AH1-133 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:37

Saltville - Tazewell 138 kV

29.4 MW Capacity / 70.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Hermes Solar LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $18,227,186 $16,823,587 = 1.08 AND ( $18,227,186 - $16,823,587 ) 70.0 = $20,051 per MW

General

The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Tazewell County, Virginia. The installed facilities will have a total capability of 70.0 MW with 29.4 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-133
Project Name:
Saltville - Tazewell 138 kV
Project Developer Name:
Hermes Solar LLC
State:
Virginia
County:
Tazewell
Transmission Owner:
American Electric Power
MFO:
70.0
MWE:
70.0
MWC:
29.4
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-133 will interconnect on the American Electric Power transmission system by tapping the Saltville - Tazewell 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-133 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-133Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$126,981$0$0
Other Scope$750,157$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$15,618,380$15,618,380$15,618,380
Network Upgrades$2,608,806$2,608,806$2,608,806
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$19,104,324$18,227,186$18,227,186

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-133

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-133
Project ID: AH1-133
20% of cost allocation for Phase II Network Upgrades:(A) $3,645,437
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $1,682,359
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $1,963,078
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Relay settings adjustments to the neighboring Saltville & Tazewell 138 kV stations

$134,274$36,009$85,161$22,838$278,282$278,282
(Pending)

SALTVILLE - TAZEWELL 138 kV line will be cut and looped into the new interconnection substation.

$1,173,377$645,520$332,558$179,069$2,330,524$2,330,524
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the AH1-133 New 138 kV Station.

$372,255$211,684$106,855$59,363$750,157$750,157
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Appalachian Power Company will install 1 mile of 144 count all dielectric self supporting (ADSS) fiber-optic cable. Appalachian Power Company will install 1 mile of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable. Appalachian Power Company will install one (1) new 1101 router at the AH1-133 New Station 138 kV Station. Appalachian Power Company will install one (1) new 8340 router at the AH1-133 New Station 138 kV Station.

$576,141$181,045$202,086$62,618$1,021,890$1,021,890
(Pending)

A new breaker and a half substation (initially populated with 3 breakers and operated as a ring bus), AH1-133 New Station (name TBD) 138 kV, will be constructed along the SALTVILLE - TAZEWELL 138 kV transmission line to interconnect the project with the APCO transmission system. Appalachian Power Company will construct a new 138 kV breaker and a half station, to be operated as a three (3) circuit breaker ring bus, initially expandable to six (6) circuit breakers. This typical arrangement is planned to be designed to accommodate 3000A of continuous current. Installation of (3) 138KV RCVTs with (1) three-phase 138KV RCVT structures & foundations. Installation of two 2 wavetrap. Appalachian Power Company will remove one 1 steel latice structure in the SALTVILLE - TAZEWELL Right of Way. 2 mile of gravel access road. Installation of three 3 breaker control at the AH1-133 New Station 138 kV Station. Installation of Bus Differential Protection at the AH1-133 New Station 138 kV Station. Replacement of the existing control house with a new 16 by 18 foot control house. Installation of DCB Line Protection at the AH1-133 New Station 138 kV Station. Appalachian Power Company will transition existing OPGW fiber-optic shield wire from the cut-in dead ends into the AH1-133 New Station 138 kV Station. Appalachian Power Company will install 1 mile of 144 count all dielectric self supporting (ADSS) fiber-optic cable. Appalachian Power Company will install 1 mile of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable. Appalachian Power Company will install one (1) new 1101 router at the AH1-133 New Station 138 kV Station. Appalachian Power Company will install one (1) new 8340 router at the AH1-133 New Station 138 kV Station.

$7,850,046$3,724,197$1,945,998$1,076,249$14,596,490$14,596,490
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

A 138 kV dead-end structure and foundation outside the fence of the Interconnection Substation, to terminate the Project Developers generator lead line. Line conductor from the dead-end structure to the bus position in the switchyard of the interconnection substation.

$99,593$7,114$18,922$1,352$126,981$126,981
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Relay settings adjustments to the neighboring Saltville & Tazewell 138 kV stations

$134,274$36,009$85,161$22,838$278,282$278,282
(Pending)

SALTVILLE - TAZEWELL 138 kV line will be cut and looped into the new interconnection substation.

$1,173,377$645,520$332,558$179,069$2,330,524$2,330,524
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight of developer design and construction of new interconnection substation

$244,623$83,373$182,825$62,310$573,131$573,131
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the AH1-133 New 138 kV Station.

$372,255$211,684$106,855$59,363$750,157$750,157
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$19,104,324$19,104,324
Developer Build Option$3,932,094$3,932,094

Based on the scope of work for the Interconnection Facilities, it is expected to take 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-133 was evaluated as a 70.0 MW (29.4 MW Capacity) injection in the AEP area.

AH1-133 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 70.0 MW (70.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05ATKINS-05RURALR 138.0 kV Ckt 1 line
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
BreakerAC105.05 %251.0B263.69
3.18
GD2AEP
05BROADF-05BROADX 138.0 kV Ckt ZB line
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
BreakerAC105.1 %278.0B292.19
3.18
GD2AEP
05BROADX-05SMYTH 138.0 kV Ckt 1 line
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
BreakerAC105.23 %278.0B292.55
3.18
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
10.06
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
10.06
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
10.06
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
10.06
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.16
10.06
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC102.09 %5523.0B5638.63
5.79
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC102.08 %5523.0B5637.94
5.79
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC300.71 %1180.0B3548.35
7.14
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC300.71 %1180.0B3548.35
7.14
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.19
7.14
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.19
7.14
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.09
7.14
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC286.57 %1180.0B3381.47
4.11
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC286.54 %1180.0B3381.22
4.11
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC253.24 %1180.0B2988.23
6.74
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17030___SRT-A
TowerAC241.49 %1180.0B2849.63
6.65
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
BusAC237.35 %1180.0B2800.7
6.43
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
BusAC236.49 %1180.0B2790.61
6.47
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC222.44 %1180.0A2624.74
3.7
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
10.06
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
10.06
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
10.06
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
10.06
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.16
10.06
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC123.36 %4571.0B5638.63
5.79
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC123.34 %4571.0B5637.94
5.79
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
BreakerAC117.51 %296.0B347.84
20.64
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
BreakerAC110.63 %296.0B327.47
20.66
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P4_#2916_05J.FERR 765_A_SRT-A
BreakerAC110.35 %296.0B326.65
20.66
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P1-2_#2915_4_SRT-A
SingleAC107.09 %296.0B316.99
11.89

Details for 05ATKINS-05RURALR 138.0 kV Ckt 1 line l/o AEP_P4_#3098_05BROADF 765_Q1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05ATKINS-05RURALR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:251.0 MVA
Rating Type:B
MVA to Mitigate:263.69
MW Contribution:
3.18
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05ATKINS-05RURALR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:95.89 %
Rating:251.0 MVA
Rating Type:B
MVA to Mitigate:240.68
MW Contribution:
3.13
Bus #Bus NameTypeMW Contribution
958121AF2-106 GEN
Solar/Wind Helper
0.833
960911AF2-382 GEN
Solar/Wind Harmer
3.536
24735205WLF2G2
Adder
2.649
24734805WLF1G4
Adder
3.219
24735105WLF2G1
Adder
2.649
24728205BUCHG1
Adder
2.603
24728305BUCHG2
Adder
2.603
270214AC2-123 GEN
Solar/Wind Helper
0.523
24734705WLF1G3
Adder
3.219
24734905WLF1G5
Adder
3.219
970563AG2-360 GEN
50/50
29.673
971313AH1-133 GEN
Solar/Wind Harmer
3.18
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.428
LAGNLTFEXP_LAGN->PJM
CLTF
1.824
NYPJM->LTFIMP_NY
CLTF
0.185
LGEELTFEXP_LGEE->PJM
CLTF
0.607
TVALTFEXP_TVA->PJM
CLTF
1.158
WECLTFEXP_WEC->PJM
CLTF
0.248
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.326
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.909
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.164
MECLTFEXP_MEC->PJM
CLTF
1.228
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for 05BROADF-05BROADX 138.0 kV Ckt ZB line l/o AEP_P4_#3098_05BROADF 765_Q1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05BROADF-05BROADX 138.0 kV Ckt ZB line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.1 %
Rating:278.0 MVA
Rating Type:B
MVA to Mitigate:292.19
MW Contribution:
3.18
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05BROADF-05BROADX 138.0 kV Ckt ZB line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:96.78 %
Rating:278.0 MVA
Rating Type:B
MVA to Mitigate:269.05
MW Contribution:
3.12
Bus #Bus NameTypeMW Contribution
958121AF2-106 GEN
Solar/Wind Helper
0.832
960911AF2-382 GEN
Solar/Wind Harmer
3.532
24735205WLF2G2
Adder
2.646
24734805WLF1G4
Adder
3.215
24735105WLF2G1
Adder
2.646
24728205BUCHG1
Adder
2.6
24728305BUCHG2
Adder
2.6
270214AC2-123 GEN
Solar/Wind Helper
0.522
24734705WLF1G3
Adder
3.215
24734905WLF1G5
Adder
3.215
970563AG2-360 GEN
50/50
29.636
971313AH1-133 GEN
Solar/Wind Harmer
3.176
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.413
LAGNLTFEXP_LAGN->PJM
CLTF
1.822
NYPJM->LTFIMP_NY
CLTF
0.185
LGEELTFEXP_LGEE->PJM
CLTF
0.606
TVALTFEXP_TVA->PJM
CLTF
1.157
WECLTFEXP_WEC->PJM
CLTF
0.248
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.326
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.898
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.159
MECLTFEXP_MEC->PJM
CLTF
1.226
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for 05BROADX-05SMYTH 138.0 kV Ckt 1 line l/o AEP_P4_#3098_05BROADF 765_Q1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05BROADX-05SMYTH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.23 %
Rating:278.0 MVA
Rating Type:B
MVA to Mitigate:292.55
MW Contribution:
3.18
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05BROADX-05SMYTH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:96.9 %
Rating:278.0 MVA
Rating Type:B
MVA to Mitigate:269.39
MW Contribution:
3.13
Bus #Bus NameTypeMW Contribution
958121AF2-106 GEN
Solar/Wind Helper
0.833
960911AF2-382 GEN
Solar/Wind Harmer
3.536
24735205WLF2G2
Adder
2.649
24734805WLF1G4
Adder
3.219
24735105WLF2G1
Adder
2.649
24728205BUCHG1
Adder
2.603
24728305BUCHG2
Adder
2.603
270214AC2-123 GEN
Solar/Wind Helper
0.523
24734705WLF1G3
Adder
3.219
24734905WLF1G5
Adder
3.219
970563AG2-360 GEN
50/50
29.673
971313AH1-133 GEN
Solar/Wind Harmer
3.18
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.428
LAGNLTFEXP_LAGN->PJM
CLTF
1.824
NYPJM->LTFIMP_NY
CLTF
0.185
LGEELTFEXP_LGEE->PJM
CLTF
0.607
TVALTFEXP_TVA->PJM
CLTF
1.158
WECLTFEXP_WEC->PJM
CLTF
0.248
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.326
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.909
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.164
MECLTFEXP_MEC->PJM
CLTF
1.228
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
10.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
238170AE2-226 GEN2
Solar/Wind Helper
0.563
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
10.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24735205WLF2G2
50/50
10.407
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
10.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
10.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
316316AC1-027 C
Solar/Wind Helper
0.36
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
10.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
971461AH1-227 GEN
Solar/Wind Harmer
8.01
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
316072AD1-144
Solar/Wind Helper
0.257
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
316185AD1-033 GEN
Solar/Wind Helper
1.07
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
5.79
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971225AH1-072 GEN
Solar/Wind Harmer
2.179
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
971227AH1-073 GEN
Solar/Wind Harmer
2.179
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
5.79
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.35
MW Contribution:
7.14
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
TVALTFEXP_TVA->PJM
CLTF
7.636
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.35
MW Contribution:
7.14
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
TVALTFEXP_TVA->PJM
CLTF
7.636
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.19
MW Contribution:
7.14
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
TVALTFEXP_TVA->PJM
CLTF
7.636
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.19
MW Contribution:
7.14
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
TVALTFEXP_TVA->PJM
CLTF
7.636
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.09
MW Contribution:
7.14
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
3142946ENON
Solar/Wind Helper
0.023
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
TVALTFEXP_TVA->PJM
CLTF
7.636
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:286.57 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3381.47
MW Contribution:
4.11
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
5.833
972103AH1-617 GEN
Solar/Wind Harmer
13.552
270030AE2-140 GEN
Solar/Wind Harmer
13.376
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
6.792
971461AH1-227 GEN
Solar/Wind Harmer
3.708
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
1.529
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
6.442
270399AC1-101 GEN
Solar/Wind Harmer
2.148
971981AH1-535 GEN
Solar/Wind Harmer
4.373
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
971329AH1-144 GEN
Solar/Wind Harmer
4.594
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
2.148
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
14.993
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
3.974
970913AG2-568 GEN
Solar/Wind Harmer
5.608
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
9.797
944971AF1-162 GEN
Solar/Wind Harmer
6.718
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
0.719
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
4.106
971061AG2-657 GEN
Solar/Wind Harmer
3.871
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
970281AG2-184 GEN
Solar/Wind Harmer
14.229
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
270583AD2-179 GEN
Solar/Wind Harmer
9.711
971225AH1-072 GEN
Solar/Wind Harmer
1.446
971227AH1-073 GEN
Solar/Wind Harmer
1.446
24723105RIVRG2
Adder
16.666
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:286.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3381.22
MW Contribution:
4.11
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
6.792
971461AH1-227 GEN
Solar/Wind Harmer
3.708
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
1.529
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
6.442
270399AC1-101 GEN
Solar/Wind Harmer
2.148
971981AH1-535 GEN
Solar/Wind Harmer
4.373
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
971329AH1-144 GEN
Solar/Wind Harmer
4.594
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
2.148
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
14.993
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
3.974
970913AG2-568 GEN
Solar/Wind Harmer
5.608
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
9.797
944971AF1-162 GEN
Solar/Wind Harmer
6.718
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
960911AF2-382 GEN
Solar/Wind Harmer
5.833
972103AH1-617 GEN
Solar/Wind Harmer
13.552
270030AE2-140 GEN
Solar/Wind Harmer
13.376
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
0.719
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
4.106
971061AG2-657 GEN
Solar/Wind Harmer
3.871
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
970281AG2-184 GEN
Solar/Wind Harmer
14.229
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
270583AD2-179 GEN
Solar/Wind Harmer
9.711
971225AH1-072 GEN
Solar/Wind Harmer
1.446
971227AH1-073 GEN
Solar/Wind Harmer
1.446
24723105RIVRG2
Adder
16.666
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:253.24 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2988.23
MW Contribution:
6.74
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270214AC2-123 GEN
Solar/Wind Harmer
3.383
270583AD2-179 GEN
Solar/Wind Harmer
13.976
971225AH1-072 GEN
Solar/Wind Harmer
1.896
971227AH1-073 GEN
Solar/Wind Harmer
1.896
971341AH1-150 GEN
Solar/Wind Harmer
10.981
971343AH1-151 GEN
Solar/Wind Harmer
10.981
970563AG2-360 GEN
50/50
33.924
24689505VACITY
50/50
3.969
274729ELWOOD EC;1P
Adder
8.897
3143526WINTERP
Solar/Wind Helper
1.209
964211AG1-282 GEN
Solar/Wind Helper
0.301
971687AH1-348 GEN
Solar/Wind Harmer
0.942
316075AC2-137 C
Solar/Wind Helper
0.351
316077AC2-138 C
Solar/Wind Helper
0.211
24290605CLAY-1
50/50
0.169
24728305BUCHG2
50/50
5.133
274732ELWOOD EC;7P
Adder
8.897
3141906WESTMOR
Solar/Wind Helper
0.09
24290705CLAY-2
50/50
0.169
3151861LOWMORA
Adder
1.295
971403AH1-188 GEN
Solar/Wind Harmer
12.423
959081AF2-199 GEN
Solar/Wind Harmer
5.491
971067AG2-660 GEN
Solar/Wind Harmer
1.277
270494AE1-108_GEN
Solar/Wind Helper
3.531
316223AC1-118
Solar/Wind Helper
0.343
24728205BUCHG1
50/50
5.133
971277AH1-098 GEN
Solar/Wind Harmer
5.61
970913AG2-568 GEN
Solar/Wind Harmer
6.125
316045AC1-158 PL2
Solar/Wind Helper
4.379
966871AG1-558 GEN
Solar/Wind Helper
0.321
316006AB2-029 C
Solar/Wind Helper
0.107
3148463FAIRFLD
Solar/Wind Harmer
-0.014
970281AG2-184 GEN
Solar/Wind Harmer
18.318
274735ELWOOD EC;4P
Adder
8.897
315651AD1-115 GEN
Solar/Wind Helper
0.755
971881AH1-461 GEN
50/50
10.678
943031AE2-326 GEN
Solar/Wind Harmer
5.324
960911AF2-382 GEN
Solar/Wind Harmer
7.746
270030AE2-140 GEN
Solar/Wind Harmer
19.126
972103AH1-617 GEN
Solar/Wind Harmer
17.445
959091AF2-200 GEN
Solar/Wind Harmer
10.981
274734ELWOOD EC;8P
Adder
8.897
274736ELWOOD EC;9P
Adder
8.897
274676JOLIET 29;8U
Adder
16.007
316447AC1-158 HLD
Solar/Wind Helper
3.012
3142416OLDCHRC
Solar/Wind Helper
0.613
3142416OLDCHRC
Solar/Wind Helper
0.235
315975AC1-164 GENB
Solar/Wind Helper
0.087
3142433PROV 92
Solar/Wind Helper
0.892
247619Y1-049
50/50
0.036
316450AC1-158 RIC
Solar/Wind Helper
0.365
970823AG2-518 GEN
50/50
5.477
24290605CLAY-1
50/50
0.169
958121AF2-106 GEN
Solar/Wind Harmer
6.343
270346AE1-212 GEN
Solar/Wind Harmer
9.332
971461AH1-227 GEN
Solar/Wind Harmer
4.864
274730ELWOOD EC;6P
Adder
8.897
316044AC1-158 PL1
Solar/Wind Helper
1.369
3143226MDLTHAN
Solar/Wind Helper
0.233
3142543TWELFTH
Solar/Wind Helper
0.022
316404AE1-155 C
Solar/Wind Helper
1.907
24290705CLAY-2
50/50
0.169
24415905BUCK
50/50
0.025
316337AD2-073 GEN
Solar/Wind Helper
0.341
3141726DUNNSVL
Solar/Wind Helper
0.895
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
6.118
270336AE1-100 GEN
Solar/Wind Harmer
1.761
943811AF1-049 GEN
Solar/Wind Harmer
3.46
957471AF2-041 GEN
Solar/Wind Harmer
16.472
274676JOLIET 29;8U
Adder
16.6
966881AG1-559 GEN
Solar/Wind Helper
0.328
316473AC1-191 GEN
Solar/Wind Helper
1.456
3142946ENON
Solar/Wind Helper
0.075
24734805WLF1G4
50/50
6.262
24735105WLF2G1
50/50
6.118
971329AH1-144 GEN
Solar/Wind Harmer
7.928
3151861LOWMORA
Adder
1.244
274731ELWOOD EC;2P
Adder
8.897
274733ELWOOD EC;3P
Adder
8.897
316164AC1-076 GEN
Solar/Wind Helper
1.11
316233AE1-074 FULL
Solar/Wind Helper
0.355
3141813NORNECK
Solar/Wind Helper
0.223
24416005BYLLESBY
50/50
0.023
24734705WLF1G3
50/50
6.262
24734905WLF1G5
50/50
6.262
966391AG1-508 GEN
Solar/Wind Harmer
4.809
971331AH1-145 GEN
Solar/Wind Harmer
12.412
270069AE2-166 C O1
Solar/Wind Harmer
9.245
315616AA1-038_C
Solar/Wind Harmer
2.777
3151881LOWMORC
Adder
1.285
3151881LOWMORC
Adder
1.264
971981AH1-535 GEN
Solar/Wind Harmer
8.769
971171AH1-044 GEN
Solar/Wind Harmer
10.981
274675JOLIET 29;7U
Adder
16.6
274675JOLIET 29;7U
Adder
16.007
3143873LANEXA
Solar/Wind Helper
0.134
971543AH1-269 GEN
50/50
8.242
971313AH1-133 GEN
Solar/Wind Harmer
6.737
274728ELWOOD EC;5P
Adder
8.897
316468AD1-105 GEN
Solar/Wind Helper
1.134
316312AB1-027
Solar/Wind Helper
0.45
3143526WINTERP
Solar/Wind Helper
1.209
315976AC1-164 GENA
Solar/Wind Helper
2.937
316169AC1-164_GENC
Solar/Wind Helper
2.537
3142946ENON
Solar/Wind Helper
0.022
CPLELTFEXP_CPLE->PJM
CLTF
2.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
83.049
LAGNLTFEXP_LAGN->PJM
CLTF
12.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.088
NYPJM->LTFIMP_NY
CLTF
2.107
LGEELTFEXP_LGEE->PJM
CLTF
4.253
WECLTFEXP_WEC->PJM
CLTF
2.106
TVALTFEXP_TVA->PJM
CLTF
6.888
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.014
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.396
MECLTFEXP_MEC->PJM
CLTF
9.684
SIGELTFEXP_SIGE->PJM
CLTF
0.319

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17030___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17030___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:241.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2849.63
MW Contribution:
6.65
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
33.343
24689505VACITY
50/50
3.901
274729ELWOOD EC;1P
Adder
8.783
3147312GRETNA
Solar/Wind Helper
0.273
24290005CRG1L
50/50
0.657
971687AH1-348 GEN
Solar/Wind Harmer
0.926
3147312GRETNA
Solar/Wind Helper
0.068
316075AC2-137 C
Solar/Wind Helper
0.344
24290605CLAY-1
50/50
0.175
24728305BUCHG2
50/50
5.054
274732ELWOOD EC;7P
Adder
8.783
316197AC1-042 GEN
Solar/Wind Helper
0.322
24290705CLAY-2
50/50
0.175
971403AH1-188 GEN
Solar/Wind Harmer
12.255
959081AF2-199 GEN
Solar/Wind Harmer
5.417
971067AG2-660 GEN
Solar/Wind Harmer
1.26
270494AE1-108_GEN
Solar/Wind Helper
4.186
270173AC1-122 GEN
Solar/Wind Helper
2.053
24728205BUCHG1
50/50
5.054
971277AH1-098 GEN
Solar/Wind Harmer
5.569
970913AG2-568 GEN
Solar/Wind Harmer
6.098
316045AC1-158 PL2
Solar/Wind Helper
4.285
966871AG1-558 GEN
Solar/Wind Helper
0.314
274735ELWOOD EC;4P
Adder
8.783
971881AH1-461 GEN
50/50
10.6
24290105CRG2H
50/50
0.806
943031AE2-326 GEN
Solar/Wind Harmer
5.244
960911AF2-382 GEN
Solar/Wind Harmer
7.628
270030AE2-140 GEN
Solar/Wind Harmer
18.948
959091AF2-200 GEN
Solar/Wind Harmer
10.834
274734ELWOOD EC;8P
Adder
8.783
274736ELWOOD EC;9P
Adder
8.783
274676JOLIET 29;8U
Adder
15.802
3147123OTTER R
Solar/Wind Helper
0.199
316447AC1-158 HLD
Solar/Wind Helper
2.947
3142416OLDCHRC
Solar/Wind Helper
0.599
3142416OLDCHRC
Solar/Wind Helper
0.23
315975AC1-164 GENB
Solar/Wind Helper
0.085
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.785
316450AC1-158 RIC
Solar/Wind Helper
0.357
970823AG2-518 GEN
50/50
5.724
24290605CLAY-1
50/50
0.175
958121AF2-106 GEN
Solar/Wind Harmer
6.537
270346AE1-212 GEN
Solar/Wind Harmer
9.433
971461AH1-227 GEN
Solar/Wind Harmer
4.785
274730ELWOOD EC;6P
Adder
8.783
316044AC1-158 PL1
Solar/Wind Helper
1.339
3143226MDLTHAN
Solar/Wind Helper
0.227
24290705CLAY-2
50/50
0.175
24415905BUCK
50/50
0.025
270205AE1-176
50/50
0.004
270336AE1-100 GEN
Solar/Wind Harmer
1.752
24735205WLF2G2
Adder
5.652
943811AF1-049 GEN
Solar/Wind Harmer
3.421
957471AF2-041 GEN
Solar/Wind Harmer
16.25
274676JOLIET 29;8U
Adder
16.387
966881AG1-559 GEN
Solar/Wind Helper
0.321
316473AC1-191 GEN
Solar/Wind Helper
1.424
971329AH1-144 GEN
Solar/Wind Harmer
8.141
24734805WLF1G4
Adder
5.791
24735105WLF2G1
Adder
5.652
274731ELWOOD EC;2P
Adder
8.783
274733ELWOOD EC;3P
Adder
8.783
316233AE1-074 FULL
Solar/Wind Helper
0.346
316164AC1-076 GEN
Solar/Wind Helper
1.072
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.774
971331AH1-145 GEN
Solar/Wind Harmer
12.745
270069AE2-166 C O1
Solar/Wind Harmer
9.341
24734705WLF1G3
Adder
5.791
24734905WLF1G5
Adder
5.791
971171AH1-044 GEN
Solar/Wind Harmer
10.834
274675JOLIET 29;7U
Adder
16.387
274675JOLIET 29;7U
Adder
15.801
3146802CHATHAM
Solar/Wind Helper
0.256
3143526WINTERP
Solar/Wind Helper
1.177
971543AH1-269 GEN
50/50
8.505
24290205CRG2L
50/50
0.675
971313AH1-133 GEN
Solar/Wind Harmer
6.653
274728ELWOOD EC;5P
Adder
8.783
316468AD1-105 GEN
Solar/Wind Helper
1.109
316312AB1-027
Solar/Wind Helper
0.44
3143526WINTERP
Solar/Wind Helper
1.177
270583AD2-179 GEN
Solar/Wind Harmer
14.401
270214AC2-123 GEN
Solar/Wind Harmer
3.332
971225AH1-072 GEN
Solar/Wind Harmer
1.865
971227AH1-073 GEN
Solar/Wind Harmer
1.865
971341AH1-150 GEN
Solar/Wind Harmer
10.834
971343AH1-151 GEN
Solar/Wind Harmer
10.834
315976AC1-164 GENA
Solar/Wind Helper
2.875
316169AC1-164_GENC
Solar/Wind Helper
2.483
CPLELTFEXP_CPLE->PJM
CLTF
1.827
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.488
LAGNLTFEXP_LAGN->PJM
CLTF
12.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.507
NYPJM->LTFIMP_NY
CLTF
2.036
LGEELTFEXP_LGEE->PJM
CLTF
4.19
TVALTFEXP_TVA->PJM
CLTF
6.738
WECLTFEXP_WEC->PJM
CLTF
2.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.022
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.871
MECLTFEXP_MEC->PJM
CLTF
9.533
SIGELTFEXP_SIGE->PJM
CLTF
0.315

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:237.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2800.7
MW Contribution:
6.43
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270214AC2-123 GEN
Solar/Wind Harmer
3.229
270583AD2-179 GEN
Solar/Wind Harmer
13.158
971225AH1-072 GEN
Solar/Wind Harmer
1.812
971227AH1-073 GEN
Solar/Wind Harmer
1.812
971341AH1-150 GEN
Solar/Wind Harmer
10.521
971343AH1-151 GEN
Solar/Wind Harmer
10.521
24416005BYLLESBY
50/50
0.022
24734705WLF1G3
50/50
5.986
24734905WLF1G5
50/50
5.986
966391AG1-508 GEN
Solar/Wind Harmer
4.579
971331AH1-145 GEN
Solar/Wind Harmer
11.701
270069AE2-166 C O1
Solar/Wind Harmer
8.726
971171AH1-044 GEN
Solar/Wind Harmer
10.521
274675JOLIET 29;7U
Adder
15.905
274675JOLIET 29;7U
Adder
15.337
970563AG2-360 GEN
50/50
32.411
24689505VACITY
50/50
3.793
274729ELWOOD EC;1P
Adder
8.525
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
971687AH1-348 GEN
Solar/Wind Harmer
0.9
3147312GRETNA
Solar/Wind Helper
0.046
24290605CLAY-1
50/50
0.159
24728305BUCHG2
50/50
4.902
274732ELWOOD EC;7P
Adder
8.525
316197AC1-042 GEN
Solar/Wind Helper
0.219
24290705CLAY-2
50/50
0.159
959081AF2-199 GEN
Solar/Wind Harmer
5.261
971067AG2-660 GEN
Solar/Wind Harmer
1.223
270494AE1-108_GEN
Solar/Wind Helper
3.291
24728205BUCHG1
50/50
4.902
971277AH1-098 GEN
Solar/Wind Harmer
5.342
316045AC1-158 PL2
Solar/Wind Helper
4.187
966871AG1-558 GEN
Solar/Wind Helper
0.305
274735ELWOOD EC;4P
Adder
8.525
971881AH1-461 GEN
50/50
10.173
943031AE2-326 GEN
Solar/Wind Harmer
5.082
960911AF2-382 GEN
Solar/Wind Harmer
7.399
270030AE2-140 GEN
Solar/Wind Harmer
18.085
959091AF2-200 GEN
Solar/Wind Harmer
10.521
274734ELWOOD EC;8P
Adder
8.525
274736ELWOOD EC;9P
Adder
8.525
274676JOLIET 29;8U
Adder
15.337
316447AC1-158 HLD
Solar/Wind Helper
2.88
3147123OTTER R
Solar/Wind Helper
0.137
3142416OLDCHRC
Solar/Wind Helper
0.582
3142416OLDCHRC
Solar/Wind Helper
0.223
247619Y1-049
50/50
0.034
316450AC1-158 RIC
Solar/Wind Helper
0.349
970823AG2-518 GEN
50/50
5.131
24290605CLAY-1
50/50
0.159
958121AF2-106 GEN
Solar/Wind Harmer
5.971
270346AE1-212 GEN
Solar/Wind Harmer
8.843
971461AH1-227 GEN
Solar/Wind Harmer
4.649
274730ELWOOD EC;6P
Adder
8.525
316044AC1-158 PL1
Solar/Wind Helper
1.309
24290705CLAY-2
50/50
0.159
24415905BUCK
50/50
0.024
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
5.85
270336AE1-100 GEN
Solar/Wind Harmer
1.667
943811AF1-049 GEN
Solar/Wind Harmer
3.27
957471AF2-041 GEN
Solar/Wind Harmer
15.782
274676JOLIET 29;8U
Adder
15.905
966881AG1-559 GEN
Solar/Wind Helper
0.312
316473AC1-191 GEN
Solar/Wind Helper
1.383
24734805WLF1G4
50/50
5.986
24735105WLF2G1
50/50
5.85
971329AH1-144 GEN
Solar/Wind Harmer
7.474
274731ELWOOD EC;2P
Adder
8.525
274733ELWOOD EC;3P
Adder
8.525
971543AH1-269 GEN
50/50
7.755
971313AH1-133 GEN
Solar/Wind Harmer
6.428
274728ELWOOD EC;5P
Adder
8.525
316468AD1-105 GEN
Solar/Wind Helper
1.079
316312AB1-027
Solar/Wind Helper
0.427
CPLELTFEXP_CPLE->PJM
CLTF
1.94
CBM West 2LTFEXP_CBM-W2->PJM
CBM
79.525
LAGNLTFEXP_LAGN->PJM
CLTF
12.384
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.49
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
4.072
WECLTFEXP_WEC->PJM
CLTF
2.017
TVALTFEXP_TVA->PJM
CLTF
6.594
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.805
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.311
MECLTFEXP_MEC->PJM
CLTF
9.276
SIGELTFEXP_SIGE->PJM
CLTF
0.306

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10265_05LEESVI 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:236.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2790.61
MW Contribution:
6.47
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270214AC2-123 GEN
Solar/Wind Harmer
3.25
270583AD2-179 GEN
Solar/Wind Harmer
13.324
971225AH1-072 GEN
Solar/Wind Harmer
1.824
971227AH1-073 GEN
Solar/Wind Harmer
1.824
971341AH1-150 GEN
Solar/Wind Harmer
10.59
971343AH1-151 GEN
Solar/Wind Harmer
10.59
24416005BYLLESBY
50/50
0.022
24734705WLF1G3
50/50
6.023
24734905WLF1G5
50/50
6.023
966391AG1-508 GEN
Solar/Wind Harmer
4.619
971331AH1-145 GEN
Solar/Wind Harmer
11.838
270069AE2-166 C O1
Solar/Wind Harmer
9.063
971171AH1-044 GEN
Solar/Wind Harmer
10.59
970563AG2-360 GEN
50/50
32.611
24689505VACITY
50/50
3.816
274729ELWOOD EC;1P
Adder
8.581
3147312GRETNA
Solar/Wind Helper
0.331
3146802CHATHAM
Solar/Wind Helper
0.31
971687AH1-348 GEN
Solar/Wind Harmer
0.906
3147312GRETNA
Solar/Wind Helper
0.083
316123AC1-075 GEN
Solar/Wind Helper
1.523
24290605CLAY-1
50/50
0.161
24728305BUCHG2
50/50
4.933
274732ELWOOD EC;7P
Adder
8.58
316197AC1-042 GEN
Solar/Wind Helper
0.39
24290705CLAY-2
50/50
0.161
959081AF2-199 GEN
Solar/Wind Harmer
5.295
971067AG2-660 GEN
Solar/Wind Harmer
1.231
270494AE1-108_GEN
Solar/Wind Helper
3.421
24728205BUCHG1
50/50
4.933
971277AH1-098 GEN
Solar/Wind Harmer
5.391
970913AG2-568 GEN
Solar/Wind Harmer
5.873
316045AC1-158 PL2
Solar/Wind Helper
4.21
966871AG1-558 GEN
Solar/Wind Helper
0.308
274735ELWOOD EC;4P
Adder
8.581
971881AH1-461 GEN
50/50
10.248
943031AE2-326 GEN
Solar/Wind Harmer
5.116
960911AF2-382 GEN
Solar/Wind Harmer
7.446
270030AE2-140 GEN
Solar/Wind Harmer
18.83
959091AF2-200 GEN
Solar/Wind Harmer
10.59
274734ELWOOD EC;8P
Adder
8.58
274736ELWOOD EC;9P
Adder
8.58
274676JOLIET 29;8U
Adder
15.437
3147123OTTER R
Solar/Wind Helper
0.234
316447AC1-158 HLD
Solar/Wind Helper
2.895
3142416OLDCHRC
Solar/Wind Helper
0.587
3142416OLDCHRC
Solar/Wind Helper
0.225
247619Y1-049
50/50
0.034
316450AC1-158 RIC
Solar/Wind Helper
0.351
970823AG2-518 GEN
50/50
5.201
24290605CLAY-1
50/50
0.161
958121AF2-106 GEN
Solar/Wind Harmer
6.047
270346AE1-212 GEN
Solar/Wind Harmer
8.928
971461AH1-227 GEN
Solar/Wind Harmer
4.678
274730ELWOOD EC;6P
Adder
8.58
316044AC1-158 PL1
Solar/Wind Helper
1.316
24290705CLAY-2
50/50
0.161
24415905BUCK
50/50
0.024
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
5.886
270336AE1-100 GEN
Solar/Wind Harmer
1.727
943811AF1-049 GEN
Solar/Wind Harmer
3.415
957471AF2-041 GEN
Solar/Wind Harmer
15.885
274676JOLIET 29;8U
Adder
16.009
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.394
24734805WLF1G4
50/50
6.023
24735105WLF2G1
50/50
5.886
971329AH1-144 GEN
Solar/Wind Harmer
7.561
274731ELWOOD EC;2P
Adder
8.581
274733ELWOOD EC;3P
Adder
8.581
274675JOLIET 29;7U
Adder
16.009
274675JOLIET 29;7U
Adder
15.437
971543AH1-269 GEN
50/50
7.854
971313AH1-133 GEN
Solar/Wind Harmer
6.472
274728ELWOOD EC;5P
Adder
8.58
316468AD1-105 GEN
Solar/Wind Helper
1.087
316312AB1-027
Solar/Wind Helper
0.431
CPLELTFEXP_CPLE->PJM
CLTF
1.968
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.048
LAGNLTFEXP_LAGN->PJM
CLTF
12.467
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.609
NYPJM->LTFIMP_NY
CLTF
2.015
LGEELTFEXP_LGEE->PJM
CLTF
4.098
TVALTFEXP_TVA->PJM
CLTF
6.637
WECLTFEXP_WEC->PJM
CLTF
2.031
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.47
MECLTFEXP_MEC->PJM
CLTF
9.336
SIGELTFEXP_SIGE->PJM
CLTF
0.308

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:222.44 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:2624.74
MW Contribution:
3.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
5.134
24290605CLAY-1
50/50
0.16
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
6.06
971461AH1-227 GEN
Solar/Wind Harmer
3.246
274730ELWOOD EC;6P
Adder
8.538
316044AC1-158 PL1
Solar/Wind Helper
1.308
24416005BYLLESBY
50/50
0.022
24734705WLF1G3
50/50
5.991
24734905WLF1G5
50/50
5.991
966391AG1-508 GEN
Solar/Wind Harmer
1.432
971331AH1-145 GEN
Solar/Wind Harmer
11.709
270069AE2-166 C O1
Solar/Wind Harmer
6.093
274675JOLIET 29;7U
Adder
15.93
274675JOLIET 29;7U
Adder
15.361
247619Y1-049
50/50
0.034
316450AC1-158 RIC
Solar/Wind Helper
0.349
24734805WLF1G4
50/50
5.991
24735105WLF2G1
50/50
5.855
971329AH1-144 GEN
Solar/Wind Harmer
4.303
274731ELWOOD EC;2P
Adder
8.538
274733ELWOOD EC;3P
Adder
8.538
24728205BUCHG1
50/50
4.906
971277AH1-098 GEN
Solar/Wind Harmer
3.729
316045AC1-158 PL2
Solar/Wind Helper
4.183
966871AG1-558 GEN
Solar/Wind Helper
0.305
24290705CLAY-2
50/50
0.16
270494AE1-108_GEN
Solar/Wind Helper
3.288
971881AH1-461 GEN
50/50
10.18
943031AE2-326 GEN
Solar/Wind Harmer
5.085
960911AF2-382 GEN
Solar/Wind Harmer
5.166
270030AE2-140 GEN
Solar/Wind Harmer
12.629
274734ELWOOD EC;8P
Adder
8.538
274736ELWOOD EC;9P
Adder
8.538
274676JOLIET 29;8U
Adder
15.361
316447AC1-158 HLD
Solar/Wind Helper
2.877
3147123OTTER R
Solar/Wind Helper
0.137
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.223
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
5.855
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
15.93
966881AG1-559 GEN
Solar/Wind Helper
0.312
316473AC1-191 GEN
Solar/Wind Helper
1.382
971687AH1-348 GEN
Solar/Wind Harmer
0.628
3147312GRETNA
Solar/Wind Helper
0.046
970563AG2-360 GEN
50/50
32.435
24689505VACITY
50/50
3.796
274729ELWOOD EC;1P
Adder
8.538
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
971543AH1-269 GEN
50/50
7.759
971313AH1-133 GEN
Solar/Wind Harmer
3.701
274728ELWOOD EC;5P
Adder
8.538
316468AD1-105 GEN
Solar/Wind Helper
1.078
274735ELWOOD EC;4P
Adder
8.538
270583AD2-179 GEN
Solar/Wind Harmer
9.185
971225AH1-072 GEN
Solar/Wind Harmer
1.266
971227AH1-073 GEN
Solar/Wind Harmer
1.266
24290605CLAY-1
50/50
0.16
24728305BUCHG2
50/50
4.906
274732ELWOOD EC;7P
Adder
8.538
316197AC1-042 GEN
Solar/Wind Helper
0.219
316312AB1-027
Solar/Wind Helper
0.427
24290705CLAY-2
50/50
0.16
24415905BUCK
50/50
0.024
CPLELTFEXP_CPLE->PJM
CLTF
1.948
CBM West 2LTFEXP_CBM-W2->PJM
CBM
79.632
LAGNLTFEXP_LAGN->PJM
CLTF
12.4
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.515
NYPJM->LTFIMP_NY
CLTF
2.001
LGEELTFEXP_LGEE->PJM
CLTF
4.077
TVALTFEXP_TVA->PJM
CLTF
6.602
WECLTFEXP_WEC->PJM
CLTF
2.02
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.921
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.342
MECLTFEXP_MEC->PJM
CLTF
9.289
SIGELTFEXP_SIGE->PJM
CLTF
0.306

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
10.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
10.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
10.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
10.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
10.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.36 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
5.79
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
5.79
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
TVALTFEXP_TVA->PJM
CLTF
12.171
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.51 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:347.84
MW Contribution:
20.64
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.35 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:329.6
MW Contribution:
20.57
Bus #Bus NameTypeMW Contribution
971461AH1-227 GEN
Solar/Wind Harmer
2.867
24290105CRG2H
50/50
0.716
24735205WLF2G2
Adder
3.651
24734805WLF1G4
Adder
4.417
24735105WLF2G1
Adder
3.651
971225AH1-072 GEN
Solar/Wind Harmer
1.118
971227AH1-073 GEN
Solar/Wind Harmer
1.118
24734705WLF1G3
Adder
4.417
24734905WLF1G5
Adder
4.417
24289905CRG1H
50/50
0.697
970563AG2-360 GEN
50/50
33.379
24689505VACITY
50/50
3.467
972273AH1-721 GEN
Adder
15.55
24290005CRG1L
50/50
0.584
971687AH1-348 GEN
Solar/Wind Harmer
0.543
24290205CRG2L
50/50
0.6
971313AH1-133 GEN
Solar/Wind Harmer
20.638
CPLELTFEXP_CPLE->PJM
CLTF
0.364
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.839
LAGNLTFEXP_LAGN->PJM
CLTF
2.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.433
NYPJM->LTFIMP_NY
CLTF
0.199
LGEELTFEXP_LGEE->PJM
CLTF
0.644
WECLTFEXP_WEC->PJM
CLTF
0.249
TVALTFEXP_TVA->PJM
CLTF
1.772
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.741
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.09
MECLTFEXP_MEC->PJM
CLTF
1.418
SIGELTFEXP_SIGE->PJM
CLTF
0.049

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P4_#14149_05BROADF 765_Q2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.63 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:327.47
MW Contribution:
20.66
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.33 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:296.98
MW Contribution:
20.62
Bus #Bus NameTypeMW Contribution
971461AH1-227 GEN
Solar/Wind Harmer
2.861
24290105CRG2H
50/50
0.714
24735205WLF2G2
Adder
3.603
24734805WLF1G4
Adder
4.382
24735105WLF2G1
Adder
3.603
971225AH1-072 GEN
Solar/Wind Harmer
1.115
971227AH1-073 GEN
Solar/Wind Harmer
1.115
24734705WLF1G3
Adder
4.382
24734905WLF1G5
Adder
4.382
24289905CRG1H
50/50
0.695
970563AG2-360 GEN
50/50
33.396
24689505VACITY
50/50
3.456
972273AH1-721 GEN
Adder
14.819
24290005CRG1L
50/50
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.542
24290205CRG2L
50/50
0.598
971313AH1-133 GEN
Solar/Wind Harmer
20.662
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.897
LAGNLTFEXP_LAGN->PJM
CLTF
2.473
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.74
NYPJM->LTFIMP_NY
CLTF
0.186
LGEELTFEXP_LGEE->PJM
CLTF
0.617
WECLTFEXP_WEC->PJM
CLTF
0.233
TVALTFEXP_TVA->PJM
CLTF
1.556
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.399
MECLTFEXP_MEC->PJM
CLTF
1.291
SIGELTFEXP_SIGE->PJM
CLTF
0.046

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P4_#2916_05J.FERR 765_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2916_05J.FERR 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.35 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:326.65
MW Contribution:
20.66
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2916_05J.FERR 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:99.96 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:295.89
MW Contribution:
20.61
Bus #Bus NameTypeMW Contribution
971461AH1-227 GEN
Solar/Wind Harmer
2.859
24290105CRG2H
50/50
0.714
24735205WLF2G2
Adder
3.602
24734805WLF1G4
Adder
4.38
24735105WLF2G1
Adder
3.602
971225AH1-072 GEN
Solar/Wind Harmer
1.115
971227AH1-073 GEN
Solar/Wind Harmer
1.115
24734705WLF1G3
Adder
4.38
24734905WLF1G5
Adder
4.38
24289905CRG1H
50/50
0.695
970563AG2-360 GEN
50/50
33.385
24689505VACITY
50/50
3.455
972273AH1-721 GEN
Adder
14.808
24290005CRG1L
50/50
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.541
24290205CRG2L
50/50
0.598
971313AH1-133 GEN
Solar/Wind Harmer
20.659
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.899
LAGNLTFEXP_LAGN->PJM
CLTF
2.477
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.779
NYPJM->LTFIMP_NY
CLTF
0.186
LGEELTFEXP_LGEE->PJM
CLTF
0.615
TVALTFEXP_TVA->PJM
CLTF
1.558
WECLTFEXP_WEC->PJM
CLTF
0.232
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.16
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.402
MECLTFEXP_MEC->PJM
CLTF
1.288
SIGELTFEXP_SIGE->PJM
CLTF
0.046

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P1-2_#2915_4_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#2915_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.09 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:316.99
MW Contribution:
11.89
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#2915_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:96.8 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:286.52
MW Contribution:
11.86
Bus #Bus NameTypeMW Contribution
24290105CRG2H
50/50
0.714
971461AH1-227 GEN
Solar/Wind Harmer
1.996
24734705WLF1G3
Adder
4.382
24734905WLF1G5
Adder
4.382
24289905CRG1H
50/50
0.695
24734805WLF1G4
Adder
4.382
24735105WLF2G1
Adder
3.603
24735205WLF2G2
Adder
3.603
24290005CRG1L
50/50
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.378
970563AG2-360 GEN
50/50
33.396
24689505VACITY
50/50
3.456
972273AH1-721 GEN
Adder
14.819
24290205CRG2L
50/50
0.598
971313AH1-133 GEN
Solar/Wind Harmer
11.888
971225AH1-072 GEN
Solar/Wind Harmer
0.778
971227AH1-073 GEN
Solar/Wind Harmer
0.778
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.897
LAGNLTFEXP_LAGN->PJM
CLTF
2.473
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.74
TVALTFEXP_TVA->PJM
CLTF
1.556
NYPJM->LTFIMP_NY
CLTF
0.186
LGEELTFEXP_LGEE->PJM
CLTF
0.617
WECLTFEXP_WEC->PJM
CLTF
0.233
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.399
MECLTFEXP_MEC->PJM
CLTF
1.291
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CONTINGENCY 'AEP_P4_#3098_05BROADF 765_Q1_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 1           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 2           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#17030___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
END
CONTINGENCY 'PECO_P2-2_PHILLIPS-BUS_SRT-A
 DISCONNECT BUS 213888   /*PHLISCT1      18.0
 DISCONNECT BUS 213889   /*PHLISCT2      18.0
 DISCONNECT BUS 213892   /*PHLISL87     230.0
END
CONTINGENCY 'AEP_P2-2_#10265_05LEESVI 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242701 TO BUS 242802 CKT 1   /*05LEESVI     138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 247284 CKT 1   /*05LEESVI     138.0 - 05LEESVG      13.8
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AEP_P4_#11112_05J.FERR 765_A1_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1    /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1    /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1    /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1    /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
CONTINGENCY 'AEP_P4_#14149_05BROADF 765_Q2_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
END
CONTINGENCY 'AEP_P4_#2916_05J.FERR 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242509 TO BUS 242545 CKT 1    /*05AXTON      765.0 - 05AXTONX     138.0
 OPEN BRANCH FROM BUS 242509 TO BUS 290609 CKT Z1   /*05AXTON      765.0 - 05AXTON_RJ   765.0
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290609 CKT 1    /*05J.FERR     765.0 - 05AXTON_RJ   765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242544 TO BUS 242545 CKT SR   /*05AXTON      138.0 - 05AXTONX     138.0
 OPEN BRANCH FROM BUS 242544 TO BUS 242545 CKT ZB   /*05AXTON      138.0 - 05AXTONX     138.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
END
CONTINGENCY 'AEP_P1-2_#2915_4_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
END
242542 to 242780 ckt 1
242566 to 242567 ckt ZB
242567 to 242803 ckt 1
290610 to 242512 ckt Z1
290614 to 242515 ckt 1
242514 to 290610 ckt 1
971312 to 242827 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.18 %2320.0B2486.65
4.58
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC104.78 %2320.0B2430.97
2.64
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
5.36
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC115.66 %3610.0B4175.28
9.35
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC115.4 %3610.0B4165.98
9.33
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC115.26 %3610.0B4160.96
9.32
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC114.94 %3610.0B4149.41
9.32
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC119.32 %5523.0B6590.12
8.78
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC117.27 %5523.0B6477.04
8.8
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC116.4 %5523.0B6428.58
5.06
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.72 %5523.0B6225.55
8.88
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC111.96 %5523.0B6183.32
9.36
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC109.18 %4558.0A4976.63
4.63
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.41 %5523.0B5987.66
10.2
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.46 %5523.0B5935.05
8.48
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.76 %5523.0B5896.19
5.87
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC105.86 %5523.0B5846.6
9.05
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC101.88 %5523.0B5626.94
9.12
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P1-2: LN 555_SRT-A
SingleAC112.06 %3220.44B3608.77
3.31
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC104.87 %3940.0C4131.96
6.5
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P1-2: LN 555_SRT-A
SingleAC111.74 %3220.44B3598.36
3.31
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC104.6 %3940.0C4121.29
6.5

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.18 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2486.65
MW Contribution:
4.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
Adder
3.63
24686505CER G6
Adder
4.748
339211AE2-254 GEN
Solar/Wind Harmer
0.852
3429241JKCT 3G
Adder
6.43
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276708O09 GEN2
Solar/Wind Harmer
1.676
276656WTG2_EQ
Solar/Wind Harmer
0.54
274766LEE CO EC;7U
Adder
4.297
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
3148013FISHERV
Solar/Wind Helper
0.287
3147666LOUISA
Solar/Wind Helper
0.335
3141906WESTMOR
Solar/Wind Helper
0.046
971687AH1-348 GEN
Solar/Wind Harmer
0.746
276621W2-048 GEN
Solar/Wind Harmer
2.987
25196008MFTGT1
Adder
0.654
25196808ZIMRHP
Adder
35.505
939741AE1-205 GEN
Solar/Wind Harmer
9.349
274858EASY ROAD;U2
Solar/Wind Harmer
2.239
274761LEE CO EC;2U
Adder
4.348
970569AG2-363 GEN
Solar/Wind Harmer
13.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
23583801GRNGAP
Solar/Wind Helper
2.128
316075AC2-137 C
Solar/Wind Helper
0.18
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
971403AH1-188 GEN
Solar/Wind Harmer
9.183
944971AF1-162 GEN
Solar/Wind Harmer
4.503
970653AG2-424 GEN
Solar/Wind Harmer
2.669
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.667
339221AD2-048_GEN
Solar/Wind Harmer
0.786
970091AG2-072 GEN
Adder
38.065
276686W4-005 GEN3
Solar/Wind Harmer
1.44
276646AC1-214 GEN2
Solar/Wind Harmer
0.626
276655WTG1_EQ
Solar/Wind Harmer
4.08
963741AG1-226 GEN
Solar/Wind Harmer
21.023
970819AG2-516 GEN
Solar/Wind Harmer
5.587
274822ROCKFORD ;11
Adder
9.119
959081AF2-199 GEN
Solar/Wind Harmer
4.64
971067AG2-660 GEN
Solar/Wind Harmer
1.079
3132273ORANGE
Solar/Wind Helper
0.03
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
316223AC1-118
Solar/Wind Helper
0.174
24735205WLF2G2
Adder
4.907
24723205RIVRG3
Adder
11.612
270336AE1-100 GEN
Solar/Wind Harmer
1.01
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
8.649
339241AF1-083 GEN
Solar/Wind Harmer
0.951
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
945681AF1-233 GEN
Solar/Wind Harmer
9.341
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
3.029
957471AF2-041 GEN
Solar/Wind Harmer
13.921
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
274745AC1-111 GEN9
Adder
2.557
274676JOLIET 29;8U
Adder
13.963
316499AE2-029_GEN
Solar/Wind Helper
0.937
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
316095T157 G97
Solar/Wind Helper
0.557
3142946ENON
Solar/Wind Helper
0.038
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
971125AH1-004 GEN
Solar/Wind Harmer
2.108
276916AD2-100_GEN
Solar/Wind Harmer
10.169
971341AH1-150 GEN
Solar/Wind Harmer
9.281
971343AH1-151 GEN
Solar/Wind Harmer
9.281
238147AE2-230_GEN1
Solar/Wind Helper
0.214
316097T157 G90
Solar/Wind Helper
0.557
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
971485AH1-239 GEN
Solar/Wind Harmer
4.84
964781AG1-341 GEN
Solar/Wind Harmer
6.17
942891AE2-308 GEN
Solar/Wind Harmer
5.443
972043AH1-570 GEN
Solar/Wind Harmer
1.293
276615X2-022 GEN
Solar/Wind Harmer
0.938
945391AF1-204 GEN
Solar/Wind Harmer
6.651
960611AF2-352 GEN
Solar/Wind Harmer
1.092
274764LEE CO EC;5U
Adder
4.358
972235AH1-702 GEN1
Adder
1.172
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
274693ROCKY RD ;1P
Adder
5.064
24728905RICHG2
Adder
1.729
274674JOLIET 9 ;6U
Adder
7.01
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316450AC1-158 RIC
Solar/Wind Helper
0.176
316487AF1-042 GEN
Solar/Wind Helper
0.113
276876AE1-163_GEN2
Solar/Wind Harmer
0.072
971461AH1-227 GEN
Solar/Wind Harmer
3.852
3429391JKCT 9G
Adder
4.482
958171AF2-111 GEN
Solar/Wind Harmer
12.218
970193AG2-126 GEN
Solar/Wind Harmer
7.158
24728705AND G3
Adder
3.771
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
1.869
274857EASY ROAD;U1
Solar/Wind Harmer
2.239
252507AC2-088 GEN
Solar/Wind Harmer
0.831
274855GSG-6 ;RU
Solar/Wind Harmer
1.71
25196608WSDLE5
Adder
3.933
274730ELWOOD EC;6P
Adder
7.484
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
238152AF2-075_GEN
Solar/Wind Helper
0.306
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316404AE1-155 C
Solar/Wind Helper
0.959
943031AE2-326 GEN
Solar/Wind Harmer
3.912
960911AF2-382 GEN
Solar/Wind Harmer
5.846
972103AH1-617 GEN
Solar/Wind Harmer
13.916
270030AE2-140 GEN
Solar/Wind Harmer
10.987
957381AF2-032 GEN
Solar/Wind Harmer
0.966
276785W4-005 GEN1
Solar/Wind Harmer
1.44
971087AG2-675 GEN
Solar/Wind Harmer
1.765
24728505AND G1
Adder
1.803
274849CRESCENT ;1U
Solar/Wind Harmer
0.865
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
959091AF2-200 GEN
Solar/Wind Harmer
9.281
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
5.57
316192AB2-158 GEN
Solar/Wind Helper
0.989
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
24734705WLF1G3
Adder
4.896
24734905WLF1G5
Adder
4.896
966391AG1-508 GEN
Solar/Wind Harmer
2.783
971981AH1-535 GEN
Solar/Wind Harmer
7.894
270399AC1-101 GEN
Solar/Wind Harmer
2.774
339216AC1-074 GEN
Solar/Wind Harmer
0.857
972165AH1-665 GEN
Solar/Wind Harmer
3.979
946321AF1-296 GEN
Solar/Wind Harmer
4.94
274853TWINGROVE;U1
Solar/Wind Harmer
3.384
972267AH1-718 GEN
Adder
1.953
274823ROCKFORD ;21
Adder
9.053
971171AH1-044 GEN
Solar/Wind Harmer
9.281
971675AH1-338 GEN
Solar/Wind Harmer
8.334
971411AH1-196 GEN
Solar/Wind Harmer
6.945
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
315616AA1-038_C
Solar/Wind Helper
1.809
3148013FISHERV
Solar/Wind Helper
0.165
316405AF2-144 C
Solar/Wind Helper
0.151
3143873LANEXA
Solar/Wind Helper
0.067
970281AG2-184 GEN
Solar/Wind Harmer
14.612
962211AG1-066 GEN
Solar/Wind Harmer
1.641
270444AC2-157 GEN1
Solar/Wind Harmer
2.733
270445AC2-157 GEN2
Solar/Wind Harmer
2.733
276763AC1-053 GEN1
Solar/Wind Harmer
1.887
276764AC1-053 GEN2
Solar/Wind Harmer
1.887
276668AB2-070 GEN1
Solar/Wind Harmer
1.055
276848AB2-070 GEN3
Solar/Wind Harmer
1.055
276849AB2-070 GEN2
Solar/Wind Harmer
1.055
274877BISHOP HL;1U
Solar/Wind Harmer
1.582
276741O09 GEN1
Solar/Wind Harmer
1.676
959341AF2-225 GEN
Solar/Wind Harmer
7.012
970169AG2-114 GEN
Solar/Wind Harmer
4.633
274744AC1-111 GEN8
Adder
2.557
274735ELWOOD EC;4P
Adder
7.484
3148463FAIRFLD
Solar/Wind Helper
0.399
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316059AD1-063 C
Solar/Wind Helper
0.113
339236AF1-050_GEN
Solar/Wind Harmer
1.045
970107AG2-081 GEN
Solar/Wind Harmer
1.581
276838X2-022 GEN2
Solar/Wind Harmer
0.111
274880W4-005 GEN4
Solar/Wind Harmer
1.44
276174W4-005 GEN2
Solar/Wind Harmer
1.44
276158O29GEN2
Solar/Wind Harmer
2.347
276157O29GEN1
Solar/Wind Harmer
1.785
276645AC1-214 GEN1
Solar/Wind Harmer
0.626
942111AE2-223 GEN
Solar/Wind Harmer
3.832
274762LEE CO EC;3U
Adder
4.348
970241AG2-163 GEN
Solar/Wind Harmer
11.68
938861AE1-114 GEN
Solar/Wind Harmer
3.826
274696ROCKY RD ;4P
Adder
5.236
274697ROCKY RD ;3P
Adder
1.389
237061AD1-155 GEN
Solar/Wind Helper
0.84
316312AB1-027
Solar/Wind Helper
0.234
3143526WINTERP
Solar/Wind Helper
0.609
970563AG2-360 GEN
50/50
26.903
962751AG1-124 GEN
Solar/Wind Harmer
9.059
972273AH1-721 GEN
Adder
50.356
970093AG2-073 GEN
Solar/Wind Harmer
2.932
972167AH1-666 GEN
Solar/Wind Harmer
3.959
942481AE2-261 GEN
Solar/Wind Harmer
14.451
971993AH1-541 GEN
Solar/Wind Harmer
4.402
270186AC1-089 GEN
Solar/Wind Harmer
2.883
25196008MFTGT1
Adder
0.634
276603SUBLETTE C
Solar/Wind Harmer
0.49
270367AC2-061_GEN
Solar/Wind Harmer
1.479
970571AG2-364 GEN
Solar/Wind Harmer
9.291
274850MENDOTA H;RU
Solar/Wind Harmer
1.189
276602WESTBROOK C
Solar/Wind Harmer
0.984
276799AD1-013 GEN
Solar/Wind Harmer
1.023
946671AF1-331 GEN
Solar/Wind Harmer
0.194
274729ELWOOD EC;1P
Adder
7.484
3147983MERCK5
Solar/Wind Helper
0.108
3143526WINTERP
Solar/Wind Helper
0.609
964211AG1-282 GEN
Solar/Wind Helper
0.152
971313AH1-133 GEN
Solar/Wind Harmer
4.584
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
971681AH1-341 GEN
Solar/Wind Harmer
7
274856ECOGROVE ;U1
Solar/Wind Harmer
1.571
276611AD2-172 GEN
Solar/Wind Harmer
1.192
276612AE2-035 GEN
Solar/Wind Harmer
1.192
276861AD2-134 GEN
Solar/Wind Harmer
0.827
276863AD2-134 GEN
Solar/Wind Harmer
0.827
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
274728ELWOOD EC;5P
Adder
7.484
3148133STUARTS
Solar/Wind Helper
0.172
316258AE1-075 C
Solar/Wind Helper
0.181
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
3141426STAFORD
Solar/Wind Helper
0.025
276889AE2-281 GEN
Solar/Wind Harmer
0.021
971277AH1-098 GEN
Solar/Wind Harmer
3.312
24728205BUCHG1
Adder
3.63
966021AG1-471 GEN
Solar/Wind Harmer
3.282
339231AF1-038_GEN
Solar/Wind Harmer
1.081
964571AG1-320 GEN
Solar/Wind Harmer
4.43
972045AH1-571 GEN
Solar/Wind Harmer
1.034
276911AD2-131_GEN
Solar/Wind Harmer
2.055
274765LEE CO EC;6U
Adder
4.358
274763LEE CO EC;4U
Adder
4.307
972236AH1-702 GEN2
Adder
1.019
252509AD1-136 GEN
Solar/Wind Harmer
0.119
25194508D.CRK3
Adder
0.65
274695ROCKY RD ;2P
Adder
5.115
24728805RICHG1
Adder
1.729
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316045AC1-158 PL2
Solar/Wind Helper
2.117
276872AE1-163_GEN1
Solar/Wind Harmer
0.072
339255AE2-071 GEN
Solar/Wind Harmer
0.685
339250AF1-203 GEN
Solar/Wind Harmer
0.353
339206AE1-143 GEN
Solar/Wind Harmer
1.218
24686405CER G5
Adder
4.71
970653AG2-424 GEN
Solar/Wind Harmer
0.386
970455AG2-298 GEN
Solar/Wind Harmer
1.905
339243AC2-075 GEN1
Solar/Wind Harmer
0.232
965931AG1-462 GEN
Solar/Wind Harmer
12.097
965091AG1-374 GEN
Solar/Wind Harmer
14.092
274878BISHOP HL;2U
Solar/Wind Harmer
1.582
274851PROVIDENC;RU
Solar/Wind Harmer
1.332
274760LEE CO EC;1U
Adder
4.348
3146776BUCKING
Solar/Wind Helper
0.05
316337AD2-073 GEN
Solar/Wind Helper
0.173
3141726DUNNSVL
Solar/Wind Helper
0.452
24735105WLF2G1
Adder
4.907
24734805WLF1G4
Adder
4.896
270400AC1-102 GEN
Solar/Wind Harmer
2.774
957241AF2-018 GEN
Solar/Wind Harmer
2.859
270053AF1-130 C
Solar/Wind Harmer
11.424
3429211JKCT 2G
Adder
6.347
972163AH1-664 GEN
Solar/Wind Harmer
4.973
944221AF1-090 GEN
Solar/Wind Harmer
5.329
274854TWINGROVE;U2
Solar/Wind Harmer
3.313
276726Z2-087_GEN
Solar/Wind Harmer
3.696
926823AC1-168 GEN
Solar/Wind Harmer
1.997
963841AG1-237 GEN
Solar/Wind Harmer
5.074
25196508WSDLE4
Adder
3.893
274746AC1-111 G10
Adder
2.557
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
316164AC1-076 GEN
Solar/Wind Helper
0.62
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141813NORNECK
Solar/Wind Helper
0.113
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
TVALTFEXP_TVA->PJM
CLTF
6.216
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2430.97
MW Contribution:
2.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
26.903
24689505VACITY
50/50
3.164
962751AG1-124 GEN
Solar/Wind Harmer
6.205
972273AH1-721 GEN
Adder
50.356
970093AG2-073 GEN
Solar/Wind Harmer
3.273
972167AH1-666 GEN
Solar/Wind Harmer
2.762
942481AE2-261 GEN
Solar/Wind Harmer
10.082
971993AH1-541 GEN
Solar/Wind Harmer
1.535
270186AC1-089 GEN
Solar/Wind Harmer
0
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
971125AH1-004 GEN
Solar/Wind Harmer
1.471
971587AH1-292 GEN
Solar/Wind Harmer
2.505
276916AD2-100_GEN
Solar/Wind Harmer
7.095
971341AH1-150 GEN
Solar/Wind Harmer
6.475
971343AH1-151 GEN
Solar/Wind Harmer
6.475
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.337
970291AG2-192 GEN
Solar/Wind Harmer
0.41
970291AG2-192 GEN
Solar/Wind Harmer
0.189
971613AH1-306 GEN
Solar/Wind Harmer
1.512
270535AF1-215 GEN1
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
10.194
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.131
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.131
274877BISHOP HL;1U
Solar/Wind Harmer
0.109
276741O09 GEN1
Solar/Wind Harmer
0.116
959341AF2-225 GEN
Solar/Wind Harmer
3.424
970169AG2-114 GEN
Solar/Wind Harmer
3.232
274744AC1-111 GEN8
Adder
2.557
274735ELWOOD EC;4P
Adder
7.484
970289AG2-191 GEN
Solar/Wind Harmer
0.599
958391AF2-133 GEN
Solar/Wind Harmer
0
3148463FAIRFLD
Solar/Wind Helper
0.399
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316059AD1-063 C
Solar/Wind Helper
0.113
24735205WLF2G2
50/50
5.207
24723205RIVRG3
Adder
11.612
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
6.034
943811AF1-049 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
6.517
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
9.712
252516AE2-318_GEN
Solar/Wind Harmer
3.594
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.557
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
13.963
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.159
970613AG2-401 GEN
Solar/Wind Harmer
2.314
270055AF2-134 C O1
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.9
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
0.937
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
316095T157 G97
Solar/Wind Helper
0.557
3142946ENON
Solar/Wind Helper
0.038
970107AG2-081 GEN
Solar/Wind Harmer
1.103
276838X2-022 GEN2
Solar/Wind Harmer
0.188
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.528
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274762LEE CO EC;3U
Adder
4.348
970241AG2-163 GEN
Solar/Wind Harmer
1.901
938861AE1-114 GEN
Solar/Wind Harmer
1.845
962581AG1-107 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.643
274696ROCKY RD ;4P
Adder
5.236
971687AH1-348 GEN
Solar/Wind Harmer
0.521
276621W2-048 GEN
Solar/Wind Harmer
0.167
25196008MFTGT1
Adder
0.654
25196808ZIMRHP
Adder
35.505
939741AE1-205 GEN
Solar/Wind Harmer
4.566
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.348
970569AG2-363 GEN
Solar/Wind Harmer
9.723
971997AH1-543 GEN
Solar/Wind Harmer
1.689
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.024
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.938
270594AE1-207 GEN
Solar/Wind Harmer
3.528
270032AE2-172
Solar/Wind Harmer
2.1
970825AG2-519 GEN
Solar/Wind Harmer
1.115
270005AE1-210 C O1
Solar/Wind Harmer
0.68
964861AG1-349 GEN
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
3.63
24686505CER G6
Adder
4.748
3429241JKCT 3G
Adder
6.43
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276708O09 GEN2
Solar/Wind Harmer
0.116
274766LEE CO EC;7U
Adder
4.297
962781AG1-127 GEN
Solar/Wind Harmer
3.062
24385905FR-11G C
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.397
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
276903AD2-071 C
Solar/Wind Harmer
3.542
270437AC2-090 C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Helper
0.287
3147666LOUISA
Solar/Wind Helper
0.335
3141906WESTMOR
Solar/Wind Helper
0.046
971403AH1-188 GEN
Solar/Wind Harmer
6.407
944971AF1-162 GEN
Solar/Wind Harmer
4.503
970653AG2-424 GEN
Solar/Wind Harmer
1.862
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.003
970091AG2-072 GEN
Adder
38.065
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
7.714
970819AG2-516 GEN
Solar/Wind Harmer
3.898
274822ROCKFORD ;11
Adder
9.119
959081AF2-199 GEN
Solar/Wind Harmer
3.237
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.375
970773AG2-487 GEN
Solar/Wind Harmer
0.568
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
941551AE2-152 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.068
970373AG2-245 GEN
Solar/Wind Harmer
6.5
3132273ORANGE
Solar/Wind Helper
0.03
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
316223AC1-118
Solar/Wind Helper
0.174
24735105WLF2G1
50/50
5.207
24734805WLF1G4
50/50
5.196
270400AC1-102 GEN
Solar/Wind Harmer
1.444
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
10.049
3429211JKCT 2G
Adder
6.347
972163AH1-664 GEN
Solar/Wind Harmer
3.863
944221AF1-090 GEN
Solar/Wind Harmer
1.996
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
270356AE2-297 GEN
Solar/Wind Harmer
0
25196508WSDLE4
Adder
3.893
274746AC1-111 G10
Adder
2.557
946581AF1-322 GEN
Solar/Wind Harmer
0
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
971609AH1-304 GEN
Solar/Wind Harmer
0.508
964611AG1-324 GEN
Solar/Wind Harmer
1.21
960681AF2-359 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
316164AC1-076 GEN
Solar/Wind Helper
0.62
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141813NORNECK
Solar/Wind Helper
0.113
971485AH1-239 GEN
Solar/Wind Harmer
3.377
964781AG1-341 GEN
Solar/Wind Harmer
4.305
942891AE2-308 GEN
Solar/Wind Harmer
3.798
972043AH1-570 GEN
Solar/Wind Harmer
0.938
276615X2-022 GEN
Solar/Wind Harmer
0.035
945391AF1-204 GEN
Solar/Wind Harmer
3.538
960611AF2-352 GEN
Solar/Wind Harmer
1.092
274764LEE CO EC;5U
Adder
4.358
972235AH1-702 GEN1
Adder
1.172
276876AE1-163_GEN2
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.364
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
274693ROCKY RD ;1P
Adder
5.064
958481AF2-142 GEN
Solar/Wind Harmer
4.795
24728905RICHG2
Adder
1.729
24697605MDL-3G C
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.01
926881AC1-175 GEN
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
2.854
970883AG2-550 GEN
Solar/Wind Harmer
3.108
960971AF2-388 GEN
Solar/Wind Harmer
1.8
970349AG2-230 GEN
Solar/Wind Harmer
4.536
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316450AC1-158 RIC
Solar/Wind Helper
0.176
316487AF1-042 GEN
Solar/Wind Helper
0.113
971277AH1-098 GEN
Solar/Wind Harmer
2.311
24728205BUCHG1
Adder
3.63
966021AG1-471 GEN
Solar/Wind Harmer
2.29
964571AG1-320 GEN
Solar/Wind Harmer
3.443
972045AH1-571 GEN
Solar/Wind Harmer
0.751
276911AD2-131_GEN
Solar/Wind Harmer
0.467
274765LEE CO EC;6U
Adder
4.358
274763LEE CO EC;4U
Adder
4.307
972236AH1-702 GEN2
Adder
1.019
252509AD1-136 GEN
Solar/Wind Harmer
0.016
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.815
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
0.65
274695ROCKY RD ;2P
Adder
5.115
24728805RICHG1
Adder
1.729
270180AB1-006 GEN1
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
4.553
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.712
970885AG2-551 GEN
Solar/Wind Harmer
1.036
964611AG1-324 GEN
Solar/Wind Harmer
0.233
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.205
965791AG1-447 GEN
Solar/Wind Harmer
2.8
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316045AC1-158 PL2
Solar/Wind Helper
2.117
971461AH1-227 GEN
Solar/Wind Harmer
2.687
3429391JKCT 9G
Adder
4.482
958171AF2-111 GEN
Solar/Wind Harmer
8.524
970193AG2-126 GEN
Solar/Wind Harmer
4.994
24728705AND G3
Adder
3.771
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.146
274855GSG-6 ;RU
Solar/Wind Harmer
0.118
276868AE1-113 GEN
Solar/Wind Harmer
0.643
274879MINONK ;1U
Solar/Wind Harmer
0.134
25196608WSDLE5
Adder
3.933
274862TOP CROP ;2U
Solar/Wind Harmer
0.432
970781AG2-491 GEN
Solar/Wind Harmer
3.187
274730ELWOOD EC;6P
Adder
7.484
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.354
274887GEN-1.85
Solar/Wind Harmer
0.082
944531AF1-118 GEN
Solar/Wind Harmer
13.572
971347AH1-153 GEN
Solar/Wind Harmer
1.512
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
238152AF2-075_GEN
Solar/Wind Helper
0.306
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316404AE1-155 C
Solar/Wind Helper
0.959
24686405CER G5
Adder
4.71
970653AG2-424 GEN
Solar/Wind Harmer
0.386
970455AG2-298 GEN
Solar/Wind Harmer
1.477
965931AG1-462 GEN
Solar/Wind Harmer
8.44
965091AG1-374 GEN
Solar/Wind Harmer
9.832
274878BISHOP HL;2U
Solar/Wind Harmer
0.109
274760LEE CO EC;1U
Adder
4.348
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.102
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
0.68
964401AG1-302 GEN
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
0.781
3146776BUCKING
Solar/Wind Helper
0.05
316337AD2-073 GEN
Solar/Wind Helper
0.173
3141726DUNNSVL
Solar/Wind Helper
0.452
24734705WLF1G3
50/50
5.196
24734905WLF1G5
50/50
5.196
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.671
270399AC1-101 GEN
Solar/Wind Harmer
1.444
339216AC1-074 GEN
Solar/Wind Harmer
0.095
972165AH1-665 GEN
Solar/Wind Harmer
3.094
946321AF1-296 GEN
Solar/Wind Harmer
1.85
972267AH1-718 GEN
Adder
1.953
274823ROCKFORD ;21
Adder
9.053
971171AH1-044 GEN
Solar/Wind Harmer
6.475
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.845
24386405FR-21G C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.499
970833AG2-524 GEN
Solar/Wind Harmer
2.333
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
960591AF2-350 GEN
Solar/Wind Harmer
3.162
971611AH1-305 GEN
Solar/Wind Harmer
1.876
971985AH1-537 GEN
Solar/Wind Harmer
0.936
959141AF2-205 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
4.672
253406AD2-031_GEN
Solar/Wind Harmer
0.23
247536S-71 GEN
Solar/Wind Harmer
0.124
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
1.809
3148013FISHERV
Solar/Wind Helper
0.165
316405AF2-144 C
Solar/Wind Helper
0.151
3143873LANEXA
Solar/Wind Helper
0.067
943031AE2-326 GEN
Solar/Wind Harmer
3.912
960911AF2-382 GEN
Solar/Wind Harmer
4.078
972103AH1-617 GEN
Solar/Wind Harmer
9.709
270030AE2-140 GEN
Solar/Wind Harmer
7.666
957381AF2-032 GEN
Solar/Wind Harmer
0.764
971087AG2-675 GEN
Solar/Wind Harmer
1.765
24728505AND G1
Adder
1.803
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
959091AF2-200 GEN
Solar/Wind Harmer
6.475
252519AF1-045_GEN
Solar/Wind Harmer
1.674
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
943121AE2-341 GEN
Solar/Wind Harmer
5.351
943591AF1-030 GEN
Solar/Wind Harmer
3.559
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
3.003
276806AD2-047 C O1
Solar/Wind Harmer
1.792
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
4.107
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
946031AF1-268 GEN
Solar/Wind Harmer
2.979
316192AB2-158 GEN
Solar/Wind Helper
0.989
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
958861AF2-177 GEN
Solar/Wind Harmer
1.334
315821AE2-092 GEN
Solar/Wind Helper
1.831
23583801GRNGAP
Solar/Wind Helper
2.128
316075AC2-137 C
Solar/Wind Helper
0.18
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
25196008MFTGT1
Adder
0.634
270367AC2-061_GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.482
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
946671AF1-331 GEN
Solar/Wind Harmer
0.345
274729ELWOOD EC;1P
Adder
7.484
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.365
253394AE2-221_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
7.973
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.643
3147983MERCK5
Solar/Wind Helper
0.108
3143526WINTERP
Solar/Wind Helper
0.609
964211AG1-282 GEN
Solar/Wind Helper
0.152
274697ROCKY RD ;3P
Adder
1.389
276893AG1-478 C
Solar/Wind Harmer
0.212
957841AF2-078 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
0.184
970941AG2-585 GEN
Solar/Wind Harmer
1.739
942221AE2-234 GEN
Solar/Wind Harmer
1.218
237061AD1-155 GEN
Solar/Wind Helper
0.84
316312AB1-027
Solar/Wind Helper
0.234
3143526WINTERP
Solar/Wind Helper
0.609
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
3.818
238147AE2-230_GEN1
Solar/Wind Helper
0.214
316097T157 G90
Solar/Wind Helper
0.557
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
971313AH1-133 GEN
Solar/Wind Harmer
2.637
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
971681AH1-341 GEN
Solar/Wind Harmer
5.242
274856ECOGROVE ;U1
Solar/Wind Harmer
0.076
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276863AD2-134 GEN
Solar/Wind Harmer
0.058
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
7.484
270543AE2-219 C
Solar/Wind Harmer
2.176
270071AF1-092 GEN
Solar/Wind Harmer
5.772
3148133STUARTS
Solar/Wind Helper
0.172
316258AE1-075 C
Solar/Wind Helper
0.181
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
3141426STAFORD
Solar/Wind Helper
0.025
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
TVALTFEXP_TVA->PJM
CLTF
6.216
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
5.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24684505SMG3
50/50
1.341
3147312GRETNA
Solar/Wind Harmer
0.047
971687AH1-348 GEN
Solar/Wind Harmer
0.947
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252510AF1-249 C
Solar/Wind Harmer
0.048
276621W2-048 GEN
Solar/Wind Harmer
0.315
253398AE2-221_GEN2
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24386605FR-22G C
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
970569AG2-363 GEN
Solar/Wind Harmer
18.425
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.195
24728305BUCHG2
50/50
7.157
24686505CER G6
Adder
9.865
3429241JKCT 3G
Adder
12.016
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
270437AC2-090 C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
8.117
24290705CLAY-2
50/50
0.252
958131AF2-107 GEN
Solar/Wind Harmer
5.335
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
960001AF2-291 GEN
Solar/Wind Harmer
0
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
970091AG2-072 GEN
Adder
73.941
971073AG2-665 GEN
Solar/Wind Harmer
1.065
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
970819AG2-516 GEN
Solar/Wind Harmer
7.371
274822ROCKFORD ;11
Adder
17.258
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
941551AE2-152 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
7.838
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
24728205BUCHG1
50/50
7.157
971277AH1-098 GEN
Solar/Wind Harmer
5.174
970913AG2-568 GEN
Solar/Wind Harmer
7.67
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
964571AG1-320 GEN
Solar/Wind Harmer
6.355
972045AH1-571 GEN
Solar/Wind Harmer
1.437
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
276911AD2-131_GEN
Solar/Wind Harmer
0.879
24728805RICHG1
Adder
3.383
24699105WLD G1 C
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
8.233
274763LEE CO EC;4U
Adder
8.136
270383AD1-128 GEN
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274695ROCKY RD ;2P
Adder
9.717
970885AG2-551 GEN
Solar/Wind Harmer
2.025
270031AE2-169
Solar/Wind Harmer
3.328
964611AG1-324 GEN
Solar/Wind Harmer
0.453
958011AF2-095 GEN
Solar/Wind Harmer
8.691
270201AC2-176 GEN
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
970281AG2-184 GEN
Solar/Wind Harmer
18.909
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
959341AF2-225 GEN
Solar/Wind Harmer
6.498
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
971881AH1-461 GEN
50/50
14.967
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147123OTTER R
Solar/Wind Harmer
0.13
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24721905FLATG4
Adder
21.662
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971087AG2-675 GEN
Solar/Wind Harmer
3.318
274767LEE CO EC;8U
Adder
8.117
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
276806AD2-047 C O1
Solar/Wind Harmer
3.42
316192AB2-158 GEN
Solar/Wind Helper
1.845
316447AC1-158 HLD
Solar/Wind Helper
2.777
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
5.792
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
972043AH1-570 GEN
Solar/Wind Harmer
1.794
25194408D.CRK1
Adder
6.93
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276615X2-022 GEN
Solar/Wind Harmer
0.065
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960611AF2-352 GEN
Solar/Wind Harmer
2.071
966841AG1-555 GEN
Solar/Wind Harmer
0.701
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
972235AH1-702 GEN1
Adder
2.217
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274693ROCKY RD ;1P
Adder
9.622
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
274674JOLIET 9 ;6U
Adder
13.36
270599AE1-208 GEN
Solar/Wind Harmer
5.547
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316450AC1-158 RIC
Solar/Wind Helper
0.337
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.731
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
9.535
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
3429391JKCT 9G
Adder
8.393
958171AF2-111 GEN
Solar/Wind Harmer
16.661
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
24728705AND G3
Adder
7.274
959611AF2-252 GEN
Solar/Wind Harmer
2.071
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
274730ELWOOD EC;6P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316044AC1-158 PL1
Solar/Wind Helper
1.262
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
7.447
24686405CER G5
Adder
9.787
970653AG2-424 GEN
Solar/Wind Harmer
0.705
970455AG2-298 GEN
Solar/Wind Harmer
2.725
965931AG1-462 GEN
Solar/Wind Harmer
15.863
965091AG1-374 GEN
Solar/Wind Harmer
18.636
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
24690905MDL-1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276843GEN-1.7
Solar/Wind Harmer
0.195
970191AG2-125 GEN
Solar/Wind Harmer
1.552
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
24735205WLF2G2
Adder
8.017
24723205RIVRG3
Adder
22.932
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
945681AF1-233 GEN
Solar/Wind Harmer
12.766
252516AE2-318_GEN
Solar/Wind Harmer
7.186
25194608D.CRK4
Adder
1.506
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
957471AF2-041 GEN
Solar/Wind Harmer
18.391
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
276694AA1-018 GEN2
Solar/Wind Harmer
0
24684305SMG1
50/50
0.795
971329AH1-144 GEN
Solar/Wind Harmer
6.744
24734805WLF1G4
Adder
8.187
24735105WLF2G1
Adder
8.017
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
3429211JKCT 2G
Adder
11.861
972163AH1-664 GEN
Solar/Wind Harmer
7.559
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196508WSDLE4
Adder
7.759
270356AE2-297 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.696
274854TWINGROVE;U2
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.044
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.61
274746AC1-111 G10
Adder
4.865
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
971609AH1-304 GEN
Solar/Wind Harmer
0.988
964611AG1-324 GEN
Solar/Wind Harmer
2.357
316164AC1-076 GEN
Solar/Wind Helper
1.176
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270069AE2-166 C O1
Solar/Wind Harmer
10.375
24734705WLF1G3
Adder
8.187
24734905WLF1G5
Adder
8.187
270399AC1-101 GEN
Solar/Wind Harmer
2.889
971981AH1-535 GEN
Solar/Wind Harmer
5.838
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
253406AD2-031_GEN
Solar/Wind Harmer
0.464
946321AF1-296 GEN
Solar/Wind Harmer
3.479
270291AC1-194 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
971029AG2-637 GEN
Solar/Wind Harmer
9.145
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.242
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148013FISHERV
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.267
276805AD2-038 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
964861AG1-349 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
315821AE2-092 GEN
Solar/Wind Helper
3.23
23583801GRNGAP
Solar/Wind Helper
4.295
24684605SMG4
50/50
2.21
970563AG2-360 GEN
50/50
45.796
962751AG1-124 GEN
Solar/Wind Harmer
12.886
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
972273AH1-721 GEN
Adder
89.23
970093AG2-073 GEN
Solar/Wind Harmer
6.071
971191AH1-055 GEN
Solar/Wind Harmer
18.034
972167AH1-666 GEN
Solar/Wind Harmer
5.413
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.251
970879AG2-548 GEN
Solar/Wind Harmer
4.688
942481AE2-261 GEN
Solar/Wind Harmer
18.979
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
12.283
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
946671AF1-331 GEN
Solar/Wind Harmer
0.653
970825AG2-519 GEN
Solar/Wind Harmer
4.603
274729ELWOOD EC;1P
Adder
14.264
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
3147983MERCK5
Solar/Wind Helper
0.198
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
5.363
971061AG2-657 GEN
Solar/Wind Harmer
5.362
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
24691005MDL-2G C
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.033
270543AE2-219 C
Solar/Wind Harmer
4.252
274728ELWOOD EC;5P
Adder
14.264
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.089
970107AG2-081 GEN
Solar/Wind Harmer
2.085
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
1.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
960201AF2-311 GEN
Solar/Wind Harmer
5.7
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
274762LEE CO EC;3U
Adder
8.213
938861AE1-114 GEN
Solar/Wind Harmer
3.487
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
274696ROCKY RD ;4P
Adder
9.947
274697ROCKY RD ;3P
Adder
2.64
276893AG1-478 C
Solar/Wind Harmer
0.404
276897AD1-100 C
Solar/Wind Harmer
15.124
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
970941AG2-585 GEN
Solar/Wind Harmer
3.319
237061AD1-155 GEN
Solar/Wind Helper
1.647
274745AC1-111 GEN9
Adder
4.865
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
26.611
316499AE2-029_GEN
Solar/Wind Helper
1.726
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
971125AH1-004 GEN
Solar/Wind Harmer
2.78
971587AH1-292 GEN
Solar/Wind Harmer
4.796
276916AD2-100_GEN
Solar/Wind Harmer
13.351
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.644
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
276741O09 GEN1
Solar/Wind Harmer
0.218
970169AG2-114 GEN
Solar/Wind Harmer
6.143
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274744AC1-111 GEN8
Adder
4.865
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
958391AF2-133 GEN
Solar/Wind Harmer
0.001
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
276903AD2-071 C
Solar/Wind Harmer
6.875
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
964401AG1-302 GEN
Solar/Wind Harmer
0.001
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
TVALTFEXP_TVA->PJM
CLTF
10.596
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.66 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4175.28
MW Contribution:
9.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.391
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.737
958121AF2-106 GEN
Solar/Wind Harmer
9.417
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
270574AD1-017 GEN2
Solar/Wind Harmer
8.474
270336AE1-100 GEN
Solar/Wind Harmer
2.754
943811AF1-049 GEN
Solar/Wind Harmer
5.701
24735205WLF2G2
Adder
8.042
24723205RIVRG3
Adder
23.046
972203AH1-686 GEN
Adder
2.716
964901AG1-354 GEN
Solar/Wind Harmer
15.55
339241AF1-083 GEN
Solar/Wind Harmer
1.722
943111AE2-339 GEN
Solar/Wind Harmer
0.887
945681AF1-233 GEN
Solar/Wind Harmer
18.414
252516AE2-318_GEN
Solar/Wind Harmer
9.259
25194608D.CRK4
Adder
1.517
253316AC1-085 GEN3
Solar/Wind Harmer
7.64
946171AF1-282 GEN
Solar/Wind Harmer
9.125
24728605AND G2
Adder
3.5
274828WAUKEGAN ;BP
Adder
9.706
274682WAUKEGAN ;7U
Adder
15.786
274745AC1-111 GEN9
Adder
4.896
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
274676JOLIET 29;8U
Adder
22.605
316499AE2-029_GEN
Solar/Wind Helper
1.728
316095T157 G97
Solar/Wind Helper
1.135
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.393
971881AH1-461 GEN
50/50
15.01
943031AE2-326 GEN
Solar/Wind Harmer
6.794
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.957
960911AF2-382 GEN
Solar/Wind Harmer
10.976
972103AH1-617 GEN
Solar/Wind Harmer
25.917
24721905FLATG4
Adder
21.789
252519AF1-045_GEN
Solar/Wind Harmer
3.37
25194608D.CRK4
Adder
1.517
252524AE2-267 GEN
Solar/Wind Harmer
1.45
957381AF2-032 GEN
Solar/Wind Harmer
1.829
253317AC1-085 GEN4
Solar/Wind Harmer
7.64
946181AF1-283 GEN
Solar/Wind Harmer
11.863
24728505AND G1
Adder
3.5
276785W4-005 GEN1
Solar/Wind Harmer
2.739
971087AG2-675 GEN
Solar/Wind Harmer
3.338
274767LEE CO EC;8U
Adder
8.167
274682WAUKEGAN ;7U
Adder
15.786
274734ELWOOD EC;8P
Adder
14.355
274736ELWOOD EC;9P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
316192AB2-158 GEN
Solar/Wind Helper
1.852
316447AC1-158 HLD
Solar/Wind Helper
2.79
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.222
24684605SMG4
50/50
2.212
970563AG2-360 GEN
50/50
45.925
962751AG1-124 GEN
Solar/Wind Harmer
18.829
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.251
972273AH1-721 GEN
Adder
89.66
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.387
966391AG1-508 GEN
Solar/Wind Harmer
6.384
270069AE2-166 C O1
Solar/Wind Harmer
14.894
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.669
971485AH1-239 GEN
Solar/Wind Harmer
8.528
964781AG1-341 GEN
Solar/Wind Harmer
11.012
942891AE2-308 GEN
Solar/Wind Harmer
10.222
972043AH1-570 GEN
Solar/Wind Harmer
2.487
25194408D.CRK1
Adder
6.977
945391AF1-204 GEN
Solar/Wind Harmer
12.785
276615X2-022 GEN
Solar/Wind Harmer
1.781
24728905RICHG2
Adder
3.406
960251AF2-316 GEN
Solar/Wind Harmer
13.508
960611AF2-352 GEN
Solar/Wind Harmer
2.083
274764LEE CO EC;5U
Adder
8.284
972235AH1-702 GEN1
Adder
2.231
274683WAUKEGAN ;8U
Adder
18.516
274683WAUKEGAN ;8U
Adder
15.608
274693ROCKY RD ;1P
Adder
9.683
274674JOLIET 9 ;6U
Adder
13.445
3132123MT JACKSON
Solar/Wind Helper
1.393
966001AG1-469 GEN
Solar/Wind Helper
0.321
238148AE2-230_GEN2
Solar/Wind Helper
0.426
316450AC1-158 RIC
Solar/Wind Helper
0.338
970093AG2-073 GEN
Solar/Wind Harmer
5.468
971191AH1-055 GEN
Solar/Wind Harmer
18.939
972167AH1-666 GEN
Solar/Wind Harmer
7.807
270186AC1-089 GEN
Solar/Wind Harmer
5.851
270367AC2-061_GEN
Solar/Wind Harmer
3.02
25196008MFTGT1
Adder
1.259
970879AG2-548 GEN
Solar/Wind Harmer
7.39
942481AE2-261 GEN
Solar/Wind Harmer
27.366
971993AH1-541 GEN
Solar/Wind Harmer
8.371
253394AE2-221_GEN
Solar/Wind Harmer
4.079
274729ELWOOD EC;1P
Adder
14.355
3147983MERCK5
Solar/Wind Helper
0.199
24684305SMG1
50/50
0.796
971329AH1-144 GEN
Solar/Wind Harmer
11.745
24734805WLF1G4
Adder
8.213
24735105WLF2G1
Adder
8.042
270400AC1-102 GEN
Solar/Wind Harmer
5.575
941621AE2-160 GEN
Adder
4.304
957241AF2-018 GEN
Solar/Wind Harmer
5.778
270053AF1-130 C
Solar/Wind Harmer
23.086
3429211JKCT 2G
Adder
11.928
972163AH1-664 GEN
Solar/Wind Harmer
9.793
944221AF1-090 GEN
Solar/Wind Harmer
10.074
25196508WSDLE4
Adder
7.812
270356AE2-297 GEN
Solar/Wind Harmer
4.168
963841AG1-237 GEN
Solar/Wind Harmer
9.807
274854TWINGROVE;U2
Solar/Wind Harmer
6.319
270340AC2-060 GEN
Solar/Wind Harmer
2.703
276726Z2-087_GEN
Solar/Wind Harmer
7.058
274746AC1-111 G10
Adder
4.896
274731ELWOOD EC;2P
Adder
14.355
274733ELWOOD EC;3P
Adder
14.355
316164AC1-076 GEN
Solar/Wind Helper
1.182
24728205BUCHG1
50/50
7.18
971277AH1-098 GEN
Solar/Wind Harmer
7.43
970913AG2-568 GEN
Solar/Wind Harmer
9.375
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.774
339231AF1-038_GEN
Solar/Wind Harmer
1.925
964571AG1-320 GEN
Solar/Wind Harmer
8.222
972045AH1-571 GEN
Solar/Wind Harmer
1.989
270583AD2-179 GEN
Solar/Wind Harmer
20.746
270214AC2-123 GEN
Solar/Wind Harmer
4.317
971225AH1-072 GEN
Solar/Wind Harmer
2.738
971227AH1-073 GEN
Solar/Wind Harmer
2.738
24723005RIVRG1
Adder
23.046
24723105RIVRG2
Adder
23.046
971125AH1-004 GEN
Solar/Wind Harmer
4.008
276916AD2-100_GEN
Solar/Wind Harmer
19.251
253370AE2-315 SEC1
Adder
1.749
316097T157 G90
Solar/Wind Helper
1.135
238147AE2-230_GEN1
Solar/Wind Helper
0.426
270197AD1-017 GEN1
Solar/Wind Harmer
2.542
970281AG2-184 GEN
Solar/Wind Harmer
27.213
962211AG1-066 GEN
Solar/Wind Harmer
3.011
270444AC2-157 GEN1
Solar/Wind Harmer
5.263
270445AC2-157 GEN2
Solar/Wind Harmer
5.263
253433AC1-085 GEN1
Solar/Wind Harmer
4.849
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
276763AC1-053 GEN1
Solar/Wind Harmer
3.586
276764AC1-053 GEN2
Solar/Wind Harmer
3.586
276668AB2-070 GEN1
Solar/Wind Harmer
2.006
276848AB2-070 GEN3
Solar/Wind Harmer
2.006
276849AB2-070 GEN2
Solar/Wind Harmer
2.006
959341AF2-225 GEN
Solar/Wind Harmer
13.389
274744AC1-111 GEN8
Adder
4.896
25306009OHH W.
Adder
2.518
274735ELWOOD EC;4P
Adder
14.355
253372AE2-315 SEC3
Adder
1.655
253372AE2-315 SEC3
Adder
1.655
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.846
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
270013AE1-250 PV
Solar/Wind Harmer
3.251
339236AF1-050_GEN
Solar/Wind Harmer
1.88
970107AG2-081 GEN
Solar/Wind Harmer
3.006
962581AG1-107 GEN
Solar/Wind Harmer
4.757
961491AF2-440 GEN
Solar/Wind Harmer
1.977
970879AG2-548 GEN
Solar/Wind Harmer
1.074
276838X2-022 GEN2
Solar/Wind Harmer
0.212
274880W4-005 GEN4
Solar/Wind Harmer
2.739
276174W4-005 GEN2
Solar/Wind Harmer
2.739
970241AG2-163 GEN
Solar/Wind Harmer
22.546
960201AF2-311 GEN
Solar/Wind Harmer
9.005
942111AE2-223 GEN
Solar/Wind Harmer
7.317
274762LEE CO EC;3U
Adder
8.264
274696ROCKY RD ;4P
Adder
10.01
274697ROCKY RD ;3P
Adder
2.656
237061AD1-155 GEN
Solar/Wind Helper
1.655
316312AB1-027
Solar/Wind Helper
0.426
24387305FR-4G C
Solar/Wind Harmer
3.45
24684505SMG3
50/50
1.342
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.363
270331AC1-082 GEN3
Solar/Wind Harmer
0.515
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
71.001
25196008MFTGT1
Adder
1.3
252510AF1-249 C
Solar/Wind Harmer
0.385
276621W2-048 GEN
Solar/Wind Harmer
5.671
253398AE2-221_GEN2
Solar/Wind Harmer
4.079
939741AE1-205 GEN
Solar/Wind Harmer
17.852
274761LEE CO EC;2U
Adder
8.264
315821AE2-092 GEN
Solar/Wind Helper
3.236
23583801GRNGAP
Solar/Wind Helper
4.324
24386605FR-22G C
Solar/Wind Harmer
2.921
971543AH1-269 GEN
50/50
12.26
24684705SMG5
50/50
0.846
971313AH1-133 GEN
Solar/Wind Harmer
9.348
971061AG2-657 GEN
Solar/Wind Harmer
11.048
25196108MFTGT2
Adder
1.433
25196108MFTGT2
Adder
1.331
25196408WSDLE3
Adder
8.125
25196308WSDLE2
Adder
8.054
25196208WSDLE1
Adder
8.034
25196708WSDLE6
Adder
8.014
274728ELWOOD EC;5P
Adder
14.355
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.321
316468AD1-105 GEN
Solar/Wind Helper
1.093
3141426STAFORD
Solar/Wind Helper
0.049
24387005FR-3G C
Solar/Wind Harmer
2.686
24734705WLF1G3
Adder
8.213
24734905WLF1G5
Adder
8.213
270399AC1-101 GEN
Solar/Wind Harmer
5.575
971981AH1-535 GEN
Solar/Wind Harmer
12.593
339216AC1-074 GEN
Solar/Wind Harmer
1.652
972165AH1-665 GEN
Solar/Wind Harmer
7.834
971985AH1-537 GEN
Solar/Wind Harmer
17.394
253406AD2-031_GEN
Solar/Wind Harmer
1.153
270291AC1-194 GEN
Solar/Wind Harmer
4.567
946321AF1-296 GEN
Solar/Wind Harmer
9.347
274853TWINGROVE;U1
Solar/Wind Harmer
6.454
972267AH1-718 GEN
Adder
3.707
274823ROCKFORD ;21
Adder
17.239
274675JOLIET 29;7U
Adder
26.781
315616AA1-038_C
Solar/Wind Helper
3.299
3148013FISHERV
Solar/Wind Helper
0.301
316405AF2-144 C
Solar/Wind Helper
0.267
24386405FR-21G C
Solar/Wind Harmer
2.921
927014AC1-188 GEN
Solar/Wind Harmer
1.537
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.603
971073AG2-665 GEN
Solar/Wind Harmer
7.39
25194508D.CRK3
Adder
1.304
276911AD2-131_GEN
Solar/Wind Harmer
3.891
24728805RICHG1
Adder
3.406
274765LEE CO EC;6U
Adder
8.284
274763LEE CO EC;4U
Adder
8.186
972236AH1-702 GEN2
Adder
1.94
274695ROCKY RD ;2P
Adder
9.779
238149AF1-291A_GEN
Solar/Wind Helper
0.122
316006AB2-029 C
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.356
316045AC1-158 PL2
Solar/Wind Helper
4.058
966871AG1-558 GEN
Solar/Wind Helper
0.307
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.446
958131AF2-107 GEN
Solar/Wind Harmer
7.107
971403AH1-188 GEN
Solar/Wind Harmer
18.915
944971AF1-162 GEN
Solar/Wind Harmer
9.1
960001AF2-291 GEN
Solar/Wind Harmer
3.133
970653AG2-424 GEN
Solar/Wind Harmer
4.903
3429421JKCT 10G
Adder
8.441
339221AD2-048_GEN
Solar/Wind Harmer
1.518
970091AG2-072 GEN
Adder
74.384
971073AG2-665 GEN
Solar/Wind Harmer
1.074
276686W4-005 GEN3
Solar/Wind Harmer
2.739
963741AG1-226 GEN
Solar/Wind Harmer
40.583
270222AC2-111 GEN
Solar/Wind Harmer
4.015
270346AE1-212 GEN
Solar/Wind Harmer
13.976
270018AE2-047 C O1
Solar/Wind Harmer
1.823
971461AH1-227 GEN
Solar/Wind Harmer
7.023
970223AG2-152 GEN
Solar/Wind Harmer
17.677
270330AC1-082 GEN2
Solar/Wind Harmer
0.514
3429391JKCT 9G
Adder
8.441
957541AF2-048 GEN
Solar/Wind Harmer
1.537
958171AF2-111 GEN
Solar/Wind Harmer
24.034
252507AC2-088 GEN
Solar/Wind Harmer
1.676
25196608WSDLE5
Adder
7.893
970193AG2-126 GEN
Solar/Wind Harmer
13.761
24728705AND G3
Adder
7.32
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274730ELWOOD EC;6P
Adder
14.355
3147666LOUISA
Solar/Wind Helper
1.093
238152AF2-075_GEN
Solar/Wind Helper
0.608
316044AC1-158 PL1
Solar/Wind Helper
1.268
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.197
24728305BUCHG2
50/50
7.18
316217AC1-145 GEN
Solar/Wind Harmer
4.244
316197AC1-042 GEN
Solar/Wind Harmer
3.217
24686505CER G6
Adder
9.917
339211AE2-254 GEN
Solar/Wind Harmer
1.567
3429241JKCT 3G
Adder
12.084
965911AG1-460 GEN
Solar/Wind Harmer
1.277
944031AF1-071 GEN
Solar/Wind Harmer
0.903
276656WTG2_EQ
Solar/Wind Harmer
1.032
274766LEE CO EC;7U
Adder
8.167
274732ELWOOD EC;7P
Adder
14.355
274674JOLIET 9 ;6U
Adder
13.445
3148013FISHERV
Solar/Wind Helper
0.524
3147666LOUISA
Solar/Wind Helper
0.628
24385905FR-11G C
Solar/Wind Harmer
5.645
276655WTG1_EQ
Solar/Wind Harmer
7.791
274822ROCKFORD ;11
Adder
17.365
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.813
24686405CER G5
Adder
9.839
270329AC1-082 GEN1
Solar/Wind Harmer
0.514
339255AE2-071 GEN
Solar/Wind Harmer
1.222
339250AF1-203 GEN
Solar/Wind Harmer
0.629
339206AE1-143 GEN
Solar/Wind Harmer
2.213
970653AG2-424 GEN
Solar/Wind Harmer
0.709
970455AG2-298 GEN
Solar/Wind Harmer
3.536
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
965931AG1-462 GEN
Solar/Wind Harmer
22.875
965091AG1-374 GEN
Solar/Wind Harmer
26.876
274760LEE CO EC;1U
Adder
8.264
24386205FR-12G C
Solar/Wind Harmer
2.911
CPLELTFEXP_CPLE->PJM
CLTF
6.224
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.642
LAGNLTFEXP_LAGN->PJM
CLTF
20.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.582
NYPJM->LTFIMP_NY
CLTF
3.28
LGEELTFEXP_LGEE->PJM
CLTF
6.795
TVALTFEXP_TVA->PJM
CLTF
10.64
WECLTFEXP_WEC->PJM
CLTF
3.389
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.053
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.452
MECLTFEXP_MEC->PJM
CLTF
15.488
SIGELTFEXP_SIGE->PJM
CLTF
0.51

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4165.98
MW Contribution:
9.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24735205WLF2G2
Adder
8.025
24723205RIVRG3
Adder
22.967
972203AH1-686 GEN
Adder
2.706
964901AG1-354 GEN
Solar/Wind Harmer
15.496
339241AF1-083 GEN
Solar/Wind Harmer
1.716
943111AE2-339 GEN
Solar/Wind Harmer
0.883
945681AF1-233 GEN
Solar/Wind Harmer
18.334
252516AE2-318_GEN
Solar/Wind Harmer
9.216
25194608D.CRK4
Adder
1.51
24728605AND G2
Adder
3.485
253316AC1-085 GEN3
Solar/Wind Harmer
7.603
946171AF1-282 GEN
Solar/Wind Harmer
9.081
274848CAMPGROVE;RU
Solar/Wind Harmer
5.733
274828WAUKEGAN ;BP
Adder
9.664
274682WAUKEGAN ;7U
Adder
15.718
274745AC1-111 GEN9
Adder
4.874
274676JOLIET 29;8U
Adder
26.663
316499AE2-029_GEN
Solar/Wind Helper
1.726
316095T157 G97
Solar/Wind Helper
1.13
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.39
971881AH1-461 GEN
50/50
14.98
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.922
960911AF2-382 GEN
Solar/Wind Harmer
10.95
972103AH1-617 GEN
Solar/Wind Harmer
25.844
24721905FLATG4
Adder
21.701
252519AF1-045_GEN
Solar/Wind Harmer
3.354
25194608D.CRK4
Adder
1.51
252524AE2-267 GEN
Solar/Wind Harmer
1.443
957381AF2-032 GEN
Solar/Wind Harmer
1.822
24728505AND G1
Adder
3.485
253317AC1-085 GEN4
Solar/Wind Harmer
7.603
946181AF1-283 GEN
Solar/Wind Harmer
11.806
276785W4-005 GEN1
Solar/Wind Harmer
2.728
971087AG2-675 GEN
Solar/Wind Harmer
3.324
274767LEE CO EC;8U
Adder
8.132
274682WAUKEGAN ;7U
Adder
15.718
274734ELWOOD EC;8P
Adder
14.292
274736ELWOOD EC;9P
Adder
14.292
316192AB2-158 GEN
Solar/Wind Helper
1.847
316447AC1-158 HLD
Solar/Wind Helper
2.781
3142416OLDCHRC
Solar/Wind Helper
0.579
3142416OLDCHRC
Solar/Wind Helper
0.222
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.664
971485AH1-239 GEN
Solar/Wind Harmer
8.501
964781AG1-341 GEN
Solar/Wind Harmer
10.975
942891AE2-308 GEN
Solar/Wind Harmer
10.182
972043AH1-570 GEN
Solar/Wind Harmer
2.477
24684605SMG4
50/50
2.211
970563AG2-360 GEN
50/50
45.836
962751AG1-124 GEN
Solar/Wind Harmer
18.819
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.249
972273AH1-721 GEN
Adder
89.361
970093AG2-073 GEN
Solar/Wind Harmer
5.447
971191AH1-055 GEN
Solar/Wind Harmer
18.847
972167AH1-666 GEN
Solar/Wind Harmer
7.773
270186AC1-089 GEN
Solar/Wind Harmer
5.824
270367AC2-061_GEN
Solar/Wind Harmer
3.006
25196008MFTGT1
Adder
1.253
970879AG2-548 GEN
Solar/Wind Harmer
7.349
942481AE2-261 GEN
Solar/Wind Harmer
27.253
971993AH1-541 GEN
Solar/Wind Harmer
8.336
253394AE2-221_GEN
Solar/Wind Harmer
4.059
274729ELWOOD EC;1P
Adder
14.292
3147983MERCK5
Solar/Wind Helper
0.199
24684305SMG1
50/50
0.796
971329AH1-144 GEN
Solar/Wind Harmer
11.729
24734805WLF1G4
Adder
8.195
24735105WLF2G1
Adder
8.025
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.288
957241AF2-018 GEN
Solar/Wind Harmer
5.76
270053AF1-130 C
Solar/Wind Harmer
23.016
3429211JKCT 2G
Adder
11.881
972163AH1-664 GEN
Solar/Wind Harmer
9.75
944221AF1-090 GEN
Solar/Wind Harmer
10.032
25196508WSDLE4
Adder
7.775
270356AE2-297 GEN
Solar/Wind Harmer
4.149
963841AG1-237 GEN
Solar/Wind Harmer
9.765
274854TWINGROVE;U2
Solar/Wind Harmer
6.292
270340AC2-060 GEN
Solar/Wind Harmer
2.689
276726Z2-087_GEN
Solar/Wind Harmer
7.027
274746AC1-111 G10
Adder
4.874
274731ELWOOD EC;2P
Adder
14.292
274733ELWOOD EC;3P
Adder
14.292
316164AC1-076 GEN
Solar/Wind Helper
1.178
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971225AH1-072 GEN
Solar/Wind Harmer
2.731
971227AH1-073 GEN
Solar/Wind Harmer
2.731
24723005RIVRG1
Adder
22.967
24723105RIVRG2
Adder
22.967
971125AH1-004 GEN
Solar/Wind Harmer
3.992
276916AD2-100_GEN
Solar/Wind Harmer
19.171
316097T157 G90
Solar/Wind Helper
1.13
238147AE2-230_GEN1
Solar/Wind Helper
0.424
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
970281AG2-184 GEN
Solar/Wind Harmer
27.137
962211AG1-066 GEN
Solar/Wind Harmer
3.002
270444AC2-157 GEN1
Solar/Wind Harmer
5.241
270445AC2-157 GEN2
Solar/Wind Harmer
5.241
253433AC1-085 GEN1
Solar/Wind Harmer
4.826
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
276668AB2-070 GEN1
Solar/Wind Harmer
1.998
276848AB2-070 GEN3
Solar/Wind Harmer
1.998
276849AB2-070 GEN2
Solar/Wind Harmer
1.998
270013AE1-250 PV
Solar/Wind Harmer
3.249
339236AF1-050_GEN
Solar/Wind Harmer
1.873
970107AG2-081 GEN
Solar/Wind Harmer
2.994
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
970879AG2-548 GEN
Solar/Wind Harmer
1.068
276838X2-022 GEN2
Solar/Wind Harmer
0.211
274880W4-005 GEN4
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
970241AG2-163 GEN
Solar/Wind Harmer
22.448
960201AF2-311 GEN
Solar/Wind Harmer
8.941
942111AE2-223 GEN
Solar/Wind Harmer
7.286
274762LEE CO EC;3U
Adder
8.229
274696ROCKY RD ;4P
Adder
9.966
274697ROCKY RD ;3P
Adder
2.645
237061AD1-155 GEN
Solar/Wind Helper
1.65
316312AB1-027
Solar/Wind Helper
0.425
24387305FR-4G C
Solar/Wind Harmer
2.471
24684505SMG3
50/50
1.342
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.359
270331AC1-082 GEN3
Solar/Wind Harmer
0.513
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.673
25196008MFTGT1
Adder
1.294
252510AF1-249 C
Solar/Wind Harmer
0.384
276621W2-048 GEN
Solar/Wind Harmer
5.648
253398AE2-221_GEN2
Solar/Wind Harmer
4.059
939741AE1-205 GEN
Solar/Wind Harmer
17.775
274761LEE CO EC;2U
Adder
8.229
315821AE2-092 GEN
Solar/Wind Helper
3.232
23583801GRNGAP
Solar/Wind Helper
4.304
24386605FR-22G C
Solar/Wind Harmer
2.093
971543AH1-269 GEN
50/50
12.246
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
9.329
971061AG2-657 GEN
Solar/Wind Harmer
11.001
25196108MFTGT2
Adder
1.427
25196108MFTGT2
Adder
1.325
25196408WSDLE3
Adder
8.087
25196308WSDLE2
Adder
8.016
25196208WSDLE1
Adder
7.996
25196708WSDLE6
Adder
7.976
274728ELWOOD EC;5P
Adder
14.292
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.09
24387005FR-3G C
Solar/Wind Harmer
1.925
25194408D.CRK1
Adder
6.944
945391AF1-204 GEN
Solar/Wind Harmer
12.73
276615X2-022 GEN
Solar/Wind Harmer
1.774
24728905RICHG2
Adder
3.39
960251AF2-316 GEN
Solar/Wind Harmer
13.412
960611AF2-352 GEN
Solar/Wind Harmer
2.075
274764LEE CO EC;5U
Adder
8.248
972235AH1-702 GEN1
Adder
2.222
274683WAUKEGAN ;8U
Adder
18.436
274683WAUKEGAN ;8U
Adder
15.54
274693ROCKY RD ;1P
Adder
9.64
274674JOLIET 9 ;6U
Adder
13.386
3132123MT JACKSON
Solar/Wind Helper
1.391
966001AG1-469 GEN
Solar/Wind Helper
0.321
238148AE2-230_GEN2
Solar/Wind Helper
0.424
316450AC1-158 RIC
Solar/Wind Helper
0.337
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.362
966391AG1-508 GEN
Solar/Wind Harmer
6.375
270069AE2-166 C O1
Solar/Wind Harmer
14.878
24734705WLF1G3
Adder
8.195
24734905WLF1G5
Adder
8.195
270399AC1-101 GEN
Solar/Wind Harmer
5.558
971981AH1-535 GEN
Solar/Wind Harmer
12.564
339216AC1-074 GEN
Solar/Wind Harmer
1.645
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.311
253406AD2-031_GEN
Solar/Wind Harmer
1.147
270291AC1-194 GEN
Solar/Wind Harmer
4.541
946321AF1-296 GEN
Solar/Wind Harmer
9.308
274853TWINGROVE;U1
Solar/Wind Harmer
6.427
972267AH1-718 GEN
Adder
3.691
274823ROCKFORD ;21
Adder
17.165
274675JOLIET 29;7U
Adder
26.663
274675JOLIET 29;7U
Adder
7.65
24728205BUCHG1
50/50
7.164
971277AH1-098 GEN
Solar/Wind Harmer
7.42
970913AG2-568 GEN
Solar/Wind Harmer
9.345
942751AE2-291 GEN
Solar/Wind Harmer
10.376
966021AG1-471 GEN
Solar/Wind Harmer
5.755
339231AF1-038_GEN
Solar/Wind Harmer
1.919
964571AG1-320 GEN
Solar/Wind Harmer
8.191
972045AH1-571 GEN
Solar/Wind Harmer
1.981
927014AC1-188 GEN
Solar/Wind Harmer
1.529
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.577
971073AG2-665 GEN
Solar/Wind Harmer
7.349
25194508D.CRK3
Adder
1.298
276911AD2-131_GEN
Solar/Wind Harmer
3.875
24728805RICHG1
Adder
3.39
274765LEE CO EC;6U
Adder
8.248
274763LEE CO EC;4U
Adder
8.151
972236AH1-702 GEN2
Adder
1.932
274695ROCKY RD ;2P
Adder
9.736
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.356
966871AG1-558 GEN
Solar/Wind Helper
0.307
316045AC1-158 PL2
Solar/Wind Helper
4.045
315616AA1-038_C
Solar/Wind Helper
3.298
3148013FISHERV
Solar/Wind Helper
0.301
316405AF2-144 C
Solar/Wind Helper
0.267
24386405FR-21G C
Solar/Wind Harmer
2.093
970823AG2-518 GEN
50/50
8.383
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.733
958121AF2-106 GEN
Solar/Wind Harmer
9.406
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270018AE2-047 C O1
Solar/Wind Harmer
1.821
971461AH1-227 GEN
Solar/Wind Harmer
7.006
970223AG2-152 GEN
Solar/Wind Harmer
17.663
270330AC1-082 GEN2
Solar/Wind Harmer
0.512
3429391JKCT 9G
Adder
8.408
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.928
252507AC2-088 GEN
Solar/Wind Harmer
1.668
25196608WSDLE5
Adder
7.856
970193AG2-126 GEN
Solar/Wind Harmer
13.702
24728705AND G3
Adder
7.288
959611AF2-252 GEN
Solar/Wind Harmer
2.075
274730ELWOOD EC;6P
Adder
14.292
3147666LOUISA
Solar/Wind Helper
1.09
238152AF2-075_GEN
Solar/Wind Helper
0.606
316044AC1-158 PL1
Solar/Wind Helper
1.264
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.196
24728305BUCHG2
50/50
7.164
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
24686505CER G6
Adder
9.881
339211AE2-254 GEN
Solar/Wind Harmer
1.561
3429241JKCT 3G
Adder
12.037
965911AG1-460 GEN
Solar/Wind Harmer
1.272
944031AF1-071 GEN
Solar/Wind Harmer
0.899
276656WTG2_EQ
Solar/Wind Harmer
1.027
274766LEE CO EC;7U
Adder
8.132
274732ELWOOD EC;7P
Adder
14.292
274674JOLIET 9 ;6U
Adder
13.386
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.627
24385905FR-11G C
Solar/Wind Harmer
4.044
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.444
958131AF2-107 GEN
Solar/Wind Harmer
7.104
971403AH1-188 GEN
Solar/Wind Harmer
18.86
944971AF1-162 GEN
Solar/Wind Harmer
9.072
960001AF2-291 GEN
Solar/Wind Harmer
3.117
970653AG2-424 GEN
Solar/Wind Harmer
4.885
3429421JKCT 10G
Adder
8.408
339221AD2-048_GEN
Solar/Wind Harmer
1.511
970091AG2-072 GEN
Adder
74.077
971073AG2-665 GEN
Solar/Wind Harmer
1.068
276686W4-005 GEN3
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.407
270222AC2-111 GEN
Solar/Wind Harmer
3.996
276655WTG1_EQ
Solar/Wind Harmer
7.757
274822ROCKFORD ;11
Adder
17.29
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.808
24686405CER G5
Adder
9.803
270329AC1-082 GEN1
Solar/Wind Harmer
0.512
339255AE2-071 GEN
Solar/Wind Harmer
1.218
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.205
970653AG2-424 GEN
Solar/Wind Harmer
0.706
970455AG2-298 GEN
Solar/Wind Harmer
3.522
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
965931AG1-462 GEN
Solar/Wind Harmer
22.779
965091AG1-374 GEN
Solar/Wind Harmer
26.762
274760LEE CO EC;1U
Adder
8.229
24386205FR-12G C
Solar/Wind Harmer
2.085
959341AF2-225 GEN
Solar/Wind Harmer
13.331
274744AC1-111 GEN8
Adder
4.874
274735ELWOOD EC;4P
Adder
14.292
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.844
CPLELTFEXP_CPLE->PJM
CLTF
6.216
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.186
LAGNLTFEXP_LAGN->PJM
CLTF
20.287
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.539
NYPJM->LTFIMP_NY
CLTF
3.263
LGEELTFEXP_LGEE->PJM
CLTF
6.768
TVALTFEXP_TVA->PJM
CLTF
10.609
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.331
MECLTFEXP_MEC->PJM
CLTF
15.426
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.26 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4160.96
MW Contribution:
9.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
270574AD1-017 GEN2
Solar/Wind Harmer
8.466
270336AE1-100 GEN
Solar/Wind Harmer
2.749
943811AF1-049 GEN
Solar/Wind Harmer
5.692
24735205WLF2G2
Adder
8.017
24723205RIVRG3
Adder
22.932
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
15.473
339241AF1-083 GEN
Solar/Wind Harmer
1.713
943111AE2-339 GEN
Solar/Wind Harmer
0.882
945681AF1-233 GEN
Solar/Wind Harmer
18.298
252516AE2-318_GEN
Solar/Wind Harmer
9.197
25194608D.CRK4
Adder
1.506
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
7.586
946171AF1-282 GEN
Solar/Wind Harmer
9.062
274848CAMPGROVE;RU
Solar/Wind Harmer
5.723
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274745AC1-111 GEN9
Adder
4.865
274676JOLIET 29;8U
Adder
26.611
316499AE2-029_GEN
Solar/Wind Helper
1.726
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
971881AH1-461 GEN
50/50
14.967
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.906
960911AF2-382 GEN
Solar/Wind Harmer
10.939
972103AH1-617 GEN
Solar/Wind Harmer
25.812
24721905FLATG4
Adder
21.662
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
252524AE2-267 GEN
Solar/Wind Harmer
1.44
957381AF2-032 GEN
Solar/Wind Harmer
1.819
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
7.586
946181AF1-283 GEN
Solar/Wind Harmer
11.78
276785W4-005 GEN1
Solar/Wind Harmer
2.723
971087AG2-675 GEN
Solar/Wind Harmer
3.318
274767LEE CO EC;8U
Adder
8.117
274682WAUKEGAN ;7U
Adder
15.687
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
316192AB2-158 GEN
Solar/Wind Helper
1.845
316447AC1-158 HLD
Solar/Wind Helper
2.777
24684605SMG4
50/50
2.21
970563AG2-360 GEN
50/50
45.796
962751AG1-124 GEN
Solar/Wind Harmer
18.814
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.247
972273AH1-721 GEN
Adder
89.23
970093AG2-073 GEN
Solar/Wind Harmer
5.438
971191AH1-055 GEN
Solar/Wind Harmer
18.807
972167AH1-666 GEN
Solar/Wind Harmer
7.758
270186AC1-089 GEN
Solar/Wind Harmer
5.812
270367AC2-061_GEN
Solar/Wind Harmer
3
25196008MFTGT1
Adder
1.251
970879AG2-548 GEN
Solar/Wind Harmer
7.33
942481AE2-261 GEN
Solar/Wind Harmer
27.203
971993AH1-541 GEN
Solar/Wind Harmer
8.32
253394AE2-221_GEN
Solar/Wind Harmer
4.05
274729ELWOOD EC;1P
Adder
14.264
3147983MERCK5
Solar/Wind Helper
0.198
24684305SMG1
50/50
0.795
971329AH1-144 GEN
Solar/Wind Harmer
11.722
24734805WLF1G4
Adder
8.187
24735105WLF2G1
Adder
8.017
270400AC1-102 GEN
Solar/Wind Harmer
5.551
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
5.752
270053AF1-130 C
Solar/Wind Harmer
22.985
3429211JKCT 2G
Adder
11.861
972163AH1-664 GEN
Solar/Wind Harmer
9.732
944221AF1-090 GEN
Solar/Wind Harmer
10.014
25196508WSDLE4
Adder
7.759
270356AE2-297 GEN
Solar/Wind Harmer
4.141
963841AG1-237 GEN
Solar/Wind Harmer
9.746
274854TWINGROVE;U2
Solar/Wind Harmer
6.28
270340AC2-060 GEN
Solar/Wind Harmer
2.683
276726Z2-087_GEN
Solar/Wind Harmer
7.014
274746AC1-111 G10
Adder
4.865
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
316164AC1-076 GEN
Solar/Wind Helper
1.176
270583AD2-179 GEN
Solar/Wind Harmer
20.71
270214AC2-123 GEN
Solar/Wind Harmer
4.308
971225AH1-072 GEN
Solar/Wind Harmer
2.728
971227AH1-073 GEN
Solar/Wind Harmer
2.728
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
971125AH1-004 GEN
Solar/Wind Harmer
3.985
276916AD2-100_GEN
Solar/Wind Harmer
19.136
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
270013AE1-250 PV
Solar/Wind Harmer
3.247
339236AF1-050_GEN
Solar/Wind Harmer
1.871
970107AG2-081 GEN
Solar/Wind Harmer
2.988
962581AG1-107 GEN
Solar/Wind Harmer
4.724
961491AF2-440 GEN
Solar/Wind Harmer
1.963
970879AG2-548 GEN
Solar/Wind Harmer
1.065
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.723
276174W4-005 GEN2
Solar/Wind Harmer
2.723
970241AG2-163 GEN
Solar/Wind Harmer
22.405
960201AF2-311 GEN
Solar/Wind Harmer
8.913
942111AE2-223 GEN
Solar/Wind Harmer
7.272
274762LEE CO EC;3U
Adder
8.213
274696ROCKY RD ;4P
Adder
9.947
274697ROCKY RD ;3P
Adder
2.64
237061AD1-155 GEN
Solar/Wind Helper
1.647
24387305FR-4G C
Solar/Wind Harmer
2.467
24684505SMG3
50/50
1.341
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.358
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252510AF1-249 C
Solar/Wind Harmer
0.383
276621W2-048 GEN
Solar/Wind Harmer
5.637
253398AE2-221_GEN2
Solar/Wind Harmer
4.05
939741AE1-205 GEN
Solar/Wind Harmer
17.741
274761LEE CO EC;2U
Adder
8.213
315821AE2-092 GEN
Solar/Wind Helper
3.23
23583801GRNGAP
Solar/Wind Helper
4.295
24386605FR-22G C
Solar/Wind Harmer
2.088
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
9.321
971061AG2-657 GEN
Solar/Wind Harmer
10.98
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.662
971485AH1-239 GEN
Solar/Wind Harmer
8.488
964781AG1-341 GEN
Solar/Wind Harmer
10.959
942891AE2-308 GEN
Solar/Wind Harmer
10.165
972043AH1-570 GEN
Solar/Wind Harmer
2.472
25194408D.CRK1
Adder
6.93
945391AF1-204 GEN
Solar/Wind Harmer
12.706
276615X2-022 GEN
Solar/Wind Harmer
1.77
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
13.37
960611AF2-352 GEN
Solar/Wind Harmer
2.071
274764LEE CO EC;5U
Adder
8.233
972235AH1-702 GEN1
Adder
2.217
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274693ROCKY RD ;1P
Adder
9.622
274674JOLIET 9 ;6U
Adder
13.36
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316450AC1-158 RIC
Solar/Wind Helper
0.337
24728205BUCHG1
50/50
7.157
971277AH1-098 GEN
Solar/Wind Harmer
7.416
970913AG2-568 GEN
Solar/Wind Harmer
9.332
942751AE2-291 GEN
Solar/Wind Harmer
10.374
966021AG1-471 GEN
Solar/Wind Harmer
5.747
339231AF1-038_GEN
Solar/Wind Harmer
1.916
964571AG1-320 GEN
Solar/Wind Harmer
8.178
972045AH1-571 GEN
Solar/Wind Harmer
1.978
927014AC1-188 GEN
Solar/Wind Harmer
1.526
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.565
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.33
276911AD2-131_GEN
Solar/Wind Harmer
3.867
24728805RICHG1
Adder
3.383
274765LEE CO EC;6U
Adder
8.233
274763LEE CO EC;4U
Adder
8.136
972236AH1-702 GEN2
Adder
1.928
274695ROCKY RD ;2P
Adder
9.717
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
966391AG1-508 GEN
Solar/Wind Harmer
6.371
270069AE2-166 C O1
Solar/Wind Harmer
14.87
24734705WLF1G3
Adder
8.187
24734905WLF1G5
Adder
8.187
270399AC1-101 GEN
Solar/Wind Harmer
5.551
971981AH1-535 GEN
Solar/Wind Harmer
12.552
339216AC1-074 GEN
Solar/Wind Harmer
1.642
972165AH1-665 GEN
Solar/Wind Harmer
7.785
971985AH1-537 GEN
Solar/Wind Harmer
17.275
253406AD2-031_GEN
Solar/Wind Harmer
1.145
946321AF1-296 GEN
Solar/Wind Harmer
9.291
274853TWINGROVE;U1
Solar/Wind Harmer
6.415
270291AC1-194 GEN
Solar/Wind Harmer
4.529
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
315616AA1-038_C
Solar/Wind Helper
3.297
3148013FISHERV
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.267
24386405FR-21G C
Solar/Wind Harmer
2.088
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.731
958121AF2-106 GEN
Solar/Wind Harmer
9.401
270346AE1-212 GEN
Solar/Wind Harmer
13.925
270018AE2-047 C O1
Solar/Wind Harmer
1.82
971461AH1-227 GEN
Solar/Wind Harmer
6.998
970223AG2-152 GEN
Solar/Wind Harmer
17.657
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
3429391JKCT 9G
Adder
8.393
957541AF2-048 GEN
Solar/Wind Harmer
1.526
958171AF2-111 GEN
Solar/Wind Harmer
23.881
252507AC2-088 GEN
Solar/Wind Harmer
1.664
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
13.676
24728705AND G3
Adder
7.274
959611AF2-252 GEN
Solar/Wind Harmer
2.071
274730ELWOOD EC;6P
Adder
14.264
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316044AC1-158 PL1
Solar/Wind Helper
1.262
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.195
24728305BUCHG2
50/50
7.157
316217AC1-145 GEN
Solar/Wind Harmer
4.241
316197AC1-042 GEN
Solar/Wind Harmer
3.215
24686505CER G6
Adder
9.865
339211AE2-254 GEN
Solar/Wind Harmer
1.559
3429241JKCT 3G
Adder
12.016
965911AG1-460 GEN
Solar/Wind Harmer
1.269
944031AF1-071 GEN
Solar/Wind Harmer
0.897
276656WTG2_EQ
Solar/Wind Harmer
1.025
274766LEE CO EC;7U
Adder
8.117
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
24385905FR-11G C
Solar/Wind Harmer
4.036
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.443
958131AF2-107 GEN
Solar/Wind Harmer
7.102
971403AH1-188 GEN
Solar/Wind Harmer
18.836
944971AF1-162 GEN
Solar/Wind Harmer
9.06
960001AF2-291 GEN
Solar/Wind Harmer
3.11
970653AG2-424 GEN
Solar/Wind Harmer
4.877
3429421JKCT 10G
Adder
8.393
339221AD2-048_GEN
Solar/Wind Harmer
1.508
970091AG2-072 GEN
Adder
73.941
971073AG2-665 GEN
Solar/Wind Harmer
1.065
276686W4-005 GEN3
Solar/Wind Harmer
2.723
963741AG1-226 GEN
Solar/Wind Harmer
40.329
270222AC2-111 GEN
Solar/Wind Harmer
3.988
276655WTG1_EQ
Solar/Wind Harmer
7.743
274822ROCKFORD ;11
Adder
17.258
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.805
24686405CER G5
Adder
9.787
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
339255AE2-071 GEN
Solar/Wind Harmer
1.216
339250AF1-203 GEN
Solar/Wind Harmer
0.626
339206AE1-143 GEN
Solar/Wind Harmer
2.202
970653AG2-424 GEN
Solar/Wind Harmer
0.705
970455AG2-298 GEN
Solar/Wind Harmer
3.516
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
965931AG1-462 GEN
Solar/Wind Harmer
22.737
965091AG1-374 GEN
Solar/Wind Harmer
26.711
274760LEE CO EC;1U
Adder
8.213
24386205FR-12G C
Solar/Wind Harmer
2.081
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
274728ELWOOD EC;5P
Adder
14.264
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.089
24387005FR-3G C
Solar/Wind Harmer
1.921
270197AD1-017 GEN1
Solar/Wind Harmer
2.54
970281AG2-184 GEN
Solar/Wind Harmer
27.103
962211AG1-066 GEN
Solar/Wind Harmer
2.998
270444AC2-157 GEN1
Solar/Wind Harmer
5.231
270445AC2-157 GEN2
Solar/Wind Harmer
5.231
253433AC1-085 GEN1
Solar/Wind Harmer
4.815
253432AC1-085 GEN2
Solar/Wind Harmer
0.242
276763AC1-053 GEN1
Solar/Wind Harmer
3.564
276764AC1-053 GEN2
Solar/Wind Harmer
3.564
276668AB2-070 GEN1
Solar/Wind Harmer
1.994
276848AB2-070 GEN3
Solar/Wind Harmer
1.994
276849AB2-070 GEN2
Solar/Wind Harmer
1.994
959341AF2-225 GEN
Solar/Wind Harmer
13.306
274744AC1-111 GEN8
Adder
4.865
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
TVALTFEXP_TVA->PJM
CLTF
10.596
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4149.41
MW Contribution:
9.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24735205WLF2G2
Adder
8.021
24723205RIVRG3
Adder
22.944
972203AH1-686 GEN
Adder
2.703
964901AG1-354 GEN
Solar/Wind Harmer
15.482
339241AF1-083 GEN
Solar/Wind Harmer
1.714
943111AE2-339 GEN
Solar/Wind Harmer
0.882
945681AF1-233 GEN
Solar/Wind Harmer
18.311
252516AE2-318_GEN
Solar/Wind Harmer
9.203
25194608D.CRK4
Adder
1.508
24728605AND G2
Adder
3.48
253316AC1-085 GEN3
Solar/Wind Harmer
7.592
946171AF1-282 GEN
Solar/Wind Harmer
9.068
274848CAMPGROVE;RU
Solar/Wind Harmer
5.727
274828WAUKEGAN ;BP
Adder
9.652
274682WAUKEGAN ;7U
Adder
15.699
274745AC1-111 GEN9
Adder
4.868
274676JOLIET 29;8U
Adder
26.631
316499AE2-029_GEN
Solar/Wind Helper
1.725
316095T157 G97
Solar/Wind Helper
1.127
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
971881AH1-461 GEN
50/50
14.973
943031AE2-326 GEN
Solar/Wind Harmer
6.783
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.919
960911AF2-382 GEN
Solar/Wind Harmer
10.944
972103AH1-617 GEN
Solar/Wind Harmer
25.825
24721905FLATG4
Adder
21.675
252519AF1-045_GEN
Solar/Wind Harmer
3.349
25194608D.CRK4
Adder
1.508
252524AE2-267 GEN
Solar/Wind Harmer
1.441
957381AF2-032 GEN
Solar/Wind Harmer
1.82
24728505AND G1
Adder
3.48
253317AC1-085 GEN4
Solar/Wind Harmer
7.592
946181AF1-283 GEN
Solar/Wind Harmer
11.789
276785W4-005 GEN1
Solar/Wind Harmer
2.725
971087AG2-675 GEN
Solar/Wind Harmer
3.32
274767LEE CO EC;8U
Adder
8.123
274682WAUKEGAN ;7U
Adder
15.699
274734ELWOOD EC;8P
Adder
14.275
274736ELWOOD EC;9P
Adder
14.275
24684605SMG4
50/50
2.211
970563AG2-360 GEN
50/50
45.815
962751AG1-124 GEN
Solar/Wind Harmer
18.82
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.249
972273AH1-721 GEN
Adder
89.284
970093AG2-073 GEN
Solar/Wind Harmer
5.442
971191AH1-055 GEN
Solar/Wind Harmer
18.819
972167AH1-666 GEN
Solar/Wind Harmer
7.764
270186AC1-089 GEN
Solar/Wind Harmer
5.816
270367AC2-061_GEN
Solar/Wind Harmer
3.002
25196008MFTGT1
Adder
1.252
970879AG2-548 GEN
Solar/Wind Harmer
7.336
942481AE2-261 GEN
Solar/Wind Harmer
27.222
971993AH1-541 GEN
Solar/Wind Harmer
8.326
253394AE2-221_GEN
Solar/Wind Harmer
4.053
24684305SMG1
50/50
0.796
971329AH1-144 GEN
Solar/Wind Harmer
11.725
24734805WLF1G4
Adder
8.191
24735105WLF2G1
Adder
8.021
270400AC1-102 GEN
Solar/Wind Harmer
5.554
941621AE2-160 GEN
Adder
4.283
957241AF2-018 GEN
Solar/Wind Harmer
5.755
270053AF1-130 C
Solar/Wind Harmer
22.996
3429211JKCT 2G
Adder
11.868
972163AH1-664 GEN
Solar/Wind Harmer
9.738
944221AF1-090 GEN
Solar/Wind Harmer
10.021
25196508WSDLE4
Adder
7.765
270356AE2-297 GEN
Solar/Wind Harmer
4.144
963841AG1-237 GEN
Solar/Wind Harmer
9.753
274854TWINGROVE;U2
Solar/Wind Harmer
6.285
270340AC2-060 GEN
Solar/Wind Harmer
2.685
276726Z2-087_GEN
Solar/Wind Harmer
7.019
274746AC1-111 G10
Adder
4.868
274731ELWOOD EC;2P
Adder
14.275
274733ELWOOD EC;3P
Adder
14.275
316164AC1-076 GEN
Solar/Wind Helper
1.176
316192AB2-158 GEN
Solar/Wind Helper
1.844
316447AC1-158 HLD
Solar/Wind Helper
2.775
270583AD2-179 GEN
Solar/Wind Harmer
20.716
270214AC2-123 GEN
Solar/Wind Harmer
4.31
971225AH1-072 GEN
Solar/Wind Harmer
2.729
971227AH1-073 GEN
Solar/Wind Harmer
2.729
24723005RIVRG1
Adder
22.944
24723105RIVRG2
Adder
22.944
971125AH1-004 GEN
Solar/Wind Harmer
3.987
276916AD2-100_GEN
Solar/Wind Harmer
19.15
316097T157 G90
Solar/Wind Helper
1.127
238147AE2-230_GEN1
Solar/Wind Helper
0.423
270013AE1-250 PV
Solar/Wind Harmer
3.249
339236AF1-050_GEN
Solar/Wind Harmer
1.872
970107AG2-081 GEN
Solar/Wind Harmer
2.99
962581AG1-107 GEN
Solar/Wind Harmer
4.728
961491AF2-440 GEN
Solar/Wind Harmer
1.965
970879AG2-548 GEN
Solar/Wind Harmer
1.066
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276174W4-005 GEN2
Solar/Wind Harmer
2.725
970241AG2-163 GEN
Solar/Wind Harmer
22.421
960201AF2-311 GEN
Solar/Wind Harmer
8.92
942111AE2-223 GEN
Solar/Wind Harmer
7.277
274762LEE CO EC;3U
Adder
8.219
274696ROCKY RD ;4P
Adder
9.954
274697ROCKY RD ;3P
Adder
2.642
237061AD1-155 GEN
Solar/Wind Helper
1.646
24387305FR-4G C
Solar/Wind Harmer
2.468
24684505SMG3
50/50
1.342
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.358
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
70.578
25196008MFTGT1
Adder
1.293
252510AF1-249 C
Solar/Wind Harmer
0.383
276621W2-048 GEN
Solar/Wind Harmer
5.641
253398AE2-221_GEN2
Solar/Wind Harmer
4.053
939741AE1-205 GEN
Solar/Wind Harmer
17.754
274761LEE CO EC;2U
Adder
8.219
315821AE2-092 GEN
Solar/Wind Helper
3.228
23583801GRNGAP
Solar/Wind Helper
4.293
24386605FR-22G C
Solar/Wind Harmer
2.09
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.665
971485AH1-239 GEN
Solar/Wind Harmer
8.494
964781AG1-341 GEN
Solar/Wind Harmer
10.966
942891AE2-308 GEN
Solar/Wind Harmer
10.171
972043AH1-570 GEN
Solar/Wind Harmer
2.474
25194408D.CRK1
Adder
6.935
945391AF1-204 GEN
Solar/Wind Harmer
12.715
276615X2-022 GEN
Solar/Wind Harmer
1.772
24728905RICHG2
Adder
3.386
960251AF2-316 GEN
Solar/Wind Harmer
13.38
960611AF2-352 GEN
Solar/Wind Harmer
2.072
274764LEE CO EC;5U
Adder
8.239
972235AH1-702 GEN1
Adder
2.219
274683WAUKEGAN ;8U
Adder
18.414
274683WAUKEGAN ;8U
Adder
15.522
274693ROCKY RD ;1P
Adder
9.629
274674JOLIET 9 ;6U
Adder
13.37
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316450AC1-158 RIC
Solar/Wind Helper
0.336
24728205BUCHG1
50/50
7.16
971277AH1-098 GEN
Solar/Wind Harmer
7.418
970913AG2-568 GEN
Solar/Wind Harmer
9.337
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.751
339231AF1-038_GEN
Solar/Wind Harmer
1.917
964571AG1-320 GEN
Solar/Wind Harmer
8.183
972045AH1-571 GEN
Solar/Wind Harmer
1.979
927014AC1-188 GEN
Solar/Wind Harmer
1.527
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.569
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.336
276911AD2-131_GEN
Solar/Wind Harmer
3.87
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.357
966391AG1-508 GEN
Solar/Wind Harmer
6.373
270069AE2-166 C O1
Solar/Wind Harmer
14.876
24734705WLF1G3
Adder
8.191
24734905WLF1G5
Adder
8.191
270399AC1-101 GEN
Solar/Wind Harmer
5.554
971981AH1-535 GEN
Solar/Wind Harmer
12.558
339216AC1-074 GEN
Solar/Wind Harmer
1.643
972165AH1-665 GEN
Solar/Wind Harmer
7.79
971985AH1-537 GEN
Solar/Wind Harmer
17.286
253406AD2-031_GEN
Solar/Wind Harmer
1.146
946321AF1-296 GEN
Solar/Wind Harmer
9.297
274853TWINGROVE;U1
Solar/Wind Harmer
6.419
270291AC1-194 GEN
Solar/Wind Harmer
4.532
972267AH1-718 GEN
Adder
3.687
274823ROCKFORD ;21
Adder
17.145
274675JOLIET 29;7U
Adder
26.631
274675JOLIET 29;7U
Adder
7.641
315616AA1-038_C
Solar/Wind Helper
3.296
3148013FISHERV
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.266
24386405FR-21G C
Solar/Wind Harmer
2.09
970823AG2-518 GEN
50/50
8.382
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.733
958121AF2-106 GEN
Solar/Wind Harmer
9.404
270346AE1-212 GEN
Solar/Wind Harmer
13.931
270018AE2-047 C O1
Solar/Wind Harmer
1.821
971461AH1-227 GEN
Solar/Wind Harmer
7.001
970223AG2-152 GEN
Solar/Wind Harmer
17.666
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
3429391JKCT 9G
Adder
8.399
957541AF2-048 GEN
Solar/Wind Harmer
1.527
958171AF2-111 GEN
Solar/Wind Harmer
23.897
252507AC2-088 GEN
Solar/Wind Harmer
1.666
25196608WSDLE5
Adder
7.845
970193AG2-126 GEN
Solar/Wind Harmer
13.686
24728705AND G3
Adder
7.279
959611AF2-252 GEN
Solar/Wind Harmer
2.072
274730ELWOOD EC;6P
Adder
14.275
3147666LOUISA
Solar/Wind Helper
1.088
238152AF2-075_GEN
Solar/Wind Helper
0.604
316044AC1-158 PL1
Solar/Wind Helper
1.261
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.196
24728305BUCHG2
50/50
7.16
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
24686505CER G6
Adder
9.87
339211AE2-254 GEN
Solar/Wind Harmer
1.56
3429241JKCT 3G
Adder
12.024
965911AG1-460 GEN
Solar/Wind Harmer
1.27
944031AF1-071 GEN
Solar/Wind Harmer
0.898
276656WTG2_EQ
Solar/Wind Harmer
1.026
274766LEE CO EC;7U
Adder
8.123
274732ELWOOD EC;7P
Adder
14.275
274674JOLIET 9 ;6U
Adder
13.37
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
24385905FR-11G C
Solar/Wind Harmer
4.039
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.444
958131AF2-107 GEN
Solar/Wind Harmer
7.106
971403AH1-188 GEN
Solar/Wind Harmer
18.845
944971AF1-162 GEN
Solar/Wind Harmer
9.064
960001AF2-291 GEN
Solar/Wind Harmer
3.112
970653AG2-424 GEN
Solar/Wind Harmer
4.88
3429421JKCT 10G
Adder
8.399
339221AD2-048_GEN
Solar/Wind Harmer
1.509
970091AG2-072 GEN
Adder
73.991
971073AG2-665 GEN
Solar/Wind Harmer
1.066
276686W4-005 GEN3
Solar/Wind Harmer
2.725
963741AG1-226 GEN
Solar/Wind Harmer
40.358
270222AC2-111 GEN
Solar/Wind Harmer
3.991
276655WTG1_EQ
Solar/Wind Harmer
7.748
274822ROCKFORD ;11
Adder
17.27
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.809
24686405CER G5
Adder
9.792
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
339255AE2-071 GEN
Solar/Wind Harmer
1.217
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.203
970653AG2-424 GEN
Solar/Wind Harmer
0.706
970455AG2-298 GEN
Solar/Wind Harmer
3.519
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
965931AG1-462 GEN
Solar/Wind Harmer
22.754
965091AG1-374 GEN
Solar/Wind Harmer
26.73
274760LEE CO EC;1U
Adder
8.219
24386205FR-12G C
Solar/Wind Harmer
2.082
971543AH1-269 GEN
50/50
12.244
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
9.325
971061AG2-657 GEN
Solar/Wind Harmer
10.986
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.323
25196408WSDLE3
Adder
8.076
25196308WSDLE2
Adder
8.005
25196208WSDLE1
Adder
7.985
25196708WSDLE6
Adder
7.965
274728ELWOOD EC;5P
Adder
14.275
3148133STUARTS
Solar/Wind Helper
0.313
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.088
24387005FR-3G C
Solar/Wind Harmer
1.922
24728805RICHG1
Adder
3.386
274765LEE CO EC;6U
Adder
8.239
274763LEE CO EC;4U
Adder
8.142
972236AH1-702 GEN2
Adder
1.93
274695ROCKY RD ;2P
Adder
9.725
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.036
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
970281AG2-184 GEN
Solar/Wind Harmer
27.117
962211AG1-066 GEN
Solar/Wind Harmer
3
270444AC2-157 GEN1
Solar/Wind Harmer
5.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.235
253433AC1-085 GEN1
Solar/Wind Harmer
4.819
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.567
276764AC1-053 GEN2
Solar/Wind Harmer
3.567
276668AB2-070 GEN1
Solar/Wind Harmer
1.995
276848AB2-070 GEN3
Solar/Wind Harmer
1.995
276849AB2-070 GEN2
Solar/Wind Harmer
1.995
959341AF2-225 GEN
Solar/Wind Harmer
13.316
274744AC1-111 GEN8
Adder
4.868
274735ELWOOD EC;4P
Adder
14.275
25306009OHH W.
Adder
2.502
3148463FAIRFLD
Solar/Wind Helper
0.726
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.842
274729ELWOOD EC;1P
Adder
14.275
3147983MERCK5
Solar/Wind Helper
0.198
CPLELTFEXP_CPLE->PJM
CLTF
6.22
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.073
LAGNLTFEXP_LAGN->PJM
CLTF
20.273
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.54
NYPJM->LTFIMP_NY
CLTF
3.251
LGEELTFEXP_LGEE->PJM
CLTF
6.761
TVALTFEXP_TVA->PJM
CLTF
10.603
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.302
MECLTFEXP_MEC->PJM
CLTF
15.41
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.32 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6590.12
MW Contribution:
8.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
31.268
962211AG1-066 GEN
Solar/Wind Harmer
3.415
270444AC2-157 GEN1
Solar/Wind Harmer
7.062
270445AC2-157 GEN2
Solar/Wind Harmer
7.062
276668AB2-070 GEN1
Solar/Wind Harmer
2.697
276848AB2-070 GEN3
Solar/Wind Harmer
2.697
276849AB2-070 GEN2
Solar/Wind Harmer
2.697
276763AC1-053 GEN1
Solar/Wind Harmer
4.814
276764AC1-053 GEN2
Solar/Wind Harmer
4.814
959341AF2-225 GEN
Solar/Wind Harmer
18.256
970169AG2-114 GEN
Solar/Wind Harmer
12.163
274744AC1-111 GEN8
Adder
6.785
958391AF2-133 GEN
Solar/Wind Harmer
11.004
972227AH1-698 GEN1
Adder
3.164
274735ELWOOD EC;4P
Adder
19.933
243186AF1-051 GEN
50/50
13.022
24721805FLATG3
50/50
2.938
970155AG2-107 GEN
Solar/Wind Harmer
29.364
24723205RIVRG3
Adder
35.405
962761AG1-125 GEN
Solar/Wind Harmer
67.342
24686505CER G6
Adder
15.123
24728305BUCHG2
Adder
6.758
24385905FR-11G C
Solar/Wind Harmer
10.201
965911AG1-460 GEN
Solar/Wind Harmer
1.699
276656WTG2_EQ
Solar/Wind Harmer
1.406
939401AE1-172 GEN
Solar/Wind Harmer
16.947
274674JOLIET 9 ;6U
Adder
18.672
274732ELWOOD EC;7P
Adder
19.933
274766LEE CO EC;7U
Adder
11.133
274802UNIV PARK;5U
Adder
6.986
20089026BF_G21_K23
Solar/Wind Helper
0.468
20084626FORWARD
Solar/Wind Helper
0.35
203855AF2-088 C
Solar/Wind Helper
0.149
203947AF1-006 C
Solar/Wind Helper
0.483
24289405MTG1
50/50
11.749
970149AG2-104 GEN
Solar/Wind Harmer
41.584
944971AF1-162 GEN
Solar/Wind Harmer
11.902
971403AH1-188 GEN
Solar/Wind Harmer
23.698
960001AF2-291 GEN
Solar/Wind Harmer
4.817
970091AG2-072 GEN
Adder
102.767
963741AG1-226 GEN
Solar/Wind Harmer
55.212
24791305MDL-5G
Solar/Wind Harmer
2.954
276686W4-005 GEN3
Solar/Wind Harmer
3.683
276655WTG1_EQ
Solar/Wind Harmer
10.623
941551AE2-152 GEN
Solar/Wind Harmer
5.509
274822ROCKFORD ;11
Adder
23.778
24721605FLATG1
50/50
2.938
957241AF2-018 GEN
Solar/Wind Harmer
7.557
270053AF1-130 C
Solar/Wind Harmer
30.195
270400AC1-102 GEN
Solar/Wind Harmer
7.142
941621AE2-160 GEN
Adder
5.016
24734805WLF1G4
Adder
7.988
24735105WLF2G1
Adder
7.848
971329AH1-144 GEN
Solar/Wind Harmer
7.552
963841AG1-237 GEN
Solar/Wind Harmer
13.411
946581AF1-322 GEN
Solar/Wind Harmer
12.536
274776LINCOLN ;7U
Adder
7.555
944221AF1-090 GEN
Solar/Wind Harmer
13.317
274854TWINGROVE;U2
Solar/Wind Harmer
8.585
276726Z2-087_GEN
Solar/Wind Harmer
9.623
274746AC1-111 G10
Adder
6.785
274731ELWOOD EC;2P
Adder
19.933
274733ELWOOD EC;3P
Adder
19.933
274687WILL CNTY;4U
Adder
33.865
274687WILL CNTY;4U
Adder
33.865
23750501ELLIOTTS
Solar/Wind Helper
0.679
241982AE2-343 S C
Solar/Wind Helper
0.221
238118U2-030_1
Solar/Wind Helper
0.291
20089126CSLMN_L13
Solar/Wind Helper
0.591
20088926STNY CRK
Solar/Wind Helper
0.806
20094526CT_V3-030
Solar/Wind Helper
0.462
20088626ARWF_N39
Solar/Wind Helper
1.182
20334926Z1-069 C
Solar/Wind Helper
1.308
926823AC1-168 GEN
Solar/Wind Harmer
0.606
966841AG1-555 GEN
Solar/Wind Harmer
3.081
945391AF1-204 GEN
Solar/Wind Harmer
17.098
24697605MDL-3G C
Solar/Wind Harmer
4.516
270181AB1-006 GEN2
Solar/Wind Harmer
0.876
276615X2-022 GEN
Solar/Wind Harmer
2.385
960611AF2-352 GEN
Solar/Wind Harmer
2.831
274693ROCKY RD ;1P
Adder
13.373
274674JOLIET 9 ;6U
Adder
18.672
274683WAUKEGAN ;8U
Adder
25.548
274683WAUKEGAN ;8U
Adder
21.536
972235AH1-702 GEN1
Adder
3.053
274764LEE CO EC;5U
Adder
11.292
23585401KL_K28_T16
Solar/Wind Helper
1.305
254305AE2-115 C
Solar/Wind Helper
0.216
241967AE2-285_GEN
Solar/Wind Helper
0.629
238117U2-030
Solar/Wind Helper
0.291
20083426SW_E13_K22
Solar/Wind Helper
0.055
946071AF1-272 GEN
Solar/Wind Helper
2.663
20088826HIGHLAND
Solar/Wind Helper
0.88
970913AG2-568 GEN
Solar/Wind Harmer
10.639
24728205BUCHG1
Adder
6.758
971277AH1-098 GEN
Solar/Wind Harmer
5.287
927014AC1-188 GEN
Solar/Wind Harmer
1.995
270180AB1-006 GEN1
Solar/Wind Harmer
8.812
24697905MDL-4G C
Solar/Wind Harmer
2.811
945421AF1-207 GEN
Solar/Wind Harmer
17.195
276911AD2-131_GEN
Solar/Wind Harmer
5.168
274695ROCKY RD ;2P
Adder
13.506
972236AH1-702 GEN2
Adder
2.655
274765LEE CO EC;6U
Adder
11.292
274763LEE CO EC;4U
Adder
11.16
254304AE2-114 C
Solar/Wind Helper
0.216
235054AD2-180 GEN
Solar/Wind Helper
1.728
235531U2-073 GEN
Solar/Wind Helper
2.761
203961AE2-224 GEN
Solar/Wind Helper
2.354
946381AF1-302 GEN
Solar/Wind Helper
0.217
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
971461AH1-227 GEN
Solar/Wind Harmer
7.556
270346AE1-212 GEN
Solar/Wind Harmer
12.339
957541AF2-048 GEN
Solar/Wind Harmer
1.995
970193AG2-126 GEN
Solar/Wind Harmer
18.403
970781AG2-491 GEN
Solar/Wind Harmer
12.252
958121AF2-106 GEN
Solar/Wind Harmer
5.546
959611AF2-252 GEN
Solar/Wind Harmer
2.831
970707AG2-453 GEN
Solar/Wind Harmer
34.064
939351AE1-166 GEN
Solar/Wind Harmer
7.204
274730ELWOOD EC;6P
Adder
19.933
274826FISK ;BP
Adder
13.253
202652Y1-033 WT C
Solar/Wind Helper
0.565
238127S14_GEN_2
Solar/Wind Helper
0.686
20092526R32
Solar/Wind Helper
1.14
20398826ARMNA MT
Solar/Wind Helper
1.443
941421AE2-139 GEN
Solar/Wind Helper
2.224
24289405MTG1
50/50
11.749
24686405CER G5
Adder
15.004
270329AC1-082 GEN1
Solar/Wind Harmer
0.789
24386205FR-12G C
Solar/Wind Harmer
5.26
24690905MDL-1G C
Solar/Wind Harmer
9.836
965091AG1-374 GEN
Solar/Wind Harmer
36.515
972038AH1-567 GEN2
Adder
0.442
274760LEE CO EC;1U
Adder
11.266
23562501BACKB
Solar/Wind Helper
0.911
203854AF2-039 C
Solar/Wind Helper
0.309
238108AE1-109 GEN1
Solar/Wind Helper
0.086
962511AG1-100 GEN
Solar/Wind Helper
0.445
972203AH1-686 GEN
Adder
4.304
24735205WLF2G2
Adder
7.848
972207SS24-0001
Solar/Wind Harmer
26.861
274871GR RIDGE ;2U
Solar/Wind Harmer
9.337
274847GR RIDGE ;BU
Solar/Wind Harmer
6.14
274745AC1-111 GEN9
Adder
6.785
274682WAUKEGAN ;7U
Adder
21.789
274676JOLIET 29;8U
Adder
37.198
274828WAUKEGAN ;BP
Adder
13.392
238185AF2-356 C
Solar/Wind Helper
2.23
241966AE1-183 GEN
Solar/Wind Helper
0.252
238120AE2-309 GEN
Solar/Wind Helper
0.432
964201AG1-281 GEN
Solar/Wind Helper
0.472
23751101LEADS_P59
Solar/Wind Helper
1.885
20091526CHSTN_FL
Solar/Wind Helper
0.569
20090526Q36
Solar/Wind Helper
1
203952AE2-129 C
Solar/Wind Helper
0.461
238109AE1-109 GEN2
Solar/Wind Helper
0.086
203830AF1-094 GEN
Solar/Wind Helper
0.449
203979AG1-198 GEN
Solar/Wind Helper
0.27
270399AC1-101 GEN
Solar/Wind Harmer
7.142
24734705WLF1G3
Adder
7.988
24734905WLF1G5
Adder
7.988
966391AG1-508 GEN
Solar/Wind Harmer
4.607
971985AH1-537 GEN
Solar/Wind Harmer
23.357
971331AH1-145 GEN
Solar/Wind Harmer
11.822
971981AH1-535 GEN
Solar/Wind Harmer
12.497
24386405FR-21G C
Solar/Wind Harmer
5.279
274775LINCOLN ;6U
Adder
7.555
274777LINCOLN ;8U
Adder
7.555
274853TWINGROVE;U1
Solar/Wind Harmer
8.769
959141AF2-205 GEN
Solar/Wind Harmer
7.348
970833AG2-524 GEN
Solar/Wind Harmer
10.601
970833AG2-524 GEN
Solar/Wind Harmer
4.931
972228AH1-698 GEN2
Adder
4.493
274675JOLIET 29;7U
Adder
37.198
24722005FLATG5
50/50
2.938
24721905FLATG4
50/50
53.66
962771AG1-126 GEN
Solar/Wind Harmer
67.342
970153AG2-106 GEN
Solar/Wind Harmer
29.364
960911AF2-382 GEN
Solar/Wind Harmer
11.34
972103AH1-617 GEN
Solar/Wind Harmer
29.779
943031AE2-326 GEN
Solar/Wind Harmer
4.878
276785W4-005 GEN1
Solar/Wind Harmer
3.683
957381AF2-032 GEN
Solar/Wind Harmer
2.435
943121AE2-341 GEN
Solar/Wind Harmer
18.219
943591AF1-030 GEN
Solar/Wind Harmer
12.146
274734ELWOOD EC;8P
Adder
19.933
274736ELWOOD EC;9P
Adder
19.933
274682WAUKEGAN ;7U
Adder
21.789
274676JOLIET 29;8U
Adder
35.87
274767LEE CO EC;8U
Adder
11.133
235058AG1-386 C
Solar/Wind Helper
0.46
964991AG1-363 GEN
Solar/Wind Helper
3.718
20303426NA_O38_P22
Solar/Wind Helper
0.969
203993AD2-133_GEN1
Solar/Wind Helper
1
238110AE1-109 GEN3
Solar/Wind Helper
0.086
24318705GVG2
50/50
12.071
270331AC1-082 GEN3
Solar/Wind Harmer
0.791
971687AH1-348 GEN
Solar/Wind Harmer
1.473
24386605FR-22G C
Solar/Wind Harmer
5.279
274773LINCOLN ;4U
Adder
7.555
274774LINCOLN ;5U
Adder
7.555
276621W2-048 GEN
Solar/Wind Harmer
7.596
940581AE2-045 GEN
Solar/Wind Harmer
12.418
971605AH1-302 GEN
Solar/Wind Harmer
10.618
939741AE1-205 GEN
Solar/Wind Harmer
24.341
971997AH1-543 GEN
Solar/Wind Harmer
19.104
274761LEE CO EC;2U
Adder
11.266
254303AC2-168 GEN
Solar/Wind Helper
0.156
238126S14_GEN_1
Solar/Wind Helper
0.686
961971AG1-040 GEN
Solar/Wind Helper
0.447
24318705GVG2
50/50
12.071
971191AH1-055 GEN
Solar/Wind Harmer
27.281
274772LINCOLN ;3U
Adder
7.555
971993AH1-541 GEN
Solar/Wind Harmer
11.253
942481AE2-261 GEN
Solar/Wind Harmer
36.404
972259AH1-714 GEN
Adder
23.175
972273AH1-721 GEN
Adder
101.006
274729ELWOOD EC;1P
Adder
19.933
237048AF1-022 C
Solar/Wind Helper
0.199
237046AF1-021 C
Solar/Wind Helper
0.345
274675JOLIET 29;7U
Adder
35.87
274823ROCKFORD ;21
Adder
23.605
972267AH1-718 GEN
Adder
5.041
23652301WDPWR_K20
Solar/Wind Helper
0.146
23750701CROSSCHOOL
Solar/Wind Helper
1.209
203955AF1-039 C O1
Solar/Wind Helper
0.373
203846AF2-130 C
Solar/Wind Helper
0.443
24387305FR-4G C
Solar/Wind Harmer
6.235
970241AG2-163 GEN
Solar/Wind Harmer
30.673
957841AF2-078 GEN
Solar/Wind Harmer
7.402
274770LINCOLN ;1U
Adder
7.555
274771LINCOLN ;2U
Adder
7.555
274880W4-005 GEN4
Solar/Wind Harmer
3.683
276174W4-005 GEN2
Solar/Wind Harmer
3.683
276838X2-022 GEN2
Solar/Wind Harmer
0.283
942111AE2-223 GEN
Solar/Wind Harmer
9.977
276897AD1-100 C
Solar/Wind Harmer
56.428
962691AG1-118 GEN
Solar/Wind Harmer
36.394
274696ROCKY RD ;4P
Adder
13.825
274697ROCKY RD ;3P
Adder
3.669
274762LEE CO EC;3U
Adder
11.266
237043AE2-125 C
Solar/Wind Helper
0.181
23751201ROTHROCK
Solar/Wind Helper
0.749
962101AG1-054 GEN
Solar/Wind Helper
0.644
203946AE2-131 C
Solar/Wind Helper
0.461
940863AE2-074 GEN
Solar/Wind Helper
0.444
203954AE2-126 C
Solar/Wind Helper
0.458
243186AF1-051 GEN
50/50
13.022
24721705FLATG2
50/50
43.628
24723005RIVRG1
Adder
35.405
24723105RIVRG2
Adder
35.405
971225AH1-072 GEN
Solar/Wind Harmer
2.946
971227AH1-073 GEN
Solar/Wind Harmer
2.946
270214AC2-123 GEN
Solar/Wind Harmer
3.099
24755605MDL-5G
Solar/Wind Harmer
2.954
270583AD2-179 GEN
Solar/Wind Harmer
12.237
276916AD2-100_GEN
Solar/Wind Harmer
25.572
241801AE1-079 GEN
Solar/Wind Helper
0.246
203818AF1-086 GEN
Solar/Wind Helper
1.65
203853AF1-134 C O1
Solar/Wind Helper
0.466
203804AE2-113_GEN
Solar/Wind Helper
1.698
203835AF1-098 GEN
Solar/Wind Helper
1.78
274800UNIV PARK;3U
Adder
7.06
274801UNIV PARK;4U
Adder
7.06
274827FISK ;RP
Adder
9.392
241997AF1-093 GEN
Solar/Wind Helper
0.252
971313AH1-133 GEN
Solar/Wind Harmer
8.781
971061AG2-657 GEN
Solar/Wind Harmer
12.335
24387005FR-3G C
Solar/Wind Harmer
4.855
24691005MDL-2G C
Solar/Wind Harmer
4.53
274863CRW1-WTG
Solar/Wind Harmer
6.788
274864CRW2-WTG
Solar/Wind Harmer
6.788
274728ELWOOD EC;5P
Adder
19.933
241985AE1-237 GEN
Solar/Wind Helper
0.246
20089226LOOKOUT
Solar/Wind Helper
0.59
203940AF1-140 C
Solar/Wind Helper
0.388
CPLELTFEXP_CPLE->PJM
CLTF
6.948
CBM West 2LTFEXP_CBM-W2->PJM
CBM
158.57
LAGNLTFEXP_LAGN->PJM
CLTF
23.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.518
NYPJM->LTFIMP_NY
CLTF
5.358
LGEELTFEXP_LGEE->PJM
CLTF
8.414
TVALTFEXP_TVA->PJM
CLTF
11.786
WECLTFEXP_WEC->PJM
CLTF
4.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.281
AH1-155LTFEXP_AH1-155->PJM
LTF
0.421
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.868
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.575
MECLTFEXP_MEC->PJM
CLTF
20.238
SIGELTFEXP_SIGE->PJM
CLTF
0.64

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.27 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6477.04
MW Contribution:
8.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24686505CER G6
Adder
15.551
962761AG1-125 GEN
Solar/Wind Harmer
54.553
24728305BUCHG2
Adder
6.8
3429241JKCT 3G
Adder
16.815
339211AE2-254 GEN
Solar/Wind Harmer
2.115
944031AF1-071 GEN
Solar/Wind Harmer
1.385
270273AD2-016 GEN
Solar/Wind Harmer
3.648
270437AC2-090 C
Solar/Wind Harmer
7.589
276903AD2-071 C
Solar/Wind Harmer
13.523
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
11.163
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274674JOLIET 9 ;6U
Adder
20.046
24289405MTG1
50/50
11.336
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
5.223
971403AH1-188 GEN
Solar/Wind Harmer
23.963
970149AG2-104 GEN
Solar/Wind Harmer
33.686
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
339221AD2-048_GEN
Solar/Wind Harmer
2.202
3429421JKCT 10G
Adder
11.809
270222AC2-111 GEN
Solar/Wind Harmer
6.156
970653AG2-424 GEN
Solar/Wind Harmer
6.638
963741AG1-226 GEN
Solar/Wind Harmer
60.722
24791305MDL-5G
Solar/Wind Harmer
3.222
274822ROCKFORD ;11
Adder
25.553
957921AF2-086 GEN
Solar/Wind Helper
0.497
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
7.699
270053AF1-130 C
Solar/Wind Harmer
30.765
270400AC1-102 GEN
Solar/Wind Harmer
7.281
941621AE2-160 GEN
Adder
5.034
972163AH1-664 GEN
Solar/Wind Harmer
14.536
3429211JKCT 2G
Adder
16.597
25196508WSDLE4
Adder
12.037
24734805WLF1G4
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
4.256
270263AC1-001 GEN
Solar/Wind Harmer
1.464
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
6.333
963841AG1-237 GEN
Solar/Wind Harmer
14.713
946581AF1-322 GEN
Solar/Wind Harmer
13.675
964611AG1-324 GEN
Solar/Wind Harmer
5.196
270432AC2-029 GEN
Solar/Wind Harmer
9.322
944221AF1-090 GEN
Solar/Wind Harmer
14.552
274776LINCOLN ;7U
Adder
11.001
274746AC1-111 G10
Adder
7.28
972043AH1-570 GEN
Solar/Wind Harmer
3.585
25194408D.CRK1
Adder
10.747
270330AC1-082 GEN2
Solar/Wind Harmer
0.842
957541AF2-048 GEN
Solar/Wind Harmer
2.477
971461AH1-227 GEN
Solar/Wind Harmer
7.797
252507AC2-088 GEN
Solar/Wind Harmer
2.586
958171AF2-111 GEN
Solar/Wind Harmer
35.846
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
24728705AND G3
Adder
10.976
970193AG2-126 GEN
Solar/Wind Harmer
20.406
270346AE1-212 GEN
Solar/Wind Harmer
12.206
970781AG2-491 GEN
Solar/Wind Harmer
13.365
274730ELWOOD EC;6P
Adder
21.404
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
207518AF1-320_GEN
Solar/Wind Helper
1.73
20674928WA_W3-044
Solar/Wind Helper
0.108
20676328BVR_Y1-020
Solar/Wind Helper
0.03
20676728BRNX1-095
Solar/Wind Helper
0.032
24289405MTG1
50/50
11.336
24686405CER G5
Adder
15.429
270329AC1-082 GEN1
Solar/Wind Harmer
0.842
243186AF1-051 GEN
50/50
12.477
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
970155AG2-107 GEN
Solar/Wind Harmer
23.787
945681AF1-233 GEN
Solar/Wind Harmer
27.387
252516AE2-318_GEN
Solar/Wind Harmer
14.288
943111AE2-339 GEN
Solar/Wind Harmer
1.257
25194608D.CRK4
Adder
2.336
253316AC1-085 GEN3
Solar/Wind Harmer
11.825
946171AF1-282 GEN
Solar/Wind Harmer
14.124
24735205WLF2G2
Adder
8.041
24728605AND G2
Adder
5.248
339241AF1-083 GEN
Solar/Wind Harmer
2.268
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
964901AG1-354 GEN
Solar/Wind Harmer
20.24
274745AC1-111 GEN9
Adder
7.28
219919AE1-041 FULL
Solar/Wind Helper
0.004
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
963711AG1-223 GEN
Solar/Wind Helper
0.069
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
962771AG1-126 GEN
Solar/Wind Harmer
54.553
970153AG2-106 GEN
Solar/Wind Harmer
23.787
972103AH1-617 GEN
Solar/Wind Harmer
31.161
960911AF2-382 GEN
Solar/Wind Harmer
11.466
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25194608D.CRK4
Adder
2.336
238185AF2-356 C
Solar/Wind Helper
2.64
238120AE2-309 GEN
Solar/Wind Helper
0.514
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
205941AD2-115 GEN
Solar/Wind Helper
0.536
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
230415AB2-049 C
Solar/Wind Helper
0.032
232406W1-004 FULL
Solar/Wind Helper
0.528
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.119
23777801MSM_W1-116
Solar/Wind Helper
0.101
252524AE2-267 GEN
Solar/Wind Harmer
2.234
253317AC1-085 GEN4
Solar/Wind Harmer
11.825
946181AF1-283 GEN
Solar/Wind Harmer
18.362
24728505AND G1
Adder
5.248
253303V4-073 C
Solar/Wind Harmer
0.157
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
247642Z2-115 C
Solar/Wind Harmer
0.086
970289AG2-191 GEN
Solar/Wind Harmer
1.035
946031AF1-268 GEN
Solar/Wind Harmer
11.153
960071AF2-298 GEN
Solar/Wind Harmer
2.031
274767LEE CO EC;8U
Adder
11.973
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
274682WAUKEGAN ;7U
Adder
7.239
235058AG1-386 C
Solar/Wind Helper
0.518
964991AG1-363 GEN
Solar/Wind Helper
4.441
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203975AE1-071-GEN
Solar/Wind Helper
2.698
20674628WNG_W3-110
Solar/Wind Helper
0.098
217208PARK ELE C
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.018
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219766PARADISE C
Solar/Wind Helper
0.058
233996TM1833_GEN
Solar/Wind Helper
0.214
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
235063AE1-101 C2
Solar/Wind Helper
1.478
24318705GVG2
50/50
11.565
270331AC1-082 GEN3
Solar/Wind Harmer
0.844
971687AH1-348 GEN
Solar/Wind Harmer
1.522
25196808ZIMRHP
Adder
108.598
252510AF1-249 C
Solar/Wind Harmer
0.594
25196008MFTGT1
Adder
1.98
253398AE2-221_GEN2
Solar/Wind Harmer
6.325
942081AE2-220 GEN
Solar/Wind Harmer
8.696
270209AC1-174_GEN
Solar/Wind Harmer
5.534
270239V3-007_GEN1
Solar/Wind Harmer
2.34
270594AE1-207 GEN
Solar/Wind Harmer
18.313
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
2.824
24386605FR-22G C
Solar/Wind Harmer
5.776
945371AF1-202 GEN
Solar/Wind Harmer
9.316
958861AF2-177 GEN
Solar/Wind Harmer
14.534
274773LINCOLN ;4U
Adder
11.001
24318705GVG2
50/50
11.565
971191AH1-055 GEN
Solar/Wind Harmer
31.162
270367AC2-061_GEN
Solar/Wind Harmer
4.689
270186AC1-089 GEN
Solar/Wind Harmer
9.011
970879AG2-548 GEN
Solar/Wind Harmer
11.654
972167AH1-666 GEN
Solar/Wind Harmer
11.619
25196008MFTGT1
Adder
1.918
970093AG2-073 GEN
Solar/Wind Harmer
7.507
253394AE2-221_GEN
Solar/Wind Harmer
6.325
972273AH1-721 GEN
Adder
114.179
270240V3-007_GEN2
Solar/Wind Harmer
8.412
965461AG1-414 GEN
Solar/Wind Harmer
3.058
970825AG2-519 GEN
Solar/Wind Harmer
7.583
962031AG1-047 GEN
Solar/Wind Harmer
4.019
274772LINCOLN ;3U
Adder
11.001
972259AH1-714 GEN
Adder
24.853
274729ELWOOD EC;1P
Adder
21.404
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
946731AF1-337 GEN
Solar/Wind Helper
0.504
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
207484AF2-139 C O1
Solar/Wind Helper
0.093
20676228FRD_X1-012
Solar/Wind Helper
0.101
20673628F1S_V4-069
Solar/Wind Helper
0.032
219908AB1-139 C
Solar/Wind Helper
0.08
218428ETC SOLAR C
Solar/Wind Helper
0.005
20716028EGP_W2-019
Solar/Wind Helper
0.02
219907AC1-030 C
Solar/Wind Helper
0.036
232408W1-005 C
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
205916AD1-020 GEN
Solar/Wind Helper
1.727
238175AF1-290_GEN
Solar/Wind Helper
0.127
957741AF2-068 GEN
Solar/Wind Harmer
8.281
270399AC1-101 GEN
Solar/Wind Harmer
7.281
971985AH1-537 GEN
Solar/Wind Harmer
27.788
972165AH1-665 GEN
Solar/Wind Harmer
11.629
339216AC1-074 GEN
Solar/Wind Harmer
2.394
24734705WLF1G3
Adder
8.159
24734905WLF1G5
Adder
8.159
253406AD2-031_GEN
Solar/Wind Harmer
1.796
270291AC1-194 GEN
Solar/Wind Harmer
7.123
971029AG2-637 GEN
Solar/Wind Harmer
20.191
24386405FR-21G C
Solar/Wind Harmer
5.776
945581AF1-223 GEN
Solar/Wind Harmer
6.056
247536S-71 GEN
Solar/Wind Harmer
5.402
961761AG1-017 GEN
Solar/Wind Harmer
0.569
274775LINCOLN ;6U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
972267AH1-718 GEN
Adder
5.423
274823ROCKFORD ;21
Adder
25.367
972228AH1-698 GEN2
Adder
4.822
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
203955AF1-039 C O1
Solar/Wind Helper
0.435
203846AF2-130 C
Solar/Wind Helper
0.501
959431AF2-234 GEN
Solar/Wind Helper
1.007
212266LOR1
Solar/Wind Helper
0.342
961261AF2-417 GEN
Solar/Wind Helper
0.499
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
219620RIDERU C
Solar/Wind Helper
0.001
219615MILLCREEK C
Solar/Wind Helper
0.028
227927V4-067C
Solar/Wind Helper
0.011
228728W1-130C
Solar/Wind Helper
0.057
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
942891AE2-308 GEN
Solar/Wind Harmer
14.201
253415AE1-040 GEN
Solar/Wind Harmer
1.57
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
18.959
926881AC1-175 GEN
Solar/Wind Harmer
7.589
24725505WLD G2 C
Solar/Wind Harmer
5.381
253349AC2-067 GEN
Solar/Wind Harmer
2.741
966841AG1-555 GEN
Solar/Wind Harmer
3.372
970883AG2-550 GEN
Solar/Wind Harmer
13.404
24697605MDL-3G C
Solar/Wind Harmer
4.927
270181AB1-006 GEN2
Solar/Wind Harmer
0.956
971485AH1-239 GEN
Solar/Wind Harmer
10.681
964781AG1-341 GEN
Solar/Wind Harmer
14.151
270599AE1-208 GEN
Solar/Wind Harmer
10.876
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
972235AH1-702 GEN1
Adder
3.282
274674JOLIET 9 ;6U
Adder
20.046
274683WAUKEGAN ;8U
Adder
27.432
23585401KL_K28_T16
Solar/Wind Helper
1.54
238117U2-030
Solar/Wind Helper
0.345
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
20675428EAM_W2-061
Solar/Wind Helper
0.017
207459AE1-142 C O1
Solar/Wind Helper
0.312
214067T20SOLAR
Solar/Wind Helper
0.012
230433AD2-135 GEN
Solar/Wind Helper
0.018
234015AF2-250 C
Solar/Wind Helper
0.04
232428Y3-058 C
Solar/Wind Helper
0.352
232424Y1-079 C
Solar/Wind Helper
0.121
235062AE1-101 C1
Solar/Wind Helper
1.478
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
962581AG1-107 GEN
Solar/Wind Harmer
7.389
961491AF2-440 GEN
Solar/Wind Harmer
3.071
970879AG2-548 GEN
Solar/Wind Harmer
1.694
970107AG2-081 GEN
Solar/Wind Harmer
4.268
339236AF1-050_GEN
Solar/Wind Harmer
2.451
970241AG2-163 GEN
Solar/Wind Harmer
33.734
24387305FR-4G C
Solar/Wind Harmer
6.822
957841AF2-078 GEN
Solar/Wind Harmer
8.063
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
274696ROCKY RD ;4P
Adder
14.841
274762LEE CO EC;3U
Adder
12.115
339243AC2-075 GEN1
Solar/Wind Harmer
0.648
970455AG2-298 GEN
Solar/Wind Harmer
4.865
970653AG2-424 GEN
Solar/Wind Harmer
0.96
339206AE1-143 GEN
Solar/Wind Harmer
2.932
24379505HDWTR1G C
Solar/Wind Harmer
10.752
270004AE1-209 GEN
Solar/Wind Harmer
7.368
24386205FR-12G C
Solar/Wind Harmer
5.756
339255AE2-071 GEN
Solar/Wind Harmer
1.57
339250AF1-203 GEN
Solar/Wind Harmer
0.808
24690905MDL-1G C
Solar/Wind Harmer
10.73
274760LEE CO EC;1U
Adder
12.115
23562501BACKB
Solar/Wind Helper
1.078
238108AE1-109 GEN1
Solar/Wind Helper
0.103
203854AF2-039 C
Solar/Wind Helper
0.357
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
23750501ELLIOTTS
Solar/Wind Helper
0.793
238118U2-030_1
Solar/Wind Helper
0.345
20089126CSLMN_L13
Solar/Wind Helper
0.688
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
20334926Z1-069 C
Solar/Wind Helper
1.501
959421AF2-233 GEN
Solar/Wind Helper
0.504
209029WAYMART-WD
Solar/Wind Helper
0.944
20675128HRM_W1-127
Solar/Wind Helper
0.033
20676428JCR_X2-075
Solar/Wind Helper
0.074
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
233901CHERRYDALE C
Solar/Wind Helper
0.242
205956AE1-196_GEN
Solar/Wind Helper
0.528
205917AD1-020 ES
Solar/Wind Helper
0.371
23779801AA1-109
Solar/Wind Helper
0.169
927014AC1-188 GEN
Solar/Wind Harmer
2.477
970913AG2-568 GEN
Solar/Wind Harmer
10.623
24728205BUCHG1
Adder
6.8
971073AG2-665 GEN
Solar/Wind Harmer
11.654
252509AD1-136 GEN
Solar/Wind Harmer
0.369
972045AH1-571 GEN
Solar/Wind Harmer
2.868
25183208HLCRTG
Solar/Wind Harmer
8.652
25194508D.CRK3
Adder
2.009
964571AG1-320 GEN
Solar/Wind Harmer
11.341
270269AC2-059
Solar/Wind Harmer
12.798
24728805RICHG1
Adder
5.185
270383AD1-128 GEN
Solar/Wind Harmer
8.27
339231AF1-038_GEN
Solar/Wind Harmer
2.457
24699105WLD G1 C
Solar/Wind Harmer
5.319
253400AC2-068 GEN
Solar/Wind Harmer
1.102
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
9.612
24697905MDL-4G C
Solar/Wind Harmer
3.067
966021AG1-471 GEN
Solar/Wind Harmer
7.208
270031AE2-169
Solar/Wind Harmer
10.876
945421AF1-207 GEN
Solar/Wind Harmer
18.73
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
270201AC2-176 GEN
Solar/Wind Harmer
6.831
274695ROCKY RD ;2P
Adder
14.499
274765LEE CO EC;6U
Adder
12.144
274763LEE CO EC;4U
Adder
12.001
972236AH1-702 GEN2
Adder
2.854
235054AD2-180 GEN
Solar/Wind Helper
2.046
235531U2-073 GEN
Solar/Wind Helper
3.281
254304AE2-114 C
Solar/Wind Helper
0.241
203961AE2-224 GEN
Solar/Wind Helper
2.731
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
946751AF1-339 GEN
Solar/Wind Helper
0.504
20674328GAR_V4-001
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219912AD2-042 GEN
Solar/Wind Helper
0.159
233994AC2-023 GEN
Solar/Wind Helper
1.001
234036AF2-325 C
Solar/Wind Helper
0.044
232436AB1-176 C
Solar/Wind Helper
0.046
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
971225AH1-072 GEN
Solar/Wind Harmer
3.04
971227AH1-073 GEN
Solar/Wind Harmer
3.04
971125AH1-004 GEN
Solar/Wind Harmer
5.691
253370AE2-315 SEC1
Adder
2.718
970291AG2-192 GEN
Solar/Wind Harmer
1.753
970291AG2-192 GEN
Solar/Wind Harmer
0.565
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24755605MDL-5G
Solar/Wind Harmer
3.222
247621Y3-024
Adder
0.321
241801AE1-079 GEN
Solar/Wind Helper
0.274
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
203804AE2-113_GEN
Solar/Wind Helper
1.942
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
20720828JCB_W4-025
Solar/Wind Helper
0.068
219906AC1-017 C
Solar/Wind Helper
0.045
219904AC1-010 C
Solar/Wind Helper
0.064
237080AD1-060 GEN
Solar/Wind Helper
0.299
970281AG2-184 GEN
Solar/Wind Harmer
32.719
962211AG1-066 GEN
Solar/Wind Harmer
3.649
253433AC1-085 GEN1
Solar/Wind Harmer
7.506
253432AC1-085 GEN2
Solar/Wind Harmer
0.378
270444AC2-157 GEN1
Solar/Wind Harmer
7.815
270445AC2-157 GEN2
Solar/Wind Harmer
7.815
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
2.562
274744AC1-111 GEN8
Adder
7.28
274735ELWOOD EC;4P
Adder
21.404
972227AH1-698 GEN1
Adder
3.396
241997AF1-093 GEN
Solar/Wind Helper
0.282
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
209054AE2-059 GEN
Solar/Wind Helper
0.091
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
230407AD2-065 C
Solar/Wind Helper
0.043
232432Z2-076 GEN
Solar/Wind Helper
0.07
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
274697ROCKY RD ;3P
Adder
3.939
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
962101AG1-054 GEN
Solar/Wind Helper
0.72
961431AF2-434 GEN
Solar/Wind Helper
0.502
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
217081WEATEXAS C
Solar/Wind Helper
0.014
219272CLEANLIGHT C
Solar/Wind Helper
0.027
228754AB1-001 C
Solar/Wind Helper
0.028
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
233946AB2-136 GEN
Solar/Wind Helper
0.592
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
223402AF1-300 C
Solar/Wind Helper
0.341
274774LINCOLN ;5U
Adder
11.001
274761LEE CO EC;2U
Adder
12.115
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
23583801GRNGAP
Solar/Wind Helper
4.315
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
207437AD2-070 GEN
Solar/Wind Helper
0.152
207510AF2-138 C
Solar/Wind Helper
0.089
20673728F2S_V4-070
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
219623KINSLEYBEA C
Solar/Wind Helper
0.002
237085AD2-009_GEN
Solar/Wind Helper
1.463
233933AB2-153 GEN
Solar/Wind Helper
0.242
971313AH1-133 GEN
Solar/Wind Harmer
8.798
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
971061AG2-657 GEN
Solar/Wind Harmer
12.288
24387005FR-3G C
Solar/Wind Harmer
5.313
270543AE2-219 C
Solar/Wind Harmer
13.404
24691005MDL-2G C
Solar/Wind Harmer
4.942
24729505KEY G4
Adder
8.55
274728ELWOOD EC;5P
Adder
21.404
20089226LOOKOUT
Solar/Wind Helper
0.686
241985AE1-237 GEN
Solar/Wind Helper
0.274
203940AF1-140 C
Solar/Wind Helper
0.45
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
209027LOR2_Q27
Solar/Wind Helper
1.174
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
20390526W1-045 C
Solar/Wind Helper
0.36
219258KINSLEYDEP C
Solar/Wind Helper
0.081
230434AG1-499 GEN
Solar/Wind Helper
0.244
233940AF2-379 C
Solar/Wind Helper
0.065
211065PSPA IPP
Solar/Wind Helper
0.169
20674128FR_U2-059
Solar/Wind Helper
0.004
207511W3-106 GEN
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
219249CENTRALDIV C
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
233935AB2-179 C
Solar/Wind Helper
1.32
237038AE2-054 C
Solar/Wind Helper
0.24
20089026BF_G21_K23
Solar/Wind Helper
0.545
20084626FORWARD
Solar/Wind Helper
0.405
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
217169METRODIV C
Solar/Wind Helper
0.004
207454AA2-184 E
Solar/Wind Helper
0.335
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
233950AC2-186 GEN
Solar/Wind Helper
0.121
235067AD1-061 GEN
Solar/Wind Helper
0.394
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
962511AG1-100 GEN
Solar/Wind Helper
0.492
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
228729W2-030 C
Solar/Wind Helper
0.117
233918AB1-142 GEN
Solar/Wind Helper
0.523
237001AB1-127_GEN
Solar/Wind Helper
0.391
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
TVALTFEXP_TVA->PJM
CLTF
12.563
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6428.58
MW Contribution:
5.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.336
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
16.719
970149AG2-104 GEN
Solar/Wind Harmer
24.844
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
3429421JKCT 10G
Adder
11.809
970653AG2-424 GEN
Solar/Wind Harmer
4.631
970773AG2-487 GEN
Solar/Wind Harmer
1.693
963741AG1-226 GEN
Solar/Wind Harmer
22.28
276655WTG1_EQ
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
11.925
970913AG2-568 GEN
Solar/Wind Harmer
8.731
24728205BUCHG1
Adder
6.8
971073AG2-665 GEN
Solar/Wind Harmer
7.453
252509AD1-136 GEN
Solar/Wind Harmer
0.05
972045AH1-571 GEN
Solar/Wind Harmer
2.084
25183208HLCRTG
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
2.009
964571AG1-320 GEN
Solar/Wind Harmer
8.813
270269AC2-059
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
5.185
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
0
966021AG1-471 GEN
Solar/Wind Harmer
5.029
270031AE2-169
Solar/Wind Harmer
5.121
945421AF1-207 GEN
Solar/Wind Harmer
0
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
270201AC2-176 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
1.282
944541AF1-119 GEN
Solar/Wind Harmer
0.618
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.642
274695ROCKY RD ;2P
Adder
14.499
274765LEE CO EC;6U
Adder
12.144
274763LEE CO EC;4U
Adder
12.001
972236AH1-702 GEN2
Adder
2.854
971277AH1-098 GEN
Solar/Wind Harmer
3.633
958011AF2-095 GEN
Solar/Wind Harmer
13.073
235054AD2-180 GEN
Solar/Wind Helper
2.046
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
962771AG1-126 GEN
Solar/Wind Harmer
46.005
970153AG2-106 GEN
Solar/Wind Harmer
29.378
972043AH1-570 GEN
Solar/Wind Harmer
2.601
25194408D.CRK1
Adder
10.747
942891AE2-308 GEN
Solar/Wind Harmer
9.908
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
10.085
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.061
970883AG2-550 GEN
Solar/Wind Harmer
9.352
24697605MDL-3G C
Solar/Wind Harmer
0
971485AH1-239 GEN
Solar/Wind Harmer
7.452
964781AG1-341 GEN
Solar/Wind Harmer
9.873
270599AE1-208 GEN
Solar/Wind Harmer
8.535
960971AF2-388 GEN
Solar/Wind Harmer
5.431
276615X2-022 GEN
Solar/Wind Harmer
0.096
960611AF2-352 GEN
Solar/Wind Harmer
3.067
276876AE1-163_GEN2
Solar/Wind Harmer
0
971461AH1-227 GEN
Solar/Wind Harmer
5.44
252507AC2-088 GEN
Solar/Wind Harmer
0.453
958171AF2-111 GEN
Solar/Wind Harmer
25.009
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
24728705AND G3
Adder
10.976
970193AG2-126 GEN
Solar/Wind Harmer
14.237
270346AE1-212 GEN
Solar/Wind Harmer
8.358
970781AG2-491 GEN
Solar/Wind Harmer
9.325
959611AF2-252 GEN
Solar/Wind Harmer
3.067
944531AF1-118 GEN
Solar/Wind Harmer
41.107
276782AC1-033 GEN
Solar/Wind Harmer
0
276868AE1-113 GEN
Solar/Wind Harmer
1.82
274879MINONK ;1U
Solar/Wind Harmer
0.38
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
29.702
274862TOP CROP ;2U
Solar/Wind Harmer
1.227
274855GSG-6 ;RU
Solar/Wind Harmer
0.332
274857EASY ROAD;U1
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
21.404
274887GEN-1.85
Solar/Wind Harmer
0.236
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
207518AF1-320_GEN
Solar/Wind Helper
1.73
20674928WA_W3-044
Solar/Wind Helper
0.108
20676328BVR_Y1-020
Solar/Wind Helper
0.03
20676728BRNX1-095
Solar/Wind Helper
0.032
219919AE1-041 FULL
Solar/Wind Helper
0.004
20715228NPK_W1-113
Solar/Wind Helper
0.084
972103AH1-617 GEN
Solar/Wind Harmer
21.74
960911AF2-382 GEN
Solar/Wind Harmer
7.999
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25194608D.CRK4
Adder
2.336
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
12.81
24728505AND G1
Adder
5.248
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.035
946031AF1-268 GEN
Solar/Wind Harmer
8.922
957381AF2-032 GEN
Solar/Wind Harmer
2.099
943031AE2-326 GEN
Solar/Wind Harmer
4.803
943121AE2-341 GEN
Solar/Wind Harmer
15.239
943591AF1-030 GEN
Solar/Wind Harmer
10.134
959091AF2-200 GEN
Solar/Wind Harmer
18.173
274767LEE CO EC;8U
Adder
11.973
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
971087AG2-675 GEN
Solar/Wind Harmer
4.845
274682WAUKEGAN ;7U
Adder
7.239
276806AD2-047 C O1
Solar/Wind Harmer
5.144
235058AG1-386 C
Solar/Wind Helper
0.518
964991AG1-363 GEN
Solar/Wind Helper
4.441
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203975AE1-071-GEN
Solar/Wind Helper
2.698
20674628WNG_W3-110
Solar/Wind Helper
0.098
217208PARK ELE C
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.018
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20714528FRN_Y2-051
Solar/Wind Helper
0.061
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
27.062
270400AC1-102 GEN
Solar/Wind Harmer
3.79
941621AE2-160 GEN
Adder
5.034
972163AH1-664 GEN
Solar/Wind Harmer
11.291
3429211JKCT 2G
Adder
16.597
25196508WSDLE4
Adder
12.037
24734805WLF1G4
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.978
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
4.07
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.521
964611AG1-324 GEN
Solar/Wind Harmer
3.625
270432AC2-029 GEN
Solar/Wind Harmer
4.119
944221AF1-090 GEN
Solar/Wind Harmer
5.449
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
0.996
926823AC1-168 GEN
Solar/Wind Harmer
1.55
274776LINCOLN ;7U
Adder
11.001
274746AC1-111 G10
Adder
7.28
274731ELWOOD EC;2P
Adder
21.404
20720528MAN_W1-024
Solar/Wind Helper
0.031
963711AG1-223 GEN
Solar/Wind Helper
0.069
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
270399AC1-101 GEN
Solar/Wind Harmer
3.79
971985AH1-537 GEN
Solar/Wind Harmer
3.231
972165AH1-665 GEN
Solar/Wind Harmer
9.043
339216AC1-074 GEN
Solar/Wind Harmer
0.266
24734705WLF1G3
Adder
8.159
24734905WLF1G5
Adder
8.159
253406AD2-031_GEN
Solar/Wind Harmer
0.728
270291AC1-194 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
14.087
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.372
971611AH1-305 GEN
Solar/Wind Harmer
5.499
959141AF2-205 GEN
Solar/Wind Harmer
0.001
966391AG1-508 GEN
Solar/Wind Harmer
1.42
274775LINCOLN ;6U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
970833AG2-524 GEN
Solar/Wind Harmer
10.003
970833AG2-524 GEN
Solar/Wind Harmer
6.669
971675AH1-338 GEN
Solar/Wind Harmer
3.544
971171AH1-044 GEN
Solar/Wind Harmer
18.173
972267AH1-718 GEN
Adder
5.423
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274823ROCKFORD ;21
Adder
25.367
971411AH1-196 GEN
Solar/Wind Harmer
13.626
972228AH1-698 GEN2
Adder
4.822
960591AF2-350 GEN
Solar/Wind Harmer
9.078
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
203955AF1-039 C O1
Solar/Wind Helper
0.435
203846AF2-130 C
Solar/Wind Helper
0.501
959431AF2-234 GEN
Solar/Wind Helper
1.007
212266LOR1
Solar/Wind Helper
0.342
24318705GVG2
50/50
11.565
971687AH1-348 GEN
Solar/Wind Harmer
1.062
25196808ZIMRHP
Adder
108.598
252510AF1-249 C
Solar/Wind Harmer
0.075
25196008MFTGT1
Adder
1.98
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
10.536
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
2.038
970825AG2-519 GEN
Solar/Wind Harmer
3.334
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.02
276621W2-048 GEN
Solar/Wind Harmer
0.463
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.546
939741AE1-205 GEN
Solar/Wind Harmer
12.866
964861AG1-349 GEN
Solar/Wind Harmer
0.001
970569AG2-363 GEN
Solar/Wind Harmer
27.326
971997AH1-543 GEN
Solar/Wind Harmer
4.779
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
276805AD2-038 GEN
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.115
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
23583801GRNGAP
Solar/Wind Helper
4.315
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
24318705GVG2
50/50
11.565
971191AH1-055 GEN
Solar/Wind Harmer
29.882
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
7.453
972167AH1-666 GEN
Solar/Wind Harmer
8.106
25196008MFTGT1
Adder
1.918
970093AG2-073 GEN
Solar/Wind Harmer
8.38
253394AE2-221_GEN
Solar/Wind Harmer
0.001
972273AH1-721 GEN
Adder
114.179
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
7.074
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.91
942481AE2-261 GEN
Solar/Wind Harmer
27.692
971993AH1-541 GEN
Solar/Wind Harmer
4.271
970571AG2-364 GEN
Solar/Wind Harmer
18.217
274772LINCOLN ;3U
Adder
11.001
972259AH1-714 GEN
Adder
24.853
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
946671AF1-331 GEN
Solar/Wind Harmer
0.969
274729ELWOOD EC;1P
Adder
21.404
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
946731AF1-337 GEN
Solar/Wind Helper
0.504
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
207484AF2-139 C O1
Solar/Wind Helper
0.093
20676228FRD_X1-012
Solar/Wind Helper
0.101
20673628F1S_V4-069
Solar/Wind Helper
0.032
219908AB1-139 C
Solar/Wind Helper
0.08
218428ETC SOLAR C
Solar/Wind Helper
0.005
20716028EGP_W2-019
Solar/Wind Helper
0.02
219907AC1-030 C
Solar/Wind Helper
0.036
232408W1-005 C
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
205916AD1-020 GEN
Solar/Wind Helper
1.727
238175AF1-290_GEN
Solar/Wind Helper
0.127
971313AH1-133 GEN
Solar/Wind Harmer
5.062
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
971061AG2-657 GEN
Solar/Wind Harmer
6.001
270543AE2-219 C
Solar/Wind Harmer
6.546
24691005MDL-2G C
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.55
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
3.032
276861AD2-134 GEN
Solar/Wind Harmer
0.162
276863AD2-134 GEN
Solar/Wind Harmer
0.162
971681AH1-341 GEN
Solar/Wind Harmer
14.63
274728ELWOOD EC;5P
Adder
21.404
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
20089226LOOKOUT
Solar/Wind Helper
0.686
241985AE1-237 GEN
Solar/Wind Helper
0.274
203940AF1-140 C
Solar/Wind Helper
0.45
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
209027LOR2_Q27
Solar/Wind Helper
1.174
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
20390526W1-045 C
Solar/Wind Helper
0.36
219258KINSLEYDEP C
Solar/Wind Helper
0.081
230434AG1-499 GEN
Solar/Wind Helper
0.244
233940AF2-379 C
Solar/Wind Helper
0.065
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970879AG2-548 GEN
Solar/Wind Harmer
1.694
970107AG2-081 GEN
Solar/Wind Harmer
2.978
970241AG2-163 GEN
Solar/Wind Harmer
5.492
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.521
942111AE2-223 GEN
Solar/Wind Harmer
2.987
276645AC1-214 GEN1
Solar/Wind Harmer
0.358
276897AD1-100 C
Solar/Wind Harmer
22.743
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.467
962691AG1-118 GEN
Solar/Wind Harmer
27.261
938861AE1-114 GEN
Solar/Wind Harmer
5.149
274696ROCKY RD ;4P
Adder
14.841
274762LEE CO EC;3U
Adder
12.115
274697ROCKY RD ;3P
Adder
3.939
276893AG1-478 C
Solar/Wind Harmer
0.606
942221AE2-234 GEN
Solar/Wind Harmer
3.648
274888KELLY CRK;1U
Solar/Wind Harmer
0.529
970941AG2-585 GEN
Solar/Wind Harmer
4.993
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
962101AG1-054 GEN
Solar/Wind Helper
0.72
961431AF2-434 GEN
Solar/Wind Helper
0.502
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
217081WEATEXAS C
Solar/Wind Helper
0.014
219272CLEANLIGHT C
Solar/Wind Helper
0.027
228754AB1-001 C
Solar/Wind Helper
0.028
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
233946AB2-136 GEN
Solar/Wind Helper
0.592
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
223402AF1-300 C
Solar/Wind Helper
0.341
243186AF1-051 GEN
50/50
12.477
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
970155AG2-107 GEN
Solar/Wind Harmer
29.378
945681AF1-233 GEN
Solar/Wind Harmer
19.107
252516AE2-318_GEN
Solar/Wind Harmer
11.165
25194608D.CRK4
Adder
2.336
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.854
24735205WLF2G2
Adder
8.041
24728605AND G2
Adder
5.248
970613AG2-401 GEN
Solar/Wind Harmer
6.957
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
964901AG1-354 GEN
Solar/Wind Harmer
14.121
965651AG1-433 GEN
Solar/Wind Harmer
2.715
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.28
957471AF2-041 GEN
Solar/Wind Harmer
27.26
238185AF2-356 C
Solar/Wind Helper
2.64
238120AE2-309 GEN
Solar/Wind Helper
0.514
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
205941AD2-115 GEN
Solar/Wind Helper
0.536
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
230415AB2-049 C
Solar/Wind Helper
0.032
232406W1-004 FULL
Solar/Wind Helper
0.528
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.119
23777801MSM_W1-116
Solar/Wind Helper
0.101
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
971225AH1-072 GEN
Solar/Wind Harmer
2.121
971227AH1-073 GEN
Solar/Wind Harmer
2.121
971125AH1-004 GEN
Solar/Wind Harmer
3.97
971587AH1-292 GEN
Solar/Wind Harmer
7.164
253370AE2-315 SEC1
Adder
2.718
970291AG2-192 GEN
Solar/Wind Harmer
1.223
970291AG2-192 GEN
Solar/Wind Harmer
0.565
971613AH1-306 GEN
Solar/Wind Harmer
4.515
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
247621Y3-024
Adder
0.321
276916AD2-100_GEN
Solar/Wind Harmer
19.462
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.173
971343AH1-151 GEN
Solar/Wind Harmer
18.173
276776AD2-060 GEN
Solar/Wind Harmer
0.968
241801AE1-079 GEN
Solar/Wind Helper
0.274
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
203804AE2-113_GEN
Solar/Wind Helper
1.942
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
20720828JCB_W4-025
Solar/Wind Helper
0.068
219906AC1-017 C
Solar/Wind Helper
0.045
219904AC1-010 C
Solar/Wind Helper
0.064
237080AD1-060 GEN
Solar/Wind Helper
0.299
970281AG2-184 GEN
Solar/Wind Harmer
22.827
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
1.788
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.362
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
9.649
970169AG2-114 GEN
Solar/Wind Harmer
9.156
274877BISHOP HL;1U
Solar/Wind Harmer
0.304
276741O09 GEN1
Solar/Wind Harmer
0.321
274744AC1-111 GEN8
Adder
7.28
274735ELWOOD EC;4P
Adder
21.404
972227AH1-698 GEN1
Adder
3.396
241997AF1-093 GEN
Solar/Wind Helper
0.282
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
209054AE2-059 GEN
Solar/Wind Helper
0.091
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
230407AD2-065 C
Solar/Wind Helper
0.043
232432Z2-076 GEN
Solar/Wind Helper
0.07
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
961261AF2-417 GEN
Solar/Wind Helper
0.499
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
219620RIDERU C
Solar/Wind Helper
0.001
219615MILLCREEK C
Solar/Wind Helper
0.028
227927V4-067C
Solar/Wind Helper
0.011
228728W1-130C
Solar/Wind Helper
0.057
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
24686505CER G6
Adder
15.551
962761AG1-125 GEN
Solar/Wind Harmer
46.005
24728305BUCHG2
Adder
6.8
3429241JKCT 3G
Adder
16.815
270273AD2-016 GEN
Solar/Wind Harmer
0.98
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
10.535
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.852
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.831
253333AC1-068 GEN
Solar/Wind Harmer
0.01
276708O09 GEN2
Solar/Wind Harmer
0.321
962781AG1-127 GEN
Solar/Wind Harmer
8.648
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274674JOLIET 9 ;6U
Adder
20.046
20089026BF_G21_K23
Solar/Wind Helper
0.545
20084626FORWARD
Solar/Wind Helper
0.405
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
217169METRODIV C
Solar/Wind Helper
0.004
207454AA2-184 E
Solar/Wind Helper
0.335
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
233950AC2-186 GEN
Solar/Wind Helper
0.121
235067AD1-061 GEN
Solar/Wind Helper
0.394
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
207437AD2-070 GEN
Solar/Wind Helper
0.152
207510AF2-138 C
Solar/Wind Helper
0.089
20673728F2S_V4-070
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
219623KINSLEYBEA C
Solar/Wind Helper
0.002
237085AD2-009_GEN
Solar/Wind Helper
1.463
233933AB2-153 GEN
Solar/Wind Helper
0.242
958481AF2-142 GEN
Solar/Wind Harmer
13.633
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
972235AH1-702 GEN1
Adder
3.282
274674JOLIET 9 ;6U
Adder
20.046
274683WAUKEGAN ;8U
Adder
27.432
23585401KL_K28_T16
Solar/Wind Helper
1.54
238117U2-030
Solar/Wind Helper
0.345
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
20675428EAM_W2-061
Solar/Wind Helper
0.017
207459AE1-142 C O1
Solar/Wind Helper
0.312
214067T20SOLAR
Solar/Wind Helper
0.012
230433AD2-135 GEN
Solar/Wind Helper
0.018
234015AF2-250 C
Solar/Wind Helper
0.04
232428Y3-058 C
Solar/Wind Helper
0.352
232424Y1-079 C
Solar/Wind Helper
0.121
235062AE1-101 C1
Solar/Wind Helper
1.478
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
274733ELWOOD EC;3P
Adder
21.404
23750501ELLIOTTS
Solar/Wind Helper
0.793
238118U2-030_1
Solar/Wind Helper
0.345
20089126CSLMN_L13
Solar/Wind Helper
0.688
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
20334926Z1-069 C
Solar/Wind Helper
1.501
959421AF2-233 GEN
Solar/Wind Helper
0.504
209029WAYMART-WD
Solar/Wind Helper
0.944
20675128HRM_W1-127
Solar/Wind Helper
0.033
20676428JCR_X2-075
Solar/Wind Helper
0.074
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
233901CHERRYDALE C
Solar/Wind Helper
0.242
205956AE1-196_GEN
Solar/Wind Helper
0.528
205917AD1-020 ES
Solar/Wind Helper
0.371
23779801AA1-109
Solar/Wind Helper
0.169
276646AC1-214 GEN2
Solar/Wind Harmer
0.358
276882AE2-255 GEN
Solar/Wind Harmer
1.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.477
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
9.087
971067AG2-660 GEN
Solar/Wind Harmer
3.029
274822ROCKFORD ;11
Adder
25.553
970819AG2-516 GEN
Solar/Wind Harmer
10.9
957921AF2-086 GEN
Solar/Wind Helper
0.497
211065PSPA IPP
Solar/Wind Helper
0.169
20674128FR_U2-059
Solar/Wind Helper
0.004
207511W3-106 GEN
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
219249CENTRALDIV C
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
233935AB2-179 C
Solar/Wind Helper
1.32
237038AE2-054 C
Solar/Wind Helper
0.24
970373AG2-245 GEN
Solar/Wind Harmer
16.807
235531U2-073 GEN
Solar/Wind Helper
3.281
254304AE2-114 C
Solar/Wind Helper
0.241
203961AE2-224 GEN
Solar/Wind Helper
2.731
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
946751AF1-339 GEN
Solar/Wind Helper
0.504
20674328GAR_V4-001
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219912AD2-042 GEN
Solar/Wind Helper
0.159
233994AC2-023 GEN
Solar/Wind Helper
1.001
234036AF2-325 C
Solar/Wind Helper
0.044
232436AB1-176 C
Solar/Wind Helper
0.046
24289405MTG1
50/50
11.336
24686405CER G5
Adder
15.429
970455AG2-298 GEN
Solar/Wind Harmer
3.77
970653AG2-424 GEN
Solar/Wind Harmer
0.96
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
2.038
970191AG2-125 GEN
Solar/Wind Harmer
2.419
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
27.602
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274878BISHOP HL;2U
Solar/Wind Harmer
0.304
253325AC1-069 GEN
Solar/Wind Harmer
0.01
274760LEE CO EC;1U
Adder
12.115
965931AG1-462 GEN
Solar/Wind Harmer
23.167
276843GEN-1.7
Solar/Wind Harmer
0.294
23562501BACKB
Solar/Wind Helper
1.078
238108AE1-109 GEN1
Solar/Wind Helper
0.103
203854AF2-039 C
Solar/Wind Helper
0.357
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
962511AG1-100 GEN
Solar/Wind Helper
0.492
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
228729W2-030 C
Solar/Wind Helper
0.117
233918AB1-142 GEN
Solar/Wind Helper
0.523
237001AB1-127_GEN
Solar/Wind Helper
0.391
219766PARADISE C
Solar/Wind Helper
0.058
233996TM1833_GEN
Solar/Wind Helper
0.214
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
235063AE1-101 C2
Solar/Wind Helper
1.478
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
TVALTFEXP_TVA->PJM
CLTF
12.563
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.72 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6225.55
MW Contribution:
8.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.548
24721805FLATG3
50/50
2.774
972203AH1-686 GEN
Adder
4.442
24723205RIVRG3
Adder
36.155
970155AG2-107 GEN
Solar/Wind Harmer
23.985
24721605FLATG1
50/50
2.774
957241AF2-018 GEN
Solar/Wind Harmer
7.761
270053AF1-130 C
Solar/Wind Harmer
31.012
270400AC1-102 GEN
Solar/Wind Harmer
7.341
941621AE2-160 GEN
Adder
5.08
972163AH1-664 GEN
Solar/Wind Harmer
14.676
3429211JKCT 2G
Adder
16.761
25196508WSDLE4
Adder
12.156
24734805WLF1G4
Adder
8.239
270340AC2-060 GEN
Solar/Wind Harmer
4.299
270263AC1-001 GEN
Solar/Wind Harmer
1.479
24735105WLF2G1
Adder
8.122
270356AE2-297 GEN
Solar/Wind Harmer
6.397
963841AG1-237 GEN
Solar/Wind Harmer
14.866
946581AF1-322 GEN
Solar/Wind Harmer
13.818
964611AG1-324 GEN
Solar/Wind Harmer
5.25
270432AC2-029 GEN
Solar/Wind Harmer
9.42
944221AF1-090 GEN
Solar/Wind Harmer
14.705
274776LINCOLN ;7U
Adder
11.119
274746AC1-111 G10
Adder
7.358
274731ELWOOD EC;2P
Adder
21.634
274733ELWOOD EC;3P
Adder
21.634
23750501ELLIOTTS
Solar/Wind Helper
0.784
238118U2-030_1
Solar/Wind Helper
0.341
20089126CSLMN_L13
Solar/Wind Helper
0.68
241982AE2-343 S C
Solar/Wind Helper
0.243
20088926STNY CRK
Solar/Wind Helper
0.922
20094526CT_V3-030
Solar/Wind Helper
0.527
20088626ARWF_N39
Solar/Wind Helper
1.354
20334926Z1-069 C
Solar/Wind Helper
1.481
24722005FLATG5
50/50
2.774
24721905FLATG4
50/50
50.672
962771AG1-126 GEN
Solar/Wind Harmer
55.006
970153AG2-106 GEN
Solar/Wind Harmer
23.985
972103AH1-617 GEN
Solar/Wind Harmer
31.441
960911AF2-382 GEN
Solar/Wind Harmer
11.571
252519AF1-045_GEN
Solar/Wind Harmer
5.251
25194608D.CRK4
Adder
2.359
252524AE2-267 GEN
Solar/Wind Harmer
2.256
253317AC1-085 GEN4
Solar/Wind Harmer
11.942
243186AF1-051 GEN
50/50
12.548
24721705FLATG2
50/50
41.198
24723005RIVRG1
Adder
36.155
24723105RIVRG2
Adder
36.155
971225AH1-072 GEN
Solar/Wind Harmer
3.068
971227AH1-073 GEN
Solar/Wind Harmer
3.068
971125AH1-004 GEN
Solar/Wind Harmer
5.746
253370AE2-315 SEC1
Adder
2.746
970291AG2-192 GEN
Solar/Wind Harmer
1.771
970291AG2-192 GEN
Solar/Wind Harmer
0.57
25322209TAIT E
Adder
13.248
25322209TAIT E
Adder
12.95
24755605MDL-5G
Solar/Wind Harmer
3.256
247621Y3-024
Adder
0.324
241801AE1-079 GEN
Solar/Wind Helper
0.27
203818AF1-086 GEN
Solar/Wind Helper
1.876
203853AF1-134 C O1
Solar/Wind Helper
0.53
203804AE2-113_GEN
Solar/Wind Helper
1.916
316097T157 G90
Solar/Wind Helper
1.146
203835AF1-098 GEN
Solar/Wind Helper
1.948
20674828DL_W4-046
Solar/Wind Helper
0.009
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.15
20714828MDF_W3-079
Solar/Wind Helper
0.138
20720828JCB_W4-025
Solar/Wind Helper
0.067
219906AC1-017 C
Solar/Wind Helper
0.044
219904AC1-010 C
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.295
962581AG1-107 GEN
Solar/Wind Harmer
7.459
961491AF2-440 GEN
Solar/Wind Harmer
3.1
24318705GVG2
50/50
11.631
270331AC1-082 GEN3
Solar/Wind Harmer
0.851
971687AH1-348 GEN
Solar/Wind Harmer
1.536
25196808ZIMRHP
Adder
109.659
252510AF1-249 C
Solar/Wind Harmer
0.6
25196008MFTGT1
Adder
1.999
253398AE2-221_GEN2
Solar/Wind Harmer
6.388
942081AE2-220 GEN
Solar/Wind Harmer
8.785
270209AC1-174_GEN
Solar/Wind Harmer
5.591
270239V3-007_GEN1
Solar/Wind Harmer
2.364
270594AE1-207 GEN
Solar/Wind Harmer
18.503
270032AE2-172
Solar/Wind Harmer
6.337
270005AE1-210 C O1
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
2.854
24386605FR-22G C
Solar/Wind Harmer
5.837
945371AF1-202 GEN
Solar/Wind Harmer
9.414
958861AF2-177 GEN
Solar/Wind Harmer
14.687
274773LINCOLN ;4U
Adder
11.119
274774LINCOLN ;5U
Adder
11.119
274761LEE CO EC;2U
Adder
12.246
238126S14_GEN_1
Solar/Wind Helper
0.805
254303AC2-168 GEN
Solar/Wind Helper
0.172
946691AF1-333 GEN
Solar/Wind Helper
0.496
946741AF1-338 GEN
Solar/Wind Helper
0.496
961421AF2-433 GEN
Solar/Wind Helper
0.495
23583801GRNGAP
Solar/Wind Helper
4.253
209116AE2-175 GEN
Solar/Wind Helper
1.956
961971AG1-040 GEN
Solar/Wind Helper
0.488
20671928W4-073
Solar/Wind Helper
0.097
207437AD2-070 GEN
Solar/Wind Helper
0.149
207510AF2-138 C
Solar/Wind Helper
0.088
20673728F2S_V4-070
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
20716928W4-060COL
Solar/Wind Helper
0.055
219612MATRIX C
Solar/Wind Helper
0.025
219623KINSLEYBEA C
Solar/Wind Helper
0.002
237085AD2-009_GEN
Solar/Wind Helper
1.442
233933AB2-153 GEN
Solar/Wind Helper
0.238
972043AH1-570 GEN
Solar/Wind Harmer
3.62
25194408D.CRK1
Adder
10.853
942891AE2-308 GEN
Solar/Wind Harmer
14.341
253415AE1-040 GEN
Solar/Wind Harmer
1.586
24728905RICHG2
Adder
5.238
945391AF1-204 GEN
Solar/Wind Harmer
19.154
926881AC1-175 GEN
Solar/Wind Harmer
7.667
24725505WLD G2 C
Solar/Wind Harmer
5.437
253349AC2-067 GEN
Solar/Wind Harmer
2.769
966841AG1-555 GEN
Solar/Wind Harmer
3.407
970883AG2-550 GEN
Solar/Wind Harmer
13.544
270399AC1-101 GEN
Solar/Wind Harmer
7.341
971985AH1-537 GEN
Solar/Wind Harmer
28.037
972165AH1-665 GEN
Solar/Wind Harmer
11.741
339216AC1-074 GEN
Solar/Wind Harmer
2.418
24734705WLF1G3
Adder
8.239
24734905WLF1G5
Adder
8.239
253406AD2-031_GEN
Solar/Wind Harmer
1.814
270291AC1-194 GEN
Solar/Wind Harmer
7.194
971029AG2-637 GEN
Solar/Wind Harmer
20.401
24386405FR-21G C
Solar/Wind Harmer
5.837
945581AF1-223 GEN
Solar/Wind Harmer
6.119
247536S-71 GEN
Solar/Wind Harmer
5.458
961761AG1-017 GEN
Solar/Wind Harmer
0.575
274775LINCOLN ;6U
Adder
11.119
274777LINCOLN ;8U
Adder
11.119
972267AH1-718 GEN
Adder
5.481
274823ROCKFORD ;21
Adder
25.64
972228AH1-698 GEN2
Adder
4.874
23652301WDPWR_K20
Solar/Wind Helper
0.167
23750701CROSSCHOOL
Solar/Wind Helper
1.42
203955AF1-039 C O1
Solar/Wind Helper
0.43
203846AF2-130 C
Solar/Wind Helper
0.494
959431AF2-234 GEN
Solar/Wind Helper
0.993
212266LOR1
Solar/Wind Helper
0.337
961261AF2-417 GEN
Solar/Wind Helper
0.492
218526CNTRALGAS2 C
Solar/Wind Helper
0.172
219620RIDERU C
Solar/Wind Helper
0.001
219615MILLCREEK C
Solar/Wind Helper
0.028
227927V4-067C
Solar/Wind Helper
0.011
228728W1-130C
Solar/Wind Helper
0.056
205943AE1-185 GEN
Solar/Wind Helper
0.52
233915AB1-141 GEN
Solar/Wind Helper
0.515
270330AC1-082 GEN2
Solar/Wind Harmer
0.849
957541AF2-048 GEN
Solar/Wind Harmer
2.499
971461AH1-227 GEN
Solar/Wind Harmer
7.869
252507AC2-088 GEN
Solar/Wind Harmer
2.611
958171AF2-111 GEN
Solar/Wind Harmer
36.196
25196608WSDLE5
Adder
12.281
3429391JKCT 9G
Adder
11.925
24728705AND G3
Adder
11.088
970193AG2-126 GEN
Solar/Wind Harmer
20.616
270346AE1-212 GEN
Solar/Wind Harmer
12.332
970781AG2-491 GEN
Solar/Wind Harmer
13.505
274730ELWOOD EC;6P
Adder
21.634
202652Y1-033 WT C
Solar/Wind Helper
0.652
238127S14_GEN_2
Solar/Wind Helper
0.805
20092526R32
Solar/Wind Helper
1.303
20398826ARMNA MT
Solar/Wind Helper
1.645
941421AE2-139 GEN
Solar/Wind Helper
2.555
209137AF2-361 C
Solar/Wind Helper
1.523
207518AF1-320_GEN
Solar/Wind Helper
1.705
20674928WA_W3-044
Solar/Wind Helper
0.107
20676328BVR_Y1-020
Solar/Wind Helper
0.029
20676728BRNX1-095
Solar/Wind Helper
0.032
219919AE1-041 FULL
Solar/Wind Helper
0.004
20715228NPK_W1-113
Solar/Wind Helper
0.083
20720528MAN_W1-024
Solar/Wind Helper
0.03
963711AG1-223 GEN
Solar/Wind Helper
0.068
219276PARKLANDSO C
Solar/Wind Helper
0.095
20715828PEM_W1-120
Solar/Wind Helper
0.101
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.52
23777901MDS_W4-102
Solar/Wind Helper
0.149
208835TUHI V3-051
Solar/Wind Helper
0.021
24686505CER G6
Adder
15.668
962761AG1-125 GEN
Solar/Wind Harmer
55.006
24728305BUCHG2
Adder
6.863
3429241JKCT 3G
Adder
16.981
339211AE2-254 GEN
Solar/Wind Harmer
2.136
944031AF1-071 GEN
Solar/Wind Harmer
1.399
24289405MTG1
50/50
11.396
944971AF1-162 GEN
Solar/Wind Harmer
12.224
960001AF2-291 GEN
Solar/Wind Harmer
5.265
971403AH1-188 GEN
Solar/Wind Harmer
24.159
970149AG2-104 GEN
Solar/Wind Harmer
33.966
970091AG2-072 GEN
Adder
114.157
971073AG2-665 GEN
Solar/Wind Harmer
1.71
339221AD2-048_GEN
Solar/Wind Harmer
2.223
3429421JKCT 10G
Adder
11.925
270222AC2-111 GEN
Solar/Wind Harmer
6.219
970653AG2-424 GEN
Solar/Wind Harmer
6.706
963741AG1-226 GEN
Solar/Wind Harmer
61.351
24791305MDL-5G
Solar/Wind Harmer
3.256
274822ROCKFORD ;11
Adder
25.827
957921AF2-086 GEN
Solar/Wind Helper
0.49
211065PSPA IPP
Solar/Wind Helper
0.167
20674128FR_U2-059
Solar/Wind Helper
0.004
207511W3-106 GEN
Solar/Wind Helper
0.029
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.349
219249CENTRALDIV C
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.101
959561AF2-247 GEN
Solar/Wind Helper
0.022
233923SMA
Solar/Wind Helper
0.772
233997TMININ_4.2
Solar/Wind Helper
0.21
232417X3-008 C
Solar/Wind Helper
0.239
233987AB2-037 GEN
Solar/Wind Helper
2.403
233935AB2-179 C
Solar/Wind Helper
1.3
237038AE2-054 C
Solar/Wind Helper
0.237
24289405MTG1
50/50
11.396
24686405CER G5
Adder
15.544
270329AC1-082 GEN1
Solar/Wind Harmer
0.849
339243AC2-075 GEN1
Solar/Wind Harmer
0.655
970455AG2-298 GEN
Solar/Wind Harmer
4.914
970653AG2-424 GEN
Solar/Wind Harmer
0.97
339206AE1-143 GEN
Solar/Wind Harmer
2.962
24379505HDWTR1G C
Solar/Wind Harmer
10.862
270004AE1-209 GEN
Solar/Wind Harmer
7.445
24386205FR-12G C
Solar/Wind Harmer
5.816
339255AE2-071 GEN
Solar/Wind Harmer
1.586
339250AF1-203 GEN
Solar/Wind Harmer
0.817
24690905MDL-1G C
Solar/Wind Harmer
10.842
274760LEE CO EC;1U
Adder
12.246
23562501BACKB
Solar/Wind Helper
1.065
238108AE1-109 GEN1
Solar/Wind Helper
0.102
203854AF2-039 C
Solar/Wind Helper
0.352
212507AE2-042_GEN
Solar/Wind Helper
1.759
961341AF2-425 GEN
Solar/Wind Helper
0.495
961301AF2-421 GEN
Solar/Wind Helper
0.492
963151AG1-164 GEN
Solar/Wind Helper
0.492
211065PSPA IPP
Solar/Wind Helper
0.167
207530AG1-191 GEN
Solar/Wind Helper
0.072
207439AE1-081 C O1
Solar/Wind Helper
0.02
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
962511AG1-100 GEN
Solar/Wind Helper
0.485
218524CNTRALGAS1 C
Solar/Wind Helper
0.172
219348LDSOLAR C
Solar/Wind Helper
0.12
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
228729W2-030 C
Solar/Wind Helper
0.116
233918AB1-142 GEN
Solar/Wind Helper
0.515
237001AB1-127_GEN
Solar/Wind Helper
0.386
270273AD2-016 GEN
Solar/Wind Harmer
3.685
270437AC2-090 C
Solar/Wind Harmer
7.667
276903AD2-071 C
Solar/Wind Harmer
13.662
25326309TAIT D
Adder
1.488
24385905FR-11G C
Solar/Wind Harmer
11.279
274766LEE CO EC;7U
Adder
12.101
274732ELWOOD EC;7P
Adder
21.634
274674JOLIET 9 ;6U
Adder
20.261
20089026BF_G21_K23
Solar/Wind Helper
0.538
20084626FORWARD
Solar/Wind Helper
0.4
203855AF2-088 C
Solar/Wind Helper
0.169
209071AE2-133 GEN
Solar/Wind Helper
0.09
961331AF2-424 GEN
Solar/Wind Helper
0.495
208972BECR K09
Solar/Wind Helper
0.37
963161AG1-165 GEN
Solar/Wind Helper
0.492
217169METRODIV C
Solar/Wind Helper
0.004
207454AA2-184 E
Solar/Wind Helper
0.33
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219914AD2-027 C
Solar/Wind Helper
0.12
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.524
233950AC2-186 GEN
Solar/Wind Helper
0.119
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
208835TUHI V3-051
Solar/Wind Helper
0.021
24697605MDL-3G C
Solar/Wind Harmer
4.978
270181AB1-006 GEN2
Solar/Wind Harmer
0.966
971485AH1-239 GEN
Solar/Wind Harmer
10.793
964781AG1-341 GEN
Solar/Wind Harmer
14.3
270599AE1-208 GEN
Solar/Wind Harmer
10.99
274693ROCKY RD ;1P
Adder
14.51
274764LEE CO EC;5U
Adder
12.274
274674JOLIET 9 ;6U
Adder
20.261
972235AH1-702 GEN1
Adder
3.317
23585401KL_K28_T16
Solar/Wind Helper
1.522
238117U2-030
Solar/Wind Helper
0.341
254305AE2-115 C
Solar/Wind Helper
0.238
20083426SW_E13_K22
Solar/Wind Helper
0.063
241967AE2-285_GEN
Solar/Wind Helper
0.691
946071AF1-272 GEN
Solar/Wind Helper
3.032
20088826HIGHLAND
Solar/Wind Helper
1.005
20675428EAM_W2-061
Solar/Wind Helper
0.017
207459AE1-142 C O1
Solar/Wind Helper
0.307
214067T20SOLAR
Solar/Wind Helper
0.012
230433AD2-135 GEN
Solar/Wind Helper
0.018
232428Y3-058 C
Solar/Wind Helper
0.347
234015AF2-250 C
Solar/Wind Helper
0.039
232424Y1-079 C
Solar/Wind Helper
0.119
235062AE1-101 C1
Solar/Wind Helper
1.456
237006AB1-125 GEN
Solar/Wind Helper
0.109
223401AF1-299 GEN
Solar/Wind Helper
0.336
971313AH1-133 GEN
Solar/Wind Harmer
8.881
25196108MFTGT2
Adder
2.204
25196108MFTGT2
Adder
2.047
25196408WSDLE3
Adder
12.643
25196308WSDLE2
Adder
12.533
25196208WSDLE1
Adder
12.501
25196708WSDLE6
Adder
12.47
971061AG2-657 GEN
Solar/Wind Harmer
12.414
24387005FR-3G C
Solar/Wind Harmer
5.368
270543AE2-219 C
Solar/Wind Harmer
13.544
24691005MDL-2G C
Solar/Wind Harmer
4.994
24729505KEY G4
Adder
8.64
274728ELWOOD EC;5P
Adder
21.634
20089226LOOKOUT
Solar/Wind Helper
0.678
241985AE1-237 GEN
Solar/Wind Helper
0.27
203940AF1-140 C
Solar/Wind Helper
0.444
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
970879AG2-548 GEN
Solar/Wind Harmer
1.71
970107AG2-081 GEN
Solar/Wind Harmer
4.31
339236AF1-050_GEN
Solar/Wind Harmer
2.477
970241AG2-163 GEN
Solar/Wind Harmer
34.084
24387305FR-4G C
Solar/Wind Harmer
6.894
957841AF2-078 GEN
Solar/Wind Harmer
8.147
274770LINCOLN ;1U
Adder
11.119
274771LINCOLN ;2U
Adder
11.119
274696ROCKY RD ;4P
Adder
15.001
274762LEE CO EC;3U
Adder
12.246
274697ROCKY RD ;3P
Adder
3.981
237043AE2-125 C
Solar/Wind Helper
0.207
23751201ROTHROCK
Solar/Wind Helper
0.874
962101AG1-054 GEN
Solar/Wind Helper
0.711
961431AF2-434 GEN
Solar/Wind Helper
0.495
207471AF2-354 C
Solar/Wind Helper
0.183
20675928HOL_W4-097
Solar/Wind Helper
0.054
217081WEATEXAS C
Solar/Wind Helper
0.014
219272CLEANLIGHT C
Solar/Wind Helper
0.027
228754AB1-001 C
Solar/Wind Helper
0.027
230511AF1-262
Solar/Wind Helper
0.015
233952AC2-187 GEN
Solar/Wind Helper
0.239
233954AC2-188 GEN
Solar/Wind Helper
0.239
232410W1-006 C
Solar/Wind Helper
0.52
233946AB2-136 GEN
Solar/Wind Helper
0.583
233982AB2-133 GEN
Solar/Wind Helper
0.368
233930AB2-032 GEN
Solar/Wind Helper
0.39
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.235
223402AF1-300 C
Solar/Wind Helper
0.336
927014AC1-188 GEN
Solar/Wind Harmer
2.499
970913AG2-568 GEN
Solar/Wind Harmer
10.718
24728205BUCHG1
Adder
6.863
971073AG2-665 GEN
Solar/Wind Harmer
11.766
252509AD1-136 GEN
Solar/Wind Harmer
0.373
972045AH1-571 GEN
Solar/Wind Harmer
2.896
25183208HLCRTG
Solar/Wind Harmer
8.737
25194508D.CRK3
Adder
2.029
964571AG1-320 GEN
Solar/Wind Harmer
11.455
270269AC2-059
Solar/Wind Harmer
12.928
24728805RICHG1
Adder
5.238
270383AD1-128 GEN
Solar/Wind Harmer
8.356
339231AF1-038_GEN
Solar/Wind Harmer
2.483
24699105WLD G1 C
Solar/Wind Harmer
5.374
253400AC2-068 GEN
Solar/Wind Harmer
1.114
970885AG2-551 GEN
Solar/Wind Harmer
3.15
270180AB1-006 GEN1
Solar/Wind Harmer
9.713
24697905MDL-4G C
Solar/Wind Harmer
3.099
966021AG1-471 GEN
Solar/Wind Harmer
7.284
270031AE2-169
Solar/Wind Harmer
10.99
945421AF1-207 GEN
Solar/Wind Harmer
18.926
25326109MON D
Adder
1.772
964611AG1-324 GEN
Solar/Wind Harmer
0.704
270201AC2-176 GEN
Solar/Wind Harmer
6.903
274695ROCKY RD ;2P
Adder
14.655
274765LEE CO EC;6U
Adder
12.274
274763LEE CO EC;4U
Adder
12.13
972236AH1-702 GEN2
Adder
2.884
235054AD2-180 GEN
Solar/Wind Helper
2.021
235531U2-073 GEN
Solar/Wind Helper
3.241
254304AE2-114 C
Solar/Wind Helper
0.238
203961AE2-224 GEN
Solar/Wind Helper
2.695
946381AF1-302 GEN
Solar/Wind Helper
0.245
203946AE2-131 C
Solar/Wind Helper
0.526
203954AE2-126 C
Solar/Wind Helper
0.519
940863AE2-074 GEN
Solar/Wind Helper
0.501
946751AF1-339 GEN
Solar/Wind Helper
0.496
20674328GAR_V4-001
Solar/Wind Helper
0.024
219607WPEMNERT C
Solar/Wind Helper
0.084
219304NAMERICA C
Solar/Wind Helper
0.138
970281AG2-184 GEN
Solar/Wind Harmer
33.013
962211AG1-066 GEN
Solar/Wind Harmer
3.683
253433AC1-085 GEN1
Solar/Wind Harmer
7.58
253432AC1-085 GEN2
Solar/Wind Harmer
0.381
270444AC2-157 GEN1
Solar/Wind Harmer
7.893
270445AC2-157 GEN2
Solar/Wind Harmer
7.893
253372AE2-315 SEC3
Adder
2.597
253372AE2-315 SEC3
Adder
2.597
25306009OHH W.
Adder
3.946
970289AG2-191 GEN
Solar/Wind Harmer
2.589
274744AC1-111 GEN8
Adder
7.358
274735ELWOOD EC;4P
Adder
21.634
972227AH1-698 GEN1
Adder
3.432
241997AF1-093 GEN
Solar/Wind Helper
0.278
200917MEHOOPANY_G
Solar/Wind Helper
2.413
209067AE2-060 GEN
Solar/Wind Helper
0.091
209054AE2-059 GEN
Solar/Wind Helper
0.09
945681AF1-233 GEN
Solar/Wind Harmer
27.651
252516AE2-318_GEN
Solar/Wind Harmer
14.428
943111AE2-339 GEN
Solar/Wind Harmer
1.269
25194608D.CRK4
Adder
2.359
253316AC1-085 GEN3
Solar/Wind Harmer
11.942
946171AF1-282 GEN
Solar/Wind Harmer
14.264
24735205WLF2G2
Adder
8.122
24728605AND G2
Adder
5.301
339241AF1-083 GEN
Solar/Wind Harmer
2.292
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
964901AG1-354 GEN
Solar/Wind Harmer
20.45
274745AC1-111 GEN9
Adder
7.358
274682WAUKEGAN ;7U
Adder
11.397
238185AF2-356 C
Solar/Wind Helper
2.609
238120AE2-309 GEN
Solar/Wind Helper
0.508
241966AE1-183 GEN
Solar/Wind Helper
0.278
23751101LEADS_P59
Solar/Wind Helper
2.213
964201AG1-281 GEN
Solar/Wind Helper
0.541
20091526CHSTN_FL
Solar/Wind Helper
0.651
238109AE1-109 GEN2
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.142
203952AE2-129 C
Solar/Wind Helper
0.526
203830AF1-094 GEN
Solar/Wind Helper
0.492
203979AG1-198 GEN
Solar/Wind Helper
0.295
316095T157 G97
Solar/Wind Helper
1.146
205941AD2-115 GEN
Solar/Wind Helper
0.528
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.005
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
230415AB2-049 C
Solar/Wind Helper
0.032
232434Z2-077 GEN
Solar/Wind Helper
0.13
232406W1-004 FULL
Solar/Wind Helper
0.52
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.117
23777801MSM_W1-116
Solar/Wind Helper
0.099
946181AF1-283 GEN
Solar/Wind Harmer
18.543
24728505AND G1
Adder
5.301
253303V4-073 C
Solar/Wind Harmer
0.159
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
247642Z2-115 C
Solar/Wind Harmer
0.087
970289AG2-191 GEN
Solar/Wind Harmer
1.046
946031AF1-268 GEN
Solar/Wind Harmer
11.269
960071AF2-298 GEN
Solar/Wind Harmer
2.052
274767LEE CO EC;8U
Adder
12.101
274734ELWOOD EC;8P
Adder
21.634
274736ELWOOD EC;9P
Adder
21.634
274682WAUKEGAN ;7U
Adder
23.647
235058AG1-386 C
Solar/Wind Helper
0.512
964991AG1-363 GEN
Solar/Wind Helper
4.388
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20303426NA_O38_P22
Solar/Wind Helper
1.11
203993AD2-133_GEN1
Solar/Wind Helper
1.142
203975AE1-071-GEN
Solar/Wind Helper
2.659
20674628WNG_W3-110
Solar/Wind Helper
0.097
217208PARK ELE C
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.018
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219766PARADISE C
Solar/Wind Helper
0.057
233996TM1833_GEN
Solar/Wind Helper
0.21
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.52
235063AE1-101 C2
Solar/Wind Helper
1.456
207408W3-077 C
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.068
20720728JCB_W1-129
Solar/Wind Helper
0.06
959381AF2-229 GEN
Solar/Wind Helper
0.361
230407AD2-065 C
Solar/Wind Helper
0.042
232432Z2-076 GEN
Solar/Wind Helper
0.069
237025AB1-124 C
Solar/Wind Helper
0.145
237030AB1-096 C
Solar/Wind Helper
0.059
238169AE2-226 GEN1
Solar/Wind Helper
0.55
238170AE2-226 GEN2
Solar/Wind Helper
0.55
24318705GVG2
50/50
11.631
971191AH1-055 GEN
Solar/Wind Harmer
31.424
270367AC2-061_GEN
Solar/Wind Harmer
4.734
270186AC1-089 GEN
Solar/Wind Harmer
9.096
970879AG2-548 GEN
Solar/Wind Harmer
11.766
972167AH1-666 GEN
Solar/Wind Harmer
11.731
25196008MFTGT1
Adder
1.936
970093AG2-073 GEN
Solar/Wind Harmer
7.582
253394AE2-221_GEN
Solar/Wind Harmer
6.388
972273AH1-721 GEN
Adder
115.342
270240V3-007_GEN2
Solar/Wind Harmer
8.498
965461AG1-414 GEN
Solar/Wind Harmer
3.09
970825AG2-519 GEN
Solar/Wind Harmer
7.662
962031AG1-047 GEN
Solar/Wind Harmer
4.061
274772LINCOLN ;3U
Adder
11.119
972259AH1-714 GEN
Adder
25.12
274729ELWOOD EC;1P
Adder
21.634
237048AF1-022 C
Solar/Wind Helper
0.229
237046AF1-021 C
Solar/Wind Helper
0.396
946731AF1-337 GEN
Solar/Wind Helper
0.496
20675728RH_W2-091
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.032
207484AF2-139 C O1
Solar/Wind Helper
0.091
20676228FRD_X1-012
Solar/Wind Helper
0.1
20673628F1S_V4-069
Solar/Wind Helper
0.032
219908AB1-139 C
Solar/Wind Helper
0.079
218428ETC SOLAR C
Solar/Wind Helper
0.005
20716028EGP_W2-019
Solar/Wind Helper
0.02
219907AC1-030 C
Solar/Wind Helper
0.036
232408W1-005 C
Solar/Wind Helper
0.52
233944AB2-135 GEN
Solar/Wind Helper
0.605
205916AD1-020 GEN
Solar/Wind Helper
1.701
238175AF1-290_GEN
Solar/Wind Helper
0.125
957741AF2-068 GEN
Solar/Wind Harmer
8.369
209027LOR2_Q27
Solar/Wind Helper
1.157
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.093
20390526W1-045 C
Solar/Wind Helper
0.355
219258KINSLEYDEP C
Solar/Wind Helper
0.08
230434AG1-499 GEN
Solar/Wind Helper
0.24
233940AF2-379 C
Solar/Wind Helper
0.064
219912AD2-042 GEN
Solar/Wind Helper
0.157
233994AC2-023 GEN
Solar/Wind Helper
0.986
234036AF2-325 C
Solar/Wind Helper
0.043
232436AB1-176 C
Solar/Wind Helper
0.046
959421AF2-233 GEN
Solar/Wind Helper
0.497
209029WAYMART-WD
Solar/Wind Helper
0.93
20675128HRM_W1-127
Solar/Wind Helper
0.032
20676428JCR_X2-075
Solar/Wind Helper
0.073
20675528CPH_W2-050
Solar/Wind Helper
0.121
20720628TIN_W1-124
Solar/Wind Helper
0.202
207445AB1-138_GEN
Solar/Wind Helper
0.111
20715028HAN_X4-015
Solar/Wind Helper
0.06
233901CHERRYDALE C
Solar/Wind Helper
0.239
205956AE1-196_GEN
Solar/Wind Helper
0.52
205917AD1-020 ES
Solar/Wind Helper
0.366
23779801AA1-109
Solar/Wind Helper
0.167
CPLELTFEXP_CPLE->PJM
CLTF
6.636
CBM West 2LTFEXP_CBM-W2->PJM
CBM
174.171
LAGNLTFEXP_LAGN->PJM
CLTF
25.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.459
NYPJM->LTFIMP_NY
CLTF
6.23
LGEELTFEXP_LGEE->PJM
CLTF
9.895
TVALTFEXP_TVA->PJM
CLTF
12.705
WECLTFEXP_WEC->PJM
CLTF
5.031
AG2-052LTFEXP_AG2-052->PJM
LTF
0.308
AH1-155LTFEXP_AH1-155->PJM
LTF
0.462
CBM West 1LTFEXP_CBM-W1->PJM
CBM
171.353
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.863
MECLTFEXP_MEC->PJM
CLTF
22.066
SIGELTFEXP_SIGE->PJM
CLTF
0.733

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.96 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6183.32
MW Contribution:
9.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
49.394
243186AF1-051 GEN
50/50
14.291
24723005RIVRG1
Adder
37.759
24723105RIVRG2
Adder
37.759
971225AH1-072 GEN
Solar/Wind Harmer
3.076
971227AH1-073 GEN
Solar/Wind Harmer
3.076
24318705GVG2
50/50
13.247
270331AC1-082 GEN3
Solar/Wind Harmer
0.847
971687AH1-348 GEN
Solar/Wind Harmer
1.537
25196008MFTGT1
Adder
1.401
25196808ZIMRHP
Adder
75.86
252510AF1-249 C
Solar/Wind Harmer
0.407
276621W2-048 GEN
Solar/Wind Harmer
5.925
24386605FR-22G C
Solar/Wind Harmer
4.038
939741AE1-205 GEN
Solar/Wind Harmer
18.37
274761LEE CO EC;2U
Adder
8.393
254303AC2-168 GEN
Solar/Wind Helper
0.145
270399AC1-101 GEN
Solar/Wind Harmer
7.582
24734705WLF1G3
Adder
8.32
24734905WLF1G5
Adder
8.32
966391AG1-508 GEN
Solar/Wind Harmer
4.969
971331AH1-145 GEN
Solar/Wind Harmer
12.844
971985AH1-537 GEN
Solar/Wind Harmer
23.127
971981AH1-535 GEN
Solar/Wind Harmer
12.746
270069AE2-166 C O1
Solar/Wind Harmer
10.572
972165AH1-665 GEN
Solar/Wind Harmer
8.654
339216AC1-074 GEN
Solar/Wind Harmer
1.805
270291AC1-194 GEN
Solar/Wind Harmer
5.169
24386405FR-21G C
Solar/Wind Harmer
4.038
274853TWINGROVE;U1
Solar/Wind Harmer
6.662
972267AH1-718 GEN
Adder
3.77
274823ROCKFORD ;21
Adder
17.467
270330AC1-082 GEN2
Solar/Wind Harmer
0.845
971461AH1-227 GEN
Solar/Wind Harmer
7.89
270346AE1-212 GEN
Solar/Wind Harmer
13.435
958121AF2-106 GEN
Solar/Wind Harmer
6.036
957541AF2-048 GEN
Solar/Wind Harmer
2.104
3429391JKCT 9G
Adder
9.153
958171AF2-111 GEN
Solar/Wind Harmer
25.759
270018AE2-047 C O1
Solar/Wind Harmer
1.267
252507AC2-088 GEN
Solar/Wind Harmer
1.823
970193AG2-126 GEN
Solar/Wind Harmer
14.771
25196608WSDLE5
Adder
8.266
24728705AND G3
Adder
7.705
959611AF2-252 GEN
Solar/Wind Harmer
2.15
970781AG2-491 GEN
Solar/Wind Harmer
9.243
274730ELWOOD EC;6P
Adder
14.442
202652Y1-033 WT C
Solar/Wind Helper
0.512
24289405MTG1
50/50
12.684
970149AG2-104 GEN
Solar/Wind Harmer
56.636
944971AF1-162 GEN
Solar/Wind Harmer
12.651
971403AH1-188 GEN
Solar/Wind Harmer
25.286
960001AF2-291 GEN
Solar/Wind Harmer
5.171
970091AG2-072 GEN
Adder
90.254
971073AG2-665 GEN
Solar/Wind Harmer
1.298
970653AG2-424 GEN
Solar/Wind Harmer
5.33
3429421JKCT 10G
Adder
9.153
339221AD2-048_GEN
Solar/Wind Harmer
1.667
270173AC1-122 GEN
Solar/Wind Harmer
1.632
963741AG1-226 GEN
Solar/Wind Harmer
43.023
276686W4-005 GEN3
Solar/Wind Harmer
2.856
24791305MDL-5G
Solar/Wind Harmer
2.228
276655WTG1_EQ
Solar/Wind Harmer
8.017
274822ROCKFORD ;11
Adder
17.595
24289405MTG1
50/50
12.684
24686405CER G5
Adder
15.983
270329AC1-082 GEN1
Solar/Wind Harmer
0.845
339206AE1-143 GEN
Solar/Wind Harmer
2.39
339255AE2-071 GEN
Solar/Wind Harmer
1.308
339250AF1-203 GEN
Solar/Wind Harmer
0.673
962761AG1-125 GEN
Solar/Wind Harmer
91.718
24686505CER G6
Adder
16.11
24728305BUCHG2
Adder
7.18
339211AE2-254 GEN
Solar/Wind Harmer
1.701
3429241JKCT 3G
Adder
13.15
965911AG1-460 GEN
Solar/Wind Harmer
1.34
24385905FR-11G C
Solar/Wind Harmer
7.803
276656WTG2_EQ
Solar/Wind Harmer
1.061
274766LEE CO EC;7U
Adder
8.294
274732ELWOOD EC;7P
Adder
14.442
274674JOLIET 9 ;6U
Adder
13.524
20089026BF_G21_K23
Solar/Wind Helper
0.425
971485AH1-239 GEN
Solar/Wind Harmer
9.077
942891AE2-308 GEN
Solar/Wind Harmer
11.161
964781AG1-341 GEN
Solar/Wind Harmer
11.789
972043AH1-570 GEN
Solar/Wind Harmer
2.731
945391AF1-204 GEN
Solar/Wind Harmer
13.723
25194408D.CRK1
Adder
7.34
276615X2-022 GEN
Solar/Wind Harmer
1.861
966841AG1-555 GEN
Solar/Wind Harmer
2.357
960611AF2-352 GEN
Solar/Wind Harmer
2.15
24697605MDL-3G C
Solar/Wind Harmer
3.407
270181AB1-006 GEN2
Solar/Wind Harmer
0.661
24728905RICHG2
Adder
3.447
274764LEE CO EC;5U
Adder
8.413
970879AG2-548 GEN
Solar/Wind Harmer
1.298
339236AF1-050_GEN
Solar/Wind Harmer
2.021
970107AG2-081 GEN
Solar/Wind Harmer
3.272
962581AG1-107 GEN
Solar/Wind Harmer
5.294
961491AF2-440 GEN
Solar/Wind Harmer
2.2
970241AG2-163 GEN
Solar/Wind Harmer
23.902
276838X2-022 GEN2
Solar/Wind Harmer
0.221
274880W4-005 GEN4
Solar/Wind Harmer
2.856
276174W4-005 GEN2
Solar/Wind Harmer
2.856
970653AG2-424 GEN
Solar/Wind Harmer
0.771
970455AG2-298 GEN
Solar/Wind Harmer
3.861
339243AC2-075 GEN1
Solar/Wind Harmer
0.489
24386205FR-12G C
Solar/Wind Harmer
4.023
965091AG1-374 GEN
Solar/Wind Harmer
27.739
24690905MDL-1G C
Solar/Wind Harmer
7.42
274760LEE CO EC;1U
Adder
8.393
23562501BACKB
Solar/Wind Helper
0.816
24721805FLATG3
50/50
3.326
243186AF1-051 GEN
50/50
14.291
970155AG2-107 GEN
Solar/Wind Harmer
39.993
24723205RIVRG3
Adder
37.759
972203AH1-686 GEN
Adder
4.539
24735205WLF2G2
Adder
8.13
270336AE1-100 GEN
Solar/Wind Harmer
2.029
943811AF1-049 GEN
Solar/Wind Harmer
4.254
339241AF1-083 GEN
Solar/Wind Harmer
1.857
964901AG1-354 GEN
Solar/Wind Harmer
16.708
943111AE2-339 GEN
Solar/Wind Harmer
0.965
945681AF1-233 GEN
Solar/Wind Harmer
20.299
252516AE2-318_GEN
Solar/Wind Harmer
9.778
25194608D.CRK4
Adder
1.596
24728605AND G2
Adder
3.684
270574AD1-017 GEN2
Solar/Wind Harmer
4.722
274828WAUKEGAN ;BP
Adder
9.796
274682WAUKEGAN ;7U
Adder
15.93
274745AC1-111 GEN9
Adder
4.935
274676JOLIET 29;8U
Adder
26.921
241966AE1-183 GEN
Solar/Wind Helper
0.235
238185AF2-356 C
Solar/Wind Helper
2.008
270214AC2-123 GEN
Solar/Wind Harmer
3.345
270583AD2-179 GEN
Solar/Wind Harmer
13.318
971125AH1-004 GEN
Solar/Wind Harmer
4.363
276916AD2-100_GEN
Solar/Wind Harmer
20.233
24755605MDL-5G
Solar/Wind Harmer
2.228
241801AE1-079 GEN
Solar/Wind Helper
0.229
972235AH1-702 GEN1
Adder
2.262
274683WAUKEGAN ;8U
Adder
18.687
274683WAUKEGAN ;8U
Adder
15.753
274693ROCKY RD ;1P
Adder
9.773
274674JOLIET 9 ;6U
Adder
13.524
254305AE2-115 C
Solar/Wind Helper
0.201
241967AE2-285_GEN
Solar/Wind Helper
0.586
23585401KL_K28_T16
Solar/Wind Helper
1.176
238117U2-030
Solar/Wind Helper
0.261
946071AF1-272 GEN
Solar/Wind Helper
2.433
20083426SW_E13_K22
Solar/Wind Helper
0.05
274675JOLIET 29;7U
Adder
26.921
274675JOLIET 29;7U
Adder
15.118
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.338
23750701CROSSCHOOL
Solar/Wind Helper
1.086
24722005FLATG5
50/50
3.326
24721905FLATG4
50/50
60.751
962771AG1-126 GEN
Solar/Wind Harmer
91.718
970153AG2-106 GEN
Solar/Wind Harmer
39.993
960911AF2-382 GEN
Solar/Wind Harmer
12.012
972103AH1-617 GEN
Solar/Wind Harmer
30.905
943031AE2-326 GEN
Solar/Wind Harmer
5.264
270030AE2-140 GEN
Solar/Wind Harmer
23
252519AF1-045_GEN
Solar/Wind Harmer
3.559
25194608D.CRK4
Adder
1.596
252524AE2-267 GEN
Solar/Wind Harmer
1.519
24728505AND G1
Adder
3.684
957381AF2-032 GEN
Solar/Wind Harmer
1.919
276785W4-005 GEN1
Solar/Wind Harmer
2.856
274767LEE CO EC;8U
Adder
8.294
274682WAUKEGAN ;7U
Adder
15.93
274734ELWOOD EC;8P
Adder
14.442
274736ELWOOD EC;9P
Adder
14.442
235058AG1-386 C
Solar/Wind Helper
0.425
964991AG1-363 GEN
Solar/Wind Helper
3.339
970281AG2-184 GEN
Solar/Wind Harmer
32.451
962211AG1-066 GEN
Solar/Wind Harmer
3.487
270444AC2-157 GEN1
Solar/Wind Harmer
5.93
270445AC2-157 GEN2
Solar/Wind Harmer
5.93
276763AC1-053 GEN1
Solar/Wind Harmer
3.74
276764AC1-053 GEN2
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
2.091
276848AB2-070 GEN3
Solar/Wind Harmer
2.091
276849AB2-070 GEN2
Solar/Wind Harmer
2.091
270197AD1-017 GEN1
Solar/Wind Harmer
1.417
959341AF2-225 GEN
Solar/Wind Harmer
13.777
274744AC1-111 GEN8
Adder
4.935
274735ELWOOD EC;4P
Adder
14.442
241997AF1-093 GEN
Solar/Wind Helper
0.235
24387305FR-4G C
Solar/Wind Harmer
4.769
942111AE2-223 GEN
Solar/Wind Harmer
7.529
274762LEE CO EC;3U
Adder
8.393
274696ROCKY RD ;4P
Adder
10.103
274697ROCKY RD ;3P
Adder
2.681
237043AE2-125 C
Solar/Wind Helper
0.166
962101AG1-054 GEN
Solar/Wind Helper
0.598
23751201ROTHROCK
Solar/Wind Helper
0.671
24318705GVG2
50/50
13.247
971191AH1-055 GEN
Solar/Wind Harmer
28.586
972273AH1-721 GEN
Adder
96.087
970093AG2-073 GEN
Solar/Wind Harmer
5.967
970879AG2-548 GEN
Solar/Wind Harmer
8.927
270186AC1-089 GEN
Solar/Wind Harmer
6.641
270367AC2-061_GEN
Solar/Wind Harmer
3.424
972167AH1-666 GEN
Solar/Wind Harmer
8.599
25196008MFTGT1
Adder
1.357
942481AE2-261 GEN
Solar/Wind Harmer
28.724
962751AG1-124 GEN
Solar/Wind Harmer
8.593
971993AH1-541 GEN
Solar/Wind Harmer
8.726
274729ELWOOD EC;1P
Adder
14.442
237048AF1-022 C
Solar/Wind Helper
0.181
237046AF1-021 C
Solar/Wind Helper
0.315
971313AH1-133 GEN
Solar/Wind Harmer
9.358
971061AG2-657 GEN
Solar/Wind Harmer
13.518
25196108MFTGT2
Adder
1.544
25196108MFTGT2
Adder
1.434
25196408WSDLE3
Adder
8.509
25196308WSDLE2
Adder
8.435
25196208WSDLE1
Adder
8.414
25196708WSDLE6
Adder
8.393
24387005FR-3G C
Solar/Wind Harmer
3.714
24691005MDL-2G C
Solar/Wind Harmer
3.418
274728ELWOOD EC;5P
Adder
14.442
241985AE1-237 GEN
Solar/Wind Helper
0.229
20089226LOOKOUT
Solar/Wind Helper
0.536
970913AG2-568 GEN
Solar/Wind Harmer
11.514
24728205BUCHG1
Adder
7.18
971277AH1-098 GEN
Solar/Wind Harmer
5.707
927014AC1-188 GEN
Solar/Wind Harmer
2.104
966021AG1-471 GEN
Solar/Wind Harmer
6.141
339231AF1-038_GEN
Solar/Wind Harmer
2.061
971073AG2-665 GEN
Solar/Wind Harmer
8.927
964571AG1-320 GEN
Solar/Wind Harmer
8.983
972045AH1-571 GEN
Solar/Wind Harmer
2.185
252509AD1-136 GEN
Solar/Wind Harmer
0.26
25183208HLCRTG
Solar/Wind Harmer
5.886
25194508D.CRK3
Adder
1.372
276911AD2-131_GEN
Solar/Wind Harmer
4.089
270180AB1-006 GEN1
Solar/Wind Harmer
6.648
24697905MDL-4G C
Solar/Wind Harmer
2.121
24728805RICHG1
Adder
3.447
274765LEE CO EC;6U
Adder
8.413
274763LEE CO EC;4U
Adder
8.314
972236AH1-702 GEN2
Adder
1.967
274695ROCKY RD ;2P
Adder
9.87
254304AE2-114 C
Solar/Wind Helper
0.201
235054AD2-180 GEN
Solar/Wind Helper
1.553
945421AF1-207 GEN
Solar/Wind Harmer
3.217
24721605FLATG1
50/50
3.326
957241AF2-018 GEN
Solar/Wind Harmer
8.033
270053AF1-130 C
Solar/Wind Harmer
32.096
270400AC1-102 GEN
Solar/Wind Harmer
7.582
941621AE2-160 GEN
Adder
5.453
24734805WLF1G4
Adder
8.32
24735105WLF2G1
Adder
8.13
971329AH1-144 GEN
Solar/Wind Harmer
8.204
3429211JKCT 2G
Adder
12.98
972163AH1-664 GEN
Solar/Wind Harmer
10.818
944221AF1-090 GEN
Solar/Wind Harmer
10.637
25196508WSDLE4
Adder
8.182
963841AG1-237 GEN
Solar/Wind Harmer
10.358
270356AE2-297 GEN
Solar/Wind Harmer
4.331
274854TWINGROVE;U2
Solar/Wind Harmer
6.522
946581AF1-322 GEN
Solar/Wind Harmer
9.458
276726Z2-087_GEN
Solar/Wind Harmer
7.262
274746AC1-111 G10
Adder
4.935
274731ELWOOD EC;2P
Adder
14.442
274733ELWOOD EC;3P
Adder
14.442
23750501ELLIOTTS
Solar/Wind Helper
0.617
241982AE2-343 S C
Solar/Wind Helper
0.206
20089126CSLMN_L13
Solar/Wind Helper
0.537
238118U2-030_1
Solar/Wind Helper
0.261
CPLELTFEXP_CPLE->PJM
CLTF
7.6
CBM West 2LTFEXP_CBM-W2->PJM
CBM
138.522
LAGNLTFEXP_LAGN->PJM
CLTF
21.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.819
NYPJM->LTFIMP_NY
CLTF
4.806
LGEELTFEXP_LGEE->PJM
CLTF
7.592
TVALTFEXP_TVA->PJM
CLTF
11.07
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.205
AH1-155LTFEXP_AH1-155->PJM
LTF
0.307
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.561
MECLTFEXP_MEC->PJM
CLTF
15.956
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4976.63
MW Contribution:
4.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318705GVG2
50/50
10.829
971191AH1-055 GEN
Solar/Wind Harmer
25.524
970879AG2-548 GEN
Solar/Wind Harmer
5.846
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
6.527
972167AH1-666 GEN
Solar/Wind Harmer
6.143
972273AH1-721 GEN
Adder
91.222
25196008MFTGT1
Adder
1.411
253394AE2-221_GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
19.808
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.022
970825AG2-519 GEN
Solar/Wind Harmer
4.865
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.45
970571AG2-364 GEN
Solar/Wind Harmer
12.579
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
946671AF1-331 GEN
Solar/Wind Harmer
0.666
274729ELWOOD EC;1P
Adder
14.558
237048AF1-022 C
Solar/Wind Helper
0.175
237046AF1-021 C
Solar/Wind Helper
0.301
971313AH1-133 GEN
Solar/Wind Harmer
4.633
971061AG2-657 GEN
Solar/Wind Harmer
5.63
25196108MFTGT2
Adder
1.606
25196108MFTGT2
Adder
1.492
25196408WSDLE3
Adder
9.098
25196308WSDLE2
Adder
9.019
25196208WSDLE1
Adder
8.997
25196708WSDLE6
Adder
8.974
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.484
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
10.116
274856ECOGROVE ;U1
Solar/Wind Harmer
0.147
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
970073AG2-061 GEN
Solar/Wind Harmer
2.078
274728ELWOOD EC;5P
Adder
14.558
970879AG2-548 GEN
Solar/Wind Harmer
1.329
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970107AG2-081 GEN
Solar/Wind Harmer
2.281
970241AG2-163 GEN
Solar/Wind Harmer
3.886
276838X2-022 GEN2
Solar/Wind Harmer
0.37
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.08
276645AC1-214 GEN1
Solar/Wind Harmer
0.248
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.019
274762LEE CO EC;3U
Adder
8.386
938861AE1-114 GEN
Solar/Wind Harmer
3.56
962691AG1-118 GEN
Solar/Wind Harmer
18.68
274696ROCKY RD ;4P
Adder
10.15
274697ROCKY RD ;3P
Adder
2.694
276897AD1-100 C
Solar/Wind Harmer
15.453
276893AG1-478 C
Solar/Wind Harmer
0.412
274888KELLY CRK;1U
Solar/Wind Harmer
0.359
970941AG2-585 GEN
Solar/Wind Harmer
3.385
237043AE2-125 C
Solar/Wind Helper
0.157
23751201ROTHROCK
Solar/Wind Helper
0.666
243186AF1-051 GEN
50/50
11.683
24721705FLATG2
50/50
36.759
24723005RIVRG1
Adder
32.69
24723105RIVRG2
Adder
32.69
971225AH1-072 GEN
Solar/Wind Harmer
1.885
971227AH1-073 GEN
Solar/Wind Harmer
1.885
270583AD2-179 GEN
Solar/Wind Harmer
7.872
971125AH1-004 GEN
Solar/Wind Harmer
3.042
971587AH1-292 GEN
Solar/Wind Harmer
5.311
276916AD2-100_GEN
Solar/Wind Harmer
13.944
970291AG2-192 GEN
Solar/Wind Harmer
0.844
970291AG2-192 GEN
Solar/Wind Harmer
0.389
971613AH1-306 GEN
Solar/Wind Harmer
3.113
253370AE2-315 SEC1
Adder
1.843
247621Y3-024
Adder
0.218
25322209TAIT E
Adder
8.794
25322209TAIT E
Adder
8.596
971341AH1-150 GEN
Solar/Wind Harmer
12.516
971343AH1-151 GEN
Solar/Wind Harmer
12.516
276901AD2-066 C O1
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.657
970281AG2-184 GEN
Solar/Wind Harmer
20.069
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.257
276848AB2-070 GEN3
Solar/Wind Harmer
0.256
276849AB2-070 GEN2
Solar/Wind Harmer
0.257
970289AG2-191 GEN
Solar/Wind Harmer
1.233
25306009OHH W.
Adder
2.654
253372AE2-315 SEC3
Adder
1.743
253372AE2-315 SEC3
Adder
1.743
959341AF2-225 GEN
Solar/Wind Harmer
6.721
274877BISHOP HL;1U
Solar/Wind Harmer
0.211
970169AG2-114 GEN
Solar/Wind Harmer
6.325
276741O09 GEN1
Solar/Wind Harmer
0.223
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
4.965
274735ELWOOD EC;4P
Adder
14.558
270399AC1-101 GEN
Solar/Wind Harmer
3.431
24734705WLF1G3
Adder
7.275
24734905WLF1G5
Adder
7.275
971985AH1-537 GEN
Solar/Wind Harmer
2.606
966391AG1-508 GEN
Solar/Wind Harmer
1.323
971331AH1-145 GEN
Solar/Wind Harmer
10.902
971981AH1-535 GEN
Solar/Wind Harmer
5.247
972165AH1-665 GEN
Solar/Wind Harmer
6.87
339216AC1-074 GEN
Solar/Wind Harmer
0.202
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270069AE2-166 C O1
Solar/Wind Harmer
6.22
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.69
247536S-71 GEN
Solar/Wind Harmer
0.254
971611AH1-305 GEN
Solar/Wind Harmer
3.778
24686505CER G6
Adder
14.074
24728305BUCHG2
Adder
6.196
3429241JKCT 3G
Adder
13.004
962761AG1-125 GEN
Solar/Wind Harmer
27.311
965911AG1-460 GEN
Solar/Wind Harmer
1.325
270437AC2-090 C
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.31
270273AD2-016 GEN
Solar/Wind Harmer
0.662
276708O09 GEN2
Solar/Wind Harmer
0.223
274766LEE CO EC;7U
Adder
8.287
243186AF1-051 GEN
50/50
11.683
24721805FLATG3
50/50
2.475
24723205RIVRG3
Adder
32.69
972203AH1-686 GEN
Adder
3.965
24735205WLF2G2
Adder
7.131
945681AF1-233 GEN
Solar/Wind Harmer
14.491
964901AG1-354 GEN
Solar/Wind Harmer
11.126
252516AE2-318_GEN
Solar/Wind Harmer
8.161
25194608D.CRK4
Adder
1.702
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.045
970155AG2-107 GEN
Solar/Wind Harmer
17.44
24728605AND G2
Adder
3.745
943811AF1-049 GEN
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.832
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
18.774
274828WAUKEGAN ;BP
Adder
9.84
274682WAUKEGAN ;7U
Adder
16.004
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.965
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
1.811
274676JOLIET 29;8U
Adder
9.572
238185AF2-356 C
Solar/Wind Helper
1.975
24318705GVG2
50/50
10.829
971687AH1-348 GEN
Solar/Wind Harmer
0.943
25196808ZIMRHP
Adder
79.991
25196008MFTGT1
Adder
1.457
252510AF1-249 C
Solar/Wind Harmer
0.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.329
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
7.264
270032AE2-172
Solar/Wind Harmer
4.324
270005AE1-210 C O1
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
2.292
939741AE1-205 GEN
Solar/Wind Harmer
8.961
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.933
970569AG2-363 GEN
Solar/Wind Harmer
18.869
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.386
945371AF1-202 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
3.283
276805AD2-038 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.692
25326309TAIT D
Adder
0.988
939401AE1-172 GEN
Solar/Wind Harmer
4.684
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
5.929
274732ELWOOD EC;7P
Adder
14.558
274674JOLIET 9 ;6U
Adder
13.632
942891AE2-308 GEN
Solar/Wind Harmer
7.677
972043AH1-570 GEN
Solar/Wind Harmer
1.99
971485AH1-239 GEN
Solar/Wind Harmer
5.968
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25194408D.CRK1
Adder
7.827
945391AF1-204 GEN
Solar/Wind Harmer
7.253
24728905RICHG2
Adder
3.656
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.068
24289405MTG1
50/50
10.896
944971AF1-162 GEN
Solar/Wind Harmer
10.992
971403AH1-188 GEN
Solar/Wind Harmer
15.251
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.329
970091AG2-072 GEN
Adder
86.562
3429421JKCT 10G
Adder
9.095
970653AG2-424 GEN
Solar/Wind Harmer
3.596
970149AG2-104 GEN
Solar/Wind Harmer
14.748
970773AG2-487 GEN
Solar/Wind Harmer
1.199
963741AG1-226 GEN
Solar/Wind Harmer
15.765
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.248
970819AG2-516 GEN
Solar/Wind Harmer
7.523
274822ROCKFORD ;11
Adder
17.613
959081AF2-199 GEN
Solar/Wind Harmer
6.258
971067AG2-660 GEN
Solar/Wind Harmer
2.086
971917AH1-482 GEN
Solar/Wind Harmer
8.135
276882AE2-255 GEN
Solar/Wind Harmer
0.729
274872LEEDK;1U
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.009
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
5.443
24721605FLATG1
50/50
2.475
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
24.531
270400AC1-102 GEN
Solar/Wind Harmer
3.431
941621AE2-160 GEN
Adder
4.685
24734805WLF1G4
Adder
7.275
24735105WLF2G1
Adder
7.131
971329AH1-144 GEN
Solar/Wind Harmer
4.007
972163AH1-664 GEN
Solar/Wind Harmer
8.578
3429211JKCT 2G
Adder
12.836
25196508WSDLE4
Adder
8.748
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.692
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.926
963841AG1-237 GEN
Solar/Wind Harmer
2.866
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
2.468
926823AC1-168 GEN
Solar/Wind Harmer
1.07
274746AC1-111 G10
Adder
4.965
274731ELWOOD EC;2P
Adder
14.558
274733ELWOOD EC;3P
Adder
14.558
23750501ELLIOTTS
Solar/Wind Helper
0.598
970913AG2-568 GEN
Solar/Wind Harmer
8.105
24728205BUCHG1
Adder
6.196
971277AH1-098 GEN
Solar/Wind Harmer
3.388
971073AG2-665 GEN
Solar/Wind Harmer
5.846
972045AH1-571 GEN
Solar/Wind Harmer
1.594
966021AG1-471 GEN
Solar/Wind Harmer
4.034
252509AD1-136 GEN
Solar/Wind Harmer
0.037
964571AG1-320 GEN
Solar/Wind Harmer
6.787
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.743
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.145
970883AG2-550 GEN
Solar/Wind Harmer
6.406
270599AE1-208 GEN
Solar/Wind Harmer
5.804
274764LEE CO EC;5U
Adder
8.405
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.263
274683WAUKEGAN ;8U
Adder
18.772
274683WAUKEGAN ;8U
Adder
15.824
274693ROCKY RD ;1P
Adder
9.818
958481AF2-142 GEN
Solar/Wind Harmer
9.318
274674JOLIET 9 ;6U
Adder
13.632
960971AF2-388 GEN
Solar/Wind Harmer
3.621
23585401KL_K28_T16
Solar/Wind Helper
1.157
971461AH1-227 GEN
Solar/Wind Harmer
4.836
270346AE1-212 GEN
Solar/Wind Harmer
7.826
958121AF2-106 GEN
Solar/Wind Harmer
0
3429391JKCT 9G
Adder
9.095
958171AF2-111 GEN
Solar/Wind Harmer
18.695
252507AC2-088 GEN
Solar/Wind Harmer
0.336
25196608WSDLE5
Adder
8.838
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.463
24728805RICHG1
Adder
3.656
276911AD2-131_GEN
Solar/Wind Harmer
0.919
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.135
270031AE2-169
Solar/Wind Harmer
3.483
964611AG1-324 GEN
Solar/Wind Harmer
0.475
270201AC2-176 GEN
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
8.405
274763LEE CO EC;4U
Adder
8.307
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.968
958491AF2-143 GEN
Solar/Wind Harmer
9.353
274695ROCKY RD ;2P
Adder
9.916
944541AF1-119 GEN
Solar/Wind Harmer
0.412
958011AF2-095 GEN
Solar/Wind Harmer
8.864
235054AD2-180 GEN
Solar/Wind Helper
1.531
970193AG2-126 GEN
Solar/Wind Harmer
10.239
24728705AND G3
Adder
7.833
970781AG2-491 GEN
Solar/Wind Harmer
6.48
959611AF2-252 GEN
Solar/Wind Harmer
2.145
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
276868AE1-113 GEN
Solar/Wind Harmer
1.25
274879MINONK ;1U
Solar/Wind Harmer
0.261
274862TOP CROP ;2U
Solar/Wind Harmer
0.839
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
14.558
970707AG2-453 GEN
Solar/Wind Harmer
20.15
274887GEN-1.85
Solar/Wind Harmer
0.16
24289405MTG1
50/50
10.896
24686405CER G5
Adder
13.963
970455AG2-298 GEN
Solar/Wind Harmer
2.913
970653AG2-424 GEN
Solar/Wind Harmer
0.745
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.4
965091AG1-374 GEN
Solar/Wind Harmer
19.301
970191AG2-125 GEN
Solar/Wind Harmer
1.638
965931AG1-462 GEN
Solar/Wind Harmer
16.203
274878BISHOP HL;2U
Solar/Wind Harmer
0.211
274760LEE CO EC;1U
Adder
8.386
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.199
23562501BACKB
Solar/Wind Helper
0.811
24722005FLATG5
50/50
2.475
24721905FLATG4
50/50
45.211
960911AF2-382 GEN
Solar/Wind Harmer
7.256
972103AH1-617 GEN
Solar/Wind Harmer
19.113
943031AE2-326 GEN
Solar/Wind Harmer
4.478
252519AF1-045_GEN
Solar/Wind Harmer
3.801
25194608D.CRK4
Adder
1.702
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.158
962771AG1-126 GEN
Solar/Wind Harmer
27.311
970153AG2-106 GEN
Solar/Wind Harmer
17.44
24728505AND G1
Adder
3.745
270030AE2-140 GEN
Solar/Wind Harmer
13.518
957381AF2-032 GEN
Solar/Wind Harmer
1.5
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.714
946031AF1-268 GEN
Solar/Wind Harmer
6.123
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
971087AG2-675 GEN
Solar/Wind Harmer
3.389
274767LEE CO EC;8U
Adder
8.287
959091AF2-200 GEN
Solar/Wind Harmer
12.516
274682WAUKEGAN ;7U
Adder
16.004
943121AE2-341 GEN
Solar/Wind Harmer
10.39
943591AF1-030 GEN
Solar/Wind Harmer
6.91
274734ELWOOD EC;8P
Adder
14.558
274736ELWOOD EC;9P
Adder
14.558
276806AD2-047 C O1
Solar/Wind Harmer
3.488
235058AG1-386 C
Solar/Wind Helper
0.387
946321AF1-296 GEN
Solar/Wind Harmer
3.554
959141AF2-205 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.763
945581AF1-223 GEN
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.485
971171AH1-044 GEN
Solar/Wind Harmer
12.516
971675AH1-338 GEN
Solar/Wind Harmer
2.437
971411AH1-196 GEN
Solar/Wind Harmer
9.369
970833AG2-524 GEN
Solar/Wind Harmer
6.809
970833AG2-524 GEN
Solar/Wind Harmer
4.54
274675JOLIET 29;7U
Adder
27.142
960591AF2-350 GEN
Solar/Wind Harmer
6.155
23652301WDPWR_K20
Solar/Wind Helper
0.127
CPLELTFEXP_CPLE->PJM
CLTF
6.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.098
LAGNLTFEXP_LAGN->PJM
CLTF
19.698
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23
NYPJM->LTFIMP_NY
CLTF
4.626
LGEELTFEXP_LGEE->PJM
CLTF
7.468
TVALTFEXP_TVA->PJM
CLTF
10.208
WECLTFEXP_WEC->PJM
CLTF
3.435
AG2-052LTFEXP_AG2-052->PJM
LTF
0.207
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
115.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.783
MECLTFEXP_MEC->PJM
CLTF
15.666
SIGELTFEXP_SIGE->PJM
CLTF
0.545

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.41 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5987.66
MW Contribution:
10.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318705GVG2
50/50
11.822
270331AC1-082 GEN3
Solar/Wind Harmer
0.864
971687AH1-348 GEN
Solar/Wind Harmer
1.658
270330AC1-082 GEN2
Solar/Wind Harmer
0.862
971461AH1-227 GEN
Solar/Wind Harmer
8.512
270346AE1-212 GEN
Solar/Wind Harmer
14.67
24686505CER G6
Adder
16.156
24728305BUCHG2
Adder
7.739
339211AE2-254 GEN
Solar/Wind Harmer
1.998
3429241JKCT 3G
Adder
15.659
962761AG1-125 GEN
Solar/Wind Harmer
38.013
316217AC1-145 GEN
Solar/Wind Harmer
2.791
316197AC1-042 GEN
Solar/Wind Harmer
2.116
944031AF1-071 GEN
Solar/Wind Harmer
1.174
965911AG1-460 GEN
Solar/Wind Harmer
1.606
270437AC2-090 C
Solar/Wind Harmer
6.354
24385905FR-11G C
Solar/Wind Harmer
9.442
276903AD2-071 C
Solar/Wind Harmer
11.325
274766LEE CO EC;7U
Adder
10.085
25326309TAIT D
Adder
1.195
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252510AF1-249 C
Solar/Wind Harmer
0.517
253398AE2-221_GEN2
Solar/Wind Harmer
5.329
3147312GRETNA
Solar/Wind Harmer
-0.003
276621W2-048 GEN
Solar/Wind Harmer
7.12
942081AE2-220 GEN
Solar/Wind Harmer
7.281
270209AC1-174_GEN
Solar/Wind Harmer
4.633
270239V3-007_GEN1
Solar/Wind Harmer
1.959
24386605FR-22G C
Solar/Wind Harmer
4.886
274761LEE CO EC;2U
Adder
10.206
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
270594AE1-207 GEN
Solar/Wind Harmer
12.561
270032AE2-172
Solar/Wind Harmer
4.302
24289405MTG1
50/50
11.78
24686405CER G5
Adder
16.028
270329AC1-082 GEN1
Solar/Wind Harmer
0.862
339206AE1-143 GEN
Solar/Wind Harmer
2.789
339243AC2-075 GEN1
Solar/Wind Harmer
0.591
970455AG2-298 GEN
Solar/Wind Harmer
4.537
970653AG2-424 GEN
Solar/Wind Harmer
0.902
339255AE2-071 GEN
Solar/Wind Harmer
1.514
339250AF1-203 GEN
Solar/Wind Harmer
0.779
941801AE2-185 GEN
Solar/Wind Harmer
6.453
24379505HDWTR1G C
Solar/Wind Harmer
9.002
24386205FR-12G C
Solar/Wind Harmer
4.868
274760LEE CO EC;1U
Adder
10.206
23562501BACKB
Solar/Wind Helper
0.87
24289405MTG1
50/50
11.78
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
26.012
960001AF2-291 GEN
Solar/Wind Harmer
5.313
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
270173AC1-122 GEN
Solar/Wind Harmer
2.206
3429421JKCT 10G
Adder
10.948
339221AD2-048_GEN
Solar/Wind Harmer
2.01
970653AG2-424 GEN
Solar/Wind Harmer
6.236
970149AG2-104 GEN
Solar/Wind Harmer
23.473
270222AC2-111 GEN
Solar/Wind Harmer
5.217
963741AG1-226 GEN
Solar/Wind Harmer
51.846
276686W4-005 GEN3
Solar/Wind Harmer
3.438
274822ROCKFORD ;11
Adder
21.436
243186AF1-051 GEN
50/50
12.754
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24735205WLF2G2
Adder
8.97
270336AE1-100 GEN
Solar/Wind Harmer
2.369
945681AF1-233 GEN
Solar/Wind Harmer
24.773
943111AE2-339 GEN
Solar/Wind Harmer
1.158
943811AF1-049 GEN
Solar/Wind Harmer
4.941
339241AF1-083 GEN
Solar/Wind Harmer
2.163
964901AG1-354 GEN
Solar/Wind Harmer
19.398
252516AE2-318_GEN
Solar/Wind Harmer
12.45
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
10.112
946171AF1-282 GEN
Solar/Wind Harmer
12.079
24728605AND G2
Adder
4.51
970155AG2-107 GEN
Solar/Wind Harmer
16.575
270574AD1-017 GEN2
Solar/Wind Harmer
5.994
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274745AC1-111 GEN9
Adder
6.042
274676JOLIET 29;8U
Adder
11.649
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
964201AG1-281 GEN
Solar/Wind Helper
0.442
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
270214AC2-123 GEN
Solar/Wind Harmer
3.869
971225AH1-072 GEN
Solar/Wind Harmer
3.319
971227AH1-073 GEN
Solar/Wind Harmer
3.319
270583AD2-179 GEN
Solar/Wind Harmer
16.289
971125AH1-004 GEN
Solar/Wind Harmer
5.238
276916AD2-100_GEN
Solar/Wind Harmer
24.22
970291AG2-192 GEN
Solar/Wind Harmer
1.461
970291AG2-192 GEN
Solar/Wind Harmer
0.47
253370AE2-315 SEC1
Adder
2.225
247621Y3-024
Adder
0.264
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
316097T157 G90
Solar/Wind Helper
1.102
942891AE2-308 GEN
Solar/Wind Harmer
13.25
972043AH1-570 GEN
Solar/Wind Harmer
3.285
971485AH1-239 GEN
Solar/Wind Harmer
10.457
964781AG1-341 GEN
Solar/Wind Harmer
13.643
25194408D.CRK1
Adder
9.34
945391AF1-204 GEN
Solar/Wind Harmer
16.433
942671AE2-283 GEN
Solar/Wind Harmer
5.701
24728905RICHG2
Adder
4.399
253415AE1-040 GEN
Solar/Wind Harmer
1.308
276615X2-022 GEN
Solar/Wind Harmer
2.236
926881AC1-175 GEN
Solar/Wind Harmer
6.354
966841AG1-555 GEN
Solar/Wind Harmer
2.852
24725505WLD G2 C
Solar/Wind Harmer
4.513
274764LEE CO EC;5U
Adder
10.23
972235AH1-702 GEN1
Adder
2.754
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274693ROCKY RD ;1P
Adder
11.949
274674JOLIET 9 ;6U
Adder
16.589
23585401KL_K28_T16
Solar/Wind Helper
1.275
238117U2-030
Solar/Wind Helper
0.29
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
958121AF2-106 GEN
Solar/Wind Harmer
7.386
957541AF2-048 GEN
Solar/Wind Harmer
2.364
3429391JKCT 9G
Adder
10.948
958171AF2-111 GEN
Solar/Wind Harmer
32.027
252507AC2-088 GEN
Solar/Wind Harmer
2.278
25196608WSDLE5
Adder
10.55
270018AE2-047 C O1
Solar/Wind Harmer
1.501
970193AG2-126 GEN
Solar/Wind Harmer
17.687
24728705AND G3
Adder
9.433
274730ELWOOD EC;6P
Adder
17.715
238127S14_GEN_2
Solar/Wind Helper
0.692
202652Y1-033 WT C
Solar/Wind Helper
0.538
20092526R32
Solar/Wind Helper
1.061
270399AC1-101 GEN
Solar/Wind Harmer
7.81
966391AG1-508 GEN
Solar/Wind Harmer
5.744
971331AH1-145 GEN
Solar/Wind Harmer
15.307
24734705WLF1G3
Adder
9.154
24734905WLF1G5
Adder
9.154
971985AH1-537 GEN
Solar/Wind Harmer
26.103
971981AH1-535 GEN
Solar/Wind Harmer
14.155
270069AE2-166 C O1
Solar/Wind Harmer
12.483
972165AH1-665 GEN
Solar/Wind Harmer
10.538
339216AC1-074 GEN
Solar/Wind Harmer
2.182
270291AC1-194 GEN
Solar/Wind Harmer
6.437
253406AD2-031_GEN
Solar/Wind Harmer
1.524
24386405FR-21G C
Solar/Wind Harmer
4.886
972267AH1-718 GEN
Adder
4.579
274823ROCKFORD ;21
Adder
21.28
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
960911AF2-382 GEN
Solar/Wind Harmer
12.889
943031AE2-326 GEN
Solar/Wind Harmer
6.089
972103AH1-617 GEN
Solar/Wind Harmer
33.161
270030AE2-140 GEN
Solar/Wind Harmer
26.764
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
252524AE2-267 GEN
Solar/Wind Harmer
1.938
253317AC1-085 GEN4
Solar/Wind Harmer
10.112
946181AF1-283 GEN
Solar/Wind Harmer
15.702
24728505AND G1
Adder
4.51
962771AG1-126 GEN
Solar/Wind Harmer
38.013
970153AG2-106 GEN
Solar/Wind Harmer
16.575
957381AF2-032 GEN
Solar/Wind Harmer
2.3
276785W4-005 GEN1
Solar/Wind Harmer
3.438
247642Z2-115 C
Solar/Wind Harmer
0.072
970289AG2-191 GEN
Solar/Wind Harmer
0.862
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274767LEE CO EC;8U
Adder
10.085
274682WAUKEGAN ;7U
Adder
19.478
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
964991AG1-363 GEN
Solar/Wind Helper
3.731
238110AE1-109 GEN3
Solar/Wind Helper
0.089
235058AG1-386 C
Solar/Wind Helper
0.381
274675JOLIET 29;7U
Adder
33.032
23750701CROSSCHOOL
Solar/Wind Helper
1.205
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
970281AG2-184 GEN
Solar/Wind Harmer
34.819
962211AG1-066 GEN
Solar/Wind Harmer
3.81
270444AC2-157 GEN1
Solar/Wind Harmer
6.941
270445AC2-157 GEN2
Solar/Wind Harmer
6.941
253433AC1-085 GEN1
Solar/Wind Harmer
6.419
253432AC1-085 GEN2
Solar/Wind Harmer
0.323
270197AD1-017 GEN1
Solar/Wind Harmer
1.798
276763AC1-053 GEN1
Solar/Wind Harmer
4.5
276764AC1-053 GEN2
Solar/Wind Harmer
4.5
276668AB2-070 GEN1
Solar/Wind Harmer
2.517
276848AB2-070 GEN3
Solar/Wind Harmer
2.517
276849AB2-070 GEN2
Solar/Wind Harmer
2.517
970289AG2-191 GEN
Solar/Wind Harmer
2.135
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
274744AC1-111 GEN8
Adder
6.042
274735ELWOOD EC;4P
Adder
17.715
970879AG2-548 GEN
Solar/Wind Harmer
1.558
970107AG2-081 GEN
Solar/Wind Harmer
3.929
962581AG1-107 GEN
Solar/Wind Harmer
6.569
961491AF2-440 GEN
Solar/Wind Harmer
2.73
339236AF1-050_GEN
Solar/Wind Harmer
2.347
970241AG2-163 GEN
Solar/Wind Harmer
28.803
276838X2-022 GEN2
Solar/Wind Harmer
0.266
274880W4-005 GEN4
Solar/Wind Harmer
3.438
276174W4-005 GEN2
Solar/Wind Harmer
3.438
24387305FR-4G C
Solar/Wind Harmer
5.77
274762LEE CO EC;3U
Adder
10.206
274696ROCKY RD ;4P
Adder
12.353
274697ROCKY RD ;3P
Adder
3.278
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
24318705GVG2
50/50
11.822
971191AH1-055 GEN
Solar/Wind Harmer
30.574
970879AG2-548 GEN
Solar/Wind Harmer
10.717
972273AH1-721 GEN
Adder
111.17
970093AG2-073 GEN
Solar/Wind Harmer
7.05
270186AC1-089 GEN
Solar/Wind Harmer
8.102
270367AC2-061_GEN
Solar/Wind Harmer
4.197
972167AH1-666 GEN
Solar/Wind Harmer
10.503
962751AG1-124 GEN
Solar/Wind Harmer
11.766
25196008MFTGT1
Adder
1.685
253394AE2-221_GEN
Solar/Wind Harmer
5.329
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
942481AE2-261 GEN
Solar/Wind Harmer
34.409
270240V3-007_GEN2
Solar/Wind Harmer
7.043
971993AH1-541 GEN
Solar/Wind Harmer
10.504
965461AG1-414 GEN
Solar/Wind Harmer
2.547
274729ELWOOD EC;1P
Adder
17.715
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
971313AH1-133 GEN
Solar/Wind Harmer
10.201
971061AG2-657 GEN
Solar/Wind Harmer
14.005
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
24387005FR-3G C
Solar/Wind Harmer
4.493
274728ELWOOD EC;5P
Adder
17.715
20089226LOOKOUT
Solar/Wind Helper
0.556
203940AF1-140 C
Solar/Wind Helper
0.362
970913AG2-568 GEN
Solar/Wind Harmer
11.956
24728205BUCHG1
Adder
7.739
971277AH1-098 GEN
Solar/Wind Harmer
6.62
927014AC1-188 GEN
Solar/Wind Harmer
2.364
971073AG2-665 GEN
Solar/Wind Harmer
10.717
339231AF1-038_GEN
Solar/Wind Harmer
2.384
972045AH1-571 GEN
Solar/Wind Harmer
2.628
966021AG1-471 GEN
Solar/Wind Harmer
7.071
964571AG1-320 GEN
Solar/Wind Harmer
10.544
252509AD1-136 GEN
Solar/Wind Harmer
0.325
25183208HLCRTG
Solar/Wind Harmer
7.535
25194508D.CRK3
Adder
1.746
24728805RICHG1
Adder
4.399
276911AD2-131_GEN
Solar/Wind Harmer
4.895
24699105WLD G1 C
Solar/Wind Harmer
4.461
270383AD1-128 GEN
Solar/Wind Harmer
6.909
274765LEE CO EC;6U
Adder
10.23
274763LEE CO EC;4U
Adder
10.109
972236AH1-702 GEN2
Adder
2.395
274695ROCKY RD ;2P
Adder
12.068
235054AD2-180 GEN
Solar/Wind Helper
1.707
235531U2-073 GEN
Solar/Wind Helper
2.776
203961AE2-224 GEN
Solar/Wind Helper
2.204
238108AE1-109 GEN1
Solar/Wind Helper
0.089
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
8.236
270053AF1-130 C
Solar/Wind Harmer
32.909
270400AC1-102 GEN
Solar/Wind Harmer
7.81
941621AE2-160 GEN
Adder
5.641
971329AH1-144 GEN
Solar/Wind Harmer
9.777
24734805WLF1G4
Adder
9.154
24735105WLF2G1
Adder
8.97
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
13.172
25196508WSDLE4
Adder
10.442
270340AC2-060 GEN
Solar/Wind Harmer
3.588
270263AC1-001 GEN
Solar/Wind Harmer
1.236
270356AE2-297 GEN
Solar/Wind Harmer
5.395
944221AF1-090 GEN
Solar/Wind Harmer
12.7
963841AG1-237 GEN
Solar/Wind Harmer
12.506
274746AC1-111 G10
Adder
6.042
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
23750501ELLIOTTS
Solar/Wind Helper
0.639
238118U2-030_1
Solar/Wind Helper
0.29
20089126CSLMN_L13
Solar/Wind Helper
0.558
20088926STNY CRK
Solar/Wind Helper
0.752
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
TVALTFEXP_TVA->PJM
CLTF
12.601
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.46 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5935.05
MW Contribution:
8.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
2.718
24721905FLATG4
50/50
49.64
962771AG1-126 GEN
Solar/Wind Harmer
51.105
970153AG2-106 GEN
Solar/Wind Harmer
22.284
960911AF2-382 GEN
Solar/Wind Harmer
10.97
972103AH1-617 GEN
Solar/Wind Harmer
29.032
943031AE2-326 GEN
Solar/Wind Harmer
4.698
24728505AND G1
Adder
4.399
957381AF2-032 GEN
Solar/Wind Harmer
2.285
276785W4-005 GEN1
Solar/Wind Harmer
3.443
247642Z2-115 C
Solar/Wind Harmer
0.073
970289AG2-191 GEN
Solar/Wind Harmer
0.868
25194608D.CRK4
Adder
1.843
274767LEE CO EC;8U
Adder
10.284
274682WAUKEGAN ;7U
Adder
20.049
274734ELWOOD EC;8P
Adder
18.315
274736ELWOOD EC;9P
Adder
18.315
235058AG1-386 C
Solar/Wind Helper
0.44
964991AG1-363 GEN
Solar/Wind Helper
3.654
20303426NA_O38_P22
Solar/Wind Helper
0.938
203993AD2-133_GEN1
Solar/Wind Helper
0.966
238110AE1-109 GEN3
Solar/Wind Helper
0.084
270330AC1-082 GEN2
Solar/Wind Harmer
0.779
971461AH1-227 GEN
Solar/Wind Harmer
7.34
270346AE1-212 GEN
Solar/Wind Harmer
11.918
957541AF2-048 GEN
Solar/Wind Harmer
2.06
3429391JKCT 9G
Adder
9.84
958121AF2-106 GEN
Solar/Wind Harmer
5.343
970193AG2-126 GEN
Solar/Wind Harmer
17.459
24728705AND G3
Adder
9.201
252507AC2-088 GEN
Solar/Wind Harmer
2.051
970781AG2-491 GEN
Solar/Wind Harmer
11.422
958171AF2-111 GEN
Solar/Wind Harmer
28.524
959611AF2-252 GEN
Solar/Wind Harmer
2.632
25196608WSDLE5
Adder
9.576
274730ELWOOD EC;6P
Adder
18.315
202652Y1-033 WT C
Solar/Wind Helper
0.551
238127S14_GEN_2
Solar/Wind Helper
0.674
20092526R32
Solar/Wind Helper
1.103
270399AC1-101 GEN
Solar/Wind Harmer
6.93
24734705WLF1G3
Adder
7.73
24734905WLF1G5
Adder
7.73
971985AH1-537 GEN
Solar/Wind Harmer
23.681
966391AG1-508 GEN
Solar/Wind Harmer
4.439
971331AH1-145 GEN
Solar/Wind Harmer
11.397
971981AH1-535 GEN
Solar/Wind Harmer
12.094
972165AH1-665 GEN
Solar/Wind Harmer
9.41
339216AC1-074 GEN
Solar/Wind Harmer
1.968
24386405FR-21G C
Solar/Wind Harmer
4.939
274853TWINGROVE;U1
Solar/Wind Harmer
8.154
972267AH1-718 GEN
Adder
4.661
274823ROCKFORD ;21
Adder
21.773
274775LINCOLN ;6U
Adder
9.41
274777LINCOLN ;8U
Adder
9.41
23652301WDPWR_K20
Solar/Wind Helper
0.142
23750701CROSSCHOOL
Solar/Wind Helper
1.189
203955AF1-039 C O1
Solar/Wind Helper
0.363
203846AF2-130 C
Solar/Wind Helper
0.423
959141AF2-205 GEN
Solar/Wind Harmer
1.763
942891AE2-308 GEN
Solar/Wind Harmer
11.926
972043AH1-570 GEN
Solar/Wind Harmer
2.957
971485AH1-239 GEN
Solar/Wind Harmer
9.407
964781AG1-341 GEN
Solar/Wind Harmer
12.396
945391AF1-204 GEN
Solar/Wind Harmer
16.22
966841AG1-555 GEN
Solar/Wind Harmer
2.883
24697605MDL-3G C
Solar/Wind Harmer
4.21
270181AB1-006 GEN2
Solar/Wind Harmer
0.817
276615X2-022 GEN
Solar/Wind Harmer
2.233
960611AF2-352 GEN
Solar/Wind Harmer
2.632
24725505WLD G2 C
Solar/Wind Harmer
4.494
25194408D.CRK1
Adder
8.477
274764LEE CO EC;5U
Adder
10.431
972235AH1-702 GEN1
Adder
2.817
274693ROCKY RD ;1P
Adder
12.303
274683WAUKEGAN ;8U
Adder
23.51
274683WAUKEGAN ;8U
Adder
19.818
274674JOLIET 9 ;6U
Adder
16.682
23585401KL_K28_T16
Solar/Wind Helper
1.282
238117U2-030
Solar/Wind Helper
0.286
254305AE2-115 C
Solar/Wind Helper
0.205
241967AE2-285_GEN
Solar/Wind Helper
0.597
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.571
20088826HIGHLAND
Solar/Wind Helper
0.851
24686505CER G6
Adder
14.723
962761AG1-125 GEN
Solar/Wind Harmer
51.105
24728305BUCHG2
Adder
6.531
339211AE2-254 GEN
Solar/Wind Harmer
1.806
3429241JKCT 3G
Adder
14.075
24385905FR-11G C
Solar/Wind Harmer
9.545
965911AG1-460 GEN
Solar/Wind Harmer
1.595
276903AD2-071 C
Solar/Wind Harmer
11.309
276656WTG2_EQ
Solar/Wind Harmer
1.306
274766LEE CO EC;7U
Adder
10.284
274732ELWOOD EC;7P
Adder
18.315
274674JOLIET 9 ;6U
Adder
17.154
20089026BF_G21_K23
Solar/Wind Helper
0.455
20084626FORWARD
Solar/Wind Helper
0.338
203855AF2-088 C
Solar/Wind Helper
0.143
24721605FLATG1
50/50
2.718
957241AF2-018 GEN
Solar/Wind Harmer
7.332
270053AF1-130 C
Solar/Wind Harmer
29.298
270400AC1-102 GEN
Solar/Wind Harmer
6.93
941621AE2-160 GEN
Adder
4.867
24734805WLF1G4
Adder
7.73
24735105WLF2G1
Adder
7.594
971329AH1-144 GEN
Solar/Wind Harmer
7.28
3429211JKCT 2G
Adder
13.893
972163AH1-664 GEN
Solar/Wind Harmer
11.763
963841AG1-237 GEN
Solar/Wind Harmer
12.582
944221AF1-090 GEN
Solar/Wind Harmer
12.541
946581AF1-322 GEN
Solar/Wind Harmer
11.687
270356AE2-297 GEN
Solar/Wind Harmer
5.225
274854TWINGROVE;U2
Solar/Wind Harmer
7.983
276726Z2-087_GEN
Solar/Wind Harmer
8.934
25196508WSDLE4
Adder
9.478
274746AC1-111 G10
Adder
6.235
274776LINCOLN ;7U
Adder
9.41
274731ELWOOD EC;2P
Adder
18.315
274733ELWOOD EC;3P
Adder
18.315
23750501ELLIOTTS
Solar/Wind Helper
0.664
238118U2-030_1
Solar/Wind Helper
0.286
241982AE2-343 S C
Solar/Wind Helper
0.209
20089126CSLMN_L13
Solar/Wind Helper
0.575
20088926STNY CRK
Solar/Wind Helper
0.78
20094526CT_V3-030
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.144
970913AG2-568 GEN
Solar/Wind Harmer
10.293
24728205BUCHG1
Adder
6.531
927014AC1-188 GEN
Solar/Wind Harmer
2.06
971277AH1-098 GEN
Solar/Wind Harmer
5.094
964571AG1-320 GEN
Solar/Wind Harmer
9.728
339231AF1-038_GEN
Solar/Wind Harmer
2.148
972045AH1-571 GEN
Solar/Wind Harmer
2.366
966021AG1-471 GEN
Solar/Wind Harmer
6.353
252509AD1-136 GEN
Solar/Wind Harmer
0.293
276911AD2-131_GEN
Solar/Wind Harmer
4.855
270180AB1-006 GEN1
Solar/Wind Harmer
8.215
24697905MDL-4G C
Solar/Wind Harmer
2.621
945421AF1-207 GEN
Solar/Wind Harmer
16.001
971073AG2-665 GEN
Solar/Wind Harmer
9.054
24699105WLD G1 C
Solar/Wind Harmer
4.441
25194508D.CRK3
Adder
1.585
274765LEE CO EC;6U
Adder
10.431
274763LEE CO EC;4U
Adder
10.309
972236AH1-702 GEN2
Adder
2.45
274695ROCKY RD ;2P
Adder
12.425
235054AD2-180 GEN
Solar/Wind Helper
1.698
254304AE2-114 C
Solar/Wind Helper
0.205
235531U2-073 GEN
Solar/Wind Helper
2.712
203961AE2-224 GEN
Solar/Wind Helper
2.277
946381AF1-302 GEN
Solar/Wind Helper
0.208
203946AE2-131 C
Solar/Wind Helper
0.445
203954AE2-126 C
Solar/Wind Helper
0.44
940863AE2-074 GEN
Solar/Wind Helper
0.426
24289405MTG1
50/50
11.32
944971AF1-162 GEN
Solar/Wind Harmer
11.548
971403AH1-188 GEN
Solar/Wind Harmer
22.954
960001AF2-291 GEN
Solar/Wind Harmer
4.782
970149AG2-104 GEN
Solar/Wind Harmer
31.557
970091AG2-072 GEN
Adder
98.735
970653AG2-424 GEN
Solar/Wind Harmer
5.716
3429421JKCT 10G
Adder
9.84
339221AD2-048_GEN
Solar/Wind Harmer
1.812
963741AG1-226 GEN
Solar/Wind Harmer
51.931
24791305MDL-5G
Solar/Wind Harmer
2.754
276686W4-005 GEN3
Solar/Wind Harmer
3.443
971073AG2-665 GEN
Solar/Wind Harmer
1.316
276655WTG1_EQ
Solar/Wind Harmer
9.862
274822ROCKFORD ;11
Adder
21.932
24289405MTG1
50/50
11.32
24686405CER G5
Adder
14.607
270329AC1-082 GEN1
Solar/Wind Harmer
0.779
970455AG2-298 GEN
Solar/Wind Harmer
4.162
339206AE1-143 GEN
Solar/Wind Harmer
2.532
970653AG2-424 GEN
Solar/Wind Harmer
0.827
339243AC2-075 GEN1
Solar/Wind Harmer
0.533
339255AE2-071 GEN
Solar/Wind Harmer
1.375
339250AF1-203 GEN
Solar/Wind Harmer
0.708
24386205FR-12G C
Solar/Wind Harmer
4.921
24690905MDL-1G C
Solar/Wind Harmer
9.169
965091AG1-374 GEN
Solar/Wind Harmer
33.954
274760LEE CO EC;1U
Adder
10.407
23562501BACKB
Solar/Wind Helper
0.897
238108AE1-109 GEN1
Solar/Wind Helper
0.084
203854AF2-039 C
Solar/Wind Helper
0.298
243186AF1-051 GEN
50/50
12.373
24721805FLATG3
50/50
2.718
24723205RIVRG3
Adder
34.305
972203AH1-686 GEN
Adder
4.176
970155AG2-107 GEN
Solar/Wind Harmer
22.284
24735205WLF2G2
Adder
7.594
339241AF1-083 GEN
Solar/Wind Harmer
1.965
943111AE2-339 GEN
Solar/Wind Harmer
1.043
964901AG1-354 GEN
Solar/Wind Harmer
17.632
945681AF1-233 GEN
Solar/Wind Harmer
22.112
24728605AND G2
Adder
4.399
25194608D.CRK4
Adder
1.843
274828WAUKEGAN ;BP
Adder
12.324
274745AC1-111 GEN9
Adder
6.235
274682WAUKEGAN ;7U
Adder
20.049
238185AF2-356 C
Solar/Wind Helper
2.191
241966AE1-183 GEN
Solar/Wind Helper
0.24
238120AE2-309 GEN
Solar/Wind Helper
0.424
23751101LEADS_P59
Solar/Wind Helper
1.865
964201AG1-281 GEN
Solar/Wind Helper
0.457
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.966
238109AE1-109 GEN2
Solar/Wind Helper
0.084
203952AE2-129 C
Solar/Wind Helper
0.445
970281AG2-184 GEN
Solar/Wind Harmer
30.484
962211AG1-066 GEN
Solar/Wind Harmer
3.344
270444AC2-157 GEN1
Solar/Wind Harmer
6.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.747
276763AC1-053 GEN1
Solar/Wind Harmer
4.503
276764AC1-053 GEN2
Solar/Wind Harmer
4.503
276668AB2-070 GEN1
Solar/Wind Harmer
2.521
276848AB2-070 GEN3
Solar/Wind Harmer
2.521
276849AB2-070 GEN2
Solar/Wind Harmer
2.521
970289AG2-191 GEN
Solar/Wind Harmer
2.148
959341AF2-225 GEN
Solar/Wind Harmer
16.948
274744AC1-111 GEN8
Adder
6.235
274735ELWOOD EC;4P
Adder
18.315
241997AF1-093 GEN
Solar/Wind Helper
0.24
24318705GVG2
50/50
11.469
270331AC1-082 GEN3
Solar/Wind Harmer
0.78
971687AH1-348 GEN
Solar/Wind Harmer
1.432
25196008MFTGT1
Adder
1.6
24386605FR-22G C
Solar/Wind Harmer
4.939
276621W2-048 GEN
Solar/Wind Harmer
7.111
25196808ZIMRHP
Adder
86.01
940581AE2-045 GEN
Solar/Wind Harmer
11.524
971605AH1-302 GEN
Solar/Wind Harmer
9.854
939741AE1-205 GEN
Solar/Wind Harmer
22.597
270594AE1-207 GEN
Solar/Wind Harmer
15.305
270032AE2-172
Solar/Wind Harmer
5.241
274761LEE CO EC;2U
Adder
10.407
274773LINCOLN ;4U
Adder
9.41
274774LINCOLN ;5U
Adder
9.41
254303AC2-168 GEN
Solar/Wind Helper
0.149
238126S14_GEN_1
Solar/Wind Helper
0.674
24318705GVG2
50/50
11.469
971191AH1-055 GEN
Solar/Wind Harmer
27.435
972273AH1-721 GEN
Adder
99.65
970093AG2-073 GEN
Solar/Wind Harmer
6.342
270186AC1-089 GEN
Solar/Wind Harmer
7.225
270367AC2-061_GEN
Solar/Wind Harmer
3.742
972167AH1-666 GEN
Solar/Wind Harmer
9.374
25196008MFTGT1
Adder
1.55
942481AE2-261 GEN
Solar/Wind Harmer
34.173
971993AH1-541 GEN
Solar/Wind Harmer
10.521
970879AG2-548 GEN
Solar/Wind Harmer
9.054
965461AG1-414 GEN
Solar/Wind Harmer
2.564
274772LINCOLN ;3U
Adder
9.41
972259AH1-714 GEN
Adder
21.265
274729ELWOOD EC;1P
Adder
18.315
237048AF1-022 C
Solar/Wind Helper
0.194
237046AF1-021 C
Solar/Wind Helper
0.336
971313AH1-133 GEN
Solar/Wind Harmer
8.48
971061AG2-657 GEN
Solar/Wind Harmer
11.954
25196108MFTGT2
Adder
1.764
25196108MFTGT2
Adder
1.638
24387005FR-3G C
Solar/Wind Harmer
4.542
24691005MDL-2G C
Solar/Wind Harmer
4.223
25196408WSDLE3
Adder
9.858
25196308WSDLE2
Adder
9.772
25196208WSDLE1
Adder
9.747
25196708WSDLE6
Adder
9.723
274728ELWOOD EC;5P
Adder
18.315
241985AE1-237 GEN
Solar/Wind Helper
0.233
20089226LOOKOUT
Solar/Wind Helper
0.573
203940AF1-140 C
Solar/Wind Helper
0.376
970107AG2-081 GEN
Solar/Wind Harmer
3.539
339236AF1-050_GEN
Solar/Wind Harmer
2.134
962581AG1-107 GEN
Solar/Wind Harmer
5.847
961491AF2-440 GEN
Solar/Wind Harmer
2.43
970241AG2-163 GEN
Solar/Wind Harmer
28.851
24387305FR-4G C
Solar/Wind Harmer
5.833
276838X2-022 GEN2
Solar/Wind Harmer
0.265
957841AF2-078 GEN
Solar/Wind Harmer
6.888
274880W4-005 GEN4
Solar/Wind Harmer
3.443
276174W4-005 GEN2
Solar/Wind Harmer
3.443
970879AG2-548 GEN
Solar/Wind Harmer
1.316
942111AE2-223 GEN
Solar/Wind Harmer
9.262
274762LEE CO EC;3U
Adder
10.407
274696ROCKY RD ;4P
Adder
12.719
274697ROCKY RD ;3P
Adder
3.375
274770LINCOLN ;1U
Adder
9.41
274771LINCOLN ;2U
Adder
9.41
237043AE2-125 C
Solar/Wind Helper
0.176
23751201ROTHROCK
Solar/Wind Helper
0.737
962101AG1-054 GEN
Solar/Wind Helper
0.612
243186AF1-051 GEN
50/50
12.373
24721705FLATG2
50/50
40.36
24723005RIVRG1
Adder
34.305
24723105RIVRG2
Adder
34.305
971225AH1-072 GEN
Solar/Wind Harmer
2.862
971227AH1-073 GEN
Solar/Wind Harmer
2.862
270214AC2-123 GEN
Solar/Wind Harmer
2.985
971125AH1-004 GEN
Solar/Wind Harmer
4.718
270583AD2-179 GEN
Solar/Wind Harmer
11.79
276916AD2-100_GEN
Solar/Wind Harmer
24.022
24755605MDL-5G
Solar/Wind Harmer
2.754
970291AG2-192 GEN
Solar/Wind Harmer
1.47
970291AG2-192 GEN
Solar/Wind Harmer
0.473
241801AE1-079 GEN
Solar/Wind Helper
0.233
203818AF1-086 GEN
Solar/Wind Helper
1.591
203853AF1-134 C O1
Solar/Wind Helper
0.449
203804AE2-113_GEN
Solar/Wind Helper
1.631
CPLELTFEXP_CPLE->PJM
CLTF
6.634
CBM West 2LTFEXP_CBM-W2->PJM
CBM
151.558
LAGNLTFEXP_LAGN->PJM
CLTF
22.209
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.481
NYPJM->LTFIMP_NY
CLTF
5.206
LGEELTFEXP_LGEE->PJM
CLTF
8.318
TVALTFEXP_TVA->PJM
CLTF
11.344
WECLTFEXP_WEC->PJM
CLTF
4.274
AG2-052LTFEXP_AG2-052->PJM
LTF
0.26
AH1-155LTFEXP_AH1-155->PJM
LTF
0.389
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.12
MECLTFEXP_MEC->PJM
CLTF
18.91
SIGELTFEXP_SIGE->PJM
CLTF
0.622

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5896.19
MW Contribution:
5.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318705GVG2
50/50
11.822
971191AH1-055 GEN
Solar/Wind Harmer
29.317
970879AG2-548 GEN
Solar/Wind Harmer
6.854
972273AH1-721 GEN
Adder
111.17
970093AG2-073 GEN
Solar/Wind Harmer
7.87
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
8.058
25196008MFTGT1
Adder
1.685
253394AE2-221_GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.122
3146802CHATHAM
Solar/Wind Harmer
0.115
942481AE2-261 GEN
Solar/Wind Harmer
24.006
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.664
970825AG2-519 GEN
Solar/Wind Harmer
5.878
970571AG2-364 GEN
Solar/Wind Harmer
15.299
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.443
274850MENDOTA H;RU
Solar/Wind Harmer
0.088
946671AF1-331 GEN
Solar/Wind Harmer
0.811
274729ELWOOD EC;1P
Adder
17.715
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
971313AH1-133 GEN
Solar/Wind Harmer
5.869
971061AG2-657 GEN
Solar/Wind Harmer
6.84
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.421
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
12.311
274856ECOGROVE ;U1
Solar/Wind Harmer
0.178
276861AD2-134 GEN
Solar/Wind Harmer
0.136
276863AD2-134 GEN
Solar/Wind Harmer
0.136
970073AG2-061 GEN
Solar/Wind Harmer
2.528
274728ELWOOD EC;5P
Adder
17.715
20089226LOOKOUT
Solar/Wind Helper
0.556
970879AG2-548 GEN
Solar/Wind Harmer
1.558
970107AG2-081 GEN
Solar/Wind Harmer
2.741
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
4.689
276838X2-022 GEN2
Solar/Wind Harmer
0.448
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.525
276645AC1-214 GEN1
Solar/Wind Harmer
0.302
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.239
274762LEE CO EC;3U
Adder
10.206
938861AE1-114 GEN
Solar/Wind Harmer
4.333
962691AG1-118 GEN
Solar/Wind Harmer
22.733
274696ROCKY RD ;4P
Adder
12.353
274697ROCKY RD ;3P
Adder
3.278
276897AD1-100 C
Solar/Wind Harmer
18.8
276893AG1-478 C
Solar/Wind Harmer
0.501
274888KELLY CRK;1U
Solar/Wind Harmer
0.437
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
971225AH1-072 GEN
Solar/Wind Harmer
2.315
971227AH1-073 GEN
Solar/Wind Harmer
2.315
270583AD2-179 GEN
Solar/Wind Harmer
11.364
971125AH1-004 GEN
Solar/Wind Harmer
3.655
971587AH1-292 GEN
Solar/Wind Harmer
6.363
276916AD2-100_GEN
Solar/Wind Harmer
16.897
970291AG2-192 GEN
Solar/Wind Harmer
1.019
970291AG2-192 GEN
Solar/Wind Harmer
0.47
971613AH1-306 GEN
Solar/Wind Harmer
3.76
253370AE2-315 SEC1
Adder
2.225
247621Y3-024
Adder
0.264
971341AH1-150 GEN
Solar/Wind Harmer
15.232
971343AH1-151 GEN
Solar/Wind Harmer
15.232
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
276901AD2-066 C O1
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.799
316097T157 G90
Solar/Wind Helper
1.102
970281AG2-184 GEN
Solar/Wind Harmer
24.292
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270197AD1-017 GEN1
Solar/Wind Harmer
1.008
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
970289AG2-191 GEN
Solar/Wind Harmer
1.489
959341AF2-225 GEN
Solar/Wind Harmer
8.158
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
274877BISHOP HL;1U
Solar/Wind Harmer
0.257
970169AG2-114 GEN
Solar/Wind Harmer
7.684
276741O09 GEN1
Solar/Wind Harmer
0.271
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
6.042
274735ELWOOD EC;4P
Adder
17.715
243186AF1-051 GEN
50/50
12.754
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24735205WLF2G2
Adder
8.97
945681AF1-233 GEN
Solar/Wind Harmer
17.283
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
964901AG1-354 GEN
Solar/Wind Harmer
13.534
252516AE2-318_GEN
Solar/Wind Harmer
9.728
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.427
24728605AND G2
Adder
4.51
970155AG2-107 GEN
Solar/Wind Harmer
20.471
970613AG2-401 GEN
Solar/Wind Harmer
5.825
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
22.848
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
6.042
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
11.649
270055AF2-134 C O1
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
964201AG1-281 GEN
Solar/Wind Helper
0.442
970941AG2-585 GEN
Solar/Wind Harmer
2.017
24318705GVG2
50/50
11.822
971687AH1-348 GEN
Solar/Wind Harmer
1.157
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252510AF1-249 C
Solar/Wind Harmer
0.065
253398AE2-221_GEN2
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.031
276621W2-048 GEN
Solar/Wind Harmer
0.398
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
8.772
270032AE2-172
Solar/Wind Harmer
5.222
270005AE1-210 C O1
Solar/Wind Harmer
1.692
970825AG2-519 GEN
Solar/Wind Harmer
2.77
939741AE1-205 GEN
Solar/Wind Harmer
10.877
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.607
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.206
970569AG2-363 GEN
Solar/Wind Harmer
22.948
945371AF1-202 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.993
964861AG1-349 GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
3.264
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
24686505CER G6
Adder
16.156
24728305BUCHG2
Adder
7.739
3429241JKCT 3G
Adder
15.659
962761AG1-125 GEN
Solar/Wind Harmer
32.057
965911AG1-460 GEN
Solar/Wind Harmer
1.606
270437AC2-090 C
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.823
270273AD2-016 GEN
Solar/Wind Harmer
0.795
276708O09 GEN2
Solar/Wind Harmer
0.271
274766LEE CO EC;7U
Adder
10.085
939401AE1-172 GEN
Solar/Wind Harmer
5.694
25326309TAIT D
Adder
1.195
962781AG1-127 GEN
Solar/Wind Harmer
7.216
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
24289405MTG1
50/50
11.78
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
18.148
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
3429421JKCT 10G
Adder
10.948
970653AG2-424 GEN
Solar/Wind Harmer
4.351
970149AG2-104 GEN
Solar/Wind Harmer
17.311
970773AG2-487 GEN
Solar/Wind Harmer
1.442
963741AG1-226 GEN
Solar/Wind Harmer
19.023
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.302
970819AG2-516 GEN
Solar/Wind Harmer
9.157
274822ROCKFORD ;11
Adder
21.436
959081AF2-199 GEN
Solar/Wind Harmer
7.616
971067AG2-660 GEN
Solar/Wind Harmer
2.539
276882AE2-255 GEN
Solar/Wind Harmer
0.887
971917AH1-482 GEN
Solar/Wind Harmer
9.865
274872LEEDK;1U
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.228
941551AE2-152 GEN
Solar/Wind Harmer
0
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
28.948
270400AC1-102 GEN
Solar/Wind Harmer
4.065
941621AE2-160 GEN
Adder
5.641
971329AH1-144 GEN
Solar/Wind Harmer
5.625
24734805WLF1G4
Adder
9.154
24735105WLF2G1
Adder
8.97
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
10.231
25196508WSDLE4
Adder
10.442
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.825
270356AE2-297 GEN
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.756
963841AG1-237 GEN
Solar/Wind Harmer
3.459
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
2.987
926823AC1-168 GEN
Solar/Wind Harmer
1.302
274746AC1-111 G10
Adder
6.042
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
23750501ELLIOTTS
Solar/Wind Helper
0.639
238118U2-030_1
Solar/Wind Helper
0.29
20089126CSLMN_L13
Solar/Wind Helper
0.558
20088926STNY CRK
Solar/Wind Helper
0.752
942891AE2-308 GEN
Solar/Wind Harmer
9.244
972043AH1-570 GEN
Solar/Wind Harmer
2.384
971485AH1-239 GEN
Solar/Wind Harmer
7.296
964781AG1-341 GEN
Solar/Wind Harmer
9.518
25194408D.CRK1
Adder
9.34
945391AF1-204 GEN
Solar/Wind Harmer
8.741
942671AE2-283 GEN
Solar/Wind Harmer
3.812
24728905RICHG2
Adder
4.399
276615X2-022 GEN
Solar/Wind Harmer
0.083
926881AC1-175 GEN
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.897
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.602
970883AG2-550 GEN
Solar/Wind Harmer
7.744
270599AE1-208 GEN
Solar/Wind Harmer
7.027
274764LEE CO EC;5U
Adder
10.23
972235AH1-702 GEN1
Adder
2.754
276876AE1-163_GEN2
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274693ROCKY RD ;1P
Adder
11.949
958481AF2-142 GEN
Solar/Wind Harmer
11.337
274674JOLIET 9 ;6U
Adder
16.589
23585401KL_K28_T16
Solar/Wind Helper
1.275
238117U2-030
Solar/Wind Helper
0.29
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
970913AG2-568 GEN
Solar/Wind Harmer
9.827
24728205BUCHG1
Adder
7.739
971277AH1-098 GEN
Solar/Wind Harmer
4.618
971073AG2-665 GEN
Solar/Wind Harmer
6.854
972045AH1-571 GEN
Solar/Wind Harmer
1.91
966021AG1-471 GEN
Solar/Wind Harmer
4.933
964571AG1-320 GEN
Solar/Wind Harmer
8.194
252509AD1-136 GEN
Solar/Wind Harmer
0.044
25183208HLCRTG
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.746
24728805RICHG1
Adder
4.399
276911AD2-131_GEN
Solar/Wind Harmer
1.113
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
970885AG2-551 GEN
Solar/Wind Harmer
2.581
270031AE2-169
Solar/Wind Harmer
4.216
964611AG1-324 GEN
Solar/Wind Harmer
0.575
274765LEE CO EC;6U
Adder
10.23
274763LEE CO EC;4U
Adder
10.109
270201AC2-176 GEN
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.395
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.378
274695ROCKY RD ;2P
Adder
12.068
958011AF2-095 GEN
Solar/Wind Harmer
10.787
235054AD2-180 GEN
Solar/Wind Helper
1.707
235531U2-073 GEN
Solar/Wind Helper
2.776
203961AE2-224 GEN
Solar/Wind Helper
2.204
971461AH1-227 GEN
Solar/Wind Harmer
5.939
270346AE1-212 GEN
Solar/Wind Harmer
10.045
958121AF2-106 GEN
Solar/Wind Harmer
0.001
3429391JKCT 9G
Adder
10.948
958171AF2-111 GEN
Solar/Wind Harmer
22.344
252507AC2-088 GEN
Solar/Wind Harmer
0.399
25196608WSDLE5
Adder
10.55
970193AG2-126 GEN
Solar/Wind Harmer
12.34
24728705AND G3
Adder
9.433
970781AG2-491 GEN
Solar/Wind Harmer
7.832
959611AF2-252 GEN
Solar/Wind Harmer
2.602
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
276868AE1-113 GEN
Solar/Wind Harmer
1.52
274879MINONK ;1U
Solar/Wind Harmer
0.317
274862TOP CROP ;2U
Solar/Wind Harmer
1.021
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
17.715
970707AG2-453 GEN
Solar/Wind Harmer
24.521
274887GEN-1.85
Solar/Wind Harmer
0.195
238127S14_GEN_2
Solar/Wind Helper
0.692
202652Y1-033 WT C
Solar/Wind Helper
0.538
20092526R32
Solar/Wind Helper
1.061
24289405MTG1
50/50
11.78
24686405CER G5
Adder
16.028
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970653AG2-424 GEN
Solar/Wind Harmer
0.902
941801AE2-185 GEN
Solar/Wind Harmer
4.901
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.692
965091AG1-374 GEN
Solar/Wind Harmer
23.422
965931AG1-462 GEN
Solar/Wind Harmer
19.72
274878BISHOP HL;2U
Solar/Wind Harmer
0.257
970191AG2-125 GEN
Solar/Wind Harmer
1.979
274760LEE CO EC;1U
Adder
10.206
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.242
23562501BACKB
Solar/Wind Helper
0.87
238108AE1-109 GEN1
Solar/Wind Helper
0.089
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
960911AF2-382 GEN
Solar/Wind Harmer
8.992
943031AE2-326 GEN
Solar/Wind Harmer
6.089
972103AH1-617 GEN
Solar/Wind Harmer
23.135
270030AE2-140 GEN
Solar/Wind Harmer
18.672
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
10.955
24728505AND G1
Adder
4.51
962771AG1-126 GEN
Solar/Wind Harmer
32.057
970153AG2-106 GEN
Solar/Wind Harmer
20.471
957381AF2-032 GEN
Solar/Wind Harmer
1.818
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.862
946031AF1-268 GEN
Solar/Wind Harmer
7.4
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
971087AG2-675 GEN
Solar/Wind Harmer
4.124
3147123OTTER R
Solar/Wind Harmer
0.087
274767LEE CO EC;8U
Adder
10.085
959091AF2-200 GEN
Solar/Wind Harmer
15.232
274682WAUKEGAN ;7U
Adder
19.478
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.409
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
270399AC1-101 GEN
Solar/Wind Harmer
4.065
966391AG1-508 GEN
Solar/Wind Harmer
1.796
971331AH1-145 GEN
Solar/Wind Harmer
15.307
24734705WLF1G3
Adder
9.154
24734905WLF1G5
Adder
9.154
971985AH1-537 GEN
Solar/Wind Harmer
3.035
971981AH1-535 GEN
Solar/Wind Harmer
6.584
270069AE2-166 C O1
Solar/Wind Harmer
8.709
972165AH1-665 GEN
Solar/Wind Harmer
8.194
339216AC1-074 GEN
Solar/Wind Harmer
0.242
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.618
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.702
946321AF1-296 GEN
Solar/Wind Harmer
4.325
247536S-71 GEN
Solar/Wind Harmer
0.307
971611AH1-305 GEN
Solar/Wind Harmer
4.575
972267AH1-718 GEN
Adder
4.579
959141AF2-205 GEN
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
21.28
971171AH1-044 GEN
Solar/Wind Harmer
15.232
945581AF1-223 GEN
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.966
971411AH1-196 GEN
Solar/Wind Harmer
11.402
970833AG2-524 GEN
Solar/Wind Harmer
8.285
970833AG2-524 GEN
Solar/Wind Harmer
5.523
274675JOLIET 29;7U
Adder
33.032
960591AF2-350 GEN
Solar/Wind Harmer
7.491
23750701CROSSCHOOL
Solar/Wind Helper
1.205
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
276806AD2-047 C O1
Solar/Wind Harmer
4.245
964991AG1-363 GEN
Solar/Wind Helper
3.731
238110AE1-109 GEN3
Solar/Wind Helper
0.089
235058AG1-386 C
Solar/Wind Helper
0.381
203940AF1-140 C
Solar/Wind Helper
0.362
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
TVALTFEXP_TVA->PJM
CLTF
12.601
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.86 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5846.6
MW Contribution:
9.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
2.66
24721905FLATG4
50/50
48.595
960911AF2-382 GEN
Solar/Wind Harmer
11.685
972103AH1-617 GEN
Solar/Wind Harmer
30.771
943031AE2-326 GEN
Solar/Wind Harmer
5.037
252519AF1-045_GEN
Solar/Wind Harmer
4.153
25194608D.CRK4
Adder
1.856
252524AE2-267 GEN
Solar/Wind Harmer
1.77
270030AE2-140 GEN
Solar/Wind Harmer
21.915
253317AC1-085 GEN4
Solar/Wind Harmer
9.117
946181AF1-283 GEN
Solar/Wind Harmer
14.157
24728505AND G1
Adder
4.021
957381AF2-032 GEN
Solar/Wind Harmer
2.028
962771AG1-126 GEN
Solar/Wind Harmer
32.808
970153AG2-106 GEN
Solar/Wind Harmer
14.306
276785W4-005 GEN1
Solar/Wind Harmer
3.022
247642Z2-115 C
Solar/Wind Harmer
0.063
970289AG2-191 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274767LEE CO EC;8U
Adder
8.766
274682WAUKEGAN ;7U
Adder
16.869
274734ELWOOD EC;8P
Adder
15.317
274736ELWOOD EC;9P
Adder
15.317
235058AG1-386 C
Solar/Wind Helper
0.455
964991AG1-363 GEN
Solar/Wind Helper
3.486
20303426NA_O38_P22
Solar/Wind Helper
0.926
203993AD2-133_GEN1
Solar/Wind Helper
0.956
270330AC1-082 GEN2
Solar/Wind Harmer
0.934
957541AF2-048 GEN
Solar/Wind Harmer
2.439
971461AH1-227 GEN
Solar/Wind Harmer
7.779
270346AE1-212 GEN
Solar/Wind Harmer
13.204
958121AF2-106 GEN
Solar/Wind Harmer
5.826
3429391JKCT 9G
Adder
9.999
252507AC2-088 GEN
Solar/Wind Harmer
2.108
958171AF2-111 GEN
Solar/Wind Harmer
29.368
25196608WSDLE5
Adder
9.632
970193AG2-126 GEN
Solar/Wind Harmer
15.734
24728705AND G3
Adder
8.411
274730ELWOOD EC;6P
Adder
15.317
202652Y1-033 WT C
Solar/Wind Helper
0.537
20092526R32
Solar/Wind Helper
1.091
238127S14_GEN_2
Solar/Wind Helper
0.645
270399AC1-101 GEN
Solar/Wind Harmer
7.458
971985AH1-537 GEN
Solar/Wind Harmer
26.806
24734705WLF1G3
Adder
8.136
24734905WLF1G5
Adder
8.136
966391AG1-508 GEN
Solar/Wind Harmer
4.767
971331AH1-145 GEN
Solar/Wind Harmer
12.423
971981AH1-535 GEN
Solar/Wind Harmer
12.575
972165AH1-665 GEN
Solar/Wind Harmer
9.725
270291AC1-194 GEN
Solar/Wind Harmer
6.12
339216AC1-074 GEN
Solar/Wind Harmer
2.003
270069AE2-166 C O1
Solar/Wind Harmer
10.085
253406AD2-031_GEN
Solar/Wind Harmer
1.368
24386405FR-21G C
Solar/Wind Harmer
4.297
972267AH1-718 GEN
Adder
3.983
274823ROCKFORD ;21
Adder
18.472
274675JOLIET 29;7U
Adder
28.551
23652301WDPWR_K20
Solar/Wind Helper
0.14
203955AF1-039 C O1
Solar/Wind Helper
0.355
23750701CROSSCHOOL
Solar/Wind Helper
1.137
203846AF2-130 C
Solar/Wind Helper
0.428
942891AE2-308 GEN
Solar/Wind Harmer
12.112
972043AH1-570 GEN
Solar/Wind Harmer
3.018
971485AH1-239 GEN
Solar/Wind Harmer
9.429
964781AG1-341 GEN
Solar/Wind Harmer
12.309
25194408D.CRK1
Adder
8.538
945391AF1-204 GEN
Solar/Wind Harmer
14.618
24728905RICHG2
Adder
3.92
253415AE1-040 GEN
Solar/Wind Harmer
1.157
926881AC1-175 GEN
Solar/Wind Harmer
5.627
276615X2-022 GEN
Solar/Wind Harmer
1.968
24725505WLD G2 C
Solar/Wind Harmer
3.981
966841AG1-555 GEN
Solar/Wind Harmer
2.508
274764LEE CO EC;5U
Adder
8.891
972235AH1-702 GEN1
Adder
2.391
274683WAUKEGAN ;8U
Adder
19.789
274683WAUKEGAN ;8U
Adder
16.681
274693ROCKY RD ;1P
Adder
10.349
274674JOLIET 9 ;6U
Adder
14.342
254305AE2-115 C
Solar/Wind Helper
0.213
241967AE2-285_GEN
Solar/Wind Helper
0.617
23585401KL_K28_T16
Solar/Wind Helper
1.231
946071AF1-272 GEN
Solar/Wind Helper
2.555
238117U2-030
Solar/Wind Helper
0.274
20083426SW_E13_K22
Solar/Wind Helper
0.053
20088826HIGHLAND
Solar/Wind Helper
0.842
24686505CER G6
Adder
16.193
24728305BUCHG2
Adder
6.959
3429241JKCT 3G
Adder
14.309
339211AE2-254 GEN
Solar/Wind Harmer
1.818
944031AF1-071 GEN
Solar/Wind Harmer
1.049
965911AG1-460 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
32.808
270437AC2-090 C
Solar/Wind Harmer
5.627
24385905FR-11G C
Solar/Wind Harmer
8.303
276903AD2-071 C
Solar/Wind Harmer
9.98
274766LEE CO EC;7U
Adder
8.766
25326309TAIT D
Adder
1.032
274732ELWOOD EC;7P
Adder
15.317
24721605FLATG1
50/50
2.66
957241AF2-018 GEN
Solar/Wind Harmer
7.904
270053AF1-130 C
Solar/Wind Harmer
31.582
270400AC1-102 GEN
Solar/Wind Harmer
7.458
941621AE2-160 GEN
Adder
5.547
24734805WLF1G4
Adder
8.136
24735105WLF2G1
Adder
7.967
971329AH1-144 GEN
Solar/Wind Harmer
7.935
972163AH1-664 GEN
Solar/Wind Harmer
12.156
3429211JKCT 2G
Adder
14.123
25196508WSDLE4
Adder
9.533
270340AC2-060 GEN
Solar/Wind Harmer
3.206
270263AC1-001 GEN
Solar/Wind Harmer
1.104
270356AE2-297 GEN
Solar/Wind Harmer
4.818
944221AF1-090 GEN
Solar/Wind Harmer
11.234
963841AG1-237 GEN
Solar/Wind Harmer
11.024
274746AC1-111 G10
Adder
5.228
274731ELWOOD EC;2P
Adder
15.317
274733ELWOOD EC;3P
Adder
15.317
23750501ELLIOTTS
Solar/Wind Helper
0.647
241982AE2-343 S C
Solar/Wind Helper
0.216
20089126CSLMN_L13
Solar/Wind Helper
0.564
238118U2-030_1
Solar/Wind Helper
0.274
20088926STNY CRK
Solar/Wind Helper
0.77
20094526CT_V3-030
Solar/Wind Helper
0.443
20088626ARWF_N39
Solar/Wind Helper
1.129
946581AF1-322 GEN
Solar/Wind Harmer
3.68
970913AG2-568 GEN
Solar/Wind Harmer
11.393
24728205BUCHG1
Adder
6.959
927014AC1-188 GEN
Solar/Wind Harmer
2.439
971277AH1-098 GEN
Solar/Wind Harmer
5.471
971073AG2-665 GEN
Solar/Wind Harmer
10.456
972045AH1-571 GEN
Solar/Wind Harmer
2.414
339231AF1-038_GEN
Solar/Wind Harmer
2.155
966021AG1-471 GEN
Solar/Wind Harmer
6.374
252509AD1-136 GEN
Solar/Wind Harmer
0.301
964571AG1-320 GEN
Solar/Wind Harmer
9.57
25183208HLCRTG
Solar/Wind Harmer
6.902
25194508D.CRK3
Adder
1.596
24728805RICHG1
Adder
3.92
276911AD2-131_GEN
Solar/Wind Harmer
4.32
24699105WLD G1 C
Solar/Wind Harmer
3.935
270383AD1-128 GEN
Solar/Wind Harmer
6.1
270180AB1-006 GEN1
Solar/Wind Harmer
7.075
274765LEE CO EC;6U
Adder
8.891
274763LEE CO EC;4U
Adder
8.787
972236AH1-702 GEN2
Adder
2.08
274695ROCKY RD ;2P
Adder
10.452
254304AE2-114 C
Solar/Wind Helper
0.213
235054AD2-180 GEN
Solar/Wind Helper
1.627
235531U2-073 GEN
Solar/Wind Helper
2.597
203961AE2-224 GEN
Solar/Wind Helper
2.25
946381AF1-302 GEN
Solar/Wind Helper
0.208
203946AE2-131 C
Solar/Wind Helper
0.441
24289405MTG1
50/50
11.749
960001AF2-291 GEN
Solar/Wind Harmer
6.049
944971AF1-162 GEN
Solar/Wind Harmer
12.449
971403AH1-188 GEN
Solar/Wind Harmer
24.722
971073AG2-665 GEN
Solar/Wind Harmer
1.52
970091AG2-072 GEN
Adder
94.28
339221AD2-048_GEN
Solar/Wind Harmer
1.847
3429421JKCT 10G
Adder
9.999
970653AG2-424 GEN
Solar/Wind Harmer
5.656
270222AC2-111 GEN
Solar/Wind Harmer
4.662
963741AG1-226 GEN
Solar/Wind Harmer
45.799
970149AG2-104 GEN
Solar/Wind Harmer
20.259
276686W4-005 GEN3
Solar/Wind Harmer
3.022
274822ROCKFORD ;11
Adder
18.607
24289405MTG1
50/50
11.749
270329AC1-082 GEN1
Solar/Wind Harmer
0.934
24686405CER G5
Adder
16.065
339243AC2-075 GEN1
Solar/Wind Harmer
0.542
339206AE1-143 GEN
Solar/Wind Harmer
2.528
970455AG2-298 GEN
Solar/Wind Harmer
4.124
970653AG2-424 GEN
Solar/Wind Harmer
0.818
339255AE2-071 GEN
Solar/Wind Harmer
1.366
339250AF1-203 GEN
Solar/Wind Harmer
0.703
24379505HDWTR1G C
Solar/Wind Harmer
7.972
243186AF1-051 GEN
50/50
12.616
24721805FLATG3
50/50
2.66
24723205RIVRG3
Adder
36.981
972203AH1-686 GEN
Adder
4.427
24735205WLF2G2
Adder
7.967
945681AF1-233 GEN
Solar/Wind Harmer
22.855
943111AE2-339 GEN
Solar/Wind Harmer
1.059
339241AF1-083 GEN
Solar/Wind Harmer
1.958
964901AG1-354 GEN
Solar/Wind Harmer
17.533
252516AE2-318_GEN
Solar/Wind Harmer
11.412
25194608D.CRK4
Adder
1.856
270336AE1-100 GEN
Solar/Wind Harmer
1.934
253316AC1-085 GEN3
Solar/Wind Harmer
9.117
946171AF1-282 GEN
Solar/Wind Harmer
10.89
943811AF1-049 GEN
Solar/Wind Harmer
4.052
24728605AND G2
Adder
4.021
970155AG2-107 GEN
Solar/Wind Harmer
14.306
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274828WAUKEGAN ;BP
Adder
10.373
274682WAUKEGAN ;7U
Adder
16.869
274745AC1-111 GEN9
Adder
5.228
274676JOLIET 29;8U
Adder
10.069
241966AE1-183 GEN
Solar/Wind Helper
0.247
238185AF2-356 C
Solar/Wind Helper
2.102
964201AG1-281 GEN
Solar/Wind Helper
0.452
20091526CHSTN_FL
Solar/Wind Helper
0.544
238120AE2-309 GEN
Solar/Wind Helper
0.406
20090526Q36
Solar/Wind Helper
0.956
203952AE2-129 C
Solar/Wind Helper
0.441
970281AG2-184 GEN
Solar/Wind Harmer
32.31
962211AG1-066 GEN
Solar/Wind Harmer
3.513
270444AC2-157 GEN1
Solar/Wind Harmer
6.262
270445AC2-157 GEN2
Solar/Wind Harmer
6.262
253433AC1-085 GEN1
Solar/Wind Harmer
5.787
253432AC1-085 GEN2
Solar/Wind Harmer
0.291
276763AC1-053 GEN1
Solar/Wind Harmer
3.957
276764AC1-053 GEN2
Solar/Wind Harmer
3.957
276668AB2-070 GEN1
Solar/Wind Harmer
2.213
276848AB2-070 GEN3
Solar/Wind Harmer
2.213
276849AB2-070 GEN2
Solar/Wind Harmer
2.213
970289AG2-191 GEN
Solar/Wind Harmer
1.875
25306009OHH W.
Adder
2.793
253372AE2-315 SEC3
Adder
1.832
253372AE2-315 SEC3
Adder
1.832
274744AC1-111 GEN8
Adder
5.228
274735ELWOOD EC;4P
Adder
15.317
241997AF1-093 GEN
Solar/Wind Helper
0.247
24318705GVG2
50/50
11.694
270331AC1-082 GEN3
Solar/Wind Harmer
0.937
971687AH1-348 GEN
Solar/Wind Harmer
1.517
25196808ZIMRHP
Adder
87.559
25196008MFTGT1
Adder
1.593
252510AF1-249 C
Solar/Wind Harmer
0.473
253398AE2-221_GEN2
Solar/Wind Harmer
4.748
942081AE2-220 GEN
Solar/Wind Harmer
6.447
270209AC1-174_GEN
Solar/Wind Harmer
4.103
270239V3-007_GEN1
Solar/Wind Harmer
1.735
276621W2-048 GEN
Solar/Wind Harmer
6.266
24386605FR-22G C
Solar/Wind Harmer
4.297
270594AE1-207 GEN
Solar/Wind Harmer
13.398
270032AE2-172
Solar/Wind Harmer
4.588
270005AE1-210 C O1
Solar/Wind Harmer
5.379
274761LEE CO EC;2U
Adder
8.871
254303AC2-168 GEN
Solar/Wind Helper
0.154
238126S14_GEN_1
Solar/Wind Helper
0.645
24318705GVG2
50/50
11.694
971191AH1-055 GEN
Solar/Wind Harmer
33.049
970879AG2-548 GEN
Solar/Wind Harmer
10.456
270186AC1-089 GEN
Solar/Wind Harmer
7.579
270367AC2-061_GEN
Solar/Wind Harmer
3.93
970093AG2-073 GEN
Solar/Wind Harmer
6.439
972167AH1-666 GEN
Solar/Wind Harmer
9.688
972273AH1-721 GEN
Adder
100.618
25196008MFTGT1
Adder
1.543
253394AE2-221_GEN
Solar/Wind Harmer
4.748
942481AE2-261 GEN
Solar/Wind Harmer
30.351
270240V3-007_GEN2
Solar/Wind Harmer
6.237
971993AH1-541 GEN
Solar/Wind Harmer
9.233
965461AG1-414 GEN
Solar/Wind Harmer
2.238
274729ELWOOD EC;1P
Adder
15.317
237048AF1-022 C
Solar/Wind Helper
0.19
237046AF1-021 C
Solar/Wind Helper
0.331
971313AH1-133 GEN
Solar/Wind Harmer
9.046
971061AG2-657 GEN
Solar/Wind Harmer
13.699
25196108MFTGT2
Adder
1.756
25196108MFTGT2
Adder
1.631
25196408WSDLE3
Adder
9.915
25196308WSDLE2
Adder
9.829
25196208WSDLE1
Adder
9.804
25196708WSDLE6
Adder
9.779
24387005FR-3G C
Solar/Wind Harmer
3.952
274728ELWOOD EC;5P
Adder
15.317
241985AE1-237 GEN
Solar/Wind Helper
0.241
20089226LOOKOUT
Solar/Wind Helper
0.562
203940AF1-140 C
Solar/Wind Helper
0.371
970879AG2-548 GEN
Solar/Wind Harmer
1.52
962581AG1-107 GEN
Solar/Wind Harmer
6.12
961491AF2-440 GEN
Solar/Wind Harmer
2.543
970107AG2-081 GEN
Solar/Wind Harmer
3.595
339236AF1-050_GEN
Solar/Wind Harmer
2.122
970241AG2-163 GEN
Solar/Wind Harmer
25.444
276838X2-022 GEN2
Solar/Wind Harmer
0.234
274880W4-005 GEN4
Solar/Wind Harmer
3.022
276174W4-005 GEN2
Solar/Wind Harmer
3.022
24387305FR-4G C
Solar/Wind Harmer
5.075
243186AF1-051 GEN
50/50
12.616
24721705FLATG2
50/50
39.51
24723005RIVRG1
Adder
36.981
24723105RIVRG2
Adder
36.981
971225AH1-072 GEN
Solar/Wind Harmer
3.033
971227AH1-073 GEN
Solar/Wind Harmer
3.033
270214AC2-123 GEN
Solar/Wind Harmer
3.2
270583AD2-179 GEN
Solar/Wind Harmer
12.855
971125AH1-004 GEN
Solar/Wind Harmer
4.793
276916AD2-100_GEN
Solar/Wind Harmer
21.377
970291AG2-192 GEN
Solar/Wind Harmer
1.283
970291AG2-192 GEN
Solar/Wind Harmer
0.413
253370AE2-315 SEC1
Adder
1.937
247621Y3-024
Adder
0.23
25322209TAIT E
Adder
9.19
25322209TAIT E
Adder
8.984
241801AE1-079 GEN
Solar/Wind Helper
0.241
203818AF1-086 GEN
Solar/Wind Helper
1.582
203853AF1-134 C O1
Solar/Wind Helper
0.446
203804AE2-113_GEN
Solar/Wind Helper
1.63
274674JOLIET 9 ;6U
Adder
14.342
20089026BF_G21_K23
Solar/Wind Helper
0.446
20084626FORWARD
Solar/Wind Helper
0.335
274762LEE CO EC;3U
Adder
8.871
274696ROCKY RD ;4P
Adder
10.699
274697ROCKY RD ;3P
Adder
2.839
237043AE2-125 C
Solar/Wind Helper
0.175
962101AG1-054 GEN
Solar/Wind Helper
0.63
23751201ROTHROCK
Solar/Wind Helper
0.704
24386205FR-12G C
Solar/Wind Harmer
4.281
270004AE1-209 GEN
Solar/Wind Harmer
5.379
24690905MDL-1G C
Solar/Wind Harmer
7.897
274760LEE CO EC;1U
Adder
8.871
23562501BACKB
Solar/Wind Helper
0.856
CPLELTFEXP_CPLE->PJM
CLTF
7.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
143.77
LAGNLTFEXP_LAGN->PJM
CLTF
21.601
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.934
NYPJM->LTFIMP_NY
CLTF
5.068
LGEELTFEXP_LGEE->PJM
CLTF
8.183
TVALTFEXP_TVA->PJM
CLTF
11.244
WECLTFEXP_WEC->PJM
CLTF
3.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.218
AH1-155LTFEXP_AH1-155->PJM
LTF
0.328
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.677
MECLTFEXP_MEC->PJM
CLTF
16.745
SIGELTFEXP_SIGE->PJM
CLTF
0.592

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.88 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5626.94
MW Contribution:
9.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
2.675
24721905FLATG4
50/50
48.862
960911AF2-382 GEN
Solar/Wind Harmer
11.778
972103AH1-617 GEN
Solar/Wind Harmer
31.019
943031AE2-326 GEN
Solar/Wind Harmer
5.082
252519AF1-045_GEN
Solar/Wind Harmer
4.199
25194608D.CRK4
Adder
1.876
252524AE2-267 GEN
Solar/Wind Harmer
1.789
270030AE2-140 GEN
Solar/Wind Harmer
22.165
253317AC1-085 GEN4
Solar/Wind Harmer
9.221
946181AF1-283 GEN
Solar/Wind Harmer
14.318
24728505AND G1
Adder
4.069
957381AF2-032 GEN
Solar/Wind Harmer
2.053
962771AG1-126 GEN
Solar/Wind Harmer
33.21
970153AG2-106 GEN
Solar/Wind Harmer
14.481
276785W4-005 GEN1
Solar/Wind Harmer
3.059
247642Z2-115 C
Solar/Wind Harmer
0.064
970289AG2-191 GEN
Solar/Wind Harmer
0.767
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274767LEE CO EC;8U
Adder
8.88
274682WAUKEGAN ;7U
Adder
17.092
274734ELWOOD EC;8P
Adder
15.521
274736ELWOOD EC;9P
Adder
15.521
235058AG1-386 C
Solar/Wind Helper
0.45
964991AG1-363 GEN
Solar/Wind Helper
3.438
20303426NA_O38_P22
Solar/Wind Helper
0.913
270330AC1-082 GEN2
Solar/Wind Harmer
0.94
957541AF2-048 GEN
Solar/Wind Harmer
2.459
971461AH1-227 GEN
Solar/Wind Harmer
7.843
270346AE1-212 GEN
Solar/Wind Harmer
13.316
958121AF2-106 GEN
Solar/Wind Harmer
5.883
3429391JKCT 9G
Adder
10.103
252507AC2-088 GEN
Solar/Wind Harmer
2.13
958171AF2-111 GEN
Solar/Wind Harmer
29.678
25196608WSDLE5
Adder
9.738
970193AG2-126 GEN
Solar/Wind Harmer
15.92
24728705AND G3
Adder
8.51
274730ELWOOD EC;6P
Adder
15.521
202652Y1-033 WT C
Solar/Wind Helper
0.53
20092526R32
Solar/Wind Helper
1.076
238127S14_GEN_2
Solar/Wind Helper
0.636
270399AC1-101 GEN
Solar/Wind Harmer
7.511
971985AH1-537 GEN
Solar/Wind Harmer
27.028
24734705WLF1G3
Adder
8.207
24734905WLF1G5
Adder
8.207
966391AG1-508 GEN
Solar/Wind Harmer
4.81
971331AH1-145 GEN
Solar/Wind Harmer
12.539
971981AH1-535 GEN
Solar/Wind Harmer
12.699
972165AH1-665 GEN
Solar/Wind Harmer
9.824
270291AC1-194 GEN
Solar/Wind Harmer
6.183
339216AC1-074 GEN
Solar/Wind Harmer
2.024
270069AE2-166 C O1
Solar/Wind Harmer
10.196
253406AD2-031_GEN
Solar/Wind Harmer
1.384
24386405FR-21G C
Solar/Wind Harmer
4.35
972267AH1-718 GEN
Adder
4.035
274823ROCKFORD ;21
Adder
18.714
274675JOLIET 29;7U
Adder
28.931
23652301WDPWR_K20
Solar/Wind Helper
0.139
203955AF1-039 C O1
Solar/Wind Helper
0.35
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203846AF2-130 C
Solar/Wind Helper
0.422
942891AE2-308 GEN
Solar/Wind Harmer
12.236
972043AH1-570 GEN
Solar/Wind Harmer
3.049
971485AH1-239 GEN
Solar/Wind Harmer
9.528
964781AG1-341 GEN
Solar/Wind Harmer
12.441
25194408D.CRK1
Adder
8.632
945391AF1-204 GEN
Solar/Wind Harmer
14.791
24728905RICHG2
Adder
3.967
253415AE1-040 GEN
Solar/Wind Harmer
1.171
926881AC1-175 GEN
Solar/Wind Harmer
5.696
276615X2-022 GEN
Solar/Wind Harmer
1.992
24725505WLD G2 C
Solar/Wind Harmer
4.03
966841AG1-555 GEN
Solar/Wind Harmer
2.539
274764LEE CO EC;5U
Adder
9.007
972235AH1-702 GEN1
Adder
2.423
274683WAUKEGAN ;8U
Adder
20.05
274683WAUKEGAN ;8U
Adder
16.901
274693ROCKY RD ;1P
Adder
10.485
274674JOLIET 9 ;6U
Adder
14.533
254305AE2-115 C
Solar/Wind Helper
0.21
241967AE2-285_GEN
Solar/Wind Helper
0.609
23585401KL_K28_T16
Solar/Wind Helper
1.215
946071AF1-272 GEN
Solar/Wind Helper
2.52
238117U2-030
Solar/Wind Helper
0.27
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.83
24721605FLATG1
50/50
2.675
957241AF2-018 GEN
Solar/Wind Harmer
7.959
270053AF1-130 C
Solar/Wind Harmer
31.802
270400AC1-102 GEN
Solar/Wind Harmer
7.511
941621AE2-160 GEN
Adder
5.587
24734805WLF1G4
Adder
8.207
24735105WLF2G1
Adder
8.038
971329AH1-144 GEN
Solar/Wind Harmer
8.009
972163AH1-664 GEN
Solar/Wind Harmer
12.28
3429211JKCT 2G
Adder
14.268
25196508WSDLE4
Adder
9.638
270340AC2-060 GEN
Solar/Wind Harmer
3.244
270263AC1-001 GEN
Solar/Wind Harmer
1.117
270356AE2-297 GEN
Solar/Wind Harmer
4.876
944221AF1-090 GEN
Solar/Wind Harmer
11.369
963841AG1-237 GEN
Solar/Wind Harmer
11.16
274746AC1-111 G10
Adder
5.298
274731ELWOOD EC;2P
Adder
15.521
274733ELWOOD EC;3P
Adder
15.521
23750501ELLIOTTS
Solar/Wind Helper
0.639
241982AE2-343 S C
Solar/Wind Helper
0.214
20089126CSLMN_L13
Solar/Wind Helper
0.556
238118U2-030_1
Solar/Wind Helper
0.27
20088926STNY CRK
Solar/Wind Helper
0.759
20094526CT_V3-030
Solar/Wind Helper
0.437
20088626ARWF_N39
Solar/Wind Helper
1.113
946581AF1-322 GEN
Solar/Wind Harmer
3.726
970913AG2-568 GEN
Solar/Wind Harmer
11.477
24728205BUCHG1
Adder
7.015
927014AC1-188 GEN
Solar/Wind Harmer
2.459
971277AH1-098 GEN
Solar/Wind Harmer
5.52
971073AG2-665 GEN
Solar/Wind Harmer
10.556
972045AH1-571 GEN
Solar/Wind Harmer
2.439
339231AF1-038_GEN
Solar/Wind Harmer
2.178
966021AG1-471 GEN
Solar/Wind Harmer
6.442
252509AD1-136 GEN
Solar/Wind Harmer
0.304
964571AG1-320 GEN
Solar/Wind Harmer
9.672
25183208HLCRTG
Solar/Wind Harmer
6.977
25194508D.CRK3
Adder
1.614
24728805RICHG1
Adder
3.967
276911AD2-131_GEN
Solar/Wind Harmer
4.373
24699105WLD G1 C
Solar/Wind Harmer
3.983
270383AD1-128 GEN
Solar/Wind Harmer
6.175
270180AB1-006 GEN1
Solar/Wind Harmer
7.164
274765LEE CO EC;6U
Adder
9.007
274763LEE CO EC;4U
Adder
8.901
972236AH1-702 GEN2
Adder
2.107
274695ROCKY RD ;2P
Adder
10.59
254304AE2-114 C
Solar/Wind Helper
0.21
235054AD2-180 GEN
Solar/Wind Helper
1.606
235531U2-073 GEN
Solar/Wind Helper
2.561
203961AE2-224 GEN
Solar/Wind Helper
2.218
946381AF1-302 GEN
Solar/Wind Helper
0.205
24289405MTG1
50/50
11.803
960001AF2-291 GEN
Solar/Wind Harmer
6.087
944971AF1-162 GEN
Solar/Wind Harmer
12.535
971403AH1-188 GEN
Solar/Wind Harmer
24.896
971073AG2-665 GEN
Solar/Wind Harmer
1.534
970091AG2-072 GEN
Adder
95.233
339221AD2-048_GEN
Solar/Wind Harmer
1.866
3429421JKCT 10G
Adder
10.103
970653AG2-424 GEN
Solar/Wind Harmer
5.716
270222AC2-111 GEN
Solar/Wind Harmer
4.717
963741AG1-226 GEN
Solar/Wind Harmer
46.357
970149AG2-104 GEN
Solar/Wind Harmer
20.507
276686W4-005 GEN3
Solar/Wind Harmer
3.059
274822ROCKFORD ;11
Adder
18.851
243186AF1-051 GEN
50/50
12.678
24721805FLATG3
50/50
2.675
24723205RIVRG3
Adder
37.214
972203AH1-686 GEN
Adder
4.456
24735205WLF2G2
Adder
8.038
945681AF1-233 GEN
Solar/Wind Harmer
23.089
943111AE2-339 GEN
Solar/Wind Harmer
1.07
339241AF1-083 GEN
Solar/Wind Harmer
1.979
964901AG1-354 GEN
Solar/Wind Harmer
17.72
252516AE2-318_GEN
Solar/Wind Harmer
11.536
25194608D.CRK4
Adder
1.876
270336AE1-100 GEN
Solar/Wind Harmer
1.956
253316AC1-085 GEN3
Solar/Wind Harmer
9.221
946171AF1-282 GEN
Solar/Wind Harmer
11.014
943811AF1-049 GEN
Solar/Wind Harmer
4.099
24728605AND G2
Adder
4.069
970155AG2-107 GEN
Solar/Wind Harmer
14.481
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274828WAUKEGAN ;BP
Adder
10.51
274682WAUKEGAN ;7U
Adder
17.092
274745AC1-111 GEN9
Adder
5.298
274676JOLIET 29;8U
Adder
10.203
241966AE1-183 GEN
Solar/Wind Helper
0.244
238185AF2-356 C
Solar/Wind Helper
2.074
964201AG1-281 GEN
Solar/Wind Helper
0.445
20091526CHSTN_FL
Solar/Wind Helper
0.536
238120AE2-309 GEN
Solar/Wind Helper
0.4
970281AG2-184 GEN
Solar/Wind Harmer
32.57
962211AG1-066 GEN
Solar/Wind Harmer
3.543
270444AC2-157 GEN1
Solar/Wind Harmer
6.331
270445AC2-157 GEN2
Solar/Wind Harmer
6.331
253433AC1-085 GEN1
Solar/Wind Harmer
5.853
253432AC1-085 GEN2
Solar/Wind Harmer
0.295
24318705GVG2
50/50
11.752
270331AC1-082 GEN3
Solar/Wind Harmer
0.942
971687AH1-348 GEN
Solar/Wind Harmer
1.53
25196808ZIMRHP
Adder
88.501
25196008MFTGT1
Adder
1.61
252510AF1-249 C
Solar/Wind Harmer
0.479
253398AE2-221_GEN2
Solar/Wind Harmer
4.804
942081AE2-220 GEN
Solar/Wind Harmer
6.527
270209AC1-174_GEN
Solar/Wind Harmer
4.153
270239V3-007_GEN1
Solar/Wind Harmer
1.756
276621W2-048 GEN
Solar/Wind Harmer
6.343
24386605FR-22G C
Solar/Wind Harmer
4.35
270594AE1-207 GEN
Solar/Wind Harmer
13.567
270032AE2-172
Solar/Wind Harmer
4.646
270005AE1-210 C O1
Solar/Wind Harmer
5.447
274761LEE CO EC;2U
Adder
8.986
254303AC2-168 GEN
Solar/Wind Helper
0.152
238126S14_GEN_1
Solar/Wind Helper
0.636
24318705GVG2
50/50
11.752
971191AH1-055 GEN
Solar/Wind Harmer
33.281
970879AG2-548 GEN
Solar/Wind Harmer
10.556
270186AC1-089 GEN
Solar/Wind Harmer
7.655
270367AC2-061_GEN
Solar/Wind Harmer
3.969
970093AG2-073 GEN
Solar/Wind Harmer
6.505
972167AH1-666 GEN
Solar/Wind Harmer
9.788
972273AH1-721 GEN
Adder
101.651
25196008MFTGT1
Adder
1.56
253394AE2-221_GEN
Solar/Wind Harmer
4.804
942481AE2-261 GEN
Solar/Wind Harmer
30.722
270240V3-007_GEN2
Solar/Wind Harmer
6.314
971993AH1-541 GEN
Solar/Wind Harmer
9.348
965461AG1-414 GEN
Solar/Wind Harmer
2.266
274729ELWOOD EC;1P
Adder
15.521
237048AF1-022 C
Solar/Wind Helper
0.188
237046AF1-021 C
Solar/Wind Helper
0.327
971313AH1-133 GEN
Solar/Wind Harmer
9.12
971061AG2-657 GEN
Solar/Wind Harmer
13.811
25196108MFTGT2
Adder
1.775
25196108MFTGT2
Adder
1.648
25196408WSDLE3
Adder
10.024
25196308WSDLE2
Adder
9.937
25196208WSDLE1
Adder
9.912
25196708WSDLE6
Adder
9.887
24387005FR-3G C
Solar/Wind Harmer
4.001
274728ELWOOD EC;5P
Adder
15.521
241985AE1-237 GEN
Solar/Wind Helper
0.238
20089226LOOKOUT
Solar/Wind Helper
0.555
203940AF1-140 C
Solar/Wind Helper
0.366
276763AC1-053 GEN1
Solar/Wind Harmer
4.006
276764AC1-053 GEN2
Solar/Wind Harmer
4.006
276668AB2-070 GEN1
Solar/Wind Harmer
2.24
276848AB2-070 GEN3
Solar/Wind Harmer
2.24
276849AB2-070 GEN2
Solar/Wind Harmer
2.24
970289AG2-191 GEN
Solar/Wind Harmer
1.899
25306009OHH W.
Adder
2.828
253372AE2-315 SEC3
Adder
1.855
253372AE2-315 SEC3
Adder
1.855
274744AC1-111 GEN8
Adder
5.298
274735ELWOOD EC;4P
Adder
15.521
241997AF1-093 GEN
Solar/Wind Helper
0.244
243186AF1-051 GEN
50/50
12.678
24721705FLATG2
50/50
39.728
24723005RIVRG1
Adder
37.214
24723105RIVRG2
Adder
37.214
971225AH1-072 GEN
Solar/Wind Harmer
3.058
971227AH1-073 GEN
Solar/Wind Harmer
3.058
270214AC2-123 GEN
Solar/Wind Harmer
3.229
270583AD2-179 GEN
Solar/Wind Harmer
12.98
971125AH1-004 GEN
Solar/Wind Harmer
4.843
276916AD2-100_GEN
Solar/Wind Harmer
21.637
970291AG2-192 GEN
Solar/Wind Harmer
1.299
970291AG2-192 GEN
Solar/Wind Harmer
0.418
253370AE2-315 SEC1
Adder
1.962
247621Y3-024
Adder
0.233
25322209TAIT E
Adder
9.312
25322209TAIT E
Adder
9.102
241801AE1-079 GEN
Solar/Wind Helper
0.238
203818AF1-086 GEN
Solar/Wind Helper
1.56
24686505CER G6
Adder
16.296
24728305BUCHG2
Adder
7.015
3429241JKCT 3G
Adder
14.456
339211AE2-254 GEN
Solar/Wind Harmer
1.837
944031AF1-071 GEN
Solar/Wind Harmer
1.061
965911AG1-460 GEN
Solar/Wind Harmer
1.434
962761AG1-125 GEN
Solar/Wind Harmer
33.21
270437AC2-090 C
Solar/Wind Harmer
5.696
24385905FR-11G C
Solar/Wind Harmer
8.406
276903AD2-071 C
Solar/Wind Harmer
10.104
274766LEE CO EC;7U
Adder
8.88
25326309TAIT D
Adder
1.046
274732ELWOOD EC;7P
Adder
15.521
274674JOLIET 9 ;6U
Adder
14.533
20089026BF_G21_K23
Solar/Wind Helper
0.44
20084626FORWARD
Solar/Wind Helper
0.33
970879AG2-548 GEN
Solar/Wind Harmer
1.534
962581AG1-107 GEN
Solar/Wind Harmer
6.183
961491AF2-440 GEN
Solar/Wind Harmer
2.569
970107AG2-081 GEN
Solar/Wind Harmer
3.632
339236AF1-050_GEN
Solar/Wind Harmer
2.145
970241AG2-163 GEN
Solar/Wind Harmer
25.754
276838X2-022 GEN2
Solar/Wind Harmer
0.237
274880W4-005 GEN4
Solar/Wind Harmer
3.059
276174W4-005 GEN2
Solar/Wind Harmer
3.059
24387305FR-4G C
Solar/Wind Harmer
5.138
274762LEE CO EC;3U
Adder
8.986
274696ROCKY RD ;4P
Adder
10.84
274697ROCKY RD ;3P
Adder
2.877
237043AE2-125 C
Solar/Wind Helper
0.172
962101AG1-054 GEN
Solar/Wind Helper
0.622
23751201ROTHROCK
Solar/Wind Helper
0.695
24289405MTG1
50/50
11.803
270329AC1-082 GEN1
Solar/Wind Harmer
0.94
24686405CER G5
Adder
16.168
339243AC2-075 GEN1
Solar/Wind Harmer
0.548
339206AE1-143 GEN
Solar/Wind Harmer
2.555
970455AG2-298 GEN
Solar/Wind Harmer
4.167
970653AG2-424 GEN
Solar/Wind Harmer
0.827
339255AE2-071 GEN
Solar/Wind Harmer
1.381
339250AF1-203 GEN
Solar/Wind Harmer
0.711
24379505HDWTR1G C
Solar/Wind Harmer
8.07
24386205FR-12G C
Solar/Wind Harmer
4.335
270004AE1-209 GEN
Solar/Wind Harmer
5.447
24690905MDL-1G C
Solar/Wind Harmer
7.997
274760LEE CO EC;1U
Adder
8.986
23562501BACKB
Solar/Wind Helper
0.844
CPLELTFEXP_CPLE->PJM
CLTF
7.358
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.448
LAGNLTFEXP_LAGN->PJM
CLTF
21.853
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
NYPJM->LTFIMP_NY
CLTF
4.988
LGEELTFEXP_LGEE->PJM
CLTF
8.269
TVALTFEXP_TVA->PJM
CLTF
11.37
WECLTFEXP_WEC->PJM
CLTF
3.678
AG2-052LTFEXP_AG2-052->PJM
LTF
0.221
AH1-155LTFEXP_AH1-155->PJM
LTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.565
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.151
MECLTFEXP_MEC->PJM
CLTF
16.954
SIGELTFEXP_SIGE->PJM
CLTF
0.599

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 555_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.06 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3608.77
MW Contribution:
3.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24288905REUSENS
50/50
0.04
970823AG2-518 GEN
50/50
5.732
24290605CLAY-1
50/50
0.17
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
5.912
970223AG2-152 GEN
Solar/Wind Harmer
8.217
24684605SMG4
50/50
1.533
962751AG1-124 GEN
Solar/Wind Harmer
9.113
3147312GRETNA
Solar/Wind Harmer
0.129
3146802CHATHAM
Solar/Wind Harmer
0.121
3147983MERCK5
Solar/Wind Helper
0.146
971543AH1-269 GEN
50/50
8.255
24684705SMG5
50/50
0.586
971313AH1-133 GEN
Solar/Wind Harmer
3.311
3148133STUARTS
Solar/Wind Helper
0.183
237061AD1-155 GEN
Solar/Wind Helper
1.4
3152021BATH 2B
50/50
16.153
270205AE1-176
50/50
0.004
24728405LEESVG
50/50
0.203
24728405LEESVG
50/50
0.202
943811AF1-049 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.226
270583AD2-179 GEN
Solar/Wind Harmer
9.704
3152031BATH 3C
50/50
16.174
3152011BATH 1A
50/50
16.153
3148463FAIRFLD
Solar/Wind Harmer
0.358
270197AD1-017 GEN1
Solar/Wind Harmer
0.971
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
3152041BATH 4D
50/50
16.147
3151881LOWMORC
50/50
4.045
3151881LOWMORC
50/50
3.981
24416005BYLLESBY
50/50
0.02
971331AH1-145 GEN
Solar/Wind Harmer
12.166
966391AG1-508 GEN
Solar/Wind Harmer
1.298
270069AE2-166 C O1
Solar/Wind Harmer
6.845
24734705WLF1G3
Adder
4.973
24734905WLF1G5
Adder
4.973
3148013FISHERV
Solar/Wind Helper
0.175
3152061BATH 6F
50/50
16.198
24290605CLAY-1
50/50
0.17
24684405SMG2
50/50
1.523
24728305BUCHG2
Adder
4.099
3148013FISHERV
Solar/Wind Helper
0.304
24684505SMG3
50/50
0.93
3147312GRETNA
Solar/Wind Harmer
0.032
23583801GRNGAP
Solar/Wind Helper
3.89
247619Y1-049
50/50
0.033
942671AE2-283 GEN
Solar/Wind Harmer
4.019
3132123MT JACKSON
Solar/Wind Helper
1.116
3152051BATH 5E
50/50
16.17
3151861LOWMORA
50/50
3.918
24684305SMG1
50/50
0.552
3151861LOWMORA
50/50
4.077
24290705CLAY-2
50/50
0.17
958131AF2-107 GEN
Solar/Wind Harmer
3.841
971329AH1-144 GEN
Solar/Wind Harmer
4.471
24734805WLF1G4
Adder
4.973
3137383CUSHAW
50/50
0.077
971277AH1-098 GEN
Solar/Wind Harmer
3.382
24728205BUCHG1
Adder
4.099
24290705CLAY-2
50/50
0.17
24415905BUCK
50/50
0.022
941801AE2-185 GEN
Solar/Wind Harmer
5.168
943031AE2-326 GEN
Solar/Wind Harmer
4.428
3147123OTTER R
Solar/Wind Harmer
0.09
270030AE2-140 GEN
Solar/Wind Harmer
14.101
960911AF2-382 GEN
Solar/Wind Harmer
4.591
CPLELTFEXP_CPLE->PJM
CLTF
3.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.738
LAGNLTFEXP_LAGN->PJM
CLTF
11.379
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.897
NYPJM->LTFIMP_NY
CLTF
2.913
LGEELTFEXP_LGEE->PJM
CLTF
3.585
TVALTFEXP_TVA->PJM
CLTF
6.026
WECLTFEXP_WEC->PJM
CLTF
1.751
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.449
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.084
MECLTFEXP_MEC->PJM
CLTF
8.168
SIGELTFEXP_SIGE->PJM
CLTF
0.27

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.87 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4131.96
MW Contribution:
6.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
4.988
3147123OTTER R
Solar/Wind Harmer
-0.011
270030AE2-140 GEN
Solar/Wind Harmer
22.56
960911AF2-382 GEN
Solar/Wind Harmer
7.439
316192AB2-158 GEN
Solar/Wind Helper
1.701
970823AG2-518 GEN
50/50
6.453
24288905REUSENS
50/50
0.044
24290605CLAY-1
50/50
0.191
958121AF2-106 GEN
Solar/Wind Harmer
7.113
270346AE1-212 GEN
Solar/Wind Harmer
9.774
270018AE2-047 C O1
Solar/Wind Harmer
1.335
970223AG2-152 GEN
Solar/Wind Harmer
12.946
971461AH1-227 GEN
Solar/Wind Harmer
4.675
3147666LOUISA
Solar/Wind Helper
1.004
238152AF2-075_GEN
Solar/Wind Helper
0.575
3152041BATH 4D
50/50
17.119
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.874
24416005BYLLESBY
50/50
0.022
315616AA1-038_C
Solar/Wind Harmer
14.227
971331AH1-145 GEN
Solar/Wind Harmer
13.713
966391AG1-508 GEN
Solar/Wind Harmer
4.679
270069AE2-166 C O1
Solar/Wind Harmer
10.973
24734705WLF1G3
Adder
5.611
24734905WLF1G5
Adder
5.611
3148013FISHERV
Solar/Wind Helper
0.263
247619Y1-049
50/50
0.037
942671AE2-283 GEN
Solar/Wind Harmer
6.661
3132123MT JACKSON
Solar/Wind Helper
1.31
966001AG1-469 GEN
Solar/Wind Helper
0.292
238148AE2-230_GEN2
Solar/Wind Helper
0.403
3152051BATH 5E
50/50
17.143
3151861LOWMORA
50/50
6.764
24684305SMG1
50/50
0.615
971329AH1-144 GEN
Solar/Wind Harmer
8.759
24734805WLF1G4
Adder
5.611
24735105WLF2G1
Adder
5.477
316164AC1-076 GEN
Solar/Wind Helper
1.099
3137383CUSHAW
50/50
0.133
971277AH1-098 GEN
Solar/Wind Harmer
5.459
24728205BUCHG1
Adder
4.632
970913AG2-568 GEN
Solar/Wind Harmer
6.181
238149AF1-291A_GEN
Solar/Wind Helper
0.115
3151861LOWMORA
50/50
7.039
24290705CLAY-2
50/50
0.191
270173AC1-122 GEN
Solar/Wind Harmer
2.679
958131AF2-107 GEN
Solar/Wind Harmer
5.401
971403AH1-188 GEN
Solar/Wind Harmer
12.18
3132273ORANGE
Solar/Wind Helper
0.051
23546401DTGZ2-030
Solar/Wind Helper
0.075
3152021BATH 2B
50/50
17.126
270205AE1-176
50/50
0.005
24728405LEESVG
50/50
0.226
24728405LEESVG
50/50
0.225
270574AD1-017 GEN2
Solar/Wind Harmer
6.411
270336AE1-100 GEN
Solar/Wind Harmer
2.015
943811AF1-049 GEN
Solar/Wind Harmer
4.146
24735205WLF2G2
Adder
5.477
316499AE2-029_GEN
Solar/Wind Helper
1.577
316095T157 G97
Solar/Wind Helper
1.083
3152031BATH 3C
50/50
17.148
3152011BATH 1A
50/50
17.126
3148463FAIRFLD
Solar/Wind Harmer
-0.069
270197AD1-017 GEN1
Solar/Wind Harmer
1.923
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
315651AD1-115 GEN
Solar/Wind Helper
0.785
24684505SMG3
50/50
1.037
3147312GRETNA
Solar/Wind Harmer
-0.004
971687AH1-348 GEN
Solar/Wind Harmer
0.905
315821AE2-092 GEN
Solar/Wind Helper
2.905
23583801GRNGAP
Solar/Wind Helper
4.13
24684605SMG4
50/50
1.709
962751AG1-124 GEN
Solar/Wind Harmer
14.722
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
270016AE1-250 BESS
Solar/Wind Harmer
2.406
3147983MERCK5
Solar/Wind Helper
0.183
971543AH1-269 GEN
50/50
9.295
24684705SMG5
50/50
0.653
971313AH1-133 GEN
Solar/Wind Harmer
6.499
3148133STUARTS
Solar/Wind Helper
0.274
270583AD2-179 GEN
Solar/Wind Harmer
15.666
270214AC2-123 GEN
Solar/Wind Harmer
3.169
971225AH1-072 GEN
Solar/Wind Harmer
1.823
971227AH1-073 GEN
Solar/Wind Harmer
1.823
316097T157 G90
Solar/Wind Helper
1.083
238147AE2-230_GEN1
Solar/Wind Helper
0.403
3152061BATH 6F
50/50
17.174
24290605CLAY-1
50/50
0.191
24684405SMG2
50/50
1.698
316217AC1-145 GEN
Solar/Wind Harmer
3.261
316197AC1-042 GEN
Solar/Wind Harmer
2.472
24728305BUCHG2
Adder
4.632
3148013FISHERV
Solar/Wind Helper
0.457
3147666LOUISA
Solar/Wind Helper
0.578
270013AE1-250 PV
Solar/Wind Harmer
2.406
237061AD1-155 GEN
Solar/Wind Helper
1.565
24290705CLAY-2
50/50
0.191
24415905BUCK
50/50
0.024
941801AE2-185 GEN
Solar/Wind Harmer
7.541
CPLELTFEXP_CPLE->PJM
CLTF
3.542
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.271
LAGNLTFEXP_LAGN->PJM
CLTF
12.819
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.276
NYPJM->LTFIMP_NY
CLTF
3.203
LGEELTFEXP_LGEE->PJM
CLTF
4.093
TVALTFEXP_TVA->PJM
CLTF
6.787
WECLTFEXP_WEC->PJM
CLTF
2.006
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.709
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.926
MECLTFEXP_MEC->PJM
CLTF
9.317
SIGELTFEXP_SIGE->PJM
CLTF
0.308

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 555_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.74 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3598.36
MW Contribution:
3.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24288905REUSENS
50/50
0.04
970823AG2-518 GEN
50/50
5.732
24684605SMG4
50/50
1.533
962751AG1-124 GEN
Solar/Wind Harmer
9.113
3147312GRETNA
Solar/Wind Harmer
0.129
3146802CHATHAM
Solar/Wind Harmer
0.121
3147983MERCK5
Solar/Wind Helper
0.146
971543AH1-269 GEN
50/50
8.255
24684705SMG5
50/50
0.586
971313AH1-133 GEN
Solar/Wind Harmer
3.311
3148133STUARTS
Solar/Wind Helper
0.183
237061AD1-155 GEN
Solar/Wind Helper
1.4
270583AD2-179 GEN
Solar/Wind Harmer
9.704
3152031BATH 3C
50/50
16.174
3152011BATH 1A
50/50
16.153
3148463FAIRFLD
Solar/Wind Harmer
0.358
270197AD1-017 GEN1
Solar/Wind Harmer
0.971
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
3152041BATH 4D
50/50
16.147
3151881LOWMORC
50/50
4.045
3151881LOWMORC
50/50
3.981
24416005BYLLESBY
50/50
0.02
971331AH1-145 GEN
Solar/Wind Harmer
12.166
966391AG1-508 GEN
Solar/Wind Harmer
1.298
270069AE2-166 C O1
Solar/Wind Harmer
6.845
24734705WLF1G3
Adder
4.973
24734905WLF1G5
Adder
4.973
3148013FISHERV
Solar/Wind Helper
0.175
3152061BATH 6F
50/50
16.198
24290605CLAY-1
50/50
0.17
24684405SMG2
50/50
1.523
24728305BUCHG2
Adder
4.099
3148013FISHERV
Solar/Wind Helper
0.304
3152021BATH 2B
50/50
16.153
270205AE1-176
50/50
0.004
24728405LEESVG
50/50
0.203
24728405LEESVG
50/50
0.202
943811AF1-049 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.226
24684505SMG3
50/50
0.93
3147312GRETNA
Solar/Wind Harmer
0.032
23583801GRNGAP
Solar/Wind Helper
3.89
247619Y1-049
50/50
0.033
942671AE2-283 GEN
Solar/Wind Harmer
4.019
3132123MT JACKSON
Solar/Wind Helper
1.116
3151861LOWMORA
50/50
4.077
24290705CLAY-2
50/50
0.17
958131AF2-107 GEN
Solar/Wind Harmer
3.841
3152051BATH 5E
50/50
16.17
3151861LOWMORA
50/50
3.918
24684305SMG1
50/50
0.552
971329AH1-144 GEN
Solar/Wind Harmer
4.471
24734805WLF1G4
Adder
4.973
3137383CUSHAW
50/50
0.077
971277AH1-098 GEN
Solar/Wind Harmer
3.382
24728205BUCHG1
Adder
4.099
24290605CLAY-1
50/50
0.17
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
5.912
970223AG2-152 GEN
Solar/Wind Harmer
8.217
24290705CLAY-2
50/50
0.17
24415905BUCK
50/50
0.022
941801AE2-185 GEN
Solar/Wind Harmer
5.168
943031AE2-326 GEN
Solar/Wind Harmer
4.428
3147123OTTER R
Solar/Wind Harmer
0.09
270030AE2-140 GEN
Solar/Wind Harmer
14.101
960911AF2-382 GEN
Solar/Wind Harmer
4.591
CPLELTFEXP_CPLE->PJM
CLTF
3.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.738
LAGNLTFEXP_LAGN->PJM
CLTF
11.379
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.897
NYPJM->LTFIMP_NY
CLTF
2.913
LGEELTFEXP_LGEE->PJM
CLTF
3.585
TVALTFEXP_TVA->PJM
CLTF
6.026
WECLTFEXP_WEC->PJM
CLTF
1.751
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.449
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.084
MECLTFEXP_MEC->PJM
CLTF
8.168
SIGELTFEXP_SIGE->PJM
CLTF
0.27

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.6 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4121.29
MW Contribution:
6.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
4.988
3147123OTTER R
Solar/Wind Harmer
-0.011
270030AE2-140 GEN
Solar/Wind Harmer
22.56
960911AF2-382 GEN
Solar/Wind Harmer
7.439
316192AB2-158 GEN
Solar/Wind Helper
1.701
970823AG2-518 GEN
50/50
6.453
24288905REUSENS
50/50
0.044
24290605CLAY-1
50/50
0.191
958121AF2-106 GEN
Solar/Wind Harmer
7.113
270346AE1-212 GEN
Solar/Wind Harmer
9.774
270018AE2-047 C O1
Solar/Wind Harmer
1.335
970223AG2-152 GEN
Solar/Wind Harmer
12.946
971461AH1-227 GEN
Solar/Wind Harmer
4.675
3147666LOUISA
Solar/Wind Helper
1.004
238152AF2-075_GEN
Solar/Wind Helper
0.575
3152041BATH 4D
50/50
17.119
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.874
24416005BYLLESBY
50/50
0.022
315616AA1-038_C
Solar/Wind Harmer
14.227
971331AH1-145 GEN
Solar/Wind Harmer
13.713
966391AG1-508 GEN
Solar/Wind Harmer
4.679
270069AE2-166 C O1
Solar/Wind Harmer
10.973
24734705WLF1G3
Adder
5.611
24734905WLF1G5
Adder
5.611
3148013FISHERV
Solar/Wind Helper
0.263
247619Y1-049
50/50
0.037
942671AE2-283 GEN
Solar/Wind Harmer
6.661
3132123MT JACKSON
Solar/Wind Helper
1.31
966001AG1-469 GEN
Solar/Wind Helper
0.292
238148AE2-230_GEN2
Solar/Wind Helper
0.403
3152051BATH 5E
50/50
17.143
3151861LOWMORA
50/50
6.764
24684305SMG1
50/50
0.615
971329AH1-144 GEN
Solar/Wind Harmer
8.759
24734805WLF1G4
Adder
5.611
24735105WLF2G1
Adder
5.477
316164AC1-076 GEN
Solar/Wind Helper
1.099
3137383CUSHAW
50/50
0.133
971277AH1-098 GEN
Solar/Wind Harmer
5.459
24728205BUCHG1
Adder
4.632
970913AG2-568 GEN
Solar/Wind Harmer
6.181
238149AF1-291A_GEN
Solar/Wind Helper
0.115
3151861LOWMORA
50/50
7.039
24290705CLAY-2
50/50
0.191
270173AC1-122 GEN
Solar/Wind Harmer
2.679
958131AF2-107 GEN
Solar/Wind Harmer
5.401
971403AH1-188 GEN
Solar/Wind Harmer
12.18
3132273ORANGE
Solar/Wind Helper
0.051
23546401DTGZ2-030
Solar/Wind Helper
0.075
3152021BATH 2B
50/50
17.126
270205AE1-176
50/50
0.005
24728405LEESVG
50/50
0.226
24728405LEESVG
50/50
0.225
270574AD1-017 GEN2
Solar/Wind Harmer
6.411
270336AE1-100 GEN
Solar/Wind Harmer
2.015
943811AF1-049 GEN
Solar/Wind Harmer
4.146
24735205WLF2G2
Adder
5.477
316499AE2-029_GEN
Solar/Wind Helper
1.577
316095T157 G97
Solar/Wind Helper
1.083
3152031BATH 3C
50/50
17.148
3152011BATH 1A
50/50
17.126
3148463FAIRFLD
Solar/Wind Harmer
-0.069
270197AD1-017 GEN1
Solar/Wind Harmer
1.923
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
315651AD1-115 GEN
Solar/Wind Helper
0.785
24684505SMG3
50/50
1.037
3147312GRETNA
Solar/Wind Harmer
-0.004
971687AH1-348 GEN
Solar/Wind Harmer
0.905
315821AE2-092 GEN
Solar/Wind Helper
2.905
23583801GRNGAP
Solar/Wind Helper
4.13
24684605SMG4
50/50
1.709
962751AG1-124 GEN
Solar/Wind Harmer
14.722
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
270016AE1-250 BESS
Solar/Wind Harmer
2.406
3147983MERCK5
Solar/Wind Helper
0.183
971543AH1-269 GEN
50/50
9.295
24684705SMG5
50/50
0.653
971313AH1-133 GEN
Solar/Wind Harmer
6.499
3148133STUARTS
Solar/Wind Helper
0.274
270583AD2-179 GEN
Solar/Wind Harmer
15.666
270214AC2-123 GEN
Solar/Wind Harmer
3.169
971225AH1-072 GEN
Solar/Wind Harmer
1.823
971227AH1-073 GEN
Solar/Wind Harmer
1.823
316097T157 G90
Solar/Wind Helper
1.083
238147AE2-230_GEN1
Solar/Wind Helper
0.403
3152061BATH 6F
50/50
17.174
24290605CLAY-1
50/50
0.191
24684405SMG2
50/50
1.698
316217AC1-145 GEN
Solar/Wind Harmer
3.261
316197AC1-042 GEN
Solar/Wind Harmer
2.472
24728305BUCHG2
Adder
4.632
3148013FISHERV
Solar/Wind Helper
0.457
3147666LOUISA
Solar/Wind Helper
0.578
270013AE1-250 PV
Solar/Wind Harmer
2.406
237061AD1-155 GEN
Solar/Wind Helper
1.565
24290705CLAY-2
50/50
0.191
24415905BUCK
50/50
0.024
941801AE2-185 GEN
Solar/Wind Harmer
7.541
CPLELTFEXP_CPLE->PJM
CLTF
3.542
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.271
LAGNLTFEXP_LAGN->PJM
CLTF
12.819
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.276
NYPJM->LTFIMP_NY
CLTF
3.203
LGEELTFEXP_LGEE->PJM
CLTF
4.093
TVALTFEXP_TVA->PJM
CLTF
6.787
WECLTFEXP_WEC->PJM
CLTF
2.006
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.709
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.926
MECLTFEXP_MEC->PJM
CLTF
9.317
SIGELTFEXP_SIGE->PJM
CLTF
0.308
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'DVP_P1-2: LN 555_SRT-A'
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
247977 to 242524 ckt 17
242519 to 314912 ckt 1
242516 to 242920 ckt 1
314901 to 314991 ckt 1
314991 to 314926 ckt 1

Winter Peak Analysis

The New Service Request AH1-133 was evaluated as a 70.0 MW (29.4 MW Capacity) injection in the AEP area.

AH1-133 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 70.0 MW (70.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-A_SENS
SingleAC220.41 %1180.0B2600.84
0.46
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 542T553_SRT-W_SENS
BreakerAC218.08 %1180.0B2573.38
0.46
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 553T564_SRT-W_SENS
BreakerAC217.06 %1180.0B2561.3
0.46
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC215.66 %1180.0B2544.77
0.5
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC194.03 %1180.0B2289.58
0.47
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC190.04 %1180.0B2242.41
0.44
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
BusAC186.82 %1180.0B2204.47
0.45
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC186.02 %1180.0B2194.98
0.45
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC180.89 %1180.0A2134.53
0.45

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:220.41 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2600.84
MW Contribution:
0.46
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.996
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.684
24728305BUCHG2
50/50
5.51
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.141
3142416OLDCHRC
Solar/Wind Helper
0.97
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.414
3142956BIRDNECK
Solar/Wind Helper
0.519
3143316POE
Solar/Wind Helper
1.304
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.352
3141913WHIT STONE
Solar/Wind Helper
0.35
3143226MDLTHAN
Solar/Wind Helper
0.36
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.189
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.255
3141726DUNNSVL
Solar/Wind Helper
1.412
24289905CRG1H
50/50
0.807
24290105CRG2H
50/50
0.813
24290005CRG1L
50/50
0.807
24290205CRG2L
50/50
0.807
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.11
316314AB2-024 C
Solar/Wind Helper
0.114
316316AC1-027 C
Solar/Wind Helper
0.089
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.284
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.239
3141196NOKESVL
Solar/Wind Helper
1.295
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.88
3143526WINTERP
Solar/Wind Helper
1.88
316404AE1-155 C
Solar/Wind Helper
0.718
316033AB2-134 GEN
Solar/Wind Helper
0.757
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.734
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.15
316369SG1_INVT
Solar/Wind Helper
0.52
315651AD1-115 GEN
Solar/Wind Helper
0.758
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.653
315662AE1-191 GEN
Solar/Wind Helper
0.451
315666AE1-190 GEN
Solar/Wind Helper
0.113
315697AD1-025 GEN
Solar/Wind Helper
0.797
316185AD1-033 GEN
Solar/Wind Helper
0.352
316280AD1-041 GEN
Solar/Wind Helper
0.282
316447AC1-158 HLD
Solar/Wind Helper
0.966
316044AC1-158 PL1
Solar/Wind Helper
0.439
316045AC1-158 PL2
Solar/Wind Helper
1.405
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.439
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.113
270583AD2-179 GEN
Solar/Wind Harmer
0.811
270346AE1-212 GEN
Solar/Wind Harmer
0.545
270030AE2-140 GEN
Solar/Wind Harmer
1.083
270069AE2-166 C O1
Solar/Wind Harmer
0.526
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
0.403
316375AC2-012 GEN
Solar/Wind Helper
0.596
316197AC1-042 GEN
Solar/Wind Helper
0.215
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.981
316169AC1-164_GENC
Solar/Wind Helper
0.847
316381AD1-082 GEN
Solar/Wind Helper
0.344
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.036
3142946ENON
Solar/Wind Helper
0.119
3144536CHRHLND
Solar/Wind Helper
0.048
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.281
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.563
961611AG1-000B GEN
Solar/Wind Helper
0.468
961951AG1-038 GEN
Solar/Wind Helper
0.254
966871AG1-558 GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.062
970563AG2-360 GEN
50/50
33.666
970823AG2-518 GEN
50/50
5.456
970913AG2-568 GEN
Solar/Wind Harmer
0.421
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.457
971329AH1-144 GEN
Solar/Wind Harmer
0.545
971331AH1-145 GEN
Solar/Wind Harmer
12.45
971403AH1-188 GEN
Solar/Wind Harmer
0.722
971461AH1-227 GEN
Solar/Wind Harmer
0.281
971543AH1-269 GEN
50/50
8.214
971687AH1-348 GEN
Solar/Wind Harmer
0.054
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.192
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.959
971981AH1-535 GEN
Solar/Wind Harmer
0.503
972103AH1-617 GEN
Solar/Wind Harmer
1.012
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.044
971881AH1-461 GEN
50/50
10.558
315773AC2-141 GEN
Solar/Wind Helper
1.246
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.256
316294AC1-161 GEN
Solar/Wind Helper
1.246
316473AC1-191 GEN
Solar/Wind Helper
0.483
316487AF1-042 GEN
Solar/Wind Helper
0.254
316484AD2-074 GEN
Solar/Wind Helper
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.356
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.618
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.657
NYPJM->LTFIMP_NY
CLTF
2.067
LGEELTFEXP_LGEE->PJM
CLTF
4.281
WECLTFEXP_WEC->PJM
CLTF
2.133
CPLELTFEXP_CPLE->PJM
CLTF
1.528
TVALTFEXP_TVA->PJM
CLTF
6.811
MECLTFEXP_MEC->PJM
CLTF
9.763
LAGNLTFEXP_LAGN->PJM
CLTF
12.763
SIGELTFEXP_SIGE->PJM
CLTF
0.322
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.192

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 542T553_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 542T553_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.08 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2573.38
MW Contribution:
0.46
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.997
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.693
24728305BUCHG2
50/50
5.518
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.141
3142416OLDCHRC
Solar/Wind Helper
0.968
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.412
3142956BIRDNECK
Solar/Wind Helper
0.518
3143316POE
Solar/Wind Helper
1.302
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.352
3141913WHIT STONE
Solar/Wind Helper
0.35
3143226MDLTHAN
Solar/Wind Helper
0.359
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.254
3141726DUNNSVL
Solar/Wind Helper
1.409
24289905CRG1H
50/50
0.808
24290105CRG2H
50/50
0.815
24290005CRG1L
50/50
0.808
24290205CRG2L
50/50
0.808
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.11
316314AB2-024 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.088
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.282
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.293
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.877
3143526WINTERP
Solar/Wind Helper
1.877
316404AE1-155 C
Solar/Wind Helper
0.716
316033AB2-134 GEN
Solar/Wind Helper
0.755
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.733
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.15
316369SG1_INVT
Solar/Wind Helper
0.519
315651AD1-115 GEN
Solar/Wind Helper
0.757
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.652
315662AE1-191 GEN
Solar/Wind Helper
0.45
315666AE1-190 GEN
Solar/Wind Helper
0.112
315697AD1-025 GEN
Solar/Wind Helper
0.796
316185AD1-033 GEN
Solar/Wind Helper
0.351
316280AD1-041 GEN
Solar/Wind Helper
0.281
316447AC1-158 HLD
Solar/Wind Helper
0.965
316044AC1-158 PL1
Solar/Wind Helper
0.439
316045AC1-158 PL2
Solar/Wind Helper
1.403
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.438
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.113
270583AD2-179 GEN
Solar/Wind Harmer
0.812
270346AE1-212 GEN
Solar/Wind Harmer
0.546
270030AE2-140 GEN
Solar/Wind Harmer
1.085
270069AE2-166 C O1
Solar/Wind Harmer
0.527
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.402
316458AB2-190 GEN2
Solar/Wind Helper
0.402
316375AC2-012 GEN
Solar/Wind Helper
0.595
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.979
316169AC1-164_GENC
Solar/Wind Helper
0.846
316381AD1-082 GEN
Solar/Wind Helper
0.344
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.035
3142946ENON
Solar/Wind Helper
0.119
3144536CHRHLND
Solar/Wind Helper
0.047
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.287
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.563
961611AG1-000B GEN
Solar/Wind Helper
0.467
961951AG1-038 GEN
Solar/Wind Helper
0.254
966871AG1-558 GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.064
970563AG2-360 GEN
50/50
33.712
970823AG2-518 GEN
50/50
5.462
970913AG2-568 GEN
Solar/Wind Harmer
0.421
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.458
971329AH1-144 GEN
Solar/Wind Harmer
0.545
971331AH1-145 GEN
Solar/Wind Harmer
12.465
971403AH1-188 GEN
Solar/Wind Harmer
0.724
971461AH1-227 GEN
Solar/Wind Harmer
0.282
971543AH1-269 GEN
50/50
8.223
971687AH1-348 GEN
Solar/Wind Harmer
0.055
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.191
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.963
971981AH1-535 GEN
Solar/Wind Harmer
0.504
972103AH1-617 GEN
Solar/Wind Harmer
1.014
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.051
971881AH1-461 GEN
50/50
10.572
315773AC2-141 GEN
Solar/Wind Helper
1.244
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.255
316294AC1-161 GEN
Solar/Wind Helper
1.244
316473AC1-191 GEN
Solar/Wind Helper
0.482
316487AF1-042 GEN
Solar/Wind Helper
0.254
316484AD2-074 GEN
Solar/Wind Helper
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.588
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.833
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.705
NYPJM->LTFIMP_NY
CLTF
2.056
LGEELTFEXP_LGEE->PJM
CLTF
4.292
WECLTFEXP_WEC->PJM
CLTF
2.14
CPLELTFEXP_CPLE->PJM
CLTF
1.545
TVALTFEXP_TVA->PJM
CLTF
6.827
MECLTFEXP_MEC->PJM
CLTF
9.79
LAGNLTFEXP_LAGN->PJM
CLTF
12.796
SIGELTFEXP_SIGE->PJM
CLTF
0.323
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 553T564_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 553T564_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:217.06 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2561.3
MW Contribution:
0.46
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.997
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.696
24728305BUCHG2
50/50
5.522
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.14
3142416OLDCHRC
Solar/Wind Helper
0.968
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.411
3142956BIRDNECK
Solar/Wind Helper
0.518
3143316POE
Solar/Wind Helper
1.301
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.351
3141913WHIT STONE
Solar/Wind Helper
0.349
3143226MDLTHAN
Solar/Wind Helper
0.359
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.063
3147312GRETNA
Solar/Wind Helper
0.254
3141726DUNNSVL
Solar/Wind Helper
1.408
24289905CRG1H
50/50
0.809
24290105CRG2H
50/50
0.815
24290005CRG1L
50/50
0.809
24290205CRG2L
50/50
0.809
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.109
316314AB2-024 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.088
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.281
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.292
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.876
3143526WINTERP
Solar/Wind Helper
1.876
316404AE1-155 C
Solar/Wind Helper
0.716
316033AB2-134 GEN
Solar/Wind Helper
0.755
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.732
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.149
316369SG1_INVT
Solar/Wind Helper
0.519
315651AD1-115 GEN
Solar/Wind Helper
0.756
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.652
315662AE1-191 GEN
Solar/Wind Helper
0.45
315666AE1-190 GEN
Solar/Wind Helper
0.112
315697AD1-025 GEN
Solar/Wind Helper
0.795
316185AD1-033 GEN
Solar/Wind Helper
0.351
316280AD1-041 GEN
Solar/Wind Helper
0.281
316447AC1-158 HLD
Solar/Wind Helper
0.964
316044AC1-158 PL1
Solar/Wind Helper
0.438
316045AC1-158 PL2
Solar/Wind Helper
1.402
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.438
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.112
270583AD2-179 GEN
Solar/Wind Harmer
0.812
270346AE1-212 GEN
Solar/Wind Harmer
0.546
270030AE2-140 GEN
Solar/Wind Harmer
1.086
270069AE2-166 C O1
Solar/Wind Harmer
0.527
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.402
316458AB2-190 GEN2
Solar/Wind Helper
0.402
316375AC2-012 GEN
Solar/Wind Helper
0.595
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.979
316169AC1-164_GENC
Solar/Wind Helper
0.845
316381AD1-082 GEN
Solar/Wind Helper
0.343
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.035
3142946ENON
Solar/Wind Helper
0.118
3144536CHRHLND
Solar/Wind Helper
0.047
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.29
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.562
961611AG1-000B GEN
Solar/Wind Helper
0.467
961951AG1-038 GEN
Solar/Wind Helper
0.253
966871AG1-558 GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.065
970563AG2-360 GEN
50/50
33.733
970823AG2-518 GEN
50/50
5.464
970913AG2-568 GEN
Solar/Wind Harmer
0.422
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.458
971329AH1-144 GEN
Solar/Wind Harmer
0.546
971331AH1-145 GEN
Solar/Wind Harmer
12.472
971403AH1-188 GEN
Solar/Wind Harmer
0.724
971461AH1-227 GEN
Solar/Wind Harmer
0.282
971543AH1-269 GEN
50/50
8.227
971687AH1-348 GEN
Solar/Wind Harmer
0.055
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.191
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.965
971981AH1-535 GEN
Solar/Wind Harmer
0.504
972103AH1-617 GEN
Solar/Wind Harmer
1.014
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.053
971881AH1-461 GEN
50/50
10.579
315773AC2-141 GEN
Solar/Wind Helper
1.243
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.255
316294AC1-161 GEN
Solar/Wind Helper
1.243
316473AC1-191 GEN
Solar/Wind Helper
0.482
316487AF1-042 GEN
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.484
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.927
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.726
NYPJM->LTFIMP_NY
CLTF
2.052
LGEELTFEXP_LGEE->PJM
CLTF
4.297
WECLTFEXP_WEC->PJM
CLTF
2.142
CPLELTFEXP_CPLE->PJM
CLTF
1.553
TVALTFEXP_TVA->PJM
CLTF
6.834
MECLTFEXP_MEC->PJM
CLTF
9.802
LAGNLTFEXP_LAGN->PJM
CLTF
12.81
SIGELTFEXP_SIGE->PJM
CLTF
0.323
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.66 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2544.77
MW Contribution:
0.5
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
1.018
24290605CLAY-1
50/50
0.171
24290605CLAY-1
50/50
0.171
24290705CLAY-2
50/50
0.171
24290705CLAY-2
50/50
0.171
24728205BUCHG1
50/50
6.231
24728305BUCHG2
50/50
6.04
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.13
3142416OLDCHRC
Solar/Wind Helper
0.878
3142416OLDCHRC
Solar/Wind Helper
0.336
3142433PROV 92
Solar/Wind Helper
1.276
316075AC2-137 C
Solar/Wind Helper
0.106
316077AC2-138 C
Solar/Wind Helper
0.072
3138133OCRAN
Solar/Wind Helper
0.095
3138133OCRAN
Solar/Wind Helper
0.19
3141766HARMONY
Solar/Wind Helper
0.064
3141783LANCAST
Solar/Wind Helper
0.191
3141783LANCAST
Solar/Wind Helper
0.127
3141813NORNECK
Solar/Wind Helper
0.322
3141913WHIT STONE
Solar/Wind Helper
0.317
3143226MDLTHAN
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.191
3147123OTTER R
Solar/Wind Helper
0.187
3147312GRETNA
Solar/Wind Helper
0.063
3147312GRETNA
Solar/Wind Helper
0.254
3147666LOUISA
Solar/Wind Helper
1.258
3147666LOUISA
Solar/Wind Helper
0.723
3141726DUNNSVL
Solar/Wind Helper
1.29
24289905CRG1H
50/50
0.888
24290105CRG2H
50/50
0.895
24290005CRG1L
50/50
0.888
24290205CRG2L
50/50
0.888
316059AD1-063 C
Solar/Wind Helper
0.077
316314AB2-024 C
Solar/Wind Helper
0.103
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.355
3141873WAN 176
Solar/Wind Helper
0.063
3143526WINTERP
Solar/Wind Helper
1.709
3143526WINTERP
Solar/Wind Helper
1.709
316404AE1-155 C
Solar/Wind Helper
0.655
3142543TWELFTH
Solar/Wind Helper
0.031
316203AE2-005 GEN
Solar/Wind Helper
0.662
316441AF1-014 GEN
Solar/Wind Helper
0.101
316312AB1-027
Solar/Wind Helper
0.136
315651AD1-115 GEN
Solar/Wind Helper
0.792
315662AE1-191 GEN
Solar/Wind Helper
0.407
315666AE1-190 GEN
Solar/Wind Helper
0.102
316280AD1-041 GEN
Solar/Wind Helper
0.254
316447AC1-158 HLD
Solar/Wind Helper
0.936
316044AC1-158 PL1
Solar/Wind Helper
0.425
316045AC1-158 PL2
Solar/Wind Helper
1.361
316450AC1-158 RIC
Solar/Wind Helper
0.113
316468AD1-105 GEN
Solar/Wind Helper
0.407
316156AD2-030 GEN
Solar/Wind Helper
0.1
316337AD2-073 GEN
Solar/Wind Helper
0.104
270399AC1-101 GEN
Solar/Wind Harmer
0.288
270583AD2-179 GEN
Solar/Wind Harmer
0.823
270494AE1-108_GEN
Solar/Wind Helper
0.847
270346AE1-212 GEN
Solar/Wind Harmer
0.589
270030AE2-140 GEN
Solar/Wind Harmer
1.139
270069AE2-166 C O1
Solar/Wind Harmer
0.548
270053AF1-130 C
Solar/Wind Harmer
1.012
316006AB2-029 C
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.442
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.105
315975AC1-164 GENB
Solar/Wind Helper
0.026
315976AC1-164 GENA
Solar/Wind Helper
0.883
316169AC1-164_GENC
Solar/Wind Helper
0.763
316233AE1-074 FULL
Solar/Wind Helper
0.106
3142946ENON
Solar/Wind Helper
0.032
3142946ENON
Solar/Wind Helper
0.107
943031AE2-326 GEN
Solar/Wind Harmer
5.484
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.53
944971AF1-162 GEN
Solar/Wind Harmer
6.858
961951AG1-038 GEN
Solar/Wind Helper
0.231
966871AG1-558 GEN
Solar/Wind Helper
0.11
966881AG1-559 GEN
Solar/Wind Helper
0.114
970281AG2-184 GEN
Solar/Wind Harmer
1.21
970563AG2-360 GEN
50/50
36.34
970823AG2-518 GEN
50/50
5.453
970913AG2-568 GEN
Solar/Wind Harmer
0.477
971061AG2-657 GEN
Solar/Wind Harmer
0.472
971225AH1-072 GEN
Solar/Wind Harmer
0.123
971227AH1-073 GEN
Solar/Wind Harmer
0.123
971277AH1-098 GEN
Solar/Wind Harmer
0.336
971313AH1-133 GEN
Solar/Wind Harmer
0.496
971329AH1-144 GEN
Solar/Wind Harmer
0.558
971331AH1-145 GEN
Solar/Wind Harmer
12.762
971403AH1-188 GEN
Solar/Wind Harmer
0.833
971461AH1-227 GEN
Solar/Wind Harmer
0.315
971543AH1-269 GEN
50/50
8.316
971687AH1-348 GEN
Solar/Wind Harmer
0.061
24415905BUCK
50/50
0.026
24416005BYLLESBY
50/50
0.049
957601AF2-054 GEN
Solar/Wind Helper
0.101
957971AF2-091 GEN
Solar/Wind Helper
0.18
964211AG1-282 GEN
Solar/Wind Helper
0.104
966391AG1-508 GEN
Solar/Wind Harmer
4.12
971981AH1-535 GEN
Solar/Wind Harmer
0.558
972103AH1-617 GEN
Solar/Wind Harmer
1.152
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.448
971881AH1-461 GEN
50/50
11.424
316164AC1-076 GEN
Solar/Wind Helper
0.342
316217AC1-145 GEN
Solar/Wind Helper
0.255
316473AC1-191 GEN
Solar/Wind Helper
0.44
270400AC1-102 GEN
Solar/Wind Harmer
0.288
316487AF1-042 GEN
Solar/Wind Helper
0.231
316484AD2-074 GEN
Solar/Wind Helper
0.442
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.464
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.422
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.119
NYPJM->LTFIMP_NY
CLTF
2.528
LGEELTFEXP_LGEE->PJM
CLTF
5.132
WECLTFEXP_WEC->PJM
CLTF
2.57
CPLELTFEXP_CPLE->PJM
CLTF
2.392
TVALTFEXP_TVA->PJM
CLTF
7.856
MECLTFEXP_MEC->PJM
CLTF
11.663
LAGNLTFEXP_LAGN->PJM
CLTF
14.865
SIGELTFEXP_SIGE->PJM
CLTF
0.385
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.446
AG2-052LTFEXP_AG2-052->PJM
LTF
0.155
AH1-155LTFEXP_AH1-155->PJM
LTF
0.233

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:194.03 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2289.58
MW Contribution:
0.47
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
1.014
24290605CLAY-1
50/50
0.172
24290605CLAY-1
50/50
0.172
24290705CLAY-2
50/50
0.172
24290705CLAY-2
50/50
0.172
24728205BUCHG1
50/50
5.791
24728305BUCHG2
50/50
5.614
3142416OLDCHRC
Solar/Wind Helper
0.842
3142416OLDCHRC
Solar/Wind Helper
0.323
316075AC2-137 C
Solar/Wind Helper
0.101
3143226MDLTHAN
Solar/Wind Helper
0.32
270205AE1-176
50/50
0.013
3143526WINTERP
Solar/Wind Helper
1.661
3143526WINTERP
Solar/Wind Helper
1.661
3148463FAIRFLD
Solar/Wind Harmer
-0.312
315616AA1-038_C
Solar/Wind Harmer
3.158
316312AB1-027
Solar/Wind Helper
0.13
316447AC1-158 HLD
Solar/Wind Helper
0.871
316044AC1-158 PL1
Solar/Wind Helper
0.396
316045AC1-158 PL2
Solar/Wind Helper
1.267
316450AC1-158 RIC
Solar/Wind Helper
0.106
316468AD1-105 GEN
Solar/Wind Helper
0.386
270399AC1-101 GEN
Solar/Wind Harmer
0.252
270583AD2-179 GEN
Solar/Wind Harmer
0.825
270494AE1-108_GEN
Solar/Wind Helper
0.869
270346AE1-212 GEN
Solar/Wind Harmer
0.553
270030AE2-140 GEN
Solar/Wind Harmer
1.13
270069AE2-166 C O1
Solar/Wind Harmer
0.546
24734705WLF1G3
50/50
7.099
24734805WLF1G4
50/50
7.099
24734905WLF1G5
50/50
7.099
24735105WLF2G1
50/50
6.939
24735205WLF2G2
50/50
6.939
315975AC1-164 GENB
Solar/Wind Helper
0.025
315976AC1-164 GENA
Solar/Wind Helper
0.849
316169AC1-164_GENC
Solar/Wind Helper
0.733
316233AE1-074 FULL
Solar/Wind Helper
0.103
943031AE2-326 GEN
Solar/Wind Harmer
5.381
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.105
966881AG1-559 GEN
Solar/Wind Helper
0.108
970281AG2-184 GEN
Solar/Wind Harmer
1.082
970563AG2-360 GEN
50/50
34.318
970823AG2-518 GEN
50/50
5.548
970913AG2-568 GEN
Solar/Wind Harmer
0.426
971225AH1-072 GEN
Solar/Wind Harmer
0.112
971227AH1-073 GEN
Solar/Wind Harmer
0.112
971277AH1-098 GEN
Solar/Wind Harmer
0.33
971313AH1-133 GEN
Solar/Wind Harmer
0.466
971329AH1-144 GEN
Solar/Wind Harmer
0.554
971331AH1-145 GEN
Solar/Wind Harmer
12.663
971403AH1-188 GEN
Solar/Wind Harmer
0.734
971461AH1-227 GEN
Solar/Wind Harmer
0.287
971543AH1-269 GEN
50/50
8.359
971687AH1-348 GEN
Solar/Wind Harmer
0.056
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.048
966391AG1-508 GEN
Solar/Wind Harmer
4.035
971981AH1-535 GEN
Solar/Wind Harmer
0.518
972103AH1-617 GEN
Solar/Wind Harmer
1.031
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.128
971881AH1-461 GEN
50/50
10.749
316164AC1-076 GEN
Solar/Wind Helper
0.321
316473AC1-191 GEN
Solar/Wind Helper
0.421
270400AC1-102 GEN
Solar/Wind Harmer
0.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
84.953
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.009
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.24
NYPJM->LTFIMP_NY
CLTF
2.009
LGEELTFEXP_LGEE->PJM
CLTF
4.347
WECLTFEXP_WEC->PJM
CLTF
2.162
CPLELTFEXP_CPLE->PJM
CLTF
2.241
TVALTFEXP_TVA->PJM
CLTF
7.056
MECLTFEXP_MEC->PJM
CLTF
9.948
LAGNLTFEXP_LAGN->PJM
CLTF
13.244
SIGELTFEXP_SIGE->PJM
CLTF
0.327
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.194

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:190.04 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2242.41
MW Contribution:
0.44
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.954
24290605CLAY-1
50/50
0.161
24290605CLAY-1
50/50
0.161
24290705CLAY-2
50/50
0.161
24290705CLAY-2
50/50
0.161
24728205BUCHG1
50/50
5.518
24728305BUCHG2
50/50
5.349
3142416OLDCHRC
Solar/Wind Helper
0.834
3142416OLDCHRC
Solar/Wind Helper
0.319
316075AC2-137 C
Solar/Wind Helper
0.1
3143226MDLTHAN
Solar/Wind Helper
0.312
3147123OTTER R
Solar/Wind Helper
0.192
3147312GRETNA
Solar/Wind Helper
0.065
3147312GRETNA
Solar/Wind Helper
0.261
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.245
3143526WINTERP
Solar/Wind Helper
1.627
3143526WINTERP
Solar/Wind Helper
1.627
316312AB1-027
Solar/Wind Helper
0.129
316447AC1-158 HLD
Solar/Wind Helper
0.869
316044AC1-158 PL1
Solar/Wind Helper
0.395
316045AC1-158 PL2
Solar/Wind Helper
1.264
316450AC1-158 RIC
Solar/Wind Helper
0.105
316468AD1-105 GEN
Solar/Wind Helper
0.383
270583AD2-179 GEN
Solar/Wind Harmer
0.773
270494AE1-108_GEN
Solar/Wind Helper
0.825
270346AE1-212 GEN
Solar/Wind Harmer
0.523
270030AE2-140 GEN
Solar/Wind Harmer
1.055
270069AE2-166 C O1
Solar/Wind Harmer
0.509
24734705WLF1G3
50/50
6.764
24734805WLF1G4
50/50
6.764
24734905WLF1G5
50/50
6.764
24735105WLF2G1
50/50
6.612
24735205WLF2G2
50/50
6.612
316197AC1-042 GEN
Solar/Wind Helper
0.22
316233AE1-074 FULL
Solar/Wind Helper
0.101
943031AE2-326 GEN
Solar/Wind Harmer
5.111
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.104
966881AG1-559 GEN
Solar/Wind Helper
0.107
970563AG2-360 GEN
50/50
32.682
970823AG2-518 GEN
50/50
5.169
970913AG2-568 GEN
Solar/Wind Harmer
0.406
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.313
971313AH1-133 GEN
Solar/Wind Harmer
0.443
971329AH1-144 GEN
Solar/Wind Harmer
0.52
971331AH1-145 GEN
Solar/Wind Harmer
11.877
971403AH1-188 GEN
Solar/Wind Harmer
0.701
971461AH1-227 GEN
Solar/Wind Harmer
0.274
971543AH1-269 GEN
50/50
7.822
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.825
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.934
971881AH1-461 GEN
50/50
10.218
316164AC1-076 GEN
Solar/Wind Helper
0.317
316217AC1-145 GEN
Solar/Wind Helper
0.262
316473AC1-191 GEN
Solar/Wind Helper
0.417
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.376
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.835
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.235
NYPJM->LTFIMP_NY
CLTF
1.913
LGEELTFEXP_LGEE->PJM
CLTF
4.185
WECLTFEXP_WEC->PJM
CLTF
2.088
CPLELTFEXP_CPLE->PJM
CLTF
1.958
TVALTFEXP_TVA->PJM
CLTF
6.727
MECLTFEXP_MEC->PJM
CLTF
9.577
LAGNLTFEXP_LAGN->PJM
CLTF
12.632
SIGELTFEXP_SIGE->PJM
CLTF
0.315
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.536
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:186.82 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2204.47
MW Contribution:
0.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.959
24290605CLAY-1
50/50
0.162
24290605CLAY-1
50/50
0.162
24290705CLAY-2
50/50
0.162
24290705CLAY-2
50/50
0.162
24728205BUCHG1
50/50
5.533
24728305BUCHG2
50/50
5.364
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.256
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.24
316447AC1-158 HLD
Solar/Wind Helper
0.833
316044AC1-158 PL1
Solar/Wind Helper
0.379
316045AC1-158 PL2
Solar/Wind Helper
1.211
316450AC1-158 RIC
Solar/Wind Helper
0.101
270583AD2-179 GEN
Solar/Wind Harmer
0.777
270494AE1-108_GEN
Solar/Wind Helper
0.809
270346AE1-212 GEN
Solar/Wind Harmer
0.524
270030AE2-140 GEN
Solar/Wind Harmer
1.069
270069AE2-166 C O1
Solar/Wind Harmer
0.515
24734705WLF1G3
50/50
6.789
24734805WLF1G4
50/50
6.789
24734905WLF1G5
50/50
6.789
24735105WLF2G1
50/50
6.638
24735205WLF2G2
50/50
6.638
316197AC1-042 GEN
Solar/Wind Helper
0.216
943031AE2-326 GEN
Solar/Wind Harmer
5.137
943811AF1-049 GEN
Solar/Wind Harmer
0
966881AG1-559 GEN
Solar/Wind Helper
0.102
970563AG2-360 GEN
50/50
32.8
970823AG2-518 GEN
50/50
5.199
970913AG2-568 GEN
Solar/Wind Harmer
0.406
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.314
971313AH1-133 GEN
Solar/Wind Harmer
0.445
971329AH1-144 GEN
Solar/Wind Harmer
0.522
971331AH1-145 GEN
Solar/Wind Harmer
11.934
971403AH1-188 GEN
Solar/Wind Harmer
0.701
971461AH1-227 GEN
Solar/Wind Harmer
0.274
971543AH1-269 GEN
50/50
7.866
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.844
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.947
971881AH1-461 GEN
50/50
10.25
316217AC1-145 GEN
Solar/Wind Helper
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.062
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.386
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.91
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.644
NYPJM->LTFIMP_NY
CLTF
1.911
LGEELTFEXP_LGEE->PJM
CLTF
4.164
WECLTFEXP_WEC->PJM
CLTF
2.073
CPLELTFEXP_CPLE->PJM
CLTF
2.153
TVALTFEXP_TVA->PJM
CLTF
6.757
MECLTFEXP_MEC->PJM
CLTF
9.533
LAGNLTFEXP_LAGN->PJM
CLTF
12.686
SIGELTFEXP_SIGE->PJM
CLTF
0.314
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.662
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:186.02 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2194.98
MW Contribution:
0.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.96
24290605CLAY-1
50/50
0.162
24290605CLAY-1
50/50
0.162
24290705CLAY-2
50/50
0.162
24290705CLAY-2
50/50
0.162
24728205BUCHG1
50/50
5.534
24728305BUCHG2
50/50
5.365
3142416OLDCHRC
Solar/Wind Helper
0.819
3142416OLDCHRC
Solar/Wind Helper
0.314
3143226MDLTHAN
Solar/Wind Helper
0.324
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.255
316258AE1-075 C
Solar/Wind Helper
0.094
316405AF2-144 C
Solar/Wind Helper
0.088
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.239
3143526WINTERP
Solar/Wind Helper
1.661
3143526WINTERP
Solar/Wind Helper
1.661
316312AB1-027
Solar/Wind Helper
0.126
316447AC1-158 HLD
Solar/Wind Helper
0.837
316044AC1-158 PL1
Solar/Wind Helper
0.381
316045AC1-158 PL2
Solar/Wind Helper
1.218
316450AC1-158 RIC
Solar/Wind Helper
0.101
316468AD1-105 GEN
Solar/Wind Helper
0.374
316313AB2-026
Solar/Wind Helper
0.104
270583AD2-179 GEN
Solar/Wind Harmer
0.778
270494AE1-108_GEN
Solar/Wind Helper
0.764
270346AE1-212 GEN
Solar/Wind Harmer
0.524
270030AE2-140 GEN
Solar/Wind Harmer
1.068
270069AE2-166 C O1
Solar/Wind Harmer
0.515
24734705WLF1G3
50/50
6.788
24734805WLF1G4
50/50
6.788
24734905WLF1G5
50/50
6.788
24735105WLF2G1
50/50
6.636
24735205WLF2G2
50/50
6.636
316197AC1-042 GEN
Solar/Wind Helper
0.215
316233AE1-074 FULL
Solar/Wind Helper
0.103
943031AE2-326 GEN
Solar/Wind Harmer
5.139
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.102
966881AG1-559 GEN
Solar/Wind Helper
0.104
970563AG2-360 GEN
50/50
32.806
970823AG2-518 GEN
50/50
5.206
970913AG2-568 GEN
Solar/Wind Harmer
0.406
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.314
971313AH1-133 GEN
Solar/Wind Harmer
0.445
971329AH1-144 GEN
Solar/Wind Harmer
0.523
971331AH1-145 GEN
Solar/Wind Harmer
11.946
971403AH1-188 GEN
Solar/Wind Harmer
0.701
971461AH1-227 GEN
Solar/Wind Harmer
0.274
971543AH1-269 GEN
50/50
7.875
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.846
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.947
971881AH1-461 GEN
50/50
10.253
316217AC1-145 GEN
Solar/Wind Helper
0.256
316473AC1-191 GEN
Solar/Wind Helper
0.41
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.009
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.274
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.872
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.539
NYPJM->LTFIMP_NY
CLTF
1.92
LGEELTFEXP_LGEE->PJM
CLTF
4.162
WECLTFEXP_WEC->PJM
CLTF
2.071
CPLELTFEXP_CPLE->PJM
CLTF
2.099
TVALTFEXP_TVA->PJM
CLTF
6.746
MECLTFEXP_MEC->PJM
CLTF
9.525
LAGNLTFEXP_LAGN->PJM
CLTF
12.662
SIGELTFEXP_SIGE->PJM
CLTF
0.313
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.646
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:180.89 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:2134.53
MW Contribution:
0.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.96
24290605CLAY-1
50/50
0.162
24290605CLAY-1
50/50
0.162
24290705CLAY-2
50/50
0.162
24290705CLAY-2
50/50
0.162
24728205BUCHG1
50/50
5.538
24728305BUCHG2
50/50
5.369
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.255
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.239
316447AC1-158 HLD
Solar/Wind Helper
0.832
316044AC1-158 PL1
Solar/Wind Helper
0.378
316045AC1-158 PL2
Solar/Wind Helper
1.21
316450AC1-158 RIC
Solar/Wind Helper
0.101
270583AD2-179 GEN
Solar/Wind Harmer
0.777
270494AE1-108_GEN
Solar/Wind Helper
0.809
270346AE1-212 GEN
Solar/Wind Harmer
0.524
270030AE2-140 GEN
Solar/Wind Harmer
1.07
270069AE2-166 C O1
Solar/Wind Harmer
0.516
24734705WLF1G3
50/50
6.796
24734805WLF1G4
50/50
6.796
24734905WLF1G5
50/50
6.796
24735105WLF2G1
50/50
6.645
24735205WLF2G2
50/50
6.645
316197AC1-042 GEN
Solar/Wind Helper
0.215
943031AE2-326 GEN
Solar/Wind Harmer
5.14
943811AF1-049 GEN
Solar/Wind Harmer
0
966881AG1-559 GEN
Solar/Wind Helper
0.102
970563AG2-360 GEN
50/50
32.828
970823AG2-518 GEN
50/50
5.203
970913AG2-568 GEN
Solar/Wind Harmer
0.407
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.314
971313AH1-133 GEN
Solar/Wind Harmer
0.445
971329AH1-144 GEN
Solar/Wind Harmer
0.522
971331AH1-145 GEN
Solar/Wind Harmer
11.943
971403AH1-188 GEN
Solar/Wind Harmer
0.702
971461AH1-227 GEN
Solar/Wind Harmer
0.275
971543AH1-269 GEN
50/50
7.871
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.846
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.951
971881AH1-461 GEN
50/50
10.259
316217AC1-145 GEN
Solar/Wind Helper
0.256
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.515
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.946
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.673
NYPJM->LTFIMP_NY
CLTF
1.904
LGEELTFEXP_LGEE->PJM
CLTF
4.171
WECLTFEXP_WEC->PJM
CLTF
2.076
CPLELTFEXP_CPLE->PJM
CLTF
2.163
TVALTFEXP_TVA->PJM
CLTF
6.767
MECLTFEXP_MEC->PJM
CLTF
9.549
LAGNLTFEXP_LAGN->PJM
CLTF
12.705
SIGELTFEXP_SIGE->PJM
CLTF
0.314
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.662
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186
CONTINGENCY 'DVP_P1-2: LN 553_SRT-A_SENS'
 OPEN BRANCH FROM BUS 314910 TO BUS 313378 CKT 1   /*8CUNINGHAM   500.0 - 8VONTAY      500.0
END
CONTINGENCY 'DVP_P4-2: 542T553_SRT-W_SENS'
 OPEN BRANCH FROM BUS 313378 TO BUS 314910 CKT 1                /*8VONTAY      500.0 - 8CUNINGHAM   500.0
 OPEN BUS 315217                                                /*1CUNINGB      18.0
 OPEN BUS 315218                                                /*1CUNINGC      18.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'DVP_P4-2: 553T564_SRT-W_SENS'
 OPEN BRANCH FROM BUS 313378 TO BUS 314910 CKT 1                /*8VONTAY      500.0 - 8CUNINGHAM   500.0
 OPEN BUS 315216                                                /*1CUNINGA      18.0
 OPEN BUS 315219                                                /*1CUNINGD      22.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2114-535_SRT-A_SENS'
 OPEN BRANCH FROM BUS 235110 TO BUS 289543 CKT 1   /*01MDWBRK     500.0 - 05YEAT       500.0
 OPEN BRANCH FROM BUS 314085 TO BUS 314110 CKT 1   /*6REMNGCT     230.0 - 6ELK RUN     230.0
 OPEN BRANCH FROM BUS 314110 TO BUS 314125 CKT 1   /*6ELK RUN     230.0 - 6VINTHIL     230.0
 OPEN BUS 314110                                   /*6ELK RUN     230.0
END
CONTINGENCY 'PECO_P2-2_PHILLIPS-BUS_SRT-A
 DISCONNECT BUS 213888   /*PHLISCT1      18.0
 DISCONNECT BUS 213889   /*PHLISCT2      18.0
 DISCONNECT BUS 213892   /*PHLISL87     230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-133 was evaluated as a 70.0 MW injection

AH1-133 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 70.0 MW (70.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC173.68 %1180.0B2049.45
6.41
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC173.67 %1180.0B2049.35
6.41
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-L
BreakerAC173.35 %1180.0B2045.56
6.41
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC171.54 %1180.0B2024.13
6.41
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
5.39
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
5.39
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC136.83 %1180.0B1614.63
5.39
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
BusAC110.97 %1180.0B1309.48
4.95
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17030___SRT-A
TowerAC110.49 %1180.0B1303.74
5.01
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17029___SRT-A
TowerAC110.3 %1180.0B1301.52
5.01
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
BusAC109.1 %1180.0B1287.39
4.93

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.68 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.45
MW Contribution:
6.41
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.581
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.418
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.519
316303AF2-085
50/50
Charging
2.243
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.49
316405AF2-144 C
50/50
Charging
1.174
316404AE1-155 C
Solar/Wind Helper
3.563
316203AE2-005 GEN
Solar/Wind Helper
3.616
316441AF1-014 GEN
Solar/Wind Helper
0.553
315616AA1-038_C
Solar/Wind Helper
1.957
316312AB1-027
Solar/Wind Helper
0.748
315651AD1-115 GEN
Solar/Wind Helper
4.201
315821AE2-092 GEN
Solar/Wind Helper
3.827
315662AE1-191 GEN
Solar/Wind Helper
2.22
315666AE1-190 GEN
Solar/Wind Helper
0.555
316280AD1-041 GEN
Solar/Wind Helper
1.388
316473AC1-191 GEN
Solar/Wind Helper
2.427
316447AC1-158 HLD
Solar/Wind Helper
5.08
316044AC1-158 PL1
Solar/Wind Helper
2.309
316045AC1-158 PL2
Solar/Wind Helper
7.388
316450AC1-158 RIC
Solar/Wind Helper
0.616
316468AD1-105 GEN
Solar/Wind Helper
2.225
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.563
316313AB2-026
Solar/Wind Helper
0.577
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
270583AD2-179 GEN
Solar/Wind Harmer
12.447
270494AE1-108_GEN
Solar/Wind Helper
5.579
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270030AE2-140 GEN
Solar/Wind Harmer
17.484
270069AE2-166 C O1
Solar/Wind Harmer
8.427
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.765
316164AC1-076 GEN
Solar/Wind Helper
1.94
316223AC1-118
Solar/Wind Helper
0.567
315975AC1-164 GENB
Solar/Wind Helper
0.061
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.709
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.856
960911AF2-382 GEN
Solar/Wind Harmer
6.617
961951AG1-038 GEN
Solar/Wind Helper
1.258
963031AG1-152 GEN
50/50
Charging
10.85
966871AG1-558 GEN
Solar/Wind Helper
0.436
966881AG1-559 GEN
Solar/Wind Helper
0.447
970119AG2-088 GEN
50/50
Charging
16.823
970281AG2-184 GEN
Solar/Wind Harmer
15.747
970417AG2-272 GEN
50/50
8.428
970563AG2-360 GEN
50/50
45.019
970823AG2-518 GEN
50/50
19.371
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971277AH1-098 GEN
Solar/Wind Harmer
4.144
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971507AH1-251 GEN
50/50
Charging
5.863
971531AH1-263 GEN
50/50
Charging
23.667
971543AH1-269 GEN
50/50
11.498
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.655
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.971
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.423
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971981AH1-535 GEN
Solar/Wind Harmer
6.611
971981AH1-535 GEN
Solar/Wind Harmer
7.212
972103AH1-617 GEN
Solar/Wind Harmer
14.997
972273AH1-721 GEN
50/50
85.07
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.246
971881AH1-461 GEN
50/50
14.324
972293SS25-0014
50/50
Charging
57.012
316487AF1-042 GEN
Solar/Wind Helper
1.165
316484AD2-074 GEN
Solar/Wind Helper
2.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.179
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.67 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.35
MW Contribution:
6.41
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.581
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.418
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.519
316303AF2-085
50/50
Charging
2.243
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.49
316405AF2-144 C
50/50
Charging
1.175
316404AE1-155 C
Solar/Wind Helper
3.563
316203AE2-005 GEN
Solar/Wind Helper
3.616
316441AF1-014 GEN
Solar/Wind Helper
0.554
315616AA1-038_C
Solar/Wind Helper
1.962
316312AB1-027
Solar/Wind Helper
0.748
315651AD1-115 GEN
Solar/Wind Helper
4.201
315821AE2-092 GEN
Solar/Wind Helper
3.827
315662AE1-191 GEN
Solar/Wind Helper
2.22
315666AE1-190 GEN
Solar/Wind Helper
0.555
316280AD1-041 GEN
Solar/Wind Helper
1.388
316473AC1-191 GEN
Solar/Wind Helper
2.427
316447AC1-158 HLD
Solar/Wind Helper
5.08
316044AC1-158 PL1
Solar/Wind Helper
2.309
316045AC1-158 PL2
Solar/Wind Helper
7.388
316450AC1-158 RIC
Solar/Wind Helper
0.616
316468AD1-105 GEN
Solar/Wind Helper
2.225
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.563
316313AB2-026
Solar/Wind Helper
0.577
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
270583AD2-179 GEN
Solar/Wind Harmer
12.447
270494AE1-108_GEN
Solar/Wind Helper
5.58
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270030AE2-140 GEN
Solar/Wind Harmer
17.484
270069AE2-166 C O1
Solar/Wind Harmer
8.427
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.765
316164AC1-076 GEN
Solar/Wind Helper
1.94
316223AC1-118
Solar/Wind Helper
0.567
315975AC1-164 GENB
Solar/Wind Helper
0.061
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.709
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.856
960911AF2-382 GEN
Solar/Wind Harmer
6.617
961951AG1-038 GEN
Solar/Wind Helper
1.258
963031AG1-152 GEN
50/50
Charging
10.85
966871AG1-558 GEN
Solar/Wind Helper
0.436
966881AG1-559 GEN
Solar/Wind Helper
0.447
970119AG2-088 GEN
50/50
Charging
16.824
970281AG2-184 GEN
Solar/Wind Harmer
15.747
970417AG2-272 GEN
50/50
8.428
970563AG2-360 GEN
50/50
45.019
970823AG2-518 GEN
50/50
19.371
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971277AH1-098 GEN
Solar/Wind Harmer
4.144
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971507AH1-251 GEN
50/50
Charging
5.863
971531AH1-263 GEN
50/50
Charging
23.667
971543AH1-269 GEN
50/50
11.498
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.655
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.971
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.423
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971981AH1-535 GEN
Solar/Wind Harmer
6.611
971981AH1-535 GEN
Solar/Wind Harmer
7.212
972103AH1-617 GEN
Solar/Wind Harmer
14.997
972273AH1-721 GEN
50/50
85.07
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.246
971881AH1-461 GEN
50/50
14.324
972293SS25-0014
50/50
Charging
57.012
316487AF1-042 GEN
Solar/Wind Helper
1.165
316484AD2-074 GEN
Solar/Wind Helper
2.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.178
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2045.56
MW Contribution:
6.41
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.582
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.419
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.52
316303AF2-085
50/50
Charging
2.246
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.491
316405AF2-144 C
50/50
Charging
1.177
316404AE1-155 C
Solar/Wind Helper
3.567
316203AE2-005 GEN
Solar/Wind Helper
3.62
316441AF1-014 GEN
Solar/Wind Helper
0.554
315616AA1-038_C
Solar/Wind Helper
2.018
316312AB1-027
Solar/Wind Helper
0.748
315651AD1-115 GEN
Solar/Wind Helper
4.205
315821AE2-092 GEN
Solar/Wind Helper
3.841
315662AE1-191 GEN
Solar/Wind Helper
2.223
315666AE1-190 GEN
Solar/Wind Helper
0.556
316280AD1-041 GEN
Solar/Wind Helper
1.389
316473AC1-191 GEN
Solar/Wind Helper
2.43
316447AC1-158 HLD
Solar/Wind Helper
5.083
316044AC1-158 PL1
Solar/Wind Helper
2.31
316045AC1-158 PL2
Solar/Wind Helper
7.393
316450AC1-158 RIC
Solar/Wind Helper
0.616
316468AD1-105 GEN
Solar/Wind Helper
2.227
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.564
316313AB2-026
Solar/Wind Helper
0.578
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
270583AD2-179 GEN
Solar/Wind Harmer
12.446
270494AE1-108_GEN
Solar/Wind Helper
5.59
270346AE1-212 GEN
Solar/Wind Harmer
8.185
270030AE2-140 GEN
Solar/Wind Harmer
17.478
270069AE2-166 C O1
Solar/Wind Harmer
8.425
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.769
316164AC1-076 GEN
Solar/Wind Helper
1.941
316223AC1-118
Solar/Wind Helper
0.568
315975AC1-164 GENB
Solar/Wind Helper
0.061
315976AC1-164 GENA
Solar/Wind Helper
2.057
316169AC1-164_GENC
Solar/Wind Helper
1.777
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.708
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.859
960911AF2-382 GEN
Solar/Wind Harmer
6.616
961951AG1-038 GEN
Solar/Wind Helper
1.26
963031AG1-152 GEN
50/50
Charging
10.856
966871AG1-558 GEN
Solar/Wind Helper
0.437
966881AG1-559 GEN
Solar/Wind Helper
0.447
970119AG2-088 GEN
50/50
Charging
16.846
970281AG2-184 GEN
Solar/Wind Harmer
15.746
970417AG2-272 GEN
50/50
8.425
970563AG2-360 GEN
50/50
45.014
970823AG2-518 GEN
50/50
19.368
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971277AH1-098 GEN
Solar/Wind Harmer
4.143
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.832
971331AH1-145 GEN
Solar/Wind Harmer
17.214
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.168
971507AH1-251 GEN
50/50
Charging
5.867
971531AH1-263 GEN
50/50
Charging
23.682
971543AH1-269 GEN
50/50
11.496
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.663
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.972
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.424
966391AG1-508 GEN
Solar/Wind Harmer
10.237
971981AH1-535 GEN
Solar/Wind Harmer
6.61
971981AH1-535 GEN
Solar/Wind Harmer
7.211
972103AH1-617 GEN
Solar/Wind Harmer
14.996
972273AH1-721 GEN
50/50
85.068
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.247
971881AH1-461 GEN
50/50
14.323
972293SS25-0014
50/50
Charging
57.048
316487AF1-042 GEN
Solar/Wind Helper
1.167
316484AD2-074 GEN
Solar/Wind Helper
2.229
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.017
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.652
NYPJM->LTFIMP_NY
CLTF
2.177
LGEELTFEXP_LGEE->PJM
CLTF
5.764
WECLTFEXP_WEC->PJM
CLTF
2.895
CPLELTFEXP_CPLE->PJM
CLTF
4.745
TVALTFEXP_TVA->PJM
CLTF
9.524
MECLTFEXP_MEC->PJM
CLTF
13.347
LAGNLTFEXP_LAGN->PJM
CLTF
17.991
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.478
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2024.13
MW Contribution:
6.41
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.581
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.418
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.519
316303AF2-085
50/50
Charging
2.243
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
50/50
Charging
1.174
316404AE1-155 C
Solar/Wind Helper
3.563
316203AE2-005 GEN
Solar/Wind Helper
3.616
316441AF1-014 GEN
Solar/Wind Helper
0.553
315616AA1-038_C
Solar/Wind Helper
1.957
315651AD1-115 GEN
Solar/Wind Helper
4.201
315821AE2-092 GEN
Solar/Wind Helper
3.827
315662AE1-191 GEN
Solar/Wind Helper
2.22
315666AE1-190 GEN
Solar/Wind Helper
0.555
316280AD1-041 GEN
Solar/Wind Helper
1.388
316473AC1-191 GEN
Solar/Wind Helper
2.427
316468AD1-105 GEN
Solar/Wind Helper
2.225
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.563
316313AB2-026
Solar/Wind Helper
0.577
270399AC1-101 GEN
Solar/Wind Harmer
3.469
270400AC1-102 GEN
Solar/Wind Harmer
3.469
270583AD2-179 GEN
Solar/Wind Harmer
12.447
270494AE1-108_GEN
Solar/Wind Helper
5.579
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270030AE2-140 GEN
Solar/Wind Harmer
17.484
270069AE2-166 C O1
Solar/Wind Harmer
8.427
270053AF1-130 C
Solar/Wind Harmer
12.797
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.765
316164AC1-076 GEN
Solar/Wind Helper
1.94
316223AC1-118
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.709
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.856
944971AF1-162 GEN
Solar/Wind Harmer
2.093
960911AF2-382 GEN
Solar/Wind Harmer
6.617
961951AG1-038 GEN
Solar/Wind Helper
1.258
963031AG1-152 GEN
50/50
Charging
10.85
970119AG2-088 GEN
50/50
Charging
16.823
970281AG2-184 GEN
Solar/Wind Harmer
15.747
970417AG2-272 GEN
50/50
8.428
970563AG2-360 GEN
50/50
45.019
970823AG2-518 GEN
50/50
19.371
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971507AH1-251 GEN
50/50
Charging
5.863
971531AH1-263 GEN
50/50
Charging
23.667
971543AH1-269 GEN
50/50
11.498
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.655
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.971
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.423
966391AG1-508 GEN
Solar/Wind Harmer
10.239
972103AH1-617 GEN
Solar/Wind Harmer
14.997
972273AH1-721 GEN
50/50
85.07
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.246
971881AH1-461 GEN
50/50
14.324
972293SS25-0014
50/50
Charging
57.012
316487AF1-042 GEN
Solar/Wind Helper
1.165
316484AD2-074 GEN
Solar/Wind Helper
2.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.179
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
5.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316312AB1-027
Solar/Wind Helper
0.693
316473AC1-191 GEN
Solar/Wind Helper
2.25
316447AC1-158 HLD
Solar/Wind Helper
4.798
316044AC1-158 PL1
Solar/Wind Helper
2.181
316045AC1-158 PL2
Solar/Wind Helper
6.979
316450AC1-158 RIC
Solar/Wind Helper
0.582
316468AD1-105 GEN
Solar/Wind Helper
2.079
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270583AD2-179 GEN
Solar/Wind Harmer
9.358
270494AE1-108_GEN
Solar/Wind Helper
4.816
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270053AF1-130 C
Solar/Wind Harmer
11.711
316006AB2-029 C
Solar/Wind Helper
0.504
316164AC1-076 GEN
Solar/Wind Helper
1.745
943031AE2-326 GEN
Solar/Wind Harmer
9.448
944491AF1-114 GEN
Solar/Wind Helper
2.702
944971AF1-162 GEN
Solar/Wind Harmer
10.409
960911AF2-382 GEN
Solar/Wind Harmer
5.69
963031AG1-152 GEN
50/50
Charging
10.244
966871AG1-558 GEN
Solar/Wind Helper
0.404
966881AG1-559 GEN
Solar/Wind Helper
0.418
970281AG2-184 GEN
Solar/Wind Harmer
14.006
970417AG2-272 GEN
50/50
6.326
970563AG2-360 GEN
50/50
37.854
970823AG2-518 GEN
50/50
14.083
970913AG2-568 GEN
Solar/Wind Harmer
5.207
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971277AH1-098 GEN
Solar/Wind Harmer
3.312
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971331AH1-145 GEN
Solar/Wind Harmer
13.165
971403AH1-188 GEN
Solar/Wind Harmer
9.621
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971507AH1-251 GEN
50/50
Charging
5.466
971531AH1-263 GEN
50/50
Charging
22.363
971543AH1-269 GEN
50/50
8.594
971687AH1-348 GEN
Solar/Wind Harmer
0.705
941621AE2-160 GEN
50/50
5.904
957191AF2-013 GEN
50/50
Charging
10.139
957971AF2-091 GEN
Solar/Wind Helper
0.919
966391AG1-508 GEN
Solar/Wind Harmer
8.202
972103AH1-617 GEN
Solar/Wind Harmer
13.339
972273AH1-721 GEN
50/50
76.948
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.154
971881AH1-461 GEN
50/50
11.944
972293SS25-0014
50/50
Charging
53.849
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
5.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316312AB1-027
Solar/Wind Helper
0.693
316473AC1-191 GEN
Solar/Wind Helper
2.25
316447AC1-158 HLD
Solar/Wind Helper
4.798
316044AC1-158 PL1
Solar/Wind Helper
2.181
316045AC1-158 PL2
Solar/Wind Helper
6.979
316450AC1-158 RIC
Solar/Wind Helper
0.582
316468AD1-105 GEN
Solar/Wind Helper
2.079
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270583AD2-179 GEN
Solar/Wind Harmer
9.358
270494AE1-108_GEN
Solar/Wind Helper
4.816
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270053AF1-130 C
Solar/Wind Harmer
11.711
316006AB2-029 C
Solar/Wind Helper
0.504
316164AC1-076 GEN
Solar/Wind Helper
1.745
943031AE2-326 GEN
Solar/Wind Harmer
9.448
944491AF1-114 GEN
Solar/Wind Helper
2.702
944971AF1-162 GEN
Solar/Wind Harmer
10.409
960911AF2-382 GEN
Solar/Wind Harmer
5.69
963031AG1-152 GEN
50/50
Charging
10.244
966871AG1-558 GEN
Solar/Wind Helper
0.404
966881AG1-559 GEN
Solar/Wind Helper
0.418
970281AG2-184 GEN
Solar/Wind Harmer
14.006
970417AG2-272 GEN
50/50
6.326
970563AG2-360 GEN
50/50
37.854
970823AG2-518 GEN
50/50
14.083
970913AG2-568 GEN
Solar/Wind Harmer
5.207
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971277AH1-098 GEN
Solar/Wind Harmer
3.312
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971331AH1-145 GEN
Solar/Wind Harmer
13.165
971403AH1-188 GEN
Solar/Wind Harmer
9.621
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971507AH1-251 GEN
50/50
Charging
5.466
971531AH1-263 GEN
50/50
Charging
22.363
971543AH1-269 GEN
50/50
8.594
971687AH1-348 GEN
Solar/Wind Harmer
0.705
941621AE2-160 GEN
50/50
5.904
957191AF2-013 GEN
50/50
Charging
10.139
957971AF2-091 GEN
Solar/Wind Helper
0.919
966391AG1-508 GEN
Solar/Wind Harmer
8.202
972103AH1-617 GEN
Solar/Wind Harmer
13.339
972273AH1-721 GEN
50/50
76.948
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.154
971881AH1-461 GEN
50/50
11.944
972293SS25-0014
50/50
Charging
53.849
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.83 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1614.63
MW Contribution:
5.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316473AC1-191 GEN
Solar/Wind Helper
2.25
316468AD1-105 GEN
Solar/Wind Helper
2.079
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270583AD2-179 GEN
Solar/Wind Harmer
9.358
270494AE1-108_GEN
Solar/Wind Helper
4.816
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270030AE2-140 GEN
Solar/Wind Harmer
3.161
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270053AF1-130 C
Solar/Wind Harmer
11.711
316006AB2-029 C
Solar/Wind Helper
0.504
316164AC1-076 GEN
Solar/Wind Helper
1.745
943031AE2-326 GEN
Solar/Wind Harmer
9.448
944491AF1-114 GEN
Solar/Wind Helper
2.702
944971AF1-162 GEN
Solar/Wind Harmer
12.03
960911AF2-382 GEN
Solar/Wind Harmer
5.69
963031AG1-152 GEN
50/50
Charging
10.244
970281AG2-184 GEN
Solar/Wind Harmer
14.006
970417AG2-272 GEN
50/50
6.326
970563AG2-360 GEN
50/50
37.854
970823AG2-518 GEN
50/50
14.083
970913AG2-568 GEN
Solar/Wind Harmer
5.207
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971331AH1-145 GEN
Solar/Wind Harmer
13.165
971403AH1-188 GEN
Solar/Wind Harmer
9.621
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971507AH1-251 GEN
50/50
Charging
5.466
971531AH1-263 GEN
50/50
Charging
22.363
971543AH1-269 GEN
50/50
8.594
971687AH1-348 GEN
Solar/Wind Harmer
0.705
941621AE2-160 GEN
50/50
5.904
957191AF2-013 GEN
50/50
Charging
10.139
957971AF2-091 GEN
Solar/Wind Helper
0.919
966391AG1-508 GEN
Solar/Wind Harmer
8.202
972103AH1-617 GEN
Solar/Wind Harmer
13.339
972273AH1-721 GEN
50/50
76.948
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.154
971881AH1-461 GEN
50/50
11.944
972293SS25-0014
50/50
Charging
53.849
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.97 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1309.48
MW Contribution:
4.95
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3147123OTTER R
Solar/Wind Harmer
0.188
3147312GRETNA
Solar/Wind Harmer
0.273
3147312GRETNA
Solar/Wind Harmer
0.068
3146802CHATHAM
Solar/Wind Harmer
0.256
316447AC1-158 HLD
Solar/Wind Helper
4.5
316044AC1-158 PL1
Solar/Wind Helper
2.046
316045AC1-158 PL2
Solar/Wind Helper
6.545
316450AC1-158 RIC
Solar/Wind Helper
0.545
270583AD2-179 GEN
Solar/Wind Harmer
9.646
270346AE1-212 GEN
Solar/Wind Harmer
6.338
270030AE2-140 GEN
Solar/Wind Harmer
14.894
270069AE2-166 C O1
Solar/Wind Harmer
7.142
942671AE2-283 GEN
Solar/Wind Harmer
3.623
943031AE2-326 GEN
Solar/Wind Harmer
9.019
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.121
962751AG1-124 GEN
Solar/Wind Harmer
6.233
966881AG1-559 GEN
Solar/Wind Helper
0.39
970281AG2-184 GEN
Solar/Wind Harmer
11.543
970417AG2-272 GEN
50/50
7.231
970563AG2-360 GEN
50/50
34.767
970823AG2-518 GEN
50/50
14.96
970913AG2-568 GEN
Solar/Wind Harmer
4.573
971225AH1-072 GEN
Solar/Wind Harmer
1.261
971227AH1-073 GEN
Solar/Wind Harmer
1.261
971277AH1-098 GEN
Solar/Wind Harmer
3.537
971277AH1-098 GEN
Solar/Wind Harmer
3.215
971313AH1-133 GEN
Solar/Wind Harmer
4.952
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971331AH1-145 GEN
Solar/Wind Harmer
13.329
971403AH1-188 GEN
Solar/Wind Harmer
8.261
971461AH1-227 GEN
Solar/Wind Harmer
3.235
971507AH1-251 GEN
50/50
Charging
5.111
971531AH1-263 GEN
50/50
Charging
20.999
971543AH1-269 GEN
50/50
8.911
971687AH1-348 GEN
Solar/Wind Harmer
0.626
941621AE2-160 GEN
50/50
5.119
941801AE2-185 GEN
Solar/Wind Harmer
4.102
966391AG1-508 GEN
Solar/Wind Harmer
7.933
971981AH1-535 GEN
Solar/Wind Harmer
5.175
971981AH1-535 GEN
Solar/Wind Harmer
5.645
958121AF2-106 GEN
Solar/Wind Harmer
0
961131AF2-404 GEN
Solar/Wind Harmer
2.357
971881AH1-461 GEN
50/50
11.072
972293SS25-0014
50/50
Charging
50.508
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.09
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.61
NYPJM->LTFIMP_NY
CLTF
1.786
LGEELTFEXP_LGEE->PJM
CLTF
4.54
WECLTFEXP_WEC->PJM
CLTF
2.293
CPLELTFEXP_CPLE->PJM
CLTF
4.184
TVALTFEXP_TVA->PJM
CLTF
7.544
MECLTFEXP_MEC->PJM
CLTF
10.573
LAGNLTFEXP_LAGN->PJM
CLTF
14.289
SIGELTFEXP_SIGE->PJM
CLTF
0.346
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
19.204
AG2-052LTFEXP_AG2-052->PJM
LTF
0.137
AH1-155LTFEXP_AH1-155->PJM
LTF
0.206

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17030___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17030___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1303.74
MW Contribution:
5.01
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Helper
4.364
316044AC1-158 PL1
Solar/Wind Helper
1.983
316045AC1-158 PL2
Solar/Wind Helper
6.347
316450AC1-158 RIC
Solar/Wind Helper
0.529
270399AC1-101 GEN
Solar/Wind Harmer
1.329
270400AC1-102 GEN
Solar/Wind Harmer
1.329
270173AC1-122 GEN
Solar/Wind Helper
2.76
270583AD2-179 GEN
Solar/Wind Harmer
9.612
270494AE1-108_GEN
Solar/Wind Helper
5.948
270346AE1-212 GEN
Solar/Wind Harmer
6.395
270030AE2-140 GEN
Solar/Wind Harmer
12.927
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
316217AC1-145 GEN
Solar/Wind Helper
1.974
943031AE2-326 GEN
Solar/Wind Harmer
9.122
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.18
970281AG2-184 GEN
Solar/Wind Harmer
12.374
970417AG2-272 GEN
50/50
6.193
970563AG2-360 GEN
50/50
35.173
970823AG2-518 GEN
50/50
14.895
970913AG2-568 GEN
Solar/Wind Harmer
4.649
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971277AH1-098 GEN
Solar/Wind Harmer
3.223
971313AH1-133 GEN
Solar/Wind Harmer
5.006
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971403AH1-188 GEN
Solar/Wind Harmer
8.401
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971531AH1-263 GEN
50/50
Charging
20.391
971543AH1-269 GEN
50/50
8.871
971687AH1-348 GEN
Solar/Wind Harmer
0.633
941621AE2-160 GEN
50/50
5.212
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971981AH1-535 GEN
Solar/Wind Harmer
5.117
971981AH1-535 GEN
Solar/Wind Harmer
5.582
972103AH1-617 GEN
Solar/Wind Harmer
11.785
958121AF2-106 GEN
Solar/Wind Harmer
0
961131AF2-404 GEN
50/50
Charging
2.924
971881AH1-461 GEN
50/50
11.185
972293SS25-0014
50/50
Charging
48.973
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
NYPJM->LTFIMP_NY
CLTF
1.631
LGEELTFEXP_LGEE->PJM
CLTF
4.594
WECLTFEXP_WEC->PJM
CLTF
2.32
CPLELTFEXP_CPLE->PJM
CLTF
3.013
TVALTFEXP_TVA->PJM
CLTF
7.367
MECLTFEXP_MEC->PJM
CLTF
10.609
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
SIGELTFEXP_SIGE->PJM
CLTF
0.348
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17029___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17029___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.3 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1301.52
MW Contribution:
5.01
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Helper
4.364
316044AC1-158 PL1
Solar/Wind Helper
1.983
316045AC1-158 PL2
Solar/Wind Helper
6.347
316450AC1-158 RIC
Solar/Wind Helper
0.529
270399AC1-101 GEN
Solar/Wind Harmer
1.329
270400AC1-102 GEN
Solar/Wind Harmer
1.329
270173AC1-122 GEN
Solar/Wind Helper
2.76
270583AD2-179 GEN
Solar/Wind Harmer
9.612
270494AE1-108_GEN
Solar/Wind Helper
5.948
270346AE1-212 GEN
Solar/Wind Harmer
6.395
270030AE2-140 GEN
Solar/Wind Harmer
12.927
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
316217AC1-145 GEN
Solar/Wind Helper
1.974
943031AE2-326 GEN
Solar/Wind Harmer
9.122
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.18
970281AG2-184 GEN
Solar/Wind Harmer
12.374
970417AG2-272 GEN
50/50
6.193
970563AG2-360 GEN
50/50
35.173
970823AG2-518 GEN
50/50
14.895
970913AG2-568 GEN
Solar/Wind Harmer
4.649
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971277AH1-098 GEN
Solar/Wind Harmer
3.223
971313AH1-133 GEN
Solar/Wind Harmer
5.006
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971403AH1-188 GEN
Solar/Wind Harmer
8.401
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971531AH1-263 GEN
50/50
Charging
20.391
971543AH1-269 GEN
50/50
8.871
971687AH1-348 GEN
Solar/Wind Harmer
0.633
941621AE2-160 GEN
50/50
5.212
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971981AH1-535 GEN
Solar/Wind Harmer
5.117
971981AH1-535 GEN
Solar/Wind Harmer
5.582
972103AH1-617 GEN
Solar/Wind Harmer
11.785
958121AF2-106 GEN
Solar/Wind Harmer
0
961131AF2-404 GEN
50/50
Charging
2.924
971881AH1-461 GEN
50/50
11.185
972293SS25-0014
50/50
Charging
48.973
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
NYPJM->LTFIMP_NY
CLTF
1.631
LGEELTFEXP_LGEE->PJM
CLTF
4.594
WECLTFEXP_WEC->PJM
CLTF
2.32
CPLELTFEXP_CPLE->PJM
CLTF
3.013
TVALTFEXP_TVA->PJM
CLTF
7.367
MECLTFEXP_MEC->PJM
CLTF
10.609
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
SIGELTFEXP_SIGE->PJM
CLTF
0.348
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1287.39
MW Contribution:
4.93
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Helper
4.334
316044AC1-158 PL1
Solar/Wind Helper
1.97
316045AC1-158 PL2
Solar/Wind Helper
6.303
316450AC1-158 RIC
Solar/Wind Helper
0.525
270399AC1-101 GEN
Solar/Wind Harmer
1.311
270400AC1-102 GEN
Solar/Wind Harmer
1.311
270173AC1-122 GEN
Solar/Wind Helper
2.227
270583AD2-179 GEN
Solar/Wind Harmer
9.325
270494AE1-108_GEN
Solar/Wind Helper
4.907
270346AE1-212 GEN
Solar/Wind Harmer
6.24
270030AE2-140 GEN
Solar/Wind Harmer
12.937
270069AE2-166 C O1
Solar/Wind Harmer
6.298
943031AE2-326 GEN
Solar/Wind Harmer
9.004
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.113
970281AG2-184 GEN
Solar/Wind Harmer
12.222
970417AG2-272 GEN
50/50
6.208
970563AG2-360 GEN
50/50
34.746
970823AG2-518 GEN
50/50
14.377
970913AG2-568 GEN
Solar/Wind Harmer
4.564
971225AH1-072 GEN
Solar/Wind Harmer
1.258
971227AH1-073 GEN
Solar/Wind Harmer
1.258
971277AH1-098 GEN
Solar/Wind Harmer
3.493
971277AH1-098 GEN
Solar/Wind Harmer
3.175
971313AH1-133 GEN
Solar/Wind Harmer
4.935
971329AH1-144 GEN
Solar/Wind Harmer
5.883
971331AH1-145 GEN
Solar/Wind Harmer
12.93
971403AH1-188 GEN
Solar/Wind Harmer
8.284
971461AH1-227 GEN
Solar/Wind Harmer
3.227
971531AH1-263 GEN
50/50
Charging
20.247
971543AH1-269 GEN
50/50
8.605
971687AH1-348 GEN
Solar/Wind Harmer
0.625
941621AE2-160 GEN
50/50
5.101
966391AG1-508 GEN
Solar/Wind Harmer
7.844
971981AH1-535 GEN
Solar/Wind Harmer
5.078
971981AH1-535 GEN
Solar/Wind Harmer
5.54
972103AH1-617 GEN
Solar/Wind Harmer
11.64
958121AF2-106 GEN
Solar/Wind Harmer
0
971881AH1-461 GEN
50/50
11.002
972293SS25-0014
50/50
Charging
48.638
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.36
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.018
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.535
NYPJM->LTFIMP_NY
CLTF
1.636
LGEELTFEXP_LGEE->PJM
CLTF
4.537
WECLTFEXP_WEC->PJM
CLTF
2.291
CPLELTFEXP_CPLE->PJM
CLTF
3.149
TVALTFEXP_TVA->PJM
CLTF
7.32
MECLTFEXP_MEC->PJM
CLTF
10.492
LAGNLTFEXP_LAGN->PJM
CLTF
13.848
SIGELTFEXP_SIGE->PJM
CLTF
0.344
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.744
AG2-052LTFEXP_AG2-052->PJM
LTF
0.138
AH1-155LTFEXP_AH1-155->PJM
LTF
0.207
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 547T566_SRT-L'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1                /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1                /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1                /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                                /*8LEXINGTN SC 500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 247669 CKT 1   /*05JOSHUA     765.0 - 05JOSHUA 1EQ   1.0
 OPEN BRANCH FROM BUS 242688 TO BUS 247670 CKT 1   /*05JOSHUA     138.0 - 05JOSHUA_XFL 138.0
 OPEN BRANCH FROM BUS 247669 TO BUS 247670 CKT 1   /*05JOSHUA 1EQ   1.0 - 05JOSHUA_XFL 138.0
END
CONTINGENCY 'AEP_P7-1_#17030___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
END
CONTINGENCY 'AEP_P7-1_#17029___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1   /*05MOSELEY    138.0 - 05REUSENS1   138.0
END
CONTINGENCY 'AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242561 TO BUS 242765 CKT 1    /*05BOONSBORO  138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242719 TO BUS 242765 CKT 1    /*05MONEL      138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1    /*05MOSELEY    138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242882 CKT 4    /*05REUSENS1   138.0 - 05REUSENS     69.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242889 CKT 1    /*05REUSENS1   138.0 - 05REUSENS     34.5
 OPEN BRANCH FROM BUS 242765 TO BUS 246229 CKT Z1   /*05REUSENS1   138.0 - 05REUSENS2   138.0
 REMOVE SWSHUNT FROM BUS 242765                     /*05REUSENS1   138.0
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-360, AH1-072, AH1-073, AH1-133, AH1-188, AH1-227 and AH1-535 in PJM Transition Cycle 2, Cluster 29 are listed in Table 1. below. This report will cover the dynamic analysis of Cluster 29 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 29 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

Cluster 29 projects were dispatched for stability analysis according to the following scenarios:

       a)       Scenario 1: AH1-535 dispatched at full MFO injection at the POI with PV MW contribution maxed out and no/reduced MW contribution from BESS.

       b)       Scenario 2: AH1-535 dispatched at full MFO injection at the POI with BESS MW contribution maxed out, and no/reduced PV MW injection.

       c)       Scenario 3: AH1-535 dispatched at full MFO injection at the POI with PV and BESS MW contribution proportional to their capacity.

       d)       Scenario 4: AH1-535 dispatched to full capacity with PV and BESS MW injection maxed out.

 

This report describes a dynamic simulation analysis of TC2 Cluster 29 for dispatch Scenario 3 as part of the overall system impact study.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 29 projects have been dispatched online at maximum power output, with 1.0 voltage at the terminal bus.

 

Transition Cycle 2 Cluster 29 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);

       f)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 29 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 peak load case:

       a)       Cluster 29 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 29 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

The IPCMD and IQCMD states in the REGCA1 models of all units of Cluster 29 showed erratic behavior for some contingencies in which queue project has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

Fictitious frequency response at AH1-227 generator bus tripped the queue project for several contingencies. Therefore, the frequency relay pickup times for instance 97146111 was set to 20 seconds to avoid fictitious frequency tripping of the unit.

 

High voltage spikes occurred in the simulations immediately after fault clearing for some of the contingencies studied which tripped the AC1-101 and AC1-102 units. The voltage spike is a known artifact of the WECC generic renewable models as stated in the WECC Solar Plant Dynamic Model Guidelines: “It should be noted that generic dynamic models for inverter-based generator tend to produce a short-duration (a cycle or shorter) voltage spike at fault inception and clearing. These spikes should be ignored in most cases, as they do not represent the performance of actual hardware. They are simply a consequence of the model’s limited bandwidth, integration time step, and the way current injection models interface with the network solution.”  A single cycle delay was added to the instantaneous over-voltage relays to avoid this fictitious over voltage tripping issue.

 

Similarly, under contingency P5.44, AH1-535 GEN1 tripped due to activation of its overvoltage protection. The issue was resolved by reducing its Vsched to 0.99 pu for this contingency.

 

AH1-227 generating unit exhibited slow active power recovery within the 20 second simulation window for contingency P1.11. This issue did not cause instability in the system,

 

however, the facility’s performance could be improved through model tuning, which can be evaluated in TC2 Phase 3 if active power recovery becomes a critical concern.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 29 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-360

Battery

AEP

250

Broadford substation 138 kV

AH1-072

Solar

AEP

20

Red Onion – VC5 69 kV

AH1-073

Solar

AEP

20

Red Onion – VC5 69 kV

AH1-133

Solar

AEP

70

Saltville – Tazewell 138 kV

AH1-188

Solar

AEP

140

Pigeon Creek substation 138 kV

AH1-227

Solar

AEP

51.3

Flemming - Fremont 69 kV

AH1-535

Solar/Battery

AEP

100

Nagel – Cane River 230 kV

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AH1-133 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVEngineering & Procurement
AC1-214Crescent RidgeIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-029Circleville 138kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-176Jay 138 kVIn Service
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVWithdrawn
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-143Marion County 161 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-175Light Foot 34.5 kVIn Service
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVSuspended
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-089Pennville-Adams 138 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVUnder Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AF1-014Harmony Village-Shackleford 115 kVSuspended
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-038Sewellton Jct-Webbs Crossroads 69 kVUnder Construction
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-090Kincaid-PanaEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVWithdrawn
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-404Gladys DP-Stonemill 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVUnder Construction
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-124Riverville - Gladstone 138 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-152Remington CT 230 kVEngineering & Procurement
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-471Up Church-Wayne County 69 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-508Point Lookout 69 kVWithdrawn
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-088Midlothian 230 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-230Dumont 345 kVActive
AG2-240Old Church 34.5 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-272Berry Hill 138 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-424Summersville - Magnolia 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-269Claytor 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-348Pound 34.5 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-461Buckhorn 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
V3-007Desoto-Tanners Creek #1 345kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
Y1-049Wurno 34.5kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AH1-133 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
AEPn9770.005ATKINS 138.0 kV to 05RURALR 138.0 kV ckt 1 - Sag StudyContingent$0N/A
AEPn9783.005BROADX 138.0 kV to 05SMYTH 138.0 - Replace station conductorContingent$0N/A
AEPs2572.3Rebuild ~21 miles of the 138KV line between Saltville and Tazewell stationsContingent$0N/A
Grand Total:$0

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9770.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9770.0 / AEP-TC2-19071
Title
05ATKINS 138.0 kV to 05RURALR 138.0 kV ckt 1 - Sag Study
Description
Sag Study Rural Retreat Loop 138 kV line from Str. 226-203 to Rural Retreat station.
Total Cost ($USD)
$500,000
Discounted Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 24 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-133 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-133 could receive cost allocation. Although AH1-133 may not presently have cost responsibility for this upgrade, AH1-133 may need this upgrade in-service to be deliverable to the PJM system. If AH1-133 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05ATKINS-05RURALR 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A251.0 MVA
(All)B330.0 MVA

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9783.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9783.0 / AEP-TC2-19115
Title
05BROADX 138.0 kV to 05SMYTH 138.0 - Replace station conductor
Description
Station conductor between Broadford and Broadford reactor towards Smyth needs to be replaced
Total Cost ($USD)
$100,000
Discounted Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 30 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-133 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-133 could receive cost allocation. Although AH1-133 may not presently have cost responsibility for this upgrade, AH1-133 may need this upgrade in-service to be deliverable to the PJM system. If AH1-133 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05BROADF-05BROADX 138.0 kV Ckt ZB line(Any)
Rating SetRating TypeRating Value
LLA246.0 MVA
LLB327.0 MVA
SUMA246.0 MVA
SUMB327.0 MVA
WINA311.0 MVA
WINB371.0 MVA
05BROADX-05SMYTH 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA246.0 MVA
LLB327.0 MVA
SUMA246.0 MVA
SUMB327.0 MVA
WINA311.0 MVA
WINB371.0 MVA

System Reinforcement: n9769.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9769.0 / AEP-TC2-19070
Title
05CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBs
Description
Upgrade/replace Cloverdale 765 kV, 4000 A CBs "CC" and "CC2" to 5000 A
Total Cost ($USD)
$25,000,000
Discounted Total Cost ($USD)
$25,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-133 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-133 could receive cost allocation. Although AH1-133 may not presently have cost responsibility for this upgrade, AH1-133 is a potential Aggregate Pool Contributor.

FacilityContingency
05CLOVRD-05CLOVRD_RJA 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: n9763.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9763.0 / AEP-TC2-19060
Title
05J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace Wavetraps
Description
Replace wave trap on 765 kV Cloverdale line. Replace/upgrade CB's B and B2 with 5000A CBs.
Total Cost ($USD)
$3,300,000
Discounted Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-133 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-133 could receive cost allocation. Although AH1-133 may not presently have cost responsibility for this upgrade, AH1-133 is a potential Aggregate Pool Contributor.

FacilityContingency
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: s2572.3
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2572.3
Title
Rebuild ~21 miles of the 138KV line between Saltville and Tazewell stations
Description
Rebuild ~21 miles of the 138KV line between Saltville and Tazewell stations
Cost Information
Time Estimate
Sep 02 2036

Contingent

Note: Although AH1-133 may not presently have cost responsibility for this upgrade, AH1-133 may need this upgrade in-service to be deliverable to the PJM system. If AH1-133 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05TAZEWE-AH1-133 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA296.0 MVA
LLB413.0 MVA
SUMA296.0 MVA
SUMB413.0 MVA
WINA375.0 MVA
WINB464.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-133 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-133 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-133


AH1-133 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-133 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-133 One Line Diagram

AH1-133 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.