AG2-665 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:20

Corwin - Elk 138 kV

54.0 MW Capacity / 80.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Hamden Energy LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $2,027,566 $19,492,148 = 0.10 AND ( $2,027,566 - $19,492,148 ) 80.0 = $-218,307 per MW

General

The Project Developer has proposed an uprate to a planned/existing Solar/Storage facility located in the American Electric Power zone — Jackson County, Ohio. This project is an increase to the developer’s AG2-548 project(s), which will share the same Point of Interconnection. The AG2-665 project is a 80.0 MW uprate (54.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 160.0 MW with 108.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-665
Project Name:
Corwin - Elk 138 kV
Project Developer Name:
Hamden Energy LLC
State:
Ohio
County:
Jackson
Transmission Owner:
American Electric Power
MFO:
160.0
MWE:
80.0
MWC:
54.0
Battery Storage Specification:
360.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Solar/Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-665 will interconnect on the American Electric Power transmission system by tapping the Corwin-Elk 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-665 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-665Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$493,084$0$0
Other Scope$301,946$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$510,945$510,945$510,945
Network Upgrades$1,366,622$1,366,622$1,366,622
System Reliability Network Upgrades
Steady State Thermal & Voltage$150,000$150,000$150,000
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$2,822,596$2,027,566$2,027,566

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-665

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-665
Project ID: AG2-665
20% of cost allocation for Phase II Network Upgrades:(A) $405,513
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $1,949,215
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

• AEP Ohio Transmission Company Inc. will review and revise (as needed) the protective relay settings at the AG2-548 New 138 kV Station.

$44,758$12,003$28,387$7,613$92,761$92,761
(Pending)

CORWIN - ELK 138 kV line will be cut and looped into the new interconnection substation.

$1,159,053$547,931$284,264$134,793$2,126,041$1,063,020 (See Note 1)
(Pending)

AEP Ohio Transmission Company Inc. will install one (1) new 1101 router at the CORWIN 138 kV Station.

$38,144$118,755$20,397$58,863$236,159$118,080 (See Note 1)
(Pending)

AEP Ohio Transmission Company Inc. will install one (1) new 8340 router at the CORWIN 138 kV Station.

$89,516$24,006$56,774$15,225$185,521$92,760 (See Note 1)
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

AEP Ohio Transmission Company Inc. will install one (1) metering panel with two (2) primary meters and one (1) ethernet switch in the AG2-665 Project Developer's collector Station.

$155,133$69,804$53,111$23,898$301,946$301,946
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

AEP Ohio Transmission Company Inc. will install 1 mile of 144 count all dielectric self supporting (ADSS) fiber-optic cable. AEP Ohio Transmission Company Inc. will install 1 mile of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable.

$576,141$181,045$202,086$62,618$1,021,890$510,945 (See Note 1)
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

A 138 kV dead-end structure and foundation outside the fence of the Interconnection Substation, to terminate the Project Developers generator lead line. Line conductor from the dead-end structure to the bus position in the switchyard of the interconnection substation. The OHTCO Interconnection Facilities will include but are not limited to the following: Installation of one (1) new steel, single circuit, single pole dead end structure and one span of ACSR 1272 (Pheasant) transmission line conductor with 7#8 Alumoweld shield wire for the generation lead circuit extending from the AG2-548 New Station 138 kV Station.

$501,438$273,318$136,830$74,581$986,167$493,084 (See Note 1)
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$4,950,485$2,672,596
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 15 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-665 was evaluated as a 80.0 MW (54.0 MW Capacity) injection in the AEP area.

AG2-665 was evaluated as part of a plant. The plant consists of AG2-665, AG2-548. The total Energy output of the plant was evaluated at its maximum seasonal capability of 160.0 MW (180.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC102.09 %5523.0B5638.63
5.91
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC102.08 %5523.0B5637.94
5.91
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC215.51 %1180.0B2543.0
6.38
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC215.51 %1180.0B2543.0
6.38
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC215.51 %1180.0B2543.0
6.38
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC215.49 %1180.0B2542.74
6.38
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC123.36 %4571.0B5638.63
5.91
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC123.34 %4571.0B5637.94
5.91
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#3149_05HANG R 765_B_SRT-A
BreakerAC143.94 %1540.0B2216.66
6.37
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#6156_05MARQUI 765_2_SRT-A
BusAC120.75 %1540.0B1859.53
6.35
GD2AEP
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
BreakerAC109.84 %255.0B280.08
78.78
GD2AEP
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
BreakerAC109.84 %255.0B280.08
78.78

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
5.91
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
5.91
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for [AG2-665] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:215.51 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.0
MW Contribution:
6.38
IPD Plant:AG2-665
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
PJM_IPD_GROUP
5.67
970879AG2-548 GEN
PJM_IPD_GROUP
0.709
971073AG2-665 GEN
PJM_IPD_GROUP
5.67
971073AG2-665 GEN
PJM_IPD_GROUP
0.709

Details for [AG2-665] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.51 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.0
MW Contribution:
6.38
IPD Plant:AG2-665
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
PJM_IPD_GROUP
5.67
970879AG2-548 GEN
PJM_IPD_GROUP
0.709
971073AG2-665 GEN
PJM_IPD_GROUP
5.67
971073AG2-665 GEN
PJM_IPD_GROUP
0.709

Details for [AG2-665] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:215.51 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.0
MW Contribution:
6.38
IPD Plant:AG2-665
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
PJM_IPD_GROUP
5.67
970879AG2-548 GEN
PJM_IPD_GROUP
0.709
971073AG2-665 GEN
PJM_IPD_GROUP
5.67
971073AG2-665 GEN
PJM_IPD_GROUP
0.709

Details for [AG2-665] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2542.74
MW Contribution:
6.38
IPD Plant:AG2-665
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
PJM_IPD_GROUP
5.67
970879AG2-548 GEN
PJM_IPD_GROUP
0.709
971073AG2-665 GEN
PJM_IPD_GROUP
5.67
971073AG2-665 GEN
PJM_IPD_GROUP
0.709

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.36 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
5.91
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
5.91
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#3149_05HANG R 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3149_05HANG R 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2216.66
MW Contribution:
6.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.427
24803206KYGER 4HP
50/50
4.417
253316AC1-085 GEN3
Solar/Wind Harmer
11.681
946171AF1-282 GEN
Solar/Wind Harmer
13.952
252516AE2-318_GEN
Solar/Wind Harmer
13.939
25196808ZIMRHP
Adder
103.883
270273AD2-016 GEN
Solar/Wind Harmer
3.628
252510AF1-249 C
Solar/Wind Harmer
0.552
25194608D.CRK4
Adder
2.171
253398AE2-221_GEN2
Solar/Wind Harmer
5.919
25196008MFTGT1
Adder
1.705
945681AF1-233 GEN
Solar/Wind Harmer
23.016
339221AD2-048_GEN
Solar/Wind Harmer
1.678
253370AE2-315 SEC1
Adder
2.154
253371AE2-315 SEC2
Adder
2.037
25326309TAIT D
Adder
1.136
270222AC2-111 GEN
Solar/Wind Harmer
4.57
944031AF1-071 GEN
Solar/Wind Harmer
1.028
943111AE2-339 GEN
Solar/Wind Harmer
0.888
3429421JKCT 10G
Adder
8.012
3429241JKCT 3G
Adder
10.994
253333AC1-068 GEN
Solar/Wind Harmer
0.911
942081AE2-220 GEN
Solar/Wind Harmer
5.25
24803006KYGER 3HP
50/50
4.478
24802806KYGER 2HP
50/50
4.462
24802906KYGER 2LP
50/50
2.619
25183008BIOENL
50/50
0.04
252509AD1-136 GEN
Solar/Wind Harmer
0.382
25183208HLCRTG
Solar/Wind Harmer
8.726
270269AC2-059
Solar/Wind Harmer
12.725
25194408D.CRK1
Adder
9.987
25194508D.CRK3
Adder
1.867
253415AE1-040 GEN
Solar/Wind Harmer
1.391
962581AG1-107 GEN
Solar/Wind Harmer
6.139
961491AF2-440 GEN
Solar/Wind Harmer
2.552
253370AE2-315 SEC1
Adder
2.154
972043AH1-570 GEN
Solar/Wind Harmer
2.668
972045AH1-571 GEN
Solar/Wind Harmer
2.134
25322209TAIT E
Adder
10.12
24803106KYGER 3LP
50/50
2.637
24803306KYGER 4LP
50/50
2.583
971191AH1-055 GEN
Solar/Wind Harmer
85.223
252507AC2-088 GEN
Solar/Wind Harmer
2.672
253317AC1-085 GEN4
Solar/Wind Harmer
11.681
946181AF1-283 GEN
Solar/Wind Harmer
18.138
252519AF1-045_GEN
Solar/Wind Harmer
5.073
25194608D.CRK4
Adder
2.171
252524AE2-267 GEN
Solar/Wind Harmer
2.074
25196608WSDLE5
Adder
11.291
958171AF2-111 GEN
Solar/Wind Harmer
32.8
253394AE2-221_GEN
Solar/Wind Harmer
5.919
270367AC2-061_GEN
Solar/Wind Harmer
3.968
270186AC1-089 GEN
Solar/Wind Harmer
7.496
972167AH1-666 GEN
Solar/Wind Harmer
9.813
25196008MFTGT1
Adder
1.652
339243AC2-075 GEN1
Solar/Wind Harmer
0.505
253303V4-073 C
Solar/Wind Harmer
0.125
253370AE2-315 SEC1
Adder
2.154
253371AE2-315 SEC2
Adder
2.037
960071AF2-298 GEN
Solar/Wind Harmer
1.548
3429391JKCT 9G
Adder
8.012
253325AC1-069 GEN
Solar/Wind Harmer
0.911
970093AG2-073 GEN
Solar/Wind Harmer
4.533
24379505HDWTR1G C
Solar/Wind Harmer
6.491
270240V3-007_GEN2
Solar/Wind Harmer
5.079
270518AE2-148 GEN
Solar/Wind Harmer
9.286
270004AE1-209 GEN
Solar/Wind Harmer
4.08
970455AG2-298 GEN
Solar/Wind Harmer
2.601
946031AF1-268 GEN
Solar/Wind Harmer
6.158
24728505AND G1
Adder
2.824
970825AG2-519 GEN
Solar/Wind Harmer
4.143
962031AG1-047 GEN
Solar/Wind Harmer
2.182
957741AF2-068 GEN
Solar/Wind Harmer
10.823
970879AG2-548 GEN
Solar/Wind Harmer
5.557
276820AF1-078_GEN
Solar/Wind Harmer
1.094
970653AG2-424 GEN
Solar/Wind Harmer
0.476
339206AE1-143 GEN
Solar/Wind Harmer
1.407
965461AG1-414 GEN
Solar/Wind Harmer
1.435
970289AG2-191 GEN
Solar/Wind Harmer
0.486
247642Z2-115 C
Solar/Wind Harmer
0.039
942051AE2-217 GEN
Solar/Wind Harmer
10.751
944531AF1-118 GEN
Solar/Wind Harmer
20.719
960801AF2-371 GEN
Solar/Wind Harmer
1.503
964871AG1-351 GEN
Solar/Wind Harmer
1.038
972273AH1-721 GEN
Adder
48.281
970193AG2-126 GEN
Solar/Wind Harmer
8.371
957541AF2-048 GEN
Solar/Wind Harmer
0.86
339255AE2-071 GEN
Solar/Wind Harmer
0.625
339250AF1-203 GEN
Solar/Wind Harmer
0.322
24386205FR-12G C
Solar/Wind Harmer
2.102
942481AE2-261 GEN
Solar/Wind Harmer
14.45
957381AF2-032 GEN
Solar/Wind Harmer
0.966
276785W4-005 GEN1
Solar/Wind Harmer
1.451
971993AH1-541 GEN
Solar/Wind Harmer
4.434
24690905MDL-1G C
Solar/Wind Harmer
3.811
274729ELWOOD EC;1P
Adder
7.239
274730ELWOOD EC;6P
Adder
7.239
274734ELWOOD EC;8P
Adder
7.239
274736ELWOOD EC;9P
Adder
7.239
972259AH1-714 GEN
Adder
8.385
24802606KYGER 1HP
50/50
4.51
24802706KYGER 1LP
50/50
2.645
24803506KYGER 5LP
50/50
2.583
971985AH1-537 GEN
Solar/Wind Harmer
56.698
253433AC1-085 GEN1
Solar/Wind Harmer
7.414
253432AC1-085 GEN2
Solar/Wind Harmer
0.373
270263AC1-001 GEN
Solar/Wind Harmer
1.45
25196408WSDLE3
Adder
11.623
270340AC2-060 GEN
Solar/Wind Harmer
3.884
253406AD2-031_GEN
Solar/Wind Harmer
1.593
25196108MFTGT2
Adder
1.88
25196108MFTGT2
Adder
1.746
972163AH1-664 GEN
Solar/Wind Harmer
12.044
972165AH1-665 GEN
Solar/Wind Harmer
9.636
339216AC1-074 GEN
Solar/Wind Harmer
1.864
270432AC2-029 GEN
Solar/Wind Harmer
7.644
253372AE2-315 SEC3
Adder
2.037
253372AE2-315 SEC3
Adder
2.037
25306009OHH W.
Adder
3.033
3429211JKCT 2G
Adder
10.852
241972AD1-140 GEN
Solar/Wind Harmer
4.019
253338AC1-165 GEN
Solar/Wind Harmer
0.945
253343AC1-166 GEN
Solar/Wind Harmer
0.945
270356AE2-297 GEN
Solar/Wind Harmer
3.987
971029AG2-637 GEN
Solar/Wind Harmer
12.539
270543AE2-219 C
Solar/Wind Harmer
7.986
247536S-71 GEN
Solar/Wind Harmer
3.092
964611AG1-324 GEN
Solar/Wind Harmer
2.831
961761AG1-017 GEN
Solar/Wind Harmer
0.309
945581AF1-223 GEN
Solar/Wind Harmer
3.114
945631AF1-228 GEN
Solar/Wind Harmer
3.07
958711AF2-162 GEN
Solar/Wind Harmer
0.655
943861AF1-054 GEN
Solar/Wind Harmer
2.451
943851AF1-053 GEN
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
1.202
24729505KEY G4
Adder
3.936
270291AC1-194 GEN
Solar/Wind Harmer
2.922
270444AC2-157 GEN1
Solar/Wind Harmer
3.091
270445AC2-157 GEN2
Solar/Wind Harmer
3.091
963791AG1-232 GEN
Solar/Wind Harmer
7.435
241955AC1-078 GEN
Solar/Wind Harmer
4.102
241973AD2-163_GEN1
Solar/Wind Harmer
1.085
241974AD2-163_GEN2
Solar/Wind Harmer
1.085
963841AG1-237 GEN
Solar/Wind Harmer
5.506
24386405FR-21G C
Solar/Wind Harmer
2.11
24387005FR-3G C
Solar/Wind Harmer
1.94
270071AF1-092 GEN
Solar/Wind Harmer
7.35
25322209TAIT E
Adder
9.892
253349AC2-067 GEN
Solar/Wind Harmer
2.068
253400AC2-068 GEN
Solar/Wind Harmer
0.832
25326109MON D
Adder
1.335
971125AH1-004 GEN
Solar/Wind Harmer
4.054
970107AG2-081 GEN
Solar/Wind Harmer
3.041
942891AE2-308 GEN
Solar/Wind Harmer
9.049
926881AC1-175 GEN
Solar/Wind Harmer
4.582
270383AD1-128 GEN
Solar/Wind Harmer
4.96
970883AG2-550 GEN
Solar/Wind Harmer
7.986
970885AG2-551 GEN
Solar/Wind Harmer
1.857
247621Y3-024
Adder
0.179
25326509SID D
Adder
0.961
964611AG1-324 GEN
Solar/Wind Harmer
0.38
270201AC2-176 GEN
Solar/Wind Harmer
3.708
964571AG1-320 GEN
Solar/Wind Harmer
5.837
971073AG2-665 GEN
Solar/Wind Harmer
5.557
970879AG2-548 GEN
Solar/Wind Harmer
0.808
24725505WLD G2 C
Solar/Wind Harmer
2.754
24699105WLD G1 C
Solar/Wind Harmer
2.722
253378AE2-206_GEN
Solar/Wind Harmer
2.463
270031AE2-169
Solar/Wind Harmer
5.579
270599AE1-208 GEN
Solar/Wind Harmer
5.579
944541AF1-119 GEN
Solar/Wind Harmer
2.712
960971AF2-388 GEN
Solar/Wind Harmer
7.079
942861AE2-305 GEN
Solar/Wind Harmer
4.965
970291AG2-192 GEN
Solar/Wind Harmer
0.823
970291AG2-192 GEN
Solar/Wind Harmer
0.265
942221AE2-234 GEN
Solar/Wind Harmer
2.13
339236AF1-050_GEN
Solar/Wind Harmer
1.062
945391AF1-204 GEN
Solar/Wind Harmer
7.777
339231AF1-038_GEN
Solar/Wind Harmer
1.01
927014AC1-188 GEN
Solar/Wind Harmer
0.86
964781AG1-341 GEN
Solar/Wind Harmer
5.607
253383AE2-342_GEN
Solar/Wind Harmer
0.463
970241AG2-163 GEN
Solar/Wind Harmer
12.901
971485AH1-239 GEN
Solar/Wind Harmer
3.962
24387305FR-4G C
Solar/Wind Harmer
2.492
966841AG1-555 GEN
Solar/Wind Harmer
1.232
966021AG1-471 GEN
Solar/Wind Harmer
2.631
276916AD2-100_GEN
Solar/Wind Harmer
10.179
276911AD2-131_GEN
Solar/Wind Harmer
2.057
276615X2-022 GEN
Solar/Wind Harmer
0.941
276838X2-022 GEN2
Solar/Wind Harmer
0.112
274880W4-005 GEN4
Solar/Wind Harmer
1.451
276174W4-005 GEN2
Solar/Wind Harmer
1.451
270180AB1-006 GEN1
Solar/Wind Harmer
3.414
24697605MDL-3G C
Solar/Wind Harmer
1.75
24755605MDL-5G
Solar/Wind Harmer
1.145
24697905MDL-4G C
Solar/Wind Harmer
1.089
270181AB1-006 GEN2
Solar/Wind Harmer
0.34
274674JOLIET 9 ;6U
Adder
6.773
274696ROCKY RD ;4P
Adder
4.997
274695ROCKY RD ;2P
Adder
4.881
274693ROCKY RD ;1P
Adder
4.833
274697ROCKY RD ;3P
Adder
1.326
274805UNIV PK N;1U
Adder
2.2
274808UNIV PK N;4U
Adder
2.186
274683WAUKEGAN ;8U
Adder
9.232
274683WAUKEGAN ;8U
Adder
7.782
274764LEE CO EC;5U
Adder
4.084
274765LEE CO EC;6U
Adder
4.084
274762LEE CO EC;3U
Adder
4.074
274763LEE CO EC;4U
Adder
4.036
237033AB1-150 GEN
Solar/Wind Helper
0.429
944221AF1-090 GEN
Solar/Wind Harmer
5.351
276763AC1-053 GEN1
Solar/Wind Harmer
1.897
276764AC1-053 GEN2
Solar/Wind Harmer
1.897
276668AB2-070 GEN1
Solar/Wind Harmer
1.062
276848AB2-070 GEN3
Solar/Wind Harmer
1.062
276849AB2-070 GEN2
Solar/Wind Harmer
1.062
946581AF1-322 GEN
Solar/Wind Harmer
4.858
24691005MDL-2G C
Solar/Wind Harmer
1.756
274731ELWOOD EC;2P
Adder
7.239
274733ELWOOD EC;3P
Adder
7.239
274735ELWOOD EC;4P
Adder
7.239
274728ELWOOD EC;5P
Adder
7.239
972228AH1-698 GEN2
Adder
1.631
972227AH1-698 GEN1
Adder
1.148
274800UNIV PARK;3U
Adder
2.561
274801UNIV PARK;4U
Adder
2.561
274675JOLIET 29;7U
Adder
13.475
274675JOLIET 29;7U
Adder
12.994
274687WILL CNTY;4U
Adder
12.271
274687WILL CNTY;4U
Adder
12.271
972037AH1-567 GEN1
Adder
0.08
274744AC1-111 GEN8
Adder
2.453
274746AC1-111 G10
Adder
2.453
274827FISK ;RP
Adder
3.404
972267AH1-718 GEN
Adder
1.824
972038AH1-567 GEN2
Adder
0.16
274676JOLIET 29;8U
Adder
12.994
274803UNIV PARK;6U
Adder
2.56
274826FISK ;BP
Adder
4.804
274814UNIV PK N;0U
Adder
2.215
274807UNIV PK N;3U
Adder
2.21
274811UNIV PK N;7U
Adder
2.195
274682WAUKEGAN ;7U
Adder
7.875
274760LEE CO EC;1U
Adder
4.074
274767LEE CO EC;8U
Adder
4.026
274724RIVER EC ;11
Adder
5.289
270330AC1-082 GEN2
Solar/Wind Helper
0.17
270329AC1-082 GEN1
Solar/Wind Helper
0.17
970781AG2-491 GEN
Solar/Wind Harmer
2.151
270209AC1-174_GEN
Solar/Wind Harmer
3.341
270437AC2-090 C
Solar/Wind Harmer
4.582
270239V3-007_GEN1
Solar/Wind Harmer
1.413
339211AE2-254 GEN
Solar/Wind Harmer
1.157
270005AE1-210 C O1
Solar/Wind Harmer
4.08
24728605AND G2
Adder
2.824
970825AG2-519 GEN
Solar/Wind Harmer
1.543
971073AG2-665 GEN
Solar/Wind Harmer
0.808
945371AF1-202 GEN
Solar/Wind Harmer
4.791
970653AG2-424 GEN
Solar/Wind Harmer
3.289
276903AD2-071 C
Solar/Wind Harmer
6.734
958861AF2-177 GEN
Solar/Wind Harmer
7.226
270594AE1-207 GEN
Solar/Wind Harmer
8.954
270032AE2-172
Solar/Wind Harmer
3.066
270024AE2-089 GEN
Solar/Wind Harmer
3.071
965651AG1-433 GEN
Solar/Wind Harmer
3.54
339241AF1-083 GEN
Solar/Wind Harmer
1.047
964901AG1-354 GEN
Solar/Wind Harmer
8.68
970091AG2-072 GEN
Adder
41.08
963741AG1-226 GEN
Solar/Wind Harmer
23.222
24385905FR-11G C
Solar/Wind Harmer
4.077
24386605FR-22G C
Solar/Wind Harmer
2.11
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
2.997
276686W4-005 GEN3
Solar/Wind Harmer
1.451
24791305MDL-5G
Solar/Wind Harmer
1.145
274732ELWOOD EC;7P
Adder
7.239
274674JOLIET 9 ;6U
Adder
6.773
274676JOLIET 29;8U
Adder
13.475
274802UNIV PARK;5U
Adder
2.56
274745AC1-111 GEN9
Adder
2.453
274812UNIV PK N;8U
Adder
2.195
274682WAUKEGAN ;7U
Adder
7.875
274828WAUKEGAN ;BP
Adder
4.839
274761LEE CO EC;2U
Adder
4.074
274766LEE CO EC;7U
Adder
4.026
274723RIVER EC ;12
Adder
7.842
960001AF2-291 GEN
Solar/Wind Helper
1.495
270331AC1-082 GEN3
Solar/Wind Helper
0.169
235780M24_1
Solar/Wind Helper
0.532
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.436
CBM West 1LTFEXP_CBM-W1->PJM
CBM
67.865
NYPJM->LTFIMP_NY
CLTF
1.649
LGEELTFEXP_LGEE->PJM
CLTF
5.838
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.827
MECLTFEXP_MEC->PJM
CLTF
7.138
SIGELTFEXP_SIGE->PJM
CLTF
0.35
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.263
LAGNLTFEXP_LAGN->PJM
CLTF
5.53
TVALTFEXP_TVA->PJM
CLTF
2.623
WECLTFEXP_WEC->PJM
CLTF
1.668
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.901
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#6156_05MARQUI 765_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6156_05MARQUI 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.75 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1859.53
MW Contribution:
6.35
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.479
24802806KYGER 2HP
50/50
4.462
24802906KYGER 2LP
50/50
2.619
25183008BIOENL
50/50
0.04
252509AD1-136 GEN
Solar/Wind Harmer
0.379
25183208HLCRTG
Solar/Wind Harmer
8.672
270269AC2-059
Solar/Wind Harmer
12.691
25194408D.CRK1
Adder
9.908
25194508D.CRK3
Adder
1.852
253415AE1-040 GEN
Solar/Wind Harmer
1.385
962581AG1-107 GEN
Solar/Wind Harmer
6.11
961491AF2-440 GEN
Solar/Wind Harmer
2.54
253370AE2-315 SEC1
Adder
2.137
972043AH1-570 GEN
Solar/Wind Harmer
2.652
972045AH1-571 GEN
Solar/Wind Harmer
2.122
25322209TAIT E
Adder
10.038
25322209TAIT E
Adder
9.812
253349AC2-067 GEN
Solar/Wind Harmer
2.05
253400AC2-068 GEN
Solar/Wind Harmer
0.824
971125AH1-004 GEN
Solar/Wind Harmer
4.03
970107AG2-081 GEN
Solar/Wind Harmer
3.023
25326109MON D
Adder
1.324
942891AE2-308 GEN
Solar/Wind Harmer
9.002
926881AC1-175 GEN
Solar/Wind Harmer
4.513
270383AD1-128 GEN
Solar/Wind Harmer
4.887
970883AG2-550 GEN
Solar/Wind Harmer
7.87
970885AG2-551 GEN
Solar/Wind Harmer
1.83
247621Y3-024
Adder
0.176
25326509SID D
Adder
0.951
964611AG1-324 GEN
Solar/Wind Harmer
0.374
270201AC2-176 GEN
Solar/Wind Harmer
3.648
964571AG1-320 GEN
Solar/Wind Harmer
5.767
971073AG2-665 GEN
Solar/Wind Harmer
5.548
970879AG2-548 GEN
Solar/Wind Harmer
0.806
24725505WLD G2 C
Solar/Wind Harmer
2.701
24699105WLD G1 C
Solar/Wind Harmer
2.67
253378AE2-206_GEN
Solar/Wind Harmer
2.436
270031AE2-169
Solar/Wind Harmer
5.48
270599AE1-208 GEN
Solar/Wind Harmer
5.48
944541AF1-119 GEN
Solar/Wind Harmer
2.663
960971AF2-388 GEN
Solar/Wind Harmer
6.95
942861AE2-305 GEN
Solar/Wind Harmer
4.917
24802606KYGER 1HP
50/50
4.511
24802706KYGER 1LP
50/50
2.645
24803506KYGER 5LP
50/50
2.583
971985AH1-537 GEN
Solar/Wind Harmer
56.568
253433AC1-085 GEN1
Solar/Wind Harmer
7.375
253432AC1-085 GEN2
Solar/Wind Harmer
0.371
270263AC1-001 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
11.529
270340AC2-060 GEN
Solar/Wind Harmer
3.869
253406AD2-031_GEN
Solar/Wind Harmer
1.584
25196108MFTGT2
Adder
1.862
25196108MFTGT2
Adder
1.729
972163AH1-664 GEN
Solar/Wind Harmer
11.991
972165AH1-665 GEN
Solar/Wind Harmer
9.592
339216AC1-074 GEN
Solar/Wind Harmer
1.851
270432AC2-029 GEN
Solar/Wind Harmer
7.618
253372AE2-315 SEC3
Adder
2.021
253372AE2-315 SEC3
Adder
2.021
25306009OHH W.
Adder
3.008
3429211JKCT 2G
Adder
10.797
241972AD1-140 GEN
Solar/Wind Harmer
3.986
253338AC1-165 GEN
Solar/Wind Harmer
0.939
253343AC1-166 GEN
Solar/Wind Harmer
0.939
270356AE2-297 GEN
Solar/Wind Harmer
3.929
971029AG2-637 GEN
Solar/Wind Harmer
12.368
270543AE2-219 C
Solar/Wind Harmer
7.87
247536S-71 GEN
Solar/Wind Harmer
3.045
964611AG1-324 GEN
Solar/Wind Harmer
2.784
961761AG1-017 GEN
Solar/Wind Harmer
0.304
945581AF1-223 GEN
Solar/Wind Harmer
3.06
945631AF1-228 GEN
Solar/Wind Harmer
3.043
958711AF2-162 GEN
Solar/Wind Harmer
0.643
943861AF1-054 GEN
Solar/Wind Harmer
2.427
943851AF1-053 GEN
Solar/Wind Harmer
1.173
970289AG2-191 GEN
Solar/Wind Harmer
1.176
24729505KEY G4
Adder
3.861
270291AC1-194 GEN
Solar/Wind Harmer
2.916
241955AC1-078 GEN
Solar/Wind Harmer
4.064
241973AD2-163_GEN1
Solar/Wind Harmer
1.073
241974AD2-163_GEN2
Solar/Wind Harmer
1.073
963791AG1-232 GEN
Solar/Wind Harmer
7.287
270444AC2-157 GEN1
Solar/Wind Harmer
2.98
270445AC2-157 GEN2
Solar/Wind Harmer
2.98
963841AG1-237 GEN
Solar/Wind Harmer
5.337
270071AF1-092 GEN
Solar/Wind Harmer
7.165
944221AF1-090 GEN
Solar/Wind Harmer
5.212
24386405FR-21G C
Solar/Wind Harmer
2.043
24387005FR-3G C
Solar/Wind Harmer
1.879
276763AC1-053 GEN1
Solar/Wind Harmer
1.847
276764AC1-053 GEN2
Solar/Wind Harmer
1.847
276668AB2-070 GEN1
Solar/Wind Harmer
1.034
276848AB2-070 GEN3
Solar/Wind Harmer
1.034
276849AB2-070 GEN2
Solar/Wind Harmer
1.034
946581AF1-322 GEN
Solar/Wind Harmer
4.702
24691005MDL-2G C
Solar/Wind Harmer
1.699
24803106KYGER 3LP
50/50
2.637
24803306KYGER 4LP
50/50
2.583
971191AH1-055 GEN
Solar/Wind Harmer
85.195
252507AC2-088 GEN
Solar/Wind Harmer
2.655
253317AC1-085 GEN4
Solar/Wind Harmer
11.619
946181AF1-283 GEN
Solar/Wind Harmer
18.042
252519AF1-045_GEN
Solar/Wind Harmer
5.038
25194608D.CRK4
Adder
2.154
252524AE2-267 GEN
Solar/Wind Harmer
2.058
25196608WSDLE5
Adder
11.2
958171AF2-111 GEN
Solar/Wind Harmer
32.628
253394AE2-221_GEN
Solar/Wind Harmer
5.885
270367AC2-061_GEN
Solar/Wind Harmer
3.949
270186AC1-089 GEN
Solar/Wind Harmer
7.462
972167AH1-666 GEN
Solar/Wind Harmer
9.768
25196008MFTGT1
Adder
1.636
339243AC2-075 GEN1
Solar/Wind Harmer
0.501
253303V4-073 C
Solar/Wind Harmer
0.124
253370AE2-315 SEC1
Adder
2.137
253371AE2-315 SEC2
Adder
2.021
960071AF2-298 GEN
Solar/Wind Harmer
1.535
3429391JKCT 9G
Adder
7.969
253325AC1-069 GEN
Solar/Wind Harmer
0.905
970093AG2-073 GEN
Solar/Wind Harmer
4.511
24379505HDWTR1G C
Solar/Wind Harmer
6.394
270240V3-007_GEN2
Solar/Wind Harmer
5.003
270518AE2-148 GEN
Solar/Wind Harmer
9.208
970455AG2-298 GEN
Solar/Wind Harmer
2.574
270004AE1-209 GEN
Solar/Wind Harmer
4.013
946031AF1-268 GEN
Solar/Wind Harmer
6.057
970825AG2-519 GEN
Solar/Wind Harmer
4.074
24728505AND G1
Adder
2.773
962031AG1-047 GEN
Solar/Wind Harmer
2.146
957741AF2-068 GEN
Solar/Wind Harmer
10.645
970879AG2-548 GEN
Solar/Wind Harmer
5.548
276820AF1-078_GEN
Solar/Wind Harmer
1.082
970653AG2-424 GEN
Solar/Wind Harmer
0.471
339206AE1-143 GEN
Solar/Wind Harmer
1.398
965461AG1-414 GEN
Solar/Wind Harmer
1.404
970289AG2-191 GEN
Solar/Wind Harmer
0.475
247642Z2-115 C
Solar/Wind Harmer
0.038
942051AE2-217 GEN
Solar/Wind Harmer
10.648
960801AF2-371 GEN
Solar/Wind Harmer
1.494
964871AG1-351 GEN
Solar/Wind Harmer
1.032
944531AF1-118 GEN
Solar/Wind Harmer
20.315
972273AH1-721 GEN
Adder
48.249
957541AF2-048 GEN
Solar/Wind Harmer
0.859
970193AG2-126 GEN
Solar/Wind Harmer
8.141
339255AE2-071 GEN
Solar/Wind Harmer
0.622
339250AF1-203 GEN
Solar/Wind Harmer
0.32
24386205FR-12G C
Solar/Wind Harmer
2.036
942481AE2-261 GEN
Solar/Wind Harmer
14.072
957381AF2-032 GEN
Solar/Wind Harmer
0.94
276785W4-005 GEN1
Solar/Wind Harmer
1.412
971993AH1-541 GEN
Solar/Wind Harmer
4.315
24690905MDL-1G C
Solar/Wind Harmer
3.689
270330AC1-082 GEN2
Solar/Wind Helper
0.169
270329AC1-082 GEN1
Solar/Wind Helper
0.169
970781AG2-491 GEN
Solar/Wind Harmer
2.082
24803406KYGER 5HP
50/50
4.427
24803206KYGER 4HP
50/50
4.417
253316AC1-085 GEN3
Solar/Wind Harmer
11.619
946171AF1-282 GEN
Solar/Wind Harmer
13.878
252516AE2-318_GEN
Solar/Wind Harmer
13.842
270273AD2-016 GEN
Solar/Wind Harmer
3.619
25196808ZIMRHP
Adder
103.16
252510AF1-249 C
Solar/Wind Harmer
0.548
25194608D.CRK4
Adder
2.154
253398AE2-221_GEN2
Solar/Wind Harmer
5.885
945681AF1-233 GEN
Solar/Wind Harmer
22.912
25196008MFTGT1
Adder
1.689
339221AD2-048_GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.137
253371AE2-315 SEC2
Adder
2.021
25326309TAIT D
Adder
1.127
270222AC2-111 GEN
Solar/Wind Harmer
4.52
944031AF1-071 GEN
Solar/Wind Harmer
1.017
943111AE2-339 GEN
Solar/Wind Harmer
0.883
3429421JKCT 10G
Adder
7.969
3429241JKCT 3G
Adder
10.939
253333AC1-068 GEN
Solar/Wind Harmer
0.905
942081AE2-220 GEN
Solar/Wind Harmer
5.172
270209AC1-174_GEN
Solar/Wind Harmer
3.291
270437AC2-090 C
Solar/Wind Harmer
4.513
270239V3-007_GEN1
Solar/Wind Harmer
1.391
339211AE2-254 GEN
Solar/Wind Harmer
1.15
270005AE1-210 C O1
Solar/Wind Harmer
4.013
970825AG2-519 GEN
Solar/Wind Harmer
1.517
24728605AND G2
Adder
2.773
971073AG2-665 GEN
Solar/Wind Harmer
0.806
970653AG2-424 GEN
Solar/Wind Harmer
3.256
945371AF1-202 GEN
Solar/Wind Harmer
4.707
276903AD2-071 C
Solar/Wind Harmer
6.601
958861AF2-177 GEN
Solar/Wind Harmer
7.096
270594AE1-207 GEN
Solar/Wind Harmer
8.773
270032AE2-172
Solar/Wind Harmer
3.005
270024AE2-089 GEN
Solar/Wind Harmer
3.017
965651AG1-433 GEN
Solar/Wind Harmer
3.475
339241AF1-083 GEN
Solar/Wind Harmer
1.04
964901AG1-354 GEN
Solar/Wind Harmer
8.626
970091AG2-072 GEN
Adder
38.834
963741AG1-226 GEN
Solar/Wind Harmer
22.53
24385905FR-11G C
Solar/Wind Harmer
3.949
24386605FR-22G C
Solar/Wind Harmer
2.043
965911AG1-460 GEN
Solar/Wind Harmer
0.657
276621W2-048 GEN
Solar/Wind Harmer
2.918
276686W4-005 GEN3
Solar/Wind Harmer
1.412
24791305MDL-5G
Solar/Wind Harmer
1.108
960001AF2-291 GEN
Solar/Wind Helper
1.492
270331AC1-082 GEN3
Solar/Wind Helper
0.168
235780M24_1
Solar/Wind Helper
0.525
970291AG2-192 GEN
Solar/Wind Harmer
0.805
970291AG2-192 GEN
Solar/Wind Harmer
0.259
942221AE2-234 GEN
Solar/Wind Harmer
2.089
339236AF1-050_GEN
Solar/Wind Harmer
1.055
339231AF1-038_GEN
Solar/Wind Harmer
1.008
927014AC1-188 GEN
Solar/Wind Harmer
0.859
945391AF1-204 GEN
Solar/Wind Harmer
7.563
964781AG1-341 GEN
Solar/Wind Harmer
5.576
253383AE2-342_GEN
Solar/Wind Harmer
0.458
970241AG2-163 GEN
Solar/Wind Harmer
12.517
971485AH1-239 GEN
Solar/Wind Harmer
3.96
966021AG1-471 GEN
Solar/Wind Harmer
2.631
24387305FR-4G C
Solar/Wind Harmer
2.413
966841AG1-555 GEN
Solar/Wind Harmer
1.193
276916AD2-100_GEN
Solar/Wind Harmer
9.913
276911AD2-131_GEN
Solar/Wind Harmer
2.003
276615X2-022 GEN
Solar/Wind Harmer
0.916
276838X2-022 GEN2
Solar/Wind Harmer
0.109
274880W4-005 GEN4
Solar/Wind Harmer
1.412
276174W4-005 GEN2
Solar/Wind Harmer
1.412
270180AB1-006 GEN1
Solar/Wind Harmer
3.305
24697605MDL-3G C
Solar/Wind Harmer
1.694
24755605MDL-5G
Solar/Wind Harmer
1.108
24697905MDL-4G C
Solar/Wind Harmer
1.055
270181AB1-006 GEN2
Solar/Wind Harmer
0.329
237033AB1-150 GEN
Solar/Wind Helper
0.424
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.383
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.406
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.825
NYPJM->LTFIMP_NY
CLTF
1.62
LGEELTFEXP_LGEE->PJM
CLTF
5.749
MECLTFEXP_MEC->PJM
CLTF
6.978
SIGELTFEXP_SIGE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.569
LAGNLTFEXP_LAGN->PJM
CLTF
5.54
TVALTFEXP_TVA->PJM
CLTF
2.651
WECLTFEXP_WEC->PJM
CLTF
1.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.817
AG2-052LTFEXP_AG2-052->PJM
LTF
0.106
AH1-155LTFEXP_AH1-155->PJM
LTF
0.159

Details for AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line l/o AEP_P4_#9758_05LEMASTER 138_A1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.84 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:280.08
MW Contribution:
78.78
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.81 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:280.02
MW Contribution:
78.78
Bus #Bus NameTypeMW Contribution
938711AE1-093 GEN
50/50
41.988
971073AG2-665 GEN
Solar/Wind Harmer
9.997
971073AG2-665 GEN
Solar/Wind Harmer
68.781
970879AG2-548 GEN
Solar/Wind Harmer
9.997
970879AG2-548 GEN
Solar/Wind Harmer
68.781
270291AC1-194 GEN
Solar/Wind Harmer
43.739
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.071
NYPJM->LTFIMP_NY
CLTF
0.015
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.048
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016

Details for AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line l/o AEP_P4_#11182_05LEMASTER 138_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.84 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:280.08
MW Contribution:
78.78
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.81 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:280.02
MW Contribution:
78.78
Bus #Bus NameTypeMW Contribution
938711AE1-093 GEN
50/50
41.988
971073AG2-665 GEN
Solar/Wind Harmer
9.997
971073AG2-665 GEN
Solar/Wind Harmer
68.781
970879AG2-548 GEN
Solar/Wind Harmer
9.997
970879AG2-548 GEN
Solar/Wind Harmer
68.781
270291AC1-194 GEN
Solar/Wind Harmer
43.739
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.071
NYPJM->LTFIMP_NY
CLTF
0.015
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.048
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 1           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 2           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AEP_P4_#3149_05HANG R 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242924 TO BUS 242927 CKT 1   /*05HANG R     765.0 - 05MARQUI     765.0
 OPEN BRANCH FROM BUS 242927 TO BUS 242938 CKT 1   /*05MARQUI     765.0 - 05MARQUI     345.0
END
CONTINGENCY 'AEP_P2-2_#6156_05MARQUI 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 242927 CKT 1   /*05HANG R     765.0 - 05MARQUI     765.0
 OPEN BRANCH FROM BUS 242927 TO BUS 242938 CKT 1   /*05MARQUI     765.0 - 05MARQUI     345.0
END
CONTINGENCY 'AEP_P4_#9758_05LEMASTER 138_A1_SRT-A'
 OPEN BRANCH FROM BUS 242812 TO BUS 244283 CKT Z1   /*05MINERAL8   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 244283 CKT 1    /*05BOLINSMLSS 138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 246684 CKT Z1   /*05BOLINSMLSS 138.0 - 05BOLINS ML8 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 247791 CKT 1    /*05BOLINSMLSS 138.0 - 05ELK        138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244283 CKT 1    /*05LEMASTER   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244569 CKT Z1   /*05LEMASTER   138.0 - 05LEMAST_CAP 138.0
END
CONTINGENCY 'AEP_P4_#11182_05LEMASTER 138_A_SRT-A'
 OPEN BRANCH FROM BUS 242812 TO BUS 244283 CKT Z1   /*05MINERAL8   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 244283 CKT 1    /*05BOLINSMLSS 138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 246684 CKT Z1   /*05BOLINSMLSS 138.0 - 05BOLINS ML8 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 247791 CKT 1    /*05BOLINSMLSS 138.0 - 05ELK        138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244283 CKT 1    /*05LEMASTER   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 247097 CKT Z1   /*05LEMASTER   138.0 - 05LEMASTERT1 138.0
 REMOVE LOAD D1 FROM BUS 247097                     /*05LEMASTERT1 138.0
END
290610 to 242512 ckt Z1
290614 to 242515 ckt 1
242514 to 290610 ckt 1
248005 to 242528 ckt 1
970878 to 243492 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC123.53 %3792.0B4684.3
9.36
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC123.51 %3792.0B4683.54
9.36
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC123.51 %3792.0B4683.44
9.39
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC122.65 %3792.0B4650.99
6.41
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC122.64 %3792.0B4650.57
6.41
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC139.19 %3792.0B5278.17
9.21
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC139.17 %3792.0B5277.43
9.21
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC138.98 %3792.0B5270.18
9.29
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC138.45 %3792.0B5250.02
6.31
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC138.41 %3792.0B5248.4
6.31
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.25 %3729.0B5006.21
10.04
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.4 %3729.0B4974.31
10.03
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC133.01 %3729.0B4959.97
10.04
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC133.01 %3729.0B4959.97
10.04
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.87 %3729.0B4917.49
6.87
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.69 %3729.0B4873.53
10.12
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.24 %3729.0B4632.89
6.63
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC101.35 %4000.0B4053.82
9.17
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC101.34 %4000.0B4053.72
9.18
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC101.32 %4000.0B4052.99
9.17
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-2_MP-500-028_SRT-A
SingleAC100.79 %4000.0B4031.79
6.28
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-3_MP-765-502T_SRT-A
SingleAC100.79 %4000.0B4031.62
6.28
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
5.75
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC115.66 %3610.0B4175.28
8.46
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC115.4 %3610.0B4165.98
8.42
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC115.26 %3610.0B4160.96
8.4
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC114.94 %3610.0B4149.41
8.4
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC135.56 %3792.0B5140.38
10.04
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC134.72 %3792.0B5108.61
10.03
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC134.34 %3792.0B5094.21
10.04
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC134.34 %3792.0B5094.21
10.04
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC133.22 %3792.0B5051.83
6.87
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC132.01 %3792.0B5005.84
10.12
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.57 %3792.0B4761.71
6.63
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC117.27 %5523.0B6477.04
13.35
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC116.4 %5523.0B6428.58
9.15
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.72 %5523.0B6225.55
13.48
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC111.96 %5523.0B6183.32
10.22
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC109.18 %4558.0A4976.63
7.17
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.41 %5523.0B5987.66
12.28
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.46 %5523.0B5935.05
10.37
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.76 %5523.0B5896.19
8.41
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC105.86 %5523.0B5846.6
11.98
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC101.88 %5523.0B5626.94
12.09

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.53 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4684.3
MW Contribution:
9.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270459AD2-067 GEN
Solar/Wind Harmer
8.564
961821AG1-024 GEN
Solar/Wind Harmer
8.695
270291AC1-194 GEN
Solar/Wind Harmer
5.184
270432AC2-029 GEN
Solar/Wind Harmer
7.128
270263AC1-001 GEN
Solar/Wind Harmer
1.061
241955AC1-078 GEN
Solar/Wind Harmer
7.548
940611AE2-048 GEN
Solar/Wind Harmer
22.264
941391AE2-136 GEN
Solar/Wind Harmer
11.537
945631AF1-228 GEN
Solar/Wind Harmer
4.727
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253338AC1-165 GEN
Solar/Wind Harmer
1.085
253343AC1-166 GEN
Solar/Wind Harmer
1.085
943861AF1-054 GEN
Solar/Wind Harmer
3.855
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
17.842
270340AC2-060 GEN
Solar/Wind Harmer
3.013
241972AD1-140 GEN
Solar/Wind Harmer
4.405
253406AD2-031_GEN
Solar/Wind Harmer
1.251
253433AC1-085 GEN1
Solar/Wind Harmer
5.175
253432AC1-085 GEN2
Solar/Wind Harmer
0.26
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270223U2-072_GEN1
Solar/Wind Harmer
1.918
270224U2-072_GEN2
Solar/Wind Harmer
1.918
270227U2-072_GEN3
Solar/Wind Harmer
1.918
270228U2-072_GEN4
Solar/Wind Harmer
1.918
270231U2-072_GEN5
Solar/Wind Harmer
1.918
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
8.028
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
14.154
972163AH1-664 GEN
Solar/Wind Harmer
9.428
972165AH1-665 GEN
Solar/Wind Harmer
7.543
270543AE2-219 C
Solar/Wind Harmer
9.417
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
3.803
958711AF2-162 GEN
Solar/Wind Harmer
0.951
945581AF1-223 GEN
Solar/Wind Harmer
4.258
961761AG1-017 GEN
Solar/Wind Harmer
0.401
964611AG1-324 GEN
Solar/Wind Harmer
3.657
270356AE2-297 GEN
Solar/Wind Harmer
4.321
270071AF1-092 GEN
Solar/Wind Harmer
14.041
970289AG2-191 GEN
Solar/Wind Harmer
1.776
963791AG1-232 GEN
Solar/Wind Harmer
12.58
959331AF2-224 GEN
Solar/Wind Harmer
9.303
247521TR3_G114
Solar/Wind Harmer
3.113
270191TR4_S_V150
Solar/Wind Harmer
2.777
965051AG1-369 GEN
Solar/Wind Harmer
4.624
965041AG1-368 GEN
Solar/Wind Harmer
9.252
957201AF2-014 GEN
Solar/Wind Harmer
4.187
270435AC2-044 GEN
Solar/Wind Harmer
1.847
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
35.963
970149AG2-104 GEN
Solar/Wind Harmer
22.207
970155AG2-107 GEN
Solar/Wind Harmer
15.681
960001AF2-291 GEN
Solar/Wind Harmer
3.191
270510AE1-227 GEN1
Solar/Wind Harmer
2.61
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
270520AE2-214 GEN
Solar/Wind Harmer
6.192
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
2.704
972203AH1-686 GEN
Adder
2.339
270286AF1-227 GEN2
Solar/Wind Harmer
2.112
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
1.046
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
4.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.153
946171AF1-282 GEN
Solar/Wind Harmer
9.738
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
1.175
270578AF1-285 GEN2
Solar/Wind Harmer
1.175
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
9.663
252510AF1-249 C
Solar/Wind Harmer
0.402
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
3.069
270485AE1-090_GEN
Solar/Wind Harmer
0.58
270222AC2-111 GEN
Solar/Wind Harmer
4.248
944031AF1-071 GEN
Solar/Wind Harmer
0.956
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
17.8
971995AH1-542 GEN
Solar/Wind Harmer
10.357
942081AE2-220 GEN
Solar/Wind Harmer
6.014
270209AC1-174_GEN
Solar/Wind Harmer
3.827
270437AC2-090 C
Solar/Wind Harmer
5.249
270239V3-007_GEN1
Solar/Wind Harmer
1.618
965651AG1-433 GEN
Solar/Wind Harmer
5.136
958861AF2-177 GEN
Solar/Wind Harmer
10.268
945371AF1-202 GEN
Solar/Wind Harmer
6.551
270005AE1-210 C O1
Solar/Wind Harmer
5.125
970825AG2-519 GEN
Solar/Wind Harmer
1.966
270024AE2-089 GEN
Solar/Wind Harmer
4.385
270594AE1-207 GEN
Solar/Wind Harmer
12.702
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
9.334
965011AG1-365 GEN
Solar/Wind Harmer
9.303
965421AG1-410 GEN
Solar/Wind Harmer
27.72
246936BC-WTG1
Solar/Wind Harmer
3.612
270489AE1-102 GEN1
Solar/Wind Harmer
1.2
24728605AND G2
Adder
3.541
24639705ELKHART HY
Adder
0.141
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274745AC1-111 GEN9
Adder
5.047
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
35.963
970153AG2-106 GEN
Solar/Wind Harmer
15.681
270512AE1-227 GEN2
Solar/Wind Harmer
2.215
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
971191AH1-055 GEN
Solar/Wind Harmer
19.337
957541AF2-048 GEN
Solar/Wind Harmer
1.627
961921AG1-034 GEN
Solar/Wind Harmer
13.042
970879AG2-548 GEN
Solar/Wind Harmer
8.168
960801AF2-371 GEN
Solar/Wind Harmer
2.586
964871AG1-351 GEN
Solar/Wind Harmer
1.786
270284AF1-227 GEN1
Solar/Wind Harmer
5.709
270287AF1-227 GEN3
Solar/Wind Harmer
2.112
942051AE2-217 GEN
Solar/Wind Harmer
18.072
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
1.046
270518AE2-148 GEN
Solar/Wind Harmer
12.072
270367AC2-061_GEN
Solar/Wind Harmer
3.102
253394AE2-221_GEN
Solar/Wind Harmer
4.42
253317AC1-085 GEN4
Solar/Wind Harmer
8.153
946181AF1-283 GEN
Solar/Wind Harmer
12.659
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
942871AE2-306 GEN
Solar/Wind Harmer
0.881
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
5.927
960071AF2-298 GEN
Solar/Wind Harmer
1.467
252507AC2-088 GEN
Solar/Wind Harmer
1.731
252519AF1-045_GEN
Solar/Wind Harmer
3.517
276820AF1-078_GEN
Solar/Wind Harmer
1.537
252524AE2-267 GEN
Solar/Wind Harmer
1.516
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
7.557
958171AF2-111 GEN
Solar/Wind Harmer
23.611
944531AF1-118 GEN
Solar/Wind Harmer
32.926
24379505HDWTR1G C
Solar/Wind Harmer
7.436
270240V3-007_GEN2
Solar/Wind Harmer
5.818
270004AE1-209 GEN
Solar/Wind Harmer
5.125
962031AG1-047 GEN
Solar/Wind Harmer
2.835
957741AF2-068 GEN
Solar/Wind Harmer
14.065
946031AF1-268 GEN
Solar/Wind Harmer
7.782
970825AG2-519 GEN
Solar/Wind Harmer
5.279
965461AG1-414 GEN
Solar/Wind Harmer
2.119
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.06
270043AE2-236 GEN
Solar/Wind Harmer
5.125
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
4.626
246938BC-WTG3
Solar/Wind Harmer
3.674
270491AE1-102 GEN2
Solar/Wind Harmer
1.2
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
3.079
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
274682WAUKEGAN ;7U
Adder
16.174
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
3.759
270471AD2-092_GEN
Solar/Wind Harmer
3.759
270054AF2-122 C O1
Solar/Wind Harmer
3.36
927014AC1-188 GEN
Solar/Wind Harmer
1.627
946101AF1-275 GEN
Solar/Wind Harmer
1.548
971073AG2-665 GEN
Solar/Wind Harmer
8.168
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
9.486
253383AE2-342_GEN
Solar/Wind Harmer
0.888
942861AE2-305 GEN
Solar/Wind Harmer
7.811
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253415AE1-040 GEN
Solar/Wind Harmer
1.12
962581AG1-107 GEN
Solar/Wind Harmer
4.922
961491AF2-440 GEN
Solar/Wind Harmer
2.045
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
20.019
25183208HLCRTG
Solar/Wind Harmer
5.858
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.247
253349AC2-067 GEN
Solar/Wind Harmer
1.965
253400AC2-068 GEN
Solar/Wind Harmer
0.79
253378AE2-206_GEN
Solar/Wind Harmer
3.461
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
6.668
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
9.417
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
5.743
926881AC1-175 GEN
Solar/Wind Harmer
5.249
944541AF1-119 GEN
Solar/Wind Harmer
3.934
960971AF2-388 GEN
Solar/Wind Harmer
10.271
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
4.819
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
7.629
270599AE1-208 GEN
Solar/Wind Harmer
7.629
942221AE2-234 GEN
Solar/Wind Harmer
3.273
970291AG2-192 GEN
Solar/Wind Harmer
1.215
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
3.711
24699105WLD G1 C
Solar/Wind Harmer
3.668
270246TR4_N_V150
Solar/Wind Harmer
0.788
270247TR4_N_V136
Solar/Wind Harmer
0.788
970349AG2-230 GEN
Solar/Wind Harmer
13.877
246937BC-WTG2
Solar/Wind Harmer
3.612
247620Y3-023
Adder
0.422
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274674JOLIET 9 ;6U
Adder
13.943
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
945421AF1-207 GEN
Solar/Wind Harmer
9.897
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4683.54
MW Contribution:
9.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270459AD2-067 GEN
Solar/Wind Harmer
8.564
961821AG1-024 GEN
Solar/Wind Harmer
8.695
270291AC1-194 GEN
Solar/Wind Harmer
5.184
270432AC2-029 GEN
Solar/Wind Harmer
7.128
270263AC1-001 GEN
Solar/Wind Harmer
1.061
241955AC1-078 GEN
Solar/Wind Harmer
7.548
940611AE2-048 GEN
Solar/Wind Harmer
22.264
941391AE2-136 GEN
Solar/Wind Harmer
11.537
945631AF1-228 GEN
Solar/Wind Harmer
4.727
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253338AC1-165 GEN
Solar/Wind Harmer
1.085
253343AC1-166 GEN
Solar/Wind Harmer
1.085
943861AF1-054 GEN
Solar/Wind Harmer
3.855
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
17.842
270340AC2-060 GEN
Solar/Wind Harmer
3.013
241972AD1-140 GEN
Solar/Wind Harmer
4.405
253406AD2-031_GEN
Solar/Wind Harmer
1.251
253433AC1-085 GEN1
Solar/Wind Harmer
5.175
253432AC1-085 GEN2
Solar/Wind Harmer
0.26
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270223U2-072_GEN1
Solar/Wind Harmer
1.918
270224U2-072_GEN2
Solar/Wind Harmer
1.918
270227U2-072_GEN3
Solar/Wind Harmer
1.918
270228U2-072_GEN4
Solar/Wind Harmer
1.918
270231U2-072_GEN5
Solar/Wind Harmer
1.918
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
8.028
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
14.154
972163AH1-664 GEN
Solar/Wind Harmer
9.428
972165AH1-665 GEN
Solar/Wind Harmer
7.543
270543AE2-219 C
Solar/Wind Harmer
9.417
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
3.803
958711AF2-162 GEN
Solar/Wind Harmer
0.951
945581AF1-223 GEN
Solar/Wind Harmer
4.258
961761AG1-017 GEN
Solar/Wind Harmer
0.401
964611AG1-324 GEN
Solar/Wind Harmer
3.657
270356AE2-297 GEN
Solar/Wind Harmer
4.321
270071AF1-092 GEN
Solar/Wind Harmer
14.041
970289AG2-191 GEN
Solar/Wind Harmer
1.776
963791AG1-232 GEN
Solar/Wind Harmer
12.58
959331AF2-224 GEN
Solar/Wind Harmer
9.303
247521TR3_G114
Solar/Wind Harmer
3.113
270191TR4_S_V150
Solar/Wind Harmer
2.777
965051AG1-369 GEN
Solar/Wind Harmer
4.624
965041AG1-368 GEN
Solar/Wind Harmer
9.252
957201AF2-014 GEN
Solar/Wind Harmer
4.187
270435AC2-044 GEN
Solar/Wind Harmer
1.847
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
35.963
970149AG2-104 GEN
Solar/Wind Harmer
22.207
970155AG2-107 GEN
Solar/Wind Harmer
15.681
960001AF2-291 GEN
Solar/Wind Harmer
3.191
270510AE1-227 GEN1
Solar/Wind Harmer
2.61
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
270520AE2-214 GEN
Solar/Wind Harmer
6.192
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
2.704
972203AH1-686 GEN
Adder
2.339
270286AF1-227 GEN2
Solar/Wind Harmer
2.112
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
1.046
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
4.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.153
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
35.963
970153AG2-106 GEN
Solar/Wind Harmer
15.681
270512AE1-227 GEN2
Solar/Wind Harmer
2.215
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
971191AH1-055 GEN
Solar/Wind Harmer
19.337
957541AF2-048 GEN
Solar/Wind Harmer
1.627
961921AG1-034 GEN
Solar/Wind Harmer
13.042
970879AG2-548 GEN
Solar/Wind Harmer
8.168
960801AF2-371 GEN
Solar/Wind Harmer
2.586
964871AG1-351 GEN
Solar/Wind Harmer
1.786
270284AF1-227 GEN1
Solar/Wind Harmer
5.709
270287AF1-227 GEN3
Solar/Wind Harmer
2.112
942051AE2-217 GEN
Solar/Wind Harmer
18.072
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
1.046
270518AE2-148 GEN
Solar/Wind Harmer
12.072
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
3.759
270471AD2-092_GEN
Solar/Wind Harmer
3.759
270054AF2-122 C O1
Solar/Wind Harmer
3.36
927014AC1-188 GEN
Solar/Wind Harmer
1.627
946101AF1-275 GEN
Solar/Wind Harmer
1.548
971073AG2-665 GEN
Solar/Wind Harmer
8.168
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
9.486
253383AE2-342_GEN
Solar/Wind Harmer
0.888
942861AE2-305 GEN
Solar/Wind Harmer
7.811
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253415AE1-040 GEN
Solar/Wind Harmer
1.12
962581AG1-107 GEN
Solar/Wind Harmer
4.922
961491AF2-440 GEN
Solar/Wind Harmer
2.045
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
20.019
25183208HLCRTG
Solar/Wind Harmer
5.858
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.247
253349AC2-067 GEN
Solar/Wind Harmer
1.965
253400AC2-068 GEN
Solar/Wind Harmer
0.79
253378AE2-206_GEN
Solar/Wind Harmer
3.461
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
6.668
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
9.417
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
5.743
926881AC1-175 GEN
Solar/Wind Harmer
5.249
944541AF1-119 GEN
Solar/Wind Harmer
3.934
960971AF2-388 GEN
Solar/Wind Harmer
10.271
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
4.819
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
7.629
270599AE1-208 GEN
Solar/Wind Harmer
7.629
942221AE2-234 GEN
Solar/Wind Harmer
3.273
970291AG2-192 GEN
Solar/Wind Harmer
1.215
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
3.711
24699105WLD G1 C
Solar/Wind Harmer
3.668
270246TR4_N_V150
Solar/Wind Harmer
0.788
270247TR4_N_V136
Solar/Wind Harmer
0.788
970349AG2-230 GEN
Solar/Wind Harmer
13.877
246937BC-WTG2
Solar/Wind Harmer
3.612
247620Y3-023
Adder
0.422
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274674JOLIET 9 ;6U
Adder
13.943
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
945421AF1-207 GEN
Solar/Wind Harmer
9.897
946171AF1-282 GEN
Solar/Wind Harmer
9.738
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
1.175
270578AF1-285 GEN2
Solar/Wind Harmer
1.175
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
9.663
252510AF1-249 C
Solar/Wind Harmer
0.402
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
3.069
270485AE1-090_GEN
Solar/Wind Harmer
0.58
270222AC2-111 GEN
Solar/Wind Harmer
4.248
944031AF1-071 GEN
Solar/Wind Harmer
0.956
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
17.8
971995AH1-542 GEN
Solar/Wind Harmer
10.357
942081AE2-220 GEN
Solar/Wind Harmer
6.014
270209AC1-174_GEN
Solar/Wind Harmer
3.827
270437AC2-090 C
Solar/Wind Harmer
5.249
270239V3-007_GEN1
Solar/Wind Harmer
1.618
965651AG1-433 GEN
Solar/Wind Harmer
5.136
958861AF2-177 GEN
Solar/Wind Harmer
10.268
945371AF1-202 GEN
Solar/Wind Harmer
6.551
270005AE1-210 C O1
Solar/Wind Harmer
5.125
970825AG2-519 GEN
Solar/Wind Harmer
1.966
270024AE2-089 GEN
Solar/Wind Harmer
4.385
270594AE1-207 GEN
Solar/Wind Harmer
12.702
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
9.334
965011AG1-365 GEN
Solar/Wind Harmer
9.303
965421AG1-410 GEN
Solar/Wind Harmer
27.72
246936BC-WTG1
Solar/Wind Harmer
3.612
270489AE1-102 GEN1
Solar/Wind Harmer
1.2
24728605AND G2
Adder
3.541
24639705ELKHART HY
Adder
0.141
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274745AC1-111 GEN9
Adder
5.047
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
270367AC2-061_GEN
Solar/Wind Harmer
3.102
253394AE2-221_GEN
Solar/Wind Harmer
4.42
253317AC1-085 GEN4
Solar/Wind Harmer
8.153
946181AF1-283 GEN
Solar/Wind Harmer
12.659
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
942871AE2-306 GEN
Solar/Wind Harmer
0.881
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
5.927
960071AF2-298 GEN
Solar/Wind Harmer
1.467
252507AC2-088 GEN
Solar/Wind Harmer
1.731
252519AF1-045_GEN
Solar/Wind Harmer
3.517
276820AF1-078_GEN
Solar/Wind Harmer
1.537
252524AE2-267 GEN
Solar/Wind Harmer
1.516
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
7.557
958171AF2-111 GEN
Solar/Wind Harmer
23.611
944531AF1-118 GEN
Solar/Wind Harmer
32.926
24379505HDWTR1G C
Solar/Wind Harmer
7.436
270240V3-007_GEN2
Solar/Wind Harmer
5.818
270004AE1-209 GEN
Solar/Wind Harmer
5.125
962031AG1-047 GEN
Solar/Wind Harmer
2.835
957741AF2-068 GEN
Solar/Wind Harmer
14.065
946031AF1-268 GEN
Solar/Wind Harmer
7.782
970825AG2-519 GEN
Solar/Wind Harmer
5.279
965461AG1-414 GEN
Solar/Wind Harmer
2.119
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.06
270043AE2-236 GEN
Solar/Wind Harmer
5.125
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
4.626
246938BC-WTG3
Solar/Wind Harmer
3.674
270491AE1-102 GEN2
Solar/Wind Harmer
1.2
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
3.079
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
274682WAUKEGAN ;7U
Adder
16.174
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4683.44
MW Contribution:
9.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270459AD2-067 GEN
Solar/Wind Harmer
8.603
961821AG1-024 GEN
Solar/Wind Harmer
8.735
270291AC1-194 GEN
Solar/Wind Harmer
5.205
270432AC2-029 GEN
Solar/Wind Harmer
7.158
270263AC1-001 GEN
Solar/Wind Harmer
1.066
241955AC1-078 GEN
Solar/Wind Harmer
7.581
940611AE2-048 GEN
Solar/Wind Harmer
22.381
941391AE2-136 GEN
Solar/Wind Harmer
11.597
945631AF1-228 GEN
Solar/Wind Harmer
4.748
241973AD2-163_GEN1
Solar/Wind Harmer
1.995
241974AD2-163_GEN2
Solar/Wind Harmer
1.995
253338AC1-165 GEN
Solar/Wind Harmer
1.089
253343AC1-166 GEN
Solar/Wind Harmer
1.089
943861AF1-054 GEN
Solar/Wind Harmer
3.872
943851AF1-053 GEN
Solar/Wind Harmer
1.871
971985AH1-537 GEN
Solar/Wind Harmer
17.911
270340AC2-060 GEN
Solar/Wind Harmer
3.025
241972AD1-140 GEN
Solar/Wind Harmer
4.424
253406AD2-031_GEN
Solar/Wind Harmer
1.256
253433AC1-085 GEN1
Solar/Wind Harmer
5.195
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
253372AE2-315 SEC3
Adder
1.85
253372AE2-315 SEC3
Adder
1.85
270223U2-072_GEN1
Solar/Wind Harmer
1.927
270224U2-072_GEN2
Solar/Wind Harmer
1.927
270227U2-072_GEN3
Solar/Wind Harmer
1.927
270228U2-072_GEN4
Solar/Wind Harmer
1.927
270231U2-072_GEN5
Solar/Wind Harmer
1.927
270578AF1-285 GEN2
Solar/Wind Harmer
0.454
25306009OHH W.
Adder
2.806
25196408WSDLE3
Adder
8.526
25196308WSDLE2
Adder
8.452
25196208WSDLE1
Adder
8.431
25196708WSDLE6
Adder
8.409
25196508WSDLE4
Adder
8.198
270302AB2-170 GEN
Solar/Wind Harmer
8.066
25196108MFTGT2
Adder
1.464
25196108MFTGT2
Adder
1.359
971029AG2-637 GEN
Solar/Wind Harmer
14.212
972163AH1-664 GEN
Solar/Wind Harmer
9.464
972165AH1-665 GEN
Solar/Wind Harmer
7.571
270543AE2-219 C
Solar/Wind Harmer
9.456
24729505KEY G4
Adder
6.127
247536S-71 GEN
Solar/Wind Harmer
3.819
958711AF2-162 GEN
Solar/Wind Harmer
0.955
945581AF1-223 GEN
Solar/Wind Harmer
4.276
961761AG1-017 GEN
Solar/Wind Harmer
0.403
964611AG1-324 GEN
Solar/Wind Harmer
3.672
270356AE2-297 GEN
Solar/Wind Harmer
4.339
270071AF1-092 GEN
Solar/Wind Harmer
14.1
970289AG2-191 GEN
Solar/Wind Harmer
1.783
963791AG1-232 GEN
Solar/Wind Harmer
12.634
959331AF2-224 GEN
Solar/Wind Harmer
9.345
247521TR3_G114
Solar/Wind Harmer
3.127
270191TR4_S_V150
Solar/Wind Harmer
2.79
965051AG1-369 GEN
Solar/Wind Harmer
4.645
965041AG1-368 GEN
Solar/Wind Harmer
9.293
957201AF2-014 GEN
Solar/Wind Harmer
4.207
270435AC2-044 GEN
Solar/Wind Harmer
1.855
274775LINCOLN ;6U
Adder
7.721
274776LINCOLN ;7U
Adder
7.721
274777LINCOLN ;8U
Adder
7.721
972037AH1-567 GEN1
Adder
0.167
972228AH1-698 GEN2
Adder
3.376
972227AH1-698 GEN1
Adder
2.377
274827FISK ;RP
Adder
7.071
274800UNIV PARK;3U
Adder
5.313
274801UNIV PARK;4U
Adder
5.313
274687WILL CNTY;4U
Adder
25.419
274687WILL CNTY;4U
Adder
25.419
274728ELWOOD EC;5P
Adder
14.948
274731ELWOOD EC;2P
Adder
14.948
274733ELWOOD EC;3P
Adder
14.948
274735ELWOOD EC;4P
Adder
14.948
274675JOLIET 29;7U
Adder
27.901
274675JOLIET 29;7U
Adder
26.905
274744AC1-111 GEN8
Adder
5.067
274746AC1-111 G10
Adder
5.067
23750701CROSSCHOOL
Solar/Wind Helper
1.353
238118U2-030_1
Solar/Wind Helper
0.311
238169AE2-226 GEN1
Solar/Wind Helper
0.61
238170AE2-226 GEN2
Solar/Wind Helper
0.61
23750501ELLIOTTS
Solar/Wind Helper
0.612
23779801AA1-109
Solar/Wind Helper
0.169
3138216PACIFIC
Solar/Wind Helper
0.038
237025AB1-124 C
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.059
970031AG2-029 GEN
Solar/Wind Harmer
4.035
23684101S70BUS1
50/50
0.296
24318905MLG2
50/50
4.853
270349AD2-093_GEN
Solar/Wind Harmer
3.775
270471AD2-092_GEN
Solar/Wind Harmer
3.775
270054AF2-122 C O1
Solar/Wind Harmer
3.376
927014AC1-188 GEN
Solar/Wind Harmer
1.634
946101AF1-275 GEN
Solar/Wind Harmer
1.555
971073AG2-665 GEN
Solar/Wind Harmer
8.201
970879AG2-548 GEN
Solar/Wind Harmer
1.192
270269AC2-059
Solar/Wind Harmer
9.525
253383AE2-342_GEN
Solar/Wind Harmer
0.892
942861AE2-305 GEN
Solar/Wind Harmer
7.845
24723005RIVRG1
Adder
18.832
24723105RIVRG2
Adder
18.832
253415AE1-040 GEN
Solar/Wind Harmer
1.125
962581AG1-107 GEN
Solar/Wind Harmer
4.941
961491AF2-440 GEN
Solar/Wind Harmer
2.053
25326109MON D
Adder
1.285
253370AE2-315 SEC1
Adder
1.955
25322209TAIT E
Adder
9.512
25322209TAIT E
Adder
9.298
972159AH1-661 GEN
Adder
0.971
938701AE1-092 GEN
Solar/Wind Harmer
20.114
25183208HLCRTG
Solar/Wind Harmer
5.882
252509AD1-136 GEN
Solar/Wind Harmer
0.248
253349AC2-067 GEN
Solar/Wind Harmer
1.973
253400AC2-068 GEN
Solar/Wind Harmer
0.793
253378AE2-206_GEN
Solar/Wind Harmer
3.476
25194408D.CRK1
Adder
7.308
25194508D.CRK3
Adder
1.366
270462AD2-086
Solar/Wind Harmer
6.699
25326509SID D
Adder
1.267
24728805RICHG1
Adder
3.578
24728905RICHG2
Adder
3.578
970883AG2-550 GEN
Solar/Wind Harmer
9.456
970885AG2-551 GEN
Solar/Wind Harmer
2.199
270383AD1-128 GEN
Solar/Wind Harmer
5.766
926881AC1-175 GEN
Solar/Wind Harmer
5.27
944541AF1-119 GEN
Solar/Wind Harmer
3.951
960971AF2-388 GEN
Solar/Wind Harmer
10.314
247621Y3-024
Adder
0.227
270201AC2-176 GEN
Solar/Wind Harmer
4.839
964611AG1-324 GEN
Solar/Wind Harmer
0.493
270031AE2-169
Solar/Wind Harmer
7.66
270599AE1-208 GEN
Solar/Wind Harmer
7.66
942221AE2-234 GEN
Solar/Wind Harmer
3.287
970291AG2-192 GEN
Solar/Wind Harmer
1.22
970291AG2-192 GEN
Solar/Wind Harmer
0.393
24725505WLD G2 C
Solar/Wind Harmer
3.726
24699105WLD G1 C
Solar/Wind Harmer
3.683
270246TR4_N_V150
Solar/Wind Harmer
0.791
270247TR4_N_V136
Solar/Wind Harmer
0.791
970349AG2-230 GEN
Solar/Wind Harmer
13.937
246937BC-WTG2
Solar/Wind Harmer
3.628
247620Y3-023
Adder
0.424
274770LINCOLN ;1U
Adder
7.721
274771LINCOLN ;2U
Adder
7.721
274805UNIV PK N;1U
Adder
4.582
274808UNIV PK N;4U
Adder
4.552
274674JOLIET 9 ;6U
Adder
14
274696ROCKY RD ;4P
Adder
10.303
274695ROCKY RD ;2P
Adder
10.065
274693ROCKY RD ;1P
Adder
9.966
274697ROCKY RD ;3P
Adder
2.734
316097T157 G90
Solar/Wind Helper
1.343
23751201ROTHROCK
Solar/Wind Helper
0.827
23585401KL_K28_T16
Solar/Wind Helper
1.409
235054AD2-180 GEN
Solar/Wind Helper
1.901
235531U2-073 GEN
Solar/Wind Helper
3.003
238117U2-030
Solar/Wind Helper
0.311
238147AE2-230_GEN1
Solar/Wind Helper
0.435
238148AE2-230_GEN2
Solar/Wind Helper
0.435
238149AF1-291A_GEN
Solar/Wind Helper
0.124
237061AD1-155 GEN
Solar/Wind Helper
1.542
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.239
237080AD1-060 GEN
Solar/Wind Helper
0.298
235062AE1-101 C1
Solar/Wind Helper
1.453
237006AB1-125 GEN
Solar/Wind Helper
0.108
316411AF1-147_GEN1
Solar/Wind Helper
0.768
23559101PLEAS2
50/50
11.912
23684201S70BUS2
50/50
0.302
23562301OGROV1
50/50
2.303
962761AG1-125 GEN
Solar/Wind Harmer
36.099
970149AG2-104 GEN
Solar/Wind Harmer
22.291
970155AG2-107 GEN
Solar/Wind Harmer
15.741
270510AE1-227 GEN1
Solar/Wind Harmer
2.626
960001AF2-291 GEN
Solar/Wind Harmer
3.203
270331AC1-082 GEN3
Solar/Wind Harmer
0.497
270520AE2-214 GEN
Solar/Wind Harmer
6.219
971073AG2-665 GEN
Solar/Wind Harmer
1.192
270273AD2-016 GEN
Solar/Wind Harmer
2.715
972203AH1-686 GEN
Adder
2.346
270286AF1-227 GEN2
Solar/Wind Harmer
2.121
24686505CER G6
Adder
8.386
253333AC1-068 GEN
Solar/Wind Harmer
1.051
24723205RIVRG3
Adder
18.832
972269AH1-719 GEN
Adder
2.301
253398AE2-221_GEN2
Solar/Wind Harmer
4.438
253316AC1-085 GEN3
Solar/Wind Harmer
8.185
946171AF1-282 GEN
Solar/Wind Harmer
9.777
253370AE2-315 SEC1
Adder
1.955
253371AE2-315 SEC2
Adder
1.85
270391AF1-285 GEN3
Solar/Wind Harmer
1.18
270578AF1-285 GEN2
Solar/Wind Harmer
1.18
25326309TAIT D
Adder
1.069
252516AE2-318_GEN
Solar/Wind Harmer
9.702
252510AF1-249 C
Solar/Wind Harmer
0.403
25194608D.CRK4
Adder
1.589
270317AD1-130_GEN
Solar/Wind Harmer
3.084
270485AE1-090_GEN
Solar/Wind Harmer
0.583
25196808ZIMRHP
Adder
73.077
270222AC2-111 GEN
Solar/Wind Harmer
4.266
944031AF1-071 GEN
Solar/Wind Harmer
0.96
25196008MFTGT1
Adder
1.328
945681AF1-233 GEN
Solar/Wind Harmer
17.868
971995AH1-542 GEN
Solar/Wind Harmer
10.409
942081AE2-220 GEN
Solar/Wind Harmer
6.039
270209AC1-174_GEN
Solar/Wind Harmer
3.843
270437AC2-090 C
Solar/Wind Harmer
5.27
270239V3-007_GEN1
Solar/Wind Harmer
1.625
965651AG1-433 GEN
Solar/Wind Harmer
5.157
958861AF2-177 GEN
Solar/Wind Harmer
10.311
945371AF1-202 GEN
Solar/Wind Harmer
6.578
270005AE1-210 C O1
Solar/Wind Harmer
5.146
23559001PLEAS1
50/50
11.912
23562401OGROV2
50/50
2.283
24318805MLG1
50/50
6.628
24721905FLATG4
Adder
24.155
962771AG1-126 GEN
Solar/Wind Harmer
36.099
970153AG2-106 GEN
Solar/Wind Harmer
15.741
270512AE1-227 GEN2
Solar/Wind Harmer
2.229
270330AC1-082 GEN2
Solar/Wind Harmer
0.495
270329AC1-082 GEN1
Solar/Wind Harmer
0.495
971191AH1-055 GEN
Solar/Wind Harmer
19.41
957541AF2-048 GEN
Solar/Wind Harmer
1.634
961921AG1-034 GEN
Solar/Wind Harmer
13.102
970879AG2-548 GEN
Solar/Wind Harmer
8.201
960801AF2-371 GEN
Solar/Wind Harmer
2.597
964871AG1-351 GEN
Solar/Wind Harmer
1.793
270284AF1-227 GEN1
Solar/Wind Harmer
5.734
270287AF1-227 GEN3
Solar/Wind Harmer
2.121
942051AE2-217 GEN
Solar/Wind Harmer
18.15
24686405CER G5
Adder
8.32
253325AC1-069 GEN
Solar/Wind Harmer
1.051
270518AE2-148 GEN
Solar/Wind Harmer
12.124
270367AC2-061_GEN
Solar/Wind Harmer
3.114
253394AE2-221_GEN
Solar/Wind Harmer
4.438
253317AC1-085 GEN4
Solar/Wind Harmer
8.185
946181AF1-283 GEN
Solar/Wind Harmer
12.71
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.955
253371AE2-315 SEC2
Adder
1.85
942871AE2-306 GEN
Solar/Wind Harmer
0.885
270391AF1-285 GEN3
Solar/Wind Harmer
0.454
270186AC1-089 GEN
Solar/Wind Harmer
5.95
960071AF2-298 GEN
Solar/Wind Harmer
1.473
252507AC2-088 GEN
Solar/Wind Harmer
1.738
252519AF1-045_GEN
Solar/Wind Harmer
3.531
276820AF1-078_GEN
Solar/Wind Harmer
1.544
252524AE2-267 GEN
Solar/Wind Harmer
1.522
25196608WSDLE5
Adder
8.282
25194608D.CRK4
Adder
1.589
25196008MFTGT1
Adder
1.286
970825AG2-519 GEN
Solar/Wind Harmer
1.974
270024AE2-089 GEN
Solar/Wind Harmer
4.403
270594AE1-207 GEN
Solar/Wind Harmer
12.754
270032AE2-172
Solar/Wind Harmer
4.368
970091AG2-072 GEN
Adder
71.916
276903AD2-071 C
Solar/Wind Harmer
9.372
965011AG1-365 GEN
Solar/Wind Harmer
9.345
965421AG1-410 GEN
Solar/Wind Harmer
27.848
246936BC-WTG1
Solar/Wind Harmer
3.628
270489AE1-102 GEN1
Solar/Wind Harmer
1.206
24728605AND G2
Adder
3.555
24639705ELKHART HY
Adder
0.141
274773LINCOLN ;4U
Adder
7.721
274774LINCOLN ;5U
Adder
7.721
274751CRETE EC ;1U
Adder
7.534
274754CRETE EC ;4U
Adder
7.534
274723RIVER EC ;12
Adder
16.377
274812UNIV PK N;8U
Adder
4.572
274802UNIV PARK;5U
Adder
5.315
274732ELWOOD EC;7P
Adder
14.948
274676JOLIET 29;8U
Adder
27.901
274674JOLIET 9 ;6U
Adder
14
274745AC1-111 GEN9
Adder
5.067
274682WAUKEGAN ;7U
Adder
1.999
23751101LEADS_P59
Solar/Wind Helper
2.36
23583801GRNGAP
Solar/Wind Helper
5.023
316095T157 G97
Solar/Wind Helper
1.343
238185AF2-356 C
Solar/Wind Helper
2.448
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238120AE2-309 GEN
Solar/Wind Helper
0.48
238126S14_GEN_1
Solar/Wind Helper
0.755
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.443
235067AD1-061 GEN
Solar/Wind Helper
0.39
237038AE2-054 C
Solar/Wind Helper
0.238
237002AB1-128_GEN
Solar/Wind Helper
0.387
23777801MSM_W1-116
Solar/Wind Helper
0.1
972167AH1-666 GEN
Solar/Wind Harmer
7.586
958171AF2-111 GEN
Solar/Wind Harmer
23.702
944531AF1-118 GEN
Solar/Wind Harmer
33.064
24379505HDWTR1G C
Solar/Wind Harmer
7.466
270240V3-007_GEN2
Solar/Wind Harmer
5.841
270004AE1-209 GEN
Solar/Wind Harmer
5.146
962031AG1-047 GEN
Solar/Wind Harmer
2.847
957741AF2-068 GEN
Solar/Wind Harmer
14.123
946031AF1-268 GEN
Solar/Wind Harmer
7.814
970825AG2-519 GEN
Solar/Wind Harmer
5.3
965461AG1-414 GEN
Solar/Wind Harmer
2.128
970289AG2-191 GEN
Solar/Wind Harmer
0.72
247642Z2-115 C
Solar/Wind Harmer
0.06
270043AE2-236 GEN
Solar/Wind Harmer
5.148
965021AG1-366 GEN
Solar/Wind Harmer
2.173
971347AH1-153 GEN
Solar/Wind Harmer
4.646
246938BC-WTG3
Solar/Wind Harmer
3.691
270491AE1-102 GEN2
Solar/Wind Harmer
1.206
24728705AND G3
Adder
7.436
24728505AND G1
Adder
3.555
24695305TIMB G C
Solar/Wind Harmer
3.093
958581AF2-149 GEN
Solar/Wind Harmer
3.962
971199AH1-059 GEN
Solar/Wind Harmer
1.944
274772LINCOLN ;3U
Adder
7.721
274752CRETE EC ;2U
Adder
7.534
274753CRETE EC ;3U
Adder
7.534
274724RIVER EC ;11
Adder
16.186
274814UNIV PK N;0U
Adder
4.612
274807UNIV PK N;3U
Adder
4.602
274811UNIV PK N;7U
Adder
4.572
274803UNIV PARK;6U
Adder
5.315
274826FISK ;BP
Adder
9.978
972038AH1-567 GEN2
Adder
0.333
972259AH1-714 GEN
Adder
17.382
274729ELWOOD EC;1P
Adder
14.948
274730ELWOOD EC;6P
Adder
14.948
274734ELWOOD EC;8P
Adder
14.948
274736ELWOOD EC;9P
Adder
14.948
274676JOLIET 29;8U
Adder
26.905
274682WAUKEGAN ;7U
Adder
16.24
964991AG1-363 GEN
Solar/Wind Helper
4.317
23562501BACKB
Solar/Wind Helper
1.016
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238127S14_GEN_2
Solar/Wind Helper
0.755
238152AF2-075_GEN
Solar/Wind Helper
0.621
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.154
235063AE1-101 C2
Solar/Wind Helper
1.453
237001AB1-127_GEN
Solar/Wind Helper
0.386
316415AF1-147_GEN2
Solar/Wind Helper
0.768
237048AF1-022 C
Solar/Wind Helper
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.694
NYPJM->LTFIMP_NY
CLTF
4.537
LGEELTFEXP_LGEE->PJM
CLTF
6.253
MECLTFEXP_MEC->PJM
CLTF
14.418
SIGELTFEXP_SIGE->PJM
CLTF
0.465
CPLELTFEXP_CPLE->PJM
CLTF
1.203
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.012
LAGNLTFEXP_LAGN->PJM
CLTF
14.087
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.851
TVALTFEXP_TVA->PJM
CLTF
6.994
WECLTFEXP_WEC->PJM
CLTF
3.425
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.32

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.99
MW Contribution:
6.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.224
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
10.862
971655AH1-328 GEN
Solar/Wind Harmer
2.4
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
0
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
960971AF2-388 GEN
Solar/Wind Harmer
3.846
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
270599AE1-208 GEN
Solar/Wind Harmer
5.986
942221AE2-234 GEN
Solar/Wind Harmer
2.621
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.041
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
246937BC-WTG2
Solar/Wind Harmer
0.26
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
965681AG1-436 GEN
Solar/Wind Harmer
8.006
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.422
972043AH1-570 GEN
Solar/Wind Harmer
1.663
972045AH1-571 GEN
Solar/Wind Harmer
1.333
970241AG2-163 GEN
Solar/Wind Harmer
3.722
961051AF2-396 GEN
Solar/Wind Harmer
12.733
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
961921AG1-034 GEN
Solar/Wind Harmer
6.37
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.608
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.304
252519AF1-045_GEN
Solar/Wind Harmer
3.517
970191AG2-125 GEN
Solar/Wind Harmer
1.734
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970825AG2-519 GEN
Solar/Wind Harmer
4.924
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
3.227
246938BC-WTG3
Solar/Wind Harmer
0.232
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274887GEN-1.85
Solar/Wind Harmer
0.165
276843GEN-1.7
Solar/Wind Harmer
0.205
276806AD2-047 C O1
Solar/Wind Harmer
3.589
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
30.328
970149AG2-104 GEN
Solar/Wind Harmer
16.378
970155AG2-107 GEN
Solar/Wind Harmer
19.366
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
270520AE2-214 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
0.726
972203AH1-686 GEN
Adder
2.339
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
7.551
252510AF1-249 C
Solar/Wind Harmer
0.051
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
7.272
965011AG1-365 GEN
Solar/Wind Harmer
6.491
965421AG1-410 GEN
Solar/Wind Harmer
19.339
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
24728605AND G2
Adder
3.541
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.351
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.48
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
971587AH1-292 GEN
Solar/Wind Harmer
4.656
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
276776AD2-060 GEN
Solar/Wind Harmer
0.676
958011AF2-095 GEN
Solar/Wind Harmer
9.122
970941AG2-585 GEN
Solar/Wind Harmer
3.484
945391AF1-204 GEN
Solar/Wind Harmer
6.73
276897AD1-100 C
Solar/Wind Harmer
15.831
274674JOLIET 9 ;6U
Adder
13.943
276893AG1-478 C
Solar/Wind Harmer
0.421
971125AH1-004 GEN
Solar/Wind Harmer
2.523
970107AG2-081 GEN
Solar/Wind Harmer
1.892
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
958491AF2-143 GEN
Solar/Wind Harmer
9.422
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
274682WAUKEGAN ;7U
Adder
16.174
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
946671AF1-331 GEN
Solar/Wind Harmer
0.667
965091AG1-374 GEN
Solar/Wind Harmer
18.751
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
270588AE1-091_GEN
Solar/Wind Harmer
4.882
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
959091AF2-200 GEN
Solar/Wind Harmer
3.185
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270291AC1-194 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
2.075
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
253406AD2-031_GEN
Solar/Wind Harmer
0.507
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972163AH1-664 GEN
Solar/Wind Harmer
7.323
972165AH1-665 GEN
Solar/Wind Harmer
5.865
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
12.517
971609AH1-304 GEN
Solar/Wind Harmer
1.067
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
959331AF2-224 GEN
Solar/Wind Harmer
4.543
247521TR3_G114
Solar/Wind Harmer
0.234
965051AG1-369 GEN
Solar/Wind Harmer
3.226
965041AG1-368 GEN
Solar/Wind Harmer
6.455
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.816
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.285
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.578
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.438
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
971171AH1-044 GEN
Solar/Wind Harmer
3.185
24639705ELKHART HY
Adder
0.141
963741AG1-226 GEN
Solar/Wind Harmer
15.1
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.32
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.718
944971AF1-162 GEN
Solar/Wind Harmer
6.303
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
971997AH1-543 GEN
Solar/Wind Harmer
3.293
276882AE2-255 GEN
Solar/Wind Harmer
0.732
962781AG1-127 GEN
Solar/Wind Harmer
5.964
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.771
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.57
MW Contribution:
6.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.224
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
10.862
971655AH1-328 GEN
Solar/Wind Harmer
2.4
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
0
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
960971AF2-388 GEN
Solar/Wind Harmer
3.846
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
270599AE1-208 GEN
Solar/Wind Harmer
5.986
942221AE2-234 GEN
Solar/Wind Harmer
2.621
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.041
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
246937BC-WTG2
Solar/Wind Harmer
0.26
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
961921AG1-034 GEN
Solar/Wind Harmer
6.37
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.608
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.304
252519AF1-045_GEN
Solar/Wind Harmer
3.517
970191AG2-125 GEN
Solar/Wind Harmer
1.734
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970825AG2-519 GEN
Solar/Wind Harmer
4.924
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
3.227
246938BC-WTG3
Solar/Wind Harmer
0.232
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274887GEN-1.85
Solar/Wind Harmer
0.165
276843GEN-1.7
Solar/Wind Harmer
0.205
276806AD2-047 C O1
Solar/Wind Harmer
3.589
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
274682WAUKEGAN ;7U
Adder
16.174
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
946671AF1-331 GEN
Solar/Wind Harmer
0.667
965091AG1-374 GEN
Solar/Wind Harmer
18.751
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
270588AE1-091_GEN
Solar/Wind Harmer
4.882
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
959091AF2-200 GEN
Solar/Wind Harmer
3.185
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270291AC1-194 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
2.075
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
253406AD2-031_GEN
Solar/Wind Harmer
0.507
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972163AH1-664 GEN
Solar/Wind Harmer
7.323
972165AH1-665 GEN
Solar/Wind Harmer
5.865
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
12.517
971609AH1-304 GEN
Solar/Wind Harmer
1.067
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
959331AF2-224 GEN
Solar/Wind Harmer
4.543
247521TR3_G114
Solar/Wind Harmer
0.234
965051AG1-369 GEN
Solar/Wind Harmer
3.226
965041AG1-368 GEN
Solar/Wind Harmer
6.455
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.816
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.285
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.578
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
30.328
970149AG2-104 GEN
Solar/Wind Harmer
16.378
970155AG2-107 GEN
Solar/Wind Harmer
19.366
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
270520AE2-214 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
0.726
972203AH1-686 GEN
Adder
2.339
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
7.551
252510AF1-249 C
Solar/Wind Harmer
0.051
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
7.272
965011AG1-365 GEN
Solar/Wind Harmer
6.491
965421AG1-410 GEN
Solar/Wind Harmer
19.339
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
24728605AND G2
Adder
3.541
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.351
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.438
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
971171AH1-044 GEN
Solar/Wind Harmer
3.185
970373AG2-245 GEN
Solar/Wind Harmer
13.48
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
963741AG1-226 GEN
Solar/Wind Harmer
15.1
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.32
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.718
944971AF1-162 GEN
Solar/Wind Harmer
6.303
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
971997AH1-543 GEN
Solar/Wind Harmer
3.293
276882AE2-255 GEN
Solar/Wind Harmer
0.732
962781AG1-127 GEN
Solar/Wind Harmer
5.964
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.771
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
965681AG1-436 GEN
Solar/Wind Harmer
8.006
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.422
972043AH1-570 GEN
Solar/Wind Harmer
1.663
972045AH1-571 GEN
Solar/Wind Harmer
1.333
970241AG2-163 GEN
Solar/Wind Harmer
3.722
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
971587AH1-292 GEN
Solar/Wind Harmer
4.656
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
276776AD2-060 GEN
Solar/Wind Harmer
0.676
958011AF2-095 GEN
Solar/Wind Harmer
9.122
970941AG2-585 GEN
Solar/Wind Harmer
3.484
945391AF1-204 GEN
Solar/Wind Harmer
6.73
276897AD1-100 C
Solar/Wind Harmer
15.831
274674JOLIET 9 ;6U
Adder
13.943
276893AG1-478 C
Solar/Wind Harmer
0.421
971125AH1-004 GEN
Solar/Wind Harmer
2.523
970107AG2-081 GEN
Solar/Wind Harmer
1.892
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
958491AF2-143 GEN
Solar/Wind Harmer
9.422
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.19 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5278.17
MW Contribution:
9.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
927014AC1-188 GEN
Solar/Wind Harmer
1.603
270349AD2-093_GEN
Solar/Wind Harmer
3.664
270471AD2-092_GEN
Solar/Wind Harmer
3.664
270054AF2-122 C O1
Solar/Wind Harmer
3.288
971073AG2-665 GEN
Solar/Wind Harmer
8.039
970879AG2-548 GEN
Solar/Wind Harmer
1.168
946101AF1-275 GEN
Solar/Wind Harmer
1.513
270269AC2-059
Solar/Wind Harmer
9.305
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253383AE2-342_GEN
Solar/Wind Harmer
0.868
942861AE2-305 GEN
Solar/Wind Harmer
7.636
253415AE1-040 GEN
Solar/Wind Harmer
1.098
962581AG1-107 GEN
Solar/Wind Harmer
4.832
961491AF2-440 GEN
Solar/Wind Harmer
2.008
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
5.747
252509AD1-136 GEN
Solar/Wind Harmer
0.243
253349AC2-067 GEN
Solar/Wind Harmer
1.925
253400AC2-068 GEN
Solar/Wind Harmer
0.774
938701AE1-092 GEN
Solar/Wind Harmer
19.541
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
253378AE2-206_GEN
Solar/Wind Harmer
3.383
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
6.502
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
9.219
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
5.623
926881AC1-175 GEN
Solar/Wind Harmer
5.139
944541AF1-119 GEN
Solar/Wind Harmer
3.848
960971AF2-388 GEN
Solar/Wind Harmer
10.047
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
4.716
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
7.466
270599AE1-208 GEN
Solar/Wind Harmer
7.466
942221AE2-234 GEN
Solar/Wind Harmer
3.201
970291AG2-192 GEN
Solar/Wind Harmer
1.189
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
3.633
24699105WLD G1 C
Solar/Wind Harmer
3.591
270246TR4_N_V150
Solar/Wind Harmer
0.769
270247TR4_N_V136
Solar/Wind Harmer
0.769
970349AG2-230 GEN
Solar/Wind Harmer
13.564
945421AF1-207 GEN
Solar/Wind Harmer
12.67
957841AF2-078 GEN
Solar/Wind Harmer
5.454
247620Y3-023
Adder
0.413
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
940611AE2-048 GEN
Solar/Wind Harmer
22.073
941391AE2-136 GEN
Solar/Wind Harmer
11.438
270291AC1-194 GEN
Solar/Wind Harmer
5.101
270459AD2-067 GEN
Solar/Wind Harmer
8.368
961821AG1-024 GEN
Solar/Wind Harmer
8.496
270432AC2-029 GEN
Solar/Wind Harmer
6.989
270263AC1-001 GEN
Solar/Wind Harmer
1.042
241955AC1-078 GEN
Solar/Wind Harmer
7.382
945631AF1-228 GEN
Solar/Wind Harmer
4.627
971985AH1-537 GEN
Solar/Wind Harmer
17.539
253338AC1-165 GEN
Solar/Wind Harmer
1.063
253343AC1-166 GEN
Solar/Wind Harmer
1.063
241973AD2-163_GEN1
Solar/Wind Harmer
1.941
241974AD2-163_GEN2
Solar/Wind Harmer
1.941
943861AF1-054 GEN
Solar/Wind Harmer
3.769
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
2.956
241972AD1-140 GEN
Solar/Wind Harmer
4.312
253406AD2-031_GEN
Solar/Wind Harmer
1.227
253433AC1-085 GEN1
Solar/Wind Harmer
5.075
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270223U2-072_GEN1
Solar/Wind Harmer
1.87
270224U2-072_GEN2
Solar/Wind Harmer
1.87
270227U2-072_GEN3
Solar/Wind Harmer
1.87
270228U2-072_GEN4
Solar/Wind Harmer
1.87
270231U2-072_GEN5
Solar/Wind Harmer
1.87
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
7.829
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
9.262
972165AH1-665 GEN
Solar/Wind Harmer
7.409
971029AG2-637 GEN
Solar/Wind Harmer
13.858
270543AE2-219 C
Solar/Wind Harmer
9.219
247536S-71 GEN
Solar/Wind Harmer
3.723
24729505KEY G4
Adder
5.966
958711AF2-162 GEN
Solar/Wind Harmer
0.93
945581AF1-223 GEN
Solar/Wind Harmer
4.167
270356AE2-297 GEN
Solar/Wind Harmer
4.233
961761AG1-017 GEN
Solar/Wind Harmer
0.393
964611AG1-324 GEN
Solar/Wind Harmer
3.579
270071AF1-092 GEN
Solar/Wind Harmer
13.725
970289AG2-191 GEN
Solar/Wind Harmer
1.738
963791AG1-232 GEN
Solar/Wind Harmer
12.295
959331AF2-224 GEN
Solar/Wind Harmer
9.086
247521TR3_G114
Solar/Wind Harmer
3.039
270191TR4_S_V150
Solar/Wind Harmer
2.712
965051AG1-369 GEN
Solar/Wind Harmer
4.516
965041AG1-368 GEN
Solar/Wind Harmer
9.035
339216AC1-074 GEN
Solar/Wind Harmer
1.512
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
35.004
970149AG2-104 GEN
Solar/Wind Harmer
21.615
970155AG2-107 GEN
Solar/Wind Harmer
15.264
270510AE1-227 GEN1
Solar/Wind Harmer
2.647
960001AF2-291 GEN
Solar/Wind Harmer
3.156
270331AC1-082 GEN3
Solar/Wind Harmer
0.491
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
6.054
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
2.653
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
270286AF1-227 GEN2
Solar/Wind Harmer
2.059
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
1.025
253398AE2-221_GEN2
Solar/Wind Harmer
4.334
253316AC1-085 GEN3
Solar/Wind Harmer
7.996
946171AF1-282 GEN
Solar/Wind Harmer
9.551
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
9.479
270391AF1-285 GEN3
Solar/Wind Harmer
1.145
270578AF1-285 GEN2
Solar/Wind Harmer
1.145
252510AF1-249 C
Solar/Wind Harmer
0.394
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
2.993
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270222AC2-111 GEN
Solar/Wind Harmer
4.163
944031AF1-071 GEN
Solar/Wind Harmer
0.937
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
17.484
942081AE2-220 GEN
Solar/Wind Harmer
5.889
270209AC1-174_GEN
Solar/Wind Harmer
3.747
270437AC2-090 C
Solar/Wind Harmer
5.139
270239V3-007_GEN1
Solar/Wind Harmer
1.584
965651AG1-433 GEN
Solar/Wind Harmer
5.023
958861AF2-177 GEN
Solar/Wind Harmer
10.045
945371AF1-202 GEN
Solar/Wind Harmer
6.41
971995AH1-542 GEN
Solar/Wind Harmer
10.104
270005AE1-210 C O1
Solar/Wind Harmer
5.017
970825AG2-519 GEN
Solar/Wind Harmer
1.925
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
12.433
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
4.289
276903AD2-071 C
Solar/Wind Harmer
9.138
965011AG1-365 GEN
Solar/Wind Harmer
9.086
24728605AND G2
Adder
3.47
339221AD2-048_GEN
Solar/Wind Harmer
1.388
965421AG1-410 GEN
Solar/Wind Harmer
27.057
24639705ELKHART HY
Adder
0.138
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
940581AE2-045 GEN
Solar/Wind Harmer
5.47
971605AH1-302 GEN
Solar/Wind Harmer
4.677
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
35.004
970153AG2-106 GEN
Solar/Wind Harmer
15.264
270512AE1-227 GEN2
Solar/Wind Harmer
2.247
270330AC1-082 GEN2
Solar/Wind Harmer
0.49
270329AC1-082 GEN1
Solar/Wind Harmer
0.49
971191AH1-055 GEN
Solar/Wind Harmer
19.037
957541AF2-048 GEN
Solar/Wind Harmer
1.603
970879AG2-548 GEN
Solar/Wind Harmer
8.039
961921AG1-034 GEN
Solar/Wind Harmer
12.743
960801AF2-371 GEN
Solar/Wind Harmer
2.536
964871AG1-351 GEN
Solar/Wind Harmer
1.751
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
5.566
270287AF1-227 GEN3
Solar/Wind Harmer
2.059
942051AE2-217 GEN
Solar/Wind Harmer
17.671
253325AC1-069 GEN
Solar/Wind Harmer
1.025
270518AE2-148 GEN
Solar/Wind Harmer
11.818
270367AC2-061_GEN
Solar/Wind Harmer
3.046
253394AE2-221_GEN
Solar/Wind Harmer
4.334
253317AC1-085 GEN4
Solar/Wind Harmer
7.996
946181AF1-283 GEN
Solar/Wind Harmer
12.416
270186AC1-089 GEN
Solar/Wind Harmer
5.821
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
960071AF2-298 GEN
Solar/Wind Harmer
1.437
252507AC2-088 GEN
Solar/Wind Harmer
1.699
252519AF1-045_GEN
Solar/Wind Harmer
3.45
942871AE2-306 GEN
Solar/Wind Harmer
0.859
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
252524AE2-267 GEN
Solar/Wind Harmer
1.486
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
276820AF1-078_GEN
Solar/Wind Harmer
1.503
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
7.423
958171AF2-111 GEN
Solar/Wind Harmer
23.182
24379505HDWTR1G C
Solar/Wind Harmer
7.281
270240V3-007_GEN2
Solar/Wind Harmer
5.697
944531AF1-118 GEN
Solar/Wind Harmer
32.194
270004AE1-209 GEN
Solar/Wind Harmer
5.017
946031AF1-268 GEN
Solar/Wind Harmer
7.618
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
970825AG2-519 GEN
Solar/Wind Harmer
5.167
965461AG1-414 GEN
Solar/Wind Harmer
2.074
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.058
270043AE2-236 GEN
Solar/Wind Harmer
5.008
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
4.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.41
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.17 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5277.43
MW Contribution:
9.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
927014AC1-188 GEN
Solar/Wind Harmer
1.603
270349AD2-093_GEN
Solar/Wind Harmer
3.664
270471AD2-092_GEN
Solar/Wind Harmer
3.664
270054AF2-122 C O1
Solar/Wind Harmer
3.288
971073AG2-665 GEN
Solar/Wind Harmer
8.039
970879AG2-548 GEN
Solar/Wind Harmer
1.168
946101AF1-275 GEN
Solar/Wind Harmer
1.513
270269AC2-059
Solar/Wind Harmer
9.305
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253383AE2-342_GEN
Solar/Wind Harmer
0.868
942861AE2-305 GEN
Solar/Wind Harmer
7.636
253415AE1-040 GEN
Solar/Wind Harmer
1.098
962581AG1-107 GEN
Solar/Wind Harmer
4.832
961491AF2-440 GEN
Solar/Wind Harmer
2.008
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
5.747
252509AD1-136 GEN
Solar/Wind Harmer
0.243
253349AC2-067 GEN
Solar/Wind Harmer
1.925
253400AC2-068 GEN
Solar/Wind Harmer
0.774
938701AE1-092 GEN
Solar/Wind Harmer
19.541
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
253378AE2-206_GEN
Solar/Wind Harmer
3.383
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
6.502
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
9.219
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
5.623
926881AC1-175 GEN
Solar/Wind Harmer
5.139
944541AF1-119 GEN
Solar/Wind Harmer
3.848
960971AF2-388 GEN
Solar/Wind Harmer
10.047
940611AE2-048 GEN
Solar/Wind Harmer
22.073
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
35.004
970149AG2-104 GEN
Solar/Wind Harmer
21.615
970155AG2-107 GEN
Solar/Wind Harmer
15.264
270510AE1-227 GEN1
Solar/Wind Harmer
2.647
960001AF2-291 GEN
Solar/Wind Harmer
3.156
270331AC1-082 GEN3
Solar/Wind Harmer
0.491
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
6.054
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
2.653
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
270286AF1-227 GEN2
Solar/Wind Harmer
2.059
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
1.025
253398AE2-221_GEN2
Solar/Wind Harmer
4.334
253316AC1-085 GEN3
Solar/Wind Harmer
7.996
946171AF1-282 GEN
Solar/Wind Harmer
9.551
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
9.479
270391AF1-285 GEN3
Solar/Wind Harmer
1.145
270578AF1-285 GEN2
Solar/Wind Harmer
1.145
252510AF1-249 C
Solar/Wind Harmer
0.394
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
2.993
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270222AC2-111 GEN
Solar/Wind Harmer
4.163
944031AF1-071 GEN
Solar/Wind Harmer
0.937
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
17.484
942081AE2-220 GEN
Solar/Wind Harmer
5.889
270209AC1-174_GEN
Solar/Wind Harmer
3.747
270437AC2-090 C
Solar/Wind Harmer
5.139
270239V3-007_GEN1
Solar/Wind Harmer
1.584
965651AG1-433 GEN
Solar/Wind Harmer
5.023
958861AF2-177 GEN
Solar/Wind Harmer
10.045
945371AF1-202 GEN
Solar/Wind Harmer
6.41
971995AH1-542 GEN
Solar/Wind Harmer
10.104
270005AE1-210 C O1
Solar/Wind Harmer
5.017
970825AG2-519 GEN
Solar/Wind Harmer
1.925
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
12.433
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
4.289
276903AD2-071 C
Solar/Wind Harmer
9.138
965011AG1-365 GEN
Solar/Wind Harmer
9.086
24728605AND G2
Adder
3.47
339221AD2-048_GEN
Solar/Wind Harmer
1.388
965421AG1-410 GEN
Solar/Wind Harmer
27.057
24639705ELKHART HY
Adder
0.138
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
4.716
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
7.466
270599AE1-208 GEN
Solar/Wind Harmer
7.466
942221AE2-234 GEN
Solar/Wind Harmer
3.201
970291AG2-192 GEN
Solar/Wind Harmer
1.189
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
3.633
24699105WLD G1 C
Solar/Wind Harmer
3.591
270246TR4_N_V150
Solar/Wind Harmer
0.769
270247TR4_N_V136
Solar/Wind Harmer
0.769
970349AG2-230 GEN
Solar/Wind Harmer
13.564
945421AF1-207 GEN
Solar/Wind Harmer
12.67
957841AF2-078 GEN
Solar/Wind Harmer
5.454
247620Y3-023
Adder
0.413
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
940581AE2-045 GEN
Solar/Wind Harmer
5.47
971605AH1-302 GEN
Solar/Wind Harmer
4.677
941391AE2-136 GEN
Solar/Wind Harmer
11.438
270291AC1-194 GEN
Solar/Wind Harmer
5.101
270459AD2-067 GEN
Solar/Wind Harmer
8.368
961821AG1-024 GEN
Solar/Wind Harmer
8.496
270432AC2-029 GEN
Solar/Wind Harmer
6.989
270263AC1-001 GEN
Solar/Wind Harmer
1.042
241955AC1-078 GEN
Solar/Wind Harmer
7.382
945631AF1-228 GEN
Solar/Wind Harmer
4.627
971985AH1-537 GEN
Solar/Wind Harmer
17.539
253338AC1-165 GEN
Solar/Wind Harmer
1.063
253343AC1-166 GEN
Solar/Wind Harmer
1.063
241973AD2-163_GEN1
Solar/Wind Harmer
1.941
241974AD2-163_GEN2
Solar/Wind Harmer
1.941
943861AF1-054 GEN
Solar/Wind Harmer
3.769
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
2.956
241972AD1-140 GEN
Solar/Wind Harmer
4.312
253406AD2-031_GEN
Solar/Wind Harmer
1.227
253433AC1-085 GEN1
Solar/Wind Harmer
5.075
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270223U2-072_GEN1
Solar/Wind Harmer
1.87
270224U2-072_GEN2
Solar/Wind Harmer
1.87
270227U2-072_GEN3
Solar/Wind Harmer
1.87
270228U2-072_GEN4
Solar/Wind Harmer
1.87
270231U2-072_GEN5
Solar/Wind Harmer
1.87
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
7.829
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
9.262
972165AH1-665 GEN
Solar/Wind Harmer
7.409
971029AG2-637 GEN
Solar/Wind Harmer
13.858
270543AE2-219 C
Solar/Wind Harmer
9.219
247536S-71 GEN
Solar/Wind Harmer
3.723
24729505KEY G4
Adder
5.966
958711AF2-162 GEN
Solar/Wind Harmer
0.93
945581AF1-223 GEN
Solar/Wind Harmer
4.167
270356AE2-297 GEN
Solar/Wind Harmer
4.233
961761AG1-017 GEN
Solar/Wind Harmer
0.393
964611AG1-324 GEN
Solar/Wind Harmer
3.579
270071AF1-092 GEN
Solar/Wind Harmer
13.725
970289AG2-191 GEN
Solar/Wind Harmer
1.738
963791AG1-232 GEN
Solar/Wind Harmer
12.295
959331AF2-224 GEN
Solar/Wind Harmer
9.086
247521TR3_G114
Solar/Wind Harmer
3.039
270191TR4_S_V150
Solar/Wind Harmer
2.712
965051AG1-369 GEN
Solar/Wind Harmer
4.516
965041AG1-368 GEN
Solar/Wind Harmer
9.035
339216AC1-074 GEN
Solar/Wind Harmer
1.512
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
35.004
970153AG2-106 GEN
Solar/Wind Harmer
15.264
270512AE1-227 GEN2
Solar/Wind Harmer
2.247
270330AC1-082 GEN2
Solar/Wind Harmer
0.49
270329AC1-082 GEN1
Solar/Wind Harmer
0.49
971191AH1-055 GEN
Solar/Wind Harmer
19.037
957541AF2-048 GEN
Solar/Wind Harmer
1.603
970879AG2-548 GEN
Solar/Wind Harmer
8.039
961921AG1-034 GEN
Solar/Wind Harmer
12.743
960801AF2-371 GEN
Solar/Wind Harmer
2.536
964871AG1-351 GEN
Solar/Wind Harmer
1.751
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
5.566
270287AF1-227 GEN3
Solar/Wind Harmer
2.059
942051AE2-217 GEN
Solar/Wind Harmer
17.671
253325AC1-069 GEN
Solar/Wind Harmer
1.025
270518AE2-148 GEN
Solar/Wind Harmer
11.818
270367AC2-061_GEN
Solar/Wind Harmer
3.046
253394AE2-221_GEN
Solar/Wind Harmer
4.334
253317AC1-085 GEN4
Solar/Wind Harmer
7.996
946181AF1-283 GEN
Solar/Wind Harmer
12.416
270186AC1-089 GEN
Solar/Wind Harmer
5.821
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
960071AF2-298 GEN
Solar/Wind Harmer
1.437
252507AC2-088 GEN
Solar/Wind Harmer
1.699
252519AF1-045_GEN
Solar/Wind Harmer
3.45
942871AE2-306 GEN
Solar/Wind Harmer
0.859
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
252524AE2-267 GEN
Solar/Wind Harmer
1.486
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
276820AF1-078_GEN
Solar/Wind Harmer
1.503
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
7.423
958171AF2-111 GEN
Solar/Wind Harmer
23.182
24379505HDWTR1G C
Solar/Wind Harmer
7.281
270240V3-007_GEN2
Solar/Wind Harmer
5.697
944531AF1-118 GEN
Solar/Wind Harmer
32.194
270004AE1-209 GEN
Solar/Wind Harmer
5.017
946031AF1-268 GEN
Solar/Wind Harmer
7.618
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
970825AG2-519 GEN
Solar/Wind Harmer
5.167
965461AG1-414 GEN
Solar/Wind Harmer
2.074
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.058
270043AE2-236 GEN
Solar/Wind Harmer
5.008
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
4.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.41
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.98 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5270.18
MW Contribution:
9.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1216.009
23684101S70BUS1
50/50
0.312
23534401HANNIB
50/50
0.148
24318905MLG2
50/50
4.725
927014AC1-188 GEN
Solar/Wind Harmer
1.616
270349AD2-093_GEN
Solar/Wind Harmer
3.698
270471AD2-092_GEN
Solar/Wind Harmer
3.698
270054AF2-122 C O1
Solar/Wind Harmer
3.319
971073AG2-665 GEN
Solar/Wind Harmer
8.107
970879AG2-548 GEN
Solar/Wind Harmer
1.178
946101AF1-275 GEN
Solar/Wind Harmer
1.527
270269AC2-059
Solar/Wind Harmer
9.386
253383AE2-342_GEN
Solar/Wind Harmer
0.876
24723005RIVRG1
Adder
18.614
24723105RIVRG2
Adder
18.614
942861AE2-305 GEN
Solar/Wind Harmer
7.705
253415AE1-040 GEN
Solar/Wind Harmer
1.108
962581AG1-107 GEN
Solar/Wind Harmer
4.871
961491AF2-440 GEN
Solar/Wind Harmer
2.024
972159AH1-661 GEN
Adder
0.964
25326109MON D
Adder
1.264
253370AE2-315 SEC1
Adder
1.924
25322209TAIT E
Adder
9.36
25322209TAIT E
Adder
9.149
25183208HLCRTG
Solar/Wind Harmer
5.795
252509AD1-136 GEN
Solar/Wind Harmer
0.245
938701AE1-092 GEN
Solar/Wind Harmer
19.736
253349AC2-067 GEN
Solar/Wind Harmer
1.941
253400AC2-068 GEN
Solar/Wind Harmer
0.781
25194408D.CRK1
Adder
7.198
25194508D.CRK3
Adder
1.346
253378AE2-206_GEN
Solar/Wind Harmer
3.414
25326509SID D
Adder
1.244
270462AD2-086
Solar/Wind Harmer
6.566
24728805RICHG1
Adder
3.521
24728905RICHG2
Adder
3.521
970883AG2-550 GEN
Solar/Wind Harmer
9.298
970885AG2-551 GEN
Solar/Wind Harmer
2.162
270383AD1-128 GEN
Solar/Wind Harmer
5.671
926881AC1-175 GEN
Solar/Wind Harmer
5.183
944541AF1-119 GEN
Solar/Wind Harmer
3.882
960971AF2-388 GEN
Solar/Wind Harmer
10.135
247621Y3-024
Adder
0.223
270201AC2-176 GEN
Solar/Wind Harmer
4.757
964611AG1-324 GEN
Solar/Wind Harmer
0.484
270031AE2-169
Solar/Wind Harmer
7.53
270599AE1-208 GEN
Solar/Wind Harmer
7.53
942221AE2-234 GEN
Solar/Wind Harmer
3.23
970291AG2-192 GEN
Solar/Wind Harmer
1.199
970291AG2-192 GEN
Solar/Wind Harmer
0.386
24725505WLD G2 C
Solar/Wind Harmer
3.664
24699105WLD G1 C
Solar/Wind Harmer
3.622
270246TR4_N_V150
Solar/Wind Harmer
0.776
270247TR4_N_V136
Solar/Wind Harmer
0.776
970349AG2-230 GEN
Solar/Wind Harmer
13.685
246937BC-WTG2
Solar/Wind Harmer
3.559
247620Y3-023
Adder
0.416
274770LINCOLN ;1U
Adder
7.587
274771LINCOLN ;2U
Adder
7.587
274805UNIV PK N;1U
Adder
4.503
274808UNIV PK N;4U
Adder
4.473
316097T157 G90
Solar/Wind Helper
1.324
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
237061AD1-155 GEN
Solar/Wind Helper
1.5
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.231
237080AD1-060 GEN
Solar/Wind Helper
0.287
235062AE1-101 C1
Solar/Wind Helper
1.395
237006AB1-125 GEN
Solar/Wind Helper
0.106
316411AF1-147_GEN1
Solar/Wind Helper
0.753
945421AF1-207 GEN
Solar/Wind Harmer
3.67
23559101PLEAS2
50/50
11.275
23684201S70BUS2
50/50
0.318
23562301OGROV1
50/50
2.457
962761AG1-125 GEN
Solar/Wind Harmer
35.283
970149AG2-104 GEN
Solar/Wind Harmer
21.787
970155AG2-107 GEN
Solar/Wind Harmer
15.385
270510AE1-227 GEN1
Solar/Wind Harmer
2.681
960001AF2-291 GEN
Solar/Wind Harmer
3.18
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
971073AG2-665 GEN
Solar/Wind Harmer
1.178
270520AE2-214 GEN
Solar/Wind Harmer
6.11
270273AD2-016 GEN
Solar/Wind Harmer
2.676
972203AH1-686 GEN
Adder
2.316
972269AH1-719 GEN
Adder
2.296
24686505CER G6
Adder
8.307
270286AF1-227 GEN2
Solar/Wind Harmer
2.078
24723205RIVRG3
Adder
18.614
253333AC1-068 GEN
Solar/Wind Harmer
1.034
253398AE2-221_GEN2
Solar/Wind Harmer
4.371
253316AC1-085 GEN3
Solar/Wind Harmer
8.063
946171AF1-282 GEN
Solar/Wind Harmer
9.631
253370AE2-315 SEC1
Adder
1.924
253371AE2-315 SEC2
Adder
1.82
25326309TAIT D
Adder
1.052
270391AF1-285 GEN3
Solar/Wind Harmer
1.157
270578AF1-285 GEN2
Solar/Wind Harmer
1.157
252516AE2-318_GEN
Solar/Wind Harmer
9.558
252510AF1-249 C
Solar/Wind Harmer
0.397
25194608D.CRK4
Adder
1.565
25196808ZIMRHP
Adder
72.004
270317AD1-130_GEN
Solar/Wind Harmer
3.023
270485AE1-090_GEN
Solar/Wind Harmer
0.571
270222AC2-111 GEN
Solar/Wind Harmer
4.198
944031AF1-071 GEN
Solar/Wind Harmer
0.945
25196008MFTGT1
Adder
1.308
945681AF1-233 GEN
Solar/Wind Harmer
17.624
942081AE2-220 GEN
Solar/Wind Harmer
5.939
270209AC1-174_GEN
Solar/Wind Harmer
3.779
270437AC2-090 C
Solar/Wind Harmer
5.183
270239V3-007_GEN1
Solar/Wind Harmer
1.598
971995AH1-542 GEN
Solar/Wind Harmer
10.211
965651AG1-433 GEN
Solar/Wind Harmer
5.067
958861AF2-177 GEN
Solar/Wind Harmer
10.133
945371AF1-202 GEN
Solar/Wind Harmer
6.466
270005AE1-210 C O1
Solar/Wind Harmer
5.06
970825AG2-519 GEN
Solar/Wind Harmer
1.941
970091AG2-072 GEN
Adder
70.821
270594AE1-207 GEN
Solar/Wind Harmer
12.54
270032AE2-172
Solar/Wind Harmer
4.294
270024AE2-089 GEN
Solar/Wind Harmer
4.327
276903AD2-071 C
Solar/Wind Harmer
9.216
965011AG1-365 GEN
Solar/Wind Harmer
9.171
24728605AND G2
Adder
3.499
339221AD2-048_GEN
Solar/Wind Harmer
1.399
965421AG1-410 GEN
Solar/Wind Harmer
27.321
246936BC-WTG1
Solar/Wind Harmer
3.559
270489AE1-102 GEN1
Solar/Wind Harmer
1.183
24639705ELKHART HY
Adder
0.139
274773LINCOLN ;4U
Adder
7.587
274774LINCOLN ;5U
Adder
7.587
274751CRETE EC ;1U
Adder
7.403
274754CRETE EC ;4U
Adder
7.403
274723RIVER EC ;12
Adder
16.092
274812UNIV PK N;8U
Adder
4.493
274802UNIV PARK;5U
Adder
5.223
274732ELWOOD EC;7P
Adder
14.692
23583801GRNGAP
Solar/Wind Helper
4.95
316095T157 G97
Solar/Wind Helper
1.324
23546401DTGZ2-030
Solar/Wind Helper
0.076
238109AE1-109 GEN2
Solar/Wind Helper
0.087
237038AE2-054 C
Solar/Wind Helper
0.229
235067AD1-061 GEN
Solar/Wind Helper
0.374
237085AD2-009_GEN
Solar/Wind Helper
1.38
237002AB1-128_GEN
Solar/Wind Helper
0.373
23777801MSM_W1-116
Solar/Wind Helper
0.098
940611AE2-048 GEN
Solar/Wind Harmer
22.313
941391AE2-136 GEN
Solar/Wind Harmer
11.562
270291AC1-194 GEN
Solar/Wind Harmer
5.145
270459AD2-067 GEN
Solar/Wind Harmer
8.448
961821AG1-024 GEN
Solar/Wind Harmer
8.577
270432AC2-029 GEN
Solar/Wind Harmer
7.05
270263AC1-001 GEN
Solar/Wind Harmer
1.051
241955AC1-078 GEN
Solar/Wind Harmer
7.45
945631AF1-228 GEN
Solar/Wind Harmer
4.669
971985AH1-537 GEN
Solar/Wind Harmer
17.679
253338AC1-165 GEN
Solar/Wind Harmer
1.072
253343AC1-166 GEN
Solar/Wind Harmer
1.072
241973AD2-163_GEN1
Solar/Wind Harmer
1.959
241974AD2-163_GEN2
Solar/Wind Harmer
1.959
943861AF1-054 GEN
Solar/Wind Harmer
3.803
943851AF1-053 GEN
Solar/Wind Harmer
1.838
270340AC2-060 GEN
Solar/Wind Harmer
2.981
241972AD1-140 GEN
Solar/Wind Harmer
4.35
253406AD2-031_GEN
Solar/Wind Harmer
1.237
253433AC1-085 GEN1
Solar/Wind Harmer
5.118
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
253372AE2-315 SEC3
Adder
1.82
253372AE2-315 SEC3
Adder
1.82
25306009OHH W.
Adder
2.761
270223U2-072_GEN1
Solar/Wind Harmer
1.888
270224U2-072_GEN2
Solar/Wind Harmer
1.888
270227U2-072_GEN3
Solar/Wind Harmer
1.888
270228U2-072_GEN4
Solar/Wind Harmer
1.888
270231U2-072_GEN5
Solar/Wind Harmer
1.888
270578AF1-285 GEN2
Solar/Wind Harmer
0.445
25196408WSDLE3
Adder
8.398
25196308WSDLE2
Adder
8.325
25196208WSDLE1
Adder
8.304
25196708WSDLE6
Adder
8.283
25196508WSDLE4
Adder
8.074
270302AB2-170 GEN
Solar/Wind Harmer
7.906
25196108MFTGT2
Adder
1.442
25196108MFTGT2
Adder
1.339
972163AH1-664 GEN
Solar/Wind Harmer
9.335
972165AH1-665 GEN
Solar/Wind Harmer
7.468
971029AG2-637 GEN
Solar/Wind Harmer
13.978
270543AE2-219 C
Solar/Wind Harmer
9.298
247536S-71 GEN
Solar/Wind Harmer
3.755
24729505KEY G4
Adder
6.019
958711AF2-162 GEN
Solar/Wind Harmer
0.938
945581AF1-223 GEN
Solar/Wind Harmer
4.203
270356AE2-297 GEN
Solar/Wind Harmer
4.269
961761AG1-017 GEN
Solar/Wind Harmer
0.396
964611AG1-324 GEN
Solar/Wind Harmer
3.61
270071AF1-092 GEN
Solar/Wind Harmer
13.847
970289AG2-191 GEN
Solar/Wind Harmer
1.753
963791AG1-232 GEN
Solar/Wind Harmer
12.407
959331AF2-224 GEN
Solar/Wind Harmer
9.171
247521TR3_G114
Solar/Wind Harmer
3.068
270191TR4_S_V150
Solar/Wind Harmer
2.738
965051AG1-369 GEN
Solar/Wind Harmer
4.559
965041AG1-368 GEN
Solar/Wind Harmer
9.12
339216AC1-074 GEN
Solar/Wind Harmer
1.524
957201AF2-014 GEN
Solar/Wind Harmer
4.127
270435AC2-044 GEN
Solar/Wind Harmer
1.82
274775LINCOLN ;6U
Adder
7.587
274776LINCOLN ;7U
Adder
7.587
274777LINCOLN ;8U
Adder
7.587
972037AH1-567 GEN1
Adder
0.164
972228AH1-698 GEN2
Adder
3.318
972227AH1-698 GEN1
Adder
2.336
274827FISK ;RP
Adder
6.949
274800UNIV PARK;3U
Adder
5.222
274801UNIV PARK;4U
Adder
5.222
274687WILL CNTY;4U
Adder
24.982
274687WILL CNTY;4U
Adder
24.982
941621AE2-160 GEN
Adder
2.939
274728ELWOOD EC;5P
Adder
14.692
274731ELWOOD EC;2P
Adder
14.692
274733ELWOOD EC;3P
Adder
14.692
274735ELWOOD EC;4P
Adder
11.662
238169AE2-226 GEN1
Solar/Wind Helper
0.593
238170AE2-226 GEN2
Solar/Wind Helper
0.593
23750701CROSSCHOOL
Solar/Wind Helper
1.115
23779801AA1-109
Solar/Wind Helper
0.164
3138216PACIFIC
Solar/Wind Helper
0.037
237030AB1-096 C
Solar/Wind Helper
0.057
237025AB1-124 C
Solar/Wind Helper
0.141
23559001PLEAS1
50/50
11.275
23562401OGROV2
50/50
2.436
24318805MLG1
50/50
6.371
24721905FLATG4
Adder
23.616
962771AG1-126 GEN
Solar/Wind Harmer
35.283
970153AG2-106 GEN
Solar/Wind Harmer
15.385
270512AE1-227 GEN2
Solar/Wind Harmer
2.276
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
971191AH1-055 GEN
Solar/Wind Harmer
19.185
957541AF2-048 GEN
Solar/Wind Harmer
1.616
970879AG2-548 GEN
Solar/Wind Harmer
8.107
961921AG1-034 GEN
Solar/Wind Harmer
12.865
960801AF2-371 GEN
Solar/Wind Harmer
2.559
964871AG1-351 GEN
Solar/Wind Harmer
1.767
24686405CER G5
Adder
8.242
270284AF1-227 GEN1
Solar/Wind Harmer
5.618
270287AF1-227 GEN3
Solar/Wind Harmer
2.078
942051AE2-217 GEN
Solar/Wind Harmer
17.832
253325AC1-069 GEN
Solar/Wind Harmer
1.034
270518AE2-148 GEN
Solar/Wind Harmer
11.924
270367AC2-061_GEN
Solar/Wind Harmer
3.071
253394AE2-221_GEN
Solar/Wind Harmer
4.371
253317AC1-085 GEN4
Solar/Wind Harmer
8.063
946181AF1-283 GEN
Solar/Wind Harmer
12.52
270186AC1-089 GEN
Solar/Wind Harmer
5.868
253303V4-073 C
Solar/Wind Harmer
0.111
253370AE2-315 SEC1
Adder
1.924
253371AE2-315 SEC2
Adder
1.82
960071AF2-298 GEN
Solar/Wind Harmer
1.449
252507AC2-088 GEN
Solar/Wind Harmer
1.712
942871AE2-306 GEN
Solar/Wind Harmer
0.867
270391AF1-285 GEN3
Solar/Wind Harmer
0.445
252519AF1-045_GEN
Solar/Wind Harmer
3.479
252524AE2-267 GEN
Solar/Wind Harmer
1.499
25196608WSDLE5
Adder
8.158
25194608D.CRK4
Adder
1.565
276820AF1-078_GEN
Solar/Wind Harmer
1.517
25196008MFTGT1
Adder
1.267
972167AH1-666 GEN
Solar/Wind Harmer
7.482
958171AF2-111 GEN
Solar/Wind Harmer
23.368
24379505HDWTR1G C
Solar/Wind Harmer
7.343
270240V3-007_GEN2
Solar/Wind Harmer
5.745
944531AF1-118 GEN
Solar/Wind Harmer
32.478
270004AE1-209 GEN
Solar/Wind Harmer
5.06
946031AF1-268 GEN
Solar/Wind Harmer
7.684
962031AG1-047 GEN
Solar/Wind Harmer
2.799
957741AF2-068 GEN
Solar/Wind Harmer
13.884
970825AG2-519 GEN
Solar/Wind Harmer
5.212
965461AG1-414 GEN
Solar/Wind Harmer
2.092
970289AG2-191 GEN
Solar/Wind Harmer
0.708
247642Z2-115 C
Solar/Wind Harmer
0.059
270043AE2-236 GEN
Solar/Wind Harmer
5.054
965021AG1-366 GEN
Solar/Wind Harmer
2.133
971347AH1-153 GEN
Solar/Wind Harmer
4.562
24728705AND G3
Adder
7.317
24728505AND G1
Adder
3.499
958581AF2-149 GEN
Solar/Wind Harmer
3.901
971199AH1-059 GEN
Solar/Wind Harmer
1.914
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
246938BC-WTG3
Solar/Wind Harmer
3.621
270491AE1-102 GEN2
Solar/Wind Harmer
1.183
274772LINCOLN ;3U
Adder
7.587
274752CRETE EC ;2U
Adder
7.403
274753CRETE EC ;3U
Adder
7.403
274724RIVER EC ;11
Adder
15.904
274814UNIV PK N;0U
Adder
4.532
274807UNIV PK N;3U
Adder
4.522
274811UNIV PK N;7U
Adder
4.493
274803UNIV PARK;6U
Adder
5.223
274826FISK ;BP
Adder
9.806
972038AH1-567 GEN2
Adder
0.327
972259AH1-714 GEN
Adder
17.082
274729ELWOOD EC;1P
Adder
14.692
274730ELWOOD EC;6P
Adder
14.692
274734ELWOOD EC;8P
Adder
14.692
964991AG1-363 GEN
Solar/Wind Helper
4.19
238152AF2-075_GEN
Solar/Wind Helper
0.604
238175AF1-290_GEN
Solar/Wind Helper
0.131
23777901MDS_W4-102
Solar/Wind Helper
0.149
238108AE1-109 GEN1
Solar/Wind Helper
0.087
238110AE1-109 GEN3
Solar/Wind Helper
0.087
237001AB1-127_GEN
Solar/Wind Helper
0.372
235063AE1-101 C2
Solar/Wind Helper
1.395
316415AF1-147_GEN2
Solar/Wind Helper
0.753
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.394
NYPJM->LTFIMP_NY
CLTF
4.427
LGEELTFEXP_LGEE->PJM
CLTF
6.165
MECLTFEXP_MEC->PJM
CLTF
14.194
SIGELTFEXP_SIGE->PJM
CLTF
0.459
CPLELTFEXP_CPLE->PJM
CLTF
1.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
103.644
LAGNLTFEXP_LAGN->PJM
CLTF
13.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.915
TVALTFEXP_TVA->PJM
CLTF
6.925
WECLTFEXP_WEC->PJM
CLTF
3.367
AG2-052LTFEXP_AG2-052->PJM
LTF
0.21
AH1-155LTFEXP_AH1-155->PJM
LTF
0.315

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5250.02
MW Contribution:
6.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
29.52
970149AG2-104 GEN
Solar/Wind Harmer
15.941
970155AG2-107 GEN
Solar/Wind Harmer
18.85
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
7.407
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
12.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970825AG2-519 GEN
Solar/Wind Harmer
2.272
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.119
965011AG1-365 GEN
Solar/Wind Harmer
6.339
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.17
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.272
24639705ELKHART HY
Adder
0.138
963741AG1-226 GEN
Solar/Wind Harmer
14.786
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.244
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.617
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.588
962781AG1-127 GEN
Solar/Wind Harmer
5.837
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
961921AG1-034 GEN
Solar/Wind Harmer
6.223
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.329
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252507AC2-088 GEN
Solar/Wind Harmer
0.298
252519AF1-045_GEN
Solar/Wind Harmer
3.45
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
970191AG2-125 GEN
Solar/Wind Harmer
1.699
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
958171AF2-111 GEN
Solar/Wind Harmer
16.173
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
28.761
270004AE1-209 GEN
Solar/Wind Harmer
1.388
946031AF1-268 GEN
Solar/Wind Harmer
6.094
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
3.154
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.226
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.532
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274887GEN-1.85
Solar/Wind Harmer
0.161
276843GEN-1.7
Solar/Wind Harmer
0.2
276806AD2-047 C O1
Solar/Wind Harmer
3.512
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
970707AG2-453 GEN
Solar/Wind Harmer
20.232
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
965091AG1-374 GEN
Solar/Wind Harmer
18.362
959611AF2-252 GEN
Solar/Wind Harmer
2.04
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
959091AF2-200 GEN
Solar/Wind Harmer
2.06
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270291AC1-194 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
971985AH1-537 GEN
Solar/Wind Harmer
2.039
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
253406AD2-031_GEN
Solar/Wind Harmer
0.497
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
7.194
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270543AE2-219 C
Solar/Wind Harmer
4.502
247536S-71 GEN
Solar/Wind Harmer
0.257
24729505KEY G4
Adder
5.966
945581AF1-223 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
270071AF1-092 GEN
Solar/Wind Harmer
12.235
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
959331AF2-224 GEN
Solar/Wind Harmer
4.437
247521TR3_G114
Solar/Wind Harmer
0.229
965051AG1-369 GEN
Solar/Wind Harmer
3.151
965041AG1-368 GEN
Solar/Wind Harmer
6.303
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270526AF1-158 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
270399AC1-101 GEN
Solar/Wind Harmer
1.959
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
970179AG2-119 GEN
Solar/Wind Harmer
5.512
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.152
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.441
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971171AH1-044 GEN
Solar/Wind Harmer
2.06
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
970879AG2-548 GEN
Solar/Wind Harmer
1.168
270269AC2-059
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
942861AE2-305 GEN
Solar/Wind Harmer
5.328
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
938701AE1-092 GEN
Solar/Wind Harmer
10.602
971655AH1-328 GEN
Solar/Wind Harmer
2.343
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
960971AF2-388 GEN
Solar/Wind Harmer
3.762
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
270599AE1-208 GEN
Solar/Wind Harmer
5.858
971613AH1-306 GEN
Solar/Wind Harmer
3.066
942221AE2-234 GEN
Solar/Wind Harmer
2.563
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.04
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
972045AH1-571 GEN
Solar/Wind Harmer
1.309
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.711
965681AG1-436 GEN
Solar/Wind Harmer
7.827
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
971587AH1-292 GEN
Solar/Wind Harmer
4.565
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
971125AH1-004 GEN
Solar/Wind Harmer
2.48
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
8.924
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
958481AF2-142 GEN
Solar/Wind Harmer
9.241
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.221
944231AF1-091 GEN
Solar/Wind Harmer
14.169
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.41 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5248.4
MW Contribution:
6.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.247
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270291AC1-194 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
971985AH1-537 GEN
Solar/Wind Harmer
2.039
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
253406AD2-031_GEN
Solar/Wind Harmer
0.497
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
7.194
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270543AE2-219 C
Solar/Wind Harmer
4.502
247536S-71 GEN
Solar/Wind Harmer
0.257
24729505KEY G4
Adder
5.966
945581AF1-223 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
270071AF1-092 GEN
Solar/Wind Harmer
12.235
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
959331AF2-224 GEN
Solar/Wind Harmer
4.437
247521TR3_G114
Solar/Wind Harmer
0.229
965051AG1-369 GEN
Solar/Wind Harmer
3.151
965041AG1-368 GEN
Solar/Wind Harmer
6.303
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270526AF1-158 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
270399AC1-101 GEN
Solar/Wind Harmer
1.959
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
970179AG2-119 GEN
Solar/Wind Harmer
5.512
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.152
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.441
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971171AH1-044 GEN
Solar/Wind Harmer
2.06
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
970879AG2-548 GEN
Solar/Wind Harmer
1.168
270269AC2-059
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
942861AE2-305 GEN
Solar/Wind Harmer
5.328
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
938701AE1-092 GEN
Solar/Wind Harmer
10.602
971655AH1-328 GEN
Solar/Wind Harmer
2.343
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
960971AF2-388 GEN
Solar/Wind Harmer
3.762
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
270599AE1-208 GEN
Solar/Wind Harmer
5.858
971613AH1-306 GEN
Solar/Wind Harmer
3.066
942221AE2-234 GEN
Solar/Wind Harmer
2.563
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.04
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
972045AH1-571 GEN
Solar/Wind Harmer
1.309
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.711
965681AG1-436 GEN
Solar/Wind Harmer
7.827
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
971587AH1-292 GEN
Solar/Wind Harmer
4.565
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
971125AH1-004 GEN
Solar/Wind Harmer
2.48
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
8.924
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
958481AF2-142 GEN
Solar/Wind Harmer
9.241
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.221
944231AF1-091 GEN
Solar/Wind Harmer
14.169
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
29.52
970149AG2-104 GEN
Solar/Wind Harmer
15.941
970155AG2-107 GEN
Solar/Wind Harmer
18.85
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
7.407
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
12.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970825AG2-519 GEN
Solar/Wind Harmer
2.272
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.119
965011AG1-365 GEN
Solar/Wind Harmer
6.339
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.17
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.272
24639705ELKHART HY
Adder
0.138
963741AG1-226 GEN
Solar/Wind Harmer
14.786
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.244
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.617
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.588
962781AG1-127 GEN
Solar/Wind Harmer
5.837
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
970879AG2-548 GEN
Solar/Wind Harmer
5.141
961921AG1-034 GEN
Solar/Wind Harmer
6.223
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.329
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252507AC2-088 GEN
Solar/Wind Harmer
0.298
252519AF1-045_GEN
Solar/Wind Harmer
3.45
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
970191AG2-125 GEN
Solar/Wind Harmer
1.699
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
958171AF2-111 GEN
Solar/Wind Harmer
16.173
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
28.761
270004AE1-209 GEN
Solar/Wind Harmer
1.388
946031AF1-268 GEN
Solar/Wind Harmer
6.094
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
3.154
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.226
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.532
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274887GEN-1.85
Solar/Wind Harmer
0.161
276843GEN-1.7
Solar/Wind Harmer
0.2
276806AD2-047 C O1
Solar/Wind Harmer
3.512
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
970707AG2-453 GEN
Solar/Wind Harmer
20.232
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
965091AG1-374 GEN
Solar/Wind Harmer
18.362
959611AF2-252 GEN
Solar/Wind Harmer
2.04
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
959091AF2-200 GEN
Solar/Wind Harmer
2.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.25 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:5006.21
MW Contribution:
10.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270459AD2-067 GEN
Solar/Wind Harmer
10.212
961821AG1-024 GEN
Solar/Wind Harmer
10.368
972239AH1-704 GEN
Adder
2.66
241955AC1-078 GEN
Solar/Wind Harmer
8.781
241973AD2-163_GEN1
Solar/Wind Harmer
2.319
241974AD2-163_GEN2
Solar/Wind Harmer
2.319
943861AF1-054 GEN
Solar/Wind Harmer
4.476
943851AF1-053 GEN
Solar/Wind Harmer
2.163
945631AF1-228 GEN
Solar/Wind Harmer
5.449
270223U2-072_GEN1
Solar/Wind Harmer
2.274
270224U2-072_GEN2
Solar/Wind Harmer
2.274
270227U2-072_GEN3
Solar/Wind Harmer
2.274
270228U2-072_GEN4
Solar/Wind Harmer
2.274
270231U2-072_GEN5
Solar/Wind Harmer
2.274
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
8.025
253338AC1-165 GEN
Solar/Wind Harmer
1.235
253343AC1-166 GEN
Solar/Wind Harmer
1.235
270302AB2-170 GEN
Solar/Wind Harmer
9.522
940611AE2-048 GEN
Solar/Wind Harmer
24.76
941391AE2-136 GEN
Solar/Wind Harmer
12.83
270263AC1-001 GEN
Solar/Wind Harmer
1.17
241972AD1-140 GEN
Solar/Wind Harmer
5.01
270291AC1-194 GEN
Solar/Wind Harmer
5.61
270340AC2-060 GEN
Solar/Wind Harmer
3.331
970179AG2-119 GEN
Solar/Wind Harmer
8.806
253372AE2-315 SEC3
Adder
2.062
253372AE2-315 SEC3
Adder
2.062
25306009OHH W.
Adder
3.128
253406AD2-031_GEN
Solar/Wind Harmer
1.383
957201AF2-014 GEN
Solar/Wind Harmer
4.888
270435AC2-044 GEN
Solar/Wind Harmer
2.156
253433AC1-085 GEN1
Solar/Wind Harmer
5.708
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.604
270191TR4_S_V150
Solar/Wind Harmer
3.216
965051AG1-369 GEN
Solar/Wind Harmer
5.355
959331AF2-224 GEN
Solar/Wind Harmer
10.725
270377AD1-106 GEN
Solar/Wind Harmer
5.62
270007AE1-245 C
Solar/Wind Harmer
5.779
965041AG1-368 GEN
Solar/Wind Harmer
10.701
24729505KEY G4
Adder
6.914
966831AG1-554 GEN
Solar/Wind Harmer
1.275
971567AH1-282 GEN
Solar/Wind Harmer
5.316
270071AF1-092 GEN
Solar/Wind Harmer
15.971
963791AG1-232 GEN
Solar/Wind Harmer
14.371
971985AH1-537 GEN
Solar/Wind Harmer
18.964
958711AF2-162 GEN
Solar/Wind Harmer
1.074
25196408WSDLE3
Adder
9.339
25196308WSDLE2
Adder
9.258
25196208WSDLE1
Adder
9.235
25196708WSDLE6
Adder
9.211
25196508WSDLE4
Adder
8.979
945581AF1-223 GEN
Solar/Wind Harmer
4.795
971029AG2-637 GEN
Solar/Wind Harmer
15.851
970031AG2-029 GEN
Solar/Wind Harmer
26.415
270404AC1-167 GEN
Solar/Wind Harmer
1.144
270543AE2-219 C
Solar/Wind Harmer
10.561
247536S-71 GEN
Solar/Wind Harmer
4.271
961761AG1-017 GEN
Solar/Wind Harmer
0.451
964611AG1-324 GEN
Solar/Wind Harmer
4.11
25196108MFTGT2
Adder
1.598
25196108MFTGT2
Adder
1.484
274775LINCOLN ;6U
Adder
8.673
274776LINCOLN ;7U
Adder
8.673
274777LINCOLN ;8U
Adder
8.673
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.938
274800UNIV PARK;3U
Adder
5.964
274801UNIV PARK;4U
Adder
5.964
972228AH1-698 GEN2
Adder
3.789
972227AH1-698 GEN1
Adder
2.668
274687WILL CNTY;4U
Adder
28.512
274687WILL CNTY;4U
Adder
28.512
274675JOLIET 29;7U
Adder
31.291
274675JOLIET 29;7U
Adder
30.174
274728ELWOOD EC;5P
Adder
16.762
274731ELWOOD EC;2P
Adder
16.762
274733ELWOOD EC;3P
Adder
16.762
274735ELWOOD EC;4P
Adder
16.762
274744AC1-111 GEN8
Adder
5.677
274746AC1-111 G10
Adder
5.677
23750701CROSSCHOOL
Solar/Wind Helper
1.517
238118U2-030_1
Solar/Wind Helper
0.345
270119AB2-067 GEN1
50/50
7.109
270120AB2-067 GEN2
50/50
7.109
24318905MLG2
50/50
7.027
270349AD2-093_GEN
Solar/Wind Harmer
4.455
270471AD2-092_GEN
Solar/Wind Harmer
4.455
270054AF2-122 C O1
Solar/Wind Harmer
3.972
946101AF1-275 GEN
Solar/Wind Harmer
1.811
253383AE2-342_GEN
Solar/Wind Harmer
1.04
942861AE2-305 GEN
Solar/Wind Harmer
9.069
938701AE1-092 GEN
Solar/Wind Harmer
23.766
270462AD2-086
Solar/Wind Harmer
7.908
270269AC2-059
Solar/Wind Harmer
10.571
253378AE2-206_GEN
Solar/Wind Harmer
3.997
972159AH1-661 GEN
Adder
1.106
253415AE1-040 GEN
Solar/Wind Harmer
1.242
25326509SID D
Adder
1.451
241960AC2-195 GEN
Solar/Wind Harmer
3.055
971073AG2-665 GEN
Solar/Wind Harmer
8.771
970879AG2-548 GEN
Solar/Wind Harmer
1.275
25326109MON D
Adder
1.442
25322209TAIT E
Adder
10.635
25322209TAIT E
Adder
10.396
253370AE2-315 SEC1
Adder
2.18
927014AC1-188 GEN
Solar/Wind Harmer
1.717
253349AC2-067 GEN
Solar/Wind Harmer
2.203
253400AC2-068 GEN
Solar/Wind Harmer
0.886
246937BC-WTG2
Solar/Wind Harmer
4.216
270246TR4_N_V150
Solar/Wind Harmer
0.912
270247TR4_N_V136
Solar/Wind Harmer
0.912
942801AE2-298 GEN
Solar/Wind Harmer
1.621
247607V1-011 GEN
Solar/Wind Harmer
4.231
962581AG1-107 GEN
Solar/Wind Harmer
5.356
961491AF2-440 GEN
Solar/Wind Harmer
2.226
25183208HLCRTG
Solar/Wind Harmer
6.427
944541AF1-119 GEN
Solar/Wind Harmer
4.444
960971AF2-388 GEN
Solar/Wind Harmer
11.601
942221AE2-234 GEN
Solar/Wind Harmer
3.71
25194408D.CRK1
Adder
8
25194508D.CRK3
Adder
1.496
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.561
970885AG2-551 GEN
Solar/Wind Harmer
2.456
270166AC1-044 GEN3
50/50
7.109
23559101PLEAS2
50/50
6.362
962761AG1-125 GEN
Solar/Wind Harmer
41.016
970149AG2-104 GEN
Solar/Wind Harmer
25.328
970155AG2-107 GEN
Solar/Wind Harmer
17.885
270286AF1-227 GEN2
Solar/Wind Harmer
2.504
270520AE2-214 GEN
Solar/Wind Harmer
7.243
270391AF1-285 GEN3
Solar/Wind Harmer
1.393
270578AF1-285 GEN2
Solar/Wind Harmer
1.393
253333AC1-068 GEN
Solar/Wind Harmer
1.191
270317AD1-130_GEN
Solar/Wind Harmer
3.64
270485AE1-090_GEN
Solar/Wind Harmer
0.688
270273AD2-016 GEN
Solar/Wind Harmer
3.013
971995AH1-542 GEN
Solar/Wind Harmer
12.463
972269AH1-719 GEN
Adder
2.545
971073AG2-665 GEN
Solar/Wind Harmer
1.275
25326309TAIT D
Adder
1.195
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
241813AF1-122_GEN
Solar/Wind Harmer
5.897
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.9
238169AE2-226 GEN1
Solar/Wind Helper
0.708
238170AE2-226 GEN2
Solar/Wind Helper
0.708
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.647
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.372
959381AF2-229 GEN
Solar/Wind Helper
0.36
20390526W1-045 C
Solar/Wind Helper
0.354
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.515
205956AE1-196_GEN
Solar/Wind Helper
0.514
233915AB1-141 GEN
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.235
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.795
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
316164AC1-076 GEN
Solar/Wind Helper
1.108
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.069
964851AG1-348 GEN
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
203955AF1-039 C O1
Solar/Wind Helper
0.332
209027LOR2_Q27
Solar/Wind Helper
1.036
212266LOR1
Solar/Wind Helper
0.302
209054AE2-059 GEN
Solar/Wind Helper
0.08
246936BC-WTG1
Solar/Wind Harmer
4.216
270489AE1-102 GEN1
Solar/Wind Harmer
1.401
965421AG1-410 GEN
Solar/Wind Harmer
32.318
960001AF2-291 GEN
Solar/Wind Harmer
3.25
253316AC1-085 GEN3
Solar/Wind Harmer
8.992
946171AF1-282 GEN
Solar/Wind Harmer
10.741
965011AG1-365 GEN
Solar/Wind Harmer
10.725
270258AD1-119 GEN
Solar/Wind Harmer
2.156
965651AG1-433 GEN
Solar/Wind Harmer
5.801
252516AE2-318_GEN
Solar/Wind Harmer
10.604
958861AF2-177 GEN
Solar/Wind Harmer
11.586
270024AE2-089 GEN
Solar/Wind Harmer
4.961
252510AF1-249 C
Solar/Wind Harmer
0.441
25194608D.CRK4
Adder
1.739
945371AF1-202 GEN
Solar/Wind Harmer
7.376
270297AD1-101 GEN
Solar/Wind Harmer
2.147
270222AC2-111 GEN
Solar/Wind Harmer
4.718
944031AF1-071 GEN
Solar/Wind Harmer
1.062
270510AE1-227 GEN1
Solar/Wind Harmer
2.605
270005AE1-210 C O1
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
6.717
270209AC1-174_GEN
Solar/Wind Harmer
4.274
270437AC2-090 C
Solar/Wind Harmer
5.862
270239V3-007_GEN1
Solar/Wind Harmer
1.807
270331AC1-082 GEN3
Solar/Wind Harmer
0.501
25196808ZIMRHP
Adder
79.685
970825AG2-519 GEN
Solar/Wind Harmer
2.203
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.634
25196008MFTGT1
Adder
1.45
274751CRETE EC ;1U
Adder
8.473
274754CRETE EC ;4U
Adder
8.473
274773LINCOLN ;4U
Adder
8.673
274774LINCOLN ;5U
Adder
8.673
274723RIVER EC ;12
Adder
18.412
274812UNIV PK N;8U
Adder
5.137
274802UNIV PARK;5U
Adder
5.968
24728605AND G2
Adder
3.925
274676JOLIET 29;8U
Adder
31.291
274732ELWOOD EC;7P
Adder
16.762
274674JOLIET 9 ;6U
Adder
15.699
972203AH1-686 GEN
Adder
2.344
274745AC1-111 GEN9
Adder
5.677
970091AG2-072 GEN
Adder
77.647
274682WAUKEGAN ;7U
Adder
18.178
316095T157 G97
Solar/Wind Helper
1.515
23583801GRNGAP
Solar/Wind Helper
5.644
238185AF2-356 C
Solar/Wind Helper
2.686
238109AE1-109 GEN2
Solar/Wind Helper
0.115
238120AE2-309 GEN
Solar/Wind Helper
0.534
238126S14_GEN_1
Solar/Wind Helper
0.836
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.667
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.451
237002AB1-128_GEN
Solar/Wind Helper
0.448
23751101LEADS_P59
Solar/Wind Helper
2.15
23777801MSM_W1-116
Solar/Wind Helper
0.116
3141196NOKESVL
Solar/Wind Helper
1.039
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.283
233987AB2-037 GEN
Solar/Wind Helper
2.369
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.235
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.76
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.513
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.118
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.501
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.329
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.091
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.799
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.443
961331AF2-424 GEN
Solar/Wind Helper
0.442
961421AF2-433 GEN
Solar/Wind Helper
0.441
957921AF2-086 GEN
Solar/Wind Helper
0.436
270594AE1-207 GEN
Solar/Wind Harmer
13.371
270032AE2-172
Solar/Wind Harmer
4.579
247621Y3-024
Adder
0.255
270201AC2-176 GEN
Solar/Wind Harmer
5.42
964611AG1-324 GEN
Solar/Wind Harmer
0.551
970349AG2-230 GEN
Solar/Wind Harmer
15.797
270031AE2-169
Solar/Wind Harmer
8.576
270599AE1-208 GEN
Solar/Wind Harmer
8.576
270383AD1-128 GEN
Solar/Wind Harmer
6.419
926881AC1-175 GEN
Solar/Wind Harmer
5.862
247620Y3-023
Adder
0.483
944231AF1-091 GEN
Solar/Wind Harmer
18.887
24728805RICHG1
Adder
3.96
24728905RICHG2
Adder
3.96
274770LINCOLN ;1U
Adder
8.673
274771LINCOLN ;2U
Adder
8.673
274805UNIV PK N;1U
Adder
5.149
274808UNIV PK N;4U
Adder
5.115
274674JOLIET 9 ;6U
Adder
15.699
274696ROCKY RD ;4P
Adder
11.533
274695ROCKY RD ;2P
Adder
11.267
274693ROCKY RD ;1P
Adder
11.156
274697ROCKY RD ;3P
Adder
3.061
274683WAUKEGAN ;8U
Adder
21.305
274683WAUKEGAN ;8U
Adder
9.68
316097T157 G90
Solar/Wind Helper
1.515
235054AD2-180 GEN
Solar/Wind Helper
2.054
23585401KL_K28_T16
Solar/Wind Helper
1.5
235531U2-073 GEN
Solar/Wind Helper
3.347
238117U2-030
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.501
238148AE2-230_GEN2
Solar/Wind Helper
0.501
238149AF1-291A_GEN
Solar/Wind Helper
0.143
23751201ROTHROCK
Solar/Wind Helper
0.836
235020AA1-095 C
Solar/Wind Helper
0.054
237061AD1-155 GEN
Solar/Wind Helper
1.772
238221AF1-254 C O1
Solar/Wind Helper
0.278
237080AD1-060 GEN
Solar/Wind Helper
0.346
235062AE1-101 C1
Solar/Wind Helper
1.678
316411AF1-147_GEN1
Solar/Wind Helper
0.898
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.371
223402AF1-300 C
Solar/Wind Helper
0.371
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.385
232424Y1-079 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.363
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.575
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.972
232428Y3-058 C
Solar/Wind Helper
0.342
232410W1-006 C
Solar/Wind Helper
0.513
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.235
233954AC2-188 GEN
Solar/Wind Helper
0.235
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.182
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.028
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.051
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
961431AF2-434 GEN
Solar/Wind Helper
0.441
24318805MLG1
50/50
10.127
23559001PLEAS1
50/50
6.362
270051AF1-062 GEN
50/50
11.798
270475AD2-096_GEN
50/50
7.137
962771AG1-126 GEN
Solar/Wind Harmer
41.016
970153AG2-106 GEN
Solar/Wind Harmer
17.885
961921AG1-034 GEN
Solar/Wind Harmer
15.551
270284AF1-227 GEN1
Solar/Wind Harmer
6.768
270287AF1-227 GEN3
Solar/Wind Harmer
2.504
24721905FLATG4
Adder
24.045
942051AE2-217 GEN
Solar/Wind Harmer
20.995
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.045
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
270518AE2-148 GEN
Solar/Wind Harmer
13.818
253325AC1-069 GEN
Solar/Wind Harmer
1.191
276820AF1-078_GEN
Solar/Wind Harmer
1.776
958581AF2-149 GEN
Solar/Wind Harmer
4.712
971199AH1-059 GEN
Solar/Wind Harmer
2.312
970879AG2-548 GEN
Solar/Wind Harmer
8.771
960071AF2-298 GEN
Solar/Wind Harmer
1.647
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.717
253394AE2-221_GEN
Solar/Wind Harmer
4.9
246938BC-WTG3
Solar/Wind Harmer
4.289
270491AE1-102 GEN2
Solar/Wind Harmer
1.401
971191AH1-055 GEN
Solar/Wind Harmer
20.077
253317AC1-085 GEN4
Solar/Wind Harmer
8.992
946181AF1-283 GEN
Solar/Wind Harmer
13.963
965021AG1-366 GEN
Solar/Wind Harmer
2.494
958091AF2-103 GEN
Solar/Wind Harmer
0.173
24695305TIMB G C
Solar/Wind Harmer
3.573
270588AE1-091_GEN
Solar/Wind Harmer
11.753
944531AF1-118 GEN
Solar/Wind Harmer
37.358
270043AE2-236 GEN
Solar/Wind Harmer
5.865
252519AF1-045_GEN
Solar/Wind Harmer
3.859
270367AC2-061_GEN
Solar/Wind Harmer
3.367
252524AE2-267 GEN
Solar/Wind Harmer
1.667
25196608WSDLE5
Adder
9.072
25194608D.CRK4
Adder
1.739
252507AC2-088 GEN
Solar/Wind Harmer
1.892
270044AE2-322 C
Solar/Wind Harmer
1.388
270063AE2-323 C
Solar/Wind Harmer
2.32
962031AG1-047 GEN
Solar/Wind Harmer
3.189
957741AF2-068 GEN
Solar/Wind Harmer
15.82
971347AH1-153 GEN
Solar/Wind Harmer
5.266
270512AE1-227 GEN2
Solar/Wind Harmer
2.212
270186AC1-089 GEN
Solar/Wind Harmer
6.425
946031AF1-268 GEN
Solar/Wind Harmer
8.725
270004AE1-209 GEN
Solar/Wind Harmer
5.743
24379505HDWTR1G C
Solar/Wind Harmer
8.305
270240V3-007_GEN2
Solar/Wind Harmer
6.498
270330AC1-082 GEN2
Solar/Wind Harmer
0.5
270329AC1-082 GEN1
Solar/Wind Harmer
0.5
970825AG2-519 GEN
Solar/Wind Harmer
5.915
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.404
274752CRETE EC ;2U
Adder
8.473
274753CRETE EC ;3U
Adder
8.473
274772LINCOLN ;3U
Adder
8.673
274724RIVER EC ;11
Adder
18.196
274814UNIV PK N;0U
Adder
5.182
274807UNIV PK N;3U
Adder
5.171
274811UNIV PK N;7U
Adder
5.137
274803UNIV PARK;6U
Adder
5.968
24728705AND G3
Adder
8.209
24728505AND G1
Adder
3.925
274826FISK ;BP
Adder
11.201
972038AH1-567 GEN2
Adder
0.373
972259AH1-714 GEN
Adder
19.5
274676JOLIET 29;8U
Adder
30.174
274729ELWOOD EC;1P
Adder
16.762
274730ELWOOD EC;6P
Adder
16.762
274734ELWOOD EC;8P
Adder
16.762
274736ELWOOD EC;9P
Adder
16.762
274682WAUKEGAN ;7U
Adder
18.178
964991AG1-363 GEN
Solar/Wind Helper
5.171
238108AE1-109 GEN1
Solar/Wind Helper
0.115
238110AE1-109 GEN3
Solar/Wind Helper
0.115
238127S14_GEN_2
Solar/Wind Helper
0.836
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.715
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.023
235063AE1-101 C2
Solar/Wind Helper
1.678
237001AB1-127_GEN
Solar/Wind Helper
0.446
237048AF1-022 C
Solar/Wind Helper
0.186
316415AF1-147_GEN2
Solar/Wind Helper
0.898
205916AD1-020 GEN
Solar/Wind Helper
1.732
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.514
233918AB1-142 GEN
Solar/Wind Helper
0.508
233944AB2-135 GEN
Solar/Wind Helper
0.596
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.513
232408W1-005 C
Solar/Wind Helper
0.513
316447AC1-158 HLD
Solar/Wind Helper
2.876
316044AC1-158 PL1
Solar/Wind Helper
1.307
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.526
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.075
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.093
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.586
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
202652Y1-033 WT C
Solar/Wind Helper
0.504
961301AF2-421 GEN
Solar/Wind Helper
0.443
963151AG1-164 GEN
Solar/Wind Helper
0.443
961341AF2-425 GEN
Solar/Wind Helper
0.442
212507AE2-042_GEN
Solar/Wind Helper
1.561
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.079
NYPJM->LTFIMP_NY
CLTF
4.85
LGEELTFEXP_LGEE->PJM
CLTF
6.747
WECLTFEXP_WEC->PJM
CLTF
3.823
MECLTFEXP_MEC->PJM
CLTF
15.894
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CPLELTFEXP_CPLE->PJM
CLTF
0.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.743
LAGNLTFEXP_LAGN->PJM
CLTF
14.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.742
TVALTFEXP_TVA->PJM
CLTF
7.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.4 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4974.31
MW Contribution:
10.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.673
270459AD2-067 GEN
Solar/Wind Harmer
10.203
961821AG1-024 GEN
Solar/Wind Harmer
10.359
241955AC1-078 GEN
Solar/Wind Harmer
8.768
241973AD2-163_GEN1
Solar/Wind Harmer
2.315
241974AD2-163_GEN2
Solar/Wind Harmer
2.315
945631AF1-228 GEN
Solar/Wind Harmer
5.44
943861AF1-054 GEN
Solar/Wind Harmer
4.468
943851AF1-053 GEN
Solar/Wind Harmer
2.159
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.013
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
940611AE2-048 GEN
Solar/Wind Harmer
24.928
941391AE2-136 GEN
Solar/Wind Harmer
12.917
270263AC1-001 GEN
Solar/Wind Harmer
1.168
241972AD1-140 GEN
Solar/Wind Harmer
4.999
270291AC1-194 GEN
Solar/Wind Harmer
5.603
970179AG2-119 GEN
Solar/Wind Harmer
8.8
270340AC2-060 GEN
Solar/Wind Harmer
3.323
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.877
270435AC2-044 GEN
Solar/Wind Harmer
2.151
270377AD1-106 GEN
Solar/Wind Harmer
5.62
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.342
959331AF2-224 GEN
Solar/Wind Harmer
10.696
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.674
971567AH1-282 GEN
Solar/Wind Harmer
5.319
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.894
270071AF1-092 GEN
Solar/Wind Harmer
15.924
963791AG1-232 GEN
Solar/Wind Harmer
14.332
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.071
25196408WSDLE3
Adder
9.314
25196308WSDLE2
Adder
9.233
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.955
945581AF1-223 GEN
Solar/Wind Harmer
4.781
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.807
970031AG2-029 GEN
Solar/Wind Harmer
26.342
270543AE2-219 C
Solar/Wind Harmer
10.531
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.099
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.48
274775LINCOLN ;6U
Adder
8.646
274776LINCOLN ;7U
Adder
8.646
274777LINCOLN ;8U
Adder
8.646
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.914
274800UNIV PARK;3U
Adder
5.946
274801UNIV PARK;4U
Adder
5.946
972228AH1-698 GEN2
Adder
3.777
972227AH1-698 GEN1
Adder
2.66
274687WILL CNTY;4U
Adder
28.425
274687WILL CNTY;4U
Adder
28.425
274675JOLIET 29;7U
Adder
31.195
274675JOLIET 29;7U
Adder
30.081
274728ELWOOD EC;5P
Adder
16.71
274731ELWOOD EC;2P
Adder
16.71
274733ELWOOD EC;3P
Adder
16.71
274735ELWOOD EC;4P
Adder
16.71
274744AC1-111 GEN8
Adder
5.66
274746AC1-111 G10
Adder
5.66
23750701CROSSCHOOL
Solar/Wind Helper
1.512
238118U2-030_1
Solar/Wind Helper
0.344
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.644
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.234
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
203955AF1-039 C O1
Solar/Wind Helper
0.331
270166AC1-044 GEN3
50/50
7.082
23559101PLEAS2
50/50
6.18
962761AG1-125 GEN
Solar/Wind Harmer
40.857
970149AG2-104 GEN
Solar/Wind Harmer
25.229
970155AG2-107 GEN
Solar/Wind Harmer
17.815
270520AE2-214 GEN
Solar/Wind Harmer
7.233
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.451
270273AD2-016 GEN
Solar/Wind Harmer
3.008
972269AH1-719 GEN
Adder
2.564
971073AG2-665 GEN
Solar/Wind Harmer
1.273
25326309TAIT D
Adder
1.192
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
241813AF1-122_GEN
Solar/Wind Harmer
5.894
971201AH1-060 GEN
Solar/Wind Harmer
1.842
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.241
960001AF2-291 GEN
Solar/Wind Harmer
3.242
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.696
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.784
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.552
270024AE2-089 GEN
Solar/Wind Harmer
4.947
252510AF1-249 C
Solar/Wind Harmer
0.44
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.355
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270005AE1-210 C O1
Solar/Wind Harmer
5.726
25196808ZIMRHP
Adder
79.465
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
942081AE2-220 GEN
Solar/Wind Harmer
6.698
270209AC1-174_GEN
Solar/Wind Harmer
4.262
270437AC2-090 C
Solar/Wind Harmer
5.845
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.448
274754CRETE EC ;4U
Adder
8.448
274773LINCOLN ;4U
Adder
8.646
274774LINCOLN ;5U
Adder
8.646
274723RIVER EC ;12
Adder
18.356
274812UNIV PK N;8U
Adder
5.122
274802UNIV PARK;5U
Adder
5.949
24728605AND G2
Adder
3.913
274676JOLIET 29;8U
Adder
31.195
274732ELWOOD EC;7P
Adder
16.71
274674JOLIET 9 ;6U
Adder
15.65
972203AH1-686 GEN
Adder
2.333
274745AC1-111 GEN9
Adder
5.66
970091AG2-072 GEN
Adder
77.376
274682WAUKEGAN ;7U
Adder
18.122
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.674
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.532
238126S14_GEN_1
Solar/Wind Helper
0.833
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.663
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.45
237002AB1-128_GEN
Solar/Wind Helper
0.447
23751101LEADS_P59
Solar/Wind Helper
2.129
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.363
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.441
270594AE1-207 GEN
Solar/Wind Harmer
13.331
270032AE2-172
Solar/Wind Harmer
4.566
270119AB2-067 GEN1
50/50
7.082
270120AB2-067 GEN2
50/50
7.082
24318905MLG2
50/50
7.035
270349AD2-093_GEN
Solar/Wind Harmer
4.445
270471AD2-092_GEN
Solar/Wind Harmer
4.445
270054AF2-122 C O1
Solar/Wind Harmer
3.971
946101AF1-275 GEN
Solar/Wind Harmer
1.808
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.053
938701AE1-092 GEN
Solar/Wind Harmer
23.731
270462AD2-086
Solar/Wind Harmer
7.892
270269AC2-059
Solar/Wind Harmer
10.554
972159AH1-661 GEN
Adder
1.111
253378AE2-206_GEN
Solar/Wind Harmer
3.988
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.053
971073AG2-665 GEN
Solar/Wind Harmer
8.757
970879AG2-548 GEN
Solar/Wind Harmer
1.273
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.371
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.713
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.41
944541AF1-119 GEN
Solar/Wind Harmer
4.431
960971AF2-388 GEN
Solar/Wind Harmer
11.568
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.978
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.531
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.405
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.75
270031AE2-169
Solar/Wind Harmer
8.551
270599AE1-208 GEN
Solar/Wind Harmer
8.551
270383AD1-128 GEN
Solar/Wind Harmer
6.401
926881AC1-175 GEN
Solar/Wind Harmer
5.845
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.84
24728805RICHG1
Adder
3.949
24728905RICHG2
Adder
3.949
274770LINCOLN ;1U
Adder
8.646
274771LINCOLN ;2U
Adder
8.646
274805UNIV PK N;1U
Adder
5.133
274808UNIV PK N;4U
Adder
5.099
274674JOLIET 9 ;6U
Adder
15.65
274696ROCKY RD ;4P
Adder
11.497
274695ROCKY RD ;2P
Adder
11.232
274693ROCKY RD ;1P
Adder
11.121
274697ROCKY RD ;3P
Adder
3.051
274683WAUKEGAN ;8U
Adder
21.239
274683WAUKEGAN ;8U
Adder
9.65
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.044
23585401KL_K28_T16
Solar/Wind Helper
1.493
235531U2-073 GEN
Solar/Wind Helper
3.333
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.5
238148AE2-230_GEN2
Solar/Wind Helper
0.5
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.83
237061AD1-155 GEN
Solar/Wind Helper
1.768
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.674
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233982AB2-133 GEN
Solar/Wind Helper
0.362
233946AB2-136 GEN
Solar/Wind Helper
0.574
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
24318805MLG1
50/50
10.084
23559001PLEAS1
50/50
6.18
270051AF1-062 GEN
50/50
11.783
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.857
970153AG2-106 GEN
Solar/Wind Harmer
17.815
961921AG1-034 GEN
Solar/Wind Harmer
15.539
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.892
942051AE2-217 GEN
Solar/Wind Harmer
20.96
960801AF2-371 GEN
Solar/Wind Harmer
2.935
964871AG1-351 GEN
Solar/Wind Harmer
2.026
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.795
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.716
971199AH1-059 GEN
Solar/Wind Harmer
2.315
970879AG2-548 GEN
Solar/Wind Harmer
8.757
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.713
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.279
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.022
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.488
958091AF2-103 GEN
Solar/Wind Harmer
0.172
24695305TIMB G C
Solar/Wind Harmer
3.564
270588AE1-091_GEN
Solar/Wind Harmer
11.739
944531AF1-118 GEN
Solar/Wind Harmer
37.25
270043AE2-236 GEN
Solar/Wind Harmer
5.848
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.18
957741AF2-068 GEN
Solar/Wind Harmer
15.775
971347AH1-153 GEN
Solar/Wind Harmer
5.25
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.7
270004AE1-209 GEN
Solar/Wind Harmer
5.726
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
24379505HDWTR1G C
Solar/Wind Harmer
8.281
270240V3-007_GEN2
Solar/Wind Harmer
6.479
970825AG2-519 GEN
Solar/Wind Harmer
5.897
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.448
274753CRETE EC ;3U
Adder
8.448
274772LINCOLN ;3U
Adder
8.646
274724RIVER EC ;11
Adder
18.141
274814UNIV PK N;0U
Adder
5.166
274807UNIV PK N;3U
Adder
5.155
274811UNIV PK N;7U
Adder
5.122
274803UNIV PARK;6U
Adder
5.949
24728705AND G3
Adder
8.184
24728505AND G1
Adder
3.913
274826FISK ;BP
Adder
11.167
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.441
274676JOLIET 29;8U
Adder
30.081
274729ELWOOD EC;1P
Adder
16.71
274730ELWOOD EC;6P
Adder
16.71
274734ELWOOD EC;8P
Adder
16.71
274736ELWOOD EC;9P
Adder
16.71
274682WAUKEGAN ;7U
Adder
18.122
964991AG1-363 GEN
Solar/Wind Helper
5.16
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.833
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.015
235063AE1-101 C2
Solar/Wind Helper
1.674
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.185
316415AF1-147_GEN2
Solar/Wind Helper
0.896
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.507
233944AB2-135 GEN
Solar/Wind Helper
0.595
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.519
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.582
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
202652Y1-033 WT C
Solar/Wind Helper
0.501
961341AF2-425 GEN
Solar/Wind Helper
0.441
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.966
NYPJM->LTFIMP_NY
CLTF
4.834
LGEELTFEXP_LGEE->PJM
CLTF
6.725
MECLTFEXP_MEC->PJM
CLTF
15.842
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.337
LAGNLTFEXP_LAGN->PJM
CLTF
14.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.682
TVALTFEXP_TVA->PJM
CLTF
7.257
WECLTFEXP_WEC->PJM
CLTF
3.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.01 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4959.97
MW Contribution:
10.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.01 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4959.97
MW Contribution:
10.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4917.49
MW Contribution:
6.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.069
23559101PLEAS2
50/50
6.097
962761AG1-125 GEN
Solar/Wind Harmer
34.394
970149AG2-104 GEN
Solar/Wind Harmer
18.573
970155AG2-107 GEN
Solar/Wind Harmer
21.963
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.894
270273AD2-016 GEN
Solar/Wind Harmer
0.807
972269AH1-719 GEN
Adder
2.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965421AG1-410 GEN
Solar/Wind Harmer
22.47
960001AF2-291 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965011AG1-365 GEN
Solar/Wind Harmer
7.453
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
958861AF2-177 GEN
Solar/Wind Harmer
3.191
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.732
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.351
970825AG2-519 GEN
Solar/Wind Harmer
2.589
24639705ELKHART HY
Adder
0.16
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
276903AD2-071 C
Solar/Wind Harmer
8.095
25196008MFTGT1
Adder
1.443
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.365
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274754CRETE EC ;4U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
274802UNIV PARK;5U
Adder
5.941
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
31.151
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
939401AE1-172 GEN
Solar/Wind Harmer
5.275
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
274682WAUKEGAN ;7U
Adder
18.096
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.818
971997AH1-543 GEN
Solar/Wind Harmer
3.68
962781AG1-127 GEN
Solar/Wind Harmer
6.668
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
316095T157 G97
Solar/Wind Helper
1.51
23583801GRNGAP
Solar/Wind Helper
5.626
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
238126S14_GEN_1
Solar/Wind Helper
0.831
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.661
237038AE2-054 C
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.792
211065PSPA IPP
Solar/Wind Helper
0.152
963161AG1-165 GEN
Solar/Wind Helper
0.441
957471AF2-041 GEN
Solar/Wind Harmer
13.586
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
270119AB2-067 GEN1
50/50
7.069
270120AB2-067 GEN2
50/50
7.069
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.31
938701AE1-092 GEN
Solar/Wind Harmer
12.867
971655AH1-328 GEN
Solar/Wind Harmer
2.843
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
25326509SID D
Adder
1.446
971073AG2-665 GEN
Solar/Wind Harmer
5.597
970879AG2-548 GEN
Solar/Wind Harmer
1.272
25326109MON D
Adder
1.437
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
246937BC-WTG2
Solar/Wind Harmer
0.302
270246TR4_N_V150
Solar/Wind Harmer
0.048
270247TR4_N_V136
Solar/Wind Harmer
0.048
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.351
944541AF1-119 GEN
Solar/Wind Harmer
0.492
960971AF2-388 GEN
Solar/Wind Harmer
4.326
942221AE2-234 GEN
Solar/Wind Harmer
2.958
25194408D.CRK1
Adder
7.968
25194508D.CRK3
Adder
1.49
970621AG2-405 GEN
Solar/Wind Harmer
1.345
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970885AG2-551 GEN
Solar/Wind Harmer
2.446
247621Y3-024
Adder
0.253
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270031AE2-169
Solar/Wind Harmer
4.021
270599AE1-208 GEN
Solar/Wind Harmer
6.701
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728805RICHG1
Adder
3.944
24728905RICHG2
Adder
3.944
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.052
965791AG1-447 GEN
Solar/Wind Harmer
6.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274805UNIV PK N;1U
Adder
5.126
274808UNIV PK N;4U
Adder
5.092
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
276776AD2-060 GEN
Solar/Wind Harmer
0.758
958011AF2-095 GEN
Solar/Wind Harmer
10.234
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
274674JOLIET 9 ;6U
Adder
15.628
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274696ROCKY RD ;4P
Adder
11.481
274695ROCKY RD ;2P
Adder
11.216
274693ROCKY RD ;1P
Adder
11.106
274697ROCKY RD ;3P
Adder
3.047
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276901AD2-066 C O1
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
962691AG1-118 GEN
Solar/Wind Harmer
21.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
942111AE2-223 GEN
Solar/Wind Harmer
2.266
316097T157 G90
Solar/Wind Helper
1.51
235054AD2-180 GEN
Solar/Wind Helper
2.04
23585401KL_K28_T16
Solar/Wind Helper
1.489
235531U2-073 GEN
Solar/Wind Helper
3.327
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.344
235062AE1-101 C1
Solar/Wind Helper
1.672
316411AF1-147_GEN1
Solar/Wind Helper
0.895
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.17
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
24318805MLG1
50/50
10.065
23559001PLEAS1
50/50
6.097
270051AF1-062 GEN
50/50
11.777
270475AD2-096_GEN
50/50
7.114
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
961921AG1-034 GEN
Solar/Wind Harmer
7.586
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
970191AG2-125 GEN
Solar/Wind Harmer
1.937
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
971191AH1-055 GEN
Solar/Wind Harmer
19.175
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
944531AF1-118 GEN
Solar/Wind Harmer
33.233
270043AE2-236 GEN
Solar/Wind Harmer
4.754
252519AF1-045_GEN
Solar/Wind Harmer
3.844
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
9.036
25194608D.CRK4
Adder
1.732
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
971347AH1-153 GEN
Solar/Wind Harmer
3.658
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.95
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
970289AG2-191 GEN
Solar/Wind Harmer
0.8
945111AF1-176 GEN
Solar/Wind Harmer
5.891
247642Z2-115 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
274753CRETE EC ;3U
Adder
8.436
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274811UNIV PK N;7U
Adder
5.114
972167AH1-666 GEN
Solar/Wind Harmer
5.69
274803UNIV PARK;6U
Adder
5.941
24728705AND G3
Adder
8.173
24728505AND G1
Adder
3.908
274887GEN-1.85
Solar/Wind Harmer
0.185
276843GEN-1.7
Solar/Wind Harmer
0.23
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274826FISK ;BP
Adder
11.151
972239AH1-704 GEN
Adder
2.678
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270291AC1-194 GEN
Solar/Wind Harmer
0
970179AG2-119 GEN
Solar/Wind Harmer
6.854
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
253406AD2-031_GEN
Solar/Wind Harmer
0.559
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270377AD1-106 GEN
Solar/Wind Harmer
2.842
247521TR3_G114
Solar/Wind Harmer
0.27
965051AG1-369 GEN
Solar/Wind Harmer
3.723
959331AF2-224 GEN
Solar/Wind Harmer
5.217
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.438
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
963791AG1-232 GEN
Solar/Wind Harmer
9.987
270071AF1-092 GEN
Solar/Wind Harmer
14.177
971985AH1-537 GEN
Solar/Wind Harmer
2.196
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
25196508WSDLE4
Adder
8.944
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
270543AE2-219 C
Solar/Wind Harmer
5.137
247536S-71 GEN
Solar/Wind Harmer
0.293
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
970289AG2-191 GEN
Solar/Wind Harmer
1.382
971771AH1-392 GEN
Solar/Wind Harmer
7.271
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
971549AH1-272 GEN
Solar/Wind Harmer
14.794
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.634
274776LINCOLN ;7U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972228AH1-698 GEN2
Adder
3.772
972227AH1-698 GEN1
Adder
2.656
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
972038AH1-567 GEN2
Adder
0.372
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
972259AH1-714 GEN
Adder
19.413
274676JOLIET 29;8U
Adder
30.039
274729ELWOOD EC;1P
Adder
16.687
274730ELWOOD EC;6P
Adder
16.687
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
274682WAUKEGAN ;7U
Adder
18.096
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970193AG2-126 GEN
Solar/Wind Harmer
10.468
970571AG2-364 GEN
Solar/Wind Harmer
13.944
964991AG1-363 GEN
Solar/Wind Helper
5.155
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.831
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
23562501BACKB
Solar/Wind Helper
1.012
235063AE1-101 C2
Solar/Wind Helper
1.672
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.512
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.594
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.868
316044AC1-158 PL1
Solar/Wind Helper
1.303
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.516
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.58
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
202652Y1-033 WT C
Solar/Wind Helper
0.5
959091AF2-200 GEN
Solar/Wind Harmer
9.057
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
274728ELWOOD EC;5P
Adder
16.687
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274735ELWOOD EC;4P
Adder
16.687
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
274744AC1-111 GEN8
Adder
5.652
274746AC1-111 G10
Adder
5.652
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
970169AG2-114 GEN
Solar/Wind Harmer
7.011
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
971411AH1-196 GEN
Solar/Wind Harmer
10.47
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.32
23750701CROSSCHOOL
Solar/Wind Helper
1.509
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.512
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.062
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.057
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.031
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.69 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4873.53
MW Contribution:
10.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.05
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
962761AG1-125 GEN
Solar/Wind Harmer
40.867
970149AG2-104 GEN
Solar/Wind Harmer
25.235
970155AG2-107 GEN
Solar/Wind Harmer
17.82
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
971995AH1-542 GEN
Solar/Wind Harmer
12.942
972269AH1-719 GEN
Adder
2.693
270317AD1-130_GEN
Solar/Wind Harmer
3.738
270485AE1-090_GEN
Solar/Wind Harmer
0.706
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965421AG1-410 GEN
Solar/Wind Harmer
33.164
971073AG2-665 GEN
Solar/Wind Harmer
1.284
25326309TAIT D
Adder
1.207
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
270297AD1-101 GEN
Solar/Wind Harmer
2.226
965011AG1-365 GEN
Solar/Wind Harmer
10.939
270258AD1-119 GEN
Solar/Wind Harmer
2.219
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
958861AF2-177 GEN
Solar/Wind Harmer
11.712
960001AF2-291 GEN
Solar/Wind Harmer
3.236
24639705ELKHART HY
Adder
0.164
945371AF1-202 GEN
Solar/Wind Harmer
7.453
270216AD2-079_GEN
Solar/Wind Harmer
0.645
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
944031AF1-071 GEN
Solar/Wind Harmer
1.069
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25194608D.CRK4
Adder
1.747
25196808ZIMRHP
Adder
79.955
23906502RICHG2&3
Adder
1.268
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274754CRETE EC ;4U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
274812UNIV PK N;8U
Adder
5.194
274802UNIV PARK;5U
Adder
6.031
23920202STRYCT
Adder
1.44
274676JOLIET 29;8U
Adder
31.606
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
23583801GRNGAP
Solar/Wind Helper
6.383
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
23546401DTGZ2-030
Solar/Wind Helper
0.1
238120AE2-309 GEN
Solar/Wind Helper
0.557
238126S14_GEN_1
Solar/Wind Helper
0.87
237038AE2-054 C
Solar/Wind Helper
0.294
235067AD1-061 GEN
Solar/Wind Helper
0.481
237085AD2-009_GEN
Solar/Wind Helper
1.776
237002AB1-128_GEN
Solar/Wind Helper
0.477
3141196NOKESVL
Solar/Wind Helper
1.144
23777801MSM_W1-116
Solar/Wind Helper
0.123
226910AB2-157 C
Solar/Wind Helper
0.016
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
3132273ORANGE
Solar/Wind Helper
0.049
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
232417X3-008 C
Solar/Wind Helper
0.238
233964AF2-378 GEN
Solar/Wind Helper
0.043
3147666LOUISA
Solar/Wind Helper
0.553
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
233950AC2-186 GEN
Solar/Wind Helper
0.119
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
966881AG1-559 GEN
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
205941AD2-115 GEN
Solar/Wind Helper
0.499
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
24318805MLG1
50/50
10
23559001PLEAS1
50/50
5.445
270051AF1-062 GEN
50/50
11.971
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
270518AE2-148 GEN
Solar/Wind Harmer
13.997
958581AF2-149 GEN
Solar/Wind Harmer
4.955
971199AH1-059 GEN
Solar/Wind Harmer
2.432
24721905FLATG4
Adder
23.444
253325AC1-069 GEN
Solar/Wind Harmer
1.205
970065AG2-057 GEN
Solar/Wind Harmer
0.972
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
961961AG1-039 GEN
Solar/Wind Harmer
3.18
246938BC-WTG3
Solar/Wind Harmer
4.404
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
970879AG2-548 GEN
Solar/Wind Harmer
8.835
958091AF2-103 GEN
Solar/Wind Harmer
0.178
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
972239AH1-704 GEN
50/50
3.095
270459AD2-067 GEN
Solar/Wind Harmer
10.428
961821AG1-024 GEN
Solar/Wind Harmer
10.588
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270302AB2-170 GEN
Solar/Wind Harmer
9.776
270432AC2-029 GEN
Solar/Wind Harmer
8.117
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253338AC1-165 GEN
Solar/Wind Harmer
1.249
253343AC1-166 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270377AD1-106 GEN
Solar/Wind Harmer
5.917
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270291AC1-194 GEN
Solar/Wind Harmer
5.669
270340AC2-060 GEN
Solar/Wind Harmer
3.354
957201AF2-014 GEN
Solar/Wind Harmer
5.019
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
270191TR4_S_V150
Solar/Wind Harmer
3.29
965051AG1-369 GEN
Solar/Wind Harmer
5.479
25306009OHH W.
Adder
3.158
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
958711AF2-162 GEN
Solar/Wind Harmer
1.086
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
270499AE1-146 GEN
Solar/Wind Harmer
2.679
270543AE2-219 C
Solar/Wind Harmer
10.668
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
964611AG1-324 GEN
Solar/Wind Harmer
4.154
971771AH1-392 GEN
Solar/Wind Harmer
9.58
944161AF1-084 GEN
Solar/Wind Harmer
2.352
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196508WSDLE4
Adder
9.023
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274775LINCOLN ;6U
Adder
8.764
274776LINCOLN ;7U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972228AH1-698 GEN2
Adder
3.828
972227AH1-698 GEN1
Adder
2.695
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
274728ELWOOD EC;5P
Adder
16.929
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
274735ELWOOD EC;4P
Adder
16.929
23750701CROSSCHOOL
Solar/Wind Helper
1.591
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
226929AD2-058 GEN
Solar/Wind Helper
0.108
3141426STAFORD
Solar/Wind Helper
0.058
315651AD1-115 GEN
Solar/Wind Helper
0.883
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
959381AF2-229 GEN
Solar/Wind Helper
0.368
20390526W1-045 C
Solar/Wind Helper
0.361
205943AE1-185 GEN
Solar/Wind Helper
0.521
205956AE1-196_GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.238
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
230434AG1-499 GEN
Solar/Wind Helper
0.234
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
20675128HRM_W1-127
Solar/Wind Helper
0.03
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.777
211065PSPA IPP
Solar/Wind Helper
0.151
960841AF2-375 GEN
Solar/Wind Harmer
0.624
24695305TIMB G C
Solar/Wind Harmer
3.661
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270043AE2-236 GEN
Solar/Wind Harmer
5.961
944531AF1-118 GEN
Solar/Wind Harmer
37.819
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971191AH1-055 GEN
Solar/Wind Harmer
20.005
971347AH1-153 GEN
Solar/Wind Harmer
5.342
247643Z2-116 C
Solar/Wind Harmer
0.074
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25196608WSDLE5
Adder
9.116
25194608D.CRK4
Adder
1.747
270367AC2-061_GEN
Solar/Wind Harmer
3.375
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
25196008MFTGT1
Adder
1.409
274752CRETE EC ;2U
Adder
8.571
274753CRETE EC ;3U
Adder
8.571
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274811UNIV PK N;7U
Adder
5.194
274803UNIV PARK;6U
Adder
6.031
274826FISK ;BP
Adder
11.319
972038AH1-567 GEN2
Adder
0.377
972259AH1-714 GEN
Adder
19.698
274676JOLIET 29;8U
Adder
30.477
274729ELWOOD EC;1P
Adder
16.929
274730ELWOOD EC;6P
Adder
16.929
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238108AE1-109 GEN1
Solar/Wind Helper
0.122
238110AE1-109 GEN3
Solar/Wind Helper
0.122
238152AF2-075_GEN
Solar/Wind Helper
0.794
238175AF1-290_GEN
Solar/Wind Helper
0.173
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
235063AE1-101 C2
Solar/Wind Helper
1.786
237001AB1-127_GEN
Solar/Wind Helper
0.476
316415AF1-147_GEN2
Solar/Wind Helper
0.984
23562501BACKB
Solar/Wind Helper
1
316447AC1-158 HLD
Solar/Wind Helper
3.193
316044AC1-158 PL1
Solar/Wind Helper
1.451
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.521
233918AB1-142 GEN
Solar/Wind Helper
0.514
233944AB2-135 GEN
Solar/Wind Helper
0.603
232426Y1-080 FULL
Solar/Wind Helper
0.04
3147666LOUISA
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
232408W1-005 C
Solar/Wind Helper
0.518
316192AB2-158 GEN
Solar/Wind Helper
1.618
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674628WNG_W3-110
Solar/Wind Helper
0.09
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674928WA_W3-044
Solar/Wind Helper
0.099
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.573
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.151
270119AB2-067 GEN1
50/50
7.05
270120AB2-067 GEN2
50/50
7.05
24318905MLG2
50/50
7.451
270054AF2-122 C O1
Solar/Wind Harmer
4.054
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
946101AF1-275 GEN
Solar/Wind Harmer
1.838
253383AE2-342_GEN
Solar/Wind Harmer
1.057
938701AE1-092 GEN
Solar/Wind Harmer
24.428
942861AE2-305 GEN
Solar/Wind Harmer
9.201
270462AD2-086
Solar/Wind Harmer
8.12
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
253415AE1-040 GEN
Solar/Wind Harmer
1.252
25326109MON D
Adder
1.457
246937BC-WTG2
Solar/Wind Harmer
4.329
971073AG2-665 GEN
Solar/Wind Harmer
8.835
970879AG2-548 GEN
Solar/Wind Harmer
1.284
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
942801AE2-298 GEN
Solar/Wind Harmer
1.666
247607V1-011 GEN
Solar/Wind Harmer
4.348
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
270247TR4_N_V136
Solar/Wind Harmer
0.933
247522W1-056 GEN
Solar/Wind Harmer
2.469
253349AC2-067 GEN
Solar/Wind Harmer
2.225
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944231AF1-091 GEN
Solar/Wind Harmer
19.433
942221AE2-234 GEN
Solar/Wind Harmer
3.759
944541AF1-119 GEN
Solar/Wind Harmer
4.494
960971AF2-388 GEN
Solar/Wind Harmer
11.731
247620Y3-023
Adder
0.492
970349AG2-230 GEN
Solar/Wind Harmer
16.027
247621Y3-024
Adder
0.257
25183208HLCRTG
Solar/Wind Harmer
6.454
970883AG2-550 GEN
Solar/Wind Harmer
10.668
970885AG2-551 GEN
Solar/Wind Harmer
2.481
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
270201AC2-176 GEN
Solar/Wind Harmer
5.48
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
24728905RICHG2
Adder
3.989
970935AG2-582 GEN
Adder
238.716
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
238148AE2-230_GEN2
Solar/Wind Helper
0.556
238149AF1-291A_GEN
Solar/Wind Helper
0.159
237061AD1-155 GEN
Solar/Wind Helper
1.974
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
23585401KL_K28_T16
Solar/Wind Helper
1.534
235020AA1-095 C
Solar/Wind Helper
0.058
238117U2-030
Solar/Wind Helper
0.357
238221AF1-254 C O1
Solar/Wind Helper
0.297
237080AD1-060 GEN
Solar/Wind Helper
0.369
235062AE1-101 C1
Solar/Wind Helper
1.786
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
237006AB1-125 GEN
Solar/Wind Helper
0.132
316006AB2-029 C
Solar/Wind Helper
0.131
223401AF1-299 GEN
Solar/Wind Helper
0.389
223402AF1-300 C
Solar/Wind Helper
0.389
316045AC1-158 PL2
Solar/Wind Helper
4.643
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
232424Y1-079 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.581
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
232410W1-006 C
Solar/Wind Helper
0.518
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
966001AG1-469 GEN
Solar/Wind Helper
0.256
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.152
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
NYPJM->LTFIMP_NY
CLTF
4.574
LGEELTFEXP_LGEE->PJM
CLTF
6.731
MECLTFEXP_MEC->PJM
CLTF
15.924
SIGELTFEXP_SIGE->PJM
CLTF
0.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078
WECLTFEXP_WEC->PJM
CLTF
3.853
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4632.89
MW Contribution:
6.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4053.82
MW Contribution:
9.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
3.829
270471AD2-092_GEN
Solar/Wind Harmer
3.829
927014AC1-188 GEN
Solar/Wind Harmer
1.622
946101AF1-275 GEN
Solar/Wind Harmer
1.527
253383AE2-342_GEN
Solar/Wind Harmer
0.892
270269AC2-059
Solar/Wind Harmer
9.392
942861AE2-305 GEN
Solar/Wind Harmer
7.837
253415AE1-040 GEN
Solar/Wind Harmer
1.128
962581AG1-107 GEN
Solar/Wind Harmer
5.045
961491AF2-440 GEN
Solar/Wind Harmer
2.097
971073AG2-665 GEN
Solar/Wind Harmer
8.007
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.254
25183208HLCRTG
Solar/Wind Harmer
6.007
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
253349AC2-067 GEN
Solar/Wind Harmer
2.007
253400AC2-068 GEN
Solar/Wind Harmer
0.807
270054AF2-122 C O1
Solar/Wind Harmer
3.197
944541AF1-119 GEN
Solar/Wind Harmer
4.095
960971AF2-388 GEN
Solar/Wind Harmer
10.691
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
38.42
970149AG2-104 GEN
Solar/Wind Harmer
23.725
970155AG2-107 GEN
Solar/Wind Harmer
16.753
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
3.193
270331AC1-082 GEN3
Solar/Wind Harmer
0.502
270286AF1-227 GEN2
Solar/Wind Harmer
2.151
270520AE2-214 GEN
Solar/Wind Harmer
6.107
270273AD2-016 GEN
Solar/Wind Harmer
2.677
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
1.043
253316AC1-085 GEN3
Solar/Wind Harmer
8.322
946171AF1-282 GEN
Solar/Wind Harmer
9.94
253398AE2-221_GEN2
Solar/Wind Harmer
4.505
252516AE2-318_GEN
Solar/Wind Harmer
9.922
252510AF1-249 C
Solar/Wind Harmer
0.413
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
270391AF1-285 GEN3
Solar/Wind Harmer
1.195
270578AF1-285 GEN2
Solar/Wind Harmer
1.195
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
270222AC2-111 GEN
Solar/Wind Harmer
4.385
944031AF1-071 GEN
Solar/Wind Harmer
0.987
965651AG1-433 GEN
Solar/Wind Harmer
5.345
958861AF2-177 GEN
Solar/Wind Harmer
10.687
942081AE2-220 GEN
Solar/Wind Harmer
6.249
270209AC1-174_GEN
Solar/Wind Harmer
3.977
270437AC2-090 C
Solar/Wind Harmer
5.454
270239V3-007_GEN1
Solar/Wind Harmer
1.681
945371AF1-202 GEN
Solar/Wind Harmer
6.817
945681AF1-233 GEN
Solar/Wind Harmer
18.397
270317AD1-130_GEN
Solar/Wind Harmer
3.123
270485AE1-090_GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
5.332
270594AE1-207 GEN
Solar/Wind Harmer
13.238
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.045
276903AD2-071 C
Solar/Wind Harmer
9.73
270024AE2-089 GEN
Solar/Wind Harmer
4.552
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
9.84
24791305MDL-5G
Solar/Wind Harmer
2.326
965011AG1-365 GEN
Solar/Wind Harmer
9.647
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
7.578
971917AH1-482 GEN
Solar/Wind Harmer
8.743
24728605AND G2
Adder
3.696
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274745AC1-111 GEN9
Adder
5.296
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
958381AF2-132 GEN
Solar/Wind Harmer
6.61
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
38.42
970153AG2-106 GEN
Solar/Wind Harmer
16.753
24686405CER G5
Adder
8.833
270330AC1-082 GEN2
Solar/Wind Harmer
0.501
270329AC1-082 GEN1
Solar/Wind Harmer
0.501
971191AH1-055 GEN
Solar/Wind Harmer
19.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.814
270287AF1-227 GEN3
Solar/Wind Harmer
2.151
957541AF2-048 GEN
Solar/Wind Harmer
1.622
270367AC2-061_GEN
Solar/Wind Harmer
3.183
970879AG2-548 GEN
Solar/Wind Harmer
8.007
942051AE2-217 GEN
Solar/Wind Harmer
18.009
253325AC1-069 GEN
Solar/Wind Harmer
1.043
270186AC1-089 GEN
Solar/Wind Harmer
6.09
270518AE2-148 GEN
Solar/Wind Harmer
12.029
253317AC1-085 GEN4
Solar/Wind Harmer
8.322
946181AF1-283 GEN
Solar/Wind Harmer
12.922
252507AC2-088 GEN
Solar/Wind Harmer
1.779
253394AE2-221_GEN
Solar/Wind Harmer
4.505
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
12.632
253303V4-073 C
Solar/Wind Harmer
0.115
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
252524AE2-267 GEN
Solar/Wind Harmer
1.558
25196608WSDLE5
Adder
8.482
942871AE2-306 GEN
Solar/Wind Harmer
0.896
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
960071AF2-298 GEN
Solar/Wind Harmer
1.495
960801AF2-371 GEN
Solar/Wind Harmer
2.503
964871AG1-351 GEN
Solar/Wind Harmer
1.728
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
34.283
276820AF1-078_GEN
Solar/Wind Harmer
1.561
24379505HDWTR1G C
Solar/Wind Harmer
7.727
270240V3-007_GEN2
Solar/Wind Harmer
6.045
972167AH1-666 GEN
Solar/Wind Harmer
7.81
270004AE1-209 GEN
Solar/Wind Harmer
5.332
946031AF1-268 GEN
Solar/Wind Harmer
8.091
965461AG1-414 GEN
Solar/Wind Harmer
2.21
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.062
970825AG2-519 GEN
Solar/Wind Harmer
5.491
958171AF2-111 GEN
Solar/Wind Harmer
24.35
962031AG1-047 GEN
Solar/Wind Harmer
2.944
957741AF2-068 GEN
Solar/Wind Harmer
14.606
270043AE2-236 GEN
Solar/Wind Harmer
5.338
971347AH1-153 GEN
Solar/Wind Harmer
4.836
24690905MDL-1G C
Solar/Wind Harmer
7.745
970781AG2-491 GEN
Solar/Wind Harmer
9.647
965021AG1-366 GEN
Solar/Wind Harmer
2.244
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
274803UNIV PARK;6U
Adder
5.55
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
972259AH1-714 GEN
Adder
18.154
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
274682WAUKEGAN ;7U
Adder
3.428
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
971985AH1-537 GEN
Solar/Wind Harmer
18.214
270263AC1-001 GEN
Solar/Wind Harmer
1.051
943861AF1-054 GEN
Solar/Wind Harmer
3.868
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
3.034
270432AC2-029 GEN
Solar/Wind Harmer
7.024
241955AC1-078 GEN
Solar/Wind Harmer
7.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.984
241974AD2-163_GEN2
Solar/Wind Harmer
1.984
253338AC1-165 GEN
Solar/Wind Harmer
1.081
253343AC1-166 GEN
Solar/Wind Harmer
1.081
945631AF1-228 GEN
Solar/Wind Harmer
4.679
253406AD2-031_GEN
Solar/Wind Harmer
1.273
241972AD1-140 GEN
Solar/Wind Harmer
4.45
253433AC1-085 GEN1
Solar/Wind Harmer
5.282
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
270459AD2-067 GEN
Solar/Wind Harmer
8.295
961821AG1-024 GEN
Solar/Wind Harmer
8.422
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270223U2-072_GEN1
Solar/Wind Harmer
1.952
270224U2-072_GEN2
Solar/Wind Harmer
1.952
270227U2-072_GEN3
Solar/Wind Harmer
1.952
270228U2-072_GEN4
Solar/Wind Harmer
1.952
270231U2-072_GEN5
Solar/Wind Harmer
1.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
5.023
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
958711AF2-162 GEN
Solar/Wind Harmer
0.989
945581AF1-223 GEN
Solar/Wind Harmer
4.431
971029AG2-637 GEN
Solar/Wind Harmer
14.654
270071AF1-092 GEN
Solar/Wind Harmer
14.639
270543AE2-219 C
Solar/Wind Harmer
9.759
270302AB2-170 GEN
Solar/Wind Harmer
8.168
247536S-71 GEN
Solar/Wind Harmer
3.945
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.799
970289AG2-191 GEN
Solar/Wind Harmer
1.852
964611AG1-324 GEN
Solar/Wind Harmer
3.798
270356AE2-297 GEN
Solar/Wind Harmer
4.491
961761AG1-017 GEN
Solar/Wind Harmer
0.417
957241AF2-018 GEN
Solar/Wind Harmer
4.296
270053AF1-130 C
Solar/Wind Harmer
17.164
963791AG1-232 GEN
Solar/Wind Harmer
13.051
946581AF1-322 GEN
Solar/Wind Harmer
9.871
24691005MDL-2G C
Solar/Wind Harmer
3.567
959331AF2-224 GEN
Solar/Wind Harmer
9.647
959141AF2-205 GEN
Solar/Wind Harmer
5.832
958391AF2-133 GEN
Solar/Wind Harmer
8.746
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
253378AE2-206_GEN
Solar/Wind Harmer
3.513
926881AC1-175 GEN
Solar/Wind Harmer
5.454
270383AD1-128 GEN
Solar/Wind Harmer
5.961
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
9.759
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
6.784
970291AG2-192 GEN
Solar/Wind Harmer
1.267
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
7.939
270599AE1-208 GEN
Solar/Wind Harmer
7.939
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
5.005
24725505WLD G2 C
Solar/Wind Harmer
3.868
24699105WLD G1 C
Solar/Wind Harmer
3.822
942221AE2-234 GEN
Solar/Wind Harmer
3.403
970349AG2-230 GEN
Solar/Wind Harmer
14.508
945421AF1-207 GEN
Solar/Wind Harmer
13.563
957841AF2-078 GEN
Solar/Wind Harmer
5.839
270180AB1-006 GEN1
Solar/Wind Harmer
6.938
24697605MDL-3G C
Solar/Wind Harmer
3.556
24755605MDL-5G
Solar/Wind Harmer
2.326
24697905MDL-4G C
Solar/Wind Harmer
2.214
270181AB1-006 GEN2
Solar/Wind Harmer
0.69
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
274674JOLIET 9 ;6U
Adder
14.625
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.34 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4053.72
MW Contribution:
9.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
5.526
24289405MTG1
50/50
6.082
243186AF1-051 GEN
50/50
6.835
962761AG1-125 GEN
Solar/Wind Harmer
38.451
970149AG2-104 GEN
Solar/Wind Harmer
23.744
970155AG2-107 GEN
Solar/Wind Harmer
16.767
972203AH1-686 GEN
Adder
2.53
24723205RIVRG3
Adder
20.295
24686505CER G6
Adder
8.909
960001AF2-291 GEN
Solar/Wind Harmer
3.196
270331AC1-082 GEN3
Solar/Wind Harmer
0.503
270286AF1-227 GEN2
Solar/Wind Harmer
2.153
270520AE2-214 GEN
Solar/Wind Harmer
6.113
270273AD2-016 GEN
Solar/Wind Harmer
2.68
971073AG2-665 GEN
Solar/Wind Harmer
1.165
253333AC1-068 GEN
Solar/Wind Harmer
1.044
253316AC1-085 GEN3
Solar/Wind Harmer
8.329
946171AF1-282 GEN
Solar/Wind Harmer
9.949
253398AE2-221_GEN2
Solar/Wind Harmer
4.509
24318805MLG1
50/50
7.629
24289405MTG1
50/50
6.082
24721905FLATG4
Adder
26.847
962771AG1-126 GEN
Solar/Wind Harmer
38.451
970153AG2-106 GEN
Solar/Wind Harmer
16.767
24686405CER G5
Adder
8.839
270330AC1-082 GEN2
Solar/Wind Harmer
0.501
270329AC1-082 GEN1
Solar/Wind Harmer
0.501
971191AH1-055 GEN
Solar/Wind Harmer
19.637
270284AF1-227 GEN1
Solar/Wind Harmer
5.82
270287AF1-227 GEN3
Solar/Wind Harmer
2.153
957541AF2-048 GEN
Solar/Wind Harmer
1.623
270367AC2-061_GEN
Solar/Wind Harmer
3.185
970879AG2-548 GEN
Solar/Wind Harmer
8.014
942051AE2-217 GEN
Solar/Wind Harmer
18.027
253325AC1-069 GEN
Solar/Wind Harmer
1.044
270186AC1-089 GEN
Solar/Wind Harmer
6.095
270518AE2-148 GEN
Solar/Wind Harmer
12.041
253317AC1-085 GEN4
Solar/Wind Harmer
8.329
946181AF1-283 GEN
Solar/Wind Harmer
12.933
252507AC2-088 GEN
Solar/Wind Harmer
1.781
253394AE2-221_GEN
Solar/Wind Harmer
4.509
252519AF1-045_GEN
Solar/Wind Harmer
3.614
961921AG1-034 GEN
Solar/Wind Harmer
12.646
253303V4-073 C
Solar/Wind Harmer
0.115
253370AE2-315 SEC1
Adder
1.985
253371AE2-315 SEC2
Adder
1.878
25194608D.CRK4
Adder
1.629
252524AE2-267 GEN
Solar/Wind Harmer
1.56
25196608WSDLE5
Adder
8.49
942871AE2-306 GEN
Solar/Wind Harmer
0.897
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
960071AF2-298 GEN
Solar/Wind Harmer
1.496
960801AF2-371 GEN
Solar/Wind Harmer
2.506
964871AG1-351 GEN
Solar/Wind Harmer
1.73
25196008MFTGT1
Adder
1.325
944531AF1-118 GEN
Solar/Wind Harmer
34.314
276820AF1-078_GEN
Solar/Wind Harmer
1.562
24379505HDWTR1G C
Solar/Wind Harmer
7.734
270240V3-007_GEN2
Solar/Wind Harmer
6.051
972167AH1-666 GEN
Solar/Wind Harmer
7.816
270004AE1-209 GEN
Solar/Wind Harmer
5.336
946031AF1-268 GEN
Solar/Wind Harmer
8.098
965461AG1-414 GEN
Solar/Wind Harmer
2.212
970289AG2-191 GEN
Solar/Wind Harmer
0.749
247642Z2-115 C
Solar/Wind Harmer
0.062
970825AG2-519 GEN
Solar/Wind Harmer
5.495
958171AF2-111 GEN
Solar/Wind Harmer
24.37
962031AG1-047 GEN
Solar/Wind Harmer
2.947
957741AF2-068 GEN
Solar/Wind Harmer
14.62
270043AE2-236 GEN
Solar/Wind Harmer
5.343
971347AH1-153 GEN
Solar/Wind Harmer
4.84
965021AG1-366 GEN
Solar/Wind Harmer
2.246
24690905MDL-1G C
Solar/Wind Harmer
7.751
970781AG2-491 GEN
Solar/Wind Harmer
9.656
24728705AND G3
Adder
7.736
24728505AND G1
Adder
3.699
274772LINCOLN ;3U
Adder
8.068
274752CRETE EC ;2U
Adder
7.868
274753CRETE EC ;3U
Adder
7.868
274724RIVER EC ;11
Adder
16.907
274814UNIV PK N;0U
Adder
4.818
274807UNIV PK N;3U
Adder
4.808
274811UNIV PK N;7U
Adder
4.777
274803UNIV PARK;6U
Adder
5.555
274826FISK ;BP
Adder
10.428
972038AH1-567 GEN2
Adder
0.348
972259AH1-714 GEN
Adder
18.171
274729ELWOOD EC;1P
Adder
15.629
274730ELWOOD EC;6P
Adder
15.629
274734ELWOOD EC;8P
Adder
15.629
274736ELWOOD EC;9P
Adder
15.629
274676JOLIET 29;8U
Adder
28.13
274682WAUKEGAN ;7U
Adder
3.431
23562501BACKB
Solar/Wind Helper
1.061
964991AG1-363 GEN
Solar/Wind Helper
3.902
237048AF1-022 C
Solar/Wind Helper
0.177
238127S14_GEN_2
Solar/Wind Helper
0.723
238108AE1-109 GEN1
Solar/Wind Helper
0.095
238110AE1-109 GEN3
Solar/Wind Helper
0.095
238175AF1-290_GEN
Solar/Wind Helper
0.12
971985AH1-537 GEN
Solar/Wind Harmer
18.229
270263AC1-001 GEN
Solar/Wind Harmer
1.052
943861AF1-054 GEN
Solar/Wind Harmer
3.872
943851AF1-053 GEN
Solar/Wind Harmer
1.871
270432AC2-029 GEN
Solar/Wind Harmer
7.031
270340AC2-060 GEN
Solar/Wind Harmer
3.037
241955AC1-078 GEN
Solar/Wind Harmer
7.469
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253338AC1-165 GEN
Solar/Wind Harmer
1.082
253343AC1-166 GEN
Solar/Wind Harmer
1.082
945631AF1-228 GEN
Solar/Wind Harmer
4.683
253406AD2-031_GEN
Solar/Wind Harmer
1.274
241972AD1-140 GEN
Solar/Wind Harmer
4.454
253433AC1-085 GEN1
Solar/Wind Harmer
5.287
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
270459AD2-067 GEN
Solar/Wind Harmer
8.304
961821AG1-024 GEN
Solar/Wind Harmer
8.431
253372AE2-315 SEC3
Adder
1.878
253372AE2-315 SEC3
Adder
1.878
25196408WSDLE3
Adder
8.74
25196308WSDLE2
Adder
8.664
25196208WSDLE1
Adder
8.642
25196708WSDLE6
Adder
8.62
25196508WSDLE4
Adder
8.403
25306009OHH W.
Adder
2.853
270223U2-072_GEN1
Solar/Wind Harmer
1.954
270224U2-072_GEN2
Solar/Wind Harmer
1.954
270227U2-072_GEN3
Solar/Wind Harmer
1.954
270228U2-072_GEN4
Solar/Wind Harmer
1.954
270231U2-072_GEN5
Solar/Wind Harmer
1.954
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
5.028
25196108MFTGT2
Adder
1.508
25196108MFTGT2
Adder
1.4
24729505KEY G4
Adder
6.358
958711AF2-162 GEN
Solar/Wind Harmer
0.99
945581AF1-223 GEN
Solar/Wind Harmer
4.435
971029AG2-637 GEN
Solar/Wind Harmer
14.667
270071AF1-092 GEN
Solar/Wind Harmer
14.653
270543AE2-219 C
Solar/Wind Harmer
9.768
270302AB2-170 GEN
Solar/Wind Harmer
8.176
247536S-71 GEN
Solar/Wind Harmer
3.949
972163AH1-664 GEN
Solar/Wind Harmer
9.757
972165AH1-665 GEN
Solar/Wind Harmer
7.806
970289AG2-191 GEN
Solar/Wind Harmer
1.853
964611AG1-324 GEN
Solar/Wind Harmer
3.802
270356AE2-297 GEN
Solar/Wind Harmer
4.495
961761AG1-017 GEN
Solar/Wind Harmer
0.417
957241AF2-018 GEN
Solar/Wind Harmer
4.299
270053AF1-130 C
Solar/Wind Harmer
17.176
963791AG1-232 GEN
Solar/Wind Harmer
13.064
959331AF2-224 GEN
Solar/Wind Harmer
9.657
946581AF1-322 GEN
Solar/Wind Harmer
9.879
24691005MDL-2G C
Solar/Wind Harmer
3.57
959141AF2-205 GEN
Solar/Wind Harmer
5.837
958391AF2-133 GEN
Solar/Wind Harmer
8.754
274775LINCOLN ;6U
Adder
8.068
274776LINCOLN ;7U
Adder
8.068
274777LINCOLN ;8U
Adder
8.068
972228AH1-698 GEN2
Adder
3.529
972227AH1-698 GEN1
Adder
2.485
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.39
274800UNIV PARK;3U
Adder
5.553
274801UNIV PARK;4U
Adder
5.553
274687WILL CNTY;4U
Adder
26.575
274687WILL CNTY;4U
Adder
26.575
274728ELWOOD EC;5P
Adder
15.629
274731ELWOOD EC;2P
Adder
15.629
274733ELWOOD EC;3P
Adder
15.629
274735ELWOOD EC;4P
Adder
15.629
274675JOLIET 29;7U
Adder
29.172
274675JOLIET 29;7U
Adder
28.13
274744AC1-111 GEN8
Adder
5.301
274746AC1-111 G10
Adder
5.301
23750701CROSSCHOOL
Solar/Wind Helper
1.289
238118U2-030_1
Solar/Wind Helper
0.304
23750501ELLIOTTS
Solar/Wind Helper
0.621
252516AE2-318_GEN
Solar/Wind Harmer
9.931
252510AF1-249 C
Solar/Wind Harmer
0.413
253370AE2-315 SEC1
Adder
1.985
253371AE2-315 SEC2
Adder
1.878
25194608D.CRK4
Adder
1.629
25326309TAIT D
Adder
1.085
270391AF1-285 GEN3
Solar/Wind Harmer
1.197
270578AF1-285 GEN2
Solar/Wind Harmer
1.197
25196808ZIMRHP
Adder
74.969
970091AG2-072 GEN
Adder
75.547
25196008MFTGT1
Adder
1.368
270222AC2-111 GEN
Solar/Wind Harmer
4.389
944031AF1-071 GEN
Solar/Wind Harmer
0.987
965651AG1-433 GEN
Solar/Wind Harmer
5.35
958861AF2-177 GEN
Solar/Wind Harmer
10.697
945371AF1-202 GEN
Solar/Wind Harmer
6.823
942081AE2-220 GEN
Solar/Wind Harmer
6.255
270209AC1-174_GEN
Solar/Wind Harmer
3.98
270437AC2-090 C
Solar/Wind Harmer
5.459
270239V3-007_GEN1
Solar/Wind Harmer
1.683
945681AF1-233 GEN
Solar/Wind Harmer
18.412
270317AD1-130_GEN
Solar/Wind Harmer
3.126
270485AE1-090_GEN
Solar/Wind Harmer
0.591
270005AE1-210 C O1
Solar/Wind Harmer
5.336
270594AE1-207 GEN
Solar/Wind Harmer
13.25
270032AE2-172
Solar/Wind Harmer
4.538
970825AG2-519 GEN
Solar/Wind Harmer
2.047
276903AD2-071 C
Solar/Wind Harmer
9.739
270024AE2-089 GEN
Solar/Wind Harmer
4.556
944971AF1-162 GEN
Solar/Wind Harmer
6.77
965011AG1-365 GEN
Solar/Wind Harmer
9.657
940581AE2-045 GEN
Solar/Wind Harmer
9.849
24791305MDL-5G
Solar/Wind Harmer
2.328
971605AH1-302 GEN
Solar/Wind Harmer
8.421
24728605AND G2
Adder
3.699
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.068
274774LINCOLN ;5U
Adder
8.068
274751CRETE EC ;1U
Adder
7.868
274754CRETE EC ;4U
Adder
7.868
274723RIVER EC ;12
Adder
17.106
274812UNIV PK N;8U
Adder
4.777
274802UNIV PARK;5U
Adder
5.555
274732ELWOOD EC;7P
Adder
15.629
274676JOLIET 29;8U
Adder
29.172
274674JOLIET 9 ;6U
Adder
14.638
274745AC1-111 GEN9
Adder
5.301
23751101LEADS_P59
Solar/Wind Helper
2.585
238185AF2-356 C
Solar/Wind Helper
2.375
23583801GRNGAP
Solar/Wind Helper
4.46
316095T157 G97
Solar/Wind Helper
1.193
238120AE2-309 GEN
Solar/Wind Helper
0.459
238126S14_GEN_1
Solar/Wind Helper
0.723
238109AE1-109 GEN2
Solar/Wind Helper
0.095
964861AG1-349 GEN
Solar/Wind Harmer
1.402
971917AH1-482 GEN
Solar/Wind Harmer
1.617
270119AB2-067 GEN1
50/50
5.526
270120AB2-067 GEN2
50/50
5.526
243186AF1-051 GEN
50/50
6.835
24318905MLG2
50/50
4.392
24723005RIVRG1
Adder
20.295
24723105RIVRG2
Adder
20.295
270349AD2-093_GEN
Solar/Wind Harmer
3.833
270471AD2-092_GEN
Solar/Wind Harmer
3.833
927014AC1-188 GEN
Solar/Wind Harmer
1.623
946101AF1-275 GEN
Solar/Wind Harmer
1.528
253383AE2-342_GEN
Solar/Wind Harmer
0.893
270269AC2-059
Solar/Wind Harmer
9.401
942861AE2-305 GEN
Solar/Wind Harmer
7.844
253415AE1-040 GEN
Solar/Wind Harmer
1.129
962581AG1-107 GEN
Solar/Wind Harmer
5.049
961491AF2-440 GEN
Solar/Wind Harmer
2.098
971073AG2-665 GEN
Solar/Wind Harmer
8.014
970879AG2-548 GEN
Solar/Wind Harmer
1.165
252509AD1-136 GEN
Solar/Wind Harmer
0.254
25183208HLCRTG
Solar/Wind Harmer
6.012
253370AE2-315 SEC1
Adder
1.985
25194408D.CRK1
Adder
7.492
25194508D.CRK3
Adder
1.401
25326109MON D
Adder
1.302
25322209TAIT E
Adder
9.654
25322209TAIT E
Adder
9.437
253349AC2-067 GEN
Solar/Wind Harmer
2.009
253400AC2-068 GEN
Solar/Wind Harmer
0.808
270054AF2-122 C O1
Solar/Wind Harmer
3.201
944541AF1-119 GEN
Solar/Wind Harmer
4.099
960971AF2-388 GEN
Solar/Wind Harmer
10.701
253378AE2-206_GEN
Solar/Wind Harmer
3.516
926881AC1-175 GEN
Solar/Wind Harmer
5.459
270383AD1-128 GEN
Solar/Wind Harmer
5.966
24728805RICHG1
Adder
3.693
24728905RICHG2
Adder
3.693
970883AG2-550 GEN
Solar/Wind Harmer
9.768
970885AG2-551 GEN
Solar/Wind Harmer
2.272
270462AD2-086
Solar/Wind Harmer
6.791
25326509SID D
Adder
1.283
970291AG2-192 GEN
Solar/Wind Harmer
1.268
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
7.946
270599AE1-208 GEN
Solar/Wind Harmer
7.946
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
5.009
24725505WLD G2 C
Solar/Wind Harmer
3.871
24699105WLD G1 C
Solar/Wind Harmer
3.826
942221AE2-234 GEN
Solar/Wind Harmer
3.406
970349AG2-230 GEN
Solar/Wind Harmer
14.521
945421AF1-207 GEN
Solar/Wind Harmer
13.575
957841AF2-078 GEN
Solar/Wind Harmer
5.844
270180AB1-006 GEN1
Solar/Wind Harmer
6.944
24697605MDL-3G C
Solar/Wind Harmer
3.559
24755605MDL-5G
Solar/Wind Harmer
2.328
24697905MDL-4G C
Solar/Wind Harmer
2.216
270181AB1-006 GEN2
Solar/Wind Harmer
0.69
938701AE1-092 GEN
Solar/Wind Harmer
19.934
247620Y3-023
Adder
0.441
274770LINCOLN ;1U
Adder
8.068
274771LINCOLN ;2U
Adder
8.068
274805UNIV PK N;1U
Adder
4.787
274808UNIV PK N;4U
Adder
4.756
274674JOLIET 9 ;6U
Adder
14.638
274695ROCKY RD ;2P
Adder
10.532
274693ROCKY RD ;1P
Adder
10.429
274697ROCKY RD ;3P
Adder
2.861
274696ROCKY RD ;4P
Adder
10.781
23751201ROTHROCK
Solar/Wind Helper
0.861
23585401KL_K28_T16
Solar/Wind Helper
1.4
235054AD2-180 GEN
Solar/Wind Helper
1.865
238117U2-030
Solar/Wind Helper
0.304
316097T157 G90
Solar/Wind Helper
1.193
235531U2-073 GEN
Solar/Wind Helper
2.906
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.853
NYPJM->LTFIMP_NY
CLTF
4.022
LGEELTFEXP_LGEE->PJM
CLTF
6.535
MECLTFEXP_MEC->PJM
CLTF
15.194
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CPLELTFEXP_CPLE->PJM
CLTF
2.146
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.043
LAGNLTFEXP_LAGN->PJM
CLTF
15.279
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.293
TVALTFEXP_TVA->PJM
CLTF
7.605
WECLTFEXP_WEC->PJM
CLTF
3.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4052.99
MW Contribution:
9.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
38.42
970153AG2-106 GEN
Solar/Wind Harmer
16.753
971985AH1-537 GEN
Solar/Wind Harmer
18.214
270263AC1-001 GEN
Solar/Wind Harmer
1.051
943861AF1-054 GEN
Solar/Wind Harmer
3.868
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
3.034
270432AC2-029 GEN
Solar/Wind Harmer
7.024
241955AC1-078 GEN
Solar/Wind Harmer
7.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.984
241974AD2-163_GEN2
Solar/Wind Harmer
1.984
253338AC1-165 GEN
Solar/Wind Harmer
1.081
253343AC1-166 GEN
Solar/Wind Harmer
1.081
945631AF1-228 GEN
Solar/Wind Harmer
4.679
253406AD2-031_GEN
Solar/Wind Harmer
1.273
241972AD1-140 GEN
Solar/Wind Harmer
4.45
253433AC1-085 GEN1
Solar/Wind Harmer
5.282
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
270459AD2-067 GEN
Solar/Wind Harmer
8.295
961821AG1-024 GEN
Solar/Wind Harmer
8.422
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
38.42
970149AG2-104 GEN
Solar/Wind Harmer
23.725
970155AG2-107 GEN
Solar/Wind Harmer
16.753
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
3.193
270331AC1-082 GEN3
Solar/Wind Harmer
0.502
270286AF1-227 GEN2
Solar/Wind Harmer
2.151
270520AE2-214 GEN
Solar/Wind Harmer
6.107
270273AD2-016 GEN
Solar/Wind Harmer
2.677
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
1.043
253316AC1-085 GEN3
Solar/Wind Harmer
8.322
946171AF1-282 GEN
Solar/Wind Harmer
9.94
253398AE2-221_GEN2
Solar/Wind Harmer
4.505
252516AE2-318_GEN
Solar/Wind Harmer
9.922
252510AF1-249 C
Solar/Wind Harmer
0.413
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
270391AF1-285 GEN3
Solar/Wind Harmer
1.195
270578AF1-285 GEN2
Solar/Wind Harmer
1.195
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
270222AC2-111 GEN
Solar/Wind Harmer
4.385
944031AF1-071 GEN
Solar/Wind Harmer
0.987
965651AG1-433 GEN
Solar/Wind Harmer
5.345
958861AF2-177 GEN
Solar/Wind Harmer
10.687
942081AE2-220 GEN
Solar/Wind Harmer
6.249
270209AC1-174_GEN
Solar/Wind Harmer
3.977
270437AC2-090 C
Solar/Wind Harmer
5.454
270239V3-007_GEN1
Solar/Wind Harmer
1.681
945371AF1-202 GEN
Solar/Wind Harmer
6.817
945681AF1-233 GEN
Solar/Wind Harmer
18.397
270317AD1-130_GEN
Solar/Wind Harmer
3.123
270485AE1-090_GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
5.332
270594AE1-207 GEN
Solar/Wind Harmer
13.238
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.045
276903AD2-071 C
Solar/Wind Harmer
9.73
270024AE2-089 GEN
Solar/Wind Harmer
4.552
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
9.84
24791305MDL-5G
Solar/Wind Harmer
2.326
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
3.829
270471AD2-092_GEN
Solar/Wind Harmer
3.829
927014AC1-188 GEN
Solar/Wind Harmer
1.622
946101AF1-275 GEN
Solar/Wind Harmer
1.527
253383AE2-342_GEN
Solar/Wind Harmer
0.892
270269AC2-059
Solar/Wind Harmer
9.392
942861AE2-305 GEN
Solar/Wind Harmer
7.837
253415AE1-040 GEN
Solar/Wind Harmer
1.128
962581AG1-107 GEN
Solar/Wind Harmer
5.045
961491AF2-440 GEN
Solar/Wind Harmer
2.097
971073AG2-665 GEN
Solar/Wind Harmer
8.007
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.254
25183208HLCRTG
Solar/Wind Harmer
6.007
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
253349AC2-067 GEN
Solar/Wind Harmer
2.007
253400AC2-068 GEN
Solar/Wind Harmer
0.807
270054AF2-122 C O1
Solar/Wind Harmer
3.197
944541AF1-119 GEN
Solar/Wind Harmer
4.095
960971AF2-388 GEN
Solar/Wind Harmer
10.691
253378AE2-206_GEN
Solar/Wind Harmer
3.513
926881AC1-175 GEN
Solar/Wind Harmer
5.454
270383AD1-128 GEN
Solar/Wind Harmer
5.961
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
9.759
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
6.784
970291AG2-192 GEN
Solar/Wind Harmer
1.267
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
7.939
270599AE1-208 GEN
Solar/Wind Harmer
7.939
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
5.005
24725505WLD G2 C
Solar/Wind Harmer
3.868
24699105WLD G1 C
Solar/Wind Harmer
3.822
942221AE2-234 GEN
Solar/Wind Harmer
3.403
970349AG2-230 GEN
Solar/Wind Harmer
14.508
945421AF1-207 GEN
Solar/Wind Harmer
13.563
957841AF2-078 GEN
Solar/Wind Harmer
5.839
270180AB1-006 GEN1
Solar/Wind Harmer
6.938
24697605MDL-3G C
Solar/Wind Harmer
3.556
24755605MDL-5G
Solar/Wind Harmer
2.326
24697905MDL-4G C
Solar/Wind Harmer
2.214
270181AB1-006 GEN2
Solar/Wind Harmer
0.69
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
274674JOLIET 9 ;6U
Adder
14.625
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
24686405CER G5
Adder
8.833
270330AC1-082 GEN2
Solar/Wind Harmer
0.501
270329AC1-082 GEN1
Solar/Wind Harmer
0.501
971191AH1-055 GEN
Solar/Wind Harmer
19.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.814
270287AF1-227 GEN3
Solar/Wind Harmer
2.151
957541AF2-048 GEN
Solar/Wind Harmer
1.622
270367AC2-061_GEN
Solar/Wind Harmer
3.183
970879AG2-548 GEN
Solar/Wind Harmer
8.007
942051AE2-217 GEN
Solar/Wind Harmer
18.009
253325AC1-069 GEN
Solar/Wind Harmer
1.043
270186AC1-089 GEN
Solar/Wind Harmer
6.09
270518AE2-148 GEN
Solar/Wind Harmer
12.029
253317AC1-085 GEN4
Solar/Wind Harmer
8.322
946181AF1-283 GEN
Solar/Wind Harmer
12.922
252507AC2-088 GEN
Solar/Wind Harmer
1.779
253394AE2-221_GEN
Solar/Wind Harmer
4.505
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
12.632
253303V4-073 C
Solar/Wind Harmer
0.115
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
252524AE2-267 GEN
Solar/Wind Harmer
1.558
25196608WSDLE5
Adder
8.482
942871AE2-306 GEN
Solar/Wind Harmer
0.896
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
960071AF2-298 GEN
Solar/Wind Harmer
1.495
960801AF2-371 GEN
Solar/Wind Harmer
2.503
964871AG1-351 GEN
Solar/Wind Harmer
1.728
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
34.283
276820AF1-078_GEN
Solar/Wind Harmer
1.561
24379505HDWTR1G C
Solar/Wind Harmer
7.727
270240V3-007_GEN2
Solar/Wind Harmer
6.045
972167AH1-666 GEN
Solar/Wind Harmer
7.81
270004AE1-209 GEN
Solar/Wind Harmer
5.332
946031AF1-268 GEN
Solar/Wind Harmer
8.091
965461AG1-414 GEN
Solar/Wind Harmer
2.21
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.062
970825AG2-519 GEN
Solar/Wind Harmer
5.491
958171AF2-111 GEN
Solar/Wind Harmer
24.35
962031AG1-047 GEN
Solar/Wind Harmer
2.944
957741AF2-068 GEN
Solar/Wind Harmer
14.606
270043AE2-236 GEN
Solar/Wind Harmer
5.338
971347AH1-153 GEN
Solar/Wind Harmer
4.836
24690905MDL-1G C
Solar/Wind Harmer
7.745
970781AG2-491 GEN
Solar/Wind Harmer
9.647
965021AG1-366 GEN
Solar/Wind Harmer
2.244
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
274803UNIV PARK;6U
Adder
5.55
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
972259AH1-714 GEN
Adder
18.154
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
274682WAUKEGAN ;7U
Adder
3.428
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270223U2-072_GEN1
Solar/Wind Harmer
1.952
270224U2-072_GEN2
Solar/Wind Harmer
1.952
270227U2-072_GEN3
Solar/Wind Harmer
1.952
270228U2-072_GEN4
Solar/Wind Harmer
1.952
270231U2-072_GEN5
Solar/Wind Harmer
1.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
5.023
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
958711AF2-162 GEN
Solar/Wind Harmer
0.989
945581AF1-223 GEN
Solar/Wind Harmer
4.431
971029AG2-637 GEN
Solar/Wind Harmer
14.654
270071AF1-092 GEN
Solar/Wind Harmer
14.639
270543AE2-219 C
Solar/Wind Harmer
9.759
270302AB2-170 GEN
Solar/Wind Harmer
8.168
247536S-71 GEN
Solar/Wind Harmer
3.945
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.799
970289AG2-191 GEN
Solar/Wind Harmer
1.852
964611AG1-324 GEN
Solar/Wind Harmer
3.798
270356AE2-297 GEN
Solar/Wind Harmer
4.491
961761AG1-017 GEN
Solar/Wind Harmer
0.417
957241AF2-018 GEN
Solar/Wind Harmer
4.296
270053AF1-130 C
Solar/Wind Harmer
17.164
963791AG1-232 GEN
Solar/Wind Harmer
13.051
946581AF1-322 GEN
Solar/Wind Harmer
9.871
24691005MDL-2G C
Solar/Wind Harmer
3.567
959331AF2-224 GEN
Solar/Wind Harmer
9.647
959141AF2-205 GEN
Solar/Wind Harmer
5.832
958391AF2-133 GEN
Solar/Wind Harmer
8.746
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
965011AG1-365 GEN
Solar/Wind Harmer
9.647
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
7.578
971917AH1-482 GEN
Solar/Wind Harmer
8.743
24728605AND G2
Adder
3.696
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274745AC1-111 GEN9
Adder
5.296
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
958381AF2-132 GEN
Solar/Wind Harmer
6.61
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.79
MW Contribution:
6.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971985AH1-537 GEN
Solar/Wind Harmer
2.118
270263AC1-001 GEN
Solar/Wind Harmer
0.702
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.516
241972AD1-140 GEN
Solar/Wind Harmer
0.757
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.113
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
247536S-71 GEN
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
7.573
972165AH1-665 GEN
Solar/Wind Harmer
6.065
970289AG2-191 GEN
Solar/Wind Harmer
1.292
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
963791AG1-232 GEN
Solar/Wind Harmer
9.106
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.711
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
965051AG1-369 GEN
Solar/Wind Harmer
3.331
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270399AC1-101 GEN
Solar/Wind Harmer
2.112
270400AC1-102 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.598
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.91
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
971171AH1-044 GEN
Solar/Wind Harmer
11.056
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
32.401
970149AG2-104 GEN
Solar/Wind Harmer
17.497
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
253398AE2-221_GEN2
Solar/Wind Harmer
0
252516AE2-318_GEN
Solar/Wind Harmer
7.753
252510AF1-249 C
Solar/Wind Harmer
0.052
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
965651AG1-433 GEN
Solar/Wind Harmer
2.002
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5
945371AF1-202 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270317AD1-130_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
970773AG2-487 GEN
Solar/Wind Harmer
1.2
276903AD2-071 C
Solar/Wind Harmer
7.58
270024AE2-089 GEN
Solar/Wind Harmer
0.001
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.743
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
941551AE2-152 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
939401AE1-172 GEN
Solar/Wind Harmer
4.951
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.213
962781AG1-127 GEN
Solar/Wind Harmer
6.263
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
19.691
971403AH1-188 GEN
Solar/Wind Harmer
9.18
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
24686405CER G5
Adder
8.833
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
942051AE2-217 GEN
Solar/Wind Harmer
12.564
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.57
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252507AC2-088 GEN
Solar/Wind Harmer
0.312
253394AE2-221_GEN
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
6.169
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
970191AG2-125 GEN
Solar/Wind Harmer
1.771
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
30.627
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
270004AE1-209 GEN
Solar/Wind Harmer
1.475
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.122
958171AF2-111 GEN
Solar/Wind Harmer
16.988
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
971347AH1-153 GEN
Solar/Wind Harmer
3.374
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.73
965021AG1-366 GEN
Solar/Wind Harmer
2.244
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
24386205FR-12G C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
276843GEN-1.7
Solar/Wind Harmer
0.215
276806AD2-047 C O1
Solar/Wind Harmer
3.764
274803UNIV PARK;6U
Adder
5.55
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
970707AG2-453 GEN
Solar/Wind Harmer
21.689
972259AH1-714 GEN
Adder
18.154
24695305TIMB G C
Solar/Wind Harmer
0.562
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
246938BC-WTG3
Solar/Wind Harmer
0.239
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
274682WAUKEGAN ;7U
Adder
3.428
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
965091AG1-374 GEN
Solar/Wind Harmer
19.702
959611AF2-252 GEN
Solar/Wind Harmer
2.189
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
959091AF2-200 GEN
Solar/Wind Harmer
11.056
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971073AG2-665 GEN
Solar/Wind Harmer
5.121
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
270054AF2-122 C O1
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
4.003
970329AG2-216 GEN
Solar/Wind Harmer
2.946
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
3.738
270599AE1-208 GEN
Solar/Wind Harmer
6.229
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.725
970349AG2-230 GEN
Solar/Wind Harmer
10.122
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.761
965681AG1-436 GEN
Solar/Wind Harmer
8.373
965791AG1-447 GEN
Solar/Wind Harmer
6.14
970241AG2-163 GEN
Solar/Wind Harmer
3.903
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
270247TR4_N_V136
Solar/Wind Harmer
0.043
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
972043AH1-570 GEN
Solar/Wind Harmer
1.73
972045AH1-571 GEN
Solar/Wind Harmer
1.386
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
276776AD2-060 GEN
Solar/Wind Harmer
0.708
958011AF2-095 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
958481AF2-142 GEN
Solar/Wind Harmer
9.909
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
958491AF2-143 GEN
Solar/Wind Harmer
9.89
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
971125AH1-004 GEN
Solar/Wind Harmer
2.63
970107AG2-081 GEN
Solar/Wind Harmer
1.973
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.62
MW Contribution:
6.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971985AH1-537 GEN
Solar/Wind Harmer
2.118
270263AC1-001 GEN
Solar/Wind Harmer
0.702
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.516
241972AD1-140 GEN
Solar/Wind Harmer
0.757
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.113
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
247536S-71 GEN
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
7.573
972165AH1-665 GEN
Solar/Wind Harmer
6.065
970289AG2-191 GEN
Solar/Wind Harmer
1.292
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
963791AG1-232 GEN
Solar/Wind Harmer
9.106
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.711
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
965051AG1-369 GEN
Solar/Wind Harmer
3.331
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270399AC1-101 GEN
Solar/Wind Harmer
2.112
270400AC1-102 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
32.401
970149AG2-104 GEN
Solar/Wind Harmer
17.497
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
253398AE2-221_GEN2
Solar/Wind Harmer
0
252516AE2-318_GEN
Solar/Wind Harmer
7.753
252510AF1-249 C
Solar/Wind Harmer
0.052
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
24686405CER G5
Adder
8.833
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
942051AE2-217 GEN
Solar/Wind Harmer
12.564
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.57
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252507AC2-088 GEN
Solar/Wind Harmer
0.312
253394AE2-221_GEN
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
6.169
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
970191AG2-125 GEN
Solar/Wind Harmer
1.771
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
30.627
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
270004AE1-209 GEN
Solar/Wind Harmer
1.475
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.122
958171AF2-111 GEN
Solar/Wind Harmer
16.988
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
971347AH1-153 GEN
Solar/Wind Harmer
3.374
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.73
965021AG1-366 GEN
Solar/Wind Harmer
2.244
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
24386205FR-12G C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
276843GEN-1.7
Solar/Wind Harmer
0.215
276806AD2-047 C O1
Solar/Wind Harmer
3.764
274803UNIV PARK;6U
Adder
5.55
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
970707AG2-453 GEN
Solar/Wind Harmer
21.689
972259AH1-714 GEN
Adder
18.154
24695305TIMB G C
Solar/Wind Harmer
0.562
274729ELWOOD EC;1P
Adder
15.615
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971073AG2-665 GEN
Solar/Wind Harmer
5.121
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
270054AF2-122 C O1
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
4.003
970329AG2-216 GEN
Solar/Wind Harmer
2.946
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
3.738
270599AE1-208 GEN
Solar/Wind Harmer
6.229
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.725
970349AG2-230 GEN
Solar/Wind Harmer
10.122
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.761
965681AG1-436 GEN
Solar/Wind Harmer
8.373
965791AG1-447 GEN
Solar/Wind Harmer
6.14
970241AG2-163 GEN
Solar/Wind Harmer
3.903
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
270247TR4_N_V136
Solar/Wind Harmer
0.043
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
972043AH1-570 GEN
Solar/Wind Harmer
1.73
972045AH1-571 GEN
Solar/Wind Harmer
1.386
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
276776AD2-060 GEN
Solar/Wind Harmer
0.708
958011AF2-095 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
958481AF2-142 GEN
Solar/Wind Harmer
9.909
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
958491AF2-143 GEN
Solar/Wind Harmer
9.89
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
971125AH1-004 GEN
Solar/Wind Harmer
2.63
970107AG2-081 GEN
Solar/Wind Harmer
1.973
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.598
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.91
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
971171AH1-044 GEN
Solar/Wind Harmer
11.056
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
965651AG1-433 GEN
Solar/Wind Harmer
2.002
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5
945371AF1-202 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270317AD1-130_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
970773AG2-487 GEN
Solar/Wind Harmer
1.2
276903AD2-071 C
Solar/Wind Harmer
7.58
270024AE2-089 GEN
Solar/Wind Harmer
0.001
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.743
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
941551AE2-152 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
939401AE1-172 GEN
Solar/Wind Harmer
4.951
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.213
962781AG1-127 GEN
Solar/Wind Harmer
6.263
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
19.691
971403AH1-188 GEN
Solar/Wind Harmer
9.18
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
246938BC-WTG3
Solar/Wind Harmer
0.239
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
274682WAUKEGAN ;7U
Adder
3.428
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
965091AG1-374 GEN
Solar/Wind Harmer
19.702
959611AF2-252 GEN
Solar/Wind Harmer
2.189
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
959091AF2-200 GEN
Solar/Wind Harmer
11.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
5.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
12.886
958121AF2-106 GEN
Solar/Wind Harmer
0.001
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
941801AE2-185 GEN
Solar/Wind Harmer
7.447
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.535
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24686405CER G5
Adder
9.787
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
970093AG2-073 GEN
Solar/Wind Harmer
6.071
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.034
970455AG2-298 GEN
Solar/Wind Harmer
2.725
972167AH1-666 GEN
Solar/Wind Harmer
5.413
958171AF2-111 GEN
Solar/Wind Harmer
16.661
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
4.688
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
942481AE2-261 GEN
Solar/Wind Harmer
18.979
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
15.863
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
18.636
959611AF2-252 GEN
Solar/Wind Harmer
2.071
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
970571AG2-364 GEN
Solar/Wind Harmer
12.283
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946671AF1-331 GEN
Solar/Wind Harmer
0.653
270004AE1-209 GEN
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
4.603
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
276843GEN-1.7
Solar/Wind Harmer
0.195
276806AD2-047 C O1
Solar/Wind Harmer
3.42
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
6.744
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
270069AE2-166 C O1
Solar/Wind Harmer
10.375
971313AH1-133 GEN
Solar/Wind Harmer
5.363
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
2.889
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
970281AG2-184 GEN
Solar/Wind Harmer
18.909
971981AH1-535 GEN
Solar/Wind Harmer
5.838
971061AG2-657 GEN
Solar/Wind Harmer
5.362
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972163AH1-664 GEN
Solar/Wind Harmer
7.559
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
270356AE2-297 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.464
963841AG1-237 GEN
Solar/Wind Harmer
2.696
946321AF1-296 GEN
Solar/Wind Harmer
3.479
274854TWINGROVE;U2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.498
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
972267AH1-718 GEN
Adder
3.684
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
926823AC1-168 GEN
Solar/Wind Harmer
1.044
970169AG2-114 GEN
Solar/Wind Harmer
6.143
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
270263AC1-001 GEN
Solar/Wind Harmer
0.61
970073AG2-061 GEN
Solar/Wind Harmer
2.033
971029AG2-637 GEN
Solar/Wind Harmer
9.145
270543AE2-219 C
Solar/Wind Harmer
4.252
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
247536S-71 GEN
Solar/Wind Harmer
0.242
25306009OHH W.
Adder
2.5
971609AH1-304 GEN
Solar/Wind Harmer
0.988
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
964611AG1-324 GEN
Solar/Wind Harmer
2.357
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
3147312GRETNA
Solar/Wind Harmer
0.047
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
5.335
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
0.947
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
960001AF2-291 GEN
Solar/Wind Harmer
0
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
945681AF1-233 GEN
Solar/Wind Harmer
12.766
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
7.186
252510AF1-249 C
Solar/Wind Harmer
0.048
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
276621W2-048 GEN
Solar/Wind Harmer
0.315
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
253398AE2-221_GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24385905FR-11G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
970819AG2-516 GEN
Solar/Wind Harmer
7.371
970569AG2-363 GEN
Solar/Wind Harmer
18.425
274822ROCKFORD ;11
Adder
17.258
957471AF2-041 GEN
Solar/Wind Harmer
18.391
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
274745AC1-111 GEN9
Adder
4.865
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
941551AE2-152 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
7.838
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971277AH1-098 GEN
Solar/Wind Harmer
5.174
942671AE2-283 GEN
Solar/Wind Harmer
5.792
970913AG2-568 GEN
Solar/Wind Harmer
7.67
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
964571AG1-320 GEN
Solar/Wind Harmer
6.355
971125AH1-004 GEN
Solar/Wind Harmer
2.78
970107AG2-081 GEN
Solar/Wind Harmer
2.085
972043AH1-570 GEN
Solar/Wind Harmer
1.794
972045AH1-571 GEN
Solar/Wind Harmer
1.437
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
4.796
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276916AD2-100_GEN
Solar/Wind Harmer
13.351
276911AD2-131_GEN
Solar/Wind Harmer
0.879
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960201AF2-311 GEN
Solar/Wind Harmer
5.7
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
938861AE1-114 GEN
Solar/Wind Harmer
3.487
270383AD1-128 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
970885AG2-551 GEN
Solar/Wind Harmer
2.025
276893AG1-478 C
Solar/Wind Harmer
0.404
274674JOLIET 9 ;6U
Adder
13.36
270031AE2-169
Solar/Wind Harmer
3.328
270599AE1-208 GEN
Solar/Wind Harmer
5.547
276897AD1-100 C
Solar/Wind Harmer
15.124
964611AG1-324 GEN
Solar/Wind Harmer
0.453
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
276776AD2-060 GEN
Solar/Wind Harmer
0.644
958011AF2-095 GEN
Solar/Wind Harmer
8.691
970941AG2-585 GEN
Solar/Wind Harmer
3.319
270201AC2-176 GEN
Solar/Wind Harmer
0
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.66 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4175.28
MW Contribution:
8.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.197
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24728305BUCHG2
50/50
7.18
270173AC1-122 GEN
Solar/Wind Harmer
3.446
316217AC1-145 GEN
Solar/Wind Harmer
4.244
316197AC1-042 GEN
Solar/Wind Harmer
3.217
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.474
270336AE1-100 GEN
Solar/Wind Harmer
2.754
943811AF1-049 GEN
Solar/Wind Harmer
5.701
958131AF2-107 GEN
Solar/Wind Harmer
7.107
24735205WLF2G2
Adder
8.042
971687AH1-348 GEN
Solar/Wind Harmer
1.363
971403AH1-188 GEN
Solar/Wind Harmer
18.915
944971AF1-162 GEN
Solar/Wind Harmer
9.1
24723205RIVRG3
Adder
23.046
24686505CER G6
Adder
9.917
972203AH1-686 GEN
Adder
2.716
270331AC1-082 GEN3
Solar/Wind Harmer
0.515
339211AE2-254 GEN
Solar/Wind Harmer
1.567
964901AG1-354 GEN
Solar/Wind Harmer
15.55
960001AF2-291 GEN
Solar/Wind Harmer
3.133
339241AF1-083 GEN
Solar/Wind Harmer
1.722
3429241JKCT 3G
Adder
12.084
970653AG2-424 GEN
Solar/Wind Harmer
4.903
3429421JKCT 10G
Adder
8.441
943111AE2-339 GEN
Solar/Wind Harmer
0.887
339221AD2-048_GEN
Solar/Wind Harmer
1.518
945681AF1-233 GEN
Solar/Wind Harmer
18.414
970091AG2-072 GEN
Adder
74.384
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
71.001
25196008MFTGT1
Adder
1.3
252516AE2-318_GEN
Solar/Wind Harmer
9.259
252510AF1-249 C
Solar/Wind Harmer
0.385
971073AG2-665 GEN
Solar/Wind Harmer
1.074
25194608D.CRK4
Adder
1.517
965911AG1-460 GEN
Solar/Wind Harmer
1.277
253316AC1-085 GEN3
Solar/Wind Harmer
7.64
946171AF1-282 GEN
Solar/Wind Harmer
9.125
24728605AND G2
Adder
3.5
276621W2-048 GEN
Solar/Wind Harmer
5.671
276686W4-005 GEN3
Solar/Wind Harmer
2.739
963741AG1-226 GEN
Solar/Wind Harmer
40.583
253398AE2-221_GEN2
Solar/Wind Harmer
4.079
270222AC2-111 GEN
Solar/Wind Harmer
4.015
944031AF1-071 GEN
Solar/Wind Harmer
0.903
276655WTG1_EQ
Solar/Wind Harmer
7.791
276656WTG2_EQ
Solar/Wind Harmer
1.032
939741AE1-205 GEN
Solar/Wind Harmer
17.852
274761LEE CO EC;2U
Adder
8.264
274766LEE CO EC;7U
Adder
8.167
274822ROCKFORD ;11
Adder
17.365
274828WAUKEGAN ;BP
Adder
9.706
274682WAUKEGAN ;7U
Adder
15.786
274745AC1-111 GEN9
Adder
4.896
274732ELWOOD EC;7P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
274674JOLIET 9 ;6U
Adder
13.445
274676JOLIET 29;8U
Adder
22.605
3148013FISHERV
Solar/Wind Helper
0.524
316499AE2-029_GEN
Solar/Wind Helper
1.728
315821AE2-092 GEN
Solar/Wind Helper
3.236
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.324
316095T157 G97
Solar/Wind Helper
1.135
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.393
24385905FR-11G C
Solar/Wind Harmer
5.645
24386605FR-22G C
Solar/Wind Harmer
2.921
970823AG2-518 GEN
50/50
8.391
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.212
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
15.01
970563AG2-360 GEN
50/50
45.925
970417AG2-272 GEN
50/50
3.737
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.417
943031AE2-326 GEN
Solar/Wind Harmer
6.794
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.813
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.976
270030AE2-140 GEN
Solar/Wind Harmer
30.957
270018AE2-047 C O1
Solar/Wind Harmer
1.823
960911AF2-382 GEN
Solar/Wind Harmer
10.976
270016AE1-250 BESS
Solar/Wind Harmer
3.251
971461AH1-227 GEN
Solar/Wind Harmer
7.023
970223AG2-152 GEN
Solar/Wind Harmer
17.677
972103AH1-617 GEN
Solar/Wind Harmer
25.917
24686405CER G5
Adder
9.839
270330AC1-082 GEN2
Solar/Wind Harmer
0.514
270329AC1-082 GEN1
Solar/Wind Harmer
0.514
972273AH1-721 GEN
Adder
89.66
24721905FLATG4
Adder
21.789
339255AE2-071 GEN
Solar/Wind Harmer
1.222
339250AF1-203 GEN
Solar/Wind Harmer
0.629
339206AE1-143 GEN
Solar/Wind Harmer
2.213
970093AG2-073 GEN
Solar/Wind Harmer
5.468
970653AG2-424 GEN
Solar/Wind Harmer
0.709
971191AH1-055 GEN
Solar/Wind Harmer
18.939
3429391JKCT 9G
Adder
8.441
970455AG2-298 GEN
Solar/Wind Harmer
3.536
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972167AH1-666 GEN
Solar/Wind Harmer
7.807
957541AF2-048 GEN
Solar/Wind Harmer
1.537
958171AF2-111 GEN
Solar/Wind Harmer
24.034
270186AC1-089 GEN
Solar/Wind Harmer
5.851
270367AC2-061_GEN
Solar/Wind Harmer
3.02
252507AC2-088 GEN
Solar/Wind Harmer
1.676
25196008MFTGT1
Adder
1.259
252519AF1-045_GEN
Solar/Wind Harmer
3.37
970879AG2-548 GEN
Solar/Wind Harmer
7.39
25194608D.CRK4
Adder
1.517
252524AE2-267 GEN
Solar/Wind Harmer
1.45
25196608WSDLE5
Adder
7.893
970193AG2-126 GEN
Solar/Wind Harmer
13.761
942481AE2-261 GEN
Solar/Wind Harmer
27.366
957381AF2-032 GEN
Solar/Wind Harmer
1.829
253317AC1-085 GEN4
Solar/Wind Harmer
7.64
946181AF1-283 GEN
Solar/Wind Harmer
11.863
24728705AND G3
Adder
7.32
24728505AND G1
Adder
3.5
276785W4-005 GEN1
Solar/Wind Harmer
2.739
971993AH1-541 GEN
Solar/Wind Harmer
8.371
253394AE2-221_GEN
Solar/Wind Harmer
4.079
965931AG1-462 GEN
Solar/Wind Harmer
22.875
971087AG2-675 GEN
Solar/Wind Harmer
3.338
965091AG1-374 GEN
Solar/Wind Harmer
26.876
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274760LEE CO EC;1U
Adder
8.264
274767LEE CO EC;8U
Adder
8.167
274682WAUKEGAN ;7U
Adder
15.786
274729ELWOOD EC;1P
Adder
14.355
274730ELWOOD EC;6P
Adder
14.355
274734ELWOOD EC;8P
Adder
14.355
274736ELWOOD EC;9P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.852
3147666LOUISA
Solar/Wind Helper
1.093
238152AF2-075_GEN
Solar/Wind Helper
0.608
316447AC1-158 HLD
Solar/Wind Helper
2.79
316044AC1-158 PL1
Solar/Wind Helper
1.268
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.222
24386205FR-12G C
Solar/Wind Harmer
2.911
971543AH1-269 GEN
50/50
12.26
24684705SMG5
50/50
0.846
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.387
971329AH1-144 GEN
Solar/Wind Harmer
11.745
966391AG1-508 GEN
Solar/Wind Harmer
6.384
270197AD1-017 GEN1
Solar/Wind Harmer
2.542
270069AE2-166 C O1
Solar/Wind Harmer
14.894
971313AH1-133 GEN
Solar/Wind Harmer
9.348
24734705WLF1G3
Adder
8.213
24734805WLF1G4
Adder
8.213
24734905WLF1G5
Adder
8.213
24735105WLF2G1
Adder
8.042
270399AC1-101 GEN
Solar/Wind Harmer
5.575
270400AC1-102 GEN
Solar/Wind Harmer
5.575
941621AE2-160 GEN
Adder
4.304
957241AF2-018 GEN
Solar/Wind Harmer
5.778
270053AF1-130 C
Solar/Wind Harmer
23.086
970281AG2-184 GEN
Solar/Wind Harmer
27.213
971981AH1-535 GEN
Solar/Wind Harmer
12.593
962211AG1-066 GEN
Solar/Wind Harmer
3.011
971061AG2-657 GEN
Solar/Wind Harmer
11.048
3429211JKCT 2G
Adder
11.928
339216AC1-074 GEN
Solar/Wind Harmer
1.652
972163AH1-664 GEN
Solar/Wind Harmer
9.793
972165AH1-665 GEN
Solar/Wind Harmer
7.834
971985AH1-537 GEN
Solar/Wind Harmer
17.394
270444AC2-157 GEN1
Solar/Wind Harmer
5.263
270445AC2-157 GEN2
Solar/Wind Harmer
5.263
25196108MFTGT2
Adder
1.433
25196108MFTGT2
Adder
1.331
944221AF1-090 GEN
Solar/Wind Harmer
10.074
25196408WSDLE3
Adder
8.125
25196308WSDLE2
Adder
8.054
25196208WSDLE1
Adder
8.034
25196708WSDLE6
Adder
8.014
25196508WSDLE4
Adder
7.812
253433AC1-085 GEN1
Solar/Wind Harmer
4.849
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
276763AC1-053 GEN1
Solar/Wind Harmer
3.586
276764AC1-053 GEN2
Solar/Wind Harmer
3.586
276668AB2-070 GEN1
Solar/Wind Harmer
2.006
276848AB2-070 GEN3
Solar/Wind Harmer
2.006
276849AB2-070 GEN2
Solar/Wind Harmer
2.006
270356AE2-297 GEN
Solar/Wind Harmer
4.168
253406AD2-031_GEN
Solar/Wind Harmer
1.153
270291AC1-194 GEN
Solar/Wind Harmer
4.567
963841AG1-237 GEN
Solar/Wind Harmer
9.807
946321AF1-296 GEN
Solar/Wind Harmer
9.347
274853TWINGROVE;U1
Solar/Wind Harmer
6.454
274854TWINGROVE;U2
Solar/Wind Harmer
6.319
270340AC2-060 GEN
Solar/Wind Harmer
2.703
276726Z2-087_GEN
Solar/Wind Harmer
7.058
959341AF2-225 GEN
Solar/Wind Harmer
13.389
972267AH1-718 GEN
Adder
3.707
274823ROCKFORD ;21
Adder
17.239
274744AC1-111 GEN8
Adder
4.896
274746AC1-111 G10
Adder
4.896
25306009OHH W.
Adder
2.518
274728ELWOOD EC;5P
Adder
14.355
274731ELWOOD EC;2P
Adder
14.355
274733ELWOOD EC;3P
Adder
14.355
274735ELWOOD EC;4P
Adder
14.355
253372AE2-315 SEC3
Adder
1.655
253372AE2-315 SEC3
Adder
1.655
274675JOLIET 29;7U
Adder
26.781
315616AA1-038_C
Solar/Wind Helper
3.299
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.846
316164AC1-076 GEN
Solar/Wind Helper
1.182
316258AE1-075 C
Solar/Wind Helper
0.321
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.093
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
3141426STAFORD
Solar/Wind Helper
0.049
24386405FR-21G C
Solar/Wind Harmer
2.921
24387005FR-3G C
Solar/Wind Harmer
2.686
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.18
270583AD2-179 GEN
Solar/Wind Harmer
20.746
270214AC2-123 GEN
Solar/Wind Harmer
4.317
971277AH1-098 GEN
Solar/Wind Harmer
7.43
942671AE2-283 GEN
Solar/Wind Harmer
8.669
270013AE1-250 PV
Solar/Wind Harmer
3.251
970913AG2-568 GEN
Solar/Wind Harmer
9.375
971225AH1-072 GEN
Solar/Wind Harmer
2.738
971227AH1-073 GEN
Solar/Wind Harmer
2.738
24723005RIVRG1
Adder
23.046
24723105RIVRG2
Adder
23.046
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.774
971485AH1-239 GEN
Solar/Wind Harmer
8.528
339231AF1-038_GEN
Solar/Wind Harmer
1.925
964781AG1-341 GEN
Solar/Wind Harmer
11.012
339236AF1-050_GEN
Solar/Wind Harmer
1.88
942891AE2-308 GEN
Solar/Wind Harmer
10.222
964571AG1-320 GEN
Solar/Wind Harmer
8.222
971125AH1-004 GEN
Solar/Wind Harmer
4.008
970107AG2-081 GEN
Solar/Wind Harmer
3.006
972043AH1-570 GEN
Solar/Wind Harmer
2.487
972045AH1-571 GEN
Solar/Wind Harmer
1.989
927014AC1-188 GEN
Solar/Wind Harmer
1.537
962581AG1-107 GEN
Solar/Wind Harmer
4.757
961491AF2-440 GEN
Solar/Wind Harmer
1.977
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.603
971073AG2-665 GEN
Solar/Wind Harmer
7.39
970879AG2-548 GEN
Solar/Wind Harmer
1.074
25194408D.CRK1
Adder
6.977
25194508D.CRK3
Adder
1.304
945391AF1-204 GEN
Solar/Wind Harmer
12.785
276916AD2-100_GEN
Solar/Wind Harmer
19.251
276911AD2-131_GEN
Solar/Wind Harmer
3.891
276615X2-022 GEN
Solar/Wind Harmer
1.781
276838X2-022 GEN2
Solar/Wind Harmer
0.212
274880W4-005 GEN4
Solar/Wind Harmer
2.739
276174W4-005 GEN2
Solar/Wind Harmer
2.739
970241AG2-163 GEN
Solar/Wind Harmer
22.546
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
960251AF2-316 GEN
Solar/Wind Harmer
13.508
960201AF2-311 GEN
Solar/Wind Harmer
9.005
960611AF2-352 GEN
Solar/Wind Harmer
2.083
942111AE2-223 GEN
Solar/Wind Harmer
7.317
274764LEE CO EC;5U
Adder
8.284
274765LEE CO EC;6U
Adder
8.284
274762LEE CO EC;3U
Adder
8.264
274763LEE CO EC;4U
Adder
8.186
972235AH1-702 GEN1
Adder
2.231
972236AH1-702 GEN2
Adder
1.94
274683WAUKEGAN ;8U
Adder
18.516
274683WAUKEGAN ;8U
Adder
15.608
274696ROCKY RD ;4P
Adder
10.01
274695ROCKY RD ;2P
Adder
9.779
274693ROCKY RD ;1P
Adder
9.683
274697ROCKY RD ;3P
Adder
2.656
253370AE2-315 SEC1
Adder
1.749
274674JOLIET 9 ;6U
Adder
13.445
3132123MT JACKSON
Solar/Wind Helper
1.393
966001AG1-469 GEN
Solar/Wind Helper
0.321
237061AD1-155 GEN
Solar/Wind Helper
1.655
316097T157 G90
Solar/Wind Helper
1.135
238147AE2-230_GEN1
Solar/Wind Helper
0.426
238148AE2-230_GEN2
Solar/Wind Helper
0.426
238149AF1-291A_GEN
Solar/Wind Helper
0.122
316006AB2-029 C
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.356
316045AC1-158 PL2
Solar/Wind Helper
4.058
316450AC1-158 RIC
Solar/Wind Helper
0.338
966871AG1-558 GEN
Solar/Wind Helper
0.307
316312AB1-027
Solar/Wind Helper
0.426
24387305FR-4G C
Solar/Wind Harmer
3.45
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.053
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.452
NYPJM->LTFIMP_NY
CLTF
3.28
LGEELTFEXP_LGEE->PJM
CLTF
6.795
MECLTFEXP_MEC->PJM
CLTF
15.488
SIGELTFEXP_SIGE->PJM
CLTF
0.51
CPLELTFEXP_CPLE->PJM
CLTF
6.224
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.642
LAGNLTFEXP_LAGN->PJM
CLTF
20.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.582
TVALTFEXP_TVA->PJM
CLTF
10.64
WECLTFEXP_WEC->PJM
CLTF
3.389
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4165.98
MW Contribution:
8.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.164
270173AC1-122 GEN
Solar/Wind Harmer
3.444
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
958131AF2-107 GEN
Solar/Wind Harmer
7.104
24735205WLF2G2
Adder
8.025
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.86
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723205RIVRG3
Adder
22.967
24686505CER G6
Adder
9.881
972203AH1-686 GEN
Adder
2.706
270331AC1-082 GEN3
Solar/Wind Harmer
0.513
964901AG1-354 GEN
Solar/Wind Harmer
15.496
339211AE2-254 GEN
Solar/Wind Harmer
1.561
339241AF1-083 GEN
Solar/Wind Harmer
1.716
960001AF2-291 GEN
Solar/Wind Harmer
3.117
3429241JKCT 3G
Adder
12.037
970653AG2-424 GEN
Solar/Wind Harmer
4.885
3429421JKCT 10G
Adder
8.408
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339221AD2-048_GEN
Solar/Wind Harmer
1.511
945681AF1-233 GEN
Solar/Wind Harmer
18.334
970091AG2-072 GEN
Adder
74.077
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.673
25196008MFTGT1
Adder
1.294
252516AE2-318_GEN
Solar/Wind Harmer
9.216
252510AF1-249 C
Solar/Wind Harmer
0.384
971073AG2-665 GEN
Solar/Wind Harmer
1.068
25194608D.CRK4
Adder
1.51
965911AG1-460 GEN
Solar/Wind Harmer
1.272
24728605AND G2
Adder
3.485
253316AC1-085 GEN3
Solar/Wind Harmer
7.603
946171AF1-282 GEN
Solar/Wind Harmer
9.081
276621W2-048 GEN
Solar/Wind Harmer
5.648
276686W4-005 GEN3
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.407
270222AC2-111 GEN
Solar/Wind Harmer
3.996
944031AF1-071 GEN
Solar/Wind Harmer
0.899
253398AE2-221_GEN2
Solar/Wind Harmer
4.059
276655WTG1_EQ
Solar/Wind Harmer
7.757
276656WTG2_EQ
Solar/Wind Harmer
1.027
939741AE1-205 GEN
Solar/Wind Harmer
17.775
274848CAMPGROVE;RU
Solar/Wind Harmer
5.733
274761LEE CO EC;2U
Adder
8.229
274766LEE CO EC;7U
Adder
8.132
274822ROCKFORD ;11
Adder
17.29
274828WAUKEGAN ;BP
Adder
9.664
274682WAUKEGAN ;7U
Adder
15.718
274745AC1-111 GEN9
Adder
4.874
274732ELWOOD EC;7P
Adder
14.292
274674JOLIET 9 ;6U
Adder
13.386
274676JOLIET 29;8U
Adder
26.663
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.232
3132273ORANGE
Solar/Wind Helper
0.056
970823AG2-518 GEN
50/50
8.383
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.211
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.98
970563AG2-360 GEN
50/50
45.836
970417AG2-272 GEN
50/50
3.733
962751AG1-124 GEN
Solar/Wind Harmer
18.819
958121AF2-106 GEN
Solar/Wind Harmer
9.406
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.808
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.922
270018AE2-047 C O1
Solar/Wind Harmer
1.821
960911AF2-382 GEN
Solar/Wind Harmer
10.95
270016AE1-250 BESS
Solar/Wind Harmer
3.249
971461AH1-227 GEN
Solar/Wind Harmer
7.006
970223AG2-152 GEN
Solar/Wind Harmer
17.663
972103AH1-617 GEN
Solar/Wind Harmer
25.844
24686405CER G5
Adder
9.803
270330AC1-082 GEN2
Solar/Wind Harmer
0.512
270329AC1-082 GEN1
Solar/Wind Harmer
0.512
972273AH1-721 GEN
Adder
89.361
24721905FLATG4
Adder
21.701
339255AE2-071 GEN
Solar/Wind Harmer
1.218
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.205
970093AG2-073 GEN
Solar/Wind Harmer
5.447
970653AG2-424 GEN
Solar/Wind Harmer
0.706
3429391JKCT 9G
Adder
8.408
971191AH1-055 GEN
Solar/Wind Harmer
18.847
970455AG2-298 GEN
Solar/Wind Harmer
3.522
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.928
270186AC1-089 GEN
Solar/Wind Harmer
5.824
270367AC2-061_GEN
Solar/Wind Harmer
3.006
252507AC2-088 GEN
Solar/Wind Harmer
1.668
25196008MFTGT1
Adder
1.253
971543AH1-269 GEN
50/50
12.246
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.362
971329AH1-144 GEN
Solar/Wind Harmer
11.729
966391AG1-508 GEN
Solar/Wind Harmer
6.375
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270069AE2-166 C O1
Solar/Wind Harmer
14.878
971313AH1-133 GEN
Solar/Wind Harmer
9.329
24734705WLF1G3
Adder
8.195
24734805WLF1G4
Adder
8.195
24734905WLF1G5
Adder
8.195
24735105WLF2G1
Adder
8.025
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.288
957241AF2-018 GEN
Solar/Wind Harmer
5.76
270053AF1-130 C
Solar/Wind Harmer
23.016
970281AG2-184 GEN
Solar/Wind Harmer
27.137
971981AH1-535 GEN
Solar/Wind Harmer
12.564
962211AG1-066 GEN
Solar/Wind Harmer
3.002
971061AG2-657 GEN
Solar/Wind Harmer
11.001
3429211JKCT 2G
Adder
11.881
339216AC1-074 GEN
Solar/Wind Harmer
1.645
972163AH1-664 GEN
Solar/Wind Harmer
9.75
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.311
270444AC2-157 GEN1
Solar/Wind Harmer
5.241
270445AC2-157 GEN2
Solar/Wind Harmer
5.241
25196108MFTGT2
Adder
1.427
25196108MFTGT2
Adder
1.325
944221AF1-090 GEN
Solar/Wind Harmer
10.032
25196408WSDLE3
Adder
8.087
25196308WSDLE2
Adder
8.016
25196208WSDLE1
Adder
7.996
25196708WSDLE6
Adder
7.976
25196508WSDLE4
Adder
7.775
253433AC1-085 GEN1
Solar/Wind Harmer
4.826
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
276668AB2-070 GEN1
Solar/Wind Harmer
1.998
276848AB2-070 GEN3
Solar/Wind Harmer
1.998
276849AB2-070 GEN2
Solar/Wind Harmer
1.998
270356AE2-297 GEN
Solar/Wind Harmer
4.149
253406AD2-031_GEN
Solar/Wind Harmer
1.147
963841AG1-237 GEN
Solar/Wind Harmer
9.765
270291AC1-194 GEN
Solar/Wind Harmer
4.541
946321AF1-296 GEN
Solar/Wind Harmer
9.308
274853TWINGROVE;U1
Solar/Wind Harmer
6.427
274854TWINGROVE;U2
Solar/Wind Harmer
6.292
270340AC2-060 GEN
Solar/Wind Harmer
2.689
276726Z2-087_GEN
Solar/Wind Harmer
7.027
959341AF2-225 GEN
Solar/Wind Harmer
13.331
972267AH1-718 GEN
Adder
3.691
274823ROCKFORD ;21
Adder
17.165
274744AC1-111 GEN8
Adder
4.874
274746AC1-111 G10
Adder
4.874
274728ELWOOD EC;5P
Adder
14.292
274731ELWOOD EC;2P
Adder
14.292
274733ELWOOD EC;3P
Adder
14.292
274735ELWOOD EC;4P
Adder
14.292
25306009OHH W.
Adder
2.505
274675JOLIET 29;7U
Adder
26.663
274675JOLIET 29;7U
Adder
7.65
315616AA1-038_C
Solar/Wind Helper
3.298
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.844
316164AC1-076 GEN
Solar/Wind Helper
1.178
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.09
24386405FR-21G C
Solar/Wind Harmer
2.093
24387005FR-3G C
Solar/Wind Harmer
1.925
3147666LOUISA
Solar/Wind Helper
0.627
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.304
316095T157 G97
Solar/Wind Helper
1.13
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.39
24385905FR-11G C
Solar/Wind Harmer
4.044
24386605FR-22G C
Solar/Wind Harmer
2.093
252519AF1-045_GEN
Solar/Wind Harmer
3.354
970879AG2-548 GEN
Solar/Wind Harmer
7.349
25194608D.CRK4
Adder
1.51
252524AE2-267 GEN
Solar/Wind Harmer
1.443
25196608WSDLE5
Adder
7.856
970193AG2-126 GEN
Solar/Wind Harmer
13.702
942481AE2-261 GEN
Solar/Wind Harmer
27.253
957381AF2-032 GEN
Solar/Wind Harmer
1.822
24728705AND G3
Adder
7.288
24728505AND G1
Adder
3.485
253317AC1-085 GEN4
Solar/Wind Harmer
7.603
946181AF1-283 GEN
Solar/Wind Harmer
11.806
276785W4-005 GEN1
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.336
253394AE2-221_GEN
Solar/Wind Harmer
4.059
965931AG1-462 GEN
Solar/Wind Harmer
22.779
971087AG2-675 GEN
Solar/Wind Harmer
3.324
965091AG1-374 GEN
Solar/Wind Harmer
26.762
959611AF2-252 GEN
Solar/Wind Harmer
2.075
274760LEE CO EC;1U
Adder
8.229
274767LEE CO EC;8U
Adder
8.132
274682WAUKEGAN ;7U
Adder
15.718
274729ELWOOD EC;1P
Adder
14.292
274730ELWOOD EC;6P
Adder
14.292
274734ELWOOD EC;8P
Adder
14.292
274736ELWOOD EC;9P
Adder
14.292
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.847
3147666LOUISA
Solar/Wind Helper
1.09
238152AF2-075_GEN
Solar/Wind Helper
0.606
316447AC1-158 HLD
Solar/Wind Helper
2.781
316044AC1-158 PL1
Solar/Wind Helper
1.264
3142416OLDCHRC
Solar/Wind Helper
0.579
3142416OLDCHRC
Solar/Wind Helper
0.222
24386205FR-12G C
Solar/Wind Harmer
2.085
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.164
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
942671AE2-283 GEN
Solar/Wind Harmer
8.664
270013AE1-250 PV
Solar/Wind Harmer
3.249
970913AG2-568 GEN
Solar/Wind Harmer
9.345
971225AH1-072 GEN
Solar/Wind Harmer
2.731
971227AH1-073 GEN
Solar/Wind Harmer
2.731
24723005RIVRG1
Adder
22.967
24723105RIVRG2
Adder
22.967
942751AE2-291 GEN
Solar/Wind Harmer
10.376
966021AG1-471 GEN
Solar/Wind Harmer
5.755
971485AH1-239 GEN
Solar/Wind Harmer
8.501
339231AF1-038_GEN
Solar/Wind Harmer
1.919
964781AG1-341 GEN
Solar/Wind Harmer
10.975
339236AF1-050_GEN
Solar/Wind Harmer
1.873
942891AE2-308 GEN
Solar/Wind Harmer
10.182
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
972043AH1-570 GEN
Solar/Wind Harmer
2.477
972045AH1-571 GEN
Solar/Wind Harmer
1.981
927014AC1-188 GEN
Solar/Wind Harmer
1.529
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.577
971073AG2-665 GEN
Solar/Wind Harmer
7.349
970879AG2-548 GEN
Solar/Wind Harmer
1.068
25194408D.CRK1
Adder
6.944
25194508D.CRK3
Adder
1.298
945391AF1-204 GEN
Solar/Wind Harmer
12.73
276916AD2-100_GEN
Solar/Wind Harmer
19.171
276911AD2-131_GEN
Solar/Wind Harmer
3.875
276615X2-022 GEN
Solar/Wind Harmer
1.774
276838X2-022 GEN2
Solar/Wind Harmer
0.211
274880W4-005 GEN4
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
970241AG2-163 GEN
Solar/Wind Harmer
22.448
24728805RICHG1
Adder
3.39
24728905RICHG2
Adder
3.39
960251AF2-316 GEN
Solar/Wind Harmer
13.412
960201AF2-311 GEN
Solar/Wind Harmer
8.941
960611AF2-352 GEN
Solar/Wind Harmer
2.075
942111AE2-223 GEN
Solar/Wind Harmer
7.286
274764LEE CO EC;5U
Adder
8.248
274765LEE CO EC;6U
Adder
8.248
274762LEE CO EC;3U
Adder
8.229
274763LEE CO EC;4U
Adder
8.151
972235AH1-702 GEN1
Adder
2.222
972236AH1-702 GEN2
Adder
1.932
274683WAUKEGAN ;8U
Adder
18.436
274683WAUKEGAN ;8U
Adder
15.54
274696ROCKY RD ;4P
Adder
9.966
274695ROCKY RD ;2P
Adder
9.736
274693ROCKY RD ;1P
Adder
9.64
274697ROCKY RD ;3P
Adder
2.645
274674JOLIET 9 ;6U
Adder
13.386
3132123MT JACKSON
Solar/Wind Helper
1.391
966001AG1-469 GEN
Solar/Wind Helper
0.321
237061AD1-155 GEN
Solar/Wind Helper
1.65
316097T157 G90
Solar/Wind Helper
1.13
238147AE2-230_GEN1
Solar/Wind Helper
0.424
238148AE2-230_GEN2
Solar/Wind Helper
0.424
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.356
966871AG1-558 GEN
Solar/Wind Helper
0.307
316045AC1-158 PL2
Solar/Wind Helper
4.045
316450AC1-158 RIC
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.425
24387305FR-4G C
Solar/Wind Harmer
2.471
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.331
NYPJM->LTFIMP_NY
CLTF
3.263
LGEELTFEXP_LGEE->PJM
CLTF
6.768
WECLTFEXP_WEC->PJM
CLTF
3.374
MECLTFEXP_MEC->PJM
CLTF
15.426
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CPLELTFEXP_CPLE->PJM
CLTF
6.216
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.186
LAGNLTFEXP_LAGN->PJM
CLTF
20.287
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.539
TVALTFEXP_TVA->PJM
CLTF
10.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.26 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4160.96
MW Contribution:
8.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
11.722
966391AG1-508 GEN
Solar/Wind Harmer
6.371
270197AD1-017 GEN1
Solar/Wind Harmer
2.54
270069AE2-166 C O1
Solar/Wind Harmer
14.87
971313AH1-133 GEN
Solar/Wind Harmer
9.321
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
5.551
270400AC1-102 GEN
Solar/Wind Harmer
5.551
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
5.752
270053AF1-130 C
Solar/Wind Harmer
22.985
970281AG2-184 GEN
Solar/Wind Harmer
27.103
971981AH1-535 GEN
Solar/Wind Harmer
12.552
962211AG1-066 GEN
Solar/Wind Harmer
2.998
971061AG2-657 GEN
Solar/Wind Harmer
10.98
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
1.642
972163AH1-664 GEN
Solar/Wind Harmer
9.732
972165AH1-665 GEN
Solar/Wind Harmer
7.785
971985AH1-537 GEN
Solar/Wind Harmer
17.275
270444AC2-157 GEN1
Solar/Wind Harmer
5.231
270445AC2-157 GEN2
Solar/Wind Harmer
5.231
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
10.014
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
253433AC1-085 GEN1
Solar/Wind Harmer
4.815
253432AC1-085 GEN2
Solar/Wind Harmer
0.242
276763AC1-053 GEN1
Solar/Wind Harmer
3.564
276764AC1-053 GEN2
Solar/Wind Harmer
3.564
276668AB2-070 GEN1
Solar/Wind Harmer
1.994
276848AB2-070 GEN3
Solar/Wind Harmer
1.994
276849AB2-070 GEN2
Solar/Wind Harmer
1.994
270356AE2-297 GEN
Solar/Wind Harmer
4.141
253406AD2-031_GEN
Solar/Wind Harmer
1.145
963841AG1-237 GEN
Solar/Wind Harmer
9.746
946321AF1-296 GEN
Solar/Wind Harmer
9.291
274853TWINGROVE;U1
Solar/Wind Harmer
6.415
274854TWINGROVE;U2
Solar/Wind Harmer
6.28
270291AC1-194 GEN
Solar/Wind Harmer
4.529
270340AC2-060 GEN
Solar/Wind Harmer
2.683
276726Z2-087_GEN
Solar/Wind Harmer
7.014
959341AF2-225 GEN
Solar/Wind Harmer
13.306
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
270173AC1-122 GEN
Solar/Wind Harmer
3.443
316217AC1-145 GEN
Solar/Wind Harmer
4.241
316197AC1-042 GEN
Solar/Wind Harmer
3.215
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.466
270336AE1-100 GEN
Solar/Wind Harmer
2.749
943811AF1-049 GEN
Solar/Wind Harmer
5.692
958131AF2-107 GEN
Solar/Wind Harmer
7.102
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
1.358
971403AH1-188 GEN
Solar/Wind Harmer
18.836
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
964901AG1-354 GEN
Solar/Wind Harmer
15.473
339211AE2-254 GEN
Solar/Wind Harmer
1.559
339241AF1-083 GEN
Solar/Wind Harmer
1.713
960001AF2-291 GEN
Solar/Wind Harmer
3.11
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
4.877
3429421JKCT 10G
Adder
8.393
943111AE2-339 GEN
Solar/Wind Harmer
0.882
339221AD2-048_GEN
Solar/Wind Harmer
1.508
945681AF1-233 GEN
Solar/Wind Harmer
18.298
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
9.197
252510AF1-249 C
Solar/Wind Harmer
0.383
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
7.586
946171AF1-282 GEN
Solar/Wind Harmer
9.062
276621W2-048 GEN
Solar/Wind Harmer
5.637
276686W4-005 GEN3
Solar/Wind Harmer
2.723
963741AG1-226 GEN
Solar/Wind Harmer
40.329
270222AC2-111 GEN
Solar/Wind Harmer
3.988
944031AF1-071 GEN
Solar/Wind Harmer
0.897
253398AE2-221_GEN2
Solar/Wind Harmer
4.05
276655WTG1_EQ
Solar/Wind Harmer
7.743
276656WTG2_EQ
Solar/Wind Harmer
1.025
939741AE1-205 GEN
Solar/Wind Harmer
17.741
274848CAMPGROVE;RU
Solar/Wind Harmer
5.723
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
274822ROCKFORD ;11
Adder
17.258
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274745AC1-111 GEN9
Adder
4.865
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
24385905FR-11G C
Solar/Wind Harmer
4.036
24386605FR-22G C
Solar/Wind Harmer
2.088
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
18.814
958121AF2-106 GEN
Solar/Wind Harmer
9.401
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.805
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.925
270030AE2-140 GEN
Solar/Wind Harmer
30.906
270018AE2-047 C O1
Solar/Wind Harmer
1.82
960911AF2-382 GEN
Solar/Wind Harmer
10.939
270016AE1-250 BESS
Solar/Wind Harmer
3.247
971461AH1-227 GEN
Solar/Wind Harmer
6.998
970223AG2-152 GEN
Solar/Wind Harmer
17.657
972103AH1-617 GEN
Solar/Wind Harmer
25.812
24686405CER G5
Adder
9.787
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
339255AE2-071 GEN
Solar/Wind Harmer
1.216
339250AF1-203 GEN
Solar/Wind Harmer
0.626
339206AE1-143 GEN
Solar/Wind Harmer
2.202
970093AG2-073 GEN
Solar/Wind Harmer
5.438
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.807
970455AG2-298 GEN
Solar/Wind Harmer
3.516
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
972167AH1-666 GEN
Solar/Wind Harmer
7.758
957541AF2-048 GEN
Solar/Wind Harmer
1.526
958171AF2-111 GEN
Solar/Wind Harmer
23.881
270186AC1-089 GEN
Solar/Wind Harmer
5.812
270367AC2-061_GEN
Solar/Wind Harmer
3
252507AC2-088 GEN
Solar/Wind Harmer
1.664
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
7.33
252524AE2-267 GEN
Solar/Wind Harmer
1.44
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
13.676
942481AE2-261 GEN
Solar/Wind Harmer
27.203
957381AF2-032 GEN
Solar/Wind Harmer
1.819
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
7.586
946181AF1-283 GEN
Solar/Wind Harmer
11.78
276785W4-005 GEN1
Solar/Wind Harmer
2.723
971993AH1-541 GEN
Solar/Wind Harmer
8.32
253394AE2-221_GEN
Solar/Wind Harmer
4.05
965931AG1-462 GEN
Solar/Wind Harmer
22.737
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
26.711
959611AF2-252 GEN
Solar/Wind Harmer
2.071
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
274682WAUKEGAN ;7U
Adder
15.687
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
3147983MERCK5
Solar/Wind Helper
0.198
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
24386405FR-21G C
Solar/Wind Harmer
2.088
24387005FR-3G C
Solar/Wind Harmer
1.921
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
24386205FR-12G C
Solar/Wind Harmer
2.081
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
20.71
270214AC2-123 GEN
Solar/Wind Harmer
4.308
971277AH1-098 GEN
Solar/Wind Harmer
7.416
942671AE2-283 GEN
Solar/Wind Harmer
8.662
270013AE1-250 PV
Solar/Wind Harmer
3.247
970913AG2-568 GEN
Solar/Wind Harmer
9.332
971225AH1-072 GEN
Solar/Wind Harmer
2.728
971227AH1-073 GEN
Solar/Wind Harmer
2.728
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
10.374
966021AG1-471 GEN
Solar/Wind Harmer
5.747
971485AH1-239 GEN
Solar/Wind Harmer
8.488
339231AF1-038_GEN
Solar/Wind Harmer
1.916
964781AG1-341 GEN
Solar/Wind Harmer
10.959
339236AF1-050_GEN
Solar/Wind Harmer
1.871
942891AE2-308 GEN
Solar/Wind Harmer
10.165
964571AG1-320 GEN
Solar/Wind Harmer
8.178
971125AH1-004 GEN
Solar/Wind Harmer
3.985
970107AG2-081 GEN
Solar/Wind Harmer
2.988
972043AH1-570 GEN
Solar/Wind Harmer
2.472
972045AH1-571 GEN
Solar/Wind Harmer
1.978
927014AC1-188 GEN
Solar/Wind Harmer
1.526
962581AG1-107 GEN
Solar/Wind Harmer
4.724
961491AF2-440 GEN
Solar/Wind Harmer
1.963
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.565
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.33
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
12.706
276916AD2-100_GEN
Solar/Wind Harmer
19.136
276911AD2-131_GEN
Solar/Wind Harmer
3.867
276615X2-022 GEN
Solar/Wind Harmer
1.77
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.723
276174W4-005 GEN2
Solar/Wind Harmer
2.723
970241AG2-163 GEN
Solar/Wind Harmer
22.405
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
13.37
960201AF2-311 GEN
Solar/Wind Harmer
8.913
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
7.272
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
274674JOLIET 9 ;6U
Adder
13.36
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
24387305FR-4G C
Solar/Wind Harmer
2.467
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4149.41
MW Contribution:
8.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.16
270173AC1-122 GEN
Solar/Wind Harmer
3.444
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
958131AF2-107 GEN
Solar/Wind Harmer
7.106
24735205WLF2G2
Adder
8.021
971687AH1-348 GEN
Solar/Wind Harmer
1.358
971403AH1-188 GEN
Solar/Wind Harmer
18.845
944971AF1-162 GEN
Solar/Wind Harmer
9.064
24723205RIVRG3
Adder
22.944
24686505CER G6
Adder
9.87
972203AH1-686 GEN
Adder
2.703
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
971543AH1-269 GEN
50/50
12.244
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.357
971329AH1-144 GEN
Solar/Wind Harmer
11.725
966391AG1-508 GEN
Solar/Wind Harmer
6.373
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270069AE2-166 C O1
Solar/Wind Harmer
14.876
971313AH1-133 GEN
Solar/Wind Harmer
9.325
24734705WLF1G3
Adder
8.191
24734805WLF1G4
Adder
8.191
24734905WLF1G5
Adder
8.191
24735105WLF2G1
Adder
8.021
270399AC1-101 GEN
Solar/Wind Harmer
5.554
270400AC1-102 GEN
Solar/Wind Harmer
5.554
941621AE2-160 GEN
Adder
4.283
957241AF2-018 GEN
Solar/Wind Harmer
5.755
270053AF1-130 C
Solar/Wind Harmer
22.996
970281AG2-184 GEN
Solar/Wind Harmer
27.117
971981AH1-535 GEN
Solar/Wind Harmer
12.558
962211AG1-066 GEN
Solar/Wind Harmer
3
971061AG2-657 GEN
Solar/Wind Harmer
10.986
3429211JKCT 2G
Adder
11.868
339216AC1-074 GEN
Solar/Wind Harmer
1.643
972163AH1-664 GEN
Solar/Wind Harmer
9.738
972165AH1-665 GEN
Solar/Wind Harmer
7.79
971985AH1-537 GEN
Solar/Wind Harmer
17.286
270444AC2-157 GEN1
Solar/Wind Harmer
5.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.235
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.323
944221AF1-090 GEN
Solar/Wind Harmer
10.021
25196408WSDLE3
Adder
8.076
25196308WSDLE2
Adder
8.005
25196208WSDLE1
Adder
7.985
25196708WSDLE6
Adder
7.965
25196508WSDLE4
Adder
7.765
253433AC1-085 GEN1
Solar/Wind Harmer
4.819
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.567
276764AC1-053 GEN2
Solar/Wind Harmer
3.567
276668AB2-070 GEN1
Solar/Wind Harmer
1.995
276848AB2-070 GEN3
Solar/Wind Harmer
1.995
276849AB2-070 GEN2
Solar/Wind Harmer
1.995
270356AE2-297 GEN
Solar/Wind Harmer
4.144
253406AD2-031_GEN
Solar/Wind Harmer
1.146
963841AG1-237 GEN
Solar/Wind Harmer
9.753
946321AF1-296 GEN
Solar/Wind Harmer
9.297
274853TWINGROVE;U1
Solar/Wind Harmer
6.419
274854TWINGROVE;U2
Solar/Wind Harmer
6.285
270291AC1-194 GEN
Solar/Wind Harmer
4.532
270340AC2-060 GEN
Solar/Wind Harmer
2.685
276726Z2-087_GEN
Solar/Wind Harmer
7.019
959341AF2-225 GEN
Solar/Wind Harmer
13.316
972267AH1-718 GEN
Adder
3.687
274823ROCKFORD ;21
Adder
17.145
274744AC1-111 GEN8
Adder
4.868
274746AC1-111 G10
Adder
4.868
274728ELWOOD EC;5P
Adder
14.275
274731ELWOOD EC;2P
Adder
14.275
274733ELWOOD EC;3P
Adder
14.275
274735ELWOOD EC;4P
Adder
14.275
25306009OHH W.
Adder
2.502
274675JOLIET 29;7U
Adder
26.631
274675JOLIET 29;7U
Adder
7.641
315616AA1-038_C
Solar/Wind Helper
3.296
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.842
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.266
316468AD1-105 GEN
Solar/Wind Helper
1.088
24386405FR-21G C
Solar/Wind Harmer
2.09
24387005FR-3G C
Solar/Wind Harmer
1.922
970823AG2-518 GEN
50/50
8.382
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.211
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.973
970563AG2-360 GEN
50/50
45.815
970417AG2-272 GEN
50/50
3.733
962751AG1-124 GEN
Solar/Wind Harmer
18.82
958121AF2-106 GEN
Solar/Wind Harmer
9.404
943031AE2-326 GEN
Solar/Wind Harmer
6.783
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.809
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.931
270030AE2-140 GEN
Solar/Wind Harmer
30.919
270018AE2-047 C O1
Solar/Wind Harmer
1.821
960911AF2-382 GEN
Solar/Wind Harmer
10.944
270016AE1-250 BESS
Solar/Wind Harmer
3.249
971461AH1-227 GEN
Solar/Wind Harmer
7.001
970223AG2-152 GEN
Solar/Wind Harmer
17.666
972103AH1-617 GEN
Solar/Wind Harmer
25.825
24686405CER G5
Adder
9.792
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
972273AH1-721 GEN
Adder
89.284
24721905FLATG4
Adder
21.675
339255AE2-071 GEN
Solar/Wind Harmer
1.217
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.203
970093AG2-073 GEN
Solar/Wind Harmer
5.442
970653AG2-424 GEN
Solar/Wind Harmer
0.706
3429391JKCT 9G
Adder
8.399
971191AH1-055 GEN
Solar/Wind Harmer
18.819
970455AG2-298 GEN
Solar/Wind Harmer
3.519
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
972167AH1-666 GEN
Solar/Wind Harmer
7.764
957541AF2-048 GEN
Solar/Wind Harmer
1.527
958171AF2-111 GEN
Solar/Wind Harmer
23.897
270186AC1-089 GEN
Solar/Wind Harmer
5.816
270367AC2-061_GEN
Solar/Wind Harmer
3.002
252507AC2-088 GEN
Solar/Wind Harmer
1.666
25196008MFTGT1
Adder
1.252
252519AF1-045_GEN
Solar/Wind Harmer
3.349
25194608D.CRK4
Adder
1.508
970879AG2-548 GEN
Solar/Wind Harmer
7.336
252524AE2-267 GEN
Solar/Wind Harmer
1.441
25196608WSDLE5
Adder
7.845
970193AG2-126 GEN
Solar/Wind Harmer
13.686
942481AE2-261 GEN
Solar/Wind Harmer
27.222
957381AF2-032 GEN
Solar/Wind Harmer
1.82
24728705AND G3
Adder
7.279
24728505AND G1
Adder
3.48
253317AC1-085 GEN4
Solar/Wind Harmer
7.592
946181AF1-283 GEN
Solar/Wind Harmer
11.789
276785W4-005 GEN1
Solar/Wind Harmer
2.725
971993AH1-541 GEN
Solar/Wind Harmer
8.326
253394AE2-221_GEN
Solar/Wind Harmer
4.053
965931AG1-462 GEN
Solar/Wind Harmer
22.754
971087AG2-675 GEN
Solar/Wind Harmer
3.32
965091AG1-374 GEN
Solar/Wind Harmer
26.73
959611AF2-252 GEN
Solar/Wind Harmer
2.072
274760LEE CO EC;1U
Adder
8.219
274767LEE CO EC;8U
Adder
8.123
274682WAUKEGAN ;7U
Adder
15.699
274729ELWOOD EC;1P
Adder
14.275
274730ELWOOD EC;6P
Adder
14.275
274734ELWOOD EC;8P
Adder
14.275
274736ELWOOD EC;9P
Adder
14.275
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.844
3147666LOUISA
Solar/Wind Helper
1.088
238152AF2-075_GEN
Solar/Wind Helper
0.604
316447AC1-158 HLD
Solar/Wind Helper
2.775
316044AC1-158 PL1
Solar/Wind Helper
1.261
24386205FR-12G C
Solar/Wind Harmer
2.082
964901AG1-354 GEN
Solar/Wind Harmer
15.482
339211AE2-254 GEN
Solar/Wind Harmer
1.56
339241AF1-083 GEN
Solar/Wind Harmer
1.714
960001AF2-291 GEN
Solar/Wind Harmer
3.112
3429241JKCT 3G
Adder
12.024
970653AG2-424 GEN
Solar/Wind Harmer
4.88
3429421JKCT 10G
Adder
8.399
943111AE2-339 GEN
Solar/Wind Harmer
0.882
339221AD2-048_GEN
Solar/Wind Harmer
1.509
945681AF1-233 GEN
Solar/Wind Harmer
18.311
970091AG2-072 GEN
Adder
73.991
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
70.578
25196008MFTGT1
Adder
1.293
252516AE2-318_GEN
Solar/Wind Harmer
9.203
252510AF1-249 C
Solar/Wind Harmer
0.383
25194608D.CRK4
Adder
1.508
971073AG2-665 GEN
Solar/Wind Harmer
1.066
965911AG1-460 GEN
Solar/Wind Harmer
1.27
24728605AND G2
Adder
3.48
253316AC1-085 GEN3
Solar/Wind Harmer
7.592
946171AF1-282 GEN
Solar/Wind Harmer
9.068
276621W2-048 GEN
Solar/Wind Harmer
5.641
276686W4-005 GEN3
Solar/Wind Harmer
2.725
963741AG1-226 GEN
Solar/Wind Harmer
40.358
270222AC2-111 GEN
Solar/Wind Harmer
3.991
944031AF1-071 GEN
Solar/Wind Harmer
0.898
253398AE2-221_GEN2
Solar/Wind Harmer
4.053
276655WTG1_EQ
Solar/Wind Harmer
7.748
276656WTG2_EQ
Solar/Wind Harmer
1.026
939741AE1-205 GEN
Solar/Wind Harmer
17.754
274848CAMPGROVE;RU
Solar/Wind Harmer
5.727
274761LEE CO EC;2U
Adder
8.219
274766LEE CO EC;7U
Adder
8.123
274822ROCKFORD ;11
Adder
17.27
274828WAUKEGAN ;BP
Adder
9.652
274682WAUKEGAN ;7U
Adder
15.699
274745AC1-111 GEN9
Adder
4.868
274732ELWOOD EC;7P
Adder
14.275
274674JOLIET 9 ;6U
Adder
13.37
274676JOLIET 29;8U
Adder
26.631
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
315821AE2-092 GEN
Solar/Wind Helper
3.228
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.293
316095T157 G97
Solar/Wind Helper
1.127
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
24385905FR-11G C
Solar/Wind Harmer
4.039
24386605FR-22G C
Solar/Wind Harmer
2.09
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.16
270583AD2-179 GEN
Solar/Wind Harmer
20.716
270214AC2-123 GEN
Solar/Wind Harmer
4.31
971277AH1-098 GEN
Solar/Wind Harmer
7.418
942671AE2-283 GEN
Solar/Wind Harmer
8.665
270013AE1-250 PV
Solar/Wind Harmer
3.249
970913AG2-568 GEN
Solar/Wind Harmer
9.337
971225AH1-072 GEN
Solar/Wind Harmer
2.729
971227AH1-073 GEN
Solar/Wind Harmer
2.729
24723005RIVRG1
Adder
22.944
24723105RIVRG2
Adder
22.944
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.751
971485AH1-239 GEN
Solar/Wind Harmer
8.494
339231AF1-038_GEN
Solar/Wind Harmer
1.917
964781AG1-341 GEN
Solar/Wind Harmer
10.966
339236AF1-050_GEN
Solar/Wind Harmer
1.872
942891AE2-308 GEN
Solar/Wind Harmer
10.171
964571AG1-320 GEN
Solar/Wind Harmer
8.183
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.474
972045AH1-571 GEN
Solar/Wind Harmer
1.979
927014AC1-188 GEN
Solar/Wind Harmer
1.527
962581AG1-107 GEN
Solar/Wind Harmer
4.728
961491AF2-440 GEN
Solar/Wind Harmer
1.965
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.569
25194408D.CRK1
Adder
6.935
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.336
970879AG2-548 GEN
Solar/Wind Harmer
1.066
945391AF1-204 GEN
Solar/Wind Harmer
12.715
276916AD2-100_GEN
Solar/Wind Harmer
19.15
276911AD2-131_GEN
Solar/Wind Harmer
3.87
276615X2-022 GEN
Solar/Wind Harmer
1.772
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276174W4-005 GEN2
Solar/Wind Harmer
2.725
970241AG2-163 GEN
Solar/Wind Harmer
22.421
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
960251AF2-316 GEN
Solar/Wind Harmer
13.38
960201AF2-311 GEN
Solar/Wind Harmer
8.92
960611AF2-352 GEN
Solar/Wind Harmer
2.072
942111AE2-223 GEN
Solar/Wind Harmer
7.277
274764LEE CO EC;5U
Adder
8.239
274765LEE CO EC;6U
Adder
8.239
274762LEE CO EC;3U
Adder
8.219
274763LEE CO EC;4U
Adder
8.142
972235AH1-702 GEN1
Adder
2.219
972236AH1-702 GEN2
Adder
1.93
274683WAUKEGAN ;8U
Adder
18.414
274683WAUKEGAN ;8U
Adder
15.522
274696ROCKY RD ;4P
Adder
9.954
274695ROCKY RD ;2P
Adder
9.725
274693ROCKY RD ;1P
Adder
9.629
274697ROCKY RD ;3P
Adder
2.642
274674JOLIET 9 ;6U
Adder
13.37
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.646
316097T157 G90
Solar/Wind Helper
1.127
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.036
316450AC1-158 RIC
Solar/Wind Helper
0.336
24387305FR-4G C
Solar/Wind Harmer
2.468
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.302
NYPJM->LTFIMP_NY
CLTF
3.251
LGEELTFEXP_LGEE->PJM
CLTF
6.761
WECLTFEXP_WEC->PJM
CLTF
3.371
MECLTFEXP_MEC->PJM
CLTF
15.41
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CPLELTFEXP_CPLE->PJM
CLTF
6.22
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.073
LAGNLTFEXP_LAGN->PJM
CLTF
20.273
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.54
TVALTFEXP_TVA->PJM
CLTF
10.603
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.56 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5140.38
MW Contribution:
10.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.109
270120AB2-067 GEN2
50/50
7.109
24318905MLG2
50/50
7.027
270349AD2-093_GEN
Solar/Wind Harmer
4.455
270471AD2-092_GEN
Solar/Wind Harmer
4.455
270054AF2-122 C O1
Solar/Wind Harmer
3.972
946101AF1-275 GEN
Solar/Wind Harmer
1.811
253383AE2-342_GEN
Solar/Wind Harmer
1.04
942861AE2-305 GEN
Solar/Wind Harmer
9.069
938701AE1-092 GEN
Solar/Wind Harmer
23.766
270462AD2-086
Solar/Wind Harmer
7.908
270269AC2-059
Solar/Wind Harmer
10.571
253378AE2-206_GEN
Solar/Wind Harmer
3.997
972159AH1-661 GEN
Adder
1.106
253415AE1-040 GEN
Solar/Wind Harmer
1.242
25326509SID D
Adder
1.451
241960AC2-195 GEN
Solar/Wind Harmer
3.055
971073AG2-665 GEN
Solar/Wind Harmer
8.771
970879AG2-548 GEN
Solar/Wind Harmer
1.275
25326109MON D
Adder
1.442
25322209TAIT E
Adder
10.635
25322209TAIT E
Adder
10.396
253370AE2-315 SEC1
Adder
2.18
927014AC1-188 GEN
Solar/Wind Harmer
1.717
253349AC2-067 GEN
Solar/Wind Harmer
2.203
253400AC2-068 GEN
Solar/Wind Harmer
0.886
246937BC-WTG2
Solar/Wind Harmer
4.216
270246TR4_N_V150
Solar/Wind Harmer
0.912
270247TR4_N_V136
Solar/Wind Harmer
0.912
942801AE2-298 GEN
Solar/Wind Harmer
1.621
247607V1-011 GEN
Solar/Wind Harmer
4.231
962581AG1-107 GEN
Solar/Wind Harmer
5.356
961491AF2-440 GEN
Solar/Wind Harmer
2.226
25183208HLCRTG
Solar/Wind Harmer
6.427
944541AF1-119 GEN
Solar/Wind Harmer
4.444
960971AF2-388 GEN
Solar/Wind Harmer
11.601
942221AE2-234 GEN
Solar/Wind Harmer
3.71
25194408D.CRK1
Adder
8
25194508D.CRK3
Adder
1.496
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.561
970885AG2-551 GEN
Solar/Wind Harmer
2.456
247621Y3-024
Adder
0.255
270201AC2-176 GEN
Solar/Wind Harmer
5.42
964611AG1-324 GEN
Solar/Wind Harmer
0.551
970349AG2-230 GEN
Solar/Wind Harmer
15.797
270031AE2-169
Solar/Wind Harmer
8.576
270599AE1-208 GEN
Solar/Wind Harmer
8.576
270383AD1-128 GEN
Solar/Wind Harmer
6.419
926881AC1-175 GEN
Solar/Wind Harmer
5.862
247620Y3-023
Adder
0.483
944231AF1-091 GEN
Solar/Wind Harmer
18.887
24728805RICHG1
Adder
3.96
24728905RICHG2
Adder
3.96
274770LINCOLN ;1U
Adder
8.673
274771LINCOLN ;2U
Adder
8.673
274805UNIV PK N;1U
Adder
5.149
274808UNIV PK N;4U
Adder
5.115
274674JOLIET 9 ;6U
Adder
15.699
274696ROCKY RD ;4P
Adder
11.533
274695ROCKY RD ;2P
Adder
11.267
274693ROCKY RD ;1P
Adder
11.156
274697ROCKY RD ;3P
Adder
3.061
274683WAUKEGAN ;8U
Adder
21.305
274683WAUKEGAN ;8U
Adder
9.68
316097T157 G90
Solar/Wind Helper
1.515
235054AD2-180 GEN
Solar/Wind Helper
2.054
23585401KL_K28_T16
Solar/Wind Helper
1.5
235531U2-073 GEN
Solar/Wind Helper
3.347
238117U2-030
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.501
238148AE2-230_GEN2
Solar/Wind Helper
0.501
238149AF1-291A_GEN
Solar/Wind Helper
0.143
23751201ROTHROCK
Solar/Wind Helper
0.836
235020AA1-095 C
Solar/Wind Helper
0.054
237061AD1-155 GEN
Solar/Wind Helper
1.772
238221AF1-254 C O1
Solar/Wind Helper
0.278
237080AD1-060 GEN
Solar/Wind Helper
0.346
235062AE1-101 C1
Solar/Wind Helper
1.678
316411AF1-147_GEN1
Solar/Wind Helper
0.898
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.371
223402AF1-300 C
Solar/Wind Helper
0.371
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.385
232424Y1-079 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.363
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.575
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.972
232428Y3-058 C
Solar/Wind Helper
0.342
232410W1-006 C
Solar/Wind Helper
0.513
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.235
233954AC2-188 GEN
Solar/Wind Helper
0.235
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.182
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
270166AC1-044 GEN3
50/50
7.109
23559101PLEAS2
50/50
6.362
962761AG1-125 GEN
Solar/Wind Harmer
41.016
970149AG2-104 GEN
Solar/Wind Harmer
25.328
970155AG2-107 GEN
Solar/Wind Harmer
17.885
270286AF1-227 GEN2
Solar/Wind Harmer
2.504
270520AE2-214 GEN
Solar/Wind Harmer
7.243
270391AF1-285 GEN3
Solar/Wind Harmer
1.393
270578AF1-285 GEN2
Solar/Wind Harmer
1.393
253333AC1-068 GEN
Solar/Wind Harmer
1.191
270317AD1-130_GEN
Solar/Wind Harmer
3.64
270485AE1-090_GEN
Solar/Wind Harmer
0.688
270273AD2-016 GEN
Solar/Wind Harmer
3.013
971995AH1-542 GEN
Solar/Wind Harmer
12.463
972269AH1-719 GEN
Adder
2.545
971073AG2-665 GEN
Solar/Wind Harmer
1.275
25326309TAIT D
Adder
1.195
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
241813AF1-122_GEN
Solar/Wind Harmer
5.897
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.9
246936BC-WTG1
Solar/Wind Harmer
4.216
270489AE1-102 GEN1
Solar/Wind Harmer
1.401
965421AG1-410 GEN
Solar/Wind Harmer
32.318
960001AF2-291 GEN
Solar/Wind Harmer
3.25
253316AC1-085 GEN3
Solar/Wind Harmer
8.992
946171AF1-282 GEN
Solar/Wind Harmer
10.741
965011AG1-365 GEN
Solar/Wind Harmer
10.725
270258AD1-119 GEN
Solar/Wind Harmer
2.156
965651AG1-433 GEN
Solar/Wind Harmer
5.801
252516AE2-318_GEN
Solar/Wind Harmer
10.604
958861AF2-177 GEN
Solar/Wind Harmer
11.586
270024AE2-089 GEN
Solar/Wind Harmer
4.961
252510AF1-249 C
Solar/Wind Harmer
0.441
25194608D.CRK4
Adder
1.739
945371AF1-202 GEN
Solar/Wind Harmer
7.376
270297AD1-101 GEN
Solar/Wind Harmer
2.147
270222AC2-111 GEN
Solar/Wind Harmer
4.718
944031AF1-071 GEN
Solar/Wind Harmer
1.062
270510AE1-227 GEN1
Solar/Wind Harmer
2.605
270005AE1-210 C O1
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
6.717
270209AC1-174_GEN
Solar/Wind Harmer
4.274
270437AC2-090 C
Solar/Wind Harmer
5.862
270239V3-007_GEN1
Solar/Wind Harmer
1.807
270331AC1-082 GEN3
Solar/Wind Harmer
0.501
25196808ZIMRHP
Adder
79.685
970825AG2-519 GEN
Solar/Wind Harmer
2.203
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.634
25196008MFTGT1
Adder
1.45
274751CRETE EC ;1U
Adder
8.473
274754CRETE EC ;4U
Adder
8.473
274773LINCOLN ;4U
Adder
8.673
274774LINCOLN ;5U
Adder
8.673
274723RIVER EC ;12
Adder
18.412
274812UNIV PK N;8U
Adder
5.137
274802UNIV PARK;5U
Adder
5.968
24728605AND G2
Adder
3.925
274676JOLIET 29;8U
Adder
31.291
274732ELWOOD EC;7P
Adder
16.762
274674JOLIET 9 ;6U
Adder
15.699
972203AH1-686 GEN
Adder
2.344
274745AC1-111 GEN9
Adder
5.677
970091AG2-072 GEN
Adder
77.647
274682WAUKEGAN ;7U
Adder
18.178
316095T157 G97
Solar/Wind Helper
1.515
23583801GRNGAP
Solar/Wind Helper
5.644
238185AF2-356 C
Solar/Wind Helper
2.686
238109AE1-109 GEN2
Solar/Wind Helper
0.115
238120AE2-309 GEN
Solar/Wind Helper
0.534
238126S14_GEN_1
Solar/Wind Helper
0.836
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.667
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.451
237002AB1-128_GEN
Solar/Wind Helper
0.448
23751101LEADS_P59
Solar/Wind Helper
2.15
23777801MSM_W1-116
Solar/Wind Helper
0.116
3141196NOKESVL
Solar/Wind Helper
1.039
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.283
233987AB2-037 GEN
Solar/Wind Helper
2.369
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.235
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.76
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.513
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.118
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.501
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.329
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.091
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.799
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.443
961331AF2-424 GEN
Solar/Wind Helper
0.442
961421AF2-433 GEN
Solar/Wind Helper
0.441
957921AF2-086 GEN
Solar/Wind Helper
0.436
270594AE1-207 GEN
Solar/Wind Harmer
13.371
270032AE2-172
Solar/Wind Harmer
4.579
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.028
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.051
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
961431AF2-434 GEN
Solar/Wind Helper
0.441
270459AD2-067 GEN
Solar/Wind Harmer
10.212
961821AG1-024 GEN
Solar/Wind Harmer
10.368
972239AH1-704 GEN
Adder
2.66
241955AC1-078 GEN
Solar/Wind Harmer
8.781
241973AD2-163_GEN1
Solar/Wind Harmer
2.319
241974AD2-163_GEN2
Solar/Wind Harmer
2.319
943861AF1-054 GEN
Solar/Wind Harmer
4.476
943851AF1-053 GEN
Solar/Wind Harmer
2.163
945631AF1-228 GEN
Solar/Wind Harmer
5.449
270223U2-072_GEN1
Solar/Wind Harmer
2.274
270224U2-072_GEN2
Solar/Wind Harmer
2.274
270227U2-072_GEN3
Solar/Wind Harmer
2.274
270228U2-072_GEN4
Solar/Wind Harmer
2.274
270231U2-072_GEN5
Solar/Wind Harmer
2.274
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
8.025
253338AC1-165 GEN
Solar/Wind Harmer
1.235
253343AC1-166 GEN
Solar/Wind Harmer
1.235
270302AB2-170 GEN
Solar/Wind Harmer
9.522
940611AE2-048 GEN
Solar/Wind Harmer
24.76
941391AE2-136 GEN
Solar/Wind Harmer
12.83
270263AC1-001 GEN
Solar/Wind Harmer
1.17
241972AD1-140 GEN
Solar/Wind Harmer
5.01
270291AC1-194 GEN
Solar/Wind Harmer
5.61
270340AC2-060 GEN
Solar/Wind Harmer
3.331
970179AG2-119 GEN
Solar/Wind Harmer
8.806
253372AE2-315 SEC3
Adder
2.062
253372AE2-315 SEC3
Adder
2.062
25306009OHH W.
Adder
3.128
253406AD2-031_GEN
Solar/Wind Harmer
1.383
957201AF2-014 GEN
Solar/Wind Harmer
4.888
270435AC2-044 GEN
Solar/Wind Harmer
2.156
253433AC1-085 GEN1
Solar/Wind Harmer
5.708
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.604
270191TR4_S_V150
Solar/Wind Harmer
3.216
965051AG1-369 GEN
Solar/Wind Harmer
5.355
959331AF2-224 GEN
Solar/Wind Harmer
10.725
270377AD1-106 GEN
Solar/Wind Harmer
5.62
270007AE1-245 C
Solar/Wind Harmer
5.779
965041AG1-368 GEN
Solar/Wind Harmer
10.701
24729505KEY G4
Adder
6.914
966831AG1-554 GEN
Solar/Wind Harmer
1.275
971567AH1-282 GEN
Solar/Wind Harmer
5.316
270071AF1-092 GEN
Solar/Wind Harmer
15.971
963791AG1-232 GEN
Solar/Wind Harmer
14.371
971985AH1-537 GEN
Solar/Wind Harmer
18.964
958711AF2-162 GEN
Solar/Wind Harmer
1.074
25196408WSDLE3
Adder
9.339
25196308WSDLE2
Adder
9.258
25196208WSDLE1
Adder
9.235
25196708WSDLE6
Adder
9.211
25196508WSDLE4
Adder
8.979
945581AF1-223 GEN
Solar/Wind Harmer
4.795
971029AG2-637 GEN
Solar/Wind Harmer
15.851
970031AG2-029 GEN
Solar/Wind Harmer
26.415
270404AC1-167 GEN
Solar/Wind Harmer
1.144
270543AE2-219 C
Solar/Wind Harmer
10.561
247536S-71 GEN
Solar/Wind Harmer
4.271
961761AG1-017 GEN
Solar/Wind Harmer
0.451
964611AG1-324 GEN
Solar/Wind Harmer
4.11
25196108MFTGT2
Adder
1.598
25196108MFTGT2
Adder
1.484
274775LINCOLN ;6U
Adder
8.673
274776LINCOLN ;7U
Adder
8.673
274777LINCOLN ;8U
Adder
8.673
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.938
274800UNIV PARK;3U
Adder
5.964
274801UNIV PARK;4U
Adder
5.964
972228AH1-698 GEN2
Adder
3.789
972227AH1-698 GEN1
Adder
2.668
274687WILL CNTY;4U
Adder
28.512
274687WILL CNTY;4U
Adder
28.512
274675JOLIET 29;7U
Adder
31.291
274675JOLIET 29;7U
Adder
30.174
274728ELWOOD EC;5P
Adder
16.762
274731ELWOOD EC;2P
Adder
16.762
274733ELWOOD EC;3P
Adder
16.762
274735ELWOOD EC;4P
Adder
16.762
274744AC1-111 GEN8
Adder
5.677
274746AC1-111 G10
Adder
5.677
23750701CROSSCHOOL
Solar/Wind Helper
1.517
238118U2-030_1
Solar/Wind Helper
0.345
238169AE2-226 GEN1
Solar/Wind Helper
0.708
238170AE2-226 GEN2
Solar/Wind Helper
0.708
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.647
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.372
959381AF2-229 GEN
Solar/Wind Helper
0.36
20390526W1-045 C
Solar/Wind Helper
0.354
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.515
205956AE1-196_GEN
Solar/Wind Helper
0.514
233915AB1-141 GEN
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.235
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.795
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
316164AC1-076 GEN
Solar/Wind Helper
1.108
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.069
964851AG1-348 GEN
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
203955AF1-039 C O1
Solar/Wind Helper
0.332
209027LOR2_Q27
Solar/Wind Helper
1.036
212266LOR1
Solar/Wind Helper
0.302
209054AE2-059 GEN
Solar/Wind Helper
0.08
24318805MLG1
50/50
10.127
23559001PLEAS1
50/50
6.362
270051AF1-062 GEN
50/50
11.798
270475AD2-096_GEN
50/50
7.137
962771AG1-126 GEN
Solar/Wind Harmer
41.016
970153AG2-106 GEN
Solar/Wind Harmer
17.885
961921AG1-034 GEN
Solar/Wind Harmer
15.551
270284AF1-227 GEN1
Solar/Wind Harmer
6.768
270287AF1-227 GEN3
Solar/Wind Harmer
2.504
24721905FLATG4
Adder
24.045
942051AE2-217 GEN
Solar/Wind Harmer
20.995
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.045
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
270518AE2-148 GEN
Solar/Wind Harmer
13.818
253325AC1-069 GEN
Solar/Wind Harmer
1.191
276820AF1-078_GEN
Solar/Wind Harmer
1.776
958581AF2-149 GEN
Solar/Wind Harmer
4.712
971199AH1-059 GEN
Solar/Wind Harmer
2.312
970879AG2-548 GEN
Solar/Wind Harmer
8.771
960071AF2-298 GEN
Solar/Wind Harmer
1.647
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.717
253394AE2-221_GEN
Solar/Wind Harmer
4.9
246938BC-WTG3
Solar/Wind Harmer
4.289
270491AE1-102 GEN2
Solar/Wind Harmer
1.401
971191AH1-055 GEN
Solar/Wind Harmer
20.077
253317AC1-085 GEN4
Solar/Wind Harmer
8.992
946181AF1-283 GEN
Solar/Wind Harmer
13.963
965021AG1-366 GEN
Solar/Wind Harmer
2.494
958091AF2-103 GEN
Solar/Wind Harmer
0.173
24695305TIMB G C
Solar/Wind Harmer
3.573
270588AE1-091_GEN
Solar/Wind Harmer
11.753
944531AF1-118 GEN
Solar/Wind Harmer
37.358
270043AE2-236 GEN
Solar/Wind Harmer
5.865
252519AF1-045_GEN
Solar/Wind Harmer
3.859
270367AC2-061_GEN
Solar/Wind Harmer
3.367
252524AE2-267 GEN
Solar/Wind Harmer
1.667
25196608WSDLE5
Adder
9.072
25194608D.CRK4
Adder
1.739
252507AC2-088 GEN
Solar/Wind Harmer
1.892
270044AE2-322 C
Solar/Wind Harmer
1.388
270063AE2-323 C
Solar/Wind Harmer
2.32
962031AG1-047 GEN
Solar/Wind Harmer
3.189
957741AF2-068 GEN
Solar/Wind Harmer
15.82
971347AH1-153 GEN
Solar/Wind Harmer
5.266
270512AE1-227 GEN2
Solar/Wind Harmer
2.212
270186AC1-089 GEN
Solar/Wind Harmer
6.425
946031AF1-268 GEN
Solar/Wind Harmer
8.725
270004AE1-209 GEN
Solar/Wind Harmer
5.743
24379505HDWTR1G C
Solar/Wind Harmer
8.305
270240V3-007_GEN2
Solar/Wind Harmer
6.498
270330AC1-082 GEN2
Solar/Wind Harmer
0.5
270329AC1-082 GEN1
Solar/Wind Harmer
0.5
970825AG2-519 GEN
Solar/Wind Harmer
5.915
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.404
274752CRETE EC ;2U
Adder
8.473
274753CRETE EC ;3U
Adder
8.473
274772LINCOLN ;3U
Adder
8.673
274724RIVER EC ;11
Adder
18.196
274814UNIV PK N;0U
Adder
5.182
274807UNIV PK N;3U
Adder
5.171
274811UNIV PK N;7U
Adder
5.137
274803UNIV PARK;6U
Adder
5.968
24728705AND G3
Adder
8.209
24728505AND G1
Adder
3.925
274826FISK ;BP
Adder
11.201
972038AH1-567 GEN2
Adder
0.373
972259AH1-714 GEN
Adder
19.5
274676JOLIET 29;8U
Adder
30.174
274729ELWOOD EC;1P
Adder
16.762
274730ELWOOD EC;6P
Adder
16.762
274734ELWOOD EC;8P
Adder
16.762
274736ELWOOD EC;9P
Adder
16.762
274682WAUKEGAN ;7U
Adder
18.178
964991AG1-363 GEN
Solar/Wind Helper
5.171
238108AE1-109 GEN1
Solar/Wind Helper
0.115
238110AE1-109 GEN3
Solar/Wind Helper
0.115
238127S14_GEN_2
Solar/Wind Helper
0.836
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.715
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.023
235063AE1-101 C2
Solar/Wind Helper
1.678
237001AB1-127_GEN
Solar/Wind Helper
0.446
237048AF1-022 C
Solar/Wind Helper
0.186
316415AF1-147_GEN2
Solar/Wind Helper
0.898
205916AD1-020 GEN
Solar/Wind Helper
1.732
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.514
233918AB1-142 GEN
Solar/Wind Helper
0.508
233944AB2-135 GEN
Solar/Wind Helper
0.596
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.513
232408W1-005 C
Solar/Wind Helper
0.513
316447AC1-158 HLD
Solar/Wind Helper
2.876
316044AC1-158 PL1
Solar/Wind Helper
1.307
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.526
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.075
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.093
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.586
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
202652Y1-033 WT C
Solar/Wind Helper
0.504
961301AF2-421 GEN
Solar/Wind Helper
0.443
963151AG1-164 GEN
Solar/Wind Helper
0.443
961341AF2-425 GEN
Solar/Wind Helper
0.442
212507AE2-042_GEN
Solar/Wind Helper
1.561
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.079
NYPJM->LTFIMP_NY
CLTF
4.85
LGEELTFEXP_LGEE->PJM
CLTF
6.747
WECLTFEXP_WEC->PJM
CLTF
3.823
MECLTFEXP_MEC->PJM
CLTF
15.894
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CPLELTFEXP_CPLE->PJM
CLTF
0.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.743
LAGNLTFEXP_LAGN->PJM
CLTF
14.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.742
TVALTFEXP_TVA->PJM
CLTF
7.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.72 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5108.61
MW Contribution:
10.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.082
23559101PLEAS2
50/50
6.18
962761AG1-125 GEN
Solar/Wind Harmer
40.857
970149AG2-104 GEN
Solar/Wind Harmer
25.229
970155AG2-107 GEN
Solar/Wind Harmer
17.815
270520AE2-214 GEN
Solar/Wind Harmer
7.233
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.451
270273AD2-016 GEN
Solar/Wind Harmer
3.008
972269AH1-719 GEN
Adder
2.564
971073AG2-665 GEN
Solar/Wind Harmer
1.273
25326309TAIT D
Adder
1.192
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
241813AF1-122_GEN
Solar/Wind Harmer
5.894
971201AH1-060 GEN
Solar/Wind Harmer
1.842
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.241
960001AF2-291 GEN
Solar/Wind Harmer
3.242
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.696
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.784
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.552
270024AE2-089 GEN
Solar/Wind Harmer
4.947
252510AF1-249 C
Solar/Wind Harmer
0.44
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.355
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270005AE1-210 C O1
Solar/Wind Harmer
5.726
25196808ZIMRHP
Adder
79.465
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
942081AE2-220 GEN
Solar/Wind Harmer
6.698
270209AC1-174_GEN
Solar/Wind Harmer
4.262
270437AC2-090 C
Solar/Wind Harmer
5.845
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.448
274754CRETE EC ;4U
Adder
8.448
274773LINCOLN ;4U
Adder
8.646
274774LINCOLN ;5U
Adder
8.646
274723RIVER EC ;12
Adder
18.356
274812UNIV PK N;8U
Adder
5.122
274802UNIV PARK;5U
Adder
5.949
24728605AND G2
Adder
3.913
274676JOLIET 29;8U
Adder
31.195
274732ELWOOD EC;7P
Adder
16.71
274674JOLIET 9 ;6U
Adder
15.65
972203AH1-686 GEN
Adder
2.333
274745AC1-111 GEN9
Adder
5.66
970091AG2-072 GEN
Adder
77.376
274682WAUKEGAN ;7U
Adder
18.122
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.674
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.532
238126S14_GEN_1
Solar/Wind Helper
0.833
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.663
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.45
237002AB1-128_GEN
Solar/Wind Helper
0.447
23751101LEADS_P59
Solar/Wind Helper
2.129
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.363
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.441
270594AE1-207 GEN
Solar/Wind Harmer
13.331
270032AE2-172
Solar/Wind Harmer
4.566
270119AB2-067 GEN1
50/50
7.082
270120AB2-067 GEN2
50/50
7.082
24318905MLG2
50/50
7.035
270349AD2-093_GEN
Solar/Wind Harmer
4.445
270471AD2-092_GEN
Solar/Wind Harmer
4.445
270054AF2-122 C O1
Solar/Wind Harmer
3.971
946101AF1-275 GEN
Solar/Wind Harmer
1.808
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.053
938701AE1-092 GEN
Solar/Wind Harmer
23.731
270462AD2-086
Solar/Wind Harmer
7.892
270269AC2-059
Solar/Wind Harmer
10.554
972159AH1-661 GEN
Adder
1.111
253378AE2-206_GEN
Solar/Wind Harmer
3.988
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.053
971073AG2-665 GEN
Solar/Wind Harmer
8.757
970879AG2-548 GEN
Solar/Wind Harmer
1.273
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.371
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.713
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.41
944541AF1-119 GEN
Solar/Wind Harmer
4.431
960971AF2-388 GEN
Solar/Wind Harmer
11.568
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.978
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.531
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.405
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.75
270031AE2-169
Solar/Wind Harmer
8.551
270599AE1-208 GEN
Solar/Wind Harmer
8.551
270383AD1-128 GEN
Solar/Wind Harmer
6.401
926881AC1-175 GEN
Solar/Wind Harmer
5.845
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.84
24728805RICHG1
Adder
3.949
24728905RICHG2
Adder
3.949
274770LINCOLN ;1U
Adder
8.646
274771LINCOLN ;2U
Adder
8.646
274805UNIV PK N;1U
Adder
5.133
274808UNIV PK N;4U
Adder
5.099
274674JOLIET 9 ;6U
Adder
15.65
274696ROCKY RD ;4P
Adder
11.497
274695ROCKY RD ;2P
Adder
11.232
274693ROCKY RD ;1P
Adder
11.121
274697ROCKY RD ;3P
Adder
3.051
274683WAUKEGAN ;8U
Adder
21.239
274683WAUKEGAN ;8U
Adder
9.65
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.044
23585401KL_K28_T16
Solar/Wind Helper
1.493
235531U2-073 GEN
Solar/Wind Helper
3.333
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.5
238148AE2-230_GEN2
Solar/Wind Helper
0.5
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.83
237061AD1-155 GEN
Solar/Wind Helper
1.768
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.674
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233982AB2-133 GEN
Solar/Wind Helper
0.362
233946AB2-136 GEN
Solar/Wind Helper
0.574
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
972239AH1-704 GEN
Adder
2.673
270459AD2-067 GEN
Solar/Wind Harmer
10.203
961821AG1-024 GEN
Solar/Wind Harmer
10.359
241955AC1-078 GEN
Solar/Wind Harmer
8.768
241973AD2-163_GEN1
Solar/Wind Harmer
2.315
241974AD2-163_GEN2
Solar/Wind Harmer
2.315
945631AF1-228 GEN
Solar/Wind Harmer
5.44
943861AF1-054 GEN
Solar/Wind Harmer
4.468
943851AF1-053 GEN
Solar/Wind Harmer
2.159
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.013
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
940611AE2-048 GEN
Solar/Wind Harmer
24.928
941391AE2-136 GEN
Solar/Wind Harmer
12.917
270263AC1-001 GEN
Solar/Wind Harmer
1.168
241972AD1-140 GEN
Solar/Wind Harmer
4.999
270291AC1-194 GEN
Solar/Wind Harmer
5.603
970179AG2-119 GEN
Solar/Wind Harmer
8.8
270340AC2-060 GEN
Solar/Wind Harmer
3.323
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.877
270435AC2-044 GEN
Solar/Wind Harmer
2.151
270377AD1-106 GEN
Solar/Wind Harmer
5.62
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.342
959331AF2-224 GEN
Solar/Wind Harmer
10.696
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.674
971567AH1-282 GEN
Solar/Wind Harmer
5.319
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.894
270071AF1-092 GEN
Solar/Wind Harmer
15.924
963791AG1-232 GEN
Solar/Wind Harmer
14.332
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.071
25196408WSDLE3
Adder
9.314
25196308WSDLE2
Adder
9.233
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.955
945581AF1-223 GEN
Solar/Wind Harmer
4.781
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.807
970031AG2-029 GEN
Solar/Wind Harmer
26.342
270543AE2-219 C
Solar/Wind Harmer
10.531
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.099
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.48
274775LINCOLN ;6U
Adder
8.646
274776LINCOLN ;7U
Adder
8.646
274777LINCOLN ;8U
Adder
8.646
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.914
274800UNIV PARK;3U
Adder
5.946
274801UNIV PARK;4U
Adder
5.946
972228AH1-698 GEN2
Adder
3.777
972227AH1-698 GEN1
Adder
2.66
274687WILL CNTY;4U
Adder
28.425
274687WILL CNTY;4U
Adder
28.425
274675JOLIET 29;7U
Adder
31.195
274675JOLIET 29;7U
Adder
30.081
274728ELWOOD EC;5P
Adder
16.71
274731ELWOOD EC;2P
Adder
16.71
274733ELWOOD EC;3P
Adder
16.71
274735ELWOOD EC;4P
Adder
16.71
274744AC1-111 GEN8
Adder
5.66
274746AC1-111 G10
Adder
5.66
23750701CROSSCHOOL
Solar/Wind Helper
1.512
238118U2-030_1
Solar/Wind Helper
0.344
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.644
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.234
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
203955AF1-039 C O1
Solar/Wind Helper
0.331
24318805MLG1
50/50
10.084
23559001PLEAS1
50/50
6.18
270051AF1-062 GEN
50/50
11.783
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.857
970153AG2-106 GEN
Solar/Wind Harmer
17.815
961921AG1-034 GEN
Solar/Wind Harmer
15.539
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.892
942051AE2-217 GEN
Solar/Wind Harmer
20.96
960801AF2-371 GEN
Solar/Wind Harmer
2.935
964871AG1-351 GEN
Solar/Wind Harmer
2.026
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.795
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.716
971199AH1-059 GEN
Solar/Wind Harmer
2.315
970879AG2-548 GEN
Solar/Wind Harmer
8.757
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.713
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.279
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.022
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.488
958091AF2-103 GEN
Solar/Wind Harmer
0.172
24695305TIMB G C
Solar/Wind Harmer
3.564
270588AE1-091_GEN
Solar/Wind Harmer
11.739
944531AF1-118 GEN
Solar/Wind Harmer
37.25
270043AE2-236 GEN
Solar/Wind Harmer
5.848
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.18
957741AF2-068 GEN
Solar/Wind Harmer
15.775
971347AH1-153 GEN
Solar/Wind Harmer
5.25
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.7
270004AE1-209 GEN
Solar/Wind Harmer
5.726
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
24379505HDWTR1G C
Solar/Wind Harmer
8.281
270240V3-007_GEN2
Solar/Wind Harmer
6.479
970825AG2-519 GEN
Solar/Wind Harmer
5.897
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.448
274753CRETE EC ;3U
Adder
8.448
274772LINCOLN ;3U
Adder
8.646
274724RIVER EC ;11
Adder
18.141
274814UNIV PK N;0U
Adder
5.166
274807UNIV PK N;3U
Adder
5.155
274811UNIV PK N;7U
Adder
5.122
274803UNIV PARK;6U
Adder
5.949
24728705AND G3
Adder
8.184
24728505AND G1
Adder
3.913
274826FISK ;BP
Adder
11.167
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.441
274676JOLIET 29;8U
Adder
30.081
274729ELWOOD EC;1P
Adder
16.71
274730ELWOOD EC;6P
Adder
16.71
274734ELWOOD EC;8P
Adder
16.71
274736ELWOOD EC;9P
Adder
16.71
274682WAUKEGAN ;7U
Adder
18.122
964991AG1-363 GEN
Solar/Wind Helper
5.16
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.833
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.015
235063AE1-101 C2
Solar/Wind Helper
1.674
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.185
316415AF1-147_GEN2
Solar/Wind Helper
0.896
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.507
233944AB2-135 GEN
Solar/Wind Helper
0.595
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.519
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.582
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
202652Y1-033 WT C
Solar/Wind Helper
0.501
961341AF2-425 GEN
Solar/Wind Helper
0.441
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.966
NYPJM->LTFIMP_NY
CLTF
4.834
LGEELTFEXP_LGEE->PJM
CLTF
6.725
MECLTFEXP_MEC->PJM
CLTF
15.842
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.337
LAGNLTFEXP_LAGN->PJM
CLTF
14.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.682
TVALTFEXP_TVA->PJM
CLTF
7.257
WECLTFEXP_WEC->PJM
CLTF
3.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5094.21
MW Contribution:
10.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5094.21
MW Contribution:
10.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.83
MW Contribution:
6.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.678
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
270119AB2-067 GEN1
50/50
7.069
270120AB2-067 GEN2
50/50
7.069
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270166AC1-044 GEN3
50/50
7.069
23559101PLEAS2
50/50
6.097
24318805MLG1
50/50
10.065
23559001PLEAS1
50/50
6.097
270051AF1-062 GEN
50/50
11.777
270475AD2-096_GEN
50/50
7.114
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
961921AG1-034 GEN
Solar/Wind Harmer
7.586
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
962761AG1-125 GEN
Solar/Wind Harmer
34.394
970149AG2-104 GEN
Solar/Wind Harmer
18.573
970155AG2-107 GEN
Solar/Wind Harmer
21.963
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.894
270273AD2-016 GEN
Solar/Wind Harmer
0.807
972269AH1-719 GEN
Adder
2.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965421AG1-410 GEN
Solar/Wind Harmer
22.47
960001AF2-291 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965011AG1-365 GEN
Solar/Wind Harmer
7.453
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
958861AF2-177 GEN
Solar/Wind Harmer
3.191
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.732
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.351
970825AG2-519 GEN
Solar/Wind Harmer
2.589
24639705ELKHART HY
Adder
0.16
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
276903AD2-071 C
Solar/Wind Harmer
8.095
25196008MFTGT1
Adder
1.443
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.365
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274754CRETE EC ;4U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
274802UNIV PARK;5U
Adder
5.941
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
31.151
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
939401AE1-172 GEN
Solar/Wind Harmer
5.275
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
274682WAUKEGAN ;7U
Adder
18.096
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.818
971997AH1-543 GEN
Solar/Wind Harmer
3.68
962781AG1-127 GEN
Solar/Wind Harmer
6.668
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
316095T157 G97
Solar/Wind Helper
1.51
23583801GRNGAP
Solar/Wind Helper
5.626
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
238126S14_GEN_1
Solar/Wind Helper
0.831
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.661
237038AE2-054 C
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.31
938701AE1-092 GEN
Solar/Wind Harmer
12.867
971655AH1-328 GEN
Solar/Wind Harmer
2.843
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
25326509SID D
Adder
1.446
971073AG2-665 GEN
Solar/Wind Harmer
5.597
970879AG2-548 GEN
Solar/Wind Harmer
1.272
25326109MON D
Adder
1.437
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
246937BC-WTG2
Solar/Wind Harmer
0.302
270246TR4_N_V150
Solar/Wind Harmer
0.048
270247TR4_N_V136
Solar/Wind Harmer
0.048
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.351
944541AF1-119 GEN
Solar/Wind Harmer
0.492
960971AF2-388 GEN
Solar/Wind Harmer
4.326
942221AE2-234 GEN
Solar/Wind Harmer
2.958
25194408D.CRK1
Adder
7.968
25194508D.CRK3
Adder
1.49
970621AG2-405 GEN
Solar/Wind Harmer
1.345
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970885AG2-551 GEN
Solar/Wind Harmer
2.446
247621Y3-024
Adder
0.253
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270031AE2-169
Solar/Wind Harmer
4.021
270599AE1-208 GEN
Solar/Wind Harmer
6.701
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728805RICHG1
Adder
3.944
24728905RICHG2
Adder
3.944
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.052
965791AG1-447 GEN
Solar/Wind Harmer
6.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274805UNIV PK N;1U
Adder
5.126
274808UNIV PK N;4U
Adder
5.092
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
276776AD2-060 GEN
Solar/Wind Harmer
0.758
958011AF2-095 GEN
Solar/Wind Harmer
10.234
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
274674JOLIET 9 ;6U
Adder
15.628
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274696ROCKY RD ;4P
Adder
11.481
274695ROCKY RD ;2P
Adder
11.216
274693ROCKY RD ;1P
Adder
11.106
274697ROCKY RD ;3P
Adder
3.047
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276901AD2-066 C O1
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
962691AG1-118 GEN
Solar/Wind Harmer
21.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
942111AE2-223 GEN
Solar/Wind Harmer
2.266
316097T157 G90
Solar/Wind Helper
1.51
235054AD2-180 GEN
Solar/Wind Helper
2.04
23585401KL_K28_T16
Solar/Wind Helper
1.489
235531U2-073 GEN
Solar/Wind Helper
3.327
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.344
235062AE1-101 C1
Solar/Wind Helper
1.672
316411AF1-147_GEN1
Solar/Wind Helper
0.895
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.118
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
970191AG2-125 GEN
Solar/Wind Harmer
1.937
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
971191AH1-055 GEN
Solar/Wind Harmer
19.175
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
944531AF1-118 GEN
Solar/Wind Harmer
33.233
270043AE2-236 GEN
Solar/Wind Harmer
4.754
252519AF1-045_GEN
Solar/Wind Harmer
3.844
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
9.036
25194608D.CRK4
Adder
1.732
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
971347AH1-153 GEN
Solar/Wind Harmer
3.658
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.95
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
970289AG2-191 GEN
Solar/Wind Harmer
0.8
945111AF1-176 GEN
Solar/Wind Harmer
5.891
247642Z2-115 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
274753CRETE EC ;3U
Adder
8.436
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274811UNIV PK N;7U
Adder
5.114
972167AH1-666 GEN
Solar/Wind Harmer
5.69
274803UNIV PARK;6U
Adder
5.941
24728705AND G3
Adder
8.173
24728505AND G1
Adder
3.908
274887GEN-1.85
Solar/Wind Harmer
0.185
276843GEN-1.7
Solar/Wind Harmer
0.23
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274826FISK ;BP
Adder
11.151
972038AH1-567 GEN2
Adder
0.372
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
972259AH1-714 GEN
Adder
19.413
274676JOLIET 29;8U
Adder
30.039
274729ELWOOD EC;1P
Adder
16.687
274730ELWOOD EC;6P
Adder
16.687
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
274682WAUKEGAN ;7U
Adder
18.096
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970193AG2-126 GEN
Solar/Wind Harmer
10.468
970571AG2-364 GEN
Solar/Wind Harmer
13.944
964991AG1-363 GEN
Solar/Wind Helper
5.155
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.831
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
23562501BACKB
Solar/Wind Helper
1.012
235063AE1-101 C2
Solar/Wind Helper
1.672
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.512
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.594
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.868
316044AC1-158 PL1
Solar/Wind Helper
1.303
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270291AC1-194 GEN
Solar/Wind Harmer
0
970179AG2-119 GEN
Solar/Wind Harmer
6.854
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
253406AD2-031_GEN
Solar/Wind Harmer
0.559
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270377AD1-106 GEN
Solar/Wind Harmer
2.842
247521TR3_G114
Solar/Wind Harmer
0.27
965051AG1-369 GEN
Solar/Wind Harmer
3.723
959331AF2-224 GEN
Solar/Wind Harmer
5.217
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.438
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
963791AG1-232 GEN
Solar/Wind Harmer
9.987
270071AF1-092 GEN
Solar/Wind Harmer
14.177
971985AH1-537 GEN
Solar/Wind Harmer
2.196
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
25196508WSDLE4
Adder
8.944
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
270543AE2-219 C
Solar/Wind Harmer
5.137
247536S-71 GEN
Solar/Wind Harmer
0.293
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
970289AG2-191 GEN
Solar/Wind Harmer
1.382
971771AH1-392 GEN
Solar/Wind Harmer
7.271
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
971549AH1-272 GEN
Solar/Wind Harmer
14.794
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.634
274776LINCOLN ;7U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972228AH1-698 GEN2
Adder
3.772
972227AH1-698 GEN1
Adder
2.656
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
274728ELWOOD EC;5P
Adder
16.687
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274735ELWOOD EC;4P
Adder
16.687
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
274744AC1-111 GEN8
Adder
5.652
274746AC1-111 G10
Adder
5.652
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
970169AG2-114 GEN
Solar/Wind Harmer
7.011
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
971411AH1-196 GEN
Solar/Wind Harmer
10.47
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.32
23750701CROSSCHOOL
Solar/Wind Helper
1.509
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.792
211065PSPA IPP
Solar/Wind Helper
0.152
963161AG1-165 GEN
Solar/Wind Helper
0.441
957471AF2-041 GEN
Solar/Wind Harmer
13.586
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.17
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
203975AE1-071-GEN
Solar/Wind Helper
2.516
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.58
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
202652Y1-033 WT C
Solar/Wind Helper
0.5
959091AF2-200 GEN
Solar/Wind Harmer
9.057
205956AE1-196_GEN
Solar/Wind Helper
0.512
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.062
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.057
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.031
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5005.84
MW Contribution:
10.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10
23559001PLEAS1
50/50
5.445
270051AF1-062 GEN
50/50
11.971
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
270518AE2-148 GEN
Solar/Wind Harmer
13.997
958581AF2-149 GEN
Solar/Wind Harmer
4.955
971199AH1-059 GEN
Solar/Wind Harmer
2.432
24721905FLATG4
Adder
23.444
253325AC1-069 GEN
Solar/Wind Harmer
1.205
970065AG2-057 GEN
Solar/Wind Harmer
0.972
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
961961AG1-039 GEN
Solar/Wind Harmer
3.18
246938BC-WTG3
Solar/Wind Harmer
4.404
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
970879AG2-548 GEN
Solar/Wind Harmer
8.835
958091AF2-103 GEN
Solar/Wind Harmer
0.178
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270043AE2-236 GEN
Solar/Wind Harmer
5.961
944531AF1-118 GEN
Solar/Wind Harmer
37.819
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971191AH1-055 GEN
Solar/Wind Harmer
20.005
971347AH1-153 GEN
Solar/Wind Harmer
5.342
247643Z2-116 C
Solar/Wind Harmer
0.074
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25196608WSDLE5
Adder
9.116
25194608D.CRK4
Adder
1.747
270367AC2-061_GEN
Solar/Wind Harmer
3.375
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
25196008MFTGT1
Adder
1.409
274752CRETE EC ;2U
Adder
8.571
274753CRETE EC ;3U
Adder
8.571
274724RIVER EC ;11
Adder
18.401
270166AC1-044 GEN3
50/50
7.05
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
962761AG1-125 GEN
Solar/Wind Harmer
40.867
970149AG2-104 GEN
Solar/Wind Harmer
25.235
970155AG2-107 GEN
Solar/Wind Harmer
17.82
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
971995AH1-542 GEN
Solar/Wind Harmer
12.942
972269AH1-719 GEN
Adder
2.693
270317AD1-130_GEN
Solar/Wind Harmer
3.738
270485AE1-090_GEN
Solar/Wind Harmer
0.706
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965421AG1-410 GEN
Solar/Wind Harmer
33.164
971073AG2-665 GEN
Solar/Wind Harmer
1.284
25326309TAIT D
Adder
1.207
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
270297AD1-101 GEN
Solar/Wind Harmer
2.226
965011AG1-365 GEN
Solar/Wind Harmer
10.939
270258AD1-119 GEN
Solar/Wind Harmer
2.219
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
270119AB2-067 GEN1
50/50
7.05
270120AB2-067 GEN2
50/50
7.05
24318905MLG2
50/50
7.451
270054AF2-122 C O1
Solar/Wind Harmer
4.054
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
946101AF1-275 GEN
Solar/Wind Harmer
1.838
253383AE2-342_GEN
Solar/Wind Harmer
1.057
938701AE1-092 GEN
Solar/Wind Harmer
24.428
942861AE2-305 GEN
Solar/Wind Harmer
9.201
270462AD2-086
Solar/Wind Harmer
8.12
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
253415AE1-040 GEN
Solar/Wind Harmer
1.252
25326109MON D
Adder
1.457
246937BC-WTG2
Solar/Wind Harmer
4.329
971073AG2-665 GEN
Solar/Wind Harmer
8.835
970879AG2-548 GEN
Solar/Wind Harmer
1.284
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
942801AE2-298 GEN
Solar/Wind Harmer
1.666
247607V1-011 GEN
Solar/Wind Harmer
4.348
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
270247TR4_N_V136
Solar/Wind Harmer
0.933
247522W1-056 GEN
Solar/Wind Harmer
2.469
253349AC2-067 GEN
Solar/Wind Harmer
2.225
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944231AF1-091 GEN
Solar/Wind Harmer
19.433
942221AE2-234 GEN
Solar/Wind Harmer
3.759
944541AF1-119 GEN
Solar/Wind Harmer
4.494
960971AF2-388 GEN
Solar/Wind Harmer
11.731
247620Y3-023
Adder
0.492
970349AG2-230 GEN
Solar/Wind Harmer
16.027
247621Y3-024
Adder
0.257
25183208HLCRTG
Solar/Wind Harmer
6.454
970883AG2-550 GEN
Solar/Wind Harmer
10.668
970885AG2-551 GEN
Solar/Wind Harmer
2.481
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
270201AC2-176 GEN
Solar/Wind Harmer
5.48
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
24728905RICHG2
Adder
3.989
970935AG2-582 GEN
Adder
238.716
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
238148AE2-230_GEN2
Solar/Wind Helper
0.556
238149AF1-291A_GEN
Solar/Wind Helper
0.159
237061AD1-155 GEN
Solar/Wind Helper
1.974
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
23585401KL_K28_T16
Solar/Wind Helper
1.534
235020AA1-095 C
Solar/Wind Helper
0.058
238117U2-030
Solar/Wind Helper
0.357
238221AF1-254 C O1
Solar/Wind Helper
0.297
237080AD1-060 GEN
Solar/Wind Helper
0.369
235062AE1-101 C1
Solar/Wind Helper
1.786
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
237006AB1-125 GEN
Solar/Wind Helper
0.132
316006AB2-029 C
Solar/Wind Helper
0.131
223401AF1-299 GEN
Solar/Wind Helper
0.389
223402AF1-300 C
Solar/Wind Helper
0.389
316045AC1-158 PL2
Solar/Wind Helper
4.643
972239AH1-704 GEN
50/50
3.095
270459AD2-067 GEN
Solar/Wind Harmer
10.428
961821AG1-024 GEN
Solar/Wind Harmer
10.588
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270302AB2-170 GEN
Solar/Wind Harmer
9.776
270432AC2-029 GEN
Solar/Wind Harmer
8.117
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253338AC1-165 GEN
Solar/Wind Harmer
1.249
253343AC1-166 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270377AD1-106 GEN
Solar/Wind Harmer
5.917
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270291AC1-194 GEN
Solar/Wind Harmer
5.669
270340AC2-060 GEN
Solar/Wind Harmer
3.354
957201AF2-014 GEN
Solar/Wind Harmer
5.019
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
270191TR4_S_V150
Solar/Wind Harmer
3.29
965051AG1-369 GEN
Solar/Wind Harmer
5.479
25306009OHH W.
Adder
3.158
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
958711AF2-162 GEN
Solar/Wind Harmer
1.086
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
270499AE1-146 GEN
Solar/Wind Harmer
2.679
270543AE2-219 C
Solar/Wind Harmer
10.668
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
964611AG1-324 GEN
Solar/Wind Harmer
4.154
971771AH1-392 GEN
Solar/Wind Harmer
9.58
944161AF1-084 GEN
Solar/Wind Harmer
2.352
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196508WSDLE4
Adder
9.023
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274775LINCOLN ;6U
Adder
8.764
274776LINCOLN ;7U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972228AH1-698 GEN2
Adder
3.828
972227AH1-698 GEN1
Adder
2.695
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
274728ELWOOD EC;5P
Adder
16.929
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
274735ELWOOD EC;4P
Adder
16.929
23750701CROSSCHOOL
Solar/Wind Helper
1.591
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
226929AD2-058 GEN
Solar/Wind Helper
0.108
3141426STAFORD
Solar/Wind Helper
0.058
315651AD1-115 GEN
Solar/Wind Helper
0.883
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
959381AF2-229 GEN
Solar/Wind Helper
0.368
20390526W1-045 C
Solar/Wind Helper
0.361
205943AE1-185 GEN
Solar/Wind Helper
0.521
205956AE1-196_GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.238
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
230434AG1-499 GEN
Solar/Wind Helper
0.234
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
958861AF2-177 GEN
Solar/Wind Harmer
11.712
960001AF2-291 GEN
Solar/Wind Harmer
3.236
24639705ELKHART HY
Adder
0.164
945371AF1-202 GEN
Solar/Wind Harmer
7.453
270216AD2-079_GEN
Solar/Wind Harmer
0.645
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
944031AF1-071 GEN
Solar/Wind Harmer
1.069
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25194608D.CRK4
Adder
1.747
25196808ZIMRHP
Adder
79.955
23906502RICHG2&3
Adder
1.268
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274754CRETE EC ;4U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
274812UNIV PK N;8U
Adder
5.194
274802UNIV PARK;5U
Adder
6.031
23920202STRYCT
Adder
1.44
274676JOLIET 29;8U
Adder
31.606
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
23583801GRNGAP
Solar/Wind Helper
6.383
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
23546401DTGZ2-030
Solar/Wind Helper
0.1
238120AE2-309 GEN
Solar/Wind Helper
0.557
238126S14_GEN_1
Solar/Wind Helper
0.87
237038AE2-054 C
Solar/Wind Helper
0.294
235067AD1-061 GEN
Solar/Wind Helper
0.481
237085AD2-009_GEN
Solar/Wind Helper
1.776
237002AB1-128_GEN
Solar/Wind Helper
0.477
3141196NOKESVL
Solar/Wind Helper
1.144
23777801MSM_W1-116
Solar/Wind Helper
0.123
226910AB2-157 C
Solar/Wind Helper
0.016
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
3132273ORANGE
Solar/Wind Helper
0.049
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
232417X3-008 C
Solar/Wind Helper
0.238
233964AF2-378 GEN
Solar/Wind Helper
0.043
3147666LOUISA
Solar/Wind Helper
0.553
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
233950AC2-186 GEN
Solar/Wind Helper
0.119
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
966881AG1-559 GEN
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
205941AD2-115 GEN
Solar/Wind Helper
0.499
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.777
211065PSPA IPP
Solar/Wind Helper
0.151
960841AF2-375 GEN
Solar/Wind Harmer
0.624
274772LINCOLN ;3U
Adder
8.764
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274811UNIV PK N;7U
Adder
5.194
274803UNIV PARK;6U
Adder
6.031
274826FISK ;BP
Adder
11.319
972038AH1-567 GEN2
Adder
0.377
972259AH1-714 GEN
Adder
19.698
274676JOLIET 29;8U
Adder
30.477
274729ELWOOD EC;1P
Adder
16.929
274730ELWOOD EC;6P
Adder
16.929
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238108AE1-109 GEN1
Solar/Wind Helper
0.122
238110AE1-109 GEN3
Solar/Wind Helper
0.122
238152AF2-075_GEN
Solar/Wind Helper
0.794
238175AF1-290_GEN
Solar/Wind Helper
0.173
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
235063AE1-101 C2
Solar/Wind Helper
1.786
237001AB1-127_GEN
Solar/Wind Helper
0.476
316415AF1-147_GEN2
Solar/Wind Helper
0.984
23562501BACKB
Solar/Wind Helper
1
316447AC1-158 HLD
Solar/Wind Helper
3.193
316044AC1-158 PL1
Solar/Wind Helper
1.451
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.521
233918AB1-142 GEN
Solar/Wind Helper
0.514
233944AB2-135 GEN
Solar/Wind Helper
0.603
232426Y1-080 FULL
Solar/Wind Helper
0.04
3147666LOUISA
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
232408W1-005 C
Solar/Wind Helper
0.518
316192AB2-158 GEN
Solar/Wind Helper
1.618
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674628WNG_W3-110
Solar/Wind Helper
0.09
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674928WA_W3-044
Solar/Wind Helper
0.099
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.573
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.151
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
20675128HRM_W1-127
Solar/Wind Helper
0.03
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
232424Y1-079 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.581
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
232410W1-006 C
Solar/Wind Helper
0.518
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
966001AG1-469 GEN
Solar/Wind Helper
0.256
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.152
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
NYPJM->LTFIMP_NY
CLTF
4.574
LGEELTFEXP_LGEE->PJM
CLTF
6.731
WECLTFEXP_WEC->PJM
CLTF
3.853
MECLTFEXP_MEC->PJM
CLTF
15.924
SIGELTFEXP_SIGE->PJM
CLTF
0.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4761.71
MW Contribution:
6.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.27 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6477.04
MW Contribution:
13.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
7.699
270053AF1-130 C
Solar/Wind Harmer
30.765
270399AC1-101 GEN
Solar/Wind Harmer
7.281
270400AC1-102 GEN
Solar/Wind Harmer
7.281
970281AG2-184 GEN
Solar/Wind Harmer
32.719
971985AH1-537 GEN
Solar/Wind Harmer
27.788
941621AE2-160 GEN
Adder
5.034
962211AG1-066 GEN
Solar/Wind Harmer
3.649
971313AH1-133 GEN
Solar/Wind Harmer
8.798
972163AH1-664 GEN
Solar/Wind Harmer
14.536
972165AH1-665 GEN
Solar/Wind Harmer
11.629
339216AC1-074 GEN
Solar/Wind Harmer
2.394
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
253433AC1-085 GEN1
Solar/Wind Harmer
7.506
253432AC1-085 GEN2
Solar/Wind Harmer
0.378
270340AC2-060 GEN
Solar/Wind Harmer
4.256
253406AD2-031_GEN
Solar/Wind Harmer
1.796
270263AC1-001 GEN
Solar/Wind Harmer
1.464
270444AC2-157 GEN1
Solar/Wind Harmer
7.815
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
927014AC1-188 GEN
Solar/Wind Harmer
2.477
970913AG2-568 GEN
Solar/Wind Harmer
10.623
971225AH1-072 GEN
Solar/Wind Harmer
3.04
971227AH1-073 GEN
Solar/Wind Harmer
3.04
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
7.389
961491AF2-440 GEN
Solar/Wind Harmer
3.071
971073AG2-665 GEN
Solar/Wind Harmer
11.654
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.369
972043AH1-570 GEN
Solar/Wind Harmer
3.585
972045AH1-571 GEN
Solar/Wind Harmer
2.868
25183208HLCRTG
Solar/Wind Harmer
8.652
971125AH1-004 GEN
Solar/Wind Harmer
5.691
970107AG2-081 GEN
Solar/Wind Harmer
4.268
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
14.201
253415AE1-040 GEN
Solar/Wind Harmer
1.57
964571AG1-320 GEN
Solar/Wind Harmer
11.341
270269AC2-059
Solar/Wind Harmer
12.798
24728805RICHG1
Adder
5.185
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
270331AC1-082 GEN3
Solar/Wind Harmer
0.844
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
5.223
971403AH1-188 GEN
Solar/Wind Harmer
23.963
962761AG1-125 GEN
Solar/Wind Harmer
54.553
970149AG2-104 GEN
Solar/Wind Harmer
33.686
970155AG2-107 GEN
Solar/Wind Harmer
23.787
971687AH1-348 GEN
Solar/Wind Harmer
1.522
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
27.387
339221AD2-048_GEN
Solar/Wind Harmer
2.202
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
14.288
252510AF1-249 C
Solar/Wind Harmer
0.594
25196008MFTGT1
Adder
1.98
943111AE2-339 GEN
Solar/Wind Harmer
1.257
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
11.825
946171AF1-282 GEN
Solar/Wind Harmer
14.124
339211AE2-254 GEN
Solar/Wind Harmer
2.115
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
6.325
270222AC2-111 GEN
Solar/Wind Harmer
6.156
944031AF1-071 GEN
Solar/Wind Harmer
1.385
970653AG2-424 GEN
Solar/Wind Harmer
6.638
270273AD2-016 GEN
Solar/Wind Harmer
3.648
24728605AND G2
Adder
5.248
339241AF1-083 GEN
Solar/Wind Harmer
2.268
942081AE2-220 GEN
Solar/Wind Harmer
8.696
270209AC1-174_GEN
Solar/Wind Harmer
5.534
270437AC2-090 C
Solar/Wind Harmer
7.589
270239V3-007_GEN1
Solar/Wind Harmer
2.34
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
13.523
963741AG1-226 GEN
Solar/Wind Harmer
60.722
964901AG1-354 GEN
Solar/Wind Harmer
20.24
270594AE1-207 GEN
Solar/Wind Harmer
18.313
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
2.824
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
11.163
24386605FR-22G C
Solar/Wind Harmer
5.776
24791305MDL-5G
Solar/Wind Harmer
3.222
945371AF1-202 GEN
Solar/Wind Harmer
9.316
958861AF2-177 GEN
Solar/Wind Harmer
14.534
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
274745AC1-111 GEN9
Adder
7.28
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
270330AC1-082 GEN2
Solar/Wind Harmer
0.842
270329AC1-082 GEN1
Solar/Wind Harmer
0.842
962771AG1-126 GEN
Solar/Wind Harmer
54.553
970153AG2-106 GEN
Solar/Wind Harmer
23.787
971191AH1-055 GEN
Solar/Wind Harmer
31.162
957541AF2-048 GEN
Solar/Wind Harmer
2.477
972103AH1-617 GEN
Solar/Wind Harmer
31.161
960911AF2-382 GEN
Solar/Wind Harmer
11.466
971461AH1-227 GEN
Solar/Wind Harmer
7.797
270367AC2-061_GEN
Solar/Wind Harmer
4.689
270186AC1-089 GEN
Solar/Wind Harmer
9.011
970879AG2-548 GEN
Solar/Wind Harmer
11.654
972167AH1-666 GEN
Solar/Wind Harmer
11.619
252507AC2-088 GEN
Solar/Wind Harmer
2.586
958171AF2-111 GEN
Solar/Wind Harmer
35.846
339243AC2-075 GEN1
Solar/Wind Harmer
0.648
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
252524AE2-267 GEN
Solar/Wind Harmer
2.234
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
7.507
253317AC1-085 GEN4
Solar/Wind Harmer
11.825
946181AF1-283 GEN
Solar/Wind Harmer
18.362
253394AE2-221_GEN
Solar/Wind Harmer
6.325
970455AG2-298 GEN
Solar/Wind Harmer
4.865
970653AG2-424 GEN
Solar/Wind Harmer
0.96
339206AE1-143 GEN
Solar/Wind Harmer
2.932
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
20.406
24379505HDWTR1G C
Solar/Wind Harmer
10.752
270240V3-007_GEN2
Solar/Wind Harmer
8.412
253303V4-073 C
Solar/Wind Harmer
0.157
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
12.206
247642Z2-115 C
Solar/Wind Harmer
0.086
965461AG1-414 GEN
Solar/Wind Harmer
3.058
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
7.583
946031AF1-268 GEN
Solar/Wind Harmer
11.153
24386205FR-12G C
Solar/Wind Harmer
5.756
960071AF2-298 GEN
Solar/Wind Harmer
2.031
339255AE2-071 GEN
Solar/Wind Harmer
1.57
339250AF1-203 GEN
Solar/Wind Harmer
0.808
24690905MDL-1G C
Solar/Wind Harmer
10.73
970781AG2-491 GEN
Solar/Wind Harmer
13.365
962031AG1-047 GEN
Solar/Wind Harmer
4.019
274772LINCOLN ;3U
Adder
11.001
972259AH1-714 GEN
Adder
24.853
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
274682WAUKEGAN ;7U
Adder
7.239
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
957741AF2-068 GEN
Solar/Wind Harmer
8.281
270445AC2-157 GEN2
Solar/Wind Harmer
7.815
270291AC1-194 GEN
Solar/Wind Harmer
7.123
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
6.333
971061AG2-657 GEN
Solar/Wind Harmer
12.288
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
2.562
963841AG1-237 GEN
Solar/Wind Harmer
14.713
971029AG2-637 GEN
Solar/Wind Harmer
20.191
24386405FR-21G C
Solar/Wind Harmer
5.776
24387005FR-3G C
Solar/Wind Harmer
5.313
270543AE2-219 C
Solar/Wind Harmer
13.404
946581AF1-322 GEN
Solar/Wind Harmer
13.675
24691005MDL-2G C
Solar/Wind Harmer
4.942
945581AF1-223 GEN
Solar/Wind Harmer
6.056
247536S-71 GEN
Solar/Wind Harmer
5.402
964611AG1-324 GEN
Solar/Wind Harmer
5.196
270432AC2-029 GEN
Solar/Wind Harmer
9.322
944221AF1-090 GEN
Solar/Wind Harmer
14.552
961761AG1-017 GEN
Solar/Wind Harmer
0.569
24729505KEY G4
Adder
8.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
972267AH1-718 GEN
Adder
5.423
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274823ROCKFORD ;21
Adder
25.367
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
18.959
926881AC1-175 GEN
Solar/Wind Harmer
7.589
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
8.27
339231AF1-038_GEN
Solar/Wind Harmer
2.457
24725505WLD G2 C
Solar/Wind Harmer
5.381
24699105WLD G1 C
Solar/Wind Harmer
5.319
339236AF1-050_GEN
Solar/Wind Harmer
2.451
970241AG2-163 GEN
Solar/Wind Harmer
33.734
970291AG2-192 GEN
Solar/Wind Harmer
1.753
970291AG2-192 GEN
Solar/Wind Harmer
0.565
253349AC2-067 GEN
Solar/Wind Harmer
2.741
253400AC2-068 GEN
Solar/Wind Harmer
1.102
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
6.822
966841AG1-555 GEN
Solar/Wind Harmer
3.372
970883AG2-550 GEN
Solar/Wind Harmer
13.404
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
4.927
24755605MDL-5G
Solar/Wind Harmer
3.222
24697905MDL-4G C
Solar/Wind Harmer
3.067
270181AB1-006 GEN2
Solar/Wind Harmer
0.956
971485AH1-239 GEN
Solar/Wind Harmer
10.681
964781AG1-341 GEN
Solar/Wind Harmer
14.151
966021AG1-471 GEN
Solar/Wind Harmer
7.208
270031AE2-169
Solar/Wind Harmer
10.876
270599AE1-208 GEN
Solar/Wind Harmer
10.876
945421AF1-207 GEN
Solar/Wind Harmer
18.73
957841AF2-078 GEN
Solar/Wind Harmer
8.063
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
6.831
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
274674JOLIET 9 ;6U
Adder
20.046
274683WAUKEGAN ;8U
Adder
27.432
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6428.58
MW Contribution:
9.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
962771AG1-126 GEN
Solar/Wind Harmer
46.005
970153AG2-106 GEN
Solar/Wind Harmer
29.378
971191AH1-055 GEN
Solar/Wind Harmer
29.882
972103AH1-617 GEN
Solar/Wind Harmer
21.74
960911AF2-382 GEN
Solar/Wind Harmer
7.999
971461AH1-227 GEN
Solar/Wind Harmer
5.44
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
7.453
972167AH1-666 GEN
Solar/Wind Harmer
8.106
252507AC2-088 GEN
Solar/Wind Harmer
0.453
958171AF2-111 GEN
Solar/Wind Harmer
25.009
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
8.38
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
12.81
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.77
970653AG2-424 GEN
Solar/Wind Harmer
0.96
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
14.237
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
8.358
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
2.038
970191AG2-125 GEN
Solar/Wind Harmer
2.419
970825AG2-519 GEN
Solar/Wind Harmer
7.074
946031AF1-268 GEN
Solar/Wind Harmer
8.922
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.325
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.91
942481AE2-261 GEN
Solar/Wind Harmer
27.692
957381AF2-032 GEN
Solar/Wind Harmer
2.099
971993AH1-541 GEN
Solar/Wind Harmer
4.271
943031AE2-326 GEN
Solar/Wind Harmer
4.803
965091AG1-374 GEN
Solar/Wind Harmer
27.602
959611AF2-252 GEN
Solar/Wind Harmer
3.067
944531AF1-118 GEN
Solar/Wind Harmer
41.107
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.304
970571AG2-364 GEN
Solar/Wind Harmer
18.217
253325AC1-069 GEN
Solar/Wind Harmer
0.01
276868AE1-113 GEN
Solar/Wind Harmer
1.82
274879MINONK ;1U
Solar/Wind Harmer
0.38
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.001
970707AG2-453 GEN
Solar/Wind Harmer
29.702
943121AE2-341 GEN
Solar/Wind Harmer
15.239
943591AF1-030 GEN
Solar/Wind Harmer
10.134
274862TOP CROP ;2U
Solar/Wind Harmer
1.227
972259AH1-714 GEN
Adder
24.853
274855GSG-6 ;RU
Solar/Wind Harmer
0.332
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
946671AF1-331 GEN
Solar/Wind Harmer
0.969
959091AF2-200 GEN
Solar/Wind Harmer
18.173
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
965931AG1-462 GEN
Solar/Wind Harmer
23.167
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
971087AG2-675 GEN
Solar/Wind Harmer
4.845
274682WAUKEGAN ;7U
Adder
7.239
274887GEN-1.85
Solar/Wind Harmer
0.236
276843GEN-1.7
Solar/Wind Harmer
0.294
276806AD2-047 C O1
Solar/Wind Harmer
5.144
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
27.062
270399AC1-101 GEN
Solar/Wind Harmer
3.79
270400AC1-102 GEN
Solar/Wind Harmer
3.79
970281AG2-184 GEN
Solar/Wind Harmer
22.827
971985AH1-537 GEN
Solar/Wind Harmer
3.231
941621AE2-160 GEN
Adder
5.034
971313AH1-133 GEN
Solar/Wind Harmer
5.062
972163AH1-664 GEN
Solar/Wind Harmer
11.291
972165AH1-665 GEN
Solar/Wind Harmer
9.043
339216AC1-074 GEN
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.728
270263AC1-001 GEN
Solar/Wind Harmer
0.978
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971061AG2-657 GEN
Solar/Wind Harmer
6.001
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
1.788
963841AG1-237 GEN
Solar/Wind Harmer
4.07
971029AG2-637 GEN
Solar/Wind Harmer
14.087
24386405FR-21G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.546
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.372
971609AH1-304 GEN
Solar/Wind Harmer
1.521
964611AG1-324 GEN
Solar/Wind Harmer
3.625
270432AC2-029 GEN
Solar/Wind Harmer
4.119
944221AF1-090 GEN
Solar/Wind Harmer
5.449
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.362
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
971611AH1-305 GEN
Solar/Wind Harmer
5.499
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.649
966391AG1-508 GEN
Solar/Wind Harmer
1.42
970169AG2-114 GEN
Solar/Wind Harmer
9.156
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
0.996
274877BISHOP HL;1U
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
1.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
970073AG2-061 GEN
Solar/Wind Harmer
3.032
276741O09 GEN1
Solar/Wind Harmer
0.321
970833AG2-524 GEN
Solar/Wind Harmer
10.003
970833AG2-524 GEN
Solar/Wind Harmer
6.669
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
276861AD2-134 GEN
Solar/Wind Harmer
0.162
276863AD2-134 GEN
Solar/Wind Harmer
0.162
971675AH1-338 GEN
Solar/Wind Harmer
3.544
971171AH1-044 GEN
Solar/Wind Harmer
18.173
971681AH1-341 GEN
Solar/Wind Harmer
14.63
972267AH1-718 GEN
Adder
5.423
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
274823ROCKFORD ;21
Adder
25.367
971411AH1-196 GEN
Solar/Wind Harmer
13.626
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
960591AF2-350 GEN
Solar/Wind Harmer
9.078
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
16.719
962761AG1-125 GEN
Solar/Wind Harmer
46.005
970149AG2-104 GEN
Solar/Wind Harmer
24.844
970155AG2-107 GEN
Solar/Wind Harmer
29.378
971687AH1-348 GEN
Solar/Wind Harmer
1.062
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
19.107
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
11.165
252510AF1-249 C
Solar/Wind Harmer
0.075
25196008MFTGT1
Adder
1.98
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.854
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
4.631
970773AG2-487 GEN
Solar/Wind Harmer
1.693
270273AD2-016 GEN
Solar/Wind Harmer
0.98
24728605AND G2
Adder
5.248
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.957
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
10.535
963741AG1-226 GEN
Solar/Wind Harmer
22.28
964901AG1-354 GEN
Solar/Wind Harmer
14.121
270594AE1-207 GEN
Solar/Wind Harmer
10.536
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
2.038
970825AG2-519 GEN
Solar/Wind Harmer
3.334
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.02
965911AG1-460 GEN
Solar/Wind Harmer
1.852
965651AG1-433 GEN
Solar/Wind Harmer
2.715
276621W2-048 GEN
Solar/Wind Harmer
0.463
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.546
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.866
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.925
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.831
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
970913AG2-568 GEN
Solar/Wind Harmer
8.731
971225AH1-072 GEN
Solar/Wind Harmer
2.121
971227AH1-073 GEN
Solar/Wind Harmer
2.121
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971073AG2-665 GEN
Solar/Wind Harmer
7.453
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.05
972043AH1-570 GEN
Solar/Wind Harmer
2.601
972045AH1-571 GEN
Solar/Wind Harmer
2.084
25183208HLCRTG
Solar/Wind Harmer
0.001
971125AH1-004 GEN
Solar/Wind Harmer
3.97
970107AG2-081 GEN
Solar/Wind Harmer
2.978
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
9.908
971587AH1-292 GEN
Solar/Wind Harmer
7.164
964571AG1-320 GEN
Solar/Wind Harmer
8.813
270269AC2-059
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
10.085
926881AC1-175 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.492
970291AG2-192 GEN
Solar/Wind Harmer
1.223
970291AG2-192 GEN
Solar/Wind Harmer
0.565
971613AH1-306 GEN
Solar/Wind Harmer
4.515
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.061
970883AG2-550 GEN
Solar/Wind Harmer
9.352
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971485AH1-239 GEN
Solar/Wind Harmer
7.452
964781AG1-341 GEN
Solar/Wind Harmer
9.873
966021AG1-471 GEN
Solar/Wind Harmer
5.029
270031AE2-169
Solar/Wind Harmer
5.121
270599AE1-208 GEN
Solar/Wind Harmer
8.535
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.358
270055AF2-134 C O1
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
27.326
971997AH1-543 GEN
Solar/Wind Harmer
4.779
253333AC1-068 GEN
Solar/Wind Harmer
0.01
276882AE2-255 GEN
Solar/Wind Harmer
1.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
276805AD2-038 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.321
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.477
274861TOP CROP ;1U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.28
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
27.26
959081AF2-199 GEN
Solar/Wind Harmer
9.087
962781AG1-127 GEN
Solar/Wind Harmer
8.648
971067AG2-660 GEN
Solar/Wind Harmer
3.029
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
970819AG2-516 GEN
Solar/Wind Harmer
10.9
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
19.462
276911AD2-131_GEN
Solar/Wind Harmer
1.282
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.431
276615X2-022 GEN
Solar/Wind Harmer
0.096
276838X2-022 GEN2
Solar/Wind Harmer
0.521
960611AF2-352 GEN
Solar/Wind Harmer
3.067
942111AE2-223 GEN
Solar/Wind Harmer
2.987
276645AC1-214 GEN1
Solar/Wind Harmer
0.358
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
22.743
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
958491AF2-143 GEN
Solar/Wind Harmer
13.642
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.467
958481AF2-142 GEN
Solar/Wind Harmer
13.633
962691AG1-118 GEN
Solar/Wind Harmer
27.261
971341AH1-150 GEN
Solar/Wind Harmer
18.173
971343AH1-151 GEN
Solar/Wind Harmer
18.173
938861AE1-114 GEN
Solar/Wind Harmer
5.149
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
276893AG1-478 C
Solar/Wind Harmer
0.606
274674JOLIET 9 ;6U
Adder
20.046
942221AE2-234 GEN
Solar/Wind Harmer
3.648
274683WAUKEGAN ;8U
Adder
27.432
971277AH1-098 GEN
Solar/Wind Harmer
3.633
274888KELLY CRK;1U
Solar/Wind Harmer
0.529
276776AD2-060 GEN
Solar/Wind Harmer
0.968
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
23777801MSM_W1-116
Solar/Wind Helper
0.101
970373AG2-245 GEN
Solar/Wind Harmer
16.807
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.72 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6225.55
MW Contribution:
13.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.774
957241AF2-018 GEN
Solar/Wind Harmer
7.761
270053AF1-130 C
Solar/Wind Harmer
31.012
270399AC1-101 GEN
Solar/Wind Harmer
7.341
270400AC1-102 GEN
Solar/Wind Harmer
7.341
970281AG2-184 GEN
Solar/Wind Harmer
33.013
971985AH1-537 GEN
Solar/Wind Harmer
28.037
941621AE2-160 GEN
Adder
5.08
962211AG1-066 GEN
Solar/Wind Harmer
3.683
971313AH1-133 GEN
Solar/Wind Harmer
8.881
972163AH1-664 GEN
Solar/Wind Harmer
14.676
972165AH1-665 GEN
Solar/Wind Harmer
11.741
339216AC1-074 GEN
Solar/Wind Harmer
2.418
25196108MFTGT2
Adder
2.204
25196108MFTGT2
Adder
2.047
3429211JKCT 2G
Adder
16.761
24289405MTG1
50/50
11.396
24318705GVG2
50/50
11.631
24722005FLATG5
50/50
2.774
24721905FLATG4
50/50
50.672
24686405CER G5
Adder
15.544
270330AC1-082 GEN2
Solar/Wind Harmer
0.849
270329AC1-082 GEN1
Solar/Wind Harmer
0.849
962771AG1-126 GEN
Solar/Wind Harmer
55.006
970153AG2-106 GEN
Solar/Wind Harmer
23.985
971191AH1-055 GEN
Solar/Wind Harmer
31.424
957541AF2-048 GEN
Solar/Wind Harmer
2.499
972103AH1-617 GEN
Solar/Wind Harmer
31.441
960911AF2-382 GEN
Solar/Wind Harmer
11.571
971461AH1-227 GEN
Solar/Wind Harmer
7.869
270367AC2-061_GEN
Solar/Wind Harmer
4.734
270186AC1-089 GEN
Solar/Wind Harmer
9.096
970879AG2-548 GEN
Solar/Wind Harmer
11.766
972167AH1-666 GEN
Solar/Wind Harmer
11.731
252507AC2-088 GEN
Solar/Wind Harmer
2.611
958171AF2-111 GEN
Solar/Wind Harmer
36.196
339243AC2-075 GEN1
Solar/Wind Harmer
0.655
252519AF1-045_GEN
Solar/Wind Harmer
5.251
25196408WSDLE3
Adder
12.643
25196308WSDLE2
Adder
12.533
25196208WSDLE1
Adder
12.501
25196708WSDLE6
Adder
12.47
25196508WSDLE4
Adder
12.156
24734705WLF1G3
Adder
8.239
24734805WLF1G4
Adder
8.239
24734905WLF1G5
Adder
8.239
253433AC1-085 GEN1
Solar/Wind Harmer
7.58
253432AC1-085 GEN2
Solar/Wind Harmer
0.381
270340AC2-060 GEN
Solar/Wind Harmer
4.299
253406AD2-031_GEN
Solar/Wind Harmer
1.814
270263AC1-001 GEN
Solar/Wind Harmer
1.479
270444AC2-157 GEN1
Solar/Wind Harmer
7.893
270445AC2-157 GEN2
Solar/Wind Harmer
7.893
270291AC1-194 GEN
Solar/Wind Harmer
7.194
24735105WLF2G1
Adder
8.122
270356AE2-297 GEN
Solar/Wind Harmer
6.397
971061AG2-657 GEN
Solar/Wind Harmer
12.414
253372AE2-315 SEC3
Adder
2.597
253372AE2-315 SEC3
Adder
2.597
25306009OHH W.
Adder
3.946
970289AG2-191 GEN
Solar/Wind Harmer
2.589
963841AG1-237 GEN
Solar/Wind Harmer
14.866
971029AG2-637 GEN
Solar/Wind Harmer
20.401
24386405FR-21G C
Solar/Wind Harmer
5.837
24387005FR-3G C
Solar/Wind Harmer
5.368
270543AE2-219 C
Solar/Wind Harmer
13.544
946581AF1-322 GEN
Solar/Wind Harmer
13.818
24691005MDL-2G C
Solar/Wind Harmer
4.994
945581AF1-223 GEN
Solar/Wind Harmer
6.119
247536S-71 GEN
Solar/Wind Harmer
5.458
964611AG1-324 GEN
Solar/Wind Harmer
5.25
270432AC2-029 GEN
Solar/Wind Harmer
9.42
944221AF1-090 GEN
Solar/Wind Harmer
14.705
961761AG1-017 GEN
Solar/Wind Harmer
0.575
24729505KEY G4
Adder
8.64
274775LINCOLN ;6U
Adder
11.119
274776LINCOLN ;7U
Adder
11.119
274777LINCOLN ;8U
Adder
11.119
274744AC1-111 GEN8
Adder
7.358
274746AC1-111 G10
Adder
7.358
972267AH1-718 GEN
Adder
5.481
274731ELWOOD EC;2P
Adder
21.634
274733ELWOOD EC;3P
Adder
21.634
274735ELWOOD EC;4P
Adder
21.634
274728ELWOOD EC;5P
Adder
21.634
274823ROCKFORD ;21
Adder
25.64
972228AH1-698 GEN2
Adder
4.874
972227AH1-698 GEN1
Adder
3.432
23750501ELLIOTTS
Solar/Wind Helper
0.784
23652301WDPWR_K20
Solar/Wind Helper
0.167
23750701CROSSCHOOL
Solar/Wind Helper
1.42
238118U2-030_1
Solar/Wind Helper
0.341
203955AF1-039 C O1
Solar/Wind Helper
0.43
20089126CSLMN_L13
Solar/Wind Helper
0.68
20089226LOOKOUT
Solar/Wind Helper
0.678
241997AF1-093 GEN
Solar/Wind Helper
0.278
241985AE1-237 GEN
Solar/Wind Helper
0.27
241982AE2-343 S C
Solar/Wind Helper
0.243
20088926STNY CRK
Solar/Wind Helper
0.922
203940AF1-140 C
Solar/Wind Helper
0.444
20094526CT_V3-030
Solar/Wind Helper
0.527
20088626ARWF_N39
Solar/Wind Helper
1.354
203846AF2-130 C
Solar/Wind Helper
0.494
20334926Z1-069 C
Solar/Wind Helper
1.481
200917MEHOOPANY_G
Solar/Wind Helper
2.413
209067AE2-060 GEN
Solar/Wind Helper
0.091
959431AF2-234 GEN
Solar/Wind Helper
0.993
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
959421AF2-233 GEN
Solar/Wind Helper
0.497
209054AE2-059 GEN
Solar/Wind Helper
0.09
209027LOR2_Q27
Solar/Wind Helper
1.157
212266LOR1
Solar/Wind Helper
0.337
209029WAYMART-WD
Solar/Wind Helper
0.93
961261AF2-417 GEN
Solar/Wind Helper
0.492
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.068
20676428JCR_X2-075
Solar/Wind Helper
0.073
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.172
20675528CPH_W2-050
Solar/Wind Helper
0.121
20720628TIN_W1-124
Solar/Wind Helper
0.202
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.111
20715028HAN_X4-015
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.06
959381AF2-229 GEN
Solar/Wind Helper
0.361
20390526W1-045 C
Solar/Wind Helper
0.355
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.08
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.042
228728W1-130C
Solar/Wind Helper
0.056
230434AG1-499 GEN
Solar/Wind Helper
0.24
232432Z2-076 GEN
Solar/Wind Helper
0.069
233901CHERRYDALE C
Solar/Wind Helper
0.239
233940AF2-379 C
Solar/Wind Helper
0.064
205956AE1-196_GEN
Solar/Wind Helper
0.52
205943AE1-185 GEN
Solar/Wind Helper
0.52
233915AB1-141 GEN
Solar/Wind Helper
0.515
205917AD1-020 ES
Solar/Wind Helper
0.366
237025AB1-124 C
Solar/Wind Helper
0.145
237030AB1-096 C
Solar/Wind Helper
0.059
24289405MTG1
50/50
11.396
243186AF1-051 GEN
50/50
12.548
24318705GVG2
50/50
11.631
24721805FLATG3
50/50
2.774
972203AH1-686 GEN
Adder
4.442
24723205RIVRG3
Adder
36.155
24686505CER G6
Adder
15.668
270331AC1-082 GEN3
Solar/Wind Harmer
0.851
944971AF1-162 GEN
Solar/Wind Harmer
12.224
960001AF2-291 GEN
Solar/Wind Harmer
5.265
971403AH1-188 GEN
Solar/Wind Harmer
24.159
962761AG1-125 GEN
Solar/Wind Harmer
55.006
970149AG2-104 GEN
Solar/Wind Harmer
33.966
970155AG2-107 GEN
Solar/Wind Harmer
23.985
971687AH1-348 GEN
Solar/Wind Harmer
1.536
24728305BUCHG2
Adder
6.863
970091AG2-072 GEN
Adder
114.157
971073AG2-665 GEN
Solar/Wind Harmer
1.71
945681AF1-233 GEN
Solar/Wind Harmer
27.651
339221AD2-048_GEN
Solar/Wind Harmer
2.223
25196808ZIMRHP
Adder
109.659
252516AE2-318_GEN
Solar/Wind Harmer
14.428
252510AF1-249 C
Solar/Wind Harmer
0.6
25196008MFTGT1
Adder
1.999
943111AE2-339 GEN
Solar/Wind Harmer
1.269
25194608D.CRK4
Adder
2.359
3429241JKCT 3G
Adder
16.981
3429421JKCT 10G
Adder
11.925
253316AC1-085 GEN3
Solar/Wind Harmer
11.942
946171AF1-282 GEN
Solar/Wind Harmer
14.264
339211AE2-254 GEN
Solar/Wind Harmer
2.136
24735205WLF2G2
Adder
8.122
253398AE2-221_GEN2
Solar/Wind Harmer
6.388
270222AC2-111 GEN
Solar/Wind Harmer
6.219
944031AF1-071 GEN
Solar/Wind Harmer
1.399
970653AG2-424 GEN
Solar/Wind Harmer
6.706
270273AD2-016 GEN
Solar/Wind Harmer
3.685
24728605AND G2
Adder
5.301
339241AF1-083 GEN
Solar/Wind Harmer
2.292
942081AE2-220 GEN
Solar/Wind Harmer
8.785
270209AC1-174_GEN
Solar/Wind Harmer
5.591
270437AC2-090 C
Solar/Wind Harmer
7.667
270239V3-007_GEN1
Solar/Wind Harmer
2.364
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
276903AD2-071 C
Solar/Wind Harmer
13.662
963741AG1-226 GEN
Solar/Wind Harmer
61.351
964901AG1-354 GEN
Solar/Wind Harmer
20.45
270594AE1-207 GEN
Solar/Wind Harmer
18.503
270032AE2-172
Solar/Wind Harmer
6.337
270005AE1-210 C O1
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
2.854
25326309TAIT D
Adder
1.488
24385905FR-11G C
Solar/Wind Harmer
11.279
24386605FR-22G C
Solar/Wind Harmer
5.837
25196008MFTGT1
Adder
1.936
25194608D.CRK4
Adder
2.359
252524AE2-267 GEN
Solar/Wind Harmer
2.256
25196608WSDLE5
Adder
12.281
3429391JKCT 9G
Adder
11.925
970093AG2-073 GEN
Solar/Wind Harmer
7.582
253317AC1-085 GEN4
Solar/Wind Harmer
11.942
946181AF1-283 GEN
Solar/Wind Harmer
18.543
253394AE2-221_GEN
Solar/Wind Harmer
6.388
970455AG2-298 GEN
Solar/Wind Harmer
4.914
970653AG2-424 GEN
Solar/Wind Harmer
0.97
339206AE1-143 GEN
Solar/Wind Harmer
2.962
972273AH1-721 GEN
Adder
115.342
24728705AND G3
Adder
11.088
24728505AND G1
Adder
5.301
970193AG2-126 GEN
Solar/Wind Harmer
20.616
24379505HDWTR1G C
Solar/Wind Harmer
10.862
270240V3-007_GEN2
Solar/Wind Harmer
8.498
253303V4-073 C
Solar/Wind Harmer
0.159
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
270346AE1-212 GEN
Solar/Wind Harmer
12.332
247642Z2-115 C
Solar/Wind Harmer
0.087
965461AG1-414 GEN
Solar/Wind Harmer
3.09
970289AG2-191 GEN
Solar/Wind Harmer
1.046
270004AE1-209 GEN
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
7.662
946031AF1-268 GEN
Solar/Wind Harmer
11.269
24386205FR-12G C
Solar/Wind Harmer
5.816
960071AF2-298 GEN
Solar/Wind Harmer
2.052
339255AE2-071 GEN
Solar/Wind Harmer
1.586
339250AF1-203 GEN
Solar/Wind Harmer
0.817
24690905MDL-1G C
Solar/Wind Harmer
10.842
970781AG2-491 GEN
Solar/Wind Harmer
13.505
962031AG1-047 GEN
Solar/Wind Harmer
4.061
274772LINCOLN ;3U
Adder
11.119
972259AH1-714 GEN
Adder
25.12
274760LEE CO EC;1U
Adder
12.246
274767LEE CO EC;8U
Adder
12.101
274729ELWOOD EC;1P
Adder
21.634
274730ELWOOD EC;6P
Adder
21.634
274734ELWOOD EC;8P
Adder
21.634
274736ELWOOD EC;9P
Adder
21.634
274682WAUKEGAN ;7U
Adder
23.647
237048AF1-022 C
Solar/Wind Helper
0.229
237046AF1-021 C
Solar/Wind Helper
0.396
235058AG1-386 C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
1.065
964991AG1-363 GEN
Solar/Wind Helper
4.388
202652Y1-033 WT C
Solar/Wind Helper
0.652
238127S14_GEN_2
Solar/Wind Helper
0.805
20092526R32
Solar/Wind Helper
1.303
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20303426NA_O38_P22
Solar/Wind Helper
1.11
203993AD2-133_GEN1
Solar/Wind Helper
1.142
203854AF2-039 C
Solar/Wind Helper
0.352
20398826ARMNA MT
Solar/Wind Helper
1.645
941421AE2-139 GEN
Solar/Wind Helper
2.555
209137AF2-361 C
Solar/Wind Helper
1.523
946731AF1-337 GEN
Solar/Wind Helper
0.496
212507AE2-042_GEN
Solar/Wind Helper
1.759
961341AF2-425 GEN
Solar/Wind Helper
0.495
961301AF2-421 GEN
Solar/Wind Helper
0.492
963151AG1-164 GEN
Solar/Wind Helper
0.492
211065PSPA IPP
Solar/Wind Helper
0.167
207518AF1-320_GEN
Solar/Wind Helper
1.705
20675728RH_W2-091
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.032
203975AE1-071-GEN
Solar/Wind Helper
2.659
207484AF2-139 C O1
Solar/Wind Helper
0.091
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
20674628WNG_W3-110
Solar/Wind Helper
0.097
20676328BVR_Y1-020
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.072
207439AE1-081 C O1
Solar/Wind Helper
0.02
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.485
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.172
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.083
20720528MAN_W1-024
Solar/Wind Helper
0.03
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219276PARKLANDSO C
Solar/Wind Helper
0.095
20715828PEM_W1-120
Solar/Wind Helper
0.101
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.12
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.057
228729W2-030 C
Solar/Wind Helper
0.116
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.52
232408W1-005 C
Solar/Wind Helper
0.52
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.52
233944AB2-135 GEN
Solar/Wind Helper
0.605
233918AB1-142 GEN
Solar/Wind Helper
0.515
235063AE1-101 C2
Solar/Wind Helper
1.456
205916AD1-020 GEN
Solar/Wind Helper
1.701
237001AB1-127_GEN
Solar/Wind Helper
0.386
23777901MDS_W4-102
Solar/Wind Helper
0.149
208835TUHI V3-051
Solar/Wind Helper
0.021
238175AF1-290_GEN
Solar/Wind Helper
0.125
957741AF2-068 GEN
Solar/Wind Harmer
8.369
24791305MDL-5G
Solar/Wind Harmer
3.256
945371AF1-202 GEN
Solar/Wind Harmer
9.414
958861AF2-177 GEN
Solar/Wind Harmer
14.687
274773LINCOLN ;4U
Adder
11.119
274774LINCOLN ;5U
Adder
11.119
274745AC1-111 GEN9
Adder
7.358
274761LEE CO EC;2U
Adder
12.246
274766LEE CO EC;7U
Adder
12.101
274732ELWOOD EC;7P
Adder
21.634
274822ROCKFORD ;11
Adder
25.827
274674JOLIET 9 ;6U
Adder
20.261
274682WAUKEGAN ;7U
Adder
11.397
238185AF2-356 C
Solar/Wind Helper
2.609
20089026BF_G21_K23
Solar/Wind Helper
0.538
238120AE2-309 GEN
Solar/Wind Helper
0.508
238126S14_GEN_1
Solar/Wind Helper
0.805
254303AC2-168 GEN
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.278
23751101LEADS_P59
Solar/Wind Helper
2.213
20084626FORWARD
Solar/Wind Helper
0.4
964201AG1-281 GEN
Solar/Wind Helper
0.541
20091526CHSTN_FL
Solar/Wind Helper
0.651
238109AE1-109 GEN2
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.142
203952AE2-129 C
Solar/Wind Helper
0.526
203855AF2-088 C
Solar/Wind Helper
0.169
209071AE2-133 GEN
Solar/Wind Helper
0.09
946691AF1-333 GEN
Solar/Wind Helper
0.496
946741AF1-338 GEN
Solar/Wind Helper
0.496
961421AF2-433 GEN
Solar/Wind Helper
0.495
957921AF2-086 GEN
Solar/Wind Helper
0.49
961331AF2-424 GEN
Solar/Wind Helper
0.495
208972BECR K09
Solar/Wind Helper
0.37
963161AG1-165 GEN
Solar/Wind Helper
0.492
203830AF1-094 GEN
Solar/Wind Helper
0.492
203979AG1-198 GEN
Solar/Wind Helper
0.295
316095T157 G97
Solar/Wind Helper
1.146
23583801GRNGAP
Solar/Wind Helper
4.253
211065PSPA IPP
Solar/Wind Helper
0.167
209116AE2-175 GEN
Solar/Wind Helper
1.956
961971AG1-040 GEN
Solar/Wind Helper
0.488
20674128FR_U2-059
Solar/Wind Helper
0.004
20671928W4-073
Solar/Wind Helper
0.097
207437AD2-070 GEN
Solar/Wind Helper
0.149
207511W3-106 GEN
Solar/Wind Helper
0.029
207510AF2-138 C
Solar/Wind Helper
0.088
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.349
20673728F2S_V4-070
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
219249CENTRALDIV C
Solar/Wind Helper
0.011
205941AD2-115 GEN
Solar/Wind Helper
0.528
20716928W4-060COL
Solar/Wind Helper
0.055
219612MATRIX C
Solar/Wind Helper
0.025
207454AA2-184 E
Solar/Wind Helper
0.33
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.005
20715728PEM_W1-119
Solar/Wind Helper
0.101
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.12
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.524
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233950AC2-186 GEN
Solar/Wind Helper
0.119
232434Z2-077 GEN
Solar/Wind Helper
0.13
233923SMA
Solar/Wind Helper
0.772
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.52
232417X3-008 C
Solar/Wind Helper
0.239
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.442
233987AB2-037 GEN
Solar/Wind Helper
2.403
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
233935AB2-179 C
Solar/Wind Helper
1.3
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
208835TUHI V3-051
Solar/Wind Helper
0.021
23777801MSM_W1-116
Solar/Wind Helper
0.099
243186AF1-051 GEN
50/50
12.548
24721705FLATG2
50/50
41.198
24723005RIVRG1
Adder
36.155
24723105RIVRG2
Adder
36.155
927014AC1-188 GEN
Solar/Wind Harmer
2.499
970913AG2-568 GEN
Solar/Wind Harmer
10.718
971225AH1-072 GEN
Solar/Wind Harmer
3.068
971227AH1-073 GEN
Solar/Wind Harmer
3.068
24728205BUCHG1
Adder
6.863
962581AG1-107 GEN
Solar/Wind Harmer
7.459
961491AF2-440 GEN
Solar/Wind Harmer
3.1
971073AG2-665 GEN
Solar/Wind Harmer
11.766
970879AG2-548 GEN
Solar/Wind Harmer
1.71
252509AD1-136 GEN
Solar/Wind Harmer
0.373
972043AH1-570 GEN
Solar/Wind Harmer
3.62
972045AH1-571 GEN
Solar/Wind Harmer
2.896
25183208HLCRTG
Solar/Wind Harmer
8.737
971125AH1-004 GEN
Solar/Wind Harmer
5.746
970107AG2-081 GEN
Solar/Wind Harmer
4.31
25194408D.CRK1
Adder
10.853
25194508D.CRK3
Adder
2.029
942891AE2-308 GEN
Solar/Wind Harmer
14.341
253415AE1-040 GEN
Solar/Wind Harmer
1.586
964571AG1-320 GEN
Solar/Wind Harmer
11.455
270269AC2-059
Solar/Wind Harmer
12.928
24728805RICHG1
Adder
5.238
24728905RICHG2
Adder
5.238
945391AF1-204 GEN
Solar/Wind Harmer
19.154
926881AC1-175 GEN
Solar/Wind Harmer
7.667
253370AE2-315 SEC1
Adder
2.746
270383AD1-128 GEN
Solar/Wind Harmer
8.356
339231AF1-038_GEN
Solar/Wind Harmer
2.483
24725505WLD G2 C
Solar/Wind Harmer
5.437
24699105WLD G1 C
Solar/Wind Harmer
5.374
339236AF1-050_GEN
Solar/Wind Harmer
2.477
970241AG2-163 GEN
Solar/Wind Harmer
34.084
970291AG2-192 GEN
Solar/Wind Harmer
1.771
970291AG2-192 GEN
Solar/Wind Harmer
0.57
253349AC2-067 GEN
Solar/Wind Harmer
2.769
253400AC2-068 GEN
Solar/Wind Harmer
1.114
25322209TAIT E
Adder
13.248
25322209TAIT E
Adder
12.95
24387305FR-4G C
Solar/Wind Harmer
6.894
966841AG1-555 GEN
Solar/Wind Harmer
3.407
970883AG2-550 GEN
Solar/Wind Harmer
13.544
970885AG2-551 GEN
Solar/Wind Harmer
3.15
270180AB1-006 GEN1
Solar/Wind Harmer
9.713
24697605MDL-3G C
Solar/Wind Harmer
4.978
24755605MDL-5G
Solar/Wind Harmer
3.256
24697905MDL-4G C
Solar/Wind Harmer
3.099
270181AB1-006 GEN2
Solar/Wind Harmer
0.966
971485AH1-239 GEN
Solar/Wind Harmer
10.793
964781AG1-341 GEN
Solar/Wind Harmer
14.3
966021AG1-471 GEN
Solar/Wind Harmer
7.284
270031AE2-169
Solar/Wind Harmer
10.99
270599AE1-208 GEN
Solar/Wind Harmer
10.99
945421AF1-207 GEN
Solar/Wind Harmer
18.926
957841AF2-078 GEN
Solar/Wind Harmer
8.147
25326109MON D
Adder
1.772
964611AG1-324 GEN
Solar/Wind Harmer
0.704
247621Y3-024
Adder
0.324
270201AC2-176 GEN
Solar/Wind Harmer
6.903
274770LINCOLN ;1U
Adder
11.119
274771LINCOLN ;2U
Adder
11.119
274696ROCKY RD ;4P
Adder
15.001
274695ROCKY RD ;2P
Adder
14.655
274693ROCKY RD ;1P
Adder
14.51
274764LEE CO EC;5U
Adder
12.274
274765LEE CO EC;6U
Adder
12.274
274762LEE CO EC;3U
Adder
12.246
274763LEE CO EC;4U
Adder
12.13
274697ROCKY RD ;3P
Adder
3.981
274674JOLIET 9 ;6U
Adder
20.261
972235AH1-702 GEN1
Adder
3.317
972236AH1-702 GEN2
Adder
2.884
23585401KL_K28_T16
Solar/Wind Helper
1.522
237043AE2-125 C
Solar/Wind Helper
0.207
23751201ROTHROCK
Solar/Wind Helper
0.874
235054AD2-180 GEN
Solar/Wind Helper
2.021
238117U2-030
Solar/Wind Helper
0.341
235531U2-073 GEN
Solar/Wind Helper
3.241
962101AG1-054 GEN
Solar/Wind Helper
0.711
254304AE2-114 C
Solar/Wind Helper
0.238
254305AE2-115 C
Solar/Wind Helper
0.238
20083426SW_E13_K22
Solar/Wind Helper
0.063
241967AE2-285_GEN
Solar/Wind Helper
0.691
241801AE1-079 GEN
Solar/Wind Helper
0.27
946071AF1-272 GEN
Solar/Wind Helper
3.032
20088826HIGHLAND
Solar/Wind Helper
1.005
203961AE2-224 GEN
Solar/Wind Helper
2.695
203818AF1-086 GEN
Solar/Wind Helper
1.876
203853AF1-134 C O1
Solar/Wind Helper
0.53
946381AF1-302 GEN
Solar/Wind Helper
0.245
203946AE2-131 C
Solar/Wind Helper
0.526
203954AE2-126 C
Solar/Wind Helper
0.519
940863AE2-074 GEN
Solar/Wind Helper
0.501
203804AE2-113_GEN
Solar/Wind Helper
1.916
946751AF1-339 GEN
Solar/Wind Helper
0.496
961431AF2-434 GEN
Solar/Wind Helper
0.495
316097T157 G90
Solar/Wind Helper
1.146
203835AF1-098 GEN
Solar/Wind Helper
1.948
207471AF2-354 C
Solar/Wind Helper
0.183
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.054
20674328GAR_V4-001
Solar/Wind Helper
0.024
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.15
20714828MDF_W3-079
Solar/Wind Helper
0.138
207459AE1-142 C O1
Solar/Wind Helper
0.307
20720828JCB_W4-025
Solar/Wind Helper
0.067
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.084
219304NAMERICA C
Solar/Wind Helper
0.138
219906AC1-017 C
Solar/Wind Helper
0.044
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.157
219904AC1-010 C
Solar/Wind Helper
0.063
228754AB1-001 C
Solar/Wind Helper
0.027
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.015
233952AC2-187 GEN
Solar/Wind Helper
0.239
233954AC2-188 GEN
Solar/Wind Helper
0.239
233994AC2-023 GEN
Solar/Wind Helper
0.986
232410W1-006 C
Solar/Wind Helper
0.52
232428Y3-058 C
Solar/Wind Helper
0.347
234015AF2-250 C
Solar/Wind Helper
0.039
233946AB2-136 GEN
Solar/Wind Helper
0.583
234036AF2-325 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.368
233930AB2-032 GEN
Solar/Wind Helper
0.39
232436AB1-176 C
Solar/Wind Helper
0.046
235062AE1-101 C1
Solar/Wind Helper
1.456
237080AD1-060 GEN
Solar/Wind Helper
0.295
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.235
237006AB1-125 GEN
Solar/Wind Helper
0.109
223401AF1-299 GEN
Solar/Wind Helper
0.336
223402AF1-300 C
Solar/Wind Helper
0.336
23779801AA1-109
Solar/Wind Helper
0.167
238169AE2-226 GEN1
Solar/Wind Helper
0.55
238170AE2-226 GEN2
Solar/Wind Helper
0.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
171.353
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.863
NYPJM->LTFIMP_NY
CLTF
6.23
LGEELTFEXP_LGEE->PJM
CLTF
9.895
MECLTFEXP_MEC->PJM
CLTF
22.066
SIGELTFEXP_SIGE->PJM
CLTF
0.733
CPLELTFEXP_CPLE->PJM
CLTF
6.636
CBM West 2LTFEXP_CBM-W2->PJM
CBM
174.171
LAGNLTFEXP_LAGN->PJM
CLTF
25.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.459
TVALTFEXP_TVA->PJM
CLTF
12.705
WECLTFEXP_WEC->PJM
CLTF
5.031
AG2-052LTFEXP_AG2-052->PJM
LTF
0.308
AH1-155LTFEXP_AH1-155->PJM
LTF
0.462

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.96 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6183.32
MW Contribution:
10.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
12.684
24722005FLATG5
50/50
3.326
24721905FLATG4
50/50
60.751
24318705GVG2
50/50
13.247
962771AG1-126 GEN
Solar/Wind Harmer
91.718
970153AG2-106 GEN
Solar/Wind Harmer
39.993
24686405CER G5
Adder
15.983
270330AC1-082 GEN2
Solar/Wind Harmer
0.845
270329AC1-082 GEN1
Solar/Wind Harmer
0.845
960911AF2-382 GEN
Solar/Wind Harmer
12.012
972103AH1-617 GEN
Solar/Wind Harmer
30.905
971461AH1-227 GEN
Solar/Wind Harmer
7.89
971191AH1-055 GEN
Solar/Wind Harmer
28.586
270346AE1-212 GEN
Solar/Wind Harmer
13.435
943031AE2-326 GEN
Solar/Wind Harmer
5.264
958121AF2-106 GEN
Solar/Wind Harmer
6.036
957541AF2-048 GEN
Solar/Wind Harmer
2.104
972273AH1-721 GEN
Adder
96.087
270030AE2-140 GEN
Solar/Wind Harmer
23
970093AG2-073 GEN
Solar/Wind Harmer
5.967
339206AE1-143 GEN
Solar/Wind Harmer
2.39
970879AG2-548 GEN
Solar/Wind Harmer
8.927
339255AE2-071 GEN
Solar/Wind Harmer
1.308
339250AF1-203 GEN
Solar/Wind Harmer
0.673
970653AG2-424 GEN
Solar/Wind Harmer
0.771
970455AG2-298 GEN
Solar/Wind Harmer
3.861
3429391JKCT 9G
Adder
9.153
270186AC1-089 GEN
Solar/Wind Harmer
6.641
339243AC2-075 GEN1
Solar/Wind Harmer
0.489
270367AC2-061_GEN
Solar/Wind Harmer
3.424
972167AH1-666 GEN
Solar/Wind Harmer
8.599
958171AF2-111 GEN
Solar/Wind Harmer
25.759
270018AE2-047 C O1
Solar/Wind Harmer
1.267
252507AC2-088 GEN
Solar/Wind Harmer
1.823
25196008MFTGT1
Adder
1.357
970193AG2-126 GEN
Solar/Wind Harmer
14.771
252519AF1-045_GEN
Solar/Wind Harmer
3.559
25194608D.CRK4
Adder
1.596
252524AE2-267 GEN
Solar/Wind Harmer
1.519
25196608WSDLE5
Adder
8.266
942481AE2-261 GEN
Solar/Wind Harmer
28.724
24728705AND G3
Adder
7.705
24728505AND G1
Adder
3.684
957381AF2-032 GEN
Solar/Wind Harmer
1.919
962751AG1-124 GEN
Solar/Wind Harmer
8.593
276785W4-005 GEN1
Solar/Wind Harmer
2.856
971993AH1-541 GEN
Solar/Wind Harmer
8.726
24386205FR-12G C
Solar/Wind Harmer
4.023
965091AG1-374 GEN
Solar/Wind Harmer
27.739
959611AF2-252 GEN
Solar/Wind Harmer
2.15
24690905MDL-1G C
Solar/Wind Harmer
7.42
970781AG2-491 GEN
Solar/Wind Harmer
9.243
274760LEE CO EC;1U
Adder
8.393
274767LEE CO EC;8U
Adder
8.294
274682WAUKEGAN ;7U
Adder
15.93
274729ELWOOD EC;1P
Adder
14.442
274730ELWOOD EC;6P
Adder
14.442
274734ELWOOD EC;8P
Adder
14.442
274736ELWOOD EC;9P
Adder
14.442
237048AF1-022 C
Solar/Wind Helper
0.181
237046AF1-021 C
Solar/Wind Helper
0.315
235058AG1-386 C
Solar/Wind Helper
0.425
202652Y1-033 WT C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
0.816
964991AG1-363 GEN
Solar/Wind Helper
3.339
24289405MTG1
50/50
12.684
24721805FLATG3
50/50
3.326
243186AF1-051 GEN
50/50
14.291
24318705GVG2
50/50
13.247
962761AG1-125 GEN
Solar/Wind Harmer
91.718
970149AG2-104 GEN
Solar/Wind Harmer
56.636
970155AG2-107 GEN
Solar/Wind Harmer
39.993
24723205RIVRG3
Adder
37.759
972203AH1-686 GEN
Adder
4.539
24686505CER G6
Adder
16.11
944971AF1-162 GEN
Solar/Wind Harmer
12.651
971403AH1-188 GEN
Solar/Wind Harmer
25.286
270331AC1-082 GEN3
Solar/Wind Harmer
0.847
960001AF2-291 GEN
Solar/Wind Harmer
5.171
24728305BUCHG2
Adder
7.18
971687AH1-348 GEN
Solar/Wind Harmer
1.537
24735205WLF2G2
Adder
8.13
270336AE1-100 GEN
Solar/Wind Harmer
2.029
970091AG2-072 GEN
Adder
90.254
943811AF1-049 GEN
Solar/Wind Harmer
4.254
24721705FLATG2
50/50
49.394
243186AF1-051 GEN
50/50
14.291
24723005RIVRG1
Adder
37.759
24723105RIVRG2
Adder
37.759
970913AG2-568 GEN
Solar/Wind Harmer
11.514
24728205BUCHG1
Adder
7.18
971225AH1-072 GEN
Solar/Wind Harmer
3.076
971227AH1-073 GEN
Solar/Wind Harmer
3.076
270214AC2-123 GEN
Solar/Wind Harmer
3.345
971277AH1-098 GEN
Solar/Wind Harmer
5.707
270583AD2-179 GEN
Solar/Wind Harmer
13.318
927014AC1-188 GEN
Solar/Wind Harmer
2.104
966021AG1-471 GEN
Solar/Wind Harmer
6.141
339231AF1-038_GEN
Solar/Wind Harmer
2.061
971485AH1-239 GEN
Solar/Wind Harmer
9.077
942891AE2-308 GEN
Solar/Wind Harmer
11.161
971073AG2-665 GEN
Solar/Wind Harmer
8.927
970879AG2-548 GEN
Solar/Wind Harmer
1.298
339236AF1-050_GEN
Solar/Wind Harmer
2.021
964781AG1-341 GEN
Solar/Wind Harmer
11.789
964571AG1-320 GEN
Solar/Wind Harmer
8.983
972043AH1-570 GEN
Solar/Wind Harmer
2.731
972045AH1-571 GEN
Solar/Wind Harmer
2.185
971125AH1-004 GEN
Solar/Wind Harmer
4.363
970107AG2-081 GEN
Solar/Wind Harmer
3.272
962581AG1-107 GEN
Solar/Wind Harmer
5.294
961491AF2-440 GEN
Solar/Wind Harmer
2.2
252509AD1-136 GEN
Solar/Wind Harmer
0.26
945391AF1-204 GEN
Solar/Wind Harmer
13.723
25183208HLCRTG
Solar/Wind Harmer
5.886
25194408D.CRK1
Adder
7.34
25194508D.CRK3
Adder
1.372
276916AD2-100_GEN
Solar/Wind Harmer
20.233
276911AD2-131_GEN
Solar/Wind Harmer
4.089
970241AG2-163 GEN
Solar/Wind Harmer
23.902
276615X2-022 GEN
Solar/Wind Harmer
1.861
276838X2-022 GEN2
Solar/Wind Harmer
0.221
274880W4-005 GEN4
Solar/Wind Harmer
2.856
276174W4-005 GEN2
Solar/Wind Harmer
2.856
24387305FR-4G C
Solar/Wind Harmer
4.769
966841AG1-555 GEN
Solar/Wind Harmer
2.357
960611AF2-352 GEN
Solar/Wind Harmer
2.15
270180AB1-006 GEN1
Solar/Wind Harmer
6.648
24697605MDL-3G C
Solar/Wind Harmer
3.407
24755605MDL-5G
Solar/Wind Harmer
2.228
24697905MDL-4G C
Solar/Wind Harmer
2.121
270181AB1-006 GEN2
Solar/Wind Harmer
0.661
942111AE2-223 GEN
Solar/Wind Harmer
7.529
24728805RICHG1
Adder
3.447
24728905RICHG2
Adder
3.447
274764LEE CO EC;5U
Adder
8.413
274765LEE CO EC;6U
Adder
8.413
274762LEE CO EC;3U
Adder
8.393
274763LEE CO EC;4U
Adder
8.314
972235AH1-702 GEN1
Adder
2.262
972236AH1-702 GEN2
Adder
1.967
274683WAUKEGAN ;8U
Adder
18.687
274683WAUKEGAN ;8U
Adder
15.753
274696ROCKY RD ;4P
Adder
10.103
274695ROCKY RD ;2P
Adder
9.87
274693ROCKY RD ;1P
Adder
9.773
274697ROCKY RD ;3P
Adder
2.681
274674JOLIET 9 ;6U
Adder
13.524
237043AE2-125 C
Solar/Wind Helper
0.166
254304AE2-114 C
Solar/Wind Helper
0.201
254305AE2-115 C
Solar/Wind Helper
0.201
962101AG1-054 GEN
Solar/Wind Helper
0.598
241967AE2-285_GEN
Solar/Wind Helper
0.586
241801AE1-079 GEN
Solar/Wind Helper
0.229
23585401KL_K28_T16
Solar/Wind Helper
1.176
23751201ROTHROCK
Solar/Wind Helper
0.671
235054AD2-180 GEN
Solar/Wind Helper
1.553
238117U2-030
Solar/Wind Helper
0.261
946071AF1-272 GEN
Solar/Wind Helper
2.433
20083426SW_E13_K22
Solar/Wind Helper
0.05
945421AF1-207 GEN
Solar/Wind Harmer
3.217
339211AE2-254 GEN
Solar/Wind Harmer
1.701
339241AF1-083 GEN
Solar/Wind Harmer
1.857
971073AG2-665 GEN
Solar/Wind Harmer
1.298
964901AG1-354 GEN
Solar/Wind Harmer
16.708
3429241JKCT 3G
Adder
13.15
970653AG2-424 GEN
Solar/Wind Harmer
5.33
3429421JKCT 10G
Adder
9.153
943111AE2-339 GEN
Solar/Wind Harmer
0.965
339221AD2-048_GEN
Solar/Wind Harmer
1.667
945681AF1-233 GEN
Solar/Wind Harmer
20.299
25196008MFTGT1
Adder
1.401
25196808ZIMRHP
Adder
75.86
252516AE2-318_GEN
Solar/Wind Harmer
9.778
252510AF1-249 C
Solar/Wind Harmer
0.407
270173AC1-122 GEN
Solar/Wind Harmer
1.632
25194608D.CRK4
Adder
1.596
965911AG1-460 GEN
Solar/Wind Harmer
1.34
24728605AND G2
Adder
3.684
963741AG1-226 GEN
Solar/Wind Harmer
43.023
276621W2-048 GEN
Solar/Wind Harmer
5.925
276686W4-005 GEN3
Solar/Wind Harmer
2.856
24385905FR-11G C
Solar/Wind Harmer
7.803
24386605FR-22G C
Solar/Wind Harmer
4.038
24791305MDL-5G
Solar/Wind Harmer
2.228
270574AD1-017 GEN2
Solar/Wind Harmer
4.722
276655WTG1_EQ
Solar/Wind Harmer
8.017
276656WTG2_EQ
Solar/Wind Harmer
1.061
939741AE1-205 GEN
Solar/Wind Harmer
18.37
274761LEE CO EC;2U
Adder
8.393
274766LEE CO EC;7U
Adder
8.294
274822ROCKFORD ;11
Adder
17.595
274828WAUKEGAN ;BP
Adder
9.796
274682WAUKEGAN ;7U
Adder
15.93
274745AC1-111 GEN9
Adder
4.935
274732ELWOOD EC;7P
Adder
14.442
274674JOLIET 9 ;6U
Adder
13.524
274676JOLIET 29;8U
Adder
26.921
254303AC2-168 GEN
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.235
238185AF2-356 C
Solar/Wind Helper
2.008
20089026BF_G21_K23
Solar/Wind Helper
0.425
24721605FLATG1
50/50
3.326
957241AF2-018 GEN
Solar/Wind Harmer
8.033
270053AF1-130 C
Solar/Wind Harmer
32.096
270399AC1-101 GEN
Solar/Wind Harmer
7.582
270400AC1-102 GEN
Solar/Wind Harmer
7.582
941621AE2-160 GEN
Adder
5.453
971313AH1-133 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
32.451
971061AG2-657 GEN
Solar/Wind Harmer
13.518
24734705WLF1G3
Adder
8.32
24734805WLF1G4
Adder
8.32
24734905WLF1G5
Adder
8.32
962211AG1-066 GEN
Solar/Wind Harmer
3.487
966391AG1-508 GEN
Solar/Wind Harmer
4.969
24735105WLF2G1
Adder
8.13
971331AH1-145 GEN
Solar/Wind Harmer
12.844
971329AH1-144 GEN
Solar/Wind Harmer
8.204
971985AH1-537 GEN
Solar/Wind Harmer
23.127
971981AH1-535 GEN
Solar/Wind Harmer
12.746
270069AE2-166 C O1
Solar/Wind Harmer
10.572
3429211JKCT 2G
Adder
12.98
972163AH1-664 GEN
Solar/Wind Harmer
10.818
972165AH1-665 GEN
Solar/Wind Harmer
8.654
339216AC1-074 GEN
Solar/Wind Harmer
1.805
270444AC2-157 GEN1
Solar/Wind Harmer
5.93
270445AC2-157 GEN2
Solar/Wind Harmer
5.93
270291AC1-194 GEN
Solar/Wind Harmer
5.169
25196108MFTGT2
Adder
1.544
25196108MFTGT2
Adder
1.434
944221AF1-090 GEN
Solar/Wind Harmer
10.637
25196408WSDLE3
Adder
8.509
25196308WSDLE2
Adder
8.435
25196208WSDLE1
Adder
8.414
25196708WSDLE6
Adder
8.393
25196508WSDLE4
Adder
8.182
963841AG1-237 GEN
Solar/Wind Harmer
10.358
276763AC1-053 GEN1
Solar/Wind Harmer
3.74
276764AC1-053 GEN2
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
2.091
276848AB2-070 GEN3
Solar/Wind Harmer
2.091
276849AB2-070 GEN2
Solar/Wind Harmer
2.091
270356AE2-297 GEN
Solar/Wind Harmer
4.331
24386405FR-21G C
Solar/Wind Harmer
4.038
24387005FR-3G C
Solar/Wind Harmer
3.714
274853TWINGROVE;U1
Solar/Wind Harmer
6.662
274854TWINGROVE;U2
Solar/Wind Harmer
6.522
946581AF1-322 GEN
Solar/Wind Harmer
9.458
24691005MDL-2G C
Solar/Wind Harmer
3.418
270197AD1-017 GEN1
Solar/Wind Harmer
1.417
276726Z2-087_GEN
Solar/Wind Harmer
7.262
959341AF2-225 GEN
Solar/Wind Harmer
13.777
972267AH1-718 GEN
Adder
3.77
274823ROCKFORD ;21
Adder
17.467
274744AC1-111 GEN8
Adder
4.935
274746AC1-111 G10
Adder
4.935
274728ELWOOD EC;5P
Adder
14.442
274731ELWOOD EC;2P
Adder
14.442
274733ELWOOD EC;3P
Adder
14.442
274735ELWOOD EC;4P
Adder
14.442
274675JOLIET 29;7U
Adder
26.921
274675JOLIET 29;7U
Adder
15.118
23750501ELLIOTTS
Solar/Wind Helper
0.617
23652301WDPWR_K20
Solar/Wind Helper
0.134
241997AF1-093 GEN
Solar/Wind Helper
0.235
241985AE1-237 GEN
Solar/Wind Helper
0.229
241982AE2-343 S C
Solar/Wind Helper
0.206
203955AF1-039 C O1
Solar/Wind Helper
0.338
23750701CROSSCHOOL
Solar/Wind Helper
1.086
20089126CSLMN_L13
Solar/Wind Helper
0.537
20089226LOOKOUT
Solar/Wind Helper
0.536
238118U2-030_1
Solar/Wind Helper
0.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.561
NYPJM->LTFIMP_NY
CLTF
4.806
LGEELTFEXP_LGEE->PJM
CLTF
7.592
WECLTFEXP_WEC->PJM
CLTF
3.434
MECLTFEXP_MEC->PJM
CLTF
15.956
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CPLELTFEXP_CPLE->PJM
CLTF
7.6
CBM West 2LTFEXP_CBM-W2->PJM
CBM
138.522
LAGNLTFEXP_LAGN->PJM
CLTF
21.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.819
TVALTFEXP_TVA->PJM
CLTF
11.07
AG2-052LTFEXP_AG2-052->PJM
LTF
0.205
AH1-155LTFEXP_AH1-155->PJM
LTF
0.307

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4976.63
MW Contribution:
7.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
10.896
24318705GVG2
50/50
10.829
24722005FLATG5
50/50
2.475
24721905FLATG4
50/50
45.211
24686405CER G5
Adder
13.963
971191AH1-055 GEN
Solar/Wind Harmer
25.524
960911AF2-382 GEN
Solar/Wind Harmer
7.256
972103AH1-617 GEN
Solar/Wind Harmer
19.113
971461AH1-227 GEN
Solar/Wind Harmer
4.836
270346AE1-212 GEN
Solar/Wind Harmer
7.826
943031AE2-326 GEN
Solar/Wind Harmer
4.478
970879AG2-548 GEN
Solar/Wind Harmer
5.846
958121AF2-106 GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
6.527
972167AH1-666 GEN
Solar/Wind Harmer
6.143
972273AH1-721 GEN
Adder
91.222
3429391JKCT 9G
Adder
9.095
970455AG2-298 GEN
Solar/Wind Harmer
2.913
958171AF2-111 GEN
Solar/Wind Harmer
18.695
252507AC2-088 GEN
Solar/Wind Harmer
0.336
970653AG2-424 GEN
Solar/Wind Harmer
0.745
25196008MFTGT1
Adder
1.411
252519AF1-045_GEN
Solar/Wind Harmer
3.801
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.838
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.158
962771AG1-126 GEN
Solar/Wind Harmer
27.311
970153AG2-106 GEN
Solar/Wind Harmer
17.44
253394AE2-221_GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.239
24728705AND G3
Adder
7.833
24728505AND G1
Adder
3.745
24721605FLATG1
50/50
2.475
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
24.531
270399AC1-101 GEN
Solar/Wind Harmer
3.431
270400AC1-102 GEN
Solar/Wind Harmer
3.431
941621AE2-160 GEN
Adder
4.685
970281AG2-184 GEN
Solar/Wind Harmer
20.069
971313AH1-133 GEN
Solar/Wind Harmer
4.633
971061AG2-657 GEN
Solar/Wind Harmer
5.63
24734705WLF1G3
Adder
7.275
24734805WLF1G4
Adder
7.275
24734905WLF1G5
Adder
7.275
971985AH1-537 GEN
Solar/Wind Harmer
2.606
24735105WLF2G1
Adder
7.131
966391AG1-508 GEN
Solar/Wind Harmer
1.323
971331AH1-145 GEN
Solar/Wind Harmer
10.902
971329AH1-144 GEN
Solar/Wind Harmer
4.007
971981AH1-535 GEN
Solar/Wind Harmer
5.247
972163AH1-664 GEN
Solar/Wind Harmer
8.578
972165AH1-665 GEN
Solar/Wind Harmer
6.87
3429211JKCT 2G
Adder
12.836
339216AC1-074 GEN
Solar/Wind Harmer
0.202
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.606
25196108MFTGT2
Adder
1.492
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
9.098
25196308WSDLE2
Adder
9.019
25196208WSDLE1
Adder
8.997
25196708WSDLE6
Adder
8.974
25196508WSDLE4
Adder
8.748
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.692
270069AE2-166 C O1
Solar/Wind Harmer
6.22
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.926
963841AG1-237 GEN
Solar/Wind Harmer
2.866
24386405FR-21G C
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.257
276848AB2-070 GEN3
Solar/Wind Harmer
0.256
276849AB2-070 GEN2
Solar/Wind Harmer
0.257
970289AG2-191 GEN
Solar/Wind Harmer
1.233
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
243186AF1-051 GEN
50/50
11.683
24721705FLATG2
50/50
36.759
24723005RIVRG1
Adder
32.69
24723105RIVRG2
Adder
32.69
970913AG2-568 GEN
Solar/Wind Harmer
8.105
24728205BUCHG1
Adder
6.196
971225AH1-072 GEN
Solar/Wind Harmer
1.885
971227AH1-073 GEN
Solar/Wind Harmer
1.885
971277AH1-098 GEN
Solar/Wind Harmer
3.388
971073AG2-665 GEN
Solar/Wind Harmer
5.846
970879AG2-548 GEN
Solar/Wind Harmer
1.329
270583AD2-179 GEN
Solar/Wind Harmer
7.872
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942891AE2-308 GEN
Solar/Wind Harmer
7.677
972043AH1-570 GEN
Solar/Wind Harmer
1.99
972045AH1-571 GEN
Solar/Wind Harmer
1.594
971125AH1-004 GEN
Solar/Wind Harmer
3.042
970107AG2-081 GEN
Solar/Wind Harmer
2.281
966021AG1-471 GEN
Solar/Wind Harmer
4.034
252509AD1-136 GEN
Solar/Wind Harmer
0.037
971485AH1-239 GEN
Solar/Wind Harmer
5.968
964571AG1-320 GEN
Solar/Wind Harmer
6.787
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25183208HLCRTG
Solar/Wind Harmer
0
971587AH1-292 GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
7.827
25194508D.CRK3
Adder
1.463
945391AF1-204 GEN
Solar/Wind Harmer
7.253
24728805RICHG1
Adder
3.656
24728905RICHG2
Adder
3.656
970241AG2-163 GEN
Solar/Wind Harmer
3.886
276916AD2-100_GEN
Solar/Wind Harmer
13.944
276911AD2-131_GEN
Solar/Wind Harmer
0.919
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.068
276838X2-022 GEN2
Solar/Wind Harmer
0.37
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.743
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.844
970291AG2-192 GEN
Solar/Wind Harmer
0.389
971613AH1-306 GEN
Solar/Wind Harmer
3.113
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
970883AG2-550 GEN
Solar/Wind Harmer
6.406
970885AG2-551 GEN
Solar/Wind Harmer
2.135
942111AE2-223 GEN
Solar/Wind Harmer
2.08
270031AE2-169
Solar/Wind Harmer
3.483
270599AE1-208 GEN
Solar/Wind Harmer
5.804
276645AC1-214 GEN1
Solar/Wind Harmer
0.248
964611AG1-324 GEN
Solar/Wind Harmer
0.475
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.019
247621Y3-024
Adder
0.218
270201AC2-176 GEN
Solar/Wind Harmer
0
25322209TAIT E
Adder
8.794
25322209TAIT E
Adder
8.596
274764LEE CO EC;5U
Adder
8.405
274765LEE CO EC;6U
Adder
8.405
274762LEE CO EC;3U
Adder
8.386
274763LEE CO EC;4U
Adder
8.307
938861AE1-114 GEN
Solar/Wind Harmer
3.56
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.263
972236AH1-702 GEN2
Adder
1.968
971341AH1-150 GEN
Solar/Wind Harmer
12.516
971343AH1-151 GEN
Solar/Wind Harmer
12.516
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.353
962691AG1-118 GEN
Solar/Wind Harmer
18.68
274683WAUKEGAN ;8U
Adder
18.772
274683WAUKEGAN ;8U
Adder
15.824
274696ROCKY RD ;4P
Adder
10.15
274695ROCKY RD ;2P
Adder
9.916
274693ROCKY RD ;1P
Adder
9.818
274697ROCKY RD ;3P
Adder
2.694
958481AF2-142 GEN
Solar/Wind Harmer
9.318
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
15.453
276893AG1-478 C
Solar/Wind Harmer
0.412
274674JOLIET 9 ;6U
Adder
13.632
944541AF1-119 GEN
Solar/Wind Harmer
0.412
960971AF2-388 GEN
Solar/Wind Harmer
3.621
274888KELLY CRK;1U
Solar/Wind Harmer
0.359
276776AD2-060 GEN
Solar/Wind Harmer
0.657
958011AF2-095 GEN
Solar/Wind Harmer
8.864
24289405MTG1
50/50
10.896
243186AF1-051 GEN
50/50
11.683
24318705GVG2
50/50
10.829
24721805FLATG3
50/50
2.475
24723205RIVRG3
Adder
32.69
972203AH1-686 GEN
Adder
3.965
24686505CER G6
Adder
14.074
944971AF1-162 GEN
Solar/Wind Harmer
10.992
971403AH1-188 GEN
Solar/Wind Harmer
15.251
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
6.196
971687AH1-348 GEN
Solar/Wind Harmer
0.943
24735205WLF2G2
Adder
7.131
971073AG2-665 GEN
Solar/Wind Harmer
1.329
970091AG2-072 GEN
Adder
86.562
945681AF1-233 GEN
Solar/Wind Harmer
14.491
3429241JKCT 3G
Adder
13.004
3429421JKCT 10G
Adder
9.095
970653AG2-424 GEN
Solar/Wind Harmer
3.596
964901AG1-354 GEN
Solar/Wind Harmer
11.126
25196808ZIMRHP
Adder
79.991
25196008MFTGT1
Adder
1.457
252516AE2-318_GEN
Solar/Wind Harmer
8.161
252510AF1-249 C
Solar/Wind Harmer
0.055
25194608D.CRK4
Adder
1.702
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.045
962761AG1-125 GEN
Solar/Wind Harmer
27.311
970149AG2-104 GEN
Solar/Wind Harmer
14.748
970155AG2-107 GEN
Solar/Wind Harmer
17.44
253398AE2-221_GEN2
Solar/Wind Harmer
0
24728605AND G2
Adder
3.745
970773AG2-487 GEN
Solar/Wind Harmer
1.199
963741AG1-226 GEN
Solar/Wind Harmer
15.765
965911AG1-460 GEN
Solar/Wind Harmer
1.325
943811AF1-049 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.832
276621W2-048 GEN
Solar/Wind Harmer
0.329
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.31
270594AE1-207 GEN
Solar/Wind Harmer
7.264
270032AE2-172
Solar/Wind Harmer
4.324
270273AD2-016 GEN
Solar/Wind Harmer
0.662
270005AE1-210 C O1
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
2.292
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.961
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.933
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.248
276708O09 GEN2
Solar/Wind Harmer
0.223
970569AG2-363 GEN
Solar/Wind Harmer
18.869
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.386
274766LEE CO EC;7U
Adder
8.287
25326309TAIT D
Adder
0.988
945371AF1-202 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
7.523
939401AE1-172 GEN
Solar/Wind Harmer
4.684
274822ROCKFORD ;11
Adder
17.613
957471AF2-041 GEN
Solar/Wind Harmer
18.774
959081AF2-199 GEN
Solar/Wind Harmer
6.258
971067AG2-660 GEN
Solar/Wind Harmer
2.086
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.135
971997AH1-543 GEN
Solar/Wind Harmer
3.283
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.729
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.929
274828WAUKEGAN ;BP
Adder
9.84
274682WAUKEGAN ;7U
Adder
16.004
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.692
276691AA1-018 GEN1
Solar/Wind Harmer
1.009
274745AC1-111 GEN9
Adder
4.965
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.558
274674JOLIET 9 ;6U
Adder
13.632
965651AG1-433 GEN
Solar/Wind Harmer
1.811
274676JOLIET 29;8U
Adder
9.572
238185AF2-356 C
Solar/Wind Helper
1.975
970373AG2-245 GEN
Solar/Wind Harmer
5.443
971029AG2-637 GEN
Solar/Wind Harmer
9.69
274854TWINGROVE;U2
Solar/Wind Harmer
0
25306009OHH W.
Adder
2.654
253372AE2-315 SEC3
Adder
1.743
253372AE2-315 SEC3
Adder
1.743
270543AE2-219 C
Solar/Wind Harmer
4.484
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.721
247536S-71 GEN
Solar/Wind Harmer
0.254
971611AH1-305 GEN
Solar/Wind Harmer
3.778
946321AF1-296 GEN
Solar/Wind Harmer
3.554
274877BISHOP HL;1U
Solar/Wind Harmer
0.211
971609AH1-304 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
2.468
970169AG2-114 GEN
Solar/Wind Harmer
6.325
276741O09 GEN1
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.763
926823AC1-168 GEN
Solar/Wind Harmer
1.07
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.116
274856ECOGROVE ;U1
Solar/Wind Harmer
0.147
274823ROCKFORD ;21
Adder
17.485
971171AH1-044 GEN
Solar/Wind Harmer
12.516
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971675AH1-338 GEN
Solar/Wind Harmer
2.437
971411AH1-196 GEN
Solar/Wind Harmer
9.369
970073AG2-061 GEN
Solar/Wind Harmer
2.078
274744AC1-111 GEN8
Adder
4.965
274746AC1-111 G10
Adder
4.965
970833AG2-524 GEN
Solar/Wind Harmer
6.809
970833AG2-524 GEN
Solar/Wind Harmer
4.54
274728ELWOOD EC;5P
Adder
14.558
274731ELWOOD EC;2P
Adder
14.558
274733ELWOOD EC;3P
Adder
14.558
274735ELWOOD EC;4P
Adder
14.558
274675JOLIET 29;7U
Adder
27.142
960591AF2-350 GEN
Solar/Wind Harmer
6.155
23750501ELLIOTTS
Solar/Wind Helper
0.598
23652301WDPWR_K20
Solar/Wind Helper
0.127
270030AE2-140 GEN
Solar/Wind Harmer
13.518
942481AE2-261 GEN
Solar/Wind Harmer
19.808
957381AF2-032 GEN
Solar/Wind Harmer
1.5
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.022
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.714
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.48
270004AE1-209 GEN
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
4.865
965091AG1-374 GEN
Solar/Wind Harmer
19.301
946031AF1-268 GEN
Solar/Wind Harmer
6.123
959611AF2-252 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
970191AG2-125 GEN
Solar/Wind Harmer
1.638
965931AG1-462 GEN
Solar/Wind Harmer
16.203
971087AG2-675 GEN
Solar/Wind Harmer
3.389
274878BISHOP HL;2U
Solar/Wind Harmer
0.211
276782AC1-033 GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.45
970571AG2-364 GEN
Solar/Wind Harmer
12.579
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.386
274767LEE CO EC;8U
Adder
8.287
959091AF2-200 GEN
Solar/Wind Harmer
12.516
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
946671AF1-331 GEN
Solar/Wind Harmer
0.666
276868AE1-113 GEN
Solar/Wind Harmer
1.25
274879MINONK ;1U
Solar/Wind Harmer
0.261
274682WAUKEGAN ;7U
Adder
16.004
274862TOP CROP ;2U
Solar/Wind Harmer
0.839
943121AE2-341 GEN
Solar/Wind Harmer
10.39
943591AF1-030 GEN
Solar/Wind Harmer
6.91
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
14.558
274730ELWOOD EC;6P
Adder
14.558
274734ELWOOD EC;8P
Adder
14.558
274736ELWOOD EC;9P
Adder
14.558
970707AG2-453 GEN
Solar/Wind Harmer
20.15
274887GEN-1.85
Solar/Wind Harmer
0.16
276843GEN-1.7
Solar/Wind Harmer
0.199
276806AD2-047 C O1
Solar/Wind Harmer
3.488
237048AF1-022 C
Solar/Wind Helper
0.175
237046AF1-021 C
Solar/Wind Helper
0.301
235058AG1-386 C
Solar/Wind Helper
0.387
23562501BACKB
Solar/Wind Helper
0.811
970941AG2-585 GEN
Solar/Wind Harmer
3.385
23585401KL_K28_T16
Solar/Wind Helper
1.157
237043AE2-125 C
Solar/Wind Helper
0.157
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.531
CBM West 1LTFEXP_CBM-W1->PJM
CBM
115.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.783
NYPJM->LTFIMP_NY
CLTF
4.626
LGEELTFEXP_LGEE->PJM
CLTF
7.468
MECLTFEXP_MEC->PJM
CLTF
15.666
SIGELTFEXP_SIGE->PJM
CLTF
0.545
CPLELTFEXP_CPLE->PJM
CLTF
6.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.098
LAGNLTFEXP_LAGN->PJM
CLTF
19.698
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23
TVALTFEXP_TVA->PJM
CLTF
10.208
WECLTFEXP_WEC->PJM
CLTF
3.435
AG2-052LTFEXP_AG2-052->PJM
LTF
0.207
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.41 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5987.66
MW Contribution:
12.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
270330AC1-082 GEN2
Solar/Wind Harmer
0.862
270329AC1-082 GEN1
Solar/Wind Harmer
0.862
960911AF2-382 GEN
Solar/Wind Harmer
12.889
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
8.512
972103AH1-617 GEN
Solar/Wind Harmer
33.161
971191AH1-055 GEN
Solar/Wind Harmer
30.574
270346AE1-212 GEN
Solar/Wind Harmer
14.67
958121AF2-106 GEN
Solar/Wind Harmer
7.386
957541AF2-048 GEN
Solar/Wind Harmer
2.364
970879AG2-548 GEN
Solar/Wind Harmer
10.717
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
26.764
970093AG2-073 GEN
Solar/Wind Harmer
7.05
270186AC1-089 GEN
Solar/Wind Harmer
8.102
270367AC2-061_GEN
Solar/Wind Harmer
4.197
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
10.503
962751AG1-124 GEN
Solar/Wind Harmer
11.766
339206AE1-143 GEN
Solar/Wind Harmer
2.789
339243AC2-075 GEN1
Solar/Wind Harmer
0.591
970455AG2-298 GEN
Solar/Wind Harmer
4.537
970653AG2-424 GEN
Solar/Wind Harmer
0.902
339255AE2-071 GEN
Solar/Wind Harmer
1.514
339250AF1-203 GEN
Solar/Wind Harmer
0.779
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
11.956
24728205BUCHG1
Adder
7.739
270214AC2-123 GEN
Solar/Wind Harmer
3.869
971225AH1-072 GEN
Solar/Wind Harmer
3.319
971227AH1-073 GEN
Solar/Wind Harmer
3.319
971277AH1-098 GEN
Solar/Wind Harmer
6.62
270583AD2-179 GEN
Solar/Wind Harmer
16.289
927014AC1-188 GEN
Solar/Wind Harmer
2.364
971073AG2-665 GEN
Solar/Wind Harmer
10.717
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
13.25
339231AF1-038_GEN
Solar/Wind Harmer
2.384
972043AH1-570 GEN
Solar/Wind Harmer
3.285
972045AH1-571 GEN
Solar/Wind Harmer
2.628
971125AH1-004 GEN
Solar/Wind Harmer
5.238
970107AG2-081 GEN
Solar/Wind Harmer
3.929
966021AG1-471 GEN
Solar/Wind Harmer
7.071
971485AH1-239 GEN
Solar/Wind Harmer
10.457
962581AG1-107 GEN
Solar/Wind Harmer
6.569
961491AF2-440 GEN
Solar/Wind Harmer
2.73
339236AF1-050_GEN
Solar/Wind Harmer
2.347
964781AG1-341 GEN
Solar/Wind Harmer
13.643
964571AG1-320 GEN
Solar/Wind Harmer
10.544
252509AD1-136 GEN
Solar/Wind Harmer
0.325
25183208HLCRTG
Solar/Wind Harmer
7.535
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
16.433
942671AE2-283 GEN
Solar/Wind Harmer
5.701
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
253415AE1-040 GEN
Solar/Wind Harmer
1.308
276916AD2-100_GEN
Solar/Wind Harmer
24.22
276911AD2-131_GEN
Solar/Wind Harmer
4.895
970241AG2-163 GEN
Solar/Wind Harmer
28.803
276615X2-022 GEN
Solar/Wind Harmer
2.236
276838X2-022 GEN2
Solar/Wind Harmer
0.266
926881AC1-175 GEN
Solar/Wind Harmer
6.354
274880W4-005 GEN4
Solar/Wind Harmer
3.438
276174W4-005 GEN2
Solar/Wind Harmer
3.438
24387305FR-4G C
Solar/Wind Harmer
5.77
966841AG1-555 GEN
Solar/Wind Harmer
2.852
24725505WLD G2 C
Solar/Wind Harmer
4.513
24699105WLD G1 C
Solar/Wind Harmer
4.461
270383AD1-128 GEN
Solar/Wind Harmer
6.909
970291AG2-192 GEN
Solar/Wind Harmer
1.461
970291AG2-192 GEN
Solar/Wind Harmer
0.47
253370AE2-315 SEC1
Adder
2.225
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
247621Y3-024
Adder
0.264
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
274674JOLIET 9 ;6U
Adder
16.589
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
26.012
270331AC1-082 GEN3
Solar/Wind Harmer
0.864
960001AF2-291 GEN
Solar/Wind Harmer
5.313
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.658
24735205WLF2G2
Adder
8.97
270336AE1-100 GEN
Solar/Wind Harmer
2.369
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
339211AE2-254 GEN
Solar/Wind Harmer
1.998
3429241JKCT 3G
Adder
15.659
270173AC1-122 GEN
Solar/Wind Harmer
2.206
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
24.773
943111AE2-339 GEN
Solar/Wind Harmer
1.158
339221AD2-048_GEN
Solar/Wind Harmer
2.01
943811AF1-049 GEN
Solar/Wind Harmer
4.941
339241AF1-083 GEN
Solar/Wind Harmer
2.163
964901AG1-354 GEN
Solar/Wind Harmer
19.398
970653AG2-424 GEN
Solar/Wind Harmer
6.236
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
12.45
252510AF1-249 C
Solar/Wind Harmer
0.517
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
10.112
946171AF1-282 GEN
Solar/Wind Harmer
12.079
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
5.329
962761AG1-125 GEN
Solar/Wind Harmer
38.013
970149AG2-104 GEN
Solar/Wind Harmer
23.473
970155AG2-107 GEN
Solar/Wind Harmer
16.575
270574AD1-017 GEN2
Solar/Wind Harmer
5.994
316217AC1-145 GEN
Solar/Wind Harmer
2.791
316197AC1-042 GEN
Solar/Wind Harmer
2.116
3147312GRETNA
Solar/Wind Harmer
-0.003
270222AC2-111 GEN
Solar/Wind Harmer
5.217
944031AF1-071 GEN
Solar/Wind Harmer
1.174
963741AG1-226 GEN
Solar/Wind Harmer
51.846
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
7.12
942081AE2-220 GEN
Solar/Wind Harmer
7.281
270209AC1-174_GEN
Solar/Wind Harmer
4.633
270437AC2-090 C
Solar/Wind Harmer
6.354
270239V3-007_GEN1
Solar/Wind Harmer
1.959
276686W4-005 GEN3
Solar/Wind Harmer
3.438
24385905FR-11G C
Solar/Wind Harmer
9.442
24386605FR-22G C
Solar/Wind Harmer
4.886
276903AD2-071 C
Solar/Wind Harmer
11.325
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
274822ROCKFORD ;11
Adder
21.436
25326309TAIT D
Adder
1.195
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274745AC1-111 GEN9
Adder
6.042
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
270594AE1-207 GEN
Solar/Wind Harmer
12.561
270032AE2-172
Solar/Wind Harmer
4.302
958171AF2-111 GEN
Solar/Wind Harmer
32.027
252507AC2-088 GEN
Solar/Wind Harmer
2.278
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
252524AE2-267 GEN
Solar/Wind Harmer
1.938
25196608WSDLE5
Adder
10.55
270018AE2-047 C O1
Solar/Wind Harmer
1.501
253317AC1-085 GEN4
Solar/Wind Harmer
10.112
946181AF1-283 GEN
Solar/Wind Harmer
15.702
970193AG2-126 GEN
Solar/Wind Harmer
17.687
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
5.329
962771AG1-126 GEN
Solar/Wind Harmer
38.013
970153AG2-106 GEN
Solar/Wind Harmer
16.575
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.453
942481AE2-261 GEN
Solar/Wind Harmer
34.409
957381AF2-032 GEN
Solar/Wind Harmer
2.3
24379505HDWTR1G C
Solar/Wind Harmer
9.002
270240V3-007_GEN2
Solar/Wind Harmer
7.043
276785W4-005 GEN1
Solar/Wind Harmer
3.438
971993AH1-541 GEN
Solar/Wind Harmer
10.504
24386205FR-12G C
Solar/Wind Harmer
4.868
247642Z2-115 C
Solar/Wind Harmer
0.072
965461AG1-414 GEN
Solar/Wind Harmer
2.547
970289AG2-191 GEN
Solar/Wind Harmer
0.862
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
274682WAUKEGAN ;7U
Adder
19.478
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
8.236
270053AF1-130 C
Solar/Wind Harmer
32.909
270399AC1-101 GEN
Solar/Wind Harmer
7.81
270400AC1-102 GEN
Solar/Wind Harmer
7.81
971313AH1-133 GEN
Solar/Wind Harmer
10.201
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
5.744
970281AG2-184 GEN
Solar/Wind Harmer
34.819
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
9.777
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
962211AG1-066 GEN
Solar/Wind Harmer
3.81
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
14.005
971985AH1-537 GEN
Solar/Wind Harmer
26.103
971981AH1-535 GEN
Solar/Wind Harmer
14.155
270069AE2-166 C O1
Solar/Wind Harmer
12.483
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
13.172
972165AH1-665 GEN
Solar/Wind Harmer
10.538
339216AC1-074 GEN
Solar/Wind Harmer
2.182
270291AC1-194 GEN
Solar/Wind Harmer
6.437
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
6.941
270445AC2-157 GEN2
Solar/Wind Harmer
6.941
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253433AC1-085 GEN1
Solar/Wind Harmer
6.419
253432AC1-085 GEN2
Solar/Wind Harmer
0.323
253406AD2-031_GEN
Solar/Wind Harmer
1.524
270340AC2-060 GEN
Solar/Wind Harmer
3.588
270263AC1-001 GEN
Solar/Wind Harmer
1.236
270197AD1-017 GEN1
Solar/Wind Harmer
1.798
270356AE2-297 GEN
Solar/Wind Harmer
5.395
944221AF1-090 GEN
Solar/Wind Harmer
12.7
963841AG1-237 GEN
Solar/Wind Harmer
12.506
276763AC1-053 GEN1
Solar/Wind Harmer
4.5
276764AC1-053 GEN2
Solar/Wind Harmer
4.5
276668AB2-070 GEN1
Solar/Wind Harmer
2.517
276848AB2-070 GEN3
Solar/Wind Harmer
2.517
276849AB2-070 GEN2
Solar/Wind Harmer
2.517
24386405FR-21G C
Solar/Wind Harmer
4.886
24387005FR-3G C
Solar/Wind Harmer
4.493
970289AG2-191 GEN
Solar/Wind Harmer
2.135
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
972267AH1-718 GEN
Adder
4.579
274823ROCKFORD ;21
Adder
21.28
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.46 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5935.05
MW Contribution:
10.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.373
24721705FLATG2
50/50
40.36
24723005RIVRG1
Adder
34.305
24723105RIVRG2
Adder
34.305
970913AG2-568 GEN
Solar/Wind Harmer
10.293
24728205BUCHG1
Adder
6.531
971225AH1-072 GEN
Solar/Wind Harmer
2.862
971227AH1-073 GEN
Solar/Wind Harmer
2.862
927014AC1-188 GEN
Solar/Wind Harmer
2.06
270214AC2-123 GEN
Solar/Wind Harmer
2.985
971277AH1-098 GEN
Solar/Wind Harmer
5.094
942891AE2-308 GEN
Solar/Wind Harmer
11.926
964571AG1-320 GEN
Solar/Wind Harmer
9.728
339231AF1-038_GEN
Solar/Wind Harmer
2.148
972043AH1-570 GEN
Solar/Wind Harmer
2.957
972045AH1-571 GEN
Solar/Wind Harmer
2.366
971125AH1-004 GEN
Solar/Wind Harmer
4.718
970107AG2-081 GEN
Solar/Wind Harmer
3.539
270583AD2-179 GEN
Solar/Wind Harmer
11.79
966021AG1-471 GEN
Solar/Wind Harmer
6.353
339236AF1-050_GEN
Solar/Wind Harmer
2.134
971485AH1-239 GEN
Solar/Wind Harmer
9.407
964781AG1-341 GEN
Solar/Wind Harmer
12.396
945391AF1-204 GEN
Solar/Wind Harmer
16.22
962581AG1-107 GEN
Solar/Wind Harmer
5.847
24289405MTG1
50/50
11.32
24318705GVG2
50/50
11.469
24722005FLATG5
50/50
2.718
24721905FLATG4
50/50
49.64
24686405CER G5
Adder
14.607
270330AC1-082 GEN2
Solar/Wind Harmer
0.779
270329AC1-082 GEN1
Solar/Wind Harmer
0.779
962771AG1-126 GEN
Solar/Wind Harmer
51.105
970153AG2-106 GEN
Solar/Wind Harmer
22.284
971191AH1-055 GEN
Solar/Wind Harmer
27.435
960911AF2-382 GEN
Solar/Wind Harmer
10.97
972103AH1-617 GEN
Solar/Wind Harmer
29.032
971461AH1-227 GEN
Solar/Wind Harmer
7.34
270346AE1-212 GEN
Solar/Wind Harmer
11.918
957541AF2-048 GEN
Solar/Wind Harmer
2.06
943031AE2-326 GEN
Solar/Wind Harmer
4.698
972273AH1-721 GEN
Adder
99.65
970093AG2-073 GEN
Solar/Wind Harmer
6.342
970455AG2-298 GEN
Solar/Wind Harmer
4.162
339206AE1-143 GEN
Solar/Wind Harmer
2.532
970653AG2-424 GEN
Solar/Wind Harmer
0.827
270186AC1-089 GEN
Solar/Wind Harmer
7.225
3429391JKCT 9G
Adder
9.84
270367AC2-061_GEN
Solar/Wind Harmer
3.742
958121AF2-106 GEN
Solar/Wind Harmer
5.343
339243AC2-075 GEN1
Solar/Wind Harmer
0.533
972167AH1-666 GEN
Solar/Wind Harmer
9.374
339255AE2-071 GEN
Solar/Wind Harmer
1.375
339250AF1-203 GEN
Solar/Wind Harmer
0.708
970193AG2-126 GEN
Solar/Wind Harmer
17.459
25196008MFTGT1
Adder
1.55
24721605FLATG1
50/50
2.718
957241AF2-018 GEN
Solar/Wind Harmer
7.332
270053AF1-130 C
Solar/Wind Harmer
29.298
270399AC1-101 GEN
Solar/Wind Harmer
6.93
270400AC1-102 GEN
Solar/Wind Harmer
6.93
941621AE2-160 GEN
Adder
4.867
970281AG2-184 GEN
Solar/Wind Harmer
30.484
971313AH1-133 GEN
Solar/Wind Harmer
8.48
962211AG1-066 GEN
Solar/Wind Harmer
3.344
24734705WLF1G3
Adder
7.73
24734805WLF1G4
Adder
7.73
24734905WLF1G5
Adder
7.73
971061AG2-657 GEN
Solar/Wind Harmer
11.954
971985AH1-537 GEN
Solar/Wind Harmer
23.681
24735105WLF2G1
Adder
7.594
966391AG1-508 GEN
Solar/Wind Harmer
4.439
971331AH1-145 GEN
Solar/Wind Harmer
11.397
971329AH1-144 GEN
Solar/Wind Harmer
7.28
971981AH1-535 GEN
Solar/Wind Harmer
12.094
270444AC2-157 GEN1
Solar/Wind Harmer
6.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.747
3429211JKCT 2G
Adder
13.893
972163AH1-664 GEN
Solar/Wind Harmer
11.763
972165AH1-665 GEN
Solar/Wind Harmer
9.41
339216AC1-074 GEN
Solar/Wind Harmer
1.968
963841AG1-237 GEN
Solar/Wind Harmer
12.582
25196108MFTGT2
Adder
1.764
25196108MFTGT2
Adder
1.638
24386405FR-21G C
Solar/Wind Harmer
4.939
24387005FR-3G C
Solar/Wind Harmer
4.542
944221AF1-090 GEN
Solar/Wind Harmer
12.541
946581AF1-322 GEN
Solar/Wind Harmer
11.687
24691005MDL-2G C
Solar/Wind Harmer
4.223
276763AC1-053 GEN1
Solar/Wind Harmer
4.503
276764AC1-053 GEN2
Solar/Wind Harmer
4.503
276668AB2-070 GEN1
Solar/Wind Harmer
2.521
276848AB2-070 GEN3
Solar/Wind Harmer
2.521
276849AB2-070 GEN2
Solar/Wind Harmer
2.521
270356AE2-297 GEN
Solar/Wind Harmer
5.225
274853TWINGROVE;U1
Solar/Wind Harmer
8.154
274854TWINGROVE;U2
Solar/Wind Harmer
7.983
970289AG2-191 GEN
Solar/Wind Harmer
2.148
276726Z2-087_GEN
Solar/Wind Harmer
8.934
959341AF2-225 GEN
Solar/Wind Harmer
16.948
972267AH1-718 GEN
Adder
4.661
274823ROCKFORD ;21
Adder
21.773
25196408WSDLE3
Adder
9.858
25196308WSDLE2
Adder
9.772
24289405MTG1
50/50
11.32
243186AF1-051 GEN
50/50
12.373
24318705GVG2
50/50
11.469
24721805FLATG3
50/50
2.718
24723205RIVRG3
Adder
34.305
972203AH1-686 GEN
Adder
4.176
24686505CER G6
Adder
14.723
944971AF1-162 GEN
Solar/Wind Harmer
11.548
971403AH1-188 GEN
Solar/Wind Harmer
22.954
270331AC1-082 GEN3
Solar/Wind Harmer
0.78
960001AF2-291 GEN
Solar/Wind Harmer
4.782
962761AG1-125 GEN
Solar/Wind Harmer
51.105
970149AG2-104 GEN
Solar/Wind Harmer
31.557
970155AG2-107 GEN
Solar/Wind Harmer
22.284
24728305BUCHG2
Adder
6.531
971687AH1-348 GEN
Solar/Wind Harmer
1.432
24735205WLF2G2
Adder
7.594
970091AG2-072 GEN
Adder
98.735
339211AE2-254 GEN
Solar/Wind Harmer
1.806
3429241JKCT 3G
Adder
14.075
970653AG2-424 GEN
Solar/Wind Harmer
5.716
339241AF1-083 GEN
Solar/Wind Harmer
1.965
3429421JKCT 10G
Adder
9.84
339221AD2-048_GEN
Solar/Wind Harmer
1.812
943111AE2-339 GEN
Solar/Wind Harmer
1.043
964901AG1-354 GEN
Solar/Wind Harmer
17.632
945681AF1-233 GEN
Solar/Wind Harmer
22.112
963741AG1-226 GEN
Solar/Wind Harmer
51.931
25196008MFTGT1
Adder
1.6
24385905FR-11G C
Solar/Wind Harmer
9.545
24386605FR-22G C
Solar/Wind Harmer
4.939
24728605AND G2
Adder
4.399
965911AG1-460 GEN
Solar/Wind Harmer
1.595
24791305MDL-5G
Solar/Wind Harmer
2.754
276621W2-048 GEN
Solar/Wind Harmer
7.111
276686W4-005 GEN3
Solar/Wind Harmer
3.443
25196808ZIMRHP
Adder
86.01
971073AG2-665 GEN
Solar/Wind Harmer
1.316
276903AD2-071 C
Solar/Wind Harmer
11.309
940581AE2-045 GEN
Solar/Wind Harmer
11.524
971605AH1-302 GEN
Solar/Wind Harmer
9.854
276655WTG1_EQ
Solar/Wind Harmer
9.862
276656WTG2_EQ
Solar/Wind Harmer
1.306
939741AE1-205 GEN
Solar/Wind Harmer
22.597
270594AE1-207 GEN
Solar/Wind Harmer
15.305
270032AE2-172
Solar/Wind Harmer
5.241
25194608D.CRK4
Adder
1.843
274761LEE CO EC;2U
Adder
10.407
274766LEE CO EC;7U
Adder
10.284
274822ROCKFORD ;11
Adder
21.932
274828WAUKEGAN ;BP
Adder
12.324
274745AC1-111 GEN9
Adder
6.235
274682WAUKEGAN ;7U
Adder
20.049
274773LINCOLN ;4U
Adder
9.41
274774LINCOLN ;5U
Adder
9.41
274732ELWOOD EC;7P
Adder
18.315
274674JOLIET 9 ;6U
Adder
17.154
238185AF2-356 C
Solar/Wind Helper
2.191
254303AC2-168 GEN
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.24
20089026BF_G21_K23
Solar/Wind Helper
0.455
238120AE2-309 GEN
Solar/Wind Helper
0.424
238126S14_GEN_1
Solar/Wind Helper
0.674
23751101LEADS_P59
Solar/Wind Helper
1.865
20084626FORWARD
Solar/Wind Helper
0.338
964201AG1-281 GEN
Solar/Wind Helper
0.457
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.966
238109AE1-109 GEN2
Solar/Wind Helper
0.084
203952AE2-129 C
Solar/Wind Helper
0.445
203855AF2-088 C
Solar/Wind Helper
0.143
25196208WSDLE1
Adder
9.747
25196708WSDLE6
Adder
9.723
25196508WSDLE4
Adder
9.478
274744AC1-111 GEN8
Adder
6.235
274746AC1-111 G10
Adder
6.235
274775LINCOLN ;6U
Adder
9.41
274776LINCOLN ;7U
Adder
9.41
274777LINCOLN ;8U
Adder
9.41
274728ELWOOD EC;5P
Adder
18.315
274731ELWOOD EC;2P
Adder
18.315
274733ELWOOD EC;3P
Adder
18.315
274735ELWOOD EC;4P
Adder
18.315
23750501ELLIOTTS
Solar/Wind Helper
0.664
23652301WDPWR_K20
Solar/Wind Helper
0.142
23750701CROSSCHOOL
Solar/Wind Helper
1.189
203955AF1-039 C O1
Solar/Wind Helper
0.363
238118U2-030_1
Solar/Wind Helper
0.286
241997AF1-093 GEN
Solar/Wind Helper
0.24
241985AE1-237 GEN
Solar/Wind Helper
0.233
241982AE2-343 S C
Solar/Wind Helper
0.209
20089126CSLMN_L13
Solar/Wind Helper
0.575
20089226LOOKOUT
Solar/Wind Helper
0.573
20088926STNY CRK
Solar/Wind Helper
0.78
203940AF1-140 C
Solar/Wind Helper
0.376
20094526CT_V3-030
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.144
203846AF2-130 C
Solar/Wind Helper
0.423
959141AF2-205 GEN
Solar/Wind Harmer
1.763
961491AF2-440 GEN
Solar/Wind Harmer
2.43
970241AG2-163 GEN
Solar/Wind Harmer
28.851
24387305FR-4G C
Solar/Wind Harmer
5.833
966841AG1-555 GEN
Solar/Wind Harmer
2.883
252509AD1-136 GEN
Solar/Wind Harmer
0.293
276916AD2-100_GEN
Solar/Wind Harmer
24.022
276911AD2-131_GEN
Solar/Wind Harmer
4.855
270180AB1-006 GEN1
Solar/Wind Harmer
8.215
24697605MDL-3G C
Solar/Wind Harmer
4.21
24755605MDL-5G
Solar/Wind Harmer
2.754
24697905MDL-4G C
Solar/Wind Harmer
2.621
270181AB1-006 GEN2
Solar/Wind Harmer
0.817
276615X2-022 GEN
Solar/Wind Harmer
2.233
276838X2-022 GEN2
Solar/Wind Harmer
0.265
945421AF1-207 GEN
Solar/Wind Harmer
16.001
957841AF2-078 GEN
Solar/Wind Harmer
6.888
274880W4-005 GEN4
Solar/Wind Harmer
3.443
276174W4-005 GEN2
Solar/Wind Harmer
3.443
971073AG2-665 GEN
Solar/Wind Harmer
9.054
960611AF2-352 GEN
Solar/Wind Harmer
2.632
970879AG2-548 GEN
Solar/Wind Harmer
1.316
970291AG2-192 GEN
Solar/Wind Harmer
1.47
970291AG2-192 GEN
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
4.494
24699105WLD G1 C
Solar/Wind Harmer
4.441
942111AE2-223 GEN
Solar/Wind Harmer
9.262
25194408D.CRK1
Adder
8.477
25194508D.CRK3
Adder
1.585
274764LEE CO EC;5U
Adder
10.431
274765LEE CO EC;6U
Adder
10.431
274762LEE CO EC;3U
Adder
10.407
274763LEE CO EC;4U
Adder
10.309
972235AH1-702 GEN1
Adder
2.817
972236AH1-702 GEN2
Adder
2.45
274696ROCKY RD ;4P
Adder
12.719
274695ROCKY RD ;2P
Adder
12.425
274693ROCKY RD ;1P
Adder
12.303
274697ROCKY RD ;3P
Adder
3.375
274683WAUKEGAN ;8U
Adder
23.51
274683WAUKEGAN ;8U
Adder
19.818
274770LINCOLN ;1U
Adder
9.41
274771LINCOLN ;2U
Adder
9.41
274674JOLIET 9 ;6U
Adder
16.682
237043AE2-125 C
Solar/Wind Helper
0.176
23585401KL_K28_T16
Solar/Wind Helper
1.282
23751201ROTHROCK
Solar/Wind Helper
0.737
235054AD2-180 GEN
Solar/Wind Helper
1.698
238117U2-030
Solar/Wind Helper
0.286
962101AG1-054 GEN
Solar/Wind Helper
0.612
254304AE2-114 C
Solar/Wind Helper
0.205
254305AE2-115 C
Solar/Wind Helper
0.205
241967AE2-285_GEN
Solar/Wind Helper
0.597
241801AE1-079 GEN
Solar/Wind Helper
0.233
235531U2-073 GEN
Solar/Wind Helper
2.712
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.571
20088826HIGHLAND
Solar/Wind Helper
0.851
203961AE2-224 GEN
Solar/Wind Helper
2.277
203818AF1-086 GEN
Solar/Wind Helper
1.591
203853AF1-134 C O1
Solar/Wind Helper
0.449
946381AF1-302 GEN
Solar/Wind Helper
0.208
203946AE2-131 C
Solar/Wind Helper
0.445
203954AE2-126 C
Solar/Wind Helper
0.44
203804AE2-113_GEN
Solar/Wind Helper
1.631
940863AE2-074 GEN
Solar/Wind Helper
0.426
24386205FR-12G C
Solar/Wind Harmer
4.921
24728705AND G3
Adder
9.201
24728505AND G1
Adder
4.399
252507AC2-088 GEN
Solar/Wind Harmer
2.051
942481AE2-261 GEN
Solar/Wind Harmer
34.173
957381AF2-032 GEN
Solar/Wind Harmer
2.285
24690905MDL-1G C
Solar/Wind Harmer
9.169
970781AG2-491 GEN
Solar/Wind Harmer
11.422
958171AF2-111 GEN
Solar/Wind Harmer
28.524
276785W4-005 GEN1
Solar/Wind Harmer
3.443
971993AH1-541 GEN
Solar/Wind Harmer
10.521
247642Z2-115 C
Solar/Wind Harmer
0.073
965091AG1-374 GEN
Solar/Wind Harmer
33.954
970879AG2-548 GEN
Solar/Wind Harmer
9.054
959611AF2-252 GEN
Solar/Wind Harmer
2.632
965461AG1-414 GEN
Solar/Wind Harmer
2.564
970289AG2-191 GEN
Solar/Wind Harmer
0.868
25194608D.CRK4
Adder
1.843
274760LEE CO EC;1U
Adder
10.407
274767LEE CO EC;8U
Adder
10.284
25196608WSDLE5
Adder
9.576
274682WAUKEGAN ;7U
Adder
20.049
274772LINCOLN ;3U
Adder
9.41
972259AH1-714 GEN
Adder
21.265
274729ELWOOD EC;1P
Adder
18.315
274730ELWOOD EC;6P
Adder
18.315
274734ELWOOD EC;8P
Adder
18.315
274736ELWOOD EC;9P
Adder
18.315
237048AF1-022 C
Solar/Wind Helper
0.194
237046AF1-021 C
Solar/Wind Helper
0.336
235058AG1-386 C
Solar/Wind Helper
0.44
23562501BACKB
Solar/Wind Helper
0.897
964991AG1-363 GEN
Solar/Wind Helper
3.654
202652Y1-033 WT C
Solar/Wind Helper
0.551
238127S14_GEN_2
Solar/Wind Helper
0.674
20092526R32
Solar/Wind Helper
1.103
20303426NA_O38_P22
Solar/Wind Helper
0.938
203993AD2-133_GEN1
Solar/Wind Helper
0.966
238108AE1-109 GEN1
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
203854AF2-039 C
Solar/Wind Helper
0.298
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.12
NYPJM->LTFIMP_NY
CLTF
5.206
LGEELTFEXP_LGEE->PJM
CLTF
8.318
MECLTFEXP_MEC->PJM
CLTF
18.91
SIGELTFEXP_SIGE->PJM
CLTF
0.622
CPLELTFEXP_CPLE->PJM
CLTF
6.634
CBM West 2LTFEXP_CBM-W2->PJM
CBM
151.558
LAGNLTFEXP_LAGN->PJM
CLTF
22.209
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.481
TVALTFEXP_TVA->PJM
CLTF
11.344
WECLTFEXP_WEC->PJM
CLTF
4.274
AG2-052LTFEXP_AG2-052->PJM
LTF
0.26
AH1-155LTFEXP_AH1-155->PJM
LTF
0.389

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5896.19
MW Contribution:
8.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
18.148
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
7.739
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
28.948
270399AC1-101 GEN
Solar/Wind Harmer
4.065
270400AC1-102 GEN
Solar/Wind Harmer
4.065
971313AH1-133 GEN
Solar/Wind Harmer
5.869
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
1.796
970281AG2-184 GEN
Solar/Wind Harmer
24.292
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
5.625
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
6.84
971985AH1-537 GEN
Solar/Wind Harmer
3.035
971981AH1-535 GEN
Solar/Wind Harmer
6.584
270069AE2-166 C O1
Solar/Wind Harmer
8.709
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
10.231
972165AH1-665 GEN
Solar/Wind Harmer
8.194
339216AC1-074 GEN
Solar/Wind Harmer
0.242
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253406AD2-031_GEN
Solar/Wind Harmer
0.618
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.825
270197AD1-017 GEN1
Solar/Wind Harmer
1.008
270356AE2-297 GEN
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.756
963841AG1-237 GEN
Solar/Wind Harmer
3.459
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.489
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.702
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.158
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
270543AE2-219 C
Solar/Wind Harmer
5.421
946321AF1-296 GEN
Solar/Wind Harmer
4.325
274877BISHOP HL;1U
Solar/Wind Harmer
0.257
247536S-71 GEN
Solar/Wind Harmer
0.307
971611AH1-305 GEN
Solar/Wind Harmer
4.575
970169AG2-114 GEN
Solar/Wind Harmer
7.684
276741O09 GEN1
Solar/Wind Harmer
0.271
972267AH1-718 GEN
Adder
4.579
971609AH1-304 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
2.987
926823AC1-168 GEN
Solar/Wind Harmer
1.302
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
12.311
274856ECOGROVE ;U1
Solar/Wind Harmer
0.178
274823ROCKFORD ;21
Adder
21.28
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.232
945581AF1-223 GEN
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.136
276863AD2-134 GEN
Solar/Wind Harmer
0.136
971675AH1-338 GEN
Solar/Wind Harmer
2.966
971411AH1-196 GEN
Solar/Wind Harmer
11.402
970073AG2-061 GEN
Solar/Wind Harmer
2.528
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
970833AG2-524 GEN
Solar/Wind Harmer
8.285
970833AG2-524 GEN
Solar/Wind Harmer
5.523
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
960591AF2-350 GEN
Solar/Wind Harmer
7.491
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
971687AH1-348 GEN
Solar/Wind Harmer
1.157
24735205WLF2G2
Adder
8.97
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
3429241JKCT 3G
Adder
15.659
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
17.283
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
964901AG1-354 GEN
Solar/Wind Harmer
13.534
970653AG2-424 GEN
Solar/Wind Harmer
4.351
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
9.728
252510AF1-249 C
Solar/Wind Harmer
0.065
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.427
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
32.057
970149AG2-104 GEN
Solar/Wind Harmer
17.311
970155AG2-107 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.031
970773AG2-487 GEN
Solar/Wind Harmer
1.442
963741AG1-226 GEN
Solar/Wind Harmer
19.023
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
0.398
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.825
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.823
270594AE1-207 GEN
Solar/Wind Harmer
8.772
270032AE2-172
Solar/Wind Harmer
5.222
270005AE1-210 C O1
Solar/Wind Harmer
1.692
970825AG2-519 GEN
Solar/Wind Harmer
2.77
270273AD2-016 GEN
Solar/Wind Harmer
0.795
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
10.877
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.302
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.607
276708O09 GEN2
Solar/Wind Harmer
0.271
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
970569AG2-363 GEN
Solar/Wind Harmer
22.948
970819AG2-516 GEN
Solar/Wind Harmer
9.157
274822ROCKFORD ;11
Adder
21.436
957471AF2-041 GEN
Solar/Wind Harmer
22.848
959081AF2-199 GEN
Solar/Wind Harmer
7.616
971067AG2-660 GEN
Solar/Wind Harmer
2.539
945371AF1-202 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.694
971997AH1-543 GEN
Solar/Wind Harmer
3.993
25326309TAIT D
Adder
1.195
276882AE2-255 GEN
Solar/Wind Harmer
0.887
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.865
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.216
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.228
274745AC1-111 GEN9
Adder
6.042
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
3.264
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
270055AF2-134 C O1
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
960911AF2-382 GEN
Solar/Wind Harmer
8.992
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
5.939
972103AH1-617 GEN
Solar/Wind Harmer
23.135
971191AH1-055 GEN
Solar/Wind Harmer
29.317
270346AE1-212 GEN
Solar/Wind Harmer
10.045
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
6.854
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
18.672
970093AG2-073 GEN
Solar/Wind Harmer
7.87
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
8.058
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970653AG2-424 GEN
Solar/Wind Harmer
0.902
958171AF2-111 GEN
Solar/Wind Harmer
22.344
252507AC2-088 GEN
Solar/Wind Harmer
0.399
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
25196608WSDLE5
Adder
10.55
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
10.955
970193AG2-126 GEN
Solar/Wind Harmer
12.34
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
0
962771AG1-126 GEN
Solar/Wind Harmer
32.057
970153AG2-106 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.122
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.901
942481AE2-261 GEN
Solar/Wind Harmer
24.006
957381AF2-032 GEN
Solar/Wind Harmer
1.818
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.664
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.862
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.832
270004AE1-209 GEN
Solar/Wind Harmer
1.692
965091AG1-374 GEN
Solar/Wind Harmer
23.422
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
9.827
24728205BUCHG1
Adder
7.739
971225AH1-072 GEN
Solar/Wind Harmer
2.315
971227AH1-073 GEN
Solar/Wind Harmer
2.315
971277AH1-098 GEN
Solar/Wind Harmer
4.618
270583AD2-179 GEN
Solar/Wind Harmer
11.364
971073AG2-665 GEN
Solar/Wind Harmer
6.854
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
9.244
972043AH1-570 GEN
Solar/Wind Harmer
2.384
972045AH1-571 GEN
Solar/Wind Harmer
1.91
971125AH1-004 GEN
Solar/Wind Harmer
3.655
970107AG2-081 GEN
Solar/Wind Harmer
2.741
966021AG1-471 GEN
Solar/Wind Harmer
4.933
971485AH1-239 GEN
Solar/Wind Harmer
7.296
962581AG1-107 GEN
Solar/Wind Harmer
0.002
964781AG1-341 GEN
Solar/Wind Harmer
9.518
964571AG1-320 GEN
Solar/Wind Harmer
8.194
252509AD1-136 GEN
Solar/Wind Harmer
0.044
25183208HLCRTG
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.363
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
8.741
942671AE2-283 GEN
Solar/Wind Harmer
3.812
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
276916AD2-100_GEN
Solar/Wind Harmer
16.897
276911AD2-131_GEN
Solar/Wind Harmer
1.113
970241AG2-163 GEN
Solar/Wind Harmer
4.689
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.448
926881AC1-175 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.897
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
1.019
970291AG2-192 GEN
Solar/Wind Harmer
0.47
971613AH1-306 GEN
Solar/Wind Harmer
3.76
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.602
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
2.525
253370AE2-315 SEC1
Adder
2.225
970883AG2-550 GEN
Solar/Wind Harmer
7.744
970885AG2-551 GEN
Solar/Wind Harmer
2.581
276645AC1-214 GEN1
Solar/Wind Harmer
0.302
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.239
270031AE2-169
Solar/Wind Harmer
4.216
270599AE1-208 GEN
Solar/Wind Harmer
7.027
964611AG1-324 GEN
Solar/Wind Harmer
0.575
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
938861AE1-114 GEN
Solar/Wind Harmer
4.333
247621Y3-024
Adder
0.264
270201AC2-176 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
15.232
971343AH1-151 GEN
Solar/Wind Harmer
15.232
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.378
962691AG1-118 GEN
Solar/Wind Harmer
22.733
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
958481AF2-142 GEN
Solar/Wind Harmer
11.337
276897AD1-100 C
Solar/Wind Harmer
18.8
276893AG1-478 C
Solar/Wind Harmer
0.501
274674JOLIET 9 ;6U
Adder
16.589
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.437
276776AD2-060 GEN
Solar/Wind Harmer
0.799
958011AF2-095 GEN
Solar/Wind Harmer
10.787
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
959611AF2-252 GEN
Solar/Wind Harmer
2.602
970825AG2-519 GEN
Solar/Wind Harmer
5.878
946031AF1-268 GEN
Solar/Wind Harmer
7.4
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
965931AG1-462 GEN
Solar/Wind Harmer
19.72
971087AG2-675 GEN
Solar/Wind Harmer
4.124
3147123OTTER R
Solar/Wind Harmer
0.087
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.257
970191AG2-125 GEN
Solar/Wind Harmer
1.979
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
970571AG2-364 GEN
Solar/Wind Harmer
15.299
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.443
959091AF2-200 GEN
Solar/Wind Harmer
15.232
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
274850MENDOTA H;RU
Solar/Wind Harmer
0.088
946671AF1-331 GEN
Solar/Wind Harmer
0.811
276868AE1-113 GEN
Solar/Wind Harmer
1.52
274879MINONK ;1U
Solar/Wind Harmer
0.317
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
19.478
274862TOP CROP ;2U
Solar/Wind Harmer
1.021
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.409
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
970707AG2-453 GEN
Solar/Wind Harmer
24.521
274887GEN-1.85
Solar/Wind Harmer
0.195
276843GEN-1.7
Solar/Wind Harmer
0.242
276806AD2-047 C O1
Solar/Wind Harmer
4.245
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
970941AG2-585 GEN
Solar/Wind Harmer
2.017
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.86 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5846.6
MW Contribution:
11.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.749
243186AF1-051 GEN
50/50
12.616
24318705GVG2
50/50
11.694
24721805FLATG3
50/50
2.66
960001AF2-291 GEN
Solar/Wind Harmer
6.049
24723205RIVRG3
Adder
36.981
270331AC1-082 GEN3
Solar/Wind Harmer
0.937
24686505CER G6
Adder
16.193
972203AH1-686 GEN
Adder
4.427
944971AF1-162 GEN
Solar/Wind Harmer
12.449
971403AH1-188 GEN
Solar/Wind Harmer
24.722
24728305BUCHG2
Adder
6.959
971687AH1-348 GEN
Solar/Wind Harmer
1.517
24735205WLF2G2
Adder
7.967
24721605FLATG1
50/50
2.66
957241AF2-018 GEN
Solar/Wind Harmer
7.904
270053AF1-130 C
Solar/Wind Harmer
31.582
270399AC1-101 GEN
Solar/Wind Harmer
7.458
270400AC1-102 GEN
Solar/Wind Harmer
7.458
941621AE2-160 GEN
Adder
5.547
970281AG2-184 GEN
Solar/Wind Harmer
32.31
971313AH1-133 GEN
Solar/Wind Harmer
9.046
971061AG2-657 GEN
Solar/Wind Harmer
13.699
971985AH1-537 GEN
Solar/Wind Harmer
26.806
962211AG1-066 GEN
Solar/Wind Harmer
3.513
24734705WLF1G3
Adder
8.136
24734805WLF1G4
Adder
8.136
24734905WLF1G5
Adder
8.136
24735105WLF2G1
Adder
7.967
966391AG1-508 GEN
Solar/Wind Harmer
4.767
971331AH1-145 GEN
Solar/Wind Harmer
12.423
971329AH1-144 GEN
Solar/Wind Harmer
7.935
971981AH1-535 GEN
Solar/Wind Harmer
12.575
972163AH1-664 GEN
Solar/Wind Harmer
12.156
972165AH1-665 GEN
Solar/Wind Harmer
9.725
3429211JKCT 2G
Adder
14.123
270291AC1-194 GEN
Solar/Wind Harmer
6.12
339216AC1-074 GEN
Solar/Wind Harmer
2.003
25196108MFTGT2
Adder
1.756
25196108MFTGT2
Adder
1.631
25196408WSDLE3
Adder
9.915
25196308WSDLE2
Adder
9.829
25196208WSDLE1
Adder
9.804
25196708WSDLE6
Adder
9.779
25196508WSDLE4
Adder
9.533
270444AC2-157 GEN1
Solar/Wind Harmer
6.262
270445AC2-157 GEN2
Solar/Wind Harmer
6.262
270069AE2-166 C O1
Solar/Wind Harmer
10.085
253433AC1-085 GEN1
Solar/Wind Harmer
5.787
253432AC1-085 GEN2
Solar/Wind Harmer
0.291
253406AD2-031_GEN
Solar/Wind Harmer
1.368
270340AC2-060 GEN
Solar/Wind Harmer
3.206
270263AC1-001 GEN
Solar/Wind Harmer
1.104
270356AE2-297 GEN
Solar/Wind Harmer
4.818
944221AF1-090 GEN
Solar/Wind Harmer
11.234
963841AG1-237 GEN
Solar/Wind Harmer
11.024
276763AC1-053 GEN1
Solar/Wind Harmer
3.957
276764AC1-053 GEN2
Solar/Wind Harmer
3.957
276668AB2-070 GEN1
Solar/Wind Harmer
2.213
276848AB2-070 GEN3
Solar/Wind Harmer
2.213
276849AB2-070 GEN2
Solar/Wind Harmer
2.213
24386405FR-21G C
Solar/Wind Harmer
4.297
24387005FR-3G C
Solar/Wind Harmer
3.952
970289AG2-191 GEN
Solar/Wind Harmer
1.875
25306009OHH W.
Adder
2.793
253372AE2-315 SEC3
Adder
1.832
253372AE2-315 SEC3
Adder
1.832
972267AH1-718 GEN
Adder
3.983
274823ROCKFORD ;21
Adder
18.472
274744AC1-111 GEN8
Adder
5.228
274746AC1-111 G10
Adder
5.228
274728ELWOOD EC;5P
Adder
15.317
274731ELWOOD EC;2P
Adder
15.317
274733ELWOOD EC;3P
Adder
15.317
274735ELWOOD EC;4P
Adder
15.317
274675JOLIET 29;7U
Adder
28.551
23750501ELLIOTTS
Solar/Wind Helper
0.647
23652301WDPWR_K20
Solar/Wind Helper
0.14
241997AF1-093 GEN
Solar/Wind Helper
0.247
241985AE1-237 GEN
Solar/Wind Helper
0.241
241982AE2-343 S C
Solar/Wind Helper
0.216
203955AF1-039 C O1
Solar/Wind Helper
0.355
23750701CROSSCHOOL
Solar/Wind Helper
1.137
20089126CSLMN_L13
Solar/Wind Helper
0.564
20089226LOOKOUT
Solar/Wind Helper
0.562
238118U2-030_1
Solar/Wind Helper
0.274
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.371
20094526CT_V3-030
Solar/Wind Helper
0.443
203846AF2-130 C
Solar/Wind Helper
0.428
20088626ARWF_N39
Solar/Wind Helper
1.129
946581AF1-322 GEN
Solar/Wind Harmer
3.68
243186AF1-051 GEN
50/50
12.616
24721705FLATG2
50/50
39.51
24723005RIVRG1
Adder
36.981
24723105RIVRG2
Adder
36.981
970913AG2-568 GEN
Solar/Wind Harmer
11.393
24728205BUCHG1
Adder
6.959
927014AC1-188 GEN
Solar/Wind Harmer
2.439
971225AH1-072 GEN
Solar/Wind Harmer
3.033
971227AH1-073 GEN
Solar/Wind Harmer
3.033
270214AC2-123 GEN
Solar/Wind Harmer
3.2
971277AH1-098 GEN
Solar/Wind Harmer
5.471
971073AG2-665 GEN
Solar/Wind Harmer
10.456
970879AG2-548 GEN
Solar/Wind Harmer
1.52
270583AD2-179 GEN
Solar/Wind Harmer
12.855
962581AG1-107 GEN
Solar/Wind Harmer
6.12
961491AF2-440 GEN
Solar/Wind Harmer
2.543
942891AE2-308 GEN
Solar/Wind Harmer
12.112
972043AH1-570 GEN
Solar/Wind Harmer
3.018
972045AH1-571 GEN
Solar/Wind Harmer
2.414
971125AH1-004 GEN
Solar/Wind Harmer
4.793
970107AG2-081 GEN
Solar/Wind Harmer
3.595
339231AF1-038_GEN
Solar/Wind Harmer
2.155
966021AG1-471 GEN
Solar/Wind Harmer
6.374
971485AH1-239 GEN
Solar/Wind Harmer
9.429
252509AD1-136 GEN
Solar/Wind Harmer
0.301
339236AF1-050_GEN
Solar/Wind Harmer
2.122
964571AG1-320 GEN
Solar/Wind Harmer
9.57
964781AG1-341 GEN
Solar/Wind Harmer
12.309
25183208HLCRTG
Solar/Wind Harmer
6.902
25194408D.CRK1
Adder
8.538
25194508D.CRK3
Adder
1.596
945391AF1-204 GEN
Solar/Wind Harmer
14.618
24728805RICHG1
Adder
3.92
24728905RICHG2
Adder
3.92
253415AE1-040 GEN
Solar/Wind Harmer
1.157
276916AD2-100_GEN
Solar/Wind Harmer
21.377
276911AD2-131_GEN
Solar/Wind Harmer
4.32
970241AG2-163 GEN
Solar/Wind Harmer
25.444
926881AC1-175 GEN
Solar/Wind Harmer
5.627
276615X2-022 GEN
Solar/Wind Harmer
1.968
276838X2-022 GEN2
Solar/Wind Harmer
0.234
971073AG2-665 GEN
Solar/Wind Harmer
1.52
970091AG2-072 GEN
Adder
94.28
945681AF1-233 GEN
Solar/Wind Harmer
22.855
3429241JKCT 3G
Adder
14.309
339221AD2-048_GEN
Solar/Wind Harmer
1.847
339211AE2-254 GEN
Solar/Wind Harmer
1.818
3429421JKCT 10G
Adder
9.999
943111AE2-339 GEN
Solar/Wind Harmer
1.059
339241AF1-083 GEN
Solar/Wind Harmer
1.958
970653AG2-424 GEN
Solar/Wind Harmer
5.656
964901AG1-354 GEN
Solar/Wind Harmer
17.533
25196808ZIMRHP
Adder
87.559
25196008MFTGT1
Adder
1.593
252516AE2-318_GEN
Solar/Wind Harmer
11.412
252510AF1-249 C
Solar/Wind Harmer
0.473
25194608D.CRK4
Adder
1.856
270336AE1-100 GEN
Solar/Wind Harmer
1.934
253316AC1-085 GEN3
Solar/Wind Harmer
9.117
946171AF1-282 GEN
Solar/Wind Harmer
10.89
943811AF1-049 GEN
Solar/Wind Harmer
4.052
24728605AND G2
Adder
4.021
253398AE2-221_GEN2
Solar/Wind Harmer
4.748
270222AC2-111 GEN
Solar/Wind Harmer
4.662
944031AF1-071 GEN
Solar/Wind Harmer
1.049
963741AG1-226 GEN
Solar/Wind Harmer
45.799
965911AG1-460 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
32.808
970149AG2-104 GEN
Solar/Wind Harmer
20.259
970155AG2-107 GEN
Solar/Wind Harmer
14.306
942081AE2-220 GEN
Solar/Wind Harmer
6.447
270209AC1-174_GEN
Solar/Wind Harmer
4.103
270437AC2-090 C
Solar/Wind Harmer
5.627
270239V3-007_GEN1
Solar/Wind Harmer
1.735
276621W2-048 GEN
Solar/Wind Harmer
6.266
276686W4-005 GEN3
Solar/Wind Harmer
3.022
24385905FR-11G C
Solar/Wind Harmer
8.303
24386605FR-22G C
Solar/Wind Harmer
4.297
276903AD2-071 C
Solar/Wind Harmer
9.98
270594AE1-207 GEN
Solar/Wind Harmer
13.398
270032AE2-172
Solar/Wind Harmer
4.588
270005AE1-210 C O1
Solar/Wind Harmer
5.379
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274761LEE CO EC;2U
Adder
8.871
274766LEE CO EC;7U
Adder
8.766
274822ROCKFORD ;11
Adder
18.607
25326309TAIT D
Adder
1.032
274828WAUKEGAN ;BP
Adder
10.373
274682WAUKEGAN ;7U
Adder
16.869
274745AC1-111 GEN9
Adder
5.228
274732ELWOOD EC;7P
Adder
15.317
274674JOLIET 9 ;6U
Adder
14.342
274676JOLIET 29;8U
Adder
10.069
254303AC2-168 GEN
Solar/Wind Helper
0.154
241966AE1-183 GEN
Solar/Wind Helper
0.247
238185AF2-356 C
Solar/Wind Helper
2.102
20089026BF_G21_K23
Solar/Wind Helper
0.446
20084626FORWARD
Solar/Wind Helper
0.335
964201AG1-281 GEN
Solar/Wind Helper
0.452
238126S14_GEN_1
Solar/Wind Helper
0.645
20091526CHSTN_FL
Solar/Wind Helper
0.544
238120AE2-309 GEN
Solar/Wind Helper
0.406
20090526Q36
Solar/Wind Helper
0.956
203952AE2-129 C
Solar/Wind Helper
0.441
24289405MTG1
50/50
11.749
24318705GVG2
50/50
11.694
24722005FLATG5
50/50
2.66
24721905FLATG4
50/50
48.595
270330AC1-082 GEN2
Solar/Wind Harmer
0.934
270329AC1-082 GEN1
Solar/Wind Harmer
0.934
24686405CER G5
Adder
16.065
971191AH1-055 GEN
Solar/Wind Harmer
33.049
960911AF2-382 GEN
Solar/Wind Harmer
11.685
957541AF2-048 GEN
Solar/Wind Harmer
2.439
972103AH1-617 GEN
Solar/Wind Harmer
30.771
971461AH1-227 GEN
Solar/Wind Harmer
7.779
270346AE1-212 GEN
Solar/Wind Harmer
13.204
943031AE2-326 GEN
Solar/Wind Harmer
5.037
970879AG2-548 GEN
Solar/Wind Harmer
10.456
958121AF2-106 GEN
Solar/Wind Harmer
5.826
270186AC1-089 GEN
Solar/Wind Harmer
7.579
270367AC2-061_GEN
Solar/Wind Harmer
3.93
970093AG2-073 GEN
Solar/Wind Harmer
6.439
972167AH1-666 GEN
Solar/Wind Harmer
9.688
972273AH1-721 GEN
Adder
100.618
3429391JKCT 9G
Adder
9.999
339243AC2-075 GEN1
Solar/Wind Harmer
0.542
339206AE1-143 GEN
Solar/Wind Harmer
2.528
970455AG2-298 GEN
Solar/Wind Harmer
4.124
252507AC2-088 GEN
Solar/Wind Harmer
2.108
958171AF2-111 GEN
Solar/Wind Harmer
29.368
970653AG2-424 GEN
Solar/Wind Harmer
0.818
339255AE2-071 GEN
Solar/Wind Harmer
1.366
339250AF1-203 GEN
Solar/Wind Harmer
0.703
25196008MFTGT1
Adder
1.543
252519AF1-045_GEN
Solar/Wind Harmer
4.153
25194608D.CRK4
Adder
1.856
252524AE2-267 GEN
Solar/Wind Harmer
1.77
25196608WSDLE5
Adder
9.632
270030AE2-140 GEN
Solar/Wind Harmer
21.915
253317AC1-085 GEN4
Solar/Wind Harmer
9.117
946181AF1-283 GEN
Solar/Wind Harmer
14.157
970193AG2-126 GEN
Solar/Wind Harmer
15.734
24728705AND G3
Adder
8.411
24728505AND G1
Adder
4.021
253394AE2-221_GEN
Solar/Wind Harmer
4.748
942481AE2-261 GEN
Solar/Wind Harmer
30.351
957381AF2-032 GEN
Solar/Wind Harmer
2.028
962771AG1-126 GEN
Solar/Wind Harmer
32.808
970153AG2-106 GEN
Solar/Wind Harmer
14.306
24379505HDWTR1G C
Solar/Wind Harmer
7.972
270240V3-007_GEN2
Solar/Wind Harmer
6.237
276785W4-005 GEN1
Solar/Wind Harmer
3.022
971993AH1-541 GEN
Solar/Wind Harmer
9.233
24386205FR-12G C
Solar/Wind Harmer
4.281
247642Z2-115 C
Solar/Wind Harmer
0.063
965461AG1-414 GEN
Solar/Wind Harmer
2.238
970289AG2-191 GEN
Solar/Wind Harmer
0.757
270004AE1-209 GEN
Solar/Wind Harmer
5.379
24690905MDL-1G C
Solar/Wind Harmer
7.897
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274760LEE CO EC;1U
Adder
8.871
274767LEE CO EC;8U
Adder
8.766
274682WAUKEGAN ;7U
Adder
16.869
274729ELWOOD EC;1P
Adder
15.317
274730ELWOOD EC;6P
Adder
15.317
274734ELWOOD EC;8P
Adder
15.317
274736ELWOOD EC;9P
Adder
15.317
237048AF1-022 C
Solar/Wind Helper
0.19
235058AG1-386 C
Solar/Wind Helper
0.455
237046AF1-021 C
Solar/Wind Helper
0.331
202652Y1-033 WT C
Solar/Wind Helper
0.537
23562501BACKB
Solar/Wind Helper
0.856
964991AG1-363 GEN
Solar/Wind Helper
3.486
20092526R32
Solar/Wind Helper
1.091
238127S14_GEN_2
Solar/Wind Helper
0.645
20303426NA_O38_P22
Solar/Wind Helper
0.926
203993AD2-133_GEN1
Solar/Wind Helper
0.956
24725505WLD G2 C
Solar/Wind Harmer
3.981
24699105WLD G1 C
Solar/Wind Harmer
3.935
274880W4-005 GEN4
Solar/Wind Harmer
3.022
276174W4-005 GEN2
Solar/Wind Harmer
3.022
270383AD1-128 GEN
Solar/Wind Harmer
6.1
24387305FR-4G C
Solar/Wind Harmer
5.075
966841AG1-555 GEN
Solar/Wind Harmer
2.508
970291AG2-192 GEN
Solar/Wind Harmer
1.283
970291AG2-192 GEN
Solar/Wind Harmer
0.413
270180AB1-006 GEN1
Solar/Wind Harmer
7.075
253370AE2-315 SEC1
Adder
1.937
247621Y3-024
Adder
0.23
274764LEE CO EC;5U
Adder
8.891
274765LEE CO EC;6U
Adder
8.891
274762LEE CO EC;3U
Adder
8.871
274763LEE CO EC;4U
Adder
8.787
972235AH1-702 GEN1
Adder
2.391
972236AH1-702 GEN2
Adder
2.08
25322209TAIT E
Adder
9.19
25322209TAIT E
Adder
8.984
274683WAUKEGAN ;8U
Adder
19.789
274683WAUKEGAN ;8U
Adder
16.681
274696ROCKY RD ;4P
Adder
10.699
274695ROCKY RD ;2P
Adder
10.452
274693ROCKY RD ;1P
Adder
10.349
274697ROCKY RD ;3P
Adder
2.839
274674JOLIET 9 ;6U
Adder
14.342
237043AE2-125 C
Solar/Wind Helper
0.175
254304AE2-114 C
Solar/Wind Helper
0.213
254305AE2-115 C
Solar/Wind Helper
0.213
962101AG1-054 GEN
Solar/Wind Helper
0.63
241967AE2-285_GEN
Solar/Wind Helper
0.617
241801AE1-079 GEN
Solar/Wind Helper
0.241
23585401KL_K28_T16
Solar/Wind Helper
1.231
23751201ROTHROCK
Solar/Wind Helper
0.704
235054AD2-180 GEN
Solar/Wind Helper
1.627
946071AF1-272 GEN
Solar/Wind Helper
2.555
238117U2-030
Solar/Wind Helper
0.274
20083426SW_E13_K22
Solar/Wind Helper
0.053
20088826HIGHLAND
Solar/Wind Helper
0.842
235531U2-073 GEN
Solar/Wind Helper
2.597
203818AF1-086 GEN
Solar/Wind Helper
1.582
203961AE2-224 GEN
Solar/Wind Helper
2.25
946381AF1-302 GEN
Solar/Wind Helper
0.208
203853AF1-134 C O1
Solar/Wind Helper
0.446
203946AE2-131 C
Solar/Wind Helper
0.441
203804AE2-113_GEN
Solar/Wind Helper
1.63
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.677
NYPJM->LTFIMP_NY
CLTF
5.068
LGEELTFEXP_LGEE->PJM
CLTF
8.183
WECLTFEXP_WEC->PJM
CLTF
3.631
MECLTFEXP_MEC->PJM
CLTF
16.745
SIGELTFEXP_SIGE->PJM
CLTF
0.592
CPLELTFEXP_CPLE->PJM
CLTF
7.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
143.77
LAGNLTFEXP_LAGN->PJM
CLTF
21.601
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.934
TVALTFEXP_TVA->PJM
CLTF
11.244
AG2-052LTFEXP_AG2-052->PJM
LTF
0.218
AH1-155LTFEXP_AH1-155->PJM
LTF
0.328

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.88 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5626.94
MW Contribution:
12.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.675
957241AF2-018 GEN
Solar/Wind Harmer
7.959
270053AF1-130 C
Solar/Wind Harmer
31.802
24289405MTG1
50/50
11.803
243186AF1-051 GEN
50/50
12.678
24318705GVG2
50/50
11.752
24721805FLATG3
50/50
2.675
960001AF2-291 GEN
Solar/Wind Harmer
6.087
24723205RIVRG3
Adder
37.214
270331AC1-082 GEN3
Solar/Wind Harmer
0.942
24686505CER G6
Adder
16.296
972203AH1-686 GEN
Adder
4.456
944971AF1-162 GEN
Solar/Wind Harmer
12.535
971403AH1-188 GEN
Solar/Wind Harmer
24.896
24728305BUCHG2
Adder
7.015
971687AH1-348 GEN
Solar/Wind Harmer
1.53
24735205WLF2G2
Adder
8.038
971073AG2-665 GEN
Solar/Wind Harmer
1.534
970091AG2-072 GEN
Adder
95.233
945681AF1-233 GEN
Solar/Wind Harmer
23.089
3429241JKCT 3G
Adder
14.456
339221AD2-048_GEN
Solar/Wind Harmer
1.866
339211AE2-254 GEN
Solar/Wind Harmer
1.837
3429421JKCT 10G
Adder
10.103
943111AE2-339 GEN
Solar/Wind Harmer
1.07
339241AF1-083 GEN
Solar/Wind Harmer
1.979
970653AG2-424 GEN
Solar/Wind Harmer
5.716
964901AG1-354 GEN
Solar/Wind Harmer
17.72
25196808ZIMRHP
Adder
88.501
25196008MFTGT1
Adder
1.61
252516AE2-318_GEN
Solar/Wind Harmer
11.536
252510AF1-249 C
Solar/Wind Harmer
0.479
25194608D.CRK4
Adder
1.876
270336AE1-100 GEN
Solar/Wind Harmer
1.956
253316AC1-085 GEN3
Solar/Wind Harmer
9.221
946171AF1-282 GEN
Solar/Wind Harmer
11.014
943811AF1-049 GEN
Solar/Wind Harmer
4.099
24728605AND G2
Adder
4.069
253398AE2-221_GEN2
Solar/Wind Harmer
4.804
270222AC2-111 GEN
Solar/Wind Harmer
4.717
944031AF1-071 GEN
Solar/Wind Harmer
1.061
963741AG1-226 GEN
Solar/Wind Harmer
46.357
965911AG1-460 GEN
Solar/Wind Harmer
1.434
962761AG1-125 GEN
Solar/Wind Harmer
33.21
970149AG2-104 GEN
Solar/Wind Harmer
20.507
970155AG2-107 GEN
Solar/Wind Harmer
14.481
942081AE2-220 GEN
Solar/Wind Harmer
6.527
24289405MTG1
50/50
11.803
24318705GVG2
50/50
11.752
24722005FLATG5
50/50
2.675
24721905FLATG4
50/50
48.862
270330AC1-082 GEN2
Solar/Wind Harmer
0.94
270329AC1-082 GEN1
Solar/Wind Harmer
0.94
24686405CER G5
Adder
16.168
971191AH1-055 GEN
Solar/Wind Harmer
33.281
960911AF2-382 GEN
Solar/Wind Harmer
11.778
957541AF2-048 GEN
Solar/Wind Harmer
2.459
972103AH1-617 GEN
Solar/Wind Harmer
31.019
971461AH1-227 GEN
Solar/Wind Harmer
7.843
270346AE1-212 GEN
Solar/Wind Harmer
13.316
943031AE2-326 GEN
Solar/Wind Harmer
5.082
970879AG2-548 GEN
Solar/Wind Harmer
10.556
958121AF2-106 GEN
Solar/Wind Harmer
5.883
270186AC1-089 GEN
Solar/Wind Harmer
7.655
270367AC2-061_GEN
Solar/Wind Harmer
3.969
970093AG2-073 GEN
Solar/Wind Harmer
6.505
972167AH1-666 GEN
Solar/Wind Harmer
9.788
972273AH1-721 GEN
Adder
101.651
3429391JKCT 9G
Adder
10.103
339243AC2-075 GEN1
Solar/Wind Harmer
0.548
339206AE1-143 GEN
Solar/Wind Harmer
2.555
970455AG2-298 GEN
Solar/Wind Harmer
4.167
252507AC2-088 GEN
Solar/Wind Harmer
2.13
958171AF2-111 GEN
Solar/Wind Harmer
29.678
970653AG2-424 GEN
Solar/Wind Harmer
0.827
339255AE2-071 GEN
Solar/Wind Harmer
1.381
339250AF1-203 GEN
Solar/Wind Harmer
0.711
25196008MFTGT1
Adder
1.56
252519AF1-045_GEN
Solar/Wind Harmer
4.199
25194608D.CRK4
Adder
1.876
252524AE2-267 GEN
Solar/Wind Harmer
1.789
25196608WSDLE5
Adder
9.738
270030AE2-140 GEN
Solar/Wind Harmer
22.165
253317AC1-085 GEN4
Solar/Wind Harmer
9.221
946181AF1-283 GEN
Solar/Wind Harmer
14.318
970193AG2-126 GEN
Solar/Wind Harmer
15.92
24728705AND G3
Adder
8.51
24728505AND G1
Adder
4.069
253394AE2-221_GEN
Solar/Wind Harmer
4.804
942481AE2-261 GEN
Solar/Wind Harmer
30.722
957381AF2-032 GEN
Solar/Wind Harmer
2.053
962771AG1-126 GEN
Solar/Wind Harmer
33.21
970153AG2-106 GEN
Solar/Wind Harmer
14.481
24379505HDWTR1G C
Solar/Wind Harmer
8.07
270240V3-007_GEN2
Solar/Wind Harmer
6.314
276785W4-005 GEN1
Solar/Wind Harmer
3.059
971993AH1-541 GEN
Solar/Wind Harmer
9.348
24386205FR-12G C
Solar/Wind Harmer
4.335
247642Z2-115 C
Solar/Wind Harmer
0.064
965461AG1-414 GEN
Solar/Wind Harmer
2.266
970289AG2-191 GEN
Solar/Wind Harmer
0.767
270004AE1-209 GEN
Solar/Wind Harmer
5.447
24690905MDL-1G C
Solar/Wind Harmer
7.997
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274760LEE CO EC;1U
Adder
8.986
274767LEE CO EC;8U
Adder
8.88
274682WAUKEGAN ;7U
Adder
17.092
274729ELWOOD EC;1P
Adder
15.521
274730ELWOOD EC;6P
Adder
15.521
274734ELWOOD EC;8P
Adder
15.521
274736ELWOOD EC;9P
Adder
15.521
237048AF1-022 C
Solar/Wind Helper
0.188
235058AG1-386 C
Solar/Wind Helper
0.45
237046AF1-021 C
Solar/Wind Helper
0.327
202652Y1-033 WT C
Solar/Wind Helper
0.53
23562501BACKB
Solar/Wind Helper
0.844
964991AG1-363 GEN
Solar/Wind Helper
3.438
20092526R32
Solar/Wind Helper
1.076
238127S14_GEN_2
Solar/Wind Helper
0.636
20303426NA_O38_P22
Solar/Wind Helper
0.913
270399AC1-101 GEN
Solar/Wind Harmer
7.511
270400AC1-102 GEN
Solar/Wind Harmer
7.511
941621AE2-160 GEN
Adder
5.587
970281AG2-184 GEN
Solar/Wind Harmer
32.57
971313AH1-133 GEN
Solar/Wind Harmer
9.12
971061AG2-657 GEN
Solar/Wind Harmer
13.811
971985AH1-537 GEN
Solar/Wind Harmer
27.028
962211AG1-066 GEN
Solar/Wind Harmer
3.543
24734705WLF1G3
Adder
8.207
24734805WLF1G4
Adder
8.207
24734905WLF1G5
Adder
8.207
24735105WLF2G1
Adder
8.038
966391AG1-508 GEN
Solar/Wind Harmer
4.81
971331AH1-145 GEN
Solar/Wind Harmer
12.539
971329AH1-144 GEN
Solar/Wind Harmer
8.009
971981AH1-535 GEN
Solar/Wind Harmer
12.699
972163AH1-664 GEN
Solar/Wind Harmer
12.28
972165AH1-665 GEN
Solar/Wind Harmer
9.824
3429211JKCT 2G
Adder
14.268
270291AC1-194 GEN
Solar/Wind Harmer
6.183
339216AC1-074 GEN
Solar/Wind Harmer
2.024
25196108MFTGT2
Adder
1.775
25196108MFTGT2
Adder
1.648
25196408WSDLE3
Adder
10.024
25196308WSDLE2
Adder
9.937
25196208WSDLE1
Adder
9.912
25196708WSDLE6
Adder
9.887
25196508WSDLE4
Adder
9.638
270444AC2-157 GEN1
Solar/Wind Harmer
6.331
270445AC2-157 GEN2
Solar/Wind Harmer
6.331
270069AE2-166 C O1
Solar/Wind Harmer
10.196
253433AC1-085 GEN1
Solar/Wind Harmer
5.853
253432AC1-085 GEN2
Solar/Wind Harmer
0.295
253406AD2-031_GEN
Solar/Wind Harmer
1.384
270340AC2-060 GEN
Solar/Wind Harmer
3.244
270263AC1-001 GEN
Solar/Wind Harmer
1.117
270356AE2-297 GEN
Solar/Wind Harmer
4.876
944221AF1-090 GEN
Solar/Wind Harmer
11.369
963841AG1-237 GEN
Solar/Wind Harmer
11.16
276763AC1-053 GEN1
Solar/Wind Harmer
4.006
276764AC1-053 GEN2
Solar/Wind Harmer
4.006
276668AB2-070 GEN1
Solar/Wind Harmer
2.24
276848AB2-070 GEN3
Solar/Wind Harmer
2.24
276849AB2-070 GEN2
Solar/Wind Harmer
2.24
24386405FR-21G C
Solar/Wind Harmer
4.35
24387005FR-3G C
Solar/Wind Harmer
4.001
970289AG2-191 GEN
Solar/Wind Harmer
1.899
25306009OHH W.
Adder
2.828
253372AE2-315 SEC3
Adder
1.855
253372AE2-315 SEC3
Adder
1.855
972267AH1-718 GEN
Adder
4.035
274823ROCKFORD ;21
Adder
18.714
274744AC1-111 GEN8
Adder
5.298
274746AC1-111 G10
Adder
5.298
274728ELWOOD EC;5P
Adder
15.521
274731ELWOOD EC;2P
Adder
15.521
274733ELWOOD EC;3P
Adder
15.521
274735ELWOOD EC;4P
Adder
15.521
274675JOLIET 29;7U
Adder
28.931
23750501ELLIOTTS
Solar/Wind Helper
0.639
23652301WDPWR_K20
Solar/Wind Helper
0.139
241997AF1-093 GEN
Solar/Wind Helper
0.244
241985AE1-237 GEN
Solar/Wind Helper
0.238
241982AE2-343 S C
Solar/Wind Helper
0.214
203955AF1-039 C O1
Solar/Wind Helper
0.35
23750701CROSSCHOOL
Solar/Wind Helper
1.122
20089126CSLMN_L13
Solar/Wind Helper
0.556
20089226LOOKOUT
Solar/Wind Helper
0.555
238118U2-030_1
Solar/Wind Helper
0.27
20088926STNY CRK
Solar/Wind Helper
0.759
203940AF1-140 C
Solar/Wind Helper
0.366
20094526CT_V3-030
Solar/Wind Helper
0.437
203846AF2-130 C
Solar/Wind Helper
0.422
20088626ARWF_N39
Solar/Wind Helper
1.113
946581AF1-322 GEN
Solar/Wind Harmer
3.726
243186AF1-051 GEN
50/50
12.678
24721705FLATG2
50/50
39.728
24723005RIVRG1
Adder
37.214
24723105RIVRG2
Adder
37.214
970913AG2-568 GEN
Solar/Wind Harmer
11.477
24728205BUCHG1
Adder
7.015
927014AC1-188 GEN
Solar/Wind Harmer
2.459
971225AH1-072 GEN
Solar/Wind Harmer
3.058
971227AH1-073 GEN
Solar/Wind Harmer
3.058
270214AC2-123 GEN
Solar/Wind Harmer
3.229
971277AH1-098 GEN
Solar/Wind Harmer
5.52
971073AG2-665 GEN
Solar/Wind Harmer
10.556
970879AG2-548 GEN
Solar/Wind Harmer
1.534
270583AD2-179 GEN
Solar/Wind Harmer
12.98
962581AG1-107 GEN
Solar/Wind Harmer
6.183
961491AF2-440 GEN
Solar/Wind Harmer
2.569
942891AE2-308 GEN
Solar/Wind Harmer
12.236
972043AH1-570 GEN
Solar/Wind Harmer
3.049
972045AH1-571 GEN
Solar/Wind Harmer
2.439
971125AH1-004 GEN
Solar/Wind Harmer
4.843
970107AG2-081 GEN
Solar/Wind Harmer
3.632
339231AF1-038_GEN
Solar/Wind Harmer
2.178
966021AG1-471 GEN
Solar/Wind Harmer
6.442
971485AH1-239 GEN
Solar/Wind Harmer
9.528
252509AD1-136 GEN
Solar/Wind Harmer
0.304
339236AF1-050_GEN
Solar/Wind Harmer
2.145
964571AG1-320 GEN
Solar/Wind Harmer
9.672
964781AG1-341 GEN
Solar/Wind Harmer
12.441
25183208HLCRTG
Solar/Wind Harmer
6.977
25194408D.CRK1
Adder
8.632
25194508D.CRK3
Adder
1.614
945391AF1-204 GEN
Solar/Wind Harmer
14.791
24728805RICHG1
Adder
3.967
24728905RICHG2
Adder
3.967
253415AE1-040 GEN
Solar/Wind Harmer
1.171
276916AD2-100_GEN
Solar/Wind Harmer
21.637
276911AD2-131_GEN
Solar/Wind Harmer
4.373
970241AG2-163 GEN
Solar/Wind Harmer
25.754
926881AC1-175 GEN
Solar/Wind Harmer
5.696
276615X2-022 GEN
Solar/Wind Harmer
1.992
276838X2-022 GEN2
Solar/Wind Harmer
0.237
24725505WLD G2 C
Solar/Wind Harmer
4.03
24699105WLD G1 C
Solar/Wind Harmer
3.983
274880W4-005 GEN4
Solar/Wind Harmer
3.059
276174W4-005 GEN2
Solar/Wind Harmer
3.059
270383AD1-128 GEN
Solar/Wind Harmer
6.175
24387305FR-4G C
Solar/Wind Harmer
5.138
966841AG1-555 GEN
Solar/Wind Harmer
2.539
970291AG2-192 GEN
Solar/Wind Harmer
1.299
970291AG2-192 GEN
Solar/Wind Harmer
0.418
270180AB1-006 GEN1
Solar/Wind Harmer
7.164
253370AE2-315 SEC1
Adder
1.962
247621Y3-024
Adder
0.233
274764LEE CO EC;5U
Adder
9.007
274765LEE CO EC;6U
Adder
9.007
274762LEE CO EC;3U
Adder
8.986
274763LEE CO EC;4U
Adder
8.901
972235AH1-702 GEN1
Adder
2.423
972236AH1-702 GEN2
Adder
2.107
25322209TAIT E
Adder
9.312
25322209TAIT E
Adder
9.102
274683WAUKEGAN ;8U
Adder
20.05
274683WAUKEGAN ;8U
Adder
16.901
274696ROCKY RD ;4P
Adder
10.84
274695ROCKY RD ;2P
Adder
10.59
274693ROCKY RD ;1P
Adder
10.485
274697ROCKY RD ;3P
Adder
2.877
274674JOLIET 9 ;6U
Adder
14.533
237043AE2-125 C
Solar/Wind Helper
0.172
254304AE2-114 C
Solar/Wind Helper
0.21
254305AE2-115 C
Solar/Wind Helper
0.21
962101AG1-054 GEN
Solar/Wind Helper
0.622
241967AE2-285_GEN
Solar/Wind Helper
0.609
241801AE1-079 GEN
Solar/Wind Helper
0.238
23585401KL_K28_T16
Solar/Wind Helper
1.215
23751201ROTHROCK
Solar/Wind Helper
0.695
235054AD2-180 GEN
Solar/Wind Helper
1.606
946071AF1-272 GEN
Solar/Wind Helper
2.52
238117U2-030
Solar/Wind Helper
0.27
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.83
235531U2-073 GEN
Solar/Wind Helper
2.561
203818AF1-086 GEN
Solar/Wind Helper
1.56
203961AE2-224 GEN
Solar/Wind Helper
2.218
946381AF1-302 GEN
Solar/Wind Helper
0.205
270209AC1-174_GEN
Solar/Wind Harmer
4.153
270437AC2-090 C
Solar/Wind Harmer
5.696
270239V3-007_GEN1
Solar/Wind Harmer
1.756
276621W2-048 GEN
Solar/Wind Harmer
6.343
276686W4-005 GEN3
Solar/Wind Harmer
3.059
24385905FR-11G C
Solar/Wind Harmer
8.406
24386605FR-22G C
Solar/Wind Harmer
4.35
276903AD2-071 C
Solar/Wind Harmer
10.104
270594AE1-207 GEN
Solar/Wind Harmer
13.567
270032AE2-172
Solar/Wind Harmer
4.646
270005AE1-210 C O1
Solar/Wind Harmer
5.447
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274761LEE CO EC;2U
Adder
8.986
274766LEE CO EC;7U
Adder
8.88
274822ROCKFORD ;11
Adder
18.851
25326309TAIT D
Adder
1.046
274828WAUKEGAN ;BP
Adder
10.51
274682WAUKEGAN ;7U
Adder
17.092
274745AC1-111 GEN9
Adder
5.298
274732ELWOOD EC;7P
Adder
15.521
274674JOLIET 9 ;6U
Adder
14.533
274676JOLIET 29;8U
Adder
10.203
254303AC2-168 GEN
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.244
238185AF2-356 C
Solar/Wind Helper
2.074
20089026BF_G21_K23
Solar/Wind Helper
0.44
20084626FORWARD
Solar/Wind Helper
0.33
964201AG1-281 GEN
Solar/Wind Helper
0.445
238126S14_GEN_1
Solar/Wind Helper
0.636
20091526CHSTN_FL
Solar/Wind Helper
0.536
238120AE2-309 GEN
Solar/Wind Helper
0.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.565
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.151
NYPJM->LTFIMP_NY
CLTF
4.988
LGEELTFEXP_LGEE->PJM
CLTF
8.269
MECLTFEXP_MEC->PJM
CLTF
16.954
SIGELTFEXP_SIGE->PJM
CLTF
0.599
CPLELTFEXP_CPLE->PJM
CLTF
7.358
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.448
LAGNLTFEXP_LAGN->PJM
CLTF
21.853
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
11.37
WECLTFEXP_WEC->PJM
CLTF
3.678
AG2-052LTFEXP_AG2-052->PJM
LTF
0.221
AH1-155LTFEXP_AH1-155->PJM
LTF
0.332
CONTINGENCY 'AEP_P4_#8975_05KAMMER 765_MM2_SRT-A'
 OPEN BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT7A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT10A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
242920 to 235102 ckt 5
242519 to 314912 ckt 1
242925 to 235117 ckt 1
242516 to 242920 ckt 1

Winter Peak Analysis

The New Service Request AG2-665 was evaluated as a 80.0 MW (54.0 MW Capacity) injection in the AEP area.

AG2-665 was evaluated as part of a plant. The plant consists of AG2-665, AG2-548. The total Energy output of the plant was evaluated at its maximum seasonal capability of 160.0 MW (180.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC179.78 %1180.0B2121.38
6.57
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-W_SENS
BreakerAC179.78 %1180.0B2121.38
6.57
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-W_SENS
BreakerAC179.78 %1180.0B2121.38
6.57
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC179.78 %1180.0B2121.37
6.57

Details for [AG2-665] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.78 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2121.38
MW Contribution:
6.57
IPD Plant:AG2-665
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
PJM_IPD_GROUP
5.838
970879AG2-548 GEN
PJM_IPD_GROUP
0.73
971073AG2-665 GEN
PJM_IPD_GROUP
5.838
971073AG2-665 GEN
PJM_IPD_GROUP
0.73

Details for [AG2-665] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.78 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2121.38
MW Contribution:
6.57
IPD Plant:AG2-665
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
PJM_IPD_GROUP
5.838
970879AG2-548 GEN
PJM_IPD_GROUP
0.73
971073AG2-665 GEN
PJM_IPD_GROUP
5.838
971073AG2-665 GEN
PJM_IPD_GROUP
0.73

Details for [AG2-665] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.78 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2121.38
MW Contribution:
6.57
IPD Plant:AG2-665
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
PJM_IPD_GROUP
5.838
970879AG2-548 GEN
PJM_IPD_GROUP
0.73
971073AG2-665 GEN
PJM_IPD_GROUP
5.838
971073AG2-665 GEN
PJM_IPD_GROUP
0.73

Details for [AG2-665] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.78 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2121.37
MW Contribution:
6.57
IPD Plant:AG2-665
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
PJM_IPD_GROUP
5.838
970879AG2-548 GEN
PJM_IPD_GROUP
0.73
971073AG2-665 GEN
PJM_IPD_GROUP
5.838
971073AG2-665 GEN
PJM_IPD_GROUP
0.73
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-W_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                   /*01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-W_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                   /*01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-665 was evaluated as a 80.0 MW injection and 90.0 MW withdrawal in the AEP area.

AG2-665 was evaluated as part of a plant. The plant consists of AG2-665, AG2-548. The total Energy output of the plant was evaluated at its maximum seasonal capability of 160.0 MW (206.45 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
BreakerAC104.71 %255.0B267.01
79.94
GD2AEP
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
BreakerAC104.71 %255.0B267.01
79.94

Details for AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line l/o AEP_P4_#9758_05LEMASTER 138_A1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.71 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:267.01
MW Contribution:
79.94
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.68 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:266.93
MW Contribution:
79.94
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
Solar/Wind Harmer
28.367
970879AG2-548 GEN
Solar/Wind Harmer
51.576
971073AG2-665 GEN
Solar/Wind Harmer
28.367
971073AG2-665 GEN
Solar/Wind Harmer
51.576
938711AE1-093 GEN
50/50
41.97
NYPJM->LTFIMP_NY
CLTF
0.039
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.184
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line l/o AEP_P4_#11182_05LEMASTER 138_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.71 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:267.01
MW Contribution:
79.94
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.68 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:266.93
MW Contribution:
79.94
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
Solar/Wind Harmer
28.367
970879AG2-548 GEN
Solar/Wind Harmer
51.576
971073AG2-665 GEN
Solar/Wind Harmer
28.367
971073AG2-665 GEN
Solar/Wind Harmer
51.576
938711AE1-093 GEN
50/50
41.97
NYPJM->LTFIMP_NY
CLTF
0.039
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.184
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'AEP_P4_#9758_05LEMASTER 138_A1_SRT-A'
 OPEN BRANCH FROM BUS 242812 TO BUS 244283 CKT Z1   /*05MINERAL8   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 244283 CKT 1    /*05BOLINSMLSS 138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 246684 CKT Z1   /*05BOLINSMLSS 138.0 - 05BOLINS ML8 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 247791 CKT 1    /*05BOLINSMLSS 138.0 - 05ELK        138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244283 CKT 1    /*05LEMASTER   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244569 CKT Z1   /*05LEMASTER   138.0 - 05LEMAST_CAP 138.0
END
CONTINGENCY 'AEP_P4_#11182_05LEMASTER 138_A_SRT-A'
 OPEN BRANCH FROM BUS 242812 TO BUS 244283 CKT Z1   /*05MINERAL8   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 244283 CKT 1    /*05BOLINSMLSS 138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 246684 CKT Z1   /*05BOLINSMLSS 138.0 - 05BOLINS ML8 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 247791 CKT 1    /*05BOLINSMLSS 138.0 - 05ELK        138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244283 CKT 1    /*05LEMASTER   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 247097 CKT Z1   /*05LEMASTER   138.0 - 05LEMASTERT1 138.0
 REMOVE LOAD D1 FROM BUS 247097                     /*05LEMASTERT1 138.0
END
970878 to 243492 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-548 and AG2-665 in PJM Transition Cycle 2, Cluster 25 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 25 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 25 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

Cluster 25 projects were dispatched for stability analysis according to the following scenarios:

       a)       Scenario 1: AG2-548 and AG2-665 dispatched at full MFO injection at the POI with PV MW contribution maxed out and no/reduced MW contribution from BESS.

       b)       Scenario 2: AG2-548 and AG2-665 dispatched at full MFO injection at the POI with BESS MW contribution maxed out, and no/reduced PV MW injection.

       c)       Scenario 3: AG2-548 and AG2-665 dispatched at full MFO injection at the POI with PV and BESS MW contribution proportional to their capacity.

       d)       Scenario 4: AG2-548 and AG2-665 dispatched to full capacity with PV and BESS MW injection maxed out.

 

This report describes a dynamic simulation analysis of TC2 Cluster 25 for dispatch Scenario 3 as part of the overall system impact study.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 25 projects have been dispatched online at maximum power output, with 1.0 pu voltage at the terminal bus.

 

Transition Cycle 2 cluster 25 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2).

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 cluster 25 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 peak load case:

       a)       Cluster 25 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 25 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

The IPCMD and IQCMD states in the REGCA1 models of AG2-548 showed erratic behavior for some contingencies in which AG2-548 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

The IPCMD and IQCMD states in the REGCA1 models of AG2-665 showed erratic behavior for some contingencies in which AG2-665 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 25 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-548

Solar/Battery

AEP

80

Corwin – Elk 138 kV

AG2-665

Solar/Battery

AEP

80

Corwin – Elk 138 kV

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AG2-665 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-150Grassy Falls 138kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVEngineering & Procurement
AC1-214Crescent RidgeIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-029Circleville 138kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-176Jay 138 kVIn Service
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-093Elk 138 kVSuspended
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-143Marion County 161 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-089Pennville-Adams 138 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVUnder Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-342Woodstock 69 kVSuspended
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-038Sewellton Jct-Webbs Crossroads 69 kVUnder Construction
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-090Kincaid-PanaEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVWithdrawn
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVUnder Construction
AG1-017Jay 138 kVIn Service
AG1-047Jay 138 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-471Up Church-Wayne County 69 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-508Point Lookout 69 kVWithdrawn
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-424Summersville - Magnolia 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-348Pound 34.5 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-073Yankee 12.5kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-665 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
AEPn9750.0AG2-548 TP 138.0 kV to 05CORWIN 138.0 kV ckt 1 - Replace EquipmentCost Allocated$150,000N/A
AEPb4000.252Replace the wave trap and upgrade the relay at Joshua Falls 765kV substationContingent$0N/A
AEPb4000.251Replace the wave trap and upgrade the relay at Cloverdale 765kV substationContingent$0N/A
Grand Total:$150,000

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9750.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9750.0 / AEP-TC2-18699
Title
AG2-548 TP 138.0 kV to 05CORWIN 138.0 kV ckt 1 - Replace Equipment
Description
At Corwin station replace the following equipment: 795 KCM AAC 37-Str, 795 KCM AAC, 37-Str (2i), 795 KCM AAC 37-Str (5i), 795 KCM AAC 37-Str. PH-A
Total Cost ($USD)
$300,000
Discounted Total Cost ($USD)
$300,000
Allocated Cost ($USD)
$150,000
Time Estimate
6 to 12 Months

Contributor

FacilityContingency
05CORWIN-AG2-548 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A287.0 MVA
(All)B337.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-548 ⧉ New AG2-548 swyd (Corwin -Elk 138 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-548, AG2-665
79.9 MW50.0%$150,000
AG2-665 ⧉ New AG2-548 swyd (Corwin -Elk 138 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-548, AG2-665
79.9 MW50.0%$150,000

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9769.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9769.0 / AEP-TC2-19070
Title
05CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBs
Description
Upgrade/replace Cloverdale 765 kV, 4000 A CBs "CC" and "CC2" to 5000 A
Total Cost ($USD)
$25,000,000
Discounted Total Cost ($USD)
$25,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-665 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-665 could receive cost allocation. Although AG2-665 may not presently have cost responsibility for this upgrade, AG2-665 is a potential Aggregate Pool Contributor.

FacilityContingency
05CLOVRD-05CLOVRD_RJA 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-665 may not presently have cost responsibility for this upgrade, AG2-665 may need this upgrade in-service to be deliverable to the PJM system. If AG2-665 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-665 may not presently have cost responsibility for this upgrade, AG2-665 may need this upgrade in-service to be deliverable to the PJM system. If AG2-665 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: n9763.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9763.0 / AEP-TC2-19060
Title
05J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace Wavetraps
Description
Replace wave trap on 765 kV Cloverdale line. Replace/upgrade CB's B and B2 with 5000A CBs.
Total Cost ($USD)
$3,300,000
Discounted Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-665 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-665 could receive cost allocation. Although AG2-665 may not presently have cost responsibility for this upgrade, AG2-665 is a potential Aggregate Pool Contributor.

FacilityContingency
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: n9759.0
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
n9759.0 / OVEC-TC2-19030
Title
06KYGER 345.0 kV to 05SPORN 345.0 kV ckt 1 - Replace Equipment
Description
Sag study Sporn - Kyger Creek line and replace section #25 OVEC element conductor 12.51 Miles At Sporn replace the following equipment: 2 - 2000 KCM AAC, 91-Str., AA1S1, AA1S2, AAS1, AAS2, KYGER CREEK #1 - PH A, KYGER CREEK #1 - PH B At Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB
Total Cost ($USD)
$38,180,000
Discounted Total Cost ($USD)
$38,180,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-665 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-665 could receive cost allocation. Although AG2-665 may not presently have cost responsibility for this upgrade, AG2-665 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1942.0 MVA
(All)B2837.0 MVA
LLA1942.0 MVA
LLB2837.0 MVA

System Reinforcement: n9753.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9753.0 / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Discounted Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-665 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-665 could receive cost allocation. Although AG2-665 may not presently have cost responsibility for this upgrade, AG2-665 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1944.0 MVA
(All)B2825.0 MVA
(All)C2468.0 MVA

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Apr 03 2028

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-665


AG2-665 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-665 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-665 One Line Diagram

AG2-665 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.