AG2-566 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:51

Briery - Finneywood 230 kV

12.0 MW Capacity / 30.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Gabriel Storage, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $13,127,199 $15,700,656 = 0.84 AND ( $13,127,199 - $15,700,656 ) 30.0 = $-85,782 per MW

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Prince Edward County, Virginia. This project is an increase to the developer’s AG2-198 project(s), which will share the same Point of Interconnection. The AG2-566 project is a 30.0 MW uprate (12.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 110.0 MW with 60.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-566
Project Name:
Briery - Finneywood 230 kV
Project Developer Name:
Gabriel Storage, LLC
State:
Virginia
County:
Prince Edward
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
110.0
MWE:
30.0
MWC:
12.0
Battery Storage Specification:
120.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-566 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system as an uprate to AG2-198 sharing the POI and Attachment Facilities.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-566 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-566Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$849,070$0$0
Other Scope$249,786$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$8,760,079$8,760,079$8,760,079
Network Upgrades$3,147,476$3,147,476$3,147,476
System Reliability Network Upgrades
Steady State Thermal & Voltage$1,219,644$1,219,644$1,219,644
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$14,226,054$13,127,199$13,127,199

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-566

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-566
Project ID: AG2-566
20% of cost allocation for Phase II Network Upgrades:(A) $2,625,440
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $1,570,066
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $1,055,374
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Cut in 230 kV line 235 into a three breaker switchyard.

$4,118,998$1,354,826$317,416$197,996$5,989,236$2,994,618 (See Note 1)
(Pending)

Remote end Network Upgrade at Finneywood Substation.

$81,544$0$8,890$0$90,434$45,217 (See Note 1)
(Pending)

Remote end Network Upgrade at Farmville Substation.

$102,346$9,723$11,258$888$124,215$62,108 (See Note 1)
(Pending)

Remote end Network Upgrade at Briery Substation.

$82,111$0$8,955$0$91,066$45,533 (See Note 1)
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Metering accuracy coupling capacitor voltage transformers (CCVT), metering accuracy current transformers (CT) and associated metering equipment.

$317,977$33,491$141,737$6,366$499,571$249,786 (See Note 1)
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Build a 230kV three breaker ring bus switchyard to support the new generation facility built by Project Developer.

$8,616,617$6,037,797$2,366,357$499,387$17,520,158$8,760,079 (See Note 1)
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

The portion of the interconnection switching station which is associated solely with the single feed to the generating facilities collector station. The equipment associated with the Transmission Owner Interconnection Facilities includes disconnect switch, conductors and connectors.

$768,060$715,020$114,242$100,818$1,698,140$849,070 (See Note 1)
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Cut in 230 kV line 235 into a three breaker switchyard.

$4,118,998$1,354,826$317,416$197,996$5,989,236$2,994,618 (See Note 1)
(Pending)

Remote end Network Upgrade at Finneywood Substation.

$81,544$0$8,890$0$90,434$45,217 (See Note 1)
(Pending)

Remote end Network Upgrade at Farmville Substation.

$102,346$9,723$11,258$888$124,215$62,108 (See Note 1)
(Pending)

Remote end Network Upgrade at Briery Substation.

$82,111$0$8,955$0$91,066$45,533 (See Note 1)
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight for newly constructed 230kV three breaker ring substation, tapping the Briery-Finneywood 230 kV line.

$1,910,523$419,381$408,416$38,380$2,776,700$1,388,350 (See Note 1)
(Pending)

Oversight for metering accuracy coupling capacitor voltage transformers (CCVT), metering accuracy current transformers (CT) and associated equipment for the AG2-198 Generation Interconnection.

$31,876$0$3,557$0$35,433$17,716 (See Note 1)
(Pending)

Oversight for the AG2-198 Generation Interconnection.

$99,752$5,865$22,556$1,034$129,207$64,604 (See Note 1)
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$26,012,820$13,006,410
Developer Build Option$9,236,291$4,618,146

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 47 to 48 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-566 was evaluated as a 30.0 MW (12.0 MW Capacity) injection in the Dominion area.

AG2-566 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 110.0 MW (30.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A_SENS
BreakerAC119.42 %830.0C991.21
2.48
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S_SENS
BreakerAC119.42 %830.0C991.21
2.48
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
SingleAC118.66 %678.68B805.35
2.51
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC109.08 %678.68B740.31
2.98
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC102.11 %830.0C847.48
2.98
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC102.11 %830.0C847.48
2.98
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC100.31 %830.0C832.54
3.02
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S_SENS
BreakerAC118.86 %830.0C986.57
2.48
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A_SENS
BreakerAC118.86 %830.0C986.57
2.48
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
SingleAC117.79 %678.68B799.44
2.51
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC108.09 %678.68B733.57
2.98
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC101.3 %830.0C840.79
2.98
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC101.3 %830.0C840.79
2.98
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC142.62 %699.0C996.88
5.54
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC142.62 %699.0C996.88
5.54
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC141.93 %699.0C992.1
5.54
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC137.85 %571.52B787.83
5.54
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC135.83 %699.0C949.42
5.54
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC135.83 %699.0C949.42
5.54
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC135.0 %571.52B771.57
5.54
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC108.05 %678.68B733.32
0.67
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC107.76 %678.68B731.37
0.67
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC117.67 %678.68B798.63
0.67
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC117.38 %678.68B796.66
0.67
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC139.62 %684.0C954.99
5.54
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC139.62 %684.0C954.99
5.54
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC138.92 %684.0C950.19
5.54
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC135.03 %559.3B755.23
5.54
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC132.9 %684.0C909.01
5.54
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC132.9 %684.0C909.01
5.54
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC132.38 %559.3B740.38
5.54
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
DVP_P4-5: 556X2_SRT-S
BreakerAC135.38 %1050.6C1422.29
4.44
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
DVP_P4-5: 556X1_SRT-S
BreakerAC134.91 %1053.0C1420.61
4.44
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
SingleAC110.74 %678.68B751.6
2.34
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC105.38 %678.68B715.22
2.78
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
SingleAC110.99 %661.76B734.51
2.34
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC105.47 %661.76B697.98
2.78
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC100.19 %809.0C810.51
2.78
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC100.19 %809.0C810.51
2.78
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
SingleAC107.84 %661.76B713.66
2.34
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC102.19 %661.76B676.22
2.78
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC107.97 %678.68B732.8
0.67
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC107.69 %678.68B730.84
0.67
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC121.66 %678.68B825.69
0.67
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC121.36 %678.68B823.67
0.67
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC210.5 %541.0B1138.82
3.58
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC210.16 %541.0B1136.95
3.57
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC210.16 %541.0B1136.95
3.57
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC201.89 %541.0B1092.2
3.53
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC201.87 %541.0B1092.14
3.53
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC172.45 %508.54B876.98
3.58
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC169.26 %508.54B860.77
3.58
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS
TowerAC105.47 %541.0B570.59
1.48
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC146.1 %684.0C999.3
5.54
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC146.1 %684.0C999.3
5.54
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC145.39 %684.0C994.49
5.54
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC141.02 %559.3B788.75
5.54
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC139.35 %684.0C953.13
5.54
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC139.35 %684.0C953.13
5.54
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC138.34 %559.3B773.73
5.54
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC148.37 %699.0C1037.09
5.54
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC148.37 %699.0C1037.09
5.54
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC147.68 %699.0C1032.31
5.54
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC143.16 %571.52B818.17
5.54
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC141.58 %699.0C989.64
5.54
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC141.58 %699.0C989.64
5.54
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC140.31 %571.52B801.9
5.54

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.42 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:991.21
MW Contribution:
2.48
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.545
3144293JTRSVLE
50/50
0.527
972003AH1-546 GEN
Solar/Wind Harmer
21.813
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.168
942461AE2-259 GEN
Solar/Wind Harmer
4.286
3147133PAMPLIN
Solar/Wind Harmer
-0.07
970257AG2-171 GEN
Solar/Wind Harmer
7.117
971775AH1-396 GEN
Solar/Wind Harmer
1.339
959311AF2-222 GEN
Solar/Wind Harmer
17.432
964241AG1-285 GEN
Solar/Wind Harmer
11.676
970221AG2-151 GEN
Solar/Wind Harmer
9.255
316478AD1-087 GEN
Solar/Wind Harmer
1.032
270494AE1-108_GEN
Solar/Wind Harmer
2.999
972205AH1-687 GEN
50/50
22.206
316303AF2-085
50/50
2.484
316322AB2-045
Solar/Wind Harmer
1.467
971845AH1-439 GEN
Solar/Wind Harmer
22.808
316258AE1-075 C
Solar/Wind Harmer
0.76
316405AF2-144 C
Solar/Wind Harmer
0.803
946301AF1-294 GEN
Solar/Wind Harmer
5.991
961791AG1-021 GEN
Solar/Wind Harmer
2.922
3144303KENBRDG
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
12.304
970681AG2-440 GEN
Solar/Wind Harmer
8.167
316238AB2-078_GEN
Solar/Wind Harmer
0.41
316239AB2-077_GEN
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.345
971281AH1-106 GEN
Solar/Wind Harmer
2.085
971283AH1-107 GEN
Solar/Wind Harmer
2.085
316486AD2-202 GEN
Solar/Wind Harmer
0.302
970909AG2-566 GEN
50/50
2.48
3144293JTRSVLE
50/50
0.527
3146776BUCKING
Solar/Wind Harmer
-0.174
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.18
316313AB2-026
Solar/Wind Harmer
0.845
970301AG2-198 GEN
Solar/Wind Harmer
13.062
958211AF2-115 GEN
Solar/Wind Harmer
3.653
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
970323AG2-213 GEN
Solar/Wind Harmer
9.489
971223AH1-071 GEN
Solar/Wind Harmer
1.962
313527AB2-043 GEN
Solar/Wind Harmer
2.256
316237AB2-079_GEN
Solar/Wind Harmer
0.41
3143526WINTERP
Solar/Wind Harmer
-0.066
970099AG2-077 GEN
Solar/Wind Harmer
14.947
962561AG1-105 GEN
Solar/Wind Harmer
6.603
964791AG1-342 GEN
Solar/Wind Harmer
2.424
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.294
316118AC1-105 GEN
Solar/Wind Harmer
0.715
3151931BEARGRDN S1
50/50
5.872
3151911BEARGRDN G1
50/50
4.545
3144293JTRSVLE
50/50
0.527
3144293JTRSVLE
50/50
0.416
970119AG2-088 GEN
50/50
18.628
970937AG2-583 GEN
Solar/Wind Harmer
33.126
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.727
971563AH1-280 GEN
Solar/Wind Harmer
2.922
970685AG2-442 GEN
Solar/Wind Harmer
16.459
315785AD2-033 C
Solar/Wind Harmer
4.092
316034AC1-036 C
Solar/Wind Harmer
0.304
3143226MDLTHAN
Solar/Wind Harmer
-0.016
315693AD1-088 GEN
Solar/Wind Harmer
7.448
971377AH1-170 GEN
Solar/Wind Harmer
1.851
3147623JAMES R
Solar/Wind Harmer
0.229
316131AB2-060 GEN
Solar/Wind Harmer
1.533
3143526WINTERP
Solar/Wind Harmer
-0.066
957481AF2-042 GEN
Solar/Wind Harmer
37.368
970401AG2-262 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
4.94
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.62
971967AH1-528 GEN
Solar/Wind Harmer
16.771
946281AF1-292 GEN
Solar/Wind Harmer
0.19
3137643SOCKMAN
Solar/Wind Harmer
-0.032
970673AG2-436 GEN
Solar/Wind Harmer
17.241
970533AG2-339 GEN
Solar/Wind Harmer
5.254
316426AA2-053 GEN
Solar/Wind Harmer
0.785
970085AG2-068 GEN
Solar/Wind Harmer
4.799
970581AG2-369 GEN
Solar/Wind Harmer
4.127
3146043SEABORD
Solar/Wind Harmer
-0.008
315814AE2-033 C
Solar/Wind Harmer
6.846
315652AC1-086 GEN
Solar/Wind Harmer
8.081
316274AC1-208 GEN
Solar/Wind Harmer
0.772
316318V4-068
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.105
3146033SCOT NK
Solar/Wind Harmer
-0.028
315839AE2-212 C
Solar/Wind Harmer
0.21
316463AE2-346 GEN
Solar/Wind Harmer
0.112
3145513AHOSKIE
Solar/Wind Harmer
0.061
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.689
970657AG2-426 GEN
Solar/Wind Harmer
0.424
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.894
315833AF1-017_GEN
Solar/Wind Harmer
1.255
316311AC2-079 GEN
Solar/Wind Harmer
3.332
315732AD1-074 GEN1
Solar/Wind Harmer
1.322
315733AD1-074 GEN2
Solar/Wind Harmer
1.322
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315697AD1-025 GEN
Solar/Wind Harmer
1.317
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.601
316174AB2-169 GEN
Solar/Wind Harmer
0.993
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
957871AF2-081 GEN
Solar/Wind Harmer
3.196
957861AF2-080 GEN
Solar/Wind Harmer
2.791
316316AC1-027 C
Solar/Wind Harmer
0.195
316236AE1-162_GEN
Solar/Wind Harmer
0.192
3151081ELIZAR1
Adder
5.199
3151091ELIZAR2
Adder
5.109
971445AH1-216 GEN
Solar/Wind Harmer
3.943
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3138266HYDRAULIC
Solar/Wind Helper
0.019
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.379
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.172
316181AB2-040 GEN
Solar/Wind Harmer
1.147
971683AH1-343 GEN
Solar/Wind Harmer
3.493
944011AF1-069 GEN
Solar/Wind Harmer
4.59
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970917AG2-570 GEN
Solar/Wind Harmer
19.442
3156081AA2-088 GEN
Solar/Wind Harmer
2.348
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.5
3145893MURPHYS
Solar/Wind Harmer
0.05
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.265
3143096IRON208
Adder
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.614
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.322
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.26
3145273HOLLAND
Solar/Wind Harmer
-0.005
970657AG2-426 GEN
Solar/Wind Harmer
1.358
970133AG2-095 GEN
Solar/Wind Harmer
0.756
315722AD1-056 GEN
Solar/Wind Harmer
2.391
3146233WITAKRS
Solar/Wind Harmer
0.139
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.004
316458AB2-190 GEN2
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.62
315778AD1-151 GEN
Solar/Wind Harmer
5.844
315735AD1-075 GEN1
Solar/Wind Harmer
0.661
3146376EDENTON
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316123AC1-075 GEN
Solar/Wind Harmer
0.697
3145963POPLR C
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
1.355
316305AF2-043 C
Solar/Wind Harmer
0.193
316246AF1-032 C
Solar/Wind Harmer
0.13
316321Z2-027
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
2.557
316320Y1-086
Solar/Wind Harmer
0.376
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.74
316420AA1-050 GEN
Solar/Wind Harmer
0.728
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
3145933PARMELE
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.342
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
28.996
944601AF1-125 GEN
Solar/Wind Harmer
28.543
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.266
3151171GRAVELC
Adder
0.794
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.511
3132273ORANGE
Solar/Wind Helper
0.026
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.122
315616AA1-038_C
Solar/Wind Helper
0.552
970933AG2-581 GEN
Solar/Wind Harmer
9.133
316248AF1-058 C
Solar/Wind Harmer
0.286
313506AB2-031 GEN
Solar/Wind Harmer
0.66
972187AH1-678 GEN
Adder
2.044
972185AH1-677 GEN
Adder
3.99
971065AG2-659 GEN
Solar/Wind Harmer
5.161
316129AC1-054 GEN
Solar/Wind Harmer
0.886
3147043LAWRENC
Adder
0.815
3150851SPRUNCC
Adder
0.379
960081AF2-299 GEN
Solar/Wind Harmer
0.953
316087AB2-174 GEN
Solar/Wind Harmer
1.183
3145783HORNRTN
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
14.649
970919AG2-571 GEN
Solar/Wind Harmer
2.461
315607AA1-063A GEN
Solar/Wind Harmer
0.776
970087AG2-069 GEN
Solar/Wind Harmer
7.198
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.501
940641AE2-051 GEN
Solar/Wind Harmer
6.871
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.212
3143096IRON208
Adder
0.265
939411AE1-173 GEN
Solar/Wind Harmer
35.461
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.242
316381AD1-082 GEN
Solar/Wind Harmer
0.616
3156021HOLLOMANSOL
Solar/Wind Harmer
0.9
316319Z2-044 C
Solar/Wind Harmer
0.368
3146233WITAKRS
Solar/Wind Harmer
-0.026
316132AB2-190 GEN1
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.654
971069AG2-661 GEN
Solar/Wind Harmer
1.039
315737AD1-076 GEN
Solar/Wind Harmer
1.244
316369SG1_INVT
Solar/Wind Harmer
1.164
316093AE2-104_GEN
Solar/Wind Harmer
1.898
315816AE2-034 GEN
Solar/Wind Harmer
0.526
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.117
3130156CHOWAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.601
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.87
3142053HEARTS
Solar/Wind Harmer
0.076
3145963POPLR C
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
3.175
944631AF1-128 GEN
Adder
27.172
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
319010AE1-072 C
Solar/Wind Harmer
1.29
3146456SLIGO L269
Solar/Wind Harmer
-0.006
3146293MARTNCO
Solar/Wind Harmer
0.04
316494AC1-189 GEN
Solar/Wind Harmer
0.686
944591AF1-124 GEN
Solar/Wind Harmer
29.1
316375AC2-012 GEN
Solar/Wind Harmer
2.204
316036AC1-147 C
Solar/Wind Harmer
0.171
3150981CHESPKA
Adder
0.708
3145336SMITFLD
Solar/Wind Harmer
-0.025
3151171GRAVELC
Adder
0.603
316072AD1-144
Solar/Wind Harmer
0.128
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.765
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.932
3145783HORNRTN
Solar/Wind Harmer
0.745
3145783HORNRTN
Solar/Wind Harmer
0.233
3145783HORNRTN
Solar/Wind Harmer
0.093
316365GEN2_N
Solar/Wind Harmer
0.501
3144356SAPONY
Solar/Wind Harmer
0.256
316315AB2-025 C
Solar/Wind Harmer
0.198
962571AG1-106 GEN
Solar/Wind Harmer
1.033
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.047
316240AF1-291 C
Solar/Wind Harmer
0.208
944641AF1-129 GEN
Adder
29.302
315742AE1-103 GEN
Solar/Wind Harmer
1.626
316083AB2-161 GEN
Solar/Wind Harmer
1.092
315724AD1-057 GEN
Solar/Wind Harmer
1.315
316349AD2-085 GEN
Solar/Wind Harmer
0.587
316065AD1-022 GEN
Solar/Wind Harmer
3.297
316033AB2-134 GEN
Solar/Wind Harmer
2.102
315835AF2-110_GEN
Solar/Wind Harmer
0.816
315614AA2-178 GEN
Solar/Wind Harmer
0.702
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316049AB1-081 GEN
Solar/Wind Harmer
0.696
316263AC1-034 GEN
Solar/Wind Harmer
3.034
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.167
316433W1029_GEN2
Solar/Wind Harmer
1.167
316435W1029_GEN3
Solar/Wind Harmer
1.167
961601AG1-000A GEN
Solar/Wind Harmer
2.525
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.755
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.43
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3150991CHESPKB
Adder
0.594
3150991CHESPKB
Adder
0.58
316005AA1-067
Solar/Wind Harmer
0.128
966001AG1-469 GEN
Solar/Wind Helper
0.182
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.81
MECLTFEXP_MEC->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
3.66
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.346
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.607
NYPJM->LTFIMP_NY
CLTF
0.429

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.42 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:991.21
MW Contribution:
2.48
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.545
3144293JTRSVLE
50/50
0.527
972003AH1-546 GEN
Solar/Wind Harmer
21.813
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.168
942461AE2-259 GEN
Solar/Wind Harmer
4.286
3147133PAMPLIN
Solar/Wind Harmer
-0.07
970257AG2-171 GEN
Solar/Wind Harmer
7.117
971775AH1-396 GEN
Solar/Wind Harmer
1.339
959311AF2-222 GEN
Solar/Wind Harmer
17.432
964241AG1-285 GEN
Solar/Wind Harmer
11.676
970221AG2-151 GEN
Solar/Wind Harmer
9.255
316478AD1-087 GEN
Solar/Wind Harmer
1.032
270494AE1-108_GEN
Solar/Wind Harmer
2.999
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.379
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.172
316181AB2-040 GEN
Solar/Wind Harmer
1.147
971683AH1-343 GEN
Solar/Wind Harmer
3.493
944011AF1-069 GEN
Solar/Wind Harmer
4.59
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970917AG2-570 GEN
Solar/Wind Harmer
19.442
3156081AA2-088 GEN
Solar/Wind Harmer
2.348
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.5
3145893MURPHYS
Solar/Wind Harmer
0.05
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.265
3143096IRON208
Adder
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.614
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.322
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.26
3145273HOLLAND
Solar/Wind Harmer
-0.005
970657AG2-426 GEN
Solar/Wind Harmer
1.358
970133AG2-095 GEN
Solar/Wind Harmer
0.756
315722AD1-056 GEN
Solar/Wind Harmer
2.391
3146233WITAKRS
Solar/Wind Harmer
0.139
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.004
316458AB2-190 GEN2
Solar/Wind Harmer
0.668
972205AH1-687 GEN
50/50
22.206
316303AF2-085
50/50
2.484
316322AB2-045
Solar/Wind Harmer
1.467
971845AH1-439 GEN
Solar/Wind Harmer
22.808
3151931BEARGRDN S1
50/50
5.872
3151911BEARGRDN G1
50/50
4.545
3144293JTRSVLE
50/50
0.527
3144293JTRSVLE
50/50
0.416
970119AG2-088 GEN
50/50
18.628
970937AG2-583 GEN
Solar/Wind Harmer
33.126
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.727
971563AH1-280 GEN
Solar/Wind Harmer
2.922
970685AG2-442 GEN
Solar/Wind Harmer
16.459
315785AD2-033 C
Solar/Wind Harmer
4.092
316034AC1-036 C
Solar/Wind Harmer
0.304
3143226MDLTHAN
Solar/Wind Harmer
-0.016
315693AD1-088 GEN
Solar/Wind Harmer
7.448
971377AH1-170 GEN
Solar/Wind Harmer
1.851
3147623JAMES R
Solar/Wind Harmer
0.229
316131AB2-060 GEN
Solar/Wind Harmer
1.533
3143526WINTERP
Solar/Wind Harmer
-0.066
957481AF2-042 GEN
Solar/Wind Harmer
37.368
970401AG2-262 GEN
Solar/Wind Harmer
0.741
971065AG2-659 GEN
Solar/Wind Harmer
5.161
316129AC1-054 GEN
Solar/Wind Harmer
0.886
3147043LAWRENC
Adder
0.815
3150851SPRUNCC
Adder
0.379
960081AF2-299 GEN
Solar/Wind Harmer
0.953
316087AB2-174 GEN
Solar/Wind Harmer
1.183
3145783HORNRTN
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
14.649
970919AG2-571 GEN
Solar/Wind Harmer
2.461
315607AA1-063A GEN
Solar/Wind Harmer
0.776
970087AG2-069 GEN
Solar/Wind Harmer
7.198
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.501
940641AE2-051 GEN
Solar/Wind Harmer
6.871
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.212
3143096IRON208
Adder
0.265
939411AE1-173 GEN
Solar/Wind Harmer
35.461
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.242
316381AD1-082 GEN
Solar/Wind Harmer
0.616
3156021HOLLOMANSOL
Solar/Wind Harmer
0.9
316319Z2-044 C
Solar/Wind Harmer
0.368
970909AG2-566 GEN
50/50
2.48
3144293JTRSVLE
50/50
0.527
3146776BUCKING
Solar/Wind Harmer
-0.174
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.18
316313AB2-026
Solar/Wind Harmer
0.845
970301AG2-198 GEN
Solar/Wind Harmer
13.062
958211AF2-115 GEN
Solar/Wind Harmer
3.653
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
970323AG2-213 GEN
Solar/Wind Harmer
9.489
971223AH1-071 GEN
Solar/Wind Harmer
1.962
313527AB2-043 GEN
Solar/Wind Harmer
2.256
316237AB2-079_GEN
Solar/Wind Harmer
0.41
3143526WINTERP
Solar/Wind Harmer
-0.066
970099AG2-077 GEN
Solar/Wind Harmer
14.947
962561AG1-105 GEN
Solar/Wind Harmer
6.603
964791AG1-342 GEN
Solar/Wind Harmer
2.424
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.294
316118AC1-105 GEN
Solar/Wind Harmer
0.715
970933AG2-581 GEN
Solar/Wind Harmer
9.133
316248AF1-058 C
Solar/Wind Harmer
0.286
313506AB2-031 GEN
Solar/Wind Harmer
0.66
972187AH1-678 GEN
Adder
2.044
972185AH1-677 GEN
Adder
3.99
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.932
3145783HORNRTN
Solar/Wind Harmer
0.745
3145783HORNRTN
Solar/Wind Harmer
0.233
3145783HORNRTN
Solar/Wind Harmer
0.093
316365GEN2_N
Solar/Wind Harmer
0.501
3144356SAPONY
Solar/Wind Harmer
0.256
316315AB2-025 C
Solar/Wind Harmer
0.198
962571AG1-106 GEN
Solar/Wind Harmer
1.033
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.047
316240AF1-291 C
Solar/Wind Harmer
0.208
944641AF1-129 GEN
Adder
29.302
315742AE1-103 GEN
Solar/Wind Harmer
1.626
316083AB2-161 GEN
Solar/Wind Harmer
1.092
315724AD1-057 GEN
Solar/Wind Harmer
1.315
316349AD2-085 GEN
Solar/Wind Harmer
0.587
316065AD1-022 GEN
Solar/Wind Harmer
3.297
316033AB2-134 GEN
Solar/Wind Harmer
2.102
315835AF2-110_GEN
Solar/Wind Harmer
0.816
315614AA2-178 GEN
Solar/Wind Harmer
0.702
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316049AB1-081 GEN
Solar/Wind Harmer
0.696
316263AC1-034 GEN
Solar/Wind Harmer
3.034
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.167
316433W1029_GEN2
Solar/Wind Harmer
1.167
316435W1029_GEN3
Solar/Wind Harmer
1.167
961601AG1-000A GEN
Solar/Wind Harmer
2.525
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.755
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.43
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3150991CHESPKB
Adder
0.594
3150991CHESPKB
Adder
0.58
316005AA1-067
Solar/Wind Harmer
0.128
966001AG1-469 GEN
Solar/Wind Helper
0.182
3146233WITAKRS
Solar/Wind Harmer
-0.026
316132AB2-190 GEN1
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.654
971069AG2-661 GEN
Solar/Wind Harmer
1.039
315737AD1-076 GEN
Solar/Wind Harmer
1.244
316369SG1_INVT
Solar/Wind Harmer
1.164
316093AE2-104_GEN
Solar/Wind Harmer
1.898
315816AE2-034 GEN
Solar/Wind Harmer
0.526
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.117
3130156CHOWAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.601
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.87
3142053HEARTS
Solar/Wind Harmer
0.076
3145963POPLR C
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
3.175
944631AF1-128 GEN
Adder
27.172
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
319010AE1-072 C
Solar/Wind Harmer
1.29
3146456SLIGO L269
Solar/Wind Harmer
-0.006
3146293MARTNCO
Solar/Wind Harmer
0.04
316494AC1-189 GEN
Solar/Wind Harmer
0.686
944591AF1-124 GEN
Solar/Wind Harmer
29.1
316375AC2-012 GEN
Solar/Wind Harmer
2.204
316036AC1-147 C
Solar/Wind Harmer
0.171
3150981CHESPKA
Adder
0.708
3145336SMITFLD
Solar/Wind Harmer
-0.025
3151171GRAVELC
Adder
0.603
316072AD1-144
Solar/Wind Harmer
0.128
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.765
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.62
315778AD1-151 GEN
Solar/Wind Harmer
5.844
315735AD1-075 GEN1
Solar/Wind Harmer
0.661
3146376EDENTON
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316123AC1-075 GEN
Solar/Wind Harmer
0.697
3145963POPLR C
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
1.355
316305AF2-043 C
Solar/Wind Harmer
0.193
316246AF1-032 C
Solar/Wind Harmer
0.13
316321Z2-027
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
2.557
316320Y1-086
Solar/Wind Harmer
0.376
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.74
316420AA1-050 GEN
Solar/Wind Harmer
0.728
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
3145933PARMELE
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.342
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
28.996
944601AF1-125 GEN
Solar/Wind Harmer
28.543
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.266
3151171GRAVELC
Adder
0.794
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.511
3132273ORANGE
Solar/Wind Helper
0.026
316258AE1-075 C
Solar/Wind Harmer
0.76
316405AF2-144 C
Solar/Wind Harmer
0.803
946301AF1-294 GEN
Solar/Wind Harmer
5.991
961791AG1-021 GEN
Solar/Wind Harmer
2.922
3144303KENBRDG
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
12.304
970681AG2-440 GEN
Solar/Wind Harmer
8.167
316238AB2-078_GEN
Solar/Wind Harmer
0.41
316239AB2-077_GEN
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.345
971281AH1-106 GEN
Solar/Wind Harmer
2.085
971283AH1-107 GEN
Solar/Wind Harmer
2.085
316486AD2-202 GEN
Solar/Wind Harmer
0.302
970831AG2-522 GEN
Solar/Wind Harmer
4.94
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.62
971967AH1-528 GEN
Solar/Wind Harmer
16.771
946281AF1-292 GEN
Solar/Wind Harmer
0.19
3137643SOCKMAN
Solar/Wind Harmer
-0.032
970673AG2-436 GEN
Solar/Wind Harmer
17.241
970533AG2-339 GEN
Solar/Wind Harmer
5.254
316426AA2-053 GEN
Solar/Wind Harmer
0.785
970085AG2-068 GEN
Solar/Wind Harmer
4.799
970581AG2-369 GEN
Solar/Wind Harmer
4.127
3146043SEABORD
Solar/Wind Harmer
-0.008
315814AE2-033 C
Solar/Wind Harmer
6.846
315652AC1-086 GEN
Solar/Wind Harmer
8.081
316274AC1-208 GEN
Solar/Wind Harmer
0.772
316318V4-068
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.105
3146033SCOT NK
Solar/Wind Harmer
-0.028
315839AE2-212 C
Solar/Wind Harmer
0.21
316463AE2-346 GEN
Solar/Wind Harmer
0.112
3145513AHOSKIE
Solar/Wind Harmer
0.061
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.689
970657AG2-426 GEN
Solar/Wind Harmer
0.424
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.894
315833AF1-017_GEN
Solar/Wind Harmer
1.255
316311AC2-079 GEN
Solar/Wind Harmer
3.332
315732AD1-074 GEN1
Solar/Wind Harmer
1.322
315733AD1-074 GEN2
Solar/Wind Harmer
1.322
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315697AD1-025 GEN
Solar/Wind Harmer
1.317
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.601
316174AB2-169 GEN
Solar/Wind Harmer
0.993
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
957871AF2-081 GEN
Solar/Wind Harmer
3.196
957861AF2-080 GEN
Solar/Wind Harmer
2.791
316316AC1-027 C
Solar/Wind Harmer
0.195
316236AE1-162_GEN
Solar/Wind Harmer
0.192
3151081ELIZAR1
Adder
5.199
3151091ELIZAR2
Adder
5.109
971445AH1-216 GEN
Solar/Wind Harmer
3.943
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.122
315616AA1-038_C
Solar/Wind Helper
0.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.81
MECLTFEXP_MEC->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
3.66
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.346
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.607
NYPJM->LTFIMP_NY
CLTF
0.429

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.66 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:805.35
MW Contribution:
2.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.808
3151911BEARGRDN G1
50/50
4.495
3144293JTRSVLE
50/50
0.534
3144293JTRSVLE
50/50
0.422
970119AG2-088 GEN
50/50
15.744
3151531CLOVER1
50/50
2.414
3151591KERR 2
50/50
0.215
3151641KERR 7
50/50
0.215
3147043LAWRENC
50/50
0.914
3151051BRUNSWICKS1
50/50
2.203
3151021BRUNSWICKG1
50/50
1.061
971451AH1-221 GEN
50/50
3.223
315243AE2-183_GT3
50/50
1.321
3151281ROARAP4
50/50
0.091
3150851SPRUNCC
50/50
0.361
3151391GASTONA
50/50
0.185
3151411GASTONB
50/50
0.185
970937AG2-583 GEN
Solar/Wind Harmer
24.603
3146776BUCKING
Solar/Wind Harmer
0.155
3146926FARMVIL
Solar/Wind Harmer
0.184
3143336POWHATN
Solar/Wind Harmer
4.701
971563AH1-280 GEN
Solar/Wind Harmer
2.249
970685AG2-442 GEN
Solar/Wind Harmer
12.826
315785AD2-033 C
Solar/Wind Harmer
1.334
316034AC1-036 C
Solar/Wind Harmer
0.01
315693AD1-088 GEN
Solar/Wind Harmer
6.634
316131AB2-060 GEN
Solar/Wind Harmer
0.41
971377AH1-170 GEN
Solar/Wind Harmer
1.355
3147623JAMES R
Solar/Wind Harmer
0.294
3143226MDLTHAN
Solar/Wind Harmer
0.118
957481AF2-042 GEN
Solar/Wind Harmer
30.149
970401AG2-262 GEN
Solar/Wind Harmer
0.621
3143526WINTERP
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
4.138
316129AC1-054 GEN
Solar/Wind Harmer
0.356
960081AF2-299 GEN
Solar/Wind Harmer
0.774
941031AE2-094 GEN
Solar/Wind Harmer
14.545
970919AG2-571 GEN
Solar/Wind Harmer
2.758
970087AG2-069 GEN
Solar/Wind Harmer
6.122
3145783HORNRTN
Solar/Wind Harmer
0.075
940641AE2-051 GEN
Solar/Wind Harmer
5.96
315607AA1-063A GEN
Solar/Wind Harmer
0.148
316023GEN1_S
Solar/Wind Harmer
0.159
939411AE1-173 GEN
Solar/Wind Harmer
30.495
3146263WOODLND
Solar/Wind Harmer
0.069
3145893MURPHYS
Solar/Wind Harmer
0.275
972205AH1-687 GEN
50/50
21.963
316303AF2-085
50/50
2.099
3151541CLOVER2
50/50
2.397
3151601KERR 3
50/50
0.215
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
963041AG1-153 GEN
50/50
2.149
315244AE2-183_ST
50/50
2.291
3151281ROARAP4
50/50
0.085
971285AH1-108 GEN
50/50
0.591
315779AE2-040
50/50
0.989
971845AH1-439 GEN
Solar/Wind Harmer
17.227
316258AE1-075 C
Solar/Wind Harmer
0.197
946301AF1-294 GEN
Solar/Wind Harmer
4.161
961791AG1-021 GEN
Solar/Wind Harmer
2.024
3144303KENBRDG
Solar/Wind Harmer
0.138
970683AG2-441 GEN
Solar/Wind Harmer
9.631
970681AG2-440 GEN
Solar/Wind Harmer
6.392
316486AD2-202 GEN
Solar/Wind Harmer
0.114
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.36
971283AH1-107 GEN
Solar/Wind Harmer
1.36
970831AG2-522 GEN
Solar/Wind Harmer
3.97
3147173SINAI
Solar/Wind Harmer
0.089
3147243WELCO
Solar/Wind Harmer
0.056
971967AH1-528 GEN
Solar/Wind Harmer
14.085
970673AG2-436 GEN
Solar/Wind Harmer
9.882
970533AG2-339 GEN
Solar/Wind Harmer
5.967
3137643SOCKMAN
Solar/Wind Harmer
0.308
970085AG2-068 GEN
Solar/Wind Harmer
4.081
970581AG2-369 GEN
Solar/Wind Harmer
3.51
316426AA2-053 GEN
Solar/Wind Harmer
0.249
3146043SEABORD
Solar/Wind Harmer
0.073
315814AE2-033 C
Solar/Wind Harmer
5.613
315652AC1-086 GEN
Solar/Wind Harmer
7.598
316274AC1-208 GEN
Solar/Wind Harmer
0.355
3145893MURPHYS
Solar/Wind Harmer
0.186
3151921BEARGRDN G2
50/50
4.495
3144293JTRSVLE
50/50
0.534
970413AG2-270 GEN
50/50
10.515
3151031BRUNSWICKG2
50/50
1.061
3151261ROARAP2
50/50
0.094
3150861SPRUNCD
50/50
0.361
3151391GASTONA
50/50
0.185
3151411GASTONB
50/50
0.185
972003AH1-546 GEN
Solar/Wind Harmer
16.394
3146776BUCKING
Solar/Wind Harmer
0.139
3146926FARMVIL
Solar/Wind Harmer
0.184
3143336POWHATN
Solar/Wind Harmer
3.996
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.64
970257AG2-171 GEN
Solar/Wind Harmer
5.525
971775AH1-396 GEN
Solar/Wind Harmer
0.276
959311AF2-222 GEN
Solar/Wind Harmer
13.645
964241AG1-285 GEN
Solar/Wind Harmer
9.212
970221AG2-151 GEN
Solar/Wind Harmer
6.773
316478AD1-087 GEN
Solar/Wind Harmer
0.389
270494AE1-108_GEN
Solar/Wind Harmer
1.182
3147043LAWRENC
Solar/Wind Harmer
0.057
944011AF1-069 GEN
Solar/Wind Harmer
4.752
316181AB2-040 GEN
Solar/Wind Harmer
0.112
970917AG2-570 GEN
Solar/Wind Harmer
6.894
971683AH1-343 GEN
Solar/Wind Harmer
2.8
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.069
316011AB1-132 GEN
Solar/Wind Harmer
1.253
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3145893MURPHYS
Solar/Wind Harmer
0.115
3145893MURPHYS
Solar/Wind Harmer
0.069
3145893MURPHYS
Solar/Wind Harmer
0.306
3145796HORNRTN
Solar/Wind Harmer
0.225
3145796HORNRTN
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
3145823KELFORD
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.067
3156021HOLLOMANSOL
Solar/Wind Harmer
0.292
3146233WITAKRS
Solar/Wind Harmer
0.256
3146206CASHIE
Solar/Wind Harmer
0.064
971547AH1-271 GEN
Solar/Wind Harmer
1.368
315737AD1-076 GEN
Solar/Wind Harmer
0.816
316381AD1-082 GEN
Solar/Wind Harmer
0.064
315816AE2-034 GEN
Solar/Wind Harmer
0.27
3145663CRESWEL
Solar/Wind Harmer
0.177
971163AH1-040 GEN
Solar/Wind Harmer
5.071
316093AE2-104_GEN
Solar/Wind Harmer
1.064
3130156CHOWAN
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.204
3146516WINFALL
Solar/Wind Harmer
0.063
3145963POPLR C
Solar/Wind Harmer
0.063
3142543TWELFTH
Solar/Wind Harmer
0.006
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
319010AE1-072 C
Solar/Wind Harmer
0.311
3146456SLIGO L269
Solar/Wind Harmer
0.062
316359AB2-059 GEN
Solar/Wind Harmer
0.222
3142053HEARTS
Solar/Wind Harmer
0.11
944591AF1-124 GEN
Solar/Wind Harmer
14.099
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150981CHESPKA
Adder
0.776
3146293MARTNCO
Solar/Wind Harmer
0.057
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.062
3145493TOT1
Solar/Wind Harmer
0.275
316494AC1-189 GEN
Solar/Wind Harmer
0.209
316072AD1-144
Solar/Wind Harmer
0.022
315671AE2-027_GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
315773AC2-141 GEN
Solar/Wind Harmer
2.232
3145336SMITFLD
Solar/Wind Harmer
0.244
316132AB2-190 GEN1
Solar/Wind Harmer
0.322
971069AG2-661 GEN
Solar/Wind Harmer
1.073
961611AG1-000B GEN
Solar/Wind Harmer
3.157
3145796HORNRTN
Solar/Wind Harmer
0.272
3145796HORNRTN
Solar/Wind Harmer
0.068
316212AC1-099_GEN
Solar/Wind Harmer
0.35
3146173TUNIS
Solar/Wind Harmer
0.068
3145823KELFORD
Solar/Wind Harmer
0.067
3145273HOLLAND
Solar/Wind Harmer
0.049
315722AD1-056 GEN
Solar/Wind Harmer
2.24
3146233WITAKRS
Solar/Wind Harmer
0.322
3146233WITAKRS
Solar/Wind Harmer
0.044
3146206CASHIE
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.042
316222AC1-221 GEN
Solar/Wind Harmer
0.263
315735AD1-075 GEN1
Solar/Wind Harmer
0.181
315813AE1-149 C
Solar/Wind Harmer
3.388
970657AG2-426 GEN
Solar/Wind Harmer
1.423
3146376EDENTON
Solar/Wind Harmer
0.063
316283AC2-100 C
Solar/Wind Harmer
0.123
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.011
3145963POPLR C
Solar/Wind Harmer
0.063
316246AF1-032 C
Solar/Wind Harmer
0.028
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.062
971153AH1-033 GEN
Solar/Wind Harmer
0.723
316017AA1-139 ULT1
Solar/Wind Harmer
0.033
971623AH1-311 GEN
Solar/Wind Harmer
0.125
944581AF1-123 GEN
Solar/Wind Harmer
14.049
944601AF1-125 GEN
Solar/Wind Harmer
13.832
3151101ELIZAR3
Adder
5.774
3144873MCLAUGH
Solar/Wind Harmer
0.002
961601AG1-000A GEN
Solar/Wind Harmer
4.415
3145933PARMELE
Solar/Wind Harmer
0.062
3146073TAR RVR
Solar/Wind Harmer
0.062
3146083TARBORO
Solar/Wind Harmer
0.062
3144536CHRHLND
Solar/Wind Harmer
0.009
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
3145336SMITFLD
Solar/Wind Harmer
0.024
316123AC1-075 GEN
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
0.581
316458AB2-190 GEN2
Solar/Wind Harmer
0.322
315778AD1-151 GEN
Solar/Wind Harmer
4.826
3145893MURPHYS
Solar/Wind Harmer
0.069
3145796HORNRTN
Solar/Wind Harmer
0.218
3145796HORNRTN
Solar/Wind Harmer
0.027
316210AC1-098 GEN
Solar/Wind Harmer
0.627
3146033SCOT NK
Solar/Wind Harmer
0.27
316463AE2-346 GEN
Solar/Wind Harmer
0.057
3145513AHOSKIE
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.133
3145683EARLEYS
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.067
316327AA2-057 GEN
Solar/Wind Harmer
0.097
3146206CASHIE
Solar/Wind Harmer
0.064
970601AG2-382 GEN
Solar/Wind Harmer
2.394
315732AD1-074 GEN1
Solar/Wind Harmer
0.362
315733AD1-074 GEN2
Solar/Wind Harmer
0.362
3143316POE
Solar/Wind Harmer
0.252
3130546PLYMOUTH
Solar/Wind Harmer
0.064
970657AG2-426 GEN
Solar/Wind Harmer
0.466
316311AC2-079 GEN
Solar/Wind Harmer
1.819
3130156CHOWAN
Solar/Wind Harmer
0.063
3130156CHOWAN
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.173
313526AB2-022
Solar/Wind Harmer
0.033
3146406KITTY HAWK
Solar/Wind Harmer
0.008
957871AF2-081 GEN
Solar/Wind Harmer
3.112
316316AC1-027 C
Solar/Wind Harmer
0.059
3151081ELIZAR1
Adder
5.701
3151091ELIZAR2
Adder
5.602
3145573BETHELC
Solar/Wind Harmer
0.062
3145573BETHELC
Solar/Wind Harmer
0.062
957861AF2-080 GEN
Solar/Wind Harmer
2.662
3145746EVERETS
Solar/Wind Harmer
0.245
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
971445AH1-216 GEN
Solar/Wind Harmer
4.283
315697AD1-025 GEN
Solar/Wind Harmer
0.064
3151201GRAVEL4
Adder
4.378
3151221GRAVEL6
Adder
4.373
3151191GRAVEL3
Adder
4.322
3151211GRAVEL5
Adder
4.322
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.107
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
315616AA1-038_C
Solar/Wind Helper
0.562
961611AG1-000B GEN
Solar/Wind Harmer
1.605
3151171GRAVELC
Adder
0.841
3143096IRON208
Adder
0.248
3143096IRON208
Adder
0.243
3148013FISHERV
Solar/Wind Helper
0.179
316499AE2-029_GEN
Solar/Wind Helper
0.52
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.259
3151171GRAVELC
Adder
0.64
3143096IRON208
Adder
0.248
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.785
3147666LOUISA
Solar/Wind Helper
0.45
970909AG2-566 GEN
50/50
2.507
3144293JTRSVLE
50/50
0.534
970535AG2-341 GEN
50/50
2.068
3151581KERR 1
50/50
0.077
3152661PLYWOOD A
50/50
0.21
3151041BRUNSWICKG3
50/50
1.061
972187AH1-678 GEN
50/50
2.435
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.315
972185AH1-677 GEN
50/50
4.769
3151261ROARAP2
50/50
0.091
3146776BUCKING
Solar/Wind Harmer
1.546
3146776BUCKING
Solar/Wind Harmer
0.125
316336AC2-165 C
Solar/Wind Harmer
15.338
316313AB2-026
Solar/Wind Harmer
0.165
970301AG2-198 GEN
Solar/Wind Harmer
10.027
958211AF2-115 GEN
Solar/Wind Harmer
2.53
3147133PAMPLIN
Solar/Wind Harmer
0.204
3147133PAMPLIN
Solar/Wind Harmer
0.163
970323AG2-213 GEN
Solar/Wind Harmer
7.367
971223AH1-071 GEN
Solar/Wind Harmer
1.259
970099AG2-077 GEN
Solar/Wind Harmer
12.06
962561AG1-105 GEN
Solar/Wind Harmer
5.245
964791AG1-342 GEN
Solar/Wind Harmer
2.031
3146843MT LREL
Solar/Wind Harmer
0.106
3146843MT LREL
Solar/Wind Harmer
0.106
3143526WINTERP
Solar/Wind Harmer
0.509
316118AC1-105 GEN
Solar/Wind Harmer
0.25
970933AG2-581 GEN
Solar/Wind Harmer
7.587
313506AB2-031 GEN
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.095
3145783HORNRTN
Solar/Wind Harmer
1.334
3145783HORNRTN
Solar/Wind Harmer
1.067
3145783HORNRTN
Solar/Wind Harmer
0.333
3145783HORNRTN
Solar/Wind Harmer
0.133
316365GEN2_N
Solar/Wind Harmer
0.159
3144356SAPONY
Solar/Wind Harmer
0.593
316315AB2-025 C
Solar/Wind Harmer
0.057
962571AG1-106 GEN
Solar/Wind Harmer
0.983
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.461
3145893MURPHYS
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.204
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
316140AB2-099
Solar/Wind Harmer
0.024
315742AE1-103 GEN
Solar/Wind Harmer
0.988
315724AD1-057 GEN
Solar/Wind Harmer
1.249
316065AD1-022 GEN
Solar/Wind Harmer
2.944
315614AA2-178 GEN
Solar/Wind Harmer
0.361
316349AD2-085 GEN
Solar/Wind Harmer
0.042
315835AF2-110_GEN
Solar/Wind Harmer
0.434
3146376EDENTON
Solar/Wind Harmer
0.281
3146376EDENTON
Solar/Wind Harmer
0.281
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146386ELIZ CT
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.25
3137176SLIGO L2192
Solar/Wind Harmer
0.249
3146456SLIGO L269
Solar/Wind Harmer
1.106
316049AB1-081 GEN
Solar/Wind Harmer
0.356
316339AD2-160 GEN
Solar/Wind Harmer
0.1
316388AE2-253 GEN
Solar/Wind Harmer
0.194
316263AC1-034 GEN
Solar/Wind Harmer
2.375
3145506HICKORY
Solar/Wind Harmer
0.25
3145506HICKORY
Solar/Wind Harmer
0.15
3145506HICKORY
Solar/Wind Harmer
0.037
3150991CHESPKB
Adder
0.651
3150991CHESPKB
Adder
0.636
961601AG1-000A GEN
Solar/Wind Harmer
1.104
3145933PARMELE
Solar/Wind Harmer
0.124
3145933PARMELE
Solar/Wind Harmer
0.062
3145493TOT1
Solar/Wind Harmer
0.143
3145453TOT5
Solar/Wind Harmer
0.086
3145603CNETO
Solar/Wind Harmer
0.057
316005AA1-067
Solar/Wind Harmer
0.066
316294AC1-161 GEN
Solar/Wind Harmer
1.057
944641AF1-129 GEN
Adder
29.012
316033AB2-134 GEN
Solar/Wind Harmer
0
966001AG1-469 GEN
Solar/Wind Helper
0.186
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.099
MECLTFEXP_MEC->PJM
CLTF
0.124
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
4.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.187
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.062
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.167
LAGNLTFEXP_LAGN->PJM
CLTF
1.43
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.724
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.695
NYPJM->LTFIMP_NY
CLTF
0.461

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.08 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:740.31
MW Contribution:
2.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.43 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:939.5
MW Contribution:
3.01
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
29.134
3151541CLOVER2
50/50
2.196
3151601KERR 3
50/50
0.2
3151611KERR 4
50/50
0.2
3151621KERR 5
50/50
0.2
3151631KERR 6
50/50
0.2
971845AH1-439 GEN
Solar/Wind Harmer
22.245
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3144303KENBRDG
Solar/Wind Harmer
0.154
970683AG2-441 GEN
Solar/Wind Harmer
10.284
970681AG2-440 GEN
Solar/Wind Harmer
6.826
316486AD2-202 GEN
Solar/Wind Harmer
0.105
3147173SINAI
Solar/Wind Harmer
0.083
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.367
971967AH1-528 GEN
Solar/Wind Harmer
9.13
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
970413AG2-270 GEN
50/50
9.635
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
3151581KERR 1
50/50
0.071
3152661PLYWOOD A
50/50
0.197
316336AC2-165 C
Solar/Wind Harmer
32.562
3146776BUCKING
Solar/Wind Harmer
2.001
3146776BUCKING
Solar/Wind Harmer
0.162
970301AG2-198 GEN
Solar/Wind Harmer
11.924
958211AF2-115 GEN
Solar/Wind Harmer
2.96
3147133PAMPLIN
Solar/Wind Harmer
0.235
3147133PAMPLIN
Solar/Wind Harmer
0.188
970323AG2-213 GEN
Solar/Wind Harmer
8.199
962561AG1-105 GEN
Solar/Wind Harmer
5.114
964791AG1-342 GEN
Solar/Wind Harmer
1.967
3146843MT LREL
Solar/Wind Harmer
0.102
3146843MT LREL
Solar/Wind Harmer
0.102
970099AG2-077 GEN
Solar/Wind Harmer
10.732
316118AC1-105 GEN
Solar/Wind Harmer
0.237
970933AG2-581 GEN
Solar/Wind Harmer
5.491
966001AG1-469 GEN
Solar/Wind Helper
0.139
972003AH1-546 GEN
Solar/Wind Harmer
21.695
3146776BUCKING
Solar/Wind Harmer
0.18
3146926FARMVIL
Solar/Wind Harmer
0.23
942461AE2-259 GEN
Solar/Wind Harmer
0.001
970221AG2-151 GEN
Solar/Wind Harmer
14.27
3147133PAMPLIN
Solar/Wind Harmer
0.737
270494AE1-108_GEN
Solar/Wind Harmer
2.499
970257AG2-171 GEN
Solar/Wind Harmer
6.149
971775AH1-396 GEN
Solar/Wind Harmer
0.307
959311AF2-222 GEN
Solar/Wind Harmer
14.386
964241AG1-285 GEN
Solar/Wind Harmer
9.36
315821AE2-092 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.357
958131AF2-107 GEN
Solar/Wind Harmer
2.368
3147043LAWRENC
Solar/Wind Harmer
0.047
971683AH1-343 GEN
Solar/Wind Harmer
2.656
316123AC1-075 GEN
Solar/Wind Harmer
0.079
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
3151531CLOVER1
50/50
2.212
3151591KERR 2
50/50
0.2
3151641KERR 7
50/50
0.2
3147043LAWRENC
50/50
0.756
970937AG2-583 GEN
Solar/Wind Harmer
39.417
3146776BUCKING
Solar/Wind Harmer
0.2
3146926FARMVIL
Solar/Wind Harmer
0.23
971377AH1-170 GEN
Solar/Wind Harmer
2.854
3147623JAMES R
Solar/Wind Harmer
0.62
971563AH1-280 GEN
Solar/Wind Harmer
2.631
970685AG2-442 GEN
Solar/Wind Harmer
14.043
315785AD2-033 C
Solar/Wind Harmer
1.465
316034AC1-036 C
Solar/Wind Harmer
0.011
315693AD1-088 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.416
970401AG2-262 GEN
Solar/Wind Harmer
0.601
957481AF2-042 GEN
Solar/Wind Harmer
26.83
971065AG2-659 GEN
Solar/Wind Harmer
3.622
316129AC1-054 GEN
Solar/Wind Harmer
0.307
960081AF2-299 GEN
Solar/Wind Harmer
0.544
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.11 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:847.48
MW Contribution:
2.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.35 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1056.99
MW Contribution:
3.01
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
972003AH1-546 GEN
Solar/Wind Harmer
28.565
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.235
970221AG2-151 GEN
Solar/Wind Harmer
18.789
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270494AE1-108_GEN
Solar/Wind Harmer
6.111
970257AG2-171 GEN
Solar/Wind Harmer
8.096
971775AH1-396 GEN
Solar/Wind Harmer
1.523
959311AF2-222 GEN
Solar/Wind Harmer
18.979
964241AG1-285 GEN
Solar/Wind Harmer
12.324
315821AE2-092 GEN
Solar/Wind Harmer
2.69
316478AD1-087 GEN
Solar/Wind Harmer
0.999
958131AF2-107 GEN
Solar/Wind Harmer
3.152
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.854
971683AH1-343 GEN
Solar/Wind Harmer
3.498
316123AC1-075 GEN
Solar/Wind Harmer
0.72
966621AG1-532 GEN
Solar/Wind Harmer
0.129
972205AH1-687 GEN
50/50
29.134
316322AB2-045
Solar/Wind Harmer
1.888
971845AH1-439 GEN
Solar/Wind Harmer
29.289
946301AF1-294 GEN
Solar/Wind Harmer
7.102
961791AG1-021 GEN
Solar/Wind Harmer
3.465
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
13.541
970681AG2-440 GEN
Solar/Wind Harmer
8.987
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316486AD2-202 GEN
Solar/Wind Harmer
0.293
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.433
971967AH1-528 GEN
Solar/Wind Harmer
12.053
946281AF1-292 GEN
Solar/Wind Harmer
0.143
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
970535AG2-341 GEN
50/50
2.001
316336AC2-165 C
Solar/Wind Harmer
45.084
3146776BUCKING
Solar/Wind Harmer
-0.224
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.7
958211AF2-115 GEN
Solar/Wind Harmer
4.331
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
970323AG2-213 GEN
Solar/Wind Harmer
10.795
313527AB2-043 GEN
Solar/Wind Harmer
2.357
316237AB2-079_GEN
Solar/Wind Harmer
0.426
962561AG1-105 GEN
Solar/Wind Harmer
6.734
964791AG1-342 GEN
Solar/Wind Harmer
2.459
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
14.131
316118AC1-105 GEN
Solar/Wind Harmer
0.714
315687AD1-152 GEN
Solar/Wind Harmer
1.245
316248AF1-058 C
Solar/Wind Harmer
0.281
970933AG2-581 GEN
Solar/Wind Harmer
7.23
966001AG1-469 GEN
Solar/Wind Helper
0.139
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
970937AG2-583 GEN
Solar/Wind Harmer
51.899
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.758
3147623JAMES R
Solar/Wind Harmer
0.465
971563AH1-280 GEN
Solar/Wind Harmer
3.465
970685AG2-442 GEN
Solar/Wind Harmer
18.491
315785AD2-033 C
Solar/Wind Harmer
4.603
316034AC1-036 C
Solar/Wind Harmer
0.329
315693AD1-088 GEN
Solar/Wind Harmer
7.766
316131AB2-060 GEN
Solar/Wind Harmer
1.615
970401AG2-262 GEN
Solar/Wind Harmer
0.751
957481AF2-042 GEN
Solar/Wind Harmer
35.327
971065AG2-659 GEN
Solar/Wind Harmer
4.769
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.712
960081AF2-299 GEN
Solar/Wind Harmer
0.716
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.11 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:847.48
MW Contribution:
2.98
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
316336AC2-165 C
Solar/Wind Harmer
45.084
3146776BUCKING
Solar/Wind Harmer
-0.224
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.7
958211AF2-115 GEN
Solar/Wind Harmer
4.331
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
970323AG2-213 GEN
Solar/Wind Harmer
10.795
313527AB2-043 GEN
Solar/Wind Harmer
2.357
316237AB2-079_GEN
Solar/Wind Harmer
0.426
962561AG1-105 GEN
Solar/Wind Harmer
6.734
964791AG1-342 GEN
Solar/Wind Harmer
2.459
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
14.131
316118AC1-105 GEN
Solar/Wind Harmer
0.714
315687AD1-152 GEN
Solar/Wind Harmer
1.245
316248AF1-058 C
Solar/Wind Harmer
0.281
970933AG2-581 GEN
Solar/Wind Harmer
7.23
966001AG1-469 GEN
Solar/Wind Helper
0.139
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
972003AH1-546 GEN
Solar/Wind Harmer
28.565
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.235
970221AG2-151 GEN
Solar/Wind Harmer
18.789
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270494AE1-108_GEN
Solar/Wind Harmer
6.111
970257AG2-171 GEN
Solar/Wind Harmer
8.096
971775AH1-396 GEN
Solar/Wind Harmer
1.523
959311AF2-222 GEN
Solar/Wind Harmer
18.979
964241AG1-285 GEN
Solar/Wind Harmer
12.324
315821AE2-092 GEN
Solar/Wind Harmer
2.69
316478AD1-087 GEN
Solar/Wind Harmer
0.999
958131AF2-107 GEN
Solar/Wind Harmer
3.152
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.854
971683AH1-343 GEN
Solar/Wind Harmer
3.498
316123AC1-075 GEN
Solar/Wind Harmer
0.72
966621AG1-532 GEN
Solar/Wind Harmer
0.129
972205AH1-687 GEN
50/50
29.134
316322AB2-045
Solar/Wind Harmer
1.888
971845AH1-439 GEN
Solar/Wind Harmer
29.289
946301AF1-294 GEN
Solar/Wind Harmer
7.102
961791AG1-021 GEN
Solar/Wind Harmer
3.465
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
13.541
970681AG2-440 GEN
Solar/Wind Harmer
8.987
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316486AD2-202 GEN
Solar/Wind Harmer
0.293
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.433
971967AH1-528 GEN
Solar/Wind Harmer
12.053
946281AF1-292 GEN
Solar/Wind Harmer
0.143
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
970937AG2-583 GEN
Solar/Wind Harmer
51.899
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.758
3147623JAMES R
Solar/Wind Harmer
0.465
971563AH1-280 GEN
Solar/Wind Harmer
3.465
970685AG2-442 GEN
Solar/Wind Harmer
18.491
315785AD2-033 C
Solar/Wind Harmer
4.603
316034AC1-036 C
Solar/Wind Harmer
0.329
315693AD1-088 GEN
Solar/Wind Harmer
7.766
316131AB2-060 GEN
Solar/Wind Harmer
1.615
970401AG2-262 GEN
Solar/Wind Harmer
0.751
957481AF2-042 GEN
Solar/Wind Harmer
35.327
971065AG2-659 GEN
Solar/Wind Harmer
4.769
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.712
960081AF2-299 GEN
Solar/Wind Harmer
0.716
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:832.54
MW Contribution:
3.02
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
3.024
3144293JTRSVLE
50/50
0.637
970535AG2-341 GEN
50/50
2.722
3151581KERR 1
50/50
0.1
3152661PLYWOOD A
50/50
0.29
3146776BUCKING
Solar/Wind Harmer
-0.183
3146776BUCKING
Solar/Wind Harmer
-0.015
316336AC2-165 C
Solar/Wind Harmer
20.18
970301AG2-198 GEN
Solar/Wind Harmer
15.924
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.412
3151921BEARGRDN G2
50/50
4.556
3144293JTRSVLE
50/50
0.637
970413AG2-270 GEN
50/50
16.613
972003AH1-546 GEN
Solar/Wind Harmer
21.973
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.023
942461AE2-259 GEN
Solar/Wind Harmer
5.02
3147133PAMPLIN
Solar/Wind Harmer
-0.089
3143336POWHATN
Solar/Wind Harmer
2.774
970257AG2-171 GEN
Solar/Wind Harmer
9.023
971775AH1-396 GEN
Solar/Wind Harmer
1.698
959311AF2-222 GEN
Solar/Wind Harmer
24.67
964241AG1-285 GEN
Solar/Wind Harmer
16.962
316478AD1-087 GEN
Solar/Wind Harmer
1.722
970221AG2-151 GEN
Solar/Wind Harmer
9.368
316003AC1-222 GEN
Solar/Wind Harmer
1.28
971683AH1-343 GEN
Solar/Wind Harmer
5.189
270494AE1-108_GEN
Solar/Wind Harmer
3.072
3147043LAWRENC
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
1.038
316222AC1-221 GEN
Solar/Wind Harmer
0.852
316283AC2-100 C
Solar/Wind Harmer
0.78
966621AG1-532 GEN
Solar/Wind Harmer
0.163
316181AB2-040 GEN
Solar/Wind Harmer
1.095
316190AA2-174 GEN
Solar/Wind Harmer
0.089
3148013FISHERV
Solar/Wind Helper
0.17
316499AE2-029_GEN
Solar/Wind Helper
0.493
3132273ORANGE
Solar/Wind Helper
0.025
972205AH1-687 GEN
50/50
22.263
3151541CLOVER2
50/50
3.787
3151601KERR 3
50/50
0.28
3151611KERR 4
50/50
0.28
3151621KERR 5
50/50
0.28
3151631KERR 6
50/50
0.28
316322AB2-045
Solar/Wind Harmer
1.543
971845AH1-439 GEN
Solar/Wind Harmer
24.09
946301AF1-294 GEN
Solar/Wind Harmer
7.236
961791AG1-021 GEN
Solar/Wind Harmer
3.53
316313AB2-026
Solar/Wind Harmer
0.74
970323AG2-213 GEN
Solar/Wind Harmer
12.03
970933AG2-581 GEN
Solar/Wind Harmer
20.164
970099AG2-077 GEN
Solar/Wind Harmer
26.441
313527AB2-043 GEN
Solar/Wind Harmer
3.123
316237AB2-079_GEN
Solar/Wind Harmer
0.568
315687AD1-152 GEN
Solar/Wind Harmer
2.079
962561AG1-105 GEN
Solar/Wind Harmer
9.401
964791AG1-342 GEN
Solar/Wind Harmer
3.473
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
316118AC1-105 GEN
Solar/Wind Harmer
1.04
316248AF1-058 C
Solar/Wind Harmer
0.424
971223AH1-071 GEN
Solar/Wind Harmer
1.137
942751AE2-291 GEN
Solar/Wind Harmer
5.435
313506AB2-031 GEN
Solar/Wind Harmer
0.63
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.064
3145783HORNRTN
Solar/Wind Harmer
0.888
3145783HORNRTN
Solar/Wind Harmer
0.71
3145783HORNRTN
Solar/Wind Harmer
0.222
3145783HORNRTN
Solar/Wind Harmer
0.089
3143526WINTERP
Solar/Wind Harmer
-0.038
966001AG1-469 GEN
Solar/Wind Helper
0.179
316258AE1-075 C
Solar/Wind Harmer
0.666
316405AF2-144 C
Solar/Wind Harmer
0.703
970683AG2-441 GEN
Solar/Wind Harmer
17.252
970681AG2-440 GEN
Solar/Wind Harmer
11.45
3144303KENBRDG
Solar/Wind Harmer
-0.019
971967AH1-528 GEN
Solar/Wind Harmer
40.435
316486AD2-202 GEN
Solar/Wind Harmer
0.504
316238AB2-078_GEN
Solar/Wind Harmer
0.568
316239AB2-077_GEN
Solar/Wind Harmer
0.568
3147173SINAI
Solar/Wind Harmer
-0.014
3147243WELCO
Solar/Wind Harmer
-0.009
970831AG2-522 GEN
Solar/Wind Harmer
6.062
946281AF1-292 GEN
Solar/Wind Harmer
0.18
3137643SOCKMAN
Solar/Wind Harmer
-0.031
316233AE1-074 FULL
Solar/Wind Harmer
0.199
971281AH1-106 GEN
Solar/Wind Harmer
1.201
971283AH1-107 GEN
Solar/Wind Harmer
1.201
316426AA2-053 GEN
Solar/Wind Harmer
0.732
3146043SEABORD
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.695
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.102
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.524
3151931BEARGRDN S1
50/50
5.887
3151911BEARGRDN G1
50/50
4.556
3144293JTRSVLE
50/50
0.637
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
3.815
3151591KERR 2
50/50
0.28
3151641KERR 7
50/50
0.28
3146776BUCKING
Solar/Wind Harmer
-0.018
970937AG2-583 GEN
Solar/Wind Harmer
32.126
3146926FARMVIL
Solar/Wind Harmer
-0.023
971563AH1-280 GEN
Solar/Wind Harmer
3.53
3143336POWHATN
Solar/Wind Harmer
3.264
970685AG2-442 GEN
Solar/Wind Harmer
22.356
316034AC1-036 C
Solar/Wind Harmer
0.432
315785AD2-033 C
Solar/Wind Harmer
5.252
315693AD1-088 GEN
Solar/Wind Harmer
11.47
957481AF2-042 GEN
Solar/Wind Harmer
66.102
316131AB2-060 GEN
Solar/Wind Harmer
2.106
970401AG2-262 GEN
Solar/Wind Harmer
1.061
971377AH1-170 GEN
Solar/Wind Harmer
1.874
3147623JAMES R
Solar/Wind Harmer
0.232
971065AG2-659 GEN
Solar/Wind Harmer
6.58
316129AC1-054 GEN
Solar/Wind Harmer
1.111
3147043LAWRENC
Adder
0.921
3143226MDLTHAN
Solar/Wind Harmer
-0.009
960081AF2-299 GEN
Solar/Wind Harmer
0.903
316087AB2-174 GEN
Solar/Wind Harmer
1.127
3145783HORNRTN
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.038
315607AA1-063A GEN
Solar/Wind Harmer
0.701
3147983MERCK5
Solar/Wind Helper
0.054
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.989
MECLTFEXP_MEC->PJM
CLTF
0.188
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.489
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.086
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.317
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.766
TVALTFEXP_TVA->PJM
CLTF
0.645
NYPJM->LTFIMP_NY
CLTF
0.388
LGEELTFEXP_LGEE->PJM
CLTF
0.003

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.86 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:986.57
MW Contribution:
2.48
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.48
3144293JTRSVLE
50/50
0.527
3146776BUCKING
Solar/Wind Harmer
-0.174
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.18
316313AB2-026
Solar/Wind Harmer
0.845
970301AG2-198 GEN
Solar/Wind Harmer
13.062
958211AF2-115 GEN
Solar/Wind Harmer
3.653
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
970323AG2-213 GEN
Solar/Wind Harmer
9.489
971223AH1-071 GEN
Solar/Wind Harmer
1.962
313527AB2-043 GEN
Solar/Wind Harmer
2.256
316237AB2-079_GEN
Solar/Wind Harmer
0.41
3143526WINTERP
Solar/Wind Harmer
-0.066
970099AG2-077 GEN
Solar/Wind Harmer
14.947
962561AG1-105 GEN
Solar/Wind Harmer
6.603
964791AG1-342 GEN
Solar/Wind Harmer
2.424
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.294
316118AC1-105 GEN
Solar/Wind Harmer
0.715
970933AG2-581 GEN
Solar/Wind Harmer
9.133
316248AF1-058 C
Solar/Wind Harmer
0.286
313506AB2-031 GEN
Solar/Wind Harmer
0.66
972187AH1-678 GEN
Adder
2.044
972185AH1-677 GEN
Adder
3.99
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.932
3145783HORNRTN
Solar/Wind Harmer
0.745
3145783HORNRTN
Solar/Wind Harmer
0.233
3145783HORNRTN
Solar/Wind Harmer
0.093
316365GEN2_N
Solar/Wind Harmer
0.501
3144356SAPONY
Solar/Wind Harmer
0.256
316315AB2-025 C
Solar/Wind Harmer
0.198
962571AG1-106 GEN
Solar/Wind Harmer
1.033
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.047
316240AF1-291 C
Solar/Wind Harmer
0.208
944641AF1-129 GEN
Adder
29.302
315742AE1-103 GEN
Solar/Wind Harmer
1.626
316083AB2-161 GEN
Solar/Wind Harmer
1.092
315724AD1-057 GEN
Solar/Wind Harmer
1.315
316349AD2-085 GEN
Solar/Wind Harmer
0.587
316065AD1-022 GEN
Solar/Wind Harmer
3.297
316033AB2-134 GEN
Solar/Wind Harmer
2.102
315835AF2-110_GEN
Solar/Wind Harmer
0.816
315614AA2-178 GEN
Solar/Wind Harmer
0.702
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316049AB1-081 GEN
Solar/Wind Harmer
0.696
316263AC1-034 GEN
Solar/Wind Harmer
3.034
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
972205AH1-687 GEN
50/50
22.206
316303AF2-085
50/50
2.484
316322AB2-045
Solar/Wind Harmer
1.467
971845AH1-439 GEN
Solar/Wind Harmer
22.808
316258AE1-075 C
Solar/Wind Harmer
0.76
316405AF2-144 C
Solar/Wind Harmer
0.803
946301AF1-294 GEN
Solar/Wind Harmer
5.991
961791AG1-021 GEN
Solar/Wind Harmer
2.922
3144303KENBRDG
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
12.304
970681AG2-440 GEN
Solar/Wind Harmer
8.167
3151921BEARGRDN G2
50/50
4.545
3144293JTRSVLE
50/50
0.527
972003AH1-546 GEN
Solar/Wind Harmer
21.813
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.168
942461AE2-259 GEN
Solar/Wind Harmer
4.286
3147133PAMPLIN
Solar/Wind Harmer
-0.07
970257AG2-171 GEN
Solar/Wind Harmer
7.117
971775AH1-396 GEN
Solar/Wind Harmer
1.339
959311AF2-222 GEN
Solar/Wind Harmer
17.432
964241AG1-285 GEN
Solar/Wind Harmer
11.676
970221AG2-151 GEN
Solar/Wind Harmer
9.255
316478AD1-087 GEN
Solar/Wind Harmer
1.032
270494AE1-108_GEN
Solar/Wind Harmer
2.999
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.379
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.172
316181AB2-040 GEN
Solar/Wind Harmer
1.147
971683AH1-343 GEN
Solar/Wind Harmer
3.493
944011AF1-069 GEN
Solar/Wind Harmer
4.59
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970917AG2-570 GEN
Solar/Wind Harmer
19.442
3156081AA2-088 GEN
Solar/Wind Harmer
2.348
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.5
3145893MURPHYS
Solar/Wind Harmer
0.05
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.265
3143096IRON208
Adder
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.614
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.322
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.26
3145273HOLLAND
Solar/Wind Harmer
-0.005
970657AG2-426 GEN
Solar/Wind Harmer
1.358
970133AG2-095 GEN
Solar/Wind Harmer
0.756
315722AD1-056 GEN
Solar/Wind Harmer
2.391
3146233WITAKRS
Solar/Wind Harmer
0.139
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.167
3151931BEARGRDN S1
50/50
5.872
3151911BEARGRDN G1
50/50
4.545
3144293JTRSVLE
50/50
0.527
3144293JTRSVLE
50/50
0.416
970119AG2-088 GEN
50/50
18.628
970937AG2-583 GEN
Solar/Wind Harmer
33.126
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.727
971563AH1-280 GEN
Solar/Wind Harmer
2.922
970685AG2-442 GEN
Solar/Wind Harmer
16.459
315785AD2-033 C
Solar/Wind Harmer
4.092
316034AC1-036 C
Solar/Wind Harmer
0.304
3143226MDLTHAN
Solar/Wind Harmer
-0.016
315693AD1-088 GEN
Solar/Wind Harmer
7.448
971377AH1-170 GEN
Solar/Wind Harmer
1.851
3147623JAMES R
Solar/Wind Harmer
0.229
316131AB2-060 GEN
Solar/Wind Harmer
1.533
3143526WINTERP
Solar/Wind Harmer
-0.066
957481AF2-042 GEN
Solar/Wind Harmer
37.368
970401AG2-262 GEN
Solar/Wind Harmer
0.741
971065AG2-659 GEN
Solar/Wind Harmer
5.161
316129AC1-054 GEN
Solar/Wind Harmer
0.886
3147043LAWRENC
Adder
0.815
3150851SPRUNCC
Adder
0.379
960081AF2-299 GEN
Solar/Wind Harmer
0.953
316087AB2-174 GEN
Solar/Wind Harmer
1.183
3145783HORNRTN
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
14.649
970919AG2-571 GEN
Solar/Wind Harmer
2.461
315607AA1-063A GEN
Solar/Wind Harmer
0.776
970087AG2-069 GEN
Solar/Wind Harmer
7.198
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.501
940641AE2-051 GEN
Solar/Wind Harmer
6.871
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.212
3143096IRON208
Adder
0.265
939411AE1-173 GEN
Solar/Wind Harmer
35.461
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.242
316381AD1-082 GEN
Solar/Wind Harmer
0.616
3156021HOLLOMANSOL
Solar/Wind Harmer
0.9
316319Z2-044 C
Solar/Wind Harmer
0.368
3146233WITAKRS
Solar/Wind Harmer
-0.026
316132AB2-190 GEN1
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.654
971069AG2-661 GEN
Solar/Wind Harmer
1.039
315737AD1-076 GEN
Solar/Wind Harmer
1.244
316369SG1_INVT
Solar/Wind Harmer
1.164
316093AE2-104_GEN
Solar/Wind Harmer
1.898
316458AB2-190 GEN2
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.62
315778AD1-151 GEN
Solar/Wind Harmer
5.844
315735AD1-075 GEN1
Solar/Wind Harmer
0.661
3146376EDENTON
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316123AC1-075 GEN
Solar/Wind Harmer
0.697
3145963POPLR C
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
1.355
315816AE2-034 GEN
Solar/Wind Harmer
0.526
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.117
3130156CHOWAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.601
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.87
3142053HEARTS
Solar/Wind Harmer
0.076
3145963POPLR C
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
3.175
944631AF1-128 GEN
Adder
27.172
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
319010AE1-072 C
Solar/Wind Harmer
1.29
3146456SLIGO L269
Solar/Wind Harmer
-0.006
3146293MARTNCO
Solar/Wind Harmer
0.04
316494AC1-189 GEN
Solar/Wind Harmer
0.686
944591AF1-124 GEN
Solar/Wind Harmer
29.1
316375AC2-012 GEN
Solar/Wind Harmer
2.204
316036AC1-147 C
Solar/Wind Harmer
0.171
3150981CHESPKA
Adder
0.708
3145336SMITFLD
Solar/Wind Harmer
-0.025
3151171GRAVELC
Adder
0.603
316072AD1-144
Solar/Wind Harmer
0.128
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.765
316305AF2-043 C
Solar/Wind Harmer
0.193
316246AF1-032 C
Solar/Wind Harmer
0.13
316321Z2-027
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
2.557
316320Y1-086
Solar/Wind Harmer
0.376
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.74
316420AA1-050 GEN
Solar/Wind Harmer
0.728
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
3145933PARMELE
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.342
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
28.996
944601AF1-125 GEN
Solar/Wind Harmer
28.543
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.266
3151171GRAVELC
Adder
0.794
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.511
3132273ORANGE
Solar/Wind Helper
0.026
316238AB2-078_GEN
Solar/Wind Harmer
0.41
316239AB2-077_GEN
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.345
971281AH1-106 GEN
Solar/Wind Harmer
2.085
971283AH1-107 GEN
Solar/Wind Harmer
2.085
316486AD2-202 GEN
Solar/Wind Harmer
0.302
970831AG2-522 GEN
Solar/Wind Harmer
4.94
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.62
971967AH1-528 GEN
Solar/Wind Harmer
16.771
946281AF1-292 GEN
Solar/Wind Harmer
0.19
3137643SOCKMAN
Solar/Wind Harmer
-0.032
970673AG2-436 GEN
Solar/Wind Harmer
17.241
970533AG2-339 GEN
Solar/Wind Harmer
5.254
316426AA2-053 GEN
Solar/Wind Harmer
0.785
970085AG2-068 GEN
Solar/Wind Harmer
4.799
970581AG2-369 GEN
Solar/Wind Harmer
4.127
3146043SEABORD
Solar/Wind Harmer
-0.008
315814AE2-033 C
Solar/Wind Harmer
6.846
315652AC1-086 GEN
Solar/Wind Harmer
8.081
316274AC1-208 GEN
Solar/Wind Harmer
0.772
316318V4-068
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.105
3146033SCOT NK
Solar/Wind Harmer
-0.028
315839AE2-212 C
Solar/Wind Harmer
0.21
316463AE2-346 GEN
Solar/Wind Harmer
0.112
3145513AHOSKIE
Solar/Wind Harmer
0.061
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.689
970657AG2-426 GEN
Solar/Wind Harmer
0.424
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.894
315833AF1-017_GEN
Solar/Wind Harmer
1.255
316311AC2-079 GEN
Solar/Wind Harmer
3.332
315732AD1-074 GEN1
Solar/Wind Harmer
1.322
315733AD1-074 GEN2
Solar/Wind Harmer
1.322
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315697AD1-025 GEN
Solar/Wind Harmer
1.317
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.601
316174AB2-169 GEN
Solar/Wind Harmer
0.993
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
957871AF2-081 GEN
Solar/Wind Harmer
3.196
957861AF2-080 GEN
Solar/Wind Harmer
2.791
316316AC1-027 C
Solar/Wind Harmer
0.195
316236AE1-162_GEN
Solar/Wind Harmer
0.192
3151081ELIZAR1
Adder
5.199
3151091ELIZAR2
Adder
5.109
971445AH1-216 GEN
Solar/Wind Harmer
3.943
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.122
315616AA1-038_C
Solar/Wind Helper
0.552
316433W1029_GEN2
Solar/Wind Harmer
1.167
316435W1029_GEN3
Solar/Wind Harmer
1.167
961601AG1-000A GEN
Solar/Wind Harmer
2.525
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.755
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.43
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3150991CHESPKB
Adder
0.594
3150991CHESPKB
Adder
0.58
316005AA1-067
Solar/Wind Harmer
0.128
966001AG1-469 GEN
Solar/Wind Helper
0.182
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.81
MECLTFEXP_MEC->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
3.66
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.346
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.607
NYPJM->LTFIMP_NY
CLTF
0.429

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.86 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:986.57
MW Contribution:
2.48
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.48
3144293JTRSVLE
50/50
0.527
3146776BUCKING
Solar/Wind Harmer
-0.174
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.18
316313AB2-026
Solar/Wind Harmer
0.845
970301AG2-198 GEN
Solar/Wind Harmer
13.062
958211AF2-115 GEN
Solar/Wind Harmer
3.653
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
970323AG2-213 GEN
Solar/Wind Harmer
9.489
971223AH1-071 GEN
Solar/Wind Harmer
1.962
313527AB2-043 GEN
Solar/Wind Harmer
2.256
316237AB2-079_GEN
Solar/Wind Harmer
0.41
3143526WINTERP
Solar/Wind Harmer
-0.066
970099AG2-077 GEN
Solar/Wind Harmer
14.947
962561AG1-105 GEN
Solar/Wind Harmer
6.603
964791AG1-342 GEN
Solar/Wind Harmer
2.424
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.294
316118AC1-105 GEN
Solar/Wind Harmer
0.715
970933AG2-581 GEN
Solar/Wind Harmer
9.133
316248AF1-058 C
Solar/Wind Harmer
0.286
313506AB2-031 GEN
Solar/Wind Harmer
0.66
972187AH1-678 GEN
Adder
2.044
972185AH1-677 GEN
Adder
3.99
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.932
3145783HORNRTN
Solar/Wind Harmer
0.745
3145783HORNRTN
Solar/Wind Harmer
0.233
3145783HORNRTN
Solar/Wind Harmer
0.093
316365GEN2_N
Solar/Wind Harmer
0.501
3144356SAPONY
Solar/Wind Harmer
0.256
316315AB2-025 C
Solar/Wind Harmer
0.198
962571AG1-106 GEN
Solar/Wind Harmer
1.033
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.047
316240AF1-291 C
Solar/Wind Harmer
0.208
944641AF1-129 GEN
Adder
29.302
315742AE1-103 GEN
Solar/Wind Harmer
1.626
316083AB2-161 GEN
Solar/Wind Harmer
1.092
315724AD1-057 GEN
Solar/Wind Harmer
1.315
316349AD2-085 GEN
Solar/Wind Harmer
0.587
316065AD1-022 GEN
Solar/Wind Harmer
3.297
316033AB2-134 GEN
Solar/Wind Harmer
2.102
315835AF2-110_GEN
Solar/Wind Harmer
0.816
315614AA2-178 GEN
Solar/Wind Harmer
0.702
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316049AB1-081 GEN
Solar/Wind Harmer
0.696
316263AC1-034 GEN
Solar/Wind Harmer
3.034
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.167
316433W1029_GEN2
Solar/Wind Harmer
1.167
316435W1029_GEN3
Solar/Wind Harmer
1.167
961601AG1-000A GEN
Solar/Wind Harmer
2.525
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.755
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.43
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
972205AH1-687 GEN
50/50
22.206
316303AF2-085
50/50
2.484
316322AB2-045
Solar/Wind Harmer
1.467
971845AH1-439 GEN
Solar/Wind Harmer
22.808
316258AE1-075 C
Solar/Wind Harmer
0.76
316405AF2-144 C
Solar/Wind Harmer
0.803
946301AF1-294 GEN
Solar/Wind Harmer
5.991
961791AG1-021 GEN
Solar/Wind Harmer
2.922
3144303KENBRDG
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
12.304
970681AG2-440 GEN
Solar/Wind Harmer
8.167
316238AB2-078_GEN
Solar/Wind Harmer
0.41
316239AB2-077_GEN
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.345
971281AH1-106 GEN
Solar/Wind Harmer
2.085
971283AH1-107 GEN
Solar/Wind Harmer
2.085
3151921BEARGRDN G2
50/50
4.545
3144293JTRSVLE
50/50
0.527
972003AH1-546 GEN
Solar/Wind Harmer
21.813
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.168
942461AE2-259 GEN
Solar/Wind Harmer
4.286
3147133PAMPLIN
Solar/Wind Harmer
-0.07
970257AG2-171 GEN
Solar/Wind Harmer
7.117
971775AH1-396 GEN
Solar/Wind Harmer
1.339
959311AF2-222 GEN
Solar/Wind Harmer
17.432
964241AG1-285 GEN
Solar/Wind Harmer
11.676
970221AG2-151 GEN
Solar/Wind Harmer
9.255
316478AD1-087 GEN
Solar/Wind Harmer
1.032
270494AE1-108_GEN
Solar/Wind Harmer
2.999
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.379
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.172
316181AB2-040 GEN
Solar/Wind Harmer
1.147
971683AH1-343 GEN
Solar/Wind Harmer
3.493
944011AF1-069 GEN
Solar/Wind Harmer
4.59
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970917AG2-570 GEN
Solar/Wind Harmer
19.442
3156081AA2-088 GEN
Solar/Wind Harmer
2.348
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.5
3145893MURPHYS
Solar/Wind Harmer
0.05
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.265
3143096IRON208
Adder
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.614
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.322
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.26
3145273HOLLAND
Solar/Wind Harmer
-0.005
970657AG2-426 GEN
Solar/Wind Harmer
1.358
970133AG2-095 GEN
Solar/Wind Harmer
0.756
315722AD1-056 GEN
Solar/Wind Harmer
2.391
3146233WITAKRS
Solar/Wind Harmer
0.139
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.004
316458AB2-190 GEN2
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.62
315778AD1-151 GEN
Solar/Wind Harmer
5.844
315735AD1-075 GEN1
Solar/Wind Harmer
0.661
3146376EDENTON
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316123AC1-075 GEN
Solar/Wind Harmer
0.697
3145963POPLR C
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
1.355
316305AF2-043 C
Solar/Wind Harmer
0.193
316246AF1-032 C
Solar/Wind Harmer
0.13
316321Z2-027
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
2.557
316320Y1-086
Solar/Wind Harmer
0.376
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.74
316420AA1-050 GEN
Solar/Wind Harmer
0.728
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
3145933PARMELE
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.342
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
28.996
944601AF1-125 GEN
Solar/Wind Harmer
28.543
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.266
3151171GRAVELC
Adder
0.794
3145746EVERETS
Solar/Wind Harmer
-0.006
3151931BEARGRDN S1
50/50
5.872
3151911BEARGRDN G1
50/50
4.545
3144293JTRSVLE
50/50
0.527
3144293JTRSVLE
50/50
0.416
970119AG2-088 GEN
50/50
18.628
970937AG2-583 GEN
Solar/Wind Harmer
33.126
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.727
971563AH1-280 GEN
Solar/Wind Harmer
2.922
970685AG2-442 GEN
Solar/Wind Harmer
16.459
315785AD2-033 C
Solar/Wind Harmer
4.092
316034AC1-036 C
Solar/Wind Harmer
0.304
3143226MDLTHAN
Solar/Wind Harmer
-0.016
315693AD1-088 GEN
Solar/Wind Harmer
7.448
971377AH1-170 GEN
Solar/Wind Harmer
1.851
3147623JAMES R
Solar/Wind Harmer
0.229
316131AB2-060 GEN
Solar/Wind Harmer
1.533
3143526WINTERP
Solar/Wind Harmer
-0.066
957481AF2-042 GEN
Solar/Wind Harmer
37.368
970401AG2-262 GEN
Solar/Wind Harmer
0.741
971065AG2-659 GEN
Solar/Wind Harmer
5.161
316129AC1-054 GEN
Solar/Wind Harmer
0.886
3147043LAWRENC
Adder
0.815
3150851SPRUNCC
Adder
0.379
960081AF2-299 GEN
Solar/Wind Harmer
0.953
316087AB2-174 GEN
Solar/Wind Harmer
1.183
3145783HORNRTN
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
14.649
970919AG2-571 GEN
Solar/Wind Harmer
2.461
315607AA1-063A GEN
Solar/Wind Harmer
0.776
970087AG2-069 GEN
Solar/Wind Harmer
7.198
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.501
940641AE2-051 GEN
Solar/Wind Harmer
6.871
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.212
3143096IRON208
Adder
0.265
939411AE1-173 GEN
Solar/Wind Harmer
35.461
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.242
316381AD1-082 GEN
Solar/Wind Harmer
0.616
3156021HOLLOMANSOL
Solar/Wind Harmer
0.9
316319Z2-044 C
Solar/Wind Harmer
0.368
3146233WITAKRS
Solar/Wind Harmer
-0.026
316132AB2-190 GEN1
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.654
971069AG2-661 GEN
Solar/Wind Harmer
1.039
315737AD1-076 GEN
Solar/Wind Harmer
1.244
316369SG1_INVT
Solar/Wind Harmer
1.164
316093AE2-104_GEN
Solar/Wind Harmer
1.898
315816AE2-034 GEN
Solar/Wind Harmer
0.526
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.117
3130156CHOWAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.601
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.87
3142053HEARTS
Solar/Wind Harmer
0.076
3145963POPLR C
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
3.175
944631AF1-128 GEN
Adder
27.172
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
319010AE1-072 C
Solar/Wind Harmer
1.29
3146456SLIGO L269
Solar/Wind Harmer
-0.006
3146293MARTNCO
Solar/Wind Harmer
0.04
316494AC1-189 GEN
Solar/Wind Harmer
0.686
944591AF1-124 GEN
Solar/Wind Harmer
29.1
316375AC2-012 GEN
Solar/Wind Harmer
2.204
316036AC1-147 C
Solar/Wind Harmer
0.171
3150981CHESPKA
Adder
0.708
3145336SMITFLD
Solar/Wind Harmer
-0.025
3151171GRAVELC
Adder
0.603
316072AD1-144
Solar/Wind Harmer
0.128
316486AD2-202 GEN
Solar/Wind Harmer
0.302
970831AG2-522 GEN
Solar/Wind Harmer
4.94
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.62
971967AH1-528 GEN
Solar/Wind Harmer
16.771
946281AF1-292 GEN
Solar/Wind Harmer
0.19
3137643SOCKMAN
Solar/Wind Harmer
-0.032
970673AG2-436 GEN
Solar/Wind Harmer
17.241
970533AG2-339 GEN
Solar/Wind Harmer
5.254
316426AA2-053 GEN
Solar/Wind Harmer
0.785
970085AG2-068 GEN
Solar/Wind Harmer
4.799
970581AG2-369 GEN
Solar/Wind Harmer
4.127
3146043SEABORD
Solar/Wind Harmer
-0.008
315814AE2-033 C
Solar/Wind Harmer
6.846
315652AC1-086 GEN
Solar/Wind Harmer
8.081
316274AC1-208 GEN
Solar/Wind Harmer
0.772
316318V4-068
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.105
3146033SCOT NK
Solar/Wind Harmer
-0.028
315839AE2-212 C
Solar/Wind Harmer
0.21
316463AE2-346 GEN
Solar/Wind Harmer
0.112
3145513AHOSKIE
Solar/Wind Harmer
0.061
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.689
970657AG2-426 GEN
Solar/Wind Harmer
0.424
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.894
315833AF1-017_GEN
Solar/Wind Harmer
1.255
316311AC2-079 GEN
Solar/Wind Harmer
3.332
315732AD1-074 GEN1
Solar/Wind Harmer
1.322
315733AD1-074 GEN2
Solar/Wind Harmer
1.322
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315697AD1-025 GEN
Solar/Wind Harmer
1.317
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.601
316174AB2-169 GEN
Solar/Wind Harmer
0.993
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
957871AF2-081 GEN
Solar/Wind Harmer
3.196
957861AF2-080 GEN
Solar/Wind Harmer
2.791
316316AC1-027 C
Solar/Wind Harmer
0.195
316236AE1-162_GEN
Solar/Wind Harmer
0.192
3151081ELIZAR1
Adder
5.199
3151091ELIZAR2
Adder
5.109
971445AH1-216 GEN
Solar/Wind Harmer
3.943
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.122
315616AA1-038_C
Solar/Wind Helper
0.552
3145746EVERETS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.511
3132273ORANGE
Solar/Wind Helper
0.026
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.765
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3150991CHESPKB
Adder
0.594
3150991CHESPKB
Adder
0.58
316005AA1-067
Solar/Wind Harmer
0.128
966001AG1-469 GEN
Solar/Wind Helper
0.182
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.81
MECLTFEXP_MEC->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
3.66
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.346
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.607
NYPJM->LTFIMP_NY
CLTF
0.429

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.79 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:799.44
MW Contribution:
2.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.963
316303AF2-085
50/50
2.099
3151541CLOVER2
50/50
2.397
3151601KERR 3
50/50
0.215
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
963041AG1-153 GEN
50/50
2.149
315244AE2-183_ST
50/50
2.291
3151281ROARAP4
50/50
0.085
971285AH1-108 GEN
50/50
0.591
315779AE2-040
50/50
0.989
971845AH1-439 GEN
Solar/Wind Harmer
17.227
316258AE1-075 C
Solar/Wind Harmer
0.197
946301AF1-294 GEN
Solar/Wind Harmer
4.161
961791AG1-021 GEN
Solar/Wind Harmer
2.024
3144303KENBRDG
Solar/Wind Harmer
0.138
970683AG2-441 GEN
Solar/Wind Harmer
9.631
970681AG2-440 GEN
Solar/Wind Harmer
6.392
316486AD2-202 GEN
Solar/Wind Harmer
0.114
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.36
971283AH1-107 GEN
Solar/Wind Harmer
1.36
970831AG2-522 GEN
Solar/Wind Harmer
3.97
3147173SINAI
Solar/Wind Harmer
0.089
3147243WELCO
Solar/Wind Harmer
0.056
971967AH1-528 GEN
Solar/Wind Harmer
14.085
970673AG2-436 GEN
Solar/Wind Harmer
9.882
970533AG2-339 GEN
Solar/Wind Harmer
5.967
3137643SOCKMAN
Solar/Wind Harmer
0.308
970085AG2-068 GEN
Solar/Wind Harmer
4.081
970581AG2-369 GEN
Solar/Wind Harmer
3.51
316426AA2-053 GEN
Solar/Wind Harmer
0.249
3146043SEABORD
Solar/Wind Harmer
0.073
315814AE2-033 C
Solar/Wind Harmer
5.613
315652AC1-086 GEN
Solar/Wind Harmer
7.598
316274AC1-208 GEN
Solar/Wind Harmer
0.355
3145893MURPHYS
Solar/Wind Harmer
0.186
3145893MURPHYS
Solar/Wind Harmer
0.069
3145796HORNRTN
Solar/Wind Harmer
0.218
3145796HORNRTN
Solar/Wind Harmer
0.027
316210AC1-098 GEN
Solar/Wind Harmer
0.627
3146033SCOT NK
Solar/Wind Harmer
0.27
316463AE2-346 GEN
Solar/Wind Harmer
0.057
3145513AHOSKIE
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.133
3145683EARLEYS
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.067
316327AA2-057 GEN
Solar/Wind Harmer
0.097
3146206CASHIE
Solar/Wind Harmer
0.064
970601AG2-382 GEN
Solar/Wind Harmer
2.394
315732AD1-074 GEN1
Solar/Wind Harmer
0.362
315733AD1-074 GEN2
Solar/Wind Harmer
0.362
3143316POE
Solar/Wind Harmer
0.252
3130546PLYMOUTH
Solar/Wind Harmer
0.064
970657AG2-426 GEN
Solar/Wind Harmer
0.466
316311AC2-079 GEN
Solar/Wind Harmer
1.819
3130156CHOWAN
Solar/Wind Harmer
0.063
3130156CHOWAN
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.173
313526AB2-022
Solar/Wind Harmer
0.033
3146406KITTY HAWK
Solar/Wind Harmer
0.008
957871AF2-081 GEN
Solar/Wind Harmer
3.112
316316AC1-027 C
Solar/Wind Harmer
0.059
3151081ELIZAR1
Adder
5.701
3151091ELIZAR2
Adder
5.602
3145573BETHELC
Solar/Wind Harmer
0.062
3145573BETHELC
Solar/Wind Harmer
0.062
957861AF2-080 GEN
Solar/Wind Harmer
2.662
3145746EVERETS
Solar/Wind Harmer
0.245
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
971445AH1-216 GEN
Solar/Wind Harmer
4.283
315697AD1-025 GEN
Solar/Wind Harmer
0.064
3151201GRAVEL4
Adder
4.378
3151221GRAVEL6
Adder
4.373
3151191GRAVEL3
Adder
4.322
3151211GRAVEL5
Adder
4.322
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.107
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
315616AA1-038_C
Solar/Wind Helper
0.562
3151921BEARGRDN G2
50/50
4.495
3144293JTRSVLE
50/50
0.534
970413AG2-270 GEN
50/50
10.515
3151031BRUNSWICKG2
50/50
1.061
3151261ROARAP2
50/50
0.094
3150861SPRUNCD
50/50
0.361
3151391GASTONA
50/50
0.185
3151411GASTONB
50/50
0.185
972003AH1-546 GEN
Solar/Wind Harmer
16.394
3146776BUCKING
Solar/Wind Harmer
0.139
3146926FARMVIL
Solar/Wind Harmer
0.184
3143336POWHATN
Solar/Wind Harmer
3.996
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.64
970257AG2-171 GEN
Solar/Wind Harmer
5.525
971775AH1-396 GEN
Solar/Wind Harmer
0.276
959311AF2-222 GEN
Solar/Wind Harmer
13.645
964241AG1-285 GEN
Solar/Wind Harmer
9.212
970221AG2-151 GEN
Solar/Wind Harmer
6.773
316478AD1-087 GEN
Solar/Wind Harmer
0.389
270494AE1-108_GEN
Solar/Wind Harmer
1.182
3147043LAWRENC
Solar/Wind Harmer
0.057
944011AF1-069 GEN
Solar/Wind Harmer
4.752
316181AB2-040 GEN
Solar/Wind Harmer
0.112
970917AG2-570 GEN
Solar/Wind Harmer
6.894
971683AH1-343 GEN
Solar/Wind Harmer
2.8
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.069
316011AB1-132 GEN
Solar/Wind Harmer
1.253
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3145893MURPHYS
Solar/Wind Harmer
0.115
3145893MURPHYS
Solar/Wind Harmer
0.069
3145796HORNRTN
Solar/Wind Harmer
0.272
3145796HORNRTN
Solar/Wind Harmer
0.068
316212AC1-099_GEN
Solar/Wind Harmer
0.35
3146173TUNIS
Solar/Wind Harmer
0.068
3145823KELFORD
Solar/Wind Harmer
0.067
3145273HOLLAND
Solar/Wind Harmer
0.049
315722AD1-056 GEN
Solar/Wind Harmer
2.24
3146233WITAKRS
Solar/Wind Harmer
0.322
3146233WITAKRS
Solar/Wind Harmer
0.044
3146206CASHIE
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.042
316222AC1-221 GEN
Solar/Wind Harmer
0.263
315735AD1-075 GEN1
Solar/Wind Harmer
0.181
315813AE1-149 C
Solar/Wind Harmer
3.388
970657AG2-426 GEN
Solar/Wind Harmer
1.423
3146376EDENTON
Solar/Wind Harmer
0.063
316283AC2-100 C
Solar/Wind Harmer
0.123
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.011
3145963POPLR C
Solar/Wind Harmer
0.063
3151931BEARGRDN S1
50/50
5.808
3151911BEARGRDN G1
50/50
4.495
3144293JTRSVLE
50/50
0.534
3144293JTRSVLE
50/50
0.422
970119AG2-088 GEN
50/50
15.744
3151531CLOVER1
50/50
2.414
3151591KERR 2
50/50
0.215
3151641KERR 7
50/50
0.215
3147043LAWRENC
50/50
0.914
3151051BRUNSWICKS1
50/50
2.203
3151021BRUNSWICKG1
50/50
1.061
971451AH1-221 GEN
50/50
3.223
315243AE2-183_GT3
50/50
1.321
3151281ROARAP4
50/50
0.091
3150851SPRUNCC
50/50
0.361
3151391GASTONA
50/50
0.185
3151411GASTONB
50/50
0.185
970937AG2-583 GEN
Solar/Wind Harmer
24.603
3146776BUCKING
Solar/Wind Harmer
0.155
3146926FARMVIL
Solar/Wind Harmer
0.184
3143336POWHATN
Solar/Wind Harmer
4.701
971563AH1-280 GEN
Solar/Wind Harmer
2.249
970685AG2-442 GEN
Solar/Wind Harmer
12.826
315785AD2-033 C
Solar/Wind Harmer
1.334
316034AC1-036 C
Solar/Wind Harmer
0.01
315693AD1-088 GEN
Solar/Wind Harmer
6.634
316131AB2-060 GEN
Solar/Wind Harmer
0.41
971377AH1-170 GEN
Solar/Wind Harmer
1.355
3147623JAMES R
Solar/Wind Harmer
0.294
3143226MDLTHAN
Solar/Wind Harmer
0.118
957481AF2-042 GEN
Solar/Wind Harmer
30.149
970401AG2-262 GEN
Solar/Wind Harmer
0.621
3143526WINTERP
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
4.138
316129AC1-054 GEN
Solar/Wind Harmer
0.356
960081AF2-299 GEN
Solar/Wind Harmer
0.774
941031AE2-094 GEN
Solar/Wind Harmer
14.545
970919AG2-571 GEN
Solar/Wind Harmer
2.758
970087AG2-069 GEN
Solar/Wind Harmer
6.122
3145783HORNRTN
Solar/Wind Harmer
0.075
940641AE2-051 GEN
Solar/Wind Harmer
5.96
315607AA1-063A GEN
Solar/Wind Harmer
0.148
316023GEN1_S
Solar/Wind Harmer
0.159
939411AE1-173 GEN
Solar/Wind Harmer
30.495
3146263WOODLND
Solar/Wind Harmer
0.069
3145893MURPHYS
Solar/Wind Harmer
0.275
3145893MURPHYS
Solar/Wind Harmer
0.306
3145796HORNRTN
Solar/Wind Harmer
0.225
3145796HORNRTN
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
316246AF1-032 C
Solar/Wind Harmer
0.028
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.062
971153AH1-033 GEN
Solar/Wind Harmer
0.723
316017AA1-139 ULT1
Solar/Wind Harmer
0.033
971623AH1-311 GEN
Solar/Wind Harmer
0.125
944581AF1-123 GEN
Solar/Wind Harmer
14.049
944601AF1-125 GEN
Solar/Wind Harmer
13.832
3151101ELIZAR3
Adder
5.774
3144873MCLAUGH
Solar/Wind Harmer
0.002
961601AG1-000A GEN
Solar/Wind Harmer
4.415
3145933PARMELE
Solar/Wind Harmer
0.062
3146073TAR RVR
Solar/Wind Harmer
0.062
3146083TARBORO
Solar/Wind Harmer
0.062
3144536CHRHLND
Solar/Wind Harmer
0.009
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
3145336SMITFLD
Solar/Wind Harmer
0.024
316123AC1-075 GEN
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
0.581
316458AB2-190 GEN2
Solar/Wind Harmer
0.322
315778AD1-151 GEN
Solar/Wind Harmer
4.826
961611AG1-000B GEN
Solar/Wind Harmer
1.605
3151171GRAVELC
Adder
0.841
3143096IRON208
Adder
0.248
3143096IRON208
Adder
0.243
3148013FISHERV
Solar/Wind Helper
0.179
316499AE2-029_GEN
Solar/Wind Helper
0.52
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.259
3145823KELFORD
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.067
3156021HOLLOMANSOL
Solar/Wind Harmer
0.292
3146233WITAKRS
Solar/Wind Harmer
0.256
3146206CASHIE
Solar/Wind Harmer
0.064
971547AH1-271 GEN
Solar/Wind Harmer
1.368
315737AD1-076 GEN
Solar/Wind Harmer
0.816
316381AD1-082 GEN
Solar/Wind Harmer
0.064
315816AE2-034 GEN
Solar/Wind Harmer
0.27
3145663CRESWEL
Solar/Wind Harmer
0.177
971163AH1-040 GEN
Solar/Wind Harmer
5.071
316093AE2-104_GEN
Solar/Wind Harmer
1.064
3130156CHOWAN
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.204
3146516WINFALL
Solar/Wind Harmer
0.063
3145963POPLR C
Solar/Wind Harmer
0.063
3142543TWELFTH
Solar/Wind Harmer
0.006
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
319010AE1-072 C
Solar/Wind Harmer
0.311
3146456SLIGO L269
Solar/Wind Harmer
0.062
316359AB2-059 GEN
Solar/Wind Harmer
0.222
3142053HEARTS
Solar/Wind Harmer
0.11
944591AF1-124 GEN
Solar/Wind Harmer
14.099
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150981CHESPKA
Adder
0.776
3146293MARTNCO
Solar/Wind Harmer
0.057
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.062
3145493TOT1
Solar/Wind Harmer
0.275
316494AC1-189 GEN
Solar/Wind Harmer
0.209
316072AD1-144
Solar/Wind Harmer
0.022
315671AE2-027_GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
315773AC2-141 GEN
Solar/Wind Harmer
2.232
3145336SMITFLD
Solar/Wind Harmer
0.244
316132AB2-190 GEN1
Solar/Wind Harmer
0.322
971069AG2-661 GEN
Solar/Wind Harmer
1.073
961611AG1-000B GEN
Solar/Wind Harmer
3.157
3151171GRAVELC
Adder
0.64
3143096IRON208
Adder
0.248
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.785
3147666LOUISA
Solar/Wind Helper
0.45
970909AG2-566 GEN
50/50
2.507
3144293JTRSVLE
50/50
0.534
970535AG2-341 GEN
50/50
2.068
3151581KERR 1
50/50
0.077
3152661PLYWOOD A
50/50
0.21
3151041BRUNSWICKG3
50/50
1.061
972187AH1-678 GEN
50/50
2.435
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.315
972185AH1-677 GEN
50/50
4.769
3151261ROARAP2
50/50
0.091
3146776BUCKING
Solar/Wind Harmer
1.546
3146776BUCKING
Solar/Wind Harmer
0.125
316336AC2-165 C
Solar/Wind Harmer
15.338
316313AB2-026
Solar/Wind Harmer
0.165
970301AG2-198 GEN
Solar/Wind Harmer
10.027
958211AF2-115 GEN
Solar/Wind Harmer
2.53
3147133PAMPLIN
Solar/Wind Harmer
0.204
3147133PAMPLIN
Solar/Wind Harmer
0.163
970323AG2-213 GEN
Solar/Wind Harmer
7.367
971223AH1-071 GEN
Solar/Wind Harmer
1.259
970099AG2-077 GEN
Solar/Wind Harmer
12.06
962561AG1-105 GEN
Solar/Wind Harmer
5.245
964791AG1-342 GEN
Solar/Wind Harmer
2.031
3146843MT LREL
Solar/Wind Harmer
0.106
3146843MT LREL
Solar/Wind Harmer
0.106
3143526WINTERP
Solar/Wind Harmer
0.509
316118AC1-105 GEN
Solar/Wind Harmer
0.25
970933AG2-581 GEN
Solar/Wind Harmer
7.587
313506AB2-031 GEN
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.095
3145783HORNRTN
Solar/Wind Harmer
1.334
3145783HORNRTN
Solar/Wind Harmer
1.067
3145783HORNRTN
Solar/Wind Harmer
0.333
3145783HORNRTN
Solar/Wind Harmer
0.133
316365GEN2_N
Solar/Wind Harmer
0.159
3144356SAPONY
Solar/Wind Harmer
0.593
316315AB2-025 C
Solar/Wind Harmer
0.057
962571AG1-106 GEN
Solar/Wind Harmer
0.983
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.461
3145893MURPHYS
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.204
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
316140AB2-099
Solar/Wind Harmer
0.024
315742AE1-103 GEN
Solar/Wind Harmer
0.988
315724AD1-057 GEN
Solar/Wind Harmer
1.249
316065AD1-022 GEN
Solar/Wind Harmer
2.944
315614AA2-178 GEN
Solar/Wind Harmer
0.361
316349AD2-085 GEN
Solar/Wind Harmer
0.042
315835AF2-110_GEN
Solar/Wind Harmer
0.434
3146376EDENTON
Solar/Wind Harmer
0.281
3146376EDENTON
Solar/Wind Harmer
0.281
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146386ELIZ CT
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.25
3137176SLIGO L2192
Solar/Wind Harmer
0.249
3146456SLIGO L269
Solar/Wind Harmer
1.106
316049AB1-081 GEN
Solar/Wind Harmer
0.356
316339AD2-160 GEN
Solar/Wind Harmer
0.1
316388AE2-253 GEN
Solar/Wind Harmer
0.194
316263AC1-034 GEN
Solar/Wind Harmer
2.375
3145506HICKORY
Solar/Wind Harmer
0.25
3145506HICKORY
Solar/Wind Harmer
0.15
3145506HICKORY
Solar/Wind Harmer
0.037
3150991CHESPKB
Adder
0.651
3150991CHESPKB
Adder
0.636
961601AG1-000A GEN
Solar/Wind Harmer
1.104
3145933PARMELE
Solar/Wind Harmer
0.124
3145933PARMELE
Solar/Wind Harmer
0.062
3145493TOT1
Solar/Wind Harmer
0.143
3145453TOT5
Solar/Wind Harmer
0.086
3145603CNETO
Solar/Wind Harmer
0.057
316005AA1-067
Solar/Wind Harmer
0.066
316294AC1-161 GEN
Solar/Wind Harmer
1.057
944641AF1-129 GEN
Adder
29.012
316033AB2-134 GEN
Solar/Wind Harmer
0
966001AG1-469 GEN
Solar/Wind Helper
0.186
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.099
MECLTFEXP_MEC->PJM
CLTF
0.124
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
4.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.187
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.062
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.167
LAGNLTFEXP_LAGN->PJM
CLTF
1.43
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.724
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.695
NYPJM->LTFIMP_NY
CLTF
0.461

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.09 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:733.57
MW Contribution:
2.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.34 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:932.1
MW Contribution:
3.01
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
29.134
3151541CLOVER2
50/50
2.196
3151601KERR 3
50/50
0.2
3151611KERR 4
50/50
0.2
3151621KERR 5
50/50
0.2
3151631KERR 6
50/50
0.2
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
3151581KERR 1
50/50
0.071
3152661PLYWOOD A
50/50
0.197
316336AC2-165 C
Solar/Wind Harmer
32.562
971845AH1-439 GEN
Solar/Wind Harmer
22.245
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3144303KENBRDG
Solar/Wind Harmer
0.154
970683AG2-441 GEN
Solar/Wind Harmer
10.284
970681AG2-440 GEN
Solar/Wind Harmer
6.826
316486AD2-202 GEN
Solar/Wind Harmer
0.105
3147173SINAI
Solar/Wind Harmer
0.083
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.367
971967AH1-528 GEN
Solar/Wind Harmer
9.13
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
970413AG2-270 GEN
50/50
9.635
972003AH1-546 GEN
Solar/Wind Harmer
21.695
3146776BUCKING
Solar/Wind Harmer
0.18
3146926FARMVIL
Solar/Wind Harmer
0.23
942461AE2-259 GEN
Solar/Wind Harmer
0.001
970221AG2-151 GEN
Solar/Wind Harmer
14.27
3147133PAMPLIN
Solar/Wind Harmer
0.737
270494AE1-108_GEN
Solar/Wind Harmer
2.499
970257AG2-171 GEN
Solar/Wind Harmer
6.149
971775AH1-396 GEN
Solar/Wind Harmer
0.307
959311AF2-222 GEN
Solar/Wind Harmer
14.386
964241AG1-285 GEN
Solar/Wind Harmer
9.36
315821AE2-092 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.357
958131AF2-107 GEN
Solar/Wind Harmer
2.368
3147043LAWRENC
Solar/Wind Harmer
0.047
971683AH1-343 GEN
Solar/Wind Harmer
2.656
316123AC1-075 GEN
Solar/Wind Harmer
0.079
3146776BUCKING
Solar/Wind Harmer
2.001
3146776BUCKING
Solar/Wind Harmer
0.162
970301AG2-198 GEN
Solar/Wind Harmer
11.924
958211AF2-115 GEN
Solar/Wind Harmer
2.96
3147133PAMPLIN
Solar/Wind Harmer
0.235
3147133PAMPLIN
Solar/Wind Harmer
0.188
970323AG2-213 GEN
Solar/Wind Harmer
8.199
962561AG1-105 GEN
Solar/Wind Harmer
5.114
964791AG1-342 GEN
Solar/Wind Harmer
1.967
3146843MT LREL
Solar/Wind Harmer
0.102
3146843MT LREL
Solar/Wind Harmer
0.102
970099AG2-077 GEN
Solar/Wind Harmer
10.732
316118AC1-105 GEN
Solar/Wind Harmer
0.237
970933AG2-581 GEN
Solar/Wind Harmer
5.491
966001AG1-469 GEN
Solar/Wind Helper
0.139
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
3151531CLOVER1
50/50
2.212
3151591KERR 2
50/50
0.2
3151641KERR 7
50/50
0.2
3147043LAWRENC
50/50
0.756
970937AG2-583 GEN
Solar/Wind Harmer
39.417
3146776BUCKING
Solar/Wind Harmer
0.2
3146926FARMVIL
Solar/Wind Harmer
0.23
971377AH1-170 GEN
Solar/Wind Harmer
2.854
3147623JAMES R
Solar/Wind Harmer
0.62
971563AH1-280 GEN
Solar/Wind Harmer
2.631
970685AG2-442 GEN
Solar/Wind Harmer
14.043
315785AD2-033 C
Solar/Wind Harmer
1.465
316034AC1-036 C
Solar/Wind Harmer
0.011
315693AD1-088 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.416
970401AG2-262 GEN
Solar/Wind Harmer
0.601
957481AF2-042 GEN
Solar/Wind Harmer
26.83
971065AG2-659 GEN
Solar/Wind Harmer
3.622
316129AC1-054 GEN
Solar/Wind Harmer
0.307
960081AF2-299 GEN
Solar/Wind Harmer
0.544
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:840.79
MW Contribution:
2.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.46 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1049.6
MW Contribution:
3.01
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
972003AH1-546 GEN
Solar/Wind Harmer
28.565
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.235
970221AG2-151 GEN
Solar/Wind Harmer
18.789
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270494AE1-108_GEN
Solar/Wind Harmer
6.111
970257AG2-171 GEN
Solar/Wind Harmer
8.096
971775AH1-396 GEN
Solar/Wind Harmer
1.523
959311AF2-222 GEN
Solar/Wind Harmer
18.979
964241AG1-285 GEN
Solar/Wind Harmer
12.324
315821AE2-092 GEN
Solar/Wind Harmer
2.69
316478AD1-087 GEN
Solar/Wind Harmer
0.999
958131AF2-107 GEN
Solar/Wind Harmer
3.152
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.854
971683AH1-343 GEN
Solar/Wind Harmer
3.498
316123AC1-075 GEN
Solar/Wind Harmer
0.72
966621AG1-532 GEN
Solar/Wind Harmer
0.129
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
316336AC2-165 C
Solar/Wind Harmer
45.084
3146776BUCKING
Solar/Wind Harmer
-0.224
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.7
958211AF2-115 GEN
Solar/Wind Harmer
4.331
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
970323AG2-213 GEN
Solar/Wind Harmer
10.795
313527AB2-043 GEN
Solar/Wind Harmer
2.357
316237AB2-079_GEN
Solar/Wind Harmer
0.426
962561AG1-105 GEN
Solar/Wind Harmer
6.734
964791AG1-342 GEN
Solar/Wind Harmer
2.459
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
14.131
316118AC1-105 GEN
Solar/Wind Harmer
0.714
315687AD1-152 GEN
Solar/Wind Harmer
1.245
316248AF1-058 C
Solar/Wind Harmer
0.281
970933AG2-581 GEN
Solar/Wind Harmer
7.23
966001AG1-469 GEN
Solar/Wind Helper
0.139
972205AH1-687 GEN
50/50
29.134
316322AB2-045
Solar/Wind Harmer
1.888
971845AH1-439 GEN
Solar/Wind Harmer
29.289
946301AF1-294 GEN
Solar/Wind Harmer
7.102
961791AG1-021 GEN
Solar/Wind Harmer
3.465
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
13.541
970681AG2-440 GEN
Solar/Wind Harmer
8.987
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316486AD2-202 GEN
Solar/Wind Harmer
0.293
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.433
971967AH1-528 GEN
Solar/Wind Harmer
12.053
946281AF1-292 GEN
Solar/Wind Harmer
0.143
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
970937AG2-583 GEN
Solar/Wind Harmer
51.899
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.758
3147623JAMES R
Solar/Wind Harmer
0.465
971563AH1-280 GEN
Solar/Wind Harmer
3.465
970685AG2-442 GEN
Solar/Wind Harmer
18.491
315785AD2-033 C
Solar/Wind Harmer
4.603
316034AC1-036 C
Solar/Wind Harmer
0.329
315693AD1-088 GEN
Solar/Wind Harmer
7.766
316131AB2-060 GEN
Solar/Wind Harmer
1.615
970401AG2-262 GEN
Solar/Wind Harmer
0.751
957481AF2-042 GEN
Solar/Wind Harmer
35.327
971065AG2-659 GEN
Solar/Wind Harmer
4.769
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.712
960081AF2-299 GEN
Solar/Wind Harmer
0.716
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:840.79
MW Contribution:
2.98
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
972003AH1-546 GEN
Solar/Wind Harmer
28.565
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.235
970221AG2-151 GEN
Solar/Wind Harmer
18.789
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270494AE1-108_GEN
Solar/Wind Harmer
6.111
970257AG2-171 GEN
Solar/Wind Harmer
8.096
971775AH1-396 GEN
Solar/Wind Harmer
1.523
959311AF2-222 GEN
Solar/Wind Harmer
18.979
964241AG1-285 GEN
Solar/Wind Harmer
12.324
315821AE2-092 GEN
Solar/Wind Harmer
2.69
316478AD1-087 GEN
Solar/Wind Harmer
0.999
958131AF2-107 GEN
Solar/Wind Harmer
3.152
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.854
971683AH1-343 GEN
Solar/Wind Harmer
3.498
316123AC1-075 GEN
Solar/Wind Harmer
0.72
966621AG1-532 GEN
Solar/Wind Harmer
0.129
972205AH1-687 GEN
50/50
29.134
316322AB2-045
Solar/Wind Harmer
1.888
971845AH1-439 GEN
Solar/Wind Harmer
29.289
946301AF1-294 GEN
Solar/Wind Harmer
7.102
961791AG1-021 GEN
Solar/Wind Harmer
3.465
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
13.541
970681AG2-440 GEN
Solar/Wind Harmer
8.987
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316486AD2-202 GEN
Solar/Wind Harmer
0.293
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.433
971967AH1-528 GEN
Solar/Wind Harmer
12.053
946281AF1-292 GEN
Solar/Wind Harmer
0.143
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
970937AG2-583 GEN
Solar/Wind Harmer
51.899
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.758
3147623JAMES R
Solar/Wind Harmer
0.465
971563AH1-280 GEN
Solar/Wind Harmer
3.465
970685AG2-442 GEN
Solar/Wind Harmer
18.491
315785AD2-033 C
Solar/Wind Harmer
4.603
316034AC1-036 C
Solar/Wind Harmer
0.329
315693AD1-088 GEN
Solar/Wind Harmer
7.766
316131AB2-060 GEN
Solar/Wind Harmer
1.615
970401AG2-262 GEN
Solar/Wind Harmer
0.751
957481AF2-042 GEN
Solar/Wind Harmer
35.327
971065AG2-659 GEN
Solar/Wind Harmer
4.769
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.712
960081AF2-299 GEN
Solar/Wind Harmer
0.716
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
316336AC2-165 C
Solar/Wind Harmer
45.084
3146776BUCKING
Solar/Wind Harmer
-0.224
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.7
958211AF2-115 GEN
Solar/Wind Harmer
4.331
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
970323AG2-213 GEN
Solar/Wind Harmer
10.795
313527AB2-043 GEN
Solar/Wind Harmer
2.357
316237AB2-079_GEN
Solar/Wind Harmer
0.426
962561AG1-105 GEN
Solar/Wind Harmer
6.734
964791AG1-342 GEN
Solar/Wind Harmer
2.459
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
14.131
316118AC1-105 GEN
Solar/Wind Harmer
0.714
315687AD1-152 GEN
Solar/Wind Harmer
1.245
316248AF1-058 C
Solar/Wind Harmer
0.281
970933AG2-581 GEN
Solar/Wind Harmer
7.23
966001AG1-469 GEN
Solar/Wind Helper
0.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.62 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:996.88
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.68 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1186.05
MW Contribution:
5.58
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.765
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.736
946301AF1-294 GEN
Solar/Wind Harmer
13.156
961791AG1-021 GEN
Solar/Wind Harmer
6.418
970683AG2-441 GEN
Solar/Wind Harmer
31.154
970681AG2-440 GEN
Solar/Wind Harmer
20.677
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.546
316486AD2-202 GEN
Solar/Wind Harmer
0.901
316238AB2-078_GEN
Solar/Wind Harmer
1.002
316239AB2-077_GEN
Solar/Wind Harmer
1.002
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.878
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.979
270455AD2-022 GEN
Solar/Wind Harmer
1.593
270457AD2-023 GEN
Solar/Wind Harmer
0.808
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.908
316327AA2-057 GEN
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.22
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.672
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.159
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.281
316405AF2-144 C
Solar/Wind Helper
0.234
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.158
970413AG2-270 GEN
50/50
29.68
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.214
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.235
971775AH1-396 GEN
Solar/Wind Harmer
3.055
959311AF2-222 GEN
Solar/Wind Harmer
44.444
964241AG1-285 GEN
Solar/Wind Harmer
30.357
316478AD1-087 GEN
Solar/Wind Harmer
3.077
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971683AH1-343 GEN
Solar/Wind Harmer
8.941
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.755
316222AC1-221 GEN
Solar/Wind Harmer
1.409
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.499
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.678
3146233WITAKRS
Solar/Wind Harmer
0.158
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.797
315722AD1-056 GEN
Solar/Wind Harmer
2.478
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.424
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.075
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.728
270494AE1-108_GEN
Solar/Wind Helper
3.729
315821AE2-092 GEN
Solar/Wind Helper
2.535
3144293JTRSVLE
50/50
1.158
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.815
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.418
970685AG2-442 GEN
Solar/Wind Harmer
40.479
316034AC1-036 C
Solar/Wind Harmer
0.777
315785AD2-033 C
Solar/Wind Harmer
9.425
315693AD1-088 GEN
Solar/Wind Harmer
20.651
957481AF2-042 GEN
Solar/Wind Harmer
118.484
316131AB2-060 GEN
Solar/Wind Harmer
3.728
970401AG2-262 GEN
Solar/Wind Harmer
1.862
971065AG2-659 GEN
Solar/Wind Harmer
10.95
316129AC1-054 GEN
Solar/Wind Harmer
1.833
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.541
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.908
316319Z2-044 C
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.973
3142053HEARTS
Solar/Wind Harmer
0.085
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.54
3144293JTRSVLE
50/50
1.158
970535AG2-341 GEN
50/50
4.753
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.506
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.178
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.022
970323AG2-213 GEN
Solar/Wind Harmer
21.647
970933AG2-581 GEN
Solar/Wind Harmer
36.177
970099AG2-077 GEN
Solar/Wind Harmer
47.394
313527AB2-043 GEN
Solar/Wind Harmer
5.52
316237AB2-079_GEN
Solar/Wind Harmer
1.002
315687AD1-152 GEN
Solar/Wind Harmer
3.681
962561AG1-105 GEN
Solar/Wind Harmer
16.518
964791AG1-342 GEN
Solar/Wind Harmer
6.094
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.82
316248AF1-058 C
Solar/Wind Harmer
0.739
942751AE2-291 GEN
Solar/Wind Harmer
9.07
313506AB2-031 GEN
Solar/Wind Harmer
0.863
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.391
961601AG1-000A GEN
Solar/Wind Harmer
2.762
315724AD1-057 GEN
Solar/Wind Harmer
1.363
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.98
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.061
3145603CNETO
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.011
316313AB2-026
Solar/Wind Helper
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.487
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.349
MECLTFEXP_MEC->PJM
CLTF
0.998
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.761
LAGNLTFEXP_LAGN->PJM
CLTF
2.651
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.334
TVALTFEXP_TVA->PJM
CLTF
1.312
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.313
WECLTFEXP_WEC->PJM
CLTF
0.159

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.62 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:996.88
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.62 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1185.66
MW Contribution:
5.58
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.765
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.736
946301AF1-294 GEN
Solar/Wind Harmer
13.156
961791AG1-021 GEN
Solar/Wind Harmer
6.418
970683AG2-441 GEN
Solar/Wind Harmer
31.154
970681AG2-440 GEN
Solar/Wind Harmer
20.677
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.546
316486AD2-202 GEN
Solar/Wind Harmer
0.901
316238AB2-078_GEN
Solar/Wind Harmer
1.002
316239AB2-077_GEN
Solar/Wind Harmer
1.002
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.878
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.979
270455AD2-022 GEN
Solar/Wind Harmer
1.593
270457AD2-023 GEN
Solar/Wind Harmer
0.808
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.908
316327AA2-057 GEN
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.22
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.672
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.159
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.281
316405AF2-144 C
Solar/Wind Helper
0.234
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.158
970413AG2-270 GEN
50/50
29.68
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.214
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.235
971775AH1-396 GEN
Solar/Wind Harmer
3.055
959311AF2-222 GEN
Solar/Wind Harmer
44.444
964241AG1-285 GEN
Solar/Wind Harmer
30.357
316478AD1-087 GEN
Solar/Wind Harmer
3.077
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971683AH1-343 GEN
Solar/Wind Harmer
8.941
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.755
316222AC1-221 GEN
Solar/Wind Harmer
1.409
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.499
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.678
3146233WITAKRS
Solar/Wind Harmer
0.158
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.797
315722AD1-056 GEN
Solar/Wind Harmer
2.478
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.424
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.075
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.728
270494AE1-108_GEN
Solar/Wind Helper
3.729
315821AE2-092 GEN
Solar/Wind Helper
2.535
3144293JTRSVLE
50/50
1.158
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.815
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.418
970685AG2-442 GEN
Solar/Wind Harmer
40.479
316034AC1-036 C
Solar/Wind Harmer
0.777
315785AD2-033 C
Solar/Wind Harmer
9.425
315693AD1-088 GEN
Solar/Wind Harmer
20.651
957481AF2-042 GEN
Solar/Wind Harmer
118.484
316131AB2-060 GEN
Solar/Wind Harmer
3.728
970401AG2-262 GEN
Solar/Wind Harmer
1.862
971065AG2-659 GEN
Solar/Wind Harmer
10.95
316129AC1-054 GEN
Solar/Wind Harmer
1.833
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.541
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.908
316319Z2-044 C
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.973
3142053HEARTS
Solar/Wind Harmer
0.085
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.54
3144293JTRSVLE
50/50
1.158
970535AG2-341 GEN
50/50
4.753
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.506
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.178
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.022
970323AG2-213 GEN
Solar/Wind Harmer
21.647
970933AG2-581 GEN
Solar/Wind Harmer
36.177
970099AG2-077 GEN
Solar/Wind Harmer
47.394
313527AB2-043 GEN
Solar/Wind Harmer
5.52
316237AB2-079_GEN
Solar/Wind Harmer
1.002
315687AD1-152 GEN
Solar/Wind Harmer
3.681
962561AG1-105 GEN
Solar/Wind Harmer
16.518
964791AG1-342 GEN
Solar/Wind Harmer
6.094
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.82
316248AF1-058 C
Solar/Wind Harmer
0.739
942751AE2-291 GEN
Solar/Wind Harmer
9.07
313506AB2-031 GEN
Solar/Wind Harmer
0.863
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.391
961601AG1-000A GEN
Solar/Wind Harmer
2.762
315724AD1-057 GEN
Solar/Wind Harmer
1.363
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.98
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.061
3145603CNETO
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.011
316313AB2-026
Solar/Wind Helper
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.487
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.349
MECLTFEXP_MEC->PJM
CLTF
0.998
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.761
LAGNLTFEXP_LAGN->PJM
CLTF
2.651
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.334
TVALTFEXP_TVA->PJM
CLTF
1.312
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.313
WECLTFEXP_WEC->PJM
CLTF
0.159

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:992.1
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.06 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1160.77
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.732
946301AF1-294 GEN
Solar/Wind Harmer
13.145
961791AG1-021 GEN
Solar/Wind Harmer
6.412
970683AG2-441 GEN
Solar/Wind Harmer
31.113
970681AG2-440 GEN
Solar/Wind Harmer
20.65
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.416
316486AD2-202 GEN
Solar/Wind Harmer
0.899
316238AB2-078_GEN
Solar/Wind Harmer
1
316239AB2-077_GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.854
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.978
270455AD2-022 GEN
Solar/Wind Harmer
1.57
270457AD2-023 GEN
Solar/Wind Harmer
0.796
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.903
316210AC1-098 GEN
Solar/Wind Harmer
1.214
316327AA2-057 GEN
Solar/Wind Harmer
0.781
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.657
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.208
3147133PAMPLIN
Solar/Wind Harmer
-0.162
970257AG2-171 GEN
Solar/Wind Harmer
16.215
971775AH1-396 GEN
Solar/Wind Harmer
3.051
959311AF2-222 GEN
Solar/Wind Harmer
44.382
964241AG1-285 GEN
Solar/Wind Harmer
30.309
316478AD1-087 GEN
Solar/Wind Harmer
3.07
316003AC1-222 GEN
Solar/Wind Harmer
2.211
971683AH1-343 GEN
Solar/Wind Harmer
8.909
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.749
316222AC1-221 GEN
Solar/Wind Harmer
1.395
316283AC2-100 C
Solar/Wind Harmer
1.274
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.497
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.765
315722AD1-056 GEN
Solar/Wind Harmer
2.458
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.421
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.303
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.08
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.72
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.412
970685AG2-442 GEN
Solar/Wind Harmer
40.43
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.413
315693AD1-088 GEN
Solar/Wind Harmer
20.618
957481AF2-042 GEN
Solar/Wind Harmer
118.263
316131AB2-060 GEN
Solar/Wind Harmer
3.721
970401AG2-262 GEN
Solar/Wind Harmer
1.857
971065AG2-659 GEN
Solar/Wind Harmer
10.923
316129AC1-054 GEN
Solar/Wind Harmer
1.828
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.54
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.907
316319Z2-044 C
Solar/Wind Harmer
0.413
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.962
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.157
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.015
970323AG2-213 GEN
Solar/Wind Harmer
21.621
970933AG2-581 GEN
Solar/Wind Harmer
36.112
970099AG2-077 GEN
Solar/Wind Harmer
47.305
313527AB2-043 GEN
Solar/Wind Harmer
5.511
316237AB2-079_GEN
Solar/Wind Harmer
1
315687AD1-152 GEN
Solar/Wind Harmer
3.67
962561AG1-105 GEN
Solar/Wind Harmer
16.477
964791AG1-342 GEN
Solar/Wind Harmer
6.078
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.814
316248AF1-058 C
Solar/Wind Harmer
0.736
942751AE2-291 GEN
Solar/Wind Harmer
9.035
313506AB2-031 GEN
Solar/Wind Harmer
0.862
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.21
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.77
316263AC1-034 GEN
Solar/Wind Harmer
3.352
961601AG1-000A GEN
Solar/Wind Harmer
2.73
315724AD1-057 GEN
Solar/Wind Harmer
1.352
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
316313AB2-026
Solar/Wind Helper
0.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.85 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:787.83
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:166.8 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:953.32
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151281ROARAP4
50/50
0.105
971845AH1-439 GEN
Solar/Wind Harmer
33.974
946301AF1-294 GEN
Solar/Wind Harmer
9.009
961791AG1-021 GEN
Solar/Wind Harmer
4.383
970683AG2-441 GEN
Solar/Wind Harmer
23.63
970681AG2-440 GEN
Solar/Wind Harmer
15.684
3144303KENBRDG
Solar/Wind Harmer
0.308
971967AH1-528 GEN
Solar/Wind Harmer
54.853
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970831AG2-522 GEN
Solar/Wind Harmer
7.484
3137643SOCKMAN
Solar/Wind Harmer
0.378
316426AA2-053 GEN
Solar/Wind Harmer
0.289
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.385
316210AC1-098 GEN
Solar/Wind Harmer
0.638
316327AA2-057 GEN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.661
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.219
3151371ROSEMS1
50/50
0.136
3151381ROSEMG2
50/50
0.102
3146776BUCKING
Solar/Wind Harmer
3.039
3146776BUCKING
Solar/Wind Harmer
0.246
970301AG2-198 GEN
Solar/Wind Harmer
22.145
3147133PAMPLIN
Solar/Wind Harmer
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.479
970323AG2-213 GEN
Solar/Wind Harmer
16.421
970933AG2-581 GEN
Solar/Wind Harmer
27.427
970099AG2-077 GEN
Solar/Wind Harmer
35.928
962561AG1-105 GEN
Solar/Wind Harmer
12.514
964791AG1-342 GEN
Solar/Wind Harmer
4.862
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.862
313506AB2-031 GEN
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.613
3145783HORNRTN
Solar/Wind Harmer
1.291
3145783HORNRTN
Solar/Wind Harmer
0.403
3145783HORNRTN
Solar/Wind Harmer
0.161
316049AB1-081 GEN
Solar/Wind Harmer
0.362
316263AC1-034 GEN
Solar/Wind Harmer
2.419
961601AG1-000A GEN
Solar/Wind Harmer
1.099
315724AD1-057 GEN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.182
962571AG1-106 GEN
Solar/Wind Harmer
0.862
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.054
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.103
316313AB2-026
Solar/Wind Helper
0.311
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3151261ROARAP2
50/50
0.115
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.379
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
1.452
970257AG2-171 GEN
Solar/Wind Harmer
12.316
971775AH1-396 GEN
Solar/Wind Harmer
0.616
959311AF2-222 GEN
Solar/Wind Harmer
33.641
964241AG1-285 GEN
Solar/Wind Harmer
23.019
316478AD1-087 GEN
Solar/Wind Harmer
1.096
971683AH1-343 GEN
Solar/Wind Harmer
6.767
3147043LAWRENC
Solar/Wind Harmer
0.096
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316222AC1-221 GEN
Solar/Wind Harmer
0.507
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
316212AC1-099_GEN
Solar/Wind Harmer
0.356
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.044
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
4.396
315722AD1-056 GEN
Solar/Wind Harmer
2.125
3145796HORNRTN
Solar/Wind Harmer
0.243
3145796HORNRTN
Solar/Wind Harmer
0.061
316011AB1-132 GEN
Solar/Wind Harmer
1.098
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3145823KELFORD
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3151281ROARAP4
50/50
0.112
971629AH1-314 GEN
50/50
5.731
3151561HALLBR1
50/50
0.157
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.87
970685AG2-442 GEN
Solar/Wind Harmer
30.706
316034AC1-036 C
Solar/Wind Harmer
0.025
315785AD2-033 C
Solar/Wind Harmer
2.995
315693AD1-088 GEN
Solar/Wind Harmer
17.617
957481AF2-042 GEN
Solar/Wind Harmer
89.82
316131AB2-060 GEN
Solar/Wind Harmer
0.958
970401AG2-262 GEN
Solar/Wind Harmer
1.486
971065AG2-659 GEN
Solar/Wind Harmer
8.296
316129AC1-054 GEN
Solar/Wind Harmer
0.695
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.161
3146233WITAKRS
Solar/Wind Harmer
0.265
3147123OTTER R
Solar/Wind Harmer
0.04
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.2
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.83 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:949.42
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:160.17 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1119.58
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.208
3147133PAMPLIN
Solar/Wind Harmer
-0.162
970257AG2-171 GEN
Solar/Wind Harmer
16.215
971775AH1-396 GEN
Solar/Wind Harmer
3.051
959311AF2-222 GEN
Solar/Wind Harmer
44.382
964241AG1-285 GEN
Solar/Wind Harmer
30.309
316478AD1-087 GEN
Solar/Wind Harmer
3.07
316003AC1-222 GEN
Solar/Wind Harmer
2.211
971683AH1-343 GEN
Solar/Wind Harmer
8.909
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.749
316222AC1-221 GEN
Solar/Wind Harmer
1.395
316283AC2-100 C
Solar/Wind Harmer
1.274
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.497
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.765
315722AD1-056 GEN
Solar/Wind Harmer
2.458
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.421
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.303
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.08
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.72
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.412
970685AG2-442 GEN
Solar/Wind Harmer
40.43
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.413
315693AD1-088 GEN
Solar/Wind Harmer
20.618
957481AF2-042 GEN
Solar/Wind Harmer
118.263
316131AB2-060 GEN
Solar/Wind Harmer
3.721
970401AG2-262 GEN
Solar/Wind Harmer
1.857
971065AG2-659 GEN
Solar/Wind Harmer
10.923
316129AC1-054 GEN
Solar/Wind Harmer
1.828
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.54
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.907
316319Z2-044 C
Solar/Wind Harmer
0.413
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.962
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.157
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.015
970323AG2-213 GEN
Solar/Wind Harmer
21.621
970099AG2-077 GEN
Solar/Wind Harmer
47.305
313527AB2-043 GEN
Solar/Wind Harmer
5.511
316237AB2-079_GEN
Solar/Wind Harmer
1
315687AD1-152 GEN
Solar/Wind Harmer
3.67
962561AG1-105 GEN
Solar/Wind Harmer
16.477
964791AG1-342 GEN
Solar/Wind Harmer
6.078
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.814
316248AF1-058 C
Solar/Wind Harmer
0.736
942751AE2-291 GEN
Solar/Wind Harmer
9.035
313506AB2-031 GEN
Solar/Wind Harmer
0.862
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.21
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.77
316263AC1-034 GEN
Solar/Wind Harmer
3.352
961601AG1-000A GEN
Solar/Wind Harmer
2.73
315724AD1-057 GEN
Solar/Wind Harmer
1.352
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
316313AB2-026
Solar/Wind Helper
0.311
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.732
946301AF1-294 GEN
Solar/Wind Harmer
13.145
961791AG1-021 GEN
Solar/Wind Harmer
6.412
970683AG2-441 GEN
Solar/Wind Harmer
31.113
970681AG2-440 GEN
Solar/Wind Harmer
20.65
3144303KENBRDG
Solar/Wind Harmer
-0.035
316486AD2-202 GEN
Solar/Wind Harmer
0.899
316238AB2-078_GEN
Solar/Wind Harmer
1
316239AB2-077_GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.854
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.978
270455AD2-022 GEN
Solar/Wind Harmer
1.57
270457AD2-023 GEN
Solar/Wind Harmer
0.796
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.903
316210AC1-098 GEN
Solar/Wind Harmer
1.214
316327AA2-057 GEN
Solar/Wind Harmer
0.781
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.657
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.83 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:949.42
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:160.17 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1119.58
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.208
3147133PAMPLIN
Solar/Wind Harmer
-0.162
970257AG2-171 GEN
Solar/Wind Harmer
16.215
971775AH1-396 GEN
Solar/Wind Harmer
3.051
959311AF2-222 GEN
Solar/Wind Harmer
44.382
964241AG1-285 GEN
Solar/Wind Harmer
30.309
316478AD1-087 GEN
Solar/Wind Harmer
3.07
316003AC1-222 GEN
Solar/Wind Harmer
2.211
971683AH1-343 GEN
Solar/Wind Harmer
8.909
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.749
316222AC1-221 GEN
Solar/Wind Harmer
1.395
316283AC2-100 C
Solar/Wind Harmer
1.274
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.497
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.765
315722AD1-056 GEN
Solar/Wind Harmer
2.458
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.421
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.303
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.08
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.72
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.412
970685AG2-442 GEN
Solar/Wind Harmer
40.43
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.413
315693AD1-088 GEN
Solar/Wind Harmer
20.618
957481AF2-042 GEN
Solar/Wind Harmer
118.263
316131AB2-060 GEN
Solar/Wind Harmer
3.721
970401AG2-262 GEN
Solar/Wind Harmer
1.857
971065AG2-659 GEN
Solar/Wind Harmer
10.923
316129AC1-054 GEN
Solar/Wind Harmer
1.828
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.54
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.907
316319Z2-044 C
Solar/Wind Harmer
0.413
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.962
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.157
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.015
970323AG2-213 GEN
Solar/Wind Harmer
21.621
970099AG2-077 GEN
Solar/Wind Harmer
47.305
313527AB2-043 GEN
Solar/Wind Harmer
5.511
316237AB2-079_GEN
Solar/Wind Harmer
1
315687AD1-152 GEN
Solar/Wind Harmer
3.67
962561AG1-105 GEN
Solar/Wind Harmer
16.477
964791AG1-342 GEN
Solar/Wind Harmer
6.078
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.814
316248AF1-058 C
Solar/Wind Harmer
0.736
942751AE2-291 GEN
Solar/Wind Harmer
9.035
313506AB2-031 GEN
Solar/Wind Harmer
0.862
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.21
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.77
316263AC1-034 GEN
Solar/Wind Harmer
3.352
961601AG1-000A GEN
Solar/Wind Harmer
2.73
315724AD1-057 GEN
Solar/Wind Harmer
1.352
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
316313AB2-026
Solar/Wind Helper
0.311
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.732
946301AF1-294 GEN
Solar/Wind Harmer
13.145
961791AG1-021 GEN
Solar/Wind Harmer
6.412
970683AG2-441 GEN
Solar/Wind Harmer
31.113
970681AG2-440 GEN
Solar/Wind Harmer
20.65
3144303KENBRDG
Solar/Wind Harmer
-0.035
316486AD2-202 GEN
Solar/Wind Harmer
0.899
316238AB2-078_GEN
Solar/Wind Harmer
1
316239AB2-077_GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.854
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.978
270455AD2-022 GEN
Solar/Wind Harmer
1.57
270457AD2-023 GEN
Solar/Wind Harmer
0.796
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.903
316210AC1-098 GEN
Solar/Wind Harmer
1.214
316327AA2-057 GEN
Solar/Wind Harmer
0.781
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.657
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.0 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:771.57
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:164.25 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:938.71
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3151261ROARAP2
50/50
0.115
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.379
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
1.452
970257AG2-171 GEN
Solar/Wind Harmer
12.316
971775AH1-396 GEN
Solar/Wind Harmer
0.616
959311AF2-222 GEN
Solar/Wind Harmer
33.641
964241AG1-285 GEN
Solar/Wind Harmer
23.019
316478AD1-087 GEN
Solar/Wind Harmer
1.096
971683AH1-343 GEN
Solar/Wind Harmer
6.767
3147043LAWRENC
Solar/Wind Harmer
0.096
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316222AC1-221 GEN
Solar/Wind Harmer
0.507
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
316212AC1-099_GEN
Solar/Wind Harmer
0.356
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.044
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
4.396
315722AD1-056 GEN
Solar/Wind Harmer
2.125
3145796HORNRTN
Solar/Wind Harmer
0.243
3145796HORNRTN
Solar/Wind Harmer
0.061
316011AB1-132 GEN
Solar/Wind Harmer
1.098
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3145823KELFORD
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151281ROARAP4
50/50
0.105
971845AH1-439 GEN
Solar/Wind Harmer
33.974
946301AF1-294 GEN
Solar/Wind Harmer
9.009
961791AG1-021 GEN
Solar/Wind Harmer
4.383
970683AG2-441 GEN
Solar/Wind Harmer
23.63
970681AG2-440 GEN
Solar/Wind Harmer
15.684
3144303KENBRDG
Solar/Wind Harmer
0.308
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970831AG2-522 GEN
Solar/Wind Harmer
7.484
3137643SOCKMAN
Solar/Wind Harmer
0.378
316426AA2-053 GEN
Solar/Wind Harmer
0.289
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.385
316210AC1-098 GEN
Solar/Wind Harmer
0.638
316327AA2-057 GEN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.661
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.219
3151371ROSEMS1
50/50
0.136
3151381ROSEMG2
50/50
0.102
3146776BUCKING
Solar/Wind Harmer
3.039
3146776BUCKING
Solar/Wind Harmer
0.246
970301AG2-198 GEN
Solar/Wind Harmer
22.145
3147133PAMPLIN
Solar/Wind Harmer
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.479
970323AG2-213 GEN
Solar/Wind Harmer
16.421
970099AG2-077 GEN
Solar/Wind Harmer
35.928
962561AG1-105 GEN
Solar/Wind Harmer
12.514
964791AG1-342 GEN
Solar/Wind Harmer
4.862
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.862
313506AB2-031 GEN
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.613
3145783HORNRTN
Solar/Wind Harmer
1.291
3145783HORNRTN
Solar/Wind Harmer
0.403
3145783HORNRTN
Solar/Wind Harmer
0.161
316049AB1-081 GEN
Solar/Wind Harmer
0.362
316263AC1-034 GEN
Solar/Wind Harmer
2.419
961601AG1-000A GEN
Solar/Wind Harmer
1.099
315724AD1-057 GEN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.182
962571AG1-106 GEN
Solar/Wind Harmer
0.862
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.054
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.103
316313AB2-026
Solar/Wind Helper
0.311
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3151281ROARAP4
50/50
0.112
971629AH1-314 GEN
50/50
5.731
3151561HALLBR1
50/50
0.157
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.87
970685AG2-442 GEN
Solar/Wind Harmer
30.706
316034AC1-036 C
Solar/Wind Harmer
0.025
315785AD2-033 C
Solar/Wind Harmer
2.995
315693AD1-088 GEN
Solar/Wind Harmer
17.617
957481AF2-042 GEN
Solar/Wind Harmer
89.82
316131AB2-060 GEN
Solar/Wind Harmer
0.958
970401AG2-262 GEN
Solar/Wind Harmer
1.486
971065AG2-659 GEN
Solar/Wind Harmer
8.296
316129AC1-054 GEN
Solar/Wind Harmer
0.695
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.161
3146233WITAKRS
Solar/Wind Harmer
0.265
3147123OTTER R
Solar/Wind Harmer
0.04
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.2
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.05 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:733.32
MW Contribution:
0.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.14 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:795.03
MW Contribution:
0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3151261ROARAP2
50/50
0.32
3144293JTRSVLE
50/50
0.217
970413AG2-270 GEN
50/50
7.462
316011AB1-132 GEN
Solar/Wind Harmer
6.264
316181AB2-040 GEN
Solar/Wind Harmer
0.488
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.288
3145796HORNRTN
Solar/Wind Harmer
0.322
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
315722AD1-056 GEN
Solar/Wind Harmer
8.499
316212AC1-099_GEN
Solar/Wind Harmer
1.032
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.939
3146233WITAKRS
Solar/Wind Harmer
0.127
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.05
3145823KELFORD
Solar/Wind Harmer
0.181
971623AH1-311 GEN
Solar/Wind Harmer
0.36
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
3146073TAR RVR
Solar/Wind Harmer
0.168
3146083TARBORO
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.276
3145893MURPHYS
Solar/Wind Harmer
0.165
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145933PARMELE
Solar/Wind Harmer
0.135
3146206CASHIE
Solar/Wind Harmer
0.127
3145963POPLR C
Solar/Wind Harmer
0.122
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
970257AG2-171 GEN
Solar/Wind Harmer
3.241
971775AH1-396 GEN
Solar/Wind Harmer
0.162
964241AG1-285 GEN
Solar/Wind Harmer
6.48
959311AF2-222 GEN
Solar/Wind Harmer
7.79
316478AD1-087 GEN
Solar/Wind Harmer
0.277
3147133PAMPLIN
Solar/Wind Harmer
0.233
971683AH1-343 GEN
Solar/Wind Harmer
2.412
942461AE2-259 GEN
Solar/Wind Harmer
0
3151281ROARAP4
50/50
0.291
3151601KERR 3
50/50
0.265
3151611KERR 4
50/50
0.265
3151621KERR 5
50/50
0.265
3151631KERR 6
50/50
0.265
3151151S HAMPT1
50/50
0.295
3151541CLOVER2
50/50
1.701
315652AC1-086 GEN
Solar/Wind Harmer
37.99
3145796HORNRTN
Solar/Wind Harmer
1.03
3145796HORNRTN
Solar/Wind Harmer
0.129
3137643SOCKMAN
Solar/Wind Harmer
1.19
316426AA2-053 GEN
Solar/Wind Harmer
0.818
3146043SEABORD
Solar/Wind Harmer
0.215
316274AC1-208 GEN
Solar/Wind Harmer
1.093
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316327AA2-057 GEN
Solar/Wind Harmer
0.288
3146033SCOT NK
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
7.902
3145683EARLEYS
Solar/Wind Harmer
0.342
3145683EARLEYS
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
0.171
316463AE2-346 GEN
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.355
3145513AHOSKIE
Solar/Wind Harmer
0.169
3145573BETHELC
Solar/Wind Harmer
0.168
3145573BETHELC
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.445
3145893MURPHYS
Solar/Wind Harmer
0.165
957861AF2-080 GEN
Solar/Wind Harmer
6.72
3145746EVERETS
Solar/Wind Harmer
0.562
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.127
970601AG2-382 GEN
Solar/Wind Harmer
4.745
315732AD1-074 GEN1
Solar/Wind Harmer
0.606
315733AD1-074 GEN2
Solar/Wind Harmer
0.606
3130546PLYMOUTH
Solar/Wind Harmer
0.103
3144303KENBRDG
Solar/Wind Harmer
0.081
946301AF1-294 GEN
Solar/Wind Harmer
1.687
961791AG1-021 GEN
Solar/Wind Harmer
0.821
970683AG2-441 GEN
Solar/Wind Harmer
5.044
970681AG2-440 GEN
Solar/Wind Harmer
3.348
316486AD2-202 GEN
Solar/Wind Harmer
0.081
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
3151361ROSEMG1
50/50
1.16
3151371ROSEMS1
50/50
0.719
3151381ROSEMG2
50/50
0.543
3151261ROARAP2
50/50
0.313
3151581KERR 1
50/50
0.094
970535AG2-341 GEN
50/50
2.22
3152661PLYWOOD A
50/50
0.19
3144293JTRSVLE
50/50
0.217
970909AG2-566 GEN
50/50
0.672
316365GEN2_N
Solar/Wind Harmer
1.159
962571AG1-106 GEN
Solar/Wind Harmer
4.914
313506AB2-031 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
0.966
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
4.494
3145783HORNRTN
Solar/Wind Harmer
3.595
3145783HORNRTN
Solar/Wind Harmer
1.123
3145783HORNRTN
Solar/Wind Harmer
0.449
315724AD1-057 GEN
Solar/Wind Harmer
4.741
961601AG1-000A GEN
Solar/Wind Harmer
3.263
316049AB1-081 GEN
Solar/Wind Harmer
1.023
316263AC1-034 GEN
Solar/Wind Harmer
6.835
316140AB2-099
Solar/Wind Harmer
0.06
3145493TOT1
Solar/Wind Harmer
0.39
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
3146173TUNIS
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
1.103
3145893MURPHYS
Solar/Wind Harmer
0.296
316005AA1-067
Solar/Wind Harmer
0.151
3145933PARMELE
Solar/Wind Harmer
0.27
3145933PARMELE
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
5.506
970323AG2-213 GEN
Solar/Wind Harmer
4.321
962561AG1-105 GEN
Solar/Wind Harmer
4.722
964791AG1-342 GEN
Solar/Wind Harmer
1.815
3146843MT LREL
Solar/Wind Harmer
0.094
3146843MT LREL
Solar/Wind Harmer
0.094
958211AF2-115 GEN
Solar/Wind Harmer
1.026
316118AC1-105 GEN
Solar/Wind Harmer
0.219
315614AA2-178 GEN
Solar/Wind Harmer
0.481
970099AG2-077 GEN
Solar/Wind Harmer
8.585
315742AE1-103 GEN
Solar/Wind Harmer
1.165
3147133PAMPLIN
Solar/Wind Harmer
0.074
3147133PAMPLIN
Solar/Wind Harmer
0.059
970301AG2-198 GEN
Solar/Wind Harmer
2.687
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3147043LAWRENC
50/50
3.131
3151281ROARAP4
50/50
0.311
3151591KERR 2
50/50
0.265
3151641KERR 7
50/50
0.265
3144293JTRSVLE
50/50
0.217
3144293JTRSVLE
50/50
0.171
3151531CLOVER1
50/50
1.713
316023GEN1_S
Solar/Wind Harmer
1.159
960081AF2-299 GEN
Solar/Wind Harmer
3.999
3145796HORNRTN
Solar/Wind Harmer
1.062
3145796HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.446
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.744
3145823KELFORD
Solar/Wind Harmer
0.181
316359AB2-059 GEN
Solar/Wind Harmer
0.64
3142053HEARTS
Solar/Wind Harmer
0.317
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.143
316129AC1-054 GEN
Solar/Wind Harmer
0.654
3145683EARLEYS
Solar/Wind Harmer
0.171
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.168
3145493TOT1
Solar/Wind Harmer
0.748
3146173TUNIS
Solar/Wind Harmer
0.168
971065AG2-659 GEN
Solar/Wind Harmer
7.153
3145893MURPHYS
Solar/Wind Harmer
0.659
3145893MURPHYS
Solar/Wind Harmer
0.732
3156021HOLLOMANSOL
Solar/Wind Harmer
0.704
316494AC1-189 GEN
Solar/Wind Harmer
0.527
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146293MARTNCO
Solar/Wind Harmer
0.125
3146206CASHIE
Solar/Wind Harmer
0.127
971547AH1-271 GEN
Solar/Wind Harmer
2.711
3145963POPLR C
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.368
315737AD1-076 GEN
Solar/Wind Harmer
1.366
315785AD2-033 C
Solar/Wind Harmer
0.845
970401AG2-262 GEN
Solar/Wind Harmer
0.555
316034AC1-036 C
Solar/Wind Harmer
0.006
971563AH1-280 GEN
Solar/Wind Harmer
0.912
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3145663CRESWEL
Solar/Wind Harmer
0.237
971163AH1-040 GEN
Solar/Wind Harmer
6.763
315693AD1-088 GEN
Solar/Wind Harmer
3.903
970685AG2-442 GEN
Solar/Wind Harmer
6.061
957481AF2-042 GEN
Solar/Wind Harmer
21.462
3146376EDENTON
Solar/Wind Harmer
0.268
3146376EDENTON
Solar/Wind Harmer
0.268
3144356SAPONY
Solar/Wind Helper
0.935
3130156CHOWAN
Solar/Wind Harmer
0.06
315671AE2-027_GEN
Solar/Wind Helper
0.949
3146376EDENTON
Solar/Wind Harmer
0.06
316222AC1-221 GEN
Solar/Wind Harmer
0.246
316283AC2-100 C
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.043
316315AB2-025 C
Solar/Wind Helper
0.796
3130156CHOWAN
Solar/Wind Harmer
0.06
3130156CHOWAN
Solar/Wind Harmer
0.06
315839AE2-212 C
Solar/Wind Helper
0.175
3143316POE
Solar/Wind Helper
0.502
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.588
MECLTFEXP_MEC->PJM
CLTF
0.854
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
4.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.63
LAGNLTFEXP_LAGN->PJM
CLTF
2.181
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.5
TVALTFEXP_TVA->PJM
CLTF
1.078
NYPJM->LTFIMP_NY
CLTF
0.358
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.141

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.76 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:731.37
MW Contribution:
0.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.51 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:790.71
MW Contribution:
0.61
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.16
3151371ROSEMS1
50/50
0.719
3151381ROSEMG2
50/50
0.543
3151261ROARAP2
50/50
0.313
3151581KERR 1
50/50
0.094
970535AG2-341 GEN
50/50
2.22
3152661PLYWOOD A
50/50
0.19
3144293JTRSVLE
50/50
0.217
970909AG2-566 GEN
50/50
0.672
316365GEN2_N
Solar/Wind Harmer
1.159
962571AG1-106 GEN
Solar/Wind Harmer
4.914
313506AB2-031 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
0.966
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
4.494
3145783HORNRTN
Solar/Wind Harmer
3.595
3145783HORNRTN
Solar/Wind Harmer
1.123
3145783HORNRTN
Solar/Wind Harmer
0.449
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3151261ROARAP2
50/50
0.32
3144293JTRSVLE
50/50
0.217
970413AG2-270 GEN
50/50
7.462
316011AB1-132 GEN
Solar/Wind Harmer
6.264
316181AB2-040 GEN
Solar/Wind Harmer
0.488
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.288
3145796HORNRTN
Solar/Wind Harmer
0.322
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
315722AD1-056 GEN
Solar/Wind Harmer
8.499
316212AC1-099_GEN
Solar/Wind Harmer
1.032
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.939
3146233WITAKRS
Solar/Wind Harmer
0.127
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.05
3145823KELFORD
Solar/Wind Harmer
0.181
971623AH1-311 GEN
Solar/Wind Harmer
0.36
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
3146073TAR RVR
Solar/Wind Harmer
0.168
3146083TARBORO
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.276
3145893MURPHYS
Solar/Wind Harmer
0.165
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3151281ROARAP4
50/50
0.291
3151601KERR 3
50/50
0.265
3151611KERR 4
50/50
0.265
3151621KERR 5
50/50
0.265
3151631KERR 6
50/50
0.265
3151151S HAMPT1
50/50
0.295
3151541CLOVER2
50/50
1.701
315652AC1-086 GEN
Solar/Wind Harmer
37.99
3145796HORNRTN
Solar/Wind Harmer
1.03
3145796HORNRTN
Solar/Wind Harmer
0.129
3137643SOCKMAN
Solar/Wind Harmer
1.19
316426AA2-053 GEN
Solar/Wind Harmer
0.818
3146043SEABORD
Solar/Wind Harmer
0.215
316274AC1-208 GEN
Solar/Wind Harmer
1.093
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316327AA2-057 GEN
Solar/Wind Harmer
0.288
3146033SCOT NK
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
7.902
3145683EARLEYS
Solar/Wind Harmer
0.342
3145683EARLEYS
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
0.171
316463AE2-346 GEN
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.355
3145513AHOSKIE
Solar/Wind Harmer
0.169
3145573BETHELC
Solar/Wind Harmer
0.168
3145573BETHELC
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.445
3145893MURPHYS
Solar/Wind Harmer
0.165
957861AF2-080 GEN
Solar/Wind Harmer
6.72
3145746EVERETS
Solar/Wind Harmer
0.562
3145746EVERETS
Solar/Wind Harmer
0.141
315724AD1-057 GEN
Solar/Wind Harmer
4.741
961601AG1-000A GEN
Solar/Wind Harmer
3.263
316049AB1-081 GEN
Solar/Wind Harmer
1.023
316263AC1-034 GEN
Solar/Wind Harmer
6.835
316140AB2-099
Solar/Wind Harmer
0.06
3145493TOT1
Solar/Wind Harmer
0.39
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
3146173TUNIS
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
1.103
3145893MURPHYS
Solar/Wind Harmer
0.296
316005AA1-067
Solar/Wind Harmer
0.151
3145933PARMELE
Solar/Wind Harmer
0.27
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3147043LAWRENC
50/50
3.131
3151281ROARAP4
50/50
0.311
3151591KERR 2
50/50
0.265
3151641KERR 7
50/50
0.265
3144293JTRSVLE
50/50
0.217
3144293JTRSVLE
50/50
0.171
3151531CLOVER1
50/50
1.713
316023GEN1_S
Solar/Wind Harmer
1.159
960081AF2-299 GEN
Solar/Wind Harmer
3.999
3145796HORNRTN
Solar/Wind Harmer
1.062
3145796HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.446
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.744
3145823KELFORD
Solar/Wind Harmer
0.181
316359AB2-059 GEN
Solar/Wind Harmer
0.64
3142053HEARTS
Solar/Wind Harmer
0.317
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.143
316129AC1-054 GEN
Solar/Wind Harmer
0.654
3145683EARLEYS
Solar/Wind Harmer
0.171
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.168
3145493TOT1
Solar/Wind Harmer
0.748
3146173TUNIS
Solar/Wind Harmer
0.168
971065AG2-659 GEN
Solar/Wind Harmer
7.153
3145893MURPHYS
Solar/Wind Harmer
0.659
3145893MURPHYS
Solar/Wind Harmer
0.732
3156021HOLLOMANSOL
Solar/Wind Harmer
0.704
316494AC1-189 GEN
Solar/Wind Harmer
0.527
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.127
970601AG2-382 GEN
Solar/Wind Harmer
4.745
315732AD1-074 GEN1
Solar/Wind Harmer
0.606
315733AD1-074 GEN2
Solar/Wind Harmer
0.606
3130546PLYMOUTH
Solar/Wind Harmer
0.103
3144303KENBRDG
Solar/Wind Harmer
0.081
946301AF1-294 GEN
Solar/Wind Harmer
1.687
961791AG1-021 GEN
Solar/Wind Harmer
0.821
970683AG2-441 GEN
Solar/Wind Harmer
5.044
970681AG2-440 GEN
Solar/Wind Harmer
3.348
971967AH1-528 GEN
Solar/Wind Harmer
12.902
316486AD2-202 GEN
Solar/Wind Harmer
0.081
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
3130156CHOWAN
Solar/Wind Harmer
0.06
3130156CHOWAN
Solar/Wind Harmer
0.06
315839AE2-212 C
Solar/Wind Helper
0.175
3143316POE
Solar/Wind Helper
0.502
3145933PARMELE
Solar/Wind Harmer
0.135
3146206CASHIE
Solar/Wind Harmer
0.127
3145963POPLR C
Solar/Wind Harmer
0.122
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
970257AG2-171 GEN
Solar/Wind Harmer
3.241
971775AH1-396 GEN
Solar/Wind Harmer
0.162
964241AG1-285 GEN
Solar/Wind Harmer
6.48
959311AF2-222 GEN
Solar/Wind Harmer
7.79
316478AD1-087 GEN
Solar/Wind Harmer
0.277
3147133PAMPLIN
Solar/Wind Harmer
0.233
971683AH1-343 GEN
Solar/Wind Harmer
2.412
942461AE2-259 GEN
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
0.06
316222AC1-221 GEN
Solar/Wind Harmer
0.246
316283AC2-100 C
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.043
3146293MARTNCO
Solar/Wind Harmer
0.125
3146206CASHIE
Solar/Wind Harmer
0.127
971547AH1-271 GEN
Solar/Wind Harmer
2.711
3145963POPLR C
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.368
315737AD1-076 GEN
Solar/Wind Harmer
1.366
315785AD2-033 C
Solar/Wind Harmer
0.845
970401AG2-262 GEN
Solar/Wind Harmer
0.555
316034AC1-036 C
Solar/Wind Harmer
0.006
971563AH1-280 GEN
Solar/Wind Harmer
0.912
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3145663CRESWEL
Solar/Wind Harmer
0.237
971163AH1-040 GEN
Solar/Wind Harmer
6.763
315693AD1-088 GEN
Solar/Wind Harmer
3.903
970685AG2-442 GEN
Solar/Wind Harmer
6.061
957481AF2-042 GEN
Solar/Wind Harmer
21.462
3130156CHOWAN
Solar/Wind Harmer
0.06
315671AE2-027_GEN
Solar/Wind Helper
0.949
3145933PARMELE
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
5.506
970323AG2-213 GEN
Solar/Wind Harmer
4.321
962561AG1-105 GEN
Solar/Wind Harmer
4.722
964791AG1-342 GEN
Solar/Wind Harmer
1.815
3146843MT LREL
Solar/Wind Harmer
0.094
3146843MT LREL
Solar/Wind Harmer
0.094
958211AF2-115 GEN
Solar/Wind Harmer
1.026
316118AC1-105 GEN
Solar/Wind Harmer
0.219
315614AA2-178 GEN
Solar/Wind Harmer
0.481
970933AG2-581 GEN
Solar/Wind Harmer
6.451
970099AG2-077 GEN
Solar/Wind Harmer
8.585
315742AE1-103 GEN
Solar/Wind Harmer
1.165
3147133PAMPLIN
Solar/Wind Harmer
0.074
3147133PAMPLIN
Solar/Wind Harmer
0.059
970301AG2-198 GEN
Solar/Wind Harmer
2.687
3146376EDENTON
Solar/Wind Harmer
0.268
3146376EDENTON
Solar/Wind Harmer
0.268
3144356SAPONY
Solar/Wind Helper
0.935
316315AB2-025 C
Solar/Wind Helper
0.796
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.588
MECLTFEXP_MEC->PJM
CLTF
0.854
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
4.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.63
LAGNLTFEXP_LAGN->PJM
CLTF
2.181
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.5
TVALTFEXP_TVA->PJM
CLTF
1.078
NYPJM->LTFIMP_NY
CLTF
0.358
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.141

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.67 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:798.63
MW Contribution:
0.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.68 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:859.72
MW Contribution:
0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3151261ROARAP2
50/50
0.32
3144293JTRSVLE
50/50
0.217
970413AG2-270 GEN
50/50
7.462
316011AB1-132 GEN
Solar/Wind Harmer
6.264
316181AB2-040 GEN
Solar/Wind Harmer
0.488
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.288
3145796HORNRTN
Solar/Wind Harmer
0.322
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
315722AD1-056 GEN
Solar/Wind Harmer
8.499
316212AC1-099_GEN
Solar/Wind Harmer
1.032
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.939
3146233WITAKRS
Solar/Wind Harmer
0.127
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.05
3145823KELFORD
Solar/Wind Harmer
0.181
971623AH1-311 GEN
Solar/Wind Harmer
0.36
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
3146073TAR RVR
Solar/Wind Harmer
0.168
3146083TARBORO
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.276
3145893MURPHYS
Solar/Wind Harmer
0.165
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145933PARMELE
Solar/Wind Harmer
0.135
3146206CASHIE
Solar/Wind Harmer
0.127
3145963POPLR C
Solar/Wind Harmer
0.122
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
970257AG2-171 GEN
Solar/Wind Harmer
3.241
971775AH1-396 GEN
Solar/Wind Harmer
0.162
964241AG1-285 GEN
Solar/Wind Harmer
6.48
959311AF2-222 GEN
Solar/Wind Harmer
7.79
316478AD1-087 GEN
Solar/Wind Harmer
0.277
3147133PAMPLIN
Solar/Wind Harmer
0.233
971683AH1-343 GEN
Solar/Wind Harmer
2.412
942461AE2-259 GEN
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
0.06
316222AC1-221 GEN
Solar/Wind Harmer
0.246
316283AC2-100 C
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.043
3151281ROARAP4
50/50
0.291
3151601KERR 3
50/50
0.265
3151611KERR 4
50/50
0.265
3151621KERR 5
50/50
0.265
3151631KERR 6
50/50
0.265
3151151S HAMPT1
50/50
0.295
3151541CLOVER2
50/50
1.701
315814AE2-033 C
Solar/Wind Harmer
66.731
315652AC1-086 GEN
Solar/Wind Harmer
37.99
3145796HORNRTN
Solar/Wind Harmer
1.03
3145796HORNRTN
Solar/Wind Harmer
0.129
3137643SOCKMAN
Solar/Wind Harmer
1.19
316426AA2-053 GEN
Solar/Wind Harmer
0.818
3146043SEABORD
Solar/Wind Harmer
0.215
316274AC1-208 GEN
Solar/Wind Harmer
1.093
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316327AA2-057 GEN
Solar/Wind Harmer
0.288
3146033SCOT NK
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
7.902
3145683EARLEYS
Solar/Wind Harmer
0.342
3145683EARLEYS
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
0.171
316463AE2-346 GEN
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.355
3145513AHOSKIE
Solar/Wind Harmer
0.169
3145573BETHELC
Solar/Wind Harmer
0.168
3145573BETHELC
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.445
3145893MURPHYS
Solar/Wind Harmer
0.165
957861AF2-080 GEN
Solar/Wind Harmer
6.72
3145746EVERETS
Solar/Wind Harmer
0.562
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.127
970601AG2-382 GEN
Solar/Wind Harmer
4.745
315732AD1-074 GEN1
Solar/Wind Harmer
0.606
315733AD1-074 GEN2
Solar/Wind Harmer
0.606
3130546PLYMOUTH
Solar/Wind Harmer
0.103
3144303KENBRDG
Solar/Wind Harmer
0.081
946301AF1-294 GEN
Solar/Wind Harmer
1.687
961791AG1-021 GEN
Solar/Wind Harmer
0.821
970683AG2-441 GEN
Solar/Wind Harmer
5.044
970681AG2-440 GEN
Solar/Wind Harmer
3.348
316486AD2-202 GEN
Solar/Wind Harmer
0.081
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
3130156CHOWAN
Solar/Wind Harmer
0.06
3130156CHOWAN
Solar/Wind Harmer
0.06
315839AE2-212 C
Solar/Wind Helper
0.175
3143316POE
Solar/Wind Helper
0.502
3151361ROSEMG1
50/50
1.16
3151371ROSEMS1
50/50
0.719
3151381ROSEMG2
50/50
0.543
3151261ROARAP2
50/50
0.313
3151581KERR 1
50/50
0.094
970535AG2-341 GEN
50/50
2.22
3152661PLYWOOD A
50/50
0.19
3144293JTRSVLE
50/50
0.217
970909AG2-566 GEN
50/50
0.672
316365GEN2_N
Solar/Wind Harmer
1.159
962571AG1-106 GEN
Solar/Wind Harmer
4.914
313506AB2-031 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
0.966
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
4.494
3145783HORNRTN
Solar/Wind Harmer
3.595
3145783HORNRTN
Solar/Wind Harmer
1.123
3145783HORNRTN
Solar/Wind Harmer
0.449
315724AD1-057 GEN
Solar/Wind Harmer
4.741
961601AG1-000A GEN
Solar/Wind Harmer
3.263
316049AB1-081 GEN
Solar/Wind Harmer
1.023
316263AC1-034 GEN
Solar/Wind Harmer
6.835
316140AB2-099
Solar/Wind Harmer
0.06
3145493TOT1
Solar/Wind Harmer
0.39
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
3146173TUNIS
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
1.103
3145893MURPHYS
Solar/Wind Harmer
0.296
316005AA1-067
Solar/Wind Harmer
0.151
3145933PARMELE
Solar/Wind Harmer
0.27
3145933PARMELE
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
5.506
970323AG2-213 GEN
Solar/Wind Harmer
4.321
962561AG1-105 GEN
Solar/Wind Harmer
4.722
964791AG1-342 GEN
Solar/Wind Harmer
1.815
3146843MT LREL
Solar/Wind Harmer
0.094
3146843MT LREL
Solar/Wind Harmer
0.094
958211AF2-115 GEN
Solar/Wind Harmer
1.026
316118AC1-105 GEN
Solar/Wind Harmer
0.219
315614AA2-178 GEN
Solar/Wind Harmer
0.481
970099AG2-077 GEN
Solar/Wind Harmer
8.585
315742AE1-103 GEN
Solar/Wind Harmer
1.165
3147133PAMPLIN
Solar/Wind Harmer
0.074
3147133PAMPLIN
Solar/Wind Harmer
0.059
970301AG2-198 GEN
Solar/Wind Harmer
2.687
3146376EDENTON
Solar/Wind Harmer
0.268
3146376EDENTON
Solar/Wind Harmer
0.268
3144356SAPONY
Solar/Wind Helper
0.935
316315AB2-025 C
Solar/Wind Helper
0.796
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3147043LAWRENC
50/50
3.131
3151281ROARAP4
50/50
0.311
3151591KERR 2
50/50
0.265
3151641KERR 7
50/50
0.265
3144293JTRSVLE
50/50
0.217
3144293JTRSVLE
50/50
0.171
3151531CLOVER1
50/50
1.713
316023GEN1_S
Solar/Wind Harmer
1.159
960081AF2-299 GEN
Solar/Wind Harmer
3.999
3145796HORNRTN
Solar/Wind Harmer
1.062
3145796HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.446
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.744
3145823KELFORD
Solar/Wind Harmer
0.181
316359AB2-059 GEN
Solar/Wind Harmer
0.64
3142053HEARTS
Solar/Wind Harmer
0.317
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.143
316129AC1-054 GEN
Solar/Wind Harmer
0.654
3145683EARLEYS
Solar/Wind Harmer
0.171
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.168
3145493TOT1
Solar/Wind Harmer
0.748
3146173TUNIS
Solar/Wind Harmer
0.168
971065AG2-659 GEN
Solar/Wind Harmer
7.153
3145893MURPHYS
Solar/Wind Harmer
0.659
3145893MURPHYS
Solar/Wind Harmer
0.732
3156021HOLLOMANSOL
Solar/Wind Harmer
0.704
316494AC1-189 GEN
Solar/Wind Harmer
0.527
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146293MARTNCO
Solar/Wind Harmer
0.125
3146206CASHIE
Solar/Wind Harmer
0.127
971547AH1-271 GEN
Solar/Wind Harmer
2.711
3145963POPLR C
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.368
315737AD1-076 GEN
Solar/Wind Harmer
1.366
315785AD2-033 C
Solar/Wind Harmer
0.845
970401AG2-262 GEN
Solar/Wind Harmer
0.555
316034AC1-036 C
Solar/Wind Harmer
0.006
971563AH1-280 GEN
Solar/Wind Harmer
0.912
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3145663CRESWEL
Solar/Wind Harmer
0.237
971163AH1-040 GEN
Solar/Wind Harmer
6.763
315693AD1-088 GEN
Solar/Wind Harmer
3.903
970685AG2-442 GEN
Solar/Wind Harmer
6.061
957481AF2-042 GEN
Solar/Wind Harmer
21.462
3130156CHOWAN
Solar/Wind Harmer
0.06
315671AE2-027_GEN
Solar/Wind Helper
0.949
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.588
MECLTFEXP_MEC->PJM
CLTF
0.854
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
4.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.63
LAGNLTFEXP_LAGN->PJM
CLTF
2.181
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.5
TVALTFEXP_TVA->PJM
CLTF
1.078
NYPJM->LTFIMP_NY
CLTF
0.358
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.141

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.38 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:796.66
MW Contribution:
0.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.04 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:855.39
MW Contribution:
0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3151261ROARAP2
50/50
0.32
3144293JTRSVLE
50/50
0.217
970413AG2-270 GEN
50/50
7.462
316011AB1-132 GEN
Solar/Wind Harmer
6.264
316181AB2-040 GEN
Solar/Wind Harmer
0.488
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.288
3145796HORNRTN
Solar/Wind Harmer
0.322
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
315722AD1-056 GEN
Solar/Wind Harmer
8.499
316212AC1-099_GEN
Solar/Wind Harmer
1.032
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.939
3146233WITAKRS
Solar/Wind Harmer
0.127
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.05
3145823KELFORD
Solar/Wind Harmer
0.181
3151361ROSEMG1
50/50
1.16
3151371ROSEMS1
50/50
0.719
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3147043LAWRENC
50/50
3.131
3151281ROARAP4
50/50
0.311
3151591KERR 2
50/50
0.265
3151641KERR 7
50/50
0.265
3144293JTRSVLE
50/50
0.217
3144293JTRSVLE
50/50
0.171
3151531CLOVER1
50/50
1.713
316023GEN1_S
Solar/Wind Harmer
1.159
960081AF2-299 GEN
Solar/Wind Harmer
3.999
3145796HORNRTN
Solar/Wind Harmer
1.062
3145796HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.446
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.744
3145823KELFORD
Solar/Wind Harmer
0.181
316359AB2-059 GEN
Solar/Wind Harmer
0.64
3142053HEARTS
Solar/Wind Harmer
0.317
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.143
316129AC1-054 GEN
Solar/Wind Harmer
0.654
3145683EARLEYS
Solar/Wind Harmer
0.171
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.168
3145493TOT1
Solar/Wind Harmer
0.748
3146173TUNIS
Solar/Wind Harmer
0.168
971065AG2-659 GEN
Solar/Wind Harmer
7.153
3145893MURPHYS
Solar/Wind Harmer
0.659
3145893MURPHYS
Solar/Wind Harmer
0.732
3156021HOLLOMANSOL
Solar/Wind Harmer
0.704
316494AC1-189 GEN
Solar/Wind Harmer
0.527
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146293MARTNCO
Solar/Wind Harmer
0.125
3146206CASHIE
Solar/Wind Harmer
0.127
971547AH1-271 GEN
Solar/Wind Harmer
2.711
3145963POPLR C
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.368
315737AD1-076 GEN
Solar/Wind Harmer
1.366
315785AD2-033 C
Solar/Wind Harmer
0.845
971623AH1-311 GEN
Solar/Wind Harmer
0.36
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
3146073TAR RVR
Solar/Wind Harmer
0.168
3146083TARBORO
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.276
3145893MURPHYS
Solar/Wind Harmer
0.165
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145933PARMELE
Solar/Wind Harmer
0.135
3146206CASHIE
Solar/Wind Harmer
0.127
3145963POPLR C
Solar/Wind Harmer
0.122
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
970257AG2-171 GEN
Solar/Wind Harmer
3.241
971775AH1-396 GEN
Solar/Wind Harmer
0.162
964241AG1-285 GEN
Solar/Wind Harmer
6.48
959311AF2-222 GEN
Solar/Wind Harmer
7.79
316478AD1-087 GEN
Solar/Wind Harmer
0.277
3147133PAMPLIN
Solar/Wind Harmer
0.233
971683AH1-343 GEN
Solar/Wind Harmer
2.412
942461AE2-259 GEN
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
0.06
316222AC1-221 GEN
Solar/Wind Harmer
0.246
316283AC2-100 C
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.043
3151381ROSEMG2
50/50
0.543
3151261ROARAP2
50/50
0.313
3151581KERR 1
50/50
0.094
970535AG2-341 GEN
50/50
2.22
3152661PLYWOOD A
50/50
0.19
3144293JTRSVLE
50/50
0.217
970909AG2-566 GEN
50/50
0.672
316365GEN2_N
Solar/Wind Harmer
1.159
962571AG1-106 GEN
Solar/Wind Harmer
4.914
313506AB2-031 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
0.966
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
4.494
3145783HORNRTN
Solar/Wind Harmer
3.595
3145783HORNRTN
Solar/Wind Harmer
1.123
3145783HORNRTN
Solar/Wind Harmer
0.449
315724AD1-057 GEN
Solar/Wind Harmer
4.741
961601AG1-000A GEN
Solar/Wind Harmer
3.263
316049AB1-081 GEN
Solar/Wind Harmer
1.023
316263AC1-034 GEN
Solar/Wind Harmer
6.835
316140AB2-099
Solar/Wind Harmer
0.06
3145493TOT1
Solar/Wind Harmer
0.39
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
3146173TUNIS
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
1.103
3145893MURPHYS
Solar/Wind Harmer
0.296
316005AA1-067
Solar/Wind Harmer
0.151
3145933PARMELE
Solar/Wind Harmer
0.27
3145933PARMELE
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
5.506
970323AG2-213 GEN
Solar/Wind Harmer
4.321
962561AG1-105 GEN
Solar/Wind Harmer
4.722
964791AG1-342 GEN
Solar/Wind Harmer
1.815
3146843MT LREL
Solar/Wind Harmer
0.094
3146843MT LREL
Solar/Wind Harmer
0.094
958211AF2-115 GEN
Solar/Wind Harmer
1.026
316118AC1-105 GEN
Solar/Wind Harmer
0.219
315614AA2-178 GEN
Solar/Wind Harmer
0.481
970933AG2-581 GEN
Solar/Wind Harmer
6.451
970099AG2-077 GEN
Solar/Wind Harmer
8.585
315742AE1-103 GEN
Solar/Wind Harmer
1.165
3147133PAMPLIN
Solar/Wind Harmer
0.074
3147133PAMPLIN
Solar/Wind Harmer
0.059
970301AG2-198 GEN
Solar/Wind Harmer
2.687
3146376EDENTON
Solar/Wind Harmer
0.268
3146376EDENTON
Solar/Wind Harmer
0.268
3144356SAPONY
Solar/Wind Helper
0.935
316315AB2-025 C
Solar/Wind Helper
0.796
3151281ROARAP4
50/50
0.291
3151601KERR 3
50/50
0.265
3151611KERR 4
50/50
0.265
3151621KERR 5
50/50
0.265
3151631KERR 6
50/50
0.265
3151151S HAMPT1
50/50
0.295
3151541CLOVER2
50/50
1.701
315814AE2-033 C
Solar/Wind Harmer
66.731
315652AC1-086 GEN
Solar/Wind Harmer
37.99
3145796HORNRTN
Solar/Wind Harmer
1.03
3145796HORNRTN
Solar/Wind Harmer
0.129
3137643SOCKMAN
Solar/Wind Harmer
1.19
316426AA2-053 GEN
Solar/Wind Harmer
0.818
3146043SEABORD
Solar/Wind Harmer
0.215
316274AC1-208 GEN
Solar/Wind Harmer
1.093
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316327AA2-057 GEN
Solar/Wind Harmer
0.288
3146033SCOT NK
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
7.902
3145683EARLEYS
Solar/Wind Harmer
0.342
3145683EARLEYS
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
0.171
316463AE2-346 GEN
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.355
3145513AHOSKIE
Solar/Wind Harmer
0.169
3145573BETHELC
Solar/Wind Harmer
0.168
3145573BETHELC
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.445
3145893MURPHYS
Solar/Wind Harmer
0.165
957861AF2-080 GEN
Solar/Wind Harmer
6.72
3145746EVERETS
Solar/Wind Harmer
0.562
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.127
970601AG2-382 GEN
Solar/Wind Harmer
4.745
315732AD1-074 GEN1
Solar/Wind Harmer
0.606
315733AD1-074 GEN2
Solar/Wind Harmer
0.606
3130546PLYMOUTH
Solar/Wind Harmer
0.103
3144303KENBRDG
Solar/Wind Harmer
0.081
946301AF1-294 GEN
Solar/Wind Harmer
1.687
961791AG1-021 GEN
Solar/Wind Harmer
0.821
970683AG2-441 GEN
Solar/Wind Harmer
5.044
970681AG2-440 GEN
Solar/Wind Harmer
3.348
971967AH1-528 GEN
Solar/Wind Harmer
12.902
316486AD2-202 GEN
Solar/Wind Harmer
0.081
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
3130156CHOWAN
Solar/Wind Harmer
0.06
3130156CHOWAN
Solar/Wind Harmer
0.06
315839AE2-212 C
Solar/Wind Helper
0.175
3143316POE
Solar/Wind Helper
0.502
970401AG2-262 GEN
Solar/Wind Harmer
0.555
316034AC1-036 C
Solar/Wind Harmer
0.006
971563AH1-280 GEN
Solar/Wind Harmer
0.912
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3145663CRESWEL
Solar/Wind Harmer
0.237
971163AH1-040 GEN
Solar/Wind Harmer
6.763
315693AD1-088 GEN
Solar/Wind Harmer
3.903
970685AG2-442 GEN
Solar/Wind Harmer
6.061
957481AF2-042 GEN
Solar/Wind Harmer
21.462
3130156CHOWAN
Solar/Wind Harmer
0.06
315671AE2-027_GEN
Solar/Wind Helper
0.949
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.588
MECLTFEXP_MEC->PJM
CLTF
0.854
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
4.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.63
LAGNLTFEXP_LAGN->PJM
CLTF
2.181
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.5
TVALTFEXP_TVA->PJM
CLTF
1.078
NYPJM->LTFIMP_NY
CLTF
0.358
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.141

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.62 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:954.99
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1145.59
MW Contribution:
5.58
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.77
3151601KERR 3
50/50
0.483
3151611KERR 4
50/50
0.483
3151621KERR 5
50/50
0.483
3151631KERR 6
50/50
0.483
946301AF1-294 GEN
Solar/Wind Harmer
13.162
961791AG1-021 GEN
Solar/Wind Harmer
6.421
970683AG2-441 GEN
Solar/Wind Harmer
31.17
970681AG2-440 GEN
Solar/Wind Harmer
20.688
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.59
316486AD2-202 GEN
Solar/Wind Harmer
0.901
316238AB2-078_GEN
Solar/Wind Harmer
1.003
316239AB2-077_GEN
Solar/Wind Harmer
1.003
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.889
946281AF1-292 GEN
Solar/Wind Harmer
0.246
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.982
270455AD2-022 GEN
Solar/Wind Harmer
1.597
270457AD2-023 GEN
Solar/Wind Harmer
0.81
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.91
316327AA2-057 GEN
Solar/Wind Harmer
0.789
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.698
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.806
316258AE1-075 C
Solar/Wind Helper
0.281
316405AF2-144 C
Solar/Wind Helper
0.234
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.158
970413AG2-270 GEN
50/50
29.699
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.217
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.244
971775AH1-396 GEN
Solar/Wind Harmer
3.056
959311AF2-222 GEN
Solar/Wind Harmer
44.468
964241AG1-285 GEN
Solar/Wind Harmer
30.375
316478AD1-087 GEN
Solar/Wind Harmer
3.079
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971683AH1-343 GEN
Solar/Wind Harmer
8.951
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.758
316222AC1-221 GEN
Solar/Wind Harmer
1.411
316283AC2-100 C
Solar/Wind Harmer
1.289
966621AG1-532 GEN
Solar/Wind Harmer
0.223
316181AB2-040 GEN
Solar/Wind Harmer
1.502
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146233WITAKRS
Solar/Wind Harmer
0.158
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.807
315722AD1-056 GEN
Solar/Wind Harmer
2.486
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.429
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.731
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.723
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.158
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.819
3151591KERR 2
50/50
0.483
3151641KERR 7
50/50
0.483
3147043LAWRENC
50/50
1.537
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.421
970685AG2-442 GEN
Solar/Wind Harmer
40.499
316034AC1-036 C
Solar/Wind Harmer
0.777
315785AD2-033 C
Solar/Wind Harmer
9.431
315693AD1-088 GEN
Solar/Wind Harmer
20.662
957481AF2-042 GEN
Solar/Wind Harmer
118.556
316131AB2-060 GEN
Solar/Wind Harmer
3.73
970401AG2-262 GEN
Solar/Wind Harmer
1.864
971065AG2-659 GEN
Solar/Wind Harmer
10.961
316129AC1-054 GEN
Solar/Wind Harmer
1.835
960081AF2-299 GEN
Solar/Wind Harmer
1.234
316087AB2-174 GEN
Solar/Wind Harmer
1.544
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.91
316319Z2-044 C
Solar/Wind Harmer
0.418
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.976
3142053HEARTS
Solar/Wind Harmer
0.085
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
3146776BUCKING
Solar/Wind Helper
0.288
970909AG2-566 GEN
50/50
5.542
3144293JTRSVLE
50/50
1.158
970535AG2-341 GEN
50/50
4.757
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.506
970301AG2-198 GEN
Solar/Wind Harmer
29.19
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.026
970323AG2-213 GEN
Solar/Wind Harmer
21.658
970933AG2-581 GEN
Solar/Wind Harmer
36.199
970099AG2-077 GEN
Solar/Wind Harmer
47.422
313527AB2-043 GEN
Solar/Wind Harmer
5.524
316237AB2-079_GEN
Solar/Wind Harmer
1.003
315687AD1-152 GEN
Solar/Wind Harmer
3.684
962561AG1-105 GEN
Solar/Wind Harmer
16.53
964791AG1-342 GEN
Solar/Wind Harmer
6.099
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.821
316248AF1-058 C
Solar/Wind Harmer
0.74
942751AE2-291 GEN
Solar/Wind Harmer
9.085
313506AB2-031 GEN
Solar/Wind Harmer
0.865
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.216
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316049AB1-081 GEN
Solar/Wind Harmer
0.781
316263AC1-034 GEN
Solar/Wind Harmer
3.402
961601AG1-000A GEN
Solar/Wind Harmer
2.771
315724AD1-057 GEN
Solar/Wind Harmer
1.367
3145796HORNRTN
Solar/Wind Harmer
-0.021
962571AG1-106 GEN
Solar/Wind Harmer
0.984
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.102
3145453TOT5
Solar/Wind Harmer
0.061
3145603CNETO
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Helper
2.883
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.715
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.409
MECLTFEXP_MEC->PJM
CLTF
1.024
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
5.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.972
LAGNLTFEXP_LAGN->PJM
CLTF
2.683
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.382
TVALTFEXP_TVA->PJM
CLTF
1.328
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.324
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.62 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:954.99
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.43 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1145.2
MW Contribution:
5.58
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.77
3151601KERR 3
50/50
0.483
3151611KERR 4
50/50
0.483
3151621KERR 5
50/50
0.483
3151631KERR 6
50/50
0.483
946301AF1-294 GEN
Solar/Wind Harmer
13.162
961791AG1-021 GEN
Solar/Wind Harmer
6.421
970683AG2-441 GEN
Solar/Wind Harmer
31.17
970681AG2-440 GEN
Solar/Wind Harmer
20.688
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.59
316486AD2-202 GEN
Solar/Wind Harmer
0.901
316238AB2-078_GEN
Solar/Wind Harmer
1.003
316239AB2-077_GEN
Solar/Wind Harmer
1.003
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.889
946281AF1-292 GEN
Solar/Wind Harmer
0.246
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.982
270455AD2-022 GEN
Solar/Wind Harmer
1.597
270457AD2-023 GEN
Solar/Wind Harmer
0.81
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.91
316327AA2-057 GEN
Solar/Wind Harmer
0.789
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.698
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.806
316258AE1-075 C
Solar/Wind Helper
0.281
316405AF2-144 C
Solar/Wind Helper
0.234
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.158
970413AG2-270 GEN
50/50
29.699
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.217
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.244
971775AH1-396 GEN
Solar/Wind Harmer
3.056
959311AF2-222 GEN
Solar/Wind Harmer
44.468
964241AG1-285 GEN
Solar/Wind Harmer
30.375
316478AD1-087 GEN
Solar/Wind Harmer
3.079
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971683AH1-343 GEN
Solar/Wind Harmer
8.951
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.758
316222AC1-221 GEN
Solar/Wind Harmer
1.411
316283AC2-100 C
Solar/Wind Harmer
1.289
966621AG1-532 GEN
Solar/Wind Harmer
0.223
316181AB2-040 GEN
Solar/Wind Harmer
1.502
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146233WITAKRS
Solar/Wind Harmer
0.158
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.807
315722AD1-056 GEN
Solar/Wind Harmer
2.486
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.429
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.731
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.723
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.158
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.819
3151591KERR 2
50/50
0.483
3151641KERR 7
50/50
0.483
3147043LAWRENC
50/50
1.537
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.421
970685AG2-442 GEN
Solar/Wind Harmer
40.499
316034AC1-036 C
Solar/Wind Harmer
0.777
315785AD2-033 C
Solar/Wind Harmer
9.431
315693AD1-088 GEN
Solar/Wind Harmer
20.662
957481AF2-042 GEN
Solar/Wind Harmer
118.556
316131AB2-060 GEN
Solar/Wind Harmer
3.73
970401AG2-262 GEN
Solar/Wind Harmer
1.864
971065AG2-659 GEN
Solar/Wind Harmer
10.961
316129AC1-054 GEN
Solar/Wind Harmer
1.835
960081AF2-299 GEN
Solar/Wind Harmer
1.234
316087AB2-174 GEN
Solar/Wind Harmer
1.544
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.91
316319Z2-044 C
Solar/Wind Harmer
0.418
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.976
3142053HEARTS
Solar/Wind Harmer
0.085
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
3146776BUCKING
Solar/Wind Helper
0.288
970909AG2-566 GEN
50/50
5.542
3144293JTRSVLE
50/50
1.158
970535AG2-341 GEN
50/50
4.757
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.506
970301AG2-198 GEN
Solar/Wind Harmer
29.19
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.026
970323AG2-213 GEN
Solar/Wind Harmer
21.658
970933AG2-581 GEN
Solar/Wind Harmer
36.199
970099AG2-077 GEN
Solar/Wind Harmer
47.422
313527AB2-043 GEN
Solar/Wind Harmer
5.524
316237AB2-079_GEN
Solar/Wind Harmer
1.003
315687AD1-152 GEN
Solar/Wind Harmer
3.684
962561AG1-105 GEN
Solar/Wind Harmer
16.53
964791AG1-342 GEN
Solar/Wind Harmer
6.099
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.821
316248AF1-058 C
Solar/Wind Harmer
0.74
942751AE2-291 GEN
Solar/Wind Harmer
9.085
313506AB2-031 GEN
Solar/Wind Harmer
0.865
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.216
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316049AB1-081 GEN
Solar/Wind Harmer
0.781
316263AC1-034 GEN
Solar/Wind Harmer
3.402
961601AG1-000A GEN
Solar/Wind Harmer
2.771
315724AD1-057 GEN
Solar/Wind Harmer
1.367
3145796HORNRTN
Solar/Wind Harmer
-0.021
962571AG1-106 GEN
Solar/Wind Harmer
0.984
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.102
3145453TOT5
Solar/Wind Harmer
0.061
3145603CNETO
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Helper
2.883
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.715
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.409
MECLTFEXP_MEC->PJM
CLTF
1.024
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
5.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.972
LAGNLTFEXP_LAGN->PJM
CLTF
2.683
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.382
TVALTFEXP_TVA->PJM
CLTF
1.328
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.324
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.92 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:950.19
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:163.86 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1120.8
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.212
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.224
971775AH1-396 GEN
Solar/Wind Harmer
3.053
959311AF2-222 GEN
Solar/Wind Harmer
44.406
964241AG1-285 GEN
Solar/Wind Harmer
30.327
316478AD1-087 GEN
Solar/Wind Harmer
3.072
316003AC1-222 GEN
Solar/Wind Harmer
2.214
971683AH1-343 GEN
Solar/Wind Harmer
8.919
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.751
316222AC1-221 GEN
Solar/Wind Harmer
1.398
316283AC2-100 C
Solar/Wind Harmer
1.276
966621AG1-532 GEN
Solar/Wind Harmer
0.223
316181AB2-040 GEN
Solar/Wind Harmer
1.501
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.677
3146233WITAKRS
Solar/Wind Harmer
0.157
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.774
315722AD1-056 GEN
Solar/Wind Harmer
2.466
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.426
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.088
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
315821AE2-092 GEN
Solar/Wind Helper
2.528
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.415
970685AG2-442 GEN
Solar/Wind Harmer
40.45
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.419
315693AD1-088 GEN
Solar/Wind Harmer
20.63
957481AF2-042 GEN
Solar/Wind Harmer
118.335
316131AB2-060 GEN
Solar/Wind Harmer
3.724
970401AG2-262 GEN
Solar/Wind Harmer
1.859
971065AG2-659 GEN
Solar/Wind Harmer
10.934
316129AC1-054 GEN
Solar/Wind Harmer
1.83
960081AF2-299 GEN
Solar/Wind Harmer
1.234
316087AB2-174 GEN
Solar/Wind Harmer
1.543
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316319Z2-044 C
Solar/Wind Harmer
0.414
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.965
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.193
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
3146776BUCKING
Solar/Wind Helper
0.288
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.746
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
29.169
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.019
970323AG2-213 GEN
Solar/Wind Harmer
21.632
970933AG2-581 GEN
Solar/Wind Harmer
36.133
970099AG2-077 GEN
Solar/Wind Harmer
47.334
313527AB2-043 GEN
Solar/Wind Harmer
5.514
316237AB2-079_GEN
Solar/Wind Harmer
1.001
315687AD1-152 GEN
Solar/Wind Harmer
3.673
962561AG1-105 GEN
Solar/Wind Harmer
16.49
964791AG1-342 GEN
Solar/Wind Harmer
6.083
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.816
316248AF1-058 C
Solar/Wind Harmer
0.737
942751AE2-291 GEN
Solar/Wind Harmer
9.05
313506AB2-031 GEN
Solar/Wind Harmer
0.864
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.772
316263AC1-034 GEN
Solar/Wind Harmer
3.363
961601AG1-000A GEN
Solar/Wind Harmer
2.739
315724AD1-057 GEN
Solar/Wind Harmer
1.356
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.982
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
3151541CLOVER2
50/50
6.756
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
946301AF1-294 GEN
Solar/Wind Harmer
13.151
961791AG1-021 GEN
Solar/Wind Harmer
6.415
970683AG2-441 GEN
Solar/Wind Harmer
31.129
970681AG2-440 GEN
Solar/Wind Harmer
20.661
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.459
316486AD2-202 GEN
Solar/Wind Harmer
0.9
316238AB2-078_GEN
Solar/Wind Harmer
1.001
316239AB2-077_GEN
Solar/Wind Harmer
1.001
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.865
946281AF1-292 GEN
Solar/Wind Harmer
0.246
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.98
270455AD2-022 GEN
Solar/Wind Harmer
1.574
270457AD2-023 GEN
Solar/Wind Harmer
0.798
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.906
316210AC1-098 GEN
Solar/Wind Harmer
1.218
316327AA2-057 GEN
Solar/Wind Harmer
0.783
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.683
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.03 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:755.23
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:164.92 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:922.4
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.756
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151281ROARAP4
50/50
0.105
946301AF1-294 GEN
Solar/Wind Harmer
9.014
961791AG1-021 GEN
Solar/Wind Harmer
4.385
970683AG2-441 GEN
Solar/Wind Harmer
23.642
970681AG2-440 GEN
Solar/Wind Harmer
15.692
3144303KENBRDG
Solar/Wind Harmer
0.308
971967AH1-528 GEN
Solar/Wind Harmer
54.886
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970831AG2-522 GEN
Solar/Wind Harmer
7.493
3137643SOCKMAN
Solar/Wind Harmer
0.379
316426AA2-053 GEN
Solar/Wind Harmer
0.29
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.386
316210AC1-098 GEN
Solar/Wind Harmer
0.64
316327AA2-057 GEN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.683
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.746
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.22
3151371ROSEMS1
50/50
0.136
3151381ROSEMG2
50/50
0.103
970301AG2-198 GEN
Solar/Wind Harmer
22.154
3147133PAMPLIN
Solar/Wind Harmer
0.463
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.481
970323AG2-213 GEN
Solar/Wind Harmer
16.429
970933AG2-581 GEN
Solar/Wind Harmer
27.443
970099AG2-077 GEN
Solar/Wind Harmer
35.95
962561AG1-105 GEN
Solar/Wind Harmer
12.524
964791AG1-342 GEN
Solar/Wind Harmer
4.866
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.873
313506AB2-031 GEN
Solar/Wind Harmer
0.294
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.617
3145783HORNRTN
Solar/Wind Harmer
1.294
3145783HORNRTN
Solar/Wind Harmer
0.404
3145783HORNRTN
Solar/Wind Harmer
0.162
316049AB1-081 GEN
Solar/Wind Harmer
0.363
316263AC1-034 GEN
Solar/Wind Harmer
2.427
961601AG1-000A GEN
Solar/Wind Harmer
1.103
315724AD1-057 GEN
Solar/Wind Harmer
1.189
3145796HORNRTN
Solar/Wind Harmer
0.183
962571AG1-106 GEN
Solar/Wind Harmer
0.864
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
3145893MURPHYS
Solar/Wind Harmer
0.383
3145893MURPHYS
Solar/Wind Harmer
0.103
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3151261ROARAP2
50/50
0.116
3151391GASTONA
50/50
0.163
3151411GASTONB
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
1.453
970257AG2-171 GEN
Solar/Wind Harmer
12.322
971775AH1-396 GEN
Solar/Wind Harmer
0.616
959311AF2-222 GEN
Solar/Wind Harmer
33.659
964241AG1-285 GEN
Solar/Wind Harmer
23.033
316478AD1-087 GEN
Solar/Wind Harmer
1.097
971683AH1-343 GEN
Solar/Wind Harmer
6.774
3147043LAWRENC
Solar/Wind Harmer
0.096
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316222AC1-221 GEN
Solar/Wind Harmer
0.508
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
316212AC1-099_GEN
Solar/Wind Harmer
0.357
3146233WITAKRS
Solar/Wind Harmer
0.335
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.044
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.128
961601AG1-000A GEN
Solar/Wind Harmer
4.411
315722AD1-056 GEN
Solar/Wind Harmer
2.132
3145796HORNRTN
Solar/Wind Harmer
0.244
3145796HORNRTN
Solar/Wind Harmer
0.061
316011AB1-132 GEN
Solar/Wind Harmer
1.102
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3145823KELFORD
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.096
3145893MURPHYS
Solar/Wind Harmer
0.057
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
315821AE2-092 GEN
Solar/Wind Helper
2.528
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3151281ROARAP4
50/50
0.112
971629AH1-314 GEN
50/50
5.749
3151561HALLBR1
50/50
0.158
3151391GASTONA
50/50
0.163
3151411GASTONB
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.872
970685AG2-442 GEN
Solar/Wind Harmer
30.722
316034AC1-036 C
Solar/Wind Harmer
0.025
315785AD2-033 C
Solar/Wind Harmer
2.997
315693AD1-088 GEN
Solar/Wind Harmer
17.627
957481AF2-042 GEN
Solar/Wind Harmer
89.874
316131AB2-060 GEN
Solar/Wind Harmer
0.958
970401AG2-262 GEN
Solar/Wind Harmer
1.487
971065AG2-659 GEN
Solar/Wind Harmer
8.305
316129AC1-054 GEN
Solar/Wind Harmer
0.696
960081AF2-299 GEN
Solar/Wind Harmer
0.937
3145783HORNRTN
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.162
3146233WITAKRS
Solar/Wind Harmer
0.266
3147123OTTER R
Solar/Wind Harmer
0.04
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
316359AB2-059 GEN
Solar/Wind Harmer
0.227
3142053HEARTS
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.229
3145893MURPHYS
Solar/Wind Harmer
0.254
3146776BUCKING
Solar/Wind Helper
0.288
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:909.01
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:157.84 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1079.63
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.756
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
946301AF1-294 GEN
Solar/Wind Harmer
13.151
961791AG1-021 GEN
Solar/Wind Harmer
6.415
970683AG2-441 GEN
Solar/Wind Harmer
31.129
970681AG2-440 GEN
Solar/Wind Harmer
20.661
3144303KENBRDG
Solar/Wind Harmer
-0.035
316486AD2-202 GEN
Solar/Wind Harmer
0.9
316238AB2-078_GEN
Solar/Wind Harmer
1.001
316239AB2-077_GEN
Solar/Wind Harmer
1.001
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.865
946281AF1-292 GEN
Solar/Wind Harmer
0.246
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.98
270455AD2-022 GEN
Solar/Wind Harmer
1.574
270457AD2-023 GEN
Solar/Wind Harmer
0.798
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.906
316210AC1-098 GEN
Solar/Wind Harmer
1.218
316327AA2-057 GEN
Solar/Wind Harmer
0.783
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.683
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.212
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.224
971775AH1-396 GEN
Solar/Wind Harmer
3.053
959311AF2-222 GEN
Solar/Wind Harmer
44.406
964241AG1-285 GEN
Solar/Wind Harmer
30.327
316478AD1-087 GEN
Solar/Wind Harmer
3.072
316003AC1-222 GEN
Solar/Wind Harmer
2.214
971683AH1-343 GEN
Solar/Wind Harmer
8.919
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.751
316222AC1-221 GEN
Solar/Wind Harmer
1.398
316283AC2-100 C
Solar/Wind Harmer
1.276
966621AG1-532 GEN
Solar/Wind Harmer
0.223
316181AB2-040 GEN
Solar/Wind Harmer
1.501
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.677
3146233WITAKRS
Solar/Wind Harmer
0.157
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.774
315722AD1-056 GEN
Solar/Wind Harmer
2.466
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.426
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.088
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
315821AE2-092 GEN
Solar/Wind Helper
2.528
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.415
970685AG2-442 GEN
Solar/Wind Harmer
40.45
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.419
315693AD1-088 GEN
Solar/Wind Harmer
20.63
957481AF2-042 GEN
Solar/Wind Harmer
118.335
316131AB2-060 GEN
Solar/Wind Harmer
3.724
970401AG2-262 GEN
Solar/Wind Harmer
1.859
971065AG2-659 GEN
Solar/Wind Harmer
10.934
316129AC1-054 GEN
Solar/Wind Harmer
1.83
960081AF2-299 GEN
Solar/Wind Harmer
1.234
316087AB2-174 GEN
Solar/Wind Harmer
1.543
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316319Z2-044 C
Solar/Wind Harmer
0.414
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.965
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.193
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
3146776BUCKING
Solar/Wind Helper
0.288
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.746
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
29.169
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.019
970323AG2-213 GEN
Solar/Wind Harmer
21.632
970099AG2-077 GEN
Solar/Wind Harmer
47.334
313527AB2-043 GEN
Solar/Wind Harmer
5.514
316237AB2-079_GEN
Solar/Wind Harmer
1.001
315687AD1-152 GEN
Solar/Wind Harmer
3.673
962561AG1-105 GEN
Solar/Wind Harmer
16.49
964791AG1-342 GEN
Solar/Wind Harmer
6.083
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.816
316248AF1-058 C
Solar/Wind Harmer
0.737
942751AE2-291 GEN
Solar/Wind Harmer
9.05
313506AB2-031 GEN
Solar/Wind Harmer
0.864
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.772
316263AC1-034 GEN
Solar/Wind Harmer
3.363
961601AG1-000A GEN
Solar/Wind Harmer
2.739
315724AD1-057 GEN
Solar/Wind Harmer
1.356
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.982
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:909.01
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:157.84 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1079.63
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.415
970685AG2-442 GEN
Solar/Wind Harmer
40.45
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.419
315693AD1-088 GEN
Solar/Wind Harmer
20.63
957481AF2-042 GEN
Solar/Wind Harmer
118.335
316131AB2-060 GEN
Solar/Wind Harmer
3.724
970401AG2-262 GEN
Solar/Wind Harmer
1.859
971065AG2-659 GEN
Solar/Wind Harmer
10.934
316129AC1-054 GEN
Solar/Wind Harmer
1.83
960081AF2-299 GEN
Solar/Wind Harmer
1.234
316087AB2-174 GEN
Solar/Wind Harmer
1.543
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316319Z2-044 C
Solar/Wind Harmer
0.414
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.965
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.193
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
3146776BUCKING
Solar/Wind Helper
0.288
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.212
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.224
971775AH1-396 GEN
Solar/Wind Harmer
3.053
959311AF2-222 GEN
Solar/Wind Harmer
44.406
964241AG1-285 GEN
Solar/Wind Harmer
30.327
316478AD1-087 GEN
Solar/Wind Harmer
3.072
316003AC1-222 GEN
Solar/Wind Harmer
2.214
971683AH1-343 GEN
Solar/Wind Harmer
8.919
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.751
316222AC1-221 GEN
Solar/Wind Harmer
1.398
316283AC2-100 C
Solar/Wind Harmer
1.276
966621AG1-532 GEN
Solar/Wind Harmer
0.223
316181AB2-040 GEN
Solar/Wind Harmer
1.501
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.677
3146233WITAKRS
Solar/Wind Harmer
0.157
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.774
315722AD1-056 GEN
Solar/Wind Harmer
2.466
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.426
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.088
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
315821AE2-092 GEN
Solar/Wind Helper
2.528
3151541CLOVER2
50/50
6.756
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
946301AF1-294 GEN
Solar/Wind Harmer
13.151
961791AG1-021 GEN
Solar/Wind Harmer
6.415
970683AG2-441 GEN
Solar/Wind Harmer
31.129
970681AG2-440 GEN
Solar/Wind Harmer
20.661
3144303KENBRDG
Solar/Wind Harmer
-0.035
316486AD2-202 GEN
Solar/Wind Harmer
0.9
316238AB2-078_GEN
Solar/Wind Harmer
1.001
316239AB2-077_GEN
Solar/Wind Harmer
1.001
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.865
946281AF1-292 GEN
Solar/Wind Harmer
0.246
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.98
270455AD2-022 GEN
Solar/Wind Harmer
1.574
270457AD2-023 GEN
Solar/Wind Harmer
0.798
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.906
316210AC1-098 GEN
Solar/Wind Harmer
1.218
316327AA2-057 GEN
Solar/Wind Harmer
0.783
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.683
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.746
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
29.169
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.019
970323AG2-213 GEN
Solar/Wind Harmer
21.632
970099AG2-077 GEN
Solar/Wind Harmer
47.334
313527AB2-043 GEN
Solar/Wind Harmer
5.514
316237AB2-079_GEN
Solar/Wind Harmer
1.001
315687AD1-152 GEN
Solar/Wind Harmer
3.673
962561AG1-105 GEN
Solar/Wind Harmer
16.49
964791AG1-342 GEN
Solar/Wind Harmer
6.083
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.816
316248AF1-058 C
Solar/Wind Harmer
0.737
942751AE2-291 GEN
Solar/Wind Harmer
9.05
313506AB2-031 GEN
Solar/Wind Harmer
0.864
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.772
316263AC1-034 GEN
Solar/Wind Harmer
3.363
961601AG1-000A GEN
Solar/Wind Harmer
2.739
315724AD1-057 GEN
Solar/Wind Harmer
1.356
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.982
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.38 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:740.38
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:162.31 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:907.81
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3151261ROARAP2
50/50
0.116
3151391GASTONA
50/50
0.163
3151411GASTONB
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
1.453
970257AG2-171 GEN
Solar/Wind Harmer
12.322
971775AH1-396 GEN
Solar/Wind Harmer
0.616
959311AF2-222 GEN
Solar/Wind Harmer
33.659
964241AG1-285 GEN
Solar/Wind Harmer
23.033
316478AD1-087 GEN
Solar/Wind Harmer
1.097
971683AH1-343 GEN
Solar/Wind Harmer
6.774
3147043LAWRENC
Solar/Wind Harmer
0.096
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316222AC1-221 GEN
Solar/Wind Harmer
0.508
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
316212AC1-099_GEN
Solar/Wind Harmer
0.357
3146233WITAKRS
Solar/Wind Harmer
0.335
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.044
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.128
961601AG1-000A GEN
Solar/Wind Harmer
4.411
315722AD1-056 GEN
Solar/Wind Harmer
2.132
3145796HORNRTN
Solar/Wind Harmer
0.244
3145796HORNRTN
Solar/Wind Harmer
0.061
316011AB1-132 GEN
Solar/Wind Harmer
1.102
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3145823KELFORD
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3151541CLOVER2
50/50
6.756
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151281ROARAP4
50/50
0.105
946301AF1-294 GEN
Solar/Wind Harmer
9.014
961791AG1-021 GEN
Solar/Wind Harmer
4.385
970683AG2-441 GEN
Solar/Wind Harmer
23.642
970681AG2-440 GEN
Solar/Wind Harmer
15.692
3144303KENBRDG
Solar/Wind Harmer
0.308
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970831AG2-522 GEN
Solar/Wind Harmer
7.493
3137643SOCKMAN
Solar/Wind Harmer
0.379
316426AA2-053 GEN
Solar/Wind Harmer
0.29
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.386
316210AC1-098 GEN
Solar/Wind Harmer
0.64
316327AA2-057 GEN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.683
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.746
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.22
3151371ROSEMS1
50/50
0.136
3151381ROSEMG2
50/50
0.103
970301AG2-198 GEN
Solar/Wind Harmer
22.154
3147133PAMPLIN
Solar/Wind Harmer
0.463
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.481
970323AG2-213 GEN
Solar/Wind Harmer
16.429
970099AG2-077 GEN
Solar/Wind Harmer
35.95
962561AG1-105 GEN
Solar/Wind Harmer
12.524
964791AG1-342 GEN
Solar/Wind Harmer
4.866
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.873
313506AB2-031 GEN
Solar/Wind Harmer
0.294
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.617
3145783HORNRTN
Solar/Wind Harmer
1.294
3145783HORNRTN
Solar/Wind Harmer
0.404
3145783HORNRTN
Solar/Wind Harmer
0.162
316049AB1-081 GEN
Solar/Wind Harmer
0.363
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.096
3145893MURPHYS
Solar/Wind Harmer
0.057
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
315821AE2-092 GEN
Solar/Wind Helper
2.528
316263AC1-034 GEN
Solar/Wind Harmer
2.427
961601AG1-000A GEN
Solar/Wind Harmer
1.103
315724AD1-057 GEN
Solar/Wind Harmer
1.189
3145796HORNRTN
Solar/Wind Harmer
0.183
962571AG1-106 GEN
Solar/Wind Harmer
0.864
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
3145893MURPHYS
Solar/Wind Harmer
0.383
3145893MURPHYS
Solar/Wind Harmer
0.103
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3151281ROARAP4
50/50
0.112
971629AH1-314 GEN
50/50
5.749
3151561HALLBR1
50/50
0.158
3151391GASTONA
50/50
0.163
3151411GASTONB
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.872
970685AG2-442 GEN
Solar/Wind Harmer
30.722
316034AC1-036 C
Solar/Wind Harmer
0.025
315785AD2-033 C
Solar/Wind Harmer
2.997
315693AD1-088 GEN
Solar/Wind Harmer
17.627
957481AF2-042 GEN
Solar/Wind Harmer
89.874
316131AB2-060 GEN
Solar/Wind Harmer
0.958
970401AG2-262 GEN
Solar/Wind Harmer
1.487
971065AG2-659 GEN
Solar/Wind Harmer
8.305
316129AC1-054 GEN
Solar/Wind Harmer
0.696
960081AF2-299 GEN
Solar/Wind Harmer
0.937
3145783HORNRTN
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.162
3146233WITAKRS
Solar/Wind Harmer
0.266
3147123OTTER R
Solar/Wind Harmer
0.04
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
316359AB2-059 GEN
Solar/Wind Harmer
0.227
3142053HEARTS
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.229
3145893MURPHYS
Solar/Wind Harmer
0.254
3146776BUCKING
Solar/Wind Helper
0.288
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-5: 556X2_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-5: 556X2_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.38 %
Rating:1050.6 MVA
Rating Type:C
MVA to Mitigate:1422.29
MW Contribution:
4.44
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-5: 556X2_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.68 %
Rating:1050.6 MVA
Rating Type:C
MVA to Mitigate:1204.79
MW Contribution:
4.46
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
35.916
3144293JTRSVLE
50/50
0.894
970909AG2-566 GEN
50/50
4.441
3144293JTRSVLE
50/50
0.894
970535AG2-341 GEN
50/50
5.689
3151581KERR 1
50/50
0.207
3152661PLYWOOD A
50/50
0.594
3151541CLOVER2
50/50
8.187
3151601KERR 3
50/50
0.581
3151611KERR 4
50/50
0.581
3151621KERR 5
50/50
0.581
3151631KERR 6
50/50
0.581
972205AH1-687 GEN
50/50
5.608
970683AG2-441 GEN
Solar/Wind Harmer
37.949
970681AG2-440 GEN
Solar/Wind Harmer
25.187
316486AD2-202 GEN
Solar/Wind Harmer
1.09
3144303KENBRDG
Solar/Wind Harmer
-0.032
316238AB2-078_GEN
Solar/Wind Harmer
1.194
316239AB2-077_GEN
Solar/Wind Harmer
1.194
946301AF1-294 GEN
Solar/Wind Harmer
10.157
961791AG1-021 GEN
Solar/Wind Harmer
4.955
3147173SINAI
Solar/Wind Harmer
-0.029
3147243WELCO
Solar/Wind Harmer
-0.018
971845AH1-439 GEN
Solar/Wind Harmer
14.44
316322AB2-045
Solar/Wind Harmer
0.883
970831AG2-522 GEN
Solar/Wind Harmer
10.919
946281AF1-292 GEN
Solar/Wind Harmer
0.186
3137643SOCKMAN
Solar/Wind Harmer
-0.032
270455AD2-022 GEN
Solar/Wind Harmer
1.341
270457AD2-023 GEN
Solar/Wind Harmer
0.68
316426AA2-053 GEN
Solar/Wind Harmer
0.697
3147133PAMPLIN
Solar/Wind Harmer
-0.048
3147133PAMPLIN
Solar/Wind Harmer
-0.038
970301AG2-198 GEN
Solar/Wind Harmer
23.39
970099AG2-077 GEN
Solar/Wind Harmer
54.045
313527AB2-043 GEN
Solar/Wind Harmer
6.575
970323AG2-213 GEN
Solar/Wind Harmer
20.016
316237AB2-079_GEN
Solar/Wind Harmer
1.194
958211AF2-115 GEN
Solar/Wind Harmer
6.193
315687AD1-152 GEN
Solar/Wind Harmer
4.374
962561AG1-105 GEN
Solar/Wind Harmer
19.525
964791AG1-342 GEN
Solar/Wind Harmer
7.192
3146843MT LREL
Solar/Wind Harmer
-0.034
3146843MT LREL
Solar/Wind Harmer
-0.034
316118AC1-105 GEN
Solar/Wind Harmer
2.139
316248AF1-058 C
Solar/Wind Harmer
0.865
3146776BUCKING
Solar/Wind Harmer
-0.105
3146776BUCKING
Solar/Wind Harmer
-0.009
942751AE2-291 GEN
Solar/Wind Harmer
11.08
313506AB2-031 GEN
Solar/Wind Harmer
0.658
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
942671AE2-283 GEN
Solar/Wind Harmer
2.69
3151921BEARGRDN G2
50/50
1.148
959311AF2-222 GEN
Solar/Wind Harmer
55.336
964241AG1-285 GEN
Solar/Wind Harmer
40.056
3147133PAMPLIN
Solar/Wind Harmer
-0.15
316478AD1-087 GEN
Solar/Wind Harmer
3.722
942461AE2-259 GEN
Solar/Wind Harmer
6.2
970257AG2-171 GEN
Solar/Wind Harmer
15.012
971775AH1-396 GEN
Solar/Wind Harmer
2.824
3146926FARMVIL
Solar/Wind Harmer
-0.022
316003AC1-222 GEN
Solar/Wind Harmer
2.609
3145783HORNRTN
Solar/Wind Harmer
0.907
3145783HORNRTN
Solar/Wind Harmer
0.726
3145783HORNRTN
Solar/Wind Harmer
0.227
3145783HORNRTN
Solar/Wind Harmer
0.091
316294AC1-161 GEN
Solar/Wind Helper
2.202
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.578
316123AC1-075 GEN
Solar/Wind Harmer
2.117
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
6.245
316222AC1-221 GEN
Solar/Wind Harmer
1.375
316283AC2-100 C
Solar/Wind Harmer
1.245
970221AG2-151 GEN
Solar/Wind Harmer
7.732
270494AE1-108_GEN
Solar/Wind Harmer
2.638
315821AE2-092 GEN
Solar/Wind Harmer
1.834
966621AG1-532 GEN
Solar/Wind Harmer
0.168
316181AB2-040 GEN
Solar/Wind Harmer
1.144
316217AC1-145 GEN
Solar/Wind Harmer
1.317
316197AC1-042 GEN
Solar/Wind Harmer
0.999
3147312GRETNA
Solar/Wind Harmer
-0.002
316190AA2-174 GEN
Solar/Wind Harmer
0.085
3151531CLOVER1
50/50
8.247
3144293JTRSVLE
50/50
0.894
3144293JTRSVLE
50/50
0.706
3151591KERR 2
50/50
0.581
3151641KERR 7
50/50
0.581
3147043LAWRENC
50/50
1.545
3151931BEARGRDN S1
50/50
1.483
3151911BEARGRDN G1
50/50
1.148
315693AD1-088 GEN
Solar/Wind Harmer
30.331
316034AC1-036 C
Solar/Wind Harmer
0.975
970685AG2-442 GEN
Solar/Wind Harmer
45.649
957481AF2-042 GEN
Solar/Wind Harmer
135.112
316131AB2-060 GEN
Solar/Wind Harmer
4.353
315785AD2-033 C
Solar/Wind Harmer
9.076
971563AH1-280 GEN
Solar/Wind Harmer
4.955
3146926FARMVIL
Solar/Wind Harmer
-0.022
970401AG2-262 GEN
Solar/Wind Harmer
2.198
3146776BUCKING
Solar/Wind Harmer
-0.01
971065AG2-659 GEN
Solar/Wind Harmer
12.517
316129AC1-054 GEN
Solar/Wind Harmer
2.067
971377AH1-170 GEN
Solar/Wind Harmer
1.546
3147623JAMES R
Solar/Wind Harmer
0.191
970937AG2-583 GEN
Solar/Wind Harmer
7.416
3147123OTTER R
Solar/Wind Harmer
-0.006
960081AF2-299 GEN
Solar/Wind Harmer
0.932
316087AB2-174 GEN
Solar/Wind Harmer
1.173
3147312GRETNA
Solar/Wind Harmer
-0.006
3146802CHATHAM
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
3.046
3145783HORNRTN
Solar/Wind Harmer
-0.008
315773AC2-141 GEN
Solar/Wind Helper
2.592
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.361
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.904
MECLTFEXP_MEC->PJM
CLTF
0.81
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
2.782
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.844
LAGNLTFEXP_LAGN->PJM
CLTF
1.679
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.694
TVALTFEXP_TVA->PJM
CLTF
0.849
NYPJM->LTFIMP_NY
CLTF
0.297
LGEELTFEXP_LGEE->PJM
CLTF
0.297
WECLTFEXP_WEC->PJM
CLTF
0.15

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: 556X1_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: 556X1_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.91 %
Rating:1053.0 MVA
Rating Type:C
MVA to Mitigate:1420.61
MW Contribution:
4.44
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: 556X1_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.29 %
Rating:1053.0 MVA
Rating Type:C
MVA to Mitigate:1203.45
MW Contribution:
4.45
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
8.177
3151601KERR 3
50/50
0.58
3151611KERR 4
50/50
0.58
3151621KERR 5
50/50
0.58
3151631KERR 6
50/50
0.58
972205AH1-687 GEN
50/50
5.601
970683AG2-441 GEN
Solar/Wind Harmer
37.904
970681AG2-440 GEN
Solar/Wind Harmer
25.158
316486AD2-202 GEN
Solar/Wind Harmer
1.089
3144303KENBRDG
Solar/Wind Harmer
-0.032
316238AB2-078_GEN
Solar/Wind Harmer
1.192
316239AB2-077_GEN
Solar/Wind Harmer
1.192
946301AF1-294 GEN
Solar/Wind Harmer
10.145
961791AG1-021 GEN
Solar/Wind Harmer
4.949
3147173SINAI
Solar/Wind Harmer
-0.029
3147243WELCO
Solar/Wind Harmer
-0.018
971845AH1-439 GEN
Solar/Wind Harmer
14.423
316322AB2-045
Solar/Wind Harmer
0.882
970909AG2-566 GEN
50/50
4.436
3144293JTRSVLE
50/50
0.893
970535AG2-341 GEN
50/50
5.682
3151581KERR 1
50/50
0.207
3152661PLYWOOD A
50/50
0.594
3147133PAMPLIN
Solar/Wind Harmer
-0.048
3147133PAMPLIN
Solar/Wind Harmer
-0.038
970301AG2-198 GEN
Solar/Wind Harmer
23.362
970099AG2-077 GEN
Solar/Wind Harmer
53.981
313527AB2-043 GEN
Solar/Wind Harmer
6.568
970323AG2-213 GEN
Solar/Wind Harmer
19.992
316237AB2-079_GEN
Solar/Wind Harmer
1.192
958211AF2-115 GEN
Solar/Wind Harmer
6.186
315687AD1-152 GEN
Solar/Wind Harmer
4.368
962561AG1-105 GEN
Solar/Wind Harmer
19.502
964791AG1-342 GEN
Solar/Wind Harmer
7.184
3146843MT LREL
Solar/Wind Harmer
-0.033
3146843MT LREL
Solar/Wind Harmer
-0.033
316118AC1-105 GEN
Solar/Wind Harmer
2.136
316248AF1-058 C
Solar/Wind Harmer
0.864
3146776BUCKING
Solar/Wind Harmer
-0.105
3146776BUCKING
Solar/Wind Harmer
-0.009
970413AG2-270 GEN
50/50
35.874
3144293JTRSVLE
50/50
0.893
3151921BEARGRDN G2
50/50
1.146
959311AF2-222 GEN
Solar/Wind Harmer
55.27
964241AG1-285 GEN
Solar/Wind Harmer
40.008
3147133PAMPLIN
Solar/Wind Harmer
-0.15
316478AD1-087 GEN
Solar/Wind Harmer
3.717
942461AE2-259 GEN
Solar/Wind Harmer
6.193
970257AG2-171 GEN
Solar/Wind Harmer
14.994
971775AH1-396 GEN
Solar/Wind Harmer
2.821
3146926FARMVIL
Solar/Wind Harmer
-0.022
316003AC1-222 GEN
Solar/Wind Harmer
2.606
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.565
316123AC1-075 GEN
Solar/Wind Harmer
2.114
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
6.237
316222AC1-221 GEN
Solar/Wind Harmer
1.374
316283AC2-100 C
Solar/Wind Harmer
1.244
970221AG2-151 GEN
Solar/Wind Harmer
7.723
270494AE1-108_GEN
Solar/Wind Harmer
2.635
315821AE2-092 GEN
Solar/Wind Harmer
1.831
942751AE2-291 GEN
Solar/Wind Harmer
11.067
313506AB2-031 GEN
Solar/Wind Harmer
0.658
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.067
942671AE2-283 GEN
Solar/Wind Harmer
2.687
3145783HORNRTN
Solar/Wind Harmer
0.906
3145783HORNRTN
Solar/Wind Harmer
0.725
3145783HORNRTN
Solar/Wind Harmer
0.227
3145783HORNRTN
Solar/Wind Harmer
0.091
316294AC1-161 GEN
Solar/Wind Helper
2.199
3151531CLOVER1
50/50
8.237
3144293JTRSVLE
50/50
0.893
3144293JTRSVLE
50/50
0.705
3151591KERR 2
50/50
0.58
3151641KERR 7
50/50
0.58
3147043LAWRENC
50/50
1.543
3151931BEARGRDN S1
50/50
1.481
3151911BEARGRDN G1
50/50
1.146
315693AD1-088 GEN
Solar/Wind Harmer
30.295
316034AC1-036 C
Solar/Wind Harmer
0.974
970685AG2-442 GEN
Solar/Wind Harmer
45.595
957481AF2-042 GEN
Solar/Wind Harmer
134.952
316131AB2-060 GEN
Solar/Wind Harmer
4.348
315785AD2-033 C
Solar/Wind Harmer
9.066
971563AH1-280 GEN
Solar/Wind Harmer
4.949
3146926FARMVIL
Solar/Wind Harmer
-0.022
970401AG2-262 GEN
Solar/Wind Harmer
2.195
3146776BUCKING
Solar/Wind Harmer
-0.01
971065AG2-659 GEN
Solar/Wind Harmer
12.502
316129AC1-054 GEN
Solar/Wind Harmer
2.064
970831AG2-522 GEN
Solar/Wind Harmer
10.906
946281AF1-292 GEN
Solar/Wind Harmer
0.185
3137643SOCKMAN
Solar/Wind Harmer
-0.032
270455AD2-022 GEN
Solar/Wind Harmer
1.34
270457AD2-023 GEN
Solar/Wind Harmer
0.679
316426AA2-053 GEN
Solar/Wind Harmer
0.696
966621AG1-532 GEN
Solar/Wind Harmer
0.168
316181AB2-040 GEN
Solar/Wind Harmer
1.142
316217AC1-145 GEN
Solar/Wind Harmer
1.316
316197AC1-042 GEN
Solar/Wind Harmer
0.997
3147312GRETNA
Solar/Wind Harmer
-0.002
316190AA2-174 GEN
Solar/Wind Harmer
0.085
971377AH1-170 GEN
Solar/Wind Harmer
1.545
3147623JAMES R
Solar/Wind Harmer
0.191
970937AG2-583 GEN
Solar/Wind Harmer
7.407
3147123OTTER R
Solar/Wind Harmer
-0.006
960081AF2-299 GEN
Solar/Wind Harmer
0.931
316087AB2-174 GEN
Solar/Wind Harmer
1.171
3147312GRETNA
Solar/Wind Harmer
-0.006
3146802CHATHAM
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
3.042
3145783HORNRTN
Solar/Wind Harmer
-0.008
315773AC2-141 GEN
Solar/Wind Helper
2.589
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.355
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.901
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
2.778
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.834
LAGNLTFEXP_LAGN->PJM
CLTF
1.677
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.687
TVALTFEXP_TVA->PJM
CLTF
0.848
NYPJM->LTFIMP_NY
CLTF
0.296
LGEELTFEXP_LGEE->PJM
CLTF
0.296
WECLTFEXP_WEC->PJM
CLTF
0.15

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.74 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:751.6
MW Contribution:
2.34
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.414
3151911BEARGRDN G1
50/50
4.191
3144293JTRSVLE
50/50
0.5
3144293JTRSVLE
50/50
0.394
970119AG2-088 GEN
50/50
14.635
3151531CLOVER1
50/50
2.268
3151591KERR 2
50/50
0.203
3151641KERR 7
50/50
0.203
3147043LAWRENC
50/50
0.857
3151051BRUNSWICKS1
50/50
2.06
3151021BRUNSWICKG1
50/50
0.993
971451AH1-221 GEN
50/50
3.014
315243AE2-183_GT3
50/50
1.235
3151281ROARAP4
50/50
0.085
3150851SPRUNCC
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
971377AH1-170 GEN
Solar/Wind Harmer
4.283
3147623JAMES R
Solar/Wind Harmer
0.93
970937AG2-583 GEN
Solar/Wind Harmer
22.933
3146776BUCKING
Solar/Wind Harmer
0.144
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
4.379
971563AH1-280 GEN
Solar/Wind Harmer
2.104
970685AG2-442 GEN
Solar/Wind Harmer
12.003
315785AD2-033 C
Solar/Wind Harmer
1.25
316034AC1-036 C
Solar/Wind Harmer
0.009
315693AD1-088 GEN
Solar/Wind Harmer
6.214
316131AB2-060 GEN
Solar/Wind Harmer
0.385
3143226MDLTHAN
Solar/Wind Harmer
0.11
957481AF2-042 GEN
Solar/Wind Harmer
28.268
970401AG2-262 GEN
Solar/Wind Harmer
0.589
971065AG2-659 GEN
Solar/Wind Harmer
3.89
3143526WINTERP
Solar/Wind Harmer
0.473
316129AC1-054 GEN
Solar/Wind Harmer
0.334
960081AF2-299 GEN
Solar/Wind Harmer
0.725
941031AE2-094 GEN
Solar/Wind Harmer
13.584
970919AG2-571 GEN
Solar/Wind Harmer
2.582
970087AG2-069 GEN
Solar/Wind Harmer
5.736
3145783HORNRTN
Solar/Wind Harmer
0.07
940641AE2-051 GEN
Solar/Wind Harmer
5.555
315607AA1-063A GEN
Solar/Wind Harmer
0.139
316023GEN1_S
Solar/Wind Harmer
0.149
939411AE1-173 GEN
Solar/Wind Harmer
28.41
3146263WOODLND
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.287
3145796HORNRTN
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
0.063
3151921BEARGRDN G2
50/50
4.191
3144293JTRSVLE
50/50
0.5
970413AG2-270 GEN
50/50
9.876
3151031BRUNSWICKG2
50/50
0.993
3151261ROARAP2
50/50
0.088
3150861SPRUNCD
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
972003AH1-546 GEN
Solar/Wind Harmer
15.285
970221AG2-151 GEN
Solar/Wind Harmer
21.415
3146776BUCKING
Solar/Wind Harmer
0.13
270494AE1-108_GEN
Solar/Wind Harmer
3.742
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
3.722
942461AE2-259 GEN
Solar/Wind Harmer
0
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.598
970257AG2-171 GEN
Solar/Wind Harmer
5.176
971775AH1-396 GEN
Solar/Wind Harmer
0.259
959311AF2-222 GEN
Solar/Wind Harmer
12.78
964241AG1-285 GEN
Solar/Wind Harmer
8.638
958131AF2-107 GEN
Solar/Wind Harmer
3.491
316478AD1-087 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.054
971683AH1-343 GEN
Solar/Wind Harmer
2.762
944011AF1-069 GEN
Solar/Wind Harmer
4.438
316181AB2-040 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.456
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.065
316011AB1-132 GEN
Solar/Wind Harmer
1.175
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.064
316212AC1-099_GEN
Solar/Wind Harmer
0.328
3146173TUNIS
Solar/Wind Harmer
0.063
316123AC1-075 GEN
Solar/Wind Harmer
0.084
3145823KELFORD
Solar/Wind Harmer
0.063
315722AD1-056 GEN
Solar/Wind Harmer
2.107
3145273HOLLAND
Solar/Wind Harmer
0.046
316222AC1-221 GEN
Solar/Wind Harmer
0.25
3146233WITAKRS
Solar/Wind Harmer
0.304
3146233WITAKRS
Solar/Wind Harmer
0.041
3138543CONSLDL
Solar/Wind Harmer
0.04
316283AC2-100 C
Solar/Wind Harmer
0.118
3146206CASHIE
Solar/Wind Harmer
0.06
315735AD1-075 GEN1
Solar/Wind Harmer
0.169
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.059
315813AE1-149 C
Solar/Wind Harmer
3.146
970657AG2-426 GEN
Solar/Wind Harmer
1.323
971623AH1-311 GEN
Solar/Wind Harmer
0.118
3146376EDENTON
Solar/Wind Harmer
0.059
3145963POPLR C
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
4.163
3145823KELFORD
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.062
3156021HOLLOMANSOL
Solar/Wind Harmer
0.273
3146233WITAKRS
Solar/Wind Harmer
0.241
3146206CASHIE
Solar/Wind Harmer
0.06
971547AH1-271 GEN
Solar/Wind Harmer
1.28
315737AD1-076 GEN
Solar/Wind Harmer
0.763
315816AE2-034 GEN
Solar/Wind Harmer
0.253
3145663CRESWEL
Solar/Wind Harmer
0.166
971163AH1-040 GEN
Solar/Wind Harmer
4.737
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.047
316381AD1-082 GEN
Solar/Wind Harmer
0.06
316359AB2-059 GEN
Solar/Wind Harmer
0.21
3142053HEARTS
Solar/Wind Harmer
0.104
3130156CHOWAN
Solar/Wind Harmer
0.059
316093AE2-104_GEN
Solar/Wind Harmer
0.99
3145963POPLR C
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.19
3146516WINFALL
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.259
319010AE1-072 C
Solar/Wind Harmer
0.29
3146293MARTNCO
Solar/Wind Harmer
0.054
3146456SLIGO L269
Solar/Wind Harmer
0.058
316494AC1-189 GEN
Solar/Wind Harmer
0.196
944591AF1-124 GEN
Solar/Wind Harmer
13.109
3142543TWELFTH
Solar/Wind Harmer
0.006
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.01
3150981CHESPKA
Adder
0.721
316072AD1-144
Solar/Wind Harmer
0.02
315671AE2-027_GEN
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.073
3145336SMITFLD
Solar/Wind Harmer
0.226
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.844
3147666LOUISA
Solar/Wind Helper
0.484
316321Z2-027
Solar/Wind Harmer
0.01
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
316246AF1-032 C
Solar/Wind Harmer
0.026
3145933PARMELE
Solar/Wind Harmer
0.058
3146456SLIGO L269
Solar/Wind Harmer
0.058
971153AH1-033 GEN
Solar/Wind Harmer
0.672
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
944581AF1-123 GEN
Solar/Wind Harmer
13.062
944601AF1-125 GEN
Solar/Wind Harmer
12.861
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151101ELIZAR3
Adder
5.368
3144873MCLAUGH
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.023
316499AE2-029_GEN
Solar/Wind Helper
0.506
3132273ORANGE
Solar/Wind Helper
0.028
3148013FISHERV
Solar/Wind Helper
0.132
3147666LOUISA
Solar/Wind Helper
0.279
972205AH1-687 GEN
50/50
20.476
316303AF2-085
50/50
1.951
3151541CLOVER2
50/50
2.251
3151601KERR 3
50/50
0.203
3151611KERR 4
50/50
0.203
3151621KERR 5
50/50
0.203
3151631KERR 6
50/50
0.203
963041AG1-153 GEN
50/50
2.01
315244AE2-183_ST
50/50
2.141
3151281ROARAP4
50/50
0.08
971285AH1-108 GEN
50/50
0.547
315779AE2-040
50/50
0.923
971845AH1-439 GEN
Solar/Wind Harmer
16.07
316258AE1-075 C
Solar/Wind Harmer
0.184
946301AF1-294 GEN
Solar/Wind Harmer
3.892
961791AG1-021 GEN
Solar/Wind Harmer
1.893
3144303KENBRDG
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
9.017
970681AG2-440 GEN
Solar/Wind Harmer
5.985
316486AD2-202 GEN
Solar/Wind Harmer
0.107
316233AE1-074 FULL
Solar/Wind Harmer
0.073
971281AH1-106 GEN
Solar/Wind Harmer
1.262
971283AH1-107 GEN
Solar/Wind Harmer
1.262
970831AG2-522 GEN
Solar/Wind Harmer
3.731
3147173SINAI
Solar/Wind Harmer
0.086
3147243WELCO
Solar/Wind Harmer
0.054
971967AH1-528 GEN
Solar/Wind Harmer
13.172
970673AG2-436 GEN
Solar/Wind Harmer
9.233
970533AG2-339 GEN
Solar/Wind Harmer
5.573
3137643SOCKMAN
Solar/Wind Harmer
0.289
970085AG2-068 GEN
Solar/Wind Harmer
3.824
970581AG2-369 GEN
Solar/Wind Harmer
3.288
316426AA2-053 GEN
Solar/Wind Harmer
0.234
3146043SEABORD
Solar/Wind Harmer
0.069
315814AE2-033 C
Solar/Wind Harmer
5.236
315652AC1-086 GEN
Solar/Wind Harmer
7.126
316274AC1-208 GEN
Solar/Wind Harmer
0.334
3145893MURPHYS
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.204
3145796HORNRTN
Solar/Wind Harmer
0.026
316210AC1-098 GEN
Solar/Wind Harmer
0.589
3146033SCOT NK
Solar/Wind Harmer
0.253
316463AE2-346 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
0.132
3145513AHOSKIE
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.125
3145683EARLEYS
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
0.062
316327AA2-057 GEN
Solar/Wind Harmer
0.092
3146206CASHIE
Solar/Wind Harmer
0.06
970601AG2-382 GEN
Solar/Wind Harmer
2.24
315732AD1-074 GEN1
Solar/Wind Harmer
0.338
315733AD1-074 GEN2
Solar/Wind Harmer
0.338
3130546PLYMOUTH
Solar/Wind Harmer
0.059
3143316POE
Solar/Wind Harmer
0.234
970657AG2-426 GEN
Solar/Wind Harmer
0.433
316311AC2-079 GEN
Solar/Wind Harmer
1.692
3130156CHOWAN
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.059
3146486SUNBURY
Solar/Wind Harmer
0.058
3146486SUNBURY
Solar/Wind Harmer
0.058
3145176PASQUOTANK
Solar/Wind Harmer
0.036
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3146406KITTY HAWK
Solar/Wind Harmer
0.007
957871AF2-081 GEN
Solar/Wind Harmer
2.894
957861AF2-080 GEN
Solar/Wind Harmer
2.505
316316AC1-027 C
Solar/Wind Harmer
0.055
3145746EVERETS
Solar/Wind Harmer
0.23
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151081ELIZAR1
Adder
5.3
3151091ELIZAR2
Adder
5.208
971445AH1-216 GEN
Solar/Wind Harmer
3.978
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.079
3148013FISHERV
Solar/Wind Helper
0.076
3148463FAIRFLD
Solar/Wind Helper
0.12
315616AA1-038_C
Solar/Wind Helper
0.544
970909AG2-566 GEN
50/50
2.342
3144293JTRSVLE
50/50
0.5
970535AG2-341 GEN
50/50
1.944
3151581KERR 1
50/50
0.072
3152661PLYWOOD A
50/50
0.2
3151041BRUNSWICKG3
50/50
0.993
972187AH1-678 GEN
50/50
2.277
315242AE2-183_GT2
50/50
1.235
315241AE2-183_GT1
50/50
1.23
972185AH1-677 GEN
50/50
4.459
3151261ROARAP2
50/50
0.086
3146776BUCKING
Solar/Wind Harmer
1.442
3146776BUCKING
Solar/Wind Harmer
0.117
316336AC2-165 C
Solar/Wind Harmer
14.292
316313AB2-026
Solar/Wind Harmer
0.153
970301AG2-198 GEN
Solar/Wind Harmer
9.368
958211AF2-115 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.152
970323AG2-213 GEN
Solar/Wind Harmer
6.901
971223AH1-071 GEN
Solar/Wind Harmer
1.171
970099AG2-077 GEN
Solar/Wind Harmer
11.307
962561AG1-105 GEN
Solar/Wind Harmer
4.967
964791AG1-342 GEN
Solar/Wind Harmer
1.927
3146843MT LREL
Solar/Wind Harmer
0.1
3146843MT LREL
Solar/Wind Harmer
0.1
316118AC1-105 GEN
Solar/Wind Harmer
0.238
3143526WINTERP
Solar/Wind Harmer
0.473
970933AG2-581 GEN
Solar/Wind Harmer
7.1
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.089
3145783HORNRTN
Solar/Wind Harmer
1.252
3145783HORNRTN
Solar/Wind Harmer
1.001
3145783HORNRTN
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
0.125
316365GEN2_N
Solar/Wind Harmer
0.149
3144356SAPONY
Solar/Wind Harmer
0.553
316315AB2-025 C
Solar/Wind Harmer
0.053
962571AG1-106 GEN
Solar/Wind Harmer
0.922
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.039
3145893MURPHYS
Solar/Wind Harmer
0.431
3145893MURPHYS
Solar/Wind Harmer
0.116
3145796HORNRTN
Solar/Wind Harmer
0.192
3146173TUNIS
Solar/Wind Harmer
0.063
3146173TUNIS
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.022
315742AE1-103 GEN
Solar/Wind Harmer
0.922
315724AD1-057 GEN
Solar/Wind Harmer
1.175
316065AD1-022 GEN
Solar/Wind Harmer
2.754
315614AA2-178 GEN
Solar/Wind Harmer
0.337
316049AB1-081 GEN
Solar/Wind Harmer
0.335
316263AC1-034 GEN
Solar/Wind Harmer
2.24
316349AD2-085 GEN
Solar/Wind Harmer
0.039
3146376EDENTON
Solar/Wind Harmer
0.262
3146376EDENTON
Solar/Wind Harmer
0.262
315835AF2-110_GEN
Solar/Wind Harmer
0.404
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
1.041
3146386ELIZ CT
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.135
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
3130086AYDLETT
Solar/Wind Harmer
0.233
3145933PARMELE
Solar/Wind Harmer
0.116
3145933PARMELE
Solar/Wind Harmer
0.058
3137176SLIGO L2192
Solar/Wind Harmer
0.231
3146456SLIGO L269
Solar/Wind Harmer
1.029
316339AD2-160 GEN
Solar/Wind Harmer
0.093
316388AE2-253 GEN
Solar/Wind Harmer
0.181
3145506HICKORY
Solar/Wind Harmer
0.232
3145506HICKORY
Solar/Wind Harmer
0.139
3145506HICKORY
Solar/Wind Harmer
0.035
316005AA1-067
Solar/Wind Harmer
0.062
3150991CHESPKB
Adder
0.605
3150991CHESPKB
Adder
0.591
942751AE2-291 GEN
Solar/Wind Harmer
3.112
316294AC1-161 GEN
Solar/Wind Harmer
0.982
944641AF1-129 GEN
Adder
26.869
966001AG1-469 GEN
Solar/Wind Helper
0.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.173
MECLTFEXP_MEC->PJM
CLTF
0.182
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.819
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.496
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.033
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
1.45
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.449
TVALTFEXP_TVA->PJM
CLTF
0.709
NYPJM->LTFIMP_NY
CLTF
0.464

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.38 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:715.22
MW Contribution:
2.78
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.24 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:938.23
MW Contribution:
2.81
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
27.167
3151541CLOVER2
50/50
2.06
3151601KERR 3
50/50
0.188
3151611KERR 4
50/50
0.188
3151621KERR 5
50/50
0.188
3151631KERR 6
50/50
0.188
971845AH1-439 GEN
Solar/Wind Harmer
20.749
946301AF1-294 GEN
Solar/Wind Harmer
4.549
961791AG1-021 GEN
Solar/Wind Harmer
2.213
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
9.617
970681AG2-440 GEN
Solar/Wind Harmer
6.383
316486AD2-202 GEN
Solar/Wind Harmer
0.098
3147173SINAI
Solar/Wind Harmer
0.08
3147243WELCO
Solar/Wind Harmer
0.05
970831AG2-522 GEN
Solar/Wind Harmer
3.162
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
970909AG2-566 GEN
50/50
2.783
3144293JTRSVLE
50/50
0.584
970535AG2-341 GEN
50/50
1.879
3151581KERR 1
50/50
0.067
3152661PLYWOOD A
50/50
0.188
316336AC2-165 C
Solar/Wind Harmer
30.363
3146776BUCKING
Solar/Wind Harmer
1.867
3146776BUCKING
Solar/Wind Harmer
0.151
970301AG2-198 GEN
Solar/Wind Harmer
11.132
958211AF2-115 GEN
Solar/Wind Harmer
2.766
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
970323AG2-213 GEN
Solar/Wind Harmer
7.672
962561AG1-105 GEN
Solar/Wind Harmer
4.838
964791AG1-342 GEN
Solar/Wind Harmer
1.864
3146843MT LREL
Solar/Wind Harmer
0.097
3146843MT LREL
Solar/Wind Harmer
0.097
970099AG2-077 GEN
Solar/Wind Harmer
10.049
316118AC1-105 GEN
Solar/Wind Harmer
0.226
970933AG2-581 GEN
Solar/Wind Harmer
5.128
942751AE2-291 GEN
Solar/Wind Harmer
3.108
966001AG1-469 GEN
Solar/Wind Helper
0.155
3151921BEARGRDN G2
50/50
5.56
3144293JTRSVLE
50/50
0.584
970413AG2-270 GEN
50/50
9.039
972003AH1-546 GEN
Solar/Wind Harmer
20.231
970221AG2-151 GEN
Solar/Wind Harmer
28.409
3146776BUCKING
Solar/Wind Harmer
0.168
270494AE1-108_GEN
Solar/Wind Harmer
4.971
3146926FARMVIL
Solar/Wind Harmer
0.215
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.689
970257AG2-171 GEN
Solar/Wind Harmer
5.754
971775AH1-396 GEN
Solar/Wind Harmer
0.288
958131AF2-107 GEN
Solar/Wind Harmer
4.68
959311AF2-222 GEN
Solar/Wind Harmer
13.458
964241AG1-285 GEN
Solar/Wind Harmer
8.766
316478AD1-087 GEN
Solar/Wind Harmer
0.335
3147043LAWRENC
Solar/Wind Harmer
0.044
971683AH1-343 GEN
Solar/Wind Harmer
2.624
316123AC1-075 GEN
Solar/Wind Harmer
0.082
3151931BEARGRDN S1
50/50
7.184
3151911BEARGRDN G1
50/50
5.56
3144293JTRSVLE
50/50
0.584
3144293JTRSVLE
50/50
0.461
3151531CLOVER1
50/50
2.075
3151591KERR 2
50/50
0.188
3151641KERR 7
50/50
0.188
3147043LAWRENC
50/50
0.708
970937AG2-583 GEN
Solar/Wind Harmer
36.756
971377AH1-170 GEN
Solar/Wind Harmer
5.682
3147623JAMES R
Solar/Wind Harmer
1.234
3146776BUCKING
Solar/Wind Harmer
0.187
3146926FARMVIL
Solar/Wind Harmer
0.215
971563AH1-280 GEN
Solar/Wind Harmer
2.459
970685AG2-442 GEN
Solar/Wind Harmer
13.128
315785AD2-033 C
Solar/Wind Harmer
1.371
316034AC1-036 C
Solar/Wind Harmer
0.01
315693AD1-088 GEN
Solar/Wind Harmer
6.208
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970401AG2-262 GEN
Solar/Wind Harmer
0.57
957481AF2-042 GEN
Solar/Wind Harmer
25.123
971065AG2-659 GEN
Solar/Wind Harmer
3.402
316129AC1-054 GEN
Solar/Wind Harmer
0.289
962751AG1-124 GEN
Solar/Wind Harmer
2.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.743
MECLTFEXP_MEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
2.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.492
LAGNLTFEXP_LAGN->PJM
CLTF
1.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.485
TVALTFEXP_TVA->PJM
CLTF
0.56
NYPJM->LTFIMP_NY
CLTF
0.403
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.99 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:734.51
MW Contribution:
2.34
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.476
316303AF2-085
50/50
1.951
3151541CLOVER2
50/50
2.251
3151601KERR 3
50/50
0.203
3151611KERR 4
50/50
0.203
3151621KERR 5
50/50
0.203
3151631KERR 6
50/50
0.203
963041AG1-153 GEN
50/50
2.01
315244AE2-183_ST
50/50
2.141
3151281ROARAP4
50/50
0.08
971285AH1-108 GEN
50/50
0.547
315779AE2-040
50/50
0.923
971845AH1-439 GEN
Solar/Wind Harmer
16.07
316258AE1-075 C
Solar/Wind Harmer
0.184
946301AF1-294 GEN
Solar/Wind Harmer
3.892
961791AG1-021 GEN
Solar/Wind Harmer
1.893
3144303KENBRDG
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
9.017
970681AG2-440 GEN
Solar/Wind Harmer
5.985
316486AD2-202 GEN
Solar/Wind Harmer
0.107
316233AE1-074 FULL
Solar/Wind Harmer
0.073
971281AH1-106 GEN
Solar/Wind Harmer
1.262
971283AH1-107 GEN
Solar/Wind Harmer
1.262
970831AG2-522 GEN
Solar/Wind Harmer
3.731
3147173SINAI
Solar/Wind Harmer
0.086
3147243WELCO
Solar/Wind Harmer
0.054
971967AH1-528 GEN
Solar/Wind Harmer
13.172
970673AG2-436 GEN
Solar/Wind Harmer
9.233
970533AG2-339 GEN
Solar/Wind Harmer
5.573
3137643SOCKMAN
Solar/Wind Harmer
0.289
970085AG2-068 GEN
Solar/Wind Harmer
3.824
970581AG2-369 GEN
Solar/Wind Harmer
3.288
316426AA2-053 GEN
Solar/Wind Harmer
0.234
3146043SEABORD
Solar/Wind Harmer
0.069
315814AE2-033 C
Solar/Wind Harmer
5.236
315652AC1-086 GEN
Solar/Wind Harmer
7.126
316274AC1-208 GEN
Solar/Wind Harmer
0.334
3145893MURPHYS
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.204
3145796HORNRTN
Solar/Wind Harmer
0.026
316210AC1-098 GEN
Solar/Wind Harmer
0.589
3146033SCOT NK
Solar/Wind Harmer
0.253
316463AE2-346 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
0.132
3145513AHOSKIE
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.125
3145683EARLEYS
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
0.062
316327AA2-057 GEN
Solar/Wind Harmer
0.092
3146206CASHIE
Solar/Wind Harmer
0.06
970601AG2-382 GEN
Solar/Wind Harmer
2.24
315732AD1-074 GEN1
Solar/Wind Harmer
0.338
315733AD1-074 GEN2
Solar/Wind Harmer
0.338
3130546PLYMOUTH
Solar/Wind Harmer
0.059
3143316POE
Solar/Wind Harmer
0.234
970657AG2-426 GEN
Solar/Wind Harmer
0.433
316311AC2-079 GEN
Solar/Wind Harmer
1.692
3130156CHOWAN
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.059
3146486SUNBURY
Solar/Wind Harmer
0.058
3146486SUNBURY
Solar/Wind Harmer
0.058
3145176PASQUOTANK
Solar/Wind Harmer
0.036
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3146406KITTY HAWK
Solar/Wind Harmer
0.007
957871AF2-081 GEN
Solar/Wind Harmer
2.894
957861AF2-080 GEN
Solar/Wind Harmer
2.505
316316AC1-027 C
Solar/Wind Harmer
0.055
3145746EVERETS
Solar/Wind Harmer
0.23
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151081ELIZAR1
Adder
5.3
3151091ELIZAR2
Adder
5.208
971445AH1-216 GEN
Solar/Wind Harmer
3.978
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.079
3148013FISHERV
Solar/Wind Helper
0.076
3148463FAIRFLD
Solar/Wind Helper
0.12
315616AA1-038_C
Solar/Wind Helper
0.544
3151921BEARGRDN G2
50/50
4.191
3144293JTRSVLE
50/50
0.5
970413AG2-270 GEN
50/50
9.876
3151031BRUNSWICKG2
50/50
0.993
3151261ROARAP2
50/50
0.088
3150861SPRUNCD
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
972003AH1-546 GEN
Solar/Wind Harmer
15.285
970221AG2-151 GEN
Solar/Wind Harmer
21.415
3146776BUCKING
Solar/Wind Harmer
0.13
270494AE1-108_GEN
Solar/Wind Harmer
3.742
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
3.722
942461AE2-259 GEN
Solar/Wind Harmer
0
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.598
970257AG2-171 GEN
Solar/Wind Harmer
5.176
971775AH1-396 GEN
Solar/Wind Harmer
0.259
959311AF2-222 GEN
Solar/Wind Harmer
12.78
964241AG1-285 GEN
Solar/Wind Harmer
8.638
958131AF2-107 GEN
Solar/Wind Harmer
3.491
316478AD1-087 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.054
971683AH1-343 GEN
Solar/Wind Harmer
2.762
944011AF1-069 GEN
Solar/Wind Harmer
4.438
316181AB2-040 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.456
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.065
316011AB1-132 GEN
Solar/Wind Harmer
1.175
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.064
316212AC1-099_GEN
Solar/Wind Harmer
0.328
3146173TUNIS
Solar/Wind Harmer
0.063
316123AC1-075 GEN
Solar/Wind Harmer
0.084
3145823KELFORD
Solar/Wind Harmer
0.063
315722AD1-056 GEN
Solar/Wind Harmer
2.107
3145273HOLLAND
Solar/Wind Harmer
0.046
316222AC1-221 GEN
Solar/Wind Harmer
0.25
3146233WITAKRS
Solar/Wind Harmer
0.304
3146233WITAKRS
Solar/Wind Harmer
0.041
3138543CONSLDL
Solar/Wind Harmer
0.04
316283AC2-100 C
Solar/Wind Harmer
0.118
3146206CASHIE
Solar/Wind Harmer
0.06
315735AD1-075 GEN1
Solar/Wind Harmer
0.169
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.059
315813AE1-149 C
Solar/Wind Harmer
3.146
970657AG2-426 GEN
Solar/Wind Harmer
1.323
971623AH1-311 GEN
Solar/Wind Harmer
0.118
3146376EDENTON
Solar/Wind Harmer
0.059
3145963POPLR C
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
4.163
316321Z2-027
Solar/Wind Harmer
0.01
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
316246AF1-032 C
Solar/Wind Harmer
0.026
3151931BEARGRDN S1
50/50
5.414
3151911BEARGRDN G1
50/50
4.191
3144293JTRSVLE
50/50
0.5
3144293JTRSVLE
50/50
0.394
970119AG2-088 GEN
50/50
14.635
3151531CLOVER1
50/50
2.268
3151591KERR 2
50/50
0.203
3151641KERR 7
50/50
0.203
3147043LAWRENC
50/50
0.857
3151051BRUNSWICKS1
50/50
2.06
3151021BRUNSWICKG1
50/50
0.993
971451AH1-221 GEN
50/50
3.014
315243AE2-183_GT3
50/50
1.235
3151281ROARAP4
50/50
0.085
3150851SPRUNCC
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
971377AH1-170 GEN
Solar/Wind Harmer
4.283
3147623JAMES R
Solar/Wind Harmer
0.93
970937AG2-583 GEN
Solar/Wind Harmer
22.933
3146776BUCKING
Solar/Wind Harmer
0.144
3146926FARMVIL
Solar/Wind Harmer
0.172
3145933PARMELE
Solar/Wind Harmer
0.058
3146456SLIGO L269
Solar/Wind Harmer
0.058
971153AH1-033 GEN
Solar/Wind Harmer
0.672
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
944581AF1-123 GEN
Solar/Wind Harmer
13.062
944601AF1-125 GEN
Solar/Wind Harmer
12.861
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151101ELIZAR3
Adder
5.368
3144873MCLAUGH
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.023
316499AE2-029_GEN
Solar/Wind Helper
0.506
3132273ORANGE
Solar/Wind Helper
0.028
3148013FISHERV
Solar/Wind Helper
0.132
3147666LOUISA
Solar/Wind Helper
0.279
3143336POWHATN
Solar/Wind Harmer
4.379
971563AH1-280 GEN
Solar/Wind Harmer
2.104
970685AG2-442 GEN
Solar/Wind Harmer
12.003
315785AD2-033 C
Solar/Wind Harmer
1.25
316034AC1-036 C
Solar/Wind Harmer
0.009
315693AD1-088 GEN
Solar/Wind Harmer
6.214
316131AB2-060 GEN
Solar/Wind Harmer
0.385
3143226MDLTHAN
Solar/Wind Harmer
0.11
957481AF2-042 GEN
Solar/Wind Harmer
28.268
970401AG2-262 GEN
Solar/Wind Harmer
0.589
971065AG2-659 GEN
Solar/Wind Harmer
3.89
3143526WINTERP
Solar/Wind Harmer
0.473
316129AC1-054 GEN
Solar/Wind Harmer
0.334
960081AF2-299 GEN
Solar/Wind Harmer
0.725
941031AE2-094 GEN
Solar/Wind Harmer
13.584
970919AG2-571 GEN
Solar/Wind Harmer
2.582
970087AG2-069 GEN
Solar/Wind Harmer
5.736
3145783HORNRTN
Solar/Wind Harmer
0.07
940641AE2-051 GEN
Solar/Wind Harmer
5.555
315607AA1-063A GEN
Solar/Wind Harmer
0.139
316023GEN1_S
Solar/Wind Harmer
0.149
939411AE1-173 GEN
Solar/Wind Harmer
28.41
3146263WOODLND
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.287
3145796HORNRTN
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
0.063
3145823KELFORD
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.062
3156021HOLLOMANSOL
Solar/Wind Harmer
0.273
3146233WITAKRS
Solar/Wind Harmer
0.241
3146206CASHIE
Solar/Wind Harmer
0.06
971547AH1-271 GEN
Solar/Wind Harmer
1.28
315737AD1-076 GEN
Solar/Wind Harmer
0.763
315816AE2-034 GEN
Solar/Wind Harmer
0.253
3145663CRESWEL
Solar/Wind Harmer
0.166
971163AH1-040 GEN
Solar/Wind Harmer
4.737
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.047
316381AD1-082 GEN
Solar/Wind Harmer
0.06
316359AB2-059 GEN
Solar/Wind Harmer
0.21
3142053HEARTS
Solar/Wind Harmer
0.104
3130156CHOWAN
Solar/Wind Harmer
0.059
316093AE2-104_GEN
Solar/Wind Harmer
0.99
3145963POPLR C
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.19
3146516WINFALL
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.259
319010AE1-072 C
Solar/Wind Harmer
0.29
3146293MARTNCO
Solar/Wind Harmer
0.054
3146456SLIGO L269
Solar/Wind Harmer
0.058
316494AC1-189 GEN
Solar/Wind Harmer
0.196
944591AF1-124 GEN
Solar/Wind Harmer
13.109
3142543TWELFTH
Solar/Wind Harmer
0.006
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.01
3150981CHESPKA
Adder
0.721
316072AD1-144
Solar/Wind Harmer
0.02
315671AE2-027_GEN
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.073
3145336SMITFLD
Solar/Wind Harmer
0.226
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.844
3147666LOUISA
Solar/Wind Helper
0.484
970909AG2-566 GEN
50/50
2.342
3144293JTRSVLE
50/50
0.5
970535AG2-341 GEN
50/50
1.944
3151581KERR 1
50/50
0.072
3152661PLYWOOD A
50/50
0.2
3151041BRUNSWICKG3
50/50
0.993
972187AH1-678 GEN
50/50
2.277
315242AE2-183_GT2
50/50
1.235
315241AE2-183_GT1
50/50
1.23
972185AH1-677 GEN
50/50
4.459
3151261ROARAP2
50/50
0.086
3146776BUCKING
Solar/Wind Harmer
1.442
3146776BUCKING
Solar/Wind Harmer
0.117
316336AC2-165 C
Solar/Wind Harmer
14.292
316313AB2-026
Solar/Wind Harmer
0.153
970301AG2-198 GEN
Solar/Wind Harmer
9.368
958211AF2-115 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.152
970323AG2-213 GEN
Solar/Wind Harmer
6.901
971223AH1-071 GEN
Solar/Wind Harmer
1.171
970099AG2-077 GEN
Solar/Wind Harmer
11.307
962561AG1-105 GEN
Solar/Wind Harmer
4.967
964791AG1-342 GEN
Solar/Wind Harmer
1.927
3146843MT LREL
Solar/Wind Harmer
0.1
3146843MT LREL
Solar/Wind Harmer
0.1
316118AC1-105 GEN
Solar/Wind Harmer
0.238
3143526WINTERP
Solar/Wind Harmer
0.473
970933AG2-581 GEN
Solar/Wind Harmer
7.1
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.089
3145783HORNRTN
Solar/Wind Harmer
1.252
3145783HORNRTN
Solar/Wind Harmer
1.001
3145783HORNRTN
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
0.125
316365GEN2_N
Solar/Wind Harmer
0.149
3144356SAPONY
Solar/Wind Harmer
0.553
316315AB2-025 C
Solar/Wind Harmer
0.053
962571AG1-106 GEN
Solar/Wind Harmer
0.922
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.039
3145893MURPHYS
Solar/Wind Harmer
0.431
3145893MURPHYS
Solar/Wind Harmer
0.116
3145796HORNRTN
Solar/Wind Harmer
0.192
3146173TUNIS
Solar/Wind Harmer
0.063
3146173TUNIS
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.022
315742AE1-103 GEN
Solar/Wind Harmer
0.922
315724AD1-057 GEN
Solar/Wind Harmer
1.175
316065AD1-022 GEN
Solar/Wind Harmer
2.754
315614AA2-178 GEN
Solar/Wind Harmer
0.337
316049AB1-081 GEN
Solar/Wind Harmer
0.335
316263AC1-034 GEN
Solar/Wind Harmer
2.24
316349AD2-085 GEN
Solar/Wind Harmer
0.039
3146376EDENTON
Solar/Wind Harmer
0.262
3146376EDENTON
Solar/Wind Harmer
0.262
315835AF2-110_GEN
Solar/Wind Harmer
0.404
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
1.041
3146386ELIZ CT
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.135
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
3130086AYDLETT
Solar/Wind Harmer
0.233
3145933PARMELE
Solar/Wind Harmer
0.116
3145933PARMELE
Solar/Wind Harmer
0.058
3137176SLIGO L2192
Solar/Wind Harmer
0.231
3146456SLIGO L269
Solar/Wind Harmer
1.029
316339AD2-160 GEN
Solar/Wind Harmer
0.093
316388AE2-253 GEN
Solar/Wind Harmer
0.181
3145506HICKORY
Solar/Wind Harmer
0.232
3145506HICKORY
Solar/Wind Harmer
0.139
3145506HICKORY
Solar/Wind Harmer
0.035
316005AA1-067
Solar/Wind Harmer
0.062
3150991CHESPKB
Adder
0.605
3150991CHESPKB
Adder
0.591
942751AE2-291 GEN
Solar/Wind Harmer
3.112
316294AC1-161 GEN
Solar/Wind Harmer
0.982
944641AF1-129 GEN
Adder
26.869
966001AG1-469 GEN
Solar/Wind Helper
0.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.173
MECLTFEXP_MEC->PJM
CLTF
0.182
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.819
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.496
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.033
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
1.45
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.449
TVALTFEXP_TVA->PJM
CLTF
0.709
NYPJM->LTFIMP_NY
CLTF
0.464

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.47 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:697.98
MW Contribution:
2.78
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.17 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:920.95
MW Contribution:
2.81
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
27.167
3151541CLOVER2
50/50
2.06
3151601KERR 3
50/50
0.188
3151611KERR 4
50/50
0.188
3151621KERR 5
50/50
0.188
3151631KERR 6
50/50
0.188
971845AH1-439 GEN
Solar/Wind Harmer
20.749
946301AF1-294 GEN
Solar/Wind Harmer
4.549
961791AG1-021 GEN
Solar/Wind Harmer
2.213
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
9.617
970681AG2-440 GEN
Solar/Wind Harmer
6.383
316486AD2-202 GEN
Solar/Wind Harmer
0.098
3147173SINAI
Solar/Wind Harmer
0.08
3147243WELCO
Solar/Wind Harmer
0.05
970831AG2-522 GEN
Solar/Wind Harmer
3.162
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151921BEARGRDN G2
50/50
5.56
3144293JTRSVLE
50/50
0.584
970413AG2-270 GEN
50/50
9.039
972003AH1-546 GEN
Solar/Wind Harmer
20.231
970221AG2-151 GEN
Solar/Wind Harmer
28.409
3146776BUCKING
Solar/Wind Harmer
0.168
270494AE1-108_GEN
Solar/Wind Harmer
4.971
3146926FARMVIL
Solar/Wind Harmer
0.215
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.689
970257AG2-171 GEN
Solar/Wind Harmer
5.754
971775AH1-396 GEN
Solar/Wind Harmer
0.288
958131AF2-107 GEN
Solar/Wind Harmer
4.68
959311AF2-222 GEN
Solar/Wind Harmer
13.458
964241AG1-285 GEN
Solar/Wind Harmer
8.766
316478AD1-087 GEN
Solar/Wind Harmer
0.335
3147043LAWRENC
Solar/Wind Harmer
0.044
971683AH1-343 GEN
Solar/Wind Harmer
2.624
316123AC1-075 GEN
Solar/Wind Harmer
0.082
970909AG2-566 GEN
50/50
2.783
3144293JTRSVLE
50/50
0.584
970535AG2-341 GEN
50/50
1.879
3151581KERR 1
50/50
0.067
3152661PLYWOOD A
50/50
0.188
316336AC2-165 C
Solar/Wind Harmer
30.363
3146776BUCKING
Solar/Wind Harmer
1.867
3146776BUCKING
Solar/Wind Harmer
0.151
970301AG2-198 GEN
Solar/Wind Harmer
11.132
958211AF2-115 GEN
Solar/Wind Harmer
2.766
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
970323AG2-213 GEN
Solar/Wind Harmer
7.672
962561AG1-105 GEN
Solar/Wind Harmer
4.838
964791AG1-342 GEN
Solar/Wind Harmer
1.864
3146843MT LREL
Solar/Wind Harmer
0.097
3146843MT LREL
Solar/Wind Harmer
0.097
970099AG2-077 GEN
Solar/Wind Harmer
10.049
316118AC1-105 GEN
Solar/Wind Harmer
0.226
970933AG2-581 GEN
Solar/Wind Harmer
5.128
942751AE2-291 GEN
Solar/Wind Harmer
3.108
966001AG1-469 GEN
Solar/Wind Helper
0.155
3151931BEARGRDN S1
50/50
7.184
3151911BEARGRDN G1
50/50
5.56
3144293JTRSVLE
50/50
0.584
3144293JTRSVLE
50/50
0.461
3151531CLOVER1
50/50
2.075
3151591KERR 2
50/50
0.188
3151641KERR 7
50/50
0.188
3147043LAWRENC
50/50
0.708
970937AG2-583 GEN
Solar/Wind Harmer
36.756
971377AH1-170 GEN
Solar/Wind Harmer
5.682
3147623JAMES R
Solar/Wind Harmer
1.234
3146776BUCKING
Solar/Wind Harmer
0.187
3146926FARMVIL
Solar/Wind Harmer
0.215
971563AH1-280 GEN
Solar/Wind Harmer
2.459
970685AG2-442 GEN
Solar/Wind Harmer
13.128
315785AD2-033 C
Solar/Wind Harmer
1.371
316034AC1-036 C
Solar/Wind Harmer
0.01
315693AD1-088 GEN
Solar/Wind Harmer
6.208
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970401AG2-262 GEN
Solar/Wind Harmer
0.57
957481AF2-042 GEN
Solar/Wind Harmer
25.123
971065AG2-659 GEN
Solar/Wind Harmer
3.402
316129AC1-054 GEN
Solar/Wind Harmer
0.289
962751AG1-124 GEN
Solar/Wind Harmer
2.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.743
MECLTFEXP_MEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
2.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.492
LAGNLTFEXP_LAGN->PJM
CLTF
1.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.485
TVALTFEXP_TVA->PJM
CLTF
0.56
NYPJM->LTFIMP_NY
CLTF
0.403
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.19 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:810.51
MW Contribution:
2.78
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.99 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1043.51
MW Contribution:
2.81
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
27.167
316322AB2-045
Solar/Wind Harmer
1.761
971845AH1-439 GEN
Solar/Wind Harmer
27.32
946301AF1-294 GEN
Solar/Wind Harmer
6.637
961791AG1-021 GEN
Solar/Wind Harmer
3.238
3144303KENBRDG
Solar/Wind Harmer
-0.016
970683AG2-441 GEN
Solar/Wind Harmer
12.663
970681AG2-440 GEN
Solar/Wind Harmer
8.405
316238AB2-078_GEN
Solar/Wind Harmer
0.4
316239AB2-077_GEN
Solar/Wind Harmer
0.4
316486AD2-202 GEN
Solar/Wind Harmer
0.275
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.163
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151921BEARGRDN G2
50/50
5.56
3144293JTRSVLE
50/50
0.584
972003AH1-546 GEN
Solar/Wind Harmer
26.637
970221AG2-151 GEN
Solar/Wind Harmer
37.406
3146776BUCKING
Solar/Wind Harmer
-0.019
270494AE1-108_GEN
Solar/Wind Harmer
12.155
3146926FARMVIL
Solar/Wind Harmer
-0.024
315821AE2-092 GEN
Solar/Wind Harmer
7.738
942461AE2-259 GEN
Solar/Wind Harmer
4.887
3147133PAMPLIN
Solar/Wind Harmer
-0.077
970257AG2-171 GEN
Solar/Wind Harmer
7.576
971775AH1-396 GEN
Solar/Wind Harmer
1.425
958131AF2-107 GEN
Solar/Wind Harmer
6.23
959311AF2-222 GEN
Solar/Wind Harmer
17.755
964241AG1-285 GEN
Solar/Wind Harmer
11.542
316478AD1-087 GEN
Solar/Wind Harmer
0.938
316003AC1-222 GEN
Solar/Wind Harmer
0.829
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.455
316123AC1-075 GEN
Solar/Wind Harmer
0.746
3151931BEARGRDN S1
50/50
7.184
3151911BEARGRDN G1
50/50
5.56
3144293JTRSVLE
50/50
0.584
3144293JTRSVLE
50/50
0.461
970937AG2-583 GEN
Solar/Wind Harmer
48.395
971377AH1-170 GEN
Solar/Wind Harmer
7.481
3147623JAMES R
Solar/Wind Harmer
0.926
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
971563AH1-280 GEN
Solar/Wind Harmer
3.238
970685AG2-442 GEN
Solar/Wind Harmer
17.285
315785AD2-033 C
Solar/Wind Harmer
4.309
316034AC1-036 C
Solar/Wind Harmer
0.308
315693AD1-088 GEN
Solar/Wind Harmer
7.265
316131AB2-060 GEN
Solar/Wind Harmer
1.515
970401AG2-262 GEN
Solar/Wind Harmer
0.712
957481AF2-042 GEN
Solar/Wind Harmer
33.079
971065AG2-659 GEN
Solar/Wind Harmer
4.479
316129AC1-054 GEN
Solar/Wind Harmer
0.759
3147043LAWRENC
Adder
0.667
962751AG1-124 GEN
Solar/Wind Harmer
4.142
970909AG2-566 GEN
50/50
2.783
3144293JTRSVLE
50/50
0.584
316336AC2-165 C
Solar/Wind Harmer
42.04
3146776BUCKING
Solar/Wind Harmer
-0.209
3146776BUCKING
Solar/Wind Harmer
-0.017
970301AG2-198 GEN
Solar/Wind Harmer
14.657
958211AF2-115 GEN
Solar/Wind Harmer
4.047
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
970323AG2-213 GEN
Solar/Wind Harmer
10.101
313527AB2-043 GEN
Solar/Wind Harmer
2.211
316237AB2-079_GEN
Solar/Wind Harmer
0.4
962561AG1-105 GEN
Solar/Wind Harmer
6.37
964791AG1-342 GEN
Solar/Wind Harmer
2.33
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.232
316118AC1-105 GEN
Solar/Wind Harmer
0.68
315687AD1-152 GEN
Solar/Wind Harmer
1.173
316248AF1-058 C
Solar/Wind Harmer
0.269
970933AG2-581 GEN
Solar/Wind Harmer
6.752
942751AE2-291 GEN
Solar/Wind Harmer
4.092
966001AG1-469 GEN
Solar/Wind Helper
0.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.743
MECLTFEXP_MEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
2.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.492
LAGNLTFEXP_LAGN->PJM
CLTF
1.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.485
TVALTFEXP_TVA->PJM
CLTF
0.56
NYPJM->LTFIMP_NY
CLTF
0.403
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.19 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:810.51
MW Contribution:
2.78
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.56
3144293JTRSVLE
50/50
0.584
972003AH1-546 GEN
Solar/Wind Harmer
26.637
970221AG2-151 GEN
Solar/Wind Harmer
37.406
3146776BUCKING
Solar/Wind Harmer
-0.019
270494AE1-108_GEN
Solar/Wind Harmer
12.155
3146926FARMVIL
Solar/Wind Harmer
-0.024
315821AE2-092 GEN
Solar/Wind Harmer
7.738
942461AE2-259 GEN
Solar/Wind Harmer
4.887
3147133PAMPLIN
Solar/Wind Harmer
-0.077
970257AG2-171 GEN
Solar/Wind Harmer
7.576
971775AH1-396 GEN
Solar/Wind Harmer
1.425
958131AF2-107 GEN
Solar/Wind Harmer
6.23
959311AF2-222 GEN
Solar/Wind Harmer
17.755
964241AG1-285 GEN
Solar/Wind Harmer
11.542
316478AD1-087 GEN
Solar/Wind Harmer
0.938
316003AC1-222 GEN
Solar/Wind Harmer
0.829
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.455
316123AC1-075 GEN
Solar/Wind Harmer
0.746
972205AH1-687 GEN
50/50
27.167
316322AB2-045
Solar/Wind Harmer
1.761
971845AH1-439 GEN
Solar/Wind Harmer
27.32
946301AF1-294 GEN
Solar/Wind Harmer
6.637
961791AG1-021 GEN
Solar/Wind Harmer
3.238
3144303KENBRDG
Solar/Wind Harmer
-0.016
970683AG2-441 GEN
Solar/Wind Harmer
12.663
970681AG2-440 GEN
Solar/Wind Harmer
8.405
316238AB2-078_GEN
Solar/Wind Harmer
0.4
316239AB2-077_GEN
Solar/Wind Harmer
0.4
316486AD2-202 GEN
Solar/Wind Harmer
0.275
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.163
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151931BEARGRDN S1
50/50
7.184
3151911BEARGRDN G1
50/50
5.56
3144293JTRSVLE
50/50
0.584
3144293JTRSVLE
50/50
0.461
970937AG2-583 GEN
Solar/Wind Harmer
48.395
971377AH1-170 GEN
Solar/Wind Harmer
7.481
3147623JAMES R
Solar/Wind Harmer
0.926
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
971563AH1-280 GEN
Solar/Wind Harmer
3.238
970685AG2-442 GEN
Solar/Wind Harmer
17.285
315785AD2-033 C
Solar/Wind Harmer
4.309
316034AC1-036 C
Solar/Wind Harmer
0.308
315693AD1-088 GEN
Solar/Wind Harmer
7.265
316131AB2-060 GEN
Solar/Wind Harmer
1.515
970401AG2-262 GEN
Solar/Wind Harmer
0.712
957481AF2-042 GEN
Solar/Wind Harmer
33.079
971065AG2-659 GEN
Solar/Wind Harmer
4.479
316129AC1-054 GEN
Solar/Wind Harmer
0.759
3147043LAWRENC
Adder
0.667
962751AG1-124 GEN
Solar/Wind Harmer
4.142
970909AG2-566 GEN
50/50
2.783
3144293JTRSVLE
50/50
0.584
316336AC2-165 C
Solar/Wind Harmer
42.04
3146776BUCKING
Solar/Wind Harmer
-0.209
3146776BUCKING
Solar/Wind Harmer
-0.017
970301AG2-198 GEN
Solar/Wind Harmer
14.657
958211AF2-115 GEN
Solar/Wind Harmer
4.047
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
970323AG2-213 GEN
Solar/Wind Harmer
10.101
313527AB2-043 GEN
Solar/Wind Harmer
2.211
316237AB2-079_GEN
Solar/Wind Harmer
0.4
962561AG1-105 GEN
Solar/Wind Harmer
6.37
964791AG1-342 GEN
Solar/Wind Harmer
2.33
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.232
316118AC1-105 GEN
Solar/Wind Harmer
0.68
315687AD1-152 GEN
Solar/Wind Harmer
1.173
316248AF1-058 C
Solar/Wind Harmer
0.269
970933AG2-581 GEN
Solar/Wind Harmer
6.752
942751AE2-291 GEN
Solar/Wind Harmer
4.092
966001AG1-469 GEN
Solar/Wind Helper
0.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.743
MECLTFEXP_MEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
2.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.492
LAGNLTFEXP_LAGN->PJM
CLTF
1.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.485
TVALTFEXP_TVA->PJM
CLTF
0.56
NYPJM->LTFIMP_NY
CLTF
0.403
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.84 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:713.66
MW Contribution:
2.34
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.414
3151911BEARGRDN G1
50/50
4.191
3144293JTRSVLE
50/50
0.5
3144293JTRSVLE
50/50
0.394
970119AG2-088 GEN
50/50
14.635
3151531CLOVER1
50/50
2.268
3151591KERR 2
50/50
0.203
3151641KERR 7
50/50
0.203
3147043LAWRENC
50/50
0.857
3151051BRUNSWICKS1
50/50
2.06
3151021BRUNSWICKG1
50/50
0.993
971451AH1-221 GEN
50/50
3.014
315243AE2-183_GT3
50/50
1.235
3151281ROARAP4
50/50
0.085
3150851SPRUNCC
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
971377AH1-170 GEN
Solar/Wind Harmer
4.283
3147623JAMES R
Solar/Wind Harmer
0.93
970937AG2-583 GEN
Solar/Wind Harmer
22.933
3146776BUCKING
Solar/Wind Harmer
0.144
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
4.379
971563AH1-280 GEN
Solar/Wind Harmer
2.104
970685AG2-442 GEN
Solar/Wind Harmer
12.003
315785AD2-033 C
Solar/Wind Harmer
1.25
316034AC1-036 C
Solar/Wind Harmer
0.009
315693AD1-088 GEN
Solar/Wind Harmer
6.214
316131AB2-060 GEN
Solar/Wind Harmer
0.385
3143226MDLTHAN
Solar/Wind Harmer
0.11
957481AF2-042 GEN
Solar/Wind Harmer
28.268
970401AG2-262 GEN
Solar/Wind Harmer
0.589
971065AG2-659 GEN
Solar/Wind Harmer
3.89
3143526WINTERP
Solar/Wind Harmer
0.473
316129AC1-054 GEN
Solar/Wind Harmer
0.334
960081AF2-299 GEN
Solar/Wind Harmer
0.725
941031AE2-094 GEN
Solar/Wind Harmer
13.584
970919AG2-571 GEN
Solar/Wind Harmer
2.582
970087AG2-069 GEN
Solar/Wind Harmer
5.736
3145783HORNRTN
Solar/Wind Harmer
0.07
940641AE2-051 GEN
Solar/Wind Harmer
5.555
315607AA1-063A GEN
Solar/Wind Harmer
0.139
316023GEN1_S
Solar/Wind Harmer
0.149
939411AE1-173 GEN
Solar/Wind Harmer
28.41
3146263WOODLND
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.287
3145796HORNRTN
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
0.063
3145823KELFORD
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.062
3156021HOLLOMANSOL
Solar/Wind Harmer
0.273
3146233WITAKRS
Solar/Wind Harmer
0.241
3146206CASHIE
Solar/Wind Harmer
0.06
971547AH1-271 GEN
Solar/Wind Harmer
1.28
315737AD1-076 GEN
Solar/Wind Harmer
0.763
315816AE2-034 GEN
Solar/Wind Harmer
0.253
3145663CRESWEL
Solar/Wind Harmer
0.166
971163AH1-040 GEN
Solar/Wind Harmer
4.737
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.047
316381AD1-082 GEN
Solar/Wind Harmer
0.06
316359AB2-059 GEN
Solar/Wind Harmer
0.21
3142053HEARTS
Solar/Wind Harmer
0.104
3130156CHOWAN
Solar/Wind Harmer
0.059
316093AE2-104_GEN
Solar/Wind Harmer
0.99
3145963POPLR C
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.19
3146516WINFALL
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.259
319010AE1-072 C
Solar/Wind Harmer
0.29
3146293MARTNCO
Solar/Wind Harmer
0.054
3146456SLIGO L269
Solar/Wind Harmer
0.058
316494AC1-189 GEN
Solar/Wind Harmer
0.196
944591AF1-124 GEN
Solar/Wind Harmer
13.109
3142543TWELFTH
Solar/Wind Harmer
0.006
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.01
3150981CHESPKA
Adder
0.721
316072AD1-144
Solar/Wind Harmer
0.02
315671AE2-027_GEN
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.073
3145336SMITFLD
Solar/Wind Harmer
0.226
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.844
3147666LOUISA
Solar/Wind Helper
0.484
3151921BEARGRDN G2
50/50
4.191
3144293JTRSVLE
50/50
0.5
970413AG2-270 GEN
50/50
9.876
3151031BRUNSWICKG2
50/50
0.993
3151261ROARAP2
50/50
0.088
3150861SPRUNCD
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
972003AH1-546 GEN
Solar/Wind Harmer
15.285
970221AG2-151 GEN
Solar/Wind Harmer
21.415
3146776BUCKING
Solar/Wind Harmer
0.13
270494AE1-108_GEN
Solar/Wind Harmer
3.742
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
3.722
942461AE2-259 GEN
Solar/Wind Harmer
0
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.598
970257AG2-171 GEN
Solar/Wind Harmer
5.176
971775AH1-396 GEN
Solar/Wind Harmer
0.259
959311AF2-222 GEN
Solar/Wind Harmer
12.78
964241AG1-285 GEN
Solar/Wind Harmer
8.638
958131AF2-107 GEN
Solar/Wind Harmer
3.491
316478AD1-087 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.054
971683AH1-343 GEN
Solar/Wind Harmer
2.762
944011AF1-069 GEN
Solar/Wind Harmer
4.438
316181AB2-040 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.456
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.065
316011AB1-132 GEN
Solar/Wind Harmer
1.175
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.064
316212AC1-099_GEN
Solar/Wind Harmer
0.328
3146173TUNIS
Solar/Wind Harmer
0.063
316123AC1-075 GEN
Solar/Wind Harmer
0.084
3145823KELFORD
Solar/Wind Harmer
0.063
315722AD1-056 GEN
Solar/Wind Harmer
2.107
3145273HOLLAND
Solar/Wind Harmer
0.046
316222AC1-221 GEN
Solar/Wind Harmer
0.25
3146233WITAKRS
Solar/Wind Harmer
0.304
3146233WITAKRS
Solar/Wind Harmer
0.041
3138543CONSLDL
Solar/Wind Harmer
0.04
316283AC2-100 C
Solar/Wind Harmer
0.118
3146206CASHIE
Solar/Wind Harmer
0.06
315735AD1-075 GEN1
Solar/Wind Harmer
0.169
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.059
315813AE1-149 C
Solar/Wind Harmer
3.146
970657AG2-426 GEN
Solar/Wind Harmer
1.323
971623AH1-311 GEN
Solar/Wind Harmer
0.118
3146376EDENTON
Solar/Wind Harmer
0.059
3145963POPLR C
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
4.163
316321Z2-027
Solar/Wind Harmer
0.01
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
316246AF1-032 C
Solar/Wind Harmer
0.026
3145933PARMELE
Solar/Wind Harmer
0.058
3146456SLIGO L269
Solar/Wind Harmer
0.058
971153AH1-033 GEN
Solar/Wind Harmer
0.672
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
944581AF1-123 GEN
Solar/Wind Harmer
13.062
944601AF1-125 GEN
Solar/Wind Harmer
12.861
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151101ELIZAR3
Adder
5.368
3144873MCLAUGH
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.023
316499AE2-029_GEN
Solar/Wind Helper
0.506
3132273ORANGE
Solar/Wind Helper
0.028
3148013FISHERV
Solar/Wind Helper
0.132
3147666LOUISA
Solar/Wind Helper
0.279
970909AG2-566 GEN
50/50
2.342
3144293JTRSVLE
50/50
0.5
970535AG2-341 GEN
50/50
1.944
3151581KERR 1
50/50
0.072
3152661PLYWOOD A
50/50
0.2
3151041BRUNSWICKG3
50/50
0.993
972187AH1-678 GEN
50/50
2.277
315242AE2-183_GT2
50/50
1.235
315241AE2-183_GT1
50/50
1.23
972185AH1-677 GEN
50/50
4.459
3151261ROARAP2
50/50
0.086
3146776BUCKING
Solar/Wind Harmer
1.442
3146776BUCKING
Solar/Wind Harmer
0.117
316336AC2-165 C
Solar/Wind Harmer
14.292
316313AB2-026
Solar/Wind Harmer
0.153
970301AG2-198 GEN
Solar/Wind Harmer
9.368
958211AF2-115 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.152
970323AG2-213 GEN
Solar/Wind Harmer
6.901
971223AH1-071 GEN
Solar/Wind Harmer
1.171
970099AG2-077 GEN
Solar/Wind Harmer
11.307
962561AG1-105 GEN
Solar/Wind Harmer
4.967
964791AG1-342 GEN
Solar/Wind Harmer
1.927
3146843MT LREL
Solar/Wind Harmer
0.1
3146843MT LREL
Solar/Wind Harmer
0.1
316118AC1-105 GEN
Solar/Wind Harmer
0.238
3143526WINTERP
Solar/Wind Harmer
0.473
970933AG2-581 GEN
Solar/Wind Harmer
7.1
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.089
3145783HORNRTN
Solar/Wind Harmer
1.252
3145783HORNRTN
Solar/Wind Harmer
1.001
3145783HORNRTN
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
0.125
316365GEN2_N
Solar/Wind Harmer
0.149
3144356SAPONY
Solar/Wind Harmer
0.553
316315AB2-025 C
Solar/Wind Harmer
0.053
962571AG1-106 GEN
Solar/Wind Harmer
0.922
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.039
3145893MURPHYS
Solar/Wind Harmer
0.431
3145893MURPHYS
Solar/Wind Harmer
0.116
3145796HORNRTN
Solar/Wind Harmer
0.192
3146173TUNIS
Solar/Wind Harmer
0.063
3146173TUNIS
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.022
315742AE1-103 GEN
Solar/Wind Harmer
0.922
315724AD1-057 GEN
Solar/Wind Harmer
1.175
316065AD1-022 GEN
Solar/Wind Harmer
2.754
315614AA2-178 GEN
Solar/Wind Harmer
0.337
316049AB1-081 GEN
Solar/Wind Harmer
0.335
316263AC1-034 GEN
Solar/Wind Harmer
2.24
316349AD2-085 GEN
Solar/Wind Harmer
0.039
3146376EDENTON
Solar/Wind Harmer
0.262
3146376EDENTON
Solar/Wind Harmer
0.262
315835AF2-110_GEN
Solar/Wind Harmer
0.404
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
1.041
3146386ELIZ CT
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.135
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
3130086AYDLETT
Solar/Wind Harmer
0.233
3145933PARMELE
Solar/Wind Harmer
0.116
3145933PARMELE
Solar/Wind Harmer
0.058
3137176SLIGO L2192
Solar/Wind Harmer
0.231
3146456SLIGO L269
Solar/Wind Harmer
1.029
316339AD2-160 GEN
Solar/Wind Harmer
0.093
316388AE2-253 GEN
Solar/Wind Harmer
0.181
3145506HICKORY
Solar/Wind Harmer
0.232
3145506HICKORY
Solar/Wind Harmer
0.139
3145506HICKORY
Solar/Wind Harmer
0.035
316005AA1-067
Solar/Wind Harmer
0.062
3150991CHESPKB
Adder
0.605
3150991CHESPKB
Adder
0.591
942751AE2-291 GEN
Solar/Wind Harmer
3.112
316294AC1-161 GEN
Solar/Wind Harmer
0.982
944641AF1-129 GEN
Adder
26.869
966001AG1-469 GEN
Solar/Wind Helper
0.199
972205AH1-687 GEN
50/50
20.476
316303AF2-085
50/50
1.951
3151541CLOVER2
50/50
2.251
3151601KERR 3
50/50
0.203
3151611KERR 4
50/50
0.203
3151621KERR 5
50/50
0.203
3151631KERR 6
50/50
0.203
963041AG1-153 GEN
50/50
2.01
315244AE2-183_ST
50/50
2.141
3151281ROARAP4
50/50
0.08
971285AH1-108 GEN
50/50
0.547
315779AE2-040
50/50
0.923
971845AH1-439 GEN
Solar/Wind Harmer
16.07
316258AE1-075 C
Solar/Wind Harmer
0.184
946301AF1-294 GEN
Solar/Wind Harmer
3.892
961791AG1-021 GEN
Solar/Wind Harmer
1.893
3144303KENBRDG
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
9.017
970681AG2-440 GEN
Solar/Wind Harmer
5.985
316486AD2-202 GEN
Solar/Wind Harmer
0.107
316233AE1-074 FULL
Solar/Wind Harmer
0.073
971281AH1-106 GEN
Solar/Wind Harmer
1.262
971283AH1-107 GEN
Solar/Wind Harmer
1.262
970831AG2-522 GEN
Solar/Wind Harmer
3.731
3147173SINAI
Solar/Wind Harmer
0.086
3147243WELCO
Solar/Wind Harmer
0.054
971967AH1-528 GEN
Solar/Wind Harmer
13.172
970673AG2-436 GEN
Solar/Wind Harmer
9.233
970533AG2-339 GEN
Solar/Wind Harmer
5.573
3137643SOCKMAN
Solar/Wind Harmer
0.289
970085AG2-068 GEN
Solar/Wind Harmer
3.824
970581AG2-369 GEN
Solar/Wind Harmer
3.288
316426AA2-053 GEN
Solar/Wind Harmer
0.234
3146043SEABORD
Solar/Wind Harmer
0.069
315814AE2-033 C
Solar/Wind Harmer
5.236
315652AC1-086 GEN
Solar/Wind Harmer
7.126
316274AC1-208 GEN
Solar/Wind Harmer
0.334
3145893MURPHYS
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.204
3145796HORNRTN
Solar/Wind Harmer
0.026
316210AC1-098 GEN
Solar/Wind Harmer
0.589
3146033SCOT NK
Solar/Wind Harmer
0.253
316463AE2-346 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
0.132
3145513AHOSKIE
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.125
3145683EARLEYS
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
0.062
316327AA2-057 GEN
Solar/Wind Harmer
0.092
3146206CASHIE
Solar/Wind Harmer
0.06
970601AG2-382 GEN
Solar/Wind Harmer
2.24
315732AD1-074 GEN1
Solar/Wind Harmer
0.338
315733AD1-074 GEN2
Solar/Wind Harmer
0.338
3130546PLYMOUTH
Solar/Wind Harmer
0.059
3143316POE
Solar/Wind Harmer
0.234
970657AG2-426 GEN
Solar/Wind Harmer
0.433
316311AC2-079 GEN
Solar/Wind Harmer
1.692
3130156CHOWAN
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.059
3146486SUNBURY
Solar/Wind Harmer
0.058
3146486SUNBURY
Solar/Wind Harmer
0.058
3145176PASQUOTANK
Solar/Wind Harmer
0.036
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3146406KITTY HAWK
Solar/Wind Harmer
0.007
957871AF2-081 GEN
Solar/Wind Harmer
2.894
957861AF2-080 GEN
Solar/Wind Harmer
2.505
316316AC1-027 C
Solar/Wind Harmer
0.055
3145746EVERETS
Solar/Wind Harmer
0.23
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151081ELIZAR1
Adder
5.3
3151091ELIZAR2
Adder
5.208
971445AH1-216 GEN
Solar/Wind Harmer
3.978
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.079
3148013FISHERV
Solar/Wind Helper
0.076
3148463FAIRFLD
Solar/Wind Helper
0.12
315616AA1-038_C
Solar/Wind Helper
0.544
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.173
MECLTFEXP_MEC->PJM
CLTF
0.182
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.819
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.496
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.033
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
1.45
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.449
TVALTFEXP_TVA->PJM
CLTF
0.709
NYPJM->LTFIMP_NY
CLTF
0.464

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:676.22
MW Contribution:
2.78
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.77 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:898.46
MW Contribution:
2.81
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.184
3151911BEARGRDN G1
50/50
5.56
3144293JTRSVLE
50/50
0.584
3144293JTRSVLE
50/50
0.461
3151531CLOVER1
50/50
2.075
3151921BEARGRDN G2
50/50
5.56
3144293JTRSVLE
50/50
0.584
970413AG2-270 GEN
50/50
9.039
972003AH1-546 GEN
Solar/Wind Harmer
20.231
970221AG2-151 GEN
Solar/Wind Harmer
28.409
3146776BUCKING
Solar/Wind Harmer
0.168
270494AE1-108_GEN
Solar/Wind Harmer
4.971
3146926FARMVIL
Solar/Wind Harmer
0.215
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.689
970257AG2-171 GEN
Solar/Wind Harmer
5.754
971775AH1-396 GEN
Solar/Wind Harmer
0.288
958131AF2-107 GEN
Solar/Wind Harmer
4.68
959311AF2-222 GEN
Solar/Wind Harmer
13.458
964241AG1-285 GEN
Solar/Wind Harmer
8.766
316478AD1-087 GEN
Solar/Wind Harmer
0.335
3147043LAWRENC
Solar/Wind Harmer
0.044
971683AH1-343 GEN
Solar/Wind Harmer
2.624
316123AC1-075 GEN
Solar/Wind Harmer
0.082
972205AH1-687 GEN
50/50
27.167
3151541CLOVER2
50/50
2.06
3151601KERR 3
50/50
0.188
3151611KERR 4
50/50
0.188
3151621KERR 5
50/50
0.188
3151631KERR 6
50/50
0.188
971845AH1-439 GEN
Solar/Wind Harmer
20.749
946301AF1-294 GEN
Solar/Wind Harmer
4.549
961791AG1-021 GEN
Solar/Wind Harmer
2.213
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
9.617
970681AG2-440 GEN
Solar/Wind Harmer
6.383
316486AD2-202 GEN
Solar/Wind Harmer
0.098
3147173SINAI
Solar/Wind Harmer
0.08
3147243WELCO
Solar/Wind Harmer
0.05
970831AG2-522 GEN
Solar/Wind Harmer
3.162
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151591KERR 2
50/50
0.188
3151641KERR 7
50/50
0.188
3147043LAWRENC
50/50
0.708
970937AG2-583 GEN
Solar/Wind Harmer
36.756
971377AH1-170 GEN
Solar/Wind Harmer
5.682
3147623JAMES R
Solar/Wind Harmer
1.234
3146776BUCKING
Solar/Wind Harmer
0.187
3146926FARMVIL
Solar/Wind Harmer
0.215
971563AH1-280 GEN
Solar/Wind Harmer
2.459
970685AG2-442 GEN
Solar/Wind Harmer
13.128
315785AD2-033 C
Solar/Wind Harmer
1.371
316034AC1-036 C
Solar/Wind Harmer
0.01
315693AD1-088 GEN
Solar/Wind Harmer
6.208
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970401AG2-262 GEN
Solar/Wind Harmer
0.57
957481AF2-042 GEN
Solar/Wind Harmer
25.123
971065AG2-659 GEN
Solar/Wind Harmer
3.402
316129AC1-054 GEN
Solar/Wind Harmer
0.289
962751AG1-124 GEN
Solar/Wind Harmer
2.837
970909AG2-566 GEN
50/50
2.783
3144293JTRSVLE
50/50
0.584
970535AG2-341 GEN
50/50
1.879
3151581KERR 1
50/50
0.067
3152661PLYWOOD A
50/50
0.188
316336AC2-165 C
Solar/Wind Harmer
30.363
3146776BUCKING
Solar/Wind Harmer
1.867
3146776BUCKING
Solar/Wind Harmer
0.151
970301AG2-198 GEN
Solar/Wind Harmer
11.132
958211AF2-115 GEN
Solar/Wind Harmer
2.766
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
970323AG2-213 GEN
Solar/Wind Harmer
7.672
962561AG1-105 GEN
Solar/Wind Harmer
4.838
964791AG1-342 GEN
Solar/Wind Harmer
1.864
3146843MT LREL
Solar/Wind Harmer
0.097
3146843MT LREL
Solar/Wind Harmer
0.097
970099AG2-077 GEN
Solar/Wind Harmer
10.049
316118AC1-105 GEN
Solar/Wind Harmer
0.226
970933AG2-581 GEN
Solar/Wind Harmer
5.128
942751AE2-291 GEN
Solar/Wind Harmer
3.108
966001AG1-469 GEN
Solar/Wind Helper
0.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.743
MECLTFEXP_MEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
2.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.492
LAGNLTFEXP_LAGN->PJM
CLTF
1.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.485
TVALTFEXP_TVA->PJM
CLTF
0.56
NYPJM->LTFIMP_NY
CLTF
0.403
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.97 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:732.8
MW Contribution:
0.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.08 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:794.6
MW Contribution:
0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3151261ROARAP2
50/50
0.32
3144293JTRSVLE
50/50
0.217
970413AG2-270 GEN
50/50
7.462
316011AB1-132 GEN
Solar/Wind Harmer
6.264
316181AB2-040 GEN
Solar/Wind Harmer
0.488
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.288
3145796HORNRTN
Solar/Wind Harmer
0.322
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
315722AD1-056 GEN
Solar/Wind Harmer
8.499
316212AC1-099_GEN
Solar/Wind Harmer
1.032
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.939
3146233WITAKRS
Solar/Wind Harmer
0.127
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.05
3145823KELFORD
Solar/Wind Harmer
0.181
971623AH1-311 GEN
Solar/Wind Harmer
0.36
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
3146073TAR RVR
Solar/Wind Harmer
0.168
3146083TARBORO
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.276
3145893MURPHYS
Solar/Wind Harmer
0.165
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145933PARMELE
Solar/Wind Harmer
0.135
3146206CASHIE
Solar/Wind Harmer
0.127
3145963POPLR C
Solar/Wind Harmer
0.122
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
970257AG2-171 GEN
Solar/Wind Harmer
3.241
971775AH1-396 GEN
Solar/Wind Harmer
0.162
964241AG1-285 GEN
Solar/Wind Harmer
6.48
959311AF2-222 GEN
Solar/Wind Harmer
7.79
316478AD1-087 GEN
Solar/Wind Harmer
0.277
3147133PAMPLIN
Solar/Wind Harmer
0.233
971683AH1-343 GEN
Solar/Wind Harmer
2.412
942461AE2-259 GEN
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
0.06
316222AC1-221 GEN
Solar/Wind Harmer
0.246
316283AC2-100 C
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.043
3151361ROSEMG1
50/50
1.16
3151371ROSEMS1
50/50
0.719
3151381ROSEMG2
50/50
0.543
3151261ROARAP2
50/50
0.313
3151581KERR 1
50/50
0.094
970535AG2-341 GEN
50/50
2.22
3152661PLYWOOD A
50/50
0.19
3144293JTRSVLE
50/50
0.217
970909AG2-566 GEN
50/50
0.672
316365GEN2_N
Solar/Wind Harmer
1.159
962571AG1-106 GEN
Solar/Wind Harmer
4.914
313506AB2-031 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
0.966
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
4.494
3145783HORNRTN
Solar/Wind Harmer
3.595
3145783HORNRTN
Solar/Wind Harmer
1.123
3145783HORNRTN
Solar/Wind Harmer
0.449
315724AD1-057 GEN
Solar/Wind Harmer
4.741
961601AG1-000A GEN
Solar/Wind Harmer
3.263
316049AB1-081 GEN
Solar/Wind Harmer
1.023
316263AC1-034 GEN
Solar/Wind Harmer
6.835
316140AB2-099
Solar/Wind Harmer
0.06
3145493TOT1
Solar/Wind Harmer
0.39
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
3146173TUNIS
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
1.103
3145893MURPHYS
Solar/Wind Harmer
0.296
316005AA1-067
Solar/Wind Harmer
0.151
3145933PARMELE
Solar/Wind Harmer
0.27
3145933PARMELE
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
5.506
970323AG2-213 GEN
Solar/Wind Harmer
4.321
962561AG1-105 GEN
Solar/Wind Harmer
4.722
964791AG1-342 GEN
Solar/Wind Harmer
1.815
3146843MT LREL
Solar/Wind Harmer
0.094
3146843MT LREL
Solar/Wind Harmer
0.094
958211AF2-115 GEN
Solar/Wind Harmer
1.026
316118AC1-105 GEN
Solar/Wind Harmer
0.219
315614AA2-178 GEN
Solar/Wind Harmer
0.481
970099AG2-077 GEN
Solar/Wind Harmer
8.585
315742AE1-103 GEN
Solar/Wind Harmer
1.165
3147133PAMPLIN
Solar/Wind Harmer
0.074
3147133PAMPLIN
Solar/Wind Harmer
0.059
970301AG2-198 GEN
Solar/Wind Harmer
2.687
3146376EDENTON
Solar/Wind Harmer
0.268
3146376EDENTON
Solar/Wind Harmer
0.268
3144356SAPONY
Solar/Wind Helper
0.935
316315AB2-025 C
Solar/Wind Helper
0.796
3151281ROARAP4
50/50
0.291
3151601KERR 3
50/50
0.265
3151611KERR 4
50/50
0.265
3151621KERR 5
50/50
0.265
3151631KERR 6
50/50
0.265
3151151S HAMPT1
50/50
0.295
3151541CLOVER2
50/50
1.701
315652AC1-086 GEN
Solar/Wind Harmer
37.99
3145796HORNRTN
Solar/Wind Harmer
1.03
3145796HORNRTN
Solar/Wind Harmer
0.129
3137643SOCKMAN
Solar/Wind Harmer
1.19
316426AA2-053 GEN
Solar/Wind Harmer
0.818
3146043SEABORD
Solar/Wind Harmer
0.215
316274AC1-208 GEN
Solar/Wind Harmer
1.093
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316327AA2-057 GEN
Solar/Wind Harmer
0.288
3146033SCOT NK
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
7.902
3145683EARLEYS
Solar/Wind Harmer
0.342
3145683EARLEYS
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
0.171
316463AE2-346 GEN
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.355
3145513AHOSKIE
Solar/Wind Harmer
0.169
3145573BETHELC
Solar/Wind Harmer
0.168
3145573BETHELC
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.445
3145893MURPHYS
Solar/Wind Harmer
0.165
957861AF2-080 GEN
Solar/Wind Harmer
6.72
3145746EVERETS
Solar/Wind Harmer
0.562
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.127
970601AG2-382 GEN
Solar/Wind Harmer
4.745
315732AD1-074 GEN1
Solar/Wind Harmer
0.606
315733AD1-074 GEN2
Solar/Wind Harmer
0.606
3130546PLYMOUTH
Solar/Wind Harmer
0.103
3144303KENBRDG
Solar/Wind Harmer
0.081
946301AF1-294 GEN
Solar/Wind Harmer
1.687
961791AG1-021 GEN
Solar/Wind Harmer
0.821
970683AG2-441 GEN
Solar/Wind Harmer
5.044
970681AG2-440 GEN
Solar/Wind Harmer
3.348
316486AD2-202 GEN
Solar/Wind Harmer
0.081
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
3130156CHOWAN
Solar/Wind Harmer
0.06
3130156CHOWAN
Solar/Wind Harmer
0.06
315839AE2-212 C
Solar/Wind Helper
0.175
3143316POE
Solar/Wind Helper
0.502
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3147043LAWRENC
50/50
3.131
3151281ROARAP4
50/50
0.311
3151591KERR 2
50/50
0.265
3151641KERR 7
50/50
0.265
3144293JTRSVLE
50/50
0.217
3144293JTRSVLE
50/50
0.171
3151531CLOVER1
50/50
1.713
316023GEN1_S
Solar/Wind Harmer
1.159
960081AF2-299 GEN
Solar/Wind Harmer
3.999
3145796HORNRTN
Solar/Wind Harmer
1.062
3145796HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.446
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.744
3145823KELFORD
Solar/Wind Harmer
0.181
316359AB2-059 GEN
Solar/Wind Harmer
0.64
3142053HEARTS
Solar/Wind Harmer
0.317
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.143
316129AC1-054 GEN
Solar/Wind Harmer
0.654
3145683EARLEYS
Solar/Wind Harmer
0.171
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.168
3145493TOT1
Solar/Wind Harmer
0.748
3146173TUNIS
Solar/Wind Harmer
0.168
971065AG2-659 GEN
Solar/Wind Harmer
7.153
3145893MURPHYS
Solar/Wind Harmer
0.659
3145893MURPHYS
Solar/Wind Harmer
0.732
3156021HOLLOMANSOL
Solar/Wind Harmer
0.704
316494AC1-189 GEN
Solar/Wind Harmer
0.527
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146293MARTNCO
Solar/Wind Harmer
0.125
3146206CASHIE
Solar/Wind Harmer
0.127
971547AH1-271 GEN
Solar/Wind Harmer
2.711
3145963POPLR C
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.368
315737AD1-076 GEN
Solar/Wind Harmer
1.366
315785AD2-033 C
Solar/Wind Harmer
0.845
970401AG2-262 GEN
Solar/Wind Harmer
0.555
316034AC1-036 C
Solar/Wind Harmer
0.006
971563AH1-280 GEN
Solar/Wind Harmer
0.912
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3145663CRESWEL
Solar/Wind Harmer
0.237
971163AH1-040 GEN
Solar/Wind Harmer
6.763
315693AD1-088 GEN
Solar/Wind Harmer
3.903
970685AG2-442 GEN
Solar/Wind Harmer
6.061
957481AF2-042 GEN
Solar/Wind Harmer
21.462
3130156CHOWAN
Solar/Wind Harmer
0.06
315671AE2-027_GEN
Solar/Wind Helper
0.949
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.588
MECLTFEXP_MEC->PJM
CLTF
0.854
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
4.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.63
LAGNLTFEXP_LAGN->PJM
CLTF
2.181
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.5
TVALTFEXP_TVA->PJM
CLTF
1.078
NYPJM->LTFIMP_NY
CLTF
0.358
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.141

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.69 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:730.84
MW Contribution:
0.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.44 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:790.28
MW Contribution:
0.61
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3151261ROARAP2
50/50
0.32
3144293JTRSVLE
50/50
0.217
970413AG2-270 GEN
50/50
7.462
316011AB1-132 GEN
Solar/Wind Harmer
6.264
316181AB2-040 GEN
Solar/Wind Harmer
0.488
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.288
3145796HORNRTN
Solar/Wind Harmer
0.322
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
315722AD1-056 GEN
Solar/Wind Harmer
8.499
316212AC1-099_GEN
Solar/Wind Harmer
1.032
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.939
3146233WITAKRS
Solar/Wind Harmer
0.127
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.05
3145823KELFORD
Solar/Wind Harmer
0.181
971623AH1-311 GEN
Solar/Wind Harmer
0.36
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
3146073TAR RVR
Solar/Wind Harmer
0.168
3146083TARBORO
Solar/Wind Harmer
0.168
3151361ROSEMG1
50/50
1.16
3151371ROSEMS1
50/50
0.719
3151381ROSEMG2
50/50
0.543
3151261ROARAP2
50/50
0.313
3151581KERR 1
50/50
0.094
970535AG2-341 GEN
50/50
2.22
3152661PLYWOOD A
50/50
0.19
3144293JTRSVLE
50/50
0.217
970909AG2-566 GEN
50/50
0.672
316365GEN2_N
Solar/Wind Harmer
1.159
962571AG1-106 GEN
Solar/Wind Harmer
4.914
313506AB2-031 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
0.966
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.32
3142666NORTHAMPTON
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
4.494
3145783HORNRTN
Solar/Wind Harmer
3.595
3145783HORNRTN
Solar/Wind Harmer
1.123
3145783HORNRTN
Solar/Wind Harmer
0.449
315724AD1-057 GEN
Solar/Wind Harmer
4.741
961601AG1-000A GEN
Solar/Wind Harmer
3.263
316049AB1-081 GEN
Solar/Wind Harmer
1.023
316263AC1-034 GEN
Solar/Wind Harmer
6.835
316140AB2-099
Solar/Wind Harmer
0.06
3145493TOT1
Solar/Wind Harmer
0.39
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
3146173TUNIS
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3151281ROARAP4
50/50
0.291
3151601KERR 3
50/50
0.265
3151611KERR 4
50/50
0.265
3151621KERR 5
50/50
0.265
3151631KERR 6
50/50
0.265
3151151S HAMPT1
50/50
0.295
3151541CLOVER2
50/50
1.701
315652AC1-086 GEN
Solar/Wind Harmer
37.99
3145796HORNRTN
Solar/Wind Harmer
1.03
3145796HORNRTN
Solar/Wind Harmer
0.129
3137643SOCKMAN
Solar/Wind Harmer
1.19
316426AA2-053 GEN
Solar/Wind Harmer
0.818
3146043SEABORD
Solar/Wind Harmer
0.215
316274AC1-208 GEN
Solar/Wind Harmer
1.093
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316327AA2-057 GEN
Solar/Wind Harmer
0.288
3146033SCOT NK
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
7.902
3145683EARLEYS
Solar/Wind Harmer
0.342
3145683EARLEYS
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
0.171
316463AE2-346 GEN
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.355
3145513AHOSKIE
Solar/Wind Harmer
0.169
3145573BETHELC
Solar/Wind Harmer
0.168
3145573BETHELC
Solar/Wind Harmer
0.168
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3147043LAWRENC
50/50
3.131
3151281ROARAP4
50/50
0.311
3151591KERR 2
50/50
0.265
3151641KERR 7
50/50
0.265
3144293JTRSVLE
50/50
0.217
3144293JTRSVLE
50/50
0.171
3151531CLOVER1
50/50
1.713
316023GEN1_S
Solar/Wind Harmer
1.159
960081AF2-299 GEN
Solar/Wind Harmer
3.999
3145796HORNRTN
Solar/Wind Harmer
1.062
3145796HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.446
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.744
3145823KELFORD
Solar/Wind Harmer
0.181
316359AB2-059 GEN
Solar/Wind Harmer
0.64
3142053HEARTS
Solar/Wind Harmer
0.317
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.143
316129AC1-054 GEN
Solar/Wind Harmer
0.654
3145683EARLEYS
Solar/Wind Harmer
0.171
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.168
3145493TOT1
Solar/Wind Harmer
0.748
3146173TUNIS
Solar/Wind Harmer
0.168
971065AG2-659 GEN
Solar/Wind Harmer
7.153
3145893MURPHYS
Solar/Wind Harmer
0.659
3145893MURPHYS
Solar/Wind Harmer
0.732
3156021HOLLOMANSOL
Solar/Wind Harmer
0.704
316494AC1-189 GEN
Solar/Wind Harmer
0.527
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146293MARTNCO
Solar/Wind Harmer
0.125
3146206CASHIE
Solar/Wind Harmer
0.127
971547AH1-271 GEN
Solar/Wind Harmer
2.711
3145963POPLR C
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.368
315737AD1-076 GEN
Solar/Wind Harmer
1.366
315785AD2-033 C
Solar/Wind Harmer
0.845
970401AG2-262 GEN
Solar/Wind Harmer
0.555
316034AC1-036 C
Solar/Wind Harmer
0.006
971563AH1-280 GEN
Solar/Wind Harmer
0.912
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3145663CRESWEL
Solar/Wind Harmer
0.237
971163AH1-040 GEN
Solar/Wind Harmer
6.763
315693AD1-088 GEN
Solar/Wind Harmer
3.903
970685AG2-442 GEN
Solar/Wind Harmer
6.061
957481AF2-042 GEN
Solar/Wind Harmer
21.462
3130156CHOWAN
Solar/Wind Harmer
0.06
315671AE2-027_GEN
Solar/Wind Helper
0.949
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.276
3145893MURPHYS
Solar/Wind Harmer
0.165
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145933PARMELE
Solar/Wind Harmer
0.135
3146206CASHIE
Solar/Wind Harmer
0.127
3145963POPLR C
Solar/Wind Harmer
0.122
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
970257AG2-171 GEN
Solar/Wind Harmer
3.241
971775AH1-396 GEN
Solar/Wind Harmer
0.162
964241AG1-285 GEN
Solar/Wind Harmer
6.48
959311AF2-222 GEN
Solar/Wind Harmer
7.79
316478AD1-087 GEN
Solar/Wind Harmer
0.277
3147133PAMPLIN
Solar/Wind Harmer
0.233
971683AH1-343 GEN
Solar/Wind Harmer
2.412
942461AE2-259 GEN
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
0.06
316222AC1-221 GEN
Solar/Wind Harmer
0.246
316283AC2-100 C
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.043
3145893MURPHYS
Solar/Wind Harmer
0.445
3145893MURPHYS
Solar/Wind Harmer
0.165
957861AF2-080 GEN
Solar/Wind Harmer
6.72
3145746EVERETS
Solar/Wind Harmer
0.562
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.127
970601AG2-382 GEN
Solar/Wind Harmer
4.745
315732AD1-074 GEN1
Solar/Wind Harmer
0.606
315733AD1-074 GEN2
Solar/Wind Harmer
0.606
3130546PLYMOUTH
Solar/Wind Harmer
0.103
3144303KENBRDG
Solar/Wind Harmer
0.081
946301AF1-294 GEN
Solar/Wind Harmer
1.687
961791AG1-021 GEN
Solar/Wind Harmer
0.821
970683AG2-441 GEN
Solar/Wind Harmer
5.044
970681AG2-440 GEN
Solar/Wind Harmer
3.348
971967AH1-528 GEN
Solar/Wind Harmer
12.902
316486AD2-202 GEN
Solar/Wind Harmer
0.081
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
3130156CHOWAN
Solar/Wind Harmer
0.06
3130156CHOWAN
Solar/Wind Harmer
0.06
315839AE2-212 C
Solar/Wind Helper
0.175
3143316POE
Solar/Wind Helper
0.502
3145893MURPHYS
Solar/Wind Harmer
1.103
3145893MURPHYS
Solar/Wind Harmer
0.296
316005AA1-067
Solar/Wind Harmer
0.151
3145933PARMELE
Solar/Wind Harmer
0.27
3145933PARMELE
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
5.506
970323AG2-213 GEN
Solar/Wind Harmer
4.321
962561AG1-105 GEN
Solar/Wind Harmer
4.722
964791AG1-342 GEN
Solar/Wind Harmer
1.815
3146843MT LREL
Solar/Wind Harmer
0.094
3146843MT LREL
Solar/Wind Harmer
0.094
958211AF2-115 GEN
Solar/Wind Harmer
1.026
316118AC1-105 GEN
Solar/Wind Harmer
0.219
315614AA2-178 GEN
Solar/Wind Harmer
0.481
970933AG2-581 GEN
Solar/Wind Harmer
6.451
970099AG2-077 GEN
Solar/Wind Harmer
8.585
315742AE1-103 GEN
Solar/Wind Harmer
1.165
3147133PAMPLIN
Solar/Wind Harmer
0.074
3147133PAMPLIN
Solar/Wind Harmer
0.059
970301AG2-198 GEN
Solar/Wind Harmer
2.687
3146376EDENTON
Solar/Wind Harmer
0.268
3146376EDENTON
Solar/Wind Harmer
0.268
3144356SAPONY
Solar/Wind Helper
0.935
316315AB2-025 C
Solar/Wind Helper
0.796
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.588
MECLTFEXP_MEC->PJM
CLTF
0.854
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
4.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.63
LAGNLTFEXP_LAGN->PJM
CLTF
2.181
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.5
TVALTFEXP_TVA->PJM
CLTF
1.078
NYPJM->LTFIMP_NY
CLTF
0.358
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.141

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.66 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:825.69
MW Contribution:
0.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.64 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:886.64
MW Contribution:
0.6
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3151261ROARAP2
50/50
0.32
3144293JTRSVLE
50/50
0.216
970413AG2-270 GEN
50/50
7.448
316011AB1-132 GEN
Solar/Wind Harmer
6.262
316181AB2-040 GEN
Solar/Wind Harmer
0.488
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.287
3145796HORNRTN
Solar/Wind Harmer
0.322
3142666NORTHAMPTON
Solar/Wind Harmer
0.319
315722AD1-056 GEN
Solar/Wind Harmer
8.494
316212AC1-099_GEN
Solar/Wind Harmer
1.031
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.938
3146233WITAKRS
Solar/Wind Harmer
0.127
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.04
3145823KELFORD
Solar/Wind Harmer
0.181
971623AH1-311 GEN
Solar/Wind Harmer
0.359
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
3146073TAR RVR
Solar/Wind Harmer
0.168
3146083TARBORO
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.275
3145893MURPHYS
Solar/Wind Harmer
0.165
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145933PARMELE
Solar/Wind Harmer
0.135
3146206CASHIE
Solar/Wind Harmer
0.127
3145963POPLR C
Solar/Wind Harmer
0.122
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
970257AG2-171 GEN
Solar/Wind Harmer
3.236
971775AH1-396 GEN
Solar/Wind Harmer
0.162
964241AG1-285 GEN
Solar/Wind Harmer
6.47
959311AF2-222 GEN
Solar/Wind Harmer
7.776
316478AD1-087 GEN
Solar/Wind Harmer
0.276
3147133PAMPLIN
Solar/Wind Harmer
0.233
971683AH1-343 GEN
Solar/Wind Harmer
2.407
942461AE2-259 GEN
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
0.06
316222AC1-221 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.043
3151361ROSEMG1
50/50
1.16
3151371ROSEMS1
50/50
0.718
3151381ROSEMG2
50/50
0.543
3151261ROARAP2
50/50
0.313
3151581KERR 1
50/50
0.094
970535AG2-341 GEN
50/50
2.217
3152661PLYWOOD A
50/50
0.19
3144293JTRSVLE
50/50
0.216
970909AG2-566 GEN
50/50
0.67
3144356SAPONY
Solar/Wind Harmer
7.203
316315AB2-025 C
Solar/Wind Harmer
0.689
316365GEN2_N
Solar/Wind Harmer
1.159
962571AG1-106 GEN
Solar/Wind Harmer
4.912
313506AB2-031 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
0.965
3142666NORTHAMPTON
Solar/Wind Harmer
0.319
3142666NORTHAMPTON
Solar/Wind Harmer
0.319
3142666NORTHAMPTON
Solar/Wind Harmer
0.319
3142666NORTHAMPTON
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
4.491
3145783HORNRTN
Solar/Wind Harmer
3.593
3145783HORNRTN
Solar/Wind Harmer
1.123
3145783HORNRTN
Solar/Wind Harmer
0.449
315724AD1-057 GEN
Solar/Wind Harmer
4.738
961601AG1-000A GEN
Solar/Wind Harmer
3.26
316049AB1-081 GEN
Solar/Wind Harmer
1.022
316263AC1-034 GEN
Solar/Wind Harmer
6.83
316140AB2-099
Solar/Wind Harmer
0.06
3145493TOT1
Solar/Wind Harmer
0.39
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
3146173TUNIS
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
1.102
3145893MURPHYS
Solar/Wind Harmer
0.296
316005AA1-067
Solar/Wind Harmer
0.151
3145933PARMELE
Solar/Wind Harmer
0.27
3145933PARMELE
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
5.499
970323AG2-213 GEN
Solar/Wind Harmer
4.315
962561AG1-105 GEN
Solar/Wind Harmer
4.714
964791AG1-342 GEN
Solar/Wind Harmer
1.813
3146843MT LREL
Solar/Wind Harmer
0.094
3146843MT LREL
Solar/Wind Harmer
0.094
958211AF2-115 GEN
Solar/Wind Harmer
1.024
316118AC1-105 GEN
Solar/Wind Harmer
0.218
315614AA2-178 GEN
Solar/Wind Harmer
0.48
970099AG2-077 GEN
Solar/Wind Harmer
8.569
315742AE1-103 GEN
Solar/Wind Harmer
1.163
3147133PAMPLIN
Solar/Wind Harmer
0.074
3147133PAMPLIN
Solar/Wind Harmer
0.059
970301AG2-198 GEN
Solar/Wind Harmer
2.681
3146376EDENTON
Solar/Wind Harmer
0.267
3146376EDENTON
Solar/Wind Harmer
0.267
315779AE2-040
50/50
12.021
3151281ROARAP4
50/50
0.291
3151601KERR 3
50/50
0.264
3151611KERR 4
50/50
0.264
3151621KERR 5
50/50
0.264
3151631KERR 6
50/50
0.264
3151151S HAMPT1
50/50
0.295
3151541CLOVER2
50/50
1.698
315814AE2-033 C
Solar/Wind Harmer
66.719
315652AC1-086 GEN
Solar/Wind Harmer
37.974
3145796HORNRTN
Solar/Wind Harmer
1.03
3145796HORNRTN
Solar/Wind Harmer
0.129
3137643SOCKMAN
Solar/Wind Harmer
1.19
316426AA2-053 GEN
Solar/Wind Harmer
0.817
3146043SEABORD
Solar/Wind Harmer
0.215
316274AC1-208 GEN
Solar/Wind Harmer
1.092
316210AC1-098 GEN
Solar/Wind Harmer
1.848
316327AA2-057 GEN
Solar/Wind Harmer
0.288
3146033SCOT NK
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
7.895
3145683EARLEYS
Solar/Wind Harmer
0.342
3145683EARLEYS
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
0.171
316463AE2-346 GEN
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.354
3145513AHOSKIE
Solar/Wind Harmer
0.169
3145573BETHELC
Solar/Wind Harmer
0.168
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3147043LAWRENC
50/50
3.13
3151281ROARAP4
50/50
0.311
3151591KERR 2
50/50
0.264
3151641KERR 7
50/50
0.264
3144293JTRSVLE
50/50
0.216
3144293JTRSVLE
50/50
0.171
3151531CLOVER1
50/50
1.71
316023GEN1_S
Solar/Wind Harmer
1.159
960081AF2-299 GEN
Solar/Wind Harmer
3.997
3145796HORNRTN
Solar/Wind Harmer
1.062
3145796HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.252
315607AA1-063A GEN
Solar/Wind Harmer
0.445
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.743
3145823KELFORD
Solar/Wind Harmer
0.181
316359AB2-059 GEN
Solar/Wind Harmer
0.639
3142053HEARTS
Solar/Wind Harmer
0.316
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.143
316129AC1-054 GEN
Solar/Wind Harmer
0.654
3145683EARLEYS
Solar/Wind Harmer
0.171
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.168
3145493TOT1
Solar/Wind Harmer
0.747
3146173TUNIS
Solar/Wind Harmer
0.168
971065AG2-659 GEN
Solar/Wind Harmer
7.147
3145893MURPHYS
Solar/Wind Harmer
0.658
3145893MURPHYS
Solar/Wind Harmer
0.732
3156021HOLLOMANSOL
Solar/Wind Harmer
0.703
316494AC1-189 GEN
Solar/Wind Harmer
0.526
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146293MARTNCO
Solar/Wind Harmer
0.125
3146206CASHIE
Solar/Wind Harmer
0.127
971547AH1-271 GEN
Solar/Wind Harmer
2.708
3145963POPLR C
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.367
315737AD1-076 GEN
Solar/Wind Harmer
1.365
315785AD2-033 C
Solar/Wind Harmer
0.844
970401AG2-262 GEN
Solar/Wind Harmer
0.554
316034AC1-036 C
Solar/Wind Harmer
0.006
971563AH1-280 GEN
Solar/Wind Harmer
0.91
315816AE2-034 GEN
Solar/Wind Harmer
0.36
3145663CRESWEL
Solar/Wind Harmer
0.236
971163AH1-040 GEN
Solar/Wind Harmer
6.751
315693AD1-088 GEN
Solar/Wind Harmer
3.896
970685AG2-442 GEN
Solar/Wind Harmer
6.05
957481AF2-042 GEN
Solar/Wind Harmer
21.422
3130156CHOWAN
Solar/Wind Harmer
0.06
315671AE2-027_GEN
Solar/Wind Helper
0.951
3145573BETHELC
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.444
3145893MURPHYS
Solar/Wind Harmer
0.165
957861AF2-080 GEN
Solar/Wind Harmer
6.714
3145746EVERETS
Solar/Wind Harmer
0.562
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.127
970601AG2-382 GEN
Solar/Wind Harmer
4.739
315732AD1-074 GEN1
Solar/Wind Harmer
0.605
315733AD1-074 GEN2
Solar/Wind Harmer
0.605
3130546PLYMOUTH
Solar/Wind Harmer
0.103
3144303KENBRDG
Solar/Wind Harmer
0.081
946301AF1-294 GEN
Solar/Wind Harmer
1.684
961791AG1-021 GEN
Solar/Wind Harmer
0.819
970683AG2-441 GEN
Solar/Wind Harmer
5.035
970681AG2-440 GEN
Solar/Wind Harmer
3.342
316486AD2-202 GEN
Solar/Wind Harmer
0.081
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
3130156CHOWAN
Solar/Wind Harmer
0.06
3130156CHOWAN
Solar/Wind Harmer
0.06
315839AE2-212 C
Solar/Wind Helper
0.176
3143316POE
Solar/Wind Helper
0.503
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.723
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.544
MECLTFEXP_MEC->PJM
CLTF
0.835
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
4.511
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.474
LAGNLTFEXP_LAGN->PJM
CLTF
2.158
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.465
TVALTFEXP_TVA->PJM
CLTF
1.066
NYPJM->LTFIMP_NY
CLTF
0.366
LGEELTFEXP_LGEE->PJM
CLTF
0.266
WECLTFEXP_WEC->PJM
CLTF
0.136

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.36 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:823.67
MW Contribution:
0.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.0 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:882.29
MW Contribution:
0.6
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.16
3151371ROSEMS1
50/50
0.718
3151381ROSEMG2
50/50
0.543
3151261ROARAP2
50/50
0.313
3151581KERR 1
50/50
0.094
970535AG2-341 GEN
50/50
2.217
3152661PLYWOOD A
50/50
0.19
3144293JTRSVLE
50/50
0.216
970909AG2-566 GEN
50/50
0.67
3144356SAPONY
Solar/Wind Harmer
7.203
316315AB2-025 C
Solar/Wind Harmer
0.689
316365GEN2_N
Solar/Wind Harmer
1.159
962571AG1-106 GEN
Solar/Wind Harmer
4.912
313506AB2-031 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
0.965
3142666NORTHAMPTON
Solar/Wind Harmer
0.319
3142666NORTHAMPTON
Solar/Wind Harmer
0.319
3142666NORTHAMPTON
Solar/Wind Harmer
0.319
3142666NORTHAMPTON
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.26
3145593CAROLNA
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
4.491
3145783HORNRTN
Solar/Wind Harmer
3.593
3145783HORNRTN
Solar/Wind Harmer
1.123
3145783HORNRTN
Solar/Wind Harmer
0.449
315724AD1-057 GEN
Solar/Wind Harmer
4.738
961601AG1-000A GEN
Solar/Wind Harmer
3.26
316049AB1-081 GEN
Solar/Wind Harmer
1.022
316263AC1-034 GEN
Solar/Wind Harmer
6.83
316140AB2-099
Solar/Wind Harmer
0.06
3145493TOT1
Solar/Wind Harmer
0.39
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
3146173TUNIS
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
1.102
3145893MURPHYS
Solar/Wind Harmer
0.296
316005AA1-067
Solar/Wind Harmer
0.151
3145933PARMELE
Solar/Wind Harmer
0.27
3145933PARMELE
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
5.499
970323AG2-213 GEN
Solar/Wind Harmer
4.315
962561AG1-105 GEN
Solar/Wind Harmer
4.714
964791AG1-342 GEN
Solar/Wind Harmer
1.813
3146843MT LREL
Solar/Wind Harmer
0.094
3146843MT LREL
Solar/Wind Harmer
0.094
958211AF2-115 GEN
Solar/Wind Harmer
1.024
316118AC1-105 GEN
Solar/Wind Harmer
0.218
315614AA2-178 GEN
Solar/Wind Harmer
0.48
970933AG2-581 GEN
Solar/Wind Harmer
6.439
970099AG2-077 GEN
Solar/Wind Harmer
8.569
315742AE1-103 GEN
Solar/Wind Harmer
1.163
3147133PAMPLIN
Solar/Wind Harmer
0.074
3147133PAMPLIN
Solar/Wind Harmer
0.059
970301AG2-198 GEN
Solar/Wind Harmer
2.681
3146376EDENTON
Solar/Wind Harmer
0.267
3146376EDENTON
Solar/Wind Harmer
0.267
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3151261ROARAP2
50/50
0.32
3144293JTRSVLE
50/50
0.216
970413AG2-270 GEN
50/50
7.448
316011AB1-132 GEN
Solar/Wind Harmer
6.262
316181AB2-040 GEN
Solar/Wind Harmer
0.488
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.287
3145796HORNRTN
Solar/Wind Harmer
0.322
3142666NORTHAMPTON
Solar/Wind Harmer
0.319
315722AD1-056 GEN
Solar/Wind Harmer
8.494
316212AC1-099_GEN
Solar/Wind Harmer
1.031
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.938
3146233WITAKRS
Solar/Wind Harmer
0.127
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.04
3145823KELFORD
Solar/Wind Harmer
0.181
971623AH1-311 GEN
Solar/Wind Harmer
0.359
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
3146073TAR RVR
Solar/Wind Harmer
0.168
3146083TARBORO
Solar/Wind Harmer
0.168
3146173TUNIS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.275
3145893MURPHYS
Solar/Wind Harmer
0.165
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145933PARMELE
Solar/Wind Harmer
0.135
3146206CASHIE
Solar/Wind Harmer
0.127
3145963POPLR C
Solar/Wind Harmer
0.122
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
970257AG2-171 GEN
Solar/Wind Harmer
3.236
971775AH1-396 GEN
Solar/Wind Harmer
0.162
964241AG1-285 GEN
Solar/Wind Harmer
6.47
959311AF2-222 GEN
Solar/Wind Harmer
7.776
316478AD1-087 GEN
Solar/Wind Harmer
0.276
3147133PAMPLIN
Solar/Wind Harmer
0.233
971683AH1-343 GEN
Solar/Wind Harmer
2.407
942461AE2-259 GEN
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
0.06
316222AC1-221 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.043
315779AE2-040
50/50
12.021
3151281ROARAP4
50/50
0.291
3151601KERR 3
50/50
0.264
3151611KERR 4
50/50
0.264
3151621KERR 5
50/50
0.264
3151631KERR 6
50/50
0.264
3151151S HAMPT1
50/50
0.295
3151541CLOVER2
50/50
1.698
315814AE2-033 C
Solar/Wind Harmer
66.719
315652AC1-086 GEN
Solar/Wind Harmer
37.974
3145796HORNRTN
Solar/Wind Harmer
1.03
3145796HORNRTN
Solar/Wind Harmer
0.129
3137643SOCKMAN
Solar/Wind Harmer
1.19
316426AA2-053 GEN
Solar/Wind Harmer
0.817
3146043SEABORD
Solar/Wind Harmer
0.215
316274AC1-208 GEN
Solar/Wind Harmer
1.092
316210AC1-098 GEN
Solar/Wind Harmer
1.848
316327AA2-057 GEN
Solar/Wind Harmer
0.288
3146033SCOT NK
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
7.895
3145683EARLEYS
Solar/Wind Harmer
0.342
3145683EARLEYS
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
0.171
316463AE2-346 GEN
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.354
3145513AHOSKIE
Solar/Wind Harmer
0.169
3145573BETHELC
Solar/Wind Harmer
0.168
3145573BETHELC
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
0.444
3145893MURPHYS
Solar/Wind Harmer
0.165
957861AF2-080 GEN
Solar/Wind Harmer
6.714
3145746EVERETS
Solar/Wind Harmer
0.562
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.127
970601AG2-382 GEN
Solar/Wind Harmer
4.739
315732AD1-074 GEN1
Solar/Wind Harmer
0.605
315733AD1-074 GEN2
Solar/Wind Harmer
0.605
3130546PLYMOUTH
Solar/Wind Harmer
0.103
3144303KENBRDG
Solar/Wind Harmer
0.081
946301AF1-294 GEN
Solar/Wind Harmer
1.684
961791AG1-021 GEN
Solar/Wind Harmer
0.819
970683AG2-441 GEN
Solar/Wind Harmer
5.035
970681AG2-440 GEN
Solar/Wind Harmer
3.342
971967AH1-528 GEN
Solar/Wind Harmer
12.878
316486AD2-202 GEN
Solar/Wind Harmer
0.081
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
3130156CHOWAN
Solar/Wind Harmer
0.06
3130156CHOWAN
Solar/Wind Harmer
0.06
315839AE2-212 C
Solar/Wind Helper
0.176
3143316POE
Solar/Wind Helper
0.503
3151391GASTONA
50/50
0.924
3151411GASTONB
50/50
0.924
3147043LAWRENC
50/50
3.13
3151281ROARAP4
50/50
0.311
3151591KERR 2
50/50
0.264
3151641KERR 7
50/50
0.264
3144293JTRSVLE
50/50
0.216
3144293JTRSVLE
50/50
0.171
3151531CLOVER1
50/50
1.71
316023GEN1_S
Solar/Wind Harmer
1.159
960081AF2-299 GEN
Solar/Wind Harmer
3.997
3145796HORNRTN
Solar/Wind Harmer
1.062
3145796HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.252
315607AA1-063A GEN
Solar/Wind Harmer
0.445
3146263WOODLND
Solar/Wind Harmer
0.195
3146233WITAKRS
Solar/Wind Harmer
0.743
3145823KELFORD
Solar/Wind Harmer
0.181
316359AB2-059 GEN
Solar/Wind Harmer
0.639
3142053HEARTS
Solar/Wind Harmer
0.316
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.143
316129AC1-054 GEN
Solar/Wind Harmer
0.654
3145683EARLEYS
Solar/Wind Harmer
0.171
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.168
3145493TOT1
Solar/Wind Harmer
0.747
3146173TUNIS
Solar/Wind Harmer
0.168
971065AG2-659 GEN
Solar/Wind Harmer
7.147
3145893MURPHYS
Solar/Wind Harmer
0.658
3145893MURPHYS
Solar/Wind Harmer
0.732
3156021HOLLOMANSOL
Solar/Wind Harmer
0.703
316494AC1-189 GEN
Solar/Wind Harmer
0.526
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3146293MARTNCO
Solar/Wind Harmer
0.125
3146206CASHIE
Solar/Wind Harmer
0.127
971547AH1-271 GEN
Solar/Wind Harmer
2.708
3145963POPLR C
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.367
315737AD1-076 GEN
Solar/Wind Harmer
1.365
315785AD2-033 C
Solar/Wind Harmer
0.844
970401AG2-262 GEN
Solar/Wind Harmer
0.554
316034AC1-036 C
Solar/Wind Harmer
0.006
971563AH1-280 GEN
Solar/Wind Harmer
0.91
315816AE2-034 GEN
Solar/Wind Harmer
0.36
3145663CRESWEL
Solar/Wind Harmer
0.236
971163AH1-040 GEN
Solar/Wind Harmer
6.751
315693AD1-088 GEN
Solar/Wind Harmer
3.896
970685AG2-442 GEN
Solar/Wind Harmer
6.05
957481AF2-042 GEN
Solar/Wind Harmer
21.422
3130156CHOWAN
Solar/Wind Harmer
0.06
315671AE2-027_GEN
Solar/Wind Helper
0.951
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.723
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.544
MECLTFEXP_MEC->PJM
CLTF
0.835
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
4.511
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.474
LAGNLTFEXP_LAGN->PJM
CLTF
2.158
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.465
TVALTFEXP_TVA->PJM
CLTF
1.066
NYPJM->LTFIMP_NY
CLTF
0.366
LGEELTFEXP_LGEE->PJM
CLTF
0.266
WECLTFEXP_WEC->PJM
CLTF
0.136

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.5 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1138.82
MW Contribution:
3.58
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:190.98 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1033.21
MW Contribution:
3.7
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.387
3151601KERR 3
50/50
0.544
3151611KERR 4
50/50
0.544
3151621KERR 5
50/50
0.544
3151631KERR 6
50/50
0.544
972205AH1-687 GEN
50/50
5.138
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316486AD2-202 GEN
Solar/Wind Harmer
1.391
971967AH1-528 GEN
Solar/Wind Harmer
96.346
970683AG2-441 GEN
Solar/Wind Harmer
31.117
970681AG2-440 GEN
Solar/Wind Harmer
20.653
316238AB2-078_GEN
Solar/Wind Harmer
1.216
316239AB2-077_GEN
Solar/Wind Harmer
1.216
3144303KENBRDG
Solar/Wind Harmer
-0.03
946301AF1-294 GEN
Solar/Wind Harmer
9.24
961791AG1-021 GEN
Solar/Wind Harmer
4.507
971845AH1-439 GEN
Solar/Wind Harmer
12.217
316322AB2-045
Solar/Wind Harmer
0.749
970831AG2-522 GEN
Solar/Wind Harmer
10.166
946281AF1-292 GEN
Solar/Wind Harmer
0.201
3137643SOCKMAN
Solar/Wind Harmer
-0.031
270455AD2-022 GEN
Solar/Wind Helper
1.388
270457AD2-023 GEN
Solar/Wind Helper
0.915
970413AG2-270 GEN
50/50
45.568
3144293JTRSVLE
50/50
0.813
3151921BEARGRDN G2
50/50
1.052
316283AC2-100 C
Solar/Wind Harmer
9.546
316222AC1-221 GEN
Solar/Wind Harmer
10.167
316003AC1-222 GEN
Solar/Wind Harmer
5.359
316478AD1-087 GEN
Solar/Wind Harmer
4.75
971683AH1-343 GEN
Solar/Wind Harmer
21.5
964241AG1-285 GEN
Solar/Wind Harmer
34.479
959311AF2-222 GEN
Solar/Wind Harmer
46.009
3147133PAMPLIN
Solar/Wind Harmer
-0.124
316123AC1-075 GEN
Solar/Wind Harmer
4.168
970257AG2-171 GEN
Solar/Wind Harmer
14.271
971775AH1-396 GEN
Solar/Wind Harmer
2.685
942461AE2-259 GEN
Solar/Wind Harmer
5.191
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
5.636
316217AC1-145 GEN
Solar/Wind Harmer
1.976
316197AC1-042 GEN
Solar/Wind Harmer
1.498
3147312GRETNA
Solar/Wind Harmer
-0.002
970221AG2-151 GEN
Solar/Wind Harmer
7.146
270494AE1-108_GEN
Solar/Wind Harmer
2.473
966621AG1-532 GEN
Solar/Wind Harmer
0.182
315821AE2-092 GEN
Solar/Wind Harmer
1.75
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3151531CLOVER1
50/50
10.463
3144293JTRSVLE
50/50
0.813
3144293JTRSVLE
50/50
0.642
3151591KERR 2
50/50
0.544
3151641KERR 7
50/50
0.544
3147043LAWRENC
50/50
1.581
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.359
3151911BEARGRDN G1
50/50
1.052
957481AF2-042 GEN
Solar/Wind Harmer
162.806
970401AG2-262 GEN
Solar/Wind Harmer
3.362
315693AD1-088 GEN
Solar/Wind Harmer
23.913
316034AC1-036 C
Solar/Wind Harmer
0.815
970685AG2-442 GEN
Solar/Wind Harmer
37.509
316131AB2-060 GEN
Solar/Wind Harmer
4.326
315785AD2-033 C
Solar/Wind Harmer
8.703
971563AH1-280 GEN
Solar/Wind Harmer
4.507
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.684
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.927
3147123OTTER R
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.569
971377AH1-170 GEN
Solar/Wind Harmer
1.429
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.4
960081AF2-299 GEN
Solar/Wind Harmer
1.007
316087AB2-174 GEN
Solar/Wind Harmer
1.198
3145783HORNRTN
Solar/Wind Harmer
-0.006
3152661PLYWOOD A
50/50
1.081
970909AG2-566 GEN
50/50
3.579
3144293JTRSVLE
50/50
0.813
970535AG2-341 GEN
50/50
5.511
3151581KERR 1
50/50
0.194
315687AD1-152 GEN
Solar/Wind Harmer
7.568
316248AF1-058 C
Solar/Wind Harmer
1.79
316118AC1-105 GEN
Solar/Wind Harmer
3.813
970099AG2-077 GEN
Solar/Wind Harmer
65.122
3146843MT LREL
Solar/Wind Harmer
-0.051
3146843MT LREL
Solar/Wind Harmer
-0.051
964791AG1-342 GEN
Solar/Wind Harmer
11.003
970933AG2-581 GEN
Solar/Wind Harmer
48.045
962561AG1-105 GEN
Solar/Wind Harmer
28.018
316237AB2-079_GEN
Solar/Wind Harmer
1.216
313527AB2-043 GEN
Solar/Wind Harmer
6.552
3147133PAMPLIN
Solar/Wind Harmer
-0.04
3147133PAMPLIN
Solar/Wind Harmer
-0.032
970323AG2-213 GEN
Solar/Wind Harmer
19.028
970301AG2-198 GEN
Solar/Wind Harmer
18.849
958211AF2-115 GEN
Solar/Wind Harmer
5.634
942751AE2-291 GEN
Solar/Wind Harmer
21.345
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
942671AE2-283 GEN
Solar/Wind Harmer
4.036
313506AB2-031 GEN
Solar/Wind Harmer
0.655
316336AC2-165 C
Solar/Wind Harmer
4.63
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.061
3145783HORNRTN
Solar/Wind Harmer
0.766
3145783HORNRTN
Solar/Wind Harmer
0.613
3145783HORNRTN
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
0.077
VTFLTFEXP_VFT->PJM
CMTX
0.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.801
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.554
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.755
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.383
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.383

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.16 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1136.95
MW Contribution:
3.57
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.66 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1004.43
MW Contribution:
3.69
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.367
3151601KERR 3
50/50
0.543
3151611KERR 4
50/50
0.543
3151621KERR 5
50/50
0.543
3151631KERR 6
50/50
0.543
972205AH1-687 GEN
50/50
5.147
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316486AD2-202 GEN
Solar/Wind Harmer
1.388
971967AH1-528 GEN
Solar/Wind Harmer
96.16
970683AG2-441 GEN
Solar/Wind Harmer
31.058
970681AG2-440 GEN
Solar/Wind Harmer
20.614
316238AB2-078_GEN
Solar/Wind Harmer
1.213
316239AB2-077_GEN
Solar/Wind Harmer
1.213
3144303KENBRDG
Solar/Wind Harmer
-0.03
946301AF1-294 GEN
Solar/Wind Harmer
9.224
961791AG1-021 GEN
Solar/Wind Harmer
4.499
971845AH1-439 GEN
Solar/Wind Harmer
12.211
316322AB2-045
Solar/Wind Harmer
0.749
970831AG2-522 GEN
Solar/Wind Harmer
10.132
946281AF1-292 GEN
Solar/Wind Harmer
0.2
3137643SOCKMAN
Solar/Wind Harmer
-0.031
316258AE1-075 C
Solar/Wind Harmer
0.154
316405AF2-144 C
Solar/Wind Harmer
0.162
270455AD2-022 GEN
Solar/Wind Helper
1.407
270457AD2-023 GEN
Solar/Wind Helper
0.927
970413AG2-270 GEN
50/50
45.479
3144293JTRSVLE
50/50
0.812
3151921BEARGRDN G2
50/50
1.053
316283AC2-100 C
Solar/Wind Harmer
9.527
316222AC1-221 GEN
Solar/Wind Harmer
10.147
316478AD1-087 GEN
Solar/Wind Harmer
4.741
316003AC1-222 GEN
Solar/Wind Harmer
5.348
971683AH1-343 GEN
Solar/Wind Harmer
21.455
964241AG1-285 GEN
Solar/Wind Harmer
34.41
959311AF2-222 GEN
Solar/Wind Harmer
45.921
3147133PAMPLIN
Solar/Wind Harmer
-0.124
316123AC1-075 GEN
Solar/Wind Harmer
4.158
970257AG2-171 GEN
Solar/Wind Harmer
14.243
971775AH1-396 GEN
Solar/Wind Harmer
2.68
942461AE2-259 GEN
Solar/Wind Harmer
5.184
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
5.643
316217AC1-145 GEN
Solar/Wind Harmer
1.969
316197AC1-042 GEN
Solar/Wind Harmer
1.492
3147312GRETNA
Solar/Wind Harmer
-0.002
970221AG2-151 GEN
Solar/Wind Harmer
7.16
270494AE1-108_GEN
Solar/Wind Harmer
2.477
966621AG1-532 GEN
Solar/Wind Harmer
0.182
315821AE2-092 GEN
Solar/Wind Harmer
1.756
316181AB2-040 GEN
Solar/Wind Harmer
1.136
3143336POWHATN
Solar/Wind Harmer
0.641
3151531CLOVER1
50/50
10.443
3144293JTRSVLE
50/50
0.812
3144293JTRSVLE
50/50
0.641
3151591KERR 2
50/50
0.543
3151641KERR 7
50/50
0.543
3147043LAWRENC
50/50
1.579
3151561HALLBR1
50/50
0.344
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.053
957481AF2-042 GEN
Solar/Wind Harmer
162.491
970401AG2-262 GEN
Solar/Wind Harmer
3.355
315693AD1-088 GEN
Solar/Wind Harmer
23.868
316034AC1-036 C
Solar/Wind Harmer
0.814
970685AG2-442 GEN
Solar/Wind Harmer
37.44
316131AB2-060 GEN
Solar/Wind Harmer
4.316
315785AD2-033 C
Solar/Wind Harmer
8.686
971563AH1-280 GEN
Solar/Wind Harmer
4.499
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.646
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.921
3147123OTTER R
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.552
971377AH1-170 GEN
Solar/Wind Harmer
1.432
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.427
960081AF2-299 GEN
Solar/Wind Harmer
1.007
316087AB2-174 GEN
Solar/Wind Harmer
1.196
3145783HORNRTN
Solar/Wind Harmer
-0.006
3143336POWHATN
Solar/Wind Harmer
0.755
270018AE2-047 C O1
Solar/Wind Helper
0.399
3152661PLYWOOD A
50/50
1.079
970909AG2-566 GEN
50/50
3.573
3144293JTRSVLE
50/50
0.812
970535AG2-341 GEN
50/50
5.496
3151581KERR 1
50/50
0.194
315687AD1-152 GEN
Solar/Wind Harmer
7.553
316248AF1-058 C
Solar/Wind Harmer
1.787
316118AC1-105 GEN
Solar/Wind Harmer
3.805
970099AG2-077 GEN
Solar/Wind Harmer
64.997
3146843MT LREL
Solar/Wind Harmer
-0.051
3146843MT LREL
Solar/Wind Harmer
-0.051
964791AG1-342 GEN
Solar/Wind Harmer
10.98
970933AG2-581 GEN
Solar/Wind Harmer
47.952
962561AG1-105 GEN
Solar/Wind Harmer
27.96
316237AB2-079_GEN
Solar/Wind Harmer
1.213
313527AB2-043 GEN
Solar/Wind Harmer
6.538
3147133PAMPLIN
Solar/Wind Harmer
-0.039
3147133PAMPLIN
Solar/Wind Harmer
-0.032
970323AG2-213 GEN
Solar/Wind Harmer
18.991
970301AG2-198 GEN
Solar/Wind Harmer
18.819
958211AF2-115 GEN
Solar/Wind Harmer
5.624
942751AE2-291 GEN
Solar/Wind Harmer
21.295
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
942671AE2-283 GEN
Solar/Wind Harmer
4.021
313506AB2-031 GEN
Solar/Wind Harmer
0.654
316336AC2-165 C
Solar/Wind Harmer
4.666
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.06
3145783HORNRTN
Solar/Wind Harmer
0.762
3145783HORNRTN
Solar/Wind Harmer
0.61
3145783HORNRTN
Solar/Wind Harmer
0.19
3145783HORNRTN
Solar/Wind Harmer
0.076
316313AB2-026
Solar/Wind Harmer
0.171
VTFLTFEXP_VFT->PJM
CMTX
0.195
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.846
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.637
G-007ALTFEXP_G-007A->PJM
CMTX
0.081
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.765
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.418
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.029
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.482

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.16 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1136.95
MW Contribution:
3.57
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.72 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1004.72
MW Contribution:
3.69
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.443
3144293JTRSVLE
50/50
0.812
3144293JTRSVLE
50/50
0.641
3151591KERR 2
50/50
0.543
3151641KERR 7
50/50
0.543
3147043LAWRENC
50/50
1.579
3151561HALLBR1
50/50
0.344
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.053
957481AF2-042 GEN
Solar/Wind Harmer
162.491
970401AG2-262 GEN
Solar/Wind Harmer
3.355
315693AD1-088 GEN
Solar/Wind Harmer
23.868
316034AC1-036 C
Solar/Wind Harmer
0.814
970685AG2-442 GEN
Solar/Wind Harmer
37.44
316131AB2-060 GEN
Solar/Wind Harmer
4.316
315785AD2-033 C
Solar/Wind Harmer
8.686
971563AH1-280 GEN
Solar/Wind Harmer
4.499
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.646
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.921
3147123OTTER R
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.552
971377AH1-170 GEN
Solar/Wind Harmer
1.432
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.427
960081AF2-299 GEN
Solar/Wind Harmer
1.007
316087AB2-174 GEN
Solar/Wind Harmer
1.196
3145783HORNRTN
Solar/Wind Harmer
-0.006
3143336POWHATN
Solar/Wind Harmer
0.755
270018AE2-047 C O1
Solar/Wind Helper
0.399
970413AG2-270 GEN
50/50
45.479
3144293JTRSVLE
50/50
0.812
3151921BEARGRDN G2
50/50
1.053
316283AC2-100 C
Solar/Wind Harmer
9.527
316222AC1-221 GEN
Solar/Wind Harmer
10.147
316478AD1-087 GEN
Solar/Wind Harmer
4.741
316003AC1-222 GEN
Solar/Wind Harmer
5.348
971683AH1-343 GEN
Solar/Wind Harmer
21.455
964241AG1-285 GEN
Solar/Wind Harmer
34.41
959311AF2-222 GEN
Solar/Wind Harmer
45.921
3147133PAMPLIN
Solar/Wind Harmer
-0.124
316123AC1-075 GEN
Solar/Wind Harmer
4.158
970257AG2-171 GEN
Solar/Wind Harmer
14.243
971775AH1-396 GEN
Solar/Wind Harmer
2.68
942461AE2-259 GEN
Solar/Wind Harmer
5.184
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
5.643
316217AC1-145 GEN
Solar/Wind Harmer
1.969
316197AC1-042 GEN
Solar/Wind Harmer
1.492
3147312GRETNA
Solar/Wind Harmer
-0.002
970221AG2-151 GEN
Solar/Wind Harmer
7.16
270494AE1-108_GEN
Solar/Wind Harmer
2.477
966621AG1-532 GEN
Solar/Wind Harmer
0.182
315821AE2-092 GEN
Solar/Wind Harmer
1.756
316181AB2-040 GEN
Solar/Wind Harmer
1.136
3143336POWHATN
Solar/Wind Harmer
0.641
3151541CLOVER2
50/50
10.367
3151601KERR 3
50/50
0.543
3151611KERR 4
50/50
0.543
3151621KERR 5
50/50
0.543
3151631KERR 6
50/50
0.543
972205AH1-687 GEN
50/50
5.147
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316486AD2-202 GEN
Solar/Wind Harmer
1.388
971967AH1-528 GEN
Solar/Wind Harmer
96.16
970683AG2-441 GEN
Solar/Wind Harmer
31.058
970681AG2-440 GEN
Solar/Wind Harmer
20.614
316238AB2-078_GEN
Solar/Wind Harmer
1.213
316239AB2-077_GEN
Solar/Wind Harmer
1.213
3144303KENBRDG
Solar/Wind Harmer
-0.03
946301AF1-294 GEN
Solar/Wind Harmer
9.224
961791AG1-021 GEN
Solar/Wind Harmer
4.499
971845AH1-439 GEN
Solar/Wind Harmer
12.211
316322AB2-045
Solar/Wind Harmer
0.749
970831AG2-522 GEN
Solar/Wind Harmer
10.132
946281AF1-292 GEN
Solar/Wind Harmer
0.2
3137643SOCKMAN
Solar/Wind Harmer
-0.031
316258AE1-075 C
Solar/Wind Harmer
0.154
316405AF2-144 C
Solar/Wind Harmer
0.162
270455AD2-022 GEN
Solar/Wind Helper
1.407
270457AD2-023 GEN
Solar/Wind Helper
0.927
3152661PLYWOOD A
50/50
1.079
970909AG2-566 GEN
50/50
3.573
3144293JTRSVLE
50/50
0.812
970535AG2-341 GEN
50/50
5.496
3151581KERR 1
50/50
0.194
315687AD1-152 GEN
Solar/Wind Harmer
7.553
316248AF1-058 C
Solar/Wind Harmer
1.787
316118AC1-105 GEN
Solar/Wind Harmer
3.805
970099AG2-077 GEN
Solar/Wind Harmer
64.997
3146843MT LREL
Solar/Wind Harmer
-0.051
3146843MT LREL
Solar/Wind Harmer
-0.051
964791AG1-342 GEN
Solar/Wind Harmer
10.98
970933AG2-581 GEN
Solar/Wind Harmer
47.952
962561AG1-105 GEN
Solar/Wind Harmer
27.96
316237AB2-079_GEN
Solar/Wind Harmer
1.213
313527AB2-043 GEN
Solar/Wind Harmer
6.538
3147133PAMPLIN
Solar/Wind Harmer
-0.039
3147133PAMPLIN
Solar/Wind Harmer
-0.032
970323AG2-213 GEN
Solar/Wind Harmer
18.991
970301AG2-198 GEN
Solar/Wind Harmer
18.819
958211AF2-115 GEN
Solar/Wind Harmer
5.624
942751AE2-291 GEN
Solar/Wind Harmer
21.295
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
942671AE2-283 GEN
Solar/Wind Harmer
4.021
313506AB2-031 GEN
Solar/Wind Harmer
0.654
316336AC2-165 C
Solar/Wind Harmer
4.666
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.06
3145783HORNRTN
Solar/Wind Harmer
0.762
3145783HORNRTN
Solar/Wind Harmer
0.61
3145783HORNRTN
Solar/Wind Harmer
0.19
3145783HORNRTN
Solar/Wind Harmer
0.076
316313AB2-026
Solar/Wind Harmer
0.171
VTFLTFEXP_VFT->PJM
CMTX
0.195
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.846
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.637
G-007ALTFEXP_G-007A->PJM
CMTX
0.081
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.765
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.418
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.029
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.482

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.89 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1092.2
MW Contribution:
3.53
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.83 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:989.14
MW Contribution:
3.65
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.593
3144293JTRSVLE
50/50
0.805
3144293JTRSVLE
50/50
0.635
3151591KERR 2
50/50
0.542
3151641KERR 7
50/50
0.542
3147043LAWRENC
50/50
1.571
3151561HALLBR1
50/50
0.347
957481AF2-042 GEN
Solar/Wind Harmer
166.61
970401AG2-262 GEN
Solar/Wind Harmer
3.363
315693AD1-088 GEN
Solar/Wind Harmer
23.555
316034AC1-036 C
Solar/Wind Harmer
0.805
970685AG2-442 GEN
Solar/Wind Harmer
37.002
316131AB2-060 GEN
Solar/Wind Harmer
4.296
315785AD2-033 C
Solar/Wind Harmer
8.632
971563AH1-280 GEN
Solar/Wind Harmer
4.462
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.637
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.92
3147123OTTER R
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.591
971377AH1-170 GEN
Solar/Wind Harmer
1.409
3147623JAMES R
Solar/Wind Harmer
0.174
970937AG2-583 GEN
Solar/Wind Harmer
7.294
960081AF2-299 GEN
Solar/Wind Harmer
1.001
316087AB2-174 GEN
Solar/Wind Harmer
1.191
3145783HORNRTN
Solar/Wind Harmer
-0.006
970413AG2-270 GEN
50/50
46.132
3144293JTRSVLE
50/50
0.805
316283AC2-100 C
Solar/Wind Harmer
9.562
316222AC1-221 GEN
Solar/Wind Harmer
10.185
316478AD1-087 GEN
Solar/Wind Harmer
4.808
316003AC1-222 GEN
Solar/Wind Harmer
5.38
971683AH1-343 GEN
Solar/Wind Harmer
21.585
964241AG1-285 GEN
Solar/Wind Harmer
34.076
959311AF2-222 GEN
Solar/Wind Harmer
45.411
3147133PAMPLIN
Solar/Wind Harmer
-0.122
316123AC1-075 GEN
Solar/Wind Harmer
4.185
970257AG2-171 GEN
Solar/Wind Harmer
14.15
971775AH1-396 GEN
Solar/Wind Harmer
2.662
942461AE2-259 GEN
Solar/Wind Harmer
5.123
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
5.556
316217AC1-145 GEN
Solar/Wind Harmer
1.986
316197AC1-042 GEN
Solar/Wind Harmer
1.505
3147312GRETNA
Solar/Wind Harmer
-0.002
970221AG2-151 GEN
Solar/Wind Harmer
7.046
270494AE1-108_GEN
Solar/Wind Harmer
2.442
966621AG1-532 GEN
Solar/Wind Harmer
0.181
315821AE2-092 GEN
Solar/Wind Harmer
1.725
316181AB2-040 GEN
Solar/Wind Harmer
1.132
3151541CLOVER2
50/50
10.515
3151601KERR 3
50/50
0.542
3151611KERR 4
50/50
0.542
3151621KERR 5
50/50
0.542
3151631KERR 6
50/50
0.542
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316486AD2-202 GEN
Solar/Wind Harmer
1.408
970683AG2-441 GEN
Solar/Wind Harmer
30.696
970681AG2-440 GEN
Solar/Wind Harmer
20.373
316238AB2-078_GEN
Solar/Wind Harmer
1.208
316239AB2-077_GEN
Solar/Wind Harmer
1.208
3144303KENBRDG
Solar/Wind Harmer
-0.03
946301AF1-294 GEN
Solar/Wind Harmer
9.146
961791AG1-021 GEN
Solar/Wind Harmer
4.462
971845AH1-439 GEN
Solar/Wind Harmer
12.045
316322AB2-045
Solar/Wind Harmer
0.739
970831AG2-522 GEN
Solar/Wind Harmer
10.124
972205AH1-687 GEN
Adder
4.774
946281AF1-292 GEN
Solar/Wind Harmer
0.199
3137643SOCKMAN
Solar/Wind Harmer
-0.03
270455AD2-022 GEN
Solar/Wind Helper
1.378
270457AD2-023 GEN
Solar/Wind Helper
0.908
3152661PLYWOOD A
50/50
1.084
970909AG2-566 GEN
50/50
3.527
3144293JTRSVLE
50/50
0.805
970535AG2-341 GEN
50/50
5.48
3151581KERR 1
50/50
0.194
315687AD1-152 GEN
Solar/Wind Harmer
7.632
316248AF1-058 C
Solar/Wind Harmer
1.797
316118AC1-105 GEN
Solar/Wind Harmer
3.822
970099AG2-077 GEN
Solar/Wind Harmer
66.644
3146843MT LREL
Solar/Wind Harmer
-0.051
3146843MT LREL
Solar/Wind Harmer
-0.051
964791AG1-342 GEN
Solar/Wind Harmer
11.008
962561AG1-105 GEN
Solar/Wind Harmer
28.005
316237AB2-079_GEN
Solar/Wind Harmer
1.208
313527AB2-043 GEN
Solar/Wind Harmer
6.508
3147133PAMPLIN
Solar/Wind Harmer
-0.039
3147133PAMPLIN
Solar/Wind Harmer
-0.031
970323AG2-213 GEN
Solar/Wind Harmer
18.867
970301AG2-198 GEN
Solar/Wind Harmer
18.574
958211AF2-115 GEN
Solar/Wind Harmer
5.577
942751AE2-291 GEN
Solar/Wind Harmer
21.432
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
942671AE2-283 GEN
Solar/Wind Harmer
4.056
313506AB2-031 GEN
Solar/Wind Harmer
0.652
316336AC2-165 C
Solar/Wind Harmer
4.562
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.06
3145783HORNRTN
Solar/Wind Harmer
0.763
3145783HORNRTN
Solar/Wind Harmer
0.61
3145783HORNRTN
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
0.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.53
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.751
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.371
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.045
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.359

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.87 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1092.14
MW Contribution:
3.53
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
46.128
3144293JTRSVLE
50/50
0.805
316283AC2-100 C
Solar/Wind Harmer
9.562
316222AC1-221 GEN
Solar/Wind Harmer
10.185
316478AD1-087 GEN
Solar/Wind Harmer
4.808
316003AC1-222 GEN
Solar/Wind Harmer
5.38
971683AH1-343 GEN
Solar/Wind Harmer
21.585
964241AG1-285 GEN
Solar/Wind Harmer
34.079
959311AF2-222 GEN
Solar/Wind Harmer
45.416
3147133PAMPLIN
Solar/Wind Harmer
-0.122
316123AC1-075 GEN
Solar/Wind Harmer
4.184
970257AG2-171 GEN
Solar/Wind Harmer
14.151
971775AH1-396 GEN
Solar/Wind Harmer
2.663
942461AE2-259 GEN
Solar/Wind Harmer
5.123
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
5.556
316217AC1-145 GEN
Solar/Wind Harmer
1.986
316197AC1-042 GEN
Solar/Wind Harmer
1.505
3147312GRETNA
Solar/Wind Harmer
-0.002
970221AG2-151 GEN
Solar/Wind Harmer
7.047
270494AE1-108_GEN
Solar/Wind Harmer
2.442
966621AG1-532 GEN
Solar/Wind Harmer
0.181
315821AE2-092 GEN
Solar/Wind Harmer
1.726
316181AB2-040 GEN
Solar/Wind Harmer
1.132
3151541CLOVER2
50/50
10.515
3151601KERR 3
50/50
0.542
3151611KERR 4
50/50
0.542
3151621KERR 5
50/50
0.542
3151631KERR 6
50/50
0.542
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316486AD2-202 GEN
Solar/Wind Harmer
1.408
970683AG2-441 GEN
Solar/Wind Harmer
30.699
970681AG2-440 GEN
Solar/Wind Harmer
20.375
316238AB2-078_GEN
Solar/Wind Harmer
1.208
316239AB2-077_GEN
Solar/Wind Harmer
1.208
3144303KENBRDG
Solar/Wind Harmer
-0.03
946301AF1-294 GEN
Solar/Wind Harmer
9.147
961791AG1-021 GEN
Solar/Wind Harmer
4.462
971845AH1-439 GEN
Solar/Wind Harmer
12.046
316322AB2-045
Solar/Wind Harmer
0.739
970831AG2-522 GEN
Solar/Wind Harmer
10.125
972205AH1-687 GEN
Adder
4.774
946281AF1-292 GEN
Solar/Wind Harmer
0.199
3137643SOCKMAN
Solar/Wind Harmer
-0.03
270455AD2-022 GEN
Solar/Wind Helper
1.378
270457AD2-023 GEN
Solar/Wind Helper
0.908
3152661PLYWOOD A
50/50
1.084
970909AG2-566 GEN
50/50
3.527
3144293JTRSVLE
50/50
0.805
970535AG2-341 GEN
50/50
5.48
3151581KERR 1
50/50
0.194
315687AD1-152 GEN
Solar/Wind Harmer
7.632
316248AF1-058 C
Solar/Wind Harmer
1.797
316118AC1-105 GEN
Solar/Wind Harmer
3.822
970099AG2-077 GEN
Solar/Wind Harmer
66.633
3146843MT LREL
Solar/Wind Harmer
-0.051
3146843MT LREL
Solar/Wind Harmer
-0.051
964791AG1-342 GEN
Solar/Wind Harmer
11.008
962561AG1-105 GEN
Solar/Wind Harmer
28.005
316237AB2-079_GEN
Solar/Wind Harmer
1.208
313527AB2-043 GEN
Solar/Wind Harmer
6.508
3147133PAMPLIN
Solar/Wind Harmer
-0.039
3147133PAMPLIN
Solar/Wind Harmer
-0.031
970323AG2-213 GEN
Solar/Wind Harmer
18.868
970301AG2-198 GEN
Solar/Wind Harmer
18.576
958211AF2-115 GEN
Solar/Wind Harmer
5.578
942751AE2-291 GEN
Solar/Wind Harmer
21.432
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
942671AE2-283 GEN
Solar/Wind Harmer
4.055
313506AB2-031 GEN
Solar/Wind Harmer
0.652
316336AC2-165 C
Solar/Wind Harmer
4.563
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.06
3145783HORNRTN
Solar/Wind Harmer
0.763
3145783HORNRTN
Solar/Wind Harmer
0.61
3145783HORNRTN
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
0.076
3151531CLOVER1
50/50
10.592
3144293JTRSVLE
50/50
0.805
3144293JTRSVLE
50/50
0.635
3151591KERR 2
50/50
0.542
3151641KERR 7
50/50
0.542
3147043LAWRENC
50/50
1.571
3151561HALLBR1
50/50
0.347
957481AF2-042 GEN
Solar/Wind Harmer
166.581
970401AG2-262 GEN
Solar/Wind Harmer
3.363
315693AD1-088 GEN
Solar/Wind Harmer
23.558
316034AC1-036 C
Solar/Wind Harmer
0.805
970685AG2-442 GEN
Solar/Wind Harmer
37.006
316131AB2-060 GEN
Solar/Wind Harmer
4.296
315785AD2-033 C
Solar/Wind Harmer
8.633
971563AH1-280 GEN
Solar/Wind Harmer
4.462
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.637
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.92
3147123OTTER R
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.591
971377AH1-170 GEN
Solar/Wind Harmer
1.409
3147623JAMES R
Solar/Wind Harmer
0.174
970937AG2-583 GEN
Solar/Wind Harmer
7.295
960081AF2-299 GEN
Solar/Wind Harmer
1.001
316087AB2-174 GEN
Solar/Wind Harmer
1.191
3145783HORNRTN
Solar/Wind Harmer
-0.006
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.53
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.751
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.371
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.045
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.359

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.45 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:876.98
MW Contribution:
3.58
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.19 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:779.01
MW Contribution:
3.7
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.387
3151601KERR 3
50/50
0.544
3151611KERR 4
50/50
0.544
3151621KERR 5
50/50
0.544
3151631KERR 6
50/50
0.544
972205AH1-687 GEN
50/50
5.138
3151281ROARAP4
50/50
0.073
3147173SINAI
Solar/Wind Harmer
0.53
3147243WELCO
Solar/Wind Harmer
0.331
316486AD2-202 GEN
Solar/Wind Harmer
0.498
971967AH1-528 GEN
Solar/Wind Harmer
72.98
970683AG2-441 GEN
Solar/Wind Harmer
23.633
970681AG2-440 GEN
Solar/Wind Harmer
15.686
3144303KENBRDG
Solar/Wind Harmer
0.271
946301AF1-294 GEN
Solar/Wind Harmer
6.333
961791AG1-021 GEN
Solar/Wind Harmer
3.081
971845AH1-439 GEN
Solar/Wind Harmer
9.279
970831AG2-522 GEN
Solar/Wind Harmer
7.721
3137643SOCKMAN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Helper
1.388
270457AD2-023 GEN
Solar/Wind Helper
0.915
970413AG2-270 GEN
50/50
45.568
3144293JTRSVLE
50/50
0.813
3151921BEARGRDN G2
50/50
1.052
3151261ROARAP2
50/50
0.08
24728405LEESVG
50/50
0.073
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.765
316222AC1-221 GEN
Solar/Wind Harmer
3.693
316478AD1-087 GEN
Solar/Wind Harmer
1.696
971683AH1-343 GEN
Solar/Wind Harmer
16.329
964241AG1-285 GEN
Solar/Wind Harmer
26.187
959311AF2-222 GEN
Solar/Wind Harmer
34.874
3147133PAMPLIN
Solar/Wind Harmer
1.108
316123AC1-075 GEN
Solar/Wind Harmer
0.46
970257AG2-171 GEN
Solar/Wind Harmer
10.839
971775AH1-396 GEN
Solar/Wind Harmer
0.542
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Harmer
0.161
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.099
972003AH1-546 GEN
Solar/Wind Harmer
4.28
3147312GRETNA
Solar/Wind Harmer
0.022
970221AG2-151 GEN
Solar/Wind Harmer
5.428
270494AE1-108_GEN
Solar/Wind Harmer
1.011
315821AE2-092 GEN
Solar/Wind Harmer
0
316181AB2-040 GEN
Solar/Wind Harmer
0.103
3151531CLOVER1
50/50
10.463
3144293JTRSVLE
50/50
0.813
3144293JTRSVLE
50/50
0.642
3151591KERR 2
50/50
0.544
3151641KERR 7
50/50
0.544
3147043LAWRENC
50/50
1.581
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.359
3151911BEARGRDN G1
50/50
1.052
3151281ROARAP4
50/50
0.078
957481AF2-042 GEN
Solar/Wind Harmer
123.65
970401AG2-262 GEN
Solar/Wind Harmer
2.69
315693AD1-088 GEN
Solar/Wind Harmer
20.432
316034AC1-036 C
Solar/Wind Harmer
0.026
970685AG2-442 GEN
Solar/Wind Harmer
28.488
316131AB2-060 GEN
Solar/Wind Harmer
1.113
315785AD2-033 C
Solar/Wind Harmer
2.77
971563AH1-280 GEN
Solar/Wind Harmer
3.423
3146926FARMVIL
Solar/Wind Harmer
0.161
971065AG2-659 GEN
Solar/Wind Harmer
8.874
3146776BUCKING
Solar/Wind Harmer
0.079
316129AC1-054 GEN
Solar/Wind Harmer
0.733
3147123OTTER R
Solar/Wind Harmer
0.088
3147312GRETNA
Solar/Wind Harmer
0.087
3146802CHATHAM
Solar/Wind Harmer
0.081
941801AE2-185 GEN
Solar/Wind Harmer
3.47
971377AH1-170 GEN
Solar/Wind Harmer
1.086
3147623JAMES R
Solar/Wind Harmer
0.236
970937AG2-583 GEN
Solar/Wind Harmer
5.62
960081AF2-299 GEN
Solar/Wind Harmer
0.765
3145783HORNRTN
Solar/Wind Harmer
0.057
3152661PLYWOOD A
50/50
1.081
970909AG2-566 GEN
50/50
3.579
3144293JTRSVLE
50/50
0.813
970535AG2-341 GEN
50/50
5.511
3151581KERR 1
50/50
0.194
3151261ROARAP2
50/50
0.078
316118AC1-105 GEN
Solar/Wind Harmer
1.267
970099AG2-077 GEN
Solar/Wind Harmer
49.46
3146843MT LREL
Solar/Wind Harmer
0.459
3146843MT LREL
Solar/Wind Harmer
0.459
964791AG1-342 GEN
Solar/Wind Harmer
8.802
970933AG2-581 GEN
Solar/Wind Harmer
36.49
962561AG1-105 GEN
Solar/Wind Harmer
21.279
3147133PAMPLIN
Solar/Wind Harmer
0.353
3147133PAMPLIN
Solar/Wind Harmer
0.282
970323AG2-213 GEN
Solar/Wind Harmer
14.452
970301AG2-198 GEN
Solar/Wind Harmer
14.316
958211AF2-115 GEN
Solar/Wind Harmer
3.851
942751AE2-291 GEN
Solar/Wind Harmer
16.211
3146776BUCKING
Solar/Wind Harmer
0.794
3146776BUCKING
Solar/Wind Harmer
0.064
942671AE2-283 GEN
Solar/Wind Harmer
2.699
313506AB2-031 GEN
Solar/Wind Harmer
0.223
316336AC2-165 C
Solar/Wind Harmer
3.344
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.081
3145783HORNRTN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
0.817
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
VTFLTFEXP_VFT->PJM
CMTX
0.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.801
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.554
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.755
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.383
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.383

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:169.26 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:860.77
MW Contribution:
3.58
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:149.86 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:762.12
MW Contribution:
3.7
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.387
3151601KERR 3
50/50
0.544
3151611KERR 4
50/50
0.544
3151621KERR 5
50/50
0.544
3151631KERR 6
50/50
0.544
972205AH1-687 GEN
50/50
5.138
3151281ROARAP4
50/50
0.073
3147173SINAI
Solar/Wind Harmer
0.53
3152661PLYWOOD A
50/50
1.081
970909AG2-566 GEN
50/50
3.579
3144293JTRSVLE
50/50
0.813
970535AG2-341 GEN
50/50
5.511
3151581KERR 1
50/50
0.194
3151261ROARAP2
50/50
0.078
316118AC1-105 GEN
Solar/Wind Harmer
1.267
970099AG2-077 GEN
Solar/Wind Harmer
49.46
3146843MT LREL
Solar/Wind Harmer
0.459
3146843MT LREL
Solar/Wind Harmer
0.459
964791AG1-342 GEN
Solar/Wind Harmer
8.802
962561AG1-105 GEN
Solar/Wind Harmer
21.279
3147133PAMPLIN
Solar/Wind Harmer
0.353
3147133PAMPLIN
Solar/Wind Harmer
0.282
970323AG2-213 GEN
Solar/Wind Harmer
14.452
970301AG2-198 GEN
Solar/Wind Harmer
14.316
958211AF2-115 GEN
Solar/Wind Harmer
3.851
942751AE2-291 GEN
Solar/Wind Harmer
16.211
3146776BUCKING
Solar/Wind Harmer
0.794
3146776BUCKING
Solar/Wind Harmer
0.064
942671AE2-283 GEN
Solar/Wind Harmer
2.699
313506AB2-031 GEN
Solar/Wind Harmer
0.223
316336AC2-165 C
Solar/Wind Harmer
3.344
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.081
3145783HORNRTN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
0.817
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
970413AG2-270 GEN
50/50
45.568
3144293JTRSVLE
50/50
0.813
3151921BEARGRDN G2
50/50
1.052
3151261ROARAP2
50/50
0.08
24728405LEESVG
50/50
0.073
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.765
316222AC1-221 GEN
Solar/Wind Harmer
3.693
316478AD1-087 GEN
Solar/Wind Harmer
1.696
971683AH1-343 GEN
Solar/Wind Harmer
16.329
964241AG1-285 GEN
Solar/Wind Harmer
26.187
959311AF2-222 GEN
Solar/Wind Harmer
34.874
3147133PAMPLIN
Solar/Wind Harmer
1.108
316123AC1-075 GEN
Solar/Wind Harmer
0.46
970257AG2-171 GEN
Solar/Wind Harmer
10.839
971775AH1-396 GEN
Solar/Wind Harmer
0.542
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Harmer
0.161
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.099
972003AH1-546 GEN
Solar/Wind Harmer
4.28
3147312GRETNA
Solar/Wind Harmer
0.022
970221AG2-151 GEN
Solar/Wind Harmer
5.428
270494AE1-108_GEN
Solar/Wind Harmer
1.011
315821AE2-092 GEN
Solar/Wind Harmer
0
316181AB2-040 GEN
Solar/Wind Harmer
0.103
3147243WELCO
Solar/Wind Harmer
0.331
316486AD2-202 GEN
Solar/Wind Harmer
0.498
970683AG2-441 GEN
Solar/Wind Harmer
23.633
970681AG2-440 GEN
Solar/Wind Harmer
15.686
3144303KENBRDG
Solar/Wind Harmer
0.271
946301AF1-294 GEN
Solar/Wind Harmer
6.333
961791AG1-021 GEN
Solar/Wind Harmer
3.081
971845AH1-439 GEN
Solar/Wind Harmer
9.279
970831AG2-522 GEN
Solar/Wind Harmer
7.721
3137643SOCKMAN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Helper
1.388
270457AD2-023 GEN
Solar/Wind Helper
0.915
3151531CLOVER1
50/50
10.463
3144293JTRSVLE
50/50
0.813
3144293JTRSVLE
50/50
0.642
3151591KERR 2
50/50
0.544
3151641KERR 7
50/50
0.544
3147043LAWRENC
50/50
1.581
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.359
3151911BEARGRDN G1
50/50
1.052
3151281ROARAP4
50/50
0.078
957481AF2-042 GEN
Solar/Wind Harmer
123.65
970401AG2-262 GEN
Solar/Wind Harmer
2.69
315693AD1-088 GEN
Solar/Wind Harmer
20.432
316034AC1-036 C
Solar/Wind Harmer
0.026
970685AG2-442 GEN
Solar/Wind Harmer
28.488
316131AB2-060 GEN
Solar/Wind Harmer
1.113
315785AD2-033 C
Solar/Wind Harmer
2.77
971563AH1-280 GEN
Solar/Wind Harmer
3.423
3146926FARMVIL
Solar/Wind Harmer
0.161
971065AG2-659 GEN
Solar/Wind Harmer
8.874
3146776BUCKING
Solar/Wind Harmer
0.079
316129AC1-054 GEN
Solar/Wind Harmer
0.733
3147123OTTER R
Solar/Wind Harmer
0.088
3147312GRETNA
Solar/Wind Harmer
0.087
3146802CHATHAM
Solar/Wind Harmer
0.081
941801AE2-185 GEN
Solar/Wind Harmer
3.47
971377AH1-170 GEN
Solar/Wind Harmer
1.086
3147623JAMES R
Solar/Wind Harmer
0.236
970937AG2-583 GEN
Solar/Wind Harmer
5.62
960081AF2-299 GEN
Solar/Wind Harmer
0.765
3145783HORNRTN
Solar/Wind Harmer
0.057
VTFLTFEXP_VFT->PJM
CMTX
0.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.801
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.554
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.755
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.383
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.383

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.47 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:570.59
MW Contribution:
1.48
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
33.592
3144293JTRSVLE
50/50
0.416
316283AC2-100 C
Solar/Wind Harmer
9.12
316222AC1-221 GEN
Solar/Wind Harmer
9.696
3151541CLOVER2
50/50
7.657
3151601KERR 3
50/50
0.299
3151611KERR 4
50/50
0.299
3151621KERR 5
50/50
0.299
3151531CLOVER1
50/50
7.713
3144293JTRSVLE
50/50
0.416
3144293JTRSVLE
50/50
0.328
3151591KERR 2
50/50
0.299
3151641KERR 7
50/50
0.299
957481AF2-042 GEN
Solar/Wind Harmer
126.372
970401AG2-262 GEN
Solar/Wind Harmer
2.493
316131AB2-060 GEN
Solar/Wind Harmer
2.471
316034AC1-036 C
Solar/Wind Harmer
0.392
315785AD2-033 C
Solar/Wind Harmer
4.766
970685AG2-442 GEN
Solar/Wind Harmer
17.526
315693AD1-088 GEN
Solar/Wind Harmer
9.446
971563AH1-280 GEN
Solar/Wind Harmer
2.304
3146926FARMVIL
Solar/Wind Harmer
-0.008
971065AG2-659 GEN
Solar/Wind Harmer
6.4
3147123OTTER R
Solar/Wind Harmer
-0.008
316129AC1-054 GEN
Solar/Wind Harmer
1.055
3147043LAWRENC
Adder
0.872
3146776BUCKING
Solar/Wind Harmer
-0.004
3147312GRETNA
Solar/Wind Harmer
-0.007
3146802CHATHAM
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
3.444
270018AE2-047 C O1
Solar/Wind Helper
0.483
270016AE1-250 BESS
Solar/Wind Helper
0.464
3152661PLYWOOD A
50/50
0.856
970535AG2-341 GEN
50/50
3.098
3144293JTRSVLE
50/50
0.416
3151581KERR 1
50/50
0.107
970909AG2-566 GEN
50/50
1.475
315687AD1-152 GEN
Solar/Wind Harmer
6.091
316248AF1-058 C
Solar/Wind Harmer
1.474
316118AC1-105 GEN
Solar/Wind Harmer
2.998
970099AG2-077 GEN
Solar/Wind Harmer
50.549
3146843MT LREL
Solar/Wind Harmer
-0.038
3146843MT LREL
Solar/Wind Harmer
-0.038
964791AG1-342 GEN
Solar/Wind Harmer
8.159
962561AG1-105 GEN
Solar/Wind Harmer
20.194
942751AE2-291 GEN
Solar/Wind Harmer
17.287
316237AB2-079_GEN
Solar/Wind Harmer
0.71
313527AB2-043 GEN
Solar/Wind Harmer
3.756
970323AG2-213 GEN
Solar/Wind Harmer
10.31
958211AF2-115 GEN
Solar/Wind Harmer
2.88
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
970301AG2-198 GEN
Solar/Wind Harmer
7.77
3146776BUCKING
Solar/Wind Harmer
-0.039
3146776BUCKING
Solar/Wind Harmer
-0.003
942671AE2-283 GEN
Solar/Wind Harmer
3.042
970933AG2-581 GEN
Solar/Wind Harmer
6.891
270013AE1-250 PV
Solar/Wind Helper
0.464
3151631KERR 6
50/50
0.299
3147173SINAI
Solar/Wind Harmer
-0.049
316003AC1-222 GEN
Solar/Wind Harmer
4.406
971683AH1-343 GEN
Solar/Wind Harmer
17.635
316478AD1-087 GEN
Solar/Wind Harmer
3.509
316123AC1-075 GEN
Solar/Wind Harmer
3.393
964241AG1-285 GEN
Solar/Wind Harmer
17.201
959311AF2-222 GEN
Solar/Wind Harmer
21.962
970257AG2-171 GEN
Solar/Wind Harmer
7.732
971775AH1-396 GEN
Solar/Wind Harmer
1.455
3147133PAMPLIN
Solar/Wind Harmer
-0.057
942461AE2-259 GEN
Solar/Wind Harmer
2.37
3146926FARMVIL
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Harmer
-0.004
316217AC1-145 GEN
Solar/Wind Harmer
1.489
316197AC1-042 GEN
Solar/Wind Harmer
1.129
3147312GRETNA
Solar/Wind Harmer
-0.002
972003AH1-546 GEN
Solar/Wind Harmer
2.666
943811AF1-049 GEN
Solar/Wind Helper
0.775
3147243WELCO
Solar/Wind Harmer
-0.03
316486AD2-202 GEN
Solar/Wind Harmer
1.027
316238AB2-078_GEN
Solar/Wind Harmer
0.71
316239AB2-077_GEN
Solar/Wind Harmer
0.71
970683AG2-441 GEN
Solar/Wind Harmer
14.577
970681AG2-440 GEN
Solar/Wind Harmer
9.675
3144303KENBRDG
Solar/Wind Harmer
-0.016
946301AF1-294 GEN
Solar/Wind Harmer
4.723
961791AG1-021 GEN
Solar/Wind Harmer
2.304
970831AG2-522 GEN
Solar/Wind Harmer
5.558
971845AH1-439 GEN
Solar/Wind Harmer
5.415
316322AB2-045
Solar/Wind Harmer
0.333
270455AD2-022 GEN
Solar/Wind Helper
1.651
270457AD2-023 GEN
Solar/Wind Helper
1.088
VTFLTFEXP_VFT->PJM
CMTX
1.447
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.021
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.094
G-007ALTFEXP_G-007A->PJM
CMTX
0.55
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.546
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.844
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.667
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.707

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.1 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:999.3
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.93 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1189.65
MW Contribution:
5.58
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.158
970413AG2-270 GEN
50/50
29.699
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.217
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.244
971775AH1-396 GEN
Solar/Wind Harmer
3.056
959311AF2-222 GEN
Solar/Wind Harmer
44.468
964241AG1-285 GEN
Solar/Wind Harmer
30.375
316478AD1-087 GEN
Solar/Wind Harmer
3.079
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971683AH1-343 GEN
Solar/Wind Harmer
8.951
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.758
316222AC1-221 GEN
Solar/Wind Harmer
1.411
316283AC2-100 C
Solar/Wind Harmer
1.289
966621AG1-532 GEN
Solar/Wind Harmer
0.223
316181AB2-040 GEN
Solar/Wind Harmer
1.502
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146233WITAKRS
Solar/Wind Harmer
0.158
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.807
315722AD1-056 GEN
Solar/Wind Harmer
2.486
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.429
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.731
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.723
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.158
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.819
3151591KERR 2
50/50
0.483
3151641KERR 7
50/50
0.483
3147043LAWRENC
50/50
1.537
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.421
970685AG2-442 GEN
Solar/Wind Harmer
40.499
316034AC1-036 C
Solar/Wind Harmer
0.777
315785AD2-033 C
Solar/Wind Harmer
9.431
315693AD1-088 GEN
Solar/Wind Harmer
20.662
957481AF2-042 GEN
Solar/Wind Harmer
118.556
316131AB2-060 GEN
Solar/Wind Harmer
3.73
970401AG2-262 GEN
Solar/Wind Harmer
1.864
971065AG2-659 GEN
Solar/Wind Harmer
10.961
316129AC1-054 GEN
Solar/Wind Harmer
1.835
960081AF2-299 GEN
Solar/Wind Harmer
1.234
316087AB2-174 GEN
Solar/Wind Harmer
1.544
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.91
316319Z2-044 C
Solar/Wind Harmer
0.418
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.976
3142053HEARTS
Solar/Wind Harmer
0.085
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
3146776BUCKING
Solar/Wind Helper
0.288
970909AG2-566 GEN
50/50
5.542
3144293JTRSVLE
50/50
1.158
970535AG2-341 GEN
50/50
4.757
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.506
970301AG2-198 GEN
Solar/Wind Harmer
29.19
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.026
970323AG2-213 GEN
Solar/Wind Harmer
21.658
970933AG2-581 GEN
Solar/Wind Harmer
36.199
970099AG2-077 GEN
Solar/Wind Harmer
47.422
313527AB2-043 GEN
Solar/Wind Harmer
5.524
316237AB2-079_GEN
Solar/Wind Harmer
1.003
315687AD1-152 GEN
Solar/Wind Harmer
3.684
962561AG1-105 GEN
Solar/Wind Harmer
16.53
964791AG1-342 GEN
Solar/Wind Harmer
6.099
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.821
316248AF1-058 C
Solar/Wind Harmer
0.74
942751AE2-291 GEN
Solar/Wind Harmer
9.085
313506AB2-031 GEN
Solar/Wind Harmer
0.865
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.216
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316049AB1-081 GEN
Solar/Wind Harmer
0.781
316263AC1-034 GEN
Solar/Wind Harmer
3.402
961601AG1-000A GEN
Solar/Wind Harmer
2.771
315724AD1-057 GEN
Solar/Wind Harmer
1.367
3145796HORNRTN
Solar/Wind Harmer
-0.021
962571AG1-106 GEN
Solar/Wind Harmer
0.984
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.102
3145453TOT5
Solar/Wind Harmer
0.061
3145603CNETO
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Helper
2.883
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.312
3151541CLOVER2
50/50
6.77
3151601KERR 3
50/50
0.483
3151611KERR 4
50/50
0.483
3151621KERR 5
50/50
0.483
3151631KERR 6
50/50
0.483
971845AH1-439 GEN
Solar/Wind Harmer
44.749
946301AF1-294 GEN
Solar/Wind Harmer
13.162
961791AG1-021 GEN
Solar/Wind Harmer
6.421
970683AG2-441 GEN
Solar/Wind Harmer
31.17
970681AG2-440 GEN
Solar/Wind Harmer
20.688
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.59
316486AD2-202 GEN
Solar/Wind Harmer
0.901
316238AB2-078_GEN
Solar/Wind Harmer
1.003
316239AB2-077_GEN
Solar/Wind Harmer
1.003
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.889
946281AF1-292 GEN
Solar/Wind Harmer
0.246
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.982
270455AD2-022 GEN
Solar/Wind Harmer
1.597
270457AD2-023 GEN
Solar/Wind Harmer
0.81
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.91
316327AA2-057 GEN
Solar/Wind Harmer
0.789
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.698
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.806
316258AE1-075 C
Solar/Wind Helper
0.281
316405AF2-144 C
Solar/Wind Helper
0.234
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.715
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.409
MECLTFEXP_MEC->PJM
CLTF
1.024
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
5.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.972
LAGNLTFEXP_LAGN->PJM
CLTF
2.683
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.382
TVALTFEXP_TVA->PJM
CLTF
1.328
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.324
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.1 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:999.3
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.87 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1189.26
MW Contribution:
5.58
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.77
3151601KERR 3
50/50
0.483
3151611KERR 4
50/50
0.483
3151621KERR 5
50/50
0.483
3151631KERR 6
50/50
0.483
971845AH1-439 GEN
Solar/Wind Harmer
44.749
946301AF1-294 GEN
Solar/Wind Harmer
13.162
961791AG1-021 GEN
Solar/Wind Harmer
6.421
970683AG2-441 GEN
Solar/Wind Harmer
31.17
970681AG2-440 GEN
Solar/Wind Harmer
20.688
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.59
316486AD2-202 GEN
Solar/Wind Harmer
0.901
316238AB2-078_GEN
Solar/Wind Harmer
1.003
316239AB2-077_GEN
Solar/Wind Harmer
1.003
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.889
946281AF1-292 GEN
Solar/Wind Harmer
0.246
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.982
270455AD2-022 GEN
Solar/Wind Harmer
1.597
270457AD2-023 GEN
Solar/Wind Harmer
0.81
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.91
316327AA2-057 GEN
Solar/Wind Harmer
0.789
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.698
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.806
316258AE1-075 C
Solar/Wind Helper
0.281
316405AF2-144 C
Solar/Wind Helper
0.234
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.158
970413AG2-270 GEN
50/50
29.699
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.217
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.244
971775AH1-396 GEN
Solar/Wind Harmer
3.056
959311AF2-222 GEN
Solar/Wind Harmer
44.468
964241AG1-285 GEN
Solar/Wind Harmer
30.375
316478AD1-087 GEN
Solar/Wind Harmer
3.079
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971683AH1-343 GEN
Solar/Wind Harmer
8.951
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.758
316222AC1-221 GEN
Solar/Wind Harmer
1.411
316283AC2-100 C
Solar/Wind Harmer
1.289
966621AG1-532 GEN
Solar/Wind Harmer
0.223
316181AB2-040 GEN
Solar/Wind Harmer
1.502
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146233WITAKRS
Solar/Wind Harmer
0.158
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.807
315722AD1-056 GEN
Solar/Wind Harmer
2.486
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.429
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.731
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.723
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.158
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.819
3151591KERR 2
50/50
0.483
3151641KERR 7
50/50
0.483
3147043LAWRENC
50/50
1.537
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.421
970685AG2-442 GEN
Solar/Wind Harmer
40.499
316034AC1-036 C
Solar/Wind Harmer
0.777
315785AD2-033 C
Solar/Wind Harmer
9.431
315693AD1-088 GEN
Solar/Wind Harmer
20.662
957481AF2-042 GEN
Solar/Wind Harmer
118.556
316131AB2-060 GEN
Solar/Wind Harmer
3.73
970401AG2-262 GEN
Solar/Wind Harmer
1.864
971065AG2-659 GEN
Solar/Wind Harmer
10.961
316129AC1-054 GEN
Solar/Wind Harmer
1.835
960081AF2-299 GEN
Solar/Wind Harmer
1.234
316087AB2-174 GEN
Solar/Wind Harmer
1.544
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.91
316319Z2-044 C
Solar/Wind Harmer
0.418
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.976
3142053HEARTS
Solar/Wind Harmer
0.085
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
3146776BUCKING
Solar/Wind Helper
0.288
970909AG2-566 GEN
50/50
5.542
3144293JTRSVLE
50/50
1.158
970535AG2-341 GEN
50/50
4.757
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.506
970301AG2-198 GEN
Solar/Wind Harmer
29.19
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.026
970323AG2-213 GEN
Solar/Wind Harmer
21.658
970933AG2-581 GEN
Solar/Wind Harmer
36.199
970099AG2-077 GEN
Solar/Wind Harmer
47.422
313527AB2-043 GEN
Solar/Wind Harmer
5.524
316237AB2-079_GEN
Solar/Wind Harmer
1.003
315687AD1-152 GEN
Solar/Wind Harmer
3.684
962561AG1-105 GEN
Solar/Wind Harmer
16.53
964791AG1-342 GEN
Solar/Wind Harmer
6.099
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.821
316248AF1-058 C
Solar/Wind Harmer
0.74
942751AE2-291 GEN
Solar/Wind Harmer
9.085
313506AB2-031 GEN
Solar/Wind Harmer
0.865
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.216
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316049AB1-081 GEN
Solar/Wind Harmer
0.781
316263AC1-034 GEN
Solar/Wind Harmer
3.402
961601AG1-000A GEN
Solar/Wind Harmer
2.771
315724AD1-057 GEN
Solar/Wind Harmer
1.367
3145796HORNRTN
Solar/Wind Harmer
-0.021
962571AG1-106 GEN
Solar/Wind Harmer
0.984
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.102
3145453TOT5
Solar/Wind Harmer
0.061
3145603CNETO
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Helper
2.883
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.715
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.409
MECLTFEXP_MEC->PJM
CLTF
1.024
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
5.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.972
LAGNLTFEXP_LAGN->PJM
CLTF
2.683
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.382
TVALTFEXP_TVA->PJM
CLTF
1.328
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.324
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.39 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:994.49
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:170.3 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1164.88
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.756
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.744
946301AF1-294 GEN
Solar/Wind Harmer
13.151
961791AG1-021 GEN
Solar/Wind Harmer
6.415
970683AG2-441 GEN
Solar/Wind Harmer
31.129
970681AG2-440 GEN
Solar/Wind Harmer
20.661
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.459
316486AD2-202 GEN
Solar/Wind Harmer
0.9
316238AB2-078_GEN
Solar/Wind Harmer
1.001
316239AB2-077_GEN
Solar/Wind Harmer
1.001
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.865
946281AF1-292 GEN
Solar/Wind Harmer
0.246
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.98
270455AD2-022 GEN
Solar/Wind Harmer
1.574
270457AD2-023 GEN
Solar/Wind Harmer
0.798
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.906
316210AC1-098 GEN
Solar/Wind Harmer
1.218
316327AA2-057 GEN
Solar/Wind Harmer
0.783
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.683
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.212
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.224
971775AH1-396 GEN
Solar/Wind Harmer
3.053
959311AF2-222 GEN
Solar/Wind Harmer
44.406
964241AG1-285 GEN
Solar/Wind Harmer
30.327
316478AD1-087 GEN
Solar/Wind Harmer
3.072
316003AC1-222 GEN
Solar/Wind Harmer
2.214
971683AH1-343 GEN
Solar/Wind Harmer
8.919
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.751
316222AC1-221 GEN
Solar/Wind Harmer
1.398
316283AC2-100 C
Solar/Wind Harmer
1.276
966621AG1-532 GEN
Solar/Wind Harmer
0.223
316181AB2-040 GEN
Solar/Wind Harmer
1.501
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.677
3146233WITAKRS
Solar/Wind Harmer
0.157
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.774
315722AD1-056 GEN
Solar/Wind Harmer
2.466
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.426
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.088
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
315821AE2-092 GEN
Solar/Wind Helper
2.528
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.415
970685AG2-442 GEN
Solar/Wind Harmer
40.45
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.419
315693AD1-088 GEN
Solar/Wind Harmer
20.63
957481AF2-042 GEN
Solar/Wind Harmer
118.335
316131AB2-060 GEN
Solar/Wind Harmer
3.724
970401AG2-262 GEN
Solar/Wind Harmer
1.859
971065AG2-659 GEN
Solar/Wind Harmer
10.934
316129AC1-054 GEN
Solar/Wind Harmer
1.83
960081AF2-299 GEN
Solar/Wind Harmer
1.234
316087AB2-174 GEN
Solar/Wind Harmer
1.543
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316319Z2-044 C
Solar/Wind Harmer
0.414
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.965
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.193
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
3146776BUCKING
Solar/Wind Helper
0.288
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.746
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
29.169
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.019
970323AG2-213 GEN
Solar/Wind Harmer
21.632
970933AG2-581 GEN
Solar/Wind Harmer
36.133
970099AG2-077 GEN
Solar/Wind Harmer
47.334
313527AB2-043 GEN
Solar/Wind Harmer
5.514
316237AB2-079_GEN
Solar/Wind Harmer
1.001
315687AD1-152 GEN
Solar/Wind Harmer
3.673
962561AG1-105 GEN
Solar/Wind Harmer
16.49
964791AG1-342 GEN
Solar/Wind Harmer
6.083
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.816
316248AF1-058 C
Solar/Wind Harmer
0.737
942751AE2-291 GEN
Solar/Wind Harmer
9.05
313506AB2-031 GEN
Solar/Wind Harmer
0.864
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.772
316263AC1-034 GEN
Solar/Wind Harmer
3.363
961601AG1-000A GEN
Solar/Wind Harmer
2.739
315724AD1-057 GEN
Solar/Wind Harmer
1.356
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.982
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.02 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:788.75
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:170.87 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:955.68
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.756
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151281ROARAP4
50/50
0.105
971845AH1-439 GEN
Solar/Wind Harmer
33.983
946301AF1-294 GEN
Solar/Wind Harmer
9.014
961791AG1-021 GEN
Solar/Wind Harmer
4.385
970683AG2-441 GEN
Solar/Wind Harmer
23.642
970681AG2-440 GEN
Solar/Wind Harmer
15.692
3144303KENBRDG
Solar/Wind Harmer
0.308
971967AH1-528 GEN
Solar/Wind Harmer
54.886
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970831AG2-522 GEN
Solar/Wind Harmer
7.493
3137643SOCKMAN
Solar/Wind Harmer
0.379
316426AA2-053 GEN
Solar/Wind Harmer
0.29
3146043SEABORD
Solar/Wind Harmer
0.078
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3151281ROARAP4
50/50
0.112
971629AH1-314 GEN
50/50
5.749
3151561HALLBR1
50/50
0.158
3151391GASTONA
50/50
0.163
3151411GASTONB
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.872
970685AG2-442 GEN
Solar/Wind Harmer
30.722
316034AC1-036 C
Solar/Wind Harmer
0.025
315785AD2-033 C
Solar/Wind Harmer
2.997
315693AD1-088 GEN
Solar/Wind Harmer
17.627
957481AF2-042 GEN
Solar/Wind Harmer
89.874
316131AB2-060 GEN
Solar/Wind Harmer
0.958
970401AG2-262 GEN
Solar/Wind Harmer
1.487
971065AG2-659 GEN
Solar/Wind Harmer
8.305
316129AC1-054 GEN
Solar/Wind Harmer
0.696
960081AF2-299 GEN
Solar/Wind Harmer
0.937
3145783HORNRTN
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.162
3146233WITAKRS
Solar/Wind Harmer
0.266
3147123OTTER R
Solar/Wind Harmer
0.04
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3151261ROARAP2
50/50
0.116
3151391GASTONA
50/50
0.163
3151411GASTONB
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
1.453
970257AG2-171 GEN
Solar/Wind Harmer
12.322
971775AH1-396 GEN
Solar/Wind Harmer
0.616
959311AF2-222 GEN
Solar/Wind Harmer
33.659
964241AG1-285 GEN
Solar/Wind Harmer
23.033
316478AD1-087 GEN
Solar/Wind Harmer
1.097
971683AH1-343 GEN
Solar/Wind Harmer
6.774
3147043LAWRENC
Solar/Wind Harmer
0.096
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316222AC1-221 GEN
Solar/Wind Harmer
0.508
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
316212AC1-099_GEN
Solar/Wind Harmer
0.357
3146233WITAKRS
Solar/Wind Harmer
0.335
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.044
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
316274AC1-208 GEN
Solar/Wind Harmer
0.386
316210AC1-098 GEN
Solar/Wind Harmer
0.64
316327AA2-057 GEN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.683
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3146263WOODLND
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.128
961601AG1-000A GEN
Solar/Wind Harmer
4.411
315722AD1-056 GEN
Solar/Wind Harmer
2.132
3145796HORNRTN
Solar/Wind Harmer
0.244
3145796HORNRTN
Solar/Wind Harmer
0.061
316011AB1-132 GEN
Solar/Wind Harmer
1.102
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3145823KELFORD
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.096
3145893MURPHYS
Solar/Wind Harmer
0.057
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
315821AE2-092 GEN
Solar/Wind Helper
2.528
3146263WOODLND
Solar/Wind Harmer
0.064
316359AB2-059 GEN
Solar/Wind Harmer
0.227
3142053HEARTS
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.229
3145893MURPHYS
Solar/Wind Harmer
0.254
3146776BUCKING
Solar/Wind Helper
0.288
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.746
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.22
3151371ROSEMS1
50/50
0.136
3151381ROSEMG2
50/50
0.103
970301AG2-198 GEN
Solar/Wind Harmer
22.154
3147133PAMPLIN
Solar/Wind Harmer
0.463
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.481
970323AG2-213 GEN
Solar/Wind Harmer
16.429
970933AG2-581 GEN
Solar/Wind Harmer
27.443
970099AG2-077 GEN
Solar/Wind Harmer
35.95
962561AG1-105 GEN
Solar/Wind Harmer
12.524
964791AG1-342 GEN
Solar/Wind Harmer
4.866
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.873
313506AB2-031 GEN
Solar/Wind Harmer
0.294
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.617
3145783HORNRTN
Solar/Wind Harmer
1.294
3145783HORNRTN
Solar/Wind Harmer
0.404
3145783HORNRTN
Solar/Wind Harmer
0.162
316049AB1-081 GEN
Solar/Wind Harmer
0.363
316263AC1-034 GEN
Solar/Wind Harmer
2.427
961601AG1-000A GEN
Solar/Wind Harmer
1.103
315724AD1-057 GEN
Solar/Wind Harmer
1.189
3145796HORNRTN
Solar/Wind Harmer
0.183
962571AG1-106 GEN
Solar/Wind Harmer
0.864
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
3145893MURPHYS
Solar/Wind Harmer
0.383
3145893MURPHYS
Solar/Wind Harmer
0.103
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.35 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:953.13
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:164.28 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1123.65
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.756
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.744
946301AF1-294 GEN
Solar/Wind Harmer
13.151
961791AG1-021 GEN
Solar/Wind Harmer
6.415
970683AG2-441 GEN
Solar/Wind Harmer
31.129
970681AG2-440 GEN
Solar/Wind Harmer
20.661
3144303KENBRDG
Solar/Wind Harmer
-0.035
316486AD2-202 GEN
Solar/Wind Harmer
0.9
316238AB2-078_GEN
Solar/Wind Harmer
1.001
316239AB2-077_GEN
Solar/Wind Harmer
1.001
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.865
946281AF1-292 GEN
Solar/Wind Harmer
0.246
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.98
270455AD2-022 GEN
Solar/Wind Harmer
1.574
270457AD2-023 GEN
Solar/Wind Harmer
0.798
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.906
316210AC1-098 GEN
Solar/Wind Harmer
1.218
316327AA2-057 GEN
Solar/Wind Harmer
0.783
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.683
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.212
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.224
971775AH1-396 GEN
Solar/Wind Harmer
3.053
959311AF2-222 GEN
Solar/Wind Harmer
44.406
964241AG1-285 GEN
Solar/Wind Harmer
30.327
316478AD1-087 GEN
Solar/Wind Harmer
3.072
316003AC1-222 GEN
Solar/Wind Harmer
2.214
971683AH1-343 GEN
Solar/Wind Harmer
8.919
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.751
316222AC1-221 GEN
Solar/Wind Harmer
1.398
316283AC2-100 C
Solar/Wind Harmer
1.276
966621AG1-532 GEN
Solar/Wind Harmer
0.223
316181AB2-040 GEN
Solar/Wind Harmer
1.501
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.677
3146233WITAKRS
Solar/Wind Harmer
0.157
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.774
315722AD1-056 GEN
Solar/Wind Harmer
2.466
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.426
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.088
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
315821AE2-092 GEN
Solar/Wind Helper
2.528
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.415
970685AG2-442 GEN
Solar/Wind Harmer
40.45
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.419
315693AD1-088 GEN
Solar/Wind Harmer
20.63
957481AF2-042 GEN
Solar/Wind Harmer
118.335
316131AB2-060 GEN
Solar/Wind Harmer
3.724
970401AG2-262 GEN
Solar/Wind Harmer
1.859
971065AG2-659 GEN
Solar/Wind Harmer
10.934
316129AC1-054 GEN
Solar/Wind Harmer
1.83
960081AF2-299 GEN
Solar/Wind Harmer
1.234
316087AB2-174 GEN
Solar/Wind Harmer
1.543
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316319Z2-044 C
Solar/Wind Harmer
0.414
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.965
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.193
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
3146776BUCKING
Solar/Wind Helper
0.288
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.746
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
29.169
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.019
970323AG2-213 GEN
Solar/Wind Harmer
21.632
970099AG2-077 GEN
Solar/Wind Harmer
47.334
313527AB2-043 GEN
Solar/Wind Harmer
5.514
316237AB2-079_GEN
Solar/Wind Harmer
1.001
315687AD1-152 GEN
Solar/Wind Harmer
3.673
962561AG1-105 GEN
Solar/Wind Harmer
16.49
964791AG1-342 GEN
Solar/Wind Harmer
6.083
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.816
316248AF1-058 C
Solar/Wind Harmer
0.737
942751AE2-291 GEN
Solar/Wind Harmer
9.05
313506AB2-031 GEN
Solar/Wind Harmer
0.864
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.772
316263AC1-034 GEN
Solar/Wind Harmer
3.363
961601AG1-000A GEN
Solar/Wind Harmer
2.739
315724AD1-057 GEN
Solar/Wind Harmer
1.356
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.982
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.35 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:953.13
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:164.28 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1123.65
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.756
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.744
946301AF1-294 GEN
Solar/Wind Harmer
13.151
961791AG1-021 GEN
Solar/Wind Harmer
6.415
970683AG2-441 GEN
Solar/Wind Harmer
31.129
970681AG2-440 GEN
Solar/Wind Harmer
20.661
3144303KENBRDG
Solar/Wind Harmer
-0.035
316486AD2-202 GEN
Solar/Wind Harmer
0.9
316238AB2-078_GEN
Solar/Wind Harmer
1.001
316239AB2-077_GEN
Solar/Wind Harmer
1.001
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.865
946281AF1-292 GEN
Solar/Wind Harmer
0.246
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.98
270455AD2-022 GEN
Solar/Wind Harmer
1.574
270457AD2-023 GEN
Solar/Wind Harmer
0.798
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.906
316210AC1-098 GEN
Solar/Wind Harmer
1.218
316327AA2-057 GEN
Solar/Wind Harmer
0.783
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.212
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.224
971775AH1-396 GEN
Solar/Wind Harmer
3.053
959311AF2-222 GEN
Solar/Wind Harmer
44.406
964241AG1-285 GEN
Solar/Wind Harmer
30.327
316478AD1-087 GEN
Solar/Wind Harmer
3.072
316003AC1-222 GEN
Solar/Wind Harmer
2.214
971683AH1-343 GEN
Solar/Wind Harmer
8.919
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.751
316222AC1-221 GEN
Solar/Wind Harmer
1.398
316283AC2-100 C
Solar/Wind Harmer
1.276
966621AG1-532 GEN
Solar/Wind Harmer
0.223
316181AB2-040 GEN
Solar/Wind Harmer
1.501
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.677
3146233WITAKRS
Solar/Wind Harmer
0.157
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.774
315722AD1-056 GEN
Solar/Wind Harmer
2.466
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.426
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.415
970685AG2-442 GEN
Solar/Wind Harmer
40.45
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.419
315693AD1-088 GEN
Solar/Wind Harmer
20.63
957481AF2-042 GEN
Solar/Wind Harmer
118.335
316131AB2-060 GEN
Solar/Wind Harmer
3.724
970401AG2-262 GEN
Solar/Wind Harmer
1.859
971065AG2-659 GEN
Solar/Wind Harmer
10.934
316129AC1-054 GEN
Solar/Wind Harmer
1.83
960081AF2-299 GEN
Solar/Wind Harmer
1.234
316087AB2-174 GEN
Solar/Wind Harmer
1.543
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316319Z2-044 C
Solar/Wind Harmer
0.414
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.965
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.193
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
3146776BUCKING
Solar/Wind Helper
0.288
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.088
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
315821AE2-092 GEN
Solar/Wind Helper
2.528
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.683
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.746
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
29.169
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.019
970323AG2-213 GEN
Solar/Wind Harmer
21.632
970099AG2-077 GEN
Solar/Wind Harmer
47.334
313527AB2-043 GEN
Solar/Wind Harmer
5.514
316237AB2-079_GEN
Solar/Wind Harmer
1.001
315687AD1-152 GEN
Solar/Wind Harmer
3.673
962561AG1-105 GEN
Solar/Wind Harmer
16.49
964791AG1-342 GEN
Solar/Wind Harmer
6.083
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.816
316248AF1-058 C
Solar/Wind Harmer
0.737
942751AE2-291 GEN
Solar/Wind Harmer
9.05
313506AB2-031 GEN
Solar/Wind Harmer
0.864
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.772
316263AC1-034 GEN
Solar/Wind Harmer
3.363
961601AG1-000A GEN
Solar/Wind Harmer
2.739
315724AD1-057 GEN
Solar/Wind Harmer
1.356
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.982
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.34 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:773.73
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:168.25 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:941.05
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.746
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.22
3151371ROSEMS1
50/50
0.136
3151381ROSEMG2
50/50
0.103
970301AG2-198 GEN
Solar/Wind Harmer
22.154
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3151281ROARAP4
50/50
0.112
971629AH1-314 GEN
50/50
5.749
3151561HALLBR1
50/50
0.158
3151391GASTONA
50/50
0.163
3151411GASTONB
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.872
970685AG2-442 GEN
Solar/Wind Harmer
30.722
316034AC1-036 C
Solar/Wind Harmer
0.025
315785AD2-033 C
Solar/Wind Harmer
2.997
315693AD1-088 GEN
Solar/Wind Harmer
17.627
957481AF2-042 GEN
Solar/Wind Harmer
89.874
316131AB2-060 GEN
Solar/Wind Harmer
0.958
970401AG2-262 GEN
Solar/Wind Harmer
1.487
971065AG2-659 GEN
Solar/Wind Harmer
8.305
316129AC1-054 GEN
Solar/Wind Harmer
0.696
960081AF2-299 GEN
Solar/Wind Harmer
0.937
3145783HORNRTN
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.162
3146233WITAKRS
Solar/Wind Harmer
0.266
3147123OTTER R
Solar/Wind Harmer
0.04
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
316359AB2-059 GEN
Solar/Wind Harmer
0.227
3142053HEARTS
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.229
3145893MURPHYS
Solar/Wind Harmer
0.254
3146776BUCKING
Solar/Wind Helper
0.288
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3151261ROARAP2
50/50
0.116
3151391GASTONA
50/50
0.163
3151411GASTONB
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
1.453
970257AG2-171 GEN
Solar/Wind Harmer
12.322
971775AH1-396 GEN
Solar/Wind Harmer
0.616
959311AF2-222 GEN
Solar/Wind Harmer
33.659
964241AG1-285 GEN
Solar/Wind Harmer
23.033
316478AD1-087 GEN
Solar/Wind Harmer
1.097
971683AH1-343 GEN
Solar/Wind Harmer
6.774
3147043LAWRENC
Solar/Wind Harmer
0.096
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316222AC1-221 GEN
Solar/Wind Harmer
0.508
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
316212AC1-099_GEN
Solar/Wind Harmer
0.357
3146233WITAKRS
Solar/Wind Harmer
0.335
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.044
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.128
961601AG1-000A GEN
Solar/Wind Harmer
4.411
315722AD1-056 GEN
Solar/Wind Harmer
2.132
3145796HORNRTN
Solar/Wind Harmer
0.244
3145796HORNRTN
Solar/Wind Harmer
0.061
316011AB1-132 GEN
Solar/Wind Harmer
1.102
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3145823KELFORD
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.096
3145893MURPHYS
Solar/Wind Harmer
0.057
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
315821AE2-092 GEN
Solar/Wind Helper
2.528
3151541CLOVER2
50/50
6.756
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151281ROARAP4
50/50
0.105
971845AH1-439 GEN
Solar/Wind Harmer
33.983
946301AF1-294 GEN
Solar/Wind Harmer
9.014
961791AG1-021 GEN
Solar/Wind Harmer
4.385
970683AG2-441 GEN
Solar/Wind Harmer
23.642
970681AG2-440 GEN
Solar/Wind Harmer
15.692
3144303KENBRDG
Solar/Wind Harmer
0.308
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970831AG2-522 GEN
Solar/Wind Harmer
7.493
3137643SOCKMAN
Solar/Wind Harmer
0.379
316426AA2-053 GEN
Solar/Wind Harmer
0.29
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.386
316210AC1-098 GEN
Solar/Wind Harmer
0.64
316327AA2-057 GEN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.683
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3147133PAMPLIN
Solar/Wind Harmer
0.463
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.481
970323AG2-213 GEN
Solar/Wind Harmer
16.429
970099AG2-077 GEN
Solar/Wind Harmer
35.95
962561AG1-105 GEN
Solar/Wind Harmer
12.524
964791AG1-342 GEN
Solar/Wind Harmer
4.866
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.873
313506AB2-031 GEN
Solar/Wind Harmer
0.294
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.617
3145783HORNRTN
Solar/Wind Harmer
1.294
3145783HORNRTN
Solar/Wind Harmer
0.404
3145783HORNRTN
Solar/Wind Harmer
0.162
316049AB1-081 GEN
Solar/Wind Harmer
0.363
316263AC1-034 GEN
Solar/Wind Harmer
2.427
961601AG1-000A GEN
Solar/Wind Harmer
1.103
315724AD1-057 GEN
Solar/Wind Harmer
1.189
3145796HORNRTN
Solar/Wind Harmer
0.183
962571AG1-106 GEN
Solar/Wind Harmer
0.864
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
3145893MURPHYS
Solar/Wind Harmer
0.383
3145893MURPHYS
Solar/Wind Harmer
0.103
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.37 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1037.09
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.39 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1225.98
MW Contribution:
5.58
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.158
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.815
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.418
970685AG2-442 GEN
Solar/Wind Harmer
40.479
316034AC1-036 C
Solar/Wind Harmer
0.777
315785AD2-033 C
Solar/Wind Harmer
9.425
315693AD1-088 GEN
Solar/Wind Harmer
20.651
957481AF2-042 GEN
Solar/Wind Harmer
118.484
316131AB2-060 GEN
Solar/Wind Harmer
3.728
970401AG2-262 GEN
Solar/Wind Harmer
1.862
971065AG2-659 GEN
Solar/Wind Harmer
10.95
316129AC1-054 GEN
Solar/Wind Harmer
1.833
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.541
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.908
316319Z2-044 C
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.973
3142053HEARTS
Solar/Wind Harmer
0.085
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
3144293JTRSVLE
50/50
1.158
970413AG2-270 GEN
50/50
29.68
972003AH1-546 GEN
Solar/Wind Harmer
41.016
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.214
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.235
971775AH1-396 GEN
Solar/Wind Harmer
3.055
959311AF2-222 GEN
Solar/Wind Harmer
44.444
964241AG1-285 GEN
Solar/Wind Harmer
30.357
316478AD1-087 GEN
Solar/Wind Harmer
3.077
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971683AH1-343 GEN
Solar/Wind Harmer
8.941
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.755
316222AC1-221 GEN
Solar/Wind Harmer
1.409
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.499
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.678
3146233WITAKRS
Solar/Wind Harmer
0.158
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.797
315722AD1-056 GEN
Solar/Wind Harmer
2.478
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.424
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.075
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.728
270494AE1-108_GEN
Solar/Wind Helper
3.729
315821AE2-092 GEN
Solar/Wind Helper
2.535
970909AG2-566 GEN
50/50
5.54
3144293JTRSVLE
50/50
1.158
970535AG2-341 GEN
50/50
4.753
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.506
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.178
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.022
970323AG2-213 GEN
Solar/Wind Harmer
21.647
970933AG2-581 GEN
Solar/Wind Harmer
36.177
970099AG2-077 GEN
Solar/Wind Harmer
47.394
313527AB2-043 GEN
Solar/Wind Harmer
5.52
316237AB2-079_GEN
Solar/Wind Harmer
1.002
315687AD1-152 GEN
Solar/Wind Harmer
3.681
962561AG1-105 GEN
Solar/Wind Harmer
16.518
964791AG1-342 GEN
Solar/Wind Harmer
6.094
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.82
316248AF1-058 C
Solar/Wind Harmer
0.739
942751AE2-291 GEN
Solar/Wind Harmer
9.07
313506AB2-031 GEN
Solar/Wind Harmer
0.863
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.391
961601AG1-000A GEN
Solar/Wind Harmer
2.762
315724AD1-057 GEN
Solar/Wind Harmer
1.363
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.98
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.061
3145603CNETO
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.011
316313AB2-026
Solar/Wind Helper
0.312
3151541CLOVER2
50/50
6.765
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.736
946301AF1-294 GEN
Solar/Wind Harmer
13.156
961791AG1-021 GEN
Solar/Wind Harmer
6.418
970683AG2-441 GEN
Solar/Wind Harmer
31.154
970681AG2-440 GEN
Solar/Wind Harmer
20.677
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.546
316486AD2-202 GEN
Solar/Wind Harmer
0.901
316238AB2-078_GEN
Solar/Wind Harmer
1.002
316239AB2-077_GEN
Solar/Wind Harmer
1.002
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.878
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.979
270455AD2-022 GEN
Solar/Wind Harmer
1.593
270457AD2-023 GEN
Solar/Wind Harmer
0.808
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.908
316327AA2-057 GEN
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.22
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.672
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.159
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.281
316405AF2-144 C
Solar/Wind Helper
0.234
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.487
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.349
MECLTFEXP_MEC->PJM
CLTF
0.998
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.761
LAGNLTFEXP_LAGN->PJM
CLTF
2.651
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.334
TVALTFEXP_TVA->PJM
CLTF
1.312
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.313
WECLTFEXP_WEC->PJM
CLTF
0.159

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.37 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1037.09
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.33 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1225.59
MW Contribution:
5.58
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.158
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.815
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.418
970685AG2-442 GEN
Solar/Wind Harmer
40.479
316034AC1-036 C
Solar/Wind Harmer
0.777
315785AD2-033 C
Solar/Wind Harmer
9.425
315693AD1-088 GEN
Solar/Wind Harmer
20.651
3144293JTRSVLE
50/50
1.158
970413AG2-270 GEN
50/50
29.68
972003AH1-546 GEN
Solar/Wind Harmer
41.016
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.214
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.235
971775AH1-396 GEN
Solar/Wind Harmer
3.055
959311AF2-222 GEN
Solar/Wind Harmer
44.444
964241AG1-285 GEN
Solar/Wind Harmer
30.357
316478AD1-087 GEN
Solar/Wind Harmer
3.077
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971683AH1-343 GEN
Solar/Wind Harmer
8.941
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.755
316222AC1-221 GEN
Solar/Wind Harmer
1.409
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.499
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.678
3146233WITAKRS
Solar/Wind Harmer
0.158
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.797
315722AD1-056 GEN
Solar/Wind Harmer
2.478
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.424
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.075
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.728
270494AE1-108_GEN
Solar/Wind Helper
3.729
315821AE2-092 GEN
Solar/Wind Helper
2.535
957481AF2-042 GEN
Solar/Wind Harmer
118.484
316131AB2-060 GEN
Solar/Wind Harmer
3.728
970401AG2-262 GEN
Solar/Wind Harmer
1.862
971065AG2-659 GEN
Solar/Wind Harmer
10.95
316129AC1-054 GEN
Solar/Wind Harmer
1.833
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.541
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.908
316319Z2-044 C
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.973
3142053HEARTS
Solar/Wind Harmer
0.085
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.54
3144293JTRSVLE
50/50
1.158
970535AG2-341 GEN
50/50
4.753
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.506
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.178
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.022
970323AG2-213 GEN
Solar/Wind Harmer
21.647
970933AG2-581 GEN
Solar/Wind Harmer
36.177
970099AG2-077 GEN
Solar/Wind Harmer
47.394
313527AB2-043 GEN
Solar/Wind Harmer
5.52
316237AB2-079_GEN
Solar/Wind Harmer
1.002
315687AD1-152 GEN
Solar/Wind Harmer
3.681
962561AG1-105 GEN
Solar/Wind Harmer
16.518
964791AG1-342 GEN
Solar/Wind Harmer
6.094
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.82
316248AF1-058 C
Solar/Wind Harmer
0.739
942751AE2-291 GEN
Solar/Wind Harmer
9.07
313506AB2-031 GEN
Solar/Wind Harmer
0.863
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.391
961601AG1-000A GEN
Solar/Wind Harmer
2.762
315724AD1-057 GEN
Solar/Wind Harmer
1.363
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.98
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.061
3145603CNETO
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.011
316313AB2-026
Solar/Wind Helper
0.312
3151541CLOVER2
50/50
6.765
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.736
946301AF1-294 GEN
Solar/Wind Harmer
13.156
961791AG1-021 GEN
Solar/Wind Harmer
6.418
970683AG2-441 GEN
Solar/Wind Harmer
31.154
970681AG2-440 GEN
Solar/Wind Harmer
20.677
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.546
316486AD2-202 GEN
Solar/Wind Harmer
0.901
316238AB2-078_GEN
Solar/Wind Harmer
1.002
316239AB2-077_GEN
Solar/Wind Harmer
1.002
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.878
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.979
270455AD2-022 GEN
Solar/Wind Harmer
1.593
270457AD2-023 GEN
Solar/Wind Harmer
0.808
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.908
316327AA2-057 GEN
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.22
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.672
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.159
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.281
316405AF2-144 C
Solar/Wind Helper
0.234
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.487
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.349
MECLTFEXP_MEC->PJM
CLTF
0.998
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
5.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.761
LAGNLTFEXP_LAGN->PJM
CLTF
2.651
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.334
TVALTFEXP_TVA->PJM
CLTF
1.312
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.313
WECLTFEXP_WEC->PJM
CLTF
0.159

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.68 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1032.31
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:171.78 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1200.74
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
972003AH1-546 GEN
Solar/Wind Harmer
41.021
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.208
3147133PAMPLIN
Solar/Wind Harmer
-0.162
970257AG2-171 GEN
Solar/Wind Harmer
16.215
971775AH1-396 GEN
Solar/Wind Harmer
3.051
959311AF2-222 GEN
Solar/Wind Harmer
44.382
964241AG1-285 GEN
Solar/Wind Harmer
30.309
316478AD1-087 GEN
Solar/Wind Harmer
3.07
316003AC1-222 GEN
Solar/Wind Harmer
2.211
971683AH1-343 GEN
Solar/Wind Harmer
8.909
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.749
316222AC1-221 GEN
Solar/Wind Harmer
1.395
316283AC2-100 C
Solar/Wind Harmer
1.274
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.497
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.765
315722AD1-056 GEN
Solar/Wind Harmer
2.458
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.732
946301AF1-294 GEN
Solar/Wind Harmer
13.145
961791AG1-021 GEN
Solar/Wind Harmer
6.412
970683AG2-441 GEN
Solar/Wind Harmer
31.113
970681AG2-440 GEN
Solar/Wind Harmer
20.65
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.416
316486AD2-202 GEN
Solar/Wind Harmer
0.899
316238AB2-078_GEN
Solar/Wind Harmer
1
316239AB2-077_GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.854
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.978
270455AD2-022 GEN
Solar/Wind Harmer
1.57
270457AD2-023 GEN
Solar/Wind Harmer
0.796
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.903
316210AC1-098 GEN
Solar/Wind Harmer
1.214
316327AA2-057 GEN
Solar/Wind Harmer
0.781
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.657
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.421
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.303
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.08
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.72
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.412
970685AG2-442 GEN
Solar/Wind Harmer
40.43
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.413
315693AD1-088 GEN
Solar/Wind Harmer
20.618
957481AF2-042 GEN
Solar/Wind Harmer
118.263
316131AB2-060 GEN
Solar/Wind Harmer
3.721
970401AG2-262 GEN
Solar/Wind Harmer
1.857
971065AG2-659 GEN
Solar/Wind Harmer
10.923
316129AC1-054 GEN
Solar/Wind Harmer
1.828
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.54
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.907
316319Z2-044 C
Solar/Wind Harmer
0.413
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.962
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.157
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.015
970323AG2-213 GEN
Solar/Wind Harmer
21.621
970933AG2-581 GEN
Solar/Wind Harmer
36.112
970099AG2-077 GEN
Solar/Wind Harmer
47.305
313527AB2-043 GEN
Solar/Wind Harmer
5.511
316237AB2-079_GEN
Solar/Wind Harmer
1
315687AD1-152 GEN
Solar/Wind Harmer
3.67
962561AG1-105 GEN
Solar/Wind Harmer
16.477
964791AG1-342 GEN
Solar/Wind Harmer
6.078
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.814
316248AF1-058 C
Solar/Wind Harmer
0.736
942751AE2-291 GEN
Solar/Wind Harmer
9.035
313506AB2-031 GEN
Solar/Wind Harmer
0.862
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.21
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.77
316263AC1-034 GEN
Solar/Wind Harmer
3.352
961601AG1-000A GEN
Solar/Wind Harmer
2.73
315724AD1-057 GEN
Solar/Wind Harmer
1.352
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
316313AB2-026
Solar/Wind Helper
0.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.16 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:818.17
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.07 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:983.41
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3151281ROARAP4
50/50
0.112
971629AH1-314 GEN
50/50
5.731
3151561HALLBR1
50/50
0.157
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.87
970685AG2-442 GEN
Solar/Wind Harmer
30.706
316034AC1-036 C
Solar/Wind Harmer
0.025
315785AD2-033 C
Solar/Wind Harmer
2.995
315693AD1-088 GEN
Solar/Wind Harmer
17.617
957481AF2-042 GEN
Solar/Wind Harmer
89.82
316131AB2-060 GEN
Solar/Wind Harmer
0.958
970401AG2-262 GEN
Solar/Wind Harmer
1.486
971065AG2-659 GEN
Solar/Wind Harmer
8.296
316129AC1-054 GEN
Solar/Wind Harmer
0.695
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.161
3146233WITAKRS
Solar/Wind Harmer
0.265
3147123OTTER R
Solar/Wind Harmer
0.04
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.112
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151281ROARAP4
50/50
0.105
971845AH1-439 GEN
Solar/Wind Harmer
33.974
946301AF1-294 GEN
Solar/Wind Harmer
9.009
961791AG1-021 GEN
Solar/Wind Harmer
4.383
970683AG2-441 GEN
Solar/Wind Harmer
23.63
970681AG2-440 GEN
Solar/Wind Harmer
15.684
3144303KENBRDG
Solar/Wind Harmer
0.308
971967AH1-528 GEN
Solar/Wind Harmer
54.853
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970831AG2-522 GEN
Solar/Wind Harmer
7.484
3137643SOCKMAN
Solar/Wind Harmer
0.378
316426AA2-053 GEN
Solar/Wind Harmer
0.289
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.385
316210AC1-098 GEN
Solar/Wind Harmer
0.638
316327AA2-057 GEN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.661
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3151261ROARAP2
50/50
0.115
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
972003AH1-546 GEN
Solar/Wind Harmer
31.155
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.379
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
1.452
970257AG2-171 GEN
Solar/Wind Harmer
12.316
971775AH1-396 GEN
Solar/Wind Harmer
0.616
959311AF2-222 GEN
Solar/Wind Harmer
33.641
964241AG1-285 GEN
Solar/Wind Harmer
23.019
316478AD1-087 GEN
Solar/Wind Harmer
1.096
971683AH1-343 GEN
Solar/Wind Harmer
6.767
3147043LAWRENC
Solar/Wind Harmer
0.096
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316222AC1-221 GEN
Solar/Wind Harmer
0.507
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
316212AC1-099_GEN
Solar/Wind Harmer
0.356
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.044
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
4.396
315722AD1-056 GEN
Solar/Wind Harmer
2.125
3145796HORNRTN
Solar/Wind Harmer
0.243
3145796HORNRTN
Solar/Wind Harmer
0.061
316011AB1-132 GEN
Solar/Wind Harmer
1.098
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3145823KELFORD
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.2
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.253
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.219
3151371ROSEMS1
50/50
0.136
3151381ROSEMG2
50/50
0.102
3146776BUCKING
Solar/Wind Harmer
3.039
3146776BUCKING
Solar/Wind Harmer
0.246
970301AG2-198 GEN
Solar/Wind Harmer
22.145
3147133PAMPLIN
Solar/Wind Harmer
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.479
970323AG2-213 GEN
Solar/Wind Harmer
16.421
970933AG2-581 GEN
Solar/Wind Harmer
27.427
970099AG2-077 GEN
Solar/Wind Harmer
35.928
962561AG1-105 GEN
Solar/Wind Harmer
12.514
964791AG1-342 GEN
Solar/Wind Harmer
4.862
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.862
313506AB2-031 GEN
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.613
3145783HORNRTN
Solar/Wind Harmer
1.291
3145783HORNRTN
Solar/Wind Harmer
0.403
3145783HORNRTN
Solar/Wind Harmer
0.161
316049AB1-081 GEN
Solar/Wind Harmer
0.362
316263AC1-034 GEN
Solar/Wind Harmer
2.419
961601AG1-000A GEN
Solar/Wind Harmer
1.099
315724AD1-057 GEN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.182
962571AG1-106 GEN
Solar/Wind Harmer
0.862
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.054
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.103
316313AB2-026
Solar/Wind Helper
0.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.58 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:989.64
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.87 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1159.42
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.732
946301AF1-294 GEN
Solar/Wind Harmer
13.145
961791AG1-021 GEN
Solar/Wind Harmer
6.412
970683AG2-441 GEN
Solar/Wind Harmer
31.113
970681AG2-440 GEN
Solar/Wind Harmer
20.65
3144303KENBRDG
Solar/Wind Harmer
-0.035
316486AD2-202 GEN
Solar/Wind Harmer
0.899
316238AB2-078_GEN
Solar/Wind Harmer
1
316239AB2-077_GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.854
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.978
270455AD2-022 GEN
Solar/Wind Harmer
1.57
270457AD2-023 GEN
Solar/Wind Harmer
0.796
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.903
316210AC1-098 GEN
Solar/Wind Harmer
1.214
316327AA2-057 GEN
Solar/Wind Harmer
0.781
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.657
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
972003AH1-546 GEN
Solar/Wind Harmer
41.021
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.208
3147133PAMPLIN
Solar/Wind Harmer
-0.162
970257AG2-171 GEN
Solar/Wind Harmer
16.215
971775AH1-396 GEN
Solar/Wind Harmer
3.051
959311AF2-222 GEN
Solar/Wind Harmer
44.382
964241AG1-285 GEN
Solar/Wind Harmer
30.309
316478AD1-087 GEN
Solar/Wind Harmer
3.07
316003AC1-222 GEN
Solar/Wind Harmer
2.211
971683AH1-343 GEN
Solar/Wind Harmer
8.909
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.749
316222AC1-221 GEN
Solar/Wind Harmer
1.395
316283AC2-100 C
Solar/Wind Harmer
1.274
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.497
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.765
315722AD1-056 GEN
Solar/Wind Harmer
2.458
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.421
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.303
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.08
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.72
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.412
970685AG2-442 GEN
Solar/Wind Harmer
40.43
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.413
315693AD1-088 GEN
Solar/Wind Harmer
20.618
957481AF2-042 GEN
Solar/Wind Harmer
118.263
316131AB2-060 GEN
Solar/Wind Harmer
3.721
970401AG2-262 GEN
Solar/Wind Harmer
1.857
971065AG2-659 GEN
Solar/Wind Harmer
10.923
316129AC1-054 GEN
Solar/Wind Harmer
1.828
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.54
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.907
316319Z2-044 C
Solar/Wind Harmer
0.413
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.962
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.157
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.015
970323AG2-213 GEN
Solar/Wind Harmer
21.621
970099AG2-077 GEN
Solar/Wind Harmer
47.305
313527AB2-043 GEN
Solar/Wind Harmer
5.511
316237AB2-079_GEN
Solar/Wind Harmer
1
315687AD1-152 GEN
Solar/Wind Harmer
3.67
962561AG1-105 GEN
Solar/Wind Harmer
16.477
964791AG1-342 GEN
Solar/Wind Harmer
6.078
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.814
316248AF1-058 C
Solar/Wind Harmer
0.736
942751AE2-291 GEN
Solar/Wind Harmer
9.035
313506AB2-031 GEN
Solar/Wind Harmer
0.862
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.21
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.77
316263AC1-034 GEN
Solar/Wind Harmer
3.352
961601AG1-000A GEN
Solar/Wind Harmer
2.73
315724AD1-057 GEN
Solar/Wind Harmer
1.352
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
316313AB2-026
Solar/Wind Helper
0.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.58 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:989.64
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.87 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1159.42
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.732
946301AF1-294 GEN
Solar/Wind Harmer
13.145
961791AG1-021 GEN
Solar/Wind Harmer
6.412
970683AG2-441 GEN
Solar/Wind Harmer
31.113
970681AG2-440 GEN
Solar/Wind Harmer
20.65
3144303KENBRDG
Solar/Wind Harmer
-0.035
316486AD2-202 GEN
Solar/Wind Harmer
0.899
316238AB2-078_GEN
Solar/Wind Harmer
1
316239AB2-077_GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.854
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.978
270455AD2-022 GEN
Solar/Wind Harmer
1.57
270457AD2-023 GEN
Solar/Wind Harmer
0.796
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.903
316210AC1-098 GEN
Solar/Wind Harmer
1.214
316327AA2-057 GEN
Solar/Wind Harmer
0.781
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.657
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
972003AH1-546 GEN
Solar/Wind Harmer
41.021
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.208
3147133PAMPLIN
Solar/Wind Harmer
-0.162
970257AG2-171 GEN
Solar/Wind Harmer
16.215
971775AH1-396 GEN
Solar/Wind Harmer
3.051
959311AF2-222 GEN
Solar/Wind Harmer
44.382
964241AG1-285 GEN
Solar/Wind Harmer
30.309
316478AD1-087 GEN
Solar/Wind Harmer
3.07
316003AC1-222 GEN
Solar/Wind Harmer
2.211
971683AH1-343 GEN
Solar/Wind Harmer
8.909
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.749
316222AC1-221 GEN
Solar/Wind Harmer
1.395
316283AC2-100 C
Solar/Wind Harmer
1.274
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.497
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.765
315722AD1-056 GEN
Solar/Wind Harmer
2.458
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.421
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.303
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.08
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.72
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.412
970685AG2-442 GEN
Solar/Wind Harmer
40.43
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.413
315693AD1-088 GEN
Solar/Wind Harmer
20.618
957481AF2-042 GEN
Solar/Wind Harmer
118.263
316131AB2-060 GEN
Solar/Wind Harmer
3.721
970401AG2-262 GEN
Solar/Wind Harmer
1.857
971065AG2-659 GEN
Solar/Wind Harmer
10.923
316129AC1-054 GEN
Solar/Wind Harmer
1.828
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.54
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.907
316319Z2-044 C
Solar/Wind Harmer
0.413
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.962
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.157
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.015
970323AG2-213 GEN
Solar/Wind Harmer
21.621
970099AG2-077 GEN
Solar/Wind Harmer
47.305
313527AB2-043 GEN
Solar/Wind Harmer
5.511
316237AB2-079_GEN
Solar/Wind Harmer
1
315687AD1-152 GEN
Solar/Wind Harmer
3.67
962561AG1-105 GEN
Solar/Wind Harmer
16.477
964791AG1-342 GEN
Solar/Wind Harmer
6.078
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.814
316248AF1-058 C
Solar/Wind Harmer
0.736
942751AE2-291 GEN
Solar/Wind Harmer
9.035
313506AB2-031 GEN
Solar/Wind Harmer
0.862
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.21
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.77
316263AC1-034 GEN
Solar/Wind Harmer
3.352
961601AG1-000A GEN
Solar/Wind Harmer
2.73
315724AD1-057 GEN
Solar/Wind Harmer
1.352
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
316313AB2-026
Solar/Wind Helper
0.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.31 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:801.9
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:169.49 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:968.67
MW Contribution:
5.57
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.219
3151371ROSEMS1
50/50
0.136
3151381ROSEMG2
50/50
0.102
3146776BUCKING
Solar/Wind Harmer
3.039
3146776BUCKING
Solar/Wind Harmer
0.246
970301AG2-198 GEN
Solar/Wind Harmer
22.145
3147133PAMPLIN
Solar/Wind Harmer
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.479
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3151261ROARAP2
50/50
0.115
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
972003AH1-546 GEN
Solar/Wind Harmer
31.155
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.379
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
1.452
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151281ROARAP4
50/50
0.105
971845AH1-439 GEN
Solar/Wind Harmer
33.974
946301AF1-294 GEN
Solar/Wind Harmer
9.009
961791AG1-021 GEN
Solar/Wind Harmer
4.383
970683AG2-441 GEN
Solar/Wind Harmer
23.63
970681AG2-440 GEN
Solar/Wind Harmer
15.684
3144303KENBRDG
Solar/Wind Harmer
0.308
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970831AG2-522 GEN
Solar/Wind Harmer
7.484
3137643SOCKMAN
Solar/Wind Harmer
0.378
316426AA2-053 GEN
Solar/Wind Harmer
0.289
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.385
316210AC1-098 GEN
Solar/Wind Harmer
0.638
316327AA2-057 GEN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.661
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970323AG2-213 GEN
Solar/Wind Harmer
16.421
970099AG2-077 GEN
Solar/Wind Harmer
35.928
962561AG1-105 GEN
Solar/Wind Harmer
12.514
964791AG1-342 GEN
Solar/Wind Harmer
4.862
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.862
313506AB2-031 GEN
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.613
3145783HORNRTN
Solar/Wind Harmer
1.291
3145783HORNRTN
Solar/Wind Harmer
0.403
3145783HORNRTN
Solar/Wind Harmer
0.161
316049AB1-081 GEN
Solar/Wind Harmer
0.362
316263AC1-034 GEN
Solar/Wind Harmer
2.419
961601AG1-000A GEN
Solar/Wind Harmer
1.099
315724AD1-057 GEN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.182
962571AG1-106 GEN
Solar/Wind Harmer
0.862
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.054
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.103
316313AB2-026
Solar/Wind Helper
0.311
970257AG2-171 GEN
Solar/Wind Harmer
12.316
971775AH1-396 GEN
Solar/Wind Harmer
0.616
959311AF2-222 GEN
Solar/Wind Harmer
33.641
964241AG1-285 GEN
Solar/Wind Harmer
23.019
316478AD1-087 GEN
Solar/Wind Harmer
1.096
971683AH1-343 GEN
Solar/Wind Harmer
6.767
3147043LAWRENC
Solar/Wind Harmer
0.096
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316222AC1-221 GEN
Solar/Wind Harmer
0.507
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
316212AC1-099_GEN
Solar/Wind Harmer
0.356
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.044
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
4.396
315722AD1-056 GEN
Solar/Wind Harmer
2.125
3145796HORNRTN
Solar/Wind Harmer
0.243
3145796HORNRTN
Solar/Wind Harmer
0.061
316011AB1-132 GEN
Solar/Wind Harmer
1.098
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3145823KELFORD
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3151281ROARAP4
50/50
0.112
971629AH1-314 GEN
50/50
5.731
3151561HALLBR1
50/50
0.157
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.87
970685AG2-442 GEN
Solar/Wind Harmer
30.706
316034AC1-036 C
Solar/Wind Harmer
0.025
315785AD2-033 C
Solar/Wind Harmer
2.995
315693AD1-088 GEN
Solar/Wind Harmer
17.617
957481AF2-042 GEN
Solar/Wind Harmer
89.82
316131AB2-060 GEN
Solar/Wind Harmer
0.958
970401AG2-262 GEN
Solar/Wind Harmer
1.486
971065AG2-659 GEN
Solar/Wind Harmer
8.296
316129AC1-054 GEN
Solar/Wind Harmer
0.695
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.161
3146233WITAKRS
Solar/Wind Harmer
0.265
3147123OTTER R
Solar/Wind Harmer
0.04
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.2
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A_SENS'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 313378 CKT 1   /*8MDLTHAN     500.0 - 8VONTAY      500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 313378 CKT 1                /*8MDLTHAN     500.0 - 8VONTAY      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 314914 TO BUS 313378 CKT 1   /*8MDLTHAN     500.0 - 8VONTAY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-3'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P4-2: 242T2027_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P4-2: 202712_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1                /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1                /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                                /*6POWHATN     230.0
 OPEN BUS 316258                                                /*AE1-075 C    230.0
 OPEN BUS 316313                                                /*AB2-026      230.0
 OPEN BUS 316405                                                /*AF2-144 C    230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
END
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 587T591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 55692_SRT-S'
 OPEN BRANCH FROM BUS 314936 TO BUS 971966 CKT 1                /*8RAWLINGS    500.0 - AH1-528 TP   500.0
 OPEN BUS 314920                                                /*8RAWLIN_STC1 500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-5: 556X2_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 556X1_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 593X1_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-5: 593X2_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS'
 OPEN BRANCH FROM BUS 313996 TO BUS 888888 CKT 1   /*6FINNEYWOOD  230.0 - AG1-285_230  230.0
 OPEN BRANCH FROM BUS 957480 TO BUS 313995 CKT 1   /*AF2-042 TP   500.0 - 8FINNEYWOOD  500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314677 to 972002 ckt 1
314563 to 313994 ckt 1
313178 to 314435 ckt 1
314692 to 971844 ckt 1
313996 to 313995 ckt 1
313996 to 313995 ckt 2
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1
313994 to 313178 ckt 1
314435 to 314282 ckt 1
316281 to 304070 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
DVP_P1-2: LN 2193_SRT-A
SingleAC110.92 %134.42B149.09
0.62
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC175.55 %678.68B1191.4
2.57
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC173.13 %830.0C1436.99
2.56
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC173.13 %830.0C1436.97
2.56
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC160.47 %830.0C1331.88
2.54
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC160.47 %830.0C1331.88
2.54
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B3_SRT-A
BusAC109.69 %830.0C910.4
2.66
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC105.52 %800.88B845.12
1.87
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC105.13 %800.88B841.95
1.87
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC174.45 %678.68B1183.97
2.57
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC172.24 %830.0C1429.6
2.56
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC172.24 %830.0C1429.58
2.56
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC159.58 %830.0C1324.55
2.54
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC159.58 %830.0C1324.55
2.54
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B3_SRT-A
BusAC108.83 %830.0C903.29
2.66
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC115.17 %571.52B658.25
6.35
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC112.6 %571.52B643.52
6.35
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC111.18 %699.0C777.13
6.35
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC111.14 %699.0C776.84
6.35
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC107.98 %699.0C754.79
6.35
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC102.05 %699.0C713.33
6.35
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC102.05 %699.0C713.33
6.35
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC107.83 %800.88B863.6
1.87
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC107.43 %800.88B860.42
1.87
GD2DVP
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC106.53 %984.18B1048.43
0.69
GD2DVP
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
DVP_P1-2: LN 550_SRT-A
SingleAC105.27 %984.18B1036.09
0.72
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC171.33 %678.68B1162.8
2.4
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC167.37 %830.0C1389.21
2.39
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC167.37 %830.0C1389.18
2.39
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC159.8 %830.0C1326.36
2.37
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC159.8 %830.0C1326.36
2.37
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC127.81 %830.0C1060.79
2.81
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC173.1 %661.76B1145.53
2.4
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC169.58 %809.0C1371.94
2.39
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC169.58 %809.0C1371.91
2.39
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC161.82 %809.0C1309.09
2.37
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC161.82 %809.0C1309.09
2.37
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC169.7 %661.76B1122.99
2.4
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC166.8 %809.0C1349.42
2.39
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC166.8 %809.0C1349.39
2.39
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC159.03 %809.0C1286.56
2.37
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC159.03 %809.0C1286.56
2.37
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC126.21 %809.0C1021.03
2.81
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC112.29 %800.88B899.3
2.11
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.55 %800.88B893.41
1.87
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2054_SRT-A
BreakerAC103.57 %980.0C1014.95
2.11
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 233T2028_SRT-A
BreakerAC101.84 %980.0C998.06
2.11
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2193_SRT-A
BreakerAC101.81 %980.0C997.75
2.14
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: WT2193_SRT-A
BreakerAC101.79 %980.0C997.51
2.14
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC101.67 %980.0C996.36
1.87
GD2DVP
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.13 %984.18B1015.01
0.69
GD2DVP
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
DVP_P1-2: LN 550_SRT-A
SingleAC101.87 %984.18B1002.59
0.72
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC103.68 %3940.0C4085.15
3.04
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 298_SRT-A-4
SingleAC103.61 %3220.44B3336.6
3.09
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC107.8 %3220.44B3471.53
2.71
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC102.28 %3940.0C4029.88
2.81
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC130.61 %4070.2B5316.1
3.79
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC125.49 %4070.2B5107.87
3.79
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 58572_SRT-A
BreakerAC117.11 %4996.0C5851.06
3.79
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-5: W72_SRT-A
BreakerAC116.55 %4996.0C5822.84
3.77
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: XT585_SRT-S
BreakerAC109.34 %4996.0C5462.74
3.79
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 54472_SRT-S
BreakerAC104.29 %2858.0C2980.61
2.9
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC118.98 %4070.2B4842.86
3.31
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC105.0 %4996.0C5245.63
3.31
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC104.56 %4996.0C5223.84
3.29
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC103.0 %4996.0C5145.98
3.26
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC112.15 %800.88B898.18
2.11
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.87 %800.88B895.98
1.87
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2054_SRT-A
BreakerAC103.54 %980.0C1014.73
2.11
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC102.07 %980.0C1000.24
1.87
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC102.06 %980.0C1000.22
1.87
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 233T2028_SRT-A
BreakerAC101.82 %980.0C997.84
2.11
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2193_SRT-A
BreakerAC101.77 %980.0C997.37
2.14
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC127.1 %4070.2B5173.4
3.31
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC113.85 %4996.0C5687.87
3.31
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC113.35 %4996.0C5662.94
3.29
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC111.73 %4996.0C5581.87
3.26
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC116.16 %571.52B663.9
6.35
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC113.59 %571.52B649.19
6.35
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC111.99 %699.0C782.79
6.35
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC111.95 %699.0C782.5
6.35
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC108.79 %699.0C760.44
6.35
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC102.86 %699.0C719.0
6.35
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC102.86 %699.0C719.0
6.35
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC121.2 %4070.2B4933.15
3.31
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC108.55 %4996.0C5423.36
3.31
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC108.09 %4996.0C5400.34
3.29
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC106.51 %4996.0C5321.19
3.26
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC109.1 %800.88B873.8
1.87
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC108.71 %800.88B870.6
1.87
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC103.13 %684.0C705.38
4.04
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC105.44 %699.0C736.99
4.03
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC100.97 %699.0C705.81
4.08

Details for 3BREMO-3FORK UNION 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.92 %
Rating:134.42 MVA
Rating Type:B
MVA to Mitigate:149.09
MW Contribution:
0.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.151
970221AG2-151 GEN
Solar/Wind Harmer
10.888
270494AE1-108_GEN
Solar/Wind Harmer
1.906
972003AH1-546 GEN
Solar/Wind Harmer
4.195
3146776BUCKING
Solar/Wind Harmer
0.035
3146926FARMVIL
Solar/Wind Harmer
0.046
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.97
958131AF2-107 GEN
Solar/Wind Harmer
1.795
3147133PAMPLIN
Solar/Wind Harmer
0.179
315821AE2-092 GEN
Solar/Wind Helper
3.512
972205AH1-687 GEN
50/50
5.623
971845AH1-439 GEN
Solar/Wind Harmer
4.382
316258AE1-075 C
Solar/Wind Harmer
0.048
970909AG2-566 GEN
50/50
0.616
3146776BUCKING
Solar/Wind Harmer
0.394
3146776BUCKING
Solar/Wind Harmer
0.032
316336AC2-165 C
Solar/Wind Harmer
3.78
316313AB2-026
Solar/Wind Harmer
0.04
970301AG2-198 GEN
Solar/Wind Harmer
2.465
3147133PAMPLIN
Solar/Wind Harmer
0.057
3147133PAMPLIN
Solar/Wind Harmer
0.046
970099AG2-077 GEN
Solar/Wind Harmer
2.64
3151931BEARGRDN S1
50/50
1.487
3151911BEARGRDN G1
50/50
1.151
971377AH1-170 GEN
Solar/Wind Harmer
2.178
3147623JAMES R
Solar/Wind Harmer
0.473
970937AG2-583 GEN
Solar/Wind Harmer
6.218
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.046
3143336POWHATN
Solar/Wind Harmer
1.141
957481AF2-042 GEN
Solar/Wind Harmer
6.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.085
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.599
MECLTFEXP_MEC->PJM
CLTF
0.086
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.611
LAGNLTFEXP_LAGN->PJM
CLTF
0.384
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.756
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.111
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.006

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.55 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1191.4
MW Contribution:
2.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.566
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.241
3151581KERR 1
50/50
0.082
3152661PLYWOOD A
50/50
0.224
3151041BRUNSWICKG3
50/50
1.136
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.414
315241AE2-183_GT1
50/50
1.41
972185AH1-677 GEN
50/50
5.112
3151261ROARAP2
50/50
0.1
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
316336AC2-165 C
Solar/Wind Harmer
15.638
316313AB2-026
Solar/Wind Harmer
0.168
970301AG2-198 GEN
Solar/Wind Harmer
10.263
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.679
970323AG2-213 GEN
Solar/Wind Harmer
7.893
971223AH1-071 GEN
Solar/Wind Harmer
1.335
962561AG1-105 GEN
Solar/Wind Harmer
5.682
970099AG2-077 GEN
Solar/Wind Harmer
12.508
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
316118AC1-105 GEN
Solar/Wind Harmer
0.268
970933AG2-581 GEN
Solar/Wind Harmer
7.997
313506AB2-031 GEN
Solar/Wind Harmer
0.263
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316365GEN2_N
Solar/Wind Harmer
0.174
3144356SAPONY
Solar/Wind Harmer
0.654
3151931BEARGRDN S1
50/50
5.865
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.682
3151531CLOVER1
50/50
2.505
3151591KERR 2
50/50
0.231
3151641KERR 7
50/50
0.231
3147043LAWRENC
50/50
1.001
3151051BRUNSWICKS1
50/50
2.358
3151021BRUNSWICKG1
50/50
1.136
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.414
3151281ROARAP4
50/50
0.099
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.202
3151411GASTONB
50/50
0.202
970937AG2-583 GEN
Solar/Wind Harmer
24.929
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
3143336POWHATN
Solar/Wind Harmer
4.81
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.92
316034AC1-036 C
Solar/Wind Harmer
0.012
315785AD2-033 C
Solar/Wind Harmer
1.433
316131AB2-060 GEN
Solar/Wind Harmer
0.448
315693AD1-088 GEN
Solar/Wind Harmer
6.777
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.271
970401AG2-262 GEN
Solar/Wind Harmer
0.671
316315AB2-025 C
Solar/Wind Harmer
0.063
962571AG1-106 GEN
Solar/Wind Harmer
1.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316140AB2-099
Solar/Wind Harmer
0.026
315742AE1-103 GEN
Solar/Wind Harmer
1.084
315724AD1-057 GEN
Solar/Wind Harmer
1.363
316349AD2-085 GEN
Solar/Wind Harmer
0.047
316065AD1-022 GEN
Solar/Wind Harmer
3.224
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315614AA2-178 GEN
Solar/Wind Harmer
0.395
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146386ELIZ CT
Solar/Wind Harmer
0.069
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.216
316339AD2-160 GEN
Solar/Wind Harmer
0.11
316388AE2-253 GEN
Solar/Wind Harmer
0.214
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.514
316049AB1-081 GEN
Solar/Wind Harmer
0.387
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
316294AC1-161 GEN
Solar/Wind Harmer
1.166
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316005AA1-067
Solar/Wind Harmer
0.072
316033AB2-134 GEN
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.447
316129AC1-054 GEN
Solar/Wind Harmer
0.383
960081AF2-299 GEN
Solar/Wind Harmer
0.847
941031AE2-094 GEN
Solar/Wind Harmer
15.643
970919AG2-571 GEN
Solar/Wind Harmer
2.954
970087AG2-069 GEN
Solar/Wind Harmer
6.56
3145783HORNRTN
Solar/Wind Harmer
0.082
940641AE2-051 GEN
Solar/Wind Harmer
6.46
315607AA1-063A GEN
Solar/Wind Harmer
0.162
316023GEN1_S
Solar/Wind Harmer
0.174
939411AE1-173 GEN
Solar/Wind Harmer
33.164
3146263WOODLND
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.335
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3156021HOLLOMANSOL
Solar/Wind Harmer
0.319
316381AD1-082 GEN
Solar/Wind Harmer
0.072
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.498
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
315737AD1-076 GEN
Solar/Wind Harmer
0.894
316093AE2-104_GEN
Solar/Wind Harmer
1.171
315816AE2-034 GEN
Solar/Wind Harmer
0.297
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.559
3130156CHOWAN
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
0
319010AE1-072 C
Solar/Wind Harmer
0.343
3146456SLIGO L269
Solar/Wind Harmer
0.069
944591AF1-124 GEN
Solar/Wind Harmer
15.516
3145963POPLR C
Solar/Wind Harmer
0.069
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.012
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.242
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.024
3146293MARTNCO
Solar/Wind Harmer
0.063
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.196
3150701DARBY 4
Adder
4.186
3150681DARBY 2
Adder
4.181
3150671DARBY 1
Adder
4.176
942751AE2-291 GEN
Solar/Wind Harmer
3.156
966001AG1-469 GEN
Solar/Wind Helper
0.19
972205AH1-687 GEN
50/50
22.181
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.485
3151601KERR 3
50/50
0.231
3151611KERR 4
50/50
0.231
3151621KERR 5
50/50
0.231
3151631KERR 6
50/50
0.231
963041AG1-153 GEN
50/50
2.3
315244AE2-183_ST
50/50
2.456
3151281ROARAP4
50/50
0.093
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.514
316258AE1-075 C
Solar/Wind Harmer
0.202
946301AF1-294 GEN
Solar/Wind Harmer
4.405
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
12.335
970681AG2-440 GEN
Solar/Wind Harmer
8.187
3144303KENBRDG
Solar/Wind Harmer
0.148
316486AD2-202 GEN
Solar/Wind Harmer
0.119
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
970831AG2-522 GEN
Solar/Wind Harmer
4.275
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.957
970673AG2-436 GEN
Solar/Wind Harmer
10.614
970533AG2-339 GEN
Solar/Wind Harmer
6.417
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.374
970581AG2-369 GEN
Solar/Wind Harmer
3.761
316426AA2-053 GEN
Solar/Wind Harmer
0.271
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.194
315652AC1-086 GEN
Solar/Wind Harmer
8.309
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
316274AC1-208 GEN
Solar/Wind Harmer
0.387
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
316210AC1-098 GEN
Solar/Wind Harmer
0.683
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
316463AE2-346 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
0.154
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.106
970657AG2-426 GEN
Solar/Wind Harmer
0.518
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.621
316311AC2-079 GEN
Solar/Wind Harmer
2.01
315732AD1-074 GEN1
Solar/Wind Harmer
0.397
315733AD1-074 GEN2
Solar/Wind Harmer
0.397
3130546PLYMOUTH
Solar/Wind Harmer
0.07
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
957871AF2-081 GEN
Solar/Wind Harmer
3.42
316316AC1-027 C
Solar/Wind Harmer
0.065
3151081ELIZAR1
Adder
6.27
3151091ELIZAR2
Adder
6.161
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
957861AF2-080 GEN
Solar/Wind Harmer
2.904
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
971445AH1-216 GEN
Solar/Wind Harmer
4.705
3151201GRAVEL4
Adder
4.805
3151221GRAVEL6
Adder
4.799
3151191GRAVEL3
Adder
4.744
3151211GRAVEL5
Adder
4.744
315697AD1-025 GEN
Solar/Wind Harmer
0.071
316159AE1-175 C
Solar/Wind Harmer
0.049
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.1
3148463FAIRFLD
Solar/Wind Helper
0.12
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.908
3151031BRUNSWICKG2
50/50
1.136
3151261ROARAP2
50/50
0.102
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.202
3151411GASTONB
50/50
0.202
972003AH1-546 GEN
Solar/Wind Harmer
16.566
3146776BUCKING
Solar/Wind Harmer
0.142
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
4.089
3147133PAMPLIN
Solar/Wind Harmer
0.741
959311AF2-222 GEN
Solar/Wind Harmer
16.947
970257AG2-171 GEN
Solar/Wind Harmer
5.92
971775AH1-396 GEN
Solar/Wind Harmer
0.296
964241AG1-285 GEN
Solar/Wind Harmer
10.433
970221AG2-151 GEN
Solar/Wind Harmer
7.011
316478AD1-087 GEN
Solar/Wind Harmer
0.404
3147043LAWRENC
Solar/Wind Harmer
0.063
270494AE1-108_GEN
Solar/Wind Harmer
1.23
316181AB2-040 GEN
Solar/Wind Harmer
0.122
944011AF1-069 GEN
Solar/Wind Harmer
5.111
970917AG2-570 GEN
Solar/Wind Harmer
7.385
971683AH1-343 GEN
Solar/Wind Harmer
2.995
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.37
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
0.073
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.785
315722AD1-056 GEN
Solar/Wind Harmer
2.443
970657AG2-426 GEN
Solar/Wind Harmer
1.583
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315735AD1-075 GEN1
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.012
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
316017AA1-139 ULT1
Solar/Wind Harmer
0.037
944581AF1-123 GEN
Solar/Wind Harmer
15.462
944601AF1-125 GEN
Solar/Wind Harmer
15.223
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.35
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
316222AC1-221 GEN
Solar/Wind Harmer
0.281
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
4.809
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.263
316458AB2-190 GEN2
Solar/Wind Harmer
0.351
970133AG2-095 GEN
Solar/Wind Harmer
0.63
316123AC1-075 GEN
Solar/Wind Harmer
0.087
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.513
3132273ORANGE
Solar/Wind Helper
0.027
3147666LOUISA
Solar/Wind Helper
0.273
315616AA1-038_C
Solar/Wind Helper
0.545
315773AC2-141 GEN
Solar/Wind Harmer
2.463
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.228
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.458
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316132AB2-190 GEN1
Solar/Wind Harmer
0.351
944631AF1-128 GEN
Adder
29.459
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.825
3147666LOUISA
Solar/Wind Helper
0.474
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.732
MECLTFEXP_MEC->PJM
CLTF
0.357
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.299
LAGNLTFEXP_LAGN->PJM
CLTF
1.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.539
TVALTFEXP_TVA->PJM
CLTF
0.872
NYPJM->LTFIMP_NY
CLTF
0.578
LGEELTFEXP_LGEE->PJM
CLTF
0.049
WECLTFEXP_WEC->PJM
CLTF
0.019

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.13 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1436.99
MW Contribution:
2.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.533
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.896
972003AH1-546 GEN
Solar/Wind Harmer
21.779
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.602
3143336POWHATN
Solar/Wind Harmer
3.063
3147133PAMPLIN
Solar/Wind Harmer
-0.083
959311AF2-222 GEN
Solar/Wind Harmer
22.328
970257AG2-171 GEN
Solar/Wind Harmer
7.784
971775AH1-396 GEN
Solar/Wind Harmer
1.465
964241AG1-285 GEN
Solar/Wind Harmer
13.72
970221AG2-151 GEN
Solar/Wind Harmer
9.179
316478AD1-087 GEN
Solar/Wind Harmer
1.131
3147043LAWRENC
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Harmer
2.99
972205AH1-687 GEN
50/50
22.147
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.483
3151601KERR 3
50/50
0.23
3151611KERR 4
50/50
0.23
3151621KERR 5
50/50
0.23
3151631KERR 6
50/50
0.23
316322AB2-045
Solar/Wind Harmer
1.48
971845AH1-439 GEN
Solar/Wind Harmer
23.026
316258AE1-075 C
Solar/Wind Harmer
0.735
316405AF2-144 C
Solar/Wind Harmer
0.776
946301AF1-294 GEN
Solar/Wind Harmer
6.418
961791AG1-021 GEN
Solar/Wind Harmer
3.131
970683AG2-441 GEN
Solar/Wind Harmer
16.22
970681AG2-440 GEN
Solar/Wind Harmer
10.765
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.466
316239AB2-077_GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.331
316233AE1-074 FULL
Solar/Wind Harmer
0.318
970909AG2-566 GEN
50/50
2.562
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.238
3151581KERR 1
50/50
0.082
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
21.624
316313AB2-026
Solar/Wind Harmer
0.817
970301AG2-198 GEN
Solar/Wind Harmer
13.495
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
970323AG2-213 GEN
Solar/Wind Harmer
10.378
313527AB2-043 GEN
Solar/Wind Harmer
2.566
316237AB2-079_GEN
Solar/Wind Harmer
0.466
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.472
970099AG2-077 GEN
Solar/Wind Harmer
16.454
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
315687AD1-152 GEN
Solar/Wind Harmer
1.429
3143526WINTERP
Solar/Wind Harmer
-0.061
316118AC1-105 GEN
Solar/Wind Harmer
0.805
970933AG2-581 GEN
Solar/Wind Harmer
10.522
316248AF1-058 C
Solar/Wind Harmer
0.321
972187AH1-678 GEN
Adder
2.455
972185AH1-677 GEN
Adder
4.816
313506AB2-031 GEN
Solar/Wind Harmer
0.771
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316365GEN2_N
Solar/Wind Harmer
0.593
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.236
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.055
315742AE1-103 GEN
Solar/Wind Harmer
1.935
316083AB2-161 GEN
Solar/Wind Harmer
1.287
315724AD1-057 GEN
Solar/Wind Harmer
1.554
316349AD2-085 GEN
Solar/Wind Harmer
0.699
316065AD1-022 GEN
Solar/Wind Harmer
3.933
315835AF2-110_GEN
Solar/Wind Harmer
0.979
315614AA2-178 GEN
Solar/Wind Harmer
0.84
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316435W1029_GEN3
Solar/Wind Harmer
1.405
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316240AF1-291 C
Solar/Wind Harmer
0.233
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316388AE2-253 GEN
Solar/Wind Harmer
0.519
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.811
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.538
316049AB1-081 GEN
Solar/Wind Harmer
0.822
316263AC1-034 GEN
Solar/Wind Harmer
3.582
316294AC1-161 GEN
Solar/Wind Harmer
2.453
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
2.985
3145493TOT1
Solar/Wind Harmer
0.117
3145453TOT5
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.152
316033AB2-134 GEN
Solar/Wind Harmer
2.383
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
-0.001
3150691DARBY 3
Adder
4.202
3150701DARBY 4
Adder
4.192
3150681DARBY 2
Adder
4.188
3150671DARBY 1
Adder
4.183
942751AE2-291 GEN
Solar/Wind Harmer
4.144
966001AG1-469 GEN
Solar/Wind Helper
0.199
316003AC1-222 GEN
Solar/Wind Harmer
0.97
966621AG1-532 GEN
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
1.34
944011AF1-069 GEN
Solar/Wind Harmer
5.605
970917AG2-570 GEN
Solar/Wind Harmer
23.325
3150861SPRUNCD
Adder
0.375
971683AH1-343 GEN
Solar/Wind Harmer
3.936
316190AA2-174 GEN
Solar/Wind Harmer
0.112
3156081AA2-088 GEN
Solar/Wind Harmer
2.772
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.772
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.722
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.986
315722AD1-056 GEN
Solar/Wind Harmer
2.825
970657AG2-426 GEN
Solar/Wind Harmer
1.602
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.79
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.208
316305AF2-043 C
Solar/Wind Harmer
0.233
316246AF1-032 C
Solar/Wind Harmer
0.156
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.894
316017AA1-139 ULT1
Solar/Wind Harmer
0.623
944581AF1-123 GEN
Solar/Wind Harmer
35.113
944601AF1-125 GEN
Solar/Wind Harmer
34.565
3145963POPLR C
Solar/Wind Harmer
-0.008
3142956BIRDNECK
Solar/Wind Harmer
0.413
3151101ELIZAR3
Adder
6.353
3144873MCLAUGH
Solar/Wind Harmer
0
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Harmer
0.772
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.022
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
316420AA1-050 GEN
Solar/Wind Harmer
0.862
316283AC2-100 C
Solar/Wind Harmer
0.713
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.003
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.924
961611AG1-000B GEN
Solar/Wind Harmer
1.561
315778AD1-151 GEN
Solar/Wind Harmer
6.583
316458AB2-190 GEN2
Solar/Wind Harmer
0.745
970133AG2-095 GEN
Solar/Wind Harmer
0.83
316123AC1-075 GEN
Solar/Wind Harmer
0.79
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.527
3142946ENON
Solar/Wind Harmer
-0.002
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
970831AG2-522 GEN
Solar/Wind Harmer
5.623
3151931BEARGRDN S1
50/50
5.856
3151911BEARGRDN G1
50/50
4.533
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.674
3151531CLOVER1
50/50
2.502
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.736
946281AF1-292 GEN
Solar/Wind Harmer
0.222
970673AG2-436 GEN
Solar/Wind Harmer
20.955
970533AG2-339 GEN
Solar/Wind Harmer
6.415
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.755
970581AG2-369 GEN
Solar/Wind Harmer
4.95
971285AH1-108 GEN
Adder
0.613
316426AA2-053 GEN
Solar/Wind Harmer
0.917
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.191
315652AC1-086 GEN
Solar/Wind Harmer
9.547
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.3
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
316463AE2-346 GEN
Solar/Wind Harmer
0.133
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.811
315839AE2-212 C
Solar/Wind Harmer
0.239
970657AG2-426 GEN
Solar/Wind Harmer
0.5
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.45
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316311AC2-079 GEN
Solar/Wind Harmer
3.969
315732AD1-074 GEN1
Solar/Wind Harmer
1.58
315733AD1-074 GEN2
Solar/Wind Harmer
1.58
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.922
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
313526AB2-022
Solar/Wind Harmer
0.208
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.66
957871AF2-081 GEN
Solar/Wind Harmer
3.861
316316AC1-027 C
Solar/Wind Harmer
0.236
3151081ELIZAR1
Adder
6.273
3151591KERR 2
50/50
0.23
3151641KERR 7
50/50
0.23
970937AG2-583 GEN
Solar/Wind Harmer
32.775
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.603
971563AH1-280 GEN
Solar/Wind Harmer
3.131
970685AG2-442 GEN
Solar/Wind Harmer
20.933
316034AC1-036 C
Solar/Wind Harmer
0.384
315785AD2-033 C
Solar/Wind Harmer
4.498
316131AB2-060 GEN
Solar/Wind Harmer
1.738
315693AD1-088 GEN
Solar/Wind Harmer
7.923
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.134
970401AG2-262 GEN
Solar/Wind Harmer
0.837
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.849
316129AC1-054 GEN
Solar/Wind Harmer
1.005
3151091ELIZAR2
Adder
6.164
316174AB2-169 GEN
Solar/Wind Harmer
1.183
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
957861AF2-080 GEN
Solar/Wind Harmer
3.309
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
316236AE1-162_GEN
Solar/Wind Harmer
0.226
971445AH1-216 GEN
Solar/Wind Harmer
4.649
3151201GRAVEL4
Adder
4.808
3151221GRAVEL6
Adder
4.802
3151191GRAVEL3
Adder
4.747
3151211GRAVEL5
Adder
4.747
315697AD1-025 GEN
Solar/Wind Harmer
1.494
316382AG1-145 C
Solar/Wind Harmer
0.195
316159AE1-175 C
Solar/Wind Harmer
0.174
957831AF2-077 GEN
Solar/Wind Harmer
0.193
3138283WHITEMARSH
Solar/Wind Harmer
0.01
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
315616AA1-038_C
Solar/Wind Helper
0.549
960081AF2-299 GEN
Solar/Wind Harmer
1.114
316087AB2-174 GEN
Solar/Wind Harmer
1.383
941031AE2-094 GEN
Solar/Wind Harmer
17.887
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
8.633
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
940641AE2-051 GEN
Solar/Wind Harmer
8.505
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316023GEN1_S
Solar/Wind Harmer
0.593
939411AE1-173 GEN
Solar/Wind Harmer
43.668
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.071
316381AD1-082 GEN
Solar/Wind Harmer
0.726
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.972
316319Z2-044 C
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.031
315737AD1-076 GEN
Solar/Wind Harmer
1.485
316093AE2-104_GEN
Solar/Wind Harmer
2.276
315816AE2-034 GEN
Solar/Wind Harmer
0.63
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.32
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.922
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.398
319010AE1-072 C
Solar/Wind Harmer
1.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
944591AF1-124 GEN
Solar/Wind Harmer
35.239
3145963POPLR C
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.657
316036AC1-147 C
Solar/Wind Harmer
0.207
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.09
316072AD1-144
Solar/Wind Harmer
0.154
315773AC2-141 GEN
Solar/Wind Harmer
3.174
3146293MARTNCO
Solar/Wind Harmer
0.047
961671AG1-007 GEN
Solar/Wind Harmer
0.096
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.225
316494AC1-189 GEN
Solar/Wind Harmer
0.814
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.03
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.703
961611AG1-000B GEN
Solar/Wind Harmer
3.659
316369SG1_INVT
Solar/Wind Harmer
1.32
971069AG2-661 GEN
Solar/Wind Harmer
1.17
316132AB2-190 GEN1
Solar/Wind Harmer
0.745
944631AF1-128 GEN
Adder
29.493
3138126ROCKLANDING
Solar/Wind Harmer
0.021
971317AH1-138 GEN
Solar/Wind Harmer
0.826
3142433PROV 92
Solar/Wind Harmer
-0.025
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.929
3147666LOUISA
Solar/Wind Helper
0.538
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
MECLTFEXP_MEC->PJM
CLTF
0.349
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.225
LAGNLTFEXP_LAGN->PJM
CLTF
1.773
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.519
TVALTFEXP_TVA->PJM
CLTF
0.866
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.017

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.13 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1436.97
MW Contribution:
2.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.562
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.238
3151581KERR 1
50/50
0.082
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
21.623
316313AB2-026
Solar/Wind Harmer
0.817
970301AG2-198 GEN
Solar/Wind Harmer
13.494
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
970323AG2-213 GEN
Solar/Wind Harmer
10.378
313527AB2-043 GEN
Solar/Wind Harmer
2.566
316237AB2-079_GEN
Solar/Wind Harmer
0.466
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.472
970099AG2-077 GEN
Solar/Wind Harmer
16.454
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
315687AD1-152 GEN
Solar/Wind Harmer
1.429
3143526WINTERP
Solar/Wind Harmer
-0.061
316118AC1-105 GEN
Solar/Wind Harmer
0.805
970933AG2-581 GEN
Solar/Wind Harmer
10.522
316248AF1-058 C
Solar/Wind Harmer
0.321
972187AH1-678 GEN
Adder
2.455
972185AH1-677 GEN
Adder
4.816
313506AB2-031 GEN
Solar/Wind Harmer
0.771
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316365GEN2_N
Solar/Wind Harmer
0.593
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.236
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.055
315742AE1-103 GEN
Solar/Wind Harmer
1.935
316083AB2-161 GEN
Solar/Wind Harmer
1.287
315724AD1-057 GEN
Solar/Wind Harmer
1.554
316349AD2-085 GEN
Solar/Wind Harmer
0.699
3151921BEARGRDN G2
50/50
4.532
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.896
972003AH1-546 GEN
Solar/Wind Harmer
21.778
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.602
3143336POWHATN
Solar/Wind Harmer
3.063
3147133PAMPLIN
Solar/Wind Harmer
-0.083
959311AF2-222 GEN
Solar/Wind Harmer
22.328
970257AG2-171 GEN
Solar/Wind Harmer
7.784
971775AH1-396 GEN
Solar/Wind Harmer
1.464
964241AG1-285 GEN
Solar/Wind Harmer
13.72
970221AG2-151 GEN
Solar/Wind Harmer
9.179
316478AD1-087 GEN
Solar/Wind Harmer
1.131
3147043LAWRENC
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Harmer
2.99
316003AC1-222 GEN
Solar/Wind Harmer
0.97
966621AG1-532 GEN
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
1.34
944011AF1-069 GEN
Solar/Wind Harmer
5.605
970917AG2-570 GEN
Solar/Wind Harmer
23.325
3150861SPRUNCD
Adder
0.375
971683AH1-343 GEN
Solar/Wind Harmer
3.936
316190AA2-174 GEN
Solar/Wind Harmer
0.112
3156081AA2-088 GEN
Solar/Wind Harmer
2.772
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.772
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.722
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.986
315722AD1-056 GEN
Solar/Wind Harmer
2.825
970657AG2-426 GEN
Solar/Wind Harmer
1.602
3146206CASHIE
Solar/Wind Harmer
-0.008
972205AH1-687 GEN
50/50
22.147
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.483
3151601KERR 3
50/50
0.23
3151611KERR 4
50/50
0.23
3151621KERR 5
50/50
0.23
3151631KERR 6
50/50
0.23
316322AB2-045
Solar/Wind Harmer
1.48
971845AH1-439 GEN
Solar/Wind Harmer
23.025
316258AE1-075 C
Solar/Wind Harmer
0.735
316405AF2-144 C
Solar/Wind Harmer
0.776
946301AF1-294 GEN
Solar/Wind Harmer
6.418
961791AG1-021 GEN
Solar/Wind Harmer
3.131
970683AG2-441 GEN
Solar/Wind Harmer
16.219
970681AG2-440 GEN
Solar/Wind Harmer
10.765
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.466
316239AB2-077_GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.331
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
970831AG2-522 GEN
Solar/Wind Harmer
5.623
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.736
946281AF1-292 GEN
Solar/Wind Harmer
0.222
970673AG2-436 GEN
Solar/Wind Harmer
20.955
970533AG2-339 GEN
Solar/Wind Harmer
6.415
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.755
970581AG2-369 GEN
Solar/Wind Harmer
4.95
971285AH1-108 GEN
Adder
0.613
316426AA2-053 GEN
Solar/Wind Harmer
0.917
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.191
315652AC1-086 GEN
Solar/Wind Harmer
9.547
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.3
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
316463AE2-346 GEN
Solar/Wind Harmer
0.133
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.811
315839AE2-212 C
Solar/Wind Harmer
0.239
970657AG2-426 GEN
Solar/Wind Harmer
0.5
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.45
315833AF1-017_GEN
Solar/Wind Harmer
1.494
3151931BEARGRDN S1
50/50
5.856
3151911BEARGRDN G1
50/50
4.532
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.674
3151531CLOVER1
50/50
2.502
3151591KERR 2
50/50
0.23
3151641KERR 7
50/50
0.23
970937AG2-583 GEN
Solar/Wind Harmer
32.775
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.603
971563AH1-280 GEN
Solar/Wind Harmer
3.131
970685AG2-442 GEN
Solar/Wind Harmer
20.932
316034AC1-036 C
Solar/Wind Harmer
0.384
315785AD2-033 C
Solar/Wind Harmer
4.498
316131AB2-060 GEN
Solar/Wind Harmer
1.738
315693AD1-088 GEN
Solar/Wind Harmer
7.923
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.134
970401AG2-262 GEN
Solar/Wind Harmer
0.837
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.849
316129AC1-054 GEN
Solar/Wind Harmer
1.005
960081AF2-299 GEN
Solar/Wind Harmer
1.114
316087AB2-174 GEN
Solar/Wind Harmer
1.383
941031AE2-094 GEN
Solar/Wind Harmer
17.887
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
8.633
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
940641AE2-051 GEN
Solar/Wind Harmer
8.505
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316023GEN1_S
Solar/Wind Harmer
0.593
939411AE1-173 GEN
Solar/Wind Harmer
43.668
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.071
316381AD1-082 GEN
Solar/Wind Harmer
0.726
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.972
316311AC2-079 GEN
Solar/Wind Harmer
3.969
315732AD1-074 GEN1
Solar/Wind Harmer
1.58
315733AD1-074 GEN2
Solar/Wind Harmer
1.58
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.922
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
313526AB2-022
Solar/Wind Harmer
0.208
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.66
957871AF2-081 GEN
Solar/Wind Harmer
3.861
316316AC1-027 C
Solar/Wind Harmer
0.236
3151081ELIZAR1
Adder
6.273
3151091ELIZAR2
Adder
6.164
316174AB2-169 GEN
Solar/Wind Harmer
1.183
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
957861AF2-080 GEN
Solar/Wind Harmer
3.309
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
316236AE1-162_GEN
Solar/Wind Harmer
0.226
971445AH1-216 GEN
Solar/Wind Harmer
4.649
3151201GRAVEL4
Adder
4.808
3151221GRAVEL6
Adder
4.802
3151191GRAVEL3
Adder
4.747
3151211GRAVEL5
Adder
4.747
315697AD1-025 GEN
Solar/Wind Harmer
1.494
316382AG1-145 C
Solar/Wind Harmer
0.195
316159AE1-175 C
Solar/Wind Harmer
0.174
316065AD1-022 GEN
Solar/Wind Harmer
3.933
315835AF2-110_GEN
Solar/Wind Harmer
0.979
315614AA2-178 GEN
Solar/Wind Harmer
0.84
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316435W1029_GEN3
Solar/Wind Harmer
1.405
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316240AF1-291 C
Solar/Wind Harmer
0.233
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316388AE2-253 GEN
Solar/Wind Harmer
0.519
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.811
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.539
316049AB1-081 GEN
Solar/Wind Harmer
0.822
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.79
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.208
316305AF2-043 C
Solar/Wind Harmer
0.233
316246AF1-032 C
Solar/Wind Harmer
0.156
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.894
316017AA1-139 ULT1
Solar/Wind Harmer
0.623
944581AF1-123 GEN
Solar/Wind Harmer
35.113
944601AF1-125 GEN
Solar/Wind Harmer
34.565
3145963POPLR C
Solar/Wind Harmer
-0.008
3142956BIRDNECK
Solar/Wind Harmer
0.413
3151101ELIZAR3
Adder
6.353
3144873MCLAUGH
Solar/Wind Harmer
0
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Harmer
0.772
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.022
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
316420AA1-050 GEN
Solar/Wind Harmer
0.862
316283AC2-100 C
Solar/Wind Harmer
0.713
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.003
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.924
961611AG1-000B GEN
Solar/Wind Harmer
1.561
315778AD1-151 GEN
Solar/Wind Harmer
6.583
316458AB2-190 GEN2
Solar/Wind Harmer
0.745
970133AG2-095 GEN
Solar/Wind Harmer
0.83
316123AC1-075 GEN
Solar/Wind Harmer
0.79
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.527
3142946ENON
Solar/Wind Harmer
-0.002
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
316263AC1-034 GEN
Solar/Wind Harmer
3.582
316294AC1-161 GEN
Solar/Wind Harmer
2.453
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
2.985
3145493TOT1
Solar/Wind Harmer
0.117
3145453TOT5
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.152
316033AB2-134 GEN
Solar/Wind Harmer
2.383
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
-0.001
3150691DARBY 3
Adder
4.202
3150701DARBY 4
Adder
4.193
3150681DARBY 2
Adder
4.188
3150671DARBY 1
Adder
4.183
942751AE2-291 GEN
Solar/Wind Harmer
4.144
316319Z2-044 C
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.031
315737AD1-076 GEN
Solar/Wind Harmer
1.485
316093AE2-104_GEN
Solar/Wind Harmer
2.276
315816AE2-034 GEN
Solar/Wind Harmer
0.63
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.32
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.922
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.398
319010AE1-072 C
Solar/Wind Harmer
1.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
944591AF1-124 GEN
Solar/Wind Harmer
35.239
3145963POPLR C
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.657
316036AC1-147 C
Solar/Wind Harmer
0.207
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.09
316072AD1-144
Solar/Wind Harmer
0.154
315773AC2-141 GEN
Solar/Wind Harmer
3.174
3146293MARTNCO
Solar/Wind Harmer
0.047
961671AG1-007 GEN
Solar/Wind Harmer
0.096
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.225
316494AC1-189 GEN
Solar/Wind Harmer
0.814
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.03
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.703
961611AG1-000B GEN
Solar/Wind Harmer
3.659
316369SG1_INVT
Solar/Wind Harmer
1.32
971069AG2-661 GEN
Solar/Wind Harmer
1.17
316132AB2-190 GEN1
Solar/Wind Harmer
0.745
944631AF1-128 GEN
Adder
29.493
3138126ROCKLANDING
Solar/Wind Harmer
0.021
971317AH1-138 GEN
Solar/Wind Harmer
0.826
3142433PROV 92
Solar/Wind Harmer
-0.025
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.93
3147666LOUISA
Solar/Wind Helper
0.539
966001AG1-469 GEN
Solar/Wind Helper
0.199
957831AF2-077 GEN
Solar/Wind Harmer
0.193
3138283WHITEMARSH
Solar/Wind Harmer
0.01
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
315616AA1-038_C
Solar/Wind Helper
0.549
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
MECLTFEXP_MEC->PJM
CLTF
0.349
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.224
LAGNLTFEXP_LAGN->PJM
CLTF
1.773
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.519
TVALTFEXP_TVA->PJM
CLTF
0.866
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.017

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:160.47 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1331.88
MW Contribution:
2.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.593
3144293JTRSVLE
50/50
0.56
972003AH1-546 GEN
Solar/Wind Harmer
22.059
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.593
3147133PAMPLIN
Solar/Wind Harmer
-0.082
959311AF2-222 GEN
Solar/Wind Harmer
22.005
970257AG2-171 GEN
Solar/Wind Harmer
7.662
971775AH1-396 GEN
Solar/Wind Harmer
1.442
964241AG1-285 GEN
Solar/Wind Harmer
13.399
970221AG2-151 GEN
Solar/Wind Harmer
9.591
316478AD1-087 GEN
Solar/Wind Harmer
1.07
270494AE1-108_GEN
Solar/Wind Harmer
3.119
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.922
966621AG1-532 GEN
Solar/Wind Harmer
0.189
316181AB2-040 GEN
Solar/Wind Harmer
1.26
971683AH1-343 GEN
Solar/Wind Harmer
3.742
316190AA2-174 GEN
Solar/Wind Harmer
0.105
944011AF1-069 GEN
Solar/Wind Harmer
4.972
970909AG2-566 GEN
50/50
2.539
3144293JTRSVLE
50/50
0.56
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.646
316313AB2-026
Solar/Wind Harmer
0.866
970301AG2-198 GEN
Solar/Wind Harmer
13.373
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
970323AG2-213 GEN
Solar/Wind Harmer
10.216
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.492
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.197
970099AG2-077 GEN
Solar/Wind Harmer
15.506
964791AG1-342 GEN
Solar/Wind Harmer
2.635
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
315687AD1-152 GEN
Solar/Wind Harmer
1.352
316118AC1-105 GEN
Solar/Wind Harmer
0.77
970933AG2-581 GEN
Solar/Wind Harmer
9.651
316248AF1-058 C
Solar/Wind Harmer
0.305
313506AB2-031 GEN
Solar/Wind Harmer
0.725
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.303
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.552
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.038
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.802
316083AB2-161 GEN
Solar/Wind Harmer
1.227
316349AD2-085 GEN
Solar/Wind Harmer
0.655
315724AD1-057 GEN
Solar/Wind Harmer
1.443
972205AH1-687 GEN
50/50
22.443
316303AF2-085
50/50
2.628
316322AB2-045
Solar/Wind Harmer
1.492
971845AH1-439 GEN
Solar/Wind Harmer
23.204
316258AE1-075 C
Solar/Wind Harmer
0.779
316405AF2-144 C
Solar/Wind Harmer
0.823
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
16.031
970681AG2-440 GEN
Solar/Wind Harmer
10.64
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.235
971283AH1-107 GEN
Solar/Wind Harmer
2.235
316486AD2-202 GEN
Solar/Wind Harmer
0.313
970831AG2-522 GEN
Solar/Wind Harmer
5.345
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
970917AG2-570 GEN
Solar/Wind Harmer
20.942
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.588
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.651
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.673
315813AE1-149 C
Solar/Wind Harmer
4.802
316317KELFORD C
Solar/Wind Harmer
0.354
3145823KELFORD
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
1.525
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.838
315722AD1-056 GEN
Solar/Wind Harmer
2.623
316458AB2-190 GEN2
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.494
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.731
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
1.509
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
316321Z2-027
Solar/Wind Harmer
0.192
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
17.883
946281AF1-292 GEN
Solar/Wind Harmer
0.209
3137643SOCKMAN
Solar/Wind Harmer
-0.035
316426AA2-053 GEN
Solar/Wind Harmer
0.86
970673AG2-436 GEN
Solar/Wind Harmer
18.644
970533AG2-339 GEN
Solar/Wind Harmer
5.691
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.171
970581AG2-369 GEN
Solar/Wind Harmer
4.447
315814AE2-033 C
Solar/Wind Harmer
7.589
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.891
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.846
315839AE2-212 C
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.212
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
0.476
316327AA2-057 GEN
Solar/Wind Harmer
0.754
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316311AC2-079 GEN
Solar/Wind Harmer
3.723
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.198
315697AD1-025 GEN
Solar/Wind Harmer
1.465
315732AD1-074 GEN1
Solar/Wind Harmer
1.463
315733AD1-074 GEN2
Solar/Wind Harmer
1.463
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.777
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316065AD1-022 GEN
Solar/Wind Harmer
3.644
315835AF2-110_GEN
Solar/Wind Harmer
0.909
316033AB2-134 GEN
Solar/Wind Harmer
2.337
3142366NRTHEST
Adder
0.21
315614AA2-178 GEN
Solar/Wind Harmer
0.777
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
316435W1029_GEN3
Solar/Wind Harmer
1.298
3151931BEARGRDN S1
50/50
5.934
3151911BEARGRDN G1
50/50
4.593
3144293JTRSVLE
50/50
0.56
3144293JTRSVLE
50/50
0.442
970119AG2-088 GEN
50/50
19.708
970937AG2-583 GEN
Solar/Wind Harmer
33.601
3146776BUCKING
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
20.721
316034AC1-036 C
Solar/Wind Harmer
0.378
315785AD2-033 C
Solar/Wind Harmer
4.42
3143226MDLTHAN
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
1.689
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.6
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.764
970401AG2-262 GEN
Solar/Wind Harmer
0.805
3147043LAWRENC
Adder
0.899
971065AG2-659 GEN
Solar/Wind Harmer
5.573
316129AC1-054 GEN
Solar/Wind Harmer
0.957
3150851SPRUNCC
Adder
0.417
960081AF2-299 GEN
Solar/Wind Harmer
1.05
316087AB2-174 GEN
Solar/Wind Harmer
1.301
3145783HORNRTN
Solar/Wind Harmer
-0.009
3142543TWELFTH
Solar/Wind Harmer
-0.001
941031AE2-094 GEN
Solar/Wind Harmer
15.869
315607AA1-063A GEN
Solar/Wind Harmer
0.851
970919AG2-571 GEN
Solar/Wind Harmer
2.651
970087AG2-069 GEN
Solar/Wind Harmer
7.756
316023GEN1_S
Solar/Wind Harmer
0.552
940641AE2-051 GEN
Solar/Wind Harmer
7.519
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.962
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.397
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316381AD1-082 GEN
Solar/Wind Harmer
0.692
3156021HOLLOMANSOL
Solar/Wind Harmer
0.994
316132AB2-190 GEN1
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
316319Z2-044 C
Solar/Wind Harmer
0.403
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.114
316369SG1_INVT
Solar/Wind Harmer
1.295
315737AD1-076 GEN
Solar/Wind Harmer
1.375
944631AF1-128 GEN
Adder
30.668
315816AE2-034 GEN
Solar/Wind Harmer
0.583
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.774
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.777
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.536
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
3142956BIRDNECK
Solar/Wind Harmer
0.381
3144873MCLAUGH
Solar/Wind Harmer
0
3151171GRAVELC
Adder
0.885
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.868
944581AF1-123 GEN
Solar/Wind Harmer
32.275
944601AF1-125 GEN
Solar/Wind Harmer
31.771
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.664
961601AG1-000A GEN
Solar/Wind Harmer
2.801
3145933PARMELE
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.799
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.751
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.834
3144216WINCHST
Adder
0.221
3145963POPLR C
Solar/Wind Harmer
-0.007
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.456
316036AC1-147 C
Solar/Wind Harmer
0.191
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.391
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.143
316359AB2-059 GEN
Solar/Wind Harmer
0.953
3142053HEARTS
Solar/Wind Harmer
0.083
3146293MARTNCO
Solar/Wind Harmer
0.044
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.208
316494AC1-189 GEN
Solar/Wind Harmer
0.754
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315773AC2-141 GEN
Solar/Wind Harmer
2.902
3138126ROCKLANDING
Solar/Wind Harmer
0.02
3142433PROV 92
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
971317AH1-138 GEN
Solar/Wind Harmer
0.794
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.8
3147666LOUISA
Solar/Wind Helper
0.46
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
316049AB1-081 GEN
Solar/Wind Harmer
0.762
316263AC1-034 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
2.766
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3150691DARBY 3
Adder
4.503
3150701DARBY 4
Adder
4.493
3150681DARBY 2
Adder
4.488
3150671DARBY 1
Adder
4.482
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.043
316005AA1-067
Solar/Wind Harmer
0.141
316294AC1-161 GEN
Solar/Wind Harmer
2.243
3142946ENON
Solar/Wind Harmer
-0.001
966001AG1-469 GEN
Solar/Wind Helper
0.186
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.192
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
316174AB2-169 GEN
Solar/Wind Harmer
1.095
316316AC1-027 C
Solar/Wind Harmer
0.218
3151201GRAVEL4
Adder
4.604
3151221GRAVEL6
Adder
4.599
3151191GRAVEL3
Adder
4.546
3151211GRAVEL5
Adder
4.546
316236AE1-162_GEN
Solar/Wind Harmer
0.214
971445AH1-216 GEN
Solar/Wind Harmer
4.396
3151081ELIZAR1
Adder
5.794
3151091ELIZAR2
Adder
5.693
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.064
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
316382AG1-145 C
Solar/Wind Harmer
0.19
316159AE1-175 C
Solar/Wind Harmer
0.169
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.102
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
315616AA1-038_C
Solar/Wind Helper
0.535
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.352
MECLTFEXP_MEC->PJM
CLTF
0.255
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
3.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.141
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.559
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.779
TVALTFEXP_TVA->PJM
CLTF
0.76
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:160.47 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1331.88
MW Contribution:
2.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.539
3144293JTRSVLE
50/50
0.56
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.646
316313AB2-026
Solar/Wind Harmer
0.866
970301AG2-198 GEN
Solar/Wind Harmer
13.373
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
970323AG2-213 GEN
Solar/Wind Harmer
10.216
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.492
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.197
970099AG2-077 GEN
Solar/Wind Harmer
15.506
964791AG1-342 GEN
Solar/Wind Harmer
2.635
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
315687AD1-152 GEN
Solar/Wind Harmer
1.352
316118AC1-105 GEN
Solar/Wind Harmer
0.77
970933AG2-581 GEN
Solar/Wind Harmer
9.651
316248AF1-058 C
Solar/Wind Harmer
0.305
313506AB2-031 GEN
Solar/Wind Harmer
0.725
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.303
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.552
3151921BEARGRDN G2
50/50
4.593
3144293JTRSVLE
50/50
0.56
972003AH1-546 GEN
Solar/Wind Harmer
22.059
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.593
3147133PAMPLIN
Solar/Wind Harmer
-0.082
959311AF2-222 GEN
Solar/Wind Harmer
22.005
970257AG2-171 GEN
Solar/Wind Harmer
7.662
971775AH1-396 GEN
Solar/Wind Harmer
1.442
964241AG1-285 GEN
Solar/Wind Harmer
13.399
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.038
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.802
316083AB2-161 GEN
Solar/Wind Harmer
1.227
316349AD2-085 GEN
Solar/Wind Harmer
0.655
315724AD1-057 GEN
Solar/Wind Harmer
1.443
316065AD1-022 GEN
Solar/Wind Harmer
3.644
315835AF2-110_GEN
Solar/Wind Harmer
0.909
316033AB2-134 GEN
Solar/Wind Harmer
2.337
3142366NRTHEST
Adder
0.21
315614AA2-178 GEN
Solar/Wind Harmer
0.777
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
316435W1029_GEN3
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
972205AH1-687 GEN
50/50
22.443
316303AF2-085
50/50
2.628
316322AB2-045
Solar/Wind Harmer
1.492
970221AG2-151 GEN
Solar/Wind Harmer
9.591
316478AD1-087 GEN
Solar/Wind Harmer
1.07
270494AE1-108_GEN
Solar/Wind Harmer
3.119
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.922
966621AG1-532 GEN
Solar/Wind Harmer
0.189
316181AB2-040 GEN
Solar/Wind Harmer
1.26
971683AH1-343 GEN
Solar/Wind Harmer
3.742
316190AA2-174 GEN
Solar/Wind Harmer
0.105
944011AF1-069 GEN
Solar/Wind Harmer
4.972
970917AG2-570 GEN
Solar/Wind Harmer
20.942
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.588
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.651
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.673
315813AE1-149 C
Solar/Wind Harmer
4.802
971845AH1-439 GEN
Solar/Wind Harmer
23.204
316258AE1-075 C
Solar/Wind Harmer
0.779
316405AF2-144 C
Solar/Wind Harmer
0.823
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
16.031
970681AG2-440 GEN
Solar/Wind Harmer
10.64
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.235
971283AH1-107 GEN
Solar/Wind Harmer
2.235
316486AD2-202 GEN
Solar/Wind Harmer
0.313
970831AG2-522 GEN
Solar/Wind Harmer
5.345
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
17.883
946281AF1-292 GEN
Solar/Wind Harmer
0.209
3137643SOCKMAN
Solar/Wind Harmer
-0.035
316426AA2-053 GEN
Solar/Wind Harmer
0.86
970673AG2-436 GEN
Solar/Wind Harmer
18.644
970533AG2-339 GEN
Solar/Wind Harmer
5.691
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.171
970581AG2-369 GEN
Solar/Wind Harmer
4.447
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
316049AB1-081 GEN
Solar/Wind Harmer
0.762
316263AC1-034 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
2.766
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3150691DARBY 3
Adder
4.503
3150701DARBY 4
Adder
4.493
3150681DARBY 2
Adder
4.488
3150671DARBY 1
Adder
4.482
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.043
316005AA1-067
Solar/Wind Harmer
0.141
316294AC1-161 GEN
Solar/Wind Harmer
2.243
3142946ENON
Solar/Wind Harmer
-0.001
966001AG1-469 GEN
Solar/Wind Helper
0.186
316317KELFORD C
Solar/Wind Harmer
0.354
3145823KELFORD
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
1.525
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.838
315722AD1-056 GEN
Solar/Wind Harmer
2.623
316458AB2-190 GEN2
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.494
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.731
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
1.509
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
316321Z2-027
Solar/Wind Harmer
0.192
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
3142956BIRDNECK
Solar/Wind Harmer
0.381
3144873MCLAUGH
Solar/Wind Harmer
0
3151171GRAVELC
Adder
0.885
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.868
944581AF1-123 GEN
Solar/Wind Harmer
32.275
944601AF1-125 GEN
Solar/Wind Harmer
31.771
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.664
961601AG1-000A GEN
Solar/Wind Harmer
2.801
3145933PARMELE
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.799
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.751
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.834
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.264
315814AE2-033 C
Solar/Wind Harmer
7.589
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.891
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.846
315839AE2-212 C
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.212
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
0.476
316327AA2-057 GEN
Solar/Wind Harmer
0.754
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316311AC2-079 GEN
Solar/Wind Harmer
3.723
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.198
315697AD1-025 GEN
Solar/Wind Harmer
1.465
315732AD1-074 GEN1
Solar/Wind Harmer
1.463
315733AD1-074 GEN2
Solar/Wind Harmer
1.463
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.777
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.192
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
316174AB2-169 GEN
Solar/Wind Harmer
1.095
316316AC1-027 C
Solar/Wind Harmer
0.218
3151201GRAVEL4
Adder
4.604
3151221GRAVEL6
Adder
4.599
3151191GRAVEL3
Adder
4.546
3151211GRAVEL5
Adder
4.546
316236AE1-162_GEN
Solar/Wind Harmer
0.214
971445AH1-216 GEN
Solar/Wind Harmer
4.396
3151081ELIZAR1
Adder
5.794
3151091ELIZAR2
Adder
5.693
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.064
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
316382AG1-145 C
Solar/Wind Harmer
0.19
316159AE1-175 C
Solar/Wind Harmer
0.169
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.102
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
315616AA1-038_C
Solar/Wind Helper
0.535
3151931BEARGRDN S1
50/50
5.934
3151911BEARGRDN G1
50/50
4.593
3144293JTRSVLE
50/50
0.56
3144293JTRSVLE
50/50
0.442
970119AG2-088 GEN
50/50
19.708
970937AG2-583 GEN
Solar/Wind Harmer
33.601
3146776BUCKING
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
20.721
316034AC1-036 C
Solar/Wind Harmer
0.378
315785AD2-033 C
Solar/Wind Harmer
4.42
3143226MDLTHAN
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
1.689
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.6
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.764
970401AG2-262 GEN
Solar/Wind Harmer
0.805
3147043LAWRENC
Adder
0.899
971065AG2-659 GEN
Solar/Wind Harmer
5.573
316129AC1-054 GEN
Solar/Wind Harmer
0.957
3150851SPRUNCC
Adder
0.417
960081AF2-299 GEN
Solar/Wind Harmer
1.05
316087AB2-174 GEN
Solar/Wind Harmer
1.301
3145783HORNRTN
Solar/Wind Harmer
-0.009
3142543TWELFTH
Solar/Wind Harmer
-0.001
941031AE2-094 GEN
Solar/Wind Harmer
15.869
315607AA1-063A GEN
Solar/Wind Harmer
0.851
970919AG2-571 GEN
Solar/Wind Harmer
2.651
970087AG2-069 GEN
Solar/Wind Harmer
7.756
316023GEN1_S
Solar/Wind Harmer
0.552
940641AE2-051 GEN
Solar/Wind Harmer
7.519
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.962
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.397
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316381AD1-082 GEN
Solar/Wind Harmer
0.692
3156021HOLLOMANSOL
Solar/Wind Harmer
0.994
316132AB2-190 GEN1
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
316319Z2-044 C
Solar/Wind Harmer
0.403
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.114
316369SG1_INVT
Solar/Wind Harmer
1.295
315737AD1-076 GEN
Solar/Wind Harmer
1.375
944631AF1-128 GEN
Adder
30.668
315816AE2-034 GEN
Solar/Wind Harmer
0.583
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.774
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.777
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.536
3145963POPLR C
Solar/Wind Harmer
-0.007
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.456
316036AC1-147 C
Solar/Wind Harmer
0.191
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.391
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.143
316359AB2-059 GEN
Solar/Wind Harmer
0.953
3142053HEARTS
Solar/Wind Harmer
0.083
3146293MARTNCO
Solar/Wind Harmer
0.044
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.208
316494AC1-189 GEN
Solar/Wind Harmer
0.754
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315773AC2-141 GEN
Solar/Wind Harmer
2.902
3138126ROCKLANDING
Solar/Wind Harmer
0.02
3142433PROV 92
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
971317AH1-138 GEN
Solar/Wind Harmer
0.794
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.8
3147666LOUISA
Solar/Wind Helper
0.46
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.352
MECLTFEXP_MEC->PJM
CLTF
0.255
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
3.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.141
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.559
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.779
TVALTFEXP_TVA->PJM
CLTF
0.76
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B3_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.69 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:910.4
MW Contribution:
2.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.994
3144293JTRSVLE
50/50
0.585
972003AH1-546 GEN
Solar/Wind Harmer
23.964
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.022
942461AE2-259 GEN
Solar/Wind Harmer
4.864
3143336POWHATN
Solar/Wind Harmer
3.18
3147133PAMPLIN
Solar/Wind Harmer
-0.086
959311AF2-222 GEN
Solar/Wind Harmer
22.721
970257AG2-171 GEN
Solar/Wind Harmer
7.89
971775AH1-396 GEN
Solar/Wind Harmer
1.485
964241AG1-285 GEN
Solar/Wind Harmer
13.573
316478AD1-087 GEN
Solar/Wind Harmer
1.034
3147043LAWRENC
Solar/Wind Harmer
-0.006
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.173
316181AB2-040 GEN
Solar/Wind Harmer
1.149
971683AH1-343 GEN
Solar/Wind Harmer
3.439
3150861SPRUNCD
Adder
0.323
316190AA2-174 GEN
Solar/Wind Harmer
0.095
970917AG2-570 GEN
Solar/Wind Harmer
18.451
944011AF1-069 GEN
Solar/Wind Harmer
4.319
3156081AA2-088 GEN
Solar/Wind Harmer
2.294
3146263WOODLND
Solar/Wind Harmer
-0.007
970909AG2-566 GEN
50/50
2.663
3144293JTRSVLE
50/50
0.585
970535AG2-341 GEN
50/50
2.129
3146776BUCKING
Solar/Wind Harmer
-0.191
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
22.829
316313AB2-026
Solar/Wind Harmer
0.848
970301AG2-198 GEN
Solar/Wind Harmer
14.027
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.022
958211AF2-115 GEN
Solar/Wind Harmer
4.057
970323AG2-213 GEN
Solar/Wind Harmer
10.52
313527AB2-043 GEN
Solar/Wind Harmer
2.494
316237AB2-079_GEN
Solar/Wind Harmer
0.451
962561AG1-105 GEN
Solar/Wind Harmer
7.051
971223AH1-071 GEN
Solar/Wind Harmer
1.533
964791AG1-342 GEN
Solar/Wind Harmer
2.569
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.915
316118AC1-105 GEN
Solar/Wind Harmer
0.741
315687AD1-152 GEN
Solar/Wind Harmer
1.294
3143526WINTERP
Solar/Wind Harmer
-0.053
316248AF1-058 C
Solar/Wind Harmer
0.289
970933AG2-581 GEN
Solar/Wind Harmer
8.888
313506AB2-031 GEN
Solar/Wind Harmer
0.662
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.093
972187AH1-678 GEN
Adder
1.941
3151931BEARGRDN S1
50/50
6.452
3151911BEARGRDN G1
50/50
4.994
3144293JTRSVLE
50/50
0.585
3144293JTRSVLE
50/50
0.462
970937AG2-583 GEN
Solar/Wind Harmer
35.585
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.022
3143336POWHATN
Solar/Wind Harmer
3.741
971563AH1-280 GEN
Solar/Wind Harmer
3.245
970685AG2-442 GEN
Solar/Wind Harmer
21.59
316034AC1-036 C
Solar/Wind Harmer
0.39
315785AD2-033 C
Solar/Wind Harmer
4.533
316131AB2-060 GEN
Solar/Wind Harmer
1.695
315693AD1-088 GEN
Solar/Wind Harmer
7.541
3143226MDLTHAN
Solar/Wind Harmer
-0.012
970401AG2-262 GEN
Solar/Wind Harmer
0.785
957481AF2-042 GEN
Solar/Wind Harmer
37.288
971065AG2-659 GEN
Solar/Wind Harmer
5.332
3147043LAWRENC
Adder
0.854
316129AC1-054 GEN
Solar/Wind Harmer
0.913
3143526WINTERP
Solar/Wind Harmer
-0.053
960081AF2-299 GEN
Solar/Wind Harmer
0.96
316087AB2-174 GEN
Solar/Wind Harmer
1.187
3150851SPRUNCC
Adder
0.323
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.767
970919AG2-571 GEN
Solar/Wind Harmer
2.336
941031AE2-094 GEN
Solar/Wind Harmer
13.785
970087AG2-069 GEN
Solar/Wind Harmer
6.83
316023GEN1_S
Solar/Wind Harmer
0.487
3146263WOODLND
Solar/Wind Harmer
-0.007
972185AH1-677 GEN
Adder
3.779
316365GEN2_N
Solar/Wind Harmer
0.487
3144356SAPONY
Solar/Wind Harmer
0.244
972205AH1-687 GEN
50/50
24.401
316322AB2-045
Solar/Wind Harmer
1.609
971845AH1-439 GEN
Solar/Wind Harmer
25.005
316258AE1-075 C
Solar/Wind Harmer
0.763
316405AF2-144 C
Solar/Wind Harmer
0.806
946301AF1-294 GEN
Solar/Wind Harmer
6.653
961791AG1-021 GEN
Solar/Wind Harmer
3.245
970683AG2-441 GEN
Solar/Wind Harmer
16.65
970681AG2-440 GEN
Solar/Wind Harmer
11.051
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.451
316239AB2-077_GEN
Solar/Wind Harmer
0.451
316486AD2-202 GEN
Solar/Wind Harmer
0.303
316233AE1-074 FULL
Solar/Wind Harmer
0.277
971281AH1-106 GEN
Solar/Wind Harmer
1.674
971283AH1-107 GEN
Solar/Wind Harmer
1.674
970831AG2-522 GEN
Solar/Wind Harmer
5.074
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
16.127
946281AF1-292 GEN
Solar/Wind Harmer
0.191
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971285AH1-108 GEN
Adder
0.528
316426AA2-053 GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970673AG2-436 GEN
Solar/Wind Harmer
16.266
970533AG2-339 GEN
Solar/Wind Harmer
4.944
970085AG2-068 GEN
Solar/Wind Harmer
4.553
970581AG2-369 GEN
Solar/Wind Harmer
3.916
316274AC1-208 GEN
Solar/Wind Harmer
0.757
315814AE2-033 C
Solar/Wind Harmer
6.529
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
316011AB1-132 GEN
Solar/Wind Harmer
1.461
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.599
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.313
3145823KELFORD
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
2.313
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.135
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.65
3138543CONSLDL
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
4.018
3143096IRON208
Adder
0.238
3143096IRON208
Adder
0.233
3146206CASHIE
Solar/Wind Harmer
-0.006
315652AC1-086 GEN
Solar/Wind Harmer
7.869
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.079
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.027
316463AE2-346 GEN
Solar/Wind Harmer
0.109
3145513AHOSKIE
Solar/Wind Harmer
0.059
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.67
3143316POE
Solar/Wind Harmer
-0.026
315839AE2-212 C
Solar/Wind Harmer
0.195
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.784
970657AG2-426 GEN
Solar/Wind Harmer
0.401
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
3148463FAIRFLD
Solar/Wind Helper
0.141
315616AA1-038_C
Solar/Wind Helper
0.642
316283AC2-100 C
Solar/Wind Harmer
0.599
970657AG2-426 GEN
Solar/Wind Harmer
1.285
315821AE2-092 GEN
Solar/Wind Helper
6.554
3148013FISHERV
Solar/Wind Helper
0.273
316499AE2-029_GEN
Solar/Wind Helper
0.588
3132273ORANGE
Solar/Wind Helper
0.023
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
940641AE2-051 GEN
Solar/Wind Harmer
6.432
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3145683EARLEYS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
33.321
3156021HOLLOMANSOL
Solar/Wind Harmer
0.868
316319Z2-044 C
Solar/Wind Harmer
0.356
3146233WITAKRS
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.238
315671AE2-027_GEN
Solar/Wind Harmer
1.15
316381AD1-082 GEN
Solar/Wind Harmer
0.583
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.591
3147983MERCK5
Solar/Wind Helper
0.064
316315AB2-025 C
Solar/Wind Harmer
0.188
962571AG1-106 GEN
Solar/Wind Harmer
1.005
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.046
315742AE1-103 GEN
Solar/Wind Harmer
1.569
315724AD1-057 GEN
Solar/Wind Harmer
1.272
316240AF1-291 C
Solar/Wind Harmer
0.192
316083AB2-161 GEN
Solar/Wind Harmer
1.033
944641AF1-129 GEN
Adder
27.005
316065AD1-022 GEN
Solar/Wind Harmer
3.169
966001AG1-469 GEN
Solar/Wind Helper
0.167
3132123MT JACKSON
Solar/Wind Helper
0.376
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.118
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.06
CPLELTFEXP_CPLE->PJM
CLTF
3.428
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.971
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.18
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.537
LAGNLTFEXP_LAGN->PJM
CLTF
0.856
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.321
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.399
NYPJM->LTFIMP_NY
CLTF
0.337

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.52 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:845.12
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.13 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:841.95
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970933AG2-581 GEN
Solar/Wind Harmer
8.916
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
971967AH1-528 GEN
Solar/Wind Harmer
17.83
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:174.45 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1183.97
MW Contribution:
2.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.566
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.241
3151581KERR 1
50/50
0.082
3152661PLYWOOD A
50/50
0.224
3151041BRUNSWICKG3
50/50
1.136
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.414
315241AE2-183_GT1
50/50
1.41
972185AH1-677 GEN
50/50
5.112
3151261ROARAP2
50/50
0.1
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
316336AC2-165 C
Solar/Wind Harmer
15.638
316313AB2-026
Solar/Wind Harmer
0.168
970301AG2-198 GEN
Solar/Wind Harmer
10.263
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.679
970323AG2-213 GEN
Solar/Wind Harmer
7.893
971223AH1-071 GEN
Solar/Wind Harmer
1.335
962561AG1-105 GEN
Solar/Wind Harmer
5.682
970099AG2-077 GEN
Solar/Wind Harmer
12.508
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.908
3151031BRUNSWICKG2
50/50
1.136
3151261ROARAP2
50/50
0.102
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.202
3151411GASTONB
50/50
0.202
972003AH1-546 GEN
Solar/Wind Harmer
16.566
972205AH1-687 GEN
50/50
22.181
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.485
3151601KERR 3
50/50
0.231
3151611KERR 4
50/50
0.231
3151621KERR 5
50/50
0.231
3151631KERR 6
50/50
0.231
963041AG1-153 GEN
50/50
2.3
315244AE2-183_ST
50/50
2.456
3151281ROARAP4
50/50
0.093
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.514
316258AE1-075 C
Solar/Wind Harmer
0.202
946301AF1-294 GEN
Solar/Wind Harmer
4.405
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
12.335
970681AG2-440 GEN
Solar/Wind Harmer
8.187
3144303KENBRDG
Solar/Wind Harmer
0.148
316486AD2-202 GEN
Solar/Wind Harmer
0.119
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
970831AG2-522 GEN
Solar/Wind Harmer
4.275
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.957
970673AG2-436 GEN
Solar/Wind Harmer
10.614
970533AG2-339 GEN
Solar/Wind Harmer
6.417
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.374
970581AG2-369 GEN
Solar/Wind Harmer
3.761
316426AA2-053 GEN
Solar/Wind Harmer
0.271
3146043SEABORD
Solar/Wind Harmer
0.08
3151931BEARGRDN S1
50/50
5.865
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.682
3151531CLOVER1
50/50
2.505
3151591KERR 2
50/50
0.231
3151641KERR 7
50/50
0.231
3147043LAWRENC
50/50
1.001
3151051BRUNSWICKS1
50/50
2.358
3151021BRUNSWICKG1
50/50
1.136
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.414
315814AE2-033 C
Solar/Wind Harmer
6.194
315652AC1-086 GEN
Solar/Wind Harmer
8.309
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
316274AC1-208 GEN
Solar/Wind Harmer
0.387
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
316210AC1-098 GEN
Solar/Wind Harmer
0.683
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
316463AE2-346 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
0.154
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.106
970657AG2-426 GEN
Solar/Wind Harmer
0.518
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.621
316311AC2-079 GEN
Solar/Wind Harmer
2.01
315732AD1-074 GEN1
Solar/Wind Harmer
0.397
315733AD1-074 GEN2
Solar/Wind Harmer
0.397
3130546PLYMOUTH
Solar/Wind Harmer
0.07
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
957871AF2-081 GEN
Solar/Wind Harmer
3.42
316316AC1-027 C
Solar/Wind Harmer
0.065
3151081ELIZAR1
Adder
6.27
3151091ELIZAR2
Adder
6.161
3146776BUCKING
Solar/Wind Harmer
0.142
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
4.089
3147133PAMPLIN
Solar/Wind Harmer
0.741
959311AF2-222 GEN
Solar/Wind Harmer
16.947
970257AG2-171 GEN
Solar/Wind Harmer
5.92
971775AH1-396 GEN
Solar/Wind Harmer
0.296
964241AG1-285 GEN
Solar/Wind Harmer
10.433
970221AG2-151 GEN
Solar/Wind Harmer
7.011
316478AD1-087 GEN
Solar/Wind Harmer
0.404
3147043LAWRENC
Solar/Wind Harmer
0.063
270494AE1-108_GEN
Solar/Wind Harmer
1.23
316181AB2-040 GEN
Solar/Wind Harmer
0.122
944011AF1-069 GEN
Solar/Wind Harmer
5.111
970917AG2-570 GEN
Solar/Wind Harmer
7.385
971683AH1-343 GEN
Solar/Wind Harmer
2.995
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.37
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
0.073
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.785
315722AD1-056 GEN
Solar/Wind Harmer
2.443
970657AG2-426 GEN
Solar/Wind Harmer
1.583
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315735AD1-075 GEN1
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.012
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
316017AA1-139 ULT1
Solar/Wind Harmer
0.037
944581AF1-123 GEN
Solar/Wind Harmer
15.462
944601AF1-125 GEN
Solar/Wind Harmer
15.223
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.35
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
316222AC1-221 GEN
Solar/Wind Harmer
0.281
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
4.809
316118AC1-105 GEN
Solar/Wind Harmer
0.268
970933AG2-581 GEN
Solar/Wind Harmer
7.997
313506AB2-031 GEN
Solar/Wind Harmer
0.263
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316365GEN2_N
Solar/Wind Harmer
0.174
3144356SAPONY
Solar/Wind Harmer
0.654
316315AB2-025 C
Solar/Wind Harmer
0.063
962571AG1-106 GEN
Solar/Wind Harmer
1.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316140AB2-099
Solar/Wind Harmer
0.026
315742AE1-103 GEN
Solar/Wind Harmer
1.084
315724AD1-057 GEN
Solar/Wind Harmer
1.363
316349AD2-085 GEN
Solar/Wind Harmer
0.047
316065AD1-022 GEN
Solar/Wind Harmer
3.224
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315614AA2-178 GEN
Solar/Wind Harmer
0.395
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146386ELIZ CT
Solar/Wind Harmer
0.069
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.216
316339AD2-160 GEN
Solar/Wind Harmer
0.11
316388AE2-253 GEN
Solar/Wind Harmer
0.214
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.514
316049AB1-081 GEN
Solar/Wind Harmer
0.387
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
316294AC1-161 GEN
Solar/Wind Harmer
1.166
3151281ROARAP4
50/50
0.099
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.202
3151411GASTONB
50/50
0.202
970937AG2-583 GEN
Solar/Wind Harmer
24.929
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
3143336POWHATN
Solar/Wind Harmer
4.81
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.92
316034AC1-036 C
Solar/Wind Harmer
0.012
315785AD2-033 C
Solar/Wind Harmer
1.433
316131AB2-060 GEN
Solar/Wind Harmer
0.448
315693AD1-088 GEN
Solar/Wind Harmer
6.777
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.271
970401AG2-262 GEN
Solar/Wind Harmer
0.671
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.447
316129AC1-054 GEN
Solar/Wind Harmer
0.383
960081AF2-299 GEN
Solar/Wind Harmer
0.847
941031AE2-094 GEN
Solar/Wind Harmer
15.643
970919AG2-571 GEN
Solar/Wind Harmer
2.954
970087AG2-069 GEN
Solar/Wind Harmer
6.56
3145783HORNRTN
Solar/Wind Harmer
0.082
940641AE2-051 GEN
Solar/Wind Harmer
6.46
315607AA1-063A GEN
Solar/Wind Harmer
0.162
316023GEN1_S
Solar/Wind Harmer
0.174
939411AE1-173 GEN
Solar/Wind Harmer
33.164
3146263WOODLND
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.335
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3156021HOLLOMANSOL
Solar/Wind Harmer
0.319
316381AD1-082 GEN
Solar/Wind Harmer
0.072
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.498
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
315737AD1-076 GEN
Solar/Wind Harmer
0.894
316093AE2-104_GEN
Solar/Wind Harmer
1.171
315816AE2-034 GEN
Solar/Wind Harmer
0.297
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.559
3130156CHOWAN
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
0
319010AE1-072 C
Solar/Wind Harmer
0.343
3146456SLIGO L269
Solar/Wind Harmer
0.069
944591AF1-124 GEN
Solar/Wind Harmer
15.516
3145963POPLR C
Solar/Wind Harmer
0.069
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.012
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.242
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.024
3146293MARTNCO
Solar/Wind Harmer
0.063
315773AC2-141 GEN
Solar/Wind Harmer
2.463
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316005AA1-067
Solar/Wind Harmer
0.072
316033AB2-134 GEN
Solar/Wind Harmer
0
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.263
316458AB2-190 GEN2
Solar/Wind Harmer
0.351
970133AG2-095 GEN
Solar/Wind Harmer
0.63
316123AC1-075 GEN
Solar/Wind Harmer
0.087
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.513
3132273ORANGE
Solar/Wind Helper
0.027
3147666LOUISA
Solar/Wind Helper
0.273
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
957861AF2-080 GEN
Solar/Wind Harmer
2.904
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
971445AH1-216 GEN
Solar/Wind Harmer
4.705
3151201GRAVEL4
Adder
4.805
3151221GRAVEL6
Adder
4.799
3151191GRAVEL3
Adder
4.744
3151211GRAVEL5
Adder
4.744
315697AD1-025 GEN
Solar/Wind Harmer
0.071
316159AE1-175 C
Solar/Wind Harmer
0.049
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.1
3148463FAIRFLD
Solar/Wind Helper
0.12
315616AA1-038_C
Solar/Wind Helper
0.545
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.196
3150701DARBY 4
Adder
4.186
3150681DARBY 2
Adder
4.181
3150671DARBY 1
Adder
4.176
942751AE2-291 GEN
Solar/Wind Harmer
3.156
966001AG1-469 GEN
Solar/Wind Helper
0.19
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.228
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.458
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316132AB2-190 GEN1
Solar/Wind Harmer
0.351
944631AF1-128 GEN
Adder
29.459
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.825
3147666LOUISA
Solar/Wind Helper
0.474
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.732
MECLTFEXP_MEC->PJM
CLTF
0.357
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.299
LAGNLTFEXP_LAGN->PJM
CLTF
1.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.539
TVALTFEXP_TVA->PJM
CLTF
0.872
NYPJM->LTFIMP_NY
CLTF
0.578
LGEELTFEXP_LGEE->PJM
CLTF
0.049
WECLTFEXP_WEC->PJM
CLTF
0.019

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.24 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1429.6
MW Contribution:
2.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.533
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.896
972003AH1-546 GEN
Solar/Wind Harmer
21.779
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.602
3143336POWHATN
Solar/Wind Harmer
3.063
3147133PAMPLIN
Solar/Wind Harmer
-0.083
959311AF2-222 GEN
Solar/Wind Harmer
22.328
970257AG2-171 GEN
Solar/Wind Harmer
7.784
971775AH1-396 GEN
Solar/Wind Harmer
1.465
964241AG1-285 GEN
Solar/Wind Harmer
13.72
970221AG2-151 GEN
Solar/Wind Harmer
9.179
316478AD1-087 GEN
Solar/Wind Harmer
1.131
3147043LAWRENC
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Harmer
2.99
316003AC1-222 GEN
Solar/Wind Harmer
0.97
966621AG1-532 GEN
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
1.34
944011AF1-069 GEN
Solar/Wind Harmer
5.605
970917AG2-570 GEN
Solar/Wind Harmer
23.325
3150861SPRUNCD
Adder
0.375
971683AH1-343 GEN
Solar/Wind Harmer
3.936
316190AA2-174 GEN
Solar/Wind Harmer
0.112
3156081AA2-088 GEN
Solar/Wind Harmer
2.772
3146263WOODLND
Solar/Wind Harmer
-0.008
3151931BEARGRDN S1
50/50
5.856
3151911BEARGRDN G1
50/50
4.533
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.674
3151531CLOVER1
50/50
2.502
3151591KERR 2
50/50
0.23
3151641KERR 7
50/50
0.23
970937AG2-583 GEN
Solar/Wind Harmer
32.775
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.603
971563AH1-280 GEN
Solar/Wind Harmer
3.131
970685AG2-442 GEN
Solar/Wind Harmer
20.933
316034AC1-036 C
Solar/Wind Harmer
0.384
315785AD2-033 C
Solar/Wind Harmer
4.498
316131AB2-060 GEN
Solar/Wind Harmer
1.738
315693AD1-088 GEN
Solar/Wind Harmer
7.923
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.134
970401AG2-262 GEN
Solar/Wind Harmer
0.837
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.849
316129AC1-054 GEN
Solar/Wind Harmer
1.005
960081AF2-299 GEN
Solar/Wind Harmer
1.114
316087AB2-174 GEN
Solar/Wind Harmer
1.383
941031AE2-094 GEN
Solar/Wind Harmer
17.887
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
8.633
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
940641AE2-051 GEN
Solar/Wind Harmer
8.505
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316023GEN1_S
Solar/Wind Harmer
0.593
939411AE1-173 GEN
Solar/Wind Harmer
43.668
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.071
316381AD1-082 GEN
Solar/Wind Harmer
0.726
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.972
316319Z2-044 C
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.031
315737AD1-076 GEN
Solar/Wind Harmer
1.485
316093AE2-104_GEN
Solar/Wind Harmer
2.276
315816AE2-034 GEN
Solar/Wind Harmer
0.63
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.32
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.922
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.398
319010AE1-072 C
Solar/Wind Harmer
1.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
944591AF1-124 GEN
Solar/Wind Harmer
35.239
3145963POPLR C
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.657
316036AC1-147 C
Solar/Wind Harmer
0.207
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.09
316072AD1-144
Solar/Wind Harmer
0.154
315773AC2-141 GEN
Solar/Wind Harmer
3.174
3146293MARTNCO
Solar/Wind Harmer
0.047
961671AG1-007 GEN
Solar/Wind Harmer
0.096
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.225
970909AG2-566 GEN
50/50
2.562
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.238
3151581KERR 1
50/50
0.082
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
21.624
316313AB2-026
Solar/Wind Harmer
0.817
970301AG2-198 GEN
Solar/Wind Harmer
13.495
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
970323AG2-213 GEN
Solar/Wind Harmer
10.378
313527AB2-043 GEN
Solar/Wind Harmer
2.566
316237AB2-079_GEN
Solar/Wind Harmer
0.466
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.472
970099AG2-077 GEN
Solar/Wind Harmer
16.454
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
315687AD1-152 GEN
Solar/Wind Harmer
1.429
3143526WINTERP
Solar/Wind Harmer
-0.061
316118AC1-105 GEN
Solar/Wind Harmer
0.805
970933AG2-581 GEN
Solar/Wind Harmer
10.522
316248AF1-058 C
Solar/Wind Harmer
0.321
972187AH1-678 GEN
Adder
2.455
972185AH1-677 GEN
Adder
4.816
313506AB2-031 GEN
Solar/Wind Harmer
0.771
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316365GEN2_N
Solar/Wind Harmer
0.593
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.236
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.055
315742AE1-103 GEN
Solar/Wind Harmer
1.935
316083AB2-161 GEN
Solar/Wind Harmer
1.287
315724AD1-057 GEN
Solar/Wind Harmer
1.554
316349AD2-085 GEN
Solar/Wind Harmer
0.699
316065AD1-022 GEN
Solar/Wind Harmer
3.933
315835AF2-110_GEN
Solar/Wind Harmer
0.979
315614AA2-178 GEN
Solar/Wind Harmer
0.84
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316435W1029_GEN3
Solar/Wind Harmer
1.405
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316240AF1-291 C
Solar/Wind Harmer
0.233
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316388AE2-253 GEN
Solar/Wind Harmer
0.519
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.811
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.538
316049AB1-081 GEN
Solar/Wind Harmer
0.822
316263AC1-034 GEN
Solar/Wind Harmer
3.582
316294AC1-161 GEN
Solar/Wind Harmer
2.453
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
2.985
3145493TOT1
Solar/Wind Harmer
0.117
3145453TOT5
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.047
972205AH1-687 GEN
50/50
22.147
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.483
3151601KERR 3
50/50
0.23
3151611KERR 4
50/50
0.23
3151621KERR 5
50/50
0.23
3151631KERR 6
50/50
0.23
316322AB2-045
Solar/Wind Harmer
1.48
971845AH1-439 GEN
Solar/Wind Harmer
23.026
316258AE1-075 C
Solar/Wind Harmer
0.735
316405AF2-144 C
Solar/Wind Harmer
0.776
946301AF1-294 GEN
Solar/Wind Harmer
6.418
961791AG1-021 GEN
Solar/Wind Harmer
3.131
970683AG2-441 GEN
Solar/Wind Harmer
16.22
970681AG2-440 GEN
Solar/Wind Harmer
10.765
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.466
316239AB2-077_GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.331
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
970831AG2-522 GEN
Solar/Wind Harmer
5.623
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.736
946281AF1-292 GEN
Solar/Wind Harmer
0.222
970673AG2-436 GEN
Solar/Wind Harmer
20.955
970533AG2-339 GEN
Solar/Wind Harmer
6.415
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.755
970581AG2-369 GEN
Solar/Wind Harmer
4.95
971285AH1-108 GEN
Adder
0.613
316426AA2-053 GEN
Solar/Wind Harmer
0.917
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.191
315652AC1-086 GEN
Solar/Wind Harmer
9.547
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.3
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
316463AE2-346 GEN
Solar/Wind Harmer
0.133
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.811
315839AE2-212 C
Solar/Wind Harmer
0.239
970657AG2-426 GEN
Solar/Wind Harmer
0.5
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.45
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316311AC2-079 GEN
Solar/Wind Harmer
3.969
315732AD1-074 GEN1
Solar/Wind Harmer
1.58
315733AD1-074 GEN2
Solar/Wind Harmer
1.58
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.922
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
313526AB2-022
Solar/Wind Harmer
0.208
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.66
957871AF2-081 GEN
Solar/Wind Harmer
3.861
316316AC1-027 C
Solar/Wind Harmer
0.236
3151081ELIZAR1
Adder
6.273
3151091ELIZAR2
Adder
6.164
316174AB2-169 GEN
Solar/Wind Harmer
1.183
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.772
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.722
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.986
315722AD1-056 GEN
Solar/Wind Harmer
2.825
970657AG2-426 GEN
Solar/Wind Harmer
1.602
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.79
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.208
316305AF2-043 C
Solar/Wind Harmer
0.233
316246AF1-032 C
Solar/Wind Harmer
0.156
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.894
316017AA1-139 ULT1
Solar/Wind Harmer
0.623
944581AF1-123 GEN
Solar/Wind Harmer
35.113
944601AF1-125 GEN
Solar/Wind Harmer
34.565
3145963POPLR C
Solar/Wind Harmer
-0.008
3142956BIRDNECK
Solar/Wind Harmer
0.413
3151101ELIZAR3
Adder
6.353
3144873MCLAUGH
Solar/Wind Harmer
0
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Harmer
0.772
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.022
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
316420AA1-050 GEN
Solar/Wind Harmer
0.862
957861AF2-080 GEN
Solar/Wind Harmer
3.309
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
316236AE1-162_GEN
Solar/Wind Harmer
0.226
971445AH1-216 GEN
Solar/Wind Harmer
4.649
3151201GRAVEL4
Adder
4.808
3151221GRAVEL6
Adder
4.802
3151191GRAVEL3
Adder
4.747
3151211GRAVEL5
Adder
4.747
315697AD1-025 GEN
Solar/Wind Harmer
1.494
316382AG1-145 C
Solar/Wind Harmer
0.195
316159AE1-175 C
Solar/Wind Harmer
0.174
957831AF2-077 GEN
Solar/Wind Harmer
0.193
3138283WHITEMARSH
Solar/Wind Harmer
0.01
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
315616AA1-038_C
Solar/Wind Helper
0.549
316283AC2-100 C
Solar/Wind Harmer
0.713
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.003
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.924
961611AG1-000B GEN
Solar/Wind Harmer
1.561
315778AD1-151 GEN
Solar/Wind Harmer
6.583
316458AB2-190 GEN2
Solar/Wind Harmer
0.745
970133AG2-095 GEN
Solar/Wind Harmer
0.83
316123AC1-075 GEN
Solar/Wind Harmer
0.79
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.527
3142946ENON
Solar/Wind Harmer
-0.002
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
316494AC1-189 GEN
Solar/Wind Harmer
0.814
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.03
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.703
961611AG1-000B GEN
Solar/Wind Harmer
3.659
316369SG1_INVT
Solar/Wind Harmer
1.32
971069AG2-661 GEN
Solar/Wind Harmer
1.17
316132AB2-190 GEN1
Solar/Wind Harmer
0.745
944631AF1-128 GEN
Adder
29.493
3138126ROCKLANDING
Solar/Wind Harmer
0.021
971317AH1-138 GEN
Solar/Wind Harmer
0.826
3142433PROV 92
Solar/Wind Harmer
-0.025
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.929
3147666LOUISA
Solar/Wind Helper
0.538
316005AA1-067
Solar/Wind Harmer
0.152
316033AB2-134 GEN
Solar/Wind Harmer
2.383
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
-0.001
3150691DARBY 3
Adder
4.202
3150701DARBY 4
Adder
4.192
3150681DARBY 2
Adder
4.188
3150671DARBY 1
Adder
4.183
942751AE2-291 GEN
Solar/Wind Harmer
4.144
966001AG1-469 GEN
Solar/Wind Helper
0.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
MECLTFEXP_MEC->PJM
CLTF
0.349
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.225
LAGNLTFEXP_LAGN->PJM
CLTF
1.773
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.519
TVALTFEXP_TVA->PJM
CLTF
0.866
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.017

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.24 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1429.58
MW Contribution:
2.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.562
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.238
3151581KERR 1
50/50
0.082
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
21.623
316313AB2-026
Solar/Wind Harmer
0.817
970301AG2-198 GEN
Solar/Wind Harmer
13.494
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3151921BEARGRDN G2
50/50
4.532
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.896
972003AH1-546 GEN
Solar/Wind Harmer
21.778
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.602
3143336POWHATN
Solar/Wind Harmer
3.063
3147133PAMPLIN
Solar/Wind Harmer
-0.083
959311AF2-222 GEN
Solar/Wind Harmer
22.328
970257AG2-171 GEN
Solar/Wind Harmer
7.784
971775AH1-396 GEN
Solar/Wind Harmer
1.464
964241AG1-285 GEN
Solar/Wind Harmer
13.72
970221AG2-151 GEN
Solar/Wind Harmer
9.179
316478AD1-087 GEN
Solar/Wind Harmer
1.131
3147043LAWRENC
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Harmer
2.99
316003AC1-222 GEN
Solar/Wind Harmer
0.97
966621AG1-532 GEN
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
1.34
944011AF1-069 GEN
Solar/Wind Harmer
5.605
970917AG2-570 GEN
Solar/Wind Harmer
23.325
3150861SPRUNCD
Adder
0.375
971683AH1-343 GEN
Solar/Wind Harmer
3.936
316190AA2-174 GEN
Solar/Wind Harmer
0.112
3156081AA2-088 GEN
Solar/Wind Harmer
2.772
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.772
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.722
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.986
315722AD1-056 GEN
Solar/Wind Harmer
2.825
970657AG2-426 GEN
Solar/Wind Harmer
1.602
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.79
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.208
316305AF2-043 C
Solar/Wind Harmer
0.233
316246AF1-032 C
Solar/Wind Harmer
0.156
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.894
316017AA1-139 ULT1
Solar/Wind Harmer
0.623
944581AF1-123 GEN
Solar/Wind Harmer
35.113
944601AF1-125 GEN
Solar/Wind Harmer
34.565
3145963POPLR C
Solar/Wind Harmer
-0.008
3142956BIRDNECK
Solar/Wind Harmer
0.413
3151101ELIZAR3
Adder
6.353
3144873MCLAUGH
Solar/Wind Harmer
0
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Harmer
0.772
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.022
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
316420AA1-050 GEN
Solar/Wind Harmer
0.862
316283AC2-100 C
Solar/Wind Harmer
0.713
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.003
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
958211AF2-115 GEN
Solar/Wind Harmer
3.913
970323AG2-213 GEN
Solar/Wind Harmer
10.378
313527AB2-043 GEN
Solar/Wind Harmer
2.566
316237AB2-079_GEN
Solar/Wind Harmer
0.466
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.472
970099AG2-077 GEN
Solar/Wind Harmer
16.454
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
315687AD1-152 GEN
Solar/Wind Harmer
1.429
3143526WINTERP
Solar/Wind Harmer
-0.061
316118AC1-105 GEN
Solar/Wind Harmer
0.805
970933AG2-581 GEN
Solar/Wind Harmer
10.522
316248AF1-058 C
Solar/Wind Harmer
0.321
972187AH1-678 GEN
Adder
2.455
972185AH1-677 GEN
Adder
4.816
313506AB2-031 GEN
Solar/Wind Harmer
0.771
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316365GEN2_N
Solar/Wind Harmer
0.593
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.236
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.055
315742AE1-103 GEN
Solar/Wind Harmer
1.935
316083AB2-161 GEN
Solar/Wind Harmer
1.287
315724AD1-057 GEN
Solar/Wind Harmer
1.554
316349AD2-085 GEN
Solar/Wind Harmer
0.699
316065AD1-022 GEN
Solar/Wind Harmer
3.933
315835AF2-110_GEN
Solar/Wind Harmer
0.979
315614AA2-178 GEN
Solar/Wind Harmer
0.84
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316435W1029_GEN3
Solar/Wind Harmer
1.405
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316240AF1-291 C
Solar/Wind Harmer
0.233
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316388AE2-253 GEN
Solar/Wind Harmer
0.519
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.811
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.539
316049AB1-081 GEN
Solar/Wind Harmer
0.822
316263AC1-034 GEN
Solar/Wind Harmer
3.582
316294AC1-161 GEN
Solar/Wind Harmer
2.453
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
2.985
3145493TOT1
Solar/Wind Harmer
0.117
3145453TOT5
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.152
972205AH1-687 GEN
50/50
22.147
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.483
3151601KERR 3
50/50
0.23
3151611KERR 4
50/50
0.23
3151621KERR 5
50/50
0.23
3151631KERR 6
50/50
0.23
316322AB2-045
Solar/Wind Harmer
1.48
971845AH1-439 GEN
Solar/Wind Harmer
23.025
316258AE1-075 C
Solar/Wind Harmer
0.735
316405AF2-144 C
Solar/Wind Harmer
0.776
946301AF1-294 GEN
Solar/Wind Harmer
6.418
961791AG1-021 GEN
Solar/Wind Harmer
3.131
970683AG2-441 GEN
Solar/Wind Harmer
16.219
970681AG2-440 GEN
Solar/Wind Harmer
10.765
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.466
316239AB2-077_GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.331
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
970831AG2-522 GEN
Solar/Wind Harmer
5.623
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.736
946281AF1-292 GEN
Solar/Wind Harmer
0.222
970673AG2-436 GEN
Solar/Wind Harmer
20.955
970533AG2-339 GEN
Solar/Wind Harmer
6.415
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.755
970581AG2-369 GEN
Solar/Wind Harmer
4.95
971285AH1-108 GEN
Adder
0.613
316426AA2-053 GEN
Solar/Wind Harmer
0.917
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.191
315652AC1-086 GEN
Solar/Wind Harmer
9.547
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.3
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
316463AE2-346 GEN
Solar/Wind Harmer
0.133
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.811
315839AE2-212 C
Solar/Wind Harmer
0.239
970657AG2-426 GEN
Solar/Wind Harmer
0.5
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.45
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316311AC2-079 GEN
Solar/Wind Harmer
3.969
315732AD1-074 GEN1
Solar/Wind Harmer
1.58
315733AD1-074 GEN2
Solar/Wind Harmer
1.58
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.922
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
313526AB2-022
Solar/Wind Harmer
0.208
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.66
957871AF2-081 GEN
Solar/Wind Harmer
3.861
316316AC1-027 C
Solar/Wind Harmer
0.236
3151081ELIZAR1
Adder
6.273
3151091ELIZAR2
Adder
6.164
316174AB2-169 GEN
Solar/Wind Harmer
1.183
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
957861AF2-080 GEN
Solar/Wind Harmer
3.309
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
316236AE1-162_GEN
Solar/Wind Harmer
0.226
971445AH1-216 GEN
Solar/Wind Harmer
4.649
3151931BEARGRDN S1
50/50
5.856
3151911BEARGRDN G1
50/50
4.532
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.674
3151531CLOVER1
50/50
2.502
3151591KERR 2
50/50
0.23
3151641KERR 7
50/50
0.23
970937AG2-583 GEN
Solar/Wind Harmer
32.775
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.603
971563AH1-280 GEN
Solar/Wind Harmer
3.131
970685AG2-442 GEN
Solar/Wind Harmer
20.932
316034AC1-036 C
Solar/Wind Harmer
0.384
315785AD2-033 C
Solar/Wind Harmer
4.498
316131AB2-060 GEN
Solar/Wind Harmer
1.738
315693AD1-088 GEN
Solar/Wind Harmer
7.923
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.134
970401AG2-262 GEN
Solar/Wind Harmer
0.837
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.849
316129AC1-054 GEN
Solar/Wind Harmer
1.005
960081AF2-299 GEN
Solar/Wind Harmer
1.114
316087AB2-174 GEN
Solar/Wind Harmer
1.383
941031AE2-094 GEN
Solar/Wind Harmer
17.887
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
8.633
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
940641AE2-051 GEN
Solar/Wind Harmer
8.505
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316023GEN1_S
Solar/Wind Harmer
0.593
939411AE1-173 GEN
Solar/Wind Harmer
43.668
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.071
316381AD1-082 GEN
Solar/Wind Harmer
0.726
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.972
316319Z2-044 C
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.031
315737AD1-076 GEN
Solar/Wind Harmer
1.485
316093AE2-104_GEN
Solar/Wind Harmer
2.276
315816AE2-034 GEN
Solar/Wind Harmer
0.63
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.32
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.922
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.398
319010AE1-072 C
Solar/Wind Harmer
1.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
944591AF1-124 GEN
Solar/Wind Harmer
35.239
3145963POPLR C
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.657
316036AC1-147 C
Solar/Wind Harmer
0.207
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.09
316072AD1-144
Solar/Wind Harmer
0.154
315773AC2-141 GEN
Solar/Wind Harmer
3.174
3146293MARTNCO
Solar/Wind Harmer
0.047
961671AG1-007 GEN
Solar/Wind Harmer
0.096
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.225
316494AC1-189 GEN
Solar/Wind Harmer
0.814
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.03
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.924
961611AG1-000B GEN
Solar/Wind Harmer
1.561
315778AD1-151 GEN
Solar/Wind Harmer
6.583
316458AB2-190 GEN2
Solar/Wind Harmer
0.745
970133AG2-095 GEN
Solar/Wind Harmer
0.83
316123AC1-075 GEN
Solar/Wind Harmer
0.79
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.527
3142946ENON
Solar/Wind Harmer
-0.002
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
316033AB2-134 GEN
Solar/Wind Harmer
2.383
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
-0.001
3150691DARBY 3
Adder
4.202
3150701DARBY 4
Adder
4.193
3150681DARBY 2
Adder
4.188
3150671DARBY 1
Adder
4.183
942751AE2-291 GEN
Solar/Wind Harmer
4.144
966001AG1-469 GEN
Solar/Wind Helper
0.199
3151171GRAVELC
Adder
0.703
961611AG1-000B GEN
Solar/Wind Harmer
3.659
316369SG1_INVT
Solar/Wind Harmer
1.32
971069AG2-661 GEN
Solar/Wind Harmer
1.17
316132AB2-190 GEN1
Solar/Wind Harmer
0.745
944631AF1-128 GEN
Adder
29.493
3138126ROCKLANDING
Solar/Wind Harmer
0.021
971317AH1-138 GEN
Solar/Wind Harmer
0.826
3142433PROV 92
Solar/Wind Harmer
-0.025
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.93
3147666LOUISA
Solar/Wind Helper
0.539
3151201GRAVEL4
Adder
4.808
3151221GRAVEL6
Adder
4.802
3151191GRAVEL3
Adder
4.747
3151211GRAVEL5
Adder
4.747
315697AD1-025 GEN
Solar/Wind Harmer
1.494
316382AG1-145 C
Solar/Wind Harmer
0.195
316159AE1-175 C
Solar/Wind Harmer
0.174
957831AF2-077 GEN
Solar/Wind Harmer
0.193
3138283WHITEMARSH
Solar/Wind Harmer
0.01
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
315616AA1-038_C
Solar/Wind Helper
0.549
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
MECLTFEXP_MEC->PJM
CLTF
0.349
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.224
LAGNLTFEXP_LAGN->PJM
CLTF
1.773
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.519
TVALTFEXP_TVA->PJM
CLTF
0.866
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.017

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.58 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1324.55
MW Contribution:
2.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.539
3144293JTRSVLE
50/50
0.56
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.646
316313AB2-026
Solar/Wind Harmer
0.866
970301AG2-198 GEN
Solar/Wind Harmer
13.373
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
970323AG2-213 GEN
Solar/Wind Harmer
10.216
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.492
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.197
970099AG2-077 GEN
Solar/Wind Harmer
15.506
964791AG1-342 GEN
Solar/Wind Harmer
2.635
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
315687AD1-152 GEN
Solar/Wind Harmer
1.352
316118AC1-105 GEN
Solar/Wind Harmer
0.77
970933AG2-581 GEN
Solar/Wind Harmer
9.651
316248AF1-058 C
Solar/Wind Harmer
0.305
313506AB2-031 GEN
Solar/Wind Harmer
0.725
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.303
3151921BEARGRDN G2
50/50
4.593
3144293JTRSVLE
50/50
0.56
972003AH1-546 GEN
Solar/Wind Harmer
22.059
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.593
3147133PAMPLIN
Solar/Wind Harmer
-0.082
959311AF2-222 GEN
Solar/Wind Harmer
22.005
970257AG2-171 GEN
Solar/Wind Harmer
7.662
971775AH1-396 GEN
Solar/Wind Harmer
1.442
964241AG1-285 GEN
Solar/Wind Harmer
13.399
970221AG2-151 GEN
Solar/Wind Harmer
9.591
316478AD1-087 GEN
Solar/Wind Harmer
1.07
270494AE1-108_GEN
Solar/Wind Harmer
3.119
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.922
966621AG1-532 GEN
Solar/Wind Harmer
0.189
316181AB2-040 GEN
Solar/Wind Harmer
1.26
971683AH1-343 GEN
Solar/Wind Harmer
3.742
316190AA2-174 GEN
Solar/Wind Harmer
0.105
944011AF1-069 GEN
Solar/Wind Harmer
4.972
970917AG2-570 GEN
Solar/Wind Harmer
20.942
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.588
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.651
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.673
315813AE1-149 C
Solar/Wind Harmer
4.802
316317KELFORD C
Solar/Wind Harmer
0.354
3145823KELFORD
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
1.525
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.838
315722AD1-056 GEN
Solar/Wind Harmer
2.623
316458AB2-190 GEN2
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.494
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.731
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
50/50
22.443
316303AF2-085
50/50
2.628
316322AB2-045
Solar/Wind Harmer
1.492
971845AH1-439 GEN
Solar/Wind Harmer
23.204
316258AE1-075 C
Solar/Wind Harmer
0.779
316405AF2-144 C
Solar/Wind Harmer
0.823
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
16.031
970681AG2-440 GEN
Solar/Wind Harmer
10.64
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.235
971283AH1-107 GEN
Solar/Wind Harmer
2.235
316486AD2-202 GEN
Solar/Wind Harmer
0.313
970831AG2-522 GEN
Solar/Wind Harmer
5.345
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
17.883
946281AF1-292 GEN
Solar/Wind Harmer
0.209
3137643SOCKMAN
Solar/Wind Harmer
-0.035
316426AA2-053 GEN
Solar/Wind Harmer
0.86
970673AG2-436 GEN
Solar/Wind Harmer
18.644
970533AG2-339 GEN
Solar/Wind Harmer
5.691
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.171
970581AG2-369 GEN
Solar/Wind Harmer
4.447
315814AE2-033 C
Solar/Wind Harmer
7.589
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.891
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.846
315839AE2-212 C
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.212
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
0.476
316327AA2-057 GEN
Solar/Wind Harmer
0.754
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316311AC2-079 GEN
Solar/Wind Harmer
3.723
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.198
315697AD1-025 GEN
Solar/Wind Harmer
1.465
315732AD1-074 GEN1
Solar/Wind Harmer
1.463
315733AD1-074 GEN2
Solar/Wind Harmer
1.463
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.777
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.552
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.038
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.802
316083AB2-161 GEN
Solar/Wind Harmer
1.227
316349AD2-085 GEN
Solar/Wind Harmer
0.655
315724AD1-057 GEN
Solar/Wind Harmer
1.443
316065AD1-022 GEN
Solar/Wind Harmer
3.644
315835AF2-110_GEN
Solar/Wind Harmer
0.909
316033AB2-134 GEN
Solar/Wind Harmer
2.337
3142366NRTHEST
Adder
0.21
315614AA2-178 GEN
Solar/Wind Harmer
0.777
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3151931BEARGRDN S1
50/50
5.934
3151911BEARGRDN G1
50/50
4.593
3144293JTRSVLE
50/50
0.56
3144293JTRSVLE
50/50
0.442
970119AG2-088 GEN
50/50
19.708
970937AG2-583 GEN
Solar/Wind Harmer
33.601
3146776BUCKING
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
20.721
316034AC1-036 C
Solar/Wind Harmer
0.378
315785AD2-033 C
Solar/Wind Harmer
4.42
3143226MDLTHAN
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
1.689
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.6
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.764
970401AG2-262 GEN
Solar/Wind Harmer
0.805
3147043LAWRENC
Adder
0.899
971065AG2-659 GEN
Solar/Wind Harmer
5.573
316129AC1-054 GEN
Solar/Wind Harmer
0.957
3150851SPRUNCC
Adder
0.417
960081AF2-299 GEN
Solar/Wind Harmer
1.05
316087AB2-174 GEN
Solar/Wind Harmer
1.301
3145783HORNRTN
Solar/Wind Harmer
-0.009
3142543TWELFTH
Solar/Wind Harmer
-0.001
941031AE2-094 GEN
Solar/Wind Harmer
15.869
315607AA1-063A GEN
Solar/Wind Harmer
0.851
970919AG2-571 GEN
Solar/Wind Harmer
2.651
970087AG2-069 GEN
Solar/Wind Harmer
7.756
316023GEN1_S
Solar/Wind Harmer
0.552
940641AE2-051 GEN
Solar/Wind Harmer
7.519
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.962
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.397
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316381AD1-082 GEN
Solar/Wind Harmer
0.692
3156021HOLLOMANSOL
Solar/Wind Harmer
0.994
316132AB2-190 GEN1
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
316319Z2-044 C
Solar/Wind Harmer
0.403
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.114
316369SG1_INVT
Solar/Wind Harmer
1.295
315737AD1-076 GEN
Solar/Wind Harmer
1.375
944631AF1-128 GEN
Adder
30.668
315816AE2-034 GEN
Solar/Wind Harmer
0.583
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.774
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.777
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
1.509
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
316321Z2-027
Solar/Wind Harmer
0.192
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
3142956BIRDNECK
Solar/Wind Harmer
0.381
3144873MCLAUGH
Solar/Wind Harmer
0
3151171GRAVELC
Adder
0.885
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.868
944581AF1-123 GEN
Solar/Wind Harmer
32.275
944601AF1-125 GEN
Solar/Wind Harmer
31.771
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.664
961601AG1-000A GEN
Solar/Wind Harmer
2.801
3145933PARMELE
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.799
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.751
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.834
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.264
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.192
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
316174AB2-169 GEN
Solar/Wind Harmer
1.095
316316AC1-027 C
Solar/Wind Harmer
0.218
3151201GRAVEL4
Adder
4.604
3151221GRAVEL6
Adder
4.599
3151191GRAVEL3
Adder
4.546
3151211GRAVEL5
Adder
4.546
316236AE1-162_GEN
Solar/Wind Harmer
0.214
971445AH1-216 GEN
Solar/Wind Harmer
4.396
3151081ELIZAR1
Adder
5.794
3151091ELIZAR2
Adder
5.693
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.064
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
316382AG1-145 C
Solar/Wind Harmer
0.19
316159AE1-175 C
Solar/Wind Harmer
0.169
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.102
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
315616AA1-038_C
Solar/Wind Helper
0.535
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
316435W1029_GEN3
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
316049AB1-081 GEN
Solar/Wind Harmer
0.762
316263AC1-034 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
2.766
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3150691DARBY 3
Adder
4.503
3150701DARBY 4
Adder
4.493
3150681DARBY 2
Adder
4.488
3150671DARBY 1
Adder
4.482
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.043
316005AA1-067
Solar/Wind Harmer
0.141
316294AC1-161 GEN
Solar/Wind Harmer
2.243
3142946ENON
Solar/Wind Harmer
-0.001
966001AG1-469 GEN
Solar/Wind Helper
0.186
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.536
3145963POPLR C
Solar/Wind Harmer
-0.007
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.456
316036AC1-147 C
Solar/Wind Harmer
0.191
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.391
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.143
316359AB2-059 GEN
Solar/Wind Harmer
0.953
3142053HEARTS
Solar/Wind Harmer
0.083
3146293MARTNCO
Solar/Wind Harmer
0.044
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.208
316494AC1-189 GEN
Solar/Wind Harmer
0.754
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315773AC2-141 GEN
Solar/Wind Harmer
2.902
3138126ROCKLANDING
Solar/Wind Harmer
0.02
3142433PROV 92
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
971317AH1-138 GEN
Solar/Wind Harmer
0.794
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.8
3147666LOUISA
Solar/Wind Helper
0.46
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.352
MECLTFEXP_MEC->PJM
CLTF
0.255
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
3.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.141
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.559
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.779
TVALTFEXP_TVA->PJM
CLTF
0.76
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.58 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1324.55
MW Contribution:
2.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.539
3144293JTRSVLE
50/50
0.56
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.646
316313AB2-026
Solar/Wind Harmer
0.866
970301AG2-198 GEN
Solar/Wind Harmer
13.373
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
970323AG2-213 GEN
Solar/Wind Harmer
10.216
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.492
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3151921BEARGRDN G2
50/50
4.593
3144293JTRSVLE
50/50
0.56
972003AH1-546 GEN
Solar/Wind Harmer
22.059
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.593
3147133PAMPLIN
Solar/Wind Harmer
-0.082
959311AF2-222 GEN
Solar/Wind Harmer
22.005
970257AG2-171 GEN
Solar/Wind Harmer
7.662
971775AH1-396 GEN
Solar/Wind Harmer
1.442
964241AG1-285 GEN
Solar/Wind Harmer
13.399
970221AG2-151 GEN
Solar/Wind Harmer
9.591
316478AD1-087 GEN
Solar/Wind Harmer
1.07
270494AE1-108_GEN
Solar/Wind Harmer
3.119
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.922
966621AG1-532 GEN
Solar/Wind Harmer
0.189
316181AB2-040 GEN
Solar/Wind Harmer
1.26
971683AH1-343 GEN
Solar/Wind Harmer
3.742
316190AA2-174 GEN
Solar/Wind Harmer
0.105
944011AF1-069 GEN
Solar/Wind Harmer
4.972
970917AG2-570 GEN
Solar/Wind Harmer
20.942
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.588
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.651
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.673
315813AE1-149 C
Solar/Wind Harmer
4.802
316317KELFORD C
Solar/Wind Harmer
0.354
3145823KELFORD
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
1.525
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.838
315722AD1-056 GEN
Solar/Wind Harmer
2.623
316458AB2-190 GEN2
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.494
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.731
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
1.509
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
316321Z2-027
Solar/Wind Harmer
0.192
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
3142956BIRDNECK
Solar/Wind Harmer
0.381
3144873MCLAUGH
Solar/Wind Harmer
0
3151171GRAVELC
Adder
0.885
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.868
944581AF1-123 GEN
Solar/Wind Harmer
32.275
944601AF1-125 GEN
Solar/Wind Harmer
31.771
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.664
961601AG1-000A GEN
Solar/Wind Harmer
2.801
3145933PARMELE
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.799
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.197
970099AG2-077 GEN
Solar/Wind Harmer
15.506
964791AG1-342 GEN
Solar/Wind Harmer
2.635
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
315687AD1-152 GEN
Solar/Wind Harmer
1.352
316118AC1-105 GEN
Solar/Wind Harmer
0.77
970933AG2-581 GEN
Solar/Wind Harmer
9.651
316248AF1-058 C
Solar/Wind Harmer
0.305
313506AB2-031 GEN
Solar/Wind Harmer
0.725
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.303
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.552
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.038
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.802
316083AB2-161 GEN
Solar/Wind Harmer
1.227
316349AD2-085 GEN
Solar/Wind Harmer
0.655
315724AD1-057 GEN
Solar/Wind Harmer
1.443
316065AD1-022 GEN
Solar/Wind Harmer
3.644
315835AF2-110_GEN
Solar/Wind Harmer
0.909
316033AB2-134 GEN
Solar/Wind Harmer
2.337
3142366NRTHEST
Adder
0.21
315614AA2-178 GEN
Solar/Wind Harmer
0.777
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
316435W1029_GEN3
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
316049AB1-081 GEN
Solar/Wind Harmer
0.762
316263AC1-034 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
2.766
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3150691DARBY 3
Adder
4.503
3150701DARBY 4
Adder
4.493
3150681DARBY 2
Adder
4.488
3150671DARBY 1
Adder
4.482
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.043
316005AA1-067
Solar/Wind Harmer
0.141
316294AC1-161 GEN
Solar/Wind Harmer
2.243
3142946ENON
Solar/Wind Harmer
-0.001
966001AG1-469 GEN
Solar/Wind Helper
0.186
316123AC1-075 GEN
Solar/Wind Harmer
0.751
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.834
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.264
3151931BEARGRDN S1
50/50
5.934
3151911BEARGRDN G1
50/50
4.593
3144293JTRSVLE
50/50
0.56
3144293JTRSVLE
50/50
0.442
970119AG2-088 GEN
50/50
19.708
970937AG2-583 GEN
Solar/Wind Harmer
33.601
3146776BUCKING
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
20.721
316034AC1-036 C
Solar/Wind Harmer
0.378
315785AD2-033 C
Solar/Wind Harmer
4.42
3143226MDLTHAN
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
1.689
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.6
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.764
970401AG2-262 GEN
Solar/Wind Harmer
0.805
3147043LAWRENC
Adder
0.899
971065AG2-659 GEN
Solar/Wind Harmer
5.573
316129AC1-054 GEN
Solar/Wind Harmer
0.957
3150851SPRUNCC
Adder
0.417
960081AF2-299 GEN
Solar/Wind Harmer
1.05
316087AB2-174 GEN
Solar/Wind Harmer
1.301
3145783HORNRTN
Solar/Wind Harmer
-0.009
3142543TWELFTH
Solar/Wind Harmer
-0.001
941031AE2-094 GEN
Solar/Wind Harmer
15.869
315607AA1-063A GEN
Solar/Wind Harmer
0.851
970919AG2-571 GEN
Solar/Wind Harmer
2.651
970087AG2-069 GEN
Solar/Wind Harmer
7.756
316023GEN1_S
Solar/Wind Harmer
0.552
940641AE2-051 GEN
Solar/Wind Harmer
7.519
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.962
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.397
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316381AD1-082 GEN
Solar/Wind Harmer
0.692
3156021HOLLOMANSOL
Solar/Wind Harmer
0.994
316132AB2-190 GEN1
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
316319Z2-044 C
Solar/Wind Harmer
0.403
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.114
316369SG1_INVT
Solar/Wind Harmer
1.295
315737AD1-076 GEN
Solar/Wind Harmer
1.375
944631AF1-128 GEN
Adder
30.668
315816AE2-034 GEN
Solar/Wind Harmer
0.583
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.774
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.777
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.536
3145963POPLR C
Solar/Wind Harmer
-0.007
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.456
316036AC1-147 C
Solar/Wind Harmer
0.191
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.391
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.143
316359AB2-059 GEN
Solar/Wind Harmer
0.953
3142053HEARTS
Solar/Wind Harmer
0.083
3146293MARTNCO
Solar/Wind Harmer
0.044
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.208
316494AC1-189 GEN
Solar/Wind Harmer
0.754
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315773AC2-141 GEN
Solar/Wind Harmer
2.902
3138126ROCKLANDING
Solar/Wind Harmer
0.02
3142433PROV 92
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
971317AH1-138 GEN
Solar/Wind Harmer
0.794
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.8
3147666LOUISA
Solar/Wind Helper
0.46
972205AH1-687 GEN
50/50
22.443
316303AF2-085
50/50
2.628
316322AB2-045
Solar/Wind Harmer
1.492
971845AH1-439 GEN
Solar/Wind Harmer
23.204
316258AE1-075 C
Solar/Wind Harmer
0.779
316405AF2-144 C
Solar/Wind Harmer
0.823
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
16.031
970681AG2-440 GEN
Solar/Wind Harmer
10.64
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.235
971283AH1-107 GEN
Solar/Wind Harmer
2.235
316486AD2-202 GEN
Solar/Wind Harmer
0.313
970831AG2-522 GEN
Solar/Wind Harmer
5.345
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
17.883
946281AF1-292 GEN
Solar/Wind Harmer
0.209
3137643SOCKMAN
Solar/Wind Harmer
-0.035
316426AA2-053 GEN
Solar/Wind Harmer
0.86
970673AG2-436 GEN
Solar/Wind Harmer
18.644
970533AG2-339 GEN
Solar/Wind Harmer
5.691
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.171
970581AG2-369 GEN
Solar/Wind Harmer
4.447
315814AE2-033 C
Solar/Wind Harmer
7.589
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.891
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.846
315839AE2-212 C
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.212
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
0.476
316327AA2-057 GEN
Solar/Wind Harmer
0.754
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316311AC2-079 GEN
Solar/Wind Harmer
3.723
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.198
315697AD1-025 GEN
Solar/Wind Harmer
1.465
315732AD1-074 GEN1
Solar/Wind Harmer
1.463
315733AD1-074 GEN2
Solar/Wind Harmer
1.463
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.777
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.192
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
316174AB2-169 GEN
Solar/Wind Harmer
1.095
316316AC1-027 C
Solar/Wind Harmer
0.218
3151201GRAVEL4
Adder
4.604
3151221GRAVEL6
Adder
4.599
3151191GRAVEL3
Adder
4.546
3151211GRAVEL5
Adder
4.546
316236AE1-162_GEN
Solar/Wind Harmer
0.214
971445AH1-216 GEN
Solar/Wind Harmer
4.396
3151081ELIZAR1
Adder
5.794
3151091ELIZAR2
Adder
5.693
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.064
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
316382AG1-145 C
Solar/Wind Harmer
0.19
316159AE1-175 C
Solar/Wind Harmer
0.169
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.102
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
315616AA1-038_C
Solar/Wind Helper
0.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.352
MECLTFEXP_MEC->PJM
CLTF
0.255
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
3.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.141
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.559
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.779
TVALTFEXP_TVA->PJM
CLTF
0.76
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B3_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.83 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:903.29
MW Contribution:
2.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.994
3144293JTRSVLE
50/50
0.585
972003AH1-546 GEN
Solar/Wind Harmer
23.964
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.022
942461AE2-259 GEN
Solar/Wind Harmer
4.864
3143336POWHATN
Solar/Wind Harmer
3.18
3147133PAMPLIN
Solar/Wind Harmer
-0.086
959311AF2-222 GEN
Solar/Wind Harmer
22.721
970257AG2-171 GEN
Solar/Wind Harmer
7.89
971775AH1-396 GEN
Solar/Wind Harmer
1.485
964241AG1-285 GEN
Solar/Wind Harmer
13.573
316478AD1-087 GEN
Solar/Wind Harmer
1.034
3147043LAWRENC
Solar/Wind Harmer
-0.006
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.173
316181AB2-040 GEN
Solar/Wind Harmer
1.149
971683AH1-343 GEN
Solar/Wind Harmer
3.439
3150861SPRUNCD
Adder
0.323
316190AA2-174 GEN
Solar/Wind Harmer
0.095
970917AG2-570 GEN
Solar/Wind Harmer
18.451
944011AF1-069 GEN
Solar/Wind Harmer
4.319
3156081AA2-088 GEN
Solar/Wind Harmer
2.294
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.461
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.599
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.313
3145823KELFORD
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
2.313
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.135
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.65
3138543CONSLDL
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
4.018
972205AH1-687 GEN
50/50
24.401
316322AB2-045
Solar/Wind Harmer
1.609
971845AH1-439 GEN
Solar/Wind Harmer
25.005
316258AE1-075 C
Solar/Wind Harmer
0.763
316405AF2-144 C
Solar/Wind Harmer
0.806
946301AF1-294 GEN
Solar/Wind Harmer
6.653
961791AG1-021 GEN
Solar/Wind Harmer
3.245
970683AG2-441 GEN
Solar/Wind Harmer
16.65
970681AG2-440 GEN
Solar/Wind Harmer
11.051
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.451
316239AB2-077_GEN
Solar/Wind Harmer
0.451
316486AD2-202 GEN
Solar/Wind Harmer
0.303
316233AE1-074 FULL
Solar/Wind Harmer
0.277
970909AG2-566 GEN
50/50
2.663
3144293JTRSVLE
50/50
0.585
970535AG2-341 GEN
50/50
2.129
3146776BUCKING
Solar/Wind Harmer
-0.191
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
22.829
316313AB2-026
Solar/Wind Harmer
0.848
970301AG2-198 GEN
Solar/Wind Harmer
14.027
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.022
958211AF2-115 GEN
Solar/Wind Harmer
4.057
970323AG2-213 GEN
Solar/Wind Harmer
10.52
313527AB2-043 GEN
Solar/Wind Harmer
2.494
316237AB2-079_GEN
Solar/Wind Harmer
0.451
962561AG1-105 GEN
Solar/Wind Harmer
7.051
971223AH1-071 GEN
Solar/Wind Harmer
1.533
964791AG1-342 GEN
Solar/Wind Harmer
2.569
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.915
316118AC1-105 GEN
Solar/Wind Harmer
0.741
315687AD1-152 GEN
Solar/Wind Harmer
1.294
3143526WINTERP
Solar/Wind Harmer
-0.053
316248AF1-058 C
Solar/Wind Harmer
0.289
970933AG2-581 GEN
Solar/Wind Harmer
8.888
313506AB2-031 GEN
Solar/Wind Harmer
0.662
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.093
972187AH1-678 GEN
Adder
1.941
972185AH1-677 GEN
Adder
3.779
316365GEN2_N
Solar/Wind Harmer
0.487
3144356SAPONY
Solar/Wind Harmer
0.244
316315AB2-025 C
Solar/Wind Harmer
0.188
962571AG1-106 GEN
Solar/Wind Harmer
1.005
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.046
315742AE1-103 GEN
Solar/Wind Harmer
1.569
315724AD1-057 GEN
Solar/Wind Harmer
1.272
316240AF1-291 C
Solar/Wind Harmer
0.192
316083AB2-161 GEN
Solar/Wind Harmer
1.033
944641AF1-129 GEN
Adder
27.005
3143096IRON208
Adder
0.238
3143096IRON208
Adder
0.233
3146206CASHIE
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.674
971283AH1-107 GEN
Solar/Wind Harmer
1.674
970831AG2-522 GEN
Solar/Wind Harmer
5.074
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
16.127
946281AF1-292 GEN
Solar/Wind Harmer
0.191
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971285AH1-108 GEN
Adder
0.528
316426AA2-053 GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970673AG2-436 GEN
Solar/Wind Harmer
16.266
970533AG2-339 GEN
Solar/Wind Harmer
4.944
970085AG2-068 GEN
Solar/Wind Harmer
4.553
970581AG2-369 GEN
Solar/Wind Harmer
3.916
316274AC1-208 GEN
Solar/Wind Harmer
0.757
315814AE2-033 C
Solar/Wind Harmer
6.529
315652AC1-086 GEN
Solar/Wind Harmer
7.869
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.079
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.027
316463AE2-346 GEN
Solar/Wind Harmer
0.109
3145513AHOSKIE
Solar/Wind Harmer
0.059
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.67
3143316POE
Solar/Wind Harmer
-0.026
315839AE2-212 C
Solar/Wind Harmer
0.195
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.784
3151931BEARGRDN S1
50/50
6.452
3151911BEARGRDN G1
50/50
4.994
3144293JTRSVLE
50/50
0.585
3144293JTRSVLE
50/50
0.462
970937AG2-583 GEN
Solar/Wind Harmer
35.585
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.022
3143336POWHATN
Solar/Wind Harmer
3.741
971563AH1-280 GEN
Solar/Wind Harmer
3.245
970685AG2-442 GEN
Solar/Wind Harmer
21.59
316034AC1-036 C
Solar/Wind Harmer
0.39
315785AD2-033 C
Solar/Wind Harmer
4.533
316131AB2-060 GEN
Solar/Wind Harmer
1.695
315693AD1-088 GEN
Solar/Wind Harmer
7.541
3143226MDLTHAN
Solar/Wind Harmer
-0.012
970401AG2-262 GEN
Solar/Wind Harmer
0.785
957481AF2-042 GEN
Solar/Wind Harmer
37.288
971065AG2-659 GEN
Solar/Wind Harmer
5.332
3147043LAWRENC
Adder
0.854
316129AC1-054 GEN
Solar/Wind Harmer
0.913
3143526WINTERP
Solar/Wind Harmer
-0.053
960081AF2-299 GEN
Solar/Wind Harmer
0.96
316087AB2-174 GEN
Solar/Wind Harmer
1.187
3150851SPRUNCC
Adder
0.323
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.767
970919AG2-571 GEN
Solar/Wind Harmer
2.336
941031AE2-094 GEN
Solar/Wind Harmer
13.785
970087AG2-069 GEN
Solar/Wind Harmer
6.83
316023GEN1_S
Solar/Wind Harmer
0.487
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
940641AE2-051 GEN
Solar/Wind Harmer
6.432
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3145683EARLEYS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
33.321
3156021HOLLOMANSOL
Solar/Wind Harmer
0.868
316319Z2-044 C
Solar/Wind Harmer
0.356
3146233WITAKRS
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.238
315671AE2-027_GEN
Solar/Wind Harmer
1.15
316381AD1-082 GEN
Solar/Wind Harmer
0.583
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.591
316065AD1-022 GEN
Solar/Wind Harmer
3.169
966001AG1-469 GEN
Solar/Wind Helper
0.167
3132123MT JACKSON
Solar/Wind Helper
0.376
316283AC2-100 C
Solar/Wind Harmer
0.599
970657AG2-426 GEN
Solar/Wind Harmer
1.285
315821AE2-092 GEN
Solar/Wind Helper
6.554
970657AG2-426 GEN
Solar/Wind Harmer
0.401
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
3148463FAIRFLD
Solar/Wind Helper
0.141
315616AA1-038_C
Solar/Wind Helper
0.642
3148013FISHERV
Solar/Wind Helper
0.273
316499AE2-029_GEN
Solar/Wind Helper
0.588
3132273ORANGE
Solar/Wind Helper
0.023
3147983MERCK5
Solar/Wind Helper
0.064
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.118
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.06
CPLELTFEXP_CPLE->PJM
CLTF
3.428
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.971
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.18
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.537
LAGNLTFEXP_LAGN->PJM
CLTF
0.856
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.321
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.399
NYPJM->LTFIMP_NY
CLTF
0.337

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.17 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:658.25
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.357
316478AD1-087 GEN
Solar/Wind Harmer
1.086
971683AH1-343 GEN
Solar/Wind Harmer
5.14
316123AC1-075 GEN
Solar/Wind Harmer
0.149
316222AC1-221 GEN
Solar/Wind Harmer
0.443
316283AC2-100 C
Solar/Wind Harmer
0.206
970909AG2-566 GEN
50/50
6.347
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
970933AG2-581 GEN
Solar/Wind Harmer
27.858
970099AG2-077 GEN
Solar/Wind Harmer
36.297
316118AC1-105 GEN
Solar/Wind Harmer
0.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.688
942751AE2-291 GEN
Solar/Wind Harmer
5.335
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.242
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.543
3147133PAMPLIN
Solar/Wind Helper
1.064
315821AE2-092 GEN
Solar/Wind Helper
1.922
270494AE1-108_GEN
Solar/Wind Helper
2.774
3151541CLOVER2
50/50
6.689
3151601KERR 3
50/50
0.297
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
3151631KERR 6
50/50
0.297
971967AH1-528 GEN
Solar/Wind Harmer
55.714
316486AD2-202 GEN
Solar/Wind Harmer
0.319
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
970831AG2-522 GEN
Solar/Wind Harmer
4.544
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.182
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.741
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
971629AH1-314 GEN
50/50
5.005
315693AD1-088 GEN
Solar/Wind Harmer
18.249
957481AF2-042 GEN
Solar/Wind Harmer
90.743
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.07
316129AC1-054 GEN
Solar/Wind Harmer
0.424
316131AB2-060 GEN
Solar/Wind Harmer
0.206
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.6 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:643.52
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.357
316478AD1-087 GEN
Solar/Wind Harmer
1.086
971683AH1-343 GEN
Solar/Wind Harmer
5.14
970909AG2-566 GEN
50/50
6.347
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
970099AG2-077 GEN
Solar/Wind Harmer
36.297
316118AC1-105 GEN
Solar/Wind Harmer
0.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.688
942751AE2-291 GEN
Solar/Wind Harmer
5.335
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.242
3151531CLOVER1
50/50
6.741
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
971629AH1-314 GEN
50/50
5.005
315693AD1-088 GEN
Solar/Wind Harmer
18.249
957481AF2-042 GEN
Solar/Wind Harmer
90.743
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.07
316129AC1-054 GEN
Solar/Wind Harmer
0.424
316131AB2-060 GEN
Solar/Wind Harmer
0.206
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.217
316123AC1-075 GEN
Solar/Wind Harmer
0.149
316222AC1-221 GEN
Solar/Wind Harmer
0.443
316283AC2-100 C
Solar/Wind Harmer
0.206
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.543
3147133PAMPLIN
Solar/Wind Helper
1.064
315821AE2-092 GEN
Solar/Wind Helper
1.922
270494AE1-108_GEN
Solar/Wind Helper
2.774
3151541CLOVER2
50/50
6.689
3151601KERR 3
50/50
0.297
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
3151631KERR 6
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.319
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
970831AG2-522 GEN
Solar/Wind Harmer
4.544
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.182
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.18 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:777.13
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.412
316478AD1-087 GEN
Solar/Wind Harmer
3.047
316003AC1-222 GEN
Solar/Wind Harmer
1.679
971683AH1-343 GEN
Solar/Wind Harmer
6.798
316123AC1-075 GEN
Solar/Wind Harmer
1.354
316222AC1-221 GEN
Solar/Wind Harmer
1.232
316283AC2-100 C
Solar/Wind Harmer
1.123
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.54
3147133PAMPLIN
Solar/Wind Helper
1.062
315821AE2-092 GEN
Solar/Wind Helper
1.926
270494AE1-108_GEN
Solar/Wind Helper
2.776
970909AG2-566 GEN
50/50
6.35
3152661PLYWOOD A
50/50
0.343
3151581KERR 1
50/50
0.106
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.444
970933AG2-581 GEN
Solar/Wind Harmer
36.737
970099AG2-077 GEN
Solar/Wind Harmer
47.87
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316248AF1-058 C
Solar/Wind Harmer
0.557
316118AC1-105 GEN
Solar/Wind Harmer
1.127
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.524
942751AE2-291 GEN
Solar/Wind Harmer
7.062
316237AB2-079_GEN
Solar/Wind Harmer
0.274
313527AB2-043 GEN
Solar/Wind Harmer
1.359
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.244
3151541CLOVER2
50/50
6.702
3151601KERR 3
50/50
0.298
3151611KERR 4
50/50
0.298
3151621KERR 5
50/50
0.298
3151631KERR 6
50/50
0.298
971967AH1-528 GEN
Solar/Wind Harmer
73.669
316486AD2-202 GEN
Solar/Wind Harmer
0.892
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
6.001
316238AB2-078_GEN
Solar/Wind Harmer
0.274
316239AB2-077_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.183
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.754
3151591KERR 2
50/50
0.298
3151641KERR 7
50/50
0.298
315693AD1-088 GEN
Solar/Wind Harmer
21.387
957481AF2-042 GEN
Solar/Wind Harmer
119.676
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316131AB2-060 GEN
Solar/Wind Harmer
0.805
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.597
MECLTFEXP_MEC->PJM
CLTF
1.296
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.231
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.155
LAGNLTFEXP_LAGN->PJM
CLTF
2.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.917
TVALTFEXP_TVA->PJM
CLTF
1.346
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.46
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.14 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:776.84
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
6.35
3152661PLYWOOD A
50/50
0.343
3151581KERR 1
50/50
0.106
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.444
970933AG2-581 GEN
Solar/Wind Harmer
36.737
970099AG2-077 GEN
Solar/Wind Harmer
47.87
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316248AF1-058 C
Solar/Wind Harmer
0.557
316118AC1-105 GEN
Solar/Wind Harmer
1.127
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.524
942751AE2-291 GEN
Solar/Wind Harmer
7.062
316237AB2-079_GEN
Solar/Wind Harmer
0.274
313527AB2-043 GEN
Solar/Wind Harmer
1.359
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.244
970413AG2-270 GEN
50/50
29.412
316478AD1-087 GEN
Solar/Wind Harmer
3.047
316003AC1-222 GEN
Solar/Wind Harmer
1.679
971683AH1-343 GEN
Solar/Wind Harmer
6.798
316123AC1-075 GEN
Solar/Wind Harmer
1.354
316222AC1-221 GEN
Solar/Wind Harmer
1.232
316283AC2-100 C
Solar/Wind Harmer
1.123
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.54
3147133PAMPLIN
Solar/Wind Helper
1.062
315821AE2-092 GEN
Solar/Wind Helper
1.926
270494AE1-108_GEN
Solar/Wind Helper
2.776
3151541CLOVER2
50/50
6.702
3151601KERR 3
50/50
0.298
3151611KERR 4
50/50
0.298
3151621KERR 5
50/50
0.298
3151631KERR 6
50/50
0.298
971967AH1-528 GEN
Solar/Wind Harmer
73.669
316486AD2-202 GEN
Solar/Wind Harmer
0.892
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
6.001
316238AB2-078_GEN
Solar/Wind Harmer
0.274
316239AB2-077_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.183
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.754
3151591KERR 2
50/50
0.298
3151641KERR 7
50/50
0.298
315693AD1-088 GEN
Solar/Wind Harmer
21.387
957481AF2-042 GEN
Solar/Wind Harmer
119.676
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316131AB2-060 GEN
Solar/Wind Harmer
0.805
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.597
MECLTFEXP_MEC->PJM
CLTF
1.296
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.231
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.155
LAGNLTFEXP_LAGN->PJM
CLTF
2.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.917
TVALTFEXP_TVA->PJM
CLTF
1.346
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.46
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.98 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:754.79
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.357
316478AD1-087 GEN
Solar/Wind Harmer
3.041
316003AC1-222 GEN
Solar/Wind Harmer
1.672
971683AH1-343 GEN
Solar/Wind Harmer
6.767
316123AC1-075 GEN
Solar/Wind Harmer
1.347
316222AC1-221 GEN
Solar/Wind Harmer
1.22
970909AG2-566 GEN
50/50
6.347
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970301AG2-198 GEN
Solar/Wind Harmer
33.427
970933AG2-581 GEN
Solar/Wind Harmer
36.679
970099AG2-077 GEN
Solar/Wind Harmer
47.791
315687AD1-152 GEN
Solar/Wind Harmer
3.506
316248AF1-058 C
Solar/Wind Harmer
0.555
316118AC1-105 GEN
Solar/Wind Harmer
1.123
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.489
942751AE2-291 GEN
Solar/Wind Harmer
7.024
316237AB2-079_GEN
Solar/Wind Harmer
0.272
313527AB2-043 GEN
Solar/Wind Harmer
1.352
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.242
316283AC2-100 C
Solar/Wind Harmer
1.112
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.543
3147133PAMPLIN
Solar/Wind Helper
1.064
315821AE2-092 GEN
Solar/Wind Helper
1.922
270494AE1-108_GEN
Solar/Wind Helper
2.774
3151541CLOVER2
50/50
6.689
3151601KERR 3
50/50
0.297
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
3151631KERR 6
50/50
0.297
971967AH1-528 GEN
Solar/Wind Harmer
73.553
316486AD2-202 GEN
Solar/Wind Harmer
0.891
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
5.983
316238AB2-078_GEN
Solar/Wind Harmer
0.272
316239AB2-077_GEN
Solar/Wind Harmer
0.272
270455AD2-022 GEN
Solar/Wind Harmer
1.349
270457AD2-023 GEN
Solar/Wind Harmer
0.684
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.182
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.741
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
315693AD1-088 GEN
Solar/Wind Harmer
21.358
957481AF2-042 GEN
Solar/Wind Harmer
119.479
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.676
316129AC1-054 GEN
Solar/Wind Harmer
1.114
316131AB2-060 GEN
Solar/Wind Harmer
0.8
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:713.33
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.357
316478AD1-087 GEN
Solar/Wind Harmer
3.041
316003AC1-222 GEN
Solar/Wind Harmer
1.672
971683AH1-343 GEN
Solar/Wind Harmer
6.767
316123AC1-075 GEN
Solar/Wind Harmer
1.347
316222AC1-221 GEN
Solar/Wind Harmer
1.22
316283AC2-100 C
Solar/Wind Harmer
1.112
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.543
3147133PAMPLIN
Solar/Wind Helper
1.064
315821AE2-092 GEN
Solar/Wind Helper
1.922
270494AE1-108_GEN
Solar/Wind Helper
2.774
970909AG2-566 GEN
50/50
6.347
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970301AG2-198 GEN
Solar/Wind Harmer
33.427
970099AG2-077 GEN
Solar/Wind Harmer
47.791
315687AD1-152 GEN
Solar/Wind Harmer
3.506
316248AF1-058 C
Solar/Wind Harmer
0.555
316118AC1-105 GEN
Solar/Wind Harmer
1.123
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.489
942751AE2-291 GEN
Solar/Wind Harmer
7.024
316237AB2-079_GEN
Solar/Wind Harmer
0.272
313527AB2-043 GEN
Solar/Wind Harmer
1.352
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.242
3151531CLOVER1
50/50
6.741
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
315693AD1-088 GEN
Solar/Wind Harmer
21.358
957481AF2-042 GEN
Solar/Wind Harmer
119.479
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.676
316129AC1-054 GEN
Solar/Wind Harmer
1.114
316131AB2-060 GEN
Solar/Wind Harmer
0.8
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.217
3151541CLOVER2
50/50
6.689
3151601KERR 3
50/50
0.297
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
3151631KERR 6
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.891
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
5.983
316238AB2-078_GEN
Solar/Wind Harmer
0.272
316239AB2-077_GEN
Solar/Wind Harmer
0.272
270455AD2-022 GEN
Solar/Wind Harmer
1.349
270457AD2-023 GEN
Solar/Wind Harmer
0.684
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.182
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:713.33
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
6.347
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970301AG2-198 GEN
Solar/Wind Harmer
33.427
970099AG2-077 GEN
Solar/Wind Harmer
47.791
315687AD1-152 GEN
Solar/Wind Harmer
3.506
316248AF1-058 C
Solar/Wind Harmer
0.555
316118AC1-105 GEN
Solar/Wind Harmer
1.123
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.489
942751AE2-291 GEN
Solar/Wind Harmer
7.024
316237AB2-079_GEN
Solar/Wind Harmer
0.272
313527AB2-043 GEN
Solar/Wind Harmer
1.352
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.242
3151541CLOVER2
50/50
6.689
3151601KERR 3
50/50
0.297
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
3151631KERR 6
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.891
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
5.983
316238AB2-078_GEN
Solar/Wind Harmer
0.272
316239AB2-077_GEN
Solar/Wind Harmer
0.272
270455AD2-022 GEN
Solar/Wind Harmer
1.349
270457AD2-023 GEN
Solar/Wind Harmer
0.684
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.182
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.357
316478AD1-087 GEN
Solar/Wind Harmer
3.041
316003AC1-222 GEN
Solar/Wind Harmer
1.672
971683AH1-343 GEN
Solar/Wind Harmer
6.767
316123AC1-075 GEN
Solar/Wind Harmer
1.347
316222AC1-221 GEN
Solar/Wind Harmer
1.22
316283AC2-100 C
Solar/Wind Harmer
1.112
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.543
3147133PAMPLIN
Solar/Wind Helper
1.064
315821AE2-092 GEN
Solar/Wind Helper
1.922
270494AE1-108_GEN
Solar/Wind Helper
2.774
3151531CLOVER1
50/50
6.741
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
315693AD1-088 GEN
Solar/Wind Harmer
21.358
957481AF2-042 GEN
Solar/Wind Harmer
119.479
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.676
316129AC1-054 GEN
Solar/Wind Harmer
1.114
316131AB2-060 GEN
Solar/Wind Harmer
0.8
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.83 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:863.6
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
970937AG2-583 GEN
Solar/Wind Harmer
28.694
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.43 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:860.42
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
971967AH1-528 GEN
Solar/Wind Harmer
17.83
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970933AG2-581 GEN
Solar/Wind Harmer
8.916
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
970937AG2-583 GEN
Solar/Wind Harmer
28.694
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.53 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1048.43
MW Contribution:
0.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.26
3151861LOWMORA
50/50
0.943
315760AF1-028 GEN
50/50
12.702
3152061BATH 6F
50/50
1.638
3152021BATH 2B
50/50
1.633
3144293JTRSVLE
50/50
0.158
3152191CUNINGD
50/50
1.058
972255AH1-712 GEN
50/50
32.029
972003AH1-546 GEN
Solar/Wind Harmer
4.596
970221AG2-151 GEN
Solar/Wind Harmer
7.054
315821AE2-092 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Harmer
0.123
270494AE1-108_GEN
Solar/Wind Harmer
1.333
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.052
942461AE2-259 GEN
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
6.157
3151881LOWMORC
50/50
0.936
3151881LOWMORC
50/50
0.921
3151861LOWMORA
50/50
0.906
3152031BATH 3C
50/50
1.635
3152051BATH 5E
50/50
1.635
3137383CUSHAW
50/50
0.018
970909AG2-566 GEN
50/50
0.694
3144293JTRSVLE
50/50
0.158
3152181CUNINGC
50/50
0.486
3152171CUNINGB
50/50
0.458
3152161CUNINGA
50/50
0.455
972193AH1-681 GEN
50/50
1.431
3146776BUCKING
Solar/Wind Harmer
0.434
3146776BUCKING
Solar/Wind Harmer
0.035
316336AC2-165 C
Solar/Wind Harmer
3.993
316313AB2-026
Solar/Wind Harmer
0.042
3147133PAMPLIN
Solar/Wind Harmer
0.066
3147133PAMPLIN
Solar/Wind Harmer
0.053
970301AG2-198 GEN
Solar/Wind Harmer
2.775
958211AF2-115 GEN
Solar/Wind Harmer
0.748
966001AG1-469 GEN
Solar/Wind Helper
0.74
316006AB2-029 C
Solar/Wind Helper
0.089
3143336POWHATN
Solar/Wind Harmer
1.009
958131AF2-107 GEN
Solar/Wind Harmer
1.905
3147133PAMPLIN
Solar/Wind Harmer
0.206
3132273ORANGE
Solar/Wind Helper
0.106
3147666LOUISA
Solar/Wind Helper
1.085
3152011BATH 1A
50/50
1.633
3152041BATH 4D
50/50
1.632
23503501NHY_Z2-039
50/50
0.004
23503401SHY_Z2-039
50/50
0.002
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
971845AH1-439 GEN
Solar/Wind Harmer
4.836
3148463FAIRFLD
Solar/Wind Harmer
0.083
316258AE1-075 C
Solar/Wind Harmer
0.05
946301AF1-294 GEN
Solar/Wind Harmer
1.229
961791AG1-021 GEN
Solar/Wind Harmer
0.598
970683AG2-441 GEN
Solar/Wind Harmer
3.461
970681AG2-440 GEN
Solar/Wind Harmer
2.297
315651AD1-115 GEN
Solar/Wind Helper
0.973
316164AC1-076 GEN
Solar/Wind Helper
1.197
3151931BEARGRDN S1
50/50
1.628
3151911BEARGRDN G1
50/50
1.26
3144293JTRSVLE
50/50
0.158
3144293JTRSVLE
50/50
0.125
972277AH1-723 GEN
50/50
37.324
971377AH1-170 GEN
Solar/Wind Harmer
1.411
3147623JAMES R
Solar/Wind Harmer
0.307
970937AG2-583 GEN
Solar/Wind Harmer
6.726
3146776BUCKING
Solar/Wind Harmer
0.043
3146926FARMVIL
Solar/Wind Harmer
0.052
3147983MERCK5
Solar/Wind Harmer
0.033
3143336POWHATN
Solar/Wind Harmer
1.187
971563AH1-280 GEN
Solar/Wind Harmer
0.665
970685AG2-442 GEN
Solar/Wind Harmer
4.455
316192AB2-158 GEN
Solar/Wind Helper
3.275
3147666LOUISA
Solar/Wind Helper
1.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.536
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.509
MECLTFEXP_MEC->PJM
CLTF
2.016
SIGELTFEXP_SIGE->PJM
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
1.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.062
LAGNLTFEXP_LAGN->PJM
CLTF
2.956
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.464
TVALTFEXP_TVA->PJM
CLTF
1.521
NYPJM->LTFIMP_NY
CLTF
0.852
LGEELTFEXP_LGEE->PJM
CLTF
0.84
WECLTFEXP_WEC->PJM
CLTF
0.429

Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 550_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.27 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1036.09
MW Contribution:
0.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3137383CUSHAW
50/50
0.023
970909AG2-566 GEN
50/50
0.722
3144293JTRSVLE
50/50
0.164
3152181CUNINGC
50/50
0.531
3152171CUNINGB
50/50
0.5
3152161CUNINGA
50/50
0.497
972193AH1-681 GEN
50/50
1.563
3146776BUCKING
Solar/Wind Harmer
0.461
3146776BUCKING
Solar/Wind Harmer
0.037
316336AC2-165 C
Solar/Wind Harmer
4.161
3132123MT JACKSON
Solar/Wind Harmer
0.226
970117AG2-086 GEN
Solar/Wind Harmer
1.736
970117AG2-086 GEN
Solar/Wind Harmer
1.158
316313AB2-026
Solar/Wind Harmer
0.043
3147133PAMPLIN
Solar/Wind Harmer
0.068
3147133PAMPLIN
Solar/Wind Harmer
0.055
970301AG2-198 GEN
Solar/Wind Harmer
2.887
958211AF2-115 GEN
Solar/Wind Harmer
0.777
3151931BEARGRDN S1
50/50
1.742
3151911BEARGRDN G1
50/50
1.348
3144293JTRSVLE
50/50
0.164
3144293JTRSVLE
50/50
0.13
972277AH1-723 GEN
50/50
40.756
3151921BEARGRDN G2
50/50
1.348
3151861LOWMORA
50/50
1.232
3152061BATH 6F
50/50
2.37
3152021BATH 2B
50/50
2.364
315760AF1-028 GEN
50/50
16.854
3144293JTRSVLE
50/50
0.164
3152191CUNINGD
50/50
1.156
972255AH1-712 GEN
50/50
34.975
3148013FISHERV
Solar/Wind Harmer
0.147
315821AE2-092 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
7.624
972003AH1-546 GEN
Solar/Wind Harmer
4.916
270494AE1-108_GEN
Solar/Wind Harmer
1.457
3146776BUCKING
Solar/Wind Harmer
0.042
3146926FARMVIL
Solar/Wind Harmer
0.055
942461AE2-259 GEN
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
2.187
3143336POWHATN
Solar/Wind Harmer
1.04
3147133PAMPLIN
Solar/Wind Harmer
0.215
966001AG1-469 GEN
Solar/Wind Helper
0.71
316006AB2-029 C
Solar/Wind Helper
0.081
972205AH1-687 GEN
50/50
6.589
3151881LOWMORC
50/50
1.223
3151881LOWMORC
50/50
1.203
3151861LOWMORA
50/50
1.184
3152031BATH 3C
50/50
2.367
3152051BATH 5E
50/50
2.366
3152011BATH 1A
50/50
2.364
3152041BATH 4D
50/50
2.363
23503501NHY_Z2-039
50/50
0.005
23503401SHY_Z2-039
50/50
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.088
3148013FISHERV
Solar/Wind Harmer
0.084
971845AH1-439 GEN
Solar/Wind Harmer
5.139
3148463FAIRFLD
Solar/Wind Harmer
0.108
316258AE1-075 C
Solar/Wind Harmer
0.051
946301AF1-294 GEN
Solar/Wind Harmer
1.278
961791AG1-021 GEN
Solar/Wind Harmer
0.622
970683AG2-441 GEN
Solar/Wind Harmer
3.582
970681AG2-440 GEN
Solar/Wind Harmer
2.378
3132273ORANGE
Solar/Wind Helper
0.101
3147666LOUISA
Solar/Wind Helper
1.02
315651AD1-115 GEN
Solar/Wind Helper
0.898
316164AC1-076 GEN
Solar/Wind Helper
1.077
971377AH1-170 GEN
Solar/Wind Harmer
1.525
3147623JAMES R
Solar/Wind Harmer
0.331
970937AG2-583 GEN
Solar/Wind Harmer
7.136
3146776BUCKING
Solar/Wind Harmer
0.046
3147983MERCK5
Solar/Wind Harmer
0.042
3146926FARMVIL
Solar/Wind Harmer
0.055
3143336POWHATN
Solar/Wind Harmer
1.223
971563AH1-280 GEN
Solar/Wind Harmer
0.691
970685AG2-442 GEN
Solar/Wind Harmer
4.622
962751AG1-124 GEN
Solar/Wind Harmer
2.727
316192AB2-158 GEN
Solar/Wind Helper
3.084
3147666LOUISA
Solar/Wind Helper
1.774
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.864
MECLTFEXP_MEC->PJM
CLTF
2.058
SIGELTFEXP_SIGE->PJM
CLTF
0.066
CPLELTFEXP_CPLE->PJM
CLTF
2.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.881
LAGNLTFEXP_LAGN->PJM
CLTF
3.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.798
TVALTFEXP_TVA->PJM
CLTF
1.628
NYPJM->LTFIMP_NY
CLTF
0.866
LGEELTFEXP_LGEE->PJM
CLTF
0.866
WECLTFEXP_WEC->PJM
CLTF
0.431

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.33 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1162.8
MW Contribution:
2.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.671
316303AF2-085
50/50
2.056
3151541CLOVER2
50/50
2.335
3151601KERR 3
50/50
0.217
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.529
970413AG2-270 GEN
50/50
10.247
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.096
3150861SPRUNCD
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
972003AH1-546 GEN
Solar/Wind Harmer
15.439
970221AG2-151 GEN
Solar/Wind Harmer
21.636
3146776BUCKING
Solar/Wind Harmer
0.132
970909AG2-566 GEN
50/50
2.396
3144293JTRSVLE
50/50
0.529
970535AG2-341 GEN
50/50
2.11
3151581KERR 1
50/50
0.078
3152661PLYWOOD A
50/50
0.215
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.318
315241AE2-183_GT1
50/50
1.314
972185AH1-677 GEN
50/50
4.763
3151261ROARAP2
50/50
0.093
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
316336AC2-165 C
Solar/Wind Harmer
14.549
316313AB2-026
Solar/Wind Harmer
0.157
970301AG2-198 GEN
Solar/Wind Harmer
9.584
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.177
958211AF2-115 GEN
Solar/Wind Harmer
2.507
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.398
970099AG2-077 GEN
Solar/Wind Harmer
11.72
964791AG1-342 GEN
Solar/Wind Harmer
2.09
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.466
313506AB2-031 GEN
Solar/Wind Harmer
0.246
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316365GEN2_N
Solar/Wind Harmer
0.163
3144356SAPONY
Solar/Wind Harmer
0.607
316315AB2-025 C
Solar/Wind Harmer
0.058
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
316140AB2-099
Solar/Wind Harmer
0.024
315742AE1-103 GEN
Solar/Wind Harmer
1.005
315724AD1-057 GEN
Solar/Wind Harmer
1.284
316065AD1-022 GEN
Solar/Wind Harmer
3.005
315614AA2-178 GEN
Solar/Wind Harmer
0.368
316349AD2-085 GEN
Solar/Wind Harmer
0.043
316049AB1-081 GEN
Solar/Wind Harmer
0.366
316263AC1-034 GEN
Solar/Wind Harmer
2.446
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.254
3146456SLIGO L269
Solar/Wind Harmer
1.121
3137176SLIGO L2192
Solar/Wind Harmer
0.252
316339AD2-160 GEN
Solar/Wind Harmer
0.101
316388AE2-253 GEN
Solar/Wind Harmer
0.197
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316005AA1-067
Solar/Wind Harmer
0.067
942751AE2-291 GEN
Solar/Wind Harmer
3.431
3150991CHESPKB
Adder
0.659
270494AE1-108_GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.801
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.693
959311AF2-222 GEN
Solar/Wind Harmer
15.886
970257AG2-171 GEN
Solar/Wind Harmer
5.551
971775AH1-396 GEN
Solar/Wind Harmer
0.278
964241AG1-285 GEN
Solar/Wind Harmer
9.805
958131AF2-107 GEN
Solar/Wind Harmer
3.652
316478AD1-087 GEN
Solar/Wind Harmer
0.38
3147043LAWRENC
Solar/Wind Harmer
0.059
971683AH1-343 GEN
Solar/Wind Harmer
2.983
316181AB2-040 GEN
Solar/Wind Harmer
0.114
944011AF1-069 GEN
Solar/Wind Harmer
4.753
970917AG2-570 GEN
Solar/Wind Harmer
6.903
3156081AA2-088 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
1.284
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.358
3146173TUNIS
Solar/Wind Harmer
0.069
316123AC1-075 GEN
Solar/Wind Harmer
0.092
3145823KELFORD
Solar/Wind Harmer
0.069
315722AD1-056 GEN
Solar/Wind Harmer
2.302
3145273HOLLAND
Solar/Wind Harmer
0.05
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
316222AC1-221 GEN
Solar/Wind Harmer
0.27
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.483
316283AC2-100 C
Solar/Wind Harmer
0.127
970657AG2-426 GEN
Solar/Wind Harmer
1.458
315735AD1-075 GEN1
Solar/Wind Harmer
0.185
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3151611KERR 4
50/50
0.217
3151621KERR 5
50/50
0.217
3151631KERR 6
50/50
0.217
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.288
3151281ROARAP4
50/50
0.087
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971845AH1-439 GEN
Solar/Wind Harmer
16.331
316258AE1-075 C
Solar/Wind Harmer
0.188
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
11.554
970681AG2-440 GEN
Solar/Wind Harmer
7.669
3144303KENBRDG
Solar/Wind Harmer
0.139
316486AD2-202 GEN
Solar/Wind Harmer
0.111
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.021
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.947
970673AG2-436 GEN
Solar/Wind Harmer
9.878
970533AG2-339 GEN
Solar/Wind Harmer
5.968
3137643SOCKMAN
Solar/Wind Harmer
0.315
970085AG2-068 GEN
Solar/Wind Harmer
4.091
970581AG2-369 GEN
Solar/Wind Harmer
3.519
316426AA2-053 GEN
Solar/Wind Harmer
0.254
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.748
315652AC1-086 GEN
Solar/Wind Harmer
7.784
316274AC1-208 GEN
Solar/Wind Harmer
0.364
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
316210AC1-098 GEN
Solar/Wind Harmer
0.642
3146033SCOT NK
Solar/Wind Harmer
0.276
316463AE2-346 GEN
Solar/Wind Harmer
0.059
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3151931BEARGRDN S1
50/50
5.466
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.529
3144293JTRSVLE
50/50
0.418
970119AG2-088 GEN
50/50
15.416
3151531CLOVER1
50/50
2.353
3151591KERR 2
50/50
0.217
3151641KERR 7
50/50
0.217
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.199
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.318
3151281ROARAP4
50/50
0.093
3150851SPRUNCC
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.218
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
3143336POWHATN
Solar/Wind Harmer
4.472
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.905
316034AC1-036 C
Solar/Wind Harmer
0.012
315785AD2-033 C
Solar/Wind Harmer
1.344
316131AB2-060 GEN
Solar/Wind Harmer
0.421
315693AD1-088 GEN
Solar/Wind Harmer
6.345
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.3
970401AG2-262 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
4.185
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.36
960081AF2-299 GEN
Solar/Wind Harmer
0.793
941031AE2-094 GEN
Solar/Wind Harmer
14.548
970919AG2-571 GEN
Solar/Wind Harmer
2.761
970087AG2-069 GEN
Solar/Wind Harmer
6.137
3145783HORNRTN
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.151
940641AE2-051 GEN
Solar/Wind Harmer
5.985
316023GEN1_S
Solar/Wind Harmer
0.163
939411AE1-173 GEN
Solar/Wind Harmer
30.688
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.298
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.397
316381AD1-082 GEN
Solar/Wind Harmer
0.066
315737AD1-076 GEN
Solar/Wind Harmer
0.833
315816AE2-034 GEN
Solar/Wind Harmer
0.276
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.168
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.229
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.215
319010AE1-072 C
Solar/Wind Harmer
0.316
3146456SLIGO L269
Solar/Wind Harmer
0.063
944591AF1-124 GEN
Solar/Wind Harmer
14.293
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
0
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150981CHESPKA
Adder
0.786
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.549
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.011
316246AF1-032 C
Solar/Wind Harmer
0.028
3145933PARMELE
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.733
316017AA1-139 ULT1
Solar/Wind Harmer
0.034
944581AF1-123 GEN
Solar/Wind Harmer
14.243
944601AF1-125 GEN
Solar/Wind Harmer
14.023
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.848
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316327AA2-057 GEN
Solar/Wind Harmer
0.1
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
970657AG2-426 GEN
Solar/Wind Harmer
0.477
315732AD1-074 GEN1
Solar/Wind Harmer
0.37
315733AD1-074 GEN2
Solar/Wind Harmer
0.37
3130546PLYMOUTH
Solar/Wind Harmer
0.065
316311AC2-079 GEN
Solar/Wind Harmer
1.854
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
313526AB2-022
Solar/Wind Harmer
0.034
957861AF2-080 GEN
Solar/Wind Harmer
2.738
3146406KITTY HAWK
Solar/Wind Harmer
0.008
957871AF2-081 GEN
Solar/Wind Harmer
3.154
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
316316AC1-027 C
Solar/Wind Harmer
0.06
3151081ELIZAR1
Adder
5.774
3151091ELIZAR2
Adder
5.674
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.025
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.82
316458AB2-190 GEN2
Solar/Wind Harmer
0.321
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.128
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.763
316294AC1-161 GEN
Solar/Wind Harmer
1.072
316033AB2-134 GEN
Solar/Wind Harmer
0
966001AG1-469 GEN
Solar/Wind Helper
0.206
971445AH1-216 GEN
Solar/Wind Harmer
4.323
3151201GRAVEL4
Adder
4.409
3151221GRAVEL6
Adder
4.404
3151191GRAVEL3
Adder
4.353
3151211GRAVEL5
Adder
4.353
315697AD1-025 GEN
Solar/Wind Harmer
0.065
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.524
316072AD1-144
Solar/Wind Harmer
0.022
315773AC2-141 GEN
Solar/Wind Harmer
2.266
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.171
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316132AB2-190 GEN1
Solar/Wind Harmer
0.321
944631AF1-128 GEN
Adder
26.814
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.905
3147666LOUISA
Solar/Wind Helper
0.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.137
MECLTFEXP_MEC->PJM
CLTF
0.549
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.728
LAGNLTFEXP_LAGN->PJM
CLTF
1.975
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.463
TVALTFEXP_TVA->PJM
CLTF
0.975
NYPJM->LTFIMP_NY
CLTF
0.615
LGEELTFEXP_LGEE->PJM
CLTF
0.138
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.37 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1389.21
MW Contribution:
2.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.293
970221AG2-151 GEN
Solar/Wind Harmer
28.434
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.114
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.731
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.52
972205AH1-687 GEN
50/50
20.635
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.467
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.402
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.595
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.538
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.927
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.892
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.504
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
970133AG2-095 GEN
Solar/Wind Harmer
0.026
316192AB2-158 GEN
Solar/Wind Helper
1.015
3147666LOUISA
Solar/Wind Helper
0.588
3147983MERCK5
Solar/Wind Helper
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.649
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.37 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1389.18
MW Contribution:
2.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.292
970221AG2-151 GEN
Solar/Wind Harmer
28.433
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.926
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.891
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.113
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.73
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
972205AH1-687 GEN
50/50
20.634
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.466
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.401
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.519
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.594
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.537
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
316192AB2-158 GEN
Solar/Wind Helper
1.016
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.648
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.8 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1326.36
MW Contribution:
2.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.8 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1326.36
MW Contribution:
2.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.81 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1060.79
MW Contribution:
2.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.579
3144293JTRSVLE
50/50
0.618
972003AH1-546 GEN
Solar/Wind Harmer
26.738
970221AG2-151 GEN
Solar/Wind Harmer
37.543
3146776BUCKING
Solar/Wind Harmer
-0.019
270494AE1-108_GEN
Solar/Wind Harmer
12.249
3146926FARMVIL
Solar/Wind Harmer
-0.024
315821AE2-092 GEN
Solar/Wind Harmer
7.754
942461AE2-259 GEN
Solar/Wind Harmer
5.223
970909AG2-566 GEN
50/50
2.805
3144293JTRSVLE
50/50
0.618
970535AG2-341 GEN
50/50
2.051
316336AC2-165 C
Solar/Wind Harmer
42.179
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
970301AG2-198 GEN
Solar/Wind Harmer
14.775
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.28
970323AG2-213 GEN
Solar/Wind Harmer
10.867
313527AB2-043 GEN
Solar/Wind Harmer
2.468
316237AB2-079_GEN
Solar/Wind Harmer
0.445
962561AG1-105 GEN
Solar/Wind Harmer
6.959
964791AG1-342 GEN
Solar/Wind Harmer
2.534
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.73
970099AG2-077 GEN
Solar/Wind Harmer
13.191
315687AD1-152 GEN
Solar/Wind Harmer
1.188
316248AF1-058 C
Solar/Wind Harmer
0.284
970933AG2-581 GEN
Solar/Wind Harmer
6.805
942751AE2-291 GEN
Solar/Wind Harmer
4.456
966001AG1-469 GEN
Solar/Wind Helper
0.159
3151931BEARGRDN S1
50/50
7.207
3151911BEARGRDN G1
50/50
5.579
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.488
970937AG2-583 GEN
Solar/Wind Harmer
48.556
971377AH1-170 GEN
Solar/Wind Harmer
7.509
3147623JAMES R
Solar/Wind Harmer
0.929
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
971563AH1-280 GEN
Solar/Wind Harmer
3.424
970685AG2-442 GEN
Solar/Wind Harmer
22.673
316034AC1-036 C
Solar/Wind Harmer
0.403
315785AD2-033 C
Solar/Wind Harmer
4.657
316131AB2-060 GEN
Solar/Wind Harmer
1.684
315693AD1-088 GEN
Solar/Wind Harmer
7.148
970401AG2-262 GEN
Solar/Wind Harmer
0.774
957481AF2-042 GEN
Solar/Wind Harmer
32.976
971065AG2-659 GEN
Solar/Wind Harmer
4.765
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.734
962751AG1-124 GEN
Solar/Wind Harmer
4.607
960081AF2-299 GEN
Solar/Wind Harmer
0.726
3147133PAMPLIN
Solar/Wind Harmer
-0.092
959311AF2-222 GEN
Solar/Wind Harmer
23.56
970257AG2-171 GEN
Solar/Wind Harmer
8.15
971775AH1-396 GEN
Solar/Wind Harmer
1.533
958131AF2-107 GEN
Solar/Wind Harmer
6.444
964241AG1-285 GEN
Solar/Wind Harmer
13.685
316478AD1-087 GEN
Solar/Wind Harmer
0.939
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971683AH1-343 GEN
Solar/Wind Harmer
3.682
316123AC1-075 GEN
Solar/Wind Harmer
0.805
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
27.258
316322AB2-045
Solar/Wind Harmer
1.775
971845AH1-439 GEN
Solar/Wind Harmer
27.551
946301AF1-294 GEN
Solar/Wind Harmer
7.02
961791AG1-021 GEN
Solar/Wind Harmer
3.424
970683AG2-441 GEN
Solar/Wind Harmer
17.408
970681AG2-440 GEN
Solar/Wind Harmer
11.554
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.445
316239AB2-077_GEN
Solar/Wind Harmer
0.445
316486AD2-202 GEN
Solar/Wind Harmer
0.275
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.429
946281AF1-292 GEN
Solar/Wind Harmer
0.145
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.289
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.592
MECLTFEXP_MEC->PJM
CLTF
0.532
SIGELTFEXP_SIGE->PJM
CLTF
0.015
CPLELTFEXP_CPLE->PJM
CLTF
2.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.391
LAGNLTFEXP_LAGN->PJM
CLTF
1.582
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.17
TVALTFEXP_TVA->PJM
CLTF
0.79
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.163
WECLTFEXP_WEC->PJM
CLTF
0.076

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:173.1 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1145.53
MW Contribution:
2.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.396
3144293JTRSVLE
50/50
0.529
970535AG2-341 GEN
50/50
2.11
3151581KERR 1
50/50
0.078
3152661PLYWOOD A
50/50
0.215
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.318
315241AE2-183_GT1
50/50
1.314
972185AH1-677 GEN
50/50
4.763
3151261ROARAP2
50/50
0.093
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
316336AC2-165 C
Solar/Wind Harmer
14.549
316313AB2-026
Solar/Wind Harmer
0.157
3151931BEARGRDN S1
50/50
5.466
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.529
3144293JTRSVLE
50/50
0.418
970119AG2-088 GEN
50/50
15.416
3151531CLOVER1
50/50
2.353
3151591KERR 2
50/50
0.217
970301AG2-198 GEN
Solar/Wind Harmer
9.584
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.177
958211AF2-115 GEN
Solar/Wind Harmer
2.507
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.398
970099AG2-077 GEN
Solar/Wind Harmer
11.72
964791AG1-342 GEN
Solar/Wind Harmer
2.09
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.466
313506AB2-031 GEN
Solar/Wind Harmer
0.246
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316365GEN2_N
Solar/Wind Harmer
0.163
3144356SAPONY
Solar/Wind Harmer
0.607
316315AB2-025 C
Solar/Wind Harmer
0.058
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
316140AB2-099
Solar/Wind Harmer
0.024
315742AE1-103 GEN
Solar/Wind Harmer
1.005
315724AD1-057 GEN
Solar/Wind Harmer
1.284
316065AD1-022 GEN
Solar/Wind Harmer
3.005
315614AA2-178 GEN
Solar/Wind Harmer
0.368
316349AD2-085 GEN
Solar/Wind Harmer
0.043
316049AB1-081 GEN
Solar/Wind Harmer
0.366
316263AC1-034 GEN
Solar/Wind Harmer
2.446
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.254
3146456SLIGO L269
Solar/Wind Harmer
1.121
3137176SLIGO L2192
Solar/Wind Harmer
0.252
316339AD2-160 GEN
Solar/Wind Harmer
0.101
316388AE2-253 GEN
Solar/Wind Harmer
0.197
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316005AA1-067
Solar/Wind Harmer
0.067
942751AE2-291 GEN
Solar/Wind Harmer
3.431
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.763
316294AC1-161 GEN
Solar/Wind Harmer
1.072
972205AH1-687 GEN
50/50
20.671
316303AF2-085
50/50
2.056
3151541CLOVER2
50/50
2.335
3151601KERR 3
50/50
0.217
3151611KERR 4
50/50
0.217
3151621KERR 5
50/50
0.217
3151631KERR 6
50/50
0.217
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.288
3151281ROARAP4
50/50
0.087
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971845AH1-439 GEN
Solar/Wind Harmer
16.331
316258AE1-075 C
Solar/Wind Harmer
0.188
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
11.554
970681AG2-440 GEN
Solar/Wind Harmer
7.669
3144303KENBRDG
Solar/Wind Harmer
0.139
316486AD2-202 GEN
Solar/Wind Harmer
0.111
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.021
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.947
970673AG2-436 GEN
Solar/Wind Harmer
9.878
970533AG2-339 GEN
Solar/Wind Harmer
5.968
3137643SOCKMAN
Solar/Wind Harmer
0.315
970085AG2-068 GEN
Solar/Wind Harmer
4.091
970581AG2-369 GEN
Solar/Wind Harmer
3.519
316426AA2-053 GEN
Solar/Wind Harmer
0.254
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.748
315652AC1-086 GEN
Solar/Wind Harmer
7.784
316274AC1-208 GEN
Solar/Wind Harmer
0.364
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
316210AC1-098 GEN
Solar/Wind Harmer
0.642
3146033SCOT NK
Solar/Wind Harmer
0.276
316463AE2-346 GEN
Solar/Wind Harmer
0.059
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.529
970413AG2-270 GEN
50/50
10.247
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.096
3150861SPRUNCD
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
972003AH1-546 GEN
Solar/Wind Harmer
15.439
970221AG2-151 GEN
Solar/Wind Harmer
21.636
3146776BUCKING
Solar/Wind Harmer
0.132
270494AE1-108_GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.801
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.693
959311AF2-222 GEN
Solar/Wind Harmer
15.886
970257AG2-171 GEN
Solar/Wind Harmer
5.551
971775AH1-396 GEN
Solar/Wind Harmer
0.278
964241AG1-285 GEN
Solar/Wind Harmer
9.805
958131AF2-107 GEN
Solar/Wind Harmer
3.652
316478AD1-087 GEN
Solar/Wind Harmer
0.38
3147043LAWRENC
Solar/Wind Harmer
0.059
971683AH1-343 GEN
Solar/Wind Harmer
2.983
316181AB2-040 GEN
Solar/Wind Harmer
0.114
944011AF1-069 GEN
Solar/Wind Harmer
4.753
970917AG2-570 GEN
Solar/Wind Harmer
6.903
3156081AA2-088 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
1.284
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.358
3146173TUNIS
Solar/Wind Harmer
0.069
316123AC1-075 GEN
Solar/Wind Harmer
0.092
3145823KELFORD
Solar/Wind Harmer
0.069
315722AD1-056 GEN
Solar/Wind Harmer
2.302
3145273HOLLAND
Solar/Wind Harmer
0.05
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
316222AC1-221 GEN
Solar/Wind Harmer
0.27
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.483
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316327AA2-057 GEN
Solar/Wind Harmer
0.1
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
970657AG2-426 GEN
Solar/Wind Harmer
0.477
315732AD1-074 GEN1
Solar/Wind Harmer
0.37
315733AD1-074 GEN2
Solar/Wind Harmer
0.37
3130546PLYMOUTH
Solar/Wind Harmer
0.065
316311AC2-079 GEN
Solar/Wind Harmer
1.854
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
313526AB2-022
Solar/Wind Harmer
0.034
957861AF2-080 GEN
Solar/Wind Harmer
2.738
3146406KITTY HAWK
Solar/Wind Harmer
0.008
957871AF2-081 GEN
Solar/Wind Harmer
3.154
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
316316AC1-027 C
Solar/Wind Harmer
0.06
3151081ELIZAR1
Adder
5.774
3151091ELIZAR2
Adder
5.674
971445AH1-216 GEN
Solar/Wind Harmer
4.323
3151201GRAVEL4
Adder
4.409
3151221GRAVEL6
Adder
4.404
3151191GRAVEL3
Adder
4.353
3151211GRAVEL5
Adder
4.353
315697AD1-025 GEN
Solar/Wind Harmer
0.065
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.524
3151641KERR 7
50/50
0.217
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.199
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.318
3151281ROARAP4
50/50
0.093
3150851SPRUNCC
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.218
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
3143336POWHATN
Solar/Wind Harmer
4.472
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.905
316034AC1-036 C
Solar/Wind Harmer
0.012
315785AD2-033 C
Solar/Wind Harmer
1.344
316131AB2-060 GEN
Solar/Wind Harmer
0.421
315693AD1-088 GEN
Solar/Wind Harmer
6.345
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.3
970401AG2-262 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
4.185
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.36
960081AF2-299 GEN
Solar/Wind Harmer
0.793
941031AE2-094 GEN
Solar/Wind Harmer
14.548
970919AG2-571 GEN
Solar/Wind Harmer
2.761
970087AG2-069 GEN
Solar/Wind Harmer
6.137
3145783HORNRTN
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.151
940641AE2-051 GEN
Solar/Wind Harmer
5.985
316023GEN1_S
Solar/Wind Harmer
0.163
939411AE1-173 GEN
Solar/Wind Harmer
30.688
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.298
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.397
316381AD1-082 GEN
Solar/Wind Harmer
0.066
315737AD1-076 GEN
Solar/Wind Harmer
0.833
315816AE2-034 GEN
Solar/Wind Harmer
0.276
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.168
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.229
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.215
319010AE1-072 C
Solar/Wind Harmer
0.316
3146456SLIGO L269
Solar/Wind Harmer
0.063
944591AF1-124 GEN
Solar/Wind Harmer
14.293
3145746EVERETS
Solar/Wind Harmer
0.063
316283AC2-100 C
Solar/Wind Harmer
0.127
970657AG2-426 GEN
Solar/Wind Harmer
1.458
315735AD1-075 GEN1
Solar/Wind Harmer
0.185
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.549
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.011
316246AF1-032 C
Solar/Wind Harmer
0.028
3145933PARMELE
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.733
316017AA1-139 ULT1
Solar/Wind Harmer
0.034
944581AF1-123 GEN
Solar/Wind Harmer
14.243
944601AF1-125 GEN
Solar/Wind Harmer
14.023
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.848
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.025
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.82
316458AB2-190 GEN2
Solar/Wind Harmer
0.321
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.128
316033AB2-134 GEN
Solar/Wind Harmer
0
966001AG1-469 GEN
Solar/Wind Helper
0.206
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
0
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.022
315773AC2-141 GEN
Solar/Wind Harmer
2.266
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.171
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316132AB2-190 GEN1
Solar/Wind Harmer
0.321
944631AF1-128 GEN
Adder
26.814
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.905
3147666LOUISA
Solar/Wind Helper
0.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.137
MECLTFEXP_MEC->PJM
CLTF
0.549
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.728
LAGNLTFEXP_LAGN->PJM
CLTF
1.975
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.463
TVALTFEXP_TVA->PJM
CLTF
0.975
NYPJM->LTFIMP_NY
CLTF
0.615
LGEELTFEXP_LGEE->PJM
CLTF
0.138
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.58 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1371.94
MW Contribution:
2.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.293
970221AG2-151 GEN
Solar/Wind Harmer
28.434
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.927
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.892
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.114
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.731
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
972205AH1-687 GEN
50/50
20.635
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.467
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.402
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.504
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.52
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.595
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.538
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
316192AB2-158 GEN
Solar/Wind Helper
1.015
3147666LOUISA
Solar/Wind Helper
0.588
3147983MERCK5
Solar/Wind Helper
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.649
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.58 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1371.91
MW Contribution:
2.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.292
970221AG2-151 GEN
Solar/Wind Harmer
28.433
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.926
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.891
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
972205AH1-687 GEN
50/50
20.634
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.466
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.401
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.113
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.73
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.519
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.594
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.537
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
316192AB2-158 GEN
Solar/Wind Helper
1.016
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.648
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.82 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1309.09
MW Contribution:
2.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.82 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1309.09
MW Contribution:
2.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:169.7 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1122.99
MW Contribution:
2.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.396
3144293JTRSVLE
50/50
0.529
970535AG2-341 GEN
50/50
2.11
3151581KERR 1
50/50
0.078
3152661PLYWOOD A
50/50
0.215
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.318
315241AE2-183_GT1
50/50
1.314
972185AH1-677 GEN
50/50
4.763
3151261ROARAP2
50/50
0.093
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
316336AC2-165 C
Solar/Wind Harmer
14.549
316313AB2-026
Solar/Wind Harmer
0.157
970301AG2-198 GEN
Solar/Wind Harmer
9.584
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.177
958211AF2-115 GEN
Solar/Wind Harmer
2.507
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.398
970099AG2-077 GEN
Solar/Wind Harmer
11.72
964791AG1-342 GEN
Solar/Wind Harmer
2.09
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.466
313506AB2-031 GEN
Solar/Wind Harmer
0.246
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316365GEN2_N
Solar/Wind Harmer
0.163
3144356SAPONY
Solar/Wind Harmer
0.607
316315AB2-025 C
Solar/Wind Harmer
0.058
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
316140AB2-099
Solar/Wind Harmer
0.024
315742AE1-103 GEN
Solar/Wind Harmer
1.005
315724AD1-057 GEN
Solar/Wind Harmer
1.284
316065AD1-022 GEN
Solar/Wind Harmer
3.005
315614AA2-178 GEN
Solar/Wind Harmer
0.368
316349AD2-085 GEN
Solar/Wind Harmer
0.043
316049AB1-081 GEN
Solar/Wind Harmer
0.366
316263AC1-034 GEN
Solar/Wind Harmer
2.446
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3151931BEARGRDN S1
50/50
5.466
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.529
3144293JTRSVLE
50/50
0.418
970119AG2-088 GEN
50/50
15.416
3151531CLOVER1
50/50
2.353
3151591KERR 2
50/50
0.217
3151641KERR 7
50/50
0.217
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.199
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.318
3151281ROARAP4
50/50
0.093
3150851SPRUNCC
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.218
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
3143336POWHATN
Solar/Wind Harmer
4.472
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.905
316034AC1-036 C
Solar/Wind Harmer
0.012
315785AD2-033 C
Solar/Wind Harmer
1.344
316131AB2-060 GEN
Solar/Wind Harmer
0.421
315693AD1-088 GEN
Solar/Wind Harmer
6.345
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.3
970401AG2-262 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
4.185
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.36
960081AF2-299 GEN
Solar/Wind Harmer
0.793
941031AE2-094 GEN
Solar/Wind Harmer
14.548
970919AG2-571 GEN
Solar/Wind Harmer
2.761
970087AG2-069 GEN
Solar/Wind Harmer
6.137
3145783HORNRTN
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.151
940641AE2-051 GEN
Solar/Wind Harmer
5.985
316023GEN1_S
Solar/Wind Harmer
0.163
939411AE1-173 GEN
Solar/Wind Harmer
30.688
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.298
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.397
316381AD1-082 GEN
Solar/Wind Harmer
0.066
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.254
3146456SLIGO L269
Solar/Wind Harmer
1.121
3137176SLIGO L2192
Solar/Wind Harmer
0.252
316339AD2-160 GEN
Solar/Wind Harmer
0.101
316388AE2-253 GEN
Solar/Wind Harmer
0.197
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316005AA1-067
Solar/Wind Harmer
0.067
942751AE2-291 GEN
Solar/Wind Harmer
3.431
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.763
316294AC1-161 GEN
Solar/Wind Harmer
1.072
315737AD1-076 GEN
Solar/Wind Harmer
0.833
315816AE2-034 GEN
Solar/Wind Harmer
0.276
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.168
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.229
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.215
319010AE1-072 C
Solar/Wind Harmer
0.316
3146456SLIGO L269
Solar/Wind Harmer
0.063
944591AF1-124 GEN
Solar/Wind Harmer
14.293
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.529
970413AG2-270 GEN
50/50
10.247
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.096
3150861SPRUNCD
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
972003AH1-546 GEN
Solar/Wind Harmer
15.439
970221AG2-151 GEN
Solar/Wind Harmer
21.636
3146776BUCKING
Solar/Wind Harmer
0.132
270494AE1-108_GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.801
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.693
959311AF2-222 GEN
Solar/Wind Harmer
15.886
970257AG2-171 GEN
Solar/Wind Harmer
5.551
971775AH1-396 GEN
Solar/Wind Harmer
0.278
964241AG1-285 GEN
Solar/Wind Harmer
9.805
958131AF2-107 GEN
Solar/Wind Harmer
3.652
316478AD1-087 GEN
Solar/Wind Harmer
0.38
3147043LAWRENC
Solar/Wind Harmer
0.059
971683AH1-343 GEN
Solar/Wind Harmer
2.983
316181AB2-040 GEN
Solar/Wind Harmer
0.114
944011AF1-069 GEN
Solar/Wind Harmer
4.753
970917AG2-570 GEN
Solar/Wind Harmer
6.903
3156081AA2-088 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
1.284
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.358
3146173TUNIS
Solar/Wind Harmer
0.069
316123AC1-075 GEN
Solar/Wind Harmer
0.092
3145823KELFORD
Solar/Wind Harmer
0.069
315722AD1-056 GEN
Solar/Wind Harmer
2.302
3145273HOLLAND
Solar/Wind Harmer
0.05
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
316222AC1-221 GEN
Solar/Wind Harmer
0.27
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.483
316283AC2-100 C
Solar/Wind Harmer
0.127
970657AG2-426 GEN
Solar/Wind Harmer
1.458
315735AD1-075 GEN1
Solar/Wind Harmer
0.185
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.549
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.011
316246AF1-032 C
Solar/Wind Harmer
0.028
3145933PARMELE
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.733
316017AA1-139 ULT1
Solar/Wind Harmer
0.034
944581AF1-123 GEN
Solar/Wind Harmer
14.243
944601AF1-125 GEN
Solar/Wind Harmer
14.023
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.848
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.025
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.253
972205AH1-687 GEN
50/50
20.671
316303AF2-085
50/50
2.056
3151541CLOVER2
50/50
2.335
3151601KERR 3
50/50
0.217
3151611KERR 4
50/50
0.217
3151621KERR 5
50/50
0.217
3151631KERR 6
50/50
0.217
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.288
3151281ROARAP4
50/50
0.087
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971845AH1-439 GEN
Solar/Wind Harmer
16.331
316258AE1-075 C
Solar/Wind Harmer
0.188
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
11.554
970681AG2-440 GEN
Solar/Wind Harmer
7.669
3144303KENBRDG
Solar/Wind Harmer
0.139
316486AD2-202 GEN
Solar/Wind Harmer
0.111
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.021
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.947
970673AG2-436 GEN
Solar/Wind Harmer
9.878
970533AG2-339 GEN
Solar/Wind Harmer
5.968
3137643SOCKMAN
Solar/Wind Harmer
0.315
970085AG2-068 GEN
Solar/Wind Harmer
4.091
970581AG2-369 GEN
Solar/Wind Harmer
3.519
316426AA2-053 GEN
Solar/Wind Harmer
0.254
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.748
315652AC1-086 GEN
Solar/Wind Harmer
7.784
316274AC1-208 GEN
Solar/Wind Harmer
0.364
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
316210AC1-098 GEN
Solar/Wind Harmer
0.642
3146033SCOT NK
Solar/Wind Harmer
0.276
316463AE2-346 GEN
Solar/Wind Harmer
0.059
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316327AA2-057 GEN
Solar/Wind Harmer
0.1
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
970657AG2-426 GEN
Solar/Wind Harmer
0.477
315732AD1-074 GEN1
Solar/Wind Harmer
0.37
315733AD1-074 GEN2
Solar/Wind Harmer
0.37
3130546PLYMOUTH
Solar/Wind Harmer
0.065
316311AC2-079 GEN
Solar/Wind Harmer
1.854
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
313526AB2-022
Solar/Wind Harmer
0.034
957861AF2-080 GEN
Solar/Wind Harmer
2.738
3146406KITTY HAWK
Solar/Wind Harmer
0.008
957871AF2-081 GEN
Solar/Wind Harmer
3.154
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
316316AC1-027 C
Solar/Wind Harmer
0.06
3151081ELIZAR1
Adder
5.774
3151091ELIZAR2
Adder
5.674
971445AH1-216 GEN
Solar/Wind Harmer
4.323
3151201GRAVEL4
Adder
4.409
3151221GRAVEL6
Adder
4.404
3151191GRAVEL3
Adder
4.353
3151211GRAVEL5
Adder
4.353
315697AD1-025 GEN
Solar/Wind Harmer
0.065
316033AB2-134 GEN
Solar/Wind Harmer
0
315671AE2-027_GEN
Solar/Wind Harmer
0
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.022
315773AC2-141 GEN
Solar/Wind Harmer
2.266
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.171
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.82
316458AB2-190 GEN2
Solar/Wind Harmer
0.321
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.128
966001AG1-469 GEN
Solar/Wind Helper
0.206
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.524
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316132AB2-190 GEN1
Solar/Wind Harmer
0.321
944631AF1-128 GEN
Adder
26.814
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.905
3147666LOUISA
Solar/Wind Helper
0.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.137
MECLTFEXP_MEC->PJM
CLTF
0.549
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.728
LAGNLTFEXP_LAGN->PJM
CLTF
1.975
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.463
TVALTFEXP_TVA->PJM
CLTF
0.975
NYPJM->LTFIMP_NY
CLTF
0.615
LGEELTFEXP_LGEE->PJM
CLTF
0.138
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.8 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1349.42
MW Contribution:
2.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.635
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.467
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.293
970221AG2-151 GEN
Solar/Wind Harmer
28.434
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.927
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.892
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.504
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.402
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.114
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.731
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.52
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.595
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.538
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
316192AB2-158 GEN
Solar/Wind Helper
1.015
3147666LOUISA
Solar/Wind Helper
0.588
3147983MERCK5
Solar/Wind Helper
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.649
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.8 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1349.39
MW Contribution:
2.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.292
970221AG2-151 GEN
Solar/Wind Harmer
28.433
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.926
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.891
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
972205AH1-687 GEN
50/50
20.634
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.466
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.401
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.113
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.73
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.519
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.594
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.537
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
316192AB2-158 GEN
Solar/Wind Helper
1.016
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.648
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.03 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1286.56
MW Contribution:
2.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.03 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1286.56
MW Contribution:
2.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.21 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1021.03
MW Contribution:
2.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.805
3144293JTRSVLE
50/50
0.618
970535AG2-341 GEN
50/50
2.051
316336AC2-165 C
Solar/Wind Harmer
42.179
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
970301AG2-198 GEN
Solar/Wind Harmer
14.775
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.28
970323AG2-213 GEN
Solar/Wind Harmer
10.867
313527AB2-043 GEN
Solar/Wind Harmer
2.468
316237AB2-079_GEN
Solar/Wind Harmer
0.445
962561AG1-105 GEN
Solar/Wind Harmer
6.959
964791AG1-342 GEN
Solar/Wind Harmer
2.534
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.73
970099AG2-077 GEN
Solar/Wind Harmer
13.191
3151921BEARGRDN G2
50/50
5.579
3144293JTRSVLE
50/50
0.618
972003AH1-546 GEN
Solar/Wind Harmer
26.738
970221AG2-151 GEN
Solar/Wind Harmer
37.543
3146776BUCKING
Solar/Wind Harmer
-0.019
270494AE1-108_GEN
Solar/Wind Harmer
12.249
3146926FARMVIL
Solar/Wind Harmer
-0.024
315821AE2-092 GEN
Solar/Wind Harmer
7.754
942461AE2-259 GEN
Solar/Wind Harmer
5.223
3147133PAMPLIN
Solar/Wind Harmer
-0.092
959311AF2-222 GEN
Solar/Wind Harmer
23.56
970257AG2-171 GEN
Solar/Wind Harmer
8.15
971775AH1-396 GEN
Solar/Wind Harmer
1.533
958131AF2-107 GEN
Solar/Wind Harmer
6.444
964241AG1-285 GEN
Solar/Wind Harmer
13.685
316478AD1-087 GEN
Solar/Wind Harmer
0.939
972205AH1-687 GEN
50/50
27.258
316322AB2-045
Solar/Wind Harmer
1.775
971845AH1-439 GEN
Solar/Wind Harmer
27.551
946301AF1-294 GEN
Solar/Wind Harmer
7.02
961791AG1-021 GEN
Solar/Wind Harmer
3.424
970683AG2-441 GEN
Solar/Wind Harmer
17.408
970681AG2-440 GEN
Solar/Wind Harmer
11.554
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.445
316239AB2-077_GEN
Solar/Wind Harmer
0.445
316486AD2-202 GEN
Solar/Wind Harmer
0.275
3151931BEARGRDN S1
50/50
7.207
3151911BEARGRDN G1
50/50
5.579
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.488
970937AG2-583 GEN
Solar/Wind Harmer
48.556
971377AH1-170 GEN
Solar/Wind Harmer
7.509
3147623JAMES R
Solar/Wind Harmer
0.929
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
971563AH1-280 GEN
Solar/Wind Harmer
3.424
315687AD1-152 GEN
Solar/Wind Harmer
1.188
316248AF1-058 C
Solar/Wind Harmer
0.284
970933AG2-581 GEN
Solar/Wind Harmer
6.805
942751AE2-291 GEN
Solar/Wind Harmer
4.456
966001AG1-469 GEN
Solar/Wind Helper
0.159
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971683AH1-343 GEN
Solar/Wind Harmer
3.682
316123AC1-075 GEN
Solar/Wind Harmer
0.805
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
970685AG2-442 GEN
Solar/Wind Harmer
22.673
316034AC1-036 C
Solar/Wind Harmer
0.403
315785AD2-033 C
Solar/Wind Harmer
4.657
316131AB2-060 GEN
Solar/Wind Harmer
1.684
315693AD1-088 GEN
Solar/Wind Harmer
7.148
970401AG2-262 GEN
Solar/Wind Harmer
0.774
957481AF2-042 GEN
Solar/Wind Harmer
32.976
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.429
946281AF1-292 GEN
Solar/Wind Harmer
0.145
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
971065AG2-659 GEN
Solar/Wind Harmer
4.765
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.734
962751AG1-124 GEN
Solar/Wind Harmer
4.607
960081AF2-299 GEN
Solar/Wind Harmer
0.726
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.289
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.592
MECLTFEXP_MEC->PJM
CLTF
0.532
SIGELTFEXP_SIGE->PJM
CLTF
0.015
CPLELTFEXP_CPLE->PJM
CLTF
2.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.391
LAGNLTFEXP_LAGN->PJM
CLTF
1.582
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.17
TVALTFEXP_TVA->PJM
CLTF
0.79
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.163
WECLTFEXP_WEC->PJM
CLTF
0.076

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.29 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:899.3
MW Contribution:
2.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.275
3151601KERR 3
50/50
0.117
3151611KERR 4
50/50
0.117
3151621KERR 5
50/50
0.117
3151631KERR 6
50/50
0.117
316258AE1-075 C
Solar/Wind Harmer
0.602
971845AH1-439 GEN
Solar/Wind Harmer
16.779
946301AF1-294 GEN
Solar/Wind Harmer
3.605
961791AG1-021 GEN
Solar/Wind Harmer
1.754
970683AG2-441 GEN
Solar/Wind Harmer
9.75
970681AG2-440 GEN
Solar/Wind Harmer
6.472
3144303KENBRDG
Solar/Wind Harmer
0.112
316233AE1-074 FULL
Solar/Wind Helper
0.266
3151921BEARGRDN G2
50/50
4.559
3144293JTRSVLE
50/50
0.463
3143336POWHATN
Solar/Wind Harmer
12.19
972003AH1-546 GEN
Solar/Wind Harmer
16.568
970221AG2-151 GEN
Solar/Wind Harmer
23.292
3146776BUCKING
Solar/Wind Harmer
0.136
270494AE1-108_GEN
Solar/Wind Harmer
4.117
315821AE2-092 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.619
959311AF2-222 GEN
Solar/Wind Harmer
12.976
958131AF2-107 GEN
Solar/Wind Harmer
4.136
970257AG2-171 GEN
Solar/Wind Harmer
4.467
971775AH1-396 GEN
Solar/Wind Harmer
0.223
964241AG1-285 GEN
Solar/Wind Harmer
7.167
970909AG2-566 GEN
50/50
2.107
3144293JTRSVLE
50/50
0.463
970535AG2-341 GEN
50/50
1.292
3151581KERR 1
50/50
0.042
316313AB2-026
Solar/Wind Harmer
0.502
316336AC2-165 C
Solar/Wind Harmer
38.092
3146776BUCKING
Solar/Wind Harmer
1.511
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
8.428
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.192
970323AG2-213 GEN
Solar/Wind Harmer
5.957
962561AG1-105 GEN
Solar/Wind Harmer
3.393
964791AG1-342 GEN
Solar/Wind Harmer
1.291
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
316118AC1-105 GEN
Solar/Wind Harmer
0.151
3143526WINTERP
Solar/Wind Helper
0.907
3151931BEARGRDN S1
50/50
5.89
3151911BEARGRDN G1
50/50
4.559
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.365
3151591KERR 2
50/50
0.117
3151641KERR 7
50/50
0.117
3143336POWHATN
Solar/Wind Harmer
14.341
970937AG2-583 GEN
Solar/Wind Harmer
37.462
971377AH1-170 GEN
Solar/Wind Harmer
4.658
3147623JAMES R
Solar/Wind Harmer
1.012
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
971563AH1-280 GEN
Solar/Wind Harmer
1.949
970685AG2-442 GEN
Solar/Wind Harmer
12.798
316034AC1-036 C
Solar/Wind Harmer
0.009
315785AD2-033 C
Solar/Wind Harmer
1.058
316131AB2-060 GEN
Solar/Wind Harmer
0.29
315693AD1-088 GEN
Solar/Wind Harmer
3.806
970401AG2-262 GEN
Solar/Wind Harmer
0.394
962751AG1-124 GEN
Solar/Wind Harmer
2.968
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.907
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.502
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.387
MECLTFEXP_MEC->PJM
CLTF
0.774
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
1.266
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.537
LAGNLTFEXP_LAGN->PJM
CLTF
1.316
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.108
TVALTFEXP_TVA->PJM
CLTF
0.676
NYPJM->LTFIMP_NY
CLTF
0.419
LGEELTFEXP_LGEE->PJM
CLTF
0.312
WECLTFEXP_WEC->PJM
CLTF
0.156

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.55 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:893.41
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
1.866
3144293JTRSVLE
50/50
0.376
970535AG2-341 GEN
50/50
1.343
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
316313AB2-026
Solar/Wind Harmer
0.443
316336AC2-165 C
Solar/Wind Harmer
32.594
3146776BUCKING
Solar/Wind Harmer
1.048
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.463
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.782
970323AG2-213 GEN
Solar/Wind Harmer
5.132
970099AG2-077 GEN
Solar/Wind Harmer
11.633
962561AG1-105 GEN
Solar/Wind Harmer
3.754
964791AG1-342 GEN
Solar/Wind Harmer
1.469
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
316118AC1-105 GEN
Solar/Wind Harmer
0.185
3143526WINTERP
Solar/Wind Helper
1.297
316240AF1-291 C
Solar/Wind Helper
0.164
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.219
3151931BEARGRDN S1
50/50
3.822
3151911BEARGRDN G1
50/50
2.958
3144293JTRSVLE
50/50
0.376
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.186
3151591KERR 2
50/50
0.132
3151641KERR 7
50/50
0.132
3143336POWHATN
Solar/Wind Harmer
12.652
970937AG2-583 GEN
Solar/Wind Harmer
28.68
971377AH1-170 GEN
Solar/Wind Harmer
3.024
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.584
970685AG2-442 GEN
Solar/Wind Harmer
10.536
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.762
315785AD2-033 C
Solar/Wind Harmer
0.926
957481AF2-042 GEN
Solar/Wind Harmer
29.081
316131AB2-060 GEN
Solar/Wind Harmer
0.28
970401AG2-262 GEN
Solar/Wind Harmer
0.449
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.297
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.954
3142416OLDCHRC
Solar/Wind Helper
0.298
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.644
3142433PROV 92
Solar/Wind Helper
0.446
3151921BEARGRDN G2
50/50
2.958
3144293JTRSVLE
50/50
0.376
970413AG2-270 GEN
50/50
9.518
3143336POWHATN
Solar/Wind Harmer
10.755
972003AH1-546 GEN
Solar/Wind Harmer
10.819
970221AG2-151 GEN
Solar/Wind Harmer
15.119
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.707
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.496
959311AF2-222 GEN
Solar/Wind Harmer
11.062
970257AG2-171 GEN
Solar/Wind Harmer
3.849
971775AH1-396 GEN
Solar/Wind Harmer
0.192
958131AF2-107 GEN
Solar/Wind Harmer
2.946
316478AD1-087 GEN
Solar/Wind Harmer
0.352
964241AG1-285 GEN
Solar/Wind Harmer
6.616
3148013FISHERV
Solar/Wind Harmer
0.07
971683AH1-343 GEN
Solar/Wind Harmer
2.311
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.713
316075AC2-137 C
Solar/Wind Helper
0.174
316458AB2-190 GEN2
Solar/Wind Helper
0.644
972205AH1-687 GEN
50/50
14.454
3151541CLOVER2
50/50
2.169
3151601KERR 3
50/50
0.132
3151611KERR 4
50/50
0.132
3151621KERR 5
50/50
0.132
3151631KERR 6
50/50
0.132
316258AE1-075 C
Solar/Wind Harmer
0.531
971845AH1-439 GEN
Solar/Wind Harmer
11.703
946301AF1-294 GEN
Solar/Wind Harmer
2.93
961791AG1-021 GEN
Solar/Wind Harmer
1.426
970683AG2-441 GEN
Solar/Wind Harmer
8.125
970681AG2-440 GEN
Solar/Wind Harmer
5.392
3144303KENBRDG
Solar/Wind Harmer
0.096
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.103
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
316233AE1-074 FULL
Solar/Wind Helper
0.381
315839AE2-212 C
Solar/Wind Helper
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.245
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.615
MECLTFEXP_MEC->PJM
CLTF
1.03
SIGELTFEXP_SIGE->PJM
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
0.585
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.743
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.969
TVALTFEXP_TVA->PJM
CLTF
0.708
NYPJM->LTFIMP_NY
CLTF
0.346
LGEELTFEXP_LGEE->PJM
CLTF
0.443
WECLTFEXP_WEC->PJM
CLTF
0.226

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2054_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.57 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1014.95
MW Contribution:
2.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.288
316258AE1-075 C
Solar/Wind Harmer
2.194
316405AF2-144 C
Solar/Wind Harmer
2.316
316322AB2-045
Solar/Wind Harmer
1.426
971845AH1-439 GEN
Solar/Wind Harmer
22.103
946301AF1-294 GEN
Solar/Wind Harmer
5.26
970909AG2-566 GEN
50/50
2.107
3144293JTRSVLE
50/50
0.463
316313AB2-026
Solar/Wind Harmer
2.438
316336AC2-165 C
Solar/Wind Harmer
52.734
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.096
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.208
970323AG2-213 GEN
Solar/Wind Harmer
7.843
313527AB2-043 GEN
Solar/Wind Harmer
1.639
316237AB2-079_GEN
Solar/Wind Harmer
0.294
962561AG1-105 GEN
Solar/Wind Harmer
4.47
964791AG1-342 GEN
Solar/Wind Harmer
1.615
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.455
3143526WINTERP
Solar/Wind Helper
0.912
3151931BEARGRDN S1
50/50
5.893
3151911BEARGRDN G1
50/50
4.561
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.365
3143336POWHATN
Solar/Wind Harmer
10.754
970937AG2-583 GEN
Solar/Wind Harmer
49.334
971377AH1-170 GEN
Solar/Wind Harmer
6.142
3147623JAMES R
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.566
970685AG2-442 GEN
Solar/Wind Harmer
16.853
316034AC1-036 C
Solar/Wind Harmer
0.291
315785AD2-033 C
Solar/Wind Harmer
3.326
316131AB2-060 GEN
Solar/Wind Harmer
1.128
315693AD1-088 GEN
Solar/Wind Harmer
4.447
970401AG2-262 GEN
Solar/Wind Harmer
0.493
962751AG1-124 GEN
Solar/Wind Harmer
4.402
3143226MDLTHAN
Solar/Wind Helper
0.216
3143526WINTERP
Solar/Wind Helper
0.912
3151921BEARGRDN G2
50/50
4.561
3144293JTRSVLE
50/50
0.463
3143336POWHATN
Solar/Wind Harmer
9.141
972003AH1-546 GEN
Solar/Wind Harmer
21.827
970221AG2-151 GEN
Solar/Wind Harmer
30.71
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
10.084
315821AE2-092 GEN
Solar/Wind Harmer
6.906
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.031
3147133PAMPLIN
Solar/Wind Harmer
-0.069
959311AF2-222 GEN
Solar/Wind Harmer
17.121
958131AF2-107 GEN
Solar/Wind Harmer
5.54
970257AG2-171 GEN
Solar/Wind Harmer
5.883
971775AH1-396 GEN
Solar/Wind Harmer
1.107
964241AG1-285 GEN
Solar/Wind Harmer
9.436
961791AG1-021 GEN
Solar/Wind Harmer
2.566
970683AG2-441 GEN
Solar/Wind Harmer
12.84
970681AG2-440 GEN
Solar/Wind Harmer
8.522
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316233AE1-074 FULL
Solar/Wind Helper
0.268
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.938
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.516
MECLTFEXP_MEC->PJM
CLTF
0.827
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
1.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.974
LAGNLTFEXP_LAGN->PJM
CLTF
1.382
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.181
TVALTFEXP_TVA->PJM
CLTF
0.71
NYPJM->LTFIMP_NY
CLTF
0.436
LGEELTFEXP_LGEE->PJM
CLTF
0.335
WECLTFEXP_WEC->PJM
CLTF
0.168

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 233T2028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.84 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:998.06
MW Contribution:
2.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.559
3144293JTRSVLE
50/50
0.463
3143336POWHATN
Solar/Wind Harmer
9.142
972003AH1-546 GEN
Solar/Wind Harmer
21.816
970221AG2-151 GEN
Solar/Wind Harmer
30.673
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
10.067
315821AE2-092 GEN
Solar/Wind Harmer
6.866
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.031
3147133PAMPLIN
Solar/Wind Harmer
-0.069
959311AF2-222 GEN
Solar/Wind Harmer
17.12
958131AF2-107 GEN
Solar/Wind Harmer
5.51
970257AG2-171 GEN
Solar/Wind Harmer
5.882
971775AH1-396 GEN
Solar/Wind Harmer
1.107
964241AG1-285 GEN
Solar/Wind Harmer
9.437
970909AG2-566 GEN
50/50
2.107
3144293JTRSVLE
50/50
0.463
316313AB2-026
Solar/Wind Harmer
2.438
316336AC2-165 C
Solar/Wind Harmer
52.74
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.096
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.207
970323AG2-213 GEN
Solar/Wind Harmer
7.843
313527AB2-043 GEN
Solar/Wind Harmer
1.64
316237AB2-079_GEN
Solar/Wind Harmer
0.294
962561AG1-105 GEN
Solar/Wind Harmer
4.468
964791AG1-342 GEN
Solar/Wind Harmer
1.614
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3143526WINTERP
Solar/Wind Helper
0.908
972205AH1-687 GEN
50/50
22.277
316258AE1-075 C
Solar/Wind Harmer
2.194
316405AF2-144 C
Solar/Wind Harmer
2.316
316322AB2-045
Solar/Wind Harmer
1.426
971845AH1-439 GEN
Solar/Wind Harmer
22.094
946301AF1-294 GEN
Solar/Wind Harmer
5.26
961791AG1-021 GEN
Solar/Wind Harmer
2.566
970683AG2-441 GEN
Solar/Wind Harmer
12.838
970681AG2-440 GEN
Solar/Wind Harmer
8.521
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316233AE1-074 FULL
Solar/Wind Helper
0.267
3151931BEARGRDN S1
50/50
5.89
3151911BEARGRDN G1
50/50
4.559
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.365
3143336POWHATN
Solar/Wind Harmer
10.756
970937AG2-583 GEN
Solar/Wind Harmer
49.326
971377AH1-170 GEN
Solar/Wind Harmer
6.135
3147623JAMES R
Solar/Wind Harmer
0.759
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.566
970685AG2-442 GEN
Solar/Wind Harmer
16.851
316034AC1-036 C
Solar/Wind Harmer
0.291
315785AD2-033 C
Solar/Wind Harmer
3.326
316131AB2-060 GEN
Solar/Wind Harmer
1.128
315693AD1-088 GEN
Solar/Wind Harmer
4.453
970401AG2-262 GEN
Solar/Wind Harmer
0.493
962751AG1-124 GEN
Solar/Wind Harmer
4.343
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.908
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.558
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.404
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.593
LAGNLTFEXP_LAGN->PJM
CLTF
1.324
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.118
TVALTFEXP_TVA->PJM
CLTF
0.68
NYPJM->LTFIMP_NY
CLTF
0.421
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.157

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.81 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:997.75
MW Contribution:
2.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.616
3144293JTRSVLE
50/50
0.469
3143336POWHATN
Solar/Wind Harmer
9.18
972003AH1-546 GEN
Solar/Wind Harmer
22.089
970221AG2-151 GEN
Solar/Wind Harmer
29.401
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.651
3146926FARMVIL
Solar/Wind Harmer
-0.019
315821AE2-092 GEN
Solar/Wind Harmer
6.501
942461AE2-259 GEN
Solar/Wind Harmer
4.086
3147133PAMPLIN
Solar/Wind Harmer
-0.07
959311AF2-222 GEN
Solar/Wind Harmer
17.375
970257AG2-171 GEN
Solar/Wind Harmer
5.971
971775AH1-396 GEN
Solar/Wind Harmer
1.123
958131AF2-107 GEN
Solar/Wind Harmer
5.288
964241AG1-285 GEN
Solar/Wind Harmer
9.588
970909AG2-566 GEN
50/50
2.137
3144293JTRSVLE
50/50
0.469
316313AB2-026
Solar/Wind Harmer
2.448
316336AC2-165 C
Solar/Wind Harmer
53.006
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.257
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.253
970323AG2-213 GEN
Solar/Wind Harmer
7.961
313527AB2-043 GEN
Solar/Wind Harmer
1.667
316237AB2-079_GEN
Solar/Wind Harmer
0.299
962561AG1-105 GEN
Solar/Wind Harmer
4.541
964791AG1-342 GEN
Solar/Wind Harmer
1.64
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3143526WINTERP
Solar/Wind Helper
0.895
3151931BEARGRDN S1
50/50
5.964
3151911BEARGRDN G1
50/50
4.616
3144293JTRSVLE
50/50
0.469
3144293JTRSVLE
50/50
0.371
3143336POWHATN
Solar/Wind Harmer
10.8
970937AG2-583 GEN
Solar/Wind Harmer
49.734
971377AH1-170 GEN
Solar/Wind Harmer
5.88
3147623JAMES R
Solar/Wind Harmer
0.728
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.602
970685AG2-442 GEN
Solar/Wind Harmer
17.094
316034AC1-036 C
Solar/Wind Harmer
0.295
315785AD2-033 C
Solar/Wind Harmer
3.377
316131AB2-060 GEN
Solar/Wind Harmer
1.147
315693AD1-088 GEN
Solar/Wind Harmer
4.54
970401AG2-262 GEN
Solar/Wind Harmer
0.501
962751AG1-124 GEN
Solar/Wind Harmer
4.175
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.895
972205AH1-687 GEN
50/50
22.554
316258AE1-075 C
Solar/Wind Harmer
2.203
316405AF2-144 C
Solar/Wind Harmer
2.326
316322AB2-045
Solar/Wind Harmer
1.444
971845AH1-439 GEN
Solar/Wind Harmer
22.379
946301AF1-294 GEN
Solar/Wind Harmer
5.335
961791AG1-021 GEN
Solar/Wind Harmer
2.602
970683AG2-441 GEN
Solar/Wind Harmer
13.026
970681AG2-440 GEN
Solar/Wind Harmer
8.645
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.299
316239AB2-077_GEN
Solar/Wind Harmer
0.299
316233AE1-074 FULL
Solar/Wind Helper
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.365
MECLTFEXP_MEC->PJM
CLTF
0.759
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
1.298
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.447
LAGNLTFEXP_LAGN->PJM
CLTF
1.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.153
TVALTFEXP_TVA->PJM
CLTF
0.671
NYPJM->LTFIMP_NY
CLTF
0.419
LGEELTFEXP_LGEE->PJM
CLTF
0.305
WECLTFEXP_WEC->PJM
CLTF
0.152

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: WT2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.79 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:997.51
MW Contribution:
2.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.616
3144293JTRSVLE
50/50
0.469
3143336POWHATN
Solar/Wind Harmer
9.18
972003AH1-546 GEN
Solar/Wind Harmer
22.089
970221AG2-151 GEN
Solar/Wind Harmer
29.401
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.651
3146926FARMVIL
Solar/Wind Harmer
-0.019
315821AE2-092 GEN
Solar/Wind Harmer
6.501
942461AE2-259 GEN
Solar/Wind Harmer
4.086
3147133PAMPLIN
Solar/Wind Harmer
-0.07
959311AF2-222 GEN
Solar/Wind Harmer
17.375
970257AG2-171 GEN
Solar/Wind Harmer
5.971
971775AH1-396 GEN
Solar/Wind Harmer
1.123
958131AF2-107 GEN
Solar/Wind Harmer
5.288
964241AG1-285 GEN
Solar/Wind Harmer
9.588
970909AG2-566 GEN
50/50
2.137
3144293JTRSVLE
50/50
0.469
316313AB2-026
Solar/Wind Harmer
2.448
316336AC2-165 C
Solar/Wind Harmer
53.006
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.257
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.253
970323AG2-213 GEN
Solar/Wind Harmer
7.961
313527AB2-043 GEN
Solar/Wind Harmer
1.667
3151931BEARGRDN S1
50/50
5.964
3151911BEARGRDN G1
50/50
4.616
3144293JTRSVLE
50/50
0.469
3144293JTRSVLE
50/50
0.371
3143336POWHATN
Solar/Wind Harmer
10.8
972205AH1-687 GEN
50/50
22.554
316258AE1-075 C
Solar/Wind Harmer
2.203
316405AF2-144 C
Solar/Wind Harmer
2.326
316322AB2-045
Solar/Wind Harmer
1.444
971845AH1-439 GEN
Solar/Wind Harmer
22.379
946301AF1-294 GEN
Solar/Wind Harmer
5.335
961791AG1-021 GEN
Solar/Wind Harmer
2.602
970683AG2-441 GEN
Solar/Wind Harmer
13.026
970681AG2-440 GEN
Solar/Wind Harmer
8.645
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.299
316239AB2-077_GEN
Solar/Wind Harmer
0.299
316237AB2-079_GEN
Solar/Wind Harmer
0.299
962561AG1-105 GEN
Solar/Wind Harmer
4.541
964791AG1-342 GEN
Solar/Wind Harmer
1.64
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3143526WINTERP
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.263
970937AG2-583 GEN
Solar/Wind Harmer
49.734
971377AH1-170 GEN
Solar/Wind Harmer
5.88
3147623JAMES R
Solar/Wind Harmer
0.728
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.602
970685AG2-442 GEN
Solar/Wind Harmer
17.094
316034AC1-036 C
Solar/Wind Harmer
0.295
315785AD2-033 C
Solar/Wind Harmer
3.377
316131AB2-060 GEN
Solar/Wind Harmer
1.147
315693AD1-088 GEN
Solar/Wind Harmer
4.54
970401AG2-262 GEN
Solar/Wind Harmer
0.501
962751AG1-124 GEN
Solar/Wind Harmer
4.175
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.895
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.365
MECLTFEXP_MEC->PJM
CLTF
0.759
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
1.298
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.447
LAGNLTFEXP_LAGN->PJM
CLTF
1.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.153
TVALTFEXP_TVA->PJM
CLTF
0.671
NYPJM->LTFIMP_NY
CLTF
0.419
LGEELTFEXP_LGEE->PJM
CLTF
0.305
WECLTFEXP_WEC->PJM
CLTF
0.152

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.67 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:996.36
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
1.869
3144293JTRSVLE
50/50
0.377
316313AB2-026
Solar/Wind Harmer
2.149
316336AC2-165 C
Solar/Wind Harmer
45.095
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
9.845
972205AH1-687 GEN
50/50
14.444
316258AE1-075 C
Solar/Wind Harmer
1.934
316405AF2-144 C
Solar/Wind Harmer
2.042
316322AB2-045
Solar/Wind Harmer
0.988
971845AH1-439 GEN
Solar/Wind Harmer
15.409
946301AF1-294 GEN
Solar/Wind Harmer
4.285
961791AG1-021 GEN
Solar/Wind Harmer
2.09
970683AG2-441 GEN
Solar/Wind Harmer
10.725
970681AG2-440 GEN
Solar/Wind Harmer
7.118
3144303KENBRDG
Solar/Wind Harmer
-0.011
971967AH1-528 GEN
Solar/Wind Harmer
23.617
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316486AD2-202 GEN
Solar/Wind Harmer
0.291
316238AB2-078_GEN
Solar/Wind Harmer
0.292
316239AB2-077_GEN
Solar/Wind Harmer
0.292
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.004
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Helper
0.383
315839AE2-212 C
Solar/Wind Helper
0.159
3151921BEARGRDN G2
50/50
2.956
3144293JTRSVLE
50/50
0.377
3143336POWHATN
Solar/Wind Harmer
8.06
972003AH1-546 GEN
Solar/Wind Harmer
14.237
970221AG2-151 GEN
Solar/Wind Harmer
19.894
3146776BUCKING
Solar/Wind Harmer
-0.01
270494AE1-108_GEN
Solar/Wind Harmer
6.615
3146926FARMVIL
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
4.818
942461AE2-259 GEN
Solar/Wind Harmer
3.131
3147133PAMPLIN
Solar/Wind Harmer
-0.056
959311AF2-222 GEN
Solar/Wind Harmer
14.638
970257AG2-171 GEN
Solar/Wind Harmer
5.084
971775AH1-396 GEN
Solar/Wind Harmer
0.956
958131AF2-107 GEN
Solar/Wind Harmer
3.928
316478AD1-087 GEN
Solar/Wind Harmer
0.993
964241AG1-285 GEN
Solar/Wind Harmer
8.748
3148013FISHERV
Solar/Wind Harmer
-0.008
316003AC1-222 GEN
Solar/Wind Harmer
0.728
971683AH1-343 GEN
Solar/Wind Harmer
3.075
316123AC1-075 GEN
Solar/Wind Harmer
0.688
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.721
316075AC2-137 C
Solar/Wind Helper
0.176
316458AB2-190 GEN2
Solar/Wind Helper
0.654
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.613
970323AG2-213 GEN
Solar/Wind Harmer
6.778
970933AG2-581 GEN
Solar/Wind Harmer
11.778
970099AG2-077 GEN
Solar/Wind Harmer
15.401
313527AB2-043 GEN
Solar/Wind Harmer
1.608
315687AD1-152 GEN
Solar/Wind Harmer
1.169
316237AB2-079_GEN
Solar/Wind Harmer
0.292
962561AG1-105 GEN
Solar/Wind Harmer
4.98
964791AG1-342 GEN
Solar/Wind Harmer
1.851
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
316118AC1-105 GEN
Solar/Wind Harmer
0.563
316248AF1-058 C
Solar/Wind Harmer
0.234
3143526WINTERP
Solar/Wind Helper
1.305
316240AF1-291 C
Solar/Wind Helper
0.166
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.159
316312AB1-027
Solar/Wind Helper
0.221
3151931BEARGRDN S1
50/50
3.819
3151911BEARGRDN G1
50/50
2.956
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.298
3143336POWHATN
Solar/Wind Harmer
9.482
970937AG2-583 GEN
Solar/Wind Harmer
37.736
971377AH1-170 GEN
Solar/Wind Harmer
3.979
3147623JAMES R
Solar/Wind Harmer
0.492
3146776BUCKING
Solar/Wind Harmer
-0.012
3146926FARMVIL
Solar/Wind Harmer
-0.014
971563AH1-280 GEN
Solar/Wind Harmer
2.09
970685AG2-442 GEN
Solar/Wind Harmer
13.906
316034AC1-036 C
Solar/Wind Harmer
0.251
315693AD1-088 GEN
Solar/Wind Harmer
6.775
315785AD2-033 C
Solar/Wind Harmer
2.921
957481AF2-042 GEN
Solar/Wind Harmer
38.503
316131AB2-060 GEN
Solar/Wind Harmer
1.093
970401AG2-262 GEN
Solar/Wind Harmer
0.565
3143226MDLTHAN
Solar/Wind Helper
0.302
3143526WINTERP
Solar/Wind Helper
1.305
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.968
3142416OLDCHRC
Solar/Wind Helper
0.301
3142416OLDCHRC
Solar/Wind Helper
0.115
316132AB2-190 GEN1
Solar/Wind Helper
0.654
3142433PROV 92
Solar/Wind Helper
0.453
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.517
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.755
MECLTFEXP_MEC->PJM
CLTF
1.071
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CPLELTFEXP_CPLE->PJM
CLTF
0.697
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.177
LAGNLTFEXP_LAGN->PJM
CLTF
1.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.22
TVALTFEXP_TVA->PJM
CLTF
0.749
NYPJM->LTFIMP_NY
CLTF
0.358
LGEELTFEXP_LGEE->PJM
CLTF
0.457
WECLTFEXP_WEC->PJM
CLTF
0.233

Details for 6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.13 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1015.01
MW Contribution:
0.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.26
3151861LOWMORA
50/50
0.943
315760AF1-028 GEN
50/50
12.702
3152061BATH 6F
50/50
1.638
3152021BATH 2B
50/50
1.633
3144293JTRSVLE
50/50
0.158
3152191CUNINGD
50/50
1.058
972255AH1-712 GEN
50/50
32.029
972003AH1-546 GEN
Solar/Wind Harmer
4.596
970221AG2-151 GEN
Solar/Wind Harmer
7.054
315821AE2-092 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Harmer
0.123
270494AE1-108_GEN
Solar/Wind Harmer
1.333
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.052
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
1.009
958131AF2-107 GEN
Solar/Wind Harmer
1.905
3147133PAMPLIN
Solar/Wind Harmer
0.206
3132273ORANGE
Solar/Wind Helper
0.106
3147666LOUISA
Solar/Wind Helper
1.085
972205AH1-687 GEN
50/50
6.157
3151881LOWMORC
50/50
0.936
3151881LOWMORC
50/50
0.921
3151861LOWMORA
50/50
0.906
3152031BATH 3C
50/50
1.635
3152051BATH 5E
50/50
1.635
3152011BATH 1A
50/50
1.633
3152041BATH 4D
50/50
1.632
23503501NHY_Z2-039
50/50
0.004
23503401SHY_Z2-039
50/50
0.002
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
971845AH1-439 GEN
Solar/Wind Harmer
4.836
3148463FAIRFLD
Solar/Wind Harmer
0.083
316258AE1-075 C
Solar/Wind Harmer
0.05
946301AF1-294 GEN
Solar/Wind Harmer
1.229
961791AG1-021 GEN
Solar/Wind Harmer
0.598
3137383CUSHAW
50/50
0.018
970909AG2-566 GEN
50/50
0.694
3144293JTRSVLE
50/50
0.158
3152181CUNINGC
50/50
0.486
3152171CUNINGB
50/50
0.458
3152161CUNINGA
50/50
0.455
972193AH1-681 GEN
50/50
1.431
3146776BUCKING
Solar/Wind Harmer
0.434
3146776BUCKING
Solar/Wind Harmer
0.035
316336AC2-165 C
Solar/Wind Harmer
3.993
316313AB2-026
Solar/Wind Harmer
0.042
3147133PAMPLIN
Solar/Wind Harmer
0.066
3147133PAMPLIN
Solar/Wind Harmer
0.053
970301AG2-198 GEN
Solar/Wind Harmer
2.775
958211AF2-115 GEN
Solar/Wind Harmer
0.748
966001AG1-469 GEN
Solar/Wind Helper
0.74
316006AB2-029 C
Solar/Wind Helper
0.089
3151931BEARGRDN S1
50/50
1.628
3151911BEARGRDN G1
50/50
1.26
3144293JTRSVLE
50/50
0.158
3144293JTRSVLE
50/50
0.125
972277AH1-723 GEN
50/50
37.324
971377AH1-170 GEN
Solar/Wind Harmer
1.411
3147623JAMES R
Solar/Wind Harmer
0.307
970937AG2-583 GEN
Solar/Wind Harmer
6.726
3146776BUCKING
Solar/Wind Harmer
0.043
3146926FARMVIL
Solar/Wind Harmer
0.052
3147983MERCK5
Solar/Wind Harmer
0.033
3143336POWHATN
Solar/Wind Harmer
1.187
971563AH1-280 GEN
Solar/Wind Harmer
0.665
970685AG2-442 GEN
Solar/Wind Harmer
4.455
316192AB2-158 GEN
Solar/Wind Helper
3.275
3147666LOUISA
Solar/Wind Helper
1.888
970683AG2-441 GEN
Solar/Wind Harmer
3.461
970681AG2-440 GEN
Solar/Wind Harmer
2.297
315651AD1-115 GEN
Solar/Wind Helper
0.973
316164AC1-076 GEN
Solar/Wind Helper
1.197
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.536
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.509
MECLTFEXP_MEC->PJM
CLTF
2.016
SIGELTFEXP_SIGE->PJM
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
1.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.062
LAGNLTFEXP_LAGN->PJM
CLTF
2.956
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.464
TVALTFEXP_TVA->PJM
CLTF
1.521
NYPJM->LTFIMP_NY
CLTF
0.852
LGEELTFEXP_LGEE->PJM
CLTF
0.84
WECLTFEXP_WEC->PJM
CLTF
0.429

Details for 6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 550_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.87 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1002.59
MW Contribution:
0.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.348
3151861LOWMORA
50/50
1.232
3152061BATH 6F
50/50
2.37
3152021BATH 2B
50/50
2.364
315760AF1-028 GEN
50/50
16.854
3144293JTRSVLE
50/50
0.164
3152191CUNINGD
50/50
1.156
972255AH1-712 GEN
50/50
34.975
3148013FISHERV
Solar/Wind Harmer
0.147
315821AE2-092 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
7.624
972003AH1-546 GEN
Solar/Wind Harmer
4.916
270494AE1-108_GEN
Solar/Wind Harmer
1.457
3146776BUCKING
Solar/Wind Harmer
0.042
3146926FARMVIL
Solar/Wind Harmer
0.055
942461AE2-259 GEN
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
2.187
3143336POWHATN
Solar/Wind Harmer
1.04
3147133PAMPLIN
Solar/Wind Harmer
0.215
3132273ORANGE
Solar/Wind Helper
0.101
3147666LOUISA
Solar/Wind Helper
1.02
972205AH1-687 GEN
50/50
6.589
3151881LOWMORC
50/50
1.223
3151881LOWMORC
50/50
1.203
3151861LOWMORA
50/50
1.184
3152031BATH 3C
50/50
2.367
3152051BATH 5E
50/50
2.366
3152011BATH 1A
50/50
2.364
3152041BATH 4D
50/50
2.363
23503501NHY_Z2-039
50/50
0.005
23503401SHY_Z2-039
50/50
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.088
3148013FISHERV
Solar/Wind Harmer
0.084
971845AH1-439 GEN
Solar/Wind Harmer
5.139
3148463FAIRFLD
Solar/Wind Harmer
0.108
316258AE1-075 C
Solar/Wind Harmer
0.051
946301AF1-294 GEN
Solar/Wind Harmer
1.278
961791AG1-021 GEN
Solar/Wind Harmer
0.622
970683AG2-441 GEN
Solar/Wind Harmer
3.582
970681AG2-440 GEN
Solar/Wind Harmer
2.378
315651AD1-115 GEN
Solar/Wind Helper
0.898
316164AC1-076 GEN
Solar/Wind Helper
1.077
3137383CUSHAW
50/50
0.023
970909AG2-566 GEN
50/50
0.722
3144293JTRSVLE
50/50
0.164
3152181CUNINGC
50/50
0.531
3152171CUNINGB
50/50
0.5
3152161CUNINGA
50/50
0.497
972193AH1-681 GEN
50/50
1.563
3146776BUCKING
Solar/Wind Harmer
0.461
3146776BUCKING
Solar/Wind Harmer
0.037
316336AC2-165 C
Solar/Wind Harmer
4.161
3132123MT JACKSON
Solar/Wind Harmer
0.226
970117AG2-086 GEN
Solar/Wind Harmer
1.736
970117AG2-086 GEN
Solar/Wind Harmer
1.158
316313AB2-026
Solar/Wind Harmer
0.043
3147133PAMPLIN
Solar/Wind Harmer
0.068
3147133PAMPLIN
Solar/Wind Harmer
0.055
970301AG2-198 GEN
Solar/Wind Harmer
2.887
958211AF2-115 GEN
Solar/Wind Harmer
0.777
966001AG1-469 GEN
Solar/Wind Helper
0.71
316006AB2-029 C
Solar/Wind Helper
0.081
3151931BEARGRDN S1
50/50
1.742
3151911BEARGRDN G1
50/50
1.348
3144293JTRSVLE
50/50
0.164
3144293JTRSVLE
50/50
0.13
972277AH1-723 GEN
50/50
40.756
971377AH1-170 GEN
Solar/Wind Harmer
1.525
3147623JAMES R
Solar/Wind Harmer
0.331
970937AG2-583 GEN
Solar/Wind Harmer
7.136
3146776BUCKING
Solar/Wind Harmer
0.046
3147983MERCK5
Solar/Wind Harmer
0.042
3146926FARMVIL
Solar/Wind Harmer
0.055
3143336POWHATN
Solar/Wind Harmer
1.223
971563AH1-280 GEN
Solar/Wind Harmer
0.691
970685AG2-442 GEN
Solar/Wind Harmer
4.622
962751AG1-124 GEN
Solar/Wind Harmer
2.727
316192AB2-158 GEN
Solar/Wind Helper
3.084
3147666LOUISA
Solar/Wind Helper
1.774
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.864
MECLTFEXP_MEC->PJM
CLTF
2.058
SIGELTFEXP_SIGE->PJM
CLTF
0.066
CPLELTFEXP_CPLE->PJM
CLTF
2.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.881
LAGNLTFEXP_LAGN->PJM
CLTF
3.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.798
TVALTFEXP_TVA->PJM
CLTF
1.628
NYPJM->LTFIMP_NY
CLTF
0.866
LGEELTFEXP_LGEE->PJM
CLTF
0.866
WECLTFEXP_WEC->PJM
CLTF
0.431

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.68 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4085.15
MW Contribution:
3.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.229
970413AG2-270 GEN
50/50
26.189
3144293JTRSVLE
50/50
0.671
3151261ROARAP2
50/50
0.282
3151391GASTONA
50/50
0.606
3151411GASTONB
50/50
0.606
944011AF1-069 GEN
Solar/Wind Harmer
22.157
970917AG2-570 GEN
Solar/Wind Harmer
86.288
3146926FARMVIL
Solar/Wind Harmer
-0.019
315242AE2-183_GT2
50/50
5.363
315241AE2-183_GT1
50/50
5.349
972185AH1-677 GEN
50/50
19.387
3151041BRUNSWICKG3
50/50
4.229
972187AH1-678 GEN
50/50
9.703
970909AG2-566 GEN
50/50
3.042
3144293JTRSVLE
50/50
0.671
970535AG2-341 GEN
50/50
4.397
3151581KERR 1
50/50
0.179
3151261ROARAP2
50/50
0.275
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.808
3151371ROSEMS1
50/50
0.501
3151381ROSEMG2
50/50
0.379
3146776BUCKING
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
12.856
316478AD1-087 GEN
Solar/Wind Harmer
2.718
942461AE2-259 GEN
Solar/Wind Harmer
4.631
3147133PAMPLIN
Solar/Wind Harmer
-0.094
959311AF2-222 GEN
Solar/Wind Harmer
30.36
970257AG2-171 GEN
Solar/Wind Harmer
10.863
971775AH1-396 GEN
Solar/Wind Harmer
2.044
964241AG1-285 GEN
Solar/Wind Harmer
22.168
3147043LAWRENC
Solar/Wind Harmer
-0.016
966621AG1-532 GEN
Solar/Wind Harmer
0.54
316181AB2-040 GEN
Solar/Wind Harmer
3.647
944581AF1-123 GEN
Solar/Wind Harmer
117.24
944601AF1-125 GEN
Solar/Wind Harmer
115.41
316190AA2-174 GEN
Solar/Wind Harmer
0.314
316011AB1-132 GEN
Solar/Wind Harmer
5.321
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
316017AA1-139 ULT1
Solar/Wind Harmer
2.042
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
2.925
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
316320Y1-086
Solar/Wind Harmer
1.474
3156081AA2-088 GEN
Solar/Wind Harmer
8.16
3142956BIRDNECK
Solar/Wind Harmer
1.349
316321Z2-027
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316305AF2-043 C
Solar/Wind Harmer
0.752
316246AF1-032 C
Solar/Wind Harmer
0.505
3151101ELIZAR3
Adder
20.667
970933AG2-581 GEN
Solar/Wind Harmer
33.318
970099AG2-077 GEN
Solar/Wind Harmer
41.272
970301AG2-198 GEN
Solar/Wind Harmer
16.023
3146776BUCKING
Solar/Wind Harmer
-0.126
3146776BUCKING
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
958211AF2-115 GEN
Solar/Wind Harmer
4.651
315687AD1-152 GEN
Solar/Wind Harmer
3.504
970323AG2-213 GEN
Solar/Wind Harmer
14.484
313527AB2-043 GEN
Solar/Wind Harmer
4.554
3144356SAPONY
Solar/Wind Harmer
0.978
316315AB2-025 C
Solar/Wind Harmer
0.754
316237AB2-079_GEN
Solar/Wind Harmer
0.84
962561AG1-105 GEN
Solar/Wind Harmer
14.998
316365GEN2_N
Solar/Wind Harmer
1.781
964791AG1-342 GEN
Solar/Wind Harmer
5.642
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
313506AB2-031 GEN
Solar/Wind Harmer
2.1
316294AC1-161 GEN
Solar/Wind Harmer
8.423
316118AC1-105 GEN
Solar/Wind Harmer
1.771
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
0.214
3145783HORNRTN
Solar/Wind Harmer
3.038
3145783HORNRTN
Solar/Wind Harmer
2.43
3145783HORNRTN
Solar/Wind Harmer
0.759
3145783HORNRTN
Solar/Wind Harmer
0.304
962571AG1-106 GEN
Solar/Wind Harmer
3.662
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.101
3145506HICKORY
Solar/Wind Harmer
-0.061
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.666
316339AD2-160 GEN
Solar/Wind Harmer
1.702
316388AE2-253 GEN
Solar/Wind Harmer
1.702
3137176SLIGO L2192
Solar/Wind Harmer
-0.1
3146456SLIGO L269
Solar/Wind Harmer
2.985
3130086AYDLETT
Solar/Wind Harmer
-0.101
316248AF1-058 C
Solar/Wind Harmer
0.759
3145796HORNRTN
Solar/Wind Harmer
-0.075
3146386ELIZ CT
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.7
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.538
316433W1029_GEN2
Solar/Wind Harmer
4.538
316435W1029_GEN3
Solar/Wind Harmer
4.538
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315244AE2-183_ST
50/50
9.313
963041AG1-153 GEN
50/50
8.562
3151541CLOVER2
50/50
5.968
315779AE2-040
50/50
3.484
3151601KERR 3
50/50
0.501
3151611KERR 4
50/50
0.501
3151621KERR 5
50/50
0.501
3151631KERR 6
50/50
0.501
3151281ROARAP4
50/50
0.256
970533AG2-339 GEN
Solar/Wind Harmer
25.362
970673AG2-436 GEN
Solar/Wind Harmer
81.518
971967AH1-528 GEN
Solar/Wind Harmer
68.252
970085AG2-068 GEN
Solar/Wind Harmer
21.238
970581AG2-369 GEN
Solar/Wind Harmer
18.265
316322AB2-045
Solar/Wind Harmer
1.062
971845AH1-439 GEN
Solar/Wind Harmer
16.816
316486AD2-202 GEN
Solar/Wind Harmer
0.796
946301AF1-294 GEN
Solar/Wind Harmer
7.628
961791AG1-021 GEN
Solar/Wind Harmer
3.721
970683AG2-441 GEN
Solar/Wind Harmer
20.75
970681AG2-440 GEN
Solar/Wind Harmer
13.772
3144303KENBRDG
Solar/Wind Harmer
-0.023
315814AE2-033 C
Solar/Wind Harmer
26.043
316238AB2-078_GEN
Solar/Wind Harmer
0.84
316239AB2-077_GEN
Solar/Wind Harmer
0.84
970831AG2-522 GEN
Solar/Wind Harmer
13.396
946281AF1-292 GEN
Solar/Wind Harmer
0.596
3137643SOCKMAN
Solar/Wind Harmer
-0.103
316426AA2-053 GEN
Solar/Wind Harmer
2.579
3146043SEABORD
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.662
316018AA1-139 ULT2
Solar/Wind Harmer
2.162
957871AF2-081 GEN
Solar/Wind Harmer
12.65
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
313526AB2-022
Solar/Wind Harmer
0.677
3146396TANGLEW
Solar/Wind Harmer
0.462
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
316316AC1-027 C
Solar/Wind Harmer
0.769
316318V4-068
Solar/Wind Harmer
0.625
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3151081ELIZAR1
Adder
20.406
315243AE2-183_GT3
50/50
5.363
3151051BRUNSWICKS1
50/50
8.78
3151021BRUNSWICKG1
50/50
4.229
971451AH1-221 GEN
50/50
12.843
3151531CLOVER1
50/50
6.014
3144293JTRSVLE
50/50
0.671
3144293JTRSVLE
50/50
0.53
3151591KERR 2
50/50
0.501
3151641KERR 7
50/50
0.501
3147043LAWRENC
50/50
2.31
3151281ROARAP4
50/50
0.274
3151391GASTONA
50/50
0.606
3151411GASTONB
50/50
0.606
941031AE2-094 GEN
Solar/Wind Harmer
70.715
940641AE2-051 GEN
Solar/Wind Harmer
34.508
970919AG2-571 GEN
Solar/Wind Harmer
10.922
970087AG2-069 GEN
Solar/Wind Harmer
31.857
939411AE1-173 GEN
Solar/Wind Harmer
169.831
957481AF2-042 GEN
Solar/Wind Harmer
103.181
315693AD1-088 GEN
Solar/Wind Harmer
16.286
3146926FARMVIL
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.013
971563AH1-280 GEN
Solar/Wind Harmer
3.721
970685AG2-442 GEN
Solar/Wind Harmer
25.864
316034AC1-036 C
Solar/Wind Harmer
0.536
315785AD2-033 C
Solar/Wind Harmer
6.517
316131AB2-060 GEN
Solar/Wind Harmer
3.025
971065AG2-659 GEN
Solar/Wind Harmer
13.518
316129AC1-054 GEN
Solar/Wind Harmer
2.354
960081AF2-299 GEN
Solar/Wind Harmer
2.991
316023GEN1_S
Solar/Wind Harmer
1.781
970401AG2-262 GEN
Solar/Wind Harmer
1.724
316087AB2-174 GEN
Solar/Wind Harmer
3.747
315773AC2-141 GEN
Solar/Wind Harmer
10.899
944591AF1-124 GEN
Solar/Wind Harmer
117.662
3145783HORNRTN
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.572
3146456SLIGO L269
Solar/Wind Harmer
-0.025
319010AE1-072 C
Solar/Wind Harmer
5.101
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.744
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
3151091ELIZAR2
Adder
20.051
315800Z1-036_GEN1
Solar/Wind Harmer
6.164
316463AE2-346 GEN
Solar/Wind Harmer
0.402
3145513AHOSKIE
Solar/Wind Harmer
0.217
961941AG1-037 GEN
Solar/Wind Harmer
0.187
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
316274AC1-208 GEN
Solar/Wind Harmer
2.665
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.827
3146033SCOT NK
Solar/Wind Harmer
-0.098
315732AD1-074 GEN1
Solar/Wind Harmer
4.993
315733AD1-074 GEN2
Solar/Wind Harmer
4.993
316210AC1-098 GEN
Solar/Wind Harmer
3.867
316327AA2-057 GEN
Solar/Wind Harmer
2.445
316174AB2-169 GEN
Solar/Wind Harmer
3.736
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
957861AF2-080 GEN
Solar/Wind Harmer
10.406
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
11.782
315833AF1-017_GEN
Solar/Wind Harmer
4.431
3143316POE
Solar/Wind Harmer
-0.086
970657AG2-426 GEN
Solar/Wind Harmer
1.359
316236AE1-162_GEN
Solar/Wind Harmer
0.645
971445AH1-216 GEN
Solar/Wind Harmer
13.157
3151201GRAVEL4
Adder
12.508
3151221GRAVEL6
Adder
12.494
3151191GRAVEL3
Adder
12.35
3151211GRAVEL5
Adder
12.35
270455AD2-022 GEN
Solar/Wind Harmer
3.349
270457AD2-023 GEN
Solar/Wind Harmer
1.698
315839AE2-212 C
Solar/Wind Harmer
0.492
315697AD1-025 GEN
Solar/Wind Harmer
3.238
957831AF2-077 GEN
Solar/Wind Harmer
0.437
3138283WHITEMARSH
Solar/Wind Harmer
0.022
316382AG1-145 C
Solar/Wind Harmer
0.436
316159AE1-175 C
Solar/Wind Harmer
0.388
316258AE1-075 C
Solar/Wind Helper
0.481
316405AF2-144 C
Solar/Wind Helper
0.401
316233AE1-074 FULL
Solar/Wind Helper
0.35
3146173TUNIS
Solar/Wind Harmer
-0.025
3146376EDENTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316317KELFORD C
Solar/Wind Harmer
1.148
3145823KELFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.025
315735AD1-075 GEN1
Solar/Wind Harmer
2.495
316212AC1-099_GEN
Solar/Wind Harmer
2.148
315722AD1-056 GEN
Solar/Wind Harmer
8.68
3145963POPLR C
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
0.502
3146233WITAKRS
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.024
3138543CONSLDL
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316003AC1-222 GEN
Solar/Wind Harmer
2.319
316420AA1-050 GEN
Solar/Wind Harmer
2.708
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.437
316222AC1-221 GEN
Solar/Wind Harmer
2.254
316283AC2-100 C
Solar/Wind Harmer
2.091
971683AH1-343 GEN
Solar/Wind Harmer
9.57
970657AG2-426 GEN
Solar/Wind Harmer
4.354
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.544
3151171GRAVELC
Adder
2.404
316123AC1-075 GEN
Solar/Wind Harmer
2.012
3144216WINCHST
Adder
0.613
3150921YORKTN3
Adder
4.042
961611AG1-000B GEN
Solar/Wind Harmer
3.8
315778AD1-151 GEN
Solar/Wind Harmer
13.575
316458AB2-190 GEN2
Solar/Wind Harmer
1.423
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
316140AB2-099
Solar/Wind Harmer
0.168
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
3150991CHESPKB
Adder
2.321
3150991CHESPKB
Adder
2.265
315742AE1-103 GEN
Solar/Wind Harmer
5.898
315614AA2-178 GEN
Solar/Wind Harmer
2.672
316065AD1-022 GEN
Solar/Wind Harmer
12.372
315835AF2-110_GEN
Solar/Wind Harmer
3.074
315724AD1-057 GEN
Solar/Wind Harmer
4.774
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
316005AA1-067
Solar/Wind Harmer
0.481
3145493TOT1
Solar/Wind Harmer
0.367
3145453TOT5
Solar/Wind Harmer
0.22
3145603CNETO
Solar/Wind Harmer
0.147
316049AB1-081 GEN
Solar/Wind Harmer
2.554
316263AC1-034 GEN
Solar/Wind Harmer
11.125
961601AG1-000A GEN
Solar/Wind Harmer
9.319
316349AD2-085 GEN
Solar/Wind Harmer
2.072
316083AB2-161 GEN
Solar/Wind Harmer
3.461
942751AE2-291 GEN
Solar/Wind Harmer
10.866
316033AB2-134 GEN
Solar/Wind Harmer
5.167
270013AE1-250 PV
Solar/Wind Harmer
2.007
316240AF1-291 C
Solar/Wind Harmer
0.388
316313AB2-026
Solar/Wind Helper
0.534
316045AC1-158 PL2
Solar/Wind Helper
4.257
316450AC1-158 RIC
Solar/Wind Helper
0.355
3143526WINTERP
Solar/Wind Helper
1.193
3146173TUNIS
Solar/Wind Harmer
-0.025
315611Z1-036_GEN2
Solar/Wind Harmer
6.164
3130156CHOWAN
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.609
316036AC1-147 C
Solar/Wind Harmer
0.67
3150981CHESPKA
Adder
2.766
3145683EARLEYS
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.004
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.279
3145823KELFORD
Solar/Wind Harmer
-0.025
3156021HOLLOMANSOL
Solar/Wind Harmer
3.327
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.187
315737AD1-076 GEN
Solar/Wind Harmer
4.693
316093AE2-104_GEN
Solar/Wind Harmer
7.15
3145963POPLR C
Solar/Wind Harmer
-0.024
316319Z2-044 C
Solar/Wind Harmer
1.326
3146233WITAKRS
Solar/Wind Harmer
-0.095
3146293MARTNCO
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316494AC1-189 GEN
Solar/Wind Harmer
2.559
961671AG1-007 GEN
Solar/Wind Harmer
0.3
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.705
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.192
3142053HEARTS
Solar/Wind Harmer
0.279
316072AD1-144
Solar/Wind Harmer
0.476
3145336SMITFLD
Solar/Wind Harmer
-0.085
316381AD1-082 GEN
Solar/Wind Harmer
1.951
3151171GRAVELC
Adder
1.828
3138126ROCKLANDING
Solar/Wind Harmer
0.056
961611AG1-000B GEN
Solar/Wind Harmer
8.906
971317AH1-138 GEN
Solar/Wind Harmer
2.061
316369SG1_INVT
Solar/Wind Harmer
2.862
971069AG2-661 GEN
Solar/Wind Harmer
2.413
315671AE2-027_GEN
Solar/Wind Harmer
2.578
316132AB2-190 GEN1
Solar/Wind Harmer
1.423
970223AG2-152 GEN
Solar/Wind Harmer
12.166
270016AE1-250 BESS
Solar/Wind Harmer
2.007
3143226MDLTHAN
Solar/Wind Helper
0.35
316447AC1-158 HLD
Solar/Wind Helper
2.927
316044AC1-158 PL1
Solar/Wind Helper
1.33
3143526WINTERP
Solar/Wind Helper
1.193
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.044
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.621
MECLTFEXP_MEC->PJM
CLTF
4.569
SIGELTFEXP_SIGE->PJM
CLTF
0.136
CPLELTFEXP_CPLE->PJM
CLTF
14.696
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.799
LAGNLTFEXP_LAGN->PJM
CLTF
9.773
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.451
TVALTFEXP_TVA->PJM
CLTF
4.879
NYPJM->LTFIMP_NY
CLTF
2.278
LGEELTFEXP_LGEE->PJM
CLTF
1.626
WECLTFEXP_WEC->PJM
CLTF
0.836

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 298_SRT-A-4


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 298_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.61 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3336.6
MW Contribution:
3.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
5.456
315241AE2-183_GT1
50/50
5.441
972185AH1-677 GEN
50/50
19.722
3151041BRUNSWICKG3
50/50
4.302
972187AH1-678 GEN
50/50
9.87
970909AG2-566 GEN
50/50
3.093
3144293JTRSVLE
50/50
0.682
970535AG2-341 GEN
50/50
4.471
3151581KERR 1
50/50
0.182
3151261ROARAP2
50/50
0.281
3152661PLYWOOD A
50/50
0.515
3151361ROSEMG1
50/50
0.826
3151371ROSEMS1
50/50
0.511
3151381ROSEMG2
50/50
0.386
970933AG2-581 GEN
Solar/Wind Harmer
25.738
970099AG2-077 GEN
Solar/Wind Harmer
31.87
970301AG2-198 GEN
Solar/Wind Harmer
12.373
3146776BUCKING
Solar/Wind Harmer
1.145
3146776BUCKING
Solar/Wind Harmer
0.093
3147133PAMPLIN
Solar/Wind Harmer
0.272
3147133PAMPLIN
Solar/Wind Harmer
0.217
958211AF2-115 GEN
Solar/Wind Harmer
3.232
970323AG2-213 GEN
Solar/Wind Harmer
11.184
3144356SAPONY
Solar/Wind Harmer
2.139
316315AB2-025 C
Solar/Wind Harmer
0.205
316365GEN2_N
Solar/Wind Harmer
0.535
962561AG1-105 GEN
Solar/Wind Harmer
11.564
964791AG1-342 GEN
Solar/Wind Harmer
4.581
3146843MT LREL
Solar/Wind Harmer
0.238
3146843MT LREL
Solar/Wind Harmer
0.238
316294AC1-161 GEN
Solar/Wind Harmer
4.107
313506AB2-031 GEN
Solar/Wind Harmer
0.73
3145593CAROLNA
Solar/Wind Harmer
0.234
3145593CAROLNA
Solar/Wind Harmer
0.234
3145593CAROLNA
Solar/Wind Harmer
0.291
316118AC1-105 GEN
Solar/Wind Harmer
0.597
3145783HORNRTN
Solar/Wind Harmer
4.134
3145783HORNRTN
Solar/Wind Harmer
3.307
3145783HORNRTN
Solar/Wind Harmer
1.033
3145783HORNRTN
Solar/Wind Harmer
0.413
962571AG1-106 GEN
Solar/Wind Harmer
3.294
3145506HICKORY
Solar/Wind Harmer
0.925
3145506HICKORY
Solar/Wind Harmer
0.555
3145506HICKORY
Solar/Wind Harmer
0.139
316339AD2-160 GEN
Solar/Wind Harmer
0.37
316388AE2-253 GEN
Solar/Wind Harmer
0.719
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3142666NORTHAMPTON
Solar/Wind Harmer
0.139
3137176SLIGO L2192
Solar/Wind Harmer
0.918
3146456SLIGO L269
Solar/Wind Harmer
4.084
3130086AYDLETT
Solar/Wind Harmer
0.922
3146386ELIZ CT
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.687
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3151031BRUNSWICKG2
50/50
4.302
970413AG2-270 GEN
50/50
26.618
3144293JTRSVLE
50/50
0.682
3151261ROARAP2
50/50
0.288
3151391GASTONA
50/50
0.619
3151411GASTONB
50/50
0.619
944011AF1-069 GEN
Solar/Wind Harmer
20.553
970917AG2-570 GEN
Solar/Wind Harmer
27.771
3146926FARMVIL
Solar/Wind Harmer
0.172
3146776BUCKING
Solar/Wind Harmer
0.103
972003AH1-546 GEN
Solar/Wind Harmer
9.927
316478AD1-087 GEN
Solar/Wind Harmer
0.986
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.853
959311AF2-222 GEN
Solar/Wind Harmer
23.396
970257AG2-171 GEN
Solar/Wind Harmer
8.388
971775AH1-396 GEN
Solar/Wind Harmer
0.419
964241AG1-285 GEN
Solar/Wind Harmer
17.117
3147043LAWRENC
Solar/Wind Harmer
0.147
316181AB2-040 GEN
Solar/Wind Harmer
0.339
944581AF1-123 GEN
Solar/Wind Harmer
52.976
944601AF1-125 GEN
Solar/Wind Harmer
52.16
316011AB1-132 GEN
Solar/Wind Harmer
4.2
316017AA1-139 ULT1
Solar/Wind Harmer
0.123
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3146456SLIGO L269
Solar/Wind Harmer
0.231
971153AH1-033 GEN
Solar/Wind Harmer
2.668
316321Z2-027
Solar/Wind Harmer
0.041
3145796HORNRTN
Solar/Wind Harmer
0.916
3145796HORNRTN
Solar/Wind Harmer
0.229
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.229
3151101ELIZAR3
Adder
21.22
316246AF1-032 C
Solar/Wind Harmer
0.102
3146263WOODLND
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.382
3145893MURPHYS
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.228
3144873MCLAUGH
Solar/Wind Harmer
0.006
3146173TUNIS
Solar/Wind Harmer
0.227
3146376EDENTON
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.169
3145823KELFORD
Solar/Wind Harmer
0.225
3146206CASHIE
Solar/Wind Harmer
0.225
315735AD1-075 GEN1
Solar/Wind Harmer
0.641
316212AC1-099_GEN
Solar/Wind Harmer
1.156
3145963POPLR C
Solar/Wind Harmer
0.221
315722AD1-056 GEN
Solar/Wind Harmer
7.652
3144536CHRHLND
Solar/Wind Harmer
0.033
3145933PARMELE
Solar/Wind Harmer
0.218
3146233WITAKRS
Solar/Wind Harmer
1.093
3146233WITAKRS
Solar/Wind Harmer
0.148
3138543CONSLDL
Solar/Wind Harmer
0.143
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
3146073TAR RVR
Solar/Wind Harmer
0.215
3146083TARBORO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
971623AH1-311 GEN
Solar/Wind Harmer
0.43
961601AG1-000A GEN
Solar/Wind Harmer
15.286
316222AC1-221 GEN
Solar/Wind Harmer
0.83
316283AC2-100 C
Solar/Wind Harmer
0.392
971683AH1-343 GEN
Solar/Wind Harmer
7.339
970657AG2-426 GEN
Solar/Wind Harmer
4.45
3145336SMITFLD
Solar/Wind Harmer
0.079
315813AE1-149 C
Solar/Wind Harmer
9.892
3151171GRAVELC
Adder
2.494
3144216WINCHST
Adder
0.635
961611AG1-000B GEN
Solar/Wind Harmer
4.458
316123AC1-075 GEN
Solar/Wind Harmer
0.223
3150921YORKTN3
Adder
4.193
315778AD1-151 GEN
Solar/Wind Harmer
11.415
316458AB2-190 GEN2
Solar/Wind Harmer
0.707
970133AG2-095 GEN
Solar/Wind Harmer
1.1
3147666LOUISA
Solar/Wind Helper
0.521
315244AE2-183_ST
50/50
9.474
963041AG1-153 GEN
50/50
8.709
3151541CLOVER2
50/50
6.065
315779AE2-040
50/50
3.569
3151601KERR 3
50/50
0.509
3151611KERR 4
50/50
0.509
3151621KERR 5
50/50
0.509
3151631KERR 6
50/50
0.509
3151281ROARAP4
50/50
0.262
970533AG2-339 GEN
Solar/Wind Harmer
25.805
970673AG2-436 GEN
Solar/Wind Harmer
41.993
971967AH1-528 GEN
Solar/Wind Harmer
52.591
970085AG2-068 GEN
Solar/Wind Harmer
16.403
970581AG2-369 GEN
Solar/Wind Harmer
14.107
971845AH1-439 GEN
Solar/Wind Harmer
12.985
316486AD2-202 GEN
Solar/Wind Harmer
0.29
946301AF1-294 GEN
Solar/Wind Harmer
5.315
961791AG1-021 GEN
Solar/Wind Harmer
2.586
970683AG2-441 GEN
Solar/Wind Harmer
16.022
970681AG2-440 GEN
Solar/Wind Harmer
10.634
3144303KENBRDG
Solar/Wind Harmer
0.209
315814AE2-033 C
Solar/Wind Harmer
20.173
970831AG2-522 GEN
Solar/Wind Harmer
10.363
3137643SOCKMAN
Solar/Wind Harmer
0.942
316426AA2-053 GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
0.232
315652AC1-086 GEN
Solar/Wind Harmer
25.468
957871AF2-081 GEN
Solar/Wind Harmer
11.5
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.123
3146396TANGLEW
Solar/Wind Harmer
0.632
316316AC1-027 C
Solar/Wind Harmer
0.219
3145176PASQUOTANK
Solar/Wind Harmer
0.142
3145796HORNRTN
Solar/Wind Harmer
0.733
3145796HORNRTN
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.228
3146486SUNBURY
Solar/Wind Harmer
0.228
3151081ELIZAR1
Adder
20.952
3151091ELIZAR2
Adder
20.588
3145893MURPHYS
Solar/Wind Harmer
0.616
3145893MURPHYS
Solar/Wind Harmer
0.228
3147173SINAI
Solar/Wind Harmer
0.227
3147243WELCO
Solar/Wind Harmer
0.142
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
316463AE2-346 GEN
Solar/Wind Harmer
0.194
3145513AHOSKIE
Solar/Wind Harmer
0.474
3145513AHOSKIE
Solar/Wind Harmer
0.227
3145683EARLEYS
Solar/Wind Harmer
0.453
3145683EARLEYS
Solar/Wind Harmer
0.226
3145683EARLEYS
Solar/Wind Harmer
0.226
3130546PLYMOUTH
Solar/Wind Harmer
0.225
3146206CASHIE
Solar/Wind Harmer
0.225
970601AG2-382 GEN
Solar/Wind Harmer
8.412
315732AD1-074 GEN1
Solar/Wind Harmer
1.284
315733AD1-074 GEN2
Solar/Wind Harmer
1.284
316274AC1-208 GEN
Solar/Wind Harmer
1.159
3146033SCOT NK
Solar/Wind Harmer
0.899
316210AC1-098 GEN
Solar/Wind Harmer
2.073
316327AA2-057 GEN
Solar/Wind Harmer
0.325
3145746EVERETS
Solar/Wind Harmer
0.861
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
957861AF2-080 GEN
Solar/Wind Harmer
9.306
3145573BETHELC
Solar/Wind Harmer
0.215
3145573BETHELC
Solar/Wind Harmer
0.215
316311AC2-079 GEN
Solar/Wind Harmer
6.146
3143316POE
Solar/Wind Harmer
0.802
970657AG2-426 GEN
Solar/Wind Harmer
1.456
971445AH1-216 GEN
Solar/Wind Harmer
13.765
3151201GRAVEL4
Adder
12.976
3151221GRAVEL6
Adder
12.961
3151191GRAVEL3
Adder
12.811
3151211GRAVEL5
Adder
12.811
315697AD1-025 GEN
Solar/Wind Harmer
0.161
3138283WHITEMARSH
Solar/Wind Harmer
0.031
316159AE1-175 C
Solar/Wind Harmer
0.116
316258AE1-075 C
Solar/Wind Helper
0.347
316405AF2-144 C
Solar/Wind Helper
0.289
3145893MURPHYS
Solar/Wind Harmer
1.528
3145893MURPHYS
Solar/Wind Harmer
0.411
3146626S HERTFORD
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.228
3150991CHESPKB
Adder
2.383
3150991CHESPKB
Adder
2.326
3146173TUNIS
Solar/Wind Harmer
0.227
3146173TUNIS
Solar/Wind Harmer
0.227
3146376EDENTON
Solar/Wind Harmer
1.01
3146376EDENTON
Solar/Wind Harmer
1.01
316140AB2-099
Solar/Wind Harmer
0.081
315742AE1-103 GEN
Solar/Wind Harmer
3.386
315614AA2-178 GEN
Solar/Wind Harmer
1.287
316065AD1-022 GEN
Solar/Wind Harmer
10.374
315835AF2-110_GEN
Solar/Wind Harmer
1.542
315724AD1-057 GEN
Solar/Wind Harmer
4.269
3145933PARMELE
Solar/Wind Harmer
0.436
3145933PARMELE
Solar/Wind Harmer
0.218
316005AA1-067
Solar/Wind Harmer
0.231
3145493TOT1
Solar/Wind Harmer
0.499
3145453TOT5
Solar/Wind Harmer
0.3
3145603CNETO
Solar/Wind Harmer
0.2
316049AB1-081 GEN
Solar/Wind Harmer
1.224
316263AC1-034 GEN
Solar/Wind Harmer
8.177
961601AG1-000A GEN
Solar/Wind Harmer
3.821
316349AD2-085 GEN
Solar/Wind Harmer
0.143
942751AE2-291 GEN
Solar/Wind Harmer
8.254
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316313AB2-026
Solar/Wind Helper
0.386
316045AC1-158 PL2
Solar/Wind Helper
4.173
316450AC1-158 RIC
Solar/Wind Helper
0.348
315243AE2-183_GT3
50/50
5.456
3151051BRUNSWICKS1
50/50
8.931
3151021BRUNSWICKG1
50/50
4.302
971451AH1-221 GEN
50/50
13.064
3151531CLOVER1
50/50
6.112
3144293JTRSVLE
50/50
0.682
3144293JTRSVLE
50/50
0.539
3151591KERR 2
50/50
0.509
3151641KERR 7
50/50
0.509
3147043LAWRENC
50/50
2.356
3151281ROARAP4
50/50
0.28
3151391GASTONA
50/50
0.619
3151411GASTONB
50/50
0.619
941031AE2-094 GEN
Solar/Wind Harmer
62.902
940641AE2-051 GEN
Solar/Wind Harmer
26.697
970919AG2-571 GEN
Solar/Wind Harmer
11.108
939411AE1-173 GEN
Solar/Wind Harmer
131.566
970087AG2-069 GEN
Solar/Wind Harmer
24.605
957481AF2-042 GEN
Solar/Wind Harmer
79.674
315693AD1-088 GEN
Solar/Wind Harmer
14.148
3146926FARMVIL
Solar/Wind Harmer
0.172
3146776BUCKING
Solar/Wind Harmer
0.115
971563AH1-280 GEN
Solar/Wind Harmer
2.873
970685AG2-442 GEN
Solar/Wind Harmer
19.971
316034AC1-036 C
Solar/Wind Harmer
0.017
315785AD2-033 C
Solar/Wind Harmer
2.108
316131AB2-060 GEN
Solar/Wind Harmer
0.791
971065AG2-659 GEN
Solar/Wind Harmer
10.452
316129AC1-054 GEN
Solar/Wind Harmer
0.911
960081AF2-299 GEN
Solar/Wind Harmer
2.32
316023GEN1_S
Solar/Wind Harmer
0.535
970401AG2-262 GEN
Solar/Wind Harmer
1.4
315773AC2-141 GEN
Solar/Wind Harmer
8.676
944591AF1-124 GEN
Solar/Wind Harmer
53.164
3145783HORNRTN
Solar/Wind Harmer
0.232
315607AA1-063A GEN
Solar/Wind Harmer
0.467
3146456SLIGO L269
Solar/Wind Harmer
0.231
319010AE1-072 C
Solar/Wind Harmer
1.151
3145796HORNRTN
Solar/Wind Harmer
0.756
3145796HORNRTN
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.741
3146516WINFALL
Solar/Wind Harmer
0.229
3146263WOODLND
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.913
3145893MURPHYS
Solar/Wind Harmer
1.015
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.04
3150981CHESPKA
Adder
2.841
3146173TUNIS
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
3145683EARLEYS
Solar/Wind Harmer
0.226
315816AE2-034 GEN
Solar/Wind Harmer
0.965
3145663CRESWEL
Solar/Wind Harmer
0.633
971163AH1-040 GEN
Solar/Wind Harmer
18.103
3145823KELFORD
Solar/Wind Harmer
0.225
3156021HOLLOMANSOL
Solar/Wind Harmer
1.014
3146206CASHIE
Solar/Wind Harmer
0.225
971547AH1-271 GEN
Solar/Wind Harmer
4.807
315737AD1-076 GEN
Solar/Wind Harmer
2.89
316093AE2-104_GEN
Solar/Wind Harmer
3.78
3145963POPLR C
Solar/Wind Harmer
0.221
3146293MARTNCO
Solar/Wind Harmer
0.202
3146233WITAKRS
Solar/Wind Harmer
0.866
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
316494AC1-189 GEN
Solar/Wind Harmer
0.729
316072AD1-144
Solar/Wind Harmer
0.077
961671AG1-007 GEN
Solar/Wind Harmer
0.033
3146083TARBORO
Solar/Wind Harmer
0.215
3145493TOT1
Solar/Wind Harmer
0.958
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.379
3145336SMITFLD
Solar/Wind Harmer
0.789
316381AD1-082 GEN
Solar/Wind Harmer
0.199
3151171GRAVELC
Adder
1.896
3138126ROCKLANDING
Solar/Wind Harmer
0.077
961611AG1-000B GEN
Solar/Wind Harmer
8.768
971317AH1-138 GEN
Solar/Wind Harmer
1.141
971069AG2-661 GEN
Solar/Wind Harmer
2.537
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316132AB2-190 GEN1
Solar/Wind Harmer
0.707
970223AG2-152 GEN
Solar/Wind Harmer
8.528
3143226MDLTHAN
Solar/Wind Helper
0.314
316447AC1-158 HLD
Solar/Wind Helper
2.869
316044AC1-158 PL1
Solar/Wind Helper
1.304
3147666LOUISA
Solar/Wind Helper
0.907
316192AB2-158 GEN
Solar/Wind Helper
1.512
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.5
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.568
MECLTFEXP_MEC->PJM
CLTF
4.516
SIGELTFEXP_SIGE->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
14.89
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.544
LAGNLTFEXP_LAGN->PJM
CLTF
9.765
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.758
TVALTFEXP_TVA->PJM
CLTF
4.87
NYPJM->LTFIMP_NY
CLTF
2.256
LGEELTFEXP_LGEE->PJM
CLTF
1.597
WECLTFEXP_WEC->PJM
CLTF
0.821

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.8 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3471.53
MW Contribution:
2.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
3.762
970413AG2-270 GEN
50/50
23.545
3151921BEARGRDN G2
50/50
2.284
3144293JTRSVLE
50/50
0.607
3151101ELIZAR3
50/50
22.881
944011AF1-069 GEN
Solar/Wind Harmer
17.916
3143336POWHATN
Solar/Wind Harmer
4.447
970917AG2-570 GEN
Solar/Wind Harmer
24.36
316478AD1-087 GEN
Solar/Wind Harmer
0.872
3146926FARMVIL
Solar/Wind Harmer
0.15
3146776BUCKING
Solar/Wind Harmer
0.089
972003AH1-546 GEN
Solar/Wind Harmer
8.543
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.757
959311AF2-222 GEN
Solar/Wind Harmer
20.976
970257AG2-171 GEN
Solar/Wind Harmer
7.53
971775AH1-396 GEN
Solar/Wind Harmer
0.377
944581AF1-123 GEN
Solar/Wind Harmer
52.851
944601AF1-125 GEN
Solar/Wind Harmer
52.037
3147043LAWRENC
Solar/Wind Harmer
0.14
316017AA1-139 ULT1
Solar/Wind Harmer
0.124
3146456SLIGO L269
Solar/Wind Harmer
0.232
971153AH1-033 GEN
Solar/Wind Harmer
2.683
964241AG1-285 GEN
Solar/Wind Harmer
15.472
3144873MCLAUGH
Solar/Wind Harmer
0.006
316246AF1-032 C
Solar/Wind Harmer
0.103
316321Z2-027
Solar/Wind Harmer
0.041
316181AB2-040 GEN
Solar/Wind Harmer
0.327
970657AG2-426 GEN
Solar/Wind Harmer
5.164
315813AE1-149 C
Solar/Wind Harmer
12.255
3145273HOLLAND
Solar/Wind Harmer
0.172
3146516WINFALL
Solar/Wind Harmer
0.229
3146626S HERTFORD
Solar/Wind Harmer
0.229
3144536CHRHLND
Solar/Wind Harmer
0.034
316303AF2-085
50/50
5.8
315244AE2-183_ST
50/50
8.277
963041AG1-153 GEN
50/50
7.616
315779AE2-040
50/50
3.593
3151541CLOVER2
50/50
5.365
972205AH1-687 GEN
50/50
11.16
970533AG2-339 GEN
Solar/Wind Harmer
22.494
970673AG2-436 GEN
Solar/Wind Harmer
36.636
316258AE1-075 C
Solar/Wind Harmer
0.22
971967AH1-528 GEN
Solar/Wind Harmer
45.971
316233AE1-074 FULL
Solar/Wind Harmer
0.222
971281AH1-106 GEN
Solar/Wind Harmer
3.846
971283AH1-107 GEN
Solar/Wind Harmer
3.846
970085AG2-068 GEN
Solar/Wind Harmer
14.405
970581AG2-369 GEN
Solar/Wind Harmer
12.389
315814AE2-033 C
Solar/Wind Harmer
20.287
316486AD2-202 GEN
Solar/Wind Harmer
0.256
971845AH1-439 GEN
Solar/Wind Harmer
11.263
3143316POE
Solar/Wind Harmer
0.959
946301AF1-294 GEN
Solar/Wind Harmer
4.73
961791AG1-021 GEN
Solar/Wind Harmer
2.301
970683AG2-441 GEN
Solar/Wind Harmer
14.318
970681AG2-440 GEN
Solar/Wind Harmer
9.503
3144303KENBRDG
Solar/Wind Harmer
0.188
316316AC1-027 C
Solar/Wind Harmer
0.222
957871AF2-081 GEN
Solar/Wind Harmer
11.569
3151081ELIZAR1
Adder
21.29
3151091ELIZAR2
Adder
20.921
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.123
316311AC2-079 GEN
Solar/Wind Harmer
6.623
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
3146486SUNBURY
Solar/Wind Harmer
0.23
315242AE2-183_GT2
50/50
4.766
315241AE2-183_GT1
50/50
4.753
972185AH1-677 GEN
50/50
17.229
3151041BRUNSWICKG3
50/50
3.762
972187AH1-678 GEN
50/50
8.631
970909AG2-566 GEN
50/50
2.711
3144293JTRSVLE
50/50
0.607
971223AH1-071 GEN
Solar/Wind Harmer
3.48
316313AB2-026
Solar/Wind Harmer
0.183
316336AC2-165 C
Solar/Wind Harmer
14.486
970933AG2-581 GEN
Solar/Wind Harmer
22.534
3143526WINTERP
Solar/Wind Harmer
1.441
970099AG2-077 GEN
Solar/Wind Harmer
28.068
3144356SAPONY
Solar/Wind Harmer
2.153
316315AB2-025 C
Solar/Wind Harmer
0.206
970301AG2-198 GEN
Solar/Wind Harmer
10.843
3146776BUCKING
Solar/Wind Harmer
0.993
3146776BUCKING
Solar/Wind Harmer
0.08
3147133PAMPLIN
Solar/Wind Harmer
0.241
3147133PAMPLIN
Solar/Wind Harmer
0.193
958211AF2-115 GEN
Solar/Wind Harmer
2.876
316365GEN2_N
Solar/Wind Harmer
0.527
970323AG2-213 GEN
Solar/Wind Harmer
10.04
316294AC1-161 GEN
Solar/Wind Harmer
4.031
3145506HICKORY
Solar/Wind Harmer
0.931
3145506HICKORY
Solar/Wind Harmer
0.559
3145506HICKORY
Solar/Wind Harmer
0.14
316339AD2-160 GEN
Solar/Wind Harmer
0.372
316388AE2-253 GEN
Solar/Wind Harmer
0.723
3137176SLIGO L2192
Solar/Wind Harmer
0.924
3146456SLIGO L269
Solar/Wind Harmer
4.107
3130086AYDLETT
Solar/Wind Harmer
0.928
3150991CHESPKB
Adder
2.428
3150991CHESPKB
Adder
2.37
3146386ELIZ CT
Solar/Wind Harmer
0.231
315835AF2-110_GEN
Solar/Wind Harmer
1.585
316349AD2-085 GEN
Solar/Wind Harmer
0.154
313506AB2-031 GEN
Solar/Wind Harmer
0.706
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
315742AE1-103 GEN
Solar/Wind Harmer
3.42
3146626S HERTFORD
Solar/Wind Harmer
0.229
3146626S HERTFORD
Solar/Wind Harmer
0.229
3146376EDENTON
Solar/Wind Harmer
0.227
3156081AA2-088 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
4.095
3142666NORTHAMPTON
Solar/Wind Harmer
0.225
3145893MURPHYS
Solar/Wind Harmer
0.376
3145893MURPHYS
Solar/Wind Harmer
0.225
3150861SPRUNCD
Adder
1.031
3146173TUNIS
Solar/Wind Harmer
0.223
3146263WOODLND
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.891
3145796HORNRTN
Solar/Wind Harmer
0.223
315735AD1-075 GEN1
Solar/Wind Harmer
0.633
3146206CASHIE
Solar/Wind Harmer
0.222
3145336SMITFLD
Solar/Wind Harmer
0.088
970221AG2-151 GEN
Solar/Wind Harmer
11.762
3145823KELFORD
Solar/Wind Harmer
0.22
3145963POPLR C
Solar/Wind Harmer
0.216
316212AC1-099_GEN
Solar/Wind Harmer
1.115
3151171GRAVELC
Adder
2.999
315722AD1-056 GEN
Solar/Wind Harmer
7.361
961611AG1-000B GEN
Solar/Wind Harmer
5.65
3145933PARMELE
Solar/Wind Harmer
0.211
3145746EVERETS
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.209
3146233WITAKRS
Solar/Wind Harmer
1.044
3146486SUNBURY
Solar/Wind Harmer
0.23
970657AG2-426 GEN
Solar/Wind Harmer
1.69
970119AG2-088 GEN
50/50
43.5
315243AE2-183_GT3
50/50
4.766
3151051BRUNSWICKS1
50/50
7.809
3151021BRUNSWICKG1
50/50
3.762
971451AH1-221 GEN
50/50
11.423
3151531CLOVER1
50/50
5.406
3151931BEARGRDN S1
50/50
2.951
3151911BEARGRDN G1
50/50
2.284
3144293JTRSVLE
50/50
0.607
3144293JTRSVLE
50/50
0.479
3147043LAWRENC
50/50
2.238
3143226MDLTHAN
Solar/Wind Harmer
0.326
941031AE2-094 GEN
Solar/Wind Harmer
54.833
940641AE2-051 GEN
Solar/Wind Harmer
23.604
3143336POWHATN
Solar/Wind Harmer
5.231
939411AE1-173 GEN
Solar/Wind Harmer
119.295
3143526WINTERP
Solar/Wind Harmer
1.441
970919AG2-571 GEN
Solar/Wind Harmer
9.744
970087AG2-069 GEN
Solar/Wind Harmer
21.608
970937AG2-583 GEN
Solar/Wind Harmer
16.216
957481AF2-042 GEN
Solar/Wind Harmer
70.171
315693AD1-088 GEN
Solar/Wind Harmer
12.465
3146926FARMVIL
Solar/Wind Harmer
0.15
3146776BUCKING
Solar/Wind Harmer
0.099
971563AH1-280 GEN
Solar/Wind Harmer
2.557
970685AG2-442 GEN
Solar/Wind Harmer
17.812
316023GEN1_S
Solar/Wind Harmer
0.527
316034AC1-036 C
Solar/Wind Harmer
0.016
944591AF1-124 GEN
Solar/Wind Harmer
53.039
315785AD2-033 C
Solar/Wind Harmer
1.896
960081AF2-299 GEN
Solar/Wind Harmer
2.25
315773AC2-141 GEN
Solar/Wind Harmer
8.516
3146456SLIGO L269
Solar/Wind Harmer
0.232
319010AE1-072 C
Solar/Wind Harmer
1.157
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.041
3150981CHESPKA
Adder
2.895
316093AE2-104_GEN
Solar/Wind Harmer
3.885
316131AB2-060 GEN
Solar/Wind Harmer
0.718
316381AD1-082 GEN
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.743
3146516WINFALL
Solar/Wind Harmer
0.229
3146376EDENTON
Solar/Wind Harmer
1.008
3146376EDENTON
Solar/Wind Harmer
1.008
962571AG1-106 GEN
Solar/Wind Harmer
3.212
3145593CAROLNA
Solar/Wind Harmer
0.225
3145593CAROLNA
Solar/Wind Harmer
0.225
3145593CAROLNA
Solar/Wind Harmer
0.281
3142666NORTHAMPTON
Solar/Wind Harmer
0.225
3142666NORTHAMPTON
Solar/Wind Harmer
0.225
3142666NORTHAMPTON
Solar/Wind Harmer
0.225
3142666NORTHAMPTON
Solar/Wind Harmer
0.135
3145893MURPHYS
Solar/Wind Harmer
1.505
3145893MURPHYS
Solar/Wind Harmer
0.405
315614AA2-178 GEN
Solar/Wind Harmer
1.278
3145783HORNRTN
Solar/Wind Harmer
3.985
3145783HORNRTN
Solar/Wind Harmer
3.188
3145783HORNRTN
Solar/Wind Harmer
0.996
3145783HORNRTN
Solar/Wind Harmer
0.398
3146173TUNIS
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.668
316140AB2-099
Solar/Wind Harmer
0.079
316065AD1-022 GEN
Solar/Wind Harmer
10.239
962561AG1-105 GEN
Solar/Wind Harmer
10.504
964791AG1-342 GEN
Solar/Wind Harmer
4.162
3146843MT LREL
Solar/Wind Harmer
0.216
3146843MT LREL
Solar/Wind Harmer
0.216
315724AD1-057 GEN
Solar/Wind Harmer
4.106
316118AC1-105 GEN
Solar/Wind Harmer
0.542
3145933PARMELE
Solar/Wind Harmer
0.422
3145933PARMELE
Solar/Wind Harmer
0.211
316005AA1-067
Solar/Wind Harmer
0.223
316033AB2-134 GEN
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
98.88
3145493TOT1
Solar/Wind Harmer
0.478
3145453TOT5
Solar/Wind Harmer
0.287
3145603CNETO
Solar/Wind Harmer
0.191
316049AB1-081 GEN
Solar/Wind Harmer
1.166
316263AC1-034 GEN
Solar/Wind Harmer
7.789
961601AG1-000A GEN
Solar/Wind Harmer
3.643
3146233WITAKRS
Solar/Wind Harmer
0.141
3138543CONSLDL
Solar/Wind Harmer
0.137
315778AD1-151 GEN
Solar/Wind Harmer
16.516
3146073TAR RVR
Solar/Wind Harmer
0.206
3146083TARBORO
Solar/Wind Harmer
0.206
3145543BTLEBRO
Solar/Wind Harmer
0.205
3145543BTLEBRO
Solar/Wind Harmer
0.205
971623AH1-311 GEN
Solar/Wind Harmer
0.41
961601AG1-000A GEN
Solar/Wind Harmer
14.572
316458AB2-190 GEN2
Solar/Wind Harmer
1.089
970133AG2-095 GEN
Solar/Wind Harmer
1.922
3144216WINCHST
Adder
0.75
3150921YORKTN3
Adder
4.942
3143096IRON208
Adder
0.779
3143096IRON208
Adder
0.764
971683AH1-343 GEN
Solar/Wind Harmer
6.809
3137643SOCKMAN
Solar/Wind Harmer
0.909
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
970831AG2-522 GEN
Solar/Wind Harmer
9.677
3146043SEABORD
Solar/Wind Harmer
0.226
315652AC1-086 GEN
Solar/Wind Harmer
24.832
3145893MURPHYS
Solar/Wind Harmer
0.607
3145893MURPHYS
Solar/Wind Harmer
0.225
316426AA2-053 GEN
Solar/Wind Harmer
0.752
971285AH1-108 GEN
Adder
1.687
3130546PLYMOUTH
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.713
3145796HORNRTN
Solar/Wind Harmer
0.089
315732AD1-074 GEN1
Solar/Wind Harmer
1.269
315733AD1-074 GEN2
Solar/Wind Harmer
1.269
316463AE2-346 GEN
Solar/Wind Harmer
0.19
3145513AHOSKIE
Solar/Wind Harmer
0.465
3145513AHOSKIE
Solar/Wind Harmer
0.222
3146206CASHIE
Solar/Wind Harmer
0.222
970601AG2-382 GEN
Solar/Wind Harmer
8.295
3145683EARLEYS
Solar/Wind Harmer
0.443
3145683EARLEYS
Solar/Wind Harmer
0.222
3145683EARLEYS
Solar/Wind Harmer
0.222
971445AH1-216 GEN
Solar/Wind Harmer
15.524
3146033SCOT NK
Solar/Wind Harmer
0.871
316274AC1-208 GEN
Solar/Wind Harmer
1.115
316210AC1-098 GEN
Solar/Wind Harmer
2
3151201GRAVEL4
Adder
15.603
3151221GRAVEL6
Adder
15.585
3151191GRAVEL3
Adder
15.406
3151211GRAVEL5
Adder
15.406
316327AA2-057 GEN
Solar/Wind Harmer
0.312
3145746EVERETS
Solar/Wind Harmer
0.831
3145746EVERETS
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.209
315697AD1-025 GEN
Solar/Wind Harmer
0.224
957861AF2-080 GEN
Solar/Wind Harmer
8.944
3147173SINAI
Solar/Wind Harmer
0.207
3147243WELCO
Solar/Wind Harmer
0.129
3145573BETHELC
Solar/Wind Harmer
0.206
3145573BETHELC
Solar/Wind Harmer
0.206
971065AG2-659 GEN
Solar/Wind Harmer
9.689
316129AC1-054 GEN
Solar/Wind Harmer
0.847
3130156CHOWAN
Solar/Wind Harmer
0.227
316072AD1-144
Solar/Wind Harmer
0.08
315607AA1-063A GEN
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
0.899
3145893MURPHYS
Solar/Wind Harmer
1
315816AE2-034 GEN
Solar/Wind Harmer
0.959
3145663CRESWEL
Solar/Wind Harmer
0.629
971163AH1-040 GEN
Solar/Wind Harmer
17.973
3145783HORNRTN
Solar/Wind Harmer
0.224
3150851SPRUNCC
Adder
1.031
3146173TUNIS
Solar/Wind Harmer
0.223
3146263WOODLND
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.735
3145796HORNRTN
Solar/Wind Harmer
0.223
315737AD1-076 GEN
Solar/Wind Harmer
2.857
3146206CASHIE
Solar/Wind Harmer
0.222
971547AH1-271 GEN
Solar/Wind Harmer
4.74
3145683EARLEYS
Solar/Wind Harmer
0.222
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
3145336SMITFLD
Solar/Wind Harmer
0.884
971377AH1-170 GEN
Solar/Wind Harmer
2.352
3147623JAMES R
Solar/Wind Harmer
0.511
3145823KELFORD
Solar/Wind Harmer
0.22
970401AG2-262 GEN
Solar/Wind Harmer
1.272
3145963POPLR C
Solar/Wind Harmer
0.216
3151171GRAVELC
Adder
2.28
315671AE2-027_GEN
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
11.112
3146293MARTNCO
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.209
3146233WITAKRS
Solar/Wind Harmer
0.828
316494AC1-189 GEN
Solar/Wind Harmer
0.701
971069AG2-661 GEN
Solar/Wind Harmer
3.67
961671AG1-007 GEN
Solar/Wind Harmer
0.032
3146083TARBORO
Solar/Wind Harmer
0.206
3145493TOT1
Solar/Wind Harmer
0.917
3145543BTLEBRO
Solar/Wind Harmer
0.205
3145543BTLEBRO
Solar/Wind Harmer
0.164
316359AB2-059 GEN
Solar/Wind Harmer
0.728
3142053HEARTS
Solar/Wind Harmer
0.361
316132AB2-190 GEN1
Solar/Wind Harmer
1.089
3138126ROCKLANDING
Solar/Wind Harmer
0.091
3142543TWELFTH
Solar/Wind Harmer
0.019
971317AH1-138 GEN
Solar/Wind Harmer
1.403
3143096IRON208
Adder
0.779
944631AF1-128 GEN
Adder
85.933
3142433PROV 92
Solar/Wind Harmer
0.664
3142433PROV 92
Adder
0.323
3142433PROV 92
Adder
0.323
971777AH1-397 GEN
Solar/Wind Harmer
0.417
3141766HARMONY
Solar/Wind Harmer
0.031
315975AC1-164 GENB
Solar/Wind Harmer
0.048
3138133OCRAN
Solar/Wind Harmer
0.091
3142416OLDCHRC
Solar/Wind Harmer
0.352
3142416OLDCHRC
Solar/Wind Harmer
0.135
962861AG1-135 GEN
Solar/Wind Harmer
4.298
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.391
3141726DUNNSVL
Solar/Wind Harmer
0.502
3150351NORNECKC2
Adder
1.222
970223AG2-152 GEN
Solar/Wind Harmer
8.332
316447AC1-158 HLD
Solar/Wind Helper
3.596
316044AC1-158 PL1
Solar/Wind Helper
1.634
3147666LOUISA
Solar/Wind Helper
1.083
316192AB2-158 GEN
Solar/Wind Helper
1.799
3142946ENON
Solar/Wind Harmer
0.017
3142366NRTHEST
Adder
0.536
3150691DARBY 3
Adder
11.623
3150701DARBY 4
Adder
11.596
3150681DARBY 2
Adder
11.583
3150671DARBY 1
Adder
11.569
316156AD2-030 GEN
Solar/Wind Harmer
0.115
315976AC1-164 GENA
Solar/Wind Harmer
1.617
316169AC1-164_GENC
Solar/Wind Harmer
1.397
942751AE2-291 GEN
Solar/Wind Harmer
8.04
316312AB1-027
Solar/Wind Harmer
0.241
3142296MT RD221
Adder
0.415
3150341NORNECKC1
Adder
1.283
3150341NORNECKC1
Adder
1.273
966871AG1-558 GEN
Solar/Wind Harmer
0.14
316045AC1-158 PL2
Solar/Wind Helper
5.23
316450AC1-158 RIC
Solar/Wind Helper
0.436
316159AE1-175 C
Solar/Wind Harmer
0.155
3138283WHITEMARSH
Solar/Wind Harmer
0.041
3142433PROV 92
Adder
0.323
3142433PROV 92
Adder
0.323
3143873LANEXA
Solar/Wind Harmer
0.095
970189AG2-124 GEN
Solar/Wind Harmer
4.684
3141873WAN 176
Solar/Wind Harmer
0.032
3141913WHIT STONE
Solar/Wind Harmer
0.152
3138133OCRAN
Solar/Wind Harmer
0.045
3141783LANCAST
Solar/Wind Harmer
0.089
3141783LANCAST
Solar/Wind Harmer
0.059
3141813NORNECK
Solar/Wind Harmer
0.122
316164AC1-076 GEN
Solar/Wind Helper
1.106
270494AE1-108_GEN
Solar/Wind Harmer
2.21
316222AC1-221 GEN
Solar/Wind Harmer
0.758
316283AC2-100 C
Solar/Wind Harmer
0.358
3142946ENON
Solar/Wind Harmer
0.058
3142433PROV 92
Adder
0.323
3142433PROV 92
Adder
0.323
316123AC1-075 GEN
Solar/Wind Harmer
0.213
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.808
3141873WAN 176
Solar/Wind Harmer
2.803
970293AG2-193 GEN
Solar/Wind Harmer
1.676
3141766HARMONY
Solar/Wind Harmer
2.071
316075AC2-137 C
Solar/Wind Harmer
0.041
315821AE2-092 GEN
Solar/Wind Harmer
0
3142416OLDCHRC
Solar/Wind Harmer
1.313
3150351NORNECKC2
Adder
1.242
316473AC1-191 GEN
Solar/Wind Harmer
0.408
3147666LOUISA
Solar/Wind Helper
0.623
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.627
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.918
MECLTFEXP_MEC->PJM
CLTF
4.371
SIGELTFEXP_SIGE->PJM
CLTF
0.131
CPLELTFEXP_CPLE->PJM
CLTF
13.745
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.549
LAGNLTFEXP_LAGN->PJM
CLTF
9.318
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.573
TVALTFEXP_TVA->PJM
CLTF
4.667
NYPJM->LTFIMP_NY
CLTF
2.496
LGEELTFEXP_LGEE->PJM
CLTF
1.573
WECLTFEXP_WEC->PJM
CLTF
0.799

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.28 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4029.88
MW Contribution:
2.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
4.893
315241AE2-183_GT1
50/50
4.88
972185AH1-677 GEN
50/50
17.685
3151041BRUNSWICKG3
50/50
3.861
972187AH1-678 GEN
50/50
8.859
970909AG2-566 GEN
50/50
2.813
3144293JTRSVLE
50/50
0.629
316336AC2-165 C
Solar/Wind Harmer
24.362
316313AB2-026
Solar/Wind Harmer
1.049
971223AH1-071 GEN
Solar/Wind Harmer
4.875
3143526WINTERP
Solar/Wind Harmer
-0.172
970933AG2-581 GEN
Solar/Wind Harmer
30.473
970099AG2-077 GEN
Solar/Wind Harmer
37.969
3144356SAPONY
Solar/Wind Harmer
1.041
316315AB2-025 C
Solar/Wind Harmer
0.803
970301AG2-198 GEN
Solar/Wind Harmer
14.816
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.022
958211AF2-115 GEN
Solar/Wind Harmer
4.36
316365GEN2_N
Solar/Wind Harmer
1.847
970323AG2-213 GEN
Solar/Wind Harmer
13.649
316294AC1-161 GEN
Solar/Wind Harmer
8.768
316185AD1-033 GEN
Solar/Wind Harmer
2.851
3145506HICKORY
Solar/Wind Harmer
-0.108
3145506HICKORY
Solar/Wind Harmer
-0.065
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.817
316388AE2-253 GEN
Solar/Wind Harmer
1.817
315687AD1-152 GEN
Solar/Wind Harmer
3.248
3137176SLIGO L2192
Solar/Wind Harmer
-0.107
3146456SLIGO L269
Solar/Wind Harmer
3.186
3150991CHESPKB
Adder
2.514
3150991CHESPKB
Adder
2.453
3130086AYDLETT
Solar/Wind Harmer
-0.107
315835AF2-110_GEN
Solar/Wind Harmer
3.356
316349AD2-085 GEN
Solar/Wind Harmer
2.383
316083AB2-161 GEN
Solar/Wind Harmer
4.353
3146386ELIZ CT
Solar/Wind Harmer
-0.027
316431W1029_GEN1
Solar/Wind Harmer
4.833
316433W1029_GEN2
Solar/Wind Harmer
4.833
316303AF2-085
50/50
6.171
315244AE2-183_ST
50/50
8.496
963041AG1-153 GEN
50/50
7.817
315779AE2-040
50/50
3.708
3151541CLOVER2
50/50
5.508
316258AE1-075 C
Solar/Wind Harmer
0.944
316405AF2-144 C
Solar/Wind Harmer
0.997
970533AG2-339 GEN
Solar/Wind Harmer
23.096
970673AG2-436 GEN
Solar/Wind Harmer
74.284
316233AE1-074 FULL
Solar/Wind Harmer
0.892
971281AH1-106 GEN
Solar/Wind Harmer
5.387
971283AH1-107 GEN
Solar/Wind Harmer
5.387
971967AH1-528 GEN
Solar/Wind Harmer
62.321
970085AG2-068 GEN
Solar/Wind Harmer
19.452
970581AG2-369 GEN
Solar/Wind Harmer
16.729
315814AE2-033 C
Solar/Wind Harmer
27.683
316322AB2-045
Solar/Wind Harmer
0.984
971845AH1-439 GEN
Solar/Wind Harmer
15.581
316486AD2-202 GEN
Solar/Wind Harmer
0.735
3143316POE
Solar/Wind Harmer
-0.111
946301AF1-294 GEN
Solar/Wind Harmer
7.15
961791AG1-021 GEN
Solar/Wind Harmer
3.488
970683AG2-441 GEN
Solar/Wind Harmer
19.5
970681AG2-440 GEN
Solar/Wind Harmer
12.943
3144303KENBRDG
Solar/Wind Harmer
-0.022
946281AF1-292 GEN
Solar/Wind Harmer
0.607
316316AC1-027 C
Solar/Wind Harmer
0.828
3151081ELIZAR1
Adder
22.035
3151091ELIZAR2
Adder
21.652
316018AA1-139 ULT2
Solar/Wind Harmer
2.308
957871AF2-081 GEN
Solar/Wind Harmer
13.504
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
5.098
316311AC2-079 GEN
Solar/Wind Harmer
13.541
970657AG2-426 GEN
Solar/Wind Harmer
1.692
313526AB2-022
Solar/Wind Harmer
0.722
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146396TANGLEW
Solar/Wind Harmer
0.493
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
316435W1029_GEN3
Solar/Wind Harmer
4.833
3151031BRUNSWICKG2
50/50
3.861
970413AG2-270 GEN
50/50
24.172
3144293JTRSVLE
50/50
0.629
3151101ELIZAR3
50/50
23.681
3143336POWHATN
Solar/Wind Harmer
3.935
944011AF1-069 GEN
Solar/Wind Harmer
20.178
970917AG2-570 GEN
Solar/Wind Harmer
78.964
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
11.912
316478AD1-087 GEN
Solar/Wind Harmer
2.509
942461AE2-259 GEN
Solar/Wind Harmer
4.313
3147133PAMPLIN
Solar/Wind Harmer
-0.088
959311AF2-222 GEN
Solar/Wind Harmer
28.588
970257AG2-171 GEN
Solar/Wind Harmer
10.237
971775AH1-396 GEN
Solar/Wind Harmer
1.926
944581AF1-123 GEN
Solar/Wind Harmer
124.097
944601AF1-125 GEN
Solar/Wind Harmer
122.161
966621AG1-532 GEN
Solar/Wind Harmer
0.55
3142956BIRDNECK
Solar/Wind Harmer
1.45
316017AA1-139 ULT1
Solar/Wind Harmer
2.179
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.122
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3147043LAWRENC
Solar/Wind Harmer
-0.016
316305AF2-043 C
Solar/Wind Harmer
0.809
316246AF1-032 C
Solar/Wind Harmer
0.543
964241AG1-285 GEN
Solar/Wind Harmer
20.977
970657AG2-426 GEN
Solar/Wind Harmer
5.422
316320Y1-086
Solar/Wind Harmer
1.571
315813AE1-149 C
Solar/Wind Harmer
16.772
316321Z2-027
Solar/Wind Harmer
0.72
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
313506AB2-031 GEN
Solar/Wind Harmer
2.134
3145273HOLLAND
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.027
3150861SPRUNCD
Adder
1.093
3144536CHRHLND
Solar/Wind Harmer
-0.004
316181AB2-040 GEN
Solar/Wind Harmer
3.707
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146376EDENTON
Solar/Wind Harmer
-0.026
3156081AA2-088 GEN
Solar/Wind Harmer
8.517
316011AB1-132 GEN
Solar/Wind Harmer
5.452
3145893MURPHYS
Solar/Wind Harmer
0.182
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
-0.026
313527AB2-043 GEN
Solar/Wind Harmer
4.319
315742AE1-103 GEN
Solar/Wind Harmer
6.309
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
316237AB2-079_GEN
Solar/Wind Harmer
0.796
3146376EDENTON
Solar/Wind Harmer
0.781
3146376EDENTON
Solar/Wind Harmer
0.781
962571AG1-106 GEN
Solar/Wind Harmer
3.752
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.727
3145893MURPHYS
Solar/Wind Harmer
-0.047
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
315614AA2-178 GEN
Solar/Wind Harmer
2.802
3145783HORNRTN
Solar/Wind Harmer
3.074
3145783HORNRTN
Solar/Wind Harmer
2.459
3145783HORNRTN
Solar/Wind Harmer
0.768
3145783HORNRTN
Solar/Wind Harmer
0.307
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
316140AB2-099
Solar/Wind Harmer
0.173
316065AD1-022 GEN
Solar/Wind Harmer
12.875
3145796HORNRTN
Solar/Wind Harmer
-0.077
962561AG1-105 GEN
Solar/Wind Harmer
14.144
964791AG1-342 GEN
Solar/Wind Harmer
5.315
3146843MT LREL
Solar/Wind Harmer
-0.025
3146843MT LREL
Solar/Wind Harmer
-0.025
316240AF1-291 C
Solar/Wind Harmer
0.747
315724AD1-057 GEN
Solar/Wind Harmer
4.807
944641AF1-129 GEN
Adder
103.647
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
316033AB2-134 GEN
Solar/Wind Harmer
7.854
316190AA2-174 GEN
Solar/Wind Harmer
0.319
3146173TUNIS
Solar/Wind Harmer
-0.026
3145336SMITFLD
Solar/Wind Harmer
-0.01
315735AD1-075 GEN1
Solar/Wind Harmer
2.602
3146263WOODLND
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.026
3146206CASHIE
Solar/Wind Harmer
-0.026
316317KELFORD C
Solar/Wind Harmer
1.176
3145823KELFORD
Solar/Wind Harmer
-0.025
3151171GRAVELC
Adder
3.119
3145963POPLR C
Solar/Wind Harmer
-0.025
316212AC1-099_GEN
Solar/Wind Harmer
2.173
961611AG1-000B GEN
Solar/Wind Harmer
5.222
315722AD1-056 GEN
Solar/Wind Harmer
8.74
3145933PARMELE
Solar/Wind Harmer
-0.024
315778AD1-151 GEN
Solar/Wind Harmer
21.565
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316458AB2-190 GEN2
Solar/Wind Harmer
2.421
3146233WITAKRS
Solar/Wind Harmer
0.502
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.016
316420AA1-050 GEN
Solar/Wind Harmer
2.716
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.392
970133AG2-095 GEN
Solar/Wind Harmer
2.653
3144216WINCHST
Adder
0.782
3150921YORKTN3
Adder
5.149
316003AC1-222 GEN
Solar/Wind Harmer
2.176
3143096IRON208
Adder
0.825
3143096IRON208
Adder
0.809
316222AC1-221 GEN
Solar/Wind Harmer
2.121
316283AC2-100 C
Solar/Wind Harmer
1.968
971683AH1-343 GEN
Solar/Wind Harmer
8.993
3142946ENON
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.341
3142433PROV 92
Adder
0.341
970293AG2-193 GEN
Solar/Wind Harmer
2.343
3141843SHACKLE
Adder
0.851
316203AE2-005 GEN
Solar/Wind Harmer
7.893
3141873WAN 176
Solar/Wind Harmer
2.214
3141766HARMONY
Solar/Wind Harmer
1.638
316075AC2-137 C
Solar/Wind Harmer
0.488
3150351NORNECKC2
Adder
1.323
3147666LOUISA
Solar/Wind Helper
0.606
971285AH1-108 GEN
Adder
1.788
316238AB2-078_GEN
Solar/Wind Harmer
0.796
316239AB2-077_GEN
Solar/Wind Harmer
0.796
315800Z1-036_GEN1
Solar/Wind Harmer
6.515
3137643SOCKMAN
Solar/Wind Harmer
-0.105
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
315839AE2-212 C
Solar/Wind Harmer
0.787
970831AG2-522 GEN
Solar/Wind Harmer
13.091
3146043SEABORD
Solar/Wind Harmer
-0.026
315652AC1-086 GEN
Solar/Wind Harmer
29.367
316318V4-068
Solar/Wind Harmer
0.649
3145893MURPHYS
Solar/Wind Harmer
-0.07
3145893MURPHYS
Solar/Wind Harmer
-0.026
316426AA2-053 GEN
Solar/Wind Harmer
2.619
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
316236AE1-162_GEN
Solar/Wind Harmer
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
5.205
316118AC1-105 GEN
Solar/Wind Harmer
1.664
316005AA1-067
Solar/Wind Harmer
0.486
3145493TOT1
Solar/Wind Harmer
0.368
3145453TOT5
Solar/Wind Harmer
0.221
3145603CNETO
Solar/Wind Harmer
0.147
316248AF1-058 C
Solar/Wind Harmer
0.711
316049AB1-081 GEN
Solar/Wind Harmer
2.54
316263AC1-034 GEN
Solar/Wind Harmer
11.064
961601AG1-000A GEN
Solar/Wind Harmer
9.275
3142946ENON
Solar/Wind Harmer
-0.002
3142366NRTHEST
Adder
0.57
3150691DARBY 3
Adder
12.353
3150701DARBY 4
Adder
12.324
3150681DARBY 2
Adder
12.31
3150671DARBY 1
Adder
12.295
316441AF1-014 GEN
Solar/Wind Harmer
1.262
315666AE1-190 GEN
Solar/Wind Harmer
0.562
316156AD2-030 GEN
Solar/Wind Harmer
0.497
315976AC1-164 GENA
Solar/Wind Harmer
4.152
316169AC1-164_GENC
Solar/Wind Harmer
3.587
3142296MT RD221
Adder
0.446
3150341NORNECKC1
Adder
1.367
3150341NORNECKC1
Adder
1.356
316045AC1-158 PL2
Solar/Wind Helper
5.054
316450AC1-158 RIC
Solar/Wind Helper
0.421
970119AG2-088 GEN
50/50
46.283
315243AE2-183_GT3
50/50
4.893
3151051BRUNSWICKS1
50/50
8.016
3151021BRUNSWICKG1
50/50
3.861
971451AH1-221 GEN
50/50
11.725
3151531CLOVER1
50/50
5.55
3144293JTRSVLE
50/50
0.629
3144293JTRSVLE
50/50
0.497
970937AG2-583 GEN
Solar/Wind Harmer
28.051
3143336POWHATN
Solar/Wind Harmer
4.63
3143226MDLTHAN
Solar/Wind Harmer
-0.039
941031AE2-094 GEN
Solar/Wind Harmer
64.396
940641AE2-051 GEN
Solar/Wind Harmer
31.952
3143526WINTERP
Solar/Wind Harmer
-0.172
939411AE1-173 GEN
Solar/Wind Harmer
161.695
970919AG2-571 GEN
Solar/Wind Harmer
9.995
970087AG2-069 GEN
Solar/Wind Harmer
29.178
957481AF2-042 GEN
Solar/Wind Harmer
94.922
315693AD1-088 GEN
Solar/Wind Harmer
15.016
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.012
971563AH1-280 GEN
Solar/Wind Harmer
3.488
970685AG2-442 GEN
Solar/Wind Harmer
24.277
316023GEN1_S
Solar/Wind Harmer
1.847
316034AC1-036 C
Solar/Wind Harmer
0.505
944591AF1-124 GEN
Solar/Wind Harmer
124.544
315785AD2-033 C
Solar/Wind Harmer
6.148
315773AC2-141 GEN
Solar/Wind Harmer
11.345
960081AF2-299 GEN
Solar/Wind Harmer
3.05
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316375AC2-012 GEN
Solar/Wind Harmer
9.324
319010AE1-072 C
Solar/Wind Harmer
5.443
316036AC1-147 C
Solar/Wind Harmer
0.725
3150981CHESPKA
Adder
2.996
3147043LAWRENC
Adder
2.171
316093AE2-104_GEN
Solar/Wind Harmer
7.807
316381AD1-082 GEN
Solar/Wind Harmer
2.455
316087AB2-174 GEN
Solar/Wind Harmer
3.812
315733AD1-074 GEN2
Solar/Wind Harmer
5.205
316463AE2-346 GEN
Solar/Wind Harmer
0.416
3145513AHOSKIE
Solar/Wind Harmer
0.225
961941AG1-037 GEN
Solar/Wind Harmer
0.194
3145513AHOSKIE
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.082
3145796HORNRTN
Solar/Wind Harmer
-0.01
971445AH1-216 GEN
Solar/Wind Harmer
15.919
3146206CASHIE
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
11.255
3145683EARLEYS
Solar/Wind Harmer
-0.051
3145683EARLEYS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
3146033SCOT NK
Solar/Wind Harmer
-0.1
3151201GRAVEL4
Adder
16.232
3151221GRAVEL6
Adder
16.214
3151191GRAVEL3
Adder
16.027
3151211GRAVEL5
Adder
16.027
316210AC1-098 GEN
Solar/Wind Harmer
3.912
316274AC1-208 GEN
Solar/Wind Harmer
2.687
316174AB2-169 GEN
Solar/Wind Harmer
3.835
315697AD1-025 GEN
Solar/Wind Harmer
4.922
316327AA2-057 GEN
Solar/Wind Harmer
2.451
3145746EVERETS
Solar/Wind Harmer
-0.095
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
957861AF2-080 GEN
Solar/Wind Harmer
10.465
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
316382AG1-145 C
Solar/Wind Harmer
0.641
316159AE1-175 C
Solar/Wind Harmer
0.571
957831AF2-077 GEN
Solar/Wind Harmer
0.63
3138283WHITEMARSH
Solar/Wind Harmer
0.032
3142433PROV 92
Adder
0.341
3142433PROV 92
Adder
0.341
3143873LANEXA
Solar/Wind Harmer
-0.011
957601AF2-054 GEN
Solar/Wind Harmer
0.558
3141873WAN 176
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.415
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.005
316164AC1-076 GEN
Solar/Wind Helper
1.068
270455AD2-022 GEN
Solar/Wind Harmer
2.53
270457AD2-023 GEN
Solar/Wind Harmer
1.283
3146516WINFALL
Solar/Wind Harmer
-0.086
3146516WINFALL
Solar/Wind Harmer
-0.027
316131AB2-060 GEN
Solar/Wind Harmer
2.867
3150851SPRUNCC
Adder
1.093
315611Z1-036_GEN2
Solar/Wind Harmer
6.515
3130156CHOWAN
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.531
971065AG2-659 GEN
Solar/Wind Harmer
13.103
316129AC1-054 GEN
Solar/Wind Harmer
2.29
315607AA1-063A GEN
Solar/Wind Harmer
2.633
3145893MURPHYS
Solar/Wind Harmer
-0.104
3145893MURPHYS
Solar/Wind Harmer
0.773
315816AE2-034 GEN
Solar/Wind Harmer
2.101
3145663CRESWEL
Solar/Wind Harmer
-0.073
971163AH1-040 GEN
Solar/Wind Harmer
24.414
3145783HORNRTN
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3145336SMITFLD
Solar/Wind Harmer
-0.103
315737AD1-076 GEN
Solar/Wind Harmer
4.894
3146263WOODLND
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.085
3145796HORNRTN
Solar/Wind Harmer
-0.026
3146206CASHIE
Solar/Wind Harmer
-0.026
971547AH1-271 GEN
Solar/Wind Harmer
6.431
3145683EARLEYS
Solar/Wind Harmer
-0.026
3156021HOLLOMANSOL
Solar/Wind Harmer
3.443
3145823KELFORD
Solar/Wind Harmer
-0.025
315671AE2-027_GEN
Solar/Wind Harmer
4.537
3151171GRAVELC
Adder
2.372
3145963POPLR C
Solar/Wind Harmer
-0.025
970401AG2-262 GEN
Solar/Wind Harmer
1.624
961611AG1-000B GEN
Solar/Wind Harmer
12.238
3146293MARTNCO
Solar/Wind Harmer
0.151
316369SG1_INVT
Solar/Wind Harmer
4.35
971069AG2-661 GEN
Solar/Wind Harmer
3.834
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316132AB2-190 GEN1
Solar/Wind Harmer
2.421
316319Z2-044 C
Solar/Wind Harmer
1.324
3146233WITAKRS
Solar/Wind Harmer
-0.095
316494AC1-189 GEN
Solar/Wind Harmer
2.574
961671AG1-007 GEN
Solar/Wind Harmer
0.301
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.705
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.174
3142053HEARTS
Solar/Wind Harmer
0.277
3142543TWELFTH
Solar/Wind Harmer
-0.002
3138126ROCKLANDING
Solar/Wind Harmer
0.071
3143096IRON208
Adder
0.825
971317AH1-138 GEN
Solar/Wind Harmer
2.756
944631AF1-128 GEN
Adder
90.654
3142433PROV 92
Solar/Wind Harmer
-0.078
3142433PROV 92
Adder
0.341
3142433PROV 92
Adder
0.341
971777AH1-397 GEN
Solar/Wind Harmer
2.185
315662AE1-191 GEN
Solar/Wind Harmer
2.248
316280AD1-041 GEN
Solar/Wind Harmer
1.405
3141766HARMONY
Solar/Wind Harmer
-0.004
315975AC1-164 GENB
Solar/Wind Harmer
0.123
316314AB2-024 C
Solar/Wind Harmer
1.56
3138133OCRAN
Solar/Wind Harmer
-0.011
3150351NORNECKC2
Adder
1.301
316447AC1-158 HLD
Solar/Wind Helper
3.476
316044AC1-158 PL1
Solar/Wind Helper
1.579
3147666LOUISA
Solar/Wind Helper
1.055
316192AB2-158 GEN
Solar/Wind Helper
1.752
CBM West 1LTFEXP_CBM-W1->PJM
CBM
26.757
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.722
MECLTFEXP_MEC->PJM
CLTF
4.27
SIGELTFEXP_SIGE->PJM
CLTF
0.127
CPLELTFEXP_CPLE->PJM
CLTF
13.965
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.859
LAGNLTFEXP_LAGN->PJM
CLTF
9.241
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.85
TVALTFEXP_TVA->PJM
CLTF
4.62
NYPJM->LTFIMP_NY
CLTF
2.404
LGEELTFEXP_LGEE->PJM
CLTF
1.52
WECLTFEXP_WEC->PJM
CLTF
0.775

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.61 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5316.1
MW Contribution:
3.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151041BRUNSWICKG3
50/50
8.509
972187AH1-678 GEN
50/50
19.524
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970535AG2-341 GEN
50/50
5.153
3144293JTRSVLE
50/50
0.686
970933AG2-581 GEN
Solar/Wind Harmer
51.56
970099AG2-077 GEN
Solar/Wind Harmer
57.909
970301AG2-198 GEN
Solar/Wind Harmer
15.175
316118AC1-105 GEN
Solar/Wind Harmer
0.853
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.163
962561AG1-105 GEN
Solar/Wind Harmer
15.161
970323AG2-213 GEN
Solar/Wind Harmer
11.876
958211AF2-115 GEN
Solar/Wind Harmer
3.249
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.756
3146776BUCKING
Solar/Wind Harmer
0.641
3146776BUCKING
Solar/Wind Harmer
0.052
942671AE2-283 GEN
Solar/Wind Harmer
3.601
316049AB1-081 GEN
Solar/Wind Harmer
0.701
316263AC1-034 GEN
Solar/Wind Harmer
4.683
961601AG1-000A GEN
Solar/Wind Harmer
2.139
316294AC1-161 GEN
Solar/Wind Helper
8.161
316185AD1-033 GEN
Solar/Wind Helper
1.897
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316240AF1-291 C
Solar/Wind Helper
0.501
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
3151051BRUNSWICKS1
50/50
17.665
3151021BRUNSWICKG1
50/50
8.509
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
971629AH1-314 GEN
50/50
19.08
3151561HALLBR1
50/50
0.4
941031AE2-094 GEN
Solar/Wind Harmer
118.958
970919AG2-571 GEN
Solar/Wind Harmer
21.594
970087AG2-069 GEN
Solar/Wind Harmer
47.528
957481AF2-042 GEN
Solar/Wind Harmer
144.773
315693AD1-088 GEN
Solar/Wind Harmer
23.773
970401AG2-262 GEN
Solar/Wind Harmer
1.883
316131AB2-060 GEN
Solar/Wind Harmer
0.892
315785AD2-033 C
Solar/Wind Harmer
2.263
316034AC1-036 C
Solar/Wind Harmer
0.019
970685AG2-442 GEN
Solar/Wind Harmer
20.361
971563AH1-280 GEN
Solar/Wind Harmer
2.888
3146926FARMVIL
Solar/Wind Harmer
0.152
971065AG2-659 GEN
Solar/Wind Harmer
9.521
316129AC1-054 GEN
Solar/Wind Harmer
0.781
970223AG2-152 GEN
Solar/Wind Harmer
12.898
3147123OTTER R
Solar/Wind Harmer
0.097
3146776BUCKING
Solar/Wind Harmer
0.064
3147312GRETNA
Solar/Wind Harmer
0.116
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.63
270030AE2-140 GEN
Solar/Wind Harmer
14.713
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.438
3142053HEARTS
Solar/Wind Harmer
0.217
315773AC2-141 GEN
Solar/Wind Helper
9.603
316375AC2-012 GEN
Solar/Wind Helper
1.073
316036AC1-147 C
Solar/Wind Helper
0.622
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
315671AE2-027_GEN
Solar/Wind Helper
3.055
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316072AD1-144
Solar/Wind Helper
0.428
316369SG1_INVT
Solar/Wind Helper
1.805
316132AB2-190 GEN1
Solar/Wind Helper
2.11
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
3138133OCRAN
Solar/Wind Helper
0.206
963041AG1-153 GEN
50/50
17.227
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151601KERR 3
50/50
0.597
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
3151631KERR 6
50/50
0.597
971967AH1-528 GEN
Solar/Wind Harmer
108.333
970673AG2-436 GEN
Solar/Wind Harmer
80.381
970533AG2-339 GEN
Solar/Wind Harmer
48.8
970085AG2-068 GEN
Solar/Wind Harmer
31.685
970581AG2-369 GEN
Solar/Wind Harmer
27.249
316486AD2-202 GEN
Solar/Wind Harmer
0.505
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
16.537
970681AG2-440 GEN
Solar/Wind Harmer
10.976
946301AF1-294 GEN
Solar/Wind Harmer
5.342
961791AG1-021 GEN
Solar/Wind Harmer
2.599
970831AG2-522 GEN
Solar/Wind Harmer
8.162
971845AH1-439 GEN
Solar/Wind Harmer
7.623
270197AD1-017 GEN1
Solar/Wind Harmer
1.01
270069AE2-166 C O1
Solar/Wind Harmer
5.95
3143316POE
Solar/Wind Helper
1.638
316316AC1-027 C
Solar/Wind Helper
0.639
316236AE1-162_GEN
Solar/Wind Helper
0.53
315839AE2-212 C
Solar/Wind Helper
0.524
316018AA1-139 ULT2
Solar/Wind Helper
1.653
315697AD1-025 GEN
Solar/Wind Helper
4.281
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
957831AF2-077 GEN
Solar/Wind Helper
0.494
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141873WAN 176
Solar/Wind Helper
0.07
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.344
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3151031BRUNSWICKG2
50/50
8.509
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
944011AF1-069 GEN
Solar/Wind Harmer
38.868
970917AG2-570 GEN
Solar/Wind Harmer
53.986
316478AD1-087 GEN
Solar/Wind Harmer
1.721
316222AC1-221 GEN
Solar/Wind Harmer
1.259
971683AH1-343 GEN
Solar/Wind Harmer
11.193
316283AC2-100 C
Solar/Wind Harmer
0.593
964241AG1-285 GEN
Solar/Wind Harmer
18.935
970257AG2-171 GEN
Solar/Wind Harmer
8.907
971775AH1-396 GEN
Solar/Wind Harmer
0.445
959311AF2-222 GEN
Solar/Wind Harmer
24.64
3147133PAMPLIN
Solar/Wind Harmer
0.841
942461AE2-259 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Harmer
0.342
3146926FARMVIL
Solar/Wind Harmer
0.152
3146776BUCKING
Solar/Wind Harmer
0.058
3147312GRETNA
Solar/Wind Harmer
0.029
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.124
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.558
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
316305AF2-043 C
Solar/Wind Helper
0.5
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316320Y1-086
Solar/Wind Helper
0.157
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
316468AD1-105 GEN
Solar/Wind Helper
1.353
315800Z1-036_GEN1
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3142946ENON
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.514
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.826
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316487AF1-042 GEN
Solar/Wind Helper
0.338
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
316435W1029_GEN3
Solar/Wind Helper
1.293
316312AB1-027
Solar/Wind Helper
0.598
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
MECLTFEXP_MEC->PJM
CLTF
7.813
SIGELTFEXP_SIGE->PJM
CLTF
0.234
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
TVALTFEXP_TVA->PJM
CLTF
7.703
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.49 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5107.87
MW Contribution:
3.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.227
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151601KERR 3
50/50
0.597
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
3151631KERR 6
50/50
0.597
971967AH1-528 GEN
Solar/Wind Harmer
108.333
970673AG2-436 GEN
Solar/Wind Harmer
80.381
970085AG2-068 GEN
Solar/Wind Harmer
31.685
970581AG2-369 GEN
Solar/Wind Harmer
27.249
316486AD2-202 GEN
Solar/Wind Harmer
0.505
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
16.537
970681AG2-440 GEN
Solar/Wind Harmer
10.976
946301AF1-294 GEN
Solar/Wind Harmer
5.342
961791AG1-021 GEN
Solar/Wind Harmer
2.599
970831AG2-522 GEN
Solar/Wind Harmer
8.162
971845AH1-439 GEN
Solar/Wind Harmer
7.623
270197AD1-017 GEN1
Solar/Wind Harmer
1.01
270069AE2-166 C O1
Solar/Wind Harmer
5.95
3143316POE
Solar/Wind Helper
1.638
316316AC1-027 C
Solar/Wind Helper
0.639
316236AE1-162_GEN
Solar/Wind Helper
0.53
315839AE2-212 C
Solar/Wind Helper
0.524
316018AA1-139 ULT2
Solar/Wind Helper
1.653
315697AD1-025 GEN
Solar/Wind Helper
4.281
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
957831AF2-077 GEN
Solar/Wind Helper
0.494
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141873WAN 176
Solar/Wind Helper
0.07
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.344
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
316468AD1-105 GEN
Solar/Wind Helper
1.353
315800Z1-036_GEN1
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.509
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
970917AG2-570 GEN
Solar/Wind Harmer
53.986
316478AD1-087 GEN
Solar/Wind Harmer
1.721
316222AC1-221 GEN
Solar/Wind Harmer
1.259
971683AH1-343 GEN
Solar/Wind Harmer
11.193
316283AC2-100 C
Solar/Wind Harmer
0.593
964241AG1-285 GEN
Solar/Wind Harmer
18.935
970257AG2-171 GEN
Solar/Wind Harmer
8.907
971775AH1-396 GEN
Solar/Wind Harmer
0.445
959311AF2-222 GEN
Solar/Wind Harmer
24.64
3147133PAMPLIN
Solar/Wind Harmer
0.841
942461AE2-259 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Harmer
0.342
3146926FARMVIL
Solar/Wind Harmer
0.152
3146776BUCKING
Solar/Wind Harmer
0.058
3147312GRETNA
Solar/Wind Harmer
0.029
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.124
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.558
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
316305AF2-043 C
Solar/Wind Helper
0.5
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316320Y1-086
Solar/Wind Helper
0.157
3142946ENON
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.514
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.826
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.509
972187AH1-678 GEN
50/50
19.524
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970535AG2-341 GEN
50/50
5.153
3144293JTRSVLE
50/50
0.686
970933AG2-581 GEN
Solar/Wind Harmer
51.56
970099AG2-077 GEN
Solar/Wind Harmer
57.909
970301AG2-198 GEN
Solar/Wind Harmer
15.175
316118AC1-105 GEN
Solar/Wind Harmer
0.853
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.163
962561AG1-105 GEN
Solar/Wind Harmer
15.161
970323AG2-213 GEN
Solar/Wind Harmer
11.876
958211AF2-115 GEN
Solar/Wind Harmer
3.249
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.756
3146776BUCKING
Solar/Wind Harmer
0.641
3146776BUCKING
Solar/Wind Harmer
0.052
942671AE2-283 GEN
Solar/Wind Harmer
3.601
316049AB1-081 GEN
Solar/Wind Harmer
0.701
316263AC1-034 GEN
Solar/Wind Harmer
4.683
961601AG1-000A GEN
Solar/Wind Harmer
2.139
316294AC1-161 GEN
Solar/Wind Helper
8.161
316185AD1-033 GEN
Solar/Wind Helper
1.897
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316240AF1-291 C
Solar/Wind Helper
0.501
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316487AF1-042 GEN
Solar/Wind Helper
0.338
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
316435W1029_GEN3
Solar/Wind Helper
1.293
316312AB1-027
Solar/Wind Helper
0.598
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
3151051BRUNSWICKS1
50/50
17.665
3151021BRUNSWICKG1
50/50
8.509
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
971629AH1-314 GEN
50/50
19.08
3151561HALLBR1
50/50
0.4
970919AG2-571 GEN
Solar/Wind Harmer
21.594
970087AG2-069 GEN
Solar/Wind Harmer
47.528
957481AF2-042 GEN
Solar/Wind Harmer
144.773
315693AD1-088 GEN
Solar/Wind Harmer
23.773
970401AG2-262 GEN
Solar/Wind Harmer
1.883
316131AB2-060 GEN
Solar/Wind Harmer
0.892
315785AD2-033 C
Solar/Wind Harmer
2.263
316034AC1-036 C
Solar/Wind Harmer
0.019
970685AG2-442 GEN
Solar/Wind Harmer
20.361
971563AH1-280 GEN
Solar/Wind Harmer
2.888
3146926FARMVIL
Solar/Wind Harmer
0.152
971065AG2-659 GEN
Solar/Wind Harmer
9.521
316129AC1-054 GEN
Solar/Wind Harmer
0.781
970223AG2-152 GEN
Solar/Wind Harmer
12.898
3147123OTTER R
Solar/Wind Harmer
0.097
3146776BUCKING
Solar/Wind Harmer
0.064
3147312GRETNA
Solar/Wind Harmer
0.116
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.63
270030AE2-140 GEN
Solar/Wind Harmer
14.713
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.438
3142053HEARTS
Solar/Wind Harmer
0.217
315773AC2-141 GEN
Solar/Wind Helper
9.603
316375AC2-012 GEN
Solar/Wind Helper
1.073
316036AC1-147 C
Solar/Wind Helper
0.622
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
315671AE2-027_GEN
Solar/Wind Helper
3.055
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316072AD1-144
Solar/Wind Helper
0.428
316369SG1_INVT
Solar/Wind Helper
1.805
316132AB2-190 GEN1
Solar/Wind Helper
2.11
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
3138133OCRAN
Solar/Wind Helper
0.206
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
MECLTFEXP_MEC->PJM
CLTF
7.813
SIGELTFEXP_SIGE->PJM
CLTF
0.234
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
TVALTFEXP_TVA->PJM
CLTF
7.703
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 58572_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 58572_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.11 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5851.06
MW Contribution:
3.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151041BRUNSWICKG3
50/50
8.509
972187AH1-678 GEN
50/50
19.524
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970535AG2-341 GEN
50/50
5.153
3144293JTRSVLE
50/50
0.686
970933AG2-581 GEN
Solar/Wind Harmer
67.888
970099AG2-077 GEN
Solar/Wind Harmer
76.247
315687AD1-152 GEN
Solar/Wind Harmer
6.011
970301AG2-198 GEN
Solar/Wind Harmer
19.981
316248AF1-058 C
Solar/Wind Harmer
1.167
316118AC1-105 GEN
Solar/Wind Harmer
2.569
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.704
962561AG1-105 GEN
Solar/Wind Harmer
19.962
316237AB2-079_GEN
Solar/Wind Harmer
0.977
313527AB2-043 GEN
Solar/Wind Harmer
5.238
970323AG2-213 GEN
Solar/Wind Harmer
15.637
958211AF2-115 GEN
Solar/Wind Harmer
4.752
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.796
270013AE1-250 PV
Solar/Wind Harmer
3.04
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
942671AE2-283 GEN
Solar/Wind Harmer
5.385
316049AB1-081 GEN
Solar/Wind Harmer
1.49
316263AC1-034 GEN
Solar/Wind Harmer
6.491
961601AG1-000A GEN
Solar/Wind Harmer
5.315
316294AC1-161 GEN
Solar/Wind Helper
8.161
316185AD1-033 GEN
Solar/Wind Helper
1.897
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316240AF1-291 C
Solar/Wind Helper
0.501
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316487AF1-042 GEN
Solar/Wind Helper
0.338
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
316435W1029_GEN3
Solar/Wind Helper
1.293
316312AB1-027
Solar/Wind Helper
0.598
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
3151051BRUNSWICKS1
50/50
17.665
3151021BRUNSWICKG1
50/50
8.509
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
971629AH1-314 GEN
50/50
19.08
3151561HALLBR1
50/50
0.4
941031AE2-094 GEN
Solar/Wind Harmer
136.066
970919AG2-571 GEN
Solar/Wind Harmer
21.594
970087AG2-069 GEN
Solar/Wind Harmer
62.578
957481AF2-042 GEN
Solar/Wind Harmer
190.618
315693AD1-088 GEN
Solar/Wind Harmer
27.824
970401AG2-262 GEN
Solar/Wind Harmer
2.354
316131AB2-060 GEN
Solar/Wind Harmer
3.464
315785AD2-033 C
Solar/Wind Harmer
7.115
316034AC1-036 C
Solar/Wind Harmer
0.578
970685AG2-442 GEN
Solar/Wind Harmer
26.809
971563AH1-280 GEN
Solar/Wind Harmer
3.802
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.535
316129AC1-054 GEN
Solar/Wind Harmer
2.056
970223AG2-152 GEN
Solar/Wind Harmer
18.394
270016AE1-250 BESS
Solar/Wind Harmer
3.04
3147123OTTER R
Solar/Wind Harmer
-0.011
3146776BUCKING
Solar/Wind Harmer
-0.007
270018AE2-047 C O1
Solar/Wind Harmer
1.464
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.096
270030AE2-140 GEN
Solar/Wind Harmer
21.088
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.862
3142053HEARTS
Solar/Wind Harmer
0.163
315773AC2-141 GEN
Solar/Wind Helper
9.603
316375AC2-012 GEN
Solar/Wind Helper
1.073
316036AC1-147 C
Solar/Wind Helper
0.622
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
315671AE2-027_GEN
Solar/Wind Helper
3.055
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316072AD1-144
Solar/Wind Helper
0.428
316369SG1_INVT
Solar/Wind Helper
1.805
316132AB2-190 GEN1
Solar/Wind Helper
2.11
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
3138133OCRAN
Solar/Wind Helper
0.206
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.509
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
944011AF1-069 GEN
Solar/Wind Harmer
42.634
970917AG2-570 GEN
Solar/Wind Harmer
170.595
316478AD1-087 GEN
Solar/Wind Harmer
4.82
316003AC1-222 GEN
Solar/Wind Harmer
3.569
316222AC1-221 GEN
Solar/Wind Harmer
3.464
971683AH1-343 GEN
Solar/Wind Harmer
14.738
316283AC2-100 C
Solar/Wind Harmer
3.207
964241AG1-285 GEN
Solar/Wind Harmer
24.931
970257AG2-171 GEN
Solar/Wind Harmer
11.728
971775AH1-396 GEN
Solar/Wind Harmer
2.207
959311AF2-222 GEN
Solar/Wind Harmer
32.508
3147133PAMPLIN
Solar/Wind Harmer
-0.094
942461AE2-259 GEN
Solar/Wind Harmer
4.405
316123AC1-075 GEN
Solar/Wind Harmer
3.105
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270574AD1-017 GEN2
Solar/Wind Harmer
6.006
316217AC1-145 GEN
Solar/Wind Harmer
2.636
316197AC1-042 GEN
Solar/Wind Harmer
1.998
3147312GRETNA
Solar/Wind Harmer
-0.003
943811AF1-049 GEN
Solar/Wind Harmer
4.097
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.382
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
316305AF2-043 C
Solar/Wind Helper
0.5
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316320Y1-086
Solar/Wind Helper
0.157
3142946ENON
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.514
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.826
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
963041AG1-153 GEN
50/50
17.227
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151601KERR 3
50/50
0.597
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
3151631KERR 6
50/50
0.597
971967AH1-528 GEN
Solar/Wind Harmer
143.019
970673AG2-436 GEN
Solar/Wind Harmer
158.752
970533AG2-339 GEN
Solar/Wind Harmer
48.8
970085AG2-068 GEN
Solar/Wind Harmer
41.719
970581AG2-369 GEN
Solar/Wind Harmer
35.878
316486AD2-202 GEN
Solar/Wind Harmer
1.412
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316238AB2-078_GEN
Solar/Wind Harmer
0.977
316239AB2-077_GEN
Solar/Wind Harmer
0.977
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
21.774
970681AG2-440 GEN
Solar/Wind Harmer
14.452
946301AF1-294 GEN
Solar/Wind Harmer
7.794
961791AG1-021 GEN
Solar/Wind Harmer
3.802
270455AD2-022 GEN
Solar/Wind Harmer
5.012
270457AD2-023 GEN
Solar/Wind Harmer
2.542
970831AG2-522 GEN
Solar/Wind Harmer
10.747
971845AH1-439 GEN
Solar/Wind Harmer
10.037
316322AB2-045
Solar/Wind Harmer
0.605
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
270069AE2-166 C O1
Solar/Wind Harmer
8.528
3143316POE
Solar/Wind Helper
1.638
316316AC1-027 C
Solar/Wind Helper
0.639
316236AE1-162_GEN
Solar/Wind Helper
0.53
315839AE2-212 C
Solar/Wind Helper
0.524
316018AA1-139 ULT2
Solar/Wind Helper
1.653
315697AD1-025 GEN
Solar/Wind Helper
4.281
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
957831AF2-077 GEN
Solar/Wind Helper
0.494
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141873WAN 176
Solar/Wind Helper
0.07
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.344
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
316468AD1-105 GEN
Solar/Wind Helper
1.353
315800Z1-036_GEN1
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
MECLTFEXP_MEC->PJM
CLTF
7.813
SIGELTFEXP_SIGE->PJM
CLTF
0.234
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
TVALTFEXP_TVA->PJM
CLTF
7.703
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-5: W72_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: W72_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.55 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5822.84
MW Contribution:
3.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151041BRUNSWICKG3
50/50
8.447
972187AH1-678 GEN
50/50
19.381
315242AE2-183_GT2
50/50
10.565
315241AE2-183_GT1
50/50
10.537
972185AH1-677 GEN
50/50
38.19
970909AG2-566 GEN
50/50
3.771
3152661PLYWOOD A
50/50
0.739
3151581KERR 1
50/50
0.213
970535AG2-341 GEN
50/50
5.158
3144293JTRSVLE
50/50
0.685
970933AG2-581 GEN
Solar/Wind Harmer
67.393
3151051BRUNSWICKS1
50/50
17.536
3151021BRUNSWICKG1
50/50
8.447
971451AH1-221 GEN
50/50
25.651
315243AE2-183_GT3
50/50
10.565
3151531CLOVER1
50/50
10.604
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3144293JTRSVLE
50/50
0.685
3144293JTRSVLE
50/50
0.541
971629AH1-314 GEN
50/50
19.016
3151561HALLBR1
50/50
0.398
941031AE2-094 GEN
Solar/Wind Harmer
135.072
970919AG2-571 GEN
Solar/Wind Harmer
21.441
970087AG2-069 GEN
Solar/Wind Harmer
62.138
957481AF2-042 GEN
Solar/Wind Harmer
189.348
315693AD1-088 GEN
Solar/Wind Harmer
27.647
970401AG2-262 GEN
Solar/Wind Harmer
2.349
316131AB2-060 GEN
Solar/Wind Harmer
3.468
315785AD2-033 C
Solar/Wind Harmer
7.115
316034AC1-036 C
Solar/Wind Harmer
0.578
970685AG2-442 GEN
Solar/Wind Harmer
26.775
970099AG2-077 GEN
Solar/Wind Harmer
75.739
315687AD1-152 GEN
Solar/Wind Harmer
5.976
970301AG2-198 GEN
Solar/Wind Harmer
19.863
316248AF1-058 C
Solar/Wind Harmer
1.162
316118AC1-105 GEN
Solar/Wind Harmer
2.561
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.689
962561AG1-105 GEN
Solar/Wind Harmer
19.93
316237AB2-079_GEN
Solar/Wind Harmer
0.978
313527AB2-043 GEN
Solar/Wind Harmer
5.244
970323AG2-213 GEN
Solar/Wind Harmer
15.633
958211AF2-115 GEN
Solar/Wind Harmer
4.745
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.731
270013AE1-250 PV
Solar/Wind Harmer
3.03
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
942671AE2-283 GEN
Solar/Wind Harmer
5.365
316049AB1-081 GEN
Solar/Wind Harmer
1.526
316263AC1-034 GEN
Solar/Wind Harmer
6.648
961601AG1-000A GEN
Solar/Wind Harmer
5.451
316294AC1-161 GEN
Solar/Wind Helper
8.256
316185AD1-033 GEN
Solar/Wind Helper
1.908
3145506HICKORY
Solar/Wind Helper
1.594
3145506HICKORY
Solar/Wind Helper
0.956
3145506HICKORY
Solar/Wind Helper
0.239
316339AD2-160 GEN
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.482
3137176SLIGO L2192
Solar/Wind Helper
1.514
3130086AYDLETT
Solar/Wind Helper
1.503
316033AB2-134 GEN
Solar/Wind Helper
1.265
316349AD2-085 GEN
Solar/Wind Helper
1.611
3146386ELIZ CT
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.469
316156AD2-030 GEN
Solar/Wind Helper
0.52
315666AE1-190 GEN
Solar/Wind Helper
0.462
3142946ENON
Solar/Wind Helper
0.033
316487AF1-042 GEN
Solar/Wind Helper
0.335
315976AC1-164 GENA
Solar/Wind Helper
4.26
316169AC1-164_GENC
Solar/Wind Helper
3.68
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
316312AB1-027
Solar/Wind Helper
0.586
3143526WINTERP
Solar/Wind Helper
1.571
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.393
3144356SAPONY
Solar/Wind Helper
0.518
316315AB2-025 C
Solar/Wind Helper
0.441
3151031BRUNSWICKG2
50/50
8.447
970413AG2-270 GEN
50/50
46.18
3144293JTRSVLE
50/50
0.685
944011AF1-069 GEN
Solar/Wind Harmer
42.323
970917AG2-570 GEN
Solar/Wind Harmer
169.383
316478AD1-087 GEN
Solar/Wind Harmer
4.79
316003AC1-222 GEN
Solar/Wind Harmer
3.555
316222AC1-221 GEN
Solar/Wind Harmer
3.451
971683AH1-343 GEN
Solar/Wind Harmer
14.679
316283AC2-100 C
Solar/Wind Harmer
3.195
964241AG1-285 GEN
Solar/Wind Harmer
24.949
970257AG2-171 GEN
Solar/Wind Harmer
11.725
971775AH1-396 GEN
Solar/Wind Harmer
2.206
959311AF2-222 GEN
Solar/Wind Harmer
32.493
3147133PAMPLIN
Solar/Wind Harmer
-0.094
942461AE2-259 GEN
Solar/Wind Harmer
4.389
316123AC1-075 GEN
Solar/Wind Harmer
3.093
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270574AD1-017 GEN2
Solar/Wind Harmer
5.986
316217AC1-145 GEN
Solar/Wind Harmer
2.627
316197AC1-042 GEN
Solar/Wind Harmer
1.991
3147312GRETNA
Solar/Wind Harmer
-0.003
943811AF1-049 GEN
Solar/Wind Harmer
4.084
270336AE1-100 GEN
Solar/Wind Harmer
1.663
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.52
3138543CONSLDL
Solar/Wind Harmer
-0.008
3144873MCLAUGH
Solar/Wind Helper
0.01
3142956BIRDNECK
Solar/Wind Helper
0.274
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.765
3146456SLIGO L269
Solar/Wind Helper
0.38
316305AF2-043 C
Solar/Wind Helper
0.501
316246AF1-032 C
Solar/Wind Helper
0.426
316458AB2-190 GEN2
Solar/Wind Helper
2.044
316320Y1-086
Solar/Wind Helper
0.157
316321Z2-027
Solar/Wind Helper
0.516
3142946ENON
Solar/Wind Helper
0.111
316484AD2-074 GEN
Solar/Wind Helper
0.64
316075AC2-137 C
Solar/Wind Helper
0.493
316077AC2-138 C
Solar/Wind Helper
0.302
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.462
3141906WESTMOR
Solar/Wind Helper
0.121
3146626S HERTFORD
Solar/Wind Helper
0.296
316473AC1-191 GEN
Solar/Wind Helper
1.782
3145273HOLLAND
Solar/Wind Helper
0.198
966881AG1-559 GEN
Solar/Wind Helper
0.345
3146376EDENTON
Solar/Wind Helper
0.239
971563AH1-280 GEN
Solar/Wind Harmer
3.796
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.632
316129AC1-054 GEN
Solar/Wind Harmer
2.075
970223AG2-152 GEN
Solar/Wind Harmer
18.332
270016AE1-250 BESS
Solar/Wind Harmer
3.03
3147123OTTER R
Solar/Wind Harmer
-0.011
3146776BUCKING
Solar/Wind Harmer
-0.007
270018AE2-047 C O1
Solar/Wind Harmer
1.459
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.074
270030AE2-140 GEN
Solar/Wind Harmer
21.018
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.907
3142053HEARTS
Solar/Wind Harmer
0.167
315773AC2-141 GEN
Solar/Wind Helper
9.714
316375AC2-012 GEN
Solar/Wind Helper
1.078
316036AC1-147 C
Solar/Wind Helper
0.625
3145336SMITFLD
Solar/Wind Helper
1.566
3146456SLIGO L269
Solar/Wind Helper
0.38
319010AE1-072 C
Solar/Wind Helper
4.323
316072AD1-144
Solar/Wind Helper
0.429
316369SG1_INVT
Solar/Wind Helper
1.762
316381AD1-082 GEN
Solar/Wind Helper
1.86
316132AB2-190 GEN1
Solar/Wind Helper
2.044
315671AE2-027_GEN
Solar/Wind Helper
2.846
315662AE1-191 GEN
Solar/Wind Helper
1.847
316280AD1-041 GEN
Solar/Wind Helper
1.154
3141766HARMONY
Solar/Wind Helper
0.068
3138133OCRAN
Solar/Wind Helper
0.204
3142433PROV 92
Solar/Wind Helper
1.343
315975AC1-164 GENB
Solar/Wind Helper
0.126
316404AE1-155 C
Solar/Wind Helper
2.803
3142543TWELFTH
Solar/Wind Helper
0.031
964211AG1-282 GEN
Solar/Wind Helper
0.434
3141726DUNNSVL
Solar/Wind Helper
1.287
3146516WINFALL
Solar/Wind Helper
1.015
3146516WINFALL
Solar/Wind Helper
0.313
316337AD2-073 GEN
Solar/Wind Helper
0.473
3142416OLDCHRC
Solar/Wind Helper
0.798
3142416OLDCHRC
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.571
3143226MDLTHAN
Solar/Wind Helper
0.297
315611Z1-036_GEN2
Solar/Wind Helper
1.391
3130156CHOWAN
Solar/Wind Helper
0.24
963041AG1-153 GEN
50/50
17.101
315244AE2-183_ST
50/50
18.346
3151541CLOVER2
50/50
10.523
3151601KERR 3
50/50
0.597
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
3151631KERR 6
50/50
0.597
971967AH1-528 GEN
Solar/Wind Harmer
141.954
970673AG2-436 GEN
Solar/Wind Harmer
157.592
970533AG2-339 GEN
Solar/Wind Harmer
48.444
970085AG2-068 GEN
Solar/Wind Harmer
41.425
970581AG2-369 GEN
Solar/Wind Harmer
35.626
316486AD2-202 GEN
Solar/Wind Harmer
1.403
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316238AB2-078_GEN
Solar/Wind Harmer
0.978
316239AB2-077_GEN
Solar/Wind Harmer
0.978
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
21.753
970681AG2-440 GEN
Solar/Wind Harmer
14.438
946301AF1-294 GEN
Solar/Wind Harmer
7.781
961791AG1-021 GEN
Solar/Wind Harmer
3.796
270455AD2-022 GEN
Solar/Wind Harmer
4.996
270457AD2-023 GEN
Solar/Wind Harmer
2.533
970831AG2-522 GEN
Solar/Wind Harmer
10.881
971845AH1-439 GEN
Solar/Wind Harmer
9.987
316322AB2-045
Solar/Wind Harmer
0.602
270197AD1-017 GEN1
Solar/Wind Harmer
1.796
270069AE2-166 C O1
Solar/Wind Harmer
8.499
316316AC1-027 C
Solar/Wind Helper
0.642
316236AE1-162_GEN
Solar/Wind Helper
0.528
316018AA1-139 ULT2
Solar/Wind Helper
1.661
3143316POE
Solar/Wind Helper
1.484
316382AG1-145 C
Solar/Wind Helper
0.496
316159AE1-175 C
Solar/Wind Helper
0.56
315697AD1-025 GEN
Solar/Wind Helper
4.181
957831AF2-077 GEN
Solar/Wind Helper
0.492
315839AE2-212 C
Solar/Wind Helper
0.483
313526AB2-022
Solar/Wind Helper
0.535
957601AF2-054 GEN
Solar/Wind Helper
0.461
3141873WAN 176
Solar/Wind Helper
0.069
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316059AD1-063 C
Solar/Wind Helper
0.344
3141913WHIT STONE
Solar/Wind Helper
0.341
3138133OCRAN
Solar/Wind Helper
0.102
3143873LANEXA
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.135
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.321
316233AE1-074 FULL
Solar/Wind Helper
0.461
316468AD1-105 GEN
Solar/Wind Helper
1.325
315800Z1-036_GEN1
Solar/Wind Helper
1.391
3130156CHOWAN
Solar/Wind Helper
0.24
3130156CHOWAN
Solar/Wind Helper
0.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.758
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.424
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CPLELTFEXP_CPLE->PJM
CLTF
20.605
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.302
LAGNLTFEXP_LAGN->PJM
CLTF
15.386
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.197
TVALTFEXP_TVA->PJM
CLTF
7.676
NYPJM->LTFIMP_NY
CLTF
2.47
LGEELTFEXP_LGEE->PJM
CLTF
2.835
WECLTFEXP_WEC->PJM
CLTF
1.484
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: XT585_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT585_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.34 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5462.74
MW Contribution:
3.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151041BRUNSWICKG3
50/50
8.509
972187AH1-678 GEN
50/50
19.524
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970535AG2-341 GEN
50/50
5.153
3144293JTRSVLE
50/50
0.686
970933AG2-581 GEN
Solar/Wind Harmer
67.888
970099AG2-077 GEN
Solar/Wind Harmer
76.247
315687AD1-152 GEN
Solar/Wind Harmer
6.011
970301AG2-198 GEN
Solar/Wind Harmer
19.981
316248AF1-058 C
Solar/Wind Harmer
1.167
316118AC1-105 GEN
Solar/Wind Harmer
2.569
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.704
962561AG1-105 GEN
Solar/Wind Harmer
19.962
316237AB2-079_GEN
Solar/Wind Harmer
0.977
313527AB2-043 GEN
Solar/Wind Harmer
5.238
970323AG2-213 GEN
Solar/Wind Harmer
15.637
958211AF2-115 GEN
Solar/Wind Harmer
4.752
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.796
270013AE1-250 PV
Solar/Wind Harmer
3.04
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
3151031BRUNSWICKG2
50/50
8.509
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
970917AG2-570 GEN
Solar/Wind Harmer
170.595
316478AD1-087 GEN
Solar/Wind Harmer
4.82
316003AC1-222 GEN
Solar/Wind Harmer
3.569
316222AC1-221 GEN
Solar/Wind Harmer
3.464
971683AH1-343 GEN
Solar/Wind Harmer
14.738
316283AC2-100 C
Solar/Wind Harmer
3.207
964241AG1-285 GEN
Solar/Wind Harmer
24.931
970257AG2-171 GEN
Solar/Wind Harmer
11.728
971775AH1-396 GEN
Solar/Wind Harmer
2.207
959311AF2-222 GEN
Solar/Wind Harmer
32.508
3147133PAMPLIN
Solar/Wind Harmer
-0.094
942461AE2-259 GEN
Solar/Wind Harmer
4.405
316123AC1-075 GEN
Solar/Wind Harmer
3.105
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270574AD1-017 GEN2
Solar/Wind Harmer
6.006
316217AC1-145 GEN
Solar/Wind Harmer
2.636
316197AC1-042 GEN
Solar/Wind Harmer
1.998
3147312GRETNA
Solar/Wind Harmer
-0.003
943811AF1-049 GEN
Solar/Wind Harmer
4.097
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.382
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
316305AF2-043 C
Solar/Wind Helper
0.5
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316320Y1-086
Solar/Wind Helper
0.157
3142946ENON
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.514
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.826
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
942671AE2-283 GEN
Solar/Wind Harmer
5.385
316049AB1-081 GEN
Solar/Wind Harmer
1.49
316263AC1-034 GEN
Solar/Wind Harmer
6.491
961601AG1-000A GEN
Solar/Wind Harmer
5.315
316294AC1-161 GEN
Solar/Wind Helper
8.161
316185AD1-033 GEN
Solar/Wind Helper
1.897
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316240AF1-291 C
Solar/Wind Helper
0.501
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316487AF1-042 GEN
Solar/Wind Helper
0.338
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
316435W1029_GEN3
Solar/Wind Helper
1.293
316312AB1-027
Solar/Wind Helper
0.598
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
963041AG1-153 GEN
50/50
17.227
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151601KERR 3
50/50
0.597
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
3151631KERR 6
50/50
0.597
971967AH1-528 GEN
Solar/Wind Harmer
143.019
970085AG2-068 GEN
Solar/Wind Harmer
41.719
970581AG2-369 GEN
Solar/Wind Harmer
35.878
316486AD2-202 GEN
Solar/Wind Harmer
1.412
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316238AB2-078_GEN
Solar/Wind Harmer
0.977
316239AB2-077_GEN
Solar/Wind Harmer
0.977
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
21.774
970681AG2-440 GEN
Solar/Wind Harmer
14.452
946301AF1-294 GEN
Solar/Wind Harmer
7.794
961791AG1-021 GEN
Solar/Wind Harmer
3.802
270455AD2-022 GEN
Solar/Wind Harmer
5.012
270457AD2-023 GEN
Solar/Wind Harmer
2.542
970831AG2-522 GEN
Solar/Wind Harmer
10.747
971845AH1-439 GEN
Solar/Wind Harmer
10.037
316322AB2-045
Solar/Wind Harmer
0.605
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
270069AE2-166 C O1
Solar/Wind Harmer
8.528
3143316POE
Solar/Wind Helper
1.638
316316AC1-027 C
Solar/Wind Helper
0.639
3151051BRUNSWICKS1
50/50
17.665
3151021BRUNSWICKG1
50/50
8.509
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
971629AH1-314 GEN
50/50
19.08
3151561HALLBR1
50/50
0.4
970919AG2-571 GEN
Solar/Wind Harmer
21.594
970087AG2-069 GEN
Solar/Wind Harmer
62.578
957481AF2-042 GEN
Solar/Wind Harmer
190.618
315693AD1-088 GEN
Solar/Wind Harmer
27.824
970401AG2-262 GEN
Solar/Wind Harmer
2.354
316131AB2-060 GEN
Solar/Wind Harmer
3.464
315785AD2-033 C
Solar/Wind Harmer
7.115
316034AC1-036 C
Solar/Wind Harmer
0.578
970685AG2-442 GEN
Solar/Wind Harmer
26.809
971563AH1-280 GEN
Solar/Wind Harmer
3.802
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.535
316129AC1-054 GEN
Solar/Wind Harmer
2.056
970223AG2-152 GEN
Solar/Wind Harmer
18.394
270016AE1-250 BESS
Solar/Wind Harmer
3.04
3147123OTTER R
Solar/Wind Harmer
-0.011
3146776BUCKING
Solar/Wind Harmer
-0.007
270018AE2-047 C O1
Solar/Wind Harmer
1.464
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.096
270030AE2-140 GEN
Solar/Wind Harmer
21.088
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.862
3142053HEARTS
Solar/Wind Harmer
0.163
315773AC2-141 GEN
Solar/Wind Helper
9.603
316375AC2-012 GEN
Solar/Wind Helper
1.073
316036AC1-147 C
Solar/Wind Helper
0.622
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
315671AE2-027_GEN
Solar/Wind Helper
3.055
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316072AD1-144
Solar/Wind Helper
0.428
316369SG1_INVT
Solar/Wind Helper
1.805
316132AB2-190 GEN1
Solar/Wind Helper
2.11
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
3138133OCRAN
Solar/Wind Helper
0.206
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
316236AE1-162_GEN
Solar/Wind Helper
0.53
315839AE2-212 C
Solar/Wind Helper
0.524
316018AA1-139 ULT2
Solar/Wind Helper
1.653
315697AD1-025 GEN
Solar/Wind Helper
4.281
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
957831AF2-077 GEN
Solar/Wind Helper
0.494
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141873WAN 176
Solar/Wind Helper
0.07
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.344
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
316468AD1-105 GEN
Solar/Wind Helper
1.353
315800Z1-036_GEN1
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
MECLTFEXP_MEC->PJM
CLTF
7.813
SIGELTFEXP_SIGE->PJM
CLTF
0.234
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
TVALTFEXP_TVA->PJM
CLTF
7.703
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 54472_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 54472_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.29 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:2980.61
MW Contribution:
2.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
7.987
3151051BRUNSWICKS1
50/50
8.582
3151021BRUNSWICKG1
50/50
4.134
971451AH1-221 GEN
50/50
12.554
315243AE2-183_GT3
50/50
3.866
3151591KERR 2
50/50
0.435
3151641KERR 7
50/50
0.435
3144293JTRSVLE
50/50
0.518
3144293JTRSVLE
50/50
0.409
971629AH1-314 GEN
50/50
11.606
957481AF2-042 GEN
Solar/Wind Harmer
144.085
315693AD1-088 GEN
Solar/Wind Harmer
21.044
970919AG2-571 GEN
Solar/Wind Harmer
10.571
970087AG2-069 GEN
Solar/Wind Harmer
30.719
970401AG2-262 GEN
Solar/Wind Harmer
1.701
316131AB2-060 GEN
Solar/Wind Harmer
2.562
315785AD2-033 C
Solar/Wind Harmer
5.309
316034AC1-036 C
Solar/Wind Harmer
0.432
970685AG2-442 GEN
Solar/Wind Harmer
20.206
971563AH1-280 GEN
Solar/Wind Harmer
2.874
3146926FARMVIL
Solar/Wind Harmer
-0.013
971065AG2-659 GEN
Solar/Wind Harmer
9.225
316129AC1-054 GEN
Solar/Wind Harmer
1.517
3146776BUCKING
Solar/Wind Harmer
-0.006
970223AG2-152 GEN
Solar/Wind Harmer
11.336
315773AC2-141 GEN
Solar/Wind Helper
5.481
315671AE2-027_GEN
Solar/Wind Helper
1.833
3151041BRUNSWICKG3
50/50
4.134
972187AH1-678 GEN
50/50
9.485
970909AG2-566 GEN
50/50
2.902
3152661PLYWOOD A
50/50
0.531
315242AE2-183_GT2
50/50
3.866
3151541CLOVER2
50/50
7.926
963041AG1-153 GEN
50/50
8.369
315244AE2-183_ST
50/50
6.714
3151601KERR 3
50/50
0.435
3151611KERR 4
50/50
0.435
3151621KERR 5
50/50
0.435
3151631KERR 6
50/50
0.435
971967AH1-528 GEN
Solar/Wind Harmer
109.533
316486AD2-202 GEN
Solar/Wind Harmer
1.056
970085AG2-068 GEN
Solar/Wind Harmer
20.479
970581AG2-369 GEN
Solar/Wind Harmer
17.612
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.72
316239AB2-077_GEN
Solar/Wind Harmer
0.72
3144303KENBRDG
Solar/Wind Harmer
-0.019
970683AG2-441 GEN
Solar/Wind Harmer
16.371
970681AG2-440 GEN
Solar/Wind Harmer
10.866
946301AF1-294 GEN
Solar/Wind Harmer
5.891
961791AG1-021 GEN
Solar/Wind Harmer
2.874
270455AD2-022 GEN
Solar/Wind Harmer
3.038
270457AD2-023 GEN
Solar/Wind Harmer
1.541
970831AG2-522 GEN
Solar/Wind Harmer
7.961
971845AH1-439 GEN
Solar/Wind Harmer
8.061
316322AB2-045
Solar/Wind Harmer
0.488
970673AG2-436 GEN
Solar/Wind Harmer
30.81
3143316POE
Solar/Wind Helper
1.003
315839AE2-212 C
Solar/Wind Helper
0.317
970413AG2-270 GEN
50/50
34.783
3151031BRUNSWICKG2
50/50
4.134
3144293JTRSVLE
50/50
0.518
316478AD1-087 GEN
Solar/Wind Harmer
3.607
970917AG2-570 GEN
Solar/Wind Harmer
83.508
316003AC1-222 GEN
Solar/Wind Harmer
2.539
971683AH1-343 GEN
Solar/Wind Harmer
10.454
964241AG1-285 GEN
Solar/Wind Harmer
18.498
970257AG2-171 GEN
Solar/Wind Harmer
8.769
971775AH1-396 GEN
Solar/Wind Harmer
1.65
959311AF2-222 GEN
Solar/Wind Harmer
24.346
3147133PAMPLIN
Solar/Wind Harmer
-0.071
942461AE2-259 GEN
Solar/Wind Harmer
3.379
3146926FARMVIL
Solar/Wind Harmer
-0.013
316222AC1-221 GEN
Solar/Wind Harmer
2.214
316283AC2-100 C
Solar/Wind Harmer
2.042
316123AC1-075 GEN
Solar/Wind Harmer
2.185
3146776BUCKING
Solar/Wind Harmer
-0.005
315241AE2-183_GT1
50/50
3.856
972185AH1-677 GEN
50/50
13.975
3151581KERR 1
50/50
0.155
970535AG2-341 GEN
50/50
3.78
3144293JTRSVLE
50/50
0.518
970933AG2-581 GEN
Solar/Wind Harmer
51.867
970099AG2-077 GEN
Solar/Wind Harmer
57.634
315687AD1-152 GEN
Solar/Wind Harmer
4.402
970301AG2-198 GEN
Solar/Wind Harmer
15.282
316248AF1-058 C
Solar/Wind Harmer
0.832
316118AC1-105 GEN
Solar/Wind Harmer
1.844
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.568
962561AG1-105 GEN
Solar/Wind Harmer
14.47
316237AB2-079_GEN
Solar/Wind Harmer
0.72
313527AB2-043 GEN
Solar/Wind Harmer
3.87
970323AG2-213 GEN
Solar/Wind Harmer
11.693
958211AF2-115 GEN
Solar/Wind Harmer
3.592
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
942751AE2-291 GEN
Solar/Wind Harmer
11.764
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.005
316294AC1-161 GEN
Solar/Wind Helper
4.658
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.693
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.444
MECLTFEXP_MEC->PJM
CLTF
4.621
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CPLELTFEXP_CPLE->PJM
CLTF
11.798
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.275
LAGNLTFEXP_LAGN->PJM
CLTF
8.951
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.467
TVALTFEXP_TVA->PJM
CLTF
4.473
NYPJM->LTFIMP_NY
CLTF
1.41
LGEELTFEXP_LGEE->PJM
CLTF
1.7
WECLTFEXP_WEC->PJM
CLTF
0.889

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.98 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4842.86
MW Contribution:
3.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
44.999
970099AG2-077 GEN
Solar/Wind Harmer
50.746
970301AG2-198 GEN
Solar/Wind Harmer
13.237
316118AC1-105 GEN
Solar/Wind Harmer
0.762
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.492
962561AG1-105 GEN
Solar/Wind Harmer
13.495
970323AG2-213 GEN
Solar/Wind Harmer
10.454
958211AF2-115 GEN
Solar/Wind Harmer
2.847
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.188
942751AE2-291 GEN
Solar/Wind Harmer
11.487
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
942671AE2-283 GEN
Solar/Wind Harmer
3.281
316049AB1-081 GEN
Solar/Wind Harmer
0.667
316263AC1-034 GEN
Solar/Wind Harmer
4.456
961601AG1-000A GEN
Solar/Wind Harmer
2.039
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
47.021
957481AF2-042 GEN
Solar/Wind Harmer
126.864
315693AD1-088 GEN
Solar/Wind Harmer
20.828
970401AG2-262 GEN
Solar/Wind Harmer
1.678
316131AB2-060 GEN
Solar/Wind Harmer
0.788
315785AD2-033 C
Solar/Wind Harmer
1.994
316034AC1-036 C
Solar/Wind Harmer
0.016
970685AG2-442 GEN
Solar/Wind Harmer
17.866
971563AH1-280 GEN
Solar/Wind Harmer
2.531
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.454
316129AC1-054 GEN
Solar/Wind Harmer
0.693
970223AG2-152 GEN
Solar/Wind Harmer
12.084
3147123OTTER R
Solar/Wind Harmer
0.088
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.219
270030AE2-140 GEN
Solar/Wind Harmer
13.827
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.417
3142053HEARTS
Solar/Wind Harmer
0.206
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
53.44
316478AD1-087 GEN
Solar/Wind Harmer
1.514
316222AC1-221 GEN
Solar/Wind Harmer
1.167
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.037
964241AG1-285 GEN
Solar/Wind Harmer
16.717
970257AG2-171 GEN
Solar/Wind Harmer
7.84
971775AH1-396 GEN
Solar/Wind Harmer
0.392
959311AF2-222 GEN
Solar/Wind Harmer
21.675
3147133PAMPLIN
Solar/Wind Harmer
0.736
316123AC1-075 GEN
Solar/Wind Harmer
0.308
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.131
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.118
971623AH1-311 GEN
Solar/Wind Harmer
0.235
961601AG1-000A GEN
Solar/Wind Harmer
8.154
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
971967AH1-528 GEN
Solar/Wind Harmer
94.459
970085AG2-068 GEN
Solar/Wind Harmer
31.347
970581AG2-369 GEN
Solar/Wind Harmer
26.958
316486AD2-202 GEN
Solar/Wind Harmer
0.444
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
14.525
970681AG2-440 GEN
Solar/Wind Harmer
9.64
946301AF1-294 GEN
Solar/Wind Harmer
4.682
961791AG1-021 GEN
Solar/Wind Harmer
2.278
970831AG2-522 GEN
Solar/Wind Harmer
7.24
971845AH1-439 GEN
Solar/Wind Harmer
6.517
270197AD1-017 GEN1
Solar/Wind Harmer
0.942
270069AE2-166 C O1
Solar/Wind Harmer
5.589
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.0 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5245.63
MW Contribution:
3.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
59.249
970099AG2-077 GEN
Solar/Wind Harmer
66.815
315687AD1-152 GEN
Solar/Wind Harmer
5.329
970301AG2-198 GEN
Solar/Wind Harmer
17.428
316248AF1-058 C
Solar/Wind Harmer
1.044
316118AC1-105 GEN
Solar/Wind Harmer
2.295
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.865
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
168.871
316478AD1-087 GEN
Solar/Wind Harmer
4.24
316003AC1-222 GEN
Solar/Wind Harmer
3.197
316222AC1-221 GEN
Solar/Wind Harmer
3.212
316283AC2-100 C
Solar/Wind Harmer
2.976
971683AH1-343 GEN
Solar/Wind Harmer
13.215
964241AG1-285 GEN
Solar/Wind Harmer
22.01
970257AG2-171 GEN
Solar/Wind Harmer
10.323
971775AH1-396 GEN
Solar/Wind Harmer
1.942
959311AF2-222 GEN
Solar/Wind Harmer
28.596
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.792
942461AE2-259 GEN
Solar/Wind Harmer
3.838
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.599
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.851
316217AC1-145 GEN
Solar/Wind Harmer
2.402
316197AC1-042 GEN
Solar/Wind Harmer
1.821
3147312GRETNA
Solar/Wind Harmer
-0.003
270336AE1-100 GEN
Solar/Wind Harmer
1.568
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.128
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
962561AG1-105 GEN
Solar/Wind Harmer
17.768
316237AB2-079_GEN
Solar/Wind Harmer
0.865
313527AB2-043 GEN
Solar/Wind Harmer
4.632
970323AG2-213 GEN
Solar/Wind Harmer
13.764
958211AF2-115 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.125
270013AE1-250 PV
Solar/Wind Harmer
2.845
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.906
316049AB1-081 GEN
Solar/Wind Harmer
1.418
316263AC1-034 GEN
Solar/Wind Harmer
6.176
961601AG1-000A GEN
Solar/Wind Harmer
5.064
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
971967AH1-528 GEN
Solar/Wind Harmer
124.702
970085AG2-068 GEN
Solar/Wind Harmer
41.274
970581AG2-369 GEN
Solar/Wind Harmer
35.495
316486AD2-202 GEN
Solar/Wind Harmer
1.242
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.022
316238AB2-078_GEN
Solar/Wind Harmer
0.865
316239AB2-077_GEN
Solar/Wind Harmer
0.865
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.124
970681AG2-440 GEN
Solar/Wind Harmer
12.693
946301AF1-294 GEN
Solar/Wind Harmer
6.831
961791AG1-021 GEN
Solar/Wind Harmer
3.332
270455AD2-022 GEN
Solar/Wind Harmer
4.718
270457AD2-023 GEN
Solar/Wind Harmer
2.392
970831AG2-522 GEN
Solar/Wind Harmer
9.533
971845AH1-439 GEN
Solar/Wind Harmer
8.58
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
316322AB2-045
Solar/Wind Harmer
0.516
270069AE2-166 C O1
Solar/Wind Harmer
8.011
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
61.91
957481AF2-042 GEN
Solar/Wind Harmer
167.038
315693AD1-088 GEN
Solar/Wind Harmer
24.377
970401AG2-262 GEN
Solar/Wind Harmer
2.098
316131AB2-060 GEN
Solar/Wind Harmer
3.062
315785AD2-033 C
Solar/Wind Harmer
6.268
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.524
971563AH1-280 GEN
Solar/Wind Harmer
3.332
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.131
316129AC1-054 GEN
Solar/Wind Harmer
1.825
970223AG2-152 GEN
Solar/Wind Harmer
17.233
270016AE1-250 BESS
Solar/Wind Harmer
2.845
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.377
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.554
270030AE2-140 GEN
Solar/Wind Harmer
19.819
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.772
3142053HEARTS
Solar/Wind Harmer
0.155
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.56 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5223.84
MW Contribution:
3.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.378
970413AG2-270 GEN
50/50
40.656
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
167.755
316478AD1-087 GEN
Solar/Wind Harmer
4.218
316003AC1-222 GEN
Solar/Wind Harmer
3.188
316222AC1-221 GEN
Solar/Wind Harmer
3.202
316283AC2-100 C
Solar/Wind Harmer
2.967
971683AH1-343 GEN
Solar/Wind Harmer
13.175
964241AG1-285 GEN
Solar/Wind Harmer
22.056
970257AG2-171 GEN
Solar/Wind Harmer
10.334
971775AH1-396 GEN
Solar/Wind Harmer
1.944
959311AF2-222 GEN
Solar/Wind Harmer
28.621
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.783
942461AE2-259 GEN
Solar/Wind Harmer
3.829
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.584
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.841
316217AC1-145 GEN
Solar/Wind Harmer
2.396
316197AC1-042 GEN
Solar/Wind Harmer
1.816
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
315242AE2-183_GT2
50/50
11.03
315241AE2-183_GT1
50/50
11.001
972185AH1-677 GEN
50/50
39.871
3151041BRUNSWICKG3
50/50
8.378
972187AH1-678 GEN
50/50
19.224
970909AG2-566 GEN
50/50
3.293
3152661PLYWOOD A
50/50
0.662
3151581KERR 1
50/50
0.19
970535AG2-341 GEN
50/50
4.581
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
58.871
970099AG2-077 GEN
Solar/Wind Harmer
66.433
315687AD1-152 GEN
Solar/Wind Harmer
5.303
970301AG2-198 GEN
Solar/Wind Harmer
17.344
316248AF1-058 C
Solar/Wind Harmer
1.041
316118AC1-105 GEN
Solar/Wind Harmer
2.29
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.859
962561AG1-105 GEN
Solar/Wind Harmer
17.76
316237AB2-079_GEN
Solar/Wind Harmer
0.867
313527AB2-043 GEN
Solar/Wind Harmer
4.644
970323AG2-213 GEN
Solar/Wind Harmer
13.779
958211AF2-115 GEN
Solar/Wind Harmer
4.164
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.08
270013AE1-250 PV
Solar/Wind Harmer
2.837
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.893
315244AE2-183_ST
50/50
19.154
963041AG1-153 GEN
50/50
16.962
3151541CLOVER2
50/50
9.264
3151601KERR 3
50/50
0.532
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
971967AH1-528 GEN
Solar/Wind Harmer
123.886
970085AG2-068 GEN
Solar/Wind Harmer
41.004
970581AG2-369 GEN
Solar/Wind Harmer
35.263
316486AD2-202 GEN
Solar/Wind Harmer
1.235
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.867
316239AB2-077_GEN
Solar/Wind Harmer
0.867
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.131
970681AG2-440 GEN
Solar/Wind Harmer
12.698
946301AF1-294 GEN
Solar/Wind Harmer
6.829
961791AG1-021 GEN
Solar/Wind Harmer
3.331
270455AD2-022 GEN
Solar/Wind Harmer
4.705
270457AD2-023 GEN
Solar/Wind Harmer
2.386
970831AG2-522 GEN
Solar/Wind Harmer
9.671
971845AH1-439 GEN
Solar/Wind Harmer
8.548
270197AD1-017 GEN1
Solar/Wind Harmer
1.675
316322AB2-045
Solar/Wind Harmer
0.514
315243AE2-183_GT3
50/50
11.03
3151051BRUNSWICKS1
50/50
17.394
3151021BRUNSWICKG1
50/50
8.378
971451AH1-221 GEN
50/50
25.443
3151531CLOVER1
50/50
9.336
3151591KERR 2
50/50
0.532
3151641KERR 7
50/50
0.532
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.474
971629AH1-314 GEN
50/50
17.894
3151561HALLBR1
50/50
0.362
970919AG2-571 GEN
Solar/Wind Harmer
21.235
970087AG2-069 GEN
Solar/Wind Harmer
61.506
957481AF2-042 GEN
Solar/Wind Harmer
166.083
315693AD1-088 GEN
Solar/Wind Harmer
24.245
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316131AB2-060 GEN
Solar/Wind Harmer
3.07
315785AD2-033 C
Solar/Wind Harmer
6.277
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.525
971563AH1-280 GEN
Solar/Wind Harmer
3.331
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.235
316129AC1-054 GEN
Solar/Wind Harmer
1.845
970223AG2-152 GEN
Solar/Wind Harmer
17.186
270016AE1-250 BESS
Solar/Wind Harmer
2.837
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.373
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.539
270030AE2-140 GEN
Solar/Wind Harmer
19.766
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.26
3144873MCLAUGH
Solar/Wind Helper
0.01
3142956BIRDNECK
Solar/Wind Helper
0.258
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.667
3146456SLIGO L269
Solar/Wind Helper
0.359
316305AF2-043 C
Solar/Wind Helper
0.474
316246AF1-032 C
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
1.935
316320Y1-086
Solar/Wind Helper
0.149
316321Z2-027
Solar/Wind Helper
0.487
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.606
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.296
316223AC1-118
Solar/Wind Helper
0.438
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.279
316473AC1-191 GEN
Solar/Wind Helper
1.693
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.328
316049AB1-081 GEN
Solar/Wind Harmer
1.452
316263AC1-034 GEN
Solar/Wind Harmer
6.326
961601AG1-000A GEN
Solar/Wind Harmer
5.194
316294AC1-161 GEN
Solar/Wind Helper
7.794
316185AD1-033 GEN
Solar/Wind Helper
1.802
3145506HICKORY
Solar/Wind Helper
1.505
3145506HICKORY
Solar/Wind Helper
0.903
3145506HICKORY
Solar/Wind Helper
0.226
316339AD2-160 GEN
Solar/Wind Helper
1.399
316388AE2-253 GEN
Solar/Wind Helper
1.399
3137176SLIGO L2192
Solar/Wind Helper
1.43
3130086AYDLETT
Solar/Wind Helper
1.419
316033AB2-134 GEN
Solar/Wind Helper
1.198
316349AD2-085 GEN
Solar/Wind Helper
1.524
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.493
315666AE1-190 GEN
Solar/Wind Helper
0.437
3142946ENON
Solar/Wind Helper
0.031
316487AF1-042 GEN
Solar/Wind Helper
0.317
315976AC1-164 GENA
Solar/Wind Helper
4.039
316169AC1-164_GENC
Solar/Wind Helper
3.489
316431W1029_GEN1
Solar/Wind Helper
1.223
316433W1029_GEN2
Solar/Wind Helper
1.223
316435W1029_GEN3
Solar/Wind Helper
1.223
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
316312AB1-027
Solar/Wind Helper
0.557
3143526WINTERP
Solar/Wind Helper
1.497
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.491
316315AB2-025 C
Solar/Wind Helper
0.418
3146376EDENTON
Solar/Wind Helper
0.226
270069AE2-166 C O1
Solar/Wind Harmer
7.989
316316AC1-027 C
Solar/Wind Helper
0.607
316236AE1-162_GEN
Solar/Wind Helper
0.499
316018AA1-139 ULT2
Solar/Wind Helper
1.569
3143316POE
Solar/Wind Helper
1.405
316382AG1-145 C
Solar/Wind Helper
0.47
316159AE1-175 C
Solar/Wind Helper
0.53
315697AD1-025 GEN
Solar/Wind Helper
3.957
957831AF2-077 GEN
Solar/Wind Helper
0.465
315839AE2-212 C
Solar/Wind Helper
0.458
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.437
3141873WAN 176
Solar/Wind Helper
0.065
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.44
316468AD1-105 GEN
Solar/Wind Helper
1.26
315800Z1-036_GEN1
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.815
3142053HEARTS
Solar/Wind Harmer
0.159
315773AC2-141 GEN
Solar/Wind Helper
9.171
316375AC2-012 GEN
Solar/Wind Helper
1.018
316036AC1-147 C
Solar/Wind Helper
0.591
3145336SMITFLD
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.359
319010AE1-072 C
Solar/Wind Helper
4.082
316072AD1-144
Solar/Wind Helper
0.405
316369SG1_INVT
Solar/Wind Helper
1.668
316381AD1-082 GEN
Solar/Wind Helper
1.76
316132AB2-190 GEN1
Solar/Wind Helper
1.935
315671AE2-027_GEN
Solar/Wind Helper
2.696
315662AE1-191 GEN
Solar/Wind Helper
1.75
316280AD1-041 GEN
Solar/Wind Helper
1.093
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.273
315975AC1-164 GENB
Solar/Wind Helper
0.119
316404AE1-155 C
Solar/Wind Helper
2.656
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.411
3141726DUNNSVL
Solar/Wind Helper
1.22
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
316337AD2-073 GEN
Solar/Wind Helper
0.449
3142416OLDCHRC
Solar/Wind Helper
0.758
3142416OLDCHRC
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.497
3143226MDLTHAN
Solar/Wind Helper
0.284
315611Z1-036_GEN2
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.147
MECLTFEXP_MEC->PJM
CLTF
7.373
SIGELTFEXP_SIGE->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
19.725
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.242
LAGNLTFEXP_LAGN->PJM
CLTF
14.661
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.209
TVALTFEXP_TVA->PJM
CLTF
7.311
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.679
WECLTFEXP_WEC->PJM
CLTF
1.402
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.0 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5145.98
MW Contribution:
3.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
10.936
315241AE2-183_GT1
50/50
10.907
972185AH1-677 GEN
50/50
39.531
3151041BRUNSWICKG3
50/50
8.307
972187AH1-678 GEN
50/50
19.06
970909AG2-566 GEN
50/50
3.258
3152661PLYWOOD A
50/50
0.655
3151581KERR 1
50/50
0.188
970535AG2-341 GEN
50/50
4.523
3144293JTRSVLE
50/50
0.593
970933AG2-581 GEN
Solar/Wind Harmer
58.356
970099AG2-077 GEN
Solar/Wind Harmer
65.833
315687AD1-152 GEN
Solar/Wind Harmer
5.255
970301AG2-198 GEN
Solar/Wind Harmer
17.157
316248AF1-058 C
Solar/Wind Harmer
1.031
316118AC1-105 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.78
962561AG1-105 GEN
Solar/Wind Harmer
17.549
316237AB2-079_GEN
Solar/Wind Harmer
0.854
313527AB2-043 GEN
Solar/Wind Harmer
4.577
970323AG2-213 GEN
Solar/Wind Harmer
13.586
958211AF2-115 GEN
Solar/Wind Harmer
4.107
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.933
270013AE1-250 PV
Solar/Wind Harmer
2.814
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.846
316049AB1-081 GEN
Solar/Wind Harmer
1.446
316263AC1-034 GEN
Solar/Wind Harmer
6.299
961601AG1-000A GEN
Solar/Wind Harmer
5.168
316294AC1-161 GEN
Solar/Wind Helper
7.251
316240AF1-291 C
Solar/Wind Helper
0.472
316033AB2-134 GEN
Solar/Wind Helper
1.145
316185AD1-033 GEN
Solar/Wind Helper
1.553
3145506HICKORY
Solar/Wind Helper
1.296
3145506HICKORY
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.194
3144356SAPONY
Solar/Wind Helper
0.58
316315AB2-025 C
Solar/Wind Helper
0.494
316339AD2-160 GEN
Solar/Wind Helper
1.203
316388AE2-253 GEN
Solar/Wind Helper
1.203
316156AD2-030 GEN
Solar/Wind Helper
0.471
3142946ENON
Solar/Wind Helper
0.031
315666AE1-190 GEN
Solar/Wind Helper
0.419
3137176SLIGO L2192
Solar/Wind Helper
1.227
316349AD2-085 GEN
Solar/Wind Helper
1.397
315976AC1-164 GENA
Solar/Wind Helper
3.933
316169AC1-164_GENC
Solar/Wind Helper
3.397
3130086AYDLETT
Solar/Wind Helper
1.217
316487AF1-042 GEN
Solar/Wind Helper
0.305
3143526WINTERP
Solar/Wind Helper
1.516
316312AB1-027
Solar/Wind Helper
0.551
3146386ELIZ CT
Solar/Wind Helper
0.282
966871AG1-558 GEN
Solar/Wind Helper
0.375
316431W1029_GEN1
Solar/Wind Helper
1.035
316433W1029_GEN2
Solar/Wind Helper
1.035
3151031BRUNSWICKG2
50/50
8.307
970413AG2-270 GEN
50/50
40.285
3144293JTRSVLE
50/50
0.593
970917AG2-570 GEN
Solar/Wind Harmer
166.334
316478AD1-087 GEN
Solar/Wind Harmer
4.179
316003AC1-222 GEN
Solar/Wind Harmer
3.156
316222AC1-221 GEN
Solar/Wind Harmer
3.175
316283AC2-100 C
Solar/Wind Harmer
2.943
971683AH1-343 GEN
Solar/Wind Harmer
13.046
964241AG1-285 GEN
Solar/Wind Harmer
21.742
970257AG2-171 GEN
Solar/Wind Harmer
10.19
971775AH1-396 GEN
Solar/Wind Harmer
1.917
959311AF2-222 GEN
Solar/Wind Harmer
28.221
3147133PAMPLIN
Solar/Wind Harmer
-0.081
316123AC1-075 GEN
Solar/Wind Harmer
2.756
942461AE2-259 GEN
Solar/Wind Harmer
3.778
3146926FARMVIL
Solar/Wind Harmer
-0.014
270574AD1-017 GEN2
Solar/Wind Harmer
5.536
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.808
316217AC1-145 GEN
Solar/Wind Harmer
2.372
316197AC1-042 GEN
Solar/Wind Harmer
1.798
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.55
961601AG1-000A GEN
Solar/Wind Harmer
5.233
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
3142956BIRDNECK
Solar/Wind Helper
0.223
316458AB2-190 GEN2
Solar/Wind Helper
1.896
316017AA1-139 ULT1
Solar/Wind Helper
1.432
3142946ENON
Solar/Wind Helper
0.104
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.582
316075AC2-137 C
Solar/Wind Helper
0.459
316305AF2-043 C
Solar/Wind Helper
0.402
316246AF1-032 C
Solar/Wind Helper
0.342
316077AC2-138 C
Solar/Wind Helper
0.276
316320Y1-086
Solar/Wind Helper
0.127
316473AC1-191 GEN
Solar/Wind Helper
1.701
316223AC1-118
Solar/Wind Helper
0.424
3141906WESTMOR
Solar/Wind Helper
0.111
316321Z2-027
Solar/Wind Helper
0.414
3146516WINFALL
Solar/Wind Helper
0.25
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.235
315244AE2-183_ST
50/50
18.991
963041AG1-153 GEN
50/50
16.818
3151541CLOVER2
50/50
9.18
3151601KERR 3
50/50
0.526
3151611KERR 4
50/50
0.526
3151621KERR 5
50/50
0.526
3151631KERR 6
50/50
0.526
971967AH1-528 GEN
Solar/Wind Harmer
122.813
970085AG2-068 GEN
Solar/Wind Harmer
40.657
970581AG2-369 GEN
Solar/Wind Harmer
34.965
316486AD2-202 GEN
Solar/Wind Harmer
1.224
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316435W1029_GEN3
Solar/Wind Helper
1.035
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146626S HERTFORD
Solar/Wind Helper
0.235
3146626S HERTFORD
Solar/Wind Helper
0.235
315243AE2-183_GT3
50/50
10.936
3151051BRUNSWICKS1
50/50
17.246
3151021BRUNSWICKG1
50/50
8.307
971451AH1-221 GEN
50/50
25.226
3151531CLOVER1
50/50
9.25
3151591KERR 2
50/50
0.526
3151641KERR 7
50/50
0.526
3144293JTRSVLE
50/50
0.593
3144293JTRSVLE
50/50
0.468
971629AH1-314 GEN
50/50
17.75
3151561HALLBR1
50/50
0.359
970919AG2-571 GEN
Solar/Wind Harmer
21.055
970087AG2-069 GEN
Solar/Wind Harmer
60.986
957481AF2-042 GEN
Solar/Wind Harmer
164.583
315693AD1-088 GEN
Solar/Wind Harmer
24.018
970401AG2-262 GEN
Solar/Wind Harmer
2.072
316131AB2-060 GEN
Solar/Wind Harmer
3.026
315785AD2-033 C
Solar/Wind Harmer
6.188
316034AC1-036 C
Solar/Wind Harmer
0.502
970685AG2-442 GEN
Solar/Wind Harmer
23.201
971563AH1-280 GEN
Solar/Wind Harmer
3.286
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.105
316129AC1-054 GEN
Solar/Wind Harmer
1.824
970223AG2-152 GEN
Solar/Wind Harmer
17.044
270016AE1-250 BESS
Solar/Wind Harmer
2.814
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.362
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.486
270030AE2-140 GEN
Solar/Wind Harmer
19.599
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.807
3142053HEARTS
Solar/Wind Harmer
0.158
315773AC2-141 GEN
Solar/Wind Helper
8.532
315671AE2-027_GEN
Solar/Wind Helper
2.884
316381AD1-082 GEN
Solar/Wind Helper
1.75
316375AC2-012 GEN
Solar/Wind Helper
0.883
316036AC1-147 C
Solar/Wind Helper
0.512
3145336SMITFLD
Solar/Wind Helper
1.329
316132AB2-190 GEN1
Solar/Wind Helper
1.896
316369SG1_INVT
Solar/Wind Helper
1.594
3142433PROV 92
Solar/Wind Helper
1.252
3142543TWELFTH
Solar/Wind Helper
0.03
315662AE1-191 GEN
Solar/Wind Helper
1.677
316280AD1-041 GEN
Solar/Wind Helper
1.048
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.351
319010AE1-072 C
Solar/Wind Helper
3.502
315975AC1-164 GENB
Solar/Wind Helper
0.116
316404AE1-155 C
Solar/Wind Helper
2.553
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.177
3143526WINTERP
Solar/Wind Helper
1.516
3142416OLDCHRC
Solar/Wind Helper
0.75
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.287
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.811
3146516WINFALL
Solar/Wind Helper
0.25
316238AB2-078_GEN
Solar/Wind Harmer
0.854
316239AB2-077_GEN
Solar/Wind Harmer
0.854
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
18.866
970681AG2-440 GEN
Solar/Wind Harmer
12.522
946301AF1-294 GEN
Solar/Wind Harmer
6.735
961791AG1-021 GEN
Solar/Wind Harmer
3.286
270455AD2-022 GEN
Solar/Wind Harmer
4.668
270457AD2-023 GEN
Solar/Wind Harmer
2.367
970831AG2-522 GEN
Solar/Wind Harmer
9.555
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
971845AH1-439 GEN
Solar/Wind Harmer
8.41
316322AB2-045
Solar/Wind Harmer
0.505
270069AE2-166 C O1
Solar/Wind Harmer
7.921
3143316POE
Solar/Wind Helper
1.568
315839AE2-212 C
Solar/Wind Helper
0.498
316236AE1-162_GEN
Solar/Wind Helper
0.448
316316AC1-027 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
3.782
316382AG1-145 C
Solar/Wind Helper
0.442
316159AE1-175 C
Solar/Wind Helper
0.498
957831AF2-077 GEN
Solar/Wind Helper
0.436
316018AA1-139 ULT2
Solar/Wind Helper
1.348
957601AF2-054 GEN
Solar/Wind Helper
0.417
3141873WAN 176
Solar/Wind Helper
0.062
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.313
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.092
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.445
313526AB2-022
Solar/Wind Helper
0.431
3146486SUNBURY
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.273
3145176PASQUOTANK
Solar/Wind Helper
0.168
316468AD1-105 GEN
Solar/Wind Helper
1.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.924
MECLTFEXP_MEC->PJM
CLTF
7.297
SIGELTFEXP_SIGE->PJM
CLTF
0.219
CPLELTFEXP_CPLE->PJM
CLTF
19.597
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.518
LAGNLTFEXP_LAGN->PJM
CLTF
14.534
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.89
TVALTFEXP_TVA->PJM
CLTF
7.248
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.65
WECLTFEXP_WEC->PJM
CLTF
1.386
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.15 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:898.18
MW Contribution:
2.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.109
3144293JTRSVLE
50/50
0.463
970535AG2-341 GEN
50/50
1.296
3151581KERR 1
50/50
0.042
316336AC2-165 C
Solar/Wind Harmer
38.103
3146776BUCKING
Solar/Wind Harmer
1.512
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
8.437
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.195
970323AG2-213 GEN
Solar/Wind Harmer
5.966
962561AG1-105 GEN
Solar/Wind Harmer
3.404
964791AG1-342 GEN
Solar/Wind Harmer
1.295
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
3151921BEARGRDN G2
50/50
4.561
3144293JTRSVLE
50/50
0.463
972003AH1-546 GEN
Solar/Wind Harmer
16.576
970221AG2-151 GEN
Solar/Wind Harmer
23.304
3146776BUCKING
Solar/Wind Harmer
0.136
270494AE1-108_GEN
Solar/Wind Harmer
4.12
315821AE2-092 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.62
959311AF2-222 GEN
Solar/Wind Harmer
12.996
958131AF2-107 GEN
Solar/Wind Harmer
4.142
970257AG2-171 GEN
Solar/Wind Harmer
4.475
971775AH1-396 GEN
Solar/Wind Harmer
0.224
964241AG1-285 GEN
Solar/Wind Harmer
7.182
972205AH1-687 GEN
50/50
22.285
3151601KERR 3
50/50
0.118
3151611KERR 4
50/50
0.118
3151621KERR 5
50/50
0.118
3151631KERR 6
50/50
0.118
971845AH1-439 GEN
Solar/Wind Harmer
16.79
946301AF1-294 GEN
Solar/Wind Harmer
3.609
961791AG1-021 GEN
Solar/Wind Harmer
1.756
970683AG2-441 GEN
Solar/Wind Harmer
9.764
970681AG2-440 GEN
Solar/Wind Harmer
6.481
3144303KENBRDG
Solar/Wind Harmer
0.112
3151931BEARGRDN S1
50/50
5.893
3151911BEARGRDN G1
50/50
4.561
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.366
3151591KERR 2
50/50
0.118
3151641KERR 7
50/50
0.118
970937AG2-583 GEN
Solar/Wind Harmer
37.476
971377AH1-170 GEN
Solar/Wind Harmer
4.661
3147623JAMES R
Solar/Wind Harmer
1.013
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
971563AH1-280 GEN
Solar/Wind Harmer
1.951
970685AG2-442 GEN
Solar/Wind Harmer
12.815
316034AC1-036 C
Solar/Wind Harmer
0.009
315785AD2-033 C
Solar/Wind Harmer
1.06
316131AB2-060 GEN
Solar/Wind Harmer
0.291
315693AD1-088 GEN
Solar/Wind Harmer
3.817
970401AG2-262 GEN
Solar/Wind Harmer
0.396
962751AG1-124 GEN
Solar/Wind Harmer
2.979
316258AE1-075 C
Solar/Wind Helper
0.865
316405AF2-144 C
Solar/Wind Helper
0.721
316233AE1-074 FULL
Solar/Wind Helper
0.266
316118AC1-105 GEN
Solar/Wind Harmer
0.151
316313AB2-026
Solar/Wind Helper
0.961
3143526WINTERP
Solar/Wind Helper
0.905
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.905
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.753
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.453
MECLTFEXP_MEC->PJM
CLTF
0.803
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.769
LAGNLTFEXP_LAGN->PJM
CLTF
1.351
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.16
TVALTFEXP_TVA->PJM
CLTF
0.693
NYPJM->LTFIMP_NY
CLTF
0.408
LGEELTFEXP_LGEE->PJM
CLTF
0.324
WECLTFEXP_WEC->PJM
CLTF
0.162

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.87 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:895.98
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
316336AC2-165 C
Solar/Wind Harmer
32.605
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
970937AG2-583 GEN
Solar/Wind Harmer
28.694
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2054_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.54 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1014.73
MW Contribution:
2.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.563
3144293JTRSVLE
50/50
0.463
972003AH1-546 GEN
Solar/Wind Harmer
21.837
970221AG2-151 GEN
Solar/Wind Harmer
30.726
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
10.091
315821AE2-092 GEN
Solar/Wind Harmer
6.911
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.035
3147133PAMPLIN
Solar/Wind Harmer
-0.069
959311AF2-222 GEN
Solar/Wind Harmer
17.147
958131AF2-107 GEN
Solar/Wind Harmer
5.549
970257AG2-171 GEN
Solar/Wind Harmer
5.892
971775AH1-396 GEN
Solar/Wind Harmer
1.109
964241AG1-285 GEN
Solar/Wind Harmer
9.456
972205AH1-687 GEN
50/50
22.298
316322AB2-045
Solar/Wind Harmer
1.427
971845AH1-439 GEN
Solar/Wind Harmer
22.116
946301AF1-294 GEN
Solar/Wind Harmer
5.267
961791AG1-021 GEN
Solar/Wind Harmer
2.569
970683AG2-441 GEN
Solar/Wind Harmer
12.858
970681AG2-440 GEN
Solar/Wind Harmer
8.534
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.295
316239AB2-077_GEN
Solar/Wind Harmer
0.295
316258AE1-075 C
Solar/Wind Helper
0.866
316405AF2-144 C
Solar/Wind Helper
0.721
316233AE1-074 FULL
Solar/Wind Helper
0.267
970909AG2-566 GEN
50/50
2.109
3144293JTRSVLE
50/50
0.463
316336AC2-165 C
Solar/Wind Harmer
52.75
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.109
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.212
970323AG2-213 GEN
Solar/Wind Harmer
7.856
313527AB2-043 GEN
Solar/Wind Harmer
1.643
316237AB2-079_GEN
Solar/Wind Harmer
0.295
962561AG1-105 GEN
Solar/Wind Harmer
4.484
964791AG1-342 GEN
Solar/Wind Harmer
1.62
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.456
316313AB2-026
Solar/Wind Helper
0.962
3143526WINTERP
Solar/Wind Helper
0.91
3151931BEARGRDN S1
50/50
5.896
3151911BEARGRDN G1
50/50
4.563
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.366
970937AG2-583 GEN
Solar/Wind Harmer
49.352
971377AH1-170 GEN
Solar/Wind Harmer
6.145
3147623JAMES R
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.569
970685AG2-442 GEN
Solar/Wind Harmer
16.876
316034AC1-036 C
Solar/Wind Harmer
0.291
315785AD2-033 C
Solar/Wind Harmer
3.332
316131AB2-060 GEN
Solar/Wind Harmer
1.131
315693AD1-088 GEN
Solar/Wind Harmer
4.459
970401AG2-262 GEN
Solar/Wind Harmer
0.495
962751AG1-124 GEN
Solar/Wind Harmer
4.417
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.91
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.581
MECLTFEXP_MEC->PJM
CLTF
0.856
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
1.3
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.206
LAGNLTFEXP_LAGN->PJM
CLTF
1.417
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.233
TVALTFEXP_TVA->PJM
CLTF
0.727
NYPJM->LTFIMP_NY
CLTF
0.425
LGEELTFEXP_LGEE->PJM
CLTF
0.347
WECLTFEXP_WEC->PJM
CLTF
0.174

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.07 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1000.24
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.958
3144293JTRSVLE
50/50
0.378
972003AH1-546 GEN
Solar/Wind Harmer
14.248
970221AG2-151 GEN
Solar/Wind Harmer
19.91
3146776BUCKING
Solar/Wind Harmer
-0.01
270494AE1-108_GEN
Solar/Wind Harmer
6.621
3146926FARMVIL
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
4.824
942461AE2-259 GEN
Solar/Wind Harmer
3.135
3147133PAMPLIN
Solar/Wind Harmer
-0.056
959311AF2-222 GEN
Solar/Wind Harmer
14.664
970257AG2-171 GEN
Solar/Wind Harmer
5.093
971775AH1-396 GEN
Solar/Wind Harmer
0.958
958131AF2-107 GEN
Solar/Wind Harmer
3.937
316478AD1-087 GEN
Solar/Wind Harmer
0.995
964241AG1-285 GEN
Solar/Wind Harmer
8.768
3148013FISHERV
Solar/Wind Harmer
-0.008
316003AC1-222 GEN
Solar/Wind Harmer
0.73
971683AH1-343 GEN
Solar/Wind Harmer
3.086
316123AC1-075 GEN
Solar/Wind Harmer
0.691
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.719
316075AC2-137 C
Solar/Wind Helper
0.175
316458AB2-190 GEN2
Solar/Wind Helper
0.652
970909AG2-566 GEN
50/50
1.872
3144293JTRSVLE
50/50
0.378
316336AC2-165 C
Solar/Wind Harmer
45.111
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
9.858
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.617
970323AG2-213 GEN
Solar/Wind Harmer
6.791
3151931BEARGRDN S1
50/50
3.822
3151911BEARGRDN G1
50/50
2.958
3144293JTRSVLE
50/50
0.378
3144293JTRSVLE
50/50
0.298
970937AG2-583 GEN
Solar/Wind Harmer
37.754
971377AH1-170 GEN
Solar/Wind Harmer
3.982
3147623JAMES R
Solar/Wind Harmer
0.493
3146776BUCKING
Solar/Wind Harmer
-0.012
3146926FARMVIL
Solar/Wind Harmer
-0.014
971563AH1-280 GEN
Solar/Wind Harmer
2.093
970685AG2-442 GEN
Solar/Wind Harmer
13.928
316034AC1-036 C
Solar/Wind Harmer
0.252
315693AD1-088 GEN
Solar/Wind Harmer
6.787
315785AD2-033 C
Solar/Wind Harmer
2.927
957481AF2-042 GEN
Solar/Wind Harmer
38.582
316131AB2-060 GEN
Solar/Wind Harmer
1.096
970401AG2-262 GEN
Solar/Wind Harmer
0.567
3143226MDLTHAN
Solar/Wind Helper
0.302
3143526WINTERP
Solar/Wind Helper
1.302
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.964
3142416OLDCHRC
Solar/Wind Helper
0.3
3142416OLDCHRC
Solar/Wind Helper
0.115
316132AB2-190 GEN1
Solar/Wind Helper
0.652
3142433PROV 92
Solar/Wind Helper
0.451
972205AH1-687 GEN
50/50
14.455
316322AB2-045
Solar/Wind Harmer
0.989
971845AH1-439 GEN
Solar/Wind Harmer
15.423
946301AF1-294 GEN
Solar/Wind Harmer
4.291
961791AG1-021 GEN
Solar/Wind Harmer
2.093
970683AG2-441 GEN
Solar/Wind Harmer
10.743
970681AG2-440 GEN
Solar/Wind Harmer
7.13
3144303KENBRDG
Solar/Wind Harmer
-0.011
971967AH1-528 GEN
Solar/Wind Harmer
23.665
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316486AD2-202 GEN
Solar/Wind Harmer
0.291
316238AB2-078_GEN
Solar/Wind Harmer
0.293
316239AB2-077_GEN
Solar/Wind Harmer
0.293
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.004
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316258AE1-075 C
Solar/Wind Helper
1.125
316405AF2-144 C
Solar/Wind Helper
0.938
316233AE1-074 FULL
Solar/Wind Helper
0.383
315839AE2-212 C
Solar/Wind Helper
0.158
970933AG2-581 GEN
Solar/Wind Harmer
11.802
970099AG2-077 GEN
Solar/Wind Harmer
15.433
313527AB2-043 GEN
Solar/Wind Harmer
1.612
315687AD1-152 GEN
Solar/Wind Harmer
1.172
316237AB2-079_GEN
Solar/Wind Harmer
0.293
962561AG1-105 GEN
Solar/Wind Harmer
4.994
964791AG1-342 GEN
Solar/Wind Harmer
1.856
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
316118AC1-105 GEN
Solar/Wind Harmer
0.565
316248AF1-058 C
Solar/Wind Harmer
0.234
316313AB2-026
Solar/Wind Helper
1.25
3143526WINTERP
Solar/Wind Helper
1.302
316240AF1-291 C
Solar/Wind Helper
0.165
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.159
316312AB1-027
Solar/Wind Helper
0.221
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.768
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.821
MECLTFEXP_MEC->PJM
CLTF
1.1
SIGELTFEXP_SIGE->PJM
CLTF
0.036
CPLELTFEXP_CPLE->PJM
CLTF
0.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.41
LAGNLTFEXP_LAGN->PJM
CLTF
1.476
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.272
TVALTFEXP_TVA->PJM
CLTF
0.766
NYPJM->LTFIMP_NY
CLTF
0.347
LGEELTFEXP_LGEE->PJM
CLTF
0.469
WECLTFEXP_WEC->PJM
CLTF
0.24

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.06 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1000.22
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.958
3144293JTRSVLE
50/50
0.378
972003AH1-546 GEN
Solar/Wind Harmer
14.248
970221AG2-151 GEN
Solar/Wind Harmer
19.91
3146776BUCKING
Solar/Wind Harmer
-0.01
3151931BEARGRDN S1
50/50
3.822
3151911BEARGRDN G1
50/50
2.958
3144293JTRSVLE
50/50
0.378
3144293JTRSVLE
50/50
0.298
970937AG2-583 GEN
Solar/Wind Harmer
37.754
971377AH1-170 GEN
Solar/Wind Harmer
3.982
3147623JAMES R
Solar/Wind Harmer
0.493
3146776BUCKING
Solar/Wind Harmer
-0.012
3146926FARMVIL
Solar/Wind Harmer
-0.014
971563AH1-280 GEN
Solar/Wind Harmer
2.093
970685AG2-442 GEN
Solar/Wind Harmer
13.928
316034AC1-036 C
Solar/Wind Harmer
0.252
315693AD1-088 GEN
Solar/Wind Harmer
6.787
315785AD2-033 C
Solar/Wind Harmer
2.927
957481AF2-042 GEN
Solar/Wind Harmer
38.582
316131AB2-060 GEN
Solar/Wind Harmer
1.096
970401AG2-262 GEN
Solar/Wind Harmer
0.567
3143226MDLTHAN
Solar/Wind Helper
0.302
3143526WINTERP
Solar/Wind Helper
1.302
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.964
972205AH1-687 GEN
50/50
14.455
316322AB2-045
Solar/Wind Harmer
0.989
971845AH1-439 GEN
Solar/Wind Harmer
15.423
946301AF1-294 GEN
Solar/Wind Harmer
4.291
961791AG1-021 GEN
Solar/Wind Harmer
2.093
970683AG2-441 GEN
Solar/Wind Harmer
10.743
970681AG2-440 GEN
Solar/Wind Harmer
7.13
3144303KENBRDG
Solar/Wind Harmer
-0.011
971967AH1-528 GEN
Solar/Wind Harmer
23.665
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316486AD2-202 GEN
Solar/Wind Harmer
0.291
316238AB2-078_GEN
Solar/Wind Harmer
0.293
316239AB2-077_GEN
Solar/Wind Harmer
0.293
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.004
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316258AE1-075 C
Solar/Wind Helper
1.125
316405AF2-144 C
Solar/Wind Helper
0.938
316233AE1-074 FULL
Solar/Wind Helper
0.383
315839AE2-212 C
Solar/Wind Helper
0.158
970909AG2-566 GEN
50/50
1.872
3144293JTRSVLE
50/50
0.378
316336AC2-165 C
Solar/Wind Harmer
45.111
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
9.858
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.617
970323AG2-213 GEN
Solar/Wind Harmer
6.791
970933AG2-581 GEN
Solar/Wind Harmer
11.802
970099AG2-077 GEN
Solar/Wind Harmer
15.433
313527AB2-043 GEN
Solar/Wind Harmer
1.612
315687AD1-152 GEN
Solar/Wind Harmer
1.172
316237AB2-079_GEN
Solar/Wind Harmer
0.293
962561AG1-105 GEN
Solar/Wind Harmer
4.994
964791AG1-342 GEN
Solar/Wind Harmer
1.856
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
316118AC1-105 GEN
Solar/Wind Harmer
0.565
316248AF1-058 C
Solar/Wind Harmer
0.234
316313AB2-026
Solar/Wind Helper
1.25
3143526WINTERP
Solar/Wind Helper
1.302
316240AF1-291 C
Solar/Wind Helper
0.165
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.159
270494AE1-108_GEN
Solar/Wind Harmer
6.621
3146926FARMVIL
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
4.824
942461AE2-259 GEN
Solar/Wind Harmer
3.135
3147133PAMPLIN
Solar/Wind Harmer
-0.056
959311AF2-222 GEN
Solar/Wind Harmer
14.664
970257AG2-171 GEN
Solar/Wind Harmer
5.093
971775AH1-396 GEN
Solar/Wind Harmer
0.958
958131AF2-107 GEN
Solar/Wind Harmer
3.937
316478AD1-087 GEN
Solar/Wind Harmer
0.995
964241AG1-285 GEN
Solar/Wind Harmer
8.768
3148013FISHERV
Solar/Wind Harmer
-0.008
316003AC1-222 GEN
Solar/Wind Harmer
0.73
971683AH1-343 GEN
Solar/Wind Harmer
3.086
316123AC1-075 GEN
Solar/Wind Harmer
0.691
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.719
3142416OLDCHRC
Solar/Wind Helper
0.3
3142416OLDCHRC
Solar/Wind Helper
0.115
316132AB2-190 GEN1
Solar/Wind Helper
0.652
3142433PROV 92
Solar/Wind Helper
0.451
316075AC2-137 C
Solar/Wind Helper
0.175
316458AB2-190 GEN2
Solar/Wind Helper
0.652
316312AB1-027
Solar/Wind Helper
0.221
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.768
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.821
MECLTFEXP_MEC->PJM
CLTF
1.1
SIGELTFEXP_SIGE->PJM
CLTF
0.036
CPLELTFEXP_CPLE->PJM
CLTF
0.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.41
LAGNLTFEXP_LAGN->PJM
CLTF
1.476
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.272
TVALTFEXP_TVA->PJM
CLTF
0.766
NYPJM->LTFIMP_NY
CLTF
0.347
LGEELTFEXP_LGEE->PJM
CLTF
0.469
WECLTFEXP_WEC->PJM
CLTF
0.24

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 233T2028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.82 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:997.84
MW Contribution:
2.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.109
3144293JTRSVLE
50/50
0.463
316336AC2-165 C
Solar/Wind Harmer
52.756
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.109
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.211
970323AG2-213 GEN
Solar/Wind Harmer
7.856
313527AB2-043 GEN
Solar/Wind Harmer
1.644
316237AB2-079_GEN
Solar/Wind Harmer
0.295
962561AG1-105 GEN
Solar/Wind Harmer
4.482
964791AG1-342 GEN
Solar/Wind Harmer
1.619
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.456
316313AB2-026
Solar/Wind Helper
0.961
3143526WINTERP
Solar/Wind Helper
0.905
972205AH1-687 GEN
50/50
22.287
316322AB2-045
Solar/Wind Harmer
1.426
971845AH1-439 GEN
Solar/Wind Harmer
22.108
946301AF1-294 GEN
Solar/Wind Harmer
5.266
961791AG1-021 GEN
Solar/Wind Harmer
2.569
970683AG2-441 GEN
Solar/Wind Harmer
12.856
970681AG2-440 GEN
Solar/Wind Harmer
8.533
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.295
316239AB2-077_GEN
Solar/Wind Harmer
0.295
316258AE1-075 C
Solar/Wind Helper
0.865
316405AF2-144 C
Solar/Wind Helper
0.721
316233AE1-074 FULL
Solar/Wind Helper
0.266
3151921BEARGRDN G2
50/50
4.561
3144293JTRSVLE
50/50
0.463
972003AH1-546 GEN
Solar/Wind Harmer
21.826
970221AG2-151 GEN
Solar/Wind Harmer
30.689
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
10.073
315821AE2-092 GEN
Solar/Wind Harmer
6.871
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.034
3147133PAMPLIN
Solar/Wind Harmer
-0.069
959311AF2-222 GEN
Solar/Wind Harmer
17.146
958131AF2-107 GEN
Solar/Wind Harmer
5.519
970257AG2-171 GEN
Solar/Wind Harmer
5.892
971775AH1-396 GEN
Solar/Wind Harmer
1.109
964241AG1-285 GEN
Solar/Wind Harmer
9.457
3151931BEARGRDN S1
50/50
5.893
3151911BEARGRDN G1
50/50
4.561
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.366
970937AG2-583 GEN
Solar/Wind Harmer
49.344
971377AH1-170 GEN
Solar/Wind Harmer
6.138
3147623JAMES R
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.569
970685AG2-442 GEN
Solar/Wind Harmer
16.873
316034AC1-036 C
Solar/Wind Harmer
0.291
315785AD2-033 C
Solar/Wind Harmer
3.332
316131AB2-060 GEN
Solar/Wind Harmer
1.131
315693AD1-088 GEN
Solar/Wind Harmer
4.466
970401AG2-262 GEN
Solar/Wind Harmer
0.495
962751AG1-124 GEN
Solar/Wind Harmer
4.358
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.905
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.469
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
1.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.825
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.17
TVALTFEXP_TVA->PJM
CLTF
0.697
NYPJM->LTFIMP_NY
CLTF
0.41
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.164

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.77 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:997.37
MW Contribution:
2.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.14
3144293JTRSVLE
50/50
0.47
316336AC2-165 C
Solar/Wind Harmer
53.022
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.269
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.257
970323AG2-213 GEN
Solar/Wind Harmer
7.973
313527AB2-043 GEN
Solar/Wind Harmer
1.671
316237AB2-079_GEN
Solar/Wind Harmer
0.3
962561AG1-105 GEN
Solar/Wind Harmer
4.556
964791AG1-342 GEN
Solar/Wind Harmer
1.645
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.463
316313AB2-026
Solar/Wind Helper
0.951
3143526WINTERP
Solar/Wind Helper
0.893
972205AH1-687 GEN
50/50
22.565
316322AB2-045
Solar/Wind Harmer
1.445
971845AH1-439 GEN
Solar/Wind Harmer
22.392
3151921BEARGRDN G2
50/50
4.618
3144293JTRSVLE
50/50
0.47
972003AH1-546 GEN
Solar/Wind Harmer
22.099
970221AG2-151 GEN
Solar/Wind Harmer
29.417
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.657
3146926FARMVIL
Solar/Wind Harmer
-0.019
315821AE2-092 GEN
Solar/Wind Harmer
6.506
942461AE2-259 GEN
Solar/Wind Harmer
4.09
3147133PAMPLIN
Solar/Wind Harmer
-0.07
959311AF2-222 GEN
Solar/Wind Harmer
17.401
970257AG2-171 GEN
Solar/Wind Harmer
5.98
971775AH1-396 GEN
Solar/Wind Harmer
1.125
958131AF2-107 GEN
Solar/Wind Harmer
5.296
964241AG1-285 GEN
Solar/Wind Harmer
9.607
3151931BEARGRDN S1
50/50
5.966
3151911BEARGRDN G1
50/50
4.618
3144293JTRSVLE
50/50
0.47
3144293JTRSVLE
50/50
0.371
970937AG2-583 GEN
Solar/Wind Harmer
49.752
971377AH1-170 GEN
Solar/Wind Harmer
5.883
3147623JAMES R
Solar/Wind Harmer
0.728
946301AF1-294 GEN
Solar/Wind Harmer
5.341
961791AG1-021 GEN
Solar/Wind Harmer
2.605
970683AG2-441 GEN
Solar/Wind Harmer
13.043
970681AG2-440 GEN
Solar/Wind Harmer
8.657
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.3
316239AB2-077_GEN
Solar/Wind Harmer
0.3
316258AE1-075 C
Solar/Wind Helper
0.856
316405AF2-144 C
Solar/Wind Helper
0.714
316233AE1-074 FULL
Solar/Wind Helper
0.262
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.605
970685AG2-442 GEN
Solar/Wind Harmer
17.117
316034AC1-036 C
Solar/Wind Harmer
0.296
315785AD2-033 C
Solar/Wind Harmer
3.382
316131AB2-060 GEN
Solar/Wind Harmer
1.15
315693AD1-088 GEN
Solar/Wind Harmer
4.553
970401AG2-262 GEN
Solar/Wind Harmer
0.503
962751AG1-124 GEN
Solar/Wind Harmer
4.191
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.893
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.609
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.431
MECLTFEXP_MEC->PJM
CLTF
0.788
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.316
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.679
LAGNLTFEXP_LAGN->PJM
CLTF
1.342
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.206
TVALTFEXP_TVA->PJM
CLTF
0.688
NYPJM->LTFIMP_NY
CLTF
0.407
LGEELTFEXP_LGEE->PJM
CLTF
0.317
WECLTFEXP_WEC->PJM
CLTF
0.159

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.1 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5173.4
MW Contribution:
3.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
44.999
970099AG2-077 GEN
Solar/Wind Harmer
50.746
970301AG2-198 GEN
Solar/Wind Harmer
13.237
316118AC1-105 GEN
Solar/Wind Harmer
0.762
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.492
962561AG1-105 GEN
Solar/Wind Harmer
13.495
970323AG2-213 GEN
Solar/Wind Harmer
10.454
958211AF2-115 GEN
Solar/Wind Harmer
2.847
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.188
942751AE2-291 GEN
Solar/Wind Harmer
11.487
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
942671AE2-283 GEN
Solar/Wind Harmer
3.281
316049AB1-081 GEN
Solar/Wind Harmer
0.667
316263AC1-034 GEN
Solar/Wind Harmer
4.456
961601AG1-000A GEN
Solar/Wind Harmer
2.039
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
941031AE2-094 GEN
Solar/Wind Harmer
138.312
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
47.021
957481AF2-042 GEN
Solar/Wind Harmer
126.864
315693AD1-088 GEN
Solar/Wind Harmer
20.828
970401AG2-262 GEN
Solar/Wind Harmer
1.678
316131AB2-060 GEN
Solar/Wind Harmer
0.788
315785AD2-033 C
Solar/Wind Harmer
1.994
316034AC1-036 C
Solar/Wind Harmer
0.016
970685AG2-442 GEN
Solar/Wind Harmer
17.866
971563AH1-280 GEN
Solar/Wind Harmer
2.531
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.454
316129AC1-054 GEN
Solar/Wind Harmer
0.693
970223AG2-152 GEN
Solar/Wind Harmer
12.084
3147123OTTER R
Solar/Wind Harmer
0.088
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.219
270030AE2-140 GEN
Solar/Wind Harmer
13.827
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.417
3142053HEARTS
Solar/Wind Harmer
0.206
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
970533AG2-339 GEN
Solar/Wind Harmer
56.74
970673AG2-436 GEN
Solar/Wind Harmer
89.687
971967AH1-528 GEN
Solar/Wind Harmer
94.459
970085AG2-068 GEN
Solar/Wind Harmer
31.347
970581AG2-369 GEN
Solar/Wind Harmer
26.958
316486AD2-202 GEN
Solar/Wind Harmer
0.444
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
14.525
970681AG2-440 GEN
Solar/Wind Harmer
9.64
946301AF1-294 GEN
Solar/Wind Harmer
4.682
961791AG1-021 GEN
Solar/Wind Harmer
2.278
970831AG2-522 GEN
Solar/Wind Harmer
7.24
971845AH1-439 GEN
Solar/Wind Harmer
6.517
270197AD1-017 GEN1
Solar/Wind Harmer
0.942
270069AE2-166 C O1
Solar/Wind Harmer
5.589
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
944011AF1-069 GEN
Solar/Wind Harmer
45.192
970917AG2-570 GEN
Solar/Wind Harmer
53.44
316478AD1-087 GEN
Solar/Wind Harmer
1.514
316222AC1-221 GEN
Solar/Wind Harmer
1.167
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.037
964241AG1-285 GEN
Solar/Wind Harmer
16.717
970257AG2-171 GEN
Solar/Wind Harmer
7.84
971775AH1-396 GEN
Solar/Wind Harmer
0.392
959311AF2-222 GEN
Solar/Wind Harmer
21.675
3147133PAMPLIN
Solar/Wind Harmer
0.736
316123AC1-075 GEN
Solar/Wind Harmer
0.308
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.131
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.118
971623AH1-311 GEN
Solar/Wind Harmer
0.235
961601AG1-000A GEN
Solar/Wind Harmer
8.154
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.85 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5687.87
MW Contribution:
3.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
944011AF1-069 GEN
Solar/Wind Harmer
49.571
970917AG2-570 GEN
Solar/Wind Harmer
168.871
316478AD1-087 GEN
Solar/Wind Harmer
4.24
316003AC1-222 GEN
Solar/Wind Harmer
3.197
316222AC1-221 GEN
Solar/Wind Harmer
3.212
316283AC2-100 C
Solar/Wind Harmer
2.976
971683AH1-343 GEN
Solar/Wind Harmer
13.215
964241AG1-285 GEN
Solar/Wind Harmer
22.01
970257AG2-171 GEN
Solar/Wind Harmer
10.323
971775AH1-396 GEN
Solar/Wind Harmer
1.942
959311AF2-222 GEN
Solar/Wind Harmer
28.596
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.792
942461AE2-259 GEN
Solar/Wind Harmer
3.838
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.599
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.851
316217AC1-145 GEN
Solar/Wind Harmer
2.402
316197AC1-042 GEN
Solar/Wind Harmer
1.821
3147312GRETNA
Solar/Wind Harmer
-0.003
270336AE1-100 GEN
Solar/Wind Harmer
1.568
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.128
3144873MCLAUGH
Solar/Wind Helper
0.01
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
970533AG2-339 GEN
Solar/Wind Harmer
56.74
970673AG2-436 GEN
Solar/Wind Harmer
177.133
971967AH1-528 GEN
Solar/Wind Harmer
124.702
970085AG2-068 GEN
Solar/Wind Harmer
41.274
970581AG2-369 GEN
Solar/Wind Harmer
35.495
316486AD2-202 GEN
Solar/Wind Harmer
1.242
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.022
316238AB2-078_GEN
Solar/Wind Harmer
0.865
316239AB2-077_GEN
Solar/Wind Harmer
0.865
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.124
970681AG2-440 GEN
Solar/Wind Harmer
12.693
946301AF1-294 GEN
Solar/Wind Harmer
6.831
961791AG1-021 GEN
Solar/Wind Harmer
3.332
270455AD2-022 GEN
Solar/Wind Harmer
4.718
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
59.249
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
270457AD2-023 GEN
Solar/Wind Harmer
2.392
970831AG2-522 GEN
Solar/Wind Harmer
9.533
971845AH1-439 GEN
Solar/Wind Harmer
8.58
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
316322AB2-045
Solar/Wind Harmer
0.516
270069AE2-166 C O1
Solar/Wind Harmer
8.011
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
970099AG2-077 GEN
Solar/Wind Harmer
66.815
315687AD1-152 GEN
Solar/Wind Harmer
5.329
970301AG2-198 GEN
Solar/Wind Harmer
17.428
316248AF1-058 C
Solar/Wind Harmer
1.044
316118AC1-105 GEN
Solar/Wind Harmer
2.295
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.865
962561AG1-105 GEN
Solar/Wind Harmer
17.768
316237AB2-079_GEN
Solar/Wind Harmer
0.865
313527AB2-043 GEN
Solar/Wind Harmer
4.632
970323AG2-213 GEN
Solar/Wind Harmer
13.764
958211AF2-115 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.125
270013AE1-250 PV
Solar/Wind Harmer
2.845
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.906
316049AB1-081 GEN
Solar/Wind Harmer
1.418
316263AC1-034 GEN
Solar/Wind Harmer
6.176
961601AG1-000A GEN
Solar/Wind Harmer
5.064
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
941031AE2-094 GEN
Solar/Wind Harmer
158.204
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
61.91
957481AF2-042 GEN
Solar/Wind Harmer
167.038
315693AD1-088 GEN
Solar/Wind Harmer
24.377
970401AG2-262 GEN
Solar/Wind Harmer
2.098
316131AB2-060 GEN
Solar/Wind Harmer
3.062
315785AD2-033 C
Solar/Wind Harmer
6.268
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.524
971563AH1-280 GEN
Solar/Wind Harmer
3.332
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.131
316129AC1-054 GEN
Solar/Wind Harmer
1.825
970223AG2-152 GEN
Solar/Wind Harmer
17.233
270016AE1-250 BESS
Solar/Wind Harmer
2.845
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.377
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.554
270030AE2-140 GEN
Solar/Wind Harmer
19.819
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.772
3142053HEARTS
Solar/Wind Harmer
0.155
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.35 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5662.94
MW Contribution:
3.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.03
315241AE2-183_GT1
50/50
11.001
972185AH1-677 GEN
50/50
39.871
3151041BRUNSWICKG3
50/50
8.378
972187AH1-678 GEN
50/50
19.224
970909AG2-566 GEN
50/50
3.293
3152661PLYWOOD A
50/50
0.662
3151581KERR 1
50/50
0.19
970535AG2-341 GEN
50/50
4.581
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
58.871
970099AG2-077 GEN
Solar/Wind Harmer
66.433
315687AD1-152 GEN
Solar/Wind Harmer
5.303
970301AG2-198 GEN
Solar/Wind Harmer
17.344
316248AF1-058 C
Solar/Wind Harmer
1.041
316118AC1-105 GEN
Solar/Wind Harmer
2.29
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.859
962561AG1-105 GEN
Solar/Wind Harmer
17.76
3151031BRUNSWICKG2
50/50
8.378
970413AG2-270 GEN
50/50
40.656
3144293JTRSVLE
50/50
0.601
944011AF1-069 GEN
Solar/Wind Harmer
49.211
970917AG2-570 GEN
Solar/Wind Harmer
167.755
316478AD1-087 GEN
Solar/Wind Harmer
4.218
316003AC1-222 GEN
Solar/Wind Harmer
3.188
316222AC1-221 GEN
Solar/Wind Harmer
3.202
316283AC2-100 C
Solar/Wind Harmer
2.967
971683AH1-343 GEN
Solar/Wind Harmer
13.175
964241AG1-285 GEN
Solar/Wind Harmer
22.056
970257AG2-171 GEN
Solar/Wind Harmer
10.334
971775AH1-396 GEN
Solar/Wind Harmer
1.944
959311AF2-222 GEN
Solar/Wind Harmer
28.621
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.783
942461AE2-259 GEN
Solar/Wind Harmer
3.829
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.584
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.841
316217AC1-145 GEN
Solar/Wind Harmer
2.396
316197AC1-042 GEN
Solar/Wind Harmer
1.816
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.26
3144873MCLAUGH
Solar/Wind Helper
0.01
3142956BIRDNECK
Solar/Wind Helper
0.258
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.667
3146456SLIGO L269
Solar/Wind Helper
0.359
316305AF2-043 C
Solar/Wind Helper
0.474
316246AF1-032 C
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
1.935
316320Y1-086
Solar/Wind Helper
0.149
316321Z2-027
Solar/Wind Helper
0.487
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.606
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.287
316237AB2-079_GEN
Solar/Wind Harmer
0.867
313527AB2-043 GEN
Solar/Wind Harmer
4.644
970323AG2-213 GEN
Solar/Wind Harmer
13.779
958211AF2-115 GEN
Solar/Wind Harmer
4.164
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.08
270013AE1-250 PV
Solar/Wind Harmer
2.837
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.893
316049AB1-081 GEN
Solar/Wind Harmer
1.452
316263AC1-034 GEN
Solar/Wind Harmer
6.326
961601AG1-000A GEN
Solar/Wind Harmer
5.194
316294AC1-161 GEN
Solar/Wind Helper
7.794
316185AD1-033 GEN
Solar/Wind Helper
1.802
3145506HICKORY
Solar/Wind Helper
1.505
3145506HICKORY
Solar/Wind Helper
0.903
3145506HICKORY
Solar/Wind Helper
0.226
316339AD2-160 GEN
Solar/Wind Helper
1.399
316388AE2-253 GEN
Solar/Wind Helper
1.399
3137176SLIGO L2192
Solar/Wind Helper
1.43
3130086AYDLETT
Solar/Wind Helper
1.419
316033AB2-134 GEN
Solar/Wind Helper
1.198
316349AD2-085 GEN
Solar/Wind Helper
1.524
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.493
315666AE1-190 GEN
Solar/Wind Helper
0.437
3142946ENON
Solar/Wind Helper
0.031
316487AF1-042 GEN
Solar/Wind Helper
0.317
315976AC1-164 GENA
Solar/Wind Helper
4.039
316169AC1-164_GENC
Solar/Wind Helper
3.489
315243AE2-183_GT3
50/50
11.03
3151051BRUNSWICKS1
50/50
17.394
3151021BRUNSWICKG1
50/50
8.378
971451AH1-221 GEN
50/50
25.443
3151531CLOVER1
50/50
9.336
3151591KERR 2
50/50
0.532
3151641KERR 7
50/50
0.532
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.474
971629AH1-314 GEN
50/50
17.894
3151561HALLBR1
50/50
0.362
941031AE2-094 GEN
Solar/Wind Harmer
157.057
970919AG2-571 GEN
Solar/Wind Harmer
21.235
970087AG2-069 GEN
Solar/Wind Harmer
61.506
957481AF2-042 GEN
Solar/Wind Harmer
166.083
315693AD1-088 GEN
Solar/Wind Harmer
24.245
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316131AB2-060 GEN
Solar/Wind Harmer
3.07
315785AD2-033 C
Solar/Wind Harmer
6.277
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.525
971563AH1-280 GEN
Solar/Wind Harmer
3.331
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.235
316129AC1-054 GEN
Solar/Wind Harmer
1.845
970223AG2-152 GEN
Solar/Wind Harmer
17.186
270016AE1-250 BESS
Solar/Wind Harmer
2.837
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.373
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.539
270030AE2-140 GEN
Solar/Wind Harmer
19.766
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.815
3142053HEARTS
Solar/Wind Harmer
0.159
315773AC2-141 GEN
Solar/Wind Helper
9.171
316375AC2-012 GEN
Solar/Wind Helper
1.018
316036AC1-147 C
Solar/Wind Helper
0.591
3145336SMITFLD
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.359
319010AE1-072 C
Solar/Wind Helper
4.082
316072AD1-144
Solar/Wind Helper
0.405
316369SG1_INVT
Solar/Wind Helper
1.668
316381AD1-082 GEN
Solar/Wind Helper
1.76
316132AB2-190 GEN1
Solar/Wind Helper
1.935
315671AE2-027_GEN
Solar/Wind Helper
2.696
315662AE1-191 GEN
Solar/Wind Helper
1.75
316280AD1-041 GEN
Solar/Wind Helper
1.093
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.273
315975AC1-164 GENB
Solar/Wind Helper
0.119
316404AE1-155 C
Solar/Wind Helper
2.656
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.411
3141726DUNNSVL
Solar/Wind Helper
1.22
3146516WINFALL
Solar/Wind Helper
0.296
316223AC1-118
Solar/Wind Helper
0.438
3141906WESTMOR
Solar/Wind Helper
0.115
316431W1029_GEN1
Solar/Wind Helper
1.223
316433W1029_GEN2
Solar/Wind Helper
1.223
316435W1029_GEN3
Solar/Wind Helper
1.223
315244AE2-183_ST
50/50
19.154
963041AG1-153 GEN
50/50
16.962
3151541CLOVER2
50/50
9.264
3151601KERR 3
50/50
0.532
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
970533AG2-339 GEN
Solar/Wind Harmer
56.328
970673AG2-436 GEN
Solar/Wind Harmer
175.868
971967AH1-528 GEN
Solar/Wind Harmer
123.886
970085AG2-068 GEN
Solar/Wind Harmer
41.004
970581AG2-369 GEN
Solar/Wind Harmer
35.263
316486AD2-202 GEN
Solar/Wind Harmer
1.235
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.867
316239AB2-077_GEN
Solar/Wind Harmer
0.867
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.131
970681AG2-440 GEN
Solar/Wind Harmer
12.698
946301AF1-294 GEN
Solar/Wind Harmer
6.829
961791AG1-021 GEN
Solar/Wind Harmer
3.331
270455AD2-022 GEN
Solar/Wind Harmer
4.705
270457AD2-023 GEN
Solar/Wind Harmer
2.386
970831AG2-522 GEN
Solar/Wind Harmer
9.671
971845AH1-439 GEN
Solar/Wind Harmer
8.548
270197AD1-017 GEN1
Solar/Wind Harmer
1.675
316322AB2-045
Solar/Wind Harmer
0.514
270069AE2-166 C O1
Solar/Wind Harmer
7.989
316316AC1-027 C
Solar/Wind Helper
0.607
316236AE1-162_GEN
Solar/Wind Helper
0.499
316018AA1-139 ULT2
Solar/Wind Helper
1.569
3143316POE
Solar/Wind Helper
1.405
316382AG1-145 C
Solar/Wind Helper
0.47
316159AE1-175 C
Solar/Wind Helper
0.53
315697AD1-025 GEN
Solar/Wind Helper
3.957
957831AF2-077 GEN
Solar/Wind Helper
0.465
315839AE2-212 C
Solar/Wind Helper
0.458
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.437
3141873WAN 176
Solar/Wind Helper
0.065
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
3145176PASQUOTANK
Solar/Wind Helper
0.197
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
316312AB1-027
Solar/Wind Helper
0.557
3143526WINTERP
Solar/Wind Helper
1.497
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.491
316315AB2-025 C
Solar/Wind Helper
0.418
3141813NORNECK
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.44
316468AD1-105 GEN
Solar/Wind Helper
1.26
315800Z1-036_GEN1
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3146626S HERTFORD
Solar/Wind Helper
0.279
316473AC1-191 GEN
Solar/Wind Helper
1.693
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146376EDENTON
Solar/Wind Helper
0.226
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
316337AD2-073 GEN
Solar/Wind Helper
0.449
3142416OLDCHRC
Solar/Wind Helper
0.758
3142416OLDCHRC
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.497
3143226MDLTHAN
Solar/Wind Helper
0.284
315611Z1-036_GEN2
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.147
MECLTFEXP_MEC->PJM
CLTF
7.373
SIGELTFEXP_SIGE->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
19.725
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.242
LAGNLTFEXP_LAGN->PJM
CLTF
14.661
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.209
TVALTFEXP_TVA->PJM
CLTF
7.311
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.679
WECLTFEXP_WEC->PJM
CLTF
1.402
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.73 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5581.87
MW Contribution:
3.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.307
970413AG2-270 GEN
50/50
40.285
3144293JTRSVLE
50/50
0.593
944011AF1-069 GEN
Solar/Wind Harmer
48.793
970917AG2-570 GEN
Solar/Wind Harmer
166.334
316478AD1-087 GEN
Solar/Wind Harmer
4.179
316003AC1-222 GEN
Solar/Wind Harmer
3.156
316222AC1-221 GEN
Solar/Wind Harmer
3.175
316283AC2-100 C
Solar/Wind Harmer
2.943
315242AE2-183_GT2
50/50
10.936
315241AE2-183_GT1
50/50
10.907
972185AH1-677 GEN
50/50
39.531
3151041BRUNSWICKG3
50/50
8.307
972187AH1-678 GEN
50/50
19.06
970909AG2-566 GEN
50/50
3.258
3152661PLYWOOD A
50/50
0.655
3151581KERR 1
50/50
0.188
970535AG2-341 GEN
50/50
4.523
3144293JTRSVLE
50/50
0.593
970933AG2-581 GEN
Solar/Wind Harmer
58.356
970099AG2-077 GEN
Solar/Wind Harmer
65.833
315687AD1-152 GEN
Solar/Wind Harmer
5.255
970301AG2-198 GEN
Solar/Wind Harmer
17.157
316248AF1-058 C
Solar/Wind Harmer
1.031
316118AC1-105 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.78
962561AG1-105 GEN
Solar/Wind Harmer
17.549
316237AB2-079_GEN
Solar/Wind Harmer
0.854
313527AB2-043 GEN
Solar/Wind Harmer
4.577
970323AG2-213 GEN
Solar/Wind Harmer
13.586
958211AF2-115 GEN
Solar/Wind Harmer
4.107
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.933
270013AE1-250 PV
Solar/Wind Harmer
2.814
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.846
316049AB1-081 GEN
Solar/Wind Harmer
1.446
316263AC1-034 GEN
Solar/Wind Harmer
6.299
961601AG1-000A GEN
Solar/Wind Harmer
5.168
316294AC1-161 GEN
Solar/Wind Helper
7.251
316240AF1-291 C
Solar/Wind Helper
0.472
316033AB2-134 GEN
Solar/Wind Helper
1.145
316185AD1-033 GEN
Solar/Wind Helper
1.553
3145506HICKORY
Solar/Wind Helper
1.296
3145506HICKORY
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.194
3144356SAPONY
Solar/Wind Helper
0.58
316315AB2-025 C
Solar/Wind Helper
0.494
316339AD2-160 GEN
Solar/Wind Helper
1.203
316388AE2-253 GEN
Solar/Wind Helper
1.203
316156AD2-030 GEN
Solar/Wind Helper
0.471
3142946ENON
Solar/Wind Helper
0.031
315666AE1-190 GEN
Solar/Wind Helper
0.419
3137176SLIGO L2192
Solar/Wind Helper
1.227
316349AD2-085 GEN
Solar/Wind Helper
1.397
315976AC1-164 GENA
Solar/Wind Helper
3.933
316169AC1-164_GENC
Solar/Wind Helper
3.397
3130086AYDLETT
Solar/Wind Helper
1.217
316487AF1-042 GEN
Solar/Wind Helper
0.305
971683AH1-343 GEN
Solar/Wind Harmer
13.046
964241AG1-285 GEN
Solar/Wind Harmer
21.742
970257AG2-171 GEN
Solar/Wind Harmer
10.19
971775AH1-396 GEN
Solar/Wind Harmer
1.917
959311AF2-222 GEN
Solar/Wind Harmer
28.221
3147133PAMPLIN
Solar/Wind Harmer
-0.081
316123AC1-075 GEN
Solar/Wind Harmer
2.756
942461AE2-259 GEN
Solar/Wind Harmer
3.778
3146926FARMVIL
Solar/Wind Harmer
-0.014
270574AD1-017 GEN2
Solar/Wind Harmer
5.536
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.808
316217AC1-145 GEN
Solar/Wind Harmer
2.372
316197AC1-042 GEN
Solar/Wind Harmer
1.798
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.55
961601AG1-000A GEN
Solar/Wind Harmer
5.233
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
3142956BIRDNECK
Solar/Wind Helper
0.223
316458AB2-190 GEN2
Solar/Wind Helper
1.896
316017AA1-139 ULT1
Solar/Wind Helper
1.432
3142946ENON
Solar/Wind Helper
0.104
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.582
315243AE2-183_GT3
50/50
10.936
3151051BRUNSWICKS1
50/50
17.246
3151021BRUNSWICKG1
50/50
8.307
971451AH1-221 GEN
50/50
25.226
3151531CLOVER1
50/50
9.25
3151591KERR 2
50/50
0.526
3151641KERR 7
50/50
0.526
3144293JTRSVLE
50/50
0.593
3144293JTRSVLE
50/50
0.468
971629AH1-314 GEN
50/50
17.75
3151561HALLBR1
50/50
0.359
941031AE2-094 GEN
Solar/Wind Harmer
155.721
970919AG2-571 GEN
Solar/Wind Harmer
21.055
970087AG2-069 GEN
Solar/Wind Harmer
60.986
957481AF2-042 GEN
Solar/Wind Harmer
164.583
315693AD1-088 GEN
Solar/Wind Harmer
24.018
970401AG2-262 GEN
Solar/Wind Harmer
2.072
316131AB2-060 GEN
Solar/Wind Harmer
3.026
315785AD2-033 C
Solar/Wind Harmer
6.188
316034AC1-036 C
Solar/Wind Harmer
0.502
970685AG2-442 GEN
Solar/Wind Harmer
23.201
971563AH1-280 GEN
Solar/Wind Harmer
3.286
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.105
316129AC1-054 GEN
Solar/Wind Harmer
1.824
970223AG2-152 GEN
Solar/Wind Harmer
17.044
270016AE1-250 BESS
Solar/Wind Harmer
2.814
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.362
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.486
270030AE2-140 GEN
Solar/Wind Harmer
19.599
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.807
3142053HEARTS
Solar/Wind Harmer
0.158
315773AC2-141 GEN
Solar/Wind Helper
8.532
315671AE2-027_GEN
Solar/Wind Helper
2.884
316381AD1-082 GEN
Solar/Wind Helper
1.75
316375AC2-012 GEN
Solar/Wind Helper
0.883
316036AC1-147 C
Solar/Wind Helper
0.512
3145336SMITFLD
Solar/Wind Helper
1.329
316132AB2-190 GEN1
Solar/Wind Helper
1.896
316369SG1_INVT
Solar/Wind Helper
1.594
3142433PROV 92
Solar/Wind Helper
1.252
3142543TWELFTH
Solar/Wind Helper
0.03
315662AE1-191 GEN
Solar/Wind Helper
1.677
316280AD1-041 GEN
Solar/Wind Helper
1.048
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.351
319010AE1-072 C
Solar/Wind Helper
3.502
315975AC1-164 GENB
Solar/Wind Helper
0.116
315244AE2-183_ST
50/50
18.991
963041AG1-153 GEN
50/50
16.818
3151541CLOVER2
50/50
9.18
3151601KERR 3
50/50
0.526
3151611KERR 4
50/50
0.526
3151621KERR 5
50/50
0.526
3151631KERR 6
50/50
0.526
970533AG2-339 GEN
Solar/Wind Harmer
55.849
970673AG2-436 GEN
Solar/Wind Harmer
174.37
971967AH1-528 GEN
Solar/Wind Harmer
122.813
970085AG2-068 GEN
Solar/Wind Harmer
40.657
970581AG2-369 GEN
Solar/Wind Harmer
34.965
316486AD2-202 GEN
Solar/Wind Harmer
1.224
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.854
316239AB2-077_GEN
Solar/Wind Harmer
0.854
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
18.866
970681AG2-440 GEN
Solar/Wind Harmer
12.522
946301AF1-294 GEN
Solar/Wind Harmer
6.735
961791AG1-021 GEN
Solar/Wind Harmer
3.286
270455AD2-022 GEN
Solar/Wind Harmer
4.668
270457AD2-023 GEN
Solar/Wind Harmer
2.367
970831AG2-522 GEN
Solar/Wind Harmer
9.555
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
971845AH1-439 GEN
Solar/Wind Harmer
8.41
316322AB2-045
Solar/Wind Harmer
0.505
270069AE2-166 C O1
Solar/Wind Harmer
7.921
3143316POE
Solar/Wind Helper
1.568
315839AE2-212 C
Solar/Wind Helper
0.498
316236AE1-162_GEN
Solar/Wind Helper
0.448
316316AC1-027 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
3.782
316382AG1-145 C
Solar/Wind Helper
0.442
316159AE1-175 C
Solar/Wind Helper
0.498
957831AF2-077 GEN
Solar/Wind Helper
0.436
316018AA1-139 ULT2
Solar/Wind Helper
1.348
957601AF2-054 GEN
Solar/Wind Helper
0.417
3141873WAN 176
Solar/Wind Helper
0.062
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.313
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.092
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.122
316075AC2-137 C
Solar/Wind Helper
0.459
316305AF2-043 C
Solar/Wind Helper
0.402
316246AF1-032 C
Solar/Wind Helper
0.342
316077AC2-138 C
Solar/Wind Helper
0.276
316320Y1-086
Solar/Wind Helper
0.127
316473AC1-191 GEN
Solar/Wind Helper
1.701
316223AC1-118
Solar/Wind Helper
0.424
3141906WESTMOR
Solar/Wind Helper
0.111
316321Z2-027
Solar/Wind Helper
0.414
3146516WINFALL
Solar/Wind Helper
0.25
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.235
3143526WINTERP
Solar/Wind Helper
1.516
316312AB1-027
Solar/Wind Helper
0.551
3146386ELIZ CT
Solar/Wind Helper
0.282
966871AG1-558 GEN
Solar/Wind Helper
0.375
316431W1029_GEN1
Solar/Wind Helper
1.035
316433W1029_GEN2
Solar/Wind Helper
1.035
316435W1029_GEN3
Solar/Wind Helper
1.035
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146626S HERTFORD
Solar/Wind Helper
0.235
3146626S HERTFORD
Solar/Wind Helper
0.235
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.445
313526AB2-022
Solar/Wind Helper
0.431
3146486SUNBURY
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.273
3145176PASQUOTANK
Solar/Wind Helper
0.168
316468AD1-105 GEN
Solar/Wind Helper
1.263
316404AE1-155 C
Solar/Wind Helper
2.553
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.177
3143526WINTERP
Solar/Wind Helper
1.516
3142416OLDCHRC
Solar/Wind Helper
0.75
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.287
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.811
3146516WINFALL
Solar/Wind Helper
0.25
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.924
MECLTFEXP_MEC->PJM
CLTF
7.297
SIGELTFEXP_SIGE->PJM
CLTF
0.219
CPLELTFEXP_CPLE->PJM
CLTF
19.597
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.518
LAGNLTFEXP_LAGN->PJM
CLTF
14.534
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.89
TVALTFEXP_TVA->PJM
CLTF
7.248
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.65
WECLTFEXP_WEC->PJM
CLTF
1.386
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.16 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:663.9
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.357
316478AD1-087 GEN
Solar/Wind Harmer
1.086
971683AH1-343 GEN
Solar/Wind Harmer
5.14
316123AC1-075 GEN
Solar/Wind Harmer
0.149
316222AC1-221 GEN
Solar/Wind Harmer
0.443
316283AC2-100 C
Solar/Wind Harmer
0.206
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.543
3147133PAMPLIN
Solar/Wind Helper
1.064
315821AE2-092 GEN
Solar/Wind Helper
1.922
270494AE1-108_GEN
Solar/Wind Helper
2.774
3151541CLOVER2
50/50
6.689
3151601KERR 3
50/50
0.297
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
3151631KERR 6
50/50
0.297
971967AH1-528 GEN
Solar/Wind Harmer
55.714
316486AD2-202 GEN
Solar/Wind Harmer
0.319
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
970831AG2-522 GEN
Solar/Wind Harmer
4.544
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.182
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970909AG2-566 GEN
50/50
6.347
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
970933AG2-581 GEN
Solar/Wind Harmer
27.858
970099AG2-077 GEN
Solar/Wind Harmer
36.297
316118AC1-105 GEN
Solar/Wind Harmer
0.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.688
942751AE2-291 GEN
Solar/Wind Harmer
5.335
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.242
3151531CLOVER1
50/50
6.741
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
971629AH1-314 GEN
50/50
5.005
315693AD1-088 GEN
Solar/Wind Harmer
18.249
957481AF2-042 GEN
Solar/Wind Harmer
90.743
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.07
316129AC1-054 GEN
Solar/Wind Harmer
0.424
316131AB2-060 GEN
Solar/Wind Harmer
0.206
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.59 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:649.19
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.689
3151601KERR 3
50/50
0.297
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
3151631KERR 6
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.319
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
970831AG2-522 GEN
Solar/Wind Harmer
4.544
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.182
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.357
316478AD1-087 GEN
Solar/Wind Harmer
1.086
971683AH1-343 GEN
Solar/Wind Harmer
5.14
316123AC1-075 GEN
Solar/Wind Harmer
0.149
316222AC1-221 GEN
Solar/Wind Harmer
0.443
316283AC2-100 C
Solar/Wind Harmer
0.206
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.543
3147133PAMPLIN
Solar/Wind Helper
1.064
315821AE2-092 GEN
Solar/Wind Helper
1.922
270494AE1-108_GEN
Solar/Wind Helper
2.774
970909AG2-566 GEN
50/50
6.347
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
970099AG2-077 GEN
Solar/Wind Harmer
36.297
316118AC1-105 GEN
Solar/Wind Harmer
0.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.688
942751AE2-291 GEN
Solar/Wind Harmer
5.335
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.242
3151531CLOVER1
50/50
6.741
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
971629AH1-314 GEN
50/50
5.005
315693AD1-088 GEN
Solar/Wind Harmer
18.249
957481AF2-042 GEN
Solar/Wind Harmer
90.743
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.07
316129AC1-054 GEN
Solar/Wind Harmer
0.424
316131AB2-060 GEN
Solar/Wind Harmer
0.206
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.99 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:782.79
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
6.35
3152661PLYWOOD A
50/50
0.343
3151581KERR 1
50/50
0.106
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.444
970933AG2-581 GEN
Solar/Wind Harmer
36.737
970099AG2-077 GEN
Solar/Wind Harmer
47.87
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316248AF1-058 C
Solar/Wind Harmer
0.557
316118AC1-105 GEN
Solar/Wind Harmer
1.127
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.524
942751AE2-291 GEN
Solar/Wind Harmer
7.062
316237AB2-079_GEN
Solar/Wind Harmer
0.274
313527AB2-043 GEN
Solar/Wind Harmer
1.359
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.244
970413AG2-270 GEN
50/50
29.412
316478AD1-087 GEN
Solar/Wind Harmer
3.047
316003AC1-222 GEN
Solar/Wind Harmer
1.679
971683AH1-343 GEN
Solar/Wind Harmer
6.798
316123AC1-075 GEN
Solar/Wind Harmer
1.354
316222AC1-221 GEN
Solar/Wind Harmer
1.232
316283AC2-100 C
Solar/Wind Harmer
1.123
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.54
3147133PAMPLIN
Solar/Wind Helper
1.062
315821AE2-092 GEN
Solar/Wind Helper
1.926
270494AE1-108_GEN
Solar/Wind Helper
2.776
3151541CLOVER2
50/50
6.702
3151601KERR 3
50/50
0.298
3151611KERR 4
50/50
0.298
3151621KERR 5
50/50
0.298
3151631KERR 6
50/50
0.298
971967AH1-528 GEN
Solar/Wind Harmer
73.669
316486AD2-202 GEN
Solar/Wind Harmer
0.892
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
6.001
316238AB2-078_GEN
Solar/Wind Harmer
0.274
316239AB2-077_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.183
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.754
3151591KERR 2
50/50
0.298
3151641KERR 7
50/50
0.298
315693AD1-088 GEN
Solar/Wind Harmer
21.387
957481AF2-042 GEN
Solar/Wind Harmer
119.676
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316131AB2-060 GEN
Solar/Wind Harmer
0.805
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.597
MECLTFEXP_MEC->PJM
CLTF
1.296
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.231
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.155
LAGNLTFEXP_LAGN->PJM
CLTF
2.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.917
TVALTFEXP_TVA->PJM
CLTF
1.346
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.46
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.95 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:782.5
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
6.35
3152661PLYWOOD A
50/50
0.343
3151581KERR 1
50/50
0.106
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.444
970933AG2-581 GEN
Solar/Wind Harmer
36.737
970099AG2-077 GEN
Solar/Wind Harmer
47.87
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316248AF1-058 C
Solar/Wind Harmer
0.557
316118AC1-105 GEN
Solar/Wind Harmer
1.127
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.524
942751AE2-291 GEN
Solar/Wind Harmer
7.062
316237AB2-079_GEN
Solar/Wind Harmer
0.274
313527AB2-043 GEN
Solar/Wind Harmer
1.359
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.244
970413AG2-270 GEN
50/50
29.412
316478AD1-087 GEN
Solar/Wind Harmer
3.047
316003AC1-222 GEN
Solar/Wind Harmer
1.679
971683AH1-343 GEN
Solar/Wind Harmer
6.798
316123AC1-075 GEN
Solar/Wind Harmer
1.354
316222AC1-221 GEN
Solar/Wind Harmer
1.232
316283AC2-100 C
Solar/Wind Harmer
1.123
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.54
3147133PAMPLIN
Solar/Wind Helper
1.062
315821AE2-092 GEN
Solar/Wind Helper
1.926
270494AE1-108_GEN
Solar/Wind Helper
2.776
3151541CLOVER2
50/50
6.702
3151601KERR 3
50/50
0.298
3151611KERR 4
50/50
0.298
3151621KERR 5
50/50
0.298
3151631KERR 6
50/50
0.298
971967AH1-528 GEN
Solar/Wind Harmer
73.669
316486AD2-202 GEN
Solar/Wind Harmer
0.892
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
6.001
316238AB2-078_GEN
Solar/Wind Harmer
0.274
316239AB2-077_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.183
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.754
3151591KERR 2
50/50
0.298
3151641KERR 7
50/50
0.298
315693AD1-088 GEN
Solar/Wind Harmer
21.387
957481AF2-042 GEN
Solar/Wind Harmer
119.676
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316131AB2-060 GEN
Solar/Wind Harmer
0.805
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.597
MECLTFEXP_MEC->PJM
CLTF
1.296
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.231
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.155
LAGNLTFEXP_LAGN->PJM
CLTF
2.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.917
TVALTFEXP_TVA->PJM
CLTF
1.346
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.46
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.79 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:760.44
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.741
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
315693AD1-088 GEN
Solar/Wind Harmer
21.358
957481AF2-042 GEN
Solar/Wind Harmer
119.479
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.676
316129AC1-054 GEN
Solar/Wind Harmer
1.114
316131AB2-060 GEN
Solar/Wind Harmer
0.8
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.217
970909AG2-566 GEN
50/50
6.347
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970301AG2-198 GEN
Solar/Wind Harmer
33.427
970933AG2-581 GEN
Solar/Wind Harmer
36.679
970099AG2-077 GEN
Solar/Wind Harmer
47.791
315687AD1-152 GEN
Solar/Wind Harmer
3.506
316248AF1-058 C
Solar/Wind Harmer
0.555
316118AC1-105 GEN
Solar/Wind Harmer
1.123
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.489
942751AE2-291 GEN
Solar/Wind Harmer
7.024
316237AB2-079_GEN
Solar/Wind Harmer
0.272
313527AB2-043 GEN
Solar/Wind Harmer
1.352
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.242
3151541CLOVER2
50/50
6.689
3151601KERR 3
50/50
0.297
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
3151631KERR 6
50/50
0.297
971967AH1-528 GEN
Solar/Wind Harmer
73.553
316486AD2-202 GEN
Solar/Wind Harmer
0.891
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
5.983
316238AB2-078_GEN
Solar/Wind Harmer
0.272
316239AB2-077_GEN
Solar/Wind Harmer
0.272
270455AD2-022 GEN
Solar/Wind Harmer
1.349
270457AD2-023 GEN
Solar/Wind Harmer
0.684
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.182
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.357
316478AD1-087 GEN
Solar/Wind Harmer
3.041
316003AC1-222 GEN
Solar/Wind Harmer
1.672
971683AH1-343 GEN
Solar/Wind Harmer
6.767
316123AC1-075 GEN
Solar/Wind Harmer
1.347
316222AC1-221 GEN
Solar/Wind Harmer
1.22
316283AC2-100 C
Solar/Wind Harmer
1.112
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.543
3147133PAMPLIN
Solar/Wind Helper
1.064
315821AE2-092 GEN
Solar/Wind Helper
1.922
270494AE1-108_GEN
Solar/Wind Helper
2.774
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.86 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:719.0
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.357
316478AD1-087 GEN
Solar/Wind Harmer
3.041
316003AC1-222 GEN
Solar/Wind Harmer
1.672
971683AH1-343 GEN
Solar/Wind Harmer
6.767
316123AC1-075 GEN
Solar/Wind Harmer
1.347
316222AC1-221 GEN
Solar/Wind Harmer
1.22
316283AC2-100 C
Solar/Wind Harmer
1.112
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.543
3147133PAMPLIN
Solar/Wind Helper
1.064
315821AE2-092 GEN
Solar/Wind Helper
1.922
270494AE1-108_GEN
Solar/Wind Helper
2.774
970909AG2-566 GEN
50/50
6.347
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970301AG2-198 GEN
Solar/Wind Harmer
33.427
970099AG2-077 GEN
Solar/Wind Harmer
47.791
315687AD1-152 GEN
Solar/Wind Harmer
3.506
316248AF1-058 C
Solar/Wind Harmer
0.555
316118AC1-105 GEN
Solar/Wind Harmer
1.123
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.489
942751AE2-291 GEN
Solar/Wind Harmer
7.024
316237AB2-079_GEN
Solar/Wind Harmer
0.272
313527AB2-043 GEN
Solar/Wind Harmer
1.352
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.242
3151531CLOVER1
50/50
6.741
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
315693AD1-088 GEN
Solar/Wind Harmer
21.358
957481AF2-042 GEN
Solar/Wind Harmer
119.479
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.676
316129AC1-054 GEN
Solar/Wind Harmer
1.114
316131AB2-060 GEN
Solar/Wind Harmer
0.8
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.217
3151541CLOVER2
50/50
6.689
3151601KERR 3
50/50
0.297
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
3151631KERR 6
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.891
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
5.983
316238AB2-078_GEN
Solar/Wind Harmer
0.272
316239AB2-077_GEN
Solar/Wind Harmer
0.272
270455AD2-022 GEN
Solar/Wind Harmer
1.349
270457AD2-023 GEN
Solar/Wind Harmer
0.684
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.182
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.86 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:719.0
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.357
316478AD1-087 GEN
Solar/Wind Harmer
3.041
316003AC1-222 GEN
Solar/Wind Harmer
1.672
971683AH1-343 GEN
Solar/Wind Harmer
6.767
316123AC1-075 GEN
Solar/Wind Harmer
1.347
316222AC1-221 GEN
Solar/Wind Harmer
1.22
316283AC2-100 C
Solar/Wind Harmer
1.112
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.543
3147133PAMPLIN
Solar/Wind Helper
1.064
315821AE2-092 GEN
Solar/Wind Helper
1.922
270494AE1-108_GEN
Solar/Wind Helper
2.774
970909AG2-566 GEN
50/50
6.347
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970301AG2-198 GEN
Solar/Wind Harmer
33.427
970099AG2-077 GEN
Solar/Wind Harmer
47.791
315687AD1-152 GEN
Solar/Wind Harmer
3.506
316248AF1-058 C
Solar/Wind Harmer
0.555
316118AC1-105 GEN
Solar/Wind Harmer
1.123
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.489
942751AE2-291 GEN
Solar/Wind Harmer
7.024
316237AB2-079_GEN
Solar/Wind Harmer
0.272
313527AB2-043 GEN
Solar/Wind Harmer
1.352
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
316313AB2-026
Solar/Wind Helper
0.242
3151531CLOVER1
50/50
6.741
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
315693AD1-088 GEN
Solar/Wind Harmer
21.358
957481AF2-042 GEN
Solar/Wind Harmer
119.479
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.676
316129AC1-054 GEN
Solar/Wind Harmer
1.114
316131AB2-060 GEN
Solar/Wind Harmer
0.8
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.217
3151541CLOVER2
50/50
6.689
3151601KERR 3
50/50
0.297
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
3151631KERR 6
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.891
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
5.983
316238AB2-078_GEN
Solar/Wind Harmer
0.272
316239AB2-077_GEN
Solar/Wind Harmer
0.272
270455AD2-022 GEN
Solar/Wind Harmer
1.349
270457AD2-023 GEN
Solar/Wind Harmer
0.684
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.182
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.2 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4933.15
MW Contribution:
3.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
970673AG2-436 GEN
Solar/Wind Harmer
89.687
971967AH1-528 GEN
Solar/Wind Harmer
94.459
970085AG2-068 GEN
Solar/Wind Harmer
31.347
970581AG2-369 GEN
Solar/Wind Harmer
26.958
316486AD2-202 GEN
Solar/Wind Harmer
0.444
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
14.525
970681AG2-440 GEN
Solar/Wind Harmer
9.64
946301AF1-294 GEN
Solar/Wind Harmer
4.682
961791AG1-021 GEN
Solar/Wind Harmer
2.278
970831AG2-522 GEN
Solar/Wind Harmer
7.24
971845AH1-439 GEN
Solar/Wind Harmer
6.517
270197AD1-017 GEN1
Solar/Wind Harmer
0.942
270069AE2-166 C O1
Solar/Wind Harmer
5.589
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
53.44
316478AD1-087 GEN
Solar/Wind Harmer
1.514
316222AC1-221 GEN
Solar/Wind Harmer
1.167
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.037
964241AG1-285 GEN
Solar/Wind Harmer
16.717
970257AG2-171 GEN
Solar/Wind Harmer
7.84
971775AH1-396 GEN
Solar/Wind Harmer
0.392
959311AF2-222 GEN
Solar/Wind Harmer
21.675
3147133PAMPLIN
Solar/Wind Harmer
0.736
316123AC1-075 GEN
Solar/Wind Harmer
0.308
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.131
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.118
971623AH1-311 GEN
Solar/Wind Harmer
0.235
961601AG1-000A GEN
Solar/Wind Harmer
8.154
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
44.999
970099AG2-077 GEN
Solar/Wind Harmer
50.746
970301AG2-198 GEN
Solar/Wind Harmer
13.237
316118AC1-105 GEN
Solar/Wind Harmer
0.762
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.492
962561AG1-105 GEN
Solar/Wind Harmer
13.495
970323AG2-213 GEN
Solar/Wind Harmer
10.454
958211AF2-115 GEN
Solar/Wind Harmer
2.847
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.188
942751AE2-291 GEN
Solar/Wind Harmer
11.487
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
942671AE2-283 GEN
Solar/Wind Harmer
3.281
316049AB1-081 GEN
Solar/Wind Harmer
0.667
316263AC1-034 GEN
Solar/Wind Harmer
4.456
961601AG1-000A GEN
Solar/Wind Harmer
2.039
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
47.021
957481AF2-042 GEN
Solar/Wind Harmer
126.864
315693AD1-088 GEN
Solar/Wind Harmer
20.828
970401AG2-262 GEN
Solar/Wind Harmer
1.678
316131AB2-060 GEN
Solar/Wind Harmer
0.788
315785AD2-033 C
Solar/Wind Harmer
1.994
316034AC1-036 C
Solar/Wind Harmer
0.016
970685AG2-442 GEN
Solar/Wind Harmer
17.866
971563AH1-280 GEN
Solar/Wind Harmer
2.531
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.454
316129AC1-054 GEN
Solar/Wind Harmer
0.693
970223AG2-152 GEN
Solar/Wind Harmer
12.084
3147123OTTER R
Solar/Wind Harmer
0.088
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.219
270030AE2-140 GEN
Solar/Wind Harmer
13.827
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.417
3142053HEARTS
Solar/Wind Harmer
0.206
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.55 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5423.36
MW Contribution:
3.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
59.249
970099AG2-077 GEN
Solar/Wind Harmer
66.815
315687AD1-152 GEN
Solar/Wind Harmer
5.329
970301AG2-198 GEN
Solar/Wind Harmer
17.428
316248AF1-058 C
Solar/Wind Harmer
1.044
316118AC1-105 GEN
Solar/Wind Harmer
2.295
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.865
962561AG1-105 GEN
Solar/Wind Harmer
17.768
316237AB2-079_GEN
Solar/Wind Harmer
0.865
313527AB2-043 GEN
Solar/Wind Harmer
4.632
970323AG2-213 GEN
Solar/Wind Harmer
13.764
958211AF2-115 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.125
270013AE1-250 PV
Solar/Wind Harmer
2.845
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.906
316049AB1-081 GEN
Solar/Wind Harmer
1.418
316263AC1-034 GEN
Solar/Wind Harmer
6.176
961601AG1-000A GEN
Solar/Wind Harmer
5.064
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
168.871
316478AD1-087 GEN
Solar/Wind Harmer
4.24
316003AC1-222 GEN
Solar/Wind Harmer
3.197
316222AC1-221 GEN
Solar/Wind Harmer
3.212
316283AC2-100 C
Solar/Wind Harmer
2.976
971683AH1-343 GEN
Solar/Wind Harmer
13.215
964241AG1-285 GEN
Solar/Wind Harmer
22.01
970257AG2-171 GEN
Solar/Wind Harmer
10.323
971775AH1-396 GEN
Solar/Wind Harmer
1.942
959311AF2-222 GEN
Solar/Wind Harmer
28.596
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.792
942461AE2-259 GEN
Solar/Wind Harmer
3.838
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.599
3146776BUCKING
Solar/Wind Harmer
-0.005
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
970673AG2-436 GEN
Solar/Wind Harmer
177.133
971967AH1-528 GEN
Solar/Wind Harmer
124.702
970085AG2-068 GEN
Solar/Wind Harmer
41.274
970581AG2-369 GEN
Solar/Wind Harmer
35.495
316486AD2-202 GEN
Solar/Wind Harmer
1.242
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.022
316238AB2-078_GEN
Solar/Wind Harmer
0.865
316239AB2-077_GEN
Solar/Wind Harmer
0.865
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.124
970681AG2-440 GEN
Solar/Wind Harmer
12.693
946301AF1-294 GEN
Solar/Wind Harmer
6.831
961791AG1-021 GEN
Solar/Wind Harmer
3.332
270455AD2-022 GEN
Solar/Wind Harmer
4.718
270457AD2-023 GEN
Solar/Wind Harmer
2.392
970831AG2-522 GEN
Solar/Wind Harmer
9.533
971845AH1-439 GEN
Solar/Wind Harmer
8.58
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
316322AB2-045
Solar/Wind Harmer
0.516
270069AE2-166 C O1
Solar/Wind Harmer
8.011
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
943811AF1-049 GEN
Solar/Wind Harmer
3.851
316217AC1-145 GEN
Solar/Wind Harmer
2.402
316197AC1-042 GEN
Solar/Wind Harmer
1.821
3147312GRETNA
Solar/Wind Harmer
-0.003
270336AE1-100 GEN
Solar/Wind Harmer
1.568
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.128
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
61.91
957481AF2-042 GEN
Solar/Wind Harmer
167.038
315693AD1-088 GEN
Solar/Wind Harmer
24.377
970401AG2-262 GEN
Solar/Wind Harmer
2.098
316131AB2-060 GEN
Solar/Wind Harmer
3.062
315785AD2-033 C
Solar/Wind Harmer
6.268
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.524
971563AH1-280 GEN
Solar/Wind Harmer
3.332
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.131
316129AC1-054 GEN
Solar/Wind Harmer
1.825
970223AG2-152 GEN
Solar/Wind Harmer
17.233
270016AE1-250 BESS
Solar/Wind Harmer
2.845
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.377
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.554
270030AE2-140 GEN
Solar/Wind Harmer
19.819
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.772
3142053HEARTS
Solar/Wind Harmer
0.155
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.09 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5400.34
MW Contribution:
3.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.378
970413AG2-270 GEN
50/50
40.656
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
167.755
316478AD1-087 GEN
Solar/Wind Harmer
4.218
316003AC1-222 GEN
Solar/Wind Harmer
3.188
316222AC1-221 GEN
Solar/Wind Harmer
3.202
316283AC2-100 C
Solar/Wind Harmer
2.967
971683AH1-343 GEN
Solar/Wind Harmer
13.175
964241AG1-285 GEN
Solar/Wind Harmer
22.056
970257AG2-171 GEN
Solar/Wind Harmer
10.334
971775AH1-396 GEN
Solar/Wind Harmer
1.944
959311AF2-222 GEN
Solar/Wind Harmer
28.621
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.783
942461AE2-259 GEN
Solar/Wind Harmer
3.829
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.584
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.841
316217AC1-145 GEN
Solar/Wind Harmer
2.396
316197AC1-042 GEN
Solar/Wind Harmer
1.816
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.26
3144873MCLAUGH
Solar/Wind Helper
0.01
3142956BIRDNECK
Solar/Wind Helper
0.258
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.667
3146456SLIGO L269
Solar/Wind Helper
0.359
316305AF2-043 C
Solar/Wind Helper
0.474
316246AF1-032 C
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
1.935
316320Y1-086
Solar/Wind Helper
0.149
316321Z2-027
Solar/Wind Helper
0.487
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.606
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.296
316223AC1-118
Solar/Wind Helper
0.438
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.279
316473AC1-191 GEN
Solar/Wind Helper
1.693
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146376EDENTON
Solar/Wind Helper
0.226
315242AE2-183_GT2
50/50
11.03
315241AE2-183_GT1
50/50
11.001
972185AH1-677 GEN
50/50
39.871
3151041BRUNSWICKG3
50/50
8.378
972187AH1-678 GEN
50/50
19.224
970909AG2-566 GEN
50/50
3.293
3152661PLYWOOD A
50/50
0.662
3151581KERR 1
50/50
0.19
970535AG2-341 GEN
50/50
4.581
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
58.871
970099AG2-077 GEN
Solar/Wind Harmer
66.433
315687AD1-152 GEN
Solar/Wind Harmer
5.303
970301AG2-198 GEN
Solar/Wind Harmer
17.344
316248AF1-058 C
Solar/Wind Harmer
1.041
316118AC1-105 GEN
Solar/Wind Harmer
2.29
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.859
962561AG1-105 GEN
Solar/Wind Harmer
17.76
316237AB2-079_GEN
Solar/Wind Harmer
0.867
313527AB2-043 GEN
Solar/Wind Harmer
4.644
970323AG2-213 GEN
Solar/Wind Harmer
13.779
958211AF2-115 GEN
Solar/Wind Harmer
4.164
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.08
270013AE1-250 PV
Solar/Wind Harmer
2.837
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.893
316049AB1-081 GEN
Solar/Wind Harmer
1.452
316263AC1-034 GEN
Solar/Wind Harmer
6.326
961601AG1-000A GEN
Solar/Wind Harmer
5.194
316294AC1-161 GEN
Solar/Wind Helper
7.794
316185AD1-033 GEN
Solar/Wind Helper
1.802
3145506HICKORY
Solar/Wind Helper
1.505
3145506HICKORY
Solar/Wind Helper
0.903
3145506HICKORY
Solar/Wind Helper
0.226
316339AD2-160 GEN
Solar/Wind Helper
1.399
316388AE2-253 GEN
Solar/Wind Helper
1.399
3137176SLIGO L2192
Solar/Wind Helper
1.43
3130086AYDLETT
Solar/Wind Helper
1.419
316033AB2-134 GEN
Solar/Wind Helper
1.198
316349AD2-085 GEN
Solar/Wind Helper
1.524
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.493
315666AE1-190 GEN
Solar/Wind Helper
0.437
3142946ENON
Solar/Wind Helper
0.031
316487AF1-042 GEN
Solar/Wind Helper
0.317
315976AC1-164 GENA
Solar/Wind Helper
4.039
316169AC1-164_GENC
Solar/Wind Helper
3.489
316431W1029_GEN1
Solar/Wind Helper
1.223
316433W1029_GEN2
Solar/Wind Helper
1.223
316435W1029_GEN3
Solar/Wind Helper
1.223
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
316312AB1-027
Solar/Wind Helper
0.557
3143526WINTERP
Solar/Wind Helper
1.497
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.491
316315AB2-025 C
Solar/Wind Helper
0.418
315243AE2-183_GT3
50/50
11.03
3151051BRUNSWICKS1
50/50
17.394
3151021BRUNSWICKG1
50/50
8.378
971451AH1-221 GEN
50/50
25.443
3151531CLOVER1
50/50
9.336
3151591KERR 2
50/50
0.532
3151641KERR 7
50/50
0.532
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.474
971629AH1-314 GEN
50/50
17.894
3151561HALLBR1
50/50
0.362
970919AG2-571 GEN
Solar/Wind Harmer
21.235
970087AG2-069 GEN
Solar/Wind Harmer
61.506
957481AF2-042 GEN
Solar/Wind Harmer
166.083
315693AD1-088 GEN
Solar/Wind Harmer
24.245
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316131AB2-060 GEN
Solar/Wind Harmer
3.07
315785AD2-033 C
Solar/Wind Harmer
6.277
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.525
971563AH1-280 GEN
Solar/Wind Harmer
3.331
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.235
316129AC1-054 GEN
Solar/Wind Harmer
1.845
970223AG2-152 GEN
Solar/Wind Harmer
17.186
270016AE1-250 BESS
Solar/Wind Harmer
2.837
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.373
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.539
315244AE2-183_ST
50/50
19.154
963041AG1-153 GEN
50/50
16.962
3151541CLOVER2
50/50
9.264
3151601KERR 3
50/50
0.532
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
970673AG2-436 GEN
Solar/Wind Harmer
175.868
971967AH1-528 GEN
Solar/Wind Harmer
123.886
970085AG2-068 GEN
Solar/Wind Harmer
41.004
970581AG2-369 GEN
Solar/Wind Harmer
35.263
316486AD2-202 GEN
Solar/Wind Harmer
1.235
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.867
316239AB2-077_GEN
Solar/Wind Harmer
0.867
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.131
970681AG2-440 GEN
Solar/Wind Harmer
12.698
946301AF1-294 GEN
Solar/Wind Harmer
6.829
961791AG1-021 GEN
Solar/Wind Harmer
3.331
270455AD2-022 GEN
Solar/Wind Harmer
4.705
270457AD2-023 GEN
Solar/Wind Harmer
2.386
970831AG2-522 GEN
Solar/Wind Harmer
9.671
971845AH1-439 GEN
Solar/Wind Harmer
8.548
270197AD1-017 GEN1
Solar/Wind Harmer
1.675
316322AB2-045
Solar/Wind Harmer
0.514
270069AE2-166 C O1
Solar/Wind Harmer
7.989
316316AC1-027 C
Solar/Wind Helper
0.607
316236AE1-162_GEN
Solar/Wind Helper
0.499
316018AA1-139 ULT2
Solar/Wind Helper
1.569
3143316POE
Solar/Wind Helper
1.405
316382AG1-145 C
Solar/Wind Helper
0.47
316159AE1-175 C
Solar/Wind Helper
0.53
315697AD1-025 GEN
Solar/Wind Helper
3.957
957831AF2-077 GEN
Solar/Wind Helper
0.465
315839AE2-212 C
Solar/Wind Helper
0.458
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.437
3141873WAN 176
Solar/Wind Helper
0.065
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.44
316468AD1-105 GEN
Solar/Wind Helper
1.26
315800Z1-036_GEN1
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
270030AE2-140 GEN
Solar/Wind Harmer
19.766
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.815
3142053HEARTS
Solar/Wind Harmer
0.159
315773AC2-141 GEN
Solar/Wind Helper
9.171
316375AC2-012 GEN
Solar/Wind Helper
1.018
316036AC1-147 C
Solar/Wind Helper
0.591
3145336SMITFLD
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.359
319010AE1-072 C
Solar/Wind Helper
4.082
316072AD1-144
Solar/Wind Helper
0.405
316369SG1_INVT
Solar/Wind Helper
1.668
316381AD1-082 GEN
Solar/Wind Helper
1.76
316132AB2-190 GEN1
Solar/Wind Helper
1.935
315671AE2-027_GEN
Solar/Wind Helper
2.696
315662AE1-191 GEN
Solar/Wind Helper
1.75
316280AD1-041 GEN
Solar/Wind Helper
1.093
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.273
315975AC1-164 GENB
Solar/Wind Helper
0.119
316404AE1-155 C
Solar/Wind Helper
2.656
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.411
3141726DUNNSVL
Solar/Wind Helper
1.22
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
316337AD2-073 GEN
Solar/Wind Helper
0.449
3142416OLDCHRC
Solar/Wind Helper
0.758
3142416OLDCHRC
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.497
3143226MDLTHAN
Solar/Wind Helper
0.284
315611Z1-036_GEN2
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.147
MECLTFEXP_MEC->PJM
CLTF
7.373
SIGELTFEXP_SIGE->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
19.725
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.242
LAGNLTFEXP_LAGN->PJM
CLTF
14.661
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.209
TVALTFEXP_TVA->PJM
CLTF
7.311
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.679
WECLTFEXP_WEC->PJM
CLTF
1.402
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.51 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5321.19
MW Contribution:
3.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
10.936
315241AE2-183_GT1
50/50
10.907
972185AH1-677 GEN
50/50
39.531
3151041BRUNSWICKG3
50/50
8.307
972187AH1-678 GEN
50/50
19.06
970909AG2-566 GEN
50/50
3.258
3152661PLYWOOD A
50/50
0.655
3151581KERR 1
50/50
0.188
970535AG2-341 GEN
50/50
4.523
3144293JTRSVLE
50/50
0.593
970933AG2-581 GEN
Solar/Wind Harmer
58.356
970099AG2-077 GEN
Solar/Wind Harmer
65.833
315687AD1-152 GEN
Solar/Wind Harmer
5.255
970301AG2-198 GEN
Solar/Wind Harmer
17.157
316248AF1-058 C
Solar/Wind Harmer
1.031
316118AC1-105 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.78
962561AG1-105 GEN
Solar/Wind Harmer
17.549
316237AB2-079_GEN
Solar/Wind Harmer
0.854
313527AB2-043 GEN
Solar/Wind Harmer
4.577
970323AG2-213 GEN
Solar/Wind Harmer
13.586
958211AF2-115 GEN
Solar/Wind Harmer
4.107
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.933
270013AE1-250 PV
Solar/Wind Harmer
2.814
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.846
316049AB1-081 GEN
Solar/Wind Harmer
1.446
316263AC1-034 GEN
Solar/Wind Harmer
6.299
961601AG1-000A GEN
Solar/Wind Harmer
5.168
316294AC1-161 GEN
Solar/Wind Helper
7.251
316240AF1-291 C
Solar/Wind Helper
0.472
315244AE2-183_ST
50/50
18.991
963041AG1-153 GEN
50/50
16.818
3151541CLOVER2
50/50
9.18
3151601KERR 3
50/50
0.526
3151611KERR 4
50/50
0.526
3151621KERR 5
50/50
0.526
3151631KERR 6
50/50
0.526
970673AG2-436 GEN
Solar/Wind Harmer
174.37
971967AH1-528 GEN
Solar/Wind Harmer
122.813
970085AG2-068 GEN
Solar/Wind Harmer
40.657
970581AG2-369 GEN
Solar/Wind Harmer
34.965
316033AB2-134 GEN
Solar/Wind Helper
1.145
316185AD1-033 GEN
Solar/Wind Helper
1.553
3145506HICKORY
Solar/Wind Helper
1.296
3145506HICKORY
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.194
3144356SAPONY
Solar/Wind Helper
0.58
316315AB2-025 C
Solar/Wind Helper
0.494
316339AD2-160 GEN
Solar/Wind Helper
1.203
316388AE2-253 GEN
Solar/Wind Helper
1.203
316156AD2-030 GEN
Solar/Wind Helper
0.471
3142946ENON
Solar/Wind Helper
0.031
315666AE1-190 GEN
Solar/Wind Helper
0.419
3137176SLIGO L2192
Solar/Wind Helper
1.227
3151031BRUNSWICKG2
50/50
8.307
970413AG2-270 GEN
50/50
40.285
3144293JTRSVLE
50/50
0.593
970917AG2-570 GEN
Solar/Wind Harmer
166.334
316478AD1-087 GEN
Solar/Wind Harmer
4.179
316003AC1-222 GEN
Solar/Wind Harmer
3.156
316222AC1-221 GEN
Solar/Wind Harmer
3.175
316283AC2-100 C
Solar/Wind Harmer
2.943
971683AH1-343 GEN
Solar/Wind Harmer
13.046
964241AG1-285 GEN
Solar/Wind Harmer
21.742
970257AG2-171 GEN
Solar/Wind Harmer
10.19
971775AH1-396 GEN
Solar/Wind Harmer
1.917
959311AF2-222 GEN
Solar/Wind Harmer
28.221
3147133PAMPLIN
Solar/Wind Harmer
-0.081
316123AC1-075 GEN
Solar/Wind Harmer
2.756
942461AE2-259 GEN
Solar/Wind Harmer
3.778
3146926FARMVIL
Solar/Wind Harmer
-0.014
270574AD1-017 GEN2
Solar/Wind Harmer
5.536
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.808
316217AC1-145 GEN
Solar/Wind Harmer
2.372
316197AC1-042 GEN
Solar/Wind Harmer
1.798
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.55
961601AG1-000A GEN
Solar/Wind Harmer
5.233
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
3142956BIRDNECK
Solar/Wind Helper
0.223
316458AB2-190 GEN2
Solar/Wind Helper
1.896
316017AA1-139 ULT1
Solar/Wind Helper
1.432
3142946ENON
Solar/Wind Helper
0.104
316486AD2-202 GEN
Solar/Wind Harmer
1.224
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.854
316239AB2-077_GEN
Solar/Wind Harmer
0.854
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
18.866
970681AG2-440 GEN
Solar/Wind Harmer
12.522
946301AF1-294 GEN
Solar/Wind Harmer
6.735
961791AG1-021 GEN
Solar/Wind Harmer
3.286
270455AD2-022 GEN
Solar/Wind Harmer
4.668
270457AD2-023 GEN
Solar/Wind Harmer
2.367
970831AG2-522 GEN
Solar/Wind Harmer
9.555
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
971845AH1-439 GEN
Solar/Wind Harmer
8.41
316322AB2-045
Solar/Wind Harmer
0.505
270069AE2-166 C O1
Solar/Wind Harmer
7.921
3143316POE
Solar/Wind Helper
1.568
315839AE2-212 C
Solar/Wind Helper
0.498
316236AE1-162_GEN
Solar/Wind Helper
0.448
316316AC1-027 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
3.782
316382AG1-145 C
Solar/Wind Helper
0.442
316159AE1-175 C
Solar/Wind Helper
0.498
957831AF2-077 GEN
Solar/Wind Helper
0.436
316018AA1-139 ULT2
Solar/Wind Helper
1.348
957601AF2-054 GEN
Solar/Wind Helper
0.417
3141873WAN 176
Solar/Wind Helper
0.062
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.313
3141913WHIT STONE
Solar/Wind Helper
0.309
315243AE2-183_GT3
50/50
10.936
3151051BRUNSWICKS1
50/50
17.246
3151021BRUNSWICKG1
50/50
8.307
971451AH1-221 GEN
50/50
25.226
3151531CLOVER1
50/50
9.25
3151591KERR 2
50/50
0.526
3151641KERR 7
50/50
0.526
3144293JTRSVLE
50/50
0.593
3144293JTRSVLE
50/50
0.468
971629AH1-314 GEN
50/50
17.75
3151561HALLBR1
50/50
0.359
970919AG2-571 GEN
Solar/Wind Harmer
21.055
970087AG2-069 GEN
Solar/Wind Harmer
60.986
957481AF2-042 GEN
Solar/Wind Harmer
164.583
315693AD1-088 GEN
Solar/Wind Harmer
24.018
970401AG2-262 GEN
Solar/Wind Harmer
2.072
316131AB2-060 GEN
Solar/Wind Harmer
3.026
315785AD2-033 C
Solar/Wind Harmer
6.188
316034AC1-036 C
Solar/Wind Harmer
0.502
970685AG2-442 GEN
Solar/Wind Harmer
23.201
971563AH1-280 GEN
Solar/Wind Harmer
3.286
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.105
316129AC1-054 GEN
Solar/Wind Harmer
1.824
970223AG2-152 GEN
Solar/Wind Harmer
17.044
270016AE1-250 BESS
Solar/Wind Harmer
2.814
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.362
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.486
270030AE2-140 GEN
Solar/Wind Harmer
19.599
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.807
3142053HEARTS
Solar/Wind Harmer
0.158
315773AC2-141 GEN
Solar/Wind Helper
8.532
315671AE2-027_GEN
Solar/Wind Helper
2.884
316381AD1-082 GEN
Solar/Wind Helper
1.75
316375AC2-012 GEN
Solar/Wind Helper
0.883
316036AC1-147 C
Solar/Wind Helper
0.512
3145336SMITFLD
Solar/Wind Helper
1.329
316132AB2-190 GEN1
Solar/Wind Helper
1.896
316369SG1_INVT
Solar/Wind Helper
1.594
3142433PROV 92
Solar/Wind Helper
1.252
3142543TWELFTH
Solar/Wind Helper
0.03
315662AE1-191 GEN
Solar/Wind Helper
1.677
316280AD1-041 GEN
Solar/Wind Helper
1.048
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
316349AD2-085 GEN
Solar/Wind Helper
1.397
315976AC1-164 GENA
Solar/Wind Helper
3.933
316169AC1-164_GENC
Solar/Wind Helper
3.397
3130086AYDLETT
Solar/Wind Helper
1.217
316487AF1-042 GEN
Solar/Wind Helper
0.305
3143526WINTERP
Solar/Wind Helper
1.516
316312AB1-027
Solar/Wind Helper
0.551
3146386ELIZ CT
Solar/Wind Helper
0.282
966871AG1-558 GEN
Solar/Wind Helper
0.375
316431W1029_GEN1
Solar/Wind Helper
1.035
316433W1029_GEN2
Solar/Wind Helper
1.035
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.582
316075AC2-137 C
Solar/Wind Helper
0.459
316305AF2-043 C
Solar/Wind Helper
0.402
316246AF1-032 C
Solar/Wind Helper
0.342
316077AC2-138 C
Solar/Wind Helper
0.276
316320Y1-086
Solar/Wind Helper
0.127
316473AC1-191 GEN
Solar/Wind Helper
1.701
316223AC1-118
Solar/Wind Helper
0.424
3141906WESTMOR
Solar/Wind Helper
0.111
316321Z2-027
Solar/Wind Helper
0.414
3146516WINFALL
Solar/Wind Helper
0.25
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.235
316435W1029_GEN3
Solar/Wind Helper
1.035
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146626S HERTFORD
Solar/Wind Helper
0.235
3146626S HERTFORD
Solar/Wind Helper
0.235
3138133OCRAN
Solar/Wind Helper
0.092
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.445
313526AB2-022
Solar/Wind Helper
0.431
3146486SUNBURY
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.273
3145176PASQUOTANK
Solar/Wind Helper
0.168
316468AD1-105 GEN
Solar/Wind Helper
1.263
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.351
319010AE1-072 C
Solar/Wind Helper
3.502
315975AC1-164 GENB
Solar/Wind Helper
0.116
316404AE1-155 C
Solar/Wind Helper
2.553
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.177
3143526WINTERP
Solar/Wind Helper
1.516
3142416OLDCHRC
Solar/Wind Helper
0.75
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.287
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.811
3146516WINFALL
Solar/Wind Helper
0.25
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.924
MECLTFEXP_MEC->PJM
CLTF
7.297
SIGELTFEXP_SIGE->PJM
CLTF
0.219
CPLELTFEXP_CPLE->PJM
CLTF
19.597
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.518
LAGNLTFEXP_LAGN->PJM
CLTF
14.534
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.89
TVALTFEXP_TVA->PJM
CLTF
7.248
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.65
WECLTFEXP_WEC->PJM
CLTF
1.386
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:873.8
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
970937AG2-583 GEN
Solar/Wind Harmer
28.694
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.71 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:870.6
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
971967AH1-528 GEN
Solar/Wind Harmer
17.83
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970933AG2-581 GEN
Solar/Wind Harmer
8.916
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
970937AG2-583 GEN
Solar/Wind Harmer
28.694
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.13 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:705.38
MW Contribution:
4.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.885
970413AG2-270 GEN
50/50
12.4
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.537
3147133PAMPLIN
Solar/Wind Harmer
-0.132
959311AF2-222 GEN
Solar/Wind Harmer
33.507
970257AG2-171 GEN
Solar/Wind Harmer
11.573
971775AH1-396 GEN
Solar/Wind Harmer
2.177
964241AG1-285 GEN
Solar/Wind Harmer
19.228
316478AD1-087 GEN
Solar/Wind Harmer
1.286
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
1.104
971683AH1-343 GEN
Solar/Wind Harmer
4.42
966621AG1-532 GEN
Solar/Wind Harmer
0.172
316181AB2-040 GEN
Solar/Wind Harmer
1.135
316123AC1-075 GEN
Solar/Wind Harmer
0.85
316222AC1-221 GEN
Solar/Wind Harmer
0.766
316283AC2-100 C
Solar/Wind Harmer
0.704
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316212AC1-099_GEN
Solar/Wind Harmer
0.551
3146776BUCKING
Solar/Wind Helper
0.313
270494AE1-108_GEN
Solar/Wind Helper
4.51
315821AE2-092 GEN
Solar/Wind Helper
3.005
3148013FISHERV
Solar/Wind Helper
0.125
970909AG2-566 GEN
50/50
4.036
3144293JTRSVLE
50/50
0.885
970535AG2-341 GEN
50/50
2.835
3151581KERR 1
50/50
0.098
3152661PLYWOOD A
50/50
0.264
970301AG2-198 GEN
Solar/Wind Harmer
21.254
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.132
970323AG2-213 GEN
Solar/Wind Harmer
15.431
313527AB2-043 GEN
Solar/Wind Harmer
3.439
316237AB2-079_GEN
Solar/Wind Harmer
0.619
962561AG1-105 GEN
Solar/Wind Harmer
9.453
964791AG1-342 GEN
Solar/Wind Harmer
3.422
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.09
316118AC1-105 GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
1.607
316248AF1-058 C
Solar/Wind Harmer
0.37
970933AG2-581 GEN
Solar/Wind Harmer
9.073
313506AB2-031 GEN
Solar/Wind Harmer
0.654
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.904
3145783HORNRTN
Solar/Wind Harmer
0.723
3151601KERR 3
50/50
0.273
3151611KERR 4
50/50
0.273
3151621KERR 5
50/50
0.273
3151631KERR 6
50/50
0.273
3151541CLOVER2
50/50
2.825
971845AH1-439 GEN
Solar/Wind Harmer
40.084
946301AF1-294 GEN
Solar/Wind Harmer
10.057
961791AG1-021 GEN
Solar/Wind Harmer
4.906
970683AG2-441 GEN
Solar/Wind Harmer
24.846
970681AG2-440 GEN
Solar/Wind Harmer
16.491
3144303KENBRDG
Solar/Wind Harmer
-0.025
316238AB2-078_GEN
Solar/Wind Harmer
0.619
316239AB2-077_GEN
Solar/Wind Harmer
0.619
316486AD2-202 GEN
Solar/Wind Harmer
0.377
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
5.983
946281AF1-292 GEN
Solar/Wind Harmer
0.19
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.946
316426AA2-053 GEN
Solar/Wind Harmer
0.745
3146043SEABORD
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.714
316210AC1-098 GEN
Solar/Wind Harmer
0.992
316322AB2-045
Solar/Wind Helper
0.974
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3145783HORNRTN
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
0.09
942751AE2-291 GEN
Solar/Wind Harmer
4.329
972187AH1-678 GEN
Adder
1.628
3146776BUCKING
Solar/Wind Helper
3.482
3146776BUCKING
Solar/Wind Helper
0.282
316313AB2-026
Solar/Wind Helper
0.342
3144293JTRSVLE
50/50
0.885
3144293JTRSVLE
50/50
0.699
3151591KERR 2
50/50
0.273
3151641KERR 7
50/50
0.273
3151531CLOVER1
50/50
2.847
3146926FARMVIL
Solar/Wind Harmer
-0.035
971563AH1-280 GEN
Solar/Wind Harmer
4.906
970685AG2-442 GEN
Solar/Wind Harmer
32.421
316034AC1-036 C
Solar/Wind Harmer
0.572
315785AD2-033 C
Solar/Wind Harmer
6.596
316131AB2-060 GEN
Solar/Wind Harmer
2.351
315693AD1-088 GEN
Solar/Wind Harmer
9.995
970401AG2-262 GEN
Solar/Wind Harmer
1.045
957481AF2-042 GEN
Solar/Wind Harmer
45.225
971065AG2-659 GEN
Solar/Wind Harmer
6.468
316129AC1-054 GEN
Solar/Wind Harmer
1.094
3147043LAWRENC
Adder
0.993
960081AF2-299 GEN
Solar/Wind Harmer
0.953
316087AB2-174 GEN
Solar/Wind Harmer
1.175
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.713
3146776BUCKING
Solar/Wind Helper
0.348
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.131
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.951
MECLTFEXP_MEC->PJM
CLTF
0.638
SIGELTFEXP_SIGE->PJM
CLTF
0.017
CPLELTFEXP_CPLE->PJM
CLTF
3.712
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.597
LAGNLTFEXP_LAGN->PJM
CLTF
1.834
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.444
TVALTFEXP_TVA->PJM
CLTF
0.9
NYPJM->LTFIMP_NY
CLTF
0.343
LGEELTFEXP_LGEE->PJM
CLTF
0.184
WECLTFEXP_WEC->PJM
CLTF
0.096

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:736.99
MW Contribution:
4.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.884
970413AG2-270 GEN
50/50
12.38
972003AH1-546 GEN
Solar/Wind Harmer
39.017
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.534
3147133PAMPLIN
Solar/Wind Harmer
-0.131
959311AF2-222 GEN
Solar/Wind Harmer
33.483
970257AG2-171 GEN
Solar/Wind Harmer
11.564
971775AH1-396 GEN
Solar/Wind Harmer
2.176
964241AG1-285 GEN
Solar/Wind Harmer
19.21
316478AD1-087 GEN
Solar/Wind Harmer
1.284
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
1.102
971683AH1-343 GEN
Solar/Wind Harmer
4.41
966621AG1-532 GEN
Solar/Wind Harmer
0.171
316181AB2-040 GEN
Solar/Wind Harmer
1.132
316123AC1-075 GEN
Solar/Wind Harmer
0.848
316222AC1-221 GEN
Solar/Wind Harmer
0.764
316283AC2-100 C
Solar/Wind Harmer
0.702
316190AA2-174 GEN
Solar/Wind Harmer
0.09
270494AE1-108_GEN
Solar/Wind Helper
4.516
315821AE2-092 GEN
Solar/Wind Helper
3.008
3148013FISHERV
Solar/Wind Helper
0.125
970909AG2-566 GEN
50/50
4.033
3144293JTRSVLE
50/50
0.884
970535AG2-341 GEN
50/50
2.831
3151581KERR 1
50/50
0.097
3152661PLYWOOD A
50/50
0.263
3146776BUCKING
Solar/Wind Harmer
-0.306
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.243
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.129
970323AG2-213 GEN
Solar/Wind Harmer
15.419
313527AB2-043 GEN
Solar/Wind Harmer
3.435
316237AB2-079_GEN
Solar/Wind Harmer
0.618
962561AG1-105 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.417
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.061
316118AC1-105 GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
1.604
316248AF1-058 C
Solar/Wind Harmer
0.369
970933AG2-581 GEN
Solar/Wind Harmer
9.052
313506AB2-031 GEN
Solar/Wind Harmer
0.652
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.721
3145783HORNRTN
Solar/Wind Harmer
0.225
3145783HORNRTN
Solar/Wind Harmer
0.09
942751AE2-291 GEN
Solar/Wind Harmer
4.314
972187AH1-678 GEN
Adder
1.622
316313AB2-026
Solar/Wind Helper
0.342
3151601KERR 3
50/50
0.273
3151611KERR 4
50/50
0.273
3151621KERR 5
50/50
0.273
3151631KERR 6
50/50
0.273
3151541CLOVER2
50/50
2.821
316322AB2-045
Solar/Wind Harmer
2.582
971845AH1-439 GEN
Solar/Wind Harmer
40.071
946301AF1-294 GEN
Solar/Wind Harmer
10.051
961791AG1-021 GEN
Solar/Wind Harmer
4.903
970683AG2-441 GEN
Solar/Wind Harmer
24.83
970681AG2-440 GEN
Solar/Wind Harmer
16.48
3144303KENBRDG
Solar/Wind Harmer
-0.025
316238AB2-078_GEN
Solar/Wind Harmer
0.618
316239AB2-077_GEN
Solar/Wind Harmer
0.618
316486AD2-202 GEN
Solar/Wind Harmer
0.376
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
5.971
946281AF1-292 GEN
Solar/Wind Harmer
0.189
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.903
316426AA2-053 GEN
Solar/Wind Harmer
0.743
3146043SEABORD
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.712
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
0.884
3144293JTRSVLE
50/50
0.698
3151591KERR 2
50/50
0.273
3151641KERR 7
50/50
0.273
3151531CLOVER1
50/50
2.843
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
971563AH1-280 GEN
Solar/Wind Harmer
4.903
970685AG2-442 GEN
Solar/Wind Harmer
32.4
316034AC1-036 C
Solar/Wind Harmer
0.571
315785AD2-033 C
Solar/Wind Harmer
6.591
316131AB2-060 GEN
Solar/Wind Harmer
2.349
315693AD1-088 GEN
Solar/Wind Harmer
9.984
970401AG2-262 GEN
Solar/Wind Harmer
1.044
957481AF2-042 GEN
Solar/Wind Harmer
45.152
971065AG2-659 GEN
Solar/Wind Harmer
6.457
316129AC1-054 GEN
Solar/Wind Harmer
1.092
3147043LAWRENC
Adder
0.991
960081AF2-299 GEN
Solar/Wind Harmer
0.95
316087AB2-174 GEN
Solar/Wind Harmer
1.171
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.71
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.9
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.89
MECLTFEXP_MEC->PJM
CLTF
0.611
SIGELTFEXP_SIGE->PJM
CLTF
0.017
CPLELTFEXP_CPLE->PJM
CLTF
3.694
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.383
LAGNLTFEXP_LAGN->PJM
CLTF
1.802
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.396
TVALTFEXP_TVA->PJM
CLTF
0.884
NYPJM->LTFIMP_NY
CLTF
0.353
LGEELTFEXP_LGEE->PJM
CLTF
0.173
WECLTFEXP_WEC->PJM
CLTF
0.09

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.97 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:705.81
MW Contribution:
4.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.285
3151611KERR 4
50/50
0.285
3151621KERR 5
50/50
0.285
3151631KERR 6
50/50
0.285
3151541CLOVER2
50/50
2.933
316322AB2-045
Solar/Wind Harmer
2.594
971845AH1-439 GEN
Solar/Wind Harmer
40.261
946301AF1-294 GEN
Solar/Wind Harmer
10.181
961791AG1-021 GEN
Solar/Wind Harmer
4.966
970683AG2-441 GEN
Solar/Wind Harmer
25.2
970681AG2-440 GEN
Solar/Wind Harmer
16.726
3144303KENBRDG
Solar/Wind Harmer
-0.025
316238AB2-078_GEN
Solar/Wind Harmer
0.636
316239AB2-077_GEN
Solar/Wind Harmer
0.636
316486AD2-202 GEN
Solar/Wind Harmer
0.391
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.293
946281AF1-292 GEN
Solar/Wind Harmer
0.203
3137643SOCKMAN
Solar/Wind Harmer
-0.034
971967AH1-528 GEN
Solar/Wind Harmer
15.92
316426AA2-053 GEN
Solar/Wind Harmer
0.807
3146043SEABORD
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.788
316210AC1-098 GEN
Solar/Wind Harmer
1.098
316327AA2-057 GEN
Solar/Wind Harmer
0.702
970085AG2-068 GEN
Solar/Wind Harmer
4.3
970581AG2-369 GEN
Solar/Wind Harmer
3.698
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.528
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.25
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
0.896
970413AG2-270 GEN
50/50
12.873
972003AH1-546 GEN
Solar/Wind Harmer
39.131
3146776BUCKING
Solar/Wind Harmer
-0.028
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.603
3147133PAMPLIN
Solar/Wind Harmer
-0.133
959311AF2-222 GEN
Solar/Wind Harmer
34.045
970257AG2-171 GEN
Solar/Wind Harmer
11.768
971775AH1-396 GEN
Solar/Wind Harmer
2.214
964241AG1-285 GEN
Solar/Wind Harmer
19.657
316478AD1-087 GEN
Solar/Wind Harmer
1.336
3147043LAWRENC
Solar/Wind Harmer
-0.008
316003AC1-222 GEN
Solar/Wind Harmer
1.157
971683AH1-343 GEN
Solar/Wind Harmer
4.627
966621AG1-532 GEN
Solar/Wind Harmer
0.184
316181AB2-040 GEN
Solar/Wind Harmer
1.219
316222AC1-221 GEN
Solar/Wind Harmer
0.851
316283AC2-100 C
Solar/Wind Harmer
0.784
316123AC1-075 GEN
Solar/Wind Harmer
0.888
316190AA2-174 GEN
Solar/Wind Harmer
0.098
316212AC1-099_GEN
Solar/Wind Harmer
0.61
970917AG2-570 GEN
Solar/Wind Harmer
17.254
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.398
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
2.351
961601AG1-000A GEN
Solar/Wind Harmer
2.603
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.079
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.481
315821AE2-092 GEN
Solar/Wind Helper
2.977
3148013FISHERV
Solar/Wind Helper
0.124
970909AG2-566 GEN
50/50
4.079
3144293JTRSVLE
50/50
0.896
970535AG2-341 GEN
50/50
2.929
3151581KERR 1
50/50
0.102
3152661PLYWOOD A
50/50
0.275
3146776BUCKING
Solar/Wind Harmer
-0.308
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.48
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.208
970323AG2-213 GEN
Solar/Wind Harmer
15.691
313527AB2-043 GEN
Solar/Wind Harmer
3.53
316237AB2-079_GEN
Solar/Wind Harmer
0.636
962561AG1-105 GEN
Solar/Wind Harmer
9.778
964791AG1-342 GEN
Solar/Wind Harmer
3.545
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.773
316118AC1-105 GEN
Solar/Wind Harmer
1.009
315687AD1-152 GEN
Solar/Wind Harmer
1.681
316248AF1-058 C
Solar/Wind Harmer
0.387
970933AG2-581 GEN
Solar/Wind Harmer
9.564
313506AB2-031 GEN
Solar/Wind Harmer
0.702
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.978
3145783HORNRTN
Solar/Wind Harmer
0.783
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
942751AE2-291 GEN
Solar/Wind Harmer
4.517
972187AH1-678 GEN
Adder
1.766
962571AG1-106 GEN
Solar/Wind Harmer
0.962
972185AH1-677 GEN
Adder
3.335
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316049AB1-081 GEN
Solar/Wind Harmer
0.714
316263AC1-034 GEN
Solar/Wind Harmer
3.112
315724AD1-057 GEN
Solar/Wind Harmer
1.293
316365GEN2_N
Solar/Wind Harmer
0.44
961601AG1-000A GEN
Solar/Wind Harmer
2.571
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316313AB2-026
Solar/Wind Helper
0.334
3144293JTRSVLE
50/50
0.896
3144293JTRSVLE
50/50
0.707
3151591KERR 2
50/50
0.285
3151641KERR 7
50/50
0.285
3151531CLOVER1
50/50
2.956
3147043LAWRENC
50/50
1.103
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
971563AH1-280 GEN
Solar/Wind Harmer
4.966
970685AG2-442 GEN
Solar/Wind Harmer
32.852
316034AC1-036 C
Solar/Wind Harmer
0.582
315785AD2-033 C
Solar/Wind Harmer
6.715
316131AB2-060 GEN
Solar/Wind Harmer
2.412
315693AD1-088 GEN
Solar/Wind Harmer
10.261
970401AG2-262 GEN
Solar/Wind Harmer
1.083
957481AF2-042 GEN
Solar/Wind Harmer
46.933
971065AG2-659 GEN
Solar/Wind Harmer
6.779
316129AC1-054 GEN
Solar/Wind Harmer
1.148
960081AF2-299 GEN
Solar/Wind Harmer
1.018
316087AB2-174 GEN
Solar/Wind Harmer
1.259
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.773
970919AG2-571 GEN
Solar/Wind Harmer
2.184
970087AG2-069 GEN
Solar/Wind Harmer
6.45
316319Z2-044 C
Solar/Wind Harmer
0.377
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.893
3142053HEARTS
Solar/Wind Harmer
0.078
316023GEN1_S
Solar/Wind Harmer
0.44
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.813
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.884
MECLTFEXP_MEC->PJM
CLTF
0.804
SIGELTFEXP_SIGE->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
4.521
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.285
LAGNLTFEXP_LAGN->PJM
CLTF
2.464
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.192
TVALTFEXP_TVA->PJM
CLTF
1.196
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.206
WECLTFEXP_WEC->PJM
CLTF
0.115
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P2-2: BREMO B3_SRT-A'
 OPEN BRANCH FROM BUS 313708 TO BUS 314744 CKT 2   /*3FORK UNION  115.0 - 3BREMO       115.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314746 CKT 1   /*3BREMO       115.0 - 4BREMO       138.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 2   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BUS 314868                                   /*3BREMO_1     115.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 587T591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 55692_SRT-S'
 OPEN BRANCH FROM BUS 314936 TO BUS 971966 CKT 1                /*8RAWLINGS    500.0 - AH1-528 TP   500.0
 OPEN BUS 314920                                                /*8RAWLIN_STC1 500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 550_SRT-A'
 OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1   /*8MT STM      500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P4-2: 202712_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1                /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1                /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                                /*6POWHATN     230.0
 OPEN BUS 316258                                                /*AE1-075 C    230.0
 OPEN BUS 316313                                                /*AB2-026      230.0
 OPEN BUS 316405                                                /*AF2-144 C    230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
END
CONTINGENCY 'DVP_P1-2: LN 2028_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P4-2: 2028T2054_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1   /*6CHARLVL     230.0 - 6PROFFIT     230.0
 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1   /*6HOLLYMD     230.0 - 6PROFFIT     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
 OPEN BUS 314772                                   /*6PROFFIT     230.0
END
CONTINGENCY 'DVP_P4-2: 233T2028_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1   /*6HYDRAULIC   230.0 - 6BARRCK2     230.0
 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1   /*6HYDRAULIC   230.0 - 6CHARLVL     230.0
 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1   /*6BARRCK2     230.0 - 6CROZET1     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1   /*6CROZET1     230.0 - 6DOOMS       230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 313826                                   /*6HYDRAULIC   230.0
 OPEN BUS 314742                                   /*6BARRCK2     230.0
 OPEN BUS 314751                                   /*6CROZET1     230.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P4-2: 2028T2193_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P4-2: WT2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313708 CKT 1   /*6FORK UNION  230.0 - 3FORK UNION  115.0
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P1-2: LN 298_SRT-A-4'
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 941030 TO BUS 970672 CKT 1   /*AE2-094 TP   500.0 - AG2-436 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 58572_SRT-A'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-5: W72_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1   /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: XT585_SRT-S'
 OPEN BRANCH FROM BUS 970672 TO BUS 314940 CKT 1                /*AG2-436 TP   500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
END
CONTINGENCY 'DVP_P4-2: 54472_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51192_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51172_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T544_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P7-1: LN 2106-2111_SRT-A'
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
END
CONTINGENCY 'AEP_P2-2_#1377_05J.FERR 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1   /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1   /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1   /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1   /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
314744 to 313708 ckt 2
314747 to 313867 ckt 1
314747 to 970936 ckt 1
313867 to 313707 ckt 1
314268 to 314692 ckt 1
313868 to 316335 ckt 1
314749 to 314772 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1
314333 to 314322 ckt 1
314772 to 314759 ckt 1
314902 to 314914 ckt 1
314914 to 314918 ckt 1
314936 to 314902 ckt 1
314940 to 970672 ckt 1
316335 to 314333 ckt 1
941030 to 314902 ckt 1
970300 to 314268 ckt 1
970672 to 941030 ckt 1
970936 to 313868 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Winter Peak Analysis

The New Service Request AG2-566 was evaluated as a 30.0 MW (12.0 MW Capacity) injection in the Dominion area.

AG2-566 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 110.0 MW (30.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-566 was evaluated as a 30.0 MW injection and 30.0 MW withdrawal in the Dominion area.

AG2-566 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 110.0 MW (30.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC116.71 %541.0B631.41
4.04
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC106.94 %508.54B543.83
4.0
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC123.01 %508.54B625.53
8.97
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC114.14 %541.0B617.48
8.97
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC114.14 %541.0B617.48
8.97
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC111.38 %508.54B566.4
8.97

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.71 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:631.41
MW Contribution:
4.04
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.84 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:615.89
MW Contribution:
4.31
Bus #Bus NameTypeMW Contribution
970919AG2-571 GEN
Solar/Wind Harmer
15.025
961601AG1-000A GEN
Solar/Wind Harmer
2.91
961601AG1-000A GEN
Solar/Wind Harmer
4.014
316118AC1-105 GEN
Solar/Wind Helper
4.009
270069AE2-166 C O1
Solar/Wind Harmer
3.403
3145493TOT1
Solar/Wind Harmer
0.175
3146233WITAKRS
Solar/Wind Harmer
0.108
316197AC1-042 GEN
Solar/Wind Helper
0.53
3146233WITAKRS
Solar/Wind Harmer
0.63
3146083TARBORO
Solar/Wind Harmer
0.175
3138543CONSLDL
Solar/Wind Harmer
0.107
316222AC1-221 GEN
Solar/Wind Helper
14.034
316486AD2-202 GEN
Solar/Wind Helper
1.116
316131AB2-060 GEN
Solar/Wind Helper
3.449
971629AH1-314 GEN
50/50
14.763
943811AF1-049 GEN
Solar/Wind Harmer
0
3146073TAR RVR
Solar/Wind Harmer
0.175
316003AC1-222 GEN
Solar/Wind Helper
5.22
316359AB2-059 GEN
Solar/Wind Harmer
0
3142053HEARTS
Solar/Wind Harmer
0.078
3146083TARBORO
Solar/Wind Harmer
0.175
316478AD1-087 GEN
Solar/Wind Helper
3.812
970413AG2-270 GEN
50/50
Charging
32.717
970909AG2-566 GEN
50/50
Charging
4.037
316034AC1-036 C
Solar/Wind Helper
0.588
957861AF2-080 GEN
Solar/Wind Harmer
2.16
316248AF1-058 C
Solar/Wind Helper
1.755
316123AC1-075 GEN
Solar/Wind Helper
4.419
316322AB2-045
Solar/Wind Helper
0.473
316129AC1-054 GEN
Solar/Wind Helper
1.268
3145573BETHELC
Solar/Wind Harmer
0.175
315687AD1-152 GEN
Solar/Wind Helper
6.698
942461AE2-259 GEN
Solar/Wind Helper
3.443
970535AG2-341 GEN
50/50
Charging
6.427
3145543BTLEBRO
Solar/Wind Harmer
0.195
3145543BTLEBRO
Solar/Wind Harmer
0.195
3145543BTLEBRO
Solar/Wind Harmer
0.156
961671AG1-007 GEN
Solar/Wind Harmer
0.329
3145453TOT5
Solar/Wind Harmer
0.055
316263AC1-034 GEN
Solar/Wind Harmer
2.947
3145573BETHELC
Solar/Wind Harmer
0.175
3145603CNETO
Solar/Wind Harmer
0.037
316237AB2-079_GEN
Solar/Wind Helper
0.878
316238AB2-078_GEN
Solar/Wind Helper
0.878
316239AB2-077_GEN
Solar/Wind Helper
0.878
970917AG2-570 GEN
Solar/Wind Harmer
34.858
970581AG2-369 GEN
Solar/Wind Harmer
7.495
3146233WITAKRS
Solar/Wind Harmer
0.38
313527AB2-043 GEN
Solar/Wind Helper
2.161
3145543BTLEBRO
Solar/Wind Harmer
0.195
315773AC2-141 GEN
Solar/Wind Helper
3.082
970085AG2-068 GEN
Solar/Wind Harmer
8.715
970087AG2-069 GEN
Solar/Wind Harmer
13.073
970223AG2-152 GEN
Solar/Wind Harmer
7.46
3145493TOT1
Solar/Wind Harmer
0.091
315785AD2-033 C
Solar/Wind Helper
4.903
316217AC1-145 GEN
Solar/Wind Helper
0.682
270030AE2-140 GEN
Solar/Wind Harmer
8.971
316283AC2-100 C
Solar/Wind Helper
13.217
316294AC1-161 GEN
Solar/Wind Helper
1.112
900033ID_568986
External Queue
3.581075668334961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.125
LGEELTFEXP_LGEE->PJM
CLTF
1.54
MECLTFEXP_MEC->PJM
CLTF
4.438
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.447
CPLELTFEXP_CPLE->PJM
CLTF
11.761
SIGELTFEXP_SIGE->PJM
CLTF
0.131
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.413
WECLTFEXP_WEC->PJM
CLTF
0.841
LAGNLTFEXP_LAGN->PJM
CLTF
8.852
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.096
NYPJM->LTFIMP_NY
CLTF
0.292
TVALTFEXP_TVA->PJM
CLTF
4.501
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
25.485

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.94 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:543.83
MW Contribution:
4.0
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:98.78 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:502.35
MW Contribution:
4.27
Bus #Bus NameTypeMW Contribution
970919AG2-571 GEN
Solar/Wind Harmer
15.147
316118AC1-105 GEN
Solar/Wind Helper
3.992
970417AG2-272 GEN
50/50
4.749
270069AE2-166 C O1
Solar/Wind Harmer
3.464
3145493TOT1
Solar/Wind Harmer
0.179
3146233WITAKRS
Solar/Wind Harmer
0.11
970533AG2-339 GEN
50/50
Charging
6.339
3146233WITAKRS
Solar/Wind Harmer
0.644
963041AG1-153 GEN
50/50
Charging
6.303
3146083TARBORO
Solar/Wind Harmer
0.179
3138543CONSLDL
Solar/Wind Harmer
0.11
316222AC1-221 GEN
Solar/Wind Helper
14.01
316486AD2-202 GEN
Solar/Wind Helper
1.11
316131AB2-060 GEN
Solar/Wind Helper
3.422
971629AH1-314 GEN
50/50
14.885
943811AF1-049 GEN
Solar/Wind Harmer
0
3146073TAR RVR
Solar/Wind Harmer
0.179
316003AC1-222 GEN
Solar/Wind Helper
5.199
316359AB2-059 GEN
Solar/Wind Harmer
0
3142053HEARTS
Solar/Wind Harmer
0.079
3146083TARBORO
Solar/Wind Harmer
0.179
316478AD1-087 GEN
Solar/Wind Helper
3.79
970413AG2-270 GEN
50/50
Charging
32.533
970909AG2-566 GEN
50/50
Charging
4
316034AC1-036 C
Solar/Wind Helper
0.583
957861AF2-080 GEN
Solar/Wind Harmer
2.209
316248AF1-058 C
Solar/Wind Helper
1.749
316123AC1-075 GEN
Solar/Wind Helper
4.393
316322AB2-045
Solar/Wind Helper
0.467
316129AC1-054 GEN
Solar/Wind Helper
1.247
972287SS25-0012
50/50
Charging
12.035
3145573BETHELC
Solar/Wind Harmer
0.179
315687AD1-152 GEN
Solar/Wind Helper
6.672
942461AE2-259 GEN
Solar/Wind Helper
3.41
970535AG2-341 GEN
50/50
Charging
6.366
3145543BTLEBRO
Solar/Wind Harmer
0.199
3145543BTLEBRO
Solar/Wind Harmer
0.199
3145543BTLEBRO
Solar/Wind Harmer
0.159
961671AG1-007 GEN
Solar/Wind Harmer
0.336
3145453TOT5
Solar/Wind Harmer
0.056
316263AC1-034 GEN
Solar/Wind Harmer
3
3145573BETHELC
Solar/Wind Harmer
0.179
3145603CNETO
Solar/Wind Harmer
0.037
316237AB2-079_GEN
Solar/Wind Helper
0.871
316238AB2-078_GEN
Solar/Wind Helper
0.871
316239AB2-077_GEN
Solar/Wind Helper
0.871
970581AG2-369 GEN
Solar/Wind Harmer
7.556
970917AG2-570 GEN
Solar/Wind Harmer
35.142
3146233WITAKRS
Solar/Wind Harmer
0.388
313527AB2-043 GEN
Solar/Wind Helper
2.145
3145543BTLEBRO
Solar/Wind Harmer
0.199
315773AC2-141 GEN
Solar/Wind Helper
3.009
970085AG2-068 GEN
Solar/Wind Harmer
8.786
970087AG2-069 GEN
Solar/Wind Harmer
13.179
970223AG2-152 GEN
Solar/Wind Harmer
7.548
3145493TOT1
Solar/Wind Harmer
0.093
315785AD2-033 C
Solar/Wind Helper
4.863
270030AE2-140 GEN
Solar/Wind Harmer
9.106
316283AC2-100 C
Solar/Wind Helper
13.194
900033ID_568986
External Queue
3.581075668334961
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.814
WECLTFEXP_WEC->PJM
CLTF
0.882
LAGNLTFEXP_LAGN->PJM
CLTF
9.066
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.634
NYPJM->LTFIMP_NY
CLTF
0.225
TVALTFEXP_TVA->PJM
CLTF
4.608
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
25.485
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.766
CPLELTFEXP_CPLE->PJM
CLTF
11.877
SIGELTFEXP_SIGE->PJM
CLTF
0.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.544
LGEELTFEXP_LGEE->PJM
CLTF
1.613
MECLTFEXP_MEC->PJM
CLTF
4.615

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.01 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:625.53
MW Contribution:
8.97
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.01 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:513.66
MW Contribution:
9.27
Bus #Bus NameTypeMW Contribution
3144303KENBRDG
Solar/Wind Harmer
0.7
946301AF1-294 GEN
Solar/Wind Harmer
3.349
957481AF2-042 GEN
Solar/Wind Harmer
119.705
970685AG2-442 GEN
Solar/Wind Harmer
27.587
970301AG2-198 GEN
Solar/Wind Harmer
13.867
970257AG2-171 GEN
Solar/Wind Harmer
10.499
3147043LAWRENC
50/50
1.588
971629AH1-314 GEN
50/50
Charging
8.256
3147133PAMPLIN
Solar/Wind Harmer
0.729
961791AG1-021 GEN
Solar/Wind Harmer
1.633
3147173SINAI
Solar/Wind Harmer
1.368
3147243WELCO
Solar/Wind Harmer
0.855
3147133PAMPLIN
Solar/Wind Harmer
2.863
270455AD2-022 GEN
Solar/Wind Helper
2.761
970413AG2-270 GEN
50/50
65.188
970909AG2-566 GEN
50/50
8.966
971683AH1-343 GEN
Solar/Wind Harmer
15.809
970683AG2-441 GEN
Solar/Wind Harmer
22.885
962561AG1-105 GEN
Solar/Wind Harmer
20.602
970681AG2-440 GEN
Solar/Wind Harmer
15.189
970099AG2-077 GEN
Solar/Wind Harmer
47.882
970401AG2-262 GEN
Solar/Wind Harmer
2.604
964241AG1-285 GEN
Solar/Wind Harmer
25.358
970535AG2-341 GEN
50/50
13.807
964791AG1-342 GEN
Solar/Wind Harmer
8.522
270457AD2-023 GEN
Solar/Wind Helper
1.553
972205AH1-687 GEN
50/50
5.169
315693AD1-088 GEN
Solar/Wind Harmer
17.585
971775AH1-396 GEN
Solar/Wind Harmer
2.081
971563AH1-280 GEN
Solar/Wind Harmer
1.633
315785AD2-033 C
Solar/Wind Harmer
0
970323AG2-213 GEN
Solar/Wind Harmer
13.998
3146843MT LREL
Solar/Wind Harmer
1.185
3146843MT LREL
Solar/Wind Harmer
1.185
959311AF2-222 GEN
Solar/Wind Harmer
33.838
3147133PAMPLIN
Solar/Wind Harmer
0.912
958211AF2-115 GEN
Solar/Wind Harmer
2.042
NYPJM->LTFIMP_NY
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.398
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.277
G-007ALTFEXP_G-007A->PJM
CMTX
0.163
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.348
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.721
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.78
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.14 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:617.48
MW Contribution:
8.97
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:93.45 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:505.57
MW Contribution:
9.27
Bus #Bus NameTypeMW Contribution
3144303KENBRDG
Solar/Wind Harmer
0.7
946301AF1-294 GEN
Solar/Wind Harmer
3.349
957481AF2-042 GEN
Solar/Wind Harmer
119.705
970685AG2-442 GEN
Solar/Wind Harmer
27.587
970301AG2-198 GEN
Solar/Wind Harmer
13.867
970257AG2-171 GEN
Solar/Wind Harmer
10.499
3147043LAWRENC
50/50
1.588
3147133PAMPLIN
Solar/Wind Harmer
0.729
961791AG1-021 GEN
Solar/Wind Harmer
1.633
970413AG2-270 GEN
50/50
65.188
970909AG2-566 GEN
50/50
8.966
971683AH1-343 GEN
Solar/Wind Harmer
15.809
970683AG2-441 GEN
Solar/Wind Harmer
22.885
962561AG1-105 GEN
Solar/Wind Harmer
20.602
970681AG2-440 GEN
Solar/Wind Harmer
15.189
970099AG2-077 GEN
Solar/Wind Harmer
47.882
970401AG2-262 GEN
Solar/Wind Harmer
2.604
964241AG1-285 GEN
Solar/Wind Harmer
25.358
970535AG2-341 GEN
50/50
13.807
964791AG1-342 GEN
Solar/Wind Harmer
8.522
270457AD2-023 GEN
Solar/Wind Helper
1.553
972205AH1-687 GEN
50/50
5.169
315693AD1-088 GEN
Solar/Wind Harmer
17.585
971775AH1-396 GEN
Solar/Wind Harmer
2.081
971563AH1-280 GEN
Solar/Wind Harmer
1.633
315785AD2-033 C
Solar/Wind Harmer
0
970323AG2-213 GEN
Solar/Wind Harmer
13.998
3147173SINAI
Solar/Wind Harmer
1.368
3147243WELCO
Solar/Wind Harmer
0.855
3147133PAMPLIN
Solar/Wind Harmer
2.863
270455AD2-022 GEN
Solar/Wind Helper
2.761
3146843MT LREL
Solar/Wind Harmer
1.185
3146843MT LREL
Solar/Wind Harmer
1.185
959311AF2-222 GEN
Solar/Wind Harmer
33.838
3147133PAMPLIN
Solar/Wind Harmer
0.912
958211AF2-115 GEN
Solar/Wind Harmer
2.042
G-007ALTFEXP_G-007A->PJM
CMTX
0.163
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.348
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.398
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.277
VFTLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.78
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.721
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.14 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:617.48
MW Contribution:
8.97
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:93.45 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:505.57
MW Contribution:
9.27
Bus #Bus NameTypeMW Contribution
3144303KENBRDG
Solar/Wind Harmer
0.7
946301AF1-294 GEN
Solar/Wind Harmer
3.349
957481AF2-042 GEN
Solar/Wind Harmer
119.705
970685AG2-442 GEN
Solar/Wind Harmer
27.587
970301AG2-198 GEN
Solar/Wind Harmer
13.867
970257AG2-171 GEN
Solar/Wind Harmer
10.499
3147043LAWRENC
50/50
1.588
3147133PAMPLIN
Solar/Wind Harmer
0.729
961791AG1-021 GEN
Solar/Wind Harmer
1.633
970413AG2-270 GEN
50/50
65.188
970909AG2-566 GEN
50/50
8.966
971683AH1-343 GEN
Solar/Wind Harmer
15.809
970683AG2-441 GEN
Solar/Wind Harmer
22.885
962561AG1-105 GEN
Solar/Wind Harmer
20.602
970681AG2-440 GEN
Solar/Wind Harmer
15.189
970099AG2-077 GEN
Solar/Wind Harmer
47.882
970401AG2-262 GEN
Solar/Wind Harmer
2.604
964241AG1-285 GEN
Solar/Wind Harmer
25.358
970535AG2-341 GEN
50/50
13.807
964791AG1-342 GEN
Solar/Wind Harmer
8.522
270457AD2-023 GEN
Solar/Wind Helper
1.553
972205AH1-687 GEN
50/50
5.169
315693AD1-088 GEN
Solar/Wind Harmer
17.585
971775AH1-396 GEN
Solar/Wind Harmer
2.081
971563AH1-280 GEN
Solar/Wind Harmer
1.633
315785AD2-033 C
Solar/Wind Harmer
0
970323AG2-213 GEN
Solar/Wind Harmer
13.998
3147173SINAI
Solar/Wind Harmer
1.368
3147243WELCO
Solar/Wind Harmer
0.855
3147133PAMPLIN
Solar/Wind Harmer
2.863
270455AD2-022 GEN
Solar/Wind Helper
2.761
3146843MT LREL
Solar/Wind Harmer
1.185
3146843MT LREL
Solar/Wind Harmer
1.185
959311AF2-222 GEN
Solar/Wind Harmer
33.838
3147133PAMPLIN
Solar/Wind Harmer
0.912
958211AF2-115 GEN
Solar/Wind Harmer
2.042
G-007ALTFEXP_G-007A->PJM
CMTX
0.163
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.348
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.398
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.277
VFTLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.78
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.721
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.38 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:566.4
MW Contribution:
8.97
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:93.04 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:473.16
MW Contribution:
9.27
Bus #Bus NameTypeMW Contribution
957481AF2-042 GEN
Solar/Wind Harmer
119.705
970685AG2-442 GEN
Solar/Wind Harmer
0.394
3147043LAWRENC
50/50
1.588
971629AH1-314 GEN
50/50
Charging
8.256
970933AG2-581 GEN
Solar/Wind Harmer
35.326
3147173SINAI
Solar/Wind Harmer
1.368
3147243WELCO
Solar/Wind Harmer
0.855
270455AD2-022 GEN
Solar/Wind Helper
2.761
970413AG2-270 GEN
50/50
65.188
970909AG2-566 GEN
50/50
8.966
971683AH1-343 GEN
Solar/Wind Harmer
15.809
970683AG2-441 GEN
Solar/Wind Harmer
22.885
962561AG1-105 GEN
Solar/Wind Harmer
20.602
970681AG2-440 GEN
Solar/Wind Harmer
15.189
970099AG2-077 GEN
Solar/Wind Harmer
47.882
970401AG2-262 GEN
Solar/Wind Harmer
2.604
964241AG1-285 GEN
Solar/Wind Harmer
25.358
970535AG2-341 GEN
50/50
13.807
964791AG1-342 GEN
Solar/Wind Harmer
8.522
270457AD2-023 GEN
Solar/Wind Helper
1.553
972205AH1-687 GEN
50/50
5.169
315693AD1-088 GEN
Solar/Wind Harmer
17.585
971967AH1-528 GEN
Solar/Wind Harmer
70.841
3146843MT LREL
Solar/Wind Harmer
1.185
3146843MT LREL
Solar/Wind Harmer
1.185
959311AF2-222 GEN
Solar/Wind Harmer
33.838
VFTLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.78
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.721
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.398
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.277
G-007ALTFEXP_G-007A->PJM
CMTX
0.163
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.348
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
304070 to 316281 ckt 1
316281 to 304070 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
DVP_P1-2: LN 2193_SRT-A
SingleAC106.22 %179.54B190.71
1.53
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 298_SRT-A-1
SingleAC109.42 %235.94B258.17
3.4
GD2DVP
3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2193_SRT-A
SingleAC106.28 %332.2B353.07
2.48
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC115.7 %830.96B961.39
6.35
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC110.58 %830.96B918.86
5.66
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC115.51 %830.96B959.87
6.35
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC110.39 %830.96B917.31
5.66
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC108.19 %698.42B755.61
13.92
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC108.06 %698.42B754.7
10.43
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC105.34 %687.14B723.8
10.43
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC105.31 %687.14B723.62
13.92
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC117.38 %830.96B975.35
5.93
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC114.63 %830.96B952.49
5.24
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC120.16 %808.4B971.38
5.93
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC117.33 %808.4B948.5
5.24
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC119.55 %808.4B966.48
5.93
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC116.72 %808.4B943.57
5.24
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC108.62 %687.14B746.38
10.43
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC108.49 %687.14B745.46
13.92
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC111.3 %698.42B777.36
10.43
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.09 %698.42B775.9
13.92

Details for 3BREMO-3FORK UNION 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.22 %
Rating:179.54 MVA
Rating Type:B
MVA to Mitigate:190.71
MW Contribution:
1.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
1.009
3146776BUCKING
Solar/Wind Harmer
0.082
3146926FARMVIL
Solar/Wind Harmer
0.119
3146926FARMVIL
Solar/Wind Harmer
0.119
970301AG2-198 GEN
Solar/Wind Harmer
2.36
971377AH1-170 GEN
Solar/Wind Harmer
2.099
3147133PAMPLIN
Solar/Wind Harmer
0.117
970937AG2-583 GEN
Solar/Wind Harmer
5.978
971845AH1-439 GEN
Solar/Wind Harmer
4.212
316336AC2-165 C
Solar/Wind Harmer
3.814
3147133PAMPLIN
Solar/Wind Harmer
0.458
970909AG2-566 GEN
50/50
1.526
3143336POWHATN
Solar/Wind Harmer
0.656
3143336POWHATN
Solar/Wind Harmer
0.558
942461AE2-259 GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.274
972003AH1-546 GEN
Solar/Wind Harmer
4.037
315821AE2-092 GEN
Solar/Wind Helper
6.339
3146776BUCKING
Solar/Wind Harmer
0.101
972205AH1-687 GEN
50/50
5.598
970221AG2-151 GEN
Solar/Wind Harmer
10.497
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.091
958131AF2-107 GEN
Solar/Wind Harmer
1.515
3147133PAMPLIN
Solar/Wind Harmer
0.146
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.057
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.017
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.507
TVALTFEXP_TVA->PJM
CLTF
0.155
LAGNLTFEXP_LAGN->PJM
CLTF
0.298
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.467
CPLELTFEXP_CPLE->PJM
CLTF
0.775
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.048
NYPJM->LTFIMP_NY
CLTF
0.138
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.217

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 298_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.42 %
Rating:235.94 MVA
Rating Type:B
MVA to Mitigate:258.17
MW Contribution:
3.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970685AG2-442 GEN
Solar/Wind Harmer
30.823
946301AF1-294 GEN
Solar/Wind Harmer
9.807
3144303KENBRDG
Solar/Wind Harmer
0.666
970257AG2-171 GEN
Solar/Wind Harmer
9.988
3147043LAWRENC
Solar/Wind Harmer
0.112
3147043LAWRENC
50/50
0.698
3147133PAMPLIN
Solar/Wind Harmer
1.055
961791AG1-021 GEN
Solar/Wind Harmer
4.784
3147133PAMPLIN
Solar/Wind Harmer
4.142
970909AG2-566 GEN
50/50
Charging
3.398
970683AG2-441 GEN
Solar/Wind Harmer
23.044
970681AG2-440 GEN
Solar/Wind Harmer
15.295
962561AG1-105 GEN
Solar/Wind Harmer
4.443
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
964241AG1-285 GEN
Solar/Wind Harmer
14.034
970401AG2-262 GEN
Solar/Wind Harmer
0.477
970535AG2-341 GEN
50/50
4.62
964791AG1-342 GEN
Solar/Wind Harmer
1.562
971563AH1-280 GEN
Solar/Wind Harmer
4.784
971775AH1-396 GEN
Solar/Wind Harmer
1.98
970323AG2-213 GEN
Solar/Wind Harmer
13.318
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
1.319
958211AF2-115 GEN
Solar/Wind Harmer
5.98
959311AF2-222 GEN
Solar/Wind Harmer
29.599
3146843MT LREL
Solar/Wind Harmer
0.216
3146843MT LREL
Solar/Wind Harmer
0.216
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.263
TVALTFEXP_TVA->PJM
CLTF
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
0.033
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.018
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.013
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.557
NYPJM->LTFIMP_NY
CLTF
0.085
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.027
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.047
CPLELTFEXP_CPLE->PJM
CLTF
0.146
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.04

Details for 3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.28 %
Rating:332.2 MVA
Rating Type:B
MVA to Mitigate:353.07
MW Contribution:
2.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
1.644
3146776BUCKING
Solar/Wind Harmer
0.133
946301AF1-294 GEN
Solar/Wind Harmer
1.826
3144303KENBRDG
Solar/Wind Harmer
0.145
3146926FARMVIL
Solar/Wind Harmer
0.193
3146926FARMVIL
Solar/Wind Harmer
0.193
970301AG2-198 GEN
Solar/Wind Harmer
3.832
970685AG2-442 GEN
Solar/Wind Harmer
5.929
971377AH1-170 GEN
Solar/Wind Harmer
3.43
970257AG2-171 GEN
Solar/Wind Harmer
2.169
3147133PAMPLIN
Solar/Wind Harmer
0.19
961791AG1-021 GEN
Solar/Wind Harmer
0.891
970937AG2-583 GEN
Solar/Wind Harmer
9.732
971845AH1-439 GEN
Solar/Wind Harmer
6.86
316336AC2-165 C
Solar/Wind Harmer
6.192
3147133PAMPLIN
Solar/Wind Harmer
0.744
970909AG2-566 GEN
50/50
2.477
970683AG2-441 GEN
Solar/Wind Harmer
4.574
3143336POWHATN
Solar/Wind Harmer
1.063
3143336POWHATN
Solar/Wind Harmer
0.904
970681AG2-440 GEN
Solar/Wind Harmer
3.036
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
3.738
3147623JAMES R
Solar/Wind Harmer
0.447
315821AE2-092 GEN
Solar/Wind Harmer
0
972003AH1-546 GEN
Solar/Wind Harmer
6.581
3146776BUCKING
Solar/Wind Harmer
0.164
972205AH1-687 GEN
50/50
9.128
971563AH1-280 GEN
Solar/Wind Harmer
0.891
971775AH1-396 GEN
Solar/Wind Harmer
0.43
970221AG2-151 GEN
Solar/Wind Harmer
17.151
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.148
958131AF2-107 GEN
Solar/Wind Harmer
2.492
970323AG2-213 GEN
Solar/Wind Harmer
2.892
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.237
958211AF2-115 GEN
Solar/Wind Harmer
1.114
959311AF2-222 GEN
Solar/Wind Harmer
6.245
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.818
CPLELTFEXP_CPLE->PJM
CLTF
1.252
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.049
NYPJM->LTFIMP_NY
CLTF
0.266
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.466
TVALTFEXP_TVA->PJM
CLTF
0.268
LAGNLTFEXP_LAGN->PJM
CLTF
0.513
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.904
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.049
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.698

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.7 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:961.39
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
941591AE2-156 GEN
50/50
5.873
3146926FARMVIL
Solar/Wind Harmer
0.482
3146926FARMVIL
Solar/Wind Harmer
0.482
970301AG2-198 GEN
Solar/Wind Harmer
9.825
970685AG2-442 GEN
Solar/Wind Harmer
15.222
3143226MDLTHAN
Solar/Wind Harmer
0.317
966001AG1-469 GEN
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
1.096
957481AF2-042 GEN
Solar/Wind Harmer
8.44
3146776BUCKING
Solar/Wind Harmer
4.029
3146776BUCKING
Solar/Wind Harmer
0.326
946301AF1-294 GEN
Solar/Wind Harmer
4.669
3144303KENBRDG
Solar/Wind Harmer
0.377
970535AG2-341 GEN
50/50
5.498
972187AH1-678 GEN
50/50
2.536
315779AE2-040
50/50
1.06
3146776BUCKING
Solar/Wind Harmer
0.403
970257AG2-171 GEN
Solar/Wind Harmer
5.65
971377AH1-170 GEN
Solar/Wind Harmer
1.331
963041AG1-153 GEN
50/50
5.594
316303AF2-085
50/50
2.183
3147043LAWRENC
50/50
0.978
3147133PAMPLIN
Solar/Wind Harmer
0.482
961791AG1-021 GEN
Solar/Wind Harmer
2.278
316192AB2-158 GEN
Solar/Wind Helper
1.359
970937AG2-583 GEN
Solar/Wind Harmer
23.961
971845AH1-439 GEN
Solar/Wind Harmer
16.828
316336AC2-165 C
Solar/Wind Harmer
15.777
3147133PAMPLIN
Solar/Wind Harmer
1.893
316499AE2-029_GEN
Solar/Wind Helper
0.952
970909AG2-566 GEN
50/50
6.352
970413AG2-270 GEN
50/50
15.273
970683AG2-441 GEN
Solar/Wind Harmer
11.789
3143336POWHATN
Solar/Wind Harmer
2.766
3143336POWHATN
Solar/Wind Harmer
2.351
970681AG2-440 GEN
Solar/Wind Harmer
7.824
962561AG1-105 GEN
Solar/Wind Harmer
5.385
972185AH1-677 GEN
50/50
4.974
944641AF1-129 GEN
50/50
16.687
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
9.936
970099AG2-077 GEN
Solar/Wind Harmer
3.376
972003AH1-546 GEN
Solar/Wind Harmer
15.936
3147623JAMES R
Solar/Wind Harmer
0.174
970119AG2-088 GEN
50/50
16.372
3146776BUCKING
Solar/Wind Harmer
0.363
970221AG2-151 GEN
Solar/Wind Harmer
6.657
971223AH1-071 GEN
Solar/Wind Harmer
1.266
972205AH1-687 GEN
50/50
22.076
970533AG2-339 GEN
50/50
6.242
971563AH1-280 GEN
Solar/Wind Harmer
2.278
971775AH1-396 GEN
Solar/Wind Harmer
1.12
315693AD1-088 GEN
Solar/Wind Harmer
5.728
970323AG2-213 GEN
Solar/Wind Harmer
7.534
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.603
958211AF2-115 GEN
Solar/Wind Harmer
2.847
959311AF2-222 GEN
Solar/Wind Harmer
16.214
NYPJM->LTFIMP_NY
CLTF
0.692
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.095
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.518
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.193
CPLELTFEXP_CPLE->PJM
CLTF
3.886
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.269
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.957
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.42
TVALTFEXP_TVA->PJM
CLTF
0.734
LAGNLTFEXP_LAGN->PJM
CLTF
1.421

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.58 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:918.86
MW Contribution:
5.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.442
3146926FARMVIL
Solar/Wind Harmer
0.442
970301AG2-198 GEN
Solar/Wind Harmer
8.757
970685AG2-442 GEN
Solar/Wind Harmer
13.551
315616AA1-038_C
Solar/Wind Helper
1.717
966001AG1-469 GEN
Solar/Wind Helper
0.328
957481AF2-042 GEN
Solar/Wind Harmer
5.432
3146776BUCKING
Solar/Wind Harmer
3.765
3146776BUCKING
Solar/Wind Harmer
0.305
946301AF1-294 GEN
Solar/Wind Harmer
4.175
3144303KENBRDG
Solar/Wind Harmer
0.33
315760AF1-028 GEN
50/50
Charging
15.654
970117AG2-086 GEN
50/50
Charging
1.264
970257AG2-171 GEN
Solar/Wind Harmer
4.955
971377AH1-170 GEN
Solar/Wind Harmer
1.09
316303AF2-085
50/50
1.486
3147043LAWRENC
50/50
0.752
3147133PAMPLIN
Solar/Wind Harmer
0.433
961791AG1-021 GEN
Solar/Wind Harmer
2.037
316192AB2-158 GEN
Solar/Wind Helper
1.365
970937AG2-583 GEN
Solar/Wind Harmer
22.254
971845AH1-439 GEN
Solar/Wind Harmer
15.705
316336AC2-165 C
Solar/Wind Harmer
14.108
3147133PAMPLIN
Solar/Wind Harmer
1.701
316499AE2-029_GEN
Solar/Wind Helper
1.241
970909AG2-566 GEN
50/50
5.662
970413AG2-270 GEN
50/50
11.968
970683AG2-441 GEN
Solar/Wind Harmer
10.452
3143336POWHATN
Solar/Wind Harmer
2.417
3143336POWHATN
Solar/Wind Harmer
2.055
970681AG2-440 GEN
Solar/Wind Harmer
6.937
962561AG1-105 GEN
Solar/Wind Harmer
4.526
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
8.531
970401AG2-262 GEN
Solar/Wind Harmer
0.533
970099AG2-077 GEN
Solar/Wind Harmer
2.173
972003AH1-546 GEN
Solar/Wind Harmer
15.074
3147623JAMES R
Solar/Wind Harmer
0.142
970535AG2-341 GEN
50/50
4.553
3146776BUCKING
Solar/Wind Harmer
0.376
964791AG1-342 GEN
Solar/Wind Harmer
1.745
970119AG2-088 GEN
50/50
11.148
3146776BUCKING
Solar/Wind Harmer
0.339
972205AH1-687 GEN
50/50
20.909
971563AH1-280 GEN
Solar/Wind Harmer
2.037
971775AH1-396 GEN
Solar/Wind Harmer
0.982
315693AD1-088 GEN
Solar/Wind Harmer
4.641
970221AG2-151 GEN
Solar/Wind Harmer
5.451
970323AG2-213 GEN
Solar/Wind Harmer
6.607
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.542
958211AF2-115 GEN
Solar/Wind Harmer
2.546
959311AF2-222 GEN
Solar/Wind Harmer
14.268
3146843MT LREL
Solar/Wind Harmer
0.242
3146843MT LREL
Solar/Wind Harmer
0.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.449
NYPJM->LTFIMP_NY
CLTF
0.698
TVALTFEXP_TVA->PJM
CLTF
1.131
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
9.964
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.78
WECLTFEXP_WEC->PJM
CLTF
0.139
LAGNLTFEXP_LAGN->PJM
CLTF
2.161
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.719
LGEELTFEXP_LGEE->PJM
CLTF
0.289
MECLTFEXP_MEC->PJM
CLTF
0.859
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.939
CPLELTFEXP_CPLE->PJM
CLTF
3.189
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.51 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:959.87
MW Contribution:
6.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
941591AE2-156 GEN
50/50
5.873
3146926FARMVIL
Solar/Wind Harmer
0.482
3146926FARMVIL
Solar/Wind Harmer
0.482
970301AG2-198 GEN
Solar/Wind Harmer
9.825
970685AG2-442 GEN
Solar/Wind Harmer
15.222
3143226MDLTHAN
Solar/Wind Harmer
0.317
966001AG1-469 GEN
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
1.096
957481AF2-042 GEN
Solar/Wind Harmer
8.44
3146776BUCKING
Solar/Wind Harmer
4.029
3146776BUCKING
Solar/Wind Harmer
0.326
946301AF1-294 GEN
Solar/Wind Harmer
4.669
3144303KENBRDG
Solar/Wind Harmer
0.377
970257AG2-171 GEN
Solar/Wind Harmer
5.65
971377AH1-170 GEN
Solar/Wind Harmer
1.331
963041AG1-153 GEN
50/50
5.594
316303AF2-085
50/50
2.183
3147043LAWRENC
50/50
0.978
3147133PAMPLIN
Solar/Wind Harmer
0.482
961791AG1-021 GEN
Solar/Wind Harmer
2.278
316192AB2-158 GEN
Solar/Wind Helper
1.359
970937AG2-583 GEN
Solar/Wind Harmer
23.961
971845AH1-439 GEN
Solar/Wind Harmer
16.828
316336AC2-165 C
Solar/Wind Harmer
15.777
3147133PAMPLIN
Solar/Wind Harmer
1.893
316499AE2-029_GEN
Solar/Wind Helper
0.952
970909AG2-566 GEN
50/50
6.352
970413AG2-270 GEN
50/50
15.273
970683AG2-441 GEN
Solar/Wind Harmer
11.789
3143336POWHATN
Solar/Wind Harmer
2.766
3143336POWHATN
Solar/Wind Harmer
2.351
970681AG2-440 GEN
Solar/Wind Harmer
7.824
962561AG1-105 GEN
Solar/Wind Harmer
5.385
972185AH1-677 GEN
50/50
4.974
944641AF1-129 GEN
50/50
16.687
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
9.936
970099AG2-077 GEN
Solar/Wind Harmer
3.376
972003AH1-546 GEN
Solar/Wind Harmer
15.936
3147623JAMES R
Solar/Wind Harmer
0.174
970535AG2-341 GEN
50/50
5.498
972187AH1-678 GEN
50/50
2.536
315779AE2-040
50/50
1.06
3146776BUCKING
Solar/Wind Harmer
0.403
970119AG2-088 GEN
50/50
16.372
3146776BUCKING
Solar/Wind Harmer
0.363
970221AG2-151 GEN
Solar/Wind Harmer
6.657
971223AH1-071 GEN
Solar/Wind Harmer
1.266
972205AH1-687 GEN
50/50
22.076
970533AG2-339 GEN
50/50
6.242
971563AH1-280 GEN
Solar/Wind Harmer
2.278
971775AH1-396 GEN
Solar/Wind Harmer
1.12
315693AD1-088 GEN
Solar/Wind Harmer
5.728
970323AG2-213 GEN
Solar/Wind Harmer
7.534
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.603
958211AF2-115 GEN
Solar/Wind Harmer
2.847
959311AF2-222 GEN
Solar/Wind Harmer
16.214
NYPJM->LTFIMP_NY
CLTF
0.692
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.095
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.518
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.193
CPLELTFEXP_CPLE->PJM
CLTF
3.886
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.269
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.957
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.42
TVALTFEXP_TVA->PJM
CLTF
0.734
LAGNLTFEXP_LAGN->PJM
CLTF
1.421

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.39 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:917.31
MW Contribution:
5.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.442
3146926FARMVIL
Solar/Wind Harmer
0.442
970301AG2-198 GEN
Solar/Wind Harmer
8.757
970685AG2-442 GEN
Solar/Wind Harmer
13.551
315616AA1-038_C
Solar/Wind Helper
1.717
966001AG1-469 GEN
Solar/Wind Helper
0.328
957481AF2-042 GEN
Solar/Wind Harmer
5.432
3146776BUCKING
Solar/Wind Harmer
3.765
3146776BUCKING
Solar/Wind Harmer
0.305
946301AF1-294 GEN
Solar/Wind Harmer
4.175
3144303KENBRDG
Solar/Wind Harmer
0.33
315760AF1-028 GEN
50/50
Charging
15.654
970117AG2-086 GEN
50/50
Charging
1.264
970257AG2-171 GEN
Solar/Wind Harmer
4.955
971377AH1-170 GEN
Solar/Wind Harmer
1.09
316303AF2-085
50/50
1.486
3147043LAWRENC
50/50
0.752
3147133PAMPLIN
Solar/Wind Harmer
0.433
961791AG1-021 GEN
Solar/Wind Harmer
2.037
316192AB2-158 GEN
Solar/Wind Helper
1.365
970937AG2-583 GEN
Solar/Wind Harmer
22.254
971845AH1-439 GEN
Solar/Wind Harmer
15.705
316336AC2-165 C
Solar/Wind Harmer
14.108
3147133PAMPLIN
Solar/Wind Harmer
1.701
316499AE2-029_GEN
Solar/Wind Helper
1.241
970909AG2-566 GEN
50/50
5.662
970413AG2-270 GEN
50/50
11.968
970683AG2-441 GEN
Solar/Wind Harmer
10.452
3143336POWHATN
Solar/Wind Harmer
2.417
3143336POWHATN
Solar/Wind Harmer
2.055
970681AG2-440 GEN
Solar/Wind Harmer
6.937
962561AG1-105 GEN
Solar/Wind Harmer
4.526
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
8.531
970401AG2-262 GEN
Solar/Wind Harmer
0.533
970099AG2-077 GEN
Solar/Wind Harmer
2.173
972003AH1-546 GEN
Solar/Wind Harmer
15.074
3147623JAMES R
Solar/Wind Harmer
0.142
970535AG2-341 GEN
50/50
4.553
3146776BUCKING
Solar/Wind Harmer
0.376
964791AG1-342 GEN
Solar/Wind Harmer
1.745
972205AH1-687 GEN
50/50
20.909
971563AH1-280 GEN
Solar/Wind Harmer
2.037
971775AH1-396 GEN
Solar/Wind Harmer
0.982
315693AD1-088 GEN
Solar/Wind Harmer
4.641
970119AG2-088 GEN
50/50
11.148
3146776BUCKING
Solar/Wind Harmer
0.339
970221AG2-151 GEN
Solar/Wind Harmer
5.451
970323AG2-213 GEN
Solar/Wind Harmer
6.607
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.542
958211AF2-115 GEN
Solar/Wind Harmer
2.546
959311AF2-222 GEN
Solar/Wind Harmer
14.268
3146843MT LREL
Solar/Wind Harmer
0.242
3146843MT LREL
Solar/Wind Harmer
0.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.939
CPLELTFEXP_CPLE->PJM
CLTF
3.189
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.719
LGEELTFEXP_LGEE->PJM
CLTF
0.289
MECLTFEXP_MEC->PJM
CLTF
0.859
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.449
NYPJM->LTFIMP_NY
CLTF
0.698
TVALTFEXP_TVA->PJM
CLTF
1.131
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
9.964
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.78
WECLTFEXP_WEC->PJM
CLTF
0.139
LAGNLTFEXP_LAGN->PJM
CLTF
2.161

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.19 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:755.61
MW Contribution:
13.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.524
3146776BUCKING
Solar/Wind Harmer
7.851
3146776BUCKING
Solar/Wind Harmer
0.636
946301AF1-294 GEN
Solar/Wind Harmer
9.591
3144303KENBRDG
Solar/Wind Harmer
0.779
970685AG2-442 GEN
Solar/Wind Harmer
31.319
957481AF2-042 GEN
Solar/Wind Harmer
87.558
316405AF2-144 C
50/50
Charging
1.03
970257AG2-171 GEN
Solar/Wind Harmer
11.691
3147043LAWRENC
50/50
1.472
971629AH1-314 GEN
50/50
5.91
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.679
971845AH1-439 GEN
Solar/Wind Harmer
32.89
3147133PAMPLIN
Solar/Wind Harmer
3.88
970909AG2-566 GEN
50/50
13.916
970413AG2-270 GEN
50/50
42.63
970683AG2-441 GEN
Solar/Wind Harmer
24.293
316258AE1-075 C
Solar/Wind Helper
0.455
970681AG2-440 GEN
Solar/Wind Harmer
16.124
962561AG1-105 GEN
Solar/Wind Harmer
7.071
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
35.023
964241AG1-285 GEN
Solar/Wind Harmer
20.715
315821AE2-092 GEN
Solar/Wind Helper
4.587
970535AG2-341 GEN
50/50
11.523
3146776BUCKING
Solar/Wind Harmer
0.785
971563AH1-280 GEN
Solar/Wind Harmer
4.679
971775AH1-396 GEN
Solar/Wind Harmer
2.317
315693AD1-088 GEN
Solar/Wind Harmer
15.284
3146776BUCKING
Solar/Wind Harmer
0.707
270494AE1-108_GEN
Solar/Wind Helper
5.532
316313AB2-026
Solar/Wind Helper
0.506
970323AG2-213 GEN
Solar/Wind Harmer
15.588
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.848
959311AF2-222 GEN
Solar/Wind Harmer
33.506
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.588
CPLELTFEXP_CPLE->PJM
CLTF
4.408
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.51
LGEELTFEXP_LGEE->PJM
CLTF
0.458
MECLTFEXP_MEC->PJM
CLTF
1.369
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.645
NYPJM->LTFIMP_NY
CLTF
0.539
TVALTFEXP_TVA->PJM
CLTF
1.544
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.222
WECLTFEXP_WEC->PJM
CLTF
0.245
LAGNLTFEXP_LAGN->PJM
CLTF
3.015

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.06 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:754.7
MW Contribution:
10.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
7.104
3146776BUCKING
Solar/Wind Harmer
0.575
946301AF1-294 GEN
Solar/Wind Harmer
7.634
3144303KENBRDG
Solar/Wind Harmer
0.594
3146926FARMVIL
Solar/Wind Harmer
0.827
3146926FARMVIL
Solar/Wind Harmer
0.827
970301AG2-198 GEN
Solar/Wind Harmer
16.132
970685AG2-442 GEN
Solar/Wind Harmer
24.684
957481AF2-042 GEN
Solar/Wind Harmer
33.356
316405AF2-144 C
50/50
Charging
1.194
970257AG2-171 GEN
Solar/Wind Harmer
8.908
963041AG1-153 GEN
50/50
5.464
3147043LAWRENC
50/50
1.212
3147133PAMPLIN
Solar/Wind Harmer
0.796
961791AG1-021 GEN
Solar/Wind Harmer
3.724
971845AH1-439 GEN
Solar/Wind Harmer
29.619
3147133PAMPLIN
Solar/Wind Harmer
3.124
970909AG2-566 GEN
50/50
10.43
970413AG2-270 GEN
50/50
20.271
970683AG2-441 GEN
Solar/Wind Harmer
18.972
316258AE1-075 C
Solar/Wind Helper
0.527
970681AG2-440 GEN
Solar/Wind Harmer
12.592
962561AG1-105 GEN
Solar/Wind Harmer
7.634
972185AH1-677 GEN
50/50
4.762
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
15.043
970401AG2-262 GEN
Solar/Wind Harmer
0.893
970099AG2-077 GEN
Solar/Wind Harmer
13.343
315821AE2-092 GEN
Solar/Wind Helper
5.466
970535AG2-341 GEN
50/50
7.78
972187AH1-678 GEN
50/50
2.477
315779AE2-040
50/50
0.832
3146776BUCKING
Solar/Wind Harmer
0.71
964791AG1-342 GEN
Solar/Wind Harmer
2.924
970533AG2-339 GEN
50/50
5.696
971563AH1-280 GEN
Solar/Wind Harmer
3.724
971775AH1-396 GEN
Solar/Wind Harmer
1.765
315693AD1-088 GEN
Solar/Wind Harmer
8.111
3146776BUCKING
Solar/Wind Harmer
0.639
270494AE1-108_GEN
Solar/Wind Helper
6.779
316313AB2-026
Solar/Wind Helper
0.586
970323AG2-213 GEN
Solar/Wind Harmer
11.877
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.995
958211AF2-115 GEN
Solar/Wind Harmer
4.655
959311AF2-222 GEN
Solar/Wind Harmer
25.726
3146843MT LREL
Solar/Wind Harmer
0.405
3146843MT LREL
Solar/Wind Harmer
0.405
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.025
WECLTFEXP_WEC->PJM
CLTF
0.125
LAGNLTFEXP_LAGN->PJM
CLTF
2.401
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.152
NYPJM->LTFIMP_NY
CLTF
0.591
TVALTFEXP_TVA->PJM
CLTF
1.227
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.981
CPLELTFEXP_CPLE->PJM
CLTF
4.418
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.321
LGEELTFEXP_LGEE->PJM
CLTF
0.232
MECLTFEXP_MEC->PJM
CLTF
0.841

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.34 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:723.8
MW Contribution:
10.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
946301AF1-294 GEN
Solar/Wind Harmer
7.637
3144303KENBRDG
Solar/Wind Harmer
0.594
3146926FARMVIL
Solar/Wind Harmer
0.827
3146926FARMVIL
Solar/Wind Harmer
0.827
970301AG2-198 GEN
Solar/Wind Harmer
16.138
970685AG2-442 GEN
Solar/Wind Harmer
24.695
957481AF2-042 GEN
Solar/Wind Harmer
38.51
316405AF2-144 C
50/50
Charging
1.192
970257AG2-171 GEN
Solar/Wind Harmer
8.912
963041AG1-153 GEN
50/50
5.474
3147043LAWRENC
50/50
1.213
3147133PAMPLIN
Solar/Wind Harmer
0.796
961791AG1-021 GEN
Solar/Wind Harmer
3.725
3147133PAMPLIN
Solar/Wind Harmer
3.125
970909AG2-566 GEN
50/50
10.434
970413AG2-270 GEN
50/50
20.29
970683AG2-441 GEN
Solar/Wind Harmer
18.98
316258AE1-075 C
Solar/Wind Helper
0.527
970681AG2-440 GEN
Solar/Wind Harmer
12.598
962561AG1-105 GEN
Solar/Wind Harmer
7.641
316322AB2-045
Solar/Wind Helper
2.071
972185AH1-677 GEN
50/50
4.77
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
15.053
970401AG2-262 GEN
Solar/Wind Harmer
0.894
970099AG2-077 GEN
Solar/Wind Harmer
15.404
970535AG2-341 GEN
50/50
7.786
972187AH1-678 GEN
50/50
2.481
315779AE2-040
50/50
0.834
964791AG1-342 GEN
Solar/Wind Harmer
2.926
315821AE2-092 GEN
Solar/Wind Helper
5.461
971065AG2-659 GEN
Solar/Wind Harmer
1.175
970533AG2-339 GEN
50/50
5.707
971563AH1-280 GEN
Solar/Wind Harmer
3.725
971775AH1-396 GEN
Solar/Wind Harmer
1.766
315693AD1-088 GEN
Solar/Wind Harmer
8.117
270494AE1-108_GEN
Solar/Wind Helper
6.773
316313AB2-026
Solar/Wind Helper
0.585
970323AG2-213 GEN
Solar/Wind Harmer
11.883
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.995
958211AF2-115 GEN
Solar/Wind Harmer
4.657
959311AF2-222 GEN
Solar/Wind Harmer
25.739
3146843MT LREL
Solar/Wind Harmer
0.406
3146843MT LREL
Solar/Wind Harmer
0.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.315
NYPJM->LTFIMP_NY
CLTF
0.584
TVALTFEXP_TVA->PJM
CLTF
1.239
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.068
WECLTFEXP_WEC->PJM
CLTF
0.129
LAGNLTFEXP_LAGN->PJM
CLTF
2.423
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.472
LGEELTFEXP_LGEE->PJM
CLTF
0.24
MECLTFEXP_MEC->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.015
CPLELTFEXP_CPLE->PJM
CLTF
4.43
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:723.62
MW Contribution:
13.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
946301AF1-294 GEN
Solar/Wind Harmer
9.595
3144303KENBRDG
Solar/Wind Harmer
0.78
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.53
970685AG2-442 GEN
Solar/Wind Harmer
31.33
957481AF2-042 GEN
Solar/Wind Harmer
87.595
316405AF2-144 C
50/50
Charging
1.029
970257AG2-171 GEN
Solar/Wind Harmer
11.696
3147043LAWRENC
50/50
1.473
971629AH1-314 GEN
50/50
5.923
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.68
3147133PAMPLIN
Solar/Wind Harmer
3.882
3147173SINAI
Solar/Wind Harmer
0.56
3147243WELCO
Solar/Wind Harmer
0.35
970909AG2-566 GEN
50/50
13.92
970413AG2-270 GEN
50/50
42.65
970683AG2-441 GEN
Solar/Wind Harmer
24.301
316258AE1-075 C
Solar/Wind Helper
0.455
970681AG2-440 GEN
Solar/Wind Harmer
16.129
962561AG1-105 GEN
Solar/Wind Harmer
11.811
316322AB2-045
Solar/Wind Helper
1.727
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
35.038
964241AG1-285 GEN
Solar/Wind Harmer
20.725
970401AG2-262 GEN
Solar/Wind Harmer
1.407
970535AG2-341 GEN
50/50
11.53
964791AG1-342 GEN
Solar/Wind Harmer
4.604
315821AE2-092 GEN
Solar/Wind Helper
4.582
971065AG2-659 GEN
Solar/Wind Harmer
0.906
971563AH1-280 GEN
Solar/Wind Harmer
4.68
971775AH1-396 GEN
Solar/Wind Harmer
2.318
315693AD1-088 GEN
Solar/Wind Harmer
15.29
270494AE1-108_GEN
Solar/Wind Helper
5.526
316313AB2-026
Solar/Wind Helper
0.505
970323AG2-213 GEN
Solar/Wind Harmer
15.594
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.85
959311AF2-222 GEN
Solar/Wind Harmer
33.519
3146843MT LREL
Solar/Wind Harmer
0.639
3146843MT LREL
Solar/Wind Harmer
0.639
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.622
CPLELTFEXP_CPLE->PJM
CLTF
4.42
SIGELTFEXP_SIGE->PJM
CLTF
0.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.661
LGEELTFEXP_LGEE->PJM
CLTF
0.466
MECLTFEXP_MEC->PJM
CLTF
1.387
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.809
NYPJM->LTFIMP_NY
CLTF
0.532
TVALTFEXP_TVA->PJM
CLTF
1.555
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.264
WECLTFEXP_WEC->PJM
CLTF
0.249
LAGNLTFEXP_LAGN->PJM
CLTF
3.038

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.38 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:975.35
MW Contribution:
5.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
941591AE2-156 GEN
50/50
5.394
3146926FARMVIL
Solar/Wind Harmer
0.449
3146926FARMVIL
Solar/Wind Harmer
0.449
970301AG2-198 GEN
Solar/Wind Harmer
9.17
970685AG2-442 GEN
Solar/Wind Harmer
14.242
3143226MDLTHAN
Solar/Wind Harmer
0.292
966001AG1-469 GEN
Solar/Wind Helper
0.335
315616AA1-038_C
Solar/Wind Helper
1.054
957481AF2-042 GEN
Solar/Wind Harmer
6.021
3146776BUCKING
Solar/Wind Harmer
3.755
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.367
3144303KENBRDG
Solar/Wind Harmer
0.353
970535AG2-341 GEN
50/50
5.173
972187AH1-678 GEN
50/50
2.361
315779AE2-040
50/50
0.981
3146776BUCKING
Solar/Wind Harmer
0.376
315760AF1-028 GEN
50/50
Charging
11.367
971377AH1-170 GEN
Solar/Wind Harmer
4.159
970257AG2-171 GEN
Solar/Wind Harmer
5.295
963041AG1-153 GEN
50/50
5.208
316303AF2-085
50/50
2.015
3147043LAWRENC
50/50
0.917
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.13
316192AB2-158 GEN
Solar/Wind Helper
1.485
970937AG2-583 GEN
Solar/Wind Harmer
22.308
971845AH1-439 GEN
Solar/Wind Harmer
15.686
316336AC2-165 C
Solar/Wind Harmer
14.671
3147133PAMPLIN
Solar/Wind Harmer
1.769
316499AE2-029_GEN
Solar/Wind Helper
0.93
970909AG2-566 GEN
50/50
5.929
970413AG2-270 GEN
50/50
14.332
970683AG2-441 GEN
Solar/Wind Harmer
11.035
3143336POWHATN
Solar/Wind Harmer
2.57
3143336POWHATN
Solar/Wind Harmer
2.185
970681AG2-440 GEN
Solar/Wind Harmer
7.324
962561AG1-105 GEN
Solar/Wind Harmer
5.111
972185AH1-677 GEN
50/50
4.626
944641AF1-129 GEN
50/50
25.925
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
9.33
970099AG2-077 GEN
Solar/Wind Harmer
2.409
972003AH1-546 GEN
Solar/Wind Harmer
14.847
3147623JAMES R
Solar/Wind Harmer
0.542
315821AE2-092 GEN
Solar/Wind Harmer
0
970119AG2-088 GEN
50/50
15.11
970221AG2-151 GEN
Solar/Wind Harmer
20.797
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
971223AH1-071 GEN
Solar/Wind Harmer
1.169
972205AH1-687 GEN
50/50
20.567
970533AG2-339 GEN
50/50
5.794
971563AH1-280 GEN
Solar/Wind Harmer
2.13
971775AH1-396 GEN
Solar/Wind Harmer
1.049
315693AD1-088 GEN
Solar/Wind Harmer
5.357
970323AG2-213 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
3.053
3147133PAMPLIN
Solar/Wind Harmer
0.563
958211AF2-115 GEN
Solar/Wind Harmer
2.663
959311AF2-222 GEN
Solar/Wind Harmer
15.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.388
TVALTFEXP_TVA->PJM
CLTF
0.837
LAGNLTFEXP_LAGN->PJM
CLTF
1.615
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.414
LGEELTFEXP_LGEE->PJM
CLTF
0.006
MECLTFEXP_MEC->PJM
CLTF
0.263
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.464
NYPJM->LTFIMP_NY
CLTF
0.728
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.01
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.599
CPLELTFEXP_CPLE->PJM
CLTF
3.766
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.005

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.63 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:952.49
MW Contribution:
5.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970301AG2-198 GEN
Solar/Wind Harmer
8.11
970685AG2-442 GEN
Solar/Wind Harmer
12.594
966001AG1-469 GEN
Solar/Wind Helper
0.359
315616AA1-038_C
Solar/Wind Helper
1.731
957481AF2-042 GEN
Solar/Wind Harmer
3.595
3146776BUCKING
Solar/Wind Harmer
3.488
3146776BUCKING
Solar/Wind Harmer
0.282
946301AF1-294 GEN
Solar/Wind Harmer
3.878
3144303KENBRDG
Solar/Wind Harmer
0.308
315760AF1-028 GEN
50/50
Charging
15.733
970117AG2-086 GEN
50/50
Charging
1.277
971377AH1-170 GEN
Solar/Wind Harmer
3.912
970257AG2-171 GEN
Solar/Wind Harmer
4.613
316303AF2-085
50/50
1.323
3147043LAWRENC
50/50
0.696
3147133PAMPLIN
Solar/Wind Harmer
0.402
961791AG1-021 GEN
Solar/Wind Harmer
1.892
316192AB2-158 GEN
Solar/Wind Helper
1.526
970937AG2-583 GEN
Solar/Wind Harmer
20.574
971845AH1-439 GEN
Solar/Wind Harmer
14.549
316336AC2-165 C
Solar/Wind Harmer
12.991
3147133PAMPLIN
Solar/Wind Harmer
1.579
316499AE2-029_GEN
Solar/Wind Helper
1.245
970909AG2-566 GEN
50/50
5.243
970413AG2-270 GEN
50/50
11.112
970683AG2-441 GEN
Solar/Wind Harmer
9.719
3143336POWHATN
Solar/Wind Harmer
2.22
3143336POWHATN
Solar/Wind Harmer
1.887
970681AG2-440 GEN
Solar/Wind Harmer
6.45
962561AG1-105 GEN
Solar/Wind Harmer
4.288
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
7.96
970401AG2-262 GEN
Solar/Wind Harmer
0.507
970099AG2-077 GEN
Solar/Wind Harmer
1.438
972003AH1-546 GEN
Solar/Wind Harmer
13.964
3147623JAMES R
Solar/Wind Harmer
0.51
315821AE2-092 GEN
Solar/Wind Harmer
0
970535AG2-341 GEN
50/50
4.255
3146776BUCKING
Solar/Wind Harmer
0.349
964791AG1-342 GEN
Solar/Wind Harmer
1.658
970119AG2-088 GEN
50/50
9.919
970221AG2-151 GEN
Solar/Wind Harmer
19.558
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
19.37
971563AH1-280 GEN
Solar/Wind Harmer
1.892
971775AH1-396 GEN
Solar/Wind Harmer
0.914
315693AD1-088 GEN
Solar/Wind Harmer
4.291
958131AF2-107 GEN
Solar/Wind Harmer
3.307
970323AG2-213 GEN
Solar/Wind Harmer
6.151
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
2.365
959311AF2-222 GEN
Solar/Wind Harmer
13.277
3146843MT LREL
Solar/Wind Harmer
0.23
3146843MT LREL
Solar/Wind Harmer
0.23
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.207
CPLELTFEXP_CPLE->PJM
CLTF
3.164
SIGELTFEXP_SIGE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.318
LGEELTFEXP_LGEE->PJM
CLTF
0.434
MECLTFEXP_MEC->PJM
CLTF
1.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.108
NYPJM->LTFIMP_NY
CLTF
0.768
TVALTFEXP_TVA->PJM
CLTF
1.33
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.536
WECLTFEXP_WEC->PJM
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
2.539

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.16 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:971.38
MW Contribution:
5.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
941591AE2-156 GEN
50/50
5.394
3146926FARMVIL
Solar/Wind Harmer
0.449
3146926FARMVIL
Solar/Wind Harmer
0.449
970301AG2-198 GEN
Solar/Wind Harmer
9.17
970685AG2-442 GEN
Solar/Wind Harmer
14.242
3143226MDLTHAN
Solar/Wind Harmer
0.292
966001AG1-469 GEN
Solar/Wind Helper
0.335
315616AA1-038_C
Solar/Wind Helper
1.054
957481AF2-042 GEN
Solar/Wind Harmer
6.021
3146776BUCKING
Solar/Wind Harmer
3.755
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.367
3144303KENBRDG
Solar/Wind Harmer
0.353
970535AG2-341 GEN
50/50
5.173
972187AH1-678 GEN
50/50
2.361
315779AE2-040
50/50
0.981
3146776BUCKING
Solar/Wind Harmer
0.376
315760AF1-028 GEN
50/50
Charging
11.367
971377AH1-170 GEN
Solar/Wind Harmer
4.159
970257AG2-171 GEN
Solar/Wind Harmer
5.295
972205AH1-687 GEN
50/50
20.567
970533AG2-339 GEN
50/50
5.794
971563AH1-280 GEN
Solar/Wind Harmer
2.13
971775AH1-396 GEN
Solar/Wind Harmer
1.049
963041AG1-153 GEN
50/50
5.208
316303AF2-085
50/50
2.015
3147043LAWRENC
50/50
0.917
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.13
316192AB2-158 GEN
Solar/Wind Helper
1.485
970937AG2-583 GEN
Solar/Wind Harmer
22.308
971845AH1-439 GEN
Solar/Wind Harmer
15.686
316336AC2-165 C
Solar/Wind Harmer
14.671
3147133PAMPLIN
Solar/Wind Harmer
1.769
316499AE2-029_GEN
Solar/Wind Helper
0.93
970909AG2-566 GEN
50/50
5.929
970413AG2-270 GEN
50/50
14.332
970683AG2-441 GEN
Solar/Wind Harmer
11.035
3143336POWHATN
Solar/Wind Harmer
2.57
3143336POWHATN
Solar/Wind Harmer
2.185
970681AG2-440 GEN
Solar/Wind Harmer
7.324
962561AG1-105 GEN
Solar/Wind Harmer
5.111
972185AH1-677 GEN
50/50
4.626
944641AF1-129 GEN
50/50
25.925
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
9.33
970099AG2-077 GEN
Solar/Wind Harmer
2.409
972003AH1-546 GEN
Solar/Wind Harmer
14.847
3147623JAMES R
Solar/Wind Harmer
0.542
315821AE2-092 GEN
Solar/Wind Harmer
0
970119AG2-088 GEN
50/50
15.11
970221AG2-151 GEN
Solar/Wind Harmer
20.797
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
971223AH1-071 GEN
Solar/Wind Harmer
1.169
315693AD1-088 GEN
Solar/Wind Harmer
5.357
970323AG2-213 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
3.053
3147133PAMPLIN
Solar/Wind Harmer
0.563
958211AF2-115 GEN
Solar/Wind Harmer
2.663
959311AF2-222 GEN
Solar/Wind Harmer
15.189
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.414
LGEELTFEXP_LGEE->PJM
CLTF
0.006
MECLTFEXP_MEC->PJM
CLTF
0.263
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.464
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.388
TVALTFEXP_TVA->PJM
CLTF
0.837
LAGNLTFEXP_LAGN->PJM
CLTF
1.615
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.599
CPLELTFEXP_CPLE->PJM
CLTF
3.766
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.728
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.01
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.33 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:948.5
MW Contribution:
5.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970301AG2-198 GEN
Solar/Wind Harmer
8.11
970685AG2-442 GEN
Solar/Wind Harmer
12.594
966001AG1-469 GEN
Solar/Wind Helper
0.359
315616AA1-038_C
Solar/Wind Helper
1.731
957481AF2-042 GEN
Solar/Wind Harmer
3.595
3146776BUCKING
Solar/Wind Harmer
3.488
3146776BUCKING
Solar/Wind Harmer
0.282
946301AF1-294 GEN
Solar/Wind Harmer
3.878
3144303KENBRDG
Solar/Wind Harmer
0.308
970535AG2-341 GEN
50/50
4.255
3146776BUCKING
Solar/Wind Harmer
0.349
964791AG1-342 GEN
Solar/Wind Harmer
1.658
315760AF1-028 GEN
50/50
Charging
15.733
970117AG2-086 GEN
50/50
Charging
1.277
971377AH1-170 GEN
Solar/Wind Harmer
3.912
970257AG2-171 GEN
Solar/Wind Harmer
4.613
316303AF2-085
50/50
1.323
3147043LAWRENC
50/50
0.696
3147133PAMPLIN
Solar/Wind Harmer
0.402
961791AG1-021 GEN
Solar/Wind Harmer
1.892
316192AB2-158 GEN
Solar/Wind Helper
1.526
970937AG2-583 GEN
Solar/Wind Harmer
20.574
971845AH1-439 GEN
Solar/Wind Harmer
14.549
316336AC2-165 C
Solar/Wind Harmer
12.991
3147133PAMPLIN
Solar/Wind Harmer
1.579
316499AE2-029_GEN
Solar/Wind Helper
1.245
970909AG2-566 GEN
50/50
5.243
970413AG2-270 GEN
50/50
11.112
970683AG2-441 GEN
Solar/Wind Harmer
9.719
3143336POWHATN
Solar/Wind Harmer
2.22
3143336POWHATN
Solar/Wind Harmer
1.887
970681AG2-440 GEN
Solar/Wind Harmer
6.45
962561AG1-105 GEN
Solar/Wind Harmer
4.288
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
7.96
970401AG2-262 GEN
Solar/Wind Harmer
0.507
970099AG2-077 GEN
Solar/Wind Harmer
1.438
972003AH1-546 GEN
Solar/Wind Harmer
13.964
3147623JAMES R
Solar/Wind Harmer
0.51
315821AE2-092 GEN
Solar/Wind Harmer
0
970119AG2-088 GEN
50/50
9.919
970221AG2-151 GEN
Solar/Wind Harmer
19.558
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
19.37
971563AH1-280 GEN
Solar/Wind Harmer
1.892
971775AH1-396 GEN
Solar/Wind Harmer
0.914
315693AD1-088 GEN
Solar/Wind Harmer
4.291
970323AG2-213 GEN
Solar/Wind Harmer
6.151
315785AD2-033 C
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
3.307
3147133PAMPLIN
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
2.365
959311AF2-222 GEN
Solar/Wind Harmer
13.277
3146843MT LREL
Solar/Wind Harmer
0.23
3146843MT LREL
Solar/Wind Harmer
0.23
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.318
LGEELTFEXP_LGEE->PJM
CLTF
0.434
MECLTFEXP_MEC->PJM
CLTF
1.183
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.207
CPLELTFEXP_CPLE->PJM
CLTF
3.164
SIGELTFEXP_SIGE->PJM
CLTF
0.036
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.536
WECLTFEXP_WEC->PJM
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
2.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.108
NYPJM->LTFIMP_NY
CLTF
0.768
TVALTFEXP_TVA->PJM
CLTF
1.33
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.55 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:966.48
MW Contribution:
5.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
941591AE2-156 GEN
50/50
5.394
3146926FARMVIL
Solar/Wind Harmer
0.449
3146926FARMVIL
Solar/Wind Harmer
0.449
970301AG2-198 GEN
Solar/Wind Harmer
9.17
970685AG2-442 GEN
Solar/Wind Harmer
14.242
3143226MDLTHAN
Solar/Wind Harmer
0.292
966001AG1-469 GEN
Solar/Wind Helper
0.335
315616AA1-038_C
Solar/Wind Helper
1.054
957481AF2-042 GEN
Solar/Wind Harmer
6.021
3146776BUCKING
Solar/Wind Harmer
3.755
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.367
3144303KENBRDG
Solar/Wind Harmer
0.353
970535AG2-341 GEN
50/50
5.173
972187AH1-678 GEN
50/50
2.361
315779AE2-040
50/50
0.981
3146776BUCKING
Solar/Wind Harmer
0.376
315760AF1-028 GEN
50/50
Charging
11.367
971377AH1-170 GEN
Solar/Wind Harmer
4.159
970257AG2-171 GEN
Solar/Wind Harmer
5.295
963041AG1-153 GEN
50/50
5.208
316303AF2-085
50/50
2.015
3147043LAWRENC
50/50
0.917
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.13
316192AB2-158 GEN
Solar/Wind Helper
1.485
970937AG2-583 GEN
Solar/Wind Harmer
22.308
971845AH1-439 GEN
Solar/Wind Harmer
15.686
316336AC2-165 C
Solar/Wind Harmer
14.671
3147133PAMPLIN
Solar/Wind Harmer
1.769
316499AE2-029_GEN
Solar/Wind Helper
0.93
970909AG2-566 GEN
50/50
5.929
970413AG2-270 GEN
50/50
14.332
970683AG2-441 GEN
Solar/Wind Harmer
11.035
3143336POWHATN
Solar/Wind Harmer
2.57
3143336POWHATN
Solar/Wind Harmer
2.185
970681AG2-440 GEN
Solar/Wind Harmer
7.324
962561AG1-105 GEN
Solar/Wind Harmer
5.111
972185AH1-677 GEN
50/50
4.626
944641AF1-129 GEN
50/50
25.925
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
9.33
970099AG2-077 GEN
Solar/Wind Harmer
2.409
972003AH1-546 GEN
Solar/Wind Harmer
14.847
3147623JAMES R
Solar/Wind Harmer
0.542
315821AE2-092 GEN
Solar/Wind Harmer
0
970119AG2-088 GEN
50/50
15.11
970221AG2-151 GEN
Solar/Wind Harmer
20.797
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
971223AH1-071 GEN
Solar/Wind Harmer
1.169
972205AH1-687 GEN
50/50
20.567
970533AG2-339 GEN
50/50
5.794
971563AH1-280 GEN
Solar/Wind Harmer
2.13
971775AH1-396 GEN
Solar/Wind Harmer
1.049
315693AD1-088 GEN
Solar/Wind Harmer
5.357
970323AG2-213 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
3.053
3147133PAMPLIN
Solar/Wind Harmer
0.563
958211AF2-115 GEN
Solar/Wind Harmer
2.663
959311AF2-222 GEN
Solar/Wind Harmer
15.189
NYPJM->LTFIMP_NY
CLTF
0.728
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.01
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.599
CPLELTFEXP_CPLE->PJM
CLTF
3.766
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.005
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.414
LGEELTFEXP_LGEE->PJM
CLTF
0.006
MECLTFEXP_MEC->PJM
CLTF
0.263
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.464
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.388
TVALTFEXP_TVA->PJM
CLTF
0.837
LAGNLTFEXP_LAGN->PJM
CLTF
1.615

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.72 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:943.57
MW Contribution:
5.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970301AG2-198 GEN
Solar/Wind Harmer
8.11
970685AG2-442 GEN
Solar/Wind Harmer
12.594
966001AG1-469 GEN
Solar/Wind Helper
0.359
315616AA1-038_C
Solar/Wind Helper
1.731
957481AF2-042 GEN
Solar/Wind Harmer
3.595
3146776BUCKING
Solar/Wind Harmer
3.488
3146776BUCKING
Solar/Wind Harmer
0.282
946301AF1-294 GEN
Solar/Wind Harmer
3.878
3144303KENBRDG
Solar/Wind Harmer
0.308
970535AG2-341 GEN
50/50
4.255
3146776BUCKING
Solar/Wind Harmer
0.349
964791AG1-342 GEN
Solar/Wind Harmer
1.658
315760AF1-028 GEN
50/50
Charging
15.733
970117AG2-086 GEN
50/50
Charging
1.277
971377AH1-170 GEN
Solar/Wind Harmer
3.912
970257AG2-171 GEN
Solar/Wind Harmer
4.613
316303AF2-085
50/50
1.323
3147043LAWRENC
50/50
0.696
3147133PAMPLIN
Solar/Wind Harmer
0.402
961791AG1-021 GEN
Solar/Wind Harmer
1.892
316192AB2-158 GEN
Solar/Wind Helper
1.526
970937AG2-583 GEN
Solar/Wind Harmer
20.574
971845AH1-439 GEN
Solar/Wind Harmer
14.549
316336AC2-165 C
Solar/Wind Harmer
12.991
3147133PAMPLIN
Solar/Wind Harmer
1.579
316499AE2-029_GEN
Solar/Wind Helper
1.245
970909AG2-566 GEN
50/50
5.243
970413AG2-270 GEN
50/50
11.112
970683AG2-441 GEN
Solar/Wind Harmer
9.719
3143336POWHATN
Solar/Wind Harmer
2.22
3143336POWHATN
Solar/Wind Harmer
1.887
970681AG2-440 GEN
Solar/Wind Harmer
6.45
962561AG1-105 GEN
Solar/Wind Harmer
4.288
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
7.96
970401AG2-262 GEN
Solar/Wind Harmer
0.507
970099AG2-077 GEN
Solar/Wind Harmer
1.438
972003AH1-546 GEN
Solar/Wind Harmer
13.964
3147623JAMES R
Solar/Wind Harmer
0.51
315821AE2-092 GEN
Solar/Wind Harmer
0
970119AG2-088 GEN
50/50
9.919
970221AG2-151 GEN
Solar/Wind Harmer
19.558
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
19.37
971563AH1-280 GEN
Solar/Wind Harmer
1.892
971775AH1-396 GEN
Solar/Wind Harmer
0.914
315693AD1-088 GEN
Solar/Wind Harmer
4.291
958131AF2-107 GEN
Solar/Wind Harmer
3.307
970323AG2-213 GEN
Solar/Wind Harmer
6.151
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
2.365
959311AF2-222 GEN
Solar/Wind Harmer
13.277
3146843MT LREL
Solar/Wind Harmer
0.23
3146843MT LREL
Solar/Wind Harmer
0.23
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.108
NYPJM->LTFIMP_NY
CLTF
0.768
TVALTFEXP_TVA->PJM
CLTF
1.33
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.536
WECLTFEXP_WEC->PJM
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
2.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.318
LGEELTFEXP_LGEE->PJM
CLTF
0.434
MECLTFEXP_MEC->PJM
CLTF
1.183
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.207
CPLELTFEXP_CPLE->PJM
CLTF
3.164
SIGELTFEXP_SIGE->PJM
CLTF
0.036

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.62 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:746.38
MW Contribution:
10.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.827
3146926FARMVIL
Solar/Wind Harmer
0.827
970301AG2-198 GEN
Solar/Wind Harmer
16.138
970685AG2-442 GEN
Solar/Wind Harmer
24.695
957481AF2-042 GEN
Solar/Wind Harmer
34.788
946301AF1-294 GEN
Solar/Wind Harmer
7.637
3144303KENBRDG
Solar/Wind Harmer
0.594
316405AF2-144 C
50/50
Charging
1.192
970257AG2-171 GEN
Solar/Wind Harmer
8.912
963041AG1-153 GEN
50/50
5.474
3147043LAWRENC
50/50
1.213
3147133PAMPLIN
Solar/Wind Harmer
0.796
961791AG1-021 GEN
Solar/Wind Harmer
3.725
971845AH1-439 GEN
Solar/Wind Harmer
29.626
3147133PAMPLIN
Solar/Wind Harmer
3.125
970909AG2-566 GEN
50/50
10.434
970413AG2-270 GEN
50/50
20.29
970683AG2-441 GEN
Solar/Wind Harmer
18.98
316258AE1-075 C
Solar/Wind Helper
0.527
970681AG2-440 GEN
Solar/Wind Harmer
12.598
962561AG1-105 GEN
Solar/Wind Harmer
7.641
316322AB2-045
Solar/Wind Helper
2.071
972185AH1-677 GEN
50/50
4.77
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
15.053
970401AG2-262 GEN
Solar/Wind Harmer
0.894
970099AG2-077 GEN
Solar/Wind Harmer
13.915
315821AE2-092 GEN
Solar/Wind Helper
5.461
970535AG2-341 GEN
50/50
7.786
972187AH1-678 GEN
50/50
2.481
315779AE2-040
50/50
0.834
964791AG1-342 GEN
Solar/Wind Harmer
2.926
970533AG2-339 GEN
50/50
5.707
971563AH1-280 GEN
Solar/Wind Harmer
3.725
971775AH1-396 GEN
Solar/Wind Harmer
1.766
315693AD1-088 GEN
Solar/Wind Harmer
8.117
270494AE1-108_GEN
Solar/Wind Helper
6.773
316313AB2-026
Solar/Wind Helper
0.585
970323AG2-213 GEN
Solar/Wind Harmer
11.883
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.995
958211AF2-115 GEN
Solar/Wind Harmer
4.657
959311AF2-222 GEN
Solar/Wind Harmer
25.739
3146843MT LREL
Solar/Wind Harmer
0.406
3146843MT LREL
Solar/Wind Harmer
0.406
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.472
LGEELTFEXP_LGEE->PJM
CLTF
0.24
MECLTFEXP_MEC->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.015
CPLELTFEXP_CPLE->PJM
CLTF
4.43
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.068
WECLTFEXP_WEC->PJM
CLTF
0.129
LAGNLTFEXP_LAGN->PJM
CLTF
2.423
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.315
NYPJM->LTFIMP_NY
CLTF
0.584
TVALTFEXP_TVA->PJM
CLTF
1.239
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.49 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:745.46
MW Contribution:
13.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.53
970685AG2-442 GEN
Solar/Wind Harmer
31.33
957481AF2-042 GEN
Solar/Wind Harmer
87.595
946301AF1-294 GEN
Solar/Wind Harmer
9.595
3144303KENBRDG
Solar/Wind Harmer
0.78
316405AF2-144 C
50/50
Charging
1.029
970257AG2-171 GEN
Solar/Wind Harmer
11.696
3147043LAWRENC
50/50
1.473
971629AH1-314 GEN
50/50
5.923
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.68
971845AH1-439 GEN
Solar/Wind Harmer
32.896
3147133PAMPLIN
Solar/Wind Harmer
3.882
970909AG2-566 GEN
50/50
13.92
970413AG2-270 GEN
50/50
42.65
970683AG2-441 GEN
Solar/Wind Harmer
24.301
316258AE1-075 C
Solar/Wind Helper
0.455
970681AG2-440 GEN
Solar/Wind Harmer
16.129
316322AB2-045
Solar/Wind Helper
1.727
962561AG1-105 GEN
Solar/Wind Harmer
10.411
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
35.038
964241AG1-285 GEN
Solar/Wind Harmer
20.725
315821AE2-092 GEN
Solar/Wind Helper
4.582
970535AG2-341 GEN
50/50
11.53
971563AH1-280 GEN
Solar/Wind Harmer
4.68
971775AH1-396 GEN
Solar/Wind Harmer
2.318
315693AD1-088 GEN
Solar/Wind Harmer
15.29
270494AE1-108_GEN
Solar/Wind Helper
5.526
316313AB2-026
Solar/Wind Helper
0.505
970323AG2-213 GEN
Solar/Wind Harmer
15.594
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.85
959311AF2-222 GEN
Solar/Wind Harmer
33.519
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.809
NYPJM->LTFIMP_NY
CLTF
0.532
TVALTFEXP_TVA->PJM
CLTF
1.555
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.264
WECLTFEXP_WEC->PJM
CLTF
0.249
LAGNLTFEXP_LAGN->PJM
CLTF
3.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.661
LGEELTFEXP_LGEE->PJM
CLTF
0.466
MECLTFEXP_MEC->PJM
CLTF
1.387
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.622
CPLELTFEXP_CPLE->PJM
CLTF
4.42
SIGELTFEXP_SIGE->PJM
CLTF
0.041

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.3 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:777.36
MW Contribution:
10.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.827
3146926FARMVIL
Solar/Wind Harmer
0.827
970301AG2-198 GEN
Solar/Wind Harmer
16.132
970685AG2-442 GEN
Solar/Wind Harmer
24.684
957481AF2-042 GEN
Solar/Wind Harmer
29.784
3146776BUCKING
Solar/Wind Harmer
7.104
3146776BUCKING
Solar/Wind Harmer
0.575
946301AF1-294 GEN
Solar/Wind Harmer
7.634
3144303KENBRDG
Solar/Wind Harmer
0.594
316405AF2-144 C
50/50
Charging
1.194
970257AG2-171 GEN
Solar/Wind Harmer
8.908
963041AG1-153 GEN
50/50
5.464
3147043LAWRENC
50/50
1.212
3147133PAMPLIN
Solar/Wind Harmer
0.796
961791AG1-021 GEN
Solar/Wind Harmer
3.724
971845AH1-439 GEN
Solar/Wind Harmer
29.619
3147133PAMPLIN
Solar/Wind Harmer
3.124
970909AG2-566 GEN
50/50
10.43
970413AG2-270 GEN
50/50
20.271
970683AG2-441 GEN
Solar/Wind Harmer
18.972
316258AE1-075 C
Solar/Wind Helper
0.527
970681AG2-440 GEN
Solar/Wind Harmer
12.592
962561AG1-105 GEN
Solar/Wind Harmer
7.634
972185AH1-677 GEN
50/50
4.762
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
15.043
970401AG2-262 GEN
Solar/Wind Harmer
0.893
970099AG2-077 GEN
Solar/Wind Harmer
11.914
972003AH1-546 GEN
Solar/Wind Harmer
28.628
315821AE2-092 GEN
Solar/Wind Helper
5.466
970535AG2-341 GEN
50/50
7.78
972187AH1-678 GEN
50/50
2.477
315779AE2-040
50/50
0.832
3146776BUCKING
Solar/Wind Harmer
0.71
964791AG1-342 GEN
Solar/Wind Harmer
2.924
3146776BUCKING
Solar/Wind Harmer
0.639
270494AE1-108_GEN
Solar/Wind Helper
6.779
316313AB2-026
Solar/Wind Helper
0.586
970533AG2-339 GEN
50/50
5.696
971563AH1-280 GEN
Solar/Wind Harmer
3.724
971775AH1-396 GEN
Solar/Wind Harmer
1.765
315693AD1-088 GEN
Solar/Wind Harmer
8.111
970323AG2-213 GEN
Solar/Wind Harmer
11.877
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.995
958211AF2-115 GEN
Solar/Wind Harmer
4.655
959311AF2-222 GEN
Solar/Wind Harmer
25.726
3146843MT LREL
Solar/Wind Harmer
0.405
3146843MT LREL
Solar/Wind Harmer
0.405
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.025
WECLTFEXP_WEC->PJM
CLTF
0.125
LAGNLTFEXP_LAGN->PJM
CLTF
2.401
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.152
NYPJM->LTFIMP_NY
CLTF
0.591
TVALTFEXP_TVA->PJM
CLTF
1.227
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.981
CPLELTFEXP_CPLE->PJM
CLTF
4.418
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.321
LGEELTFEXP_LGEE->PJM
CLTF
0.232
MECLTFEXP_MEC->PJM
CLTF
0.841

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.09 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:775.9
MW Contribution:
13.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.524
970685AG2-442 GEN
Solar/Wind Harmer
31.319
957481AF2-042 GEN
Solar/Wind Harmer
87.558
3146776BUCKING
Solar/Wind Harmer
7.851
3146776BUCKING
Solar/Wind Harmer
0.636
946301AF1-294 GEN
Solar/Wind Harmer
9.591
3144303KENBRDG
Solar/Wind Harmer
0.779
316405AF2-144 C
50/50
Charging
1.03
970257AG2-171 GEN
Solar/Wind Harmer
11.691
3147043LAWRENC
50/50
1.472
971629AH1-314 GEN
50/50
5.91
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.679
971845AH1-439 GEN
Solar/Wind Harmer
32.89
3147133PAMPLIN
Solar/Wind Harmer
3.88
970909AG2-566 GEN
50/50
13.916
970413AG2-270 GEN
50/50
42.63
970683AG2-441 GEN
Solar/Wind Harmer
24.293
316258AE1-075 C
Solar/Wind Helper
0.455
970681AG2-440 GEN
Solar/Wind Harmer
16.124
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
35.023
964241AG1-285 GEN
Solar/Wind Harmer
18.877
972003AH1-546 GEN
Solar/Wind Harmer
30.103
315821AE2-092 GEN
Solar/Wind Helper
4.587
970535AG2-341 GEN
50/50
11.523
3146776BUCKING
Solar/Wind Harmer
0.785
3146776BUCKING
Solar/Wind Harmer
0.707
270494AE1-108_GEN
Solar/Wind Helper
5.532
316313AB2-026
Solar/Wind Helper
0.506
971563AH1-280 GEN
Solar/Wind Harmer
4.679
971775AH1-396 GEN
Solar/Wind Harmer
2.317
315693AD1-088 GEN
Solar/Wind Harmer
15.284
970323AG2-213 GEN
Solar/Wind Harmer
15.588
315785AD2-033 C
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.848
959311AF2-222 GEN
Solar/Wind Harmer
33.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.51
LGEELTFEXP_LGEE->PJM
CLTF
0.458
MECLTFEXP_MEC->PJM
CLTF
1.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.588
CPLELTFEXP_CPLE->PJM
CLTF
4.408
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.222
WECLTFEXP_WEC->PJM
CLTF
0.245
LAGNLTFEXP_LAGN->PJM
CLTF
3.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.645
NYPJM->LTFIMP_NY
CLTF
0.539
TVALTFEXP_TVA->PJM
CLTF
1.544
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P1-2: LN 298_SRT-A-1'
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 971844 TO BUS 314692 CKT 1   /*AH1-439 TP   230.0 - 6FARMVIL     230.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-L'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-L'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3359 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314744 to 313708 ckt 2
314691 to 314692 ckt 1
313708 to 313707 ckt 1
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314677 to 972002 ckt 1
314692 to 971844 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 2 Cluster 3 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 3 projects.

 

Table 1: Transition Cycle 2 Cluster 3 Projects

 

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Trans. Owner

MFO (MW)

MWE

(MW)

MWC

(MW)

Point of Interconnection

3

AG2-151

PV

Dominion

100

100

60

Trices Lake - James River Tap 115 kV

AG2-198

PV

Dominion

80

80

48

Briery - Finneywood 230 kV

AG2-566

BS

Dominion

30

30

12

Briery - Finneywood 230 kV

AG2-583

PV

Dominion

115

115

69

Bremo - Cartersville 230 kV

AH1-170

PV

Dominion

20

20

12

Columbia DP 115 kV

AH1-439

PV

Dominion

85

85

51

Buckingham - Farmville 230 kV

AH1-546

PV

Dominion

65

65

39

Bremo - Buckingham 230 kV

 

The purpose of the transient stability analysis is to determine the system impact of the generation facility. This study will determine system improvements, if any, needed to reduce violations in the transient stability analysis caused by the addition of the projects in Cluster 3.

 

The load flow scenario for the analysis was based on the Regional Transmission Expansion Plan (RTEP) 2028 summer peak case, modified to include applicable projects. The TC2 Cluster 3 projects have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer.

 

Cluster 3 projects were tested for compliance with NERC, PJM, Dominion Energy and other applicable criteria. 264 contingencies were studied, each with a 20 second simulation time period. The contingencies studied included:

 

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults placed at 80% of the line with delayed clearing at remote line end because of primary communications/relaying failure
  • Single-phase faults with loss of multiple-circuit tower line

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

The results of the analysis were evaluated against the following recovery criteria per PJM’s Regional Transmission Planning Process and Dominion Energy’s transmission planning criteria:

 

  • Cluster 3 projects were able to ride through the faults (except for faults where protective action trips a generator(s)).
  • The system with Cluster 3 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

 

AH1-546: Main Power Transformer High side to Tertiary impedance from Next Gen data (0.0033 + j0.141) does not match PSSE case (0.0033 + j0.0002). Main Power Transformer Low side to Tertiary impedance from Next Gen data (0.0033 + j0.0288) does not match PSSE case (0.0033 + j0.141). Case was set up using the PSSE case provided during DP1 Round 2 data. The IC should review the impedance and align the sav case and Next Gen data in the DP2 submittal.

 

No mitigation is required.

 

The following settings were adjusted in order to meet the evaluation criteria. The generator owners should provide their preferred adjustment for the issues described in the summary of results.

 

AG2-566 Results

No voltage-reactive droop setting was identified for AG2-566; implementation of a 4% voltage reactive droop is recommended to coordinate voltage and reactive power control with nearby generating facilities.

 

AG2-583 Results

No voltage-reactive droop setting was identified for AG2-583; implementation of a 4% voltage reactive droop is recommended to coordinate voltage and reactive power control with nearby generating facilities.

 

AH1-170 Results

AH1-170 experienced numerical convergency issues post fault for certain contingencies. Updating the REPCA RefFlag from 0 to 1 prevented any convergency issues for the generator.

 

Voltage-reactive droop setting was identified for AH1-170; implementation of a 4% voltage reactive droop is recommended to coordinate voltage and reactive power control with nearby generating facilities.

 

AH1-546 Results

No voltage-reactive droop setting was identified for AH1-546; implementation of a 4% voltage reactive droop is recommended to coordinate voltage and reactive power control with nearby generating facilities.

 

AE2-092 Results

No voltage-reactive droop setting was identified for AE2-092; Updating the REPCA VCFlag from 1 to 0 is recommended to coordinate voltage and reactive power control with nearby generating facilities.

 

Note: PJM will contact the project developer to verify the model tuning recommendation for non TC2 Cycle project.

Reactive Power Analysis

AG2-566 met the 0.95 leading and 0.95 lagging power factor requirements measured at the high side of the main transformer.

 

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVEngineering & Procurement
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVUnder Construction
AC1-098Dawson-South Justice 115kVIn Service
AC1-099Dawson-South Justice 115kVIn Service
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVUnder Construction
AC2-100Halifax-Person 230kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-149Disputanta-Poe 115 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVUnder Construction
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVIn Service
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVWithdrawn
AE2-140Axton-Danville 138 kVSuspended
AE2-166Stockton 138 kVSuspended
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-123Harper 230 kVUnder Construction
AF1-124Harper 230 kVPartially in Service - Under Construction
AF1-125Harper 230 kVUnder Construction
AF1-128Chesterfield 230 kVUnder Construction
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVUnder Construction
AF1-294Jetersville-Ponton 115 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVEngineering & Procurement
AF2-043Suffolk 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVWithdrawn
AF2-081Moyock 230 kVEngineering & Procurement
AF2-085Midlothian 34.5 kVIn Service
AF2-107Clifford 138 kVWithdrawn
AF2-110Suffolk 115 kVWithdrawn
AF2-115Jetersville-Ponton 115 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVEngineering & Procurement
AF2-299Fields 34.5 kVEngineering & Procurement
AG1-007Tar River 12.5 kVWithdrawn
AG1-021Jetersville-Ponton 115 kVEngineering & Procurement
AG1-037Ahoskie 34.5 kVWithdrawn
AG1-105Mount Laurel-Barnes Junction 115 kVUnder Construction
AG1-106Thelma 230 kVWithdrawn
AG1-124Riverville - Gladstone 138 kVEngineering & Procurement
AG1-153Heritage 500 kVUnder Construction
AG1-285Chase City-Central 115 kVEngineering & Procurement
AG1-342Dryburg 115 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-532Fields 34.5 kVUnder Construction
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-088Midlothian 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg - Nutbush 115 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-272Berry Hill 138 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-522Five Forks DP - Littleton DP 115 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings - Unity 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-659Palmer Springs - Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-170Columbia DP 115kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-221Heritage 500 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-396Gary 24.94 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-687Bear Garden 230kVActive
V4-068Murphy's 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AG2-566 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Identified Impacts
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Impacted FacilityTransmission OwnerReinforcementCostCost Allocated to AG2-566Scenarios
  • Person 230.0 - Hendricks 230.0 CKT 1
CPLE Construction of the line Person-Hendricks 230 kV
this is the contingent upgrade identified for TC2
projects in DEP AFS report issued on 5/14/2026.
new rating to be 1195 MVA
$7,727,000$0
  • Contingent
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-566 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9729.0Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated deviceCost Allocated$544,309N/A
Dominionn9727.0Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated deviceCost Allocated$544,277N/A
Dominionn9726.0Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.Cost Allocated$60,956N/A
Dominionn9221.0Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).Cost Allocated$44,277N/A
Dominionn9730.0Replace switches 29824 and 29825 at Bremo 230 kVCost Allocated$17,217N/A
Dominionn9728.0Replace wave trap 298 WT at Bremo 230 kVCost Allocated$8,609N/A
Dominionn9630.0Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Contingent$0N/A
AEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Contingent$0N/A
Dominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Contingent$0N/A
Dominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Contingent$0N/A
Dominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Contingent$0N/A
Dominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Contingent$0N/A
Dominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Contingent$0N/A
Dominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Contingent$0N/A
Dominionn9220.0Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Contingent$0N/A
Dominionn9217.0Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.Contingent$0N/A
Dominionb4030.9Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.New ReinforcementContingent$0N/A
Dominionb4030.11Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.Contingent$0N/A
Dominionb4030.15Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.Contingent$0N/A
Dominionb4030.12Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.Contingent$0N/A
Dominionb4030.10Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.Contingent$0N/A
Dominionb4030.14Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.Contingent$0N/A
Dominionb4030.13Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.Contingent$0N/A
Grand Total:$1,219,645

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Discounted Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Contingent

Note: Based on PJM cost allocation criteria, AG2-566 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-566 may not have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9729.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9729.0 / TC2-PH1-DOM-2092
Title
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Total Cost ($USD)
$38,000,000
Discounted Total Cost ($USD)
$38,000,000
Allocated Cost ($USD)
$544,309
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2304.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07754.0 MW17.4%$6,623,607
AG2-17115.0 MW4.8%$1,839,802
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
23.4 MW7.5%$2,866,577
AG2-21320.0 MW6.5%$2,453,070
AG2-27035.9 MW11.6%$4,401,831
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
25.2 MW8.1%$3,086,951
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
37.9 MW12.2%$4,650,918
AG2-44245.6 MW14.7%$5,594,623
AG2-52210.9 MW3.5%$1,338,194
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
4.4 MW1.4%$544,309
AG2-65912.5 MW4.0%$1,534,027
AH1-34310.6 MW3.4%$1,296,353
AH1-43914.4 MW4.7%$1,769,739

System Reinforcement: n9727.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9727.0 / TC2-PH1-DOM-2091
Title
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Total Cost ($USD)
$38,000,000
Discounted Total Cost ($USD)
$38,000,000
Allocated Cost ($USD)
$544,277
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2304.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07754.0 MW17.4%$6,623,610
AG2-17115.0 MW4.8%$1,839,830
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
23.4 MW7.5%$2,866,616
AG2-21320.0 MW6.5%$2,453,107
AG2-27035.9 MW11.6%$4,401,769
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
25.2 MW8.1%$3,086,851
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
37.9 MW12.2%$4,650,928
AG2-44245.6 MW14.7%$5,594,619
AG2-52210.9 MW3.5%$1,338,203
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
4.4 MW1.4%$544,277
AG2-65912.5 MW4.0%$1,534,050
AH1-34310.6 MW3.4%$1,296,411
AH1-43914.4 MW4.7%$1,769,728

System Reinforcement: n9726.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9726.0 / TC2-PH1-DOM-2043
Title
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Description
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Total Cost ($USD)
$3,534,000
Discounted Total Cost ($USD)
$3,534,000
Allocated Cost ($USD)
$60,956
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1410.0 MVA
LLB1481.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1446.0 MVA
WINB1517.0 MVA
WINC1631.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07765.1 MW12.5%$442,733
AG2-1517.1 MW1.4%$48,582
AG2-17114.3 MW2.7%$97,022
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
18.8 MW3.6%$128,145
AG2-21319.0 MW3.7%$129,362
AG2-27065.2 MW12.5%$443,182
AG2-34113.8 MW2.7%$93,867
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.0%$140,410
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.1 MW6.0%$211,550
AG2-44237.5 MW7.2%$255,006
AG2-52210.2 MW2.0%$69,114
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
9.0 MW1.7%$60,956
AG2-58148.0 MW9.2%$326,635
AG2-5837.4 MW1.4%$50,309
AG2-65911.7 MW2.2%$79,434
AH1-34321.5 MW4.1%$146,168
AH1-43912.2 MW2.4%$83,058
AH1-52896.3 MW18.5%$655,010
AH1-5465.6 MW1.1%$38,316
AH1-6875.2 MW1.0%$35,142

System Reinforcement: n9221.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9221.0 / TC1-PH3-DOM-015-TC2
Title
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Description
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Total Cost ($USD)
$2,057,335
Discounted Total Cost ($USD)
$2,057,335
Allocated Cost ($USD)
$44,277
Time Estimate
38 to 39 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1035.0 MVA
LLB1091.0 MVA
LLC1201.0 MVA
SUMA900.0 MVA
SUMB964.0 MVA
SUMC1115.0 MVA
WINA1067.0 MVA
WINB1123.0 MVA
WINC1219.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07747.4 MW9.8%$201,196
AG2-17116.2 MW3.3%$68,920
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
29.2 MW6.0%$123,866
AG2-21321.6 MW4.5%$91,895
AG2-27029.7 MW6.1%$125,997
AG2-3417.8 MW1.6%$33,027
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.3%$87,777
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.2 MW6.4%$132,254
AG2-44240.5 MW8.4%$171,840
AG2-5229.9 MW2.0%$41,934
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
10.4 MW2.2%$44,277
AG2-58136.2 MW7.5%$153,578
AG2-65910.9 MW2.3%$46,485
AH1-3145.7 MW1.2%$24,329
AH1-3438.9 MW1.8%$37,956
AH1-43944.7 MW9.2%$189,912
AH1-52872.5 MW15.0%$307,970
AH1-54641.0 MW8.5%$174,120

System Reinforcement: n9730.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9730.0 / TC2-PH1-DOM-2077
Title
Replace switches 29824 and 29825 at Bremo 230 kV
Description
Replace switches 29824 and 29825 at Bremo 230 kV
Total Cost ($USD)
$800,000
Discounted Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$17,217
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1145.0 MVA
LLB1183.0 MVA
LLC1201.0 MVA
SUMA1050.0 MVA
SUMB1094.0 MVA
SUMC1115.0 MVA
WINA1164.0 MVA
WINB1201.0 MVA
WINC1219.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07747.4 MW9.8%$78,236
AG2-17116.2 MW3.3%$26,800
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
29.2 MW6.0%$48,166
AG2-21321.6 MW4.5%$35,734
AG2-27029.7 MW6.1%$48,994
AG2-3417.8 MW1.6%$12,843
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.3%$34,133
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.2 MW6.4%$51,427
AG2-44240.5 MW8.4%$66,821
AG2-5229.9 MW2.0%$16,306
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
10.4 MW2.2%$17,217
AG2-58136.2 MW7.5%$59,719
AG2-65910.9 MW2.3%$18,076
AH1-3145.7 MW1.2%$9,460
AH1-3438.9 MW1.8%$14,759
AH1-43944.7 MW9.2%$73,848
AH1-52872.5 MW15.0%$119,755
AH1-54641.0 MW8.5%$67,707

System Reinforcement: n9728.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9728.0 / TC2-PH1-DOM-2076
Title
Replace wave trap 298 WT at Bremo 230 kV
Description
Replace wave trap 298 WT at Bremo 230 kV
Total Cost ($USD)
$400,000
Discounted Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$8,609
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA956.0 MVA
LLB1011.0 MVA
LLC1091.0 MVA
SUMA812.0 MVA
SUMB876.0 MVA
SUMC964.0 MVA
WINA979.0 MVA
WINB1043.0 MVA
WINC1115.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07747.4 MW9.8%$39,118
AG2-17116.2 MW3.3%$13,400
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
29.2 MW6.0%$24,083
AG2-21321.6 MW4.5%$17,867
AG2-27029.7 MW6.1%$24,497
AG2-3417.8 MW1.6%$6,421
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.3%$17,066
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.2 MW6.4%$25,714
AG2-44240.5 MW8.4%$33,410
AG2-5229.9 MW2.0%$8,153
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
10.4 MW2.2%$8,609
AG2-58136.2 MW7.5%$29,860
AG2-65910.9 MW2.3%$9,038
AH1-3145.7 MW1.2%$4,730
AH1-3438.9 MW1.8%$7,380
AH1-43944.7 MW9.2%$36,924
AH1-52872.5 MW15.0%$59,878
AH1-54641.0 MW8.5%$33,854

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: WT2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: WT2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: WT2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: WT2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: WT2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Discounted Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-566 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-566 may not have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1553.0 MVA
LLB1634.0 MVA
LLC1879.0 MVA
SUMA1350.0 MVA
SUMB1446.0 MVA
SUMC1756.0 MVA
WINA1598.0 MVA
WINB1648.0 MVA
WINC1895.0 MVA
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA940.0 MVA
LLB987.0 MVA
LLC1091.0 MVA
SUMA812.0 MVA
SUMB868.0 MVA
SUMC964.0 MVA
WINA964.0 MVA
WINB1011.0 MVA
WINC1115.0 MVA

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Discounted Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-566 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-566 may not have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BUCKING-AH1-439 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1553.0 MVA
LLB1634.0 MVA
LLC1879.0 MVA
SUMA1350.0 MVA
SUMB1446.0 MVA
SUMC1756.0 MVA
WINA1598.0 MVA
WINB1648.0 MVA
WINC1895.0 MVA
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA940.0 MVA
LLB987.0 MVA
LLC1163.0 MVA
SUMA812.0 MVA
SUMB868.0 MVA
SUMC1123.0 MVA
WINA964.0 MVA
WINB1011.0 MVA
WINC1171.0 MVA

System Reinforcement: s3671.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
s3671.5
Title
Rebuild Line 238 from Carson to Clubhouse for a normal summer rating of 1573 MVA
Description
Rebuild Line 238 from Carson to Clubhouse for a normal summer rating of 1573 MVA
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-566 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-566 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA
6OTTERDAM-6CLUBHSE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA
6ENCLAVE-6OTTERDAM 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1572.0 MVA
(All)B1572.0 MVA
(All)C1808.0 MVA

System Reinforcement: b4030.9
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.9
Title
Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.New Reinforcement
Description
Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
LLA1410.0 MVA
LLB1481.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1446.0 MVA
WINB1517.0 MVA
WINC1631.0 MVA
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA

System Reinforcement: b4030.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.11
Title
Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Description
Charlottesville 230 kV substation scope: Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC16480.0 MVA

System Reinforcement: b4030.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.15
Title
Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.
Description
Mt. Eagle tap 230 kV substation scope: Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
LLA1585.0 MVA
LLB1634.0 MVA
LLC1879.0 MVA
SUMA1524.0 MVA
SUMB1571.0 MVA
SUMC1801.0 MVA
WINA1598.0 MVA
WINB1648.0 MVA
WINC1895.0 MVA

System Reinforcement: b4030.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.12
Title
Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Description
Fork Union 230 kV substation scope: Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
LLA1585.0 MVA
LLB1634.0 MVA
LLC1879.0 MVA
SUMA1524.0 MVA
SUMB1571.0 MVA
SUMC1801.0 MVA
WINA1598.0 MVA
WINB1648.0 MVA
WINC1895.0 MVA

System Reinforcement: b4030.10
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.10
Title
Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.
Description
Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB16480.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.14
Title
Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Description
Bremo 230 kV substation scope: Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.13
Title
Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Description
Fork Union 230 kV substation scope: Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AG2-566 may not presently have cost responsibility for this upgrade, AG2-566 may need this upgrade in-service to be deliverable to the PJM system. If AG2-566 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
DVP Rating: 961/961/1106 MVA
Description
DVP Rating: 961/961/1106 MVA
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A961.0 MVA
(All)B961.0 MVA
(All)C1106.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-566


AG2-566 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
StabilityDominionn9630.0 / TC1-PH3-DOM-013Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.Topology-0.0%Contingent$0
Load FlowAEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Topology-0.0%Contingent$0
Load FlowDominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Topology-0.0%Contingent$0
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Topology-0.0%Contingent$0
Load FlowDominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Topology-0.0%Contingent$0
Load FlowDominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Load FlowDominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Topology-0.0%Contingent$0
Load FlowDominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Topology-0.0%Contingent$0
Load FlowDominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-566 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-566 One Line Diagram

AG2-566 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.