AH1-263 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:49

Chancellor 115 kV

200.0 MW Capacity / 200.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Scarlet Energy Storage LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $18,009,366 $14,704,615 = 1.22 AND ( $18,009,366 - $14,704,615 ) 200.0 = $16,524 per MW

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Spotsylvania County, Virginia. The installed facilities will have a total capability of 200.0 MW with 200.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-263
Project Name:
Chancellor 115 kV
Project Developer Name:
Scarlet Energy Storage LLC
State:
Virginia
County:
Spotsylvania
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
200.0
MWE:
200.0
MWC:
200.0
Battery Storage Specification:
800.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-263 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system at the Chancellor 115 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-263 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-263Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$4,333,155$0$0
Other Scope$483,290$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$18,009,366$18,009,366$18,009,366
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$22,825,811$18,009,366$18,009,366

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-263

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-263
Project ID: AH1-263
20% of cost allocation for Phase II Network Upgrades:(A) $3,601,873
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $2,701,161
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $900,712
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Add one new line position and two new 115kV breakers installed at Chancellor Substation.

$11,824,317$3,522,287$2,477,584$185,178$18,009,366$18,009,366
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

This scope includes metering accuracy coupling capacitor voltage transformers (CCVT), metering accuracy current transformers (CT) and associated equipment.

$322,219$33,939$121,390$5,742$483,290$483,290
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Portion of the interconnection switching station soley associated with the single feed to the generating facilities collector station including disconnect switch, conductors and connectors.

$3,347,000$661,737$252,696$71,722$4,333,155$4,333,155
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$22,825,811$22,825,811
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 36 to 37 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-263 was evaluated as a 200.0 MW (200.0 MW Capacity) injection in the Dominion area.

AH1-263 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (200.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: 545T594_SRT-S
BreakerAC120.94 %3966.0C4796.52
71.76
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC119.54 %4070.2B4865.39
86.34
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC113.04 %4070.2B4600.84
73.13
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC109.1 %5010.0C5465.85
86.44
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC109.02 %5010.0C5461.82
86.43
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: 515T594_SRT-S
BreakerAC109.01 %5010.0C5461.43
86.34
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: H1T573_SRT-S
BreakerAC106.65 %5010.0C5342.95
86.59
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC121.15 %3220.44B3901.64
38.56
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC117.91 %3940.0C4645.47
39.67
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: H3T552_SRT-S
BreakerAC110.65 %3940.0C4359.44
38.58
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC110.56 %3940.0C4356.04
38.56
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC102.14 %3099.0B3165.31
25.52
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC175.64 %3118.0C5476.52
58.97
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC161.05 %3220.44B5186.56
60.36
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC147.64 %3940.0C5817.13
60.36

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.94 %
Rating:3966.0 MVA
Rating Type:C
MVA to Mitigate:4796.52
MW Contribution:
71.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150381LDYSMT2
50/50
27.974
3151201GRAVEL4
Adder
13.845
3151221GRAVEL6
Adder
13.83
3151211GRAVEL5
Adder
13.67
3142433PROV 92
Adder
0.368
3142433PROV 92
Adder
0.368
316311AC2-079 GEN
Solar/Wind Harmer
10.545
316059AD1-063 C
Solar/Wind Harmer
0.469
313526AB2-022
Solar/Wind Harmer
0.557
3146396TANGLEW
Solar/Wind Harmer
0.379
315814AE2-033 C
Solar/Wind Harmer
18.812
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.019
316318V4-068
Solar/Wind Harmer
0.468
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316486AD2-202 GEN
Solar/Wind Harmer
0.443
316274AC1-208 GEN
Solar/Wind Harmer
1.86
961791AG1-021 GEN
Solar/Wind Harmer
2.057
3150371LDYSMT1
50/50
28.156
315051AA1-145 CT1
50/50
1.62
966881AG1-559 GEN
Solar/Wind Harmer
0.691
3142416OLDCHRC
Solar/Wind Harmer
2.274
3142946ENON
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
2.353
970133AG2-095 GEN
Solar/Wind Harmer
2.448
315813AE1-149 C
Solar/Wind Harmer
13.31
3145336SMITFLD
Solar/Wind Harmer
-0.008
3142433PROV 92
Adder
0.368
3142433PROV 92
Adder
0.368
316017AA1-139 ULT1
Solar/Wind Harmer
1.69
3146456SLIGO L269
Solar/Wind Harmer
-0.021
971153AH1-033 GEN
Solar/Wind Harmer
2.419
3141766HARMONY
Solar/Wind Harmer
1.853
3145273HOLLAND
Solar/Wind Harmer
-0.015
3146376EDENTON
Solar/Wind Harmer
-0.02
961951AG1-038 GEN
Solar/Wind Harmer
2.576
3146206CASHIE
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
971781AH1-399 GEN
Solar/Wind Harmer
1.14
316181AB2-040 GEN
Solar/Wind Harmer
2.53
3147043LAWRENC
Solar/Wind Harmer
-0.011
316478AD1-087 GEN
Solar/Wind Harmer
1.514
316420AA1-050 GEN
Solar/Wind Harmer
1.893
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
959311AF2-222 GEN
Solar/Wind Harmer
17.217
3138543CONSLDL
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.051
972255AH1-712 GEN
Adder
70.069
3150411LDYSMT5
50/50
29.23
972215AH1-692 GEN
50/50
4.732
316164AC1-076 GEN
Solar/Wind Harmer
1.969
316233AE1-074 FULL
Solar/Wind Harmer
0.599
971283AH1-107 GEN
Solar/Wind Harmer
3.619
3151191GRAVEL3
Adder
13.67
3138283WHITEMARSH
Solar/Wind Harmer
0.033
316018AA1-139 ULT2
Solar/Wind Harmer
1.789
315833AF1-017_GEN
Solar/Wind Harmer
3.97
3146406KITTY HAWK
Solar/Wind Harmer
0.017
957601AF2-054 GEN
Solar/Wind Harmer
0.617
315800Z1-036_GEN1
Solar/Wind Harmer
4.934
971967AH1-528 GEN
Solar/Wind Harmer
36.918
315732AD1-074 GEN1
Solar/Wind Harmer
3.845
3145893MURPHYS
Solar/Wind Harmer
-0.05
3145893MURPHYS
Solar/Wind Harmer
-0.019
970085AG2-068 GEN
Solar/Wind Harmer
11.676
3141813NORNECK
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.299
3145513AHOSKIE
Solar/Wind Harmer
0.161
3145513AHOSKIE
Solar/Wind Harmer
-0.018
315652AC1-086 GEN
Solar/Wind Harmer
20.352
3137643SOCKMAN
Solar/Wind Harmer
-0.072
316426AA2-053 GEN
Solar/Wind Harmer
1.817
316174AB2-169 GEN
Solar/Wind Harmer
2.772
316327AA2-057 GEN
Solar/Wind Harmer
1.693
3144303KENBRDG
Solar/Wind Harmer
-0.013
946301AF1-294 GEN
Solar/Wind Harmer
4.216
971531AH1-263 GEN
50/50
71.761
972213AH1-691 GEN
50/50
4.732
971281AH1-106 GEN
Solar/Wind Harmer
3.619
316382AG1-145 C
Solar/Wind Harmer
0.65
316159AE1-175 C
Solar/Wind Harmer
0.579
3143316POE
Solar/Wind Harmer
-0.084
316236AE1-162_GEN
Solar/Wind Harmer
0.64
970657AG2-426 GEN
Solar/Wind Harmer
1.331
3143873LANEXA
Solar/Wind Harmer
-0.012
316044AC1-158 PL1
Solar/Wind Harmer
2.793
3143226MDLTHAN
Solar/Wind Harmer
-0.022
3143096IRON208
Adder
0.826
3142543TWELFTH
Solar/Wind Harmer
-0.002
971069AG2-661 GEN
Solar/Wind Harmer
3.416
316369SG1_INVT
Solar/Wind Harmer
3.842
961611AG1-000B GEN
Solar/Wind Harmer
10.58
3138126ROCKLANDING
Solar/Wind Harmer
0.066
3151171GRAVELC
Adder
2.023
3150981CHESPKA
Adder
2.35
316381AD1-082 GEN
Solar/Wind Harmer
1.934
319010AE1-072 C
Solar/Wind Harmer
4.215
315662AE1-191 GEN
Solar/Wind Harmer
2.493
316280AD1-041 GEN
Solar/Wind Harmer
1.558
3138133OCRAN
Solar/Wind Harmer
-0.012
315611Z1-036_GEN2
Solar/Wind Harmer
4.934
3130156CHOWAN
Solar/Wind Harmer
-0.02
315816AE2-034 GEN
Solar/Wind Harmer
1.569
971163AH1-040 GEN
Solar/Wind Harmer
18.23
316404AE1-155 C
Solar/Wind Harmer
3.672
3147666LOUISA
Solar/Wind Harmer
-0.076
315737AD1-076 GEN
Solar/Wind Harmer
3.615
970087AG2-069 GEN
Solar/Wind Harmer
17.514
316087AB2-174 GEN
Solar/Wind Harmer
2.595
957481AF2-042 GEN
Solar/Wind Harmer
56.755
315693AD1-088 GEN
Solar/Wind Harmer
8.927
3146293MARTNCO
Solar/Wind Harmer
0.108
3146233WITAKRS
Solar/Wind Harmer
-0.065
3145493TOT1
Solar/Wind Harmer
0.49
315785AD2-033 C
Solar/Wind Harmer
3.735
970685AG2-442 GEN
Solar/Wind Harmer
14.408
971563AH1-280 GEN
Solar/Wind Harmer
2.057
3146926FARMVIL
Solar/Wind Harmer
-0.01
3151751LOISA D
Adder
7.344
3152261N ANNA2
50/50
11.686
3150401LDYSMT4
50/50
29.139
3150861SPRUNCD
Adder
0.91
3143096IRON208
Adder
0.826
3143096IRON208
Adder
0.81
316458AB2-190 GEN2
Solar/Wind Harmer
2.184
961611AG1-000B GEN
Solar/Wind Harmer
4.514
3141873WAN 176
Solar/Wind Harmer
-0.004
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
970533AG2-339 GEN
Solar/Wind Harmer
13.63
3138133OCRAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
316405AF2-144 C
Solar/Wind Harmer
0.495
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
315733AD1-074 GEN2
Solar/Wind Harmer
3.845
970601AG2-382 GEN
Solar/Wind Harmer
8.25
970581AG2-369 GEN
Solar/Wind Harmer
10.042
946281AF1-292 GEN
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.07
972205AH1-687 GEN
Adder
5.728
3151171GRAVELC
Adder
2.661
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
4.266
316246AF1-032 C
Solar/Wind Harmer
0.421
3141843SHACKLE
Adder
0.946
3141873WAN 176
Solar/Wind Harmer
2.449
316321Z2-027
Solar/Wind Harmer
0.554
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3147666LOUISA
Solar/Wind Harmer
-0.044
3156081AA2-088 GEN
Solar/Wind Harmer
6.175
970917AG2-570 GEN
Solar/Wind Harmer
47.267
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316190AA2-174 GEN
Solar/Wind Harmer
0.221
3145933PARMELE
Solar/Wind Harmer
-0.017
3141906WESTMOR
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.346
3146233WITAKRS
Solar/Wind Harmer
-0.011
970257AG2-171 GEN
Solar/Wind Harmer
6.188
971775AH1-396 GEN
Solar/Wind Harmer
1.164
3146926FARMVIL
Solar/Wind Harmer
-0.01
972195AH1-682 GEN
50/50
3.822
972189AH1-679 GEN
50/50
3.638
316450AC1-158 RIC
Solar/Wind Harmer
0.745
315673AE1-157 GEN
Solar/Wind Harmer
17.251
3150681DARBY 2
Adder
14.269
316033AB2-134 GEN
Solar/Wind Harmer
6.938
3145506HICKORY
Solar/Wind Harmer
-0.084
3142366NRTHEST
50/50
0.692
3150691DARBY 3
Adder
14.319
3150701DARBY 4
Adder
14.286
315976AC1-164 GENA
Solar/Wind Harmer
4.995
316169AC1-164_GENC
Solar/Wind Harmer
4.316
3142946ENON
Solar/Wind Harmer
-0.002
316294AC1-161 GEN
Solar/Wind Harmer
6.91
316083AB2-161 GEN
Solar/Wind Harmer
3.43
971507AH1-251 GEN
50/50
14.479
972197AH1-683 GEN
50/50
4.55
316447AC1-158 HLD
Solar/Wind Harmer
6.144
966881AG1-559 GEN
Solar/Wind Harmer
0.237
3142416OLDCHRC
Solar/Wind Harmer
-0.058
3142416OLDCHRC
Solar/Wind Harmer
-0.022
315975AC1-164 GENB
Solar/Wind Harmer
0.148
970293AG2-193 GEN
Solar/Wind Harmer
2.783
3150921YORKTN3
Adder
4.789
3144536CHRHLND
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
96.244
3142956BIRDNECK
Solar/Wind Harmer
1.132
316305AF2-043 C
Solar/Wind Harmer
0.627
316203AE2-005 GEN
Solar/Wind Harmer
8.774
316320Y1-086
Solar/Wind Harmer
1.211
3146516WINFALL
Solar/Wind Harmer
-0.02
944011AF1-069 GEN
Solar/Wind Harmer
11.908
315735AD1-075 GEN1
Solar/Wind Harmer
1.922
3145893MURPHYS
Solar/Wind Harmer
0.131
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146263WOODLND
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
316011AB1-132 GEN
Solar/Wind Harmer
3.778
316223AC1-118
Solar/Wind Harmer
0.447
961601AG1-000A GEN
Solar/Wind Harmer
5.629
3145336SMITFLD
Solar/Wind Harmer
-0.085
3142433PROV 92
Solar/Wind Harmer
-0.085
3142433PROV 92
Adder
0.368
3142433PROV 92
Adder
0.368
316375AC2-012 GEN
Solar/Wind Harmer
7.314
3146456SLIGO L269
Solar/Wind Harmer
-0.021
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.429
3145663CRESWEL
Solar/Wind Harmer
-0.054
958261AF2-120 GEN
Solar/Wind Harmer
7.454
3146206CASHIE
Solar/Wind Harmer
-0.019
316023GEN1_S
Solar/Wind Harmer
1.266
316192AB2-158 GEN
Solar/Wind Harmer
2.231
3146173TUNIS
Solar/Wind Harmer
-0.019
3156021HOLLOMANSOL
Solar/Wind Harmer
2.497
3145683EARLEYS
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.434
970937AG2-583 GEN
Solar/Wind Harmer
12
316131AB2-060 GEN
Solar/Wind Harmer
1.781
316319Z2-044 C
Solar/Wind Harmer
0.912
3146083TARBORO
Solar/Wind Harmer
-0.016
316349AD2-085 GEN
Solar/Wind Harmer
1.856
3146456SLIGO L269
Solar/Wind Harmer
2.468
3146386ELIZ CT
Solar/Wind Harmer
-0.021
316431W1029_GEN1
Solar/Wind Harmer
3.709
316433W1029_GEN2
Solar/Wind Harmer
3.709
315742AE1-103 GEN
Solar/Wind Harmer
4.742
3146376EDENTON
Solar/Wind Harmer
0.59
3146376EDENTON
Solar/Wind Harmer
0.59
970933AG2-581 GEN
Solar/Wind Harmer
18.083
316365GEN2_N
Solar/Wind Harmer
1.266
316336AC2-165 C
Solar/Wind Harmer
11.627
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
958211AF2-115 GEN
Solar/Wind Harmer
2.571
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3147133PAMPLIN
Solar/Wind Harmer
-0.013
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.012
316339AD2-160 GEN
Solar/Wind Harmer
1.41
316388AE2-253 GEN
Solar/Wind Harmer
1.41
3137176SLIGO L2192
Solar/Wind Harmer
-0.083
3130086AYDLETT
Solar/Wind Harmer
-0.083
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
316487AF1-042 GEN
Solar/Wind Harmer
2.576
3150341NORNECKC1
Adder
1.739
3150341NORNECKC1
Adder
1.725
313506AB2-031 GEN
Solar/Wind Harmer
1.456
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
0.149
3145933PARMELE
Solar/Wind Harmer
-0.035
3145933PARMELE
Solar/Wind Harmer
-0.017
970301AG2-198 GEN
Solar/Wind Harmer
8.492
313527AB2-043 GEN
Solar/Wind Harmer
2.688
3145493TOT1
Solar/Wind Harmer
0.255
970323AG2-213 GEN
Solar/Wind Harmer
8.251
3151731LOISA B
Adder
7.344
3152251N ANNA1
50/50
11.68
315052AA1-145 CT2
50/50
1.63
3150851SPRUNCC
Adder
0.91
316132AB2-190 GEN1
Solar/Wind Harmer
2.184
315773AC2-141 GEN
Solar/Wind Harmer
8.941
316036AC1-147 C
Solar/Wind Harmer
0.569
316093AE2-104_GEN
Solar/Wind Harmer
6.036
3146516WINFALL
Solar/Wind Harmer
-0.066
3146516WINFALL
Solar/Wind Harmer
-0.02
962861AG1-135 GEN
Solar/Wind Harmer
7.246
3141726DUNNSVL
Solar/Wind Harmer
-0.075
970919AG2-571 GEN
Solar/Wind Harmer
5.983
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.557
315607AA1-063A GEN
Solar/Wind Harmer
1.848
3146263WOODLND
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
316337AD2-073 GEN
Solar/Wind Harmer
0.474
316494AC1-189 GEN
Solar/Wind Harmer
1.803
961671AG1-007 GEN
Solar/Wind Harmer
0.209
3142296MT RD221
50/50
0.687
316045AC1-158 PL2
Solar/Wind Harmer
8.938
3150671DARBY 1
Adder
14.253
971223AH1-071 GEN
Solar/Wind Harmer
2.779
966871AG1-558 GEN
Solar/Wind Harmer
0.657
966871AG1-558 GEN
Solar/Wind Harmer
0.225
316240AF1-291 C
Solar/Wind Harmer
0.654
3150991CHESPKB
Adder
1.972
3150991CHESPKB
Adder
1.924
315835AF2-110_GEN
Solar/Wind Harmer
2.595
315666AE1-190 GEN
Solar/Wind Harmer
0.623
316156AD2-030 GEN
Solar/Wind Harmer
0.549
316435W1029_GEN3
Solar/Wind Harmer
3.709
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
972187AH1-678 GEN
Adder
4.959
315614AA2-178 GEN
Solar/Wind Harmer
2.092
316313AB2-026
Solar/Wind Harmer
0.521
316065AD1-022 GEN
Solar/Wind Harmer
9.464
3145893MURPHYS
Solar/Wind Harmer
0.524
3145893MURPHYS
Solar/Wind Harmer
-0.034
316140AB2-099
Solar/Wind Harmer
0.125
316005AA1-067
Solar/Wind Harmer
0.344
3145453TOT5
Solar/Wind Harmer
0.153
972193AH1-681 GEN
Adder
3.131
961601AG1-000A GEN
Solar/Wind Harmer
5.558
971285AH1-108 GEN
Adder
1.489
315839AE2-212 C
Solar/Wind Harmer
0.649
315697AD1-025 GEN
Solar/Wind Harmer
4.348
971445AH1-216 GEN
Solar/Wind Harmer
13.18
3151081ELIZAR1
Adder
17.26
3151091ELIZAR2
Adder
16.96
316316AC1-027 C
Solar/Wind Harmer
0.647
957831AF2-077 GEN
Solar/Wind Harmer
0.633
957871AF2-081 GEN
Solar/Wind Harmer
10.472
3141913WHIT STONE
Solar/Wind Harmer
-0.02
970673AG2-436 GEN
Solar/Wind Harmer
43.914
316258AE1-075 C
Solar/Wind Harmer
0.469
316468AD1-105 GEN
Solar/Wind Harmer
2.114
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
2.728
970831AG2-522 GEN
Solar/Wind Harmer
8.603
3145746EVERETS
Solar/Wind Harmer
-0.067
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
957861AF2-080 GEN
Solar/Wind Harmer
7.33
316238AB2-078_GEN
Solar/Wind Harmer
0.497
316239AB2-077_GEN
Solar/Wind Harmer
0.497
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
970683AG2-441 GEN
Solar/Wind Harmer
11.637
970681AG2-440 GEN
Solar/Wind Harmer
7.724
316075AC2-137 C
Solar/Wind Harmer
0.596
315778AD1-151 GEN
Solar/Wind Harmer
19.214
3144216WINCHST
Adder
0.719
944601AF1-125 GEN
Solar/Wind Harmer
94.742
3151101ELIZAR3
Adder
17.481
316484AD2-074 GEN
Solar/Wind Harmer
4.923
3143336POWHATN
Solar/Wind Harmer
1.954
316077AC2-138 C
Solar/Wind Harmer
0.393
3150351NORNECKC2
Adder
1.684
966621AG1-532 GEN
Solar/Wind Harmer
0.373
316317KELFORD C
Solar/Wind Harmer
0.836
3145823KELFORD
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.018
316212AC1-099_GEN
Solar/Wind Harmer
1.516
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
315722AD1-056 GEN
Solar/Wind Harmer
6.025
964241AG1-285 GEN
Solar/Wind Harmer
12.92
3144293JTRSVLE
Adder
0.35
942461AE2-259 GEN
Solar/Wind Harmer
2.464
3151761LOISA E
Adder
14.972
3151721LOISA A
Adder
7.306
3141196NOKESVL
Solar/Wind Helper
1.311
972219AH1-694 GEN
50/50
3.276
3143526WINTERP
Solar/Wind Harmer
-0.115
944631AF1-128 GEN
Adder
93.221
315671AE2-027_GEN
Solar/Wind Harmer
3.904
971317AH1-138 GEN
Solar/Wind Harmer
2.674
944591AF1-124 GEN
Solar/Wind Harmer
96.591
939411AE1-173 GEN
Solar/Wind Harmer
105.13
940641AE2-051 GEN
Solar/Wind Harmer
19.697
316072AD1-144
Solar/Wind Harmer
0.423
316314AB2-024 C
Solar/Wind Harmer
1.789
941031AE2-094 GEN
Solar/Wind Harmer
38.003
3143336POWHATN
Solar/Wind Harmer
2.299
964211AG1-282 GEN
Solar/Wind Harmer
0.57
971547AH1-271 GEN
Solar/Wind Harmer
4.715
3150351NORNECKC2
Adder
1.656
960081AF2-299 GEN
Solar/Wind Harmer
2.066
3145823KELFORD
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.018
316129AC1-054 GEN
Solar/Wind Harmer
1.496
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
8.517
316034AC1-036 C
Solar/Wind Harmer
0.305
3144293JTRSVLE
Adder
0.35
3144293JTRSVLE
Adder
0.276
972277AH1-723 GEN
Adder
81.652
3150391LDYSMT3
50/50
29.085
316312AB1-027
Solar/Wind Harmer
0.758
3143526WINTERP
Solar/Wind Harmer
-0.115
944641AF1-129 GEN
Adder
92.575
316185AD1-033 GEN
Solar/Wind Harmer
2.219
316441AF1-014 GEN
Solar/Wind Harmer
1.403
3144356SAPONY
Solar/Wind Harmer
0.707
316315AB2-025 C
Solar/Wind Harmer
0.545
972185AH1-677 GEN
Adder
9.88
970099AG2-077 GEN
Solar/Wind Harmer
22.702
962571AG1-106 GEN
Solar/Wind Harmer
2.601
3145783HORNRTN
Solar/Wind Harmer
2.117
3145783HORNRTN
Solar/Wind Harmer
1.694
3145783HORNRTN
Solar/Wind Harmer
0.529
3145783HORNRTN
Solar/Wind Harmer
0.212
3145796HORNRTN
Solar/Wind Harmer
-0.053
315724AD1-057 GEN
Solar/Wind Harmer
3.314
315687AD1-152 GEN
Solar/Wind Harmer
1.995
316237AB2-079_GEN
Solar/Wind Harmer
0.497
3145603CNETO
Solar/Wind Harmer
0.102
3144293JTRSVLE
Adder
0.35
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.963
LGEELTFEXP_LGEE->PJM
CLTF
1.264
MECLTFEXP_MEC->PJM
CLTF
3.37
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.103
NYPJM->LTFIMP_NY
CLTF
2.843
TVALTFEXP_TVA->PJM
CLTF
3.547
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.835
CPLELTFEXP_CPLE->PJM
CLTF
9.401
SIGELTFEXP_SIGE->PJM
CLTF
0.103
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.166
WECLTFEXP_WEC->PJM
CLTF
0.621
LAGNLTFEXP_LAGN->PJM
CLTF
6.998

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.54 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4865.39
MW Contribution:
86.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150381LDYSMT2
50/50
35.726
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3151201GRAVEL4
Adder
17.117
3151221GRAVEL6
Adder
17.097
3151211GRAVEL5
Adder
16.9
316311AC2-079 GEN
Solar/Wind Harmer
6.594
313526AB2-022
Solar/Wind Harmer
0.121
3146396TANGLEW
Solar/Wind Harmer
0.623
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
315814AE2-033 C
Solar/Wind Harmer
17.519
3146206CASHIE
Solar/Wind Harmer
0.206
3145683EARLEYS
Solar/Wind Harmer
0.403
3145683EARLEYS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.201
3146043SEABORD
Solar/Wind Harmer
0.201
316486AD2-202 GEN
Solar/Wind Harmer
0.194
316274AC1-208 GEN
Solar/Wind Harmer
0.972
961791AG1-021 GEN
Solar/Wind Harmer
1.708
971845AH1-439 GEN
Solar/Wind Harmer
7.683
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.102
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
971507AH1-251 GEN
50/50
17.357
972197AH1-683 GEN
50/50
5.811
316447AC1-158 HLD
Solar/Wind Harmer
3.325
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.647
3142416OLDCHRC
Solar/Wind Harmer
0.248
315975AC1-164 GENB
Solar/Wind Harmer
0.076
3142433PROV 92
Solar/Wind Harmer
0.943
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3145336SMITFLD
Solar/Wind Harmer
0.936
316375AC2-012 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.611
3150371LDYSMT1
50/50
35.958
315051AA1-145 CT1
50/50
2.024
3142416OLDCHRC
Solar/Wind Harmer
2.412
316473AC1-191 GEN
Solar/Wind Harmer
0.821
3142946ENON
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
2.301
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3145336SMITFLD
Solar/Wind Harmer
0.094
315813AE1-149 C
Solar/Wind Harmer
12.487
3141766HARMONY
Solar/Wind Harmer
3.088
316017AA1-139 ULT1
Solar/Wind Harmer
0.123
3146456SLIGO L269
Solar/Wind Harmer
0.229
971153AH1-033 GEN
Solar/Wind Harmer
2.653
3145273HOLLAND
Solar/Wind Harmer
0.166
3146376EDENTON
Solar/Wind Harmer
0.218
971781AH1-399 GEN
Solar/Wind Harmer
0.278
3146206CASHIE
Solar/Wind Harmer
0.206
3146173TUNIS
Solar/Wind Harmer
0.203
316181AB2-040 GEN
Solar/Wind Harmer
0.282
3147043LAWRENC
Solar/Wind Harmer
0.117
316478AD1-087 GEN
Solar/Wind Harmer
0.661
3146073TAR RVR
Solar/Wind Harmer
0.18
3146083TARBORO
Solar/Wind Harmer
0.18
3138543CONSLDL
Solar/Wind Harmer
0.118
959311AF2-222 GEN
Solar/Wind Harmer
15.874
3147133PAMPLIN
Solar/Wind Harmer
0.557
971623AH1-311 GEN
Solar/Wind Harmer
0.353
972255AH1-712 GEN
Adder
84.292
316222AC1-221 GEN
Solar/Wind Harmer
0.612
316283AC2-100 C
Solar/Wind Harmer
0.289
3150411LDYSMT5
50/50
37.33
972215AH1-692 GEN
50/50
6.043
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971283AH1-107 GEN
Solar/Wind Harmer
3.394
316164AC1-076 GEN
Solar/Wind Harmer
0.334
3151191GRAVEL3
Adder
16.9
3138283WHITEMARSH
Solar/Wind Harmer
0.054
970189AG2-124 GEN
Solar/Wind Harmer
6.859
3146406KITTY HAWK
Solar/Wind Harmer
0.029
971967AH1-528 GEN
Solar/Wind Harmer
34.357
3141813NORNECK
Solar/Wind Harmer
0.212
315732AD1-074 GEN1
Solar/Wind Harmer
1.188
3145893MURPHYS
Solar/Wind Harmer
0.555
3145893MURPHYS
Solar/Wind Harmer
0.205
970085AG2-068 GEN
Solar/Wind Harmer
10.883
316463AE2-346 GEN
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
0.423
3145513AHOSKIE
Solar/Wind Harmer
0.202
315652AC1-086 GEN
Solar/Wind Harmer
21.728
3137643SOCKMAN
Solar/Wind Harmer
0.787
316426AA2-053 GEN
Solar/Wind Harmer
0.658
316327AA2-057 GEN
Solar/Wind Harmer
0.27
3144303KENBRDG
Solar/Wind Harmer
0.143
946301AF1-294 GEN
Solar/Wind Harmer
3.51
3138216PACIFIC
Solar/Wind Helper
0.039
971531AH1-263 GEN
50/50
86.339
972213AH1-691 GEN
50/50
6.043
971281AH1-106 GEN
Solar/Wind Harmer
3.394
316159AE1-175 C
Solar/Wind Harmer
0.204
3143316POE
Solar/Wind Harmer
0.926
3143873LANEXA
Solar/Wind Harmer
0.14
970657AG2-426 GEN
Solar/Wind Harmer
1.704
3141873WAN 176
Solar/Wind Harmer
0.046
3146486SUNBURY
Solar/Wind Harmer
0.226
3146486SUNBURY
Solar/Wind Harmer
0.226
3138133OCRAN
Solar/Wind Harmer
0.068
3145176PASQUOTANK
Solar/Wind Harmer
0.14
970533AG2-339 GEN
Solar/Wind Harmer
16.767
3130156CHOWAN
Solar/Wind Harmer
0.218
3130156CHOWAN
Solar/Wind Harmer
0.218
3130546PLYMOUTH
Solar/Wind Harmer
0.209
315733AD1-074 GEN2
Solar/Wind Harmer
1.188
970601AG2-382 GEN
Solar/Wind Harmer
7.704
970581AG2-369 GEN
Solar/Wind Harmer
9.359
3146033SCOT NK
Solar/Wind Harmer
0.773
944491AF1-114 GEN
Solar/Wind Harmer
0
972205AH1-687 GEN
Adder
6.848
3147346CASHSCORNER
Solar/Wind Harmer
0.277
316044AC1-158 PL1
Solar/Wind Harmer
1.512
3143096IRON208
Adder
1.024
3143226MDLTHAN
Solar/Wind Harmer
0.244
3142543TWELFTH
Solar/Wind Harmer
0.023
971069AG2-661 GEN
Solar/Wind Harmer
4.226
3138126ROCKLANDING
Solar/Wind Harmer
0.108
961611AG1-000B GEN
Solar/Wind Harmer
12.373
3151171GRAVELC
Adder
2.502
3150981CHESPKA
Adder
2.901
316381AD1-082 GEN
Solar/Wind Harmer
0.236
319010AE1-072 C
Solar/Wind Harmer
1.144
3138133OCRAN
Solar/Wind Harmer
0.136
3130156CHOWAN
Solar/Wind Harmer
0.218
316404AE1-155 C
Solar/Wind Harmer
0
315816AE2-034 GEN
Solar/Wind Harmer
0.909
971163AH1-040 GEN
Solar/Wind Harmer
17.043
315737AD1-076 GEN
Solar/Wind Harmer
2.675
970087AG2-069 GEN
Solar/Wind Harmer
16.324
3147666LOUISA
Solar/Wind Harmer
0.803
957481AF2-042 GEN
Solar/Wind Harmer
52.774
315693AD1-088 GEN
Solar/Wind Harmer
9.325
3146293MARTNCO
Solar/Wind Harmer
0.176
3145493TOT1
Solar/Wind Harmer
0.799
3146233WITAKRS
Solar/Wind Harmer
0.715
315785AD2-033 C
Solar/Wind Harmer
1.446
970685AG2-442 GEN
Solar/Wind Harmer
13.298
971563AH1-280 GEN
Solar/Wind Harmer
1.897
3146926FARMVIL
Solar/Wind Harmer
0.106
971377AH1-170 GEN
Solar/Wind Harmer
1.61
3151751LOISA D
Adder
8.017
316254AC1-120 GEN1
Solar/Wind Harmer
4.309
3152261N ANNA2
50/50
14.393
3150401LDYSMT4
50/50
37.213
3143096IRON208
Adder
1.024
3143096IRON208
Adder
1.003
3150861SPRUNCD
Adder
1.126
316458AB2-190 GEN2
Solar/Wind Harmer
1.272
961611AG1-000B GEN
Solar/Wind Harmer
6.292
3151171GRAVELC
Adder
3.289
3144873MCLAUGH
Solar/Wind Harmer
0.006
970657AG2-426 GEN
Solar/Wind Harmer
5.208
3141843SHACKLE
Adder
1.183
3141873WAN 176
Solar/Wind Harmer
4.085
316246AF1-032 C
Solar/Wind Harmer
0.102
316321Z2-027
Solar/Wind Harmer
0.04
3146626S HERTFORD
Solar/Wind Harmer
0.222
3156081AA2-088 GEN
Solar/Wind Harmer
0
970917AG2-570 GEN
Solar/Wind Harmer
18.362
3147666LOUISA
Solar/Wind Harmer
0.462
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3141906WESTMOR
Solar/Wind Harmer
0.077
3145933PARMELE
Solar/Wind Harmer
0.19
3146233WITAKRS
Solar/Wind Harmer
0.902
3146233WITAKRS
Solar/Wind Harmer
0.122
970257AG2-171 GEN
Solar/Wind Harmer
5.718
971775AH1-396 GEN
Solar/Wind Harmer
0.286
3146926FARMVIL
Solar/Wind Harmer
0.106
972195AH1-682 GEN
50/50
4.881
972189AH1-679 GEN
50/50
4.546
316450AC1-158 RIC
Solar/Wind Harmer
0.403
315673AE1-157 GEN
Solar/Wind Harmer
17.965
3150681DARBY 2
Adder
17.693
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.924
3145506HICKORY
Solar/Wind Harmer
0.554
3145506HICKORY
Solar/Wind Harmer
0.139
316339AD2-160 GEN
Solar/Wind Harmer
0.368
316388AE2-253 GEN
Solar/Wind Harmer
0.716
3137176SLIGO L2192
Solar/Wind Harmer
0.913
3130086AYDLETT
Solar/Wind Harmer
0.916
3146626S HERTFORD
Solar/Wind Harmer
0.222
3146626S HERTFORD
Solar/Wind Harmer
0.222
3150341NORNECKC1
Adder
2.217
3150341NORNECKC1
Adder
2.199
313506AB2-031 GEN
Solar/Wind Harmer
0.608
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3145593CAROLNA
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.244
3145933PARMELE
Solar/Wind Harmer
0.379
3145933PARMELE
Solar/Wind Harmer
0.19
970301AG2-198 GEN
Solar/Wind Harmer
7.839
3145493TOT1
Solar/Wind Harmer
0.417
970323AG2-213 GEN
Solar/Wind Harmer
7.624
316049AB1-081 GEN
Solar/Wind Harmer
1.003
966001AG1-469 GEN
Solar/Wind Harmer
0.072
3151731LOISA B
Adder
8.017
3142366NRTHEST
50/50
0.857
3150691DARBY 3
Adder
17.755
3150701DARBY 4
Adder
17.714
315976AC1-164 GENA
Solar/Wind Harmer
2.554
316169AC1-164_GENC
Solar/Wind Harmer
2.207
3142946ENON
Solar/Wind Harmer
0.024
316294AC1-161 GEN
Solar/Wind Harmer
4.056
316349AD2-085 GEN
Solar/Wind Harmer
0.153
3146456SLIGO L269
Solar/Wind Harmer
4.061
3146386ELIZ CT
Solar/Wind Harmer
0.227
315742AE1-103 GEN
Solar/Wind Harmer
3.271
3146376EDENTON
Solar/Wind Harmer
0.969
3146376EDENTON
Solar/Wind Harmer
0.969
970933AG2-581 GEN
Solar/Wind Harmer
16.86
316365GEN2_N
Solar/Wind Harmer
0.458
3146173TUNIS
Solar/Wind Harmer
0.203
3146173TUNIS
Solar/Wind Harmer
0.203
316336AC2-165 C
Solar/Wind Harmer
10.224
958211AF2-115 GEN
Solar/Wind Harmer
2.135
3147133PAMPLIN
Solar/Wind Harmer
0.177
3147133PAMPLIN
Solar/Wind Harmer
0.142
3146843MT LREL
Solar/Wind Harmer
0.17
3146843MT LREL
Solar/Wind Harmer
0.17
3146456SLIGO L269
Solar/Wind Harmer
0.229
958261AF2-120 GEN
Solar/Wind Harmer
7.175
3145663CRESWEL
Solar/Wind Harmer
0.596
3146206CASHIE
Solar/Wind Harmer
0.206
316023GEN1_S
Solar/Wind Harmer
0.458
3146173TUNIS
Solar/Wind Harmer
0.203
3156021HOLLOMANSOL
Solar/Wind Harmer
0.914
3145683EARLEYS
Solar/Wind Harmer
0.201
316192AB2-158 GEN
Solar/Wind Harmer
1.103
3147043LAWRENC
Adder
1.757
3146083TARBORO
Solar/Wind Harmer
0.18
316131AB2-060 GEN
Solar/Wind Harmer
0.559
970937AG2-583 GEN
Solar/Wind Harmer
10.998
972135AH1-637 GEN
Solar/Wind Harmer
1.52
316359AB2-059 GEN
Solar/Wind Harmer
0.627
3142053HEARTS
Solar/Wind Harmer
0.311
970293AG2-193 GEN
Solar/Wind Harmer
2.622
3150921YORKTN3
Adder
5.932
3144536CHRHLND
Solar/Wind Harmer
0.035
944581AF1-123 GEN
Solar/Wind Harmer
52.325
316203AE2-005 GEN
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.224
944011AF1-069 GEN
Solar/Wind Harmer
13.354
315735AD1-075 GEN1
Solar/Wind Harmer
0.593
3145893MURPHYS
Solar/Wind Harmer
0.344
3145893MURPHYS
Solar/Wind Harmer
0.205
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.198
316011AB1-132 GEN
Solar/Wind Harmer
3.583
316223AC1-118
Solar/Wind Harmer
0.137
961601AG1-000A GEN
Solar/Wind Harmer
12.548
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.176
3146776BUCKING
Solar/Wind Harmer
0.061
970221AG2-151 GEN
Solar/Wind Harmer
8.049
3132273ORANGE
Solar/Wind Harmer
0.028
270494AE1-108_GEN
Solar/Wind Harmer
1.598
3150331BIRCHWDA
Adder
21.248
3142296MT RD221
50/50
0.852
316045AC1-158 PL2
Solar/Wind Harmer
4.839
3150671DARBY 1
Adder
17.672
971223AH1-071 GEN
Solar/Wind Harmer
2.602
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3150991CHESPKB
Adder
2.434
3150991CHESPKB
Adder
2.375
316156AD2-030 GEN
Solar/Wind Harmer
0.168
315835AF2-110_GEN
Solar/Wind Harmer
1.564
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
972187AH1-678 GEN
Adder
6.093
315614AA2-178 GEN
Solar/Wind Harmer
1.212
316313AB2-026
Solar/Wind Harmer
0.131
316065AD1-022 GEN
Solar/Wind Harmer
9.539
3145893MURPHYS
Solar/Wind Harmer
1.375
3145893MURPHYS
Solar/Wind Harmer
0.37
971285AH1-108 GEN
Adder
1.842
315697AD1-025 GEN
Solar/Wind Harmer
0.255
971445AH1-216 GEN
Solar/Wind Harmer
16.491
3151081ELIZAR1
Adder
21.305
3151091ELIZAR2
Adder
20.935
316316AC1-027 C
Solar/Wind Harmer
0.221
957871AF2-081 GEN
Solar/Wind Harmer
11.449
3141913WHIT STONE
Solar/Wind Harmer
0.227
970673AG2-436 GEN
Solar/Wind Harmer
27.344
316258AE1-075 C
Solar/Wind Harmer
0.157
3145796HORNRTN
Solar/Wind Harmer
0.622
3145796HORNRTN
Solar/Wind Harmer
0.078
316210AC1-098 GEN
Solar/Wind Harmer
1.756
970831AG2-522 GEN
Solar/Wind Harmer
7.993
3145746EVERETS
Solar/Wind Harmer
0.739
3145746EVERETS
Solar/Wind Harmer
0.186
3152251N ANNA1
50/50
14.386
315052AA1-145 CT2
50/50
2.037
3150851SPRUNCC
Adder
1.126
316132AB2-190 GEN1
Solar/Wind Harmer
1.272
315773AC2-141 GEN
Solar/Wind Harmer
8.57
316036AC1-147 C
Solar/Wind Harmer
0.041
316093AE2-104_GEN
Solar/Wind Harmer
3.834
3146516WINFALL
Solar/Wind Harmer
0.726
3146516WINFALL
Solar/Wind Harmer
0.224
962861AG1-135 GEN
Solar/Wind Harmer
6.968
3141726DUNNSVL
Solar/Wind Harmer
0.858
970919AG2-571 GEN
Solar/Wind Harmer
7.345
3145893MURPHYS
Solar/Wind Harmer
0.822
3145893MURPHYS
Solar/Wind Harmer
0.913
316337AD2-073 GEN
Solar/Wind Harmer
0.175
315607AA1-063A GEN
Solar/Wind Harmer
0.403
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.198
316494AC1-189 GEN
Solar/Wind Harmer
0.617
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.141
3146776BUCKING
Solar/Wind Harmer
0.068
316170AC1-121 GEN2
Solar/Wind Harmer
1.48
316140AB2-099
Solar/Wind Harmer
0.072
316005AA1-067
Solar/Wind Harmer
0.198
3145453TOT5
Solar/Wind Harmer
0.25
961601AG1-000A GEN
Solar/Wind Harmer
3.137
964791AG1-342 GEN
Solar/Wind Harmer
3.271
3146776BUCKING
Solar/Wind Harmer
0.675
3146776BUCKING
Solar/Wind Harmer
0.055
316118AC1-105 GEN
Solar/Wind Harmer
0.427
972193AH1-681 GEN
Adder
3.766
942751AE2-291 GEN
Solar/Wind Harmer
6.895
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
957861AF2-080 GEN
Solar/Wind Harmer
7.87
3145573BETHELC
Solar/Wind Harmer
0.18
3145573BETHELC
Solar/Wind Harmer
0.18
970683AG2-441 GEN
Solar/Wind Harmer
10.744
970681AG2-440 GEN
Solar/Wind Harmer
7.131
972219AH1-694 GEN
50/50
4.184
3143526WINTERP
Solar/Wind Harmer
1.272
944631AF1-128 GEN
Adder
115.543
315671AE2-027_GEN
Solar/Wind Harmer
0.002
971317AH1-138 GEN
Solar/Wind Harmer
1.763
944591AF1-124 GEN
Solar/Wind Harmer
52.511
316072AD1-144
Solar/Wind Harmer
0.082
939411AE1-173 GEN
Solar/Wind Harmer
98.409
940641AE2-051 GEN
Solar/Wind Harmer
18.429
941031AE2-094 GEN
Solar/Wind Harmer
40.872
3150351NORNECKC2
Adder
2.111
3143336POWHATN
Solar/Wind Harmer
3.743
971547AH1-271 GEN
Solar/Wind Harmer
4.402
960081AF2-299 GEN
Solar/Wind Harmer
1.925
3145823KELFORD
Solar/Wind Harmer
0.197
3145783HORNRTN
Solar/Wind Harmer
0.195
316075AC2-137 C
Solar/Wind Harmer
0.065
315778AD1-151 GEN
Solar/Wind Harmer
19.016
3144216WINCHST
Adder
0.89
944601AF1-125 GEN
Solar/Wind Harmer
51.52
3151101ELIZAR3
Adder
21.578
3150351NORNECKC2
Adder
2.146
3143336POWHATN
Solar/Wind Harmer
3.181
3145823KELFORD
Solar/Wind Harmer
0.197
3145796HORNRTN
Solar/Wind Harmer
0.778
3145796HORNRTN
Solar/Wind Harmer
0.194
316212AC1-099_GEN
Solar/Wind Harmer
0.98
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
315722AD1-056 GEN
Solar/Wind Harmer
6.378
964241AG1-285 GEN
Solar/Wind Harmer
11.954
3144293JTRSVLE
Adder
0.425
942461AE2-259 GEN
Solar/Wind Harmer
0
972003AH1-546 GEN
Solar/Wind Harmer
5.592
971683AH1-343 GEN
Solar/Wind Harmer
5.518
316123AC1-075 GEN
Solar/Wind Harmer
0.179
315821AE2-092 GEN
Solar/Wind Harmer
0
3151761LOISA E
Adder
16.344
3151721LOISA A
Adder
7.975
3141196NOKESVL
Solar/Wind Helper
1.254
3145796HORNRTN
Solar/Wind Harmer
0.641
3145796HORNRTN
Solar/Wind Harmer
0.194
316129AC1-054 GEN
Solar/Wind Harmer
0.695
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
971065AG2-659 GEN
Solar/Wind Harmer
7.908
316034AC1-036 C
Solar/Wind Harmer
0.012
3144293JTRSVLE
Adder
0.425
3144293JTRSVLE
Adder
0.335
970401AG2-262 GEN
Solar/Wind Harmer
0.999
972277AH1-723 GEN
Adder
98.225
3147623JAMES R
Solar/Wind Harmer
0.35
316415AF1-147_GEN2
Solar/Wind Helper
0.811
3150391LDYSMT3
50/50
37.144
316312AB1-027
Solar/Wind Harmer
0.443
3143526WINTERP
Solar/Wind Harmer
1.272
944641AF1-129 GEN
Adder
114.524
3144356SAPONY
Solar/Wind Harmer
1.859
316315AB2-025 C
Solar/Wind Harmer
0.178
972185AH1-677 GEN
Adder
12.144
970099AG2-077 GEN
Solar/Wind Harmer
21.11
962571AG1-106 GEN
Solar/Wind Harmer
2.81
3145783HORNRTN
Solar/Wind Harmer
3.462
3145783HORNRTN
Solar/Wind Harmer
2.769
3145783HORNRTN
Solar/Wind Harmer
0.865
3145783HORNRTN
Solar/Wind Harmer
0.346
3145796HORNRTN
Solar/Wind Harmer
0.583
315724AD1-057 GEN
Solar/Wind Harmer
3.558
3145603CNETO
Solar/Wind Harmer
0.167
3144293JTRSVLE
Adder
0.425
316263AC1-034 GEN
Solar/Wind Harmer
6.702
962561AG1-105 GEN
Solar/Wind Harmer
8.245
316411AF1-147_GEN1
Solar/Wind Helper
0.811
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.232
LGEELTFEXP_LGEE->PJM
CLTF
1.325
MECLTFEXP_MEC->PJM
CLTF
3.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.187
NYPJM->LTFIMP_NY
CLTF
3.271
TVALTFEXP_TVA->PJM
CLTF
4.055
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.949
CPLELTFEXP_CPLE->PJM
CLTF
11.373
SIGELTFEXP_SIGE->PJM
CLTF
0.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.788
WECLTFEXP_WEC->PJM
CLTF
0.638
LAGNLTFEXP_LAGN->PJM
CLTF
7.995

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4600.84
MW Contribution:
73.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
14.176
315052AA1-145 CT2
50/50
2.012
3150851SPRUNCC
Adder
1.11
316132AB2-190 GEN1
Solar/Wind Harmer
1.255
315773AC2-141 GEN
Solar/Wind Harmer
8.457
316036AC1-147 C
Solar/Wind Harmer
0.041
316093AE2-104_GEN
Solar/Wind Harmer
3.783
3146516WINFALL
Solar/Wind Harmer
0.716
3146516WINFALL
Solar/Wind Harmer
0.221
962861AG1-135 GEN
Solar/Wind Harmer
6.884
3141726DUNNSVL
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
7.244
3145893MURPHYS
Solar/Wind Harmer
0.81
3145893MURPHYS
Solar/Wind Harmer
0.901
316337AD2-073 GEN
Solar/Wind Harmer
0.173
315607AA1-063A GEN
Solar/Wind Harmer
0.397
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
316494AC1-189 GEN
Solar/Wind Harmer
0.608
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.139
3146776BUCKING
Solar/Wind Harmer
0.066
972219AH1-694 GEN
50/50
4.141
3143526WINTERP
Solar/Wind Harmer
1.254
944631AF1-128 GEN
Adder
114.046
315671AE2-027_GEN
Solar/Wind Harmer
0.002
971317AH1-138 GEN
Solar/Wind Harmer
1.74
944591AF1-124 GEN
Solar/Wind Harmer
51.815
316072AD1-144
Solar/Wind Harmer
0.081
939411AE1-173 GEN
Solar/Wind Harmer
97.075
940641AE2-051 GEN
Solar/Wind Harmer
18.178
941031AE2-094 GEN
Solar/Wind Harmer
40.308
3150351NORNECKC2
Adder
2.086
3143336POWHATN
Solar/Wind Harmer
3.673
971547AH1-271 GEN
Solar/Wind Harmer
4.344
960081AF2-299 GEN
Solar/Wind Harmer
1.899
3145823KELFORD
Solar/Wind Harmer
0.195
3145783HORNRTN
Solar/Wind Harmer
0.192
3145796HORNRTN
Solar/Wind Harmer
0.633
3145796HORNRTN
Solar/Wind Harmer
0.192
316129AC1-054 GEN
Solar/Wind Harmer
0.685
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
971065AG2-659 GEN
Solar/Wind Harmer
7.794
316034AC1-036 C
Solar/Wind Harmer
0.012
3144293JTRSVLE
Adder
0.417
3144293JTRSVLE
Adder
0.329
970401AG2-262 GEN
Solar/Wind Harmer
0.984
972277AH1-723 GEN
Adder
96.787
3147623JAMES R
Solar/Wind Harmer
0.34
316415AF1-147_GEN2
Solar/Wind Helper
0.788
3150391LDYSMT3
50/50
36.76
316312AB1-027
Solar/Wind Harmer
0.437
3143526WINTERP
Solar/Wind Harmer
1.254
944641AF1-129 GEN
Adder
113.017
3144356SAPONY
Solar/Wind Harmer
1.834
316315AB2-025 C
Solar/Wind Harmer
0.175
972185AH1-677 GEN
Adder
11.976
970099AG2-077 GEN
Solar/Wind Harmer
20.798
962571AG1-106 GEN
Solar/Wind Harmer
2.772
3145783HORNRTN
Solar/Wind Harmer
3.414
3145783HORNRTN
Solar/Wind Harmer
2.731
3145783HORNRTN
Solar/Wind Harmer
0.854
3145783HORNRTN
Solar/Wind Harmer
0.341
3145796HORNRTN
Solar/Wind Harmer
0.575
315724AD1-057 GEN
Solar/Wind Harmer
3.51
3145603CNETO
Solar/Wind Harmer
0.164
3144293JTRSVLE
Adder
0.417
316263AC1-034 GEN
Solar/Wind Harmer
6.613
962561AG1-105 GEN
Solar/Wind Harmer
8.121
316411AF1-147_GEN1
Solar/Wind Helper
0.788
972197AH1-683 GEN
50/50
5.751
966881AG1-559 GEN
Solar/Wind Harmer
0.296
3142416OLDCHRC
Solar/Wind Harmer
0.639
3142416OLDCHRC
Solar/Wind Harmer
0.245
315975AC1-164 GENB
Solar/Wind Harmer
0.075
3142433PROV 92
Solar/Wind Harmer
0.931
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
3145336SMITFLD
Solar/Wind Harmer
0.924
316375AC2-012 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.603
3146456SLIGO L269
Solar/Wind Harmer
0.226
958261AF2-120 GEN
Solar/Wind Harmer
7.088
3145663CRESWEL
Solar/Wind Harmer
0.588
3146206CASHIE
Solar/Wind Harmer
0.203
316023GEN1_S
Solar/Wind Harmer
0.451
3146173TUNIS
Solar/Wind Harmer
0.201
3156021HOLLOMANSOL
Solar/Wind Harmer
0.902
3145683EARLEYS
Solar/Wind Harmer
0.199
3147043LAWRENC
Adder
1.732
316192AB2-158 GEN
Solar/Wind Harmer
1.035
3146083TARBORO
Solar/Wind Harmer
0.177
316131AB2-060 GEN
Solar/Wind Harmer
0.55
972135AH1-637 GEN
Solar/Wind Harmer
1.504
970937AG2-583 GEN
Solar/Wind Harmer
10.738
316359AB2-059 GEN
Solar/Wind Harmer
0.618
3142053HEARTS
Solar/Wind Harmer
0.306
316447AC1-158 HLD
Solar/Wind Helper
4.178
3143096IRON208
Adder
1.01
3142543TWELFTH
Solar/Wind Harmer
0.023
3143226MDLTHAN
Solar/Wind Harmer
0.24
971069AG2-661 GEN
Solar/Wind Harmer
4.17
3138126ROCKLANDING
Solar/Wind Harmer
0.107
961611AG1-000B GEN
Solar/Wind Harmer
12.211
3151171GRAVELC
Adder
2.469
3150981CHESPKA
Adder
2.863
316381AD1-082 GEN
Solar/Wind Harmer
0.232
319010AE1-072 C
Solar/Wind Harmer
1.128
3138133OCRAN
Solar/Wind Harmer
0.134
3130156CHOWAN
Solar/Wind Harmer
0.215
316404AE1-155 C
Solar/Wind Harmer
0
315816AE2-034 GEN
Solar/Wind Harmer
0.897
971163AH1-040 GEN
Solar/Wind Harmer
16.816
315737AD1-076 GEN
Solar/Wind Harmer
2.64
970087AG2-069 GEN
Solar/Wind Harmer
16.1
957481AF2-042 GEN
Solar/Wind Harmer
51.995
315693AD1-088 GEN
Solar/Wind Harmer
9.181
3147666LOUISA
Solar/Wind Harmer
0.756
3146293MARTNCO
Solar/Wind Harmer
0.174
3145493TOT1
Solar/Wind Harmer
0.789
3146233WITAKRS
Solar/Wind Harmer
0.706
315785AD2-033 C
Solar/Wind Harmer
1.422
970685AG2-442 GEN
Solar/Wind Harmer
13.06
971563AH1-280 GEN
Solar/Wind Harmer
1.863
3146926FARMVIL
Solar/Wind Harmer
0.103
971377AH1-170 GEN
Solar/Wind Harmer
1.565
316044AC1-158 PL1
Solar/Wind Helper
1.899
3142366NRTHEST
50/50
0.846
3150691DARBY 3
Adder
17.527
3150701DARBY 4
Adder
17.486
315976AC1-164 GENA
Solar/Wind Harmer
2.522
316169AC1-164_GENC
Solar/Wind Harmer
2.179
3142946ENON
Solar/Wind Harmer
0.024
316294AC1-161 GEN
Solar/Wind Harmer
4.003
316349AD2-085 GEN
Solar/Wind Harmer
0.151
3146456SLIGO L269
Solar/Wind Harmer
4.007
3146386ELIZ CT
Solar/Wind Harmer
0.224
315742AE1-103 GEN
Solar/Wind Harmer
3.228
3146376EDENTON
Solar/Wind Harmer
0.956
3146376EDENTON
Solar/Wind Harmer
0.956
970933AG2-581 GEN
Solar/Wind Harmer
16.621
316365GEN2_N
Solar/Wind Harmer
0.451
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
316336AC2-165 C
Solar/Wind Harmer
10.02
958211AF2-115 GEN
Solar/Wind Harmer
2.096
3147133PAMPLIN
Solar/Wind Harmer
0.174
3147133PAMPLIN
Solar/Wind Harmer
0.139
3146843MT LREL
Solar/Wind Harmer
0.168
3146843MT LREL
Solar/Wind Harmer
0.168
972195AH1-682 GEN
50/50
4.831
972189AH1-679 GEN
50/50
4.491
315673AE1-157 GEN
Solar/Wind Harmer
17.771
3150681DARBY 2
Adder
17.466
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.911
3145506HICKORY
Solar/Wind Harmer
0.547
3145506HICKORY
Solar/Wind Harmer
0.137
316339AD2-160 GEN
Solar/Wind Harmer
0.363
316388AE2-253 GEN
Solar/Wind Harmer
0.707
3137176SLIGO L2192
Solar/Wind Harmer
0.901
3130086AYDLETT
Solar/Wind Harmer
0.904
3146626S HERTFORD
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.219
3150341NORNECKC1
Adder
2.191
3150341NORNECKC1
Adder
2.173
313506AB2-031 GEN
Solar/Wind Harmer
0.6
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
3142666NORTHAMPTON
Solar/Wind Harmer
0.117
3145593CAROLNA
Solar/Wind Harmer
0.193
3145593CAROLNA
Solar/Wind Harmer
0.193
3145593CAROLNA
Solar/Wind Harmer
0.24
3145933PARMELE
Solar/Wind Harmer
0.374
3145933PARMELE
Solar/Wind Harmer
0.187
970301AG2-198 GEN
Solar/Wind Harmer
7.694
3145493TOT1
Solar/Wind Harmer
0.411
970323AG2-213 GEN
Solar/Wind Harmer
7.495
316049AB1-081 GEN
Solar/Wind Harmer
0.99
316450AC1-158 RIC
Solar/Wind Helper
0.506
3150371LDYSMT1
50/50
35.587
315051AA1-145 CT1
50/50
2
3142416OLDCHRC
Solar/Wind Harmer
2.382
316473AC1-191 GEN
Solar/Wind Harmer
0.811
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.271
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
3145336SMITFLD
Solar/Wind Harmer
0.092
315813AE1-149 C
Solar/Wind Harmer
12.322
3141766HARMONY
Solar/Wind Harmer
3.05
316017AA1-139 ULT1
Solar/Wind Harmer
0.121
3146456SLIGO L269
Solar/Wind Harmer
0.226
971153AH1-033 GEN
Solar/Wind Harmer
2.618
3145273HOLLAND
Solar/Wind Harmer
0.164
3146376EDENTON
Solar/Wind Harmer
0.215
971781AH1-399 GEN
Solar/Wind Harmer
0.275
3146206CASHIE
Solar/Wind Harmer
0.203
3146173TUNIS
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.115
316478AD1-087 GEN
Solar/Wind Harmer
0.651
3146073TAR RVR
Solar/Wind Harmer
0.177
3146083TARBORO
Solar/Wind Harmer
0.177
3138543CONSLDL
Solar/Wind Harmer
0.117
959311AF2-222 GEN
Solar/Wind Harmer
15.601
3147133PAMPLIN
Solar/Wind Harmer
0.547
971623AH1-311 GEN
Solar/Wind Harmer
0.348
972255AH1-712 GEN
Adder
83.058
316222AC1-221 GEN
Solar/Wind Harmer
0.604
316283AC2-100 C
Solar/Wind Harmer
0.286
3150381LDYSMT2
50/50
35.357
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
3151201GRAVEL4
Adder
16.892
3151221GRAVEL6
Adder
16.873
3151211GRAVEL5
Adder
16.678
316311AC2-079 GEN
Solar/Wind Harmer
6.506
313526AB2-022
Solar/Wind Harmer
0.12
3146396TANGLEW
Solar/Wind Harmer
0.615
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
315814AE2-033 C
Solar/Wind Harmer
17.282
3146206CASHIE
Solar/Wind Harmer
0.203
3145683EARLEYS
Solar/Wind Harmer
0.398
3145683EARLEYS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.199
3146043SEABORD
Solar/Wind Harmer
0.198
316486AD2-202 GEN
Solar/Wind Harmer
0.191
316274AC1-208 GEN
Solar/Wind Harmer
0.959
961791AG1-021 GEN
Solar/Wind Harmer
1.677
971845AH1-439 GEN
Solar/Wind Harmer
7.501
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.101
3142296MT RD221
50/50
0.841
3150671DARBY 1
Adder
17.445
971223AH1-071 GEN
Solar/Wind Harmer
2.564
966871AG1-558 GEN
Solar/Wind Harmer
0.277
3150991CHESPKB
Adder
2.401
3150991CHESPKB
Adder
2.344
316156AD2-030 GEN
Solar/Wind Harmer
0.166
315835AF2-110_GEN
Solar/Wind Harmer
1.544
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
972187AH1-678 GEN
Adder
6.009
315614AA2-178 GEN
Solar/Wind Harmer
1.196
316313AB2-026
Solar/Wind Harmer
0.129
316065AD1-022 GEN
Solar/Wind Harmer
9.412
3145893MURPHYS
Solar/Wind Harmer
1.356
3145893MURPHYS
Solar/Wind Harmer
0.365
316140AB2-099
Solar/Wind Harmer
0.071
316005AA1-067
Solar/Wind Harmer
0.195
3145453TOT5
Solar/Wind Harmer
0.247
961601AG1-000A GEN
Solar/Wind Harmer
3.095
964791AG1-342 GEN
Solar/Wind Harmer
3.222
3146776BUCKING
Solar/Wind Harmer
0.659
3146776BUCKING
Solar/Wind Harmer
0.053
316118AC1-105 GEN
Solar/Wind Harmer
0.421
972193AH1-681 GEN
Adder
3.711
942751AE2-291 GEN
Solar/Wind Harmer
6.798
316045AC1-158 PL2
Solar/Wind Helper
6.076
316006AB2-029 C
Solar/Wind Helper
0.111
3150411LDYSMT5
50/50
36.944
972215AH1-692 GEN
50/50
5.981
316233AE1-074 FULL
Solar/Wind Harmer
0.193
971283AH1-107 GEN
Solar/Wind Harmer
3.346
3151191GRAVEL3
Adder
16.678
3138283WHITEMARSH
Solar/Wind Harmer
0.053
970189AG2-124 GEN
Solar/Wind Harmer
6.773
3146406KITTY HAWK
Solar/Wind Harmer
0.028
971967AH1-528 GEN
Solar/Wind Harmer
33.875
3141813NORNECK
Solar/Wind Harmer
0.209
315732AD1-074 GEN1
Solar/Wind Harmer
1.172
3145893MURPHYS
Solar/Wind Harmer
0.547
3145893MURPHYS
Solar/Wind Harmer
0.203
970085AG2-068 GEN
Solar/Wind Harmer
10.733
316463AE2-346 GEN
Solar/Wind Harmer
0.171
3145513AHOSKIE
Solar/Wind Harmer
0.418
3145513AHOSKIE
Solar/Wind Harmer
0.2
315652AC1-086 GEN
Solar/Wind Harmer
21.435
3137643SOCKMAN
Solar/Wind Harmer
0.776
316426AA2-053 GEN
Solar/Wind Harmer
0.649
316327AA2-057 GEN
Solar/Wind Harmer
0.267
3144303KENBRDG
Solar/Wind Harmer
0.14
946301AF1-294 GEN
Solar/Wind Harmer
3.446
3138216PACIFIC
Solar/Wind Helper
0.038
970293AG2-193 GEN
Solar/Wind Harmer
2.588
3150921YORKTN3
Adder
5.855
3144536CHRHLND
Solar/Wind Harmer
0.034
944581AF1-123 GEN
Solar/Wind Harmer
51.631
316203AE2-005 GEN
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.221
944011AF1-069 GEN
Solar/Wind Harmer
13.17
315735AD1-075 GEN1
Solar/Wind Harmer
0.585
3145893MURPHYS
Solar/Wind Harmer
0.339
3145893MURPHYS
Solar/Wind Harmer
0.203
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
316011AB1-132 GEN
Solar/Wind Harmer
3.535
316223AC1-118
Solar/Wind Harmer
0.136
961601AG1-000A GEN
Solar/Wind Harmer
12.382
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.174
3146776BUCKING
Solar/Wind Harmer
0.059
970221AG2-151 GEN
Solar/Wind Harmer
7.825
270494AE1-108_GEN
Solar/Wind Harmer
1.557
3150331BIRCHWDA
Adder
21.106
971285AH1-108 GEN
Adder
1.817
315697AD1-025 GEN
Solar/Wind Harmer
0.252
971445AH1-216 GEN
Solar/Wind Harmer
16.274
3151081ELIZAR1
Adder
21.023
3151091ELIZAR2
Adder
20.658
316316AC1-027 C
Solar/Wind Harmer
0.218
957871AF2-081 GEN
Solar/Wind Harmer
11.297
3141913WHIT STONE
Solar/Wind Harmer
0.224
970673AG2-436 GEN
Solar/Wind Harmer
26.967
316258AE1-075 C
Solar/Wind Harmer
0.154
3145796HORNRTN
Solar/Wind Harmer
0.614
3145796HORNRTN
Solar/Wind Harmer
0.077
316210AC1-098 GEN
Solar/Wind Harmer
1.733
970831AG2-522 GEN
Solar/Wind Harmer
7.879
3145746EVERETS
Solar/Wind Harmer
0.729
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
957861AF2-080 GEN
Solar/Wind Harmer
7.766
3145573BETHELC
Solar/Wind Harmer
0.177
3145573BETHELC
Solar/Wind Harmer
0.177
970683AG2-441 GEN
Solar/Wind Harmer
10.555
970681AG2-440 GEN
Solar/Wind Harmer
7.006
316075AC2-137 C
Solar/Wind Harmer
0.064
315778AD1-151 GEN
Solar/Wind Harmer
18.767
3144216WINCHST
Adder
0.878
944601AF1-125 GEN
Solar/Wind Harmer
50.836
3151101ELIZAR3
Adder
21.292
3150351NORNECKC2
Adder
2.121
3143336POWHATN
Solar/Wind Harmer
3.122
3145823KELFORD
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.767
3145796HORNRTN
Solar/Wind Harmer
0.192
316212AC1-099_GEN
Solar/Wind Harmer
0.966
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
315722AD1-056 GEN
Solar/Wind Harmer
6.293
964241AG1-285 GEN
Solar/Wind Harmer
11.761
3144293JTRSVLE
Adder
0.417
942461AE2-259 GEN
Solar/Wind Harmer
0
972003AH1-546 GEN
Solar/Wind Harmer
5.44
971683AH1-343 GEN
Solar/Wind Harmer
5.439
316123AC1-075 GEN
Solar/Wind Harmer
0.176
315821AE2-092 GEN
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.228
971531AH1-263 GEN
50/50
73.133
972213AH1-691 GEN
50/50
5.981
971281AH1-106 GEN
Solar/Wind Harmer
3.346
316159AE1-175 C
Solar/Wind Harmer
0.201
3143316POE
Solar/Wind Harmer
0.914
3143873LANEXA
Solar/Wind Harmer
0.139
970657AG2-426 GEN
Solar/Wind Harmer
1.682
3141873WAN 176
Solar/Wind Harmer
0.045
3138133OCRAN
Solar/Wind Harmer
0.067
3146486SUNBURY
Solar/Wind Harmer
0.223
3146486SUNBURY
Solar/Wind Harmer
0.223
3145176PASQUOTANK
Solar/Wind Harmer
0.138
970533AG2-339 GEN
Solar/Wind Harmer
16.536
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
0.206
315733AD1-074 GEN2
Solar/Wind Harmer
1.172
970601AG2-382 GEN
Solar/Wind Harmer
7.602
970581AG2-369 GEN
Solar/Wind Harmer
9.231
3146033SCOT NK
Solar/Wind Harmer
0.763
944491AF1-114 GEN
Solar/Wind Harmer
0
972205AH1-687 GEN
Adder
6.658
3152261N ANNA2
50/50
14.183
3150401LDYSMT4
50/50
36.829
3143096IRON208
Adder
1.01
3143096IRON208
Adder
0.99
3150861SPRUNCD
Adder
1.11
316458AB2-190 GEN2
Solar/Wind Harmer
1.255
961611AG1-000B GEN
Solar/Wind Harmer
6.209
3151171GRAVELC
Adder
3.246
3144873MCLAUGH
Solar/Wind Harmer
0.006
970657AG2-426 GEN
Solar/Wind Harmer
5.139
3141843SHACKLE
Adder
1.168
3141873WAN 176
Solar/Wind Harmer
4.033
316246AF1-032 C
Solar/Wind Harmer
0.101
316321Z2-027
Solar/Wind Harmer
0.04
3146626S HERTFORD
Solar/Wind Harmer
0.219
3156081AA2-088 GEN
Solar/Wind Harmer
0
970917AG2-570 GEN
Solar/Wind Harmer
18.109
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
3141906WESTMOR
Solar/Wind Harmer
0.076
3147666LOUISA
Solar/Wind Harmer
0.435
3145933PARMELE
Solar/Wind Harmer
0.187
3146233WITAKRS
Solar/Wind Harmer
0.89
3146233WITAKRS
Solar/Wind Harmer
0.121
970257AG2-171 GEN
Solar/Wind Harmer
5.621
971775AH1-396 GEN
Solar/Wind Harmer
0.281
3146926FARMVIL
Solar/Wind Harmer
0.103
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.295
LGEELTFEXP_LGEE->PJM
CLTF
1.343
MECLTFEXP_MEC->PJM
CLTF
3.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.728
NYPJM->LTFIMP_NY
CLTF
3.156
TVALTFEXP_TVA->PJM
CLTF
4.04
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.669
CPLELTFEXP_CPLE->PJM
CLTF
11.231
SIGELTFEXP_SIGE->PJM
CLTF
0.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.762
WECLTFEXP_WEC->PJM
CLTF
0.65
LAGNLTFEXP_LAGN->PJM
CLTF
7.97

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5465.85
MW Contribution:
86.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150381LDYSMT2
50/50
35.738
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3151201GRAVEL4
Adder
17.144
3151221GRAVEL6
Adder
17.125
3151211GRAVEL5
Adder
16.927
316059AD1-063 C
Solar/Wind Harmer
0.588
316311AC2-079 GEN
Solar/Wind Harmer
13.036
313526AB2-022
Solar/Wind Harmer
0.688
3146396TANGLEW
Solar/Wind Harmer
0.468
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
315814AE2-033 C
Solar/Wind Harmer
23.213
3146206CASHIE
Solar/Wind Harmer
-0.023
316318V4-068
Solar/Wind Harmer
0.576
961941AG1-037 GEN
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
316486AD2-202 GEN
Solar/Wind Harmer
0.543
316274AC1-208 GEN
Solar/Wind Harmer
2.284
961791AG1-021 GEN
Solar/Wind Harmer
2.508
3150371LDYSMT1
50/50
35.97
315051AA1-145 CT1
50/50
2.026
966881AG1-559 GEN
Solar/Wind Harmer
0.875
3142416OLDCHRC
Solar/Wind Harmer
2.826
316473AC1-191 GEN
Solar/Wind Harmer
2.941
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.035
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.469
3141766HARMONY
Solar/Wind Harmer
2.32
316017AA1-139 ULT1
Solar/Wind Harmer
2.089
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
2.989
3145273HOLLAND
Solar/Wind Harmer
-0.019
961951AG1-038 GEN
Solar/Wind Harmer
3.259
3146376EDENTON
Solar/Wind Harmer
-0.024
971781AH1-399 GEN
Solar/Wind Harmer
1.466
3146206CASHIE
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.11
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.856
316420AA1-050 GEN
Solar/Wind Harmer
2.322
3146073TAR RVR
Solar/Wind Harmer
-0.02
3146083TARBORO
Solar/Wind Harmer
-0.02
3138543CONSLDL
Solar/Wind Harmer
-0.013
959311AF2-222 GEN
Solar/Wind Harmer
21.016
3150411LDYSMT5
50/50
37.342
972215AH1-692 GEN
50/50
6.045
316164AC1-076 GEN
Solar/Wind Harmer
2.333
316233AE1-074 FULL
Solar/Wind Harmer
0.741
971283AH1-107 GEN
Solar/Wind Harmer
4.478
3147133PAMPLIN
Solar/Wind Harmer
-0.063
972255AH1-712 GEN
Adder
84.514
971531AH1-263 GEN
50/50
86.436
972213AH1-691 GEN
50/50
6.045
971281AH1-106 GEN
Solar/Wind Harmer
4.478
316382AG1-145 C
Solar/Wind Harmer
0.807
316159AE1-175 C
Solar/Wind Harmer
0.719
316236AE1-162_GEN
Solar/Wind Harmer
0.792
3143316POE
Solar/Wind Harmer
-0.104
3143873LANEXA
Solar/Wind Harmer
-0.016
970657AG2-426 GEN
Solar/Wind Harmer
1.647
3141873WAN 176
Solar/Wind Harmer
-0.005
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
970533AG2-339 GEN
Solar/Wind Harmer
16.8
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
316405AF2-144 C
Solar/Wind Harmer
0.607
3130546PLYMOUTH
Solar/Wind Harmer
-0.023
315733AD1-074 GEN2
Solar/Wind Harmer
4.738
970601AG2-382 GEN
Solar/Wind Harmer
10.163
970581AG2-369 GEN
Solar/Wind Harmer
12.348
946281AF1-292 GEN
Solar/Wind Harmer
0.506
3146033SCOT NK
Solar/Wind Harmer
-0.087
972205AH1-687 GEN
Adder
6.9
3152261N ANNA2
50/50
14.422
3150401LDYSMT4
50/50
37.226
3143096IRON208
Adder
1.025
3143096IRON208
Adder
1.005
3150861SPRUNCD
Adder
1.128
316458AB2-190 GEN2
Solar/Wind Harmer
2.706
961611AG1-000B GEN
Solar/Wind Harmer
5.591
3151171GRAVELC
Adder
3.295
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
5.277
3141843SHACKLE
Adder
1.184
3141873WAN 176
Solar/Wind Harmer
3.068
316246AF1-032 C
Solar/Wind Harmer
0.52
316321Z2-027
Solar/Wind Harmer
0.684
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3156081AA2-088 GEN
Solar/Wind Harmer
7.607
970917AG2-570 GEN
Solar/Wind Harmer
58.143
3147666LOUISA
Solar/Wind Harmer
-0.053
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.272
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145933PARMELE
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.424
3146233WITAKRS
Solar/Wind Harmer
-0.014
970257AG2-171 GEN
Solar/Wind Harmer
7.555
971775AH1-396 GEN
Solar/Wind Harmer
1.421
3146926FARMVIL
Solar/Wind Harmer
-0.012
3151191GRAVEL3
Adder
16.927
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316018AA1-139 ULT2
Solar/Wind Harmer
2.212
315833AF1-017_GEN
Solar/Wind Harmer
4.908
957601AF2-054 GEN
Solar/Wind Harmer
0.773
3146406KITTY HAWK
Solar/Wind Harmer
0.021
315800Z1-036_GEN1
Solar/Wind Harmer
6.09
971967AH1-528 GEN
Solar/Wind Harmer
45.452
3141813NORNECK
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.738
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
970085AG2-068 GEN
Solar/Wind Harmer
14.358
316463AE2-346 GEN
Solar/Wind Harmer
0.368
3145513AHOSKIE
Solar/Wind Harmer
0.199
3145513AHOSKIE
Solar/Wind Harmer
-0.023
315652AC1-086 GEN
Solar/Wind Harmer
25.027
3137643SOCKMAN
Solar/Wind Harmer
-0.088
316426AA2-053 GEN
Solar/Wind Harmer
2.233
316174AB2-169 GEN
Solar/Wind Harmer
3.41
316327AA2-057 GEN
Solar/Wind Harmer
2.076
3144303KENBRDG
Solar/Wind Harmer
-0.016
946301AF1-294 GEN
Solar/Wind Harmer
5.141
3138216PACIFIC
Solar/Wind Helper
0.039
970293AG2-193 GEN
Solar/Wind Harmer
3.457
3150921YORKTN3
Adder
5.941
3144536CHRHLND
Solar/Wind Harmer
-0.004
944581AF1-123 GEN
Solar/Wind Harmer
118.979
3142956BIRDNECK
Solar/Wind Harmer
1.4
316203AE2-005 GEN
Solar/Wind Harmer
10.98
316305AF2-043 C
Solar/Wind Harmer
0.775
316320Y1-086
Solar/Wind Harmer
1.497
3146516WINFALL
Solar/Wind Harmer
-0.025
944011AF1-069 GEN
Solar/Wind Harmer
14.677
315735AD1-075 GEN1
Solar/Wind Harmer
2.368
3145893MURPHYS
Solar/Wind Harmer
0.161
3145893MURPHYS
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316011AB1-132 GEN
Solar/Wind Harmer
4.646
316223AC1-118
Solar/Wind Harmer
0.584
3150331BIRCHWDA
Adder
21.25
961601AG1-000A GEN
Solar/Wind Harmer
5.896
971507AH1-251 GEN
50/50
17.436
972197AH1-683 GEN
50/50
5.813
316447AC1-158 HLD
Solar/Wind Harmer
7.573
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
-0.072
3142416OLDCHRC
Solar/Wind Harmer
-0.028
315975AC1-164 GENB
Solar/Wind Harmer
0.184
3142433PROV 92
Solar/Wind Harmer
-0.106
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3145336SMITFLD
Solar/Wind Harmer
-0.105
316375AC2-012 GEN
Solar/Wind Harmer
9.043
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.04
3146456SLIGO L269
Solar/Wind Harmer
-0.026
958261AF2-120 GEN
Solar/Wind Harmer
9.459
3145663CRESWEL
Solar/Wind Harmer
-0.067
3146206CASHIE
Solar/Wind Harmer
-0.023
316023GEN1_S
Solar/Wind Harmer
1.559
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.074
3145683EARLEYS
Solar/Wind Harmer
-0.023
316192AB2-158 GEN
Solar/Wind Harmer
2.67
3147043LAWRENC
Adder
1.761
970937AG2-583 GEN
Solar/Wind Harmer
14.567
3146083TARBORO
Solar/Wind Harmer
-0.02
316319Z2-044 C
Solar/Wind Harmer
1.118
316131AB2-060 GEN
Solar/Wind Harmer
2.177
972195AH1-682 GEN
50/50
4.883
972189AH1-679 GEN
50/50
4.55
316450AC1-158 RIC
Solar/Wind Harmer
0.918
315673AE1-157 GEN
Solar/Wind Harmer
21.903
3150681DARBY 2
Adder
17.718
316033AB2-134 GEN
Solar/Wind Harmer
8.595
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.742
316388AE2-253 GEN
Solar/Wind Harmer
1.742
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316487AF1-042 GEN
Solar/Wind Harmer
3.259
3150341NORNECKC1
Adder
2.22
3150341NORNECKC1
Adder
2.202
313506AB2-031 GEN
Solar/Wind Harmer
1.79
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142296MT RD221
50/50
0.853
316045AC1-158 PL2
Solar/Wind Harmer
11.017
3150671DARBY 1
Adder
17.697
971223AH1-071 GEN
Solar/Wind Harmer
3.433
966871AG1-558 GEN
Solar/Wind Harmer
0.822
966871AG1-558 GEN
Solar/Wind Harmer
0.281
316240AF1-291 C
Solar/Wind Harmer
0.811
3150991CHESPKB
Adder
2.438
3150991CHESPKB
Adder
2.379
315666AE1-190 GEN
Solar/Wind Harmer
0.78
316156AD2-030 GEN
Solar/Wind Harmer
0.688
315835AF2-110_GEN
Solar/Wind Harmer
3.207
316435W1029_GEN3
Solar/Wind Harmer
4.581
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
972187AH1-678 GEN
Adder
6.106
315614AA2-178 GEN
Solar/Wind Harmer
2.58
316313AB2-026
Solar/Wind Harmer
0.639
316065AD1-022 GEN
Solar/Wind Harmer
11.66
3145893MURPHYS
Solar/Wind Harmer
0.645
3145893MURPHYS
Solar/Wind Harmer
-0.042
316140AB2-099
Solar/Wind Harmer
0.153
316005AA1-067
Solar/Wind Harmer
0.422
3145453TOT5
Solar/Wind Harmer
0.188
972193AH1-681 GEN
Adder
3.776
961601AG1-000A GEN
Solar/Wind Harmer
5.822
971285AH1-108 GEN
Adder
1.845
315839AE2-212 C
Solar/Wind Harmer
0.803
315697AD1-025 GEN
Solar/Wind Harmer
5.387
971445AH1-216 GEN
Solar/Wind Harmer
16.312
957831AF2-077 GEN
Solar/Wind Harmer
0.788
3151081ELIZAR1
Adder
21.341
3151091ELIZAR2
Adder
20.97
316316AC1-027 C
Solar/Wind Harmer
0.8
957871AF2-081 GEN
Solar/Wind Harmer
12.942
3141913WHIT STONE
Solar/Wind Harmer
-0.025
970673AG2-436 GEN
Solar/Wind Harmer
54.112
316468AD1-105 GEN
Solar/Wind Harmer
2.719
316258AE1-075 C
Solar/Wind Harmer
0.575
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
3.351
970831AG2-522 GEN
Solar/Wind Harmer
10.549
3145746EVERETS
Solar/Wind Harmer
-0.083
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
957861AF2-080 GEN
Solar/Wind Harmer
8.991
3145573BETHELC
Solar/Wind Harmer
-0.02
3145573BETHELC
Solar/Wind Harmer
-0.02
316238AB2-078_GEN
Solar/Wind Harmer
0.607
316239AB2-077_GEN
Solar/Wind Harmer
0.607
970683AG2-441 GEN
Solar/Wind Harmer
14.199
970681AG2-440 GEN
Solar/Wind Harmer
9.424
316075AC2-137 C
Solar/Wind Harmer
0.741
315778AD1-151 GEN
Solar/Wind Harmer
23.807
3144216WINCHST
Adder
0.891
944601AF1-125 GEN
Solar/Wind Harmer
117.122
3151101ELIZAR3
Adder
21.614
316484AD2-074 GEN
Solar/Wind Harmer
6.228
316077AC2-138 C
Solar/Wind Harmer
0.501
3150351NORNECKC2
Adder
2.149
3143336POWHATN
Solar/Wind Harmer
2.395
966621AG1-532 GEN
Solar/Wind Harmer
0.458
316317KELFORD C
Solar/Wind Harmer
1.029
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
316212AC1-099_GEN
Solar/Wind Harmer
1.862
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
315722AD1-056 GEN
Solar/Wind Harmer
7.393
964241AG1-285 GEN
Solar/Wind Harmer
15.789
3144293JTRSVLE
Adder
0.426
942461AE2-259 GEN
Solar/Wind Harmer
3
3151761LOISA E
Adder
17.13
3151721LOISA A
Adder
8.359
3141196NOKESVL
Solar/Wind Helper
1.245
972219AH1-694 GEN
50/50
4.185
3143526WINTERP
Solar/Wind Harmer
-0.143
944631AF1-128 GEN
Adder
115.714
315671AE2-027_GEN
Solar/Wind Harmer
4.837
971317AH1-138 GEN
Solar/Wind Harmer
3.321
316314AB2-024 C
Solar/Wind Harmer
2.238
944591AF1-124 GEN
Solar/Wind Harmer
119.408
939411AE1-173 GEN
Solar/Wind Harmer
129.806
316072AD1-144
Solar/Wind Harmer
0.524
940641AE2-051 GEN
Solar/Wind Harmer
24.31
941031AE2-094 GEN
Solar/Wind Harmer
46.842
964211AG1-282 GEN
Solar/Wind Harmer
0.726
3150351NORNECKC2
Adder
2.113
3143336POWHATN
Solar/Wind Harmer
2.818
971547AH1-271 GEN
Solar/Wind Harmer
5.807
960081AF2-299 GEN
Solar/Wind Harmer
2.541
3145823KELFORD
Solar/Wind Harmer
-0.022
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
316129AC1-054 GEN
Solar/Wind Harmer
1.833
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
971065AG2-659 GEN
Solar/Wind Harmer
10.438
316034AC1-036 C
Solar/Wind Harmer
0.373
3142366NRTHEST
50/50
0.858
3150691DARBY 3
Adder
17.78
3150701DARBY 4
Adder
17.739
315976AC1-164 GENA
Solar/Wind Harmer
6.211
316169AC1-164_GENC
Solar/Wind Harmer
5.366
3142946ENON
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.544
316083AB2-161 GEN
Solar/Wind Harmer
4.242
316349AD2-085 GEN
Solar/Wind Harmer
2.295
3146456SLIGO L269
Solar/Wind Harmer
3.051
3146386ELIZ CT
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.581
316433W1029_GEN2
Solar/Wind Harmer
4.581
315742AE1-103 GEN
Solar/Wind Harmer
5.852
3146376EDENTON
Solar/Wind Harmer
0.728
3146376EDENTON
Solar/Wind Harmer
0.728
970933AG2-581 GEN
Solar/Wind Harmer
22.248
316365GEN2_N
Solar/Wind Harmer
1.559
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
14.217
958211AF2-115 GEN
Solar/Wind Harmer
3.135
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
972135AH1-637 GEN
Solar/Wind Harmer
2.003
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
0.183
3145933PARMELE
Solar/Wind Harmer
-0.042
3145933PARMELE
Solar/Wind Harmer
-0.021
970301AG2-198 GEN
Solar/Wind Harmer
10.362
313527AB2-043 GEN
Solar/Wind Harmer
3.287
3145493TOT1
Solar/Wind Harmer
0.313
970323AG2-213 GEN
Solar/Wind Harmer
10.073
3151731LOISA B
Adder
8.402
316044AC1-158 PL1
Solar/Wind Harmer
3.443
3143096IRON208
Adder
1.025
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
971069AG2-661 GEN
Solar/Wind Harmer
4.232
316369SG1_INVT
Solar/Wind Harmer
4.76
3138126ROCKLANDING
Solar/Wind Harmer
0.081
961611AG1-000B GEN
Solar/Wind Harmer
13.104
3151171GRAVELC
Adder
2.506
3150981CHESPKA
Adder
2.906
316381AD1-082 GEN
Solar/Wind Harmer
2.392
315662AE1-191 GEN
Solar/Wind Harmer
3.122
316280AD1-041 GEN
Solar/Wind Harmer
1.951
319010AE1-072 C
Solar/Wind Harmer
5.21
3138133OCRAN
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.09
3130156CHOWAN
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.66
315816AE2-034 GEN
Solar/Wind Harmer
1.935
971163AH1-040 GEN
Solar/Wind Harmer
22.48
315737AD1-076 GEN
Solar/Wind Harmer
4.454
3147666LOUISA
Solar/Wind Harmer
-0.091
970087AG2-069 GEN
Solar/Wind Harmer
21.537
316087AB2-174 GEN
Solar/Wind Harmer
3.191
957481AF2-042 GEN
Solar/Wind Harmer
69.658
315693AD1-088 GEN
Solar/Wind Harmer
10.944
3146293MARTNCO
Solar/Wind Harmer
0.132
3145493TOT1
Solar/Wind Harmer
0.601
3146233WITAKRS
Solar/Wind Harmer
-0.08
315785AD2-033 C
Solar/Wind Harmer
4.562
970685AG2-442 GEN
Solar/Wind Harmer
17.575
3152251N ANNA1
50/50
14.415
315052AA1-145 CT2
50/50
2.039
3150851SPRUNCC
Adder
1.128
316132AB2-190 GEN1
Solar/Wind Harmer
2.706
315773AC2-141 GEN
Solar/Wind Harmer
11.055
316036AC1-147 C
Solar/Wind Harmer
0.704
316093AE2-104_GEN
Solar/Wind Harmer
7.46
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
962861AG1-135 GEN
Solar/Wind Harmer
9.187
3141726DUNNSVL
Solar/Wind Harmer
-0.096
970919AG2-571 GEN
Solar/Wind Harmer
7.36
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.686
316337AD2-073 GEN
Solar/Wind Harmer
0.611
315607AA1-063A GEN
Solar/Wind Harmer
2.273
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.211
961671AG1-007 GEN
Solar/Wind Harmer
0.256
971563AH1-280 GEN
Solar/Wind Harmer
2.508
3146926FARMVIL
Solar/Wind Harmer
-0.012
3151751LOISA D
Adder
8.402
3150391LDYSMT3
50/50
37.156
316312AB1-027
Solar/Wind Harmer
0.942
3143526WINTERP
Solar/Wind Harmer
-0.143
944641AF1-129 GEN
Adder
114.705
316185AD1-033 GEN
Solar/Wind Harmer
2.743
316441AF1-014 GEN
Solar/Wind Harmer
1.755
3144356SAPONY
Solar/Wind Harmer
0.873
316315AB2-025 C
Solar/Wind Harmer
0.673
972185AH1-677 GEN
Adder
12.168
970099AG2-077 GEN
Solar/Wind Harmer
27.863
962571AG1-106 GEN
Solar/Wind Harmer
3.198
3145783HORNRTN
Solar/Wind Harmer
2.602
3145783HORNRTN
Solar/Wind Harmer
2.081
3145783HORNRTN
Solar/Wind Harmer
0.65
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.065
315724AD1-057 GEN
Solar/Wind Harmer
4.066
315687AD1-152 GEN
Solar/Wind Harmer
2.441
3145603CNETO
Solar/Wind Harmer
0.125
316237AB2-079_GEN
Solar/Wind Harmer
0.607
3144293JTRSVLE
Adder
0.426
316411AF1-147_GEN1
Solar/Wind Helper
0.812
3144293JTRSVLE
Adder
0.426
3144293JTRSVLE
Adder
0.337
972277AH1-723 GEN
Adder
98.484
316415AF1-147_GEN2
Solar/Wind Helper
0.812
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.343
LGEELTFEXP_LGEE->PJM
CLTF
1.329
MECLTFEXP_MEC->PJM
CLTF
3.609
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.241
NYPJM->LTFIMP_NY
CLTF
3.282
TVALTFEXP_TVA->PJM
CLTF
4.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.011
CPLELTFEXP_CPLE->PJM
CLTF
11.4
SIGELTFEXP_SIGE->PJM
CLTF
0.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.826
WECLTFEXP_WEC->PJM
CLTF
0.64
LAGNLTFEXP_LAGN->PJM
CLTF
8.017

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.02 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5461.82
MW Contribution:
86.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150381LDYSMT2
50/50
35.723
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3151201GRAVEL4
Adder
17.114
3151221GRAVEL6
Adder
17.095
3151211GRAVEL5
Adder
16.898
316059AD1-063 C
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
13.012
313526AB2-022
Solar/Wind Harmer
0.686
3146396TANGLEW
Solar/Wind Harmer
0.467
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
315814AE2-033 C
Solar/Wind Harmer
23.166
3146206CASHIE
Solar/Wind Harmer
-0.023
316318V4-068
Solar/Wind Harmer
0.575
961941AG1-037 GEN
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
316486AD2-202 GEN
Solar/Wind Harmer
0.542
316274AC1-208 GEN
Solar/Wind Harmer
2.279
961791AG1-021 GEN
Solar/Wind Harmer
2.498
3150371LDYSMT1
50/50
35.955
315051AA1-145 CT1
50/50
2.024
966881AG1-559 GEN
Solar/Wind Harmer
0.874
3142416OLDCHRC
Solar/Wind Harmer
2.821
316473AC1-191 GEN
Solar/Wind Harmer
2.937
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.03
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.439
3141766HARMONY
Solar/Wind Harmer
2.316
316017AA1-139 ULT1
Solar/Wind Harmer
2.085
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
2.984
3145273HOLLAND
Solar/Wind Harmer
-0.019
961951AG1-038 GEN
Solar/Wind Harmer
3.254
3146376EDENTON
Solar/Wind Harmer
-0.024
971781AH1-399 GEN
Solar/Wind Harmer
1.464
3146206CASHIE
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.103
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.851
316420AA1-050 GEN
Solar/Wind Harmer
2.317
3146073TAR RVR
Solar/Wind Harmer
-0.02
3146083TARBORO
Solar/Wind Harmer
-0.02
3138543CONSLDL
Solar/Wind Harmer
-0.013
959311AF2-222 GEN
Solar/Wind Harmer
20.939
3147133PAMPLIN
Solar/Wind Harmer
-0.062
972255AH1-712 GEN
Adder
84.285
3150411LDYSMT5
50/50
37.326
972215AH1-692 GEN
50/50
6.043
316233AE1-074 FULL
Solar/Wind Harmer
0.74
971283AH1-107 GEN
Solar/Wind Harmer
4.468
316164AC1-076 GEN
Solar/Wind Harmer
2.299
3151191GRAVEL3
Adder
16.898
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316018AA1-139 ULT2
Solar/Wind Harmer
2.208
957601AF2-054 GEN
Solar/Wind Harmer
0.772
315833AF1-017_GEN
Solar/Wind Harmer
4.899
3146406KITTY HAWK
Solar/Wind Harmer
0.021
315800Z1-036_GEN1
Solar/Wind Harmer
6.078
971967AH1-528 GEN
Solar/Wind Harmer
45.349
3141813NORNECK
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.728
316044AC1-158 PL1
Solar/Wind Harmer
3.433
3143096IRON208
Adder
1.023
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
971069AG2-661 GEN
Solar/Wind Harmer
4.225
316369SG1_INVT
Solar/Wind Harmer
4.752
3138126ROCKLANDING
Solar/Wind Harmer
0.081
971531AH1-263 GEN
50/50
86.428
972213AH1-691 GEN
50/50
6.043
971281AH1-106 GEN
Solar/Wind Harmer
4.468
316382AG1-145 C
Solar/Wind Harmer
0.806
316159AE1-175 C
Solar/Wind Harmer
0.718
316236AE1-162_GEN
Solar/Wind Harmer
0.791
3143316POE
Solar/Wind Harmer
-0.103
3143873LANEXA
Solar/Wind Harmer
-0.016
970657AG2-426 GEN
Solar/Wind Harmer
1.644
3141873WAN 176
Solar/Wind Harmer
-0.005
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
970533AG2-339 GEN
Solar/Wind Harmer
16.764
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
316405AF2-144 C
Solar/Wind Harmer
0.604
3130546PLYMOUTH
Solar/Wind Harmer
-0.023
315733AD1-074 GEN2
Solar/Wind Harmer
4.728
970601AG2-382 GEN
Solar/Wind Harmer
10.142
970581AG2-369 GEN
Solar/Wind Harmer
12.32
946281AF1-292 GEN
Solar/Wind Harmer
0.505
3146033SCOT NK
Solar/Wind Harmer
-0.086
972205AH1-687 GEN
Adder
6.848
3152261N ANNA2
50/50
14.389
3150401LDYSMT4
50/50
37.21
3143096IRON208
Adder
1.023
3143096IRON208
Adder
1.003
3150861SPRUNCD
Adder
1.125
316458AB2-190 GEN2
Solar/Wind Harmer
2.702
961611AG1-000B GEN
Solar/Wind Harmer
5.581
3151171GRAVELC
Adder
3.289
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
5.267
3141843SHACKLE
Adder
1.183
3141873WAN 176
Solar/Wind Harmer
3.063
316246AF1-032 C
Solar/Wind Harmer
0.519
316321Z2-027
Solar/Wind Harmer
0.683
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3156081AA2-088 GEN
Solar/Wind Harmer
7.591
970917AG2-570 GEN
Solar/Wind Harmer
58.014
3147666LOUISA
Solar/Wind Harmer
-0.052
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.271
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145933PARMELE
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.423
3146233WITAKRS
Solar/Wind Harmer
-0.014
970257AG2-171 GEN
Solar/Wind Harmer
7.528
971775AH1-396 GEN
Solar/Wind Harmer
1.416
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
970085AG2-068 GEN
Solar/Wind Harmer
14.326
316463AE2-346 GEN
Solar/Wind Harmer
0.367
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145513AHOSKIE
Solar/Wind Harmer
-0.023
315652AC1-086 GEN
Solar/Wind Harmer
24.973
3137643SOCKMAN
Solar/Wind Harmer
-0.088
316426AA2-053 GEN
Solar/Wind Harmer
2.228
316174AB2-169 GEN
Solar/Wind Harmer
3.403
316327AA2-057 GEN
Solar/Wind Harmer
2.071
3144303KENBRDG
Solar/Wind Harmer
-0.016
946301AF1-294 GEN
Solar/Wind Harmer
5.121
3138216PACIFIC
Solar/Wind Helper
0.039
970293AG2-193 GEN
Solar/Wind Harmer
3.451
3150921YORKTN3
Adder
5.931
3144536CHRHLND
Solar/Wind Harmer
-0.004
944581AF1-123 GEN
Solar/Wind Harmer
118.761
3142956BIRDNECK
Solar/Wind Harmer
1.397
316203AE2-005 GEN
Solar/Wind Harmer
10.964
316305AF2-043 C
Solar/Wind Harmer
0.774
316320Y1-086
Solar/Wind Harmer
1.494
3146516WINFALL
Solar/Wind Harmer
-0.025
944011AF1-069 GEN
Solar/Wind Harmer
14.646
315735AD1-075 GEN1
Solar/Wind Harmer
2.363
3145893MURPHYS
Solar/Wind Harmer
0.161
3145893MURPHYS
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316011AB1-132 GEN
Solar/Wind Harmer
4.636
316223AC1-118
Solar/Wind Harmer
0.583
3150331BIRCHWDA
Adder
21.246
961601AG1-000A GEN
Solar/Wind Harmer
5.871
971507AH1-251 GEN
50/50
17.409
972197AH1-683 GEN
50/50
5.81
316447AC1-158 HLD
Solar/Wind Harmer
7.55
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
-0.072
3142416OLDCHRC
Solar/Wind Harmer
-0.028
315975AC1-164 GENB
Solar/Wind Harmer
0.183
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3145336SMITFLD
Solar/Wind Harmer
-0.105
316375AC2-012 GEN
Solar/Wind Harmer
9.026
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.035
3146456SLIGO L269
Solar/Wind Harmer
-0.026
958261AF2-120 GEN
Solar/Wind Harmer
9.446
3145663CRESWEL
Solar/Wind Harmer
-0.067
3146206CASHIE
Solar/Wind Harmer
-0.023
316023GEN1_S
Solar/Wind Harmer
1.556
3146173TUNIS
Solar/Wind Harmer
-0.023
3142366NRTHEST
50/50
0.857
3150691DARBY 3
Adder
17.752
3150701DARBY 4
Adder
17.711
972195AH1-682 GEN
50/50
4.881
972189AH1-679 GEN
50/50
4.545
316450AC1-158 RIC
Solar/Wind Harmer
0.915
315673AE1-157 GEN
Solar/Wind Harmer
21.889
3150681DARBY 2
Adder
17.69
316033AB2-134 GEN
Solar/Wind Harmer
8.58
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.739
316388AE2-253 GEN
Solar/Wind Harmer
1.739
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3130086AYDLETT
Solar/Wind Harmer
-0.102
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316487AF1-042 GEN
Solar/Wind Harmer
3.254
3150341NORNECKC1
Adder
2.217
3150341NORNECKC1
Adder
2.199
313506AB2-031 GEN
Solar/Wind Harmer
1.786
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
0.183
3145933PARMELE
Solar/Wind Harmer
-0.042
3145933PARMELE
Solar/Wind Harmer
-0.021
970301AG2-198 GEN
Solar/Wind Harmer
10.32
3145493TOT1
Solar/Wind Harmer
0.312
313527AB2-043 GEN
Solar/Wind Harmer
3.276
970323AG2-213 GEN
Solar/Wind Harmer
10.037
3151731LOISA B
Adder
8.022
3152251N ANNA1
50/50
14.381
315052AA1-145 CT2
50/50
2.037
3150851SPRUNCC
Adder
1.125
316132AB2-190 GEN1
Solar/Wind Harmer
2.702
315773AC2-141 GEN
Solar/Wind Harmer
11.035
316036AC1-147 C
Solar/Wind Harmer
0.702
3142296MT RD221
50/50
0.852
316045AC1-158 PL2
Solar/Wind Harmer
10.985
3150671DARBY 1
Adder
17.67
971223AH1-071 GEN
Solar/Wind Harmer
3.425
966871AG1-558 GEN
Solar/Wind Harmer
0.821
966871AG1-558 GEN
Solar/Wind Harmer
0.281
316240AF1-291 C
Solar/Wind Harmer
0.809
3150991CHESPKB
Adder
2.433
3150991CHESPKB
Adder
2.375
315666AE1-190 GEN
Solar/Wind Harmer
0.779
316156AD2-030 GEN
Solar/Wind Harmer
0.687
315835AF2-110_GEN
Solar/Wind Harmer
3.201
316435W1029_GEN3
Solar/Wind Harmer
4.572
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
972187AH1-678 GEN
Adder
6.092
315614AA2-178 GEN
Solar/Wind Harmer
2.575
316313AB2-026
Solar/Wind Harmer
0.636
316065AD1-022 GEN
Solar/Wind Harmer
11.636
3145893MURPHYS
Solar/Wind Harmer
0.644
3145893MURPHYS
Solar/Wind Harmer
-0.041
316140AB2-099
Solar/Wind Harmer
0.153
316005AA1-067
Solar/Wind Harmer
0.421
3145453TOT5
Solar/Wind Harmer
0.187
972193AH1-681 GEN
Adder
3.766
961601AG1-000A GEN
Solar/Wind Harmer
5.798
971285AH1-108 GEN
Adder
1.842
315839AE2-212 C
Solar/Wind Harmer
0.802
315697AD1-025 GEN
Solar/Wind Harmer
5.378
971445AH1-216 GEN
Solar/Wind Harmer
16.283
957831AF2-077 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
21.302
3151091ELIZAR2
Adder
20.932
316316AC1-027 C
Solar/Wind Harmer
0.798
957871AF2-081 GEN
Solar/Wind Harmer
12.918
3141913WHIT STONE
Solar/Wind Harmer
-0.025
970673AG2-436 GEN
Solar/Wind Harmer
53.996
316468AD1-105 GEN
Solar/Wind Harmer
2.715
316258AE1-075 C
Solar/Wind Harmer
0.573
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
3.344
970831AG2-522 GEN
Solar/Wind Harmer
10.522
3145746EVERETS
Solar/Wind Harmer
-0.083
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
957861AF2-080 GEN
Solar/Wind Harmer
8.972
3145573BETHELC
Solar/Wind Harmer
-0.02
3145573BETHELC
Solar/Wind Harmer
-0.02
316238AB2-078_GEN
Solar/Wind Harmer
0.605
316239AB2-077_GEN
Solar/Wind Harmer
0.605
970683AG2-441 GEN
Solar/Wind Harmer
14.145
970681AG2-440 GEN
Solar/Wind Harmer
9.388
316075AC2-137 C
Solar/Wind Harmer
0.74
315778AD1-151 GEN
Solar/Wind Harmer
23.766
3144216WINCHST
Adder
0.89
944601AF1-125 GEN
Solar/Wind Harmer
116.907
3151101ELIZAR3
Adder
21.574
316484AD2-074 GEN
Solar/Wind Harmer
6.219
316077AC2-138 C
Solar/Wind Harmer
0.501
3150351NORNECKC2
Adder
2.146
3143336POWHATN
Solar/Wind Harmer
2.386
966621AG1-532 GEN
Solar/Wind Harmer
0.457
316317KELFORD C
Solar/Wind Harmer
1.026
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
316212AC1-099_GEN
Solar/Wind Harmer
1.858
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
315722AD1-056 GEN
Solar/Wind Harmer
7.377
964241AG1-285 GEN
Solar/Wind Harmer
15.737
3144293JTRSVLE
Adder
0.425
942461AE2-259 GEN
Solar/Wind Harmer
2.986
3151761LOISA E
Adder
16.354
3151721LOISA A
Adder
7.98
3141196NOKESVL
Solar/Wind Helper
1.254
972219AH1-694 GEN
50/50
4.184
3143526WINTERP
Solar/Wind Harmer
-0.142
944631AF1-128 GEN
Adder
115.526
315671AE2-027_GEN
Solar/Wind Harmer
4.828
971317AH1-138 GEN
Solar/Wind Harmer
3.316
316314AB2-024 C
Solar/Wind Harmer
2.234
944591AF1-124 GEN
Solar/Wind Harmer
119.189
316072AD1-144
Solar/Wind Harmer
0.523
939411AE1-173 GEN
Solar/Wind Harmer
129.549
940641AE2-051 GEN
Solar/Wind Harmer
24.261
941031AE2-094 GEN
Solar/Wind Harmer
46.742
964211AG1-282 GEN
Solar/Wind Harmer
0.725
3150351NORNECKC2
Adder
2.11
3143336POWHATN
Solar/Wind Harmer
2.807
971547AH1-271 GEN
Solar/Wind Harmer
5.796
960081AF2-299 GEN
Solar/Wind Harmer
2.535
3145823KELFORD
Solar/Wind Harmer
-0.022
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
316129AC1-054 GEN
Solar/Wind Harmer
1.829
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
971065AG2-659 GEN
Solar/Wind Harmer
10.411
315976AC1-164 GENA
Solar/Wind Harmer
6.201
316169AC1-164_GENC
Solar/Wind Harmer
5.358
3142946ENON
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.528
316083AB2-161 GEN
Solar/Wind Harmer
4.234
316349AD2-085 GEN
Solar/Wind Harmer
2.29
3146456SLIGO L269
Solar/Wind Harmer
3.045
3146386ELIZ CT
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.572
316433W1029_GEN2
Solar/Wind Harmer
4.572
315742AE1-103 GEN
Solar/Wind Harmer
5.841
3146376EDENTON
Solar/Wind Harmer
0.726
3146376EDENTON
Solar/Wind Harmer
0.726
970933AG2-581 GEN
Solar/Wind Harmer
22.195
316365GEN2_N
Solar/Wind Harmer
1.556
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
14.153
958211AF2-115 GEN
Solar/Wind Harmer
3.122
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3156021HOLLOMANSOL
Solar/Wind Harmer
3.068
3145683EARLEYS
Solar/Wind Harmer
-0.023
316192AB2-158 GEN
Solar/Wind Harmer
2.618
3147043LAWRENC
Adder
1.757
3146083TARBORO
Solar/Wind Harmer
-0.02
316319Z2-044 C
Solar/Wind Harmer
1.115
316131AB2-060 GEN
Solar/Wind Harmer
2.17
970937AG2-583 GEN
Solar/Wind Harmer
14.479
972135AH1-637 GEN
Solar/Wind Harmer
2.001
961611AG1-000B GEN
Solar/Wind Harmer
13.081
3151171GRAVELC
Adder
2.501
3150981CHESPKA
Adder
2.901
316381AD1-082 GEN
Solar/Wind Harmer
2.388
315662AE1-191 GEN
Solar/Wind Harmer
3.117
316280AD1-041 GEN
Solar/Wind Harmer
1.948
319010AE1-072 C
Solar/Wind Harmer
5.2
3138133OCRAN
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.078
3130156CHOWAN
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.653
315816AE2-034 GEN
Solar/Wind Harmer
1.931
971163AH1-040 GEN
Solar/Wind Harmer
22.436
315737AD1-076 GEN
Solar/Wind Harmer
4.445
970087AG2-069 GEN
Solar/Wind Harmer
21.489
3147666LOUISA
Solar/Wind Harmer
-0.09
316087AB2-174 GEN
Solar/Wind Harmer
3.184
957481AF2-042 GEN
Solar/Wind Harmer
69.474
315693AD1-088 GEN
Solar/Wind Harmer
10.912
3146293MARTNCO
Solar/Wind Harmer
0.132
3145493TOT1
Solar/Wind Harmer
0.599
3146233WITAKRS
Solar/Wind Harmer
-0.08
315785AD2-033 C
Solar/Wind Harmer
4.546
970685AG2-442 GEN
Solar/Wind Harmer
17.506
316093AE2-104_GEN
Solar/Wind Harmer
7.446
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
962861AG1-135 GEN
Solar/Wind Harmer
9.174
3141726DUNNSVL
Solar/Wind Harmer
-0.096
970919AG2-571 GEN
Solar/Wind Harmer
7.344
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.685
316337AD2-073 GEN
Solar/Wind Harmer
0.61
315607AA1-063A GEN
Solar/Wind Harmer
2.268
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.206
961671AG1-007 GEN
Solar/Wind Harmer
0.255
971563AH1-280 GEN
Solar/Wind Harmer
2.498
3151751LOISA D
Adder
8.022
3150391LDYSMT3
50/50
37.14
316312AB1-027
Solar/Wind Harmer
0.94
3143526WINTERP
Solar/Wind Harmer
-0.142
944641AF1-129 GEN
Adder
114.506
316185AD1-033 GEN
Solar/Wind Harmer
2.738
316441AF1-014 GEN
Solar/Wind Harmer
1.753
3144356SAPONY
Solar/Wind Harmer
0.871
316315AB2-025 C
Solar/Wind Harmer
0.672
972185AH1-677 GEN
Adder
12.142
970099AG2-077 GEN
Solar/Wind Harmer
27.79
962571AG1-106 GEN
Solar/Wind Harmer
3.191
3145783HORNRTN
Solar/Wind Harmer
2.596
3145783HORNRTN
Solar/Wind Harmer
2.077
3145783HORNRTN
Solar/Wind Harmer
0.649
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.065
315724AD1-057 GEN
Solar/Wind Harmer
4.057
315687AD1-152 GEN
Solar/Wind Harmer
2.434
3145603CNETO
Solar/Wind Harmer
0.125
316237AB2-079_GEN
Solar/Wind Harmer
0.605
3144293JTRSVLE
Adder
0.425
316411AF1-147_GEN1
Solar/Wind Helper
0.811
316034AC1-036 C
Solar/Wind Harmer
0.371
3144293JTRSVLE
Adder
0.425
3144293JTRSVLE
Adder
0.335
972277AH1-723 GEN
Adder
98.218
316415AF1-147_GEN2
Solar/Wind Helper
0.811
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.227
LGEELTFEXP_LGEE->PJM
CLTF
1.325
MECLTFEXP_MEC->PJM
CLTF
3.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.185
NYPJM->LTFIMP_NY
CLTF
3.271
TVALTFEXP_TVA->PJM
CLTF
4.054
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.945
CPLELTFEXP_CPLE->PJM
CLTF
11.372
SIGELTFEXP_SIGE->PJM
CLTF
0.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.786
WECLTFEXP_WEC->PJM
CLTF
0.638
LAGNLTFEXP_LAGN->PJM
CLTF
7.994

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 515T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.01 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5461.43
MW Contribution:
86.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
14.386
315052AA1-145 CT2
50/50
2.037
3150851SPRUNCC
Adder
1.126
316132AB2-190 GEN1
Solar/Wind Harmer
2.702
315773AC2-141 GEN
Solar/Wind Harmer
11.037
316036AC1-147 C
Solar/Wind Harmer
0.702
316093AE2-104_GEN
Solar/Wind Harmer
7.447
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
962861AG1-135 GEN
Solar/Wind Harmer
9.175
3141726DUNNSVL
Solar/Wind Harmer
-0.096
970919AG2-571 GEN
Solar/Wind Harmer
7.345
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.685
316337AD2-073 GEN
Solar/Wind Harmer
0.61
315607AA1-063A GEN
Solar/Wind Harmer
2.268
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.207
961671AG1-007 GEN
Solar/Wind Harmer
0.255
972219AH1-694 GEN
50/50
4.184
3143526WINTERP
Solar/Wind Harmer
-0.142
944631AF1-128 GEN
Adder
115.543
315671AE2-027_GEN
Solar/Wind Harmer
4.829
971317AH1-138 GEN
Solar/Wind Harmer
3.316
316314AB2-024 C
Solar/Wind Harmer
2.235
944591AF1-124 GEN
Solar/Wind Harmer
119.208
316072AD1-144
Solar/Wind Harmer
0.523
939411AE1-173 GEN
Solar/Wind Harmer
129.571
940641AE2-051 GEN
Solar/Wind Harmer
24.265
941031AE2-094 GEN
Solar/Wind Harmer
46.75
964211AG1-282 GEN
Solar/Wind Harmer
0.725
3150351NORNECKC2
Adder
2.111
3143336POWHATN
Solar/Wind Harmer
2.807
971547AH1-271 GEN
Solar/Wind Harmer
5.797
960081AF2-299 GEN
Solar/Wind Harmer
2.535
3145823KELFORD
Solar/Wind Harmer
-0.022
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
316129AC1-054 GEN
Solar/Wind Harmer
1.829
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
971065AG2-659 GEN
Solar/Wind Harmer
10.412
316034AC1-036 C
Solar/Wind Harmer
0.371
3144293JTRSVLE
Adder
0.425
3144293JTRSVLE
Adder
0.335
972277AH1-723 GEN
Adder
98.225
316415AF1-147_GEN2
Solar/Wind Helper
0.811
3150391LDYSMT3
50/50
37.144
316312AB1-027
Solar/Wind Harmer
0.941
3143526WINTERP
Solar/Wind Harmer
-0.142
944641AF1-129 GEN
Adder
114.524
316185AD1-033 GEN
Solar/Wind Harmer
2.738
316441AF1-014 GEN
Solar/Wind Harmer
1.753
3144356SAPONY
Solar/Wind Harmer
0.871
316315AB2-025 C
Solar/Wind Harmer
0.672
972185AH1-677 GEN
Adder
12.144
970099AG2-077 GEN
Solar/Wind Harmer
27.794
962571AG1-106 GEN
Solar/Wind Harmer
3.192
971507AH1-251 GEN
50/50
17.357
972197AH1-683 GEN
50/50
5.811
316447AC1-158 HLD
Solar/Wind Harmer
7.555
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
-0.072
3142416OLDCHRC
Solar/Wind Harmer
-0.028
315975AC1-164 GENB
Solar/Wind Harmer
0.183
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
316044AC1-158 PL1
Solar/Wind Harmer
3.435
3143096IRON208
Adder
1.024
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
3145336SMITFLD
Solar/Wind Harmer
-0.105
316375AC2-012 GEN
Solar/Wind Harmer
9.028
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.035
3146456SLIGO L269
Solar/Wind Harmer
-0.026
958261AF2-120 GEN
Solar/Wind Harmer
9.447
3145663CRESWEL
Solar/Wind Harmer
-0.067
3146206CASHIE
Solar/Wind Harmer
-0.023
316023GEN1_S
Solar/Wind Harmer
1.556
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.068
3145683EARLEYS
Solar/Wind Harmer
-0.023
316192AB2-158 GEN
Solar/Wind Harmer
2.618
3147043LAWRENC
Adder
1.757
3146083TARBORO
Solar/Wind Harmer
-0.02
316319Z2-044 C
Solar/Wind Harmer
1.115
316131AB2-060 GEN
Solar/Wind Harmer
2.171
970937AG2-583 GEN
Solar/Wind Harmer
14.481
972135AH1-637 GEN
Solar/Wind Harmer
2.001
3142366NRTHEST
50/50
0.857
3150691DARBY 3
Adder
17.755
3150701DARBY 4
Adder
17.714
315976AC1-164 GENA
Solar/Wind Harmer
6.202
316169AC1-164_GENC
Solar/Wind Harmer
5.359
3142946ENON
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.53
971069AG2-661 GEN
Solar/Wind Harmer
4.226
316369SG1_INVT
Solar/Wind Harmer
4.753
3138126ROCKLANDING
Solar/Wind Harmer
0.081
961611AG1-000B GEN
Solar/Wind Harmer
13.083
3151171GRAVELC
Adder
2.502
3150981CHESPKA
Adder
2.901
316381AD1-082 GEN
Solar/Wind Harmer
2.388
315662AE1-191 GEN
Solar/Wind Harmer
3.118
316280AD1-041 GEN
Solar/Wind Harmer
1.948
319010AE1-072 C
Solar/Wind Harmer
5.201
3138133OCRAN
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.079
3130156CHOWAN
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.654
315816AE2-034 GEN
Solar/Wind Harmer
1.931
971163AH1-040 GEN
Solar/Wind Harmer
22.439
315737AD1-076 GEN
Solar/Wind Harmer
4.446
970087AG2-069 GEN
Solar/Wind Harmer
21.493
3147666LOUISA
Solar/Wind Harmer
-0.09
316087AB2-174 GEN
Solar/Wind Harmer
3.184
972195AH1-682 GEN
50/50
4.881
972189AH1-679 GEN
50/50
4.546
316450AC1-158 RIC
Solar/Wind Harmer
0.916
315673AE1-157 GEN
Solar/Wind Harmer
21.891
3150681DARBY 2
Adder
17.693
316033AB2-134 GEN
Solar/Wind Harmer
8.581
316083AB2-161 GEN
Solar/Wind Harmer
4.235
316349AD2-085 GEN
Solar/Wind Harmer
2.291
3146456SLIGO L269
Solar/Wind Harmer
3.046
3146386ELIZ CT
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.573
316433W1029_GEN2
Solar/Wind Harmer
4.573
315742AE1-103 GEN
Solar/Wind Harmer
5.842
3146376EDENTON
Solar/Wind Harmer
0.727
3146376EDENTON
Solar/Wind Harmer
0.727
970933AG2-581 GEN
Solar/Wind Harmer
22.199
316365GEN2_N
Solar/Wind Harmer
1.556
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
14.155
958211AF2-115 GEN
Solar/Wind Harmer
3.123
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3150371LDYSMT1
50/50
35.958
315051AA1-145 CT1
50/50
2.024
966881AG1-559 GEN
Solar/Wind Harmer
0.874
3142416OLDCHRC
Solar/Wind Harmer
2.822
316473AC1-191 GEN
Solar/Wind Harmer
2.938
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.03
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.442
3141766HARMONY
Solar/Wind Harmer
2.316
316017AA1-139 ULT1
Solar/Wind Harmer
2.085
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
2.984
3145273HOLLAND
Solar/Wind Harmer
-0.019
961951AG1-038 GEN
Solar/Wind Harmer
3.255
3146376EDENTON
Solar/Wind Harmer
-0.024
971781AH1-399 GEN
Solar/Wind Harmer
1.464
3146206CASHIE
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3150381LDYSMT2
50/50
35.726
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3151201GRAVEL4
Adder
17.117
3151221GRAVEL6
Adder
17.097
3151211GRAVEL5
Adder
16.9
316059AD1-063 C
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
13.014
313526AB2-022
Solar/Wind Harmer
0.686
3146396TANGLEW
Solar/Wind Harmer
0.467
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
315814AE2-033 C
Solar/Wind Harmer
23.17
3146206CASHIE
Solar/Wind Harmer
-0.023
316318V4-068
Solar/Wind Harmer
0.575
961941AG1-037 GEN
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
316486AD2-202 GEN
Solar/Wind Harmer
0.542
316274AC1-208 GEN
Solar/Wind Harmer
2.279
961791AG1-021 GEN
Solar/Wind Harmer
2.498
3142296MT RD221
50/50
0.852
316045AC1-158 PL2
Solar/Wind Harmer
10.991
3150671DARBY 1
Adder
17.672
971223AH1-071 GEN
Solar/Wind Harmer
3.426
966871AG1-558 GEN
Solar/Wind Harmer
0.821
966871AG1-558 GEN
Solar/Wind Harmer
0.281
316240AF1-291 C
Solar/Wind Harmer
0.809
3150991CHESPKB
Adder
2.434
3150991CHESPKB
Adder
2.375
315666AE1-190 GEN
Solar/Wind Harmer
0.779
316156AD2-030 GEN
Solar/Wind Harmer
0.687
315835AF2-110_GEN
Solar/Wind Harmer
3.202
316435W1029_GEN3
Solar/Wind Harmer
4.573
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
972187AH1-678 GEN
Adder
6.093
315614AA2-178 GEN
Solar/Wind Harmer
2.575
316313AB2-026
Solar/Wind Harmer
0.636
316065AD1-022 GEN
Solar/Wind Harmer
11.638
3145893MURPHYS
Solar/Wind Harmer
0.644
3145893MURPHYS
Solar/Wind Harmer
-0.041
316140AB2-099
Solar/Wind Harmer
0.153
316005AA1-067
Solar/Wind Harmer
0.421
3145453TOT5
Solar/Wind Harmer
0.187
972193AH1-681 GEN
Adder
3.766
961601AG1-000A GEN
Solar/Wind Harmer
5.799
3150411LDYSMT5
50/50
37.33
972215AH1-692 GEN
50/50
6.043
316233AE1-074 FULL
Solar/Wind Harmer
0.74
971283AH1-107 GEN
Solar/Wind Harmer
4.469
316164AC1-076 GEN
Solar/Wind Harmer
2.287
3151191GRAVEL3
Adder
16.9
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316018AA1-139 ULT2
Solar/Wind Harmer
2.208
957601AF2-054 GEN
Solar/Wind Harmer
0.772
315833AF1-017_GEN
Solar/Wind Harmer
4.9
3146406KITTY HAWK
Solar/Wind Harmer
0.021
315800Z1-036_GEN1
Solar/Wind Harmer
6.079
971967AH1-528 GEN
Solar/Wind Harmer
45.357
3141813NORNECK
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.729
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
970085AG2-068 GEN
Solar/Wind Harmer
14.329
316463AE2-346 GEN
Solar/Wind Harmer
0.367
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145513AHOSKIE
Solar/Wind Harmer
-0.023
315652AC1-086 GEN
Solar/Wind Harmer
24.977
3137643SOCKMAN
Solar/Wind Harmer
-0.088
316426AA2-053 GEN
Solar/Wind Harmer
2.229
316174AB2-169 GEN
Solar/Wind Harmer
3.403
316327AA2-057 GEN
Solar/Wind Harmer
2.072
3144303KENBRDG
Solar/Wind Harmer
-0.016
946301AF1-294 GEN
Solar/Wind Harmer
5.121
3138216PACIFIC
Solar/Wind Helper
0.039
3145783HORNRTN
Solar/Wind Harmer
2.596
3145783HORNRTN
Solar/Wind Harmer
2.077
3145783HORNRTN
Solar/Wind Harmer
0.649
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.065
315724AD1-057 GEN
Solar/Wind Harmer
4.058
315687AD1-152 GEN
Solar/Wind Harmer
2.435
3145603CNETO
Solar/Wind Harmer
0.125
316237AB2-079_GEN
Solar/Wind Harmer
0.605
3144293JTRSVLE
Adder
0.425
316411AF1-147_GEN1
Solar/Wind Helper
0.811
971285AH1-108 GEN
Adder
1.842
315839AE2-212 C
Solar/Wind Harmer
0.802
315697AD1-025 GEN
Solar/Wind Harmer
5.378
971445AH1-216 GEN
Solar/Wind Harmer
16.285
957831AF2-077 GEN
Solar/Wind Harmer
0.787
970293AG2-193 GEN
Solar/Wind Harmer
3.452
3150921YORKTN3
Adder
5.932
3144536CHRHLND
Solar/Wind Harmer
-0.004
944581AF1-123 GEN
Solar/Wind Harmer
118.78
3142956BIRDNECK
Solar/Wind Harmer
1.398
316203AE2-005 GEN
Solar/Wind Harmer
10.965
316305AF2-043 C
Solar/Wind Harmer
0.774
316320Y1-086
Solar/Wind Harmer
1.494
3146516WINFALL
Solar/Wind Harmer
-0.025
944011AF1-069 GEN
Solar/Wind Harmer
14.648
315735AD1-075 GEN1
Solar/Wind Harmer
2.364
3145893MURPHYS
Solar/Wind Harmer
0.161
3145893MURPHYS
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316011AB1-132 GEN
Solar/Wind Harmer
4.637
316223AC1-118
Solar/Wind Harmer
0.583
3150331BIRCHWDA
Adder
21.248
961601AG1-000A GEN
Solar/Wind Harmer
5.872
3151081ELIZAR1
Adder
21.305
3151091ELIZAR2
Adder
20.935
316316AC1-027 C
Solar/Wind Harmer
0.798
957871AF2-081 GEN
Solar/Wind Harmer
12.921
3141913WHIT STONE
Solar/Wind Harmer
-0.025
970673AG2-436 GEN
Solar/Wind Harmer
54.005
316468AD1-105 GEN
Solar/Wind Harmer
2.716
316258AE1-075 C
Solar/Wind Harmer
0.573
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
3.344
970831AG2-522 GEN
Solar/Wind Harmer
10.524
3145746EVERETS
Solar/Wind Harmer
-0.083
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
957861AF2-080 GEN
Solar/Wind Harmer
8.973
3145573BETHELC
Solar/Wind Harmer
-0.02
3145573BETHELC
Solar/Wind Harmer
-0.02
316238AB2-078_GEN
Solar/Wind Harmer
0.605
316239AB2-077_GEN
Solar/Wind Harmer
0.605
970683AG2-441 GEN
Solar/Wind Harmer
14.147
970681AG2-440 GEN
Solar/Wind Harmer
9.389
316181AB2-040 GEN
Solar/Wind Harmer
3.103
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.851
316420AA1-050 GEN
Solar/Wind Harmer
2.317
3146073TAR RVR
Solar/Wind Harmer
-0.02
3146083TARBORO
Solar/Wind Harmer
-0.02
3138543CONSLDL
Solar/Wind Harmer
-0.013
959311AF2-222 GEN
Solar/Wind Harmer
20.942
3147133PAMPLIN
Solar/Wind Harmer
-0.062
972255AH1-712 GEN
Adder
84.292
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.739
316388AE2-253 GEN
Solar/Wind Harmer
1.739
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3130086AYDLETT
Solar/Wind Harmer
-0.102
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
971531AH1-263 GEN
50/50
86.339
972213AH1-691 GEN
50/50
6.043
971281AH1-106 GEN
Solar/Wind Harmer
4.469
316382AG1-145 C
Solar/Wind Harmer
0.806
316159AE1-175 C
Solar/Wind Harmer
0.718
316236AE1-162_GEN
Solar/Wind Harmer
0.791
3143316POE
Solar/Wind Harmer
-0.103
3143873LANEXA
Solar/Wind Harmer
-0.016
970657AG2-426 GEN
Solar/Wind Harmer
1.644
3141873WAN 176
Solar/Wind Harmer
-0.005
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
970533AG2-339 GEN
Solar/Wind Harmer
16.767
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
316405AF2-144 C
Solar/Wind Harmer
0.604
3130546PLYMOUTH
Solar/Wind Harmer
-0.023
315733AD1-074 GEN2
Solar/Wind Harmer
4.729
970601AG2-382 GEN
Solar/Wind Harmer
10.144
970581AG2-369 GEN
Solar/Wind Harmer
12.323
946281AF1-292 GEN
Solar/Wind Harmer
0.505
3146033SCOT NK
Solar/Wind Harmer
-0.086
972205AH1-687 GEN
Adder
6.848
3152261N ANNA2
50/50
14.393
3150401LDYSMT4
50/50
37.213
3143096IRON208
Adder
1.024
3143096IRON208
Adder
1.003
3150861SPRUNCD
Adder
1.126
316458AB2-190 GEN2
Solar/Wind Harmer
2.702
961611AG1-000B GEN
Solar/Wind Harmer
5.582
3151171GRAVELC
Adder
3.289
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
5.268
3141843SHACKLE
Adder
1.183
3141873WAN 176
Solar/Wind Harmer
3.063
316246AF1-032 C
Solar/Wind Harmer
0.519
316321Z2-027
Solar/Wind Harmer
0.683
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3156081AA2-088 GEN
Solar/Wind Harmer
7.593
970917AG2-570 GEN
Solar/Wind Harmer
58.024
3147666LOUISA
Solar/Wind Harmer
-0.052
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.271
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145933PARMELE
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.423
3146233WITAKRS
Solar/Wind Harmer
-0.014
970257AG2-171 GEN
Solar/Wind Harmer
7.529
971775AH1-396 GEN
Solar/Wind Harmer
1.417
957481AF2-042 GEN
Solar/Wind Harmer
69.485
315693AD1-088 GEN
Solar/Wind Harmer
10.913
3146293MARTNCO
Solar/Wind Harmer
0.132
3145493TOT1
Solar/Wind Harmer
0.599
3146233WITAKRS
Solar/Wind Harmer
-0.08
315785AD2-033 C
Solar/Wind Harmer
4.546
970685AG2-442 GEN
Solar/Wind Harmer
17.509
971563AH1-280 GEN
Solar/Wind Harmer
2.498
3151751LOISA D
Adder
8.017
316487AF1-042 GEN
Solar/Wind Harmer
3.255
3150341NORNECKC1
Adder
2.217
3150341NORNECKC1
Adder
2.199
313506AB2-031 GEN
Solar/Wind Harmer
1.786
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
0.183
3145933PARMELE
Solar/Wind Harmer
-0.042
3145933PARMELE
Solar/Wind Harmer
-0.021
970301AG2-198 GEN
Solar/Wind Harmer
10.321
3145493TOT1
Solar/Wind Harmer
0.313
313527AB2-043 GEN
Solar/Wind Harmer
3.277
970323AG2-213 GEN
Solar/Wind Harmer
10.039
3151731LOISA B
Adder
8.017
316075AC2-137 C
Solar/Wind Harmer
0.74
315778AD1-151 GEN
Solar/Wind Harmer
23.77
3144216WINCHST
Adder
0.89
944601AF1-125 GEN
Solar/Wind Harmer
116.926
3151101ELIZAR3
Adder
21.578
316484AD2-074 GEN
Solar/Wind Harmer
6.22
316077AC2-138 C
Solar/Wind Harmer
0.501
3150351NORNECKC2
Adder
2.146
3143336POWHATN
Solar/Wind Harmer
2.386
966621AG1-532 GEN
Solar/Wind Harmer
0.457
316317KELFORD C
Solar/Wind Harmer
1.027
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
316212AC1-099_GEN
Solar/Wind Harmer
1.858
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
315722AD1-056 GEN
Solar/Wind Harmer
7.378
964241AG1-285 GEN
Solar/Wind Harmer
15.739
3144293JTRSVLE
Adder
0.425
942461AE2-259 GEN
Solar/Wind Harmer
2.987
3151761LOISA E
Adder
16.344
3151721LOISA A
Adder
7.975
3141196NOKESVL
Solar/Wind Helper
1.254
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.232
LGEELTFEXP_LGEE->PJM
CLTF
1.325
MECLTFEXP_MEC->PJM
CLTF
3.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.187
NYPJM->LTFIMP_NY
CLTF
3.271
TVALTFEXP_TVA->PJM
CLTF
4.055
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.949
CPLELTFEXP_CPLE->PJM
CLTF
11.373
SIGELTFEXP_SIGE->PJM
CLTF
0.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.788
WECLTFEXP_WEC->PJM
CLTF
0.638
LAGNLTFEXP_LAGN->PJM
CLTF
7.995

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.65 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5342.95
MW Contribution:
86.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150381LDYSMT2
50/50
35.846
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3151201GRAVEL4
Adder
17.18
3151221GRAVEL6
Adder
17.16
3151211GRAVEL5
Adder
16.963
316059AD1-063 C
Solar/Wind Harmer
0.589
316311AC2-079 GEN
Solar/Wind Harmer
13.063
313526AB2-022
Solar/Wind Harmer
0.689
3146396TANGLEW
Solar/Wind Harmer
0.469
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
315814AE2-033 C
Solar/Wind Harmer
23.261
3146206CASHIE
Solar/Wind Harmer
-0.023
316318V4-068
Solar/Wind Harmer
0.578
961941AG1-037 GEN
Solar/Wind Harmer
0.172
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
316486AD2-202 GEN
Solar/Wind Harmer
0.544
316274AC1-208 GEN
Solar/Wind Harmer
2.29
961791AG1-021 GEN
Solar/Wind Harmer
2.511
3150371LDYSMT1
50/50
36.079
315051AA1-145 CT1
50/50
2.031
966881AG1-559 GEN
Solar/Wind Harmer
0.877
3142416OLDCHRC
Solar/Wind Harmer
2.832
316473AC1-191 GEN
Solar/Wind Harmer
2.948
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.041
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.503
3141766HARMONY
Solar/Wind Harmer
2.325
316017AA1-139 ULT1
Solar/Wind Harmer
2.093
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
2.996
3145273HOLLAND
Solar/Wind Harmer
-0.019
961951AG1-038 GEN
Solar/Wind Harmer
3.268
3146376EDENTON
Solar/Wind Harmer
-0.025
971781AH1-399 GEN
Solar/Wind Harmer
1.471
3146206CASHIE
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.117
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.859
316420AA1-050 GEN
Solar/Wind Harmer
2.328
3146073TAR RVR
Solar/Wind Harmer
-0.02
3146083TARBORO
Solar/Wind Harmer
-0.02
3138543CONSLDL
Solar/Wind Harmer
-0.013
959311AF2-222 GEN
Solar/Wind Harmer
21.045
3147133PAMPLIN
Solar/Wind Harmer
-0.063
972255AH1-712 GEN
Adder
84.749
971531AH1-263 GEN
50/50
86.589
972213AH1-691 GEN
50/50
6.064
971281AH1-106 GEN
Solar/Wind Harmer
4.485
316382AG1-145 C
Solar/Wind Harmer
0.809
316159AE1-175 C
Solar/Wind Harmer
0.72
316236AE1-162_GEN
Solar/Wind Harmer
0.794
3143316POE
Solar/Wind Harmer
-0.104
3143873LANEXA
Solar/Wind Harmer
-0.016
970657AG2-426 GEN
Solar/Wind Harmer
1.65
3141873WAN 176
Solar/Wind Harmer
-0.005
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
970533AG2-339 GEN
Solar/Wind Harmer
16.832
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316405AF2-144 C
Solar/Wind Harmer
0.607
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315733AD1-074 GEN2
Solar/Wind Harmer
4.749
970601AG2-382 GEN
Solar/Wind Harmer
10.187
970581AG2-369 GEN
Solar/Wind Harmer
12.375
946281AF1-292 GEN
Solar/Wind Harmer
0.507
3146033SCOT NK
Solar/Wind Harmer
-0.087
972205AH1-687 GEN
Adder
6.886
3152261N ANNA2
50/50
14.431
3150401LDYSMT4
50/50
37.339
3143096IRON208
Adder
1.027
3143096IRON208
Adder
1.007
3150861SPRUNCD
Adder
1.13
316458AB2-190 GEN2
Solar/Wind Harmer
2.712
961611AG1-000B GEN
Solar/Wind Harmer
5.603
3151171GRAVELC
Adder
3.302
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
5.287
3141843SHACKLE
Adder
1.187
3141873WAN 176
Solar/Wind Harmer
3.075
316246AF1-032 C
Solar/Wind Harmer
0.521
316321Z2-027
Solar/Wind Harmer
0.686
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3156081AA2-088 GEN
Solar/Wind Harmer
7.624
970917AG2-570 GEN
Solar/Wind Harmer
58.268
3147666LOUISA
Solar/Wind Harmer
-0.052
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.272
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145933PARMELE
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.425
3146233WITAKRS
Solar/Wind Harmer
-0.014
970257AG2-171 GEN
Solar/Wind Harmer
7.566
971775AH1-396 GEN
Solar/Wind Harmer
1.424
3150411LDYSMT5
50/50
37.455
972215AH1-692 GEN
50/50
6.064
316233AE1-074 FULL
Solar/Wind Harmer
0.742
971283AH1-107 GEN
Solar/Wind Harmer
4.485
316164AC1-076 GEN
Solar/Wind Harmer
2.308
3151191GRAVEL3
Adder
16.963
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316018AA1-139 ULT2
Solar/Wind Harmer
2.216
957601AF2-054 GEN
Solar/Wind Harmer
0.775
315833AF1-017_GEN
Solar/Wind Harmer
4.919
3146406KITTY HAWK
Solar/Wind Harmer
0.021
315800Z1-036_GEN1
Solar/Wind Harmer
6.103
971967AH1-528 GEN
Solar/Wind Harmer
45.541
3141813NORNECK
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.749
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
970085AG2-068 GEN
Solar/Wind Harmer
14.39
316463AE2-346 GEN
Solar/Wind Harmer
0.369
3145513AHOSKIE
Solar/Wind Harmer
0.199
3145513AHOSKIE
Solar/Wind Harmer
-0.023
315652AC1-086 GEN
Solar/Wind Harmer
25.088
3137643SOCKMAN
Solar/Wind Harmer
-0.088
316426AA2-053 GEN
Solar/Wind Harmer
2.238
316174AB2-169 GEN
Solar/Wind Harmer
3.418
316327AA2-057 GEN
Solar/Wind Harmer
2.082
3144303KENBRDG
Solar/Wind Harmer
-0.016
946301AF1-294 GEN
Solar/Wind Harmer
5.147
3138216PACIFIC
Solar/Wind Helper
0.039
970293AG2-193 GEN
Solar/Wind Harmer
3.464
3150921YORKTN3
Adder
5.954
3144536CHRHLND
Solar/Wind Harmer
-0.004
944581AF1-123 GEN
Solar/Wind Harmer
119.224
3142956BIRDNECK
Solar/Wind Harmer
1.403
316203AE2-005 GEN
Solar/Wind Harmer
11.007
316305AF2-043 C
Solar/Wind Harmer
0.777
316320Y1-086
Solar/Wind Harmer
1.5
3146516WINFALL
Solar/Wind Harmer
-0.025
944011AF1-069 GEN
Solar/Wind Harmer
14.706
315735AD1-075 GEN1
Solar/Wind Harmer
2.374
3145893MURPHYS
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
316011AB1-132 GEN
Solar/Wind Harmer
4.657
316223AC1-118
Solar/Wind Harmer
0.586
961601AG1-000A GEN
Solar/Wind Harmer
7.931
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3150331BIRCHWDA
Adder
21.4
3142296MT RD221
50/50
0.855
3150671DARBY 1
Adder
17.735
971223AH1-071 GEN
Solar/Wind Harmer
3.438
966871AG1-558 GEN
Solar/Wind Harmer
0.824
966871AG1-558 GEN
Solar/Wind Harmer
0.282
316240AF1-291 C
Solar/Wind Harmer
0.812
3150991CHESPKB
Adder
2.443
3150991CHESPKB
Adder
2.384
315666AE1-190 GEN
Solar/Wind Harmer
0.782
316156AD2-030 GEN
Solar/Wind Harmer
0.69
315835AF2-110_GEN
Solar/Wind Harmer
3.214
316435W1029_GEN3
Solar/Wind Harmer
4.59
3146516WINFALL
Solar/Wind Harmer
-0.025
971285AH1-108 GEN
Adder
1.848
315839AE2-212 C
Solar/Wind Harmer
0.805
315697AD1-025 GEN
Solar/Wind Harmer
5.398
971445AH1-216 GEN
Solar/Wind Harmer
16.346
957831AF2-077 GEN
Solar/Wind Harmer
0.79
3151081ELIZAR1
Adder
21.385
3151091ELIZAR2
Adder
21.013
316316AC1-027 C
Solar/Wind Harmer
0.801
957871AF2-081 GEN
Solar/Wind Harmer
12.969
3141913WHIT STONE
Solar/Wind Harmer
-0.026
970673AG2-436 GEN
Solar/Wind Harmer
54.218
316468AD1-105 GEN
Solar/Wind Harmer
2.727
316258AE1-075 C
Solar/Wind Harmer
0.575
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
3.359
970831AG2-522 GEN
Solar/Wind Harmer
10.573
3145746EVERETS
Solar/Wind Harmer
-0.083
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
957861AF2-080 GEN
Solar/Wind Harmer
9.016
3145573BETHELC
Solar/Wind Harmer
-0.02
3145573BETHELC
Solar/Wind Harmer
-0.02
316238AB2-078_GEN
Solar/Wind Harmer
0.608
316239AB2-077_GEN
Solar/Wind Harmer
0.608
970683AG2-441 GEN
Solar/Wind Harmer
14.217
970681AG2-440 GEN
Solar/Wind Harmer
9.436
316075AC2-137 C
Solar/Wind Harmer
0.742
315778AD1-151 GEN
Solar/Wind Harmer
23.857
3144216WINCHST
Adder
0.893
944601AF1-125 GEN
Solar/Wind Harmer
117.363
3151101ELIZAR3
Adder
21.658
316484AD2-074 GEN
Solar/Wind Harmer
6.245
316077AC2-138 C
Solar/Wind Harmer
0.503
3150351NORNECKC2
Adder
2.155
3143336POWHATN
Solar/Wind Harmer
2.396
966621AG1-532 GEN
Solar/Wind Harmer
0.459
316317KELFORD C
Solar/Wind Harmer
1.031
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
316212AC1-099_GEN
Solar/Wind Harmer
1.866
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
315722AD1-056 GEN
Solar/Wind Harmer
7.413
964241AG1-285 GEN
Solar/Wind Harmer
15.817
3144293JTRSVLE
Adder
0.427
942461AE2-259 GEN
Solar/Wind Harmer
3.001
3151761LOISA E
Adder
16.474
3151721LOISA A
Adder
8.039
3141196NOKESVL
Solar/Wind Helper
1.246
3142366NRTHEST
50/50
0.86
3150691DARBY 3
Adder
17.818
3150701DARBY 4
Adder
17.776
315976AC1-164 GENA
Solar/Wind Harmer
6.225
316169AC1-164_GENC
Solar/Wind Harmer
5.378
3142946ENON
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.561
316083AB2-161 GEN
Solar/Wind Harmer
4.251
316349AD2-085 GEN
Solar/Wind Harmer
2.299
3146456SLIGO L269
Solar/Wind Harmer
3.057
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.59
316433W1029_GEN2
Solar/Wind Harmer
4.59
315742AE1-103 GEN
Solar/Wind Harmer
5.865
3146376EDENTON
Solar/Wind Harmer
0.729
3146376EDENTON
Solar/Wind Harmer
0.729
970933AG2-581 GEN
Solar/Wind Harmer
22.291
316365GEN2_N
Solar/Wind Harmer
1.563
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
14.217
958211AF2-115 GEN
Solar/Wind Harmer
3.138
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
971507AH1-251 GEN
50/50
17.449
972197AH1-683 GEN
50/50
5.831
966881AG1-559 GEN
Solar/Wind Harmer
0.3
3142416OLDCHRC
Solar/Wind Harmer
-0.073
3142416OLDCHRC
Solar/Wind Harmer
-0.028
315975AC1-164 GENB
Solar/Wind Harmer
0.184
3142433PROV 92
Solar/Wind Harmer
-0.106
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3145336SMITFLD
Solar/Wind Harmer
-0.105
316375AC2-012 GEN
Solar/Wind Harmer
9.062
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.047
3146456SLIGO L269
Solar/Wind Harmer
-0.026
958261AF2-120 GEN
Solar/Wind Harmer
9.485
3145663CRESWEL
Solar/Wind Harmer
-0.067
3146206CASHIE
Solar/Wind Harmer
-0.023
316023GEN1_S
Solar/Wind Harmer
1.563
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.081
3145683EARLEYS
Solar/Wind Harmer
-0.023
316192AB2-158 GEN
Solar/Wind Harmer
2.63
3147043LAWRENC
Adder
1.765
3146083TARBORO
Solar/Wind Harmer
-0.02
316319Z2-044 C
Solar/Wind Harmer
1.121
316131AB2-060 GEN
Solar/Wind Harmer
2.181
970937AG2-583 GEN
Solar/Wind Harmer
14.553
972135AH1-637 GEN
Solar/Wind Harmer
2.011
972195AH1-682 GEN
50/50
4.898
972189AH1-679 GEN
50/50
4.561
315673AE1-157 GEN
Solar/Wind Harmer
21.965
3150681DARBY 2
Adder
17.755
316033AB2-134 GEN
Solar/Wind Harmer
8.613
3145506HICKORY
Solar/Wind Harmer
-0.104
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.746
316388AE2-253 GEN
Solar/Wind Harmer
1.746
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316487AF1-042 GEN
Solar/Wind Harmer
3.268
3150341NORNECKC1
Adder
2.226
3150341NORNECKC1
Adder
2.208
313506AB2-031 GEN
Solar/Wind Harmer
1.794
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
0.184
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.021
970301AG2-198 GEN
Solar/Wind Harmer
10.371
3145493TOT1
Solar/Wind Harmer
0.314
313527AB2-043 GEN
Solar/Wind Harmer
3.293
970323AG2-213 GEN
Solar/Wind Harmer
10.088
316049AB1-081 GEN
Solar/Wind Harmer
2.143
3151731LOISA B
Adder
8.081
316450AC1-158 RIC
Solar/Wind Helper
0.575
316359AB2-059 GEN
Solar/Wind Harmer
2.678
316447AC1-158 HLD
Solar/Wind Helper
4.741
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
972187AH1-678 GEN
Adder
6.118
315614AA2-178 GEN
Solar/Wind Harmer
2.586
316313AB2-026
Solar/Wind Harmer
0.639
316065AD1-022 GEN
Solar/Wind Harmer
11.687
3145893MURPHYS
Solar/Wind Harmer
0.647
3145893MURPHYS
Solar/Wind Harmer
-0.042
316140AB2-099
Solar/Wind Harmer
0.154
316005AA1-067
Solar/Wind Harmer
0.423
3145453TOT5
Solar/Wind Harmer
0.188
961601AG1-000A GEN
Solar/Wind Harmer
7.832
972193AH1-681 GEN
Adder
3.787
316045AC1-158 PL2
Solar/Wind Helper
6.895
3152251N ANNA1
50/50
14.423
315052AA1-145 CT2
50/50
2.044
3150851SPRUNCC
Adder
1.13
316132AB2-190 GEN1
Solar/Wind Harmer
2.712
315773AC2-141 GEN
Solar/Wind Harmer
11.077
316036AC1-147 C
Solar/Wind Harmer
0.705
316093AE2-104_GEN
Solar/Wind Harmer
7.476
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
962861AG1-135 GEN
Solar/Wind Harmer
9.212
3141726DUNNSVL
Solar/Wind Harmer
-0.096
970919AG2-571 GEN
Solar/Wind Harmer
7.376
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.688
316337AD2-073 GEN
Solar/Wind Harmer
0.613
315607AA1-063A GEN
Solar/Wind Harmer
2.278
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.217
961671AG1-007 GEN
Solar/Wind Harmer
0.257
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3143096IRON208
Adder
1.027
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
971069AG2-661 GEN
Solar/Wind Harmer
4.241
316369SG1_INVT
Solar/Wind Harmer
4.77
3138126ROCKLANDING
Solar/Wind Harmer
0.081
961611AG1-000B GEN
Solar/Wind Harmer
13.131
3151171GRAVELC
Adder
2.511
3150981CHESPKA
Adder
2.912
316381AD1-082 GEN
Solar/Wind Harmer
2.397
315662AE1-191 GEN
Solar/Wind Harmer
3.129
316280AD1-041 GEN
Solar/Wind Harmer
1.956
319010AE1-072 C
Solar/Wind Harmer
5.221
3138133OCRAN
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.103
3130156CHOWAN
Solar/Wind Harmer
-0.025
316404AE1-155 C
Solar/Wind Harmer
4.673
315816AE2-034 GEN
Solar/Wind Harmer
1.939
971163AH1-040 GEN
Solar/Wind Harmer
22.531
315737AD1-076 GEN
Solar/Wind Harmer
4.464
970087AG2-069 GEN
Solar/Wind Harmer
21.585
3147666LOUISA
Solar/Wind Harmer
-0.09
316087AB2-174 GEN
Solar/Wind Harmer
3.198
957481AF2-042 GEN
Solar/Wind Harmer
69.792
315693AD1-088 GEN
Solar/Wind Harmer
10.962
3146293MARTNCO
Solar/Wind Harmer
0.133
3145493TOT1
Solar/Wind Harmer
0.602
3146233WITAKRS
Solar/Wind Harmer
-0.08
315785AD2-033 C
Solar/Wind Harmer
4.569
970685AG2-442 GEN
Solar/Wind Harmer
17.595
971563AH1-280 GEN
Solar/Wind Harmer
2.511
3151751LOISA D
Adder
8.081
316044AC1-158 PL1
Solar/Wind Helper
2.155
3150391LDYSMT3
50/50
37.269
316312AB1-027
Solar/Wind Harmer
0.944
3143526WINTERP
Solar/Wind Harmer
-0.143
944641AF1-129 GEN
Adder
114.938
316185AD1-033 GEN
Solar/Wind Harmer
2.748
316441AF1-014 GEN
Solar/Wind Harmer
1.76
3144356SAPONY
Solar/Wind Harmer
0.874
316315AB2-025 C
Solar/Wind Harmer
0.675
972185AH1-677 GEN
Adder
12.193
970099AG2-077 GEN
Solar/Wind Harmer
27.917
962571AG1-106 GEN
Solar/Wind Harmer
3.206
3145783HORNRTN
Solar/Wind Harmer
2.608
3145783HORNRTN
Solar/Wind Harmer
2.086
3145783HORNRTN
Solar/Wind Harmer
0.652
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
-0.065
315724AD1-057 GEN
Solar/Wind Harmer
4.077
315687AD1-152 GEN
Solar/Wind Harmer
2.447
3145603CNETO
Solar/Wind Harmer
0.126
316237AB2-079_GEN
Solar/Wind Harmer
0.608
3144293JTRSVLE
Adder
0.427
316411AF1-147_GEN1
Solar/Wind Helper
0.805
316263AC1-034 GEN
Solar/Wind Harmer
4.211
972219AH1-694 GEN
50/50
4.198
3143526WINTERP
Solar/Wind Harmer
-0.143
944631AF1-128 GEN
Adder
115.958
315671AE2-027_GEN
Solar/Wind Harmer
4.847
971317AH1-138 GEN
Solar/Wind Harmer
3.329
316314AB2-024 C
Solar/Wind Harmer
2.243
944591AF1-124 GEN
Solar/Wind Harmer
119.653
316072AD1-144
Solar/Wind Harmer
0.525
939411AE1-173 GEN
Solar/Wind Harmer
130.058
940641AE2-051 GEN
Solar/Wind Harmer
24.356
941031AE2-094 GEN
Solar/Wind Harmer
46.933
964211AG1-282 GEN
Solar/Wind Harmer
0.728
3150351NORNECKC2
Adder
2.119
3143336POWHATN
Solar/Wind Harmer
2.819
971547AH1-271 GEN
Solar/Wind Harmer
5.821
960081AF2-299 GEN
Solar/Wind Harmer
2.546
3145823KELFORD
Solar/Wind Harmer
-0.022
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
316129AC1-054 GEN
Solar/Wind Harmer
1.838
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
971065AG2-659 GEN
Solar/Wind Harmer
10.461
316034AC1-036 C
Solar/Wind Harmer
0.373
3144293JTRSVLE
Adder
0.427
3144293JTRSVLE
Adder
0.337
972277AH1-723 GEN
Adder
98.758
316415AF1-147_GEN2
Solar/Wind Helper
0.805
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.162
LGEELTFEXP_LGEE->PJM
CLTF
1.373
MECLTFEXP_MEC->PJM
CLTF
3.715
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.199
NYPJM->LTFIMP_NY
CLTF
3.226
TVALTFEXP_TVA->PJM
CLTF
4.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.156
CPLELTFEXP_CPLE->PJM
CLTF
11.448
SIGELTFEXP_SIGE->PJM
CLTF
0.113
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.05
WECLTFEXP_WEC->PJM
CLTF
0.665
LAGNLTFEXP_LAGN->PJM
CLTF
8.135

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.15 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3901.64
MW Contribution:
38.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315052AA1-145 CT2
50/50
1.577
3150851SPRUNCC
Adder
0.843
316132AB2-190 GEN1
Solar/Wind Harmer
0.957
315773AC2-141 GEN
Solar/Wind Harmer
6.405
316036AC1-147 C
Solar/Wind Harmer
0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.865
3146516WINFALL
Solar/Wind Harmer
0.543
3146516WINFALL
Solar/Wind Harmer
0.167
962861AG1-135 GEN
Solar/Wind Harmer
5.01
3145893MURPHYS
Solar/Wind Harmer
0.616
3145893MURPHYS
Solar/Wind Harmer
0.685
3141726DUNNSVL
Solar/Wind Harmer
0.611
970919AG2-571 GEN
Solar/Wind Harmer
5.394
315607AA1-063A GEN
Solar/Wind Harmer
0.302
972219AH1-694 GEN
50/50
3.203
944631AF1-128 GEN
Adder
87.526
3143526WINTERP
Solar/Wind Harmer
0.936
315671AE2-027_GEN
Solar/Wind Harmer
0.001
971317AH1-138 GEN
Solar/Wind Harmer
1.326
944591AF1-124 GEN
Solar/Wind Harmer
39.202
316072AD1-144
Solar/Wind Harmer
0.061
939411AE1-173 GEN
Solar/Wind Harmer
72.216
940641AE2-051 GEN
Solar/Wind Harmer
13.444
941031AE2-094 GEN
Solar/Wind Harmer
29.76
3150391LDYSMT3
50/50
28.436
316312AB1-027
Solar/Wind Harmer
0.341
944641AF1-129 GEN
Adder
86.186
3143526WINTERP
Solar/Wind Harmer
0.936
972197AH1-683 GEN
50/50
4.449
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
0.498
3142416OLDCHRC
Solar/Wind Harmer
0.191
315975AC1-164 GENB
Solar/Wind Harmer
0.058
3142433PROV 92
Solar/Wind Harmer
0.707
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3145336SMITFLD
Solar/Wind Harmer
0.701
316375AC2-012 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
0.034
3143096IRON208
Adder
0.775
3142543TWELFTH
Solar/Wind Harmer
0.018
971069AG2-661 GEN
Solar/Wind Harmer
3.178
3142366NRTHEST
50/50
0.655
3150691DARBY 3
Adder
13.558
3150701DARBY 4
Adder
13.527
315976AC1-164 GENA
Solar/Wind Harmer
1.947
316169AC1-164_GENC
Solar/Wind Harmer
1.682
3142946ENON
Solar/Wind Harmer
0.018
316294AC1-161 GEN
Solar/Wind Harmer
3.032
3150371LDYSMT1
50/50
27.528
315051AA1-145 CT1
50/50
1.568
3142416OLDCHRC
Solar/Wind Harmer
1.859
316473AC1-191 GEN
Solar/Wind Harmer
0.624
3142946ENON
Solar/Wind Harmer
0.062
970133AG2-095 GEN
Solar/Wind Harmer
1.734
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3145336SMITFLD
Solar/Wind Harmer
0.07
315813AE1-149 C
Solar/Wind Harmer
9.324
3141766HARMONY
Solar/Wind Harmer
2.298
3150381LDYSMT2
50/50
27.35
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151201GRAVEL4
Adder
12.843
3151221GRAVEL6
Adder
12.828
3151211GRAVEL5
Adder
12.68
316311AC2-079 GEN
Solar/Wind Harmer
4.926
313526AB2-022
Solar/Wind Harmer
0.091
3146396TANGLEW
Solar/Wind Harmer
0.466
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
315814AE2-033 C
Solar/Wind Harmer
12.96
3146206CASHIE
Solar/Wind Harmer
0.155
3145683EARLEYS
Solar/Wind Harmer
0.303
3145683EARLEYS
Solar/Wind Harmer
0.151
3145683EARLEYS
Solar/Wind Harmer
0.151
3146043SEABORD
Solar/Wind Harmer
0.151
316274AC1-208 GEN
Solar/Wind Harmer
0.732
316486AD2-202 GEN
Solar/Wind Harmer
0.144
961791AG1-021 GEN
Solar/Wind Harmer
1.294
971845AH1-439 GEN
Solar/Wind Harmer
5.912
3147173SINAI
Solar/Wind Harmer
0.124
3147243WELCO
Solar/Wind Harmer
0.078
971777AH1-397 GEN
Solar/Wind Harmer
0.454
3146456SLIGO L269
Solar/Wind Harmer
0.171
3145663CRESWEL
Solar/Wind Harmer
0.447
958261AF2-120 GEN
Solar/Wind Harmer
5.148
3146206CASHIE
Solar/Wind Harmer
0.155
316023GEN1_S
Solar/Wind Harmer
0.341
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.686
3145683EARLEYS
Solar/Wind Harmer
0.151
3147043LAWRENC
Adder
1.317
970937AG2-583 GEN
Solar/Wind Harmer
8.399
3146083TARBORO
Solar/Wind Harmer
0.136
316131AB2-060 GEN
Solar/Wind Harmer
0.422
316359AB2-059 GEN
Solar/Wind Harmer
0.475
3142053HEARTS
Solar/Wind Harmer
0.235
316192AB2-158 GEN
Solar/Wind Harmer
0.738
3146263WOODLND
Solar/Wind Harmer
0.15
3145963POPLR C
Solar/Wind Harmer
0.149
316337AD2-073 GEN
Solar/Wind Harmer
0.12
316494AC1-189 GEN
Solar/Wind Harmer
0.466
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3145543BTLEBRO
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.107
3146776BUCKING
Solar/Wind Harmer
0.052
3142296MT RD221
50/50
0.659
3150671DARBY 1
Adder
13.495
966871AG1-558 GEN
Solar/Wind Harmer
0.214
971223AH1-071 GEN
Solar/Wind Harmer
1.883
3150991CHESPKB
Adder
1.818
3150991CHESPKB
Adder
1.775
3150411LDYSMT5
50/50
28.578
972215AH1-692 GEN
50/50
4.627
316233AE1-074 FULL
Solar/Wind Harmer
0.144
971283AH1-107 GEN
Solar/Wind Harmer
2.497
3151191GRAVEL3
Adder
12.68
3138283WHITEMARSH
Solar/Wind Harmer
0.04
970189AG2-124 GEN
Solar/Wind Harmer
5.099
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3144356SAPONY
Solar/Wind Harmer
1.375
316315AB2-025 C
Solar/Wind Harmer
0.132
972185AH1-677 GEN
Adder
8.87
962571AG1-106 GEN
Solar/Wind Harmer
2.107
970099AG2-077 GEN
Solar/Wind Harmer
15.63
3145783HORNRTN
Solar/Wind Harmer
2.599
3145783HORNRTN
Solar/Wind Harmer
2.079
3145783HORNRTN
Solar/Wind Harmer
0.65
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
0.438
315724AD1-057 GEN
Solar/Wind Harmer
2.684
3145603CNETO
Solar/Wind Harmer
0.126
970293AG2-193 GEN
Solar/Wind Harmer
2.002
3150921YORKTN3
Adder
4.461
3144536CHRHLND
Solar/Wind Harmer
0.026
944581AF1-123 GEN
Solar/Wind Harmer
39.063
316203AE2-005 GEN
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.167
944011AF1-069 GEN
Solar/Wind Harmer
9.724
315735AD1-075 GEN1
Solar/Wind Harmer
0.445
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.154
3146263WOODLND
Solar/Wind Harmer
0.15
3145963POPLR C
Solar/Wind Harmer
0.149
316011AB1-132 GEN
Solar/Wind Harmer
2.686
961601AG1-000A GEN
Solar/Wind Harmer
9.505
3145543BTLEBRO
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.133
3146776BUCKING
Solar/Wind Harmer
0.047
316223AC1-118
Solar/Wind Harmer
0.091
970221AG2-151 GEN
Solar/Wind Harmer
6.373
971285AH1-108 GEN
Adder
1.379
315697AD1-025 GEN
Solar/Wind Harmer
0.192
971445AH1-216 GEN
Solar/Wind Harmer
12.355
3151081ELIZAR1
Adder
15.915
3151091ELIZAR2
Adder
15.638
316316AC1-027 C
Solar/Wind Harmer
0.165
957871AF2-081 GEN
Solar/Wind Harmer
8.553
971967AH1-528 GEN
Solar/Wind Harmer
25.131
315732AD1-074 GEN1
Solar/Wind Harmer
0.891
3145893MURPHYS
Solar/Wind Harmer
0.416
3145893MURPHYS
Solar/Wind Harmer
0.154
316463AE2-346 GEN
Solar/Wind Harmer
0.13
3145513AHOSKIE
Solar/Wind Harmer
0.318
3145513AHOSKIE
Solar/Wind Harmer
0.152
970085AG2-068 GEN
Solar/Wind Harmer
8.004
3141813NORNECK
Solar/Wind Harmer
0.15
315652AC1-086 GEN
Solar/Wind Harmer
16.288
316426AA2-053 GEN
Solar/Wind Harmer
0.494
3137643SOCKMAN
Solar/Wind Harmer
0.59
316327AA2-057 GEN
Solar/Wind Harmer
0.204
3144303KENBRDG
Solar/Wind Harmer
0.108
946301AF1-294 GEN
Solar/Wind Harmer
2.66
226929AD2-058 GEN
Solar/Wind Helper
0.118
316017AA1-139 ULT1
Solar/Wind Harmer
0.092
3146456SLIGO L269
Solar/Wind Harmer
0.171
971153AH1-033 GEN
Solar/Wind Harmer
1.982
3145273HOLLAND
Solar/Wind Harmer
0.124
3146376EDENTON
Solar/Wind Harmer
0.163
3146206CASHIE
Solar/Wind Harmer
0.155
3146173TUNIS
Solar/Wind Harmer
0.153
971781AH1-399 GEN
Solar/Wind Harmer
0.196
316181AB2-040 GEN
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.087
316478AD1-087 GEN
Solar/Wind Harmer
0.492
972255AH1-712 GEN
Adder
72.54
3146073TAR RVR
Solar/Wind Harmer
0.136
3146083TARBORO
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.089
959311AF2-222 GEN
Solar/Wind Harmer
12.009
3147133PAMPLIN
Solar/Wind Harmer
0.423
971623AH1-311 GEN
Solar/Wind Harmer
0.267
316222AC1-221 GEN
Solar/Wind Harmer
0.471
316283AC2-100 C
Solar/Wind Harmer
0.223
227287AC2-120 GEN
Solar/Wind Helper
0.389
972195AH1-682 GEN
50/50
3.737
972189AH1-679 GEN
50/50
3.521
315673AE1-157 GEN
Solar/Wind Harmer
13.8
3150681DARBY 2
Adder
13.511
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.69
3145506HICKORY
Solar/Wind Harmer
0.414
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.275
316388AE2-253 GEN
Solar/Wind Harmer
0.535
971531AH1-263 GEN
50/50
38.564
972213AH1-691 GEN
50/50
4.627
316159AE1-175 C
Solar/Wind Harmer
0.154
971281AH1-106 GEN
Solar/Wind Harmer
2.497
3143873LANEXA
Solar/Wind Harmer
0.105
3143316POE
Solar/Wind Harmer
0.689
970657AG2-426 GEN
Solar/Wind Harmer
1.273
3141873WAN 176
Solar/Wind Harmer
0.034
3146486SUNBURY
Solar/Wind Harmer
0.169
3146486SUNBURY
Solar/Wind Harmer
0.169
3145176PASQUOTANK
Solar/Wind Harmer
0.105
3150401LDYSMT4
50/50
28.489
3143096IRON208
Adder
0.775
3143096IRON208
Adder
0.759
3150861SPRUNCD
Adder
0.843
316458AB2-190 GEN2
Solar/Wind Harmer
0.957
961611AG1-000B GEN
Solar/Wind Harmer
4.724
3151171GRAVELC
Adder
2.468
3144873MCLAUGH
Solar/Wind Harmer
0.004
970657AG2-426 GEN
Solar/Wind Harmer
3.889
3141843SHACKLE
Adder
0.879
316246AF1-032 C
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
3.026
316321Z2-027
Solar/Wind Harmer
0.03
3146626S HERTFORD
Solar/Wind Harmer
0.166
3156081AA2-088 GEN
Solar/Wind Harmer
0
970917AG2-570 GEN
Solar/Wind Harmer
13.485
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
3145933PARMELE
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
0.682
3138133OCRAN
Solar/Wind Harmer
0.05
3130156CHOWAN
Solar/Wind Harmer
0.163
3130156CHOWAN
Solar/Wind Harmer
0.163
970533AG2-339 GEN
Solar/Wind Harmer
12.209
3130546PLYMOUTH
Solar/Wind Harmer
0.157
315733AD1-074 GEN2
Solar/Wind Harmer
0.891
970601AG2-382 GEN
Solar/Wind Harmer
5.781
970581AG2-369 GEN
Solar/Wind Harmer
6.884
3146033SCOT NK
Solar/Wind Harmer
0.582
972205AH1-687 GEN
Adder
5.352
316349AD2-085 GEN
Solar/Wind Harmer
0.114
3146456SLIGO L269
Solar/Wind Harmer
3.034
3146386ELIZ CT
Solar/Wind Harmer
0.17
315742AE1-103 GEN
Solar/Wind Harmer
2.447
3146376EDENTON
Solar/Wind Harmer
0.725
3146376EDENTON
Solar/Wind Harmer
0.725
970933AG2-581 GEN
Solar/Wind Harmer
12.367
316365GEN2_N
Solar/Wind Harmer
0.341
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316336AC2-165 C
Solar/Wind Harmer
7.636
958211AF2-115 GEN
Solar/Wind Harmer
1.618
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
3138126ROCKLANDING
Solar/Wind Harmer
0.081
961611AG1-000B GEN
Solar/Wind Harmer
9.291
3143226MDLTHAN
Solar/Wind Harmer
0.176
3151171GRAVELC
Adder
1.877
3150981CHESPKA
Adder
2.167
316381AD1-082 GEN
Solar/Wind Harmer
0.176
319010AE1-072 C
Solar/Wind Harmer
0.854
3138133OCRAN
Solar/Wind Harmer
0.1
3130156CHOWAN
Solar/Wind Harmer
0.163
315816AE2-034 GEN
Solar/Wind Harmer
0.681
971163AH1-040 GEN
Solar/Wind Harmer
12.772
315737AD1-076 GEN
Solar/Wind Harmer
2.007
316404AE1-155 C
Solar/Wind Harmer
0
970087AG2-069 GEN
Solar/Wind Harmer
12.006
957481AF2-042 GEN
Solar/Wind Harmer
39.076
315693AD1-088 GEN
Solar/Wind Harmer
6.932
3146293MARTNCO
Solar/Wind Harmer
0.133
3145493TOT1
Solar/Wind Harmer
0.605
3146233WITAKRS
Solar/Wind Harmer
0.541
315785AD2-033 C
Solar/Wind Harmer
1.093
970685AG2-442 GEN
Solar/Wind Harmer
10.073
971563AH1-280 GEN
Solar/Wind Harmer
1.438
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.533
971377AH1-170 GEN
Solar/Wind Harmer
1.275
3137176SLIGO L2192
Solar/Wind Harmer
0.682
3130086AYDLETT
Solar/Wind Harmer
0.685
3146626S HERTFORD
Solar/Wind Harmer
0.166
3146626S HERTFORD
Solar/Wind Harmer
0.166
3150341NORNECKC1
Adder
1.568
3150341NORNECKC1
Adder
1.555
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
3142666NORTHAMPTON
Solar/Wind Harmer
0.089
313506AB2-031 GEN
Solar/Wind Harmer
0.455
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.183
3145933PARMELE
Solar/Wind Harmer
0.286
3145933PARMELE
Solar/Wind Harmer
0.143
970301AG2-198 GEN
Solar/Wind Harmer
5.907
3145493TOT1
Solar/Wind Harmer
0.315
970323AG2-213 GEN
Solar/Wind Harmer
5.766
316049AB1-081 GEN
Solar/Wind Harmer
0.76
3146233WITAKRS
Solar/Wind Harmer
0.092
970257AG2-171 GEN
Solar/Wind Harmer
4.324
971775AH1-396 GEN
Solar/Wind Harmer
0.216
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.307
3141906WESTMOR
Solar/Wind Harmer
0.051
315835AF2-110_GEN
Solar/Wind Harmer
1.169
316156AD2-030 GEN
Solar/Wind Harmer
0.125
3146516WINFALL
Solar/Wind Harmer
0.167
3146516WINFALL
Solar/Wind Harmer
0.167
3146516WINFALL
Solar/Wind Harmer
0.167
315614AA2-178 GEN
Solar/Wind Harmer
0.908
972187AH1-678 GEN
Adder
4.457
316313AB2-026
Solar/Wind Harmer
0.097
316065AD1-022 GEN
Solar/Wind Harmer
7.157
3145893MURPHYS
Solar/Wind Harmer
1.031
3145893MURPHYS
Solar/Wind Harmer
0.277
316140AB2-099
Solar/Wind Harmer
0.054
972193AH1-681 GEN
Adder
3.241
316005AA1-067
Solar/Wind Harmer
0.15
3145453TOT5
Solar/Wind Harmer
0.189
961601AG1-000A GEN
Solar/Wind Harmer
2.376
3146776BUCKING
Solar/Wind Harmer
0.52
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.48
316118AC1-105 GEN
Solar/Wind Harmer
0.325
316075AC2-137 C
Solar/Wind Harmer
0.05
315778AD1-151 GEN
Solar/Wind Harmer
14.303
3144216WINCHST
Adder
0.669
3151101ELIZAR3
Adder
16.118
944601AF1-125 GEN
Solar/Wind Harmer
38.461
3143336POWHATN
Solar/Wind Harmer
2.358
3150351NORNECKC2
Adder
1.518
3145823KELFORD
Solar/Wind Harmer
0.148
3145796HORNRTN
Solar/Wind Harmer
0.584
3145796HORNRTN
Solar/Wind Harmer
0.146
316212AC1-099_GEN
Solar/Wind Harmer
0.738
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
315722AD1-056 GEN
Solar/Wind Harmer
4.811
964241AG1-285 GEN
Solar/Wind Harmer
9.026
3144293JTRSVLE
Adder
0.322
942461AE2-259 GEN
Solar/Wind Harmer
0
972003AH1-546 GEN
Solar/Wind Harmer
4.363
971683AH1-343 GEN
Solar/Wind Harmer
4.262
226910AB2-157 C
Solar/Wind Helper
0.016
3141913WHIT STONE
Solar/Wind Harmer
0.167
970673AG2-436 GEN
Solar/Wind Harmer
19.934
316258AE1-075 C
Solar/Wind Harmer
0.117
3145796HORNRTN
Solar/Wind Harmer
0.467
3145796HORNRTN
Solar/Wind Harmer
0.058
316210AC1-098 GEN
Solar/Wind Harmer
1.323
970831AG2-522 GEN
Solar/Wind Harmer
6.009
3145746EVERETS
Solar/Wind Harmer
0.558
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
957861AF2-080 GEN
Solar/Wind Harmer
5.951
3145573BETHELC
Solar/Wind Harmer
0.136
3145573BETHELC
Solar/Wind Harmer
0.136
970683AG2-441 GEN
Solar/Wind Harmer
8.135
970681AG2-440 GEN
Solar/Wind Harmer
5.399
3143336POWHATN
Solar/Wind Harmer
2.775
971547AH1-271 GEN
Solar/Wind Harmer
3.304
960081AF2-299 GEN
Solar/Wind Harmer
1.44
3150351NORNECKC2
Adder
1.493
3145823KELFORD
Solar/Wind Harmer
0.148
3145783HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.482
3145796HORNRTN
Solar/Wind Harmer
0.146
972277AH1-723 GEN
Adder
84.53
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.523
971065AG2-659 GEN
Solar/Wind Harmer
5.948
316034AC1-036 C
Solar/Wind Harmer
0.009
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.254
970401AG2-262 GEN
Solar/Wind Harmer
0.758
3147623JAMES R
Solar/Wind Harmer
0.277
3144293JTRSVLE
Adder
0.322
316263AC1-034 GEN
Solar/Wind Harmer
5.077
962561AG1-105 GEN
Solar/Wind Harmer
6.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.841
LGEELTFEXP_LGEE->PJM
CLTF
1.602
MECLTFEXP_MEC->PJM
CLTF
4.136
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.651
NYPJM->LTFIMP_NY
CLTF
2.859
TVALTFEXP_TVA->PJM
CLTF
3.819
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.159
CPLELTFEXP_CPLE->PJM
CLTF
8.867
SIGELTFEXP_SIGE->PJM
CLTF
0.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.334
WECLTFEXP_WEC->PJM
CLTF
0.813
LAGNLTFEXP_LAGN->PJM
CLTF
7.542

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.91 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4645.47
MW Contribution:
39.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3142366NRTHEST
50/50
0.663
3150691DARBY 3
Adder
13.729
3150701DARBY 4
Adder
13.697
315976AC1-164 GENA
Solar/Wind Harmer
4.783
316169AC1-164_GENC
Solar/Wind Harmer
4.132
3142946ENON
Solar/Wind Harmer
-0.002
3150381LDYSMT2
50/50
27.099
3151201GRAVEL4
Adder
13.054
3151221GRAVEL6
Adder
13.039
3151211GRAVEL5
Adder
12.889
3142433PROV 92
Adder
0.347
3142433PROV 92
Adder
0.347
316311AC2-079 GEN
Solar/Wind Harmer
9.899
316059AD1-063 C
Solar/Wind Harmer
0.44
313526AB2-022
Solar/Wind Harmer
0.523
3146396TANGLEW
Solar/Wind Harmer
0.356
315814AE2-033 C
Solar/Wind Harmer
17.496
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.44
961941AG1-037 GEN
Solar/Wind Harmer
0.131
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146043SEABORD
Solar/Wind Harmer
-0.017
316486AD2-202 GEN
Solar/Wind Harmer
0.414
316274AC1-208 GEN
Solar/Wind Harmer
1.756
961791AG1-021 GEN
Solar/Wind Harmer
1.947
972197AH1-683 GEN
50/50
4.408
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.022
315975AC1-164 GENB
Solar/Wind Harmer
0.141
3142433PROV 92
Solar/Wind Harmer
-0.08
3142433PROV 92
Adder
0.347
3142433PROV 92
Adder
0.347
3145336SMITFLD
Solar/Wind Harmer
-0.08
316375AC2-012 GEN
Solar/Wind Harmer
6.866
3146456SLIGO L269
Solar/Wind Harmer
-0.02
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.277
3145663CRESWEL
Solar/Wind Harmer
-0.051
3146206CASHIE
Solar/Wind Harmer
-0.018
316023GEN1_S
Solar/Wind Harmer
1.186
3146173TUNIS
Solar/Wind Harmer
-0.017
958261AF2-120 GEN
Solar/Wind Harmer
6.788
3156021HOLLOMANSOL
Solar/Wind Harmer
2.352
3145683EARLEYS
Solar/Wind Harmer
-0.017
3147043LAWRENC
Adder
1.348
970937AG2-583 GEN
Solar/Wind Harmer
11.413
316192AB2-158 GEN
Solar/Wind Harmer
1.874
3146083TARBORO
Solar/Wind Harmer
-0.016
3150391LDYSMT3
50/50
28.174
316312AB1-027
Solar/Wind Harmer
0.733
944641AF1-129 GEN
Adder
87.536
3143526WINTERP
Solar/Wind Harmer
-0.107
316185AD1-033 GEN
Solar/Wind Harmer
2.082
316441AF1-014 GEN
Solar/Wind Harmer
1.315
3144356SAPONY
Solar/Wind Harmer
0.657
316315AB2-025 C
Solar/Wind Harmer
0.507
3150411LDYSMT5
50/50
28.315
972215AH1-692 GEN
50/50
4.584
316233AE1-074 FULL
Solar/Wind Harmer
0.555
971283AH1-107 GEN
Solar/Wind Harmer
3.352
3151191GRAVEL3
Adder
12.889
3138283WHITEMARSH
Solar/Wind Harmer
0.031
316018AA1-139 ULT2
Solar/Wind Harmer
1.68
315833AF1-017_GEN
Solar/Wind Harmer
3.727
3146406KITTY HAWK
Solar/Wind Harmer
0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.577
315800Z1-036_GEN1
Solar/Wind Harmer
4.638
971967AH1-528 GEN
Solar/Wind Harmer
33.968
315732AD1-074 GEN1
Solar/Wind Harmer
3.62
3145893MURPHYS
Solar/Wind Harmer
-0.047
3145893MURPHYS
Solar/Wind Harmer
-0.018
316463AE2-346 GEN
Solar/Wind Harmer
0.281
3145513AHOSKIE
Solar/Wind Harmer
0.152
3145513AHOSKIE
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.794
315652AC1-086 GEN
Solar/Wind Harmer
19.138
316174AB2-169 GEN
Solar/Wind Harmer
2.617
316426AA2-053 GEN
Solar/Wind Harmer
1.71
3137643SOCKMAN
Solar/Wind Harmer
-0.067
3141813NORNECK
Solar/Wind Harmer
-0.017
316327AA2-057 GEN
Solar/Wind Harmer
1.601
3144303KENBRDG
Solar/Wind Harmer
-0.012
946301AF1-294 GEN
Solar/Wind Harmer
3.992
226929AD2-058 GEN
Solar/Wind Helper
0.128
316319Z2-044 C
Solar/Wind Harmer
0.864
316131AB2-060 GEN
Solar/Wind Harmer
1.681
316359AB2-059 GEN
Solar/Wind Harmer
2.067
315051AA1-145 CT1
50/50
1.577
3150371LDYSMT1
50/50
27.275
966881AG1-559 GEN
Solar/Wind Harmer
0.671
3142416OLDCHRC
Solar/Wind Harmer
2.198
3142946ENON
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
2.251
970133AG2-095 GEN
Solar/Wind Harmer
2.318
3142433PROV 92
Adder
0.347
3142433PROV 92
Adder
0.347
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.492
316017AA1-139 ULT1
Solar/Wind Harmer
1.586
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.271
3141766HARMONY
Solar/Wind Harmer
1.739
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.019
961951AG1-038 GEN
Solar/Wind Harmer
2.361
3146206CASHIE
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.017
316181AB2-040 GEN
Solar/Wind Harmer
2.376
3147043LAWRENC
Solar/Wind Harmer
-0.01
971781AH1-399 GEN
Solar/Wind Harmer
1.024
316478AD1-087 GEN
Solar/Wind Harmer
1.413
972255AH1-712 GEN
Adder
74.11
316420AA1-050 GEN
Solar/Wind Harmer
1.794
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
16.28
3147133PAMPLIN
Solar/Wind Harmer
-0.049
227287AC2-120 GEN
Solar/Wind Helper
0.42
971531AH1-263 GEN
50/50
39.671
972213AH1-691 GEN
50/50
4.584
971281AH1-106 GEN
Solar/Wind Harmer
3.352
316382AG1-145 C
Solar/Wind Harmer
0.618
316159AE1-175 C
Solar/Wind Harmer
0.55
316236AE1-162_GEN
Solar/Wind Harmer
0.603
3143316POE
Solar/Wind Harmer
-0.078
970657AG2-426 GEN
Solar/Wind Harmer
1.25
3143873LANEXA
Solar/Wind Harmer
-0.012
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
3141873WAN 176
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
970533AG2-339 GEN
Solar/Wind Harmer
12.493
316405AF2-144 C
Solar/Wind Harmer
0.46
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315733AD1-074 GEN2
Solar/Wind Harmer
3.62
970601AG2-382 GEN
Solar/Wind Harmer
7.769
970581AG2-369 GEN
Solar/Wind Harmer
9.283
946281AF1-292 GEN
Solar/Wind Harmer
0.386
3146033SCOT NK
Solar/Wind Harmer
-0.066
972205AH1-687 GEN
Adder
5.545
316294AC1-161 GEN
Solar/Wind Harmer
6.49
316083AB2-161 GEN
Solar/Wind Harmer
3.219
316349AD2-085 GEN
Solar/Wind Harmer
1.742
3146456SLIGO L269
Solar/Wind Harmer
2.317
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.483
316433W1029_GEN2
Solar/Wind Harmer
3.483
315742AE1-103 GEN
Solar/Wind Harmer
4.455
3146376EDENTON
Solar/Wind Harmer
0.554
3146376EDENTON
Solar/Wind Harmer
0.554
970933AG2-581 GEN
Solar/Wind Harmer
16.676
316365GEN2_N
Solar/Wind Harmer
1.186
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
10.869
958211AF2-115 GEN
Solar/Wind Harmer
2.434
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3147133PAMPLIN
Solar/Wind Harmer
-0.012
3143096IRON208
Adder
0.786
3142543TWELFTH
Solar/Wind Harmer
-0.002
971069AG2-661 GEN
Solar/Wind Harmer
3.228
316369SG1_INVT
Solar/Wind Harmer
3.63
3143226MDLTHAN
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.062
961611AG1-000B GEN
Solar/Wind Harmer
9.983
3151171GRAVELC
Adder
1.908
3150981CHESPKA
Adder
2.206
316381AD1-082 GEN
Solar/Wind Harmer
1.815
319010AE1-072 C
Solar/Wind Harmer
3.957
315662AE1-191 GEN
Solar/Wind Harmer
2.335
316280AD1-041 GEN
Solar/Wind Harmer
1.459
3138133OCRAN
Solar/Wind Harmer
-0.011
315611Z1-036_GEN2
Solar/Wind Harmer
4.638
3130156CHOWAN
Solar/Wind Harmer
-0.019
315816AE2-034 GEN
Solar/Wind Harmer
1.476
971163AH1-040 GEN
Solar/Wind Harmer
17.152
315737AD1-076 GEN
Solar/Wind Harmer
3.403
316404AE1-155 C
Solar/Wind Harmer
3.344
970087AG2-069 GEN
Solar/Wind Harmer
16.191
316087AB2-174 GEN
Solar/Wind Harmer
2.437
957481AF2-042 GEN
Solar/Wind Harmer
52.746
315693AD1-088 GEN
Solar/Wind Harmer
8.323
3146293MARTNCO
Solar/Wind Harmer
0.102
3147666LOUISA
Solar/Wind Harmer
-0.064
3145493TOT1
Solar/Wind Harmer
0.464
3146233WITAKRS
Solar/Wind Harmer
-0.062
315785AD2-033 C
Solar/Wind Harmer
3.531
970685AG2-442 GEN
Solar/Wind Harmer
13.636
971563AH1-280 GEN
Solar/Wind Harmer
1.947
3146926FARMVIL
Solar/Wind Harmer
-0.009
972189AH1-679 GEN
50/50
3.54
972195AH1-682 GEN
50/50
3.702
315673AE1-157 GEN
Solar/Wind Harmer
16.734
3150681DARBY 2
Adder
13.681
316033AB2-134 GEN
Solar/Wind Harmer
6.554
3145506HICKORY
Solar/Wind Harmer
-0.079
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.012
316339AD2-160 GEN
Solar/Wind Harmer
1.323
316388AE2-253 GEN
Solar/Wind Harmer
1.323
3137176SLIGO L2192
Solar/Wind Harmer
-0.078
3130086AYDLETT
Solar/Wind Harmer
-0.078
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
316487AF1-042 GEN
Solar/Wind Harmer
2.361
313506AB2-031 GEN
Solar/Wind Harmer
1.368
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
0.14
3150341NORNECKC1
Adder
1.565
3150341NORNECKC1
Adder
1.552
3145933PARMELE
Solar/Wind Harmer
-0.033
3145933PARMELE
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
7.999
3145493TOT1
Solar/Wind Harmer
0.242
313527AB2-043 GEN
Solar/Wind Harmer
2.537
3150401LDYSMT4
50/50
28.227
3152261N ANNA2
50/50
8.945
3143096IRON208
Adder
0.786
3143096IRON208
Adder
0.77
3150861SPRUNCD
Adder
0.856
316458AB2-190 GEN2
Solar/Wind Harmer
2.065
961611AG1-000B GEN
Solar/Wind Harmer
4.26
3151171GRAVELC
Adder
2.509
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
4.004
316246AF1-032 C
Solar/Wind Harmer
0.395
3141843SHACKLE
Adder
0.887
316321Z2-027
Solar/Wind Harmer
0.52
3141873WAN 176
Solar/Wind Harmer
2.289
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3156081AA2-088 GEN
Solar/Wind Harmer
5.807
970917AG2-570 GEN
Solar/Wind Harmer
43.64
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316190AA2-174 GEN
Solar/Wind Harmer
0.208
3145933PARMELE
Solar/Wind Harmer
-0.016
3147666LOUISA
Solar/Wind Harmer
-0.037
3146233WITAKRS
Solar/Wind Harmer
0.327
3146233WITAKRS
Solar/Wind Harmer
-0.011
970257AG2-171 GEN
Solar/Wind Harmer
5.85
971775AH1-396 GEN
Solar/Wind Harmer
1.101
3146926FARMVIL
Solar/Wind Harmer
-0.009
970323AG2-213 GEN
Solar/Wind Harmer
7.8
316049AB1-081 GEN
Solar/Wind Harmer
1.654
970293AG2-193 GEN
Solar/Wind Harmer
2.669
3150921YORKTN3
Adder
4.527
3144536CHRHLND
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
90.294
3142956BIRDNECK
Solar/Wind Harmer
1.063
316305AF2-043 C
Solar/Wind Harmer
0.589
316203AE2-005 GEN
Solar/Wind Harmer
8.225
316320Y1-086
Solar/Wind Harmer
1.137
3146516WINFALL
Solar/Wind Harmer
-0.019
944011AF1-069 GEN
Solar/Wind Harmer
10.915
315735AD1-075 GEN1
Solar/Wind Harmer
1.809
3145893MURPHYS
Solar/Wind Harmer
0.123
3145893MURPHYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.553
961601AG1-000A GEN
Solar/Wind Harmer
6.122
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3142296MT RD221
50/50
0.666
3150671DARBY 1
Adder
13.665
966871AG1-558 GEN
Solar/Wind Harmer
0.629
966871AG1-558 GEN
Solar/Wind Harmer
0.215
316240AF1-291 C
Solar/Wind Harmer
0.618
971223AH1-071 GEN
Solar/Wind Harmer
2.535
3150991CHESPKB
Adder
1.851
3150991CHESPKB
Adder
1.807
315835AF2-110_GEN
Solar/Wind Harmer
2.436
315666AE1-190 GEN
Solar/Wind Harmer
0.584
316156AD2-030 GEN
Solar/Wind Harmer
0.514
316435W1029_GEN3
Solar/Wind Harmer
3.483
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
315614AA2-178 GEN
Solar/Wind Harmer
1.968
316313AB2-026
Solar/Wind Harmer
0.484
972187AH1-678 GEN
Adder
4.563
316065AD1-022 GEN
Solar/Wind Harmer
8.911
3145893MURPHYS
Solar/Wind Harmer
0.493
3145893MURPHYS
Solar/Wind Harmer
-0.032
316140AB2-099
Solar/Wind Harmer
0.117
972193AH1-681 GEN
Adder
3.311
316005AA1-067
Solar/Wind Harmer
0.325
3145453TOT5
Solar/Wind Harmer
0.145
961601AG1-000A GEN
Solar/Wind Harmer
6.045
315052AA1-145 CT2
50/50
1.586
3152251N ANNA1
50/50
8.941
3150851SPRUNCC
Adder
0.856
316132AB2-190 GEN1
Solar/Wind Harmer
2.065
315773AC2-141 GEN
Solar/Wind Harmer
8.398
316036AC1-147 C
Solar/Wind Harmer
0.534
316093AE2-104_GEN
Solar/Wind Harmer
5.667
3146516WINFALL
Solar/Wind Harmer
-0.062
3146516WINFALL
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.07
3145893MURPHYS
Solar/Wind Harmer
0.524
962861AG1-135 GEN
Solar/Wind Harmer
6.609
970919AG2-571 GEN
Solar/Wind Harmer
5.524
315607AA1-063A GEN
Solar/Wind Harmer
1.738
3146263WOODLND
Solar/Wind Harmer
-0.017
3141726DUNNSVL
Solar/Wind Harmer
-0.068
3145963POPLR C
Solar/Wind Harmer
-0.017
316494AC1-189 GEN
Solar/Wind Harmer
1.707
961671AG1-007 GEN
Solar/Wind Harmer
0.198
316337AD2-073 GEN
Solar/Wind Harmer
0.417
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.012
971285AH1-108 GEN
Adder
1.402
315697AD1-025 GEN
Solar/Wind Harmer
4.108
315839AE2-212 C
Solar/Wind Harmer
0.61
971445AH1-216 GEN
Solar/Wind Harmer
12.408
3151081ELIZAR1
Adder
16.203
3151091ELIZAR2
Adder
15.921
316316AC1-027 C
Solar/Wind Harmer
0.607
957831AF2-077 GEN
Solar/Wind Harmer
0.595
957871AF2-081 GEN
Solar/Wind Harmer
9.83
3141913WHIT STONE
Solar/Wind Harmer
-0.019
970673AG2-436 GEN
Solar/Wind Harmer
40.293
316258AE1-075 C
Solar/Wind Harmer
0.436
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.007
316468AD1-105 GEN
Solar/Wind Harmer
1.898
316210AC1-098 GEN
Solar/Wind Harmer
2.576
970831AG2-522 GEN
Solar/Wind Harmer
8.103
3145746EVERETS
Solar/Wind Harmer
-0.064
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
957861AF2-080 GEN
Solar/Wind Harmer
6.942
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.469
316239AB2-077_GEN
Solar/Wind Harmer
0.469
970683AG2-441 GEN
Solar/Wind Harmer
11.01
970681AG2-440 GEN
Solar/Wind Harmer
7.307
972219AH1-694 GEN
50/50
3.174
944631AF1-128 GEN
Adder
88.715
3143526WINTERP
Solar/Wind Harmer
-0.107
315671AE2-027_GEN
Solar/Wind Harmer
3.679
971317AH1-138 GEN
Solar/Wind Harmer
2.528
944591AF1-124 GEN
Solar/Wind Harmer
90.619
316072AD1-144
Solar/Wind Harmer
0.398
316314AB2-024 C
Solar/Wind Harmer
1.682
939411AE1-173 GEN
Solar/Wind Harmer
97.087
940641AE2-051 GEN
Solar/Wind Harmer
18.091
941031AE2-094 GEN
Solar/Wind Harmer
34.835
3143336POWHATN
Solar/Wind Harmer
2.137
971547AH1-271 GEN
Solar/Wind Harmer
4.439
960081AF2-299 GEN
Solar/Wind Harmer
1.938
964211AG1-282 GEN
Solar/Wind Harmer
0.516
3145823KELFORD
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.017
3150351NORNECKC2
Adder
1.49
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.017
972277AH1-723 GEN
Adder
86.36
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.409
971065AG2-659 GEN
Solar/Wind Harmer
8.024
316034AC1-036 C
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.331
3144293JTRSVLE
Adder
0.261
316075AC2-137 C
Solar/Wind Harmer
0.572
315778AD1-151 GEN
Solar/Wind Harmer
18.159
3144216WINCHST
Adder
0.679
3151101ELIZAR3
Adder
16.41
944601AF1-125 GEN
Solar/Wind Harmer
88.885
3143336POWHATN
Solar/Wind Harmer
1.816
316484AD2-074 GEN
Solar/Wind Harmer
4.512
966621AG1-532 GEN
Solar/Wind Harmer
0.35
316317KELFORD C
Solar/Wind Harmer
0.788
3145823KELFORD
Solar/Wind Harmer
-0.017
316077AC2-138 C
Solar/Wind Harmer
0.353
3150351NORNECKC2
Adder
1.515
3145796HORNRTN
Solar/Wind Harmer
-0.067
3145796HORNRTN
Solar/Wind Harmer
-0.017
316212AC1-099_GEN
Solar/Wind Harmer
1.431
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
315722AD1-056 GEN
Solar/Wind Harmer
5.695
964241AG1-285 GEN
Solar/Wind Harmer
12.203
3144293JTRSVLE
Adder
0.331
942461AE2-259 GEN
Solar/Wind Harmer
2.337
226910AB2-157 C
Solar/Wind Helper
0.017
972185AH1-677 GEN
Adder
9.079
962571AG1-106 GEN
Solar/Wind Harmer
2.445
970099AG2-077 GEN
Solar/Wind Harmer
21.098
3145783HORNRTN
Solar/Wind Harmer
1.993
3145783HORNRTN
Solar/Wind Harmer
1.595
3145783HORNRTN
Solar/Wind Harmer
0.498
3145783HORNRTN
Solar/Wind Harmer
0.199
3145796HORNRTN
Solar/Wind Harmer
-0.05
315724AD1-057 GEN
Solar/Wind Harmer
3.132
3145603CNETO
Solar/Wind Harmer
0.097
316237AB2-079_GEN
Solar/Wind Harmer
0.469
315687AD1-152 GEN
Solar/Wind Harmer
1.873
3144293JTRSVLE
Adder
0.331
316263AC1-034 GEN
Solar/Wind Harmer
6.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.073
LGEELTFEXP_LGEE->PJM
CLTF
1.708
MECLTFEXP_MEC->PJM
CLTF
4.396
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.76
NYPJM->LTFIMP_NY
CLTF
2.998
TVALTFEXP_TVA->PJM
CLTF
3.998
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.817
CPLELTFEXP_CPLE->PJM
CLTF
9.123
SIGELTFEXP_SIGE->PJM
CLTF
0.136
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.992
WECLTFEXP_WEC->PJM
CLTF
0.87
LAGNLTFEXP_LAGN->PJM
CLTF
7.898

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: H3T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.65 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4359.44
MW Contribution:
38.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150381LDYSMT2
50/50
27.357
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151201GRAVEL4
Adder
12.847
3151221GRAVEL6
Adder
12.832
3151211GRAVEL5
Adder
12.684
316059AD1-063 C
Solar/Wind Harmer
0.437
316311AC2-079 GEN
Solar/Wind Harmer
9.725
313526AB2-022
Solar/Wind Harmer
0.513
3146396TANGLEW
Solar/Wind Harmer
0.349
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
315814AE2-033 C
Solar/Wind Harmer
17.146
3146206CASHIE
Solar/Wind Harmer
-0.017
316318V4-068
Solar/Wind Harmer
0.432
961941AG1-037 GEN
Solar/Wind Harmer
0.128
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146043SEABORD
Solar/Wind Harmer
-0.017
316274AC1-208 GEN
Solar/Wind Harmer
1.718
316486AD2-202 GEN
Solar/Wind Harmer
0.404
961791AG1-021 GEN
Solar/Wind Harmer
1.894
3150411LDYSMT5
50/50
28.586
972215AH1-692 GEN
50/50
4.628
316233AE1-074 FULL
Solar/Wind Harmer
0.544
971283AH1-107 GEN
Solar/Wind Harmer
3.289
3151191GRAVEL3
Adder
12.684
3138283WHITEMARSH
Solar/Wind Harmer
0.03
316018AA1-139 ULT2
Solar/Wind Harmer
1.65
315833AF1-017_GEN
Solar/Wind Harmer
3.662
3146406KITTY HAWK
Solar/Wind Harmer
0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.572
315800Z1-036_GEN1
Solar/Wind Harmer
4.552
971967AH1-528 GEN
Solar/Wind Harmer
33.189
315732AD1-074 GEN1
Solar/Wind Harmer
3.549
3145893MURPHYS
Solar/Wind Harmer
-0.046
3145893MURPHYS
Solar/Wind Harmer
-0.017
316463AE2-346 GEN
Solar/Wind Harmer
0.276
3145513AHOSKIE
Solar/Wind Harmer
0.149
3145513AHOSKIE
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.543
3141813NORNECK
Solar/Wind Harmer
-0.017
315652AC1-086 GEN
Solar/Wind Harmer
18.73
316174AB2-169 GEN
Solar/Wind Harmer
2.563
316426AA2-053 GEN
Solar/Wind Harmer
1.673
3137643SOCKMAN
Solar/Wind Harmer
-0.066
972197AH1-683 GEN
50/50
4.45
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.021
315975AC1-164 GENB
Solar/Wind Harmer
0.14
3142433PROV 92
Solar/Wind Harmer
-0.079
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3145336SMITFLD
Solar/Wind Harmer
-0.078
316375AC2-012 GEN
Solar/Wind Harmer
6.747
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.257
3146456SLIGO L269
Solar/Wind Harmer
-0.019
3145663CRESWEL
Solar/Wind Harmer
-0.05
958261AF2-120 GEN
Solar/Wind Harmer
6.781
3146206CASHIE
Solar/Wind Harmer
-0.017
316023GEN1_S
Solar/Wind Harmer
1.161
3150371LDYSMT1
50/50
27.535
315051AA1-145 CT1
50/50
1.568
966881AG1-559 GEN
Solar/Wind Harmer
0.673
3142416OLDCHRC
Solar/Wind Harmer
2.175
316473AC1-191 GEN
Solar/Wind Harmer
2.234
3142946ENON
Solar/Wind Harmer
-0.007
970133AG2-095 GEN
Solar/Wind Harmer
2.284
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.28
3141766HARMONY
Solar/Wind Harmer
1.724
316017AA1-139 ULT1
Solar/Wind Harmer
1.558
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.23
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.018
961951AG1-038 GEN
Solar/Wind Harmer
2.354
3146206CASHIE
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
971781AH1-399 GEN
Solar/Wind Harmer
1.032
316181AB2-040 GEN
Solar/Wind Harmer
2.325
3147043LAWRENC
Solar/Wind Harmer
-0.01
316478AD1-087 GEN
Solar/Wind Harmer
1.378
972255AH1-712 GEN
Adder
72.561
316420AA1-050 GEN
Solar/Wind Harmer
1.753
3146073TAR RVR
Solar/Wind Harmer
-0.015
3146083TARBORO
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
15.849
3147133PAMPLIN
Solar/Wind Harmer
-0.047
227287AC2-120 GEN
Solar/Wind Helper
0.389
316327AA2-057 GEN
Solar/Wind Harmer
1.565
3144303KENBRDG
Solar/Wind Harmer
-0.012
946301AF1-294 GEN
Solar/Wind Harmer
3.883
226929AD2-058 GEN
Solar/Wind Helper
0.118
971531AH1-263 GEN
50/50
38.578
972213AH1-691 GEN
50/50
4.628
316382AG1-145 C
Solar/Wind Harmer
0.609
316159AE1-175 C
Solar/Wind Harmer
0.543
971281AH1-106 GEN
Solar/Wind Harmer
3.289
316236AE1-162_GEN
Solar/Wind Harmer
0.593
3143873LANEXA
Solar/Wind Harmer
-0.012
3143316POE
Solar/Wind Harmer
-0.077
970657AG2-426 GEN
Solar/Wind Harmer
1.228
3141873WAN 176
Solar/Wind Harmer
-0.004
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
3138133OCRAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.018
3130156CHOWAN
Solar/Wind Harmer
-0.018
970533AG2-339 GEN
Solar/Wind Harmer
12.213
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315733AD1-074 GEN2
Solar/Wind Harmer
3.549
316405AF2-144 C
Solar/Wind Harmer
0.448
970601AG2-382 GEN
Solar/Wind Harmer
7.614
970581AG2-369 GEN
Solar/Wind Harmer
9.067
946281AF1-292 GEN
Solar/Wind Harmer
0.377
3146033SCOT NK
Solar/Wind Harmer
-0.065
3142366NRTHEST
50/50
0.655
3150691DARBY 3
Adder
13.563
3150701DARBY 4
Adder
13.531
315976AC1-164 GENA
Solar/Wind Harmer
4.729
316169AC1-164_GENC
Solar/Wind Harmer
4.086
3142946ENON
Solar/Wind Harmer
-0.002
316294AC1-161 GEN
Solar/Wind Harmer
6.377
316083AB2-161 GEN
Solar/Wind Harmer
3.164
316349AD2-085 GEN
Solar/Wind Harmer
1.712
3146456SLIGO L269
Solar/Wind Harmer
2.276
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.42
316433W1029_GEN2
Solar/Wind Harmer
3.42
315742AE1-103 GEN
Solar/Wind Harmer
4.372
3146376EDENTON
Solar/Wind Harmer
0.544
972205AH1-687 GEN
Adder
5.354
3143096IRON208
Adder
0.775
3142543TWELFTH
Solar/Wind Harmer
-0.002
971069AG2-661 GEN
Solar/Wind Harmer
3.179
316369SG1_INVT
Solar/Wind Harmer
3.574
3138126ROCKLANDING
Solar/Wind Harmer
0.061
961611AG1-000B GEN
Solar/Wind Harmer
9.827
3143226MDLTHAN
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
1.877
3150981CHESPKA
Adder
2.168
316381AD1-082 GEN
Solar/Wind Harmer
1.784
319010AE1-072 C
Solar/Wind Harmer
3.887
315662AE1-191 GEN
Solar/Wind Harmer
2.315
316280AD1-041 GEN
Solar/Wind Harmer
1.447
3138133OCRAN
Solar/Wind Harmer
-0.011
315611Z1-036_GEN2
Solar/Wind Harmer
4.552
3130156CHOWAN
Solar/Wind Harmer
-0.018
315816AE2-034 GEN
Solar/Wind Harmer
1.448
971163AH1-040 GEN
Solar/Wind Harmer
16.823
315737AD1-076 GEN
Solar/Wind Harmer
3.336
316404AE1-155 C
Solar/Wind Harmer
3.34
970087AG2-069 GEN
Solar/Wind Harmer
15.814
316087AB2-174 GEN
Solar/Wind Harmer
2.385
957481AF2-042 GEN
Solar/Wind Harmer
51.468
315693AD1-088 GEN
Solar/Wind Harmer
8.116
3146293MARTNCO
Solar/Wind Harmer
0.1
3145493TOT1
Solar/Wind Harmer
0.454
3146233WITAKRS
Solar/Wind Harmer
-0.06
315785AD2-033 C
Solar/Wind Harmer
3.438
970685AG2-442 GEN
Solar/Wind Harmer
13.267
971563AH1-280 GEN
Solar/Wind Harmer
1.894
3146926FARMVIL
Solar/Wind Harmer
-0.009
3147666LOUISA
Solar/Wind Harmer
-0.06
3150401LDYSMT4
50/50
28.497
3143096IRON208
Adder
0.775
3143096IRON208
Adder
0.76
3150861SPRUNCD
Adder
0.843
316458AB2-190 GEN2
Solar/Wind Harmer
2.034
961611AG1-000B GEN
Solar/Wind Harmer
4.193
3151171GRAVELC
Adder
2.469
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
3.935
3141843SHACKLE
Adder
0.88
316246AF1-032 C
Solar/Wind Harmer
0.388
3141873WAN 176
Solar/Wind Harmer
2.27
316321Z2-027
Solar/Wind Harmer
0.511
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3156081AA2-088 GEN
Solar/Wind Harmer
5.691
970917AG2-570 GEN
Solar/Wind Harmer
42.629
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316190AA2-174 GEN
Solar/Wind Harmer
0.204
3145933PARMELE
Solar/Wind Harmer
-0.016
3146233WITAKRS
Solar/Wind Harmer
0.32
3146233WITAKRS
Solar/Wind Harmer
-0.01
970257AG2-171 GEN
Solar/Wind Harmer
5.696
971775AH1-396 GEN
Solar/Wind Harmer
1.072
3146926FARMVIL
Solar/Wind Harmer
-0.009
3147666LOUISA
Solar/Wind Harmer
-0.034
972195AH1-682 GEN
50/50
3.738
972189AH1-679 GEN
50/50
3.522
315673AE1-157 GEN
Solar/Wind Harmer
16.82
3150681DARBY 2
Adder
13.515
316033AB2-134 GEN
Solar/Wind Harmer
6.454
3145506HICKORY
Solar/Wind Harmer
-0.077
3145506HICKORY
Solar/Wind Harmer
-0.046
3145506HICKORY
Solar/Wind Harmer
-0.012
316339AD2-160 GEN
Solar/Wind Harmer
1.3
316388AE2-253 GEN
Solar/Wind Harmer
1.3
3137176SLIGO L2192
Solar/Wind Harmer
-0.076
3130086AYDLETT
Solar/Wind Harmer
-0.077
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
316487AF1-042 GEN
Solar/Wind Harmer
2.354
3150341NORNECKC1
Adder
1.568
3150341NORNECKC1
Adder
1.556
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
1.338
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
0.137
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
7.78
3145493TOT1
Solar/Wind Harmer
0.237
313527AB2-043 GEN
Solar/Wind Harmer
2.473
970323AG2-213 GEN
Solar/Wind Harmer
7.595
316049AB1-081 GEN
Solar/Wind Harmer
1.616
3146376EDENTON
Solar/Wind Harmer
0.544
970933AG2-581 GEN
Solar/Wind Harmer
16.289
316365GEN2_N
Solar/Wind Harmer
1.161
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
10.577
958211AF2-115 GEN
Solar/Wind Harmer
2.368
3147133PAMPLIN
Solar/Wind Harmer
-0.015
3147133PAMPLIN
Solar/Wind Harmer
-0.012
3146173TUNIS
Solar/Wind Harmer
-0.017
3156021HOLLOMANSOL
Solar/Wind Harmer
2.304
3145683EARLEYS
Solar/Wind Harmer
-0.017
3147043LAWRENC
Adder
1.317
970937AG2-583 GEN
Solar/Wind Harmer
11.063
3146083TARBORO
Solar/Wind Harmer
-0.015
316319Z2-044 C
Solar/Wind Harmer
0.844
316131AB2-060 GEN
Solar/Wind Harmer
1.639
316359AB2-059 GEN
Solar/Wind Harmer
2.019
3142053HEARTS
Solar/Wind Harmer
0.177
316192AB2-158 GEN
Solar/Wind Harmer
0.906
970293AG2-193 GEN
Solar/Wind Harmer
2.637
3150921YORKTN3
Adder
4.463
3144536CHRHLND
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
88.703
3142956BIRDNECK
Solar/Wind Harmer
1.044
316203AE2-005 GEN
Solar/Wind Harmer
8.154
316305AF2-043 C
Solar/Wind Harmer
0.579
316320Y1-086
Solar/Wind Harmer
1.117
3146516WINFALL
Solar/Wind Harmer
-0.019
944011AF1-069 GEN
Solar/Wind Harmer
10.67
315735AD1-075 GEN1
Solar/Wind Harmer
1.774
3145893MURPHYS
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.477
961601AG1-000A GEN
Solar/Wind Harmer
5.98
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3142296MT RD221
50/50
0.659
3150671DARBY 1
Adder
13.499
966871AG1-558 GEN
Solar/Wind Harmer
0.624
966871AG1-558 GEN
Solar/Wind Harmer
0.214
316240AF1-291 C
Solar/Wind Harmer
0.608
971223AH1-071 GEN
Solar/Wind Harmer
2.48
3150991CHESPKB
Adder
1.819
3150991CHESPKB
Adder
1.775
315666AE1-190 GEN
Solar/Wind Harmer
0.579
315835AF2-110_GEN
Solar/Wind Harmer
2.393
316156AD2-030 GEN
Solar/Wind Harmer
0.509
316435W1029_GEN3
Solar/Wind Harmer
3.42
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
315614AA2-178 GEN
Solar/Wind Harmer
1.931
972187AH1-678 GEN
Adder
4.458
316313AB2-026
Solar/Wind Harmer
0.472
316065AD1-022 GEN
Solar/Wind Harmer
8.735
3145893MURPHYS
Solar/Wind Harmer
0.483
3145893MURPHYS
Solar/Wind Harmer
-0.031
316140AB2-099
Solar/Wind Harmer
0.115
315052AA1-145 CT2
50/50
1.578
3150851SPRUNCC
Adder
0.843
316132AB2-190 GEN1
Solar/Wind Harmer
2.034
315773AC2-141 GEN
Solar/Wind Harmer
8.252
316036AC1-147 C
Solar/Wind Harmer
0.525
316093AE2-104_GEN
Solar/Wind Harmer
5.566
3146516WINFALL
Solar/Wind Harmer
-0.061
3146516WINFALL
Solar/Wind Harmer
-0.019
962861AG1-135 GEN
Solar/Wind Harmer
6.599
3145893MURPHYS
Solar/Wind Harmer
-0.069
971285AH1-108 GEN
Adder
1.38
315697AD1-025 GEN
Solar/Wind Harmer
4.045
315839AE2-212 C
Solar/Wind Harmer
0.6
971445AH1-216 GEN
Solar/Wind Harmer
12.204
957831AF2-077 GEN
Solar/Wind Harmer
0.588
3151081ELIZAR1
Adder
15.92
3151091ELIZAR2
Adder
15.643
316316AC1-027 C
Solar/Wind Harmer
0.597
957871AF2-081 GEN
Solar/Wind Harmer
9.656
3141913WHIT STONE
Solar/Wind Harmer
-0.019
970673AG2-436 GEN
Solar/Wind Harmer
39.384
316258AE1-075 C
Solar/Wind Harmer
0.425
316468AD1-105 GEN
Solar/Wind Harmer
1.914
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
316210AC1-098 GEN
Solar/Wind Harmer
2.519
970831AG2-522 GEN
Solar/Wind Harmer
7.914
3145746EVERETS
Solar/Wind Harmer
-0.062
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145893MURPHYS
Solar/Wind Harmer
0.514
3141726DUNNSVL
Solar/Wind Harmer
-0.068
970919AG2-571 GEN
Solar/Wind Harmer
5.396
315607AA1-063A GEN
Solar/Wind Harmer
1.702
3146263WOODLND
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
316337AD2-073 GEN
Solar/Wind Harmer
0.42
316494AC1-189 GEN
Solar/Wind Harmer
1.669
961671AG1-007 GEN
Solar/Wind Harmer
0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.012
972193AH1-681 GEN
Adder
3.242
316005AA1-067
Solar/Wind Harmer
0.318
3145453TOT5
Solar/Wind Harmer
0.142
961601AG1-000A GEN
Solar/Wind Harmer
5.905
972219AH1-694 GEN
50/50
3.204
944631AF1-128 GEN
Adder
87.553
3143526WINTERP
Solar/Wind Harmer
-0.105
315671AE2-027_GEN
Solar/Wind Harmer
3.622
971317AH1-138 GEN
Solar/Wind Harmer
2.494
316314AB2-024 C
Solar/Wind Harmer
1.667
944591AF1-124 GEN
Solar/Wind Harmer
89.022
316072AD1-144
Solar/Wind Harmer
0.391
939411AE1-173 GEN
Solar/Wind Harmer
95.117
940641AE2-051 GEN
Solar/Wind Harmer
17.707
941031AE2-094 GEN
Solar/Wind Harmer
34.052
3143336POWHATN
Solar/Wind Harmer
2.082
971547AH1-271 GEN
Solar/Wind Harmer
4.351
964211AG1-282 GEN
Solar/Wind Harmer
0.517
957861AF2-080 GEN
Solar/Wind Harmer
6.787
3145573BETHELC
Solar/Wind Harmer
-0.015
3145573BETHELC
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.457
316239AB2-077_GEN
Solar/Wind Harmer
0.457
970683AG2-441 GEN
Solar/Wind Harmer
10.714
970681AG2-440 GEN
Solar/Wind Harmer
7.111
316075AC2-137 C
Solar/Wind Harmer
0.565
315778AD1-151 GEN
Solar/Wind Harmer
17.884
3144216WINCHST
Adder
0.669
3151101ELIZAR3
Adder
16.124
944601AF1-125 GEN
Solar/Wind Harmer
87.318
316484AD2-074 GEN
Solar/Wind Harmer
4.499
3143336POWHATN
Solar/Wind Harmer
1.769
966621AG1-532 GEN
Solar/Wind Harmer
0.342
316077AC2-138 C
Solar/Wind Harmer
0.354
3150351NORNECKC2
Adder
1.518
316317KELFORD C
Solar/Wind Harmer
0.772
3145823KELFORD
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.016
316212AC1-099_GEN
Solar/Wind Harmer
1.4
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
315722AD1-056 GEN
Solar/Wind Harmer
5.567
964241AG1-285 GEN
Solar/Wind Harmer
11.889
3144293JTRSVLE
Adder
0.322
942461AE2-259 GEN
Solar/Wind Harmer
2.271
226910AB2-157 C
Solar/Wind Helper
0.016
960081AF2-299 GEN
Solar/Wind Harmer
1.896
3150351NORNECKC2
Adder
1.493
3145823KELFORD
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.016
972277AH1-723 GEN
Adder
84.556
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.376
971065AG2-659 GEN
Solar/Wind Harmer
7.834
316034AC1-036 C
Solar/Wind Harmer
0.281
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.254
3150391LDYSMT3
50/50
28.443
316312AB1-027
Solar/Wind Harmer
0.725
944641AF1-129 GEN
Adder
86.214
3143526WINTERP
Solar/Wind Harmer
-0.105
316185AD1-033 GEN
Solar/Wind Harmer
2.046
316441AF1-014 GEN
Solar/Wind Harmer
1.304
3144356SAPONY
Solar/Wind Harmer
0.644
316315AB2-025 C
Solar/Wind Harmer
0.497
972185AH1-677 GEN
Adder
8.873
962571AG1-106 GEN
Solar/Wind Harmer
2.393
970099AG2-077 GEN
Solar/Wind Harmer
20.587
3145783HORNRTN
Solar/Wind Harmer
1.95
3145783HORNRTN
Solar/Wind Harmer
1.56
3145783HORNRTN
Solar/Wind Harmer
0.488
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
-0.049
315724AD1-057 GEN
Solar/Wind Harmer
3.062
3145603CNETO
Solar/Wind Harmer
0.095
316237AB2-079_GEN
Solar/Wind Harmer
0.457
315687AD1-152 GEN
Solar/Wind Harmer
1.826
3144293JTRSVLE
Adder
0.322
316263AC1-034 GEN
Solar/Wind Harmer
7.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.856
LGEELTFEXP_LGEE->PJM
CLTF
1.602
MECLTFEXP_MEC->PJM
CLTF
4.138
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.661
NYPJM->LTFIMP_NY
CLTF
2.86
TVALTFEXP_TVA->PJM
CLTF
3.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.167
CPLELTFEXP_CPLE->PJM
CLTF
8.87
SIGELTFEXP_SIGE->PJM
CLTF
0.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.339
WECLTFEXP_WEC->PJM
CLTF
0.813
LAGNLTFEXP_LAGN->PJM
CLTF
7.545

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.56 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4356.04
MW Contribution:
38.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150381LDYSMT2
50/50
27.35
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151201GRAVEL4
Adder
12.843
3151221GRAVEL6
Adder
12.828
3151211GRAVEL5
Adder
12.68
316059AD1-063 C
Solar/Wind Harmer
0.437
316311AC2-079 GEN
Solar/Wind Harmer
9.722
313526AB2-022
Solar/Wind Harmer
0.513
3146396TANGLEW
Solar/Wind Harmer
0.349
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
315814AE2-033 C
Solar/Wind Harmer
17.141
3146206CASHIE
Solar/Wind Harmer
-0.017
316318V4-068
Solar/Wind Harmer
0.431
961941AG1-037 GEN
Solar/Wind Harmer
0.128
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146043SEABORD
Solar/Wind Harmer
-0.017
316274AC1-208 GEN
Solar/Wind Harmer
1.717
316486AD2-202 GEN
Solar/Wind Harmer
0.403
961791AG1-021 GEN
Solar/Wind Harmer
1.893
3150371LDYSMT1
50/50
27.528
315051AA1-145 CT1
50/50
1.568
966881AG1-559 GEN
Solar/Wind Harmer
0.673
3142416OLDCHRC
Solar/Wind Harmer
2.174
316473AC1-191 GEN
Solar/Wind Harmer
2.234
3142946ENON
Solar/Wind Harmer
-0.007
970133AG2-095 GEN
Solar/Wind Harmer
2.283
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.276
3141766HARMONY
Solar/Wind Harmer
1.723
316017AA1-139 ULT1
Solar/Wind Harmer
1.558
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.23
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.018
961951AG1-038 GEN
Solar/Wind Harmer
2.354
3146206CASHIE
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
971781AH1-399 GEN
Solar/Wind Harmer
1.032
316181AB2-040 GEN
Solar/Wind Harmer
2.324
3147043LAWRENC
Solar/Wind Harmer
-0.01
316478AD1-087 GEN
Solar/Wind Harmer
1.377
972255AH1-712 GEN
Adder
72.54
316420AA1-050 GEN
Solar/Wind Harmer
1.753
3146073TAR RVR
Solar/Wind Harmer
-0.015
3146083TARBORO
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
15.843
3147133PAMPLIN
Solar/Wind Harmer
-0.047
227287AC2-120 GEN
Solar/Wind Helper
0.389
3150411LDYSMT5
50/50
28.578
972215AH1-692 GEN
50/50
4.627
316233AE1-074 FULL
Solar/Wind Harmer
0.544
971283AH1-107 GEN
Solar/Wind Harmer
3.288
3151191GRAVEL3
Adder
12.68
3138283WHITEMARSH
Solar/Wind Harmer
0.03
316018AA1-139 ULT2
Solar/Wind Harmer
1.649
315833AF1-017_GEN
Solar/Wind Harmer
3.66
3146406KITTY HAWK
Solar/Wind Harmer
0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.572
315800Z1-036_GEN1
Solar/Wind Harmer
4.55
971967AH1-528 GEN
Solar/Wind Harmer
33.177
315732AD1-074 GEN1
Solar/Wind Harmer
3.548
3145893MURPHYS
Solar/Wind Harmer
-0.046
3145893MURPHYS
Solar/Wind Harmer
-0.017
316463AE2-346 GEN
Solar/Wind Harmer
0.276
3145513AHOSKIE
Solar/Wind Harmer
0.149
3145513AHOSKIE
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.539
3141813NORNECK
Solar/Wind Harmer
-0.017
315652AC1-086 GEN
Solar/Wind Harmer
18.724
316174AB2-169 GEN
Solar/Wind Harmer
2.562
316426AA2-053 GEN
Solar/Wind Harmer
1.672
3137643SOCKMAN
Solar/Wind Harmer
-0.066
316327AA2-057 GEN
Solar/Wind Harmer
1.565
3144303KENBRDG
Solar/Wind Harmer
-0.012
946301AF1-294 GEN
Solar/Wind Harmer
3.881
226929AD2-058 GEN
Solar/Wind Helper
0.118
971531AH1-263 GEN
50/50
38.564
972213AH1-691 GEN
50/50
4.627
316382AG1-145 C
Solar/Wind Harmer
0.609
316159AE1-175 C
Solar/Wind Harmer
0.542
971281AH1-106 GEN
Solar/Wind Harmer
3.288
316236AE1-162_GEN
Solar/Wind Harmer
0.592
3143873LANEXA
Solar/Wind Harmer
-0.012
3143316POE
Solar/Wind Harmer
-0.077
970657AG2-426 GEN
Solar/Wind Harmer
1.228
3143096IRON208
Adder
0.775
3142543TWELFTH
Solar/Wind Harmer
-0.002
971069AG2-661 GEN
Solar/Wind Harmer
3.178
316369SG1_INVT
Solar/Wind Harmer
3.573
3138126ROCKLANDING
Solar/Wind Harmer
0.061
961611AG1-000B GEN
Solar/Wind Harmer
9.824
3143226MDLTHAN
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
1.877
3150981CHESPKA
Adder
2.167
316381AD1-082 GEN
Solar/Wind Harmer
1.783
319010AE1-072 C
Solar/Wind Harmer
3.886
315662AE1-191 GEN
Solar/Wind Harmer
2.314
316280AD1-041 GEN
Solar/Wind Harmer
1.446
3138133OCRAN
Solar/Wind Harmer
-0.011
315611Z1-036_GEN2
Solar/Wind Harmer
4.55
3130156CHOWAN
Solar/Wind Harmer
-0.018
315816AE2-034 GEN
Solar/Wind Harmer
1.448
971163AH1-040 GEN
Solar/Wind Harmer
16.817
315737AD1-076 GEN
Solar/Wind Harmer
3.335
316404AE1-155 C
Solar/Wind Harmer
3.339
970087AG2-069 GEN
Solar/Wind Harmer
15.808
316087AB2-174 GEN
Solar/Wind Harmer
2.384
957481AF2-042 GEN
Solar/Wind Harmer
51.45
315693AD1-088 GEN
Solar/Wind Harmer
8.113
3146293MARTNCO
Solar/Wind Harmer
0.1
3141873WAN 176
Solar/Wind Harmer
-0.004
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
3138133OCRAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.018
3130156CHOWAN
Solar/Wind Harmer
-0.018
970533AG2-339 GEN
Solar/Wind Harmer
12.209
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315733AD1-074 GEN2
Solar/Wind Harmer
3.548
316405AF2-144 C
Solar/Wind Harmer
0.448
970601AG2-382 GEN
Solar/Wind Harmer
7.612
970581AG2-369 GEN
Solar/Wind Harmer
9.063
946281AF1-292 GEN
Solar/Wind Harmer
0.377
3146033SCOT NK
Solar/Wind Harmer
-0.065
972205AH1-687 GEN
Adder
5.352
3150401LDYSMT4
50/50
28.489
3143096IRON208
Adder
0.775
3143096IRON208
Adder
0.759
3150861SPRUNCD
Adder
0.843
316458AB2-190 GEN2
Solar/Wind Harmer
2.034
961611AG1-000B GEN
Solar/Wind Harmer
4.192
3151171GRAVELC
Adder
2.468
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
3.934
3141843SHACKLE
Adder
0.879
316246AF1-032 C
Solar/Wind Harmer
0.388
3141873WAN 176
Solar/Wind Harmer
2.269
316321Z2-027
Solar/Wind Harmer
0.511
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3156081AA2-088 GEN
Solar/Wind Harmer
5.689
970917AG2-570 GEN
Solar/Wind Harmer
42.614
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316190AA2-174 GEN
Solar/Wind Harmer
0.204
3145933PARMELE
Solar/Wind Harmer
-0.016
3146233WITAKRS
Solar/Wind Harmer
0.32
3146233WITAKRS
Solar/Wind Harmer
-0.01
970257AG2-171 GEN
Solar/Wind Harmer
5.694
971775AH1-396 GEN
Solar/Wind Harmer
1.071
3146926FARMVIL
Solar/Wind Harmer
-0.009
3147666LOUISA
Solar/Wind Harmer
-0.034
972195AH1-682 GEN
50/50
3.737
972189AH1-679 GEN
50/50
3.521
315673AE1-157 GEN
Solar/Wind Harmer
16.816
3150681DARBY 2
Adder
13.511
316033AB2-134 GEN
Solar/Wind Harmer
6.451
3145506HICKORY
Solar/Wind Harmer
-0.077
3145506HICKORY
Solar/Wind Harmer
-0.046
3145506HICKORY
Solar/Wind Harmer
-0.012
3142366NRTHEST
50/50
0.655
3150691DARBY 3
Adder
13.558
3150701DARBY 4
Adder
13.527
315976AC1-164 GENA
Solar/Wind Harmer
4.727
316169AC1-164_GENC
Solar/Wind Harmer
4.084
3142946ENON
Solar/Wind Harmer
-0.002
316294AC1-161 GEN
Solar/Wind Harmer
6.375
316083AB2-161 GEN
Solar/Wind Harmer
3.163
316349AD2-085 GEN
Solar/Wind Harmer
1.711
3146456SLIGO L269
Solar/Wind Harmer
2.275
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.419
316433W1029_GEN2
Solar/Wind Harmer
3.419
315742AE1-103 GEN
Solar/Wind Harmer
4.37
3146376EDENTON
Solar/Wind Harmer
0.544
3146376EDENTON
Solar/Wind Harmer
0.544
972197AH1-683 GEN
50/50
4.449
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.021
315975AC1-164 GENB
Solar/Wind Harmer
0.14
3142433PROV 92
Solar/Wind Harmer
-0.079
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3145336SMITFLD
Solar/Wind Harmer
-0.078
316375AC2-012 GEN
Solar/Wind Harmer
6.744
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.256
3146456SLIGO L269
Solar/Wind Harmer
-0.019
3145663CRESWEL
Solar/Wind Harmer
-0.05
958261AF2-120 GEN
Solar/Wind Harmer
6.778
3146206CASHIE
Solar/Wind Harmer
-0.017
316023GEN1_S
Solar/Wind Harmer
1.161
970293AG2-193 GEN
Solar/Wind Harmer
2.636
3150921YORKTN3
Adder
4.461
3144536CHRHLND
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
88.673
3142956BIRDNECK
Solar/Wind Harmer
1.044
316203AE2-005 GEN
Solar/Wind Harmer
8.151
316305AF2-043 C
Solar/Wind Harmer
0.578
316320Y1-086
Solar/Wind Harmer
1.117
3146516WINFALL
Solar/Wind Harmer
-0.019
944011AF1-069 GEN
Solar/Wind Harmer
10.666
315735AD1-075 GEN1
Solar/Wind Harmer
1.773
3145893MURPHYS
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.476
961601AG1-000A GEN
Solar/Wind Harmer
5.978
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.017
3156021HOLLOMANSOL
Solar/Wind Harmer
2.303
3145683EARLEYS
Solar/Wind Harmer
-0.017
3147043LAWRENC
Adder
1.317
970937AG2-583 GEN
Solar/Wind Harmer
11.059
3146083TARBORO
Solar/Wind Harmer
-0.015
316319Z2-044 C
Solar/Wind Harmer
0.844
316131AB2-060 GEN
Solar/Wind Harmer
1.638
316359AB2-059 GEN
Solar/Wind Harmer
2.019
3142053HEARTS
Solar/Wind Harmer
0.176
316192AB2-158 GEN
Solar/Wind Harmer
0.906
970933AG2-581 GEN
Solar/Wind Harmer
16.283
316365GEN2_N
Solar/Wind Harmer
1.161
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
10.573
958211AF2-115 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
-0.015
3147133PAMPLIN
Solar/Wind Harmer
-0.012
316339AD2-160 GEN
Solar/Wind Harmer
1.299
316388AE2-253 GEN
Solar/Wind Harmer
1.299
3137176SLIGO L2192
Solar/Wind Harmer
-0.076
3130086AYDLETT
Solar/Wind Harmer
-0.077
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
316487AF1-042 GEN
Solar/Wind Harmer
2.354
3150341NORNECKC1
Adder
1.568
3150341NORNECKC1
Adder
1.555
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
1.338
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
0.137
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
7.778
3145493TOT1
Solar/Wind Harmer
0.236
313527AB2-043 GEN
Solar/Wind Harmer
2.472
970323AG2-213 GEN
Solar/Wind Harmer
7.592
316049AB1-081 GEN
Solar/Wind Harmer
1.615
315052AA1-145 CT2
50/50
1.577
3150851SPRUNCC
Adder
0.843
316132AB2-190 GEN1
Solar/Wind Harmer
2.034
315773AC2-141 GEN
Solar/Wind Harmer
8.249
316036AC1-147 C
Solar/Wind Harmer
0.525
316093AE2-104_GEN
Solar/Wind Harmer
5.564
3146516WINFALL
Solar/Wind Harmer
-0.061
3146516WINFALL
Solar/Wind Harmer
-0.019
962861AG1-135 GEN
Solar/Wind Harmer
6.597
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.514
3141726DUNNSVL
Solar/Wind Harmer
-0.068
970919AG2-571 GEN
Solar/Wind Harmer
5.394
315607AA1-063A GEN
Solar/Wind Harmer
1.701
3146263WOODLND
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
316337AD2-073 GEN
Solar/Wind Harmer
0.42
316494AC1-189 GEN
Solar/Wind Harmer
1.669
961671AG1-007 GEN
Solar/Wind Harmer
0.193
3142296MT RD221
50/50
0.659
3150671DARBY 1
Adder
13.495
966871AG1-558 GEN
Solar/Wind Harmer
0.624
966871AG1-558 GEN
Solar/Wind Harmer
0.214
316240AF1-291 C
Solar/Wind Harmer
0.608
971223AH1-071 GEN
Solar/Wind Harmer
2.479
3150991CHESPKB
Adder
1.818
3150991CHESPKB
Adder
1.775
315666AE1-190 GEN
Solar/Wind Harmer
0.579
315835AF2-110_GEN
Solar/Wind Harmer
2.392
316156AD2-030 GEN
Solar/Wind Harmer
0.509
316435W1029_GEN3
Solar/Wind Harmer
3.419
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
315614AA2-178 GEN
Solar/Wind Harmer
1.93
972187AH1-678 GEN
Adder
4.457
316313AB2-026
Solar/Wind Harmer
0.472
316065AD1-022 GEN
Solar/Wind Harmer
8.732
3145893MURPHYS
Solar/Wind Harmer
0.483
3145893MURPHYS
Solar/Wind Harmer
-0.031
316140AB2-099
Solar/Wind Harmer
0.115
972193AH1-681 GEN
Adder
3.241
316005AA1-067
Solar/Wind Harmer
0.318
3145453TOT5
Solar/Wind Harmer
0.142
961601AG1-000A GEN
Solar/Wind Harmer
5.903
971285AH1-108 GEN
Adder
1.379
315697AD1-025 GEN
Solar/Wind Harmer
4.043
315839AE2-212 C
Solar/Wind Harmer
0.6
971445AH1-216 GEN
Solar/Wind Harmer
12.2
957831AF2-077 GEN
Solar/Wind Harmer
0.588
3151081ELIZAR1
Adder
15.915
3151091ELIZAR2
Adder
15.638
316316AC1-027 C
Solar/Wind Harmer
0.596
957871AF2-081 GEN
Solar/Wind Harmer
9.652
3141913WHIT STONE
Solar/Wind Harmer
-0.019
970673AG2-436 GEN
Solar/Wind Harmer
39.37
316258AE1-075 C
Solar/Wind Harmer
0.425
316468AD1-105 GEN
Solar/Wind Harmer
1.913
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
316210AC1-098 GEN
Solar/Wind Harmer
2.518
970831AG2-522 GEN
Solar/Wind Harmer
7.912
3145746EVERETS
Solar/Wind Harmer
-0.062
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
957861AF2-080 GEN
Solar/Wind Harmer
6.785
3145573BETHELC
Solar/Wind Harmer
-0.015
3145573BETHELC
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.457
316239AB2-077_GEN
Solar/Wind Harmer
0.457
970683AG2-441 GEN
Solar/Wind Harmer
10.71
970681AG2-440 GEN
Solar/Wind Harmer
7.109
316075AC2-137 C
Solar/Wind Harmer
0.565
315778AD1-151 GEN
Solar/Wind Harmer
17.878
3144216WINCHST
Adder
0.669
3151101ELIZAR3
Adder
16.118
944601AF1-125 GEN
Solar/Wind Harmer
87.289
316484AD2-074 GEN
Solar/Wind Harmer
4.498
3143336POWHATN
Solar/Wind Harmer
1.769
966621AG1-532 GEN
Solar/Wind Harmer
0.342
316077AC2-138 C
Solar/Wind Harmer
0.354
3150351NORNECKC2
Adder
1.518
316317KELFORD C
Solar/Wind Harmer
0.772
3145823KELFORD
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.016
316212AC1-099_GEN
Solar/Wind Harmer
1.399
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
315722AD1-056 GEN
Solar/Wind Harmer
5.565
964241AG1-285 GEN
Solar/Wind Harmer
11.884
3144293JTRSVLE
Adder
0.322
942461AE2-259 GEN
Solar/Wind Harmer
2.27
226910AB2-157 C
Solar/Wind Helper
0.016
972219AH1-694 GEN
50/50
3.203
944631AF1-128 GEN
Adder
87.526
3143526WINTERP
Solar/Wind Harmer
-0.105
315671AE2-027_GEN
Solar/Wind Harmer
3.621
971317AH1-138 GEN
Solar/Wind Harmer
2.493
316314AB2-024 C
Solar/Wind Harmer
1.667
944591AF1-124 GEN
Solar/Wind Harmer
88.993
316072AD1-144
Solar/Wind Harmer
0.391
939411AE1-173 GEN
Solar/Wind Harmer
95.084
940641AE2-051 GEN
Solar/Wind Harmer
17.701
941031AE2-094 GEN
Solar/Wind Harmer
34.04
3143336POWHATN
Solar/Wind Harmer
2.081
971547AH1-271 GEN
Solar/Wind Harmer
4.35
964211AG1-282 GEN
Solar/Wind Harmer
0.517
960081AF2-299 GEN
Solar/Wind Harmer
1.895
3150351NORNECKC2
Adder
1.493
3145823KELFORD
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.016
972277AH1-723 GEN
Adder
84.53
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.375
971065AG2-659 GEN
Solar/Wind Harmer
7.831
316034AC1-036 C
Solar/Wind Harmer
0.281
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.254
3145493TOT1
Solar/Wind Harmer
0.454
3146233WITAKRS
Solar/Wind Harmer
-0.06
315785AD2-033 C
Solar/Wind Harmer
3.437
970685AG2-442 GEN
Solar/Wind Harmer
13.262
971563AH1-280 GEN
Solar/Wind Harmer
1.893
3146926FARMVIL
Solar/Wind Harmer
-0.009
3147666LOUISA
Solar/Wind Harmer
-0.06
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3150391LDYSMT3
50/50
28.436
316312AB1-027
Solar/Wind Harmer
0.725
944641AF1-129 GEN
Adder
86.186
3143526WINTERP
Solar/Wind Harmer
-0.105
316185AD1-033 GEN
Solar/Wind Harmer
2.045
316441AF1-014 GEN
Solar/Wind Harmer
1.303
3144356SAPONY
Solar/Wind Harmer
0.644
316315AB2-025 C
Solar/Wind Harmer
0.497
972185AH1-677 GEN
Adder
8.87
962571AG1-106 GEN
Solar/Wind Harmer
2.392
970099AG2-077 GEN
Solar/Wind Harmer
20.58
3145783HORNRTN
Solar/Wind Harmer
1.949
3145783HORNRTN
Solar/Wind Harmer
1.559
3145783HORNRTN
Solar/Wind Harmer
0.487
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
-0.049
315724AD1-057 GEN
Solar/Wind Harmer
3.061
3145603CNETO
Solar/Wind Harmer
0.095
316237AB2-079_GEN
Solar/Wind Harmer
0.457
315687AD1-152 GEN
Solar/Wind Harmer
1.826
3144293JTRSVLE
Adder
0.322
316263AC1-034 GEN
Solar/Wind Harmer
7.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.841
LGEELTFEXP_LGEE->PJM
CLTF
1.602
MECLTFEXP_MEC->PJM
CLTF
4.136
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.651
NYPJM->LTFIMP_NY
CLTF
2.859
TVALTFEXP_TVA->PJM
CLTF
3.819
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.159
CPLELTFEXP_CPLE->PJM
CLTF
8.867
SIGELTFEXP_SIGE->PJM
CLTF
0.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.334
WECLTFEXP_WEC->PJM
CLTF
0.813
LAGNLTFEXP_LAGN->PJM
CLTF
7.542

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.14 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3165.31
MW Contribution:
25.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.78
3150381LDYSMT2
50/50
21.258
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
316059AD1-063 C
Solar/Wind Harmer
0.347
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
3151201GRAVEL4
Adder
9.562
3151221GRAVEL6
Adder
9.551
3151211GRAVEL5
Adder
9.441
316311AC2-079 GEN
Solar/Wind Harmer
7.311
315651AD1-115 GEN
Solar/Wind Harmer
6.333
313526AB2-022
Solar/Wind Harmer
0.387
3146396TANGLEW
Solar/Wind Harmer
0.264
315814AE2-033 C
Solar/Wind Harmer
13.181
3146206CASHIE
Solar/Wind Harmer
-0.014
316318V4-068
Solar/Wind Harmer
0.34
961941AG1-037 GEN
Solar/Wind Harmer
0.102
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.013
3146043SEABORD
Solar/Wind Harmer
-0.013
316486AD2-202 GEN
Solar/Wind Harmer
0.332
971845AH1-439 GEN
Solar/Wind Harmer
6.949
316274AC1-208 GEN
Solar/Wind Harmer
1.402
961791AG1-021 GEN
Solar/Wind Harmer
1.623
232432Z2-076 GEN
Solar/Wind Helper
0.065
3150011OMF A
50/50
0.31
972197AH1-683 GEN
50/50
3.458
972135AH1-637 GEN
Solar/Wind Harmer
1.693
966881AG1-559 GEN
Solar/Wind Harmer
0.173
958261AF2-120 GEN
Solar/Wind Harmer
6.126
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.796
3142433PROV 92
Solar/Wind Harmer
-0.061
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
315975AC1-164 GENB
Solar/Wind Harmer
0.103
316447AC1-158 HLD
Solar/Wind Harmer
3.264
316192AB2-158 GEN
Solar/Wind Harmer
1.754
3145336SMITFLD
Solar/Wind Harmer
-0.058
316375AC2-012 GEN
Solar/Wind Harmer
5.039
3146456SLIGO L269
Solar/Wind Harmer
-0.014
315683AE1-153 C
Solar/Wind Harmer
13.012
3145663CRESWEL
Solar/Wind Harmer
-0.039
3150221REMNGT2
Adder
15.587
3150211REMNGT1
Adder
15.484
972201AH1-685 GEN
Adder
2.689
3146206CASHIE
Solar/Wind Harmer
-0.014
316023GEN1_S
Solar/Wind Harmer
0.916
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.819
3145683EARLEYS
Solar/Wind Harmer
-0.013
970937AG2-583 GEN
Solar/Wind Harmer
9.671
3147043LAWRENC
Adder
1.069
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.2
3150151POSSMC1
50/50
1.949
316337AD2-073 GEN
Solar/Wind Harmer
0.435
3141726DUNNSVL
Solar/Wind Harmer
-0.063
962861AG1-135 GEN
Solar/Wind Harmer
5.92
3150851SPRUNCC
Adder
0.619
316132AB2-190 GEN1
Solar/Wind Harmer
1.504
3150151POSSMC1
50/50
1.949
3150151POSSMC1
50/50
1.949
3150331BIRCHWDA
50/50
29.448
3150501FRIVERG
50/50
1.196
316223AC1-118
Solar/Wind Harmer
0.444
316203AE2-005 GEN
Solar/Wind Harmer
6.488
970293AG2-193 GEN
Solar/Wind Harmer
1.912
3150921YORKTN3
Adder
3.335
3144536CHRHLND
Solar/Wind Harmer
-0.002
944581AF1-123 GEN
Solar/Wind Harmer
66.227
3142956BIRDNECK
Solar/Wind Harmer
0.781
316305AF2-043 C
Solar/Wind Harmer
0.435
316320Y1-086
Solar/Wind Harmer
0.842
3132273ORANGE
Solar/Wind Harmer
-0.003
3146516WINFALL
Solar/Wind Harmer
-0.014
944011AF1-069 GEN
Solar/Wind Harmer
8.27
3150411LDYSMT5
50/50
22.212
972215AH1-692 GEN
50/50
3.596
3141813NORNECK
Solar/Wind Harmer
-0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.461
3138283WHITEMARSH
Solar/Wind Harmer
0.023
316233AE1-074 FULL
Solar/Wind Harmer
0.405
971283AH1-107 GEN
Solar/Wind Harmer
2.444
316164AC1-076 GEN
Solar/Wind Harmer
1.258
3151191GRAVEL3
Adder
9.441
315833AF1-017_GEN
Solar/Wind Harmer
2.753
316018AA1-139 ULT2
Solar/Wind Harmer
1.238
3146406KITTY HAWK
Solar/Wind Harmer
0.012
315800Z1-036_GEN1
Solar/Wind Harmer
3.483
971967AH1-528 GEN
Solar/Wind Harmer
26.063
315732AD1-074 GEN1
Solar/Wind Harmer
2.771
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
316463AE2-346 GEN
Solar/Wind Harmer
0.218
3145513AHOSKIE
Solar/Wind Harmer
0.118
3145513AHOSKIE
Solar/Wind Harmer
-0.013
970085AG2-068 GEN
Solar/Wind Harmer
8.424
3137643SOCKMAN
Solar/Wind Harmer
-0.053
315652AC1-086 GEN
Solar/Wind Harmer
15.006
316426AA2-053 GEN
Solar/Wind Harmer
1.343
316174AB2-169 GEN
Solar/Wind Harmer
2.049
946301AF1-294 GEN
Solar/Wind Harmer
3.327
3144303KENBRDG
Solar/Wind Harmer
-0.01
226929AD2-058 GEN
Solar/Wind Helper
0.404
233901CHERRYDALE C
Solar/Wind Helper
0.227
3150021OMF B
50/50
0.31
3150371LDYSMT1
50/50
21.396
966881AG1-559 GEN
Solar/Wind Harmer
0.505
971781AH1-399 GEN
Solar/Wind Harmer
1.013
961951AG1-038 GEN
Solar/Wind Harmer
2.07
316473AC1-191 GEN
Solar/Wind Harmer
1.685
3142416OLDCHRC
Solar/Wind Harmer
1.554
3141766HARMONY
Solar/Wind Harmer
1.371
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.685
3145336SMITFLD
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
9.176
316017AA1-139 ULT1
Solar/Wind Harmer
1.169
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.674
3145273HOLLAND
Solar/Wind Harmer
-0.011
3146376EDENTON
Solar/Wind Harmer
-0.014
3150241REMNGT4
Adder
15.69
972199AH1-684 GEN
Adder
2.379
3146206CASHIE
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.864
3147043LAWRENC
Solar/Wind Harmer
-0.008
316478AD1-087 GEN
Solar/Wind Harmer
1.135
972255AH1-712 GEN
Adder
59.346
3147133PAMPLIN
Solar/Wind Harmer
-0.041
959311AF2-222 GEN
Solar/Wind Harmer
13.501
227287AC2-120 GEN
Solar/Wind Helper
1.296
232422X3-066 FULL
Solar/Wind Helper
0.112
233964AF2-378 GEN
Solar/Wind Helper
0.041
232406W1-004 FULL
Solar/Wind Helper
0.494
232434Z2-077 GEN
Solar/Wind Helper
0.124
3140676OCCOQUN
50/50
0.023
972213AH1-691 GEN
50/50
3.596
971531AH1-263 GEN
50/50
25.524
944491AF1-114 GEN
Solar/Wind Harmer
5.021
3138133OCRAN
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.003
3143873LANEXA
Solar/Wind Harmer
-0.009
316382AG1-145 C
Solar/Wind Harmer
0.452
316159AE1-175 C
Solar/Wind Harmer
0.403
971281AH1-106 GEN
Solar/Wind Harmer
2.444
316236AE1-162_GEN
Solar/Wind Harmer
0.442
3143316POE
Solar/Wind Harmer
-0.058
970657AG2-426 GEN
Solar/Wind Harmer
0.92
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
316405AF2-144 C
Solar/Wind Harmer
0.362
970533AG2-339 GEN
Solar/Wind Harmer
9.467
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
3147346CASHSCORNER
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315733AD1-074 GEN2
Solar/Wind Harmer
2.771
970601AG2-382 GEN
Solar/Wind Harmer
5.972
970581AG2-369 GEN
Solar/Wind Harmer
7.245
946281AF1-292 GEN
Solar/Wind Harmer
0.302
3146033SCOT NK
Solar/Wind Harmer
-0.053
972205AH1-687 GEN
Adder
4.951
233915AB1-141 GEN
Solar/Wind Helper
0.494
957191AF2-013 GEN
50/50
14.107
3150691DARBY 3
Adder
9.796
3150701DARBY 4
Adder
9.773
3142366NRTHEST
Adder
0.445
315976AC1-164 GENA
Solar/Wind Harmer
3.472
316169AC1-164_GENC
Solar/Wind Harmer
3
3142946ENON
Solar/Wind Harmer
-0.002
316294AC1-161 GEN
Solar/Wind Harmer
4.728
316083AB2-161 GEN
Solar/Wind Harmer
2.37
316349AD2-085 GEN
Solar/Wind Harmer
1.287
3146456SLIGO L269
Solar/Wind Harmer
1.708
3146386ELIZ CT
Solar/Wind Harmer
-0.014
316431W1029_GEN1
Solar/Wind Harmer
2.59
316433W1029_GEN2
Solar/Wind Harmer
2.59
315742AE1-103 GEN
Solar/Wind Harmer
3.349
3146376EDENTON
Solar/Wind Harmer
0.417
3146376EDENTON
Solar/Wind Harmer
0.417
316336AC2-165 C
Solar/Wind Harmer
8.722
970933AG2-581 GEN
Solar/Wind Harmer
12.891
316365GEN2_N
Solar/Wind Harmer
0.916
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.013
3147133PAMPLIN
Solar/Wind Harmer
-0.01
958211AF2-115 GEN
Solar/Wind Harmer
2.029
957971AF2-091 GEN
Solar/Wind Harmer
1.707
316404AE1-155 C
Solar/Wind Harmer
3.018
3138133OCRAN
Solar/Wind Harmer
-0.009
315662AE1-191 GEN
Solar/Wind Harmer
1.851
316280AD1-041 GEN
Solar/Wind Harmer
1.157
3143096IRON208
Adder
0.566
316044AC1-158 PL1
Solar/Wind Harmer
1.484
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.015
3138126ROCKLANDING
Solar/Wind Harmer
0.046
971069AG2-661 GEN
Solar/Wind Harmer
2.354
316369SG1_INVT
Solar/Wind Harmer
2.649
3147666LOUISA
Solar/Wind Harmer
-0.059
961611AG1-000B GEN
Solar/Wind Harmer
7.302
3151171GRAVELC
Adder
1.397
316381AD1-082 GEN
Solar/Wind Harmer
1.336
3150981CHESPKA
Adder
1.619
316254AC1-120 GEN1
Solar/Wind Harmer
5.447
319010AE1-072 C
Solar/Wind Harmer
2.919
315611Z1-036_GEN2
Solar/Wind Harmer
3.483
3151751LOISA D
Adder
8.126
3130156CHOWAN
Solar/Wind Harmer
-0.014
3150281M RUN A
Adder
16.771
315816AE2-034 GEN
Solar/Wind Harmer
1.121
971163AH1-040 GEN
Solar/Wind Harmer
13.019
315737AD1-076 GEN
Solar/Wind Harmer
2.605
970087AG2-069 GEN
Solar/Wind Harmer
12.637
316087AB2-174 GEN
Solar/Wind Harmer
1.91
957481AF2-042 GEN
Solar/Wind Harmer
41.796
315693AD1-088 GEN
Solar/Wind Harmer
6.657
3146926FARMVIL
Solar/Wind Harmer
-0.008
3146293MARTNCO
Solar/Wind Harmer
0.081
971563AH1-280 GEN
Solar/Wind Harmer
1.623
970685AG2-442 GEN
Solar/Wind Harmer
11.348
208835TUHI V3-051
Solar/Wind Helper
0.028
233998TM1NIN_3.36
Solar/Wind Helper
0.2
232404W1-003 C
Solar/Wind Helper
0.494
315785AD2-033 C
Solar/Wind Harmer
1.614
3150181POSSMC2
50/50
1.965
3150181POSSMC2
50/50
1.949
3150181POSSMC2
50/50
1.949
972195AH1-682 GEN
50/50
2.904
315673AE1-157 GEN
Solar/Wind Harmer
12.782
972189AH1-679 GEN
Adder
2.385
3150341NORNECKC1
Adder
1.489
3150341NORNECKC1
Adder
1.477
316487AF1-042 GEN
Solar/Wind Harmer
2.07
3150681DARBY 2
Adder
9.762
316450AC1-158 RIC
Solar/Wind Harmer
0.396
316033AB2-134 GEN
Solar/Wind Harmer
4.783
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316339AD2-160 GEN
Solar/Wind Harmer
0.975
316388AE2-253 GEN
Solar/Wind Harmer
0.975
3137176SLIGO L2192
Solar/Wind Harmer
-0.057
3130086AYDLETT
Solar/Wind Harmer
-0.058
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
966001AG1-469 GEN
Solar/Wind Harmer
0.266
3151731LOISA B
Adder
8.126
313506AB2-031 GEN
Solar/Wind Harmer
1.073
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
0.11
970301AG2-198 GEN
Solar/Wind Harmer
6.602
3145933PARMELE
Solar/Wind Harmer
-0.026
3145933PARMELE
Solar/Wind Harmer
-0.013
970323AG2-213 GEN
Solar/Wind Harmer
6.463
223401AF1-299 GEN
Solar/Wind Helper
0.71
232424Y1-079 C
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.33
234015AF2-250 C
Solar/Wind Helper
0.037
3150101POSSM6S
50/50
2.207
3150401LDYSMT4
50/50
22.143
3141906WESTMOR
Solar/Wind Harmer
-0.007
3141873WAN 176
Solar/Wind Harmer
1.828
3141843SHACKLE
Adder
0.7
3143096IRON208
Adder
0.566
3143096IRON208
Adder
0.555
3150861SPRUNCD
Adder
0.619
316458AB2-190 GEN2
Solar/Wind Harmer
1.504
3147666LOUISA
Solar/Wind Harmer
-0.034
961611AG1-000B GEN
Solar/Wind Harmer
3.116
3151171GRAVELC
Adder
1.838
970657AG2-426 GEN
Solar/Wind Harmer
2.949
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.292
316321Z2-027
Solar/Wind Harmer
0.386
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3150301M RUN C
Adder
16.761
3156081AA2-088 GEN
Solar/Wind Harmer
4.454
970917AG2-570 GEN
Solar/Wind Harmer
33.913
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316190AA2-174 GEN
Solar/Wind Harmer
0.163
3146926FARMVIL
Solar/Wind Harmer
-0.008
3145933PARMELE
Solar/Wind Harmer
-0.013
970257AG2-171 GEN
Solar/Wind Harmer
4.847
971775AH1-396 GEN
Solar/Wind Harmer
0.912
208835TUHI V3-051
Solar/Wind Helper
0.028
233950AC2-186 GEN
Solar/Wind Helper
0.113
3150291M RUN B
Adder
16.636
315735AD1-075 GEN1
Solar/Wind Harmer
1.385
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
-0.014
3146263WOODLND
Solar/Wind Harmer
-0.013
3145963POPLR C
Solar/Wind Harmer
-0.013
316011AB1-132 GEN
Solar/Wind Harmer
2.786
3146776BUCKING
Solar/Wind Harmer
-0.005
233935AB2-179 C
Solar/Wind Helper
1.256
233987AB2-037 GEN
Solar/Wind Helper
2.288
232417X3-008 C
Solar/Wind Helper
0.227
233923SMA
Solar/Wind Helper
0.733
233997TMININ_4.2
Solar/Wind Helper
0.2
3150091POSSM6B
50/50
1.449
966871AG1-558 GEN
Solar/Wind Harmer
0.471
966871AG1-558 GEN
Solar/Wind Harmer
0.161
3142296MT RD221
Adder
0.438
316156AD2-030 GEN
Solar/Wind Harmer
0.41
315666AE1-190 GEN
Solar/Wind Harmer
0.463
3150671DARBY 1
Adder
9.75
316045AC1-158 PL2
Solar/Wind Harmer
4.749
971223AH1-071 GEN
Solar/Wind Harmer
1.867
316240AF1-291 C
Solar/Wind Harmer
0.449
3150991CHESPKB
Adder
1.358
3150991CHESPKB
Adder
1.326
315835AF2-110_GEN
Solar/Wind Harmer
1.803
316435W1029_GEN3
Solar/Wind Harmer
2.59
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
316313AB2-026
Solar/Wind Harmer
0.381
316006AB2-029 C
Solar/Wind Harmer
0.802
315614AA2-178 GEN
Solar/Wind Harmer
1.494
972187AH1-678 GEN
Adder
3.503
316065AD1-022 GEN
Solar/Wind Harmer
6.84
3145893MURPHYS
Solar/Wind Harmer
0.38
3145893MURPHYS
Solar/Wind Harmer
-0.024
316140AB2-099
Solar/Wind Harmer
0.091
3146776BUCKING
Solar/Wind Harmer
-0.052
3146776BUCKING
Solar/Wind Harmer
-0.004
972193AH1-681 GEN
Adder
2.652
316005AA1-067
Solar/Wind Harmer
0.261
232436AB1-176 C
Solar/Wind Helper
0.044
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.937
315773AC2-141 GEN
Solar/Wind Harmer
6.117
316036AC1-147 C
Solar/Wind Harmer
0.392
316170AC1-121 GEN2
Solar/Wind Harmer
1.816
316093AE2-104_GEN
Solar/Wind Harmer
4.194
3146516WINFALL
Solar/Wind Harmer
-0.046
3146516WINFALL
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
0.404
970919AG2-571 GEN
Solar/Wind Harmer
4.293
315607AA1-063A GEN
Solar/Wind Harmer
1.355
3146263WOODLND
Solar/Wind Harmer
-0.013
3145963POPLR C
Solar/Wind Harmer
-0.013
3146776BUCKING
Solar/Wind Harmer
-0.005
233918AB1-142 GEN
Solar/Wind Helper
0.494
3150081POSSM6A
50/50
1.449
316077AC2-138 C
Solar/Wind Harmer
0.336
3150351NORNECKC2
Adder
1.441
316484AD2-074 GEN
Solar/Wind Harmer
3.957
316075AC2-137 C
Solar/Wind Harmer
0.412
3144216WINCHST
Adder
0.5
315778AD1-151 GEN
Solar/Wind Harmer
13.243
3151101ELIZAR3
Adder
12.041
944601AF1-125 GEN
Solar/Wind Harmer
65.193
3143336POWHATN
Solar/Wind Harmer
1.429
3151761LOISA E
Adder
16.567
3151721LOISA A
Adder
8.084
3141316ARNOLDS
50/50
0.022
3141426STAFORD
Solar/Wind Harmer
-0.004
316468AD1-105 GEN
Solar/Wind Harmer
1.878
3141913WHIT STONE
Solar/Wind Harmer
-0.015
957831AF2-077 GEN
Solar/Wind Harmer
0.455
971285AH1-108 GEN
Adder
1.013
315697AD1-025 GEN
Solar/Wind Harmer
2.998
315839AE2-212 C
Solar/Wind Harmer
0.446
971445AH1-216 GEN
Solar/Wind Harmer
9.094
3151081ELIZAR1
Adder
11.889
3151091ELIZAR2
Adder
11.683
316316AC1-027 C
Solar/Wind Harmer
0.446
957871AF2-081 GEN
Solar/Wind Harmer
7.242
316258AE1-075 C
Solar/Wind Harmer
0.343
970673AG2-436 GEN
Solar/Wind Harmer
30.638
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.005
316210AC1-098 GEN
Solar/Wind Harmer
2.048
316322AB2-045
Solar/Wind Harmer
0.439
970831AG2-522 GEN
Solar/Wind Harmer
6.516
970683AG2-441 GEN
Solar/Wind Harmer
9.15
970681AG2-440 GEN
Solar/Wind Harmer
6.073
3145746EVERETS
Solar/Wind Harmer
-0.051
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
233940AF2-379 C
Solar/Wind Helper
0.06
972223AH1-696 GEN
50/50
15.393
3141346CRANES
50/50
0.214
972219AH1-694 GEN
50/50
2.49
3150351NORNECKC2
Adder
1.418
964211AG1-282 GEN
Solar/Wind Harmer
0.478
316314AB2-024 C
Solar/Wind Harmer
1.316
944631AF1-128 GEN
Adder
64.269
3143526WINTERP
Solar/Wind Harmer
-0.078
971317AH1-138 GEN
Solar/Wind Harmer
1.876
315671AE2-027_GEN
Solar/Wind Harmer
2.688
944591AF1-124 GEN
Solar/Wind Harmer
66.465
316072AD1-144
Solar/Wind Harmer
0.293
939411AE1-173 GEN
Solar/Wind Harmer
72.085
940641AE2-051 GEN
Solar/Wind Harmer
13.479
3143336POWHATN
Solar/Wind Harmer
1.681
941031AE2-094 GEN
Solar/Wind Harmer
26.395
971685AH1-345 GEN
Solar/Wind Harmer
1.224
971547AH1-271 GEN
Solar/Wind Harmer
3.413
960081AF2-299 GEN
Solar/Wind Harmer
1.515
3145823KELFORD
Solar/Wind Harmer
-0.013
3145783HORNRTN
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.013
972277AH1-723 GEN
Adder
69.157
316129AC1-054 GEN
Solar/Wind Harmer
1.136
3144293JTRSVLE
Adder
0.276
3144293JTRSVLE
Adder
0.218
971065AG2-659 GEN
Solar/Wind Harmer
6.485
316034AC1-036 C
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
233944AB2-135 GEN
Solar/Wind Helper
0.579
232408W1-005 C
Solar/Wind Helper
0.494
972217AH1-693 GEN
Adder
2.069
966621AG1-532 GEN
Solar/Wind Harmer
0.273
3141196NOKESVL
Solar/Wind Harmer
-0.054
316317KELFORD C
Solar/Wind Harmer
0.617
3145823KELFORD
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.013
316212AC1-099_GEN
Solar/Wind Harmer
1.138
942461AE2-259 GEN
Solar/Wind Harmer
1.963
972003AH1-546 GEN
Solar/Wind Harmer
5.292
3144293JTRSVLE
Adder
0.276
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
226910AB2-157 C
Solar/Wind Helper
0.05
233933AB2-153 GEN
Solar/Wind Helper
0.228
3150071POSSM 5
50/50
89.066
3150391LDYSMT3
50/50
22.101
316312AB1-027
Solar/Wind Harmer
0.518
316441AF1-014 GEN
Solar/Wind Harmer
1.037
3143526WINTERP
Solar/Wind Harmer
-0.078
944641AF1-129 GEN
Adder
63.441
316185AD1-033 GEN
Solar/Wind Harmer
1.53
3144356SAPONY
Solar/Wind Harmer
0.495
316315AB2-025 C
Solar/Wind Harmer
0.382
972185AH1-677 GEN
Adder
6.942
970099AG2-077 GEN
Solar/Wind Harmer
16.718
962571AG1-106 GEN
Solar/Wind Harmer
1.917
3145783HORNRTN
Solar/Wind Harmer
1.573
3145783HORNRTN
Solar/Wind Harmer
1.258
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
3145796HORNRTN
Solar/Wind Harmer
-0.039
3144293JTRSVLE
Adder
0.276
223402AF1-300 C
Solar/Wind Helper
0.71
233982AB2-133 GEN
Solar/Wind Helper
0.353
233930AB2-032 GEN
Solar/Wind Helper
0.374
233946AB2-136 GEN
Solar/Wind Helper
0.555
232410W1-006 C
Solar/Wind Helper
0.494
233952AC2-187 GEN
Solar/Wind Helper
0.227
233954AC2-188 GEN
Solar/Wind Helper
0.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
68.184
LGEELTFEXP_LGEE->PJM
CLTF
3.215
MECLTFEXP_MEC->PJM
CLTF
7.907
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.085
NYPJM->LTFIMP_NY
CLTF
3.83
TVALTFEXP_TVA->PJM
CLTF
5.501
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.864
CPLELTFEXP_CPLE->PJM
CLTF
8.311
SIGELTFEXP_SIGE->PJM
CLTF
0.248
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.104
WECLTFEXP_WEC->PJM
CLTF
1.726
LAGNLTFEXP_LAGN->PJM
CLTF
10.93

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.64 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5476.52
MW Contribution:
58.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
19.197
970119AG2-088 GEN
50/50
34.653
3150851SPRUNCC
50/50
1.197
315773AC2-141 GEN
Solar/Wind Harmer
11.191
316132AB2-190 GEN1
Solar/Wind Harmer
2.685
3143526WINTERP
Solar/Wind Harmer
-0.147
940641AE2-051 GEN
Solar/Wind Harmer
25.67
939411AE1-173 GEN
Solar/Wind Harmer
135.71
315671AE2-027_GEN
Solar/Wind Harmer
4.83
944631AF1-128 GEN
Adder
112.885
941031AE2-094 GEN
Solar/Wind Harmer
49.846
944641AF1-129 GEN
50/50
120.863
3143526WINTERP
Solar/Wind Harmer
-0.147
316312AB1-027
Solar/Wind Harmer
0.89
316185AD1-033 GEN
Solar/Wind Harmer
2.781
971507AH1-251 GEN
50/50
16.234
316447AC1-158 HLD
Solar/Wind Harmer
14.621
316192AB2-158 GEN
Solar/Wind Harmer
3.418
3143096IRON208
50/50
1.064
316044AC1-158 PL1
Solar/Wind Harmer
6.648
3147666LOUISA
Solar/Wind Harmer
-0.117
3143226MDLTHAN
Solar/Wind Harmer
-0.029
3142543TWELFTH
Solar/Wind Harmer
-0.003
971069AG2-661 GEN
Solar/Wind Harmer
4.207
316369SG1_INVT
Solar/Wind Harmer
4.737
3142366NRTHEST
50/50
0.827
3150691DARBY 3
50/50
18.147
3150701DARBY 4
50/50
18.105
316294AC1-161 GEN
Solar/Wind Harmer
8.649
3142946ENON
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
4.292
315976AC1-164 GENA
Solar/Wind Harmer
5.959
316169AC1-164_GENC
Solar/Wind Harmer
5.149
3146456SLIGO L269
Solar/Wind Harmer
3.095
3150681DARBY 2
50/50
18.083
316450AC1-158 RIC
Solar/Wind Harmer
1.773
316033AB2-134 GEN
Solar/Wind Harmer
8.553
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.768
316388AE2-253 GEN
Solar/Wind Harmer
1.768
3137176SLIGO L2192
Solar/Wind Harmer
-0.104
316349AD2-085 GEN
Solar/Wind Harmer
2.326
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.653
316433W1029_GEN2
Solar/Wind Harmer
4.653
970933AG2-581 GEN
Solar/Wind Harmer
23.595
315742AE1-103 GEN
Solar/Wind Harmer
5.961
3146376EDENTON
Solar/Wind Harmer
0.741
3146376EDENTON
Solar/Wind Harmer
0.741
316336AC2-165 C
Solar/Wind Harmer
14.972
316365GEN2_N
Solar/Wind Harmer
1.611
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.273
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.017
970133AG2-095 GEN
Solar/Wind Harmer
3.001
315813AE1-149 C
Solar/Wind Harmer
16.644
3142946ENON
Solar/Wind Harmer
-0.009
3145336SMITFLD
Solar/Wind Harmer
-0.01
3142416OLDCHRC
Solar/Wind Harmer
2.671
316017AA1-139 ULT1
Solar/Wind Harmer
2.119
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.033
316303AF2-085
50/50
4.62
3151201GRAVEL4
Adder
17.149
3151221GRAVEL6
Adder
17.13
3151211GRAVEL5
Adder
16.932
316311AC2-079 GEN
Solar/Wind Harmer
13.213
313526AB2-022
Solar/Wind Harmer
0.698
3146396TANGLEW
Solar/Wind Harmer
0.475
315814AE2-033 C
Solar/Wind Harmer
24.049
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
316059AD1-063 C
Solar/Wind Harmer
0.57
3150381LDYSMT2
Adder
28.487
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3146206CASHIE
Solar/Wind Harmer
-0.024
316318V4-068
Solar/Wind Harmer
0.59
961941AG1-037 GEN
Solar/Wind Harmer
0.176
3146043SEABORD
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316486AD2-202 GEN
Solar/Wind Harmer
0.572
316274AC1-208 GEN
Solar/Wind Harmer
2.352
961791AG1-021 GEN
Solar/Wind Harmer
2.618
316375AC2-012 GEN
Solar/Wind Harmer
9.16
3145336SMITFLD
Solar/Wind Harmer
-0.105
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
315975AC1-164 GENB
Solar/Wind Harmer
0.176
3146456SLIGO L269
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.103
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
966881AG1-559 GEN
Solar/Wind Harmer
0.262
971777AH1-397 GEN
Solar/Wind Harmer
2.952
3141766HARMONY
Solar/Wind Harmer
-0.005
972197AH1-683 GEN
Adder
4.633
3145663CRESWEL
Solar/Wind Harmer
-0.068
316023GEN1_S
Solar/Wind Harmer
1.611
3146206CASHIE
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.159
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.146
3145683EARLEYS
Solar/Wind Harmer
-0.023
3147043LAWRENC
Adder
1.825
970937AG2-583 GEN
Solar/Wind Harmer
15.235
316131AB2-060 GEN
Solar/Wind Harmer
2.27
316319Z2-044 C
Solar/Wind Harmer
1.151
3146083TARBORO
Solar/Wind Harmer
-0.021
316036AC1-147 C
Solar/Wind Harmer
0.713
316093AE2-104_GEN
Solar/Wind Harmer
7.57
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
970919AG2-571 GEN
Solar/Wind Harmer
7.8
962861AG1-135 GEN
Solar/Wind Harmer
8.898
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.703
3141726DUNNSVL
Solar/Wind Harmer
-0.093
315607AA1-063A GEN
Solar/Wind Harmer
2.337
3146263WOODLND
Solar/Wind Harmer
-0.023
316045AC1-158 PL2
Solar/Wind Harmer
21.272
971223AH1-071 GEN
Solar/Wind Harmer
3.65
316240AF1-291 C
Solar/Wind Harmer
0.807
3150671DARBY 1
Adder
17.022
3142296MT RD221
Adder
0.756
3150991CHESPKB
Adder
2.469
3150991CHESPKB
Adder
2.41
315835AF2-110_GEN
Solar/Wind Harmer
3.255
966871AG1-558 GEN
Solar/Wind Harmer
0.774
966871AG1-558 GEN
Solar/Wind Harmer
0.265
316435W1029_GEN3
Solar/Wind Harmer
4.653
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
316164AC1-076 GEN
Solar/Wind Harmer
2.864
316233AE1-074 FULL
Solar/Wind Harmer
0.766
971283AH1-107 GEN
Solar/Wind Harmer
4.625
3151191GRAVEL3
Adder
16.932
316018AA1-139 ULT2
Solar/Wind Harmer
2.244
315833AF1-017_GEN
Solar/Wind Harmer
4.975
3146406KITTY HAWK
Solar/Wind Harmer
0.022
3138283WHITEMARSH
Solar/Wind Harmer
0.04
971967AH1-528 GEN
Solar/Wind Harmer
48.266
957601AF2-054 GEN
Solar/Wind Harmer
0.752
315800Z1-036_GEN1
Solar/Wind Harmer
6.196
3150411LDYSMT5
Adder
29.765
972215AH1-692 GEN
Adder
4.819
970085AG2-068 GEN
Solar/Wind Harmer
15.207
315732AD1-074 GEN1
Solar/Wind Harmer
4.836
944011AF1-069 GEN
Solar/Wind Harmer
15.618
944581AF1-123 GEN
Solar/Wind Harmer
120.729
970293AG2-193 GEN
Solar/Wind Harmer
3.318
3144536CHRHLND
Solar/Wind Harmer
-0.004
3142956BIRDNECK
Solar/Wind Harmer
1.419
3150921YORKTN3
Adder
5.878
316305AF2-043 C
Solar/Wind Harmer
0.787
316320Y1-086
Solar/Wind Harmer
1.519
3144356SAPONY
Solar/Wind Harmer
0.904
316315AB2-025 C
Solar/Wind Harmer
0.697
972185AH1-677 GEN
Adder
12.93
316441AF1-014 GEN
Solar/Wind Harmer
1.705
3150391LDYSMT3
Adder
29.617
970099AG2-077 GEN
Solar/Wind Harmer
29.42
962571AG1-106 GEN
Solar/Wind Harmer
3.295
3145783HORNRTN
Solar/Wind Harmer
2.682
3145783HORNRTN
Solar/Wind Harmer
2.145
3145783HORNRTN
Solar/Wind Harmer
0.67
3145783HORNRTN
Solar/Wind Harmer
0.268
3145796HORNRTN
Solar/Wind Harmer
-0.067
315724AD1-057 GEN
Solar/Wind Harmer
4.19
315687AD1-152 GEN
Solar/Wind Harmer
2.562
316237AB2-079_GEN
Solar/Wind Harmer
0.633
3144293JTRSVLE
Adder
0.445
3145603CNETO
Solar/Wind Harmer
0.129
316411AF1-147_GEN1
Solar/Wind Helper
0.773
971285AH1-108 GEN
50/50
1.959
3146516WINFALL
Solar/Wind Harmer
-0.026
316203AE2-005 GEN
Solar/Wind Harmer
10.664
315735AD1-075 GEN1
Solar/Wind Harmer
2.417
3145893MURPHYS
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.377
3145513AHOSKIE
Solar/Wind Harmer
0.204
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3141813NORNECK
Solar/Wind Harmer
-0.023
315652AC1-086 GEN
Solar/Wind Harmer
25.789
315839AE2-212 C
Solar/Wind Harmer
0.807
315697AD1-025 GEN
Solar/Wind Harmer
5.361
3151081ELIZAR1
Adder
21.62
3151091ELIZAR2
Adder
21.245
971445AH1-216 GEN
Solar/Wind Harmer
16.388
316316AC1-027 C
Solar/Wind Harmer
0.81
970673AG2-436 GEN
Solar/Wind Harmer
57.55
957871AF2-081 GEN
Solar/Wind Harmer
13.131
957831AF2-077 GEN
Solar/Wind Harmer
0.774
316258AE1-075 C
Solar/Wind Harmer
0.607
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.009
316468AD1-105 GEN
Solar/Wind Harmer
2.561
316210AC1-098 GEN
Solar/Wind Harmer
3.447
970831AG2-522 GEN
Solar/Wind Harmer
10.939
3145746EVERETS
Solar/Wind Harmer
-0.085
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
315778AD1-151 GEN
Solar/Wind Harmer
23.662
944601AF1-125 GEN
Solar/Wind Harmer
118.845
3151101ELIZAR3
Adder
21.897
316075AC2-137 C
Solar/Wind Harmer
0.709
3144216WINCHST
Adder
0.883
3137643SOCKMAN
Solar/Wind Harmer
-0.091
316426AA2-053 GEN
Solar/Wind Harmer
2.3
316174AB2-169 GEN
Solar/Wind Harmer
3.49
316327AA2-057 GEN
Solar/Wind Harmer
2.138
3144303KENBRDG
Solar/Wind Harmer
-0.017
946301AF1-294 GEN
Solar/Wind Harmer
5.368
3138216PACIFIC
Solar/Wind Helper
0.038
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
316473AC1-191 GEN
Solar/Wind Harmer
2.769
966881AG1-559 GEN
Solar/Wind Harmer
0.766
3145273HOLLAND
Solar/Wind Harmer
-0.019
3141766HARMONY
Solar/Wind Harmer
2.248
3146376EDENTON
Solar/Wind Harmer
-0.025
3150371LDYSMT1
Adder
28.672
961951AG1-038 GEN
Solar/Wind Harmer
3.159
3146206CASHIE
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.211
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.954
971781AH1-399 GEN
Solar/Wind Harmer
1.381
959311AF2-222 GEN
Solar/Wind Harmer
21.929
316420AA1-050 GEN
Solar/Wind Harmer
2.387
3147133PAMPLIN
Solar/Wind Harmer
-0.065
3146073TAR RVR
Solar/Wind Harmer
-0.021
3146083TARBORO
Solar/Wind Harmer
-0.021
3138543CONSLDL
Solar/Wind Harmer
-0.014
972255AH1-712 GEN
Adder
73.955
971531AH1-263 GEN
50/50
58.97
971281AH1-106 GEN
Solar/Wind Harmer
4.625
3143316POE
Solar/Wind Harmer
-0.106
970533AG2-339 GEN
Solar/Wind Harmer
17.877
316236AE1-162_GEN
Solar/Wind Harmer
0.796
970657AG2-426 GEN
Solar/Wind Harmer
1.667
316382AG1-145 C
Solar/Wind Harmer
0.79
316159AE1-175 C
Solar/Wind Harmer
0.703
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3143873LANEXA
Solar/Wind Harmer
-0.015
3141873WAN 176
Solar/Wind Harmer
-0.005
316405AF2-144 C
Solar/Wind Harmer
0.64
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
972213AH1-691 GEN
Adder
4.819
3138133OCRAN
Solar/Wind Harmer
-0.007
970581AG2-369 GEN
Solar/Wind Harmer
13.078
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315733AD1-074 GEN2
Solar/Wind Harmer
4.836
970601AG2-382 GEN
Solar/Wind Harmer
10.385
946281AF1-292 GEN
Solar/Wind Harmer
0.523
3146033SCOT NK
Solar/Wind Harmer
-0.089
3152261N ANNA2
50/50
19.207
3150861SPRUNCD
50/50
1.197
3143096IRON208
50/50
1.064
3143096IRON208
50/50
1.042
3147666LOUISA
Solar/Wind Harmer
-0.067
316458AB2-190 GEN2
Solar/Wind Harmer
2.685
961611AG1-000B GEN
Solar/Wind Harmer
5.582
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3151171GRAVELC
Adder
3.296
970657AG2-426 GEN
Solar/Wind Harmer
5.34
316246AF1-032 C
Solar/Wind Harmer
0.528
972205AH1-687 GEN
Adder
7.164
961611AG1-000B GEN
Solar/Wind Harmer
13.081
3150981CHESPKA
Adder
2.943
3151171GRAVELC
Adder
2.506
316381AD1-082 GEN
Solar/Wind Harmer
2.42
3138126ROCKLANDING
Solar/Wind Harmer
0.081
319010AE1-072 C
Solar/Wind Harmer
5.286
315662AE1-191 GEN
Solar/Wind Harmer
3.033
316280AD1-041 GEN
Solar/Wind Harmer
1.896
315611Z1-036_GEN2
Solar/Wind Harmer
6.196
3130156CHOWAN
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.015
315816AE2-034 GEN
Solar/Wind Harmer
1.972
971163AH1-040 GEN
Solar/Wind Harmer
22.915
970087AG2-069 GEN
Solar/Wind Harmer
22.81
315737AD1-076 GEN
Solar/Wind Harmer
4.547
316404AE1-155 C
Solar/Wind Harmer
4.512
957481AF2-042 GEN
Solar/Wind Harmer
73.55
316087AB2-174 GEN
Solar/Wind Harmer
3.296
315693AD1-088 GEN
Solar/Wind Harmer
11.536
3146293MARTNCO
Solar/Wind Harmer
0.136
315785AD2-033 C
Solar/Wind Harmer
4.759
970685AG2-442 GEN
Solar/Wind Harmer
18.346
971563AH1-280 GEN
Solar/Wind Harmer
2.618
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145493TOT1
Solar/Wind Harmer
0.618
3146926FARMVIL
Solar/Wind Harmer
-0.012
3151751LOISA D
Adder
10.097
972189AH1-679 GEN
Adder
3.905
3130086AYDLETT
Solar/Wind Harmer
-0.104
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315673AE1-157 GEN
Solar/Wind Harmer
18.939
972195AH1-682 GEN
Adder
3.892
316487AF1-042 GEN
Solar/Wind Harmer
3.159
313506AB2-031 GEN
Solar/Wind Harmer
1.848
3150341NORNECKC1
Adder
2.145
3150341NORNECKC1
Adder
2.128
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.189
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
970301AG2-198 GEN
Solar/Wind Harmer
10.875
313527AB2-043 GEN
Solar/Wind Harmer
3.426
970323AG2-213 GEN
Solar/Wind Harmer
10.51
3145493TOT1
Solar/Wind Harmer
0.322
3151731LOISA B
Adder
10.097
316321Z2-027
Solar/Wind Harmer
0.695
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3141843SHACKLE
Adder
1.15
3141873WAN 176
Solar/Wind Harmer
2.983
3150401LDYSMT4
Adder
29.673
970917AG2-570 GEN
Solar/Wind Harmer
61.622
3156081AA2-088 GEN
Solar/Wind Harmer
7.785
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.28
3145933PARMELE
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
7.882
971775AH1-396 GEN
Solar/Wind Harmer
1.483
3141906WESTMOR
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.436
3146233WITAKRS
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.012
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.023
316011AB1-132 GEN
Solar/Wind Harmer
4.788
3145963POPLR C
Solar/Wind Harmer
-0.023
316223AC1-118
Solar/Wind Harmer
0.562
3150331BIRCHWDA
Adder
20.228
961601AG1-000A GEN
Solar/Wind Harmer
7.106
972187AH1-678 GEN
Adder
6.484
315666AE1-190 GEN
Solar/Wind Harmer
0.758
316156AD2-030 GEN
Solar/Wind Harmer
0.669
316313AB2-026
Solar/Wind Harmer
0.674
315614AA2-178 GEN
Solar/Wind Harmer
2.63
316065AD1-022 GEN
Solar/Wind Harmer
11.91
3145893MURPHYS
Solar/Wind Harmer
0.661
3145893MURPHYS
Solar/Wind Harmer
-0.043
316140AB2-099
Solar/Wind Harmer
0.157
316005AA1-067
Solar/Wind Harmer
0.433
3145453TOT5
Solar/Wind Harmer
0.193
972193AH1-681 GEN
Adder
3.304
316006AB2-029 C
Solar/Wind Helper
0.109
961601AG1-000A GEN
Solar/Wind Harmer
7.017
3145963POPLR C
Solar/Wind Harmer
-0.023
316337AD2-073 GEN
Solar/Wind Harmer
0.59
316494AC1-189 GEN
Solar/Wind Harmer
2.272
961671AG1-007 GEN
Solar/Wind Harmer
0.263
3143336POWHATN
Solar/Wind Harmer
2.528
957861AF2-080 GEN
Solar/Wind Harmer
9.24
316238AB2-078_GEN
Solar/Wind Harmer
0.633
316239AB2-077_GEN
Solar/Wind Harmer
0.633
970683AG2-441 GEN
Solar/Wind Harmer
14.819
970681AG2-440 GEN
Solar/Wind Harmer
9.836
3145573BETHELC
Solar/Wind Harmer
-0.021
3145573BETHELC
Solar/Wind Harmer
-0.021
944591AF1-124 GEN
Solar/Wind Harmer
121.164
316072AD1-144
Solar/Wind Harmer
0.529
971317AH1-138 GEN
Solar/Wind Harmer
3.269
316314AB2-024 C
Solar/Wind Harmer
2.165
3143336POWHATN
Solar/Wind Harmer
2.974
972219AH1-694 GEN
Adder
3.336
971547AH1-271 GEN
Solar/Wind Harmer
5.934
960081AF2-299 GEN
Solar/Wind Harmer
2.626
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3150351NORNECKC2
Adder
2.042
3145823KELFORD
Solar/Wind Harmer
-0.023
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.022
316129AC1-054 GEN
Solar/Wind Harmer
1.903
971065AG2-659 GEN
Solar/Wind Harmer
10.839
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
316034AC1-036 C
Solar/Wind Harmer
0.389
3144293JTRSVLE
Adder
0.445
3144293JTRSVLE
Adder
0.351
972277AH1-723 GEN
Adder
86.18
316415AF1-147_GEN2
Solar/Wind Helper
0.773
316484AD2-074 GEN
Solar/Wind Harmer
6.037
966621AG1-532 GEN
Solar/Wind Harmer
0.474
316077AC2-138 C
Solar/Wind Harmer
0.484
3150351NORNECKC2
Adder
2.077
316317KELFORD C
Solar/Wind Harmer
1.055
3145823KELFORD
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.022
316212AC1-099_GEN
Solar/Wind Harmer
1.915
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
315722AD1-056 GEN
Solar/Wind Harmer
7.618
964241AG1-285 GEN
Solar/Wind Harmer
16.465
3144293JTRSVLE
Adder
0.445
942461AE2-259 GEN
Solar/Wind Harmer
3.135
3151761LOISA E
Adder
20.585
3151721LOISA A
Adder
10.045
3141196NOKESVL
Solar/Wind Helper
0.971
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.747
LGEELTFEXP_LGEE->PJM
CLTF
1.147
MECLTFEXP_MEC->PJM
CLTF
3.205
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.335
NYPJM->LTFIMP_NY
CLTF
3.267
TVALTFEXP_TVA->PJM
CLTF
3.917
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.44
CPLELTFEXP_CPLE->PJM
CLTF
11.736
SIGELTFEXP_SIGE->PJM
CLTF
0.097
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.188
WECLTFEXP_WEC->PJM
CLTF
0.539
LAGNLTFEXP_LAGN->PJM
CLTF
7.726

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:161.05 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5186.56
MW Contribution:
60.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
19.692
970119AG2-088 GEN
50/50
35.314
3150851SPRUNCC
50/50
1.215
315773AC2-141 GEN
Solar/Wind Harmer
8.836
316132AB2-190 GEN1
Solar/Wind Harmer
1.282
316036AC1-147 C
Solar/Wind Harmer
0.043
316093AE2-104_GEN
Solar/Wind Harmer
3.964
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
970919AG2-571 GEN
Solar/Wind Harmer
7.964
3145893MURPHYS
Solar/Wind Harmer
0.859
3145893MURPHYS
Solar/Wind Harmer
0.955
962861AG1-135 GEN
Solar/Wind Harmer
6.77
315607AA1-063A GEN
Solar/Wind Harmer
0.423
3146263WOODLND
Solar/Wind Harmer
0.21
3145963POPLR C
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.829
316337AD2-073 GEN
Solar/Wind Harmer
0.168
316494AC1-189 GEN
Solar/Wind Harmer
0.649
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.149
3146776BUCKING
Solar/Wind Harmer
0.073
316170AC1-121 GEN2
Solar/Wind Harmer
2.073
3143526WINTERP
Solar/Wind Harmer
1.339
940641AE2-051 GEN
Solar/Wind Harmer
19.868
939411AE1-173 GEN
Solar/Wind Harmer
104.983
315671AE2-027_GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
44.451
944591AF1-124 GEN
Solar/Wind Harmer
54.274
944631AF1-128 GEN
Adder
114.38
316072AD1-144
Solar/Wind Harmer
0.084
971317AH1-138 GEN
Solar/Wind Harmer
1.761
3143336POWHATN
Solar/Wind Harmer
4.059
972219AH1-694 GEN
Adder
3.301
971547AH1-271 GEN
Solar/Wind Harmer
4.593
960081AF2-299 GEN
Solar/Wind Harmer
2.035
3145823KELFORD
Solar/Wind Harmer
0.207
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.676
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.039
316129AC1-054 GEN
Solar/Wind Harmer
0.739
971065AG2-659 GEN
Solar/Wind Harmer
8.417
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
316034AC1-036 C
Solar/Wind Harmer
0.013
3144293JTRSVLE
Adder
0.457
3144293JTRSVLE
Adder
0.36
970401AG2-262 GEN
Solar/Wind Harmer
1.07
3147623JAMES R
Solar/Wind Harmer
0.376
972277AH1-723 GEN
Adder
88.48
316415AF1-147_GEN2
Solar/Wind Helper
0.823
944641AF1-129 GEN
50/50
122.663
3150791HOPHCF3
50/50
0.977
3143526WINTERP
Solar/Wind Harmer
1.339
316312AB1-027
Solar/Wind Harmer
0.424
972185AH1-677 GEN
Adder
13.194
3144356SAPONY
Solar/Wind Harmer
1.966
316315AB2-025 C
Solar/Wind Harmer
0.188
3150391LDYSMT3
Adder
29.307
970099AG2-077 GEN
Solar/Wind Harmer
22.839
962571AG1-106 GEN
Solar/Wind Harmer
2.96
3145783HORNRTN
Solar/Wind Harmer
3.649
3145783HORNRTN
Solar/Wind Harmer
2.919
3145783HORNRTN
Solar/Wind Harmer
0.912
3145783HORNRTN
Solar/Wind Harmer
0.365
3145796HORNRTN
Solar/Wind Harmer
0.615
315724AD1-057 GEN
Solar/Wind Harmer
3.752
3144293JTRSVLE
Adder
0.457
3145603CNETO
Solar/Wind Harmer
0.176
316263AC1-034 GEN
Solar/Wind Harmer
7.074
962561AG1-105 GEN
Solar/Wind Harmer
8.825
316411AF1-147_GEN1
Solar/Wind Helper
0.823
971507AH1-251 GEN
50/50
16.761
3152331SURRY 2
50/50
9.861
316447AC1-158 HLD
Solar/Wind Harmer
6.655
316192AB2-158 GEN
Solar/Wind Harmer
1.504
316375AC2-012 GEN
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
0.957
3142416OLDCHRC
Solar/Wind Harmer
0.619
3142416OLDCHRC
Solar/Wind Harmer
0.237
3146456SLIGO L269
Solar/Wind Harmer
0.237
315975AC1-164 GENB
Solar/Wind Harmer
0.073
3142433PROV 92
Solar/Wind Harmer
0.928
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
971777AH1-397 GEN
Solar/Wind Harmer
0.599
3141766HARMONY
Solar/Wind Harmer
0.045
966881AG1-559 GEN
Solar/Wind Harmer
0.261
3145663CRESWEL
Solar/Wind Harmer
0.62
972197AH1-683 GEN
Adder
4.585
316023GEN1_S
Solar/Wind Harmer
0.483
3146206CASHIE
Solar/Wind Harmer
0.215
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.956
3145683EARLEYS
Solar/Wind Harmer
0.211
958261AF2-120 GEN
Solar/Wind Harmer
6.965
3147043LAWRENC
Adder
1.864
970937AG2-583 GEN
Solar/Wind Harmer
11.909
316131AB2-060 GEN
Solar/Wind Harmer
0.598
3146083TARBORO
Solar/Wind Harmer
0.189
316359AB2-059 GEN
Solar/Wind Harmer
0.662
3142053HEARTS
Solar/Wind Harmer
0.328
972135AH1-637 GEN
Solar/Wind Harmer
1.428
3143096IRON208
50/50
1.078
3150771HOPHCF1
50/50
0.977
316044AC1-158 PL1
Solar/Wind Harmer
3.026
3147666LOUISA
Solar/Wind Harmer
1.095
3143226MDLTHAN
Solar/Wind Harmer
0.265
3142543TWELFTH
Solar/Wind Harmer
0.023
971069AG2-661 GEN
Solar/Wind Harmer
4.269
3150981CHESPKA
Adder
2.993
961611AG1-000B GEN
Solar/Wind Harmer
12.562
316381AD1-082 GEN
Solar/Wind Harmer
0.243
3151171GRAVELC
Adder
2.545
3138126ROCKLANDING
Solar/Wind Harmer
0.109
319010AE1-072 C
Solar/Wind Harmer
1.182
3130156CHOWAN
Solar/Wind Harmer
0.226
3138133OCRAN
Solar/Wind Harmer
0.133
315816AE2-034 GEN
Solar/Wind Harmer
0.945
971163AH1-040 GEN
Solar/Wind Harmer
17.724
970087AG2-069 GEN
Solar/Wind Harmer
17.689
315737AD1-076 GEN
Solar/Wind Harmer
2.787
957481AF2-042 GEN
Solar/Wind Harmer
57.098
316404AE1-155 C
Solar/Wind Harmer
0
315693AD1-088 GEN
Solar/Wind Harmer
10.082
3146293MARTNCO
Solar/Wind Harmer
0.184
315785AD2-033 C
Solar/Wind Harmer
1.551
970685AG2-442 GEN
Solar/Wind Harmer
14.29
971563AH1-280 GEN
Solar/Wind Harmer
2.04
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.754
3145493TOT1
Solar/Wind Harmer
0.842
316254AC1-120 GEN1
Solar/Wind Harmer
6.037
3151751LOISA D
Adder
10.875
3142366NRTHEST
50/50
0.837
3150691DARBY 3
50/50
18.374
3150701DARBY 4
50/50
18.331
316294AC1-161 GEN
Solar/Wind Harmer
4.182
3142946ENON
Solar/Wind Harmer
0.024
3146456SLIGO L269
Solar/Wind Harmer
4.197
316349AD2-085 GEN
Solar/Wind Harmer
0.158
315976AC1-164 GENA
Solar/Wind Harmer
2.483
316169AC1-164_GENC
Solar/Wind Harmer
2.145
3146386ELIZ CT
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
18.296
315742AE1-103 GEN
Solar/Wind Harmer
3.398
3146376EDENTON
Solar/Wind Harmer
1.005
3146376EDENTON
Solar/Wind Harmer
1.005
316336AC2-165 C
Solar/Wind Harmer
11.083
316365GEN2_N
Solar/Wind Harmer
0.483
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958211AF2-115 GEN
Solar/Wind Harmer
2.295
3147133PAMPLIN
Solar/Wind Harmer
0.191
971377AH1-170 GEN
Solar/Wind Harmer
1.732
316450AC1-158 RIC
Solar/Wind Harmer
0.807
3150681DARBY 2
Adder
17.255
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
0.153
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
970133AG2-095 GEN
Solar/Wind Harmer
2.312
315813AE1-149 C
Solar/Wind Harmer
12.846
3145336SMITFLD
Solar/Wind Harmer
0.096
3142946ENON
Solar/Wind Harmer
0.08
3142416OLDCHRC
Solar/Wind Harmer
2.309
316017AA1-139 ULT1
Solar/Wind Harmer
0.127
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.742
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
316473AC1-191 GEN
Solar/Wind Harmer
0.78
3145273HOLLAND
Solar/Wind Harmer
0.172
3141766HARMONY
Solar/Wind Harmer
3.024
3146376EDENTON
Solar/Wind Harmer
0.226
3150371LDYSMT1
Adder
28.372
3146206CASHIE
Solar/Wind Harmer
0.215
3146173TUNIS
Solar/Wind Harmer
0.213
316181AB2-040 GEN
Solar/Wind Harmer
0.298
3147043LAWRENC
Solar/Wind Harmer
0.124
316478AD1-087 GEN
Solar/Wind Harmer
0.713
971781AH1-399 GEN
Solar/Wind Harmer
0.26
959311AF2-222 GEN
Solar/Wind Harmer
17.039
3147133PAMPLIN
Solar/Wind Harmer
0.6
3146073TAR RVR
Solar/Wind Harmer
0.189
3146083TARBORO
Solar/Wind Harmer
0.189
3138543CONSLDL
Solar/Wind Harmer
0.125
971623AH1-311 GEN
Solar/Wind Harmer
0.372
316222AC1-221 GEN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Harmer
0.308
972255AH1-712 GEN
Adder
75.929
316303AF2-085
50/50
4.708
3151201GRAVEL4
Adder
17.415
3151221GRAVEL6
Adder
17.395
3151211GRAVEL5
Adder
17.195
316311AC2-079 GEN
Solar/Wind Harmer
6.807
313526AB2-022
Solar/Wind Harmer
0.125
315814AE2-033 C
Solar/Wind Harmer
18.521
3146396TANGLEW
Solar/Wind Harmer
0.645
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150381LDYSMT2
Adder
28.188
3146206CASHIE
Solar/Wind Harmer
0.215
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.422
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
316486AD2-202 GEN
Solar/Wind Harmer
0.21
316274AC1-208 GEN
Solar/Wind Harmer
1.024
961791AG1-021 GEN
Solar/Wind Harmer
1.836
971845AH1-439 GEN
Solar/Wind Harmer
8.303
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.109
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.003
315651AD1-115 GEN
Solar/Wind Harmer
0
3150781HOPHCF2
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
9.684
971223AH1-071 GEN
Solar/Wind Harmer
2.825
3150671DARBY 1
Adder
17.235
3142296MT RD221
Adder
0.765
3150991CHESPKB
Adder
2.511
3150991CHESPKB
Adder
2.45
315835AF2-110_GEN
Solar/Wind Harmer
1.617
972187AH1-678 GEN
Adder
6.617
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
966871AG1-558 GEN
Solar/Wind Harmer
0.267
316313AB2-026
Solar/Wind Harmer
0.142
316156AD2-030 GEN
Solar/Wind Harmer
0.165
315614AA2-178 GEN
Solar/Wind Harmer
1.26
316065AD1-022 GEN
Solar/Wind Harmer
9.946
3145893MURPHYS
Solar/Wind Harmer
1.438
3145893MURPHYS
Solar/Wind Harmer
0.387
316140AB2-099
Solar/Wind Harmer
0.075
316005AA1-067
Solar/Wind Harmer
0.208
3145453TOT5
Solar/Wind Harmer
0.263
961601AG1-000A GEN
Solar/Wind Harmer
3.311
3146776BUCKING
Solar/Wind Harmer
0.73
3146776BUCKING
Solar/Wind Harmer
0.059
964791AG1-342 GEN
Solar/Wind Harmer
3.501
316118AC1-105 GEN
Solar/Wind Harmer
0.457
972193AH1-681 GEN
Adder
3.393
942751AE2-291 GEN
Solar/Wind Harmer
7.272
316164AC1-076 GEN
Solar/Wind Harmer
0.439
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971283AH1-107 GEN
Solar/Wind Harmer
3.573
3151191GRAVEL3
Adder
17.195
3146406KITTY HAWK
Solar/Wind Harmer
0.029
971967AH1-528 GEN
Solar/Wind Harmer
37.313
3138283WHITEMARSH
Solar/Wind Harmer
0.054
970189AG2-124 GEN
Solar/Wind Harmer
6.729
970085AG2-068 GEN
Solar/Wind Harmer
11.793
3150411LDYSMT5
Adder
29.454
972215AH1-692 GEN
Adder
4.768
315732AD1-074 GEN1
Solar/Wind Harmer
1.238
3145893MURPHYS
Solar/Wind Harmer
0.58
3145893MURPHYS
Solar/Wind Harmer
0.215
316463AE2-346 GEN
Solar/Wind Harmer
0.181
3145513AHOSKIE
Solar/Wind Harmer
0.443
3145513AHOSKIE
Solar/Wind Harmer
0.212
315652AC1-086 GEN
Solar/Wind Harmer
22.888
3137643SOCKMAN
Solar/Wind Harmer
0.83
316426AA2-053 GEN
Solar/Wind Harmer
0.693
3141813NORNECK
Solar/Wind Harmer
0.204
316327AA2-057 GEN
Solar/Wind Harmer
0.285
3144303KENBRDG
Solar/Wind Harmer
0.153
946301AF1-294 GEN
Solar/Wind Harmer
3.774
3138216PACIFIC
Solar/Wind Helper
0.04
3150761HOPPOLC
50/50
0.611
3151161SURRY 1
50/50
9.746
944011AF1-069 GEN
Solar/Wind Harmer
14.524
944581AF1-123 GEN
Solar/Wind Harmer
54.082
3144536CHRHLND
Solar/Wind Harmer
0.036
970293AG2-193 GEN
Solar/Wind Harmer
2.551
3150921YORKTN3
Adder
5.961
3146516WINFALL
Solar/Wind Harmer
0.232
316203AE2-005 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.618
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
3146263WOODLND
Solar/Wind Harmer
0.21
316011AB1-132 GEN
Solar/Wind Harmer
3.774
3145963POPLR C
Solar/Wind Harmer
0.207
3132273ORANGE
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
13.243
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.186
316223AC1-118
Solar/Wind Harmer
0.131
3146776BUCKING
Solar/Wind Harmer
0.066
970221AG2-151 GEN
Solar/Wind Harmer
8.658
270494AE1-108_GEN
Solar/Wind Harmer
1.705
971285AH1-108 GEN
50/50
1.989
315697AD1-025 GEN
Solar/Wind Harmer
0.258
3151081ELIZAR1
Adder
21.982
3151091ELIZAR2
Adder
21.6
971445AH1-216 GEN
Solar/Wind Harmer
16.859
316316AC1-027 C
Solar/Wind Harmer
0.228
970673AG2-436 GEN
Solar/Wind Harmer
29.727
957871AF2-081 GEN
Solar/Wind Harmer
11.832
316258AE1-075 C
Solar/Wind Harmer
0.17
3141913WHIT STONE
Solar/Wind Harmer
0.222
3145796HORNRTN
Solar/Wind Harmer
0.655
3145796HORNRTN
Solar/Wind Harmer
0.082
316210AC1-098 GEN
Solar/Wind Harmer
1.848
970831AG2-522 GEN
Solar/Wind Harmer
8.491
3145746EVERETS
Solar/Wind Harmer
0.776
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
957861AF2-080 GEN
Solar/Wind Harmer
8.277
970683AG2-441 GEN
Solar/Wind Harmer
11.541
970681AG2-440 GEN
Solar/Wind Harmer
7.66
3145573BETHELC
Solar/Wind Harmer
0.189
3145573BETHELC
Solar/Wind Harmer
0.189
3150801HOPHCF4
50/50
1.422
944601AF1-125 GEN
Solar/Wind Harmer
53.249
315778AD1-151 GEN
Solar/Wind Harmer
19.212
3151101ELIZAR3
Adder
22.264
3144216WINCHST
Adder
0.895
316075AC2-137 C
Solar/Wind Harmer
0.063
3143336POWHATN
Solar/Wind Harmer
3.45
3145506HICKORY
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
316339AD2-160 GEN
Solar/Wind Harmer
0.381
316388AE2-253 GEN
Solar/Wind Harmer
0.74
3137176SLIGO L2192
Solar/Wind Harmer
0.944
3130086AYDLETT
Solar/Wind Harmer
0.947
972189AH1-679 GEN
Adder
3.929
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146626S HERTFORD
Solar/Wind Harmer
0.23
315673AE1-157 GEN
Solar/Wind Harmer
15.458
972195AH1-682 GEN
Adder
3.851
313506AB2-031 GEN
Solar/Wind Harmer
0.642
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
3145593CAROLNA
Solar/Wind Harmer
0.206
3145593CAROLNA
Solar/Wind Harmer
0.206
3145593CAROLNA
Solar/Wind Harmer
0.257
3150341NORNECKC1
Adder
2.142
3150341NORNECKC1
Adder
2.124
3145933PARMELE
Solar/Wind Harmer
0.398
3145933PARMELE
Solar/Wind Harmer
0.199
970301AG2-198 GEN
Solar/Wind Harmer
8.471
970323AG2-213 GEN
Solar/Wind Harmer
8.181
3145493TOT1
Solar/Wind Harmer
0.439
316049AB1-081 GEN
Solar/Wind Harmer
1.059
966001AG1-469 GEN
Solar/Wind Harmer
0.098
3151731LOISA B
Adder
10.875
971531AH1-263 GEN
50/50
60.361
971281AH1-106 GEN
Solar/Wind Harmer
3.573
3143316POE
Solar/Wind Harmer
0.961
970533AG2-339 GEN
Solar/Wind Harmer
18.235
970657AG2-426 GEN
Solar/Wind Harmer
1.756
316159AE1-175 C
Solar/Wind Harmer
0.203
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
3145176PASQUOTANK
Solar/Wind Harmer
0.145
3143873LANEXA
Solar/Wind Harmer
0.137
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
3138133OCRAN
Solar/Wind Harmer
0.066
970581AG2-369 GEN
Solar/Wind Harmer
10.142
972213AH1-691 GEN
Adder
4.768
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315733AD1-074 GEN2
Solar/Wind Harmer
1.238
970601AG2-382 GEN
Solar/Wind Harmer
8.037
3146033SCOT NK
Solar/Wind Harmer
0.812
972205AH1-687 GEN
Adder
7.406
3147346CASHSCORNER
Solar/Wind Harmer
0.369
944491AF1-114 GEN
Solar/Wind Harmer
0
3152261N ANNA2
50/50
19.702
3150861SPRUNCD
50/50
1.215
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.057
3147666LOUISA
Solar/Wind Harmer
0.63
316458AB2-190 GEN2
Solar/Wind Harmer
1.282
3144873MCLAUGH
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
6.387
3151171GRAVELC
Adder
3.347
970657AG2-426 GEN
Solar/Wind Harmer
5.366
316246AF1-032 C
Solar/Wind Harmer
0.105
316321Z2-027
Solar/Wind Harmer
0.042
3146626S HERTFORD
Solar/Wind Harmer
0.23
3141843SHACKLE
Adder
1.16
3141873WAN 176
Solar/Wind Harmer
4.01
970917AG2-570 GEN
Solar/Wind Harmer
19.909
3150401LDYSMT4
Adder
29.362
3156081AA2-088 GEN
Solar/Wind Harmer
0
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
3145933PARMELE
Solar/Wind Harmer
0.199
970257AG2-171 GEN
Solar/Wind Harmer
6.136
971775AH1-396 GEN
Solar/Wind Harmer
0.307
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.952
3146233WITAKRS
Solar/Wind Harmer
0.129
3141906WESTMOR
Solar/Wind Harmer
0.073
3145823KELFORD
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
0.819
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.073
316212AC1-099_GEN
Solar/Wind Harmer
1.031
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
6.726
964241AG1-285 GEN
Solar/Wind Harmer
12.809
3144293JTRSVLE
Adder
0.457
942461AE2-259 GEN
Solar/Wind Harmer
0
972003AH1-546 GEN
Solar/Wind Harmer
6.047
3151761LOISA E
Adder
22.171
3151721LOISA A
Adder
10.819
971683AH1-343 GEN
Solar/Wind Harmer
5.878
316123AC1-075 GEN
Solar/Wind Harmer
0.189
315821AE2-092 GEN
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.552
LGEELTFEXP_LGEE->PJM
CLTF
1.281
MECLTFEXP_MEC->PJM
CLTF
3.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.986
NYPJM->LTFIMP_NY
CLTF
3.442
TVALTFEXP_TVA->PJM
CLTF
4.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.265
CPLELTFEXP_CPLE->PJM
CLTF
12.057
SIGELTFEXP_SIGE->PJM
CLTF
0.107
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.014
WECLTFEXP_WEC->PJM
CLTF
0.611
LAGNLTFEXP_LAGN->PJM
CLTF
8.173

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.64 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5817.13
MW Contribution:
60.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
19.692
970119AG2-088 GEN
50/50
35.314
3150851SPRUNCC
50/50
1.215
315773AC2-141 GEN
Solar/Wind Harmer
11.379
316132AB2-190 GEN1
Solar/Wind Harmer
2.725
316036AC1-147 C
Solar/Wind Harmer
0.725
316093AE2-104_GEN
Solar/Wind Harmer
7.699
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
970919AG2-571 GEN
Solar/Wind Harmer
7.964
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.716
962861AG1-135 GEN
Solar/Wind Harmer
8.914
315607AA1-063A GEN
Solar/Wind Harmer
2.383
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316337AD2-073 GEN
Solar/Wind Harmer
0.585
316494AC1-189 GEN
Solar/Wind Harmer
2.321
961671AG1-007 GEN
Solar/Wind Harmer
0.269
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.16
939411AE1-173 GEN
Solar/Wind Harmer
138.227
315671AE2-027_GEN
Solar/Wind Harmer
4.903
941031AE2-094 GEN
Solar/Wind Harmer
50.844
944591AF1-124 GEN
Solar/Wind Harmer
123.208
944631AF1-128 GEN
Adder
114.38
316072AD1-144
Solar/Wind Harmer
0.538
971317AH1-138 GEN
Solar/Wind Harmer
3.313
3143336POWHATN
Solar/Wind Harmer
3.044
316314AB2-024 C
Solar/Wind Harmer
2.184
972219AH1-694 GEN
Adder
3.301
971547AH1-271 GEN
Solar/Wind Harmer
6.047
960081AF2-299 GEN
Solar/Wind Harmer
2.68
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3145823KELFORD
Solar/Wind Harmer
-0.023
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.039
316129AC1-054 GEN
Solar/Wind Harmer
1.945
971065AG2-659 GEN
Solar/Wind Harmer
11.082
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316034AC1-036 C
Solar/Wind Harmer
0.398
3144293JTRSVLE
Adder
0.457
3144293JTRSVLE
Adder
0.36
972277AH1-723 GEN
Adder
88.48
316415AF1-147_GEN2
Solar/Wind Helper
0.823
944641AF1-129 GEN
50/50
122.663
3150791HOPHCF3
50/50
0.977
3143526WINTERP
Solar/Wind Harmer
-0.15
316185AD1-033 GEN
Solar/Wind Harmer
2.828
316312AB1-027
Solar/Wind Harmer
0.9
972185AH1-677 GEN
Adder
13.194
3144356SAPONY
Solar/Wind Harmer
0.921
316315AB2-025 C
Solar/Wind Harmer
0.71
316441AF1-014 GEN
Solar/Wind Harmer
1.72
3150391LDYSMT3
Adder
29.307
970099AG2-077 GEN
Solar/Wind Harmer
30.072
962571AG1-106 GEN
Solar/Wind Harmer
3.362
3145783HORNRTN
Solar/Wind Harmer
2.737
3145783HORNRTN
Solar/Wind Harmer
2.19
3145783HORNRTN
Solar/Wind Harmer
0.684
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
315724AD1-057 GEN
Solar/Wind Harmer
4.279
315687AD1-152 GEN
Solar/Wind Harmer
2.622
316237AB2-079_GEN
Solar/Wind Harmer
0.648
3144293JTRSVLE
Adder
0.457
3145603CNETO
Solar/Wind Harmer
0.132
316411AF1-147_GEN1
Solar/Wind Helper
0.823
971507AH1-251 GEN
50/50
16.761
3152331SURRY 2
50/50
9.861
316447AC1-158 HLD
Solar/Wind Harmer
15.119
316192AB2-158 GEN
Solar/Wind Harmer
3.571
316375AC2-012 GEN
Solar/Wind Harmer
9.313
3145336SMITFLD
Solar/Wind Harmer
-0.107
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
-0.027
315975AC1-164 GENB
Solar/Wind Harmer
0.178
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
971777AH1-397 GEN
Solar/Wind Harmer
2.978
3141766HARMONY
Solar/Wind Harmer
-0.005
966881AG1-559 GEN
Solar/Wind Harmer
0.261
3145663CRESWEL
Solar/Wind Harmer
-0.069
972197AH1-683 GEN
Adder
4.585
316023GEN1_S
Solar/Wind Harmer
1.642
3146206CASHIE
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.207
3145683EARLEYS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.171
3147043LAWRENC
Adder
1.864
970937AG2-583 GEN
Solar/Wind Harmer
15.68
316131AB2-060 GEN
Solar/Wind Harmer
2.325
316319Z2-044 C
Solar/Wind Harmer
1.177
3146083TARBORO
Solar/Wind Harmer
-0.021
3143096IRON208
50/50
1.078
3150771HOPHCF1
50/50
0.977
316044AC1-158 PL1
Solar/Wind Harmer
6.874
3147666LOUISA
Solar/Wind Harmer
-0.122
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3142543TWELFTH
Solar/Wind Harmer
-0.003
971069AG2-661 GEN
Solar/Wind Harmer
4.269
316369SG1_INVT
Solar/Wind Harmer
4.808
3150981CHESPKA
Adder
2.993
961611AG1-000B GEN
Solar/Wind Harmer
13.282
316381AD1-082 GEN
Solar/Wind Harmer
2.46
3151171GRAVELC
Adder
2.545
3138126ROCKLANDING
Solar/Wind Harmer
0.082
319010AE1-072 C
Solar/Wind Harmer
5.376
315611Z1-036_GEN2
Solar/Wind Harmer
6.307
315662AE1-191 GEN
Solar/Wind Harmer
3.059
316280AD1-041 GEN
Solar/Wind Harmer
1.912
3130156CHOWAN
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.015
315816AE2-034 GEN
Solar/Wind Harmer
2.009
971163AH1-040 GEN
Solar/Wind Harmer
23.336
970087AG2-069 GEN
Solar/Wind Harmer
23.291
315737AD1-076 GEN
Solar/Wind Harmer
4.632
957481AF2-042 GEN
Solar/Wind Harmer
75.18
316404AE1-155 C
Solar/Wind Harmer
4.518
316087AB2-174 GEN
Solar/Wind Harmer
3.363
315693AD1-088 GEN
Solar/Wind Harmer
11.799
3146293MARTNCO
Solar/Wind Harmer
0.138
315785AD2-033 C
Solar/Wind Harmer
4.877
970685AG2-442 GEN
Solar/Wind Harmer
18.815
971563AH1-280 GEN
Solar/Wind Harmer
2.686
3146926FARMVIL
Solar/Wind Harmer
-0.013
3146233WITAKRS
Solar/Wind Harmer
-0.084
3145493TOT1
Solar/Wind Harmer
0.631
3151751LOISA D
Adder
10.875
3142366NRTHEST
50/50
0.837
3150691DARBY 3
50/50
18.374
3150701DARBY 4
50/50
18.331
316294AC1-161 GEN
Solar/Wind Harmer
8.794
316083AB2-161 GEN
Solar/Wind Harmer
4.363
3142946ENON
Solar/Wind Harmer
-0.003
3146456SLIGO L269
Solar/Wind Harmer
3.148
316349AD2-085 GEN
Solar/Wind Harmer
2.365
315976AC1-164 GENA
Solar/Wind Harmer
6.029
316169AC1-164_GENC
Solar/Wind Harmer
5.209
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.734
316433W1029_GEN2
Solar/Wind Harmer
4.734
970933AG2-581 GEN
Solar/Wind Harmer
24.089
315742AE1-103 GEN
Solar/Wind Harmer
6.067
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
316336AC2-165 C
Solar/Wind Harmer
15.345
316365GEN2_N
Solar/Wind Harmer
1.642
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958211AF2-115 GEN
Solar/Wind Harmer
3.357
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.017
316450AC1-158 RIC
Solar/Wind Harmer
1.833
3150681DARBY 2
Adder
17.255
316033AB2-134 GEN
Solar/Wind Harmer
8.682
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.798
316388AE2-253 GEN
Solar/Wind Harmer
1.798
3137176SLIGO L2192
Solar/Wind Harmer
-0.105
3130086AYDLETT
Solar/Wind Harmer
-0.106
972189AH1-679 GEN
Adder
3.929
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
315673AE1-157 GEN
Solar/Wind Harmer
18.836
972195AH1-682 GEN
Adder
3.851
316487AF1-042 GEN
Solar/Wind Harmer
3.168
313506AB2-031 GEN
Solar/Wind Harmer
1.886
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.193
3150341NORNECKC1
Adder
2.142
3150341NORNECKC1
Adder
2.124
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
970301AG2-198 GEN
Solar/Wind Harmer
11.154
313527AB2-043 GEN
Solar/Wind Harmer
3.508
970323AG2-213 GEN
Solar/Wind Harmer
10.772
3145493TOT1
Solar/Wind Harmer
0.329
3151731LOISA B
Adder
10.875
970133AG2-095 GEN
Solar/Wind Harmer
3.045
315813AE1-149 C
Solar/Wind Harmer
16.914
3145336SMITFLD
Solar/Wind Harmer
-0.011
3142946ENON
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
2.701
316017AA1-139 ULT1
Solar/Wind Harmer
2.155
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.085
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
316473AC1-191 GEN
Solar/Wind Harmer
2.791
3145273HOLLAND
Solar/Wind Harmer
-0.019
3141766HARMONY
Solar/Wind Harmer
2.268
3146376EDENTON
Solar/Wind Harmer
-0.025
966881AG1-559 GEN
Solar/Wind Harmer
0.764
3150371LDYSMT1
Adder
28.372
3146206CASHIE
Solar/Wind Harmer
-0.024
961951AG1-038 GEN
Solar/Wind Harmer
3.168
3146173TUNIS
Solar/Wind Harmer
-0.024
316181AB2-040 GEN
Solar/Wind Harmer
3.276
3147043LAWRENC
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
1.999
971781AH1-399 GEN
Solar/Wind Harmer
1.371
959311AF2-222 GEN
Solar/Wind Harmer
22.479
3147133PAMPLIN
Solar/Wind Harmer
-0.067
316420AA1-050 GEN
Solar/Wind Harmer
2.439
3146073TAR RVR
Solar/Wind Harmer
-0.021
3146083TARBORO
Solar/Wind Harmer
-0.021
3138543CONSLDL
Solar/Wind Harmer
-0.014
972255AH1-712 GEN
Adder
75.929
316303AF2-085
50/50
4.708
3151201GRAVEL4
Adder
17.415
3151221GRAVEL6
Adder
17.395
3151211GRAVEL5
Adder
17.195
316311AC2-079 GEN
Solar/Wind Harmer
13.436
313526AB2-022
Solar/Wind Harmer
0.71
315814AE2-033 C
Solar/Wind Harmer
24.496
3146396TANGLEW
Solar/Wind Harmer
0.484
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
316059AD1-063 C
Solar/Wind Harmer
0.574
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150381LDYSMT2
Adder
28.188
3146206CASHIE
Solar/Wind Harmer
-0.024
316318V4-068
Solar/Wind Harmer
0.602
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
316486AD2-202 GEN
Solar/Wind Harmer
0.585
316274AC1-208 GEN
Solar/Wind Harmer
2.401
961791AG1-021 GEN
Solar/Wind Harmer
2.686
3150781HOPHCF2
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
21.996
971223AH1-071 GEN
Solar/Wind Harmer
3.72
316240AF1-291 C
Solar/Wind Harmer
0.819
3150671DARBY 1
Adder
17.235
3142296MT RD221
Adder
0.765
3150991CHESPKB
Adder
2.511
3150991CHESPKB
Adder
2.45
315835AF2-110_GEN
Solar/Wind Harmer
3.31
316435W1029_GEN3
Solar/Wind Harmer
4.734
972187AH1-678 GEN
Adder
6.617
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.78
966871AG1-558 GEN
Solar/Wind Harmer
0.267
316313AB2-026
Solar/Wind Harmer
0.69
315666AE1-190 GEN
Solar/Wind Harmer
0.765
316156AD2-030 GEN
Solar/Wind Harmer
0.675
315614AA2-178 GEN
Solar/Wind Harmer
2.678
316065AD1-022 GEN
Solar/Wind Harmer
12.135
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
316140AB2-099
Solar/Wind Harmer
0.16
316005AA1-067
Solar/Wind Harmer
0.442
3145453TOT5
Solar/Wind Harmer
0.197
972193AH1-681 GEN
Adder
3.393
961601AG1-000A GEN
Solar/Wind Harmer
7.45
316164AC1-076 GEN
Solar/Wind Harmer
3.008
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971283AH1-107 GEN
Solar/Wind Harmer
4.705
3151191GRAVEL3
Adder
17.195
316018AA1-139 ULT2
Solar/Wind Harmer
2.282
315833AF1-017_GEN
Solar/Wind Harmer
5.059
3146406KITTY HAWK
Solar/Wind Harmer
0.022
971967AH1-528 GEN
Solar/Wind Harmer
49.26
3138283WHITEMARSH
Solar/Wind Harmer
0.04
315800Z1-036_GEN1
Solar/Wind Harmer
6.307
957601AF2-054 GEN
Solar/Wind Harmer
0.758
970085AG2-068 GEN
Solar/Wind Harmer
15.527
3150411LDYSMT5
Adder
29.454
972215AH1-692 GEN
Adder
4.768
315732AD1-074 GEN1
Solar/Wind Harmer
4.927
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.384
3145513AHOSKIE
Solar/Wind Harmer
0.208
3145513AHOSKIE
Solar/Wind Harmer
-0.024
315652AC1-086 GEN
Solar/Wind Harmer
26.311
3137643SOCKMAN
Solar/Wind Harmer
-0.093
316426AA2-053 GEN
Solar/Wind Harmer
2.346
316174AB2-169 GEN
Solar/Wind Harmer
3.559
3141813NORNECK
Solar/Wind Harmer
-0.023
316327AA2-057 GEN
Solar/Wind Harmer
2.184
3144303KENBRDG
Solar/Wind Harmer
-0.017
946301AF1-294 GEN
Solar/Wind Harmer
5.506
3138216PACIFIC
Solar/Wind Helper
0.04
971285AH1-108 GEN
50/50
1.989
315839AE2-212 C
Solar/Wind Harmer
0.82
315697AD1-025 GEN
Solar/Wind Harmer
5.441
3151081ELIZAR1
Adder
21.982
3151091ELIZAR2
Adder
21.6
971445AH1-216 GEN
Solar/Wind Harmer
16.648
316316AC1-027 C
Solar/Wind Harmer
0.824
970673AG2-436 GEN
Solar/Wind Harmer
58.71
957871AF2-081 GEN
Solar/Wind Harmer
13.354
957831AF2-077 GEN
Solar/Wind Harmer
0.782
316258AE1-075 C
Solar/Wind Harmer
0.621
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
3.519
970831AG2-522 GEN
Solar/Wind Harmer
11.18
316468AD1-105 GEN
Solar/Wind Harmer
2.542
3145746EVERETS
Solar/Wind Harmer
-0.087
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
957861AF2-080 GEN
Solar/Wind Harmer
9.438
316238AB2-078_GEN
Solar/Wind Harmer
0.648
316239AB2-077_GEN
Solar/Wind Harmer
0.648
970683AG2-441 GEN
Solar/Wind Harmer
15.196
970681AG2-440 GEN
Solar/Wind Harmer
10.086
3145573BETHELC
Solar/Wind Harmer
-0.021
3145573BETHELC
Solar/Wind Harmer
-0.021
3150761HOPPOLC
50/50
0.611
3151161SURRY 1
50/50
9.746
944011AF1-069 GEN
Solar/Wind Harmer
15.931
944581AF1-123 GEN
Solar/Wind Harmer
122.766
3144536CHRHLND
Solar/Wind Harmer
-0.004
3142956BIRDNECK
Solar/Wind Harmer
1.443
970293AG2-193 GEN
Solar/Wind Harmer
3.358
3150921YORKTN3
Adder
5.961
316305AF2-043 C
Solar/Wind Harmer
0.8
316320Y1-086
Solar/Wind Harmer
1.546
3146516WINFALL
Solar/Wind Harmer
-0.026
316203AE2-005 GEN
Solar/Wind Harmer
10.757
315735AD1-075 GEN1
Solar/Wind Harmer
2.463
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.023
316011AB1-132 GEN
Solar/Wind Harmer
4.884
3145963POPLR C
Solar/Wind Harmer
-0.023
3132273ORANGE
Solar/Wind Harmer
-0.004
961601AG1-000A GEN
Solar/Wind Harmer
7.544
971531AH1-263 GEN
50/50
60.361
971281AH1-106 GEN
Solar/Wind Harmer
4.705
3143316POE
Solar/Wind Harmer
-0.107
970533AG2-339 GEN
Solar/Wind Harmer
18.235
316236AE1-162_GEN
Solar/Wind Harmer
0.809
970657AG2-426 GEN
Solar/Wind Harmer
1.694
316382AG1-145 C
Solar/Wind Harmer
0.8
316159AE1-175 C
Solar/Wind Harmer
0.712
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3143873LANEXA
Solar/Wind Harmer
-0.015
316405AF2-144 C
Solar/Wind Harmer
0.655
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3141873WAN 176
Solar/Wind Harmer
-0.005
3138133OCRAN
Solar/Wind Harmer
-0.007
970581AG2-369 GEN
Solar/Wind Harmer
13.353
972213AH1-691 GEN
Adder
4.768
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315733AD1-074 GEN2
Solar/Wind Harmer
4.927
970601AG2-382 GEN
Solar/Wind Harmer
10.582
946281AF1-292 GEN
Solar/Wind Harmer
0.534
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.406
3152261N ANNA2
50/50
19.702
3150861SPRUNCD
50/50
1.215
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.057
3147666LOUISA
Solar/Wind Harmer
-0.07
316458AB2-190 GEN2
Solar/Wind Harmer
2.725
3144873MCLAUGH
Solar/Wind Harmer
-0.001
961611AG1-000B GEN
Solar/Wind Harmer
5.667
3151171GRAVELC
Adder
3.347
970657AG2-426 GEN
Solar/Wind Harmer
5.428
316246AF1-032 C
Solar/Wind Harmer
0.537
316321Z2-027
Solar/Wind Harmer
0.707
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3141843SHACKLE
Adder
1.16
3141873WAN 176
Solar/Wind Harmer
3.007
970917AG2-570 GEN
Solar/Wind Harmer
62.912
3150401LDYSMT4
Adder
29.362
3156081AA2-088 GEN
Solar/Wind Harmer
7.933
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3145933PARMELE
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.079
971775AH1-396 GEN
Solar/Wind Harmer
1.52
3146926FARMVIL
Solar/Wind Harmer
-0.013
3146233WITAKRS
Solar/Wind Harmer
0.446
3146233WITAKRS
Solar/Wind Harmer
-0.014
3150801HOPHCF4
50/50
1.422
944601AF1-125 GEN
Solar/Wind Harmer
120.85
315778AD1-151 GEN
Solar/Wind Harmer
24.016
3151101ELIZAR3
Adder
22.264
3144216WINCHST
Adder
0.895
316075AC2-137 C
Solar/Wind Harmer
0.718
3143336POWHATN
Solar/Wind Harmer
2.587
316484AD2-074 GEN
Solar/Wind Harmer
6.055
966621AG1-532 GEN
Solar/Wind Harmer
0.483
316317KELFORD C
Solar/Wind Harmer
1.077
3145823KELFORD
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
316077AC2-138 C
Solar/Wind Harmer
0.484
3150351NORNECKC2
Adder
2.073
316212AC1-099_GEN
Solar/Wind Harmer
1.955
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
315722AD1-056 GEN
Solar/Wind Harmer
7.781
964241AG1-285 GEN
Solar/Wind Harmer
16.865
3144293JTRSVLE
Adder
0.457
942461AE2-259 GEN
Solar/Wind Harmer
3.219
3151761LOISA E
Adder
22.171
3151721LOISA A
Adder
10.819
3141196NOKESVL
Solar/Wind Helper
1.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.552
LGEELTFEXP_LGEE->PJM
CLTF
1.281
MECLTFEXP_MEC->PJM
CLTF
3.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.986
NYPJM->LTFIMP_NY
CLTF
3.442
TVALTFEXP_TVA->PJM
CLTF
4.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.265
CPLELTFEXP_CPLE->PJM
CLTF
12.057
SIGELTFEXP_SIGE->PJM
CLTF
0.107
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.014
WECLTFEXP_WEC->PJM
CLTF
0.611
LAGNLTFEXP_LAGN->PJM
CLTF
8.173
CONTINGENCY 'DVP_P4-2: 545T594_SRT-S'
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: 515T594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314934 TO BUS 314944 CKT 1                /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 OPEN BUS 314944                                                /*8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T573_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H3T552_SRT-S'
 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 2                /*6BRISTER     230.0 - 8BRISTER     500.0
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019F_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1          /*BRIGHTON     500.0 - 01DOUBS      500.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 2          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 4          /*01DOUBS      500.0 - 01DOUBS      230.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 1                  /*01DOUBS      500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
END
314905 to 314900 ckt 1
314911 to 314922 ckt 1
314922 to 200019 ckt 1
314934 to 314916 ckt 1

Winter Peak Analysis

The New Service Request AH1-263 was evaluated as a 200.0 MW (200.0 MW Capacity) injection in the Dominion area.

AH1-263 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (200.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-263 was evaluated as a 200.0 MW injection and 200.0 MW withdrawal in the Dominion area.

AH1-263 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (200.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC173.68 %1180.0B2049.45
23.67
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC173.67 %1180.0B2049.35
23.67
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-L
BreakerAC173.35 %1180.0B2045.56
23.68
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC171.54 %1180.0B2024.13
23.67
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
22.36
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
22.36
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC136.83 %1180.0B1614.63
22.36
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
BusAC110.97 %1180.0B1309.48
21.0
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17030___SRT-A
TowerAC110.49 %1180.0B1303.74
20.39
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17029___SRT-A
TowerAC110.3 %1180.0B1301.52
20.39
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
BusAC109.1 %1180.0B1287.39
20.25

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.68 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.45
MW Contribution:
23.67
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.581
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.418
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.519
316303AF2-085
50/50
Charging
2.243
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.49
316405AF2-144 C
50/50
Charging
1.174
316404AE1-155 C
Solar/Wind Helper
3.563
316203AE2-005 GEN
Solar/Wind Helper
3.616
316441AF1-014 GEN
Solar/Wind Helper
0.553
315616AA1-038_C
Solar/Wind Helper
1.957
316312AB1-027
Solar/Wind Helper
0.748
315651AD1-115 GEN
Solar/Wind Helper
4.201
315821AE2-092 GEN
Solar/Wind Helper
3.827
315662AE1-191 GEN
Solar/Wind Helper
2.22
315666AE1-190 GEN
Solar/Wind Helper
0.555
316280AD1-041 GEN
Solar/Wind Helper
1.388
316473AC1-191 GEN
Solar/Wind Helper
2.427
316447AC1-158 HLD
Solar/Wind Helper
5.08
316044AC1-158 PL1
Solar/Wind Helper
2.309
316045AC1-158 PL2
Solar/Wind Helper
7.388
316450AC1-158 RIC
Solar/Wind Helper
0.616
316468AD1-105 GEN
Solar/Wind Helper
2.225
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.563
316313AB2-026
Solar/Wind Helper
0.577
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
270583AD2-179 GEN
Solar/Wind Harmer
12.447
270494AE1-108_GEN
Solar/Wind Helper
5.579
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270030AE2-140 GEN
Solar/Wind Harmer
17.484
270069AE2-166 C O1
Solar/Wind Harmer
8.427
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.765
316164AC1-076 GEN
Solar/Wind Helper
1.94
316223AC1-118
Solar/Wind Helper
0.567
315975AC1-164 GENB
Solar/Wind Helper
0.061
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.709
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.856
960911AF2-382 GEN
Solar/Wind Harmer
6.617
961951AG1-038 GEN
Solar/Wind Helper
1.258
963031AG1-152 GEN
50/50
Charging
10.85
966871AG1-558 GEN
Solar/Wind Helper
0.436
966881AG1-559 GEN
Solar/Wind Helper
0.447
970119AG2-088 GEN
50/50
Charging
16.823
970281AG2-184 GEN
Solar/Wind Harmer
15.747
970417AG2-272 GEN
50/50
8.428
970563AG2-360 GEN
50/50
45.019
970823AG2-518 GEN
50/50
19.371
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971277AH1-098 GEN
Solar/Wind Harmer
4.144
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971507AH1-251 GEN
50/50
Charging
5.863
971531AH1-263 GEN
50/50
Charging
23.667
971543AH1-269 GEN
50/50
11.498
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.655
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.971
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.423
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971981AH1-535 GEN
Solar/Wind Harmer
6.611
971981AH1-535 GEN
Solar/Wind Harmer
7.212
972103AH1-617 GEN
Solar/Wind Harmer
14.997
972273AH1-721 GEN
50/50
85.07
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.246
971881AH1-461 GEN
50/50
14.324
972293SS25-0014
50/50
Charging
57.012
316487AF1-042 GEN
Solar/Wind Helper
1.165
316484AD2-074 GEN
Solar/Wind Helper
2.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.179
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.67 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.35
MW Contribution:
23.67
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.581
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.418
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.519
316303AF2-085
50/50
Charging
2.243
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.49
316405AF2-144 C
50/50
Charging
1.175
316404AE1-155 C
Solar/Wind Helper
3.563
316203AE2-005 GEN
Solar/Wind Helper
3.616
316441AF1-014 GEN
Solar/Wind Helper
0.554
315616AA1-038_C
Solar/Wind Helper
1.962
316312AB1-027
Solar/Wind Helper
0.748
315651AD1-115 GEN
Solar/Wind Helper
4.201
315821AE2-092 GEN
Solar/Wind Helper
3.827
315662AE1-191 GEN
Solar/Wind Helper
2.22
315666AE1-190 GEN
Solar/Wind Helper
0.555
316280AD1-041 GEN
Solar/Wind Helper
1.388
316473AC1-191 GEN
Solar/Wind Helper
2.427
316447AC1-158 HLD
Solar/Wind Helper
5.08
316044AC1-158 PL1
Solar/Wind Helper
2.309
316045AC1-158 PL2
Solar/Wind Helper
7.388
316450AC1-158 RIC
Solar/Wind Helper
0.616
316468AD1-105 GEN
Solar/Wind Helper
2.225
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.563
316313AB2-026
Solar/Wind Helper
0.577
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
270583AD2-179 GEN
Solar/Wind Harmer
12.447
270494AE1-108_GEN
Solar/Wind Helper
5.58
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270030AE2-140 GEN
Solar/Wind Harmer
17.484
270069AE2-166 C O1
Solar/Wind Harmer
8.427
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.765
316164AC1-076 GEN
Solar/Wind Helper
1.94
316223AC1-118
Solar/Wind Helper
0.567
315975AC1-164 GENB
Solar/Wind Helper
0.061
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.709
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.856
960911AF2-382 GEN
Solar/Wind Harmer
6.617
961951AG1-038 GEN
Solar/Wind Helper
1.258
963031AG1-152 GEN
50/50
Charging
10.85
966871AG1-558 GEN
Solar/Wind Helper
0.436
966881AG1-559 GEN
Solar/Wind Helper
0.447
970119AG2-088 GEN
50/50
Charging
16.824
970281AG2-184 GEN
Solar/Wind Harmer
15.747
970417AG2-272 GEN
50/50
8.428
970563AG2-360 GEN
50/50
45.019
970823AG2-518 GEN
50/50
19.371
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971277AH1-098 GEN
Solar/Wind Harmer
4.144
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971507AH1-251 GEN
50/50
Charging
5.863
971531AH1-263 GEN
50/50
Charging
23.667
971543AH1-269 GEN
50/50
11.498
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.655
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.971
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.423
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971981AH1-535 GEN
Solar/Wind Harmer
6.611
971981AH1-535 GEN
Solar/Wind Harmer
7.212
972103AH1-617 GEN
Solar/Wind Harmer
14.997
972273AH1-721 GEN
50/50
85.07
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.246
971881AH1-461 GEN
50/50
14.324
972293SS25-0014
50/50
Charging
57.012
316487AF1-042 GEN
Solar/Wind Helper
1.165
316484AD2-074 GEN
Solar/Wind Helper
2.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.178
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2045.56
MW Contribution:
23.68
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.582
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.419
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.52
316303AF2-085
50/50
Charging
2.246
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.491
316405AF2-144 C
50/50
Charging
1.177
316404AE1-155 C
Solar/Wind Helper
3.567
316203AE2-005 GEN
Solar/Wind Helper
3.62
316441AF1-014 GEN
Solar/Wind Helper
0.554
315616AA1-038_C
Solar/Wind Helper
2.018
316312AB1-027
Solar/Wind Helper
0.748
315651AD1-115 GEN
Solar/Wind Helper
4.205
315821AE2-092 GEN
Solar/Wind Helper
3.841
315662AE1-191 GEN
Solar/Wind Helper
2.223
315666AE1-190 GEN
Solar/Wind Helper
0.556
316280AD1-041 GEN
Solar/Wind Helper
1.389
316473AC1-191 GEN
Solar/Wind Helper
2.43
316447AC1-158 HLD
Solar/Wind Helper
5.083
316044AC1-158 PL1
Solar/Wind Helper
2.31
316045AC1-158 PL2
Solar/Wind Helper
7.393
316450AC1-158 RIC
Solar/Wind Helper
0.616
316468AD1-105 GEN
Solar/Wind Helper
2.227
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.564
316313AB2-026
Solar/Wind Helper
0.578
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
270583AD2-179 GEN
Solar/Wind Harmer
12.446
270494AE1-108_GEN
Solar/Wind Helper
5.59
270346AE1-212 GEN
Solar/Wind Harmer
8.185
270030AE2-140 GEN
Solar/Wind Harmer
17.478
270069AE2-166 C O1
Solar/Wind Harmer
8.425
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.769
316164AC1-076 GEN
Solar/Wind Helper
1.941
316223AC1-118
Solar/Wind Helper
0.568
315975AC1-164 GENB
Solar/Wind Helper
0.061
315976AC1-164 GENA
Solar/Wind Helper
2.057
316169AC1-164_GENC
Solar/Wind Helper
1.777
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.708
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.859
960911AF2-382 GEN
Solar/Wind Harmer
6.616
961951AG1-038 GEN
Solar/Wind Helper
1.26
963031AG1-152 GEN
50/50
Charging
10.856
966871AG1-558 GEN
Solar/Wind Helper
0.437
966881AG1-559 GEN
Solar/Wind Helper
0.447
970119AG2-088 GEN
50/50
Charging
16.846
970281AG2-184 GEN
Solar/Wind Harmer
15.746
970417AG2-272 GEN
50/50
8.425
970563AG2-360 GEN
50/50
45.014
970823AG2-518 GEN
50/50
19.368
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971277AH1-098 GEN
Solar/Wind Harmer
4.143
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.832
971331AH1-145 GEN
Solar/Wind Harmer
17.214
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.168
971507AH1-251 GEN
50/50
Charging
5.867
971531AH1-263 GEN
50/50
Charging
23.682
971543AH1-269 GEN
50/50
11.496
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.663
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.972
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.424
966391AG1-508 GEN
Solar/Wind Harmer
10.237
971981AH1-535 GEN
Solar/Wind Harmer
6.61
971981AH1-535 GEN
Solar/Wind Harmer
7.211
972103AH1-617 GEN
Solar/Wind Harmer
14.996
972273AH1-721 GEN
50/50
85.068
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.247
971881AH1-461 GEN
50/50
14.323
972293SS25-0014
50/50
Charging
57.048
316487AF1-042 GEN
Solar/Wind Helper
1.167
316484AD2-074 GEN
Solar/Wind Helper
2.229
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.017
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.652
NYPJM->LTFIMP_NY
CLTF
2.177
LGEELTFEXP_LGEE->PJM
CLTF
5.764
WECLTFEXP_WEC->PJM
CLTF
2.895
CPLELTFEXP_CPLE->PJM
CLTF
4.745
TVALTFEXP_TVA->PJM
CLTF
9.524
MECLTFEXP_MEC->PJM
CLTF
13.347
LAGNLTFEXP_LAGN->PJM
CLTF
17.991
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.478
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2024.13
MW Contribution:
23.67
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.581
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.418
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.519
316303AF2-085
50/50
Charging
2.243
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
50/50
Charging
1.174
316404AE1-155 C
Solar/Wind Helper
3.563
316203AE2-005 GEN
Solar/Wind Helper
3.616
316441AF1-014 GEN
Solar/Wind Helper
0.553
315616AA1-038_C
Solar/Wind Helper
1.957
315651AD1-115 GEN
Solar/Wind Helper
4.201
315821AE2-092 GEN
Solar/Wind Helper
3.827
315662AE1-191 GEN
Solar/Wind Helper
2.22
315666AE1-190 GEN
Solar/Wind Helper
0.555
316280AD1-041 GEN
Solar/Wind Helper
1.388
316473AC1-191 GEN
Solar/Wind Helper
2.427
316468AD1-105 GEN
Solar/Wind Helper
2.225
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.563
316313AB2-026
Solar/Wind Helper
0.577
270399AC1-101 GEN
Solar/Wind Harmer
3.469
270400AC1-102 GEN
Solar/Wind Harmer
3.469
270583AD2-179 GEN
Solar/Wind Harmer
12.447
270494AE1-108_GEN
Solar/Wind Helper
5.579
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270030AE2-140 GEN
Solar/Wind Harmer
17.484
270069AE2-166 C O1
Solar/Wind Harmer
8.427
270053AF1-130 C
Solar/Wind Harmer
12.797
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.765
316164AC1-076 GEN
Solar/Wind Helper
1.94
316223AC1-118
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.709
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.856
944971AF1-162 GEN
Solar/Wind Harmer
2.093
960911AF2-382 GEN
Solar/Wind Harmer
6.617
961951AG1-038 GEN
Solar/Wind Helper
1.258
963031AG1-152 GEN
50/50
Charging
10.85
970119AG2-088 GEN
50/50
Charging
16.823
970281AG2-184 GEN
Solar/Wind Harmer
15.747
970417AG2-272 GEN
50/50
8.428
970563AG2-360 GEN
50/50
45.019
970823AG2-518 GEN
50/50
19.371
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971507AH1-251 GEN
50/50
Charging
5.863
971531AH1-263 GEN
50/50
Charging
23.667
971543AH1-269 GEN
50/50
11.498
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.655
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.971
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.423
966391AG1-508 GEN
Solar/Wind Harmer
10.239
972103AH1-617 GEN
Solar/Wind Harmer
14.997
972273AH1-721 GEN
50/50
85.07
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.246
971881AH1-461 GEN
50/50
14.324
972293SS25-0014
50/50
Charging
57.012
316487AF1-042 GEN
Solar/Wind Helper
1.165
316484AD2-074 GEN
Solar/Wind Helper
2.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.179
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
22.36
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316312AB1-027
Solar/Wind Helper
0.693
316473AC1-191 GEN
Solar/Wind Helper
2.25
316447AC1-158 HLD
Solar/Wind Helper
4.798
316044AC1-158 PL1
Solar/Wind Helper
2.181
316045AC1-158 PL2
Solar/Wind Helper
6.979
316450AC1-158 RIC
Solar/Wind Helper
0.582
316468AD1-105 GEN
Solar/Wind Helper
2.079
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270583AD2-179 GEN
Solar/Wind Harmer
9.358
270494AE1-108_GEN
Solar/Wind Helper
4.816
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270053AF1-130 C
Solar/Wind Harmer
11.711
316006AB2-029 C
Solar/Wind Helper
0.504
316164AC1-076 GEN
Solar/Wind Helper
1.745
943031AE2-326 GEN
Solar/Wind Harmer
9.448
944491AF1-114 GEN
Solar/Wind Helper
2.702
944971AF1-162 GEN
Solar/Wind Harmer
10.409
960911AF2-382 GEN
Solar/Wind Harmer
5.69
963031AG1-152 GEN
50/50
Charging
10.244
966871AG1-558 GEN
Solar/Wind Helper
0.404
966881AG1-559 GEN
Solar/Wind Helper
0.418
970281AG2-184 GEN
Solar/Wind Harmer
14.006
970417AG2-272 GEN
50/50
6.326
970563AG2-360 GEN
50/50
37.854
970823AG2-518 GEN
50/50
14.083
970913AG2-568 GEN
Solar/Wind Harmer
5.207
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971277AH1-098 GEN
Solar/Wind Harmer
3.312
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971331AH1-145 GEN
Solar/Wind Harmer
13.165
971403AH1-188 GEN
Solar/Wind Harmer
9.621
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971507AH1-251 GEN
50/50
Charging
5.466
971531AH1-263 GEN
50/50
Charging
22.363
971543AH1-269 GEN
50/50
8.594
971687AH1-348 GEN
Solar/Wind Harmer
0.705
941621AE2-160 GEN
50/50
5.904
957191AF2-013 GEN
50/50
Charging
10.139
957971AF2-091 GEN
Solar/Wind Helper
0.919
966391AG1-508 GEN
Solar/Wind Harmer
8.202
972103AH1-617 GEN
Solar/Wind Harmer
13.339
972273AH1-721 GEN
50/50
76.948
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.154
971881AH1-461 GEN
50/50
11.944
972293SS25-0014
50/50
Charging
53.849
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
22.36
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316312AB1-027
Solar/Wind Helper
0.693
316473AC1-191 GEN
Solar/Wind Helper
2.25
316447AC1-158 HLD
Solar/Wind Helper
4.798
316044AC1-158 PL1
Solar/Wind Helper
2.181
316045AC1-158 PL2
Solar/Wind Helper
6.979
316450AC1-158 RIC
Solar/Wind Helper
0.582
316468AD1-105 GEN
Solar/Wind Helper
2.079
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270583AD2-179 GEN
Solar/Wind Harmer
9.358
270494AE1-108_GEN
Solar/Wind Helper
4.816
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270053AF1-130 C
Solar/Wind Harmer
11.711
316006AB2-029 C
Solar/Wind Helper
0.504
316164AC1-076 GEN
Solar/Wind Helper
1.745
943031AE2-326 GEN
Solar/Wind Harmer
9.448
944491AF1-114 GEN
Solar/Wind Helper
2.702
944971AF1-162 GEN
Solar/Wind Harmer
10.409
960911AF2-382 GEN
Solar/Wind Harmer
5.69
963031AG1-152 GEN
50/50
Charging
10.244
966871AG1-558 GEN
Solar/Wind Helper
0.404
966881AG1-559 GEN
Solar/Wind Helper
0.418
970281AG2-184 GEN
Solar/Wind Harmer
14.006
970417AG2-272 GEN
50/50
6.326
970563AG2-360 GEN
50/50
37.854
970823AG2-518 GEN
50/50
14.083
970913AG2-568 GEN
Solar/Wind Harmer
5.207
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971277AH1-098 GEN
Solar/Wind Harmer
3.312
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971331AH1-145 GEN
Solar/Wind Harmer
13.165
971403AH1-188 GEN
Solar/Wind Harmer
9.621
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971507AH1-251 GEN
50/50
Charging
5.466
971531AH1-263 GEN
50/50
Charging
22.363
971543AH1-269 GEN
50/50
8.594
971687AH1-348 GEN
Solar/Wind Harmer
0.705
941621AE2-160 GEN
50/50
5.904
957191AF2-013 GEN
50/50
Charging
10.139
957971AF2-091 GEN
Solar/Wind Helper
0.919
966391AG1-508 GEN
Solar/Wind Harmer
8.202
972103AH1-617 GEN
Solar/Wind Harmer
13.339
972273AH1-721 GEN
50/50
76.948
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.154
971881AH1-461 GEN
50/50
11.944
972293SS25-0014
50/50
Charging
53.849
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.83 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1614.63
MW Contribution:
22.36
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316473AC1-191 GEN
Solar/Wind Helper
2.25
316468AD1-105 GEN
Solar/Wind Helper
2.079
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270583AD2-179 GEN
Solar/Wind Harmer
9.358
270494AE1-108_GEN
Solar/Wind Helper
4.816
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270030AE2-140 GEN
Solar/Wind Harmer
3.161
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270053AF1-130 C
Solar/Wind Harmer
11.711
316006AB2-029 C
Solar/Wind Helper
0.504
316164AC1-076 GEN
Solar/Wind Helper
1.745
943031AE2-326 GEN
Solar/Wind Harmer
9.448
944491AF1-114 GEN
Solar/Wind Helper
2.702
944971AF1-162 GEN
Solar/Wind Harmer
12.03
960911AF2-382 GEN
Solar/Wind Harmer
5.69
963031AG1-152 GEN
50/50
Charging
10.244
970281AG2-184 GEN
Solar/Wind Harmer
14.006
970417AG2-272 GEN
50/50
6.326
970563AG2-360 GEN
50/50
37.854
970823AG2-518 GEN
50/50
14.083
970913AG2-568 GEN
Solar/Wind Harmer
5.207
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971331AH1-145 GEN
Solar/Wind Harmer
13.165
971403AH1-188 GEN
Solar/Wind Harmer
9.621
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971507AH1-251 GEN
50/50
Charging
5.466
971531AH1-263 GEN
50/50
Charging
22.363
971543AH1-269 GEN
50/50
8.594
971687AH1-348 GEN
Solar/Wind Harmer
0.705
941621AE2-160 GEN
50/50
5.904
957191AF2-013 GEN
50/50
Charging
10.139
957971AF2-091 GEN
Solar/Wind Helper
0.919
966391AG1-508 GEN
Solar/Wind Harmer
8.202
972103AH1-617 GEN
Solar/Wind Harmer
13.339
972273AH1-721 GEN
50/50
76.948
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.154
971881AH1-461 GEN
50/50
11.944
972293SS25-0014
50/50
Charging
53.849
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.97 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1309.48
MW Contribution:
21.0
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3147123OTTER R
Solar/Wind Harmer
0.188
3147312GRETNA
Solar/Wind Harmer
0.273
3147312GRETNA
Solar/Wind Harmer
0.068
3146802CHATHAM
Solar/Wind Harmer
0.256
316447AC1-158 HLD
Solar/Wind Helper
4.5
316044AC1-158 PL1
Solar/Wind Helper
2.046
316045AC1-158 PL2
Solar/Wind Helper
6.545
316450AC1-158 RIC
Solar/Wind Helper
0.545
270583AD2-179 GEN
Solar/Wind Harmer
9.646
270346AE1-212 GEN
Solar/Wind Harmer
6.338
270030AE2-140 GEN
Solar/Wind Harmer
14.894
270069AE2-166 C O1
Solar/Wind Harmer
7.142
942671AE2-283 GEN
Solar/Wind Harmer
3.623
943031AE2-326 GEN
Solar/Wind Harmer
9.019
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.121
962751AG1-124 GEN
Solar/Wind Harmer
6.233
966881AG1-559 GEN
Solar/Wind Helper
0.39
970281AG2-184 GEN
Solar/Wind Harmer
11.543
970417AG2-272 GEN
50/50
7.231
970563AG2-360 GEN
50/50
34.767
970823AG2-518 GEN
50/50
14.96
970913AG2-568 GEN
Solar/Wind Harmer
4.573
971225AH1-072 GEN
Solar/Wind Harmer
1.261
971227AH1-073 GEN
Solar/Wind Harmer
1.261
971277AH1-098 GEN
Solar/Wind Harmer
3.537
971277AH1-098 GEN
Solar/Wind Harmer
3.215
971313AH1-133 GEN
Solar/Wind Harmer
4.952
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971331AH1-145 GEN
Solar/Wind Harmer
13.329
971403AH1-188 GEN
Solar/Wind Harmer
8.261
971461AH1-227 GEN
Solar/Wind Harmer
3.235
971507AH1-251 GEN
50/50
Charging
5.111
971531AH1-263 GEN
50/50
Charging
20.999
971543AH1-269 GEN
50/50
8.911
971687AH1-348 GEN
Solar/Wind Harmer
0.626
941621AE2-160 GEN
50/50
5.119
941801AE2-185 GEN
Solar/Wind Harmer
4.102
966391AG1-508 GEN
Solar/Wind Harmer
7.933
971981AH1-535 GEN
Solar/Wind Harmer
5.175
971981AH1-535 GEN
Solar/Wind Harmer
5.645
958121AF2-106 GEN
Solar/Wind Harmer
0
961131AF2-404 GEN
Solar/Wind Harmer
2.357
971881AH1-461 GEN
50/50
11.072
972293SS25-0014
50/50
Charging
50.508
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.09
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.61
NYPJM->LTFIMP_NY
CLTF
1.786
LGEELTFEXP_LGEE->PJM
CLTF
4.54
WECLTFEXP_WEC->PJM
CLTF
2.293
CPLELTFEXP_CPLE->PJM
CLTF
4.184
TVALTFEXP_TVA->PJM
CLTF
7.544
MECLTFEXP_MEC->PJM
CLTF
10.573
LAGNLTFEXP_LAGN->PJM
CLTF
14.289
SIGELTFEXP_SIGE->PJM
CLTF
0.346
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
19.204
AG2-052LTFEXP_AG2-052->PJM
LTF
0.137
AH1-155LTFEXP_AH1-155->PJM
LTF
0.206

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17030___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17030___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1303.74
MW Contribution:
20.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Helper
4.364
316044AC1-158 PL1
Solar/Wind Helper
1.983
316045AC1-158 PL2
Solar/Wind Helper
6.347
316450AC1-158 RIC
Solar/Wind Helper
0.529
270399AC1-101 GEN
Solar/Wind Harmer
1.329
270400AC1-102 GEN
Solar/Wind Harmer
1.329
270173AC1-122 GEN
Solar/Wind Helper
2.76
270583AD2-179 GEN
Solar/Wind Harmer
9.612
270494AE1-108_GEN
Solar/Wind Helper
5.948
270346AE1-212 GEN
Solar/Wind Harmer
6.395
270030AE2-140 GEN
Solar/Wind Harmer
12.927
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
316217AC1-145 GEN
Solar/Wind Helper
1.974
943031AE2-326 GEN
Solar/Wind Harmer
9.122
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.18
970281AG2-184 GEN
Solar/Wind Harmer
12.374
970417AG2-272 GEN
50/50
6.193
970563AG2-360 GEN
50/50
35.173
970823AG2-518 GEN
50/50
14.895
970913AG2-568 GEN
Solar/Wind Harmer
4.649
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971277AH1-098 GEN
Solar/Wind Harmer
3.223
971313AH1-133 GEN
Solar/Wind Harmer
5.006
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971403AH1-188 GEN
Solar/Wind Harmer
8.401
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971531AH1-263 GEN
50/50
Charging
20.391
971543AH1-269 GEN
50/50
8.871
971687AH1-348 GEN
Solar/Wind Harmer
0.633
941621AE2-160 GEN
50/50
5.212
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971981AH1-535 GEN
Solar/Wind Harmer
5.117
971981AH1-535 GEN
Solar/Wind Harmer
5.582
972103AH1-617 GEN
Solar/Wind Harmer
11.785
958121AF2-106 GEN
Solar/Wind Harmer
0
961131AF2-404 GEN
50/50
Charging
2.924
971881AH1-461 GEN
50/50
11.185
972293SS25-0014
50/50
Charging
48.973
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
NYPJM->LTFIMP_NY
CLTF
1.631
LGEELTFEXP_LGEE->PJM
CLTF
4.594
WECLTFEXP_WEC->PJM
CLTF
2.32
CPLELTFEXP_CPLE->PJM
CLTF
3.013
TVALTFEXP_TVA->PJM
CLTF
7.367
MECLTFEXP_MEC->PJM
CLTF
10.609
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
SIGELTFEXP_SIGE->PJM
CLTF
0.348
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17029___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17029___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.3 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1301.52
MW Contribution:
20.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Helper
4.364
316044AC1-158 PL1
Solar/Wind Helper
1.983
316045AC1-158 PL2
Solar/Wind Helper
6.347
316450AC1-158 RIC
Solar/Wind Helper
0.529
270399AC1-101 GEN
Solar/Wind Harmer
1.329
270400AC1-102 GEN
Solar/Wind Harmer
1.329
270173AC1-122 GEN
Solar/Wind Helper
2.76
270583AD2-179 GEN
Solar/Wind Harmer
9.612
270494AE1-108_GEN
Solar/Wind Helper
5.948
270346AE1-212 GEN
Solar/Wind Harmer
6.395
270030AE2-140 GEN
Solar/Wind Harmer
12.927
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
316217AC1-145 GEN
Solar/Wind Helper
1.974
943031AE2-326 GEN
Solar/Wind Harmer
9.122
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.18
970281AG2-184 GEN
Solar/Wind Harmer
12.374
970417AG2-272 GEN
50/50
6.193
970563AG2-360 GEN
50/50
35.173
970823AG2-518 GEN
50/50
14.895
970913AG2-568 GEN
Solar/Wind Harmer
4.649
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971277AH1-098 GEN
Solar/Wind Harmer
3.223
971313AH1-133 GEN
Solar/Wind Harmer
5.006
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971403AH1-188 GEN
Solar/Wind Harmer
8.401
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971531AH1-263 GEN
50/50
Charging
20.391
971543AH1-269 GEN
50/50
8.871
971687AH1-348 GEN
Solar/Wind Harmer
0.633
941621AE2-160 GEN
50/50
5.212
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971981AH1-535 GEN
Solar/Wind Harmer
5.117
971981AH1-535 GEN
Solar/Wind Harmer
5.582
972103AH1-617 GEN
Solar/Wind Harmer
11.785
958121AF2-106 GEN
Solar/Wind Harmer
0
961131AF2-404 GEN
50/50
Charging
2.924
971881AH1-461 GEN
50/50
11.185
972293SS25-0014
50/50
Charging
48.973
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
NYPJM->LTFIMP_NY
CLTF
1.631
LGEELTFEXP_LGEE->PJM
CLTF
4.594
WECLTFEXP_WEC->PJM
CLTF
2.32
CPLELTFEXP_CPLE->PJM
CLTF
3.013
TVALTFEXP_TVA->PJM
CLTF
7.367
MECLTFEXP_MEC->PJM
CLTF
10.609
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
SIGELTFEXP_SIGE->PJM
CLTF
0.348
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1287.39
MW Contribution:
20.25
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Helper
4.334
316044AC1-158 PL1
Solar/Wind Helper
1.97
316045AC1-158 PL2
Solar/Wind Helper
6.303
316450AC1-158 RIC
Solar/Wind Helper
0.525
270399AC1-101 GEN
Solar/Wind Harmer
1.311
270400AC1-102 GEN
Solar/Wind Harmer
1.311
270173AC1-122 GEN
Solar/Wind Helper
2.227
270583AD2-179 GEN
Solar/Wind Harmer
9.325
270494AE1-108_GEN
Solar/Wind Helper
4.907
270346AE1-212 GEN
Solar/Wind Harmer
6.24
270030AE2-140 GEN
Solar/Wind Harmer
12.937
270069AE2-166 C O1
Solar/Wind Harmer
6.298
943031AE2-326 GEN
Solar/Wind Harmer
9.004
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.113
970281AG2-184 GEN
Solar/Wind Harmer
12.222
970417AG2-272 GEN
50/50
6.208
970563AG2-360 GEN
50/50
34.746
970823AG2-518 GEN
50/50
14.377
970913AG2-568 GEN
Solar/Wind Harmer
4.564
971225AH1-072 GEN
Solar/Wind Harmer
1.258
971227AH1-073 GEN
Solar/Wind Harmer
1.258
971277AH1-098 GEN
Solar/Wind Harmer
3.493
971277AH1-098 GEN
Solar/Wind Harmer
3.175
971313AH1-133 GEN
Solar/Wind Harmer
4.935
971329AH1-144 GEN
Solar/Wind Harmer
5.883
971331AH1-145 GEN
Solar/Wind Harmer
12.93
971403AH1-188 GEN
Solar/Wind Harmer
8.284
971461AH1-227 GEN
Solar/Wind Harmer
3.227
971531AH1-263 GEN
50/50
Charging
20.247
971543AH1-269 GEN
50/50
8.605
971687AH1-348 GEN
Solar/Wind Harmer
0.625
941621AE2-160 GEN
50/50
5.101
966391AG1-508 GEN
Solar/Wind Harmer
7.844
971981AH1-535 GEN
Solar/Wind Harmer
5.078
971981AH1-535 GEN
Solar/Wind Harmer
5.54
972103AH1-617 GEN
Solar/Wind Harmer
11.64
958121AF2-106 GEN
Solar/Wind Harmer
0
971881AH1-461 GEN
50/50
11.002
972293SS25-0014
50/50
Charging
48.638
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.36
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.018
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.535
NYPJM->LTFIMP_NY
CLTF
1.636
LGEELTFEXP_LGEE->PJM
CLTF
4.537
WECLTFEXP_WEC->PJM
CLTF
2.291
CPLELTFEXP_CPLE->PJM
CLTF
3.149
TVALTFEXP_TVA->PJM
CLTF
7.32
MECLTFEXP_MEC->PJM
CLTF
10.492
LAGNLTFEXP_LAGN->PJM
CLTF
13.848
SIGELTFEXP_SIGE->PJM
CLTF
0.344
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.744
AG2-052LTFEXP_AG2-052->PJM
LTF
0.138
AH1-155LTFEXP_AH1-155->PJM
LTF
0.207
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 547T566_SRT-L'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1                /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1                /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1                /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                                /*8LEXINGTN SC 500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 247669 CKT 1   /*05JOSHUA     765.0 - 05JOSHUA 1EQ   1.0
 OPEN BRANCH FROM BUS 242688 TO BUS 247670 CKT 1   /*05JOSHUA     138.0 - 05JOSHUA_XFL 138.0
 OPEN BRANCH FROM BUS 247669 TO BUS 247670 CKT 1   /*05JOSHUA 1EQ   1.0 - 05JOSHUA_XFL 138.0
END
CONTINGENCY 'AEP_P7-1_#17030___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
END
CONTINGENCY 'AEP_P7-1_#17029___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1   /*05MOSELEY    138.0 - 05REUSENS1   138.0
END
CONTINGENCY 'AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242561 TO BUS 242765 CKT 1    /*05BOONSBORO  138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242719 TO BUS 242765 CKT 1    /*05MONEL      138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1    /*05MOSELEY    138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242882 CKT 4    /*05REUSENS1   138.0 - 05REUSENS     69.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242889 CKT 1    /*05REUSENS1   138.0 - 05REUSENS     34.5
 OPEN BRANCH FROM BUS 242765 TO BUS 246229 CKT Z1   /*05REUSENS1   138.0 - 05REUSENS2   138.0
 REMOVE SWSHUNT FROM BUS 242765                     /*05REUSENS1   138.0
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 2 Cluster 15 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 15 projects.

 

Table 1: Transition Cycle 2 Cluster 15 Projects

 

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO (MW)

MWE (MW)

MWC (MW)

Point of Interconnection

15

AH1-251

Storage

Dominion

50

50

50

Todds Tavern – Spotsylvania 115 kV line

AH1-263

Storage

Dominion

200

200

200

Chancellor 115 kV substation

 

The purpose of the transient stability analysis is to determine the system impact of the generation facility. This study will determine system improvements, if any, needed to reduce violations in the transient stability analysis caused by the addition of the projects in Cluster 15.

 

The load flow scenario for the analysis was based on the Regional Transmission Expansion Plan (RTEP) 2028 summer peak case, modified to include applicable projects. Cluster 15 projects have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer.

 

Cluster 15 projects were tested for compliance with NERC, PJM, Dominion Energy and other applicable criteria. 83 contingencies were studied, each with a 20 second simulation time period. The contingencies studied included:

 

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults placed at 80% of the line with delayed clearing at remote line end because of primary communications/relaying failure
  • Single-phase faults with loss of multiple-circuit tower line.

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

The results of the analysis were evaluated against the following recovery criteria per PJM’s Regional Transmission Planning Process and Dominion Energy’s transmission planning criteria:

 

  • Cluster 15 projects were able to ride through the faults (except for faults where protective action trips a generator(s)).
  • The system with Cluster 15 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

No mitigation is required to connect projects in TC2 Cluster 15.

 

Note: AC1-158 generator tripped for over voltages above 1.31 p.u. The unit rode through when the pickup timer increased from 0.014 seconds to 0.017 seconds. Generation facility owner will need to verify ride through capability.

 

Reactive Power Analysis

The reactive power capability of AH1-263 met the 0.95 leading and lagging power factor requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-027Old Church 34.5 KVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-191Elmont 115kVEngineering & Procurement
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD2-030Wan 34.5 kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-179Morgans Cut-Glen Lyn 138kVWithdrawn
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-212Grandview-Clifftop 138 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AF1-014Harmony Village-Shackleford 115 kVSuspended
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-162Inez 138 kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-382Hurley 69 kVEngineering & Procurement
AF2-404Gladys DP-Stonemill 69 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-124Riverville - Gladstone 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-152Remington CT 230 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-508Point Lookout 69 kVWithdrawn
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-088Midlothian 230 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-240Old Church 34.5 kVActive
AG2-272Berry Hill 138 kVActive
AG2-360Broadford 138 kVActive
AG2-518Tech Drive 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-269Claytor 138 kVActive
AH1-348Pound 34.5 kVActive
AH1-461Buckhorn 138 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-721Laurel-Cooper 161 kVActive

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AH1-263 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
AEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
AEPb4000.251Replace the wave trap and upgrade the relay at Cloverdale 765kV substationContingent$0N/A
AEPb4000.252Replace the wave trap and upgrade the relay at Joshua Falls 765kV substationContingent$0N/A
Dominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Contingent$0N/A
Dominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Contingent$0N/A
Dominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Contingent$0N/A
Grand Total:$0

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-263 may not presently have cost responsibility for this upgrade, AH1-263 may need this upgrade in-service to be deliverable to the PJM system. If AH1-263 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.29
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4053.29
Title
Uprate 500 kV line No. 560 terminal equipment at Burches Hill substation in PEPCO so as not to limit the conductor rating.
Description
Uprate 500 kV line No. 560 terminal equipment at Burches Hill substation in PEPCO so as not to limit the conductor rating. The scope includes upgrading/replacing two circuit breakers, four switches and two different portions of stranded bus.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-263 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-263 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4087.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA4673.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
No overload on Dominion equipment for 8POSSUM - BURCHES (TC2)
Description
Dominion End Ratings Winter: 5414/5581/6107 Light Load: 5227/5388/5941 Summer: 4257/4388/5046
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA5227.0 MVA
LLB5388.0 MVA
LLC5941.0 MVA
SUMA4257.0 MVA
SUMB4388.0 MVA
SUMC5046.0 MVA
WINA5414.0 MVA
WINB5581.0 MVA
WINC6107.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-263


AH1-263 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Topology-0.0%Contingent$0
Load FlowAEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Topology-0.0%Contingent$0
Load FlowDominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Topology-0.0%Contingent$0
Load FlowDominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-263 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-263 One Line Diagram

AH1-263 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.