132 GEN
Solar/Wind Harmer
4.85
962781AG1-127 GEN
Solar/Wind Harmer
5.072
964861AG1-349 GEN
Solar/Wind Harmer
4.19
971917AH1-482 GEN
Solar/Wind Harmer
4.834
939401AE1-172 GEN
Solar/Wind Harmer
7.419
274872LEEDK;1U
Solar/Wind Harmer
4.367
942081AE2-220 GEN
Solar/Wind Harmer
3.401
270209AC1-174_GEN
Solar/Wind Harmer
2.164
270437AC2-090 C
Solar/Wind Harmer
2.968
270239V3-007_GEN1
Solar/Wind Harmer
0.915
276882AE2-255 GEN
Solar/Wind Harmer
1.792
971997AH1-543 GEN
Solar/Wind Harmer
8.324
274822ROCKFORD ;11
Adder
10.241
274761LEE CO EC;2U
Adder
4.765
274766LEE CO EC;7U
Adder
4.709
246936BC-WTG1
Solar/Wind Helper
11.036
270317AD1-130_GEN
Solar/Wind Helper
3.868
270485AE1-090_GEN
Solar/Wind Helper
0.304
270391AF1-285 GEN3
Solar/Wind Helper
0.541
270578AF1-285 GEN2
Solar/Wind Helper
0.541
960841AF2-375 GEN
Solar/Wind Helper
1.162
270286AF1-227 GEN2
Solar/Wind Helper
0.561
24727205RPMNG3
50/50
3.23
959331AF2-224 GEN
Solar/Wind Harmer
18.598
963791AG1-232 GEN
Solar/Wind Harmer
15.623
965041AG1-368 GEN
Solar/Wind Harmer
11.086
970031AG2-029 GEN
Solar/Wind Harmer
26.405
247521TR3_G114
Solar/Wind Harmer
3.175
270191TR4_S_V150
Solar/Wind Harmer
2.833
965051AG1-369 GEN
Solar/Wind Harmer
4.718
270071AF1-092 GEN
Solar/Wind Harmer
13.713
24729505KEY G4
Adder
5.561
958711AF2-162 GEN
Solar/Wind Harmer
0.793
945581AF1-223 GEN
Solar/Wind Harmer
3.239
961761AG1-017 GEN
Solar/Wind Harmer
0.291
964611AG1-324 GEN
Solar/Wind Harmer
2.595
971771AH1-392 GEN
Solar/Wind Harmer
5.962
270526AF1-158 GEN
Solar/Wind Harmer
2.882
944161AF1-084 GEN
Solar/Wind Harmer
1.401
960681AF2-359 GEN
Solar/Wind Harmer
2.303
247536S-71 GEN
Solar/Wind Harmer
2.449
274775LINCOLN ;6U
Adder
3.515
274776LINCOLN ;7U
Adder
3.515
274777LINCOLN ;8U
Adder
3.515
972037AH1-567 GEN1
Adder
0.103
274827FISK ;RP
Adder
4.374
274800UNIV PARK;3U
Adder
3.279
274801UNIV PARK;4U
Adder
3.279
960591AF2-350 GEN
Solar/Wind Harmer
5.615
970289AG2-191 GEN
Solar/Wind Harmer
1.064
972228AH1-698 GEN2
Adder
2.072
972227AH1-698 GEN1
Adder
1.459
274687WILL CNTY;4U
Adder
15.547
274687WILL CNTY;4U
Adder
15.547
274675JOLIET 29;7U
Adder
17.026
274675JOLIET 29;7U
Adder
16.418
276893AG1-478 C
Solar/Wind Harmer
0.304
274728ELWOOD EC;5P
Adder
9.094
274731ELWOOD EC;2P
Adder
9.094
274733ELWOOD EC;3P
Adder
9.094
274735ELWOOD EC;4P
Adder
9.094
970833AG2-524 GEN
Solar/Wind Harmer
4.8
970833AG2-524 GEN
Solar/Wind Harmer
2.233
274744AC1-111 GEN8
Adder
3.049
274746AC1-111 G10
Adder
3.049
270543AE2-219 C
Solar/Wind Harmer
5.424
970073AG2-061 GEN
Solar/Wind Harmer
1.245
971549AH1-272 GEN
Solar/Wind Harmer
9.762
971411AH1-196 GEN
Solar/Wind Harmer
7.911
274823ROCKFORD ;21
Adder
10.167
972267AH1-718 GEN
Adder
2.11
957201AF2-014 GEN
Solar/Wind Helper
8.718
270223U2-072_GEN1
Solar/Wind Helper
0.8
270224U2-072_GEN2
Solar/Wind Helper
0.8
270227U2-072_GEN3
Solar/Wind Helper
0.8
270228U2-072_GEN4
Solar/Wind Helper
0.8
270231U2-072_GEN5
Solar/Wind Helper
0.8
966831AG1-554 GEN
Solar/Wind Helper
0.85
270499AE1-146 GEN
Solar/Wind Helper
1.94
945641AF1-229 GEN
Solar/Wind Helper
0.909
971675AH1-338 GEN
Solar/Wind Harmer
1.224
965431AG1-411 GEN
50/50
44.703
24727105RPMNG2
50/50
3.249
970583AG2-370 GEN
50/50
2.578
965021AG1-366 GEN
Solar/Wind Harmer
4.325
270043AE2-236 GEN
Solar/Wind Harmer
5.574
270063AE2-323 C
Solar/Wind Harmer
2.002
944531AF1-118 GEN
Solar/Wind Harmer
30.925
24695305TIMB G C
Solar/Wind Harmer
2.72
247643Z2-116 C
Solar/Wind Harmer
0.049
962031AG1-047 GEN
Solar/Wind Harmer
2.058
957741AF2-068 GEN
Solar/Wind Harmer
10.212
945111AF1-176 GEN
Solar/Wind Harmer
3.843
270505AE1-170 C O1
Solar/Wind Harmer
9.849
971347AH1-153 GEN
Solar/Wind Harmer
3.193
24441505OLIV SLR
Solar/Wind Harmer
0.084
946031AF1-268 GEN
Solar/Wind Harmer
5.047
270004AE1-209 GEN
Solar/Wind Harmer
3.317
970825AG2-519 GEN
Solar/Wind Harmer
3.366
972231SS25-0005
Solar/Wind Harmer
5.502
972181SS23-001
Solar/Wind Harmer
3.439
274752CRETE EC ;2U
Adder
2.834
274753CRETE EC ;3U
Adder
2.834
274724RIVER EC ;11
Adder
10.213
274814UNIV PK N;0U
Adder
2.888
274807UNIV PK N;3U
Adder
2.882
274811UNIV PK N;7U
Adder
2.863
276164X3-005 C
Solar/Wind Harmer
0.401
274772LINCOLN ;3U
Adder
3.515
274803UNIV PARK;6U
Adder
3.291
274826FISK ;BP
Adder
6.171
972038AH1-567 GEN2
Adder
0.205
274887GEN-1.85
Solar/Wind Harmer
2.991
276772AC2-154 GEN
Solar/Wind Harmer
1.567
276843GEN-1.7
Solar/Wind Harmer
0.322
276806AD2-047 C O1
Solar/Wind Harmer
6.006
965461AG1-414 GEN
Solar/Wind Harmer
1.269
970289AG2-191 GEN
Solar/Wind Harmer
0.43
972259AH1-714 GEN
Adder
10.62
970707AG2-453 GEN
Solar/Wind Harmer
15.561
274676JOLIET 29;8U
Adder
16.417
939351AE1-166 GEN
Solar/Wind Harmer
3.29
247642Z2-115 C
Solar/Wind Harmer
0.035
274729ELWOOD EC;1P
Adder
9.094
274730ELWOOD EC;6P
Adder
9.094
274734ELWOOD EC;8P
Adder
9.094
274736ELWOOD EC;9P
Adder
9.094
943121AE2-341 GEN
Solar/Wind Harmer
8.182
943591AF1-030 GEN
Solar/Wind Harmer
5.455
274862TOP CROP ;2U
Solar/Wind Harmer
2.744
274682WAUKEGAN ;7U
Adder
9.692
964401AG1-302 GEN
Solar/Wind Harmer
4.85
24379505HDWTR1G C
Solar/Wind Harmer
4.205
270240V3-007_GEN2
Solar/Wind Harmer
3.29
276868AE1-113 GEN
Solar/Wind Harmer
5.377
274879MINONK ;1U
Solar/Wind Harmer
3.585
276799AD1-013 GEN
Solar/Wind Harmer
1.164
946671AF1-331 GEN
Solar/Wind Harmer
0.221
274760LEE CO EC;1U
Adder
4.765
274767LEE CO EC;8U
Adder
4.709
246938BC-WTG3
Solar/Wind Helper
11.226
942871AE2-306 GEN
Solar/Wind Helper
0.406
270284AF1-227 GEN1
Solar/Wind Helper
1.528
270287AF1-227 GEN3
Solar/Wind Helper
0.561
276820AF1-078_GEN
Solar/Wind Helper
0.309
270541AE2-072 C
Solar/Wind Helper
0.974
270246TR4_N_V150
Solar/Wind Harmer
0.803
270247TR4_N_V136
Solar/Wind Harmer
0.803
944231AF1-091 GEN
Solar/Wind Harmer
16.007
942221AE2-234 GEN
Solar/Wind Harmer
3.102
247620Y3-023
Adder
0.361
944541AF1-119 GEN
Solar/Wind Harmer
3.282
960971AF2-388 GEN
Solar/Wind Harmer
8.568
270201AC2-176 GEN
Solar/Wind Harmer
3.499
270031AE2-169
Solar/Wind Harmer
5.52
270599AE1-208 GEN
Solar/Wind Harmer
5.52
964611AG1-324 GEN
Solar/Wind Harmer
0.348
961051AF2-396 GEN
Solar/Wind Harmer
10.449
961051AF2-396 GEN
Solar/Wind Harmer
4.86
247621Y3-024
Adder
0.156
970349AG2-230 GEN
Solar/Wind Harmer
9.58
965681AG1-436 GEN
Solar/Wind Harmer
7.619
965791AG1-447 GEN
Solar/Wind Harmer
3.898
274805UNIV PK N;1U
Adder
2.869
274808UNIV PK N;4U
Adder
2.851
274770LINCOLN ;1U
Adder
3.515
274771LINCOLN ;2U
Adder
3.515
274888KELLY CRK;1U
Solar/Wind Harmer
3.313
276776AD2-060 GEN
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
8.085
970941AG2-585 GEN
Solar/Wind Harmer
3.088
970291AG2-192 GEN
Solar/Wind Harmer
0.728
970291AG2-192 GEN
Solar/Wind Harmer
0.234
276897AD1-100 C
Solar/Wind Harmer
25.767
274674JOLIET 9 ;6U
Adder
8.521
276893AG1-478 C
Solar/Wind Harmer
0.243
270535AF1-215 GEN1
Solar/Wind Harmer
2.495
270536AF1-215 GEN2
Solar/Wind Harmer
2.495
958481AF2-142 GEN
Solar/Wind Harmer
8.14
970883AG2-550 GEN
Solar/Wind Harmer
5.424
970885AG2-551 GEN
Solar/Wind Harmer
1.261
274696ROCKY RD ;4P
Adder
6.146
274695ROCKY RD ;2P
Adder
6.005
274693ROCKY RD ;1P
Adder
5.946
274697ROCKY RD ;3P
Adder
1.631
274683WAUKEGAN ;8U
Adder
11.349
274683WAUKEGAN ;8U
Adder
9.567
958491AF2-143 GEN
Solar/Wind Harmer
8.029
962691AG1-118 GEN
Solar/Wind Harmer
16.041
24725505WLD G2 C
Solar/Wind Harmer
2.122
24699105WLD G1 C
Solar/Wind Harmer
2.097
960751AF2-366 GEN
Solar/Wind Harmer
1.53
276901AD2-066 C O1
Solar/Wind Harmer
1.868
926881AC1-175 GEN
Solar/Wind Harmer
2.968
972235AH1-702 GEN1
Adder
1.312
972236AH1-702 GEN2
Adder
1.141
274764LEE CO EC;5U
Adder
4.777
274765LEE CO EC;6U
Adder
4.777
274762LEE CO EC;3U
Adder
4.765
274763LEE CO EC;4U
Adder
4.721
246937BC-WTG2
Solar/Wind Helper
11.036
270462AD2-086
Solar/Wind Helper
3.497
247522W1-056 GEN
Solar/Wind Helper
1.143
253378AE2-206_GEN
Solar/Wind Helper
0.662
990497J1323
External Queue
1.5405974388122559
990792J1392
External Queue
5.299654960632324
LAGNLTFEXP_LAGN->PJM
CLTF
4.166
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.237
TVALTFEXP_TVA->PJM
CLTF
1.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.107
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.281
MECLTFEXP_MEC->PJM
CLTF
7.242
SIGELTFEXP_SIGE->PJM
CLTF
0.143
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.662
NYPJM->LTFIMP_NY
CLTF
0.907
LGEELTFEXP_LGEE->PJM
CLTF
1.248
WECLTFEXP_WEC->PJM
CLTF
1.986
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.192

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#10527_05BLUFFP 138_E2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.45 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:279.09
MW Contribution:
65.63
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.07 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:283.22
MW Contribution:
65.63
Bus #Bus NameTypeMW Contribution
970883AG2-550 GEN
Solar/Wind Harmer
65.634
970885AG2-551 GEN
Solar/Wind Harmer
15.264
971029AG2-637 GEN
Solar/Wind Harmer
100.53
247536S-71 GEN
Solar/Wind Harmer
26.558
270543AE2-219 C
Solar/Wind Harmer
65.634
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.013
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
0.044
TVALTFEXP_TVA->PJM
CLTF
0.012
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.906
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.023
MECLTFEXP_MEC->PJM
CLTF
0.107
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.556
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.012
WECLTFEXP_WEC->PJM
CLTF
0.029
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.009

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#14047_05DESOTO 138_F_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.88 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:277.66
MW Contribution:
36.31
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.91 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:290.46
MW Contribution:
36.31
Bus #Bus NameTypeMW Contribution
270024AE2-089 GEN
Solar/Wind Harmer
8.101
247621Y3-024
50/50
0.702
970883AG2-550 GEN
Solar/Wind Harmer
36.314
970885AG2-551 GEN
Solar/Wind Harmer
8.445
270201AC2-176 GEN
Solar/Wind Harmer
11.883
964611AG1-324 GEN
Solar/Wind Harmer
1.21
942221AE2-234 GEN
Solar/Wind Harmer
2.447
971029AG2-637 GEN
Solar/Wind Harmer
65.061
270543AE2-219 C
Solar/Wind Harmer
36.314
247536S-71 GEN
Solar/Wind Harmer
12.36
961761AG1-017 GEN
Solar/Wind Harmer
0.99
964611AG1-324 GEN
Solar/Wind Harmer
9.017
963791AG1-232 GEN
Solar/Wind Harmer
11.525
962031AG1-047 GEN
Solar/Wind Harmer
6.99
957741AF2-068 GEN
Solar/Wind Harmer
34.679
946031AF1-268 GEN
Solar/Wind Harmer
19.189
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.148
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.443
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.258
MECLTFEXP_MEC->PJM
CLTF
0.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.148
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.027
WECLTFEXP_WEC->PJM
CLTF
0.093
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.85 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:277.57
MW Contribution:
36.31
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.88 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:290.39
MW Contribution:
36.31
Bus #Bus NameTypeMW Contribution
270024AE2-089 GEN
Solar/Wind Harmer
8.1
247621Y3-024
50/50
0.702
970883AG2-550 GEN
Solar/Wind Harmer
36.31
970885AG2-551 GEN
Solar/Wind Harmer
8.444
270201AC2-176 GEN
Solar/Wind Harmer
11.881
964611AG1-324 GEN
Solar/Wind Harmer
1.21
942221AE2-234 GEN
Solar/Wind Harmer
2.446
971029AG2-637 GEN
Solar/Wind Harmer
65.055
270543AE2-219 C
Solar/Wind Harmer
36.31
247536S-71 GEN
Solar/Wind Harmer
12.359
961761AG1-017 GEN
Solar/Wind Harmer
0.989
964611AG1-324 GEN
Solar/Wind Harmer
9.015
963791AG1-232 GEN
Solar/Wind Harmer
11.522
962031AG1-047 GEN
Solar/Wind Harmer
6.989
957741AF2-068 GEN
Solar/Wind Harmer
34.675
946031AF1-268 GEN
Solar/Wind Harmer
19.186
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.147
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.441
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.259
MECLTFEXP_MEC->PJM
CLTF
0.271
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.161
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.027
WECLTFEXP_WEC->PJM
CLTF
0.093
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DEOK_P4_1403_MIAMI FORT_SRT-A'
 OPEN BRANCH FROM BUS 249567 TO BUS 243233 CKT 1   /*08M.FORT     345.0 - 05TANNER     345.0
 OPEN BRANCH FROM BUS 249567 TO BUS 251950 CKT 7   /*08M.FORT     345.0 - 08M.FRT7      22.0
END
CONTINGENCY 'AEP_P4_#10527_05BLUFFP 138_E2_SRT-A'
 OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1   /*05BLUFFP     138.0 - 05JAY        138.0
 OPEN BRANCH FROM BUS 243253 TO BUS 246014 CKT 1   /*05BLUFFP     138.0 - 05BLUFFPNT    69.0
END
CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A'
 OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1   /*05DESOTO     138.0 - 05MEDFOR     138.0
 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1   /*05DESOTO     138.0 - AF1-268 TP   138.0
END
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1'
 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1   /*05DESOTO     138.0 - AF1-268 TP   138.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS'
 OPEN BRANCH FROM BUS 962760 TO BUS 248125 CKT 1   /*AG1-125 TP   765.0 - 05ADKINS     765.0
END
CONTINGENCY 'AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 243207 TO BUS 248105 CKT 1   /*05GRNTWN     765.0 - 05GREENTW_RM 765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248102 CKT 1   /*05TEDDY_RG   765.0 - 05TEDDY      765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248105 CKT 1   /*05TEDDY_RG   765.0 - 05GREENTW_RM 765.0
END
CONTINGENCY 'AEP_P1-2_#9287_1679_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290597 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290597 CKT 1    /*05GRNTWN     765.0 - 05DUMONT_RG  765.0
END
CONTINGENCY 'AEP_P4_#3149_05HANG R 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242924 TO BUS 242927 CKT 1   /*05HANG R     765.0 - 05MARQUI     765.0
 OPEN BRANCH FROM BUS 242927 TO BUS 242938 CKT 1   /*05MARQUI     765.0 - 05MARQUI     345.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#1558_05BAKER 765_Q_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#309_05HANG R 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#1560_05BAKER 765_Q2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242523 CKT 1   /*05BAKER      765.0 - 05BAKER      345.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P2-2_#6156_05MARQUI 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 242927 CKT 1   /*05HANG R     765.0 - 05MARQUI     765.0
 OPEN BRANCH FROM BUS 242927 TO BUS 242938 CKT 1   /*05MARQUI     765.0 - 05MARQUI     345.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P2-2_#6763_05BIERSR 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243454 TO BUS 246888 CKT 1   /*05BIXBY      345.0 - 05BIERSR     345.0
END
CONTINGENCY 'AEP_P2-2_#308_05CULLOD 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
END
CONTINGENCY 'AEP_P7-1_#11019___SRT-A-2'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 944530 TO BUS 243232 CKT 2   /*AF1-118 TP   345.0 - 05SORENS     345.0
END
CONTINGENCY '34569 34598 34524_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 249578 CKT 1   /*08FOSTER     345.0 - 08HILCRT     345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT5_SRT-SL'
 OPEN BRANCH FROM BUS 235851 TO BUS 235850 CKT 1                /*01NTHLNV     500.0 - 01LONGVIEW   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235111 TO BUS 235851 CKT 1 /*01 502 J     500.0 - 01NTHLNV     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235851 TO BUS 235106 CKT 1 /*01NTHLNV     500.0 - 01FMARTN     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235111 TO BUS 235851 CKT 1 /*01 502 J     500.0 - 01NTHLNV     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235851 TO BUS 235106 CKT 1 /*01NTHLNV     500.0 - 01FMARTN     500.0
END
CONTINGENCY 'AEP_P2-2_#316_05AMOS 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242508 TO BUS 290927 CKT 5    /*05AMOS       765.0 - 05AMOS 5EQ     1.0
 OPEN BRANCH FROM BUS 242522 TO BUS 247504 CKT Z5   /*05AMOS       345.0 - 05AMOS_5_XFL 345.0
 OPEN BRANCH FROM BUS 247504 TO BUS 290927 CKT 5    /*05AMOS_5_XFL 345.0 - 05AMOS 5EQ     1.0
 OPEN BRANCH FROM BUS 290927 TO BUS 290928 CKT 5    /*05AMOS 5EQ     1.0 - 05AMOS T5     34.5
END
CONTINGENCY 'DEOK_P_CIRCUIT3281&13803_SRT-A'
 OPEN BUS 250144   /*08HUSTRC     138.0
 OPEN BUS 250168   /*08TRENTON_2  138.0
END
CONTINGENCY 'AEP_P4_05MARYSV 765_A_SRT-A_SENS'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A_SENS'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
290610 to 242512 ckt Z1
243262 to 250001 ckt 1
290085 to 290084 ckt 1
242514 to 290610 ckt 1
290623 to 242925 ckt Z1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
248005 to 242528 ckt 1
251382 to 251376 ckt 1
965420 to 246929 ckt 1
971028 to 290085 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC123.53 %3792.0B4684.3
9.42
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC123.51 %3792.0B4683.54
9.42
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC123.51 %3792.0B4683.44
9.46
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC122.65 %3792.0B4650.99
6.57
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC122.64 %3792.0B4650.57
6.57
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC139.19 %3792.0B5278.17
9.22
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC139.17 %3792.0B5277.43
9.22
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC138.98 %3792.0B5270.18
9.3
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC138.45 %3792.0B5250.02
6.43
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC138.41 %3792.0B5248.4
6.43
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.25 %3729.0B5006.21
10.56
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.4 %3729.0B4974.31
10.53
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC133.01 %3729.0B4959.97
10.53
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC133.01 %3729.0B4959.97
10.53
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.87 %3729.0B4917.49
7.34
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.69 %3729.0B4873.53
10.67
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.24 %3729.0B4632.89
7.09
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC113.4 %1683.0B1908.5
3.2
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC110.65 %1737.0B1922.03
4.63
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC101.35 %4000.0B4053.82
9.76
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC101.34 %4000.0B4053.72
9.77
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC101.32 %4000.0B4052.99
9.76
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-2_MP-500-028_SRT-A
SingleAC100.79 %4000.0B4031.79
6.81
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-3_MP-765-502T_SRT-A
SingleAC100.79 %4000.0B4031.62
6.81
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
BreakerAC106.46 %1203.0B1280.75
4.97
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#16620_05ADKINS 345_A_SRT-A
BreakerAC104.16 %1203.0B1253.03
5.02
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
BreakerAC104.15 %1203.0B1252.96
5.02
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
BreakerAC104.15 %1203.0B1252.95
5.02
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#2085_05BEATTY 345_304C_SRT-A
BreakerAC101.98 %1203.0B1226.82
4.57
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC104.78 %2320.0B2430.97
3.11
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
6.07
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
AEP_P4_#2812_05TANNER 345_T2_SRT-A
BreakerAC107.21 %178.0B190.84
7.09
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
DEOK_P4_1401_MIAMI FORT_SRT-A
BreakerAC107.08 %178.0B190.6
7.09
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
DEOK_P_4561TODWOOD14562TODWOOD2_SRT-A
TowerAC103.44 %178.0B184.13
6.93
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
DEOK_P4_1301_TERMINAL_SRT-A
BreakerAC101.5 %178.0B180.68
6.98
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
DAY_BLAZER_FB_??_B_SRT-A
BreakerAC101.48 %178.0B180.64
8.19
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#15023_05JAY 138_E_SRT-A
BreakerAC104.98 %255.0B267.7
36.58
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#15176_05JAY 138_E2_SRT-A
BreakerAC104.25 %255.0B265.84
36.46
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC116.82 %1409.0B1646.06
4.46
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC110.97 %1409.0B1563.59
4.45
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC110.88 %1409.0B1562.23
4.45
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC105.36 %1409.0B1484.58
4.43
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC105.35 %1409.0B1484.33
4.43
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC135.56 %3792.0B5140.38
10.56
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC134.72 %3792.0B5108.61
10.53
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC134.34 %3792.0B5094.21
10.53
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC134.34 %3792.0B5094.21
10.53
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC133.22 %3792.0B5051.83
7.34
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC132.01 %3792.0B5005.84
10.67
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.57 %3792.0B4761.71
7.09
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC111.91 %2246.0B2513.45
4.43
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC127.9 %4142.0B5297.56
7.11
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC108.0 %4142.0B4473.55
7.4
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.31 %4571.0B5773.71
6.69
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC110.01 %4571.0B5028.49
7.17
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.34 %4571.0B5774.92
6.69
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC110.28 %4571.0B5040.8
7.17
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Base Case
SingleAC120.76 %4047.0A4887.22
7.66
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC117.27 %5523.0B6477.04
13.4
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC116.4 %5523.0B6428.58
9.35
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.72 %5523.0B6225.55
13.54
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC109.18 %4558.0A4976.63
6.41
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.76 %5523.0B5896.19
7.74
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC122.25 %1868.0B2283.58
4.48
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7443_05DUMONT 765_A_SRT-A
BreakerAC111.31 %3097.0B3447.28
11.39
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7442_05SORENS 765_K2_SRT-A
BreakerAC111.22 %3097.0B3444.48
11.39
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7444_05DUMONT 765_A2_SRT-A
BreakerAC111.06 %3097.0B3439.41
11.4
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC103.01 %3097.0B3190.2
7.95
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.53 %5523.0B5607.44
8.88
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC123.9 %2317.0B2870.85
7.04
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC121.45 %2317.0B2813.9
7.1
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC121.4 %2317.0B2812.93
7.03
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
BreakerAC121.23 %2317.0B2808.9
13.07
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
BusAC121.23 %2317.0B2808.8
13.07
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC112.63 %2317.0B2609.67
4.95
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A
TowerAC106.66 %2317.0B2471.36
8.26
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P7-1_#485___SRT-A
TowerAC106.66 %2317.0B2471.23
8.26
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
DEOK_P4_1579_EASTBEND_SRT-A
BreakerAC104.35 %2317.0B2417.88
7.12
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC153.59 %1540.0B2365.35
7.25
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC141.94 %1540.0B2185.8
4.91
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC133.27 %1540.0B2052.4
4.8
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC107.31 %1540.0B1652.5
6.56
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC102.96 %1540.0B1585.6
6.6
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
BreakerAC115.81 %1203.0B1393.24
4.92
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
BreakerAC113.59 %1203.0B1366.44
4.97
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#16620_05ADKINS 345_A_SRT-A
BreakerAC113.56 %1203.0B1366.12
4.97
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
BreakerAC113.56 %1203.0B1366.07
4.97
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#2085_05BEATTY 345_304C_SRT-A
BreakerAC110.85 %1203.0B1333.47
4.52
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC128.82 %1868.0B2406.35
4.48
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P7-1_#11067___SRT-A
TowerAC103.3 %1868.0B1929.56
5.18
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-032T_SRT-A
TowerAC102.98 %1868.0B1923.66
4.89
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC100.16 %1868.0B1870.91
4.84
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#15023_05JAY 138_E_SRT-A
BreakerAC105.03 %255.0B267.84
36.58
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#15176_05JAY 138_E2_SRT-A
BreakerAC104.3 %255.0B265.97
36.46

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.53 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4684.3
MW Contribution:
9.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270459AD2-067 GEN
Solar/Wind Harmer
8.564
961821AG1-024 GEN
Solar/Wind Harmer
8.695
270291AC1-194 GEN
Solar/Wind Harmer
5.184
270432AC2-029 GEN
Solar/Wind Harmer
7.128
270263AC1-001 GEN
Solar/Wind Harmer
1.061
241955AC1-078 GEN
Solar/Wind Harmer
7.548
940611AE2-048 GEN
Solar/Wind Harmer
22.264
941391AE2-136 GEN
Solar/Wind Harmer
11.537
945631AF1-228 GEN
Solar/Wind Harmer
4.727
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253338AC1-165 GEN
Solar/Wind Harmer
1.085
253343AC1-166 GEN
Solar/Wind Harmer
1.085
943861AF1-054 GEN
Solar/Wind Harmer
3.855
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
17.842
270340AC2-060 GEN
Solar/Wind Harmer
3.013
241972AD1-140 GEN
Solar/Wind Harmer
4.405
253406AD2-031_GEN
Solar/Wind Harmer
1.251
253433AC1-085 GEN1
Solar/Wind Harmer
5.175
253432AC1-085 GEN2
Solar/Wind Harmer
0.26
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270223U2-072_GEN1
Solar/Wind Harmer
1.918
270224U2-072_GEN2
Solar/Wind Harmer
1.918
270227U2-072_GEN3
Solar/Wind Harmer
1.918
270228U2-072_GEN4
Solar/Wind Harmer
1.918
270231U2-072_GEN5
Solar/Wind Harmer
1.918
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
8.028
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
14.154
972163AH1-664 GEN
Solar/Wind Harmer
9.428
972165AH1-665 GEN
Solar/Wind Harmer
7.543
270543AE2-219 C
Solar/Wind Harmer
9.417
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
3.803
958711AF2-162 GEN
Solar/Wind Harmer
0.951
945581AF1-223 GEN
Solar/Wind Harmer
4.258
961761AG1-017 GEN
Solar/Wind Harmer
0.401
964611AG1-324 GEN
Solar/Wind Harmer
3.657
270356AE2-297 GEN
Solar/Wind Harmer
4.321
270071AF1-092 GEN
Solar/Wind Harmer
14.041
970289AG2-191 GEN
Solar/Wind Harmer
1.776
963791AG1-232 GEN
Solar/Wind Harmer
12.58
959331AF2-224 GEN
Solar/Wind Harmer
9.303
247521TR3_G114
Solar/Wind Harmer
3.113
270191TR4_S_V150
Solar/Wind Harmer
2.777
965051AG1-369 GEN
Solar/Wind Harmer
4.624
965041AG1-368 GEN
Solar/Wind Harmer
9.252
957201AF2-014 GEN
Solar/Wind Harmer
4.187
270435AC2-044 GEN
Solar/Wind Harmer
1.847
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
35.963
970149AG2-104 GEN
Solar/Wind Harmer
22.207
970155AG2-107 GEN
Solar/Wind Harmer
15.681
960001AF2-291 GEN
Solar/Wind Harmer
3.191
270510AE1-227 GEN1
Solar/Wind Harmer
2.61
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
270520AE2-214 GEN
Solar/Wind Harmer
6.192
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
2.704
972203AH1-686 GEN
Adder
2.339
270286AF1-227 GEN2
Solar/Wind Harmer
2.112
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
1.046
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
4.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.153
946171AF1-282 GEN
Solar/Wind Harmer
9.738
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
1.175
270578AF1-285 GEN2
Solar/Wind Harmer
1.175
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
9.663
252510AF1-249 C
Solar/Wind Harmer
0.402
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
3.069
270485AE1-090_GEN
Solar/Wind Harmer
0.58
270222AC2-111 GEN
Solar/Wind Harmer
4.248
944031AF1-071 GEN
Solar/Wind Harmer
0.956
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
17.8
971995AH1-542 GEN
Solar/Wind Harmer
10.357
942081AE2-220 GEN
Solar/Wind Harmer
6.014
270209AC1-174_GEN
Solar/Wind Harmer
3.827
270437AC2-090 C
Solar/Wind Harmer
5.249
270239V3-007_GEN1
Solar/Wind Harmer
1.618
965651AG1-433 GEN
Solar/Wind Harmer
5.136
958861AF2-177 GEN
Solar/Wind Harmer
10.268
945371AF1-202 GEN
Solar/Wind Harmer
6.551
270005AE1-210 C O1
Solar/Wind Harmer
5.125
970825AG2-519 GEN
Solar/Wind Harmer
1.966
270024AE2-089 GEN
Solar/Wind Harmer
4.385
270594AE1-207 GEN
Solar/Wind Harmer
12.702
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
9.334
965011AG1-365 GEN
Solar/Wind Harmer
9.303
965421AG1-410 GEN
Solar/Wind Harmer
27.72
246936BC-WTG1
Solar/Wind Harmer
3.612
270489AE1-102 GEN1
Solar/Wind Harmer
1.2
24728605AND G2
Adder
3.541
24639705ELKHART HY
Adder
0.141
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274745AC1-111 GEN9
Adder
5.047
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
35.963
970153AG2-106 GEN
Solar/Wind Harmer
15.681
270512AE1-227 GEN2
Solar/Wind Harmer
2.215
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
971191AH1-055 GEN
Solar/Wind Harmer
19.337
957541AF2-048 GEN
Solar/Wind Harmer
1.627
961921AG1-034 GEN
Solar/Wind Harmer
13.042
970879AG2-548 GEN
Solar/Wind Harmer
8.168
960801AF2-371 GEN
Solar/Wind Harmer
2.586
964871AG1-351 GEN
Solar/Wind Harmer
1.786
270284AF1-227 GEN1
Solar/Wind Harmer
5.709
270287AF1-227 GEN3
Solar/Wind Harmer
2.112
942051AE2-217 GEN
Solar/Wind Harmer
18.072
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
1.046
270518AE2-148 GEN
Solar/Wind Harmer
12.072
270367AC2-061_GEN
Solar/Wind Harmer
3.102
253394AE2-221_GEN
Solar/Wind Harmer
4.42
253317AC1-085 GEN4
Solar/Wind Harmer
8.153
946181AF1-283 GEN
Solar/Wind Harmer
12.659
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
942871AE2-306 GEN
Solar/Wind Harmer
0.881
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
5.927
960071AF2-298 GEN
Solar/Wind Harmer
1.467
252507AC2-088 GEN
Solar/Wind Harmer
1.731
252519AF1-045_GEN
Solar/Wind Harmer
3.517
276820AF1-078_GEN
Solar/Wind Harmer
1.537
252524AE2-267 GEN
Solar/Wind Harmer
1.516
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
7.557
958171AF2-111 GEN
Solar/Wind Harmer
23.611
944531AF1-118 GEN
Solar/Wind Harmer
32.926
24379505HDWTR1G C
Solar/Wind Harmer
7.436
270240V3-007_GEN2
Solar/Wind Harmer
5.818
270004AE1-209 GEN
Solar/Wind Harmer
5.125
962031AG1-047 GEN
Solar/Wind Harmer
2.835
957741AF2-068 GEN
Solar/Wind Harmer
14.065
946031AF1-268 GEN
Solar/Wind Harmer
7.782
970825AG2-519 GEN
Solar/Wind Harmer
5.279
965461AG1-414 GEN
Solar/Wind Harmer
2.119
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.06
270043AE2-236 GEN
Solar/Wind Harmer
5.125
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
4.626
246938BC-WTG3
Solar/Wind Harmer
3.674
270491AE1-102 GEN2
Solar/Wind Harmer
1.2
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
3.079
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
274682WAUKEGAN ;7U
Adder
16.174
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
3.759
270471AD2-092_GEN
Solar/Wind Harmer
3.759
270054AF2-122 C O1
Solar/Wind Harmer
3.36
927014AC1-188 GEN
Solar/Wind Harmer
1.627
946101AF1-275 GEN
Solar/Wind Harmer
1.548
971073AG2-665 GEN
Solar/Wind Harmer
8.168
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
9.486
253383AE2-342_GEN
Solar/Wind Harmer
0.888
942861AE2-305 GEN
Solar/Wind Harmer
7.811
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253415AE1-040 GEN
Solar/Wind Harmer
1.12
962581AG1-107 GEN
Solar/Wind Harmer
4.922
961491AF2-440 GEN
Solar/Wind Harmer
2.045
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
20.019
25183208HLCRTG
Solar/Wind Harmer
5.858
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.247
253349AC2-067 GEN
Solar/Wind Harmer
1.965
253400AC2-068 GEN
Solar/Wind Harmer
0.79
253378AE2-206_GEN
Solar/Wind Harmer
3.461
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
6.668
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
9.417
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
5.743
926881AC1-175 GEN
Solar/Wind Harmer
5.249
944541AF1-119 GEN
Solar/Wind Harmer
3.934
960971AF2-388 GEN
Solar/Wind Harmer
10.271
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
4.819
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
7.629
270599AE1-208 GEN
Solar/Wind Harmer
7.629
942221AE2-234 GEN
Solar/Wind Harmer
3.273
970291AG2-192 GEN
Solar/Wind Harmer
1.215
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
3.711
24699105WLD G1 C
Solar/Wind Harmer
3.668
270246TR4_N_V150
Solar/Wind Harmer
0.788
270247TR4_N_V136
Solar/Wind Harmer
0.788
970349AG2-230 GEN
Solar/Wind Harmer
13.877
246937BC-WTG2
Solar/Wind Harmer
3.612
247620Y3-023
Adder
0.422
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274674JOLIET 9 ;6U
Adder
13.943
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
945421AF1-207 GEN
Solar/Wind Harmer
9.897
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4683.54
MW Contribution:
9.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
35.963
970149AG2-104 GEN
Solar/Wind Harmer
22.207
970155AG2-107 GEN
Solar/Wind Harmer
15.681
960001AF2-291 GEN
Solar/Wind Harmer
3.191
270510AE1-227 GEN1
Solar/Wind Harmer
2.61
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
270520AE2-214 GEN
Solar/Wind Harmer
6.192
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
2.704
972203AH1-686 GEN
Adder
2.339
270286AF1-227 GEN2
Solar/Wind Harmer
2.112
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
1.046
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
4.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.153
946171AF1-282 GEN
Solar/Wind Harmer
9.738
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
1.175
270578AF1-285 GEN2
Solar/Wind Harmer
1.175
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
9.663
270459AD2-067 GEN
Solar/Wind Harmer
8.564
961821AG1-024 GEN
Solar/Wind Harmer
8.695
270291AC1-194 GEN
Solar/Wind Harmer
5.184
270432AC2-029 GEN
Solar/Wind Harmer
7.128
270263AC1-001 GEN
Solar/Wind Harmer
1.061
241955AC1-078 GEN
Solar/Wind Harmer
7.548
940611AE2-048 GEN
Solar/Wind Harmer
22.264
941391AE2-136 GEN
Solar/Wind Harmer
11.537
945631AF1-228 GEN
Solar/Wind Harmer
4.727
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253338AC1-165 GEN
Solar/Wind Harmer
1.085
253343AC1-166 GEN
Solar/Wind Harmer
1.085
943861AF1-054 GEN
Solar/Wind Harmer
3.855
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
17.842
270340AC2-060 GEN
Solar/Wind Harmer
3.013
241972AD1-140 GEN
Solar/Wind Harmer
4.405
253406AD2-031_GEN
Solar/Wind Harmer
1.251
253433AC1-085 GEN1
Solar/Wind Harmer
5.175
253432AC1-085 GEN2
Solar/Wind Harmer
0.26
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270223U2-072_GEN1
Solar/Wind Harmer
1.918
270224U2-072_GEN2
Solar/Wind Harmer
1.918
270227U2-072_GEN3
Solar/Wind Harmer
1.918
270228U2-072_GEN4
Solar/Wind Harmer
1.918
270231U2-072_GEN5
Solar/Wind Harmer
1.918
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
3.759
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
8.028
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
14.154
972163AH1-664 GEN
Solar/Wind Harmer
9.428
972165AH1-665 GEN
Solar/Wind Harmer
7.543
270543AE2-219 C
Solar/Wind Harmer
9.417
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
3.803
958711AF2-162 GEN
Solar/Wind Harmer
0.951
945581AF1-223 GEN
Solar/Wind Harmer
4.258
961761AG1-017 GEN
Solar/Wind Harmer
0.401
964611AG1-324 GEN
Solar/Wind Harmer
3.657
270356AE2-297 GEN
Solar/Wind Harmer
4.321
270071AF1-092 GEN
Solar/Wind Harmer
14.041
970289AG2-191 GEN
Solar/Wind Harmer
1.776
963791AG1-232 GEN
Solar/Wind Harmer
12.58
959331AF2-224 GEN
Solar/Wind Harmer
9.303
247521TR3_G114
Solar/Wind Harmer
3.113
270191TR4_S_V150
Solar/Wind Harmer
2.777
965051AG1-369 GEN
Solar/Wind Harmer
4.624
965041AG1-368 GEN
Solar/Wind Harmer
9.252
957201AF2-014 GEN
Solar/Wind Harmer
4.187
270435AC2-044 GEN
Solar/Wind Harmer
1.847
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
270471AD2-092_GEN
Solar/Wind Harmer
3.759
270054AF2-122 C O1
Solar/Wind Harmer
3.36
927014AC1-188 GEN
Solar/Wind Harmer
1.627
946101AF1-275 GEN
Solar/Wind Harmer
1.548
971073AG2-665 GEN
Solar/Wind Harmer
8.168
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
9.486
253383AE2-342_GEN
Solar/Wind Harmer
0.888
942861AE2-305 GEN
Solar/Wind Harmer
7.811
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253415AE1-040 GEN
Solar/Wind Harmer
1.12
962581AG1-107 GEN
Solar/Wind Harmer
4.922
961491AF2-440 GEN
Solar/Wind Harmer
2.045
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
20.019
25183208HLCRTG
Solar/Wind Harmer
5.858
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.247
253349AC2-067 GEN
Solar/Wind Harmer
1.965
253400AC2-068 GEN
Solar/Wind Harmer
0.79
253378AE2-206_GEN
Solar/Wind Harmer
3.461
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
6.668
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
9.417
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
5.743
926881AC1-175 GEN
Solar/Wind Harmer
5.249
944541AF1-119 GEN
Solar/Wind Harmer
3.934
960971AF2-388 GEN
Solar/Wind Harmer
10.271
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
4.819
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
7.629
270599AE1-208 GEN
Solar/Wind Harmer
7.629
942221AE2-234 GEN
Solar/Wind Harmer
3.273
970291AG2-192 GEN
Solar/Wind Harmer
1.215
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
3.711
24699105WLD G1 C
Solar/Wind Harmer
3.668
270246TR4_N_V150
Solar/Wind Harmer
0.788
270247TR4_N_V136
Solar/Wind Harmer
0.788
970349AG2-230 GEN
Solar/Wind Harmer
13.877
246937BC-WTG2
Solar/Wind Harmer
3.612
247620Y3-023
Adder
0.422
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274674JOLIET 9 ;6U
Adder
13.943
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
945421AF1-207 GEN
Solar/Wind Harmer
9.897
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
35.963
970153AG2-106 GEN
Solar/Wind Harmer
15.681
270512AE1-227 GEN2
Solar/Wind Harmer
2.215
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
971191AH1-055 GEN
Solar/Wind Harmer
19.337
957541AF2-048 GEN
Solar/Wind Harmer
1.627
961921AG1-034 GEN
Solar/Wind Harmer
13.042
970879AG2-548 GEN
Solar/Wind Harmer
8.168
960801AF2-371 GEN
Solar/Wind Harmer
2.586
964871AG1-351 GEN
Solar/Wind Harmer
1.786
270284AF1-227 GEN1
Solar/Wind Harmer
5.709
270287AF1-227 GEN3
Solar/Wind Harmer
2.112
942051AE2-217 GEN
Solar/Wind Harmer
18.072
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
1.046
270518AE2-148 GEN
Solar/Wind Harmer
12.072
270367AC2-061_GEN
Solar/Wind Harmer
3.102
253394AE2-221_GEN
Solar/Wind Harmer
4.42
253317AC1-085 GEN4
Solar/Wind Harmer
8.153
946181AF1-283 GEN
Solar/Wind Harmer
12.659
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
942871AE2-306 GEN
Solar/Wind Harmer
0.881
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
5.927
960071AF2-298 GEN
Solar/Wind Harmer
1.467
252507AC2-088 GEN
Solar/Wind Harmer
1.731
252519AF1-045_GEN
Solar/Wind Harmer
3.517
276820AF1-078_GEN
Solar/Wind Harmer
1.537
252524AE2-267 GEN
Solar/Wind Harmer
1.516
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
7.557
958171AF2-111 GEN
Solar/Wind Harmer
23.611
944531AF1-118 GEN
Solar/Wind Harmer
32.926
24379505HDWTR1G C
Solar/Wind Harmer
7.436
270240V3-007_GEN2
Solar/Wind Harmer
5.818
270004AE1-209 GEN
Solar/Wind Harmer
5.125
962031AG1-047 GEN
Solar/Wind Harmer
2.835
957741AF2-068 GEN
Solar/Wind Harmer
14.065
946031AF1-268 GEN
Solar/Wind Harmer
7.782
970825AG2-519 GEN
Solar/Wind Harmer
5.279
965461AG1-414 GEN
Solar/Wind Harmer
2.119
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.06
270043AE2-236 GEN
Solar/Wind Harmer
5.125
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
4.626
246938BC-WTG3
Solar/Wind Harmer
3.674
270491AE1-102 GEN2
Solar/Wind Harmer
1.2
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
3.079
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
274682WAUKEGAN ;7U
Adder
16.174
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
252510AF1-249 C
Solar/Wind Harmer
0.402
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
3.069
270485AE1-090_GEN
Solar/Wind Harmer
0.58
270222AC2-111 GEN
Solar/Wind Harmer
4.248
944031AF1-071 GEN
Solar/Wind Harmer
0.956
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
17.8
971995AH1-542 GEN
Solar/Wind Harmer
10.357
942081AE2-220 GEN
Solar/Wind Harmer
6.014
270209AC1-174_GEN
Solar/Wind Harmer
3.827
270437AC2-090 C
Solar/Wind Harmer
5.249
270239V3-007_GEN1
Solar/Wind Harmer
1.618
965651AG1-433 GEN
Solar/Wind Harmer
5.136
958861AF2-177 GEN
Solar/Wind Harmer
10.268
945371AF1-202 GEN
Solar/Wind Harmer
6.551
270005AE1-210 C O1
Solar/Wind Harmer
5.125
970825AG2-519 GEN
Solar/Wind Harmer
1.966
270024AE2-089 GEN
Solar/Wind Harmer
4.385
270594AE1-207 GEN
Solar/Wind Harmer
12.702
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
9.334
965011AG1-365 GEN
Solar/Wind Harmer
9.303
965421AG1-410 GEN
Solar/Wind Harmer
27.72
246936BC-WTG1
Solar/Wind Harmer
3.612
270489AE1-102 GEN1
Solar/Wind Harmer
1.2
24728605AND G2
Adder
3.541
24639705ELKHART HY
Adder
0.141
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274745AC1-111 GEN9
Adder
5.047
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4683.44
MW Contribution:
9.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270459AD2-067 GEN
Solar/Wind Harmer
8.603
961821AG1-024 GEN
Solar/Wind Harmer
8.735
270291AC1-194 GEN
Solar/Wind Harmer
5.205
270432AC2-029 GEN
Solar/Wind Harmer
7.158
270263AC1-001 GEN
Solar/Wind Harmer
1.066
241955AC1-078 GEN
Solar/Wind Harmer
7.581
940611AE2-048 GEN
Solar/Wind Harmer
22.381
941391AE2-136 GEN
Solar/Wind Harmer
11.597
945631AF1-228 GEN
Solar/Wind Harmer
4.748
241973AD2-163_GEN1
Solar/Wind Harmer
1.995
241974AD2-163_GEN2
Solar/Wind Harmer
1.995
253338AC1-165 GEN
Solar/Wind Harmer
1.089
253343AC1-166 GEN
Solar/Wind Harmer
1.089
943861AF1-054 GEN
Solar/Wind Harmer
3.872
943851AF1-053 GEN
Solar/Wind Harmer
1.871
971985AH1-537 GEN
Solar/Wind Harmer
17.911
270340AC2-060 GEN
Solar/Wind Harmer
3.025
241972AD1-140 GEN
Solar/Wind Harmer
4.424
253406AD2-031_GEN
Solar/Wind Harmer
1.256
253433AC1-085 GEN1
Solar/Wind Harmer
5.195
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
253372AE2-315 SEC3
Adder
1.85
253372AE2-315 SEC3
Adder
1.85
270223U2-072_GEN1
Solar/Wind Harmer
1.927
270224U2-072_GEN2
Solar/Wind Harmer
1.927
270227U2-072_GEN3
Solar/Wind Harmer
1.927
270228U2-072_GEN4
Solar/Wind Harmer
1.927
270231U2-072_GEN5
Solar/Wind Harmer
1.927
270578AF1-285 GEN2
Solar/Wind Harmer
0.454
25306009OHH W.
Adder
2.806
25196408WSDLE3
Adder
8.526
25196308WSDLE2
Adder
8.452
25196208WSDLE1
Adder
8.431
25196708WSDLE6
Adder
8.409
25196508WSDLE4
Adder
8.198
270302AB2-170 GEN
Solar/Wind Harmer
8.066
25196108MFTGT2
Adder
1.464
25196108MFTGT2
Adder
1.359
971029AG2-637 GEN
Solar/Wind Harmer
14.212
972163AH1-664 GEN
Solar/Wind Harmer
9.464
972165AH1-665 GEN
Solar/Wind Harmer
7.571
270543AE2-219 C
Solar/Wind Harmer
9.456
24729505KEY G4
Adder
6.127
247536S-71 GEN
Solar/Wind Harmer
3.819
958711AF2-162 GEN
Solar/Wind Harmer
0.955
945581AF1-223 GEN
Solar/Wind Harmer
4.276
961761AG1-017 GEN
Solar/Wind Harmer
0.403
964611AG1-324 GEN
Solar/Wind Harmer
3.672
270356AE2-297 GEN
Solar/Wind Harmer
4.339
270071AF1-092 GEN
Solar/Wind Harmer
14.1
970289AG2-191 GEN
Solar/Wind Harmer
1.783
963791AG1-232 GEN
Solar/Wind Harmer
12.634
959331AF2-224 GEN
Solar/Wind Harmer
9.345
247521TR3_G114
Solar/Wind Harmer
3.127
270191TR4_S_V150
Solar/Wind Harmer
2.79
965051AG1-369 GEN
Solar/Wind Harmer
4.645
965041AG1-368 GEN
Solar/Wind Harmer
9.293
957201AF2-014 GEN
Solar/Wind Harmer
4.207
270435AC2-044 GEN
Solar/Wind Harmer
1.855
274775LINCOLN ;6U
Adder
7.721
274776LINCOLN ;7U
Adder
7.721
274777LINCOLN ;8U
Adder
7.721
972037AH1-567 GEN1
Adder
0.167
972228AH1-698 GEN2
Adder
3.376
972227AH1-698 GEN1
Adder
2.377
274827FISK ;RP
Adder
7.071
274800UNIV PARK;3U
Adder
5.313
274801UNIV PARK;4U
Adder
5.313
274687WILL CNTY;4U
Adder
25.419
274687WILL CNTY;4U
Adder
25.419
274728ELWOOD EC;5P
Adder
14.948
274731ELWOOD EC;2P
Adder
14.948
274733ELWOOD EC;3P
Adder
14.948
274735ELWOOD EC;4P
Adder
14.948
274675JOLIET 29;7U
Adder
27.901
274675JOLIET 29;7U
Adder
26.905
274744AC1-111 GEN8
Adder
5.067
274746AC1-111 G10
Adder
5.067
23750701CROSSCHOOL
Solar/Wind Helper
1.353
23684101S70BUS1
50/50
0.296
24318905MLG2
50/50
4.853
270349AD2-093_GEN
Solar/Wind Harmer
3.775
270471AD2-092_GEN
Solar/Wind Harmer
3.775
270054AF2-122 C O1
Solar/Wind Harmer
3.376
927014AC1-188 GEN
Solar/Wind Harmer
1.634
946101AF1-275 GEN
Solar/Wind Harmer
1.555
971073AG2-665 GEN
Solar/Wind Harmer
8.201
970879AG2-548 GEN
Solar/Wind Harmer
1.192
270269AC2-059
Solar/Wind Harmer
9.525
253383AE2-342_GEN
Solar/Wind Harmer
0.892
942861AE2-305 GEN
Solar/Wind Harmer
7.845
24723005RIVRG1
Adder
18.832
24723105RIVRG2
Adder
18.832
253415AE1-040 GEN
Solar/Wind Harmer
1.125
962581AG1-107 GEN
Solar/Wind Harmer
4.941
961491AF2-440 GEN
Solar/Wind Harmer
2.053
25326109MON D
Adder
1.285
253370AE2-315 SEC1
Adder
1.955
25322209TAIT E
Adder
9.512
25322209TAIT E
Adder
9.298
972159AH1-661 GEN
Adder
0.971
938701AE1-092 GEN
Solar/Wind Harmer
20.114
25183208HLCRTG
Solar/Wind Harmer
5.882
252509AD1-136 GEN
Solar/Wind Harmer
0.248
253349AC2-067 GEN
Solar/Wind Harmer
1.973
253400AC2-068 GEN
Solar/Wind Harmer
0.793
253378AE2-206_GEN
Solar/Wind Harmer
3.476
25194408D.CRK1
Adder
7.308
25194508D.CRK3
Adder
1.366
270462AD2-086
Solar/Wind Harmer
6.699
25326509SID D
Adder
1.267
24728805RICHG1
Adder
3.578
24728905RICHG2
Adder
3.578
970883AG2-550 GEN
Solar/Wind Harmer
9.456
970885AG2-551 GEN
Solar/Wind Harmer
2.199
270383AD1-128 GEN
Solar/Wind Harmer
5.766
926881AC1-175 GEN
Solar/Wind Harmer
5.27
944541AF1-119 GEN
Solar/Wind Harmer
3.951
960971AF2-388 GEN
Solar/Wind Harmer
10.314
247621Y3-024
Adder
0.227
270201AC2-176 GEN
Solar/Wind Harmer
4.839
964611AG1-324 GEN
Solar/Wind Harmer
0.493
270031AE2-169
Solar/Wind Harmer
7.66
270599AE1-208 GEN
Solar/Wind Harmer
7.66
942221AE2-234 GEN
Solar/Wind Harmer
3.287
970291AG2-192 GEN
Solar/Wind Harmer
1.22
970291AG2-192 GEN
Solar/Wind Harmer
0.393
24725505WLD G2 C
Solar/Wind Harmer
3.726
24699105WLD G1 C
Solar/Wind Harmer
3.683
270246TR4_N_V150
Solar/Wind Harmer
0.791
270247TR4_N_V136
Solar/Wind Harmer
0.791
970349AG2-230 GEN
Solar/Wind Harmer
13.937
246937BC-WTG2
Solar/Wind Harmer
3.628
247620Y3-023
Adder
0.424
274770LINCOLN ;1U
Adder
7.721
23559001PLEAS1
50/50
11.912
23562401OGROV2
50/50
2.283
24318805MLG1
50/50
6.628
24721905FLATG4
Adder
24.155
962771AG1-126 GEN
Solar/Wind Harmer
36.099
970153AG2-106 GEN
Solar/Wind Harmer
15.741
270512AE1-227 GEN2
Solar/Wind Harmer
2.229
270330AC1-082 GEN2
Solar/Wind Harmer
0.495
270329AC1-082 GEN1
Solar/Wind Harmer
0.495
971191AH1-055 GEN
Solar/Wind Harmer
19.41
957541AF2-048 GEN
Solar/Wind Harmer
1.634
961921AG1-034 GEN
Solar/Wind Harmer
13.102
970879AG2-548 GEN
Solar/Wind Harmer
8.201
960801AF2-371 GEN
Solar/Wind Harmer
2.597
964871AG1-351 GEN
Solar/Wind Harmer
1.793
270284AF1-227 GEN1
Solar/Wind Harmer
5.734
270287AF1-227 GEN3
Solar/Wind Harmer
2.121
942051AE2-217 GEN
Solar/Wind Harmer
18.15
24686405CER G5
Adder
8.32
253325AC1-069 GEN
Solar/Wind Harmer
1.051
270518AE2-148 GEN
Solar/Wind Harmer
12.124
270367AC2-061_GEN
Solar/Wind Harmer
3.114
23559101PLEAS2
50/50
11.912
23684201S70BUS2
50/50
0.302
23562301OGROV1
50/50
2.303
962761AG1-125 GEN
Solar/Wind Harmer
36.099
970149AG2-104 GEN
Solar/Wind Harmer
22.291
970155AG2-107 GEN
Solar/Wind Harmer
15.741
270510AE1-227 GEN1
Solar/Wind Harmer
2.626
960001AF2-291 GEN
Solar/Wind Harmer
3.203
270331AC1-082 GEN3
Solar/Wind Harmer
0.497
270520AE2-214 GEN
Solar/Wind Harmer
6.219
971073AG2-665 GEN
Solar/Wind Harmer
1.192
270273AD2-016 GEN
Solar/Wind Harmer
2.715
972203AH1-686 GEN
Adder
2.346
270286AF1-227 GEN2
Solar/Wind Harmer
2.121
24686505CER G6
Adder
8.386
253333AC1-068 GEN
Solar/Wind Harmer
1.051
24723205RIVRG3
Adder
18.832
972269AH1-719 GEN
Adder
2.301
253398AE2-221_GEN2
Solar/Wind Harmer
4.438
253316AC1-085 GEN3
Solar/Wind Harmer
8.185
946171AF1-282 GEN
Solar/Wind Harmer
9.777
253370AE2-315 SEC1
Adder
1.955
253371AE2-315 SEC2
Adder
1.85
270391AF1-285 GEN3
Solar/Wind Harmer
1.18
270578AF1-285 GEN2
Solar/Wind Harmer
1.18
25326309TAIT D
Adder
1.069
252516AE2-318_GEN
Solar/Wind Harmer
9.702
252510AF1-249 C
Solar/Wind Harmer
0.403
25194608D.CRK4
Adder
1.589
270317AD1-130_GEN
Solar/Wind Harmer
3.084
270485AE1-090_GEN
Solar/Wind Harmer
0.583
25196808ZIMRHP
Adder
73.077
270222AC2-111 GEN
Solar/Wind Harmer
4.266
944031AF1-071 GEN
Solar/Wind Harmer
0.96
25196008MFTGT1
Adder
1.328
945681AF1-233 GEN
Solar/Wind Harmer
17.868
971995AH1-542 GEN
Solar/Wind Harmer
10.409
942081AE2-220 GEN
Solar/Wind Harmer
6.039
270209AC1-174_GEN
Solar/Wind Harmer
3.843
270437AC2-090 C
Solar/Wind Harmer
5.27
270239V3-007_GEN1
Solar/Wind Harmer
1.625
253394AE2-221_GEN
Solar/Wind Harmer
4.438
253317AC1-085 GEN4
Solar/Wind Harmer
8.185
946181AF1-283 GEN
Solar/Wind Harmer
12.71
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.955
253371AE2-315 SEC2
Adder
1.85
942871AE2-306 GEN
Solar/Wind Harmer
0.885
270391AF1-285 GEN3
Solar/Wind Harmer
0.454
270186AC1-089 GEN
Solar/Wind Harmer
5.95
960071AF2-298 GEN
Solar/Wind Harmer
1.473
252507AC2-088 GEN
Solar/Wind Harmer
1.738
252519AF1-045_GEN
Solar/Wind Harmer
3.531
276820AF1-078_GEN
Solar/Wind Harmer
1.544
252524AE2-267 GEN
Solar/Wind Harmer
1.522
25196608WSDLE5
Adder
8.282
25194608D.CRK4
Adder
1.589
25196008MFTGT1
Adder
1.286
972167AH1-666 GEN
Solar/Wind Harmer
7.586
958171AF2-111 GEN
Solar/Wind Harmer
23.702
944531AF1-118 GEN
Solar/Wind Harmer
33.064
24379505HDWTR1G C
Solar/Wind Harmer
7.466
270240V3-007_GEN2
Solar/Wind Harmer
5.841
270004AE1-209 GEN
Solar/Wind Harmer
5.146
962031AG1-047 GEN
Solar/Wind Harmer
2.847
957741AF2-068 GEN
Solar/Wind Harmer
14.123
946031AF1-268 GEN
Solar/Wind Harmer
7.814
970825AG2-519 GEN
Solar/Wind Harmer
5.3
965461AG1-414 GEN
Solar/Wind Harmer
2.128
965651AG1-433 GEN
Solar/Wind Harmer
5.157
958861AF2-177 GEN
Solar/Wind Harmer
10.311
945371AF1-202 GEN
Solar/Wind Harmer
6.578
270005AE1-210 C O1
Solar/Wind Harmer
5.146
970825AG2-519 GEN
Solar/Wind Harmer
1.974
270024AE2-089 GEN
Solar/Wind Harmer
4.403
270594AE1-207 GEN
Solar/Wind Harmer
12.754
270032AE2-172
Solar/Wind Harmer
4.368
970091AG2-072 GEN
Adder
71.916
276903AD2-071 C
Solar/Wind Harmer
9.372
965011AG1-365 GEN
Solar/Wind Harmer
9.345
965421AG1-410 GEN
Solar/Wind Harmer
27.848
246936BC-WTG1
Solar/Wind Harmer
3.628
270489AE1-102 GEN1
Solar/Wind Harmer
1.206
24728605AND G2
Adder
3.555
24639705ELKHART HY
Adder
0.141
274773LINCOLN ;4U
Adder
7.721
274774LINCOLN ;5U
Adder
7.721
274751CRETE EC ;1U
Adder
7.534
274754CRETE EC ;4U
Adder
7.534
274723RIVER EC ;12
Adder
16.377
274812UNIV PK N;8U
Adder
4.572
274802UNIV PARK;5U
Adder
5.315
274732ELWOOD EC;7P
Adder
14.948
274676JOLIET 29;8U
Adder
27.901
274674JOLIET 9 ;6U
Adder
14
274745AC1-111 GEN9
Adder
5.067
274682WAUKEGAN ;7U
Adder
1.999
23751101LEADS_P59
Solar/Wind Helper
2.36
23583801GRNGAP
Solar/Wind Helper
5.023
316095T157 G97
Solar/Wind Helper
1.343
238185AF2-356 C
Solar/Wind Helper
2.448
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238120AE2-309 GEN
Solar/Wind Helper
0.48
238126S14_GEN_1
Solar/Wind Helper
0.755
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.443
235067AD1-061 GEN
Solar/Wind Helper
0.39
237038AE2-054 C
Solar/Wind Helper
0.238
237002AB1-128_GEN
Solar/Wind Helper
0.387
238118U2-030_1
Solar/Wind Helper
0.311
238169AE2-226 GEN1
Solar/Wind Helper
0.61
238170AE2-226 GEN2
Solar/Wind Helper
0.61
23750501ELLIOTTS
Solar/Wind Helper
0.612
23779801AA1-109
Solar/Wind Helper
0.169
3138216PACIFIC
Solar/Wind Helper
0.038
237025AB1-124 C
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.059
970031AG2-029 GEN
Solar/Wind Harmer
4.035
23777801MSM_W1-116
Solar/Wind Helper
0.1
970289AG2-191 GEN
Solar/Wind Harmer
0.72
247642Z2-115 C
Solar/Wind Harmer
0.06
270043AE2-236 GEN
Solar/Wind Harmer
5.148
965021AG1-366 GEN
Solar/Wind Harmer
2.173
971347AH1-153 GEN
Solar/Wind Harmer
4.646
246938BC-WTG3
Solar/Wind Harmer
3.691
270491AE1-102 GEN2
Solar/Wind Harmer
1.206
24728705AND G3
Adder
7.436
24728505AND G1
Adder
3.555
24695305TIMB G C
Solar/Wind Harmer
3.093
958581AF2-149 GEN
Solar/Wind Harmer
3.962
971199AH1-059 GEN
Solar/Wind Harmer
1.944
274772LINCOLN ;3U
Adder
7.721
274752CRETE EC ;2U
Adder
7.534
274753CRETE EC ;3U
Adder
7.534
274724RIVER EC ;11
Adder
16.186
274814UNIV PK N;0U
Adder
4.612
274807UNIV PK N;3U
Adder
4.602
274811UNIV PK N;7U
Adder
4.572
274803UNIV PARK;6U
Adder
5.315
274826FISK ;BP
Adder
9.978
972038AH1-567 GEN2
Adder
0.333
972259AH1-714 GEN
Adder
17.382
274729ELWOOD EC;1P
Adder
14.948
274730ELWOOD EC;6P
Adder
14.948
274734ELWOOD EC;8P
Adder
14.948
274736ELWOOD EC;9P
Adder
14.948
274676JOLIET 29;8U
Adder
26.905
274682WAUKEGAN ;7U
Adder
16.24
964991AG1-363 GEN
Solar/Wind Helper
4.317
23562501BACKB
Solar/Wind Helper
1.016
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238127S14_GEN_2
Solar/Wind Helper
0.755
238152AF2-075_GEN
Solar/Wind Helper
0.621
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.154
235063AE1-101 C2
Solar/Wind Helper
1.453
237001AB1-127_GEN
Solar/Wind Helper
0.386
316415AF1-147_GEN2
Solar/Wind Helper
0.768
237048AF1-022 C
Solar/Wind Helper
0.156
274771LINCOLN ;2U
Adder
7.721
274805UNIV PK N;1U
Adder
4.582
274808UNIV PK N;4U
Adder
4.552
274674JOLIET 9 ;6U
Adder
14
274696ROCKY RD ;4P
Adder
10.303
274695ROCKY RD ;2P
Adder
10.065
274693ROCKY RD ;1P
Adder
9.966
274697ROCKY RD ;3P
Adder
2.734
316097T157 G90
Solar/Wind Helper
1.343
23751201ROTHROCK
Solar/Wind Helper
0.827
23585401KL_K28_T16
Solar/Wind Helper
1.409
235054AD2-180 GEN
Solar/Wind Helper
1.901
235531U2-073 GEN
Solar/Wind Helper
3.003
238117U2-030
Solar/Wind Helper
0.311
238147AE2-230_GEN1
Solar/Wind Helper
0.435
238148AE2-230_GEN2
Solar/Wind Helper
0.435
238149AF1-291A_GEN
Solar/Wind Helper
0.124
237061AD1-155 GEN
Solar/Wind Helper
1.542
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.239
237080AD1-060 GEN
Solar/Wind Helper
0.298
235062AE1-101 C1
Solar/Wind Helper
1.453
237006AB1-125 GEN
Solar/Wind Helper
0.108
316411AF1-147_GEN1
Solar/Wind Helper
0.768
LAGNLTFEXP_LAGN->PJM
CLTF
14.087
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.851
TVALTFEXP_TVA->PJM
CLTF
6.994
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.694
MECLTFEXP_MEC->PJM
CLTF
14.418
SIGELTFEXP_SIGE->PJM
CLTF
0.465
CPLELTFEXP_CPLE->PJM
CLTF
1.203
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.012
NYPJM->LTFIMP_NY
CLTF
4.537
LGEELTFEXP_LGEE->PJM
CLTF
6.253
WECLTFEXP_WEC->PJM
CLTF
3.425
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.32

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.99
MW Contribution:
6.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
30.328
970149AG2-104 GEN
Solar/Wind Harmer
16.378
970155AG2-107 GEN
Solar/Wind Harmer
19.366
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
270520AE2-214 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
0.726
972203AH1-686 GEN
Adder
2.339
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
7.551
252510AF1-249 C
Solar/Wind Harmer
0.051
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.323
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
961921AG1-034 GEN
Solar/Wind Harmer
6.37
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.608
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.304
252519AF1-045_GEN
Solar/Wind Harmer
3.517
970191AG2-125 GEN
Solar/Wind Harmer
1.734
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970825AG2-519 GEN
Solar/Wind Harmer
4.924
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
3.227
246938BC-WTG3
Solar/Wind Harmer
0.232
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274887GEN-1.85
Solar/Wind Harmer
0.165
276843GEN-1.7
Solar/Wind Harmer
0.205
276806AD2-047 C O1
Solar/Wind Harmer
3.589
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
274682WAUKEGAN ;7U
Adder
16.174
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
946671AF1-331 GEN
Solar/Wind Harmer
0.667
965091AG1-374 GEN
Solar/Wind Harmer
18.751
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
270588AE1-091_GEN
Solar/Wind Harmer
4.882
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
959091AF2-200 GEN
Solar/Wind Harmer
3.185
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270291AC1-194 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
2.075
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
253406AD2-031_GEN
Solar/Wind Harmer
0.507
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972163AH1-664 GEN
Solar/Wind Harmer
7.323
972165AH1-665 GEN
Solar/Wind Harmer
5.865
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
12.517
971609AH1-304 GEN
Solar/Wind Harmer
1.067
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
959331AF2-224 GEN
Solar/Wind Harmer
4.543
247521TR3_G114
Solar/Wind Harmer
0.234
965051AG1-369 GEN
Solar/Wind Harmer
3.226
965041AG1-368 GEN
Solar/Wind Harmer
6.455
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.816
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.285
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.578
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.438
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
7.272
965011AG1-365 GEN
Solar/Wind Harmer
6.491
965421AG1-410 GEN
Solar/Wind Harmer
19.339
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
24728605AND G2
Adder
3.541
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.351
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.48
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
963741AG1-226 GEN
Solar/Wind Harmer
15.1
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.32
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.718
944971AF1-162 GEN
Solar/Wind Harmer
6.303
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
971997AH1-543 GEN
Solar/Wind Harmer
3.293
276882AE2-255 GEN
Solar/Wind Harmer
0.732
962781AG1-127 GEN
Solar/Wind Harmer
5.964
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.771
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
971171AH1-044 GEN
Solar/Wind Harmer
3.185
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.224
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
10.862
971655AH1-328 GEN
Solar/Wind Harmer
2.4
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
0
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
960971AF2-388 GEN
Solar/Wind Harmer
3.846
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
270599AE1-208 GEN
Solar/Wind Harmer
5.986
942221AE2-234 GEN
Solar/Wind Harmer
2.621
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.041
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
246937BC-WTG2
Solar/Wind Harmer
0.26
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
965681AG1-436 GEN
Solar/Wind Harmer
8.006
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.422
972043AH1-570 GEN
Solar/Wind Harmer
1.663
972045AH1-571 GEN
Solar/Wind Harmer
1.333
970241AG2-163 GEN
Solar/Wind Harmer
3.722
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
971587AH1-292 GEN
Solar/Wind Harmer
4.656
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
276776AD2-060 GEN
Solar/Wind Harmer
0.676
958011AF2-095 GEN
Solar/Wind Harmer
9.122
970941AG2-585 GEN
Solar/Wind Harmer
3.484
945391AF1-204 GEN
Solar/Wind Harmer
6.73
276897AD1-100 C
Solar/Wind Harmer
15.831
274674JOLIET 9 ;6U
Adder
13.943
276893AG1-478 C
Solar/Wind Harmer
0.421
971125AH1-004 GEN
Solar/Wind Harmer
2.523
970107AG2-081 GEN
Solar/Wind Harmer
1.892
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
958491AF2-143 GEN
Solar/Wind Harmer
9.422
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.57
MW Contribution:
6.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.224
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
10.862
971655AH1-328 GEN
Solar/Wind Harmer
2.4
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
0
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
960971AF2-388 GEN
Solar/Wind Harmer
3.846
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
270599AE1-208 GEN
Solar/Wind Harmer
5.986
942221AE2-234 GEN
Solar/Wind Harmer
2.621
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.041
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
246937BC-WTG2
Solar/Wind Harmer
0.26
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
965681AG1-436 GEN
Solar/Wind Harmer
8.006
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.422
972043AH1-570 GEN
Solar/Wind Harmer
1.663
972045AH1-571 GEN
Solar/Wind Harmer
1.333
970241AG2-163 GEN
Solar/Wind Harmer
3.722
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
971587AH1-292 GEN
Solar/Wind Harmer
4.656
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
276776AD2-060 GEN
Solar/Wind Harmer
0.676
958011AF2-095 GEN
Solar/Wind Harmer
9.122
970941AG2-585 GEN
Solar/Wind Harmer
3.484
945391AF1-204 GEN
Solar/Wind Harmer
6.73
276897AD1-100 C
Solar/Wind Harmer
15.831
274674JOLIET 9 ;6U
Adder
13.943
276893AG1-478 C
Solar/Wind Harmer
0.421
971125AH1-004 GEN
Solar/Wind Harmer
2.523
970107AG2-081 GEN
Solar/Wind Harmer
1.892
958481AF2-142 GEN
Solar/Wind Harmer
9.443
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
30.328
970149AG2-104 GEN
Solar/Wind Harmer
16.378
970155AG2-107 GEN
Solar/Wind Harmer
19.366
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
270520AE2-214 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
0.726
972203AH1-686 GEN
Adder
2.339
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
7.551
252510AF1-249 C
Solar/Wind Harmer
0.051
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
7.272
965011AG1-365 GEN
Solar/Wind Harmer
6.491
965421AG1-410 GEN
Solar/Wind Harmer
19.339
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
24728605AND G2
Adder
3.541
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.351
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.48
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
963741AG1-226 GEN
Solar/Wind Harmer
15.1
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.32
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.718
944971AF1-162 GEN
Solar/Wind Harmer
6.303
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
971997AH1-543 GEN
Solar/Wind Harmer
3.293
276882AE2-255 GEN
Solar/Wind Harmer
0.732
962781AG1-127 GEN
Solar/Wind Harmer
5.964
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.771
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270291AC1-194 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
2.075
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
253406AD2-031_GEN
Solar/Wind Harmer
0.507
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972163AH1-664 GEN
Solar/Wind Harmer
7.323
972165AH1-665 GEN
Solar/Wind Harmer
5.865
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
12.517
971609AH1-304 GEN
Solar/Wind Harmer
1.067
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
959331AF2-224 GEN
Solar/Wind Harmer
4.543
247521TR3_G114
Solar/Wind Harmer
0.234
965051AG1-369 GEN
Solar/Wind Harmer
3.226
965041AG1-368 GEN
Solar/Wind Harmer
6.455
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.816
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.285
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.578
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.438
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
971171AH1-044 GEN
Solar/Wind Harmer
3.185
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
961921AG1-034 GEN
Solar/Wind Harmer
6.37
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.608
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.304
252519AF1-045_GEN
Solar/Wind Harmer
3.517
970191AG2-125 GEN
Solar/Wind Harmer
1.734
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970825AG2-519 GEN
Solar/Wind Harmer
4.924
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
3.227
246938BC-WTG3
Solar/Wind Harmer
0.232
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274887GEN-1.85
Solar/Wind Harmer
0.165
276843GEN-1.7
Solar/Wind Harmer
0.205
276806AD2-047 C O1
Solar/Wind Harmer
3.589
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
274682WAUKEGAN ;7U
Adder
16.174
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
946671AF1-331 GEN
Solar/Wind Harmer
0.667
965091AG1-374 GEN
Solar/Wind Harmer
18.751
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
270588AE1-091_GEN
Solar/Wind Harmer
4.882
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
959091AF2-200 GEN
Solar/Wind Harmer
3.185
944231AF1-091 GEN
Solar/Wind Harmer
14.516
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
958491AF2-143 GEN
Solar/Wind Harmer
9.422
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.19 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5278.17
MW Contribution:
9.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
35.004
970153AG2-106 GEN
Solar/Wind Harmer
15.264
270512AE1-227 GEN2
Solar/Wind Harmer
2.247
270330AC1-082 GEN2
Solar/Wind Harmer
0.49
270329AC1-082 GEN1
Solar/Wind Harmer
0.49
971191AH1-055 GEN
Solar/Wind Harmer
19.037
957541AF2-048 GEN
Solar/Wind Harmer
1.603
970879AG2-548 GEN
Solar/Wind Harmer
8.039
940611AE2-048 GEN
Solar/Wind Harmer
22.073
941391AE2-136 GEN
Solar/Wind Harmer
11.438
270291AC1-194 GEN
Solar/Wind Harmer
5.101
270459AD2-067 GEN
Solar/Wind Harmer
8.368
961821AG1-024 GEN
Solar/Wind Harmer
8.496
270432AC2-029 GEN
Solar/Wind Harmer
6.989
270263AC1-001 GEN
Solar/Wind Harmer
1.042
241955AC1-078 GEN
Solar/Wind Harmer
7.382
945631AF1-228 GEN
Solar/Wind Harmer
4.627
971985AH1-537 GEN
Solar/Wind Harmer
17.539
253338AC1-165 GEN
Solar/Wind Harmer
1.063
253343AC1-166 GEN
Solar/Wind Harmer
1.063
241973AD2-163_GEN1
Solar/Wind Harmer
1.941
241974AD2-163_GEN2
Solar/Wind Harmer
1.941
943861AF1-054 GEN
Solar/Wind Harmer
3.769
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
2.956
241972AD1-140 GEN
Solar/Wind Harmer
4.312
253406AD2-031_GEN
Solar/Wind Harmer
1.227
253433AC1-085 GEN1
Solar/Wind Harmer
5.075
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270223U2-072_GEN1
Solar/Wind Harmer
1.87
270224U2-072_GEN2
Solar/Wind Harmer
1.87
270227U2-072_GEN3
Solar/Wind Harmer
1.87
270228U2-072_GEN4
Solar/Wind Harmer
1.87
270231U2-072_GEN5
Solar/Wind Harmer
1.87
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
7.829
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
9.262
972165AH1-665 GEN
Solar/Wind Harmer
7.409
971029AG2-637 GEN
Solar/Wind Harmer
13.858
270543AE2-219 C
Solar/Wind Harmer
9.219
247536S-71 GEN
Solar/Wind Harmer
3.723
24729505KEY G4
Adder
5.966
958711AF2-162 GEN
Solar/Wind Harmer
0.93
945581AF1-223 GEN
Solar/Wind Harmer
4.167
270356AE2-297 GEN
Solar/Wind Harmer
4.233
961761AG1-017 GEN
Solar/Wind Harmer
0.393
964611AG1-324 GEN
Solar/Wind Harmer
3.579
270071AF1-092 GEN
Solar/Wind Harmer
13.725
970289AG2-191 GEN
Solar/Wind Harmer
1.738
963791AG1-232 GEN
Solar/Wind Harmer
12.295
959331AF2-224 GEN
Solar/Wind Harmer
9.086
247521TR3_G114
Solar/Wind Harmer
3.039
270191TR4_S_V150
Solar/Wind Harmer
2.712
965051AG1-369 GEN
Solar/Wind Harmer
4.516
965041AG1-368 GEN
Solar/Wind Harmer
9.035
339216AC1-074 GEN
Solar/Wind Harmer
1.512
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
35.004
970149AG2-104 GEN
Solar/Wind Harmer
21.615
970155AG2-107 GEN
Solar/Wind Harmer
15.264
270510AE1-227 GEN1
Solar/Wind Harmer
2.647
960001AF2-291 GEN
Solar/Wind Harmer
3.156
270331AC1-082 GEN3
Solar/Wind Harmer
0.491
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
6.054
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
2.653
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
270286AF1-227 GEN2
Solar/Wind Harmer
2.059
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
1.025
253398AE2-221_GEN2
Solar/Wind Harmer
4.334
253316AC1-085 GEN3
Solar/Wind Harmer
7.996
946171AF1-282 GEN
Solar/Wind Harmer
9.551
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
9.479
270391AF1-285 GEN3
Solar/Wind Harmer
1.145
270578AF1-285 GEN2
Solar/Wind Harmer
1.145
252510AF1-249 C
Solar/Wind Harmer
0.394
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
2.993
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270222AC2-111 GEN
Solar/Wind Harmer
4.163
944031AF1-071 GEN
Solar/Wind Harmer
0.937
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
17.484
942081AE2-220 GEN
Solar/Wind Harmer
5.889
270209AC1-174_GEN
Solar/Wind Harmer
3.747
270437AC2-090 C
Solar/Wind Harmer
5.139
270239V3-007_GEN1
Solar/Wind Harmer
1.584
965651AG1-433 GEN
Solar/Wind Harmer
5.023
958861AF2-177 GEN
Solar/Wind Harmer
10.045
945371AF1-202 GEN
Solar/Wind Harmer
6.41
971995AH1-542 GEN
Solar/Wind Harmer
10.104
270005AE1-210 C O1
Solar/Wind Harmer
5.017
970825AG2-519 GEN
Solar/Wind Harmer
1.925
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
12.433
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
4.289
276903AD2-071 C
Solar/Wind Harmer
9.138
965011AG1-365 GEN
Solar/Wind Harmer
9.086
24728605AND G2
Adder
3.47
339221AD2-048_GEN
Solar/Wind Harmer
1.388
965421AG1-410 GEN
Solar/Wind Harmer
27.057
24639705ELKHART HY
Adder
0.138
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
940581AE2-045 GEN
Solar/Wind Harmer
5.47
971605AH1-302 GEN
Solar/Wind Harmer
4.677
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
927014AC1-188 GEN
Solar/Wind Harmer
1.603
270349AD2-093_GEN
Solar/Wind Harmer
3.664
270471AD2-092_GEN
Solar/Wind Harmer
3.664
961921AG1-034 GEN
Solar/Wind Harmer
12.743
960801AF2-371 GEN
Solar/Wind Harmer
2.536
964871AG1-351 GEN
Solar/Wind Harmer
1.751
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
5.566
270287AF1-227 GEN3
Solar/Wind Harmer
2.059
942051AE2-217 GEN
Solar/Wind Harmer
17.671
253325AC1-069 GEN
Solar/Wind Harmer
1.025
270518AE2-148 GEN
Solar/Wind Harmer
11.818
270367AC2-061_GEN
Solar/Wind Harmer
3.046
253394AE2-221_GEN
Solar/Wind Harmer
4.334
253317AC1-085 GEN4
Solar/Wind Harmer
7.996
946181AF1-283 GEN
Solar/Wind Harmer
12.416
270186AC1-089 GEN
Solar/Wind Harmer
5.821
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
960071AF2-298 GEN
Solar/Wind Harmer
1.437
252507AC2-088 GEN
Solar/Wind Harmer
1.699
252519AF1-045_GEN
Solar/Wind Harmer
3.45
942871AE2-306 GEN
Solar/Wind Harmer
0.859
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
252524AE2-267 GEN
Solar/Wind Harmer
1.486
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
276820AF1-078_GEN
Solar/Wind Harmer
1.503
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
7.423
958171AF2-111 GEN
Solar/Wind Harmer
23.182
24379505HDWTR1G C
Solar/Wind Harmer
7.281
270240V3-007_GEN2
Solar/Wind Harmer
5.697
944531AF1-118 GEN
Solar/Wind Harmer
32.194
270004AE1-209 GEN
Solar/Wind Harmer
5.017
946031AF1-268 GEN
Solar/Wind Harmer
7.618
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
970825AG2-519 GEN
Solar/Wind Harmer
5.167
965461AG1-414 GEN
Solar/Wind Harmer
2.074
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.058
270043AE2-236 GEN
Solar/Wind Harmer
5.008
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
4.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.41
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
270054AF2-122 C O1
Solar/Wind Harmer
3.288
971073AG2-665 GEN
Solar/Wind Harmer
8.039
970879AG2-548 GEN
Solar/Wind Harmer
1.168
946101AF1-275 GEN
Solar/Wind Harmer
1.513
270269AC2-059
Solar/Wind Harmer
9.305
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253383AE2-342_GEN
Solar/Wind Harmer
0.868
942861AE2-305 GEN
Solar/Wind Harmer
7.636
253415AE1-040 GEN
Solar/Wind Harmer
1.098
962581AG1-107 GEN
Solar/Wind Harmer
4.832
961491AF2-440 GEN
Solar/Wind Harmer
2.008
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
5.747
252509AD1-136 GEN
Solar/Wind Harmer
0.243
253349AC2-067 GEN
Solar/Wind Harmer
1.925
253400AC2-068 GEN
Solar/Wind Harmer
0.774
938701AE1-092 GEN
Solar/Wind Harmer
19.541
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
253378AE2-206_GEN
Solar/Wind Harmer
3.383
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
6.502
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
9.219
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
5.623
926881AC1-175 GEN
Solar/Wind Harmer
5.139
944541AF1-119 GEN
Solar/Wind Harmer
3.848
960971AF2-388 GEN
Solar/Wind Harmer
10.047
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
4.716
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
7.466
270599AE1-208 GEN
Solar/Wind Harmer
7.466
942221AE2-234 GEN
Solar/Wind Harmer
3.201
970291AG2-192 GEN
Solar/Wind Harmer
1.189
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
3.633
24699105WLD G1 C
Solar/Wind Harmer
3.591
270246TR4_N_V150
Solar/Wind Harmer
0.769
270247TR4_N_V136
Solar/Wind Harmer
0.769
970349AG2-230 GEN
Solar/Wind Harmer
13.564
945421AF1-207 GEN
Solar/Wind Harmer
12.67
957841AF2-078 GEN
Solar/Wind Harmer
5.454
247620Y3-023
Adder
0.413
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.17 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5277.43
MW Contribution:
9.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
35.004
970153AG2-106 GEN
Solar/Wind Harmer
15.264
270512AE1-227 GEN2
Solar/Wind Harmer
2.247
270330AC1-082 GEN2
Solar/Wind Harmer
0.49
270329AC1-082 GEN1
Solar/Wind Harmer
0.49
971191AH1-055 GEN
Solar/Wind Harmer
19.037
957541AF2-048 GEN
Solar/Wind Harmer
1.603
970879AG2-548 GEN
Solar/Wind Harmer
8.039
961921AG1-034 GEN
Solar/Wind Harmer
12.743
960801AF2-371 GEN
Solar/Wind Harmer
2.536
964871AG1-351 GEN
Solar/Wind Harmer
1.751
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
5.566
270287AF1-227 GEN3
Solar/Wind Harmer
2.059
942051AE2-217 GEN
Solar/Wind Harmer
17.671
253325AC1-069 GEN
Solar/Wind Harmer
1.025
270518AE2-148 GEN
Solar/Wind Harmer
11.818
270367AC2-061_GEN
Solar/Wind Harmer
3.046
253394AE2-221_GEN
Solar/Wind Harmer
4.334
253317AC1-085 GEN4
Solar/Wind Harmer
7.996
946181AF1-283 GEN
Solar/Wind Harmer
12.416
270186AC1-089 GEN
Solar/Wind Harmer
5.821
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
960071AF2-298 GEN
Solar/Wind Harmer
1.437
252507AC2-088 GEN
Solar/Wind Harmer
1.699
252519AF1-045_GEN
Solar/Wind Harmer
3.45
942871AE2-306 GEN
Solar/Wind Harmer
0.859
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
252524AE2-267 GEN
Solar/Wind Harmer
1.486
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
276820AF1-078_GEN
Solar/Wind Harmer
1.503
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
7.423
958171AF2-111 GEN
Solar/Wind Harmer
23.182
24379505HDWTR1G C
Solar/Wind Harmer
7.281
270240V3-007_GEN2
Solar/Wind Harmer
5.697
944531AF1-118 GEN
Solar/Wind Harmer
32.194
270004AE1-209 GEN
Solar/Wind Harmer
5.017
946031AF1-268 GEN
Solar/Wind Harmer
7.618
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
970825AG2-519 GEN
Solar/Wind Harmer
5.167
965461AG1-414 GEN
Solar/Wind Harmer
2.074
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.058
270043AE2-236 GEN
Solar/Wind Harmer
5.008
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
4.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.41
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
35.004
970149AG2-104 GEN
Solar/Wind Harmer
21.615
970155AG2-107 GEN
Solar/Wind Harmer
15.264
270510AE1-227 GEN1
Solar/Wind Harmer
2.647
960001AF2-291 GEN
Solar/Wind Harmer
3.156
270331AC1-082 GEN3
Solar/Wind Harmer
0.491
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
6.054
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
2.653
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
270286AF1-227 GEN2
Solar/Wind Harmer
2.059
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
1.025
940611AE2-048 GEN
Solar/Wind Harmer
22.073
941391AE2-136 GEN
Solar/Wind Harmer
11.438
253398AE2-221_GEN2
Solar/Wind Harmer
4.334
253316AC1-085 GEN3
Solar/Wind Harmer
7.996
946171AF1-282 GEN
Solar/Wind Harmer
9.551
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
9.479
270391AF1-285 GEN3
Solar/Wind Harmer
1.145
270578AF1-285 GEN2
Solar/Wind Harmer
1.145
252510AF1-249 C
Solar/Wind Harmer
0.394
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
2.993
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270222AC2-111 GEN
Solar/Wind Harmer
4.163
944031AF1-071 GEN
Solar/Wind Harmer
0.937
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
17.484
942081AE2-220 GEN
Solar/Wind Harmer
5.889
270209AC1-174_GEN
Solar/Wind Harmer
3.747
270437AC2-090 C
Solar/Wind Harmer
5.139
270239V3-007_GEN1
Solar/Wind Harmer
1.584
965651AG1-433 GEN
Solar/Wind Harmer
5.023
958861AF2-177 GEN
Solar/Wind Harmer
10.045
945371AF1-202 GEN
Solar/Wind Harmer
6.41
971995AH1-542 GEN
Solar/Wind Harmer
10.104
270005AE1-210 C O1
Solar/Wind Harmer
5.017
970825AG2-519 GEN
Solar/Wind Harmer
1.925
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
12.433
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
4.289
276903AD2-071 C
Solar/Wind Harmer
9.138
965011AG1-365 GEN
Solar/Wind Harmer
9.086
24728605AND G2
Adder
3.47
339221AD2-048_GEN
Solar/Wind Harmer
1.388
965421AG1-410 GEN
Solar/Wind Harmer
27.057
24639705ELKHART HY
Adder
0.138
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
940581AE2-045 GEN
Solar/Wind Harmer
5.47
971605AH1-302 GEN
Solar/Wind Harmer
4.677
270291AC1-194 GEN
Solar/Wind Harmer
5.101
270459AD2-067 GEN
Solar/Wind Harmer
8.368
961821AG1-024 GEN
Solar/Wind Harmer
8.496
270432AC2-029 GEN
Solar/Wind Harmer
6.989
270263AC1-001 GEN
Solar/Wind Harmer
1.042
241955AC1-078 GEN
Solar/Wind Harmer
7.382
945631AF1-228 GEN
Solar/Wind Harmer
4.627
971985AH1-537 GEN
Solar/Wind Harmer
17.539
253338AC1-165 GEN
Solar/Wind Harmer
1.063
253343AC1-166 GEN
Solar/Wind Harmer
1.063
241973AD2-163_GEN1
Solar/Wind Harmer
1.941
241974AD2-163_GEN2
Solar/Wind Harmer
1.941
943861AF1-054 GEN
Solar/Wind Harmer
3.769
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
2.956
241972AD1-140 GEN
Solar/Wind Harmer
4.312
253406AD2-031_GEN
Solar/Wind Harmer
1.227
253433AC1-085 GEN1
Solar/Wind Harmer
5.075
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270223U2-072_GEN1
Solar/Wind Harmer
1.87
270224U2-072_GEN2
Solar/Wind Harmer
1.87
270227U2-072_GEN3
Solar/Wind Harmer
1.87
270228U2-072_GEN4
Solar/Wind Harmer
1.87
270231U2-072_GEN5
Solar/Wind Harmer
1.87
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
7.829
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
9.262
972165AH1-665 GEN
Solar/Wind Harmer
7.409
971029AG2-637 GEN
Solar/Wind Harmer
13.858
270543AE2-219 C
Solar/Wind Harmer
9.219
247536S-71 GEN
Solar/Wind Harmer
3.723
24729505KEY G4
Adder
5.966
958711AF2-162 GEN
Solar/Wind Harmer
0.93
945581AF1-223 GEN
Solar/Wind Harmer
4.167
270356AE2-297 GEN
Solar/Wind Harmer
4.233
961761AG1-017 GEN
Solar/Wind Harmer
0.393
964611AG1-324 GEN
Solar/Wind Harmer
3.579
270071AF1-092 GEN
Solar/Wind Harmer
13.725
970289AG2-191 GEN
Solar/Wind Harmer
1.738
963791AG1-232 GEN
Solar/Wind Harmer
12.295
959331AF2-224 GEN
Solar/Wind Harmer
9.086
247521TR3_G114
Solar/Wind Harmer
3.039
270191TR4_S_V150
Solar/Wind Harmer
2.712
965051AG1-369 GEN
Solar/Wind Harmer
4.516
965041AG1-368 GEN
Solar/Wind Harmer
9.035
339216AC1-074 GEN
Solar/Wind Harmer
1.512
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
927014AC1-188 GEN
Solar/Wind Harmer
1.603
270349AD2-093_GEN
Solar/Wind Harmer
3.664
270471AD2-092_GEN
Solar/Wind Harmer
3.664
270054AF2-122 C O1
Solar/Wind Harmer
3.288
971073AG2-665 GEN
Solar/Wind Harmer
8.039
970879AG2-548 GEN
Solar/Wind Harmer
1.168
946101AF1-275 GEN
Solar/Wind Harmer
1.513
270269AC2-059
Solar/Wind Harmer
9.305
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253383AE2-342_GEN
Solar/Wind Harmer
0.868
942861AE2-305 GEN
Solar/Wind Harmer
7.636
253415AE1-040 GEN
Solar/Wind Harmer
1.098
962581AG1-107 GEN
Solar/Wind Harmer
4.832
961491AF2-440 GEN
Solar/Wind Harmer
2.008
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
5.747
252509AD1-136 GEN
Solar/Wind Harmer
0.243
253349AC2-067 GEN
Solar/Wind Harmer
1.925
253400AC2-068 GEN
Solar/Wind Harmer
0.774
938701AE1-092 GEN
Solar/Wind Harmer
19.541
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
253378AE2-206_GEN
Solar/Wind Harmer
3.383
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
6.502
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
9.219
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
5.623
926881AC1-175 GEN
Solar/Wind Harmer
5.139
944541AF1-119 GEN
Solar/Wind Harmer
3.848
960971AF2-388 GEN
Solar/Wind Harmer
10.047
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
4.716
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
7.466
270599AE1-208 GEN
Solar/Wind Harmer
7.466
942221AE2-234 GEN
Solar/Wind Harmer
3.201
970291AG2-192 GEN
Solar/Wind Harmer
1.189
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
3.633
24699105WLD G1 C
Solar/Wind Harmer
3.591
270246TR4_N_V150
Solar/Wind Harmer
0.769
270247TR4_N_V136
Solar/Wind Harmer
0.769
970349AG2-230 GEN
Solar/Wind Harmer
13.564
945421AF1-207 GEN
Solar/Wind Harmer
12.67
957841AF2-078 GEN
Solar/Wind Harmer
5.454
247620Y3-023
Adder
0.413
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.98 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5270.18
MW Contribution:
9.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.275
23562401OGROV2
50/50
2.436
24318805MLG1
50/50
6.371
24721905FLATG4
Adder
23.616
962771AG1-126 GEN
Solar/Wind Harmer
35.283
970153AG2-106 GEN
Solar/Wind Harmer
15.385
270512AE1-227 GEN2
Solar/Wind Harmer
2.276
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
971191AH1-055 GEN
Solar/Wind Harmer
19.185
957541AF2-048 GEN
Solar/Wind Harmer
1.616
970879AG2-548 GEN
Solar/Wind Harmer
8.107
961921AG1-034 GEN
Solar/Wind Harmer
12.865
960801AF2-371 GEN
Solar/Wind Harmer
2.559
964871AG1-351 GEN
Solar/Wind Harmer
1.767
24686405CER G5
Adder
8.242
270284AF1-227 GEN1
Solar/Wind Harmer
5.618
270287AF1-227 GEN3
Solar/Wind Harmer
2.078
942051AE2-217 GEN
Solar/Wind Harmer
17.832
253325AC1-069 GEN
Solar/Wind Harmer
1.034
270518AE2-148 GEN
Solar/Wind Harmer
11.924
270367AC2-061_GEN
Solar/Wind Harmer
3.071
253394AE2-221_GEN
Solar/Wind Harmer
4.371
253317AC1-085 GEN4
Solar/Wind Harmer
8.063
946181AF1-283 GEN
Solar/Wind Harmer
12.52
270186AC1-089 GEN
Solar/Wind Harmer
5.868
253303V4-073 C
Solar/Wind Harmer
0.111
253370AE2-315 SEC1
Adder
1.924
253371AE2-315 SEC2
Adder
1.82
960071AF2-298 GEN
Solar/Wind Harmer
1.449
252507AC2-088 GEN
Solar/Wind Harmer
1.712
942871AE2-306 GEN
Solar/Wind Harmer
0.867
270391AF1-285 GEN3
Solar/Wind Harmer
0.445
252519AF1-045_GEN
Solar/Wind Harmer
3.479
252524AE2-267 GEN
Solar/Wind Harmer
1.499
25196608WSDLE5
Adder
8.158
25194608D.CRK4
Adder
1.565
276820AF1-078_GEN
Solar/Wind Harmer
1.517
25196008MFTGT1
Adder
1.267
972167AH1-666 GEN
Solar/Wind Harmer
7.482
958171AF2-111 GEN
Solar/Wind Harmer
23.368
24379505HDWTR1G C
Solar/Wind Harmer
7.343
270240V3-007_GEN2
Solar/Wind Harmer
5.745
944531AF1-118 GEN
Solar/Wind Harmer
32.478
270004AE1-209 GEN
Solar/Wind Harmer
5.06
946031AF1-268 GEN
Solar/Wind Harmer
7.684
962031AG1-047 GEN
Solar/Wind Harmer
2.799
957741AF2-068 GEN
Solar/Wind Harmer
13.884
970825AG2-519 GEN
Solar/Wind Harmer
5.212
965461AG1-414 GEN
Solar/Wind Harmer
2.092
970289AG2-191 GEN
Solar/Wind Harmer
0.708
247642Z2-115 C
Solar/Wind Harmer
0.059
270043AE2-236 GEN
Solar/Wind Harmer
5.054
965021AG1-366 GEN
Solar/Wind Harmer
2.133
971347AH1-153 GEN
Solar/Wind Harmer
4.562
24728705AND G3
Adder
7.317
24728505AND G1
Adder
3.499
958581AF2-149 GEN
Solar/Wind Harmer
3.901
971199AH1-059 GEN
Solar/Wind Harmer
1.914
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
246938BC-WTG3
Solar/Wind Harmer
3.621
270491AE1-102 GEN2
Solar/Wind Harmer
1.183
274772LINCOLN ;3U
Adder
7.587
274752CRETE EC ;2U
Adder
7.403
274753CRETE EC ;3U
Adder
7.403
274724RIVER EC ;11
Adder
15.904
274814UNIV PK N;0U
Adder
4.532
274807UNIV PK N;3U
Adder
4.522
274811UNIV PK N;7U
Adder
4.493
274803UNIV PARK;6U
Adder
5.223
274826FISK ;BP
Adder
9.806
972038AH1-567 GEN2
Adder
0.327
972259AH1-714 GEN
Adder
17.082
274729ELWOOD EC;1P
Adder
14.692
274730ELWOOD EC;6P
Adder
14.692
274734ELWOOD EC;8P
Adder
14.692
964991AG1-363 GEN
Solar/Wind Helper
4.19
238152AF2-075_GEN
Solar/Wind Helper
0.604
238175AF1-290_GEN
Solar/Wind Helper
0.131
23777901MDS_W4-102
Solar/Wind Helper
0.149
238108AE1-109 GEN1
Solar/Wind Helper
0.087
238110AE1-109 GEN3
Solar/Wind Helper
0.087
237001AB1-127_GEN
Solar/Wind Helper
0.372
235063AE1-101 C2
Solar/Wind Helper
1.395
316415AF1-147_GEN2
Solar/Wind Helper
0.753
23559101PLEAS2
50/50
11.275
23684201S70BUS2
50/50
0.318
23562301OGROV1
50/50
2.457
962761AG1-125 GEN
Solar/Wind Harmer
35.283
970149AG2-104 GEN
Solar/Wind Harmer
21.787
970155AG2-107 GEN
Solar/Wind Harmer
15.385
270510AE1-227 GEN1
Solar/Wind Harmer
2.681
960001AF2-291 GEN
Solar/Wind Harmer
3.18
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
971073AG2-665 GEN
Solar/Wind Harmer
1.178
270520AE2-214 GEN
Solar/Wind Harmer
6.11
270273AD2-016 GEN
Solar/Wind Harmer
2.676
972203AH1-686 GEN
Adder
2.316
972269AH1-719 GEN
Adder
2.296
24686505CER G6
Adder
8.307
270286AF1-227 GEN2
Solar/Wind Harmer
2.078
24723205RIVRG3
Adder
18.614
253333AC1-068 GEN
Solar/Wind Harmer
1.034
253398AE2-221_GEN2
Solar/Wind Harmer
4.371
253316AC1-085 GEN3
Solar/Wind Harmer
8.063
946171AF1-282 GEN
Solar/Wind Harmer
9.631
253370AE2-315 SEC1
Adder
1.924
253371AE2-315 SEC2
Adder
1.82
25326309TAIT D
Adder
1.052
270391AF1-285 GEN3
Solar/Wind Harmer
1.157
270578AF1-285 GEN2
Solar/Wind Harmer
1.157
252516AE2-318_GEN
Solar/Wind Harmer
9.558
252510AF1-249 C
Solar/Wind Harmer
0.397
25194608D.CRK4
Adder
1.565
25196808ZIMRHP
Adder
72.004
270317AD1-130_GEN
Solar/Wind Harmer
3.023
270485AE1-090_GEN
Solar/Wind Harmer
0.571
270222AC2-111 GEN
Solar/Wind Harmer
4.198
944031AF1-071 GEN
Solar/Wind Harmer
0.945
25196008MFTGT1
Adder
1.308
945681AF1-233 GEN
Solar/Wind Harmer
17.624
942081AE2-220 GEN
Solar/Wind Harmer
5.939
270209AC1-174_GEN
Solar/Wind Harmer
3.779
270437AC2-090 C
Solar/Wind Harmer
5.183
270239V3-007_GEN1
Solar/Wind Harmer
1.598
971995AH1-542 GEN
Solar/Wind Harmer
10.211
965651AG1-433 GEN
Solar/Wind Harmer
5.067
958861AF2-177 GEN
Solar/Wind Harmer
10.133
945371AF1-202 GEN
Solar/Wind Harmer
6.466
270005AE1-210 C O1
Solar/Wind Harmer
5.06
970825AG2-519 GEN
Solar/Wind Harmer
1.941
970091AG2-072 GEN
Adder
70.821
940611AE2-048 GEN
Solar/Wind Harmer
22.313
941391AE2-136 GEN
Solar/Wind Harmer
11.562
270291AC1-194 GEN
Solar/Wind Harmer
5.145
270459AD2-067 GEN
Solar/Wind Harmer
8.448
961821AG1-024 GEN
Solar/Wind Harmer
8.577
270432AC2-029 GEN
Solar/Wind Harmer
7.05
270263AC1-001 GEN
Solar/Wind Harmer
1.051
241955AC1-078 GEN
Solar/Wind Harmer
7.45
945631AF1-228 GEN
Solar/Wind Harmer
4.669
971985AH1-537 GEN
Solar/Wind Harmer
17.679
253338AC1-165 GEN
Solar/Wind Harmer
1.072
253343AC1-166 GEN
Solar/Wind Harmer
1.072
241973AD2-163_GEN1
Solar/Wind Harmer
1.959
241974AD2-163_GEN2
Solar/Wind Harmer
1.959
943861AF1-054 GEN
Solar/Wind Harmer
3.803
943851AF1-053 GEN
Solar/Wind Harmer
1.838
270340AC2-060 GEN
Solar/Wind Harmer
2.981
241972AD1-140 GEN
Solar/Wind Harmer
4.35
253406AD2-031_GEN
Solar/Wind Harmer
1.237
253433AC1-085 GEN1
Solar/Wind Harmer
5.118
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
253372AE2-315 SEC3
Adder
1.82
253372AE2-315 SEC3
Adder
1.82
25306009OHH W.
Adder
2.761
270223U2-072_GEN1
Solar/Wind Harmer
1.888
270224U2-072_GEN2
Solar/Wind Harmer
1.888
270227U2-072_GEN3
Solar/Wind Harmer
1.888
270228U2-072_GEN4
Solar/Wind Harmer
1.888
270231U2-072_GEN5
Solar/Wind Harmer
1.888
270578AF1-285 GEN2
Solar/Wind Harmer
0.445
270594AE1-207 GEN
Solar/Wind Harmer
12.54
270032AE2-172
Solar/Wind Harmer
4.294
270024AE2-089 GEN
Solar/Wind Harmer
4.327
276903AD2-071 C
Solar/Wind Harmer
9.216
965011AG1-365 GEN
Solar/Wind Harmer
9.171
24728605AND G2
Adder
3.499
339221AD2-048_GEN
Solar/Wind Harmer
1.399
965421AG1-410 GEN
Solar/Wind Harmer
27.321
246936BC-WTG1
Solar/Wind Harmer
3.559
270489AE1-102 GEN1
Solar/Wind Harmer
1.183
24639705ELKHART HY
Adder
0.139
274773LINCOLN ;4U
Adder
7.587
274774LINCOLN ;5U
Adder
7.587
274751CRETE EC ;1U
Adder
7.403
274754CRETE EC ;4U
Adder
7.403
274723RIVER EC ;12
Adder
16.092
274812UNIV PK N;8U
Adder
4.493
274802UNIV PARK;5U
Adder
5.223
274732ELWOOD EC;7P
Adder
14.692
23583801GRNGAP
Solar/Wind Helper
4.95
316095T157 G97
Solar/Wind Helper
1.324
23546401DTGZ2-030
Solar/Wind Helper
0.076
238109AE1-109 GEN2
Solar/Wind Helper
0.087
237038AE2-054 C
Solar/Wind Helper
0.229
235067AD1-061 GEN
Solar/Wind Helper
0.374
237085AD2-009_GEN
Solar/Wind Helper
1.38
237002AB1-128_GEN
Solar/Wind Helper
0.373
23777801MSM_W1-116
Solar/Wind Helper
0.098
25196408WSDLE3
Adder
8.398
25196308WSDLE2
Adder
8.325
25196208WSDLE1
Adder
8.304
25196708WSDLE6
Adder
8.283
25196508WSDLE4
Adder
8.074
270302AB2-170 GEN
Solar/Wind Harmer
7.906
25196108MFTGT2
Adder
1.442
25196108MFTGT2
Adder
1.339
972163AH1-664 GEN
Solar/Wind Harmer
9.335
972165AH1-665 GEN
Solar/Wind Harmer
7.468
971029AG2-637 GEN
Solar/Wind Harmer
13.978
270543AE2-219 C
Solar/Wind Harmer
9.298
247536S-71 GEN
Solar/Wind Harmer
3.755
24729505KEY G4
Adder
6.019
958711AF2-162 GEN
Solar/Wind Harmer
0.938
945581AF1-223 GEN
Solar/Wind Harmer
4.203
270356AE2-297 GEN
Solar/Wind Harmer
4.269
961761AG1-017 GEN
Solar/Wind Harmer
0.396
964611AG1-324 GEN
Solar/Wind Harmer
3.61
270071AF1-092 GEN
Solar/Wind Harmer
13.847
970289AG2-191 GEN
Solar/Wind Harmer
1.753
963791AG1-232 GEN
Solar/Wind Harmer
12.407
959331AF2-224 GEN
Solar/Wind Harmer
9.171
247521TR3_G114
Solar/Wind Harmer
3.068
270191TR4_S_V150
Solar/Wind Harmer
2.738
965051AG1-369 GEN
Solar/Wind Harmer
4.559
965041AG1-368 GEN
Solar/Wind Harmer
9.12
339216AC1-074 GEN
Solar/Wind Harmer
1.524
957201AF2-014 GEN
Solar/Wind Harmer
4.127
270435AC2-044 GEN
Solar/Wind Harmer
1.82
274775LINCOLN ;6U
Adder
7.587
274776LINCOLN ;7U
Adder
7.587
274777LINCOLN ;8U
Adder
7.587
972037AH1-567 GEN1
Adder
0.164
972228AH1-698 GEN2
Adder
3.318
972227AH1-698 GEN1
Adder
2.336
274827FISK ;RP
Adder
6.949
274800UNIV PARK;3U
Adder
5.222
274801UNIV PARK;4U
Adder
5.222
274687WILL CNTY;4U
Adder
24.982
274687WILL CNTY;4U
Adder
24.982
941621AE2-160 GEN
Adder
2.939
274728ELWOOD EC;5P
Adder
14.692
274731ELWOOD EC;2P
Adder
14.692
274733ELWOOD EC;3P
Adder
14.692
274735ELWOOD EC;4P
Adder
11.662
238169AE2-226 GEN1
Solar/Wind Helper
0.593
238170AE2-226 GEN2
Solar/Wind Helper
0.593
23750701CROSSCHOOL
Solar/Wind Helper
1.115
23779801AA1-109
Solar/Wind Helper
0.164
3138216PACIFIC
Solar/Wind Helper
0.037
237030AB1-096 C
Solar/Wind Helper
0.057
237025AB1-124 C
Solar/Wind Helper
0.141
970935AG2-582 GEN
50/50
1216.009
23684101S70BUS1
50/50
0.312
23534401HANNIB
50/50
0.148
24318905MLG2
50/50
4.725
927014AC1-188 GEN
Solar/Wind Harmer
1.616
270349AD2-093_GEN
Solar/Wind Harmer
3.698
270471AD2-092_GEN
Solar/Wind Harmer
3.698
270054AF2-122 C O1
Solar/Wind Harmer
3.319
971073AG2-665 GEN
Solar/Wind Harmer
8.107
970879AG2-548 GEN
Solar/Wind Harmer
1.178
946101AF1-275 GEN
Solar/Wind Harmer
1.527
270269AC2-059
Solar/Wind Harmer
9.386
253383AE2-342_GEN
Solar/Wind Harmer
0.876
24723005RIVRG1
Adder
18.614
24723105RIVRG2
Adder
18.614
942861AE2-305 GEN
Solar/Wind Harmer
7.705
253415AE1-040 GEN
Solar/Wind Harmer
1.108
962581AG1-107 GEN
Solar/Wind Harmer
4.871
961491AF2-440 GEN
Solar/Wind Harmer
2.024
972159AH1-661 GEN
Adder
0.964
25326109MON D
Adder
1.264
253370AE2-315 SEC1
Adder
1.924
25322209TAIT E
Adder
9.36
25322209TAIT E
Adder
9.149
25183208HLCRTG
Solar/Wind Harmer
5.795
252509AD1-136 GEN
Solar/Wind Harmer
0.245
938701AE1-092 GEN
Solar/Wind Harmer
19.736
253349AC2-067 GEN
Solar/Wind Harmer
1.941
253400AC2-068 GEN
Solar/Wind Harmer
0.781
25194408D.CRK1
Adder
7.198
25194508D.CRK3
Adder
1.346
253378AE2-206_GEN
Solar/Wind Harmer
3.414
25326509SID D
Adder
1.244
270462AD2-086
Solar/Wind Harmer
6.566
24728805RICHG1
Adder
3.521
24728905RICHG2
Adder
3.521
970883AG2-550 GEN
Solar/Wind Harmer
9.298
970885AG2-551 GEN
Solar/Wind Harmer
2.162
270383AD1-128 GEN
Solar/Wind Harmer
5.671
926881AC1-175 GEN
Solar/Wind Harmer
5.183
944541AF1-119 GEN
Solar/Wind Harmer
3.882
960971AF2-388 GEN
Solar/Wind Harmer
10.135
247621Y3-024
Adder
0.223
270201AC2-176 GEN
Solar/Wind Harmer
4.757
964611AG1-324 GEN
Solar/Wind Harmer
0.484
270031AE2-169
Solar/Wind Harmer
7.53
270599AE1-208 GEN
Solar/Wind Harmer
7.53
942221AE2-234 GEN
Solar/Wind Harmer
3.23
970291AG2-192 GEN
Solar/Wind Harmer
1.199
970291AG2-192 GEN
Solar/Wind Harmer
0.386
24725505WLD G2 C
Solar/Wind Harmer
3.664
24699105WLD G1 C
Solar/Wind Harmer
3.622
270246TR4_N_V150
Solar/Wind Harmer
0.776
270247TR4_N_V136
Solar/Wind Harmer
0.776
970349AG2-230 GEN
Solar/Wind Harmer
13.685
246937BC-WTG2
Solar/Wind Harmer
3.559
247620Y3-023
Adder
0.416
274770LINCOLN ;1U
Adder
7.587
274771LINCOLN ;2U
Adder
7.587
274805UNIV PK N;1U
Adder
4.503
274808UNIV PK N;4U
Adder
4.473
316097T157 G90
Solar/Wind Helper
1.324
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
237061AD1-155 GEN
Solar/Wind Helper
1.5
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.231
237080AD1-060 GEN
Solar/Wind Helper
0.287
235062AE1-101 C1
Solar/Wind Helper
1.395
237006AB1-125 GEN
Solar/Wind Helper
0.106
316411AF1-147_GEN1
Solar/Wind Helper
0.753
945421AF1-207 GEN
Solar/Wind Harmer
3.67
LAGNLTFEXP_LAGN->PJM
CLTF
13.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.915
TVALTFEXP_TVA->PJM
CLTF
6.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.394
MECLTFEXP_MEC->PJM
CLTF
14.194
SIGELTFEXP_SIGE->PJM
CLTF
0.459
CPLELTFEXP_CPLE->PJM
CLTF
1.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
103.644
NYPJM->LTFIMP_NY
CLTF
4.427
LGEELTFEXP_LGEE->PJM
CLTF
6.165
WECLTFEXP_WEC->PJM
CLTF
3.367
AG2-052LTFEXP_AG2-052->PJM
LTF
0.21
AH1-155LTFEXP_AH1-155->PJM
LTF
0.315

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5250.02
MW Contribution:
6.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
970879AG2-548 GEN
Solar/Wind Harmer
1.168
270269AC2-059
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
942861AE2-305 GEN
Solar/Wind Harmer
5.328
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
938701AE1-092 GEN
Solar/Wind Harmer
10.602
971655AH1-328 GEN
Solar/Wind Harmer
2.343
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
960971AF2-388 GEN
Solar/Wind Harmer
3.762
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
270599AE1-208 GEN
Solar/Wind Harmer
5.858
971613AH1-306 GEN
Solar/Wind Harmer
3.066
942221AE2-234 GEN
Solar/Wind Harmer
2.563
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.04
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
972045AH1-571 GEN
Solar/Wind Harmer
1.309
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.711
965681AG1-436 GEN
Solar/Wind Harmer
7.827
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
971587AH1-292 GEN
Solar/Wind Harmer
4.565
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
971125AH1-004 GEN
Solar/Wind Harmer
2.48
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
8.924
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
958481AF2-142 GEN
Solar/Wind Harmer
9.241
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.221
944231AF1-091 GEN
Solar/Wind Harmer
14.169
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270291AC1-194 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
971985AH1-537 GEN
Solar/Wind Harmer
2.039
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
253406AD2-031_GEN
Solar/Wind Harmer
0.497
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
7.194
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270543AE2-219 C
Solar/Wind Harmer
4.502
247536S-71 GEN
Solar/Wind Harmer
0.257
24729505KEY G4
Adder
5.966
945581AF1-223 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
270071AF1-092 GEN
Solar/Wind Harmer
12.235
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
959331AF2-224 GEN
Solar/Wind Harmer
4.437
247521TR3_G114
Solar/Wind Harmer
0.229
965051AG1-369 GEN
Solar/Wind Harmer
3.151
965041AG1-368 GEN
Solar/Wind Harmer
6.303
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270526AF1-158 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
270399AC1-101 GEN
Solar/Wind Harmer
1.959
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
970179AG2-119 GEN
Solar/Wind Harmer
5.512
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.152
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.441
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971171AH1-044 GEN
Solar/Wind Harmer
2.06
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
29.52
970149AG2-104 GEN
Solar/Wind Harmer
15.941
970155AG2-107 GEN
Solar/Wind Harmer
18.85
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
7.407
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
12.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970825AG2-519 GEN
Solar/Wind Harmer
2.272
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.119
965011AG1-365 GEN
Solar/Wind Harmer
6.339
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.17
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.272
24639705ELKHART HY
Adder
0.138
963741AG1-226 GEN
Solar/Wind Harmer
14.786
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.244
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.617
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.588
962781AG1-127 GEN
Solar/Wind Harmer
5.837
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
961921AG1-034 GEN
Solar/Wind Harmer
6.223
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.329
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252507AC2-088 GEN
Solar/Wind Harmer
0.298
252519AF1-045_GEN
Solar/Wind Harmer
3.45
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
970191AG2-125 GEN
Solar/Wind Harmer
1.699
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
958171AF2-111 GEN
Solar/Wind Harmer
16.173
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
28.761
270004AE1-209 GEN
Solar/Wind Harmer
1.388
946031AF1-268 GEN
Solar/Wind Harmer
6.094
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
3.154
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.226
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.532
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274887GEN-1.85
Solar/Wind Harmer
0.161
276843GEN-1.7
Solar/Wind Harmer
0.2
276806AD2-047 C O1
Solar/Wind Harmer
3.512
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
970707AG2-453 GEN
Solar/Wind Harmer
20.232
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
965091AG1-374 GEN
Solar/Wind Harmer
18.362
959611AF2-252 GEN
Solar/Wind Harmer
2.04
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
959091AF2-200 GEN
Solar/Wind Harmer
2.06
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.41 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5248.4
MW Contribution:
6.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
970879AG2-548 GEN
Solar/Wind Harmer
1.168
270269AC2-059
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
942861AE2-305 GEN
Solar/Wind Harmer
5.328
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
938701AE1-092 GEN
Solar/Wind Harmer
10.602
971655AH1-328 GEN
Solar/Wind Harmer
2.343
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
960971AF2-388 GEN
Solar/Wind Harmer
3.762
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
270599AE1-208 GEN
Solar/Wind Harmer
5.858
971613AH1-306 GEN
Solar/Wind Harmer
3.066
942221AE2-234 GEN
Solar/Wind Harmer
2.563
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.04
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
972045AH1-571 GEN
Solar/Wind Harmer
1.309
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.711
965681AG1-436 GEN
Solar/Wind Harmer
7.827
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
971587AH1-292 GEN
Solar/Wind Harmer
4.565
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
971125AH1-004 GEN
Solar/Wind Harmer
2.48
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
8.924
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270291AC1-194 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
971985AH1-537 GEN
Solar/Wind Harmer
2.039
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
253406AD2-031_GEN
Solar/Wind Harmer
0.497
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
7.194
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270543AE2-219 C
Solar/Wind Harmer
4.502
247536S-71 GEN
Solar/Wind Harmer
0.257
24729505KEY G4
Adder
5.966
945581AF1-223 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
270071AF1-092 GEN
Solar/Wind Harmer
12.235
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
959331AF2-224 GEN
Solar/Wind Harmer
4.437
247521TR3_G114
Solar/Wind Harmer
0.229
965051AG1-369 GEN
Solar/Wind Harmer
3.151
965041AG1-368 GEN
Solar/Wind Harmer
6.303
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270526AF1-158 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
270399AC1-101 GEN
Solar/Wind Harmer
1.959
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
970179AG2-119 GEN
Solar/Wind Harmer
5.512
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.152
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.441
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971171AH1-044 GEN
Solar/Wind Harmer
2.06
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
29.52
970149AG2-104 GEN
Solar/Wind Harmer
15.941
970155AG2-107 GEN
Solar/Wind Harmer
18.85
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
7.407
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
12.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970825AG2-519 GEN
Solar/Wind Harmer
2.272
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.119
965011AG1-365 GEN
Solar/Wind Harmer
6.339
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.17
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.272
24639705ELKHART HY
Adder
0.138
963741AG1-226 GEN
Solar/Wind Harmer
14.786
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.244
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.617
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.588
962781AG1-127 GEN
Solar/Wind Harmer
5.837
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
958481AF2-142 GEN
Solar/Wind Harmer
9.241
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.221
944231AF1-091 GEN
Solar/Wind Harmer
14.169
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
961921AG1-034 GEN
Solar/Wind Harmer
6.223
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.329
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252507AC2-088 GEN
Solar/Wind Harmer
0.298
252519AF1-045_GEN
Solar/Wind Harmer
3.45
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
970191AG2-125 GEN
Solar/Wind Harmer
1.699
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
958171AF2-111 GEN
Solar/Wind Harmer
16.173
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
28.761
270004AE1-209 GEN
Solar/Wind Harmer
1.388
946031AF1-268 GEN
Solar/Wind Harmer
6.094
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
3.154
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.226
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.532
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274887GEN-1.85
Solar/Wind Harmer
0.161
276843GEN-1.7
Solar/Wind Harmer
0.2
276806AD2-047 C O1
Solar/Wind Harmer
3.512
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
970707AG2-453 GEN
Solar/Wind Harmer
20.232
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
965091AG1-374 GEN
Solar/Wind Harmer
18.362
959611AF2-252 GEN
Solar/Wind Harmer
2.04
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
959091AF2-200 GEN
Solar/Wind Harmer
2.06
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.25 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:5006.21
MW Contribution:
10.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270459AD2-067 GEN
Solar/Wind Harmer
10.212
961821AG1-024 GEN
Solar/Wind Harmer
10.368
972239AH1-704 GEN
Adder
2.66
241955AC1-078 GEN
Solar/Wind Harmer
8.781
241973AD2-163_GEN1
Solar/Wind Harmer
2.319
241974AD2-163_GEN2
Solar/Wind Harmer
2.319
943861AF1-054 GEN
Solar/Wind Harmer
4.476
943851AF1-053 GEN
Solar/Wind Harmer
2.163
945631AF1-228 GEN
Solar/Wind Harmer
5.449
270223U2-072_GEN1
Solar/Wind Harmer
2.274
270224U2-072_GEN2
Solar/Wind Harmer
2.274
270227U2-072_GEN3
Solar/Wind Harmer
2.274
270228U2-072_GEN4
Solar/Wind Harmer
2.274
270231U2-072_GEN5
Solar/Wind Harmer
2.274
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
8.025
253338AC1-165 GEN
Solar/Wind Harmer
1.235
253343AC1-166 GEN
Solar/Wind Harmer
1.235
270302AB2-170 GEN
Solar/Wind Harmer
9.522
940611AE2-048 GEN
Solar/Wind Harmer
24.76
941391AE2-136 GEN
Solar/Wind Harmer
12.83
270263AC1-001 GEN
Solar/Wind Harmer
1.17
241972AD1-140 GEN
Solar/Wind Harmer
5.01
270291AC1-194 GEN
Solar/Wind Harmer
5.61
270340AC2-060 GEN
Solar/Wind Harmer
3.331
970179AG2-119 GEN
Solar/Wind Harmer
8.806
253372AE2-315 SEC3
Adder
2.062
253372AE2-315 SEC3
Adder
2.062
25306009OHH W.
Adder
3.128
253406AD2-031_GEN
Solar/Wind Harmer
1.383
957201AF2-014 GEN
Solar/Wind Harmer
4.888
270435AC2-044 GEN
Solar/Wind Harmer
2.156
253433AC1-085 GEN1
Solar/Wind Harmer
5.708
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.604
270191TR4_S_V150
Solar/Wind Harmer
3.216
965051AG1-369 GEN
Solar/Wind Harmer
5.355
959331AF2-224 GEN
Solar/Wind Harmer
10.725
270377AD1-106 GEN
Solar/Wind Harmer
5.62
270007AE1-245 C
Solar/Wind Harmer
5.779
965041AG1-368 GEN
Solar/Wind Harmer
10.701
24729505KEY G4
Adder
6.914
966831AG1-554 GEN
Solar/Wind Harmer
1.275
971567AH1-282 GEN
Solar/Wind Harmer
5.316
270071AF1-092 GEN
Solar/Wind Harmer
15.971
963791AG1-232 GEN
Solar/Wind Harmer
14.371
971985AH1-537 GEN
Solar/Wind Harmer
18.964
958711AF2-162 GEN
Solar/Wind Harmer
1.074
25196408WSDLE3
Adder
9.339
25196308WSDLE2
Adder
9.258
25196208WSDLE1
Adder
9.235
25196708WSDLE6
Adder
9.211
25196508WSDLE4
Adder
8.979
945581AF1-223 GEN
Solar/Wind Harmer
4.795
971029AG2-637 GEN
Solar/Wind Harmer
15.851
970031AG2-029 GEN
Solar/Wind Harmer
26.415
270404AC1-167 GEN
Solar/Wind Harmer
1.144
270543AE2-219 C
Solar/Wind Harmer
10.561
247536S-71 GEN
Solar/Wind Harmer
4.271
961761AG1-017 GEN
Solar/Wind Harmer
0.451
964611AG1-324 GEN
Solar/Wind Harmer
4.11
25196108MFTGT2
Adder
1.598
25196108MFTGT2
Adder
1.484
274775LINCOLN ;6U
Adder
8.673
274776LINCOLN ;7U
Adder
8.673
274777LINCOLN ;8U
Adder
8.673
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.938
274800UNIV PARK;3U
Adder
5.964
274801UNIV PARK;4U
Adder
5.964
972228AH1-698 GEN2
Adder
3.789
972227AH1-698 GEN1
Adder
2.668
274687WILL CNTY;4U
Adder
28.512
274687WILL CNTY;4U
Adder
28.512
274675JOLIET 29;7U
Adder
31.291
274675JOLIET 29;7U
Adder
30.174
274728ELWOOD EC;5P
Adder
16.762
274731ELWOOD EC;2P
Adder
16.762
274733ELWOOD EC;3P
Adder
16.762
274735ELWOOD EC;4P
Adder
16.762
274744AC1-111 GEN8
Adder
5.677
274746AC1-111 G10
Adder
5.677
23750701CROSSCHOOL
Solar/Wind Helper
1.517
270166AC1-044 GEN3
50/50
7.109
23559101PLEAS2
50/50
6.362
962761AG1-125 GEN
Solar/Wind Harmer
41.016
970149AG2-104 GEN
Solar/Wind Harmer
25.328
970155AG2-107 GEN
Solar/Wind Harmer
17.885
270286AF1-227 GEN2
Solar/Wind Harmer
2.504
270520AE2-214 GEN
Solar/Wind Harmer
7.243
270391AF1-285 GEN3
Solar/Wind Harmer
1.393
270578AF1-285 GEN2
Solar/Wind Harmer
1.393
253333AC1-068 GEN
Solar/Wind Harmer
1.191
270317AD1-130_GEN
Solar/Wind Harmer
3.64
270485AE1-090_GEN
Solar/Wind Harmer
0.688
270273AD2-016 GEN
Solar/Wind Harmer
3.013
971995AH1-542 GEN
Solar/Wind Harmer
12.463
972269AH1-719 GEN
Adder
2.545
971073AG2-665 GEN
Solar/Wind Harmer
1.275
25326309TAIT D
Adder
1.195
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
241813AF1-122_GEN
Solar/Wind Harmer
5.897
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.9
246936BC-WTG1
Solar/Wind Harmer
4.216
270489AE1-102 GEN1
Solar/Wind Harmer
1.401
965421AG1-410 GEN
Solar/Wind Harmer
32.318
960001AF2-291 GEN
Solar/Wind Harmer
3.25
253316AC1-085 GEN3
Solar/Wind Harmer
8.992
946171AF1-282 GEN
Solar/Wind Harmer
10.741
965011AG1-365 GEN
Solar/Wind Harmer
10.725
270258AD1-119 GEN
Solar/Wind Harmer
2.156
965651AG1-433 GEN
Solar/Wind Harmer
5.801
252516AE2-318_GEN
Solar/Wind Harmer
10.604
958861AF2-177 GEN
Solar/Wind Harmer
11.586
270024AE2-089 GEN
Solar/Wind Harmer
4.961
252510AF1-249 C
Solar/Wind Harmer
0.441
25194608D.CRK4
Adder
1.739
945371AF1-202 GEN
Solar/Wind Harmer
7.376
270297AD1-101 GEN
Solar/Wind Harmer
2.147
270222AC2-111 GEN
Solar/Wind Harmer
4.718
944031AF1-071 GEN
Solar/Wind Harmer
1.062
270510AE1-227 GEN1
Solar/Wind Harmer
2.605
270005AE1-210 C O1
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
6.717
270209AC1-174_GEN
Solar/Wind Harmer
4.274
270437AC2-090 C
Solar/Wind Harmer
5.862
270239V3-007_GEN1
Solar/Wind Harmer
1.807
270331AC1-082 GEN3
Solar/Wind Harmer
0.501
25196808ZIMRHP
Adder
79.685
970825AG2-519 GEN
Solar/Wind Harmer
2.203
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.634
25196008MFTGT1
Adder
1.45
274751CRETE EC ;1U
Adder
8.473
274754CRETE EC ;4U
Adder
8.473
274773LINCOLN ;4U
Adder
8.673
274774LINCOLN ;5U
Adder
8.673
274723RIVER EC ;12
Adder
18.412
274812UNIV PK N;8U
Adder
5.137
274802UNIV PARK;5U
Adder
5.968
24728605AND G2
Adder
3.925
274676JOLIET 29;8U
Adder
31.291
274732ELWOOD EC;7P
Adder
16.762
274674JOLIET 9 ;6U
Adder
15.699
972203AH1-686 GEN
Adder
2.344
274745AC1-111 GEN9
Adder
5.677
970091AG2-072 GEN
Adder
77.647
274682WAUKEGAN ;7U
Adder
18.178
316095T157 G97
Solar/Wind Helper
1.515
23583801GRNGAP
Solar/Wind Helper
5.644
238185AF2-356 C
Solar/Wind Helper
2.686
238109AE1-109 GEN2
Solar/Wind Helper
0.115
238120AE2-309 GEN
Solar/Wind Helper
0.534
238126S14_GEN_1
Solar/Wind Helper
0.836
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.667
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.451
237002AB1-128_GEN
Solar/Wind Helper
0.448
23751101LEADS_P59
Solar/Wind Helper
2.15
23777801MSM_W1-116
Solar/Wind Helper
0.116
3141196NOKESVL
Solar/Wind Helper
1.039
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.283
233987AB2-037 GEN
Solar/Wind Helper
2.369
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.235
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.76
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.513
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.118
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
238118U2-030_1
Solar/Wind Helper
0.345
238169AE2-226 GEN1
Solar/Wind Helper
0.708
238170AE2-226 GEN2
Solar/Wind Helper
0.708
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.647
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.372
959381AF2-229 GEN
Solar/Wind Helper
0.36
20390526W1-045 C
Solar/Wind Helper
0.354
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.515
205956AE1-196_GEN
Solar/Wind Helper
0.514
233915AB1-141 GEN
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.235
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.795
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
316164AC1-076 GEN
Solar/Wind Helper
1.108
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.069
964851AG1-348 GEN
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
203955AF1-039 C O1
Solar/Wind Helper
0.332
209027LOR2_Q27
Solar/Wind Helper
1.036
212266LOR1
Solar/Wind Helper
0.302
209054AE2-059 GEN
Solar/Wind Helper
0.08
24318805MLG1
50/50
10.127
23559001PLEAS1
50/50
6.362
270051AF1-062 GEN
50/50
11.798
270475AD2-096_GEN
50/50
7.137
962771AG1-126 GEN
Solar/Wind Harmer
41.016
970153AG2-106 GEN
Solar/Wind Harmer
17.885
961921AG1-034 GEN
Solar/Wind Harmer
15.551
270284AF1-227 GEN1
Solar/Wind Harmer
6.768
270287AF1-227 GEN3
Solar/Wind Harmer
2.504
24721905FLATG4
Adder
24.045
942051AE2-217 GEN
Solar/Wind Harmer
20.995
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.045
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
270518AE2-148 GEN
Solar/Wind Harmer
13.818
253325AC1-069 GEN
Solar/Wind Harmer
1.191
276820AF1-078_GEN
Solar/Wind Harmer
1.776
958581AF2-149 GEN
Solar/Wind Harmer
4.712
971199AH1-059 GEN
Solar/Wind Harmer
2.312
970879AG2-548 GEN
Solar/Wind Harmer
8.771
960071AF2-298 GEN
Solar/Wind Harmer
1.647
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.717
253394AE2-221_GEN
Solar/Wind Harmer
4.9
246938BC-WTG3
Solar/Wind Harmer
4.289
270491AE1-102 GEN2
Solar/Wind Harmer
1.401
971191AH1-055 GEN
Solar/Wind Harmer
20.077
253317AC1-085 GEN4
Solar/Wind Harmer
8.992
946181AF1-283 GEN
Solar/Wind Harmer
13.963
965021AG1-366 GEN
Solar/Wind Harmer
2.494
958091AF2-103 GEN
Solar/Wind Harmer
0.173
24695305TIMB G C
Solar/Wind Harmer
3.573
270588AE1-091_GEN
Solar/Wind Harmer
11.753
944531AF1-118 GEN
Solar/Wind Harmer
37.358
270043AE2-236 GEN
Solar/Wind Harmer
5.865
252519AF1-045_GEN
Solar/Wind Harmer
3.859
270367AC2-061_GEN
Solar/Wind Harmer
3.367
252524AE2-267 GEN
Solar/Wind Harmer
1.667
25196608WSDLE5
Adder
9.072
25194608D.CRK4
Adder
1.739
252507AC2-088 GEN
Solar/Wind Harmer
1.892
270044AE2-322 C
Solar/Wind Harmer
1.388
270063AE2-323 C
Solar/Wind Harmer
2.32
962031AG1-047 GEN
Solar/Wind Harmer
3.189
957741AF2-068 GEN
Solar/Wind Harmer
15.82
971347AH1-153 GEN
Solar/Wind Harmer
5.266
270512AE1-227 GEN2
Solar/Wind Harmer
2.212
270186AC1-089 GEN
Solar/Wind Harmer
6.425
946031AF1-268 GEN
Solar/Wind Harmer
8.725
270004AE1-209 GEN
Solar/Wind Harmer
5.743
24379505HDWTR1G C
Solar/Wind Harmer
8.305
270240V3-007_GEN2
Solar/Wind Harmer
6.498
270330AC1-082 GEN2
Solar/Wind Harmer
0.5
270329AC1-082 GEN1
Solar/Wind Harmer
0.5
970825AG2-519 GEN
Solar/Wind Harmer
5.915
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.404
274752CRETE EC ;2U
Adder
8.473
274753CRETE EC ;3U
Adder
8.473
274772LINCOLN ;3U
Adder
8.673
274724RIVER EC ;11
Adder
18.196
274814UNIV PK N;0U
Adder
5.182
274807UNIV PK N;3U
Adder
5.171
274811UNIV PK N;7U
Adder
5.137
274803UNIV PARK;6U
Adder
5.968
24728705AND G3
Adder
8.209
24728505AND G1
Adder
3.925
274826FISK ;BP
Adder
11.201
972038AH1-567 GEN2
Adder
0.373
972259AH1-714 GEN
Adder
19.5
274676JOLIET 29;8U
Adder
30.174
274729ELWOOD EC;1P
Adder
16.762
274730ELWOOD EC;6P
Adder
16.762
274734ELWOOD EC;8P
Adder
16.762
274736ELWOOD EC;9P
Adder
16.762
274682WAUKEGAN ;7U
Adder
18.178
964991AG1-363 GEN
Solar/Wind Helper
5.171
238108AE1-109 GEN1
Solar/Wind Helper
0.115
238110AE1-109 GEN3
Solar/Wind Helper
0.115
238127S14_GEN_2
Solar/Wind Helper
0.836
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.715
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.023
235063AE1-101 C2
Solar/Wind Helper
1.678
237001AB1-127_GEN
Solar/Wind Helper
0.446
237048AF1-022 C
Solar/Wind Helper
0.186
316415AF1-147_GEN2
Solar/Wind Helper
0.898
205916AD1-020 GEN
Solar/Wind Helper
1.732
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.514
233918AB1-142 GEN
Solar/Wind Helper
0.508
233944AB2-135 GEN
Solar/Wind Helper
0.596
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.513
232408W1-005 C
Solar/Wind Helper
0.513
316447AC1-158 HLD
Solar/Wind Helper
2.876
316044AC1-158 PL1
Solar/Wind Helper
1.307
228729W2-030 C
Solar/Wind Helper
0.112
270119AB2-067 GEN1
50/50
7.109
270120AB2-067 GEN2
50/50
7.109
24318905MLG2
50/50
7.027
270349AD2-093_GEN
Solar/Wind Harmer
4.455
270471AD2-092_GEN
Solar/Wind Harmer
4.455
270054AF2-122 C O1
Solar/Wind Harmer
3.972
946101AF1-275 GEN
Solar/Wind Harmer
1.811
253383AE2-342_GEN
Solar/Wind Harmer
1.04
942861AE2-305 GEN
Solar/Wind Harmer
9.069
938701AE1-092 GEN
Solar/Wind Harmer
23.766
270462AD2-086
Solar/Wind Harmer
7.908
270269AC2-059
Solar/Wind Harmer
10.571
253378AE2-206_GEN
Solar/Wind Harmer
3.997
972159AH1-661 GEN
Adder
1.106
253415AE1-040 GEN
Solar/Wind Harmer
1.242
25326509SID D
Adder
1.451
241960AC2-195 GEN
Solar/Wind Harmer
3.055
971073AG2-665 GEN
Solar/Wind Harmer
8.771
970879AG2-548 GEN
Solar/Wind Harmer
1.275
25326109MON D
Adder
1.442
25322209TAIT E
Adder
10.635
25322209TAIT E
Adder
10.396
253370AE2-315 SEC1
Adder
2.18
927014AC1-188 GEN
Solar/Wind Harmer
1.717
253349AC2-067 GEN
Solar/Wind Harmer
2.203
253400AC2-068 GEN
Solar/Wind Harmer
0.886
246937BC-WTG2
Solar/Wind Harmer
4.216
270246TR4_N_V150
Solar/Wind Harmer
0.912
270247TR4_N_V136
Solar/Wind Harmer
0.912
942801AE2-298 GEN
Solar/Wind Harmer
1.621
247607V1-011 GEN
Solar/Wind Harmer
4.231
962581AG1-107 GEN
Solar/Wind Harmer
5.356
961491AF2-440 GEN
Solar/Wind Harmer
2.226
25183208HLCRTG
Solar/Wind Harmer
6.427
944541AF1-119 GEN
Solar/Wind Harmer
4.444
960971AF2-388 GEN
Solar/Wind Harmer
11.601
942221AE2-234 GEN
Solar/Wind Harmer
3.71
25194408D.CRK1
Adder
8
25194508D.CRK3
Adder
1.496
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.561
970885AG2-551 GEN
Solar/Wind Harmer
2.456
247621Y3-024
Adder
0.255
270201AC2-176 GEN
Solar/Wind Harmer
5.42
964611AG1-324 GEN
Solar/Wind Harmer
0.551
970349AG2-230 GEN
Solar/Wind Harmer
15.797
270031AE2-169
Solar/Wind Harmer
8.576
270599AE1-208 GEN
Solar/Wind Harmer
8.576
270383AD1-128 GEN
Solar/Wind Harmer
6.419
926881AC1-175 GEN
Solar/Wind Harmer
5.862
247620Y3-023
Adder
0.483
944231AF1-091 GEN
Solar/Wind Harmer
18.887
24728805RICHG1
Adder
3.96
24728905RICHG2
Adder
3.96
274770LINCOLN ;1U
Adder
8.673
274771LINCOLN ;2U
Adder
8.673
274805UNIV PK N;1U
Adder
5.149
274808UNIV PK N;4U
Adder
5.115
274674JOLIET 9 ;6U
Adder
15.699
274696ROCKY RD ;4P
Adder
11.533
274695ROCKY RD ;2P
Adder
11.267
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.501
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.329
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.091
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.799
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.443
961331AF2-424 GEN
Solar/Wind Helper
0.442
961421AF2-433 GEN
Solar/Wind Helper
0.441
957921AF2-086 GEN
Solar/Wind Helper
0.436
270594AE1-207 GEN
Solar/Wind Harmer
13.371
270032AE2-172
Solar/Wind Harmer
4.579
274693ROCKY RD ;1P
Adder
11.156
274697ROCKY RD ;3P
Adder
3.061
274683WAUKEGAN ;8U
Adder
21.305
274683WAUKEGAN ;8U
Adder
9.68
316097T157 G90
Solar/Wind Helper
1.515
235054AD2-180 GEN
Solar/Wind Helper
2.054
23585401KL_K28_T16
Solar/Wind Helper
1.5
235531U2-073 GEN
Solar/Wind Helper
3.347
238117U2-030
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.501
238148AE2-230_GEN2
Solar/Wind Helper
0.501
238149AF1-291A_GEN
Solar/Wind Helper
0.143
23751201ROTHROCK
Solar/Wind Helper
0.836
235020AA1-095 C
Solar/Wind Helper
0.054
237061AD1-155 GEN
Solar/Wind Helper
1.772
238221AF1-254 C O1
Solar/Wind Helper
0.278
237080AD1-060 GEN
Solar/Wind Helper
0.346
235062AE1-101 C1
Solar/Wind Helper
1.678
316411AF1-147_GEN1
Solar/Wind Helper
0.898
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.371
223402AF1-300 C
Solar/Wind Helper
0.371
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.385
232424Y1-079 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.363
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.575
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.972
232428Y3-058 C
Solar/Wind Helper
0.342
232410W1-006 C
Solar/Wind Helper
0.513
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.235
233954AC2-188 GEN
Solar/Wind Helper
0.235
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.182
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.028
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.051
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
961431AF2-434 GEN
Solar/Wind Helper
0.441
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.526
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.075
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.093
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.586
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
202652Y1-033 WT C
Solar/Wind Helper
0.504
961301AF2-421 GEN
Solar/Wind Helper
0.443
963151AG1-164 GEN
Solar/Wind Helper
0.443
961341AF2-425 GEN
Solar/Wind Helper
0.442
212507AE2-042_GEN
Solar/Wind Helper
1.561
LAGNLTFEXP_LAGN->PJM
CLTF
14.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.742
TVALTFEXP_TVA->PJM
CLTF
7.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.079
MECLTFEXP_MEC->PJM
CLTF
15.894
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CPLELTFEXP_CPLE->PJM
CLTF
0.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.743
NYPJM->LTFIMP_NY
CLTF
4.85
LGEELTFEXP_LGEE->PJM
CLTF
6.747
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.4 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4974.31
MW Contribution:
10.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.082
23559101PLEAS2
50/50
6.18
962761AG1-125 GEN
Solar/Wind Harmer
40.857
970149AG2-104 GEN
Solar/Wind Harmer
25.229
24318805MLG1
50/50
10.084
23559001PLEAS1
50/50
6.18
270051AF1-062 GEN
50/50
11.783
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.857
970153AG2-106 GEN
Solar/Wind Harmer
17.815
961921AG1-034 GEN
Solar/Wind Harmer
15.539
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.892
942051AE2-217 GEN
Solar/Wind Harmer
20.96
960801AF2-371 GEN
Solar/Wind Harmer
2.935
964871AG1-351 GEN
Solar/Wind Harmer
2.026
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.795
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
972239AH1-704 GEN
Adder
2.673
270459AD2-067 GEN
Solar/Wind Harmer
10.203
961821AG1-024 GEN
Solar/Wind Harmer
10.359
241955AC1-078 GEN
Solar/Wind Harmer
8.768
241973AD2-163_GEN1
Solar/Wind Harmer
2.315
241974AD2-163_GEN2
Solar/Wind Harmer
2.315
945631AF1-228 GEN
Solar/Wind Harmer
5.44
943861AF1-054 GEN
Solar/Wind Harmer
4.468
943851AF1-053 GEN
Solar/Wind Harmer
2.159
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
970155AG2-107 GEN
Solar/Wind Harmer
17.815
270520AE2-214 GEN
Solar/Wind Harmer
7.233
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.451
270273AD2-016 GEN
Solar/Wind Harmer
3.008
972269AH1-719 GEN
Adder
2.564
971073AG2-665 GEN
Solar/Wind Harmer
1.273
25326309TAIT D
Adder
1.192
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
241813AF1-122_GEN
Solar/Wind Harmer
5.894
971201AH1-060 GEN
Solar/Wind Harmer
1.842
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.241
960001AF2-291 GEN
Solar/Wind Harmer
3.242
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.696
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.784
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.552
270024AE2-089 GEN
Solar/Wind Harmer
4.947
252510AF1-249 C
Solar/Wind Harmer
0.44
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.355
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270005AE1-210 C O1
Solar/Wind Harmer
5.726
25196808ZIMRHP
Adder
79.465
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
942081AE2-220 GEN
Solar/Wind Harmer
6.698
270209AC1-174_GEN
Solar/Wind Harmer
4.262
270437AC2-090 C
Solar/Wind Harmer
5.845
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.448
274754CRETE EC ;4U
Adder
8.448
274773LINCOLN ;4U
Adder
8.646
274774LINCOLN ;5U
Adder
8.646
274723RIVER EC ;12
Adder
18.356
274812UNIV PK N;8U
Adder
5.122
274802UNIV PARK;5U
Adder
5.949
24728605AND G2
Adder
3.913
274676JOLIET 29;8U
Adder
31.195
274732ELWOOD EC;7P
Adder
16.71
274674JOLIET 9 ;6U
Adder
15.65
972203AH1-686 GEN
Adder
2.333
274745AC1-111 GEN9
Adder
5.66
970091AG2-072 GEN
Adder
77.376
274682WAUKEGAN ;7U
Adder
18.122
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.674
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.532
238126S14_GEN_1
Solar/Wind Helper
0.833
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.663
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.45
237002AB1-128_GEN
Solar/Wind Helper
0.447
23751101LEADS_P59
Solar/Wind Helper
2.129
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.363
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.441
270594AE1-207 GEN
Solar/Wind Harmer
13.331
270032AE2-172
Solar/Wind Harmer
4.566
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.013
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
940611AE2-048 GEN
Solar/Wind Harmer
24.928
941391AE2-136 GEN
Solar/Wind Harmer
12.917
270263AC1-001 GEN
Solar/Wind Harmer
1.168
241972AD1-140 GEN
Solar/Wind Harmer
4.999
270291AC1-194 GEN
Solar/Wind Harmer
5.603
970179AG2-119 GEN
Solar/Wind Harmer
8.8
270340AC2-060 GEN
Solar/Wind Harmer
3.323
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.877
270435AC2-044 GEN
Solar/Wind Harmer
2.151
270377AD1-106 GEN
Solar/Wind Harmer
5.62
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.342
959331AF2-224 GEN
Solar/Wind Harmer
10.696
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.674
971567AH1-282 GEN
Solar/Wind Harmer
5.319
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.894
270071AF1-092 GEN
Solar/Wind Harmer
15.924
963791AG1-232 GEN
Solar/Wind Harmer
14.332
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.071
25196408WSDLE3
Adder
9.314
25196308WSDLE2
Adder
9.233
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.955
945581AF1-223 GEN
Solar/Wind Harmer
4.781
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.807
970031AG2-029 GEN
Solar/Wind Harmer
26.342
270543AE2-219 C
Solar/Wind Harmer
10.531
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.099
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.48
274775LINCOLN ;6U
Adder
8.646
274776LINCOLN ;7U
Adder
8.646
274777LINCOLN ;8U
Adder
8.646
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.914
274800UNIV PARK;3U
Adder
5.946
274801UNIV PARK;4U
Adder
5.946
972228AH1-698 GEN2
Adder
3.777
972227AH1-698 GEN1
Adder
2.66
274687WILL CNTY;4U
Adder
28.425
274687WILL CNTY;4U
Adder
28.425
274675JOLIET 29;7U
Adder
31.195
274675JOLIET 29;7U
Adder
30.081
274728ELWOOD EC;5P
Adder
16.71
274731ELWOOD EC;2P
Adder
16.71
274733ELWOOD EC;3P
Adder
16.71
274735ELWOOD EC;4P
Adder
16.71
274744AC1-111 GEN8
Adder
5.66
274746AC1-111 G10
Adder
5.66
23750701CROSSCHOOL
Solar/Wind Helper
1.512
238118U2-030_1
Solar/Wind Helper
0.344
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.644
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.234
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
203955AF1-039 C O1
Solar/Wind Helper
0.331
958581AF2-149 GEN
Solar/Wind Harmer
4.716
971199AH1-059 GEN
Solar/Wind Harmer
2.315
970879AG2-548 GEN
Solar/Wind Harmer
8.757
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.713
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.279
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.022
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.488
958091AF2-103 GEN
Solar/Wind Harmer
0.172
24695305TIMB G C
Solar/Wind Harmer
3.564
270588AE1-091_GEN
Solar/Wind Harmer
11.739
944531AF1-118 GEN
Solar/Wind Harmer
37.25
270043AE2-236 GEN
Solar/Wind Harmer
5.848
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.18
957741AF2-068 GEN
Solar/Wind Harmer
15.775
971347AH1-153 GEN
Solar/Wind Harmer
5.25
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.7
270004AE1-209 GEN
Solar/Wind Harmer
5.726
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
24379505HDWTR1G C
Solar/Wind Harmer
8.281
270240V3-007_GEN2
Solar/Wind Harmer
6.479
970825AG2-519 GEN
Solar/Wind Harmer
5.897
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.448
274753CRETE EC ;3U
Adder
8.448
274772LINCOLN ;3U
Adder
8.646
274724RIVER EC ;11
Adder
18.141
274814UNIV PK N;0U
Adder
5.166
274807UNIV PK N;3U
Adder
5.155
274811UNIV PK N;7U
Adder
5.122
274803UNIV PARK;6U
Adder
5.949
24728705AND G3
Adder
8.184
24728505AND G1
Adder
3.913
274826FISK ;BP
Adder
11.167
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.441
274676JOLIET 29;8U
Adder
30.081
274729ELWOOD EC;1P
Adder
16.71
274730ELWOOD EC;6P
Adder
16.71
274734ELWOOD EC;8P
Adder
16.71
274736ELWOOD EC;9P
Adder
16.71
274682WAUKEGAN ;7U
Adder
18.122
964991AG1-363 GEN
Solar/Wind Helper
5.16
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.833
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.015
235063AE1-101 C2
Solar/Wind Helper
1.674
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.185
316415AF1-147_GEN2
Solar/Wind Helper
0.896
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.507
233944AB2-135 GEN
Solar/Wind Helper
0.595
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.519
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.582
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
202652Y1-033 WT C
Solar/Wind Helper
0.501
961341AF2-425 GEN
Solar/Wind Helper
0.441
270119AB2-067 GEN1
50/50
7.082
270120AB2-067 GEN2
50/50
7.082
24318905MLG2
50/50
7.035
270349AD2-093_GEN
Solar/Wind Harmer
4.445
270471AD2-092_GEN
Solar/Wind Harmer
4.445
270054AF2-122 C O1
Solar/Wind Harmer
3.971
946101AF1-275 GEN
Solar/Wind Harmer
1.808
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.053
938701AE1-092 GEN
Solar/Wind Harmer
23.731
270462AD2-086
Solar/Wind Harmer
7.892
270269AC2-059
Solar/Wind Harmer
10.554
972159AH1-661 GEN
Adder
1.111
253378AE2-206_GEN
Solar/Wind Harmer
3.988
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.053
971073AG2-665 GEN
Solar/Wind Harmer
8.757
970879AG2-548 GEN
Solar/Wind Harmer
1.273
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.371
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.713
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.41
944541AF1-119 GEN
Solar/Wind Harmer
4.431
960971AF2-388 GEN
Solar/Wind Harmer
11.568
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.978
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.531
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.405
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.75
270031AE2-169
Solar/Wind Harmer
8.551
270599AE1-208 GEN
Solar/Wind Harmer
8.551
270383AD1-128 GEN
Solar/Wind Harmer
6.401
926881AC1-175 GEN
Solar/Wind Harmer
5.845
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.84
24728805RICHG1
Adder
3.949
24728905RICHG2
Adder
3.949
274770LINCOLN ;1U
Adder
8.646
274771LINCOLN ;2U
Adder
8.646
274805UNIV PK N;1U
Adder
5.133
274808UNIV PK N;4U
Adder
5.099
274674JOLIET 9 ;6U
Adder
15.65
274696ROCKY RD ;4P
Adder
11.497
274695ROCKY RD ;2P
Adder
11.232
274693ROCKY RD ;1P
Adder
11.121
274697ROCKY RD ;3P
Adder
3.051
274683WAUKEGAN ;8U
Adder
21.239
274683WAUKEGAN ;8U
Adder
9.65
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.044
23585401KL_K28_T16
Solar/Wind Helper
1.493
235531U2-073 GEN
Solar/Wind Helper
3.333
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.5
238148AE2-230_GEN2
Solar/Wind Helper
0.5
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.83
237061AD1-155 GEN
Solar/Wind Helper
1.768
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.674
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233982AB2-133 GEN
Solar/Wind Helper
0.362
233946AB2-136 GEN
Solar/Wind Helper
0.574
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
14.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.682
TVALTFEXP_TVA->PJM
CLTF
7.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.966
MECLTFEXP_MEC->PJM
CLTF
15.842
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.337
NYPJM->LTFIMP_NY
CLTF
4.834
LGEELTFEXP_LGEE->PJM
CLTF
6.725
WECLTFEXP_WEC->PJM
CLTF
3.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.01 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4959.97
MW Contribution:
10.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.01 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4959.97
MW Contribution:
10.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4917.49
MW Contribution:
7.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.678
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270291AC1-194 GEN
Solar/Wind Harmer
0
970179AG2-119 GEN
Solar/Wind Harmer
6.854
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
253406AD2-031_GEN
Solar/Wind Harmer
0.559
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270377AD1-106 GEN
Solar/Wind Harmer
2.842
247521TR3_G114
Solar/Wind Harmer
0.27
965051AG1-369 GEN
Solar/Wind Harmer
3.723
959331AF2-224 GEN
Solar/Wind Harmer
5.217
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.438
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
963791AG1-232 GEN
Solar/Wind Harmer
9.987
270071AF1-092 GEN
Solar/Wind Harmer
14.177
971985AH1-537 GEN
Solar/Wind Harmer
2.196
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
25196508WSDLE4
Adder
8.944
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
270543AE2-219 C
Solar/Wind Harmer
5.137
247536S-71 GEN
Solar/Wind Harmer
0.293
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
970289AG2-191 GEN
Solar/Wind Harmer
1.382
971771AH1-392 GEN
Solar/Wind Harmer
7.271
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
971549AH1-272 GEN
Solar/Wind Harmer
14.794
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.634
274776LINCOLN ;7U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972228AH1-698 GEN2
Adder
3.772
972227AH1-698 GEN1
Adder
2.656
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
274728ELWOOD EC;5P
Adder
16.687
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274735ELWOOD EC;4P
Adder
16.687
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
274744AC1-111 GEN8
Adder
5.652
274746AC1-111 G10
Adder
5.652
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
970169AG2-114 GEN
Solar/Wind Harmer
7.011
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
971411AH1-196 GEN
Solar/Wind Harmer
10.47
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.32
23750701CROSSCHOOL
Solar/Wind Helper
1.509
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.512
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.062
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.057
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
270166AC1-044 GEN3
50/50
7.069
23559101PLEAS2
50/50
6.097
962761AG1-125 GEN
Solar/Wind Harmer
34.394
970149AG2-104 GEN
Solar/Wind Harmer
18.573
970155AG2-107 GEN
Solar/Wind Harmer
21.963
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.894
270273AD2-016 GEN
Solar/Wind Harmer
0.807
972269AH1-719 GEN
Adder
2.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965421AG1-410 GEN
Solar/Wind Harmer
22.47
960001AF2-291 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965011AG1-365 GEN
Solar/Wind Harmer
7.453
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
958861AF2-177 GEN
Solar/Wind Harmer
3.191
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.732
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.351
970825AG2-519 GEN
Solar/Wind Harmer
2.589
24639705ELKHART HY
Adder
0.16
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
276903AD2-071 C
Solar/Wind Harmer
8.095
25196008MFTGT1
Adder
1.443
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.365
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274754CRETE EC ;4U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
274802UNIV PARK;5U
Adder
5.941
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
31.151
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
939401AE1-172 GEN
Solar/Wind Harmer
5.275
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
274682WAUKEGAN ;7U
Adder
18.096
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.818
971997AH1-543 GEN
Solar/Wind Harmer
3.68
962781AG1-127 GEN
Solar/Wind Harmer
6.668
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
316095T157 G97
Solar/Wind Helper
1.51
23583801GRNGAP
Solar/Wind Helper
5.626
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
238126S14_GEN_1
Solar/Wind Helper
0.831
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.661
237038AE2-054 C
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
270119AB2-067 GEN1
50/50
7.069
270120AB2-067 GEN2
50/50
7.069
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.31
938701AE1-092 GEN
Solar/Wind Harmer
12.867
971655AH1-328 GEN
Solar/Wind Harmer
2.843
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
25326509SID D
Adder
1.446
971073AG2-665 GEN
Solar/Wind Harmer
5.597
970879AG2-548 GEN
Solar/Wind Harmer
1.272
25326109MON D
Adder
1.437
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
246937BC-WTG2
Solar/Wind Harmer
0.302
270246TR4_N_V150
Solar/Wind Harmer
0.048
270247TR4_N_V136
Solar/Wind Harmer
0.048
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.351
944541AF1-119 GEN
Solar/Wind Harmer
0.492
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.792
211065PSPA IPP
Solar/Wind Helper
0.152
963161AG1-165 GEN
Solar/Wind Helper
0.441
957471AF2-041 GEN
Solar/Wind Harmer
13.586
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
24318805MLG1
50/50
10.065
23559001PLEAS1
50/50
6.097
270051AF1-062 GEN
50/50
11.777
270475AD2-096_GEN
50/50
7.114
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
961921AG1-034 GEN
Solar/Wind Harmer
7.586
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
970191AG2-125 GEN
Solar/Wind Harmer
1.937
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
971191AH1-055 GEN
Solar/Wind Harmer
19.175
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
944531AF1-118 GEN
Solar/Wind Harmer
33.233
270043AE2-236 GEN
Solar/Wind Harmer
4.754
252519AF1-045_GEN
Solar/Wind Harmer
3.844
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
9.036
25194608D.CRK4
Adder
1.732
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
971347AH1-153 GEN
Solar/Wind Harmer
3.658
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.95
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
970289AG2-191 GEN
Solar/Wind Harmer
0.8
945111AF1-176 GEN
Solar/Wind Harmer
5.891
247642Z2-115 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
274753CRETE EC ;3U
Adder
8.436
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274811UNIV PK N;7U
Adder
5.114
972167AH1-666 GEN
Solar/Wind Harmer
5.69
274803UNIV PARK;6U
Adder
5.941
24728705AND G3
Adder
8.173
24728505AND G1
Adder
3.908
274887GEN-1.85
Solar/Wind Harmer
0.185
276843GEN-1.7
Solar/Wind Harmer
0.23
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274826FISK ;BP
Adder
11.151
972038AH1-567 GEN2
Adder
0.372
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
972259AH1-714 GEN
Adder
19.413
274676JOLIET 29;8U
Adder
30.039
274729ELWOOD EC;1P
Adder
16.687
274730ELWOOD EC;6P
Adder
16.687
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
274682WAUKEGAN ;7U
Adder
18.096
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970193AG2-126 GEN
Solar/Wind Harmer
10.468
970571AG2-364 GEN
Solar/Wind Harmer
13.944
964991AG1-363 GEN
Solar/Wind Helper
5.155
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.831
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
23562501BACKB
Solar/Wind Helper
1.012
235063AE1-101 C2
Solar/Wind Helper
1.672
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.512
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.594
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.868
316044AC1-158 PL1
Solar/Wind Helper
1.303
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.516
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
960971AF2-388 GEN
Solar/Wind Harmer
4.326
942221AE2-234 GEN
Solar/Wind Harmer
2.958
25194408D.CRK1
Adder
7.968
25194508D.CRK3
Adder
1.49
970621AG2-405 GEN
Solar/Wind Harmer
1.345
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970885AG2-551 GEN
Solar/Wind Harmer
2.446
247621Y3-024
Adder
0.253
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270031AE2-169
Solar/Wind Harmer
4.021
270599AE1-208 GEN
Solar/Wind Harmer
6.701
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728805RICHG1
Adder
3.944
24728905RICHG2
Adder
3.944
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.052
965791AG1-447 GEN
Solar/Wind Harmer
6.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274805UNIV PK N;1U
Adder
5.126
274808UNIV PK N;4U
Adder
5.092
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
276776AD2-060 GEN
Solar/Wind Harmer
0.758
958011AF2-095 GEN
Solar/Wind Harmer
10.234
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
274674JOLIET 9 ;6U
Adder
15.628
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274696ROCKY RD ;4P
Adder
11.481
274695ROCKY RD ;2P
Adder
11.216
274693ROCKY RD ;1P
Adder
11.106
274697ROCKY RD ;3P
Adder
3.047
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276901AD2-066 C O1
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
962691AG1-118 GEN
Solar/Wind Harmer
21.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
942111AE2-223 GEN
Solar/Wind Harmer
2.266
316097T157 G90
Solar/Wind Helper
1.51
235054AD2-180 GEN
Solar/Wind Helper
2.04
23585401KL_K28_T16
Solar/Wind Helper
1.489
235531U2-073 GEN
Solar/Wind Helper
3.327
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.344
235062AE1-101 C1
Solar/Wind Helper
1.672
316411AF1-147_GEN1
Solar/Wind Helper
0.895
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.17
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.031
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.58
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
202652Y1-033 WT C
Solar/Wind Helper
0.5
959091AF2-200 GEN
Solar/Wind Harmer
9.057
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.69 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4873.53
MW Contribution:
10.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.05
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
962761AG1-125 GEN
Solar/Wind Harmer
40.867
970149AG2-104 GEN
Solar/Wind Harmer
25.235
970155AG2-107 GEN
Solar/Wind Harmer
17.82
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
971995AH1-542 GEN
Solar/Wind Harmer
12.942
972269AH1-719 GEN
Adder
2.693
270317AD1-130_GEN
Solar/Wind Harmer
3.738
270485AE1-090_GEN
Solar/Wind Harmer
0.706
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
972239AH1-704 GEN
50/50
3.095
270459AD2-067 GEN
Solar/Wind Harmer
10.428
961821AG1-024 GEN
Solar/Wind Harmer
10.588
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270302AB2-170 GEN
Solar/Wind Harmer
9.776
270432AC2-029 GEN
Solar/Wind Harmer
8.117
24318805MLG1
50/50
10
23559001PLEAS1
50/50
5.445
270051AF1-062 GEN
50/50
11.971
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965421AG1-410 GEN
Solar/Wind Harmer
33.164
971073AG2-665 GEN
Solar/Wind Harmer
1.284
25326309TAIT D
Adder
1.207
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
270297AD1-101 GEN
Solar/Wind Harmer
2.226
965011AG1-365 GEN
Solar/Wind Harmer
10.939
270258AD1-119 GEN
Solar/Wind Harmer
2.219
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
958861AF2-177 GEN
Solar/Wind Harmer
11.712
960001AF2-291 GEN
Solar/Wind Harmer
3.236
24639705ELKHART HY
Adder
0.164
945371AF1-202 GEN
Solar/Wind Harmer
7.453
270216AD2-079_GEN
Solar/Wind Harmer
0.645
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
944031AF1-071 GEN
Solar/Wind Harmer
1.069
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25194608D.CRK4
Adder
1.747
25196808ZIMRHP
Adder
79.955
23906502RICHG2&3
Adder
1.268
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274754CRETE EC ;4U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
274812UNIV PK N;8U
Adder
5.194
274802UNIV PARK;5U
Adder
6.031
23920202STRYCT
Adder
1.44
274676JOLIET 29;8U
Adder
31.606
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
23583801GRNGAP
Solar/Wind Helper
6.383
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
23546401DTGZ2-030
Solar/Wind Helper
0.1
238120AE2-309 GEN
Solar/Wind Helper
0.557
238126S14_GEN_1
Solar/Wind Helper
0.87
237038AE2-054 C
Solar/Wind Helper
0.294
235067AD1-061 GEN
Solar/Wind Helper
0.481
237085AD2-009_GEN
Solar/Wind Helper
1.776
237002AB1-128_GEN
Solar/Wind Helper
0.477
3141196NOKESVL
Solar/Wind Helper
1.144
23777801MSM_W1-116
Solar/Wind Helper
0.123
226910AB2-157 C
Solar/Wind Helper
0.016
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
3132273ORANGE
Solar/Wind Helper
0.049
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
232417X3-008 C
Solar/Wind Helper
0.238
233964AF2-378 GEN
Solar/Wind Helper
0.043
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253338AC1-165 GEN
Solar/Wind Harmer
1.249
253343AC1-166 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270377AD1-106 GEN
Solar/Wind Harmer
5.917
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270291AC1-194 GEN
Solar/Wind Harmer
5.669
270340AC2-060 GEN
Solar/Wind Harmer
3.354
957201AF2-014 GEN
Solar/Wind Harmer
5.019
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
270191TR4_S_V150
Solar/Wind Harmer
3.29
965051AG1-369 GEN
Solar/Wind Harmer
5.479
25306009OHH W.
Adder
3.158
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
3147666LOUISA
Solar/Wind Helper
0.553
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
233950AC2-186 GEN
Solar/Wind Helper
0.119
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
966881AG1-559 GEN
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
205941AD2-115 GEN
Solar/Wind Helper
0.499
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.777
211065PSPA IPP
Solar/Wind Helper
0.151
960841AF2-375 GEN
Solar/Wind Harmer
0.624
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
958711AF2-162 GEN
Solar/Wind Harmer
1.086
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
270499AE1-146 GEN
Solar/Wind Harmer
2.679
270543AE2-219 C
Solar/Wind Harmer
10.668
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
964611AG1-324 GEN
Solar/Wind Harmer
4.154
971771AH1-392 GEN
Solar/Wind Harmer
9.58
944161AF1-084 GEN
Solar/Wind Harmer
2.352
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196508WSDLE4
Adder
9.023
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274775LINCOLN ;6U
Adder
8.764
274776LINCOLN ;7U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972228AH1-698 GEN2
Adder
3.828
972227AH1-698 GEN1
Adder
2.695
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
274728ELWOOD EC;5P
Adder
16.929
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
274735ELWOOD EC;4P
Adder
16.929
23750701CROSSCHOOL
Solar/Wind Helper
1.591
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
226929AD2-058 GEN
Solar/Wind Helper
0.108
3141426STAFORD
Solar/Wind Helper
0.058
315651AD1-115 GEN
Solar/Wind Helper
0.883
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
959381AF2-229 GEN
Solar/Wind Helper
0.368
20390526W1-045 C
Solar/Wind Helper
0.361
205943AE1-185 GEN
Solar/Wind Helper
0.521
205956AE1-196_GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.238
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
230434AG1-499 GEN
Solar/Wind Helper
0.234
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
20675128HRM_W1-127
Solar/Wind Helper
0.03
270119AB2-067 GEN1
50/50
7.05
270120AB2-067 GEN2
50/50
7.05
24318905MLG2
50/50
7.451
270054AF2-122 C O1
Solar/Wind Harmer
4.054
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
946101AF1-275 GEN
Solar/Wind Harmer
1.838
253383AE2-342_GEN
Solar/Wind Harmer
1.057
938701AE1-092 GEN
Solar/Wind Harmer
24.428
942861AE2-305 GEN
Solar/Wind Harmer
9.201
270462AD2-086
Solar/Wind Harmer
8.12
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
253415AE1-040 GEN
Solar/Wind Harmer
1.252
25326109MON D
Adder
1.457
246937BC-WTG2
Solar/Wind Harmer
4.329
971073AG2-665 GEN
Solar/Wind Harmer
8.835
970879AG2-548 GEN
Solar/Wind Harmer
1.284
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
942801AE2-298 GEN
Solar/Wind Harmer
1.666
247607V1-011 GEN
Solar/Wind Harmer
4.348
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
270247TR4_N_V136
Solar/Wind Harmer
0.933
247522W1-056 GEN
Solar/Wind Harmer
2.469
253349AC2-067 GEN
Solar/Wind Harmer
2.225
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944231AF1-091 GEN
Solar/Wind Harmer
19.433
942221AE2-234 GEN
Solar/Wind Harmer
3.759
944541AF1-119 GEN
Solar/Wind Harmer
4.494
960971AF2-388 GEN
Solar/Wind Harmer
11.731
247620Y3-023
Adder
0.492
970349AG2-230 GEN
Solar/Wind Harmer
16.027
247621Y3-024
Adder
0.257
25183208HLCRTG
Solar/Wind Harmer
6.454
970883AG2-550 GEN
Solar/Wind Harmer
10.668
970885AG2-551 GEN
Solar/Wind Harmer
2.481
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
270201AC2-176 GEN
Solar/Wind Harmer
5.48
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
24728905RICHG2
Adder
3.989
970935AG2-582 GEN
Adder
238.716
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
238148AE2-230_GEN2
Solar/Wind Helper
0.556
238149AF1-291A_GEN
Solar/Wind Helper
0.159
237061AD1-155 GEN
Solar/Wind Helper
1.974
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
23585401KL_K28_T16
Solar/Wind Helper
1.534
235020AA1-095 C
Solar/Wind Helper
0.058
238117U2-030
Solar/Wind Helper
0.357
238221AF1-254 C O1
Solar/Wind Helper
0.297
237080AD1-060 GEN
Solar/Wind Helper
0.369
235062AE1-101 C1
Solar/Wind Helper
1.786
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
237006AB1-125 GEN
Solar/Wind Helper
0.132
316006AB2-029 C
Solar/Wind Helper
0.131
223401AF1-299 GEN
Solar/Wind Helper
0.389
223402AF1-300 C
Solar/Wind Helper
0.389
316045AC1-158 PL2
Solar/Wind Helper
4.643
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
232424Y1-079 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.581
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
232410W1-006 C
Solar/Wind Helper
0.518
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
966001AG1-469 GEN
Solar/Wind Helper
0.256
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.152
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
270518AE2-148 GEN
Solar/Wind Harmer
13.997
958581AF2-149 GEN
Solar/Wind Harmer
4.955
971199AH1-059 GEN
Solar/Wind Harmer
2.432
24721905FLATG4
Adder
23.444
253325AC1-069 GEN
Solar/Wind Harmer
1.205
970065AG2-057 GEN
Solar/Wind Harmer
0.972
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
961961AG1-039 GEN
Solar/Wind Harmer
3.18
246938BC-WTG3
Solar/Wind Harmer
4.404
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
970879AG2-548 GEN
Solar/Wind Harmer
8.835
958091AF2-103 GEN
Solar/Wind Harmer
0.178
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270043AE2-236 GEN
Solar/Wind Harmer
5.961
944531AF1-118 GEN
Solar/Wind Harmer
37.819
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971191AH1-055 GEN
Solar/Wind Harmer
20.005
971347AH1-153 GEN
Solar/Wind Harmer
5.342
247643Z2-116 C
Solar/Wind Harmer
0.074
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25196608WSDLE5
Adder
9.116
25194608D.CRK4
Adder
1.747
270367AC2-061_GEN
Solar/Wind Harmer
3.375
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
25196008MFTGT1
Adder
1.409
274752CRETE EC ;2U
Adder
8.571
274753CRETE EC ;3U
Adder
8.571
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274811UNIV PK N;7U
Adder
5.194
274803UNIV PARK;6U
Adder
6.031
274826FISK ;BP
Adder
11.319
972038AH1-567 GEN2
Adder
0.377
972259AH1-714 GEN
Adder
19.698
274676JOLIET 29;8U
Adder
30.477
274729ELWOOD EC;1P
Adder
16.929
274730ELWOOD EC;6P
Adder
16.929
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238108AE1-109 GEN1
Solar/Wind Helper
0.122
238110AE1-109 GEN3
Solar/Wind Helper
0.122
238152AF2-075_GEN
Solar/Wind Helper
0.794
238175AF1-290_GEN
Solar/Wind Helper
0.173
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
235063AE1-101 C2
Solar/Wind Helper
1.786
237001AB1-127_GEN
Solar/Wind Helper
0.476
316415AF1-147_GEN2
Solar/Wind Helper
0.984
23562501BACKB
Solar/Wind Helper
1
316447AC1-158 HLD
Solar/Wind Helper
3.193
316044AC1-158 PL1
Solar/Wind Helper
1.451
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.521
233918AB1-142 GEN
Solar/Wind Helper
0.514
233944AB2-135 GEN
Solar/Wind Helper
0.603
232426Y1-080 FULL
Solar/Wind Helper
0.04
3147666LOUISA
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
232408W1-005 C
Solar/Wind Helper
0.518
316192AB2-158 GEN
Solar/Wind Helper
1.618
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674628WNG_W3-110
Solar/Wind Helper
0.09
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674928WA_W3-044
Solar/Wind Helper
0.099
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.573
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.151
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
MECLTFEXP_MEC->PJM
CLTF
15.924
SIGELTFEXP_SIGE->PJM
CLTF
0.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
NYPJM->LTFIMP_NY
CLTF
4.574
LGEELTFEXP_LGEE->PJM
CLTF
6.731
WECLTFEXP_WEC->PJM
CLTF
3.853
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4632.89
MW Contribution:
7.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.4 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:1908.5
MW Contribution:
3.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
1.525
23888602TROY G2
50/50
1.525
945411AF1-206 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.522
270575GUS2 35KV
Solar/Wind Harmer
4.522
270499AE1-146 GEN
Solar/Wind Harmer
0.021
971549AH1-272 GEN
Solar/Wind Harmer
11.979
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.588
270007AE1-245 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.388
971771AH1-392 GEN
Solar/Wind Harmer
4.384
965041AG1-368 GEN
Solar/Wind Harmer
4.372
247521TR3_G114
Solar/Wind Harmer
0.157
965051AG1-369 GEN
Solar/Wind Harmer
2.168
270526AF1-158 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.976
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.581
960681AF2-359 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.317
971567AH1-282 GEN
Solar/Wind Harmer
3.005
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
270071AF1-092 GEN
Solar/Wind Harmer
7.265
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
274800UNIV PARK;3U
Adder
3.125
274801UNIV PARK;4U
Adder
3.125
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.514
274776LINCOLN ;7U
Adder
4.514
274777LINCOLN ;8U
Adder
4.514
971611AH1-305 GEN
Solar/Wind Harmer
2.221
972228AH1-698 GEN2
Adder
1.977
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.866
274687WILL CNTY;4U
Adder
14.866
274675JOLIET 29;7U
Adder
16.29
274675JOLIET 29;7U
Adder
15.708
274728ELWOOD EC;5P
Adder
8.713
274731ELWOOD EC;2P
Adder
8.712
274733ELWOOD EC;3P
Adder
8.712
274735ELWOOD EC;4P
Adder
8.712
970833AG2-524 GEN
Solar/Wind Harmer
4.048
970833AG2-524 GEN
Solar/Wind Harmer
2.699
274744AC1-111 GEN8
Adder
2.931
274746AC1-111 G10
Adder
2.931
970073AG2-061 GEN
Solar/Wind Harmer
1.208
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
5.374
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.396
276861AD2-134 GEN
Solar/Wind Harmer
0.064
276863AD2-134 GEN
Solar/Wind Harmer
0.064
971171AH1-044 GEN
Solar/Wind Harmer
7.132
274823ROCKFORD ;21
Adder
9.94
926823AC1-168 GEN
Solar/Wind Harmer
0.603
970169AG2-114 GEN
Solar/Wind Harmer
3.545
274856ECOGROVE ;U1
Solar/Wind Harmer
0.083
24729505KEY G4
Adder
3.292
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
2.087
276741O09 GEN1
Solar/Wind Harmer
0.123
274877BISHOP HL;1U
Solar/Wind Harmer
0.116
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.643
963841AG1-237 GEN
Solar/Wind Harmer
1.491
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.921
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.549
970289AG2-191 GEN
Solar/Wind Harmer
0.635
964611AG1-324 GEN
Solar/Wind Harmer
1.3
276668AB2-070 GEN1
Solar/Wind Harmer
0.13
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.13
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
1.251
247536S-71 GEN
Solar/Wind Harmer
0.131
270543AE2-219 C
Solar/Wind Harmer
2.237
944221AF1-090 GEN
Solar/Wind Harmer
1.843
971029AG2-637 GEN
Solar/Wind Harmer
4.677
241886AC2-103 GEN2
Solar/Wind Helper
6.847
241985AE1-237 GEN
Solar/Wind Helper
0.134
241982AE2-343 S C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
20334926Z1-069 C
Solar/Wind Helper
0.646
24189902OREGON_CT2
50/50
4.122
23856402BAYSG1
50/50
1.575
23888702TROY G3
50/50
1.525
972253AH1-711 GEN
50/50
46.615
23920202STRYCT
50/50
1.928
241858AF1-205_GEN
Solar/Wind Harmer
3.781
23906502RICHG2&3
Adder
1.343
960841AF2-375 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
0.187
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.25
957891AF2-083 GEN
Solar/Wind Harmer
7.68
965421AG1-410 GEN
Solar/Wind Harmer
13.812
24639705ELKHART HY
Adder
0.098
965011AG1-365 GEN
Solar/Wind Harmer
4.252
270317AD1-130_GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.303
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.532
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.781
274812UNIV PK N;8U
Adder
2.722
274802UNIV PARK;5U
Adder
3.135
274773LINCOLN ;4U
Adder
4.514
274774LINCOLN ;5U
Adder
4.514
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.29
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.713
274674JOLIET 9 ;6U
Adder
8.16
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.594
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.362
274828WAUKEGAN ;BP
Adder
5.749
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.702
276882AE2-255 GEN
Solar/Wind Harmer
0.421
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.886
270024AE2-089 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
10.699
959081AF2-199 GEN
Solar/Wind Harmer
3.566
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.012
970569AG2-363 GEN
Solar/Wind Harmer
10.659
970819AG2-516 GEN
Solar/Wind Harmer
4.255
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276708O09 GEN2
Solar/Wind Harmer
0.123
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.858
965651AG1-433 GEN
Solar/Wind Harmer
1.011
958861AF2-177 GEN
Solar/Wind Harmer
1.481
963741AG1-226 GEN
Solar/Wind Harmer
7.998
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
3.712
270032AE2-172
Solar/Wind Harmer
2.209
276621W2-048 GEN
Solar/Wind Harmer
0.164
276903AD2-071 C
Solar/Wind Harmer
3.645
970825AG2-519 GEN
Solar/Wind Harmer
1.151
270005AE1-210 C O1
Solar/Wind Harmer
0.699
965911AG1-460 GEN
Solar/Wind Harmer
0.643
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.285
24728605AND G2
Adder
1.661
241885AC2-103 GEN1
Solar/Wind Helper
6.847
241807AE2-176_GEN
Solar/Wind Helper
1.645
203947AF1-006 C
Solar/Wind Helper
0.391
961971AG1-040 GEN
Solar/Wind Helper
0.342
203830AF1-094 GEN
Solar/Wind Helper
0.331
203979AG1-198 GEN
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
23929302BS-PKR
50/50
2.775
958321AF2-126 GEN
Solar/Wind Harmer
1.137
23906402RICHG1
Adder
1.346
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.167
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
270505AE1-170 C O1
Solar/Wind Harmer
4.855
945111AF1-176 GEN
Solar/Wind Harmer
3.748
270588AE1-091_GEN
Solar/Wind Harmer
3.596
24695305TIMB G C
Solar/Wind Harmer
0.378
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.417
971347AH1-153 GEN
Solar/Wind Harmer
2.049
270043AE2-236 GEN
Solar/Wind Harmer
2.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
9.665
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274811UNIV PK N;7U
Adder
2.722
274803UNIV PARK;6U
Adder
3.135
274826FISK ;BP
Adder
5.877
972038AH1-567 GEN2
Adder
0.196
274887GEN-1.85
Solar/Wind Harmer
0.097
276843GEN-1.7
Solar/Wind Harmer
0.121
276806AD2-047 C O1
Solar/Wind Harmer
2.116
274772LINCOLN ;3U
Adder
4.514
972259AH1-714 GEN
Adder
10.137
274676JOLIET 29;8U
Adder
15.708
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
8.712
274730ELWOOD EC;6P
Adder
8.713
274734ELWOOD EC;8P
Adder
8.713
274736ELWOOD EC;9P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.078
943121AE2-341 GEN
Solar/Wind Harmer
6.131
943591AF1-030 GEN
Solar/Wind Harmer
4.077
274862TOP CROP ;2U
Solar/Wind Harmer
0.494
274682WAUKEGAN ;7U
Adder
9.362
276868AE1-113 GEN
Solar/Wind Harmer
0.722
274879MINONK ;1U
Solar/Wind Harmer
0.151
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.598
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
944531AF1-118 GEN
Solar/Wind Harmer
16.015
959091AF2-200 GEN
Solar/Wind Harmer
7.132
970571AG2-364 GEN
Solar/Wind Harmer
7.106
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
4.638
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.116
965091AG1-374 GEN
Solar/Wind Harmer
10.297
959611AF2-252 GEN
Solar/Wind Harmer
1.144
965931AG1-462 GEN
Solar/Wind Harmer
8.718
971087AG2-675 GEN
Solar/Wind Harmer
1.823
247642Z2-115 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.032
970289AG2-191 GEN
Solar/Wind Harmer
0.367
971993AH1-541 GEN
Solar/Wind Harmer
1.533
946031AF1-268 GEN
Solar/Wind Harmer
3.094
970825AG2-519 GEN
Solar/Wind Harmer
2.443
270004AE1-209 GEN
Solar/Wind Harmer
0.699
957381AF2-032 GEN
Solar/Wind Harmer
0.73
942481AE2-261 GEN
Solar/Wind Harmer
9.607
970193AG2-126 GEN
Solar/Wind Harmer
4.752
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
3.474
24728505AND G1
Adder
1.661
962511AG1-100 GEN
Solar/Wind Helper
0.35
24190002OREGON_ST1
50/50
5.546
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.525
970621AG2-405 GEN
Solar/Wind Harmer
0.945
944231AF1-091 GEN
Solar/Wind Harmer
11.69
970623AG2-406 GEN
Solar/Wind Harmer
0.886
961051AF2-396 GEN
Solar/Wind Harmer
9.383
961051AF2-396 GEN
Solar/Wind Harmer
6.256
246937BC-WTG2
Solar/Wind Harmer
0.187
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.296
270246TR4_N_V150
Solar/Wind Harmer
0.028
270247TR4_N_V136
Solar/Wind Harmer
0.028
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.151
965791AG1-447 GEN
Solar/Wind Harmer
3.777
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.728
274808UNIV PK N;4U
Adder
2.71
274888KELLY CRK;1U
Solar/Wind Harmer
0.218
276776AD2-060 GEN
Solar/Wind Harmer
0.398
958011AF2-095 GEN
Solar/Wind Harmer
5.377
970941AG2-585 GEN
Solar/Wind Harmer
2.054
274770LINCOLN ;1U
Adder
4.514
274771LINCOLN ;2U
Adder
4.514
276897AD1-100 C
Solar/Wind Harmer
9.25
276893AG1-478 C
Solar/Wind Harmer
0.247
274674JOLIET 9 ;6U
Adder
8.16
958481AF2-142 GEN
Solar/Wind Harmer
5.484
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
1.462
274696ROCKY RD ;4P
Adder
5.935
274695ROCKY RD ;2P
Adder
5.798
274693ROCKY RD ;1P
Adder
5.741
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.968
274683WAUKEGAN ;8U
Adder
9.245
958491AF2-143 GEN
Solar/Wind Harmer
5.438
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
10.839
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
7.132
971343AH1-151 GEN
Solar/Wind Harmer
7.132
972235AH1-702 GEN1
Adder
1.284
972236AH1-702 GEN2
Adder
1.116
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.397
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.564
942111AE2-223 GEN
Solar/Wind Harmer
1.128
944541AF1-119 GEN
Solar/Wind Harmer
0.23
960971AF2-388 GEN
Solar/Wind Harmer
2.023
960611AF2-352 GEN
Solar/Wind Harmer
1.144
970241AG2-163 GEN
Solar/Wind Harmer
1.971
270031AE2-169
Solar/Wind Harmer
1.849
270599AE1-208 GEN
Solar/Wind Harmer
3.081
270201AC2-176 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.434
970291AG2-192 GEN
Solar/Wind Harmer
0.2
964611AG1-324 GEN
Solar/Wind Harmer
0.25
247621Y3-024
Adder
0.115
971613AH1-306 GEN
Solar/Wind Harmer
1.591
276615X2-022 GEN
Solar/Wind Harmer
0.034
276838X2-022 GEN2
Solar/Wind Harmer
0.185
25326509SID D
Adder
0.616
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
1.397
276916AD2-100_GEN
Solar/Wind Harmer
6.713
276911AD2-131_GEN
Solar/Wind Harmer
0.442
970883AG2-550 GEN
Solar/Wind Harmer
3.196
970885AG2-551 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
3.366
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
203835AF1-098 GEN
Solar/Wind Helper
1.351
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.135
254304AE2-114 C
Solar/Wind Helper
0.114
254305AE2-115 C
Solar/Wind Helper
0.114
962101AG1-054 GEN
Solar/Wind Helper
0.331
203804AE2-113_GEN
Solar/Wind Helper
0.87
940863AE2-074 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Helper
0.105
990142J1224
External Queue
14.793254852294922
990527J1329
External Queue
2.0237011909484863
991177J1571 G
External Queue
15.794994354248047
991182J1586 G
External Queue
28.12165069580078
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.401
TVALTFEXP_TVA->PJM
CLTF
2.775
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.534
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.945
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.65 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:1922.03
MW Contribution:
4.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.456
970521AG2-332 GEN
50/50
11.157
24639705ELKHART HY
50/50
0.154
270143AC1-141 CT2_
50/50
2.081
24344105CKG2
50/50
6.284
24307105BERRINSP G
50/50
0.018
965011AG1-365 GEN
Solar/Wind Harmer
13.973
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.92
958861AF2-177 GEN
Solar/Wind Harmer
2.759
945111AF1-176 GEN
Solar/Wind Harmer
10.951
957891AF2-083 GEN
Solar/Wind Harmer
10.053
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.079
970373AG2-245 GEN
Solar/Wind Harmer
11.559
274751CRETE EC ;1U
Adder
6.49
274754CRETE EC ;4U
Adder
6.49
274723RIVER EC ;12
Adder
14.067
274812UNIV PK N;8U
Adder
3.9
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.547
274774LINCOLN ;5U
Adder
6.547
274802UNIV PARK;5U
Adder
4.495
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.946
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
23.324
274674JOLIET 9 ;6U
Adder
11.68
274732ELWOOD EC;7P
Adder
12.465
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.552
270594AE1-207 GEN
Solar/Wind Harmer
5.867
270032AE2-172
Solar/Wind Harmer
3.492
270005AE1-210 C O1
Solar/Wind Harmer
1.133
274745AC1-111 GEN9
Adder
4.189
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.845
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.842
274682WAUKEGAN ;7U
Adder
13.321
274828WAUKEGAN ;BP
Adder
8.177
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.874
939401AE1-172 GEN
Solar/Wind Harmer
3.83
274872LEEDK;1U
Solar/Wind Harmer
0
24729505KEY G4
50/50
6.995
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.016
270144AC1-141 ST1_
50/50
1.838
24344005CKG1
50/50
5.28
959331AF2-224 GEN
Solar/Wind Harmer
9.781
963791AG1-232 GEN
Solar/Wind Harmer
12.238
970031AG2-029 GEN
Solar/Wind Harmer
4.668
965041AG1-368 GEN
Solar/Wind Harmer
8.594
270071AF1-092 GEN
Solar/Wind Harmer
14.854
247521TR3_G114
Solar/Wind Harmer
0.267
965051AG1-369 GEN
Solar/Wind Harmer
3.677
971771AH1-392 GEN
Solar/Wind Harmer
6.058
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.946
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.189
274775LINCOLN ;6U
Adder
6.547
274776LINCOLN ;7U
Adder
6.547
274777LINCOLN ;8U
Adder
6.547
972037AH1-567 GEN1
Adder
0.141
274827FISK ;RP
Adder
5.975
274800UNIV PARK;3U
Adder
4.482
274801UNIV PARK;4U
Adder
4.482
960591AF2-350 GEN
Solar/Wind Harmer
5.357
972228AH1-698 GEN2
Adder
2.836
972227AH1-698 GEN1
Adder
1.997
274687WILL CNTY;4U
Adder
21.288
274687WILL CNTY;4U
Adder
21.288
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
23.324
274675JOLIET 29;7U
Adder
22.491
274728ELWOOD EC;5P
Adder
12.465
274731ELWOOD EC;2P
Adder
12.464
274733ELWOOD EC;3P
Adder
12.464
274735ELWOOD EC;4P
Adder
12.464
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.003
970833AG2-524 GEN
Solar/Wind Harmer
5.794
970833AG2-524 GEN
Solar/Wind Harmer
3.862
971611AH1-305 GEN
Solar/Wind Harmer
3.121
274744AC1-111 GEN8
Adder
4.189
274746AC1-111 G10
Adder
4.189
970073AG2-061 GEN
Solar/Wind Harmer
1.711
247536S-71 GEN
Solar/Wind Harmer
0.205
971411AH1-196 GEN
Solar/Wind Harmer
7.602
971675AH1-338 GEN
Solar/Wind Harmer
1.975
276861AD2-134 GEN
Solar/Wind Harmer
0.09
276863AD2-134 GEN
Solar/Wind Harmer
0.09
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
10.069
276882AE2-255 GEN
Solar/Wind Harmer
0.596
971997AH1-543 GEN
Solar/Wind Harmer
2.669
957471AF2-041 GEN
Solar/Wind Harmer
15.103
959081AF2-199 GEN
Solar/Wind Harmer
5.034
971067AG2-660 GEN
Solar/Wind Harmer
1.678
274822ROCKFORD ;11
Adder
14.119
276903AD2-071 C
Solar/Wind Harmer
5.594
970819AG2-516 GEN
Solar/Wind Harmer
5.99
970569AG2-363 GEN
Solar/Wind Harmer
14.964
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.581
274766LEE CO EC;7U
Adder
6.504
276708O09 GEN2
Solar/Wind Harmer
0.172
276646AC1-214 GEN2
Solar/Wind Harmer
0.191
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.73
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.397
963741AG1-226 GEN
Solar/Wind Harmer
10.829
276621W2-048 GEN
Solar/Wind Harmer
0.22
965911AG1-460 GEN
Solar/Wind Harmer
0.85
24728605AND G2
Adder
2.182
970773AG2-487 GEN
Solar/Wind Harmer
0.657
246936BC-WTG1
Solar/Wind Helper
10.844
270317AD1-130_GEN
Solar/Wind Helper
4.072
270485AE1-090_GEN
Solar/Wind Helper
0.32
270391AF1-285 GEN3
Solar/Wind Helper
0.582
270578AF1-285 GEN2
Solar/Wind Helper
0.582
274823ROCKFORD ;21
Adder
14.017
274856ECOGROVE ;U1
Solar/Wind Harmer
0.116
926823AC1-168 GEN
Solar/Wind Harmer
0.847
970169AG2-114 GEN
Solar/Wind Harmer
4.974
971681AH1-341 GEN
Solar/Wind Harmer
7.978
971549AH1-272 GEN
Solar/Wind Harmer
10.208
972267AH1-718 GEN
Adder
2.917
276741O09 GEN1
Solar/Wind Harmer
0.172
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.162
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
5.047
946321AF1-296 GEN
Solar/Wind Harmer
2.661
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.041
270543AE2-219 C
Solar/Wind Harmer
3.242
276668AB2-070 GEN1
Solar/Wind Harmer
0.176
276848AB2-070 GEN3
Solar/Wind Harmer
0.175
276849AB2-070 GEN2
Solar/Wind Harmer
0.176
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
6.154
944221AF1-090 GEN
Solar/Wind Harmer
2.4
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.567
270223U2-072_GEN1
Solar/Wind Helper
0.859
270224U2-072_GEN2
Solar/Wind Helper
0.859
270227U2-072_GEN3
Solar/Wind Helper
0.859
270228U2-072_GEN4
Solar/Wind Helper
0.859
270231U2-072_GEN5
Solar/Wind Helper
0.859
966831AG1-554 GEN
Solar/Wind Helper
0.861
270499AE1-146 GEN
Solar/Wind Helper
1.911
945641AF1-229 GEN
Solar/Wind Helper
0.907
970583AG2-370 GEN
50/50
2.865
270142AC1-141 CT1_
50/50
2.081
24642205MAYFLWER
50/50
0.032
944961AF1-161 GEN
50/50
2.458
962601AG1-109 GEN
50/50
2.458
965021AG1-366 GEN
Solar/Wind Harmer
4.658
270043AE2-236 GEN
Solar/Wind Harmer
5.337
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
32.656
24695305TIMB G C
Solar/Wind Harmer
0.545
945111AF1-176 GEN
Solar/Wind Harmer
4.975
971347AH1-153 GEN
Solar/Wind Harmer
3.002
270505AE1-170 C O1
Solar/Wind Harmer
6.29
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.571
274752CRETE EC ;2U
Adder
6.49
274753CRETE EC ;3U
Adder
6.49
274724RIVER EC ;11
Adder
13.897
274814UNIV PK N;0U
Adder
3.935
274807UNIV PK N;3U
Adder
3.926
274811UNIV PK N;7U
Adder
3.9
274772LINCOLN ;3U
Adder
6.547
274803UNIV PARK;6U
Adder
4.495
274826FISK ;BP
Adder
8.431
972038AH1-567 GEN2
Adder
0.281
274887GEN-1.85
Solar/Wind Harmer
0.139
276843GEN-1.7
Solar/Wind Harmer
0.173
276806AD2-047 C O1
Solar/Wind Harmer
3.036
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.564
970707AG2-453 GEN
Solar/Wind Harmer
17.395
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.491
274729ELWOOD EC;1P
Adder
12.464
274730ELWOOD EC;6P
Adder
12.465
274734ELWOOD EC;8P
Adder
12.465
274736ELWOOD EC;9P
Adder
12.465
970289AG2-191 GEN
Solar/Wind Harmer
0.58
946031AF1-268 GEN
Solar/Wind Harmer
4.982
943121AE2-341 GEN
Solar/Wind Harmer
8.771
943591AF1-030 GEN
Solar/Wind Harmer
5.832
270004AE1-209 GEN
Solar/Wind Harmer
1.133
274862TOP CROP ;2U
Solar/Wind Harmer
0.701
970825AG2-519 GEN
Solar/Wind Harmer
3.908
274682WAUKEGAN ;7U
Adder
13.321
276868AE1-113 GEN
Solar/Wind Harmer
1.021
274879MINONK ;1U
Solar/Wind Harmer
0.213
946671AF1-331 GEN
Solar/Wind Harmer
0.54
274855GSG-6 ;RU
Solar/Wind Harmer
0.185
274850MENDOTA H;RU
Solar/Wind Harmer
0.059
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
5.046
959091AF2-200 GEN
Solar/Wind Harmer
10.069
970571AG2-364 GEN
Solar/Wind Harmer
9.976
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.581
274767LEE CO EC;8U
Adder
6.504
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.162
965091AG1-374 GEN
Solar/Wind Harmer
14.177
959611AF2-252 GEN
Solar/Wind Harmer
1.575
965931AG1-462 GEN
Solar/Wind Harmer
12.05
971087AG2-675 GEN
Solar/Wind Harmer
2.52
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.067
957381AF2-032 GEN
Solar/Wind Harmer
0.966
942481AE2-261 GEN
Solar/Wind Harmer
12.705
970193AG2-126 GEN
Solar/Wind Harmer
6.182
24728705AND G3
Adder
4.563
24728505AND G1
Adder
2.182
246938BC-WTG3
Solar/Wind Helper
11.03
942871AE2-306 GEN
Solar/Wind Helper
0.436
270284AF1-227 GEN1
Solar/Wind Helper
1.841
270287AF1-227 GEN3
Solar/Wind Helper
0.675
276820AF1-078_GEN
Solar/Wind Helper
0.321
270541AE2-072 C
Solar/Wind Helper
0.902
270286AF1-227 GEN2
Solar/Wind Helper
0.675
960841AF2-375 GEN
Solar/Wind Helper
1.143
24729405KEY G3
50/50
0.382
24729305KEY G2
50/50
0.375
24729205KEY G1
50/50
0.374
247620Y3-023
50/50
0.478
960851AF2-376 GEN
50/50
2.145
24643105BUCHANAN
50/50
0.011
270102X2-052 ST
50/50
1.316
270100X2-052 CT1
50/50
1.216
270101X2-052 CT2
50/50
1.216
270246TR4_N_V150
Solar/Wind Harmer
0.047
270247TR4_N_V136
Solar/Wind Harmer
0.047
942221AE2-234 GEN
Solar/Wind Harmer
2.915
944231AF1-091 GEN
Solar/Wind Harmer
16.486
944541AF1-119 GEN
Solar/Wind Harmer
0.437
960971AF2-388 GEN
Solar/Wind Harmer
3.84
970349AG2-230 GEN
Solar/Wind Harmer
9.006
961051AF2-396 GEN
Solar/Wind Harmer
11.975
961051AF2-396 GEN
Solar/Wind Harmer
7.983
270031AE2-169
Solar/Wind Harmer
3.187
270599AE1-208 GEN
Solar/Wind Harmer
5.311
965681AG1-436 GEN
Solar/Wind Harmer
7.151
965791AG1-447 GEN
Solar/Wind Harmer
5.244
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.421
247621Y3-024
Adder
0.188
274805UNIV PK N;1U
Adder
3.909
274808UNIV PK N;4U
Adder
3.883
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.547
274771LINCOLN ;2U
Adder
6.547
274888KELLY CRK;1U
Solar/Wind Harmer
0.312
276776AD2-060 GEN
Solar/Wind Harmer
0.571
958011AF2-095 GEN
Solar/Wind Harmer
7.714
970941AG2-585 GEN
Solar/Wind Harmer
2.946
276897AD1-100 C
Solar/Wind Harmer
13.263
274674JOLIET 9 ;6U
Adder
11.68
276893AG1-478 C
Solar/Wind Harmer
0.353
970291AG2-192 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.317
971613AH1-306 GEN
Solar/Wind Harmer
2.514
958481AF2-142 GEN
Solar/Wind Harmer
7.796
274696ROCKY RD ;4P
Adder
8.451
274695ROCKY RD ;2P
Adder
8.256
274693ROCKY RD ;1P
Adder
8.175
274697ROCKY RD ;3P
Adder
2.243
274683WAUKEGAN ;8U
Adder
15.599
274683WAUKEGAN ;8U
Adder
13.149
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
15.403
958491AF2-143 GEN
Solar/Wind Harmer
7.702
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
10.069
971343AH1-151 GEN
Solar/Wind Harmer
10.069
972235AH1-702 GEN1
Adder
1.809
972236AH1-702 GEN2
Adder
1.573
938861AE1-114 GEN
Solar/Wind Harmer
2.807
274764LEE CO EC;5U
Adder
6.597
274765LEE CO EC;6U
Adder
6.597
274762LEE CO EC;3U
Adder
6.581
274763LEE CO EC;4U
Adder
6.519
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.787
276645AC1-214 GEN1
Solar/Wind Harmer
0.191
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.55
942111AE2-223 GEN
Solar/Wind Harmer
1.562
960611AF2-352 GEN
Solar/Wind Harmer
1.575
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.631
970885AG2-551 GEN
Solar/Wind Harmer
1.544
970241AG2-163 GEN
Solar/Wind Harmer
2.669
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.046
276838X2-022 GEN2
Solar/Wind Harmer
0.248
276916AD2-100_GEN
Solar/Wind Harmer
8.848
276911AD2-131_GEN
Solar/Wind Harmer
0.583
945391AF1-204 GEN
Solar/Wind Harmer
4.379
970623AG2-406 GEN
Solar/Wind Harmer
0.684
971587AH1-292 GEN
Solar/Wind Harmer
2.578
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.844
270462AD2-086
Solar/Wind Helper
3.683
247522W1-056 GEN
Solar/Wind Helper
1.146
253378AE2-206_GEN
Solar/Wind Helper
0.688
270349AD2-093_GEN
Solar/Wind Helper
0.824
270471AD2-092_GEN
Solar/Wind Helper
0.824
241960AC2-195 GEN
Solar/Wind Helper
0.664
990497J1323
External Queue
1.5952997207641602
990792J1392
External Queue
5.487830638885498
LAGNLTFEXP_LAGN->PJM
CLTF
6.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.165
TVALTFEXP_TVA->PJM
CLTF
2.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.755
MECLTFEXP_MEC->PJM
CLTF
10.148
SIGELTFEXP_SIGE->PJM
CLTF
0.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.75
NYPJM->LTFIMP_NY
CLTF
1.125
LGEELTFEXP_LGEE->PJM
CLTF
1.97
WECLTFEXP_WEC->PJM
CLTF
2.738
AG2-052LTFEXP_AG2-052->PJM
LTF
0.177
AH1-155LTFEXP_AH1-155->PJM
LTF
0.266

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4053.82
MW Contribution:
9.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
38.42
970149AG2-104 GEN
Solar/Wind Harmer
23.725
970155AG2-107 GEN
Solar/Wind Harmer
16.753
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
3.193
270331AC1-082 GEN3
Solar/Wind Harmer
0.502
270286AF1-227 GEN2
Solar/Wind Harmer
2.151
270520AE2-214 GEN
Solar/Wind Harmer
6.107
270273AD2-016 GEN
Solar/Wind Harmer
2.677
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
1.043
253316AC1-085 GEN3
Solar/Wind Harmer
8.322
946171AF1-282 GEN
Solar/Wind Harmer
9.94
253398AE2-221_GEN2
Solar/Wind Harmer
4.505
252516AE2-318_GEN
Solar/Wind Harmer
9.922
252510AF1-249 C
Solar/Wind Harmer
0.413
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
270391AF1-285 GEN3
Solar/Wind Harmer
1.195
270578AF1-285 GEN2
Solar/Wind Harmer
1.195
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
270222AC2-111 GEN
Solar/Wind Harmer
4.385
944031AF1-071 GEN
Solar/Wind Harmer
0.987
965651AG1-433 GEN
Solar/Wind Harmer
5.345
958861AF2-177 GEN
Solar/Wind Harmer
10.687
942081AE2-220 GEN
Solar/Wind Harmer
6.249
270209AC1-174_GEN
Solar/Wind Harmer
3.977
270437AC2-090 C
Solar/Wind Harmer
5.454
270239V3-007_GEN1
Solar/Wind Harmer
1.681
945371AF1-202 GEN
Solar/Wind Harmer
6.817
945681AF1-233 GEN
Solar/Wind Harmer
18.397
270317AD1-130_GEN
Solar/Wind Harmer
3.123
270485AE1-090_GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
5.332
270594AE1-207 GEN
Solar/Wind Harmer
13.238
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.045
276903AD2-071 C
Solar/Wind Harmer
9.73
270024AE2-089 GEN
Solar/Wind Harmer
4.552
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
9.84
24791305MDL-5G
Solar/Wind Harmer
2.326
965011AG1-365 GEN
Solar/Wind Harmer
9.647
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
7.578
971917AH1-482 GEN
Solar/Wind Harmer
8.743
24728605AND G2
Adder
3.696
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274745AC1-111 GEN9
Adder
5.296
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
3.829
270471AD2-092_GEN
Solar/Wind Harmer
3.829
927014AC1-188 GEN
Solar/Wind Harmer
1.622
946101AF1-275 GEN
Solar/Wind Harmer
1.527
253383AE2-342_GEN
Solar/Wind Harmer
0.892
270269AC2-059
Solar/Wind Harmer
9.392
942861AE2-305 GEN
Solar/Wind Harmer
7.837
253415AE1-040 GEN
Solar/Wind Harmer
1.128
962581AG1-107 GEN
Solar/Wind Harmer
5.045
961491AF2-440 GEN
Solar/Wind Harmer
2.097
971073AG2-665 GEN
Solar/Wind Harmer
8.007
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.254
25183208HLCRTG
Solar/Wind Harmer
6.007
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
253349AC2-067 GEN
Solar/Wind Harmer
2.007
253400AC2-068 GEN
Solar/Wind Harmer
0.807
270054AF2-122 C O1
Solar/Wind Harmer
3.197
944541AF1-119 GEN
Solar/Wind Harmer
4.095
960971AF2-388 GEN
Solar/Wind Harmer
10.691
253378AE2-206_GEN
Solar/Wind Harmer
3.513
926881AC1-175 GEN
Solar/Wind Harmer
5.454
270383AD1-128 GEN
Solar/Wind Harmer
5.961
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
9.759
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
6.784
970291AG2-192 GEN
Solar/Wind Harmer
1.267
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
7.939
270599AE1-208 GEN
Solar/Wind Harmer
7.939
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
5.005
24725505WLD G2 C
Solar/Wind Harmer
3.868
24699105WLD G1 C
Solar/Wind Harmer
3.822
942221AE2-234 GEN
Solar/Wind Harmer
3.403
970349AG2-230 GEN
Solar/Wind Harmer
14.508
945421AF1-207 GEN
Solar/Wind Harmer
13.563
957841AF2-078 GEN
Solar/Wind Harmer
5.839
270180AB1-006 GEN1
Solar/Wind Harmer
6.938
24697605MDL-3G C
Solar/Wind Harmer
3.556
24755605MDL-5G
Solar/Wind Harmer
2.326
24697905MDL-4G C
Solar/Wind Harmer
2.214
270181AB1-006 GEN2
Solar/Wind Harmer
0.69
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
971985AH1-537 GEN
Solar/Wind Harmer
18.214
270263AC1-001 GEN
Solar/Wind Harmer
1.051
943861AF1-054 GEN
Solar/Wind Harmer
3.868
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
3.034
270432AC2-029 GEN
Solar/Wind Harmer
7.024
241955AC1-078 GEN
Solar/Wind Harmer
7.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.984
241974AD2-163_GEN2
Solar/Wind Harmer
1.984
253338AC1-165 GEN
Solar/Wind Harmer
1.081
253343AC1-166 GEN
Solar/Wind Harmer
1.081
945631AF1-228 GEN
Solar/Wind Harmer
4.679
253406AD2-031_GEN
Solar/Wind Harmer
1.273
241972AD1-140 GEN
Solar/Wind Harmer
4.45
253433AC1-085 GEN1
Solar/Wind Harmer
5.282
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
270459AD2-067 GEN
Solar/Wind Harmer
8.295
961821AG1-024 GEN
Solar/Wind Harmer
8.422
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270223U2-072_GEN1
Solar/Wind Harmer
1.952
270224U2-072_GEN2
Solar/Wind Harmer
1.952
270227U2-072_GEN3
Solar/Wind Harmer
1.952
270228U2-072_GEN4
Solar/Wind Harmer
1.952
270231U2-072_GEN5
Solar/Wind Harmer
1.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
5.023
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
958711AF2-162 GEN
Solar/Wind Harmer
0.989
945581AF1-223 GEN
Solar/Wind Harmer
4.431
971029AG2-637 GEN
Solar/Wind Harmer
14.654
270071AF1-092 GEN
Solar/Wind Harmer
14.639
270543AE2-219 C
Solar/Wind Harmer
9.759
270302AB2-170 GEN
Solar/Wind Harmer
8.168
247536S-71 GEN
Solar/Wind Harmer
3.945
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.799
970289AG2-191 GEN
Solar/Wind Harmer
1.852
964611AG1-324 GEN
Solar/Wind Harmer
3.798
270356AE2-297 GEN
Solar/Wind Harmer
4.491
961761AG1-017 GEN
Solar/Wind Harmer
0.417
957241AF2-018 GEN
Solar/Wind Harmer
4.296
270053AF1-130 C
Solar/Wind Harmer
17.164
963791AG1-232 GEN
Solar/Wind Harmer
13.051
946581AF1-322 GEN
Solar/Wind Harmer
9.871
24691005MDL-2G C
Solar/Wind Harmer
3.567
959331AF2-224 GEN
Solar/Wind Harmer
9.647
959141AF2-205 GEN
Solar/Wind Harmer
5.832
958391AF2-133 GEN
Solar/Wind Harmer
8.746
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
958381AF2-132 GEN
Solar/Wind Harmer
6.61
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
38.42
970153AG2-106 GEN
Solar/Wind Harmer
16.753
24686405CER G5
Adder
8.833
270330AC1-082 GEN2
Solar/Wind Harmer
0.501
270329AC1-082 GEN1
Solar/Wind Harmer
0.501
274674JOLIET 9 ;6U
Adder
14.625
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
971191AH1-055 GEN
Solar/Wind Harmer
19.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.814
270287AF1-227 GEN3
Solar/Wind Harmer
2.151
957541AF2-048 GEN
Solar/Wind Harmer
1.622
270367AC2-061_GEN
Solar/Wind Harmer
3.183
970879AG2-548 GEN
Solar/Wind Harmer
8.007
942051AE2-217 GEN
Solar/Wind Harmer
18.009
253325AC1-069 GEN
Solar/Wind Harmer
1.043
270186AC1-089 GEN
Solar/Wind Harmer
6.09
270518AE2-148 GEN
Solar/Wind Harmer
12.029
253317AC1-085 GEN4
Solar/Wind Harmer
8.322
946181AF1-283 GEN
Solar/Wind Harmer
12.922
252507AC2-088 GEN
Solar/Wind Harmer
1.779
253394AE2-221_GEN
Solar/Wind Harmer
4.505
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
12.632
253303V4-073 C
Solar/Wind Harmer
0.115
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
252524AE2-267 GEN
Solar/Wind Harmer
1.558
25196608WSDLE5
Adder
8.482
942871AE2-306 GEN
Solar/Wind Harmer
0.896
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
960071AF2-298 GEN
Solar/Wind Harmer
1.495
960801AF2-371 GEN
Solar/Wind Harmer
2.503
964871AG1-351 GEN
Solar/Wind Harmer
1.728
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
34.283
276820AF1-078_GEN
Solar/Wind Harmer
1.561
24379505HDWTR1G C
Solar/Wind Harmer
7.727
270240V3-007_GEN2
Solar/Wind Harmer
6.045
972167AH1-666 GEN
Solar/Wind Harmer
7.81
270004AE1-209 GEN
Solar/Wind Harmer
5.332
946031AF1-268 GEN
Solar/Wind Harmer
8.091
965461AG1-414 GEN
Solar/Wind Harmer
2.21
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.062
970825AG2-519 GEN
Solar/Wind Harmer
5.491
958171AF2-111 GEN
Solar/Wind Harmer
24.35
962031AG1-047 GEN
Solar/Wind Harmer
2.944
957741AF2-068 GEN
Solar/Wind Harmer
14.606
270043AE2-236 GEN
Solar/Wind Harmer
5.338
971347AH1-153 GEN
Solar/Wind Harmer
4.836
24690905MDL-1G C
Solar/Wind Harmer
7.745
970781AG2-491 GEN
Solar/Wind Harmer
9.647
965021AG1-366 GEN
Solar/Wind Harmer
2.244
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
274803UNIV PARK;6U
Adder
5.55
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
972259AH1-714 GEN
Adder
18.154
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
274682WAUKEGAN ;7U
Adder
3.428
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.34 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4053.72
MW Contribution:
9.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
5.526
24289405MTG1
50/50
6.082
243186AF1-051 GEN
50/50
6.835
962761AG1-125 GEN
Solar/Wind Harmer
38.451
970149AG2-104 GEN
Solar/Wind Harmer
23.744
970155AG2-107 GEN
Solar/Wind Harmer
16.767
972203AH1-686 GEN
Adder
2.53
24723205RIVRG3
Adder
20.295
24686505CER G6
Adder
8.909
960001AF2-291 GEN
Solar/Wind Harmer
3.196
270331AC1-082 GEN3
Solar/Wind Harmer
0.503
270286AF1-227 GEN2
Solar/Wind Harmer
2.153
270520AE2-214 GEN
Solar/Wind Harmer
6.113
270273AD2-016 GEN
Solar/Wind Harmer
2.68
971073AG2-665 GEN
Solar/Wind Harmer
1.165
253333AC1-068 GEN
Solar/Wind Harmer
1.044
253316AC1-085 GEN3
Solar/Wind Harmer
8.329
946171AF1-282 GEN
Solar/Wind Harmer
9.949
253398AE2-221_GEN2
Solar/Wind Harmer
4.509
252516AE2-318_GEN
Solar/Wind Harmer
9.931
252510AF1-249 C
Solar/Wind Harmer
0.413
253370AE2-315 SEC1
Adder
1.985
253371AE2-315 SEC2
Adder
1.878
25194608D.CRK4
Adder
1.629
25326309TAIT D
Adder
1.085
270391AF1-285 GEN3
Solar/Wind Harmer
1.197
270578AF1-285 GEN2
Solar/Wind Harmer
1.197
25196808ZIMRHP
Adder
74.969
970091AG2-072 GEN
Adder
75.547
25196008MFTGT1
Adder
1.368
270222AC2-111 GEN
Solar/Wind Harmer
4.389
944031AF1-071 GEN
Solar/Wind Harmer
0.987
965651AG1-433 GEN
Solar/Wind Harmer
5.35
958861AF2-177 GEN
Solar/Wind Harmer
10.697
945371AF1-202 GEN
Solar/Wind Harmer
6.823
942081AE2-220 GEN
Solar/Wind Harmer
6.255
270209AC1-174_GEN
Solar/Wind Harmer
3.98
270437AC2-090 C
Solar/Wind Harmer
5.459
270239V3-007_GEN1
Solar/Wind Harmer
1.683
945681AF1-233 GEN
Solar/Wind Harmer
18.412
270317AD1-130_GEN
Solar/Wind Harmer
3.126
270485AE1-090_GEN
Solar/Wind Harmer
0.591
270005AE1-210 C O1
Solar/Wind Harmer
5.336
270594AE1-207 GEN
Solar/Wind Harmer
13.25
270032AE2-172
Solar/Wind Harmer
4.538
970825AG2-519 GEN
Solar/Wind Harmer
2.047
276903AD2-071 C
Solar/Wind Harmer
9.739
270024AE2-089 GEN
Solar/Wind Harmer
4.556
944971AF1-162 GEN
Solar/Wind Harmer
6.77
965011AG1-365 GEN
Solar/Wind Harmer
9.657
940581AE2-045 GEN
Solar/Wind Harmer
9.849
971985AH1-537 GEN
Solar/Wind Harmer
18.229
270263AC1-001 GEN
Solar/Wind Harmer
1.052
24318805MLG1
50/50
7.629
24289405MTG1
50/50
6.082
24721905FLATG4
Adder
26.847
962771AG1-126 GEN
Solar/Wind Harmer
38.451
970153AG2-106 GEN
Solar/Wind Harmer
16.767
24686405CER G5
Adder
8.839
270330AC1-082 GEN2
Solar/Wind Harmer
0.501
270329AC1-082 GEN1
Solar/Wind Harmer
0.501
971191AH1-055 GEN
Solar/Wind Harmer
19.637
270284AF1-227 GEN1
Solar/Wind Harmer
5.82
270287AF1-227 GEN3
Solar/Wind Harmer
2.153
957541AF2-048 GEN
Solar/Wind Harmer
1.623
270367AC2-061_GEN
Solar/Wind Harmer
3.185
970879AG2-548 GEN
Solar/Wind Harmer
8.014
942051AE2-217 GEN
Solar/Wind Harmer
18.027
253325AC1-069 GEN
Solar/Wind Harmer
1.044
270186AC1-089 GEN
Solar/Wind Harmer
6.095
270518AE2-148 GEN
Solar/Wind Harmer
12.041
253317AC1-085 GEN4
Solar/Wind Harmer
8.329
946181AF1-283 GEN
Solar/Wind Harmer
12.933
252507AC2-088 GEN
Solar/Wind Harmer
1.781
253394AE2-221_GEN
Solar/Wind Harmer
4.509
252519AF1-045_GEN
Solar/Wind Harmer
3.614
961921AG1-034 GEN
Solar/Wind Harmer
12.646
253303V4-073 C
Solar/Wind Harmer
0.115
253370AE2-315 SEC1
Adder
1.985
253371AE2-315 SEC2
Adder
1.878
25194608D.CRK4
Adder
1.629
252524AE2-267 GEN
Solar/Wind Harmer
1.56
25196608WSDLE5
Adder
8.49
942871AE2-306 GEN
Solar/Wind Harmer
0.897
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
960071AF2-298 GEN
Solar/Wind Harmer
1.496
960801AF2-371 GEN
Solar/Wind Harmer
2.506
964871AG1-351 GEN
Solar/Wind Harmer
1.73
25196008MFTGT1
Adder
1.325
24791305MDL-5G
Solar/Wind Harmer
2.328
971605AH1-302 GEN
Solar/Wind Harmer
8.421
24728605AND G2
Adder
3.699
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.068
274774LINCOLN ;5U
Adder
8.068
274751CRETE EC ;1U
Adder
7.868
274754CRETE EC ;4U
Adder
7.868
274723RIVER EC ;12
Adder
17.106
274812UNIV PK N;8U
Adder
4.777
274802UNIV PARK;5U
Adder
5.555
274732ELWOOD EC;7P
Adder
15.629
274676JOLIET 29;8U
Adder
29.172
274674JOLIET 9 ;6U
Adder
14.638
274745AC1-111 GEN9
Adder
5.301
23751101LEADS_P59
Solar/Wind Helper
2.585
238185AF2-356 C
Solar/Wind Helper
2.375
23583801GRNGAP
Solar/Wind Helper
4.46
316095T157 G97
Solar/Wind Helper
1.193
238120AE2-309 GEN
Solar/Wind Helper
0.459
238126S14_GEN_1
Solar/Wind Helper
0.723
238109AE1-109 GEN2
Solar/Wind Helper
0.095
964861AG1-349 GEN
Solar/Wind Harmer
1.402
971917AH1-482 GEN
Solar/Wind Harmer
1.617
943861AF1-054 GEN
Solar/Wind Harmer
3.872
943851AF1-053 GEN
Solar/Wind Harmer
1.871
270432AC2-029 GEN
Solar/Wind Harmer
7.031
270340AC2-060 GEN
Solar/Wind Harmer
3.037
241955AC1-078 GEN
Solar/Wind Harmer
7.469
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253338AC1-165 GEN
Solar/Wind Harmer
1.082
253343AC1-166 GEN
Solar/Wind Harmer
1.082
945631AF1-228 GEN
Solar/Wind Harmer
4.683
253406AD2-031_GEN
Solar/Wind Harmer
1.274
241972AD1-140 GEN
Solar/Wind Harmer
4.454
253433AC1-085 GEN1
Solar/Wind Harmer
5.287
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
270459AD2-067 GEN
Solar/Wind Harmer
8.304
961821AG1-024 GEN
Solar/Wind Harmer
8.431
253372AE2-315 SEC3
Adder
1.878
253372AE2-315 SEC3
Adder
1.878
25196408WSDLE3
Adder
8.74
25196308WSDLE2
Adder
8.664
25196208WSDLE1
Adder
8.642
25196708WSDLE6
Adder
8.62
25196508WSDLE4
Adder
8.403
25306009OHH W.
Adder
2.853
270223U2-072_GEN1
Solar/Wind Harmer
1.954
270224U2-072_GEN2
Solar/Wind Harmer
1.954
270227U2-072_GEN3
Solar/Wind Harmer
1.954
270228U2-072_GEN4
Solar/Wind Harmer
1.954
270231U2-072_GEN5
Solar/Wind Harmer
1.954
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
5.028
25196108MFTGT2
Adder
1.508
25196108MFTGT2
Adder
1.4
24729505KEY G4
Adder
6.358
958711AF2-162 GEN
Solar/Wind Harmer
0.99
945581AF1-223 GEN
Solar/Wind Harmer
4.435
971029AG2-637 GEN
Solar/Wind Harmer
14.667
270071AF1-092 GEN
Solar/Wind Harmer
14.653
270543AE2-219 C
Solar/Wind Harmer
9.768
270302AB2-170 GEN
Solar/Wind Harmer
8.176
247536S-71 GEN
Solar/Wind Harmer
3.949
972163AH1-664 GEN
Solar/Wind Harmer
9.757
972165AH1-665 GEN
Solar/Wind Harmer
7.806
970289AG2-191 GEN
Solar/Wind Harmer
1.853
964611AG1-324 GEN
Solar/Wind Harmer
3.802
270356AE2-297 GEN
Solar/Wind Harmer
4.495
961761AG1-017 GEN
Solar/Wind Harmer
0.417
957241AF2-018 GEN
Solar/Wind Harmer
4.299
270053AF1-130 C
Solar/Wind Harmer
17.176
963791AG1-232 GEN
Solar/Wind Harmer
13.064
959331AF2-224 GEN
Solar/Wind Harmer
9.657
946581AF1-322 GEN
Solar/Wind Harmer
9.879
24691005MDL-2G C
Solar/Wind Harmer
3.57
959141AF2-205 GEN
Solar/Wind Harmer
5.837
958391AF2-133 GEN
Solar/Wind Harmer
8.754
274775LINCOLN ;6U
Adder
8.068
274776LINCOLN ;7U
Adder
8.068
274777LINCOLN ;8U
Adder
8.068
972228AH1-698 GEN2
Adder
3.529
972227AH1-698 GEN1
Adder
2.485
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.39
274800UNIV PARK;3U
Adder
5.553
274801UNIV PARK;4U
Adder
5.553
274687WILL CNTY;4U
Adder
26.575
274687WILL CNTY;4U
Adder
26.575
274728ELWOOD EC;5P
Adder
15.629
274731ELWOOD EC;2P
Adder
15.629
274733ELWOOD EC;3P
Adder
15.629
274735ELWOOD EC;4P
Adder
15.629
274675JOLIET 29;7U
Adder
29.172
274675JOLIET 29;7U
Adder
28.13
274744AC1-111 GEN8
Adder
5.301
274746AC1-111 G10
Adder
5.301
23750701CROSSCHOOL
Solar/Wind Helper
1.289
238118U2-030_1
Solar/Wind Helper
0.304
23750501ELLIOTTS
Solar/Wind Helper
0.621
944531AF1-118 GEN
Solar/Wind Harmer
34.314
276820AF1-078_GEN
Solar/Wind Harmer
1.562
24379505HDWTR1G C
Solar/Wind Harmer
7.734
270240V3-007_GEN2
Solar/Wind Harmer
6.051
972167AH1-666 GEN
Solar/Wind Harmer
7.816
270004AE1-209 GEN
Solar/Wind Harmer
5.336
946031AF1-268 GEN
Solar/Wind Harmer
8.098
965461AG1-414 GEN
Solar/Wind Harmer
2.212
970289AG2-191 GEN
Solar/Wind Harmer
0.749
247642Z2-115 C
Solar/Wind Harmer
0.062
970825AG2-519 GEN
Solar/Wind Harmer
5.495
958171AF2-111 GEN
Solar/Wind Harmer
24.37
962031AG1-047 GEN
Solar/Wind Harmer
2.947
957741AF2-068 GEN
Solar/Wind Harmer
14.62
270043AE2-236 GEN
Solar/Wind Harmer
5.343
971347AH1-153 GEN
Solar/Wind Harmer
4.84
965021AG1-366 GEN
Solar/Wind Harmer
2.246
24690905MDL-1G C
Solar/Wind Harmer
7.751
970781AG2-491 GEN
Solar/Wind Harmer
9.656
24728705AND G3
Adder
7.736
24728505AND G1
Adder
3.699
274772LINCOLN ;3U
Adder
8.068
274752CRETE EC ;2U
Adder
7.868
274753CRETE EC ;3U
Adder
7.868
274724RIVER EC ;11
Adder
16.907
274814UNIV PK N;0U
Adder
4.818
274807UNIV PK N;3U
Adder
4.808
274811UNIV PK N;7U
Adder
4.777
274803UNIV PARK;6U
Adder
5.555
274826FISK ;BP
Adder
10.428
972038AH1-567 GEN2
Adder
0.348
972259AH1-714 GEN
Adder
18.171
274729ELWOOD EC;1P
Adder
15.629
274730ELWOOD EC;6P
Adder
15.629
274734ELWOOD EC;8P
Adder
15.629
274736ELWOOD EC;9P
Adder
15.629
274676JOLIET 29;8U
Adder
28.13
274682WAUKEGAN ;7U
Adder
3.431
23562501BACKB
Solar/Wind Helper
1.061
964991AG1-363 GEN
Solar/Wind Helper
3.902
237048AF1-022 C
Solar/Wind Helper
0.177
238127S14_GEN_2
Solar/Wind Helper
0.723
238108AE1-109 GEN1
Solar/Wind Helper
0.095
238110AE1-109 GEN3
Solar/Wind Helper
0.095
238175AF1-290_GEN
Solar/Wind Helper
0.12
270119AB2-067 GEN1
50/50
5.526
270120AB2-067 GEN2
50/50
5.526
243186AF1-051 GEN
50/50
6.835
24318905MLG2
50/50
4.392
24723005RIVRG1
Adder
20.295
24723105RIVRG2
Adder
20.295
270349AD2-093_GEN
Solar/Wind Harmer
3.833
270471AD2-092_GEN
Solar/Wind Harmer
3.833
927014AC1-188 GEN
Solar/Wind Harmer
1.623
946101AF1-275 GEN
Solar/Wind Harmer
1.528
253383AE2-342_GEN
Solar/Wind Harmer
0.893
270269AC2-059
Solar/Wind Harmer
9.401
942861AE2-305 GEN
Solar/Wind Harmer
7.844
253415AE1-040 GEN
Solar/Wind Harmer
1.129
962581AG1-107 GEN
Solar/Wind Harmer
5.049
961491AF2-440 GEN
Solar/Wind Harmer
2.098
971073AG2-665 GEN
Solar/Wind Harmer
8.014
970879AG2-548 GEN
Solar/Wind Harmer
1.165
252509AD1-136 GEN
Solar/Wind Harmer
0.254
25183208HLCRTG
Solar/Wind Harmer
6.012
253370AE2-315 SEC1
Adder
1.985
25194408D.CRK1
Adder
7.492
25194508D.CRK3
Adder
1.401
25326109MON D
Adder
1.302
25322209TAIT E
Adder
9.654
25322209TAIT E
Adder
9.437
253349AC2-067 GEN
Solar/Wind Harmer
2.009
253400AC2-068 GEN
Solar/Wind Harmer
0.808
270054AF2-122 C O1
Solar/Wind Harmer
3.201
944541AF1-119 GEN
Solar/Wind Harmer
4.099
960971AF2-388 GEN
Solar/Wind Harmer
10.701
253378AE2-206_GEN
Solar/Wind Harmer
3.516
926881AC1-175 GEN
Solar/Wind Harmer
5.459
270383AD1-128 GEN
Solar/Wind Harmer
5.966
24728805RICHG1
Adder
3.693
24728905RICHG2
Adder
3.693
970883AG2-550 GEN
Solar/Wind Harmer
9.768
970885AG2-551 GEN
Solar/Wind Harmer
2.272
270462AD2-086
Solar/Wind Harmer
6.791
25326509SID D
Adder
1.283
970291AG2-192 GEN
Solar/Wind Harmer
1.268
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
7.946
270599AE1-208 GEN
Solar/Wind Harmer
7.946
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
5.009
24725505WLD G2 C
Solar/Wind Harmer
3.871
24699105WLD G1 C
Solar/Wind Harmer
3.826
942221AE2-234 GEN
Solar/Wind Harmer
3.406
970349AG2-230 GEN
Solar/Wind Harmer
14.521
945421AF1-207 GEN
Solar/Wind Harmer
13.575
957841AF2-078 GEN
Solar/Wind Harmer
5.844
270180AB1-006 GEN1
Solar/Wind Harmer
6.944
24697605MDL-3G C
Solar/Wind Harmer
3.559
24755605MDL-5G
Solar/Wind Harmer
2.328
24697905MDL-4G C
Solar/Wind Harmer
2.216
270181AB1-006 GEN2
Solar/Wind Harmer
0.69
938701AE1-092 GEN
Solar/Wind Harmer
19.934
247620Y3-023
Adder
0.441
274770LINCOLN ;1U
Adder
8.068
274771LINCOLN ;2U
Adder
8.068
274805UNIV PK N;1U
Adder
4.787
274808UNIV PK N;4U
Adder
4.756
274674JOLIET 9 ;6U
Adder
14.638
274695ROCKY RD ;2P
Adder
10.532
274693ROCKY RD ;1P
Adder
10.429
274697ROCKY RD ;3P
Adder
2.861
274696ROCKY RD ;4P
Adder
10.781
23751201ROTHROCK
Solar/Wind Helper
0.861
23585401KL_K28_T16
Solar/Wind Helper
1.4
235054AD2-180 GEN
Solar/Wind Helper
1.865
238117U2-030
Solar/Wind Helper
0.304
316097T157 G90
Solar/Wind Helper
1.193
235531U2-073 GEN
Solar/Wind Helper
2.906
LAGNLTFEXP_LAGN->PJM
CLTF
15.279
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.293
TVALTFEXP_TVA->PJM
CLTF
7.605
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.853
MECLTFEXP_MEC->PJM
CLTF
15.194
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CPLELTFEXP_CPLE->PJM
CLTF
2.146
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.043
NYPJM->LTFIMP_NY
CLTF
4.022
LGEELTFEXP_LGEE->PJM
CLTF
6.535
WECLTFEXP_WEC->PJM
CLTF
3.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4052.99
MW Contribution:
9.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
38.42
970149AG2-104 GEN
Solar/Wind Harmer
23.725
970155AG2-107 GEN
Solar/Wind Harmer
16.753
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
3.193
270331AC1-082 GEN3
Solar/Wind Harmer
0.502
270286AF1-227 GEN2
Solar/Wind Harmer
2.151
270520AE2-214 GEN
Solar/Wind Harmer
6.107
270273AD2-016 GEN
Solar/Wind Harmer
2.677
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
1.043
253316AC1-085 GEN3
Solar/Wind Harmer
8.322
946171AF1-282 GEN
Solar/Wind Harmer
9.94
253398AE2-221_GEN2
Solar/Wind Harmer
4.505
252516AE2-318_GEN
Solar/Wind Harmer
9.922
252510AF1-249 C
Solar/Wind Harmer
0.413
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
270391AF1-285 GEN3
Solar/Wind Harmer
1.195
270578AF1-285 GEN2
Solar/Wind Harmer
1.195
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
270222AC2-111 GEN
Solar/Wind Harmer
4.385
944031AF1-071 GEN
Solar/Wind Harmer
0.987
965651AG1-433 GEN
Solar/Wind Harmer
5.345
958861AF2-177 GEN
Solar/Wind Harmer
10.687
942081AE2-220 GEN
Solar/Wind Harmer
6.249
270209AC1-174_GEN
Solar/Wind Harmer
3.977
270437AC2-090 C
Solar/Wind Harmer
5.454
270239V3-007_GEN1
Solar/Wind Harmer
1.681
945371AF1-202 GEN
Solar/Wind Harmer
6.817
945681AF1-233 GEN
Solar/Wind Harmer
18.397
270317AD1-130_GEN
Solar/Wind Harmer
3.123
270485AE1-090_GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
5.332
270594AE1-207 GEN
Solar/Wind Harmer
13.238
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.045
276903AD2-071 C
Solar/Wind Harmer
9.73
270024AE2-089 GEN
Solar/Wind Harmer
4.552
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
9.84
24791305MDL-5G
Solar/Wind Harmer
2.326
965011AG1-365 GEN
Solar/Wind Harmer
9.647
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
7.578
971917AH1-482 GEN
Solar/Wind Harmer
8.743
24728605AND G2
Adder
3.696
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274745AC1-111 GEN9
Adder
5.296
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
958381AF2-132 GEN
Solar/Wind Harmer
6.61
971985AH1-537 GEN
Solar/Wind Harmer
18.214
270263AC1-001 GEN
Solar/Wind Harmer
1.051
943861AF1-054 GEN
Solar/Wind Harmer
3.868
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
3.034
270432AC2-029 GEN
Solar/Wind Harmer
7.024
241955AC1-078 GEN
Solar/Wind Harmer
7.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.984
241974AD2-163_GEN2
Solar/Wind Harmer
1.984
253338AC1-165 GEN
Solar/Wind Harmer
1.081
253343AC1-166 GEN
Solar/Wind Harmer
1.081
945631AF1-228 GEN
Solar/Wind Harmer
4.679
253406AD2-031_GEN
Solar/Wind Harmer
1.273
241972AD1-140 GEN
Solar/Wind Harmer
4.45
253433AC1-085 GEN1
Solar/Wind Harmer
5.282
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
270459AD2-067 GEN
Solar/Wind Harmer
8.295
961821AG1-024 GEN
Solar/Wind Harmer
8.422
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270223U2-072_GEN1
Solar/Wind Harmer
1.952
270224U2-072_GEN2
Solar/Wind Harmer
1.952
270227U2-072_GEN3
Solar/Wind Harmer
1.952
270228U2-072_GEN4
Solar/Wind Harmer
1.952
270231U2-072_GEN5
Solar/Wind Harmer
1.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
5.023
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
958711AF2-162 GEN
Solar/Wind Harmer
0.989
945581AF1-223 GEN
Solar/Wind Harmer
4.431
971029AG2-637 GEN
Solar/Wind Harmer
14.654
270071AF1-092 GEN
Solar/Wind Harmer
14.639
270543AE2-219 C
Solar/Wind Harmer
9.759
270302AB2-170 GEN
Solar/Wind Harmer
8.168
247536S-71 GEN
Solar/Wind Harmer
3.945
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.799
970289AG2-191 GEN
Solar/Wind Harmer
1.852
964611AG1-324 GEN
Solar/Wind Harmer
3.798
270356AE2-297 GEN
Solar/Wind Harmer
4.491
961761AG1-017 GEN
Solar/Wind Harmer
0.417
957241AF2-018 GEN
Solar/Wind Harmer
4.296
270053AF1-130 C
Solar/Wind Harmer
17.164
963791AG1-232 GEN
Solar/Wind Harmer
13.051
946581AF1-322 GEN
Solar/Wind Harmer
9.871
24691005MDL-2G C
Solar/Wind Harmer
3.567
959331AF2-224 GEN
Solar/Wind Harmer
9.647
959141AF2-205 GEN
Solar/Wind Harmer
5.832
958391AF2-133 GEN
Solar/Wind Harmer
8.746
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
38.42
970153AG2-106 GEN
Solar/Wind Harmer
16.753
24686405CER G5
Adder
8.833
270330AC1-082 GEN2
Solar/Wind Harmer
0.501
270329AC1-082 GEN1
Solar/Wind Harmer
0.501
971191AH1-055 GEN
Solar/Wind Harmer
19.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.814
270287AF1-227 GEN3
Solar/Wind Harmer
2.151
957541AF2-048 GEN
Solar/Wind Harmer
1.622
270367AC2-061_GEN
Solar/Wind Harmer
3.183
970879AG2-548 GEN
Solar/Wind Harmer
8.007
942051AE2-217 GEN
Solar/Wind Harmer
18.009
253325AC1-069 GEN
Solar/Wind Harmer
1.043
270186AC1-089 GEN
Solar/Wind Harmer
6.09
270518AE2-148 GEN
Solar/Wind Harmer
12.029
253317AC1-085 GEN4
Solar/Wind Harmer
8.322
946181AF1-283 GEN
Solar/Wind Harmer
12.922
252507AC2-088 GEN
Solar/Wind Harmer
1.779
253394AE2-221_GEN
Solar/Wind Harmer
4.505
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
12.632
253303V4-073 C
Solar/Wind Harmer
0.115
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
252524AE2-267 GEN
Solar/Wind Harmer
1.558
25196608WSDLE5
Adder
8.482
942871AE2-306 GEN
Solar/Wind Harmer
0.896
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
960071AF2-298 GEN
Solar/Wind Harmer
1.495
960801AF2-371 GEN
Solar/Wind Harmer
2.503
964871AG1-351 GEN
Solar/Wind Harmer
1.728
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
34.283
276820AF1-078_GEN
Solar/Wind Harmer
1.561
24379505HDWTR1G C
Solar/Wind Harmer
7.727
270240V3-007_GEN2
Solar/Wind Harmer
6.045
972167AH1-666 GEN
Solar/Wind Harmer
7.81
270004AE1-209 GEN
Solar/Wind Harmer
5.332
946031AF1-268 GEN
Solar/Wind Harmer
8.091
965461AG1-414 GEN
Solar/Wind Harmer
2.21
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.062
970825AG2-519 GEN
Solar/Wind Harmer
5.491
958171AF2-111 GEN
Solar/Wind Harmer
24.35
962031AG1-047 GEN
Solar/Wind Harmer
2.944
957741AF2-068 GEN
Solar/Wind Harmer
14.606
270043AE2-236 GEN
Solar/Wind Harmer
5.338
971347AH1-153 GEN
Solar/Wind Harmer
4.836
24690905MDL-1G C
Solar/Wind Harmer
7.745
970781AG2-491 GEN
Solar/Wind Harmer
9.647
965021AG1-366 GEN
Solar/Wind Harmer
2.244
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
274803UNIV PARK;6U
Adder
5.55
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
972259AH1-714 GEN
Adder
18.154
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
274682WAUKEGAN ;7U
Adder
3.428
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
3.829
270471AD2-092_GEN
Solar/Wind Harmer
3.829
927014AC1-188 GEN
Solar/Wind Harmer
1.622
946101AF1-275 GEN
Solar/Wind Harmer
1.527
253383AE2-342_GEN
Solar/Wind Harmer
0.892
270269AC2-059
Solar/Wind Harmer
9.392
942861AE2-305 GEN
Solar/Wind Harmer
7.837
253415AE1-040 GEN
Solar/Wind Harmer
1.128
962581AG1-107 GEN
Solar/Wind Harmer
5.045
961491AF2-440 GEN
Solar/Wind Harmer
2.097
971073AG2-665 GEN
Solar/Wind Harmer
8.007
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.254
25183208HLCRTG
Solar/Wind Harmer
6.007
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
253349AC2-067 GEN
Solar/Wind Harmer
2.007
253400AC2-068 GEN
Solar/Wind Harmer
0.807
270054AF2-122 C O1
Solar/Wind Harmer
3.197
944541AF1-119 GEN
Solar/Wind Harmer
4.095
960971AF2-388 GEN
Solar/Wind Harmer
10.691
253378AE2-206_GEN
Solar/Wind Harmer
3.513
926881AC1-175 GEN
Solar/Wind Harmer
5.454
270383AD1-128 GEN
Solar/Wind Harmer
5.961
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
9.759
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
6.784
970291AG2-192 GEN
Solar/Wind Harmer
1.267
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
7.939
270599AE1-208 GEN
Solar/Wind Harmer
7.939
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
5.005
24725505WLD G2 C
Solar/Wind Harmer
3.868
24699105WLD G1 C
Solar/Wind Harmer
3.822
942221AE2-234 GEN
Solar/Wind Harmer
3.403
970349AG2-230 GEN
Solar/Wind Harmer
14.508
945421AF1-207 GEN
Solar/Wind Harmer
13.563
957841AF2-078 GEN
Solar/Wind Harmer
5.839
270180AB1-006 GEN1
Solar/Wind Harmer
6.938
24697605MDL-3G C
Solar/Wind Harmer
3.556
24755605MDL-5G
Solar/Wind Harmer
2.326
24697905MDL-4G C
Solar/Wind Harmer
2.214
270181AB1-006 GEN2
Solar/Wind Harmer
0.69
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
274674JOLIET 9 ;6U
Adder
14.625
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.79
MW Contribution:
6.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971985AH1-537 GEN
Solar/Wind Harmer
2.118
270263AC1-001 GEN
Solar/Wind Harmer
0.702
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.516
241972AD1-140 GEN
Solar/Wind Harmer
0.757
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.113
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
247536S-71 GEN
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
7.573
972165AH1-665 GEN
Solar/Wind Harmer
6.065
970289AG2-191 GEN
Solar/Wind Harmer
1.292
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
963791AG1-232 GEN
Solar/Wind Harmer
9.106
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.711
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
965051AG1-369 GEN
Solar/Wind Harmer
3.331
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270399AC1-101 GEN
Solar/Wind Harmer
2.112
270400AC1-102 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
32.401
970149AG2-104 GEN
Solar/Wind Harmer
17.497
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
253398AE2-221_GEN2
Solar/Wind Harmer
0
252516AE2-318_GEN
Solar/Wind Harmer
7.753
252510AF1-249 C
Solar/Wind Harmer
0.052
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
965651AG1-433 GEN
Solar/Wind Harmer
2.002
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5
945371AF1-202 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270317AD1-130_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
970773AG2-487 GEN
Solar/Wind Harmer
1.2
276903AD2-071 C
Solar/Wind Harmer
7.58
270024AE2-089 GEN
Solar/Wind Harmer
0.001
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.743
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971073AG2-665 GEN
Solar/Wind Harmer
5.121
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
270054AF2-122 C O1
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
4.003
970329AG2-216 GEN
Solar/Wind Harmer
2.946
926881AC1-175 GEN
Solar/Wind Harmer
0
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
24686405CER G5
Adder
8.833
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
942051AE2-217 GEN
Solar/Wind Harmer
12.564
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.57
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252507AC2-088 GEN
Solar/Wind Harmer
0.312
253394AE2-221_GEN
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
6.169
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
970191AG2-125 GEN
Solar/Wind Harmer
1.771
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
30.627
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
270004AE1-209 GEN
Solar/Wind Harmer
1.475
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.122
958171AF2-111 GEN
Solar/Wind Harmer
16.988
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
971347AH1-153 GEN
Solar/Wind Harmer
3.374
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.73
965021AG1-366 GEN
Solar/Wind Harmer
2.244
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
24386205FR-12G C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
276843GEN-1.7
Solar/Wind Harmer
0.215
276806AD2-047 C O1
Solar/Wind Harmer
3.764
274803UNIV PARK;6U
Adder
5.55
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
970707AG2-453 GEN
Solar/Wind Harmer
21.689
972259AH1-714 GEN
Adder
18.154
24695305TIMB G C
Solar/Wind Harmer
0.562
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
246938BC-WTG3
Solar/Wind Harmer
0.239
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
274682WAUKEGAN ;7U
Adder
3.428
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
965091AG1-374 GEN
Solar/Wind Harmer
19.702
959611AF2-252 GEN
Solar/Wind Harmer
2.189
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
3.738
270599AE1-208 GEN
Solar/Wind Harmer
6.229
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.725
970349AG2-230 GEN
Solar/Wind Harmer
10.122
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.761
965681AG1-436 GEN
Solar/Wind Harmer
8.373
965791AG1-447 GEN
Solar/Wind Harmer
6.14
970241AG2-163 GEN
Solar/Wind Harmer
3.903
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
270247TR4_N_V136
Solar/Wind Harmer
0.043
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
972043AH1-570 GEN
Solar/Wind Harmer
1.73
972045AH1-571 GEN
Solar/Wind Harmer
1.386
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
276776AD2-060 GEN
Solar/Wind Harmer
0.708
958011AF2-095 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
958481AF2-142 GEN
Solar/Wind Harmer
9.909
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
958491AF2-143 GEN
Solar/Wind Harmer
9.89
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
971125AH1-004 GEN
Solar/Wind Harmer
2.63
970107AG2-081 GEN
Solar/Wind Harmer
1.973
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
941551AE2-152 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
939401AE1-172 GEN
Solar/Wind Harmer
4.951
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.213
962781AG1-127 GEN
Solar/Wind Harmer
6.263
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
19.691
971403AH1-188 GEN
Solar/Wind Harmer
9.18
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.598
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.91
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
971171AH1-044 GEN
Solar/Wind Harmer
11.056
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
959091AF2-200 GEN
Solar/Wind Harmer
11.056
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.62
MW Contribution:
6.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
24686405CER G5
Adder
8.833
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
942051AE2-217 GEN
Solar/Wind Harmer
12.564
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.57
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252507AC2-088 GEN
Solar/Wind Harmer
0.312
253394AE2-221_GEN
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
6.169
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
970191AG2-125 GEN
Solar/Wind Harmer
1.771
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
30.627
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
270004AE1-209 GEN
Solar/Wind Harmer
1.475
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.122
958171AF2-111 GEN
Solar/Wind Harmer
16.988
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
971347AH1-153 GEN
Solar/Wind Harmer
3.374
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.73
965021AG1-366 GEN
Solar/Wind Harmer
2.244
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
24386205FR-12G C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
276843GEN-1.7
Solar/Wind Harmer
0.215
276806AD2-047 C O1
Solar/Wind Harmer
3.764
274803UNIV PARK;6U
Adder
5.55
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
970707AG2-453 GEN
Solar/Wind Harmer
21.689
972259AH1-714 GEN
Adder
18.154
24695305TIMB G C
Solar/Wind Harmer
0.562
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
246938BC-WTG3
Solar/Wind Harmer
0.239
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
274682WAUKEGAN ;7U
Adder
3.428
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
965091AG1-374 GEN
Solar/Wind Harmer
19.702
959611AF2-252 GEN
Solar/Wind Harmer
2.189
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
23562501BACKB
Solar/Wind Helper
1.069
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
32.401
970149AG2-104 GEN
Solar/Wind Harmer
17.497
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
253398AE2-221_GEN2
Solar/Wind Harmer
0
252516AE2-318_GEN
Solar/Wind Harmer
7.753
252510AF1-249 C
Solar/Wind Harmer
0.052
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
965651AG1-433 GEN
Solar/Wind Harmer
2.002
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5
945371AF1-202 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270317AD1-130_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
970773AG2-487 GEN
Solar/Wind Harmer
1.2
276903AD2-071 C
Solar/Wind Harmer
7.58
270024AE2-089 GEN
Solar/Wind Harmer
0.001
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.743
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
941551AE2-152 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.118
270263AC1-001 GEN
Solar/Wind Harmer
0.702
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.516
241972AD1-140 GEN
Solar/Wind Harmer
0.757
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.113
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
247536S-71 GEN
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
7.573
972165AH1-665 GEN
Solar/Wind Harmer
6.065
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
959091AF2-200 GEN
Solar/Wind Harmer
11.056
943021AE2-325 GEN
Solar/Wind Harmer
3.463
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
939401AE1-172 GEN
Solar/Wind Harmer
4.951
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.213
962781AG1-127 GEN
Solar/Wind Harmer
6.263
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
19.691
971403AH1-188 GEN
Solar/Wind Harmer
9.18
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
970289AG2-191 GEN
Solar/Wind Harmer
1.292
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
963791AG1-232 GEN
Solar/Wind Harmer
9.106
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.711
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
965051AG1-369 GEN
Solar/Wind Harmer
3.331
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270399AC1-101 GEN
Solar/Wind Harmer
2.112
270400AC1-102 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.598
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.91
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
971171AH1-044 GEN
Solar/Wind Harmer
11.056
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971073AG2-665 GEN
Solar/Wind Harmer
5.121
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
270054AF2-122 C O1
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
4.003
970329AG2-216 GEN
Solar/Wind Harmer
2.946
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
3.738
270599AE1-208 GEN
Solar/Wind Harmer
6.229
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.725
970349AG2-230 GEN
Solar/Wind Harmer
10.122
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.761
965681AG1-436 GEN
Solar/Wind Harmer
8.373
965791AG1-447 GEN
Solar/Wind Harmer
6.14
970241AG2-163 GEN
Solar/Wind Harmer
3.903
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
270247TR4_N_V136
Solar/Wind Harmer
0.043
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
972043AH1-570 GEN
Solar/Wind Harmer
1.73
972045AH1-571 GEN
Solar/Wind Harmer
1.386
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
276776AD2-060 GEN
Solar/Wind Harmer
0.708
958011AF2-095 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
958481AF2-142 GEN
Solar/Wind Harmer
9.909
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
958491AF2-143 GEN
Solar/Wind Harmer
9.89
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
971125AH1-004 GEN
Solar/Wind Harmer
2.63
970107AG2-081 GEN
Solar/Wind Harmer
1.973
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.46 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1280.75
MW Contribution:
4.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.883
253372AE2-315 SEC3
50/50
2.883
25322309TAIT W
50/50
0.725
963581AG1-207 GEN
50/50
13.122
25306009OHH W.
50/50
4.036
253406AD2-031_GEN
Solar/Wind Harmer
1.502
253433AC1-085 GEN1
Solar/Wind Harmer
6.126
253432AC1-085 GEN2
Solar/Wind Harmer
0.308
241972AD1-140 GEN
Solar/Wind Harmer
5.064
25196408WSDLE3
Adder
7.962
25196308WSDLE2
Adder
7.892
25196208WSDLE1
Adder
7.873
25196708WSDLE6
Adder
7.853
25196508WSDLE4
Adder
7.655
253338AC1-165 GEN
Solar/Wind Harmer
0.936
253343AC1-166 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.08
25196108MFTGT2
Adder
1.003
972163AH1-664 GEN
Solar/Wind Harmer
6.541
972165AH1-665 GEN
Solar/Wind Harmer
5.233
339216AC1-074 GEN
Solar/Wind Harmer
0.983
971029AG2-637 GEN
Solar/Wind Harmer
8.241
3429211JKCT 2G
Adder
5.992
270340AC2-060 GEN
Solar/Wind Harmer
1.546
270543AE2-219 C
Solar/Wind Harmer
4.97
270356AE2-297 GEN
Solar/Wind Harmer
2.178
247536S-71 GEN
Solar/Wind Harmer
1.819
945631AF1-228 GEN
Solar/Wind Helper
5.27
241955AC1-078 GEN
Solar/Wind Helper
1.493
253370AE2-315 SEC1
50/50
3.048
253371AE2-315 SEC2
50/50
2.883
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.706
270518AE2-148 GEN
Solar/Wind Harmer
58.665
253303V4-073 C
Solar/Wind Harmer
0.166
253394AE2-221_GEN
Solar/Wind Harmer
6.188
960071AF2-298 GEN
Solar/Wind Harmer
2
253317AC1-085 GEN4
Solar/Wind Harmer
9.651
946181AF1-283 GEN
Solar/Wind Harmer
14.986
252524AE2-267 GEN
Solar/Wind Harmer
1.421
25196608WSDLE5
Adder
7.734
252519AF1-045_GEN
Solar/Wind Harmer
3.241
25194608D.CRK4
Adder
1.453
253325AC1-069 GEN
Solar/Wind Harmer
0.903
252507AC2-088 GEN
Solar/Wind Harmer
1.396
958171AF2-111 GEN
Solar/Wind Harmer
17.698
25196008MFTGT1
Adder
0.949
270367AC2-061_GEN
Solar/Wind Harmer
2.224
270186AC1-089 GEN
Solar/Wind Harmer
4.095
972167AH1-666 GEN
Solar/Wind Harmer
5.322
276820AF1-078_GEN
Solar/Wind Harmer
1.05
339243AC2-075 GEN1
Solar/Wind Harmer
0.266
3429391JKCT 9G
Adder
4.401
970093AG2-073 GEN
Solar/Wind Harmer
2.526
960801AF2-371 GEN
Solar/Wind Helper
0.81
964871AG1-351 GEN
Solar/Wind Helper
0.559
253370AE2-315 SEC1
50/50
3.048
253371AE2-315 SEC2
50/50
2.883
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.715
25326309TAIT D
50/50
1.634
253398AE2-221_GEN2
Solar/Wind Harmer
6.188
253316AC1-085 GEN3
Solar/Wind Harmer
9.651
946171AF1-282 GEN
Solar/Wind Harmer
11.528
252516AE2-318_GEN
Solar/Wind Harmer
8.904
25194608D.CRK4
Adder
1.453
252510AF1-249 C
Solar/Wind Harmer
0.366
253333AC1-068 GEN
Solar/Wind Harmer
0.903
25196808ZIMRHP
Adder
60.379
270222AC2-111 GEN
Solar/Wind Harmer
3.28
944031AF1-071 GEN
Solar/Wind Harmer
0.738
25196008MFTGT1
Adder
0.98
945681AF1-233 GEN
Solar/Wind Harmer
12.49
339221AD2-048_GEN
Solar/Wind Harmer
0.892
943111AE2-339 GEN
Solar/Wind Harmer
0.482
3429421JKCT 10G
Adder
4.401
3429241JKCT 3G
Adder
6.071
270520AE2-214 GEN
Solar/Wind Helper
3.42
270273AD2-016 GEN
Solar/Wind Helper
1.39
25326109MON D
50/50
2.073
253370AE2-315 SEC1
50/50
3.048
25322209TAIT E
50/50
14.549
25322209TAIT E
50/50
14.222
253349AC2-067 GEN
Solar/Wind Harmer
2.467
253400AC2-068 GEN
Solar/Wind Harmer
0.992
25183208HLCRTG
Solar/Wind Harmer
5.429
25194408D.CRK1
Adder
6.682
25194508D.CRK3
Adder
1.249
252509AD1-136 GEN
Solar/Wind Harmer
0.199
962581AG1-107 GEN
Solar/Wind Harmer
3.84
961491AF2-440 GEN
Solar/Wind Harmer
1.596
25326509SID D
Adder
0.994
253378AE2-206_GEN
Solar/Wind Harmer
2.364
253415AE1-040 GEN
Solar/Wind Harmer
0.712
24728805RICHG1
Adder
2.328
24728905RICHG2
Adder
2.328
972043AH1-570 GEN
Solar/Wind Harmer
1.433
972045AH1-571 GEN
Solar/Wind Harmer
1.146
971125AH1-004 GEN
Solar/Wind Harmer
2.193
970107AG2-081 GEN
Solar/Wind Harmer
1.645
942891AE2-308 GEN
Solar/Wind Harmer
4.996
970883AG2-550 GEN
Solar/Wind Harmer
4.97
970885AG2-551 GEN
Solar/Wind Harmer
1.156
270383AD1-128 GEN
Solar/Wind Harmer
2.879
946101AF1-275 GEN
Solar/Wind Helper
0.855
270054AF2-122 C O1
Solar/Wind Helper
0.905
LAGNLTFEXP_LAGN->PJM
CLTF
3.675
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.51
TVALTFEXP_TVA->PJM
CLTF
1.909
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.793
MECLTFEXP_MEC->PJM
CLTF
3.19
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.187
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.289
NYPJM->LTFIMP_NY
CLTF
0.854
LGEELTFEXP_LGEE->PJM
CLTF
2.959
WECLTFEXP_WEC->PJM
CLTF
0.652

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#16620_05ADKINS 345_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16620_05ADKINS 345_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.16 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1253.03
MW Contribution:
5.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.9
253372AE2-315 SEC3
50/50
2.9
25322309TAIT W
50/50
0.729
963581AG1-207 GEN
50/50
13.198
25306009OHH W.
50/50
4.06
253406AD2-031_GEN
Solar/Wind Harmer
1.511
253433AC1-085 GEN1
Solar/Wind Harmer
6.167
253432AC1-085 GEN2
Solar/Wind Harmer
0.31
241972AD1-140 GEN
Solar/Wind Harmer
5.057
25196408WSDLE3
Adder
8.018
25196308WSDLE2
Adder
7.948
25196208WSDLE1
Adder
7.928
25196708WSDLE6
Adder
7.908
25196508WSDLE4
Adder
7.709
253338AC1-165 GEN
Solar/Wind Harmer
0.943
253343AC1-166 GEN
Solar/Wind Harmer
0.943
25196108MFTGT2
Adder
1.089
25196108MFTGT2
Adder
1.011
972163AH1-664 GEN
Solar/Wind Harmer
6.591
972165AH1-665 GEN
Solar/Wind Harmer
5.273
339216AC1-074 GEN
Solar/Wind Harmer
0.991
971029AG2-637 GEN
Solar/Wind Harmer
8.312
3429211JKCT 2G
Adder
6.044
270340AC2-060 GEN
Solar/Wind Harmer
1.547
270543AE2-219 C
Solar/Wind Harmer
5.016
270356AE2-297 GEN
Solar/Wind Harmer
2.199
247536S-71 GEN
Solar/Wind Harmer
1.837
945631AF1-228 GEN
Solar/Wind Helper
5.193
241955AC1-078 GEN
Solar/Wind Helper
1.665
253370AE2-315 SEC1
50/50
3.066
253371AE2-315 SEC2
50/50
2.9
25322309TAIT W
50/50
0.719
25322209TAIT E
50/50
0.719
25326309TAIT D
50/50
1.644
253398AE2-221_GEN2
Solar/Wind Harmer
6.228
253316AC1-085 GEN3
Solar/Wind Harmer
9.716
946171AF1-282 GEN
Solar/Wind Harmer
11.605
252516AE2-318_GEN
Solar/Wind Harmer
8.966
25194608D.CRK4
Adder
1.463
252510AF1-249 C
Solar/Wind Harmer
0.369
253333AC1-068 GEN
Solar/Wind Harmer
0.909
25196808ZIMRHP
Adder
60.821
270222AC2-111 GEN
Solar/Wind Harmer
3.305
944031AF1-071 GEN
Solar/Wind Harmer
0.744
25196008MFTGT1
Adder
0.988
945681AF1-233 GEN
Solar/Wind Harmer
12.585
339221AD2-048_GEN
Solar/Wind Harmer
0.899
943111AE2-339 GEN
Solar/Wind Harmer
0.486
3429421JKCT 10G
Adder
4.439
3429241JKCT 3G
Adder
6.123
339211AE2-254 GEN
Solar/Wind Harmer
0.652
270520AE2-214 GEN
Solar/Wind Helper
3.359
270273AD2-016 GEN
Solar/Wind Helper
1.454
253370AE2-315 SEC1
50/50
3.066
253371AE2-315 SEC2
50/50
2.9
25322309TAIT W
50/50
0.719
25322209TAIT E
50/50
0.71
270518AE2-148 GEN
Solar/Wind Harmer
59.047
253303V4-073 C
Solar/Wind Harmer
0.167
253394AE2-221_GEN
Solar/Wind Harmer
6.228
960071AF2-298 GEN
Solar/Wind Harmer
2.012
253317AC1-085 GEN4
Solar/Wind Harmer
9.716
946181AF1-283 GEN
Solar/Wind Harmer
15.086
252524AE2-267 GEN
Solar/Wind Harmer
1.431
25196608WSDLE5
Adder
7.789
252519AF1-045_GEN
Solar/Wind Harmer
3.263
25194608D.CRK4
Adder
1.463
253325AC1-069 GEN
Solar/Wind Harmer
0.909
252507AC2-088 GEN
Solar/Wind Harmer
1.407
958171AF2-111 GEN
Solar/Wind Harmer
17.831
25196008MFTGT1
Adder
0.956
270367AC2-061_GEN
Solar/Wind Harmer
2.237
270186AC1-089 GEN
Solar/Wind Harmer
4.121
972167AH1-666 GEN
Solar/Wind Harmer
5.363
276820AF1-078_GEN
Solar/Wind Harmer
1.057
339243AC2-075 GEN1
Solar/Wind Harmer
0.268
3429391JKCT 9G
Adder
4.439
970093AG2-073 GEN
Solar/Wind Harmer
2.549
960801AF2-371 GEN
Solar/Wind Helper
0.86
964871AG1-351 GEN
Solar/Wind Helper
0.594
25326109MON D
50/50
2.084
253370AE2-315 SEC1
50/50
3.066
25322209TAIT E
50/50
14.633
25322209TAIT E
50/50
14.305
253349AC2-067 GEN
Solar/Wind Harmer
2.483
253400AC2-068 GEN
Solar/Wind Harmer
0.998
25183208HLCRTG
Solar/Wind Harmer
5.467
25194408D.CRK1
Adder
6.73
25194508D.CRK3
Adder
1.258
252509AD1-136 GEN
Solar/Wind Harmer
0.201
962581AG1-107 GEN
Solar/Wind Harmer
3.863
961491AF2-440 GEN
Solar/Wind Harmer
1.605
25326509SID D
Adder
1.001
253378AE2-206_GEN
Solar/Wind Harmer
2.38
253415AE1-040 GEN
Solar/Wind Harmer
0.714
24728805RICHG1
Adder
2.347
24728905RICHG2
Adder
2.347
972043AH1-570 GEN
Solar/Wind Harmer
1.444
972045AH1-571 GEN
Solar/Wind Harmer
1.155
971125AH1-004 GEN
Solar/Wind Harmer
2.212
970107AG2-081 GEN
Solar/Wind Harmer
1.659
942891AE2-308 GEN
Solar/Wind Harmer
5.04
970883AG2-550 GEN
Solar/Wind Harmer
5.016
970885AG2-551 GEN
Solar/Wind Harmer
1.166
270383AD1-128 GEN
Solar/Wind Harmer
2.906
946101AF1-275 GEN
Solar/Wind Helper
0.84
270054AF2-122 C O1
Solar/Wind Helper
0.906
LAGNLTFEXP_LAGN->PJM
CLTF
3.736
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.581
TVALTFEXP_TVA->PJM
CLTF
1.94
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.406
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.915
MECLTFEXP_MEC->PJM
CLTF
3.243
SIGELTFEXP_SIGE->PJM
CLTF
0.182
CPLELTFEXP_CPLE->PJM
CLTF
0.211
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.723
NYPJM->LTFIMP_NY
CLTF
0.842
LGEELTFEXP_LGEE->PJM
CLTF
2.987
WECLTFEXP_WEC->PJM
CLTF
0.664

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#16621_05ADKINS 345_A1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.15 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1252.96
MW Contribution:
5.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.066
253371AE2-315 SEC2
50/50
2.9
25322309TAIT W
50/50
0.719
25322209TAIT E
50/50
0.719
25326309TAIT D
50/50
1.644
253398AE2-221_GEN2
Solar/Wind Harmer
6.228
253316AC1-085 GEN3
Solar/Wind Harmer
9.716
946171AF1-282 GEN
Solar/Wind Harmer
11.605
252516AE2-318_GEN
Solar/Wind Harmer
8.966
25194608D.CRK4
Adder
1.463
252510AF1-249 C
Solar/Wind Harmer
0.369
253333AC1-068 GEN
Solar/Wind Harmer
0.909
25196808ZIMRHP
Adder
60.821
270222AC2-111 GEN
Solar/Wind Harmer
3.305
944031AF1-071 GEN
Solar/Wind Harmer
0.744
25196008MFTGT1
Adder
0.988
945681AF1-233 GEN
Solar/Wind Harmer
12.585
339221AD2-048_GEN
Solar/Wind Harmer
0.899
943111AE2-339 GEN
Solar/Wind Harmer
0.486
3429421JKCT 10G
Adder
4.439
3429241JKCT 3G
Adder
6.123
339211AE2-254 GEN
Solar/Wind Harmer
0.652
270520AE2-214 GEN
Solar/Wind Helper
3.359
270273AD2-016 GEN
Solar/Wind Helper
1.454
25326109MON D
50/50
2.084
253370AE2-315 SEC1
50/50
3.066
25322209TAIT E
50/50
14.633
25322209TAIT E
50/50
14.305
253349AC2-067 GEN
Solar/Wind Harmer
2.483
253400AC2-068 GEN
Solar/Wind Harmer
0.998
25183208HLCRTG
Solar/Wind Harmer
5.467
25194408D.CRK1
Adder
6.73
25194508D.CRK3
Adder
1.258
252509AD1-136 GEN
Solar/Wind Harmer
0.201
962581AG1-107 GEN
Solar/Wind Harmer
3.863
961491AF2-440 GEN
Solar/Wind Harmer
1.605
25326509SID D
Adder
1.001
253378AE2-206_GEN
Solar/Wind Harmer
2.38
253415AE1-040 GEN
Solar/Wind Harmer
0.714
24728805RICHG1
Adder
2.347
24728905RICHG2
Adder
2.347
972043AH1-570 GEN
Solar/Wind Harmer
1.444
972045AH1-571 GEN
Solar/Wind Harmer
1.155
971125AH1-004 GEN
Solar/Wind Harmer
2.212
970107AG2-081 GEN
Solar/Wind Harmer
1.659
942891AE2-308 GEN
Solar/Wind Harmer
5.04
970883AG2-550 GEN
Solar/Wind Harmer
5.016
970885AG2-551 GEN
Solar/Wind Harmer
1.166
270383AD1-128 GEN
Solar/Wind Harmer
2.906
946101AF1-275 GEN
Solar/Wind Helper
0.84
270054AF2-122 C O1
Solar/Wind Helper
0.906
253372AE2-315 SEC3
50/50
2.9
253372AE2-315 SEC3
50/50
2.9
25322309TAIT W
50/50
0.729
963581AG1-207 GEN
50/50
13.198
25306009OHH W.
50/50
4.06
253406AD2-031_GEN
Solar/Wind Harmer
1.511
253433AC1-085 GEN1
Solar/Wind Harmer
6.167
253432AC1-085 GEN2
Solar/Wind Harmer
0.31
241972AD1-140 GEN
Solar/Wind Harmer
5.057
25196408WSDLE3
Adder
8.018
25196308WSDLE2
Adder
7.948
25196208WSDLE1
Adder
7.928
25196708WSDLE6
Adder
7.908
25196508WSDLE4
Adder
7.709
253338AC1-165 GEN
Solar/Wind Harmer
0.943
253343AC1-166 GEN
Solar/Wind Harmer
0.943
25196108MFTGT2
Adder
1.089
25196108MFTGT2
Adder
1.011
972163AH1-664 GEN
Solar/Wind Harmer
6.591
972165AH1-665 GEN
Solar/Wind Harmer
5.273
339216AC1-074 GEN
Solar/Wind Harmer
0.991
971029AG2-637 GEN
Solar/Wind Harmer
8.312
3429211JKCT 2G
Adder
6.044
270340AC2-060 GEN
Solar/Wind Harmer
1.547
270543AE2-219 C
Solar/Wind Harmer
5.016
270356AE2-297 GEN
Solar/Wind Harmer
2.199
247536S-71 GEN
Solar/Wind Harmer
1.837
945631AF1-228 GEN
Solar/Wind Helper
5.193
241955AC1-078 GEN
Solar/Wind Helper
1.665
253370AE2-315 SEC1
50/50
3.066
253371AE2-315 SEC2
50/50
2.9
25322309TAIT W
50/50
0.719
25322209TAIT E
50/50
0.71
270518AE2-148 GEN
Solar/Wind Harmer
59.047
253303V4-073 C
Solar/Wind Harmer
0.167
253394AE2-221_GEN
Solar/Wind Harmer
6.228
960071AF2-298 GEN
Solar/Wind Harmer
2.012
253317AC1-085 GEN4
Solar/Wind Harmer
9.716
946181AF1-283 GEN
Solar/Wind Harmer
15.086
252524AE2-267 GEN
Solar/Wind Harmer
1.431
25196608WSDLE5
Adder
7.789
252519AF1-045_GEN
Solar/Wind Harmer
3.263
25194608D.CRK4
Adder
1.463
253325AC1-069 GEN
Solar/Wind Harmer
0.909
252507AC2-088 GEN
Solar/Wind Harmer
1.407
958171AF2-111 GEN
Solar/Wind Harmer
17.831
25196008MFTGT1
Adder
0.956
270367AC2-061_GEN
Solar/Wind Harmer
2.237
270186AC1-089 GEN
Solar/Wind Harmer
4.121
972167AH1-666 GEN
Solar/Wind Harmer
5.363
276820AF1-078_GEN
Solar/Wind Harmer
1.057
339243AC2-075 GEN1
Solar/Wind Harmer
0.268
3429391JKCT 9G
Adder
4.439
970093AG2-073 GEN
Solar/Wind Harmer
2.549
960801AF2-371 GEN
Solar/Wind Helper
0.86
964871AG1-351 GEN
Solar/Wind Helper
0.594
LAGNLTFEXP_LAGN->PJM
CLTF
3.736
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.581
TVALTFEXP_TVA->PJM
CLTF
1.94
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.406
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.915
MECLTFEXP_MEC->PJM
CLTF
3.243
SIGELTFEXP_SIGE->PJM
CLTF
0.182
CPLELTFEXP_CPLE->PJM
CLTF
0.211
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.723
NYPJM->LTFIMP_NY
CLTF
0.842
LGEELTFEXP_LGEE->PJM
CLTF
2.987
WECLTFEXP_WEC->PJM
CLTF
0.664

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#16622_05ADKINS 345_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.15 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1252.95
MW Contribution:
5.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.9
253372AE2-315 SEC3
50/50
2.9
25322309TAIT W
50/50
0.729
963581AG1-207 GEN
50/50
13.198
25306009OHH W.
50/50
4.06
253406AD2-031_GEN
Solar/Wind Harmer
1.511
253433AC1-085 GEN1
Solar/Wind Harmer
6.167
253432AC1-085 GEN2
Solar/Wind Harmer
0.31
241972AD1-140 GEN
Solar/Wind Harmer
5.057
25196408WSDLE3
Adder
8.018
25196308WSDLE2
Adder
7.948
25196208WSDLE1
Adder
7.928
25196708WSDLE6
Adder
7.908
25196508WSDLE4
Adder
7.709
253338AC1-165 GEN
Solar/Wind Harmer
0.943
253343AC1-166 GEN
Solar/Wind Harmer
0.943
25196108MFTGT2
Adder
1.089
25196108MFTGT2
Adder
1.011
972163AH1-664 GEN
Solar/Wind Harmer
6.591
972165AH1-665 GEN
Solar/Wind Harmer
5.273
339216AC1-074 GEN
Solar/Wind Harmer
0.991
971029AG2-637 GEN
Solar/Wind Harmer
8.312
3429211JKCT 2G
Adder
6.044
270340AC2-060 GEN
Solar/Wind Harmer
1.547
270543AE2-219 C
Solar/Wind Harmer
5.016
270356AE2-297 GEN
Solar/Wind Harmer
2.199
247536S-71 GEN
Solar/Wind Harmer
1.837
945631AF1-228 GEN
Solar/Wind Helper
5.193
241955AC1-078 GEN
Solar/Wind Helper
1.665
253370AE2-315 SEC1
50/50
3.066
253371AE2-315 SEC2
50/50
2.9
25322309TAIT W
50/50
0.719
25322209TAIT E
50/50
0.719
25326309TAIT D
50/50
1.644
253398AE2-221_GEN2
Solar/Wind Harmer
6.228
253316AC1-085 GEN3
Solar/Wind Harmer
9.716
946171AF1-282 GEN
Solar/Wind Harmer
11.605
252516AE2-318_GEN
Solar/Wind Harmer
8.966
25194608D.CRK4
Adder
1.463
252510AF1-249 C
Solar/Wind Harmer
0.369
253333AC1-068 GEN
Solar/Wind Harmer
0.909
25196808ZIMRHP
Adder
60.821
270222AC2-111 GEN
Solar/Wind Harmer
3.305
944031AF1-071 GEN
Solar/Wind Harmer
0.744
25196008MFTGT1
Adder
0.988
945681AF1-233 GEN
Solar/Wind Harmer
12.585
339221AD2-048_GEN
Solar/Wind Harmer
0.899
943111AE2-339 GEN
Solar/Wind Harmer
0.486
3429421JKCT 10G
Adder
4.439
3429241JKCT 3G
Adder
6.123
339211AE2-254 GEN
Solar/Wind Harmer
0.652
270520AE2-214 GEN
Solar/Wind Helper
3.359
270273AD2-016 GEN
Solar/Wind Helper
1.454
253370AE2-315 SEC1
50/50
3.066
253371AE2-315 SEC2
50/50
2.9
25322309TAIT W
50/50
0.719
25322209TAIT E
50/50
0.71
270518AE2-148 GEN
Solar/Wind Harmer
59.047
253303V4-073 C
Solar/Wind Harmer
0.167
253394AE2-221_GEN
Solar/Wind Harmer
6.228
960071AF2-298 GEN
Solar/Wind Harmer
2.012
253317AC1-085 GEN4
Solar/Wind Harmer
9.716
946181AF1-283 GEN
Solar/Wind Harmer
15.086
252524AE2-267 GEN
Solar/Wind Harmer
1.431
25196608WSDLE5
Adder
7.789
252519AF1-045_GEN
Solar/Wind Harmer
3.263
25194608D.CRK4
Adder
1.463
253325AC1-069 GEN
Solar/Wind Harmer
0.909
252507AC2-088 GEN
Solar/Wind Harmer
1.407
958171AF2-111 GEN
Solar/Wind Harmer
17.831
25196008MFTGT1
Adder
0.956
270367AC2-061_GEN
Solar/Wind Harmer
2.237
270186AC1-089 GEN
Solar/Wind Harmer
4.121
972167AH1-666 GEN
Solar/Wind Harmer
5.363
276820AF1-078_GEN
Solar/Wind Harmer
1.057
339243AC2-075 GEN1
Solar/Wind Harmer
0.268
3429391JKCT 9G
Adder
4.439
970093AG2-073 GEN
Solar/Wind Harmer
2.549
960801AF2-371 GEN
Solar/Wind Helper
0.86
964871AG1-351 GEN
Solar/Wind Helper
0.594
25326109MON D
50/50
2.084
253370AE2-315 SEC1
50/50
3.066
25322209TAIT E
50/50
14.633
25322209TAIT E
50/50
14.305
253349AC2-067 GEN
Solar/Wind Harmer
2.483
253400AC2-068 GEN
Solar/Wind Harmer
0.998
25183208HLCRTG
Solar/Wind Harmer
5.467
25194408D.CRK1
Adder
6.73
25194508D.CRK3
Adder
1.258
252509AD1-136 GEN
Solar/Wind Harmer
0.201
962581AG1-107 GEN
Solar/Wind Harmer
3.863
961491AF2-440 GEN
Solar/Wind Harmer
1.605
25326509SID D
Adder
1.001
253378AE2-206_GEN
Solar/Wind Harmer
2.38
253415AE1-040 GEN
Solar/Wind Harmer
0.714
24728805RICHG1
Adder
2.347
24728905RICHG2
Adder
2.347
972043AH1-570 GEN
Solar/Wind Harmer
1.444
972045AH1-571 GEN
Solar/Wind Harmer
1.155
971125AH1-004 GEN
Solar/Wind Harmer
2.212
970107AG2-081 GEN
Solar/Wind Harmer
1.659
942891AE2-308 GEN
Solar/Wind Harmer
5.04
970883AG2-550 GEN
Solar/Wind Harmer
5.016
970885AG2-551 GEN
Solar/Wind Harmer
1.166
270383AD1-128 GEN
Solar/Wind Harmer
2.906
946101AF1-275 GEN
Solar/Wind Helper
0.84
270054AF2-122 C O1
Solar/Wind Helper
0.906
LAGNLTFEXP_LAGN->PJM
CLTF
3.736
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.581
TVALTFEXP_TVA->PJM
CLTF
1.94
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.406
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.915
MECLTFEXP_MEC->PJM
CLTF
3.243
SIGELTFEXP_SIGE->PJM
CLTF
0.182
CPLELTFEXP_CPLE->PJM
CLTF
0.211
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.723
NYPJM->LTFIMP_NY
CLTF
0.842
LGEELTFEXP_LGEE->PJM
CLTF
2.987
WECLTFEXP_WEC->PJM
CLTF
0.664

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#2085_05BEATTY 345_304C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2085_05BEATTY 345_304C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.98 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1226.82
MW Contribution:
4.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
2.823
253371AE2-315 SEC2
50/50
2.67
25322209TAIT E
50/50
0.661
25322309TAIT W
50/50
0.661
25326309TAIT D
50/50
1.511
253398AE2-221_GEN2
Solar/Wind Harmer
5.774
253316AC1-085 GEN3
Solar/Wind Harmer
9.029
946171AF1-282 GEN
Solar/Wind Harmer
10.784
252516AE2-318_GEN
Solar/Wind Harmer
8.328
25194608D.CRK4
Adder
1.356
252510AF1-249 C
Solar/Wind Harmer
0.342
253333AC1-068 GEN
Solar/Wind Harmer
0.849
25196808ZIMRHP
Adder
56.544
270222AC2-111 GEN
Solar/Wind Harmer
3.041
944031AF1-071 GEN
Solar/Wind Harmer
0.684
25196008MFTGT1
Adder
0.915
945681AF1-233 GEN
Solar/Wind Harmer
11.75
339221AD2-048_GEN
Solar/Wind Harmer
0.838
943111AE2-339 GEN
Solar/Wind Harmer
0.453
3429421JKCT 10G
Adder
4.135
3429241JKCT 3G
Adder
5.704
270520AE2-214 GEN
Solar/Wind Helper
4.219
270273AD2-016 GEN
Solar/Wind Helper
1.295
253372AE2-315 SEC3
50/50
2.67
253372AE2-315 SEC3
50/50
2.67
25322309TAIT W
50/50
0.67
963581AG1-207 GEN
50/50
12.089
25306009OHH W.
50/50
3.736
253406AD2-031_GEN
Solar/Wind Harmer
1.405
253433AC1-085 GEN1
Solar/Wind Harmer
5.731
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
241972AD1-140 GEN
Solar/Wind Harmer
4.493
25196408WSDLE3
Adder
7.43
25196308WSDLE2
Adder
7.365
25196208WSDLE1
Adder
7.346
25196708WSDLE6
Adder
7.328
25196508WSDLE4
Adder
7.143
253338AC1-165 GEN
Solar/Wind Harmer
0.881
253343AC1-166 GEN
Solar/Wind Harmer
0.881
25196108MFTGT2
Adder
1.009
25196108MFTGT2
Adder
0.937
972163AH1-664 GEN
Solar/Wind Harmer
6.153
972165AH1-665 GEN
Solar/Wind Harmer
4.923
339216AC1-074 GEN
Solar/Wind Harmer
0.923
971029AG2-637 GEN
Solar/Wind Harmer
7.591
270340AC2-060 GEN
Solar/Wind Harmer
1.502
3429211JKCT 2G
Adder
5.63
270543AE2-219 C
Solar/Wind Harmer
4.57
270356AE2-297 GEN
Solar/Wind Harmer
2.014
945631AF1-228 GEN
Solar/Wind Helper
6.053
241955AC1-078 GEN
Solar/Wind Helper
2.047
253370AE2-315 SEC1
50/50
2.823
253371AE2-315 SEC2
50/50
2.67
25322209TAIT E
50/50
0.653
25322309TAIT W
50/50
0.661
270518AE2-148 GEN
Solar/Wind Harmer
54.738
253303V4-073 C
Solar/Wind Harmer
0.154
253394AE2-221_GEN
Solar/Wind Harmer
5.774
960071AF2-298 GEN
Solar/Wind Harmer
1.849
253317AC1-085 GEN4
Solar/Wind Harmer
9.029
946181AF1-283 GEN
Solar/Wind Harmer
14.019
252524AE2-267 GEN
Solar/Wind Harmer
1.326
25196608WSDLE5
Adder
7.217
252519AF1-045_GEN
Solar/Wind Harmer
3.031
25194608D.CRK4
Adder
1.356
253325AC1-069 GEN
Solar/Wind Harmer
0.849
252507AC2-088 GEN
Solar/Wind Harmer
1.31
958171AF2-111 GEN
Solar/Wind Harmer
16.639
270367AC2-061_GEN
Solar/Wind Harmer
2.092
25196008MFTGT1
Adder
0.886
270186AC1-089 GEN
Solar/Wind Harmer
3.855
972167AH1-666 GEN
Solar/Wind Harmer
5.007
276820AF1-078_GEN
Solar/Wind Harmer
0.937
339243AC2-075 GEN1
Solar/Wind Harmer
0.25
3429391JKCT 9G
Adder
4.135
970093AG2-073 GEN
Solar/Wind Harmer
2.373
960801AF2-371 GEN
Solar/Wind Helper
0.879
964871AG1-351 GEN
Solar/Wind Helper
0.607
25326109MON D
50/50
1.913
253370AE2-315 SEC1
50/50
2.823
25322209TAIT E
50/50
13.451
25322209TAIT E
50/50
13.148
253349AC2-067 GEN
Solar/Wind Harmer
2.282
253400AC2-068 GEN
Solar/Wind Harmer
0.917
25183208HLCRTG
Solar/Wind Harmer
5.085
25194408D.CRK1
Adder
6.238
25194508D.CRK3
Adder
1.166
252509AD1-136 GEN
Solar/Wind Harmer
0.187
962581AG1-107 GEN
Solar/Wind Harmer
3.603
961491AF2-440 GEN
Solar/Wind Harmer
1.498
25326509SID D
Adder
0.898
253415AE1-040 GEN
Solar/Wind Harmer
0.682
253378AE2-206_GEN
Solar/Wind Harmer
2.109
24728805RICHG1
Adder
2.155
24728905RICHG2
Adder
2.155
972043AH1-570 GEN
Solar/Wind Harmer
1.346
972045AH1-571 GEN
Solar/Wind Harmer
1.077
971125AH1-004 GEN
Solar/Wind Harmer
2.06
970107AG2-081 GEN
Solar/Wind Harmer
1.545
942891AE2-308 GEN
Solar/Wind Harmer
4.694
970883AG2-550 GEN
Solar/Wind Harmer
4.57
970885AG2-551 GEN
Solar/Wind Harmer
1.063
270383AD1-128 GEN
Solar/Wind Harmer
2.651
946101AF1-275 GEN
Solar/Wind Helper
1.055
270054AF2-122 C O1
Solar/Wind Helper
0.766
LAGNLTFEXP_LAGN->PJM
CLTF
3.423
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.503
TVALTFEXP_TVA->PJM
CLTF
1.789
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.232
MECLTFEXP_MEC->PJM
CLTF
2.893
SIGELTFEXP_SIGE->PJM
CLTF
0.168
CPLELTFEXP_CPLE->PJM
CLTF
0.21
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.05
NYPJM->LTFIMP_NY
CLTF
0.777
LGEELTFEXP_LGEE->PJM
CLTF
2.766
WECLTFEXP_WEC->PJM
CLTF
0.582

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2430.97
MW Contribution:
3.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
26.903
24689505VACITY
50/50
3.164
943031AE2-326 GEN
Solar/Wind Harmer
3.912
962751AG1-124 GEN
Solar/Wind Harmer
6.205
960911AF2-382 GEN
Solar/Wind Harmer
4.078
971461AH1-227 GEN
Solar/Wind Harmer
2.687
972103AH1-617 GEN
Solar/Wind Harmer
9.709
972273AH1-721 GEN
Adder
50.356
24686405CER G5
Adder
4.71
970093AG2-073 GEN
Solar/Wind Harmer
3.273
970653AG2-424 GEN
Solar/Wind Harmer
0.386
270030AE2-140 GEN
Solar/Wind Harmer
7.666
970455AG2-298 GEN
Solar/Wind Harmer
1.477
3429391JKCT 9G
Adder
4.482
972167AH1-666 GEN
Solar/Wind Harmer
2.762
958171AF2-111 GEN
Solar/Wind Harmer
8.524
942481AE2-261 GEN
Solar/Wind Harmer
10.082
957381AF2-032 GEN
Solar/Wind Harmer
0.764
970193AG2-126 GEN
Solar/Wind Harmer
4.994
971993AH1-541 GEN
Solar/Wind Harmer
1.535
965931AG1-462 GEN
Solar/Wind Harmer
8.44
971087AG2-675 GEN
Solar/Wind Harmer
1.765
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.771
24728505AND G1
Adder
1.803
965091AG1-374 GEN
Solar/Wind Harmer
9.832
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.109
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.348
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
270367AC2-061_GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.482
959091AF2-200 GEN
Solar/Wind Harmer
6.475
252507AC2-088 GEN
Solar/Wind Harmer
0.146
274855GSG-6 ;RU
Solar/Wind Harmer
0.118
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276868AE1-113 GEN
Solar/Wind Harmer
0.643
274879MINONK ;1U
Solar/Wind Harmer
0.134
24386205FR-12G C
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
1.674
24735205WLF2G2
50/50
5.207
24728305BUCHG2
Adder
3.63
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.407
944971AF1-162 GEN
Solar/Wind Harmer
4.503
24723205RIVRG3
Adder
11.612
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
6.034
24686505CER G6
Adder
4.748
970653AG2-424 GEN
Solar/Wind Harmer
1.862
3429241JKCT 3G
Adder
6.43
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.003
943811AF1-049 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
38.065
945681AF1-233 GEN
Solar/Wind Harmer
6.517
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
0.167
25196008MFTGT1
Adder
0.654
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.116
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
25196808ZIMRHP
Adder
35.505
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.566
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.348
24735105WLF2G1
50/50
5.207
24734705WLF1G3
50/50
5.196
24734805WLF1G4
50/50
5.196
24734905WLF1G5
50/50
5.196
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.671
971313AH1-133 GEN
Solar/Wind Harmer
2.637
970281AG2-184 GEN
Solar/Wind Harmer
10.194
270399AC1-101 GEN
Solar/Wind Harmer
1.444
270400AC1-102 GEN
Solar/Wind Harmer
1.444
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
10.049
3429211JKCT 2G
Adder
6.347
339216AC1-074 GEN
Solar/Wind Harmer
0.095
972163AH1-664 GEN
Solar/Wind Harmer
3.863
972165AH1-665 GEN
Solar/Wind Harmer
3.094
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.131
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.131
946321AF1-296 GEN
Solar/Wind Harmer
1.85
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
274854TWINGROVE;U2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.109
276741O09 GEN1
Solar/Wind Harmer
0.116
972267AH1-718 GEN
Adder
1.953
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.424
971681AH1-341 GEN
Solar/Wind Harmer
5.242
274856ECOGROVE ;U1
Solar/Wind Harmer
0.076
274823ROCKFORD ;21
Adder
9.053
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.475
970169AG2-114 GEN
Solar/Wind Harmer
3.232
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276863AD2-134 GEN
Solar/Wind Harmer
0.058
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
25196508WSDLE4
Adder
3.893
274744AC1-111 GEN8
Adder
2.557
274746AC1-111 G10
Adder
2.557
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.499
970833AG2-524 GEN
Solar/Wind Harmer
2.333
274728ELWOOD EC;5P
Adder
7.484
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
274735ELWOOD EC;4P
Adder
7.484
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
960591AF2-350 GEN
Solar/Wind Harmer
3.162
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971611AH1-305 GEN
Solar/Wind Harmer
1.876
971985AH1-537 GEN
Solar/Wind Harmer
0.936
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
4.672
971609AH1-304 GEN
Solar/Wind Harmer
0.508
270543AE2-219 C
Solar/Wind Harmer
2.176
253406AD2-031_GEN
Solar/Wind Harmer
0.23
964611AG1-324 GEN
Solar/Wind Harmer
1.21
247536S-71 GEN
Solar/Wind Harmer
0.124
945581AF1-223 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
5.772
315616AA1-038_C
Solar/Wind Helper
1.809
3148463FAIRFLD
Solar/Wind Helper
0.399
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316258AE1-075 C
Solar/Wind Helper
0.181
316405AF2-144 C
Solar/Wind Helper
0.151
316164AC1-076 GEN
Solar/Wind Helper
0.62
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.113
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
25196608WSDLE5
Adder
3.933
274862TOP CROP ;2U
Solar/Wind Harmer
0.432
943121AE2-341 GEN
Solar/Wind Harmer
5.351
943591AF1-030 GEN
Solar/Wind Harmer
3.559
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.187
274729ELWOOD EC;1P
Adder
7.484
274730ELWOOD EC;6P
Adder
7.484
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
3.003
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.354
274766LEE CO EC;7U
Adder
4.297
963741AG1-226 GEN
Solar/Wind Harmer
7.714
970819AG2-516 GEN
Solar/Wind Harmer
3.898
274822ROCKFORD ;11
Adder
9.119
970569AG2-363 GEN
Solar/Wind Harmer
9.723
957471AF2-041 GEN
Solar/Wind Harmer
9.712
959081AF2-199 GEN
Solar/Wind Harmer
3.237
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.689
276882AE2-255 GEN
Solar/Wind Harmer
0.375
962781AG1-127 GEN
Solar/Wind Harmer
3.062
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
0.568
276805AD2-038 GEN
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.024
252516AE2-318_GEN
Solar/Wind Harmer
3.594
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
939401AE1-172 GEN
Solar/Wind Harmer
2.397
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
274745AC1-111 GEN9
Adder
2.557
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
274676JOLIET 29;8U
Adder
13.963
276903AD2-071 C
Solar/Wind Harmer
3.542
941551AE2-152 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.159
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.314
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.938
270594AE1-207 GEN
Solar/Wind Harmer
3.528
270032AE2-172
Solar/Wind Harmer
2.1
970825AG2-519 GEN
Solar/Wind Harmer
1.115
270005AE1-210 C O1
Solar/Wind Harmer
0.68
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.068
958381AF2-132 GEN
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.5
958861AF2-177 GEN
Solar/Wind Harmer
1.334
965651AG1-433 GEN
Solar/Wind Harmer
0.9
270024AE2-089 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
23583801GRNGAP
Solar/Wind Helper
2.128
316095T157 G97
Solar/Wind Helper
0.557
316075AC2-137 C
Solar/Wind Helper
0.18
316223AC1-118
Solar/Wind Helper
0.174
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
971277AH1-098 GEN
Solar/Wind Harmer
2.311
24728205BUCHG1
Adder
3.63
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
966021AG1-471 GEN
Solar/Wind Harmer
2.29
971485AH1-239 GEN
Solar/Wind Harmer
3.377
964781AG1-341 GEN
Solar/Wind Harmer
4.305
942891AE2-308 GEN
Solar/Wind Harmer
3.798
964571AG1-320 GEN
Solar/Wind Harmer
3.443
971125AH1-004 GEN
Solar/Wind Harmer
1.471
970107AG2-081 GEN
Solar/Wind Harmer
1.103
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.751
971587AH1-292 GEN
Solar/Wind Harmer
2.505
276916AD2-100_GEN
Solar/Wind Harmer
7.095
276911AD2-131_GEN
Solar/Wind Harmer
0.467
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.188
945391AF1-204 GEN
Solar/Wind Harmer
3.538
960611AF2-352 GEN
Solar/Wind Harmer
1.092
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.528
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274764LEE CO EC;5U
Adder
4.358
274765LEE CO EC;6U
Adder
4.358
274762LEE CO EC;3U
Adder
4.348
274763LEE CO EC;4U
Adder
4.307
970241AG2-163 GEN
Solar/Wind Harmer
1.901
938861AE1-114 GEN
Solar/Wind Harmer
1.845
972235AH1-702 GEN1
Adder
1.172
972236AH1-702 GEN2
Adder
1.019
971341AH1-150 GEN
Solar/Wind Harmer
6.475
971343AH1-151 GEN
Solar/Wind Harmer
6.475
252509AD1-136 GEN
Solar/Wind Harmer
0.016
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.643
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.815
25183208HLCRTG
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
25194508D.CRK3
Adder
0.65
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.064
274697ROCKY RD ;3P
Adder
1.389
958481AF2-142 GEN
Solar/Wind Harmer
4.795
24728805RICHG1
Adder
1.729
24728905RICHG2
Adder
1.729
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.01
276893AG1-478 C
Solar/Wind Harmer
0.212
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
0.184
276776AD2-060 GEN
Solar/Wind Harmer
0.337
958011AF2-095 GEN
Solar/Wind Harmer
4.553
970941AG2-585 GEN
Solar/Wind Harmer
1.739
926881AC1-175 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.41
970291AG2-192 GEN
Solar/Wind Harmer
0.189
971613AH1-306 GEN
Solar/Wind Harmer
1.512
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.712
270599AE1-208 GEN
Solar/Wind Harmer
2.854
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
3.108
970885AG2-551 GEN
Solar/Wind Harmer
1.036
964611AG1-324 GEN
Solar/Wind Harmer
0.233
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.205
960971AF2-388 GEN
Solar/Wind Harmer
1.8
965681AG1-436 GEN
Solar/Wind Harmer
3.818
965791AG1-447 GEN
Solar/Wind Harmer
2.8
942221AE2-234 GEN
Solar/Wind Harmer
1.218
970349AG2-230 GEN
Solar/Wind Harmer
4.536
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
237061AD1-155 GEN
Solar/Wind Helper
0.84
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238147AE2-230_GEN1
Solar/Wind Helper
0.214
238148AE2-230_GEN2
Solar/Wind Helper
0.214
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316312AB1-027
Solar/Wind Helper
0.234
316097T157 G90
Solar/Wind Helper
0.557
316045AC1-158 PL2
Solar/Wind Helper
2.117
316450AC1-158 RIC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.609
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
274887GEN-1.85
Solar/Wind Harmer
0.082
276843GEN-1.7
Solar/Wind Harmer
0.102
276806AD2-047 C O1
Solar/Wind Harmer
1.792
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
4.107
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970825AG2-519 GEN
Solar/Wind Harmer
2.365
270004AE1-209 GEN
Solar/Wind Harmer
0.68
946031AF1-268 GEN
Solar/Wind Harmer
2.979
964401AG1-302 GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
7.973
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.643
970191AG2-125 GEN
Solar/Wind Harmer
0.781
944531AF1-118 GEN
Solar/Wind Harmer
13.572
971347AH1-153 GEN
Solar/Wind Harmer
1.512
3147983MERCK5
Solar/Wind Helper
0.108
316192AB2-158 GEN
Solar/Wind Helper
0.989
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
3146776BUCKING
Solar/Wind Helper
0.05
238152AF2-075_GEN
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.173
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.959
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
6.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
6.744
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
270069AE2-166 C O1
Solar/Wind Harmer
10.375
971313AH1-133 GEN
Solar/Wind Harmer
5.363
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
2.889
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
970281AG2-184 GEN
Solar/Wind Harmer
18.909
971981AH1-535 GEN
Solar/Wind Harmer
5.838
971061AG2-657 GEN
Solar/Wind Harmer
5.362
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972163AH1-664 GEN
Solar/Wind Harmer
7.559
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
270356AE2-297 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.464
963841AG1-237 GEN
Solar/Wind Harmer
2.696
946321AF1-296 GEN
Solar/Wind Harmer
3.479
274854TWINGROVE;U2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.498
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
972267AH1-718 GEN
Adder
3.684
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
926823AC1-168 GEN
Solar/Wind Harmer
1.044
970169AG2-114 GEN
Solar/Wind Harmer
6.143
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
270263AC1-001 GEN
Solar/Wind Harmer
0.61
970073AG2-061 GEN
Solar/Wind Harmer
2.033
971029AG2-637 GEN
Solar/Wind Harmer
9.145
270543AE2-219 C
Solar/Wind Harmer
4.252
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
247536S-71 GEN
Solar/Wind Harmer
0.242
25306009OHH W.
Adder
2.5
971609AH1-304 GEN
Solar/Wind Harmer
0.988
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
964611AG1-324 GEN
Solar/Wind Harmer
2.357
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
12.886
958121AF2-106 GEN
Solar/Wind Harmer
0.001
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
941801AE2-185 GEN
Solar/Wind Harmer
7.447
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.535
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24686405CER G5
Adder
9.787
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
970093AG2-073 GEN
Solar/Wind Harmer
6.071
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.034
970455AG2-298 GEN
Solar/Wind Harmer
2.725
972167AH1-666 GEN
Solar/Wind Harmer
5.413
958171AF2-111 GEN
Solar/Wind Harmer
16.661
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
4.688
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
942481AE2-261 GEN
Solar/Wind Harmer
18.979
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
15.863
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
18.636
959611AF2-252 GEN
Solar/Wind Harmer
2.071
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
970571AG2-364 GEN
Solar/Wind Harmer
12.283
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946671AF1-331 GEN
Solar/Wind Harmer
0.653
270004AE1-209 GEN
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
4.603
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
276843GEN-1.7
Solar/Wind Harmer
0.195
276806AD2-047 C O1
Solar/Wind Harmer
3.42
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
3147312GRETNA
Solar/Wind Harmer
0.047
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
5.335
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
0.947
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
960001AF2-291 GEN
Solar/Wind Harmer
0
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
945681AF1-233 GEN
Solar/Wind Harmer
12.766
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
7.186
252510AF1-249 C
Solar/Wind Harmer
0.048
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
276621W2-048 GEN
Solar/Wind Harmer
0.315
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
253398AE2-221_GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24385905FR-11G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
970819AG2-516 GEN
Solar/Wind Harmer
7.371
970569AG2-363 GEN
Solar/Wind Harmer
18.425
274822ROCKFORD ;11
Adder
17.258
957471AF2-041 GEN
Solar/Wind Harmer
18.391
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
274745AC1-111 GEN9
Adder
4.865
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
941551AE2-152 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
7.838
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971277AH1-098 GEN
Solar/Wind Harmer
5.174
942671AE2-283 GEN
Solar/Wind Harmer
5.792
970913AG2-568 GEN
Solar/Wind Harmer
7.67
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
964571AG1-320 GEN
Solar/Wind Harmer
6.355
971125AH1-004 GEN
Solar/Wind Harmer
2.78
970107AG2-081 GEN
Solar/Wind Harmer
2.085
972043AH1-570 GEN
Solar/Wind Harmer
1.794
972045AH1-571 GEN
Solar/Wind Harmer
1.437
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
4.796
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276916AD2-100_GEN
Solar/Wind Harmer
13.351
276911AD2-131_GEN
Solar/Wind Harmer
0.879
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960201AF2-311 GEN
Solar/Wind Harmer
5.7
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
938861AE1-114 GEN
Solar/Wind Harmer
3.487
270383AD1-128 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
970885AG2-551 GEN
Solar/Wind Harmer
2.025
276893AG1-478 C
Solar/Wind Harmer
0.404
274674JOLIET 9 ;6U
Adder
13.36
270031AE2-169
Solar/Wind Harmer
3.328
270599AE1-208 GEN
Solar/Wind Harmer
5.547
276897AD1-100 C
Solar/Wind Harmer
15.124
964611AG1-324 GEN
Solar/Wind Harmer
0.453
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
276776AD2-060 GEN
Solar/Wind Harmer
0.644
958011AF2-095 GEN
Solar/Wind Harmer
8.691
970941AG2-585 GEN
Solar/Wind Harmer
3.319
270201AC2-176 GEN
Solar/Wind Harmer
0
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o AEP_P4_#2812_05TANNER 345_T2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2812_05TANNER 345_T2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.21 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:190.84
MW Contribution:
7.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
12.828
270543AE2-219 C
Solar/Wind Harmer
7.093
247536S-71 GEN
Solar/Wind Harmer
2.335
270222AC2-111 GEN
Solar/Wind Harmer
8.489
944031AF1-071 GEN
Solar/Wind Harmer
1.91
252510AF1-249 C
Solar/Wind Helper
0.214
24728805RICHG1
50/50
4.516
24728905RICHG2
50/50
4.516
970883AG2-550 GEN
Solar/Wind Harmer
7.093
970885AG2-551 GEN
Solar/Wind Harmer
1.65
270383AD1-128 GEN
Solar/Wind Harmer
4.089
247621Y3-024
Adder
0.125
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
0.309
TVALTFEXP_TVA->PJM
CLTF
0.091
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.232
MECLTFEXP_MEC->PJM
CLTF
0.666
SIGELTFEXP_SIGE->PJM
CLTF
0.017
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.897
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.05
WECLTFEXP_WEC->PJM
CLTF
0.178
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o DEOK_P4_1401_MIAMI FORT_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1401_MIAMI FORT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.08 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:190.6
MW Contribution:
7.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270222AC2-111 GEN
Solar/Wind Harmer
8.489
944031AF1-071 GEN
Solar/Wind Harmer
1.91
252510AF1-249 C
Solar/Wind Helper
0.214
971029AG2-637 GEN
Solar/Wind Harmer
12.828
270543AE2-219 C
Solar/Wind Harmer
7.093
247536S-71 GEN
Solar/Wind Harmer
2.335
24728805RICHG1
50/50
4.516
24728905RICHG2
50/50
4.516
970883AG2-550 GEN
Solar/Wind Harmer
7.093
970885AG2-551 GEN
Solar/Wind Harmer
1.65
270383AD1-128 GEN
Solar/Wind Harmer
4.089
247621Y3-024
Adder
0.125
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
0.312
TVALTFEXP_TVA->PJM
CLTF
0.093
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.663
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.239
MECLTFEXP_MEC->PJM
CLTF
0.668
SIGELTFEXP_SIGE->PJM
CLTF
0.017
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.918
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.05
WECLTFEXP_WEC->PJM
CLTF
0.178
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o DEOK_P_4561TODWOOD14562TODWOOD2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
DEOK_P_4561TODWOOD14562TODWOOD2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.44 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:184.13
MW Contribution:
6.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270222AC2-111 GEN
Solar/Wind Harmer
8.409
944031AF1-071 GEN
Solar/Wind Harmer
1.892
252510AF1-249 C
Solar/Wind Helper
0.216
971029AG2-637 GEN
Solar/Wind Harmer
12.591
270543AE2-219 C
Solar/Wind Harmer
6.927
247536S-71 GEN
Solar/Wind Harmer
2.264
24728805RICHG1
50/50
4.462
24728905RICHG2
50/50
4.462
970883AG2-550 GEN
Solar/Wind Harmer
6.927
970885AG2-551 GEN
Solar/Wind Harmer
1.611
270383AD1-128 GEN
Solar/Wind Harmer
3.959
247621Y3-024
Adder
0.121
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.059
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.144
LAGNLTFEXP_LAGN->PJM
CLTF
0.216
TVALTFEXP_TVA->PJM
CLTF
0.053
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.731
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.103
MECLTFEXP_MEC->PJM
CLTF
0.542
SIGELTFEXP_SIGE->PJM
CLTF
0.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.994
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.05
WECLTFEXP_WEC->PJM
CLTF
0.148
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o DEOK_P4_1301_TERMINAL_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1301_TERMINAL_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.5 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:180.68
MW Contribution:
6.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270222AC2-111 GEN
Solar/Wind Harmer
8.458
944031AF1-071 GEN
Solar/Wind Harmer
1.903
252510AF1-249 C
Solar/Wind Helper
0.2
24728805RICHG1
50/50
4.49
24728905RICHG2
50/50
4.49
970883AG2-550 GEN
Solar/Wind Harmer
6.984
970885AG2-551 GEN
Solar/Wind Harmer
1.624
270383AD1-128 GEN
Solar/Wind Harmer
3.993
247621Y3-024
Adder
0.122
971029AG2-637 GEN
Solar/Wind Harmer
12.687
270543AE2-219 C
Solar/Wind Harmer
6.984
247536S-71 GEN
Solar/Wind Harmer
2.285
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.066
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.166
LAGNLTFEXP_LAGN->PJM
CLTF
0.215
TVALTFEXP_TVA->PJM
CLTF
0.05
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.88
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.08
MECLTFEXP_MEC->PJM
CLTF
0.555
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.03
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.152
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o DAY_BLAZER_FB_??_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
DAY_BLAZER_FB_??_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.48 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:180.64
MW Contribution:
8.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270222AC2-111 GEN
Solar/Wind Harmer
8.968
944031AF1-071 GEN
Solar/Wind Harmer
2.018
252510AF1-249 C
Solar/Wind Helper
0.19
971029AG2-637 GEN
Solar/Wind Harmer
15.021
270543AE2-219 C
Solar/Wind Harmer
8.193
247536S-71 GEN
Solar/Wind Harmer
2.652
961761AG1-017 GEN
Solar/Wind Harmer
0.185
962031AG1-047 GEN
Solar/Wind Harmer
1.31
957741AF2-068 GEN
Solar/Wind Harmer
6.501
24728805RICHG1
50/50
4.956
24728905RICHG2
50/50
4.956
970883AG2-550 GEN
Solar/Wind Harmer
8.193
970885AG2-551 GEN
Solar/Wind Harmer
1.905
270383AD1-128 GEN
Solar/Wind Harmer
4.277
247621Y3-024
Adder
0.141
270201AC2-176 GEN
Solar/Wind Harmer
2.227
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.053
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
LAGNLTFEXP_LAGN->PJM
CLTF
0.261
TVALTFEXP_TVA->PJM
CLTF
0.075
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.022
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.016
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.182
MECLTFEXP_MEC->PJM
CLTF
0.584
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.306
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.158
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.039

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#15023_05JAY 138_E_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15023_05JAY 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.98 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:267.7
MW Contribution:
36.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
65.379
270543AE2-219 C
Solar/Wind Harmer
36.583
247536S-71 GEN
Solar/Wind Harmer
12.493
961761AG1-017 GEN
Solar/Wind Harmer
1.017
963791AG1-232 GEN
Solar/Wind Harmer
11.698
962031AG1-047 GEN
Solar/Wind Harmer
7.183
957741AF2-068 GEN
Solar/Wind Harmer
35.634
270024AE2-089 GEN
Solar/Wind Harmer
8.289
247621Y3-024
50/50
0.702
970883AG2-550 GEN
Solar/Wind Harmer
36.583
970885AG2-551 GEN
Solar/Wind Harmer
8.508
270201AC2-176 GEN
Solar/Wind Harmer
12.209
942221AE2-234 GEN
Solar/Wind Harmer
2.408
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.146
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.438
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.034
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.504
MECLTFEXP_MEC->PJM
CLTF
0.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.278
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.103
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.054

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#15176_05JAY 138_E2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15176_05JAY 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.25 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:265.84
MW Contribution:
36.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
65.236
270543AE2-219 C
Solar/Wind Harmer
36.464
247536S-71 GEN
Solar/Wind Harmer
12.435
961761AG1-017 GEN
Solar/Wind Harmer
1.005
963791AG1-232 GEN
Solar/Wind Harmer
11.627
962031AG1-047 GEN
Solar/Wind Harmer
7.099
957741AF2-068 GEN
Solar/Wind Harmer
35.219
270024AE2-089 GEN
Solar/Wind Harmer
8.209
247621Y3-024
50/50
0.702
970883AG2-550 GEN
Solar/Wind Harmer
36.464
970885AG2-551 GEN
Solar/Wind Harmer
8.48
270201AC2-176 GEN
Solar/Wind Harmer
12.067
942221AE2-234 GEN
Solar/Wind Harmer
2.427
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.146
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.436
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.515
MECLTFEXP_MEC->PJM
CLTF
0.306
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.294
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.103
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.054

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.82 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1646.06
MW Contribution:
4.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
5.428
270349AD2-093_GEN
Solar/Wind Harmer
4.875
270471AD2-092_GEN
Solar/Wind Harmer
4.875
938701AE1-092 GEN
Solar/Wind Harmer
21.99
270462AD2-086
Solar/Wind Harmer
6.492
946101AF1-275 GEN
Solar/Wind Harmer
1.347
241960AC2-195 GEN
Solar/Wind Harmer
2.356
253378AE2-206_GEN
Solar/Wind Harmer
2.404
25326509SID D
Adder
0.839
246937BC-WTG2
Solar/Wind Harmer
2.351
942801AE2-298 GEN
Solar/Wind Harmer
0.86
247607V1-011 GEN
Solar/Wind Harmer
2.234
270286AF1-227 GEN2
Solar/Wind Harmer
2.53
971995AH1-542 GEN
Solar/Wind Harmer
11.797
270391AF1-285 GEN3
Solar/Wind Harmer
1.209
270578AF1-285 GEN2
Solar/Wind Harmer
1.209
270317AD1-130_GEN
Solar/Wind Harmer
2.988
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270520AE2-214 GEN
Solar/Wind Harmer
5.389
241813AF1-122_GEN
Solar/Wind Harmer
4.164
971201AH1-060 GEN
Solar/Wind Harmer
1.301
962761AG1-125 GEN
Solar/Wind Harmer
20.895
970149AG2-104 GEN
Solar/Wind Harmer
12.903
970155AG2-107 GEN
Solar/Wind Harmer
9.111
246936BC-WTG1
Solar/Wind Harmer
2.351
270489AE1-102 GEN1
Solar/Wind Harmer
0.781
965421AG1-410 GEN
Solar/Wind Harmer
17.827
270297AD1-101 GEN
Solar/Wind Harmer
1.129
270258AD1-119 GEN
Solar/Wind Harmer
1.095
965011AG1-365 GEN
Solar/Wind Harmer
5.3
253333AC1-068 GEN
Solar/Wind Harmer
0.505
25326309TAIT D
Adder
0.527
270024AE2-089 GEN
Solar/Wind Harmer
2.197
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
965651AG1-433 GEN
Solar/Wind Harmer
2.534
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.279
958861AF2-177 GEN
Solar/Wind Harmer
5.03
945111AF1-176 GEN
Solar/Wind Harmer
8.149
957891AF2-083 GEN
Solar/Wind Harmer
6.834
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.271
943021AE2-325 GEN
Solar/Wind Harmer
1.652
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.221
270005AE1-210 C O1
Solar/Wind Harmer
2.395
970825AG2-519 GEN
Solar/Wind Harmer
0.919
274751CRETE EC ;1U
Adder
2.136
274754CRETE EC ;4U
Adder
2.136
972207SS24-0001
Solar/Wind Harmer
9.624
274773LINCOLN ;4U
Adder
2.707
274774LINCOLN ;5U
Adder
2.707
274723RIVER EC ;12
Adder
7.823
270055AF2-134 C O1
Solar/Wind Harmer
1.317
274812UNIV PK N;8U
Adder
2.178
270594AE1-207 GEN
Solar/Wind Harmer
5.904
270032AE2-172
Solar/Wind Harmer
2.022
274802UNIV PARK;5U
Adder
2.524
958381AF2-132 GEN
Solar/Wind Harmer
3.921
274676JOLIET 29;8U
Adder
13.196
270475AD2-096_GEN
50/50
7.81
270284AF1-227 GEN1
Solar/Wind Harmer
6.84
270287AF1-227 GEN3
Solar/Wind Harmer
2.53
942871AE2-306 GEN
Solar/Wind Harmer
0.907
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
942051AE2-217 GEN
Solar/Wind Harmer
13.98
970065AG2-057 GEN
Solar/Wind Harmer
0.651
276820AF1-078_GEN
Solar/Wind Harmer
1.068
962771AG1-126 GEN
Solar/Wind Harmer
20.895
970153AG2-106 GEN
Solar/Wind Harmer
9.111
246938BC-WTG3
Solar/Wind Harmer
2.392
270491AE1-102 GEN2
Solar/Wind Harmer
0.781
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.831
965021AG1-366 GEN
Solar/Wind Harmer
1.232
270044AE2-322 C
Solar/Wind Harmer
0.692
270518AE2-148 GEN
Solar/Wind Harmer
6.261
270588AE1-091_GEN
Solar/Wind Harmer
5.505
270043AE2-236 GEN
Solar/Wind Harmer
2.704
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
0.73
270063AE2-323 C
Solar/Wind Harmer
1.052
944531AF1-118 GEN
Solar/Wind Harmer
16.732
270541AE2-072 C
Solar/Wind Harmer
2.158
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
971347AH1-153 GEN
Solar/Wind Harmer
2.305
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.583
270505AE1-170 C O1
Solar/Wind Harmer
6.831
962031AG1-047 GEN
Solar/Wind Harmer
1.364
957741AF2-068 GEN
Solar/Wind Harmer
6.767
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.655
270004AE1-209 GEN
Solar/Wind Harmer
2.395
970825AG2-519 GEN
Solar/Wind Harmer
2.467
972231SS25-0005
Solar/Wind Harmer
4.147
972181SS23-001
Solar/Wind Harmer
2.592
274752CRETE EC ;2U
Adder
2.136
274753CRETE EC ;3U
Adder
2.136
274772LINCOLN ;3U
Adder
2.707
274724RIVER EC ;11
Adder
7.731
276164X3-005 C
Solar/Wind Harmer
0.306
274814UNIV PK N;0U
Adder
2.197
274807UNIV PK N;3U
Adder
2.192
274811UNIV PK N;7U
Adder
2.178
965461AG1-414 GEN
Solar/Wind Harmer
0.984
970289AG2-191 GEN
Solar/Wind Harmer
0.333
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.524
274826FISK ;BP
Adder
4.738
274887GEN-1.85
Solar/Wind Harmer
2.304
276772AC2-154 GEN
Solar/Wind Harmer
1.207
276843GEN-1.7
Solar/Wind Harmer
0.248
276806AD2-047 C O1
Solar/Wind Harmer
4.627
972038AH1-567 GEN2
Adder
0.158
964401AG1-302 GEN
Solar/Wind Harmer
3.921
972259AH1-714 GEN
Adder
8.237
274676JOLIET 29;8U
Adder
12.724
970707AG2-453 GEN
Solar/Wind Harmer
11.087
270036AE2-216 BAT
50/50
5.971
270223U2-072_GEN1
Solar/Wind Harmer
1.974
270224U2-072_GEN2
Solar/Wind Harmer
1.974
270227U2-072_GEN3
Solar/Wind Harmer
1.974
270228U2-072_GEN4
Solar/Wind Harmer
1.974
270231U2-072_GEN5
Solar/Wind Harmer
1.974
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
241973AD2-163_GEN1
Solar/Wind Harmer
1.951
241974AD2-163_GEN2
Solar/Wind Harmer
1.951
270302AB2-170 GEN
Solar/Wind Harmer
7.816
970179AG2-119 GEN
Solar/Wind Harmer
6.791
241955AC1-078 GEN
Solar/Wind Harmer
4.994
957201AF2-014 GEN
Solar/Wind Harmer
2.726
270435AC2-044 GEN
Solar/Wind Harmer
1.202
241972AD1-140 GEN
Solar/Wind Harmer
2.573
270007AE1-245 C
Solar/Wind Harmer
3.051
247521TR3_G114
Solar/Wind Harmer
1.861
270191TR4_S_V150
Solar/Wind Harmer
1.66
965051AG1-369 GEN
Solar/Wind Harmer
2.764
965041AG1-368 GEN
Solar/Wind Harmer
5.371
945631AF1-228 GEN
Solar/Wind Harmer
2.514
959331AF2-224 GEN
Solar/Wind Harmer
5.3
270404AC1-167 GEN
Solar/Wind Harmer
0.571
943861AF1-054 GEN
Solar/Wind Harmer
1.939
943851AF1-053 GEN
Solar/Wind Harmer
0.937
963791AG1-232 GEN
Solar/Wind Harmer
6.712
253338AC1-165 GEN
Solar/Wind Harmer
0.524
253343AC1-166 GEN
Solar/Wind Harmer
0.524
970031AG2-029 GEN
Solar/Wind Harmer
12.056
270071AF1-092 GEN
Solar/Wind Harmer
7.206
24729505KEY G4
Adder
3.077
25306009OHH W.
Adder
1.341
253372AE2-315 SEC3
Adder
0.879
253372AE2-315 SEC3
Adder
0.879
958711AF2-162 GEN
Solar/Wind Harmer
0.469
971771AH1-392 GEN
Solar/Wind Harmer
4.103
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.999
270526AF1-158 GEN
Solar/Wind Harmer
2.05
961761AG1-017 GEN
Solar/Wind Harmer
0.193
964611AG1-324 GEN
Solar/Wind Harmer
1.75
247536S-71 GEN
Solar/Wind Harmer
1.815
960681AF2-359 GEN
Solar/Wind Harmer
1.694
270543AE2-219 C
Solar/Wind Harmer
4.458
971029AG2-637 GEN
Solar/Wind Harmer
6.646
971549AH1-272 GEN
Solar/Wind Harmer
8.101
274775LINCOLN ;6U
Adder
2.707
274776LINCOLN ;7U
Adder
2.707
274777LINCOLN ;8U
Adder
2.707
970289AG2-191 GEN
Solar/Wind Harmer
0.824
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.358
960591AF2-350 GEN
Solar/Wind Harmer
4.325
274800UNIV PARK;3U
Adder
2.522
274801UNIV PARK;4U
Adder
2.522
972228AH1-698 GEN2
Adder
1.601
972227AH1-698 GEN1
Adder
1.127
274687WILL CNTY;4U
Adder
12.029
274687WILL CNTY;4U
Adder
12.029
274675JOLIET 29;7U
Adder
13.196
274675JOLIET 29;7U
Adder
12.725
270246TR4_N_V150
Solar/Wind Harmer
0.471
270247TR4_N_V136
Solar/Wind Harmer
0.471
942861AE2-305 GEN
Solar/Wind Harmer
3.928
25326109MON D
Adder
0.654
944231AF1-091 GEN
Solar/Wind Harmer
8.795
25322209TAIT E
Adder
4.684
25322209TAIT E
Adder
4.578
942221AE2-234 GEN
Solar/Wind Harmer
1.652
253349AC2-067 GEN
Solar/Wind Harmer
0.96
253400AC2-068 GEN
Solar/Wind Harmer
0.386
247620Y3-023
Adder
0.214
253370AE2-315 SEC1
Adder
0.929
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.068
970349AG2-230 GEN
Solar/Wind Harmer
6.915
961051AF2-396 GEN
Solar/Wind Harmer
7.218
961051AF2-396 GEN
Solar/Wind Harmer
3.357
247621Y3-024
Adder
0.109
270201AC2-176 GEN
Solar/Wind Harmer
2.319
253383AE2-342_GEN
Solar/Wind Harmer
0.398
964611AG1-324 GEN
Solar/Wind Harmer
0.235
965681AG1-436 GEN
Solar/Wind Harmer
5.605
965791AG1-447 GEN
Solar/Wind Harmer
2.868
270031AE2-169
Solar/Wind Harmer
3.645
270599AE1-208 GEN
Solar/Wind Harmer
3.645
970883AG2-550 GEN
Solar/Wind Harmer
4.458
970885AG2-551 GEN
Solar/Wind Harmer
1.037
274770LINCOLN ;1U
Adder
2.707
274771LINCOLN ;2U
Adder
2.707
270535AF1-215 GEN1
Solar/Wind Harmer
1.976
270536AF1-215 GEN2
Solar/Wind Harmer
1.976
274805UNIV PK N;1U
Adder
2.183
274808UNIV PK N;4U
Adder
2.168
970291AG2-192 GEN
Solar/Wind Harmer
0.564
970291AG2-192 GEN
Solar/Wind Harmer
0.182
270383AD1-128 GEN
Solar/Wind Harmer
2.644
274888KELLY CRK;1U
Solar/Wind Harmer
2.552
276776AD2-060 GEN
Solar/Wind Harmer
0.181
958011AF2-095 GEN
Solar/Wind Harmer
6.228
970941AG2-585 GEN
Solar/Wind Harmer
2.379
270054AF2-122 C O1
Solar/Wind Helper
0.827
LAGNLTFEXP_LAGN->PJM
CLTF
5.1
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.32
TVALTFEXP_TVA->PJM
CLTF
2.365
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.311
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.538
MECLTFEXP_MEC->PJM
CLTF
6.315
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.726
NYPJM->LTFIMP_NY
CLTF
1.312
LGEELTFEXP_LGEE->PJM
CLTF
2.29
WECLTFEXP_WEC->PJM
CLTF
1.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.97 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1563.59
MW Contribution:
4.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.957
270223U2-072_GEN1
Solar/Wind Harmer
1.969
270224U2-072_GEN2
Solar/Wind Harmer
1.969
270227U2-072_GEN3
Solar/Wind Harmer
1.969
270228U2-072_GEN4
Solar/Wind Harmer
1.969
270231U2-072_GEN5
Solar/Wind Harmer
1.969
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.945
241974AD2-163_GEN2
Solar/Wind Harmer
1.945
270302AB2-170 GEN
Solar/Wind Harmer
7.798
970179AG2-119 GEN
Solar/Wind Harmer
6.776
241955AC1-078 GEN
Solar/Wind Harmer
4.984
957201AF2-014 GEN
Solar/Wind Harmer
2.72
270435AC2-044 GEN
Solar/Wind Harmer
1.199
241972AD1-140 GEN
Solar/Wind Harmer
2.566
270007AE1-245 C
Solar/Wind Harmer
3.044
247521TR3_G114
Solar/Wind Harmer
1.857
270191TR4_S_V150
Solar/Wind Harmer
1.657
965051AG1-369 GEN
Solar/Wind Harmer
2.758
965041AG1-368 GEN
Solar/Wind Harmer
5.359
945631AF1-228 GEN
Solar/Wind Harmer
2.509
959331AF2-224 GEN
Solar/Wind Harmer
5.288
270404AC1-167 GEN
Solar/Wind Harmer
0.569
943861AF1-054 GEN
Solar/Wind Harmer
1.926
943851AF1-053 GEN
Solar/Wind Harmer
0.931
963791AG1-232 GEN
Solar/Wind Harmer
6.697
270286AF1-227 GEN2
Solar/Wind Harmer
2.524
971995AH1-542 GEN
Solar/Wind Harmer
11.77
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270317AD1-130_GEN
Solar/Wind Harmer
2.981
270485AE1-090_GEN
Solar/Wind Harmer
0.563
270520AE2-214 GEN
Solar/Wind Harmer
5.374
241813AF1-122_GEN
Solar/Wind Harmer
4.155
971201AH1-060 GEN
Solar/Wind Harmer
1.298
962761AG1-125 GEN
Solar/Wind Harmer
20.847
970149AG2-104 GEN
Solar/Wind Harmer
12.873
970155AG2-107 GEN
Solar/Wind Harmer
9.09
246936BC-WTG1
Solar/Wind Harmer
2.346
270489AE1-102 GEN1
Solar/Wind Harmer
0.78
965421AG1-410 GEN
Solar/Wind Harmer
17.787
270297AD1-101 GEN
Solar/Wind Harmer
1.127
270258AD1-119 GEN
Solar/Wind Harmer
1.093
965011AG1-365 GEN
Solar/Wind Harmer
5.288
253333AC1-068 GEN
Solar/Wind Harmer
0.504
25326309TAIT D
Adder
0.526
270024AE2-089 GEN
Solar/Wind Harmer
2.192
965651AG1-433 GEN
Solar/Wind Harmer
2.529
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.278
270475AD2-096_GEN
50/50
7.792
270284AF1-227 GEN1
Solar/Wind Harmer
6.824
270287AF1-227 GEN3
Solar/Wind Harmer
2.524
942871AE2-306 GEN
Solar/Wind Harmer
0.905
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
942051AE2-217 GEN
Solar/Wind Harmer
13.942
970065AG2-057 GEN
Solar/Wind Harmer
0.649
276820AF1-078_GEN
Solar/Wind Harmer
1.065
962771AG1-126 GEN
Solar/Wind Harmer
20.847
970153AG2-106 GEN
Solar/Wind Harmer
9.09
246938BC-WTG3
Solar/Wind Harmer
2.386
270491AE1-102 GEN2
Solar/Wind Harmer
0.78
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.827
965021AG1-366 GEN
Solar/Wind Harmer
1.23
270044AE2-322 C
Solar/Wind Harmer
0.691
270518AE2-148 GEN
Solar/Wind Harmer
6.249
270588AE1-091_GEN
Solar/Wind Harmer
5.494
270043AE2-236 GEN
Solar/Wind Harmer
2.698
253325AC1-069 GEN
Solar/Wind Harmer
0.504
960071AF2-298 GEN
Solar/Wind Harmer
0.728
270063AE2-323 C
Solar/Wind Harmer
1.049
944531AF1-118 GEN
Solar/Wind Harmer
16.696
270541AE2-072 C
Solar/Wind Harmer
2.153
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
971347AH1-153 GEN
Solar/Wind Harmer
2.3
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.577
270505AE1-170 C O1
Solar/Wind Harmer
6.816
962031AG1-047 GEN
Solar/Wind Harmer
1.361
957741AF2-068 GEN
Solar/Wind Harmer
6.753
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253343AC1-166 GEN
Solar/Wind Harmer
0.523
970031AG2-029 GEN
Solar/Wind Harmer
12.029
270071AF1-092 GEN
Solar/Wind Harmer
7.19
24729505KEY G4
Adder
3.07
25306009OHH W.
Adder
1.338
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.647
270004AE1-209 GEN
Solar/Wind Harmer
2.39
270466AD2-091
50/50
5.415
270349AD2-093_GEN
Solar/Wind Harmer
4.863
270471AD2-092_GEN
Solar/Wind Harmer
4.863
938701AE1-092 GEN
Solar/Wind Harmer
21.934
270462AD2-086
Solar/Wind Harmer
6.477
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.35
253378AE2-206_GEN
Solar/Wind Harmer
2.398
25326509SID D
Adder
0.837
246937BC-WTG2
Solar/Wind Harmer
2.346
942801AE2-298 GEN
Solar/Wind Harmer
0.858
247607V1-011 GEN
Solar/Wind Harmer
2.229
270246TR4_N_V150
Solar/Wind Harmer
0.47
270247TR4_N_V136
Solar/Wind Harmer
0.47
942861AE2-305 GEN
Solar/Wind Harmer
3.903
25326109MON D
Adder
0.652
944231AF1-091 GEN
Solar/Wind Harmer
8.776
25322209TAIT E
Adder
4.673
25322209TAIT E
Adder
4.568
942221AE2-234 GEN
Solar/Wind Harmer
1.648
253349AC2-067 GEN
Solar/Wind Harmer
0.958
253400AC2-068 GEN
Solar/Wind Harmer
0.385
247620Y3-023
Adder
0.214
944541AF1-119 GEN
Solar/Wind Harmer
1.937
960971AF2-388 GEN
Solar/Wind Harmer
5.057
253370AE2-315 SEC1
Adder
0.927
970349AG2-230 GEN
Solar/Wind Harmer
6.9
961051AF2-396 GEN
Solar/Wind Harmer
7.203
961051AF2-396 GEN
Solar/Wind Harmer
3.35
247621Y3-024
Adder
0.109
270201AC2-176 GEN
Solar/Wind Harmer
2.314
964611AG1-324 GEN
Solar/Wind Harmer
0.234
965681AG1-436 GEN
Solar/Wind Harmer
5.593
965791AG1-447 GEN
Solar/Wind Harmer
2.861
253383AE2-342_GEN
Solar/Wind Harmer
0.395
270031AE2-169
Solar/Wind Harmer
3.637
270599AE1-208 GEN
Solar/Wind Harmer
3.637
970883AG2-550 GEN
Solar/Wind Harmer
4.448
970885AG2-551 GEN
Solar/Wind Harmer
1.034
274770LINCOLN ;1U
Adder
2.701
274771LINCOLN ;2U
Adder
2.701
270535AF1-215 GEN1
Solar/Wind Harmer
1.972
270536AF1-215 GEN2
Solar/Wind Harmer
1.972
274805UNIV PK N;1U
Adder
2.178
274808UNIV PK N;4U
Adder
2.164
970291AG2-192 GEN
Solar/Wind Harmer
0.563
970291AG2-192 GEN
Solar/Wind Harmer
0.181
270383AD1-128 GEN
Solar/Wind Harmer
2.638
274888KELLY CRK;1U
Solar/Wind Harmer
2.547
276776AD2-060 GEN
Solar/Wind Harmer
0.181
958011AF2-095 GEN
Solar/Wind Harmer
6.215
970941AG2-585 GEN
Solar/Wind Harmer
2.374
270054AF2-122 C O1
Solar/Wind Helper
0.821
958861AF2-177 GEN
Solar/Wind Harmer
5.02
945111AF1-176 GEN
Solar/Wind Harmer
8.131
957891AF2-083 GEN
Solar/Wind Harmer
6.82
945371AF1-202 GEN
Solar/Wind Harmer
3.158
270449AD2-020 GEN
Solar/Wind Harmer
1.268
943021AE2-325 GEN
Solar/Wind Harmer
1.648
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.201
270005AE1-210 C O1
Solar/Wind Harmer
2.39
970825AG2-519 GEN
Solar/Wind Harmer
0.917
274751CRETE EC ;1U
Adder
2.131
274754CRETE EC ;4U
Adder
2.131
972207SS24-0001
Solar/Wind Harmer
9.604
274773LINCOLN ;4U
Adder
2.701
274774LINCOLN ;5U
Adder
2.701
274723RIVER EC ;12
Adder
7.806
270055AF2-134 C O1
Solar/Wind Harmer
1.315
274812UNIV PK N;8U
Adder
2.173
270594AE1-207 GEN
Solar/Wind Harmer
5.891
270032AE2-172
Solar/Wind Harmer
2.018
274802UNIV PARK;5U
Adder
2.519
958381AF2-132 GEN
Solar/Wind Harmer
3.912
958711AF2-162 GEN
Solar/Wind Harmer
0.468
253372AE2-315 SEC3
Adder
0.877
253372AE2-315 SEC3
Adder
0.877
971771AH1-392 GEN
Solar/Wind Harmer
4.095
945581AF1-223 GEN
Solar/Wind Harmer
2.053
944161AF1-084 GEN
Solar/Wind Harmer
0.997
270526AF1-158 GEN
Solar/Wind Harmer
2.045
961761AG1-017 GEN
Solar/Wind Harmer
0.193
964611AG1-324 GEN
Solar/Wind Harmer
1.747
247536S-71 GEN
Solar/Wind Harmer
1.811
960681AF2-359 GEN
Solar/Wind Harmer
1.691
270543AE2-219 C
Solar/Wind Harmer
4.448
971029AG2-637 GEN
Solar/Wind Harmer
6.632
971549AH1-272 GEN
Solar/Wind Harmer
8.084
274775LINCOLN ;6U
Adder
2.701
274776LINCOLN ;7U
Adder
2.701
274777LINCOLN ;8U
Adder
2.701
970289AG2-191 GEN
Solar/Wind Harmer
0.823
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.351
960591AF2-350 GEN
Solar/Wind Harmer
4.316
274800UNIV PARK;3U
Adder
2.516
274801UNIV PARK;4U
Adder
2.516
972228AH1-698 GEN2
Adder
1.597
972227AH1-698 GEN1
Adder
1.125
970825AG2-519 GEN
Solar/Wind Harmer
2.462
972231SS25-0005
Solar/Wind Harmer
4.138
972181SS23-001
Solar/Wind Harmer
2.586
274752CRETE EC ;2U
Adder
2.131
274753CRETE EC ;3U
Adder
2.131
274772LINCOLN ;3U
Adder
2.701
274724RIVER EC ;11
Adder
7.714
276164X3-005 C
Solar/Wind Harmer
0.305
274814UNIV PK N;0U
Adder
2.192
274807UNIV PK N;3U
Adder
2.187
274811UNIV PK N;7U
Adder
2.173
965461AG1-414 GEN
Solar/Wind Harmer
0.982
970289AG2-191 GEN
Solar/Wind Harmer
0.332
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.519
274826FISK ;BP
Adder
4.728
274887GEN-1.85
Solar/Wind Harmer
2.299
276772AC2-154 GEN
Solar/Wind Harmer
1.204
276843GEN-1.7
Solar/Wind Harmer
0.247
276806AD2-047 C O1
Solar/Wind Harmer
4.617
972038AH1-567 GEN2
Adder
0.157
964401AG1-302 GEN
Solar/Wind Harmer
3.912
972259AH1-714 GEN
Adder
8.22
970707AG2-453 GEN
Solar/Wind Harmer
11.064
LAGNLTFEXP_LAGN->PJM
CLTF
5.09
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.316
TVALTFEXP_TVA->PJM
CLTF
2.361
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.519
MECLTFEXP_MEC->PJM
CLTF
6.302
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.643
NYPJM->LTFIMP_NY
CLTF
1.31
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.584
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.88 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1562.23
MW Contribution:
4.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.954
270223U2-072_GEN1
Solar/Wind Harmer
1.968
270224U2-072_GEN2
Solar/Wind Harmer
1.968
270227U2-072_GEN3
Solar/Wind Harmer
1.968
270228U2-072_GEN4
Solar/Wind Harmer
1.968
270231U2-072_GEN5
Solar/Wind Harmer
1.968
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
270302AB2-170 GEN
Solar/Wind Harmer
7.794
970179AG2-119 GEN
Solar/Wind Harmer
6.772
241955AC1-078 GEN
Solar/Wind Harmer
4.982
957201AF2-014 GEN
Solar/Wind Harmer
2.718
270435AC2-044 GEN
Solar/Wind Harmer
1.199
241972AD1-140 GEN
Solar/Wind Harmer
2.564
270007AE1-245 C
Solar/Wind Harmer
3.043
247521TR3_G114
Solar/Wind Harmer
1.856
270191TR4_S_V150
Solar/Wind Harmer
1.656
965051AG1-369 GEN
Solar/Wind Harmer
2.757
965041AG1-368 GEN
Solar/Wind Harmer
5.357
945631AF1-228 GEN
Solar/Wind Harmer
2.508
959331AF2-224 GEN
Solar/Wind Harmer
5.285
270404AC1-167 GEN
Solar/Wind Harmer
0.569
943861AF1-054 GEN
Solar/Wind Harmer
1.923
943851AF1-053 GEN
Solar/Wind Harmer
0.929
963791AG1-232 GEN
Solar/Wind Harmer
6.694
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253343AC1-166 GEN
Solar/Wind Harmer
0.523
970031AG2-029 GEN
Solar/Wind Harmer
12.023
270071AF1-092 GEN
Solar/Wind Harmer
7.187
24729505KEY G4
Adder
3.068
25306009OHH W.
Adder
1.337
958711AF2-162 GEN
Solar/Wind Harmer
0.468
253372AE2-315 SEC3
Adder
0.876
253372AE2-315 SEC3
Adder
0.876
971771AH1-392 GEN
Solar/Wind Harmer
4.093
945581AF1-223 GEN
Solar/Wind Harmer
2.052
944161AF1-084 GEN
Solar/Wind Harmer
0.996
270526AF1-158 GEN
Solar/Wind Harmer
2.044
961761AG1-017 GEN
Solar/Wind Harmer
0.193
964611AG1-324 GEN
Solar/Wind Harmer
1.746
247536S-71 GEN
Solar/Wind Harmer
1.81
960681AF2-359 GEN
Solar/Wind Harmer
1.69
270543AE2-219 C
Solar/Wind Harmer
4.446
971029AG2-637 GEN
Solar/Wind Harmer
6.628
971549AH1-272 GEN
Solar/Wind Harmer
8.08
274775LINCOLN ;6U
Adder
2.7
274776LINCOLN ;7U
Adder
2.7
274777LINCOLN ;8U
Adder
2.7
970289AG2-191 GEN
Solar/Wind Harmer
0.822
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.349
274800UNIV PARK;3U
Adder
2.515
274801UNIV PARK;4U
Adder
2.515
960591AF2-350 GEN
Solar/Wind Harmer
4.314
972228AH1-698 GEN2
Adder
1.596
972227AH1-698 GEN1
Adder
1.124
270286AF1-227 GEN2
Solar/Wind Harmer
2.523
971995AH1-542 GEN
Solar/Wind Harmer
11.763
270391AF1-285 GEN3
Solar/Wind Harmer
1.205
270578AF1-285 GEN2
Solar/Wind Harmer
1.205
270317AD1-130_GEN
Solar/Wind Harmer
2.98
270485AE1-090_GEN
Solar/Wind Harmer
0.563
270520AE2-214 GEN
Solar/Wind Harmer
5.371
241813AF1-122_GEN
Solar/Wind Harmer
4.152
971201AH1-060 GEN
Solar/Wind Harmer
1.298
962761AG1-125 GEN
Solar/Wind Harmer
20.836
970149AG2-104 GEN
Solar/Wind Harmer
12.866
970155AG2-107 GEN
Solar/Wind Harmer
9.086
246936BC-WTG1
Solar/Wind Harmer
2.344
270489AE1-102 GEN1
Solar/Wind Harmer
0.779
965421AG1-410 GEN
Solar/Wind Harmer
17.778
270297AD1-101 GEN
Solar/Wind Harmer
1.126
270258AD1-119 GEN
Solar/Wind Harmer
1.092
965011AG1-365 GEN
Solar/Wind Harmer
5.285
253333AC1-068 GEN
Solar/Wind Harmer
0.504
25326309TAIT D
Adder
0.525
270024AE2-089 GEN
Solar/Wind Harmer
2.191
965651AG1-433 GEN
Solar/Wind Harmer
2.527
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.278
958861AF2-177 GEN
Solar/Wind Harmer
5.017
945111AF1-176 GEN
Solar/Wind Harmer
8.127
957891AF2-083 GEN
Solar/Wind Harmer
6.816
945371AF1-202 GEN
Solar/Wind Harmer
3.157
270449AD2-020 GEN
Solar/Wind Harmer
1.268
943021AE2-325 GEN
Solar/Wind Harmer
1.648
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.197
270005AE1-210 C O1
Solar/Wind Harmer
2.388
970825AG2-519 GEN
Solar/Wind Harmer
0.916
274751CRETE EC ;1U
Adder
2.13
274754CRETE EC ;4U
Adder
2.13
972207SS24-0001
Solar/Wind Harmer
9.599
274773LINCOLN ;4U
Adder
2.7
274774LINCOLN ;5U
Adder
2.7
274723RIVER EC ;12
Adder
7.802
270055AF2-134 C O1
Solar/Wind Harmer
1.314
274812UNIV PK N;8U
Adder
2.172
270594AE1-207 GEN
Solar/Wind Harmer
5.888
270032AE2-172
Solar/Wind Harmer
2.017
274802UNIV PARK;5U
Adder
2.518
958381AF2-132 GEN
Solar/Wind Harmer
3.91
270475AD2-096_GEN
50/50
7.787
270284AF1-227 GEN1
Solar/Wind Harmer
6.82
270287AF1-227 GEN3
Solar/Wind Harmer
2.523
942871AE2-306 GEN
Solar/Wind Harmer
0.904
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
942051AE2-217 GEN
Solar/Wind Harmer
13.933
970065AG2-057 GEN
Solar/Wind Harmer
0.649
276820AF1-078_GEN
Solar/Wind Harmer
1.065
962771AG1-126 GEN
Solar/Wind Harmer
20.836
970153AG2-106 GEN
Solar/Wind Harmer
9.086
246938BC-WTG3
Solar/Wind Harmer
2.385
270491AE1-102 GEN2
Solar/Wind Harmer
0.779
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.826
965021AG1-366 GEN
Solar/Wind Harmer
1.229
270044AE2-322 C
Solar/Wind Harmer
0.691
270518AE2-148 GEN
Solar/Wind Harmer
6.247
270588AE1-091_GEN
Solar/Wind Harmer
5.492
270043AE2-236 GEN
Solar/Wind Harmer
2.697
253325AC1-069 GEN
Solar/Wind Harmer
0.504
960071AF2-298 GEN
Solar/Wind Harmer
0.728
270063AE2-323 C
Solar/Wind Harmer
1.049
944531AF1-118 GEN
Solar/Wind Harmer
16.688
270541AE2-072 C
Solar/Wind Harmer
2.152
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
971347AH1-153 GEN
Solar/Wind Harmer
2.299
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.576
270505AE1-170 C O1
Solar/Wind Harmer
6.813
962031AG1-047 GEN
Solar/Wind Harmer
1.36
957741AF2-068 GEN
Solar/Wind Harmer
6.749
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.645
270004AE1-209 GEN
Solar/Wind Harmer
2.388
970825AG2-519 GEN
Solar/Wind Harmer
2.461
972231SS25-0005
Solar/Wind Harmer
4.136
972181SS23-001
Solar/Wind Harmer
2.585
274752CRETE EC ;2U
Adder
2.13
274753CRETE EC ;3U
Adder
2.13
274772LINCOLN ;3U
Adder
2.7
274724RIVER EC ;11
Adder
7.711
276164X3-005 C
Solar/Wind Harmer
0.305
274814UNIV PK N;0U
Adder
2.191
274807UNIV PK N;3U
Adder
2.186
274811UNIV PK N;7U
Adder
2.172
965461AG1-414 GEN
Solar/Wind Harmer
0.981
970289AG2-191 GEN
Solar/Wind Harmer
0.332
274803UNIV PARK;6U
Adder
2.518
247642Z2-115 C
Solar/Wind Harmer
0.028
274826FISK ;BP
Adder
4.726
972038AH1-567 GEN2
Adder
0.157
274887GEN-1.85
Solar/Wind Harmer
2.298
276772AC2-154 GEN
Solar/Wind Harmer
1.204
276843GEN-1.7
Solar/Wind Harmer
0.247
276806AD2-047 C O1
Solar/Wind Harmer
4.615
964401AG1-302 GEN
Solar/Wind Harmer
3.91
972259AH1-714 GEN
Adder
8.216
970707AG2-453 GEN
Solar/Wind Harmer
11.058
270466AD2-091
50/50
5.413
270349AD2-093_GEN
Solar/Wind Harmer
4.86
270471AD2-092_GEN
Solar/Wind Harmer
4.86
938701AE1-092 GEN
Solar/Wind Harmer
21.921
270462AD2-086
Solar/Wind Harmer
6.473
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.349
253378AE2-206_GEN
Solar/Wind Harmer
2.397
25326509SID D
Adder
0.837
246937BC-WTG2
Solar/Wind Harmer
2.344
942801AE2-298 GEN
Solar/Wind Harmer
0.858
247607V1-011 GEN
Solar/Wind Harmer
2.227
270246TR4_N_V150
Solar/Wind Harmer
0.469
270247TR4_N_V136
Solar/Wind Harmer
0.469
942861AE2-305 GEN
Solar/Wind Harmer
3.897
25326109MON D
Adder
0.652
944231AF1-091 GEN
Solar/Wind Harmer
8.771
25322209TAIT E
Adder
4.67
25322209TAIT E
Adder
4.565
942221AE2-234 GEN
Solar/Wind Harmer
1.648
253349AC2-067 GEN
Solar/Wind Harmer
0.957
253400AC2-068 GEN
Solar/Wind Harmer
0.385
247620Y3-023
Adder
0.214
944541AF1-119 GEN
Solar/Wind Harmer
1.936
960971AF2-388 GEN
Solar/Wind Harmer
5.055
253370AE2-315 SEC1
Adder
0.926
970349AG2-230 GEN
Solar/Wind Harmer
6.897
961051AF2-396 GEN
Solar/Wind Harmer
7.199
961051AF2-396 GEN
Solar/Wind Harmer
3.348
247621Y3-024
Adder
0.109
270201AC2-176 GEN
Solar/Wind Harmer
2.313
964611AG1-324 GEN
Solar/Wind Harmer
0.234
965681AG1-436 GEN
Solar/Wind Harmer
5.59
965791AG1-447 GEN
Solar/Wind Harmer
2.86
270031AE2-169
Solar/Wind Harmer
3.636
270599AE1-208 GEN
Solar/Wind Harmer
3.636
253383AE2-342_GEN
Solar/Wind Harmer
0.394
970883AG2-550 GEN
Solar/Wind Harmer
4.446
970885AG2-551 GEN
Solar/Wind Harmer
1.034
274770LINCOLN ;1U
Adder
2.7
274771LINCOLN ;2U
Adder
2.7
270535AF1-215 GEN1
Solar/Wind Harmer
1.971
270536AF1-215 GEN2
Solar/Wind Harmer
1.971
274805UNIV PK N;1U
Adder
2.177
274808UNIV PK N;4U
Adder
2.163
970291AG2-192 GEN
Solar/Wind Harmer
0.562
970291AG2-192 GEN
Solar/Wind Harmer
0.181
270383AD1-128 GEN
Solar/Wind Harmer
2.637
274888KELLY CRK;1U
Solar/Wind Harmer
2.545
276776AD2-060 GEN
Solar/Wind Harmer
0.181
958011AF2-095 GEN
Solar/Wind Harmer
6.212
970941AG2-585 GEN
Solar/Wind Harmer
2.372
270054AF2-122 C O1
Solar/Wind Helper
0.82
LAGNLTFEXP_LAGN->PJM
CLTF
5.087
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.315
TVALTFEXP_TVA->PJM
CLTF
2.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.165
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.515
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.624
NYPJM->LTFIMP_NY
CLTF
1.309
LGEELTFEXP_LGEE->PJM
CLTF
2.284
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1484.58
MW Contribution:
4.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.928
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.959
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.933
241974AD2-163_GEN2
Solar/Wind Harmer
1.933
270302AB2-170 GEN
Solar/Wind Harmer
7.76
970179AG2-119 GEN
Solar/Wind Harmer
6.743
241955AC1-078 GEN
Solar/Wind Harmer
4.963
957201AF2-014 GEN
Solar/Wind Harmer
2.707
270435AC2-044 GEN
Solar/Wind Harmer
1.194
241972AD1-140 GEN
Solar/Wind Harmer
2.551
270007AE1-245 C
Solar/Wind Harmer
3.03
247521TR3_G114
Solar/Wind Harmer
1.848
270191TR4_S_V150
Solar/Wind Harmer
1.649
965051AG1-369 GEN
Solar/Wind Harmer
2.745
965041AG1-368 GEN
Solar/Wind Harmer
5.334
945631AF1-228 GEN
Solar/Wind Harmer
2.5
959331AF2-224 GEN
Solar/Wind Harmer
5.263
270404AC1-167 GEN
Solar/Wind Harmer
0.567
963791AG1-232 GEN
Solar/Wind Harmer
6.667
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
253338AC1-165 GEN
Solar/Wind Harmer
0.521
253343AC1-166 GEN
Solar/Wind Harmer
0.521
970031AG2-029 GEN
Solar/Wind Harmer
11.974
270071AF1-092 GEN
Solar/Wind Harmer
7.157
24729505KEY G4
Adder
3.056
25306009OHH W.
Adder
1.331
958711AF2-162 GEN
Solar/Wind Harmer
0.466
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
971771AH1-392 GEN
Solar/Wind Harmer
4.076
945581AF1-223 GEN
Solar/Wind Harmer
2.044
944161AF1-084 GEN
Solar/Wind Harmer
0.992
270526AF1-158 GEN
Solar/Wind Harmer
2.036
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
971995AH1-542 GEN
Solar/Wind Harmer
11.711
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270317AD1-130_GEN
Solar/Wind Harmer
2.967
270485AE1-090_GEN
Solar/Wind Harmer
0.56
270520AE2-214 GEN
Solar/Wind Harmer
5.342
241813AF1-122_GEN
Solar/Wind Harmer
4.135
971201AH1-060 GEN
Solar/Wind Harmer
1.292
962761AG1-125 GEN
Solar/Wind Harmer
20.746
970149AG2-104 GEN
Solar/Wind Harmer
12.811
970155AG2-107 GEN
Solar/Wind Harmer
9.046
246936BC-WTG1
Solar/Wind Harmer
2.335
270489AE1-102 GEN1
Solar/Wind Harmer
0.776
965421AG1-410 GEN
Solar/Wind Harmer
17.703
270297AD1-101 GEN
Solar/Wind Harmer
1.121
270258AD1-119 GEN
Solar/Wind Harmer
1.088
270475AD2-096_GEN
50/50
7.753
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
942051AE2-217 GEN
Solar/Wind Harmer
13.86
970065AG2-057 GEN
Solar/Wind Harmer
0.646
965011AG1-365 GEN
Solar/Wind Harmer
5.263
253333AC1-068 GEN
Solar/Wind Harmer
0.503
25326309TAIT D
Adder
0.523
270024AE2-089 GEN
Solar/Wind Harmer
2.182
965651AG1-433 GEN
Solar/Wind Harmer
2.517
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.277
958861AF2-177 GEN
Solar/Wind Harmer
4.997
945111AF1-176 GEN
Solar/Wind Harmer
8.094
957891AF2-083 GEN
Solar/Wind Harmer
6.788
945371AF1-202 GEN
Solar/Wind Harmer
3.144
270449AD2-020 GEN
Solar/Wind Harmer
1.263
943021AE2-325 GEN
Solar/Wind Harmer
1.641
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.16
270005AE1-210 C O1
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
0.913
274751CRETE EC ;1U
Adder
2.121
274754CRETE EC ;4U
Adder
2.121
972207SS24-0001
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
2.689
274774LINCOLN ;5U
Adder
2.689
274723RIVER EC ;12
Adder
7.77
270055AF2-134 C O1
Solar/Wind Harmer
1.309
274812UNIV PK N;8U
Adder
2.163
270594AE1-207 GEN
Solar/Wind Harmer
5.865
270032AE2-172
Solar/Wind Harmer
2.008
274802UNIV PARK;5U
Adder
2.508
276820AF1-078_GEN
Solar/Wind Harmer
1.059
962771AG1-126 GEN
Solar/Wind Harmer
20.746
970153AG2-106 GEN
Solar/Wind Harmer
9.046
246938BC-WTG3
Solar/Wind Harmer
2.375
270491AE1-102 GEN2
Solar/Wind Harmer
0.776
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.818
965021AG1-366 GEN
Solar/Wind Harmer
1.224
270044AE2-322 C
Solar/Wind Harmer
0.688
270518AE2-148 GEN
Solar/Wind Harmer
6.224
270588AE1-091_GEN
Solar/Wind Harmer
5.471
270043AE2-236 GEN
Solar/Wind Harmer
2.686
253325AC1-069 GEN
Solar/Wind Harmer
0.503
960071AF2-298 GEN
Solar/Wind Harmer
0.725
270063AE2-323 C
Solar/Wind Harmer
1.045
944531AF1-118 GEN
Solar/Wind Harmer
16.62
270541AE2-072 C
Solar/Wind Harmer
2.143
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
971347AH1-153 GEN
Solar/Wind Harmer
2.29
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.565
270505AE1-170 C O1
Solar/Wind Harmer
6.785
962031AG1-047 GEN
Solar/Wind Harmer
1.355
957741AF2-068 GEN
Solar/Wind Harmer
6.722
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.631
270004AE1-209 GEN
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
2.451
972231SS25-0005
Solar/Wind Harmer
4.119
972181SS23-001
Solar/Wind Harmer
2.574
274752CRETE EC ;2U
Adder
2.121
274753CRETE EC ;3U
Adder
2.121
274772LINCOLN ;3U
Adder
2.689
274724RIVER EC ;11
Adder
7.679
276164X3-005 C
Solar/Wind Harmer
0.304
274814UNIV PK N;0U
Adder
2.182
274807UNIV PK N;3U
Adder
2.178
274811UNIV PK N;7U
Adder
2.163
965461AG1-414 GEN
Solar/Wind Harmer
0.977
970289AG2-191 GEN
Solar/Wind Harmer
0.331
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.508
961761AG1-017 GEN
Solar/Wind Harmer
0.192
964611AG1-324 GEN
Solar/Wind Harmer
1.739
247536S-71 GEN
Solar/Wind Harmer
1.803
960681AF2-359 GEN
Solar/Wind Harmer
1.683
270543AE2-219 C
Solar/Wind Harmer
4.428
971029AG2-637 GEN
Solar/Wind Harmer
6.602
971549AH1-272 GEN
Solar/Wind Harmer
8.047
274775LINCOLN ;6U
Adder
2.689
274776LINCOLN ;7U
Adder
2.689
274777LINCOLN ;8U
Adder
2.689
970289AG2-191 GEN
Solar/Wind Harmer
0.819
972037AH1-567 GEN1
Adder
0.079
270466AD2-091
50/50
5.389
270349AD2-093_GEN
Solar/Wind Harmer
4.839
270471AD2-092_GEN
Solar/Wind Harmer
4.839
938701AE1-092 GEN
Solar/Wind Harmer
21.815
270462AD2-086
Solar/Wind Harmer
6.445
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.339
253378AE2-206_GEN
Solar/Wind Harmer
2.385
25326509SID D
Adder
0.833
246937BC-WTG2
Solar/Wind Harmer
2.335
942801AE2-298 GEN
Solar/Wind Harmer
0.854
247607V1-011 GEN
Solar/Wind Harmer
2.218
270246TR4_N_V150
Solar/Wind Harmer
0.468
270247TR4_N_V136
Solar/Wind Harmer
0.468
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.649
944231AF1-091 GEN
Solar/Wind Harmer
8.735
25322209TAIT E
Adder
4.65
25322209TAIT E
Adder
4.546
942221AE2-234 GEN
Solar/Wind Harmer
1.641
253349AC2-067 GEN
Solar/Wind Harmer
0.953
253400AC2-068 GEN
Solar/Wind Harmer
0.383
247620Y3-023
Adder
0.213
944541AF1-119 GEN
Solar/Wind Harmer
1.928
960971AF2-388 GEN
Solar/Wind Harmer
5.034
253370AE2-315 SEC1
Adder
0.922
970349AG2-230 GEN
Solar/Wind Harmer
6.869
961051AF2-396 GEN
Solar/Wind Harmer
7.17
961051AF2-396 GEN
Solar/Wind Harmer
3.335
247621Y3-024
Adder
0.108
270201AC2-176 GEN
Solar/Wind Harmer
2.303
964611AG1-324 GEN
Solar/Wind Harmer
0.233
965681AG1-436 GEN
Solar/Wind Harmer
5.567
965791AG1-447 GEN
Solar/Wind Harmer
2.848
270031AE2-169
Solar/Wind Harmer
3.621
270599AE1-208 GEN
Solar/Wind Harmer
3.621
970883AG2-550 GEN
Solar/Wind Harmer
4.428
970885AG2-551 GEN
Solar/Wind Harmer
1.03
253383AE2-342_GEN
Solar/Wind Harmer
0.387
274770LINCOLN ;1U
Adder
2.689
274771LINCOLN ;2U
Adder
2.689
270535AF1-215 GEN1
Solar/Wind Harmer
1.963
270536AF1-215 GEN2
Solar/Wind Harmer
1.963
274805UNIV PK N;1U
Adder
2.168
274808UNIV PK N;4U
Adder
2.154
970291AG2-192 GEN
Solar/Wind Harmer
0.56
970291AG2-192 GEN
Solar/Wind Harmer
0.18
270383AD1-128 GEN
Solar/Wind Harmer
2.627
270054AF2-122 C O1
Solar/Wind Helper
0.81
LAGNLTFEXP_LAGN->PJM
CLTF
5.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.308
TVALTFEXP_TVA->PJM
CLTF
2.351
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.48
MECLTFEXP_MEC->PJM
CLTF
6.274
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.337
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.469
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.276
WECLTFEXP_WEC->PJM
CLTF
1.577
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.149

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.35 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1484.33
MW Contribution:
4.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.928
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.959
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.933
241974AD2-163_GEN2
Solar/Wind Harmer
1.933
270302AB2-170 GEN
Solar/Wind Harmer
7.76
970179AG2-119 GEN
Solar/Wind Harmer
6.743
241955AC1-078 GEN
Solar/Wind Harmer
4.963
957201AF2-014 GEN
Solar/Wind Harmer
2.707
270435AC2-044 GEN
Solar/Wind Harmer
1.194
241972AD1-140 GEN
Solar/Wind Harmer
2.551
270007AE1-245 C
Solar/Wind Harmer
3.03
247521TR3_G114
Solar/Wind Harmer
1.848
270191TR4_S_V150
Solar/Wind Harmer
1.649
965051AG1-369 GEN
Solar/Wind Harmer
2.745
965041AG1-368 GEN
Solar/Wind Harmer
5.334
945631AF1-228 GEN
Solar/Wind Harmer
2.5
959331AF2-224 GEN
Solar/Wind Harmer
5.263
270404AC1-167 GEN
Solar/Wind Harmer
0.567
963791AG1-232 GEN
Solar/Wind Harmer
6.667
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
253338AC1-165 GEN
Solar/Wind Harmer
0.521
270475AD2-096_GEN
50/50
7.753
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
942051AE2-217 GEN
Solar/Wind Harmer
13.86
970065AG2-057 GEN
Solar/Wind Harmer
0.646
276820AF1-078_GEN
Solar/Wind Harmer
1.059
962771AG1-126 GEN
Solar/Wind Harmer
20.746
970153AG2-106 GEN
Solar/Wind Harmer
9.046
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
971995AH1-542 GEN
Solar/Wind Harmer
11.711
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270317AD1-130_GEN
Solar/Wind Harmer
2.967
270485AE1-090_GEN
Solar/Wind Harmer
0.56
270520AE2-214 GEN
Solar/Wind Harmer
5.342
241813AF1-122_GEN
Solar/Wind Harmer
4.135
971201AH1-060 GEN
Solar/Wind Harmer
1.292
962761AG1-125 GEN
Solar/Wind Harmer
20.746
970149AG2-104 GEN
Solar/Wind Harmer
12.811
970155AG2-107 GEN
Solar/Wind Harmer
9.046
246936BC-WTG1
Solar/Wind Harmer
2.335
270489AE1-102 GEN1
Solar/Wind Harmer
0.776
965421AG1-410 GEN
Solar/Wind Harmer
17.703
270297AD1-101 GEN
Solar/Wind Harmer
1.121
270258AD1-119 GEN
Solar/Wind Harmer
1.088
965011AG1-365 GEN
Solar/Wind Harmer
5.263
253333AC1-068 GEN
Solar/Wind Harmer
0.503
25326309TAIT D
Adder
0.523
270024AE2-089 GEN
Solar/Wind Harmer
2.182
965651AG1-433 GEN
Solar/Wind Harmer
2.517
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.277
958861AF2-177 GEN
Solar/Wind Harmer
4.997
945111AF1-176 GEN
Solar/Wind Harmer
8.094
957891AF2-083 GEN
Solar/Wind Harmer
6.788
945371AF1-202 GEN
Solar/Wind Harmer
3.144
270449AD2-020 GEN
Solar/Wind Harmer
1.263
943021AE2-325 GEN
Solar/Wind Harmer
1.641
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.16
270005AE1-210 C O1
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
0.913
274751CRETE EC ;1U
Adder
2.121
274754CRETE EC ;4U
Adder
2.121
972207SS24-0001
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
2.689
274774LINCOLN ;5U
Adder
2.689
274723RIVER EC ;12
Adder
7.77
270055AF2-134 C O1
Solar/Wind Harmer
1.309
274812UNIV PK N;8U
Adder
2.163
270594AE1-207 GEN
Solar/Wind Harmer
5.865
270032AE2-172
Solar/Wind Harmer
2.008
274802UNIV PARK;5U
Adder
2.508
253343AC1-166 GEN
Solar/Wind Harmer
0.521
970031AG2-029 GEN
Solar/Wind Harmer
11.974
270071AF1-092 GEN
Solar/Wind Harmer
7.157
24729505KEY G4
Adder
3.056
25306009OHH W.
Adder
1.331
958711AF2-162 GEN
Solar/Wind Harmer
0.466
253372AE2-315 SEC3
Adder
0.873
270466AD2-091
50/50
5.389
270349AD2-093_GEN
Solar/Wind Harmer
4.839
270471AD2-092_GEN
Solar/Wind Harmer
4.839
938701AE1-092 GEN
Solar/Wind Harmer
21.815
270462AD2-086
Solar/Wind Harmer
6.445
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.339
253378AE2-206_GEN
Solar/Wind Harmer
2.385
25326509SID D
Adder
0.833
246937BC-WTG2
Solar/Wind Harmer
2.335
942801AE2-298 GEN
Solar/Wind Harmer
0.854
247607V1-011 GEN
Solar/Wind Harmer
2.218
270246TR4_N_V150
Solar/Wind Harmer
0.468
270247TR4_N_V136
Solar/Wind Harmer
0.468
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.649
944231AF1-091 GEN
Solar/Wind Harmer
8.735
25322209TAIT E
Adder
4.65
25322209TAIT E
Adder
4.546
942221AE2-234 GEN
Solar/Wind Harmer
1.641
253349AC2-067 GEN
Solar/Wind Harmer
0.953
253400AC2-068 GEN
Solar/Wind Harmer
0.383
247620Y3-023
Adder
0.213
944541AF1-119 GEN
Solar/Wind Harmer
1.928
960971AF2-388 GEN
Solar/Wind Harmer
5.034
253370AE2-315 SEC1
Adder
0.922
970349AG2-230 GEN
Solar/Wind Harmer
6.869
961051AF2-396 GEN
Solar/Wind Harmer
7.17
961051AF2-396 GEN
Solar/Wind Harmer
3.335
247621Y3-024
Adder
0.108
270201AC2-176 GEN
Solar/Wind Harmer
2.303
964611AG1-324 GEN
Solar/Wind Harmer
0.233
965681AG1-436 GEN
Solar/Wind Harmer
5.567
965791AG1-447 GEN
Solar/Wind Harmer
2.848
270031AE2-169
Solar/Wind Harmer
3.621
270599AE1-208 GEN
Solar/Wind Harmer
3.621
970883AG2-550 GEN
Solar/Wind Harmer
4.428
970885AG2-551 GEN
Solar/Wind Harmer
1.03
253383AE2-342_GEN
Solar/Wind Harmer
0.387
274770LINCOLN ;1U
Adder
2.689
274771LINCOLN ;2U
Adder
2.689
270535AF1-215 GEN1
Solar/Wind Harmer
1.963
270536AF1-215 GEN2
Solar/Wind Harmer
1.963
274805UNIV PK N;1U
Adder
2.168
274808UNIV PK N;4U
Adder
2.154
970291AG2-192 GEN
Solar/Wind Harmer
0.56
970291AG2-192 GEN
Solar/Wind Harmer
0.18
270383AD1-128 GEN
Solar/Wind Harmer
2.627
270054AF2-122 C O1
Solar/Wind Helper
0.81
253372AE2-315 SEC3
Adder
0.873
971771AH1-392 GEN
Solar/Wind Harmer
4.076
945581AF1-223 GEN
Solar/Wind Harmer
2.044
944161AF1-084 GEN
Solar/Wind Harmer
0.992
270526AF1-158 GEN
Solar/Wind Harmer
2.036
961761AG1-017 GEN
Solar/Wind Harmer
0.192
964611AG1-324 GEN
Solar/Wind Harmer
1.739
247536S-71 GEN
Solar/Wind Harmer
1.803
960681AF2-359 GEN
Solar/Wind Harmer
1.683
270543AE2-219 C
Solar/Wind Harmer
4.428
971029AG2-637 GEN
Solar/Wind Harmer
6.602
971549AH1-272 GEN
Solar/Wind Harmer
8.047
274775LINCOLN ;6U
Adder
2.689
274776LINCOLN ;7U
Adder
2.689
274777LINCOLN ;8U
Adder
2.689
970289AG2-191 GEN
Solar/Wind Harmer
0.819
972037AH1-567 GEN1
Adder
0.079
246938BC-WTG3
Solar/Wind Harmer
2.375
270491AE1-102 GEN2
Solar/Wind Harmer
0.776
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.818
965021AG1-366 GEN
Solar/Wind Harmer
1.224
270044AE2-322 C
Solar/Wind Harmer
0.688
270518AE2-148 GEN
Solar/Wind Harmer
6.224
270588AE1-091_GEN
Solar/Wind Harmer
5.471
270043AE2-236 GEN
Solar/Wind Harmer
2.686
253325AC1-069 GEN
Solar/Wind Harmer
0.503
960071AF2-298 GEN
Solar/Wind Harmer
0.725
270063AE2-323 C
Solar/Wind Harmer
1.045
944531AF1-118 GEN
Solar/Wind Harmer
16.62
270541AE2-072 C
Solar/Wind Harmer
2.143
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
971347AH1-153 GEN
Solar/Wind Harmer
2.29
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.565
270505AE1-170 C O1
Solar/Wind Harmer
6.785
962031AG1-047 GEN
Solar/Wind Harmer
1.355
957741AF2-068 GEN
Solar/Wind Harmer
6.722
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.631
270004AE1-209 GEN
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
2.451
972231SS25-0005
Solar/Wind Harmer
4.119
972181SS23-001
Solar/Wind Harmer
2.574
274752CRETE EC ;2U
Adder
2.121
274753CRETE EC ;3U
Adder
2.121
274772LINCOLN ;3U
Adder
2.689
274724RIVER EC ;11
Adder
7.679
276164X3-005 C
Solar/Wind Harmer
0.304
274814UNIV PK N;0U
Adder
2.182
274807UNIV PK N;3U
Adder
2.178
274811UNIV PK N;7U
Adder
2.163
965461AG1-414 GEN
Solar/Wind Harmer
0.977
970289AG2-191 GEN
Solar/Wind Harmer
0.331
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.508
LAGNLTFEXP_LAGN->PJM
CLTF
5.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.308
TVALTFEXP_TVA->PJM
CLTF
2.351
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.48
MECLTFEXP_MEC->PJM
CLTF
6.274
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.337
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.469
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.276
WECLTFEXP_WEC->PJM
CLTF
1.577
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.149

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.56 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5140.38
MW Contribution:
10.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.127
23559001PLEAS1
50/50
6.362
270051AF1-062 GEN
50/50
11.798
270475AD2-096_GEN
50/50
7.137
962771AG1-126 GEN
Solar/Wind Harmer
41.016
970153AG2-106 GEN
Solar/Wind Harmer
17.885
961921AG1-034 GEN
Solar/Wind Harmer
15.551
270284AF1-227 GEN1
Solar/Wind Harmer
6.768
270287AF1-227 GEN3
Solar/Wind Harmer
2.504
24721905FLATG4
Adder
24.045
942051AE2-217 GEN
Solar/Wind Harmer
20.995
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.045
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
270518AE2-148 GEN
Solar/Wind Harmer
13.818
253325AC1-069 GEN
Solar/Wind Harmer
1.191
276820AF1-078_GEN
Solar/Wind Harmer
1.776
958581AF2-149 GEN
Solar/Wind Harmer
4.712
971199AH1-059 GEN
Solar/Wind Harmer
2.312
970879AG2-548 GEN
Solar/Wind Harmer
8.771
960071AF2-298 GEN
Solar/Wind Harmer
1.647
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.717
253394AE2-221_GEN
Solar/Wind Harmer
4.9
246938BC-WTG3
Solar/Wind Harmer
4.289
270491AE1-102 GEN2
Solar/Wind Harmer
1.401
971191AH1-055 GEN
Solar/Wind Harmer
20.077
253317AC1-085 GEN4
Solar/Wind Harmer
8.992
946181AF1-283 GEN
Solar/Wind Harmer
13.963
965021AG1-366 GEN
Solar/Wind Harmer
2.494
958091AF2-103 GEN
Solar/Wind Harmer
0.173
24695305TIMB G C
Solar/Wind Harmer
3.573
270588AE1-091_GEN
Solar/Wind Harmer
11.753
944531AF1-118 GEN
Solar/Wind Harmer
37.358
270043AE2-236 GEN
Solar/Wind Harmer
5.865
252519AF1-045_GEN
Solar/Wind Harmer
3.859
270367AC2-061_GEN
Solar/Wind Harmer
3.367
252524AE2-267 GEN
Solar/Wind Harmer
1.667
25196608WSDLE5
Adder
9.072
25194608D.CRK4
Adder
1.739
252507AC2-088 GEN
Solar/Wind Harmer
1.892
270044AE2-322 C
Solar/Wind Harmer
1.388
270063AE2-323 C
Solar/Wind Harmer
2.32
962031AG1-047 GEN
Solar/Wind Harmer
3.189
957741AF2-068 GEN
Solar/Wind Harmer
15.82
971347AH1-153 GEN
Solar/Wind Harmer
5.266
270512AE1-227 GEN2
Solar/Wind Harmer
2.212
270186AC1-089 GEN
Solar/Wind Harmer
6.425
946031AF1-268 GEN
Solar/Wind Harmer
8.725
270004AE1-209 GEN
Solar/Wind Harmer
5.743
24379505HDWTR1G C
Solar/Wind Harmer
8.305
270240V3-007_GEN2
Solar/Wind Harmer
6.498
270330AC1-082 GEN2
Solar/Wind Harmer
0.5
270329AC1-082 GEN1
Solar/Wind Harmer
0.5
970825AG2-519 GEN
Solar/Wind Harmer
5.915
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.404
274752CRETE EC ;2U
Adder
8.473
274753CRETE EC ;3U
Adder
8.473
274772LINCOLN ;3U
Adder
8.673
274724RIVER EC ;11
Adder
18.196
274814UNIV PK N;0U
Adder
5.182
274807UNIV PK N;3U
Adder
5.171
274811UNIV PK N;7U
Adder
5.137
274803UNIV PARK;6U
Adder
5.968
24728705AND G3
Adder
8.209
24728505AND G1
Adder
3.925
274826FISK ;BP
Adder
11.201
972038AH1-567 GEN2
Adder
0.373
972259AH1-714 GEN
Adder
19.5
274676JOLIET 29;8U
Adder
30.174
274729ELWOOD EC;1P
Adder
16.762
274730ELWOOD EC;6P
Adder
16.762
274734ELWOOD EC;8P
Adder
16.762
274736ELWOOD EC;9P
Adder
16.762
274682WAUKEGAN ;7U
Adder
18.178
964991AG1-363 GEN
Solar/Wind Helper
5.171
238108AE1-109 GEN1
Solar/Wind Helper
0.115
238110AE1-109 GEN3
Solar/Wind Helper
0.115
238127S14_GEN_2
Solar/Wind Helper
0.836
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.715
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.023
235063AE1-101 C2
Solar/Wind Helper
1.678
237001AB1-127_GEN
Solar/Wind Helper
0.446
237048AF1-022 C
Solar/Wind Helper
0.186
316415AF1-147_GEN2
Solar/Wind Helper
0.898
205916AD1-020 GEN
Solar/Wind Helper
1.732
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.514
233918AB1-142 GEN
Solar/Wind Helper
0.508
233944AB2-135 GEN
Solar/Wind Helper
0.596
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.513
232408W1-005 C
Solar/Wind Helper
0.513
316447AC1-158 HLD
Solar/Wind Helper
2.876
316044AC1-158 PL1
Solar/Wind Helper
1.307
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.526
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.075
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.093
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.586
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
202652Y1-033 WT C
Solar/Wind Helper
0.504
961301AF2-421 GEN
Solar/Wind Helper
0.443
963151AG1-164 GEN
Solar/Wind Helper
0.443
961341AF2-425 GEN
Solar/Wind Helper
0.442
212507AE2-042_GEN
Solar/Wind Helper
1.561
270166AC1-044 GEN3
50/50
7.109
23559101PLEAS2
50/50
6.362
962761AG1-125 GEN
Solar/Wind Harmer
41.016
970149AG2-104 GEN
Solar/Wind Harmer
25.328
970155AG2-107 GEN
Solar/Wind Harmer
17.885
270286AF1-227 GEN2
Solar/Wind Harmer
2.504
270520AE2-214 GEN
Solar/Wind Harmer
7.243
270391AF1-285 GEN3
Solar/Wind Harmer
1.393
270578AF1-285 GEN2
Solar/Wind Harmer
1.393
253333AC1-068 GEN
Solar/Wind Harmer
1.191
270317AD1-130_GEN
Solar/Wind Harmer
3.64
270485AE1-090_GEN
Solar/Wind Harmer
0.688
270273AD2-016 GEN
Solar/Wind Harmer
3.013
971995AH1-542 GEN
Solar/Wind Harmer
12.463
972269AH1-719 GEN
Adder
2.545
971073AG2-665 GEN
Solar/Wind Harmer
1.275
25326309TAIT D
Adder
1.195
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
241813AF1-122_GEN
Solar/Wind Harmer
5.897
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.9
246936BC-WTG1
Solar/Wind Harmer
4.216
270489AE1-102 GEN1
Solar/Wind Harmer
1.401
965421AG1-410 GEN
Solar/Wind Harmer
32.318
960001AF2-291 GEN
Solar/Wind Harmer
3.25
253316AC1-085 GEN3
Solar/Wind Harmer
8.992
946171AF1-282 GEN
Solar/Wind Harmer
10.741
965011AG1-365 GEN
Solar/Wind Harmer
10.725
270258AD1-119 GEN
Solar/Wind Harmer
2.156
965651AG1-433 GEN
Solar/Wind Harmer
5.801
252516AE2-318_GEN
Solar/Wind Harmer
10.604
958861AF2-177 GEN
Solar/Wind Harmer
11.586
270024AE2-089 GEN
Solar/Wind Harmer
4.961
252510AF1-249 C
Solar/Wind Harmer
0.441
25194608D.CRK4
Adder
1.739
945371AF1-202 GEN
Solar/Wind Harmer
7.376
270297AD1-101 GEN
Solar/Wind Harmer
2.147
270222AC2-111 GEN
Solar/Wind Harmer
4.718
944031AF1-071 GEN
Solar/Wind Harmer
1.062
270510AE1-227 GEN1
Solar/Wind Harmer
2.605
270005AE1-210 C O1
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
6.717
270209AC1-174_GEN
Solar/Wind Harmer
4.274
270437AC2-090 C
Solar/Wind Harmer
5.862
270239V3-007_GEN1
Solar/Wind Harmer
1.807
270331AC1-082 GEN3
Solar/Wind Harmer
0.501
25196808ZIMRHP
Adder
79.685
970825AG2-519 GEN
Solar/Wind Harmer
2.203
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.634
25196008MFTGT1
Adder
1.45
274751CRETE EC ;1U
Adder
8.473
274754CRETE EC ;4U
Adder
8.473
274773LINCOLN ;4U
Adder
8.673
274774LINCOLN ;5U
Adder
8.673
274723RIVER EC ;12
Adder
18.412
274812UNIV PK N;8U
Adder
5.137
274802UNIV PARK;5U
Adder
5.968
24728605AND G2
Adder
3.925
274676JOLIET 29;8U
Adder
31.291
274732ELWOOD EC;7P
Adder
16.762
274674JOLIET 9 ;6U
Adder
15.699
972203AH1-686 GEN
Adder
2.344
274745AC1-111 GEN9
Adder
5.677
970091AG2-072 GEN
Adder
77.647
274682WAUKEGAN ;7U
Adder
18.178
316095T157 G97
Solar/Wind Helper
1.515
23583801GRNGAP
Solar/Wind Helper
5.644
238185AF2-356 C
Solar/Wind Helper
2.686
238109AE1-109 GEN2
Solar/Wind Helper
0.115
238120AE2-309 GEN
Solar/Wind Helper
0.534
238126S14_GEN_1
Solar/Wind Helper
0.836
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.667
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.451
237002AB1-128_GEN
Solar/Wind Helper
0.448
23751101LEADS_P59
Solar/Wind Helper
2.15
270459AD2-067 GEN
Solar/Wind Harmer
10.212
961821AG1-024 GEN
Solar/Wind Harmer
10.368
972239AH1-704 GEN
Adder
2.66
241955AC1-078 GEN
Solar/Wind Harmer
8.781
241973AD2-163_GEN1
Solar/Wind Harmer
2.319
241974AD2-163_GEN2
Solar/Wind Harmer
2.319
943861AF1-054 GEN
Solar/Wind Harmer
4.476
943851AF1-053 GEN
Solar/Wind Harmer
2.163
945631AF1-228 GEN
Solar/Wind Harmer
5.449
270223U2-072_GEN1
Solar/Wind Harmer
2.274
270224U2-072_GEN2
Solar/Wind Harmer
2.274
270227U2-072_GEN3
Solar/Wind Harmer
2.274
270228U2-072_GEN4
Solar/Wind Harmer
2.274
270231U2-072_GEN5
Solar/Wind Harmer
2.274
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
8.025
253338AC1-165 GEN
Solar/Wind Harmer
1.235
253343AC1-166 GEN
Solar/Wind Harmer
1.235
270302AB2-170 GEN
Solar/Wind Harmer
9.522
940611AE2-048 GEN
Solar/Wind Harmer
24.76
941391AE2-136 GEN
Solar/Wind Harmer
12.83
270263AC1-001 GEN
Solar/Wind Harmer
1.17
241972AD1-140 GEN
Solar/Wind Harmer
5.01
270291AC1-194 GEN
Solar/Wind Harmer
5.61
270340AC2-060 GEN
Solar/Wind Harmer
3.331
970179AG2-119 GEN
Solar/Wind Harmer
8.806
253372AE2-315 SEC3
Adder
2.062
253372AE2-315 SEC3
Adder
2.062
25306009OHH W.
Adder
3.128
253406AD2-031_GEN
Solar/Wind Harmer
1.383
957201AF2-014 GEN
Solar/Wind Harmer
4.888
270435AC2-044 GEN
Solar/Wind Harmer
2.156
253433AC1-085 GEN1
Solar/Wind Harmer
5.708
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.604
270191TR4_S_V150
Solar/Wind Harmer
3.216
965051AG1-369 GEN
Solar/Wind Harmer
5.355
959331AF2-224 GEN
Solar/Wind Harmer
10.725
270377AD1-106 GEN
Solar/Wind Harmer
5.62
270007AE1-245 C
Solar/Wind Harmer
5.779
965041AG1-368 GEN
Solar/Wind Harmer
10.701
24729505KEY G4
Adder
6.914
966831AG1-554 GEN
Solar/Wind Harmer
1.275
971567AH1-282 GEN
Solar/Wind Harmer
5.316
270071AF1-092 GEN
Solar/Wind Harmer
15.971
963791AG1-232 GEN
Solar/Wind Harmer
14.371
971985AH1-537 GEN
Solar/Wind Harmer
18.964
958711AF2-162 GEN
Solar/Wind Harmer
1.074
25196408WSDLE3
Adder
9.339
25196308WSDLE2
Adder
9.258
25196208WSDLE1
Adder
9.235
25196708WSDLE6
Adder
9.211
25196508WSDLE4
Adder
8.979
945581AF1-223 GEN
Solar/Wind Harmer
4.795
23777801MSM_W1-116
Solar/Wind Helper
0.116
3141196NOKESVL
Solar/Wind Helper
1.039
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.283
233987AB2-037 GEN
Solar/Wind Helper
2.369
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.235
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.76
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.513
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.118
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.501
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.329
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.091
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.799
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.443
961331AF2-424 GEN
Solar/Wind Helper
0.442
961421AF2-433 GEN
Solar/Wind Helper
0.441
957921AF2-086 GEN
Solar/Wind Helper
0.436
270594AE1-207 GEN
Solar/Wind Harmer
13.371
270032AE2-172
Solar/Wind Harmer
4.579
971029AG2-637 GEN
Solar/Wind Harmer
15.851
970031AG2-029 GEN
Solar/Wind Harmer
26.415
270404AC1-167 GEN
Solar/Wind Harmer
1.144
270543AE2-219 C
Solar/Wind Harmer
10.561
247536S-71 GEN
Solar/Wind Harmer
4.271
961761AG1-017 GEN
Solar/Wind Harmer
0.451
964611AG1-324 GEN
Solar/Wind Harmer
4.11
25196108MFTGT2
Adder
1.598
25196108MFTGT2
Adder
1.484
274775LINCOLN ;6U
Adder
8.673
274776LINCOLN ;7U
Adder
8.673
274777LINCOLN ;8U
Adder
8.673
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.938
274800UNIV PARK;3U
Adder
5.964
274801UNIV PARK;4U
Adder
5.964
972228AH1-698 GEN2
Adder
3.789
972227AH1-698 GEN1
Adder
2.668
274687WILL CNTY;4U
Adder
28.512
274687WILL CNTY;4U
Adder
28.512
274675JOLIET 29;7U
Adder
31.291
274675JOLIET 29;7U
Adder
30.174
274728ELWOOD EC;5P
Adder
16.762
274731ELWOOD EC;2P
Adder
16.762
274733ELWOOD EC;3P
Adder
16.762
274735ELWOOD EC;4P
Adder
16.762
274744AC1-111 GEN8
Adder
5.677
274746AC1-111 G10
Adder
5.677
23750701CROSSCHOOL
Solar/Wind Helper
1.517
238118U2-030_1
Solar/Wind Helper
0.345
238169AE2-226 GEN1
Solar/Wind Helper
0.708
238170AE2-226 GEN2
Solar/Wind Helper
0.708
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.647
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.372
959381AF2-229 GEN
Solar/Wind Helper
0.36
20390526W1-045 C
Solar/Wind Helper
0.354
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.515
205956AE1-196_GEN
Solar/Wind Helper
0.514
233915AB1-141 GEN
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.235
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.795
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
316164AC1-076 GEN
Solar/Wind Helper
1.108
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.069
964851AG1-348 GEN
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
203955AF1-039 C O1
Solar/Wind Helper
0.332
209027LOR2_Q27
Solar/Wind Helper
1.036
212266LOR1
Solar/Wind Helper
0.302
209054AE2-059 GEN
Solar/Wind Helper
0.08
270119AB2-067 GEN1
50/50
7.109
270120AB2-067 GEN2
50/50
7.109
24318905MLG2
50/50
7.027
270349AD2-093_GEN
Solar/Wind Harmer
4.455
270471AD2-092_GEN
Solar/Wind Harmer
4.455
270054AF2-122 C O1
Solar/Wind Harmer
3.972
946101AF1-275 GEN
Solar/Wind Harmer
1.811
253383AE2-342_GEN
Solar/Wind Harmer
1.04
942861AE2-305 GEN
Solar/Wind Harmer
9.069
938701AE1-092 GEN
Solar/Wind Harmer
23.766
270462AD2-086
Solar/Wind Harmer
7.908
270269AC2-059
Solar/Wind Harmer
10.571
253378AE2-206_GEN
Solar/Wind Harmer
3.997
972159AH1-661 GEN
Adder
1.106
253415AE1-040 GEN
Solar/Wind Harmer
1.242
25326509SID D
Adder
1.451
241960AC2-195 GEN
Solar/Wind Harmer
3.055
971073AG2-665 GEN
Solar/Wind Harmer
8.771
970879AG2-548 GEN
Solar/Wind Harmer
1.275
25326109MON D
Adder
1.442
25322209TAIT E
Adder
10.635
25322209TAIT E
Adder
10.396
253370AE2-315 SEC1
Adder
2.18
927014AC1-188 GEN
Solar/Wind Harmer
1.717
253349AC2-067 GEN
Solar/Wind Harmer
2.203
253400AC2-068 GEN
Solar/Wind Harmer
0.886
246937BC-WTG2
Solar/Wind Harmer
4.216
270246TR4_N_V150
Solar/Wind Harmer
0.912
270247TR4_N_V136
Solar/Wind Harmer
0.912
942801AE2-298 GEN
Solar/Wind Harmer
1.621
247607V1-011 GEN
Solar/Wind Harmer
4.231
962581AG1-107 GEN
Solar/Wind Harmer
5.356
961491AF2-440 GEN
Solar/Wind Harmer
2.226
25183208HLCRTG
Solar/Wind Harmer
6.427
944541AF1-119 GEN
Solar/Wind Harmer
4.444
960971AF2-388 GEN
Solar/Wind Harmer
11.601
942221AE2-234 GEN
Solar/Wind Harmer
3.71
25194408D.CRK1
Adder
8
25194508D.CRK3
Adder
1.496
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.561
970885AG2-551 GEN
Solar/Wind Harmer
2.456
247621Y3-024
Adder
0.255
270201AC2-176 GEN
Solar/Wind Harmer
5.42
964611AG1-324 GEN
Solar/Wind Harmer
0.551
970349AG2-230 GEN
Solar/Wind Harmer
15.797
270031AE2-169
Solar/Wind Harmer
8.576
270599AE1-208 GEN
Solar/Wind Harmer
8.576
270383AD1-128 GEN
Solar/Wind Harmer
6.419
926881AC1-175 GEN
Solar/Wind Harmer
5.862
247620Y3-023
Adder
0.483
944231AF1-091 GEN
Solar/Wind Harmer
18.887
24728805RICHG1
Adder
3.96
24728905RICHG2
Adder
3.96
274770LINCOLN ;1U
Adder
8.673
274771LINCOLN ;2U
Adder
8.673
274805UNIV PK N;1U
Adder
5.149
274808UNIV PK N;4U
Adder
5.115
274674JOLIET 9 ;6U
Adder
15.699
274696ROCKY RD ;4P
Adder
11.533
274695ROCKY RD ;2P
Adder
11.267
274693ROCKY RD ;1P
Adder
11.156
274697ROCKY RD ;3P
Adder
3.061
274683WAUKEGAN ;8U
Adder
21.305
274683WAUKEGAN ;8U
Adder
9.68
316097T157 G90
Solar/Wind Helper
1.515
235054AD2-180 GEN
Solar/Wind Helper
2.054
23585401KL_K28_T16
Solar/Wind Helper
1.5
235531U2-073 GEN
Solar/Wind Helper
3.347
238117U2-030
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.501
238148AE2-230_GEN2
Solar/Wind Helper
0.501
238149AF1-291A_GEN
Solar/Wind Helper
0.143
23751201ROTHROCK
Solar/Wind Helper
0.836
235020AA1-095 C
Solar/Wind Helper
0.054
237061AD1-155 GEN
Solar/Wind Helper
1.772
238221AF1-254 C O1
Solar/Wind Helper
0.278
237080AD1-060 GEN
Solar/Wind Helper
0.346
235062AE1-101 C1
Solar/Wind Helper
1.678
316411AF1-147_GEN1
Solar/Wind Helper
0.898
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.371
223402AF1-300 C
Solar/Wind Helper
0.371
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.385
232424Y1-079 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.363
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.575
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.972
232428Y3-058 C
Solar/Wind Helper
0.342
232410W1-006 C
Solar/Wind Helper
0.513
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.235
233954AC2-188 GEN
Solar/Wind Helper
0.235
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.182
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.028
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.051
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
961431AF2-434 GEN
Solar/Wind Helper
0.441
LAGNLTFEXP_LAGN->PJM
CLTF
14.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.742
TVALTFEXP_TVA->PJM
CLTF
7.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.079
MECLTFEXP_MEC->PJM
CLTF
15.894
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CPLELTFEXP_CPLE->PJM
CLTF
0.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.743
NYPJM->LTFIMP_NY
CLTF
4.85
LGEELTFEXP_LGEE->PJM
CLTF
6.747
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.72 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5108.61
MW Contribution:
10.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.084
23559001PLEAS1
50/50
6.18
270051AF1-062 GEN
50/50
11.783
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.857
970153AG2-106 GEN
Solar/Wind Harmer
17.815
961921AG1-034 GEN
Solar/Wind Harmer
15.539
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.892
942051AE2-217 GEN
Solar/Wind Harmer
20.96
960801AF2-371 GEN
Solar/Wind Harmer
2.935
964871AG1-351 GEN
Solar/Wind Harmer
2.026
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.795
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.716
971199AH1-059 GEN
Solar/Wind Harmer
2.315
970879AG2-548 GEN
Solar/Wind Harmer
8.757
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.713
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
253394AE2-221_GEN
Solar/Wind Harmer
4.888
270166AC1-044 GEN3
50/50
7.082
23559101PLEAS2
50/50
6.18
962761AG1-125 GEN
Solar/Wind Harmer
40.857
970149AG2-104 GEN
Solar/Wind Harmer
25.229
970155AG2-107 GEN
Solar/Wind Harmer
17.815
270520AE2-214 GEN
Solar/Wind Harmer
7.233
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972239AH1-704 GEN
Adder
2.673
270459AD2-067 GEN
Solar/Wind Harmer
10.203
961821AG1-024 GEN
Solar/Wind Harmer
10.359
241955AC1-078 GEN
Solar/Wind Harmer
8.768
241973AD2-163_GEN1
Solar/Wind Harmer
2.315
971995AH1-542 GEN
Solar/Wind Harmer
12.451
270273AD2-016 GEN
Solar/Wind Harmer
3.008
972269AH1-719 GEN
Adder
2.564
971073AG2-665 GEN
Solar/Wind Harmer
1.273
25326309TAIT D
Adder
1.192
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
241813AF1-122_GEN
Solar/Wind Harmer
5.894
971201AH1-060 GEN
Solar/Wind Harmer
1.842
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.241
960001AF2-291 GEN
Solar/Wind Harmer
3.242
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.696
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.784
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.552
270024AE2-089 GEN
Solar/Wind Harmer
4.947
252510AF1-249 C
Solar/Wind Harmer
0.44
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.355
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270005AE1-210 C O1
Solar/Wind Harmer
5.726
25196808ZIMRHP
Adder
79.465
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
942081AE2-220 GEN
Solar/Wind Harmer
6.698
270209AC1-174_GEN
Solar/Wind Harmer
4.262
270437AC2-090 C
Solar/Wind Harmer
5.845
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.448
274754CRETE EC ;4U
Adder
8.448
274773LINCOLN ;4U
Adder
8.646
274774LINCOLN ;5U
Adder
8.646
274723RIVER EC ;12
Adder
18.356
274812UNIV PK N;8U
Adder
5.122
274802UNIV PARK;5U
Adder
5.949
24728605AND G2
Adder
3.913
274676JOLIET 29;8U
Adder
31.195
274732ELWOOD EC;7P
Adder
16.71
274674JOLIET 9 ;6U
Adder
15.65
972203AH1-686 GEN
Adder
2.333
274745AC1-111 GEN9
Adder
5.66
970091AG2-072 GEN
Adder
77.376
274682WAUKEGAN ;7U
Adder
18.122
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.674
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.532
238126S14_GEN_1
Solar/Wind Helper
0.833
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.663
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.45
237002AB1-128_GEN
Solar/Wind Helper
0.447
23751101LEADS_P59
Solar/Wind Helper
2.129
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.363
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.441
270594AE1-207 GEN
Solar/Wind Harmer
13.331
270032AE2-172
Solar/Wind Harmer
4.566
241974AD2-163_GEN2
Solar/Wind Harmer
2.315
945631AF1-228 GEN
Solar/Wind Harmer
5.44
943861AF1-054 GEN
Solar/Wind Harmer
4.468
943851AF1-053 GEN
Solar/Wind Harmer
2.159
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.013
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
940611AE2-048 GEN
Solar/Wind Harmer
24.928
941391AE2-136 GEN
Solar/Wind Harmer
12.917
270263AC1-001 GEN
Solar/Wind Harmer
1.168
241972AD1-140 GEN
Solar/Wind Harmer
4.999
270291AC1-194 GEN
Solar/Wind Harmer
5.603
970179AG2-119 GEN
Solar/Wind Harmer
8.8
270340AC2-060 GEN
Solar/Wind Harmer
3.323
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.877
270435AC2-044 GEN
Solar/Wind Harmer
2.151
270377AD1-106 GEN
Solar/Wind Harmer
5.62
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.342
959331AF2-224 GEN
Solar/Wind Harmer
10.696
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.674
971567AH1-282 GEN
Solar/Wind Harmer
5.319
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.894
270071AF1-092 GEN
Solar/Wind Harmer
15.924
963791AG1-232 GEN
Solar/Wind Harmer
14.332
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.071
25196408WSDLE3
Adder
9.314
25196308WSDLE2
Adder
9.233
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.955
945581AF1-223 GEN
Solar/Wind Harmer
4.781
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.807
970031AG2-029 GEN
Solar/Wind Harmer
26.342
270543AE2-219 C
Solar/Wind Harmer
10.531
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.099
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.48
274775LINCOLN ;6U
Adder
8.646
274776LINCOLN ;7U
Adder
8.646
274777LINCOLN ;8U
Adder
8.646
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.914
274800UNIV PARK;3U
Adder
5.946
274801UNIV PARK;4U
Adder
5.946
972228AH1-698 GEN2
Adder
3.777
972227AH1-698 GEN1
Adder
2.66
274687WILL CNTY;4U
Adder
28.425
274687WILL CNTY;4U
Adder
28.425
274675JOLIET 29;7U
Adder
31.195
274675JOLIET 29;7U
Adder
30.081
274728ELWOOD EC;5P
Adder
16.71
274731ELWOOD EC;2P
Adder
16.71
274733ELWOOD EC;3P
Adder
16.71
274735ELWOOD EC;4P
Adder
16.71
274744AC1-111 GEN8
Adder
5.66
274746AC1-111 G10
Adder
5.66
23750701CROSSCHOOL
Solar/Wind Helper
1.512
238118U2-030_1
Solar/Wind Helper
0.344
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.644
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.234
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
246938BC-WTG3
Solar/Wind Harmer
4.279
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.022
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.488
958091AF2-103 GEN
Solar/Wind Harmer
0.172
24695305TIMB G C
Solar/Wind Harmer
3.564
270588AE1-091_GEN
Solar/Wind Harmer
11.739
944531AF1-118 GEN
Solar/Wind Harmer
37.25
270043AE2-236 GEN
Solar/Wind Harmer
5.848
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.18
957741AF2-068 GEN
Solar/Wind Harmer
15.775
971347AH1-153 GEN
Solar/Wind Harmer
5.25
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.7
270004AE1-209 GEN
Solar/Wind Harmer
5.726
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
24379505HDWTR1G C
Solar/Wind Harmer
8.281
270240V3-007_GEN2
Solar/Wind Harmer
6.479
970825AG2-519 GEN
Solar/Wind Harmer
5.897
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.448
274753CRETE EC ;3U
Adder
8.448
274772LINCOLN ;3U
Adder
8.646
274724RIVER EC ;11
Adder
18.141
274814UNIV PK N;0U
Adder
5.166
274807UNIV PK N;3U
Adder
5.155
274811UNIV PK N;7U
Adder
5.122
274803UNIV PARK;6U
Adder
5.949
24728705AND G3
Adder
8.184
24728505AND G1
Adder
3.913
274826FISK ;BP
Adder
11.167
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.441
274676JOLIET 29;8U
Adder
30.081
274729ELWOOD EC;1P
Adder
16.71
274730ELWOOD EC;6P
Adder
16.71
274734ELWOOD EC;8P
Adder
16.71
274736ELWOOD EC;9P
Adder
16.71
274682WAUKEGAN ;7U
Adder
18.122
964991AG1-363 GEN
Solar/Wind Helper
5.16
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.833
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.015
235063AE1-101 C2
Solar/Wind Helper
1.674
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.185
316415AF1-147_GEN2
Solar/Wind Helper
0.896
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.507
233944AB2-135 GEN
Solar/Wind Helper
0.595
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.519
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.582
20675828AU_W4-064
Solar/Wind Helper
0.03
270119AB2-067 GEN1
50/50
7.082
270120AB2-067 GEN2
50/50
7.082
24318905MLG2
50/50
7.035
270349AD2-093_GEN
Solar/Wind Harmer
4.445
270471AD2-092_GEN
Solar/Wind Harmer
4.445
270054AF2-122 C O1
Solar/Wind Harmer
3.971
946101AF1-275 GEN
Solar/Wind Harmer
1.808
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.053
938701AE1-092 GEN
Solar/Wind Harmer
23.731
270462AD2-086
Solar/Wind Harmer
7.892
270269AC2-059
Solar/Wind Harmer
10.554
972159AH1-661 GEN
Adder
1.111
253378AE2-206_GEN
Solar/Wind Harmer
3.988
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.053
971073AG2-665 GEN
Solar/Wind Harmer
8.757
970879AG2-548 GEN
Solar/Wind Harmer
1.273
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.371
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.713
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
202652Y1-033 WT C
Solar/Wind Helper
0.501
961341AF2-425 GEN
Solar/Wind Helper
0.441
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
203955AF1-039 C O1
Solar/Wind Helper
0.331
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.41
944541AF1-119 GEN
Solar/Wind Harmer
4.431
960971AF2-388 GEN
Solar/Wind Harmer
11.568
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.978
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.531
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.405
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.75
270031AE2-169
Solar/Wind Harmer
8.551
270599AE1-208 GEN
Solar/Wind Harmer
8.551
270383AD1-128 GEN
Solar/Wind Harmer
6.401
926881AC1-175 GEN
Solar/Wind Harmer
5.845
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.84
24728805RICHG1
Adder
3.949
24728905RICHG2
Adder
3.949
274770LINCOLN ;1U
Adder
8.646
274771LINCOLN ;2U
Adder
8.646
274805UNIV PK N;1U
Adder
5.133
274808UNIV PK N;4U
Adder
5.099
274674JOLIET 9 ;6U
Adder
15.65
274696ROCKY RD ;4P
Adder
11.497
274695ROCKY RD ;2P
Adder
11.232
274693ROCKY RD ;1P
Adder
11.121
274697ROCKY RD ;3P
Adder
3.051
274683WAUKEGAN ;8U
Adder
21.239
274683WAUKEGAN ;8U
Adder
9.65
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.044
23585401KL_K28_T16
Solar/Wind Helper
1.493
235531U2-073 GEN
Solar/Wind Helper
3.333
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.5
238148AE2-230_GEN2
Solar/Wind Helper
0.5
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.83
237061AD1-155 GEN
Solar/Wind Helper
1.768
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.674
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233982AB2-133 GEN
Solar/Wind Helper
0.362
233946AB2-136 GEN
Solar/Wind Helper
0.574
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
14.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.682
TVALTFEXP_TVA->PJM
CLTF
7.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.966
MECLTFEXP_MEC->PJM
CLTF
15.842
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.337
NYPJM->LTFIMP_NY
CLTF
4.834
LGEELTFEXP_LGEE->PJM
CLTF
6.725
WECLTFEXP_WEC->PJM
CLTF
3.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5094.21
MW Contribution:
10.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5094.21
MW Contribution:
10.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.83
MW Contribution:
7.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.678
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270291AC1-194 GEN
Solar/Wind Harmer
0
970179AG2-119 GEN
Solar/Wind Harmer
6.854
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
253406AD2-031_GEN
Solar/Wind Harmer
0.559
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270377AD1-106 GEN
Solar/Wind Harmer
2.842
247521TR3_G114
Solar/Wind Harmer
0.27
965051AG1-369 GEN
Solar/Wind Harmer
3.723
959331AF2-224 GEN
Solar/Wind Harmer
5.217
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.438
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
963791AG1-232 GEN
Solar/Wind Harmer
9.987
270071AF1-092 GEN
Solar/Wind Harmer
14.177
971985AH1-537 GEN
Solar/Wind Harmer
2.196
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
25196508WSDLE4
Adder
8.944
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
270543AE2-219 C
Solar/Wind Harmer
5.137
247536S-71 GEN
Solar/Wind Harmer
0.293
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
970289AG2-191 GEN
Solar/Wind Harmer
1.382
971771AH1-392 GEN
Solar/Wind Harmer
7.271
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
971549AH1-272 GEN
Solar/Wind Harmer
14.794
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
270166AC1-044 GEN3
50/50
7.069
23559101PLEAS2
50/50
6.097
962761AG1-125 GEN
Solar/Wind Harmer
34.394
970149AG2-104 GEN
Solar/Wind Harmer
18.573
970155AG2-107 GEN
Solar/Wind Harmer
21.963
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.894
270273AD2-016 GEN
Solar/Wind Harmer
0.807
972269AH1-719 GEN
Adder
2.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965421AG1-410 GEN
Solar/Wind Harmer
22.47
960001AF2-291 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965011AG1-365 GEN
Solar/Wind Harmer
7.453
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
958861AF2-177 GEN
Solar/Wind Harmer
3.191
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.732
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.351
970825AG2-519 GEN
Solar/Wind Harmer
2.589
24639705ELKHART HY
Adder
0.16
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
276903AD2-071 C
Solar/Wind Harmer
8.095
25196008MFTGT1
Adder
1.443
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.365
270119AB2-067 GEN1
50/50
7.069
270120AB2-067 GEN2
50/50
7.069
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.31
938701AE1-092 GEN
Solar/Wind Harmer
12.867
971655AH1-328 GEN
Solar/Wind Harmer
2.843
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
25326509SID D
Adder
1.446
971073AG2-665 GEN
Solar/Wind Harmer
5.597
970879AG2-548 GEN
Solar/Wind Harmer
1.272
25326109MON D
Adder
1.437
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
246937BC-WTG2
Solar/Wind Harmer
0.302
270246TR4_N_V150
Solar/Wind Harmer
0.048
270247TR4_N_V136
Solar/Wind Harmer
0.048
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.351
944541AF1-119 GEN
Solar/Wind Harmer
0.492
960971AF2-388 GEN
Solar/Wind Harmer
4.326
942221AE2-234 GEN
Solar/Wind Harmer
2.958
25194408D.CRK1
Adder
7.968
25194508D.CRK3
Adder
1.49
970621AG2-405 GEN
Solar/Wind Harmer
1.345
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970885AG2-551 GEN
Solar/Wind Harmer
2.446
247621Y3-024
Adder
0.253
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270031AE2-169
Solar/Wind Harmer
4.021
270599AE1-208 GEN
Solar/Wind Harmer
6.701
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728805RICHG1
Adder
3.944
24728905RICHG2
Adder
3.944
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.052
965791AG1-447 GEN
Solar/Wind Harmer
6.638
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274754CRETE EC ;4U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
274802UNIV PARK;5U
Adder
5.941
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
31.151
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
939401AE1-172 GEN
Solar/Wind Harmer
5.275
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
274682WAUKEGAN ;7U
Adder
18.096
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.818
971997AH1-543 GEN
Solar/Wind Harmer
3.68
962781AG1-127 GEN
Solar/Wind Harmer
6.668
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
316095T157 G97
Solar/Wind Helper
1.51
23583801GRNGAP
Solar/Wind Helper
5.626
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
238126S14_GEN_1
Solar/Wind Helper
0.831
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.661
237038AE2-054 C
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.792
211065PSPA IPP
Solar/Wind Helper
0.152
963161AG1-165 GEN
Solar/Wind Helper
0.441
957471AF2-041 GEN
Solar/Wind Harmer
13.586
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
24318805MLG1
50/50
10.065
23559001PLEAS1
50/50
6.097
270051AF1-062 GEN
50/50
11.777
270475AD2-096_GEN
50/50
7.114
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
961921AG1-034 GEN
Solar/Wind Harmer
7.586
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
970191AG2-125 GEN
Solar/Wind Harmer
1.937
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
971191AH1-055 GEN
Solar/Wind Harmer
19.175
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
944531AF1-118 GEN
Solar/Wind Harmer
33.233
270043AE2-236 GEN
Solar/Wind Harmer
4.754
252519AF1-045_GEN
Solar/Wind Harmer
3.844
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
9.036
25194608D.CRK4
Adder
1.732
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
971347AH1-153 GEN
Solar/Wind Harmer
3.658
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.95
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
970289AG2-191 GEN
Solar/Wind Harmer
0.8
945111AF1-176 GEN
Solar/Wind Harmer
5.891
247642Z2-115 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
274753CRETE EC ;3U
Adder
8.436
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274811UNIV PK N;7U
Adder
5.114
972167AH1-666 GEN
Solar/Wind Harmer
5.69
274803UNIV PARK;6U
Adder
5.941
24728705AND G3
Adder
8.173
24728505AND G1
Adder
3.908
274887GEN-1.85
Solar/Wind Harmer
0.185
276843GEN-1.7
Solar/Wind Harmer
0.23
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274826FISK ;BP
Adder
11.151
972038AH1-567 GEN2
Adder
0.372
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
972259AH1-714 GEN
Adder
19.413
274676JOLIET 29;8U
Adder
30.039
274729ELWOOD EC;1P
Adder
16.687
274730ELWOOD EC;6P
Adder
16.687
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
274682WAUKEGAN ;7U
Adder
18.096
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970193AG2-126 GEN
Solar/Wind Harmer
10.468
970571AG2-364 GEN
Solar/Wind Harmer
13.944
274775LINCOLN ;6U
Adder
8.634
274776LINCOLN ;7U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972228AH1-698 GEN2
Adder
3.772
972227AH1-698 GEN1
Adder
2.656
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
274728ELWOOD EC;5P
Adder
16.687
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274735ELWOOD EC;4P
Adder
16.687
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
274744AC1-111 GEN8
Adder
5.652
274746AC1-111 G10
Adder
5.652
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
970169AG2-114 GEN
Solar/Wind Harmer
7.011
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
971411AH1-196 GEN
Solar/Wind Harmer
10.47
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.32
23750701CROSSCHOOL
Solar/Wind Helper
1.509
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.512
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.062
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.057
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.031
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
964991AG1-363 GEN
Solar/Wind Helper
5.155
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.831
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
23562501BACKB
Solar/Wind Helper
1.012
235063AE1-101 C2
Solar/Wind Helper
1.672
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.512
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.594
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.868
316044AC1-158 PL1
Solar/Wind Helper
1.303
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.516
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.58
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
202652Y1-033 WT C
Solar/Wind Helper
0.5
959091AF2-200 GEN
Solar/Wind Harmer
9.057
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274805UNIV PK N;1U
Adder
5.126
274808UNIV PK N;4U
Adder
5.092
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
276776AD2-060 GEN
Solar/Wind Harmer
0.758
958011AF2-095 GEN
Solar/Wind Harmer
10.234
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
274674JOLIET 9 ;6U
Adder
15.628
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274696ROCKY RD ;4P
Adder
11.481
274695ROCKY RD ;2P
Adder
11.216
274693ROCKY RD ;1P
Adder
11.106
274697ROCKY RD ;3P
Adder
3.047
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276901AD2-066 C O1
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
962691AG1-118 GEN
Solar/Wind Harmer
21.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
942111AE2-223 GEN
Solar/Wind Harmer
2.266
316097T157 G90
Solar/Wind Helper
1.51
235054AD2-180 GEN
Solar/Wind Helper
2.04
23585401KL_K28_T16
Solar/Wind Helper
1.489
235531U2-073 GEN
Solar/Wind Helper
3.327
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.344
235062AE1-101 C1
Solar/Wind Helper
1.672
316411AF1-147_GEN1
Solar/Wind Helper
0.895
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.17
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5005.84
MW Contribution:
10.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
3.095
270459AD2-067 GEN
Solar/Wind Harmer
10.428
961821AG1-024 GEN
Solar/Wind Harmer
10.588
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270302AB2-170 GEN
Solar/Wind Harmer
9.776
270432AC2-029 GEN
Solar/Wind Harmer
8.117
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253338AC1-165 GEN
Solar/Wind Harmer
1.249
253343AC1-166 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270377AD1-106 GEN
Solar/Wind Harmer
5.917
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270291AC1-194 GEN
Solar/Wind Harmer
5.669
270340AC2-060 GEN
Solar/Wind Harmer
3.354
957201AF2-014 GEN
Solar/Wind Harmer
5.019
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
270191TR4_S_V150
Solar/Wind Harmer
3.29
965051AG1-369 GEN
Solar/Wind Harmer
5.479
25306009OHH W.
Adder
3.158
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
958711AF2-162 GEN
Solar/Wind Harmer
1.086
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
270499AE1-146 GEN
Solar/Wind Harmer
2.679
270543AE2-219 C
Solar/Wind Harmer
10.668
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
964611AG1-324 GEN
Solar/Wind Harmer
4.154
971771AH1-392 GEN
Solar/Wind Harmer
9.58
944161AF1-084 GEN
Solar/Wind Harmer
2.352
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196508WSDLE4
Adder
9.023
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274775LINCOLN ;6U
Adder
8.764
274776LINCOLN ;7U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972228AH1-698 GEN2
Adder
3.828
972227AH1-698 GEN1
Adder
2.695
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
274728ELWOOD EC;5P
Adder
16.929
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
274735ELWOOD EC;4P
Adder
16.929
23750701CROSSCHOOL
Solar/Wind Helper
1.591
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
270166AC1-044 GEN3
50/50
7.05
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
962761AG1-125 GEN
Solar/Wind Harmer
40.867
970149AG2-104 GEN
Solar/Wind Harmer
25.235
970155AG2-107 GEN
Solar/Wind Harmer
17.82
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
971995AH1-542 GEN
Solar/Wind Harmer
12.942
972269AH1-719 GEN
Adder
2.693
270317AD1-130_GEN
Solar/Wind Harmer
3.738
270485AE1-090_GEN
Solar/Wind Harmer
0.706
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965421AG1-410 GEN
Solar/Wind Harmer
33.164
971073AG2-665 GEN
Solar/Wind Harmer
1.284
25326309TAIT D
Adder
1.207
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
270297AD1-101 GEN
Solar/Wind Harmer
2.226
965011AG1-365 GEN
Solar/Wind Harmer
10.939
270258AD1-119 GEN
Solar/Wind Harmer
2.219
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
958861AF2-177 GEN
Solar/Wind Harmer
11.712
960001AF2-291 GEN
Solar/Wind Harmer
3.236
24639705ELKHART HY
Adder
0.164
945371AF1-202 GEN
Solar/Wind Harmer
7.453
270216AD2-079_GEN
Solar/Wind Harmer
0.645
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
944031AF1-071 GEN
Solar/Wind Harmer
1.069
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25194608D.CRK4
Adder
1.747
25196808ZIMRHP
Adder
79.955
23906502RICHG2&3
Adder
1.268
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274754CRETE EC ;4U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
274812UNIV PK N;8U
Adder
5.194
274802UNIV PARK;5U
Adder
6.031
23920202STRYCT
Adder
1.44
274676JOLIET 29;8U
Adder
31.606
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
23583801GRNGAP
Solar/Wind Helper
6.383
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
23546401DTGZ2-030
Solar/Wind Helper
0.1
238120AE2-309 GEN
Solar/Wind Helper
0.557
238126S14_GEN_1
Solar/Wind Helper
0.87
237038AE2-054 C
Solar/Wind Helper
0.294
235067AD1-061 GEN
Solar/Wind Helper
0.481
237085AD2-009_GEN
Solar/Wind Helper
1.776
237002AB1-128_GEN
Solar/Wind Helper
0.477
3141196NOKESVL
Solar/Wind Helper
1.144
23777801MSM_W1-116
Solar/Wind Helper
0.123
226910AB2-157 C
Solar/Wind Helper
0.016
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
3132273ORANGE
Solar/Wind Helper
0.049
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
232417X3-008 C
Solar/Wind Helper
0.238
233964AF2-378 GEN
Solar/Wind Helper
0.043
3147666LOUISA
Solar/Wind Helper
0.553
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
233950AC2-186 GEN
Solar/Wind Helper
0.119
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
966881AG1-559 GEN
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
205941AD2-115 GEN
Solar/Wind Helper
0.499
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.777
211065PSPA IPP
Solar/Wind Helper
0.151
960841AF2-375 GEN
Solar/Wind Harmer
0.624
23779801AA1-109
Solar/Wind Helper
0.208
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
226929AD2-058 GEN
Solar/Wind Helper
0.108
3141426STAFORD
Solar/Wind Helper
0.058
315651AD1-115 GEN
Solar/Wind Helper
0.883
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
959381AF2-229 GEN
Solar/Wind Helper
0.368
20390526W1-045 C
Solar/Wind Helper
0.361
205943AE1-185 GEN
Solar/Wind Helper
0.521
205956AE1-196_GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.238
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
230434AG1-499 GEN
Solar/Wind Helper
0.234
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
20675128HRM_W1-127
Solar/Wind Helper
0.03
270119AB2-067 GEN1
50/50
7.05
270120AB2-067 GEN2
50/50
7.05
24318905MLG2
50/50
7.451
270054AF2-122 C O1
Solar/Wind Harmer
4.054
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
946101AF1-275 GEN
Solar/Wind Harmer
1.838
253383AE2-342_GEN
Solar/Wind Harmer
1.057
938701AE1-092 GEN
Solar/Wind Harmer
24.428
942861AE2-305 GEN
Solar/Wind Harmer
9.201
270462AD2-086
Solar/Wind Harmer
8.12
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
253415AE1-040 GEN
Solar/Wind Harmer
1.252
25326109MON D
Adder
1.457
246937BC-WTG2
Solar/Wind Harmer
4.329
971073AG2-665 GEN
Solar/Wind Harmer
8.835
970879AG2-548 GEN
Solar/Wind Harmer
1.284
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
942801AE2-298 GEN
Solar/Wind Harmer
1.666
247607V1-011 GEN
Solar/Wind Harmer
4.348
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
270247TR4_N_V136
Solar/Wind Harmer
0.933
247522W1-056 GEN
Solar/Wind Harmer
2.469
253349AC2-067 GEN
Solar/Wind Harmer
2.225
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944231AF1-091 GEN
Solar/Wind Harmer
19.433
942221AE2-234 GEN
Solar/Wind Harmer
3.759
944541AF1-119 GEN
Solar/Wind Harmer
4.494
960971AF2-388 GEN
Solar/Wind Harmer
11.731
247620Y3-023
Adder
0.492
970349AG2-230 GEN
Solar/Wind Harmer
16.027
247621Y3-024
Adder
0.257
25183208HLCRTG
Solar/Wind Harmer
6.454
970883AG2-550 GEN
Solar/Wind Harmer
10.668
970885AG2-551 GEN
Solar/Wind Harmer
2.481
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
270201AC2-176 GEN
Solar/Wind Harmer
5.48
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
24728905RICHG2
Adder
3.989
970935AG2-582 GEN
Adder
238.716
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
238148AE2-230_GEN2
Solar/Wind Helper
0.556
238149AF1-291A_GEN
Solar/Wind Helper
0.159
237061AD1-155 GEN
Solar/Wind Helper
1.974
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
23585401KL_K28_T16
Solar/Wind Helper
1.534
235020AA1-095 C
Solar/Wind Helper
0.058
238117U2-030
Solar/Wind Helper
0.357
238221AF1-254 C O1
Solar/Wind Helper
0.297
237080AD1-060 GEN
Solar/Wind Helper
0.369
235062AE1-101 C1
Solar/Wind Helper
1.786
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
237006AB1-125 GEN
Solar/Wind Helper
0.132
316006AB2-029 C
Solar/Wind Helper
0.131
223401AF1-299 GEN
Solar/Wind Helper
0.389
223402AF1-300 C
Solar/Wind Helper
0.389
316045AC1-158 PL2
Solar/Wind Helper
4.643
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
232424Y1-079 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.581
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
232410W1-006 C
Solar/Wind Helper
0.518
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
966001AG1-469 GEN
Solar/Wind Helper
0.256
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.152
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
24318805MLG1
50/50
10
23559001PLEAS1
50/50
5.445
270051AF1-062 GEN
50/50
11.971
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
270518AE2-148 GEN
Solar/Wind Harmer
13.997
958581AF2-149 GEN
Solar/Wind Harmer
4.955
971199AH1-059 GEN
Solar/Wind Harmer
2.432
24721905FLATG4
Adder
23.444
253325AC1-069 GEN
Solar/Wind Harmer
1.205
970065AG2-057 GEN
Solar/Wind Harmer
0.972
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
961961AG1-039 GEN
Solar/Wind Harmer
3.18
246938BC-WTG3
Solar/Wind Harmer
4.404
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
970879AG2-548 GEN
Solar/Wind Harmer
8.835
958091AF2-103 GEN
Solar/Wind Harmer
0.178
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270043AE2-236 GEN
Solar/Wind Harmer
5.961
944531AF1-118 GEN
Solar/Wind Harmer
37.819
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971191AH1-055 GEN
Solar/Wind Harmer
20.005
971347AH1-153 GEN
Solar/Wind Harmer
5.342
247643Z2-116 C
Solar/Wind Harmer
0.074
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25196608WSDLE5
Adder
9.116
25194608D.CRK4
Adder
1.747
270367AC2-061_GEN
Solar/Wind Harmer
3.375
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
25196008MFTGT1
Adder
1.409
274752CRETE EC ;2U
Adder
8.571
274753CRETE EC ;3U
Adder
8.571
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274811UNIV PK N;7U
Adder
5.194
274803UNIV PARK;6U
Adder
6.031
274826FISK ;BP
Adder
11.319
972038AH1-567 GEN2
Adder
0.377
972259AH1-714 GEN
Adder
19.698
274676JOLIET 29;8U
Adder
30.477
274729ELWOOD EC;1P
Adder
16.929
274730ELWOOD EC;6P
Adder
16.929
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238108AE1-109 GEN1
Solar/Wind Helper
0.122
238110AE1-109 GEN3
Solar/Wind Helper
0.122
238152AF2-075_GEN
Solar/Wind Helper
0.794
238175AF1-290_GEN
Solar/Wind Helper
0.173
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
235063AE1-101 C2
Solar/Wind Helper
1.786
237001AB1-127_GEN
Solar/Wind Helper
0.476
316415AF1-147_GEN2
Solar/Wind Helper
0.984
23562501BACKB
Solar/Wind Helper
1
316447AC1-158 HLD
Solar/Wind Helper
3.193
316044AC1-158 PL1
Solar/Wind Helper
1.451
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.521
233918AB1-142 GEN
Solar/Wind Helper
0.514
233944AB2-135 GEN
Solar/Wind Helper
0.603
232426Y1-080 FULL
Solar/Wind Helper
0.04
3147666LOUISA
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
232408W1-005 C
Solar/Wind Helper
0.518
316192AB2-158 GEN
Solar/Wind Helper
1.618
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674628WNG_W3-110
Solar/Wind Helper
0.09
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674928WA_W3-044
Solar/Wind Helper
0.099
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.573
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.151
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
MECLTFEXP_MEC->PJM
CLTF
15.924
SIGELTFEXP_SIGE->PJM
CLTF
0.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
NYPJM->LTFIMP_NY
CLTF
4.574
LGEELTFEXP_LGEE->PJM
CLTF
6.731
WECLTFEXP_WEC->PJM
CLTF
3.853
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4761.71
MW Contribution:
7.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.91 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2513.45
MW Contribution:
4.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.291
24729505KEY G4
50/50
6.793
24653605MOTTVILLE
50/50
0.003
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.776
957201AF2-014 GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
3.627
959331AF2-224 GEN
Solar/Wind Harmer
9.638
963791AG1-232 GEN
Solar/Wind Harmer
11.962
970031AG2-029 GEN
Solar/Wind Harmer
4.557
965041AG1-368 GEN
Solar/Wind Harmer
8.389
270071AF1-092 GEN
Solar/Wind Harmer
14.462
247521TR3_G114
Solar/Wind Harmer
0.259
965051AG1-369 GEN
Solar/Wind Harmer
3.575
971771AH1-392 GEN
Solar/Wind Harmer
5.853
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.913
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.109
274775LINCOLN ;6U
Adder
6.299
274776LINCOLN ;7U
Adder
6.299
274777LINCOLN ;8U
Adder
6.299
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.748
274800UNIV PARK;3U
Adder
4.311
274801UNIV PARK;4U
Adder
4.311
960591AF2-350 GEN
Solar/Wind Harmer
5.152
972228AH1-698 GEN2
Adder
2.728
972227AH1-698 GEN1
Adder
1.92
274687WILL CNTY;4U
Adder
20.467
274687WILL CNTY;4U
Adder
20.467
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.423
274675JOLIET 29;7U
Adder
21.622
274728ELWOOD EC;5P
Adder
11.982
274731ELWOOD EC;2P
Adder
11.982
274733ELWOOD EC;3P
Adder
11.982
274735ELWOOD EC;4P
Adder
11.982
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.964
24727005RPMNG1
50/50
3.31
960861AF2-377 GEN
50/50
2.388
970521AG2-332 GEN
50/50
10.816
24639705ELKHART HY
50/50
0.149
270143AC1-141 CT2_
50/50
2.011
246936BC-WTG1
Solar/Wind Harmer
1.154
270489AE1-102 GEN1
Solar/Wind Harmer
3.723
965421AG1-410 GEN
Solar/Wind Harmer
81.634
965011AG1-365 GEN
Solar/Wind Harmer
13.768
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.86
958861AF2-177 GEN
Solar/Wind Harmer
2.67
945111AF1-176 GEN
Solar/Wind Harmer
10.586
957891AF2-083 GEN
Solar/Wind Harmer
9.711
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.972
970373AG2-245 GEN
Solar/Wind Harmer
11.129
274751CRETE EC ;1U
Adder
6.248
274754CRETE EC ;4U
Adder
6.248
274723RIVER EC ;12
Adder
13.542
274812UNIV PK N;8U
Adder
3.753
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.299
274774LINCOLN ;5U
Adder
6.299
274802UNIV PARK;5U
Adder
4.324
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.679
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.423
274674JOLIET 9 ;6U
Adder
11.228
274732ELWOOD EC;7P
Adder
11.982
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.296
270594AE1-207 GEN
Solar/Wind Harmer
5.638
270032AE2-172
Solar/Wind Harmer
3.356
270005AE1-210 C O1
Solar/Wind Harmer
1.089
274745AC1-111 GEN9
Adder
4.025
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.811
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.769
274682WAUKEGAN ;7U
Adder
12.793
274828WAUKEGAN ;BP
Adder
7.853
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.68
939401AE1-172 GEN
Solar/Wind Harmer
3.677
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971997AH1-543 GEN
Solar/Wind Harmer
2.561
957471AF2-041 GEN
Solar/Wind Harmer
14.489
959081AF2-199 GEN
Solar/Wind Harmer
4.83
971067AG2-660 GEN
Solar/Wind Harmer
1.61
274822ROCKFORD ;11
Adder
13.543
276903AD2-071 C
Solar/Wind Harmer
5.365
970819AG2-516 GEN
Solar/Wind Harmer
5.744
970569AG2-363 GEN
Solar/Wind Harmer
14.349
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.308
274766LEE CO EC;7U
Adder
6.234
276708O09 GEN2
Solar/Wind Harmer
0.165
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.443
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.247
963741AG1-226 GEN
Solar/Wind Harmer
10.345
276621W2-048 GEN
Solar/Wind Harmer
0.21
965911AG1-460 GEN
Solar/Wind Harmer
0.809
24728605AND G2
Adder
2.069
970773AG2-487 GEN
Solar/Wind Harmer
0.62
270317AD1-130_GEN
Solar/Wind Helper
4.168
270485AE1-090_GEN
Solar/Wind Helper
0.328
270391AF1-285 GEN3
Solar/Wind Helper
0.597
270578AF1-285 GEN2
Solar/Wind Helper
0.597
270286AF1-227 GEN2
Solar/Wind Helper
0.701
960841AF2-375 GEN
Solar/Wind Helper
1.192
970833AG2-524 GEN
Solar/Wind Harmer
5.568
970833AG2-524 GEN
Solar/Wind Harmer
3.712
971611AH1-305 GEN
Solar/Wind Harmer
2.999
274744AC1-111 GEN8
Adder
4.025
274746AC1-111 G10
Adder
4.025
970073AG2-061 GEN
Solar/Wind Harmer
1.643
247536S-71 GEN
Solar/Wind Harmer
0.197
971411AH1-196 GEN
Solar/Wind Harmer
7.295
971675AH1-338 GEN
Solar/Wind Harmer
1.895
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276863AD2-134 GEN
Solar/Wind Harmer
0.087
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.659
274823ROCKFORD ;21
Adder
13.445
274856ECOGROVE ;U1
Solar/Wind Harmer
0.112
926823AC1-168 GEN
Solar/Wind Harmer
0.812
970169AG2-114 GEN
Solar/Wind Harmer
4.769
971681AH1-341 GEN
Solar/Wind Harmer
7.649
971549AH1-272 GEN
Solar/Wind Harmer
9.785
972267AH1-718 GEN
Adder
2.795
276741O09 GEN1
Solar/Wind Harmer
0.165
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.155
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.832
946321AF1-296 GEN
Solar/Wind Harmer
2.546
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.952
270543AE2-219 C
Solar/Wind Harmer
3.099
276668AB2-070 GEN1
Solar/Wind Harmer
0.168
276848AB2-070 GEN3
Solar/Wind Harmer
0.167
276849AB2-070 GEN2
Solar/Wind Harmer
0.168
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.847
944221AF1-090 GEN
Solar/Wind Harmer
2.28
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
0.881
270224U2-072_GEN2
Solar/Wind Helper
0.881
270227U2-072_GEN3
Solar/Wind Helper
0.881
270228U2-072_GEN4
Solar/Wind Helper
0.881
270231U2-072_GEN5
Solar/Wind Helper
0.881
966831AG1-554 GEN
Solar/Wind Helper
0.889
270499AE1-146 GEN
Solar/Wind Helper
1.989
945641AF1-229 GEN
Solar/Wind Helper
0.952
965431AG1-411 GEN
50/50
45.352
24727105RPMNG2
50/50
3.311
970583AG2-370 GEN
50/50
2.796
270142AC1-141 CT1_
50/50
2.011
24642205MAYFLWER
50/50
0.03
246938BC-WTG3
Solar/Wind Harmer
1.031
270491AE1-102 GEN2
Solar/Wind Harmer
3.723
965021AG1-366 GEN
Solar/Wind Harmer
4.589
270043AE2-236 GEN
Solar/Wind Harmer
5.206
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.738
24695305TIMB G C
Solar/Wind Harmer
0.527
945111AF1-176 GEN
Solar/Wind Harmer
4.809
971347AH1-153 GEN
Solar/Wind Harmer
2.9
270505AE1-170 C O1
Solar/Wind Harmer
6.075
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.264
274752CRETE EC ;2U
Adder
6.248
274753CRETE EC ;3U
Adder
6.248
274724RIVER EC ;11
Adder
13.377
274814UNIV PK N;0U
Adder
3.786
274807UNIV PK N;3U
Adder
3.778
274811UNIV PK N;7U
Adder
3.753
274772LINCOLN ;3U
Adder
6.299
274803UNIV PARK;6U
Adder
4.324
274826FISK ;BP
Adder
8.11
972038AH1-567 GEN2
Adder
0.27
274887GEN-1.85
Solar/Wind Harmer
0.134
276843GEN-1.7
Solar/Wind Harmer
0.167
276806AD2-047 C O1
Solar/Wind Harmer
2.92
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.004
970707AG2-453 GEN
Solar/Wind Harmer
16.726
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.622
274729ELWOOD EC;1P
Adder
11.982
274730ELWOOD EC;6P
Adder
11.982
274734ELWOOD EC;8P
Adder
11.982
274736ELWOOD EC;9P
Adder
11.982
970289AG2-191 GEN
Solar/Wind Harmer
0.558
946031AF1-268 GEN
Solar/Wind Harmer
4.787
943121AE2-341 GEN
Solar/Wind Harmer
8.427
943591AF1-030 GEN
Solar/Wind Harmer
5.604
270004AE1-209 GEN
Solar/Wind Harmer
1.089
274862TOP CROP ;2U
Solar/Wind Harmer
0.674
970825AG2-519 GEN
Solar/Wind Harmer
3.754
274682WAUKEGAN ;7U
Adder
12.793
276868AE1-113 GEN
Solar/Wind Harmer
0.98
274879MINONK ;1U
Solar/Wind Harmer
0.204
946671AF1-331 GEN
Solar/Wind Harmer
0.519
274855GSG-6 ;RU
Solar/Wind Harmer
0.177
274850MENDOTA H;RU
Solar/Wind Harmer
0.056
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.841
959091AF2-200 GEN
Solar/Wind Harmer
9.659
970571AG2-364 GEN
Solar/Wind Harmer
9.566
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.308
274767LEE CO EC;8U
Adder
6.234
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.155
965091AG1-374 GEN
Solar/Wind Harmer
13.563
965931AG1-462 GEN
Solar/Wind Harmer
11.528
971087AG2-675 GEN
Solar/Wind Harmer
2.411
959611AF2-252 GEN
Solar/Wind Harmer
1.507
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.973
957381AF2-032 GEN
Solar/Wind Harmer
0.92
942481AE2-261 GEN
Solar/Wind Harmer
12.093
970193AG2-126 GEN
Solar/Wind Harmer
5.875
24728705AND G3
Adder
4.327
24728505AND G1
Adder
2.069
942871AE2-306 GEN
Solar/Wind Helper
0.448
270284AF1-227 GEN1
Solar/Wind Helper
1.912
270287AF1-227 GEN3
Solar/Wind Helper
0.701
276820AF1-078_GEN
Solar/Wind Helper
0.338
270541AE2-072 C
Solar/Wind Helper
0.958
24729405KEY G3
50/50
0.371
24729305KEY G2
50/50
0.365
24729205KEY G1
50/50
0.363
247620Y3-023
50/50
0.463
960851AF2-376 GEN
50/50
2.077
24643105BUCHANAN
50/50
0.01
246937BC-WTG2
Solar/Wind Harmer
1.154
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.833
944231AF1-091 GEN
Solar/Wind Harmer
16.013
944541AF1-119 GEN
Solar/Wind Harmer
0.423
960971AF2-388 GEN
Solar/Wind Harmer
3.72
970349AG2-230 GEN
Solar/Wind Harmer
8.699
961051AF2-396 GEN
Solar/Wind Harmer
11.565
961051AF2-396 GEN
Solar/Wind Harmer
7.71
270031AE2-169
Solar/Wind Harmer
3.074
270599AE1-208 GEN
Solar/Wind Harmer
5.123
965681AG1-436 GEN
Solar/Wind Harmer
6.895
965791AG1-447 GEN
Solar/Wind Harmer
5.056
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.406
247621Y3-024
Adder
0.181
274805UNIV PK N;1U
Adder
3.762
274808UNIV PK N;4U
Adder
3.737
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.299
274771LINCOLN ;2U
Adder
6.299
274888KELLY CRK;1U
Solar/Wind Harmer
0.3
276776AD2-060 GEN
Solar/Wind Harmer
0.55
958011AF2-095 GEN
Solar/Wind Harmer
7.42
970941AG2-585 GEN
Solar/Wind Harmer
2.834
276897AD1-100 C
Solar/Wind Harmer
12.751
274674JOLIET 9 ;6U
Adder
11.228
276893AG1-478 C
Solar/Wind Harmer
0.339
970291AG2-192 GEN
Solar/Wind Harmer
0.659
970291AG2-192 GEN
Solar/Wind Harmer
0.304
971613AH1-306 GEN
Solar/Wind Harmer
2.416
958481AF2-142 GEN
Solar/Wind Harmer
7.489
274696ROCKY RD ;4P
Adder
8.116
274695ROCKY RD ;2P
Adder
7.929
274693ROCKY RD ;1P
Adder
7.851
274697ROCKY RD ;3P
Adder
2.154
274683WAUKEGAN ;8U
Adder
14.981
274683WAUKEGAN ;8U
Adder
12.628
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
7.394
962691AG1-118 GEN
Solar/Wind Harmer
14.789
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.659
971343AH1-151 GEN
Solar/Wind Harmer
9.659
972235AH1-702 GEN1
Adder
1.735
972236AH1-702 GEN2
Adder
1.509
938861AE1-114 GEN
Solar/Wind Harmer
2.691
274764LEE CO EC;5U
Adder
6.323
274765LEE CO EC;6U
Adder
6.323
274762LEE CO EC;3U
Adder
6.308
274763LEE CO EC;4U
Adder
6.249
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.754
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.527
942111AE2-223 GEN
Solar/Wind Harmer
1.496
960611AF2-352 GEN
Solar/Wind Harmer
1.507
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.427
970885AG2-551 GEN
Solar/Wind Harmer
1.476
970241AG2-163 GEN
Solar/Wind Harmer
2.55
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.043
276838X2-022 GEN2
Solar/Wind Harmer
0.236
276916AD2-100_GEN
Solar/Wind Harmer
8.418
276911AD2-131_GEN
Solar/Wind Harmer
0.555
945391AF1-204 GEN
Solar/Wind Harmer
4.161
970623AG2-406 GEN
Solar/Wind Harmer
0.646
971587AH1-292 GEN
Solar/Wind Harmer
2.428
247607V1-011 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
3.77
247522W1-056 GEN
Solar/Wind Helper
1.187
253378AE2-206_GEN
Solar/Wind Helper
0.725
270349AD2-093_GEN
Solar/Wind Helper
0.869
270471AD2-092_GEN
Solar/Wind Helper
0.869
241960AC2-195 GEN
Solar/Wind Helper
0.709
990497J1323
External Queue
1.5952997207641602
990792J1392
External Queue
5.487830638885498
LAGNLTFEXP_LAGN->PJM
CLTF
5.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.274
TVALTFEXP_TVA->PJM
CLTF
2.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.114
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.636
MECLTFEXP_MEC->PJM
CLTF
9.653
SIGELTFEXP_SIGE->PJM
CLTF
0.197
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.784
NYPJM->LTFIMP_NY
CLTF
1.314
LGEELTFEXP_LGEE->PJM
CLTF
1.767
WECLTFEXP_WEC->PJM
CLTF
2.626
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.9 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5297.56
MW Contribution:
7.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.726
24344105CKG2
50/50
10.12
962761AG1-125 GEN
Solar/Wind Harmer
74.4
970149AG2-104 GEN
Solar/Wind Harmer
40.177
970155AG2-107 GEN
Solar/Wind Harmer
47.51
274773LINCOLN ;4U
Adder
10.701
274774LINCOLN ;5U
Adder
10.701
274723RIVER EC ;12
Adder
22.518
24639705ELKHART HY
Adder
0.193
274751CRETE EC ;1U
Adder
10.338
274754CRETE EC ;4U
Adder
10.338
274812UNIV PK N;8U
Adder
6.271
957891AF2-083 GEN
Solar/Wind Harmer
14.548
274802UNIV PARK;5U
Adder
7.287
945111AF1-176 GEN
Solar/Wind Harmer
15.539
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.275
274676JOLIET 29;8U
Adder
38.191
274674JOLIET 9 ;6U
Adder
19.151
274732ELWOOD EC;7P
Adder
20.437
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.515
274745AC1-111 GEN9
Adder
6.924
270055AF2-134 C O1
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.615
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.395
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.104
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
13.576
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.138
939401AE1-172 GEN
Solar/Wind Harmer
6.395
962781AG1-127 GEN
Solar/Wind Harmer
8.134
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.993
971997AH1-543 GEN
Solar/Wind Harmer
4.466
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.605
957471AF2-041 GEN
Solar/Wind Harmer
25.396
959081AF2-199 GEN
Solar/Wind Harmer
8.465
971067AG2-660 GEN
Solar/Wind Harmer
2.822
965651AG1-433 GEN
Solar/Wind Harmer
2.481
274822ROCKFORD ;11
Adder
23.769
970819AG2-516 GEN
Solar/Wind Harmer
10.109
970569AG2-363 GEN
Solar/Wind Harmer
25.234
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.167
274766LEE CO EC;7U
Adder
11.036
958861AF2-177 GEN
Solar/Wind Harmer
3.623
276708O09 GEN2
Solar/Wind Harmer
0.294
276646AC1-214 GEN2
Solar/Wind Harmer
0.326
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.579
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.871
276621W2-048 GEN
Solar/Wind Harmer
0.396
270594AE1-207 GEN
Solar/Wind Harmer
8.855
270032AE2-172
Solar/Wind Harmer
5.271
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.696
965911AG1-460 GEN
Solar/Wind Harmer
1.557
270005AE1-210 C O1
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
2.723
965421AG1-410 GEN
Solar/Wind Harmer
22.474
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.436
246936BC-WTG1
Solar/Wind Harmer
0.297
270489AE1-102 GEN1
Solar/Wind Harmer
0.958
24728605AND G2
Adder
3.974
970091AG2-072 GEN
Adder
78.436
970773AG2-487 GEN
Solar/Wind Harmer
1.228
270317AD1-130_GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.059
24723205RIVRG3
Adder
16.391
24721605FLATG1
50/50
1.726
270071AF1-092 GEN
Solar/Wind Harmer
17.295
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
10.701
274776LINCOLN ;7U
Adder
10.701
274777LINCOLN ;8U
Adder
10.701
971771AH1-392 GEN
Solar/Wind Harmer
8.847
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
8.138
274827FISK ;RP
Adder
9.698
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.72
972228AH1-698 GEN2
Adder
4.629
972227AH1-698 GEN1
Adder
3.26
274800UNIV PARK;3U
Adder
7.284
274801UNIV PARK;4U
Adder
7.284
970031AG2-029 GEN
Solar/Wind Harmer
4.711
274687WILL CNTY;4U
Adder
34.799
274687WILL CNTY;4U
Adder
34.799
274675JOLIET 29;7U
Adder
38.191
274675JOLIET 29;7U
Adder
36.827
274728ELWOOD EC;5P
Adder
20.437
274731ELWOOD EC;2P
Adder
20.436
274733ELWOOD EC;3P
Adder
20.436
274735ELWOOD EC;4P
Adder
20.436
970833AG2-524 GEN
Solar/Wind Harmer
9.54
970833AG2-524 GEN
Solar/Wind Harmer
6.36
274744AC1-111 GEN8
Adder
6.924
274746AC1-111 G10
Adder
6.924
959331AF2-224 GEN
Solar/Wind Harmer
6.031
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
2.844
959141AF2-205 GEN
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
3.313
971411AH1-196 GEN
Solar/Wind Harmer
12.74
276861AD2-134 GEN
Solar/Wind Harmer
0.151
276863AD2-134 GEN
Solar/Wind Harmer
0.151
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
5.051
971171AH1-044 GEN
Solar/Wind Harmer
16.931
274823ROCKFORD ;21
Adder
23.596
970169AG2-114 GEN
Solar/Wind Harmer
8.419
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.43
971681AH1-341 GEN
Solar/Wind Harmer
13.512
972267AH1-718 GEN
Adder
4.973
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.294
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.684
946321AF1-296 GEN
Solar/Wind Harmer
4.596
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
11.059
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.499
965041AG1-368 GEN
Solar/Wind Harmer
8.029
970289AG2-191 GEN
Solar/Wind Harmer
1.518
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.297
971549AH1-272 GEN
Solar/Wind Harmer
16.346
247521TR3_G114
Solar/Wind Harmer
0.284
965051AG1-369 GEN
Solar/Wind Harmer
3.91
944221AF1-090 GEN
Solar/Wind Harmer
4.487
964611AG1-324 GEN
Solar/Wind Harmer
2.967
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.934
247536S-71 GEN
Solar/Wind Harmer
0.293
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.979
270007AE1-245 C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
971029AG2-637 GEN
Solar/Wind Harmer
10.316
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.938
24722005FLATG5
50/50
1.726
24721905FLATG4
50/50
31.534
962771AG1-126 GEN
Solar/Wind Harmer
74.4
970153AG2-106 GEN
Solar/Wind Harmer
47.51
971347AH1-153 GEN
Solar/Wind Harmer
4.619
270043AE2-236 GEN
Solar/Wind Harmer
5.83
944531AF1-118 GEN
Solar/Wind Harmer
39.701
274772LINCOLN ;3U
Adder
10.701
274724RIVER EC ;11
Adder
22.258
274752CRETE EC ;2U
Adder
10.338
274753CRETE EC ;3U
Adder
10.338
970707AG2-453 GEN
Solar/Wind Harmer
28.587
274814UNIV PK N;0U
Adder
6.326
274807UNIV PK N;3U
Adder
6.312
274811UNIV PK N;7U
Adder
6.271
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
9.169
972259AH1-714 GEN
Adder
23.869
274826FISK ;BP
Adder
13.684
274803UNIV PARK;6U
Adder
7.287
274887GEN-1.85
Solar/Wind Harmer
0.227
276843GEN-1.7
Solar/Wind Harmer
0.282
276806AD2-047 C O1
Solar/Wind Harmer
4.941
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.059
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
36.827
274729ELWOOD EC;1P
Adder
20.436
274730ELWOOD EC;6P
Adder
20.437
274734ELWOOD EC;8P
Adder
20.437
274736ELWOOD EC;9P
Adder
20.437
943121AE2-341 GEN
Solar/Wind Harmer
14.508
943591AF1-030 GEN
Solar/Wind Harmer
9.648
965021AG1-366 GEN
Solar/Wind Harmer
2.872
274862TOP CROP ;2U
Solar/Wind Harmer
1.159
274682WAUKEGAN ;7U
Adder
22.104
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.703
274879MINONK ;1U
Solar/Wind Harmer
0.355
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274855GSG-6 ;RU
Solar/Wind Harmer
0.31
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
16.931
970571AG2-364 GEN
Solar/Wind Harmer
16.823
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.167
274767LEE CO EC;8U
Adder
11.036
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.328
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
965091AG1-374 GEN
Solar/Wind Harmer
24.6
959611AF2-252 GEN
Solar/Wind Harmer
2.733
24386205FR-12G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
20.87
971087AG2-675 GEN
Solar/Wind Harmer
4.365
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.879
971993AH1-541 GEN
Solar/Wind Harmer
3.686
957381AF2-032 GEN
Solar/Wind Harmer
1.767
942481AE2-261 GEN
Solar/Wind Harmer
23.27
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
5.778
24695305TIMB G C
Solar/Wind Harmer
0.648
946031AF1-268 GEN
Solar/Wind Harmer
7.259
970193AG2-126 GEN
Solar/Wind Harmer
11.441
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.403
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.266
270491AE1-102 GEN2
Solar/Wind Harmer
0.958
24728705AND G3
Adder
8.312
24728505AND G1
Adder
3.974
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
24721705FLATG2
50/50
25.639
270102X2-052 ST
50/50
2.04
270100X2-052 CT1
50/50
1.885
270101X2-052 CT2
50/50
1.885
970349AG2-230 GEN
Solar/Wind Harmer
13.856
965681AG1-436 GEN
Solar/Wind Harmer
11.105
965791AG1-447 GEN
Solar/Wind Harmer
8.144
274770LINCOLN ;1U
Adder
10.701
274771LINCOLN ;2U
Adder
10.701
274805UNIV PK N;1U
Adder
6.285
274808UNIV PK N;4U
Adder
6.243
247620Y3-023
Adder
0.576
274888KELLY CRK;1U
Solar/Wind Harmer
0.509
276776AD2-060 GEN
Solar/Wind Harmer
0.93
958011AF2-095 GEN
Solar/Wind Harmer
12.557
970941AG2-585 GEN
Solar/Wind Harmer
4.796
276897AD1-100 C
Solar/Wind Harmer
21.761
274674JOLIET 9 ;6U
Adder
19.151
961051AF2-396 GEN
Solar/Wind Harmer
17.344
961051AF2-396 GEN
Solar/Wind Harmer
11.563
276893AG1-478 C
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.031
274695ROCKY RD ;2P
Adder
13.708
274693ROCKY RD ;1P
Adder
13.573
274697ROCKY RD ;3P
Adder
3.724
958481AF2-142 GEN
Solar/Wind Harmer
12.877
274683WAUKEGAN ;8U
Adder
25.9
274683WAUKEGAN ;8U
Adder
21.833
962691AG1-118 GEN
Solar/Wind Harmer
25.676
958491AF2-143 GEN
Solar/Wind Harmer
12.799
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
16.931
971343AH1-151 GEN
Solar/Wind Harmer
16.931
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.565
960971AF2-388 GEN
Solar/Wind Harmer
4.962
972235AH1-702 GEN1
Adder
3.049
972236AH1-702 GEN2
Adder
2.651
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
4.755
274764LEE CO EC;5U
Adder
11.194
274765LEE CO EC;6U
Adder
11.194
274762LEE CO EC;3U
Adder
11.167
274763LEE CO EC;4U
Adder
11.062
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.343
276645AC1-214 GEN1
Solar/Wind Harmer
0.326
942111AE2-223 GEN
Solar/Wind Harmer
2.688
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
3.3
960611AF2-352 GEN
Solar/Wind Harmer
2.733
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.927
970291AG2-192 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.479
970241AG2-163 GEN
Solar/Wind Harmer
4.651
270031AE2-169
Solar/Wind Harmer
4.369
270599AE1-208 GEN
Solar/Wind Harmer
7.282
276615X2-022 GEN
Solar/Wind Harmer
0.082
276838X2-022 GEN2
Solar/Wind Harmer
0.445
971613AH1-306 GEN
Solar/Wind Harmer
3.795
270246TR4_N_V150
Solar/Wind Harmer
0.05
270247TR4_N_V136
Solar/Wind Harmer
0.05
276916AD2-100_GEN
Solar/Wind Harmer
16.28
276911AD2-131_GEN
Solar/Wind Harmer
1.072
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
17.757
945391AF1-204 GEN
Solar/Wind Harmer
8.104
964611AG1-324 GEN
Solar/Wind Harmer
0.571
270201AC2-176 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.257
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.297
971587AH1-292 GEN
Solar/Wind Harmer
5.361
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.112
970885AG2-551 GEN
Solar/Wind Harmer
2.371
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.29
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.474
24728905RICHG2
Adder
3.474
24723005RIVRG1
Adder
16.391
24723105RIVRG2
Adder
16.391
LAGNLTFEXP_LAGN->PJM
CLTF
16.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.242
TVALTFEXP_TVA->PJM
CLTF
7.96
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.416
MECLTFEXP_MEC->PJM
CLTF
18.61
SIGELTFEXP_SIGE->PJM
CLTF
0.498
CPLELTFEXP_CPLE->PJM
CLTF
3.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.551
NYPJM->LTFIMP_NY
CLTF
3.901
LGEELTFEXP_LGEE->PJM
CLTF
5.998
WECLTFEXP_WEC->PJM
CLTF
4.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4473.55
MW Contribution:
7.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
4.711
24722005FLATG5
50/50
4.711
24721905FLATG4
50/50
86.05
270475AD2-096_GEN
50/50
10.483
270142AC1-141 CT1_
50/50
3.456
24642205MAYFLWER
50/50
0.053
944961AF1-161 GEN
50/50
4.124
962601AG1-109 GEN
50/50
4.124
962771AG1-126 GEN
Solar/Wind Harmer
109.537
970153AG2-106 GEN
Solar/Wind Harmer
69.947
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270043AE2-236 GEN
Solar/Wind Harmer
6.765
971347AH1-153 GEN
Solar/Wind Harmer
5.221
965021AG1-366 GEN
Solar/Wind Harmer
3.44
270391AF1-285 GEN3
Solar/Wind Harmer
0.682
270063AE2-323 C
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
10.472
944531AF1-118 GEN
Solar/Wind Harmer
44.69
945111AF1-176 GEN
Solar/Wind Harmer
8.069
274772LINCOLN ;3U
Adder
11.612
274724RIVER EC ;11
Adder
24.187
274752CRETE EC ;2U
Adder
11.245
274753CRETE EC ;3U
Adder
11.245
274814UNIV PK N;0U
Adder
6.855
274807UNIV PK N;3U
Adder
6.84
274811UNIV PK N;7U
Adder
6.795
970707AG2-453 GEN
Solar/Wind Harmer
30.807
24695305TIMB G C
Solar/Wind Harmer
0.797
274803UNIV PARK;6U
Adder
7.869
274826FISK ;BP
Adder
14.772
274887GEN-1.85
Solar/Wind Harmer
0.244
276843GEN-1.7
Solar/Wind Harmer
0.304
276806AD2-047 C O1
Solar/Wind Harmer
5.33
972038AH1-567 GEN2
Adder
0.492
972259AH1-714 GEN
Adder
25.709
246938BC-WTG3
Solar/Wind Harmer
0.338
270491AE1-102 GEN2
Solar/Wind Harmer
1.219
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
39.574
274729ELWOOD EC;1P
Adder
21.939
24721805FLATG3
50/50
4.711
24344105CKG2
50/50
11.483
270143AC1-141 CT2_
50/50
3.456
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.675
24307105BERRINSP G
50/50
0.03
962761AG1-125 GEN
Solar/Wind Harmer
109.537
970149AG2-104 GEN
Solar/Wind Harmer
59.152
970155AG2-107 GEN
Solar/Wind Harmer
69.947
965011AG1-365 GEN
Solar/Wind Harmer
10.32
957891AF2-083 GEN
Solar/Wind Harmer
16.606
945111AF1-176 GEN
Solar/Wind Harmer
17.763
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
5.166
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
274773LINCOLN ;4U
Adder
11.612
274774LINCOLN ;5U
Adder
11.612
274723RIVER EC ;12
Adder
24.471
274751CRETE EC ;1U
Adder
11.245
274754CRETE EC ;4U
Adder
11.245
965421AG1-410 GEN
Solar/Wind Harmer
28.412
970373AG2-245 GEN
Solar/Wind Harmer
19.884
274812UNIV PK N;8U
Adder
6.795
274802UNIV PARK;5U
Adder
7.869
246936BC-WTG1
Solar/Wind Harmer
0.378
270489AE1-102 GEN1
Solar/Wind Harmer
1.219
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
41.04
270055AF2-134 C O1
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
20.564
274732ELWOOD EC;7P
Adder
21.94
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.726
274745AC1-111 GEN9
Adder
7.404
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.902
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.486
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
23.522
958861AF2-177 GEN
Solar/Wind Harmer
3.956
274828WAUKEGAN ;BP
Adder
14.44
24721705FLATG2
50/50
69.962
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.277
270100X2-052 CT1
50/50
2.104
270101X2-052 CT2
50/50
2.104
24643105BUCHANAN
50/50
0.018
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
15.664
961051AF2-396 GEN
Solar/Wind Harmer
19.838
961051AF2-396 GEN
Solar/Wind Harmer
13.225
965681AG1-436 GEN
Solar/Wind Harmer
12.356
965791AG1-447 GEN
Solar/Wind Harmer
9.061
270462AD2-086
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
11.612
274771LINCOLN ;2U
Adder
11.612
270246TR4_N_V150
Solar/Wind Harmer
0.061
270247TR4_N_V136
Solar/Wind Harmer
0.061
274805UNIV PK N;1U
Adder
6.81
274808UNIV PK N;4U
Adder
6.766
274888KELLY CRK;1U
Solar/Wind Harmer
0.548
276776AD2-060 GEN
Solar/Wind Harmer
1.003
958011AF2-095 GEN
Solar/Wind Harmer
13.543
970941AG2-585 GEN
Solar/Wind Harmer
5.173
246937BC-WTG2
Solar/Wind Harmer
0.378
276897AD1-100 C
Solar/Wind Harmer
23.396
944231AF1-091 GEN
Solar/Wind Harmer
21.57
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
20.564
276893AG1-478 C
Solar/Wind Harmer
0.621
944541AF1-119 GEN
Solar/Wind Harmer
0.62
960971AF2-388 GEN
Solar/Wind Harmer
5.451
958481AF2-142 GEN
Solar/Wind Harmer
13.721
274695ROCKY RD ;2P
Adder
14.592
274693ROCKY RD ;1P
Adder
14.449
274697ROCKY RD ;3P
Adder
3.964
274696ROCKY RD ;4P
Adder
14.936
942221AE2-234 GEN
Solar/Wind Harmer
3.664
274683WAUKEGAN ;8U
Adder
27.547
274683WAUKEGAN ;8U
Adder
23.221
962691AG1-118 GEN
Solar/Wind Harmer
27.25
958491AF2-143 GEN
Solar/Wind Harmer
13.572
276901AD2-066 C O1
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.823
971343AH1-151 GEN
Solar/Wind Harmer
17.823
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.202
972236AH1-702 GEN2
Adder
2.785
970623AG2-406 GEN
Solar/Wind Harmer
1.615
938861AE1-114 GEN
Solar/Wind Harmer
4.972
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274764LEE CO EC;5U
Adder
11.687
274765LEE CO EC;6U
Adder
11.687
274762LEE CO EC;3U
Adder
11.659
274763LEE CO EC;4U
Adder
11.55
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.395
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.774
270031AE2-169
Solar/Wind Harmer
4.65
270599AE1-208 GEN
Solar/Wind Harmer
7.749
960611AF2-352 GEN
Solar/Wind Harmer
2.8
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.946
970291AG2-192 GEN
Solar/Wind Harmer
1.081
970291AG2-192 GEN
Solar/Wind Harmer
0.499
971613AH1-306 GEN
Solar/Wind Harmer
3.949
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.604
970241AG2-163 GEN
Solar/Wind Harmer
4.646
970621AG2-405 GEN
Solar/Wind Harmer
1.449
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
247621Y3-024
Adder
0.272
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
926881AC1-175 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
15.862
276911AD2-131_GEN
Solar/Wind Harmer
1.045
970883AG2-550 GEN
Solar/Wind Harmer
7.401
970885AG2-551 GEN
Solar/Wind Harmer
2.467
270383AD1-128 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.788
971587AH1-292 GEN
Solar/Wind Harmer
4.757
24728805RICHG1
Adder
3.35
24728905RICHG2
Adder
3.35
970329AG2-216 GEN
Solar/Wind Harmer
2.663
25326509SID D
Adder
1.142
270144AC1-141 ST1_
50/50
3.051
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.268
24653605MOTTVILLE
50/50
0.005
959331AF2-224 GEN
Solar/Wind Harmer
7.224
270578AF1-285 GEN2
Solar/Wind Harmer
0.682
270071AF1-092 GEN
Solar/Wind Harmer
19.599
970031AG2-029 GEN
Solar/Wind Harmer
5.461
971771AH1-392 GEN
Solar/Wind Harmer
10.022
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24729505KEY G4
Adder
9.105
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.376
965041AG1-368 GEN
Solar/Wind Harmer
9.736
274775LINCOLN ;6U
Adder
11.612
274776LINCOLN ;7U
Adder
11.612
274777LINCOLN ;8U
Adder
11.612
247521TR3_G114
Solar/Wind Harmer
0.347
965051AG1-369 GEN
Solar/Wind Harmer
4.782
963791AG1-232 GEN
Solar/Wind Harmer
12.72
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.469
960591AF2-350 GEN
Solar/Wind Harmer
9.405
274800UNIV PARK;3U
Adder
7.859
274801UNIV PARK;4U
Adder
7.859
972228AH1-698 GEN2
Adder
4.989
972227AH1-698 GEN1
Adder
3.513
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.188
274687WILL CNTY;4U
Adder
37.422
274687WILL CNTY;4U
Adder
37.422
274675JOLIET 29;7U
Adder
41.04
274675JOLIET 29;7U
Adder
39.575
274728ELWOOD EC;5P
Adder
21.94
274731ELWOOD EC;2P
Adder
21.939
274733ELWOOD EC;3P
Adder
21.939
274735ELWOOD EC;4P
Adder
21.939
970833AG2-524 GEN
Solar/Wind Harmer
10.228
970833AG2-524 GEN
Solar/Wind Harmer
6.819
971549AH1-272 GEN
Solar/Wind Harmer
19.166
962781AG1-127 GEN
Solar/Wind Harmer
8.625
939401AE1-172 GEN
Solar/Wind Harmer
6.778
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.051
971997AH1-543 GEN
Solar/Wind Harmer
4.72
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.201
957471AF2-041 GEN
Solar/Wind Harmer
26.735
959081AF2-199 GEN
Solar/Wind Harmer
8.912
971067AG2-660 GEN
Solar/Wind Harmer
2.971
274822ROCKFORD ;11
Adder
24.99
970819AG2-516 GEN
Solar/Wind Harmer
10.604
945371AF1-202 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
26.447
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.659
274766LEE CO EC;7U
Adder
11.522
276708O09 GEN2
Solar/Wind Harmer
0.306
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.948
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.214
270032AE2-172
Solar/Wind Harmer
5.485
270005AE1-210 C O1
Solar/Wind Harmer
1.752
276903AD2-071 C
Solar/Wind Harmer
8.936
970825AG2-519 GEN
Solar/Wind Harmer
2.836
963741AG1-226 GEN
Solar/Wind Harmer
18.848
276621W2-048 GEN
Solar/Wind Harmer
0.393
965911AG1-460 GEN
Solar/Wind Harmer
1.522
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.54
24728605AND G2
Adder
3.831
970773AG2-487 GEN
Solar/Wind Harmer
1.192
23906502RICHG2&3
Adder
1.11
274744AC1-111 GEN8
Adder
7.404
274746AC1-111 G10
Adder
7.404
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
3.016
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.448
971675AH1-338 GEN
Solar/Wind Harmer
3.496
276861AD2-134 GEN
Solar/Wind Harmer
0.16
276863AD2-134 GEN
Solar/Wind Harmer
0.16
971611AH1-305 GEN
Solar/Wind Harmer
5.334
270007AE1-245 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.823
274823ROCKFORD ;21
Adder
24.808
274856ECOGROVE ;U1
Solar/Wind Harmer
0.206
945581AF1-223 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.499
970169AG2-114 GEN
Solar/Wind Harmer
8.815
971681AH1-341 GEN
Solar/Wind Harmer
14.132
972267AH1-718 GEN
Adder
5.171
276741O09 GEN1
Solar/Wind Harmer
0.306
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.961
971609AH1-304 GEN
Solar/Wind Harmer
1.381
946321AF1-296 GEN
Solar/Wind Harmer
4.723
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.58
963841AG1-237 GEN
Solar/Wind Harmer
3.532
964611AG1-324 GEN
Solar/Wind Harmer
3.142
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.308
270543AE2-219 C
Solar/Wind Harmer
5.181
944221AF1-090 GEN
Solar/Wind Harmer
4.314
971029AG2-637 GEN
Solar/Wind Harmer
10.609
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
21.94
274734ELWOOD EC;8P
Adder
21.94
274736ELWOOD EC;9P
Adder
21.94
943121AE2-341 GEN
Solar/Wind Harmer
15.518
943591AF1-030 GEN
Solar/Wind Harmer
10.32
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
1.234
274682WAUKEGAN ;7U
Adder
23.522
276868AE1-113 GEN
Solar/Wind Harmer
1.802
274879MINONK ;1U
Solar/Wind Harmer
0.376
946671AF1-331 GEN
Solar/Wind Harmer
0.957
274855GSG-6 ;RU
Solar/Wind Harmer
0.327
274850MENDOTA H;RU
Solar/Wind Harmer
0.104
959091AF2-200 GEN
Solar/Wind Harmer
17.823
970571AG2-364 GEN
Solar/Wind Harmer
17.631
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.659
274767LEE CO EC;8U
Adder
11.522
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.625
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965091AG1-374 GEN
Solar/Wind Harmer
25.202
959611AF2-252 GEN
Solar/Wind Harmer
2.8
247642Z2-115 C
Solar/Wind Harmer
0.003
965931AG1-462 GEN
Solar/Wind Harmer
21.395
971087AG2-675 GEN
Solar/Wind Harmer
4.475
24386205FR-12G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.915
270004AE1-209 GEN
Solar/Wind Harmer
1.752
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.121
970825AG2-519 GEN
Solar/Wind Harmer
6.019
971993AH1-541 GEN
Solar/Wind Harmer
3.688
946031AF1-268 GEN
Solar/Wind Harmer
7.583
957381AF2-032 GEN
Solar/Wind Harmer
1.73
942481AE2-261 GEN
Solar/Wind Harmer
22.758
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.995
24728705AND G3
Adder
8.012
24728505AND G1
Adder
3.831
270541AE2-072 C
Solar/Wind Harmer
0
23906402RICHG1
Adder
1.111
23906502RICHG2&3
Adder
1.11
LAGNLTFEXP_LAGN->PJM
CLTF
11.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.981
TVALTFEXP_TVA->PJM
CLTF
4.815
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.375
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.313
MECLTFEXP_MEC->PJM
CLTF
18.13
SIGELTFEXP_SIGE->PJM
CLTF
0.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.889
NYPJM->LTFIMP_NY
CLTF
3.074
LGEELTFEXP_LGEE->PJM
CLTF
4.556
WECLTFEXP_WEC->PJM
CLTF
4.845
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.158
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.31 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5773.71
MW Contribution:
6.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
80.774
970149AG2-104 GEN
Solar/Wind Harmer
43.619
970155AG2-107 GEN
Solar/Wind Harmer
51.58
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
10.415
274754CRETE EC ;4U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
15.659
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
6.422
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
17.36
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274775LINCOLN ;6U
Adder
10.797
274776LINCOLN ;7U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
5.989
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.434
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
971347AH1-153 GEN
Solar/Wind Harmer
4.684
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274753CRETE EC ;3U
Adder
10.415
270505AE1-170 C O1
Solar/Wind Harmer
9.246
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
0.228
276843GEN-1.7
Solar/Wind Harmer
0.284
276806AD2-047 C O1
Solar/Wind Harmer
4.976
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971997AH1-543 GEN
Solar/Wind Harmer
4.485
957471AF2-041 GEN
Solar/Wind Harmer
25.504
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
965651AG1-433 GEN
Solar/Wind Harmer
2.449
276708O09 GEN2
Solar/Wind Harmer
0.295
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
965911AG1-460 GEN
Solar/Wind Harmer
1.542
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.459
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
965421AG1-410 GEN
Solar/Wind Harmer
21.55
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.196
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
972203AH1-686 GEN
Adder
1.998
970169AG2-114 GEN
Solar/Wind Harmer
8.435
971681AH1-341 GEN
Solar/Wind Harmer
13.557
972267AH1-718 GEN
Adder
4.986
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
17.002
970571AG2-364 GEN
Solar/Wind Harmer
16.871
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
965931AG1-462 GEN
Solar/Wind Harmer
20.885
971087AG2-675 GEN
Solar/Wind Harmer
4.368
965091AG1-374 GEN
Solar/Wind Harmer
24.551
959611AF2-252 GEN
Solar/Wind Harmer
2.728
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.663
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
942481AE2-261 GEN
Solar/Wind Harmer
23.05
270004AE1-209 GEN
Solar/Wind Harmer
1.624
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24695305TIMB G C
Solar/Wind Harmer
0.627
970825AG2-519 GEN
Solar/Wind Harmer
5.579
946031AF1-268 GEN
Solar/Wind Harmer
6.994
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
959341AF2-225 GEN
Solar/Wind Harmer
8.677
946321AF1-296 GEN
Solar/Wind Harmer
4.601
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
10.858
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
971549AH1-272 GEN
Solar/Wind Harmer
16.367
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.859
970289AG2-191 GEN
Solar/Wind Harmer
1.486
971609AH1-304 GEN
Solar/Wind Harmer
1.264
247521TR3_G114
Solar/Wind Harmer
0.275
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.891
247536S-71 GEN
Solar/Wind Harmer
0.278
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
14.053
965681AG1-436 GEN
Solar/Wind Harmer
11.209
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
276776AD2-060 GEN
Solar/Wind Harmer
0.937
958011AF2-095 GEN
Solar/Wind Harmer
12.646
970941AG2-585 GEN
Solar/Wind Harmer
4.83
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
21.908
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.582
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
25.814
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.897
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.686
960611AF2-352 GEN
Solar/Wind Harmer
2.728
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.921
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
270031AE2-169
Solar/Wind Harmer
4.257
270599AE1-208 GEN
Solar/Wind Harmer
7.096
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
276911AD2-131_GEN
Solar/Wind Harmer
1.062
270246TR4_N_V150
Solar/Wind Harmer
0.049
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.284
270383AD1-128 GEN
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
970883AG2-550 GEN
Solar/Wind Harmer
6.689
970885AG2-551 GEN
Solar/Wind Harmer
2.23
270054AF2-122 C O1
Solar/Wind Helper
1.547
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.01 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5028.49
MW Contribution:
7.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
5.165
270144AC1-141 ST1_
50/50
3.155
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.587
24653605MOTTVILLE
50/50
0.006
959331AF2-224 GEN
Solar/Wind Harmer
7.385
270071AF1-092 GEN
Solar/Wind Harmer
20.17
970031AG2-029 GEN
Solar/Wind Harmer
5.617
971771AH1-392 GEN
Solar/Wind Harmer
10.358
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24729505KEY G4
Adder
9.292
274775LINCOLN ;6U
Adder
11.987
274776LINCOLN ;7U
Adder
11.987
274777LINCOLN ;8U
Adder
11.987
965041AG1-368 GEN
Solar/Wind Harmer
9.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
972037AH1-567 GEN1
Adder
0.255
274827FISK ;RP
Adder
10.79
274800UNIV PARK;3U
Adder
8.099
274801UNIV PARK;4U
Adder
8.099
960591AF2-350 GEN
Solar/Wind Harmer
9.692
972228AH1-698 GEN2
Adder
5.142
972227AH1-698 GEN1
Adder
3.62
247521TR3_G114
Solar/Wind Harmer
0.349
965051AG1-369 GEN
Solar/Wind Harmer
4.809
274687WILL CNTY;4U
Adder
38.553
274687WILL CNTY;4U
Adder
38.553
274675JOLIET 29;7U
Adder
42.278
274675JOLIET 29;7U
Adder
40.768
274728ELWOOD EC;5P
Adder
22.596
274731ELWOOD EC;2P
Adder
22.596
274733ELWOOD EC;3P
Adder
22.596
274735ELWOOD EC;4P
Adder
22.596
970833AG2-524 GEN
Solar/Wind Harmer
10.534
970833AG2-524 GEN
Solar/Wind Harmer
7.023
971549AH1-272 GEN
Solar/Wind Harmer
19.703
963791AG1-232 GEN
Solar/Wind Harmer
12.868
274744AC1-111 GEN8
Adder
7.624
274746AC1-111 G10
Adder
7.624
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.313
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
3.1
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.821
971675AH1-338 GEN
Solar/Wind Harmer
3.593
276861AD2-134 GEN
Solar/Wind Harmer
0.164
276863AD2-134 GEN
Solar/Wind Harmer
0.164
971611AH1-305 GEN
Solar/Wind Harmer
5.462
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.31
274823ROCKFORD ;21
Adder
25.482
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
926823AC1-168 GEN
Solar/Wind Harmer
1.537
970169AG2-114 GEN
Solar/Wind Harmer
9.036
971681AH1-341 GEN
Solar/Wind Harmer
14.503
972267AH1-718 GEN
Adder
5.303
270007AE1-245 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.313
274877BISHOP HL;1U
Solar/Wind Harmer
0.294
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.159
946321AF1-296 GEN
Solar/Wind Harmer
4.834
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.383
970289AG2-191 GEN
Solar/Wind Harmer
1.586
963841AG1-237 GEN
Solar/Wind Harmer
3.581
276668AB2-070 GEN1
Solar/Wind Harmer
0.319
276848AB2-070 GEN3
Solar/Wind Harmer
0.317
276849AB2-070 GEN2
Solar/Wind Harmer
0.319
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.111
247536S-71 GEN
Solar/Wind Harmer
0.301
944221AF1-090 GEN
Solar/Wind Harmer
4.35
270543AE2-219 C
Solar/Wind Harmer
5.021
971029AG2-637 GEN
Solar/Wind Harmer
10.16
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24722005FLATG5
50/50
5.165
24721905FLATG4
50/50
94.337
270475AD2-096_GEN
50/50
10.024
270142AC1-141 CT1_
50/50
3.573
24642205MAYFLWER
50/50
0.054
944961AF1-161 GEN
50/50
4.258
962601AG1-109 GEN
50/50
4.258
962771AG1-126 GEN
Solar/Wind Harmer
120.056
970153AG2-106 GEN
Solar/Wind Harmer
76.664
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270043AE2-236 GEN
Solar/Wind Harmer
6.98
971347AH1-153 GEN
Solar/Wind Harmer
5.418
965021AG1-366 GEN
Solar/Wind Harmer
3.517
270063AE2-323 C
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
10.819
945111AF1-176 GEN
Solar/Wind Harmer
8.333
944531AF1-118 GEN
Solar/Wind Harmer
45.71
274772LINCOLN ;3U
Adder
11.987
274724RIVER EC ;11
Adder
24.945
274752CRETE EC ;2U
Adder
11.595
274753CRETE EC ;3U
Adder
11.595
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.066
274807UNIV PK N;3U
Adder
7.051
274811UNIV PK N;7U
Adder
7.005
970707AG2-453 GEN
Solar/Wind Harmer
31.765
274803UNIV PARK;6U
Adder
8.11
274826FISK ;BP
Adder
15.225
972038AH1-567 GEN2
Adder
0.507
274887GEN-1.85
Solar/Wind Harmer
0.252
276843GEN-1.7
Solar/Wind Harmer
0.313
276806AD2-047 C O1
Solar/Wind Harmer
5.492
972259AH1-714 GEN
Adder
26.498
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
40.767
274730ELWOOD EC;6P
Adder
22.596
274734ELWOOD EC;8P
Adder
22.596
274736ELWOOD EC;9P
Adder
22.596
274729ELWOOD EC;1P
Adder
22.596
943121AE2-341 GEN
Solar/Wind Harmer
15.981
943591AF1-030 GEN
Solar/Wind Harmer
10.628
24695305TIMB G C
Solar/Wind Harmer
0.801
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
1.27
274682WAUKEGAN ;7U
Adder
24.202
246938BC-WTG3
Solar/Wind Harmer
0.336
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
276868AE1-113 GEN
Solar/Wind Harmer
1.852
274879MINONK ;1U
Solar/Wind Harmer
0.386
946671AF1-331 GEN
Solar/Wind Harmer
0.983
274855GSG-6 ;RU
Solar/Wind Harmer
0.336
274850MENDOTA H;RU
Solar/Wind Harmer
0.107
959091AF2-200 GEN
Solar/Wind Harmer
18.31
970571AG2-364 GEN
Solar/Wind Harmer
18.089
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.963
274767LEE CO EC;8U
Adder
11.822
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.294
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.799
965931AG1-462 GEN
Solar/Wind Harmer
21.892
971087AG2-675 GEN
Solar/Wind Harmer
4.579
965091AG1-374 GEN
Solar/Wind Harmer
25.724
959611AF2-252 GEN
Solar/Wind Harmer
2.858
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.918
971993AH1-541 GEN
Solar/Wind Harmer
3.746
270004AE1-209 GEN
Solar/Wind Harmer
1.741
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.999
970825AG2-519 GEN
Solar/Wind Harmer
5.97
946031AF1-268 GEN
Solar/Wind Harmer
7.51
957381AF2-032 GEN
Solar/Wind Harmer
1.751
942481AE2-261 GEN
Solar/Wind Harmer
23.025
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
11.007
24728705AND G3
Adder
7.849
24728505AND G1
Adder
3.753
23906402RICHG1
Adder
1.086
23906502RICHG2&3
Adder
1.085
270541AE2-072 C
Solar/Wind Harmer
0
24721805FLATG3
50/50
5.165
24344105CKG2
50/50
11.949
270143AC1-141 CT2_
50/50
3.573
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.205
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
120.056
970149AG2-104 GEN
Solar/Wind Harmer
64.832
970155AG2-107 GEN
Solar/Wind Harmer
76.664
965011AG1-365 GEN
Solar/Wind Harmer
10.55
957891AF2-083 GEN
Solar/Wind Harmer
17.154
945111AF1-176 GEN
Solar/Wind Harmer
18.343
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
5.335
274773LINCOLN ;4U
Adder
11.987
274774LINCOLN ;5U
Adder
11.987
274723RIVER EC ;12
Adder
25.237
274751CRETE EC ;1U
Adder
11.595
274754CRETE EC ;4U
Adder
11.595
274812UNIV PK N;8U
Adder
7.005
970373AG2-245 GEN
Solar/Wind Harmer
20.466
274802UNIV PARK;5U
Adder
8.11
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.277
274674JOLIET 9 ;6U
Adder
21.182
274732ELWOOD EC;7P
Adder
22.596
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.624
965421AG1-410 GEN
Solar/Wind Harmer
28.373
965651AG1-433 GEN
Solar/Wind Harmer
2.763
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.529
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.202
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.213
274828WAUKEGAN ;BP
Adder
14.856
246936BC-WTG1
Solar/Wind Harmer
0.377
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.87
939401AE1-172 GEN
Solar/Wind Harmer
6.964
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.08
971997AH1-543 GEN
Solar/Wind Harmer
4.85
958861AF2-177 GEN
Solar/Wind Harmer
4.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.469
957471AF2-041 GEN
Solar/Wind Harmer
27.465
959081AF2-199 GEN
Solar/Wind Harmer
9.155
971067AG2-660 GEN
Solar/Wind Harmer
3.052
274822ROCKFORD ;11
Adder
25.668
970819AG2-516 GEN
Solar/Wind Harmer
10.889
970569AG2-363 GEN
Solar/Wind Harmer
27.133
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.963
274766LEE CO EC;7U
Adder
11.822
945371AF1-202 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.313
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.212
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.223
270032AE2-172
Solar/Wind Harmer
5.49
963741AG1-226 GEN
Solar/Wind Harmer
19.06
270005AE1-210 C O1
Solar/Wind Harmer
1.741
276903AD2-071 C
Solar/Wind Harmer
8.916
276621W2-048 GEN
Solar/Wind Harmer
0.399
970825AG2-519 GEN
Solar/Wind Harmer
2.813
965911AG1-460 GEN
Solar/Wind Harmer
1.54
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.437
24728605AND G2
Adder
3.753
970773AG2-487 GEN
Solar/Wind Harmer
1.148
23906502RICHG2&3
Adder
1.085
24721705FLATG2
50/50
76.7
247620Y3-023
50/50
0.723
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.175
270101X2-052 CT2
50/50
2.175
24643105BUCHANAN
50/50
0.019
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.255
961051AF2-396 GEN
Solar/Wind Harmer
20.485
961051AF2-396 GEN
Solar/Wind Harmer
13.656
965681AG1-436 GEN
Solar/Wind Harmer
12.767
965791AG1-447 GEN
Solar/Wind Harmer
9.363
274770LINCOLN ;1U
Adder
11.987
274771LINCOLN ;2U
Adder
11.987
274805UNIV PK N;1U
Adder
7.02
274808UNIV PK N;4U
Adder
6.974
274888KELLY CRK;1U
Solar/Wind Harmer
0.565
276776AD2-060 GEN
Solar/Wind Harmer
1.034
958011AF2-095 GEN
Solar/Wind Harmer
13.957
970941AG2-585 GEN
Solar/Wind Harmer
5.331
276897AD1-100 C
Solar/Wind Harmer
24.102
270246TR4_N_V150
Solar/Wind Harmer
0.062
270247TR4_N_V136
Solar/Wind Harmer
0.062
274674JOLIET 9 ;6U
Adder
21.182
276893AG1-478 C
Solar/Wind Harmer
0.639
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
21.933
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.526
958481AF2-142 GEN
Solar/Wind Harmer
14.114
274695ROCKY RD ;2P
Adder
15.016
274693ROCKY RD ;1P
Adder
14.868
274697ROCKY RD ;3P
Adder
4.079
274696ROCKY RD ;4P
Adder
15.37
274683WAUKEGAN ;8U
Adder
28.341
274683WAUKEGAN ;8U
Adder
23.89
962691AG1-118 GEN
Solar/Wind Harmer
28.03
246937BC-WTG2
Solar/Wind Harmer
0.377
270462AD2-086
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.95
276901AD2-066 C O1
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
3.701
971341AH1-150 GEN
Solar/Wind Harmer
18.31
971343AH1-151 GEN
Solar/Wind Harmer
18.31
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.289
972236AH1-702 GEN2
Adder
2.86
938861AE1-114 GEN
Solar/Wind Harmer
5.103
274764LEE CO EC;5U
Adder
11.991
274765LEE CO EC;6U
Adder
11.991
274762LEE CO EC;3U
Adder
11.963
274763LEE CO EC;4U
Adder
11.851
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.43
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.607
942111AE2-223 GEN
Solar/Wind Harmer
2.835
960611AF2-352 GEN
Solar/Wind Harmer
2.858
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.962
270031AE2-169
Solar/Wind Harmer
4.656
270599AE1-208 GEN
Solar/Wind Harmer
7.759
970291AG2-192 GEN
Solar/Wind Harmer
1.085
970291AG2-192 GEN
Solar/Wind Harmer
0.501
971613AH1-306 GEN
Solar/Wind Harmer
3.953
970241AG2-163 GEN
Solar/Wind Harmer
4.698
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.598
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.449
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
247621Y3-024
Adder
0.268
970621AG2-405 GEN
Solar/Wind Harmer
1.408
276916AD2-100_GEN
Solar/Wind Harmer
16.036
276911AD2-131_GEN
Solar/Wind Harmer
1.056
926881AC1-175 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.796
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.172
970885AG2-551 GEN
Solar/Wind Harmer
2.391
971587AH1-292 GEN
Solar/Wind Harmer
4.706
LAGNLTFEXP_LAGN->PJM
CLTF
11.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.355
TVALTFEXP_TVA->PJM
CLTF
4.573
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.612
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.183
MECLTFEXP_MEC->PJM
CLTF
18.423
SIGELTFEXP_SIGE->PJM
CLTF
0.4
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.213
NYPJM->LTFIMP_NY
CLTF
2.987
LGEELTFEXP_LGEE->PJM
CLTF
4.166
WECLTFEXP_WEC->PJM
CLTF
4.975
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.28
AG2-052LTFEXP_AG2-052->PJM
LTF
0.313
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5774.92
MW Contribution:
6.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
80.774
970149AG2-104 GEN
Solar/Wind Harmer
43.619
970155AG2-107 GEN
Solar/Wind Harmer
51.58
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
10.415
274754CRETE EC ;4U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
15.659
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
17.36
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274775LINCOLN ;6U
Adder
10.797
274776LINCOLN ;7U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
6.422
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971997AH1-543 GEN
Solar/Wind Harmer
4.485
957471AF2-041 GEN
Solar/Wind Harmer
25.504
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
965651AG1-433 GEN
Solar/Wind Harmer
2.449
276708O09 GEN2
Solar/Wind Harmer
0.295
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
965911AG1-460 GEN
Solar/Wind Harmer
1.542
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.459
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
965421AG1-410 GEN
Solar/Wind Harmer
21.55
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.196
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
972203AH1-686 GEN
Adder
1.998
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
5.989
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.434
970169AG2-114 GEN
Solar/Wind Harmer
8.435
971681AH1-341 GEN
Solar/Wind Harmer
13.557
972267AH1-718 GEN
Adder
4.986
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.677
946321AF1-296 GEN
Solar/Wind Harmer
4.601
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
10.858
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
971549AH1-272 GEN
Solar/Wind Harmer
16.367
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.859
970289AG2-191 GEN
Solar/Wind Harmer
1.486
971609AH1-304 GEN
Solar/Wind Harmer
1.264
247521TR3_G114
Solar/Wind Harmer
0.275
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.891
247536S-71 GEN
Solar/Wind Harmer
0.278
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
971347AH1-153 GEN
Solar/Wind Harmer
4.684
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274753CRETE EC ;3U
Adder
10.415
270505AE1-170 C O1
Solar/Wind Harmer
9.246
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
0.228
276843GEN-1.7
Solar/Wind Harmer
0.284
276806AD2-047 C O1
Solar/Wind Harmer
4.976
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
17.002
970571AG2-364 GEN
Solar/Wind Harmer
16.871
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
965931AG1-462 GEN
Solar/Wind Harmer
20.885
971087AG2-675 GEN
Solar/Wind Harmer
4.368
965091AG1-374 GEN
Solar/Wind Harmer
24.551
959611AF2-252 GEN
Solar/Wind Harmer
2.728
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.663
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
942481AE2-261 GEN
Solar/Wind Harmer
23.05
270004AE1-209 GEN
Solar/Wind Harmer
1.624
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24695305TIMB G C
Solar/Wind Harmer
0.627
970825AG2-519 GEN
Solar/Wind Harmer
5.579
946031AF1-268 GEN
Solar/Wind Harmer
6.994
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
14.053
965681AG1-436 GEN
Solar/Wind Harmer
11.209
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
276776AD2-060 GEN
Solar/Wind Harmer
0.937
958011AF2-095 GEN
Solar/Wind Harmer
12.646
970941AG2-585 GEN
Solar/Wind Harmer
4.83
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
21.908
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.582
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
25.814
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.897
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.686
960611AF2-352 GEN
Solar/Wind Harmer
2.728
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.921
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
270031AE2-169
Solar/Wind Harmer
4.257
270599AE1-208 GEN
Solar/Wind Harmer
7.096
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
276911AD2-131_GEN
Solar/Wind Harmer
1.062
270246TR4_N_V150
Solar/Wind Harmer
0.049
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.284
270383AD1-128 GEN
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
970883AG2-550 GEN
Solar/Wind Harmer
6.689
970885AG2-551 GEN
Solar/Wind Harmer
2.23
270054AF2-122 C O1
Solar/Wind Helper
1.547
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.28 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5040.8
MW Contribution:
7.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
5.165
24344105CKG2
50/50
11.949
270143AC1-141 CT2_
50/50
3.573
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.205
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
120.056
970149AG2-104 GEN
Solar/Wind Harmer
64.832
970155AG2-107 GEN
Solar/Wind Harmer
76.664
965011AG1-365 GEN
Solar/Wind Harmer
10.55
957891AF2-083 GEN
Solar/Wind Harmer
17.154
945111AF1-176 GEN
Solar/Wind Harmer
18.343
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
5.335
274773LINCOLN ;4U
Adder
11.987
274774LINCOLN ;5U
Adder
11.987
274723RIVER EC ;12
Adder
25.237
274751CRETE EC ;1U
Adder
11.595
274754CRETE EC ;4U
Adder
11.595
274812UNIV PK N;8U
Adder
7.005
970373AG2-245 GEN
Solar/Wind Harmer
20.466
274802UNIV PARK;5U
Adder
8.11
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.277
274674JOLIET 9 ;6U
Adder
21.182
274732ELWOOD EC;7P
Adder
22.596
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.624
965421AG1-410 GEN
Solar/Wind Harmer
28.373
965651AG1-433 GEN
Solar/Wind Harmer
2.763
24721705FLATG2
50/50
76.7
247620Y3-023
50/50
0.723
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.175
270101X2-052 CT2
50/50
2.175
24643105BUCHANAN
50/50
0.019
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.255
961051AF2-396 GEN
Solar/Wind Harmer
20.485
961051AF2-396 GEN
Solar/Wind Harmer
13.656
965681AG1-436 GEN
Solar/Wind Harmer
12.767
965791AG1-447 GEN
Solar/Wind Harmer
9.363
274770LINCOLN ;1U
Adder
11.987
274771LINCOLN ;2U
Adder
11.987
274805UNIV PK N;1U
Adder
7.02
274808UNIV PK N;4U
Adder
6.974
274888KELLY CRK;1U
Solar/Wind Harmer
0.565
276776AD2-060 GEN
Solar/Wind Harmer
1.034
958011AF2-095 GEN
Solar/Wind Harmer
13.957
970941AG2-585 GEN
Solar/Wind Harmer
5.331
276897AD1-100 C
Solar/Wind Harmer
24.102
270246TR4_N_V150
Solar/Wind Harmer
0.062
270247TR4_N_V136
Solar/Wind Harmer
0.062
274674JOLIET 9 ;6U
Adder
21.182
276893AG1-478 C
Solar/Wind Harmer
0.639
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
21.933
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.526
958481AF2-142 GEN
Solar/Wind Harmer
14.114
274695ROCKY RD ;2P
Adder
15.016
274693ROCKY RD ;1P
Adder
14.868
274697ROCKY RD ;3P
Adder
4.079
274696ROCKY RD ;4P
Adder
15.37
274683WAUKEGAN ;8U
Adder
28.341
274683WAUKEGAN ;8U
Adder
23.89
962691AG1-118 GEN
Solar/Wind Harmer
28.03
246937BC-WTG2
Solar/Wind Harmer
0.377
270462AD2-086
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.95
276901AD2-066 C O1
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
3.701
971341AH1-150 GEN
Solar/Wind Harmer
18.31
971343AH1-151 GEN
Solar/Wind Harmer
18.31
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.289
972236AH1-702 GEN2
Adder
2.86
938861AE1-114 GEN
Solar/Wind Harmer
5.103
274764LEE CO EC;5U
Adder
11.991
274765LEE CO EC;6U
Adder
11.991
274762LEE CO EC;3U
Adder
11.963
274763LEE CO EC;4U
Adder
11.851
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.43
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.607
942111AE2-223 GEN
Solar/Wind Harmer
2.835
960611AF2-352 GEN
Solar/Wind Harmer
2.858
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.962
270031AE2-169
Solar/Wind Harmer
4.656
270599AE1-208 GEN
Solar/Wind Harmer
7.759
970291AG2-192 GEN
Solar/Wind Harmer
1.085
970291AG2-192 GEN
Solar/Wind Harmer
0.501
971613AH1-306 GEN
Solar/Wind Harmer
3.953
970241AG2-163 GEN
Solar/Wind Harmer
4.698
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.598
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.449
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
247621Y3-024
Adder
0.268
970621AG2-405 GEN
Solar/Wind Harmer
1.408
276916AD2-100_GEN
Solar/Wind Harmer
16.036
276911AD2-131_GEN
Solar/Wind Harmer
1.056
926881AC1-175 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.796
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.172
970885AG2-551 GEN
Solar/Wind Harmer
2.391
971587AH1-292 GEN
Solar/Wind Harmer
4.706
24721605FLATG1
50/50
5.165
270144AC1-141 ST1_
50/50
3.155
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.587
24653605MOTTVILLE
50/50
0.006
959331AF2-224 GEN
Solar/Wind Harmer
7.385
270071AF1-092 GEN
Solar/Wind Harmer
20.17
970031AG2-029 GEN
Solar/Wind Harmer
5.617
971771AH1-392 GEN
Solar/Wind Harmer
10.358
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24729505KEY G4
Adder
9.292
274775LINCOLN ;6U
Adder
11.987
274776LINCOLN ;7U
Adder
11.987
274777LINCOLN ;8U
Adder
11.987
965041AG1-368 GEN
Solar/Wind Harmer
9.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
972037AH1-567 GEN1
Adder
0.255
274827FISK ;RP
Adder
10.79
274800UNIV PARK;3U
Adder
8.099
274801UNIV PARK;4U
Adder
8.099
960591AF2-350 GEN
Solar/Wind Harmer
9.692
972228AH1-698 GEN2
Adder
5.142
972227AH1-698 GEN1
Adder
3.62
247521TR3_G114
Solar/Wind Harmer
0.349
965051AG1-369 GEN
Solar/Wind Harmer
4.809
274687WILL CNTY;4U
Adder
38.553
274687WILL CNTY;4U
Adder
38.553
274675JOLIET 29;7U
Adder
42.278
274675JOLIET 29;7U
Adder
40.768
274728ELWOOD EC;5P
Adder
22.596
274731ELWOOD EC;2P
Adder
22.596
274733ELWOOD EC;3P
Adder
22.596
274735ELWOOD EC;4P
Adder
22.596
970833AG2-524 GEN
Solar/Wind Harmer
10.534
970833AG2-524 GEN
Solar/Wind Harmer
7.023
971549AH1-272 GEN
Solar/Wind Harmer
19.703
963791AG1-232 GEN
Solar/Wind Harmer
12.868
274744AC1-111 GEN8
Adder
7.624
274746AC1-111 G10
Adder
7.624
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.313
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
3.1
959141AF2-205 GEN
Solar/Wind Harmer
0.001
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.529
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.202
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.213
274828WAUKEGAN ;BP
Adder
14.856
246936BC-WTG1
Solar/Wind Harmer
0.377
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.87
939401AE1-172 GEN
Solar/Wind Harmer
6.964
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.08
971997AH1-543 GEN
Solar/Wind Harmer
4.85
971411AH1-196 GEN
Solar/Wind Harmer
13.821
971675AH1-338 GEN
Solar/Wind Harmer
3.593
276861AD2-134 GEN
Solar/Wind Harmer
0.164
276863AD2-134 GEN
Solar/Wind Harmer
0.164
971611AH1-305 GEN
Solar/Wind Harmer
5.462
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.31
274823ROCKFORD ;21
Adder
25.482
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
926823AC1-168 GEN
Solar/Wind Harmer
1.537
958861AF2-177 GEN
Solar/Wind Harmer
4.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.469
957471AF2-041 GEN
Solar/Wind Harmer
27.465
959081AF2-199 GEN
Solar/Wind Harmer
9.155
971067AG2-660 GEN
Solar/Wind Harmer
3.052
274822ROCKFORD ;11
Adder
25.668
970819AG2-516 GEN
Solar/Wind Harmer
10.889
970569AG2-363 GEN
Solar/Wind Harmer
27.133
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.963
274766LEE CO EC;7U
Adder
11.822
945371AF1-202 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.313
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.212
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.223
270032AE2-172
Solar/Wind Harmer
5.49
963741AG1-226 GEN
Solar/Wind Harmer
19.06
270005AE1-210 C O1
Solar/Wind Harmer
1.741
276903AD2-071 C
Solar/Wind Harmer
8.916
276621W2-048 GEN
Solar/Wind Harmer
0.399
970825AG2-519 GEN
Solar/Wind Harmer
2.813
965911AG1-460 GEN
Solar/Wind Harmer
1.54
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.437
24728605AND G2
Adder
3.753
970773AG2-487 GEN
Solar/Wind Harmer
1.148
23906502RICHG2&3
Adder
1.085
970169AG2-114 GEN
Solar/Wind Harmer
9.036
971681AH1-341 GEN
Solar/Wind Harmer
14.503
972267AH1-718 GEN
Adder
5.303
270007AE1-245 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.313
274877BISHOP HL;1U
Solar/Wind Harmer
0.294
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.159
946321AF1-296 GEN
Solar/Wind Harmer
4.834
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.383
970289AG2-191 GEN
Solar/Wind Harmer
1.586
963841AG1-237 GEN
Solar/Wind Harmer
3.581
276668AB2-070 GEN1
Solar/Wind Harmer
0.319
276848AB2-070 GEN3
Solar/Wind Harmer
0.317
276849AB2-070 GEN2
Solar/Wind Harmer
0.319
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.111
247536S-71 GEN
Solar/Wind Harmer
0.301
944221AF1-090 GEN
Solar/Wind Harmer
4.35
270543AE2-219 C
Solar/Wind Harmer
5.021
971029AG2-637 GEN
Solar/Wind Harmer
10.16
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24722005FLATG5
50/50
5.165
24721905FLATG4
50/50
94.337
270475AD2-096_GEN
50/50
10.024
270142AC1-141 CT1_
50/50
3.573
24642205MAYFLWER
50/50
0.054
944961AF1-161 GEN
50/50
4.258
962601AG1-109 GEN
50/50
4.258
962771AG1-126 GEN
Solar/Wind Harmer
120.056
970153AG2-106 GEN
Solar/Wind Harmer
76.664
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270043AE2-236 GEN
Solar/Wind Harmer
6.98
971347AH1-153 GEN
Solar/Wind Harmer
5.418
965021AG1-366 GEN
Solar/Wind Harmer
3.517
270063AE2-323 C
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
10.819
945111AF1-176 GEN
Solar/Wind Harmer
8.333
944531AF1-118 GEN
Solar/Wind Harmer
45.71
274772LINCOLN ;3U
Adder
11.987
274724RIVER EC ;11
Adder
24.945
274752CRETE EC ;2U
Adder
11.595
274753CRETE EC ;3U
Adder
11.595
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.066
274807UNIV PK N;3U
Adder
7.051
274811UNIV PK N;7U
Adder
7.005
970707AG2-453 GEN
Solar/Wind Harmer
31.765
274803UNIV PARK;6U
Adder
8.11
274826FISK ;BP
Adder
15.225
972038AH1-567 GEN2
Adder
0.507
274887GEN-1.85
Solar/Wind Harmer
0.252
276843GEN-1.7
Solar/Wind Harmer
0.313
276806AD2-047 C O1
Solar/Wind Harmer
5.492
972259AH1-714 GEN
Adder
26.498
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
40.767
274730ELWOOD EC;6P
Adder
22.596
274734ELWOOD EC;8P
Adder
22.596
274736ELWOOD EC;9P
Adder
22.596
274729ELWOOD EC;1P
Adder
22.596
943121AE2-341 GEN
Solar/Wind Harmer
15.981
943591AF1-030 GEN
Solar/Wind Harmer
10.628
24695305TIMB G C
Solar/Wind Harmer
0.801
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
1.27
274682WAUKEGAN ;7U
Adder
24.202
246938BC-WTG3
Solar/Wind Harmer
0.336
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
276868AE1-113 GEN
Solar/Wind Harmer
1.852
274879MINONK ;1U
Solar/Wind Harmer
0.386
946671AF1-331 GEN
Solar/Wind Harmer
0.983
274855GSG-6 ;RU
Solar/Wind Harmer
0.336
274850MENDOTA H;RU
Solar/Wind Harmer
0.107
959091AF2-200 GEN
Solar/Wind Harmer
18.31
970571AG2-364 GEN
Solar/Wind Harmer
18.089
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.963
274767LEE CO EC;8U
Adder
11.822
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.294
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.799
965931AG1-462 GEN
Solar/Wind Harmer
21.892
971087AG2-675 GEN
Solar/Wind Harmer
4.579
965091AG1-374 GEN
Solar/Wind Harmer
25.724
959611AF2-252 GEN
Solar/Wind Harmer
2.858
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.918
971993AH1-541 GEN
Solar/Wind Harmer
3.746
270004AE1-209 GEN
Solar/Wind Harmer
1.741
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.999
970825AG2-519 GEN
Solar/Wind Harmer
5.97
946031AF1-268 GEN
Solar/Wind Harmer
7.51
957381AF2-032 GEN
Solar/Wind Harmer
1.751
942481AE2-261 GEN
Solar/Wind Harmer
23.025
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
11.007
24728705AND G3
Adder
7.849
24728505AND G1
Adder
3.753
23906402RICHG1
Adder
1.086
23906502RICHG2&3
Adder
1.085
270541AE2-072 C
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
11.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.355
TVALTFEXP_TVA->PJM
CLTF
4.573
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.612
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.183
MECLTFEXP_MEC->PJM
CLTF
18.423
SIGELTFEXP_SIGE->PJM
CLTF
0.4
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.213
NYPJM->LTFIMP_NY
CLTF
2.987
LGEELTFEXP_LGEE->PJM
CLTF
4.166
WECLTFEXP_WEC->PJM
CLTF
4.975
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.28
AG2-052LTFEXP_AG2-052->PJM
LTF
0.313
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.76 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4887.22
MW Contribution:
7.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
15.609
270143AC1-141 CT2_
50/50
4.509
24639705ELKHART HY
50/50
0.301
970521AG2-332 GEN
50/50
21.375
24307105BERRINSP G
50/50
0.039
274773LINCOLN ;4U
50/50
16.29
274774LINCOLN ;5U
50/50
16.29
957891AF2-083 GEN
Solar/Wind Harmer
21.547
945111AF1-176 GEN
Solar/Wind Harmer
22.973
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
6.687
274723RIVER EC ;12
Adder
32.136
274751CRETE EC ;1U
Adder
14.744
274754CRETE EC ;4U
Adder
14.744
274812UNIV PK N;8U
Adder
8.912
274802UNIV PARK;5U
Adder
10.322
970373AG2-245 GEN
Solar/Wind Harmer
25.838
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.799
274674JOLIET 9 ;6U
Adder
26.949
274732ELWOOD EC;7P
Adder
28.742
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.698
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.939
274682WAUKEGAN ;7U
Adder
30.726
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
18.858
962781AG1-127 GEN
Solar/Wind Harmer
11.253
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
8.816
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
15.316
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.367
971997AH1-543 GEN
Solar/Wind Harmer
6.138
965011AG1-365 GEN
Solar/Wind Harmer
11.662
957471AF2-041 GEN
Solar/Wind Harmer
34.756
959081AF2-199 GEN
Solar/Wind Harmer
11.585
971067AG2-660 GEN
Solar/Wind Harmer
3.862
274822ROCKFORD ;11
Adder
32.468
970819AG2-516 GEN
Solar/Wind Harmer
13.763
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
14.32
970569AG2-363 GEN
Solar/Wind Harmer
34.22
965651AG1-433 GEN
Solar/Wind Harmer
3.342
274858EASY ROAD;U2
Solar/Wind Harmer
0
24344005CKG1
50/50
12.151
270144AC1-141 ST1_
50/50
3.981
24641605TWIN BRNCH
50/50
0.032
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
16.29
274776LINCOLN ;7U
50/50
16.29
274777LINCOLN ;8U
50/50
16.29
971771AH1-392 GEN
Solar/Wind Harmer
13.087
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
24.893
970031AG2-029 GEN
Solar/Wind Harmer
6.756
972037AH1-567 GEN1
Adder
0.324
274827FISK ;RP
Adder
13.736
960591AF2-350 GEN
Solar/Wind Harmer
12.34
274800UNIV PARK;3U
Adder
10.31
274801UNIV PARK;4U
Adder
10.31
972228AH1-698 GEN2
Adder
6.548
972227AH1-698 GEN1
Adder
4.611
274687WILL CNTY;4U
Adder
49.058
274687WILL CNTY;4U
Adder
49.058
24729505KEY G4
Adder
11.387
274675JOLIET 29;7U
Adder
53.8
274675JOLIET 29;7U
Adder
51.878
274728ELWOOD EC;5P
Adder
28.742
274731ELWOOD EC;2P
Adder
28.741
274733ELWOOD EC;3P
Adder
28.741
274735ELWOOD EC;4P
Adder
28.741
970833AG2-524 GEN
Solar/Wind Harmer
13.404
970833AG2-524 GEN
Solar/Wind Harmer
8.936
274744AC1-111 GEN8
Adder
9.698
274746AC1-111 G10
Adder
9.698
970073AG2-061 GEN
Solar/Wind Harmer
3.925
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
4.551
971411AH1-196 GEN
Solar/Wind Harmer
17.505
276861AD2-134 GEN
Solar/Wind Harmer
0.208
276863AD2-134 GEN
Solar/Wind Harmer
0.208
959331AF2-224 GEN
Solar/Wind Harmer
8.163
971549AH1-272 GEN
Solar/Wind Harmer
24.049
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
23.171
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
32.233
971611AH1-305 GEN
Solar/Wind Harmer
6.82
274856ECOGROVE ;U1
Solar/Wind Harmer
0.267
926823AC1-168 GEN
Solar/Wind Harmer
1.939
970169AG2-114 GEN
Solar/Wind Harmer
11.381
971681AH1-341 GEN
Solar/Wind Harmer
18.311
972267AH1-718 GEN
Adder
6.682
276741O09 GEN1
Solar/Wind Harmer
0.394
274877BISHOP HL;1U
Solar/Wind Harmer
0.369
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
11.46
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.067
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
14.314
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.381
270142AC1-141 CT1_
50/50
4.509
24642205MAYFLWER
50/50
0.068
944961AF1-161 GEN
50/50
5.338
962601AG1-109 GEN
50/50
5.338
274772LINCOLN ;3U
50/50
16.29
971347AH1-153 GEN
Solar/Wind Harmer
6.994
270043AE2-236 GEN
Solar/Wind Harmer
8.579
270505AE1-170 C O1
Solar/Wind Harmer
13.603
945111AF1-176 GEN
Solar/Wind Harmer
10.436
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
56.263
274724RIVER EC ;11
Adder
31.767
274752CRETE EC ;2U
Adder
14.744
274753CRETE EC ;3U
Adder
14.744
274814UNIV PK N;0U
Adder
8.99
274807UNIV PK N;3U
Adder
8.97
274811UNIV PK N;7U
Adder
8.912
970707AG2-453 GEN
Solar/Wind Harmer
40.554
972259AH1-714 GEN
Adder
33.781
274803UNIV PARK;6U
Adder
10.322
274826FISK ;BP
Adder
19.382
274887GEN-1.85
Solar/Wind Harmer
0.321
276843GEN-1.7
Solar/Wind Harmer
0.399
276806AD2-047 C O1
Solar/Wind Harmer
6.993
972038AH1-567 GEN2
Adder
0.645
939351AE1-166 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
51.877
274729ELWOOD EC;1P
Adder
28.741
274730ELWOOD EC;6P
Adder
28.742
274734ELWOOD EC;8P
Adder
28.742
274736ELWOOD EC;9P
Adder
28.742
943121AE2-341 GEN
Solar/Wind Harmer
20.341
943591AF1-030 GEN
Solar/Wind Harmer
13.527
274682WAUKEGAN ;7U
Adder
30.726
274862TOP CROP ;2U
Solar/Wind Harmer
1.61
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
2.344
274879MINONK ;1U
Solar/Wind Harmer
0.489
946671AF1-331 GEN
Solar/Wind Harmer
1.245
274855GSG-6 ;RU
Solar/Wind Harmer
0.426
274850MENDOTA H;RU
Solar/Wind Harmer
0.136
965021AG1-366 GEN
Solar/Wind Harmer
3.887
959091AF2-200 GEN
Solar/Wind Harmer
23.171
970571AG2-364 GEN
Solar/Wind Harmer
22.813
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
15.096
274767LEE CO EC;8U
Adder
14.918
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.369
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.899
965931AG1-462 GEN
Solar/Wind Harmer
27.452
971087AG2-675 GEN
Solar/Wind Harmer
5.742
965091AG1-374 GEN
Solar/Wind Harmer
32.089
959611AF2-252 GEN
Solar/Wind Harmer
3.565
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.004
971993AH1-541 GEN
Solar/Wind Harmer
4.623
970289AG2-191 GEN
Solar/Wind Harmer
1.091
957381AF2-032 GEN
Solar/Wind Harmer
2.142
942481AE2-261 GEN
Solar/Wind Harmer
28.148
270004AE1-209 GEN
Solar/Wind Harmer
2.023
970825AG2-519 GEN
Solar/Wind Harmer
6.871
946031AF1-268 GEN
Solar/Wind Harmer
8.578
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.45
24695305TIMB G C
Solar/Wind Harmer
0.754
970193AG2-126 GEN
Solar/Wind Harmer
13.114
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
15.096
274766LEE CO EC;7U
Adder
14.918
276708O09 GEN2
Solar/Wind Harmer
0.394
276646AC1-214 GEN2
Solar/Wind Harmer
0.437
958861AF2-177 GEN
Solar/Wind Harmer
4.817
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
15.28
945371AF1-202 GEN
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.491
963741AG1-226 GEN
Solar/Wind Harmer
23.192
270594AE1-207 GEN
Solar/Wind Harmer
10.875
270032AE2-172
Solar/Wind Harmer
6.473
270024AE2-089 GEN
Solar/Wind Harmer
0.002
965911AG1-460 GEN
Solar/Wind Harmer
1.883
276903AD2-071 C
Solar/Wind Harmer
10.45
270005AE1-210 C O1
Solar/Wind Harmer
2.023
970825AG2-519 GEN
Solar/Wind Harmer
3.238
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.152
24728605AND G2
Adder
4.25
965421AG1-410 GEN
Solar/Wind Harmer
22.891
246936BC-WTG1
Solar/Wind Harmer
0.29
270489AE1-102 GEN1
Solar/Wind Harmer
0.936
970773AG2-487 GEN
Solar/Wind Harmer
1.245
970091AG2-072 GEN
Adder
68.038
270102X2-052 ST
50/50
3
270100X2-052 CT1
50/50
2.772
270101X2-052 CT2
50/50
2.772
24643105BUCHANAN
50/50
0.023
247620Y3-023
50/50
0.894
274770LINCOLN ;1U
50/50
16.29
274771LINCOLN ;2U
50/50
16.29
970349AG2-230 GEN
Solar/Wind Harmer
20.983
965681AG1-436 GEN
Solar/Wind Harmer
16.258
965791AG1-447 GEN
Solar/Wind Harmer
11.923
961051AF2-396 GEN
Solar/Wind Harmer
25.67
961051AF2-396 GEN
Solar/Wind Harmer
17.113
274805UNIV PK N;1U
Adder
8.931
274808UNIV PK N;4U
Adder
8.873
274888KELLY CRK;1U
Solar/Wind Harmer
0.72
276776AD2-060 GEN
Solar/Wind Harmer
1.316
958011AF2-095 GEN
Solar/Wind Harmer
17.77
970941AG2-585 GEN
Solar/Wind Harmer
6.787
276897AD1-100 C
Solar/Wind Harmer
30.687
274674JOLIET 9 ;6U
Adder
26.949
276893AG1-478 C
Solar/Wind Harmer
0.813
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274695ROCKY RD ;2P
Adder
19.071
274693ROCKY RD ;1P
Adder
18.884
274697ROCKY RD ;3P
Adder
5.181
274696ROCKY RD ;4P
Adder
19.521
958481AF2-142 GEN
Solar/Wind Harmer
17.9
274683WAUKEGAN ;8U
Adder
35.976
274683WAUKEGAN ;8U
Adder
30.326
962691AG1-118 GEN
Solar/Wind Harmer
35.572
958491AF2-143 GEN
Solar/Wind Harmer
17.663
276901AD2-066 C O1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
23.171
971343AH1-151 GEN
Solar/Wind Harmer
23.171
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.159
972236AH1-702 GEN2
Adder
3.616
944541AF1-119 GEN
Solar/Wind Harmer
0.761
960971AF2-388 GEN
Solar/Wind Harmer
6.685
938861AE1-114 GEN
Solar/Wind Harmer
6.442
274764LEE CO EC;5U
Adder
15.132
274765LEE CO EC;6U
Adder
15.132
274762LEE CO EC;3U
Adder
15.096
274763LEE CO EC;4U
Adder
14.954
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.801
276645AC1-214 GEN1
Solar/Wind Harmer
0.437
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
3.547
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
4.299
960611AF2-352 GEN
Solar/Wind Harmer
3.565
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.183
944231AF1-091 GEN
Solar/Wind Harmer
23.934
970291AG2-192 GEN
Solar/Wind Harmer
1.289
970291AG2-192 GEN
Solar/Wind Harmer
0.595
270031AE2-169
Solar/Wind Harmer
5.447
270599AE1-208 GEN
Solar/Wind Harmer
9.078
276615X2-022 GEN
Solar/Wind Harmer
0.102
276838X2-022 GEN2
Solar/Wind Harmer
0.552
970241AG2-163 GEN
Solar/Wind Harmer
5.716
971613AH1-306 GEN
Solar/Wind Harmer
4.661
276916AD2-100_GEN
Solar/Wind Harmer
19.57
276911AD2-131_GEN
Solar/Wind Harmer
1.289
270246TR4_N_V150
Solar/Wind Harmer
0.059
270247TR4_N_V136
Solar/Wind Harmer
0.059
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.673
270201AC2-176 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
9.289
247621Y3-024
Adder
0.295
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.411
970883AG2-550 GEN
Solar/Wind Harmer
7.657
970885AG2-551 GEN
Solar/Wind Harmer
2.552
971587AH1-292 GEN
Solar/Wind Harmer
5.454
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.29
270349AD2-093_GEN
Solar/Wind Helper
1.569
270471AD2-092_GEN
Solar/Wind Helper
1.569
965041AG1-368 GEN
Solar/Wind Harmer
10.029
276668AB2-070 GEN1
Solar/Wind Harmer
0.393
276848AB2-070 GEN3
Solar/Wind Harmer
0.392
276849AB2-070 GEN2
Solar/Wind Harmer
0.393
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.884
971609AH1-304 GEN
Solar/Wind Harmer
1.618
247521TR3_G114
Solar/Wind Harmer
0.333
965051AG1-369 GEN
Solar/Wind Harmer
4.586
944221AF1-090 GEN
Solar/Wind Harmer
5.276
964611AG1-324 GEN
Solar/Wind Harmer
3.501
247536S-71 GEN
Solar/Wind Harmer
0.329
270543AE2-219 C
Solar/Wind Harmer
5.36
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.912
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.541
24728705AND G3
Adder
8.888
24728505AND G1
Adder
4.25
246938BC-WTG3
Solar/Wind Harmer
0.259
270491AE1-102 GEN2
Solar/Wind Harmer
0.936
LAGNLTFEXP_LAGN->PJM
CLTF
12.231
TVALTFEXP_TVA->PJM
CLTF
4.659
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.285
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.325
MECLTFEXP_MEC->PJM
CLTF
22.729
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM West 2LTFEXP_CBM-W2->PJM
CBM
110.466
NYPJM->LTFIMP_NY
CLTF
2.94
LGEELTFEXP_LGEE->PJM
CLTF
4.042
WECLTFEXP_WEC->PJM
CLTF
6.289
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.78
AG2-052LTFEXP_AG2-052->PJM
LTF
0.393
AH1-155LTFEXP_AH1-155->PJM
LTF
0.59

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.27 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6477.04
MW Contribution:
13.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
270331AC1-082 GEN3
Solar/Wind Harmer
0.844
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
5.223
971403AH1-188 GEN
Solar/Wind Harmer
23.963
962761AG1-125 GEN
Solar/Wind Harmer
54.553
970149AG2-104 GEN
Solar/Wind Harmer
33.686
970155AG2-107 GEN
Solar/Wind Harmer
23.787
971687AH1-348 GEN
Solar/Wind Harmer
1.522
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
27.387
339221AD2-048_GEN
Solar/Wind Harmer
2.202
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
14.288
252510AF1-249 C
Solar/Wind Harmer
0.594
25196008MFTGT1
Adder
1.98
943111AE2-339 GEN
Solar/Wind Harmer
1.257
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
11.825
946171AF1-282 GEN
Solar/Wind Harmer
14.124
339211AE2-254 GEN
Solar/Wind Harmer
2.115
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
6.325
270222AC2-111 GEN
Solar/Wind Harmer
6.156
944031AF1-071 GEN
Solar/Wind Harmer
1.385
970653AG2-424 GEN
Solar/Wind Harmer
6.638
270273AD2-016 GEN
Solar/Wind Harmer
3.648
24728605AND G2
Adder
5.248
339241AF1-083 GEN
Solar/Wind Harmer
2.268
942081AE2-220 GEN
Solar/Wind Harmer
8.696
270209AC1-174_GEN
Solar/Wind Harmer
5.534
270437AC2-090 C
Solar/Wind Harmer
7.589
270239V3-007_GEN1
Solar/Wind Harmer
2.34
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
13.523
963741AG1-226 GEN
Solar/Wind Harmer
60.722
964901AG1-354 GEN
Solar/Wind Harmer
20.24
270594AE1-207 GEN
Solar/Wind Harmer
18.313
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
7.699
270053AF1-130 C
Solar/Wind Harmer
30.765
270399AC1-101 GEN
Solar/Wind Harmer
7.281
270400AC1-102 GEN
Solar/Wind Harmer
7.281
970281AG2-184 GEN
Solar/Wind Harmer
32.719
971985AH1-537 GEN
Solar/Wind Harmer
27.788
941621AE2-160 GEN
Adder
5.034
962211AG1-066 GEN
Solar/Wind Harmer
3.649
971313AH1-133 GEN
Solar/Wind Harmer
8.798
972163AH1-664 GEN
Solar/Wind Harmer
14.536
972165AH1-665 GEN
Solar/Wind Harmer
11.629
339216AC1-074 GEN
Solar/Wind Harmer
2.394
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
253433AC1-085 GEN1
Solar/Wind Harmer
7.506
253432AC1-085 GEN2
Solar/Wind Harmer
0.378
270340AC2-060 GEN
Solar/Wind Harmer
4.256
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
2.824
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
11.163
24386605FR-22G C
Solar/Wind Harmer
5.776
24791305MDL-5G
Solar/Wind Harmer
3.222
945371AF1-202 GEN
Solar/Wind Harmer
9.316
958861AF2-177 GEN
Solar/Wind Harmer
14.534
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
927014AC1-188 GEN
Solar/Wind Harmer
2.477
970913AG2-568 GEN
Solar/Wind Harmer
10.623
971225AH1-072 GEN
Solar/Wind Harmer
3.04
971227AH1-073 GEN
Solar/Wind Harmer
3.04
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
7.389
961491AF2-440 GEN
Solar/Wind Harmer
3.071
971073AG2-665 GEN
Solar/Wind Harmer
11.654
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.369
972043AH1-570 GEN
Solar/Wind Harmer
3.585
972045AH1-571 GEN
Solar/Wind Harmer
2.868
25183208HLCRTG
Solar/Wind Harmer
8.652
971125AH1-004 GEN
Solar/Wind Harmer
5.691
970107AG2-081 GEN
Solar/Wind Harmer
4.268
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
14.201
253415AE1-040 GEN
Solar/Wind Harmer
1.57
964571AG1-320 GEN
Solar/Wind Harmer
11.341
270269AC2-059
Solar/Wind Harmer
12.798
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
18.959
926881AC1-175 GEN
Solar/Wind Harmer
7.589
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
8.27
339231AF1-038_GEN
Solar/Wind Harmer
2.457
24725505WLD G2 C
Solar/Wind Harmer
5.381
24699105WLD G1 C
Solar/Wind Harmer
5.319
339236AF1-050_GEN
Solar/Wind Harmer
2.451
970241AG2-163 GEN
Solar/Wind Harmer
33.734
970291AG2-192 GEN
Solar/Wind Harmer
1.753
970291AG2-192 GEN
Solar/Wind Harmer
0.565
253349AC2-067 GEN
Solar/Wind Harmer
2.741
253400AC2-068 GEN
Solar/Wind Harmer
1.102
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
6.822
966841AG1-555 GEN
Solar/Wind Harmer
3.372
970883AG2-550 GEN
Solar/Wind Harmer
13.404
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
4.927
24755605MDL-5G
Solar/Wind Harmer
3.222
24697905MDL-4G C
Solar/Wind Harmer
3.067
270181AB1-006 GEN2
Solar/Wind Harmer
0.956
971485AH1-239 GEN
Solar/Wind Harmer
10.681
964781AG1-341 GEN
Solar/Wind Harmer
14.151
966021AG1-471 GEN
Solar/Wind Harmer
7.208
270031AE2-169
Solar/Wind Harmer
10.876
270599AE1-208 GEN
Solar/Wind Harmer
10.876
945421AF1-207 GEN
Solar/Wind Harmer
18.73
957841AF2-078 GEN
Solar/Wind Harmer
8.063
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
6.831
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
274674JOLIET 9 ;6U
Adder
20.046
274683WAUKEGAN ;8U
Adder
27.432
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
274745AC1-111 GEN9
Adder
7.28
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
253406AD2-031_GEN
Solar/Wind Harmer
1.796
270263AC1-001 GEN
Solar/Wind Harmer
1.464
270444AC2-157 GEN1
Solar/Wind Harmer
7.815
270445AC2-157 GEN2
Solar/Wind Harmer
7.815
270291AC1-194 GEN
Solar/Wind Harmer
7.123
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
6.333
971061AG2-657 GEN
Solar/Wind Harmer
12.288
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
2.562
963841AG1-237 GEN
Solar/Wind Harmer
14.713
971029AG2-637 GEN
Solar/Wind Harmer
20.191
24386405FR-21G C
Solar/Wind Harmer
5.776
24387005FR-3G C
Solar/Wind Harmer
5.313
270543AE2-219 C
Solar/Wind Harmer
13.404
946581AF1-322 GEN
Solar/Wind Harmer
13.675
24691005MDL-2G C
Solar/Wind Harmer
4.942
945581AF1-223 GEN
Solar/Wind Harmer
6.056
247536S-71 GEN
Solar/Wind Harmer
5.402
964611AG1-324 GEN
Solar/Wind Harmer
5.196
270432AC2-029 GEN
Solar/Wind Harmer
9.322
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
944221AF1-090 GEN
Solar/Wind Harmer
14.552
961761AG1-017 GEN
Solar/Wind Harmer
0.569
24729505KEY G4
Adder
8.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
972267AH1-718 GEN
Adder
5.423
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274823ROCKFORD ;21
Adder
25.367
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
270330AC1-082 GEN2
Solar/Wind Harmer
0.842
270329AC1-082 GEN1
Solar/Wind Harmer
0.842
962771AG1-126 GEN
Solar/Wind Harmer
54.553
970153AG2-106 GEN
Solar/Wind Harmer
23.787
971191AH1-055 GEN
Solar/Wind Harmer
31.162
957541AF2-048 GEN
Solar/Wind Harmer
2.477
972103AH1-617 GEN
Solar/Wind Harmer
31.161
960911AF2-382 GEN
Solar/Wind Harmer
11.466
971461AH1-227 GEN
Solar/Wind Harmer
7.797
270367AC2-061_GEN
Solar/Wind Harmer
4.689
270186AC1-089 GEN
Solar/Wind Harmer
9.011
970879AG2-548 GEN
Solar/Wind Harmer
11.654
972167AH1-666 GEN
Solar/Wind Harmer
11.619
252507AC2-088 GEN
Solar/Wind Harmer
2.586
958171AF2-111 GEN
Solar/Wind Harmer
35.846
339243AC2-075 GEN1
Solar/Wind Harmer
0.648
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
252524AE2-267 GEN
Solar/Wind Harmer
2.234
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
7.507
253317AC1-085 GEN4
Solar/Wind Harmer
11.825
946181AF1-283 GEN
Solar/Wind Harmer
18.362
253394AE2-221_GEN
Solar/Wind Harmer
6.325
970455AG2-298 GEN
Solar/Wind Harmer
4.865
970653AG2-424 GEN
Solar/Wind Harmer
0.96
339206AE1-143 GEN
Solar/Wind Harmer
2.932
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
20.406
24379505HDWTR1G C
Solar/Wind Harmer
10.752
270240V3-007_GEN2
Solar/Wind Harmer
8.412
253303V4-073 C
Solar/Wind Harmer
0.157
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
12.206
247642Z2-115 C
Solar/Wind Harmer
0.086
965461AG1-414 GEN
Solar/Wind Harmer
3.058
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
7.583
946031AF1-268 GEN
Solar/Wind Harmer
11.153
24386205FR-12G C
Solar/Wind Harmer
5.756
960071AF2-298 GEN
Solar/Wind Harmer
2.031
339255AE2-071 GEN
Solar/Wind Harmer
1.57
339250AF1-203 GEN
Solar/Wind Harmer
0.808
24690905MDL-1G C
Solar/Wind Harmer
10.73
970781AG2-491 GEN
Solar/Wind Harmer
13.365
962031AG1-047 GEN
Solar/Wind Harmer
4.019
274772LINCOLN ;3U
Adder
11.001
972259AH1-714 GEN
Adder
24.853
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
274682WAUKEGAN ;7U
Adder
7.239
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
957741AF2-068 GEN
Solar/Wind Harmer
8.281
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6428.58
MW Contribution:
9.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
16.719
962761AG1-125 GEN
Solar/Wind Harmer
46.005
970149AG2-104 GEN
Solar/Wind Harmer
24.844
970155AG2-107 GEN
Solar/Wind Harmer
29.378
971687AH1-348 GEN
Solar/Wind Harmer
1.062
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
19.107
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
11.165
252510AF1-249 C
Solar/Wind Harmer
0.075
25196008MFTGT1
Adder
1.98
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.854
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
4.631
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
962771AG1-126 GEN
Solar/Wind Harmer
46.005
970153AG2-106 GEN
Solar/Wind Harmer
29.378
971191AH1-055 GEN
Solar/Wind Harmer
29.882
972103AH1-617 GEN
Solar/Wind Harmer
21.74
960911AF2-382 GEN
Solar/Wind Harmer
7.999
971461AH1-227 GEN
Solar/Wind Harmer
5.44
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
7.453
972167AH1-666 GEN
Solar/Wind Harmer
8.106
252507AC2-088 GEN
Solar/Wind Harmer
0.453
958171AF2-111 GEN
Solar/Wind Harmer
25.009
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
8.38
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
12.81
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.77
970653AG2-424 GEN
Solar/Wind Harmer
0.96
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
14.237
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
8.358
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
2.038
970191AG2-125 GEN
Solar/Wind Harmer
2.419
970825AG2-519 GEN
Solar/Wind Harmer
7.074
946031AF1-268 GEN
Solar/Wind Harmer
8.922
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.325
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.91
942481AE2-261 GEN
Solar/Wind Harmer
27.692
957381AF2-032 GEN
Solar/Wind Harmer
2.099
971993AH1-541 GEN
Solar/Wind Harmer
4.271
943031AE2-326 GEN
Solar/Wind Harmer
4.803
965091AG1-374 GEN
Solar/Wind Harmer
27.602
959611AF2-252 GEN
Solar/Wind Harmer
3.067
944531AF1-118 GEN
Solar/Wind Harmer
41.107
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.304
970571AG2-364 GEN
Solar/Wind Harmer
18.217
253325AC1-069 GEN
Solar/Wind Harmer
0.01
276868AE1-113 GEN
Solar/Wind Harmer
1.82
274879MINONK ;1U
Solar/Wind Harmer
0.38
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.001
970707AG2-453 GEN
Solar/Wind Harmer
29.702
943121AE2-341 GEN
Solar/Wind Harmer
15.239
943591AF1-030 GEN
Solar/Wind Harmer
10.134
274862TOP CROP ;2U
Solar/Wind Harmer
1.227
972259AH1-714 GEN
Adder
24.853
274855GSG-6 ;RU
Solar/Wind Harmer
0.332
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
946671AF1-331 GEN
Solar/Wind Harmer
0.969
959091AF2-200 GEN
Solar/Wind Harmer
18.173
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
965931AG1-462 GEN
Solar/Wind Harmer
23.167
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
27.062
270399AC1-101 GEN
Solar/Wind Harmer
3.79
270400AC1-102 GEN
Solar/Wind Harmer
3.79
970281AG2-184 GEN
Solar/Wind Harmer
22.827
971985AH1-537 GEN
Solar/Wind Harmer
3.231
941621AE2-160 GEN
Adder
5.034
971313AH1-133 GEN
Solar/Wind Harmer
5.062
972163AH1-664 GEN
Solar/Wind Harmer
11.291
972165AH1-665 GEN
Solar/Wind Harmer
9.043
339216AC1-074 GEN
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.728
270263AC1-001 GEN
Solar/Wind Harmer
0.978
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971061AG2-657 GEN
Solar/Wind Harmer
6.001
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
1.788
963841AG1-237 GEN
Solar/Wind Harmer
4.07
971029AG2-637 GEN
Solar/Wind Harmer
14.087
24386405FR-21G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.546
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.372
971609AH1-304 GEN
Solar/Wind Harmer
1.521
964611AG1-324 GEN
Solar/Wind Harmer
3.625
270432AC2-029 GEN
Solar/Wind Harmer
4.119
944221AF1-090 GEN
Solar/Wind Harmer
5.449
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.362
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
971611AH1-305 GEN
Solar/Wind Harmer
5.499
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.649
966391AG1-508 GEN
Solar/Wind Harmer
1.42
970169AG2-114 GEN
Solar/Wind Harmer
9.156
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
0.996
274877BISHOP HL;1U
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
1.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
970073AG2-061 GEN
Solar/Wind Harmer
3.032
276741O09 GEN1
Solar/Wind Harmer
0.321
970833AG2-524 GEN
Solar/Wind Harmer
10.003
970833AG2-524 GEN
Solar/Wind Harmer
6.669
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
276861AD2-134 GEN
Solar/Wind Harmer
0.162
276863AD2-134 GEN
Solar/Wind Harmer
0.162
971675AH1-338 GEN
Solar/Wind Harmer
3.544
971171AH1-044 GEN
Solar/Wind Harmer
18.173
971681AH1-341 GEN
Solar/Wind Harmer
14.63
972267AH1-718 GEN
Adder
5.423
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
274823ROCKFORD ;21
Adder
25.367
971411AH1-196 GEN
Solar/Wind Harmer
13.626
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
960591AF2-350 GEN
Solar/Wind Harmer
9.078
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
970773AG2-487 GEN
Solar/Wind Harmer
1.693
270273AD2-016 GEN
Solar/Wind Harmer
0.98
24728605AND G2
Adder
5.248
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.957
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
10.535
963741AG1-226 GEN
Solar/Wind Harmer
22.28
964901AG1-354 GEN
Solar/Wind Harmer
14.121
270594AE1-207 GEN
Solar/Wind Harmer
10.536
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
2.038
970825AG2-519 GEN
Solar/Wind Harmer
3.334
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.02
965911AG1-460 GEN
Solar/Wind Harmer
1.852
965651AG1-433 GEN
Solar/Wind Harmer
2.715
276621W2-048 GEN
Solar/Wind Harmer
0.463
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.546
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.866
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.925
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.831
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.358
270055AF2-134 C O1
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
27.326
971997AH1-543 GEN
Solar/Wind Harmer
4.779
253333AC1-068 GEN
Solar/Wind Harmer
0.01
276882AE2-255 GEN
Solar/Wind Harmer
1.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
276805AD2-038 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.321
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.477
274861TOP CROP ;1U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.28
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
27.26
959081AF2-199 GEN
Solar/Wind Harmer
9.087
962781AG1-127 GEN
Solar/Wind Harmer
8.648
971067AG2-660 GEN
Solar/Wind Harmer
3.029
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
970819AG2-516 GEN
Solar/Wind Harmer
10.9
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
970373AG2-245 GEN
Solar/Wind Harmer
16.807
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
971087AG2-675 GEN
Solar/Wind Harmer
4.845
274682WAUKEGAN ;7U
Adder
7.239
274887GEN-1.85
Solar/Wind Harmer
0.236
276843GEN-1.7
Solar/Wind Harmer
0.294
276806AD2-047 C O1
Solar/Wind Harmer
5.144
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
970913AG2-568 GEN
Solar/Wind Harmer
8.731
971225AH1-072 GEN
Solar/Wind Harmer
2.121
971227AH1-073 GEN
Solar/Wind Harmer
2.121
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971073AG2-665 GEN
Solar/Wind Harmer
7.453
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.05
972043AH1-570 GEN
Solar/Wind Harmer
2.601
972045AH1-571 GEN
Solar/Wind Harmer
2.084
25183208HLCRTG
Solar/Wind Harmer
0.001
971125AH1-004 GEN
Solar/Wind Harmer
3.97
970107AG2-081 GEN
Solar/Wind Harmer
2.978
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
9.908
971587AH1-292 GEN
Solar/Wind Harmer
7.164
964571AG1-320 GEN
Solar/Wind Harmer
8.813
270269AC2-059
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
10.085
926881AC1-175 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.492
970291AG2-192 GEN
Solar/Wind Harmer
1.223
970291AG2-192 GEN
Solar/Wind Harmer
0.565
971613AH1-306 GEN
Solar/Wind Harmer
4.515
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.061
970883AG2-550 GEN
Solar/Wind Harmer
9.352
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971485AH1-239 GEN
Solar/Wind Harmer
7.452
964781AG1-341 GEN
Solar/Wind Harmer
9.873
966021AG1-471 GEN
Solar/Wind Harmer
5.029
270031AE2-169
Solar/Wind Harmer
5.121
270599AE1-208 GEN
Solar/Wind Harmer
8.535
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
19.462
276911AD2-131_GEN
Solar/Wind Harmer
1.282
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.431
276615X2-022 GEN
Solar/Wind Harmer
0.096
276838X2-022 GEN2
Solar/Wind Harmer
0.521
960611AF2-352 GEN
Solar/Wind Harmer
3.067
942111AE2-223 GEN
Solar/Wind Harmer
2.987
276645AC1-214 GEN1
Solar/Wind Harmer
0.358
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
22.743
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
958491AF2-143 GEN
Solar/Wind Harmer
13.642
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.467
958481AF2-142 GEN
Solar/Wind Harmer
13.633
962691AG1-118 GEN
Solar/Wind Harmer
27.261
971341AH1-150 GEN
Solar/Wind Harmer
18.173
971343AH1-151 GEN
Solar/Wind Harmer
18.173
938861AE1-114 GEN
Solar/Wind Harmer
5.149
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
276893AG1-478 C
Solar/Wind Harmer
0.606
274674JOLIET 9 ;6U
Adder
20.046
942221AE2-234 GEN
Solar/Wind Harmer
3.648
274683WAUKEGAN ;8U
Adder
27.432
971277AH1-098 GEN
Solar/Wind Harmer
3.633
274888KELLY CRK;1U
Solar/Wind Harmer
0.529
276776AD2-060 GEN
Solar/Wind Harmer
0.968
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.72 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6225.55
MW Contribution:
13.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.396
243186AF1-051 GEN
50/50
12.548
24318705GVG2
50/50
11.631
24721805FLATG3
50/50
2.774
972203AH1-686 GEN
Adder
4.442
24723205RIVRG3
Adder
36.155
24686505CER G6
Adder
15.668
270331AC1-082 GEN3
Solar/Wind Harmer
0.851
944971AF1-162 GEN
Solar/Wind Harmer
12.224
960001AF2-291 GEN
Solar/Wind Harmer
5.265
971403AH1-188 GEN
Solar/Wind Harmer
24.159
962761AG1-125 GEN
Solar/Wind Harmer
55.006
970149AG2-104 GEN
Solar/Wind Harmer
33.966
970155AG2-107 GEN
Solar/Wind Harmer
23.985
971687AH1-348 GEN
Solar/Wind Harmer
1.536
24728305BUCHG2
Adder
6.863
970091AG2-072 GEN
Adder
114.157
971073AG2-665 GEN
Solar/Wind Harmer
1.71
945681AF1-233 GEN
Solar/Wind Harmer
27.651
339221AD2-048_GEN
Solar/Wind Harmer
2.223
25196808ZIMRHP
Adder
109.659
252516AE2-318_GEN
Solar/Wind Harmer
14.428
252510AF1-249 C
Solar/Wind Harmer
0.6
25196008MFTGT1
Adder
1.999
943111AE2-339 GEN
Solar/Wind Harmer
1.269
25194608D.CRK4
Adder
2.359
3429241JKCT 3G
Adder
16.981
3429421JKCT 10G
Adder
11.925
253316AC1-085 GEN3
Solar/Wind Harmer
11.942
946171AF1-282 GEN
Solar/Wind Harmer
14.264
339211AE2-254 GEN
Solar/Wind Harmer
2.136
24735205WLF2G2
Adder
8.122
253398AE2-221_GEN2
Solar/Wind Harmer
6.388
270222AC2-111 GEN
Solar/Wind Harmer
6.219
944031AF1-071 GEN
Solar/Wind Harmer
1.399
970653AG2-424 GEN
Solar/Wind Harmer
6.706
270273AD2-016 GEN
Solar/Wind Harmer
3.685
24728605AND G2
Adder
5.301
339241AF1-083 GEN
Solar/Wind Harmer
2.292
942081AE2-220 GEN
Solar/Wind Harmer
8.785
270209AC1-174_GEN
Solar/Wind Harmer
5.591
270437AC2-090 C
Solar/Wind Harmer
7.667
270239V3-007_GEN1
Solar/Wind Harmer
2.364
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
276903AD2-071 C
Solar/Wind Harmer
13.662
963741AG1-226 GEN
Solar/Wind Harmer
61.351
964901AG1-354 GEN
Solar/Wind Harmer
20.45
270594AE1-207 GEN
Solar/Wind Harmer
18.503
270032AE2-172
Solar/Wind Harmer
6.337
270005AE1-210 C O1
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
2.854
25326309TAIT D
Adder
1.488
24385905FR-11G C
Solar/Wind Harmer
11.279
24386605FR-22G C
Solar/Wind Harmer
5.837
24791305MDL-5G
Solar/Wind Harmer
3.256
945371AF1-202 GEN
Solar/Wind Harmer
9.414
958861AF2-177 GEN
Solar/Wind Harmer
14.687
274773LINCOLN ;4U
Adder
11.119
274774LINCOLN ;5U
Adder
11.119
274745AC1-111 GEN9
Adder
7.358
274761LEE CO EC;2U
Adder
12.246
274766LEE CO EC;7U
Adder
12.101
274732ELWOOD EC;7P
Adder
21.634
274822ROCKFORD ;11
Adder
25.827
274674JOLIET 9 ;6U
Adder
20.261
274682WAUKEGAN ;7U
Adder
11.397
238185AF2-356 C
Solar/Wind Helper
2.609
20089026BF_G21_K23
Solar/Wind Helper
0.538
238120AE2-309 GEN
Solar/Wind Helper
0.508
238126S14_GEN_1
Solar/Wind Helper
0.805
254303AC2-168 GEN
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.278
23751101LEADS_P59
Solar/Wind Helper
2.213
20084626FORWARD
Solar/Wind Helper
0.4
964201AG1-281 GEN
Solar/Wind Helper
0.541
20091526CHSTN_FL
Solar/Wind Helper
0.651
238109AE1-109 GEN2
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.142
203952AE2-129 C
Solar/Wind Helper
0.526
203855AF2-088 C
Solar/Wind Helper
0.169
209071AE2-133 GEN
Solar/Wind Helper
0.09
946691AF1-333 GEN
Solar/Wind Helper
0.496
946741AF1-338 GEN
Solar/Wind Helper
0.496
961421AF2-433 GEN
Solar/Wind Helper
0.495
957921AF2-086 GEN
Solar/Wind Helper
0.49
961331AF2-424 GEN
Solar/Wind Helper
0.495
208972BECR K09
Solar/Wind Helper
0.37
963161AG1-165 GEN
Solar/Wind Helper
0.492
203830AF1-094 GEN
Solar/Wind Helper
0.492
203979AG1-198 GEN
Solar/Wind Helper
0.295
316095T157 G97
Solar/Wind Helper
1.146
23583801GRNGAP
Solar/Wind Helper
4.253
211065PSPA IPP
Solar/Wind Helper
0.167
209116AE2-175 GEN
Solar/Wind Helper
1.956
961971AG1-040 GEN
Solar/Wind Helper
0.488
20674128FR_U2-059
Solar/Wind Helper
0.004
20671928W4-073
Solar/Wind Helper
0.097
207437AD2-070 GEN
Solar/Wind Helper
0.149
207511W3-106 GEN
Solar/Wind Helper
0.029
207510AF2-138 C
Solar/Wind Helper
0.088
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.349
20673728F2S_V4-070
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
219249CENTRALDIV C
Solar/Wind Helper
0.011
205941AD2-115 GEN
Solar/Wind Helper
0.528
20716928W4-060COL
Solar/Wind Helper
0.055
219612MATRIX C
Solar/Wind Helper
0.025
207454AA2-184 E
Solar/Wind Helper
0.33
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.005
20715728PEM_W1-119
Solar/Wind Helper
0.101
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.12
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.524
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233950AC2-186 GEN
Solar/Wind Helper
0.119
232434Z2-077 GEN
Solar/Wind Helper
0.13
233923SMA
Solar/Wind Helper
0.772
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.52
232417X3-008 C
Solar/Wind Helper
0.239
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.442
233987AB2-037 GEN
Solar/Wind Helper
2.403
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
233935AB2-179 C
Solar/Wind Helper
1.3
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
208835TUHI V3-051
Solar/Wind Helper
0.021
23777801MSM_W1-116
Solar/Wind Helper
0.099
24721605FLATG1
50/50
2.774
957241AF2-018 GEN
Solar/Wind Harmer
7.761
270053AF1-130 C
Solar/Wind Harmer
31.012
270399AC1-101 GEN
Solar/Wind Harmer
7.341
270400AC1-102 GEN
Solar/Wind Harmer
7.341
970281AG2-184 GEN
Solar/Wind Harmer
33.013
971985AH1-537 GEN
Solar/Wind Harmer
28.037
941621AE2-160 GEN
Adder
5.08
962211AG1-066 GEN
Solar/Wind Harmer
3.683
971313AH1-133 GEN
Solar/Wind Harmer
8.881
972163AH1-664 GEN
Solar/Wind Harmer
14.676
972165AH1-665 GEN
Solar/Wind Harmer
11.741
339216AC1-074 GEN
Solar/Wind Harmer
2.418
25196108MFTGT2
Adder
2.204
25196108MFTGT2
Adder
2.047
3429211JKCT 2G
Adder
16.761
25196408WSDLE3
Adder
12.643
25196308WSDLE2
Adder
12.533
25196208WSDLE1
Adder
12.501
25196708WSDLE6
Adder
12.47
25196508WSDLE4
Adder
12.156
24734705WLF1G3
Adder
8.239
24734805WLF1G4
Adder
8.239
24734905WLF1G5
Adder
8.239
253433AC1-085 GEN1
Solar/Wind Harmer
7.58
253432AC1-085 GEN2
Solar/Wind Harmer
0.381
270340AC2-060 GEN
Solar/Wind Harmer
4.299
253406AD2-031_GEN
Solar/Wind Harmer
1.814
270263AC1-001 GEN
Solar/Wind Harmer
1.479
270444AC2-157 GEN1
Solar/Wind Harmer
7.893
270445AC2-157 GEN2
Solar/Wind Harmer
7.893
270291AC1-194 GEN
Solar/Wind Harmer
7.194
24735105WLF2G1
Adder
8.122
270356AE2-297 GEN
Solar/Wind Harmer
6.397
971061AG2-657 GEN
Solar/Wind Harmer
12.414
253372AE2-315 SEC3
Adder
2.597
253372AE2-315 SEC3
Adder
2.597
25306009OHH W.
Adder
3.946
970289AG2-191 GEN
Solar/Wind Harmer
2.589
963841AG1-237 GEN
Solar/Wind Harmer
14.866
971029AG2-637 GEN
Solar/Wind Harmer
20.401
24386405FR-21G C
Solar/Wind Harmer
5.837
24387005FR-3G C
Solar/Wind Harmer
5.368
270543AE2-219 C
Solar/Wind Harmer
13.544
946581AF1-322 GEN
Solar/Wind Harmer
13.818
24691005MDL-2G C
Solar/Wind Harmer
4.994
945581AF1-223 GEN
Solar/Wind Harmer
6.119
247536S-71 GEN
Solar/Wind Harmer
5.458
964611AG1-324 GEN
Solar/Wind Harmer
5.25
270432AC2-029 GEN
Solar/Wind Harmer
9.42
944221AF1-090 GEN
Solar/Wind Harmer
14.705
961761AG1-017 GEN
Solar/Wind Harmer
0.575
24729505KEY G4
Adder
8.64
274775LINCOLN ;6U
Adder
11.119
274776LINCOLN ;7U
Adder
11.119
274777LINCOLN ;8U
Adder
11.119
274744AC1-111 GEN8
Adder
7.358
274746AC1-111 G10
Adder
7.358
972267AH1-718 GEN
Adder
5.481
274731ELWOOD EC;2P
Adder
21.634
274733ELWOOD EC;3P
Adder
21.634
274735ELWOOD EC;4P
Adder
21.634
274728ELWOOD EC;5P
Adder
21.634
274823ROCKFORD ;21
Adder
25.64
972228AH1-698 GEN2
Adder
4.874
972227AH1-698 GEN1
Adder
3.432
23750501ELLIOTTS
Solar/Wind Helper
0.784
23652301WDPWR_K20
Solar/Wind Helper
0.167
23750701CROSSCHOOL
Solar/Wind Helper
1.42
238118U2-030_1
Solar/Wind Helper
0.341
203955AF1-039 C O1
Solar/Wind Helper
0.43
20089126CSLMN_L13
Solar/Wind Helper
0.68
20089226LOOKOUT
Solar/Wind Helper
0.678
241997AF1-093 GEN
Solar/Wind Helper
0.278
241985AE1-237 GEN
Solar/Wind Helper
0.27
241982AE2-343 S C
Solar/Wind Helper
0.243
20088926STNY CRK
Solar/Wind Helper
0.922
203940AF1-140 C
Solar/Wind Helper
0.444
20094526CT_V3-030
Solar/Wind Helper
0.527
20088626ARWF_N39
Solar/Wind Helper
1.354
203846AF2-130 C
Solar/Wind Helper
0.494
20334926Z1-069 C
Solar/Wind Helper
1.481
200917MEHOOPANY_G
Solar/Wind Helper
2.413
209067AE2-060 GEN
Solar/Wind Helper
0.091
959431AF2-234 GEN
Solar/Wind Helper
0.993
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
959421AF2-233 GEN
Solar/Wind Helper
0.497
209054AE2-059 GEN
Solar/Wind Helper
0.09
209027LOR2_Q27
Solar/Wind Helper
1.157
212266LOR1
Solar/Wind Helper
0.337
209029WAYMART-WD
Solar/Wind Helper
0.93
961261AF2-417 GEN
Solar/Wind Helper
0.492
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.068
20676428JCR_X2-075
Solar/Wind Helper
0.073
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.172
20675528CPH_W2-050
Solar/Wind Helper
0.121
20720628TIN_W1-124
Solar/Wind Helper
0.202
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.111
20715028HAN_X4-015
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.06
959381AF2-229 GEN
Solar/Wind Helper
0.361
20390526W1-045 C
Solar/Wind Helper
0.355
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.08
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.042
228728W1-130C
Solar/Wind Helper
0.056
230434AG1-499 GEN
Solar/Wind Helper
0.24
232432Z2-076 GEN
Solar/Wind Helper
0.069
233901CHERRYDALE C
Solar/Wind Helper
0.239
233940AF2-379 C
Solar/Wind Helper
0.064
205956AE1-196_GEN
Solar/Wind Helper
0.52
205943AE1-185 GEN
Solar/Wind Helper
0.52
233915AB1-141 GEN
Solar/Wind Helper
0.515
205917AD1-020 ES
Solar/Wind Helper
0.366
237025AB1-124 C
Solar/Wind Helper
0.145
237030AB1-096 C
Solar/Wind Helper
0.059
23779801AA1-109
Solar/Wind Helper
0.167
238169AE2-226 GEN1
Solar/Wind Helper
0.55
238170AE2-226 GEN2
Solar/Wind Helper
0.55
24289405MTG1
50/50
11.396
24318705GVG2
50/50
11.631
24722005FLATG5
50/50
2.774
24721905FLATG4
50/50
50.672
24686405CER G5
Adder
15.544
270330AC1-082 GEN2
Solar/Wind Harmer
0.849
270329AC1-082 GEN1
Solar/Wind Harmer
0.849
962771AG1-126 GEN
Solar/Wind Harmer
55.006
970153AG2-106 GEN
Solar/Wind Harmer
23.985
971191AH1-055 GEN
Solar/Wind Harmer
31.424
957541AF2-048 GEN
Solar/Wind Harmer
2.499
972103AH1-617 GEN
Solar/Wind Harmer
31.441
960911AF2-382 GEN
Solar/Wind Harmer
11.571
971461AH1-227 GEN
Solar/Wind Harmer
7.869
270367AC2-061_GEN
Solar/Wind Harmer
4.734
270186AC1-089 GEN
Solar/Wind Harmer
9.096
970879AG2-548 GEN
Solar/Wind Harmer
11.766
972167AH1-666 GEN
Solar/Wind Harmer
11.731
252507AC2-088 GEN
Solar/Wind Harmer
2.611
958171AF2-111 GEN
Solar/Wind Harmer
36.196
339243AC2-075 GEN1
Solar/Wind Harmer
0.655
252519AF1-045_GEN
Solar/Wind Harmer
5.251
25196008MFTGT1
Adder
1.936
25194608D.CRK4
Adder
2.359
252524AE2-267 GEN
Solar/Wind Harmer
2.256
25196608WSDLE5
Adder
12.281
3429391JKCT 9G
Adder
11.925
970093AG2-073 GEN
Solar/Wind Harmer
7.582
253317AC1-085 GEN4
Solar/Wind Harmer
11.942
946181AF1-283 GEN
Solar/Wind Harmer
18.543
253394AE2-221_GEN
Solar/Wind Harmer
6.388
970455AG2-298 GEN
Solar/Wind Harmer
4.914
970653AG2-424 GEN
Solar/Wind Harmer
0.97
339206AE1-143 GEN
Solar/Wind Harmer
2.962
972273AH1-721 GEN
Adder
115.342
24728705AND G3
Adder
11.088
24728505AND G1
Adder
5.301
970193AG2-126 GEN
Solar/Wind Harmer
20.616
24379505HDWTR1G C
Solar/Wind Harmer
10.862
270240V3-007_GEN2
Solar/Wind Harmer
8.498
253303V4-073 C
Solar/Wind Harmer
0.159
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
270346AE1-212 GEN
Solar/Wind Harmer
12.332
247642Z2-115 C
Solar/Wind Harmer
0.087
965461AG1-414 GEN
Solar/Wind Harmer
3.09
970289AG2-191 GEN
Solar/Wind Harmer
1.046
270004AE1-209 GEN
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
7.662
946031AF1-268 GEN
Solar/Wind Harmer
11.269
24386205FR-12G C
Solar/Wind Harmer
5.816
960071AF2-298 GEN
Solar/Wind Harmer
2.052
339255AE2-071 GEN
Solar/Wind Harmer
1.586
339250AF1-203 GEN
Solar/Wind Harmer
0.817
24690905MDL-1G C
Solar/Wind Harmer
10.842
970781AG2-491 GEN
Solar/Wind Harmer
13.505
962031AG1-047 GEN
Solar/Wind Harmer
4.061
274772LINCOLN ;3U
Adder
11.119
972259AH1-714 GEN
Adder
25.12
274760LEE CO EC;1U
Adder
12.246
274767LEE CO EC;8U
Adder
12.101
274729ELWOOD EC;1P
Adder
21.634
274730ELWOOD EC;6P
Adder
21.634
274734ELWOOD EC;8P
Adder
21.634
274736ELWOOD EC;9P
Adder
21.634
274682WAUKEGAN ;7U
Adder
23.647
237048AF1-022 C
Solar/Wind Helper
0.229
237046AF1-021 C
Solar/Wind Helper
0.396
235058AG1-386 C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
1.065
964991AG1-363 GEN
Solar/Wind Helper
4.388
202652Y1-033 WT C
Solar/Wind Helper
0.652
238127S14_GEN_2
Solar/Wind Helper
0.805
20092526R32
Solar/Wind Helper
1.303
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20303426NA_O38_P22
Solar/Wind Helper
1.11
203993AD2-133_GEN1
Solar/Wind Helper
1.142
203854AF2-039 C
Solar/Wind Helper
0.352
20398826ARMNA MT
Solar/Wind Helper
1.645
941421AE2-139 GEN
Solar/Wind Helper
2.555
209137AF2-361 C
Solar/Wind Helper
1.523
946731AF1-337 GEN
Solar/Wind Helper
0.496
212507AE2-042_GEN
Solar/Wind Helper
1.759
961341AF2-425 GEN
Solar/Wind Helper
0.495
961301AF2-421 GEN
Solar/Wind Helper
0.492
963151AG1-164 GEN
Solar/Wind Helper
0.492
211065PSPA IPP
Solar/Wind Helper
0.167
207518AF1-320_GEN
Solar/Wind Helper
1.705
20675728RH_W2-091
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.032
203975AE1-071-GEN
Solar/Wind Helper
2.659
207484AF2-139 C O1
Solar/Wind Helper
0.091
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
20674628WNG_W3-110
Solar/Wind Helper
0.097
20676328BVR_Y1-020
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.072
207439AE1-081 C O1
Solar/Wind Helper
0.02
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.485
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.172
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.083
20720528MAN_W1-024
Solar/Wind Helper
0.03
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219276PARKLANDSO C
Solar/Wind Helper
0.095
20715828PEM_W1-120
Solar/Wind Helper
0.101
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.12
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.057
228729W2-030 C
Solar/Wind Helper
0.116
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.52
232408W1-005 C
Solar/Wind Helper
0.52
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.52
233944AB2-135 GEN
Solar/Wind Helper
0.605
233918AB1-142 GEN
Solar/Wind Helper
0.515
235063AE1-101 C2
Solar/Wind Helper
1.456
205916AD1-020 GEN
Solar/Wind Helper
1.701
237001AB1-127_GEN
Solar/Wind Helper
0.386
23777901MDS_W4-102
Solar/Wind Helper
0.149
208835TUHI V3-051
Solar/Wind Helper
0.021
238175AF1-290_GEN
Solar/Wind Helper
0.125
957741AF2-068 GEN
Solar/Wind Harmer
8.369
243186AF1-051 GEN
50/50
12.548
24721705FLATG2
50/50
41.198
24723005RIVRG1
Adder
36.155
24723105RIVRG2
Adder
36.155
927014AC1-188 GEN
Solar/Wind Harmer
2.499
970913AG2-568 GEN
Solar/Wind Harmer
10.718
971225AH1-072 GEN
Solar/Wind Harmer
3.068
971227AH1-073 GEN
Solar/Wind Harmer
3.068
24728205BUCHG1
Adder
6.863
962581AG1-107 GEN
Solar/Wind Harmer
7.459
961491AF2-440 GEN
Solar/Wind Harmer
3.1
971073AG2-665 GEN
Solar/Wind Harmer
11.766
970879AG2-548 GEN
Solar/Wind Harmer
1.71
252509AD1-136 GEN
Solar/Wind Harmer
0.373
972043AH1-570 GEN
Solar/Wind Harmer
3.62
972045AH1-571 GEN
Solar/Wind Harmer
2.896
25183208HLCRTG
Solar/Wind Harmer
8.737
971125AH1-004 GEN
Solar/Wind Harmer
5.746
970107AG2-081 GEN
Solar/Wind Harmer
4.31
25194408D.CRK1
Adder
10.853
25194508D.CRK3
Adder
2.029
942891AE2-308 GEN
Solar/Wind Harmer
14.341
253415AE1-040 GEN
Solar/Wind Harmer
1.586
964571AG1-320 GEN
Solar/Wind Harmer
11.455
270269AC2-059
Solar/Wind Harmer
12.928
24728805RICHG1
Adder
5.238
24728905RICHG2
Adder
5.238
945391AF1-204 GEN
Solar/Wind Harmer
19.154
926881AC1-175 GEN
Solar/Wind Harmer
7.667
253370AE2-315 SEC1
Adder
2.746
270383AD1-128 GEN
Solar/Wind Harmer
8.356
339231AF1-038_GEN
Solar/Wind Harmer
2.483
24725505WLD G2 C
Solar/Wind Harmer
5.437
24699105WLD G1 C
Solar/Wind Harmer
5.374
339236AF1-050_GEN
Solar/Wind Harmer
2.477
970241AG2-163 GEN
Solar/Wind Harmer
34.084
970291AG2-192 GEN
Solar/Wind Harmer
1.771
970291AG2-192 GEN
Solar/Wind Harmer
0.57
253349AC2-067 GEN
Solar/Wind Harmer
2.769
253400AC2-068 GEN
Solar/Wind Harmer
1.114
25322209TAIT E
Adder
13.248
25322209TAIT E
Adder
12.95
24387305FR-4G C
Solar/Wind Harmer
6.894
966841AG1-555 GEN
Solar/Wind Harmer
3.407
970883AG2-550 GEN
Solar/Wind Harmer
13.544
970885AG2-551 GEN
Solar/Wind Harmer
3.15
270180AB1-006 GEN1
Solar/Wind Harmer
9.713
24697605MDL-3G C
Solar/Wind Harmer
4.978
24755605MDL-5G
Solar/Wind Harmer
3.256
24697905MDL-4G C
Solar/Wind Harmer
3.099
270181AB1-006 GEN2
Solar/Wind Harmer
0.966
971485AH1-239 GEN
Solar/Wind Harmer
10.793
964781AG1-341 GEN
Solar/Wind Harmer
14.3
966021AG1-471 GEN
Solar/Wind Harmer
7.284
270031AE2-169
Solar/Wind Harmer
10.99
270599AE1-208 GEN
Solar/Wind Harmer
10.99
945421AF1-207 GEN
Solar/Wind Harmer
18.926
957841AF2-078 GEN
Solar/Wind Harmer
8.147
25326109MON D
Adder
1.772
964611AG1-324 GEN
Solar/Wind Harmer
0.704
247621Y3-024
Adder
0.324
270201AC2-176 GEN
Solar/Wind Harmer
6.903
274770LINCOLN ;1U
Adder
11.119
274771LINCOLN ;2U
Adder
11.119
274696ROCKY RD ;4P
Adder
15.001
274695ROCKY RD ;2P
Adder
14.655
274693ROCKY RD ;1P
Adder
14.51
274764LEE CO EC;5U
Adder
12.274
274765LEE CO EC;6U
Adder
12.274
274762LEE CO EC;3U
Adder
12.246
274763LEE CO EC;4U
Adder
12.13
274697ROCKY RD ;3P
Adder
3.981
274674JOLIET 9 ;6U
Adder
20.261
972235AH1-702 GEN1
Adder
3.317
972236AH1-702 GEN2
Adder
2.884
23585401KL_K28_T16
Solar/Wind Helper
1.522
237043AE2-125 C
Solar/Wind Helper
0.207
23751201ROTHROCK
Solar/Wind Helper
0.874
235054AD2-180 GEN
Solar/Wind Helper
2.021
238117U2-030
Solar/Wind Helper
0.341
235531U2-073 GEN
Solar/Wind Helper
3.241
962101AG1-054 GEN
Solar/Wind Helper
0.711
254304AE2-114 C
Solar/Wind Helper
0.238
254305AE2-115 C
Solar/Wind Helper
0.238
20083426SW_E13_K22
Solar/Wind Helper
0.063
241967AE2-285_GEN
Solar/Wind Helper
0.691
241801AE1-079 GEN
Solar/Wind Helper
0.27
946071AF1-272 GEN
Solar/Wind Helper
3.032
20088826HIGHLAND
Solar/Wind Helper
1.005
203961AE2-224 GEN
Solar/Wind Helper
2.695
203818AF1-086 GEN
Solar/Wind Helper
1.876
203853AF1-134 C O1
Solar/Wind Helper
0.53
946381AF1-302 GEN
Solar/Wind Helper
0.245
203946AE2-131 C
Solar/Wind Helper
0.526
203954AE2-126 C
Solar/Wind Helper
0.519
940863AE2-074 GEN
Solar/Wind Helper
0.501
203804AE2-113_GEN
Solar/Wind Helper
1.916
946751AF1-339 GEN
Solar/Wind Helper
0.496
961431AF2-434 GEN
Solar/Wind Helper
0.495
316097T157 G90
Solar/Wind Helper
1.146
203835AF1-098 GEN
Solar/Wind Helper
1.948
207471AF2-354 C
Solar/Wind Helper
0.183
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.054
20674328GAR_V4-001
Solar/Wind Helper
0.024
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.15
20714828MDF_W3-079
Solar/Wind Helper
0.138
207459AE1-142 C O1
Solar/Wind Helper
0.307
20720828JCB_W4-025
Solar/Wind Helper
0.067
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.084
219304NAMERICA C
Solar/Wind Helper
0.138
219906AC1-017 C
Solar/Wind Helper
0.044
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.157
219904AC1-010 C
Solar/Wind Helper
0.063
228754AB1-001 C
Solar/Wind Helper
0.027
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.015
233952AC2-187 GEN
Solar/Wind Helper
0.239
233954AC2-188 GEN
Solar/Wind Helper
0.239
233994AC2-023 GEN
Solar/Wind Helper
0.986
232410W1-006 C
Solar/Wind Helper
0.52
232428Y3-058 C
Solar/Wind Helper
0.347
234015AF2-250 C
Solar/Wind Helper
0.039
233946AB2-136 GEN
Solar/Wind Helper
0.583
234036AF2-325 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.368
233930AB2-032 GEN
Solar/Wind Helper
0.39
232436AB1-176 C
Solar/Wind Helper
0.046
235062AE1-101 C1
Solar/Wind Helper
1.456
237080AD1-060 GEN
Solar/Wind Helper
0.295
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.235
237006AB1-125 GEN
Solar/Wind Helper
0.109
223401AF1-299 GEN
Solar/Wind Helper
0.336
223402AF1-300 C
Solar/Wind Helper
0.336
LAGNLTFEXP_LAGN->PJM
CLTF
25.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.459
TVALTFEXP_TVA->PJM
CLTF
12.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
171.353
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.863
MECLTFEXP_MEC->PJM
CLTF
22.066
SIGELTFEXP_SIGE->PJM
CLTF
0.733
CPLELTFEXP_CPLE->PJM
CLTF
6.636
CBM West 2LTFEXP_CBM-W2->PJM
CBM
174.171
NYPJM->LTFIMP_NY
CLTF
6.23
LGEELTFEXP_LGEE->PJM
CLTF
9.895
WECLTFEXP_WEC->PJM
CLTF
5.031
AG2-052LTFEXP_AG2-052->PJM
LTF
0.308
AH1-155LTFEXP_AH1-155->PJM
LTF
0.462

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4976.63
MW Contribution:
6.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
10.896
243186AF1-051 GEN
50/50
11.683
24318705GVG2
50/50
10.829
24721805FLATG3
50/50
2.475
24723205RIVRG3
Adder
32.69
972203AH1-686 GEN
Adder
3.965
24686505CER G6
Adder
14.074
944971AF1-162 GEN
Solar/Wind Harmer
10.992
971403AH1-188 GEN
Solar/Wind Harmer
15.251
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
6.196
971687AH1-348 GEN
Solar/Wind Harmer
0.943
24735205WLF2G2
Adder
7.131
971073AG2-665 GEN
Solar/Wind Harmer
1.329
970091AG2-072 GEN
Adder
86.562
945681AF1-233 GEN
Solar/Wind Harmer
14.491
3429241JKCT 3G
Adder
13.004
3429421JKCT 10G
Adder
9.095
970653AG2-424 GEN
Solar/Wind Harmer
3.596
964901AG1-354 GEN
Solar/Wind Harmer
11.126
25196808ZIMRHP
Adder
79.991
25196008MFTGT1
Adder
1.457
252516AE2-318_GEN
Solar/Wind Harmer
8.161
252510AF1-249 C
Solar/Wind Harmer
0.055
25194608D.CRK4
Adder
1.702
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.045
962761AG1-125 GEN
Solar/Wind Harmer
27.311
970149AG2-104 GEN
Solar/Wind Harmer
14.748
970155AG2-107 GEN
Solar/Wind Harmer
17.44
253398AE2-221_GEN2
Solar/Wind Harmer
0
24728605AND G2
Adder
3.745
970773AG2-487 GEN
Solar/Wind Harmer
1.199
963741AG1-226 GEN
Solar/Wind Harmer
15.765
965911AG1-460 GEN
Solar/Wind Harmer
1.325
943811AF1-049 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.832
276621W2-048 GEN
Solar/Wind Harmer
0.329
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.31
270594AE1-207 GEN
Solar/Wind Harmer
7.264
270032AE2-172
Solar/Wind Harmer
4.324
270273AD2-016 GEN
Solar/Wind Harmer
0.662
270005AE1-210 C O1
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
2.292
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.961
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.933
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.248
276708O09 GEN2
Solar/Wind Harmer
0.223
970569AG2-363 GEN
Solar/Wind Harmer
18.869
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.386
24721605FLATG1
50/50
2.475
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
24.531
270399AC1-101 GEN
Solar/Wind Harmer
3.431
270400AC1-102 GEN
Solar/Wind Harmer
3.431
941621AE2-160 GEN
Adder
4.685
970281AG2-184 GEN
Solar/Wind Harmer
20.069
971313AH1-133 GEN
Solar/Wind Harmer
4.633
971061AG2-657 GEN
Solar/Wind Harmer
5.63
24734705WLF1G3
Adder
7.275
24734805WLF1G4
Adder
7.275
24734905WLF1G5
Adder
7.275
971985AH1-537 GEN
Solar/Wind Harmer
2.606
24735105WLF2G1
Adder
7.131
966391AG1-508 GEN
Solar/Wind Harmer
1.323
971331AH1-145 GEN
Solar/Wind Harmer
10.902
971329AH1-144 GEN
Solar/Wind Harmer
4.007
971981AH1-535 GEN
Solar/Wind Harmer
5.247
972163AH1-664 GEN
Solar/Wind Harmer
8.578
972165AH1-665 GEN
Solar/Wind Harmer
6.87
3429211JKCT 2G
Adder
12.836
339216AC1-074 GEN
Solar/Wind Harmer
0.202
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.606
25196108MFTGT2
Adder
1.492
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
9.098
25196308WSDLE2
Adder
9.019
25196208WSDLE1
Adder
8.997
25196708WSDLE6
Adder
8.974
25196508WSDLE4
Adder
8.748
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.692
270069AE2-166 C O1
Solar/Wind Harmer
6.22
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.926
963841AG1-237 GEN
Solar/Wind Harmer
2.866
24386405FR-21G C
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.257
276848AB2-070 GEN3
Solar/Wind Harmer
0.256
276849AB2-070 GEN2
Solar/Wind Harmer
0.257
970289AG2-191 GEN
Solar/Wind Harmer
1.233
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.69
274854TWINGROVE;U2
Solar/Wind Harmer
0
25306009OHH W.
Adder
2.654
253372AE2-315 SEC3
Adder
1.743
253372AE2-315 SEC3
Adder
1.743
270543AE2-219 C
Solar/Wind Harmer
4.484
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.721
247536S-71 GEN
Solar/Wind Harmer
0.254
971611AH1-305 GEN
Solar/Wind Harmer
3.778
946321AF1-296 GEN
Solar/Wind Harmer
3.554
274877BISHOP HL;1U
Solar/Wind Harmer
0.211
24289405MTG1
50/50
10.896
24318705GVG2
50/50
10.829
24722005FLATG5
50/50
2.475
24721905FLATG4
50/50
45.211
24686405CER G5
Adder
13.963
971191AH1-055 GEN
Solar/Wind Harmer
25.524
960911AF2-382 GEN
Solar/Wind Harmer
7.256
972103AH1-617 GEN
Solar/Wind Harmer
19.113
971461AH1-227 GEN
Solar/Wind Harmer
4.836
270346AE1-212 GEN
Solar/Wind Harmer
7.826
943031AE2-326 GEN
Solar/Wind Harmer
4.478
970879AG2-548 GEN
Solar/Wind Harmer
5.846
958121AF2-106 GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
6.527
972167AH1-666 GEN
Solar/Wind Harmer
6.143
972273AH1-721 GEN
Adder
91.222
3429391JKCT 9G
Adder
9.095
970455AG2-298 GEN
Solar/Wind Harmer
2.913
958171AF2-111 GEN
Solar/Wind Harmer
18.695
252507AC2-088 GEN
Solar/Wind Harmer
0.336
970653AG2-424 GEN
Solar/Wind Harmer
0.745
25196008MFTGT1
Adder
1.411
252519AF1-045_GEN
Solar/Wind Harmer
3.801
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.838
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.158
962771AG1-126 GEN
Solar/Wind Harmer
27.311
970153AG2-106 GEN
Solar/Wind Harmer
17.44
253394AE2-221_GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.239
24728705AND G3
Adder
7.833
24728505AND G1
Adder
3.745
270030AE2-140 GEN
Solar/Wind Harmer
13.518
942481AE2-261 GEN
Solar/Wind Harmer
19.808
957381AF2-032 GEN
Solar/Wind Harmer
1.5
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.022
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.714
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.48
270004AE1-209 GEN
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
4.865
965091AG1-374 GEN
Solar/Wind Harmer
19.301
946031AF1-268 GEN
Solar/Wind Harmer
6.123
959611AF2-252 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
970191AG2-125 GEN
Solar/Wind Harmer
1.638
965931AG1-462 GEN
Solar/Wind Harmer
16.203
971087AG2-675 GEN
Solar/Wind Harmer
3.389
274878BISHOP HL;2U
Solar/Wind Harmer
0.211
276782AC1-033 GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.45
970571AG2-364 GEN
Solar/Wind Harmer
12.579
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.386
274767LEE CO EC;8U
Adder
8.287
959091AF2-200 GEN
Solar/Wind Harmer
12.516
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
946671AF1-331 GEN
Solar/Wind Harmer
0.666
276868AE1-113 GEN
Solar/Wind Harmer
1.25
274879MINONK ;1U
Solar/Wind Harmer
0.261
274682WAUKEGAN ;7U
Adder
16.004
274862TOP CROP ;2U
Solar/Wind Harmer
0.839
943121AE2-341 GEN
Solar/Wind Harmer
10.39
943591AF1-030 GEN
Solar/Wind Harmer
6.91
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
14.558
274730ELWOOD EC;6P
Adder
14.558
274734ELWOOD EC;8P
Adder
14.558
274736ELWOOD EC;9P
Adder
14.558
970707AG2-453 GEN
Solar/Wind Harmer
20.15
274887GEN-1.85
Solar/Wind Harmer
0.16
276843GEN-1.7
Solar/Wind Harmer
0.199
276806AD2-047 C O1
Solar/Wind Harmer
3.488
237048AF1-022 C
Solar/Wind Helper
0.175
237046AF1-021 C
Solar/Wind Helper
0.301
235058AG1-386 C
Solar/Wind Helper
0.387
23562501BACKB
Solar/Wind Helper
0.811
274766LEE CO EC;7U
Adder
8.287
25326309TAIT D
Adder
0.988
945371AF1-202 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
7.523
939401AE1-172 GEN
Solar/Wind Harmer
4.684
274822ROCKFORD ;11
Adder
17.613
957471AF2-041 GEN
Solar/Wind Harmer
18.774
959081AF2-199 GEN
Solar/Wind Harmer
6.258
971067AG2-660 GEN
Solar/Wind Harmer
2.086
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.135
971997AH1-543 GEN
Solar/Wind Harmer
3.283
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.729
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.929
274828WAUKEGAN ;BP
Adder
9.84
274682WAUKEGAN ;7U
Adder
16.004
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.692
276691AA1-018 GEN1
Solar/Wind Harmer
1.009
274745AC1-111 GEN9
Adder
4.965
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.558
274674JOLIET 9 ;6U
Adder
13.632
965651AG1-433 GEN
Solar/Wind Harmer
1.811
274676JOLIET 29;8U
Adder
9.572
238185AF2-356 C
Solar/Wind Helper
1.975
970373AG2-245 GEN
Solar/Wind Harmer
5.443
971609AH1-304 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
2.468
970169AG2-114 GEN
Solar/Wind Harmer
6.325
276741O09 GEN1
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.763
926823AC1-168 GEN
Solar/Wind Harmer
1.07
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.116
274856ECOGROVE ;U1
Solar/Wind Harmer
0.147
274823ROCKFORD ;21
Adder
17.485
971171AH1-044 GEN
Solar/Wind Harmer
12.516
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971675AH1-338 GEN
Solar/Wind Harmer
2.437
971411AH1-196 GEN
Solar/Wind Harmer
9.369
970073AG2-061 GEN
Solar/Wind Harmer
2.078
274744AC1-111 GEN8
Adder
4.965
274746AC1-111 G10
Adder
4.965
970833AG2-524 GEN
Solar/Wind Harmer
6.809
970833AG2-524 GEN
Solar/Wind Harmer
4.54
274728ELWOOD EC;5P
Adder
14.558
274731ELWOOD EC;2P
Adder
14.558
274733ELWOOD EC;3P
Adder
14.558
274735ELWOOD EC;4P
Adder
14.558
274675JOLIET 29;7U
Adder
27.142
960591AF2-350 GEN
Solar/Wind Harmer
6.155
23750501ELLIOTTS
Solar/Wind Helper
0.598
23652301WDPWR_K20
Solar/Wind Helper
0.127
243186AF1-051 GEN
50/50
11.683
24721705FLATG2
50/50
36.759
24723005RIVRG1
Adder
32.69
24723105RIVRG2
Adder
32.69
970913AG2-568 GEN
Solar/Wind Harmer
8.105
24728205BUCHG1
Adder
6.196
971225AH1-072 GEN
Solar/Wind Harmer
1.885
971227AH1-073 GEN
Solar/Wind Harmer
1.885
971277AH1-098 GEN
Solar/Wind Harmer
3.388
971073AG2-665 GEN
Solar/Wind Harmer
5.846
970879AG2-548 GEN
Solar/Wind Harmer
1.329
270583AD2-179 GEN
Solar/Wind Harmer
7.872
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942891AE2-308 GEN
Solar/Wind Harmer
7.677
972043AH1-570 GEN
Solar/Wind Harmer
1.99
972045AH1-571 GEN
Solar/Wind Harmer
1.594
971125AH1-004 GEN
Solar/Wind Harmer
3.042
970107AG2-081 GEN
Solar/Wind Harmer
2.281
966021AG1-471 GEN
Solar/Wind Harmer
4.034
252509AD1-136 GEN
Solar/Wind Harmer
0.037
971485AH1-239 GEN
Solar/Wind Harmer
5.968
964571AG1-320 GEN
Solar/Wind Harmer
6.787
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25183208HLCRTG
Solar/Wind Harmer
0
971587AH1-292 GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
7.827
25194508D.CRK3
Adder
1.463
945391AF1-204 GEN
Solar/Wind Harmer
7.253
24728805RICHG1
Adder
3.656
24728905RICHG2
Adder
3.656
970241AG2-163 GEN
Solar/Wind Harmer
3.886
276916AD2-100_GEN
Solar/Wind Harmer
13.944
276911AD2-131_GEN
Solar/Wind Harmer
0.919
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.068
276838X2-022 GEN2
Solar/Wind Harmer
0.37
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.743
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.844
970291AG2-192 GEN
Solar/Wind Harmer
0.389
971613AH1-306 GEN
Solar/Wind Harmer
3.113
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
970883AG2-550 GEN
Solar/Wind Harmer
6.406
970885AG2-551 GEN
Solar/Wind Harmer
2.135
942111AE2-223 GEN
Solar/Wind Harmer
2.08
270031AE2-169
Solar/Wind Harmer
3.483
270599AE1-208 GEN
Solar/Wind Harmer
5.804
276645AC1-214 GEN1
Solar/Wind Harmer
0.248
964611AG1-324 GEN
Solar/Wind Harmer
0.475
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.019
247621Y3-024
Adder
0.218
270201AC2-176 GEN
Solar/Wind Harmer
0
25322209TAIT E
Adder
8.794
25322209TAIT E
Adder
8.596
274764LEE CO EC;5U
Adder
8.405
274765LEE CO EC;6U
Adder
8.405
274762LEE CO EC;3U
Adder
8.386
274763LEE CO EC;4U
Adder
8.307
938861AE1-114 GEN
Solar/Wind Harmer
3.56
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.263
972236AH1-702 GEN2
Adder
1.968
971341AH1-150 GEN
Solar/Wind Harmer
12.516
971343AH1-151 GEN
Solar/Wind Harmer
12.516
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.353
962691AG1-118 GEN
Solar/Wind Harmer
18.68
274683WAUKEGAN ;8U
Adder
18.772
274683WAUKEGAN ;8U
Adder
15.824
274696ROCKY RD ;4P
Adder
10.15
274695ROCKY RD ;2P
Adder
9.916
274693ROCKY RD ;1P
Adder
9.818
274697ROCKY RD ;3P
Adder
2.694
958481AF2-142 GEN
Solar/Wind Harmer
9.318
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
15.453
276893AG1-478 C
Solar/Wind Harmer
0.412
274674JOLIET 9 ;6U
Adder
13.632
944541AF1-119 GEN
Solar/Wind Harmer
0.412
960971AF2-388 GEN
Solar/Wind Harmer
3.621
274888KELLY CRK;1U
Solar/Wind Harmer
0.359
276776AD2-060 GEN
Solar/Wind Harmer
0.657
958011AF2-095 GEN
Solar/Wind Harmer
8.864
970941AG2-585 GEN
Solar/Wind Harmer
3.385
23585401KL_K28_T16
Solar/Wind Helper
1.157
237043AE2-125 C
Solar/Wind Helper
0.157
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.531
LAGNLTFEXP_LAGN->PJM
CLTF
19.698
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23
TVALTFEXP_TVA->PJM
CLTF
10.208
CBM West 1LTFEXP_CBM-W1->PJM
CBM
115.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.783
MECLTFEXP_MEC->PJM
CLTF
15.666
SIGELTFEXP_SIGE->PJM
CLTF
0.545
CPLELTFEXP_CPLE->PJM
CLTF
6.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.098
NYPJM->LTFIMP_NY
CLTF
4.626
LGEELTFEXP_LGEE->PJM
CLTF
7.468
WECLTFEXP_WEC->PJM
CLTF
3.435
AG2-052LTFEXP_AG2-052->PJM
LTF
0.207
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5896.19
MW Contribution:
7.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
9.827
24728205BUCHG1
Adder
7.739
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
18.148
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.157
24735205WLF2G2
Adder
8.97
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
3429241JKCT 3G
Adder
15.659
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
17.283
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
964901AG1-354 GEN
Solar/Wind Harmer
13.534
970653AG2-424 GEN
Solar/Wind Harmer
4.351
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
9.728
252510AF1-249 C
Solar/Wind Harmer
0.065
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.427
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
32.057
970149AG2-104 GEN
Solar/Wind Harmer
17.311
970155AG2-107 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.031
970773AG2-487 GEN
Solar/Wind Harmer
1.442
963741AG1-226 GEN
Solar/Wind Harmer
19.023
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
0.398
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.825
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.823
270594AE1-207 GEN
Solar/Wind Harmer
8.772
270032AE2-172
Solar/Wind Harmer
5.222
270005AE1-210 C O1
Solar/Wind Harmer
1.692
970825AG2-519 GEN
Solar/Wind Harmer
2.77
270273AD2-016 GEN
Solar/Wind Harmer
0.795
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
10.877
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.302
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.607
276708O09 GEN2
Solar/Wind Harmer
0.271
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
970569AG2-363 GEN
Solar/Wind Harmer
22.948
970819AG2-516 GEN
Solar/Wind Harmer
9.157
274822ROCKFORD ;11
Adder
21.436
957471AF2-041 GEN
Solar/Wind Harmer
22.848
959081AF2-199 GEN
Solar/Wind Harmer
7.616
971067AG2-660 GEN
Solar/Wind Harmer
2.539
945371AF1-202 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.694
971997AH1-543 GEN
Solar/Wind Harmer
3.993
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
28.948
270399AC1-101 GEN
Solar/Wind Harmer
4.065
270400AC1-102 GEN
Solar/Wind Harmer
4.065
971313AH1-133 GEN
Solar/Wind Harmer
5.869
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
1.796
970281AG2-184 GEN
Solar/Wind Harmer
24.292
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
5.625
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
6.84
971985AH1-537 GEN
Solar/Wind Harmer
3.035
971981AH1-535 GEN
Solar/Wind Harmer
6.584
270069AE2-166 C O1
Solar/Wind Harmer
8.709
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
10.231
972165AH1-665 GEN
Solar/Wind Harmer
8.194
339216AC1-074 GEN
Solar/Wind Harmer
0.242
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253406AD2-031_GEN
Solar/Wind Harmer
0.618
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.825
270197AD1-017 GEN1
Solar/Wind Harmer
1.008
270356AE2-297 GEN
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.756
963841AG1-237 GEN
Solar/Wind Harmer
3.459
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.489
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.702
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.158
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
270543AE2-219 C
Solar/Wind Harmer
5.421
946321AF1-296 GEN
Solar/Wind Harmer
4.325
274877BISHOP HL;1U
Solar/Wind Harmer
0.257
247536S-71 GEN
Solar/Wind Harmer
0.307
971611AH1-305 GEN
Solar/Wind Harmer
4.575
970169AG2-114 GEN
Solar/Wind Harmer
7.684
276741O09 GEN1
Solar/Wind Harmer
0.271
972267AH1-718 GEN
Adder
4.579
971609AH1-304 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
2.987
926823AC1-168 GEN
Solar/Wind Harmer
1.302
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
12.311
274856ECOGROVE ;U1
Solar/Wind Harmer
0.178
274823ROCKFORD ;21
Adder
21.28
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.232
25326309TAIT D
Adder
1.195
276882AE2-255 GEN
Solar/Wind Harmer
0.887
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.865
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.216
958381AF2-132 GEN
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.136
276863AD2-134 GEN
Solar/Wind Harmer
0.136
971675AH1-338 GEN
Solar/Wind Harmer
2.966
971411AH1-196 GEN
Solar/Wind Harmer
11.402
970073AG2-061 GEN
Solar/Wind Harmer
2.528
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
970833AG2-524 GEN
Solar/Wind Harmer
8.285
970833AG2-524 GEN
Solar/Wind Harmer
5.523
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
960591AF2-350 GEN
Solar/Wind Harmer
7.491
971225AH1-072 GEN
Solar/Wind Harmer
2.315
971227AH1-073 GEN
Solar/Wind Harmer
2.315
971277AH1-098 GEN
Solar/Wind Harmer
4.618
270583AD2-179 GEN
Solar/Wind Harmer
11.364
971073AG2-665 GEN
Solar/Wind Harmer
6.854
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
9.244
972043AH1-570 GEN
Solar/Wind Harmer
2.384
972045AH1-571 GEN
Solar/Wind Harmer
1.91
971125AH1-004 GEN
Solar/Wind Harmer
3.655
970107AG2-081 GEN
Solar/Wind Harmer
2.741
966021AG1-471 GEN
Solar/Wind Harmer
4.933
971485AH1-239 GEN
Solar/Wind Harmer
7.296
962581AG1-107 GEN
Solar/Wind Harmer
0.002
964781AG1-341 GEN
Solar/Wind Harmer
9.518
964571AG1-320 GEN
Solar/Wind Harmer
8.194
252509AD1-136 GEN
Solar/Wind Harmer
0.044
25183208HLCRTG
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.363
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
8.741
942671AE2-283 GEN
Solar/Wind Harmer
3.812
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
276916AD2-100_GEN
Solar/Wind Harmer
16.897
276911AD2-131_GEN
Solar/Wind Harmer
1.113
970241AG2-163 GEN
Solar/Wind Harmer
4.689
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.448
926881AC1-175 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.897
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
1.019
970291AG2-192 GEN
Solar/Wind Harmer
0.47
971613AH1-306 GEN
Solar/Wind Harmer
3.76
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.602
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
2.525
253370AE2-315 SEC1
Adder
2.225
970883AG2-550 GEN
Solar/Wind Harmer
7.744
970885AG2-551 GEN
Solar/Wind Harmer
2.581
276645AC1-214 GEN1
Solar/Wind Harmer
0.302
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
960911AF2-382 GEN
Solar/Wind Harmer
8.992
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
5.939
972103AH1-617 GEN
Solar/Wind Harmer
23.135
971191AH1-055 GEN
Solar/Wind Harmer
29.317
270346AE1-212 GEN
Solar/Wind Harmer
10.045
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
6.854
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
18.672
970093AG2-073 GEN
Solar/Wind Harmer
7.87
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
8.058
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970653AG2-424 GEN
Solar/Wind Harmer
0.902
958171AF2-111 GEN
Solar/Wind Harmer
22.344
252507AC2-088 GEN
Solar/Wind Harmer
0.399
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
25196608WSDLE5
Adder
10.55
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
10.955
970193AG2-126 GEN
Solar/Wind Harmer
12.34
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
0
962771AG1-126 GEN
Solar/Wind Harmer
32.057
970153AG2-106 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.122
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.901
942481AE2-261 GEN
Solar/Wind Harmer
24.006
957381AF2-032 GEN
Solar/Wind Harmer
1.818
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.664
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.862
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.832
270004AE1-209 GEN
Solar/Wind Harmer
1.692
965091AG1-374 GEN
Solar/Wind Harmer
23.422
959611AF2-252 GEN
Solar/Wind Harmer
2.602
970825AG2-519 GEN
Solar/Wind Harmer
5.878
946031AF1-268 GEN
Solar/Wind Harmer
7.4
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
965931AG1-462 GEN
Solar/Wind Harmer
19.72
971087AG2-675 GEN
Solar/Wind Harmer
4.124
3147123OTTER R
Solar/Wind Harmer
0.087
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.257
970191AG2-125 GEN
Solar/Wind Harmer
1.979
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
970571AG2-364 GEN
Solar/Wind Harmer
15.299
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.443
959091AF2-200 GEN
Solar/Wind Harmer
15.232
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
274850MENDOTA H;RU
Solar/Wind Harmer
0.088
946671AF1-331 GEN
Solar/Wind Harmer
0.811
276868AE1-113 GEN
Solar/Wind Harmer
1.52
274879MINONK ;1U
Solar/Wind Harmer
0.317
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
19.478
274862TOP CROP ;2U
Solar/Wind Harmer
1.021
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.409
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
970707AG2-453 GEN
Solar/Wind Harmer
24.521
274887GEN-1.85
Solar/Wind Harmer
0.195
276843GEN-1.7
Solar/Wind Harmer
0.242
276806AD2-047 C O1
Solar/Wind Harmer
4.245
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.228
274745AC1-111 GEN9
Adder
6.042
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
3.264
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
270055AF2-134 C O1
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.239
270031AE2-169
Solar/Wind Harmer
4.216
270599AE1-208 GEN
Solar/Wind Harmer
7.027
964611AG1-324 GEN
Solar/Wind Harmer
0.575
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
938861AE1-114 GEN
Solar/Wind Harmer
4.333
247621Y3-024
Adder
0.264
270201AC2-176 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
15.232
971343AH1-151 GEN
Solar/Wind Harmer
15.232
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.378
962691AG1-118 GEN
Solar/Wind Harmer
22.733
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
958481AF2-142 GEN
Solar/Wind Harmer
11.337
276897AD1-100 C
Solar/Wind Harmer
18.8
276893AG1-478 C
Solar/Wind Harmer
0.501
274674JOLIET 9 ;6U
Adder
16.589
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.437
276776AD2-060 GEN
Solar/Wind Harmer
0.799
958011AF2-095 GEN
Solar/Wind Harmer
10.787
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
970941AG2-585 GEN
Solar/Wind Harmer
2.017
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.25 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2283.58
MW Contribution:
4.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.374
24729305KEY G2
50/50
0.367
24729205KEY G1
50/50
0.366
247620Y3-023
50/50
0.467
960851AF2-376 GEN
50/50
2.095
24643105BUCHANAN
50/50
0.01
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.855
944231AF1-091 GEN
Solar/Wind Harmer
16.139
944541AF1-119 GEN
Solar/Wind Harmer
0.427
960971AF2-388 GEN
Solar/Wind Harmer
3.752
970349AG2-230 GEN
Solar/Wind Harmer
8.78
961051AF2-396 GEN
Solar/Wind Harmer
11.674
961051AF2-396 GEN
Solar/Wind Harmer
7.782
270031AE2-169
Solar/Wind Harmer
3.104
270599AE1-208 GEN
Solar/Wind Harmer
5.173
965681AG1-436 GEN
Solar/Wind Harmer
6.963
965791AG1-447 GEN
Solar/Wind Harmer
5.106
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.41
247621Y3-024
Adder
0.183
274805UNIV PK N;1U
Adder
3.801
274808UNIV PK N;4U
Adder
3.776
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.365
274771LINCOLN ;2U
Adder
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
0.304
276776AD2-060 GEN
Solar/Wind Harmer
0.555
958011AF2-095 GEN
Solar/Wind Harmer
7.498
970941AG2-585 GEN
Solar/Wind Harmer
2.864
276897AD1-100 C
Solar/Wind Harmer
12.887
274674JOLIET 9 ;6U
Adder
11.348
276893AG1-478 C
Solar/Wind Harmer
0.343
970291AG2-192 GEN
Solar/Wind Harmer
0.666
970291AG2-192 GEN
Solar/Wind Harmer
0.308
971613AH1-306 GEN
Solar/Wind Harmer
2.442
958481AF2-142 GEN
Solar/Wind Harmer
7.57
274695ROCKY RD ;2P
Adder
8.016
274693ROCKY RD ;1P
Adder
7.937
274697ROCKY RD ;3P
Adder
2.178
274696ROCKY RD ;4P
Adder
8.205
274683WAUKEGAN ;8U
Adder
15.145
274683WAUKEGAN ;8U
Adder
12.766
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
14.951
958491AF2-143 GEN
Solar/Wind Harmer
7.476
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.768
971343AH1-151 GEN
Solar/Wind Harmer
9.768
972235AH1-702 GEN1
Adder
1.755
972236AH1-702 GEN2
Adder
1.526
938861AE1-114 GEN
Solar/Wind Harmer
2.722
274764LEE CO EC;5U
Adder
6.396
274765LEE CO EC;6U
Adder
6.396
274762LEE CO EC;3U
Adder
6.381
274763LEE CO EC;4U
Adder
6.321
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.763
276645AC1-214 GEN1
Solar/Wind Harmer
0.185
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.533
942111AE2-223 GEN
Solar/Wind Harmer
1.513
960611AF2-352 GEN
Solar/Wind Harmer
1.525
926881AC1-175 GEN
Solar/Wind Harmer
0
24727005RPMNG1
50/50
3.317
960861AF2-377 GEN
50/50
2.406
24727205RPMNG3
50/50
3.298
24729505KEY G4
50/50
6.847
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.792
959331AF2-224 GEN
Solar/Wind Harmer
9.676
963791AG1-232 GEN
Solar/Wind Harmer
12.035
970031AG2-029 GEN
Solar/Wind Harmer
4.587
965041AG1-368 GEN
Solar/Wind Harmer
8.443
270071AF1-092 GEN
Solar/Wind Harmer
14.566
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.602
971771AH1-392 GEN
Solar/Wind Harmer
5.907
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.922
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.13
274775LINCOLN ;6U
Adder
6.365
274776LINCOLN ;7U
Adder
6.365
274777LINCOLN ;8U
Adder
6.365
972037AH1-567 GEN1
Adder
0.137
274827FISK ;RP
Adder
5.808
274800UNIV PARK;3U
Adder
4.357
274801UNIV PARK;4U
Adder
4.357
960591AF2-350 GEN
Solar/Wind Harmer
5.207
972228AH1-698 GEN2
Adder
2.756
972227AH1-698 GEN1
Adder
1.941
274687WILL CNTY;4U
Adder
20.685
274687WILL CNTY;4U
Adder
20.685
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.662
274675JOLIET 29;7U
Adder
21.853
274728ELWOOD EC;5P
Adder
12.11
274731ELWOOD EC;2P
Adder
12.11
274733ELWOOD EC;3P
Adder
12.11
274735ELWOOD EC;4P
Adder
12.11
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.974
970833AG2-524 GEN
Solar/Wind Harmer
5.628
970833AG2-524 GEN
Solar/Wind Harmer
3.752
971611AH1-305 GEN
Solar/Wind Harmer
3.031
274744AC1-111 GEN8
Adder
4.068
274746AC1-111 G10
Adder
4.068
970073AG2-061 GEN
Solar/Wind Harmer
1.661
247536S-71 GEN
Solar/Wind Harmer
0.199
971411AH1-196 GEN
Solar/Wind Harmer
7.376
971675AH1-338 GEN
Solar/Wind Harmer
1.916
276861AD2-134 GEN
Solar/Wind Harmer
0.088
276863AD2-134 GEN
Solar/Wind Harmer
0.088
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.768
274823ROCKFORD ;21
Adder
13.596
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
926823AC1-168 GEN
Solar/Wind Harmer
0.821
970169AG2-114 GEN
Solar/Wind Harmer
4.823
971681AH1-341 GEN
Solar/Wind Harmer
7.736
971549AH1-272 GEN
Solar/Wind Harmer
9.898
972267AH1-718 GEN
Adder
2.828
276741O09 GEN1
Solar/Wind Harmer
0.167
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.157
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.889
946321AF1-296 GEN
Solar/Wind Harmer
2.577
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.976
270543AE2-219 C
Solar/Wind Harmer
3.137
276668AB2-070 GEN1
Solar/Wind Harmer
0.17
276848AB2-070 GEN3
Solar/Wind Harmer
0.169
276849AB2-070 GEN2
Solar/Wind Harmer
0.17
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.928
944221AF1-090 GEN
Solar/Wind Harmer
2.312
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.609
270223U2-072_GEN1
Solar/Wind Helper
0.876
270224U2-072_GEN2
Solar/Wind Helper
0.876
270227U2-072_GEN3
Solar/Wind Helper
0.876
270228U2-072_GEN4
Solar/Wind Helper
0.876
270231U2-072_GEN5
Solar/Wind Helper
0.876
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
1.968
945641AF1-229 GEN
Solar/Wind Helper
0.94
24727105RPMNG2
50/50
3.318
970583AG2-370 GEN
50/50
2.814
270142AC1-141 CT1_
50/50
2.029
24642205MAYFLWER
50/50
0.031
944961AF1-161 GEN
50/50
2.395
962601AG1-109 GEN
50/50
2.395
965021AG1-366 GEN
Solar/Wind Harmer
4.607
270043AE2-236 GEN
Solar/Wind Harmer
5.241
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.981
24695305TIMB G C
Solar/Wind Harmer
0.532
945111AF1-176 GEN
Solar/Wind Harmer
4.853
971347AH1-153 GEN
Solar/Wind Harmer
2.927
270505AE1-170 C O1
Solar/Wind Harmer
6.132
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.345
274752CRETE EC ;2U
Adder
6.312
274753CRETE EC ;3U
Adder
6.312
274724RIVER EC ;11
Adder
13.515
274814UNIV PK N;0U
Adder
3.826
274807UNIV PK N;3U
Adder
3.817
274811UNIV PK N;7U
Adder
3.792
274772LINCOLN ;3U
Adder
6.365
274803UNIV PARK;6U
Adder
4.369
274826FISK ;BP
Adder
8.195
972038AH1-567 GEN2
Adder
0.273
274887GEN-1.85
Solar/Wind Harmer
0.135
276843GEN-1.7
Solar/Wind Harmer
0.168
276806AD2-047 C O1
Solar/Wind Harmer
2.951
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.153
970707AG2-453 GEN
Solar/Wind Harmer
16.903
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.852
274729ELWOOD EC;1P
Adder
12.11
274730ELWOOD EC;6P
Adder
12.11
274734ELWOOD EC;8P
Adder
12.11
274736ELWOOD EC;9P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.564
946031AF1-268 GEN
Solar/Wind Harmer
4.838
943121AE2-341 GEN
Solar/Wind Harmer
8.518
943591AF1-030 GEN
Solar/Wind Harmer
5.665
270004AE1-209 GEN
Solar/Wind Harmer
1.101
274862TOP CROP ;2U
Solar/Wind Harmer
0.681
970825AG2-519 GEN
Solar/Wind Harmer
3.795
274682WAUKEGAN ;7U
Adder
12.933
276868AE1-113 GEN
Solar/Wind Harmer
0.991
274879MINONK ;1U
Solar/Wind Harmer
0.207
946671AF1-331 GEN
Solar/Wind Harmer
0.524
274855GSG-6 ;RU
Solar/Wind Harmer
0.179
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.895
959091AF2-200 GEN
Solar/Wind Harmer
9.768
970571AG2-364 GEN
Solar/Wind Harmer
9.675
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.381
274767LEE CO EC;8U
Adder
6.306
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.157
965091AG1-374 GEN
Solar/Wind Harmer
13.726
965931AG1-462 GEN
Solar/Wind Harmer
11.666
971087AG2-675 GEN
Solar/Wind Harmer
2.44
959611AF2-252 GEN
Solar/Wind Harmer
1.525
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.998
957381AF2-032 GEN
Solar/Wind Harmer
0.932
942481AE2-261 GEN
Solar/Wind Harmer
12.255
970193AG2-126 GEN
Solar/Wind Harmer
5.956
24728705AND G3
Adder
4.39
24728505AND G1
Adder
2.099
246938BC-WTG3
Solar/Wind Helper
11.083
942871AE2-306 GEN
Solar/Wind Helper
0.445
270284AF1-227 GEN1
Solar/Wind Helper
1.893
270287AF1-227 GEN3
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.334
270541AE2-072 C
Solar/Wind Helper
0.943
970521AG2-332 GEN
50/50
10.906
24639705ELKHART HY
50/50
0.151
270143AC1-141 CT2_
50/50
2.029
965011AG1-365 GEN
Solar/Wind Harmer
13.822
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.876
958861AF2-177 GEN
Solar/Wind Harmer
2.694
945111AF1-176 GEN
Solar/Wind Harmer
10.683
957891AF2-083 GEN
Solar/Wind Harmer
9.802
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3
970373AG2-245 GEN
Solar/Wind Harmer
11.243
274751CRETE EC ;1U
Adder
6.312
274754CRETE EC ;4U
Adder
6.312
274723RIVER EC ;12
Adder
13.681
274812UNIV PK N;8U
Adder
3.792
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.365
274774LINCOLN ;5U
Adder
6.365
274802UNIV PARK;5U
Adder
4.369
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.75
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.662
274674JOLIET 9 ;6U
Adder
11.348
274732ELWOOD EC;7P
Adder
12.11
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.364
270594AE1-207 GEN
Solar/Wind Harmer
5.699
270032AE2-172
Solar/Wind Harmer
3.392
270005AE1-210 C O1
Solar/Wind Harmer
1.101
274745AC1-111 GEN9
Adder
4.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.82
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.788
274682WAUKEGAN ;7U
Adder
12.933
274828WAUKEGAN ;BP
Adder
7.939
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.731
939401AE1-172 GEN
Solar/Wind Harmer
3.718
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.578
971997AH1-543 GEN
Solar/Wind Harmer
2.59
957471AF2-041 GEN
Solar/Wind Harmer
14.651
959081AF2-199 GEN
Solar/Wind Harmer
4.884
971067AG2-660 GEN
Solar/Wind Harmer
1.628
274822ROCKFORD ;11
Adder
13.696
276903AD2-071 C
Solar/Wind Harmer
5.426
970819AG2-516 GEN
Solar/Wind Harmer
5.809
970569AG2-363 GEN
Solar/Wind Harmer
14.512
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.381
274766LEE CO EC;7U
Adder
6.306
276708O09 GEN2
Solar/Wind Harmer
0.167
276646AC1-214 GEN2
Solar/Wind Harmer
0.185
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.519
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.287
963741AG1-226 GEN
Solar/Wind Harmer
10.473
276621W2-048 GEN
Solar/Wind Harmer
0.213
965911AG1-460 GEN
Solar/Wind Harmer
0.82
24728605AND G2
Adder
2.099
970773AG2-487 GEN
Solar/Wind Harmer
0.63
246936BC-WTG1
Solar/Wind Helper
10.897
270317AD1-130_GEN
Solar/Wind Helper
4.143
270485AE1-090_GEN
Solar/Wind Helper
0.326
270391AF1-285 GEN3
Solar/Wind Helper
0.593
270578AF1-285 GEN2
Solar/Wind Helper
0.593
270286AF1-227 GEN2
Solar/Wind Helper
0.694
960841AF2-375 GEN
Solar/Wind Helper
1.179
970883AG2-550 GEN
Solar/Wind Harmer
4.481
970885AG2-551 GEN
Solar/Wind Harmer
1.494
970241AG2-163 GEN
Solar/Wind Harmer
2.581
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.044
276838X2-022 GEN2
Solar/Wind Harmer
0.239
276916AD2-100_GEN
Solar/Wind Harmer
8.532
276911AD2-131_GEN
Solar/Wind Harmer
0.562
945391AF1-204 GEN
Solar/Wind Harmer
4.219
970623AG2-406 GEN
Solar/Wind Harmer
0.656
971587AH1-292 GEN
Solar/Wind Harmer
2.468
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.897
270462AD2-086
Solar/Wind Helper
3.747
247522W1-056 GEN
Solar/Wind Helper
1.177
253378AE2-206_GEN
Solar/Wind Helper
0.715
270349AD2-093_GEN
Solar/Wind Helper
0.857
270471AD2-092_GEN
Solar/Wind Helper
0.857
241960AC2-195 GEN
Solar/Wind Helper
0.697
990497J1323
External Queue
1.5952997207641602
990792J1392
External Queue
5.487830638885498
LAGNLTFEXP_LAGN->PJM
CLTF
5.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.51
TVALTFEXP_TVA->PJM
CLTF
2.319
CBM West 1LTFEXP_CBM-W1->PJM
CBM
70.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.933
MECLTFEXP_MEC->PJM
CLTF
9.784
SIGELTFEXP_SIGE->PJM
CLTF
0.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.835
NYPJM->LTFIMP_NY
CLTF
1.264
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
AG2-052LTFEXP_AG2-052->PJM
LTF
0.172
AH1-155LTFEXP_AH1-155->PJM
LTF
0.258

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7443_05DUMONT 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7443_05DUMONT 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.31 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3447.28
MW Contribution:
11.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
3.387
970521AG2-332 GEN
50/50
16.25
24639705ELKHART HY
50/50
0.226
24727005RPMNG1
50/50
1.31
270143AC1-141 CT2_
50/50
3.129
965011AG1-365 GEN
Solar/Wind Harmer
18.284
965651AG1-433 GEN
Solar/Wind Harmer
9.79
958861AF2-177 GEN
Solar/Wind Harmer
19
945371AF1-202 GEN
Solar/Wind Harmer
11.421
270024AE2-089 GEN
Solar/Wind Harmer
6.78
270005AE1-210 C O1
Solar/Wind Harmer
7.652
270216AD2-079_GEN
Solar/Wind Harmer
0.82
970825AG2-519 GEN
Solar/Wind Harmer
2.798
945111AF1-176 GEN
Solar/Wind Harmer
23.522
957891AF2-083 GEN
Solar/Wind Harmer
19.527
270449AD2-020 GEN
Solar/Wind Harmer
3.602
943021AE2-325 GEN
Solar/Wind Harmer
4.68
270594AE1-207 GEN
Solar/Wind Harmer
17.413
270032AE2-172
Solar/Wind Harmer
5.963
942081AE2-220 GEN
Solar/Wind Harmer
8.015
270209AC1-174_GEN
Solar/Wind Harmer
5.1
270437AC2-090 C
Solar/Wind Harmer
6.995
270239V3-007_GEN1
Solar/Wind Harmer
2.156
965421AG1-410 GEN
Solar/Wind Harmer
37.54
24441205WTRV SLR C
Solar/Wind Harmer
0.168
276903AD2-071 C
Solar/Wind Harmer
12.221
270258AD1-119 GEN
Solar/Wind Harmer
2.454
246936BC-WTG1
Solar/Wind Harmer
4.655
270489AE1-102 GEN1
Solar/Wind Harmer
1.547
970373AG2-245 GEN
Solar/Wind Harmer
24.25
270055AF2-134 C O1
Solar/Wind Harmer
3.437
274751CRETE EC ;1U
Adder
5.519
274754CRETE EC ;4U
Adder
5.519
274723RIVER EC ;12
Adder
20.108
958381AF2-132 GEN
Solar/Wind Harmer
10.14
964861AG1-349 GEN
Solar/Wind Harmer
8.772
971917AH1-482 GEN
Solar/Wind Harmer
10.12
274812UNIV PK N;8U
Adder
5.575
274802UNIV PARK;5U
Adder
6.408
972207SS24-0001
Solar/Wind Harmer
24.135
274773LINCOLN ;4U
Adder
6.788
274774LINCOLN ;5U
Adder
6.788
940581AE2-045 GEN
Solar/Wind Harmer
11.134
971605AH1-302 GEN
Solar/Wind Harmer
9.52
274676JOLIET 29;8U
Adder
33.167
941551AE2-152 GEN
Solar/Wind Harmer
4.9
274674JOLIET 9 ;6U
Adder
16.609
274732ELWOOD EC;7P
Adder
17.731
274871GR RIDGE ;2U
Solar/Wind Harmer
8.237
274847GR RIDGE ;BU
Solar/Wind Harmer
5.417
274745AC1-111 GEN9
Adder
5.943
276694AA1-018 GEN2
Solar/Wind Harmer
6.698
276691AA1-018 GEN1
Solar/Wind Harmer
0.801
274861TOP CROP ;1U
Solar/Wind Harmer
6.429
274682WAUKEGAN ;7U
Adder
18.924
274828WAUKEGAN ;BP
Adder
11.616
24791305MDL-5G
Solar/Wind Harmer
2.531
276805AD2-038 GEN
Solar/Wind Harmer
5.38
274822ROCKFORD ;11
Adder
20.064
274761LEE CO EC;2U
Adder
9.359
274766LEE CO EC;7U
Adder
9.249
24728605AND G2
Adder
3.739
23906502RICHG2&3
Adder
0.873
970091AG2-072 GEN
Adder
47.041
23920202STRYCT
Adder
0.787
270286AF1-227 GEN2
Solar/Wind Helper
0.43
270520AE2-214 GEN
Solar/Wind Helper
1.202
24729505KEY G4
50/50
13.446
24727205RPMNG3
50/50
1.303
24653605MOTTVILLE
50/50
0.005
24641605TWIN BRNCH
50/50
0.023
270144AC1-141 ST1_
50/50
2.763
270071AF1-092 GEN
Solar/Wind Harmer
28.587
959331AF2-224 GEN
Solar/Wind Harmer
18.284
958711AF2-162 GEN
Solar/Wind Harmer
1.812
970031AG2-029 GEN
Solar/Wind Harmer
41.433
945581AF1-223 GEN
Solar/Wind Harmer
7.424
963791AG1-232 GEN
Solar/Wind Harmer
21.919
965041AG1-368 GEN
Solar/Wind Harmer
15.73
247521TR3_G114
Solar/Wind Harmer
4.891
270191TR4_S_V150
Solar/Wind Harmer
4.365
965051AG1-369 GEN
Solar/Wind Harmer
7.267
961761AG1-017 GEN
Solar/Wind Harmer
0.569
964611AG1-324 GEN
Solar/Wind Harmer
5.187
971771AH1-392 GEN
Solar/Wind Harmer
11.667
944161AF1-084 GEN
Solar/Wind Harmer
2.814
970289AG2-191 GEN
Solar/Wind Harmer
2.41
270526AF1-158 GEN
Solar/Wind Harmer
5.674
270404AC1-167 GEN
Solar/Wind Harmer
1.327
247536S-71 GEN
Solar/Wind Harmer
4.946
960681AF2-359 GEN
Solar/Wind Harmer
4.549
971549AH1-272 GEN
Solar/Wind Harmer
22.038
957201AF2-014 GEN
Solar/Wind Harmer
5.398
270435AC2-044 GEN
Solar/Wind Harmer
2.38
270007AE1-245 C
Solar/Wind Harmer
6.335
270543AE2-219 C
Solar/Wind Harmer
11.387
958391AF2-133 GEN
Solar/Wind Harmer
10.051
959141AF2-205 GEN
Solar/Wind Harmer
6.656
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.513
274800UNIV PARK;3U
Adder
6.385
274801UNIV PARK;4U
Adder
6.385
274775LINCOLN ;6U
Adder
6.788
274776LINCOLN ;7U
Adder
6.788
274777LINCOLN ;8U
Adder
6.788
960591AF2-350 GEN
Solar/Wind Harmer
10.932
972228AH1-698 GEN2
Adder
4.033
972227AH1-698 GEN1
Adder
2.84
274687WILL CNTY;4U
Adder
30.287
274687WILL CNTY;4U
Adder
30.287
274675JOLIET 29;7U
Adder
33.168
274675JOLIET 29;7U
Adder
31.983
276893AG1-478 C
Solar/Wind Harmer
0.594
274728ELWOOD EC;5P
Adder
17.731
274731ELWOOD EC;2P
Adder
17.73
274733ELWOOD EC;3P
Adder
17.73
274735ELWOOD EC;4P
Adder
17.73
970833AG2-524 GEN
Solar/Wind Harmer
9.36
970833AG2-524 GEN
Solar/Wind Harmer
4.354
274744AC1-111 GEN8
Adder
5.943
274746AC1-111 G10
Adder
5.943
946581AF1-322 GEN
Solar/Wind Harmer
10.743
24691005MDL-2G C
Solar/Wind Harmer
3.882
274823ROCKFORD ;21
Adder
19.918
972267AH1-718 GEN
Adder
4.15
970073AG2-061 GEN
Solar/Wind Harmer
0.945
970583AG2-370 GEN
50/50
3.658
24727105RPMNG2
50/50
1.311
270142AC1-141 CT1_
50/50
3.129
944961AF1-161 GEN
50/50
3.736
962601AG1-109 GEN
50/50
3.736
24642205MAYFLWER
50/50
0.047
944531AF1-118 GEN
Solar/Wind Harmer
70.411
270043AE2-236 GEN
Solar/Wind Harmer
10.84
965021AG1-366 GEN
Solar/Wind Harmer
4.252
270063AE2-323 C
Solar/Wind Harmer
3.377
24695305TIMB G C
Solar/Wind Harmer
4.71
270004AE1-209 GEN
Solar/Wind Harmer
7.652
247643Z2-116 C
Solar/Wind Harmer
0.094
970825AG2-519 GEN
Solar/Wind Harmer
7.511
962031AG1-047 GEN
Solar/Wind Harmer
4.022
957741AF2-068 GEN
Solar/Wind Harmer
19.956
946031AF1-268 GEN
Solar/Wind Harmer
11.028
945111AF1-176 GEN
Solar/Wind Harmer
7.455
270505AE1-170 C O1
Solar/Wind Harmer
19.458
965461AG1-414 GEN
Solar/Wind Harmer
2.876
970289AG2-191 GEN
Solar/Wind Harmer
0.973
971347AH1-153 GEN
Solar/Wind Harmer
6.284
247642Z2-115 C
Solar/Wind Harmer
0.08
24379505HDWTR1G C
Solar/Wind Harmer
9.909
270240V3-007_GEN2
Solar/Wind Harmer
7.753
24441505OLIV SLR
Solar/Wind Harmer
0.166
270044AE2-322 C
Solar/Wind Harmer
1.609
246938BC-WTG3
Solar/Wind Harmer
4.736
270491AE1-102 GEN2
Solar/Wind Harmer
1.547
958091AF2-103 GEN
Solar/Wind Harmer
0.19
972231SS25-0005
Solar/Wind Harmer
10.716
972181SS23-001
Solar/Wind Harmer
6.698
274752CRETE EC ;2U
Adder
5.519
274753CRETE EC ;3U
Adder
5.519
274724RIVER EC ;11
Adder
19.865
964401AG1-302 GEN
Solar/Wind Harmer
10.14
274814UNIV PK N;0U
Adder
5.624
274807UNIV PK N;3U
Adder
5.612
274811UNIV PK N;7U
Adder
5.575
276164X3-005 C
Solar/Wind Harmer
0.78
274803UNIV PARK;6U
Adder
6.408
274826FISK ;BP
Adder
12.013
972038AH1-567 GEN2
Adder
0.4
274772LINCOLN ;3U
Adder
6.788
274887GEN-1.85
Solar/Wind Harmer
5.824
276772AC2-154 GEN
Solar/Wind Harmer
3.051
276843GEN-1.7
Solar/Wind Harmer
0.627
276806AD2-047 C O1
Solar/Wind Harmer
11.694
972259AH1-714 GEN
Adder
20.661
274676JOLIET 29;8U
Adder
31.983
939351AE1-166 GEN
Solar/Wind Harmer
6.408
970707AG2-453 GEN
Solar/Wind Harmer
30.235
274730ELWOOD EC;6P
Adder
17.731
274734ELWOOD EC;8P
Adder
17.731
274736ELWOOD EC;9P
Adder
17.731
274729ELWOOD EC;1P
Adder
17.73
943121AE2-341 GEN
Solar/Wind Harmer
15.942
943591AF1-030 GEN
Solar/Wind Harmer
10.628
274862TOP CROP ;2U
Solar/Wind Harmer
5.367
274682WAUKEGAN ;7U
Adder
18.924
24690905MDL-1G C
Solar/Wind Harmer
8.429
970781AG2-491 GEN
Solar/Wind Harmer
10.499
274760LEE CO EC;1U
Adder
9.359
274767LEE CO EC;8U
Adder
9.249
24728705AND G3
Adder
7.821
24728505AND G1
Adder
3.739
23906402RICHG1
Adder
0.88
23906502RICHG2&3
Adder
0.873
270284AF1-227 GEN1
Solar/Wind Helper
1.173
270287AF1-227 GEN3
Solar/Wind Helper
0.43
24729405KEY G3
50/50
0.734
24729305KEY G2
50/50
0.722
24729205KEY G1
50/50
0.718
247620Y3-023
50/50
0.693
960851AF2-376 GEN
50/50
3.281
24643105BUCHANAN
50/50
0.016
247621Y3-024
50/50
0.324
944541AF1-119 GEN
Solar/Wind Harmer
7.5
960971AF2-388 GEN
Solar/Wind Harmer
19.579
942221AE2-234 GEN
Solar/Wind Harmer
5.649
944231AF1-091 GEN
Solar/Wind Harmer
27.774
270031AE2-169
Solar/Wind Harmer
11.918
270599AE1-208 GEN
Solar/Wind Harmer
11.918
270246TR4_N_V150
Solar/Wind Harmer
1.238
270247TR4_N_V136
Solar/Wind Harmer
1.238
270201AC2-176 GEN
Solar/Wind Harmer
6.838
964611AG1-324 GEN
Solar/Wind Harmer
0.696
961051AF2-396 GEN
Solar/Wind Harmer
20.595
961051AF2-396 GEN
Solar/Wind Harmer
9.579
970291AG2-192 GEN
Solar/Wind Harmer
1.649
970291AG2-192 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
18.853
926881AC1-175 GEN
Solar/Wind Harmer
6.995
24725505WLD G2 C
Solar/Wind Harmer
4.822
24699105WLD G1 C
Solar/Wind Harmer
4.765
965681AG1-436 GEN
Solar/Wind Harmer
15.047
965791AG1-447 GEN
Solar/Wind Harmer
7.699
246937BC-WTG2
Solar/Wind Harmer
4.655
247607V1-011 GEN
Solar/Wind Harmer
4.641
270383AD1-128 GEN
Solar/Wind Harmer
7.127
970883AG2-550 GEN
Solar/Wind Harmer
11.387
970885AG2-551 GEN
Solar/Wind Harmer
2.648
270535AF1-215 GEN1
Solar/Wind Harmer
5.155
270536AF1-215 GEN2
Solar/Wind Harmer
5.155
274805UNIV PK N;1U
Adder
5.587
274808UNIV PK N;4U
Adder
5.551
274770LINCOLN ;1U
Adder
6.788
274771LINCOLN ;2U
Adder
6.788
274888KELLY CRK;1U
Solar/Wind Harmer
6.451
276776AD2-060 GEN
Solar/Wind Harmer
0.458
958011AF2-095 GEN
Solar/Wind Harmer
15.741
970941AG2-585 GEN
Solar/Wind Harmer
6.012
276897AD1-100 C
Solar/Wind Harmer
50.193
276893AG1-478 C
Solar/Wind Harmer
0.473
274674JOLIET 9 ;6U
Adder
16.609
945421AF1-207 GEN
Solar/Wind Harmer
14.979
957841AF2-078 GEN
Solar/Wind Harmer
6.448
958481AF2-142 GEN
Solar/Wind Harmer
15.922
942801AE2-298 GEN
Solar/Wind Harmer
1.595
274695ROCKY RD ;2P
Adder
11.722
274693ROCKY RD ;1P
Adder
11.606
274697ROCKY RD ;3P
Adder
3.184
274696ROCKY RD ;4P
Adder
11.998
274683WAUKEGAN ;8U
Adder
22.161
274683WAUKEGAN ;8U
Adder
18.68
270180AB1-006 GEN1
Solar/Wind Harmer
7.551
24697605MDL-3G C
Solar/Wind Harmer
3.87
24755605MDL-5G
Solar/Wind Harmer
2.531
24697905MDL-4G C
Solar/Wind Harmer
2.409
270181AB1-006 GEN2
Solar/Wind Harmer
0.751
972235AH1-702 GEN1
Adder
2.571
972236AH1-702 GEN2
Adder
2.236
274764LEE CO EC;5U
Adder
9.381
274765LEE CO EC;6U
Adder
9.381
274762LEE CO EC;3U
Adder
9.359
274763LEE CO EC;4U
Adder
9.271
24728805RICHG1
Adder
3.096
24728905RICHG2
Adder
3.096
270349AD2-093_GEN
Solar/Wind Helper
1.08
270471AD2-092_GEN
Solar/Wind Helper
1.08
270054AF2-122 C O1
Solar/Wind Helper
0.78
946101AF1-275 GEN
Solar/Wind Helper
0.301
958491AF2-143 GEN
Solar/Wind Harmer
6.092
990497J1323
External Queue
1.9189454317092896
LAGNLTFEXP_LAGN->PJM
CLTF
8.355
TVALTFEXP_TVA->PJM
CLTF
3.311
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.395
MECLTFEXP_MEC->PJM
CLTF
14.451
SIGELTFEXP_SIGE->PJM
CLTF
0.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.342
NYPJM->LTFIMP_NY
CLTF
1.987
LGEELTFEXP_LGEE->PJM
CLTF
3.249
WECLTFEXP_WEC->PJM
CLTF
3.892
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.513
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.387

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7442_05SORENS 765_K2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7442_05SORENS 765_K2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.22 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3444.48
MW Contribution:
11.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729505KEY G4
50/50
13.443
24727205RPMNG3
50/50
1.301
24653605MOTTVILLE
50/50
0.005
24641605TWIN BRNCH
50/50
0.023
270144AC1-141 ST1_
50/50
2.734
270071AF1-092 GEN
Solar/Wind Harmer
28.591
959331AF2-224 GEN
Solar/Wind Harmer
18.262
958711AF2-162 GEN
Solar/Wind Harmer
1.812
970031AG2-029 GEN
Solar/Wind Harmer
41.334
945581AF1-223 GEN
Solar/Wind Harmer
7.425
963791AG1-232 GEN
Solar/Wind Harmer
21.902
965041AG1-368 GEN
Solar/Wind Harmer
15.709
247521TR3_G114
Solar/Wind Harmer
4.885
270191TR4_S_V150
Solar/Wind Harmer
4.359
965051AG1-369 GEN
Solar/Wind Harmer
7.258
961761AG1-017 GEN
Solar/Wind Harmer
0.57
964611AG1-324 GEN
Solar/Wind Harmer
5.189
971771AH1-392 GEN
Solar/Wind Harmer
11.607
970289AG2-191 GEN
Solar/Wind Harmer
2.414
944161AF1-084 GEN
Solar/Wind Harmer
2.786
270526AF1-158 GEN
Solar/Wind Harmer
5.65
247536S-71 GEN
Solar/Wind Harmer
4.948
270404AC1-167 GEN
Solar/Wind Harmer
1.324
960681AF2-359 GEN
Solar/Wind Harmer
4.537
957201AF2-014 GEN
Solar/Wind Harmer
5.389
270435AC2-044 GEN
Solar/Wind Harmer
2.376
971549AH1-272 GEN
Solar/Wind Harmer
21.886
270007AE1-245 C
Solar/Wind Harmer
6.325
270543AE2-219 C
Solar/Wind Harmer
11.391
958391AF2-133 GEN
Solar/Wind Harmer
10.055
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.547
959141AF2-205 GEN
Solar/Wind Harmer
6.661
274775LINCOLN ;6U
Adder
6.826
274776LINCOLN ;7U
Adder
6.826
274777LINCOLN ;8U
Adder
6.826
274800UNIV PARK;3U
Adder
6.411
274801UNIV PARK;4U
Adder
6.411
960591AF2-350 GEN
Solar/Wind Harmer
10.977
972228AH1-698 GEN2
Adder
4.051
972227AH1-698 GEN1
Adder
2.852
274687WILL CNTY;4U
Adder
30.416
274687WILL CNTY;4U
Adder
30.416
274675JOLIET 29;7U
Adder
33.312
274675JOLIET 29;7U
Adder
32.122
276893AG1-478 C
Solar/Wind Harmer
0.596
274728ELWOOD EC;5P
Adder
17.809
274731ELWOOD EC;2P
Adder
17.808
274733ELWOOD EC;3P
Adder
17.808
274735ELWOOD EC;4P
Adder
17.808
970833AG2-524 GEN
Solar/Wind Harmer
9.404
970833AG2-524 GEN
Solar/Wind Harmer
4.374
274744AC1-111 GEN8
Adder
5.972
274746AC1-111 G10
Adder
5.972
970073AG2-061 GEN
Solar/Wind Harmer
2.45
946581AF1-322 GEN
Solar/Wind Harmer
10.767
24691005MDL-2G C
Solar/Wind Harmer
3.891
274823ROCKFORD ;21
Adder
20.012
972267AH1-718 GEN
Adder
4.17
960861AF2-377 GEN
50/50
3.382
970521AG2-332 GEN
50/50
16.165
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.308
270143AC1-141 CT2_
50/50
3.096
965011AG1-365 GEN
Solar/Wind Harmer
18.262
965651AG1-433 GEN
Solar/Wind Harmer
9.789
958861AF2-177 GEN
Solar/Wind Harmer
18.999
945371AF1-202 GEN
Solar/Wind Harmer
11.422
270024AE2-089 GEN
Solar/Wind Harmer
6.779
270005AE1-210 C O1
Solar/Wind Harmer
7.655
270216AD2-079_GEN
Solar/Wind Harmer
0.816
970825AG2-519 GEN
Solar/Wind Harmer
2.799
945111AF1-176 GEN
Solar/Wind Harmer
23.333
957891AF2-083 GEN
Solar/Wind Harmer
19.366
270594AE1-207 GEN
Solar/Wind Harmer
17.44
270032AE2-172
Solar/Wind Harmer
5.973
270449AD2-020 GEN
Solar/Wind Harmer
3.568
943021AE2-325 GEN
Solar/Wind Harmer
4.637
942081AE2-220 GEN
Solar/Wind Harmer
8.019
270209AC1-174_GEN
Solar/Wind Harmer
5.103
270437AC2-090 C
Solar/Wind Harmer
6.998
270239V3-007_GEN1
Solar/Wind Harmer
2.158
965421AG1-410 GEN
Solar/Wind Harmer
37.481
24441205WTRV SLR C
Solar/Wind Harmer
0.166
276903AD2-071 C
Solar/Wind Harmer
12.241
270258AD1-119 GEN
Solar/Wind Harmer
2.449
246936BC-WTG1
Solar/Wind Harmer
4.648
270489AE1-102 GEN1
Solar/Wind Harmer
1.545
970373AG2-245 GEN
Solar/Wind Harmer
24.219
270055AF2-134 C O1
Solar/Wind Harmer
3.435
274751CRETE EC ;1U
Adder
5.533
274754CRETE EC ;4U
Adder
5.533
274723RIVER EC ;12
Adder
20.174
958381AF2-132 GEN
Solar/Wind Harmer
10.14
274812UNIV PK N;8U
Adder
5.593
964861AG1-349 GEN
Solar/Wind Harmer
8.773
971917AH1-482 GEN
Solar/Wind Harmer
10.122
274802UNIV PARK;5U
Adder
6.433
972207SS24-0001
Solar/Wind Harmer
24.27
274773LINCOLN ;4U
Adder
6.826
274774LINCOLN ;5U
Adder
6.826
940581AE2-045 GEN
Solar/Wind Harmer
11.146
971605AH1-302 GEN
Solar/Wind Harmer
9.53
274676JOLIET 29;8U
Adder
33.312
941551AE2-152 GEN
Solar/Wind Harmer
4.923
274674JOLIET 9 ;6U
Adder
16.683
274732ELWOOD EC;7P
Adder
17.809
274871GR RIDGE ;2U
Solar/Wind Harmer
8.276
274847GR RIDGE ;BU
Solar/Wind Harmer
5.442
274745AC1-111 GEN9
Adder
5.972
276694AA1-018 GEN2
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.804
274861TOP CROP ;1U
Solar/Wind Harmer
6.456
274682WAUKEGAN ;7U
Adder
19.011
274828WAUKEGAN ;BP
Adder
11.67
276805AD2-038 GEN
Solar/Wind Harmer
5.403
24791305MDL-5G
Solar/Wind Harmer
2.537
274822ROCKFORD ;11
Adder
20.159
274761LEE CO EC;2U
Adder
9.403
274766LEE CO EC;7U
Adder
9.292
24728605AND G2
Adder
3.747
23906502RICHG2&3
Adder
0.869
970091AG2-072 GEN
Adder
47.294
23920202STRYCT
Adder
0.781
270286AF1-227 GEN2
Solar/Wind Helper
0.431
270520AE2-214 GEN
Solar/Wind Helper
1.202
970583AG2-370 GEN
50/50
3.653
24727105RPMNG2
50/50
1.309
270142AC1-141 CT1_
50/50
3.096
24642205MAYFLWER
50/50
0.047
944961AF1-161 GEN
50/50
3.701
962601AG1-109 GEN
50/50
3.701
944531AF1-118 GEN
Solar/Wind Harmer
70.391
270043AE2-236 GEN
Solar/Wind Harmer
10.829
965021AG1-366 GEN
Solar/Wind Harmer
4.247
270063AE2-323 C
Solar/Wind Harmer
3.366
24695305TIMB G C
Solar/Wind Harmer
4.703
270004AE1-209 GEN
Solar/Wind Harmer
7.655
247643Z2-116 C
Solar/Wind Harmer
0.094
970825AG2-519 GEN
Solar/Wind Harmer
7.516
962031AG1-047 GEN
Solar/Wind Harmer
4.023
957741AF2-068 GEN
Solar/Wind Harmer
19.961
946031AF1-268 GEN
Solar/Wind Harmer
11.033
945111AF1-176 GEN
Solar/Wind Harmer
7.395
270505AE1-170 C O1
Solar/Wind Harmer
19.285
965461AG1-414 GEN
Solar/Wind Harmer
2.881
970289AG2-191 GEN
Solar/Wind Harmer
0.975
971347AH1-153 GEN
Solar/Wind Harmer
6.301
247642Z2-115 C
Solar/Wind Harmer
0.08
24379505HDWTR1G C
Solar/Wind Harmer
9.914
270240V3-007_GEN2
Solar/Wind Harmer
7.757
24441505OLIV SLR
Solar/Wind Harmer
0.165
270044AE2-322 C
Solar/Wind Harmer
1.606
246938BC-WTG3
Solar/Wind Harmer
4.728
270491AE1-102 GEN2
Solar/Wind Harmer
1.545
958091AF2-103 GEN
Solar/Wind Harmer
0.189
972231SS25-0005
Solar/Wind Harmer
10.742
972181SS23-001
Solar/Wind Harmer
6.714
274752CRETE EC ;2U
Adder
5.533
274753CRETE EC ;3U
Adder
5.533
274724RIVER EC ;11
Adder
19.931
964401AG1-302 GEN
Solar/Wind Harmer
10.14
274814UNIV PK N;0U
Adder
5.641
274807UNIV PK N;3U
Adder
5.629
274811UNIV PK N;7U
Adder
5.593
276164X3-005 C
Solar/Wind Harmer
0.783
274803UNIV PARK;6U
Adder
6.433
274826FISK ;BP
Adder
12.06
274772LINCOLN ;3U
Adder
6.826
972038AH1-567 GEN2
Adder
0.401
274887GEN-1.85
Solar/Wind Harmer
5.848
276772AC2-154 GEN
Solar/Wind Harmer
3.063
276843GEN-1.7
Solar/Wind Harmer
0.629
276806AD2-047 C O1
Solar/Wind Harmer
11.743
972259AH1-714 GEN
Adder
20.761
274676JOLIET 29;8U
Adder
32.122
939351AE1-166 GEN
Solar/Wind Harmer
6.438
970707AG2-453 GEN
Solar/Wind Harmer
30.394
274730ELWOOD EC;6P
Adder
17.809
274734ELWOOD EC;8P
Adder
17.809
274736ELWOOD EC;9P
Adder
17.809
274729ELWOOD EC;1P
Adder
17.808
943121AE2-341 GEN
Solar/Wind Harmer
16.022
943591AF1-030 GEN
Solar/Wind Harmer
10.681
274862TOP CROP ;2U
Solar/Wind Harmer
5.39
274682WAUKEGAN ;7U
Adder
19.011
24690905MDL-1G C
Solar/Wind Harmer
8.448
274760LEE CO EC;1U
Adder
9.403
274767LEE CO EC;8U
Adder
9.292
24728705AND G3
Adder
7.836
24728505AND G1
Adder
3.747
23906402RICHG1
Adder
0.876
23906502RICHG2&3
Adder
0.869
270284AF1-227 GEN1
Solar/Wind Helper
1.175
270287AF1-227 GEN3
Solar/Wind Helper
0.431
970781AG2-491 GEN
Solar/Wind Harmer
0.942
24729405KEY G3
50/50
0.734
24729305KEY G2
50/50
0.721
24729205KEY G1
50/50
0.718
247620Y3-023
50/50
0.69
960851AF2-376 GEN
50/50
3.277
24643105BUCHANAN
50/50
0.016
247621Y3-024
50/50
0.324
944541AF1-119 GEN
Solar/Wind Harmer
7.499
960971AF2-388 GEN
Solar/Wind Harmer
19.578
942221AE2-234 GEN
Solar/Wind Harmer
5.648
944231AF1-091 GEN
Solar/Wind Harmer
27.723
270031AE2-169
Solar/Wind Harmer
11.922
270599AE1-208 GEN
Solar/Wind Harmer
11.922
270246TR4_N_V150
Solar/Wind Harmer
1.236
270247TR4_N_V136
Solar/Wind Harmer
1.236
270201AC2-176 GEN
Solar/Wind Harmer
6.839
964611AG1-324 GEN
Solar/Wind Harmer
0.696
961051AF2-396 GEN
Solar/Wind Harmer
20.413
961051AF2-396 GEN
Solar/Wind Harmer
9.495
970291AG2-192 GEN
Solar/Wind Harmer
1.652
970291AG2-192 GEN
Solar/Wind Harmer
0.532
970349AG2-230 GEN
Solar/Wind Harmer
18.902
926881AC1-175 GEN
Solar/Wind Harmer
6.998
24725505WLD G2 C
Solar/Wind Harmer
4.829
24699105WLD G1 C
Solar/Wind Harmer
4.772
965681AG1-436 GEN
Solar/Wind Harmer
15.008
965791AG1-447 GEN
Solar/Wind Harmer
7.678
246937BC-WTG2
Solar/Wind Harmer
4.648
247607V1-011 GEN
Solar/Wind Harmer
4.633
270383AD1-128 GEN
Solar/Wind Harmer
7.132
970883AG2-550 GEN
Solar/Wind Harmer
11.391
970885AG2-551 GEN
Solar/Wind Harmer
2.649
270535AF1-215 GEN1
Solar/Wind Harmer
5.152
270536AF1-215 GEN2
Solar/Wind Harmer
5.152
274805UNIV PK N;1U
Adder
5.605
274808UNIV PK N;4U
Adder
5.568
274770LINCOLN ;1U
Adder
6.826
274771LINCOLN ;2U
Adder
6.826
274888KELLY CRK;1U
Solar/Wind Harmer
6.478
276776AD2-060 GEN
Solar/Wind Harmer
0.46
958011AF2-095 GEN
Solar/Wind Harmer
15.807
970941AG2-585 GEN
Solar/Wind Harmer
6.037
276897AD1-100 C
Solar/Wind Harmer
50.428
276893AG1-478 C
Solar/Wind Harmer
0.475
274674JOLIET 9 ;6U
Adder
16.683
945421AF1-207 GEN
Solar/Wind Harmer
15.011
957841AF2-078 GEN
Solar/Wind Harmer
6.462
958481AF2-142 GEN
Solar/Wind Harmer
15.989
274696ROCKY RD ;4P
Adder
12.055
274695ROCKY RD ;2P
Adder
11.777
274693ROCKY RD ;1P
Adder
11.662
274697ROCKY RD ;3P
Adder
3.199
274683WAUKEGAN ;8U
Adder
22.263
274683WAUKEGAN ;8U
Adder
18.767
958491AF2-143 GEN
Solar/Wind Harmer
15.803
270180AB1-006 GEN1
Solar/Wind Harmer
7.568
24697605MDL-3G C
Solar/Wind Harmer
3.879
24755605MDL-5G
Solar/Wind Harmer
2.537
24697905MDL-4G C
Solar/Wind Harmer
2.415
270181AB1-006 GEN2
Solar/Wind Harmer
0.753
972235AH1-702 GEN1
Adder
2.583
972236AH1-702 GEN2
Adder
2.246
274764LEE CO EC;5U
Adder
9.425
274765LEE CO EC;6U
Adder
9.425
274762LEE CO EC;3U
Adder
9.403
274763LEE CO EC;4U
Adder
9.314
24728805RICHG1
Adder
3.1
24728905RICHG2
Adder
3.1
270349AD2-093_GEN
Solar/Wind Helper
1.081
270471AD2-092_GEN
Solar/Wind Helper
1.081
270054AF2-122 C O1
Solar/Wind Helper
0.78
946101AF1-275 GEN
Solar/Wind Helper
0.301
990497J1323
External Queue
1.9028279781341553
LAGNLTFEXP_LAGN->PJM
CLTF
8.402
TVALTFEXP_TVA->PJM
CLTF
3.331
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.333
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.471
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.688
NYPJM->LTFIMP_NY
CLTF
1.989
LGEELTFEXP_LGEE->PJM
CLTF
3.263
WECLTFEXP_WEC->PJM
CLTF
3.91
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7444_05DUMONT 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7444_05DUMONT 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.06 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3439.41
MW Contribution:
11.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
3.392
970521AG2-332 GEN
50/50
16.268
24639705ELKHART HY
50/50
0.226
24727005RPMNG1
50/50
1.312
270143AC1-141 CT2_
50/50
3.115
965011AG1-365 GEN
Solar/Wind Harmer
18.309
965651AG1-433 GEN
Solar/Wind Harmer
9.804
958861AF2-177 GEN
Solar/Wind Harmer
19.027
945371AF1-202 GEN
Solar/Wind Harmer
11.437
270024AE2-089 GEN
Solar/Wind Harmer
6.789
270005AE1-210 C O1
Solar/Wind Harmer
7.662
270216AD2-079_GEN
Solar/Wind Harmer
0.823
970825AG2-519 GEN
Solar/Wind Harmer
2.801
945111AF1-176 GEN
Solar/Wind Harmer
23.483
957891AF2-083 GEN
Solar/Wind Harmer
19.496
270594AE1-207 GEN
Solar/Wind Harmer
17.423
270032AE2-172
Solar/Wind Harmer
5.967
270449AD2-020 GEN
Solar/Wind Harmer
3.59
943021AE2-325 GEN
Solar/Wind Harmer
4.666
942081AE2-220 GEN
Solar/Wind Harmer
8.026
270209AC1-174_GEN
Solar/Wind Harmer
5.107
24729505KEY G4
50/50
13.466
24727205RPMNG3
50/50
1.305
24653605MOTTVILLE
50/50
0.005
24641605TWIN BRNCH
50/50
0.023
270144AC1-141 ST1_
50/50
2.751
270071AF1-092 GEN
Solar/Wind Harmer
28.619
970583AG2-370 GEN
50/50
3.663
24727105RPMNG2
50/50
1.313
270142AC1-141 CT1_
50/50
3.115
24642205MAYFLWER
50/50
0.047
944961AF1-161 GEN
50/50
3.724
962601AG1-109 GEN
50/50
3.724
944531AF1-118 GEN
Solar/Wind Harmer
70.518
270043AE2-236 GEN
Solar/Wind Harmer
10.858
965021AG1-366 GEN
Solar/Wind Harmer
4.258
270063AE2-323 C
Solar/Wind Harmer
3.386
24695305TIMB G C
Solar/Wind Harmer
4.717
270004AE1-209 GEN
Solar/Wind Harmer
7.662
247643Z2-116 C
Solar/Wind Harmer
0.094
970825AG2-519 GEN
Solar/Wind Harmer
7.521
962031AG1-047 GEN
Solar/Wind Harmer
4.028
957741AF2-068 GEN
Solar/Wind Harmer
19.982
946031AF1-268 GEN
Solar/Wind Harmer
11.042
945111AF1-176 GEN
Solar/Wind Harmer
7.443
270505AE1-170 C O1
Solar/Wind Harmer
19.413
971347AH1-153 GEN
Solar/Wind Harmer
6.431
965461AG1-414 GEN
Solar/Wind Harmer
2.877
970289AG2-191 GEN
Solar/Wind Harmer
0.974
247642Z2-115 C
Solar/Wind Harmer
0.08
24379505HDWTR1G C
Solar/Wind Harmer
9.923
270240V3-007_GEN2
Solar/Wind Harmer
7.763
959331AF2-224 GEN
Solar/Wind Harmer
18.309
958711AF2-162 GEN
Solar/Wind Harmer
1.815
970031AG2-029 GEN
Solar/Wind Harmer
41.465
945581AF1-223 GEN
Solar/Wind Harmer
7.435
963791AG1-232 GEN
Solar/Wind Harmer
21.949
965041AG1-368 GEN
Solar/Wind Harmer
15.752
247521TR3_G114
Solar/Wind Harmer
4.899
270191TR4_S_V150
Solar/Wind Harmer
4.371
965051AG1-369 GEN
Solar/Wind Harmer
7.278
961761AG1-017 GEN
Solar/Wind Harmer
0.57
964611AG1-324 GEN
Solar/Wind Harmer
5.194
971771AH1-392 GEN
Solar/Wind Harmer
11.707
970289AG2-191 GEN
Solar/Wind Harmer
2.411
944161AF1-084 GEN
Solar/Wind Harmer
2.803
270526AF1-158 GEN
Solar/Wind Harmer
5.698
270404AC1-167 GEN
Solar/Wind Harmer
1.328
247536S-71 GEN
Solar/Wind Harmer
4.953
960681AF2-359 GEN
Solar/Wind Harmer
4.577
971549AH1-272 GEN
Solar/Wind Harmer
22.073
957201AF2-014 GEN
Solar/Wind Harmer
5.406
270435AC2-044 GEN
Solar/Wind Harmer
2.384
270007AE1-245 C
Solar/Wind Harmer
6.344
270543AE2-219 C
Solar/Wind Harmer
11.402
958391AF2-133 GEN
Solar/Wind Harmer
10.08
959141AF2-205 GEN
Solar/Wind Harmer
6.674
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.539
274800UNIV PARK;3U
Adder
6.404
274801UNIV PARK;4U
Adder
6.404
960591AF2-350 GEN
Solar/Wind Harmer
10.961
274775LINCOLN ;6U
Adder
6.795
274776LINCOLN ;7U
Adder
6.795
274777LINCOLN ;8U
Adder
6.795
972228AH1-698 GEN2
Adder
4.043
972227AH1-698 GEN1
Adder
2.846
274687WILL CNTY;4U
Adder
30.363
274687WILL CNTY;4U
Adder
30.363
274675JOLIET 29;7U
Adder
33.246
274675JOLIET 29;7U
Adder
32.058
276893AG1-478 C
Solar/Wind Harmer
0.595
274728ELWOOD EC;5P
Adder
17.772
274731ELWOOD EC;2P
Adder
17.771
274733ELWOOD EC;3P
Adder
17.771
274735ELWOOD EC;4P
Adder
17.771
970833AG2-524 GEN
Solar/Wind Harmer
9.378
970833AG2-524 GEN
Solar/Wind Harmer
4.362
274744AC1-111 GEN8
Adder
5.954
274746AC1-111 G10
Adder
5.954
970073AG2-061 GEN
Solar/Wind Harmer
2.445
946581AF1-322 GEN
Solar/Wind Harmer
10.756
24691005MDL-2G C
Solar/Wind Harmer
3.887
274823ROCKFORD ;21
Adder
19.955
972267AH1-718 GEN
Adder
4.158
24441505OLIV SLR
Solar/Wind Harmer
0.167
270044AE2-322 C
Solar/Wind Harmer
1.611
246938BC-WTG3
Solar/Wind Harmer
4.743
270491AE1-102 GEN2
Solar/Wind Harmer
1.55
958091AF2-103 GEN
Solar/Wind Harmer
0.19
972231SS25-0005
Solar/Wind Harmer
10.76
972181SS23-001
Solar/Wind Harmer
6.725
274752CRETE EC ;2U
Adder
5.542
274753CRETE EC ;3U
Adder
5.542
274724RIVER EC ;11
Adder
19.952
964401AG1-302 GEN
Solar/Wind Harmer
10.173
274814UNIV PK N;0U
Adder
5.643
274807UNIV PK N;3U
Adder
5.631
274811UNIV PK N;7U
Adder
5.594
276164X3-005 C
Solar/Wind Harmer
0.783
274803UNIV PARK;6U
Adder
6.428
274826FISK ;BP
Adder
12.049
972038AH1-567 GEN2
Adder
0.401
274887GEN-1.85
Solar/Wind Harmer
5.84
276772AC2-154 GEN
Solar/Wind Harmer
3.059
276843GEN-1.7
Solar/Wind Harmer
0.628
276806AD2-047 C O1
Solar/Wind Harmer
11.726
274772LINCOLN ;3U
Adder
6.795
972259AH1-714 GEN
Adder
20.698
274676JOLIET 29;8U
Adder
32.058
939351AE1-166 GEN
Solar/Wind Harmer
6.421
970707AG2-453 GEN
Solar/Wind Harmer
30.273
274730ELWOOD EC;6P
Adder
17.772
274734ELWOOD EC;8P
Adder
17.772
274736ELWOOD EC;9P
Adder
17.772
274729ELWOOD EC;1P
Adder
17.771
943121AE2-341 GEN
Solar/Wind Harmer
15.967
943591AF1-030 GEN
Solar/Wind Harmer
10.645
274862TOP CROP ;2U
Solar/Wind Harmer
5.381
274682WAUKEGAN ;7U
Adder
18.961
24690905MDL-1G C
Solar/Wind Harmer
8.44
274760LEE CO EC;1U
Adder
9.376
274767LEE CO EC;8U
Adder
9.265
24728705AND G3
Adder
7.828
24728505AND G1
Adder
3.743
23906402RICHG1
Adder
0.88
23906502RICHG2&3
Adder
0.873
270284AF1-227 GEN1
Solar/Wind Helper
1.171
270287AF1-227 GEN3
Solar/Wind Helper
0.429
270437AC2-090 C
Solar/Wind Harmer
7.004
270239V3-007_GEN1
Solar/Wind Harmer
2.159
965421AG1-410 GEN
Solar/Wind Harmer
37.596
24441205WTRV SLR C
Solar/Wind Harmer
0.167
276903AD2-071 C
Solar/Wind Harmer
12.228
270258AD1-119 GEN
Solar/Wind Harmer
2.457
246936BC-WTG1
Solar/Wind Harmer
4.662
270489AE1-102 GEN1
Solar/Wind Harmer
1.55
970373AG2-245 GEN
Solar/Wind Harmer
24.361
270055AF2-134 C O1
Solar/Wind Harmer
3.45
274751CRETE EC ;1U
Adder
5.542
274754CRETE EC ;4U
Adder
5.542
274723RIVER EC ;12
Adder
20.195
958381AF2-132 GEN
Solar/Wind Harmer
10.173
964861AG1-349 GEN
Solar/Wind Harmer
8.8
971917AH1-482 GEN
Solar/Wind Harmer
10.153
274812UNIV PK N;8U
Adder
5.594
274802UNIV PARK;5U
Adder
6.428
972207SS24-0001
Solar/Wind Harmer
24.158
274773LINCOLN ;4U
Adder
6.795
274774LINCOLN ;5U
Adder
6.795
940581AE2-045 GEN
Solar/Wind Harmer
11.159
971605AH1-302 GEN
Solar/Wind Harmer
9.542
274676JOLIET 29;8U
Adder
33.245
941551AE2-152 GEN
Solar/Wind Harmer
4.91
274674JOLIET 9 ;6U
Adder
16.648
274732ELWOOD EC;7P
Adder
17.772
274871GR RIDGE ;2U
Solar/Wind Harmer
8.252
274847GR RIDGE ;BU
Solar/Wind Harmer
5.426
274745AC1-111 GEN9
Adder
5.954
276694AA1-018 GEN2
Solar/Wind Harmer
6.714
276691AA1-018 GEN1
Solar/Wind Harmer
0.803
274861TOP CROP ;1U
Solar/Wind Harmer
6.444
274682WAUKEGAN ;7U
Adder
18.961
274828WAUKEGAN ;BP
Adder
11.639
276805AD2-038 GEN
Solar/Wind Harmer
5.392
24791305MDL-5G
Solar/Wind Harmer
2.534
274822ROCKFORD ;11
Adder
20.1
274761LEE CO EC;2U
Adder
9.376
274766LEE CO EC;7U
Adder
9.265
24728605AND G2
Adder
3.743
23906502RICHG2&3
Adder
0.873
970091AG2-072 GEN
Adder
47.024
23920202STRYCT
Adder
0.786
270286AF1-227 GEN2
Solar/Wind Helper
0.429
270520AE2-214 GEN
Solar/Wind Helper
1.2
24729405KEY G3
50/50
0.735
24729305KEY G2
50/50
0.723
24729205KEY G1
50/50
0.719
247620Y3-023
50/50
0.695
960851AF2-376 GEN
50/50
3.286
24643105BUCHANAN
50/50
0.016
247621Y3-024
50/50
0.325
944541AF1-119 GEN
Solar/Wind Harmer
7.511
960971AF2-388 GEN
Solar/Wind Harmer
19.608
942221AE2-234 GEN
Solar/Wind Harmer
5.657
944231AF1-091 GEN
Solar/Wind Harmer
27.808
270031AE2-169
Solar/Wind Harmer
11.933
270599AE1-208 GEN
Solar/Wind Harmer
11.933
270246TR4_N_V150
Solar/Wind Harmer
1.239
270247TR4_N_V136
Solar/Wind Harmer
1.239
270201AC2-176 GEN
Solar/Wind Harmer
6.846
964611AG1-324 GEN
Solar/Wind Harmer
0.697
961051AF2-396 GEN
Solar/Wind Harmer
20.542
961051AF2-396 GEN
Solar/Wind Harmer
9.554
970349AG2-230 GEN
Solar/Wind Harmer
19.294
970291AG2-192 GEN
Solar/Wind Harmer
1.649
970291AG2-192 GEN
Solar/Wind Harmer
0.531
926881AC1-175 GEN
Solar/Wind Harmer
7.004
24725505WLD G2 C
Solar/Wind Harmer
4.825
24699105WLD G1 C
Solar/Wind Harmer
4.769
965681AG1-436 GEN
Solar/Wind Harmer
15.141
965791AG1-447 GEN
Solar/Wind Harmer
7.747
246937BC-WTG2
Solar/Wind Harmer
4.662
247607V1-011 GEN
Solar/Wind Harmer
4.647
270383AD1-128 GEN
Solar/Wind Harmer
7.136
270535AF1-215 GEN1
Solar/Wind Harmer
5.176
270536AF1-215 GEN2
Solar/Wind Harmer
5.176
970883AG2-550 GEN
Solar/Wind Harmer
11.402
970885AG2-551 GEN
Solar/Wind Harmer
2.652
274805UNIV PK N;1U
Adder
5.606
274808UNIV PK N;4U
Adder
5.57
274888KELLY CRK;1U
Solar/Wind Harmer
6.468
276776AD2-060 GEN
Solar/Wind Harmer
0.459
958011AF2-095 GEN
Solar/Wind Harmer
15.784
274770LINCOLN ;1U
Adder
6.795
274771LINCOLN ;2U
Adder
6.795
970941AG2-585 GEN
Solar/Wind Harmer
6.029
276897AD1-100 C
Solar/Wind Harmer
50.292
276893AG1-478 C
Solar/Wind Harmer
0.474
274674JOLIET 9 ;6U
Adder
16.648
945421AF1-207 GEN
Solar/Wind Harmer
14.999
957841AF2-078 GEN
Solar/Wind Harmer
6.457
958481AF2-142 GEN
Solar/Wind Harmer
15.961
942801AE2-298 GEN
Solar/Wind Harmer
1.597
274695ROCKY RD ;2P
Adder
11.743
274693ROCKY RD ;1P
Adder
11.627
274697ROCKY RD ;3P
Adder
3.19
274696ROCKY RD ;4P
Adder
12.02
274683WAUKEGAN ;8U
Adder
22.204
274683WAUKEGAN ;8U
Adder
18.717
958491AF2-143 GEN
Solar/Wind Harmer
15.773
24697605MDL-3G C
Solar/Wind Harmer
3.875
24755605MDL-5G
Solar/Wind Harmer
2.534
24697905MDL-4G C
Solar/Wind Harmer
2.412
972235AH1-702 GEN1
Adder
2.576
972236AH1-702 GEN2
Adder
2.24
274764LEE CO EC;5U
Adder
9.398
274765LEE CO EC;6U
Adder
9.398
274762LEE CO EC;3U
Adder
9.376
274763LEE CO EC;4U
Adder
9.287
24728805RICHG1
Adder
3.1
24728905RICHG2
Adder
3.1
270349AD2-093_GEN
Solar/Wind Helper
1.079
270471AD2-092_GEN
Solar/Wind Helper
1.079
270054AF2-122 C O1
Solar/Wind Helper
0.779
946101AF1-275 GEN
Solar/Wind Helper
0.3
270180AB1-006 GEN1
Solar/Wind Harmer
6.97
270181AB1-006 GEN2
Solar/Wind Harmer
0.693
990497J1323
External Queue
1.920957326889038
LAGNLTFEXP_LAGN->PJM
CLTF
8.372
TVALTFEXP_TVA->PJM
CLTF
3.318
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.42
MECLTFEXP_MEC->PJM
CLTF
14.477
SIGELTFEXP_SIGE->PJM
CLTF
0.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.462
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
3.252
WECLTFEXP_WEC->PJM
CLTF
3.899
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.509
AG2-052LTFEXP_AG2-052->PJM
LTF
0.26
AH1-155LTFEXP_AH1-155->PJM
LTF
0.39

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.01 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3190.2
MW Contribution:
7.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.734
24729305KEY G2
50/50
0.721
24729205KEY G1
50/50
0.718
247620Y3-023
50/50
0.69
960851AF2-376 GEN
50/50
3.277
24643105BUCHANAN
50/50
0.016
247621Y3-024
50/50
0.324
944541AF1-119 GEN
Solar/Wind Harmer
0.834
960971AF2-388 GEN
Solar/Wind Harmer
7.331
960861AF2-377 GEN
50/50
3.382
970521AG2-332 GEN
50/50
16.165
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.308
270143AC1-141 CT2_
50/50
3.096
965011AG1-365 GEN
Solar/Wind Harmer
12.741
965651AG1-433 GEN
Solar/Wind Harmer
3.666
958861AF2-177 GEN
Solar/Wind Harmer
5.255
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.002
270005AE1-210 C O1
Solar/Wind Harmer
2.117
970825AG2-519 GEN
Solar/Wind Harmer
3.304
945111AF1-176 GEN
Solar/Wind Harmer
16.279
957891AF2-083 GEN
Solar/Wind Harmer
15.012
270594AE1-207 GEN
Solar/Wind Harmer
10.034
270032AE2-172
Solar/Wind Harmer
5.973
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.637
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.415
965421AG1-410 GEN
Solar/Wind Harmer
26.149
276903AD2-071 C
Solar/Wind Harmer
9.536
246936BC-WTG1
Solar/Wind Harmer
0.334
270489AE1-102 GEN1
Solar/Wind Harmer
1.078
970373AG2-245 GEN
Solar/Wind Harmer
16.897
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
9.326
274754CRETE EC ;4U
Adder
9.326
274723RIVER EC ;12
Adder
20.174
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
5.593
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
10.122
274802UNIV PARK;5U
Adder
6.433
274773LINCOLN ;4U
Adder
9.292
274774LINCOLN ;5U
Adder
9.292
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.53
274676JOLIET 29;8U
Adder
33.312
941551AE2-152 GEN
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
16.683
274732ELWOOD EC;7P
Adder
17.809
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.972
24729505KEY G4
50/50
13.443
24727205RPMNG3
50/50
1.301
24653605MOTTVILLE
50/50
0.005
24641605TWIN BRNCH
50/50
0.023
270144AC1-141 ST1_
50/50
2.734
270071AF1-092 GEN
Solar/Wind Harmer
25.488
959331AF2-224 GEN
Solar/Wind Harmer
8.919
970031AG2-029 GEN
Solar/Wind Harmer
6.248
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
15.281
965041AG1-368 GEN
Solar/Wind Harmer
10.96
971609AH1-304 GEN
Solar/Wind Harmer
1.667
247521TR3_G114
Solar/Wind Harmer
0.367
965051AG1-369 GEN
Solar/Wind Harmer
5.063
964611AG1-324 GEN
Solar/Wind Harmer
3.62
971771AH1-392 GEN
Solar/Wind Harmer
8.998
970289AG2-191 GEN
Solar/Wind Harmer
1.684
270526AF1-158 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.341
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.05
971549AH1-272 GEN
Solar/Wind Harmer
17.043
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.563
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.547
959141AF2-205 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
9.292
274776LINCOLN ;7U
Adder
9.292
274777LINCOLN ;8U
Adder
9.292
274800UNIV PARK;3U
Adder
6.411
274801UNIV PARK;4U
Adder
6.411
960591AF2-350 GEN
Solar/Wind Harmer
7.658
972228AH1-698 GEN2
Adder
4.051
972227AH1-698 GEN1
Adder
2.852
971611AH1-305 GEN
Solar/Wind Harmer
4.539
274687WILL CNTY;4U
Adder
30.416
274687WILL CNTY;4U
Adder
30.416
274675JOLIET 29;7U
Adder
33.312
274675JOLIET 29;7U
Adder
32.122
274728ELWOOD EC;5P
Adder
17.809
274731ELWOOD EC;2P
Adder
17.808
274733ELWOOD EC;3P
Adder
17.808
274735ELWOOD EC;4P
Adder
17.808
970833AG2-524 GEN
Solar/Wind Harmer
8.267
970833AG2-524 GEN
Solar/Wind Harmer
5.511
274744AC1-111 GEN8
Adder
5.972
970583AG2-370 GEN
50/50
3.653
24727105RPMNG2
50/50
1.309
270142AC1-141 CT1_
50/50
3.096
24642205MAYFLWER
50/50
0.047
944961AF1-161 GEN
50/50
3.701
962601AG1-109 GEN
50/50
3.701
944531AF1-118 GEN
Solar/Wind Harmer
62.885
270043AE2-236 GEN
Solar/Wind Harmer
8.814
965021AG1-366 GEN
Solar/Wind Harmer
4.247
270063AE2-323 C
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.832
270004AE1-209 GEN
Solar/Wind Harmer
2.117
970825AG2-519 GEN
Solar/Wind Harmer
7.011
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.926
946031AF1-268 GEN
Solar/Wind Harmer
8.826
945111AF1-176 GEN
Solar/Wind Harmer
7.395
270505AE1-170 C O1
Solar/Wind Harmer
9.418
970289AG2-191 GEN
Solar/Wind Harmer
0.975
971347AH1-153 GEN
Solar/Wind Harmer
4.396
247642Z2-115 C
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.299
270491AE1-102 GEN2
Solar/Wind Harmer
1.078
274752CRETE EC ;2U
Adder
9.326
274753CRETE EC ;3U
Adder
9.326
274724RIVER EC ;11
Adder
19.931
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.641
274807UNIV PK N;3U
Adder
5.629
274811UNIV PK N;7U
Adder
5.593
274803UNIV PARK;6U
Adder
6.433
274826FISK ;BP
Adder
12.06
274772LINCOLN ;3U
Adder
9.292
972038AH1-567 GEN2
Adder
0.401
274887GEN-1.85
Solar/Wind Harmer
0.199
276843GEN-1.7
Solar/Wind Harmer
0.248
276806AD2-047 C O1
Solar/Wind Harmer
4.34
972259AH1-714 GEN
Adder
20.761
274676JOLIET 29;8U
Adder
32.122
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
24.739
942221AE2-234 GEN
Solar/Wind Harmer
4.522
944231AF1-091 GEN
Solar/Wind Harmer
24.786
270031AE2-169
Solar/Wind Harmer
5.613
270599AE1-208 GEN
Solar/Wind Harmer
9.355
270246TR4_N_V150
Solar/Wind Harmer
0.065
270247TR4_N_V136
Solar/Wind Harmer
0.065
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.696
961051AF2-396 GEN
Solar/Wind Harmer
17.945
961051AF2-396 GEN
Solar/Wind Harmer
11.963
971613AH1-306 GEN
Solar/Wind Harmer
4.3
970291AG2-192 GEN
Solar/Wind Harmer
1.152
970291AG2-192 GEN
Solar/Wind Harmer
0.532
970349AG2-230 GEN
Solar/Wind Harmer
13.187
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.54
965681AG1-436 GEN
Solar/Wind Harmer
10.47
965791AG1-447 GEN
Solar/Wind Harmer
7.678
246937BC-WTG2
Solar/Wind Harmer
0.334
247607V1-011 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.947
970885AG2-551 GEN
Solar/Wind Harmer
2.649
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.208
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
19.011
274828WAUKEGAN ;BP
Adder
11.67
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.485
962781AG1-127 GEN
Solar/Wind Harmer
6.953
276882AE2-255 GEN
Solar/Wind Harmer
0.852
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.817
957471AF2-041 GEN
Solar/Wind Harmer
21.562
959081AF2-199 GEN
Solar/Wind Harmer
7.187
971067AG2-660 GEN
Solar/Wind Harmer
2.396
274822ROCKFORD ;11
Adder
20.159
970569AG2-363 GEN
Solar/Wind Harmer
21.445
274746AC1-111 G10
Adder
5.972
970073AG2-061 GEN
Solar/Wind Harmer
2.45
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.958
274863CRW1-WTG
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
17.809
274734ELWOOD EC;8P
Adder
17.809
274736ELWOOD EC;9P
Adder
17.809
274729ELWOOD EC;1P
Adder
17.808
943121AE2-341 GEN
Solar/Wind Harmer
12.495
943591AF1-030 GEN
Solar/Wind Harmer
8.309
274862TOP CROP ;2U
Solar/Wind Harmer
1.004
274682WAUKEGAN ;7U
Adder
19.011
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.342
276868AE1-113 GEN
Solar/Wind Harmer
1.461
274879MINONK ;1U
Solar/Wind Harmer
0.305
946671AF1-331 GEN
Solar/Wind Harmer
0.771
274855GSG-6 ;RU
Solar/Wind Harmer
0.264
274850MENDOTA H;RU
Solar/Wind Harmer
0.084
959091AF2-200 GEN
Solar/Wind Harmer
14.375
970571AG2-364 GEN
Solar/Wind Harmer
14.297
24386205FR-12G C
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.403
274767LEE CO EC;8U
Adder
9.292
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
965091AG1-374 GEN
Solar/Wind Harmer
20.486
959611AF2-252 GEN
Solar/Wind Harmer
2.276
24728705AND G3
Adder
7.836
24728505AND G1
Adder
3.747
965931AG1-462 GEN
Solar/Wind Harmer
17.242
971087AG2-675 GEN
Solar/Wind Harmer
3.606
971993AH1-541 GEN
Solar/Wind Harmer
3.006
970193AG2-126 GEN
Solar/Wind Harmer
9.362
957381AF2-032 GEN
Solar/Wind Harmer
1.409
942481AE2-261 GEN
Solar/Wind Harmer
18.539
23906402RICHG1
Adder
0.876
23906502RICHG2&3
Adder
0.869
270541AE2-072 C
Solar/Wind Harmer
0
958321AF2-126 GEN
Solar/Wind Harmer
0.443
270284AF1-227 GEN1
Solar/Wind Helper
1.175
270287AF1-227 GEN3
Solar/Wind Helper
0.431
970819AG2-516 GEN
Solar/Wind Harmer
8.554
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.403
274766LEE CO EC;7U
Adder
9.292
276646AC1-214 GEN2
Solar/Wind Harmer
0.274
276708O09 GEN2
Solar/Wind Harmer
0.247
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.71
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
3.747
970773AG2-487 GEN
Solar/Wind Harmer
1.202
963741AG1-226 GEN
Solar/Wind Harmer
16.041
276621W2-048 GEN
Solar/Wind Harmer
0.32
965911AG1-460 GEN
Solar/Wind Harmer
1.24
23906502RICHG2&3
Adder
0.869
970091AG2-072 GEN
Adder
47.294
23920202STRYCT
Adder
0.781
241858AF1-205_GEN
Solar/Wind Harmer
1.344
270286AF1-227 GEN2
Solar/Wind Helper
0.431
270520AE2-214 GEN
Solar/Wind Helper
1.202
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
10.852
971675AH1-338 GEN
Solar/Wind Harmer
2.819
276861AD2-134 GEN
Solar/Wind Harmer
0.129
276863AD2-134 GEN
Solar/Wind Harmer
0.129
971171AH1-044 GEN
Solar/Wind Harmer
14.375
274823ROCKFORD ;21
Adder
20.012
970169AG2-114 GEN
Solar/Wind Harmer
7.144
926823AC1-168 GEN
Solar/Wind Harmer
1.213
274856ECOGROVE ;U1
Solar/Wind Harmer
0.166
24386405FR-21G C
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
11.398
972267AH1-718 GEN
Adder
4.17
276741O09 GEN1
Solar/Wind Harmer
0.247
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.282
963841AG1-237 GEN
Solar/Wind Harmer
3.005
274854TWINGROVE;U2
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
3.807
276668AB2-070 GEN1
Solar/Wind Harmer
0.256
276848AB2-070 GEN3
Solar/Wind Harmer
0.255
276849AB2-070 GEN2
Solar/Wind Harmer
0.256
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.516
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.605
274808UNIV PK N;4U
Adder
5.568
274770LINCOLN ;1U
Adder
9.292
274771LINCOLN ;2U
Adder
9.292
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
276776AD2-060 GEN
Solar/Wind Harmer
0.817
958011AF2-095 GEN
Solar/Wind Harmer
11.028
970941AG2-585 GEN
Solar/Wind Harmer
4.212
276897AD1-100 C
Solar/Wind Harmer
18.934
276893AG1-478 C
Solar/Wind Harmer
0.504
274674JOLIET 9 ;6U
Adder
16.683
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
11.155
274696ROCKY RD ;4P
Adder
12.055
274695ROCKY RD ;2P
Adder
11.777
274693ROCKY RD ;1P
Adder
11.662
274697ROCKY RD ;3P
Adder
3.199
274683WAUKEGAN ;8U
Adder
22.263
274683WAUKEGAN ;8U
Adder
18.767
958491AF2-143 GEN
Solar/Wind Harmer
11.026
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
21.97
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.375
971343AH1-151 GEN
Solar/Wind Harmer
14.375
972235AH1-702 GEN1
Adder
2.583
972236AH1-702 GEN2
Adder
2.246
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.805
938861AE1-114 GEN
Solar/Wind Harmer
4.01
274764LEE CO EC;5U
Adder
9.425
274765LEE CO EC;6U
Adder
9.425
274762LEE CO EC;3U
Adder
9.403
274763LEE CO EC;4U
Adder
9.314
276645AC1-214 GEN1
Solar/Wind Harmer
0.274
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.126
942111AE2-223 GEN
Solar/Wind Harmer
2.254
960611AF2-352 GEN
Solar/Wind Harmer
2.276
970241AG2-163 GEN
Solar/Wind Harmer
3.954
276615X2-022 GEN
Solar/Wind Harmer
0.066
276838X2-022 GEN2
Solar/Wind Harmer
0.361
945391AF1-204 GEN
Solar/Wind Harmer
6.631
276916AD2-100_GEN
Solar/Wind Harmer
12.922
276911AD2-131_GEN
Solar/Wind Harmer
0.851
24728805RICHG1
Adder
3.1
24728905RICHG2
Adder
3.1
970621AG2-405 GEN
Solar/Wind Harmer
1.034
971587AH1-292 GEN
Solar/Wind Harmer
3.867
964571AG1-320 GEN
Solar/Wind Harmer
2.864
270349AD2-093_GEN
Solar/Wind Helper
1.081
270471AD2-092_GEN
Solar/Wind Helper
1.081
270054AF2-122 C O1
Solar/Wind Helper
0.78
946101AF1-275 GEN
Solar/Wind Helper
0.301
990497J1323
External Queue
1.9028279781341553
991297J1743
External Queue
13.235071182250977
990792J1392
External Queue
6.545727729797363
LAGNLTFEXP_LAGN->PJM
CLTF
8.402
TVALTFEXP_TVA->PJM
CLTF
3.331
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.333
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.471
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.688
NYPJM->LTFIMP_NY
CLTF
1.989
LGEELTFEXP_LGEE->PJM
CLTF
3.263
WECLTFEXP_WEC->PJM
CLTF
3.91
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.53 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5607.44
MW Contribution:
8.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
13.518
270144AC1-141 ST1_
50/50
4.427
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
18.336
274776LINCOLN ;7U
50/50
18.336
274777LINCOLN ;8U
50/50
18.336
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
14.587
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
27.676
972037AH1-567 GEN1
Adder
0.366
274827FISK ;RP
Adder
15.501
960591AF2-350 GEN
Solar/Wind Harmer
13.932
972228AH1-698 GEN2
Adder
7.394
972227AH1-698 GEN1
Adder
5.206
274800UNIV PARK;3U
Adder
11.637
274801UNIV PARK;4U
Adder
11.637
270142AC1-141 CT1_
50/50
5.013
24642205MAYFLWER
50/50
0.076
274772LINCOLN ;3U
50/50
18.336
944961AF1-161 GEN
50/50
5.942
962601AG1-109 GEN
50/50
5.942
971347AH1-153 GEN
Solar/Wind Harmer
7.766
270043AE2-236 GEN
Solar/Wind Harmer
9.417
270505AE1-170 C O1
Solar/Wind Harmer
15.137
945111AF1-176 GEN
Solar/Wind Harmer
11.613
274724RIVER EC ;11
Adder
35.793
274752CRETE EC ;2U
Adder
16.621
274753CRETE EC ;3U
Adder
16.621
270063AE2-323 C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
10.141
274807UNIV PK N;3U
Adder
10.119
274811UNIV PK N;7U
Adder
10.053
970707AG2-453 GEN
Solar/Wind Harmer
45.738
972259AH1-714 GEN
Adder
38.13
274803UNIV PARK;6U
Adder
11.65
274826FISK ;BP
Adder
21.872
274887GEN-1.85
Solar/Wind Harmer
0.362
276843GEN-1.7
Solar/Wind Harmer
0.45
276806AD2-047 C O1
Solar/Wind Harmer
7.895
972038AH1-567 GEN2
Adder
0.728
939351AE1-166 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
61.966
274676JOLIET 29;8U
Adder
58.599
274729ELWOOD EC;1P
Adder
32.486
274730ELWOOD EC;6P
Adder
32.486
274734ELWOOD EC;8P
Adder
32.486
274736ELWOOD EC;9P
Adder
32.486
943121AE2-341 GEN
Solar/Wind Harmer
22.986
943591AF1-030 GEN
Solar/Wind Harmer
15.286
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.824
274682WAUKEGAN ;7U
Adder
34.771
276868AE1-113 GEN
Solar/Wind Harmer
2.661
274879MINONK ;1U
Solar/Wind Harmer
0.555
946671AF1-331 GEN
Solar/Wind Harmer
1.412
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.154
959091AF2-200 GEN
Solar/Wind Harmer
26.289
970571AG2-364 GEN
Solar/Wind Harmer
25.984
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
17.161
274767LEE CO EC;8U
Adder
16.958
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
12.865
965021AG1-366 GEN
Solar/Wind Harmer
4.261
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.422
24386205FR-12G C
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
37.086
959611AF2-252 GEN
Solar/Wind Harmer
4.121
965931AG1-462 GEN
Solar/Wind Harmer
31.345
971087AG2-675 GEN
Solar/Wind Harmer
6.556
247642Z2-115 C
Solar/Wind Harmer
0.005
971993AH1-541 GEN
Solar/Wind Harmer
5.405
970289AG2-191 GEN
Solar/Wind Harmer
1.271
957381AF2-032 GEN
Solar/Wind Harmer
2.525
942481AE2-261 GEN
Solar/Wind Harmer
33.208
270004AE1-209 GEN
Solar/Wind Harmer
2.315
970193AG2-126 GEN
Solar/Wind Harmer
16.03
970825AG2-519 GEN
Solar/Wind Harmer
7.905
946031AF1-268 GEN
Solar/Wind Harmer
9.859
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.395
24695305TIMB G C
Solar/Wind Harmer
0.837
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
10.702
24728505AND G1
Adder
5.117
246938BC-WTG3
Solar/Wind Harmer
0.29
270491AE1-102 GEN2
Solar/Wind Harmer
1.048
24344105CKG2
50/50
17.278
270143AC1-141 CT2_
50/50
5.013
24639705ELKHART HY
50/50
0.334
274773LINCOLN ;4U
50/50
18.336
274774LINCOLN ;5U
50/50
18.336
970521AG2-332 GEN
50/50
23.772
24307105BERRINSP G
50/50
0.044
957891AF2-083 GEN
Solar/Wind Harmer
23.982
945111AF1-176 GEN
Solar/Wind Harmer
25.563
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
7.444
274723RIVER EC ;12
Adder
36.21
274751CRETE EC ;1U
Adder
16.621
274754CRETE EC ;4U
Adder
16.621
970373AG2-245 GEN
Solar/Wind Harmer
29.476
274812UNIV PK N;8U
Adder
10.053
274802UNIV PARK;5U
Adder
11.65
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
60.769
274674JOLIET 9 ;6U
Adder
30.452
274732ELWOOD EC;7P
Adder
32.486
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
10.963
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
17.697
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
2.197
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
34.771
274828WAUKEGAN ;BP
Adder
21.342
939401AE1-172 GEN
Solar/Wind Harmer
10.03
962781AG1-127 GEN
Solar/Wind Harmer
12.744
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
16.687
276882AE2-255 GEN
Solar/Wind Harmer
1.552
971997AH1-543 GEN
Solar/Wind Harmer
6.973
957471AF2-041 GEN
Solar/Wind Harmer
39.433
959081AF2-199 GEN
Solar/Wind Harmer
13.144
971067AG2-660 GEN
Solar/Wind Harmer
4.381
274822ROCKFORD ;11
Adder
36.841
970819AG2-516 GEN
Solar/Wind Harmer
15.625
970569AG2-363 GEN
Solar/Wind Harmer
38.976
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
17.161
274766LEE CO EC;7U
Adder
16.958
965011AG1-365 GEN
Solar/Wind Harmer
12.784
276708O09 GEN2
Solar/Wind Harmer
0.449
276646AC1-214 GEN2
Solar/Wind Harmer
0.499
965651AG1-433 GEN
Solar/Wind Harmer
3.724
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
17.604
270102X2-052 ST
50/50
3.362
270100X2-052 CT1
50/50
3.107
270101X2-052 CT2
50/50
3.107
24643105BUCHANAN
50/50
0.026
274770LINCOLN ;1U
50/50
18.336
274771LINCOLN ;2U
50/50
18.336
247620Y3-023
50/50
0.993
970349AG2-230 GEN
Solar/Wind Harmer
23.297
965681AG1-436 GEN
Solar/Wind Harmer
18.242
965791AG1-447 GEN
Solar/Wind Harmer
13.377
961051AF2-396 GEN
Solar/Wind Harmer
28.57
961051AF2-396 GEN
Solar/Wind Harmer
19.046
274805UNIV PK N;1U
Adder
10.075
274808UNIV PK N;4U
Adder
10.009
274888KELLY CRK;1U
Solar/Wind Harmer
0.813
276776AD2-060 GEN
Solar/Wind Harmer
1.486
958011AF2-095 GEN
Solar/Wind Harmer
20.062
970941AG2-585 GEN
Solar/Wind Harmer
7.663
276897AD1-100 C
Solar/Wind Harmer
34.688
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
30.452
276893AG1-478 C
Solar/Wind Harmer
0.919
274695ROCKY RD ;2P
Adder
21.58
274693ROCKY RD ;1P
Adder
21.367
274697ROCKY RD ;3P
Adder
5.862
274696ROCKY RD ;4P
Adder
22.088
958481AF2-142 GEN
Solar/Wind Harmer
20.28
274683WAUKEGAN ;8U
Adder
40.715
274683WAUKEGAN ;8U
Adder
34.321
962691AG1-118 GEN
Solar/Wind Harmer
40.277
958491AF2-143 GEN
Solar/Wind Harmer
20.043
276901AD2-066 C O1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
26.289
971343AH1-151 GEN
Solar/Wind Harmer
26.289
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
4.72
972236AH1-702 GEN2
Adder
4.104
938861AE1-114 GEN
Solar/Wind Harmer
7.321
274764LEE CO EC;5U
Adder
17.201
274765LEE CO EC;6U
Adder
17.201
274762LEE CO EC;3U
Adder
17.161
274763LEE CO EC;4U
Adder
16.999
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
2.052
276645AC1-214 GEN1
Solar/Wind Harmer
0.499
944541AF1-119 GEN
Solar/Wind Harmer
0.848
960971AF2-388 GEN
Solar/Wind Harmer
7.448
942111AE2-223 GEN
Solar/Wind Harmer
4.087
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.408
960611AF2-352 GEN
Solar/Wind Harmer
4.121
942221AE2-234 GEN
Solar/Wind Harmer
4.822
970241AG2-163 GEN
Solar/Wind Harmer
6.864
970291AG2-192 GEN
Solar/Wind Harmer
1.502
970291AG2-192 GEN
Solar/Wind Harmer
0.693
276615X2-022 GEN
Solar/Wind Harmer
0.119
276838X2-022 GEN2
Solar/Wind Harmer
0.647
944231AF1-091 GEN
Solar/Wind Harmer
26.413
971613AH1-306 GEN
Solar/Wind Harmer
5.417
270031AE2-169
Solar/Wind Harmer
6.202
270599AE1-208 GEN
Solar/Wind Harmer
10.337
276916AD2-100_GEN
Solar/Wind Harmer
23.132
276911AD2-131_GEN
Solar/Wind Harmer
1.524
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
11.354
964611AG1-324 GEN
Solar/Wind Harmer
0.771
270201AC2-176 GEN
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.065
270247TR4_N_V136
Solar/Wind Harmer
0.065
971587AH1-292 GEN
Solar/Wind Harmer
7.235
247621Y3-024
Adder
0.338
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
8.884
970885AG2-551 GEN
Solar/Wind Harmer
2.961
970623AG2-406 GEN
Solar/Wind Harmer
1.577
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.325
24728805RICHG1
Adder
3.746
24728905RICHG2
Adder
3.746
270349AD2-093_GEN
Solar/Wind Helper
1.553
270471AD2-092_GEN
Solar/Wind Helper
1.553
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
5.383
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
27.848
276621W2-048 GEN
Solar/Wind Harmer
0.575
270594AE1-207 GEN
Solar/Wind Harmer
12.64
270032AE2-172
Solar/Wind Harmer
7.524
965911AG1-460 GEN
Solar/Wind Harmer
2.221
276903AD2-071 C
Solar/Wind Harmer
12.218
270024AE2-089 GEN
Solar/Wind Harmer
0.002
270005AE1-210 C O1
Solar/Wind Harmer
2.315
970825AG2-519 GEN
Solar/Wind Harmer
3.725
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.127
970091AG2-072 GEN
Adder
105.739
24728605AND G2
Adder
5.117
965421AG1-410 GEN
Solar/Wind Harmer
25.535
970773AG2-487 GEN
Solar/Wind Harmer
1.491
246936BC-WTG1
Solar/Wind Harmer
0.325
270489AE1-102 GEN1
Solar/Wind Harmer
1.048
274687WILL CNTY;4U
Adder
55.408
274687WILL CNTY;4U
Adder
55.408
274675JOLIET 29;7U
Adder
60.77
274675JOLIET 29;7U
Adder
58.6
970031AG2-029 GEN
Solar/Wind Harmer
7.48
274728ELWOOD EC;5P
Adder
32.486
274731ELWOOD EC;2P
Adder
32.486
274733ELWOOD EC;3P
Adder
32.486
274735ELWOOD EC;4P
Adder
32.486
970833AG2-524 GEN
Solar/Wind Harmer
15.154
970833AG2-524 GEN
Solar/Wind Harmer
10.103
274744AC1-111 GEN8
Adder
10.963
274746AC1-111 G10
Adder
10.963
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.577
959141AF2-205 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
4.454
971611AH1-305 GEN
Solar/Wind Harmer
7.947
971675AH1-338 GEN
Solar/Wind Harmer
5.16
971411AH1-196 GEN
Solar/Wind Harmer
19.845
276861AD2-134 GEN
Solar/Wind Harmer
0.236
276863AD2-134 GEN
Solar/Wind Harmer
0.236
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
26.289
274823ROCKFORD ;21
Adder
36.573
970169AG2-114 GEN
Solar/Wind Harmer
13.017
274856ECOGROVE ;U1
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
2.21
971549AH1-272 GEN
Solar/Wind Harmer
26.772
971681AH1-341 GEN
Solar/Wind Harmer
20.809
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
8.949
972267AH1-718 GEN
Adder
7.604
276741O09 GEN1
Solar/Wind Harmer
0.449
274877BISHOP HL;1U
Solar/Wind Harmer
0.422
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
13.203
24386405FR-21G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.924
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
5.236
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
15.924
276668AB2-070 GEN1
Solar/Wind Harmer
0.46
276848AB2-070 GEN3
Solar/Wind Harmer
0.458
276849AB2-070 GEN2
Solar/Wind Harmer
0.46
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
2.196
971609AH1-304 GEN
Solar/Wind Harmer
1.842
965041AG1-368 GEN
Solar/Wind Harmer
11.074
944221AF1-090 GEN
Solar/Wind Harmer
6.279
964611AG1-324 GEN
Solar/Wind Harmer
4.011
247521TR3_G114
Solar/Wind Harmer
0.369
965051AG1-369 GEN
Solar/Wind Harmer
5.084
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.379
270543AE2-219 C
Solar/Wind Harmer
6.219
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
12.334
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.021
LAGNLTFEXP_LAGN->PJM
CLTF
14.281
TVALTFEXP_TVA->PJM
CLTF
5.469
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5
CBM West 1LTFEXP_CBM-W1->PJM
CBM
218.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.394
MECLTFEXP_MEC->PJM
CLTF
26.166
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.166
NYPJM->LTFIMP_NY
CLTF
3.371
LGEELTFEXP_LGEE->PJM
CLTF
5.638
WECLTFEXP_WEC->PJM
CLTF
7.136
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.164
AG2-052LTFEXP_AG2-052->PJM
LTF
0.449
AH1-155LTFEXP_AH1-155->PJM
LTF
0.674

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.9 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2870.85
MW Contribution:
7.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726405LAWG1A
50/50
3.341
961171AF2-408 GEN
50/50
9.597
942081AE2-220 GEN
Solar/Wind Harmer
9.75
270209AC1-174_GEN
Solar/Wind Harmer
6.204
270437AC2-090 C
Solar/Wind Harmer
8.509
270239V3-007_GEN1
Solar/Wind Harmer
2.623
270005AE1-210 C O1
Solar/Wind Harmer
6.653
945371AF1-202 GEN
Solar/Wind Harmer
7.542
970825AG2-519 GEN
Solar/Wind Harmer
2.207
958861AF2-177 GEN
Solar/Wind Harmer
11.178
965651AG1-433 GEN
Solar/Wind Harmer
5.422
276903AD2-071 C
Solar/Wind Harmer
9.241
270594AE1-207 GEN
Solar/Wind Harmer
12.304
270032AE2-172
Solar/Wind Harmer
4.214
24728605AND G2
Adder
3.238
270024AE2-089 GEN
Solar/Wind Harmer
3.555
963741AG1-226 GEN
Solar/Wind Harmer
25.12
24385905FR-11G C
Solar/Wind Harmer
4.469
24386605FR-22G C
Solar/Wind Harmer
2.312
24791305MDL-5G
Solar/Wind Harmer
1.271
940581AE2-045 GEN
Solar/Wind Harmer
5.273
971605AH1-302 GEN
Solar/Wind Harmer
4.508
964861AG1-349 GEN
Solar/Wind Harmer
4.023
971917AH1-482 GEN
Solar/Wind Harmer
4.642
958381AF2-132 GEN
Solar/Wind Harmer
4.638
270055AF2-134 C O1
Solar/Wind Harmer
1.534
970373AG2-245 GEN
Solar/Wind Harmer
10.573
276686W4-005 GEN3
Solar/Wind Harmer
1.514
276655WTG1_EQ
Solar/Wind Harmer
4.359
276656WTG2_EQ
Solar/Wind Harmer
0.577
939741AE1-205 GEN
Solar/Wind Harmer
9.988
276621W2-048 GEN
Solar/Wind Harmer
3.107
939401AE1-172 GEN
Solar/Wind Harmer
6.9
965911AG1-460 GEN
Solar/Wind Harmer
0.689
972207SS24-0001
Solar/Wind Harmer
10.879
274773LINCOLN ;4U
Adder
3.06
274774LINCOLN ;5U
Adder
3.06
941551AE2-152 GEN
Solar/Wind Harmer
2.235
274723RIVER EC ;12
Adder
8.805
274751CRETE EC ;1U
Adder
4.047
274754CRETE EC ;4U
Adder
4.047
274812UNIV PK N;8U
Adder
2.458
274802UNIV PARK;5U
Adder
2.86
274732ELWOOD EC;7P
Adder
8.05
274674JOLIET 9 ;6U
Adder
7.534
274676JOLIET 29;8U
Adder
15.001
274745AC1-111 GEN9
Adder
2.72
274682WAUKEGAN ;7U
Adder
8.691
274828WAUKEGAN ;BP
Adder
5.338
970091AG2-072 GEN
Adder
37.044
274822ROCKFORD ;11
Adder
9.374
24639705ELKHART HY
Adder
0.073
274761LEE CO EC;2U
Adder
4.417
274766LEE CO EC;7U
Adder
4.365
252510AF1-249 C
Solar/Wind Helper
0.651
253398AE2-221_GEN2
Solar/Wind Helper
1.621
253333AC1-068 GEN
Solar/Wind Helper
0.625
24726905LAWG2S
50/50
5.169
24726605LAWG1S
50/50
5.167
24726705LAWG2A
50/50
3.465
24726505LAWG1B
50/50
3.441
24726805LAWG2B
50/50
3.426
24729505KEY G4
50/50
6.188
270356AE2-297 GEN
Solar/Wind Harmer
6.685
945581AF1-223 GEN
Solar/Wind Harmer
4.903
958711AF2-162 GEN
Solar/Wind Harmer
1.004
964611AG1-324 GEN
Solar/Wind Harmer
3.524
961761AG1-017 GEN
Solar/Wind Harmer
0.371
970289AG2-191 GEN
Solar/Wind Harmer
1.621
247536S-71 GEN
Solar/Wind Harmer
3.11
270543AE2-219 C
Solar/Wind Harmer
7.041
971029AG2-637 GEN
Solar/Wind Harmer
9.434
270071AF1-092 GEN
Solar/Wind Harmer
8.906
963791AG1-232 GEN
Solar/Wind Harmer
7.881
963841AG1-237 GEN
Solar/Wind Harmer
5.993
24386405FR-21G C
Solar/Wind Harmer
2.312
24387005FR-3G C
Solar/Wind Harmer
2.127
270444AC2-157 GEN1
Solar/Wind Harmer
2.99
270445AC2-157 GEN2
Solar/Wind Harmer
2.99
946581AF1-322 GEN
Solar/Wind Harmer
5.395
24691005MDL-2G C
Solar/Wind Harmer
1.95
959141AF2-205 GEN
Solar/Wind Harmer
3.114
958391AF2-133 GEN
Solar/Wind Harmer
4.657
276668AB2-070 GEN1
Solar/Wind Harmer
1.108
276848AB2-070 GEN3
Solar/Wind Harmer
1.108
276849AB2-070 GEN2
Solar/Wind Harmer
1.108
276763AC1-053 GEN1
Solar/Wind Harmer
1.975
276764AC1-053 GEN2
Solar/Wind Harmer
1.975
276726Z2-087_GEN
Solar/Wind Harmer
3.949
959341AF2-225 GEN
Solar/Wind Harmer
7.491
274853TWINGROVE;U1
Solar/Wind Harmer
3.593
274854TWINGROVE;U2
Solar/Wind Harmer
3.518
970169AG2-114 GEN
Solar/Wind Harmer
4.96
274863CRW1-WTG
Solar/Wind Harmer
2.768
274864CRW2-WTG
Solar/Wind Harmer
2.768
274775LINCOLN ;6U
Adder
3.06
274776LINCOLN ;7U
Adder
3.06
274777LINCOLN ;8U
Adder
3.06
944221AF1-090 GEN
Solar/Wind Harmer
5.39
972228AH1-698 GEN2
Adder
1.821
972227AH1-698 GEN1
Adder
1.282
960591AF2-350 GEN
Solar/Wind Harmer
4.914
972037AH1-567 GEN1
Adder
0.09
274800UNIV PARK;3U
Adder
2.86
274801UNIV PARK;4U
Adder
2.86
274827FISK ;RP
Adder
3.804
274728ELWOOD EC;5P
Adder
8.05
274731ELWOOD EC;2P
Adder
8.05
274733ELWOOD EC;3P
Adder
8.05
274735ELWOOD EC;4P
Adder
8.05
274687WILL CNTY;4U
Adder
13.668
274687WILL CNTY;4U
Adder
13.668
274675JOLIET 29;7U
Adder
15.001
274675JOLIET 29;7U
Adder
14.465
274744AC1-111 GEN8
Adder
2.72
274746AC1-111 G10
Adder
2.72
274823ROCKFORD ;21
Adder
9.306
972267AH1-718 GEN
Adder
1.97
241972AD1-140 GEN
Solar/Wind Helper
3.531
253406AD2-031_GEN
Solar/Wind Helper
0.917
241973AD2-163_GEN1
Solar/Wind Helper
1.085
241974AD2-163_GEN2
Solar/Wind Helper
1.085
945631AF1-228 GEN
Solar/Wind Helper
1.128
253338AC1-165 GEN
Solar/Wind Helper
0.603
253343AC1-166 GEN
Solar/Wind Helper
0.603
270340AC2-060 GEN
Solar/Wind Helper
1.204
25194708EBND2
50/50
6.267
24729405KEY G3
50/50
0.338
24729305KEY G2
50/50
0.332
24729205KEY G1
50/50
0.33
926881AC1-175 GEN
Solar/Wind Harmer
8.509
944541AF1-119 GEN
Solar/Wind Harmer
4.154
960971AF2-388 GEN
Solar/Wind Harmer
10.844
24725505WLD G2 C
Solar/Wind Harmer
3.815
24699105WLD G1 C
Solar/Wind Harmer
3.77
270031AE2-169
Solar/Wind Harmer
7.745
270599AE1-208 GEN
Solar/Wind Harmer
7.745
270383AD1-128 GEN
Solar/Wind Harmer
5.605
964611AG1-324 GEN
Solar/Wind Harmer
0.473
270201AC2-176 GEN
Solar/Wind Harmer
4.459
970291AG2-192 GEN
Solar/Wind Harmer
1.109
970291AG2-192 GEN
Solar/Wind Harmer
0.357
247621Y3-024
Adder
0.187
942221AE2-234 GEN
Solar/Wind Harmer
2.617
970883AG2-550 GEN
Solar/Wind Harmer
7.041
970885AG2-551 GEN
Solar/Wind Harmer
1.637
945391AF1-204 GEN
Solar/Wind Harmer
8.252
970241AG2-163 GEN
Solar/Wind Harmer
13.956
24387305FR-4G C
Solar/Wind Harmer
2.731
966841AG1-555 GEN
Solar/Wind Harmer
1.35
270180AB1-006 GEN1
Solar/Wind Harmer
3.792
24697605MDL-3G C
Solar/Wind Harmer
1.943
24755605MDL-5G
Solar/Wind Harmer
1.271
24697905MDL-4G C
Solar/Wind Harmer
1.21
241955AC1-078 GEN
Solar/Wind Helper
1.036
960681AF2-359 GEN
Solar/Wind Harmer
0.806
270181AB1-006 GEN2
Solar/Wind Harmer
0.377
945421AF1-207 GEN
Solar/Wind Harmer
7.337
957841AF2-078 GEN
Solar/Wind Harmer
3.159
270535AF1-215 GEN1
Solar/Wind Harmer
2.301
270536AF1-215 GEN2
Solar/Wind Harmer
2.301
274880W4-005 GEN4
Solar/Wind Harmer
1.514
276174W4-005 GEN2
Solar/Wind Harmer
1.514
24728805RICHG1
Adder
1.891
24728905RICHG2
Adder
1.891
942111AE2-223 GEN
Solar/Wind Harmer
4.094
960611AF2-352 GEN
Solar/Wind Harmer
1.16
276615X2-022 GEN
Solar/Wind Harmer
0.976
276838X2-022 GEN2
Solar/Wind Harmer
0.116
970349AG2-230 GEN
Solar/Wind Harmer
7.463
276916AD2-100_GEN
Solar/Wind Harmer
10.37
276911AD2-131_GEN
Solar/Wind Harmer
2.096
274770LINCOLN ;1U
Adder
3.06
274771LINCOLN ;2U
Adder
3.06
276897AD1-100 C
Solar/Wind Harmer
22.894
274888KELLY CRK;1U
Solar/Wind Harmer
2.9
276776AD2-060 GEN
Solar/Wind Harmer
0.206
958011AF2-095 GEN
Solar/Wind Harmer
7.075
970941AG2-585 GEN
Solar/Wind Harmer
2.702
274805UNIV PK N;1U
Adder
2.464
274808UNIV PK N;4U
Adder
2.448
274674JOLIET 9 ;6U
Adder
7.534
274696ROCKY RD ;4P
Adder
5.517
274695ROCKY RD ;2P
Adder
5.39
274693ROCKY RD ;1P
Adder
5.337
274697ROCKY RD ;3P
Adder
1.464
274683WAUKEGAN ;8U
Adder
10.184
274683WAUKEGAN ;8U
Adder
8.585
972235AH1-702 GEN1
Adder
1.203
972236AH1-702 GEN2
Adder
1.046
274764LEE CO EC;5U
Adder
4.428
274765LEE CO EC;6U
Adder
4.428
274762LEE CO EC;3U
Adder
4.417
274763LEE CO EC;4U
Adder
4.376
247620Y3-023
Adder
0.218
25183208HLCRTG
Solar/Wind Helper
2.488
252509AD1-136 GEN
Solar/Wind Helper
0.195
253378AE2-206_GEN
Solar/Wind Helper
1.034
962581AG1-107 GEN
Solar/Wind Helper
1.013
961491AF2-440 GEN
Solar/Wind Helper
0.042
253349AC2-067 GEN
Solar/Wind Helper
0.271
253400AC2-068 GEN
Solar/Wind Helper
0.109
253415AE1-040 GEN
Solar/Wind Helper
0.56
253383AE2-342_GEN
Solar/Wind Helper
0.497
965681AG1-436 GEN
Solar/Wind Harmer
2.667
965791AG1-447 GEN
Solar/Wind Harmer
1.364
961161AF2-407 GEN
50/50
36.093
24379505HDWTR1G C
Solar/Wind Harmer
12.055
270240V3-007_GEN2
Solar/Wind Harmer
9.431
270004AE1-209 GEN
Solar/Wind Harmer
6.653
970825AG2-519 GEN
Solar/Wind Harmer
5.927
946031AF1-268 GEN
Solar/Wind Harmer
8.612
962031AG1-047 GEN
Solar/Wind Harmer
2.623
957741AF2-068 GEN
Solar/Wind Harmer
13.014
944531AF1-118 GEN
Solar/Wind Harmer
30.282
965461AG1-414 GEN
Solar/Wind Harmer
1.934
970289AG2-191 GEN
Solar/Wind Harmer
0.655
24728705AND G3
Adder
6.772
24728505AND G1
Adder
3.238
247642Z2-115 C
Solar/Wind Harmer
0.051
970193AG2-126 GEN
Solar/Wind Harmer
8.882
270043AE2-236 GEN
Solar/Wind Harmer
2.988
24386205FR-12G C
Solar/Wind Harmer
2.304
24690905MDL-1G C
Solar/Wind Harmer
4.233
970781AG2-491 GEN
Solar/Wind Harmer
5.272
964401AG1-302 GEN
Solar/Wind Harmer
4.638
276785W4-005 GEN1
Solar/Wind Harmer
1.514
971993AH1-541 GEN
Solar/Wind Harmer
4.627
965091AG1-374 GEN
Solar/Wind Harmer
14.962
959611AF2-252 GEN
Solar/Wind Harmer
1.16
971347AH1-153 GEN
Solar/Wind Harmer
2.488
957381AF2-032 GEN
Solar/Wind Harmer
0.988
942481AE2-261 GEN
Solar/Wind Harmer
14.771
274772LINCOLN ;3U
Adder
3.06
939351AE1-166 GEN
Solar/Wind Harmer
2.923
274887GEN-1.85
Solar/Wind Harmer
2.618
276772AC2-154 GEN
Solar/Wind Harmer
1.371
276843GEN-1.7
Solar/Wind Harmer
0.282
276806AD2-047 C O1
Solar/Wind Harmer
5.256
274724RIVER EC ;11
Adder
8.701
274752CRETE EC ;2U
Adder
4.047
274753CRETE EC ;3U
Adder
4.047
274814UNIV PK N;0U
Adder
2.48
274807UNIV PK N;3U
Adder
2.474
274811UNIV PK N;7U
Adder
2.458
972259AH1-714 GEN
Adder
9.364
274803UNIV PARK;6U
Adder
2.86
972038AH1-567 GEN2
Adder
0.179
274826FISK ;BP
Adder
5.367
274729ELWOOD EC;1P
Adder
8.05
274730ELWOOD EC;6P
Adder
8.05
274734ELWOOD EC;8P
Adder
8.05
274736ELWOOD EC;9P
Adder
8.05
274676JOLIET 29;8U
Adder
14.465
274682WAUKEGAN ;7U
Adder
8.691
274760LEE CO EC;1U
Adder
4.417
274767LEE CO EC;8U
Adder
4.365
252524AE2-267 GEN
Solar/Wind Helper
1.061
960071AF2-298 GEN
Solar/Wind Helper
0.569
253394AE2-221_GEN
Solar/Wind Helper
1.621
252507AC2-088 GEN
Solar/Wind Helper
1.367
276820AF1-078_GEN
Solar/Wind Helper
0.483
270367AC2-061_GEN
Solar/Wind Helper
1.966
270518AE2-148 GEN
Solar/Wind Helper
8.74
270186AC1-089 GEN
Solar/Wind Helper
0.819
253325AC1-069 GEN
Solar/Wind Helper
0.625
LAGNLTFEXP_LAGN->PJM
CLTF
4.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.848
TVALTFEXP_TVA->PJM
CLTF
2.022
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.795
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.657
MECLTFEXP_MEC->PJM
CLTF
7.324
SIGELTFEXP_SIGE->PJM
CLTF
0.239
CPLELTFEXP_CPLE->PJM
CLTF
0.006
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.804
NYPJM->LTFIMP_NY
CLTF
0.662
LGEELTFEXP_LGEE->PJM
CLTF
1.453
WECLTFEXP_WEC->PJM
CLTF
1.818
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.45 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2813.9
MW Contribution:
7.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
5.175
24726605LAWG1S
50/50
5.173
24726705LAWG2A
50/50
3.469
24726505LAWG1B
50/50
3.445
24726805LAWG2B
50/50
3.43
24729505KEY G4
50/50
6.226
270356AE2-297 GEN
Solar/Wind Harmer
6.702
945581AF1-223 GEN
Solar/Wind Harmer
4.925
958711AF2-162 GEN
Solar/Wind Harmer
1.009
964611AG1-324 GEN
Solar/Wind Harmer
3.546
961761AG1-017 GEN
Solar/Wind Harmer
0.374
970289AG2-191 GEN
Solar/Wind Harmer
1.628
247536S-71 GEN
Solar/Wind Harmer
3.133
270543AE2-219 C
Solar/Wind Harmer
7.099
971029AG2-637 GEN
Solar/Wind Harmer
9.524
270071AF1-092 GEN
Solar/Wind Harmer
8.99
963791AG1-232 GEN
Solar/Wind Harmer
7.988
963841AG1-237 GEN
Solar/Wind Harmer
6.016
24386405FR-21G C
Solar/Wind Harmer
2.322
24387005FR-3G C
Solar/Wind Harmer
2.136
270444AC2-157 GEN1
Solar/Wind Harmer
2.989
270445AC2-157 GEN2
Solar/Wind Harmer
2.989
946581AF1-322 GEN
Solar/Wind Harmer
5.421
24691005MDL-2G C
Solar/Wind Harmer
1.959
959141AF2-205 GEN
Solar/Wind Harmer
3.133
958391AF2-133 GEN
Solar/Wind Harmer
4.686
276668AB2-070 GEN1
Solar/Wind Harmer
1.112
276848AB2-070 GEN3
Solar/Wind Harmer
1.112
276849AB2-070 GEN2
Solar/Wind Harmer
1.112
276726Z2-087_GEN
Solar/Wind Harmer
3.966
959341AF2-225 GEN
Solar/Wind Harmer
7.524
276763AC1-053 GEN1
Solar/Wind Harmer
1.982
276764AC1-053 GEN2
Solar/Wind Harmer
1.982
274853TWINGROVE;U1
Solar/Wind Harmer
3.608
274854TWINGROVE;U2
Solar/Wind Harmer
3.532
274863CRW1-WTG
Solar/Wind Harmer
2.782
274864CRW2-WTG
Solar/Wind Harmer
2.782
970169AG2-114 GEN
Solar/Wind Harmer
4.985
274775LINCOLN ;6U
Adder
3.08
274776LINCOLN ;7U
Adder
3.08
274777LINCOLN ;8U
Adder
3.08
960681AF2-359 GEN
Solar/Wind Harmer
1.872
972228AH1-698 GEN2
Adder
1.832
972227AH1-698 GEN1
Adder
1.29
972037AH1-567 GEN1
Adder
0.09
274800UNIV PARK;3U
Adder
2.879
274801UNIV PARK;4U
Adder
2.879
274827FISK ;RP
Adder
3.829
274728ELWOOD EC;5P
Adder
8.1
274731ELWOOD EC;2P
Adder
8.1
274733ELWOOD EC;3P
Adder
8.1
274735ELWOOD EC;4P
Adder
8.1
274687WILL CNTY;4U
Adder
13.754
274687WILL CNTY;4U
Adder
13.754
274675JOLIET 29;7U
Adder
15.095
274675JOLIET 29;7U
Adder
14.556
274744AC1-111 GEN8
Adder
2.736
961161AF2-407 GEN
50/50
36.206
24379505HDWTR1G C
Solar/Wind Harmer
12.089
24726405LAWG1A
50/50
3.345
961171AF2-408 GEN
50/50
9.629
942081AE2-220 GEN
Solar/Wind Harmer
9.778
270209AC1-174_GEN
Solar/Wind Harmer
6.222
270437AC2-090 C
Solar/Wind Harmer
8.533
270239V3-007_GEN1
Solar/Wind Harmer
2.631
270005AE1-210 C O1
Solar/Wind Harmer
6.678
945371AF1-202 GEN
Solar/Wind Harmer
7.577
970825AG2-519 GEN
Solar/Wind Harmer
2.217
958861AF2-177 GEN
Solar/Wind Harmer
11.235
965651AG1-433 GEN
Solar/Wind Harmer
5.451
276903AD2-071 C
Solar/Wind Harmer
9.279
270594AE1-207 GEN
Solar/Wind Harmer
12.358
270032AE2-172
Solar/Wind Harmer
4.232
24728605AND G2
Adder
3.249
270024AE2-089 GEN
Solar/Wind Harmer
3.586
963741AG1-226 GEN
Solar/Wind Harmer
25.209
24385905FR-11G C
Solar/Wind Harmer
4.488
24386605FR-22G C
Solar/Wind Harmer
2.322
24791305MDL-5G
Solar/Wind Harmer
1.277
940581AE2-045 GEN
Solar/Wind Harmer
5.303
971605AH1-302 GEN
Solar/Wind Harmer
4.534
964861AG1-349 GEN
Solar/Wind Harmer
4.049
971917AH1-482 GEN
Solar/Wind Harmer
4.671
958381AF2-132 GEN
Solar/Wind Harmer
4.668
270055AF2-134 C O1
Solar/Wind Harmer
1.544
970373AG2-245 GEN
Solar/Wind Harmer
10.65
276686W4-005 GEN3
Solar/Wind Harmer
1.519
276655WTG1_EQ
Solar/Wind Harmer
4.378
276656WTG2_EQ
Solar/Wind Harmer
0.58
939741AE1-205 GEN
Solar/Wind Harmer
10.033
276621W2-048 GEN
Solar/Wind Harmer
3.116
939401AE1-172 GEN
Solar/Wind Harmer
6.938
972207SS24-0001
Solar/Wind Harmer
10.951
274773LINCOLN ;4U
Adder
3.08
25194708EBND2
50/50
6.282
24729405KEY G3
50/50
0.34
24729305KEY G2
50/50
0.334
24729205KEY G1
50/50
0.332
926881AC1-175 GEN
Solar/Wind Harmer
8.533
944541AF1-119 GEN
Solar/Wind Harmer
4.176
960971AF2-388 GEN
Solar/Wind Harmer
10.902
24725505WLD G2 C
Solar/Wind Harmer
3.83
24699105WLD G1 C
Solar/Wind Harmer
3.785
270031AE2-169
Solar/Wind Harmer
7.785
270599AE1-208 GEN
Solar/Wind Harmer
7.785
270383AD1-128 GEN
Solar/Wind Harmer
5.635
964611AG1-324 GEN
Solar/Wind Harmer
0.476
270201AC2-176 GEN
Solar/Wind Harmer
4.488
970291AG2-192 GEN
Solar/Wind Harmer
1.114
970291AG2-192 GEN
Solar/Wind Harmer
0.359
247621Y3-024
Adder
0.189
942221AE2-234 GEN
Solar/Wind Harmer
2.639
970883AG2-550 GEN
Solar/Wind Harmer
7.099
970885AG2-551 GEN
Solar/Wind Harmer
1.651
945391AF1-204 GEN
Solar/Wind Harmer
8.271
970241AG2-163 GEN
Solar/Wind Harmer
14.005
24387305FR-4G C
Solar/Wind Harmer
2.743
966841AG1-555 GEN
Solar/Wind Harmer
1.356
270180AB1-006 GEN1
Solar/Wind Harmer
3.81
24697605MDL-3G C
Solar/Wind Harmer
1.953
24755605MDL-5G
Solar/Wind Harmer
1.277
24697905MDL-4G C
Solar/Wind Harmer
1.216
270181AB1-006 GEN2
Solar/Wind Harmer
0.379
945421AF1-207 GEN
Solar/Wind Harmer
7.375
957841AF2-078 GEN
Solar/Wind Harmer
3.175
270535AF1-215 GEN1
Solar/Wind Harmer
2.317
270536AF1-215 GEN2
Solar/Wind Harmer
2.317
24728805RICHG1
Adder
1.91
24728905RICHG2
Adder
1.91
274880W4-005 GEN4
Solar/Wind Harmer
1.519
276174W4-005 GEN2
Solar/Wind Harmer
1.519
970349AG2-230 GEN
Solar/Wind Harmer
7.53
942111AE2-223 GEN
Solar/Wind Harmer
4.112
960611AF2-352 GEN
Solar/Wind Harmer
1.165
276615X2-022 GEN
Solar/Wind Harmer
0.979
276838X2-022 GEN2
Solar/Wind Harmer
0.116
274770LINCOLN ;1U
Adder
3.08
274771LINCOLN ;2U
Adder
3.08
276897AD1-100 C
Solar/Wind Harmer
23.036
965681AG1-436 GEN
Solar/Wind Harmer
6.193
965791AG1-447 GEN
Solar/Wind Harmer
3.169
276916AD2-100_GEN
Solar/Wind Harmer
10.394
276911AD2-131_GEN
Solar/Wind Harmer
2.101
274888KELLY CRK;1U
Solar/Wind Harmer
2.918
276776AD2-060 GEN
Solar/Wind Harmer
0.207
274805UNIV PK N;1U
Adder
2.48
274808UNIV PK N;4U
Adder
2.464
274674JOLIET 9 ;6U
Adder
7.581
274696ROCKY RD ;4P
Adder
5.549
274695ROCKY RD ;2P
Adder
5.421
274693ROCKY RD ;1P
Adder
5.368
274697ROCKY RD ;3P
Adder
1.473
274683WAUKEGAN ;8U
Adder
10.242
274683WAUKEGAN ;8U
Adder
8.634
972235AH1-702 GEN1
Adder
1.209
972236AH1-702 GEN2
Adder
1.051
247620Y3-023
Adder
0.221
274764LEE CO EC;5U
Adder
4.449
274765LEE CO EC;6U
Adder
4.449
274762LEE CO EC;3U
Adder
4.439
274763LEE CO EC;4U
Adder
4.397
25183208HLCRTG
Solar/Wind Helper
2.475
252509AD1-136 GEN
Solar/Wind Helper
0.194
253378AE2-206_GEN
Solar/Wind Helper
1.008
962581AG1-107 GEN
Solar/Wind Helper
1.008
961491AF2-440 GEN
Solar/Wind Helper
0.041
253349AC2-067 GEN
Solar/Wind Helper
0.267
253400AC2-068 GEN
Solar/Wind Helper
0.107
253415AE1-040 GEN
Solar/Wind Helper
0.551
253383AE2-342_GEN
Solar/Wind Helper
0.473
958011AF2-095 GEN
Solar/Wind Harmer
5.873
270240V3-007_GEN2
Solar/Wind Harmer
9.459
270004AE1-209 GEN
Solar/Wind Harmer
6.678
970825AG2-519 GEN
Solar/Wind Harmer
5.953
946031AF1-268 GEN
Solar/Wind Harmer
8.652
962031AG1-047 GEN
Solar/Wind Harmer
2.64
957741AF2-068 GEN
Solar/Wind Harmer
13.098
944531AF1-118 GEN
Solar/Wind Harmer
30.481
965461AG1-414 GEN
Solar/Wind Harmer
1.943
970289AG2-191 GEN
Solar/Wind Harmer
0.658
24728705AND G3
Adder
6.794
24728505AND G1
Adder
3.249
247642Z2-115 C
Solar/Wind Harmer
0.052
970193AG2-126 GEN
Solar/Wind Harmer
8.903
270043AE2-236 GEN
Solar/Wind Harmer
3.024
24386205FR-12G C
Solar/Wind Harmer
2.314
24690905MDL-1G C
Solar/Wind Harmer
4.253
970781AG2-491 GEN
Solar/Wind Harmer
5.298
964401AG1-302 GEN
Solar/Wind Harmer
4.668
276785W4-005 GEN1
Solar/Wind Harmer
1.519
971993AH1-541 GEN
Solar/Wind Harmer
4.642
971347AH1-153 GEN
Solar/Wind Harmer
2.51
965091AG1-374 GEN
Solar/Wind Harmer
15.024
959611AF2-252 GEN
Solar/Wind Harmer
1.165
274772LINCOLN ;3U
Adder
3.08
939351AE1-166 GEN
Solar/Wind Harmer
2.941
957381AF2-032 GEN
Solar/Wind Harmer
0.991
942481AE2-261 GEN
Solar/Wind Harmer
14.807
274724RIVER EC ;11
Adder
8.762
972231SS25-0005
Solar/Wind Harmer
4.695
972181SS23-001
Solar/Wind Harmer
2.934
274752CRETE EC ;2U
Adder
2.418
274753CRETE EC ;3U
Adder
2.418
274887GEN-1.85
Solar/Wind Harmer
2.635
276772AC2-154 GEN
Solar/Wind Harmer
1.38
276843GEN-1.7
Solar/Wind Harmer
0.283
276164X3-005 C
Solar/Wind Harmer
0.347
276806AD2-047 C O1
Solar/Wind Harmer
5.29
274814UNIV PK N;0U
Adder
2.497
274807UNIV PK N;3U
Adder
2.491
274811UNIV PK N;7U
Adder
2.475
972259AH1-714 GEN
Adder
9.423
274803UNIV PARK;6U
Adder
2.879
972038AH1-567 GEN2
Adder
0.18
274826FISK ;BP
Adder
5.402
274729ELWOOD EC;1P
Adder
8.1
274730ELWOOD EC;6P
Adder
8.1
274734ELWOOD EC;8P
Adder
8.1
274736ELWOOD EC;9P
Adder
8.1
274676JOLIET 29;8U
Adder
14.556
274682WAUKEGAN ;7U
Adder
8.741
274760LEE CO EC;1U
Adder
4.439
274767LEE CO EC;8U
Adder
4.387
252524AE2-267 GEN
Solar/Wind Helper
1.058
960071AF2-298 GEN
Solar/Wind Helper
0.562
274774LINCOLN ;5U
Adder
3.08
941551AE2-152 GEN
Solar/Wind Harmer
2.249
965911AG1-460 GEN
Solar/Wind Harmer
0.691
274723RIVER EC ;12
Adder
8.866
274751CRETE EC ;1U
Adder
2.418
274754CRETE EC ;4U
Adder
2.418
274812UNIV PK N;8U
Adder
2.475
274802UNIV PARK;5U
Adder
2.879
274732ELWOOD EC;7P
Adder
8.1
274674JOLIET 9 ;6U
Adder
7.581
274676JOLIET 29;8U
Adder
15.095
274745AC1-111 GEN9
Adder
2.736
274682WAUKEGAN ;7U
Adder
8.741
274828WAUKEGAN ;BP
Adder
5.369
24639705ELKHART HY
Adder
0.074
970091AG2-072 GEN
Adder
36.89
274822ROCKFORD ;11
Adder
9.422
274761LEE CO EC;2U
Adder
4.439
274766LEE CO EC;7U
Adder
4.387
252510AF1-249 C
Solar/Wind Helper
0.649
253398AE2-221_GEN2
Solar/Wind Helper
1.605
253333AC1-068 GEN
Solar/Wind Helper
0.605
274746AC1-111 G10
Adder
2.736
274823ROCKFORD ;21
Adder
9.354
972267AH1-718 GEN
Adder
1.98
241972AD1-140 GEN
Solar/Wind Helper
3.462
253406AD2-031_GEN
Solar/Wind Helper
0.908
270340AC2-060 GEN
Solar/Wind Helper
1.186
253338AC1-165 GEN
Solar/Wind Helper
0.584
253343AC1-166 GEN
Solar/Wind Helper
0.584
241973AD2-163_GEN1
Solar/Wind Helper
1.034
241974AD2-163_GEN2
Solar/Wind Helper
1.034
945631AF1-228 GEN
Solar/Wind Helper
1.084
241955AC1-078 GEN
Solar/Wind Helper
0.981
253394AE2-221_GEN
Solar/Wind Helper
1.605
252507AC2-088 GEN
Solar/Wind Helper
1.361
276820AF1-078_GEN
Solar/Wind Helper
0.471
270367AC2-061_GEN
Solar/Wind Helper
1.959
270186AC1-089 GEN
Solar/Wind Helper
0.816
270518AE2-148 GEN
Solar/Wind Helper
8.492
253325AC1-069 GEN
Solar/Wind Helper
0.605
LAGNLTFEXP_LAGN->PJM
CLTF
4.89
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.583
TVALTFEXP_TVA->PJM
CLTF
1.97
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.493
MECLTFEXP_MEC->PJM
CLTF
7.337
SIGELTFEXP_SIGE->PJM
CLTF
0.239
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.525
NYPJM->LTFIMP_NY
CLTF
0.654
LGEELTFEXP_LGEE->PJM
CLTF
1.45
WECLTFEXP_WEC->PJM
CLTF
1.827
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.4 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2812.93
MW Contribution:
7.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
5.166
24726605LAWG1S
50/50
5.163
24726705LAWG2A
50/50
3.463
24726505LAWG1B
50/50
3.439
24726805LAWG2B
50/50
3.424
24729505KEY G4
50/50
6.173
270356AE2-297 GEN
Solar/Wind Harmer
6.673
945581AF1-223 GEN
Solar/Wind Harmer
4.892
958711AF2-162 GEN
Solar/Wind Harmer
1.001
964611AG1-324 GEN
Solar/Wind Harmer
3.517
961761AG1-017 GEN
Solar/Wind Harmer
0.371
970289AG2-191 GEN
Solar/Wind Harmer
1.616
247536S-71 GEN
Solar/Wind Harmer
3.103
270543AE2-219 C
Solar/Wind Harmer
7.025
971029AG2-637 GEN
Solar/Wind Harmer
9.412
270071AF1-092 GEN
Solar/Wind Harmer
8.872
963791AG1-232 GEN
Solar/Wind Harmer
7.862
963841AG1-237 GEN
Solar/Wind Harmer
5.953
24386405FR-21G C
Solar/Wind Harmer
2.297
24387005FR-3G C
Solar/Wind Harmer
2.113
270444AC2-157 GEN1
Solar/Wind Harmer
2.964
270445AC2-157 GEN2
Solar/Wind Harmer
2.964
946581AF1-322 GEN
Solar/Wind Harmer
5.359
24691005MDL-2G C
Solar/Wind Harmer
1.937
959141AF2-205 GEN
Solar/Wind Harmer
3.095
958391AF2-133 GEN
Solar/Wind Harmer
4.629
276668AB2-070 GEN1
Solar/Wind Harmer
1.1
276848AB2-070 GEN3
Solar/Wind Harmer
1.1
276849AB2-070 GEN2
Solar/Wind Harmer
1.1
276726Z2-087_GEN
Solar/Wind Harmer
3.921
959341AF2-225 GEN
Solar/Wind Harmer
7.438
276763AC1-053 GEN1
Solar/Wind Harmer
1.96
276764AC1-053 GEN2
Solar/Wind Harmer
1.96
274853TWINGROVE;U1
Solar/Wind Harmer
3.567
274854TWINGROVE;U2
Solar/Wind Harmer
3.492
970169AG2-114 GEN
Solar/Wind Harmer
4.926
274863CRW1-WTG
Solar/Wind Harmer
2.749
274864CRW2-WTG
Solar/Wind Harmer
2.749
274775LINCOLN ;6U
Adder
3.041
274776LINCOLN ;7U
Adder
3.041
274777LINCOLN ;8U
Adder
3.041
944221AF1-090 GEN
Solar/Wind Harmer
5.345
960681AF2-359 GEN
Solar/Wind Harmer
1.846
972228AH1-698 GEN2
Adder
1.809
972227AH1-698 GEN1
Adder
1.274
972037AH1-567 GEN1
Adder
0.089
274800UNIV PARK;3U
Adder
2.842
274801UNIV PARK;4U
Adder
2.842
274827FISK ;RP
Adder
3.78
274728ELWOOD EC;5P
Adder
7.998
274731ELWOOD EC;2P
Adder
7.998
274733ELWOOD EC;3P
Adder
7.998
274735ELWOOD EC;4P
Adder
7.998
274687WILL CNTY;4U
Adder
13.58
274687WILL CNTY;4U
Adder
13.58
274675JOLIET 29;7U
Adder
14.904
274675JOLIET 29;7U
Adder
14.372
274744AC1-111 GEN8
Adder
2.702
274746AC1-111 G10
Adder
2.702
274823ROCKFORD ;21
Adder
9.239
972267AH1-718 GEN
Adder
1.956
241972AD1-140 GEN
Solar/Wind Helper
3.504
253406AD2-031_GEN
Solar/Wind Helper
0.915
241973AD2-163_GEN1
Solar/Wind Helper
1.061
241974AD2-163_GEN2
Solar/Wind Helper
1.061
270340AC2-060 GEN
Solar/Wind Helper
1.197
253338AC1-165 GEN
Solar/Wind Helper
0.592
253343AC1-166 GEN
Solar/Wind Helper
0.592
945631AF1-228 GEN
Solar/Wind Helper
1.101
241955AC1-078 GEN
Solar/Wind Helper
1.004
960591AF2-350 GEN
Solar/Wind Harmer
1.305
24726405LAWG1A
50/50
3.339
961171AF2-408 GEN
50/50
9.571
942081AE2-220 GEN
Solar/Wind Harmer
9.735
270209AC1-174_GEN
Solar/Wind Harmer
6.195
270437AC2-090 C
Solar/Wind Harmer
8.496
270239V3-007_GEN1
Solar/Wind Harmer
2.619
270005AE1-210 C O1
Solar/Wind Harmer
6.64
945371AF1-202 GEN
Solar/Wind Harmer
7.526
970825AG2-519 GEN
Solar/Wind Harmer
2.203
958861AF2-177 GEN
Solar/Wind Harmer
11.154
965651AG1-433 GEN
Solar/Wind Harmer
5.41
276903AD2-071 C
Solar/Wind Harmer
9.214
270594AE1-207 GEN
Solar/Wind Harmer
12.268
270032AE2-172
Solar/Wind Harmer
4.201
24728605AND G2
Adder
3.226
270024AE2-089 GEN
Solar/Wind Harmer
3.547
963741AG1-226 GEN
Solar/Wind Harmer
24.954
24385905FR-11G C
Solar/Wind Harmer
4.439
24386605FR-22G C
Solar/Wind Harmer
2.297
24791305MDL-5G
Solar/Wind Harmer
1.263
940581AE2-045 GEN
Solar/Wind Harmer
5.24
971605AH1-302 GEN
Solar/Wind Harmer
4.48
964861AG1-349 GEN
Solar/Wind Harmer
3.999
971917AH1-482 GEN
Solar/Wind Harmer
4.613
958381AF2-132 GEN
Solar/Wind Harmer
4.61
270055AF2-134 C O1
Solar/Wind Harmer
1.525
970373AG2-245 GEN
Solar/Wind Harmer
10.512
276686W4-005 GEN3
Solar/Wind Harmer
1.503
276655WTG1_EQ
Solar/Wind Harmer
4.328
276656WTG2_EQ
Solar/Wind Harmer
0.573
939741AE1-205 GEN
Solar/Wind Harmer
9.918
276621W2-048 GEN
Solar/Wind Harmer
3.083
939401AE1-172 GEN
Solar/Wind Harmer
6.854
972207SS24-0001
Solar/Wind Harmer
10.811
274773LINCOLN ;4U
Adder
3.041
274774LINCOLN ;5U
Adder
3.041
965911AG1-460 GEN
Solar/Wind Harmer
0.684
941551AE2-152 GEN
Solar/Wind Harmer
2.221
274723RIVER EC ;12
Adder
8.751
274751CRETE EC ;1U
Adder
4.023
274754CRETE EC ;4U
Adder
4.023
274812UNIV PK N;8U
Adder
2.443
274802UNIV PARK;5U
Adder
2.842
274732ELWOOD EC;7P
Adder
7.998
274674JOLIET 9 ;6U
Adder
7.485
274676JOLIET 29;8U
Adder
14.904
274745AC1-111 GEN9
Adder
2.702
274682WAUKEGAN ;7U
Adder
8.632
274828WAUKEGAN ;BP
Adder
5.302
970091AG2-072 GEN
Adder
36.602
24639705ELKHART HY
Adder
0.073
274822ROCKFORD ;11
Adder
9.307
274761LEE CO EC;2U
Adder
4.385
274766LEE CO EC;7U
Adder
4.333
252510AF1-249 C
Solar/Wind Helper
0.651
253398AE2-221_GEN2
Solar/Wind Helper
1.618
253333AC1-068 GEN
Solar/Wind Helper
0.614
961161AF2-407 GEN
50/50
35.992
24379505HDWTR1G C
Solar/Wind Harmer
12.037
270240V3-007_GEN2
Solar/Wind Harmer
9.417
270004AE1-209 GEN
Solar/Wind Harmer
6.64
970825AG2-519 GEN
Solar/Wind Harmer
5.914
946031AF1-268 GEN
Solar/Wind Harmer
8.593
962031AG1-047 GEN
Solar/Wind Harmer
2.617
957741AF2-068 GEN
Solar/Wind Harmer
12.985
944531AF1-118 GEN
Solar/Wind Harmer
30.209
965461AG1-414 GEN
Solar/Wind Harmer
1.928
970289AG2-191 GEN
Solar/Wind Harmer
0.653
24728705AND G3
Adder
6.747
24728505AND G1
Adder
3.226
247642Z2-115 C
Solar/Wind Harmer
0.051
970193AG2-126 GEN
Solar/Wind Harmer
8.823
270043AE2-236 GEN
Solar/Wind Harmer
2.977
24386205FR-12G C
Solar/Wind Harmer
2.289
24690905MDL-1G C
Solar/Wind Harmer
4.205
970781AG2-491 GEN
Solar/Wind Harmer
5.238
964401AG1-302 GEN
Solar/Wind Harmer
4.61
276785W4-005 GEN1
Solar/Wind Harmer
1.503
971993AH1-541 GEN
Solar/Wind Harmer
4.592
965091AG1-374 GEN
Solar/Wind Harmer
14.854
959611AF2-252 GEN
Solar/Wind Harmer
1.151
971347AH1-153 GEN
Solar/Wind Harmer
2.475
274772LINCOLN ;3U
Adder
3.041
957381AF2-032 GEN
Solar/Wind Harmer
0.98
942481AE2-261 GEN
Solar/Wind Harmer
14.652
939351AE1-166 GEN
Solar/Wind Harmer
2.904
274724RIVER EC ;11
Adder
8.648
274887GEN-1.85
Solar/Wind Harmer
2.601
276772AC2-154 GEN
Solar/Wind Harmer
1.363
276843GEN-1.7
Solar/Wind Harmer
0.28
276806AD2-047 C O1
Solar/Wind Harmer
5.223
274752CRETE EC ;2U
Adder
4.023
274753CRETE EC ;3U
Adder
4.023
274814UNIV PK N;0U
Adder
2.464
274807UNIV PK N;3U
Adder
2.459
274811UNIV PK N;7U
Adder
2.443
972259AH1-714 GEN
Adder
9.304
274803UNIV PARK;6U
Adder
2.842
972038AH1-567 GEN2
Adder
0.178
274826FISK ;BP
Adder
5.333
274729ELWOOD EC;1P
Adder
7.998
274730ELWOOD EC;6P
Adder
7.998
274734ELWOOD EC;8P
Adder
7.998
274736ELWOOD EC;9P
Adder
7.998
274676JOLIET 29;8U
Adder
14.372
274682WAUKEGAN ;7U
Adder
8.632
274760LEE CO EC;1U
Adder
4.385
274767LEE CO EC;8U
Adder
4.333
252524AE2-267 GEN
Solar/Wind Helper
1.061
960071AF2-298 GEN
Solar/Wind Helper
0.567
253394AE2-221_GEN
Solar/Wind Helper
1.618
252507AC2-088 GEN
Solar/Wind Helper
1.369
276820AF1-078_GEN
Solar/Wind Helper
0.481
270367AC2-061_GEN
Solar/Wind Helper
1.971
270518AE2-148 GEN
Solar/Wind Helper
8.602
270186AC1-089 GEN
Solar/Wind Helper
0.821
253325AC1-069 GEN
Solar/Wind Helper
0.614
25194708EBND2
50/50
6.26
24729405KEY G3
50/50
0.337
24729305KEY G2
50/50
0.331
24729205KEY G1
50/50
0.33
926881AC1-175 GEN
Solar/Wind Harmer
8.496
944541AF1-119 GEN
Solar/Wind Harmer
4.145
960971AF2-388 GEN
Solar/Wind Harmer
10.82
24725505WLD G2 C
Solar/Wind Harmer
3.804
24699105WLD G1 C
Solar/Wind Harmer
3.76
270031AE2-169
Solar/Wind Harmer
7.727
270599AE1-208 GEN
Solar/Wind Harmer
7.727
270383AD1-128 GEN
Solar/Wind Harmer
5.593
964611AG1-324 GEN
Solar/Wind Harmer
0.472
270201AC2-176 GEN
Solar/Wind Harmer
4.449
970291AG2-192 GEN
Solar/Wind Harmer
1.105
970291AG2-192 GEN
Solar/Wind Harmer
0.356
247621Y3-024
Adder
0.187
942221AE2-234 GEN
Solar/Wind Harmer
2.61
970883AG2-550 GEN
Solar/Wind Harmer
7.025
970885AG2-551 GEN
Solar/Wind Harmer
1.634
945391AF1-204 GEN
Solar/Wind Harmer
8.198
970241AG2-163 GEN
Solar/Wind Harmer
13.864
24387305FR-4G C
Solar/Wind Harmer
2.713
966841AG1-555 GEN
Solar/Wind Harmer
1.341
270180AB1-006 GEN1
Solar/Wind Harmer
3.767
24697605MDL-3G C
Solar/Wind Harmer
1.931
24755605MDL-5G
Solar/Wind Harmer
1.263
24697905MDL-4G C
Solar/Wind Harmer
1.202
270181AB1-006 GEN2
Solar/Wind Harmer
0.375
945421AF1-207 GEN
Solar/Wind Harmer
7.29
957841AF2-078 GEN
Solar/Wind Harmer
3.138
270535AF1-215 GEN1
Solar/Wind Harmer
2.287
270536AF1-215 GEN2
Solar/Wind Harmer
2.287
24728805RICHG1
Adder
1.885
24728905RICHG2
Adder
1.885
274880W4-005 GEN4
Solar/Wind Harmer
1.503
276174W4-005 GEN2
Solar/Wind Harmer
1.503
942111AE2-223 GEN
Solar/Wind Harmer
4.065
960611AF2-352 GEN
Solar/Wind Harmer
1.151
970349AG2-230 GEN
Solar/Wind Harmer
7.425
276615X2-022 GEN
Solar/Wind Harmer
0.968
276838X2-022 GEN2
Solar/Wind Harmer
0.115
274770LINCOLN ;1U
Adder
3.041
274771LINCOLN ;2U
Adder
3.041
276916AD2-100_GEN
Solar/Wind Harmer
10.286
276911AD2-131_GEN
Solar/Wind Harmer
2.079
276897AD1-100 C
Solar/Wind Harmer
22.747
965681AG1-436 GEN
Solar/Wind Harmer
6.108
965791AG1-447 GEN
Solar/Wind Harmer
3.125
274888KELLY CRK;1U
Solar/Wind Harmer
2.881
276776AD2-060 GEN
Solar/Wind Harmer
0.204
958011AF2-095 GEN
Solar/Wind Harmer
7.031
274805UNIV PK N;1U
Adder
2.448
274808UNIV PK N;4U
Adder
2.432
274674JOLIET 9 ;6U
Adder
7.485
274695ROCKY RD ;2P
Adder
5.353
274693ROCKY RD ;1P
Adder
5.301
274697ROCKY RD ;3P
Adder
1.454
274696ROCKY RD ;4P
Adder
5.48
274683WAUKEGAN ;8U
Adder
10.115
274683WAUKEGAN ;8U
Adder
8.526
972235AH1-702 GEN1
Adder
1.194
972236AH1-702 GEN2
Adder
1.038
274764LEE CO EC;5U
Adder
4.395
274765LEE CO EC;6U
Adder
4.395
274762LEE CO EC;3U
Adder
4.385
274763LEE CO EC;4U
Adder
4.344
247620Y3-023
Adder
0.217
25183208HLCRTG
Solar/Wind Helper
2.489
252509AD1-136 GEN
Solar/Wind Helper
0.196
253378AE2-206_GEN
Solar/Wind Helper
1.03
962581AG1-107 GEN
Solar/Wind Helper
1.015
961491AF2-440 GEN
Solar/Wind Helper
0.042
253349AC2-067 GEN
Solar/Wind Helper
0.271
253400AC2-068 GEN
Solar/Wind Helper
0.109
253415AE1-040 GEN
Solar/Wind Helper
0.556
253383AE2-342_GEN
Solar/Wind Helper
0.486
LAGNLTFEXP_LAGN->PJM
CLTF
4.848
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.625
TVALTFEXP_TVA->PJM
CLTF
1.954
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.471
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.418
MECLTFEXP_MEC->PJM
CLTF
7.254
SIGELTFEXP_SIGE->PJM
CLTF
0.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.09
NYPJM->LTFIMP_NY
CLTF
0.639
LGEELTFEXP_LGEE->PJM
CLTF
1.423
WECLTFEXP_WEC->PJM
CLTF
1.805
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.23 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2808.9
MW Contribution:
13.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247621Y3-024
50/50
0.342
24729405KEY G3
50/50
0.494
24729305KEY G2
50/50
0.486
24729205KEY G1
50/50
0.483
24728805RICHG1
50/50
4.622
24728905RICHG2
50/50
4.622
926881AC1-175 GEN
Solar/Wind Harmer
13.941
270383AD1-128 GEN
Solar/Wind Harmer
9.794
944541AF1-119 GEN
Solar/Wind Harmer
6.275
960971AF2-388 GEN
Solar/Wind Harmer
16.382
964611AG1-324 GEN
Solar/Wind Harmer
0.778
270031AE2-169
Solar/Wind Harmer
12.049
270599AE1-208 GEN
Solar/Wind Harmer
12.049
24725505WLD G2 C
Solar/Wind Harmer
5.843
24699105WLD G1 C
Solar/Wind Harmer
5.775
270201AC2-176 GEN
Solar/Wind Harmer
7.367
970883AG2-550 GEN
Solar/Wind Harmer
13.066
970885AG2-551 GEN
Solar/Wind Harmer
3.039
970291AG2-192 GEN
Solar/Wind Harmer
1.607
970291AG2-192 GEN
Solar/Wind Harmer
0.518
942221AE2-234 GEN
Solar/Wind Harmer
3.933
945391AF1-204 GEN
Solar/Wind Harmer
9.432
970241AG2-163 GEN
Solar/Wind Harmer
14.805
24387305FR-4G C
Solar/Wind Harmer
2.746
966841AG1-555 GEN
Solar/Wind Harmer
1.357
270180AB1-006 GEN1
Solar/Wind Harmer
3.713
24697605MDL-3G C
Solar/Wind Harmer
1.903
24755605MDL-5G
Solar/Wind Harmer
1.245
24697905MDL-4G C
Solar/Wind Harmer
1.185
270181AB1-006 GEN2
Solar/Wind Harmer
0.369
274880W4-005 GEN4
Solar/Wind Harmer
1.539
276174W4-005 GEN2
Solar/Wind Harmer
1.539
276615X2-022 GEN
Solar/Wind Harmer
0.993
276838X2-022 GEN2
Solar/Wind Harmer
0.118
945421AF1-207 GEN
Solar/Wind Harmer
7.096
957841AF2-078 GEN
Solar/Wind Harmer
3.055
276916AD2-100_GEN
Solar/Wind Harmer
10.583
276911AD2-131_GEN
Solar/Wind Harmer
2.139
960611AF2-352 GEN
Solar/Wind Harmer
1.161
942111AE2-223 GEN
Solar/Wind Harmer
4.087
247620Y3-023
Adder
0.229
270535AF1-215 GEN1
Solar/Wind Harmer
2.223
270536AF1-215 GEN2
Solar/Wind Harmer
2.223
944231AF1-091 GEN
Solar/Wind Harmer
8.554
276897AD1-100 C
Solar/Wind Harmer
22.071
274805UNIV PK N;1U
Adder
2.378
274808UNIV PK N;4U
Adder
2.363
274674JOLIET 9 ;6U
Adder
7.256
274770LINCOLN ;1U
Adder
3.967
274771LINCOLN ;2U
Adder
3.967
274696ROCKY RD ;4P
Adder
5.308
274695ROCKY RD ;2P
Adder
5.185
274693ROCKY RD ;1P
Adder
5.134
274697ROCKY RD ;3P
Adder
1.409
274683WAUKEGAN ;8U
Adder
9.803
274683WAUKEGAN ;8U
Adder
8.263
972235AH1-702 GEN1
Adder
1.161
972236AH1-702 GEN2
Adder
1.009
274764LEE CO EC;5U
Adder
4.279
274765LEE CO EC;6U
Adder
4.279
274762LEE CO EC;3U
Adder
4.269
274763LEE CO EC;4U
Adder
4.229
252509AD1-136 GEN
Solar/Wind Helper
0.244
25183208HLCRTG
Solar/Wind Helper
2.612
962581AG1-107 GEN
Solar/Wind Helper
0.944
961491AF2-440 GEN
Solar/Wind Helper
0.039
253415AE1-040 GEN
Solar/Wind Helper
0.542
253378AE2-206_GEN
Solar/Wind Helper
0.696
24726405LAWG1A
50/50
5.753
961171AF2-408 GEN
50/50
15.251
24728605AND G2
50/50
5.346
942081AE2-220 GEN
Solar/Wind Harmer
15.974
270209AC1-174_GEN
Solar/Wind Harmer
10.165
270437AC2-090 C
Solar/Wind Harmer
13.941
270239V3-007_GEN1
Solar/Wind Harmer
4.298
270005AE1-210 C O1
Solar/Wind Harmer
10.625
970825AG2-519 GEN
Solar/Wind Harmer
3.543
945371AF1-202 GEN
Solar/Wind Harmer
11.683
958861AF2-177 GEN
Solar/Wind Harmer
17.042
965651AG1-433 GEN
Solar/Wind Harmer
8.191
276903AD2-071 C
Solar/Wind Harmer
13.916
270594AE1-207 GEN
Solar/Wind Harmer
18.403
270032AE2-172
Solar/Wind Harmer
6.303
270222AC2-111 GEN
Solar/Wind Harmer
5.586
944031AF1-071 GEN
Solar/Wind Harmer
1.257
270024AE2-089 GEN
Solar/Wind Harmer
5.691
963741AG1-226 GEN
Solar/Wind Harmer
26.648
965011AG1-365 GEN
Solar/Wind Harmer
5.463
24385905FR-11G C
Solar/Wind Harmer
4.493
24386605FR-22G C
Solar/Wind Harmer
2.325
24791305MDL-5G
Solar/Wind Harmer
1.245
276686W4-005 GEN3
Solar/Wind Harmer
1.539
276621W2-048 GEN
Solar/Wind Harmer
3.16
965911AG1-460 GEN
Solar/Wind Harmer
0.703
940581AE2-045 GEN
Solar/Wind Harmer
5.097
971605AH1-302 GEN
Solar/Wind Harmer
4.358
276655WTG1_EQ
Solar/Wind Harmer
4.351
276656WTG2_EQ
Solar/Wind Harmer
0.576
939741AE1-205 GEN
Solar/Wind Harmer
9.97
964861AG1-349 GEN
Solar/Wind Harmer
3.888
971917AH1-482 GEN
Solar/Wind Harmer
4.486
958381AF2-132 GEN
Solar/Wind Harmer
4.482
24639705ELKHART HY
Adder
0.076
270055AF2-134 C O1
Solar/Wind Harmer
1.482
270216AD2-079_GEN
Solar/Wind Harmer
0.295
970373AG2-245 GEN
Solar/Wind Harmer
10.21
939401AE1-172 GEN
Solar/Wind Harmer
6.733
941551AE2-152 GEN
Solar/Wind Harmer
2.155
274723RIVER EC ;12
Adder
8.494
274812UNIV PK N;8U
Adder
2.373
274802UNIV PARK;5U
Adder
2.757
274732ELWOOD EC;7P
Adder
7.759
274674JOLIET 9 ;6U
Adder
7.256
274676JOLIET 29;8U
Adder
14.438
274773LINCOLN ;4U
Adder
3.967
274774LINCOLN ;5U
Adder
3.967
274745AC1-111 GEN9
Adder
2.614
274682WAUKEGAN ;7U
Adder
8.365
274828WAUKEGAN ;BP
Adder
5.138
274822ROCKFORD ;11
Adder
9.041
274761LEE CO EC;2U
Adder
4.269
274766LEE CO EC;7U
Adder
4.219
252510AF1-249 C
Solar/Wind Helper
0.565
253398AE2-221_GEN2
Solar/Wind Helper
1.56
339221AD2-048_GEN
Solar/Wind Helper
0.776
253333AC1-068 GEN
Solar/Wind Helper
0.572
274751CRETE EC ;1U
Solar/Wind Harmer
1.981
274754CRETE EC ;4U
Solar/Wind Harmer
1.981
24726905LAWG2S
50/50
8.9
24726605LAWG1S
50/50
8.896
24726705LAWG2A
50/50
5.966
24726505LAWG1B
50/50
5.924
24726805LAWG2B
50/50
5.898
24729505KEY G4
50/50
9.047
270356AE2-297 GEN
Solar/Wind Harmer
11.188
945581AF1-223 GEN
Solar/Wind Harmer
7.594
958711AF2-162 GEN
Solar/Wind Harmer
1.516
964611AG1-324 GEN
Solar/Wind Harmer
5.798
961761AG1-017 GEN
Solar/Wind Harmer
0.613
247536S-71 GEN
Solar/Wind Harmer
5.469
270543AE2-219 C
Solar/Wind Harmer
13.066
971029AG2-637 GEN
Solar/Wind Harmer
18.762
970289AG2-191 GEN
Solar/Wind Harmer
2.349
963791AG1-232 GEN
Solar/Wind Harmer
11.705
270071AF1-092 GEN
Solar/Wind Harmer
10.756
963841AG1-237 GEN
Solar/Wind Harmer
6.201
959331AF2-224 GEN
Solar/Wind Harmer
5.463
970031AG2-029 GEN
Solar/Wind Harmer
13.609
24386405FR-21G C
Solar/Wind Harmer
2.325
24387005FR-3G C
Solar/Wind Harmer
2.138
946581AF1-322 GEN
Solar/Wind Harmer
5.283
24691005MDL-2G C
Solar/Wind Harmer
1.909
276668AB2-070 GEN1
Solar/Wind Harmer
1.127
276848AB2-070 GEN3
Solar/Wind Harmer
1.127
276849AB2-070 GEN2
Solar/Wind Harmer
1.127
276763AC1-053 GEN1
Solar/Wind Harmer
2.009
276764AC1-053 GEN2
Solar/Wind Harmer
2.009
270444AC2-157 GEN1
Solar/Wind Harmer
2.828
270445AC2-157 GEN2
Solar/Wind Harmer
2.828
944221AF1-090 GEN
Solar/Wind Harmer
5.52
274853TWINGROVE;U1
Solar/Wind Harmer
3.598
274854TWINGROVE;U2
Solar/Wind Harmer
3.523
276726Z2-087_GEN
Solar/Wind Harmer
3.942
959341AF2-225 GEN
Solar/Wind Harmer
7.478
959141AF2-205 GEN
Solar/Wind Harmer
3.01
958391AF2-133 GEN
Solar/Wind Harmer
4.501
970169AG2-114 GEN
Solar/Wind Harmer
4.887
274863CRW1-WTG
Solar/Wind Harmer
2.714
274864CRW2-WTG
Solar/Wind Harmer
2.714
971771AH1-392 GEN
Solar/Wind Harmer
4.311
965041AG1-368 GEN
Solar/Wind Harmer
4.761
270526AF1-158 GEN
Solar/Wind Harmer
2.156
972228AH1-698 GEN2
Adder
1.753
972227AH1-698 GEN1
Adder
1.234
972037AH1-567 GEN1
Adder
0.087
274800UNIV PARK;3U
Adder
2.756
274801UNIV PARK;4U
Adder
2.756
274827FISK ;RP
Adder
3.664
274728ELWOOD EC;5P
Adder
7.759
274731ELWOOD EC;2P
Adder
7.759
274733ELWOOD EC;3P
Adder
7.759
274735ELWOOD EC;4P
Adder
7.759
274687WILL CNTY;4U
Adder
13.159
274687WILL CNTY;4U
Adder
13.159
274675JOLIET 29;7U
Adder
14.438
274675JOLIET 29;7U
Adder
13.922
274775LINCOLN ;6U
Adder
3.967
274776LINCOLN ;7U
Adder
3.967
274777LINCOLN ;8U
Adder
3.967
274744AC1-111 GEN8
Adder
2.614
274746AC1-111 G10
Adder
2.614
961161AF2-407 GEN
50/50
56.483
24728705AND G3
50/50
11.18
24728505AND G1
50/50
5.346
24379505HDWTR1G C
Solar/Wind Harmer
19.751
270240V3-007_GEN2
Solar/Wind Harmer
15.453
270004AE1-209 GEN
Solar/Wind Harmer
10.625
970825AG2-519 GEN
Solar/Wind Harmer
9.513
946031AF1-268 GEN
Solar/Wind Harmer
13.978
962031AG1-047 GEN
Solar/Wind Harmer
4.334
957741AF2-068 GEN
Solar/Wind Harmer
21.5
944531AF1-118 GEN
Solar/Wind Harmer
43.67
965461AG1-414 GEN
Solar/Wind Harmer
2.803
970289AG2-191 GEN
Solar/Wind Harmer
0.949
247642Z2-115 C
Solar/Wind Harmer
0.072
970193AG2-126 GEN
Solar/Wind Harmer
10.152
270043AE2-236 GEN
Solar/Wind Harmer
3.554
965021AG1-366 GEN
Solar/Wind Harmer
1.27
24386205FR-12G C
Solar/Wind Harmer
2.317
270063AE2-323 C
Solar/Wind Harmer
1.145
24690905MDL-1G C
Solar/Wind Harmer
4.145
970781AG2-491 GEN
Solar/Wind Harmer
5.163
276785W4-005 GEN1
Solar/Wind Harmer
1.539
971993AH1-541 GEN
Solar/Wind Harmer
4.704
942481AE2-261 GEN
Solar/Wind Harmer
15.058
957381AF2-032 GEN
Solar/Wind Harmer
1.007
965091AG1-374 GEN
Solar/Wind Harmer
14.983
959611AF2-252 GEN
Solar/Wind Harmer
1.161
964401AG1-302 GEN
Solar/Wind Harmer
4.482
247643Z2-116 C
Solar/Wind Harmer
0.034
939351AE1-166 GEN
Solar/Wind Harmer
2.818
274724RIVER EC ;11
Adder
8.392
274814UNIV PK N;0U
Adder
2.394
274807UNIV PK N;3U
Adder
2.388
274811UNIV PK N;7U
Adder
2.373
274803UNIV PARK;6U
Adder
2.757
972038AH1-567 GEN2
Adder
0.172
274826FISK ;BP
Adder
5.17
274729ELWOOD EC;1P
Adder
7.759
274730ELWOOD EC;6P
Adder
7.759
274734ELWOOD EC;8P
Adder
7.759
274736ELWOOD EC;9P
Adder
7.759
972259AH1-714 GEN
Adder
8.99
274676JOLIET 29;8U
Adder
13.922
274772LINCOLN ;3U
Adder
3.967
274682WAUKEGAN ;7U
Adder
8.365
274760LEE CO EC;1U
Adder
4.269
274767LEE CO EC;8U
Adder
4.219
252524AE2-267 GEN
Solar/Wind Helper
0.838
252507AC2-088 GEN
Solar/Wind Helper
1.707
253394AE2-221_GEN
Solar/Wind Helper
1.56
270367AC2-061_GEN
Solar/Wind Helper
1.89
270186AC1-089 GEN
Solar/Wind Helper
0.826
960071AF2-298 GEN
Solar/Wind Helper
0.389
270518AE2-148 GEN
Solar/Wind Helper
7.411
276820AF1-078_GEN
Solar/Wind Helper
0.325
339243AC2-075 GEN1
Solar/Wind Helper
0.22
253325AC1-069 GEN
Solar/Wind Helper
0.572
972231SS25-0005
Solar/Wind Harmer
3.846
972181SS23-001
Solar/Wind Harmer
2.404
274752CRETE EC ;2U
Solar/Wind Harmer
1.981
274753CRETE EC ;3U
Solar/Wind Harmer
1.981
274823ROCKFORD ;21
Adder
8.975
972267AH1-718 GEN
Adder
1.906
253406AD2-031_GEN
Solar/Wind Helper
0.863
241972AD1-140 GEN
Solar/Wind Helper
2.854
270340AC2-060 GEN
Solar/Wind Helper
1.194
339216AC1-074 GEN
Solar/Wind Helper
0.954
253338AC1-165 GEN
Solar/Wind Helper
0.552
253343AC1-166 GEN
Solar/Wind Helper
0.552
945631AF1-228 GEN
Solar/Wind Helper
0.943
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.129
LAGNLTFEXP_LAGN->PJM
CLTF
4.233
TVALTFEXP_TVA->PJM
CLTF
1.546
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.609
MECLTFEXP_MEC->PJM
CLTF
7.098
SIGELTFEXP_SIGE->PJM
CLTF
0.251
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.549
NYPJM->LTFIMP_NY
CLTF
0.677
WECLTFEXP_WEC->PJM
CLTF
1.752
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.306
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.182

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.23 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2808.8
MW Contribution:
13.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
8.9
24726605LAWG1S
50/50
8.896
24726705LAWG2A
50/50
5.966
24726505LAWG1B
50/50
5.924
24726805LAWG2B
50/50
5.898
24729505KEY G4
50/50
9.047
270356AE2-297 GEN
Solar/Wind Harmer
11.188
945581AF1-223 GEN
Solar/Wind Harmer
7.594
958711AF2-162 GEN
Solar/Wind Harmer
1.516
964611AG1-324 GEN
Solar/Wind Harmer
5.798
961761AG1-017 GEN
Solar/Wind Harmer
0.613
247536S-71 GEN
Solar/Wind Harmer
5.469
270543AE2-219 C
Solar/Wind Harmer
13.066
971029AG2-637 GEN
Solar/Wind Harmer
18.762
970289AG2-191 GEN
Solar/Wind Harmer
2.349
963791AG1-232 GEN
Solar/Wind Harmer
11.705
270071AF1-092 GEN
Solar/Wind Harmer
10.756
963841AG1-237 GEN
Solar/Wind Harmer
6.201
959331AF2-224 GEN
Solar/Wind Harmer
5.463
970031AG2-029 GEN
Solar/Wind Harmer
13.609
24386405FR-21G C
Solar/Wind Harmer
2.325
24387005FR-3G C
Solar/Wind Harmer
2.138
946581AF1-322 GEN
Solar/Wind Harmer
5.283
24691005MDL-2G C
Solar/Wind Harmer
1.909
276668AB2-070 GEN1
Solar/Wind Harmer
1.127
276848AB2-070 GEN3
Solar/Wind Harmer
1.127
24726405LAWG1A
50/50
5.753
961171AF2-408 GEN
50/50
15.251
24728605AND G2
50/50
5.346
942081AE2-220 GEN
Solar/Wind Harmer
15.974
270209AC1-174_GEN
Solar/Wind Harmer
10.165
270437AC2-090 C
Solar/Wind Harmer
13.941
270239V3-007_GEN1
Solar/Wind Harmer
4.298
270005AE1-210 C O1
Solar/Wind Harmer
10.625
970825AG2-519 GEN
Solar/Wind Harmer
3.543
945371AF1-202 GEN
Solar/Wind Harmer
11.683
958861AF2-177 GEN
Solar/Wind Harmer
17.042
965651AG1-433 GEN
Solar/Wind Harmer
8.191
276903AD2-071 C
Solar/Wind Harmer
13.916
270594AE1-207 GEN
Solar/Wind Harmer
18.403
270032AE2-172
Solar/Wind Harmer
6.303
270222AC2-111 GEN
Solar/Wind Harmer
5.586
944031AF1-071 GEN
Solar/Wind Harmer
1.257
270024AE2-089 GEN
Solar/Wind Harmer
5.691
963741AG1-226 GEN
Solar/Wind Harmer
26.648
965011AG1-365 GEN
Solar/Wind Harmer
5.463
24385905FR-11G C
Solar/Wind Harmer
4.493
24386605FR-22G C
Solar/Wind Harmer
2.325
24791305MDL-5G
Solar/Wind Harmer
1.245
276686W4-005 GEN3
Solar/Wind Harmer
1.539
276621W2-048 GEN
Solar/Wind Harmer
3.16
965911AG1-460 GEN
Solar/Wind Harmer
0.703
940581AE2-045 GEN
Solar/Wind Harmer
5.097
971605AH1-302 GEN
Solar/Wind Harmer
4.358
276655WTG1_EQ
Solar/Wind Harmer
4.351
276656WTG2_EQ
Solar/Wind Harmer
0.576
939741AE1-205 GEN
Solar/Wind Harmer
9.97
964861AG1-349 GEN
Solar/Wind Harmer
3.888
971917AH1-482 GEN
Solar/Wind Harmer
4.486
958381AF2-132 GEN
Solar/Wind Harmer
4.482
24639705ELKHART HY
Adder
0.076
270055AF2-134 C O1
Solar/Wind Harmer
1.482
270216AD2-079_GEN
Solar/Wind Harmer
0.295
970373AG2-245 GEN
Solar/Wind Harmer
10.21
939401AE1-172 GEN
Solar/Wind Harmer
6.733
941551AE2-152 GEN
Solar/Wind Harmer
2.155
274723RIVER EC ;12
Adder
8.494
274812UNIV PK N;8U
Adder
2.373
274802UNIV PARK;5U
Adder
2.757
274732ELWOOD EC;7P
Adder
7.759
274674JOLIET 9 ;6U
Adder
7.256
274676JOLIET 29;8U
Adder
14.438
274773LINCOLN ;4U
Adder
3.967
274774LINCOLN ;5U
Adder
3.967
274745AC1-111 GEN9
Adder
2.614
274682WAUKEGAN ;7U
Adder
8.365
274828WAUKEGAN ;BP
Adder
5.138
274822ROCKFORD ;11
Adder
9.041
274761LEE CO EC;2U
Adder
4.269
274766LEE CO EC;7U
Adder
4.219
252510AF1-249 C
Solar/Wind Helper
0.565
253398AE2-221_GEN2
Solar/Wind Helper
1.56
339221AD2-048_GEN
Solar/Wind Helper
0.776
253333AC1-068 GEN
Solar/Wind Helper
0.572
274751CRETE EC ;1U
Solar/Wind Harmer
1.981
274754CRETE EC ;4U
Solar/Wind Harmer
1.981
247621Y3-024
50/50
0.342
24729405KEY G3
50/50
0.494
24729305KEY G2
50/50
0.486
24729205KEY G1
50/50
0.483
24728805RICHG1
50/50
4.622
24728905RICHG2
50/50
4.622
926881AC1-175 GEN
Solar/Wind Harmer
13.941
270383AD1-128 GEN
Solar/Wind Harmer
9.794
944541AF1-119 GEN
Solar/Wind Harmer
6.275
960971AF2-388 GEN
Solar/Wind Harmer
16.382
964611AG1-324 GEN
Solar/Wind Harmer
0.778
270031AE2-169
Solar/Wind Harmer
12.049
276849AB2-070 GEN2
Solar/Wind Harmer
1.127
276763AC1-053 GEN1
Solar/Wind Harmer
2.009
276764AC1-053 GEN2
Solar/Wind Harmer
2.009
270444AC2-157 GEN1
Solar/Wind Harmer
2.828
270445AC2-157 GEN2
Solar/Wind Harmer
2.828
944221AF1-090 GEN
Solar/Wind Harmer
5.52
274853TWINGROVE;U1
Solar/Wind Harmer
3.598
274854TWINGROVE;U2
Solar/Wind Harmer
3.523
276726Z2-087_GEN
Solar/Wind Harmer
3.942
959341AF2-225 GEN
Solar/Wind Harmer
7.478
959141AF2-205 GEN
Solar/Wind Harmer
3.01
958391AF2-133 GEN
Solar/Wind Harmer
4.501
970169AG2-114 GEN
Solar/Wind Harmer
4.887
274863CRW1-WTG
Solar/Wind Harmer
2.714
274864CRW2-WTG
Solar/Wind Harmer
2.714
971771AH1-392 GEN
Solar/Wind Harmer
4.311
965041AG1-368 GEN
Solar/Wind Harmer
4.761
270526AF1-158 GEN
Solar/Wind Harmer
2.156
972228AH1-698 GEN2
Adder
1.753
972227AH1-698 GEN1
Adder
1.234
972037AH1-567 GEN1
Adder
0.087
274800UNIV PARK;3U
Adder
2.756
274801UNIV PARK;4U
Adder
2.756
274827FISK ;RP
Adder
3.664
274728ELWOOD EC;5P
Adder
7.759
274731ELWOOD EC;2P
Adder
7.759
274733ELWOOD EC;3P
Adder
7.759
274735ELWOOD EC;4P
Adder
7.759
274687WILL CNTY;4U
Adder
13.159
274687WILL CNTY;4U
Adder
13.159
274675JOLIET 29;7U
Adder
14.438
274675JOLIET 29;7U
Adder
13.922
274775LINCOLN ;6U
Adder
3.967
274776LINCOLN ;7U
Adder
3.967
274777LINCOLN ;8U
Adder
3.967
274744AC1-111 GEN8
Adder
2.614
274746AC1-111 G10
Adder
2.614
274823ROCKFORD ;21
Adder
8.975
972267AH1-718 GEN
Adder
1.906
253406AD2-031_GEN
Solar/Wind Helper
0.863
241972AD1-140 GEN
Solar/Wind Helper
2.854
270340AC2-060 GEN
Solar/Wind Helper
1.194
339216AC1-074 GEN
Solar/Wind Helper
0.954
253338AC1-165 GEN
Solar/Wind Helper
0.552
253343AC1-166 GEN
Solar/Wind Helper
0.552
945631AF1-228 GEN
Solar/Wind Helper
0.943
961161AF2-407 GEN
50/50
56.483
24728705AND G3
50/50
11.18
24728505AND G1
50/50
5.346
24379505HDWTR1G C
Solar/Wind Harmer
19.751
270240V3-007_GEN2
Solar/Wind Harmer
15.453
270004AE1-209 GEN
Solar/Wind Harmer
10.625
970825AG2-519 GEN
Solar/Wind Harmer
9.513
946031AF1-268 GEN
Solar/Wind Harmer
13.978
962031AG1-047 GEN
Solar/Wind Harmer
4.334
957741AF2-068 GEN
Solar/Wind Harmer
21.5
944531AF1-118 GEN
Solar/Wind Harmer
43.67
965461AG1-414 GEN
Solar/Wind Harmer
2.803
970289AG2-191 GEN
Solar/Wind Harmer
0.949
247642Z2-115 C
Solar/Wind Harmer
0.072
970193AG2-126 GEN
Solar/Wind Harmer
10.152
270043AE2-236 GEN
Solar/Wind Harmer
3.554
965021AG1-366 GEN
Solar/Wind Harmer
1.27
24386205FR-12G C
Solar/Wind Harmer
2.317
270063AE2-323 C
Solar/Wind Harmer
1.145
24690905MDL-1G C
Solar/Wind Harmer
4.145
970781AG2-491 GEN
Solar/Wind Harmer
5.163
276785W4-005 GEN1
Solar/Wind Harmer
1.539
971993AH1-541 GEN
Solar/Wind Harmer
4.704
942481AE2-261 GEN
Solar/Wind Harmer
15.058
957381AF2-032 GEN
Solar/Wind Harmer
1.007
965091AG1-374 GEN
Solar/Wind Harmer
14.983
959611AF2-252 GEN
Solar/Wind Harmer
1.161
964401AG1-302 GEN
Solar/Wind Harmer
4.482
247643Z2-116 C
Solar/Wind Harmer
0.034
939351AE1-166 GEN
Solar/Wind Harmer
2.818
274724RIVER EC ;11
Adder
8.392
274814UNIV PK N;0U
Adder
2.394
274807UNIV PK N;3U
Adder
2.388
274811UNIV PK N;7U
Adder
2.373
274803UNIV PARK;6U
Adder
2.757
972038AH1-567 GEN2
Adder
0.172
274826FISK ;BP
Adder
5.17
274729ELWOOD EC;1P
Adder
7.759
274730ELWOOD EC;6P
Adder
7.759
274734ELWOOD EC;8P
Adder
7.759
274736ELWOOD EC;9P
Adder
7.759
972259AH1-714 GEN
Adder
8.99
274676JOLIET 29;8U
Adder
13.922
274772LINCOLN ;3U
Adder
3.967
274682WAUKEGAN ;7U
Adder
8.365
274760LEE CO EC;1U
Adder
4.269
274767LEE CO EC;8U
Adder
4.219
252524AE2-267 GEN
Solar/Wind Helper
0.838
252507AC2-088 GEN
Solar/Wind Helper
1.707
253394AE2-221_GEN
Solar/Wind Helper
1.56
270367AC2-061_GEN
Solar/Wind Helper
1.89
270186AC1-089 GEN
Solar/Wind Helper
0.826
960071AF2-298 GEN
Solar/Wind Helper
0.389
270518AE2-148 GEN
Solar/Wind Helper
7.411
276820AF1-078_GEN
Solar/Wind Helper
0.325
339243AC2-075 GEN1
Solar/Wind Helper
0.22
253325AC1-069 GEN
Solar/Wind Helper
0.572
972231SS25-0005
Solar/Wind Harmer
3.846
972181SS23-001
Solar/Wind Harmer
2.404
274752CRETE EC ;2U
Solar/Wind Harmer
1.981
274753CRETE EC ;3U
Solar/Wind Harmer
1.981
270599AE1-208 GEN
Solar/Wind Harmer
12.049
24725505WLD G2 C
Solar/Wind Harmer
5.843
24699105WLD G1 C
Solar/Wind Harmer
5.775
270201AC2-176 GEN
Solar/Wind Harmer
7.367
970883AG2-550 GEN
Solar/Wind Harmer
13.066
970885AG2-551 GEN
Solar/Wind Harmer
3.039
970291AG2-192 GEN
Solar/Wind Harmer
1.607
970291AG2-192 GEN
Solar/Wind Harmer
0.518
942221AE2-234 GEN
Solar/Wind Harmer
3.933
945391AF1-204 GEN
Solar/Wind Harmer
9.432
970241AG2-163 GEN
Solar/Wind Harmer
14.805
24387305FR-4G C
Solar/Wind Harmer
2.746
966841AG1-555 GEN
Solar/Wind Harmer
1.357
270180AB1-006 GEN1
Solar/Wind Harmer
3.713
24697605MDL-3G C
Solar/Wind Harmer
1.903
24755605MDL-5G
Solar/Wind Harmer
1.245
24697905MDL-4G C
Solar/Wind Harmer
1.185
270181AB1-006 GEN2
Solar/Wind Harmer
0.369
274880W4-005 GEN4
Solar/Wind Harmer
1.539
276174W4-005 GEN2
Solar/Wind Harmer
1.539
276615X2-022 GEN
Solar/Wind Harmer
0.993
276838X2-022 GEN2
Solar/Wind Harmer
0.118
945421AF1-207 GEN
Solar/Wind Harmer
7.096
957841AF2-078 GEN
Solar/Wind Harmer
3.055
276916AD2-100_GEN
Solar/Wind Harmer
10.583
276911AD2-131_GEN
Solar/Wind Harmer
2.139
960611AF2-352 GEN
Solar/Wind Harmer
1.161
942111AE2-223 GEN
Solar/Wind Harmer
4.087
247620Y3-023
Adder
0.229
270535AF1-215 GEN1
Solar/Wind Harmer
2.223
270536AF1-215 GEN2
Solar/Wind Harmer
2.223
944231AF1-091 GEN
Solar/Wind Harmer
8.554
276897AD1-100 C
Solar/Wind Harmer
22.071
274805UNIV PK N;1U
Adder
2.378
274808UNIV PK N;4U
Adder
2.363
274674JOLIET 9 ;6U
Adder
7.256
274770LINCOLN ;1U
Adder
3.967
274771LINCOLN ;2U
Adder
3.967
274696ROCKY RD ;4P
Adder
5.308
274695ROCKY RD ;2P
Adder
5.185
274693ROCKY RD ;1P
Adder
5.134
274697ROCKY RD ;3P
Adder
1.409
274683WAUKEGAN ;8U
Adder
9.803
274683WAUKEGAN ;8U
Adder
8.263
972235AH1-702 GEN1
Adder
1.161
972236AH1-702 GEN2
Adder
1.009
274764LEE CO EC;5U
Adder
4.279
274765LEE CO EC;6U
Adder
4.279
274762LEE CO EC;3U
Adder
4.269
274763LEE CO EC;4U
Adder
4.229
252509AD1-136 GEN
Solar/Wind Helper
0.244
25183208HLCRTG
Solar/Wind Helper
2.612
962581AG1-107 GEN
Solar/Wind Helper
0.944
961491AF2-440 GEN
Solar/Wind Helper
0.039
253415AE1-040 GEN
Solar/Wind Helper
0.542
253378AE2-206_GEN
Solar/Wind Helper
0.696
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.129
LAGNLTFEXP_LAGN->PJM
CLTF
4.233
TVALTFEXP_TVA->PJM
CLTF
1.546
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.609
MECLTFEXP_MEC->PJM
CLTF
7.098
SIGELTFEXP_SIGE->PJM
CLTF
0.251
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.549
NYPJM->LTFIMP_NY
CLTF
0.677
WECLTFEXP_WEC->PJM
CLTF
1.752
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.306
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.182

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.63 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2609.67
MW Contribution:
4.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
5.175
24726605LAWG1S
50/50
5.173
24726705LAWG2A
50/50
3.469
24726505LAWG1B
50/50
3.445
24726805LAWG2B
50/50
3.43
24729505KEY G4
50/50
6.226
270356AE2-297 GEN
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.089
964611AG1-324 GEN
Solar/Wind Harmer
2.474
970289AG2-191 GEN
Solar/Wind Harmer
1.136
247536S-71 GEN
Solar/Wind Harmer
0.216
270543AE2-219 C
Solar/Wind Harmer
3.467
971029AG2-637 GEN
Solar/Wind Harmer
6.645
270071AF1-092 GEN
Solar/Wind Harmer
8.015
963791AG1-232 GEN
Solar/Wind Harmer
5.573
963841AG1-237 GEN
Solar/Wind Harmer
1.664
24386405FR-21G C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.16
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.138
276848AB2-070 GEN3
Solar/Wind Harmer
0.137
276849AB2-070 GEN2
Solar/Wind Harmer
0.138
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.675
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
3.478
274775LINCOLN ;6U
Adder
4.193
274776LINCOLN ;7U
Adder
4.193
274777LINCOLN ;8U
Adder
4.193
960681AF2-359 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
1.832
972227AH1-698 GEN1
Adder
1.29
960591AF2-350 GEN
Solar/Wind Harmer
3.45
944221AF1-090 GEN
Solar/Wind Harmer
2.022
972037AH1-567 GEN1
Adder
0.09
274800UNIV PARK;3U
Adder
2.879
274801UNIV PARK;4U
Adder
2.879
274827FISK ;RP
Adder
3.829
970833AG2-524 GEN
Solar/Wind Harmer
3.784
970833AG2-524 GEN
Solar/Wind Harmer
2.522
274728ELWOOD EC;5P
Adder
8.1
274731ELWOOD EC;2P
Adder
8.1
274733ELWOOD EC;3P
Adder
8.1
274735ELWOOD EC;4P
Adder
8.1
274687WILL CNTY;4U
Adder
13.754
274687WILL CNTY;4U
Adder
13.754
274675JOLIET 29;7U
Adder
15.095
274675JOLIET 29;7U
Adder
14.556
274744AC1-111 GEN8
Adder
2.736
274746AC1-111 G10
Adder
2.736
970073AG2-061 GEN
Solar/Wind Harmer
1.138
270526AF1-158 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.579
971771AH1-392 GEN
Solar/Wind Harmer
3.397
970031AG2-029 GEN
Solar/Wind Harmer
1.836
276861AD2-134 GEN
Solar/Wind Harmer
0.06
276863AD2-134 GEN
Solar/Wind Harmer
0.06
971675AH1-338 GEN
Solar/Wind Harmer
1.313
274877BISHOP HL;1U
Solar/Wind Harmer
0.112
971411AH1-196 GEN
Solar/Wind Harmer
5.046
971171AH1-044 GEN
Solar/Wind Harmer
6.717
274823ROCKFORD ;21
Adder
9.354
274856ECOGROVE ;U1
Solar/Wind Harmer
0.078
971681AH1-341 GEN
Solar/Wind Harmer
5.372
276741O09 GEN1
Solar/Wind Harmer
0.118
972267AH1-718 GEN
Adder
1.98
946321AF1-296 GEN
Solar/Wind Harmer
1.835
959331AF2-224 GEN
Solar/Wind Harmer
2.126
241972AD1-140 GEN
Solar/Wind Helper
3.462
253406AD2-031_GEN
Solar/Wind Helper
0.908
270340AC2-060 GEN
Solar/Wind Helper
1.186
253338AC1-165 GEN
Solar/Wind Helper
0.584
253343AC1-166 GEN
Solar/Wind Helper
0.584
241973AD2-163_GEN1
Solar/Wind Helper
1.034
241974AD2-163_GEN2
Solar/Wind Helper
1.034
945631AF1-228 GEN
Solar/Wind Helper
1.084
241955AC1-078 GEN
Solar/Wind Helper
0.981
961161AF2-407 GEN
50/50
36.206
24728705AND G3
50/50
7.209
24728505AND G1
50/50
3.447
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.847
970825AG2-519 GEN
Solar/Wind Harmer
5.553
946031AF1-268 GEN
Solar/Wind Harmer
6.921
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.138
944531AF1-118 GEN
Solar/Wind Harmer
27.23
970289AG2-191 GEN
Solar/Wind Harmer
0.658
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
6.211
270043AE2-236 GEN
Solar/Wind Harmer
2.461
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.696
964401AG1-302 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.619
971347AH1-153 GEN
Solar/Wind Harmer
1.751
965091AG1-374 GEN
Solar/Wind Harmer
10.482
959611AF2-252 GEN
Solar/Wind Harmer
1.165
274772LINCOLN ;3U
Adder
4.193
939351AE1-166 GEN
Solar/Wind Harmer
0
957381AF2-032 GEN
Solar/Wind Harmer
0.783
942481AE2-261 GEN
Solar/Wind Harmer
10.33
274724RIVER EC ;11
Adder
8.762
274752CRETE EC ;2U
Adder
4.076
274753CRETE EC ;3U
Adder
4.076
274887GEN-1.85
Solar/Wind Harmer
0.09
276843GEN-1.7
Solar/Wind Harmer
0.112
276806AD2-047 C O1
Solar/Wind Harmer
1.955
274814UNIV PK N;0U
Adder
2.497
274807UNIV PK N;3U
Adder
2.491
274811UNIV PK N;7U
Adder
2.475
972259AH1-714 GEN
Adder
9.423
274803UNIV PARK;6U
Adder
2.879
972038AH1-567 GEN2
Adder
0.18
274826FISK ;BP
Adder
5.402
970707AG2-453 GEN
Solar/Wind Harmer
11.245
274729ELWOOD EC;1P
Adder
8.1
274730ELWOOD EC;6P
Adder
8.1
274734ELWOOD EC;8P
Adder
8.1
274736ELWOOD EC;9P
Adder
8.1
274676JOLIET 29;8U
Adder
14.556
274862TOP CROP ;2U
Solar/Wind Harmer
0.462
943121AE2-341 GEN
Solar/Wind Harmer
5.725
943591AF1-030 GEN
Solar/Wind Harmer
3.807
276868AE1-113 GEN
Solar/Wind Harmer
0.682
274879MINONK ;1U
Solar/Wind Harmer
0.142
970571AG2-364 GEN
Solar/Wind Harmer
6.786
274682WAUKEGAN ;7U
Adder
8.741
946671AF1-331 GEN
Solar/Wind Harmer
0.359
274855GSG-6 ;RU
Solar/Wind Harmer
0.123
274850MENDOTA H;RU
Solar/Wind Harmer
0.039
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.112
959091AF2-200 GEN
Solar/Wind Harmer
6.717
270063AE2-323 C
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.439
274767LEE CO EC;8U
Adder
4.387
270505AE1-170 C O1
Solar/Wind Harmer
3.482
945111AF1-176 GEN
Solar/Wind Harmer
2.686
965931AG1-462 GEN
Solar/Wind Harmer
8.333
971087AG2-675 GEN
Solar/Wind Harmer
1.743
965021AG1-366 GEN
Solar/Wind Harmer
1.012
252524AE2-267 GEN
Solar/Wind Helper
1.058
960071AF2-298 GEN
Solar/Wind Helper
0.562
253394AE2-221_GEN
Solar/Wind Helper
1.605
252507AC2-088 GEN
Solar/Wind Helper
1.361
276820AF1-078_GEN
Solar/Wind Helper
0.471
270367AC2-061_GEN
Solar/Wind Helper
1.959
270186AC1-089 GEN
Solar/Wind Helper
0.816
270518AE2-148 GEN
Solar/Wind Helper
8.492
253325AC1-069 GEN
Solar/Wind Helper
0.605
24726405LAWG1A
50/50
3.345
961171AF2-408 GEN
50/50
9.629
24728605AND G2
50/50
3.447
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.823
970773AG2-487 GEN
Solar/Wind Harmer
1.792
270005AE1-210 C O1
Solar/Wind Harmer
1.847
945371AF1-202 GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.617
958861AF2-177 GEN
Solar/Wind Harmer
3.107
965651AG1-433 GEN
Solar/Wind Harmer
2.041
276903AD2-071 C
Solar/Wind Harmer
7.229
270594AE1-207 GEN
Solar/Wind Harmer
7.11
270032AE2-172
Solar/Wind Harmer
4.232
270024AE2-089 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
9.25
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.534
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.671
958381AF2-132 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.43
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.9
276621W2-048 GEN
Solar/Wind Harmer
0.174
939401AE1-172 GEN
Solar/Wind Harmer
2.598
274773LINCOLN ;4U
Adder
4.193
274774LINCOLN ;5U
Adder
4.193
941551AE2-152 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.691
274723RIVER EC ;12
Adder
8.866
274751CRETE EC ;1U
Adder
4.076
274754CRETE EC ;4U
Adder
4.076
274812UNIV PK N;8U
Adder
2.475
274802UNIV PARK;5U
Adder
2.879
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.1
274674JOLIET 9 ;6U
Adder
7.581
274676JOLIET 29;8U
Adder
15.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.556
274861TOP CROP ;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.792
274745AC1-111 GEN9
Adder
2.736
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.398
970569AG2-363 GEN
Solar/Wind Harmer
10.179
274682WAUKEGAN ;7U
Adder
8.741
274828WAUKEGAN ;BP
Adder
5.369
962781AG1-127 GEN
Solar/Wind Harmer
3.219
274872LEEDK;1U
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.133
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.074
957471AF2-041 GEN
Solar/Wind Harmer
10.076
959081AF2-199 GEN
Solar/Wind Harmer
3.359
971067AG2-660 GEN
Solar/Wind Harmer
1.12
970091AG2-072 GEN
Adder
36.89
274822ROCKFORD ;11
Adder
9.422
970819AG2-516 GEN
Solar/Wind Harmer
4.01
276708O09 GEN2
Solar/Wind Harmer
0.118
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.439
274766LEE CO EC;7U
Adder
4.387
957891AF2-083 GEN
Solar/Wind Harmer
5.533
945111AF1-176 GEN
Solar/Wind Harmer
5.913
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.71
965011AG1-365 GEN
Solar/Wind Harmer
3.036
252510AF1-249 C
Solar/Wind Helper
0.649
253398AE2-221_GEN2
Solar/Wind Helper
1.605
253333AC1-068 GEN
Solar/Wind Helper
0.605
25194708EBND2
50/50
6.282
24729405KEY G3
50/50
0.34
24729305KEY G2
50/50
0.334
24729205KEY G1
50/50
0.332
247621Y3-024
50/50
0.2
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.465
960971AF2-388 GEN
Solar/Wind Harmer
4.082
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.665
270599AE1-208 GEN
Solar/Wind Harmer
6.109
270383AD1-128 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.047
964611AG1-324 GEN
Solar/Wind Harmer
0.476
270201AC2-176 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.777
970291AG2-192 GEN
Solar/Wind Harmer
0.359
942221AE2-234 GEN
Solar/Wind Harmer
2.113
970883AG2-550 GEN
Solar/Wind Harmer
4.953
970885AG2-551 GEN
Solar/Wind Harmer
1.651
945391AF1-204 GEN
Solar/Wind Harmer
4.4
970241AG2-163 GEN
Solar/Wind Harmer
2.28
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.427
971587AH1-292 GEN
Solar/Wind Harmer
2.74
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24728805RICHG1
Adder
1.91
24728905RICHG2
Adder
1.91
970349AG2-230 GEN
Solar/Wind Harmer
5.254
942111AE2-223 GEN
Solar/Wind Harmer
1.137
960611AF2-352 GEN
Solar/Wind Harmer
1.165
276615X2-022 GEN
Solar/Wind Harmer
0.036
276838X2-022 GEN2
Solar/Wind Harmer
0.196
274770LINCOLN ;1U
Adder
4.193
274771LINCOLN ;2U
Adder
4.193
276897AD1-100 C
Solar/Wind Harmer
8.649
965681AG1-436 GEN
Solar/Wind Harmer
4.321
965791AG1-447 GEN
Solar/Wind Harmer
3.169
276916AD2-100_GEN
Solar/Wind Harmer
7.252
276911AD2-131_GEN
Solar/Wind Harmer
0.478
274888KELLY CRK;1U
Solar/Wind Harmer
0.201
276776AD2-060 GEN
Solar/Wind Harmer
0.368
958011AF2-095 GEN
Solar/Wind Harmer
4.968
970941AG2-585 GEN
Solar/Wind Harmer
1.898
274805UNIV PK N;1U
Adder
2.48
274808UNIV PK N;4U
Adder
2.464
276893AG1-478 C
Solar/Wind Harmer
0.229
274674JOLIET 9 ;6U
Adder
7.581
276901AD2-066 C O1
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.132
958491AF2-143 GEN
Solar/Wind Harmer
5.119
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.549
274695ROCKY RD ;2P
Adder
5.421
274693ROCKY RD ;1P
Adder
5.368
274697ROCKY RD ;3P
Adder
1.473
274683WAUKEGAN ;8U
Adder
10.242
274683WAUKEGAN ;8U
Adder
8.634
962691AG1-118 GEN
Solar/Wind Harmer
10.16
276645AC1-214 GEN1
Solar/Wind Harmer
0.133
971341AH1-150 GEN
Solar/Wind Harmer
6.717
971343AH1-151 GEN
Solar/Wind Harmer
6.717
972235AH1-702 GEN1
Adder
1.209
972236AH1-702 GEN2
Adder
1.051
247620Y3-023
Adder
0.221
938861AE1-114 GEN
Solar/Wind Harmer
1.89
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.537
274764LEE CO EC;5U
Adder
4.449
274765LEE CO EC;6U
Adder
4.449
274762LEE CO EC;3U
Adder
4.439
274763LEE CO EC;4U
Adder
4.397
961051AF2-396 GEN
Solar/Wind Harmer
6.579
961051AF2-396 GEN
Solar/Wind Harmer
4.386
25183208HLCRTG
Solar/Wind Helper
2.475
252509AD1-136 GEN
Solar/Wind Helper
0.194
253378AE2-206_GEN
Solar/Wind Helper
1.008
962581AG1-107 GEN
Solar/Wind Helper
1.008
961491AF2-440 GEN
Solar/Wind Helper
0.041
253349AC2-067 GEN
Solar/Wind Helper
0.267
253400AC2-068 GEN
Solar/Wind Helper
0.107
253415AE1-040 GEN
Solar/Wind Helper
0.551
253383AE2-342_GEN
Solar/Wind Helper
0.473
LAGNLTFEXP_LAGN->PJM
CLTF
4.89
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.583
TVALTFEXP_TVA->PJM
CLTF
1.97
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.493
MECLTFEXP_MEC->PJM
CLTF
7.337
SIGELTFEXP_SIGE->PJM
CLTF
0.239
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.525
NYPJM->LTFIMP_NY
CLTF
0.654
LGEELTFEXP_LGEE->PJM
CLTF
1.45
WECLTFEXP_WEC->PJM
CLTF
1.827
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.66 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2471.36
MW Contribution:
8.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726405LAWG1A
50/50
3.987
961171AF2-408 GEN
50/50
10.898
24728605AND G2
50/50
3.896
942081AE2-220 GEN
Solar/Wind Harmer
11.184
270209AC1-174_GEN
Solar/Wind Harmer
7.117
270437AC2-090 C
Solar/Wind Harmer
9.761
270239V3-007_GEN1
Solar/Wind Harmer
3.009
270005AE1-210 C O1
Solar/Wind Harmer
7.479
945371AF1-202 GEN
Solar/Wind Harmer
8.257
970825AG2-519 GEN
Solar/Wind Harmer
2.478
958861AF2-177 GEN
Solar/Wind Harmer
12.07
965651AG1-433 GEN
Solar/Wind Harmer
5.808
276903AD2-071 C
Solar/Wind Harmer
10.145
270594AE1-207 GEN
Solar/Wind Harmer
13.398
270032AE2-172
Solar/Wind Harmer
4.588
270024AE2-089 GEN
Solar/Wind Harmer
3.883
270222AC2-111 GEN
Solar/Wind Harmer
2.921
24726905LAWG2S
50/50
6.169
24726605LAWG1S
50/50
6.166
24726705LAWG2A
50/50
4.135
24726505LAWG1B
50/50
4.106
24726805LAWG2B
50/50
4.088
24729505KEY G4
50/50
6.445
270356AE2-297 GEN
Solar/Wind Harmer
7.795
945581AF1-223 GEN
Solar/Wind Harmer
5.367
958711AF2-162 GEN
Solar/Wind Harmer
1.075
964611AG1-324 GEN
Solar/Wind Harmer
3.96
961761AG1-017 GEN
Solar/Wind Harmer
0.417
970289AG2-191 GEN
Solar/Wind Harmer
1.741
247536S-71 GEN
Solar/Wind Harmer
3.572
270543AE2-219 C
Solar/Wind Harmer
8.26
971029AG2-637 GEN
Solar/Wind Harmer
11.382
963791AG1-232 GEN
Solar/Wind Harmer
8.055
270071AF1-092 GEN
Solar/Wind Harmer
8.272
270444AC2-157 GEN1
Solar/Wind Harmer
3.044
270445AC2-157 GEN2
Solar/Wind Harmer
3.044
963841AG1-237 GEN
Solar/Wind Harmer
5.767
24386405FR-21G C
Solar/Wind Harmer
2.189
24387005FR-3G C
Solar/Wind Harmer
2.013
946581AF1-322 GEN
Solar/Wind Harmer
5.003
24691005MDL-2G C
Solar/Wind Harmer
1.808
944221AF1-090 GEN
Solar/Wind Harmer
5.208
276668AB2-070 GEN1
Solar/Wind Harmer
1.043
276848AB2-070 GEN3
Solar/Wind Harmer
1.043
276849AB2-070 GEN2
Solar/Wind Harmer
1.043
276763AC1-053 GEN1
Solar/Wind Harmer
1.862
276764AC1-053 GEN2
Solar/Wind Harmer
1.862
959141AF2-205 GEN
Solar/Wind Harmer
2.809
958391AF2-133 GEN
Solar/Wind Harmer
4.185
274853TWINGROVE;U1
Solar/Wind Harmer
3.304
274854TWINGROVE;U2
Solar/Wind Harmer
3.235
276726Z2-087_GEN
Solar/Wind Harmer
3.608
959341AF2-225 GEN
Solar/Wind Harmer
6.844
970169AG2-114 GEN
Solar/Wind Harmer
4.452
274863CRW1-WTG
Solar/Wind Harmer
2.467
274864CRW2-WTG
Solar/Wind Harmer
2.467
926823AC1-168 GEN
Solar/Wind Harmer
1.854
241972AD1-140 GEN
Solar/Wind Helper
3.411
253406AD2-031_GEN
Solar/Wind Helper
0.947
270340AC2-060 GEN
Solar/Wind Helper
1.277
253338AC1-165 GEN
Solar/Wind Helper
0.593
253343AC1-166 GEN
Solar/Wind Helper
0.593
945631AF1-228 GEN
Solar/Wind Helper
1.063
241973AD2-163_GEN1
Solar/Wind Helper
0.965
241974AD2-163_GEN2
Solar/Wind Helper
0.965
339216AC1-074 GEN
Solar/Wind Helper
0.844
241955AC1-078 GEN
Solar/Wind Helper
0.93
944031AF1-071 GEN
Solar/Wind Harmer
0.657
963741AG1-226 GEN
Solar/Wind Harmer
24.533
24385905FR-11G C
Solar/Wind Harmer
4.23
24386605FR-22G C
Solar/Wind Harmer
2.189
24791305MDL-5G
Solar/Wind Harmer
1.179
970091AG2-072 GEN
Adder
36.849
965911AG1-460 GEN
Solar/Wind Harmer
0.658
276686W4-005 GEN3
Solar/Wind Harmer
1.425
276621W2-048 GEN
Solar/Wind Harmer
2.936
940581AE2-045 GEN
Solar/Wind Harmer
4.779
971605AH1-302 GEN
Solar/Wind Harmer
4.087
964861AG1-349 GEN
Solar/Wind Harmer
3.601
971917AH1-482 GEN
Solar/Wind Harmer
4.154
958381AF2-132 GEN
Solar/Wind Harmer
4.147
276655WTG1_EQ
Solar/Wind Harmer
3.982
276656WTG2_EQ
Solar/Wind Harmer
0.527
939741AE1-205 GEN
Solar/Wind Harmer
9.125
270055AF2-134 C O1
Solar/Wind Harmer
1.357
970373AG2-245 GEN
Solar/Wind Harmer
9.263
939401AE1-172 GEN
Solar/Wind Harmer
6.105
274848CAMPGROVE;RU
Solar/Wind Harmer
2.786
276646AC1-214 GEN2
Solar/Wind Harmer
0.578
252510AF1-249 C
Solar/Wind Helper
0.646
253398AE2-221_GEN2
Solar/Wind Helper
1.675
253333AC1-068 GEN
Solar/Wind Helper
0.614
339221AD2-048_GEN
Solar/Wind Helper
0.683
961161AF2-407 GEN
50/50
40.787
24728705AND G3
50/50
8.148
24728505AND G1
50/50
3.896
24379505HDWTR1G C
Solar/Wind Harmer
13.828
270240V3-007_GEN2
Solar/Wind Harmer
10.819
270004AE1-209 GEN
Solar/Wind Harmer
7.479
970825AG2-519 GEN
Solar/Wind Harmer
6.654
946031AF1-268 GEN
Solar/Wind Harmer
9.699
962031AG1-047 GEN
Solar/Wind Harmer
2.945
957741AF2-068 GEN
Solar/Wind Harmer
14.611
965461AG1-414 GEN
Solar/Wind Harmer
2.078
970289AG2-191 GEN
Solar/Wind Harmer
0.703
944531AF1-118 GEN
Solar/Wind Harmer
31.168
247642Z2-115 C
Solar/Wind Harmer
0.054
970193AG2-126 GEN
Solar/Wind Harmer
9.071
24386205FR-12G C
Solar/Wind Harmer
2.181
24690905MDL-1G C
Solar/Wind Harmer
3.925
970781AG2-491 GEN
Solar/Wind Harmer
4.89
270043AE2-236 GEN
Solar/Wind Harmer
2.678
942481AE2-261 GEN
Solar/Wind Harmer
14.096
276785W4-005 GEN1
Solar/Wind Harmer
1.425
971993AH1-541 GEN
Solar/Wind Harmer
4.354
957381AF2-032 GEN
Solar/Wind Harmer
0.942
965091AG1-374 GEN
Solar/Wind Harmer
13.758
959611AF2-252 GEN
Solar/Wind Harmer
1.067
964401AG1-302 GEN
Solar/Wind Harmer
4.147
274851PROVIDENC;RU
Solar/Wind Harmer
1.228
274849CRESCENT ;1U
Solar/Wind Harmer
0.797
252524AE2-267 GEN
Solar/Wind Helper
1.024
252507AC2-088 GEN
Solar/Wind Helper
1.663
253394AE2-221_GEN
Solar/Wind Helper
1.675
960071AF2-298 GEN
Solar/Wind Helper
0.538
270367AC2-061_GEN
Solar/Wind Helper
2.061
276820AF1-078_GEN
Solar/Wind Helper
0.44
270186AC1-089 GEN
Solar/Wind Helper
0.873
270518AE2-148 GEN
Solar/Wind Helper
8.43
253325AC1-069 GEN
Solar/Wind Helper
0.614
339243AC2-075 GEN1
Solar/Wind Helper
0.194
25194708EBND2
50/50
7.996
24729405KEY G3
50/50
0.352
24729305KEY G2
50/50
0.346
24729205KEY G1
50/50
0.344
247621Y3-024
50/50
0.226
926881AC1-175 GEN
Solar/Wind Harmer
9.761
270383AD1-128 GEN
Solar/Wind Harmer
6.5
944541AF1-119 GEN
Solar/Wind Harmer
4.45
960971AF2-388 GEN
Solar/Wind Harmer
11.617
24725505WLD G2 C
Solar/Wind Harmer
4.224
24699105WLD G1 C
Solar/Wind Harmer
4.175
270031AE2-169
Solar/Wind Harmer
8.504
270599AE1-208 GEN
Solar/Wind Harmer
8.504
964611AG1-324 GEN
Solar/Wind Harmer
0.531
270201AC2-176 GEN
Solar/Wind Harmer
5.006
970291AG2-192 GEN
Solar/Wind Harmer
1.191
970291AG2-192 GEN
Solar/Wind Harmer
0.384
970883AG2-550 GEN
Solar/Wind Harmer
8.26
970885AG2-551 GEN
Solar/Wind Harmer
1.921
942221AE2-234 GEN
Solar/Wind Harmer
2.761
24728805RICHG1
Adder
2.466
24728905RICHG2
Adder
2.466
945391AF1-204 GEN
Solar/Wind Harmer
8.428
970241AG2-163 GEN
Solar/Wind Harmer
13.629
24387305FR-4G C
Solar/Wind Harmer
2.585
966841AG1-555 GEN
Solar/Wind Harmer
1.277
270180AB1-006 GEN1
Solar/Wind Harmer
3.517
24697605MDL-3G C
Solar/Wind Harmer
1.802
24755605MDL-5G
Solar/Wind Harmer
1.179
24697905MDL-4G C
Solar/Wind Harmer
1.122
270181AB1-006 GEN2
Solar/Wind Harmer
0.35
945421AF1-207 GEN
Solar/Wind Harmer
6.736
957841AF2-078 GEN
Solar/Wind Harmer
2.9
276916AD2-100_GEN
Solar/Wind Harmer
9.924
276911AD2-131_GEN
Solar/Wind Harmer
2.006
274880W4-005 GEN4
Solar/Wind Harmer
1.425
276174W4-005 GEN2
Solar/Wind Harmer
1.425
276615X2-022 GEN
Solar/Wind Harmer
0.922
276838X2-022 GEN2
Solar/Wind Harmer
0.11
960611AF2-352 GEN
Solar/Wind Harmer
1.067
942111AE2-223 GEN
Solar/Wind Harmer
3.74
270535AF1-215 GEN1
Solar/Wind Harmer
2.036
270536AF1-215 GEN2
Solar/Wind Harmer
2.036
276645AC1-214 GEN1
Solar/Wind Harmer
0.578
25183208HLCRTG
Solar/Wind Helper
2.686
252509AD1-136 GEN
Solar/Wind Helper
0.238
253378AE2-206_GEN
Solar/Wind Helper
0.943
962581AG1-107 GEN
Solar/Wind Helper
1.056
961491AF2-440 GEN
Solar/Wind Helper
0.043
253415AE1-040 GEN
Solar/Wind Helper
0.585
253349AC2-067 GEN
Solar/Wind Helper
0.246
253400AC2-068 GEN
Solar/Wind Helper
0.099
253383AE2-342_GEN
Solar/Wind Helper
0.434
LAGNLTFEXP_LAGN->PJM
CLTF
4.676
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.277
TVALTFEXP_TVA->PJM
CLTF
1.91
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.74
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.455
MECLTFEXP_MEC->PJM
CLTF
6.681
SIGELTFEXP_SIGE->PJM
CLTF
0.259
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.796
NYPJM->LTFIMP_NY
CLTF
0.614
LGEELTFEXP_LGEE->PJM
CLTF
1.6
WECLTFEXP_WEC->PJM
CLTF
1.598
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.039
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P7-1_#485___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#485___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.66 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2471.23
MW Contribution:
8.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726405LAWG1A
50/50
3.987
961171AF2-408 GEN
50/50
10.898
24728605AND G2
50/50
3.896
942081AE2-220 GEN
Solar/Wind Harmer
11.184
270209AC1-174_GEN
Solar/Wind Harmer
7.117
270437AC2-090 C
Solar/Wind Harmer
9.761
270239V3-007_GEN1
Solar/Wind Harmer
3.009
270005AE1-210 C O1
Solar/Wind Harmer
7.479
945371AF1-202 GEN
Solar/Wind Harmer
8.257
970825AG2-519 GEN
Solar/Wind Harmer
2.478
958861AF2-177 GEN
Solar/Wind Harmer
12.07
965651AG1-433 GEN
Solar/Wind Harmer
5.808
276903AD2-071 C
Solar/Wind Harmer
10.145
270594AE1-207 GEN
Solar/Wind Harmer
13.398
270032AE2-172
Solar/Wind Harmer
4.588
270024AE2-089 GEN
Solar/Wind Harmer
3.883
270222AC2-111 GEN
Solar/Wind Harmer
2.921
944031AF1-071 GEN
Solar/Wind Harmer
0.657
963741AG1-226 GEN
Solar/Wind Harmer
24.533
24385905FR-11G C
Solar/Wind Harmer
4.23
24386605FR-22G C
Solar/Wind Harmer
2.189
24791305MDL-5G
Solar/Wind Harmer
1.179
970091AG2-072 GEN
Adder
36.849
965911AG1-460 GEN
Solar/Wind Harmer
0.658
276686W4-005 GEN3
Solar/Wind Harmer
1.425
276621W2-048 GEN
Solar/Wind Harmer
2.936
940581AE2-045 GEN
Solar/Wind Harmer
4.779
971605AH1-302 GEN
Solar/Wind Harmer
4.087
964861AG1-349 GEN
Solar/Wind Harmer
3.601
971917AH1-482 GEN
Solar/Wind Harmer
4.154
958381AF2-132 GEN
Solar/Wind Harmer
4.147
276655WTG1_EQ
Solar/Wind Harmer
3.982
276656WTG2_EQ
Solar/Wind Harmer
0.527
939741AE1-205 GEN
Solar/Wind Harmer
9.125
270055AF2-134 C O1
Solar/Wind Harmer
1.357
970373AG2-245 GEN
Solar/Wind Harmer
9.263
939401AE1-172 GEN
Solar/Wind Harmer
6.105
274848CAMPGROVE;RU
Solar/Wind Harmer
2.786
276646AC1-214 GEN2
Solar/Wind Harmer
0.578
252510AF1-249 C
Solar/Wind Helper
0.646
253398AE2-221_GEN2
Solar/Wind Helper
1.675
253333AC1-068 GEN
Solar/Wind Helper
0.614
339221AD2-048_GEN
Solar/Wind Helper
0.683
24726905LAWG2S
50/50
6.169
24726605LAWG1S
50/50
6.166
24726705LAWG2A
50/50
4.135
24726505LAWG1B
50/50
4.106
24726805LAWG2B
50/50
4.088
24729505KEY G4
50/50
6.445
270356AE2-297 GEN
Solar/Wind Harmer
7.795
945581AF1-223 GEN
Solar/Wind Harmer
5.367
958711AF2-162 GEN
Solar/Wind Harmer
1.075
964611AG1-324 GEN
Solar/Wind Harmer
3.96
961761AG1-017 GEN
Solar/Wind Harmer
0.417
970289AG2-191 GEN
Solar/Wind Harmer
1.741
247536S-71 GEN
Solar/Wind Harmer
3.572
270543AE2-219 C
Solar/Wind Harmer
8.26
971029AG2-637 GEN
Solar/Wind Harmer
11.382
963791AG1-232 GEN
Solar/Wind Harmer
8.055
270071AF1-092 GEN
Solar/Wind Harmer
8.272
270444AC2-157 GEN1
Solar/Wind Harmer
3.044
270445AC2-157 GEN2
Solar/Wind Harmer
3.044
963841AG1-237 GEN
Solar/Wind Harmer
5.767
24386405FR-21G C
Solar/Wind Harmer
2.189
24387005FR-3G C
Solar/Wind Harmer
2.013
946581AF1-322 GEN
Solar/Wind Harmer
5.003
24691005MDL-2G C
Solar/Wind Harmer
1.808
944221AF1-090 GEN
Solar/Wind Harmer
5.208
276668AB2-070 GEN1
Solar/Wind Harmer
1.043
276848AB2-070 GEN3
Solar/Wind Harmer
1.043
276849AB2-070 GEN2
Solar/Wind Harmer
1.043
276763AC1-053 GEN1
Solar/Wind Harmer
1.862
276764AC1-053 GEN2
Solar/Wind Harmer
1.862
959141AF2-205 GEN
Solar/Wind Harmer
2.809
958391AF2-133 GEN
Solar/Wind Harmer
4.185
274853TWINGROVE;U1
Solar/Wind Harmer
3.304
274854TWINGROVE;U2
Solar/Wind Harmer
3.235
276726Z2-087_GEN
Solar/Wind Harmer
3.608
959341AF2-225 GEN
Solar/Wind Harmer
6.844
970169AG2-114 GEN
Solar/Wind Harmer
4.452
274863CRW1-WTG
Solar/Wind Harmer
2.467
274864CRW2-WTG
Solar/Wind Harmer
2.467
926823AC1-168 GEN
Solar/Wind Harmer
1.854
241972AD1-140 GEN
Solar/Wind Helper
3.411
253406AD2-031_GEN
Solar/Wind Helper
0.947
270340AC2-060 GEN
Solar/Wind Helper
1.277
253338AC1-165 GEN
Solar/Wind Helper
0.593
253343AC1-166 GEN
Solar/Wind Helper
0.593
945631AF1-228 GEN
Solar/Wind Helper
1.063
241973AD2-163_GEN1
Solar/Wind Helper
0.965
241974AD2-163_GEN2
Solar/Wind Helper
0.965
339216AC1-074 GEN
Solar/Wind Helper
0.844
241955AC1-078 GEN
Solar/Wind Helper
0.93
961161AF2-407 GEN
50/50
40.787
24728705AND G3
50/50
8.148
24728505AND G1
50/50
3.896
24379505HDWTR1G C
Solar/Wind Harmer
13.828
270240V3-007_GEN2
Solar/Wind Harmer
10.819
270004AE1-209 GEN
Solar/Wind Harmer
7.479
970825AG2-519 GEN
Solar/Wind Harmer
6.654
946031AF1-268 GEN
Solar/Wind Harmer
9.699
962031AG1-047 GEN
Solar/Wind Harmer
2.945
957741AF2-068 GEN
Solar/Wind Harmer
14.611
965461AG1-414 GEN
Solar/Wind Harmer
2.078
970289AG2-191 GEN
Solar/Wind Harmer
0.703
944531AF1-118 GEN
Solar/Wind Harmer
31.168
247642Z2-115 C
Solar/Wind Harmer
0.054
970193AG2-126 GEN
Solar/Wind Harmer
9.071
24386205FR-12G C
Solar/Wind Harmer
2.181
24690905MDL-1G C
Solar/Wind Harmer
3.925
970781AG2-491 GEN
Solar/Wind Harmer
4.89
270043AE2-236 GEN
Solar/Wind Harmer
2.678
942481AE2-261 GEN
Solar/Wind Harmer
14.096
276785W4-005 GEN1
Solar/Wind Harmer
1.425
971993AH1-541 GEN
Solar/Wind Harmer
4.354
957381AF2-032 GEN
Solar/Wind Harmer
0.942
965091AG1-374 GEN
Solar/Wind Harmer
13.758
959611AF2-252 GEN
Solar/Wind Harmer
1.067
964401AG1-302 GEN
Solar/Wind Harmer
4.147
274851PROVIDENC;RU
Solar/Wind Harmer
1.228
274849CRESCENT ;1U
Solar/Wind Harmer
0.797
252524AE2-267 GEN
Solar/Wind Helper
1.024
252507AC2-088 GEN
Solar/Wind Helper
1.663
253394AE2-221_GEN
Solar/Wind Helper
1.675
960071AF2-298 GEN
Solar/Wind Helper
0.538
270367AC2-061_GEN
Solar/Wind Helper
2.061
276820AF1-078_GEN
Solar/Wind Helper
0.44
270186AC1-089 GEN
Solar/Wind Helper
0.873
270518AE2-148 GEN
Solar/Wind Helper
8.43
253325AC1-069 GEN
Solar/Wind Helper
0.614
339243AC2-075 GEN1
Solar/Wind Helper
0.194
25194708EBND2
50/50
7.996
24729405KEY G3
50/50
0.352
24729305KEY G2
50/50
0.346
24729205KEY G1
50/50
0.344
247621Y3-024
50/50
0.226
926881AC1-175 GEN
Solar/Wind Harmer
9.761
270383AD1-128 GEN
Solar/Wind Harmer
6.5
944541AF1-119 GEN
Solar/Wind Harmer
4.45
960971AF2-388 GEN
Solar/Wind Harmer
11.617
24725505WLD G2 C
Solar/Wind Harmer
4.224
24699105WLD G1 C
Solar/Wind Harmer
4.175
270031AE2-169
Solar/Wind Harmer
8.504
270599AE1-208 GEN
Solar/Wind Harmer
8.504
964611AG1-324 GEN
Solar/Wind Harmer
0.531
270201AC2-176 GEN
Solar/Wind Harmer
5.006
970291AG2-192 GEN
Solar/Wind Harmer
1.191
970291AG2-192 GEN
Solar/Wind Harmer
0.384
970883AG2-550 GEN
Solar/Wind Harmer
8.26
970885AG2-551 GEN
Solar/Wind Harmer
1.921
942221AE2-234 GEN
Solar/Wind Harmer
2.761
24728805RICHG1
Adder
2.466
24728905RICHG2
Adder
2.466
945391AF1-204 GEN
Solar/Wind Harmer
8.428
970241AG2-163 GEN
Solar/Wind Harmer
13.629
24387305FR-4G C
Solar/Wind Harmer
2.585
966841AG1-555 GEN
Solar/Wind Harmer
1.277
270180AB1-006 GEN1
Solar/Wind Harmer
3.517
24697605MDL-3G C
Solar/Wind Harmer
1.802
24755605MDL-5G
Solar/Wind Harmer
1.179
24697905MDL-4G C
Solar/Wind Harmer
1.122
270181AB1-006 GEN2
Solar/Wind Harmer
0.35
945421AF1-207 GEN
Solar/Wind Harmer
6.736
957841AF2-078 GEN
Solar/Wind Harmer
2.9
276916AD2-100_GEN
Solar/Wind Harmer
9.924
276911AD2-131_GEN
Solar/Wind Harmer
2.006
274880W4-005 GEN4
Solar/Wind Harmer
1.425
276174W4-005 GEN2
Solar/Wind Harmer
1.425
276615X2-022 GEN
Solar/Wind Harmer
0.922
276838X2-022 GEN2
Solar/Wind Harmer
0.11
960611AF2-352 GEN
Solar/Wind Harmer
1.067
942111AE2-223 GEN
Solar/Wind Harmer
3.74
270535AF1-215 GEN1
Solar/Wind Harmer
2.036
270536AF1-215 GEN2
Solar/Wind Harmer
2.036
276645AC1-214 GEN1
Solar/Wind Harmer
0.578
25183208HLCRTG
Solar/Wind Helper
2.686
252509AD1-136 GEN
Solar/Wind Helper
0.238
253378AE2-206_GEN
Solar/Wind Helper
0.943
962581AG1-107 GEN
Solar/Wind Helper
1.056
961491AF2-440 GEN
Solar/Wind Helper
0.043
253415AE1-040 GEN
Solar/Wind Helper
0.585
253349AC2-067 GEN
Solar/Wind Helper
0.246
253400AC2-068 GEN
Solar/Wind Helper
0.099
253383AE2-342_GEN
Solar/Wind Helper
0.434
LAGNLTFEXP_LAGN->PJM
CLTF
4.676
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.277
TVALTFEXP_TVA->PJM
CLTF
1.91
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.74
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.455
MECLTFEXP_MEC->PJM
CLTF
6.681
SIGELTFEXP_SIGE->PJM
CLTF
0.259
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.796
NYPJM->LTFIMP_NY
CLTF
0.614
LGEELTFEXP_LGEE->PJM
CLTF
1.6
WECLTFEXP_WEC->PJM
CLTF
1.598
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.039
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o DEOK_P4_1579_EASTBEND_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1579_EASTBEND_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.35 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2417.88
MW Contribution:
7.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726405LAWG1A
50/50
3.773
961171AF2-408 GEN
50/50
9.972
961161AF2-407 GEN
50/50
37.427
24728705AND G3
50/50
7.358
24728505AND G1
50/50
3.518
24379505HDWTR1G C
Solar/Wind Harmer
12.891
270240V3-007_GEN2
Solar/Wind Harmer
10.086
24726905LAWG2S
50/50
5.837
24726605LAWG1S
50/50
5.834
24726705LAWG2A
50/50
3.913
24726505LAWG1B
50/50
3.885
24726805LAWG2B
50/50
3.868
270356AE2-297 GEN
Solar/Wind Harmer
7.217
945581AF1-223 GEN
Solar/Wind Harmer
4.951
958711AF2-162 GEN
Solar/Wind Harmer
0.99
964611AG1-324 GEN
Solar/Wind Harmer
3.572
961761AG1-017 GEN
Solar/Wind Harmer
0.375
24729505KEY G4
Adder
5.574
970289AG2-191 GEN
Solar/Wind Harmer
1.592
247536S-71 GEN
Solar/Wind Harmer
3.137
270543AE2-219 C
Solar/Wind Harmer
7.118
971029AG2-637 GEN
Solar/Wind Harmer
9.557
963791AG1-232 GEN
Solar/Wind Harmer
7.137
270444AC2-157 GEN1
Solar/Wind Harmer
2.786
270445AC2-157 GEN2
Solar/Wind Harmer
2.786
270071AF1-092 GEN
Solar/Wind Harmer
7.467
963841AG1-237 GEN
Solar/Wind Harmer
5.243
24386405FR-21G C
Solar/Wind Harmer
1.99
24387005FR-3G C
Solar/Wind Harmer
1.83
946581AF1-322 GEN
Solar/Wind Harmer
4.548
24691005MDL-2G C
Solar/Wind Harmer
1.644
944221AF1-090 GEN
Solar/Wind Harmer
4.703
241972AD1-140 GEN
Solar/Wind Helper
3.805
253406AD2-031_GEN
Solar/Wind Helper
1.056
270340AC2-060 GEN
Solar/Wind Helper
1.349
253338AC1-165 GEN
Solar/Wind Helper
0.652
253343AC1-166 GEN
Solar/Wind Helper
0.652
945631AF1-228 GEN
Solar/Wind Helper
1.154
241973AD2-163_GEN1
Solar/Wind Helper
1.06
241974AD2-163_GEN2
Solar/Wind Helper
1.06
339216AC1-074 GEN
Solar/Wind Helper
0.966
241955AC1-078 GEN
Solar/Wind Helper
0.999
24728605AND G2
50/50
3.518
942081AE2-220 GEN
Solar/Wind Harmer
10.427
270209AC1-174_GEN
Solar/Wind Harmer
6.635
270437AC2-090 C
Solar/Wind Harmer
9.099
270239V3-007_GEN1
Solar/Wind Harmer
2.805
270005AE1-210 C O1
Solar/Wind Harmer
6.917
945371AF1-202 GEN
Solar/Wind Harmer
7.617
970825AG2-519 GEN
Solar/Wind Harmer
2.268
958861AF2-177 GEN
Solar/Wind Harmer
11.119
965651AG1-433 GEN
Solar/Wind Harmer
5.346
276903AD2-071 C
Solar/Wind Harmer
9.285
270594AE1-207 GEN
Solar/Wind Harmer
12.254
270032AE2-172
Solar/Wind Harmer
4.196
270024AE2-089 GEN
Solar/Wind Harmer
3.476
963741AG1-226 GEN
Solar/Wind Harmer
22.302
270222AC2-111 GEN
Solar/Wind Harmer
2.188
944031AF1-071 GEN
Solar/Wind Harmer
0.492
24385905FR-11G C
Solar/Wind Harmer
3.846
24386605FR-22G C
Solar/Wind Harmer
1.99
970091AG2-072 GEN
Adder
34.506
24791305MDL-5G
Solar/Wind Harmer
1.072
252510AF1-249 C
Solar/Wind Helper
0.751
253398AE2-221_GEN2
Solar/Wind Helper
1.897
253333AC1-068 GEN
Solar/Wind Helper
0.676
339221AD2-048_GEN
Solar/Wind Helper
0.795
943111AE2-339 GEN
Solar/Wind Helper
0.367
270004AE1-209 GEN
Solar/Wind Harmer
6.917
970825AG2-519 GEN
Solar/Wind Harmer
6.089
946031AF1-268 GEN
Solar/Wind Harmer
8.852
962031AG1-047 GEN
Solar/Wind Harmer
2.646
957741AF2-068 GEN
Solar/Wind Harmer
13.128
965461AG1-414 GEN
Solar/Wind Harmer
1.9
970289AG2-191 GEN
Solar/Wind Harmer
0.643
944531AF1-118 GEN
Solar/Wind Harmer
28.568
247642Z2-115 C
Solar/Wind Harmer
0.05
970193AG2-126 GEN
Solar/Wind Harmer
8.244
24386205FR-12G C
Solar/Wind Harmer
1.983
24690905MDL-1G C
Solar/Wind Harmer
3.568
970781AG2-491 GEN
Solar/Wind Harmer
4.445
270043AE2-236 GEN
Solar/Wind Harmer
2.399
252524AE2-267 GEN
Solar/Wind Helper
1.144
252507AC2-088 GEN
Solar/Wind Helper
1.776
253394AE2-221_GEN
Solar/Wind Helper
1.897
960071AF2-298 GEN
Solar/Wind Helper
0.617
270367AC2-061_GEN
Solar/Wind Helper
2.314
276820AF1-078_GEN
Solar/Wind Helper
0.491
270186AC1-089 GEN
Solar/Wind Helper
0.981
270518AE2-148 GEN
Solar/Wind Helper
9.267
253325AC1-069 GEN
Solar/Wind Helper
0.676
339243AC2-075 GEN1
Solar/Wind Helper
0.222
25194708EBND2
50/50
13.343
926881AC1-175 GEN
Solar/Wind Harmer
9.099
944541AF1-119 GEN
Solar/Wind Harmer
4.096
960971AF2-388 GEN
Solar/Wind Harmer
10.692
24725505WLD G2 C
Solar/Wind Harmer
3.867
24699105WLD G1 C
Solar/Wind Harmer
3.822
270031AE2-169
Solar/Wind Harmer
7.767
270599AE1-208 GEN
Solar/Wind Harmer
7.767
270383AD1-128 GEN
Solar/Wind Harmer
5.785
964611AG1-324 GEN
Solar/Wind Harmer
0.479
270201AC2-176 GEN
Solar/Wind Harmer
4.498
970291AG2-192 GEN
Solar/Wind Harmer
1.089
970291AG2-192 GEN
Solar/Wind Harmer
0.351
247621Y3-024
Adder
0.188
970883AG2-550 GEN
Solar/Wind Harmer
7.118
970885AG2-551 GEN
Solar/Wind Harmer
1.655
942221AE2-234 GEN
Solar/Wind Harmer
2.49
945391AF1-204 GEN
Solar/Wind Harmer
7.659
24728805RICHG1
Adder
1.94
24728905RICHG2
Adder
1.94
970241AG2-163 GEN
Solar/Wind Harmer
12.39
24387305FR-4G C
Solar/Wind Harmer
2.35
966841AG1-555 GEN
Solar/Wind Harmer
1.162
270180AB1-006 GEN1
Solar/Wind Harmer
3.197
24697605MDL-3G C
Solar/Wind Harmer
1.638
24755605MDL-5G
Solar/Wind Harmer
1.072
24697905MDL-4G C
Solar/Wind Harmer
1.02
270181AB1-006 GEN2
Solar/Wind Harmer
0.318
945421AF1-207 GEN
Solar/Wind Harmer
6.122
957841AF2-078 GEN
Solar/Wind Harmer
2.636
25183208HLCRTG
Solar/Wind Helper
3.053
252509AD1-136 GEN
Solar/Wind Helper
0.254
253378AE2-206_GEN
Solar/Wind Helper
1.051
962581AG1-107 GEN
Solar/Wind Helper
1.185
961491AF2-440 GEN
Solar/Wind Helper
0.049
253349AC2-067 GEN
Solar/Wind Helper
0.297
253400AC2-068 GEN
Solar/Wind Helper
0.119
253415AE1-040 GEN
Solar/Wind Helper
0.626
253383AE2-342_GEN
Solar/Wind Helper
0.477
LAGNLTFEXP_LAGN->PJM
CLTF
4.128
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.397
TVALTFEXP_TVA->PJM
CLTF
1.652
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.488
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.265
MECLTFEXP_MEC->PJM
CLTF
6
SIGELTFEXP_SIGE->PJM
CLTF
0.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.436
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
1.198
WECLTFEXP_WEC->PJM
CLTF
1.438
AG2-052LTFEXP_AG2-052->PJM
LTF
0.098
AH1-155LTFEXP_AH1-155->PJM
LTF
0.146

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.59 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2365.35
MW Contribution:
7.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.429
24803306KYGER 4LP
50/50
2.378
971191AH1-055 GEN
Solar/Wind Harmer
71.613
252507AC2-088 GEN
Solar/Wind Harmer
2.061
252519AF1-045_GEN
Solar/Wind Harmer
3.919
25194608D.CRK4
Adder
1.717
252524AE2-267 GEN
Solar/Wind Harmer
1.644
25196608WSDLE5
Adder
8.95
253317AC1-085 GEN4
Solar/Wind Harmer
8.534
946181AF1-283 GEN
Solar/Wind Harmer
13.251
25196008MFTGT1
Adder
1.348
958171AF2-111 GEN
Solar/Wind Harmer
24.74
253394AE2-221_GEN
Solar/Wind Harmer
4.361
972167AH1-666 GEN
Solar/Wind Harmer
7.448
270367AC2-061_GEN
Solar/Wind Harmer
2.87
270186AC1-089 GEN
Solar/Wind Harmer
5.445
339243AC2-075 GEN1
Solar/Wind Harmer
0.401
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.651
253371AE2-315 SEC2
Adder
1.561
960071AF2-298 GEN
Solar/Wind Harmer
1.198
3429391JKCT 9G
Adder
6.485
24379505HDWTR1G C
Solar/Wind Harmer
5.968
270240V3-007_GEN2
Solar/Wind Harmer
4.669
970093AG2-073 GEN
Solar/Wind Harmer
3.762
270004AE1-209 GEN
Solar/Wind Harmer
3.872
24728705AND G3
Adder
5.634
24728505AND G1
Adder
2.694
946031AF1-268 GEN
Solar/Wind Harmer
5.828
970825AG2-519 GEN
Solar/Wind Harmer
3.944
962031AG1-047 GEN
Solar/Wind Harmer
2.067
957741AF2-068 GEN
Solar/Wind Harmer
10.253
970455AG2-298 GEN
Solar/Wind Harmer
2.327
965461AG1-414 GEN
Solar/Wind Harmer
1.471
970289AG2-191 GEN
Solar/Wind Harmer
0.498
247642Z2-115 C
Solar/Wind Harmer
0.041
970653AG2-424 GEN
Solar/Wind Harmer
0.434
944531AF1-118 GEN
Solar/Wind Harmer
21.518
253325AC1-069 GEN
Solar/Wind Harmer
0.639
970193AG2-126 GEN
Solar/Wind Harmer
8.969
339206AE1-143 GEN
Solar/Wind Harmer
1.271
24386205FR-12G C
Solar/Wind Harmer
2.428
24690905MDL-1G C
Solar/Wind Harmer
4.487
970781AG2-491 GEN
Solar/Wind Harmer
5.589
270518AE2-148 GEN
Solar/Wind Harmer
6.728
964401AG1-302 GEN
Solar/Wind Harmer
4.923
276785W4-005 GEN1
Solar/Wind Harmer
1.638
971993AH1-541 GEN
Solar/Wind Harmer
5.005
942481AE2-261 GEN
Solar/Wind Harmer
16.153
957381AF2-032 GEN
Solar/Wind Harmer
1.08
972273AH1-721 GEN
Adder
43.936
274772LINCOLN ;3U
Adder
4.436
972259AH1-714 GEN
Adder
10.006
274729ELWOOD EC;1P
Adder
8.614
274730ELWOOD EC;6P
Adder
8.613
274734ELWOOD EC;8P
Adder
8.613
274736ELWOOD EC;9P
Adder
8.613
274803UNIV PARK;6U
Adder
3.054
972038AH1-567 GEN2
Adder
0.191
274826FISK ;BP
Adder
5.733
274814UNIV PK N;0U
Adder
2.645
274807UNIV PK N;3U
Adder
2.64
274811UNIV PK N;7U
Adder
2.622
274724RIVER EC ;11
Adder
9.272
274752CRETE EC ;2U
Adder
4.313
274753CRETE EC ;3U
Adder
4.313
274676JOLIET 29;8U
Adder
15.48
274682WAUKEGAN ;7U
Adder
5.491
270330AC1-082 GEN2
Solar/Wind Helper
0.195
270329AC1-082 GEN1
Solar/Wind Helper
0.195
24803406KYGER 5HP
50/50
4.081
24803206KYGER 4HP
50/50
4.076
252516AE2-318_GEN
Solar/Wind Harmer
10.768
25196808ZIMRHP
Adder
80.577
25194608D.CRK4
Adder
1.717
252510AF1-249 C
Solar/Wind Harmer
0.435
253316AC1-085 GEN3
Solar/Wind Harmer
8.534
946171AF1-282 GEN
Solar/Wind Harmer
10.193
25196008MFTGT1
Adder
1.391
253398AE2-221_GEN2
Solar/Wind Harmer
4.361
945681AF1-233 GEN
Solar/Wind Harmer
17.478
339221AD2-048_GEN
Solar/Wind Harmer
1.333
270222AC2-111 GEN
Solar/Wind Harmer
3.827
944031AF1-071 GEN
Solar/Wind Harmer
0.861
270273AD2-016 GEN
Solar/Wind Harmer
2.247
253370AE2-315 SEC1
Adder
1.651
253371AE2-315 SEC2
Adder
1.561
943111AE2-339 GEN
Solar/Wind Harmer
0.715
25326309TAIT D
Adder
0.874
3429421JKCT 10G
Adder
6.485
3429241JKCT 3G
Adder
8.957
942081AE2-220 GEN
Solar/Wind Harmer
4.827
270209AC1-174_GEN
Solar/Wind Harmer
3.072
270437AC2-090 C
Solar/Wind Harmer
4.212
270239V3-007_GEN1
Solar/Wind Harmer
1.299
270005AE1-210 C O1
Solar/Wind Harmer
3.872
24728605AND G2
Adder
2.694
970825AG2-519 GEN
Solar/Wind Harmer
1.469
945371AF1-202 GEN
Solar/Wind Harmer
4.69
276903AD2-071 C
Solar/Wind Harmer
6.702
270594AE1-207 GEN
Solar/Wind Harmer
8.993
270032AE2-172
Solar/Wind Harmer
3.08
339211AE2-254 GEN
Solar/Wind Harmer
0.998
958861AF2-177 GEN
Solar/Wind Harmer
7.178
965651AG1-433 GEN
Solar/Wind Harmer
3.544
270024AE2-089 GEN
Solar/Wind Harmer
2.988
970653AG2-424 GEN
Solar/Wind Harmer
3.003
253333AC1-068 GEN
Solar/Wind Harmer
0.639
970091AG2-072 GEN
Adder
46.355
963741AG1-226 GEN
Solar/Wind Harmer
26.027
339241AF1-083 GEN
Solar/Wind Harmer
0.959
24385905FR-11G C
Solar/Wind Harmer
4.709
24386605FR-22G C
Solar/Wind Harmer
2.437
24791305MDL-5G
Solar/Wind Harmer
1.347
940581AE2-045 GEN
Solar/Wind Harmer
5.601
971605AH1-302 GEN
Solar/Wind Harmer
4.789
964861AG1-349 GEN
Solar/Wind Harmer
4.271
971917AH1-482 GEN
Solar/Wind Harmer
4.927
958381AF2-132 GEN
Solar/Wind Harmer
4.923
964901AG1-354 GEN
Solar/Wind Harmer
8.138
276686W4-005 GEN3
Solar/Wind Harmer
1.638
276621W2-048 GEN
Solar/Wind Harmer
3.373
965911AG1-460 GEN
Solar/Wind Harmer
0.754
270055AF2-134 C O1
Solar/Wind Harmer
1.627
274773LINCOLN ;4U
Adder
4.436
274774LINCOLN ;5U
Adder
4.436
274732ELWOOD EC;7P
Adder
8.613
274802UNIV PARK;5U
Adder
3.054
274674JOLIET 9 ;6U
Adder
8.063
274812UNIV PK N;8U
Adder
2.622
274723RIVER EC ;12
Adder
9.381
274751CRETE EC ;1U
Adder
4.313
274754CRETE EC ;4U
Adder
4.313
274676JOLIET 29;8U
Adder
16.054
274745AC1-111 GEN9
Adder
2.918
960001AF2-291 GEN
Solar/Wind Helper
1.729
270331AC1-082 GEN3
Solar/Wind Helper
0.194
235780M24_1
Solar/Wind Helper
0.507
24802606KYGER 1HP
50/50
4.153
24802706KYGER 1LP
50/50
2.435
24803506KYGER 5LP
50/50
2.378
971985AH1-537 GEN
Solar/Wind Harmer
49.684
25196408WSDLE3
Adder
9.213
25196308WSDLE2
Adder
9.133
25196208WSDLE1
Adder
9.11
25196708WSDLE6
Adder
9.087
25196508WSDLE4
Adder
8.858
253433AC1-085 GEN1
Solar/Wind Harmer
5.417
253432AC1-085 GEN2
Solar/Wind Harmer
0.273
25196108MFTGT2
Adder
1.534
25196108MFTGT2
Adder
1.424
972163AH1-664 GEN
Solar/Wind Harmer
9.168
972165AH1-665 GEN
Solar/Wind Harmer
7.335
253406AD2-031_GEN
Solar/Wind Harmer
1.154
339216AC1-074 GEN
Solar/Wind Harmer
1.482
270340AC2-060 GEN
Solar/Wind Harmer
2.616
270263AC1-001 GEN
Solar/Wind Harmer
0.88
253372AE2-315 SEC3
Adder
1.561
253372AE2-315 SEC3
Adder
1.561
25306009OHH W.
Adder
2.343
270356AE2-297 GEN
Solar/Wind Harmer
3.599
3429211JKCT 2G
Adder
8.841
971029AG2-637 GEN
Solar/Wind Harmer
11.181
270543AE2-219 C
Solar/Wind Harmer
7.251
247536S-71 GEN
Solar/Wind Harmer
2.858
964611AG1-324 GEN
Solar/Wind Harmer
2.681
961761AG1-017 GEN
Solar/Wind Harmer
0.293
945581AF1-223 GEN
Solar/Wind Harmer
3.049
241972AD1-140 GEN
Solar/Wind Harmer
2.984
270432AC2-029 GEN
Solar/Wind Harmer
4.634
970289AG2-191 GEN
Solar/Wind Harmer
1.232
958711AF2-162 GEN
Solar/Wind Harmer
0.656
24729505KEY G4
Adder
4.046
253338AC1-165 GEN
Solar/Wind Harmer
0.663
253343AC1-166 GEN
Solar/Wind Harmer
0.663
270444AC2-157 GEN1
Solar/Wind Harmer
3.34
270445AC2-157 GEN2
Solar/Wind Harmer
3.34
963841AG1-237 GEN
Solar/Wind Harmer
6.259
24386405FR-21G C
Solar/Wind Harmer
2.437
24387005FR-3G C
Solar/Wind Harmer
2.241
963791AG1-232 GEN
Solar/Wind Harmer
7.617
946581AF1-322 GEN
Solar/Wind Harmer
5.719
24691005MDL-2G C
Solar/Wind Harmer
2.067
270071AF1-092 GEN
Solar/Wind Harmer
8.327
959141AF2-205 GEN
Solar/Wind Harmer
3.307
958391AF2-133 GEN
Solar/Wind Harmer
4.945
944221AF1-090 GEN
Solar/Wind Harmer
5.93
276668AB2-070 GEN1
Solar/Wind Harmer
1.199
276848AB2-070 GEN3
Solar/Wind Harmer
1.199
276849AB2-070 GEN2
Solar/Wind Harmer
1.199
276763AC1-053 GEN1
Solar/Wind Harmer
2.139
276764AC1-053 GEN2
Solar/Wind Harmer
2.139
274853TWINGROVE;U1
Solar/Wind Harmer
3.87
274775LINCOLN ;6U
Adder
4.436
274776LINCOLN ;7U
Adder
4.436
274777LINCOLN ;8U
Adder
4.436
972227AH1-698 GEN1
Adder
1.369
972228AH1-698 GEN2
Adder
1.944
274728ELWOOD EC;5P
Adder
8.613
274731ELWOOD EC;2P
Adder
8.614
274733ELWOOD EC;3P
Adder
8.614
274735ELWOOD EC;4P
Adder
8.614
274800UNIV PARK;3U
Adder
3.055
274801UNIV PARK;4U
Adder
3.055
972037AH1-567 GEN1
Adder
0.096
274827FISK ;RP
Adder
4.063
274687WILL CNTY;4U
Adder
14.622
274687WILL CNTY;4U
Adder
14.622
274675JOLIET 29;7U
Adder
16.054
274675JOLIET 29;7U
Adder
15.48
274744AC1-111 GEN8
Adder
2.918
274746AC1-111 G10
Adder
2.918
274854TWINGROVE;U2
Solar/Wind Harmer
0.363
24803006KYGER 3HP
50/50
4.125
24802806KYGER 2HP
50/50
4.108
24802906KYGER 2LP
50/50
2.412
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.294
25183208HLCRTG
Solar/Wind Harmer
6.595
25194408D.CRK1
Adder
7.9
25194508D.CRK3
Adder
1.477
962581AG1-107 GEN
Solar/Wind Harmer
4.434
961491AF2-440 GEN
Solar/Wind Harmer
1.843
972043AH1-570 GEN
Solar/Wind Harmer
2.117
972045AH1-571 GEN
Solar/Wind Harmer
1.694
270269AC2-059
Solar/Wind Harmer
7.883
253415AE1-040 GEN
Solar/Wind Harmer
0.948
253370AE2-315 SEC1
Adder
1.651
971125AH1-004 GEN
Solar/Wind Harmer
3.263
970107AG2-081 GEN
Solar/Wind Harmer
2.447
24728805RICHG1
Adder
3.029
24728905RICHG2
Adder
3.029
25322209TAIT E
Adder
7.785
25322209TAIT E
Adder
7.61
253349AC2-067 GEN
Solar/Wind Harmer
1.622
253400AC2-068 GEN
Solar/Wind Harmer
0.652
25326109MON D
Adder
1.021
926881AC1-175 GEN
Solar/Wind Harmer
4.212
942891AE2-308 GEN
Solar/Wind Harmer
7.426
270383AD1-128 GEN
Solar/Wind Harmer
4.53
970883AG2-550 GEN
Solar/Wind Harmer
7.251
970885AG2-551 GEN
Solar/Wind Harmer
1.686
247621Y3-024
Adder
0.167
964611AG1-324 GEN
Solar/Wind Harmer
0.36
270201AC2-176 GEN
Solar/Wind Harmer
3.513
24725505WLD G2 C
Solar/Wind Harmer
2.705
24699105WLD G1 C
Solar/Wind Harmer
2.673
270031AE2-169
Solar/Wind Harmer
5.45
270599AE1-208 GEN
Solar/Wind Harmer
5.45
964571AG1-320 GEN
Solar/Wind Harmer
5.334
970291AG2-192 GEN
Solar/Wind Harmer
0.843
970291AG2-192 GEN
Solar/Wind Harmer
0.272
944541AF1-119 GEN
Solar/Wind Harmer
2.715
960971AF2-388 GEN
Solar/Wind Harmer
7.089
942221AE2-234 GEN
Solar/Wind Harmer
2.151
945391AF1-204 GEN
Solar/Wind Harmer
8.333
970241AG2-163 GEN
Solar/Wind Harmer
14.459
25326509SID D
Adder
0.751
24387305FR-4G C
Solar/Wind Harmer
2.878
966841AG1-555 GEN
Solar/Wind Harmer
1.422
270180AB1-006 GEN1
Solar/Wind Harmer
4.02
24697605MDL-3G C
Solar/Wind Harmer
2.06
24755605MDL-5G
Solar/Wind Harmer
1.347
24697905MDL-4G C
Solar/Wind Harmer
1.282
270181AB1-006 GEN2
Solar/Wind Harmer
0.4
945421AF1-207 GEN
Solar/Wind Harmer
7.8
957841AF2-078 GEN
Solar/Wind Harmer
3.358
339236AF1-050_GEN
Solar/Wind Harmer
0.993
274880W4-005 GEN4
Solar/Wind Harmer
1.638
276174W4-005 GEN2
Solar/Wind Harmer
1.638
276615X2-022 GEN
Solar/Wind Harmer
1.059
276838X2-022 GEN2
Solar/Wind Harmer
0.126
276916AD2-100_GEN
Solar/Wind Harmer
11.356
276911AD2-131_GEN
Solar/Wind Harmer
2.295
270535AF1-215 GEN1
Solar/Wind Harmer
2.441
270536AF1-215 GEN2
Solar/Wind Harmer
2.441
274770LINCOLN ;1U
Adder
4.436
274771LINCOLN ;2U
Adder
4.436
274674JOLIET 9 ;6U
Adder
8.063
274805UNIV PK N;1U
Adder
2.628
274808UNIV PK N;4U
Adder
2.611
274696ROCKY RD ;4P
Adder
5.933
274695ROCKY RD ;2P
Adder
5.796
274693ROCKY RD ;1P
Adder
5.739
274697ROCKY RD ;3P
Adder
1.575
237033AB1-150 GEN
Solar/Wind Helper
0.409
960611AF2-352 GEN
Solar/Wind Harmer
0.12
LAGNLTFEXP_LAGN->PJM
CLTF
6.674
TVALTFEXP_TVA->PJM
CLTF
3.152
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.061
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.047
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.848
MECLTFEXP_MEC->PJM
CLTF
8.254
SIGELTFEXP_SIGE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.683
NYPJM->LTFIMP_NY
CLTF
1.71
LGEELTFEXP_LGEE->PJM
CLTF
5.221
WECLTFEXP_WEC->PJM
CLTF
1.971
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.322
AG2-052LTFEXP_AG2-052->PJM
LTF
0.126
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2185.8
MW Contribution:
4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.079
252516AE2-318_GEN
Solar/Wind Harmer
8.283
25196808ZIMRHP
Adder
79.38
25194608D.CRK4
Adder
1.689
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.986
25196008MFTGT1
Adder
1.369
253398AE2-221_GEN2
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.031
270273AD2-016 GEN
Solar/Wind Harmer
0.594
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
25326309TAIT D
Adder
0.844
3429421JKCT 10G
Adder
6.396
970773AG2-487 GEN
Solar/Wind Harmer
0.939
3429241JKCT 3G
Adder
8.835
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.76
270005AE1-210 C O1
Solar/Wind Harmer
1.04
24728605AND G2
Adder
2.628
970825AG2-519 GEN
Solar/Wind Harmer
1.683
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.07
270594AE1-207 GEN
Solar/Wind Harmer
5.019
270032AE2-172
Solar/Wind Harmer
2.988
958861AF2-177 GEN
Solar/Wind Harmer
1.919
965651AG1-433 GEN
Solar/Wind Harmer
1.282
270024AE2-089 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.063
970091AG2-072 GEN
Adder
45.503
253333AC1-068 GEN
Solar/Wind Harmer
0.005
963741AG1-226 GEN
Solar/Wind Harmer
9.274
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
964901AG1-354 GEN
Solar/Wind Harmer
5.594
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.628
276621W2-048 GEN
Solar/Wind Harmer
0.183
965911AG1-460 GEN
Solar/Wind Harmer
0.732
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.756
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
5.074
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.536
939401AE1-172 GEN
Solar/Wind Harmer
2.672
941551AE2-152 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
4.277
274774LINCOLN ;5U
Adder
4.277
971997AH1-543 GEN
Solar/Wind Harmer
1.853
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.311
274674JOLIET 9 ;6U
Adder
7.779
276694AA1-018 GEN2
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
10.575
274802UNIV PARK;5U
Adder
2.945
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.411
276646AC1-214 GEN2
Solar/Wind Harmer
0.138
274848CAMPGROVE;RU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.488
274812UNIV PK N;8U
Adder
2.528
274723RIVER EC ;12
Adder
9.04
274751CRETE EC ;1U
Adder
4.155
274754CRETE EC ;4U
Adder
4.155
274745AC1-111 GEN9
Adder
2.817
962781AG1-127 GEN
Solar/Wind Harmer
3.332
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
10.473
959081AF2-199 GEN
Solar/Wind Harmer
3.491
971067AG2-660 GEN
Solar/Wind Harmer
1.164
276708O09 GEN2
Solar/Wind Harmer
0.123
970819AG2-516 GEN
Solar/Wind Harmer
4.177
274858EASY ROAD;U2
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
5.58
945111AF1-176 GEN
Solar/Wind Harmer
5.962
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.73
965011AG1-365 GEN
Solar/Wind Harmer
3.232
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.193
235780M24_1
Solar/Wind Helper
0.496
24803006KYGER 3HP
50/50
4.127
24802806KYGER 2HP
50/50
4.111
24802906KYGER 2LP
50/50
2.413
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.768
25194508D.CRK3
Adder
1.452
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.516
972045AH1-571 GEN
Solar/Wind Harmer
1.214
270269AC2-059
Solar/Wind Harmer
0
971125AH1-004 GEN
Solar/Wind Harmer
2.245
970107AG2-081 GEN
Solar/Wind Harmer
1.684
253370AE2-315 SEC1
Adder
1.601
24728805RICHG1
Adder
2.955
24728905RICHG2
Adder
2.955
25322209TAIT E
Adder
7.522
25322209TAIT E
Adder
7.353
25326109MON D
Adder
0.984
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.111
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.905
970885AG2-551 GEN
Solar/Wind Harmer
1.635
247621Y3-024
Adder
0.162
964611AG1-324 GEN
Solar/Wind Harmer
0.348
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
2.485
270599AE1-208 GEN
Solar/Wind Harmer
4.141
971613AH1-306 GEN
Solar/Wind Harmer
2.151
964571AG1-320 GEN
Solar/Wind Harmer
4.079
970291AG2-192 GEN
Solar/Wind Harmer
0.57
970291AG2-192 GEN
Solar/Wind Harmer
0.263
944541AF1-119 GEN
Solar/Wind Harmer
0.292
960971AF2-388 GEN
Solar/Wind Harmer
2.564
942221AE2-234 GEN
Solar/Wind Harmer
1.655
971587AH1-292 GEN
Solar/Wind Harmer
2.993
945391AF1-204 GEN
Solar/Wind Harmer
4.316
970241AG2-163 GEN
Solar/Wind Harmer
2.286
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.434
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.7
276911AD2-131_GEN
Solar/Wind Harmer
0.507
276615X2-022 GEN
Solar/Wind Harmer
0.038
276838X2-022 GEN2
Solar/Wind Harmer
0.206
25326509SID D
Adder
0.689
960611AF2-352 GEN
Solar/Wind Harmer
1.21
942111AE2-223 GEN
Solar/Wind Harmer
1.178
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
8.857
274770LINCOLN ;1U
Adder
4.277
274771LINCOLN ;2U
Adder
4.277
276901AD2-066 C O1
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.206
276776AD2-060 GEN
Solar/Wind Harmer
0.377
958011AF2-095 GEN
Solar/Wind Harmer
5.084
970941AG2-585 GEN
Solar/Wind Harmer
1.942
276893AG1-478 C
Solar/Wind Harmer
0.235
274674JOLIET 9 ;6U
Adder
7.779
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.287
958491AF2-143 GEN
Solar/Wind Harmer
5.287
276645AC1-214 GEN1
Solar/Wind Harmer
0.138
274805UNIV PK N;1U
Adder
2.533
274808UNIV PK N;4U
Adder
2.517
274696ROCKY RD ;4P
Adder
5.728
274695ROCKY RD ;2P
Adder
5.596
274693ROCKY RD ;1P
Adder
5.541
274697ROCKY RD ;3P
Adder
1.52
962691AG1-118 GEN
Solar/Wind Harmer
10.508
964781AG1-341 GEN
Solar/Wind Harmer
3.705
971341AH1-150 GEN
Solar/Wind Harmer
6.982
971343AH1-151 GEN
Solar/Wind Harmer
6.982
970349AG2-230 GEN
Solar/Wind Harmer
5.234
965681AG1-436 GEN
Solar/Wind Harmer
4.361
965791AG1-447 GEN
Solar/Wind Harmer
3.198
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.562
938861AE1-114 GEN
Solar/Wind Harmer
1.972
970329AG2-216 GEN
Solar/Wind Harmer
1.444
961051AF2-396 GEN
Solar/Wind Harmer
6.65
961051AF2-396 GEN
Solar/Wind Harmer
4.433
971485AH1-239 GEN
Solar/Wind Harmer
2.603
966021AG1-471 GEN
Solar/Wind Harmer
1.739
270246TR4_N_V150
Solar/Wind Harmer
0.019
270247TR4_N_V136
Solar/Wind Harmer
0.019
237033AB1-150 GEN
Solar/Wind Helper
0.401
24803106KYGER 3LP
50/50
2.43
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
68.684
252507AC2-088 GEN
Solar/Wind Harmer
0.357
252519AF1-045_GEN
Solar/Wind Harmer
3.858
25194608D.CRK4
Adder
1.689
25196608WSDLE5
Adder
8.798
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.081
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
17.024
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.127
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
970191AG2-125 GEN
Solar/Wind Harmer
1.385
3429391JKCT 9G
Adder
6.396
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.143
270004AE1-209 GEN
Solar/Wind Harmer
1.04
24728705AND G3
Adder
5.496
24728505AND G1
Adder
2.628
946031AF1-268 GEN
Solar/Wind Harmer
4.524
970825AG2-519 GEN
Solar/Wind Harmer
3.571
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.92
970455AG2-298 GEN
Solar/Wind Harmer
1.776
970289AG2-191 GEN
Solar/Wind Harmer
0.483
247642Z2-115 C
Solar/Wind Harmer
0.002
970653AG2-424 GEN
Solar/Wind Harmer
0.428
944531AF1-118 GEN
Solar/Wind Harmer
18.504
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970193AG2-126 GEN
Solar/Wind Harmer
6.094
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.775
270518AE2-148 GEN
Solar/Wind Harmer
0.304
971993AH1-541 GEN
Solar/Wind Harmer
1.694
942481AE2-261 GEN
Solar/Wind Harmer
10.95
957381AF2-032 GEN
Solar/Wind Harmer
0.83
964401AG1-302 GEN
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
43.369
965091AG1-374 GEN
Solar/Wind Harmer
10.891
959611AF2-252 GEN
Solar/Wind Harmer
1.21
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
4.277
274887GEN-1.85
Solar/Wind Harmer
0.092
276843GEN-1.7
Solar/Wind Harmer
0.114
276806AD2-047 C O1
Solar/Wind Harmer
2.001
972259AH1-714 GEN
Adder
9.653
274729ELWOOD EC;1P
Adder
8.311
274730ELWOOD EC;6P
Adder
8.311
274734ELWOOD EC;8P
Adder
8.311
274736ELWOOD EC;9P
Adder
8.311
970707AG2-453 GEN
Solar/Wind Harmer
11.521
270043AE2-236 GEN
Solar/Wind Harmer
2.263
972038AH1-567 GEN2
Adder
0.184
970571AG2-364 GEN
Solar/Wind Harmer
7.05
274803UNIV PARK;6U
Adder
2.945
276868AE1-113 GEN
Solar/Wind Harmer
0.705
274879MINONK ;1U
Solar/Wind Harmer
0.147
274862TOP CROP ;2U
Solar/Wind Harmer
0.476
274826FISK ;BP
Adder
5.528
274676JOLIET 29;8U
Adder
14.935
274814UNIV PK N;0U
Adder
2.55
274807UNIV PK N;3U
Adder
2.544
274811UNIV PK N;7U
Adder
2.528
274724RIVER EC ;11
Adder
8.935
274752CRETE EC ;2U
Adder
4.155
274753CRETE EC ;3U
Adder
4.155
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
943121AE2-341 GEN
Solar/Wind Harmer
5.893
943591AF1-030 GEN
Solar/Wind Harmer
3.919
274682WAUKEGAN ;7U
Adder
5.301
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
959091AF2-200 GEN
Solar/Wind Harmer
6.982
971347AH1-153 GEN
Solar/Wind Harmer
1.745
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
8.801
971087AG2-675 GEN
Solar/Wind Harmer
1.841
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
3.511
945111AF1-176 GEN
Solar/Wind Harmer
2.708
965021AG1-366 GEN
Solar/Wind Harmer
1.077
270330AC1-082 GEN2
Solar/Wind Helper
0.194
270329AC1-082 GEN1
Solar/Wind Helper
0.194
24802606KYGER 1HP
50/50
4.156
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
971985AH1-537 GEN
Solar/Wind Harmer
5.763
25196408WSDLE3
Adder
9.057
25196308WSDLE2
Adder
8.978
25196208WSDLE1
Adder
8.956
25196708WSDLE6
Adder
8.933
25196508WSDLE4
Adder
8.708
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.401
972163AH1-664 GEN
Solar/Wind Harmer
7.027
972165AH1-665 GEN
Solar/Wind Harmer
5.628
253406AD2-031_GEN
Solar/Wind Harmer
0.458
339216AC1-074 GEN
Solar/Wind Harmer
0.162
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.58
253372AE2-315 SEC3
Adder
1.514
253372AE2-315 SEC3
Adder
1.514
25306009OHH W.
Adder
2.27
270356AE2-297 GEN
Solar/Wind Harmer
0
3429211JKCT 2G
Adder
8.721
971029AG2-637 GEN
Solar/Wind Harmer
7.57
270543AE2-219 C
Solar/Wind Harmer
3.433
247536S-71 GEN
Solar/Wind Harmer
0.191
964611AG1-324 GEN
Solar/Wind Harmer
1.811
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.738
270432AC2-029 GEN
Solar/Wind Harmer
2.001
241972AD1-140 GEN
Solar/Wind Harmer
0.484
970289AG2-191 GEN
Solar/Wind Harmer
0.834
24729505KEY G4
Adder
3.899
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.68
24386405FR-21G C
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.053
270071AF1-092 GEN
Solar/Wind Harmer
7.11
971611AH1-305 GEN
Solar/Wind Harmer
2.204
959141AF2-205 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.16
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.144
276848AB2-070 GEN3
Solar/Wind Harmer
0.143
276849AB2-070 GEN2
Solar/Wind Harmer
0.144
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.806
970169AG2-114 GEN
Solar/Wind Harmer
3.591
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
4.277
274776LINCOLN ;7U
Adder
4.277
274777LINCOLN ;8U
Adder
4.277
926823AC1-168 GEN
Solar/Wind Harmer
0.6
972228AH1-698 GEN2
Adder
1.875
972227AH1-698 GEN1
Adder
1.321
970833AG2-524 GEN
Solar/Wind Harmer
3.884
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.53
274728ELWOOD EC;5P
Adder
8.311
274731ELWOOD EC;2P
Adder
8.311
274733ELWOOD EC;3P
Adder
8.311
274735ELWOOD EC;4P
Adder
8.311
274800UNIV PARK;3U
Adder
2.946
274801UNIV PARK;4U
Adder
2.946
970073AG2-061 GEN
Solar/Wind Harmer
1.175
972037AH1-567 GEN1
Adder
0.092
274827FISK ;RP
Adder
3.918
274675JOLIET 29;7U
Adder
15.488
274675JOLIET 29;7U
Adder
14.935
274687WILL CNTY;4U
Adder
14.106
274687WILL CNTY;4U
Adder
14.106
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
274744AC1-111 GEN8
Adder
2.817
274746AC1-111 G10
Adder
2.817
276861AD2-134 GEN
Solar/Wind Harmer
0.062
276863AD2-134 GEN
Solar/Wind Harmer
0.062
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.237
971171AH1-044 GEN
Solar/Wind Harmer
6.982
960681AF2-359 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.123
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
971681AH1-341 GEN
Solar/Wind Harmer
5.605
946321AF1-296 GEN
Solar/Wind Harmer
1.935
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.411
970031AG2-029 GEN
Solar/Wind Harmer
1.822
959331AF2-224 GEN
Solar/Wind Harmer
2.262
965041AG1-368 GEN
Solar/Wind Harmer
3.099
247521TR3_G114
Solar/Wind Harmer
0.11
965051AG1-369 GEN
Solar/Wind Harmer
1.514
945631AF1-228 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
6.245
LAGNLTFEXP_LAGN->PJM
CLTF
6.552
TVALTFEXP_TVA->PJM
CLTF
3.106
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.044
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.317
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.627
MECLTFEXP_MEC->PJM
CLTF
8.009
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.393
NYPJM->LTFIMP_NY
CLTF
1.666
LGEELTFEXP_LGEE->PJM
CLTF
5.14
WECLTFEXP_WEC->PJM
CLTF
1.904
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.289
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.27 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2052.4
MW Contribution:
4.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252516AE2-318_GEN
Solar/Wind Harmer
8.746
25196808ZIMRHP
Adder
83.622
25194608D.CRK4
Adder
1.776
252510AF1-249 C
Solar/Wind Harmer
0.057
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.475
25196008MFTGT1
Adder
1.43
253398AE2-221_GEN2
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.627
270273AD2-016 GEN
Solar/Wind Harmer
0.667
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
25326309TAIT D
Adder
0.906
3429421JKCT 10G
Adder
6.589
3429241JKCT 3G
Adder
9.074
24803006KYGER 3HP
50/50
4.179
24802806KYGER 2HP
50/50
4.162
24802906KYGER 2LP
50/50
2.443
25183008BIOENL
50/50
0.032
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
8.168
25194508D.CRK3
Adder
1.527
270269AC2-059
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.575
24803106KYGER 3LP
50/50
2.46
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
70.432
252507AC2-088 GEN
Solar/Wind Harmer
0.376
252519AF1-045_GEN
Solar/Wind Harmer
4.074
25194608D.CRK4
Adder
1.776
25196608WSDLE5
Adder
9.253
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.717
958171AF2-111 GEN
Solar/Wind Harmer
17.947
25196008MFTGT1
Adder
1.385
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.382
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.262
253370AE2-315 SEC1
Adder
1.716
971125AH1-004 GEN
Solar/Wind Harmer
2.323
970107AG2-081 GEN
Solar/Wind Harmer
1.743
25322209TAIT E
Adder
8.074
25322209TAIT E
Adder
7.893
25326109MON D
Adder
1.062
24728805RICHG1
Adder
2.987
24728905RICHG2
Adder
2.987
942891AE2-308 GEN
Solar/Wind Harmer
5.239
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.803
970885AG2-551 GEN
Solar/Wind Harmer
1.601
247621Y3-024
Adder
0.156
964571AG1-320 GEN
Solar/Wind Harmer
4.114
964611AG1-324 GEN
Solar/Wind Harmer
0.333
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
2.045
270031AE2-169
Solar/Wind Harmer
2.337
270599AE1-208 GEN
Solar/Wind Harmer
3.895
970291AG2-192 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.25
971587AH1-292 GEN
Solar/Wind Harmer
3.03
25326509SID D
Adder
0.755
24802606KYGER 1HP
50/50
4.207
24802706KYGER 1LP
50/50
2.467
24803506KYGER 5LP
50/50
2.41
971985AH1-537 GEN
Solar/Wind Harmer
5.9
25196408WSDLE3
Adder
9.526
25196308WSDLE2
Adder
9.443
25196208WSDLE1
Adder
9.419
25196708WSDLE6
Adder
9.395
25196508WSDLE4
Adder
9.159
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
253406AD2-031_GEN
Solar/Wind Harmer
0.493
972163AH1-664 GEN
Solar/Wind Harmer
7.368
972165AH1-665 GEN
Solar/Wind Harmer
5.901
270263AC1-001 GEN
Solar/Wind Harmer
0.65
270340AC2-060 GEN
Solar/Wind Harmer
0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.169
253372AE2-315 SEC3
Adder
1.623
253372AE2-315 SEC3
Adder
1.623
25306009OHH W.
Adder
2.424
3429211JKCT 2G
Adder
8.956
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.299
971029AG2-637 GEN
Solar/Wind Harmer
7.492
241972AD1-140 GEN
Solar/Wind Harmer
0.535
270543AE2-219 C
Solar/Wind Harmer
3.362
247536S-71 GEN
Solar/Wind Harmer
0.185
964611AG1-324 GEN
Solar/Wind Harmer
1.732
971609AH1-304 GEN
Solar/Wind Harmer
0.694
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.79
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.463
963841AG1-237 GEN
Solar/Wind Harmer
1.583
945631AF1-228 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.658
24728605AND G2
Adder
2.584
253333AC1-068 GEN
Solar/Wind Harmer
0.005
270005AE1-210 C O1
Solar/Wind Harmer
0.992
970825AG2-519 GEN
Solar/Wind Harmer
1.611
970091AG2-072 GEN
Adder
49.338
276903AD2-071 C
Solar/Wind Harmer
4.853
970653AG2-424 GEN
Solar/Wind Harmer
2.069
270594AE1-207 GEN
Solar/Wind Harmer
4.771
270032AE2-172
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.758
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.166
963741AG1-226 GEN
Solar/Wind Harmer
8.794
972203AH1-686 GEN
Adder
1.223
964901AG1-354 GEN
Solar/Wind Harmer
5.49
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276621W2-048 GEN
Solar/Wind Harmer
0.169
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.21
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
970191AG2-125 GEN
Solar/Wind Harmer
1.47
3429391JKCT 9G
Adder
6.589
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.224
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970455AG2-298 GEN
Solar/Wind Harmer
1.797
270004AE1-209 GEN
Solar/Wind Harmer
0.992
946031AF1-268 GEN
Solar/Wind Harmer
4.337
970825AG2-519 GEN
Solar/Wind Harmer
3.419
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.615
970653AG2-424 GEN
Solar/Wind Harmer
0.429
270518AE2-148 GEN
Solar/Wind Harmer
0.348
970289AG2-191 GEN
Solar/Wind Harmer
0.457
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
5.894
944531AF1-118 GEN
Solar/Wind Harmer
16.286
24386205FR-12G C
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
42.335
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.495
942481AE2-261 GEN
Solar/Wind Harmer
10.146
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.274
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.558
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.636
939401AE1-172 GEN
Solar/Wind Harmer
2.347
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.122
970569AG2-363 GEN
Solar/Wind Harmer
9.303
971997AH1-543 GEN
Solar/Wind Harmer
1.622
276882AE2-255 GEN
Solar/Wind Harmer
0.36
276805AD2-038 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.499
276708O09 GEN2
Solar/Wind Harmer
0.108
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.204
274674JOLIET 9 ;6U
Adder
6.739
274676JOLIET 29;8U
Adder
13.407
274802UNIV PARK;5U
Adder
2.546
274745AC1-111 GEN9
Adder
2.441
957471AF2-041 GEN
Solar/Wind Harmer
9.139
959081AF2-199 GEN
Solar/Wind Harmer
3.046
971067AG2-660 GEN
Solar/Wind Harmer
1.015
274872LEEDK;1U
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.061
274766LEE CO EC;7U
Adder
4.013
962781AG1-127 GEN
Solar/Wind Harmer
2.898
274682WAUKEGAN ;7U
Adder
7.839
274828WAUKEGAN ;BP
Adder
4.817
274822ROCKFORD ;11
Adder
2.437
970819AG2-516 GEN
Solar/Wind Harmer
3.649
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.501
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.02
963791AG1-232 GEN
Solar/Wind Harmer
4.554
971611AH1-305 GEN
Solar/Wind Harmer
2.005
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.132
276848AB2-070 GEN3
Solar/Wind Harmer
0.132
276849AB2-070 GEN2
Solar/Wind Harmer
0.132
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.273
943851AF1-053 GEN
Solar/Wind Harmer
0.882
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.418
270071AF1-092 GEN
Solar/Wind Harmer
6.13
970169AG2-114 GEN
Solar/Wind Harmer
3.185
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.104
926823AC1-168 GEN
Solar/Wind Harmer
0.529
970073AG2-061 GEN
Solar/Wind Harmer
1.026
276741O09 GEN1
Solar/Wind Harmer
0.108
970833AG2-524 GEN
Solar/Wind Harmer
3.368
970833AG2-524 GEN
Solar/Wind Harmer
2.246
274728ELWOOD EC;5P
Adder
7.204
274731ELWOOD EC;2P
Adder
7.204
274733ELWOOD EC;3P
Adder
7.204
274735ELWOOD EC;4P
Adder
7.204
972227AH1-698 GEN1
Adder
1.143
972228AH1-698 GEN2
Adder
1.623
960591AF2-350 GEN
Solar/Wind Harmer
3.054
274675JOLIET 29;7U
Adder
13.407
274675JOLIET 29;7U
Adder
12.928
274687WILL CNTY;4U
Adder
12.208
274687WILL CNTY;4U
Adder
12.208
274800UNIV PARK;3U
Adder
2.547
274801UNIV PARK;4U
Adder
2.547
971681AH1-341 GEN
Solar/Wind Harmer
4.906
274744AC1-111 GEN8
Adder
2.441
274746AC1-111 G10
Adder
2.441
972267AH1-718 GEN
Adder
1.819
972037AH1-567 GEN1
Adder
0.08
276861AD2-134 GEN
Solar/Wind Harmer
0.054
276863AD2-134 GEN
Solar/Wind Harmer
0.054
971171AH1-044 GEN
Solar/Wind Harmer
6.093
957381AF2-032 GEN
Solar/Wind Harmer
0.768
971993AH1-541 GEN
Solar/Wind Harmer
1.554
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
9.828
959611AF2-252 GEN
Solar/Wind Harmer
1.092
274878BISHOP HL;2U
Solar/Wind Harmer
0.104
276782AC1-033 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.202
942051AE2-217 GEN
Solar/Wind Harmer
5.57
276868AE1-113 GEN
Solar/Wind Harmer
0.616
274879MINONK ;1U
Solar/Wind Harmer
0.129
939351AE1-166 GEN
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.415
274729ELWOOD EC;1P
Adder
7.204
274730ELWOOD EC;6P
Adder
7.204
274734ELWOOD EC;8P
Adder
7.204
274736ELWOOD EC;9P
Adder
7.204
274887GEN-1.85
Solar/Wind Harmer
0.079
276843GEN-1.7
Solar/Wind Harmer
0.099
276806AD2-047 C O1
Solar/Wind Harmer
1.73
972259AH1-714 GEN
Adder
8.342
274676JOLIET 29;8U
Adder
12.928
972038AH1-567 GEN2
Adder
0.159
274803UNIV PARK;6U
Adder
2.546
274855GSG-6 ;RU
Solar/Wind Harmer
0.111
274850MENDOTA H;RU
Solar/Wind Harmer
0.035
946671AF1-331 GEN
Solar/Wind Harmer
0.325
959091AF2-200 GEN
Solar/Wind Harmer
6.093
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
7.765
274760LEE CO EC;1U
Adder
4.061
274767LEE CO EC;8U
Adder
4.013
971087AG2-675 GEN
Solar/Wind Harmer
1.624
274826FISK ;BP
Adder
4.777
943121AE2-341 GEN
Solar/Wind Harmer
5.104
943591AF1-030 GEN
Solar/Wind Harmer
3.394
274682WAUKEGAN ;7U
Adder
7.839
970707AG2-453 GEN
Solar/Wind Harmer
9.937
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
971675AH1-338 GEN
Solar/Wind Harmer
1.188
946321AF1-296 GEN
Solar/Wind Harmer
1.706
274827FISK ;RP
Adder
3.386
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971411AH1-196 GEN
Solar/Wind Harmer
4.564
944541AF1-119 GEN
Solar/Wind Harmer
0.265
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.175
942221AE2-234 GEN
Solar/Wind Harmer
1.514
970329AG2-216 GEN
Solar/Wind Harmer
1.606
970241AG2-163 GEN
Solar/Wind Harmer
2.168
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.406
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.149
276911AD2-131_GEN
Solar/Wind Harmer
0.471
964781AG1-341 GEN
Solar/Wind Harmer
3.596
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.19
942861AE2-305 GEN
Solar/Wind Harmer
2.579
960611AF2-352 GEN
Solar/Wind Harmer
1.092
942111AE2-223 GEN
Solar/Wind Harmer
1.058
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.122
971485AH1-239 GEN
Solar/Wind Harmer
2.492
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.619
966021AG1-471 GEN
Solar/Wind Harmer
1.662
276897AD1-100 C
Solar/Wind Harmer
7.68
958481AF2-142 GEN
Solar/Wind Harmer
4.605
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.494
276893AG1-478 C
Solar/Wind Harmer
0.204
274888KELLY CRK;1U
Solar/Wind Harmer
0.178
276776AD2-060 GEN
Solar/Wind Harmer
0.326
958011AF2-095 GEN
Solar/Wind Harmer
4.397
274674JOLIET 9 ;6U
Adder
6.739
970941AG2-585 GEN
Solar/Wind Harmer
1.679
971341AH1-150 GEN
Solar/Wind Harmer
6.093
971343AH1-151 GEN
Solar/Wind Harmer
6.093
938861AE1-114 GEN
Solar/Wind Harmer
1.726
962691AG1-118 GEN
Solar/Wind Harmer
9.136
274764LEE CO EC;5U
Adder
4.07
274765LEE CO EC;6U
Adder
4.07
274762LEE CO EC;3U
Adder
4.061
274763LEE CO EC;4U
Adder
4.023
274696ROCKY RD ;4P
Adder
4.974
274695ROCKY RD ;2P
Adder
4.859
274693ROCKY RD ;1P
Adder
4.811
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.19
274683WAUKEGAN ;8U
Adder
7.747
972235AH1-702 GEN1
Adder
1.099
972236AH1-702 GEN2
Adder
0.956
237033AB1-150 GEN
Solar/Wind Helper
0.404
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
TVALTFEXP_TVA->PJM
CLTF
2.665
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.274
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.431
MECLTFEXP_MEC->PJM
CLTF
7.137
SIGELTFEXP_SIGE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.865
NYPJM->LTFIMP_NY
CLTF
1.597
LGEELTFEXP_LGEE->PJM
CLTF
5.305
WECLTFEXP_WEC->PJM
CLTF
1.662
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.31 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1652.5
MW Contribution:
6.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
25194408D.CRK1
Adder
7.451
25194508D.CRK3
Adder
1.393
252509AD1-136 GEN
Solar/Wind Harmer
0.247
24728805RICHG1
Adder
2.815
24728905RICHG2
Adder
2.815
926881AC1-175 GEN
Solar/Wind Harmer
4.028
25183208HLCRTG
Solar/Wind Harmer
4.167
270383AD1-128 GEN
Solar/Wind Harmer
4.197
970883AG2-550 GEN
Solar/Wind Harmer
6.559
970885AG2-551 GEN
Solar/Wind Harmer
1.525
24725505WLD G2 C
Solar/Wind Harmer
2.554
24699105WLD G1 C
Solar/Wind Harmer
2.524
247621Y3-024
Adder
0.151
964611AG1-324 GEN
Solar/Wind Harmer
0.327
270201AC2-176 GEN
Solar/Wind Harmer
3.18
270031AE2-169
Solar/Wind Harmer
4.953
270599AE1-208 GEN
Solar/Wind Harmer
4.953
970291AG2-192 GEN
Solar/Wind Harmer
0.79
970291AG2-192 GEN
Solar/Wind Harmer
0.254
253349AC2-067 GEN
Solar/Wind Harmer
1.23
253400AC2-068 GEN
Solar/Wind Harmer
0.495
945391AF1-204 GEN
Solar/Wind Harmer
8.204
964571AG1-320 GEN
Solar/Wind Harmer
4.812
253370AE2-315 SEC1
Adder
1.168
25322209TAIT E
Adder
5.648
25322209TAIT E
Adder
5.521
944541AF1-119 GEN
Solar/Wind Harmer
2.383
960971AF2-388 GEN
Solar/Wind Harmer
6.222
970241AG2-163 GEN
Solar/Wind Harmer
14.001
25326109MON D
Adder
0.735
24387305FR-4G C
Solar/Wind Harmer
2.757
966841AG1-555 GEN
Solar/Wind Harmer
1.362
942221AE2-234 GEN
Solar/Wind Harmer
1.865
270180AB1-006 GEN1
Solar/Wind Harmer
3.807
24697605MDL-3G C
Solar/Wind Harmer
1.951
24755605MDL-5G
Solar/Wind Harmer
1.276
24697905MDL-4G C
Solar/Wind Harmer
1.214
270181AB1-006 GEN2
Solar/Wind Harmer
0.378
945421AF1-207 GEN
Solar/Wind Harmer
7.341
957841AF2-078 GEN
Solar/Wind Harmer
3.16
972043AH1-570 GEN
Solar/Wind Harmer
1.299
972045AH1-571 GEN
Solar/Wind Harmer
1.039
971125AH1-004 GEN
Solar/Wind Harmer
2.039
970107AG2-081 GEN
Solar/Wind Harmer
1.529
276916AD2-100_GEN
Solar/Wind Harmer
10.576
276911AD2-131_GEN
Solar/Wind Harmer
2.137
276615X2-022 GEN
Solar/Wind Harmer
0.977
276838X2-022 GEN2
Solar/Wind Harmer
0.116
274880W4-005 GEN4
Solar/Wind Harmer
1.506
276174W4-005 GEN2
Solar/Wind Harmer
1.506
960611AF2-352 GEN
Solar/Wind Harmer
1.127
25196008MFTGT1
Adder
1.41
25194608D.CRK4
Adder
1.62
252510AF1-249 C
Solar/Wind Harmer
0.398
252516AE2-318_GEN
Solar/Wind Harmer
8.654
25196808ZIMRHP
Adder
62.026
270222AC2-111 GEN
Solar/Wind Harmer
3.535
944031AF1-071 GEN
Solar/Wind Harmer
0.795
970091AG2-072 GEN
Adder
56.358
942081AE2-220 GEN
Solar/Wind Harmer
4.616
270209AC1-174_GEN
Solar/Wind Harmer
2.937
270437AC2-090 C
Solar/Wind Harmer
4.028
270239V3-007_GEN1
Solar/Wind Harmer
1.242
24728605AND G2
Adder
2.609
270005AE1-210 C O1
Solar/Wind Harmer
3.603
970825AG2-519 GEN
Solar/Wind Harmer
1.361
276903AD2-071 C
Solar/Wind Harmer
6.32
270594AE1-207 GEN
Solar/Wind Harmer
8.405
270032AE2-172
Solar/Wind Harmer
2.878
945371AF1-202 GEN
Solar/Wind Harmer
4.219
253370AE2-315 SEC1
Adder
1.168
253371AE2-315 SEC2
Adder
1.104
958861AF2-177 GEN
Solar/Wind Harmer
6.355
25326309TAIT D
Adder
0.634
965651AG1-433 GEN
Solar/Wind Harmer
3.111
270024AE2-089 GEN
Solar/Wind Harmer
2.629
963741AG1-226 GEN
Solar/Wind Harmer
25.203
339221AD2-048_GEN
Solar/Wind Harmer
0.859
24385905FR-11G C
Solar/Wind Harmer
4.511
24386605FR-22G C
Solar/Wind Harmer
2.334
970653AG2-424 GEN
Solar/Wind Harmer
2.607
24791305MDL-5G
Solar/Wind Harmer
1.276
940581AE2-045 GEN
Solar/Wind Harmer
5.184
971605AH1-302 GEN
Solar/Wind Harmer
4.432
965911AG1-460 GEN
Solar/Wind Harmer
0.7
943111AE2-339 GEN
Solar/Wind Harmer
0.443
276621W2-048 GEN
Solar/Wind Harmer
3.11
276686W4-005 GEN3
Solar/Wind Harmer
1.506
964861AG1-349 GEN
Solar/Wind Harmer
3.886
971917AH1-482 GEN
Solar/Wind Harmer
4.484
958381AF2-132 GEN
Solar/Wind Harmer
4.474
270055AF2-134 C O1
Solar/Wind Harmer
1.459
276655WTG1_EQ
Solar/Wind Harmer
4.203
276656WTG2_EQ
Solar/Wind Harmer
0.556
939741AE1-205 GEN
Solar/Wind Harmer
9.631
339211AE2-254 GEN
Solar/Wind Harmer
0.727
970373AG2-245 GEN
Solar/Wind Harmer
9.915
339241AF1-083 GEN
Solar/Wind Harmer
0.777
3429421JKCT 10G
Adder
3.875
939401AE1-172 GEN
Solar/Wind Harmer
6.459
274848CAMPGROVE;RU
Solar/Wind Harmer
2.964
276646AC1-214 GEN2
Solar/Wind Harmer
0.614
3429241JKCT 3G
Adder
5.431
274732ELWOOD EC;7P
Adder
7.412
274674JOLIET 9 ;6U
Adder
6.933
274676JOLIET 29;8U
Adder
13.79
274802UNIV PARK;5U
Adder
2.62
274745AC1-111 GEN9
Adder
2.509
274812UNIV PK N;8U
Adder
2.247
274773LINCOLN ;4U
Adder
3.782
274774LINCOLN ;5U
Adder
3.782
274682WAUKEGAN ;7U
Adder
8.051
274828WAUKEGAN ;BP
Adder
4.947
274751CRETE EC ;1U
Adder
3.69
274754CRETE EC ;4U
Adder
3.69
274723RIVER EC ;12
Adder
8.017
270273AD2-016 GEN
Solar/Wind Helper
1.464
270331AC1-082 GEN3
Solar/Wind Helper
0.094
960001AF2-291 GEN
Solar/Wind Helper
0.555
970569AG2-363 GEN
Solar/Wind Harmer
11.221
270535AF1-215 GEN1
Solar/Wind Harmer
2.188
270536AF1-215 GEN2
Solar/Wind Harmer
2.188
942111AE2-223 GEN
Solar/Wind Harmer
3.947
942891AE2-308 GEN
Solar/Wind Harmer
4.665
276645AC1-214 GEN1
Solar/Wind Harmer
0.614
274674JOLIET 9 ;6U
Adder
6.933
274805UNIV PK N;1U
Adder
2.252
274808UNIV PK N;4U
Adder
2.237
274696ROCKY RD ;4P
Adder
5.109
274695ROCKY RD ;2P
Adder
4.991
274693ROCKY RD ;1P
Adder
4.942
274697ROCKY RD ;3P
Adder
1.356
274770LINCOLN ;1U
Adder
3.782
274771LINCOLN ;2U
Adder
3.782
274683WAUKEGAN ;8U
Adder
9.438
274683WAUKEGAN ;8U
Adder
7.956
274764LEE CO EC;5U
Adder
4.17
274765LEE CO EC;6U
Adder
0.868
927014AC1-188 GEN
Solar/Wind Helper
0.884
25196108MFTGT2
Adder
1.554
25196108MFTGT2
Adder
1.443
25196408WSDLE3
Adder
8.826
25196308WSDLE2
Adder
8.749
25196208WSDLE1
Adder
8.727
25196708WSDLE6
Adder
8.705
25196508WSDLE4
Adder
8.486
971985AH1-537 GEN
Solar/Wind Harmer
17.68
270356AE2-297 GEN
Solar/Wind Harmer
3.518
971029AG2-637 GEN
Solar/Wind Harmer
10.113
270543AE2-219 C
Solar/Wind Harmer
6.559
270444AC2-157 GEN1
Solar/Wind Harmer
3.564
270445AC2-157 GEN2
Solar/Wind Harmer
3.564
247536S-71 GEN
Solar/Wind Harmer
2.584
964611AG1-324 GEN
Solar/Wind Harmer
2.438
961761AG1-017 GEN
Solar/Wind Harmer
0.265
970289AG2-191 GEN
Solar/Wind Harmer
1.154
945581AF1-223 GEN
Solar/Wind Harmer
2.743
339216AC1-074 GEN
Solar/Wind Harmer
0.988
25306009OHH W.
Adder
1.692
253372AE2-315 SEC3
Adder
1.104
253372AE2-315 SEC3
Adder
1.104
958711AF2-162 GEN
Solar/Wind Harmer
0.576
963841AG1-237 GEN
Solar/Wind Harmer
6.03
24386405FR-21G C
Solar/Wind Harmer
2.334
24387005FR-3G C
Solar/Wind Harmer
2.147
24729505KEY G4
Adder
3.451
946581AF1-322 GEN
Solar/Wind Harmer
5.415
24691005MDL-2G C
Solar/Wind Harmer
1.957
944221AF1-090 GEN
Solar/Wind Harmer
5.569
959141AF2-205 GEN
Solar/Wind Harmer
3.042
958391AF2-133 GEN
Solar/Wind Harmer
4.525
276763AC1-053 GEN1
Solar/Wind Harmer
1.968
276764AC1-053 GEN2
Solar/Wind Harmer
1.968
276668AB2-070 GEN1
Solar/Wind Harmer
1.102
276848AB2-070 GEN3
Solar/Wind Harmer
1.102
276849AB2-070 GEN2
Solar/Wind Harmer
1.102
274853TWINGROVE;U1
Solar/Wind Harmer
3.491
274854TWINGROVE;U2
Solar/Wind Harmer
3.418
276726Z2-087_GEN
Solar/Wind Harmer
3.807
959341AF2-225 GEN
Solar/Wind Harmer
7.223
970169AG2-114 GEN
Solar/Wind Harmer
4.707
963791AG1-232 GEN
Solar/Wind Harmer
6.325
274863CRW1-WTG
Solar/Wind Harmer
2.609
274864CRW2-WTG
Solar/Wind Harmer
2.609
270071AF1-092 GEN
Solar/Wind Harmer
6.933
3429211JKCT 2G
Adder
5.361
926823AC1-168 GEN
Solar/Wind Harmer
1.969
274877BISHOP HL;1U
Solar/Wind Harmer
1.543
274728ELWOOD EC;5P
Adder
7.412
274731ELWOOD EC;2P
Adder
7.412
274733ELWOOD EC;3P
Adder
7.412
274735ELWOOD EC;4P
Adder
7.412
972228AH1-698 GEN2
Adder
1.67
972227AH1-698 GEN1
Adder
1.176
274800UNIV PARK;3U
Adder
2.621
274801UNIV PARK;4U
Adder
2.621
274675JOLIET 29;7U
Adder
13.79
274675JOLIET 29;7U
Adder
13.298
972037AH1-567 GEN1
Adder
0.082
274687WILL CNTY;4U
Adder
12.558
274687WILL CNTY;4U
Adder
12.558
274827FISK ;RP
Adder
3.484
274744AC1-111 GEN8
Adder
2.509
274746AC1-111 G10
Adder
2.509
274775LINCOLN ;6U
Adder
3.782
274776LINCOLN ;7U
Adder
3.782
274777LINCOLN ;8U
Adder
3.782
972267AH1-718 GEN
Adder
1.863
270263AC1-001 GEN
Solar/Wind Helper
0.628
270291AC1-194 GEN
Solar/Wind Helper
0.524
25196008MFTGT1
Adder
1.366
252524AE2-267 GEN
Solar/Wind Harmer
1.575
25196608WSDLE5
Adder
8.573
25194608D.CRK4
Adder
1.62
252507AC2-088 GEN
Solar/Wind Harmer
1.729
252519AF1-045_GEN
Solar/Wind Harmer
3.15
24379505HDWTR1G C
Solar/Wind Harmer
5.707
270240V3-007_GEN2
Solar/Wind Harmer
4.465
24728705AND G3
Adder
5.457
24728505AND G1
Adder
2.609
270004AE1-209 GEN
Solar/Wind Harmer
3.603
970825AG2-519 GEN
Solar/Wind Harmer
3.655
946031AF1-268 GEN
Solar/Wind Harmer
5.382
962031AG1-047 GEN
Solar/Wind Harmer
1.871
957741AF2-068 GEN
Solar/Wind Harmer
9.281
965461AG1-414 GEN
Solar/Wind Harmer
1.378
970289AG2-191 GEN
Solar/Wind Harmer
0.466
247642Z2-115 C
Solar/Wind Harmer
0.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.268
970193AG2-126 GEN
Solar/Wind Harmer
8.831
253303V4-073 C
Solar/Wind Harmer
0.068
253370AE2-315 SEC1
Adder
1.168
253371AE2-315 SEC2
Adder
1.104
960071AF2-298 GEN
Solar/Wind Harmer
0.881
970455AG2-298 GEN
Solar/Wind Harmer
2.002
24386205FR-12G C
Solar/Wind Harmer
2.326
970653AG2-424 GEN
Solar/Wind Harmer
0.377
24690905MDL-1G C
Solar/Wind Harmer
4.249
970781AG2-491 GEN
Solar/Wind Harmer
5.293
944531AF1-118 GEN
Solar/Wind Harmer
18.147
942481AE2-261 GEN
Solar/Wind Harmer
15.006
957381AF2-032 GEN
Solar/Wind Harmer
1.003
276785W4-005 GEN1
Solar/Wind Harmer
1.506
971993AH1-541 GEN
Solar/Wind Harmer
4.6
964401AG1-302 GEN
Solar/Wind Harmer
4.474
965091AG1-374 GEN
Solar/Wind Harmer
14.538
959611AF2-252 GEN
Solar/Wind Harmer
1.127
339206AE1-143 GEN
Solar/Wind Harmer
1.012
3429391JKCT 9G
Adder
3.875
274851PROVIDENC;RU
Solar/Wind Harmer
1.306
274849CRESCENT ;1U
Solar/Wind Harmer
0.848
276782AC1-033 GEN
Solar/Wind Harmer
1.823
274878BISHOP HL;2U
Solar/Wind Harmer
1.543
274729ELWOOD EC;1P
Adder
7.412
274730ELWOOD EC;6P
Adder
7.412
274734ELWOOD EC;8P
Adder
7.412
274736ELWOOD EC;9P
Adder
7.412
972259AH1-714 GEN
Adder
8.585
972038AH1-567 GEN2
Adder
0.164
274676JOLIET 29;8U
Adder
13.298
274803UNIV PARK;6U
Adder
2.62
274826FISK ;BP
Adder
4.915
274814UNIV PK N;0U
Adder
2.267
274807UNIV PK N;3U
Adder
2.262
274811UNIV PK N;7U
Adder
2.247
274772LINCOLN ;3U
Adder
3.782
274682WAUKEGAN ;7U
Adder
8.051
274752CRETE EC ;2U
Adder
3.69
274753CRETE EC ;3U
Adder
3.69
274724RIVER EC ;11
Adder
7.922
957541AF2-048 GEN
Solar/Wind Helper
0.884
270330AC1-082 GEN2
Solar/Wind Helper
0.094
270329AC1-082 GEN1
Solar/Wind Helper
0.094
970571AG2-364 GEN
Solar/Wind Harmer
7.481
LAGNLTFEXP_LAGN->PJM
CLTF
5.26
TVALTFEXP_TVA->PJM
CLTF
2.352
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.345
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.476
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.36
MECLTFEXP_MEC->PJM
CLTF
7.227
SIGELTFEXP_SIGE->PJM
CLTF
0.329
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.922
NYPJM->LTFIMP_NY
CLTF
1.096
LGEELTFEXP_LGEE->PJM
CLTF
5.198
WECLTFEXP_WEC->PJM
CLTF
1.703
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.674
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1585.6
MW Contribution:
6.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
25196108MFTGT2
Adder
1.561
25196108MFTGT2
Adder
1.449
25196408WSDLE3
Adder
8.863
25196308WSDLE2
Adder
8.786
25196208WSDLE1
Adder
8.764
25196708WSDLE6
Adder
8.742
25196508WSDLE4
Adder
8.522
971985AH1-537 GEN
Solar/Wind Harmer
17.756
270356AE2-297 GEN
Solar/Wind Harmer
3.537
971029AG2-637 GEN
Solar/Wind Harmer
10.176
270543AE2-219 C
Solar/Wind Harmer
6.601
270444AC2-157 GEN1
Solar/Wind Harmer
3.588
270445AC2-157 GEN2
Solar/Wind Harmer
3.588
247536S-71 GEN
Solar/Wind Harmer
2.601
964611AG1-324 GEN
Solar/Wind Harmer
2.454
961761AG1-017 GEN
Solar/Wind Harmer
0.267
970289AG2-191 GEN
Solar/Wind Harmer
1.163
945581AF1-223 GEN
Solar/Wind Harmer
2.762
339216AC1-074 GEN
Solar/Wind Harmer
0.995
25306009OHH W.
Adder
1.704
253372AE2-315 SEC3
Adder
1.112
253372AE2-315 SEC3
Adder
1.112
958711AF2-162 GEN
Solar/Wind Harmer
0.58
963841AG1-237 GEN
Solar/Wind Harmer
6.076
24386405FR-21G C
Solar/Wind Harmer
2.352
24387005FR-3G C
Solar/Wind Harmer
2.164
24729505KEY G4
Adder
3.478
946581AF1-322 GEN
Solar/Wind Harmer
5.459
24691005MDL-2G C
Solar/Wind Harmer
1.973
944221AF1-090 GEN
Solar/Wind Harmer
5.616
25196008MFTGT1
Adder
1.416
25194608D.CRK4
Adder
1.627
252510AF1-249 C
Solar/Wind Harmer
0.4
252516AE2-318_GEN
Solar/Wind Harmer
8.697
25196808ZIMRHP
Adder
62.349
270222AC2-111 GEN
Solar/Wind Harmer
3.554
944031AF1-071 GEN
Solar/Wind Harmer
0.8
970091AG2-072 GEN
Adder
56.685
942081AE2-220 GEN
Solar/Wind Harmer
4.643
270209AC1-174_GEN
Solar/Wind Harmer
2.954
270437AC2-090 C
Solar/Wind Harmer
4.052
270239V3-007_GEN1
Solar/Wind Harmer
1.249
24728605AND G2
Adder
2.625
270005AE1-210 C O1
Solar/Wind Harmer
3.626
970825AG2-519 GEN
Solar/Wind Harmer
1.37
276903AD2-071 C
Solar/Wind Harmer
6.363
270594AE1-207 GEN
Solar/Wind Harmer
8.462
270032AE2-172
Solar/Wind Harmer
2.898
945371AF1-202 GEN
Solar/Wind Harmer
4.249
253370AE2-315 SEC1
Adder
1.176
253371AE2-315 SEC2
Adder
1.112
958861AF2-177 GEN
Solar/Wind Harmer
6.402
25326309TAIT D
Adder
0.639
965651AG1-433 GEN
Solar/Wind Harmer
3.134
270024AE2-089 GEN
Solar/Wind Harmer
2.649
963741AG1-226 GEN
Solar/Wind Harmer
25.394
339221AD2-048_GEN
Solar/Wind Harmer
0.866
24385905FR-11G C
Solar/Wind Harmer
4.546
24386605FR-22G C
Solar/Wind Harmer
2.352
970653AG2-424 GEN
Solar/Wind Harmer
2.628
24791305MDL-5G
Solar/Wind Harmer
1.286
940581AE2-045 GEN
Solar/Wind Harmer
5.227
971605AH1-302 GEN
Solar/Wind Harmer
4.47
965911AG1-460 GEN
Solar/Wind Harmer
0.706
943111AE2-339 GEN
Solar/Wind Harmer
0.446
276621W2-048 GEN
Solar/Wind Harmer
3.137
276686W4-005 GEN3
Solar/Wind Harmer
1.518
964861AG1-349 GEN
Solar/Wind Harmer
3.92
971917AH1-482 GEN
Solar/Wind Harmer
4.523
958381AF2-132 GEN
Solar/Wind Harmer
4.513
270055AF2-134 C O1
Solar/Wind Harmer
1.472
276655WTG1_EQ
Solar/Wind Harmer
4.24
276656WTG2_EQ
Solar/Wind Harmer
0.561
939741AE1-205 GEN
Solar/Wind Harmer
9.716
339211AE2-254 GEN
Solar/Wind Harmer
0.733
970373AG2-245 GEN
Solar/Wind Harmer
10.005
339241AF1-083 GEN
Solar/Wind Harmer
0.784
3429421JKCT 10G
Adder
3.91
939401AE1-172 GEN
Solar/Wind Harmer
6.518
274848CAMPGROVE;RU
Solar/Wind Harmer
2.991
276646AC1-214 GEN2
Solar/Wind Harmer
0.62
3429241JKCT 3G
Adder
5.482
274732ELWOOD EC;7P
Adder
7.482
274674JOLIET 9 ;6U
Adder
6.998
274676JOLIET 29;8U
Adder
13.921
274802UNIV PARK;5U
Adder
2.645
274745AC1-111 GEN9
Adder
2.533
274812UNIV PK N;8U
Adder
2.268
274773LINCOLN ;4U
Adder
3.818
274774LINCOLN ;5U
Adder
3.818
25196008MFTGT1
Adder
1.371
252524AE2-267 GEN
Solar/Wind Harmer
1.582
25196608WSDLE5
Adder
8.61
25194608D.CRK4
Adder
1.627
252507AC2-088 GEN
Solar/Wind Harmer
1.737
252519AF1-045_GEN
Solar/Wind Harmer
3.165
24379505HDWTR1G C
Solar/Wind Harmer
5.74
270240V3-007_GEN2
Solar/Wind Harmer
4.491
24728705AND G3
Adder
5.491
24728505AND G1
Adder
2.625
270004AE1-209 GEN
Solar/Wind Harmer
3.626
970825AG2-519 GEN
Solar/Wind Harmer
3.679
946031AF1-268 GEN
Solar/Wind Harmer
5.417
962031AG1-047 GEN
Solar/Wind Harmer
1.884
957741AF2-068 GEN
Solar/Wind Harmer
9.345
965461AG1-414 GEN
Solar/Wind Harmer
1.387
970289AG2-191 GEN
Solar/Wind Harmer
0.47
247642Z2-115 C
Solar/Wind Harmer
0.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.269
970193AG2-126 GEN
Solar/Wind Harmer
8.895
253303V4-073 C
Solar/Wind Harmer
0.068
253370AE2-315 SEC1
Adder
1.176
253371AE2-315 SEC2
Adder
1.112
960071AF2-298 GEN
Solar/Wind Harmer
0.887
970455AG2-298 GEN
Solar/Wind Harmer
2.017
24386205FR-12G C
Solar/Wind Harmer
2.344
970653AG2-424 GEN
Solar/Wind Harmer
0.38
24690905MDL-1G C
Solar/Wind Harmer
4.283
970781AG2-491 GEN
Solar/Wind Harmer
5.335
944531AF1-118 GEN
Solar/Wind Harmer
18.296
942481AE2-261 GEN
Solar/Wind Harmer
15.134
957381AF2-032 GEN
Solar/Wind Harmer
1.011
276785W4-005 GEN1
Solar/Wind Harmer
1.518
971993AH1-541 GEN
Solar/Wind Harmer
4.64
964401AG1-302 GEN
Solar/Wind Harmer
4.513
965091AG1-374 GEN
Solar/Wind Harmer
14.666
959611AF2-252 GEN
Solar/Wind Harmer
1.137
339206AE1-143 GEN
Solar/Wind Harmer
1.021
3429391JKCT 9G
Adder
3.91
274851PROVIDENC;RU
Solar/Wind Harmer
1.318
274849CRESCENT ;1U
Solar/Wind Harmer
0.856
276782AC1-033 GEN
Solar/Wind Harmer
1.84
274878BISHOP HL;2U
Solar/Wind Harmer
1.557
274729ELWOOD EC;1P
Adder
7.482
274730ELWOOD EC;6P
Adder
7.482
274734ELWOOD EC;8P
Adder
7.482
274736ELWOOD EC;9P
Adder
7.482
972259AH1-714 GEN
Adder
8.666
972038AH1-567 GEN2
Adder
0.166
274676JOLIET 29;8U
Adder
13.424
274803UNIV PARK;6U
Adder
2.645
274826FISK ;BP
Adder
4.962
274814UNIV PK N;0U
Adder
2.288
274807UNIV PK N;3U
Adder
2.283
274811UNIV PK N;7U
Adder
2.268
274772LINCOLN ;3U
Adder
3.818
274682WAUKEGAN ;7U
Adder
8.127
274828WAUKEGAN ;BP
Adder
4.994
274751CRETE EC ;1U
Adder
3.725
274754CRETE EC ;4U
Adder
3.725
274723RIVER EC ;12
Adder
8.094
270273AD2-016 GEN
Solar/Wind Helper
1.452
270331AC1-082 GEN3
Solar/Wind Helper
0.093
970569AG2-363 GEN
Solar/Wind Harmer
11.326
959141AF2-205 GEN
Solar/Wind Harmer
3.067
958391AF2-133 GEN
Solar/Wind Harmer
4.563
276763AC1-053 GEN1
Solar/Wind Harmer
1.985
276764AC1-053 GEN2
Solar/Wind Harmer
1.985
276668AB2-070 GEN1
Solar/Wind Harmer
1.111
276848AB2-070 GEN3
Solar/Wind Harmer
1.111
276849AB2-070 GEN2
Solar/Wind Harmer
1.111
274853TWINGROVE;U1
Solar/Wind Harmer
3.522
274854TWINGROVE;U2
Solar/Wind Harmer
3.448
276726Z2-087_GEN
Solar/Wind Harmer
3.841
959341AF2-225 GEN
Solar/Wind Harmer
7.287
970169AG2-114 GEN
Solar/Wind Harmer
4.75
963791AG1-232 GEN
Solar/Wind Harmer
6.383
274863CRW1-WTG
Solar/Wind Harmer
2.632
274864CRW2-WTG
Solar/Wind Harmer
2.632
270071AF1-092 GEN
Solar/Wind Harmer
6.997
3429211JKCT 2G
Adder
5.411
926823AC1-168 GEN
Solar/Wind Harmer
1.987
274877BISHOP HL;1U
Solar/Wind Harmer
1.557
274731ELWOOD EC;2P
Adder
7.482
274733ELWOOD EC;3P
Adder
7.482
274735ELWOOD EC;4P
Adder
7.482
972228AH1-698 GEN2
Adder
1.686
972227AH1-698 GEN1
Adder
1.187
274728ELWOOD EC;5P
Adder
7.482
274800UNIV PARK;3U
Adder
2.646
274801UNIV PARK;4U
Adder
2.646
274675JOLIET 29;7U
Adder
13.921
274675JOLIET 29;7U
Adder
13.424
274687WILL CNTY;4U
Adder
12.677
274687WILL CNTY;4U
Adder
12.677
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.517
274744AC1-111 GEN8
Adder
2.533
274746AC1-111 G10
Adder
2.533
274775LINCOLN ;6U
Adder
3.818
274776LINCOLN ;7U
Adder
3.818
274777LINCOLN ;8U
Adder
3.818
972267AH1-718 GEN
Adder
1.88
270263AC1-001 GEN
Solar/Wind Helper
0.624
270291AC1-194 GEN
Solar/Wind Helper
0.52
274682WAUKEGAN ;7U
Adder
8.127
274752CRETE EC ;2U
Adder
3.725
274753CRETE EC ;3U
Adder
3.725
274724RIVER EC ;11
Adder
7.998
957541AF2-048 GEN
Solar/Wind Helper
0.878
270330AC1-082 GEN2
Solar/Wind Helper
0.093
270329AC1-082 GEN1
Solar/Wind Helper
0.093
970571AG2-364 GEN
Solar/Wind Harmer
7.551
25194408D.CRK1
Adder
7.483
25194508D.CRK3
Adder
1.399
252509AD1-136 GEN
Solar/Wind Harmer
0.248
24728805RICHG1
Adder
2.831
24728905RICHG2
Adder
2.831
926881AC1-175 GEN
Solar/Wind Harmer
4.052
25183208HLCRTG
Solar/Wind Harmer
4.193
270383AD1-128 GEN
Solar/Wind Harmer
4.223
970883AG2-550 GEN
Solar/Wind Harmer
6.601
970885AG2-551 GEN
Solar/Wind Harmer
1.535
24725505WLD G2 C
Solar/Wind Harmer
2.571
24699105WLD G1 C
Solar/Wind Harmer
2.541
247621Y3-024
Adder
0.152
964611AG1-324 GEN
Solar/Wind Harmer
0.329
270201AC2-176 GEN
Solar/Wind Harmer
3.202
270031AE2-169
Solar/Wind Harmer
4.988
270599AE1-208 GEN
Solar/Wind Harmer
4.988
970291AG2-192 GEN
Solar/Wind Harmer
0.795
970291AG2-192 GEN
Solar/Wind Harmer
0.256
253349AC2-067 GEN
Solar/Wind Harmer
1.239
253400AC2-068 GEN
Solar/Wind Harmer
0.498
945391AF1-204 GEN
Solar/Wind Harmer
8.264
964571AG1-320 GEN
Solar/Wind Harmer
4.847
253370AE2-315 SEC1
Adder
1.176
25322209TAIT E
Adder
5.689
25322209TAIT E
Adder
5.561
944541AF1-119 GEN
Solar/Wind Harmer
2.401
960971AF2-388 GEN
Solar/Wind Harmer
6.268
970241AG2-163 GEN
Solar/Wind Harmer
14.108
25326109MON D
Adder
0.741
24387305FR-4G C
Solar/Wind Harmer
2.778
966841AG1-555 GEN
Solar/Wind Harmer
1.373
942221AE2-234 GEN
Solar/Wind Harmer
1.88
270180AB1-006 GEN1
Solar/Wind Harmer
3.837
24697605MDL-3G C
Solar/Wind Harmer
1.967
24755605MDL-5G
Solar/Wind Harmer
1.286
24697905MDL-4G C
Solar/Wind Harmer
1.224
270181AB1-006 GEN2
Solar/Wind Harmer
0.382
945421AF1-207 GEN
Solar/Wind Harmer
7.401
957841AF2-078 GEN
Solar/Wind Harmer
3.186
972043AH1-570 GEN
Solar/Wind Harmer
1.31
972045AH1-571 GEN
Solar/Wind Harmer
1.048
971125AH1-004 GEN
Solar/Wind Harmer
2.056
970107AG2-081 GEN
Solar/Wind Harmer
1.542
276916AD2-100_GEN
Solar/Wind Harmer
10.665
276911AD2-131_GEN
Solar/Wind Harmer
2.155
276615X2-022 GEN
Solar/Wind Harmer
0.985
276838X2-022 GEN2
Solar/Wind Harmer
0.117
274880W4-005 GEN4
Solar/Wind Harmer
1.518
276174W4-005 GEN2
Solar/Wind Harmer
1.518
960611AF2-352 GEN
Solar/Wind Harmer
1.137
270535AF1-215 GEN1
Solar/Wind Harmer
2.208
270536AF1-215 GEN2
Solar/Wind Harmer
2.208
942111AE2-223 GEN
Solar/Wind Harmer
3.982
942891AE2-308 GEN
Solar/Wind Harmer
4.707
276645AC1-214 GEN1
Solar/Wind Harmer
0.62
274674JOLIET 9 ;6U
Adder
6.998
274805UNIV PK N;1U
Adder
2.273
274808UNIV PK N;4U
Adder
2.258
274696ROCKY RD ;4P
Adder
5.158
274695ROCKY RD ;2P
Adder
5.039
274693ROCKY RD ;1P
Adder
4.989
274697ROCKY RD ;3P
Adder
1.369
274770LINCOLN ;1U
Adder
3.818
274771LINCOLN ;2U
Adder
3.818
274683WAUKEGAN ;8U
Adder
9.528
274683WAUKEGAN ;8U
Adder
8.032
274764LEE CO EC;5U
Adder
4.21
274765LEE CO EC;6U
Adder
0.877
927014AC1-188 GEN
Solar/Wind Helper
0.878
LAGNLTFEXP_LAGN->PJM
CLTF
5.346
TVALTFEXP_TVA->PJM
CLTF
2.395
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.328
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.099
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.523
MECLTFEXP_MEC->PJM
CLTF
7.298
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.498
NYPJM->LTFIMP_NY
CLTF
1.069
LGEELTFEXP_LGEE->PJM
CLTF
5.227
WECLTFEXP_WEC->PJM
CLTF
1.719
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.646
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
AH1-155LTFEXP_AH1-155->PJM
LTF
0.17

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1393.24
MW Contribution:
4.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.038
253371AE2-315 SEC2
50/50
2.873
25322309TAIT W
50/50
0.713
25322209TAIT E
50/50
0.712
25326309TAIT D
50/50
1.629
253398AE2-221_GEN2
Solar/Wind Harmer
6.166
253316AC1-085 GEN3
Solar/Wind Harmer
9.612
946171AF1-282 GEN
Solar/Wind Harmer
11.481
252516AE2-318_GEN
Solar/Wind Harmer
8.856
25194608D.CRK4
Adder
1.445
252510AF1-249 C
Solar/Wind Harmer
0.364
253333AC1-068 GEN
Solar/Wind Harmer
0.898
25196808ZIMRHP
Adder
60.02
270222AC2-111 GEN
Solar/Wind Harmer
3.259
944031AF1-071 GEN
Solar/Wind Harmer
0.733
25196008MFTGT1
Adder
0.973
945681AF1-233 GEN
Solar/Wind Harmer
12.401
339221AD2-048_GEN
Solar/Wind Harmer
0.885
943111AE2-339 GEN
Solar/Wind Harmer
0.478
3429421JKCT 10G
Adder
4.362
3429241JKCT 3G
Adder
6.015
270520AE2-214 GEN
Solar/Wind Helper
3.432
270273AD2-016 GEN
Solar/Wind Helper
1.403
253372AE2-315 SEC3
50/50
2.873
253372AE2-315 SEC3
50/50
2.873
25322309TAIT W
50/50
0.722
963581AG1-207 GEN
50/50
13.076
25306009OHH W.
50/50
4.021
945631AF1-228 GEN
Solar/Wind Harmer
27.82
253406AD2-031_GEN
Solar/Wind Harmer
1.496
253433AC1-085 GEN1
Solar/Wind Harmer
6.101
253432AC1-085 GEN2
Solar/Wind Harmer
0.307
241972AD1-140 GEN
Solar/Wind Harmer
5.043
25196408WSDLE3
Adder
7.92
25196308WSDLE2
Adder
7.851
25196208WSDLE1
Adder
7.831
25196708WSDLE6
Adder
7.812
25196508WSDLE4
Adder
7.615
253338AC1-165 GEN
Solar/Wind Harmer
0.931
253343AC1-166 GEN
Solar/Wind Harmer
0.931
25196108MFTGT2
Adder
1.073
25196108MFTGT2
Adder
0.996
972163AH1-664 GEN
Solar/Wind Harmer
6.493
972165AH1-665 GEN
Solar/Wind Harmer
5.195
339216AC1-074 GEN
Solar/Wind Harmer
0.975
971029AG2-637 GEN
Solar/Wind Harmer
8.17
3429211JKCT 2G
Adder
5.937
270340AC2-060 GEN
Solar/Wind Harmer
1.532
270543AE2-219 C
Solar/Wind Harmer
4.923
270356AE2-297 GEN
Solar/Wind Harmer
2.157
247536S-71 GEN
Solar/Wind Harmer
1.8
241955AC1-078 GEN
Solar/Wind Helper
1.503
253370AE2-315 SEC1
50/50
3.038
253371AE2-315 SEC2
50/50
2.873
25322309TAIT W
50/50
0.713
25322209TAIT E
50/50
0.703
270518AE2-148 GEN
Solar/Wind Harmer
58.607
253303V4-073 C
Solar/Wind Harmer
0.166
253394AE2-221_GEN
Solar/Wind Harmer
6.166
960071AF2-298 GEN
Solar/Wind Harmer
1.993
253317AC1-085 GEN4
Solar/Wind Harmer
9.612
946181AF1-283 GEN
Solar/Wind Harmer
14.925
252524AE2-267 GEN
Solar/Wind Harmer
1.414
25196608WSDLE5
Adder
7.694
252519AF1-045_GEN
Solar/Wind Harmer
3.223
25194608D.CRK4
Adder
1.445
253325AC1-069 GEN
Solar/Wind Harmer
0.898
252507AC2-088 GEN
Solar/Wind Harmer
1.388
958171AF2-111 GEN
Solar/Wind Harmer
17.58
25196008MFTGT1
Adder
0.943
270367AC2-061_GEN
Solar/Wind Harmer
2.209
270186AC1-089 GEN
Solar/Wind Harmer
4.066
972167AH1-666 GEN
Solar/Wind Harmer
5.284
276820AF1-078_GEN
Solar/Wind Harmer
1.043
339243AC2-075 GEN1
Solar/Wind Harmer
0.264
3429391JKCT 9G
Adder
4.362
970093AG2-073 GEN
Solar/Wind Harmer
2.501
960801AF2-371 GEN
Solar/Wind Helper
0.815
964871AG1-351 GEN
Solar/Wind Helper
0.563
25326109MON D
50/50
2.066
253370AE2-315 SEC1
50/50
3.038
25322209TAIT E
50/50
14.5
25322209TAIT E
50/50
14.174
253349AC2-067 GEN
Solar/Wind Harmer
2.458
253400AC2-068 GEN
Solar/Wind Harmer
0.988
25183208HLCRTG
Solar/Wind Harmer
5.4
25194408D.CRK1
Adder
6.646
25194508D.CRK3
Adder
1.243
252509AD1-136 GEN
Solar/Wind Harmer
0.198
962581AG1-107 GEN
Solar/Wind Harmer
3.816
961491AF2-440 GEN
Solar/Wind Harmer
1.586
25326509SID D
Adder
0.988
253378AE2-206_GEN
Solar/Wind Harmer
2.347
253415AE1-040 GEN
Solar/Wind Harmer
0.707
24728805RICHG1
Adder
2.311
24728905RICHG2
Adder
2.311
972043AH1-570 GEN
Solar/Wind Harmer
1.421
972045AH1-571 GEN
Solar/Wind Harmer
1.137
971125AH1-004 GEN
Solar/Wind Harmer
2.175
970107AG2-081 GEN
Solar/Wind Harmer
1.631
942891AE2-308 GEN
Solar/Wind Harmer
4.949
970883AG2-550 GEN
Solar/Wind Harmer
4.923
970885AG2-551 GEN
Solar/Wind Harmer
1.145
270383AD1-128 GEN
Solar/Wind Harmer
2.85
946101AF1-275 GEN
Solar/Wind Helper
0.858
270054AF2-122 C O1
Solar/Wind Helper
0.912
LAGNLTFEXP_LAGN->PJM
CLTF
3.578
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.366
TVALTFEXP_TVA->PJM
CLTF
1.861
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.28
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.613
MECLTFEXP_MEC->PJM
CLTF
3.11
SIGELTFEXP_SIGE->PJM
CLTF
0.178
CPLELTFEXP_CPLE->PJM
CLTF
0.135
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.65
NYPJM->LTFIMP_NY
CLTF
0.884
LGEELTFEXP_LGEE->PJM
CLTF
2.926
WECLTFEXP_WEC->PJM
CLTF
0.634

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#16622_05ADKINS 345_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.59 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1366.44
MW Contribution:
4.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.056
253371AE2-315 SEC2
50/50
2.89
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.716
25326309TAIT D
50/50
1.638
253398AE2-221_GEN2
Solar/Wind Harmer
6.206
253316AC1-085 GEN3
Solar/Wind Harmer
9.676
946171AF1-282 GEN
Solar/Wind Harmer
11.557
252516AE2-318_GEN
Solar/Wind Harmer
8.919
25194608D.CRK4
Adder
1.455
252510AF1-249 C
Solar/Wind Harmer
0.367
253333AC1-068 GEN
Solar/Wind Harmer
0.904
25196808ZIMRHP
Adder
60.461
270222AC2-111 GEN
Solar/Wind Harmer
3.284
944031AF1-071 GEN
Solar/Wind Harmer
0.739
25196008MFTGT1
Adder
0.981
945681AF1-233 GEN
Solar/Wind Harmer
12.496
339221AD2-048_GEN
Solar/Wind Harmer
0.892
943111AE2-339 GEN
Solar/Wind Harmer
0.482
3429421JKCT 10G
Adder
4.399
3429241JKCT 3G
Adder
6.067
270520AE2-214 GEN
Solar/Wind Helper
3.371
270273AD2-016 GEN
Solar/Wind Helper
1.467
253372AE2-315 SEC3
50/50
2.89
253372AE2-315 SEC3
50/50
2.89
25322309TAIT W
50/50
0.727
963581AG1-207 GEN
50/50
13.151
25306009OHH W.
50/50
4.045
945631AF1-228 GEN
Solar/Wind Harmer
28.002
253406AD2-031_GEN
Solar/Wind Harmer
1.505
253433AC1-085 GEN1
Solar/Wind Harmer
6.141
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
241972AD1-140 GEN
Solar/Wind Harmer
5.035
25196408WSDLE3
Adder
7.976
25196308WSDLE2
Adder
7.907
25196208WSDLE1
Adder
7.887
25196708WSDLE6
Adder
7.867
25196508WSDLE4
Adder
7.669
253338AC1-165 GEN
Solar/Wind Harmer
0.937
253343AC1-166 GEN
Solar/Wind Harmer
0.937
25196108MFTGT2
Adder
1.081
25196108MFTGT2
Adder
1.004
972163AH1-664 GEN
Solar/Wind Harmer
6.543
972165AH1-665 GEN
Solar/Wind Harmer
5.235
339216AC1-074 GEN
Solar/Wind Harmer
0.983
971029AG2-637 GEN
Solar/Wind Harmer
8.241
3429211JKCT 2G
Adder
5.989
270340AC2-060 GEN
Solar/Wind Harmer
1.532
270543AE2-219 C
Solar/Wind Harmer
4.968
270356AE2-297 GEN
Solar/Wind Harmer
2.177
247536S-71 GEN
Solar/Wind Harmer
1.818
241955AC1-078 GEN
Solar/Wind Helper
1.675
253370AE2-315 SEC1
50/50
3.056
253371AE2-315 SEC2
50/50
2.89
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.708
270518AE2-148 GEN
Solar/Wind Harmer
58.989
253303V4-073 C
Solar/Wind Harmer
0.167
253394AE2-221_GEN
Solar/Wind Harmer
6.206
960071AF2-298 GEN
Solar/Wind Harmer
2.005
253317AC1-085 GEN4
Solar/Wind Harmer
9.676
946181AF1-283 GEN
Solar/Wind Harmer
15.024
252524AE2-267 GEN
Solar/Wind Harmer
1.424
25196608WSDLE5
Adder
7.748
252519AF1-045_GEN
Solar/Wind Harmer
3.246
25194608D.CRK4
Adder
1.455
253325AC1-069 GEN
Solar/Wind Harmer
0.904
252507AC2-088 GEN
Solar/Wind Harmer
1.398
958171AF2-111 GEN
Solar/Wind Harmer
17.712
25196008MFTGT1
Adder
0.95
270367AC2-061_GEN
Solar/Wind Harmer
2.222
270186AC1-089 GEN
Solar/Wind Harmer
4.092
972167AH1-666 GEN
Solar/Wind Harmer
5.325
276820AF1-078_GEN
Solar/Wind Harmer
1.05
339243AC2-075 GEN1
Solar/Wind Harmer
0.266
3429391JKCT 9G
Adder
4.399
970093AG2-073 GEN
Solar/Wind Harmer
2.524
960801AF2-371 GEN
Solar/Wind Helper
0.865
964871AG1-351 GEN
Solar/Wind Helper
0.597
25326109MON D
50/50
2.078
253370AE2-315 SEC1
50/50
3.056
25322209TAIT E
50/50
14.584
25322209TAIT E
50/50
14.257
253349AC2-067 GEN
Solar/Wind Harmer
2.473
253400AC2-068 GEN
Solar/Wind Harmer
0.994
25183208HLCRTG
Solar/Wind Harmer
5.438
25194408D.CRK1
Adder
6.694
25194508D.CRK3
Adder
1.251
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.839
961491AF2-440 GEN
Solar/Wind Harmer
1.595
25326509SID D
Adder
0.995
253378AE2-206_GEN
Solar/Wind Harmer
2.363
253415AE1-040 GEN
Solar/Wind Harmer
0.708
24728805RICHG1
Adder
2.33
24728905RICHG2
Adder
2.33
972043AH1-570 GEN
Solar/Wind Harmer
1.432
972045AH1-571 GEN
Solar/Wind Harmer
1.146
971125AH1-004 GEN
Solar/Wind Harmer
2.193
970107AG2-081 GEN
Solar/Wind Harmer
1.645
942891AE2-308 GEN
Solar/Wind Harmer
4.993
970883AG2-550 GEN
Solar/Wind Harmer
4.968
970885AG2-551 GEN
Solar/Wind Harmer
1.155
270383AD1-128 GEN
Solar/Wind Harmer
2.877
946101AF1-275 GEN
Solar/Wind Helper
0.843
270054AF2-122 C O1
Solar/Wind Helper
0.913
LAGNLTFEXP_LAGN->PJM
CLTF
3.639
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.437
TVALTFEXP_TVA->PJM
CLTF
1.892
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.734
MECLTFEXP_MEC->PJM
CLTF
3.163
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.159
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.082
NYPJM->LTFIMP_NY
CLTF
0.873
LGEELTFEXP_LGEE->PJM
CLTF
2.954
WECLTFEXP_WEC->PJM
CLTF
0.645

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#16620_05ADKINS 345_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16620_05ADKINS 345_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.56 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1366.12
MW Contribution:
4.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.056
253371AE2-315 SEC2
50/50
2.89
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.716
25326309TAIT D
50/50
1.638
253398AE2-221_GEN2
Solar/Wind Harmer
6.206
253316AC1-085 GEN3
Solar/Wind Harmer
9.676
946171AF1-282 GEN
Solar/Wind Harmer
11.557
252516AE2-318_GEN
Solar/Wind Harmer
8.919
25194608D.CRK4
Adder
1.455
252510AF1-249 C
Solar/Wind Harmer
0.367
253333AC1-068 GEN
Solar/Wind Harmer
0.904
25196808ZIMRHP
Adder
60.461
270222AC2-111 GEN
Solar/Wind Harmer
3.284
944031AF1-071 GEN
Solar/Wind Harmer
0.739
25196008MFTGT1
Adder
0.981
945681AF1-233 GEN
Solar/Wind Harmer
12.496
339221AD2-048_GEN
Solar/Wind Harmer
0.892
943111AE2-339 GEN
Solar/Wind Harmer
0.482
3429421JKCT 10G
Adder
4.399
3429241JKCT 3G
Adder
6.067
270520AE2-214 GEN
Solar/Wind Helper
3.371
270273AD2-016 GEN
Solar/Wind Helper
1.467
253372AE2-315 SEC3
50/50
2.89
253372AE2-315 SEC3
50/50
2.89
25322309TAIT W
50/50
0.727
963581AG1-207 GEN
50/50
13.151
25306009OHH W.
50/50
4.045
945631AF1-228 GEN
Solar/Wind Harmer
28.002
253406AD2-031_GEN
Solar/Wind Harmer
1.505
253433AC1-085 GEN1
Solar/Wind Harmer
6.141
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
241972AD1-140 GEN
Solar/Wind Harmer
5.035
25196408WSDLE3
Adder
7.976
25196308WSDLE2
Adder
7.907
25196208WSDLE1
Adder
7.887
25196708WSDLE6
Adder
7.867
25196508WSDLE4
Adder
7.669
253338AC1-165 GEN
Solar/Wind Harmer
0.937
253343AC1-166 GEN
Solar/Wind Harmer
0.937
25196108MFTGT2
Adder
1.081
25196108MFTGT2
Adder
1.004
972163AH1-664 GEN
Solar/Wind Harmer
6.543
972165AH1-665 GEN
Solar/Wind Harmer
5.235
339216AC1-074 GEN
Solar/Wind Harmer
0.983
971029AG2-637 GEN
Solar/Wind Harmer
8.241
3429211JKCT 2G
Adder
5.989
270340AC2-060 GEN
Solar/Wind Harmer
1.532
270543AE2-219 C
Solar/Wind Harmer
4.968
270356AE2-297 GEN
Solar/Wind Harmer
2.177
247536S-71 GEN
Solar/Wind Harmer
1.818
241955AC1-078 GEN
Solar/Wind Helper
1.675
253370AE2-315 SEC1
50/50
3.056
253371AE2-315 SEC2
50/50
2.89
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.708
270518AE2-148 GEN
Solar/Wind Harmer
58.989
253303V4-073 C
Solar/Wind Harmer
0.167
253394AE2-221_GEN
Solar/Wind Harmer
6.206
960071AF2-298 GEN
Solar/Wind Harmer
2.005
253317AC1-085 GEN4
Solar/Wind Harmer
9.676
946181AF1-283 GEN
Solar/Wind Harmer
15.024
252524AE2-267 GEN
Solar/Wind Harmer
1.424
25196608WSDLE5
Adder
7.748
252519AF1-045_GEN
Solar/Wind Harmer
3.246
25194608D.CRK4
Adder
1.455
253325AC1-069 GEN
Solar/Wind Harmer
0.904
252507AC2-088 GEN
Solar/Wind Harmer
1.398
958171AF2-111 GEN
Solar/Wind Harmer
17.712
25196008MFTGT1
Adder
0.95
270367AC2-061_GEN
Solar/Wind Harmer
2.222
270186AC1-089 GEN
Solar/Wind Harmer
4.092
972167AH1-666 GEN
Solar/Wind Harmer
5.325
276820AF1-078_GEN
Solar/Wind Harmer
1.05
339243AC2-075 GEN1
Solar/Wind Harmer
0.266
3429391JKCT 9G
Adder
4.399
970093AG2-073 GEN
Solar/Wind Harmer
2.524
960801AF2-371 GEN
Solar/Wind Helper
0.865
964871AG1-351 GEN
Solar/Wind Helper
0.597
25326109MON D
50/50
2.078
253370AE2-315 SEC1
50/50
3.056
25322209TAIT E
50/50
14.584
25322209TAIT E
50/50
14.257
253349AC2-067 GEN
Solar/Wind Harmer
2.473
253400AC2-068 GEN
Solar/Wind Harmer
0.994
25183208HLCRTG
Solar/Wind Harmer
5.438
25194408D.CRK1
Adder
6.694
25194508D.CRK3
Adder
1.251
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.839
961491AF2-440 GEN
Solar/Wind Harmer
1.595
25326509SID D
Adder
0.995
253378AE2-206_GEN
Solar/Wind Harmer
2.363
253415AE1-040 GEN
Solar/Wind Harmer
0.708
24728805RICHG1
Adder
2.33
24728905RICHG2
Adder
2.33
972043AH1-570 GEN
Solar/Wind Harmer
1.432
972045AH1-571 GEN
Solar/Wind Harmer
1.146
971125AH1-004 GEN
Solar/Wind Harmer
2.193
970107AG2-081 GEN
Solar/Wind Harmer
1.645
942891AE2-308 GEN
Solar/Wind Harmer
4.993
970883AG2-550 GEN
Solar/Wind Harmer
4.968
970885AG2-551 GEN
Solar/Wind Harmer
1.155
270383AD1-128 GEN
Solar/Wind Harmer
2.877
946101AF1-275 GEN
Solar/Wind Helper
0.843
270054AF2-122 C O1
Solar/Wind Helper
0.913
LAGNLTFEXP_LAGN->PJM
CLTF
3.639
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.437
TVALTFEXP_TVA->PJM
CLTF
1.892
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.734
MECLTFEXP_MEC->PJM
CLTF
3.163
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.159
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.082
NYPJM->LTFIMP_NY
CLTF
0.873
LGEELTFEXP_LGEE->PJM
CLTF
2.954
WECLTFEXP_WEC->PJM
CLTF
0.645

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#16621_05ADKINS 345_A1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.56 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1366.07
MW Contribution:
4.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.056
253371AE2-315 SEC2
50/50
2.89
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.716
25326309TAIT D
50/50
1.638
253398AE2-221_GEN2
Solar/Wind Harmer
6.206
253316AC1-085 GEN3
Solar/Wind Harmer
9.676
946171AF1-282 GEN
Solar/Wind Harmer
11.557
252516AE2-318_GEN
Solar/Wind Harmer
8.919
25194608D.CRK4
Adder
1.455
252510AF1-249 C
Solar/Wind Harmer
0.367
253333AC1-068 GEN
Solar/Wind Harmer
0.904
25196808ZIMRHP
Adder
60.461
270222AC2-111 GEN
Solar/Wind Harmer
3.284
944031AF1-071 GEN
Solar/Wind Harmer
0.739
25196008MFTGT1
Adder
0.981
945681AF1-233 GEN
Solar/Wind Harmer
12.496
339221AD2-048_GEN
Solar/Wind Harmer
0.892
943111AE2-339 GEN
Solar/Wind Harmer
0.482
3429421JKCT 10G
Adder
4.399
3429241JKCT 3G
Adder
6.067
270520AE2-214 GEN
Solar/Wind Helper
3.371
270273AD2-016 GEN
Solar/Wind Helper
1.467
253372AE2-315 SEC3
50/50
2.89
253372AE2-315 SEC3
50/50
2.89
25322309TAIT W
50/50
0.727
963581AG1-207 GEN
50/50
13.151
25306009OHH W.
50/50
4.045
945631AF1-228 GEN
Solar/Wind Harmer
28.002
253406AD2-031_GEN
Solar/Wind Harmer
1.505
253433AC1-085 GEN1
Solar/Wind Harmer
6.141
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
241972AD1-140 GEN
Solar/Wind Harmer
5.035
25196408WSDLE3
Adder
7.976
25196308WSDLE2
Adder
7.907
25196208WSDLE1
Adder
7.887
25196708WSDLE6
Adder
7.867
25196508WSDLE4
Adder
7.669
253338AC1-165 GEN
Solar/Wind Harmer
0.937
253343AC1-166 GEN
Solar/Wind Harmer
0.937
25196108MFTGT2
Adder
1.081
25196108MFTGT2
Adder
1.004
972163AH1-664 GEN
Solar/Wind Harmer
6.543
972165AH1-665 GEN
Solar/Wind Harmer
5.235
339216AC1-074 GEN
Solar/Wind Harmer
0.983
971029AG2-637 GEN
Solar/Wind Harmer
8.241
3429211JKCT 2G
Adder
5.989
270340AC2-060 GEN
Solar/Wind Harmer
1.532
270543AE2-219 C
Solar/Wind Harmer
4.968
270356AE2-297 GEN
Solar/Wind Harmer
2.177
247536S-71 GEN
Solar/Wind Harmer
1.818
241955AC1-078 GEN
Solar/Wind Helper
1.675
253370AE2-315 SEC1
50/50
3.056
253371AE2-315 SEC2
50/50
2.89
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.708
270518AE2-148 GEN
Solar/Wind Harmer
58.989
253303V4-073 C
Solar/Wind Harmer
0.167
253394AE2-221_GEN
Solar/Wind Harmer
6.206
960071AF2-298 GEN
Solar/Wind Harmer
2.005
253317AC1-085 GEN4
Solar/Wind Harmer
9.676
946181AF1-283 GEN
Solar/Wind Harmer
15.024
252524AE2-267 GEN
Solar/Wind Harmer
1.424
25196608WSDLE5
Adder
7.748
252519AF1-045_GEN
Solar/Wind Harmer
3.246
25194608D.CRK4
Adder
1.455
253325AC1-069 GEN
Solar/Wind Harmer
0.904
252507AC2-088 GEN
Solar/Wind Harmer
1.398
958171AF2-111 GEN
Solar/Wind Harmer
17.712
25196008MFTGT1
Adder
0.95
270367AC2-061_GEN
Solar/Wind Harmer
2.222
270186AC1-089 GEN
Solar/Wind Harmer
4.092
972167AH1-666 GEN
Solar/Wind Harmer
5.325
276820AF1-078_GEN
Solar/Wind Harmer
1.05
339243AC2-075 GEN1
Solar/Wind Harmer
0.266
3429391JKCT 9G
Adder
4.399
970093AG2-073 GEN
Solar/Wind Harmer
2.524
960801AF2-371 GEN
Solar/Wind Helper
0.865
964871AG1-351 GEN
Solar/Wind Helper
0.597
25326109MON D
50/50
2.078
253370AE2-315 SEC1
50/50
3.056
25322209TAIT E
50/50
14.584
25322209TAIT E
50/50
14.257
253349AC2-067 GEN
Solar/Wind Harmer
2.473
253400AC2-068 GEN
Solar/Wind Harmer
0.994
25183208HLCRTG
Solar/Wind Harmer
5.438
25194408D.CRK1
Adder
6.694
25194508D.CRK3
Adder
1.251
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.839
961491AF2-440 GEN
Solar/Wind Harmer
1.595
25326509SID D
Adder
0.995
253378AE2-206_GEN
Solar/Wind Harmer
2.363
253415AE1-040 GEN
Solar/Wind Harmer
0.708
24728805RICHG1
Adder
2.33
24728905RICHG2
Adder
2.33
972043AH1-570 GEN
Solar/Wind Harmer
1.432
972045AH1-571 GEN
Solar/Wind Harmer
1.146
971125AH1-004 GEN
Solar/Wind Harmer
2.193
970107AG2-081 GEN
Solar/Wind Harmer
1.645
942891AE2-308 GEN
Solar/Wind Harmer
4.993
970883AG2-550 GEN
Solar/Wind Harmer
4.968
970885AG2-551 GEN
Solar/Wind Harmer
1.155
270383AD1-128 GEN
Solar/Wind Harmer
2.877
946101AF1-275 GEN
Solar/Wind Helper
0.843
270054AF2-122 C O1
Solar/Wind Helper
0.913
LAGNLTFEXP_LAGN->PJM
CLTF
3.639
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.437
TVALTFEXP_TVA->PJM
CLTF
1.892
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.734
MECLTFEXP_MEC->PJM
CLTF
3.163
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.159
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.082
NYPJM->LTFIMP_NY
CLTF
0.873
LGEELTFEXP_LGEE->PJM
CLTF
2.954
WECLTFEXP_WEC->PJM
CLTF
0.645

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#2085_05BEATTY 345_304C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2085_05BEATTY 345_304C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.85 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1333.47
MW Contribution:
4.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.661
253372AE2-315 SEC3
50/50
2.661
25322309TAIT W
50/50
0.668
963581AG1-207 GEN
50/50
12.043
25306009OHH W.
50/50
3.721
945631AF1-228 GEN
Solar/Wind Harmer
25.969
253406AD2-031_GEN
Solar/Wind Harmer
1.399
253433AC1-085 GEN1
Solar/Wind Harmer
5.705
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
241972AD1-140 GEN
Solar/Wind Harmer
4.472
25196408WSDLE3
Adder
7.388
25196308WSDLE2
Adder
7.324
25196208WSDLE1
Adder
7.305
25196708WSDLE6
Adder
7.287
25196508WSDLE4
Adder
7.103
253338AC1-165 GEN
Solar/Wind Harmer
0.876
253343AC1-166 GEN
Solar/Wind Harmer
0.876
25196108MFTGT2
Adder
1.001
25196108MFTGT2
Adder
0.93
972163AH1-664 GEN
Solar/Wind Harmer
6.106
972165AH1-665 GEN
Solar/Wind Harmer
4.885
339216AC1-074 GEN
Solar/Wind Harmer
0.915
971029AG2-637 GEN
Solar/Wind Harmer
7.52
270340AC2-060 GEN
Solar/Wind Harmer
1.487
3429211JKCT 2G
Adder
5.575
270543AE2-219 C
Solar/Wind Harmer
4.522
270356AE2-297 GEN
Solar/Wind Harmer
1.992
241955AC1-078 GEN
Solar/Wind Helper
2.057
253370AE2-315 SEC1
50/50
2.813
253371AE2-315 SEC2
50/50
2.661
25322209TAIT E
50/50
0.658
25322309TAIT W
50/50
0.659
25326309TAIT D
50/50
1.505
253398AE2-221_GEN2
Solar/Wind Harmer
5.753
253316AC1-085 GEN3
Solar/Wind Harmer
8.989
946171AF1-282 GEN
Solar/Wind Harmer
10.737
252516AE2-318_GEN
Solar/Wind Harmer
8.28
25194608D.CRK4
Adder
1.348
252510AF1-249 C
Solar/Wind Harmer
0.34
253333AC1-068 GEN
Solar/Wind Harmer
0.844
25196808ZIMRHP
Adder
56.185
270222AC2-111 GEN
Solar/Wind Harmer
3.02
944031AF1-071 GEN
Solar/Wind Harmer
0.68
25196008MFTGT1
Adder
0.908
945681AF1-233 GEN
Solar/Wind Harmer
11.661
339221AD2-048_GEN
Solar/Wind Harmer
0.83
943111AE2-339 GEN
Solar/Wind Harmer
0.449
3429421JKCT 10G
Adder
4.096
3429241JKCT 3G
Adder
5.648
270520AE2-214 GEN
Solar/Wind Helper
4.231
270273AD2-016 GEN
Solar/Wind Helper
1.308
253370AE2-315 SEC1
50/50
2.813
253371AE2-315 SEC2
50/50
2.661
25322209TAIT E
50/50
0.65
25322309TAIT W
50/50
0.659
270518AE2-148 GEN
Solar/Wind Harmer
54.681
253303V4-073 C
Solar/Wind Harmer
0.153
253394AE2-221_GEN
Solar/Wind Harmer
5.753
960071AF2-298 GEN
Solar/Wind Harmer
1.841
253317AC1-085 GEN4
Solar/Wind Harmer
8.989
946181AF1-283 GEN
Solar/Wind Harmer
13.958
252524AE2-267 GEN
Solar/Wind Harmer
1.319
25196608WSDLE5
Adder
7.177
252519AF1-045_GEN
Solar/Wind Harmer
3.014
25194608D.CRK4
Adder
1.348
253325AC1-069 GEN
Solar/Wind Harmer
0.844
252507AC2-088 GEN
Solar/Wind Harmer
1.301
958171AF2-111 GEN
Solar/Wind Harmer
16.521
270367AC2-061_GEN
Solar/Wind Harmer
2.077
25196008MFTGT1
Adder
0.88
270186AC1-089 GEN
Solar/Wind Harmer
3.826
972167AH1-666 GEN
Solar/Wind Harmer
4.969
276820AF1-078_GEN
Solar/Wind Harmer
0.929
339243AC2-075 GEN1
Solar/Wind Harmer
0.248
3429391JKCT 9G
Adder
4.096
970093AG2-073 GEN
Solar/Wind Harmer
2.348
960801AF2-371 GEN
Solar/Wind Helper
0.884
964871AG1-351 GEN
Solar/Wind Helper
0.61
25326109MON D
50/50
1.906
253370AE2-315 SEC1
50/50
2.813
25322209TAIT E
50/50
13.402
25322209TAIT E
50/50
13.101
253349AC2-067 GEN
Solar/Wind Harmer
2.272
253400AC2-068 GEN
Solar/Wind Harmer
0.914
25183208HLCRTG
Solar/Wind Harmer
5.057
25194408D.CRK1
Adder
6.202
25194508D.CRK3
Adder
1.16
252509AD1-136 GEN
Solar/Wind Harmer
0.186
962581AG1-107 GEN
Solar/Wind Harmer
3.579
961491AF2-440 GEN
Solar/Wind Harmer
1.488
25326509SID D
Adder
0.892
253415AE1-040 GEN
Solar/Wind Harmer
0.677
253378AE2-206_GEN
Solar/Wind Harmer
2.092
24728805RICHG1
Adder
2.138
24728905RICHG2
Adder
2.138
972043AH1-570 GEN
Solar/Wind Harmer
1.334
972045AH1-571 GEN
Solar/Wind Harmer
1.067
971125AH1-004 GEN
Solar/Wind Harmer
2.041
970107AG2-081 GEN
Solar/Wind Harmer
1.531
942891AE2-308 GEN
Solar/Wind Harmer
4.647
970883AG2-550 GEN
Solar/Wind Harmer
4.522
970885AG2-551 GEN
Solar/Wind Harmer
1.052
946101AF1-275 GEN
Solar/Wind Helper
1.058
270054AF2-122 C O1
Solar/Wind Helper
0.772
LAGNLTFEXP_LAGN->PJM
CLTF
3.327
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.36
TVALTFEXP_TVA->PJM
CLTF
1.741
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.066
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.052
MECLTFEXP_MEC->PJM
CLTF
2.814
SIGELTFEXP_SIGE->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.158
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.411
NYPJM->LTFIMP_NY
CLTF
0.808
LGEELTFEXP_LGEE->PJM
CLTF
2.734
WECLTFEXP_WEC->PJM
CLTF
0.564

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.82 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2406.35
MW Contribution:
4.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.317
960861AF2-377 GEN
50/50
2.406
970521AG2-332 GEN
50/50
10.906
24639705ELKHART HY
50/50
0.151
270143AC1-141 CT2_
50/50
2.029
965421AG1-410 GEN
Solar/Wind Harmer
81.797
965011AG1-365 GEN
Solar/Wind Harmer
13.822
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.876
958861AF2-177 GEN
Solar/Wind Harmer
2.694
945111AF1-176 GEN
Solar/Wind Harmer
10.683
957891AF2-083 GEN
Solar/Wind Harmer
9.802
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3
970373AG2-245 GEN
Solar/Wind Harmer
11.243
274751CRETE EC ;1U
Adder
6.312
274754CRETE EC ;4U
Adder
6.312
274723RIVER EC ;12
Adder
13.681
274812UNIV PK N;8U
Adder
3.792
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.365
274774LINCOLN ;5U
Adder
6.365
274802UNIV PARK;5U
Adder
4.369
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.75
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.662
274674JOLIET 9 ;6U
Adder
11.348
274732ELWOOD EC;7P
Adder
12.11
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.364
270594AE1-207 GEN
Solar/Wind Harmer
5.699
270032AE2-172
Solar/Wind Harmer
3.392
270005AE1-210 C O1
Solar/Wind Harmer
1.101
274745AC1-111 GEN9
Adder
4.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.82
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.788
274682WAUKEGAN ;7U
Adder
12.933
274828WAUKEGAN ;BP
Adder
7.939
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.731
939401AE1-172 GEN
Solar/Wind Harmer
3.718
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.578
971997AH1-543 GEN
Solar/Wind Harmer
2.59
957471AF2-041 GEN
Solar/Wind Harmer
14.651
959081AF2-199 GEN
Solar/Wind Harmer
4.884
971067AG2-660 GEN
Solar/Wind Harmer
1.628
274822ROCKFORD ;11
Adder
13.696
276903AD2-071 C
Solar/Wind Harmer
5.426
970819AG2-516 GEN
Solar/Wind Harmer
5.809
970569AG2-363 GEN
Solar/Wind Harmer
14.512
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.381
274766LEE CO EC;7U
Adder
6.306
276708O09 GEN2
Solar/Wind Harmer
0.167
276646AC1-214 GEN2
Solar/Wind Harmer
0.185
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.519
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.287
963741AG1-226 GEN
Solar/Wind Harmer
10.473
276621W2-048 GEN
Solar/Wind Harmer
0.213
965911AG1-460 GEN
Solar/Wind Harmer
0.82
24728605AND G2
Adder
2.099
970773AG2-487 GEN
Solar/Wind Harmer
0.63
246936BC-WTG1
Solar/Wind Helper
10.897
270317AD1-130_GEN
Solar/Wind Helper
4.143
270485AE1-090_GEN
Solar/Wind Helper
0.326
270391AF1-285 GEN3
Solar/Wind Helper
0.593
270578AF1-285 GEN2
Solar/Wind Helper
0.593
270286AF1-227 GEN2
Solar/Wind Helper
0.694
960841AF2-375 GEN
Solar/Wind Helper
1.179
24727205RPMNG3
50/50
3.298
24729505KEY G4
50/50
6.847
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.792
959331AF2-224 GEN
Solar/Wind Harmer
9.676
963791AG1-232 GEN
Solar/Wind Harmer
12.035
970031AG2-029 GEN
Solar/Wind Harmer
4.587
965041AG1-368 GEN
Solar/Wind Harmer
8.443
270071AF1-092 GEN
Solar/Wind Harmer
14.566
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.602
971771AH1-392 GEN
Solar/Wind Harmer
5.907
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.922
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.13
274775LINCOLN ;6U
Adder
6.365
274776LINCOLN ;7U
Adder
6.365
274777LINCOLN ;8U
Adder
6.365
972037AH1-567 GEN1
Adder
0.137
274827FISK ;RP
Adder
5.808
274800UNIV PARK;3U
Adder
4.357
274801UNIV PARK;4U
Adder
4.357
960591AF2-350 GEN
Solar/Wind Harmer
5.207
972228AH1-698 GEN2
Adder
2.756
972227AH1-698 GEN1
Adder
1.941
274687WILL CNTY;4U
Adder
20.685
274687WILL CNTY;4U
Adder
20.685
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.662
274675JOLIET 29;7U
Adder
21.853
274728ELWOOD EC;5P
Adder
12.11
274731ELWOOD EC;2P
Adder
12.11
274733ELWOOD EC;3P
Adder
12.11
274735ELWOOD EC;4P
Adder
12.11
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.974
970833AG2-524 GEN
Solar/Wind Harmer
5.628
970833AG2-524 GEN
Solar/Wind Harmer
3.752
971611AH1-305 GEN
Solar/Wind Harmer
3.031
274744AC1-111 GEN8
Adder
4.068
274746AC1-111 G10
Adder
4.068
970073AG2-061 GEN
Solar/Wind Harmer
1.661
247536S-71 GEN
Solar/Wind Harmer
0.199
971411AH1-196 GEN
Solar/Wind Harmer
7.376
971675AH1-338 GEN
Solar/Wind Harmer
1.916
276861AD2-134 GEN
Solar/Wind Harmer
0.088
276863AD2-134 GEN
Solar/Wind Harmer
0.088
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.768
274823ROCKFORD ;21
Adder
13.596
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
926823AC1-168 GEN
Solar/Wind Harmer
0.821
970169AG2-114 GEN
Solar/Wind Harmer
4.823
971681AH1-341 GEN
Solar/Wind Harmer
7.736
971549AH1-272 GEN
Solar/Wind Harmer
9.898
972267AH1-718 GEN
Adder
2.828
276741O09 GEN1
Solar/Wind Harmer
0.167
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.157
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.889
946321AF1-296 GEN
Solar/Wind Harmer
2.577
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.976
270543AE2-219 C
Solar/Wind Harmer
3.137
276668AB2-070 GEN1
Solar/Wind Harmer
0.17
276848AB2-070 GEN3
Solar/Wind Harmer
0.169
276849AB2-070 GEN2
Solar/Wind Harmer
0.17
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.928
944221AF1-090 GEN
Solar/Wind Harmer
2.312
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.609
270223U2-072_GEN1
Solar/Wind Helper
0.876
270224U2-072_GEN2
Solar/Wind Helper
0.876
270227U2-072_GEN3
Solar/Wind Helper
0.876
270228U2-072_GEN4
Solar/Wind Helper
0.876
270231U2-072_GEN5
Solar/Wind Helper
0.876
965431AG1-411 GEN
50/50
45.443
24727105RPMNG2
50/50
3.318
970583AG2-370 GEN
50/50
2.814
270142AC1-141 CT1_
50/50
2.029
24642205MAYFLWER
50/50
0.031
965021AG1-366 GEN
Solar/Wind Harmer
4.607
270043AE2-236 GEN
Solar/Wind Harmer
5.241
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.981
24695305TIMB G C
Solar/Wind Harmer
0.532
945111AF1-176 GEN
Solar/Wind Harmer
4.853
971347AH1-153 GEN
Solar/Wind Harmer
2.927
270505AE1-170 C O1
Solar/Wind Harmer
6.132
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.345
274752CRETE EC ;2U
Adder
6.312
274753CRETE EC ;3U
Adder
6.312
274724RIVER EC ;11
Adder
13.515
274814UNIV PK N;0U
Adder
3.826
274807UNIV PK N;3U
Adder
3.817
274811UNIV PK N;7U
Adder
3.792
274772LINCOLN ;3U
Adder
6.365
274803UNIV PARK;6U
Adder
4.369
274826FISK ;BP
Adder
8.195
972038AH1-567 GEN2
Adder
0.273
274887GEN-1.85
Solar/Wind Harmer
0.135
276843GEN-1.7
Solar/Wind Harmer
0.168
276806AD2-047 C O1
Solar/Wind Harmer
2.951
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.153
970707AG2-453 GEN
Solar/Wind Harmer
16.903
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.852
274729ELWOOD EC;1P
Adder
12.11
274730ELWOOD EC;6P
Adder
12.11
274734ELWOOD EC;8P
Adder
12.11
274736ELWOOD EC;9P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.564
946031AF1-268 GEN
Solar/Wind Harmer
4.838
943121AE2-341 GEN
Solar/Wind Harmer
8.518
943591AF1-030 GEN
Solar/Wind Harmer
5.665
270004AE1-209 GEN
Solar/Wind Harmer
1.101
274862TOP CROP ;2U
Solar/Wind Harmer
0.681
970825AG2-519 GEN
Solar/Wind Harmer
3.795
274682WAUKEGAN ;7U
Adder
12.933
276868AE1-113 GEN
Solar/Wind Harmer
0.991
274879MINONK ;1U
Solar/Wind Harmer
0.207
946671AF1-331 GEN
Solar/Wind Harmer
0.524
274855GSG-6 ;RU
Solar/Wind Harmer
0.179
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.895
959091AF2-200 GEN
Solar/Wind Harmer
9.768
970571AG2-364 GEN
Solar/Wind Harmer
9.675
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.381
274767LEE CO EC;8U
Adder
6.306
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.157
965091AG1-374 GEN
Solar/Wind Harmer
13.726
965931AG1-462 GEN
Solar/Wind Harmer
11.666
971087AG2-675 GEN
Solar/Wind Harmer
2.44
959611AF2-252 GEN
Solar/Wind Harmer
1.525
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.998
957381AF2-032 GEN
Solar/Wind Harmer
0.932
942481AE2-261 GEN
Solar/Wind Harmer
12.255
970193AG2-126 GEN
Solar/Wind Harmer
5.956
24728705AND G3
Adder
4.39
24728505AND G1
Adder
2.099
246938BC-WTG3
Solar/Wind Helper
11.083
942871AE2-306 GEN
Solar/Wind Helper
0.445
270284AF1-227 GEN1
Solar/Wind Helper
1.893
270287AF1-227 GEN3
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.334
270541AE2-072 C
Solar/Wind Helper
0.943
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
1.968
945641AF1-229 GEN
Solar/Wind Helper
0.94
24729405KEY G3
50/50
0.374
24729305KEY G2
50/50
0.367
24729205KEY G1
50/50
0.366
247620Y3-023
50/50
0.467
960851AF2-376 GEN
50/50
2.095
24643105BUCHANAN
50/50
0.01
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.855
944231AF1-091 GEN
Solar/Wind Harmer
16.139
944541AF1-119 GEN
Solar/Wind Harmer
0.427
960971AF2-388 GEN
Solar/Wind Harmer
3.752
970349AG2-230 GEN
Solar/Wind Harmer
8.78
961051AF2-396 GEN
Solar/Wind Harmer
11.674
961051AF2-396 GEN
Solar/Wind Harmer
7.782
270031AE2-169
Solar/Wind Harmer
3.104
270599AE1-208 GEN
Solar/Wind Harmer
5.173
965681AG1-436 GEN
Solar/Wind Harmer
6.963
965791AG1-447 GEN
Solar/Wind Harmer
5.106
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.41
247621Y3-024
Adder
0.183
274805UNIV PK N;1U
Adder
3.801
274808UNIV PK N;4U
Adder
3.776
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.365
274771LINCOLN ;2U
Adder
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
0.304
276776AD2-060 GEN
Solar/Wind Harmer
0.555
958011AF2-095 GEN
Solar/Wind Harmer
7.498
970941AG2-585 GEN
Solar/Wind Harmer
2.864
276897AD1-100 C
Solar/Wind Harmer
12.887
274674JOLIET 9 ;6U
Adder
11.348
276893AG1-478 C
Solar/Wind Harmer
0.343
970291AG2-192 GEN
Solar/Wind Harmer
0.666
970291AG2-192 GEN
Solar/Wind Harmer
0.308
971613AH1-306 GEN
Solar/Wind Harmer
2.442
958481AF2-142 GEN
Solar/Wind Harmer
7.57
274695ROCKY RD ;2P
Adder
8.016
274693ROCKY RD ;1P
Adder
7.937
274697ROCKY RD ;3P
Adder
2.178
274696ROCKY RD ;4P
Adder
8.205
274683WAUKEGAN ;8U
Adder
15.145
274683WAUKEGAN ;8U
Adder
12.766
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
14.951
958491AF2-143 GEN
Solar/Wind Harmer
7.476
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.768
971343AH1-151 GEN
Solar/Wind Harmer
9.768
972235AH1-702 GEN1
Adder
1.755
972236AH1-702 GEN2
Adder
1.526
938861AE1-114 GEN
Solar/Wind Harmer
2.722
274764LEE CO EC;5U
Adder
6.396
274765LEE CO EC;6U
Adder
6.396
274762LEE CO EC;3U
Adder
6.381
274763LEE CO EC;4U
Adder
6.321
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.763
276645AC1-214 GEN1
Solar/Wind Harmer
0.185
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.533
942111AE2-223 GEN
Solar/Wind Harmer
1.513
960611AF2-352 GEN
Solar/Wind Harmer
1.525
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.481
970885AG2-551 GEN
Solar/Wind Harmer
1.494
970241AG2-163 GEN
Solar/Wind Harmer
2.581
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.044
276838X2-022 GEN2
Solar/Wind Harmer
0.239
276916AD2-100_GEN
Solar/Wind Harmer
8.532
276911AD2-131_GEN
Solar/Wind Harmer
0.562
945391AF1-204 GEN
Solar/Wind Harmer
4.219
970623AG2-406 GEN
Solar/Wind Harmer
0.656
971587AH1-292 GEN
Solar/Wind Harmer
2.468
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.897
270462AD2-086
Solar/Wind Helper
3.747
247522W1-056 GEN
Solar/Wind Helper
1.177
253378AE2-206_GEN
Solar/Wind Helper
0.715
270349AD2-093_GEN
Solar/Wind Helper
0.857
270471AD2-092_GEN
Solar/Wind Helper
0.857
241960AC2-195 GEN
Solar/Wind Helper
0.697
990497J1323
External Queue
1.5952997207641602
990792J1392
External Queue
5.487830638885498
LAGNLTFEXP_LAGN->PJM
CLTF
5.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.51
TVALTFEXP_TVA->PJM
CLTF
2.319
CBM West 1LTFEXP_CBM-W1->PJM
CBM
70.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.933
MECLTFEXP_MEC->PJM
CLTF
9.784
SIGELTFEXP_SIGE->PJM
CLTF
0.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.835
NYPJM->LTFIMP_NY
CLTF
1.264
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
AG2-052LTFEXP_AG2-052->PJM
LTF
0.172
AH1-155LTFEXP_AH1-155->PJM
LTF
0.258

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P7-1_#11067___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11067___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.3 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1929.56
MW Contribution:
5.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.185
960861AF2-377 GEN
50/50
3.578
965421AG1-410 GEN
Solar/Wind Harmer
113.181
965011AG1-365 GEN
Solar/Wind Harmer
18.262
270024AE2-089 GEN
Solar/Wind Harmer
4.053
965651AG1-433 GEN
Solar/Wind Harmer
3.873
958861AF2-177 GEN
Solar/Wind Harmer
7.52
24639705ELKHART HY
Adder
0.105
945371AF1-202 GEN
Solar/Wind Harmer
4.526
270216AD2-079_GEN
Solar/Wind Harmer
0.388
945111AF1-176 GEN
Solar/Wind Harmer
10.859
957891AF2-083 GEN
Solar/Wind Harmer
8.864
270449AD2-020 GEN
Solar/Wind Harmer
1.606
943021AE2-325 GEN
Solar/Wind Harmer
2.088
965431AG1-411 GEN
50/50
43.869
24727105RPMNG2
50/50
3.185
970583AG2-370 GEN
50/50
3.578
965021AG1-366 GEN
Solar/Wind Harmer
4.247
24695305TIMB G C
Solar/Wind Harmer
5.136
270043AE2-236 GEN
Solar/Wind Harmer
5.189
270063AE2-323 C
Solar/Wind Harmer
1.883
944531AF1-118 GEN
Solar/Wind Harmer
27.792
962031AG1-047 GEN
Solar/Wind Harmer
1.999
957741AF2-068 GEN
Solar/Wind Harmer
9.918
247643Z2-116 C
Solar/Wind Harmer
0.044
945111AF1-176 GEN
Solar/Wind Harmer
3.441
270505AE1-170 C O1
Solar/Wind Harmer
8.758
946031AF1-268 GEN
Solar/Wind Harmer
4.749
971347AH1-153 GEN
Solar/Wind Harmer
2.802
24441505OLIV SLR
Solar/Wind Harmer
0.075
970825AG2-519 GEN
Solar/Wind Harmer
3.152
270004AE1-209 GEN
Solar/Wind Harmer
3.044
247642Z2-115 C
Solar/Wind Harmer
0.035
965461AG1-414 GEN
Solar/Wind Harmer
1.253
970289AG2-191 GEN
Solar/Wind Harmer
0.424
972231SS25-0005
Solar/Wind Harmer
4.922
972181SS23-001
Solar/Wind Harmer
3.076
274752CRETE EC ;2U
Adder
2.535
274753CRETE EC ;3U
Adder
2.535
274724RIVER EC ;11
Adder
9.117
964401AG1-302 GEN
Solar/Wind Harmer
4.654
274814UNIV PK N;0U
Adder
2.581
274807UNIV PK N;3U
Adder
2.575
274811UNIV PK N;7U
Adder
2.559
276164X3-005 C
Solar/Wind Harmer
0.358
274803UNIV PARK;6U
Adder
2.938
274826FISK ;BP
Adder
5.508
972038AH1-567 GEN2
Adder
0.183
274887GEN-1.85
Solar/Wind Harmer
2.669
276772AC2-154 GEN
Solar/Wind Harmer
1.398
276843GEN-1.7
Solar/Wind Harmer
0.287
276806AD2-047 C O1
Solar/Wind Harmer
5.359
274772LINCOLN ;3U
Adder
3.105
972259AH1-714 GEN
Adder
9.459
274676JOLIET 29;8U
Adder
14.653
939351AE1-166 GEN
Solar/Wind Harmer
2.933
970707AG2-453 GEN
Solar/Wind Harmer
13.835
274730ELWOOD EC;6P
Adder
8.121
274734ELWOOD EC;8P
Adder
8.121
274736ELWOOD EC;9P
Adder
8.121
274729ELWOOD EC;1P
Adder
8.121
24690905MDL-1G C
Solar/Wind Harmer
3.92
970781AG2-491 GEN
Solar/Wind Harmer
4.882
24379505HDWTR1G C
Solar/Wind Harmer
3.852
270240V3-007_GEN2
Solar/Wind Harmer
3.014
943121AE2-341 GEN
Solar/Wind Harmer
7.298
943591AF1-030 GEN
Solar/Wind Harmer
4.865
274862TOP CROP ;2U
Solar/Wind Harmer
2.458
274682WAUKEGAN ;7U
Adder
8.668
970825AG2-519 GEN
Solar/Wind Harmer
1.174
270005AE1-210 C O1
Solar/Wind Harmer
3.044
270594AE1-207 GEN
Solar/Wind Harmer
7.495
270032AE2-172
Solar/Wind Harmer
2.567
24441205WTRV SLR C
Solar/Wind Harmer
0.072
970373AG2-245 GEN
Solar/Wind Harmer
11.017
24727205RPMNG3
50/50
3.166
959331AF2-224 GEN
Solar/Wind Harmer
18.262
965041AG1-368 GEN
Solar/Wind Harmer
15.386
247521TR3_G114
Solar/Wind Harmer
5.167
270191TR4_S_V150
Solar/Wind Harmer
4.611
965051AG1-369 GEN
Solar/Wind Harmer
7.677
963791AG1-232 GEN
Solar/Wind Harmer
16.236
970031AG2-029 GEN
Solar/Wind Harmer
24.959
270071AF1-092 GEN
Solar/Wind Harmer
12.96
24729505KEY G4
Adder
5.004
958711AF2-162 GEN
Solar/Wind Harmer
0.717
961761AG1-017 GEN
Solar/Wind Harmer
0.283
945581AF1-223 GEN
Solar/Wind Harmer
2.942
964611AG1-324 GEN
Solar/Wind Harmer
2.505
971771AH1-392 GEN
Solar/Wind Harmer
5.322
247536S-71 GEN
Solar/Wind Harmer
2.362
270526AF1-158 GEN
Solar/Wind Harmer
2.566
944161AF1-084 GEN
Solar/Wind Harmer
1.241
970289AG2-191 GEN
Solar/Wind Harmer
1.05
960681AF2-359 GEN
Solar/Wind Harmer
2.043
270543AE2-219 C
Solar/Wind Harmer
5.183
958391AF2-133 GEN
Solar/Wind Harmer
4.626
959141AF2-205 GEN
Solar/Wind Harmer
3.07
972037AH1-567 GEN1
Adder
0.092
274827FISK ;RP
Adder
3.903
274800UNIV PARK;3U
Adder
2.927
274801UNIV PARK;4U
Adder
2.927
960591AF2-350 GEN
Solar/Wind Harmer
5.009
274775LINCOLN ;6U
Adder
3.105
274776LINCOLN ;7U
Adder
3.105
274777LINCOLN ;8U
Adder
3.105
972228AH1-698 GEN2
Adder
1.847
972227AH1-698 GEN1
Adder
1.301
274687WILL CNTY;4U
Adder
13.878
274687WILL CNTY;4U
Adder
13.878
274675JOLIET 29;7U
Adder
15.196
274675JOLIET 29;7U
Adder
14.653
276893AG1-478 C
Solar/Wind Harmer
0.272
274728ELWOOD EC;5P
Adder
8.121
274731ELWOOD EC;2P
Adder
8.121
274733ELWOOD EC;3P
Adder
8.121
274735ELWOOD EC;4P
Adder
8.121
970833AG2-524 GEN
Solar/Wind Harmer
4.285
970833AG2-524 GEN
Solar/Wind Harmer
1.993
946581AF1-322 GEN
Solar/Wind Harmer
4.996
24691005MDL-2G C
Solar/Wind Harmer
1.805
274744AC1-111 GEN8
Adder
2.721
274746AC1-111 G10
Adder
2.721
970073AG2-061 GEN
Solar/Wind Harmer
1.117
274823ROCKFORD ;21
Adder
9.124
972267AH1-718 GEN
Adder
1.901
957201AF2-014 GEN
Solar/Wind Helper
8.864
270223U2-072_GEN1
Solar/Wind Helper
0.868
270224U2-072_GEN2
Solar/Wind Helper
0.868
270227U2-072_GEN3
Solar/Wind Helper
0.868
270228U2-072_GEN4
Solar/Wind Helper
0.868
270231U2-072_GEN5
Solar/Wind Helper
0.868
966831AG1-554 GEN
Solar/Wind Helper
0.996
270007AE1-245 C
Solar/Wind Helper
2.031
270499AE1-146 GEN
Solar/Wind Helper
2.272
945641AF1-229 GEN
Solar/Wind Helper
1.011
276903AD2-071 C
Solar/Wind Harmer
5.245
270055AF2-134 C O1
Solar/Wind Harmer
1.569
274751CRETE EC ;1U
Adder
2.535
274754CRETE EC ;4U
Adder
2.535
274723RIVER EC ;12
Adder
9.232
958381AF2-132 GEN
Solar/Wind Harmer
4.654
964861AG1-349 GEN
Solar/Wind Harmer
4.028
971917AH1-482 GEN
Solar/Wind Harmer
4.648
274812UNIV PK N;8U
Adder
2.559
940581AE2-045 GEN
Solar/Wind Harmer
5.149
971605AH1-302 GEN
Solar/Wind Harmer
4.403
274802UNIV PARK;5U
Adder
2.938
972207SS24-0001
Solar/Wind Harmer
11.039
274773LINCOLN ;4U
Adder
3.105
274774LINCOLN ;5U
Adder
3.105
274676JOLIET 29;8U
Adder
15.195
941551AE2-152 GEN
Solar/Wind Harmer
2.243
274732ELWOOD EC;7P
Adder
8.121
274674JOLIET 9 ;6U
Adder
7.608
274871GR RIDGE ;2U
Solar/Wind Harmer
3.771
274847GR RIDGE ;BU
Solar/Wind Harmer
2.479
24791305MDL-5G
Solar/Wind Harmer
1.177
942081AE2-220 GEN
Solar/Wind Harmer
3.115
270209AC1-174_GEN
Solar/Wind Harmer
1.982
270437AC2-090 C
Solar/Wind Harmer
2.719
270239V3-007_GEN1
Solar/Wind Harmer
0.838
274745AC1-111 GEN9
Adder
2.721
276694AA1-018 GEN2
Solar/Wind Harmer
3.068
276691AA1-018 GEN1
Solar/Wind Harmer
0.367
274861TOP CROP ;1U
Solar/Wind Harmer
2.944
274682WAUKEGAN ;7U
Adder
8.668
274828WAUKEGAN ;BP
Adder
5.321
276805AD2-038 GEN
Solar/Wind Harmer
2.463
274822ROCKFORD ;11
Adder
9.191
274761LEE CO EC;2U
Adder
4.287
274766LEE CO EC;7U
Adder
4.237
246936BC-WTG1
Solar/Wind Helper
11.22
270317AD1-130_GEN
Solar/Wind Helper
4.192
270485AE1-090_GEN
Solar/Wind Helper
0.33
270391AF1-285 GEN3
Solar/Wind Helper
0.588
270578AF1-285 GEN2
Solar/Wind Helper
0.588
960841AF2-375 GEN
Solar/Wind Helper
1.352
270286AF1-227 GEN2
Solar/Wind Helper
0.616
270297AD1-101 GEN
Solar/Wind Helper
0.284
241840AF1-064_GEN
Solar/Wind Helper
0.504
939401AE1-172 GEN
Solar/Wind Harmer
3.286
274760LEE CO EC;1U
Adder
4.287
274767LEE CO EC;8U
Adder
4.237
246938BC-WTG3
Solar/Wind Helper
11.413
942871AE2-306 GEN
Solar/Wind Helper
0.441
270284AF1-227 GEN1
Solar/Wind Helper
1.68
270287AF1-227 GEN3
Solar/Wind Helper
0.616
270541AE2-072 C
Solar/Wind Helper
1.274
276820AF1-078_GEN
Solar/Wind Helper
0.369
960851AF2-376 GEN
50/50
3.578
270246TR4_N_V150
Solar/Wind Harmer
1.307
270247TR4_N_V136
Solar/Wind Harmer
1.307
942221AE2-234 GEN
Solar/Wind Harmer
3.036
944231AF1-091 GEN
Solar/Wind Harmer
14.301
247620Y3-023
Adder
0.331
944541AF1-119 GEN
Solar/Wind Harmer
2.967
960971AF2-388 GEN
Solar/Wind Harmer
7.745
270201AC2-176 GEN
Solar/Wind Harmer
3.398
964611AG1-324 GEN
Solar/Wind Harmer
0.336
270031AE2-169
Solar/Wind Harmer
5.184
270599AE1-208 GEN
Solar/Wind Harmer
5.184
247621Y3-024
Adder
0.152
961051AF2-396 GEN
Solar/Wind Harmer
9.307
961051AF2-396 GEN
Solar/Wind Harmer
4.329
970349AG2-230 GEN
Solar/Wind Harmer
8.406
970291AG2-192 GEN
Solar/Wind Harmer
0.718
970291AG2-192 GEN
Solar/Wind Harmer
0.231
965681AG1-436 GEN
Solar/Wind Harmer
6.759
965791AG1-447 GEN
Solar/Wind Harmer
3.458
270535AF1-215 GEN1
Solar/Wind Harmer
2.354
270536AF1-215 GEN2
Solar/Wind Harmer
2.354
970883AG2-550 GEN
Solar/Wind Harmer
5.183
970885AG2-551 GEN
Solar/Wind Harmer
1.205
24725505WLD G2 C
Solar/Wind Harmer
2.053
24699105WLD G1 C
Solar/Wind Harmer
2.029
274805UNIV PK N;1U
Adder
2.564
274808UNIV PK N;4U
Adder
2.547
274888KELLY CRK;1U
Solar/Wind Harmer
2.956
276776AD2-060 GEN
Solar/Wind Harmer
0.21
958011AF2-095 GEN
Solar/Wind Harmer
7.213
274770LINCOLN ;1U
Adder
3.105
274771LINCOLN ;2U
Adder
3.105
970941AG2-585 GEN
Solar/Wind Harmer
2.755
945421AF1-207 GEN
Solar/Wind Harmer
6.981
957841AF2-078 GEN
Solar/Wind Harmer
3.005
276897AD1-100 C
Solar/Wind Harmer
22.972
276893AG1-478 C
Solar/Wind Harmer
0.217
274674JOLIET 9 ;6U
Adder
7.608
270180AB1-006 GEN1
Solar/Wind Harmer
3.511
24697605MDL-3G C
Solar/Wind Harmer
1.8
24755605MDL-5G
Solar/Wind Harmer
1.177
24697905MDL-4G C
Solar/Wind Harmer
1.12
270181AB1-006 GEN2
Solar/Wind Harmer
0.349
926881AC1-175 GEN
Solar/Wind Harmer
2.719
958481AF2-142 GEN
Solar/Wind Harmer
7.293
274696ROCKY RD ;4P
Adder
5.495
274695ROCKY RD ;2P
Adder
5.368
274693ROCKY RD ;1P
Adder
5.315
274697ROCKY RD ;3P
Adder
1.458
274683WAUKEGAN ;8U
Adder
10.151
274683WAUKEGAN ;8U
Adder
8.557
958491AF2-143 GEN
Solar/Wind Harmer
7.206
962691AG1-118 GEN
Solar/Wind Harmer
14.351
276901AD2-066 C O1
Solar/Wind Harmer
1.677
972235AH1-702 GEN1
Adder
1.178
972236AH1-702 GEN2
Adder
1.024
274764LEE CO EC;5U
Adder
4.297
274765LEE CO EC;6U
Adder
4.297
274762LEE CO EC;3U
Adder
4.287
274763LEE CO EC;4U
Adder
4.247
246937BC-WTG2
Solar/Wind Helper
11.22
270462AD2-086
Solar/Wind Helper
3.792
247522W1-056 GEN
Solar/Wind Helper
1.355
247607V1-011 GEN
Solar/Wind Helper
1.354
942801AE2-298 GEN
Solar/Wind Helper
0.468
253378AE2-206_GEN
Solar/Wind Helper
0.791
990497J1323
External Queue
1.4865119457244873
990792J1392
External Queue
5.113600730895996
LAGNLTFEXP_LAGN->PJM
CLTF
4.154
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.89
TVALTFEXP_TVA->PJM
CLTF
1.699
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.921
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.475
MECLTFEXP_MEC->PJM
CLTF
6.646
SIGELTFEXP_SIGE->PJM
CLTF
0.141
CPLELTFEXP_CPLE->PJM
CLTF
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.83
NYPJM->LTFIMP_NY
CLTF
0.85
LGEELTFEXP_LGEE->PJM
CLTF
1.262
WECLTFEXP_WEC->PJM
CLTF
1.784
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-032T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-032T_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.98 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1923.66
MW Contribution:
4.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.145
965421AG1-410 GEN
Solar/Wind Harmer
112.286
965011AG1-365 GEN
Solar/Wind Harmer
17.416
270024AE2-089 GEN
Solar/Wind Harmer
3.678
24639705ELKHART HY
Adder
0.105
965651AG1-433 GEN
Solar/Wind Harmer
3.74
958861AF2-177 GEN
Solar/Wind Harmer
7.267
270216AD2-079_GEN
Solar/Wind Harmer
0.394
945371AF1-202 GEN
Solar/Wind Harmer
4.378
945111AF1-176 GEN
Solar/Wind Harmer
11.193
957891AF2-083 GEN
Solar/Wind Harmer
9.167
270449AD2-020 GEN
Solar/Wind Harmer
1.677
943021AE2-325 GEN
Solar/Wind Harmer
2.18
24441205WTRV SLR C
Solar/Wind Harmer
0.077
270005AE1-210 C O1
Solar/Wind Harmer
2.952
970825AG2-519 GEN
Solar/Wind Harmer
1.131
270594AE1-207 GEN
Solar/Wind Harmer
7.28
270032AE2-172
Solar/Wind Harmer
2.493
970373AG2-245 GEN
Solar/Wind Harmer
11.236
270055AF2-134 C O1
Solar/Wind Harmer
1.597
274751CRETE EC ;1U
Adder
2.576
274754CRETE EC ;4U
Adder
2.576
274723RIVER EC ;12
Adder
9.377
958381AF2-132 GEN
Solar/Wind Harmer
4.729
964861AG1-349 GEN
Solar/Wind Harmer
4.093
971917AH1-482 GEN
Solar/Wind Harmer
4.722
274812UNIV PK N;8U
Adder
2.599
274802UNIV PARK;5U
Adder
2.984
940581AE2-045 GEN
Solar/Wind Harmer
5.219
971605AH1-302 GEN
Solar/Wind Harmer
4.462
276903AD2-071 C
Solar/Wind Harmer
5.107
972207SS24-0001
Solar/Wind Harmer
11.205
274773LINCOLN ;4U
Adder
3.152
274774LINCOLN ;5U
Adder
3.152
274676JOLIET 29;8U
Adder
15.429
941551AE2-152 GEN
Solar/Wind Harmer
2.277
274732ELWOOD EC;7P
Adder
8.246
274674JOLIET 9 ;6U
Adder
7.724
274871GR RIDGE ;2U
Solar/Wind Harmer
3.828
274847GR RIDGE ;BU
Solar/Wind Harmer
2.517
274745AC1-111 GEN9
Adder
2.763
276694AA1-018 GEN2
Solar/Wind Harmer
3.115
276691AA1-018 GEN1
Solar/Wind Harmer
0.372
274861TOP CROP ;1U
Solar/Wind Harmer
2.99
24791305MDL-5G
Solar/Wind Harmer
1.189
274682WAUKEGAN ;7U
Adder
8.801
274828WAUKEGAN ;BP
Adder
5.402
276805AD2-038 GEN
Solar/Wind Harmer
2.501
939401AE1-172 GEN
Solar/Wind Harmer
6.76
962781AG1-127 GEN
Solar/Wind Harmer
4.608
274822ROCKFORD ;11
Adder
9.331
274761LEE CO EC;2U
Adder
4.352
274766LEE CO EC;7U
Adder
4.301
246936BC-WTG1
Solar/Wind Helper
11.279
270317AD1-130_GEN
Solar/Wind Helper
4.051
270485AE1-090_GEN
Solar/Wind Helper
0.319
270391AF1-285 GEN3
Solar/Wind Helper
0.567
270578AF1-285 GEN2
Solar/Wind Helper
0.567
960841AF2-375 GEN
Solar/Wind Helper
1.323
270286AF1-227 GEN2
Solar/Wind Helper
0.59
241840AF1-064_GEN
Solar/Wind Helper
0.505
241807AE2-176_GEN
Solar/Wind Helper
0.732
276882AE2-255 GEN
Solar/Wind Harmer
1.15
24727205RPMNG3
50/50
3.127
959331AF2-224 GEN
Solar/Wind Harmer
17.416
963791AG1-232 GEN
Solar/Wind Harmer
14.325
965041AG1-368 GEN
Solar/Wind Harmer
10.007
970031AG2-029 GEN
Solar/Wind Harmer
24.399
247521TR3_G114
Solar/Wind Harmer
2.827
270191TR4_S_V150
Solar/Wind Harmer
2.523
965051AG1-369 GEN
Solar/Wind Harmer
4.201
270071AF1-092 GEN
Solar/Wind Harmer
12.386
24729505KEY G4
Adder
4.827
958711AF2-162 GEN
Solar/Wind Harmer
0.692
945581AF1-223 GEN
Solar/Wind Harmer
2.846
961761AG1-017 GEN
Solar/Wind Harmer
0.264
971771AH1-392 GEN
Solar/Wind Harmer
5.448
964611AG1-324 GEN
Solar/Wind Harmer
2.349
944161AF1-084 GEN
Solar/Wind Harmer
1.304
270526AF1-158 GEN
Solar/Wind Harmer
2.633
960681AF2-359 GEN
Solar/Wind Harmer
2.093
247536S-71 GEN
Solar/Wind Harmer
2.215
970289AG2-191 GEN
Solar/Wind Harmer
1.022
971549AH1-272 GEN
Solar/Wind Harmer
9.608
958391AF2-133 GEN
Solar/Wind Harmer
4.696
959141AF2-205 GEN
Solar/Wind Harmer
3.114
972037AH1-567 GEN1
Adder
0.094
274827FISK ;RP
Adder
3.964
274800UNIV PARK;3U
Adder
2.972
274801UNIV PARK;4U
Adder
2.972
960591AF2-350 GEN
Solar/Wind Harmer
5.086
274775LINCOLN ;6U
Adder
3.152
274776LINCOLN ;7U
Adder
3.152
274777LINCOLN ;8U
Adder
3.152
972228AH1-698 GEN2
Adder
1.876
972227AH1-698 GEN1
Adder
1.321
274687WILL CNTY;4U
Adder
14.092
274687WILL CNTY;4U
Adder
14.092
274675JOLIET 29;7U
Adder
15.429
274675JOLIET 29;7U
Adder
14.878
276893AG1-478 C
Solar/Wind Harmer
0.276
274728ELWOOD EC;5P
Adder
8.246
274731ELWOOD EC;2P
Adder
8.246
274733ELWOOD EC;3P
Adder
8.246
274735ELWOOD EC;4P
Adder
8.246
970833AG2-524 GEN
Solar/Wind Harmer
4.35
970833AG2-524 GEN
Solar/Wind Harmer
2.023
274744AC1-111 GEN8
Adder
2.763
274746AC1-111 G10
Adder
2.763
946581AF1-322 GEN
Solar/Wind Harmer
5.048
24691005MDL-2G C
Solar/Wind Harmer
1.824
270543AE2-219 C
Solar/Wind Harmer
4.891
970073AG2-061 GEN
Solar/Wind Harmer
1.134
274823ROCKFORD ;21
Adder
9.263
972267AH1-718 GEN
Adder
1.93
957201AF2-014 GEN
Solar/Wind Helper
8.91
270223U2-072_GEN1
Solar/Wind Helper
0.838
270224U2-072_GEN2
Solar/Wind Helper
0.838
270227U2-072_GEN3
Solar/Wind Helper
0.838
270228U2-072_GEN4
Solar/Wind Helper
0.838
270231U2-072_GEN5
Solar/Wind Helper
0.838
966831AG1-554 GEN
Solar/Wind Helper
0.91
270499AE1-146 GEN
Solar/Wind Helper
2.194
945641AF1-229 GEN
Solar/Wind Helper
1.04
965431AG1-411 GEN
50/50
43.522
24727105RPMNG2
50/50
3.146
970583AG2-370 GEN
50/50
2.327
965021AG1-366 GEN
Solar/Wind Harmer
4.05
270043AE2-236 GEN
Solar/Wind Harmer
4.963
270063AE2-323 C
Solar/Wind Harmer
1.824
944531AF1-118 GEN
Solar/Wind Harmer
26.796
24695305TIMB G C
Solar/Wind Harmer
2.376
247643Z2-116 C
Solar/Wind Harmer
0.045
945111AF1-176 GEN
Solar/Wind Harmer
3.547
962031AG1-047 GEN
Solar/Wind Harmer
1.866
957741AF2-068 GEN
Solar/Wind Harmer
9.255
270505AE1-170 C O1
Solar/Wind Harmer
9.079
24441505OLIV SLR
Solar/Wind Harmer
0.077
971347AH1-153 GEN
Solar/Wind Harmer
2.853
946031AF1-268 GEN
Solar/Wind Harmer
4.547
270004AE1-209 GEN
Solar/Wind Harmer
2.952
247642Z2-115 C
Solar/Wind Harmer
0.035
970825AG2-519 GEN
Solar/Wind Harmer
3.037
965461AG1-414 GEN
Solar/Wind Harmer
1.219
970289AG2-191 GEN
Solar/Wind Harmer
0.413
972231SS25-0005
Solar/Wind Harmer
5.002
270246TR4_N_V150
Solar/Wind Harmer
0.715
270247TR4_N_V136
Solar/Wind Harmer
0.715
942221AE2-234 GEN
Solar/Wind Harmer
2.805
944231AF1-091 GEN
Solar/Wind Harmer
14.059
247620Y3-023
Adder
0.331
944541AF1-119 GEN
Solar/Wind Harmer
2.865
960971AF2-388 GEN
Solar/Wind Harmer
7.48
270201AC2-176 GEN
Solar/Wind Harmer
3.171
270031AE2-169
Solar/Wind Harmer
4.967
270599AE1-208 GEN
Solar/Wind Harmer
4.967
961051AF2-396 GEN
Solar/Wind Harmer
9.671
961051AF2-396 GEN
Solar/Wind Harmer
4.498
964611AG1-324 GEN
Solar/Wind Harmer
0.315
247621Y3-024
Adder
0.141
970349AG2-230 GEN
Solar/Wind Harmer
8.559
965681AG1-436 GEN
Solar/Wind Harmer
6.923
965791AG1-447 GEN
Solar/Wind Harmer
3.542
970291AG2-192 GEN
Solar/Wind Harmer
0.699
970291AG2-192 GEN
Solar/Wind Harmer
0.225
270535AF1-215 GEN1
Solar/Wind Harmer
2.396
270536AF1-215 GEN2
Solar/Wind Harmer
2.396
274805UNIV PK N;1U
Adder
2.605
274808UNIV PK N;4U
Adder
2.588
274888KELLY CRK;1U
Solar/Wind Harmer
3.002
276776AD2-060 GEN
Solar/Wind Harmer
0.213
958011AF2-095 GEN
Solar/Wind Harmer
7.324
970941AG2-585 GEN
Solar/Wind Harmer
2.798
274770LINCOLN ;1U
Adder
3.152
274771LINCOLN ;2U
Adder
3.152
24725505WLD G2 C
Solar/Wind Harmer
1.998
24699105WLD G1 C
Solar/Wind Harmer
1.974
945421AF1-207 GEN
Solar/Wind Harmer
7.056
957841AF2-078 GEN
Solar/Wind Harmer
3.037
276897AD1-100 C
Solar/Wind Harmer
23.32
276893AG1-478 C
Solar/Wind Harmer
0.22
274674JOLIET 9 ;6U
Adder
7.724
958481AF2-142 GEN
Solar/Wind Harmer
7.404
270180AB1-006 GEN1
Solar/Wind Harmer
3.548
24697605MDL-3G C
Solar/Wind Harmer
1.818
24755605MDL-5G
Solar/Wind Harmer
1.189
24697905MDL-4G C
Solar/Wind Harmer
1.132
270181AB1-006 GEN2
Solar/Wind Harmer
0.353
274696ROCKY RD ;4P
Adder
5.578
274695ROCKY RD ;2P
Adder
5.45
274693ROCKY RD ;1P
Adder
5.396
274697ROCKY RD ;3P
Adder
1.48
274683WAUKEGAN ;8U
Adder
10.306
274683WAUKEGAN ;8U
Adder
8.688
970883AG2-550 GEN
Solar/Wind Harmer
4.891
970885AG2-551 GEN
Solar/Wind Harmer
1.137
958491AF2-143 GEN
Solar/Wind Harmer
7.315
962691AG1-118 GEN
Solar/Wind Harmer
14.569
276901AD2-066 C O1
Solar/Wind Harmer
1.703
960751AF2-366 GEN
Solar/Wind Harmer
1.39
972235AH1-702 GEN1
Adder
1.196
972236AH1-702 GEN2
Adder
1.04
274764LEE CO EC;5U
Adder
4.363
274765LEE CO EC;6U
Adder
4.363
274762LEE CO EC;3U
Adder
4.352
274763LEE CO EC;4U
Adder
4.311
246937BC-WTG2
Solar/Wind Helper
11.279
270462AD2-086
Solar/Wind Helper
3.664
247522W1-056 GEN
Solar/Wind Helper
1.247
253378AE2-206_GEN
Solar/Wind Helper
0.704
972181SS23-001
Solar/Wind Harmer
3.126
274752CRETE EC ;2U
Adder
2.576
274753CRETE EC ;3U
Adder
2.576
274724RIVER EC ;11
Adder
9.26
964401AG1-302 GEN
Solar/Wind Harmer
4.729
274814UNIV PK N;0U
Adder
2.622
274807UNIV PK N;3U
Adder
2.616
274811UNIV PK N;7U
Adder
2.599
276164X3-005 C
Solar/Wind Harmer
0.363
274803UNIV PARK;6U
Adder
2.984
274826FISK ;BP
Adder
5.593
972038AH1-567 GEN2
Adder
0.186
274887GEN-1.85
Solar/Wind Harmer
2.71
276772AC2-154 GEN
Solar/Wind Harmer
1.419
276843GEN-1.7
Solar/Wind Harmer
0.292
276806AD2-047 C O1
Solar/Wind Harmer
5.441
274772LINCOLN ;3U
Adder
3.152
972259AH1-714 GEN
Adder
9.603
274676JOLIET 29;8U
Adder
14.878
939351AE1-166 GEN
Solar/Wind Harmer
2.977
274729ELWOOD EC;1P
Adder
8.246
274730ELWOOD EC;6P
Adder
8.246
274734ELWOOD EC;8P
Adder
8.246
274736ELWOOD EC;9P
Adder
8.246
970707AG2-453 GEN
Solar/Wind Harmer
14.045
943121AE2-341 GEN
Solar/Wind Harmer
7.409
943591AF1-030 GEN
Solar/Wind Harmer
4.939
274862TOP CROP ;2U
Solar/Wind Harmer
2.496
24690905MDL-1G C
Solar/Wind Harmer
3.961
970781AG2-491 GEN
Solar/Wind Harmer
4.933
274682WAUKEGAN ;7U
Adder
8.801
274760LEE CO EC;1U
Adder
4.352
274767LEE CO EC;8U
Adder
4.301
246938BC-WTG3
Solar/Wind Helper
11.472
942871AE2-306 GEN
Solar/Wind Helper
0.426
270284AF1-227 GEN1
Solar/Wind Helper
1.61
270287AF1-227 GEN3
Solar/Wind Helper
0.59
270541AE2-072 C
Solar/Wind Helper
1.17
276820AF1-078_GEN
Solar/Wind Helper
0.329
276868AE1-113 GEN
Solar/Wind Harmer
3.451
990497J1323
External Queue
1.3108574151992798
LAGNLTFEXP_LAGN->PJM
CLTF
4.246
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
1.745
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.654
MECLTFEXP_MEC->PJM
CLTF
6.749
SIGELTFEXP_SIGE->PJM
CLTF
0.143
CPLELTFEXP_CPLE->PJM
CLTF
0.049
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.399
NYPJM->LTFIMP_NY
CLTF
0.879
LGEELTFEXP_LGEE->PJM
CLTF
1.302
WECLTFEXP_WEC->PJM
CLTF
1.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.16 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1870.91
MW Contribution:
4.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.153
965421AG1-410 GEN
Solar/Wind Harmer
112.627
965011AG1-365 GEN
Solar/Wind Harmer
17.395
270024AE2-089 GEN
Solar/Wind Harmer
3.658
965651AG1-433 GEN
Solar/Wind Harmer
3.713
958861AF2-177 GEN
Solar/Wind Harmer
7.211
24639705ELKHART HY
Adder
0.101
945371AF1-202 GEN
Solar/Wind Harmer
4.341
270216AD2-079_GEN
Solar/Wind Harmer
0.375
945111AF1-176 GEN
Solar/Wind Harmer
10.514
957891AF2-083 GEN
Solar/Wind Harmer
8.594
270449AD2-020 GEN
Solar/Wind Harmer
1.559
943021AE2-325 GEN
Solar/Wind Harmer
2.026
270246TR4_N_V150
Solar/Wind Harmer
0.719
270247TR4_N_V136
Solar/Wind Harmer
0.719
942221AE2-234 GEN
Solar/Wind Harmer
2.788
944231AF1-091 GEN
Solar/Wind Harmer
14.177
247620Y3-023
Adder
0.318
944541AF1-119 GEN
Solar/Wind Harmer
2.844
960971AF2-388 GEN
Solar/Wind Harmer
7.426
270201AC2-176 GEN
Solar/Wind Harmer
3.145
270031AE2-169
Solar/Wind Harmer
4.918
270599AE1-208 GEN
Solar/Wind Harmer
4.918
964611AG1-324 GEN
Solar/Wind Harmer
0.312
247621Y3-024
Adder
0.14
961051AF2-396 GEN
Solar/Wind Harmer
9.024
961051AF2-396 GEN
Solar/Wind Harmer
4.197
970349AG2-230 GEN
Solar/Wind Harmer
8.196
970291AG2-192 GEN
Solar/Wind Harmer
0.688
970291AG2-192 GEN
Solar/Wind Harmer
0.222
965681AG1-436 GEN
Solar/Wind Harmer
6.585
965791AG1-447 GEN
Solar/Wind Harmer
3.369
270535AF1-215 GEN1
Solar/Wind Harmer
2.292
270536AF1-215 GEN2
Solar/Wind Harmer
2.292
274805UNIV PK N;1U
Adder
2.501
274808UNIV PK N;4U
Adder
2.485
24725505WLD G2 C
Solar/Wind Harmer
1.967
24699105WLD G1 C
Solar/Wind Harmer
1.944
274770LINCOLN ;1U
Adder
3.034
270005AE1-210 C O1
Solar/Wind Harmer
2.922
970825AG2-519 GEN
Solar/Wind Harmer
1.119
24727205RPMNG3
50/50
3.135
959331AF2-224 GEN
Solar/Wind Harmer
17.395
963791AG1-232 GEN
Solar/Wind Harmer
14.285
965041AG1-368 GEN
Solar/Wind Harmer
10.035
970031AG2-029 GEN
Solar/Wind Harmer
23.846
247521TR3_G114
Solar/Wind Harmer
2.843
270191TR4_S_V150
Solar/Wind Harmer
2.536
965051AG1-369 GEN
Solar/Wind Harmer
4.223
270071AF1-092 GEN
Solar/Wind Harmer
12.276
24729505KEY G4
Adder
4.796
958711AF2-162 GEN
Solar/Wind Harmer
0.687
945581AF1-223 GEN
Solar/Wind Harmer
2.822
961761AG1-017 GEN
Solar/Wind Harmer
0.262
964611AG1-324 GEN
Solar/Wind Harmer
2.329
971771AH1-392 GEN
Solar/Wind Harmer
5.16
270526AF1-158 GEN
Solar/Wind Harmer
2.493
944161AF1-084 GEN
Solar/Wind Harmer
1.205
247536S-71 GEN
Solar/Wind Harmer
2.195
970289AG2-191 GEN
Solar/Wind Harmer
1.005
960681AF2-359 GEN
Solar/Wind Harmer
1.99
958391AF2-133 GEN
Solar/Wind Harmer
4.504
959141AF2-205 GEN
Solar/Wind Harmer
2.989
972037AH1-567 GEN1
Adder
0.09
274827FISK ;RP
Adder
3.81
274800UNIV PARK;3U
Adder
2.857
274801UNIV PARK;4U
Adder
2.857
270594AE1-207 GEN
Solar/Wind Harmer
7.172
270032AE2-172
Solar/Wind Harmer
2.456
24441205WTRV SLR C
Solar/Wind Harmer
0.07
970373AG2-245 GEN
Solar/Wind Harmer
10.729
274751CRETE EC ;1U
Adder
2.472
274754CRETE EC ;4U
Adder
2.472
270055AF2-134 C O1
Solar/Wind Harmer
1.528
276903AD2-071 C
Solar/Wind Harmer
5.027
274723RIVER EC ;12
Adder
9.005
958381AF2-132 GEN
Solar/Wind Harmer
4.531
964861AG1-349 GEN
Solar/Wind Harmer
3.922
971917AH1-482 GEN
Solar/Wind Harmer
4.525
274812UNIV PK N;8U
Adder
2.496
274802UNIV PARK;5U
Adder
2.868
940581AE2-045 GEN
Solar/Wind Harmer
5.013
971605AH1-302 GEN
Solar/Wind Harmer
4.286
972207SS24-0001
Solar/Wind Harmer
10.788
274773LINCOLN ;4U
Adder
3.034
274774LINCOLN ;5U
Adder
3.034
274676JOLIET 29;8U
Adder
14.839
941551AE2-152 GEN
Solar/Wind Harmer
2.191
274674JOLIET 9 ;6U
Adder
7.43
274732ELWOOD EC;7P
Adder
7.931
274871GR RIDGE ;2U
Solar/Wind Harmer
3.683
274847GR RIDGE ;BU
Solar/Wind Harmer
2.422
274745AC1-111 GEN9
Adder
2.659
24791305MDL-5G
Solar/Wind Harmer
1.146
276694AA1-018 GEN2
Solar/Wind Harmer
2.996
276691AA1-018 GEN1
Solar/Wind Harmer
0.358
274861TOP CROP ;1U
Solar/Wind Harmer
2.875
274682WAUKEGAN ;7U
Adder
8.468
274828WAUKEGAN ;BP
Adder
5.198
276805AD2-038 GEN
Solar/Wind Harmer
2.406
942081AE2-220 GEN
Solar/Wind Harmer
2.999
270209AC1-174_GEN
Solar/Wind Harmer
1.909
270437AC2-090 C
Solar/Wind Harmer
2.618
270239V3-007_GEN1
Solar/Wind Harmer
0.807
274822ROCKFORD ;11
Adder
8.982
274761LEE CO EC;2U
Adder
4.19
274766LEE CO EC;7U
Adder
4.141
246936BC-WTG1
Solar/Wind Helper
11.248
270317AD1-130_GEN
Solar/Wind Helper
3.957
270485AE1-090_GEN
Solar/Wind Helper
0.311
270391AF1-285 GEN3
Solar/Wind Helper
0.553
270578AF1-285 GEN2
Solar/Wind Helper
0.553
960841AF2-375 GEN
Solar/Wind Helper
1.221
270286AF1-227 GEN2
Solar/Wind Helper
0.568
939401AE1-172 GEN
Solar/Wind Harmer
3.21
274771LINCOLN ;2U
Adder
3.034
274888KELLY CRK;1U
Solar/Wind Harmer
2.886
276776AD2-060 GEN
Solar/Wind Harmer
0.205
958011AF2-095 GEN
Solar/Wind Harmer
7.042
970941AG2-585 GEN
Solar/Wind Harmer
2.69
970883AG2-550 GEN
Solar/Wind Harmer
4.844
970885AG2-551 GEN
Solar/Wind Harmer
1.127
945421AF1-207 GEN
Solar/Wind Harmer
6.795
957841AF2-078 GEN
Solar/Wind Harmer
2.925
276897AD1-100 C
Solar/Wind Harmer
22.437
276893AG1-478 C
Solar/Wind Harmer
0.212
274674JOLIET 9 ;6U
Adder
7.43
270180AB1-006 GEN1
Solar/Wind Harmer
3.419
24697605MDL-3G C
Solar/Wind Harmer
1.752
24755605MDL-5G
Solar/Wind Harmer
1.146
24697905MDL-4G C
Solar/Wind Harmer
1.091
270181AB1-006 GEN2
Solar/Wind Harmer
0.34
958481AF2-142 GEN
Solar/Wind Harmer
7.122
274696ROCKY RD ;4P
Adder
5.368
274695ROCKY RD ;2P
Adder
5.245
274693ROCKY RD ;1P
Adder
5.193
274697ROCKY RD ;3P
Adder
1.425
274683WAUKEGAN ;8U
Adder
9.917
274683WAUKEGAN ;8U
Adder
8.36
958491AF2-143 GEN
Solar/Wind Harmer
7.038
926881AC1-175 GEN
Solar/Wind Harmer
2.618
962691AG1-118 GEN
Solar/Wind Harmer
14.023
276901AD2-066 C O1
Solar/Wind Harmer
1.639
972235AH1-702 GEN1
Adder
1.151
972236AH1-702 GEN2
Adder
1.001
274764LEE CO EC;5U
Adder
4.2
274765LEE CO EC;6U
Adder
4.2
274762LEE CO EC;3U
Adder
4.19
274763LEE CO EC;4U
Adder
4.151
246937BC-WTG2
Solar/Wind Helper
11.248
270462AD2-086
Solar/Wind Helper
3.579
247522W1-056 GEN
Solar/Wind Helper
1.191
253378AE2-206_GEN
Solar/Wind Helper
0.692
274775LINCOLN ;6U
Adder
3.034
274776LINCOLN ;7U
Adder
3.034
274777LINCOLN ;8U
Adder
3.034
960591AF2-350 GEN
Solar/Wind Harmer
4.891
972228AH1-698 GEN2
Adder
1.804
972227AH1-698 GEN1
Adder
1.27
274687WILL CNTY;4U
Adder
13.551
274687WILL CNTY;4U
Adder
13.551
270543AE2-219 C
Solar/Wind Harmer
4.844
274675JOLIET 29;7U
Adder
14.839
274675JOLIET 29;7U
Adder
14.309
276893AG1-478 C
Solar/Wind Harmer
0.266
274728ELWOOD EC;5P
Adder
7.931
274731ELWOOD EC;2P
Adder
7.931
274733ELWOOD EC;3P
Adder
7.931
274735ELWOOD EC;4P
Adder
7.931
970833AG2-524 GEN
Solar/Wind Harmer
4.185
970833AG2-524 GEN
Solar/Wind Harmer
1.947
274744AC1-111 GEN8
Adder
2.659
274746AC1-111 G10
Adder
2.659
946581AF1-322 GEN
Solar/Wind Harmer
4.864
24691005MDL-2G C
Solar/Wind Harmer
1.758
970073AG2-061 GEN
Solar/Wind Harmer
1.091
274823ROCKFORD ;21
Adder
8.917
972267AH1-718 GEN
Adder
1.858
957201AF2-014 GEN
Solar/Wind Helper
8.886
270223U2-072_GEN1
Solar/Wind Helper
0.817
270224U2-072_GEN2
Solar/Wind Helper
0.817
270227U2-072_GEN3
Solar/Wind Helper
0.817
270228U2-072_GEN4
Solar/Wind Helper
0.817
270231U2-072_GEN5
Solar/Wind Helper
0.817
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
2.038
945641AF1-229 GEN
Solar/Wind Helper
0.949
965431AG1-411 GEN
50/50
43.654
24727105RPMNG2
50/50
3.154
970583AG2-370 GEN
50/50
2.334
965021AG1-366 GEN
Solar/Wind Harmer
4.045
270043AE2-236 GEN
Solar/Wind Harmer
4.904
270063AE2-323 C
Solar/Wind Harmer
1.778
944531AF1-118 GEN
Solar/Wind Harmer
26.634
24695305TIMB G C
Solar/Wind Harmer
2.398
247643Z2-116 C
Solar/Wind Harmer
0.043
962031AG1-047 GEN
Solar/Wind Harmer
1.85
957741AF2-068 GEN
Solar/Wind Harmer
9.18
945111AF1-176 GEN
Solar/Wind Harmer
3.332
270505AE1-170 C O1
Solar/Wind Harmer
8.496
971347AH1-153 GEN
Solar/Wind Harmer
2.732
24441505OLIV SLR
Solar/Wind Harmer
0.073
946031AF1-268 GEN
Solar/Wind Harmer
4.5
270004AE1-209 GEN
Solar/Wind Harmer
2.922
970825AG2-519 GEN
Solar/Wind Harmer
3.004
247642Z2-115 C
Solar/Wind Harmer
0.034
965461AG1-414 GEN
Solar/Wind Harmer
1.2
970289AG2-191 GEN
Solar/Wind Harmer
0.406
972231SS25-0005
Solar/Wind Harmer
4.799
972181SS23-001
Solar/Wind Harmer
2.999
274752CRETE EC ;2U
Adder
2.472
274753CRETE EC ;3U
Adder
2.472
274724RIVER EC ;11
Adder
8.893
964401AG1-302 GEN
Solar/Wind Harmer
4.531
274814UNIV PK N;0U
Adder
2.518
274807UNIV PK N;3U
Adder
2.512
274811UNIV PK N;7U
Adder
2.496
276164X3-005 C
Solar/Wind Harmer
0.349
274803UNIV PARK;6U
Adder
2.868
274826FISK ;BP
Adder
5.376
972038AH1-567 GEN2
Adder
0.179
274772LINCOLN ;3U
Adder
3.034
274887GEN-1.85
Solar/Wind Harmer
2.606
276772AC2-154 GEN
Solar/Wind Harmer
1.365
276843GEN-1.7
Solar/Wind Harmer
0.28
276806AD2-047 C O1
Solar/Wind Harmer
5.232
972259AH1-714 GEN
Adder
9.24
274676JOLIET 29;8U
Adder
14.309
939351AE1-166 GEN
Solar/Wind Harmer
2.865
970707AG2-453 GEN
Solar/Wind Harmer
13.519
274729ELWOOD EC;1P
Adder
7.931
274730ELWOOD EC;6P
Adder
7.931
274734ELWOOD EC;8P
Adder
7.931
274736ELWOOD EC;9P
Adder
7.931
943121AE2-341 GEN
Solar/Wind Harmer
7.131
943591AF1-030 GEN
Solar/Wind Harmer
4.754
24690905MDL-1G C
Solar/Wind Harmer
3.816
970781AG2-491 GEN
Solar/Wind Harmer
4.753
274862TOP CROP ;2U
Solar/Wind Harmer
2.401
274682WAUKEGAN ;7U
Adder
8.468
24379505HDWTR1G C
Solar/Wind Harmer
3.708
270240V3-007_GEN2
Solar/Wind Harmer
2.901
274760LEE CO EC;1U
Adder
4.19
274767LEE CO EC;8U
Adder
4.141
246938BC-WTG3
Solar/Wind Helper
11.44
942871AE2-306 GEN
Solar/Wind Helper
0.415
270284AF1-227 GEN1
Solar/Wind Helper
1.55
270287AF1-227 GEN3
Solar/Wind Helper
0.568
270541AE2-072 C
Solar/Wind Helper
1.068
276820AF1-078_GEN
Solar/Wind Helper
0.323
990497J1323
External Queue
1.3924421072006226
990792J1392
External Queue
4.7900004386901855
LAGNLTFEXP_LAGN->PJM
CLTF
4.113
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.97
TVALTFEXP_TVA->PJM
CLTF
1.694
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.532
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.457
MECLTFEXP_MEC->PJM
CLTF
6.506
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CPLELTFEXP_CPLE->PJM
CLTF
0.049
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.258
NYPJM->LTFIMP_NY
CLTF
0.855
LGEELTFEXP_LGEE->PJM
CLTF
1.261
WECLTFEXP_WEC->PJM
CLTF
1.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.115
AH1-155LTFEXP_AH1-155->PJM
LTF
0.172

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#15023_05JAY 138_E_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15023_05JAY 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.03 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:267.84
MW Contribution:
36.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270024AE2-089 GEN
Solar/Wind Harmer
8.289
962031AG1-047 GEN
Solar/Wind Harmer
7.183
957741AF2-068 GEN
Solar/Wind Harmer
35.634
971029AG2-637 GEN
Solar/Wind Harmer
65.379
270543AE2-219 C
Solar/Wind Harmer
36.583
247536S-71 GEN
Solar/Wind Harmer
12.493
961761AG1-017 GEN
Solar/Wind Harmer
1.017
963791AG1-232 GEN
Solar/Wind Harmer
11.698
247621Y3-024
50/50
0.702
970883AG2-550 GEN
Solar/Wind Harmer
36.583
970885AG2-551 GEN
Solar/Wind Harmer
8.508
270201AC2-176 GEN
Solar/Wind Harmer
12.209
942221AE2-234 GEN
Solar/Wind Harmer
2.408
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.146
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.438
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.034
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.504
MECLTFEXP_MEC->PJM
CLTF
0.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.278
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.103
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.054

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#15176_05JAY 138_E2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15176_05JAY 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.3 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:265.97
MW Contribution:
36.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
65.236
270543AE2-219 C
Solar/Wind Harmer
36.464
247536S-71 GEN
Solar/Wind Harmer
12.435
961761AG1-017 GEN
Solar/Wind Harmer
1.005
963791AG1-232 GEN
Solar/Wind Harmer
11.627
962031AG1-047 GEN
Solar/Wind Harmer
7.099
957741AF2-068 GEN
Solar/Wind Harmer
35.219
270024AE2-089 GEN
Solar/Wind Harmer
8.209
247621Y3-024
50/50
0.702
970883AG2-550 GEN
Solar/Wind Harmer
36.464
970885AG2-551 GEN
Solar/Wind Harmer
8.48
270201AC2-176 GEN
Solar/Wind Harmer
12.067
942221AE2-234 GEN
Solar/Wind Harmer
2.427
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.146
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.436
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.515
MECLTFEXP_MEC->PJM
CLTF
0.306
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.294
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.103
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.054
CONTINGENCY 'AEP_P4_#8975_05KAMMER 765_MM2_SRT-A'
 OPEN BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT7A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT10A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 243469 CKT 3   /*05BEATTY     345.0 - 05BEATTY     138.0
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1   /*05BEATTY     345.0 - 05ADKINS     345.0
END
CONTINGENCY 'AEP_P4_#16620_05ADKINS 345_A_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1   /*05BEATTY     345.0 - 05ADKINS     345.0
 OPEN BRANCH FROM BUS 245769 TO BUS 253100 CKT 1   /*05ADKINS     345.0 - 09ATLNTA     345.0
END
CONTINGENCY 'AEP_P4_#16621_05ADKINS 345_A1_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1                /*05BEATTY     345.0 - 05ADKINS     345.0
 OPEN BRANCH FROM BUS 245769 TO BUS 270156 TO BUS 270157 CKT 1  /*05ADKINS     345.0 - DARBY CT1     13.8 - DARBY CT2     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270158 TO BUS 270159 CKT 1  /*05ADKINS     345.0 - DARBY CT3     13.8 - DARBY CT4     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270160 TO BUS 270161 CKT 1  /*05ADKINS     345.0 - DARBY CT5     13.8 - DARBY CT6     13.8
END
CONTINGENCY 'AEP_P4_#16622_05ADKINS 345_B1_SRT-A'
 OPEN BRANCH FROM BUS 245769 TO BUS 253100 CKT 1                /*05ADKINS     345.0 - 09ATLNTA     345.0
 OPEN BRANCH FROM BUS 245769 TO BUS 270156 TO BUS 270157 CKT 1  /*05ADKINS     345.0 - DARBY CT1     13.8 - DARBY CT2     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270158 TO BUS 270159 CKT 1  /*05ADKINS     345.0 - DARBY CT3     13.8 - DARBY CT4     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270160 TO BUS 270161 CKT 1  /*05ADKINS     345.0 - DARBY CT5     13.8 - DARBY CT6     13.8
END
CONTINGENCY 'AEP_P4_#2085_05BEATTY 345_304C_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1   /*05BEATTY     345.0 - 05ADKINS     345.0
 OPEN BRANCH FROM BUS 243453 TO BUS 288778 CKT 1   /*05BEATTY     345.0 - 05CYPRUS     345.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P4_#2812_05TANNER 345_T2_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 249567 CKT 1   /*05TANNER     345.0 - 08M.FORT     345.0
END
CONTINGENCY 'DEOK_P4_1401_MIAMI FORT_SRT-A'
 OPEN BRANCH FROM BUS 249567 TO BUS 243233 CKT 1   /*08M.FORT     345.0 - 05TANNER     345.0
 OPEN BRANCH FROM BUS 249567 TO BUS 250057 CKT 9   /*08M.FORT     345.0 - 08M.FORT     138.0
END
CONTINGENCY 'DEOK_P_4561TODWOOD14562TODWOOD2_SRT-A'
 OPEN BRANCH FROM BUS 249574 TO BUS 249576 CKT 1   /*08TDHNTR     345.0 - 08WODSDL     345.0
 OPEN BRANCH FROM BUS 249574 TO BUS 249576 CKT 2   /*08TDHNTR     345.0 - 08WODSDL     345.0
END
CONTINGENCY 'DEOK_P4_1301_TERMINAL_SRT-A'
 OPEN BRANCH FROM BUS 249565 TO BUS 249575 CKT 1   /*08EBEND      345.0 - 08TERMNL     345.0
 OPEN BRANCH FROM BUS 249567 TO BUS 249575 CKT 1   /*08M.FORT     345.0 - 08TERMNL     345.0
END
CONTINGENCY 'DAY_BLAZER_FB_??_B_SRT-A'
 DISCONNECT BUS 253290   /*09BLAZER     138.0
 DISCONNECT BUS 253291   /*09ORPHRD     138.0
END
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'
 OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4   /*05JAY        138.0 - 05JAY 4EQ      1.0
 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1   /*05JAY        138.0 - AG1-324 TP   138.0
 OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4   /*05JAY         34.5 - 05JAY 4EQ      1.0
 OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4   /*05JAY         69.0 - 05JAY 4EQ      1.0
END
CONTINGENCY 'AEP_P4_#15176_05JAY 138_E2_SRT-A'
 OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2   /*05JAY        138.0 - 05JAY 2EQ      1.0
 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1   /*05JAY        138.0 - AG1-324 TP   138.0
 OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2   /*05JAY         69.0 - 05JAY 2EQ      1.0
 OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2   /*05JAY 2EQ      1.0 - 05JAY T2      13.1
 REMOVE SWSHUNT FROM BUS 243319                    /*05JAY        138.0
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P4_#7443_05DUMONT 765_A_SRT-A'
 OPEN BRANCH FROM BUS 243205 TO BUS 243206 CKT 1    /*05COOK       765.0 - 05DUMONT     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#7442_05SORENS 765_K2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#7444_05DUMONT 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243641 CKT 2    /*05DUMONT     765.0 - 05DUMONT 2EQ   1.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 243219 TO BUS 243641 CKT 2    /*05DUMONT     345.0 - 05DUMONT 2EQ   1.0
 OPEN BRANCH FROM BUS 243641 TO BUS 243642 CKT 2    /*05DUMONT 2EQ   1.0 - 05DUMONT T2   34.5
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#9456_06DEARB1 345_DC_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'AEP_P2-2_#9456_06DEARB1 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A'
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1   /*06DEARB1     345.0 - 06PIERCE     345.0
 OPEN BRANCH FROM BUS 248002 TO BUS 248000 CKT 2   /*06DEARB2     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 248002 TO BUS 249564 CKT 1   /*06DEARB2     345.0 - 08BUFTN1     345.0
END
CONTINGENCY 'AEP_P7-1_#485___SRT-A'
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1   /*06DEARB1     345.0 - 06PIERCE     345.0
 OPEN BRANCH FROM BUS 248002 TO BUS 249564 CKT 1   /*06DEARB2     345.0 - 08BUFTN1     345.0
END
CONTINGENCY 'DEOK_P4_1579_EASTBEND_SRT-A'
 OPEN BRANCH FROM BUS 249565 TO BUS 249575 CKT 1   /*08EBEND      345.0 - 08TERMNL     345.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P7-1_#11067___SRT-A'
 OPEN BRANCH FROM BUS 243051 TO BUS 247864 CKT 1   /*05NDELPH     138.0 - 05LOGTOWN    138.0
 OPEN BRANCH FROM BUS 246352 TO BUS 246950 CKT 1   /*05HAVILAND2  138.0 - 05TIMBER SW  138.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-032T_SRT-A'
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 256583 CKT 1   /*19LULU       345.0 - 18MOROCCO    345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264613 CKT 1   /*19LULU       345.0 - 19MON34      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264839 CKT 1   /*19LULU       345.0 - 19MILAN      345.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
238563 to 238654 ckt 1
243211 to 242933 ckt 1
242920 to 235102 ckt 5
288724 to 945630 ckt 1
247977 to 242524 ckt 17
242519 to 314912 ckt 1
243262 to 250001 ckt 1
290085 to 290084 ckt 1
243458 to 246752 ckt 1
242925 to 235117 ckt 1
246929 to 242935 ckt 1
242926 to 246751 ckt 1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
242516 to 242920 ckt 1
242933 to 965420 ckt 1
243232 to 246999 ckt 3
246999 to 290607 ckt Z1
243233 to 249567 ckt 1
248005 to 242528 ckt 1
248013 to 242938 ckt 1
945630 to 243453 ckt 1
965420 to 246929 ckt 1
971028 to 290085 ckt 1

Winter Peak Analysis

The New Service Request AG2-550 was evaluated as a 100.0 MW (60.0 MW Capacity) injection in the AEP area.

AG2-550 was evaluated as part of a plant. The plant consists of AG2-550, AG2-551. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (120.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC120.49 %1737.0B2092.95
0.36
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC118.4 %1737.0B2056.53
0.37
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC116.41 %1737.0B2022.06
0.37
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC115.97 %1737.0B2014.34
0.35
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC113.19 %4961.0B5615.13
0.72
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC103.69 %4961.0B5144.06
0.73
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC103.1 %4961.0B5114.58
0.73
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC102.1 %4961.0B5065.25
0.73
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC102.1 %4961.0B5065.17
0.73
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC103.66 %2219.0B2300.12
0.36
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC101.06 %2219.0B2242.58
0.37
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC100.53 %2219.0B2230.82
0.37
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC100.04 %2219.0B2219.82
0.35
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC108.89 %2317.0B2523.04
0.4
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC107.9 %2317.0B2499.98
0.41
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC107.01 %2317.0B2479.49
0.41
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC107.01 %2317.0B2479.4
0.4
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
BusAC106.64 %2317.0B2470.96
0.75
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
BreakerAC106.64 %2317.0B2470.93
0.75
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC106.03 %2219.0B2352.88
0.36
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC103.21 %2219.0B2290.26
0.37
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC102.89 %2219.0B2283.06
0.37
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC102.36 %2219.0B2271.47
0.35

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.49 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2092.95
MW Contribution:
0.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.345
24729305KEY G2
50/50
6.841
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.937
957891AF2-083 GEN
Solar/Wind Harmer
0.723
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.683
274888KELLY CRK;1U
Solar/Wind Harmer
5.846
276893AG1-478 C
Solar/Wind Harmer
0.338
270005AE1-210 C O1
Solar/Wind Harmer
6.493
276602WESTBROOK C
Solar/Wind Harmer
1.703
274863CRW1-WTG
Solar/Wind Harmer
4.717
274864CRW2-WTG
Solar/Wind Harmer
4.717
276603SUBLETTE C
Solar/Wind Harmer
0.798
24387305FR-4G C
Solar/Wind Harmer
4.532
24386605FR-22G C
Solar/Wind Harmer
3.021
24387005FR-3G C
Solar/Wind Harmer
2.991
274880W4-005 GEN4
Solar/Wind Harmer
2.126
246936BC-WTG1
Solar/Wind Helper
17.073
246937BC-WTG2
Solar/Wind Helper
17.073
960841AF2-375 GEN
Solar/Wind Helper
0.563
965651AG1-433 GEN
Solar/Wind Harmer
8.19
972181SS23-001
Solar/Wind Harmer
0.439
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.299
970289AG2-191 GEN
Solar/Wind Harmer
0.08
274847GR RIDGE ;BU
Solar/Wind Harmer
4.836
946031AF1-268 GEN
Solar/Wind Harmer
0.346
959091AF2-200 GEN
Solar/Wind Harmer
0.804
274849CRESCENT ;1U
Solar/Wind Harmer
1.651
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.704
270227U2-072_GEN3
Solar/Wind Helper
1.995
270228U2-072_GEN4
Solar/Wind Helper
1.995
270231U2-072_GEN5
Solar/Wind Helper
1.995
270349AD2-093_GEN
Solar/Wind Helper
0.454
24639705ELKHART HY
50/50
0.148
963791AG1-232 GEN
Solar/Wind Harmer
0.988
247521TR3_G114
Solar/Wind Harmer
4.555
24695305TIMB G C
Solar/Wind Harmer
3.924
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.418
276694AA1-018 GEN2
Solar/Wind Harmer
4.411
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.096
971343AH1-151 GEN
Solar/Wind Harmer
0.804
970169AG2-114 GEN
Solar/Wind Harmer
0.397
959341AF2-225 GEN
Solar/Wind Harmer
0.575
971087AG2-675 GEN
Solar/Wind Harmer
2.412
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729205KEY G1
50/50
6.727
270201AC2-176 GEN
Solar/Wind Harmer
4.618
970373AG2-245 GEN
Solar/Wind Harmer
0.924
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.493
274872LEEDK;1U
Solar/Wind Harmer
7.643
276872AE1-163_GEN1
Solar/Wind Harmer
5.502
959081AF2-199 GEN
Solar/Wind Harmer
0.402
274851PROVIDENC;RU
Solar/Wind Harmer
2.244
24386205FR-12G C
Solar/Wind Harmer
3.154
24379505HDWTR1G C
Solar/Wind Harmer
5.718
970885AG2-551 GEN
Solar/Wind Harmer
1.46
963741AG1-226 GEN
Solar/Wind Harmer
1.64
276686W4-005 GEN3
Solar/Wind Harmer
2.126
276764AC1-053 GEN2
Solar/Wind Harmer
2.764
276911AD2-131_GEN
Solar/Wind Harmer
0.168
270246TR4_N_V150
Solar/Wind Harmer
1.152
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.556
970291AG2-192 GEN
Solar/Wind Harmer
0.303
274871GR RIDGE ;2U
Solar/Wind Harmer
5.335
943121AE2-341 GEN
Solar/Wind Harmer
0.627
957471AF2-041 GEN
Solar/Wind Harmer
1.206
274848CAMPGROVE;RU
Solar/Wind Harmer
4.509
276785W4-005 GEN1
Solar/Wind Harmer
2.126
276849AB2-070 GEN2
Solar/Wind Harmer
1.825
957201AF2-014 GEN
Solar/Wind Helper
3.942
270284AF1-227 GEN1
Solar/Wind Helper
0.948
270428AC2-015 C
Solar/Wind Helper
0.374
253383AE2-342_GEN
Solar/Wind Helper
0.103
965011AG1-365 GEN
Solar/Wind Harmer
1.139
945111AF1-176 GEN
Solar/Wind Harmer
0.876
945111AF1-176 GEN
Solar/Wind Harmer
4.774
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.668
970073AG2-061 GEN
Solar/Wind Harmer
1.641
274850MENDOTA H;RU
Solar/Wind Harmer
2.401
276863AD2-134 GEN
Solar/Wind Harmer
1.67
276861AD2-134 GEN
Solar/Wind Harmer
1.67
970571AG2-364 GEN
Solar/Wind Harmer
0.796
274856ECOGROVE ;U1
Solar/Wind Harmer
3.104
971681AH1-341 GEN
Solar/Wind Harmer
0.593
938861AE1-114 GEN
Solar/Wind Harmer
9.255
274858EASY ROAD;U2
Solar/Wind Harmer
3.688
270240V3-007_GEN2
Solar/Wind Harmer
4.477
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.353
961051AF2-396 GEN
Solar/Wind Harmer
0.957
961051AF2-396 GEN
Solar/Wind Harmer
7.653
270599AE1-208 GEN
Solar/Wind Harmer
0.377
972231SS25-0005
Solar/Wind Harmer
0.703
971411AH1-196 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
3.454
276876AE1-163_GEN2
Solar/Wind Harmer
5.502
24386405FR-21G C
Solar/Wind Harmer
3.021
276782AC1-033 GEN
Solar/Wind Harmer
3.04
276763AC1-053 GEN1
Solar/Wind Harmer
2.764
971029AG2-637 GEN
Solar/Wind Harmer
0.481
270224U2-072_GEN2
Solar/Wind Helper
1.995
942871AE2-306 GEN
Solar/Wind Helper
0.214
945641AF1-229 GEN
Solar/Wind Helper
0.454
270541AE2-072 C
Solar/Wind Helper
0.459
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.152
944531AF1-118 GEN
Solar/Wind Harmer
2.052
970707AG2-453 GEN
Solar/Wind Harmer
1.192
970833AG2-524 GEN
Solar/Wind Harmer
3.705
958481AF2-142 GEN
Solar/Wind Harmer
0.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.856
274879MINONK ;1U
Solar/Wind Harmer
6.36
971675AH1-338 GEN
Solar/Wind Harmer
0.728
970781AG2-491 GEN
Solar/Wind Harmer
0.403
276903AD2-071 C
Solar/Wind Harmer
0.399
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.811
945391AF1-204 GEN
Solar/Wind Harmer
13.018
270391AF1-285 GEN3
Solar/Wind Helper
0.285
241847AF2-150_GEN
Solar/Wind Helper
0.265
970583AG2-370 GEN
50/50
2.758
965051AG1-369 GEN
Solar/Wind Harmer
0.293
970349AG2-230 GEN
Solar/Wind Harmer
0.721
971347AH1-153 GEN
Solar/Wind Harmer
0.24
961761AG1-017 GEN
Solar/Wind Harmer
0.449
960591AF2-350 GEN
Solar/Wind Harmer
0.428
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
16.272
247536S-71 GEN
Solar/Wind Harmer
3.798
926823AC1-168 GEN
Solar/Wind Harmer
4.874
274857EASY ROAD;U1
Solar/Wind Harmer
3.688
24725505WLD G2 C
Solar/Wind Harmer
3.052
276656WTG2_EQ
Solar/Wind Harmer
0.874
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.587
270462AD2-086
Solar/Wind Helper
1.788
270317AD1-130_GEN
Solar/Wind Helper
1.166
270287AF1-227 GEN3
Solar/Wind Helper
0.35
970031AG2-029 GEN
Solar/Wind Harmer
1.74
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.381
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.278
970833AG2-524 GEN
Solar/Wind Harmer
0.463
962781AG1-127 GEN
Solar/Wind Harmer
0.389
276868AE1-113 GEN
Solar/Wind Harmer
9.54
24697605MDL-3G C
Solar/Wind Harmer
3.143
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.804
24385905FR-11G C
Solar/Wind Harmer
5.939
946321AF1-296 GEN
Solar/Wind Harmer
11.289
274853TWINGROVE;U1
Solar/Wind Harmer
5.82
959611AF2-252 GEN
Solar/Wind Harmer
1.507
960611AF2-352 GEN
Solar/Wind Harmer
1.507
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.365
970193AG2-126 GEN
Solar/Wind Harmer
0.491
958581AF2-149 GEN
Solar/Wind Helper
0.222
270191TR4_S_V150
Solar/Wind Harmer
3.471
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.032
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.18
270180AB1-006 GEN1
Solar/Wind Harmer
5.658
24791305MDL-5G
Solar/Wind Harmer
2.096
276741O09 GEN1
Solar/Wind Harmer
3.218
276726Z2-087_GEN
Solar/Wind Harmer
5.982
944221AF1-090 GEN
Solar/Wind Harmer
10.146
966831AG1-554 GEN
Solar/Wind Helper
0.281
943021AE2-325 GEN
Solar/Wind Harmer
2.95
964611AG1-324 GEN
Solar/Wind Harmer
0.402
276843GEN-1.7
Solar/Wind Harmer
0.568
958011AF2-095 GEN
Solar/Wind Harmer
0.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.447
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.615
24697905MDL-4G C
Solar/Wind Harmer
2.096
970819AG2-516 GEN
Solar/Wind Harmer
0.478
276646AC1-214 GEN2
Solar/Wind Harmer
1.204
274878BISHOP HL;2U
Solar/Wind Harmer
3.016
274854TWINGROVE;U2
Solar/Wind Harmer
5.82
965091AG1-374 GEN
Solar/Wind Harmer
1.13
965931AG1-462 GEN
Solar/Wind Harmer
0.961
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.995
270499AE1-146 GEN
Solar/Wind Helper
0.544
970521AG2-332 GEN
50/50
10.74
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.192
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.016
276848AB2-070 GEN3
Solar/Wind Harmer
1.825
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.166
270471AD2-092_GEN
Solar/Wind Helper
0.454
276820AF1-078_GEN
Solar/Wind Helper
0.159
960851AF2-376 GEN
50/50
2.033
965021AG1-366 GEN
Solar/Wind Harmer
4.557
942221AE2-234 GEN
Solar/Wind Harmer
0.204
958861AF2-177 GEN
Solar/Wind Harmer
15.92
945371AF1-202 GEN
Solar/Wind Harmer
7.521
270505AE1-170 C O1
Solar/Wind Harmer
0.718
270032AE2-172
Solar/Wind Harmer
3.34
970825AG2-519 GEN
Solar/Wind Harmer
1.758
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.231
971997AH1-543 GEN
Solar/Wind Harmer
0.639
276889AE2-281 GEN
Solar/Wind Harmer
1.572
24691005MDL-2G C
Solar/Wind Harmer
3.143
971549AH1-272 GEN
Solar/Wind Harmer
0.722
276158O29GEN2
Solar/Wind Harmer
3.427
276708O09 GEN2
Solar/Wind Harmer
3.218
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.241
270543AE2-219 C
Solar/Wind Harmer
0.365
971993AH1-541 GEN
Solar/Wind Harmer
0.329
276621W2-048 GEN
Solar/Wind Harmer
5.054
942481AE2-261 GEN
Solar/Wind Harmer
1.011
270485AE1-090_GEN
Solar/Wind Helper
0.155
24729405KEY G3
50/50
6.841
24729505KEY G4
50/50
6.727
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.436
970941AG2-585 GEN
Solar/Wind Harmer
0.236
276897AD1-100 C
Solar/Wind Harmer
56.232
971605AH1-302 GEN
Solar/Wind Harmer
6.283
970825AG2-519 GEN
Solar/Wind Harmer
0.274
276805AD2-038 GEN
Solar/Wind Harmer
4.799
970569AG2-363 GEN
Solar/Wind Harmer
1.195
276157O29GEN1
Solar/Wind Harmer
3.427
276645AC1-214 GEN1
Solar/Wind Harmer
1.204
939741AE1-205 GEN
Solar/Wind Harmer
0.767
942111AE2-223 GEN
Solar/Wind Harmer
8.972
970241AG2-163 GEN
Solar/Wind Harmer
0.911
276174W4-005 GEN2
Solar/Wind Harmer
2.126
276668AB2-070 GEN1
Solar/Wind Harmer
1.825
276838X2-022 GEN2
Solar/Wind Harmer
0.188
246938BC-WTG3
Solar/Wind Helper
17.366
247620Y3-023
50/50
0.46
959331AF2-224 GEN
Solar/Wind Harmer
1.139
965041AG1-368 GEN
Solar/Wind Harmer
0.69
270031AE2-169
Solar/Wind Harmer
0.377
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.661
274861TOP CROP ;1U
Solar/Wind Harmer
4.856
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.349
971067AG2-660 GEN
Solar/Wind Harmer
1.608
24699105WLD G1 C
Solar/Wind Harmer
3.052
276655WTG1_EQ
Solar/Wind Harmer
6.603
963841AG1-237 GEN
Solar/Wind Harmer
11.714
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.285
247522W1-056 GEN
Solar/Wind Helper
1.919
270286AF1-227 GEN2
Solar/Wind Helper
0.35
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.296
990792J1392
External Queue
0.3027859032154083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.873
TVALTFEXP_TVA->PJM
CLTF
2.36
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.443
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.032
WECLTFEXP_WEC->PJM
CLTF
2.627
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.255
LGEELTFEXP_LGEE->PJM
CLTF
1.795
LAGNLTFEXP_LAGN->PJM
CLTF
5.817
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.204
NYPJM->LTFIMP_NY
CLTF
1.303
MECLTFEXP_MEC->PJM
CLTF
9.641
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.4 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2056.53
MW Contribution:
0.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.018
270143AC1-141 CT2_
50/50
2.018
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
270100X2-052 CT1
50/50
1.179
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
270102X2-052 ST
50/50
1.276
970901AG2-562 GEN
50/50
4.835
24344005CKG1
50/50
5.553
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
24643105BUCHANAN
50/50
0.01
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
24344105CKG2
50/50
6.328
270101X2-052 CT2
50/50
1.179
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.787
24642205MAYFLWER
50/50
0.618
962601AG1-109 GEN
50/50
2.385
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
960851AF2-376 GEN
50/50
2.087
24307105BERRINSP G
50/50
0.017
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
944961AF1-161 GEN
50/50
2.385
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
990792J1392
External Queue
0.30737584829330444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.41 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2022.06
MW Contribution:
0.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
247620Y3-023
50/50
0.466
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
990792J1392
External Queue
0.30737584829330444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.97 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2014.34
MW Contribution:
0.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.286
24729305KEY G2
50/50
6.704
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.92
957891AF2-083 GEN
Solar/Wind Harmer
0.707
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.667
274888KELLY CRK;1U
Solar/Wind Harmer
5.697
276893AG1-478 C
Solar/Wind Harmer
0.33
270005AE1-210 C O1
Solar/Wind Harmer
6.326
276602WESTBROOK C
Solar/Wind Harmer
1.658
274863CRW1-WTG
Solar/Wind Harmer
4.59
274864CRW2-WTG
Solar/Wind Harmer
4.59
276603SUBLETTE C
Solar/Wind Harmer
0.776
24387305FR-4G C
Solar/Wind Harmer
4.404
24386605FR-22G C
Solar/Wind Harmer
2.936
24387005FR-3G C
Solar/Wind Harmer
2.906
274880W4-005 GEN4
Solar/Wind Harmer
2.063
246936BC-WTG1
Solar/Wind Helper
17.184
246937BC-WTG2
Solar/Wind Helper
17.184
960841AF2-375 GEN
Solar/Wind Helper
0.576
965651AG1-433 GEN
Solar/Wind Harmer
8.016
972181SS23-001
Solar/Wind Harmer
0.428
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.266
970289AG2-191 GEN
Solar/Wind Harmer
0.078
274847GR RIDGE ;BU
Solar/Wind Harmer
4.711
946031AF1-268 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
0.782
274849CRESCENT ;1U
Solar/Wind Harmer
1.605
957381AF2-032 GEN
Solar/Wind Harmer
0.066
276916AD2-100_GEN
Solar/Wind Harmer
0.681
270227U2-072_GEN3
Solar/Wind Helper
2.097
270228U2-072_GEN4
Solar/Wind Helper
2.097
270231U2-072_GEN5
Solar/Wind Helper
2.097
270349AD2-093_GEN
Solar/Wind Helper
0.517
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.971
247521TR3_G114
Solar/Wind Harmer
4.44
24695305TIMB G C
Solar/Wind Harmer
3.811
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.053
943591AF1-030 GEN
Solar/Wind Harmer
0.407
276694AA1-018 GEN2
Solar/Wind Harmer
4.296
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.038
971343AH1-151 GEN
Solar/Wind Harmer
0.782
970169AG2-114 GEN
Solar/Wind Harmer
0.386
959341AF2-225 GEN
Solar/Wind Harmer
0.559
971087AG2-675 GEN
Solar/Wind Harmer
2.343
270445AC2-157 GEN2
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
1.123
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.295
274871GR RIDGE ;2U
Solar/Wind Harmer
5.196
943121AE2-341 GEN
Solar/Wind Harmer
0.611
957471AF2-041 GEN
Solar/Wind Harmer
1.174
274848CAMPGROVE;RU
Solar/Wind Harmer
4.383
276785W4-005 GEN1
Solar/Wind Harmer
2.063
276849AB2-070 GEN2
Solar/Wind Harmer
1.771
957201AF2-014 GEN
Solar/Wind Helper
3.968
270284AF1-227 GEN1
Solar/Wind Helper
1.035
270428AC2-015 C
Solar/Wind Helper
0.376
253383AE2-342_GEN
Solar/Wind Helper
0.105
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.856
945111AF1-176 GEN
Solar/Wind Harmer
4.667
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.651
970073AG2-061 GEN
Solar/Wind Harmer
1.597
274850MENDOTA H;RU
Solar/Wind Harmer
2.337
276863AD2-134 GEN
Solar/Wind Harmer
1.625
276861AD2-134 GEN
Solar/Wind Harmer
1.625
970571AG2-364 GEN
Solar/Wind Harmer
0.775
274856ECOGROVE ;U1
Solar/Wind Harmer
3.02
971681AH1-341 GEN
Solar/Wind Harmer
0.577
938861AE1-114 GEN
Solar/Wind Harmer
9.003
274858EASY ROAD;U2
Solar/Wind Harmer
3.587
270240V3-007_GEN2
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.369
961051AF2-396 GEN
Solar/Wind Harmer
0.935
961051AF2-396 GEN
Solar/Wind Harmer
7.477
270599AE1-208 GEN
Solar/Wind Harmer
0.368
972231SS25-0005
Solar/Wind Harmer
0.685
971411AH1-196 GEN
Solar/Wind Harmer
0.591
274855GSG-6 ;RU
Solar/Wind Harmer
3.361
276876AE1-163_GEN2
Solar/Wind Harmer
5.354
24386405FR-21G C
Solar/Wind Harmer
2.936
276782AC1-033 GEN
Solar/Wind Harmer
2.956
276763AC1-053 GEN1
Solar/Wind Harmer
2.681
971029AG2-637 GEN
Solar/Wind Harmer
0.465
270224U2-072_GEN2
Solar/Wind Helper
2.097
942871AE2-306 GEN
Solar/Wind Helper
0.225
945641AF1-229 GEN
Solar/Wind Helper
0.46
270541AE2-072 C
Solar/Wind Helper
0.478
944531AF1-118 GEN
Solar/Wind Harmer
2.012
270247TR4_N_V136
Solar/Wind Harmer
1.123
970707AG2-453 GEN
Solar/Wind Harmer
1.161
970833AG2-524 GEN
Solar/Wind Harmer
3.609
958481AF2-142 GEN
Solar/Wind Harmer
0.607
274862TOP CROP ;2U
Solar/Wind Harmer
4.729
274879MINONK ;1U
Solar/Wind Harmer
6.19
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
276903AD2-071 C
Solar/Wind Harmer
0.388
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.786
945391AF1-204 GEN
Solar/Wind Harmer
12.593
270391AF1-285 GEN3
Solar/Wind Helper
0.3
241847AF2-150_GEN
Solar/Wind Helper
0.265
970583AG2-370 GEN
50/50
2.702
965051AG1-369 GEN
Solar/Wind Harmer
0.285
970349AG2-230 GEN
Solar/Wind Harmer
0.704
971347AH1-153 GEN
Solar/Wind Harmer
0.235
961761AG1-017 GEN
Solar/Wind Harmer
0.438
960591AF2-350 GEN
Solar/Wind Harmer
0.417
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
15.839
247536S-71 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
4.742
274857EASY ROAD;U1
Solar/Wind Harmer
3.587
24725505WLD G2 C
Solar/Wind Harmer
2.968
276656WTG2_EQ
Solar/Wind Harmer
0.85
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.539
270462AD2-086
Solar/Wind Helper
1.865
270317AD1-130_GEN
Solar/Wind Helper
1.216
270287AF1-227 GEN3
Solar/Wind Helper
0.382
24729205KEY G1
50/50
6.593
270201AC2-176 GEN
Solar/Wind Harmer
4.506
970373AG2-245 GEN
Solar/Wind Harmer
0.901
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.326
274872LEEDK;1U
Solar/Wind Harmer
7.44
276872AE1-163_GEN1
Solar/Wind Harmer
5.354
959081AF2-199 GEN
Solar/Wind Harmer
0.391
274851PROVIDENC;RU
Solar/Wind Harmer
2.181
24386205FR-12G C
Solar/Wind Harmer
3.065
24379505HDWTR1G C
Solar/Wind Harmer
5.555
970885AG2-551 GEN
Solar/Wind Harmer
1.417
963741AG1-226 GEN
Solar/Wind Harmer
1.592
276686W4-005 GEN3
Solar/Wind Harmer
2.063
276764AC1-053 GEN2
Solar/Wind Harmer
2.681
276911AD2-131_GEN
Solar/Wind Harmer
0.162
970031AG2-029 GEN
Solar/Wind Harmer
1.71
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.032
945581AF1-223 GEN
Solar/Wind Harmer
0
270191TR4_S_V150
Solar/Wind Harmer
3.383
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.91
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.095
270180AB1-006 GEN1
Solar/Wind Harmer
5.504
24791305MDL-5G
Solar/Wind Harmer
2.038
276741O09 GEN1
Solar/Wind Harmer
3.129
276726Z2-087_GEN
Solar/Wind Harmer
5.813
944221AF1-090 GEN
Solar/Wind Harmer
9.816
966831AG1-554 GEN
Solar/Wind Helper
0.286
943021AE2-325 GEN
Solar/Wind Harmer
2.881
964611AG1-324 GEN
Solar/Wind Harmer
0.393
276843GEN-1.7
Solar/Wind Harmer
0.553
958011AF2-095 GEN
Solar/Wind Harmer
0.601
276691AA1-018 GEN1
Solar/Wind Harmer
0.435
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
24697905MDL-4G C
Solar/Wind Harmer
2.038
970819AG2-516 GEN
Solar/Wind Harmer
0.465
276646AC1-214 GEN2
Solar/Wind Harmer
1.17
274878BISHOP HL;2U
Solar/Wind Harmer
2.932
965931AG1-462 GEN
Solar/Wind Harmer
0.934
274854TWINGROVE;U2
Solar/Wind Harmer
5.654
965091AG1-374 GEN
Solar/Wind Harmer
1.098
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
2.097
270499AE1-146 GEN
Solar/Wind Helper
0.556
274887GEN-1.85
Solar/Wind Harmer
5.144
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
276868AE1-113 GEN
Solar/Wind Harmer
9.286
24697605MDL-3G C
Solar/Wind Harmer
3.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.782
24385905FR-11G C
Solar/Wind Harmer
5.772
946321AF1-296 GEN
Solar/Wind Harmer
10.97
274853TWINGROVE;U1
Solar/Wind Harmer
5.654
959611AF2-252 GEN
Solar/Wind Harmer
1.464
960611AF2-352 GEN
Solar/Wind Harmer
1.464
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.354
970193AG2-126 GEN
Solar/Wind Harmer
0.475
958581AF2-149 GEN
Solar/Wind Helper
0.216
965021AG1-366 GEN
Solar/Wind Harmer
4.503
942221AE2-234 GEN
Solar/Wind Harmer
0.2
958861AF2-177 GEN
Solar/Wind Harmer
15.573
945371AF1-202 GEN
Solar/Wind Harmer
7.349
270505AE1-170 C O1
Solar/Wind Harmer
0.702
270032AE2-172
Solar/Wind Harmer
3.253
970825AG2-519 GEN
Solar/Wind Harmer
1.712
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.198
971997AH1-543 GEN
Solar/Wind Harmer
0.622
276889AE2-281 GEN
Solar/Wind Harmer
1.53
24691005MDL-2G C
Solar/Wind Harmer
3.058
971549AH1-272 GEN
Solar/Wind Harmer
0.702
276158O29GEN2
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
3.129
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.205
270543AE2-219 C
Solar/Wind Harmer
0.354
971993AH1-541 GEN
Solar/Wind Harmer
0.319
276621W2-048 GEN
Solar/Wind Harmer
4.9
942481AE2-261 GEN
Solar/Wind Harmer
0.979
270485AE1-090_GEN
Solar/Wind Helper
0.162
24729405KEY G3
50/50
6.704
24729505KEY G4
50/50
6.593
270043AE2-236 GEN
Solar/Wind Harmer
0.363
971771AH1-392 GEN
Solar/Wind Harmer
0.426
970941AG2-585 GEN
Solar/Wind Harmer
0.23
276897AD1-100 C
Solar/Wind Harmer
54.783
971605AH1-302 GEN
Solar/Wind Harmer
6.118
970825AG2-519 GEN
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
4.671
970569AG2-363 GEN
Solar/Wind Harmer
1.162
276157O29GEN1
Solar/Wind Harmer
3.332
276645AC1-214 GEN1
Solar/Wind Harmer
1.17
939741AE1-205 GEN
Solar/Wind Harmer
0.745
942111AE2-223 GEN
Solar/Wind Harmer
8.72
970241AG2-163 GEN
Solar/Wind Harmer
0.884
276174W4-005 GEN2
Solar/Wind Harmer
2.063
276668AB2-070 GEN1
Solar/Wind Harmer
1.771
276838X2-022 GEN2
Solar/Wind Harmer
0.183
246938BC-WTG3
Solar/Wind Helper
17.48
247620Y3-023
50/50
0.45
959331AF2-224 GEN
Solar/Wind Harmer
1.126
965041AG1-368 GEN
Solar/Wind Harmer
0.675
270031AE2-169
Solar/Wind Harmer
0.368
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.489
274861TOP CROP ;1U
Solar/Wind Harmer
4.729
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.176
971067AG2-660 GEN
Solar/Wind Harmer
1.565
24699105WLD G1 C
Solar/Wind Harmer
2.968
276655WTG1_EQ
Solar/Wind Harmer
6.417
963841AG1-237 GEN
Solar/Wind Harmer
11.375
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.3
270286AF1-227 GEN2
Solar/Wind Helper
0.382
247522W1-056 GEN
Solar/Wind Helper
1.958
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.299
970521AG2-332 GEN
50/50
10.514
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
12.855
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.782
274877BISHOP HL;1U
Solar/Wind Harmer
2.932
276848AB2-070 GEN3
Solar/Wind Harmer
1.771
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.216
270471AD2-092_GEN
Solar/Wind Helper
0.517
276820AF1-078_GEN
Solar/Wind Helper
0.166
990792J1392
External Queue
0.3014104962348938
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.406
WECLTFEXP_WEC->PJM
CLTF
2.556
LAGNLTFEXP_LAGN->PJM
CLTF
5.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.955
LGEELTFEXP_LGEE->PJM
CLTF
1.68
MECLTFEXP_MEC->PJM
CLTF
9.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.67
NYPJM->LTFIMP_NY
CLTF
1.235
TVALTFEXP_TVA->PJM
CLTF
2.193
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.304
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
SIGELTFEXP_SIGE->PJM
CLTF
0.19

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.19 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5615.13
MW Contribution:
0.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24653605MOTTVILLE
50/50
0.008
957891AF2-083 GEN
Solar/Wind Harmer
1.911
270071AF1-092 GEN
Solar/Wind Harmer
1.896
274888KELLY CRK;1U
Solar/Wind Harmer
16.946
276893AG1-478 C
Solar/Wind Harmer
0.983
274863CRW1-WTG
Solar/Wind Harmer
13.812
274864CRW2-WTG
Solar/Wind Harmer
13.812
276602WESTBROOK C
Solar/Wind Harmer
4.959
24387305FR-4G C
Solar/Wind Harmer
13.414
24386605FR-22G C
Solar/Wind Harmer
8.942
24387005FR-3G C
Solar/Wind Harmer
8.853
276603SUBLETTE C
Solar/Wind Harmer
2.319
274880W4-005 GEN4
Solar/Wind Harmer
6.269
270005AE1-210 C O1
Solar/Wind Harmer
13.761
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.279
246936BC-WTG1
Solar/Wind Harmer
6.236
246937BC-WTG2
Solar/Wind Harmer
6.236
270459AD2-067 GEN
Solar/Wind Helper
0.77
972207SS24-0001
Solar/Wind Harmer
3.817
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
1.254
274847GR RIDGE ;BU
Solar/Wind Harmer
14.105
959091AF2-200 GEN
Solar/Wind Harmer
2.34
274849CRESCENT ;1U
Solar/Wind Harmer
4.808
965651AG1-433 GEN
Solar/Wind Harmer
16.648
970289AG2-191 GEN
Solar/Wind Harmer
0.192
957381AF2-032 GEN
Solar/Wind Harmer
0.2
276916AD2-100_GEN
Solar/Wind Harmer
2.081
946031AF1-268 GEN
Solar/Wind Harmer
0.712
270142AC1-141 CT1_
50/50
5.318
270143AC1-141 CT2_
50/50
5.318
24639705ELKHART HY
50/50
0.355
965681AG1-436 GEN
Solar/Wind Harmer
1.626
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.221
276694AA1-018 GEN2
Solar/Wind Harmer
12.798
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
6.168
971343AH1-151 GEN
Solar/Wind Harmer
2.34
970169AG2-114 GEN
Solar/Wind Harmer
1.163
959341AF2-225 GEN
Solar/Wind Harmer
1.689
971087AG2-675 GEN
Solar/Wind Harmer
6.993
970291AG2-192 GEN
Solar/Wind Harmer
0.131
963791AG1-232 GEN
Solar/Wind Harmer
1.357
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
6.782
24695305TIMB G C
Solar/Wind Harmer
6.541
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
15.559
943121AE2-341 GEN
Solar/Wind Harmer
1.831
957471AF2-041 GEN
Solar/Wind Harmer
3.51
274848CAMPGROVE;RU
Solar/Wind Harmer
13.133
276785W4-005 GEN1
Solar/Wind Harmer
6.269
276849AB2-070 GEN2
Solar/Wind Harmer
5.38
970289AG2-191 GEN
Solar/Wind Harmer
1.334
970291AG2-192 GEN
Solar/Wind Harmer
0.728
270246TR4_N_V150
Solar/Wind Harmer
1.716
957201AF2-014 GEN
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
3.322
274770LINCOLN ;1U
50/50
19.594
274771LINCOLN ;2U
50/50
19.594
945111AF1-176 GEN
Solar/Wind Harmer
2.262
945111AF1-176 GEN
Solar/Wind Harmer
12.331
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.763
274850MENDOTA H;RU
Solar/Wind Harmer
6.991
276863AD2-134 GEN
Solar/Wind Harmer
4.863
270102X2-052 ST
50/50
3.595
970901AG2-562 GEN
50/50
13.622
24344005CKG1
50/50
15.603
274777LINCOLN ;8U
50/50
19.594
961051AF2-396 GEN
Solar/Wind Harmer
2.529
961051AF2-396 GEN
Solar/Wind Harmer
20.232
972231SS25-0005
Solar/Wind Harmer
2.007
971411AH1-196 GEN
Solar/Wind Harmer
1.767
274855GSG-6 ;RU
Solar/Wind Harmer
10.056
24641605TWIN BRNCH
50/50
0.038
970707AG2-453 GEN
Solar/Wind Harmer
3.491
970833AG2-524 GEN
Solar/Wind Harmer
10.802
958481AF2-142 GEN
Solar/Wind Harmer
1.807
274862TOP CROP ;2U
Solar/Wind Harmer
14.086
274775LINCOLN ;6U
50/50
19.594
970349AG2-230 GEN
Solar/Wind Harmer
2.066
971347AH1-153 GEN
Solar/Wind Harmer
0.689
960591AF2-350 GEN
Solar/Wind Harmer
1.241
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
47.612
926823AC1-168 GEN
Solar/Wind Harmer
14.207
274857EASY ROAD;U1
Solar/Wind Harmer
10.718
276656WTG2_EQ
Solar/Wind Harmer
2.567
276615X2-022 GEN
Solar/Wind Harmer
4.681
24725505WLD G2 C
Solar/Wind Harmer
7.118
965051AG1-369 GEN
Solar/Wind Harmer
0.436
961761AG1-017 GEN
Solar/Wind Harmer
0.84
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.286
958091AF2-103 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
1.186
274879MINONK ;1U
Solar/Wind Harmer
18.49
971675AH1-338 GEN
Solar/Wind Harmer
2.12
944531AF1-118 GEN
Solar/Wind Harmer
4.1
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.397
945391AF1-204 GEN
Solar/Wind Harmer
38.775
276903AD2-071 C
Solar/Wind Harmer
0.942
270247TR4_N_V136
Solar/Wind Harmer
1.716
274776LINCOLN ;7U
50/50
19.594
970373AG2-245 GEN
Solar/Wind Harmer
2.66
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
22.268
276872AE1-163_GEN1
Solar/Wind Harmer
15.988
959081AF2-199 GEN
Solar/Wind Harmer
1.17
24386205FR-12G C
Solar/Wind Harmer
9.336
274851PROVIDENC;RU
Solar/Wind Harmer
6.535
963741AG1-226 GEN
Solar/Wind Harmer
4.866
276686W4-005 GEN3
Solar/Wind Harmer
6.269
276764AC1-053 GEN2
Solar/Wind Harmer
8.149
276911AD2-131_GEN
Solar/Wind Harmer
0.495
270004AE1-209 GEN
Solar/Wind Harmer
13.761
270201AC2-176 GEN
Solar/Wind Harmer
8.644
24379505HDWTR1G C
Solar/Wind Harmer
12.238
970885AG2-551 GEN
Solar/Wind Harmer
2.885
965421AG1-410 GEN
Solar/Wind Harmer
2.186
270349AD2-093_GEN
Solar/Wind Helper
0.732
276876AE1-163_GEN2
Solar/Wind Harmer
15.988
24386405FR-21G C
Solar/Wind Harmer
8.942
276782AC1-033 GEN
Solar/Wind Harmer
8.851
276763AC1-053 GEN1
Solar/Wind Harmer
8.149
270599AE1-208 GEN
Solar/Wind Harmer
0.772
971029AG2-637 GEN
Solar/Wind Harmer
0.988
270054AF2-122 C O1
Solar/Wind Helper
0.559
24344105CKG2
50/50
19.094
270101X2-052 CT2
50/50
3.322
965791AG1-447 GEN
Solar/Wind Harmer
14.312
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
16.653
24791305MDL-5G
Solar/Wind Harmer
6.168
276882AE2-255 GEN
Solar/Wind Harmer
9.245
276741O09 GEN1
Solar/Wind Harmer
9.356
276726Z2-087_GEN
Solar/Wind Harmer
17.562
944541AF1-119 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
30.092
270191TR4_S_V150
Solar/Wind Harmer
5.168
943021AE2-325 GEN
Solar/Wind Harmer
7.909
276843GEN-1.7
Solar/Wind Harmer
1.646
958011AF2-095 GEN
Solar/Wind Harmer
1.788
945421AF1-207 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.297
958491AF2-143 GEN
Solar/Wind Harmer
1.786
24697905MDL-4G C
Solar/Wind Harmer
6.168
970819AG2-516 GEN
Solar/Wind Harmer
1.391
276646AC1-214 GEN2
Solar/Wind Harmer
3.506
274878BISHOP HL;2U
Solar/Wind Harmer
8.781
274854TWINGROVE;U2
Solar/Wind Harmer
17.103
965091AG1-374 GEN
Solar/Wind Harmer
3.322
965931AG1-462 GEN
Solar/Wind Harmer
2.786
964611AG1-324 GEN
Solar/Wind Harmer
0.768
270491AE1-102 GEN2
Solar/Wind Harmer
0.09
270356AE2-297 GEN
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
4.863
970571AG2-364 GEN
Solar/Wind Harmer
2.316
274856ECOGROVE ;U1
Solar/Wind Harmer
9.025
971681AH1-341 GEN
Solar/Wind Harmer
1.725
938861AE1-114 GEN
Solar/Wind Harmer
26.903
274858EASY ROAD;U2
Solar/Wind Harmer
10.718
965011AG1-365 GEN
Solar/Wind Harmer
1.101
270594AE1-207 GEN
Solar/Wind Harmer
1.561
270240V3-007_GEN2
Solar/Wind Harmer
9.582
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.09
24643105BUCHANAN
50/50
0.028
274887GEN-1.85
Solar/Wind Harmer
15.299
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.35
970031AG2-029 GEN
Solar/Wind Harmer
3.022
962781AG1-127 GEN
Solar/Wind Harmer
1.134
24697605MDL-3G C
Solar/Wind Harmer
9.252
270181AB1-006 GEN2
Solar/Wind Harmer
1.85
276868AE1-113 GEN
Solar/Wind Harmer
27.735
971171AH1-044 GEN
Solar/Wind Harmer
2.34
24385905FR-11G C
Solar/Wind Harmer
17.58
274853TWINGROVE;U1
Solar/Wind Harmer
17.103
959611AF2-252 GEN
Solar/Wind Harmer
4.43
960611AF2-352 GEN
Solar/Wind Harmer
4.43
946321AF1-296 GEN
Solar/Wind Harmer
32.747
960971AF2-388 GEN
Solar/Wind Harmer
33.297
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.462
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.721
274773LINCOLN ;4U
50/50
19.594
24307105BERRINSP G
50/50
0.047
270505AE1-170 C O1
Solar/Wind Harmer
1.915
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.586
24691005MDL-2G C
Solar/Wind Harmer
9.252
971997AH1-543 GEN
Solar/Wind Harmer
1.864
276889AE2-281 GEN
Solar/Wind Harmer
4.568
971549AH1-272 GEN
Solar/Wind Harmer
2.119
276158O29GEN2
Solar/Wind Harmer
9.962
276708O09 GEN2
Solar/Wind Harmer
9.356
965021AG1-366 GEN
Solar/Wind Harmer
4.406
971993AH1-541 GEN
Solar/Wind Harmer
0.971
958861AF2-177 GEN
Solar/Wind Harmer
32.514
276621W2-048 GEN
Solar/Wind Harmer
14.904
942221AE2-234 GEN
Solar/Wind Harmer
0.357
942481AE2-261 GEN
Solar/Wind Harmer
2.986
945371AF1-202 GEN
Solar/Wind Harmer
15.509
270032AE2-172
Solar/Wind Harmer
7.806
970825AG2-519 GEN
Solar/Wind Harmer
3.715
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.656
270543AE2-219 C
Solar/Wind Harmer
0.721
247607V1-011 GEN
Solar/Wind Harmer
5.418
270435AC2-044 GEN
Solar/Wind Harmer
0.138
274772LINCOLN ;3U
50/50
19.594
274774LINCOLN ;5U
50/50
19.594
944961AF1-161 GEN
50/50
6.313
971771AH1-392 GEN
Solar/Wind Harmer
1.164
270043AE2-236 GEN
Solar/Wind Harmer
0.701
970941AG2-585 GEN
Solar/Wind Harmer
0.683
276897AD1-100 C
Solar/Wind Harmer
163.988
971605AH1-302 GEN
Solar/Wind Harmer
18.338
276805AD2-038 GEN
Solar/Wind Harmer
13.931
970569AG2-363 GEN
Solar/Wind Harmer
3.474
276645AC1-214 GEN1
Solar/Wind Harmer
3.506
276157O29GEN1
Solar/Wind Harmer
9.962
939741AE1-205 GEN
Solar/Wind Harmer
2.252
942111AE2-223 GEN
Solar/Wind Harmer
26.343
970241AG2-163 GEN
Solar/Wind Harmer
2.703
276174W4-005 GEN2
Solar/Wind Harmer
6.269
276668AB2-070 GEN1
Solar/Wind Harmer
5.38
276838X2-022 GEN2
Solar/Wind Harmer
0.556
970825AG2-519 GEN
Solar/Wind Harmer
0.58
270007AE1-245 C
Solar/Wind Harmer
7.597
246938BC-WTG3
Solar/Wind Harmer
6.344
270144AC1-141 ST1_
50/50
4.707
24642205MAYFLWER
50/50
1.638
962601AG1-109 GEN
50/50
6.313
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.337
274861TOP CROP ;1U
Solar/Wind Harmer
14.086
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
18.688
971067AG2-660 GEN
Solar/Wind Harmer
4.679
276655WTG1_EQ
Solar/Wind Harmer
19.386
963841AG1-237 GEN
Solar/Wind Harmer
34.712
959331AF2-224 GEN
Solar/Wind Harmer
1.101
965041AG1-368 GEN
Solar/Wind Harmer
0.951
270031AE2-169
Solar/Wind Harmer
0.772
24699105WLD G1 C
Solar/Wind Harmer
7.118
270383AD1-128 GEN
Solar/Wind Harmer
0
970521AG2-332 GEN
50/50
25.194
276806AD2-047 C O1
Solar/Wind Harmer
38.236
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.34
274877BISHOP HL;1U
Solar/Wind Harmer
8.781
276848AB2-070 GEN3
Solar/Wind Harmer
5.38
270444AC2-157 GEN1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.732
NYPJM->LTFIMP_NY
CLTF
3.691
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.533
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.712
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.521
LAGNLTFEXP_LAGN->PJM
CLTF
14.07
AH1-155LTFEXP_AH1-155->PJM
LTF
0.713
CBM West 2LTFEXP_CBM-W2->PJM
CBM
137.069
WECLTFEXP_WEC->PJM
CLTF
7.629
MECLTFEXP_MEC->PJM
CLTF
27.64
AG2-052LTFEXP_AG2-052->PJM
LTF
0.475
CBM West 1LTFEXP_CBM-W1->PJM
CBM
234.012
LGEELTFEXP_LGEE->PJM
CLTF
3.98
TVALTFEXP_TVA->PJM
CLTF
5.131
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
50.708

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.69 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5144.06
MW Contribution:
0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24641605TWIN BRNCH
50/50
0.035
970707AG2-453 GEN
Solar/Wind Harmer
3.232
944531AF1-118 GEN
Solar/Wind Harmer
3.989
970833AG2-524 GEN
Solar/Wind Harmer
9.992
958481AF2-142 GEN
Solar/Wind Harmer
1.671
274862TOP CROP ;2U
Solar/Wind Harmer
13.024
274879MINONK ;1U
Solar/Wind Harmer
17.091
971675AH1-338 GEN
Solar/Wind Harmer
1.962
970781AG2-491 GEN
Solar/Wind Harmer
1.059
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.19
276903AD2-071 C
Solar/Wind Harmer
0.899
945391AF1-204 GEN
Solar/Wind Harmer
34.921
270247TR4_N_V136
Solar/Wind Harmer
1.644
274776LINCOLN ;7U
50/50
18.14
970373AG2-245 GEN
Solar/Wind Harmer
2.43
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
20.606
959081AF2-199 GEN
Solar/Wind Harmer
1.082
276872AE1-163_GEN1
Solar/Wind Harmer
14.773
274851PROVIDENC;RU
Solar/Wind Harmer
6.034
24386205FR-12G C
Solar/Wind Harmer
8.33
963741AG1-226 GEN
Solar/Wind Harmer
4.356
276686W4-005 GEN3
Solar/Wind Harmer
5.74
276764AC1-053 GEN2
Solar/Wind Harmer
7.46
276911AD2-131_GEN
Solar/Wind Harmer
0.453
270004AE1-209 GEN
Solar/Wind Harmer
13.697
270201AC2-176 GEN
Solar/Wind Harmer
8.545
24379505HDWTR1G C
Solar/Wind Harmer
12.438
970885AG2-551 GEN
Solar/Wind Harmer
2.911
972207SS24-0001
Solar/Wind Harmer
3.534
972181SS23-001
Solar/Wind Harmer
1.16
270055AF2-134 C O1
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
13.046
959091AF2-200 GEN
Solar/Wind Harmer
2.165
274849CRESCENT ;1U
Solar/Wind Harmer
4.44
965651AG1-433 GEN
Solar/Wind Harmer
16.307
970289AG2-191 GEN
Solar/Wind Harmer
0.181
957381AF2-032 GEN
Solar/Wind Harmer
0.183
276916AD2-100_GEN
Solar/Wind Harmer
1.901
946031AF1-268 GEN
Solar/Wind Harmer
0.706
965421AG1-410 GEN
Solar/Wind Harmer
2.09
270349AD2-093_GEN
Solar/Wind Helper
0.722
270102X2-052 ST
50/50
3.326
970901AG2-562 GEN
50/50
12.603
24344005CKG1
50/50
14.512
274777LINCOLN ;8U
50/50
18.14
961051AF2-396 GEN
Solar/Wind Harmer
2.356
961051AF2-396 GEN
Solar/Wind Harmer
18.844
972231SS25-0005
Solar/Wind Harmer
1.856
971411AH1-196 GEN
Solar/Wind Harmer
1.635
274855GSG-6 ;RU
Solar/Wind Harmer
9.305
276876AE1-163_GEN2
Solar/Wind Harmer
14.773
276782AC1-033 GEN
Solar/Wind Harmer
8.174
24386405FR-21G C
Solar/Wind Harmer
7.979
276763AC1-053 GEN1
Solar/Wind Harmer
7.46
270599AE1-208 GEN
Solar/Wind Harmer
0.756
971029AG2-637 GEN
Solar/Wind Harmer
1.009
943021AE2-325 GEN
Solar/Wind Harmer
7.365
276843GEN-1.7
Solar/Wind Harmer
1.523
958011AF2-095 GEN
Solar/Wind Harmer
1.654
276691AA1-018 GEN1
Solar/Wind Harmer
1.199
958491AF2-143 GEN
Solar/Wind Harmer
1.651
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.287
24697905MDL-4G C
Solar/Wind Harmer
5.509
276646AC1-214 GEN2
Solar/Wind Harmer
3.237
274878BISHOP HL;2U
Solar/Wind Harmer
8.109
274854TWINGROVE;U2
Solar/Wind Harmer
15.712
965091AG1-374 GEN
Solar/Wind Harmer
3.052
965931AG1-462 GEN
Solar/Wind Harmer
2.578
964611AG1-324 GEN
Solar/Wind Harmer
0.76
274775LINCOLN ;6U
50/50
18.14
970349AG2-230 GEN
Solar/Wind Harmer
1.922
971347AH1-153 GEN
Solar/Wind Harmer
0.641
960591AF2-350 GEN
Solar/Wind Harmer
1.148
939351AE1-166 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
43.942
926823AC1-168 GEN
Solar/Wind Harmer
13.12
274857EASY ROAD;U1
Solar/Wind Harmer
9.917
276656WTG2_EQ
Solar/Wind Harmer
2.36
276615X2-022 GEN
Solar/Wind Harmer
4.283
24725505WLD G2 C
Solar/Wind Harmer
6.849
961761AG1-017 GEN
Solar/Wind Harmer
0.831
965051AG1-369 GEN
Solar/Wind Harmer
0.417
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.279
958091AF2-103 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
50/50
18.14
24307105BERRINSP G
50/50
0.043
270505AE1-170 C O1
Solar/Wind Harmer
1.783
962691AG1-118 GEN
Solar/Wind Harmer
3.318
971997AH1-543 GEN
Solar/Wind Harmer
1.723
276889AE2-281 GEN
Solar/Wind Harmer
4.221
957841AF2-078 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
1.975
24691005MDL-2G C
Solar/Wind Harmer
8.264
965021AG1-366 GEN
Solar/Wind Harmer
4.211
276158O29GEN2
Solar/Wind Harmer
9.213
276708O09 GEN2
Solar/Wind Harmer
8.652
958861AF2-177 GEN
Solar/Wind Harmer
31.906
942221AE2-234 GEN
Solar/Wind Harmer
0.346
945371AF1-202 GEN
Solar/Wind Harmer
15.277
971993AH1-541 GEN
Solar/Wind Harmer
0.889
276621W2-048 GEN
Solar/Wind Harmer
13.64
270032AE2-172
Solar/Wind Harmer
7.423
942481AE2-261 GEN
Solar/Wind Harmer
2.729
970825AG2-519 GEN
Solar/Wind Harmer
3.672
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.699
270543AE2-219 C
Solar/Wind Harmer
0.728
247607V1-011 GEN
Solar/Wind Harmer
5.196
270435AC2-044 GEN
Solar/Wind Harmer
0.132
24653605MOTTVILLE
50/50
0.008
270071AF1-092 GEN
Solar/Wind Harmer
1.786
957891AF2-083 GEN
Solar/Wind Harmer
1.78
274888KELLY CRK;1U
Solar/Wind Harmer
15.676
276893AG1-478 C
Solar/Wind Harmer
0.909
276602WESTBROOK C
Solar/Wind Harmer
4.589
274863CRW1-WTG
Solar/Wind Harmer
12.737
274864CRW2-WTG
Solar/Wind Harmer
12.737
276603SUBLETTE C
Solar/Wind Harmer
2.146
24387305FR-4G C
Solar/Wind Harmer
11.969
24386605FR-22G C
Solar/Wind Harmer
7.979
24387005FR-3G C
Solar/Wind Harmer
7.9
274880W4-005 GEN4
Solar/Wind Harmer
5.74
270005AE1-210 C O1
Solar/Wind Harmer
13.697
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.264
246936BC-WTG1
Solar/Wind Harmer
5.962
246937BC-WTG2
Solar/Wind Harmer
5.962
270100X2-052 CT1
50/50
3.074
274770LINCOLN ;1U
50/50
18.14
274771LINCOLN ;2U
50/50
18.14
945111AF1-176 GEN
Solar/Wind Harmer
2.108
945111AF1-176 GEN
Solar/Wind Harmer
11.49
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.402
940581AE2-045 GEN
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
6.469
276863AD2-134 GEN
Solar/Wind Harmer
4.499
276861AD2-134 GEN
Solar/Wind Harmer
4.499
274856ECOGROVE ;U1
Solar/Wind Harmer
8.351
970571AG2-364 GEN
Solar/Wind Harmer
2.139
971681AH1-341 GEN
Solar/Wind Harmer
1.596
938861AE1-114 GEN
Solar/Wind Harmer
24.893
274858EASY ROAD;U2
Solar/Wind Harmer
9.917
965011AG1-365 GEN
Solar/Wind Harmer
1.053
270594AE1-207 GEN
Solar/Wind Harmer
1.485
270240V3-007_GEN2
Solar/Wind Harmer
9.739
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.086
24344105CKG2
50/50
17.764
270101X2-052 CT2
50/50
3.074
965791AG1-447 GEN
Solar/Wind Harmer
13.238
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
8.546
270180AB1-006 GEN1
Solar/Wind Harmer
14.875
24791305MDL-5G
Solar/Wind Harmer
5.509
276741O09 GEN1
Solar/Wind Harmer
8.652
944541AF1-119 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
16.147
944221AF1-090 GEN
Solar/Wind Harmer
27.427
270191TR4_S_V150
Solar/Wind Harmer
4.951
270356AE2-297 GEN
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.086
24643105BUCHANAN
50/50
0.026
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
14.152
970031AG2-029 GEN
Solar/Wind Harmer
2.845
970833AG2-524 GEN
Solar/Wind Harmer
1.249
962781AG1-127 GEN
Solar/Wind Harmer
1.049
276868AE1-113 GEN
Solar/Wind Harmer
25.637
971171AH1-044 GEN
Solar/Wind Harmer
2.165
24697605MDL-3G C
Solar/Wind Harmer
8.264
270181AB1-006 GEN2
Solar/Wind Harmer
1.653
960971AF2-388 GEN
Solar/Wind Harmer
32.614
24385905FR-11G C
Solar/Wind Harmer
15.687
946321AF1-296 GEN
Solar/Wind Harmer
30.3
274853TWINGROVE;U1
Solar/Wind Harmer
15.712
959611AF2-252 GEN
Solar/Wind Harmer
4.069
960611AF2-352 GEN
Solar/Wind Harmer
4.069
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.317
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.728
274772LINCOLN ;3U
50/50
18.14
274774LINCOLN ;5U
50/50
18.14
944961AF1-161 GEN
50/50
5.878
270043AE2-236 GEN
Solar/Wind Harmer
0.666
971771AH1-392 GEN
Solar/Wind Harmer
1.083
970941AG2-585 GEN
Solar/Wind Harmer
0.632
276897AD1-100 C
Solar/Wind Harmer
151.637
276805AD2-038 GEN
Solar/Wind Harmer
12.877
971605AH1-302 GEN
Solar/Wind Harmer
16.497
970569AG2-363 GEN
Solar/Wind Harmer
3.209
276157O29GEN1
Solar/Wind Harmer
9.213
276645AC1-214 GEN1
Solar/Wind Harmer
3.237
939741AE1-205 GEN
Solar/Wind Harmer
2.07
942111AE2-223 GEN
Solar/Wind Harmer
24.22
970241AG2-163 GEN
Solar/Wind Harmer
2.42
276174W4-005 GEN2
Solar/Wind Harmer
5.74
276668AB2-070 GEN1
Solar/Wind Harmer
4.926
276838X2-022 GEN2
Solar/Wind Harmer
0.509
970825AG2-519 GEN
Solar/Wind Harmer
0.573
270007AE1-245 C
Solar/Wind Harmer
7.285
246938BC-WTG3
Solar/Wind Harmer
6.065
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
14.391
943121AE2-341 GEN
Solar/Wind Harmer
1.695
957471AF2-041 GEN
Solar/Wind Harmer
3.247
274848CAMPGROVE;RU
Solar/Wind Harmer
12.124
276785W4-005 GEN1
Solar/Wind Harmer
5.74
276849AB2-070 GEN2
Solar/Wind Harmer
4.926
970289AG2-191 GEN
Solar/Wind Harmer
1.255
970291AG2-192 GEN
Solar/Wind Harmer
0.684
270246TR4_N_V150
Solar/Wind Harmer
1.644
957201AF2-014 GEN
Solar/Wind Harmer
0
270142AC1-141 CT1_
50/50
4.953
270143AC1-141 CT2_
50/50
4.953
24639705ELKHART HY
50/50
0.331
965681AG1-436 GEN
Solar/Wind Harmer
1.504
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.13
276694AA1-018 GEN2
Solar/Wind Harmer
11.833
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.165
970169AG2-114 GEN
Solar/Wind Harmer
1.072
24755605MDL-5G
Solar/Wind Harmer
5.509
959341AF2-225 GEN
Solar/Wind Harmer
1.553
971087AG2-675 GEN
Solar/Wind Harmer
6.471
963791AG1-232 GEN
Solar/Wind Harmer
1.31
970291AG2-192 GEN
Solar/Wind Harmer
0.124
247521TR3_G114
Solar/Wind Harmer
6.497
24695305TIMB G C
Solar/Wind Harmer
6.263
270445AC2-157 GEN2
Solar/Wind Harmer
0
270144AC1-141 ST1_
50/50
4.385
24642205MAYFLWER
50/50
1.524
962601AG1-109 GEN
50/50
5.878
247620Y3-023
50/50
0.982
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.5
274861TOP CROP ;1U
Solar/Wind Harmer
13.024
971067AG2-660 GEN
Solar/Wind Harmer
4.33
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
16.693
959331AF2-224 GEN
Solar/Wind Harmer
1.053
276655WTG1_EQ
Solar/Wind Harmer
17.823
963841AG1-237 GEN
Solar/Wind Harmer
31.024
270031AE2-169
Solar/Wind Harmer
0.756
965041AG1-368 GEN
Solar/Wind Harmer
0.91
24699105WLD G1 C
Solar/Wind Harmer
6.849
270383AD1-128 GEN
Solar/Wind Harmer
0
970521AG2-332 GEN
50/50
23.519
276806AD2-047 C O1
Solar/Wind Harmer
35.37
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.165
274877BISHOP HL;1U
Solar/Wind Harmer
8.109
276848AB2-070 GEN3
Solar/Wind Harmer
4.926
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.722
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.307
LAGNLTFEXP_LAGN->PJM
CLTF
13.625
AH1-155LTFEXP_AH1-155->PJM
LTF
0.653
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.183
WECLTFEXP_WEC->PJM
CLTF
7.061
MECLTFEXP_MEC->PJM
CLTF
25.64
AG2-052LTFEXP_AG2-052->PJM
LTF
0.436
CBM West 1LTFEXP_CBM-W1->PJM
CBM
218.246
LGEELTFEXP_LGEE->PJM
CLTF
5.512
TVALTFEXP_TVA->PJM
CLTF
5.176
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.752
NYPJM->LTFIMP_NY
CLTF
3.51
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.586
SIGELTFEXP_SIGE->PJM
CLTF
0.545

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.1 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5114.58
MW Contribution:
0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24641605TWIN BRNCH
50/50
0.038
970707AG2-453 GEN
Solar/Wind Harmer
3.442
970833AG2-524 GEN
Solar/Wind Harmer
10.625
958481AF2-142 GEN
Solar/Wind Harmer
1.773
274862TOP CROP ;2U
Solar/Wind Harmer
13.823
944531AF1-118 GEN
Solar/Wind Harmer
4.124
274879MINONK ;1U
Solar/Wind Harmer
18.098
970781AG2-491 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
2.078
966841AG1-555 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.948
965911AG1-460 GEN
Solar/Wind Harmer
2.235
945391AF1-204 GEN
Solar/Wind Harmer
35.346
270247TR4_N_V136
Solar/Wind Harmer
1.736
972207SS24-0001
Solar/Wind Harmer
3.771
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
1.24
274847GR RIDGE ;BU
Solar/Wind Harmer
13.871
959091AF2-200 GEN
Solar/Wind Harmer
2.292
274849CRESCENT ;1U
Solar/Wind Harmer
4.671
270102X2-052 ST
50/50
3.588
970901AG2-562 GEN
50/50
13.596
24344005CKG1
50/50
15.641
274777LINCOLN ;8U
50/50
19.36
961051AF2-396 GEN
Solar/Wind Harmer
2.534
961051AF2-396 GEN
Solar/Wind Harmer
20.273
972231SS25-0005
Solar/Wind Harmer
1.984
971411AH1-196 GEN
Solar/Wind Harmer
1.732
274855GSG-6 ;RU
Solar/Wind Harmer
9.856
276876AE1-163_GEN2
Solar/Wind Harmer
15.618
24386405FR-21G C
Solar/Wind Harmer
8.604
276782AC1-033 GEN
Solar/Wind Harmer
8.596
276763AC1-053 GEN1
Solar/Wind Harmer
7.686
270599AE1-208 GEN
Solar/Wind Harmer
0.777
971029AG2-637 GEN
Solar/Wind Harmer
1.009
965651AG1-433 GEN
Solar/Wind Harmer
16.751
970289AG2-191 GEN
Solar/Wind Harmer
0.194
957381AF2-032 GEN
Solar/Wind Harmer
0.187
276916AD2-100_GEN
Solar/Wind Harmer
1.936
946031AF1-268 GEN
Solar/Wind Harmer
0.718
965421AG1-410 GEN
Solar/Wind Harmer
2.22
270349AD2-093_GEN
Solar/Wind Helper
0.709
274775LINCOLN ;6U
50/50
19.36
970349AG2-230 GEN
Solar/Wind Harmer
2.07
971347AH1-153 GEN
Solar/Wind Harmer
0.69
958381AF2-132 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.224
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
46.474
926823AC1-168 GEN
Solar/Wind Harmer
13.842
274857EASY ROAD;U1
Solar/Wind Harmer
10.475
276656WTG2_EQ
Solar/Wind Harmer
2.468
276615X2-022 GEN
Solar/Wind Harmer
4.403
24725505WLD G2 C
Solar/Wind Harmer
7.152
965051AG1-369 GEN
Solar/Wind Harmer
0.441
961761AG1-017 GEN
Solar/Wind Harmer
0.849
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.391
958091AF2-103 GEN
Solar/Wind Harmer
0
24307105BERRINSP G
50/50
0.047
274773LINCOLN ;4U
50/50
19.36
270505AE1-170 C O1
Solar/Wind Harmer
1.918
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.521
24691005MDL-2G C
Solar/Wind Harmer
9.046
971997AH1-543 GEN
Solar/Wind Harmer
1.823
971549AH1-272 GEN
Solar/Wind Harmer
2.128
276889AE2-281 GEN
Solar/Wind Harmer
4.462
965021AG1-366 GEN
Solar/Wind Harmer
4.438
24653605MOTTVILLE
50/50
0.008
957891AF2-083 GEN
Solar/Wind Harmer
1.915
270071AF1-092 GEN
Solar/Wind Harmer
1.91
274888KELLY CRK;1U
Solar/Wind Harmer
16.701
276893AG1-478 C
Solar/Wind Harmer
0.967
276602WESTBROOK C
Solar/Wind Harmer
4.861
274863CRW1-WTG
Solar/Wind Harmer
13.439
274864CRW2-WTG
Solar/Wind Harmer
13.439
276603SUBLETTE C
Solar/Wind Harmer
2.266
24387305FR-4G C
Solar/Wind Harmer
12.907
24386605FR-22G C
Solar/Wind Harmer
8.604
24387005FR-3G C
Solar/Wind Harmer
8.518
274880W4-005 GEN4
Solar/Wind Harmer
5.919
270005AE1-210 C O1
Solar/Wind Harmer
13.854
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.292
246936BC-WTG1
Solar/Wind Harmer
6.341
246937BC-WTG2
Solar/Wind Harmer
6.341
270100X2-052 CT1
50/50
3.316
274770LINCOLN ;1U
50/50
19.36
274771LINCOLN ;2U
50/50
19.36
945111AF1-176 GEN
Solar/Wind Harmer
2.267
945111AF1-176 GEN
Solar/Wind Harmer
12.356
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.665
274850MENDOTA H;RU
Solar/Wind Harmer
6.853
276863AD2-134 GEN
Solar/Wind Harmer
4.766
276861AD2-134 GEN
Solar/Wind Harmer
4.766
274856ECOGROVE ;U1
Solar/Wind Harmer
8.831
970571AG2-364 GEN
Solar/Wind Harmer
2.258
971681AH1-341 GEN
Solar/Wind Harmer
1.687
938861AE1-114 GEN
Solar/Wind Harmer
26.302
274858EASY ROAD;U2
Solar/Wind Harmer
10.475
965011AG1-365 GEN
Solar/Wind Harmer
1.11
24344105CKG2
50/50
19.181
270101X2-052 CT2
50/50
3.316
965791AG1-447 GEN
Solar/Wind Harmer
14.269
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
9.049
270180AB1-006 GEN1
Solar/Wind Harmer
16.282
24791305MDL-5G
Solar/Wind Harmer
6.03
276741O09 GEN1
Solar/Wind Harmer
9.119
276726Z2-087_GEN
Solar/Wind Harmer
16.885
944541AF1-119 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
27.731
270191TR4_S_V150
Solar/Wind Harmer
5.23
943021AE2-325 GEN
Solar/Wind Harmer
7.925
276843GEN-1.7
Solar/Wind Harmer
1.622
958011AF2-095 GEN
Solar/Wind Harmer
1.762
945421AF1-207 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.273
958491AF2-143 GEN
Solar/Wind Harmer
1.749
24697905MDL-4G C
Solar/Wind Harmer
6.03
970819AG2-516 GEN
Solar/Wind Harmer
1.361
276646AC1-214 GEN2
Solar/Wind Harmer
3.406
274878BISHOP HL;2U
Solar/Wind Harmer
8.527
965931AG1-462 GEN
Solar/Wind Harmer
2.709
274854TWINGROVE;U2
Solar/Wind Harmer
16.378
965091AG1-374 GEN
Solar/Wind Harmer
3.181
964611AG1-324 GEN
Solar/Wind Harmer
0.776
270491AE1-102 GEN2
Solar/Wind Harmer
0.091
270356AE2-297 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
1.575
270240V3-007_GEN2
Solar/Wind Harmer
9.719
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.091
276158O29GEN2
Solar/Wind Harmer
9.711
276708O09 GEN2
Solar/Wind Harmer
9.119
958861AF2-177 GEN
Solar/Wind Harmer
32.716
942221AE2-234 GEN
Solar/Wind Harmer
0.36
945371AF1-202 GEN
Solar/Wind Harmer
15.608
971993AH1-541 GEN
Solar/Wind Harmer
0.917
270032AE2-172
Solar/Wind Harmer
7.876
276621W2-048 GEN
Solar/Wind Harmer
14.021
942481AE2-261 GEN
Solar/Wind Harmer
2.785
970825AG2-519 GEN
Solar/Wind Harmer
3.741
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.694
270543AE2-219 C
Solar/Wind Harmer
0.734
247607V1-011 GEN
Solar/Wind Harmer
5.511
270435AC2-044 GEN
Solar/Wind Harmer
0.14
944961AF1-161 GEN
50/50
6.326
274772LINCOLN ;3U
50/50
19.36
274774LINCOLN ;5U
50/50
19.36
971771AH1-392 GEN
Solar/Wind Harmer
1.165
270043AE2-236 GEN
Solar/Wind Harmer
0.704
970941AG2-585 GEN
Solar/Wind Harmer
0.673
276897AD1-100 C
Solar/Wind Harmer
161.319
971605AH1-302 GEN
Solar/Wind Harmer
18.099
276805AD2-038 GEN
Solar/Wind Harmer
13.646
970569AG2-363 GEN
Solar/Wind Harmer
3.387
276157O29GEN1
Solar/Wind Harmer
9.711
276645AC1-214 GEN1
Solar/Wind Harmer
3.406
939741AE1-205 GEN
Solar/Wind Harmer
2.165
942111AE2-223 GEN
Solar/Wind Harmer
25.328
970241AG2-163 GEN
Solar/Wind Harmer
2.554
276174W4-005 GEN2
Solar/Wind Harmer
5.919
276668AB2-070 GEN1
Solar/Wind Harmer
5.081
276838X2-022 GEN2
Solar/Wind Harmer
0.523
970825AG2-519 GEN
Solar/Wind Harmer
0.584
270007AE1-245 C
Solar/Wind Harmer
7.728
246938BC-WTG3
Solar/Wind Harmer
6.451
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
15.301
943121AE2-341 GEN
Solar/Wind Harmer
1.802
957471AF2-041 GEN
Solar/Wind Harmer
3.438
274848CAMPGROVE;RU
Solar/Wind Harmer
12.74
970289AG2-191 GEN
Solar/Wind Harmer
1.347
970291AG2-192 GEN
Solar/Wind Harmer
0.735
276785W4-005 GEN1
Solar/Wind Harmer
5.919
276849AB2-070 GEN2
Solar/Wind Harmer
5.081
270246TR4_N_V150
Solar/Wind Harmer
1.736
957201AF2-014 GEN
Solar/Wind Harmer
0
270142AC1-141 CT1_
50/50
5.33
270143AC1-141 CT2_
50/50
5.33
24639705ELKHART HY
50/50
0.355
965681AG1-436 GEN
Solar/Wind Harmer
1.621
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.201
276694AA1-018 GEN2
Solar/Wind Harmer
12.56
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
6.03
971343AH1-151 GEN
Solar/Wind Harmer
2.292
970169AG2-114 GEN
Solar/Wind Harmer
1.128
959341AF2-225 GEN
Solar/Wind Harmer
1.624
971087AG2-675 GEN
Solar/Wind Harmer
6.799
970291AG2-192 GEN
Solar/Wind Harmer
0.133
963791AG1-232 GEN
Solar/Wind Harmer
1.369
247521TR3_G114
Solar/Wind Harmer
6.863
24695305TIMB G C
Solar/Wind Harmer
6.622
270445AC2-157 GEN2
Solar/Wind Harmer
0
270144AC1-141 ST1_
50/50
4.718
24642205MAYFLWER
50/50
1.639
962601AG1-109 GEN
50/50
6.326
247620Y3-023
50/50
1.053
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.13
274861TOP CROP ;1U
Solar/Wind Harmer
13.823
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
18.272
971067AG2-660 GEN
Solar/Wind Harmer
4.584
959331AF2-224 GEN
Solar/Wind Harmer
1.11
276655WTG1_EQ
Solar/Wind Harmer
18.638
963841AG1-237 GEN
Solar/Wind Harmer
33.096
965041AG1-368 GEN
Solar/Wind Harmer
0.961
270031AE2-169
Solar/Wind Harmer
0.777
24699105WLD G1 C
Solar/Wind Harmer
7.152
270383AD1-128 GEN
Solar/Wind Harmer
0
24643105BUCHANAN
50/50
0.028
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
15.078
970031AG2-029 GEN
Solar/Wind Harmer
3.032
970833AG2-524 GEN
Solar/Wind Harmer
1.328
962781AG1-127 GEN
Solar/Wind Harmer
1.113
276868AE1-113 GEN
Solar/Wind Harmer
27.147
24697605MDL-3G C
Solar/Wind Harmer
9.046
270181AB1-006 GEN2
Solar/Wind Harmer
1.809
971171AH1-044 GEN
Solar/Wind Harmer
2.292
24385905FR-11G C
Solar/Wind Harmer
16.916
960971AF2-388 GEN
Solar/Wind Harmer
33.501
946321AF1-296 GEN
Solar/Wind Harmer
31.858
274853TWINGROVE;U1
Solar/Wind Harmer
16.378
959611AF2-252 GEN
Solar/Wind Harmer
4.242
960611AF2-352 GEN
Solar/Wind Harmer
4.242
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.333
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.734
274776LINCOLN ;7U
50/50
19.36
970373AG2-245 GEN
Solar/Wind Harmer
2.641
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
21.85
959081AF2-199 GEN
Solar/Wind Harmer
1.146
276872AE1-163_GEN1
Solar/Wind Harmer
15.618
24386205FR-12G C
Solar/Wind Harmer
8.983
274851PROVIDENC;RU
Solar/Wind Harmer
6.348
963741AG1-226 GEN
Solar/Wind Harmer
4.597
276686W4-005 GEN3
Solar/Wind Harmer
5.919
276764AC1-053 GEN2
Solar/Wind Harmer
7.686
276911AD2-131_GEN
Solar/Wind Harmer
0.461
270004AE1-209 GEN
Solar/Wind Harmer
13.854
270201AC2-176 GEN
Solar/Wind Harmer
8.734
24379505HDWTR1G C
Solar/Wind Harmer
12.413
970885AG2-551 GEN
Solar/Wind Harmer
2.937
970521AG2-332 GEN
50/50
25.247
276806AD2-047 C O1
Solar/Wind Harmer
37.684
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.292
274877BISHOP HL;1U
Solar/Wind Harmer
8.527
276848AB2-070 GEN3
Solar/Wind Harmer
5.081
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.709
CBM West 2LTFEXP_CBM-W2->PJM
CBM
127.984
WECLTFEXP_WEC->PJM
CLTF
7.473
MECLTFEXP_MEC->PJM
CLTF
26.605
AG2-052LTFEXP_AG2-052->PJM
LTF
0.465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
229.695
LGEELTFEXP_LGEE->PJM
CLTF
4.399
TVALTFEXP_TVA->PJM
CLTF
4.838
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
52.01
NYPJM->LTFIMP_NY
CLTF
3.513
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.679
SIGELTFEXP_SIGE->PJM
CLTF
0.501
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.218
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.445
LAGNLTFEXP_LAGN->PJM
CLTF
13.263
AH1-155LTFEXP_AH1-155->PJM
LTF
0.698

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5065.25
MW Contribution:
0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24653605MOTTVILLE
50/50
0.008
270071AF1-092 GEN
Solar/Wind Harmer
1.791
957891AF2-083 GEN
Solar/Wind Harmer
1.784
274888KELLY CRK;1U
Solar/Wind Harmer
15.718
276893AG1-478 C
Solar/Wind Harmer
0.911
276602WESTBROOK C
Solar/Wind Harmer
4.602
274863CRW1-WTG
Solar/Wind Harmer
12.774
274864CRW2-WTG
Solar/Wind Harmer
12.774
276603SUBLETTE C
Solar/Wind Harmer
2.152
24387305FR-4G C
Solar/Wind Harmer
12.006
24386605FR-22G C
Solar/Wind Harmer
8.004
24387005FR-3G C
Solar/Wind Harmer
7.924
274880W4-005 GEN4
Solar/Wind Harmer
5.759
270005AE1-210 C O1
Solar/Wind Harmer
13.746
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.269
246936BC-WTG1
Solar/Wind Harmer
5.99
246937BC-WTG2
Solar/Wind Harmer
5.99
972207SS24-0001
Solar/Wind Harmer
3.543
972181SS23-001
Solar/Wind Harmer
1.163
270055AF2-134 C O1
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
13.082
959091AF2-200 GEN
Solar/Wind Harmer
2.171
274849CRESCENT ;1U
Solar/Wind Harmer
4.453
965651AG1-433 GEN
Solar/Wind Harmer
16.356
970289AG2-191 GEN
Solar/Wind Harmer
0.181
957381AF2-032 GEN
Solar/Wind Harmer
0.184
276916AD2-100_GEN
Solar/Wind Harmer
1.907
946031AF1-268 GEN
Solar/Wind Harmer
0.709
965421AG1-410 GEN
Solar/Wind Harmer
2.099
270349AD2-093_GEN
Solar/Wind Helper
0.718
270142AC1-141 CT1_
50/50
4.966
270143AC1-141 CT2_
50/50
4.966
24639705ELKHART HY
50/50
0.332
965681AG1-436 GEN
Solar/Wind Harmer
1.508
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.133
276694AA1-018 GEN2
Solar/Wind Harmer
11.866
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.171
970169AG2-114 GEN
Solar/Wind Harmer
1.075
24755605MDL-5G
Solar/Wind Harmer
5.525
959341AF2-225 GEN
Solar/Wind Harmer
1.557
971087AG2-675 GEN
Solar/Wind Harmer
6.491
963791AG1-232 GEN
Solar/Wind Harmer
1.314
970291AG2-192 GEN
Solar/Wind Harmer
0.124
247521TR3_G114
Solar/Wind Harmer
6.522
24695305TIMB G C
Solar/Wind Harmer
6.288
270445AC2-157 GEN2
Solar/Wind Harmer
0
274776LINCOLN ;7U
50/50
18.189
970373AG2-245 GEN
Solar/Wind Harmer
2.436
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
20.665
959081AF2-199 GEN
Solar/Wind Harmer
1.086
276872AE1-163_GEN1
Solar/Wind Harmer
14.816
274851PROVIDENC;RU
Solar/Wind Harmer
6.052
24386205FR-12G C
Solar/Wind Harmer
8.356
963741AG1-226 GEN
Solar/Wind Harmer
4.37
276686W4-005 GEN3
Solar/Wind Harmer
5.759
276764AC1-053 GEN2
Solar/Wind Harmer
7.485
276911AD2-131_GEN
Solar/Wind Harmer
0.454
270004AE1-209 GEN
Solar/Wind Harmer
13.746
270201AC2-176 GEN
Solar/Wind Harmer
8.576
24379505HDWTR1G C
Solar/Wind Harmer
12.487
970885AG2-551 GEN
Solar/Wind Harmer
2.924
270100X2-052 CT1
50/50
3.082
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
14.431
943121AE2-341 GEN
Solar/Wind Harmer
1.699
957471AF2-041 GEN
Solar/Wind Harmer
3.257
274848CAMPGROVE;RU
Solar/Wind Harmer
12.161
276785W4-005 GEN1
Solar/Wind Harmer
5.759
276849AB2-070 GEN2
Solar/Wind Harmer
4.942
970289AG2-191 GEN
Solar/Wind Harmer
1.259
970291AG2-192 GEN
Solar/Wind Harmer
0.687
270246TR4_N_V150
Solar/Wind Harmer
1.65
957201AF2-014 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
50/50
18.189
274771LINCOLN ;2U
50/50
18.189
945111AF1-176 GEN
Solar/Wind Harmer
2.113
945111AF1-176 GEN
Solar/Wind Harmer
11.52
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.415
940581AE2-045 GEN
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
6.488
276863AD2-134 GEN
Solar/Wind Harmer
4.512
276861AD2-134 GEN
Solar/Wind Harmer
4.512
274856ECOGROVE ;U1
Solar/Wind Harmer
8.375
970571AG2-364 GEN
Solar/Wind Harmer
2.146
971681AH1-341 GEN
Solar/Wind Harmer
1.601
938861AE1-114 GEN
Solar/Wind Harmer
24.967
274858EASY ROAD;U2
Solar/Wind Harmer
9.947
965011AG1-365 GEN
Solar/Wind Harmer
1.056
270594AE1-207 GEN
Solar/Wind Harmer
1.49
270240V3-007_GEN2
Solar/Wind Harmer
9.777
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.086
270102X2-052 ST
50/50
3.334
970901AG2-562 GEN
50/50
12.636
24344005CKG1
50/50
14.55
274777LINCOLN ;8U
50/50
18.189
961051AF2-396 GEN
Solar/Wind Harmer
2.362
961051AF2-396 GEN
Solar/Wind Harmer
18.894
972231SS25-0005
Solar/Wind Harmer
1.861
971411AH1-196 GEN
Solar/Wind Harmer
1.64
274855GSG-6 ;RU
Solar/Wind Harmer
9.332
276876AE1-163_GEN2
Solar/Wind Harmer
14.816
276782AC1-033 GEN
Solar/Wind Harmer
8.199
24386405FR-21G C
Solar/Wind Harmer
8.004
276763AC1-053 GEN1
Solar/Wind Harmer
7.485
270599AE1-208 GEN
Solar/Wind Harmer
0.758
971029AG2-637 GEN
Solar/Wind Harmer
1.014
24641605TWIN BRNCH
50/50
0.036
970707AG2-453 GEN
Solar/Wind Harmer
3.24
944531AF1-118 GEN
Solar/Wind Harmer
4
970833AG2-524 GEN
Solar/Wind Harmer
10.019
958481AF2-142 GEN
Solar/Wind Harmer
1.675
274862TOP CROP ;2U
Solar/Wind Harmer
13.061
274879MINONK ;1U
Solar/Wind Harmer
17.14
971675AH1-338 GEN
Solar/Wind Harmer
1.967
970781AG2-491 GEN
Solar/Wind Harmer
1.063
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.198
276903AD2-071 C
Solar/Wind Harmer
0.902
945391AF1-204 GEN
Solar/Wind Harmer
35.046
270247TR4_N_V136
Solar/Wind Harmer
1.65
274775LINCOLN ;6U
50/50
18.189
970349AG2-230 GEN
Solar/Wind Harmer
1.927
971347AH1-153 GEN
Solar/Wind Harmer
0.642
960591AF2-350 GEN
Solar/Wind Harmer
1.152
939351AE1-166 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
44.067
926823AC1-168 GEN
Solar/Wind Harmer
13.159
274857EASY ROAD;U1
Solar/Wind Harmer
9.947
276656WTG2_EQ
Solar/Wind Harmer
2.367
276615X2-022 GEN
Solar/Wind Harmer
4.298
24725505WLD G2 C
Solar/Wind Harmer
6.873
961761AG1-017 GEN
Solar/Wind Harmer
0.834
965051AG1-369 GEN
Solar/Wind Harmer
0.419
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.309
958091AF2-103 GEN
Solar/Wind Harmer
0
24643105BUCHANAN
50/50
0.026
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
14.191
970031AG2-029 GEN
Solar/Wind Harmer
2.853
970833AG2-524 GEN
Solar/Wind Harmer
1.252
962781AG1-127 GEN
Solar/Wind Harmer
1.052
276868AE1-113 GEN
Solar/Wind Harmer
25.71
971171AH1-044 GEN
Solar/Wind Harmer
2.171
24697605MDL-3G C
Solar/Wind Harmer
8.288
270181AB1-006 GEN2
Solar/Wind Harmer
1.658
960971AF2-388 GEN
Solar/Wind Harmer
32.712
24385905FR-11G C
Solar/Wind Harmer
15.735
946321AF1-296 GEN
Solar/Wind Harmer
30.393
24344105CKG2
50/50
17.806
270101X2-052 CT2
50/50
3.082
965791AG1-447 GEN
Solar/Wind Harmer
13.273
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
8.57
270180AB1-006 GEN1
Solar/Wind Harmer
14.919
24791305MDL-5G
Solar/Wind Harmer
5.525
276741O09 GEN1
Solar/Wind Harmer
8.678
944541AF1-119 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
16.196
944221AF1-090 GEN
Solar/Wind Harmer
27.525
270191TR4_S_V150
Solar/Wind Harmer
4.97
274853TWINGROVE;U1
Solar/Wind Harmer
15.76
959611AF2-252 GEN
Solar/Wind Harmer
4.082
960611AF2-352 GEN
Solar/Wind Harmer
4.082
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.322
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.731
943021AE2-325 GEN
Solar/Wind Harmer
7.384
276843GEN-1.7
Solar/Wind Harmer
1.527
958011AF2-095 GEN
Solar/Wind Harmer
1.658
276691AA1-018 GEN1
Solar/Wind Harmer
1.202
958491AF2-143 GEN
Solar/Wind Harmer
1.656
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.291
24697905MDL-4G C
Solar/Wind Harmer
5.525
276646AC1-214 GEN2
Solar/Wind Harmer
3.247
274878BISHOP HL;2U
Solar/Wind Harmer
8.133
274854TWINGROVE;U2
Solar/Wind Harmer
15.76
965091AG1-374 GEN
Solar/Wind Harmer
3.061
965931AG1-462 GEN
Solar/Wind Harmer
2.586
964611AG1-324 GEN
Solar/Wind Harmer
0.763
270356AE2-297 GEN
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.086
270144AC1-141 ST1_
50/50
4.396
24642205MAYFLWER
50/50
1.528
962601AG1-109 GEN
50/50
5.894
247620Y3-023
50/50
0.985
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.549
274861TOP CROP ;1U
Solar/Wind Harmer
13.061
971067AG2-660 GEN
Solar/Wind Harmer
4.343
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
16.742
959331AF2-224 GEN
Solar/Wind Harmer
1.056
276655WTG1_EQ
Solar/Wind Harmer
17.878
963841AG1-237 GEN
Solar/Wind Harmer
31.122
270031AE2-169
Solar/Wind Harmer
0.758
965041AG1-368 GEN
Solar/Wind Harmer
0.913
24699105WLD G1 C
Solar/Wind Harmer
6.873
270383AD1-128 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
50/50
18.189
24307105BERRINSP G
50/50
0.044
270505AE1-170 C O1
Solar/Wind Harmer
1.788
962691AG1-118 GEN
Solar/Wind Harmer
3.328
971997AH1-543 GEN
Solar/Wind Harmer
1.728
276889AE2-281 GEN
Solar/Wind Harmer
4.233
957841AF2-078 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
1.981
24691005MDL-2G C
Solar/Wind Harmer
8.288
965021AG1-366 GEN
Solar/Wind Harmer
4.223
276158O29GEN2
Solar/Wind Harmer
9.24
276708O09 GEN2
Solar/Wind Harmer
8.678
958861AF2-177 GEN
Solar/Wind Harmer
32.004
942221AE2-234 GEN
Solar/Wind Harmer
0.347
945371AF1-202 GEN
Solar/Wind Harmer
15.326
971993AH1-541 GEN
Solar/Wind Harmer
0.892
276621W2-048 GEN
Solar/Wind Harmer
13.685
270032AE2-172
Solar/Wind Harmer
7.448
942481AE2-261 GEN
Solar/Wind Harmer
2.738
970825AG2-519 GEN
Solar/Wind Harmer
3.685
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.71
270543AE2-219 C
Solar/Wind Harmer
0.731
247607V1-011 GEN
Solar/Wind Harmer
5.22
270435AC2-044 GEN
Solar/Wind Harmer
0.132
970521AG2-332 GEN
50/50
23.582
276806AD2-047 C O1
Solar/Wind Harmer
35.467
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.171
274877BISHOP HL;1U
Solar/Wind Harmer
8.133
276848AB2-070 GEN3
Solar/Wind Harmer
4.942
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.718
274772LINCOLN ;3U
50/50
18.189
274774LINCOLN ;5U
50/50
18.189
944961AF1-161 GEN
50/50
5.894
270043AE2-236 GEN
Solar/Wind Harmer
0.667
971771AH1-392 GEN
Solar/Wind Harmer
1.085
970941AG2-585 GEN
Solar/Wind Harmer
0.633
276897AD1-100 C
Solar/Wind Harmer
152.054
276805AD2-038 GEN
Solar/Wind Harmer
12.914
971605AH1-302 GEN
Solar/Wind Harmer
16.544
970569AG2-363 GEN
Solar/Wind Harmer
3.218
276157O29GEN1
Solar/Wind Harmer
9.24
276645AC1-214 GEN1
Solar/Wind Harmer
3.247
939741AE1-205 GEN
Solar/Wind Harmer
2.076
942111AE2-223 GEN
Solar/Wind Harmer
24.294
970241AG2-163 GEN
Solar/Wind Harmer
2.428
276174W4-005 GEN2
Solar/Wind Harmer
5.759
276668AB2-070 GEN1
Solar/Wind Harmer
4.942
276838X2-022 GEN2
Solar/Wind Harmer
0.51
970825AG2-519 GEN
Solar/Wind Harmer
0.575
270007AE1-245 C
Solar/Wind Harmer
7.32
246938BC-WTG3
Solar/Wind Harmer
6.094
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.913
WECLTFEXP_WEC->PJM
CLTF
7.082
MECLTFEXP_MEC->PJM
CLTF
25.731
AG2-052LTFEXP_AG2-052->PJM
LTF
0.437
CBM West 1LTFEXP_CBM-W1->PJM
CBM
219.037
LGEELTFEXP_LGEE->PJM
CLTF
5.55
TVALTFEXP_TVA->PJM
CLTF
5.231
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.752
NYPJM->LTFIMP_NY
CLTF
3.476
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.564
SIGELTFEXP_SIGE->PJM
CLTF
0.547
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.553
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.271
LAGNLTFEXP_LAGN->PJM
CLTF
13.735
AH1-155LTFEXP_AH1-155->PJM
LTF
0.655

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5065.17
MW Contribution:
0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
18.189
970349AG2-230 GEN
Solar/Wind Harmer
1.927
971347AH1-153 GEN
Solar/Wind Harmer
0.642
960591AF2-350 GEN
Solar/Wind Harmer
1.152
24653605MOTTVILLE
50/50
0.008
270071AF1-092 GEN
Solar/Wind Harmer
1.791
957891AF2-083 GEN
Solar/Wind Harmer
1.784
274888KELLY CRK;1U
Solar/Wind Harmer
15.718
276893AG1-478 C
Solar/Wind Harmer
0.911
276602WESTBROOK C
Solar/Wind Harmer
4.602
274863CRW1-WTG
Solar/Wind Harmer
12.774
274864CRW2-WTG
Solar/Wind Harmer
12.774
276603SUBLETTE C
Solar/Wind Harmer
2.152
24387305FR-4G C
Solar/Wind Harmer
12.006
24344105CKG2
50/50
17.806
270101X2-052 CT2
50/50
3.082
965791AG1-447 GEN
Solar/Wind Harmer
13.273
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
8.57
270180AB1-006 GEN1
Solar/Wind Harmer
14.919
24791305MDL-5G
Solar/Wind Harmer
5.525
276741O09 GEN1
Solar/Wind Harmer
8.678
944541AF1-119 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
16.196
944221AF1-090 GEN
Solar/Wind Harmer
27.525
270191TR4_S_V150
Solar/Wind Harmer
4.97
943021AE2-325 GEN
Solar/Wind Harmer
7.384
276843GEN-1.7
Solar/Wind Harmer
1.527
958011AF2-095 GEN
Solar/Wind Harmer
1.658
276691AA1-018 GEN1
Solar/Wind Harmer
1.202
958491AF2-143 GEN
Solar/Wind Harmer
1.656
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.291
24697905MDL-4G C
Solar/Wind Harmer
5.525
276646AC1-214 GEN2
Solar/Wind Harmer
3.247
274878BISHOP HL;2U
Solar/Wind Harmer
8.133
274854TWINGROVE;U2
Solar/Wind Harmer
15.76
965091AG1-374 GEN
Solar/Wind Harmer
3.061
965931AG1-462 GEN
Solar/Wind Harmer
2.586
964611AG1-324 GEN
Solar/Wind Harmer
0.763
270356AE2-297 GEN
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.086
939351AE1-166 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
44.067
926823AC1-168 GEN
Solar/Wind Harmer
13.159
274857EASY ROAD;U1
Solar/Wind Harmer
9.947
276656WTG2_EQ
Solar/Wind Harmer
2.367
276615X2-022 GEN
Solar/Wind Harmer
4.298
24725505WLD G2 C
Solar/Wind Harmer
6.873
961761AG1-017 GEN
Solar/Wind Harmer
0.834
965051AG1-369 GEN
Solar/Wind Harmer
0.419
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.309
958091AF2-103 GEN
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
3.082
274770LINCOLN ;1U
50/50
18.189
274771LINCOLN ;2U
50/50
18.189
945111AF1-176 GEN
Solar/Wind Harmer
2.113
945111AF1-176 GEN
Solar/Wind Harmer
11.52
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.415
940581AE2-045 GEN
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
6.488
276863AD2-134 GEN
Solar/Wind Harmer
4.512
276861AD2-134 GEN
Solar/Wind Harmer
4.512
274856ECOGROVE ;U1
Solar/Wind Harmer
8.375
970571AG2-364 GEN
Solar/Wind Harmer
2.146
971681AH1-341 GEN
Solar/Wind Harmer
1.601
938861AE1-114 GEN
Solar/Wind Harmer
24.967
274858EASY ROAD;U2
Solar/Wind Harmer
9.947
965011AG1-365 GEN
Solar/Wind Harmer
1.056
270594AE1-207 GEN
Solar/Wind Harmer
1.49
270240V3-007_GEN2
Solar/Wind Harmer
9.777
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.086
274773LINCOLN ;4U
50/50
18.189
24307105BERRINSP G
50/50
0.044
270505AE1-170 C O1
Solar/Wind Harmer
1.788
962691AG1-118 GEN
Solar/Wind Harmer
3.328
971997AH1-543 GEN
Solar/Wind Harmer
1.728
276889AE2-281 GEN
Solar/Wind Harmer
4.233
957841AF2-078 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
1.981
24691005MDL-2G C
Solar/Wind Harmer
8.288
965021AG1-366 GEN
Solar/Wind Harmer
4.223
276158O29GEN2
Solar/Wind Harmer
9.24
276708O09 GEN2
Solar/Wind Harmer
8.678
958861AF2-177 GEN
Solar/Wind Harmer
32.004
942221AE2-234 GEN
Solar/Wind Harmer
0.347
945371AF1-202 GEN
Solar/Wind Harmer
15.326
971993AH1-541 GEN
Solar/Wind Harmer
0.892
276621W2-048 GEN
Solar/Wind Harmer
13.685
270032AE2-172
Solar/Wind Harmer
7.448
942481AE2-261 GEN
Solar/Wind Harmer
2.738
970825AG2-519 GEN
Solar/Wind Harmer
3.685
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.71
270543AE2-219 C
Solar/Wind Harmer
0.731
247607V1-011 GEN
Solar/Wind Harmer
5.22
270435AC2-044 GEN
Solar/Wind Harmer
0.132
270142AC1-141 CT1_
50/50
4.966
270143AC1-141 CT2_
50/50
4.966
24639705ELKHART HY
50/50
0.332
965681AG1-436 GEN
Solar/Wind Harmer
1.508
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.133
276694AA1-018 GEN2
Solar/Wind Harmer
11.866
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.171
970169AG2-114 GEN
Solar/Wind Harmer
1.075
24755605MDL-5G
Solar/Wind Harmer
5.525
959341AF2-225 GEN
Solar/Wind Harmer
1.557
971087AG2-675 GEN
Solar/Wind Harmer
6.491
963791AG1-232 GEN
Solar/Wind Harmer
1.314
970291AG2-192 GEN
Solar/Wind Harmer
0.124
247521TR3_G114
Solar/Wind Harmer
6.522
24695305TIMB G C
Solar/Wind Harmer
6.288
270445AC2-157 GEN2
Solar/Wind Harmer
0
270102X2-052 ST
50/50
3.334
970901AG2-562 GEN
50/50
12.636
24344005CKG1
50/50
14.55
274777LINCOLN ;8U
50/50
18.189
961051AF2-396 GEN
Solar/Wind Harmer
2.362
961051AF2-396 GEN
Solar/Wind Harmer
18.894
972231SS25-0005
Solar/Wind Harmer
1.861
971411AH1-196 GEN
Solar/Wind Harmer
1.64
274855GSG-6 ;RU
Solar/Wind Harmer
9.332
276876AE1-163_GEN2
Solar/Wind Harmer
14.816
276782AC1-033 GEN
Solar/Wind Harmer
8.199
24386405FR-21G C
Solar/Wind Harmer
8.004
276763AC1-053 GEN1
Solar/Wind Harmer
7.485
270599AE1-208 GEN
Solar/Wind Harmer
0.758
971029AG2-637 GEN
Solar/Wind Harmer
1.014
972207SS24-0001
Solar/Wind Harmer
3.543
972181SS23-001
Solar/Wind Harmer
1.163
270055AF2-134 C O1
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
13.082
959091AF2-200 GEN
Solar/Wind Harmer
2.171
274849CRESCENT ;1U
Solar/Wind Harmer
4.453
965651AG1-433 GEN
Solar/Wind Harmer
16.356
970289AG2-191 GEN
Solar/Wind Harmer
0.181
957381AF2-032 GEN
Solar/Wind Harmer
0.184
276916AD2-100_GEN
Solar/Wind Harmer
1.907
946031AF1-268 GEN
Solar/Wind Harmer
0.709
965421AG1-410 GEN
Solar/Wind Harmer
2.099
270349AD2-093_GEN
Solar/Wind Helper
0.718
24643105BUCHANAN
50/50
0.026
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
14.191
970031AG2-029 GEN
Solar/Wind Harmer
2.853
970833AG2-524 GEN
Solar/Wind Harmer
1.252
962781AG1-127 GEN
Solar/Wind Harmer
1.052
276868AE1-113 GEN
Solar/Wind Harmer
25.71
971171AH1-044 GEN
Solar/Wind Harmer
2.171
24697605MDL-3G C
Solar/Wind Harmer
8.288
270181AB1-006 GEN2
Solar/Wind Harmer
1.658
960971AF2-388 GEN
Solar/Wind Harmer
32.712
24385905FR-11G C
Solar/Wind Harmer
15.735
946321AF1-296 GEN
Solar/Wind Harmer
30.393
274853TWINGROVE;U1
Solar/Wind Harmer
15.76
959611AF2-252 GEN
Solar/Wind Harmer
4.082
960611AF2-352 GEN
Solar/Wind Harmer
4.082
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.322
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.731
274772LINCOLN ;3U
50/50
18.189
274774LINCOLN ;5U
50/50
18.189
944961AF1-161 GEN
50/50
5.894
270043AE2-236 GEN
Solar/Wind Harmer
0.667
971771AH1-392 GEN
Solar/Wind Harmer
1.085
970941AG2-585 GEN
Solar/Wind Harmer
0.633
276897AD1-100 C
Solar/Wind Harmer
152.054
276805AD2-038 GEN
Solar/Wind Harmer
12.914
971605AH1-302 GEN
Solar/Wind Harmer
16.544
24386605FR-22G C
Solar/Wind Harmer
8.004
24387005FR-3G C
Solar/Wind Harmer
7.924
274880W4-005 GEN4
Solar/Wind Harmer
5.759
270005AE1-210 C O1
Solar/Wind Harmer
13.746
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.269
246936BC-WTG1
Solar/Wind Harmer
5.99
246937BC-WTG2
Solar/Wind Harmer
5.99
970569AG2-363 GEN
Solar/Wind Harmer
3.218
276157O29GEN1
Solar/Wind Harmer
9.24
276645AC1-214 GEN1
Solar/Wind Harmer
3.247
939741AE1-205 GEN
Solar/Wind Harmer
2.076
942111AE2-223 GEN
Solar/Wind Harmer
24.294
970241AG2-163 GEN
Solar/Wind Harmer
2.428
276174W4-005 GEN2
Solar/Wind Harmer
5.759
276668AB2-070 GEN1
Solar/Wind Harmer
4.942
276838X2-022 GEN2
Solar/Wind Harmer
0.51
970825AG2-519 GEN
Solar/Wind Harmer
0.575
270007AE1-245 C
Solar/Wind Harmer
7.32
246938BC-WTG3
Solar/Wind Harmer
6.094
270144AC1-141 ST1_
50/50
4.396
24642205MAYFLWER
50/50
1.528
962601AG1-109 GEN
50/50
5.894
247620Y3-023
50/50
0.985
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.549
274861TOP CROP ;1U
Solar/Wind Harmer
13.061
971067AG2-660 GEN
Solar/Wind Harmer
4.343
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
16.742
959331AF2-224 GEN
Solar/Wind Harmer
1.056
276655WTG1_EQ
Solar/Wind Harmer
17.878
963841AG1-237 GEN
Solar/Wind Harmer
31.122
270031AE2-169
Solar/Wind Harmer
0.758
965041AG1-368 GEN
Solar/Wind Harmer
0.913
24699105WLD G1 C
Solar/Wind Harmer
6.873
270383AD1-128 GEN
Solar/Wind Harmer
0
970521AG2-332 GEN
50/50
23.582
276806AD2-047 C O1
Solar/Wind Harmer
35.467
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.171
274877BISHOP HL;1U
Solar/Wind Harmer
8.133
276848AB2-070 GEN3
Solar/Wind Harmer
4.942
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.718
274776LINCOLN ;7U
50/50
18.189
970373AG2-245 GEN
Solar/Wind Harmer
2.436
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
20.665
959081AF2-199 GEN
Solar/Wind Harmer
1.086
276872AE1-163_GEN1
Solar/Wind Harmer
14.816
274851PROVIDENC;RU
Solar/Wind Harmer
6.052
24386205FR-12G C
Solar/Wind Harmer
8.356
963741AG1-226 GEN
Solar/Wind Harmer
4.37
276686W4-005 GEN3
Solar/Wind Harmer
5.759
276764AC1-053 GEN2
Solar/Wind Harmer
7.485
276911AD2-131_GEN
Solar/Wind Harmer
0.454
270004AE1-209 GEN
Solar/Wind Harmer
13.746
270201AC2-176 GEN
Solar/Wind Harmer
8.576
24379505HDWTR1G C
Solar/Wind Harmer
12.487
970885AG2-551 GEN
Solar/Wind Harmer
2.924
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
14.431
943121AE2-341 GEN
Solar/Wind Harmer
1.699
957471AF2-041 GEN
Solar/Wind Harmer
3.257
274848CAMPGROVE;RU
Solar/Wind Harmer
12.161
276785W4-005 GEN1
Solar/Wind Harmer
5.759
276849AB2-070 GEN2
Solar/Wind Harmer
4.942
970289AG2-191 GEN
Solar/Wind Harmer
1.259
970291AG2-192 GEN
Solar/Wind Harmer
0.687
270246TR4_N_V150
Solar/Wind Harmer
1.65
957201AF2-014 GEN
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.036
970707AG2-453 GEN
Solar/Wind Harmer
3.24
944531AF1-118 GEN
Solar/Wind Harmer
4
970833AG2-524 GEN
Solar/Wind Harmer
10.019
958481AF2-142 GEN
Solar/Wind Harmer
1.675
274862TOP CROP ;2U
Solar/Wind Harmer
13.061
274879MINONK ;1U
Solar/Wind Harmer
17.14
971675AH1-338 GEN
Solar/Wind Harmer
1.967
970781AG2-491 GEN
Solar/Wind Harmer
1.063
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.198
276903AD2-071 C
Solar/Wind Harmer
0.902
945391AF1-204 GEN
Solar/Wind Harmer
35.046
270247TR4_N_V136
Solar/Wind Harmer
1.65
CBM West 1LTFEXP_CBM-W1->PJM
CBM
219.037
LGEELTFEXP_LGEE->PJM
CLTF
5.55
TVALTFEXP_TVA->PJM
CLTF
5.231
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.752
NYPJM->LTFIMP_NY
CLTF
3.476
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.564
SIGELTFEXP_SIGE->PJM
CLTF
0.547
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.553
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.271
LAGNLTFEXP_LAGN->PJM
CLTF
13.735
AH1-155LTFEXP_AH1-155->PJM
LTF
0.655
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.913
WECLTFEXP_WEC->PJM
CLTF
7.082
MECLTFEXP_MEC->PJM
CLTF
25.731
AG2-052LTFEXP_AG2-052->PJM
LTF
0.437

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.66 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2300.12
MW Contribution:
0.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.152
944531AF1-118 GEN
Solar/Wind Harmer
2.052
970707AG2-453 GEN
Solar/Wind Harmer
1.192
970833AG2-524 GEN
Solar/Wind Harmer
3.705
958481AF2-142 GEN
Solar/Wind Harmer
0.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.856
274879MINONK ;1U
Solar/Wind Harmer
6.36
971675AH1-338 GEN
Solar/Wind Harmer
0.728
970781AG2-491 GEN
Solar/Wind Harmer
0.403
276903AD2-071 C
Solar/Wind Harmer
0.399
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.811
945391AF1-204 GEN
Solar/Wind Harmer
13.018
270391AF1-285 GEN3
Solar/Wind Helper
0.285
241847AF2-150_GEN
Solar/Wind Helper
0.265
24729205KEY G1
50/50
6.727
270201AC2-176 GEN
Solar/Wind Harmer
4.618
970373AG2-245 GEN
Solar/Wind Harmer
0.924
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.493
274872LEEDK;1U
Solar/Wind Harmer
7.643
965651AG1-433 GEN
Solar/Wind Harmer
8.19
972181SS23-001
Solar/Wind Harmer
0.439
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.299
970289AG2-191 GEN
Solar/Wind Harmer
0.08
274847GR RIDGE ;BU
Solar/Wind Harmer
4.836
946031AF1-268 GEN
Solar/Wind Harmer
0.346
959091AF2-200 GEN
Solar/Wind Harmer
0.804
274849CRESCENT ;1U
Solar/Wind Harmer
1.651
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.704
270227U2-072_GEN3
Solar/Wind Helper
1.995
270228U2-072_GEN4
Solar/Wind Helper
1.995
270231U2-072_GEN5
Solar/Wind Helper
1.995
270349AD2-093_GEN
Solar/Wind Helper
0.454
961051AF2-396 GEN
Solar/Wind Harmer
0.957
961051AF2-396 GEN
Solar/Wind Harmer
7.653
270599AE1-208 GEN
Solar/Wind Harmer
0.377
972231SS25-0005
Solar/Wind Harmer
0.703
971411AH1-196 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
3.454
276876AE1-163_GEN2
Solar/Wind Harmer
5.502
24386405FR-21G C
Solar/Wind Harmer
3.021
276782AC1-033 GEN
Solar/Wind Harmer
3.04
276763AC1-053 GEN1
Solar/Wind Harmer
2.764
971029AG2-637 GEN
Solar/Wind Harmer
0.481
270224U2-072_GEN2
Solar/Wind Helper
1.995
942871AE2-306 GEN
Solar/Wind Helper
0.214
945641AF1-229 GEN
Solar/Wind Helper
0.454
270541AE2-072 C
Solar/Wind Helper
0.459
970583AG2-370 GEN
50/50
2.758
965051AG1-369 GEN
Solar/Wind Harmer
0.293
970349AG2-230 GEN
Solar/Wind Harmer
0.721
971347AH1-153 GEN
Solar/Wind Harmer
0.24
961761AG1-017 GEN
Solar/Wind Harmer
0.449
960591AF2-350 GEN
Solar/Wind Harmer
0.428
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
16.272
247536S-71 GEN
Solar/Wind Harmer
3.798
926823AC1-168 GEN
Solar/Wind Harmer
4.874
274857EASY ROAD;U1
Solar/Wind Harmer
3.688
24725505WLD G2 C
Solar/Wind Harmer
3.052
276656WTG2_EQ
Solar/Wind Harmer
0.874
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.587
270462AD2-086
Solar/Wind Helper
1.788
270317AD1-130_GEN
Solar/Wind Helper
1.166
270287AF1-227 GEN3
Solar/Wind Helper
0.35
960851AF2-376 GEN
50/50
2.033
965021AG1-366 GEN
Solar/Wind Harmer
4.557
942221AE2-234 GEN
Solar/Wind Harmer
0.204
958861AF2-177 GEN
Solar/Wind Harmer
15.92
945371AF1-202 GEN
Solar/Wind Harmer
7.521
270505AE1-170 C O1
Solar/Wind Harmer
0.718
270032AE2-172
Solar/Wind Harmer
3.34
970825AG2-519 GEN
Solar/Wind Harmer
1.758
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.231
971997AH1-543 GEN
Solar/Wind Harmer
0.639
276889AE2-281 GEN
Solar/Wind Harmer
1.572
24691005MDL-2G C
Solar/Wind Harmer
3.143
971549AH1-272 GEN
Solar/Wind Harmer
0.722
276158O29GEN2
Solar/Wind Harmer
3.427
276708O09 GEN2
Solar/Wind Harmer
3.218
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.241
270543AE2-219 C
Solar/Wind Harmer
0.365
971993AH1-541 GEN
Solar/Wind Harmer
0.329
276621W2-048 GEN
Solar/Wind Harmer
5.054
942481AE2-261 GEN
Solar/Wind Harmer
1.011
270485AE1-090_GEN
Solar/Wind Helper
0.155
960861AF2-377 GEN
50/50
2.345
24729305KEY G2
50/50
6.841
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.937
957891AF2-083 GEN
Solar/Wind Harmer
0.723
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.683
274888KELLY CRK;1U
Solar/Wind Harmer
5.846
276893AG1-478 C
Solar/Wind Harmer
0.338
270005AE1-210 C O1
Solar/Wind Harmer
6.493
276602WESTBROOK C
Solar/Wind Harmer
1.703
274863CRW1-WTG
Solar/Wind Harmer
4.717
274864CRW2-WTG
Solar/Wind Harmer
4.717
276603SUBLETTE C
Solar/Wind Harmer
0.798
24387305FR-4G C
Solar/Wind Harmer
4.532
24386605FR-22G C
Solar/Wind Harmer
3.021
24387005FR-3G C
Solar/Wind Harmer
2.991
274880W4-005 GEN4
Solar/Wind Harmer
2.126
246936BC-WTG1
Solar/Wind Helper
17.073
246937BC-WTG2
Solar/Wind Helper
17.073
960841AF2-375 GEN
Solar/Wind Helper
0.563
965011AG1-365 GEN
Solar/Wind Harmer
1.139
945111AF1-176 GEN
Solar/Wind Harmer
0.876
945111AF1-176 GEN
Solar/Wind Harmer
4.774
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.668
970073AG2-061 GEN
Solar/Wind Harmer
1.641
274850MENDOTA H;RU
Solar/Wind Harmer
2.401
276863AD2-134 GEN
Solar/Wind Harmer
1.67
276861AD2-134 GEN
Solar/Wind Harmer
1.67
970571AG2-364 GEN
Solar/Wind Harmer
0.796
274856ECOGROVE ;U1
Solar/Wind Harmer
3.104
971681AH1-341 GEN
Solar/Wind Harmer
0.593
938861AE1-114 GEN
Solar/Wind Harmer
9.255
274858EASY ROAD;U2
Solar/Wind Harmer
3.688
270240V3-007_GEN2
Solar/Wind Harmer
4.477
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.353
270191TR4_S_V150
Solar/Wind Harmer
3.471
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.032
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.18
270180AB1-006 GEN1
Solar/Wind Harmer
5.658
24791305MDL-5G
Solar/Wind Harmer
2.096
276741O09 GEN1
Solar/Wind Harmer
3.218
276726Z2-087_GEN
Solar/Wind Harmer
5.982
944221AF1-090 GEN
Solar/Wind Harmer
10.146
966831AG1-554 GEN
Solar/Wind Helper
0.281
943021AE2-325 GEN
Solar/Wind Harmer
2.95
964611AG1-324 GEN
Solar/Wind Harmer
0.402
276843GEN-1.7
Solar/Wind Harmer
0.568
958011AF2-095 GEN
Solar/Wind Harmer
0.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.447
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.615
24697905MDL-4G C
Solar/Wind Harmer
2.096
970819AG2-516 GEN
Solar/Wind Harmer
0.478
276646AC1-214 GEN2
Solar/Wind Harmer
1.204
274878BISHOP HL;2U
Solar/Wind Harmer
3.016
274854TWINGROVE;U2
Solar/Wind Harmer
5.82
965091AG1-374 GEN
Solar/Wind Harmer
1.13
965931AG1-462 GEN
Solar/Wind Harmer
0.961
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.995
270499AE1-146 GEN
Solar/Wind Helper
0.544
970031AG2-029 GEN
Solar/Wind Harmer
1.74
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.381
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.278
970833AG2-524 GEN
Solar/Wind Harmer
0.463
962781AG1-127 GEN
Solar/Wind Harmer
0.389
276868AE1-113 GEN
Solar/Wind Harmer
9.54
24697605MDL-3G C
Solar/Wind Harmer
3.143
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.804
24385905FR-11G C
Solar/Wind Harmer
5.939
24729405KEY G3
50/50
6.841
24729505KEY G4
50/50
6.727
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.436
970941AG2-585 GEN
Solar/Wind Harmer
0.236
276897AD1-100 C
Solar/Wind Harmer
56.232
971605AH1-302 GEN
Solar/Wind Harmer
6.283
970825AG2-519 GEN
Solar/Wind Harmer
0.274
276805AD2-038 GEN
Solar/Wind Harmer
4.799
970569AG2-363 GEN
Solar/Wind Harmer
1.195
276157O29GEN1
Solar/Wind Harmer
3.427
276645AC1-214 GEN1
Solar/Wind Harmer
1.204
939741AE1-205 GEN
Solar/Wind Harmer
0.767
942111AE2-223 GEN
Solar/Wind Harmer
8.972
970241AG2-163 GEN
Solar/Wind Harmer
0.911
276174W4-005 GEN2
Solar/Wind Harmer
2.126
276668AB2-070 GEN1
Solar/Wind Harmer
1.825
276838X2-022 GEN2
Solar/Wind Harmer
0.188
246938BC-WTG3
Solar/Wind Helper
17.366
24727105RPMNG2
50/50
68.356
270246TR4_N_V150
Solar/Wind Harmer
1.152
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.556
970291AG2-192 GEN
Solar/Wind Harmer
0.303
274871GR RIDGE ;2U
Solar/Wind Harmer
5.335
943121AE2-341 GEN
Solar/Wind Harmer
0.627
957471AF2-041 GEN
Solar/Wind Harmer
1.206
274848CAMPGROVE;RU
Solar/Wind Harmer
4.509
276785W4-005 GEN1
Solar/Wind Harmer
2.126
276849AB2-070 GEN2
Solar/Wind Harmer
1.825
957201AF2-014 GEN
Solar/Wind Helper
3.942
270284AF1-227 GEN1
Solar/Wind Helper
0.948
270428AC2-015 C
Solar/Wind Helper
0.374
253383AE2-342_GEN
Solar/Wind Helper
0.103
24727205RPMNG3
50/50
68.356
24639705ELKHART HY
50/50
0.148
963791AG1-232 GEN
Solar/Wind Harmer
0.988
247521TR3_G114
Solar/Wind Harmer
4.555
24695305TIMB G C
Solar/Wind Harmer
3.924
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.418
276694AA1-018 GEN2
Solar/Wind Harmer
4.411
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.096
971343AH1-151 GEN
Solar/Wind Harmer
0.804
970169AG2-114 GEN
Solar/Wind Harmer
0.397
959341AF2-225 GEN
Solar/Wind Harmer
0.575
971087AG2-675 GEN
Solar/Wind Harmer
2.412
270445AC2-157 GEN2
Solar/Wind Harmer
0
24727005RPMNG1
50/50
68.356
247620Y3-023
50/50
0.46
959331AF2-224 GEN
Solar/Wind Harmer
1.139
965041AG1-368 GEN
Solar/Wind Harmer
0.69
270031AE2-169
Solar/Wind Harmer
0.377
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.661
274861TOP CROP ;1U
Solar/Wind Harmer
4.856
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.349
971067AG2-660 GEN
Solar/Wind Harmer
1.608
24699105WLD G1 C
Solar/Wind Harmer
3.052
276655WTG1_EQ
Solar/Wind Harmer
6.603
963841AG1-237 GEN
Solar/Wind Harmer
11.714
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.285
247522W1-056 GEN
Solar/Wind Helper
1.919
270286AF1-227 GEN2
Solar/Wind Helper
0.35
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.296
946321AF1-296 GEN
Solar/Wind Harmer
11.289
274853TWINGROVE;U1
Solar/Wind Harmer
5.82
959611AF2-252 GEN
Solar/Wind Harmer
1.507
960611AF2-352 GEN
Solar/Wind Harmer
1.507
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.365
970193AG2-126 GEN
Solar/Wind Harmer
0.491
958581AF2-149 GEN
Solar/Wind Helper
0.222
276872AE1-163_GEN1
Solar/Wind Harmer
5.502
959081AF2-199 GEN
Solar/Wind Harmer
0.402
274851PROVIDENC;RU
Solar/Wind Harmer
2.244
24386205FR-12G C
Solar/Wind Harmer
3.154
24379505HDWTR1G C
Solar/Wind Harmer
5.718
970885AG2-551 GEN
Solar/Wind Harmer
1.46
963741AG1-226 GEN
Solar/Wind Harmer
1.64
276686W4-005 GEN3
Solar/Wind Harmer
2.126
276764AC1-053 GEN2
Solar/Wind Harmer
2.764
276911AD2-131_GEN
Solar/Wind Harmer
0.168
970521AG2-332 GEN
50/50
10.74
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.192
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.016
276848AB2-070 GEN3
Solar/Wind Harmer
1.825
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.166
270471AD2-092_GEN
Solar/Wind Helper
0.454
276820AF1-078_GEN
Solar/Wind Helper
0.159
990792J1392
External Queue
0.3027859032154083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.873
TVALTFEXP_TVA->PJM
CLTF
2.36
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.443
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.032
WECLTFEXP_WEC->PJM
CLTF
2.627
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.255
LGEELTFEXP_LGEE->PJM
CLTF
1.795
LAGNLTFEXP_LAGN->PJM
CLTF
5.817
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.204
NYPJM->LTFIMP_NY
CLTF
1.303
MECLTFEXP_MEC->PJM
CLTF
9.641
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.06 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2242.58
MW Contribution:
0.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.018
270143AC1-141 CT2_
50/50
2.018
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
24643105BUCHANAN
50/50
0.01
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.787
24642205MAYFLWER
50/50
0.618
962601AG1-109 GEN
50/50
2.385
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
944961AF1-161 GEN
50/50
2.385
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
990792J1392
External Queue
0.30737584829330444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.53 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2230.82
MW Contribution:
0.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
990792J1392
External Queue
0.30737584829330444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.04 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2219.82
MW Contribution:
0.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
943021AE2-325 GEN
Solar/Wind Harmer
2.881
964611AG1-324 GEN
Solar/Wind Harmer
0.393
276843GEN-1.7
Solar/Wind Harmer
0.553
958011AF2-095 GEN
Solar/Wind Harmer
0.601
276691AA1-018 GEN1
Solar/Wind Harmer
0.435
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
24697905MDL-4G C
Solar/Wind Harmer
2.038
970819AG2-516 GEN
Solar/Wind Harmer
0.465
276646AC1-214 GEN2
Solar/Wind Harmer
1.17
274878BISHOP HL;2U
Solar/Wind Harmer
2.932
965931AG1-462 GEN
Solar/Wind Harmer
0.934
274854TWINGROVE;U2
Solar/Wind Harmer
5.654
965091AG1-374 GEN
Solar/Wind Harmer
1.098
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
2.097
270499AE1-146 GEN
Solar/Wind Helper
0.556
965021AG1-366 GEN
Solar/Wind Harmer
4.503
942221AE2-234 GEN
Solar/Wind Harmer
0.2
958861AF2-177 GEN
Solar/Wind Harmer
15.573
945371AF1-202 GEN
Solar/Wind Harmer
7.349
270505AE1-170 C O1
Solar/Wind Harmer
0.702
270032AE2-172
Solar/Wind Harmer
3.253
970825AG2-519 GEN
Solar/Wind Harmer
1.712
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.198
971997AH1-543 GEN
Solar/Wind Harmer
0.622
276889AE2-281 GEN
Solar/Wind Harmer
1.53
24691005MDL-2G C
Solar/Wind Harmer
3.058
971549AH1-272 GEN
Solar/Wind Harmer
0.702
276158O29GEN2
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
3.129
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.205
270543AE2-219 C
Solar/Wind Harmer
0.354
961051AF2-396 GEN
Solar/Wind Harmer
0.935
961051AF2-396 GEN
Solar/Wind Harmer
7.477
270599AE1-208 GEN
Solar/Wind Harmer
0.368
972231SS25-0005
Solar/Wind Harmer
0.685
971411AH1-196 GEN
Solar/Wind Harmer
0.591
274855GSG-6 ;RU
Solar/Wind Harmer
3.361
276876AE1-163_GEN2
Solar/Wind Harmer
5.354
24386405FR-21G C
Solar/Wind Harmer
2.936
276782AC1-033 GEN
Solar/Wind Harmer
2.956
276763AC1-053 GEN1
Solar/Wind Harmer
2.681
965651AG1-433 GEN
Solar/Wind Harmer
8.016
972181SS23-001
Solar/Wind Harmer
0.428
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.266
970289AG2-191 GEN
Solar/Wind Harmer
0.078
274847GR RIDGE ;BU
Solar/Wind Harmer
4.711
946031AF1-268 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
0.782
274849CRESCENT ;1U
Solar/Wind Harmer
1.605
957381AF2-032 GEN
Solar/Wind Harmer
0.066
276916AD2-100_GEN
Solar/Wind Harmer
0.681
270227U2-072_GEN3
Solar/Wind Helper
2.097
270228U2-072_GEN4
Solar/Wind Helper
2.097
270231U2-072_GEN5
Solar/Wind Helper
2.097
270349AD2-093_GEN
Solar/Wind Helper
0.517
971029AG2-637 GEN
Solar/Wind Harmer
0.465
270224U2-072_GEN2
Solar/Wind Helper
2.097
942871AE2-306 GEN
Solar/Wind Helper
0.225
945641AF1-229 GEN
Solar/Wind Helper
0.46
270541AE2-072 C
Solar/Wind Helper
0.478
970031AG2-029 GEN
Solar/Wind Harmer
1.71
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.032
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.144
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
276868AE1-113 GEN
Solar/Wind Harmer
9.286
24697605MDL-3G C
Solar/Wind Harmer
3.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.782
24385905FR-11G C
Solar/Wind Harmer
5.772
946321AF1-296 GEN
Solar/Wind Harmer
10.97
274853TWINGROVE;U1
Solar/Wind Harmer
5.654
959611AF2-252 GEN
Solar/Wind Harmer
1.464
960611AF2-352 GEN
Solar/Wind Harmer
1.464
270437AC2-090 C
Solar/Wind Harmer
0
960861AF2-377 GEN
50/50
2.286
24729305KEY G2
50/50
6.704
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.92
957891AF2-083 GEN
Solar/Wind Harmer
0.707
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.667
274888KELLY CRK;1U
Solar/Wind Harmer
5.697
276893AG1-478 C
Solar/Wind Harmer
0.33
270005AE1-210 C O1
Solar/Wind Harmer
6.326
276602WESTBROOK C
Solar/Wind Harmer
1.658
274863CRW1-WTG
Solar/Wind Harmer
4.59
274864CRW2-WTG
Solar/Wind Harmer
4.59
276603SUBLETTE C
Solar/Wind Harmer
0.776
24387305FR-4G C
Solar/Wind Harmer
4.404
24386605FR-22G C
Solar/Wind Harmer
2.936
24387005FR-3G C
Solar/Wind Harmer
2.906
274880W4-005 GEN4
Solar/Wind Harmer
2.063
246936BC-WTG1
Solar/Wind Helper
17.184
246937BC-WTG2
Solar/Wind Helper
17.184
960841AF2-375 GEN
Solar/Wind Helper
0.576
24727005RPMNG1
50/50
67.807
247620Y3-023
50/50
0.45
959331AF2-224 GEN
Solar/Wind Harmer
1.126
965041AG1-368 GEN
Solar/Wind Harmer
0.675
270031AE2-169
Solar/Wind Harmer
0.368
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.489
274861TOP CROP ;1U
Solar/Wind Harmer
4.729
946581AF1-322 GEN
Solar/Wind Harmer
0
970521AG2-332 GEN
50/50
10.514
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
12.855
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.782
274877BISHOP HL;1U
Solar/Wind Harmer
2.932
276848AB2-070 GEN3
Solar/Wind Harmer
1.771
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.216
270471AD2-092_GEN
Solar/Wind Helper
0.517
276820AF1-078_GEN
Solar/Wind Helper
0.166
24727205RPMNG3
50/50
67.807
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.971
247521TR3_G114
Solar/Wind Harmer
4.44
24695305TIMB G C
Solar/Wind Harmer
3.811
24729205KEY G1
50/50
6.593
270201AC2-176 GEN
Solar/Wind Harmer
4.506
970373AG2-245 GEN
Solar/Wind Harmer
0.901
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.326
274872LEEDK;1U
Solar/Wind Harmer
7.44
276872AE1-163_GEN1
Solar/Wind Harmer
5.354
959081AF2-199 GEN
Solar/Wind Harmer
0.391
274851PROVIDENC;RU
Solar/Wind Harmer
2.181
24386205FR-12G C
Solar/Wind Harmer
3.065
24379505HDWTR1G C
Solar/Wind Harmer
5.555
970885AG2-551 GEN
Solar/Wind Harmer
1.417
963741AG1-226 GEN
Solar/Wind Harmer
1.592
276686W4-005 GEN3
Solar/Wind Harmer
2.063
276764AC1-053 GEN2
Solar/Wind Harmer
2.681
276911AD2-131_GEN
Solar/Wind Harmer
0.162
24690905MDL-1G C
Solar/Wind Harmer
6.176
971067AG2-660 GEN
Solar/Wind Harmer
1.565
24699105WLD G1 C
Solar/Wind Harmer
2.968
276655WTG1_EQ
Solar/Wind Harmer
6.417
963841AG1-237 GEN
Solar/Wind Harmer
11.375
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.3
270286AF1-227 GEN2
Solar/Wind Helper
0.382
247522W1-056 GEN
Solar/Wind Helper
1.958
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.299
270191TR4_S_V150
Solar/Wind Harmer
3.383
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.91
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.095
270180AB1-006 GEN1
Solar/Wind Harmer
5.504
24791305MDL-5G
Solar/Wind Harmer
2.038
276741O09 GEN1
Solar/Wind Harmer
3.129
276726Z2-087_GEN
Solar/Wind Harmer
5.813
944221AF1-090 GEN
Solar/Wind Harmer
9.816
966831AG1-554 GEN
Solar/Wind Helper
0.286
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.053
943591AF1-030 GEN
Solar/Wind Harmer
0.407
276694AA1-018 GEN2
Solar/Wind Harmer
4.296
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.038
971343AH1-151 GEN
Solar/Wind Harmer
0.782
970169AG2-114 GEN
Solar/Wind Harmer
0.386
959341AF2-225 GEN
Solar/Wind Harmer
0.559
971087AG2-675 GEN
Solar/Wind Harmer
2.343
270445AC2-157 GEN2
Solar/Wind Harmer
0
24727105RPMNG2
50/50
67.807
270246TR4_N_V150
Solar/Wind Harmer
1.123
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.295
274871GR RIDGE ;2U
Solar/Wind Harmer
5.196
943121AE2-341 GEN
Solar/Wind Harmer
0.611
957471AF2-041 GEN
Solar/Wind Harmer
1.174
274848CAMPGROVE;RU
Solar/Wind Harmer
4.383
276785W4-005 GEN1
Solar/Wind Harmer
2.063
276849AB2-070 GEN2
Solar/Wind Harmer
1.771
957201AF2-014 GEN
Solar/Wind Helper
3.968
270284AF1-227 GEN1
Solar/Wind Helper
1.035
270428AC2-015 C
Solar/Wind Helper
0.376
253383AE2-342_GEN
Solar/Wind Helper
0.105
24729405KEY G3
50/50
6.704
24729505KEY G4
50/50
6.593
270043AE2-236 GEN
Solar/Wind Harmer
0.363
971771AH1-392 GEN
Solar/Wind Harmer
0.426
970941AG2-585 GEN
Solar/Wind Harmer
0.23
276897AD1-100 C
Solar/Wind Harmer
54.783
971605AH1-302 GEN
Solar/Wind Harmer
6.118
970825AG2-519 GEN
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
4.671
970569AG2-363 GEN
Solar/Wind Harmer
1.162
276157O29GEN1
Solar/Wind Harmer
3.332
276645AC1-214 GEN1
Solar/Wind Harmer
1.17
939741AE1-205 GEN
Solar/Wind Harmer
0.745
942111AE2-223 GEN
Solar/Wind Harmer
8.72
970241AG2-163 GEN
Solar/Wind Harmer
0.884
276174W4-005 GEN2
Solar/Wind Harmer
2.063
276668AB2-070 GEN1
Solar/Wind Harmer
1.771
276838X2-022 GEN2
Solar/Wind Harmer
0.183
246938BC-WTG3
Solar/Wind Helper
17.48
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.856
945111AF1-176 GEN
Solar/Wind Harmer
4.667
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.651
970073AG2-061 GEN
Solar/Wind Harmer
1.597
274850MENDOTA H;RU
Solar/Wind Harmer
2.337
276863AD2-134 GEN
Solar/Wind Harmer
1.625
276861AD2-134 GEN
Solar/Wind Harmer
1.625
970571AG2-364 GEN
Solar/Wind Harmer
0.775
274856ECOGROVE ;U1
Solar/Wind Harmer
3.02
971681AH1-341 GEN
Solar/Wind Harmer
0.577
938861AE1-114 GEN
Solar/Wind Harmer
9.003
274858EASY ROAD;U2
Solar/Wind Harmer
3.587
270240V3-007_GEN2
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.369
971993AH1-541 GEN
Solar/Wind Harmer
0.319
276621W2-048 GEN
Solar/Wind Harmer
4.9
942481AE2-261 GEN
Solar/Wind Harmer
0.979
970883AG2-550 GEN
Solar/Wind Harmer
0.354
970193AG2-126 GEN
Solar/Wind Harmer
0.475
958581AF2-149 GEN
Solar/Wind Helper
0.216
944531AF1-118 GEN
Solar/Wind Harmer
2.012
270247TR4_N_V136
Solar/Wind Harmer
1.123
970707AG2-453 GEN
Solar/Wind Harmer
1.161
970833AG2-524 GEN
Solar/Wind Harmer
3.609
958481AF2-142 GEN
Solar/Wind Harmer
0.607
274862TOP CROP ;2U
Solar/Wind Harmer
4.729
274879MINONK ;1U
Solar/Wind Harmer
6.19
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
276903AD2-071 C
Solar/Wind Harmer
0.388
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.786
945391AF1-204 GEN
Solar/Wind Harmer
12.593
270391AF1-285 GEN3
Solar/Wind Helper
0.3
241847AF2-150_GEN
Solar/Wind Helper
0.265
270485AE1-090_GEN
Solar/Wind Helper
0.162
970583AG2-370 GEN
50/50
2.702
965051AG1-369 GEN
Solar/Wind Harmer
0.285
970349AG2-230 GEN
Solar/Wind Harmer
0.704
971347AH1-153 GEN
Solar/Wind Harmer
0.235
961761AG1-017 GEN
Solar/Wind Harmer
0.438
960591AF2-350 GEN
Solar/Wind Harmer
0.417
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
15.839
247536S-71 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
4.742
274857EASY ROAD;U1
Solar/Wind Harmer
3.587
24725505WLD G2 C
Solar/Wind Harmer
2.968
276656WTG2_EQ
Solar/Wind Harmer
0.85
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.539
270462AD2-086
Solar/Wind Helper
1.865
270317AD1-130_GEN
Solar/Wind Helper
1.216
270287AF1-227 GEN3
Solar/Wind Helper
0.382
990792J1392
External Queue
0.3014104962348938
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.406
WECLTFEXP_WEC->PJM
CLTF
2.556
LAGNLTFEXP_LAGN->PJM
CLTF
5.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.955
LGEELTFEXP_LGEE->PJM
CLTF
1.68
MECLTFEXP_MEC->PJM
CLTF
9.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.67
NYPJM->LTFIMP_NY
CLTF
1.235
TVALTFEXP_TVA->PJM
CLTF
2.193
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.304
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
SIGELTFEXP_SIGE->PJM
CLTF
0.19

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.89 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2523.04
MW Contribution:
0.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729305KEY G2
50/50
6.183
270005AE1-210 C O1
Solar/Wind Harmer
10.924
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.745
270071AF1-092 GEN
Solar/Wind Harmer
0.507
24387305FR-4G C
Solar/Wind Harmer
3.572
24386605FR-22G C
Solar/Wind Harmer
2.381
24387005FR-3G C
Solar/Wind Harmer
2.358
274880W4-005 GEN4
Solar/Wind Harmer
1.694
274863CRW1-WTG
Solar/Wind Harmer
3.289
274864CRW2-WTG
Solar/Wind Harmer
3.289
274888KELLY CRK;1U
Solar/Wind Harmer
3.801
276893AG1-478 C
Solar/Wind Harmer
0.222
276602WESTBROOK C
Solar/Wind Harmer
1.145
276603SUBLETTE C
Solar/Wind Harmer
0.546
957891AF2-083 GEN
Solar/Wind Harmer
0.4
252510AF1-249 C
Solar/Wind Helper
0.173
253394AE2-221_GEN
Solar/Wind Helper
0.748
253398AE2-221_GEN2
Solar/Wind Helper
0.748
970291AG2-192 GEN
Solar/Wind Harmer
0.064
963791AG1-232 GEN
Solar/Wind Harmer
0.448
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
1.557
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.425
970169AG2-114 GEN
Solar/Wind Harmer
0.281
965681AG1-436 GEN
Solar/Wind Harmer
0.348
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.934
943591AF1-030 GEN
Solar/Wind Harmer
0.276
971343AH1-151 GEN
Solar/Wind Harmer
0.542
971087AG2-675 GEN
Solar/Wind Harmer
1.689
960071AF2-298 GEN
Solar/Wind Helper
0.264
253303V4-073 C
Solar/Wind Helper
0.011
241974AD2-163_GEN2
Solar/Wind Helper
0.307
253338AC1-165 GEN
Solar/Wind Helper
0.168
241955AC1-078 GEN
Solar/Wind Helper
0.57
961171AF2-408 GEN
50/50
9.476
970289AG2-191 GEN
Solar/Wind Harmer
0.645
970291AG2-192 GEN
Solar/Wind Harmer
0.352
276785W4-005 GEN1
Solar/Wind Harmer
1.694
276849AB2-070 GEN2
Solar/Wind Harmer
1.453
274871GR RIDGE ;2U
Solar/Wind Harmer
3.521
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
4.292
961761AG1-017 GEN
Solar/Wind Harmer
0.49
247536S-71 GEN
Solar/Wind Harmer
4.111
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0.646
276615X2-022 GEN
Solar/Wind Harmer
1.279
970349AG2-230 GEN
Solar/Wind Harmer
0.423
971347AH1-153 GEN
Solar/Wind Harmer
0.141
939401AE1-172 GEN
Solar/Wind Harmer
11.164
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.278
926823AC1-168 GEN
Solar/Wind Harmer
3.373
274857EASY ROAD;U1
Solar/Wind Harmer
2.516
252507AC2-088 GEN
Solar/Wind Helper
0.343
276903AD2-071 C
Solar/Wind Harmer
0.53
944531AF1-118 GEN
Solar/Wind Harmer
1.735
945391AF1-204 GEN
Solar/Wind Harmer
13.406
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.299
965911AG1-460 GEN
Solar/Wind Harmer
0.672
970707AG2-453 GEN
Solar/Wind Harmer
0.778
970833AG2-524 GEN
Solar/Wind Harmer
2.444
958481AF2-142 GEN
Solar/Wind Harmer
0.414
274862TOP CROP ;2U
Solar/Wind Harmer
3.231
274879MINONK ;1U
Solar/Wind Harmer
4.294
971675AH1-338 GEN
Solar/Wind Harmer
0.49
253406AD2-031_GEN
Solar/Wind Helper
0.233
942051AE2-217 GEN
Solar/Wind Helper
0.623
270520AE2-214 GEN
Solar/Wind Helper
0.504
24729205KEY G1
50/50
6.08
24379505HDWTR1G C
Solar/Wind Harmer
13.709
270004AE1-209 GEN
Solar/Wind Harmer
10.924
270201AC2-176 GEN
Solar/Wind Harmer
5.039
970885AG2-551 GEN
Solar/Wind Harmer
1.607
963741AG1-226 GEN
Solar/Wind Harmer
1.428
24386205FR-12G C
Solar/Wind Harmer
2.486
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.6
276686W4-005 GEN3
Solar/Wind Harmer
1.694
276764AC1-053 GEN2
Solar/Wind Harmer
2.21
276911AD2-131_GEN
Solar/Wind Harmer
0.14
276872AE1-163_GEN1
Solar/Wind Harmer
3.749
274851PROVIDENC;RU
Solar/Wind Harmer
1.576
274872LEEDK;1U
Solar/Wind Harmer
5.11
959081AF2-199 GEN
Solar/Wind Harmer
0.271
25183208HLCRTG
Solar/Wind Helper
1.145
253325AC1-069 GEN
Solar/Wind Helper
0.168
943121AE2-341 GEN
Solar/Wind Harmer
0.414
946031AF1-268 GEN
Solar/Wind Harmer
0.494
965651AG1-433 GEN
Solar/Wind Harmer
8.883
970289AG2-191 GEN
Solar/Wind Harmer
0.093
270055AF2-134 C O1
Solar/Wind Harmer
0
957381AF2-032 GEN
Solar/Wind Harmer
0.056
276916AD2-100_GEN
Solar/Wind Harmer
0.588
972207SS24-0001
Solar/Wind Harmer
0.839
972181SS23-001
Solar/Wind Harmer
0.278
274847GR RIDGE ;BU
Solar/Wind Harmer
3.192
274849CRESCENT ;1U
Solar/Wind Harmer
1.159
959091AF2-200 GEN
Solar/Wind Harmer
0.542
253333AC1-068 GEN
Solar/Wind Helper
0.168
961161AF2-407 GEN
50/50
35.642
270599AE1-208 GEN
Solar/Wind Harmer
0.444
971029AG2-637 GEN
Solar/Wind Harmer
0.537
24386405FR-21G C
Solar/Wind Harmer
2.381
276763AC1-053 GEN1
Solar/Wind Harmer
2.21
972231SS25-0005
Solar/Wind Harmer
0.445
276876AE1-163_GEN2
Solar/Wind Harmer
3.749
274855GSG-6 ;RU
Solar/Wind Harmer
2.322
276782AC1-033 GEN
Solar/Wind Harmer
2.137
971411AH1-196 GEN
Solar/Wind Harmer
0.408
961051AF2-396 GEN
Solar/Wind Harmer
0.528
961051AF2-396 GEN
Solar/Wind Harmer
4.221
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.203
24791305MDL-5G
Solar/Wind Harmer
1.557
276726Z2-087_GEN
Solar/Wind Harmer
4.417
944221AF1-090 GEN
Solar/Wind Harmer
8.719
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.063
276882AE2-255 GEN
Solar/Wind Harmer
2.147
270526AF1-158 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
2.224
270518AE2-148 GEN
Solar/Wind Helper
2.34
270340AC2-060 GEN
Solar/Wind Helper
0.401
24726805LAWG2B
50/50
3.437
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.466
24697905MDL-4G C
Solar/Wind Harmer
1.557
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.367
965091AG1-374 GEN
Solar/Wind Harmer
0.848
276843GEN-1.7
Solar/Wind Harmer
0.369
958011AF2-095 GEN
Solar/Wind Harmer
0.401
276691AA1-018 GEN1
Solar/Wind Harmer
0.297
958491AF2-143 GEN
Solar/Wind Harmer
0.413
276646AC1-214 GEN2
Solar/Wind Harmer
0.845
274878BISHOP HL;2U
Solar/Wind Harmer
2.121
970819AG2-516 GEN
Solar/Wind Harmer
0.324
965931AG1-462 GEN
Solar/Wind Harmer
0.673
943021AE2-325 GEN
Solar/Wind Harmer
1.645
241972AD1-140 GEN
Solar/Wind Helper
0.895
945631AF1-228 GEN
Solar/Wind Helper
0.524
24726405LAWG1A
50/50
3.657
270240V3-007_GEN2
Solar/Wind Harmer
10.734
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.831
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.102
970571AG2-364 GEN
Solar/Wind Harmer
0.548
274850MENDOTA H;RU
Solar/Wind Harmer
1.615
276863AD2-134 GEN
Solar/Wind Harmer
1.123
276861AD2-134 GEN
Solar/Wind Harmer
1.123
274856ECOGROVE ;U1
Solar/Wind Harmer
2.105
971681AH1-341 GEN
Solar/Wind Harmer
0.404
938861AE1-114 GEN
Solar/Wind Harmer
6.303
274858EASY ROAD;U2
Solar/Wind Harmer
2.516
945111AF1-176 GEN
Solar/Wind Harmer
0.474
945111AF1-176 GEN
Solar/Wind Harmer
2.586
253378AE2-206_GEN
Solar/Wind Helper
0.483
24726905LAWG2S
50/50
5.634
24726705LAWG2A
50/50
3.657
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
17.765
970883AG2-550 GEN
Solar/Wind Harmer
0.402
970193AG2-126 GEN
Solar/Wind Harmer
0.506
24385905FR-11G C
Solar/Wind Harmer
4.682
24697605MDL-3G C
Solar/Wind Harmer
2.335
270181AB1-006 GEN2
Solar/Wind Harmer
0.467
274853TWINGROVE;U1
Solar/Wind Harmer
4.367
959611AF2-252 GEN
Solar/Wind Harmer
1.131
960611AF2-352 GEN
Solar/Wind Harmer
1.131
274887GEN-1.85
Solar/Wind Harmer
3.432
970833AG2-524 GEN
Solar/Wind Harmer
0.305
276868AE1-113 GEN
Solar/Wind Harmer
6.441
962781AG1-127 GEN
Solar/Wind Harmer
0.26
970031AG2-029 GEN
Solar/Wind Harmer
0.678
971171AH1-044 GEN
Solar/Wind Harmer
0.542
270063AE2-323 C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
7.882
253415AE1-040 GEN
Solar/Wind Helper
0.17
24726505LAWG1B
50/50
3.657
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.975
945371AF1-202 GEN
Solar/Wind Harmer
9.688
970825AG2-519 GEN
Solar/Wind Harmer
2.573
958861AF2-177 GEN
Solar/Wind Harmer
18.319
270032AE2-172
Solar/Wind Harmer
4.154
942221AE2-234 GEN
Solar/Wind Harmer
0.15
270543AE2-219 C
Solar/Wind Harmer
0.402
24691005MDL-2G C
Solar/Wind Harmer
2.335
957841AF2-078 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
0.262
276621W2-048 GEN
Solar/Wind Harmer
4.073
942481AE2-261 GEN
Solar/Wind Harmer
0.837
971997AH1-543 GEN
Solar/Wind Harmer
0.434
276889AE2-281 GEN
Solar/Wind Harmer
1.071
962691AG1-118 GEN
Solar/Wind Harmer
0.82
276158O29GEN2
Solar/Wind Harmer
2.368
276708O09 GEN2
Solar/Wind Harmer
2.224
270505AE1-170 C O1
Solar/Wind Harmer
0.399
270367AC2-061_GEN
Solar/Wind Helper
0.535
962581AG1-107 GEN
Solar/Wind Helper
0.634
24726605LAWG1S
50/50
5.634
24729405KEY G3
50/50
6.183
24729505KEY G4
50/50
6.08
970825AG2-519 GEN
Solar/Wind Harmer
0.402
970241AG2-163 GEN
Solar/Wind Harmer
0.793
270043AE2-236 GEN
Solar/Wind Harmer
0.17
971605AH1-302 GEN
Solar/Wind Harmer
4.401
276174W4-005 GEN2
Solar/Wind Harmer
1.694
276668AB2-070 GEN1
Solar/Wind Harmer
1.453
939741AE1-205 GEN
Solar/Wind Harmer
0.566
942111AE2-223 GEN
Solar/Wind Harmer
6.625
276838X2-022 GEN2
Solar/Wind Harmer
0.152
276897AD1-100 C
Solar/Wind Harmer
37.041
970941AG2-585 GEN
Solar/Wind Harmer
0.153
276805AD2-038 GEN
Solar/Wind Harmer
3.224
970569AG2-363 GEN
Solar/Wind Harmer
0.822
276645AC1-214 GEN1
Solar/Wind Harmer
0.845
971771AH1-392 GEN
Solar/Wind Harmer
0.246
276157O29GEN1
Solar/Wind Harmer
2.368
961491AF2-440 GEN
Solar/Wind Helper
0.211
25194708EBND2
50/50
6.217
24699105WLD G1 C
Solar/Wind Harmer
4.292
270031AE2-169
Solar/Wind Harmer
0.444
270383AD1-128 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
9.721
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.717
971917AH1-482 GEN
Solar/Wind Harmer
4.53
276655WTG1_EQ
Solar/Wind Harmer
4.876
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.231
971067AG2-660 GEN
Solar/Wind Harmer
1.085
252509AD1-136 GEN
Solar/Wind Helper
0.049
270186AC1-089 GEN
Solar/Wind Helper
0.595
946101AF1-275 GEN
Solar/Wind Helper
0.126
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.453
276806AD2-047 C O1
Solar/Wind Harmer
8.577
274877BISHOP HL;1U
Solar/Wind Harmer
2.121
971341AH1-150 GEN
Solar/Wind Harmer
0.542
276820AF1-078_GEN
Solar/Wind Helper
0.217
253316AC1-085 GEN3
Solar/Wind Helper
0.701
253433AC1-085 GEN1
Solar/Wind Helper
0.444
253349AC2-067 GEN
Solar/Wind Helper
0.2
253343AC1-166 GEN
Solar/Wind Helper
0.168
274848CAMPGROVE;RU
Solar/Wind Harmer
3.187
957471AF2-041 GEN
Solar/Wind Harmer
0.814
270449AD2-020 GEN
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Helper
0.57
253317AC1-085 GEN4
Solar/Wind Helper
0.701
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253400AC2-068 GEN
Solar/Wind Helper
0.08
253383AE2-342_GEN
Solar/Wind Helper
0.141
241973AD2-163_GEN1
Solar/Wind Helper
0.307
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.797
NYPJM->LTFIMP_NY
CLTF
0.737
MECLTFEXP_MEC->PJM
CLTF
7.099
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.474
TVALTFEXP_TVA->PJM
CLTF
1.881
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.163
WECLTFEXP_WEC->PJM
CLTF
1.772
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.45
LGEELTFEXP_LGEE->PJM
CLTF
1.395
LAGNLTFEXP_LAGN->PJM
CLTF
4.67

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.9 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2499.98
MW Contribution:
0.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729305KEY G2
50/50
6.222
270005AE1-210 C O1
Solar/Wind Harmer
10.966
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.75
270071AF1-092 GEN
Solar/Wind Harmer
0.512
24387305FR-4G C
Solar/Wind Harmer
3.589
24386605FR-22G C
Solar/Wind Harmer
2.392
24387005FR-3G C
Solar/Wind Harmer
2.368
274880W4-005 GEN4
Solar/Wind Harmer
1.7
274863CRW1-WTG
Solar/Wind Harmer
3.307
274864CRW2-WTG
Solar/Wind Harmer
3.307
274888KELLY CRK;1U
Solar/Wind Harmer
3.828
276893AG1-478 C
Solar/Wind Harmer
0.224
276602WESTBROOK C
Solar/Wind Harmer
1.152
276603SUBLETTE C
Solar/Wind Harmer
0.548
957891AF2-083 GEN
Solar/Wind Harmer
0.404
252510AF1-249 C
Solar/Wind Helper
0.172
253394AE2-221_GEN
Solar/Wind Helper
0.74
253398AE2-221_GEN2
Solar/Wind Helper
0.74
946031AF1-268 GEN
Solar/Wind Harmer
0.497
965651AG1-433 GEN
Solar/Wind Harmer
8.932
970289AG2-191 GEN
Solar/Wind Harmer
0.093
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
0.845
957381AF2-032 GEN
Solar/Wind Harmer
0.056
276916AD2-100_GEN
Solar/Wind Harmer
0.589
972181SS23-001
Solar/Wind Harmer
0.28
274847GR RIDGE ;BU
Solar/Wind Harmer
3.213
274849CRESCENT ;1U
Solar/Wind Harmer
1.165
959091AF2-200 GEN
Solar/Wind Harmer
0.545
253333AC1-068 GEN
Solar/Wind Helper
0.163
970291AG2-192 GEN
Solar/Wind Harmer
0.064
963791AG1-232 GEN
Solar/Wind Harmer
0.455
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
1.565
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.427
970169AG2-114 GEN
Solar/Wind Harmer
0.283
965681AG1-436 GEN
Solar/Wind Harmer
0.351
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.953
943591AF1-030 GEN
Solar/Wind Harmer
0.277
971343AH1-151 GEN
Solar/Wind Harmer
0.545
971087AG2-675 GEN
Solar/Wind Harmer
1.697
960071AF2-298 GEN
Solar/Wind Helper
0.261
253303V4-073 C
Solar/Wind Helper
0.01
253338AC1-165 GEN
Solar/Wind Helper
0.163
241974AD2-163_GEN2
Solar/Wind Helper
0.292
241955AC1-078 GEN
Solar/Wind Helper
0.54
24729205KEY G1
50/50
6.119
24379505HDWTR1G C
Solar/Wind Harmer
13.75
270004AE1-209 GEN
Solar/Wind Harmer
10.966
270201AC2-176 GEN
Solar/Wind Harmer
5.072
970885AG2-551 GEN
Solar/Wind Harmer
1.621
963741AG1-226 GEN
Solar/Wind Harmer
1.434
24386205FR-12G C
Solar/Wind Harmer
2.498
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.604
276686W4-005 GEN3
Solar/Wind Harmer
1.7
276764AC1-053 GEN2
Solar/Wind Harmer
2.217
276911AD2-131_GEN
Solar/Wind Harmer
0.14
276872AE1-163_GEN1
Solar/Wind Harmer
3.771
274872LEEDK;1U
Solar/Wind Harmer
5.14
274851PROVIDENC;RU
Solar/Wind Harmer
1.584
959081AF2-199 GEN
Solar/Wind Harmer
0.273
25183208HLCRTG
Solar/Wind Helper
1.139
253325AC1-069 GEN
Solar/Wind Helper
0.163
961171AF2-408 GEN
50/50
9.509
24728605AND G2
50/50
4.239
970289AG2-191 GEN
Solar/Wind Harmer
0.648
970291AG2-192 GEN
Solar/Wind Harmer
0.353
276785W4-005 GEN1
Solar/Wind Harmer
1.7
276849AB2-070 GEN2
Solar/Wind Harmer
1.459
274871GR RIDGE ;2U
Solar/Wind Harmer
3.544
943121AE2-341 GEN
Solar/Wind Harmer
0.416
274848CAMPGROVE;RU
Solar/Wind Harmer
3.202
957471AF2-041 GEN
Solar/Wind Harmer
0.818
270449AD2-020 GEN
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Helper
0.568
24726405LAWG1A
50/50
3.661
270240V3-007_GEN2
Solar/Wind Harmer
10.766
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.835
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.109
970571AG2-364 GEN
Solar/Wind Harmer
0.551
274850MENDOTA H;RU
Solar/Wind Harmer
1.624
276863AD2-134 GEN
Solar/Wind Harmer
1.129
276861AD2-134 GEN
Solar/Wind Harmer
1.129
274856ECOGROVE ;U1
Solar/Wind Harmer
2.116
971681AH1-341 GEN
Solar/Wind Harmer
0.406
938861AE1-114 GEN
Solar/Wind Harmer
6.337
274858EASY ROAD;U2
Solar/Wind Harmer
2.53
945111AF1-176 GEN
Solar/Wind Harmer
0.48
945111AF1-176 GEN
Solar/Wind Harmer
2.617
253378AE2-206_GEN
Solar/Wind Helper
0.471
253317AC1-085 GEN4
Solar/Wind Helper
0.695
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253400AC2-068 GEN
Solar/Wind Helper
0.079
253383AE2-342_GEN
Solar/Wind Helper
0.134
241973AD2-163_GEN1
Solar/Wind Helper
0.292
961161AF2-407 GEN
50/50
35.759
270599AE1-208 GEN
Solar/Wind Harmer
0.447
971029AG2-637 GEN
Solar/Wind Harmer
0.542
24386405FR-21G C
Solar/Wind Harmer
2.392
276763AC1-053 GEN1
Solar/Wind Harmer
2.217
972231SS25-0005
Solar/Wind Harmer
0.449
276876AE1-163_GEN2
Solar/Wind Harmer
3.771
274855GSG-6 ;RU
Solar/Wind Harmer
2.336
971411AH1-196 GEN
Solar/Wind Harmer
0.41
276782AC1-033 GEN
Solar/Wind Harmer
2.148
961051AF2-396 GEN
Solar/Wind Harmer
0.534
961051AF2-396 GEN
Solar/Wind Harmer
4.273
276903AD2-071 C
Solar/Wind Harmer
0.532
944531AF1-118 GEN
Solar/Wind Harmer
1.747
945391AF1-204 GEN
Solar/Wind Harmer
13.441
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.301
965911AG1-460 GEN
Solar/Wind Harmer
0.674
970707AG2-453 GEN
Solar/Wind Harmer
0.783
970833AG2-524 GEN
Solar/Wind Harmer
2.46
958481AF2-142 GEN
Solar/Wind Harmer
0.417
274862TOP CROP ;2U
Solar/Wind Harmer
3.251
274879MINONK ;1U
Solar/Wind Harmer
4.319
971675AH1-338 GEN
Solar/Wind Harmer
0.492
253406AD2-031_GEN
Solar/Wind Helper
0.23
942051AE2-217 GEN
Solar/Wind Helper
0.597
24728705AND G3
50/50
8.972
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
4.31
961761AG1-017 GEN
Solar/Wind Harmer
0.493
247536S-71 GEN
Solar/Wind Harmer
4.144
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.427
971347AH1-153 GEN
Solar/Wind Harmer
0.142
276656WTG2_EQ
Solar/Wind Harmer
0.649
276615X2-022 GEN
Solar/Wind Harmer
1.283
939401AE1-172 GEN
Solar/Wind Harmer
11.231
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.28
926823AC1-168 GEN
Solar/Wind Harmer
3.391
274857EASY ROAD;U1
Solar/Wind Harmer
2.53
252507AC2-088 GEN
Solar/Wind Helper
0.342
24726905LAWG2S
50/50
5.641
24726705LAWG2A
50/50
3.661
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
17.863
970883AG2-550 GEN
Solar/Wind Harmer
0.405
970193AG2-126 GEN
Solar/Wind Harmer
0.507
24385905FR-11G C
Solar/Wind Harmer
4.703
24697605MDL-3G C
Solar/Wind Harmer
2.347
270181AB1-006 GEN2
Solar/Wind Harmer
0.469
274853TWINGROVE;U1
Solar/Wind Harmer
4.386
959611AF2-252 GEN
Solar/Wind Harmer
1.136
960611AF2-352 GEN
Solar/Wind Harmer
1.136
274887GEN-1.85
Solar/Wind Harmer
3.456
970833AG2-524 GEN
Solar/Wind Harmer
0.307
276868AE1-113 GEN
Solar/Wind Harmer
6.479
970031AG2-029 GEN
Solar/Wind Harmer
0.688
962781AG1-127 GEN
Solar/Wind Harmer
0.261
971171AH1-044 GEN
Solar/Wind Harmer
0.545
270063AE2-323 C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
7.918
253415AE1-040 GEN
Solar/Wind Helper
0.167
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.225
24791305MDL-5G
Solar/Wind Harmer
1.565
276726Z2-087_GEN
Solar/Wind Harmer
4.438
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.091
944221AF1-090 GEN
Solar/Wind Harmer
8.739
270526AF1-158 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
2.16
276741O09 GEN1
Solar/Wind Harmer
2.235
270518AE2-148 GEN
Solar/Wind Helper
2.274
270340AC2-060 GEN
Solar/Wind Helper
0.395
24726805LAWG2B
50/50
3.441
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.469
24697905MDL-4G C
Solar/Wind Harmer
1.565
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.386
965091AG1-374 GEN
Solar/Wind Harmer
0.852
276843GEN-1.7
Solar/Wind Harmer
0.372
958011AF2-095 GEN
Solar/Wind Harmer
0.404
276691AA1-018 GEN1
Solar/Wind Harmer
0.299
958491AF2-143 GEN
Solar/Wind Harmer
0.416
276646AC1-214 GEN2
Solar/Wind Harmer
0.85
274878BISHOP HL;2U
Solar/Wind Harmer
2.131
970819AG2-516 GEN
Solar/Wind Harmer
0.326
943021AE2-325 GEN
Solar/Wind Harmer
1.665
965931AG1-462 GEN
Solar/Wind Harmer
0.676
241972AD1-140 GEN
Solar/Wind Helper
0.878
945631AF1-228 GEN
Solar/Wind Helper
0.503
25194708EBND2
50/50
6.232
24699105WLD G1 C
Solar/Wind Harmer
4.31
270031AE2-169
Solar/Wind Harmer
0.447
270383AD1-128 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
9.762
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.741
971917AH1-482 GEN
Solar/Wind Harmer
4.561
276655WTG1_EQ
Solar/Wind Harmer
4.899
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.251
971067AG2-660 GEN
Solar/Wind Harmer
1.091
252509AD1-136 GEN
Solar/Wind Helper
0.049
270186AC1-089 GEN
Solar/Wind Helper
0.593
24726505LAWG1B
50/50
3.661
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.984
945371AF1-202 GEN
Solar/Wind Harmer
9.734
970825AG2-519 GEN
Solar/Wind Harmer
2.585
958861AF2-177 GEN
Solar/Wind Harmer
18.415
270032AE2-172
Solar/Wind Harmer
4.174
942221AE2-234 GEN
Solar/Wind Harmer
0.151
270543AE2-219 C
Solar/Wind Harmer
0.405
24691005MDL-2G C
Solar/Wind Harmer
2.347
957841AF2-078 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
0.263
276621W2-048 GEN
Solar/Wind Harmer
4.087
942481AE2-261 GEN
Solar/Wind Harmer
0.839
971997AH1-543 GEN
Solar/Wind Harmer
0.437
276889AE2-281 GEN
Solar/Wind Harmer
1.077
962691AG1-118 GEN
Solar/Wind Harmer
0.825
276158O29GEN2
Solar/Wind Harmer
2.38
276708O09 GEN2
Solar/Wind Harmer
2.235
270505AE1-170 C O1
Solar/Wind Harmer
0.404
270367AC2-061_GEN
Solar/Wind Helper
0.533
962581AG1-107 GEN
Solar/Wind Helper
0.631
24728505AND G1
50/50
4.239
247621Y3-024
50/50
0.287
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.459
276806AD2-047 C O1
Solar/Wind Harmer
8.636
274877BISHOP HL;1U
Solar/Wind Harmer
2.131
971341AH1-150 GEN
Solar/Wind Harmer
0.545
276820AF1-078_GEN
Solar/Wind Helper
0.212
253316AC1-085 GEN3
Solar/Wind Helper
0.695
253433AC1-085 GEN1
Solar/Wind Helper
0.44
253349AC2-067 GEN
Solar/Wind Helper
0.197
253343AC1-166 GEN
Solar/Wind Helper
0.163
24726605LAWG1S
50/50
5.641
24729405KEY G3
50/50
6.222
24729505KEY G4
50/50
6.119
970825AG2-519 GEN
Solar/Wind Harmer
0.404
970241AG2-163 GEN
Solar/Wind Harmer
0.796
270043AE2-236 GEN
Solar/Wind Harmer
0.172
971605AH1-302 GEN
Solar/Wind Harmer
4.428
276174W4-005 GEN2
Solar/Wind Harmer
1.7
276668AB2-070 GEN1
Solar/Wind Harmer
1.459
939741AE1-205 GEN
Solar/Wind Harmer
0.569
942111AE2-223 GEN
Solar/Wind Harmer
6.657
276838X2-022 GEN2
Solar/Wind Harmer
0.152
276897AD1-100 C
Solar/Wind Harmer
37.287
970941AG2-585 GEN
Solar/Wind Harmer
0.154
276805AD2-038 GEN
Solar/Wind Harmer
3.244
971771AH1-392 GEN
Solar/Wind Harmer
0.248
970569AG2-363 GEN
Solar/Wind Harmer
0.827
276645AC1-214 GEN1
Solar/Wind Harmer
0.85
276157O29GEN1
Solar/Wind Harmer
2.38
961491AF2-440 GEN
Solar/Wind Helper
0.21
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.002
WECLTFEXP_WEC->PJM
CLTF
1.782
LAGNLTFEXP_LAGN->PJM
CLTF
4.587
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.192
LGEELTFEXP_LGEE->PJM
CLTF
1.394
MECLTFEXP_MEC->PJM
CLTF
7.114
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.33
NYPJM->LTFIMP_NY
CLTF
0.729
TVALTFEXP_TVA->PJM
CLTF
1.829
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.213
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053
SIGELTFEXP_SIGE->PJM
CLTF
0.233

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.01 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2479.49
MW Contribution:
0.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729305KEY G2
50/50
6.222
270005AE1-210 C O1
Solar/Wind Harmer
10.966
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.75
270071AF1-092 GEN
Solar/Wind Harmer
0.512
24387305FR-4G C
Solar/Wind Harmer
3.589
24386605FR-22G C
Solar/Wind Harmer
2.392
24387005FR-3G C
Solar/Wind Harmer
2.368
274880W4-005 GEN4
Solar/Wind Harmer
1.7
274863CRW1-WTG
Solar/Wind Harmer
3.307
970291AG2-192 GEN
Solar/Wind Harmer
0.064
963791AG1-232 GEN
Solar/Wind Harmer
0.455
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
1.565
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.427
970169AG2-114 GEN
Solar/Wind Harmer
0.283
965681AG1-436 GEN
Solar/Wind Harmer
0.351
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.953
943591AF1-030 GEN
Solar/Wind Harmer
0.277
971343AH1-151 GEN
Solar/Wind Harmer
0.545
971087AG2-675 GEN
Solar/Wind Harmer
1.697
960071AF2-298 GEN
Solar/Wind Helper
0.261
253303V4-073 C
Solar/Wind Helper
0.01
253338AC1-165 GEN
Solar/Wind Helper
0.163
241974AD2-163_GEN2
Solar/Wind Helper
0.292
241955AC1-078 GEN
Solar/Wind Helper
0.54
274864CRW2-WTG
Solar/Wind Harmer
3.307
274888KELLY CRK;1U
Solar/Wind Harmer
3.828
276893AG1-478 C
Solar/Wind Harmer
0.224
276602WESTBROOK C
Solar/Wind Harmer
1.152
276603SUBLETTE C
Solar/Wind Harmer
0.548
957891AF2-083 GEN
Solar/Wind Harmer
0.404
252510AF1-249 C
Solar/Wind Helper
0.172
253394AE2-221_GEN
Solar/Wind Helper
0.74
253398AE2-221_GEN2
Solar/Wind Helper
0.74
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
4.31
961761AG1-017 GEN
Solar/Wind Harmer
0.493
247536S-71 GEN
Solar/Wind Harmer
4.144
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.427
971347AH1-153 GEN
Solar/Wind Harmer
0.142
276656WTG2_EQ
Solar/Wind Harmer
0.649
276615X2-022 GEN
Solar/Wind Harmer
1.283
939401AE1-172 GEN
Solar/Wind Harmer
11.231
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.28
926823AC1-168 GEN
Solar/Wind Harmer
3.391
274857EASY ROAD;U1
Solar/Wind Harmer
2.53
252507AC2-088 GEN
Solar/Wind Helper
0.342
276903AD2-071 C
Solar/Wind Harmer
0.532
944531AF1-118 GEN
Solar/Wind Harmer
1.747
945391AF1-204 GEN
Solar/Wind Harmer
13.441
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.301
965911AG1-460 GEN
Solar/Wind Harmer
0.674
970707AG2-453 GEN
Solar/Wind Harmer
0.783
970833AG2-524 GEN
Solar/Wind Harmer
2.46
958481AF2-142 GEN
Solar/Wind Harmer
0.417
274862TOP CROP ;2U
Solar/Wind Harmer
3.251
274879MINONK ;1U
Solar/Wind Harmer
4.319
971675AH1-338 GEN
Solar/Wind Harmer
0.492
253406AD2-031_GEN
Solar/Wind Helper
0.23
942051AE2-217 GEN
Solar/Wind Helper
0.597
24729205KEY G1
50/50
6.119
24379505HDWTR1G C
Solar/Wind Harmer
13.75
270004AE1-209 GEN
Solar/Wind Harmer
10.966
270201AC2-176 GEN
Solar/Wind Harmer
5.072
970885AG2-551 GEN
Solar/Wind Harmer
1.621
963741AG1-226 GEN
Solar/Wind Harmer
1.434
24386205FR-12G C
Solar/Wind Harmer
2.498
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.604
276686W4-005 GEN3
Solar/Wind Harmer
1.7
276764AC1-053 GEN2
Solar/Wind Harmer
2.217
276911AD2-131_GEN
Solar/Wind Harmer
0.14
276872AE1-163_GEN1
Solar/Wind Harmer
3.771
274872LEEDK;1U
Solar/Wind Harmer
5.14
274851PROVIDENC;RU
Solar/Wind Harmer
1.584
959081AF2-199 GEN
Solar/Wind Harmer
0.273
25183208HLCRTG
Solar/Wind Helper
1.139
253325AC1-069 GEN
Solar/Wind Helper
0.163
946031AF1-268 GEN
Solar/Wind Harmer
0.497
965651AG1-433 GEN
Solar/Wind Harmer
8.932
970289AG2-191 GEN
Solar/Wind Harmer
0.093
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
0.845
957381AF2-032 GEN
Solar/Wind Harmer
0.056
276916AD2-100_GEN
Solar/Wind Harmer
0.589
972181SS23-001
Solar/Wind Harmer
0.28
274847GR RIDGE ;BU
Solar/Wind Harmer
3.213
274849CRESCENT ;1U
Solar/Wind Harmer
1.165
959091AF2-200 GEN
Solar/Wind Harmer
0.545
253333AC1-068 GEN
Solar/Wind Helper
0.163
961161AF2-407 GEN
50/50
35.759
270599AE1-208 GEN
Solar/Wind Harmer
0.447
971029AG2-637 GEN
Solar/Wind Harmer
0.542
24386405FR-21G C
Solar/Wind Harmer
2.392
276763AC1-053 GEN1
Solar/Wind Harmer
2.217
972231SS25-0005
Solar/Wind Harmer
0.449
276876AE1-163_GEN2
Solar/Wind Harmer
3.771
274855GSG-6 ;RU
Solar/Wind Harmer
2.336
971411AH1-196 GEN
Solar/Wind Harmer
0.41
276782AC1-033 GEN
Solar/Wind Harmer
2.148
961051AF2-396 GEN
Solar/Wind Harmer
0.534
961051AF2-396 GEN
Solar/Wind Harmer
4.273
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.225
24791305MDL-5G
Solar/Wind Harmer
1.565
276726Z2-087_GEN
Solar/Wind Harmer
4.438
24726805LAWG2B
50/50
3.441
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.469
24697905MDL-4G C
Solar/Wind Harmer
1.565
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.386
965091AG1-374 GEN
Solar/Wind Harmer
0.852
276843GEN-1.7
Solar/Wind Harmer
0.372
958011AF2-095 GEN
Solar/Wind Harmer
0.404
276691AA1-018 GEN1
Solar/Wind Harmer
0.299
958491AF2-143 GEN
Solar/Wind Harmer
0.416
276646AC1-214 GEN2
Solar/Wind Harmer
0.85
274878BISHOP HL;2U
Solar/Wind Harmer
2.131
970819AG2-516 GEN
Solar/Wind Harmer
0.326
943021AE2-325 GEN
Solar/Wind Harmer
1.665
965931AG1-462 GEN
Solar/Wind Harmer
0.676
241972AD1-140 GEN
Solar/Wind Helper
0.878
945631AF1-228 GEN
Solar/Wind Helper
0.503
24726405LAWG1A
50/50
3.661
270240V3-007_GEN2
Solar/Wind Harmer
10.766
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.835
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.109
970571AG2-364 GEN
Solar/Wind Harmer
0.551
274850MENDOTA H;RU
Solar/Wind Harmer
1.624
276863AD2-134 GEN
Solar/Wind Harmer
1.129
276861AD2-134 GEN
Solar/Wind Harmer
1.129
274856ECOGROVE ;U1
Solar/Wind Harmer
2.116
971681AH1-341 GEN
Solar/Wind Harmer
0.406
938861AE1-114 GEN
Solar/Wind Harmer
6.337
274858EASY ROAD;U2
Solar/Wind Harmer
2.53
945111AF1-176 GEN
Solar/Wind Harmer
0.48
945111AF1-176 GEN
Solar/Wind Harmer
2.617
253378AE2-206_GEN
Solar/Wind Helper
0.471
24726905LAWG2S
50/50
5.641
24726705LAWG2A
50/50
3.661
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
17.863
970883AG2-550 GEN
Solar/Wind Harmer
0.405
970193AG2-126 GEN
Solar/Wind Harmer
0.507
24385905FR-11G C
Solar/Wind Harmer
4.703
24697605MDL-3G C
Solar/Wind Harmer
2.347
270181AB1-006 GEN2
Solar/Wind Harmer
0.469
274853TWINGROVE;U1
Solar/Wind Harmer
4.386
959611AF2-252 GEN
Solar/Wind Harmer
1.136
960611AF2-352 GEN
Solar/Wind Harmer
1.136
274887GEN-1.85
Solar/Wind Harmer
3.456
970833AG2-524 GEN
Solar/Wind Harmer
0.307
276868AE1-113 GEN
Solar/Wind Harmer
6.479
970031AG2-029 GEN
Solar/Wind Harmer
0.688
962781AG1-127 GEN
Solar/Wind Harmer
0.261
971171AH1-044 GEN
Solar/Wind Harmer
0.545
270063AE2-323 C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
7.918
253415AE1-040 GEN
Solar/Wind Helper
0.167
24726505LAWG1B
50/50
3.661
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.984
945371AF1-202 GEN
Solar/Wind Harmer
9.734
970825AG2-519 GEN
Solar/Wind Harmer
2.585
958861AF2-177 GEN
Solar/Wind Harmer
18.415
270032AE2-172
Solar/Wind Harmer
4.174
942221AE2-234 GEN
Solar/Wind Harmer
0.151
270543AE2-219 C
Solar/Wind Harmer
0.405
24691005MDL-2G C
Solar/Wind Harmer
2.347
957841AF2-078 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
0.263
276621W2-048 GEN
Solar/Wind Harmer
4.087
942481AE2-261 GEN
Solar/Wind Harmer
0.839
971997AH1-543 GEN
Solar/Wind Harmer
0.437
276889AE2-281 GEN
Solar/Wind Harmer
1.077
962691AG1-118 GEN
Solar/Wind Harmer
0.825
276158O29GEN2
Solar/Wind Harmer
2.38
276708O09 GEN2
Solar/Wind Harmer
2.235
270505AE1-170 C O1
Solar/Wind Harmer
0.404
270367AC2-061_GEN
Solar/Wind Helper
0.533
962581AG1-107 GEN
Solar/Wind Helper
0.631
24726605LAWG1S
50/50
5.641
24729405KEY G3
50/50
6.222
24729505KEY G4
50/50
6.119
970825AG2-519 GEN
Solar/Wind Harmer
0.404
970241AG2-163 GEN
Solar/Wind Harmer
0.796
270043AE2-236 GEN
Solar/Wind Harmer
0.172
971605AH1-302 GEN
Solar/Wind Harmer
4.428
276174W4-005 GEN2
Solar/Wind Harmer
1.7
276668AB2-070 GEN1
Solar/Wind Harmer
1.459
939741AE1-205 GEN
Solar/Wind Harmer
0.569
942111AE2-223 GEN
Solar/Wind Harmer
6.657
276838X2-022 GEN2
Solar/Wind Harmer
0.152
276897AD1-100 C
Solar/Wind Harmer
37.287
970941AG2-585 GEN
Solar/Wind Harmer
0.154
276805AD2-038 GEN
Solar/Wind Harmer
3.244
971771AH1-392 GEN
Solar/Wind Harmer
0.248
970569AG2-363 GEN
Solar/Wind Harmer
0.827
276645AC1-214 GEN1
Solar/Wind Harmer
0.85
276157O29GEN1
Solar/Wind Harmer
2.38
961491AF2-440 GEN
Solar/Wind Helper
0.21
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.091
944221AF1-090 GEN
Solar/Wind Harmer
8.739
270526AF1-158 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
2.16
276741O09 GEN1
Solar/Wind Harmer
2.235
270518AE2-148 GEN
Solar/Wind Helper
2.274
270340AC2-060 GEN
Solar/Wind Helper
0.395
25194708EBND2
50/50
6.232
24699105WLD G1 C
Solar/Wind Harmer
4.31
270031AE2-169
Solar/Wind Harmer
0.447
270383AD1-128 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
9.762
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.741
971917AH1-482 GEN
Solar/Wind Harmer
4.561
276655WTG1_EQ
Solar/Wind Harmer
4.899
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.251
971067AG2-660 GEN
Solar/Wind Harmer
1.091
252509AD1-136 GEN
Solar/Wind Helper
0.049
270186AC1-089 GEN
Solar/Wind Helper
0.593
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.459
276806AD2-047 C O1
Solar/Wind Harmer
8.636
274877BISHOP HL;1U
Solar/Wind Harmer
2.131
971341AH1-150 GEN
Solar/Wind Harmer
0.545
276820AF1-078_GEN
Solar/Wind Helper
0.212
253316AC1-085 GEN3
Solar/Wind Helper
0.695
253433AC1-085 GEN1
Solar/Wind Helper
0.44
253349AC2-067 GEN
Solar/Wind Helper
0.197
253343AC1-166 GEN
Solar/Wind Helper
0.163
961171AF2-408 GEN
50/50
9.509
970289AG2-191 GEN
Solar/Wind Harmer
0.648
970291AG2-192 GEN
Solar/Wind Harmer
0.353
276785W4-005 GEN1
Solar/Wind Harmer
1.7
276849AB2-070 GEN2
Solar/Wind Harmer
1.459
274871GR RIDGE ;2U
Solar/Wind Harmer
3.544
943121AE2-341 GEN
Solar/Wind Harmer
0.416
274848CAMPGROVE;RU
Solar/Wind Harmer
3.202
957471AF2-041 GEN
Solar/Wind Harmer
0.818
270449AD2-020 GEN
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Helper
0.568
253317AC1-085 GEN4
Solar/Wind Helper
0.695
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253400AC2-068 GEN
Solar/Wind Helper
0.079
253383AE2-342_GEN
Solar/Wind Helper
0.134
241973AD2-163_GEN1
Solar/Wind Helper
0.292
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.213
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.002
WECLTFEXP_WEC->PJM
CLTF
1.782
LAGNLTFEXP_LAGN->PJM
CLTF
4.587
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.192
LGEELTFEXP_LGEE->PJM
CLTF
1.394
MECLTFEXP_MEC->PJM
CLTF
7.114
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.33
NYPJM->LTFIMP_NY
CLTF
0.729
TVALTFEXP_TVA->PJM
CLTF
1.829
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.01 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2479.4
MW Contribution:
0.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970291AG2-192 GEN
Solar/Wind Harmer
0.063
963791AG1-232 GEN
Solar/Wind Harmer
0.447
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
1.546
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.421
970169AG2-114 GEN
Solar/Wind Harmer
0.279
965681AG1-436 GEN
Solar/Wind Harmer
0.346
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.913
943591AF1-030 GEN
Solar/Wind Harmer
0.274
971343AH1-151 GEN
Solar/Wind Harmer
0.538
971087AG2-675 GEN
Solar/Wind Harmer
1.675
960071AF2-298 GEN
Solar/Wind Helper
0.263
253303V4-073 C
Solar/Wind Helper
0.011
241974AD2-163_GEN2
Solar/Wind Helper
0.3
253338AC1-165 GEN
Solar/Wind Helper
0.165
241955AC1-078 GEN
Solar/Wind Helper
0.553
24729305KEY G2
50/50
6.167
270005AE1-210 C O1
Solar/Wind Harmer
10.901
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.744
270071AF1-092 GEN
Solar/Wind Harmer
0.505
24387305FR-4G C
Solar/Wind Harmer
3.547
24386605FR-22G C
Solar/Wind Harmer
2.365
24387005FR-3G C
Solar/Wind Harmer
2.341
274880W4-005 GEN4
Solar/Wind Harmer
1.68
274863CRW1-WTG
Solar/Wind Harmer
3.265
274864CRW2-WTG
Solar/Wind Harmer
3.265
274888KELLY CRK;1U
Solar/Wind Harmer
3.775
276893AG1-478 C
Solar/Wind Harmer
0.22
276602WESTBROOK C
Solar/Wind Harmer
1.137
276603SUBLETTE C
Solar/Wind Harmer
0.541
957891AF2-083 GEN
Solar/Wind Harmer
0.398
252510AF1-249 C
Solar/Wind Helper
0.173
253394AE2-221_GEN
Solar/Wind Helper
0.746
253398AE2-221_GEN2
Solar/Wind Helper
0.746
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
4.279
961761AG1-017 GEN
Solar/Wind Harmer
0.489
247536S-71 GEN
Solar/Wind Harmer
4.101
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0.641
970349AG2-230 GEN
Solar/Wind Harmer
0.421
971347AH1-153 GEN
Solar/Wind Harmer
0.14
276615X2-022 GEN
Solar/Wind Harmer
1.269
939401AE1-172 GEN
Solar/Wind Harmer
11.084
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.277
926823AC1-168 GEN
Solar/Wind Harmer
3.347
274857EASY ROAD;U1
Solar/Wind Harmer
2.497
252507AC2-088 GEN
Solar/Wind Helper
0.344
276903AD2-071 C
Solar/Wind Harmer
0.528
944531AF1-118 GEN
Solar/Wind Harmer
1.73
945391AF1-204 GEN
Solar/Wind Harmer
13.313
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.297
965911AG1-460 GEN
Solar/Wind Harmer
0.666
970707AG2-453 GEN
Solar/Wind Harmer
0.773
970833AG2-524 GEN
Solar/Wind Harmer
2.427
958481AF2-142 GEN
Solar/Wind Harmer
0.411
274862TOP CROP ;2U
Solar/Wind Harmer
3.208
274879MINONK ;1U
Solar/Wind Harmer
4.262
971675AH1-338 GEN
Solar/Wind Harmer
0.486
253406AD2-031_GEN
Solar/Wind Helper
0.232
942051AE2-217 GEN
Solar/Wind Helper
0.61
24729205KEY G1
50/50
6.064
24379505HDWTR1G C
Solar/Wind Harmer
13.687
270004AE1-209 GEN
Solar/Wind Harmer
10.901
270201AC2-176 GEN
Solar/Wind Harmer
5.026
970885AG2-551 GEN
Solar/Wind Harmer
1.603
963741AG1-226 GEN
Solar/Wind Harmer
1.418
24386205FR-12G C
Solar/Wind Harmer
2.469
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.596
276686W4-005 GEN3
Solar/Wind Harmer
1.68
276764AC1-053 GEN2
Solar/Wind Harmer
2.192
276911AD2-131_GEN
Solar/Wind Harmer
0.139
276872AE1-163_GEN1
Solar/Wind Harmer
3.721
274872LEEDK;1U
Solar/Wind Harmer
5.072
274851PROVIDENC;RU
Solar/Wind Harmer
1.563
959081AF2-199 GEN
Solar/Wind Harmer
0.269
25183208HLCRTG
Solar/Wind Helper
1.146
253325AC1-069 GEN
Solar/Wind Helper
0.165
946031AF1-268 GEN
Solar/Wind Harmer
0.493
965651AG1-433 GEN
Solar/Wind Harmer
8.861
970289AG2-191 GEN
Solar/Wind Harmer
0.093
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
0.834
957381AF2-032 GEN
Solar/Wind Harmer
0.056
276916AD2-100_GEN
Solar/Wind Harmer
0.583
972181SS23-001
Solar/Wind Harmer
0.277
274847GR RIDGE ;BU
Solar/Wind Harmer
3.17
274849CRESCENT ;1U
Solar/Wind Harmer
1.15
959091AF2-200 GEN
Solar/Wind Harmer
0.538
253333AC1-068 GEN
Solar/Wind Helper
0.165
961161AF2-407 GEN
50/50
35.536
270599AE1-208 GEN
Solar/Wind Harmer
0.443
971029AG2-637 GEN
Solar/Wind Harmer
0.536
24386405FR-21G C
Solar/Wind Harmer
2.365
276763AC1-053 GEN1
Solar/Wind Harmer
2.192
972231SS25-0005
Solar/Wind Harmer
0.442
276876AE1-163_GEN2
Solar/Wind Harmer
3.721
274855GSG-6 ;RU
Solar/Wind Harmer
2.305
276782AC1-033 GEN
Solar/Wind Harmer
2.121
971411AH1-196 GEN
Solar/Wind Harmer
0.404
961051AF2-396 GEN
Solar/Wind Harmer
0.525
961051AF2-396 GEN
Solar/Wind Harmer
4.201
24726805LAWG2B
50/50
3.434
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.465
24697905MDL-4G C
Solar/Wind Harmer
1.546
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.333
965091AG1-374 GEN
Solar/Wind Harmer
0.842
276843GEN-1.7
Solar/Wind Harmer
0.367
958011AF2-095 GEN
Solar/Wind Harmer
0.398
276691AA1-018 GEN1
Solar/Wind Harmer
0.295
958491AF2-143 GEN
Solar/Wind Harmer
0.41
276646AC1-214 GEN2
Solar/Wind Harmer
0.839
274878BISHOP HL;2U
Solar/Wind Harmer
2.104
970819AG2-516 GEN
Solar/Wind Harmer
0.321
965931AG1-462 GEN
Solar/Wind Harmer
0.667
943021AE2-325 GEN
Solar/Wind Harmer
1.637
241972AD1-140 GEN
Solar/Wind Helper
0.889
945631AF1-228 GEN
Solar/Wind Helper
0.511
24726405LAWG1A
50/50
3.654
270240V3-007_GEN2
Solar/Wind Harmer
10.716
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.828
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.094
970571AG2-364 GEN
Solar/Wind Harmer
0.544
274850MENDOTA H;RU
Solar/Wind Harmer
1.602
276863AD2-134 GEN
Solar/Wind Harmer
1.115
276861AD2-134 GEN
Solar/Wind Harmer
1.115
274856ECOGROVE ;U1
Solar/Wind Harmer
2.088
971681AH1-341 GEN
Solar/Wind Harmer
0.401
938861AE1-114 GEN
Solar/Wind Harmer
6.254
274858EASY ROAD;U2
Solar/Wind Harmer
2.497
945111AF1-176 GEN
Solar/Wind Harmer
0.472
945111AF1-176 GEN
Solar/Wind Harmer
2.573
253378AE2-206_GEN
Solar/Wind Helper
0.481
24726905LAWG2S
50/50
5.63
24726705LAWG2A
50/50
3.654
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
17.723
970883AG2-550 GEN
Solar/Wind Harmer
0.401
970193AG2-126 GEN
Solar/Wind Harmer
0.502
24385905FR-11G C
Solar/Wind Harmer
4.649
24697605MDL-3G C
Solar/Wind Harmer
2.319
270181AB1-006 GEN2
Solar/Wind Harmer
0.464
274853TWINGROVE;U1
Solar/Wind Harmer
4.333
959611AF2-252 GEN
Solar/Wind Harmer
1.122
960611AF2-352 GEN
Solar/Wind Harmer
1.122
274887GEN-1.85
Solar/Wind Harmer
3.408
970833AG2-524 GEN
Solar/Wind Harmer
0.303
276868AE1-113 GEN
Solar/Wind Harmer
6.393
962781AG1-127 GEN
Solar/Wind Harmer
0.258
970031AG2-029 GEN
Solar/Wind Harmer
0.675
971171AH1-044 GEN
Solar/Wind Harmer
0.538
24726505LAWG1B
50/50
3.654
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.97
945371AF1-202 GEN
Solar/Wind Harmer
9.666
970825AG2-519 GEN
Solar/Wind Harmer
2.567
958861AF2-177 GEN
Solar/Wind Harmer
18.276
270032AE2-172
Solar/Wind Harmer
4.141
942221AE2-234 GEN
Solar/Wind Harmer
0.149
270543AE2-219 C
Solar/Wind Harmer
0.401
24691005MDL-2G C
Solar/Wind Harmer
2.319
957841AF2-078 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
0.26
276621W2-048 GEN
Solar/Wind Harmer
4.04
942481AE2-261 GEN
Solar/Wind Harmer
0.83
971997AH1-543 GEN
Solar/Wind Harmer
0.431
276889AE2-281 GEN
Solar/Wind Harmer
1.063
962691AG1-118 GEN
Solar/Wind Harmer
0.814
276158O29GEN2
Solar/Wind Harmer
2.349
276708O09 GEN2
Solar/Wind Harmer
2.206
270505AE1-170 C O1
Solar/Wind Harmer
0.397
270367AC2-061_GEN
Solar/Wind Helper
0.537
962581AG1-107 GEN
Solar/Wind Helper
0.635
24726605LAWG1S
50/50
5.63
24729405KEY G3
50/50
6.167
24729505KEY G4
50/50
6.064
970825AG2-519 GEN
Solar/Wind Harmer
0.401
970241AG2-163 GEN
Solar/Wind Harmer
0.788
270043AE2-236 GEN
Solar/Wind Harmer
0.169
971605AH1-302 GEN
Solar/Wind Harmer
4.371
276174W4-005 GEN2
Solar/Wind Harmer
1.68
276668AB2-070 GEN1
Solar/Wind Harmer
1.442
939741AE1-205 GEN
Solar/Wind Harmer
0.562
942111AE2-223 GEN
Solar/Wind Harmer
6.575
276838X2-022 GEN2
Solar/Wind Harmer
0.151
276897AD1-100 C
Solar/Wind Harmer
36.785
970941AG2-585 GEN
Solar/Wind Harmer
0.152
276805AD2-038 GEN
Solar/Wind Harmer
3.201
970569AG2-363 GEN
Solar/Wind Harmer
0.816
971771AH1-392 GEN
Solar/Wind Harmer
0.244
276645AC1-214 GEN1
Solar/Wind Harmer
0.839
276157O29GEN1
Solar/Wind Harmer
2.349
961491AF2-440 GEN
Solar/Wind Helper
0.212
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.174
24791305MDL-5G
Solar/Wind Harmer
1.546
276726Z2-087_GEN
Solar/Wind Harmer
4.384
941551AE2-152 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
8.642
965791AG1-447 GEN
Solar/Wind Harmer
3.045
276882AE2-255 GEN
Solar/Wind Harmer
2.131
270526AF1-158 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
2.206
270518AE2-148 GEN
Solar/Wind Helper
2.304
270340AC2-060 GEN
Solar/Wind Helper
0.399
25194708EBND2
50/50
6.209
24699105WLD G1 C
Solar/Wind Harmer
4.279
270031AE2-169
Solar/Wind Harmer
0.443
270383AD1-128 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
9.652
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.684
971917AH1-482 GEN
Solar/Wind Harmer
4.5
276655WTG1_EQ
Solar/Wind Harmer
4.839
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.208
971067AG2-660 GEN
Solar/Wind Harmer
1.077
252509AD1-136 GEN
Solar/Wind Helper
0.049
270186AC1-089 GEN
Solar/Wind Helper
0.597
270063AE2-323 C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
7.816
253415AE1-040 GEN
Solar/Wind Helper
0.168
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.442
276806AD2-047 C O1
Solar/Wind Harmer
8.519
274877BISHOP HL;1U
Solar/Wind Harmer
2.104
971341AH1-150 GEN
Solar/Wind Harmer
0.538
961171AF2-408 GEN
50/50
9.449
970289AG2-191 GEN
Solar/Wind Harmer
0.643
970291AG2-192 GEN
Solar/Wind Harmer
0.351
276785W4-005 GEN1
Solar/Wind Harmer
1.68
276849AB2-070 GEN2
Solar/Wind Harmer
1.442
274871GR RIDGE ;2U
Solar/Wind Harmer
3.497
943121AE2-341 GEN
Solar/Wind Harmer
0.411
274848CAMPGROVE;RU
Solar/Wind Harmer
3.162
957471AF2-041 GEN
Solar/Wind Harmer
0.807
270449AD2-020 GEN
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Helper
0.57
253317AC1-085 GEN4
Solar/Wind Helper
0.7
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253400AC2-068 GEN
Solar/Wind Helper
0.08
253383AE2-342_GEN
Solar/Wind Helper
0.138
241973AD2-163_GEN1
Solar/Wind Helper
0.3
276820AF1-078_GEN
Solar/Wind Helper
0.216
253316AC1-085 GEN3
Solar/Wind Helper
0.7
253433AC1-085 GEN1
Solar/Wind Helper
0.443
253349AC2-067 GEN
Solar/Wind Helper
0.2
253343AC1-166 GEN
Solar/Wind Helper
0.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.716
LGEELTFEXP_LGEE->PJM
CLTF
1.364
MECLTFEXP_MEC->PJM
CLTF
7.026
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.401
NYPJM->LTFIMP_NY
CLTF
0.715
TVALTFEXP_TVA->PJM
CLTF
1.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.247
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
SIGELTFEXP_SIGE->PJM
CLTF
0.23
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.917
WECLTFEXP_WEC->PJM
CLTF
1.758
LAGNLTFEXP_LAGN->PJM
CLTF
4.541

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.64 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2470.96
MW Contribution:
0.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726805LAWG2B
50/50
5.929
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.772
24697905MDL-4G C
Solar/Wind Harmer
1.526
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.378
965091AG1-374 GEN
Solar/Wind Harmer
0.85
276843GEN-1.7
Solar/Wind Harmer
0.356
946031AF1-268 GEN
Solar/Wind Harmer
0.807
965651AG1-433 GEN
Solar/Wind Harmer
13.484
970289AG2-191 GEN
Solar/Wind Harmer
0.135
276916AD2-100_GEN
Solar/Wind Harmer
0.601
957381AF2-032 GEN
Solar/Wind Harmer
0.057
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
0.269
274847GR RIDGE ;BU
Solar/Wind Harmer
3.075
274849CRESCENT ;1U
Solar/Wind Harmer
1.135
972207SS24-0001
Solar/Wind Harmer
0.8
959091AF2-200 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Helper
0.154
943111AE2-339 GEN
Solar/Wind Helper
0.102
961161AF2-407 GEN
50/50
56.057
24728905RICHG2
50/50
5.791
270599AE1-208 GEN
Solar/Wind Harmer
0.695
971029AG2-637 GEN
Solar/Wind Harmer
1.08
24386405FR-21G C
Solar/Wind Harmer
2.397
276763AC1-053 GEN1
Solar/Wind Harmer
2.251
972231SS25-0005
Solar/Wind Harmer
0.431
276876AE1-163_GEN2
Solar/Wind Harmer
3.647
276782AC1-033 GEN
Solar/Wind Harmer
2.091
961051AF2-396 GEN
Solar/Wind Harmer
0.531
961051AF2-396 GEN
Solar/Wind Harmer
4.249
274855GSG-6 ;RU
Solar/Wind Harmer
2.239
971411AH1-196 GEN
Solar/Wind Harmer
0.393
24729305KEY G2
50/50
9.086
270005AE1-210 C O1
Solar/Wind Harmer
17.522
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.239
270071AF1-092 GEN
Solar/Wind Harmer
0.615
24387305FR-4G C
Solar/Wind Harmer
3.596
24386605FR-22G C
Solar/Wind Harmer
2.397
24387005FR-3G C
Solar/Wind Harmer
2.373
274880W4-005 GEN4
Solar/Wind Harmer
1.725
274863CRW1-WTG
Solar/Wind Harmer
3.228
274864CRW2-WTG
Solar/Wind Harmer
3.228
274888KELLY CRK;1U
Solar/Wind Harmer
3.664
276893AG1-478 C
Solar/Wind Harmer
0.214
957891AF2-083 GEN
Solar/Wind Harmer
0.401
276602WESTBROOK C
Solar/Wind Harmer
1.104
276603SUBLETTE C
Solar/Wind Harmer
0.528
252510AF1-249 C
Solar/Wind Helper
0.15
253394AE2-221_GEN
Solar/Wind Helper
0.719
253398AE2-221_GEN2
Solar/Wind Helper
0.719
247621Y3-024
50/50
0.493
24728505AND G1
50/50
6.613
270024AE2-089 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.48
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
8.268
274877BISHOP HL;1U
Solar/Wind Harmer
2.074
971341AH1-150 GEN
Solar/Wind Harmer
0.523
253316AC1-085 GEN3
Solar/Wind Helper
0.707
253433AC1-085 GEN1
Solar/Wind Helper
0.448
276820AF1-078_GEN
Solar/Wind Helper
0.147
253343AC1-166 GEN
Solar/Wind Helper
0.154
24729205KEY G1
50/50
8.934
24379505HDWTR1G C
Solar/Wind Harmer
22.542
270004AE1-209 GEN
Solar/Wind Harmer
17.522
270201AC2-176 GEN
Solar/Wind Harmer
8.378
970885AG2-551 GEN
Solar/Wind Harmer
3.01
963741AG1-226 GEN
Solar/Wind Harmer
1.519
24386205FR-12G C
Solar/Wind Harmer
2.503
276686W4-005 GEN3
Solar/Wind Harmer
1.725
276764AC1-053 GEN2
Solar/Wind Harmer
2.251
276911AD2-131_GEN
Solar/Wind Harmer
0.143
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.579
276872AE1-163_GEN1
Solar/Wind Harmer
3.647
274851PROVIDENC;RU
Solar/Wind Harmer
1.542
274872LEEDK;1U
Solar/Wind Harmer
4.922
959081AF2-199 GEN
Solar/Wind Harmer
0.262
25183208HLCRTG
Solar/Wind Helper
1.201
253325AC1-069 GEN
Solar/Wind Helper
0.154
24728805RICHG1
50/50
5.791
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.695
24699105WLD G1 C
Solar/Wind Harmer
6.608
963841AG1-237 GEN
Solar/Wind Harmer
10.078
959331AF2-224 GEN
Solar/Wind Harmer
0.311
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.622
276655WTG1_EQ
Solar/Wind Harmer
4.873
971917AH1-482 GEN
Solar/Wind Harmer
4.379
965041AG1-368 GEN
Solar/Wind Harmer
0.27
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.128
971067AG2-660 GEN
Solar/Wind Harmer
1.047
252509AD1-136 GEN
Solar/Wind Helper
0.061
270186AC1-089 GEN
Solar/Wind Helper
0.6
339243AC2-075 GEN1
Solar/Wind Helper
0.064
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.119
24791305MDL-5G
Solar/Wind Harmer
1.526
944221AF1-090 GEN
Solar/Wind Harmer
8.946
276726Z2-087_GEN
Solar/Wind Harmer
4.415
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
2.958
276882AE2-255 GEN
Solar/Wind Harmer
2.083
276741O09 GEN1
Solar/Wind Harmer
2.159
270518AE2-148 GEN
Solar/Wind Helper
1.988
270340AC2-060 GEN
Solar/Wind Helper
0.398
339221AD2-048_GEN
Solar/Wind Helper
0.219
958011AF2-095 GEN
Solar/Wind Harmer
0.387
276691AA1-018 GEN1
Solar/Wind Harmer
0.288
958491AF2-143 GEN
Solar/Wind Harmer
0.401
276646AC1-214 GEN2
Solar/Wind Harmer
0.827
274878BISHOP HL;2U
Solar/Wind Harmer
2.074
943021AE2-325 GEN
Solar/Wind Harmer
1.651
970819AG2-516 GEN
Solar/Wind Harmer
0.313
965931AG1-462 GEN
Solar/Wind Harmer
0.653
241972AD1-140 GEN
Solar/Wind Helper
0.725
945631AF1-228 GEN
Solar/Wind Helper
0.439
970291AG2-192 GEN
Solar/Wind Harmer
0.093
963791AG1-232 GEN
Solar/Wind Harmer
0.671
24755605MDL-5G
Solar/Wind Harmer
1.526
270445AC2-157 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.424
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
0.277
965681AG1-436 GEN
Solar/Wind Harmer
0.336
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.841
943591AF1-030 GEN
Solar/Wind Harmer
0.265
971343AH1-151 GEN
Solar/Wind Harmer
0.523
971087AG2-675 GEN
Solar/Wind Harmer
1.64
253303V4-073 C
Solar/Wind Helper
0.008
960071AF2-298 GEN
Solar/Wind Helper
0.181
253338AC1-165 GEN
Solar/Wind Helper
0.154
241974AD2-163_GEN2
Solar/Wind Helper
0.227
961171AF2-408 GEN
50/50
15.137
24728605AND G2
50/50
6.613
970289AG2-191 GEN
Solar/Wind Harmer
0.94
970291AG2-192 GEN
Solar/Wind Harmer
0.513
276785W4-005 GEN1
Solar/Wind Harmer
1.725
276849AB2-070 GEN2
Solar/Wind Harmer
1.48
274871GR RIDGE ;2U
Solar/Wind Harmer
3.392
274848CAMPGROVE;RU
Solar/Wind Harmer
3.123
943121AE2-341 GEN
Solar/Wind Harmer
0.397
270449AD2-020 GEN
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
0.785
252524AE2-267 GEN
Solar/Wind Helper
0.451
253317AC1-085 GEN4
Solar/Wind Helper
0.707
253432AC1-085 GEN2
Solar/Wind Helper
0.024
241973AD2-163_GEN1
Solar/Wind Helper
0.227
24726605LAWG1S
50/50
9.719
24729405KEY G3
50/50
9.086
24729505KEY G4
50/50
8.934
970825AG2-519 GEN
Solar/Wind Harmer
0.648
270043AE2-236 GEN
Solar/Wind Harmer
0.203
970241AG2-163 GEN
Solar/Wind Harmer
0.844
276174W4-005 GEN2
Solar/Wind Harmer
1.725
276668AB2-070 GEN1
Solar/Wind Harmer
1.48
276838X2-022 GEN2
Solar/Wind Harmer
0.155
971605AH1-302 GEN
Solar/Wind Harmer
4.256
939741AE1-205 GEN
Solar/Wind Harmer
0.566
942111AE2-223 GEN
Solar/Wind Harmer
6.622
971771AH1-392 GEN
Solar/Wind Harmer
0.245
276897AD1-100 C
Solar/Wind Harmer
35.724
970941AG2-585 GEN
Solar/Wind Harmer
0.148
276805AD2-038 GEN
Solar/Wind Harmer
3.128
276645AC1-214 GEN1
Solar/Wind Harmer
0.827
970569AG2-363 GEN
Solar/Wind Harmer
0.801
276157O29GEN1
Solar/Wind Harmer
2.299
961491AF2-440 GEN
Solar/Wind Helper
0.197
24726405LAWG1A
50/50
6.308
270240V3-007_GEN2
Solar/Wind Harmer
17.65
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
1.249
965011AG1-365 GEN
Solar/Wind Harmer
0.311
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.48
945111AF1-176 GEN
Solar/Wind Harmer
2.617
970073AG2-061 GEN
Solar/Wind Harmer
1.069
970571AG2-364 GEN
Solar/Wind Harmer
0.534
274850MENDOTA H;RU
Solar/Wind Harmer
1.557
276863AD2-134 GEN
Solar/Wind Harmer
1.083
276861AD2-134 GEN
Solar/Wind Harmer
1.083
274856ECOGROVE ;U1
Solar/Wind Harmer
2.033
971681AH1-341 GEN
Solar/Wind Harmer
0.391
938861AE1-114 GEN
Solar/Wind Harmer
6.093
274858EASY ROAD;U2
Solar/Wind Harmer
2.433
253378AE2-206_GEN
Solar/Wind Helper
0.327
24726905LAWG2S
50/50
9.719
24726705LAWG2A
50/50
6.308
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
26.967
970883AG2-550 GEN
Solar/Wind Harmer
0.753
970193AG2-126 GEN
Solar/Wind Harmer
0.58
970031AG2-029 GEN
Solar/Wind Harmer
0.774
24385905FR-11G C
Solar/Wind Harmer
4.713
270063AE2-323 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
2.288
270181AB1-006 GEN2
Solar/Wind Harmer
0.458
274853TWINGROVE;U1
Solar/Wind Harmer
4.378
959611AF2-252 GEN
Solar/Wind Harmer
1.134
960611AF2-352 GEN
Solar/Wind Harmer
1.134
944231AF1-091 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
3.308
970833AG2-524 GEN
Solar/Wind Harmer
0.294
276868AE1-113 GEN
Solar/Wind Harmer
6.248
962781AG1-127 GEN
Solar/Wind Harmer
0.25
971171AH1-044 GEN
Solar/Wind Harmer
0.523
946321AF1-296 GEN
Solar/Wind Harmer
7.649
253415AE1-040 GEN
Solar/Wind Helper
0.164
339216AC1-074 GEN
Solar/Wind Helper
0.256
276903AD2-071 C
Solar/Wind Harmer
0.802
24726505LAWG1B
50/50
6.308
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
4.892
970825AG2-519 GEN
Solar/Wind Harmer
4.152
945371AF1-202 GEN
Solar/Wind Harmer
15.077
958861AF2-177 GEN
Solar/Wind Harmer
28.062
270032AE2-172
Solar/Wind Harmer
6.246
270543AE2-219 C
Solar/Wind Harmer
0.753
942221AE2-234 GEN
Solar/Wind Harmer
0.226
965021AG1-366 GEN
Solar/Wind Harmer
1.243
24691005MDL-2G C
Solar/Wind Harmer
2.288
971993AH1-541 GEN
Solar/Wind Harmer
0.267
276621W2-048 GEN
Solar/Wind Harmer
4.151
957841AF2-078 GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
0.855
971997AH1-543 GEN
Solar/Wind Harmer
0.422
276889AE2-281 GEN
Solar/Wind Harmer
1.042
270505AE1-170 C O1
Solar/Wind Harmer
0.399
962691AG1-118 GEN
Solar/Wind Harmer
0.79
276158O29GEN2
Solar/Wind Harmer
2.299
276708O09 GEN2
Solar/Wind Harmer
2.159
270367AC2-061_GEN
Solar/Wind Helper
0.514
962581AG1-107 GEN
Solar/Wind Helper
0.591
944531AF1-118 GEN
Solar/Wind Harmer
2.515
945391AF1-204 GEN
Solar/Wind Harmer
15.38
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.293
965911AG1-460 GEN
Solar/Wind Harmer
0.686
970833AG2-524 GEN
Solar/Wind Harmer
2.354
274862TOP CROP ;2U
Solar/Wind Harmer
3.128
958481AF2-142 GEN
Solar/Wind Harmer
0.401
274879MINONK ;1U
Solar/Wind Harmer
4.165
970707AG2-453 GEN
Solar/Wind Harmer
0.744
971675AH1-338 GEN
Solar/Wind Harmer
0.472
253406AD2-031_GEN
Solar/Wind Helper
0.219
942051AE2-217 GEN
Solar/Wind Helper
0.479
24728705AND G3
50/50
13.997
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
6.608
961761AG1-017 GEN
Solar/Wind Harmer
0.815
247536S-71 GEN
Solar/Wind Harmer
7.289
276615X2-022 GEN
Solar/Wind Harmer
1.304
276656WTG2_EQ
Solar/Wind Harmer
0.645
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
10.902
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.268
926823AC1-168 GEN
Solar/Wind Harmer
3.292
970349AG2-230 GEN
Solar/Wind Harmer
0.402
971347AH1-153 GEN
Solar/Wind Harmer
0.134
274857EASY ROAD;U1
Solar/Wind Harmer
2.433
252507AC2-088 GEN
Solar/Wind Helper
0.43
NYPJM->LTFIMP_NY
CLTF
0.75
TVALTFEXP_TVA->PJM
CLTF
1.407
LAGNLTFEXP_LAGN->PJM
CLTF
3.93
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.069
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.195
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.031
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.447
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.381
MECLTFEXP_MEC->PJM
CLTF
6.886
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.851
WECLTFEXP_WEC->PJM
CLTF
1.709
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.203
SIGELTFEXP_SIGE->PJM
CLTF
0.245

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.64 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2470.93
MW Contribution:
0.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970291AG2-192 GEN
Solar/Wind Harmer
0.093
963791AG1-232 GEN
Solar/Wind Harmer
0.671
24755605MDL-5G
Solar/Wind Harmer
1.526
270445AC2-157 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.424
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
0.277
965681AG1-436 GEN
Solar/Wind Harmer
0.336
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.841
943591AF1-030 GEN
Solar/Wind Harmer
0.265
971343AH1-151 GEN
Solar/Wind Harmer
0.523
971087AG2-675 GEN
Solar/Wind Harmer
1.64
253303V4-073 C
Solar/Wind Helper
0.008
960071AF2-298 GEN
Solar/Wind Helper
0.181
253338AC1-165 GEN
Solar/Wind Helper
0.154
241974AD2-163_GEN2
Solar/Wind Helper
0.227
24729305KEY G2
50/50
9.086
270005AE1-210 C O1
Solar/Wind Harmer
17.522
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.239
270071AF1-092 GEN
Solar/Wind Harmer
0.615
24387305FR-4G C
Solar/Wind Harmer
3.596
24386605FR-22G C
Solar/Wind Harmer
2.397
24387005FR-3G C
Solar/Wind Harmer
2.373
274880W4-005 GEN4
Solar/Wind Harmer
1.725
274863CRW1-WTG
Solar/Wind Harmer
3.228
274864CRW2-WTG
Solar/Wind Harmer
3.228
274888KELLY CRK;1U
Solar/Wind Harmer
3.664
276893AG1-478 C
Solar/Wind Harmer
0.214
957891AF2-083 GEN
Solar/Wind Harmer
0.401
276602WESTBROOK C
Solar/Wind Harmer
1.104
276603SUBLETTE C
Solar/Wind Harmer
0.528
252510AF1-249 C
Solar/Wind Helper
0.15
253394AE2-221_GEN
Solar/Wind Helper
0.719
253398AE2-221_GEN2
Solar/Wind Helper
0.719
24728705AND G3
50/50
13.997
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
6.608
961761AG1-017 GEN
Solar/Wind Harmer
0.815
247536S-71 GEN
Solar/Wind Harmer
7.289
276615X2-022 GEN
Solar/Wind Harmer
1.304
276656WTG2_EQ
Solar/Wind Harmer
0.645
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
10.902
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.268
926823AC1-168 GEN
Solar/Wind Harmer
3.292
970349AG2-230 GEN
Solar/Wind Harmer
0.402
971347AH1-153 GEN
Solar/Wind Harmer
0.134
274857EASY ROAD;U1
Solar/Wind Harmer
2.433
252507AC2-088 GEN
Solar/Wind Helper
0.43
276903AD2-071 C
Solar/Wind Harmer
0.802
944531AF1-118 GEN
Solar/Wind Harmer
2.515
945391AF1-204 GEN
Solar/Wind Harmer
15.38
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.293
965911AG1-460 GEN
Solar/Wind Harmer
0.686
970833AG2-524 GEN
Solar/Wind Harmer
2.354
274862TOP CROP ;2U
Solar/Wind Harmer
3.128
958481AF2-142 GEN
Solar/Wind Harmer
0.401
274879MINONK ;1U
Solar/Wind Harmer
4.165
970707AG2-453 GEN
Solar/Wind Harmer
0.744
971675AH1-338 GEN
Solar/Wind Harmer
0.472
253406AD2-031_GEN
Solar/Wind Helper
0.219
942051AE2-217 GEN
Solar/Wind Helper
0.479
24729205KEY G1
50/50
8.934
24379505HDWTR1G C
Solar/Wind Harmer
22.542
270004AE1-209 GEN
Solar/Wind Harmer
17.522
270201AC2-176 GEN
Solar/Wind Harmer
8.378
970885AG2-551 GEN
Solar/Wind Harmer
3.01
963741AG1-226 GEN
Solar/Wind Harmer
1.519
24386205FR-12G C
Solar/Wind Harmer
2.503
276686W4-005 GEN3
Solar/Wind Harmer
1.725
276764AC1-053 GEN2
Solar/Wind Harmer
2.251
276911AD2-131_GEN
Solar/Wind Harmer
0.143
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.579
276872AE1-163_GEN1
Solar/Wind Harmer
3.647
274851PROVIDENC;RU
Solar/Wind Harmer
1.542
274872LEEDK;1U
Solar/Wind Harmer
4.922
959081AF2-199 GEN
Solar/Wind Harmer
0.262
25183208HLCRTG
Solar/Wind Helper
1.201
253325AC1-069 GEN
Solar/Wind Helper
0.154
946031AF1-268 GEN
Solar/Wind Harmer
0.807
965651AG1-433 GEN
Solar/Wind Harmer
13.484
970289AG2-191 GEN
Solar/Wind Harmer
0.135
276916AD2-100_GEN
Solar/Wind Harmer
0.601
957381AF2-032 GEN
Solar/Wind Harmer
0.057
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
0.269
274847GR RIDGE ;BU
Solar/Wind Harmer
3.075
274849CRESCENT ;1U
Solar/Wind Harmer
1.135
972207SS24-0001
Solar/Wind Harmer
0.8
959091AF2-200 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Helper
0.154
943111AE2-339 GEN
Solar/Wind Helper
0.102
961161AF2-407 GEN
50/50
56.057
24728905RICHG2
50/50
5.791
270599AE1-208 GEN
Solar/Wind Harmer
0.695
971029AG2-637 GEN
Solar/Wind Harmer
1.08
24386405FR-21G C
Solar/Wind Harmer
2.397
276763AC1-053 GEN1
Solar/Wind Harmer
2.251
972231SS25-0005
Solar/Wind Harmer
0.431
276876AE1-163_GEN2
Solar/Wind Harmer
3.647
276782AC1-033 GEN
Solar/Wind Harmer
2.091
961051AF2-396 GEN
Solar/Wind Harmer
0.531
961051AF2-396 GEN
Solar/Wind Harmer
4.249
274855GSG-6 ;RU
Solar/Wind Harmer
2.239
971411AH1-196 GEN
Solar/Wind Harmer
0.393
24726805LAWG2B
50/50
5.929
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.772
24697905MDL-4G C
Solar/Wind Harmer
1.526
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.378
965091AG1-374 GEN
Solar/Wind Harmer
0.85
276843GEN-1.7
Solar/Wind Harmer
0.356
958011AF2-095 GEN
Solar/Wind Harmer
0.387
276691AA1-018 GEN1
Solar/Wind Harmer
0.288
958491AF2-143 GEN
Solar/Wind Harmer
0.401
276646AC1-214 GEN2
Solar/Wind Harmer
0.827
274878BISHOP HL;2U
Solar/Wind Harmer
2.074
943021AE2-325 GEN
Solar/Wind Harmer
1.651
970819AG2-516 GEN
Solar/Wind Harmer
0.313
965931AG1-462 GEN
Solar/Wind Harmer
0.653
241972AD1-140 GEN
Solar/Wind Helper
0.725
945631AF1-228 GEN
Solar/Wind Helper
0.439
24726405LAWG1A
50/50
6.308
270240V3-007_GEN2
Solar/Wind Harmer
17.65
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
1.249
965011AG1-365 GEN
Solar/Wind Harmer
0.311
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.48
945111AF1-176 GEN
Solar/Wind Harmer
2.617
970073AG2-061 GEN
Solar/Wind Harmer
1.069
970571AG2-364 GEN
Solar/Wind Harmer
0.534
274850MENDOTA H;RU
Solar/Wind Harmer
1.557
276863AD2-134 GEN
Solar/Wind Harmer
1.083
276861AD2-134 GEN
Solar/Wind Harmer
1.083
274856ECOGROVE ;U1
Solar/Wind Harmer
2.033
971681AH1-341 GEN
Solar/Wind Harmer
0.391
938861AE1-114 GEN
Solar/Wind Harmer
6.093
274858EASY ROAD;U2
Solar/Wind Harmer
2.433
253378AE2-206_GEN
Solar/Wind Helper
0.327
24726505LAWG1B
50/50
6.308
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
4.892
970825AG2-519 GEN
Solar/Wind Harmer
4.152
945371AF1-202 GEN
Solar/Wind Harmer
15.077
958861AF2-177 GEN
Solar/Wind Harmer
28.062
270032AE2-172
Solar/Wind Harmer
6.246
270543AE2-219 C
Solar/Wind Harmer
0.753
942221AE2-234 GEN
Solar/Wind Harmer
0.226
965021AG1-366 GEN
Solar/Wind Harmer
1.243
24691005MDL-2G C
Solar/Wind Harmer
2.288
971993AH1-541 GEN
Solar/Wind Harmer
0.267
276621W2-048 GEN
Solar/Wind Harmer
4.151
957841AF2-078 GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
0.855
971997AH1-543 GEN
Solar/Wind Harmer
0.422
276889AE2-281 GEN
Solar/Wind Harmer
1.042
270505AE1-170 C O1
Solar/Wind Harmer
0.399
962691AG1-118 GEN
Solar/Wind Harmer
0.79
276158O29GEN2
Solar/Wind Harmer
2.299
276708O09 GEN2
Solar/Wind Harmer
2.159
270367AC2-061_GEN
Solar/Wind Helper
0.514
962581AG1-107 GEN
Solar/Wind Helper
0.591
24726605LAWG1S
50/50
9.719
24729405KEY G3
50/50
9.086
24729505KEY G4
50/50
8.934
970825AG2-519 GEN
Solar/Wind Harmer
0.648
270043AE2-236 GEN
Solar/Wind Harmer
0.203
970241AG2-163 GEN
Solar/Wind Harmer
0.844
276174W4-005 GEN2
Solar/Wind Harmer
1.725
276668AB2-070 GEN1
Solar/Wind Harmer
1.48
276838X2-022 GEN2
Solar/Wind Harmer
0.155
971605AH1-302 GEN
Solar/Wind Harmer
4.256
939741AE1-205 GEN
Solar/Wind Harmer
0.566
942111AE2-223 GEN
Solar/Wind Harmer
6.622
971771AH1-392 GEN
Solar/Wind Harmer
0.245
276897AD1-100 C
Solar/Wind Harmer
35.724
970941AG2-585 GEN
Solar/Wind Harmer
0.148
276805AD2-038 GEN
Solar/Wind Harmer
3.128
276645AC1-214 GEN1
Solar/Wind Harmer
0.827
970569AG2-363 GEN
Solar/Wind Harmer
0.801
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.119
24791305MDL-5G
Solar/Wind Harmer
1.526
944221AF1-090 GEN
Solar/Wind Harmer
8.946
276726Z2-087_GEN
Solar/Wind Harmer
4.415
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
2.958
276882AE2-255 GEN
Solar/Wind Harmer
2.083
276741O09 GEN1
Solar/Wind Harmer
2.159
270518AE2-148 GEN
Solar/Wind Helper
1.988
270340AC2-060 GEN
Solar/Wind Helper
0.398
339221AD2-048_GEN
Solar/Wind Helper
0.219
24728805RICHG1
50/50
5.791
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.695
24699105WLD G1 C
Solar/Wind Harmer
6.608
963841AG1-237 GEN
Solar/Wind Harmer
10.078
959331AF2-224 GEN
Solar/Wind Harmer
0.311
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.622
276655WTG1_EQ
Solar/Wind Harmer
4.873
971917AH1-482 GEN
Solar/Wind Harmer
4.379
965041AG1-368 GEN
Solar/Wind Harmer
0.27
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.128
971067AG2-660 GEN
Solar/Wind Harmer
1.047
252509AD1-136 GEN
Solar/Wind Helper
0.061
270186AC1-089 GEN
Solar/Wind Helper
0.6
339243AC2-075 GEN1
Solar/Wind Helper
0.064
24726905LAWG2S
50/50
9.719
24726705LAWG2A
50/50
6.308
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
26.967
970883AG2-550 GEN
Solar/Wind Harmer
0.753
970193AG2-126 GEN
Solar/Wind Harmer
0.58
970031AG2-029 GEN
Solar/Wind Harmer
0.774
24385905FR-11G C
Solar/Wind Harmer
4.713
270063AE2-323 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
2.288
270181AB1-006 GEN2
Solar/Wind Harmer
0.458
274853TWINGROVE;U1
Solar/Wind Harmer
4.378
959611AF2-252 GEN
Solar/Wind Harmer
1.134
960611AF2-352 GEN
Solar/Wind Harmer
1.134
944231AF1-091 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
3.308
970833AG2-524 GEN
Solar/Wind Harmer
0.294
276868AE1-113 GEN
Solar/Wind Harmer
6.248
962781AG1-127 GEN
Solar/Wind Harmer
0.25
971171AH1-044 GEN
Solar/Wind Harmer
0.523
946321AF1-296 GEN
Solar/Wind Harmer
7.649
253415AE1-040 GEN
Solar/Wind Helper
0.164
339216AC1-074 GEN
Solar/Wind Helper
0.256
276157O29GEN1
Solar/Wind Harmer
2.299
961491AF2-440 GEN
Solar/Wind Helper
0.197
961171AF2-408 GEN
50/50
15.137
24728605AND G2
50/50
6.613
970289AG2-191 GEN
Solar/Wind Harmer
0.94
970291AG2-192 GEN
Solar/Wind Harmer
0.513
276785W4-005 GEN1
Solar/Wind Harmer
1.725
276849AB2-070 GEN2
Solar/Wind Harmer
1.48
274871GR RIDGE ;2U
Solar/Wind Harmer
3.392
274848CAMPGROVE;RU
Solar/Wind Harmer
3.123
943121AE2-341 GEN
Solar/Wind Harmer
0.397
270449AD2-020 GEN
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
0.785
252524AE2-267 GEN
Solar/Wind Helper
0.451
253317AC1-085 GEN4
Solar/Wind Helper
0.707
253432AC1-085 GEN2
Solar/Wind Helper
0.024
241973AD2-163_GEN1
Solar/Wind Helper
0.227
247621Y3-024
50/50
0.493
24728505AND G1
50/50
6.613
270024AE2-089 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.48
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
8.268
274877BISHOP HL;1U
Solar/Wind Harmer
2.074
971341AH1-150 GEN
Solar/Wind Harmer
0.523
253316AC1-085 GEN3
Solar/Wind Helper
0.707
253433AC1-085 GEN1
Solar/Wind Helper
0.448
276820AF1-078_GEN
Solar/Wind Helper
0.147
253343AC1-166 GEN
Solar/Wind Helper
0.154
NYPJM->LTFIMP_NY
CLTF
0.75
TVALTFEXP_TVA->PJM
CLTF
1.407
LAGNLTFEXP_LAGN->PJM
CLTF
3.93
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.069
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.195
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.031
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.447
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.381
MECLTFEXP_MEC->PJM
CLTF
6.886
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.851
WECLTFEXP_WEC->PJM
CLTF
1.709
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.203
SIGELTFEXP_SIGE->PJM
CLTF
0.245

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.03 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2352.88
MW Contribution:
0.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
45.078
24727205RPMNG3
50/50
68.356
24639705ELKHART HY
50/50
0.148
963791AG1-232 GEN
Solar/Wind Harmer
0.988
247521TR3_G114
Solar/Wind Harmer
4.555
24695305TIMB G C
Solar/Wind Harmer
3.924
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.418
276694AA1-018 GEN2
Solar/Wind Harmer
4.411
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.096
971343AH1-151 GEN
Solar/Wind Harmer
0.804
970583AG2-370 GEN
50/50
2.758
965051AG1-369 GEN
Solar/Wind Harmer
0.293
970349AG2-230 GEN
Solar/Wind Harmer
0.721
971347AH1-153 GEN
Solar/Wind Harmer
0.24
961761AG1-017 GEN
Solar/Wind Harmer
0.449
960591AF2-350 GEN
Solar/Wind Harmer
0.428
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
16.272
247536S-71 GEN
Solar/Wind Harmer
3.798
926823AC1-168 GEN
Solar/Wind Harmer
4.874
274857EASY ROAD;U1
Solar/Wind Harmer
3.688
24725505WLD G2 C
Solar/Wind Harmer
3.052
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.152
944531AF1-118 GEN
Solar/Wind Harmer
2.052
970707AG2-453 GEN
Solar/Wind Harmer
1.192
970833AG2-524 GEN
Solar/Wind Harmer
3.705
958481AF2-142 GEN
Solar/Wind Harmer
0.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.856
274879MINONK ;1U
Solar/Wind Harmer
6.36
971675AH1-338 GEN
Solar/Wind Harmer
0.728
970781AG2-491 GEN
Solar/Wind Harmer
0.403
276903AD2-071 C
Solar/Wind Harmer
0.399
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.811
945391AF1-204 GEN
Solar/Wind Harmer
13.018
270391AF1-285 GEN3
Solar/Wind Helper
0.285
241847AF2-150_GEN
Solar/Wind Helper
0.265
24729205KEY G1
50/50
6.727
270201AC2-176 GEN
Solar/Wind Harmer
4.618
970373AG2-245 GEN
Solar/Wind Harmer
0.924
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.493
274872LEEDK;1U
Solar/Wind Harmer
7.643
276872AE1-163_GEN1
Solar/Wind Harmer
5.502
959081AF2-199 GEN
Solar/Wind Harmer
0.402
274851PROVIDENC;RU
Solar/Wind Harmer
2.244
24386205FR-12G C
Solar/Wind Harmer
3.154
24379505HDWTR1G C
Solar/Wind Harmer
5.718
970885AG2-551 GEN
Solar/Wind Harmer
1.46
963741AG1-226 GEN
Solar/Wind Harmer
1.64
276686W4-005 GEN3
Solar/Wind Harmer
2.126
276764AC1-053 GEN2
Solar/Wind Harmer
2.764
276911AD2-131_GEN
Solar/Wind Harmer
0.168
965421AG1-410 GEN
Solar/Wind Harmer
6.762
965651AG1-433 GEN
Solar/Wind Harmer
8.19
972181SS23-001
Solar/Wind Harmer
0.439
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.299
970289AG2-191 GEN
Solar/Wind Harmer
0.08
274847GR RIDGE ;BU
Solar/Wind Harmer
4.836
946031AF1-268 GEN
Solar/Wind Harmer
0.346
959091AF2-200 GEN
Solar/Wind Harmer
0.804
274849CRESCENT ;1U
Solar/Wind Harmer
1.651
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.704
270227U2-072_GEN3
Solar/Wind Helper
1.995
270228U2-072_GEN4
Solar/Wind Helper
1.995
270231U2-072_GEN5
Solar/Wind Helper
1.995
270349AD2-093_GEN
Solar/Wind Helper
0.454
961051AF2-396 GEN
Solar/Wind Harmer
0.957
961051AF2-396 GEN
Solar/Wind Harmer
7.653
270599AE1-208 GEN
Solar/Wind Harmer
0.377
972231SS25-0005
Solar/Wind Harmer
0.703
971411AH1-196 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
3.454
276876AE1-163_GEN2
Solar/Wind Harmer
5.502
24386405FR-21G C
Solar/Wind Harmer
3.021
276782AC1-033 GEN
Solar/Wind Harmer
3.04
276763AC1-053 GEN1
Solar/Wind Harmer
2.764
971029AG2-637 GEN
Solar/Wind Harmer
0.481
270224U2-072_GEN2
Solar/Wind Helper
1.995
942871AE2-306 GEN
Solar/Wind Helper
0.214
945641AF1-229 GEN
Solar/Wind Helper
0.454
270541AE2-072 C
Solar/Wind Helper
0.459
943021AE2-325 GEN
Solar/Wind Harmer
2.95
964611AG1-324 GEN
Solar/Wind Harmer
0.402
276843GEN-1.7
Solar/Wind Harmer
0.568
958011AF2-095 GEN
Solar/Wind Harmer
0.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.447
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.615
24697905MDL-4G C
Solar/Wind Harmer
2.096
970819AG2-516 GEN
Solar/Wind Harmer
0.478
276646AC1-214 GEN2
Solar/Wind Harmer
1.204
274878BISHOP HL;2U
Solar/Wind Harmer
3.016
274854TWINGROVE;U2
Solar/Wind Harmer
5.82
965091AG1-374 GEN
Solar/Wind Harmer
1.13
965931AG1-462 GEN
Solar/Wind Harmer
0.961
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.995
270499AE1-146 GEN
Solar/Wind Helper
0.544
965011AG1-365 GEN
Solar/Wind Harmer
1.139
945111AF1-176 GEN
Solar/Wind Harmer
0.876
945111AF1-176 GEN
Solar/Wind Harmer
4.774
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.668
970073AG2-061 GEN
Solar/Wind Harmer
1.641
274850MENDOTA H;RU
Solar/Wind Harmer
2.401
276863AD2-134 GEN
Solar/Wind Harmer
1.67
276861AD2-134 GEN
Solar/Wind Harmer
1.67
970571AG2-364 GEN
Solar/Wind Harmer
0.796
274856ECOGROVE ;U1
Solar/Wind Harmer
3.104
971681AH1-341 GEN
Solar/Wind Harmer
0.593
938861AE1-114 GEN
Solar/Wind Harmer
9.255
276656WTG2_EQ
Solar/Wind Harmer
0.874
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.587
270462AD2-086
Solar/Wind Helper
1.788
270317AD1-130_GEN
Solar/Wind Helper
1.166
270287AF1-227 GEN3
Solar/Wind Helper
0.35
960851AF2-376 GEN
50/50
2.033
965021AG1-366 GEN
Solar/Wind Harmer
4.557
942221AE2-234 GEN
Solar/Wind Harmer
0.204
958861AF2-177 GEN
Solar/Wind Harmer
15.92
945371AF1-202 GEN
Solar/Wind Harmer
7.521
270505AE1-170 C O1
Solar/Wind Harmer
0.718
270032AE2-172
Solar/Wind Harmer
3.34
970825AG2-519 GEN
Solar/Wind Harmer
1.758
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.231
971997AH1-543 GEN
Solar/Wind Harmer
0.639
276889AE2-281 GEN
Solar/Wind Harmer
1.572
24691005MDL-2G C
Solar/Wind Harmer
3.143
971549AH1-272 GEN
Solar/Wind Harmer
0.722
276158O29GEN2
Solar/Wind Harmer
3.427
276708O09 GEN2
Solar/Wind Harmer
3.218
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.241
270543AE2-219 C
Solar/Wind Harmer
0.365
971993AH1-541 GEN
Solar/Wind Harmer
0.329
276621W2-048 GEN
Solar/Wind Harmer
5.054
942481AE2-261 GEN
Solar/Wind Harmer
1.011
270485AE1-090_GEN
Solar/Wind Helper
0.155
960861AF2-377 GEN
50/50
2.345
24729305KEY G2
50/50
6.841
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.937
957891AF2-083 GEN
Solar/Wind Harmer
0.723
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.683
274888KELLY CRK;1U
Solar/Wind Harmer
5.846
276893AG1-478 C
Solar/Wind Harmer
0.338
270005AE1-210 C O1
Solar/Wind Harmer
6.493
276602WESTBROOK C
Solar/Wind Harmer
1.703
274863CRW1-WTG
Solar/Wind Harmer
4.717
274864CRW2-WTG
Solar/Wind Harmer
4.717
276603SUBLETTE C
Solar/Wind Harmer
0.798
24387305FR-4G C
Solar/Wind Harmer
4.532
24386605FR-22G C
Solar/Wind Harmer
3.021
24387005FR-3G C
Solar/Wind Harmer
2.991
274880W4-005 GEN4
Solar/Wind Harmer
2.126
246936BC-WTG1
Solar/Wind Helper
17.073
246937BC-WTG2
Solar/Wind Helper
17.073
960841AF2-375 GEN
Solar/Wind Helper
0.563
274858EASY ROAD;U2
Solar/Wind Harmer
3.688
270240V3-007_GEN2
Solar/Wind Harmer
4.477
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.353
270191TR4_S_V150
Solar/Wind Harmer
3.471
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.032
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.18
270180AB1-006 GEN1
Solar/Wind Harmer
5.658
24791305MDL-5G
Solar/Wind Harmer
2.096
276741O09 GEN1
Solar/Wind Harmer
3.218
276726Z2-087_GEN
Solar/Wind Harmer
5.982
944221AF1-090 GEN
Solar/Wind Harmer
10.146
966831AG1-554 GEN
Solar/Wind Helper
0.281
24727005RPMNG1
50/50
68.356
247620Y3-023
50/50
0.46
959331AF2-224 GEN
Solar/Wind Harmer
1.139
965041AG1-368 GEN
Solar/Wind Harmer
0.69
270031AE2-169
Solar/Wind Harmer
0.377
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.661
274861TOP CROP ;1U
Solar/Wind Harmer
4.856
946581AF1-322 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
1.74
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.381
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.278
970833AG2-524 GEN
Solar/Wind Harmer
0.463
962781AG1-127 GEN
Solar/Wind Harmer
0.389
276868AE1-113 GEN
Solar/Wind Harmer
9.54
24697605MDL-3G C
Solar/Wind Harmer
3.143
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.804
24385905FR-11G C
Solar/Wind Harmer
5.939
946321AF1-296 GEN
Solar/Wind Harmer
11.289
274853TWINGROVE;U1
Solar/Wind Harmer
5.82
959611AF2-252 GEN
Solar/Wind Harmer
1.507
960611AF2-352 GEN
Solar/Wind Harmer
1.507
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.365
970193AG2-126 GEN
Solar/Wind Harmer
0.491
958581AF2-149 GEN
Solar/Wind Helper
0.222
24729405KEY G3
50/50
6.841
24729505KEY G4
50/50
6.727
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.436
970941AG2-585 GEN
Solar/Wind Harmer
0.236
276897AD1-100 C
Solar/Wind Harmer
56.232
971605AH1-302 GEN
Solar/Wind Harmer
6.283
970825AG2-519 GEN
Solar/Wind Harmer
0.274
276805AD2-038 GEN
Solar/Wind Harmer
4.799
970569AG2-363 GEN
Solar/Wind Harmer
1.195
276157O29GEN1
Solar/Wind Harmer
3.427
276645AC1-214 GEN1
Solar/Wind Harmer
1.204
939741AE1-205 GEN
Solar/Wind Harmer
0.767
942111AE2-223 GEN
Solar/Wind Harmer
8.972
970241AG2-163 GEN
Solar/Wind Harmer
0.911
276174W4-005 GEN2
Solar/Wind Harmer
2.126
276668AB2-070 GEN1
Solar/Wind Harmer
1.825
276838X2-022 GEN2
Solar/Wind Harmer
0.188
246938BC-WTG3
Solar/Wind Helper
17.366
24727105RPMNG2
50/50
68.356
270246TR4_N_V150
Solar/Wind Harmer
1.152
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.556
970291AG2-192 GEN
Solar/Wind Harmer
0.303
274871GR RIDGE ;2U
Solar/Wind Harmer
5.335
943121AE2-341 GEN
Solar/Wind Harmer
0.627
957471AF2-041 GEN
Solar/Wind Harmer
1.206
274848CAMPGROVE;RU
Solar/Wind Harmer
4.509
276785W4-005 GEN1
Solar/Wind Harmer
2.126
276849AB2-070 GEN2
Solar/Wind Harmer
1.825
957201AF2-014 GEN
Solar/Wind Helper
3.942
270284AF1-227 GEN1
Solar/Wind Helper
0.948
270428AC2-015 C
Solar/Wind Helper
0.374
253383AE2-342_GEN
Solar/Wind Helper
0.103
970169AG2-114 GEN
Solar/Wind Harmer
0.397
959341AF2-225 GEN
Solar/Wind Harmer
0.575
971087AG2-675 GEN
Solar/Wind Harmer
2.412
270445AC2-157 GEN2
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.349
971067AG2-660 GEN
Solar/Wind Harmer
1.608
24699105WLD G1 C
Solar/Wind Harmer
3.052
276655WTG1_EQ
Solar/Wind Harmer
6.603
963841AG1-237 GEN
Solar/Wind Harmer
11.714
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.285
247522W1-056 GEN
Solar/Wind Helper
1.919
270286AF1-227 GEN2
Solar/Wind Helper
0.35
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.296
970521AG2-332 GEN
50/50
10.74
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.192
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.016
276848AB2-070 GEN3
Solar/Wind Harmer
1.825
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.166
270471AD2-092_GEN
Solar/Wind Helper
0.454
276820AF1-078_GEN
Solar/Wind Helper
0.159
990792J1392
External Queue
0.3027859032154083
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.204
NYPJM->LTFIMP_NY
CLTF
1.303
MECLTFEXP_MEC->PJM
CLTF
9.641
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.873
TVALTFEXP_TVA->PJM
CLTF
2.36
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.443
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.032
WECLTFEXP_WEC->PJM
CLTF
2.627
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.255
LGEELTFEXP_LGEE->PJM
CLTF
1.795
LAGNLTFEXP_LAGN->PJM
CLTF
5.817
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.21 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2290.26
MW Contribution:
0.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
965421AG1-410 GEN
Solar/Wind Harmer
6.81
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
965431AG1-411 GEN
50/50
45.403
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.018
270143AC1-141 CT2_
50/50
2.018
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
24643105BUCHANAN
50/50
0.01
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.787
24642205MAYFLWER
50/50
0.618
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
990792J1392
External Queue
0.30737584829330444
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.89 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2283.06
MW Contribution:
0.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
965421AG1-410 GEN
Solar/Wind Harmer
6.81
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
965431AG1-411 GEN
50/50
45.403
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
990792J1392
External Queue
0.30737584829330444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.36 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2271.47
MW Contribution:
0.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965421AG1-410 GEN
Solar/Wind Harmer
6.711
965651AG1-433 GEN
Solar/Wind Harmer
8.016
972181SS23-001
Solar/Wind Harmer
0.428
970583AG2-370 GEN
50/50
2.702
965051AG1-369 GEN
Solar/Wind Harmer
0.285
970349AG2-230 GEN
Solar/Wind Harmer
0.704
971347AH1-153 GEN
Solar/Wind Harmer
0.235
961761AG1-017 GEN
Solar/Wind Harmer
0.438
960591AF2-350 GEN
Solar/Wind Harmer
0.417
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
15.839
247536S-71 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
4.742
274857EASY ROAD;U1
Solar/Wind Harmer
3.587
24725505WLD G2 C
Solar/Wind Harmer
2.968
276656WTG2_EQ
Solar/Wind Harmer
0.85
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.539
270462AD2-086
Solar/Wind Helper
1.865
270317AD1-130_GEN
Solar/Wind Helper
1.216
270287AF1-227 GEN3
Solar/Wind Helper
0.382
960861AF2-377 GEN
50/50
2.286
24729305KEY G2
50/50
6.704
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.92
957891AF2-083 GEN
Solar/Wind Harmer
0.707
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.667
274888KELLY CRK;1U
Solar/Wind Harmer
5.697
276893AG1-478 C
Solar/Wind Harmer
0.33
270005AE1-210 C O1
Solar/Wind Harmer
6.326
276602WESTBROOK C
Solar/Wind Harmer
1.658
274863CRW1-WTG
Solar/Wind Harmer
4.59
274864CRW2-WTG
Solar/Wind Harmer
4.59
276603SUBLETTE C
Solar/Wind Harmer
0.776
24387305FR-4G C
Solar/Wind Harmer
4.404
24386605FR-22G C
Solar/Wind Harmer
2.936
24387005FR-3G C
Solar/Wind Harmer
2.906
274880W4-005 GEN4
Solar/Wind Harmer
2.063
246936BC-WTG1
Solar/Wind Helper
17.184
246937BC-WTG2
Solar/Wind Helper
17.184
960841AF2-375 GEN
Solar/Wind Helper
0.576
270191TR4_S_V150
Solar/Wind Harmer
3.383
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.91
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.095
270180AB1-006 GEN1
Solar/Wind Harmer
5.504
24791305MDL-5G
Solar/Wind Harmer
2.038
276741O09 GEN1
Solar/Wind Harmer
3.129
276726Z2-087_GEN
Solar/Wind Harmer
5.813
944221AF1-090 GEN
Solar/Wind Harmer
9.816
966831AG1-554 GEN
Solar/Wind Helper
0.286
943021AE2-325 GEN
Solar/Wind Harmer
2.881
964611AG1-324 GEN
Solar/Wind Harmer
0.393
276843GEN-1.7
Solar/Wind Harmer
0.553
958011AF2-095 GEN
Solar/Wind Harmer
0.601
276691AA1-018 GEN1
Solar/Wind Harmer
0.435
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
24697905MDL-4G C
Solar/Wind Harmer
2.038
970819AG2-516 GEN
Solar/Wind Harmer
0.465
276646AC1-214 GEN2
Solar/Wind Harmer
1.17
274878BISHOP HL;2U
Solar/Wind Harmer
2.932
965931AG1-462 GEN
Solar/Wind Harmer
0.934
274854TWINGROVE;U2
Solar/Wind Harmer
5.654
965091AG1-374 GEN
Solar/Wind Harmer
1.098
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
2.097
270499AE1-146 GEN
Solar/Wind Helper
0.556
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.856
945111AF1-176 GEN
Solar/Wind Harmer
4.667
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.651
970073AG2-061 GEN
Solar/Wind Harmer
1.597
274850MENDOTA H;RU
Solar/Wind Harmer
2.337
276863AD2-134 GEN
Solar/Wind Harmer
1.625
276861AD2-134 GEN
Solar/Wind Harmer
1.625
970571AG2-364 GEN
Solar/Wind Harmer
0.775
274856ECOGROVE ;U1
Solar/Wind Harmer
3.02
971681AH1-341 GEN
Solar/Wind Harmer
0.577
938861AE1-114 GEN
Solar/Wind Harmer
9.003
274858EASY ROAD;U2
Solar/Wind Harmer
3.587
270240V3-007_GEN2
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.369
965021AG1-366 GEN
Solar/Wind Harmer
4.503
942221AE2-234 GEN
Solar/Wind Harmer
0.2
958861AF2-177 GEN
Solar/Wind Harmer
15.573
945371AF1-202 GEN
Solar/Wind Harmer
7.349
270505AE1-170 C O1
Solar/Wind Harmer
0.702
270032AE2-172
Solar/Wind Harmer
3.253
970825AG2-519 GEN
Solar/Wind Harmer
1.712
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.198
971997AH1-543 GEN
Solar/Wind Harmer
0.622
276889AE2-281 GEN
Solar/Wind Harmer
1.53
24691005MDL-2G C
Solar/Wind Harmer
3.058
971549AH1-272 GEN
Solar/Wind Harmer
0.702
276158O29GEN2
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
3.129
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.205
270543AE2-219 C
Solar/Wind Harmer
0.354
971993AH1-541 GEN
Solar/Wind Harmer
0.319
276621W2-048 GEN
Solar/Wind Harmer
4.9
942481AE2-261 GEN
Solar/Wind Harmer
0.979
270485AE1-090_GEN
Solar/Wind Helper
0.162
24729405KEY G3
50/50
6.704
24729505KEY G4
50/50
6.593
270043AE2-236 GEN
Solar/Wind Harmer
0.363
971771AH1-392 GEN
Solar/Wind Harmer
0.426
970941AG2-585 GEN
Solar/Wind Harmer
0.23
276897AD1-100 C
Solar/Wind Harmer
54.783
971605AH1-302 GEN
Solar/Wind Harmer
6.118
970825AG2-519 GEN
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
4.671
970569AG2-363 GEN
Solar/Wind Harmer
1.162
24727105RPMNG2
50/50
67.807
270246TR4_N_V150
Solar/Wind Harmer
1.123
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.295
274871GR RIDGE ;2U
Solar/Wind Harmer
5.196
965431AG1-411 GEN
50/50
44.74
24727205RPMNG3
50/50
67.807
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.971
247521TR3_G114
Solar/Wind Harmer
4.44
24695305TIMB G C
Solar/Wind Harmer
3.811
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.053
943591AF1-030 GEN
Solar/Wind Harmer
0.407
276694AA1-018 GEN2
Solar/Wind Harmer
4.296
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.038
971343AH1-151 GEN
Solar/Wind Harmer
0.782
970169AG2-114 GEN
Solar/Wind Harmer
0.386
959341AF2-225 GEN
Solar/Wind Harmer
0.559
971087AG2-675 GEN
Solar/Wind Harmer
2.343
270445AC2-157 GEN2
Solar/Wind Harmer
0
24727005RPMNG1
50/50
67.807
247620Y3-023
50/50
0.45
959331AF2-224 GEN
Solar/Wind Harmer
1.126
965041AG1-368 GEN
Solar/Wind Harmer
0.675
270031AE2-169
Solar/Wind Harmer
0.368
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.489
274861TOP CROP ;1U
Solar/Wind Harmer
4.729
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.176
971067AG2-660 GEN
Solar/Wind Harmer
1.565
24699105WLD G1 C
Solar/Wind Harmer
2.968
276655WTG1_EQ
Solar/Wind Harmer
6.417
963841AG1-237 GEN
Solar/Wind Harmer
11.375
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.3
270286AF1-227 GEN2
Solar/Wind Helper
0.382
247522W1-056 GEN
Solar/Wind Helper
1.958
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.299
961051AF2-396 GEN
Solar/Wind Harmer
0.935
961051AF2-396 GEN
Solar/Wind Harmer
7.477
270599AE1-208 GEN
Solar/Wind Harmer
0.368
972231SS25-0005
Solar/Wind Harmer
0.685
971411AH1-196 GEN
Solar/Wind Harmer
0.591
274855GSG-6 ;RU
Solar/Wind Harmer
3.361
276876AE1-163_GEN2
Solar/Wind Harmer
5.354
24386405FR-21G C
Solar/Wind Harmer
2.936
276782AC1-033 GEN
Solar/Wind Harmer
2.956
276763AC1-053 GEN1
Solar/Wind Harmer
2.681
971029AG2-637 GEN
Solar/Wind Harmer
0.465
270224U2-072_GEN2
Solar/Wind Helper
2.097
942871AE2-306 GEN
Solar/Wind Helper
0.225
945641AF1-229 GEN
Solar/Wind Helper
0.46
270541AE2-072 C
Solar/Wind Helper
0.478
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.266
970289AG2-191 GEN
Solar/Wind Harmer
0.078
274847GR RIDGE ;BU
Solar/Wind Harmer
4.711
946031AF1-268 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
0.782
274849CRESCENT ;1U
Solar/Wind Harmer
1.605
957381AF2-032 GEN
Solar/Wind Harmer
0.066
276916AD2-100_GEN
Solar/Wind Harmer
0.681
270227U2-072_GEN3
Solar/Wind Helper
2.097
270228U2-072_GEN4
Solar/Wind Helper
2.097
270231U2-072_GEN5
Solar/Wind Helper
2.097
270349AD2-093_GEN
Solar/Wind Helper
0.517
970031AG2-029 GEN
Solar/Wind Harmer
1.71
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.032
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.144
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
276868AE1-113 GEN
Solar/Wind Harmer
9.286
24697605MDL-3G C
Solar/Wind Harmer
3.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.782
24385905FR-11G C
Solar/Wind Harmer
5.772
946321AF1-296 GEN
Solar/Wind Harmer
10.97
274853TWINGROVE;U1
Solar/Wind Harmer
5.654
959611AF2-252 GEN
Solar/Wind Harmer
1.464
960611AF2-352 GEN
Solar/Wind Harmer
1.464
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.354
970193AG2-126 GEN
Solar/Wind Harmer
0.475
958581AF2-149 GEN
Solar/Wind Helper
0.216
276157O29GEN1
Solar/Wind Harmer
3.332
276645AC1-214 GEN1
Solar/Wind Harmer
1.17
939741AE1-205 GEN
Solar/Wind Harmer
0.745
942111AE2-223 GEN
Solar/Wind Harmer
8.72
970241AG2-163 GEN
Solar/Wind Harmer
0.884
276174W4-005 GEN2
Solar/Wind Harmer
2.063
276668AB2-070 GEN1
Solar/Wind Harmer
1.771
276838X2-022 GEN2
Solar/Wind Harmer
0.183
246938BC-WTG3
Solar/Wind Helper
17.48
24729205KEY G1
50/50
6.593
270201AC2-176 GEN
Solar/Wind Harmer
4.506
970373AG2-245 GEN
Solar/Wind Harmer
0.901
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.326
274872LEEDK;1U
Solar/Wind Harmer
7.44
276872AE1-163_GEN1
Solar/Wind Harmer
5.354
959081AF2-199 GEN
Solar/Wind Harmer
0.391
274851PROVIDENC;RU
Solar/Wind Harmer
2.181
24386205FR-12G C
Solar/Wind Harmer
3.065
24379505HDWTR1G C
Solar/Wind Harmer
5.555
970885AG2-551 GEN
Solar/Wind Harmer
1.417
963741AG1-226 GEN
Solar/Wind Harmer
1.592
276686W4-005 GEN3
Solar/Wind Harmer
2.063
276764AC1-053 GEN2
Solar/Wind Harmer
2.681
276911AD2-131_GEN
Solar/Wind Harmer
0.162
970521AG2-332 GEN
50/50
10.514
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
12.855
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.782
274877BISHOP HL;1U
Solar/Wind Harmer
2.932
276848AB2-070 GEN3
Solar/Wind Harmer
1.771
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.216
270471AD2-092_GEN
Solar/Wind Helper
0.517
276820AF1-078_GEN
Solar/Wind Helper
0.166
943121AE2-341 GEN
Solar/Wind Harmer
0.611
957471AF2-041 GEN
Solar/Wind Harmer
1.174
274848CAMPGROVE;RU
Solar/Wind Harmer
4.383
276785W4-005 GEN1
Solar/Wind Harmer
2.063
276849AB2-070 GEN2
Solar/Wind Harmer
1.771
957201AF2-014 GEN
Solar/Wind Helper
3.968
270284AF1-227 GEN1
Solar/Wind Helper
1.035
270428AC2-015 C
Solar/Wind Helper
0.376
253383AE2-342_GEN
Solar/Wind Helper
0.105
944531AF1-118 GEN
Solar/Wind Harmer
2.012
270247TR4_N_V136
Solar/Wind Harmer
1.123
970707AG2-453 GEN
Solar/Wind Harmer
1.161
970833AG2-524 GEN
Solar/Wind Harmer
3.609
958481AF2-142 GEN
Solar/Wind Harmer
0.607
274862TOP CROP ;2U
Solar/Wind Harmer
4.729
274879MINONK ;1U
Solar/Wind Harmer
6.19
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
276903AD2-071 C
Solar/Wind Harmer
0.388
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.786
945391AF1-204 GEN
Solar/Wind Harmer
12.593
270391AF1-285 GEN3
Solar/Wind Helper
0.3
241847AF2-150_GEN
Solar/Wind Helper
0.265
990792J1392
External Queue
0.3014104962348938
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
SIGELTFEXP_SIGE->PJM
CLTF
0.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.406
WECLTFEXP_WEC->PJM
CLTF
2.556
LAGNLTFEXP_LAGN->PJM
CLTF
5.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.955
LGEELTFEXP_LGEE->PJM
CLTF
1.68
MECLTFEXP_MEC->PJM
CLTF
9.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.67
NYPJM->LTFIMP_NY
CLTF
1.235
TVALTFEXP_TVA->PJM
CLTF
2.193
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.304
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P2-2_#9456_06DEARB1 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'AEP_P4_#9456_06DEARB1 345_DC_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
243211 to 242933 ckt 1
290608 to 242928 ckt Z1
242933 to 965420 ckt 1
243233 to 249567 ckt 1
965420 to 246929 ckt 1

Light Load Analysis

The New Service Request AG2-550 was evaluated as a 100.0 MW injection

AG2-550 was evaluated as part of a plant. The plant consists of AG2-550, AG2-551. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#14047_05DESOTO 138_F_SRT-A
BreakerAC121.88 %255.0B310.8
23.21
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P1-2_#15020_SRT-A-1
SingleAC121.84 %255.0B310.69
23.21
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
BreakerAC121.84 %255.0B310.69
23.21
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P1-2_#15020_SRT-A-2
SingleAC117.16 %255.0B298.77
23.21
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#15023_05JAY 138_E_SRT-A
BreakerAC114.97 %255.0B293.18
23.38
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#15176_05JAY 138_E2_SRT-A
BreakerAC114.41 %255.0B291.74
23.31
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
BreakerAC111.56 %255.0B284.47
42.05
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P7-1_#11036___SRT-A
TowerAC101.68 %255.0B259.28
17.7
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Base Case
SingleAC100.68 %219.0A220.48
17.96
GD2DEO&K
08MCGFY1-08LOCST1 69.0 kV Ckt 1 line
DEOK_P_CIRCUIT3281&13803_SRT-A
TowerAC108.43 %54.0B58.55
1.58
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#14047_05DESOTO 138_F_SRT-A
BreakerAC121.92 %255.0B310.91
23.21
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P1-2_#15020_SRT-A-1
SingleAC121.88 %255.0B310.79
23.21
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
BreakerAC121.88 %255.0B310.79
23.21
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P1-2_#15020_SRT-A-2
SingleAC117.21 %255.0B298.88
23.21
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#15023_05JAY 138_E_SRT-A
BreakerAC115.02 %255.0B293.3
23.38
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#15176_05JAY 138_E2_SRT-A
BreakerAC114.46 %255.0B291.86
23.31
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
BreakerAC111.55 %255.0B284.46
42.05
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P7-1_#11036___SRT-A
TowerAC101.73 %255.0B259.42
17.7
GD2AEP
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Base Case
SingleAC100.69 %219.0A220.51
17.96

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#14047_05DESOTO 138_F_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.88 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:310.8
MW Contribution:
23.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.33 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:319.59
MW Contribution:
23.21
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.592
970883AG2-550 GEN
Solar/Wind Harmer
23.212
247536S-71 GEN
Solar/Wind Harmer
18.311
944031AF1-071 GEN
Solar/Wind Helper
0.349
961761AG1-017 GEN
Solar/Wind Harmer
1.459
970885AG2-551 GEN
Solar/Wind Harmer
21.102
964611AG1-324 GEN
Solar/Wind Harmer
3.019
270222AC2-111 GEN
Solar/Wind Helper
1.55
270201AC2-176 GEN
Solar/Wind Harmer
15.004
964611AG1-324 GEN
Solar/Wind Harmer
5.757
946031AF1-268 GEN
Solar/Wind Harmer
12.252
963791AG1-232 GEN
Solar/Wind Harmer
7.322
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.143
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.212
942221AE2-234 GEN
Solar/Wind Harmer
1.551
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.055
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.374
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.057
WECLTFEXP_WEC->PJM
CLTF
0.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.579
NYPJM->LTFIMP_NY
CLTF
0.07
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.151

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P1-2_#15020_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.84 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:310.69
MW Contribution:
23.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.29 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:319.5
MW Contribution:
23.21
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.588
970883AG2-550 GEN
Solar/Wind Harmer
23.209
247536S-71 GEN
Solar/Wind Harmer
18.309
944031AF1-071 GEN
Solar/Wind Helper
0.349
961761AG1-017 GEN
Solar/Wind Harmer
1.459
970885AG2-551 GEN
Solar/Wind Harmer
21.099
964611AG1-324 GEN
Solar/Wind Harmer
3.019
270222AC2-111 GEN
Solar/Wind Helper
1.551
270201AC2-176 GEN
Solar/Wind Harmer
15.002
964611AG1-324 GEN
Solar/Wind Harmer
5.756
946031AF1-268 GEN
Solar/Wind Harmer
12.251
963791AG1-232 GEN
Solar/Wind Harmer
7.32
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.14
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.209
942221AE2-234 GEN
Solar/Wind Harmer
1.551
NYPJM->LTFIMP_NY
CLTF
0.07
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.152
WECLTFEXP_WEC->PJM
CLTF
0.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.577
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.052
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.375
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.027

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#15019_05DESOTO 138_F1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.84 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:310.69
MW Contribution:
23.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.29 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:319.5
MW Contribution:
23.21
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.588
970883AG2-550 GEN
Solar/Wind Harmer
23.209
247536S-71 GEN
Solar/Wind Harmer
18.309
944031AF1-071 GEN
Solar/Wind Helper
0.349
961761AG1-017 GEN
Solar/Wind Harmer
1.459
970885AG2-551 GEN
Solar/Wind Harmer
21.099
964611AG1-324 GEN
Solar/Wind Harmer
3.019
270222AC2-111 GEN
Solar/Wind Helper
1.551
270201AC2-176 GEN
Solar/Wind Harmer
15.002
964611AG1-324 GEN
Solar/Wind Harmer
5.756
946031AF1-268 GEN
Solar/Wind Harmer
12.251
963791AG1-232 GEN
Solar/Wind Harmer
7.32
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.14
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.209
942221AE2-234 GEN
Solar/Wind Harmer
1.551
NYPJM->LTFIMP_NY
CLTF
0.07
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.152
WECLTFEXP_WEC->PJM
CLTF
0.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.577
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.052
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.375
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.027

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P1-2_#15020_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.16 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:298.77
MW Contribution:
23.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.62 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:307.59
MW Contribution:
23.21
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.588
970883AG2-550 GEN
Solar/Wind Harmer
23.209
247536S-71 GEN
Solar/Wind Harmer
18.309
944031AF1-071 GEN
Solar/Wind Helper
0.349
961761AG1-017 GEN
Solar/Wind Harmer
1.459
970885AG2-551 GEN
Solar/Wind Harmer
21.099
964611AG1-324 GEN
Solar/Wind Harmer
3.019
270222AC2-111 GEN
Solar/Wind Helper
1.551
270201AC2-176 GEN
Solar/Wind Harmer
15.002
964611AG1-324 GEN
Solar/Wind Harmer
5.756
963791AG1-232 GEN
Solar/Wind Harmer
7.32
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.14
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.209
942221AE2-234 GEN
Solar/Wind Harmer
1.551
WECLTFEXP_WEC->PJM
CLTF
0.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.577
NYPJM->LTFIMP_NY
CLTF
0.07
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.152
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.375
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.052
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#15023_05JAY 138_E_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15023_05JAY 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.97 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:293.18
MW Contribution:
23.38
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15023_05JAY 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.38 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:301.88
MW Contribution:
23.38
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.796
970883AG2-550 GEN
Solar/Wind Harmer
23.383
247536S-71 GEN
Solar/Wind Harmer
18.506
944031AF1-071 GEN
Solar/Wind Helper
0.347
961761AG1-017 GEN
Solar/Wind Harmer
1.499
970885AG2-551 GEN
Solar/Wind Harmer
21.257
270222AC2-111 GEN
Solar/Wind Helper
1.544
270201AC2-176 GEN
Solar/Wind Harmer
15.414
963791AG1-232 GEN
Solar/Wind Harmer
7.424
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.749
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.383
942221AE2-234 GEN
Solar/Wind Harmer
1.523
WECLTFEXP_WEC->PJM
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.192
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.582
NYPJM->LTFIMP_NY
CLTF
0.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.095
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.061
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#15176_05JAY 138_E2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15176_05JAY 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.41 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:291.74
MW Contribution:
23.31
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15176_05JAY 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.84 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:300.5
MW Contribution:
23.31
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.705
970883AG2-550 GEN
Solar/Wind Harmer
23.307
247536S-71 GEN
Solar/Wind Harmer
18.42
944031AF1-071 GEN
Solar/Wind Helper
0.348
961761AG1-017 GEN
Solar/Wind Harmer
1.481
970885AG2-551 GEN
Solar/Wind Harmer
21.188
270222AC2-111 GEN
Solar/Wind Helper
1.547
270201AC2-176 GEN
Solar/Wind Harmer
15.234
963791AG1-232 GEN
Solar/Wind Harmer
7.379
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.482
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.307
942221AE2-234 GEN
Solar/Wind Harmer
1.536
NYPJM->LTFIMP_NY
CLTF
0.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.15
WECLTFEXP_WEC->PJM
CLTF
0.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.192
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.58
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.057
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.359
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.023

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#10527_05BLUFFP 138_E2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.56 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:284.47
MW Contribution:
42.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.52 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:289.48
MW Contribution:
42.04
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
64.388
247536S-71 GEN
Solar/Wind Harmer
39.445
970883AG2-550 GEN
Solar/Wind Harmer
42.045
970885AG2-551 GEN
Solar/Wind Harmer
38.223
270543AE2-219 C
Solar/Wind Harmer
42.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.467
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.03
MECLTFEXP_MEC->PJM
CLTF
0.051
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.645
NYPJM->LTFIMP_NY
CLTF
0.033
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.034
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.097
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.089
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.017
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P7-1_#11036___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11036___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.68 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:259.28
MW Contribution:
17.7
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11036___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.78 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:274.84
MW Contribution:
17.7
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
34.504
970883AG2-550 GEN
Solar/Wind Harmer
17.697
247536S-71 GEN
Solar/Wind Harmer
12.304
944031AF1-071 GEN
Solar/Wind Helper
0.592
961761AG1-017 GEN
Solar/Wind Harmer
0.675
253349AC2-067 GEN
Solar/Wind Helper
0.99
970885AG2-551 GEN
Solar/Wind Harmer
16.088
964611AG1-324 GEN
Solar/Wind Harmer
1.232
270383AD1-128 GEN
Solar/Wind Harmer
0
270222AC2-111 GEN
Solar/Wind Helper
2.629
270201AC2-176 GEN
Solar/Wind Harmer
6.941
964611AG1-324 GEN
Solar/Wind Harmer
2.348
253400AC2-068 GEN
Solar/Wind Helper
0.398
946031AF1-268 GEN
Solar/Wind Harmer
2.514
963791AG1-232 GEN
Solar/Wind Harmer
3.771
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.244
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
17.697
NYPJM->LTFIMP_NY
CLTF
0.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.136
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.824
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.077
MECLTFEXP_MEC->PJM
CLTF
0.381
SIGELTFEXP_SIGE->PJM
CLTF
0.003
WECLTFEXP_WEC->PJM
CLTF
0.116
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.049
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.2
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.046
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.865

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.68 %
Rating:219.0 MVA
Rating Type:A
MVA to Mitigate:220.48
MW Contribution:
17.96
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.73 %
Rating:219.0 MVA
Rating Type:A
MVA to Mitigate:231.55
MW Contribution:
17.96
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
35.363
970883AG2-550 GEN
Solar/Wind Harmer
17.96
247536S-71 GEN
Solar/Wind Harmer
12.328
944031AF1-071 GEN
Solar/Wind Helper
0.384
961761AG1-017 GEN
Solar/Wind Harmer
0.644
253349AC2-067 GEN
Solar/Wind Helper
0.808
970885AG2-551 GEN
Solar/Wind Harmer
16.327
964611AG1-324 GEN
Solar/Wind Harmer
1.153
270222AC2-111 GEN
Solar/Wind Helper
1.708
270201AC2-176 GEN
Solar/Wind Harmer
6.622
964611AG1-324 GEN
Solar/Wind Harmer
2.199
253400AC2-068 GEN
Solar/Wind Helper
0.325
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.774
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
17.96
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.546
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.037
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.082
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.058
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.114
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.333
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.703
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.062
MECLTFEXP_MEC->PJM
CLTF
0.254
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.414

Details for 08MCGFY1-08LOCST1 69.0 kV Ckt 1 line l/o DEOK_P_CIRCUIT3281&13803_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DEO&K
Facility Description:
08MCGFY1-08LOCST1 69.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT3281&13803_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.43 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:58.55
MW Contribution:
1.58
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DEO&K
Facility Description:
08MCGFY1-08LOCST1 69.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT3281&13803_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:114.44 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:61.8
MW Contribution:
1.58
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
2.889
970883AG2-550 GEN
Solar/Wind Harmer
1.584
970885AG2-551 GEN
Solar/Wind Harmer
1.44
NYPJM->LTFIMP_NY
CLTF
0.026
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.041
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.251
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027
MECLTFEXP_MEC->PJM
CLTF
0.13
SIGELTFEXP_SIGE->PJM
CLTF
0.003
WECLTFEXP_WEC->PJM
CLTF
0.037
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.575
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.196

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#14047_05DESOTO 138_F_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.92 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:310.91
MW Contribution:
23.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.41 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:319.78
MW Contribution:
23.21
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.592
970883AG2-550 GEN
Solar/Wind Harmer
23.212
247536S-71 GEN
Solar/Wind Harmer
18.311
944031AF1-071 GEN
Solar/Wind Helper
0.349
961761AG1-017 GEN
Solar/Wind Harmer
1.459
970885AG2-551 GEN
Solar/Wind Harmer
21.102
964611AG1-324 GEN
Solar/Wind Harmer
3.019
270222AC2-111 GEN
Solar/Wind Helper
1.55
270201AC2-176 GEN
Solar/Wind Harmer
15.004
964611AG1-324 GEN
Solar/Wind Harmer
5.757
946031AF1-268 GEN
Solar/Wind Harmer
12.252
963791AG1-232 GEN
Solar/Wind Harmer
7.322
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.143
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.212
942221AE2-234 GEN
Solar/Wind Harmer
1.551
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.374
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.057
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.055
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.07
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.151
WECLTFEXP_WEC->PJM
CLTF
0.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.579

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P1-2_#15020_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.88 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:310.79
MW Contribution:
23.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.37 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:319.69
MW Contribution:
23.21
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.588
970883AG2-550 GEN
Solar/Wind Harmer
23.209
247536S-71 GEN
Solar/Wind Harmer
18.309
944031AF1-071 GEN
Solar/Wind Helper
0.349
961761AG1-017 GEN
Solar/Wind Harmer
1.459
970885AG2-551 GEN
Solar/Wind Harmer
21.099
964611AG1-324 GEN
Solar/Wind Harmer
3.019
270222AC2-111 GEN
Solar/Wind Helper
1.551
270201AC2-176 GEN
Solar/Wind Harmer
15.002
964611AG1-324 GEN
Solar/Wind Harmer
5.756
946031AF1-268 GEN
Solar/Wind Harmer
12.251
963791AG1-232 GEN
Solar/Wind Harmer
7.32
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.14
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.209
942221AE2-234 GEN
Solar/Wind Harmer
1.551
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.052
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.375
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.027
WECLTFEXP_WEC->PJM
CLTF
0.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.577
NYPJM->LTFIMP_NY
CLTF
0.07
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.152

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#15019_05DESOTO 138_F1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.88 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:310.79
MW Contribution:
23.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.37 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:319.68
MW Contribution:
23.21
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.588
970883AG2-550 GEN
Solar/Wind Harmer
23.209
247536S-71 GEN
Solar/Wind Harmer
18.309
944031AF1-071 GEN
Solar/Wind Helper
0.349
961761AG1-017 GEN
Solar/Wind Harmer
1.459
970885AG2-551 GEN
Solar/Wind Harmer
21.099
964611AG1-324 GEN
Solar/Wind Harmer
3.019
270222AC2-111 GEN
Solar/Wind Helper
1.551
270201AC2-176 GEN
Solar/Wind Harmer
15.002
964611AG1-324 GEN
Solar/Wind Harmer
5.756
946031AF1-268 GEN
Solar/Wind Harmer
12.251
963791AG1-232 GEN
Solar/Wind Harmer
7.32
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.14
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.209
942221AE2-234 GEN
Solar/Wind Harmer
1.551
WECLTFEXP_WEC->PJM
CLTF
0.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.577
NYPJM->LTFIMP_NY
CLTF
0.07
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.152
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.375
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.052
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P1-2_#15020_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.21 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:298.88
MW Contribution:
23.21
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.7 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:307.79
MW Contribution:
23.21
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.588
970883AG2-550 GEN
Solar/Wind Harmer
23.209
247536S-71 GEN
Solar/Wind Harmer
18.309
944031AF1-071 GEN
Solar/Wind Helper
0.349
961761AG1-017 GEN
Solar/Wind Harmer
1.459
970885AG2-551 GEN
Solar/Wind Harmer
21.099
964611AG1-324 GEN
Solar/Wind Harmer
3.019
270222AC2-111 GEN
Solar/Wind Helper
1.551
270201AC2-176 GEN
Solar/Wind Harmer
15.002
964611AG1-324 GEN
Solar/Wind Harmer
5.756
963791AG1-232 GEN
Solar/Wind Harmer
7.32
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.14
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.209
942221AE2-234 GEN
Solar/Wind Harmer
1.551
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.375
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.052
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.07
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.152
WECLTFEXP_WEC->PJM
CLTF
0.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.577

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#15023_05JAY 138_E_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15023_05JAY 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.02 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:293.3
MW Contribution:
23.38
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15023_05JAY 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.46 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:302.08
MW Contribution:
23.38
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.796
970883AG2-550 GEN
Solar/Wind Harmer
23.383
247536S-71 GEN
Solar/Wind Harmer
18.506
944031AF1-071 GEN
Solar/Wind Helper
0.347
961761AG1-017 GEN
Solar/Wind Harmer
1.499
970885AG2-551 GEN
Solar/Wind Harmer
21.257
270222AC2-111 GEN
Solar/Wind Helper
1.544
270201AC2-176 GEN
Solar/Wind Harmer
15.414
963791AG1-232 GEN
Solar/Wind Harmer
7.424
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.749
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.383
942221AE2-234 GEN
Solar/Wind Harmer
1.523
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.095
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.061
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.148
WECLTFEXP_WEC->PJM
CLTF
0.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.192
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.582

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#15176_05JAY 138_E2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15176_05JAY 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.46 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:291.86
MW Contribution:
23.31
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15176_05JAY 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.92 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:300.7
MW Contribution:
23.31
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.705
970883AG2-550 GEN
Solar/Wind Harmer
23.307
247536S-71 GEN
Solar/Wind Harmer
18.42
944031AF1-071 GEN
Solar/Wind Helper
0.348
961761AG1-017 GEN
Solar/Wind Harmer
1.481
970885AG2-551 GEN
Solar/Wind Harmer
21.188
270222AC2-111 GEN
Solar/Wind Helper
1.547
270201AC2-176 GEN
Solar/Wind Harmer
15.234
963791AG1-232 GEN
Solar/Wind Harmer
7.379
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
22.482
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
23.307
942221AE2-234 GEN
Solar/Wind Harmer
1.536
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.057
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.359
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.023
WECLTFEXP_WEC->PJM
CLTF
0.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.192
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.58
NYPJM->LTFIMP_NY
CLTF
0.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
MECLTFEXP_MEC->PJM
CLTF
0.15

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#10527_05BLUFFP 138_E2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.55 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:284.46
MW Contribution:
42.05
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.52 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:289.48
MW Contribution:
42.04
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
64.388
247536S-71 GEN
Solar/Wind Harmer
39.445
970883AG2-550 GEN
Solar/Wind Harmer
42.045
970885AG2-551 GEN
Solar/Wind Harmer
38.223
270543AE2-219 C
Solar/Wind Harmer
42.045
WECLTFEXP_WEC->PJM
CLTF
0.017
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.089
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.467
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.03
MECLTFEXP_MEC->PJM
CLTF
0.051
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.645
NYPJM->LTFIMP_NY
CLTF
0.033
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.034
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.097

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P7-1_#11036___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11036___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.73 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:259.42
MW Contribution:
17.7
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11036___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.88 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:275.08
MW Contribution:
17.7
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
34.504
970883AG2-550 GEN
Solar/Wind Harmer
17.697
247536S-71 GEN
Solar/Wind Harmer
12.304
944031AF1-071 GEN
Solar/Wind Helper
0.592
961761AG1-017 GEN
Solar/Wind Harmer
0.675
253349AC2-067 GEN
Solar/Wind Helper
0.99
970885AG2-551 GEN
Solar/Wind Harmer
16.088
964611AG1-324 GEN
Solar/Wind Harmer
1.232
270383AD1-128 GEN
Solar/Wind Harmer
0
270222AC2-111 GEN
Solar/Wind Helper
2.629
270201AC2-176 GEN
Solar/Wind Harmer
6.941
964611AG1-324 GEN
Solar/Wind Harmer
2.348
253400AC2-068 GEN
Solar/Wind Helper
0.398
946031AF1-268 GEN
Solar/Wind Harmer
2.514
963791AG1-232 GEN
Solar/Wind Harmer
3.771
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.244
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
17.697
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.824
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.077
MECLTFEXP_MEC->PJM
CLTF
0.381
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.136
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.391
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.2
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.046
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.865
WECLTFEXP_WEC->PJM
CLTF
0.116
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.049

Details for AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.69 %
Rating:219.0 MVA
Rating Type:A
MVA to Mitigate:220.51
MW Contribution:
17.96
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG2-637 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.79 %
Rating:219.0 MVA
Rating Type:A
MVA to Mitigate:231.68
MW Contribution:
17.96
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
35.363
970883AG2-550 GEN
Solar/Wind Harmer
17.96
247536S-71 GEN
Solar/Wind Harmer
12.328
944031AF1-071 GEN
Solar/Wind Helper
0.384
961761AG1-017 GEN
Solar/Wind Harmer
0.644
253349AC2-067 GEN
Solar/Wind Helper
0.808
970885AG2-551 GEN
Solar/Wind Harmer
16.327
964611AG1-324 GEN
Solar/Wind Harmer
1.153
270222AC2-111 GEN
Solar/Wind Helper
1.708
270201AC2-176 GEN
Solar/Wind Harmer
6.622
964611AG1-324 GEN
Solar/Wind Harmer
2.199
253400AC2-068 GEN
Solar/Wind Helper
0.325
270024AE2-089 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.774
962031AG1-047 GEN
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
17.96
NYPJM->LTFIMP_NY
CLTF
0.058
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.114
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.333
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.703
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.062
MECLTFEXP_MEC->PJM
CLTF
0.254
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.414
WECLTFEXP_WEC->PJM
CLTF
0.082
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.546
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.037
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A'
 OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1   /*05DESOTO     138.0 - 05MEDFOR     138.0
 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1   /*05DESOTO     138.0 - AF1-268 TP   138.0
END
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1'
 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1   /*05DESOTO     138.0 - AF1-268 TP   138.0
END
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A'
 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1   /*05DESOTO     138.0 - AF1-268 TP   138.0
END
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2'
 OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1   /*AF1-268 TP   138.0 - 05PERCH      138.0
 OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1   /*AG1-324 TP   138.0 - 05PERCH      138.0
END
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'
 OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4   /*05JAY        138.0 - 05JAY 4EQ      1.0
 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1   /*05JAY        138.0 - AG1-324 TP   138.0
 OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4   /*05JAY         34.5 - 05JAY 4EQ      1.0
 OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4   /*05JAY         69.0 - 05JAY 4EQ      1.0
END
CONTINGENCY 'AEP_P4_#15176_05JAY 138_E2_SRT-A'
 OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2   /*05JAY        138.0 - 05JAY 2EQ      1.0
 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1   /*05JAY        138.0 - AG1-324 TP   138.0
 OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2   /*05JAY         69.0 - 05JAY 2EQ      1.0
 OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2   /*05JAY 2EQ      1.0 - 05JAY T2      13.1
 REMOVE SWSHUNT FROM BUS 243319                    /*05JAY        138.0
END
CONTINGENCY 'AEP_P4_#10527_05BLUFFP 138_E2_SRT-A'
 OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1   /*05BLUFFP     138.0 - 05JAY        138.0
 OPEN BRANCH FROM BUS 243253 TO BUS 246014 CKT 1   /*05BLUFFP     138.0 - 05BLUFFPNT    69.0
END
CONTINGENCY 'AEP_P7-1_#11036___SRT-A'
 OPEN BRANCH FROM BUS 243259 TO BUS 243262 CKT 1   /*05CNTRVL     138.0 - 05COLLEGE C  138.0
 OPEN BRANCH FROM BUS 243259 TO BUS 243344 CKT 1   /*05CNTRVL     138.0 - 05MODOC      138.0
 OPEN BRANCH FROM BUS 243259 TO BUS 250345 CKT 1   /*05CNTRVL     138.0 - 08CENTVL      69.0
 OPEN BRANCH FROM BUS 243364 TO BUS 288599 CKT 1   /*05RICHMO     138.0 - 05MODOC_BP   138.0
 OPEN BRANCH FROM BUS 243373 TO BUS 288599 CKT 1   /*05SELMAP     138.0 - 05MODOC_BP   138.0
 OPEN BRANCH FROM BUS 243407 TO BUS 250345 CKT 1   /*05RICHCT      69.0 - 08CENTVL      69.0
 OPEN BRANCH FROM BUS 250345 TO BUS 250734 CKT 1   /*08CENTVL      69.0 - 08NWRICH      69.0
END
CONTINGENCY 'DEOK_P_CIRCUIT3281&13803_SRT-A'
 OPEN BUS 250144   /*08HUSTRC     138.0
 OPEN BUS 250168   /*08TRENTON_2  138.0
END
290085 to 290084 ckt 1
251382 to 251376 ckt 1
971028 to 290085 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-550, AG2-551 and AG2-637 in PJM Transition Cycle 2, Cluster 23 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 23 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 23 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 23 projects have been dispatched online at maximum power output, with 1.0 voltage at the terminal bus.

 

Transition Cycle 2 Cluster 23 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);

       f)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 23 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 peak load case:

       a)       Cluster 23 projects were able to ride through the faults (except for faults where protective action trips a generator(s)).

       b)       The system with Cluster 23 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

Fictitious frequency response at high-side of the shared MPT of AG2-550 and AG2-551 tripped the two queue projects due to the action of under-frequency relays in P1.05 and over-frequency relays in P1.06. Therefore, the frequency relay pickup times in the corresponding relay instances (i.e., 97088303 and 97088503 for P1.05 and 97088301 and 97088501 for P1.06) were set to 20 seconds to avoid fictitious frequency tripping of the unit. The system was found to be stable afterwards.

 

Fictitious frequency response at AG1-017 generator bus tripped the project due to the action of under-frequency/over-frequency relay during P1.26-P1.31 and P1.33-P1.34. Therefore, the frequency relay pickup time in the corresponding relay instance (i.e., 93359413) was set to 20 seconds to avoid fictitious frequency tripping of the unit. The system was found to be stable afterwards.

 

In P1.26 and P1.31, it was observed that AG1-047 generator bus trip because of the high voltage spikes following fault clearance. It is known that voltage spikes are a modeling limitation of WECC generic renewable models . Consequently, the pickup timer of corresponding relay instance (i.e., 96203404) has been increased to 2 cycles, and no further stability issue was observed.

 

In P4.24, AE2-219 terminal voltage experiences an overvoltage post-fault and reaches around 1.08 pu. The overvoltage at the generator terminal did not cause any instability issue.

 

The IPCMD and IQCMD states in the REGCA1 models of AG2-550 showed erratic behavior for some contingencies in which AG2-550 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

The IPCMD and IQCMD states in the REGCA1 models of AG2-551 showed erratic behavior for some contingencies in which AG2-551 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

The IPCMD and IQCMD states in the REGCA1 models of AG2-637 showed erratic behavior for some contingencies in which AG2-637 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

No mitigations were found to be required.

 

 

Table 1: Transition Cycle 2 Cluster 23 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-550

Solar

AEP

100

Randolph - Bluff Point 138 kV

AG2-551

Battery

AEP

50

Randolph - Bluff Point 138 kV

AG2-637

Solar

AEP

150

Randolph - Hayes 138 kV

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AG2-550 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-150Grassy Falls 138kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVEngineering & Procurement
AC1-214Crescent RidgeIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-106North Waldo-Wild Creek 138 kVWithdrawn
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVWithdrawn
AD2-093Marysville 345kVPartially in Service - Under Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVEngineering & Procurement
AE1-102Maddox Creek 345 kVSuspended
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-143Marion County 161 kVUnder Construction
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-175Light Foot 34.5 kVIn Service
AE1-183Maysville-McDowell 69 kVUnder Construction
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVPartially in Service - Under Construction
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-089Pennville-Adams 138 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-214Cole 345 kVUnder Construction
AE2-216Hardin Switch 345 kVSuspended
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-285Maysville 69 kVUnder Construction
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-306Gunn Road 345 kVUnder Construction
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVWithdrawn
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVUnder Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-342Woodstock 69 kVSuspended
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-038Sewellton Jct-Webbs Crossroads 69 kVUnder Construction
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-084Hartford-Almena 69 kVUnder Construction
AF1-086Madera-Westover South 115 kVPartially in Service - Under Construction
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-093Henderson-Stoneboro 69 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVSuspended
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVUnder Construction
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVEngineering & Procurement
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-229Galion-South Berwick 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVUnder Construction
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-302Brookville-Squab Hollow 138 kVUnder Construction
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-014Maddox Creek 345 kVUnder Construction
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVWithdrawn
AF2-039Shawville-Clearfield 34.5 kVUnder Construction
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-122Kirk 138 kVPartially in Service - Under Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVPartially in Service - Under Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-377Logtown 138 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVUnder Construction
AG1-017Jay 138 kVIn Service
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-109Valley 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-198Union City 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-411Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-471Up Church-Wayne County 69 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-508Point Lookout 69 kVWithdrawn
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-029Forest G. Hipple-Dunton Lake 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-332East Elkhart - Elcona Tap 138 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-370Tillman 138 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-424Summersville - Magnolia 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-348Pound 34.5 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Delaware Business Park 138kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-073Yankee 12.5kVIn Service
W1-056Ada-Dunkirk 69kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-550 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
AEPn9746.005HODGIN_BP 138.0 kV to 05HAYES 138.0 kV ckt 1 - Replace ConductorCost Allocated$35,049N/A
AEPn9747.0AG2-637 TP 138.0 kV to 05HODGIN_BP 138.0 kV ckt 1 - Replace conductorCost Allocated$35,049N/A
DEOKb4003.1Rebuild the College Corner (AEP)-Collinsville (DEOK) 138 kV circuit. (DEOK Portion)Contingent$0N/A
DEOKb3944.1Rebuild the McGuffey to Locust 69 kV line (~1.35 miles) with 954 ACSR rail conductor and OPGW.Contingent$0N/A
Grand Total:$70,098

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9746.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9746.0 / AEP-TC2-18625
Title
05HODGIN_BP 138.0 kV to 05HAYES 138.0 kV ckt 1 - Replace Conductor
Description
Replace at Hodgin 138 kV 795kCM AAC 37-Str bus conductor
Total Cost ($USD)
$100,000
Discounted Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$35,049
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
05HAYES-05HODGIN_BP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A277.0 MVA
(All)B355.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-550 ⧉ New AE2-219 swyd (Bluff Point - Randolph 138 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-550, AG2-551
65.6 MW35.0%$35,049
AG2-551 ⧉ New AE2-219 swyd (Bluff Point - Randolph 138 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-550, AG2-551
21.1 MW11.3%$11,268
AG2-637100.5 MW53.7%$53,683

System Reinforcement: n9747.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9747.0 / AEP-TC2-18633
Title
AG2-637 TP 138.0 kV to 05HODGIN_BP 138.0 kV ckt 1 - Replace conductor
Description
Replace at Hodgin 138 kV 795kCM AAC 37-Str bus conductor
Total Cost ($USD)
$100,000
Discounted Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$35,049
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
05HODGIN_BP-AG2-637 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A277.0 MVA
(All)B355.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-550 ⧉ New AE2-219 swyd (Bluff Point - Randolph 138 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-550, AG2-551
65.6 MW35.0%$35,049
AG2-551 ⧉ New AE2-219 swyd (Bluff Point - Randolph 138 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-550, AG2-551
21.1 MW11.3%$11,268
AG2-637100.5 MW53.7%$53,683

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3877.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3877.1
Title
Replace station conductor and switches in the 345 kV yard at Beatty
Description
Replace station conductor and switches in the 345 kV yard at Beatty that are currently limiting the 345 kV lines to Adkins and Chenoweth.
Cost Information
Time Estimate
Feb 01 2028

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05BEATTY-AF1-228 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1442.0 MVA
(All)B1635.0 MVA
(All)C1685.0 MVA
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1442.0 MVA
(All)B1635.0 MVA
(All)C1685.0 MVA

System Reinforcement: n9769.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9769.0 / AEP-TC2-19070
Title
05CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBs
Description
Upgrade/replace Cloverdale 765 kV, 4000 A CBs "CC" and "CC2" to 5000 A
Total Cost ($USD)
$25,000,000
Discounted Total Cost ($USD)
$25,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05CLOVRD-05CLOVRD_RJA 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending)
Title
AEP End Rating 245 MVA Rate B
Description
AEP End Rating 245 MVA Rate B
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A167.0 MVA
(All)B245.0 MVA

System Reinforcement: b4003.1
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
b4003.1 / (Pending)
Title
Rebuild the College Corner (AEP)-Collinsville (DEOK) 138 kV circuit. (DEOK Portion)
Description
Rebuild the College Corner (AEP)-Collinsville (DEOK) 138 kV circuit from the OH/IN state line (tower 10P-X1-129) to Collinsville substation.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 may need this upgrade in-service to be deliverable to the PJM system. If AG2-550 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA480.0 MVA
LLB480.0 MVA
LLC480.0 MVA
SUMA480.0 MVA
SUMB480.0 MVA
SUMC480.0 MVA
WINA520.0 MVA
WINB520.0 MVA
WINC520.0 MVA

System Reinforcement: n9763.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9763.0 / AEP-TC2-19060
Title
05J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace Wavetraps
Description
Replace wave trap on 765 kV Cloverdale line. Replace/upgrade CB's B and B2 with 5000A CBs.
Total Cost ($USD)
$3,300,000
Discounted Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: n9767.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9767.0 / AEP-TC2-19068
Title
05KAMMER_RG 765.0 kV to 05KAMMER 765.0 kV ckt Z1 - Replace Wavetraps
Description
Replace the existing 3000A wave trap at Kammer 765 station towards Guernsey with a 5000A wave trap. Additionally, replace the 3000A circuit breaker QQ1 with a 5000A circuit breaker. Disconnect switches and a relays will be upgraded as well.
Total Cost ($USD)
$4,500,000
Discounted Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3851.2
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.2
Title
Rebuild R.P. Mone – Maddox Creek 345kV line (9.4 miles).
Description
Rebuild R.P. Mone – Maddox Creek 345kV line (9.4 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA
(All)C3774.0 MVA
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA
(All)C3774.0 MVA

System Reinforcement: n9786.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9786.0 / AEP-TC2-19161
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Wave Traps
Description
Replace wave tap at Maliszewski towards Marysville
Total Cost ($USD)
$3,000,000
Discounted Total Cost ($USD)
$3,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B5523.0 MVA

System Reinforcement: n9766.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9766.0 / AEP-TC2_19067
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Wavetrap
Description
Replace 4000A Wavetrap towards Maliszewski with 5000A equivalent
Total Cost ($USD)
$1,100,000
Discounted Total Cost ($USD)
$1,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Nov 12 2027

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B6667.0 MVA
(All)C6868.0 MVA

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA

System Reinforcement: n9759.0
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
n9759.0 / OVEC-TC2-19030
Title
06KYGER 345.0 kV to 05SPORN 345.0 kV ckt 1 - Replace Equipment
Description
Sag study Sporn - Kyger Creek line and replace section #25 OVEC element conductor 12.51 Miles At Sporn replace the following equipment: 2 - 2000 KCM AAC, 91-Str., AA1S1, AA1S2, AAS1, AAS2, KYGER CREEK #1 - PH A, KYGER CREEK #1 - PH B At Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB
Total Cost ($USD)
$38,180,000
Discounted Total Cost ($USD)
$38,180,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1942.0 MVA
(All)B2837.0 MVA
LLA1942.0 MVA
LLB2837.0 MVA

System Reinforcement: n9753.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9753.0 / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Discounted Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1944.0 MVA
(All)B2825.0 MVA
(All)C2468.0 MVA

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Apr 03 2028

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: b2831.2
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
b2831.2
Title
Rebuild the Tanner Creek – Miami Fort 345kV line (DEOK portion), Actual In-service date 5/14/2021
Description
Rebuild the Tanner Creek – Miami Fort 345kV line (DEOK portion) Actual In-service date 5/14/2021
Cost Information
Time Estimate
May 14 2021

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2390.0 MVA
(All)B2390.0 MVA
(All)C2390.0 MVA

System Reinforcement: s2019
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
s2019 / AEP Project Resolves Overload
Title
AEP Project s2019 Resolves DEOK Overload
Description
Install two (2) new 345 kV breakers and move the existing M2 breaker into the new N string at Tanners Creek station. Terminate the Dearborn line and the transformer into the new N string. Install a new 345 kV breaker “T” to complete the T string. Projected in-service date 5/23/2023.
Cost Information
Time Estimate
May 26 2021

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-550 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2403.0 MVA
(All)B2403.0 MVA

System Reinforcement: b2968
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b2968
Title
Upgrade existing 345kV terminal equipment at Tanners Creek station on Tanners Creek - Miami Fort 345kV line, Actual In-Service Date 12/22/2020
Description
Upgrade existing 345kV terminal equipment at Tanners Creek station on Tanners Creek - Miami Fort 345kV line, Actual In-Service Date 12/22/2020
Cost Information
Time Estimate
Dec 22 2020

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B2542.0 MVA

System Reinforcement: b3944.1
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
b3944.1 / (Pending)
Title
Rebuild the McGuffey to Locust 69 kV line (~1.35 miles) with 954 ACSR rail conductor and OPGW.
Description
Rebuild the McGuffey to Locust 69 kV line (~1.35 miles) with 954 ACSR rail conductor and OPGW.
Cost Information
Time Estimate
May 25 2029

Contingent

Note: Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 may need this upgrade in-service to be deliverable to the PJM system. If AG2-550 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
08LOCST1-08MCGFY1 69.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA102.0 MVA
LLB102.0 MVA
LLC120.0 MVA
SUMA102.0 MVA
SUMB102.0 MVA
SUMC120.0 MVA
WINA127.0 MVA
WINB127.0 MVA
WINC140.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-550


AG2-550 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-550 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-550 One Line Diagram

AG2-550 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.