AH1-272 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:44

Argenta - Twin Branch 345 kV

123.9 MW Capacity / 185.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Bankson Solar Project, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is AEP Indiana Michigan Transmission Company, Inc..

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request meets the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposits refunded. See Readiness Deposit calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $63,157,840 $31,084,224 = 2.03 AND ( $63,157,840 - $31,084,224 ) 185.0 = $173,371 per MW

General

The Project Developer has proposed a Solar generating facility located in the AEP Indiana Michigan Transmission Company, Inc. zone — Van Buren County, Michigan. The installed facilities will have a total capability of 185.0 MW with 123.9 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-272
Project Name:
Argenta - Twin Branch 345 kV
Project Developer Name:
Bankson Solar Project, LLC
State:
Michigan
County:
Van Buren
Transmission Owner:
AEP Indiana Michigan Transmission Company, Inc.
MFO:
185.0
MWE:
185.0
MWC:
123.9
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-272 will interconnect on the American Electric Power transmission system by tapping the Argenta (MISO) - Twin Branch 345 kV line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-272 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-272Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$1,659,783$0$0
Other Scope$1,117,553$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$47,585,040$47,585,040$47,585,040
Network Upgrades$10,643,266$10,643,266$10,643,266
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$4,880,003$0$4,880,003
AFS - Non-PJM Violations$49,531$0$49,531
Total$65,935,176$58,228,306$63,157,840

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-272

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-272
Project ID: AH1-272
20% of cost allocation for Phase II Network Upgrades:(A) $11,645,661
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $3,108,422
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $8,537,239
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Removal of two 2 existing wavetraps at the Twin Branch 345 kV Station.

$30,105$6,477$31,749$6,831$75,162$75,162
(Pending)

Argenta – Twin Branch 345 kV line will be cut and looped into the new interconnection substation.

$4,563,837$3,760,706$1,270,358$973,203$10,568,104$10,568,104
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase coupling capacitor voltage transformers (CCVT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the AH1-272 New Station 345 kV Station.

$534,797$346,663$144,903$91,190$1,117,553$1,117,553
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

AEP Indiana Michigan Transmission Company Inc. will install 4 miles of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable. AEP Indiana Michigan Transmission Company Inc. will install 32 miles of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable. AEP Indiana Michigan Transmission Company Inc. will install 37 miles of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable.

$15,664,806$6,308,363$4,678,524$1,876,935$28,528,628$28,528,628
(Pending)

A new 345 kV breaker and a half substation, AH1-272, will be constructed along the Argenta - Twin Branch 345 kV transmission line to interconnect the project with the IMTCO transmission system. Installation of (3) 345KV RCVTs with (3) single-phase 345KV CCVT structures, foundations, and adapter steel. AEP Indiana Michigan Transmission Company Inc. will construct a new 345 kV breaker and a half station, to be operated as a three (3) circuit breaker ring bus, initially expandable to six (6) circuit breakers. This typical arrangement is planned to be designed to accommodate 5000A of continuous current. Installation of two (2) Fiber Protection panels at the AH1-272 New Station 345 kV Station. AEP Indiana Michigan Transmission Company Inc. will install one (1) new 8340 router at the AH1-272 New Station 345 kV Station.

$7,981,805$7,436,138$1,829,740$1,808,729$19,056,412$19,056,412
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

A 345 kV dead-end structure and foundation outside the fence of the Interconnection Substation, to terminate the Project Developer’s generator lead line. Line conductor from the dead-end structure to the bus position in the switchyard of the interconnection substation. The IMTCO Interconnection Facilities will include but are not limited to the following: • Installation of one (1) new steel, 120', single circuit, single pole dead end structure on a concrete pier foundation with an anchor bolt cage and one span of double bundle ACSR 954 (Cardinal) transmission line conductor with 7#8 Alumoweld shield wire for the generation lead circuit extending from the AH1-272 New Station 345 kV Station.

$737,022$584,658$188,540$149,563$1,659,783$1,659,783
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Removal of two 2 existing wavetraps at the Twin Branch 345 kV Station.

$30,105$6,477$31,749$6,831$75,162$75,162
(Pending)

Argenta – Twin Branch 345 kV line will be cut and looped into the new interconnection substation.

$4,563,837$3,760,706$1,270,358$973,203$10,568,104$10,568,104
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight of developer design and construction of new interconnection substation

$409,606$123,028$276,344$83,002$891,980$891,980
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase coupling capacitor voltage transformers (CCVT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the AH1-272 New Station 345 kV Station.

$534,797$346,663$144,903$91,190$1,117,553$1,117,553
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$61,005,642$61,005,642
Developer Build Option$12,652,799$12,652,799

Based on the scope of work for the Interconnection Facilities, it is expected to take 42 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Remote end work required on a Facility owned by a non-PJM Transmission Owner:

 

Please note that your project interconnects directly to an AEP (PJM Transmission Owner) facility which shares a tie line with MISO Transmission Owner, METC (non-PJM Transmission Owner). The Transmission Owner Scope of Work above outlines the interconnection facilities required on the AEP facilities. Your project will also require upgrades at the remote end METC (MISO) facility. PJM will coordinate this study with MISO and will include remote end facility report (if available) in Phase III System Impact Study report.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-272 was evaluated as a 185.0 MW (123.9 MW Capacity) injection in the AEP area.

AH1-272 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 185.0 MW (185.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-002_SRT-A
BreakerAC112.58 %1878.0B2114.26
12.85
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC215.53 %1180.0B2543.22
12.84
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC215.53 %1180.0B2543.22
12.84
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC215.53 %1180.0B2543.22
12.84
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC215.5 %1180.0B2542.96
12.84
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#2979_05DUMONT 765_B2_SRT-A
BreakerAC101.9 %5001.0B5096.22
26.73
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC104.04 %4142.0B4309.27
20.9
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC101.22 %4142.0B4192.73
17.76
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC100.26 %4142.0B4152.93
23.86
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC100.15 %4142.0B4148.28
23.86
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P4_#ADKINS AG1125_SRT-A_SENS
BreakerAC104.63 %4571.0B4782.69
25.44
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.48 %4571.0B4638.62
19.81
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#ADKINS AG1125_SRT-A_SENS
BreakerAC105.09 %4571.0B4803.57
25.44
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.94 %4571.0B4659.48
19.81
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#707_05MARYSV 765_B1_SRT-A_SENS
BreakerAC100.72 %4571.0B4604.1
25.44
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS
BreakerAC130.7 %4142.0B5413.79
30.94
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS
SingleAC120.92 %4142.0B5008.41
24.09
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC114.91 %4142.0B4759.65
28.24
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#2979_05DUMONT 765_B2_SRT-A
BreakerAC114.85 %4142.0B4756.98
31.7
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#TEDDY MARY_SRT-A_SENS
BreakerAC110.67 %4142.0B4583.78
27.69
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_05MARYSV 765_C2_SRT-A_SENS
BreakerAC110.05 %4142.0B4558.43
27.79
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC109.64 %4142.0B4541.17
27.32
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC108.44 %4142.0B4491.48
27.37
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#2995_05E LIMA 345_M_SRT-A
BreakerAC108.11 %4142.0B4477.92
27.16
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC107.56 %4142.0B4455.3
28.03
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P7-1_#11010___SRT-A
TowerAC103.94 %4142.0B4305.0
27.2
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#9287_1679_SRT-A
SingleAC103.12 %4142.0B4271.28
24.69
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P7-1_#11087___SRT-A-1
TowerAC103.11 %4142.0B4270.92
27.45
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC100.58 %4142.0B4166.12
25.47
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
BusAC100.54 %4142.0B4164.42
26.29
GD2ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-022T_SRT-A_SENS
TowerAC116.55 %1793.0B2089.8
25.85
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_05MARYSV 765_A_SRT-A_SENS
BreakerAC103.61 %1868.0B1935.5
9.78
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC103.36 %1868.0B1930.81
9.76

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-002_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-002_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.58 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2114.26
MW Contribution:
12.85
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-002_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.06 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2930.9
MW Contribution:
14.21
Bus #Bus NameTypeMW Contribution
957071AF2-004 GEN
50/50
15.111
23929302BS-PKR
50/50
2.564
23857102WLORG-A
Adder
8.069
241832AE2-181_GEN
Solar/Wind Harmer
2.119
958321AF2-126 GEN
Solar/Wind Harmer
1.652
23906402RICHG1
Adder
1.43
23906502RICHG2&3
Adder
1.428
270541AE2-072 C
Solar/Wind Harmer
4.762
270588AE1-091_GEN
Solar/Wind Harmer
7.73
270044AE2-322 C
Solar/Wind Harmer
0.894
961961AG1-039 GEN
Solar/Wind Harmer
1.859
958091AF2-103 GEN
Solar/Wind Harmer
0.099
246938BC-WTG3
Solar/Wind Harmer
2.391
270491AE1-102 GEN2
Solar/Wind Harmer
0.781
24695305TIMB G C
Solar/Wind Harmer
1.933
945111AF1-176 GEN
Solar/Wind Harmer
3.07
270505AE1-170 C O1
Solar/Wind Harmer
8.128
970065AG2-057 GEN
Solar/Wind Harmer
0.45
270063AE2-323 C
Solar/Wind Harmer
1.163
965021AG1-366 GEN
Solar/Wind Harmer
1.223
247643Z2-116 C
Solar/Wind Harmer
0.036
942871AE2-306 GEN
Solar/Wind Harmer
0.454
270391AF1-285 GEN3
Solar/Wind Harmer
0.233
24441505OLIV SLR
Solar/Wind Harmer
0.066
270043AE2-236 GEN
Solar/Wind Harmer
2.674
971347AH1-153 GEN
Solar/Wind Harmer
2.359
972231SS25-0005
Solar/Wind Harmer
4.134
972181SS23-001
Solar/Wind Harmer
2.584
274752CRETE EC ;2U
Adder
2.129
274753CRETE EC ;3U
Adder
2.129
274724RIVER EC ;11
Adder
7.651
962511AG1-100 GEN
Solar/Wind Helper
0.454
203854AF2-039 C
Solar/Wind Helper
0.167
20398826ARMNA MT
Solar/Wind Helper
0.785
235058AG1-386 C
Solar/Wind Helper
0.2
203993AD2-133_GEN1
Solar/Wind Helper
0.497
23917202WLORG-3
50/50
1.941
23917302WLORG-4
50/50
1.898
966311AG1-500 GEN
50/50
176.524
23867002DVBSG1
50/50
12.603
24190002OREGON_ST1
50/50
3.625
24189802OREGON_CT1
50/50
2.75
23857202WLORG-B
Adder
8.313
241996AE2-282_GEN
Solar/Wind Harmer
2.339
241808AF1-120 C
Solar/Wind Harmer
1.304
247522W1-056 GEN
Solar/Wind Harmer
1.879
944231AF1-091 GEN
Solar/Wind Harmer
12.113
247607V1-011 GEN
Solar/Wind Harmer
2.419
942801AE2-298 GEN
Solar/Wind Harmer
0.922
246937BC-WTG2
Solar/Wind Harmer
2.35
270246TR4_N_V150
Solar/Wind Harmer
0.472
270247TR4_N_V136
Solar/Wind Harmer
0.472
961051AF2-396 GEN
Solar/Wind Harmer
8.744
961051AF2-396 GEN
Solar/Wind Harmer
4.067
270462AD2-086
Solar/Wind Harmer
3.781
247620Y3-023
Adder
0.245
241960AC2-195 GEN
Solar/Wind Harmer
1.397
970349AG2-230 GEN
Solar/Wind Harmer
7.078
965681AG1-436 GEN
Solar/Wind Harmer
5.896
965791AG1-447 GEN
Solar/Wind Harmer
3.017
270535AF1-215 GEN1
Solar/Wind Harmer
1.98
270536AF1-215 GEN2
Solar/Wind Harmer
1.98
23860102FRMENG 1
50/50
1.798
23860202FRMENG 2
50/50
1.798
241886AC2-103 GEN2
Solar/Wind Harmer
17.897
24191202EL_AA1-006
Adder
0.352
945411AF1-206 GEN
Solar/Wind Harmer
8.76
270361_3
Solar/Wind Harmer
10.197
270575GUS2 35KV
Solar/Wind Harmer
12.013
270499AE1-146 GEN
Solar/Wind Harmer
2.797
945641AF1-229 GEN
Solar/Wind Harmer
3.889
270428AC2-015 C
Solar/Wind Harmer
5.2
970159AG2-109 GEN
Solar/Wind Harmer
3.775
971549AH1-272 GEN
Solar/Wind Harmer
12.854
966831AG1-554 GEN
Solar/Wind Harmer
0.826
270404AC1-167 GEN
Solar/Wind Harmer
0.737
971567AH1-282 GEN
Solar/Wind Harmer
3.214
270007AE1-245 C
Solar/Wind Harmer
3.305
957201AF2-014 GEN
Solar/Wind Harmer
2.725
270435AC2-044 GEN
Solar/Wind Harmer
1.202
270377AD1-106 GEN
Solar/Wind Harmer
3.053
944161AF1-084 GEN
Solar/Wind Harmer
1.246
965041AG1-368 GEN
Solar/Wind Harmer
5.565
247521TR3_G114
Solar/Wind Harmer
1.865
270191TR4_S_V150
Solar/Wind Harmer
1.664
965051AG1-369 GEN
Solar/Wind Harmer
2.771
270302AB2-170 GEN
Solar/Wind Harmer
4.551
970031AG2-029 GEN
Solar/Wind Harmer
13.191
959331AF2-224 GEN
Solar/Wind Harmer
5.26
971771AH1-392 GEN
Solar/Wind Harmer
4.593
970179AG2-119 GEN
Solar/Wind Harmer
4.027
270223U2-072_GEN1
Solar/Wind Harmer
0.989
270224U2-072_GEN2
Solar/Wind Harmer
0.989
270227U2-072_GEN3
Solar/Wind Harmer
0.989
270228U2-072_GEN4
Solar/Wind Harmer
0.989
270231U2-072_GEN5
Solar/Wind Harmer
0.989
270578AF1-285 GEN2
Solar/Wind Harmer
0.233
270526AF1-158 GEN
Solar/Wind Harmer
2.256
23917402WLORG-5
50/50
1.908
23917102WLORG-2
50/50
1.88
24189902OREGON_CT2
50/50
2.692
23856402BAYSG1
50/50
1.455
23860302FRMENG 3
50/50
3.65
241885AC2-103 GEN1
Solar/Wind Harmer
17.897
241807AE2-176_GEN
Solar/Wind Harmer
7.207
972253AH1-711 GEN
Adder
53.07
241858AF1-205_GEN
Solar/Wind Harmer
5.982
966321AG1-501 GEN
Adder
1.627
957111AF2-005 GEN
Adder
1.302
23920202STRYCT
Adder
1.949
241840AF1-064_GEN
Solar/Wind Harmer
1.536
23906502RICHG2&3
Adder
1.428
960841AF2-375 GEN
Solar/Wind Harmer
4.495
270297AD1-101 GEN
Solar/Wind Harmer
1.496
270258AD1-119 GEN
Solar/Wind Harmer
1.322
241847AF2-150_GEN
Solar/Wind Harmer
2.695
246936BC-WTG1
Solar/Wind Harmer
2.35
270489AE1-102 GEN1
Solar/Wind Harmer
0.781
965421AG1-410 GEN
Solar/Wind Harmer
17.81
24441205WTRV SLR C
Solar/Wind Harmer
0.079
270449AD2-020 GEN
Solar/Wind Harmer
1.557
943021AE2-325 GEN
Solar/Wind Harmer
2.023
270317AD1-130_GEN
Solar/Wind Harmer
1.74
270485AE1-090_GEN
Solar/Wind Harmer
0.329
945111AF1-176 GEN
Solar/Wind Harmer
9.687
957891AF2-083 GEN
Solar/Wind Harmer
8.1
241813AF1-122_GEN
Solar/Wind Harmer
2.879
971201AH1-060 GEN
Solar/Wind Harmer
0.9
24639705ELKHART HY
Adder
0.081
965011AG1-365 GEN
Solar/Wind Harmer
5.26
270216AD2-079_GEN
Solar/Wind Harmer
0.315
270391AF1-285 GEN3
Solar/Wind Harmer
0.606
270578AF1-285 GEN2
Solar/Wind Harmer
0.606
970373AG2-245 GEN
Solar/Wind Harmer
9.365
270055AF2-134 C O1
Solar/Wind Harmer
1.32
274751CRETE EC ;1U
Adder
2.129
274754CRETE EC ;4U
Adder
2.129
274723RIVER EC ;12
Adder
7.743
203947AF1-006 C
Solar/Wind Helper
0.508
961971AG1-040 GEN
Solar/Wind Helper
0.442
203830AF1-094 GEN
Solar/Wind Helper
0.426
203979AG1-198 GEN
Solar/Wind Helper
0.256
241966AE1-183 GEN
Solar/Wind Helper
0.157
254303AC2-168 GEN
Solar/Wind Helper
0.091
203855AF2-088 C
Solar/Wind Helper
0.081
203952AE2-129 C
Solar/Wind Helper
0.238
20090526Q36
Solar/Wind Helper
0.497
20091526CHSTN_FL
Solar/Wind Helper
0.266
963791AG1-232 GEN
Solar/Wind Harmer
6.482
960681AF2-359 GEN
Solar/Wind Harmer
1.782
270071AF1-092 GEN
Solar/Wind Harmer
6.649
203846AF2-130 C
Solar/Wind Helper
0.312
241985AE1-237 GEN
Solar/Wind Helper
0.159
241982AE2-343 S C
Solar/Wind Helper
0.143
241997AF1-093 GEN
Solar/Wind Helper
0.157
20334926Z1-069 C
Solar/Wind Helper
0.787
20094526CT_V3-030
Solar/Wind Helper
0.225
942221AE2-234 GEN
Solar/Wind Harmer
1.509
203835AF1-098 GEN
Solar/Wind Helper
1.743
241801AE1-079 GEN
Solar/Wind Helper
0.16
241967AE2-285_GEN
Solar/Wind Helper
0.41
254304AE2-114 C
Solar/Wind Helper
0.137
254305AE2-115 C
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.393
203804AE2-113_GEN
Solar/Wind Helper
1.068
940863AE2-074 GEN
Solar/Wind Helper
0.276
946381AF1-302 GEN
Solar/Wind Helper
0.128
203954AE2-126 C
Solar/Wind Helper
0.264
203853AF1-134 C O1
Solar/Wind Helper
0.245
203818AF1-086 GEN
Solar/Wind Helper
0.851
203946AE2-131 C
Solar/Wind Helper
0.238
946071AF1-272 GEN
Solar/Wind Helper
1.261
990142J1224
External Queue
14.317364692687988
990527J1329
External Queue
1.9586000442504883
991182J1586 G
External Queue
26.50733757019043
991177J1571 G
External Queue
16.711238861083984
LAGNLTFEXP_LAGN->PJM
CLTF
4.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.326
TVALTFEXP_TVA->PJM
CLTF
1.871
NYPJM->LTFIMP_NY
CLTF
2.203
LGEELTFEXP_LGEE->PJM
CLTF
1.76
WECLTFEXP_WEC->PJM
CLTF
1.522
AG2-052LTFEXP_AG2-052->PJM
LTF
0.098
AH1-155LTFEXP_AH1-155->PJM
LTF
0.147
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.951
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.496
MECLTFEXP_MEC->PJM
CLTF
5.849
SIGELTFEXP_SIGE->PJM
CLTF
0.148
CPLELTFEXP_CPLE->PJM
CLTF
0.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.551

Details for [AH1-272] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:215.53 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.22
MW Contribution:
12.84
IPD Plant:AH1-272
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
PJM_IPD
12.84

Details for [AH1-272] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:215.53 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.22
MW Contribution:
12.84
IPD Plant:AH1-272
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
PJM_IPD
12.84

Details for [AH1-272] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.53 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.22
MW Contribution:
12.84
IPD Plant:AH1-272
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
PJM_IPD
12.84

Details for [AH1-272] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.5 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2542.96
MW Contribution:
12.84
IPD Plant:AH1-272
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
PJM_IPD
12.84

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#2979_05DUMONT 765_B2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2979_05DUMONT 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.9 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5096.22
MW Contribution:
26.73
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
20.648
274773LINCOLN ;4U
50/50
13.735
274774LINCOLN ;5U
50/50
13.735
972207SS24-0001
Solar/Wind Harmer
46.022
941551AE2-152 GEN
Solar/Wind Harmer
8.62
274723RIVER EC ;12
Adder
33.711
274802UNIV PARK;5U
Adder
10.93
274871GR RIDGE ;2U
Solar/Wind Harmer
14.405
274847GR RIDGE ;BU
Solar/Wind Harmer
9.472
274676JOLIET 29;8U
Adder
57.487
274674JOLIET 9 ;6U
Adder
28.766
274745AC1-111 GEN9
Adder
10.422
274732ELWOOD EC;7P
Adder
30.613
274812UNIV PK N;8U
Adder
9.317
274751CRETE EC ;1U
Adder
9.004
274754CRETE EC ;4U
Adder
9.004
274682WAUKEGAN ;7U
Adder
32.625
274828WAUKEGAN ;BP
Adder
20.009
962781AG1-127 GEN
Solar/Wind Harmer
17.098
274872LEEDK;1U
Solar/Wind Harmer
14.699
276694AA1-018 GEN2
Solar/Wind Harmer
11.281
276691AA1-018 GEN1
Solar/Wind Harmer
1.348
274861TOP CROP ;1U
Solar/Wind Harmer
10.814
939401AE1-172 GEN
Solar/Wind Harmer
24.479
276805AD2-038 GEN
Solar/Wind Harmer
8.969
971997AH1-543 GEN
Solar/Wind Harmer
27.414
274770LINCOLN ;1U
50/50
13.735
274771LINCOLN ;2U
50/50
13.735
270102X2-052 ST
50/50
3.072
270100X2-052 CT1
50/50
2.838
270101X2-052 CT2
50/50
2.838
970349AG2-230 GEN
Solar/Wind Harmer
32.81
276897AD1-100 C
Solar/Wind Harmer
88.29
965681AG1-436 GEN
Solar/Wind Harmer
23.688
965791AG1-447 GEN
Solar/Wind Harmer
12.12
274888KELLY CRK;1U
Solar/Wind Harmer
11.148
276776AD2-060 GEN
Solar/Wind Harmer
0.791
958011AF2-095 GEN
Solar/Wind Harmer
27.203
970941AG2-585 GEN
Solar/Wind Harmer
10.39
274674JOLIET 9 ;6U
Adder
28.766
274805UNIV PK N;1U
Adder
9.337
274808UNIV PK N;4U
Adder
9.276
276893AG1-478 C
Solar/Wind Harmer
0.815
274695ROCKY RD ;2P
Adder
20.321
274693ROCKY RD ;1P
Adder
20.121
274697ROCKY RD ;3P
Adder
5.52
274696ROCKY RD ;4P
Adder
20.799
274683WAUKEGAN ;8U
Adder
38.171
274683WAUKEGAN ;8U
Adder
32.177
962691AG1-118 GEN
Solar/Wind Harmer
54.174
960751AF2-366 GEN
Solar/Wind Harmer
5.158
958481AF2-142 GEN
Solar/Wind Harmer
26.819
958491AF2-143 GEN
Solar/Wind Harmer
26.235
276901AD2-066 C O1
Solar/Wind Harmer
6.125
971341AH1-150 GEN
Solar/Wind Harmer
34.748
971343AH1-151 GEN
Solar/Wind Harmer
34.748
972235AH1-702 GEN1
Adder
4.335
972236AH1-702 GEN2
Adder
3.77
276872AE1-163_GEN1
Solar/Wind Harmer
11.383
276876AE1-163_GEN2
Solar/Wind Harmer
11.383
938861AE1-114 GEN
Solar/Wind Harmer
13.805
274764LEE CO EC;5U
Adder
15.601
274765LEE CO EC;6U
Adder
15.601
274762LEE CO EC;3U
Adder
15.564
274763LEE CO EC;4U
Adder
15.417
276158O29GEN2
Solar/Wind Harmer
8.134
276157O29GEN1
Solar/Wind Harmer
6.184
961051AF2-396 GEN
Solar/Wind Harmer
25.769
961051AF2-396 GEN
Solar/Wind Harmer
11.985
276645AC1-214 GEN1
Solar/Wind Harmer
2.128
942111AE2-223 GEN
Solar/Wind Harmer
12.128
247620Y3-023
Adder
0.561
276882AE2-255 GEN
Solar/Wind Harmer
5.867
957471AF2-041 GEN
Solar/Wind Harmer
52.122
959081AF2-199 GEN
Solar/Wind Harmer
17.374
971067AG2-660 GEN
Solar/Wind Harmer
4.04
274822ROCKFORD ;11
Adder
33.903
970819AG2-516 GEN
Solar/Wind Harmer
20.52
24441205WTRV SLR C
Solar/Wind Harmer
0.226
274858EASY ROAD;U2
Solar/Wind Harmer
8.014
274761LEE CO EC;2U
Adder
15.564
274766LEE CO EC;7U
Adder
15.381
970569AG2-363 GEN
Solar/Wind Harmer
49.74
270449AD2-020 GEN
Solar/Wind Harmer
4.631
943021AE2-325 GEN
Solar/Wind Harmer
6.02
957891AF2-083 GEN
Solar/Wind Harmer
24.69
276708O09 GEN2
Solar/Wind Harmer
5.807
276646AC1-214 GEN2
Solar/Wind Harmer
2.128
945111AF1-176 GEN
Solar/Wind Harmer
28.079
274848CAMPGROVE;RU
Solar/Wind Harmer
10.071
270216AD2-079_GEN
Solar/Wind Harmer
0.917
276655WTG1_EQ
Solar/Wind Harmer
12.913
276656WTG2_EQ
Solar/Wind Harmer
1.71
939741AE1-205 GEN
Solar/Wind Harmer
29.59
970373AG2-245 GEN
Solar/Wind Harmer
30.409
24639705ELKHART HY
Adder
0.208
274772LINCOLN ;3U
50/50
13.735
972259AH1-714 GEN
50/50
38.928
971347AH1-153 GEN
Solar/Wind Harmer
10.937
970707AG2-453 GEN
Solar/Wind Harmer
54.845
939351AE1-166 GEN
Solar/Wind Harmer
11.272
276164X3-005 C
Solar/Wind Harmer
1.332
274887GEN-1.85
Solar/Wind Harmer
10.065
276772AC2-154 GEN
Solar/Wind Harmer
5.272
276843GEN-1.7
Solar/Wind Harmer
1.083
276806AD2-047 C O1
Solar/Wind Harmer
20.209
274724RIVER EC ;11
Adder
33.374
274826FISK ;BP
Adder
20.603
972038AH1-567 GEN2
Adder
0.686
943121AE2-341 GEN
Solar/Wind Harmer
28.173
943591AF1-030 GEN
Solar/Wind Harmer
18.782
274803UNIV PARK;6U
Adder
10.93
274676JOLIET 29;8U
Adder
55.433
274729ELWOOD EC;1P
Adder
30.614
274730ELWOOD EC;6P
Adder
30.613
274734ELWOOD EC;8P
Adder
30.613
274736ELWOOD EC;9P
Adder
30.613
274814UNIV PK N;0U
Adder
9.398
274807UNIV PK N;3U
Adder
9.378
274811UNIV PK N;7U
Adder
9.317
972231SS25-0005
Solar/Wind Harmer
17.483
972181SS23-001
Solar/Wind Harmer
10.927
274752CRETE EC ;2U
Adder
9.004
274753CRETE EC ;3U
Adder
9.004
274682WAUKEGAN ;7U
Adder
32.625
24441505OLIV SLR
Solar/Wind Harmer
0.24
274862TOP CROP ;2U
Solar/Wind Harmer
9.03
276799AD1-013 GEN
Solar/Wind Harmer
3.89
946671AF1-331 GEN
Solar/Wind Harmer
0.737
274855GSG-6 ;RU
Solar/Wind Harmer
6.491
274850MENDOTA H;RU
Solar/Wind Harmer
4.513
276602WESTBROOK C
Solar/Wind Harmer
3.737
276868AE1-113 GEN
Solar/Wind Harmer
17.601
274879MINONK ;1U
Solar/Wind Harmer
11.735
959091AF2-200 GEN
Solar/Wind Harmer
34.748
270505AE1-170 C O1
Solar/Wind Harmer
25.155
274857EASY ROAD;U1
Solar/Wind Harmer
8.014
274760LEE CO EC;1U
Adder
15.564
274767LEE CO EC;8U
Adder
15.381
276603SUBLETTE C
Solar/Wind Harmer
1.748
970571AG2-364 GEN
Solar/Wind Harmer
33.16
274851PROVIDENC;RU
Solar/Wind Harmer
4.524
274849CRESCENT ;1U
Solar/Wind Harmer
2.937
276782AC1-033 GEN
Solar/Wind Harmer
6.287
274878BISHOP HL;2U
Solar/Wind Harmer
5.319
945111AF1-176 GEN
Solar/Wind Harmer
8.899
965931AG1-462 GEN
Solar/Wind Harmer
39.241
971087AG2-675 GEN
Solar/Wind Harmer
5.726
247643Z2-116 C
Solar/Wind Harmer
0.107
965091AG1-374 GEN
Solar/Wind Harmer
42.222
274775LINCOLN ;6U
50/50
13.735
274776LINCOLN ;7U
50/50
13.735
274777LINCOLN ;8U
50/50
13.735
24344005CKG1
50/50
12.627
274661LASCO STA;2U
50/50
10.703
274660LASCO STA;1U
50/50
13.826
972227AH1-698 GEN1
Adder
4.953
972228AH1-698 GEN2
Adder
7.034
960681AF2-359 GEN
Solar/Wind Harmer
7.16
960591AF2-350 GEN
Solar/Wind Harmer
18.891
274827FISK ;RP
Adder
14.602
274800UNIV PARK;3U
Adder
10.964
274801UNIV PARK;4U
Adder
10.964
972037AH1-567 GEN1
Adder
0.343
274675JOLIET 29;7U
Adder
57.489
274675JOLIET 29;7U
Adder
55.436
970833AG2-524 GEN
Solar/Wind Harmer
16.357
970833AG2-524 GEN
Solar/Wind Harmer
7.608
274687WILL CNTY;4U
Adder
52.33
274687WILL CNTY;4U
Adder
52.33
274744AC1-111 GEN8
Adder
10.422
274746AC1-111 G10
Adder
10.422
274728ELWOOD EC;5P
Adder
30.613
274731ELWOOD EC;2P
Adder
30.614
274733ELWOOD EC;3P
Adder
30.614
274735ELWOOD EC;4P
Adder
30.614
276893AG1-478 C
Solar/Wind Harmer
1.022
270526AF1-158 GEN
Solar/Wind Harmer
8.061
971675AH1-338 GEN
Solar/Wind Harmer
31.664
276861AD2-134 GEN
Solar/Wind Harmer
3.139
276863AD2-134 GEN
Solar/Wind Harmer
3.139
971411AH1-196 GEN
Solar/Wind Harmer
26.364
970073AG2-061 GEN
Solar/Wind Harmer
4.067
971171AH1-044 GEN
Solar/Wind Harmer
34.748
274823ROCKFORD ;21
Adder
33.657
274856ECOGROVE ;U1
Solar/Wind Harmer
5.747
276611AD2-172 GEN
Solar/Wind Harmer
4.36
276612AE2-035 GEN
Solar/Wind Harmer
4.36
971771AH1-392 GEN
Solar/Wind Harmer
15.314
276889AE2-281 GEN
Solar/Wind Harmer
3.252
274863CRW1-WTG
Solar/Wind Harmer
9.452
274864CRW2-WTG
Solar/Wind Harmer
9.452
971681AH1-341 GEN
Solar/Wind Harmer
25.271
926823AC1-168 GEN
Solar/Wind Harmer
7.138
944161AF1-084 GEN
Solar/Wind Harmer
3.664
972267AH1-718 GEN
Adder
6.837
970169AG2-114 GEN
Solar/Wind Harmer
16.278
276741O09 GEN1
Solar/Wind Harmer
5.807
274877BISHOP HL;1U
Solar/Wind Harmer
5.319
946321AF1-296 GEN
Solar/Wind Harmer
16.221
276726Z2-087_GEN
Solar/Wind Harmer
11.699
959341AF2-225 GEN
Solar/Wind Harmer
22.192
971549AH1-272 GEN
Solar/Wind Harmer
26.725
274853TWINGROVE;U1
Solar/Wind Harmer
10.227
274854TWINGROVE;U2
Solar/Wind Harmer
10.013
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.249
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.529
LAGNLTFEXP_LAGN->PJM
CLTF
7.188
TVALTFEXP_TVA->PJM
CLTF
1.859
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
2.275
WECLTFEXP_WEC->PJM
CLTF
6.547
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.201
AG2-052LTFEXP_AG2-052->PJM
LTF
0.338
AH1-155LTFEXP_AH1-155->PJM
LTF
0.506
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
174.519
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.552
MECLTFEXP_MEC->PJM
CLTF
21.076
SIGELTFEXP_SIGE->PJM
CLTF
0.094
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.708
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4309.27
MW Contribution:
20.9
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:92.06 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3813.12
MW Contribution:
17.08
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
17.244
24721705FLATG2
50/50
3.319
24721805FLATG3
50/50
3.319
962761AG1-125 GEN
Solar/Wind Harmer
73.48
970149AG2-104 GEN
Solar/Wind Harmer
39.681
970155AG2-107 GEN
Solar/Wind Harmer
46.922
270520AE2-214 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.014
971995AH1-542 GEN
Solar/Wind Harmer
4.575
246936BC-WTG1
Solar/Wind Harmer
0.455
270489AE1-102 GEN1
Solar/Wind Harmer
1.468
965421AG1-410 GEN
Solar/Wind Harmer
33.842
965011AG1-365 GEN
Solar/Wind Harmer
11.206
24639705ELKHART HY
Adder
0.237
957891AF2-083 GEN
Solar/Wind Harmer
17.821
945111AF1-176 GEN
Solar/Wind Harmer
19.076
970373AG2-245 GEN
Solar/Wind Harmer
22.382
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.553
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.746
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
13.152
965651AG1-433 GEN
Solar/Wind Harmer
3.072
274773LINCOLN ;4U
Adder
12.619
274774LINCOLN ;5U
Adder
12.619
24721905FLATG4
50/50
3.319
24722005FLATG5
50/50
3.319
270051AF1-062 GEN
50/50
23.559
270475AD2-096_GEN
50/50
14.072
962771AG1-126 GEN
Solar/Wind Harmer
73.48
970153AG2-106 GEN
Solar/Wind Harmer
46.922
961921AG1-034 GEN
Solar/Wind Harmer
14.732
270284AF1-227 GEN1
Solar/Wind Harmer
0
270391AF1-285 GEN3
Solar/Wind Harmer
0.932
942051AE2-217 GEN
Solar/Wind Harmer
25.116
270518AE2-148 GEN
Solar/Wind Harmer
1.063
253325AC1-069 GEN
Solar/Wind Harmer
0.014
246938BC-WTG3
Solar/Wind Harmer
0.406
270491AE1-102 GEN2
Solar/Wind Harmer
1.468
965021AG1-366 GEN
Solar/Wind Harmer
3.735
270043AE2-236 GEN
Solar/Wind Harmer
7.125
24695305TIMB G C
Solar/Wind Harmer
0.934
971347AH1-153 GEN
Solar/Wind Harmer
5.488
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
48.343
971199AH1-059 GEN
Solar/Wind Harmer
2.255
270505AE1-170 C O1
Solar/Wind Harmer
11.228
945111AF1-176 GEN
Solar/Wind Harmer
8.665
964401AG1-302 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
8.236
274772LINCOLN ;3U
Adder
12.619
274752CRETE EC ;2U
Adder
12.279
274753CRETE EC ;3U
Adder
12.279
274724RIVER EC ;11
Adder
26.355
247642Z2-115 C
Solar/Wind Harmer
0.004
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.354
274814UNIV PK N;0U
Adder
7.488
274807UNIV PK N;3U
Adder
7.472
274811UNIV PK N;7U
Adder
7.423
970289AG2-191 GEN
Solar/Wind Harmer
1.133
274803UNIV PARK;6U
Adder
8.599
274826FISK ;BP
Adder
16.137
274887GEN-1.85
Solar/Wind Harmer
0.267
276843GEN-1.7
Solar/Wind Harmer
0.332
276806AD2-047 C O1
Solar/Wind Harmer
5.825
972038AH1-567 GEN2
Adder
0.538
970707AG2-453 GEN
Solar/Wind Harmer
33.528
972259AH1-714 GEN
Adder
28.051
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
43.287
274730ELWOOD EC;6P
Adder
24.024
274734ELWOOD EC;8P
Adder
24.024
274736ELWOOD EC;9P
Adder
24.024
274729ELWOOD EC;1P
Adder
24.024
970065AG2-057 GEN
Solar/Wind Harmer
1.014
943121AE2-341 GEN
Solar/Wind Harmer
16.972
943591AF1-030 GEN
Solar/Wind Harmer
11.286
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
24386205FR-12G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
2.597
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.132
274862TOP CROP ;2U
Solar/Wind Harmer
1.359
274682WAUKEGAN ;7U
Adder
25.826
276868AE1-113 GEN
Solar/Wind Harmer
1.991
274879MINONK ;1U
Solar/Wind Harmer
0.415
946031AF1-268 GEN
Solar/Wind Harmer
9.47
970825AG2-519 GEN
Solar/Wind Harmer
7.486
270004AE1-209 GEN
Solar/Wind Harmer
2.149
946671AF1-331 GEN
Solar/Wind Harmer
1.054
274855GSG-6 ;RU
Solar/Wind Harmer
0.361
274850MENDOTA H;RU
Solar/Wind Harmer
0.115
959091AF2-200 GEN
Solar/Wind Harmer
19.677
970571AG2-364 GEN
Solar/Wind Harmer
19.606
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.93
274767LEE CO EC;8U
Adder
12.777
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.321
965091AG1-374 GEN
Solar/Wind Harmer
28.713
959611AF2-252 GEN
Solar/Wind Harmer
3.19
253394AE2-221_GEN
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
23.963
971087AG2-675 GEN
Solar/Wind Harmer
5.012
971993AH1-541 GEN
Solar/Wind Harmer
4.285
24728505AND G1
Adder
5.071
970193AG2-126 GEN
Solar/Wind Harmer
13.784
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.737
270541AE2-072 C
Solar/Wind Harmer
0.001
957381AF2-032 GEN
Solar/Wind Harmer
2.038
25196608WSDLE5
Adder
10.619
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.61
23906502RICHG2&3
Adder
1.439
23906402RICHG1
Adder
1.437
237048AF1-022 C
Solar/Wind Helper
0.174
237046AF1-021 C
Solar/Wind Helper
0.304
964991AG1-363 GEN
Solar/Wind Helper
3.522
23562501BACKB
Solar/Wind Helper
0.847
235058AG1-386 C
Solar/Wind Helper
0.4
238127S14_GEN_2
Solar/Wind Helper
0.635
202652Y1-033 WT C
Solar/Wind Helper
0.501
942481AE2-261 GEN
Solar/Wind Harmer
16.491
270119AB2-067 GEN1
50/50
17.244
270120AB2-067 GEN2
50/50
17.244
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
10.655
270462AD2-086
Solar/Wind Harmer
0.002
938701AE1-092 GEN
Solar/Wind Harmer
21.46
971655AH1-328 GEN
Solar/Wind Harmer
4.742
970329AG2-216 GEN
Solar/Wind Harmer
5.083
25326509SID D
Adder
2.143
246937BC-WTG2
Solar/Wind Harmer
0.455
270246TR4_N_V150
Solar/Wind Harmer
0.071
270247TR4_N_V136
Solar/Wind Harmer
0.071
247607V1-011 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
16.464
247620Y3-023
Adder
0.71
965681AG1-436 GEN
Solar/Wind Harmer
13.426
965791AG1-447 GEN
Solar/Wind Harmer
9.845
970623AG2-406 GEN
Solar/Wind Harmer
1.96
961051AF2-396 GEN
Solar/Wind Harmer
21.315
961051AF2-396 GEN
Solar/Wind Harmer
14.21
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.994
942221AE2-234 GEN
Solar/Wind Harmer
4.232
944541AF1-119 GEN
Solar/Wind Harmer
0.7
960971AF2-388 GEN
Solar/Wind Harmer
6.145
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.914
944231AF1-091 GEN
Solar/Wind Harmer
24.097
274770LINCOLN ;1U
Adder
12.619
274771LINCOLN ;2U
Adder
12.619
270269AC2-059
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
7.439
274808UNIV PK N;4U
Adder
7.391
25322209TAIT E
Adder
14.396
25322209TAIT E
Adder
14.072
970291AG2-192 GEN
Solar/Wind Harmer
1.338
970291AG2-192 GEN
Solar/Wind Harmer
0.618
274888KELLY CRK;1U
Solar/Wind Harmer
0.6
276776AD2-060 GEN
Solar/Wind Harmer
1.097
958011AF2-095 GEN
Solar/Wind Harmer
14.803
970941AG2-585 GEN
Solar/Wind Harmer
5.654
276897AD1-100 C
Solar/Wind Harmer
25.624
971613AH1-306 GEN
Solar/Wind Harmer
4.9
274674JOLIET 9 ;6U
Adder
22.504
276893AG1-478 C
Solar/Wind Harmer
0.68
270031AE2-169
Solar/Wind Harmer
5.58
270599AE1-208 GEN
Solar/Wind Harmer
9.3
253370AE2-315 SEC1
Adder
2.904
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.147
270201AC2-176 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
15.103
247621Y3-024
Adder
0.348
964611AG1-324 GEN
Solar/Wind Harmer
0.754
274696ROCKY RD ;4P
Adder
16.391
274695ROCKY RD ;2P
Adder
16.014
274693ROCKY RD ;1P
Adder
15.856
274697ROCKY RD ;3P
Adder
4.35
274683WAUKEGAN ;8U
Adder
30.253
274683WAUKEGAN ;8U
Adder
25.502
958491AF2-143 GEN
Solar/Wind Harmer
14.984
962691AG1-118 GEN
Solar/Wind Harmer
29.945
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24721605FLATG1
50/50
3.319
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
9.821
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.932
945631AF1-228 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
5.259
943851AF1-053 GEN
Solar/Wind Harmer
3.643
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.888
241972AD1-140 GEN
Solar/Wind Harmer
1.272
270432AC2-029 GEN
Solar/Wind Harmer
5.04
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.43
959331AF2-224 GEN
Solar/Wind Harmer
7.844
247521TR3_G114
Solar/Wind Harmer
0.403
965051AG1-369 GEN
Solar/Wind Harmer
5.558
270071AF1-092 GEN
Solar/Wind Harmer
21.261
965041AG1-368 GEN
Solar/Wind Harmer
11.063
270007AE1-245 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
5.889
970179AG2-119 GEN
Solar/Wind Harmer
9.709
971771AH1-392 GEN
Solar/Wind Harmer
10.756
963791AG1-232 GEN
Solar/Wind Harmer
14.514
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
9.953
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.264
274775LINCOLN ;6U
Adder
12.619
274776LINCOLN ;7U
Adder
12.619
274777LINCOLN ;8U
Adder
12.619
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.956
972037AH1-567 GEN1
Adder
0.27
274827FISK ;RP
Adder
11.436
960591AF2-350 GEN
Solar/Wind Harmer
10.28
274800UNIV PARK;3U
Adder
8.587
274801UNIV PARK;4U
Adder
8.587
972228AH1-698 GEN2
Adder
5.454
970883AG2-550 GEN
Solar/Wind Harmer
9.92
970885AG2-551 GEN
Solar/Wind Harmer
3.307
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
19.677
971343AH1-151 GEN
Solar/Wind Harmer
19.677
972235AH1-702 GEN1
Adder
3.539
972236AH1-702 GEN2
Adder
3.077
270383AD1-128 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.694
938861AE1-114 GEN
Solar/Wind Harmer
5.51
274764LEE CO EC;5U
Adder
12.96
274765LEE CO EC;6U
Adder
12.96
274762LEE CO EC;3U
Adder
12.93
274763LEE CO EC;4U
Adder
12.808
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
3.143
276645AC1-214 GEN1
Solar/Wind Harmer
0.379
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.554
960611AF2-352 GEN
Solar/Wind Harmer
3.19
945391AF1-204 GEN
Solar/Wind Harmer
9.764
276615X2-022 GEN
Solar/Wind Harmer
0.095
276838X2-022 GEN2
Solar/Wind Harmer
0.516
25194408D.CRK1
Adder
9.313
25194508D.CRK3
Adder
1.741
972159AH1-661 GEN
Adder
1.225
23751201ROTHROCK
Solar/Wind Helper
0.691
23585401KL_K28_T16
Solar/Wind Helper
1.178
237043AE2-125 C
Solar/Wind Helper
0.16
235054AD2-180 GEN
Solar/Wind Helper
1.576
238117U2-030
Solar/Wind Helper
0.267
235531U2-073 GEN
Solar/Wind Helper
2.548
972227AH1-698 GEN1
Adder
3.84
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
40.93
274687WILL CNTY;4U
Adder
40.93
274675JOLIET 29;7U
Adder
44.89
274675JOLIET 29;7U
Adder
43.287
274728ELWOOD EC;5P
Adder
24.024
274731ELWOOD EC;2P
Adder
24.024
274733ELWOOD EC;3P
Adder
24.024
274735ELWOOD EC;4P
Adder
24.024
970833AG2-524 GEN
Solar/Wind Harmer
11.198
970833AG2-524 GEN
Solar/Wind Harmer
7.465
270377AD1-106 GEN
Solar/Wind Harmer
3.864
971609AH1-304 GEN
Solar/Wind Harmer
1.657
971549AH1-272 GEN
Solar/Wind Harmer
20.903
274744AC1-111 GEN8
Adder
8.105
274746AC1-111 G10
Adder
8.105
253372AE2-315 SEC3
Adder
2.747
253372AE2-315 SEC3
Adder
2.747
24386405FR-21G C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.923
25306009OHH W.
Adder
4.15
247536S-71 GEN
Solar/Wind Harmer
0.4
970073AG2-061 GEN
Solar/Wind Harmer
3.33
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.303
270543AE2-219 C
Solar/Wind Harmer
6.944
971675AH1-338 GEN
Solar/Wind Harmer
3.854
971411AH1-196 GEN
Solar/Wind Harmer
14.823
276861AD2-134 GEN
Solar/Wind Harmer
0.176
276863AD2-134 GEN
Solar/Wind Harmer
0.176
970169AG2-114 GEN
Solar/Wind Harmer
9.859
971171AH1-044 GEN
Solar/Wind Harmer
19.677
971029AG2-637 GEN
Solar/Wind Harmer
14.756
274823ROCKFORD ;21
Adder
27.402
926823AC1-168 GEN
Solar/Wind Harmer
1.667
274856ECOGROVE ;U1
Solar/Wind Harmer
0.228
971681AH1-341 GEN
Solar/Wind Harmer
15.659
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.156
972267AH1-718 GEN
Adder
5.748
276741O09 GEN1
Solar/Wind Harmer
0.34
274877BISHOP HL;1U
Solar/Wind Harmer
0.321
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.283
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.365
276848AB2-070 GEN3
Solar/Wind Harmer
0.363
276849AB2-070 GEN2
Solar/Wind Harmer
0.365
270263AC1-001 GEN
Solar/Wind Harmer
0.924
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.684
25196408WSDLE3
Adder
10.931
25196108MFTGT2
Adder
1.832
25196108MFTGT2
Adder
1.701
23750501ELLIOTTS
Solar/Wind Helper
0.6
23652301WDPWR_K20
Solar/Wind Helper
0.129
23750701CROSSCHOOL
Solar/Wind Helper
1.119
238118U2-030_1
Solar/Wind Helper
0.267
203955AF1-039 C O1
Solar/Wind Helper
0.331
958861AF2-177 GEN
Solar/Wind Harmer
4.506
274751CRETE EC ;1U
Adder
12.279
274754CRETE EC ;4U
Adder
12.279
270273AD2-016 GEN
Solar/Wind Harmer
1.064
274723RIVER EC ;12
Adder
26.668
270024AE2-089 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.423
25326309TAIT D
Adder
1.618
274802UNIV PARK;5U
Adder
8.599
945371AF1-202 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
44.89
270594AE1-207 GEN
Solar/Wind Harmer
11.433
270032AE2-172
Solar/Wind Harmer
6.805
274674JOLIET 9 ;6U
Adder
22.504
274732ELWOOD EC;7P
Adder
24.024
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
4.544
971201AH1-060 GEN
Solar/Wind Harmer
2.029
274745AC1-111 GEN9
Adder
8.105
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.636
274861TOP CROP ;1U
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
11.216
939401AE1-172 GEN
Solar/Wind Harmer
7.51
274682WAUKEGAN ;7U
Adder
25.826
274828WAUKEGAN ;BP
Adder
15.858
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.482
276882AE2-255 GEN
Solar/Wind Harmer
1.162
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.217
970825AG2-519 GEN
Solar/Wind Harmer
3.528
270005AE1-210 C O1
Solar/Wind Harmer
2.149
957471AF2-041 GEN
Solar/Wind Harmer
29.515
959081AF2-199 GEN
Solar/Wind Harmer
9.838
971067AG2-660 GEN
Solar/Wind Harmer
3.279
274822ROCKFORD ;11
Adder
27.602
970569AG2-363 GEN
Solar/Wind Harmer
29.408
970819AG2-516 GEN
Solar/Wind Harmer
11.727
963741AG1-226 GEN
Solar/Wind Harmer
23.101
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.93
274766LEE CO EC;7U
Adder
12.777
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.109
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
13.541
276646AC1-214 GEN2
Solar/Wind Harmer
0.379
276708O09 GEN2
Solar/Wind Harmer
0.34
274848CAMPGROVE;RU
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.647
24728605AND G2
Adder
5.071
276621W2-048 GEN
Solar/Wind Harmer
0.459
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.029
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.662
23906502RICHG2&3
Adder
1.439
25196808ZIMRHP
Adder
90.149
970091AG2-072 GEN
Adder
20.654
238185AF2-356 C
Solar/Wind Helper
2.037
23751101LEADS_P59
Solar/Wind Helper
1.839
238120AE2-309 GEN
Solar/Wind Helper
0.401
238126S14_GEN_1
Solar/Wind Helper
0.635
965911AG1-460 GEN
Solar/Wind Harmer
1.103
LAGNLTFEXP_LAGN->PJM
CLTF
14.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
TVALTFEXP_TVA->PJM
CLTF
6.29
NYPJM->LTFIMP_NY
CLTF
4.821
LGEELTFEXP_LGEE->PJM
CLTF
7.242
WECLTFEXP_WEC->PJM
CLTF
5.355
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.468
AG2-052LTFEXP_AG2-052->PJM
LTF
0.342
AH1-155LTFEXP_AH1-155->PJM
LTF
0.513
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.5
MECLTFEXP_MEC->PJM
CLTF
20.741
SIGELTFEXP_SIGE->PJM
CLTF
0.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
124.415

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.22 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4192.73
MW Contribution:
17.76
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
16.019
962761AG1-125 GEN
Solar/Wind Harmer
53.025
970149AG2-104 GEN
Solar/Wind Harmer
28.634
970155AG2-107 GEN
Solar/Wind Harmer
33.86
270520AE2-214 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.012
971995AH1-542 GEN
Solar/Wind Harmer
3.792
270273AD2-016 GEN
Solar/Wind Harmer
0.99
965011AG1-365 GEN
Solar/Wind Harmer
9.509
965421AG1-410 GEN
Solar/Wind Harmer
28.445
246936BC-WTG1
Solar/Wind Harmer
0.382
270489AE1-102 GEN1
Solar/Wind Harmer
1.232
25326309TAIT D
Adder
1.47
253370AE2-315 SEC1
Adder
2.657
270119AB2-067 GEN1
50/50
16.019
270120AB2-067 GEN2
50/50
16.019
270160DARBY CT5
50/50
0.863
270161DARBY CT6
50/50
0.851
270466AD2-091
50/50
9.17
25326509SID D
50/50
1.973
25326109MON D
50/50
1.91
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
9.172
938701AE1-092 GEN
Solar/Wind Harmer
17.933
971655AH1-328 GEN
Solar/Wind Harmer
3.962
270462AD2-086
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
4.378
270269AC2-059
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.382
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
970349AG2-230 GEN
Solar/Wind Harmer
14.122
25322209TAIT E
Adder
13.082
25322209TAIT E
Adder
12.788
965681AG1-436 GEN
Solar/Wind Harmer
11.573
965791AG1-447 GEN
Solar/Wind Harmer
8.487
247607V1-011 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.657
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270051AF1-062 GEN
50/50
19.835
270475AD2-096_GEN
50/50
11.402
961921AG1-034 GEN
Solar/Wind Harmer
12.522
962771AG1-126 GEN
Solar/Wind Harmer
53.025
970153AG2-106 GEN
Solar/Wind Harmer
33.86
270284AF1-227 GEN1
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Harmer
21.484
270391AF1-285 GEN3
Solar/Wind Harmer
0.762
270518AE2-148 GEN
Solar/Wind Harmer
0.922
253325AC1-069 GEN
Solar/Wind Harmer
0.012
965021AG1-366 GEN
Solar/Wind Harmer
3.17
270043AE2-236 GEN
Solar/Wind Harmer
6.088
246938BC-WTG3
Solar/Wind Harmer
0.341
270491AE1-102 GEN2
Solar/Wind Harmer
1.232
971347AH1-153 GEN
Solar/Wind Harmer
4.707
944531AF1-118 GEN
Solar/Wind Harmer
42.014
24695305TIMB G C
Solar/Wind Harmer
0.79
270063AE2-323 C
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
2.657
253371AE2-315 SEC2
Adder
2.513
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970191AG2-125 GEN
Solar/Wind Harmer
2.366
247642Z2-115 C
Solar/Wind Harmer
0.004
270505AE1-170 C O1
Solar/Wind Harmer
9.607
945111AF1-176 GEN
Solar/Wind Harmer
7.414
970289AG2-191 GEN
Solar/Wind Harmer
1.004
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.119
274772LINCOLN ;3U
Adder
10.998
274752CRETE EC ;2U
Adder
10.696
274753CRETE EC ;3U
Adder
10.696
274724RIVER EC ;11
Adder
22.971
274814UNIV PK N;0U
Adder
6.534
274807UNIV PK N;3U
Adder
6.52
274811UNIV PK N;7U
Adder
6.477
971199AH1-059 GEN
Solar/Wind Harmer
1.894
274803UNIV PARK;6U
Adder
7.515
274887GEN-1.85
Solar/Wind Harmer
0.234
276843GEN-1.7
Solar/Wind Harmer
0.291
276806AD2-047 C O1
Solar/Wind Harmer
5.094
274826FISK ;BP
Adder
14.105
972038AH1-567 GEN2
Adder
0.47
970707AG2-453 GEN
Solar/Wind Harmer
29.335
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.47
972259AH1-714 GEN
Adder
24.546
939351AE1-166 GEN
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.916
274729ELWOOD EC;1P
Adder
21.052
274730ELWOOD EC;6P
Adder
21.052
274734ELWOOD EC;8P
Adder
21.052
274736ELWOOD EC;9P
Adder
21.052
946031AF1-268 GEN
Solar/Wind Harmer
8.48
970825AG2-519 GEN
Solar/Wind Harmer
6.707
270004AE1-209 GEN
Solar/Wind Harmer
1.926
943121AE2-341 GEN
Solar/Wind Harmer
14.899
943591AF1-030 GEN
Solar/Wind Harmer
9.908
253394AE2-221_GEN
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
1.195
274682WAUKEGAN ;7U
Adder
22.722
276868AE1-113 GEN
Solar/Wind Harmer
1.756
274879MINONK ;1U
Solar/Wind Harmer
0.366
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
6.834
946671AF1-331 GEN
Solar/Wind Harmer
0.931
274855GSG-6 ;RU
Solar/Wind Harmer
0.318
274850MENDOTA H;RU
Solar/Wind Harmer
0.101
959091AF2-200 GEN
Solar/Wind Harmer
17.396
970571AG2-364 GEN
Solar/Wind Harmer
17.364
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.189
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.473
274767LEE CO EC;8U
Adder
11.338
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.286
965091AG1-374 GEN
Solar/Wind Harmer
25.673
959611AF2-252 GEN
Solar/Wind Harmer
2.853
24728505AND G1
Adder
4.655
965931AG1-462 GEN
Solar/Wind Harmer
21.435
971087AG2-675 GEN
Solar/Wind Harmer
4.483
970193AG2-126 GEN
Solar/Wind Harmer
12.603
971993AH1-541 GEN
Solar/Wind Harmer
3.869
970065AG2-057 GEN
Solar/Wind Harmer
0.833
25196608WSDLE5
Adder
10.184
25194608D.CRK4
Adder
1.946
252519AF1-045_GEN
Solar/Wind Harmer
4.291
957381AF2-032 GEN
Solar/Wind Harmer
1.857
25196008MFTGT1
Adder
1.556
237048AF1-022 C
Solar/Wind Helper
0.17
235058AG1-386 C
Solar/Wind Helper
0.41
237046AF1-021 C
Solar/Wind Helper
0.301
964991AG1-363 GEN
Solar/Wind Helper
3.439
942481AE2-261 GEN
Solar/Wind Harmer
2.388
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.608
942221AE2-234 GEN
Solar/Wind Harmer
3.698
944541AF1-119 GEN
Solar/Wind Harmer
0.615
960971AF2-388 GEN
Solar/Wind Harmer
5.398
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.187
970291AG2-192 GEN
Solar/Wind Harmer
0.548
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
18.232
961051AF2-396 GEN
Solar/Wind Harmer
12.155
274770LINCOLN ;1U
Adder
10.998
274771LINCOLN ;2U
Adder
10.998
971613AH1-306 GEN
Solar/Wind Harmer
4.356
970623AG2-406 GEN
Solar/Wind Harmer
1.654
274805UNIV PK N;1U
Adder
6.492
274808UNIV PK N;4U
Adder
6.449
270031AE2-169
Solar/Wind Harmer
4.956
270599AE1-208 GEN
Solar/Wind Harmer
8.26
274888KELLY CRK;1U
Solar/Wind Harmer
0.524
276776AD2-060 GEN
Solar/Wind Harmer
0.959
958011AF2-095 GEN
Solar/Wind Harmer
12.944
970941AG2-585 GEN
Solar/Wind Harmer
4.944
270201AC2-176 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
22.435
247621Y3-024
Adder
0.31
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.017
964611AG1-324 GEN
Solar/Wind Harmer
0.672
274674JOLIET 9 ;6U
Adder
19.719
276893AG1-478 C
Solar/Wind Harmer
0.596
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
8.912
970885AG2-551 GEN
Solar/Wind Harmer
2.971
958481AF2-142 GEN
Solar/Wind Harmer
13.279
944231AF1-091 GEN
Solar/Wind Harmer
20.375
274696ROCKY RD ;4P
Adder
14.42
274695ROCKY RD ;2P
Adder
14.087
274693ROCKY RD ;1P
Adder
13.949
274697ROCKY RD ;3P
Adder
3.827
270383AD1-128 GEN
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
26.624
274683WAUKEGAN ;8U
Adder
22.442
958491AF2-143 GEN
Solar/Wind Harmer
13.202
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
26.378
926881AC1-175 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.107
970621AG2-405 GEN
Solar/Wind Harmer
1.602
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.396
971343AH1-151 GEN
Solar/Wind Harmer
17.396
972235AH1-702 GEN1
Adder
3.132
972236AH1-702 GEN2
Adder
2.723
938861AE1-114 GEN
Solar/Wind Harmer
4.886
942111AE2-223 GEN
Solar/Wind Harmer
2.802
274764LEE CO EC;5U
Adder
11.5
274765LEE CO EC;6U
Adder
11.5
274762LEE CO EC;3U
Adder
11.473
274763LEE CO EC;4U
Adder
11.365
276645AC1-214 GEN1
Solar/Wind Harmer
0.337
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.382
960611AF2-352 GEN
Solar/Wind Harmer
2.853
945391AF1-204 GEN
Solar/Wind Harmer
8.927
276615X2-022 GEN
Solar/Wind Harmer
0.086
276838X2-022 GEN2
Solar/Wind Harmer
0.468
25194408D.CRK1
Adder
8.951
25194508D.CRK3
Adder
1.673
25183208HLCRTG
Solar/Wind Harmer
0.001
237043AE2-125 C
Solar/Wind Helper
0.16
23585401KL_K28_T16
Solar/Wind Helper
1.133
254304AE2-114 C
Solar/Wind Helper
0.19
254305AE2-115 C
Solar/Wind Helper
0.19
235054AD2-180 GEN
Solar/Wind Helper
1.517
962101AG1-054 GEN
Solar/Wind Helper
0.562
23751201ROTHROCK
Solar/Wind Helper
0.651
253371AE2-315 SEC2
Adder
2.513
270156DARBY CT1
50/50
0.88
270157DARBY CT2
50/50
0.878
270159DARBY CT4
50/50
0.866
270158DARBY CT3
50/50
0.864
270036AE2-216 BAT
50/50
10.087
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
8.348
970373AG2-245 GEN
Solar/Wind Harmer
19.415
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.985
24639705ELKHART HY
Adder
0.203
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.504
965651AG1-433 GEN
Solar/Wind Harmer
2.699
958861AF2-177 GEN
Solar/Wind Harmer
3.969
957891AF2-083 GEN
Solar/Wind Harmer
15.253
945111AF1-176 GEN
Solar/Wind Harmer
16.322
270024AE2-089 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.749
274773LINCOLN ;4U
Adder
10.998
274774LINCOLN ;5U
Adder
10.998
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
10.163
270032AE2-172
Solar/Wind Harmer
6.05
274751CRETE EC ;1U
Adder
10.696
274754CRETE EC ;4U
Adder
10.696
274723RIVER EC ;12
Adder
23.243
274812UNIV PK N;8U
Adder
6.477
274802UNIV PARK;5U
Adder
7.515
276903AD2-071 C
Solar/Wind Harmer
10.022
941551AE2-152 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
39.32
274732ELWOOD EC;7P
Adder
21.052
274674JOLIET 9 ;6U
Adder
19.719
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
3.16
270005AE1-210 C O1
Solar/Wind Harmer
1.926
274745AC1-111 GEN9
Adder
7.116
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.439
274861TOP CROP ;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
6.617
274682WAUKEGAN ;7U
Adder
22.722
274828WAUKEGAN ;BP
Adder
13.956
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
8.357
276882AE2-255 GEN
Solar/Wind Harmer
1.024
971997AH1-543 GEN
Solar/Wind Harmer
4.604
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.435
274872LEEDK;1U
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
20.72
957471AF2-041 GEN
Solar/Wind Harmer
26.094
959081AF2-199 GEN
Solar/Wind Harmer
8.698
971067AG2-660 GEN
Solar/Wind Harmer
2.899
970569AG2-363 GEN
Solar/Wind Harmer
26.046
274822ROCKFORD ;11
Adder
24.417
970819AG2-516 GEN
Solar/Wind Harmer
10.384
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.07
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.607
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.473
274766LEE CO EC;7U
Adder
11.338
276646AC1-214 GEN2
Solar/Wind Harmer
0.337
970773AG2-487 GEN
Solar/Wind Harmer
1.513
276708O09 GEN2
Solar/Wind Harmer
0.302
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
4.655
241813AF1-122_GEN
Solar/Wind Harmer
3.73
971201AH1-060 GEN
Solar/Wind Harmer
1.665
276621W2-048 GEN
Solar/Wind Harmer
0.416
25194608D.CRK4
Adder
1.946
252510AF1-249 C
Solar/Wind Harmer
0.062
252516AE2-318_GEN
Solar/Wind Harmer
9.213
25196808ZIMRHP
Adder
87.807
25196008MFTGT1
Adder
1.606
970091AG2-072 GEN
Adder
14.929
254303AC2-168 GEN
Solar/Wind Helper
0.138
238185AF2-356 C
Solar/Wind Helper
1.967
241966AE1-183 GEN
Solar/Wind Helper
0.22
965911AG1-460 GEN
Solar/Wind Harmer
0.16
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
4.527
943851AF1-053 GEN
Solar/Wind Harmer
3.136
270578AF1-285 GEN2
Solar/Wind Harmer
0.762
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.548
241972AD1-140 GEN
Solar/Wind Harmer
1.127
270432AC2-029 GEN
Solar/Wind Harmer
4.567
270071AF1-092 GEN
Solar/Wind Harmer
18.287
959331AF2-224 GEN
Solar/Wind Harmer
6.656
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.201
247521TR3_G114
Solar/Wind Harmer
0.342
965051AG1-369 GEN
Solar/Wind Harmer
4.708
965041AG1-368 GEN
Solar/Wind Harmer
9.38
24729505KEY G4
Adder
8.674
970031AG2-029 GEN
Solar/Wind Harmer
5.031
963791AG1-232 GEN
Solar/Wind Harmer
12.53
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270007AE1-245 C
Solar/Wind Harmer
0
253372AE2-315 SEC3
Adder
2.513
253372AE2-315 SEC3
Adder
2.513
971771AH1-392 GEN
Solar/Wind Harmer
9.227
270526AF1-158 GEN
Solar/Wind Harmer
0.001
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
5.479
25306009OHH W.
Adder
3.797
970289AG2-191 GEN
Solar/Wind Harmer
1.735
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
10.998
274776LINCOLN ;7U
Adder
10.998
274777LINCOLN ;8U
Adder
10.998
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.472
972037AH1-567 GEN1
Adder
0.236
960591AF2-350 GEN
Solar/Wind Harmer
8.989
274827FISK ;RP
Adder
9.996
274800UNIV PARK;3U
Adder
7.508
274801UNIV PARK;4U
Adder
7.508
972228AH1-698 GEN2
Adder
4.77
972227AH1-698 GEN1
Adder
3.359
24386405FR-21G C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.496
970179AG2-119 GEN
Solar/Wind Harmer
8.005
274687WILL CNTY;4U
Adder
35.839
274687WILL CNTY;4U
Adder
35.839
247536S-71 GEN
Solar/Wind Harmer
0.358
274675JOLIET 29;7U
Adder
39.32
274675JOLIET 29;7U
Adder
37.916
274728ELWOOD EC;5P
Adder
21.052
274731ELWOOD EC;2P
Adder
21.052
274733ELWOOD EC;3P
Adder
21.052
274735ELWOOD EC;4P
Adder
21.052
270340AC2-060 GEN
Solar/Wind Harmer
0.001
970833AG2-524 GEN
Solar/Wind Harmer
9.819
970833AG2-524 GEN
Solar/Wind Harmer
6.546
270543AE2-219 C
Solar/Wind Harmer
6.239
270263AC1-001 GEN
Solar/Wind Harmer
0.889
274744AC1-111 GEN8
Adder
7.116
274746AC1-111 G10
Adder
7.116
971029AG2-637 GEN
Solar/Wind Harmer
13.318
963841AG1-237 GEN
Solar/Wind Harmer
3.839
970073AG2-061 GEN
Solar/Wind Harmer
2.934
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.648
970169AG2-114 GEN
Solar/Wind Harmer
8.734
971675AH1-338 GEN
Solar/Wind Harmer
3.404
971411AH1-196 GEN
Solar/Wind Harmer
13.089
276861AD2-134 GEN
Solar/Wind Harmer
0.155
276863AD2-134 GEN
Solar/Wind Harmer
0.155
971171AH1-044 GEN
Solar/Wind Harmer
17.396
926823AC1-168 GEN
Solar/Wind Harmer
1.477
274823ROCKFORD ;21
Adder
24.24
274856ECOGROVE ;U1
Solar/Wind Harmer
0.202
971681AH1-341 GEN
Solar/Wind Harmer
13.885
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.052
971549AH1-272 GEN
Solar/Wind Harmer
17.758
270356AE2-297 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.302
274877BISHOP HL;1U
Solar/Wind Harmer
0.286
972267AH1-718 GEN
Adder
5.109
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
3.219
946321AF1-296 GEN
Solar/Wind Harmer
4.721
276668AB2-070 GEN1
Solar/Wind Harmer
0.329
276848AB2-070 GEN3
Solar/Wind Harmer
0.328
276849AB2-070 GEN2
Solar/Wind Harmer
0.329
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
10.483
25196108MFTGT2
Adder
1.771
25196108MFTGT2
Adder
1.644
23652301WDPWR_K20
Solar/Wind Helper
0.128
23750501ELLIOTTS
Solar/Wind Helper
0.584
23750701CROSSCHOOL
Solar/Wind Helper
1.083
241997AF1-093 GEN
Solar/Wind Helper
0.22
LAGNLTFEXP_LAGN->PJM
CLTF
15.297
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.659
TVALTFEXP_TVA->PJM
CLTF
7.122
NYPJM->LTFIMP_NY
CLTF
4.811
LGEELTFEXP_LGEE->PJM
CLTF
7.229
WECLTFEXP_WEC->PJM
CLTF
4.742
AG2-052LTFEXP_AG2-052->PJM
LTF
0.3
AH1-155LTFEXP_AH1-155->PJM
LTF
0.45
CBM West 1LTFEXP_CBM-W1->PJM
CBM
162.339
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.047
MECLTFEXP_MEC->PJM
CLTF
18.973
SIGELTFEXP_SIGE->PJM
CLTF
0.561
CPLELTFEXP_CPLE->PJM
CLTF
0.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.622

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-030_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.26 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4152.93
MW Contribution:
23.86
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:96.51 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3997.33
MW Contribution:
19.98
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
19.36
270475AD2-096_GEN
50/50
11.209
961921AG1-034 GEN
Solar/Wind Harmer
25.037
962771AG1-126 GEN
Solar/Wind Harmer
61.099
970153AG2-106 GEN
Solar/Wind Harmer
26.642
270284AF1-227 GEN1
Solar/Wind Harmer
10.292
270287AF1-227 GEN3
Solar/Wind Harmer
3.807
942051AE2-217 GEN
Solar/Wind Harmer
30.068
942871AE2-306 GEN
Solar/Wind Harmer
1.499
270391AF1-285 GEN3
Solar/Wind Harmer
0.769
270518AE2-148 GEN
Solar/Wind Harmer
18.916
253325AC1-069 GEN
Solar/Wind Harmer
1.593
960801AF2-371 GEN
Solar/Wind Harmer
3.709
964871AG1-351 GEN
Solar/Wind Harmer
2.561
276820AF1-078_GEN
Solar/Wind Harmer
2.306
246938BC-WTG3
Solar/Wind Harmer
5.543
270491AE1-102 GEN2
Solar/Wind Harmer
1.811
965021AG1-366 GEN
Solar/Wind Harmer
3.212
270043AE2-236 GEN
Solar/Wind Harmer
7.533
24695305TIMB G C
Solar/Wind Harmer
4.562
958091AF2-103 GEN
Solar/Wind Harmer
0.22
971347AH1-153 GEN
Solar/Wind Harmer
6.782
270063AE2-323 C
Solar/Wind Harmer
2.966
247643Z2-116 C
Solar/Wind Harmer
0.093
944531AF1-118 GEN
Solar/Wind Harmer
46.834
270505AE1-170 C O1
Solar/Wind Harmer
20.011
945111AF1-176 GEN
Solar/Wind Harmer
7.543
24441505OLIV SLR
Solar/Wind Harmer
0.178
270044AE2-322 C
Solar/Wind Harmer
1.744
964401AG1-302 GEN
Solar/Wind Harmer
11.955
270588AE1-091_GEN
Solar/Wind Harmer
14.355
960071AF2-298 GEN
Solar/Wind Harmer
1.969
274772LINCOLN ;3U
Adder
8.061
247642Z2-115 C
Solar/Wind Harmer
0.083
972231SS25-0005
Solar/Wind Harmer
12.318
972181SS23-001
Solar/Wind Harmer
7.699
270156DARBY CT1
50/50
0.855
270157DARBY CT2
50/50
0.853
270166AC1-044 GEN3
50/50
15.769
962761AG1-125 GEN
Solar/Wind Harmer
61.099
970149AG2-104 GEN
Solar/Wind Harmer
37.729
970155AG2-107 GEN
Solar/Wind Harmer
26.642
270520AE2-214 GEN
Solar/Wind Harmer
11.097
270286AF1-227 GEN2
Solar/Wind Harmer
3.807
270391AF1-285 GEN3
Solar/Wind Harmer
1.999
270578AF1-285 GEN2
Solar/Wind Harmer
1.999
270317AD1-130_GEN
Solar/Wind Harmer
5.121
270485AE1-090_GEN
Solar/Wind Harmer
0.968
253333AC1-068 GEN
Solar/Wind Harmer
1.593
971995AH1-542 GEN
Solar/Wind Harmer
16.172
246936BC-WTG1
Solar/Wind Harmer
5.449
270489AE1-102 GEN1
Solar/Wind Harmer
1.811
965421AG1-410 GEN
Solar/Wind Harmer
41.76
965011AG1-365 GEN
Solar/Wind Harmer
13.812
270216AD2-079_GEN
Solar/Wind Harmer
0.811
270258AD1-119 GEN
Solar/Wind Harmer
2.722
24639705ELKHART HY
Adder
0.206
945111AF1-176 GEN
Solar/Wind Harmer
23.801
957891AF2-083 GEN
Solar/Wind Harmer
20.009
270449AD2-020 GEN
Solar/Wind Harmer
3.725
943021AE2-325 GEN
Solar/Wind Harmer
4.842
970373AG2-245 GEN
Solar/Wind Harmer
27.846
270055AF2-134 C O1
Solar/Wind Harmer
3.997
270273AD2-016 GEN
Solar/Wind Harmer
3.511
24441205WTRV SLR C
Solar/Wind Harmer
0.178
958381AF2-132 GEN
Solar/Wind Harmer
11.955
964861AG1-349 GEN
Solar/Wind Harmer
10.357
270297AD1-101 GEN
Solar/Wind Harmer
2.676
971917AH1-482 GEN
Solar/Wind Harmer
11.949
940581AE2-045 GEN
Solar/Wind Harmer
13.384
971605AH1-302 GEN
Solar/Wind Harmer
11.444
965651AG1-433 GEN
Solar/Wind Harmer
7.153
25326309TAIT D
Adder
1.431
958861AF2-177 GEN
Solar/Wind Harmer
14.228
972207SS24-0001
Solar/Wind Harmer
28.659
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
270024AE2-089 GEN
Solar/Wind Harmer
6.086
274751CRETE EC ;1U
Adder
6.344
274754CRETE EC ;4U
Adder
6.344
274723RIVER EC ;12
Adder
23.228
24791305MDL-5G
Solar/Wind Harmer
3.124
274812UNIV PK N;8U
Adder
6.471
945371AF1-202 GEN
Solar/Wind Harmer
8.988
253370AE2-315 SEC1
Adder
2.58
253371AE2-315 SEC2
Adder
2.44
274802UNIV PARK;5U
Adder
7.502
274676JOLIET 29;8U
Adder
39.213
274732ELWOOD EC;7P
Adder
20.991
274674JOLIET 9 ;6U
Adder
19.662
274745AC1-111 GEN9
Adder
7.091
274682WAUKEGAN ;7U
Adder
22.632
274828WAUKEGAN ;BP
Adder
13.9
274822ROCKFORD ;11
Adder
24.287
274761LEE CO EC;2U
Adder
11.403
274766LEE CO EC;7U
Adder
11.269
24728605AND G2
Adder
4.559
23906502RICHG2&3
Adder
1.375
25194608D.CRK4
Adder
1.872
25196008MFTGT1
Adder
1.547
25196808ZIMRHP
Adder
84.175
23920202STRYCT
Adder
1.48
970091AG2-072 GEN
Adder
42.348
254303AC2-168 GEN
Solar/Wind Helper
0.157
241966AE1-183 GEN
Solar/Wind Helper
0.252
238185AF2-356 C
Solar/Wind Helper
1.95
961971AG1-040 GEN
Solar/Wind Helper
0.445
203830AF1-094 GEN
Solar/Wind Helper
0.445
203979AG1-198 GEN
Solar/Wind Helper
0.267
20089026BF_G21_K23
Solar/Wind Helper
0.424
203947AF1-006 C
Solar/Wind Helper
0.484
20084626FORWARD
Solar/Wind Helper
0.322
270594AE1-207 GEN
Solar/Wind Harmer
5.091
270032AE2-172
Solar/Wind Harmer
1.743
274752CRETE EC ;2U
Adder
6.344
274753CRETE EC ;3U
Adder
6.344
274724RIVER EC ;11
Adder
22.955
24690905MDL-1G C
Solar/Wind Harmer
10.402
970781AG2-491 GEN
Solar/Wind Harmer
12.958
276164X3-005 C
Solar/Wind Harmer
0.908
274814UNIV PK N;0U
Adder
6.527
274807UNIV PK N;3U
Adder
6.513
274811UNIV PK N;7U
Adder
6.471
965461AG1-414 GEN
Solar/Wind Harmer
2.929
970289AG2-191 GEN
Solar/Wind Harmer
0.991
253303V4-073 C
Solar/Wind Harmer
0.149
253370AE2-315 SEC1
Adder
2.58
253371AE2-315 SEC2
Adder
2.44
274803UNIV PARK;6U
Adder
7.502
274826FISK ;BP
Adder
14.078
274887GEN-1.85
Solar/Wind Harmer
6.849
276772AC2-154 GEN
Solar/Wind Harmer
3.588
276843GEN-1.7
Solar/Wind Harmer
0.737
276806AD2-047 C O1
Solar/Wind Harmer
13.753
972038AH1-567 GEN2
Adder
0.469
972259AH1-714 GEN
Adder
24.478
274676JOLIET 29;8U
Adder
37.812
274729ELWOOD EC;1P
Adder
20.991
274730ELWOOD EC;6P
Adder
20.991
274734ELWOOD EC;8P
Adder
20.991
274736ELWOOD EC;9P
Adder
20.991
274682WAUKEGAN ;7U
Adder
22.632
274760LEE CO EC;1U
Adder
11.403
274767LEE CO EC;8U
Adder
11.269
24728505AND G1
Adder
4.559
25196608WSDLE5
Adder
9.804
23906502RICHG2&3
Adder
1.375
23906402RICHG1
Adder
1.374
25194608D.CRK4
Adder
1.872
25196008MFTGT1
Adder
1.498
235058AG1-386 C
Solar/Wind Helper
0.454
237048AF1-022 C
Solar/Wind Helper
0.176
237046AF1-021 C
Solar/Wind Helper
0.314
202652Y1-033 WT C
Solar/Wind Helper
0.507
23562501BACKB
Solar/Wind Helper
0.81
962511AG1-100 GEN
Solar/Wind Helper
0.445
964991AG1-363 GEN
Solar/Wind Helper
3.324
270119AB2-067 GEN1
50/50
15.769
270120AB2-067 GEN2
50/50
15.769
270160DARBY CT5
50/50
0.838
270161DARBY CT6
50/50
0.827
270466AD2-091
50/50
9.303
25326509SID D
50/50
1.962
270349AD2-093_GEN
Solar/Wind Harmer
6.996
270471AD2-092_GEN
Solar/Wind Harmer
6.996
270054AF2-122 C O1
Solar/Wind Harmer
6.002
946101AF1-275 GEN
Solar/Wind Harmer
2.774
253383AE2-342_GEN
Solar/Wind Harmer
1.515
942861AE2-305 GEN
Solar/Wind Harmer
12.851
270462AD2-086
Solar/Wind Harmer
11.128
938701AE1-092 GEN
Solar/Wind Harmer
32.666
253378AE2-206_GEN
Solar/Wind Harmer
5.191
246937BC-WTG2
Solar/Wind Harmer
5.449
270246TR4_N_V150
Solar/Wind Harmer
1.17
270247TR4_N_V136
Solar/Wind Harmer
1.17
247607V1-011 GEN
Solar/Wind Harmer
5.389
942801AE2-298 GEN
Solar/Wind Harmer
2.059
970349AG2-230 GEN
Solar/Wind Harmer
20.346
247620Y3-023
Adder
0.617
965681AG1-436 GEN
Solar/Wind Harmer
16.676
965791AG1-447 GEN
Solar/Wind Harmer
8.532
25326109MON D
Adder
1.754
961051AF2-396 GEN
Solar/Wind Harmer
21.131
961051AF2-396 GEN
Solar/Wind Harmer
9.828
270535AF1-215 GEN1
Solar/Wind Harmer
5.996
270536AF1-215 GEN2
Solar/Wind Harmer
5.996
270269AC2-059
Solar/Wind Harmer
12.313
944231AF1-091 GEN
Solar/Wind Harmer
23.698
942221AE2-234 GEN
Solar/Wind Harmer
4.606
944541AF1-119 GEN
Solar/Wind Harmer
5.48
960971AF2-388 GEN
Solar/Wind Harmer
14.305
945421AF1-207 GEN
Solar/Wind Harmer
18.355
957841AF2-078 GEN
Solar/Wind Harmer
7.901
25322209TAIT E
Adder
12.734
25322209TAIT E
Adder
12.447
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
270180AB1-006 GEN1
Solar/Wind Harmer
9.319
24697605MDL-3G C
Solar/Wind Harmer
4.776
24755605MDL-5G
Solar/Wind Harmer
3.124
24697905MDL-4G C
Solar/Wind Harmer
2.973
270181AB1-006 GEN2
Solar/Wind Harmer
0.927
274805UNIV PK N;1U
Adder
6.485
274808UNIV PK N;4U
Adder
6.442
970291AG2-192 GEN
Solar/Wind Harmer
1.679
970291AG2-192 GEN
Solar/Wind Harmer
0.541
253370AE2-315 SEC1
Adder
2.58
274888KELLY CRK;1U
Solar/Wind Harmer
7.586
276776AD2-060 GEN
Solar/Wind Harmer
0.538
958011AF2-095 GEN
Solar/Wind Harmer
18.512
970941AG2-585 GEN
Solar/Wind Harmer
7.071
253349AC2-067 GEN
Solar/Wind Harmer
2.612
253400AC2-068 GEN
Solar/Wind Harmer
1.051
274674JOLIET 9 ;6U
Adder
19.662
247621Y3-024
Adder
0.307
274696ROCKY RD ;4P
Adder
14.362
274695ROCKY RD ;2P
Adder
14.031
274693ROCKY RD ;1P
Adder
13.893
274697ROCKY RD ;3P
Adder
3.812
274683WAUKEGAN ;8U
Adder
26.517
274683WAUKEGAN ;8U
Adder
22.352
972235AH1-702 GEN1
Adder
3.115
972236AH1-702 GEN2
Adder
2.709
274764LEE CO EC;5U
Adder
11.43
274765LEE CO EC;6U
Adder
11.43
274762LEE CO EC;3U
Adder
11.403
274763LEE CO EC;4U
Adder
11.296
25194408D.CRK1
Adder
8.612
25194508D.CRK3
Adder
1.61
254304AE2-114 C
Solar/Wind Helper
0.219
254305AE2-115 C
Solar/Wind Helper
0.219
241967AE2-285_GEN
Solar/Wind Helper
0.634
241801AE1-079 GEN
Solar/Wind Helper
0.248
962101AG1-054 GEN
Solar/Wind Helper
0.64
237043AE2-125 C
Solar/Wind Helper
0.169
946071AF1-272 GEN
Solar/Wind Helper
2.473
23585401KL_K28_T16
Solar/Wind Helper
1.134
23751201ROTHROCK
Solar/Wind Helper
0.663
20083426SW_E13_K22
Solar/Wind Helper
0.05
203835AF1-098 GEN
Solar/Wind Helper
1.767
946381AF1-302 GEN
Solar/Wind Helper
0.204
270159DARBY CT4
50/50
0.841
270158DARBY CT3
50/50
0.839
270036AE2-216 BAT
50/50
10.234
270459AD2-067 GEN
Solar/Wind Harmer
16.44
961821AG1-024 GEN
Solar/Wind Harmer
16.692
241955AC1-078 GEN
Solar/Wind Harmer
12.841
241973AD2-163_GEN1
Solar/Wind Harmer
3.356
241974AD2-163_GEN2
Solar/Wind Harmer
3.356
945631AF1-228 GEN
Solar/Wind Harmer
7.764
270223U2-072_GEN1
Solar/Wind Harmer
3.264
270224U2-072_GEN2
Solar/Wind Harmer
3.264
270227U2-072_GEN3
Solar/Wind Harmer
3.264
270228U2-072_GEN4
Solar/Wind Harmer
3.264
270231U2-072_GEN5
Solar/Wind Harmer
3.264
270578AF1-285 GEN2
Solar/Wind Harmer
0.769
943861AF1-054 GEN
Solar/Wind Harmer
6.343
943851AF1-053 GEN
Solar/Wind Harmer
3.065
270302AB2-170 GEN
Solar/Wind Harmer
13.397
253338AC1-165 GEN
Solar/Wind Harmer
1.652
253343AC1-166 GEN
Solar/Wind Harmer
1.652
241972AD1-140 GEN
Solar/Wind Harmer
6.448
270432AC2-029 GEN
Solar/Wind Harmer
9.905
957201AF2-014 GEN
Solar/Wind Harmer
6.318
270435AC2-044 GEN
Solar/Wind Harmer
2.786
959331AF2-224 GEN
Solar/Wind Harmer
13.812
247521TR3_G114
Solar/Wind Harmer
4.624
270191TR4_S_V150
Solar/Wind Harmer
4.126
965051AG1-369 GEN
Solar/Wind Harmer
6.87
965041AG1-368 GEN
Solar/Wind Harmer
13.691
270071AF1-092 GEN
Solar/Wind Harmer
20.508
270007AE1-245 C
Solar/Wind Harmer
7.361
970031AG2-029 GEN
Solar/Wind Harmer
33.755
971771AH1-392 GEN
Solar/Wind Harmer
12.042
963791AG1-232 GEN
Solar/Wind Harmer
18.061
270526AF1-158 GEN
Solar/Wind Harmer
6.052
960681AF2-359 GEN
Solar/Wind Harmer
5.041
24729505KEY G4
Adder
8.63
270404AC1-167 GEN
Solar/Wind Harmer
1.437
944161AF1-084 GEN
Solar/Wind Harmer
2.932
958391AF2-133 GEN
Solar/Wind Harmer
11.935
959141AF2-205 GEN
Solar/Wind Harmer
7.947
958711AF2-162 GEN
Solar/Wind Harmer
1.324
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
946581AF1-322 GEN
Solar/Wind Harmer
13.258
24691005MDL-2G C
Solar/Wind Harmer
4.791
970289AG2-191 GEN
Solar/Wind Harmer
2.454
971549AH1-272 GEN
Solar/Wind Harmer
23.856
945581AF1-223 GEN
Solar/Wind Harmer
5.843
253372AE2-315 SEC3
Adder
2.44
253372AE2-315 SEC3
Adder
2.44
972037AH1-567 GEN1
Adder
0.235
274827FISK ;RP
Adder
9.977
960591AF2-350 GEN
Solar/Wind Harmer
12.856
274800UNIV PARK;3U
Adder
7.493
274801UNIV PARK;4U
Adder
7.493
972228AH1-698 GEN2
Adder
4.758
972227AH1-698 GEN1
Adder
3.351
25306009OHH W.
Adder
3.692
274687WILL CNTY;4U
Adder
35.747
274687WILL CNTY;4U
Adder
35.747
274675JOLIET 29;7U
Adder
39.213
274675JOLIET 29;7U
Adder
37.813
274728ELWOOD EC;5P
Adder
20.991
274731ELWOOD EC;2P
Adder
20.991
274733ELWOOD EC;3P
Adder
20.991
274735ELWOOD EC;4P
Adder
20.991
274744AC1-111 GEN8
Adder
7.091
274746AC1-111 G10
Adder
7.091
274823ROCKFORD ;21
Adder
24.111
972267AH1-718 GEN
Adder
5.076
25196408WSDLE3
Adder
10.092
25196108MFTGT2
Adder
1.705
25196108MFTGT2
Adder
1.583
241985AE1-237 GEN
Solar/Wind Helper
0.248
241982AE2-343 S C
Solar/Wind Helper
0.222
241997AF1-093 GEN
Solar/Wind Helper
0.252
23652301WDPWR_K20
Solar/Wind Helper
0.135
23750501ELLIOTTS
Solar/Wind Helper
0.602
203846AF2-130 C
Solar/Wind Helper
0.426
203955AF1-039 C O1
Solar/Wind Helper
0.334
20089126CSLMN_L13
Solar/Wind Helper
0.536
20089226LOOKOUT
Solar/Wind Helper
0.534
20088926STNY CRK
Solar/Wind Helper
0.738
LAGNLTFEXP_LAGN->PJM
CLTF
14.706
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.029
TVALTFEXP_TVA->PJM
CLTF
6.774
NYPJM->LTFIMP_NY
CLTF
4.743
LGEELTFEXP_LGEE->PJM
CLTF
6.936
WECLTFEXP_WEC->PJM
CLTF
4.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.299
AH1-155LTFEXP_AH1-155->PJM
LTF
0.449
CBM West 1LTFEXP_CBM-W1->PJM
CBM
168.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.689
MECLTFEXP_MEC->PJM
CLTF
18.731
SIGELTFEXP_SIGE->PJM
CLTF
0.544
CPLELTFEXP_CPLE->PJM
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.936

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-031_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.15 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4148.28
MW Contribution:
23.86
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:96.38 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3992.14
MW Contribution:
19.98
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
15.77
270120AB2-067 GEN2
50/50
15.77
270160DARBY CT5
50/50
0.838
270161DARBY CT6
50/50
0.827
270466AD2-091
50/50
9.305
25326509SID D
50/50
1.962
270349AD2-093_GEN
Solar/Wind Harmer
6.997
270471AD2-092_GEN
Solar/Wind Harmer
6.997
270054AF2-122 C O1
Solar/Wind Harmer
6.003
946101AF1-275 GEN
Solar/Wind Harmer
2.775
253383AE2-342_GEN
Solar/Wind Harmer
1.515
942861AE2-305 GEN
Solar/Wind Harmer
12.854
270462AD2-086
Solar/Wind Harmer
11.13
938701AE1-092 GEN
Solar/Wind Harmer
32.673
253378AE2-206_GEN
Solar/Wind Harmer
5.193
246937BC-WTG2
Solar/Wind Harmer
5.451
270246TR4_N_V150
Solar/Wind Harmer
1.17
270247TR4_N_V136
Solar/Wind Harmer
1.17
247607V1-011 GEN
Solar/Wind Harmer
5.39
942801AE2-298 GEN
Solar/Wind Harmer
2.06
970349AG2-230 GEN
Solar/Wind Harmer
20.351
247620Y3-023
Adder
0.617
965681AG1-436 GEN
Solar/Wind Harmer
16.68
270051AF1-062 GEN
50/50
19.363
270475AD2-096_GEN
50/50
11.21
961921AG1-034 GEN
Solar/Wind Harmer
25.042
962771AG1-126 GEN
Solar/Wind Harmer
61.109
970153AG2-106 GEN
Solar/Wind Harmer
26.647
270284AF1-227 GEN1
Solar/Wind Harmer
10.294
270287AF1-227 GEN3
Solar/Wind Harmer
3.807
942051AE2-217 GEN
Solar/Wind Harmer
30.074
942871AE2-306 GEN
Solar/Wind Harmer
1.499
270391AF1-285 GEN3
Solar/Wind Harmer
0.769
270518AE2-148 GEN
Solar/Wind Harmer
18.92
253325AC1-069 GEN
Solar/Wind Harmer
1.594
960801AF2-371 GEN
Solar/Wind Harmer
3.709
964871AG1-351 GEN
Solar/Wind Harmer
2.561
276820AF1-078_GEN
Solar/Wind Harmer
2.307
246938BC-WTG3
Solar/Wind Harmer
5.545
270491AE1-102 GEN2
Solar/Wind Harmer
1.811
965021AG1-366 GEN
Solar/Wind Harmer
3.213
270043AE2-236 GEN
Solar/Wind Harmer
7.535
24695305TIMB G C
Solar/Wind Harmer
4.564
958091AF2-103 GEN
Solar/Wind Harmer
0.22
971347AH1-153 GEN
Solar/Wind Harmer
6.784
270063AE2-323 C
Solar/Wind Harmer
2.967
247643Z2-116 C
Solar/Wind Harmer
0.093
944531AF1-118 GEN
Solar/Wind Harmer
46.845
270505AE1-170 C O1
Solar/Wind Harmer
20.016
945111AF1-176 GEN
Solar/Wind Harmer
7.545
24441505OLIV SLR
Solar/Wind Harmer
0.178
270044AE2-322 C
Solar/Wind Harmer
1.744
964401AG1-302 GEN
Solar/Wind Harmer
11.958
270588AE1-091_GEN
Solar/Wind Harmer
14.359
960071AF2-298 GEN
Solar/Wind Harmer
1.969
274772LINCOLN ;3U
Adder
8.063
247642Z2-115 C
Solar/Wind Harmer
0.083
972231SS25-0005
Solar/Wind Harmer
12.321
972181SS23-001
Solar/Wind Harmer
7.701
274752CRETE EC ;2U
Adder
6.346
274753CRETE EC ;3U
Adder
6.346
274724RIVER EC ;11
Adder
22.961
24690905MDL-1G C
Solar/Wind Harmer
10.405
970781AG2-491 GEN
Solar/Wind Harmer
12.961
276164X3-005 C
Solar/Wind Harmer
0.908
274814UNIV PK N;0U
Adder
6.529
274807UNIV PK N;3U
Adder
6.515
274811UNIV PK N;7U
Adder
6.472
965461AG1-414 GEN
Solar/Wind Harmer
2.93
970289AG2-191 GEN
Solar/Wind Harmer
0.992
253303V4-073 C
Solar/Wind Harmer
0.149
253370AE2-315 SEC1
Adder
2.581
253371AE2-315 SEC2
Adder
2.441
274803UNIV PARK;6U
Adder
7.503
274826FISK ;BP
Adder
14.081
274887GEN-1.85
Solar/Wind Harmer
6.851
276772AC2-154 GEN
Solar/Wind Harmer
3.589
276843GEN-1.7
Solar/Wind Harmer
0.737
270166AC1-044 GEN3
50/50
15.77
962761AG1-125 GEN
Solar/Wind Harmer
61.109
970149AG2-104 GEN
Solar/Wind Harmer
37.735
970155AG2-107 GEN
Solar/Wind Harmer
26.647
270520AE2-214 GEN
Solar/Wind Harmer
11.099
270286AF1-227 GEN2
Solar/Wind Harmer
3.807
270391AF1-285 GEN3
Solar/Wind Harmer
1.999
270578AF1-285 GEN2
Solar/Wind Harmer
1.999
270317AD1-130_GEN
Solar/Wind Harmer
5.122
270485AE1-090_GEN
Solar/Wind Harmer
0.968
253333AC1-068 GEN
Solar/Wind Harmer
1.594
971995AH1-542 GEN
Solar/Wind Harmer
16.176
246936BC-WTG1
Solar/Wind Harmer
5.451
270489AE1-102 GEN1
Solar/Wind Harmer
1.811
965421AG1-410 GEN
Solar/Wind Harmer
41.769
965011AG1-365 GEN
Solar/Wind Harmer
13.815
270216AD2-079_GEN
Solar/Wind Harmer
0.811
270258AD1-119 GEN
Solar/Wind Harmer
2.723
24639705ELKHART HY
Adder
0.206
945111AF1-176 GEN
Solar/Wind Harmer
23.807
957891AF2-083 GEN
Solar/Wind Harmer
20.013
270449AD2-020 GEN
Solar/Wind Harmer
3.726
943021AE2-325 GEN
Solar/Wind Harmer
4.844
970373AG2-245 GEN
Solar/Wind Harmer
27.853
270055AF2-134 C O1
Solar/Wind Harmer
3.998
270273AD2-016 GEN
Solar/Wind Harmer
3.512
24441205WTRV SLR C
Solar/Wind Harmer
0.178
958381AF2-132 GEN
Solar/Wind Harmer
11.958
964861AG1-349 GEN
Solar/Wind Harmer
10.359
971917AH1-482 GEN
Solar/Wind Harmer
11.952
270297AD1-101 GEN
Solar/Wind Harmer
2.676
940581AE2-045 GEN
Solar/Wind Harmer
13.387
971605AH1-302 GEN
Solar/Wind Harmer
11.446
965651AG1-433 GEN
Solar/Wind Harmer
7.154
25326309TAIT D
Adder
1.432
958861AF2-177 GEN
Solar/Wind Harmer
14.232
972207SS24-0001
Solar/Wind Harmer
28.666
274773LINCOLN ;4U
Adder
8.063
274774LINCOLN ;5U
Adder
8.063
270024AE2-089 GEN
Solar/Wind Harmer
6.087
274751CRETE EC ;1U
Adder
6.346
274754CRETE EC ;4U
Adder
6.346
274723RIVER EC ;12
Adder
23.234
24791305MDL-5G
Solar/Wind Harmer
3.125
274812UNIV PK N;8U
Adder
6.472
945371AF1-202 GEN
Solar/Wind Harmer
8.99
253370AE2-315 SEC1
Adder
2.581
253371AE2-315 SEC2
Adder
2.441
274802UNIV PARK;5U
Adder
7.503
274676JOLIET 29;8U
Adder
39.223
274732ELWOOD EC;7P
Adder
20.997
274674JOLIET 9 ;6U
Adder
19.667
274745AC1-111 GEN9
Adder
7.092
274682WAUKEGAN ;7U
Adder
22.638
274828WAUKEGAN ;BP
Adder
13.903
274822ROCKFORD ;11
Adder
24.293
274761LEE CO EC;2U
Adder
11.406
274766LEE CO EC;7U
Adder
11.272
24728605AND G2
Adder
4.56
23906502RICHG2&3
Adder
1.375
25194608D.CRK4
Adder
1.873
25196008MFTGT1
Adder
1.547
25196808ZIMRHP
Adder
84.199
23920202STRYCT
Adder
1.481
276806AD2-047 C O1
Solar/Wind Harmer
13.756
972038AH1-567 GEN2
Adder
0.469
972259AH1-714 GEN
Adder
24.485
274676JOLIET 29;8U
Adder
37.822
274729ELWOOD EC;1P
Adder
20.997
274730ELWOOD EC;6P
Adder
20.997
274734ELWOOD EC;8P
Adder
20.997
274736ELWOOD EC;9P
Adder
20.997
274682WAUKEGAN ;7U
Adder
22.638
274760LEE CO EC;1U
Adder
11.406
274767LEE CO EC;8U
Adder
11.272
24728505AND G1
Adder
4.56
25196608WSDLE5
Adder
9.806
23906502RICHG2&3
Adder
1.375
23906402RICHG1
Adder
1.375
25194608D.CRK4
Adder
1.873
25196008MFTGT1
Adder
1.498
235058AG1-386 C
Solar/Wind Helper
0.454
237048AF1-022 C
Solar/Wind Helper
0.176
237046AF1-021 C
Solar/Wind Helper
0.314
202652Y1-033 WT C
Solar/Wind Helper
0.506
23562501BACKB
Solar/Wind Helper
0.809
962511AG1-100 GEN
Solar/Wind Helper
0.444
964991AG1-363 GEN
Solar/Wind Helper
3.323
965791AG1-447 GEN
Solar/Wind Harmer
8.534
25326109MON D
Adder
1.754
961051AF2-396 GEN
Solar/Wind Harmer
21.136
961051AF2-396 GEN
Solar/Wind Harmer
9.831
270535AF1-215 GEN1
Solar/Wind Harmer
5.998
270536AF1-215 GEN2
Solar/Wind Harmer
5.998
270269AC2-059
Solar/Wind Harmer
12.316
944231AF1-091 GEN
Solar/Wind Harmer
23.704
942221AE2-234 GEN
Solar/Wind Harmer
4.607
944541AF1-119 GEN
Solar/Wind Harmer
5.481
960971AF2-388 GEN
Solar/Wind Harmer
14.309
945421AF1-207 GEN
Solar/Wind Harmer
18.359
957841AF2-078 GEN
Solar/Wind Harmer
7.903
25322209TAIT E
Adder
12.737
25322209TAIT E
Adder
12.451
274770LINCOLN ;1U
Adder
8.063
274771LINCOLN ;2U
Adder
8.063
270180AB1-006 GEN1
Solar/Wind Harmer
9.321
24697605MDL-3G C
Solar/Wind Harmer
4.778
24755605MDL-5G
Solar/Wind Harmer
3.125
24697905MDL-4G C
Solar/Wind Harmer
2.974
270181AB1-006 GEN2
Solar/Wind Harmer
0.927
274805UNIV PK N;1U
Adder
6.486
274808UNIV PK N;4U
Adder
6.444
970291AG2-192 GEN
Solar/Wind Harmer
1.68
970291AG2-192 GEN
Solar/Wind Harmer
0.541
253370AE2-315 SEC1
Adder
2.581
274888KELLY CRK;1U
Solar/Wind Harmer
7.588
276776AD2-060 GEN
Solar/Wind Harmer
0.538
958011AF2-095 GEN
Solar/Wind Harmer
18.517
970941AG2-585 GEN
Solar/Wind Harmer
7.072
253349AC2-067 GEN
Solar/Wind Harmer
2.613
253400AC2-068 GEN
Solar/Wind Harmer
1.051
274674JOLIET 9 ;6U
Adder
19.667
247621Y3-024
Adder
0.307
274696ROCKY RD ;4P
Adder
14.366
274695ROCKY RD ;2P
Adder
14.034
274693ROCKY RD ;1P
Adder
13.896
274697ROCKY RD ;3P
Adder
3.812
274683WAUKEGAN ;8U
Adder
26.524
274683WAUKEGAN ;8U
Adder
22.358
972235AH1-702 GEN1
Adder
3.116
972236AH1-702 GEN2
Adder
2.709
274764LEE CO EC;5U
Adder
11.433
274765LEE CO EC;6U
Adder
11.433
274762LEE CO EC;3U
Adder
11.406
274763LEE CO EC;4U
Adder
11.299
25194408D.CRK1
Adder
8.615
25194508D.CRK3
Adder
1.611
254304AE2-114 C
Solar/Wind Helper
0.219
254305AE2-115 C
Solar/Wind Helper
0.219
241967AE2-285_GEN
Solar/Wind Helper
0.634
241801AE1-079 GEN
Solar/Wind Helper
0.248
962101AG1-054 GEN
Solar/Wind Helper
0.64
237043AE2-125 C
Solar/Wind Helper
0.169
946071AF1-272 GEN
Solar/Wind Helper
2.472
23585401KL_K28_T16
Solar/Wind Helper
1.134
23751201ROTHROCK
Solar/Wind Helper
0.662
20083426SW_E13_K22
Solar/Wind Helper
0.05
203835AF1-098 GEN
Solar/Wind Helper
1.766
946381AF1-302 GEN
Solar/Wind Helper
0.204
970091AG2-072 GEN
Adder
42.361
254303AC2-168 GEN
Solar/Wind Helper
0.157
241966AE1-183 GEN
Solar/Wind Helper
0.252
238185AF2-356 C
Solar/Wind Helper
1.949
961971AG1-040 GEN
Solar/Wind Helper
0.445
203830AF1-094 GEN
Solar/Wind Helper
0.445
203979AG1-198 GEN
Solar/Wind Helper
0.267
20089026BF_G21_K23
Solar/Wind Helper
0.424
203947AF1-006 C
Solar/Wind Helper
0.484
20084626FORWARD
Solar/Wind Helper
0.322
270594AE1-207 GEN
Solar/Wind Harmer
5.092
270032AE2-172
Solar/Wind Harmer
1.744
270156DARBY CT1
50/50
0.855
270157DARBY CT2
50/50
0.853
270159DARBY CT4
50/50
0.841
270158DARBY CT3
50/50
0.839
270036AE2-216 BAT
50/50
10.236
270459AD2-067 GEN
Solar/Wind Harmer
16.443
961821AG1-024 GEN
Solar/Wind Harmer
16.694
241955AC1-078 GEN
Solar/Wind Harmer
12.844
241973AD2-163_GEN1
Solar/Wind Harmer
3.356
241974AD2-163_GEN2
Solar/Wind Harmer
3.356
945631AF1-228 GEN
Solar/Wind Harmer
7.765
270223U2-072_GEN1
Solar/Wind Harmer
3.264
270224U2-072_GEN2
Solar/Wind Harmer
3.264
270227U2-072_GEN3
Solar/Wind Harmer
3.264
270228U2-072_GEN4
Solar/Wind Harmer
3.264
270231U2-072_GEN5
Solar/Wind Harmer
3.264
270578AF1-285 GEN2
Solar/Wind Harmer
0.769
943861AF1-054 GEN
Solar/Wind Harmer
6.345
943851AF1-053 GEN
Solar/Wind Harmer
3.066
270302AB2-170 GEN
Solar/Wind Harmer
13.399
253338AC1-165 GEN
Solar/Wind Harmer
1.653
253343AC1-166 GEN
Solar/Wind Harmer
1.653
241972AD1-140 GEN
Solar/Wind Harmer
6.45
270432AC2-029 GEN
Solar/Wind Harmer
9.907
957201AF2-014 GEN
Solar/Wind Harmer
6.32
270435AC2-044 GEN
Solar/Wind Harmer
2.787
959331AF2-224 GEN
Solar/Wind Harmer
13.815
247521TR3_G114
Solar/Wind Harmer
4.625
270191TR4_S_V150
Solar/Wind Harmer
4.127
965051AG1-369 GEN
Solar/Wind Harmer
6.871
965041AG1-368 GEN
Solar/Wind Harmer
13.694
270071AF1-092 GEN
Solar/Wind Harmer
20.513
270007AE1-245 C
Solar/Wind Harmer
7.363
970031AG2-029 GEN
Solar/Wind Harmer
33.763
971771AH1-392 GEN
Solar/Wind Harmer
12.045
963791AG1-232 GEN
Solar/Wind Harmer
18.065
270526AF1-158 GEN
Solar/Wind Harmer
6.053
960681AF2-359 GEN
Solar/Wind Harmer
5.042
24729505KEY G4
Adder
8.632
270404AC1-167 GEN
Solar/Wind Harmer
1.438
944161AF1-084 GEN
Solar/Wind Harmer
2.932
958391AF2-133 GEN
Solar/Wind Harmer
11.938
959141AF2-205 GEN
Solar/Wind Harmer
7.949
958711AF2-162 GEN
Solar/Wind Harmer
1.324
274775LINCOLN ;6U
Adder
8.063
274776LINCOLN ;7U
Adder
8.063
274777LINCOLN ;8U
Adder
8.063
946581AF1-322 GEN
Solar/Wind Harmer
13.262
24691005MDL-2G C
Solar/Wind Harmer
4.793
970289AG2-191 GEN
Solar/Wind Harmer
2.455
971549AH1-272 GEN
Solar/Wind Harmer
23.862
945581AF1-223 GEN
Solar/Wind Harmer
5.844
253372AE2-315 SEC3
Adder
2.441
253372AE2-315 SEC3
Adder
2.441
972037AH1-567 GEN1
Adder
0.236
274827FISK ;RP
Adder
9.979
960591AF2-350 GEN
Solar/Wind Harmer
12.859
274800UNIV PARK;3U
Adder
7.495
274801UNIV PARK;4U
Adder
7.495
972228AH1-698 GEN2
Adder
4.76
972227AH1-698 GEN1
Adder
3.351
25306009OHH W.
Adder
3.693
274687WILL CNTY;4U
Adder
35.756
274687WILL CNTY;4U
Adder
35.756
274675JOLIET 29;7U
Adder
39.223
274675JOLIET 29;7U
Adder
37.822
274728ELWOOD EC;5P
Adder
20.997
274731ELWOOD EC;2P
Adder
20.997
274733ELWOOD EC;3P
Adder
20.997
274735ELWOOD EC;4P
Adder
20.997
274744AC1-111 GEN8
Adder
7.092
274746AC1-111 G10
Adder
7.092
274823ROCKFORD ;21
Adder
24.117
972267AH1-718 GEN
Adder
5.077
25196408WSDLE3
Adder
10.095
25196108MFTGT2
Adder
1.705
25196108MFTGT2
Adder
1.584
241985AE1-237 GEN
Solar/Wind Helper
0.247
241982AE2-343 S C
Solar/Wind Helper
0.222
241997AF1-093 GEN
Solar/Wind Helper
0.252
23652301WDPWR_K20
Solar/Wind Helper
0.134
23750501ELLIOTTS
Solar/Wind Helper
0.601
203846AF2-130 C
Solar/Wind Helper
0.426
203955AF1-039 C O1
Solar/Wind Helper
0.334
20089126CSLMN_L13
Solar/Wind Helper
0.536
20089226LOOKOUT
Solar/Wind Helper
0.534
20088926STNY CRK
Solar/Wind Helper
0.738
LAGNLTFEXP_LAGN->PJM
CLTF
14.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.039
TVALTFEXP_TVA->PJM
CLTF
6.778
NYPJM->LTFIMP_NY
CLTF
4.741
LGEELTFEXP_LGEE->PJM
CLTF
6.938
WECLTFEXP_WEC->PJM
CLTF
4.717
AG2-052LTFEXP_AG2-052->PJM
LTF
0.299
AH1-155LTFEXP_AH1-155->PJM
LTF
0.449
CBM West 1LTFEXP_CBM-W1->PJM
CBM
168.737
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.702
MECLTFEXP_MEC->PJM
CLTF
18.736
SIGELTFEXP_SIGE->PJM
CLTF
0.544
CPLELTFEXP_CPLE->PJM
CLTF
0.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.979

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#ADKINS AG1125_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#ADKINS AG1125_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4782.69
MW Contribution:
25.44
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
6.24
270471AD2-092_GEN
Solar/Wind Harmer
6.24
970349AG2-230 GEN
Solar/Wind Harmer
23.509
965681AG1-436 GEN
Solar/Wind Harmer
18.941
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
23.569
961051AF2-396 GEN
Solar/Wind Harmer
10.962
270535AF1-215 GEN1
Solar/Wind Harmer
6.708
270536AF1-215 GEN2
Solar/Wind Harmer
6.708
274770LINCOLN ;1U
Adder
9.097
274771LINCOLN ;2U
Adder
9.097
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
20.2
957841AF2-078 GEN
Solar/Wind Harmer
8.696
274888KELLY CRK;1U
Solar/Wind Harmer
8.462
276776AD2-060 GEN
Solar/Wind Harmer
0.6
958011AF2-095 GEN
Solar/Wind Harmer
20.65
970941AG2-585 GEN
Solar/Wind Harmer
7.887
276897AD1-100 C
Solar/Wind Harmer
66.349
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.622
270180AB1-006 GEN1
Solar/Wind Harmer
10.164
24697605MDL-3G C
Solar/Wind Harmer
5.21
24755605MDL-5G
Solar/Wind Harmer
3.407
24697905MDL-4G C
Solar/Wind Harmer
3.243
270181AB1-006 GEN2
Solar/Wind Harmer
1.011
958481AF2-142 GEN
Solar/Wind Harmer
20.916
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
41.457
958491AF2-143 GEN
Solar/Wind Harmer
20.688
960751AF2-366 GEN
Solar/Wind Harmer
3.956
276901AD2-066 C O1
Solar/Wind Harmer
4.828
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
247621Y3-024
Adder
0.274
270054AF2-122 C O1
Solar/Wind Helper
1.203
24387305FR-4G C
Solar/Wind Harmer
6.907
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
110.681
970153AG2-106 GEN
Solar/Wind Harmer
48.262
270284AF1-227 GEN1
Solar/Wind Harmer
8.999
270287AF1-227 GEN3
Solar/Wind Harmer
3.328
971347AH1-153 GEN
Solar/Wind Harmer
7.836
270043AE2-236 GEN
Solar/Wind Harmer
8.379
24441505OLIV SLR
Solar/Wind Harmer
0.201
247643Z2-116 C
Solar/Wind Harmer
0.105
270505AE1-170 C O1
Solar/Wind Harmer
22.409
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
3.264
964401AG1-302 GEN
Solar/Wind Harmer
13.317
274772LINCOLN ;3U
Adder
9.097
965021AG1-366 GEN
Solar/Wind Harmer
3.4
972231SS25-0005
Solar/Wind Harmer
13.792
972181SS23-001
Solar/Wind Harmer
8.62
274752CRETE EC ;2U
Adder
7.103
274753CRETE EC ;3U
Adder
7.103
274724RIVER EC ;11
Adder
25.717
276164X3-005 C
Solar/Wind Harmer
1.016
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
40.157
274887GEN-1.85
Solar/Wind Harmer
7.64
276772AC2-154 GEN
Solar/Wind Harmer
4.002
276843GEN-1.7
Solar/Wind Harmer
0.822
276806AD2-047 C O1
Solar/Wind Harmer
15.341
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
8.47
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
49.583
24690905MDL-1G C
Solar/Wind Harmer
11.346
970781AG2-491 GEN
Solar/Wind Harmer
14.133
943121AE2-341 GEN
Solar/Wind Harmer
21.118
943591AF1-030 GEN
Solar/Wind Harmer
14.078
274862TOP CROP ;2U
Solar/Wind Harmer
7.05
942871AE2-306 GEN
Solar/Wind Harmer
1.262
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
13.887
274879MINONK ;1U
Solar/Wind Harmer
9.259
276799AD1-013 GEN
Solar/Wind Harmer
3.014
946671AF1-331 GEN
Solar/Wind Harmer
0.571
274855GSG-6 ;RU
Solar/Wind Harmer
5.034
274850MENDOTA H;RU
Solar/Wind Harmer
3.5
276602WESTBROOK C
Solar/Wind Harmer
2.898
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
24386205FR-12G C
Solar/Wind Harmer
5.827
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
22.781
960681AF2-359 GEN
Solar/Wind Harmer
5.725
971771AH1-392 GEN
Solar/Wind Harmer
13.577
270526AF1-158 GEN
Solar/Wind Harmer
6.833
970031AG2-029 GEN
Solar/Wind Harmer
36.912
944161AF1-084 GEN
Solar/Wind Harmer
3.26
274775LINCOLN ;6U
Adder
9.097
274776LINCOLN ;7U
Adder
9.097
274777LINCOLN ;8U
Adder
9.097
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
110.681
970149AG2-104 GEN
Solar/Wind Harmer
68.345
970155AG2-107 GEN
Solar/Wind Harmer
48.262
270286AF1-227 GEN2
Solar/Wind Harmer
3.328
270216AD2-079_GEN
Solar/Wind Harmer
0.91
957891AF2-083 GEN
Solar/Wind Harmer
22.392
970373AG2-245 GEN
Solar/Wind Harmer
31.282
945111AF1-176 GEN
Solar/Wind Harmer
26.576
270449AD2-020 GEN
Solar/Wind Harmer
4.153
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
4.472
958381AF2-132 GEN
Solar/Wind Harmer
13.317
972207SS24-0001
Solar/Wind Harmer
32.343
274773LINCOLN ;4U
Adder
9.097
274774LINCOLN ;5U
Adder
9.097
964861AG1-349 GEN
Solar/Wind Harmer
11.531
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
14.62
24441205WTRV SLR C
Solar/Wind Harmer
0.197
274751CRETE EC ;1U
Adder
7.103
274754CRETE EC ;4U
Adder
7.103
940581AE2-045 GEN
Solar/Wind Harmer
14.817
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
6.478
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
10.884
274847GR RIDGE ;BU
Solar/Wind Harmer
7.156
24791305MDL-5G
Solar/Wind Harmer
3.407
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
8.798
276691AA1-018 GEN1
Solar/Wind Harmer
1.052
274861TOP CROP ;1U
Solar/Wind Harmer
8.443
270391AF1-285 GEN3
Solar/Wind Harmer
1.682
270578AF1-285 GEN2
Solar/Wind Harmer
1.682
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
19.294
276805AD2-038 GEN
Solar/Wind Harmer
7.072
962781AG1-127 GEN
Solar/Wind Harmer
13.111
274872LEEDK;1U
Solar/Wind Harmer
11.294
276882AE2-255 GEN
Solar/Wind Harmer
4.629
971997AH1-543 GEN
Solar/Wind Harmer
21.574
274822ROCKFORD ;11
Adder
26.521
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
24728605AND G2
Adder
4.035
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
24385905FR-11G C
Solar/Wind Harmer
11.302
24386605FR-22G C
Solar/Wind Harmer
5.848
958391AF2-133 GEN
Solar/Wind Harmer
13.265
959331AF2-224 GEN
Solar/Wind Harmer
14.62
959141AF2-205 GEN
Solar/Wind Harmer
8.817
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
14.34
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
276893AG1-478 C
Solar/Wind Harmer
0.78
970833AG2-524 GEN
Solar/Wind Harmer
12.364
970833AG2-524 GEN
Solar/Wind Harmer
5.751
946581AF1-322 GEN
Solar/Wind Harmer
14.461
24691005MDL-2G C
Solar/Wind Harmer
5.226
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270223U2-072_GEN1
Solar/Wind Harmer
2.747
270224U2-072_GEN2
Solar/Wind Harmer
2.747
270227U2-072_GEN3
Solar/Wind Harmer
2.747
270228U2-072_GEN4
Solar/Wind Harmer
2.747
270231U2-072_GEN5
Solar/Wind Harmer
2.747
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
25.443
965041AG1-368 GEN
Solar/Wind Harmer
13.732
274863CRW1-WTG
Solar/Wind Harmer
7.627
274864CRW2-WTG
Solar/Wind Harmer
7.627
971411AH1-196 GEN
Solar/Wind Harmer
20.459
971675AH1-338 GEN
Solar/Wind Harmer
24.548
276861AD2-134 GEN
Solar/Wind Harmer
2.434
276863AD2-134 GEN
Solar/Wind Harmer
2.434
274823ROCKFORD ;21
Adder
26.328
972267AH1-718 GEN
Adder
5.487
24386405FR-21G C
Solar/Wind Harmer
5.848
24387005FR-3G C
Solar/Wind Harmer
5.379
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.48 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4638.62
MW Contribution:
19.81
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274752CRETE EC ;2U
Adder
11.974
274753CRETE EC ;3U
Adder
11.974
274724RIVER EC ;11
Adder
25.717
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
276843GEN-1.7
Solar/Wind Harmer
0.323
276806AD2-047 C O1
Solar/Wind Harmer
5.669
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
44.295
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.86
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
24386205FR-12G C
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
18.917
970571AG2-364 GEN
Solar/Wind Harmer
18.75
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
10.525
270526AF1-158 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274776LINCOLN ;7U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959331AF2-224 GEN
Solar/Wind Harmer
7.14
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
10.005
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
965041AG1-368 GEN
Solar/Wind Harmer
9.581
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
965051AG1-369 GEN
Solar/Wind Harmer
4.689
963791AG1-232 GEN
Solar/Wind Harmer
12.673
926823AC1-168 GEN
Solar/Wind Harmer
1.594
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
963841AG1-237 GEN
Solar/Wind Harmer
3.99
972267AH1-718 GEN
Adder
5.487
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.153
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
93.339
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970155AG2-107 GEN
Solar/Wind Harmer
59.604
957891AF2-083 GEN
Solar/Wind Harmer
17.358
970373AG2-245 GEN
Solar/Wind Harmer
21.825
945111AF1-176 GEN
Solar/Wind Harmer
18.541
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
274754CRETE EC ;4U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.154
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
28.375
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276708O09 GEN2
Solar/Wind Harmer
0.324
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.763
274848CAMPGROVE;RU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
963741AG1-226 GEN
Solar/Wind Harmer
21.176
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.571
276621W2-048 GEN
Solar/Wind Harmer
0.421
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.401
965681AG1-436 GEN
Solar/Wind Harmer
13.215
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
276776AD2-060 GEN
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
14.407
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.66
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
28.923
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.429
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
960611AF2-352 GEN
Solar/Wind Harmer
2.992
970241AG2-163 GEN
Solar/Wind Harmer
5.219
971613AH1-306 GEN
Solar/Wind Harmer
4.231
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
270031AE2-169
Solar/Wind Harmer
4.725
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
276838X2-022 GEN2
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276916AD2-100_GEN
Solar/Wind Harmer
16.976
276911AD2-131_GEN
Solar/Wind Harmer
1.118
945391AF1-204 GEN
Solar/Wind Harmer
8.566
247621Y3-024
Adder
0.274
926881AC1-175 GEN
Solar/Wind Harmer
0
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
970885AG2-551 GEN
Solar/Wind Harmer
2.468
971587AH1-292 GEN
Solar/Wind Harmer
5.199
270054AF2-122 C O1
Solar/Wind Helper
1.203
24695305TIMB G C
Solar/Wind Harmer
0.78
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
246938BC-WTG3
Solar/Wind Harmer
0.328
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
0.995
965091AG1-374 GEN
Solar/Wind Harmer
26.927
959611AF2-252 GEN
Solar/Wind Harmer
2.992
965931AG1-462 GEN
Solar/Wind Harmer
22.694
971087AG2-675 GEN
Solar/Wind Harmer
4.746
971993AH1-541 GEN
Solar/Wind Harmer
3.947
957381AF2-032 GEN
Solar/Wind Harmer
1.851
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
270004AE1-209 GEN
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
6.118
946031AF1-268 GEN
Solar/Wind Harmer
7.675
970193AG2-126 GEN
Solar/Wind Harmer
12.093
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270541AE2-072 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.719
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
247536S-71 GEN
Solar/Wind Harmer
0.309
270543AE2-219 C
Solar/Wind Harmer
5.183
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270356AE2-297 GEN
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#ADKINS AG1125_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#ADKINS AG1125_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.09 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4803.57
MW Contribution:
25.44
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
6.24
270471AD2-092_GEN
Solar/Wind Harmer
6.24
970349AG2-230 GEN
Solar/Wind Harmer
23.509
965681AG1-436 GEN
Solar/Wind Harmer
18.941
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
23.569
961051AF2-396 GEN
Solar/Wind Harmer
10.962
270535AF1-215 GEN1
Solar/Wind Harmer
6.708
270536AF1-215 GEN2
Solar/Wind Harmer
6.708
274770LINCOLN ;1U
Adder
9.097
274771LINCOLN ;2U
Adder
9.097
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
20.2
957841AF2-078 GEN
Solar/Wind Harmer
8.696
274888KELLY CRK;1U
Solar/Wind Harmer
8.462
276776AD2-060 GEN
Solar/Wind Harmer
0.6
958011AF2-095 GEN
Solar/Wind Harmer
20.65
970941AG2-585 GEN
Solar/Wind Harmer
7.887
276897AD1-100 C
Solar/Wind Harmer
66.349
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.622
270180AB1-006 GEN1
Solar/Wind Harmer
10.164
24697605MDL-3G C
Solar/Wind Harmer
5.21
24755605MDL-5G
Solar/Wind Harmer
3.407
24697905MDL-4G C
Solar/Wind Harmer
3.243
270181AB1-006 GEN2
Solar/Wind Harmer
1.011
958481AF2-142 GEN
Solar/Wind Harmer
20.916
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
41.457
958491AF2-143 GEN
Solar/Wind Harmer
20.688
960751AF2-366 GEN
Solar/Wind Harmer
3.956
276901AD2-066 C O1
Solar/Wind Harmer
4.828
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
247621Y3-024
Adder
0.274
270054AF2-122 C O1
Solar/Wind Helper
1.203
24387305FR-4G C
Solar/Wind Harmer
6.907
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
110.681
970153AG2-106 GEN
Solar/Wind Harmer
48.262
270284AF1-227 GEN1
Solar/Wind Harmer
8.999
270287AF1-227 GEN3
Solar/Wind Harmer
3.328
971347AH1-153 GEN
Solar/Wind Harmer
7.836
270043AE2-236 GEN
Solar/Wind Harmer
8.379
24441505OLIV SLR
Solar/Wind Harmer
0.201
247643Z2-116 C
Solar/Wind Harmer
0.105
270505AE1-170 C O1
Solar/Wind Harmer
22.409
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
3.264
964401AG1-302 GEN
Solar/Wind Harmer
13.317
274772LINCOLN ;3U
Adder
9.097
965021AG1-366 GEN
Solar/Wind Harmer
3.4
972231SS25-0005
Solar/Wind Harmer
13.792
972181SS23-001
Solar/Wind Harmer
8.62
274752CRETE EC ;2U
Adder
7.103
274753CRETE EC ;3U
Adder
7.103
274724RIVER EC ;11
Adder
25.717
276164X3-005 C
Solar/Wind Harmer
1.016
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
40.157
274887GEN-1.85
Solar/Wind Harmer
7.64
276772AC2-154 GEN
Solar/Wind Harmer
4.002
276843GEN-1.7
Solar/Wind Harmer
0.822
276806AD2-047 C O1
Solar/Wind Harmer
15.341
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
8.47
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
49.583
24690905MDL-1G C
Solar/Wind Harmer
11.346
970781AG2-491 GEN
Solar/Wind Harmer
14.133
943121AE2-341 GEN
Solar/Wind Harmer
21.118
943591AF1-030 GEN
Solar/Wind Harmer
14.078
274862TOP CROP ;2U
Solar/Wind Harmer
7.05
942871AE2-306 GEN
Solar/Wind Harmer
1.262
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
13.887
274879MINONK ;1U
Solar/Wind Harmer
9.259
276799AD1-013 GEN
Solar/Wind Harmer
3.014
946671AF1-331 GEN
Solar/Wind Harmer
0.571
274855GSG-6 ;RU
Solar/Wind Harmer
5.034
274850MENDOTA H;RU
Solar/Wind Harmer
3.5
276602WESTBROOK C
Solar/Wind Harmer
2.898
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
24386205FR-12G C
Solar/Wind Harmer
5.827
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
110.681
970149AG2-104 GEN
Solar/Wind Harmer
68.345
970155AG2-107 GEN
Solar/Wind Harmer
48.262
270286AF1-227 GEN2
Solar/Wind Harmer
3.328
270216AD2-079_GEN
Solar/Wind Harmer
0.91
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
22.781
960681AF2-359 GEN
Solar/Wind Harmer
5.725
971771AH1-392 GEN
Solar/Wind Harmer
13.577
270526AF1-158 GEN
Solar/Wind Harmer
6.833
970031AG2-029 GEN
Solar/Wind Harmer
36.912
944161AF1-084 GEN
Solar/Wind Harmer
3.26
274775LINCOLN ;6U
Adder
9.097
274776LINCOLN ;7U
Adder
9.097
274777LINCOLN ;8U
Adder
9.097
958391AF2-133 GEN
Solar/Wind Harmer
13.265
957891AF2-083 GEN
Solar/Wind Harmer
22.392
970373AG2-245 GEN
Solar/Wind Harmer
31.282
945111AF1-176 GEN
Solar/Wind Harmer
26.576
270449AD2-020 GEN
Solar/Wind Harmer
4.153
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
4.472
958381AF2-132 GEN
Solar/Wind Harmer
13.317
972207SS24-0001
Solar/Wind Harmer
32.343
274773LINCOLN ;4U
Adder
9.097
274774LINCOLN ;5U
Adder
9.097
964861AG1-349 GEN
Solar/Wind Harmer
11.531
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
14.62
24441205WTRV SLR C
Solar/Wind Harmer
0.197
274751CRETE EC ;1U
Adder
7.103
274754CRETE EC ;4U
Adder
7.103
940581AE2-045 GEN
Solar/Wind Harmer
14.817
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
6.478
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
10.884
274847GR RIDGE ;BU
Solar/Wind Harmer
7.156
24791305MDL-5G
Solar/Wind Harmer
3.407
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
8.798
959331AF2-224 GEN
Solar/Wind Harmer
14.62
959141AF2-205 GEN
Solar/Wind Harmer
8.817
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
14.34
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
276893AG1-478 C
Solar/Wind Harmer
0.78
970833AG2-524 GEN
Solar/Wind Harmer
12.364
970833AG2-524 GEN
Solar/Wind Harmer
5.751
946581AF1-322 GEN
Solar/Wind Harmer
14.461
24691005MDL-2G C
Solar/Wind Harmer
5.226
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270223U2-072_GEN1
Solar/Wind Harmer
2.747
270224U2-072_GEN2
Solar/Wind Harmer
2.747
270227U2-072_GEN3
Solar/Wind Harmer
2.747
270228U2-072_GEN4
Solar/Wind Harmer
2.747
270231U2-072_GEN5
Solar/Wind Harmer
2.747
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
25.443
965041AG1-368 GEN
Solar/Wind Harmer
13.732
274863CRW1-WTG
Solar/Wind Harmer
7.627
274864CRW2-WTG
Solar/Wind Harmer
7.627
971411AH1-196 GEN
Solar/Wind Harmer
20.459
971675AH1-338 GEN
Solar/Wind Harmer
24.548
276861AD2-134 GEN
Solar/Wind Harmer
2.434
276863AD2-134 GEN
Solar/Wind Harmer
2.434
274823ROCKFORD ;21
Adder
26.328
972267AH1-718 GEN
Adder
5.487
24386405FR-21G C
Solar/Wind Harmer
5.848
24387005FR-3G C
Solar/Wind Harmer
5.379
276691AA1-018 GEN1
Solar/Wind Harmer
1.052
274861TOP CROP ;1U
Solar/Wind Harmer
8.443
270391AF1-285 GEN3
Solar/Wind Harmer
1.682
270578AF1-285 GEN2
Solar/Wind Harmer
1.682
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
19.294
276805AD2-038 GEN
Solar/Wind Harmer
7.072
962781AG1-127 GEN
Solar/Wind Harmer
13.111
274872LEEDK;1U
Solar/Wind Harmer
11.294
276882AE2-255 GEN
Solar/Wind Harmer
4.629
971997AH1-543 GEN
Solar/Wind Harmer
21.574
274822ROCKFORD ;11
Adder
26.521
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
24728605AND G2
Adder
4.035
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
24385905FR-11G C
Solar/Wind Harmer
11.302
24386605FR-22G C
Solar/Wind Harmer
5.848
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4659.48
MW Contribution:
19.81
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274752CRETE EC ;2U
Adder
11.974
274753CRETE EC ;3U
Adder
11.974
274724RIVER EC ;11
Adder
25.717
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
276843GEN-1.7
Solar/Wind Harmer
0.323
276806AD2-047 C O1
Solar/Wind Harmer
5.669
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
44.295
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.86
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
24386205FR-12G C
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
18.917
970571AG2-364 GEN
Solar/Wind Harmer
18.75
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
246938BC-WTG3
Solar/Wind Harmer
0.328
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
0.995
965091AG1-374 GEN
Solar/Wind Harmer
26.927
959611AF2-252 GEN
Solar/Wind Harmer
2.992
965931AG1-462 GEN
Solar/Wind Harmer
22.694
971087AG2-675 GEN
Solar/Wind Harmer
4.746
971993AH1-541 GEN
Solar/Wind Harmer
3.947
957381AF2-032 GEN
Solar/Wind Harmer
1.851
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
270004AE1-209 GEN
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
6.118
946031AF1-268 GEN
Solar/Wind Harmer
7.675
970193AG2-126 GEN
Solar/Wind Harmer
12.093
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270541AE2-072 C
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.401
965681AG1-436 GEN
Solar/Wind Harmer
13.215
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
276776AD2-060 GEN
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
14.407
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.66
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
28.923
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.429
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
960611AF2-352 GEN
Solar/Wind Harmer
2.992
970241AG2-163 GEN
Solar/Wind Harmer
5.219
971613AH1-306 GEN
Solar/Wind Harmer
4.231
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
270031AE2-169
Solar/Wind Harmer
4.725
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
276838X2-022 GEN2
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276916AD2-100_GEN
Solar/Wind Harmer
16.976
276911AD2-131_GEN
Solar/Wind Harmer
1.118
945391AF1-204 GEN
Solar/Wind Harmer
8.566
247621Y3-024
Adder
0.274
926881AC1-175 GEN
Solar/Wind Harmer
0
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
970885AG2-551 GEN
Solar/Wind Harmer
2.468
971587AH1-292 GEN
Solar/Wind Harmer
5.199
270054AF2-122 C O1
Solar/Wind Helper
1.203
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
10.525
270526AF1-158 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274776LINCOLN ;7U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959331AF2-224 GEN
Solar/Wind Harmer
7.14
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
10.005
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
965041AG1-368 GEN
Solar/Wind Harmer
9.581
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
965051AG1-369 GEN
Solar/Wind Harmer
4.689
963791AG1-232 GEN
Solar/Wind Harmer
12.673
926823AC1-168 GEN
Solar/Wind Harmer
1.594
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
963841AG1-237 GEN
Solar/Wind Harmer
3.99
972267AH1-718 GEN
Adder
5.487
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
1.719
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
247536S-71 GEN
Solar/Wind Harmer
0.309
270543AE2-219 C
Solar/Wind Harmer
5.183
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270356AE2-297 GEN
Solar/Wind Harmer
0
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
93.339
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970155AG2-107 GEN
Solar/Wind Harmer
59.604
957891AF2-083 GEN
Solar/Wind Harmer
17.358
970373AG2-245 GEN
Solar/Wind Harmer
21.825
945111AF1-176 GEN
Solar/Wind Harmer
18.541
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
274754CRETE EC ;4U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.154
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
28.375
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276708O09 GEN2
Solar/Wind Harmer
0.324
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.763
274848CAMPGROVE;RU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
963741AG1-226 GEN
Solar/Wind Harmer
21.176
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.571
276621W2-048 GEN
Solar/Wind Harmer
0.421
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#707_05MARYSV 765_B1_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#707_05MARYSV 765_B1_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.72 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4604.1
MW Contribution:
25.44
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
6.24
270471AD2-092_GEN
Solar/Wind Harmer
6.24
970349AG2-230 GEN
Solar/Wind Harmer
23.509
965681AG1-436 GEN
Solar/Wind Harmer
18.941
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
23.569
961051AF2-396 GEN
Solar/Wind Harmer
10.962
270535AF1-215 GEN1
Solar/Wind Harmer
6.708
270536AF1-215 GEN2
Solar/Wind Harmer
6.708
274770LINCOLN ;1U
Adder
9.097
274771LINCOLN ;2U
Adder
9.097
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
20.2
957841AF2-078 GEN
Solar/Wind Harmer
8.696
274888KELLY CRK;1U
Solar/Wind Harmer
8.462
276776AD2-060 GEN
Solar/Wind Harmer
0.6
958011AF2-095 GEN
Solar/Wind Harmer
20.65
970941AG2-585 GEN
Solar/Wind Harmer
7.887
276897AD1-100 C
Solar/Wind Harmer
66.349
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.622
270180AB1-006 GEN1
Solar/Wind Harmer
10.164
24697605MDL-3G C
Solar/Wind Harmer
5.21
24755605MDL-5G
Solar/Wind Harmer
3.407
24697905MDL-4G C
Solar/Wind Harmer
3.243
270181AB1-006 GEN2
Solar/Wind Harmer
1.011
958481AF2-142 GEN
Solar/Wind Harmer
20.916
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
41.457
958491AF2-143 GEN
Solar/Wind Harmer
20.688
960751AF2-366 GEN
Solar/Wind Harmer
3.956
276901AD2-066 C O1
Solar/Wind Harmer
4.828
24387305FR-4G C
Solar/Wind Harmer
6.912
966841AG1-555 GEN
Solar/Wind Harmer
3.417
276872AE1-163_GEN1
Solar/Wind Harmer
9.121
276876AE1-163_GEN2
Solar/Wind Harmer
9.121
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
247621Y3-024
Adder
0.274
270054AF2-122 C O1
Solar/Wind Helper
1.203
971341AH1-150 GEN
Solar/Wind Harmer
21.089
971343AH1-151 GEN
Solar/Wind Harmer
21.089
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
270284AF1-227 GEN1
Solar/Wind Harmer
8.999
270287AF1-227 GEN3
Solar/Wind Harmer
3.328
971347AH1-153 GEN
Solar/Wind Harmer
7.836
270043AE2-236 GEN
Solar/Wind Harmer
8.379
24441505OLIV SLR
Solar/Wind Harmer
0.201
247643Z2-116 C
Solar/Wind Harmer
0.105
270505AE1-170 C O1
Solar/Wind Harmer
22.409
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
3.264
964401AG1-302 GEN
Solar/Wind Harmer
13.317
274772LINCOLN ;3U
Adder
9.097
965021AG1-366 GEN
Solar/Wind Harmer
3.4
972231SS25-0005
Solar/Wind Harmer
13.792
972181SS23-001
Solar/Wind Harmer
8.62
274752CRETE EC ;2U
Adder
7.103
274753CRETE EC ;3U
Adder
7.103
274724RIVER EC ;11
Adder
25.717
276164X3-005 C
Solar/Wind Harmer
1.016
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
40.157
274887GEN-1.85
Solar/Wind Harmer
7.64
276772AC2-154 GEN
Solar/Wind Harmer
4.002
276843GEN-1.7
Solar/Wind Harmer
0.822
276806AD2-047 C O1
Solar/Wind Harmer
15.341
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
8.47
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
49.583
24690905MDL-1G C
Solar/Wind Harmer
11.346
970781AG2-491 GEN
Solar/Wind Harmer
14.133
943121AE2-341 GEN
Solar/Wind Harmer
21.118
943591AF1-030 GEN
Solar/Wind Harmer
14.078
274862TOP CROP ;2U
Solar/Wind Harmer
7.05
942871AE2-306 GEN
Solar/Wind Harmer
1.262
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
13.887
274879MINONK ;1U
Solar/Wind Harmer
9.259
276799AD1-013 GEN
Solar/Wind Harmer
3.014
946671AF1-331 GEN
Solar/Wind Harmer
0.571
274855GSG-6 ;RU
Solar/Wind Harmer
5.034
274850MENDOTA H;RU
Solar/Wind Harmer
3.5
276602WESTBROOK C
Solar/Wind Harmer
2.898
24386205FR-12G C
Solar/Wind Harmer
5.831
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
959091AF2-200 GEN
Solar/Wind Harmer
21.089
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
22.781
960681AF2-359 GEN
Solar/Wind Harmer
5.725
971771AH1-392 GEN
Solar/Wind Harmer
13.577
270526AF1-158 GEN
Solar/Wind Harmer
6.833
970031AG2-029 GEN
Solar/Wind Harmer
36.912
944161AF1-084 GEN
Solar/Wind Harmer
3.26
274775LINCOLN ;6U
Adder
9.097
274776LINCOLN ;7U
Adder
9.097
274777LINCOLN ;8U
Adder
9.097
958391AF2-133 GEN
Solar/Wind Harmer
13.265
959331AF2-224 GEN
Solar/Wind Harmer
14.62
959141AF2-205 GEN
Solar/Wind Harmer
8.817
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
14.34
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
276893AG1-478 C
Solar/Wind Harmer
0.78
970833AG2-524 GEN
Solar/Wind Harmer
12.364
970833AG2-524 GEN
Solar/Wind Harmer
5.751
946581AF1-322 GEN
Solar/Wind Harmer
14.461
24691005MDL-2G C
Solar/Wind Harmer
5.226
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
270286AF1-227 GEN2
Solar/Wind Harmer
3.328
270216AD2-079_GEN
Solar/Wind Harmer
0.91
957891AF2-083 GEN
Solar/Wind Harmer
22.392
970373AG2-245 GEN
Solar/Wind Harmer
31.282
945111AF1-176 GEN
Solar/Wind Harmer
26.576
270449AD2-020 GEN
Solar/Wind Harmer
4.153
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
4.472
958381AF2-132 GEN
Solar/Wind Harmer
13.317
972207SS24-0001
Solar/Wind Harmer
32.343
274773LINCOLN ;4U
Adder
9.097
274774LINCOLN ;5U
Adder
9.097
964861AG1-349 GEN
Solar/Wind Harmer
11.531
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
14.62
24441205WTRV SLR C
Solar/Wind Harmer
0.197
274751CRETE EC ;1U
Adder
7.103
274754CRETE EC ;4U
Adder
7.103
940581AE2-045 GEN
Solar/Wind Harmer
14.817
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
6.478
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
10.884
274847GR RIDGE ;BU
Solar/Wind Harmer
7.156
24791305MDL-5G
Solar/Wind Harmer
3.407
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
8.798
276691AA1-018 GEN1
Solar/Wind Harmer
1.052
274861TOP CROP ;1U
Solar/Wind Harmer
8.443
270391AF1-285 GEN3
Solar/Wind Harmer
1.682
270578AF1-285 GEN2
Solar/Wind Harmer
1.682
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
19.294
276805AD2-038 GEN
Solar/Wind Harmer
7.072
962781AG1-127 GEN
Solar/Wind Harmer
13.111
274872LEEDK;1U
Solar/Wind Harmer
11.294
276882AE2-255 GEN
Solar/Wind Harmer
4.629
971997AH1-543 GEN
Solar/Wind Harmer
21.574
24385905FR-11G C
Solar/Wind Harmer
11.309
24386605FR-22G C
Solar/Wind Harmer
5.852
274822ROCKFORD ;11
Adder
26.521
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
24728605AND G2
Adder
4.035
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
957471AF2-041 GEN
Solar/Wind Harmer
31.633
959081AF2-199 GEN
Solar/Wind Harmer
10.544
971067AG2-660 GEN
Solar/Wind Harmer
2.452
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270223U2-072_GEN1
Solar/Wind Harmer
2.747
270224U2-072_GEN2
Solar/Wind Harmer
2.747
270227U2-072_GEN3
Solar/Wind Harmer
2.747
270228U2-072_GEN4
Solar/Wind Harmer
2.747
270231U2-072_GEN5
Solar/Wind Harmer
2.747
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
25.443
965041AG1-368 GEN
Solar/Wind Harmer
13.732
274863CRW1-WTG
Solar/Wind Harmer
7.627
274864CRW2-WTG
Solar/Wind Harmer
7.627
971411AH1-196 GEN
Solar/Wind Harmer
20.459
971675AH1-338 GEN
Solar/Wind Harmer
24.548
276861AD2-134 GEN
Solar/Wind Harmer
2.434
276863AD2-134 GEN
Solar/Wind Harmer
2.434
24386405FR-21G C
Solar/Wind Harmer
5.852
24387005FR-3G C
Solar/Wind Harmer
5.382
276889AE2-281 GEN
Solar/Wind Harmer
2.606
274823ROCKFORD ;21
Adder
26.328
972267AH1-718 GEN
Adder
5.487
971171AH1-044 GEN
Solar/Wind Harmer
21.089
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.7 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5413.79
MW Contribution:
30.94
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
12.247
270144AC1-141 ST1_
50/50
4.015
24641605TWIN BRNCH
50/50
0.032
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
12.161
274776LINCOLN ;7U
50/50
12.161
274777LINCOLN ;8U
50/50
12.161
960681AF2-359 GEN
Solar/Wind Harmer
7.172
971771AH1-392 GEN
Solar/Wind Harmer
17.021
270526AF1-158 GEN
Solar/Wind Harmer
8.553
270071AF1-092 GEN
Solar/Wind Harmer
27.991
944161AF1-084 GEN
Solar/Wind Harmer
4.059
970031AG2-029 GEN
Solar/Wind Harmer
44.798
972037AH1-567 GEN1
Adder
0.327
274827FISK ;RP
Adder
13.882
960591AF2-350 GEN
Solar/Wind Harmer
17.879
274800UNIV PARK;3U
Adder
10.418
274801UNIV PARK;4U
Adder
10.418
972228AH1-698 GEN2
Adder
6.619
972227AH1-698 GEN1
Adder
4.661
274687WILL CNTY;4U
Adder
49.553
274687WILL CNTY;4U
Adder
49.553
274675JOLIET 29;7U
Adder
54.333
274675JOLIET 29;7U
Adder
52.393
274728ELWOOD EC;5P
Adder
29.026
274731ELWOOD EC;2P
Adder
29.025
274733ELWOOD EC;3P
Adder
29.025
274735ELWOOD EC;4P
Adder
29.025
276893AG1-478 C
Solar/Wind Harmer
0.971
970833AG2-524 GEN
Solar/Wind Harmer
15.389
970833AG2-524 GEN
Solar/Wind Harmer
7.158
24729505KEY G4
Adder
11.373
274744AC1-111 GEN8
Adder
9.782
274746AC1-111 G10
Adder
9.782
970073AG2-061 GEN
Solar/Wind Harmer
3.962
958391AF2-133 GEN
Solar/Wind Harmer
15.328
971411AH1-196 GEN
Solar/Wind Harmer
25.298
971675AH1-338 GEN
Solar/Wind Harmer
30.351
276861AD2-134 GEN
Solar/Wind Harmer
3.009
276863AD2-134 GEN
Solar/Wind Harmer
3.009
274863CRW1-WTG
Solar/Wind Harmer
9.359
274864CRW2-WTG
Solar/Wind Harmer
9.359
959141AF2-205 GEN
Solar/Wind Harmer
10.125
971171AH1-044 GEN
Solar/Wind Harmer
33.478
270142AC1-141 CT1_
50/50
4.53
24642205MAYFLWER
50/50
0.069
274772LINCOLN ;3U
50/50
12.161
944961AF1-161 GEN
50/50
5.371
270102X2-052 ST
50/50
3.058
270100X2-052 CT1
50/50
2.825
270101X2-052 CT2
50/50
2.825
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
12.161
274771LINCOLN ;2U
50/50
12.161
247620Y3-023
50/50
0.898
970349AG2-230 GEN
Solar/Wind Harmer
30.128
965681AG1-436 GEN
Solar/Wind Harmer
23.727
965791AG1-447 GEN
Solar/Wind Harmer
12.14
961051AF2-396 GEN
Solar/Wind Harmer
29.38
961051AF2-396 GEN
Solar/Wind Harmer
13.665
274805UNIV PK N;1U
Adder
9.031
274808UNIV PK N;4U
Adder
8.972
274888KELLY CRK;1U
Solar/Wind Harmer
10.551
276776AD2-060 GEN
Solar/Wind Harmer
0.748
958011AF2-095 GEN
Solar/Wind Harmer
25.746
970941AG2-585 GEN
Solar/Wind Harmer
9.834
276897AD1-100 C
Solar/Wind Harmer
82.695
274674JOLIET 9 ;6U
Adder
27.209
276893AG1-478 C
Solar/Wind Harmer
0.774
270535AF1-215 GEN1
Solar/Wind Harmer
7.938
270536AF1-215 GEN2
Solar/Wind Harmer
7.938
274695ROCKY RD ;2P
Adder
19.235
274693ROCKY RD ;1P
Adder
19.046
274697ROCKY RD ;3P
Adder
5.225
274696ROCKY RD ;4P
Adder
19.689
958481AF2-142 GEN
Solar/Wind Harmer
25.905
274683WAUKEGAN ;8U
Adder
36.293
274683WAUKEGAN ;8U
Adder
30.593
962691AG1-118 GEN
Solar/Wind Harmer
51.409
960751AF2-366 GEN
Solar/Wind Harmer
4.903
958491AF2-143 GEN
Solar/Wind Harmer
25.552
276901AD2-066 C O1
Solar/Wind Harmer
5.96
971341AH1-150 GEN
Solar/Wind Harmer
33.478
971343AH1-151 GEN
Solar/Wind Harmer
33.478
276872AE1-163_GEN1
Solar/Wind Harmer
11.22
276876AE1-163_GEN2
Solar/Wind Harmer
11.22
972235AH1-702 GEN1
Adder
4.192
972236AH1-702 GEN2
Adder
3.645
938861AE1-114 GEN
Solar/Wind Harmer
13.462
274764LEE CO EC;5U
Adder
15.248
274765LEE CO EC;6U
Adder
15.248
274762LEE CO EC;3U
Adder
15.212
274763LEE CO EC;4U
Adder
15.069
247621Y3-024
Adder
0.288
270349AD2-093_GEN
Solar/Wind Helper
1.835
270471AD2-092_GEN
Solar/Wind Helper
1.835
946101AF1-275 GEN
Solar/Wind Helper
0.65
270054AF2-122 C O1
Solar/Wind Helper
1.32
962601AG1-109 GEN
50/50
5.371
971347AH1-153 GEN
Solar/Wind Harmer
10.043
270043AE2-236 GEN
Solar/Wind Harmer
10.577
24441505OLIV SLR
Solar/Wind Harmer
0.252
247643Z2-116 C
Solar/Wind Harmer
0.131
270505AE1-170 C O1
Solar/Wind Harmer
28.028
945111AF1-176 GEN
Solar/Wind Harmer
10.497
270063AE2-323 C
Solar/Wind Harmer
3.999
274724RIVER EC ;11
Adder
32.107
972231SS25-0005
Solar/Wind Harmer
17.176
972181SS23-001
Solar/Wind Harmer
10.735
274752CRETE EC ;2U
Adder
8.846
274753CRETE EC ;3U
Adder
8.846
276164X3-005 C
Solar/Wind Harmer
1.268
274814UNIV PK N;0U
Adder
9.09
274807UNIV PK N;3U
Adder
9.07
274811UNIV PK N;7U
Adder
9.011
944531AF1-118 GEN
Solar/Wind Harmer
62.961
970707AG2-453 GEN
Solar/Wind Harmer
50.24
274803UNIV PARK;6U
Adder
10.432
274826FISK ;BP
Adder
19.587
274887GEN-1.85
Solar/Wind Harmer
9.526
276772AC2-154 GEN
Solar/Wind Harmer
4.99
276843GEN-1.7
Solar/Wind Harmer
1.025
276806AD2-047 C O1
Solar/Wind Harmer
19.127
972259AH1-714 GEN
Adder
34.103
972038AH1-567 GEN2
Adder
0.652
939351AE1-166 GEN
Solar/Wind Harmer
10.557
274676JOLIET 29;8U
Adder
52.392
274730ELWOOD EC;6P
Adder
29.026
274734ELWOOD EC;8P
Adder
29.026
274736ELWOOD EC;9P
Adder
29.026
274729ELWOOD EC;1P
Adder
29.025
943121AE2-341 GEN
Solar/Wind Harmer
26.3
943591AF1-030 GEN
Solar/Wind Harmer
17.534
274862TOP CROP ;2U
Solar/Wind Harmer
8.73
274682WAUKEGAN ;7U
Adder
30.998
964401AG1-302 GEN
Solar/Wind Harmer
15.516
276868AE1-113 GEN
Solar/Wind Harmer
17.138
274879MINONK ;1U
Solar/Wind Harmer
11.426
276799AD1-013 GEN
Solar/Wind Harmer
3.727
946671AF1-331 GEN
Solar/Wind Harmer
0.706
274855GSG-6 ;RU
Solar/Wind Harmer
6.223
274850MENDOTA H;RU
Solar/Wind Harmer
4.327
276602WESTBROOK C
Solar/Wind Harmer
3.583
959091AF2-200 GEN
Solar/Wind Harmer
33.478
965021AG1-366 GEN
Solar/Wind Harmer
3.873
970571AG2-364 GEN
Solar/Wind Harmer
32.97
274760LEE CO EC;1U
Adder
15.212
274767LEE CO EC;8U
Adder
15.033
24728505AND G1
Adder
4.166
270284AF1-227 GEN1
Solar/Wind Helper
2.228
270287AF1-227 GEN3
Solar/Wind Helper
0.817
274857EASY ROAD;U1
Solar/Wind Harmer
7.817
24344105CKG2
50/50
15.733
270143AC1-141 CT2_
50/50
4.53
24639705ELKHART HY
50/50
0.302
274773LINCOLN ;4U
50/50
12.161
274774LINCOLN ;5U
50/50
12.161
970521AG2-332 GEN
50/50
21.475
24307105BERRINSP G
50/50
0.04
270216AD2-079_GEN
Solar/Wind Harmer
1.137
957891AF2-083 GEN
Solar/Wind Harmer
27.973
945111AF1-176 GEN
Solar/Wind Harmer
33.122
972207SS24-0001
Solar/Wind Harmer
40.749
270449AD2-020 GEN
Solar/Wind Harmer
5.177
943021AE2-325 GEN
Solar/Wind Harmer
6.729
24441205WTRV SLR C
Solar/Wind Harmer
0.244
274723RIVER EC ;12
Adder
32.481
274751CRETE EC ;1U
Adder
8.846
274754CRETE EC ;4U
Adder
8.846
274812UNIV PK N;8U
Adder
9.011
274802UNIV PARK;5U
Adder
10.432
970373AG2-245 GEN
Solar/Wind Harmer
37.559
941551AE2-152 GEN
Solar/Wind Harmer
8.074
274676JOLIET 29;8U
Adder
54.332
274674JOLIET 9 ;6U
Adder
27.209
274732ELWOOD EC;7P
Adder
29.026
274871GR RIDGE ;2U
Solar/Wind Harmer
13.547
274847GR RIDGE ;BU
Solar/Wind Harmer
8.907
270055AF2-134 C O1
Solar/Wind Harmer
5.292
274745AC1-111 GEN9
Adder
9.782
276694AA1-018 GEN2
Solar/Wind Harmer
10.897
276691AA1-018 GEN1
Solar/Wind Harmer
1.302
274861TOP CROP ;1U
Solar/Wind Harmer
10.456
274682WAUKEGAN ;7U
Adder
30.998
274828WAUKEGAN ;BP
Adder
19.024
958381AF2-132 GEN
Solar/Wind Harmer
15.516
962781AG1-127 GEN
Solar/Wind Harmer
16.251
939401AE1-172 GEN
Solar/Wind Harmer
23.79
964861AG1-349 GEN
Solar/Wind Harmer
13.413
971917AH1-482 GEN
Solar/Wind Harmer
15.475
274872LEEDK;1U
Solar/Wind Harmer
13.992
276805AD2-038 GEN
Solar/Wind Harmer
8.735
276882AE2-255 GEN
Solar/Wind Harmer
5.713
971997AH1-543 GEN
Solar/Wind Harmer
26.614
957471AF2-041 GEN
Solar/Wind Harmer
50.217
959081AF2-199 GEN
Solar/Wind Harmer
16.739
971067AG2-660 GEN
Solar/Wind Harmer
3.893
274822ROCKFORD ;11
Adder
32.73
965011AG1-365 GEN
Solar/Wind Harmer
16.653
970819AG2-516 GEN
Solar/Wind Harmer
19.884
940581AE2-045 GEN
Solar/Wind Harmer
16.88
971605AH1-302 GEN
Solar/Wind Harmer
14.433
970569AG2-363 GEN
Solar/Wind Harmer
49.456
274761LEE CO EC;2U
Adder
15.212
274766LEE CO EC;7U
Adder
15.033
24728605AND G2
Adder
4.166
970091AG2-072 GEN
Adder
67.129
270520AE2-214 GEN
Solar/Wind Helper
2.6
270286AF1-227 GEN2
Solar/Wind Helper
0.817
274858EASY ROAD;U2
Solar/Wind Harmer
7.817
971549AH1-272 GEN
Solar/Wind Harmer
30.938
276889AE2-281 GEN
Solar/Wind Harmer
3.206
274823ROCKFORD ;21
Adder
32.492
959331AF2-224 GEN
Solar/Wind Harmer
16.653
274856ECOGROVE ;U1
Solar/Wind Harmer
5.577
276611AD2-172 GEN
Solar/Wind Harmer
4.231
276612AE2-035 GEN
Solar/Wind Harmer
4.231
926823AC1-168 GEN
Solar/Wind Harmer
7.084
970169AG2-114 GEN
Solar/Wind Harmer
16.447
971681AH1-341 GEN
Solar/Wind Harmer
24.643
972267AH1-718 GEN
Adder
6.732
LAGNLTFEXP_LAGN->PJM
CLTF
12.121
TVALTFEXP_TVA->PJM
CLTF
4.571
NYPJM->LTFIMP_NY
CLTF
2.831
LGEELTFEXP_LGEE->PJM
CLTF
3.802
WECLTFEXP_WEC->PJM
CLTF
6.34
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.778
AG2-052LTFEXP_AG2-052->PJM
LTF
0.395
AH1-155LTFEXP_AH1-155->PJM
LTF
0.593
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.577
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.817
MECLTFEXP_MEC->PJM
CLTF
22.833
SIGELTFEXP_SIGE->PJM
CLTF
0.424
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.518

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.92 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5008.41
MW Contribution:
24.09
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.53
24642205MAYFLWER
50/50
0.069
274772LINCOLN ;3U
50/50
16.554
944961AF1-161 GEN
50/50
5.371
962601AG1-109 GEN
50/50
5.371
971347AH1-153 GEN
Solar/Wind Harmer
7.007
270043AE2-236 GEN
Solar/Wind Harmer
8.609
270505AE1-170 C O1
Solar/Wind Harmer
13.688
945111AF1-176 GEN
Solar/Wind Harmer
10.497
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
32.107
274752CRETE EC ;2U
Adder
14.913
274753CRETE EC ;3U
Adder
14.913
274814UNIV PK N;0U
Adder
9.09
270102X2-052 ST
50/50
3.058
270100X2-052 CT1
50/50
2.825
270101X2-052 CT2
50/50
2.825
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
16.554
274771LINCOLN ;2U
50/50
16.554
247620Y3-023
50/50
0.898
970349AG2-230 GEN
Solar/Wind Harmer
21.02
965681AG1-436 GEN
Solar/Wind Harmer
16.554
965791AG1-447 GEN
Solar/Wind Harmer
12.14
961051AF2-396 GEN
Solar/Wind Harmer
25.827
961051AF2-396 GEN
Solar/Wind Harmer
17.218
274805UNIV PK N;1U
Adder
9.031
274808UNIV PK N;4U
Adder
8.972
274888KELLY CRK;1U
Solar/Wind Harmer
0.727
276776AD2-060 GEN
Solar/Wind Harmer
1.331
958011AF2-095 GEN
Solar/Wind Harmer
17.963
970941AG2-585 GEN
Solar/Wind Harmer
6.861
276897AD1-100 C
Solar/Wind Harmer
31.049
274674JOLIET 9 ;6U
Adder
27.209
276893AG1-478 C
Solar/Wind Harmer
0.821
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274695ROCKY RD ;2P
Adder
19.235
274693ROCKY RD ;1P
Adder
19.046
274697ROCKY RD ;3P
Adder
5.225
274696ROCKY RD ;4P
Adder
19.689
958481AF2-142 GEN
Solar/Wind Harmer
18.073
274683WAUKEGAN ;8U
Adder
36.293
274683WAUKEGAN ;8U
Adder
30.593
962691AG1-118 GEN
Solar/Wind Harmer
35.867
958491AF2-143 GEN
Solar/Wind Harmer
17.827
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
23.357
971343AH1-151 GEN
Solar/Wind Harmer
23.357
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.192
972236AH1-702 GEN2
Adder
3.645
938861AE1-114 GEN
Solar/Wind Harmer
6.492
274764LEE CO EC;5U
Adder
15.248
274765LEE CO EC;6U
Adder
15.248
274762LEE CO EC;3U
Adder
15.212
274763LEE CO EC;4U
Adder
15.069
944541AF1-119 GEN
Solar/Wind Harmer
0.758
960971AF2-388 GEN
Solar/Wind Harmer
6.656
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.814
276645AC1-214 GEN1
Solar/Wind Harmer
0.44
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
3.572
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
3.589
942221AE2-234 GEN
Solar/Wind Harmer
4.268
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.188
944231AF1-091 GEN
Solar/Wind Harmer
23.789
276615X2-022 GEN
Solar/Wind Harmer
0.102
276838X2-022 GEN2
Solar/Wind Harmer
0.554
970291AG2-192 GEN
Solar/Wind Harmer
1.278
970291AG2-192 GEN
Solar/Wind Harmer
0.59
970241AG2-163 GEN
Solar/Wind Harmer
5.718
270031AE2-169
Solar/Wind Harmer
5.389
270599AE1-208 GEN
Solar/Wind Harmer
8.982
971613AH1-306 GEN
Solar/Wind Harmer
4.613
276916AD2-100_GEN
Solar/Wind Harmer
19.611
276911AD2-131_GEN
Solar/Wind Harmer
1.292
270246TR4_N_V150
Solar/Wind Harmer
0.058
270247TR4_N_V136
Solar/Wind Harmer
0.058
24725505WLD G2 C
Solar/Wind Harmer
0
274807UNIV PK N;3U
Adder
9.07
274811UNIV PK N;7U
Adder
9.011
944531AF1-118 GEN
Solar/Wind Harmer
56.246
970707AG2-453 GEN
Solar/Wind Harmer
40.893
274803UNIV PARK;6U
Adder
10.432
274826FISK ;BP
Adder
19.587
274887GEN-1.85
Solar/Wind Harmer
0.324
276843GEN-1.7
Solar/Wind Harmer
0.403
276806AD2-047 C O1
Solar/Wind Harmer
7.069
972259AH1-714 GEN
Adder
34.103
972038AH1-567 GEN2
Adder
0.652
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
52.392
274730ELWOOD EC;6P
Adder
29.026
274734ELWOOD EC;8P
Adder
29.026
274736ELWOOD EC;9P
Adder
29.026
274729ELWOOD EC;1P
Adder
29.025
943121AE2-341 GEN
Solar/Wind Harmer
20.51
943591AF1-030 GEN
Solar/Wind Harmer
13.64
274862TOP CROP ;2U
Solar/Wind Harmer
1.626
274682WAUKEGAN ;7U
Adder
30.998
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
2.364
274879MINONK ;1U
Solar/Wind Harmer
0.493
946671AF1-331 GEN
Solar/Wind Harmer
1.255
274855GSG-6 ;RU
Solar/Wind Harmer
0.429
274850MENDOTA H;RU
Solar/Wind Harmer
0.137
959091AF2-200 GEN
Solar/Wind Harmer
23.357
965021AG1-366 GEN
Solar/Wind Harmer
3.873
970571AG2-364 GEN
Solar/Wind Harmer
23.003
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
15.212
274767LEE CO EC;8U
Adder
15.033
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.946
965931AG1-462 GEN
Solar/Wind Harmer
27.64
971087AG2-675 GEN
Solar/Wind Harmer
5.781
965091AG1-374 GEN
Solar/Wind Harmer
32.301
959611AF2-252 GEN
Solar/Wind Harmer
3.589
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
4.642
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.081
957381AF2-032 GEN
Solar/Wind Harmer
2.147
942481AE2-261 GEN
Solar/Wind Harmer
28.217
270004AE1-209 GEN
Solar/Wind Harmer
1.995
970825AG2-519 GEN
Solar/Wind Harmer
6.765
946031AF1-268 GEN
Solar/Wind Harmer
8.435
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.208
24695305TIMB G C
Solar/Wind Harmer
0.74
970193AG2-126 GEN
Solar/Wind Harmer
13.057
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.166
246938BC-WTG3
Solar/Wind Harmer
0.25
270491AE1-102 GEN2
Solar/Wind Harmer
0.903
270284AF1-227 GEN1
Solar/Wind Helper
2.228
270287AF1-227 GEN3
Solar/Wind Helper
0.817
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.661
270201AC2-176 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
9.248
247621Y3-024
Adder
0.288
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.371
970883AG2-550 GEN
Solar/Wind Harmer
7.415
970885AG2-551 GEN
Solar/Wind Harmer
2.472
971587AH1-292 GEN
Solar/Wind Harmer
5.408
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.28
270349AD2-093_GEN
Solar/Wind Helper
1.835
270471AD2-092_GEN
Solar/Wind Helper
1.835
946101AF1-275 GEN
Solar/Wind Helper
0.65
270054AF2-122 C O1
Solar/Wind Helper
1.32
24344005CKG1
50/50
12.247
270144AC1-141 ST1_
50/50
4.015
24641605TWIN BRNCH
50/50
0.032
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
16.554
274776LINCOLN ;7U
50/50
16.554
274777LINCOLN ;8U
50/50
16.554
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
13.194
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
24.953
970031AG2-029 GEN
Solar/Wind Harmer
6.772
972037AH1-567 GEN1
Adder
0.327
274827FISK ;RP
Adder
13.882
960591AF2-350 GEN
Solar/Wind Harmer
12.474
274800UNIV PARK;3U
Adder
10.418
274801UNIV PARK;4U
Adder
10.418
972228AH1-698 GEN2
Adder
6.619
972227AH1-698 GEN1
Adder
4.661
274687WILL CNTY;4U
Adder
49.553
274687WILL CNTY;4U
Adder
49.553
274675JOLIET 29;7U
Adder
54.333
274675JOLIET 29;7U
Adder
52.393
274728ELWOOD EC;5P
Adder
29.026
274731ELWOOD EC;2P
Adder
29.025
274733ELWOOD EC;3P
Adder
29.025
274735ELWOOD EC;4P
Adder
29.025
970833AG2-524 GEN
Solar/Wind Harmer
13.528
970833AG2-524 GEN
Solar/Wind Harmer
9.019
24729505KEY G4
Adder
11.373
274744AC1-111 GEN8
Adder
9.782
274746AC1-111 G10
Adder
9.782
970073AG2-061 GEN
Solar/Wind Harmer
3.962
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971411AH1-196 GEN
Solar/Wind Harmer
17.649
971675AH1-338 GEN
Solar/Wind Harmer
4.588
276861AD2-134 GEN
Solar/Wind Harmer
0.21
276863AD2-134 GEN
Solar/Wind Harmer
0.21
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
23.357
971549AH1-272 GEN
Solar/Wind Harmer
24.093
274823ROCKFORD ;21
Adder
32.492
959331AF2-224 GEN
Solar/Wind Harmer
8.133
971611AH1-305 GEN
Solar/Wind Harmer
6.874
274856ECOGROVE ;U1
Solar/Wind Harmer
0.27
926823AC1-168 GEN
Solar/Wind Harmer
1.955
970169AG2-114 GEN
Solar/Wind Harmer
11.475
971681AH1-341 GEN
Solar/Wind Harmer
18.454
972267AH1-718 GEN
Adder
6.732
276741O09 GEN1
Solar/Wind Harmer
0.397
274877BISHOP HL;1U
Solar/Wind Harmer
0.372
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
11.542
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.109
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
14.195
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.388
276668AB2-070 GEN1
Solar/Wind Harmer
0.395
276848AB2-070 GEN3
Solar/Wind Harmer
0.393
276849AB2-070 GEN2
Solar/Wind Harmer
0.395
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
9.911
970289AG2-191 GEN
Solar/Wind Harmer
1.868
971609AH1-304 GEN
Solar/Wind Harmer
1.601
247521TR3_G114
Solar/Wind Harmer
0.327
965051AG1-369 GEN
Solar/Wind Harmer
4.503
944221AF1-090 GEN
Solar/Wind Harmer
5.281
964611AG1-324 GEN
Solar/Wind Harmer
3.439
247536S-71 GEN
Solar/Wind Harmer
0.321
270543AE2-219 C
Solar/Wind Harmer
5.19
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.88
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.12
24344105CKG2
50/50
15.733
270143AC1-141 CT2_
50/50
4.53
24639705ELKHART HY
50/50
0.302
274773LINCOLN ;4U
50/50
16.554
274774LINCOLN ;5U
50/50
16.554
970521AG2-332 GEN
50/50
21.475
24307105BERRINSP G
50/50
0.04
957891AF2-083 GEN
Solar/Wind Harmer
21.685
945111AF1-176 GEN
Solar/Wind Harmer
23.109
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.729
274723RIVER EC ;12
Adder
32.481
274751CRETE EC ;1U
Adder
14.913
274754CRETE EC ;4U
Adder
14.913
274812UNIV PK N;8U
Adder
9.011
274802UNIV PARK;5U
Adder
10.432
970373AG2-245 GEN
Solar/Wind Harmer
26.204
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
54.332
274674JOLIET 9 ;6U
Adder
27.209
274732ELWOOD EC;7P
Adder
29.026
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.782
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.958
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
30.998
274828WAUKEGAN ;BP
Adder
19.024
958381AF2-132 GEN
Solar/Wind Harmer
0.002
962781AG1-127 GEN
Solar/Wind Harmer
11.346
939401AE1-172 GEN
Solar/Wind Harmer
8.909
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
15.475
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.379
971997AH1-543 GEN
Solar/Wind Harmer
6.189
957471AF2-041 GEN
Solar/Wind Harmer
35.035
959081AF2-199 GEN
Solar/Wind Harmer
11.678
971067AG2-660 GEN
Solar/Wind Harmer
3.893
274822ROCKFORD ;11
Adder
32.73
965011AG1-365 GEN
Solar/Wind Harmer
11.618
970819AG2-516 GEN
Solar/Wind Harmer
13.872
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
14.433
970569AG2-363 GEN
Solar/Wind Harmer
34.504
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
15.212
274766LEE CO EC;7U
Adder
15.033
965651AG1-433 GEN
Solar/Wind Harmer
3.328
276708O09 GEN2
Solar/Wind Harmer
0.397
276646AC1-214 GEN2
Solar/Wind Harmer
0.44
274848CAMPGROVE;RU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.79
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
15.389
945371AF1-202 GEN
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.492
963741AG1-226 GEN
Solar/Wind Harmer
23.2
270594AE1-207 GEN
Solar/Wind Harmer
10.763
270032AE2-172
Solar/Wind Harmer
6.407
270024AE2-089 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.887
276903AD2-071 C
Solar/Wind Harmer
10.328
270005AE1-210 C O1
Solar/Wind Harmer
1.995
970825AG2-519 GEN
Solar/Wind Harmer
3.188
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.023
24728605AND G2
Adder
4.166
965421AG1-410 GEN
Solar/Wind Harmer
22.186
246936BC-WTG1
Solar/Wind Harmer
0.28
270489AE1-102 GEN1
Solar/Wind Harmer
0.903
970773AG2-487 GEN
Solar/Wind Harmer
1.206
970091AG2-072 GEN
Adder
67.129
270520AE2-214 GEN
Solar/Wind Helper
2.6
270286AF1-227 GEN2
Solar/Wind Helper
0.817
LAGNLTFEXP_LAGN->PJM
CLTF
12.121
TVALTFEXP_TVA->PJM
CLTF
4.571
NYPJM->LTFIMP_NY
CLTF
2.831
LGEELTFEXP_LGEE->PJM
CLTF
3.802
WECLTFEXP_WEC->PJM
CLTF
6.34
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.778
AG2-052LTFEXP_AG2-052->PJM
LTF
0.395
AH1-155LTFEXP_AH1-155->PJM
LTF
0.593
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.577
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.817
MECLTFEXP_MEC->PJM
CLTF
22.833
SIGELTFEXP_SIGE->PJM
CLTF
0.424
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.518

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.91 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4759.65
MW Contribution:
28.24
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:160.5 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6648.0
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.103
24642205MAYFLWER
50/50
0.062
944961AF1-161 GEN
50/50
4.866
962601AG1-109 GEN
50/50
4.866
971347AH1-153 GEN
Solar/Wind Harmer
9.045
270043AE2-236 GEN
Solar/Wind Harmer
9.926
247643Z2-116 C
Solar/Wind Harmer
0.119
944531AF1-118 GEN
Solar/Wind Harmer
59.639
270505AE1-170 C O1
Solar/Wind Harmer
25.381
24441505OLIV SLR
Solar/Wind Harmer
0.226
945111AF1-176 GEN
Solar/Wind Harmer
9.517
270063AE2-323 C
Solar/Wind Harmer
3.694
274772LINCOLN ;3U
Adder
10.256
274724RIVER EC ;11
Adder
28.691
972231SS25-0005
Solar/Wind Harmer
15.332
972181SS23-001
Solar/Wind Harmer
9.583
274752CRETE EC ;2U
Adder
7.897
274753CRETE EC ;3U
Adder
7.897
276164X3-005 C
Solar/Wind Harmer
1.134
274814UNIV PK N;0U
Adder
8.117
274807UNIV PK N;3U
Adder
8.1
274811UNIV PK N;7U
Adder
8.047
970707AG2-453 GEN
Solar/Wind Harmer
44.915
965021AG1-366 GEN
Solar/Wind Harmer
3.724
274803UNIV PARK;6U
Adder
9.32
274826FISK ;BP
Adder
17.501
274887GEN-1.85
Solar/Wind Harmer
8.512
276772AC2-154 GEN
Solar/Wind Harmer
4.459
276843GEN-1.7
Solar/Wind Harmer
0.916
276806AD2-047 C O1
Solar/Wind Harmer
17.091
972259AH1-714 GEN
Adder
30.481
972038AH1-567 GEN2
Adder
0.583
939351AE1-166 GEN
Solar/Wind Harmer
9.436
274676JOLIET 29;8U
Adder
46.808
274729ELWOOD EC;1P
Adder
25.931
274730ELWOOD EC;6P
Adder
25.932
274734ELWOOD EC;8P
Adder
25.932
274736ELWOOD EC;9P
Adder
25.932
943121AE2-341 GEN
Solar/Wind Harmer
23.498
943591AF1-030 GEN
Solar/Wind Harmer
15.666
274862TOP CROP ;2U
Solar/Wind Harmer
7.796
274682WAUKEGAN ;7U
Adder
27.68
276868AE1-113 GEN
Solar/Wind Harmer
15.302
274879MINONK ;1U
Solar/Wind Harmer
10.201
276799AD1-013 GEN
Solar/Wind Harmer
3.327
946671AF1-331 GEN
Solar/Wind Harmer
0.63
274855GSG-6 ;RU
Solar/Wind Harmer
5.555
274850MENDOTA H;RU
Solar/Wind Harmer
3.862
276602WESTBROOK C
Solar/Wind Harmer
3.198
959091AF2-200 GEN
Solar/Wind Harmer
29.877
970571AG2-364 GEN
Solar/Wind Harmer
29.423
274857EASY ROAD;U1
Solar/Wind Harmer
6.987
274760LEE CO EC;1U
Adder
13.568
274767LEE CO EC;8U
Adder
13.409
276603SUBLETTE C
Solar/Wind Harmer
1.527
964401AG1-302 GEN
Solar/Wind Harmer
13.125
24728505AND G1
Adder
3.588
270102X2-052 ST
50/50
2.731
270100X2-052 CT1
50/50
2.523
270101X2-052 CT2
50/50
2.523
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.819
24729405KEY G3
50/50
0.623
24729305KEY G2
50/50
0.612
24729205KEY G1
50/50
0.609
970349AG2-230 GEN
Solar/Wind Harmer
27.136
965681AG1-436 GEN
Solar/Wind Harmer
21.178
965791AG1-447 GEN
Solar/Wind Harmer
10.836
961051AF2-396 GEN
Solar/Wind Harmer
26.623
961051AF2-396 GEN
Solar/Wind Harmer
12.383
274770LINCOLN ;1U
Adder
10.256
274771LINCOLN ;2U
Adder
10.256
274805UNIV PK N;1U
Adder
8.064
274808UNIV PK N;4U
Adder
8.012
274888KELLY CRK;1U
Solar/Wind Harmer
9.428
276776AD2-060 GEN
Solar/Wind Harmer
0.669
958011AF2-095 GEN
Solar/Wind Harmer
23.007
970941AG2-585 GEN
Solar/Wind Harmer
8.787
276897AD1-100 C
Solar/Wind Harmer
73.913
274674JOLIET 9 ;6U
Adder
24.31
276893AG1-478 C
Solar/Wind Harmer
0.691
274695ROCKY RD ;2P
Adder
17.178
274693ROCKY RD ;1P
Adder
17.009
274697ROCKY RD ;3P
Adder
4.667
24344105CKG2
50/50
14.17
270143AC1-141 CT2_
50/50
4.103
24639705ELKHART HY
50/50
0.275
970521AG2-332 GEN
50/50
19.534
24307105BERRINSP G
50/50
0.036
270216AD2-079_GEN
Solar/Wind Harmer
1.031
957891AF2-083 GEN
Solar/Wind Harmer
25.331
945111AF1-176 GEN
Solar/Wind Harmer
30.029
270449AD2-020 GEN
Solar/Wind Harmer
4.69
943021AE2-325 GEN
Solar/Wind Harmer
6.096
972207SS24-0001
Solar/Wind Harmer
36.463
274773LINCOLN ;4U
Adder
10.256
274774LINCOLN ;5U
Adder
10.256
24441205WTRV SLR C
Solar/Wind Harmer
0.221
274723RIVER EC ;12
Adder
29.023
274751CRETE EC ;1U
Adder
7.897
274754CRETE EC ;4U
Adder
7.897
274812UNIV PK N;8U
Adder
8.047
965011AG1-365 GEN
Solar/Wind Harmer
16.013
274802UNIV PARK;5U
Adder
9.32
941551AE2-152 GEN
Solar/Wind Harmer
7.216
274676JOLIET 29;8U
Adder
48.541
24344005CKG1
50/50
11.061
270144AC1-141 ST1_
50/50
3.636
24641605TWIN BRNCH
50/50
0.029
24653605MOTTVILLE
50/50
0.006
24729505KEY G4
50/50
11.404
274674JOLIET 9 ;6U
Adder
24.31
274732ELWOOD EC;7P
Adder
25.932
274871GR RIDGE ;2U
Solar/Wind Harmer
12.105
274847GR RIDGE ;BU
Solar/Wind Harmer
7.959
274745AC1-111 GEN9
Adder
8.739
970373AG2-245 GEN
Solar/Wind Harmer
32.504
276694AA1-018 GEN2
Solar/Wind Harmer
9.731
276691AA1-018 GEN1
Solar/Wind Harmer
1.163
274861TOP CROP ;1U
Solar/Wind Harmer
9.337
274682WAUKEGAN ;7U
Adder
27.68
274828WAUKEGAN ;BP
Adder
16.987
962781AG1-127 GEN
Solar/Wind Harmer
14.51
965651AG1-433 GEN
Solar/Wind Harmer
8.337
939401AE1-172 GEN
Solar/Wind Harmer
21.253
274872LEEDK;1U
Solar/Wind Harmer
12.493
276805AD2-038 GEN
Solar/Wind Harmer
7.799
276882AE2-255 GEN
Solar/Wind Harmer
5.101
971997AH1-543 GEN
Solar/Wind Harmer
23.764
270055AF2-134 C O1
Solar/Wind Harmer
4.53
957471AF2-041 GEN
Solar/Wind Harmer
44.816
959081AF2-199 GEN
Solar/Wind Harmer
14.939
971067AG2-660 GEN
Solar/Wind Harmer
3.474
274822ROCKFORD ;11
Adder
29.205
958861AF2-177 GEN
Solar/Wind Harmer
16.204
970819AG2-516 GEN
Solar/Wind Harmer
17.74
970569AG2-363 GEN
Solar/Wind Harmer
44.135
274858EASY ROAD;U2
Solar/Wind Harmer
6.987
274696ROCKY RD ;4P
Adder
17.583
958481AF2-142 GEN
Solar/Wind Harmer
23.134
274683WAUKEGAN ;8U
Adder
32.408
274683WAUKEGAN ;8U
Adder
27.318
962691AG1-118 GEN
Solar/Wind Harmer
45.905
960751AF2-366 GEN
Solar/Wind Harmer
4.378
944541AF1-119 GEN
Solar/Wind Harmer
6.387
960971AF2-388 GEN
Solar/Wind Harmer
16.674
958491AF2-143 GEN
Solar/Wind Harmer
22.814
276901AD2-066 C O1
Solar/Wind Harmer
5.321
270535AF1-215 GEN1
Solar/Wind Harmer
6.796
270536AF1-215 GEN2
Solar/Wind Harmer
6.796
971341AH1-150 GEN
Solar/Wind Harmer
29.877
971343AH1-151 GEN
Solar/Wind Harmer
29.877
276872AE1-163_GEN1
Solar/Wind Harmer
10.015
276876AE1-163_GEN2
Solar/Wind Harmer
10.015
972235AH1-702 GEN1
Adder
3.74
972236AH1-702 GEN2
Adder
3.253
938861AE1-114 GEN
Solar/Wind Harmer
12.009
274764LEE CO EC;5U
Adder
13.6
274765LEE CO EC;6U
Adder
13.6
274762LEE CO EC;3U
Adder
13.568
274763LEE CO EC;4U
Adder
13.441
247621Y3-024
Adder
0.264
270349AD2-093_GEN
Solar/Wind Helper
1.336
270471AD2-092_GEN
Solar/Wind Helper
1.336
276158O29GEN2
Solar/Wind Harmer
0.363
276157O29GEN1
Solar/Wind Harmer
0.276
971771AH1-392 GEN
Solar/Wind Harmer
15.361
270071AF1-092 GEN
Solar/Wind Harmer
25.452
960681AF2-359 GEN
Solar/Wind Harmer
6.402
270526AF1-158 GEN
Solar/Wind Harmer
7.683
944161AF1-084 GEN
Solar/Wind Harmer
3.677
970031AG2-029 GEN
Solar/Wind Harmer
41.499
274775LINCOLN ;6U
Adder
10.256
274776LINCOLN ;7U
Adder
10.256
274777LINCOLN ;8U
Adder
10.256
959331AF2-224 GEN
Solar/Wind Harmer
16.013
972037AH1-567 GEN1
Adder
0.293
274827FISK ;RP
Adder
12.403
960591AF2-350 GEN
Solar/Wind Harmer
15.977
972228AH1-698 GEN2
Adder
5.915
972227AH1-698 GEN1
Adder
4.165
274800UNIV PARK;3U
Adder
9.308
274801UNIV PARK;4U
Adder
9.308
274687WILL CNTY;4U
Adder
44.271
274687WILL CNTY;4U
Adder
44.271
274675JOLIET 29;7U
Adder
48.542
274675JOLIET 29;7U
Adder
46.808
274728ELWOOD EC;5P
Adder
25.932
274731ELWOOD EC;2P
Adder
25.931
274733ELWOOD EC;3P
Adder
25.931
274735ELWOOD EC;4P
Adder
25.931
276893AG1-478 C
Solar/Wind Harmer
0.867
970833AG2-524 GEN
Solar/Wind Harmer
13.751
970833AG2-524 GEN
Solar/Wind Harmer
6.396
274744AC1-111 GEN8
Adder
8.739
274746AC1-111 G10
Adder
8.739
971549AH1-272 GEN
Solar/Wind Harmer
28.236
958711AF2-162 GEN
Solar/Wind Harmer
1.543
970073AG2-061 GEN
Solar/Wind Harmer
3.537
971411AH1-196 GEN
Solar/Wind Harmer
22.579
971675AH1-338 GEN
Solar/Wind Harmer
27.091
276861AD2-134 GEN
Solar/Wind Harmer
2.686
276863AD2-134 GEN
Solar/Wind Harmer
2.686
274863CRW1-WTG
Solar/Wind Harmer
8.359
274864CRW2-WTG
Solar/Wind Harmer
8.359
971171AH1-044 GEN
Solar/Wind Harmer
29.877
276889AE2-281 GEN
Solar/Wind Harmer
2.861
274823ROCKFORD ;21
Adder
28.993
274856ECOGROVE ;U1
Solar/Wind Harmer
4.976
276611AD2-172 GEN
Solar/Wind Harmer
3.774
276612AE2-035 GEN
Solar/Wind Harmer
3.774
926823AC1-168 GEN
Solar/Wind Harmer
6.322
970169AG2-114 GEN
Solar/Wind Harmer
14.684
971681AH1-341 GEN
Solar/Wind Harmer
21.982
972267AH1-718 GEN
Adder
6.003
274761LEE CO EC;2U
Adder
13.568
274766LEE CO EC;7U
Adder
13.409
958381AF2-132 GEN
Solar/Wind Harmer
13.125
964861AG1-349 GEN
Solar/Wind Harmer
11.331
971917AH1-482 GEN
Solar/Wind Harmer
13.073
970091AG2-072 GEN
Adder
79.856
24728605AND G2
Adder
3.588
LAGNLTFEXP_LAGN->PJM
CLTF
10.079
TVALTFEXP_TVA->PJM
CLTF
3.622
NYPJM->LTFIMP_NY
CLTF
2.521
LGEELTFEXP_LGEE->PJM
CLTF
2.734
WECLTFEXP_WEC->PJM
CLTF
5.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.033
AG2-052LTFEXP_AG2-052->PJM
LTF
0.348
AH1-155LTFEXP_AH1-155->PJM
LTF
0.523
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.48
CBM West 1LTFEXP_CBM-W1->PJM
CBM
172.315
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.846
MECLTFEXP_MEC->PJM
CLTF
20.244
SIGELTFEXP_SIGE->PJM
CLTF
0.357
CBM West 2LTFEXP_CBM-W2->PJM
CBM
93.961

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#2979_05DUMONT 765_B2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2979_05DUMONT 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.85 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4756.98
MW Contribution:
31.7
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.628
24642205MAYFLWER
50/50
0.07
944961AF1-161 GEN
50/50
5.457
962601AG1-109 GEN
50/50
5.457
274772LINCOLN ;3U
50/50
12.299
971347AH1-153 GEN
Solar/Wind Harmer
10.453
270505AE1-170 C O1
Solar/Wind Harmer
28.486
247643Z2-116 C
Solar/Wind Harmer
0.132
24441505OLIV SLR
Solar/Wind Harmer
0.251
945111AF1-176 GEN
Solar/Wind Harmer
10.605
270043AE2-236 GEN
Solar/Wind Harmer
10.177
270063AE2-323 C
Solar/Wind Harmer
3.996
274724RIVER EC ;11
Adder
31.767
970707AG2-453 GEN
Solar/Wind Harmer
50.114
276164X3-005 C
Solar/Wind Harmer
1.256
972231SS25-0005
Solar/Wind Harmer
16.875
972181SS23-001
Solar/Wind Harmer
10.547
274752CRETE EC ;2U
Adder
8.691
274753CRETE EC ;3U
Adder
8.691
972259AH1-714 GEN
Adder
33.857
274814UNIV PK N;0U
Adder
8.953
274807UNIV PK N;3U
Adder
8.934
274811UNIV PK N;7U
Adder
8.876
274826FISK ;BP
Adder
19.361
274887GEN-1.85
Solar/Wind Harmer
9.417
276772AC2-154 GEN
Solar/Wind Harmer
4.933
276843GEN-1.7
Solar/Wind Harmer
1.013
276806AD2-047 C O1
Solar/Wind Harmer
18.909
274803UNIV PARK;6U
Adder
10.298
972038AH1-567 GEN2
Adder
0.644
939351AE1-166 GEN
Solar/Wind Harmer
10.439
274676JOLIET 29;8U
Adder
51.744
274729ELWOOD EC;1P
Adder
28.61
274730ELWOOD EC;6P
Adder
28.611
274734ELWOOD EC;8P
Adder
28.611
274736ELWOOD EC;9P
Adder
28.611
943121AE2-341 GEN
Solar/Wind Harmer
26.017
943591AF1-030 GEN
Solar/Wind Harmer
17.345
944531AF1-118 GEN
Solar/Wind Harmer
60.194
270102X2-052 ST
50/50
3.04
270100X2-052 CT1
50/50
2.808
270101X2-052 CT2
50/50
2.808
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
12.299
274771LINCOLN ;2U
50/50
12.299
247620Y3-023
50/50
0.894
970349AG2-230 GEN
Solar/Wind Harmer
31.359
965681AG1-436 GEN
Solar/Wind Harmer
23.471
965791AG1-447 GEN
Solar/Wind Harmer
12.008
961051AF2-396 GEN
Solar/Wind Harmer
29.784
961051AF2-396 GEN
Solar/Wind Harmer
13.853
274805UNIV PK N;1U
Adder
8.895
274808UNIV PK N;4U
Adder
8.837
274888KELLY CRK;1U
Solar/Wind Harmer
10.43
276776AD2-060 GEN
Solar/Wind Harmer
0.74
958011AF2-095 GEN
Solar/Wind Harmer
25.453
970941AG2-585 GEN
Solar/Wind Harmer
9.721
276897AD1-100 C
Solar/Wind Harmer
81.771
274674JOLIET 9 ;6U
Adder
26.849
276893AG1-478 C
Solar/Wind Harmer
0.762
274695ROCKY RD ;2P
Adder
18.919
274693ROCKY RD ;1P
Adder
18.733
274697ROCKY RD ;3P
Adder
5.139
274696ROCKY RD ;4P
Adder
19.364
274683WAUKEGAN ;8U
Adder
35.646
274683WAUKEGAN ;8U
Adder
30.048
958481AF2-142 GEN
Solar/Wind Harmer
25.309
962691AG1-118 GEN
Solar/Wind Harmer
50.464
960751AF2-366 GEN
Solar/Wind Harmer
4.809
958491AF2-143 GEN
Solar/Wind Harmer
24.84
276901AD2-066 C O1
Solar/Wind Harmer
5.786
971341AH1-150 GEN
Solar/Wind Harmer
32.614
971343AH1-151 GEN
Solar/Wind Harmer
32.614
972235AH1-702 GEN1
Adder
4.077
972236AH1-702 GEN2
Adder
3.545
276872AE1-163_GEN1
Solar/Wind Harmer
10.83
276876AE1-163_GEN2
Solar/Wind Harmer
10.83
938861AE1-114 GEN
Solar/Wind Harmer
13.035
274764LEE CO EC;5U
Adder
14.746
274765LEE CO EC;6U
Adder
14.746
274762LEE CO EC;3U
Adder
14.712
274763LEE CO EC;4U
Adder
14.573
276158O29GEN2
Solar/Wind Harmer
7.743
276157O29GEN1
Solar/Wind Harmer
5.887
276645AC1-214 GEN1
Solar/Wind Harmer
2.044
944541AF1-119 GEN
Solar/Wind Harmer
6.319
960971AF2-388 GEN
Solar/Wind Harmer
16.496
247621Y3-024
Adder
0.245
270349AD2-093_GEN
Solar/Wind Helper
1.46
270471AD2-092_GEN
Solar/Wind Helper
1.46
274682WAUKEGAN ;7U
Adder
30.457
274862TOP CROP ;2U
Solar/Wind Harmer
8.526
965021AG1-366 GEN
Solar/Wind Harmer
3.852
276799AD1-013 GEN
Solar/Wind Harmer
3.64
946671AF1-331 GEN
Solar/Wind Harmer
0.69
274855GSG-6 ;RU
Solar/Wind Harmer
6.077
274850MENDOTA H;RU
Solar/Wind Harmer
4.225
276602WESTBROOK C
Solar/Wind Harmer
3.498
276868AE1-113 GEN
Solar/Wind Harmer
16.642
274879MINONK ;1U
Solar/Wind Harmer
11.095
959091AF2-200 GEN
Solar/Wind Harmer
32.614
970571AG2-364 GEN
Solar/Wind Harmer
31.659
274857EASY ROAD;U1
Solar/Wind Harmer
7.576
274760LEE CO EC;1U
Adder
14.712
274767LEE CO EC;8U
Adder
14.538
276603SUBLETTE C
Solar/Wind Harmer
1.654
274851PROVIDENC;RU
Solar/Wind Harmer
4.346
274849CRESCENT ;1U
Solar/Wind Harmer
2.821
276782AC1-033 GEN
Solar/Wind Harmer
6.044
274878BISHOP HL;2U
Solar/Wind Harmer
5.114
965931AG1-462 GEN
Solar/Wind Harmer
9.79
971087AG2-675 GEN
Solar/Wind Harmer
1.429
24344105CKG2
50/50
17.101
270143AC1-141 CT2_
50/50
4.628
274773LINCOLN ;4U
50/50
12.299
274774LINCOLN ;5U
50/50
12.299
24307105BERRINSP G
50/50
0.04
24639705ELKHART HY
50/50
0.302
247604X1-042
50/50
0.044
970521AG2-332 GEN
50/50
21.337
270216AD2-079_GEN
Solar/Wind Harmer
1.143
957891AF2-083 GEN
Solar/Wind Harmer
28.345
270449AD2-020 GEN
Solar/Wind Harmer
5.259
943021AE2-325 GEN
Solar/Wind Harmer
6.836
945111AF1-176 GEN
Solar/Wind Harmer
33.461
972207SS24-0001
Solar/Wind Harmer
41.211
24441205WTRV SLR C
Solar/Wind Harmer
0.249
24344005CKG1
50/50
12.668
270144AC1-141 ST1_
50/50
4.102
24641605TWIN BRNCH
50/50
0.033
274775LINCOLN ;6U
50/50
12.299
274776LINCOLN ;7U
50/50
12.299
274777LINCOLN ;8U
50/50
12.299
24653605MOTTVILLE
50/50
0.007
971771AH1-392 GEN
Solar/Wind Harmer
17.135
270526AF1-158 GEN
Solar/Wind Harmer
8.541
960681AF2-359 GEN
Solar/Wind Harmer
7.094
944161AF1-084 GEN
Solar/Wind Harmer
4.127
274827FISK ;RP
Adder
13.721
972228AH1-698 GEN2
Adder
6.549
972227AH1-698 GEN1
Adder
4.611
960591AF2-350 GEN
Solar/Wind Harmer
17.675
972037AH1-567 GEN1
Adder
0.323
274800UNIV PARK;3U
Adder
10.294
274801UNIV PARK;4U
Adder
10.294
274687WILL CNTY;4U
Adder
48.934
274687WILL CNTY;4U
Adder
48.934
274675JOLIET 29;7U
Adder
53.662
274675JOLIET 29;7U
Adder
51.745
274728ELWOOD EC;5P
Adder
28.611
274731ELWOOD EC;2P
Adder
28.61
274733ELWOOD EC;3P
Adder
28.61
274735ELWOOD EC;4P
Adder
28.61
970833AG2-524 GEN
Solar/Wind Harmer
15.187
970833AG2-524 GEN
Solar/Wind Harmer
7.064
276893AG1-478 C
Solar/Wind Harmer
0.956
274744AC1-111 GEN8
Adder
9.659
274746AC1-111 G10
Adder
9.659
970031AG2-029 GEN
Solar/Wind Harmer
42.986
971549AH1-272 GEN
Solar/Wind Harmer
31.699
24729505KEY G4
Adder
10.795
959331AF2-224 GEN
Solar/Wind Harmer
16.564
970073AG2-061 GEN
Solar/Wind Harmer
3.851
971411AH1-196 GEN
Solar/Wind Harmer
24.707
971675AH1-338 GEN
Solar/Wind Harmer
29.639
276861AD2-134 GEN
Solar/Wind Harmer
2.938
276863AD2-134 GEN
Solar/Wind Harmer
2.938
971171AH1-044 GEN
Solar/Wind Harmer
32.614
274823ROCKFORD ;21
Adder
31.63
276889AE2-281 GEN
Solar/Wind Harmer
3.094
274863CRW1-WTG
Solar/Wind Harmer
8.971
274864CRW2-WTG
Solar/Wind Harmer
8.971
274856ECOGROVE ;U1
Solar/Wind Harmer
5.414
276611AD2-172 GEN
Solar/Wind Harmer
4.107
276612AE2-035 GEN
Solar/Wind Harmer
4.107
971681AH1-341 GEN
Solar/Wind Harmer
23.859
274723RIVER EC ;12
Adder
32.119
274751CRETE EC ;1U
Adder
8.691
274754CRETE EC ;4U
Adder
8.691
274812UNIV PK N;8U
Adder
8.876
274802UNIV PARK;5U
Adder
10.298
941551AE2-152 GEN
Solar/Wind Harmer
7.984
274676JOLIET 29;8U
Adder
53.66
274674JOLIET 9 ;6U
Adder
26.849
274732ELWOOD EC;7P
Adder
28.611
274871GR RIDGE ;2U
Solar/Wind Harmer
13.369
274847GR RIDGE ;BU
Solar/Wind Harmer
8.79
274745AC1-111 GEN9
Adder
9.659
274682WAUKEGAN ;7U
Adder
30.457
274828WAUKEGAN ;BP
Adder
18.685
276694AA1-018 GEN2
Solar/Wind Harmer
10.646
276691AA1-018 GEN1
Solar/Wind Harmer
1.273
274861TOP CROP ;1U
Solar/Wind Harmer
10.212
962781AG1-127 GEN
Solar/Wind Harmer
15.939
274872LEEDK;1U
Solar/Wind Harmer
13.713
965011AG1-365 GEN
Solar/Wind Harmer
16.564
276805AD2-038 GEN
Solar/Wind Harmer
8.492
939401AE1-172 GEN
Solar/Wind Harmer
23.028
276882AE2-255 GEN
Solar/Wind Harmer
5.548
971997AH1-543 GEN
Solar/Wind Harmer
25.828
957471AF2-041 GEN
Solar/Wind Harmer
48.921
959081AF2-199 GEN
Solar/Wind Harmer
16.307
971067AG2-660 GEN
Solar/Wind Harmer
3.792
274822ROCKFORD ;11
Adder
31.861
970819AG2-516 GEN
Solar/Wind Harmer
19.318
970569AG2-363 GEN
Solar/Wind Harmer
47.488
274858EASY ROAD;U2
Solar/Wind Harmer
7.576
274761LEE CO EC;2U
Adder
14.712
274766LEE CO EC;7U
Adder
14.538
276708O09 GEN2
Solar/Wind Harmer
5.528
970373AG2-245 GEN
Solar/Wind Harmer
32.096
276646AC1-214 GEN2
Solar/Wind Harmer
2.044
965651AG1-433 GEN
Solar/Wind Harmer
8.248
274848CAMPGROVE;RU
Solar/Wind Harmer
9.713
926823AC1-168 GEN
Solar/Wind Harmer
6.797
270071AF1-092 GEN
Solar/Wind Harmer
23.687
970169AG2-114 GEN
Solar/Wind Harmer
15.602
972267AH1-718 GEN
Adder
6.485
276741O09 GEN1
Solar/Wind Harmer
5.528
274877BISHOP HL;1U
Solar/Wind Harmer
5.114
958711AF2-162 GEN
Solar/Wind Harmer
1.527
946321AF1-296 GEN
Solar/Wind Harmer
15.545
LAGNLTFEXP_LAGN->PJM
CLTF
9.08
TVALTFEXP_TVA->PJM
CLTF
3.004
NYPJM->LTFIMP_NY
CLTF
2.551
LGEELTFEXP_LGEE->PJM
CLTF
1.869
WECLTFEXP_WEC->PJM
CLTF
6.165
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.118
AG2-052LTFEXP_AG2-052->PJM
LTF
0.357
AH1-155LTFEXP_AH1-155->PJM
LTF
0.535
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
184.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.09
MECLTFEXP_MEC->PJM
CLTF
20.956
SIGELTFEXP_SIGE->PJM
CLTF
0.265
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.536

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#TEDDY MARY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#TEDDY MARY_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.67 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4583.78
MW Contribution:
27.69
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.706
270100X2-052 CT1
50/50
2.499
270101X2-052 CT2
50/50
2.499
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.805
274770LINCOLN ;1U
50/50
10.763
274771LINCOLN ;2U
50/50
10.763
970349AG2-230 GEN
Solar/Wind Harmer
26.84
965681AG1-436 GEN
Solar/Wind Harmer
20.979
965791AG1-447 GEN
Solar/Wind Harmer
10.734
961051AF2-396 GEN
Solar/Wind Harmer
26.235
961051AF2-396 GEN
Solar/Wind Harmer
12.202
274805UNIV PK N;1U
Adder
7.977
274808UNIV PK N;4U
Adder
7.925
274888KELLY CRK;1U
Solar/Wind Harmer
9.321
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
22.746
970941AG2-585 GEN
Solar/Wind Harmer
8.688
276897AD1-100 C
Solar/Wind Harmer
73.044
274674JOLIET 9 ;6U
Adder
24.034
276893AG1-478 C
Solar/Wind Harmer
0.683
274695ROCKY RD ;2P
Adder
16.985
274693ROCKY RD ;1P
Adder
16.818
274697ROCKY RD ;3P
Adder
4.614
274696ROCKY RD ;4P
Adder
17.386
958481AF2-142 GEN
Solar/Wind Harmer
22.862
274683WAUKEGAN ;8U
Adder
32.045
274683WAUKEGAN ;8U
Adder
27.013
962691AG1-118 GEN
Solar/Wind Harmer
45.388
944541AF1-119 GEN
Solar/Wind Harmer
6.322
960971AF2-388 GEN
Solar/Wind Harmer
16.503
960751AF2-366 GEN
Solar/Wind Harmer
4.328
958491AF2-143 GEN
Solar/Wind Harmer
22.54
270535AF1-215 GEN1
Solar/Wind Harmer
6.807
270536AF1-215 GEN2
Solar/Wind Harmer
6.807
276901AD2-066 C O1
Solar/Wind Harmer
5.256
971341AH1-150 GEN
Solar/Wind Harmer
29.539
971343AH1-151 GEN
Solar/Wind Harmer
29.539
276872AE1-163_GEN1
Solar/Wind Harmer
9.891
276876AE1-163_GEN2
Solar/Wind Harmer
9.891
972235AH1-702 GEN1
Adder
3.698
972236AH1-702 GEN2
Adder
3.216
938861AE1-114 GEN
Solar/Wind Harmer
11.872
274764LEE CO EC;5U
Adder
13.446
274765LEE CO EC;6U
Adder
13.446
274762LEE CO EC;3U
Adder
13.415
274763LEE CO EC;4U
Adder
13.288
247621Y3-024
Adder
0.267
270349AD2-093_GEN
Solar/Wind Helper
1.727
270471AD2-092_GEN
Solar/Wind Helper
1.727
270142AC1-141 CT1_
50/50
4.046
24642205MAYFLWER
50/50
0.061
944961AF1-161 GEN
50/50
4.795
962601AG1-109 GEN
50/50
4.795
274772LINCOLN ;3U
50/50
10.763
971347AH1-153 GEN
Solar/Wind Harmer
8.947
270043AE2-236 GEN
Solar/Wind Harmer
9.698
247643Z2-116 C
Solar/Wind Harmer
0.117
944531AF1-118 GEN
Solar/Wind Harmer
58.604
24441505OLIV SLR
Solar/Wind Harmer
0.224
270505AE1-170 C O1
Solar/Wind Harmer
25.022
945111AF1-176 GEN
Solar/Wind Harmer
9.378
270063AE2-323 C
Solar/Wind Harmer
3.618
274724RIVER EC ;11
Adder
28.38
972231SS25-0005
Solar/Wind Harmer
15.171
972181SS23-001
Solar/Wind Harmer
9.482
274752CRETE EC ;2U
Adder
7.813
274753CRETE EC ;3U
Adder
7.813
276164X3-005 C
Solar/Wind Harmer
1.121
274814UNIV PK N;0U
Adder
8.029
274807UNIV PK N;3U
Adder
8.012
274811UNIV PK N;7U
Adder
7.96
970707AG2-453 GEN
Solar/Wind Harmer
44.413
274826FISK ;BP
Adder
17.307
274803UNIV PARK;6U
Adder
9.216
274887GEN-1.85
Solar/Wind Harmer
8.416
276772AC2-154 GEN
Solar/Wind Harmer
4.408
276843GEN-1.7
Solar/Wind Harmer
0.906
276806AD2-047 C O1
Solar/Wind Harmer
16.898
972259AH1-714 GEN
Adder
30.137
972038AH1-567 GEN2
Adder
0.576
939351AE1-166 GEN
Solar/Wind Harmer
9.325
274676JOLIET 29;8U
Adder
46.282
274729ELWOOD EC;1P
Adder
25.635
274730ELWOOD EC;6P
Adder
25.635
274734ELWOOD EC;8P
Adder
25.635
274736ELWOOD EC;9P
Adder
25.635
943121AE2-341 GEN
Solar/Wind Harmer
23.235
943591AF1-030 GEN
Solar/Wind Harmer
15.49
965021AG1-366 GEN
Solar/Wind Harmer
3.589
274862TOP CROP ;2U
Solar/Wind Harmer
7.704
274682WAUKEGAN ;7U
Adder
27.371
276868AE1-113 GEN
Solar/Wind Harmer
15.116
274879MINONK ;1U
Solar/Wind Harmer
10.078
276799AD1-013 GEN
Solar/Wind Harmer
3.289
946671AF1-331 GEN
Solar/Wind Harmer
0.623
274855GSG-6 ;RU
Solar/Wind Harmer
5.492
274850MENDOTA H;RU
Solar/Wind Harmer
3.818
276602WESTBROOK C
Solar/Wind Harmer
3.162
959091AF2-200 GEN
Solar/Wind Harmer
29.539
964401AG1-302 GEN
Solar/Wind Harmer
13.188
970571AG2-364 GEN
Solar/Wind Harmer
29.049
274857EASY ROAD;U1
Solar/Wind Harmer
6.908
274760LEE CO EC;1U
Adder
13.415
274767LEE CO EC;8U
Adder
13.257
276603SUBLETTE C
Solar/Wind Harmer
1.51
24728505AND G1
Adder
3.684
270284AF1-227 GEN1
Solar/Wind Helper
2.091
270287AF1-227 GEN3
Solar/Wind Helper
0.767
24344005CKG1
50/50
10.917
270144AC1-141 ST1_
50/50
3.585
24641605TWIN BRNCH
50/50
0.029
24653605MOTTVILLE
50/50
0.006
274775LINCOLN ;6U
50/50
10.763
274776LINCOLN ;7U
50/50
10.763
274777LINCOLN ;8U
50/50
10.763
971771AH1-392 GEN
Solar/Wind Harmer
15.164
960681AF2-359 GEN
Solar/Wind Harmer
6.341
270071AF1-092 GEN
Solar/Wind Harmer
25.17
270526AF1-158 GEN
Solar/Wind Harmer
7.595
944161AF1-084 GEN
Solar/Wind Harmer
3.623
24729505KEY G4
Adder
10.579
970031AG2-029 GEN
Solar/Wind Harmer
40.589
274827FISK ;RP
Adder
12.265
972037AH1-567 GEN1
Adder
0.289
960591AF2-350 GEN
Solar/Wind Harmer
15.796
274800UNIV PARK;3U
Adder
9.204
274801UNIV PARK;4U
Adder
9.204
972228AH1-698 GEN2
Adder
5.848
972227AH1-698 GEN1
Adder
4.117
274687WILL CNTY;4U
Adder
43.775
274687WILL CNTY;4U
Adder
43.775
274675JOLIET 29;7U
Adder
47.997
274675JOLIET 29;7U
Adder
46.283
274728ELWOOD EC;5P
Adder
25.635
274731ELWOOD EC;2P
Adder
25.635
274733ELWOOD EC;3P
Adder
25.635
274735ELWOOD EC;4P
Adder
25.635
276893AG1-478 C
Solar/Wind Harmer
0.857
970833AG2-524 GEN
Solar/Wind Harmer
13.592
970833AG2-524 GEN
Solar/Wind Harmer
6.322
274744AC1-111 GEN8
Adder
8.641
274746AC1-111 G10
Adder
8.641
959331AF2-224 GEN
Solar/Wind Harmer
15.433
958711AF2-162 GEN
Solar/Wind Harmer
1.527
970073AG2-061 GEN
Solar/Wind Harmer
3.495
971549AH1-272 GEN
Solar/Wind Harmer
27.69
971411AH1-196 GEN
Solar/Wind Harmer
22.326
971675AH1-338 GEN
Solar/Wind Harmer
26.785
276861AD2-134 GEN
Solar/Wind Harmer
2.656
276863AD2-134 GEN
Solar/Wind Harmer
2.656
971171AH1-044 GEN
Solar/Wind Harmer
29.539
274863CRW1-WTG
Solar/Wind Harmer
8.241
274864CRW2-WTG
Solar/Wind Harmer
8.241
276889AE2-281 GEN
Solar/Wind Harmer
2.826
274823ROCKFORD ;21
Adder
28.668
274856ECOGROVE ;U1
Solar/Wind Harmer
4.92
276611AD2-172 GEN
Solar/Wind Harmer
3.732
276612AE2-035 GEN
Solar/Wind Harmer
3.732
926823AC1-168 GEN
Solar/Wind Harmer
6.24
971681AH1-341 GEN
Solar/Wind Harmer
21.732
970169AG2-114 GEN
Solar/Wind Harmer
14.468
972267AH1-718 GEN
Adder
5.934
958391AF2-133 GEN
Solar/Wind Harmer
0.636
24344105CKG2
50/50
14.029
270143AC1-141 CT2_
50/50
4.046
24639705ELKHART HY
50/50
0.271
970521AG2-332 GEN
50/50
19.228
274773LINCOLN ;4U
50/50
10.763
274774LINCOLN ;5U
50/50
10.763
24307105BERRINSP G
50/50
0.035
270216AD2-079_GEN
Solar/Wind Harmer
1.016
957891AF2-083 GEN
Solar/Wind Harmer
24.972
945111AF1-176 GEN
Solar/Wind Harmer
29.59
270449AD2-020 GEN
Solar/Wind Harmer
4.622
943021AE2-325 GEN
Solar/Wind Harmer
6.007
972207SS24-0001
Solar/Wind Harmer
36.063
24441205WTRV SLR C
Solar/Wind Harmer
0.218
274723RIVER EC ;12
Adder
28.708
274751CRETE EC ;1U
Adder
7.813
274754CRETE EC ;4U
Adder
7.813
274812UNIV PK N;8U
Adder
7.96
274802UNIV PARK;5U
Adder
9.216
941551AE2-152 GEN
Solar/Wind Harmer
7.132
274676JOLIET 29;8U
Adder
47.996
274674JOLIET 9 ;6U
Adder
24.034
274732ELWOOD EC;7P
Adder
25.635
274871GR RIDGE ;2U
Solar/Wind Harmer
11.964
274847GR RIDGE ;BU
Solar/Wind Harmer
7.867
274745AC1-111 GEN9
Adder
8.641
970373AG2-245 GEN
Solar/Wind Harmer
32.464
965011AG1-365 GEN
Solar/Wind Harmer
15.433
276694AA1-018 GEN2
Solar/Wind Harmer
9.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.149
274861TOP CROP ;1U
Solar/Wind Harmer
9.227
274682WAUKEGAN ;7U
Adder
27.371
274828WAUKEGAN ;BP
Adder
16.798
965651AG1-433 GEN
Solar/Wind Harmer
8.251
962781AG1-127 GEN
Solar/Wind Harmer
14.347
274872LEEDK;1U
Solar/Wind Harmer
12.352
939401AE1-172 GEN
Solar/Wind Harmer
20.968
276805AD2-038 GEN
Solar/Wind Harmer
7.705
270055AF2-134 C O1
Solar/Wind Harmer
4.538
276882AE2-255 GEN
Solar/Wind Harmer
5.039
971997AH1-543 GEN
Solar/Wind Harmer
23.469
957471AF2-041 GEN
Solar/Wind Harmer
44.308
959081AF2-199 GEN
Solar/Wind Harmer
14.769
971067AG2-660 GEN
Solar/Wind Harmer
3.435
274822ROCKFORD ;11
Adder
28.877
958861AF2-177 GEN
Solar/Wind Harmer
16.07
970819AG2-516 GEN
Solar/Wind Harmer
17.541
958381AF2-132 GEN
Solar/Wind Harmer
13.188
970569AG2-363 GEN
Solar/Wind Harmer
43.574
964861AG1-349 GEN
Solar/Wind Harmer
11.39
971917AH1-482 GEN
Solar/Wind Harmer
13.141
274858EASY ROAD;U2
Solar/Wind Harmer
6.908
274761LEE CO EC;2U
Adder
13.415
274766LEE CO EC;7U
Adder
13.257
24728605AND G2
Adder
3.684
270286AF1-227 GEN2
Solar/Wind Helper
0.767
LAGNLTFEXP_LAGN->PJM
CLTF
10.559
TVALTFEXP_TVA->PJM
CLTF
3.978
NYPJM->LTFIMP_NY
CLTF
2.548
LGEELTFEXP_LGEE->PJM
CLTF
3.406
WECLTFEXP_WEC->PJM
CLTF
5.594
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.738
AG2-052LTFEXP_AG2-052->PJM
LTF
0.346
AH1-155LTFEXP_AH1-155->PJM
LTF
0.518
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.604
MECLTFEXP_MEC->PJM
CLTF
20.061
SIGELTFEXP_SIGE->PJM
CLTF
0.371
CBM West 2LTFEXP_CBM-W2->PJM
CBM
95.278

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_05MARYSV 765_C2_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_05MARYSV 765_C2_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.05 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4558.43
MW Contribution:
27.79
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.707
270100X2-052 CT1
50/50
2.5
270101X2-052 CT2
50/50
2.5
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.807
274770LINCOLN ;1U
50/50
10.761
274771LINCOLN ;2U
50/50
10.761
970349AG2-230 GEN
Solar/Wind Harmer
26.838
965681AG1-436 GEN
Solar/Wind Harmer
20.988
965791AG1-447 GEN
Solar/Wind Harmer
10.738
961051AF2-396 GEN
Solar/Wind Harmer
26.277
961051AF2-396 GEN
Solar/Wind Harmer
12.222
274805UNIV PK N;1U
Adder
7.979
274808UNIV PK N;4U
Adder
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
9.323
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
22.75
970941AG2-585 GEN
Solar/Wind Harmer
8.689
276897AD1-100 C
Solar/Wind Harmer
73.051
274674JOLIET 9 ;6U
Adder
24.037
276893AG1-478 C
Solar/Wind Harmer
0.683
274695ROCKY RD ;2P
Adder
16.987
274693ROCKY RD ;1P
Adder
16.82
274697ROCKY RD ;3P
Adder
4.615
274696ROCKY RD ;4P
Adder
17.388
958481AF2-142 GEN
Solar/Wind Harmer
22.866
274683WAUKEGAN ;8U
Adder
32.05
274683WAUKEGAN ;8U
Adder
27.017
944541AF1-119 GEN
Solar/Wind Harmer
6.339
960971AF2-388 GEN
Solar/Wind Harmer
16.546
962691AG1-118 GEN
Solar/Wind Harmer
45.394
960751AF2-366 GEN
Solar/Wind Harmer
4.329
958491AF2-143 GEN
Solar/Wind Harmer
22.545
270535AF1-215 GEN1
Solar/Wind Harmer
6.814
270536AF1-215 GEN2
Solar/Wind Harmer
6.814
276901AD2-066 C O1
Solar/Wind Harmer
5.257
971341AH1-150 GEN
Solar/Wind Harmer
29.544
971343AH1-151 GEN
Solar/Wind Harmer
29.544
276872AE1-163_GEN1
Solar/Wind Harmer
9.894
276876AE1-163_GEN2
Solar/Wind Harmer
9.894
972235AH1-702 GEN1
Adder
3.699
972236AH1-702 GEN2
Adder
3.217
938861AE1-114 GEN
Solar/Wind Harmer
11.875
274764LEE CO EC;5U
Adder
13.449
274765LEE CO EC;6U
Adder
13.449
274762LEE CO EC;3U
Adder
13.418
274763LEE CO EC;4U
Adder
13.291
247621Y3-024
Adder
0.269
270349AD2-093_GEN
Solar/Wind Helper
1.483
270471AD2-092_GEN
Solar/Wind Helper
1.483
270142AC1-141 CT1_
50/50
4.051
24642205MAYFLWER
50/50
0.062
944961AF1-161 GEN
50/50
4.803
962601AG1-109 GEN
50/50
4.803
274772LINCOLN ;3U
50/50
10.761
971347AH1-153 GEN
Solar/Wind Harmer
8.946
270043AE2-236 GEN
Solar/Wind Harmer
9.722
247643Z2-116 C
Solar/Wind Harmer
0.117
944531AF1-118 GEN
Solar/Wind Harmer
58.718
24441505OLIV SLR
Solar/Wind Harmer
0.224
270505AE1-170 C O1
Solar/Wind Harmer
25.058
945111AF1-176 GEN
Solar/Wind Harmer
9.393
270063AE2-323 C
Solar/Wind Harmer
3.63
274724RIVER EC ;11
Adder
28.386
972231SS25-0005
Solar/Wind Harmer
15.175
972181SS23-001
Solar/Wind Harmer
9.485
274752CRETE EC ;2U
Adder
7.816
274753CRETE EC ;3U
Adder
7.816
276164X3-005 C
Solar/Wind Harmer
1.121
274814UNIV PK N;0U
Adder
8.031
274807UNIV PK N;3U
Adder
8.014
274811UNIV PK N;7U
Adder
7.962
970707AG2-453 GEN
Solar/Wind Harmer
44.413
274826FISK ;BP
Adder
17.309
274803UNIV PARK;6U
Adder
9.218
274887GEN-1.85
Solar/Wind Harmer
8.417
276772AC2-154 GEN
Solar/Wind Harmer
4.409
276843GEN-1.7
Solar/Wind Harmer
0.906
276806AD2-047 C O1
Solar/Wind Harmer
16.9
972259AH1-714 GEN
Adder
30.138
972038AH1-567 GEN2
Adder
0.576
939351AE1-166 GEN
Solar/Wind Harmer
9.326
274676JOLIET 29;8U
Adder
46.288
274730ELWOOD EC;6P
Adder
25.639
274734ELWOOD EC;8P
Adder
25.639
274736ELWOOD EC;9P
Adder
25.639
274729ELWOOD EC;1P
Adder
25.638
965021AG1-366 GEN
Solar/Wind Harmer
3.621
943121AE2-341 GEN
Solar/Wind Harmer
23.236
943591AF1-030 GEN
Solar/Wind Harmer
15.491
274862TOP CROP ;2U
Solar/Wind Harmer
7.706
274682WAUKEGAN ;7U
Adder
27.375
276868AE1-113 GEN
Solar/Wind Harmer
15.119
274879MINONK ;1U
Solar/Wind Harmer
10.08
276799AD1-013 GEN
Solar/Wind Harmer
3.29
946671AF1-331 GEN
Solar/Wind Harmer
0.623
274855GSG-6 ;RU
Solar/Wind Harmer
5.493
274850MENDOTA H;RU
Solar/Wind Harmer
3.819
276602WESTBROOK C
Solar/Wind Harmer
3.162
959091AF2-200 GEN
Solar/Wind Harmer
29.544
964401AG1-302 GEN
Solar/Wind Harmer
13.205
970571AG2-364 GEN
Solar/Wind Harmer
29.059
274857EASY ROAD;U1
Solar/Wind Harmer
6.909
274760LEE CO EC;1U
Adder
13.418
274767LEE CO EC;8U
Adder
13.26
276603SUBLETTE C
Solar/Wind Harmer
1.51
24728505AND G1
Adder
3.703
24344105CKG2
50/50
14.019
270143AC1-141 CT2_
50/50
4.051
24639705ELKHART HY
50/50
0.271
970521AG2-332 GEN
50/50
19.267
24307105BERRINSP G
50/50
0.035
274773LINCOLN ;4U
50/50
10.761
274774LINCOLN ;5U
50/50
10.761
270216AD2-079_GEN
Solar/Wind Harmer
1.018
957891AF2-083 GEN
Solar/Wind Harmer
25.008
945111AF1-176 GEN
Solar/Wind Harmer
29.638
270449AD2-020 GEN
Solar/Wind Harmer
4.629
943021AE2-325 GEN
Solar/Wind Harmer
6.017
972207SS24-0001
Solar/Wind Harmer
36.058
24441205WTRV SLR C
Solar/Wind Harmer
0.218
274723RIVER EC ;12
Adder
28.715
274751CRETE EC ;1U
Adder
7.816
274754CRETE EC ;4U
Adder
7.816
274812UNIV PK N;8U
Adder
7.962
274802UNIV PARK;5U
Adder
9.218
941551AE2-152 GEN
Solar/Wind Harmer
7.132
274676JOLIET 29;8U
Adder
48.002
274674JOLIET 9 ;6U
Adder
24.037
274732ELWOOD EC;7P
Adder
25.639
965011AG1-365 GEN
Solar/Wind Harmer
15.569
274871GR RIDGE ;2U
Solar/Wind Harmer
11.966
274847GR RIDGE ;BU
Solar/Wind Harmer
7.868
970373AG2-245 GEN
Solar/Wind Harmer
32.493
274745AC1-111 GEN9
Adder
8.641
276694AA1-018 GEN2
Solar/Wind Harmer
9.619
276691AA1-018 GEN1
Solar/Wind Harmer
1.15
274861TOP CROP ;1U
Solar/Wind Harmer
9.229
274682WAUKEGAN ;7U
Adder
27.375
274828WAUKEGAN ;BP
Adder
16.8
965651AG1-433 GEN
Solar/Wind Harmer
8.273
962781AG1-127 GEN
Solar/Wind Harmer
14.349
939401AE1-172 GEN
Solar/Wind Harmer
20.973
274872LEEDK;1U
Solar/Wind Harmer
12.354
276805AD2-038 GEN
Solar/Wind Harmer
7.707
270055AF2-134 C O1
Solar/Wind Harmer
4.543
276882AE2-255 GEN
Solar/Wind Harmer
5.04
971997AH1-543 GEN
Solar/Wind Harmer
23.475
957471AF2-041 GEN
Solar/Wind Harmer
44.316
959081AF2-199 GEN
Solar/Wind Harmer
14.772
971067AG2-660 GEN
Solar/Wind Harmer
3.435
958861AF2-177 GEN
Solar/Wind Harmer
16.115
274822ROCKFORD ;11
Adder
28.883
970819AG2-516 GEN
Solar/Wind Harmer
17.544
958381AF2-132 GEN
Solar/Wind Harmer
13.205
970569AG2-363 GEN
Solar/Wind Harmer
43.588
964861AG1-349 GEN
Solar/Wind Harmer
11.404
971917AH1-482 GEN
Solar/Wind Harmer
13.158
274858EASY ROAD;U2
Solar/Wind Harmer
6.909
274761LEE CO EC;2U
Adder
13.418
24344005CKG1
50/50
10.928
270144AC1-141 ST1_
50/50
3.59
24641605TWIN BRNCH
50/50
0.029
24653605MOTTVILLE
50/50
0.006
274775LINCOLN ;6U
50/50
10.761
274776LINCOLN ;7U
50/50
10.761
274777LINCOLN ;8U
50/50
10.761
971771AH1-392 GEN
Solar/Wind Harmer
15.181
270071AF1-092 GEN
Solar/Wind Harmer
25.227
960681AF2-359 GEN
Solar/Wind Harmer
6.344
270526AF1-158 GEN
Solar/Wind Harmer
7.601
944161AF1-084 GEN
Solar/Wind Harmer
3.629
24729505KEY G4
Adder
10.601
970031AG2-029 GEN
Solar/Wind Harmer
40.745
274827FISK ;RP
Adder
12.267
972037AH1-567 GEN1
Adder
0.289
960591AF2-350 GEN
Solar/Wind Harmer
15.798
274800UNIV PARK;3U
Adder
9.206
274801UNIV PARK;4U
Adder
9.206
972228AH1-698 GEN2
Adder
5.848
972227AH1-698 GEN1
Adder
4.118
274687WILL CNTY;4U
Adder
43.781
274687WILL CNTY;4U
Adder
43.781
274675JOLIET 29;7U
Adder
48.003
274675JOLIET 29;7U
Adder
46.289
274728ELWOOD EC;5P
Adder
25.639
274731ELWOOD EC;2P
Adder
25.638
274733ELWOOD EC;3P
Adder
25.638
274735ELWOOD EC;4P
Adder
25.638
276893AG1-478 C
Solar/Wind Harmer
0.857
970833AG2-524 GEN
Solar/Wind Harmer
13.593
970833AG2-524 GEN
Solar/Wind Harmer
6.322
959331AF2-224 GEN
Solar/Wind Harmer
15.569
274744AC1-111 GEN8
Adder
8.641
274746AC1-111 G10
Adder
8.641
958711AF2-162 GEN
Solar/Wind Harmer
1.531
970073AG2-061 GEN
Solar/Wind Harmer
3.495
971549AH1-272 GEN
Solar/Wind Harmer
27.785
971411AH1-196 GEN
Solar/Wind Harmer
22.33
971675AH1-338 GEN
Solar/Wind Harmer
26.789
276861AD2-134 GEN
Solar/Wind Harmer
2.656
276863AD2-134 GEN
Solar/Wind Harmer
2.656
971171AH1-044 GEN
Solar/Wind Harmer
29.544
274863CRW1-WTG
Solar/Wind Harmer
8.244
274864CRW2-WTG
Solar/Wind Harmer
8.244
276889AE2-281 GEN
Solar/Wind Harmer
2.827
274823ROCKFORD ;21
Adder
28.673
274856ECOGROVE ;U1
Solar/Wind Harmer
4.921
276611AD2-172 GEN
Solar/Wind Harmer
3.733
276612AE2-035 GEN
Solar/Wind Harmer
3.733
926823AC1-168 GEN
Solar/Wind Harmer
6.242
971681AH1-341 GEN
Solar/Wind Harmer
21.737
970169AG2-114 GEN
Solar/Wind Harmer
14.474
972267AH1-718 GEN
Adder
5.936
958391AF2-133 GEN
Solar/Wind Harmer
0.637
274766LEE CO EC;7U
Adder
13.26
24728605AND G2
Adder
3.703
LAGNLTFEXP_LAGN->PJM
CLTF
10.564
TVALTFEXP_TVA->PJM
CLTF
3.981
NYPJM->LTFIMP_NY
CLTF
2.562
LGEELTFEXP_LGEE->PJM
CLTF
3.44
WECLTFEXP_WEC->PJM
CLTF
5.595
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.756
AG2-052LTFEXP_AG2-052->PJM
LTF
0.346
AH1-155LTFEXP_AH1-155->PJM
LTF
0.519
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.297
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.281
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.645
MECLTFEXP_MEC->PJM
CLTF
20.072
SIGELTFEXP_SIGE->PJM
CLTF
0.372
CBM West 2LTFEXP_CBM-W2->PJM
CBM
95.453

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.64 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4541.17
MW Contribution:
27.32
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.88 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6125.38
MW Contribution:
34.29
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
3.969
24642205MAYFLWER
50/50
0.06
944961AF1-161 GEN
50/50
4.707
962601AG1-109 GEN
50/50
4.707
270043AE2-236 GEN
Solar/Wind Harmer
9.708
971347AH1-153 GEN
Solar/Wind Harmer
8.745
944531AF1-118 GEN
Solar/Wind Harmer
59.074
247643Z2-116 C
Solar/Wind Harmer
0.115
270505AE1-170 C O1
Solar/Wind Harmer
24.553
270063AE2-323 C
Solar/Wind Harmer
3.592
24441505OLIV SLR
Solar/Wind Harmer
0.218
945111AF1-176 GEN
Solar/Wind Harmer
9.209
274772LINCOLN ;3U
Adder
9.889
965021AG1-366 GEN
Solar/Wind Harmer
3.65
274724RIVER EC ;11
Adder
27.655
972231SS25-0005
Solar/Wind Harmer
14.775
972181SS23-001
Solar/Wind Harmer
9.234
274752CRETE EC ;2U
Adder
7.609
274753CRETE EC ;3U
Adder
7.609
276164X3-005 C
Solar/Wind Harmer
1.093
274814UNIV PK N;0U
Adder
7.822
274807UNIV PK N;3U
Adder
7.805
274811UNIV PK N;7U
Adder
7.754
970707AG2-453 GEN
Solar/Wind Harmer
43.293
274826FISK ;BP
Adder
16.866
274803UNIV PARK;6U
Adder
8.981
972259AH1-714 GEN
Adder
29.375
274887GEN-1.85
Solar/Wind Harmer
8.202
276772AC2-154 GEN
Solar/Wind Harmer
4.296
276843GEN-1.7
Solar/Wind Harmer
0.883
276806AD2-047 C O1
Solar/Wind Harmer
16.469
972038AH1-567 GEN2
Adder
0.561
939351AE1-166 GEN
Solar/Wind Harmer
9.09
274676JOLIET 29;8U
Adder
45.107
274730ELWOOD EC;6P
Adder
24.985
274734ELWOOD EC;8P
Adder
24.985
274736ELWOOD EC;9P
Adder
24.985
274729ELWOOD EC;1P
Adder
24.985
943121AE2-341 GEN
Solar/Wind Harmer
22.647
943591AF1-030 GEN
Solar/Wind Harmer
15.098
274862TOP CROP ;2U
Solar/Wind Harmer
7.509
274682WAUKEGAN ;7U
Adder
26.676
276868AE1-113 GEN
Solar/Wind Harmer
14.735
274879MINONK ;1U
Solar/Wind Harmer
9.824
276799AD1-013 GEN
Solar/Wind Harmer
3.206
946671AF1-331 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
5.353
274850MENDOTA H;RU
Solar/Wind Harmer
3.722
276602WESTBROOK C
Solar/Wind Harmer
3.082
959091AF2-200 GEN
Solar/Wind Harmer
28.79
970571AG2-364 GEN
Solar/Wind Harmer
28.322
274857EASY ROAD;U1
Solar/Wind Harmer
6.732
274760LEE CO EC;1U
Adder
13.074
274767LEE CO EC;8U
Adder
12.92
276603SUBLETTE C
Solar/Wind Harmer
1.471
24728505AND G1
Adder
3.591
270102X2-052 ST
50/50
2.634
270100X2-052 CT1
50/50
2.433
270101X2-052 CT2
50/50
2.433
24729405KEY G3
50/50
0.617
24729305KEY G2
50/50
0.607
24729205KEY G1
50/50
0.604
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.794
970349AG2-230 GEN
Solar/Wind Harmer
26.234
965681AG1-436 GEN
Solar/Wind Harmer
20.418
965791AG1-447 GEN
Solar/Wind Harmer
10.446
961051AF2-396 GEN
Solar/Wind Harmer
25.755
961051AF2-396 GEN
Solar/Wind Harmer
11.979
274770LINCOLN ;1U
Adder
9.889
274771LINCOLN ;2U
Adder
9.889
274805UNIV PK N;1U
Adder
7.771
274808UNIV PK N;4U
Adder
7.72
274888KELLY CRK;1U
Solar/Wind Harmer
9.085
276776AD2-060 GEN
Solar/Wind Harmer
0.644
958011AF2-095 GEN
Solar/Wind Harmer
22.169
970941AG2-585 GEN
Solar/Wind Harmer
8.467
276897AD1-100 C
Solar/Wind Harmer
71.205
274674JOLIET 9 ;6U
Adder
23.424
276893AG1-478 C
Solar/Wind Harmer
0.666
944541AF1-119 GEN
Solar/Wind Harmer
6.354
960971AF2-388 GEN
Solar/Wind Harmer
16.587
274695ROCKY RD ;2P
Adder
16.555
274693ROCKY RD ;1P
Adder
16.392
274697ROCKY RD ;3P
Adder
4.497
274696ROCKY RD ;4P
Adder
16.945
958481AF2-142 GEN
Solar/Wind Harmer
22.283
274683WAUKEGAN ;8U
Adder
31.232
274683WAUKEGAN ;8U
Adder
26.327
962691AG1-118 GEN
Solar/Wind Harmer
44.239
960751AF2-366 GEN
Solar/Wind Harmer
4.219
958491AF2-143 GEN
Solar/Wind Harmer
21.971
276901AD2-066 C O1
Solar/Wind Harmer
5.123
971341AH1-150 GEN
Solar/Wind Harmer
28.79
971343AH1-151 GEN
Solar/Wind Harmer
28.79
276872AE1-163_GEN1
Solar/Wind Harmer
9.642
276876AE1-163_GEN2
Solar/Wind Harmer
9.642
972235AH1-702 GEN1
Adder
3.605
972236AH1-702 GEN2
Adder
3.134
270535AF1-215 GEN1
Solar/Wind Harmer
6.477
270536AF1-215 GEN2
Solar/Wind Harmer
6.477
938861AE1-114 GEN
Solar/Wind Harmer
11.571
274764LEE CO EC;5U
Adder
13.105
274765LEE CO EC;6U
Adder
13.105
274762LEE CO EC;3U
Adder
13.074
274763LEE CO EC;4U
Adder
12.951
942221AE2-234 GEN
Solar/Wind Harmer
4.887
247621Y3-024
Adder
0.265
270349AD2-093_GEN
Solar/Wind Helper
1.354
270471AD2-092_GEN
Solar/Wind Helper
1.354
276158O29GEN2
Solar/Wind Harmer
5.508
276157O29GEN1
Solar/Wind Harmer
4.188
270144AC1-141 ST1_
50/50
3.518
24344005CKG1
50/50
10.694
24641605TWIN BRNCH
50/50
0.028
24729505KEY G4
50/50
11.308
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
24.785
971771AH1-392 GEN
Solar/Wind Harmer
14.851
270526AF1-158 GEN
Solar/Wind Harmer
7.418
960681AF2-359 GEN
Solar/Wind Harmer
6.172
970031AG2-029 GEN
Solar/Wind Harmer
40.379
944161AF1-084 GEN
Solar/Wind Harmer
3.556
274775LINCOLN ;6U
Adder
9.889
274776LINCOLN ;7U
Adder
9.889
274777LINCOLN ;8U
Adder
9.889
959331AF2-224 GEN
Solar/Wind Harmer
15.695
274827FISK ;RP
Adder
11.953
972037AH1-567 GEN1
Adder
0.282
960591AF2-350 GEN
Solar/Wind Harmer
15.395
972228AH1-698 GEN2
Adder
5.699
972227AH1-698 GEN1
Adder
4.013
274800UNIV PARK;3U
Adder
8.97
274801UNIV PARK;4U
Adder
8.97
274687WILL CNTY;4U
Adder
42.663
274687WILL CNTY;4U
Adder
42.663
274675JOLIET 29;7U
Adder
46.778
274675JOLIET 29;7U
Adder
45.107
274728ELWOOD EC;5P
Adder
24.985
274731ELWOOD EC;2P
Adder
24.985
274733ELWOOD EC;3P
Adder
24.985
274735ELWOOD EC;4P
Adder
24.985
276893AG1-478 C
Solar/Wind Harmer
0.836
970833AG2-524 GEN
Solar/Wind Harmer
13.249
970833AG2-524 GEN
Solar/Wind Harmer
6.162
958711AF2-162 GEN
Solar/Wind Harmer
1.535
274744AC1-111 GEN8
Adder
8.422
274746AC1-111 G10
Adder
8.422
971549AH1-272 GEN
Solar/Wind Harmer
27.315
970073AG2-061 GEN
Solar/Wind Harmer
3.406
971411AH1-196 GEN
Solar/Wind Harmer
21.759
971675AH1-338 GEN
Solar/Wind Harmer
26.106
276861AD2-134 GEN
Solar/Wind Harmer
2.589
276863AD2-134 GEN
Solar/Wind Harmer
2.589
274863CRW1-WTG
Solar/Wind Harmer
8.038
274864CRW2-WTG
Solar/Wind Harmer
8.038
971171AH1-044 GEN
Solar/Wind Harmer
28.79
276889AE2-281 GEN
Solar/Wind Harmer
2.755
274823ROCKFORD ;21
Adder
27.94
274856ECOGROVE ;U1
Solar/Wind Harmer
4.795
276611AD2-172 GEN
Solar/Wind Harmer
3.637
276612AE2-035 GEN
Solar/Wind Harmer
3.637
926823AC1-168 GEN
Solar/Wind Harmer
6.084
971681AH1-341 GEN
Solar/Wind Harmer
21.181
970169AG2-114 GEN
Solar/Wind Harmer
14.112
963791AG1-232 GEN
Solar/Wind Harmer
18.963
945581AF1-223 GEN
Solar/Wind Harmer
6.342
972267AH1-718 GEN
Adder
5.784
24344105CKG2
50/50
13.703
270143AC1-141 CT2_
50/50
3.969
24639705ELKHART HY
50/50
0.266
970521AG2-332 GEN
50/50
18.921
24307105BERRINSP G
50/50
0.035
270216AD2-079_GEN
Solar/Wind Harmer
0.998
957891AF2-083 GEN
Solar/Wind Harmer
24.504
945111AF1-176 GEN
Solar/Wind Harmer
29.057
270449AD2-020 GEN
Solar/Wind Harmer
4.536
943021AE2-325 GEN
Solar/Wind Harmer
5.896
972207SS24-0001
Solar/Wind Harmer
35.159
274773LINCOLN ;4U
Adder
9.889
274774LINCOLN ;5U
Adder
9.889
24441205WTRV SLR C
Solar/Wind Harmer
0.214
965011AG1-365 GEN
Solar/Wind Harmer
15.695
274723RIVER EC ;12
Adder
27.973
274751CRETE EC ;1U
Adder
7.609
274754CRETE EC ;4U
Adder
7.609
274812UNIV PK N;8U
Adder
7.754
274802UNIV PARK;5U
Adder
8.981
941551AE2-152 GEN
Solar/Wind Harmer
6.952
274676JOLIET 29;8U
Adder
46.777
274674JOLIET 9 ;6U
Adder
23.424
274732ELWOOD EC;7P
Adder
24.985
965651AG1-433 GEN
Solar/Wind Harmer
8.293
274871GR RIDGE ;2U
Solar/Wind Harmer
11.662
274847GR RIDGE ;BU
Solar/Wind Harmer
7.668
274745AC1-111 GEN9
Adder
8.422
276694AA1-018 GEN2
Solar/Wind Harmer
9.373
276691AA1-018 GEN1
Solar/Wind Harmer
1.12
274861TOP CROP ;1U
Solar/Wind Harmer
8.994
274682WAUKEGAN ;7U
Adder
26.676
274828WAUKEGAN ;BP
Adder
16.371
970373AG2-245 GEN
Solar/Wind Harmer
31.076
958861AF2-177 GEN
Solar/Wind Harmer
16.139
962781AG1-127 GEN
Solar/Wind Harmer
13.983
939401AE1-172 GEN
Solar/Wind Harmer
20.448
274872LEEDK;1U
Solar/Wind Harmer
12.039
276805AD2-038 GEN
Solar/Wind Harmer
7.511
276882AE2-255 GEN
Solar/Wind Harmer
4.912
971997AH1-543 GEN
Solar/Wind Harmer
22.881
957471AF2-041 GEN
Solar/Wind Harmer
43.185
959081AF2-199 GEN
Solar/Wind Harmer
14.395
971067AG2-660 GEN
Solar/Wind Harmer
3.348
274822ROCKFORD ;11
Adder
28.144
270055AF2-134 C O1
Solar/Wind Harmer
4.318
970819AG2-516 GEN
Solar/Wind Harmer
17.095
970569AG2-363 GEN
Solar/Wind Harmer
42.484
274858EASY ROAD;U2
Solar/Wind Harmer
6.732
274761LEE CO EC;2U
Adder
13.074
274766LEE CO EC;7U
Adder
12.92
945371AF1-202 GEN
Solar/Wind Harmer
9.756
24728605AND G2
Adder
3.591
LAGNLTFEXP_LAGN->PJM
CLTF
9.979
TVALTFEXP_TVA->PJM
CLTF
3.685
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
3.498
WECLTFEXP_WEC->PJM
CLTF
5.451
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.96
AG2-052LTFEXP_AG2-052->PJM
LTF
0.335
AH1-155LTFEXP_AH1-155->PJM
LTF
0.502
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.433
CBM West 1LTFEXP_CBM-W1->PJM
CBM
166.786
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.792
MECLTFEXP_MEC->PJM
CLTF
19.53
SIGELTFEXP_SIGE->PJM
CLTF
0.368
CBM West 2LTFEXP_CBM-W2->PJM
CBM
92.071

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.44 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4491.48
MW Contribution:
27.37
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.29 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6059.51
MW Contribution:
34.38
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
3.977
24642205MAYFLWER
50/50
0.06
944961AF1-161 GEN
50/50
4.716
962601AG1-109 GEN
50/50
4.716
270043AE2-236 GEN
Solar/Wind Harmer
9.725
971347AH1-153 GEN
Solar/Wind Harmer
8.761
944531AF1-118 GEN
Solar/Wind Harmer
59.186
247643Z2-116 C
Solar/Wind Harmer
0.115
270505AE1-170 C O1
Solar/Wind Harmer
24.601
270063AE2-323 C
Solar/Wind Harmer
3.599
24441505OLIV SLR
Solar/Wind Harmer
0.219
945111AF1-176 GEN
Solar/Wind Harmer
9.227
274772LINCOLN ;3U
Adder
9.909
965021AG1-366 GEN
Solar/Wind Harmer
3.658
274724RIVER EC ;11
Adder
27.711
972231SS25-0005
Solar/Wind Harmer
14.805
972181SS23-001
Solar/Wind Harmer
9.253
274752CRETE EC ;2U
Adder
7.625
274753CRETE EC ;3U
Adder
7.625
276164X3-005 C
Solar/Wind Harmer
1.095
274814UNIV PK N;0U
Adder
7.838
274807UNIV PK N;3U
Adder
7.821
274811UNIV PK N;7U
Adder
7.77
970707AG2-453 GEN
Solar/Wind Harmer
43.383
274826FISK ;BP
Adder
16.901
274803UNIV PARK;6U
Adder
9
972259AH1-714 GEN
Adder
29.436
274887GEN-1.85
Solar/Wind Harmer
8.22
276772AC2-154 GEN
Solar/Wind Harmer
4.305
276843GEN-1.7
Solar/Wind Harmer
0.884
276806AD2-047 C O1
Solar/Wind Harmer
16.503
972038AH1-567 GEN2
Adder
0.563
939351AE1-166 GEN
Solar/Wind Harmer
9.109
274676JOLIET 29;8U
Adder
45.202
274730ELWOOD EC;6P
Adder
25.038
274734ELWOOD EC;8P
Adder
25.038
274736ELWOOD EC;9P
Adder
25.038
274729ELWOOD EC;1P
Adder
25.038
943121AE2-341 GEN
Solar/Wind Harmer
22.695
943591AF1-030 GEN
Solar/Wind Harmer
15.13
274862TOP CROP ;2U
Solar/Wind Harmer
7.526
274682WAUKEGAN ;7U
Adder
26.734
276868AE1-113 GEN
Solar/Wind Harmer
14.768
274879MINONK ;1U
Solar/Wind Harmer
9.846
276799AD1-013 GEN
Solar/Wind Harmer
3.213
946671AF1-331 GEN
Solar/Wind Harmer
0.609
274855GSG-6 ;RU
Solar/Wind Harmer
5.365
274850MENDOTA H;RU
Solar/Wind Harmer
3.73
276602WESTBROOK C
Solar/Wind Harmer
3.088
959091AF2-200 GEN
Solar/Wind Harmer
28.854
970571AG2-364 GEN
Solar/Wind Harmer
28.387
274857EASY ROAD;U1
Solar/Wind Harmer
6.748
274760LEE CO EC;1U
Adder
13.104
274767LEE CO EC;8U
Adder
12.95
24344105CKG2
50/50
13.727
270143AC1-141 CT2_
50/50
3.977
24639705ELKHART HY
50/50
0.267
970521AG2-332 GEN
50/50
18.959
24307105BERRINSP G
50/50
0.035
270216AD2-079_GEN
Solar/Wind Harmer
1
957891AF2-083 GEN
Solar/Wind Harmer
24.552
945111AF1-176 GEN
Solar/Wind Harmer
29.114
270449AD2-020 GEN
Solar/Wind Harmer
4.545
943021AE2-325 GEN
Solar/Wind Harmer
5.908
972207SS24-0001
Solar/Wind Harmer
35.229
274773LINCOLN ;4U
Adder
9.909
274774LINCOLN ;5U
Adder
9.909
24441205WTRV SLR C
Solar/Wind Harmer
0.214
965011AG1-365 GEN
Solar/Wind Harmer
15.727
274723RIVER EC ;12
Adder
28.031
274751CRETE EC ;1U
Adder
7.625
274754CRETE EC ;4U
Adder
7.625
274812UNIV PK N;8U
Adder
7.77
274802UNIV PARK;5U
Adder
9
941551AE2-152 GEN
Solar/Wind Harmer
6.967
274676JOLIET 29;8U
Adder
46.876
274674JOLIET 9 ;6U
Adder
23.474
274732ELWOOD EC;7P
Adder
25.038
965651AG1-433 GEN
Solar/Wind Harmer
8.311
274871GR RIDGE ;2U
Solar/Wind Harmer
11.687
274847GR RIDGE ;BU
Solar/Wind Harmer
7.685
274745AC1-111 GEN9
Adder
8.44
276694AA1-018 GEN2
Solar/Wind Harmer
9.394
276691AA1-018 GEN1
Solar/Wind Harmer
1.123
274861TOP CROP ;1U
Solar/Wind Harmer
9.013
274682WAUKEGAN ;7U
Adder
26.734
274828WAUKEGAN ;BP
Adder
16.407
970373AG2-245 GEN
Solar/Wind Harmer
31.143
958861AF2-177 GEN
Solar/Wind Harmer
16.174
962781AG1-127 GEN
Solar/Wind Harmer
14.014
939401AE1-172 GEN
Solar/Wind Harmer
20.492
274872LEEDK;1U
Solar/Wind Harmer
12.065
276805AD2-038 GEN
Solar/Wind Harmer
7.527
276882AE2-255 GEN
Solar/Wind Harmer
4.923
971997AH1-543 GEN
Solar/Wind Harmer
22.932
957471AF2-041 GEN
Solar/Wind Harmer
43.281
959081AF2-199 GEN
Solar/Wind Harmer
14.427
971067AG2-660 GEN
Solar/Wind Harmer
3.355
274822ROCKFORD ;11
Adder
28.207
270055AF2-134 C O1
Solar/Wind Harmer
4.328
970819AG2-516 GEN
Solar/Wind Harmer
17.133
270144AC1-141 ST1_
50/50
3.524
24344005CKG1
50/50
10.714
24641605TWIN BRNCH
50/50
0.028
24729505KEY G4
50/50
11.33
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
24.834
971771AH1-392 GEN
Solar/Wind Harmer
14.88
270526AF1-158 GEN
Solar/Wind Harmer
7.433
960681AF2-359 GEN
Solar/Wind Harmer
6.184
970031AG2-029 GEN
Solar/Wind Harmer
40.46
944161AF1-084 GEN
Solar/Wind Harmer
3.563
274775LINCOLN ;6U
Adder
9.909
274776LINCOLN ;7U
Adder
9.909
274777LINCOLN ;8U
Adder
9.909
959331AF2-224 GEN
Solar/Wind Harmer
15.727
274827FISK ;RP
Adder
11.978
972037AH1-567 GEN1
Adder
0.283
960591AF2-350 GEN
Solar/Wind Harmer
15.427
972228AH1-698 GEN2
Adder
5.711
972227AH1-698 GEN1
Adder
4.021
274800UNIV PARK;3U
Adder
8.989
274801UNIV PARK;4U
Adder
8.989
274687WILL CNTY;4U
Adder
42.752
274687WILL CNTY;4U
Adder
42.752
274675JOLIET 29;7U
Adder
46.876
274675JOLIET 29;7U
Adder
45.202
274728ELWOOD EC;5P
Adder
25.038
274731ELWOOD EC;2P
Adder
25.038
274733ELWOOD EC;3P
Adder
25.038
274735ELWOOD EC;4P
Adder
25.038
276893AG1-478 C
Solar/Wind Harmer
0.837
958711AF2-162 GEN
Solar/Wind Harmer
1.538
970833AG2-524 GEN
Solar/Wind Harmer
13.277
970833AG2-524 GEN
Solar/Wind Harmer
6.175
274744AC1-111 GEN8
Adder
8.44
274746AC1-111 G10
Adder
8.44
971549AH1-272 GEN
Solar/Wind Harmer
27.374
970073AG2-061 GEN
Solar/Wind Harmer
3.414
971411AH1-196 GEN
Solar/Wind Harmer
21.807
971675AH1-338 GEN
Solar/Wind Harmer
26.164
276861AD2-134 GEN
Solar/Wind Harmer
2.594
276863AD2-134 GEN
Solar/Wind Harmer
2.594
274863CRW1-WTG
Solar/Wind Harmer
8.055
274864CRW2-WTG
Solar/Wind Harmer
8.055
971171AH1-044 GEN
Solar/Wind Harmer
28.854
276889AE2-281 GEN
Solar/Wind Harmer
2.761
274823ROCKFORD ;21
Adder
28.002
274856ECOGROVE ;U1
Solar/Wind Harmer
4.806
276611AD2-172 GEN
Solar/Wind Harmer
3.645
276612AE2-035 GEN
Solar/Wind Harmer
3.645
926823AC1-168 GEN
Solar/Wind Harmer
6.098
971681AH1-341 GEN
Solar/Wind Harmer
21.229
970169AG2-114 GEN
Solar/Wind Harmer
14.144
963791AG1-232 GEN
Solar/Wind Harmer
19.006
945581AF1-223 GEN
Solar/Wind Harmer
6.356
972267AH1-718 GEN
Adder
5.797
276603SUBLETTE C
Solar/Wind Harmer
1.475
24728505AND G1
Adder
3.604
270102X2-052 ST
50/50
2.639
270100X2-052 CT1
50/50
2.438
270101X2-052 CT2
50/50
2.438
24729405KEY G3
50/50
0.619
24729305KEY G2
50/50
0.608
24729205KEY G1
50/50
0.605
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.795
970349AG2-230 GEN
Solar/Wind Harmer
26.283
965681AG1-436 GEN
Solar/Wind Harmer
20.458
965791AG1-447 GEN
Solar/Wind Harmer
10.467
961051AF2-396 GEN
Solar/Wind Harmer
25.806
961051AF2-396 GEN
Solar/Wind Harmer
12.003
274770LINCOLN ;1U
Adder
9.909
274771LINCOLN ;2U
Adder
9.909
274805UNIV PK N;1U
Adder
7.787
274808UNIV PK N;4U
Adder
7.736
274888KELLY CRK;1U
Solar/Wind Harmer
9.104
276776AD2-060 GEN
Solar/Wind Harmer
0.646
958011AF2-095 GEN
Solar/Wind Harmer
22.215
970941AG2-585 GEN
Solar/Wind Harmer
8.485
276897AD1-100 C
Solar/Wind Harmer
71.354
274674JOLIET 9 ;6U
Adder
23.474
276893AG1-478 C
Solar/Wind Harmer
0.667
944541AF1-119 GEN
Solar/Wind Harmer
6.368
960971AF2-388 GEN
Solar/Wind Harmer
16.622
274695ROCKY RD ;2P
Adder
16.591
274693ROCKY RD ;1P
Adder
16.427
274697ROCKY RD ;3P
Adder
4.507
274696ROCKY RD ;4P
Adder
16.982
958481AF2-142 GEN
Solar/Wind Harmer
22.332
274683WAUKEGAN ;8U
Adder
31.299
274683WAUKEGAN ;8U
Adder
26.384
962691AG1-118 GEN
Solar/Wind Harmer
44.335
960751AF2-366 GEN
Solar/Wind Harmer
4.228
958491AF2-143 GEN
Solar/Wind Harmer
22.019
276901AD2-066 C O1
Solar/Wind Harmer
5.135
971341AH1-150 GEN
Solar/Wind Harmer
28.854
971343AH1-151 GEN
Solar/Wind Harmer
28.854
276872AE1-163_GEN1
Solar/Wind Harmer
9.664
276876AE1-163_GEN2
Solar/Wind Harmer
9.664
972235AH1-702 GEN1
Adder
3.613
972236AH1-702 GEN2
Adder
3.141
270535AF1-215 GEN1
Solar/Wind Harmer
6.492
270536AF1-215 GEN2
Solar/Wind Harmer
6.492
938861AE1-114 GEN
Solar/Wind Harmer
11.597
274764LEE CO EC;5U
Adder
13.135
274765LEE CO EC;6U
Adder
13.135
274762LEE CO EC;3U
Adder
13.104
274763LEE CO EC;4U
Adder
12.98
942221AE2-234 GEN
Solar/Wind Harmer
4.898
247621Y3-024
Adder
0.266
270349AD2-093_GEN
Solar/Wind Helper
1.349
270471AD2-092_GEN
Solar/Wind Helper
1.349
276158O29GEN2
Solar/Wind Harmer
5.521
276157O29GEN1
Solar/Wind Harmer
4.198
970569AG2-363 GEN
Solar/Wind Harmer
42.58
274858EASY ROAD;U2
Solar/Wind Harmer
6.748
274761LEE CO EC;2U
Adder
13.104
274766LEE CO EC;7U
Adder
12.95
945371AF1-202 GEN
Solar/Wind Harmer
9.778
24728605AND G2
Adder
3.604
LAGNLTFEXP_LAGN->PJM
CLTF
10.044
TVALTFEXP_TVA->PJM
CLTF
3.718
NYPJM->LTFIMP_NY
CLTF
2.463
LGEELTFEXP_LGEE->PJM
CLTF
3.52
WECLTFEXP_WEC->PJM
CLTF
5.463
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.938
AG2-052LTFEXP_AG2-052->PJM
LTF
0.336
AH1-155LTFEXP_AH1-155->PJM
LTF
0.503
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.42
CBM West 1LTFEXP_CBM-W1->PJM
CBM
167.255
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.914
MECLTFEXP_MEC->PJM
CLTF
19.584
SIGELTFEXP_SIGE->PJM
CLTF
0.37
CBM West 2LTFEXP_CBM-W2->PJM
CBM
92.505

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#2995_05E LIMA 345_M_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2995_05E LIMA 345_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.11 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4477.92
MW Contribution:
27.16
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2995_05E LIMA 345_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.61 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5824.03
MW Contribution:
33.08
Bus #Bus NameTypeMW Contribution
24727105RPMNG2
50/50
1.813
965431AG1-411 GEN
50/50
22.127
270142AC1-141 CT1_
50/50
3.995
24642205MAYFLWER
50/50
0.06
944961AF1-161 GEN
50/50
4.731
962601AG1-109 GEN
50/50
4.731
965021AG1-366 GEN
Solar/Wind Harmer
4.428
246938BC-WTG3
Solar/Wind Harmer
7.572
270491AE1-102 GEN2
Solar/Wind Harmer
2.474
270043AE2-236 GEN
Solar/Wind Harmer
10.28
944531AF1-118 GEN
Solar/Wind Harmer
61.625
971347AH1-153 GEN
Solar/Wind Harmer
8.728
270063AE2-323 C
Solar/Wind Harmer
3.769
247643Z2-116 C
Solar/Wind Harmer
0.117
270505AE1-170 C O1
Solar/Wind Harmer
24.702
945111AF1-176 GEN
Solar/Wind Harmer
9.302
24441505OLIV SLR
Solar/Wind Harmer
0.218
274772LINCOLN ;3U
Adder
9.759
274724RIVER EC ;11
Adder
27.355
972231SS25-0005
Solar/Wind Harmer
14.622
972181SS23-001
Solar/Wind Harmer
9.139
274752CRETE EC ;2U
Adder
7.531
274753CRETE EC ;3U
Adder
7.531
276164X3-005 C
Solar/Wind Harmer
1.08
274814UNIV PK N;0U
Adder
7.731
274807UNIV PK N;3U
Adder
7.714
274811UNIV PK N;7U
Adder
7.664
970707AG2-453 GEN
Solar/Wind Harmer
42.675
274826FISK ;BP
Adder
16.649
274803UNIV PARK;6U
Adder
8.866
274887GEN-1.85
Solar/Wind Harmer
8.092
276772AC2-154 GEN
Solar/Wind Harmer
4.238
276843GEN-1.7
Solar/Wind Harmer
0.871
276806AD2-047 C O1
Solar/Wind Harmer
16.247
972038AH1-567 GEN2
Adder
0.554
972259AH1-714 GEN
Adder
28.957
939351AE1-166 GEN
Solar/Wind Harmer
8.954
274676JOLIET 29;8U
Adder
44.469
274730ELWOOD EC;6P
Adder
24.621
274734ELWOOD EC;8P
Adder
24.621
274736ELWOOD EC;9P
Adder
24.621
274729ELWOOD EC;1P
Adder
24.62
943121AE2-341 GEN
Solar/Wind Harmer
22.301
943591AF1-030 GEN
Solar/Wind Harmer
14.867
274682WAUKEGAN ;7U
Adder
26.255
274862TOP CROP ;2U
Solar/Wind Harmer
7.389
276868AE1-113 GEN
Solar/Wind Harmer
14.473
274879MINONK ;1U
Solar/Wind Harmer
9.649
276799AD1-013 GEN
Solar/Wind Harmer
3.15
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274855GSG-6 ;RU
Solar/Wind Harmer
5.26
274850MENDOTA H;RU
Solar/Wind Harmer
3.657
276602WESTBROOK C
Solar/Wind Harmer
3.028
959091AF2-200 GEN
Solar/Wind Harmer
28.278
274760LEE CO EC;1U
Adder
12.825
274767LEE CO EC;8U
Adder
12.674
24728505AND G1
Adder
3.423
970571AG2-364 GEN
Solar/Wind Harmer
14.539
24729405KEY G3
50/50
0.643
24729305KEY G2
50/50
0.632
24729205KEY G1
50/50
0.628
247620Y3-023
50/50
0.816
270102X2-052 ST
50/50
2.62
270100X2-052 CT1
50/50
2.421
270101X2-052 CT2
50/50
2.421
24643105BUCHANAN
50/50
0.021
246937BC-WTG2
Solar/Wind Harmer
7.443
970349AG2-230 GEN
Solar/Wind Harmer
26.183
961051AF2-396 GEN
Solar/Wind Harmer
25.937
961051AF2-396 GEN
Solar/Wind Harmer
12.064
965681AG1-436 GEN
Solar/Wind Harmer
20.299
965791AG1-447 GEN
Solar/Wind Harmer
10.386
274770LINCOLN ;1U
Adder
9.759
274771LINCOLN ;2U
Adder
9.759
944541AF1-119 GEN
Solar/Wind Harmer
6.566
960971AF2-388 GEN
Solar/Wind Harmer
17.14
274805UNIV PK N;1U
Adder
7.681
274808UNIV PK N;4U
Adder
7.63
274888KELLY CRK;1U
Solar/Wind Harmer
8.962
276776AD2-060 GEN
Solar/Wind Harmer
0.636
958011AF2-095 GEN
Solar/Wind Harmer
21.87
970941AG2-585 GEN
Solar/Wind Harmer
8.353
276897AD1-100 C
Solar/Wind Harmer
70.136
274674JOLIET 9 ;6U
Adder
23.085
276893AG1-478 C
Solar/Wind Harmer
0.656
944231AF1-091 GEN
Solar/Wind Harmer
26.716
942221AE2-234 GEN
Solar/Wind Harmer
5.174
274695ROCKY RD ;2P
Adder
16.292
274693ROCKY RD ;1P
Adder
16.131
274697ROCKY RD ;3P
Adder
4.426
274696ROCKY RD ;4P
Adder
16.676
958481AF2-142 GEN
Solar/Wind Harmer
21.925
274683WAUKEGAN ;8U
Adder
30.736
274683WAUKEGAN ;8U
Adder
25.909
962691AG1-118 GEN
Solar/Wind Harmer
43.51
960751AF2-366 GEN
Solar/Wind Harmer
4.149
958491AF2-143 GEN
Solar/Wind Harmer
21.593
276901AD2-066 C O1
Solar/Wind Harmer
5.032
971341AH1-150 GEN
Solar/Wind Harmer
28.278
971343AH1-151 GEN
Solar/Wind Harmer
28.278
276872AE1-163_GEN1
Solar/Wind Harmer
9.46
276876AE1-163_GEN2
Solar/Wind Harmer
9.46
972235AH1-702 GEN1
Adder
3.54
972236AH1-702 GEN2
Adder
3.078
270535AF1-215 GEN1
Solar/Wind Harmer
6.341
270536AF1-215 GEN2
Solar/Wind Harmer
6.341
274764LEE CO EC;5U
Adder
12.855
274765LEE CO EC;6U
Adder
12.855
274762LEE CO EC;3U
Adder
12.825
274763LEE CO EC;4U
Adder
12.704
247621Y3-024
Adder
0.273
270349AD2-093_GEN
Solar/Wind Helper
1.504
270471AD2-092_GEN
Solar/Wind Helper
1.504
24727005RPMNG1
50/50
1.813
24344105CKG2
50/50
13.608
270143AC1-141 CT2_
50/50
3.995
24639705ELKHART HY
50/50
0.272
970521AG2-332 GEN
50/50
19.364
24307105BERRINSP G
50/50
0.035
965011AG1-365 GEN
Solar/Wind Harmer
19.039
965421AG1-410 GEN
Solar/Wind Harmer
57.088
246936BC-WTG1
Solar/Wind Harmer
7.443
270489AE1-102 GEN1
Solar/Wind Harmer
2.474
270216AD2-079_GEN
Solar/Wind Harmer
1.012
957891AF2-083 GEN
Solar/Wind Harmer
24.678
945111AF1-176 GEN
Solar/Wind Harmer
29.352
270449AD2-020 GEN
Solar/Wind Harmer
4.56
943021AE2-325 GEN
Solar/Wind Harmer
5.927
24441205WTRV SLR C
Solar/Wind Harmer
0.214
972207SS24-0001
Solar/Wind Harmer
34.698
274773LINCOLN ;4U
Adder
9.759
274774LINCOLN ;5U
Adder
9.759
965651AG1-433 GEN
Solar/Wind Harmer
8.57
274723RIVER EC ;12
Adder
27.672
274751CRETE EC ;1U
Adder
7.531
274754CRETE EC ;4U
Adder
7.531
274812UNIV PK N;8U
Adder
7.664
958861AF2-177 GEN
Solar/Wind Harmer
16.633
274802UNIV PARK;5U
Adder
8.866
941551AE2-152 GEN
Solar/Wind Harmer
6.848
274676JOLIET 29;8U
Adder
46.116
274674JOLIET 9 ;6U
Adder
23.085
274732ELWOOD EC;7P
Adder
24.621
274871GR RIDGE ;2U
Solar/Wind Harmer
11.484
274847GR RIDGE ;BU
Solar/Wind Harmer
7.551
274745AC1-111 GEN9
Adder
8.293
276694AA1-018 GEN2
Solar/Wind Harmer
9.223
276691AA1-018 GEN1
Solar/Wind Harmer
1.102
274682WAUKEGAN ;7U
Adder
26.255
274861TOP CROP ;1U
Solar/Wind Harmer
8.849
274828WAUKEGAN ;BP
Adder
16.111
970373AG2-245 GEN
Solar/Wind Harmer
30.552
962781AG1-127 GEN
Solar/Wind Harmer
13.751
274872LEEDK;1U
Solar/Wind Harmer
11.837
276805AD2-038 GEN
Solar/Wind Harmer
7.382
939401AE1-172 GEN
Solar/Wind Harmer
20.046
945371AF1-202 GEN
Solar/Wind Harmer
10
276882AE2-255 GEN
Solar/Wind Harmer
4.824
971997AH1-543 GEN
Solar/Wind Harmer
22.456
957471AF2-041 GEN
Solar/Wind Harmer
42.418
959081AF2-199 GEN
Solar/Wind Harmer
14.139
971067AG2-660 GEN
Solar/Wind Harmer
3.288
274822ROCKFORD ;11
Adder
27.643
970819AG2-516 GEN
Solar/Wind Harmer
16.785
270055AF2-134 C O1
Solar/Wind Harmer
4.227
274761LEE CO EC;2U
Adder
12.825
274766LEE CO EC;7U
Adder
12.674
24728605AND G2
Adder
3.423
970569AG2-363 GEN
Solar/Wind Harmer
21.809
24727205RPMNG3
50/50
1.802
24729505KEY G4
50/50
11.769
24641605TWIN BRNCH
50/50
0.029
270144AC1-141 ST1_
50/50
3.54
24653605MOTTVILLE
50/50
0.006
24344005CKG1
50/50
10.676
959331AF2-224 GEN
Solar/Wind Harmer
19.039
957201AF2-014 GEN
Solar/Wind Harmer
8.63
270435AC2-044 GEN
Solar/Wind Harmer
3.806
970031AG2-029 GEN
Solar/Wind Harmer
43.332
270071AF1-092 GEN
Solar/Wind Harmer
25.897
971771AH1-392 GEN
Solar/Wind Harmer
14.928
270526AF1-158 GEN
Solar/Wind Harmer
7.419
960681AF2-359 GEN
Solar/Wind Harmer
6.136
944161AF1-084 GEN
Solar/Wind Harmer
3.57
274775LINCOLN ;6U
Adder
9.759
274776LINCOLN ;7U
Adder
9.759
274777LINCOLN ;8U
Adder
9.759
958711AF2-162 GEN
Solar/Wind Harmer
1.586
963791AG1-232 GEN
Solar/Wind Harmer
21.097
274827FISK ;RP
Adder
11.799
972037AH1-567 GEN1
Adder
0.278
960591AF2-350 GEN
Solar/Wind Harmer
15.187
274800UNIV PARK;3U
Adder
8.852
274801UNIV PARK;4U
Adder
8.852
972228AH1-698 GEN2
Adder
5.62
972227AH1-698 GEN1
Adder
3.957
965041AG1-368 GEN
Solar/Wind Harmer
15.116
274687WILL CNTY;4U
Adder
42.069
274687WILL CNTY;4U
Adder
42.069
274675JOLIET 29;7U
Adder
46.117
274675JOLIET 29;7U
Adder
44.47
274728ELWOOD EC;5P
Adder
24.621
274731ELWOOD EC;2P
Adder
24.62
274733ELWOOD EC;3P
Adder
24.62
274735ELWOOD EC;4P
Adder
24.62
276893AG1-478 C
Solar/Wind Harmer
0.823
970833AG2-524 GEN
Solar/Wind Harmer
13.046
970833AG2-524 GEN
Solar/Wind Harmer
6.068
274744AC1-111 GEN8
Adder
8.293
274746AC1-111 G10
Adder
8.293
971549AH1-272 GEN
Solar/Wind Harmer
27.16
970073AG2-061 GEN
Solar/Wind Harmer
3.348
945581AF1-223 GEN
Solar/Wind Harmer
6.5
971411AH1-196 GEN
Solar/Wind Harmer
21.386
971675AH1-338 GEN
Solar/Wind Harmer
25.652
276861AD2-134 GEN
Solar/Wind Harmer
2.543
276863AD2-134 GEN
Solar/Wind Harmer
2.543
971171AH1-044 GEN
Solar/Wind Harmer
28.278
274863CRW1-WTG
Solar/Wind Harmer
7.865
274864CRW2-WTG
Solar/Wind Harmer
7.865
276889AE2-281 GEN
Solar/Wind Harmer
2.703
274823ROCKFORD ;21
Adder
27.443
274856ECOGROVE ;U1
Solar/Wind Harmer
4.707
276611AD2-172 GEN
Solar/Wind Harmer
3.57
276612AE2-035 GEN
Solar/Wind Harmer
3.57
972267AH1-718 GEN
Adder
5.669
LAGNLTFEXP_LAGN->PJM
CLTF
9.622
TVALTFEXP_TVA->PJM
CLTF
3.539
NYPJM->LTFIMP_NY
CLTF
2.386
LGEELTFEXP_LGEE->PJM
CLTF
2.809
WECLTFEXP_WEC->PJM
CLTF
5.354
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.74
AG2-052LTFEXP_AG2-052->PJM
LTF
0.329
AH1-155LTFEXP_AH1-155->PJM
LTF
0.493
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.304
CBM West 1LTFEXP_CBM-W1->PJM
CBM
160.28
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.664
MECLTFEXP_MEC->PJM
CLTF
18.986
SIGELTFEXP_SIGE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.937

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.56 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4455.3
MW Contribution:
28.03
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.65 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6115.5
MW Contribution:
36.89
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.07
24642205MAYFLWER
50/50
0.062
944961AF1-161 GEN
50/50
4.826
962601AG1-109 GEN
50/50
4.826
270043AE2-236 GEN
Solar/Wind Harmer
9.883
971347AH1-153 GEN
Solar/Wind Harmer
8.969
944531AF1-118 GEN
Solar/Wind Harmer
59.59
247643Z2-116 C
Solar/Wind Harmer
0.118
270505AE1-170 C O1
Solar/Wind Harmer
25.173
24441505OLIV SLR
Solar/Wind Harmer
0.224
270063AE2-323 C
Solar/Wind Harmer
3.671
945111AF1-176 GEN
Solar/Wind Harmer
9.44
274772LINCOLN ;3U
Adder
10.099
965021AG1-366 GEN
Solar/Wind Harmer
3.714
274724RIVER EC ;11
Adder
28.247
972231SS25-0005
Solar/Wind Harmer
15.097
972181SS23-001
Solar/Wind Harmer
9.436
274752CRETE EC ;2U
Adder
7.776
274753CRETE EC ;3U
Adder
7.776
276164X3-005 C
Solar/Wind Harmer
1.115
274814UNIV PK N;0U
Adder
7.987
274807UNIV PK N;3U
Adder
7.97
274811UNIV PK N;7U
Adder
7.918
970707AG2-453 GEN
Solar/Wind Harmer
44.159
274826FISK ;BP
Adder
17.21
274803UNIV PARK;6U
Adder
9.165
274887GEN-1.85
Solar/Wind Harmer
8.368
276772AC2-154 GEN
Solar/Wind Harmer
4.383
276843GEN-1.7
Solar/Wind Harmer
0.9
276806AD2-047 C O1
Solar/Wind Harmer
16.801
972259AH1-714 GEN
Adder
29.959
972038AH1-567 GEN2
Adder
0.573
939351AE1-166 GEN
Solar/Wind Harmer
9.267
274676JOLIET 29;8U
Adder
45.995
274730ELWOOD EC;6P
Adder
25.471
274734ELWOOD EC;8P
Adder
25.471
274736ELWOOD EC;9P
Adder
25.471
274729ELWOOD EC;1P
Adder
25.47
270102X2-052 ST
50/50
2.703
270100X2-052 CT1
50/50
2.497
270101X2-052 CT2
50/50
2.497
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.813
24729405KEY G3
50/50
0.622
24729305KEY G2
50/50
0.612
24729205KEY G1
50/50
0.609
970349AG2-230 GEN
Solar/Wind Harmer
26.907
965681AG1-436 GEN
Solar/Wind Harmer
20.943
965791AG1-447 GEN
Solar/Wind Harmer
10.715
961051AF2-396 GEN
Solar/Wind Harmer
26.405
961051AF2-396 GEN
Solar/Wind Harmer
12.281
274770LINCOLN ;1U
Adder
10.099
274771LINCOLN ;2U
Adder
10.099
274805UNIV PK N;1U
Adder
7.935
274808UNIV PK N;4U
Adder
7.883
274888KELLY CRK;1U
Solar/Wind Harmer
9.268
276776AD2-060 GEN
Solar/Wind Harmer
0.657
958011AF2-095 GEN
Solar/Wind Harmer
22.615
970941AG2-585 GEN
Solar/Wind Harmer
8.638
276897AD1-100 C
Solar/Wind Harmer
72.59
274674JOLIET 9 ;6U
Adder
23.881
276893AG1-478 C
Solar/Wind Harmer
0.679
944541AF1-119 GEN
Solar/Wind Harmer
6.389
960971AF2-388 GEN
Solar/Wind Harmer
16.678
274695ROCKY RD ;2P
Adder
16.86
274693ROCKY RD ;1P
Adder
16.694
274697ROCKY RD ;3P
Adder
4.58
274696ROCKY RD ;4P
Adder
17.257
958481AF2-142 GEN
Solar/Wind Harmer
22.69
274683WAUKEGAN ;8U
Adder
31.805
274683WAUKEGAN ;8U
Adder
26.81
962691AG1-118 GEN
Solar/Wind Harmer
45.034
960751AF2-366 GEN
Solar/Wind Harmer
4.294
958491AF2-143 GEN
Solar/Wind Harmer
22.353
276901AD2-066 C O1
Solar/Wind Harmer
5.211
270535AF1-215 GEN1
Solar/Wind Harmer
6.678
270536AF1-215 GEN2
Solar/Wind Harmer
6.678
971341AH1-150 GEN
Solar/Wind Harmer
29.275
971343AH1-151 GEN
Solar/Wind Harmer
29.275
276872AE1-163_GEN1
Solar/Wind Harmer
9.799
276876AE1-163_GEN2
Solar/Wind Harmer
9.799
972235AH1-702 GEN1
Adder
3.664
972236AH1-702 GEN2
Adder
3.186
938861AE1-114 GEN
Solar/Wind Harmer
11.755
274764LEE CO EC;5U
Adder
13.311
274765LEE CO EC;6U
Adder
13.311
274762LEE CO EC;3U
Adder
13.28
274763LEE CO EC;4U
Adder
13.154
247621Y3-024
Adder
0.265
270349AD2-093_GEN
Solar/Wind Helper
1.323
270471AD2-092_GEN
Solar/Wind Helper
1.323
24344005CKG1
50/50
10.972
270144AC1-141 ST1_
50/50
3.606
24641605TWIN BRNCH
50/50
0.029
24653605MOTTVILLE
50/50
0.006
943121AE2-341 GEN
Solar/Wind Harmer
23.078
943591AF1-030 GEN
Solar/Wind Harmer
15.385
274682WAUKEGAN ;7U
Adder
27.167
274862TOP CROP ;2U
Solar/Wind Harmer
7.646
276868AE1-113 GEN
Solar/Wind Harmer
14.986
274879MINONK ;1U
Solar/Wind Harmer
9.991
276799AD1-013 GEN
Solar/Wind Harmer
3.261
946671AF1-331 GEN
Solar/Wind Harmer
0.618
274855GSG-6 ;RU
Solar/Wind Harmer
5.445
274850MENDOTA H;RU
Solar/Wind Harmer
3.786
276602WESTBROOK C
Solar/Wind Harmer
3.134
959091AF2-200 GEN
Solar/Wind Harmer
29.275
970571AG2-364 GEN
Solar/Wind Harmer
28.757
274857EASY ROAD;U1
Solar/Wind Harmer
6.838
274760LEE CO EC;1U
Adder
13.28
274767LEE CO EC;8U
Adder
13.123
276603SUBLETTE C
Solar/Wind Harmer
1.494
964401AG1-302 GEN
Solar/Wind Harmer
12.872
24728505AND G1
Adder
3.549
24729505KEY G4
50/50
11.397
971771AH1-392 GEN
Solar/Wind Harmer
15.224
270071AF1-092 GEN
Solar/Wind Harmer
25.344
270526AF1-158 GEN
Solar/Wind Harmer
7.606
960681AF2-359 GEN
Solar/Wind Harmer
6.33
944161AF1-084 GEN
Solar/Wind Harmer
3.647
970031AG2-029 GEN
Solar/Wind Harmer
41.238
274775LINCOLN ;6U
Adder
10.099
274776LINCOLN ;7U
Adder
10.099
274777LINCOLN ;8U
Adder
10.099
959331AF2-224 GEN
Solar/Wind Harmer
15.97
274827FISK ;RP
Adder
12.197
972037AH1-567 GEN1
Adder
0.288
960591AF2-350 GEN
Solar/Wind Harmer
15.705
274800UNIV PARK;3U
Adder
9.152
274801UNIV PARK;4U
Adder
9.152
972228AH1-698 GEN2
Adder
5.813
972227AH1-698 GEN1
Adder
4.093
274687WILL CNTY;4U
Adder
43.508
274687WILL CNTY;4U
Adder
43.508
274675JOLIET 29;7U
Adder
47.699
274675JOLIET 29;7U
Adder
45.996
274728ELWOOD EC;5P
Adder
25.471
274731ELWOOD EC;2P
Adder
25.47
274733ELWOOD EC;3P
Adder
25.47
274735ELWOOD EC;4P
Adder
25.47
276893AG1-478 C
Solar/Wind Harmer
0.852
970833AG2-524 GEN
Solar/Wind Harmer
13.502
970833AG2-524 GEN
Solar/Wind Harmer
6.28
274744AC1-111 GEN8
Adder
8.582
274746AC1-111 G10
Adder
8.582
958711AF2-162 GEN
Solar/Wind Harmer
1.544
971549AH1-272 GEN
Solar/Wind Harmer
28.027
970073AG2-061 GEN
Solar/Wind Harmer
3.466
971411AH1-196 GEN
Solar/Wind Harmer
22.136
971675AH1-338 GEN
Solar/Wind Harmer
26.555
276861AD2-134 GEN
Solar/Wind Harmer
2.633
276863AD2-134 GEN
Solar/Wind Harmer
2.633
971171AH1-044 GEN
Solar/Wind Harmer
29.275
274863CRW1-WTG
Solar/Wind Harmer
8.159
274864CRW2-WTG
Solar/Wind Harmer
8.159
276889AE2-281 GEN
Solar/Wind Harmer
2.8
274823ROCKFORD ;21
Adder
28.408
274856ECOGROVE ;U1
Solar/Wind Harmer
4.873
276611AD2-172 GEN
Solar/Wind Harmer
3.697
276612AE2-035 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
6.176
971681AH1-341 GEN
Solar/Wind Harmer
21.518
970169AG2-114 GEN
Solar/Wind Harmer
14.308
963791AG1-232 GEN
Solar/Wind Harmer
19.213
972267AH1-718 GEN
Adder
5.871
24344105CKG2
50/50
14.069
270143AC1-141 CT2_
50/50
4.07
24639705ELKHART HY
50/50
0.273
970521AG2-332 GEN
50/50
19.38
24307105BERRINSP G
50/50
0.036
270216AD2-079_GEN
Solar/Wind Harmer
1.023
957891AF2-083 GEN
Solar/Wind Harmer
25.121
945111AF1-176 GEN
Solar/Wind Harmer
29.785
270449AD2-020 GEN
Solar/Wind Harmer
4.651
943021AE2-325 GEN
Solar/Wind Harmer
6.046
24441205WTRV SLR C
Solar/Wind Harmer
0.219
972207SS24-0001
Solar/Wind Harmer
35.905
274773LINCOLN ;4U
Adder
10.099
274774LINCOLN ;5U
Adder
10.099
965011AG1-365 GEN
Solar/Wind Harmer
15.97
274723RIVER EC ;12
Adder
28.574
274751CRETE EC ;1U
Adder
7.776
274754CRETE EC ;4U
Adder
7.776
274812UNIV PK N;8U
Adder
7.918
274802UNIV PARK;5U
Adder
9.165
941551AE2-152 GEN
Solar/Wind Harmer
7.087
274676JOLIET 29;8U
Adder
47.698
274674JOLIET 9 ;6U
Adder
23.881
274732ELWOOD EC;7P
Adder
25.471
274871GR RIDGE ;2U
Solar/Wind Harmer
11.885
274847GR RIDGE ;BU
Solar/Wind Harmer
7.815
274745AC1-111 GEN9
Adder
8.582
965651AG1-433 GEN
Solar/Wind Harmer
8.339
970373AG2-245 GEN
Solar/Wind Harmer
31.999
276694AA1-018 GEN2
Solar/Wind Harmer
9.544
276691AA1-018 GEN1
Solar/Wind Harmer
1.141
274682WAUKEGAN ;7U
Adder
27.167
274861TOP CROP ;1U
Solar/Wind Harmer
9.157
274828WAUKEGAN ;BP
Adder
16.671
962781AG1-127 GEN
Solar/Wind Harmer
14.233
274872LEEDK;1U
Solar/Wind Harmer
12.252
939401AE1-172 GEN
Solar/Wind Harmer
20.783
276805AD2-038 GEN
Solar/Wind Harmer
7.642
958861AF2-177 GEN
Solar/Wind Harmer
16.213
276882AE2-255 GEN
Solar/Wind Harmer
4.996
971997AH1-543 GEN
Solar/Wind Harmer
23.262
270055AF2-134 C O1
Solar/Wind Harmer
4.452
957471AF2-041 GEN
Solar/Wind Harmer
43.912
959081AF2-199 GEN
Solar/Wind Harmer
14.637
971067AG2-660 GEN
Solar/Wind Harmer
3.404
274822ROCKFORD ;11
Adder
28.615
970819AG2-516 GEN
Solar/Wind Harmer
17.376
970569AG2-363 GEN
Solar/Wind Harmer
43.135
274858EASY ROAD;U2
Solar/Wind Harmer
6.838
274761LEE CO EC;2U
Adder
13.28
274766LEE CO EC;7U
Adder
13.123
958381AF2-132 GEN
Solar/Wind Harmer
12.872
24728605AND G2
Adder
3.549
964861AG1-349 GEN
Solar/Wind Harmer
2.543
971917AH1-482 GEN
Solar/Wind Harmer
2.934
LAGNLTFEXP_LAGN->PJM
CLTF
9.729
TVALTFEXP_TVA->PJM
CLTF
3.517
NYPJM->LTFIMP_NY
CLTF
2.449
LGEELTFEXP_LGEE->PJM
CLTF
3.05
WECLTFEXP_WEC->PJM
CLTF
5.542
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.992
AG2-052LTFEXP_AG2-052->PJM
LTF
0.341
AH1-155LTFEXP_AH1-155->PJM
LTF
0.512
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.832
MECLTFEXP_MEC->PJM
CLTF
19.669
SIGELTFEXP_SIGE->PJM
CLTF
0.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.964

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11010___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11010___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.94 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4305.0
MW Contribution:
27.2
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11010___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.03 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5634.35
MW Contribution:
33.14
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.651
24729305KEY G2
50/50
0.64
24729205KEY G1
50/50
0.637
247620Y3-023
50/50
0.813
270102X2-052 ST
50/50
2.629
270100X2-052 CT1
50/50
2.429
270101X2-052 CT2
50/50
2.429
24643105BUCHANAN
50/50
0.021
970349AG2-230 GEN
Solar/Wind Harmer
26.286
961051AF2-396 GEN
Solar/Wind Harmer
25.955
961051AF2-396 GEN
Solar/Wind Harmer
12.072
965681AG1-436 GEN
Solar/Wind Harmer
20.368
965791AG1-447 GEN
Solar/Wind Harmer
10.421
944541AF1-119 GEN
Solar/Wind Harmer
6.65
960971AF2-388 GEN
Solar/Wind Harmer
17.358
274770LINCOLN ;1U
Adder
9.8
274771LINCOLN ;2U
Adder
9.8
274805UNIV PK N;1U
Adder
7.71
274808UNIV PK N;4U
Adder
7.659
274888KELLY CRK;1U
Solar/Wind Harmer
8.998
276776AD2-060 GEN
Solar/Wind Harmer
0.638
958011AF2-095 GEN
Solar/Wind Harmer
21.958
970941AG2-585 GEN
Solar/Wind Harmer
8.387
276897AD1-100 C
Solar/Wind Harmer
70.43
274674JOLIET 9 ;6U
Adder
23.181
276893AG1-478 C
Solar/Wind Harmer
0.659
942221AE2-234 GEN
Solar/Wind Harmer
5.15
274695ROCKY RD ;2P
Adder
16.363
274693ROCKY RD ;1P
Adder
16.202
274697ROCKY RD ;3P
Adder
4.445
274696ROCKY RD ;4P
Adder
16.748
958481AF2-142 GEN
Solar/Wind Harmer
22.019
274683WAUKEGAN ;8U
Adder
30.87
274683WAUKEGAN ;8U
Adder
26.022
962691AG1-118 GEN
Solar/Wind Harmer
43.703
944231AF1-091 GEN
Solar/Wind Harmer
26.155
960751AF2-366 GEN
Solar/Wind Harmer
4.167
958491AF2-143 GEN
Solar/Wind Harmer
21.687
276901AD2-066 C O1
Solar/Wind Harmer
5.054
971341AH1-150 GEN
Solar/Wind Harmer
28.407
971343AH1-151 GEN
Solar/Wind Harmer
28.407
276872AE1-163_GEN1
Solar/Wind Harmer
9.503
276876AE1-163_GEN2
Solar/Wind Harmer
9.503
972235AH1-702 GEN1
Adder
3.556
972236AH1-702 GEN2
Adder
3.092
270535AF1-215 GEN1
Solar/Wind Harmer
6.365
270536AF1-215 GEN2
Solar/Wind Harmer
6.365
274764LEE CO EC;5U
Adder
12.916
274765LEE CO EC;6U
Adder
12.916
274762LEE CO EC;3U
Adder
12.885
274763LEE CO EC;4U
Adder
12.764
247621Y3-024
Adder
0.272
270349AD2-093_GEN
Solar/Wind Helper
1.489
270471AD2-092_GEN
Solar/Wind Helper
1.489
938861AE1-114 GEN
Solar/Wind Harmer
10.898
24344105CKG2
50/50
13.662
270143AC1-141 CT2_
50/50
4
24639705ELKHART HY
50/50
0.271
970521AG2-332 GEN
50/50
19.317
24307105BERRINSP G
50/50
0.035
965011AG1-365 GEN
Solar/Wind Harmer
18.046
270216AD2-079_GEN
Solar/Wind Harmer
1.012
957891AF2-083 GEN
Solar/Wind Harmer
24.7
945111AF1-176 GEN
Solar/Wind Harmer
29.357
270449AD2-020 GEN
Solar/Wind Harmer
4.565
943021AE2-325 GEN
Solar/Wind Harmer
5.933
24441205WTRV SLR C
Solar/Wind Harmer
0.214
965651AG1-433 GEN
Solar/Wind Harmer
8.679
972207SS24-0001
Solar/Wind Harmer
34.843
274773LINCOLN ;4U
Adder
9.8
270142AC1-141 CT1_
50/50
4
24642205MAYFLWER
50/50
0.061
944961AF1-161 GEN
50/50
4.736
962601AG1-109 GEN
50/50
4.736
270043AE2-236 GEN
Solar/Wind Harmer
10.297
965021AG1-366 GEN
Solar/Wind Harmer
4.197
944531AF1-118 GEN
Solar/Wind Harmer
62.429
971347AH1-153 GEN
Solar/Wind Harmer
8.762
270063AE2-323 C
Solar/Wind Harmer
3.738
247643Z2-116 C
Solar/Wind Harmer
0.117
270505AE1-170 C O1
Solar/Wind Harmer
24.73
945111AF1-176 GEN
Solar/Wind Harmer
9.304
24441505OLIV SLR
Solar/Wind Harmer
0.219
274772LINCOLN ;3U
Adder
9.8
274724RIVER EC ;11
Adder
27.457
972231SS25-0005
Solar/Wind Harmer
14.674
972181SS23-001
Solar/Wind Harmer
9.171
274752CRETE EC ;2U
Adder
7.558
274753CRETE EC ;3U
Adder
7.558
276164X3-005 C
Solar/Wind Harmer
1.084
274814UNIV PK N;0U
Adder
7.76
274807UNIV PK N;3U
Adder
7.743
274811UNIV PK N;7U
Adder
7.693
970707AG2-453 GEN
Solar/Wind Harmer
42.855
274826FISK ;BP
Adder
16.714
274803UNIV PARK;6U
Adder
8.901
274887GEN-1.85
Solar/Wind Harmer
8.124
276772AC2-154 GEN
Solar/Wind Harmer
4.255
276843GEN-1.7
Solar/Wind Harmer
0.874
276806AD2-047 C O1
Solar/Wind Harmer
16.312
972038AH1-567 GEN2
Adder
0.556
972259AH1-714 GEN
Adder
29.077
939351AE1-166 GEN
Solar/Wind Harmer
8.991
274676JOLIET 29;8U
Adder
44.652
274730ELWOOD EC;6P
Adder
24.723
274734ELWOOD EC;8P
Adder
24.723
274736ELWOOD EC;9P
Adder
24.723
274729ELWOOD EC;1P
Adder
24.722
943121AE2-341 GEN
Solar/Wind Harmer
22.397
943591AF1-030 GEN
Solar/Wind Harmer
14.931
274682WAUKEGAN ;7U
Adder
26.369
274862TOP CROP ;2U
Solar/Wind Harmer
7.42
276868AE1-113 GEN
Solar/Wind Harmer
14.537
274879MINONK ;1U
Solar/Wind Harmer
9.692
276799AD1-013 GEN
Solar/Wind Harmer
3.164
946671AF1-331 GEN
Solar/Wind Harmer
0.6
274855GSG-6 ;RU
Solar/Wind Harmer
5.284
274850MENDOTA H;RU
Solar/Wind Harmer
3.673
276602WESTBROOK C
Solar/Wind Harmer
3.042
959091AF2-200 GEN
Solar/Wind Harmer
28.407
970571AG2-364 GEN
Solar/Wind Harmer
27.882
274760LEE CO EC;1U
Adder
12.885
274767LEE CO EC;8U
Adder
12.734
24728505AND G1
Adder
3.46
24729505KEY G4
50/50
11.921
24641605TWIN BRNCH
50/50
0.029
270144AC1-141 ST1_
50/50
3.545
24344005CKG1
50/50
10.701
24653605MOTTVILLE
50/50
0.006
959331AF2-224 GEN
Solar/Wind Harmer
18.046
270071AF1-092 GEN
Solar/Wind Harmer
26.047
970031AG2-029 GEN
Solar/Wind Harmer
42.785
971771AH1-392 GEN
Solar/Wind Harmer
14.954
270526AF1-158 GEN
Solar/Wind Harmer
7.436
960681AF2-359 GEN
Solar/Wind Harmer
6.157
944161AF1-084 GEN
Solar/Wind Harmer
3.574
958711AF2-162 GEN
Solar/Wind Harmer
1.607
274775LINCOLN ;6U
Adder
9.8
274776LINCOLN ;7U
Adder
9.8
274777LINCOLN ;8U
Adder
9.8
274827FISK ;RP
Adder
11.846
972037AH1-567 GEN1
Adder
0.279
960591AF2-350 GEN
Solar/Wind Harmer
15.248
274800UNIV PARK;3U
Adder
8.887
274801UNIV PARK;4U
Adder
8.887
972228AH1-698 GEN2
Adder
5.643
972227AH1-698 GEN1
Adder
3.973
963791AG1-232 GEN
Solar/Wind Harmer
20.548
274687WILL CNTY;4U
Adder
42.241
274687WILL CNTY;4U
Adder
42.241
274675JOLIET 29;7U
Adder
46.307
274675JOLIET 29;7U
Adder
44.653
274728ELWOOD EC;5P
Adder
24.723
274731ELWOOD EC;2P
Adder
24.722
274733ELWOOD EC;3P
Adder
24.722
274735ELWOOD EC;4P
Adder
24.722
276893AG1-478 C
Solar/Wind Harmer
0.827
970833AG2-524 GEN
Solar/Wind Harmer
13.102
970833AG2-524 GEN
Solar/Wind Harmer
6.094
274744AC1-111 GEN8
Adder
8.328
274746AC1-111 G10
Adder
8.328
971549AH1-272 GEN
Solar/Wind Harmer
27.198
945581AF1-223 GEN
Solar/Wind Harmer
6.582
965041AG1-368 GEN
Solar/Wind Harmer
14.485
970073AG2-061 GEN
Solar/Wind Harmer
3.362
971411AH1-196 GEN
Solar/Wind Harmer
21.482
971675AH1-338 GEN
Solar/Wind Harmer
25.768
276861AD2-134 GEN
Solar/Wind Harmer
2.555
276863AD2-134 GEN
Solar/Wind Harmer
2.555
971171AH1-044 GEN
Solar/Wind Harmer
28.407
274863CRW1-WTG
Solar/Wind Harmer
7.901
274864CRW2-WTG
Solar/Wind Harmer
7.901
276889AE2-281 GEN
Solar/Wind Harmer
2.715
274823ROCKFORD ;21
Adder
27.568
274856ECOGROVE ;U1
Solar/Wind Harmer
4.729
276611AD2-172 GEN
Solar/Wind Harmer
3.587
276612AE2-035 GEN
Solar/Wind Harmer
3.587
926823AC1-168 GEN
Solar/Wind Harmer
5.986
971681AH1-341 GEN
Solar/Wind Harmer
20.879
972267AH1-718 GEN
Adder
5.696
274774LINCOLN ;5U
Adder
9.8
274723RIVER EC ;12
Adder
27.774
274751CRETE EC ;1U
Adder
7.558
274754CRETE EC ;4U
Adder
7.558
958861AF2-177 GEN
Solar/Wind Harmer
16.844
274812UNIV PK N;8U
Adder
7.693
274802UNIV PARK;5U
Adder
8.901
941551AE2-152 GEN
Solar/Wind Harmer
6.876
274676JOLIET 29;8U
Adder
46.306
274674JOLIET 9 ;6U
Adder
23.181
274732ELWOOD EC;7P
Adder
24.723
274871GR RIDGE ;2U
Solar/Wind Harmer
11.532
274847GR RIDGE ;BU
Solar/Wind Harmer
7.583
274745AC1-111 GEN9
Adder
8.328
276694AA1-018 GEN2
Solar/Wind Harmer
9.262
276691AA1-018 GEN1
Solar/Wind Harmer
1.107
274682WAUKEGAN ;7U
Adder
26.369
274861TOP CROP ;1U
Solar/Wind Harmer
8.887
274828WAUKEGAN ;BP
Adder
16.181
970373AG2-245 GEN
Solar/Wind Harmer
30.663
962781AG1-127 GEN
Solar/Wind Harmer
13.812
945371AF1-202 GEN
Solar/Wind Harmer
10.125
274872LEEDK;1U
Solar/Wind Harmer
11.89
276805AD2-038 GEN
Solar/Wind Harmer
7.414
939401AE1-172 GEN
Solar/Wind Harmer
20.136
276882AE2-255 GEN
Solar/Wind Harmer
4.846
971997AH1-543 GEN
Solar/Wind Harmer
22.557
957471AF2-041 GEN
Solar/Wind Harmer
42.611
959081AF2-199 GEN
Solar/Wind Harmer
14.204
971067AG2-660 GEN
Solar/Wind Harmer
3.303
274822ROCKFORD ;11
Adder
27.77
970819AG2-516 GEN
Solar/Wind Harmer
16.862
270055AF2-134 C O1
Solar/Wind Harmer
4.243
970569AG2-363 GEN
Solar/Wind Harmer
41.823
274761LEE CO EC;2U
Adder
12.885
274766LEE CO EC;7U
Adder
12.734
24728605AND G2
Adder
3.46
LAGNLTFEXP_LAGN->PJM
CLTF
9.779
TVALTFEXP_TVA->PJM
CLTF
3.619
NYPJM->LTFIMP_NY
CLTF
2.337
LGEELTFEXP_LGEE->PJM
CLTF
2.867
WECLTFEXP_WEC->PJM
CLTF
5.379
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.687
AG2-052LTFEXP_AG2-052->PJM
LTF
0.33
AH1-155LTFEXP_AH1-155->PJM
LTF
0.495
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
160.996
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.967
MECLTFEXP_MEC->PJM
CLTF
19.101
SIGELTFEXP_SIGE->PJM
CLTF
0.332
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.977

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#9287_1679_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#9287_1679_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.12 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4271.28
MW Contribution:
24.69
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.628
24642205MAYFLWER
50/50
0.07
944961AF1-161 GEN
50/50
5.457
962601AG1-109 GEN
50/50
5.457
274772LINCOLN ;3U
50/50
16.742
971347AH1-153 GEN
Solar/Wind Harmer
7.293
270505AE1-170 C O1
Solar/Wind Harmer
13.912
945111AF1-176 GEN
Solar/Wind Harmer
10.605
270043AE2-236 GEN
Solar/Wind Harmer
8.283
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
31.767
970707AG2-453 GEN
Solar/Wind Harmer
40.791
274752CRETE EC ;2U
Adder
14.651
274753CRETE EC ;3U
Adder
14.651
972259AH1-714 GEN
Adder
33.857
274814UNIV PK N;0U
Adder
8.953
274807UNIV PK N;3U
Adder
8.934
274811UNIV PK N;7U
Adder
8.876
274826FISK ;BP
Adder
19.361
274887GEN-1.85
Solar/Wind Harmer
0.321
276843GEN-1.7
Solar/Wind Harmer
0.399
276806AD2-047 C O1
Solar/Wind Harmer
6.988
274803UNIV PARK;6U
Adder
10.298
972038AH1-567 GEN2
Adder
0.644
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
51.744
274729ELWOOD EC;1P
Adder
28.61
274730ELWOOD EC;6P
Adder
28.611
274734ELWOOD EC;8P
Adder
28.611
274736ELWOOD EC;9P
Adder
28.611
943121AE2-341 GEN
Solar/Wind Harmer
20.29
943591AF1-030 GEN
Solar/Wind Harmer
13.493
944531AF1-118 GEN
Solar/Wind Harmer
53.775
274682WAUKEGAN ;7U
Adder
30.457
274862TOP CROP ;2U
Solar/Wind Harmer
1.588
965021AG1-366 GEN
Solar/Wind Harmer
3.852
946671AF1-331 GEN
Solar/Wind Harmer
1.226
274855GSG-6 ;RU
Solar/Wind Harmer
0.419
274850MENDOTA H;RU
Solar/Wind Harmer
0.133
276868AE1-113 GEN
Solar/Wind Harmer
2.296
274879MINONK ;1U
Solar/Wind Harmer
0.479
959091AF2-200 GEN
Solar/Wind Harmer
22.754
970571AG2-364 GEN
Solar/Wind Harmer
22.087
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
14.712
274767LEE CO EC;8U
Adder
14.538
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.353
965931AG1-462 GEN
Solar/Wind Harmer
26.286
971087AG2-675 GEN
Solar/Wind Harmer
5.498
965091AG1-374 GEN
Solar/Wind Harmer
29.5
959611AF2-252 GEN
Solar/Wind Harmer
3.278
964401AG1-302 GEN
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.055
24695305TIMB G C
Solar/Wind Harmer
0.742
957381AF2-032 GEN
Solar/Wind Harmer
1.822
942481AE2-261 GEN
Solar/Wind Harmer
23.884
270004AE1-209 GEN
Solar/Wind Harmer
1.716
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.272
946031AF1-268 GEN
Solar/Wind Harmer
7.057
970825AG2-519 GEN
Solar/Wind Harmer
5.584
246938BC-WTG3
Solar/Wind Harmer
0.259
270491AE1-102 GEN2
Solar/Wind Harmer
0.935
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.599
24386205FR-12G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.679
270102X2-052 ST
50/50
3.04
270100X2-052 CT1
50/50
2.808
270101X2-052 CT2
50/50
2.808
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
16.742
274771LINCOLN ;2U
50/50
16.742
247620Y3-023
50/50
0.894
970349AG2-230 GEN
Solar/Wind Harmer
21.879
965681AG1-436 GEN
Solar/Wind Harmer
16.375
965791AG1-447 GEN
Solar/Wind Harmer
12.008
961051AF2-396 GEN
Solar/Wind Harmer
26.182
961051AF2-396 GEN
Solar/Wind Harmer
17.455
274805UNIV PK N;1U
Adder
8.895
274808UNIV PK N;4U
Adder
8.837
274888KELLY CRK;1U
Solar/Wind Harmer
0.719
276776AD2-060 GEN
Solar/Wind Harmer
1.315
958011AF2-095 GEN
Solar/Wind Harmer
17.758
970941AG2-585 GEN
Solar/Wind Harmer
6.782
276897AD1-100 C
Solar/Wind Harmer
30.703
274674JOLIET 9 ;6U
Adder
26.849
276893AG1-478 C
Solar/Wind Harmer
0.809
274695ROCKY RD ;2P
Adder
18.919
274693ROCKY RD ;1P
Adder
18.733
274697ROCKY RD ;3P
Adder
5.139
274696ROCKY RD ;4P
Adder
19.364
274683WAUKEGAN ;8U
Adder
35.646
274683WAUKEGAN ;8U
Adder
30.048
958481AF2-142 GEN
Solar/Wind Harmer
17.657
962691AG1-118 GEN
Solar/Wind Harmer
35.208
958491AF2-143 GEN
Solar/Wind Harmer
17.33
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
22.754
971343AH1-151 GEN
Solar/Wind Harmer
22.754
972235AH1-702 GEN1
Adder
4.077
972236AH1-702 GEN2
Adder
3.545
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
6.286
274764LEE CO EC;5U
Adder
14.746
274765LEE CO EC;6U
Adder
14.746
274762LEE CO EC;3U
Adder
14.712
274763LEE CO EC;4U
Adder
14.573
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.741
276645AC1-214 GEN1
Solar/Wind Harmer
0.418
24344005CKG1
50/50
12.668
270144AC1-141 ST1_
50/50
4.102
24641605TWIN BRNCH
50/50
0.033
274775LINCOLN ;6U
50/50
16.742
274776LINCOLN ;7U
50/50
16.742
274777LINCOLN ;8U
50/50
16.742
24653605MOTTVILLE
50/50
0.007
971771AH1-392 GEN
Solar/Wind Harmer
13.283
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274827FISK ;RP
Adder
13.721
972228AH1-698 GEN2
Adder
6.549
972227AH1-698 GEN1
Adder
4.611
960591AF2-350 GEN
Solar/Wind Harmer
12.332
972037AH1-567 GEN1
Adder
0.323
274800UNIV PARK;3U
Adder
10.294
274801UNIV PARK;4U
Adder
10.294
274687WILL CNTY;4U
Adder
48.934
274687WILL CNTY;4U
Adder
48.934
274675JOLIET 29;7U
Adder
53.662
274675JOLIET 29;7U
Adder
51.745
274728ELWOOD EC;5P
Adder
28.611
274731ELWOOD EC;2P
Adder
28.61
274733ELWOOD EC;3P
Adder
28.61
274735ELWOOD EC;4P
Adder
28.61
970833AG2-524 GEN
Solar/Wind Harmer
13.35
970833AG2-524 GEN
Solar/Wind Harmer
8.9
274744AC1-111 GEN8
Adder
9.659
274746AC1-111 G10
Adder
9.659
970031AG2-029 GEN
Solar/Wind Harmer
6.498
971549AH1-272 GEN
Solar/Wind Harmer
24.686
24729505KEY G4
Adder
10.795
959331AF2-224 GEN
Solar/Wind Harmer
8.089
970073AG2-061 GEN
Solar/Wind Harmer
3.851
971411AH1-196 GEN
Solar/Wind Harmer
17.237
971675AH1-338 GEN
Solar/Wind Harmer
4.48
276861AD2-134 GEN
Solar/Wind Harmer
0.205
276863AD2-134 GEN
Solar/Wind Harmer
0.205
971171AH1-044 GEN
Solar/Wind Harmer
22.754
274823ROCKFORD ;21
Adder
31.63
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.262
971681AH1-341 GEN
Solar/Wind Harmer
17.867
926823AC1-168 GEN
Solar/Wind Harmer
1.875
270071AF1-092 GEN
Solar/Wind Harmer
21.116
970169AG2-114 GEN
Solar/Wind Harmer
10.885
972267AH1-718 GEN
Adder
6.485
276741O09 GEN1
Solar/Wind Harmer
0.381
274877BISHOP HL;1U
Solar/Wind Harmer
0.353
946321AF1-296 GEN
Solar/Wind Harmer
5.822
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.652
963791AG1-232 GEN
Solar/Wind Harmer
13.422
965041AG1-368 GEN
Solar/Wind Harmer
9.865
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.327
965051AG1-369 GEN
Solar/Wind Harmer
4.508
276668AB2-070 GEN1
Solar/Wind Harmer
0.345
276848AB2-070 GEN3
Solar/Wind Harmer
0.343
276849AB2-070 GEN2
Solar/Wind Harmer
0.345
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.357
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.686
964611AG1-324 GEN
Solar/Wind Harmer
2.923
944221AF1-090 GEN
Solar/Wind Harmer
4.332
944541AF1-119 GEN
Solar/Wind Harmer
0.704
960971AF2-388 GEN
Solar/Wind Harmer
6.177
944231AF1-091 GEN
Solar/Wind Harmer
23.61
942111AE2-223 GEN
Solar/Wind Harmer
3.297
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
3.278
942221AE2-234 GEN
Solar/Wind Harmer
3.817
270246TR4_N_V150
Solar/Wind Harmer
0.058
270247TR4_N_V136
Solar/Wind Harmer
0.058
276615X2-022 GEN
Solar/Wind Harmer
0.088
276838X2-022 GEN2
Solar/Wind Harmer
0.479
270031AE2-169
Solar/Wind Harmer
4.571
270599AE1-208 GEN
Solar/Wind Harmer
7.618
276916AD2-100_GEN
Solar/Wind Harmer
16.489
276911AD2-131_GEN
Solar/Wind Harmer
1.086
970623AG2-406 GEN
Solar/Wind Harmer
1.389
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.562
246937BC-WTG2
Solar/Wind Harmer
0.29
247607V1-011 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.098
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.721
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
6.198
970885AG2-551 GEN
Solar/Wind Harmer
2.066
970291AG2-192 GEN
Solar/Wind Harmer
0.802
970291AG2-192 GEN
Solar/Wind Harmer
0.37
970241AG2-163 GEN
Solar/Wind Harmer
3.55
270349AD2-093_GEN
Solar/Wind Helper
1.46
270471AD2-092_GEN
Solar/Wind Helper
1.46
24344105CKG2
50/50
17.101
270143AC1-141 CT2_
50/50
4.628
274773LINCOLN ;4U
50/50
16.742
274774LINCOLN ;5U
50/50
16.742
24307105BERRINSP G
50/50
0.04
24639705ELKHART HY
50/50
0.302
247604X1-042
50/50
0.044
970521AG2-332 GEN
50/50
21.337
957891AF2-083 GEN
Solar/Wind Harmer
21.973
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.836
945111AF1-176 GEN
Solar/Wind Harmer
23.345
274723RIVER EC ;12
Adder
32.119
274751CRETE EC ;1U
Adder
14.651
274754CRETE EC ;4U
Adder
14.651
274812UNIV PK N;8U
Adder
8.876
274802UNIV PARK;5U
Adder
10.298
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.66
274674JOLIET 9 ;6U
Adder
26.849
274732ELWOOD EC;7P
Adder
28.611
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.659
274682WAUKEGAN ;7U
Adder
30.457
274828WAUKEGAN ;BP
Adder
18.685
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.913
274861TOP CROP ;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
11.128
274872LEEDK;1U
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
11.556
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
8.623
276882AE2-255 GEN
Solar/Wind Harmer
1.339
971997AH1-543 GEN
Solar/Wind Harmer
6.007
957471AF2-041 GEN
Solar/Wind Harmer
34.131
959081AF2-199 GEN
Solar/Wind Harmer
11.377
971067AG2-660 GEN
Solar/Wind Harmer
3.792
274822ROCKFORD ;11
Adder
31.861
970819AG2-516 GEN
Solar/Wind Harmer
13.478
970569AG2-363 GEN
Solar/Wind Harmer
33.131
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
14.712
274766LEE CO EC;7U
Adder
14.538
276708O09 GEN2
Solar/Wind Harmer
0.381
970373AG2-245 GEN
Solar/Wind Harmer
22.393
276646AC1-214 GEN2
Solar/Wind Harmer
0.418
965651AG1-433 GEN
Solar/Wind Harmer
3.089
274848CAMPGROVE;RU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.409
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
14.202
270055AF2-134 C O1
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.626
276621W2-048 GEN
Solar/Wind Harmer
0.426
270024AE2-089 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.598
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.911
270007AE1-245 C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.271
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.716
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
9.838
965421AG1-410 GEN
Solar/Wind Harmer
22.84
970825AG2-519 GEN
Solar/Wind Harmer
2.631
246936BC-WTG1
Solar/Wind Harmer
0.29
270489AE1-102 GEN1
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.078
270594AE1-207 GEN
Solar/Wind Harmer
7.228
270032AE2-172
Solar/Wind Harmer
4.303
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
6.868
963741AG1-226 GEN
Solar/Wind Harmer
14.404
963841AG1-237 GEN
Solar/Wind Harmer
2.694
270543AE2-219 C
Solar/Wind Harmer
4.339
970289AG2-191 GEN
Solar/Wind Harmer
1.173
LAGNLTFEXP_LAGN->PJM
CLTF
9.08
TVALTFEXP_TVA->PJM
CLTF
3.004
NYPJM->LTFIMP_NY
CLTF
2.551
LGEELTFEXP_LGEE->PJM
CLTF
1.869
WECLTFEXP_WEC->PJM
CLTF
6.165
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.118
AG2-052LTFEXP_AG2-052->PJM
LTF
0.357
AH1-155LTFEXP_AH1-155->PJM
LTF
0.535
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
184.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.09
MECLTFEXP_MEC->PJM
CLTF
20.956
SIGELTFEXP_SIGE->PJM
CLTF
0.265
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.536

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11087___SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11087___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.11 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4270.92
MW Contribution:
27.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.843
24729305KEY G2
50/50
0.829
24729205KEY G1
50/50
0.824
247620Y3-023
50/50
0.804
270102X2-052 ST
50/50
2.593
270100X2-052 CT1
50/50
2.396
270101X2-052 CT2
50/50
2.396
24643105BUCHANAN
50/50
0.021
944541AF1-119 GEN
Solar/Wind Harmer
9.386
960971AF2-388 GEN
Solar/Wind Harmer
24.501
970349AG2-230 GEN
Solar/Wind Harmer
26.041
961051AF2-396 GEN
Solar/Wind Harmer
25.785
961051AF2-396 GEN
Solar/Wind Harmer
11.993
965681AG1-436 GEN
Solar/Wind Harmer
20.057
965791AG1-447 GEN
Solar/Wind Harmer
10.262
274770LINCOLN ;1U
Adder
9.548
274771LINCOLN ;2U
Adder
9.548
274805UNIV PK N;1U
Adder
7.501
274808UNIV PK N;4U
Adder
7.452
274888KELLY CRK;1U
Solar/Wind Harmer
8.737
276776AD2-060 GEN
Solar/Wind Harmer
0.62
958011AF2-095 GEN
Solar/Wind Harmer
21.32
970941AG2-585 GEN
Solar/Wind Harmer
8.143
276897AD1-100 C
Solar/Wind Harmer
68.272
274674JOLIET 9 ;6U
Adder
22.471
944231AF1-091 GEN
Solar/Wind Harmer
26.227
276893AG1-478 C
Solar/Wind Harmer
0.639
274696ROCKY RD ;4P
Adder
16.191
274695ROCKY RD ;2P
Adder
15.818
274693ROCKY RD ;1P
Adder
15.663
274697ROCKY RD ;3P
Adder
4.297
958481AF2-142 GEN
Solar/Wind Harmer
21.274
274683WAUKEGAN ;8U
Adder
29.837
274683WAUKEGAN ;8U
Adder
25.151
962691AG1-118 GEN
Solar/Wind Harmer
42.204
960751AF2-366 GEN
Solar/Wind Harmer
4.023
958491AF2-143 GEN
Solar/Wind Harmer
20.909
276901AD2-066 C O1
Solar/Wind Harmer
4.868
971341AH1-150 GEN
Solar/Wind Harmer
27.351
971343AH1-151 GEN
Solar/Wind Harmer
27.351
276872AE1-163_GEN1
Solar/Wind Harmer
9.134
276876AE1-163_GEN2
Solar/Wind Harmer
9.134
270535AF1-215 GEN1
Solar/Wind Harmer
6.165
270536AF1-215 GEN2
Solar/Wind Harmer
6.165
972235AH1-702 GEN1
Adder
3.422
972236AH1-702 GEN2
Adder
2.975
938861AE1-114 GEN
Solar/Wind Harmer
10.955
274764LEE CO EC;5U
Adder
12.398
274765LEE CO EC;6U
Adder
12.398
274762LEE CO EC;3U
Adder
12.369
274763LEE CO EC;4U
Adder
12.252
270349AD2-093_GEN
Solar/Wind Helper
1.352
270471AD2-092_GEN
Solar/Wind Helper
1.352
270142AC1-141 CT1_
50/50
3.972
24642205MAYFLWER
50/50
0.06
944961AF1-161 GEN
50/50
4.708
962601AG1-109 GEN
50/50
4.708
944531AF1-118 GEN
Solar/Wind Harmer
78.519
270043AE2-236 GEN
Solar/Wind Harmer
10.234
971347AH1-153 GEN
Solar/Wind Harmer
8.68
965021AG1-366 GEN
Solar/Wind Harmer
3.909
270063AE2-323 C
Solar/Wind Harmer
3.683
247643Z2-116 C
Solar/Wind Harmer
0.115
270505AE1-170 C O1
Solar/Wind Harmer
24.563
945111AF1-176 GEN
Solar/Wind Harmer
9.233
24441505OLIV SLR
Solar/Wind Harmer
0.216
274772LINCOLN ;3U
Adder
9.548
274724RIVER EC ;11
Adder
26.744
972231SS25-0005
Solar/Wind Harmer
14.298
972181SS23-001
Solar/Wind Harmer
8.936
274752CRETE EC ;2U
Adder
7.364
274753CRETE EC ;3U
Adder
7.364
276164X3-005 C
Solar/Wind Harmer
1.055
274814UNIV PK N;0U
Adder
7.55
274807UNIV PK N;3U
Adder
7.533
274811UNIV PK N;7U
Adder
7.484
970707AG2-453 GEN
Solar/Wind Harmer
41.611
274826FISK ;BP
Adder
16.239
274803UNIV PARK;6U
Adder
8.648
972038AH1-567 GEN2
Adder
0.54
274887GEN-1.85
Solar/Wind Harmer
7.888
276772AC2-154 GEN
Solar/Wind Harmer
4.132
276843GEN-1.7
Solar/Wind Harmer
0.849
276806AD2-047 C O1
Solar/Wind Harmer
15.838
972259AH1-714 GEN
Adder
28.221
939351AE1-166 GEN
Solar/Wind Harmer
8.716
274676JOLIET 29;8U
Adder
43.306
274730ELWOOD EC;6P
Adder
23.961
274734ELWOOD EC;8P
Adder
23.961
274736ELWOOD EC;9P
Adder
23.961
274729ELWOOD EC;1P
Adder
23.96
943121AE2-341 GEN
Solar/Wind Harmer
21.689
943591AF1-030 GEN
Solar/Wind Harmer
14.459
274682WAUKEGAN ;7U
Adder
25.491
274862TOP CROP ;2U
Solar/Wind Harmer
7.169
276868AE1-113 GEN
Solar/Wind Harmer
14.002
274879MINONK ;1U
Solar/Wind Harmer
9.335
276799AD1-013 GEN
Solar/Wind Harmer
3.05
946671AF1-331 GEN
Solar/Wind Harmer
0.578
274855GSG-6 ;RU
Solar/Wind Harmer
5.091
274850MENDOTA H;RU
Solar/Wind Harmer
3.54
276602WESTBROOK C
Solar/Wind Harmer
2.931
959091AF2-200 GEN
Solar/Wind Harmer
27.351
970571AG2-364 GEN
Solar/Wind Harmer
26.739
274857EASY ROAD;U1
Solar/Wind Harmer
6.369
274760LEE CO EC;1U
Adder
12.369
274767LEE CO EC;8U
Adder
12.223
276603SUBLETTE C
Solar/Wind Harmer
1.391
24729505KEY G4
50/50
15.44
270144AC1-141 ST1_
50/50
3.52
24641605TWIN BRNCH
50/50
0.029
24344005CKG1
50/50
10.642
24653605MOTTVILLE
50/50
0.006
958711AF2-162 GEN
Solar/Wind Harmer
2.268
945581AF1-223 GEN
Solar/Wind Harmer
10.161
270071AF1-092 GEN
Solar/Wind Harmer
25.377
959331AF2-224 GEN
Solar/Wind Harmer
16.808
970031AG2-029 GEN
Solar/Wind Harmer
41.911
971771AH1-392 GEN
Solar/Wind Harmer
14.805
270526AF1-158 GEN
Solar/Wind Harmer
7.346
944161AF1-084 GEN
Solar/Wind Harmer
3.556
960681AF2-359 GEN
Solar/Wind Harmer
6.063
274775LINCOLN ;6U
Adder
9.548
274776LINCOLN ;7U
Adder
9.548
274777LINCOLN ;8U
Adder
9.548
971549AH1-272 GEN
Solar/Wind Harmer
27.449
274827FISK ;RP
Adder
11.509
972037AH1-567 GEN1
Adder
0.271
274800UNIV PARK;3U
Adder
8.632
274801UNIV PARK;4U
Adder
8.632
960591AF2-350 GEN
Solar/Wind Harmer
14.805
972228AH1-698 GEN2
Adder
5.477
972227AH1-698 GEN1
Adder
3.857
274687WILL CNTY;4U
Adder
40.979
274687WILL CNTY;4U
Adder
40.979
274675JOLIET 29;7U
Adder
44.911
274675JOLIET 29;7U
Adder
43.307
274728ELWOOD EC;5P
Adder
23.961
274731ELWOOD EC;2P
Adder
23.96
274733ELWOOD EC;3P
Adder
23.96
274735ELWOOD EC;4P
Adder
23.96
276893AG1-478 C
Solar/Wind Harmer
0.801
970833AG2-524 GEN
Solar/Wind Harmer
12.689
970833AG2-524 GEN
Solar/Wind Harmer
5.902
274744AC1-111 GEN8
Adder
8.063
274746AC1-111 G10
Adder
8.063
965041AG1-368 GEN
Solar/Wind Harmer
14.212
970073AG2-061 GEN
Solar/Wind Harmer
3.242
971411AH1-196 GEN
Solar/Wind Harmer
20.707
971675AH1-338 GEN
Solar/Wind Harmer
24.832
276861AD2-134 GEN
Solar/Wind Harmer
2.462
276863AD2-134 GEN
Solar/Wind Harmer
2.462
971171AH1-044 GEN
Solar/Wind Harmer
27.351
274823ROCKFORD ;21
Adder
26.536
276889AE2-281 GEN
Solar/Wind Harmer
2.61
274863CRW1-WTG
Solar/Wind Harmer
7.572
274864CRW2-WTG
Solar/Wind Harmer
7.572
274856ECOGROVE ;U1
Solar/Wind Harmer
4.546
276611AD2-172 GEN
Solar/Wind Harmer
3.449
276612AE2-035 GEN
Solar/Wind Harmer
3.449
971681AH1-341 GEN
Solar/Wind Harmer
20.052
926823AC1-168 GEN
Solar/Wind Harmer
5.737
972267AH1-718 GEN
Adder
5.459
970169AG2-114 GEN
Solar/Wind Harmer
7.94
24344105CKG2
50/50
13.551
270143AC1-141 CT2_
50/50
3.972
24639705ELKHART HY
50/50
0.268
970521AG2-332 GEN
50/50
19.098
24307105BERRINSP G
50/50
0.034
247604X1-042
50/50
0.038
965651AG1-433 GEN
Solar/Wind Harmer
12.251
958861AF2-177 GEN
Solar/Wind Harmer
24.497
945371AF1-202 GEN
Solar/Wind Harmer
15.631
965011AG1-365 GEN
Solar/Wind Harmer
16.808
270216AD2-079_GEN
Solar/Wind Harmer
1.003
957891AF2-083 GEN
Solar/Wind Harmer
24.519
945111AF1-176 GEN
Solar/Wind Harmer
29.132
270449AD2-020 GEN
Solar/Wind Harmer
4.538
943021AE2-325 GEN
Solar/Wind Harmer
5.899
24441205WTRV SLR C
Solar/Wind Harmer
0.214
972207SS24-0001
Solar/Wind Harmer
33.946
274773LINCOLN ;4U
Adder
9.548
274774LINCOLN ;5U
Adder
9.548
274723RIVER EC ;12
Adder
27.053
274751CRETE EC ;1U
Adder
7.364
274754CRETE EC ;4U
Adder
7.364
274812UNIV PK N;8U
Adder
7.484
274802UNIV PARK;5U
Adder
8.648
941551AE2-152 GEN
Solar/Wind Harmer
6.666
274676JOLIET 29;8U
Adder
44.91
274674JOLIET 9 ;6U
Adder
22.471
274732ELWOOD EC;7P
Adder
23.961
274871GR RIDGE ;2U
Solar/Wind Harmer
11.169
274847GR RIDGE ;BU
Solar/Wind Harmer
7.344
274745AC1-111 GEN9
Adder
8.063
970373AG2-245 GEN
Solar/Wind Harmer
29.843
274682WAUKEGAN ;7U
Adder
25.491
276694AA1-018 GEN2
Solar/Wind Harmer
8.949
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274861TOP CROP ;1U
Solar/Wind Harmer
8.586
274828WAUKEGAN ;BP
Adder
15.64
962781AG1-127 GEN
Solar/Wind Harmer
13.334
274872LEEDK;1U
Solar/Wind Harmer
11.474
276805AD2-038 GEN
Solar/Wind Harmer
7.148
939401AE1-172 GEN
Solar/Wind Harmer
19.364
276882AE2-255 GEN
Solar/Wind Harmer
4.668
971997AH1-543 GEN
Solar/Wind Harmer
21.709
957471AF2-041 GEN
Solar/Wind Harmer
41.026
959081AF2-199 GEN
Solar/Wind Harmer
13.675
971067AG2-660 GEN
Solar/Wind Harmer
3.18
274822ROCKFORD ;11
Adder
26.729
270055AF2-134 C O1
Solar/Wind Harmer
4.11
970819AG2-516 GEN
Solar/Wind Harmer
16.217
970569AG2-363 GEN
Solar/Wind Harmer
40.109
274858EASY ROAD;U2
Solar/Wind Harmer
6.369
274761LEE CO EC;2U
Adder
12.369
274766LEE CO EC;7U
Adder
12.223
LAGNLTFEXP_LAGN->PJM
CLTF
8.172
TVALTFEXP_TVA->PJM
CLTF
2.793
NYPJM->LTFIMP_NY
CLTF
2.22
LGEELTFEXP_LGEE->PJM
CLTF
1.872
WECLTFEXP_WEC->PJM
CLTF
5.176
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.893
AG2-052LTFEXP_AG2-052->PJM
LTF
0.316
AH1-155LTFEXP_AH1-155->PJM
LTF
0.474
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.417
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.531
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.443
MECLTFEXP_MEC->PJM
CLTF
17.903
SIGELTFEXP_SIGE->PJM
CLTF
0.245
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.447

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.58 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4166.12
MW Contribution:
25.47
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.51 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5405.77
MW Contribution:
30.83
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
3.706
24642205MAYFLWER
50/50
0.056
944961AF1-161 GEN
50/50
4.391
962601AG1-109 GEN
50/50
4.391
270043AE2-236 GEN
Solar/Wind Harmer
9.148
971347AH1-153 GEN
Solar/Wind Harmer
8.171
944531AF1-118 GEN
Solar/Wind Harmer
55.502
247643Z2-116 C
Solar/Wind Harmer
0.107
270063AE2-323 C
Solar/Wind Harmer
3.364
270505AE1-170 C O1
Solar/Wind Harmer
22.912
945111AF1-176 GEN
Solar/Wind Harmer
8.593
24441505OLIV SLR
Solar/Wind Harmer
0.203
965021AG1-366 GEN
Solar/Wind Harmer
3.44
274772LINCOLN ;3U
Adder
9.151
274724RIVER EC ;11
Adder
25.556
972231SS25-0005
Solar/Wind Harmer
13.649
972181SS23-001
Solar/Wind Harmer
8.531
274752CRETE EC ;2U
Adder
7.03
274753CRETE EC ;3U
Adder
7.03
276164X3-005 C
Solar/Wind Harmer
1.009
274814UNIV PK N;0U
Adder
7.222
274807UNIV PK N;3U
Adder
7.207
274811UNIV PK N;7U
Adder
7.16
970707AG2-453 GEN
Solar/Wind Harmer
39.966
274826FISK ;BP
Adder
15.565
274803UNIV PARK;6U
Adder
8.288
972259AH1-714 GEN
Adder
27.103
274887GEN-1.85
Solar/Wind Harmer
7.567
276772AC2-154 GEN
Solar/Wind Harmer
3.964
276843GEN-1.7
Solar/Wind Harmer
0.814
276806AD2-047 C O1
Solar/Wind Harmer
15.194
972038AH1-567 GEN2
Adder
0.518
939351AE1-166 GEN
Solar/Wind Harmer
8.379
274676JOLIET 29;8U
Adder
41.593
274729ELWOOD EC;1P
Adder
23.027
274730ELWOOD EC;6P
Adder
23.027
274734ELWOOD EC;8P
Adder
23.027
274736ELWOOD EC;9P
Adder
23.027
943121AE2-341 GEN
Solar/Wind Harmer
20.872
943591AF1-030 GEN
Solar/Wind Harmer
13.915
274682WAUKEGAN ;7U
Adder
24.557
274862TOP CROP ;2U
Solar/Wind Harmer
6.907
276868AE1-113 GEN
Solar/Wind Harmer
13.528
274879MINONK ;1U
Solar/Wind Harmer
9.019
276799AD1-013 GEN
Solar/Wind Harmer
2.946
946671AF1-331 GEN
Solar/Wind Harmer
0.558
274855GSG-6 ;RU
Solar/Wind Harmer
4.919
274850MENDOTA H;RU
Solar/Wind Harmer
3.42
276602WESTBROOK C
Solar/Wind Harmer
2.832
959091AF2-200 GEN
Solar/Wind Harmer
26.442
970571AG2-364 GEN
Solar/Wind Harmer
25.929
274857EASY ROAD;U1
Solar/Wind Harmer
6.173
274760LEE CO EC;1U
Adder
11.987
274767LEE CO EC;8U
Adder
11.846
270144AC1-141 ST1_
50/50
3.285
24344005CKG1
50/50
9.982
24641605TWIN BRNCH
50/50
0.027
24729505KEY G4
50/50
10.601
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
23.135
24344105CKG2
50/50
12.842
270143AC1-141 CT2_
50/50
3.706
24639705ELKHART HY
50/50
0.248
970521AG2-332 GEN
50/50
17.662
24307105BERRINSP G
50/50
0.032
270216AD2-079_GEN
Solar/Wind Harmer
0.932
957891AF2-083 GEN
Solar/Wind Harmer
22.862
945111AF1-176 GEN
Solar/Wind Harmer
27.114
270449AD2-020 GEN
Solar/Wind Harmer
4.232
943021AE2-325 GEN
Solar/Wind Harmer
5.501
24441205WTRV SLR C
Solar/Wind Harmer
0.199
965011AG1-365 GEN
Solar/Wind Harmer
14.791
972207SS24-0001
Solar/Wind Harmer
32.535
274773LINCOLN ;4U
Adder
9.151
274774LINCOLN ;5U
Adder
9.151
274723RIVER EC ;12
Adder
25.85
274751CRETE EC ;1U
Adder
7.03
274754CRETE EC ;4U
Adder
7.03
274812UNIV PK N;8U
Adder
7.16
274802UNIV PARK;5U
Adder
8.288
965651AG1-433 GEN
Solar/Wind Harmer
7.723
941551AE2-152 GEN
Solar/Wind Harmer
6.408
274676JOLIET 29;8U
Adder
43.134
274674JOLIET 9 ;6U
Adder
21.593
274732ELWOOD EC;7P
Adder
23.027
274871GR RIDGE ;2U
Solar/Wind Harmer
10.745
274847GR RIDGE ;BU
Solar/Wind Harmer
7.065
274745AC1-111 GEN9
Adder
7.76
958861AF2-177 GEN
Solar/Wind Harmer
14.991
274682WAUKEGAN ;7U
Adder
24.557
276694AA1-018 GEN2
Solar/Wind Harmer
8.621
276691AA1-018 GEN1
Solar/Wind Harmer
1.03
274861TOP CROP ;1U
Solar/Wind Harmer
8.272
274828WAUKEGAN ;BP
Adder
15.069
970373AG2-245 GEN
Solar/Wind Harmer
28.422
962781AG1-127 GEN
Solar/Wind Harmer
12.863
274872LEEDK;1U
Solar/Wind Harmer
11.072
276805AD2-038 GEN
Solar/Wind Harmer
6.899
939401AE1-172 GEN
Solar/Wind Harmer
18.745
276882AE2-255 GEN
Solar/Wind Harmer
4.509
971997AH1-543 GEN
Solar/Wind Harmer
20.995
957471AF2-041 GEN
Solar/Wind Harmer
39.664
959081AF2-199 GEN
Solar/Wind Harmer
13.221
971771AH1-392 GEN
Solar/Wind Harmer
13.843
270526AF1-158 GEN
Solar/Wind Harmer
6.901
960681AF2-359 GEN
Solar/Wind Harmer
5.729
970031AG2-029 GEN
Solar/Wind Harmer
37.809
944161AF1-084 GEN
Solar/Wind Harmer
3.317
959331AF2-224 GEN
Solar/Wind Harmer
14.791
274775LINCOLN ;6U
Adder
9.151
274776LINCOLN ;7U
Adder
9.151
274777LINCOLN ;8U
Adder
9.151
274827FISK ;RP
Adder
11.031
972037AH1-567 GEN1
Adder
0.26
960591AF2-350 GEN
Solar/Wind Harmer
14.203
274800UNIV PARK;3U
Adder
8.277
274801UNIV PARK;4U
Adder
8.277
972228AH1-698 GEN2
Adder
5.257
972227AH1-698 GEN1
Adder
3.702
958711AF2-162 GEN
Solar/Wind Harmer
1.429
274687WILL CNTY;4U
Adder
39.344
274687WILL CNTY;4U
Adder
39.344
274675JOLIET 29;7U
Adder
43.134
274675JOLIET 29;7U
Adder
41.594
274728ELWOOD EC;5P
Adder
23.027
274731ELWOOD EC;2P
Adder
23.027
274733ELWOOD EC;3P
Adder
23.027
274735ELWOOD EC;4P
Adder
23.027
276893AG1-478 C
Solar/Wind Harmer
0.77
970833AG2-524 GEN
Solar/Wind Harmer
12.207
970833AG2-524 GEN
Solar/Wind Harmer
5.678
274744AC1-111 GEN8
Adder
7.76
274746AC1-111 G10
Adder
7.76
971549AH1-272 GEN
Solar/Wind Harmer
25.468
970073AG2-061 GEN
Solar/Wind Harmer
3.129
971411AH1-196 GEN
Solar/Wind Harmer
19.999
971675AH1-338 GEN
Solar/Wind Harmer
23.99
276861AD2-134 GEN
Solar/Wind Harmer
2.379
276863AD2-134 GEN
Solar/Wind Harmer
2.379
971171AH1-044 GEN
Solar/Wind Harmer
26.442
274863CRW1-WTG
Solar/Wind Harmer
7.351
274864CRW2-WTG
Solar/Wind Harmer
7.351
274823ROCKFORD ;21
Adder
25.659
276889AE2-281 GEN
Solar/Wind Harmer
2.526
963791AG1-232 GEN
Solar/Wind Harmer
17.669
274856ECOGROVE ;U1
Solar/Wind Harmer
4.4
276611AD2-172 GEN
Solar/Wind Harmer
3.338
276612AE2-035 GEN
Solar/Wind Harmer
3.338
926823AC1-168 GEN
Solar/Wind Harmer
5.568
971681AH1-341 GEN
Solar/Wind Harmer
19.426
945581AF1-223 GEN
Solar/Wind Harmer
5.86
972267AH1-718 GEN
Adder
5.298
970169AG2-114 GEN
Solar/Wind Harmer
0.069
971067AG2-660 GEN
Solar/Wind Harmer
3.075
274822ROCKFORD ;11
Adder
25.846
970819AG2-516 GEN
Solar/Wind Harmer
15.692
270055AF2-134 C O1
Solar/Wind Harmer
3.927
970569AG2-363 GEN
Solar/Wind Harmer
38.894
945371AF1-202 GEN
Solar/Wind Harmer
9.015
274858EASY ROAD;U2
Solar/Wind Harmer
6.173
274761LEE CO EC;2U
Adder
11.987
274766LEE CO EC;7U
Adder
11.846
24729405KEY G3
50/50
0.579
24729305KEY G2
50/50
0.569
24729205KEY G1
50/50
0.566
270102X2-052 ST
50/50
2.448
270100X2-052 CT1
50/50
2.261
270101X2-052 CT2
50/50
2.261
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.742
970349AG2-230 GEN
Solar/Wind Harmer
24.512
965681AG1-436 GEN
Solar/Wind Harmer
18.953
965791AG1-447 GEN
Solar/Wind Harmer
9.697
961051AF2-396 GEN
Solar/Wind Harmer
24.029
961051AF2-396 GEN
Solar/Wind Harmer
11.176
274770LINCOLN ;1U
Adder
9.151
274771LINCOLN ;2U
Adder
9.151
274805UNIV PK N;1U
Adder
7.175
274808UNIV PK N;4U
Adder
7.128
274888KELLY CRK;1U
Solar/Wind Harmer
8.381
276776AD2-060 GEN
Solar/Wind Harmer
0.595
958011AF2-095 GEN
Solar/Wind Harmer
20.452
970941AG2-585 GEN
Solar/Wind Harmer
7.812
944541AF1-119 GEN
Solar/Wind Harmer
5.917
960971AF2-388 GEN
Solar/Wind Harmer
15.445
276897AD1-100 C
Solar/Wind Harmer
65.634
274674JOLIET 9 ;6U
Adder
21.593
276893AG1-478 C
Solar/Wind Harmer
0.614
274695ROCKY RD ;2P
Adder
15.241
274693ROCKY RD ;1P
Adder
15.091
274697ROCKY RD ;3P
Adder
4.14
274696ROCKY RD ;4P
Adder
15.6
958481AF2-142 GEN
Solar/Wind Harmer
20.495
274683WAUKEGAN ;8U
Adder
28.748
274683WAUKEGAN ;8U
Adder
24.233
962691AG1-118 GEN
Solar/Wind Harmer
40.703
960751AF2-366 GEN
Solar/Wind Harmer
3.881
958491AF2-143 GEN
Solar/Wind Harmer
20.181
276901AD2-066 C O1
Solar/Wind Harmer
4.703
971341AH1-150 GEN
Solar/Wind Harmer
26.442
971343AH1-151 GEN
Solar/Wind Harmer
26.442
276872AE1-163_GEN1
Solar/Wind Harmer
8.84
276876AE1-163_GEN2
Solar/Wind Harmer
8.84
972235AH1-702 GEN1
Adder
3.31
972236AH1-702 GEN2
Adder
2.878
270535AF1-215 GEN1
Solar/Wind Harmer
5.891
270536AF1-215 GEN2
Solar/Wind Harmer
5.891
944231AF1-091 GEN
Solar/Wind Harmer
23.318
938861AE1-114 GEN
Solar/Wind Harmer
10.612
942221AE2-234 GEN
Solar/Wind Harmer
4.526
274764LEE CO EC;5U
Adder
12.016
274765LEE CO EC;6U
Adder
12.016
274762LEE CO EC;3U
Adder
11.987
274763LEE CO EC;4U
Adder
11.875
247621Y3-024
Adder
0.24
270349AD2-093_GEN
Solar/Wind Helper
1.399
270471AD2-092_GEN
Solar/Wind Helper
1.399
LAGNLTFEXP_LAGN->PJM
CLTF
8.841
TVALTFEXP_TVA->PJM
CLTF
3.224
NYPJM->LTFIMP_NY
CLTF
2.224
LGEELTFEXP_LGEE->PJM
CLTF
2.572
WECLTFEXP_WEC->PJM
CLTF
5.005
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.748
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.458
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.319
CBM West 1LTFEXP_CBM-W1->PJM
CBM
152.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.46
MECLTFEXP_MEC->PJM
CLTF
17.697
SIGELTFEXP_SIGE->PJM
CLTF
0.3
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.129

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.54 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4164.42
MW Contribution:
26.29
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.92 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5422.72
MW Contribution:
31.92
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.593
24729305KEY G2
50/50
0.582
24729205KEY G1
50/50
0.579
247620Y3-023
50/50
0.762
270102X2-052 ST
50/50
2.487
270100X2-052 CT1
50/50
2.298
270101X2-052 CT2
50/50
2.298
24643105BUCHANAN
50/50
0.02
970349AG2-230 GEN
Solar/Wind Harmer
24.878
961051AF2-396 GEN
Solar/Wind Harmer
24.588
961051AF2-396 GEN
Solar/Wind Harmer
11.436
965681AG1-436 GEN
Solar/Wind Harmer
19.26
965791AG1-447 GEN
Solar/Wind Harmer
9.854
274770LINCOLN ;1U
Adder
9.268
274771LINCOLN ;2U
Adder
9.268
274805UNIV PK N;1U
Adder
7.278
274808UNIV PK N;4U
Adder
7.231
944541AF1-119 GEN
Solar/Wind Harmer
6.059
960971AF2-388 GEN
Solar/Wind Harmer
15.817
274888KELLY CRK;1U
Solar/Wind Harmer
8.497
958011AF2-095 GEN
Solar/Wind Harmer
20.735
970941AG2-585 GEN
Solar/Wind Harmer
7.919
276776AD2-060 GEN
Solar/Wind Harmer
0.603
276897AD1-100 C
Solar/Wind Harmer
66.515
274674JOLIET 9 ;6U
Adder
21.887
276893AG1-478 C
Solar/Wind Harmer
0.622
274695ROCKY RD ;2P
Adder
15.445
274693ROCKY RD ;1P
Adder
15.293
274697ROCKY RD ;3P
Adder
4.196
274696ROCKY RD ;4P
Adder
15.809
958481AF2-142 GEN
Solar/Wind Harmer
20.777
274683WAUKEGAN ;8U
Adder
29.135
274683WAUKEGAN ;8U
Adder
24.56
944231AF1-091 GEN
Solar/Wind Harmer
24.809
962691AG1-118 GEN
Solar/Wind Harmer
41.245
960751AF2-366 GEN
Solar/Wind Harmer
3.932
958491AF2-143 GEN
Solar/Wind Harmer
20.457
276901AD2-066 C O1
Solar/Wind Harmer
4.767
971341AH1-150 GEN
Solar/Wind Harmer
26.795
971343AH1-151 GEN
Solar/Wind Harmer
26.795
942221AE2-234 GEN
Solar/Wind Harmer
4.687
276872AE1-163_GEN1
Solar/Wind Harmer
8.96
276876AE1-163_GEN2
Solar/Wind Harmer
8.96
972235AH1-702 GEN1
Adder
3.354
972236AH1-702 GEN2
Adder
2.916
270535AF1-215 GEN1
Solar/Wind Harmer
5.982
270536AF1-215 GEN2
Solar/Wind Harmer
5.982
274764LEE CO EC;5U
Adder
12.176
270142AC1-141 CT1_
50/50
3.786
24642205MAYFLWER
50/50
0.057
944961AF1-161 GEN
50/50
4.493
962601AG1-109 GEN
50/50
4.493
270043AE2-236 GEN
Solar/Wind Harmer
9.415
971347AH1-153 GEN
Solar/Wind Harmer
8.293
944531AF1-118 GEN
Solar/Wind Harmer
56.817
270063AE2-323 C
Solar/Wind Harmer
3.473
247643Z2-116 C
Solar/Wind Harmer
0.11
965021AG1-366 GEN
Solar/Wind Harmer
3.655
270505AE1-170 C O1
Solar/Wind Harmer
23.422
945111AF1-176 GEN
Solar/Wind Harmer
8.794
24441505OLIV SLR
Solar/Wind Harmer
0.207
274772LINCOLN ;3U
Adder
9.268
274724RIVER EC ;11
Adder
25.925
972231SS25-0005
Solar/Wind Harmer
13.851
972181SS23-001
Solar/Wind Harmer
8.657
274752CRETE EC ;2U
Adder
7.134
274753CRETE EC ;3U
Adder
7.134
276164X3-005 C
Solar/Wind Harmer
1.023
274814UNIV PK N;0U
Adder
7.326
274807UNIV PK N;3U
Adder
7.31
274811UNIV PK N;7U
Adder
7.263
970707AG2-453 GEN
Solar/Wind Harmer
40.492
274826FISK ;BP
Adder
15.782
274803UNIV PARK;6U
Adder
8.404
274887GEN-1.85
Solar/Wind Harmer
7.672
276843GEN-1.7
Solar/Wind Harmer
0.825
276772AC2-154 GEN
Solar/Wind Harmer
4.018
276806AD2-047 C O1
Solar/Wind Harmer
15.404
972259AH1-714 GEN
Adder
27.466
972038AH1-567 GEN2
Adder
0.525
939351AE1-166 GEN
Solar/Wind Harmer
8.492
274676JOLIET 29;8U
Adder
42.161
274730ELWOOD EC;6P
Adder
23.342
274734ELWOOD EC;8P
Adder
23.342
274736ELWOOD EC;9P
Adder
23.342
274729ELWOOD EC;1P
Adder
23.341
943121AE2-341 GEN
Solar/Wind Harmer
21.149
943591AF1-030 GEN
Solar/Wind Harmer
14.099
274682WAUKEGAN ;7U
Adder
24.888
274862TOP CROP ;2U
Solar/Wind Harmer
7.001
276868AE1-113 GEN
Solar/Wind Harmer
13.712
274879MINONK ;1U
Solar/Wind Harmer
9.142
276799AD1-013 GEN
Solar/Wind Harmer
2.985
946671AF1-331 GEN
Solar/Wind Harmer
0.566
274855GSG-6 ;RU
Solar/Wind Harmer
4.985
274850MENDOTA H;RU
Solar/Wind Harmer
3.466
276602WESTBROOK C
Solar/Wind Harmer
2.869
959091AF2-200 GEN
Solar/Wind Harmer
26.795
970571AG2-364 GEN
Solar/Wind Harmer
26.281
274760LEE CO EC;1U
Adder
12.147
274767LEE CO EC;8U
Adder
12.004
270284AF1-227 GEN1
Solar/Wind Helper
2.463
270287AF1-227 GEN3
Solar/Wind Helper
0.904
24344105CKG2
50/50
12.998
270143AC1-141 CT2_
50/50
3.786
24639705ELKHART HY
50/50
0.255
970521AG2-332 GEN
50/50
18.115
24307105BERRINSP G
50/50
0.033
247604X1-042
50/50
0.036
270216AD2-079_GEN
Solar/Wind Harmer
0.953
965011AG1-365 GEN
Solar/Wind Harmer
15.718
957891AF2-083 GEN
Solar/Wind Harmer
23.376
945111AF1-176 GEN
Solar/Wind Harmer
27.748
270449AD2-020 GEN
Solar/Wind Harmer
4.33
943021AE2-325 GEN
Solar/Wind Harmer
5.628
24441205WTRV SLR C
Solar/Wind Harmer
0.204
972207SS24-0001
Solar/Wind Harmer
32.952
274773LINCOLN ;4U
Adder
9.268
274774LINCOLN ;5U
Adder
9.268
274723RIVER EC ;12
Adder
26.223
274751CRETE EC ;1U
Adder
7.134
274754CRETE EC ;4U
Adder
7.134
270144AC1-141 ST1_
50/50
3.355
24344005CKG1
50/50
10.183
24729505KEY G4
50/50
10.853
24641605TWIN BRNCH
50/50
0.027
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
23.728
959331AF2-224 GEN
Solar/Wind Harmer
15.718
971771AH1-392 GEN
Solar/Wind Harmer
14.124
970031AG2-029 GEN
Solar/Wind Harmer
39.158
270526AF1-158 GEN
Solar/Wind Harmer
7.03
960681AF2-359 GEN
Solar/Wind Harmer
5.822
944161AF1-084 GEN
Solar/Wind Harmer
3.395
274775LINCOLN ;6U
Adder
9.268
274776LINCOLN ;7U
Adder
9.268
274777LINCOLN ;8U
Adder
9.268
958711AF2-162 GEN
Solar/Wind Harmer
1.464
274827FISK ;RP
Adder
11.185
972037AH1-567 GEN1
Adder
0.264
960591AF2-350 GEN
Solar/Wind Harmer
14.399
274800UNIV PARK;3U
Adder
8.392
274801UNIV PARK;4U
Adder
8.392
972228AH1-698 GEN2
Adder
5.329
972227AH1-698 GEN1
Adder
3.752
274687WILL CNTY;4U
Adder
39.884
274687WILL CNTY;4U
Adder
39.884
274675JOLIET 29;7U
Adder
43.724
274675JOLIET 29;7U
Adder
42.162
971549AH1-272 GEN
Solar/Wind Harmer
26.288
274728ELWOOD EC;5P
Adder
23.342
274731ELWOOD EC;2P
Adder
23.341
274733ELWOOD EC;3P
Adder
23.341
274735ELWOOD EC;4P
Adder
23.341
276893AG1-478 C
Solar/Wind Harmer
0.781
970833AG2-524 GEN
Solar/Wind Harmer
12.371
970833AG2-524 GEN
Solar/Wind Harmer
5.754
274744AC1-111 GEN8
Adder
7.864
274746AC1-111 G10
Adder
7.864
963791AG1-232 GEN
Solar/Wind Harmer
18.586
965041AG1-368 GEN
Solar/Wind Harmer
13.667
970073AG2-061 GEN
Solar/Wind Harmer
3.172
971411AH1-196 GEN
Solar/Wind Harmer
20.266
971675AH1-338 GEN
Solar/Wind Harmer
24.31
276861AD2-134 GEN
Solar/Wind Harmer
2.41
276863AD2-134 GEN
Solar/Wind Harmer
2.41
971171AH1-044 GEN
Solar/Wind Harmer
26.795
274863CRW1-WTG
Solar/Wind Harmer
7.45
274864CRW2-WTG
Solar/Wind Harmer
7.45
274823ROCKFORD ;21
Adder
26.002
276889AE2-281 GEN
Solar/Wind Harmer
2.56
945581AF1-223 GEN
Solar/Wind Harmer
6.004
274856ECOGROVE ;U1
Solar/Wind Harmer
4.459
276611AD2-172 GEN
Solar/Wind Harmer
3.383
276612AE2-035 GEN
Solar/Wind Harmer
3.383
926823AC1-168 GEN
Solar/Wind Harmer
5.643
971681AH1-341 GEN
Solar/Wind Harmer
19.685
972267AH1-718 GEN
Adder
5.369
274812UNIV PK N;8U
Adder
7.263
965651AG1-433 GEN
Solar/Wind Harmer
7.909
274802UNIV PARK;5U
Adder
8.404
941551AE2-152 GEN
Solar/Wind Harmer
6.494
274676JOLIET 29;8U
Adder
43.723
274674JOLIET 9 ;6U
Adder
21.887
274732ELWOOD EC;7P
Adder
23.342
274871GR RIDGE ;2U
Solar/Wind Harmer
10.889
274847GR RIDGE ;BU
Solar/Wind Harmer
7.16
274745AC1-111 GEN9
Adder
7.864
958861AF2-177 GEN
Solar/Wind Harmer
15.354
276694AA1-018 GEN2
Solar/Wind Harmer
8.74
276691AA1-018 GEN1
Solar/Wind Harmer
1.045
274682WAUKEGAN ;7U
Adder
24.888
274861TOP CROP ;1U
Solar/Wind Harmer
8.385
274828WAUKEGAN ;BP
Adder
15.272
970373AG2-245 GEN
Solar/Wind Harmer
28.867
962781AG1-127 GEN
Solar/Wind Harmer
13.035
274872LEEDK;1U
Solar/Wind Harmer
11.22
276805AD2-038 GEN
Solar/Wind Harmer
6.993
939401AE1-172 GEN
Solar/Wind Harmer
18.996
276882AE2-255 GEN
Solar/Wind Harmer
4.571
971997AH1-543 GEN
Solar/Wind Harmer
21.278
957471AF2-041 GEN
Solar/Wind Harmer
40.193
959081AF2-199 GEN
Solar/Wind Harmer
13.398
971067AG2-660 GEN
Solar/Wind Harmer
3.116
274822ROCKFORD ;11
Adder
26.192
970819AG2-516 GEN
Solar/Wind Harmer
15.902
945371AF1-202 GEN
Solar/Wind Harmer
9.236
270055AF2-134 C O1
Solar/Wind Harmer
3.988
970569AG2-363 GEN
Solar/Wind Harmer
39.422
274761LEE CO EC;2U
Adder
12.147
274766LEE CO EC;7U
Adder
12.004
270286AF1-227 GEN2
Solar/Wind Helper
0.904
274765LEE CO EC;6U
Adder
12.176
274762LEE CO EC;3U
Adder
12.147
274763LEE CO EC;4U
Adder
12.033
247621Y3-024
Adder
0.249
270349AD2-093_GEN
Solar/Wind Helper
1.583
270471AD2-092_GEN
Solar/Wind Helper
1.583
938861AE1-114 GEN
Solar/Wind Harmer
10.275
LAGNLTFEXP_LAGN->PJM
CLTF
8.91
TVALTFEXP_TVA->PJM
CLTF
3.239
NYPJM->LTFIMP_NY
CLTF
2.259
LGEELTFEXP_LGEE->PJM
CLTF
2.616
WECLTFEXP_WEC->PJM
CLTF
5.072
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.466
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.348
CBM West 1LTFEXP_CBM-W1->PJM
CBM
157.25
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.547
MECLTFEXP_MEC->PJM
CLTF
17.928
SIGELTFEXP_SIGE->PJM
CLTF
0.305
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.085

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-022T_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-022T_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.55 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:2089.8
MW Contribution:
25.85
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
944961AF1-161 GEN
50/50
2.637
962601AG1-109 GEN
50/50
2.637
270505AE1-170 C O1
Solar/Wind Harmer
12.905
945111AF1-176 GEN
Solar/Wind Harmer
4.799
247643Z2-116 C
Solar/Wind Harmer
0.053
24441505OLIV SLR
Solar/Wind Harmer
0.098
971347AH1-153 GEN
Solar/Wind Harmer
3.328
270063AE2-323 C
Solar/Wind Harmer
1.303
972231SS25-0005
Solar/Wind Harmer
5.592
972181SS23-001
Solar/Wind Harmer
3.495
274752CRETE EC ;2U
Adder
2.88
274753CRETE EC ;3U
Adder
2.88
274724RIVER EC ;11
Adder
10.289
274814UNIV PK N;0U
Adder
2.914
274807UNIV PK N;3U
Adder
2.908
274811UNIV PK N;7U
Adder
2.889
276164X3-005 C
Solar/Wind Harmer
0.402
274803UNIV PARK;6U
Adder
3.299
274826FISK ;BP
Adder
6.177
964401AG1-302 GEN
Solar/Wind Harmer
5.114
972038AH1-567 GEN2
Adder
0.205
274887GEN-1.85
Solar/Wind Harmer
2.987
276772AC2-154 GEN
Solar/Wind Harmer
1.565
276843GEN-1.7
Solar/Wind Harmer
0.321
276806AD2-047 C O1
Solar/Wind Harmer
5.998
274772LINCOLN ;3U
Adder
3.459
274676JOLIET 29;8U
Adder
16.383
972259AH1-714 GEN
Adder
10.554
274729ELWOOD EC;1P
Adder
9.071
274730ELWOOD EC;6P
Adder
9.072
274734ELWOOD EC;8P
Adder
9.072
274736ELWOOD EC;9P
Adder
9.072
939351AE1-166 GEN
Solar/Wind Harmer
3.267
970707AG2-453 GEN
Solar/Wind Harmer
15.412
274862TOP CROP ;2U
Solar/Wind Harmer
2.742
943121AE2-341 GEN
Solar/Wind Harmer
8.126
943591AF1-030 GEN
Solar/Wind Harmer
5.417
274682WAUKEGAN ;7U
Adder
9.659
276868AE1-113 GEN
Solar/Wind Harmer
5.362
274879MINONK ;1U
Solar/Wind Harmer
3.575
276799AD1-013 GEN
Solar/Wind Harmer
1.159
946671AF1-331 GEN
Solar/Wind Harmer
0.22
274855GSG-6 ;RU
Solar/Wind Harmer
1.936
274850MENDOTA H;RU
Solar/Wind Harmer
1.346
276602WESTBROOK C
Solar/Wind Harmer
1.115
961051AF2-396 GEN
Solar/Wind Harmer
14.056
961051AF2-396 GEN
Solar/Wind Harmer
6.538
247620Y3-023
Adder
0.331
965681AG1-436 GEN
Solar/Wind Harmer
8.463
965791AG1-447 GEN
Solar/Wind Harmer
4.33
970349AG2-230 GEN
Solar/Wind Harmer
9.984
270535AF1-215 GEN1
Solar/Wind Harmer
2.67
270536AF1-215 GEN2
Solar/Wind Harmer
2.67
274805UNIV PK N;1U
Adder
2.895
274808UNIV PK N;4U
Adder
2.876
274888KELLY CRK;1U
Solar/Wind Harmer
3.309
276776AD2-060 GEN
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
8.074
970941AG2-585 GEN
Solar/Wind Harmer
3.084
274770LINCOLN ;1U
Adder
3.459
274771LINCOLN ;2U
Adder
3.459
276893AG1-478 C
Solar/Wind Harmer
0.242
274674JOLIET 9 ;6U
Adder
8.497
276897AD1-100 C
Solar/Wind Harmer
25.593
958481AF2-142 GEN
Solar/Wind Harmer
8.131
274696ROCKY RD ;4P
Adder
6.118
274695ROCKY RD ;2P
Adder
5.977
274693ROCKY RD ;1P
Adder
5.918
274697ROCKY RD ;3P
Adder
1.624
274683WAUKEGAN ;8U
Adder
11.31
274683WAUKEGAN ;8U
Adder
9.534
958491AF2-143 GEN
Solar/Wind Harmer
8.016
962691AG1-118 GEN
Solar/Wind Harmer
15.961
276901AD2-066 C O1
Solar/Wind Harmer
1.861
960751AF2-366 GEN
Solar/Wind Harmer
1.523
276872AE1-163_GEN1
Solar/Wind Harmer
3.518
276876AE1-163_GEN2
Solar/Wind Harmer
3.518
971341AH1-150 GEN
Solar/Wind Harmer
10.43
971343AH1-151 GEN
Solar/Wind Harmer
10.43
972235AH1-702 GEN1
Adder
1.308
972236AH1-702 GEN2
Adder
1.137
274764LEE CO EC;5U
Adder
4.765
274765LEE CO EC;6U
Adder
4.765
274762LEE CO EC;3U
Adder
4.753
274763LEE CO EC;4U
Adder
4.709
241996AE2-282_GEN
Solar/Wind Helper
2.772
241808AF1-120 C
Solar/Wind Helper
1.549
247522W1-056 GEN
Solar/Wind Helper
0.794
247604X1-042
50/50
0.026
24307105BERRINSP G
50/50
0.02
24441205WTRV SLR C
Solar/Wind Harmer
0.137
270449AD2-020 GEN
Solar/Wind Harmer
2.542
943021AE2-325 GEN
Solar/Wind Harmer
3.304
957891AF2-083 GEN
Solar/Wind Harmer
12.756
945111AF1-176 GEN
Solar/Wind Harmer
15.144
270216AD2-079_GEN
Solar/Wind Harmer
0.459
24639705ELKHART HY
Adder
0.115
970373AG2-245 GEN
Solar/Wind Harmer
12.863
274751CRETE EC ;1U
Adder
2.88
274754CRETE EC ;4U
Adder
2.88
270055AF2-134 C O1
Solar/Wind Harmer
1.78
274723RIVER EC ;12
Adder
10.412
274812UNIV PK N;8U
Adder
2.889
274802UNIV PARK;5U
Adder
3.299
958381AF2-132 GEN
Solar/Wind Harmer
5.114
964861AG1-349 GEN
Solar/Wind Harmer
4.411
971917AH1-482 GEN
Solar/Wind Harmer
5.089
972207SS24-0001
Solar/Wind Harmer
12.298
274773LINCOLN ;4U
Adder
3.459
274774LINCOLN ;5U
Adder
3.459
274676JOLIET 29;8U
Adder
16.99
274732ELWOOD EC;7P
Adder
9.072
274674JOLIET 9 ;6U
Adder
8.497
941551AE2-152 GEN
Solar/Wind Harmer
2.499
274871GR RIDGE ;2U
Solar/Wind Harmer
4.2
274847GR RIDGE ;BU
Solar/Wind Harmer
2.761
274745AC1-111 GEN9
Adder
3.031
274861TOP CROP ;1U
Solar/Wind Harmer
3.284
276694AA1-018 GEN2
Solar/Wind Harmer
3.42
276691AA1-018 GEN1
Solar/Wind Harmer
0.409
274682WAUKEGAN ;7U
Adder
9.659
274828WAUKEGAN ;BP
Adder
5.929
276805AD2-038 GEN
Solar/Wind Harmer
2.74
962781AG1-127 GEN
Solar/Wind Harmer
5.047
276882AE2-255 GEN
Solar/Wind Harmer
1.787
274872LEEDK;1U
Solar/Wind Harmer
4.347
940581AE2-045 GEN
Solar/Wind Harmer
5.396
971605AH1-302 GEN
Solar/Wind Harmer
4.614
939401AE1-172 GEN
Solar/Wind Harmer
7.352
971997AH1-543 GEN
Solar/Wind Harmer
8.282
957471AF2-041 GEN
Solar/Wind Harmer
15.644
959081AF2-199 GEN
Solar/Wind Harmer
5.215
971067AG2-660 GEN
Solar/Wind Harmer
1.213
274822ROCKFORD ;11
Adder
10.209
970819AG2-516 GEN
Solar/Wind Harmer
6.206
970569AG2-363 GEN
Solar/Wind Harmer
15.499
274761LEE CO EC;2U
Adder
4.753
274766LEE CO EC;7U
Adder
4.697
241840AF1-064_GEN
Solar/Wind Helper
1.561
241807AE2-176_GEN
Solar/Wind Helper
1.818
241885AC2-103 GEN1
Solar/Wind Helper
2.422
960841AF2-375 GEN
Solar/Wind Helper
1.504
958961AF2-187 GEN
Solar/Wind Helper
1.052
959091AF2-200 GEN
Solar/Wind Harmer
10.43
970571AG2-364 GEN
Solar/Wind Harmer
10.332
274760LEE CO EC;1U
Adder
4.753
274767LEE CO EC;8U
Adder
4.697
241832AE2-181_GEN
Solar/Wind Helper
1.209
270541AE2-072 C
Solar/Wind Helper
1.802
24344005CKG1
50/50
5.708
971549AH1-272 GEN
Solar/Wind Harmer
25.846
944161AF1-084 GEN
Solar/Wind Harmer
2.074
971771AH1-392 GEN
Solar/Wind Harmer
6.841
270526AF1-158 GEN
Solar/Wind Harmer
3.349
960681AF2-359 GEN
Solar/Wind Harmer
2.558
970031AG2-029 GEN
Solar/Wind Harmer
15.55
972037AH1-567 GEN1
Adder
0.104
274827FISK ;RP
Adder
4.378
274800UNIV PARK;3U
Adder
3.28
274801UNIV PARK;4U
Adder
3.28
960591AF2-350 GEN
Solar/Wind Harmer
5.607
274775LINCOLN ;6U
Adder
3.459
274776LINCOLN ;7U
Adder
3.459
274777LINCOLN ;8U
Adder
3.459
972228AH1-698 GEN2
Adder
2.066
972227AH1-698 GEN1
Adder
1.454
274687WILL CNTY;4U
Adder
15.527
274687WILL CNTY;4U
Adder
15.527
274675JOLIET 29;7U
Adder
16.99
274675JOLIET 29;7U
Adder
16.383
276893AG1-478 C
Solar/Wind Harmer
0.304
274728ELWOOD EC;5P
Adder
9.072
274731ELWOOD EC;2P
Adder
9.071
274733ELWOOD EC;3P
Adder
9.071
274735ELWOOD EC;4P
Adder
9.071
958391AF2-133 GEN
Solar/Wind Harmer
4.996
970833AG2-524 GEN
Solar/Wind Harmer
4.773
970833AG2-524 GEN
Solar/Wind Harmer
2.22
274744AC1-111 GEN8
Adder
3.031
274746AC1-111 G10
Adder
3.031
959141AF2-205 GEN
Solar/Wind Harmer
3.272
970073AG2-061 GEN
Solar/Wind Harmer
1.243
971411AH1-196 GEN
Solar/Wind Harmer
7.883
971675AH1-338 GEN
Solar/Wind Harmer
9.442
276861AD2-134 GEN
Solar/Wind Harmer
0.936
276863AD2-134 GEN
Solar/Wind Harmer
0.936
276889AE2-281 GEN
Solar/Wind Harmer
1.005
971171AH1-044 GEN
Solar/Wind Harmer
10.43
274823ROCKFORD ;21
Adder
10.135
274863CRW1-WTG
Solar/Wind Harmer
2.896
274864CRW2-WTG
Solar/Wind Harmer
2.896
274856ECOGROVE ;U1
Solar/Wind Harmer
1.741
276611AD2-172 GEN
Solar/Wind Harmer
1.321
276612AE2-035 GEN
Solar/Wind Harmer
1.321
926823AC1-168 GEN
Solar/Wind Harmer
2.21
972267AH1-718 GEN
Adder
2.106
945411AF1-206 GEN
Solar/Wind Helper
5.235
241886AC2-103 GEN2
Solar/Wind Helper
2.422
945641AF1-229 GEN
Solar/Wind Helper
1.376
270499AE1-146 GEN
Solar/Wind Helper
2.296
971681AH1-341 GEN
Solar/Wind Harmer
7.02
990142J1224
External Queue
49.30740737915039
990527J1329
External Queue
6.745199680328369
991182J1586 G
External Queue
85.20255279541016
991227J1663 G
External Queue
17.943559646606445
991177J1571 G
External Queue
65.40199279785156
LAGNLTFEXP_LAGN->PJM
CLTF
4.718
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.835
TVALTFEXP_TVA->PJM
CLTF
1.976
NYPJM->LTFIMP_NY
CLTF
0.965
LGEELTFEXP_LGEE->PJM
CLTF
1.446
WECLTFEXP_WEC->PJM
CLTF
1.982
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.659
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.508
MECLTFEXP_MEC->PJM
CLTF
7.305
SIGELTFEXP_SIGE->PJM
CLTF
0.142
CPLELTFEXP_CPLE->PJM
CLTF
0.359
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.015

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_05MARYSV 765_A_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_05MARYSV 765_A_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.61 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1935.5
MW Contribution:
9.78
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270246TR4_N_V150
Solar/Wind Harmer
0.804
270247TR4_N_V136
Solar/Wind Harmer
0.804
944231AF1-091 GEN
Solar/Wind Harmer
16.021
942221AE2-234 GEN
Solar/Wind Harmer
3.104
247620Y3-023
Adder
0.361
944541AF1-119 GEN
Solar/Wind Harmer
3.285
960971AF2-388 GEN
Solar/Wind Harmer
8.576
270201AC2-176 GEN
Solar/Wind Harmer
3.503
270031AE2-169
Solar/Wind Harmer
5.526
270599AE1-208 GEN
Solar/Wind Harmer
5.526
964611AG1-324 GEN
Solar/Wind Harmer
0.349
961051AF2-396 GEN
Solar/Wind Harmer
10.462
961051AF2-396 GEN
Solar/Wind Harmer
4.866
247621Y3-024
Adder
0.156
970349AG2-230 GEN
Solar/Wind Harmer
9.594
965681AG1-436 GEN
Solar/Wind Harmer
7.631
965791AG1-447 GEN
Solar/Wind Harmer
3.904
274805UNIV PK N;1U
Adder
2.874
274808UNIV PK N;4U
Adder
2.855
274770LINCOLN ;1U
Adder
3.521
274771LINCOLN ;2U
Adder
3.521
274888KELLY CRK;1U
Solar/Wind Harmer
3.318
276776AD2-060 GEN
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
8.098
970941AG2-585 GEN
Solar/Wind Harmer
3.093
970291AG2-192 GEN
Solar/Wind Harmer
0.729
970291AG2-192 GEN
Solar/Wind Harmer
0.235
276897AD1-100 C
Solar/Wind Harmer
25.808
274674JOLIET 9 ;6U
Adder
8.535
276893AG1-478 C
Solar/Wind Harmer
0.243
270535AF1-215 GEN1
Solar/Wind Harmer
2.5
270536AF1-215 GEN2
Solar/Wind Harmer
2.5
958481AF2-142 GEN
Solar/Wind Harmer
8.153
970883AG2-550 GEN
Solar/Wind Harmer
5.431
970885AG2-551 GEN
Solar/Wind Harmer
1.263
274696ROCKY RD ;4P
Adder
6.156
274695ROCKY RD ;2P
Adder
6.014
274693ROCKY RD ;1P
Adder
5.955
274697ROCKY RD ;3P
Adder
1.634
274683WAUKEGAN ;8U
Adder
11.367
274683WAUKEGAN ;8U
Adder
9.582
958491AF2-143 GEN
Solar/Wind Harmer
8.042
962691AG1-118 GEN
Solar/Wind Harmer
16.067
24725505WLD G2 C
Solar/Wind Harmer
2.125
24699105WLD G1 C
Solar/Wind Harmer
2.1
960751AF2-366 GEN
Solar/Wind Harmer
1.533
276901AD2-066 C O1
Solar/Wind Harmer
1.871
926881AC1-175 GEN
Solar/Wind Harmer
2.972
972235AH1-702 GEN1
Adder
1.314
972236AH1-702 GEN2
Adder
1.143
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.773
274763LEE CO EC;4U
Adder
4.728
246937BC-WTG2
Solar/Wind Helper
11.034
270462AD2-086
Solar/Wind Helper
3.494
247522W1-056 GEN
Solar/Wind Helper
1.143
253378AE2-206_GEN
Solar/Wind Helper
0.662
965431AG1-411 GEN
50/50
44.712
24727105RPMNG2
50/50
3.25
970583AG2-370 GEN
50/50
2.58
965021AG1-366 GEN
Solar/Wind Harmer
4.327
270043AE2-236 GEN
Solar/Wind Harmer
5.578
270063AE2-323 C
Solar/Wind Harmer
2.004
944531AF1-118 GEN
Solar/Wind Harmer
30.953
24695305TIMB G C
Solar/Wind Harmer
2.723
247643Z2-116 C
Solar/Wind Harmer
0.049
962031AG1-047 GEN
Solar/Wind Harmer
2.06
957741AF2-068 GEN
Solar/Wind Harmer
10.222
945111AF1-176 GEN
Solar/Wind Harmer
3.848
270505AE1-170 C O1
Solar/Wind Harmer
9.863
971347AH1-153 GEN
Solar/Wind Harmer
3.198
24441505OLIV SLR
Solar/Wind Harmer
0.084
946031AF1-268 GEN
Solar/Wind Harmer
5.053
270004AE1-209 GEN
Solar/Wind Harmer
3.321
970825AG2-519 GEN
Solar/Wind Harmer
3.37
972231SS25-0005
Solar/Wind Harmer
5.51
972181SS23-001
Solar/Wind Harmer
3.444
274752CRETE EC ;2U
Adder
2.838
274753CRETE EC ;3U
Adder
2.838
274724RIVER EC ;11
Adder
10.229
274814UNIV PK N;0U
Adder
2.893
274807UNIV PK N;3U
Adder
2.886
274811UNIV PK N;7U
Adder
2.868
276164X3-005 C
Solar/Wind Harmer
0.402
274772LINCOLN ;3U
Adder
3.521
274803UNIV PARK;6U
Adder
3.296
274826FISK ;BP
Adder
6.181
972038AH1-567 GEN2
Adder
0.206
274887GEN-1.85
Solar/Wind Harmer
2.996
276772AC2-154 GEN
Solar/Wind Harmer
1.569
276843GEN-1.7
Solar/Wind Harmer
0.322
276806AD2-047 C O1
Solar/Wind Harmer
6.016
965461AG1-414 GEN
Solar/Wind Harmer
1.271
970289AG2-191 GEN
Solar/Wind Harmer
0.43
972259AH1-714 GEN
Adder
10.637
970707AG2-453 GEN
Solar/Wind Harmer
15.585
274676JOLIET 29;8U
Adder
16.443
939351AE1-166 GEN
Solar/Wind Harmer
3.295
247642Z2-115 C
Solar/Wind Harmer
0.035
274729ELWOOD EC;1P
Adder
9.108
274730ELWOOD EC;6P
Adder
9.109
274734ELWOOD EC;8P
Adder
9.109
274736ELWOOD EC;9P
Adder
9.109
943121AE2-341 GEN
Solar/Wind Harmer
8.195
943591AF1-030 GEN
Solar/Wind Harmer
5.463
274862TOP CROP ;2U
Solar/Wind Harmer
2.748
274682WAUKEGAN ;7U
Adder
9.708
964401AG1-302 GEN
Solar/Wind Harmer
4.858
24379505HDWTR1G C
Solar/Wind Harmer
4.211
270240V3-007_GEN2
Solar/Wind Harmer
3.294
276868AE1-113 GEN
Solar/Wind Harmer
5.385
274879MINONK ;1U
Solar/Wind Harmer
3.59
276799AD1-013 GEN
Solar/Wind Harmer
1.166
946671AF1-331 GEN
Solar/Wind Harmer
0.221
274760LEE CO EC;1U
Adder
4.773
274767LEE CO EC;8U
Adder
4.717
246938BC-WTG3
Solar/Wind Helper
11.224
942871AE2-306 GEN
Solar/Wind Helper
0.405
270284AF1-227 GEN1
Solar/Wind Helper
1.524
270287AF1-227 GEN3
Solar/Wind Helper
0.559
276820AF1-078_GEN
Solar/Wind Helper
0.309
270541AE2-072 C
Solar/Wind Helper
0.973
24727005RPMNG1
50/50
3.25
960861AF2-377 GEN
50/50
2.2
965421AG1-410 GEN
Solar/Wind Harmer
115.358
965011AG1-365 GEN
Solar/Wind Harmer
18.606
270024AE2-089 GEN
Solar/Wind Harmer
4.038
965651AG1-433 GEN
Solar/Wind Harmer
4.288
958861AF2-177 GEN
Solar/Wind Harmer
8.314
24639705ELKHART HY
Adder
0.115
945371AF1-202 GEN
Solar/Wind Harmer
4.987
270216AD2-079_GEN
Solar/Wind Harmer
0.431
945111AF1-176 GEN
Solar/Wind Harmer
12.142
957891AF2-083 GEN
Solar/Wind Harmer
9.957
270449AD2-020 GEN
Solar/Wind Harmer
1.811
943021AE2-325 GEN
Solar/Wind Harmer
2.354
270005AE1-210 C O1
Solar/Wind Harmer
3.321
24441205WTRV SLR C
Solar/Wind Harmer
0.082
970825AG2-519 GEN
Solar/Wind Harmer
1.255
274751CRETE EC ;1U
Adder
2.838
274754CRETE EC ;4U
Adder
2.838
274723RIVER EC ;12
Adder
10.355
274812UNIV PK N;8U
Adder
2.868
972207SS24-0001
Solar/Wind Harmer
12.518
274773LINCOLN ;4U
Adder
3.521
274774LINCOLN ;5U
Adder
3.521
270594AE1-207 GEN
Solar/Wind Harmer
7.706
270032AE2-172
Solar/Wind Harmer
2.639
970373AG2-245 GEN
Solar/Wind Harmer
11.888
24727205RPMNG3
50/50
3.231
959331AF2-224 GEN
Solar/Wind Harmer
18.606
963791AG1-232 GEN
Solar/Wind Harmer
15.633
965041AG1-368 GEN
Solar/Wind Harmer
11.094
970031AG2-029 GEN
Solar/Wind Harmer
26.426
247521TR3_G114
Solar/Wind Harmer
3.178
270191TR4_S_V150
Solar/Wind Harmer
2.836
965051AG1-369 GEN
Solar/Wind Harmer
4.721
270071AF1-092 GEN
Solar/Wind Harmer
13.726
24729505KEY G4
Adder
5.566
958711AF2-162 GEN
Solar/Wind Harmer
0.794
945581AF1-223 GEN
Solar/Wind Harmer
3.242
961761AG1-017 GEN
Solar/Wind Harmer
0.292
964611AG1-324 GEN
Solar/Wind Harmer
2.597
971771AH1-392 GEN
Solar/Wind Harmer
5.97
270526AF1-158 GEN
Solar/Wind Harmer
2.886
944161AF1-084 GEN
Solar/Wind Harmer
1.403
960681AF2-359 GEN
Solar/Wind Harmer
2.307
247536S-71 GEN
Solar/Wind Harmer
2.452
274775LINCOLN ;6U
Adder
3.521
274776LINCOLN ;7U
Adder
3.521
274777LINCOLN ;8U
Adder
3.521
972037AH1-567 GEN1
Adder
0.103
274827FISK ;RP
Adder
4.38
274800UNIV PARK;3U
Adder
3.284
274801UNIV PARK;4U
Adder
3.284
960591AF2-350 GEN
Solar/Wind Harmer
5.623
970289AG2-191 GEN
Solar/Wind Harmer
1.065
972228AH1-698 GEN2
Adder
2.075
972227AH1-698 GEN1
Adder
1.461
274687WILL CNTY;4U
Adder
15.572
274687WILL CNTY;4U
Adder
15.572
274675JOLIET 29;7U
Adder
17.053
274675JOLIET 29;7U
Adder
16.444
276893AG1-478 C
Solar/Wind Harmer
0.305
274728ELWOOD EC;5P
Adder
9.109
274802UNIV PARK;5U
Adder
3.296
274676JOLIET 29;8U
Adder
17.052
941551AE2-152 GEN
Solar/Wind Harmer
2.52
274674JOLIET 9 ;6U
Adder
8.535
274732ELWOOD EC;7P
Adder
9.109
270055AF2-134 C O1
Solar/Wind Harmer
1.666
274871GR RIDGE ;2U
Solar/Wind Harmer
4.231
274847GR RIDGE ;BU
Solar/Wind Harmer
2.782
274745AC1-111 GEN9
Adder
3.054
276694AA1-018 GEN2
Solar/Wind Harmer
3.43
276691AA1-018 GEN1
Solar/Wind Harmer
0.41
274861TOP CROP ;1U
Solar/Wind Harmer
3.292
274682WAUKEGAN ;7U
Adder
9.708
274828WAUKEGAN ;BP
Adder
5.958
276903AD2-071 C
Solar/Wind Harmer
5.388
276805AD2-038 GEN
Solar/Wind Harmer
2.749
958381AF2-132 GEN
Solar/Wind Harmer
4.858
962781AG1-127 GEN
Solar/Wind Harmer
5.08
964861AG1-349 GEN
Solar/Wind Harmer
4.197
971917AH1-482 GEN
Solar/Wind Harmer
4.843
939401AE1-172 GEN
Solar/Wind Harmer
7.431
274872LEEDK;1U
Solar/Wind Harmer
4.374
942081AE2-220 GEN
Solar/Wind Harmer
3.406
270209AC1-174_GEN
Solar/Wind Harmer
2.167
270437AC2-090 C
Solar/Wind Harmer
2.972
270239V3-007_GEN1
Solar/Wind Harmer
0.916
276882AE2-255 GEN
Solar/Wind Harmer
1.795
971997AH1-543 GEN
Solar/Wind Harmer
8.338
274822ROCKFORD ;11
Adder
10.257
274761LEE CO EC;2U
Adder
4.773
274766LEE CO EC;7U
Adder
4.717
246936BC-WTG1
Solar/Wind Helper
11.034
270317AD1-130_GEN
Solar/Wind Helper
3.865
270485AE1-090_GEN
Solar/Wind Helper
0.304
270391AF1-285 GEN3
Solar/Wind Helper
0.541
270578AF1-285 GEN2
Solar/Wind Helper
0.541
960841AF2-375 GEN
Solar/Wind Helper
1.161
270286AF1-227 GEN2
Solar/Wind Helper
0.559
274731ELWOOD EC;2P
Adder
9.108
274733ELWOOD EC;3P
Adder
9.108
274735ELWOOD EC;4P
Adder
9.108
970833AG2-524 GEN
Solar/Wind Harmer
4.808
970833AG2-524 GEN
Solar/Wind Harmer
2.236
274744AC1-111 GEN8
Adder
3.054
274746AC1-111 G10
Adder
3.054
270543AE2-219 C
Solar/Wind Harmer
5.431
970073AG2-061 GEN
Solar/Wind Harmer
1.247
971549AH1-272 GEN
Solar/Wind Harmer
9.777
971411AH1-196 GEN
Solar/Wind Harmer
7.924
274823ROCKFORD ;21
Adder
10.183
972267AH1-718 GEN
Adder
2.114
957201AF2-014 GEN
Solar/Wind Helper
8.717
270223U2-072_GEN1
Solar/Wind Helper
0.799
270224U2-072_GEN2
Solar/Wind Helper
0.799
270227U2-072_GEN3
Solar/Wind Helper
0.799
270228U2-072_GEN4
Solar/Wind Helper
0.799
270231U2-072_GEN5
Solar/Wind Helper
0.799
966831AG1-554 GEN
Solar/Wind Helper
0.85
270499AE1-146 GEN
Solar/Wind Helper
1.939
945641AF1-229 GEN
Solar/Wind Helper
0.909
971675AH1-338 GEN
Solar/Wind Harmer
1.226
990497J1323
External Queue
1.5409908294677734
990792J1392
External Queue
5.301008224487305
LAGNLTFEXP_LAGN->PJM
CLTF
4.175
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.241
TVALTFEXP_TVA->PJM
CLTF
1.645
NYPJM->LTFIMP_NY
CLTF
0.909
LGEELTFEXP_LGEE->PJM
CLTF
1.252
WECLTFEXP_WEC->PJM
CLTF
1.989
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.209
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.297
MECLTFEXP_MEC->PJM
CLTF
7.255
SIGELTFEXP_SIGE->PJM
CLTF
0.143
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.738

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.36 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1930.81
MW Contribution:
9.76
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.2 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2600.32
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
44.703
24727105RPMNG2
50/50
3.249
970583AG2-370 GEN
50/50
2.578
965021AG1-366 GEN
Solar/Wind Harmer
4.325
270043AE2-236 GEN
Solar/Wind Harmer
5.574
270063AE2-323 C
Solar/Wind Harmer
2.002
944531AF1-118 GEN
Solar/Wind Harmer
30.925
24695305TIMB G C
Solar/Wind Harmer
2.72
247643Z2-116 C
Solar/Wind Harmer
0.049
962031AG1-047 GEN
Solar/Wind Harmer
2.058
957741AF2-068 GEN
Solar/Wind Harmer
10.212
945111AF1-176 GEN
Solar/Wind Harmer
3.843
270505AE1-170 C O1
Solar/Wind Harmer
9.849
971347AH1-153 GEN
Solar/Wind Harmer
3.193
24441505OLIV SLR
Solar/Wind Harmer
0.084
946031AF1-268 GEN
Solar/Wind Harmer
5.047
270004AE1-209 GEN
Solar/Wind Harmer
3.317
970825AG2-519 GEN
Solar/Wind Harmer
3.366
972231SS25-0005
Solar/Wind Harmer
5.502
972181SS23-001
Solar/Wind Harmer
3.439
274752CRETE EC ;2U
Adder
2.834
274753CRETE EC ;3U
Adder
2.834
274724RIVER EC ;11
Adder
10.213
274814UNIV PK N;0U
Adder
2.888
274807UNIV PK N;3U
Adder
2.882
274811UNIV PK N;7U
Adder
2.863
276164X3-005 C
Solar/Wind Harmer
0.401
274772LINCOLN ;3U
Adder
3.515
274803UNIV PARK;6U
Adder
3.291
274826FISK ;BP
Adder
6.171
972038AH1-567 GEN2
Adder
0.205
274887GEN-1.85
Solar/Wind Harmer
2.991
276772AC2-154 GEN
Solar/Wind Harmer
1.567
276843GEN-1.7
Solar/Wind Harmer
0.322
276806AD2-047 C O1
Solar/Wind Harmer
6.006
965461AG1-414 GEN
Solar/Wind Harmer
1.269
970289AG2-191 GEN
Solar/Wind Harmer
0.43
972259AH1-714 GEN
Adder
10.62
970707AG2-453 GEN
Solar/Wind Harmer
15.561
274676JOLIET 29;8U
Adder
16.417
939351AE1-166 GEN
Solar/Wind Harmer
3.29
247642Z2-115 C
Solar/Wind Harmer
0.035
274729ELWOOD EC;1P
Adder
9.094
274730ELWOOD EC;6P
Adder
9.094
274734ELWOOD EC;8P
Adder
9.094
274736ELWOOD EC;9P
Adder
9.094
943121AE2-341 GEN
Solar/Wind Harmer
8.182
943591AF1-030 GEN
Solar/Wind Harmer
5.455
274862TOP CROP ;2U
Solar/Wind Harmer
2.744
274682WAUKEGAN ;7U
Adder
9.692
964401AG1-302 GEN
Solar/Wind Harmer
4.85
24379505HDWTR1G C
Solar/Wind Harmer
4.205
270246TR4_N_V150
Solar/Wind Harmer
0.803
270247TR4_N_V136
Solar/Wind Harmer
0.803
944231AF1-091 GEN
Solar/Wind Harmer
16.007
942221AE2-234 GEN
Solar/Wind Harmer
3.102
247620Y3-023
Adder
0.361
944541AF1-119 GEN
Solar/Wind Harmer
3.282
960971AF2-388 GEN
Solar/Wind Harmer
8.568
270201AC2-176 GEN
Solar/Wind Harmer
3.499
270031AE2-169
Solar/Wind Harmer
5.52
270599AE1-208 GEN
Solar/Wind Harmer
5.52
964611AG1-324 GEN
Solar/Wind Harmer
0.348
961051AF2-396 GEN
Solar/Wind Harmer
10.449
961051AF2-396 GEN
Solar/Wind Harmer
4.86
247621Y3-024
Adder
0.156
970349AG2-230 GEN
Solar/Wind Harmer
9.58
965681AG1-436 GEN
Solar/Wind Harmer
7.619
965791AG1-447 GEN
Solar/Wind Harmer
3.898
274805UNIV PK N;1U
Adder
2.869
274808UNIV PK N;4U
Adder
2.851
274770LINCOLN ;1U
Adder
3.515
274771LINCOLN ;2U
Adder
3.515
274888KELLY CRK;1U
Solar/Wind Harmer
3.313
276776AD2-060 GEN
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
8.085
970941AG2-585 GEN
Solar/Wind Harmer
3.088
970291AG2-192 GEN
Solar/Wind Harmer
0.728
970291AG2-192 GEN
Solar/Wind Harmer
0.234
276897AD1-100 C
Solar/Wind Harmer
25.767
24727005RPMNG1
50/50
3.249
960861AF2-377 GEN
50/50
2.199
965421AG1-410 GEN
Solar/Wind Harmer
115.334
965011AG1-365 GEN
Solar/Wind Harmer
18.598
270024AE2-089 GEN
Solar/Wind Harmer
4.034
965651AG1-433 GEN
Solar/Wind Harmer
4.284
958861AF2-177 GEN
Solar/Wind Harmer
8.306
24639705ELKHART HY
Adder
0.115
945371AF1-202 GEN
Solar/Wind Harmer
4.982
270216AD2-079_GEN
Solar/Wind Harmer
0.43
945111AF1-176 GEN
Solar/Wind Harmer
12.127
957891AF2-083 GEN
Solar/Wind Harmer
9.944
270449AD2-020 GEN
Solar/Wind Harmer
1.809
943021AE2-325 GEN
Solar/Wind Harmer
2.351
270005AE1-210 C O1
Solar/Wind Harmer
3.317
24441205WTRV SLR C
Solar/Wind Harmer
0.082
970825AG2-519 GEN
Solar/Wind Harmer
1.254
274751CRETE EC ;1U
Adder
2.834
274754CRETE EC ;4U
Adder
2.834
274723RIVER EC ;12
Adder
10.339
274812UNIV PK N;8U
Adder
2.863
972207SS24-0001
Solar/Wind Harmer
12.498
274773LINCOLN ;4U
Adder
3.515
274774LINCOLN ;5U
Adder
3.515
270594AE1-207 GEN
Solar/Wind Harmer
7.695
270032AE2-172
Solar/Wind Harmer
2.635
970373AG2-245 GEN
Solar/Wind Harmer
11.868
274802UNIV PARK;5U
Adder
3.291
274676JOLIET 29;8U
Adder
17.025
941551AE2-152 GEN
Solar/Wind Harmer
2.516
274674JOLIET 9 ;6U
Adder
8.521
274732ELWOOD EC;7P
Adder
9.094
270055AF2-134 C O1
Solar/Wind Harmer
1.663
274871GR RIDGE ;2U
Solar/Wind Harmer
4.224
274847GR RIDGE ;BU
Solar/Wind Harmer
2.778
274745AC1-111 GEN9
Adder
3.049
276694AA1-018 GEN2
Solar/Wind Harmer
3.424
276691AA1-018 GEN1
Solar/Wind Harmer
0.409
274861TOP CROP ;1U
Solar/Wind Harmer
3.286
274682WAUKEGAN ;7U
Adder
9.692
274828WAUKEGAN ;BP
Adder
5.949
276903AD2-071 C
Solar/Wind Harmer
5.38
276805AD2-038 GEN
Solar/Wind Harmer
2.745
958381AF2-132 GEN
Solar/Wind Harmer
4.85
962781AG1-127 GEN
Solar/Wind Harmer
5.072
964861AG1-349 GEN
Solar/Wind Harmer
4.19
971917AH1-482 GEN
Solar/Wind Harmer
4.834
939401AE1-172 GEN
Solar/Wind Harmer
7.419
274872LEEDK;1U
Solar/Wind Harmer
4.367
942081AE2-220 GEN
Solar/Wind Harmer
3.401
270209AC1-174_GEN
Solar/Wind Harmer
2.164
270437AC2-090 C
Solar/Wind Harmer
2.968
270239V3-007_GEN1
Solar/Wind Harmer
0.915
276882AE2-255 GEN
Solar/Wind Harmer
1.792
971997AH1-543 GEN
Solar/Wind Harmer
8.324
274822ROCKFORD ;11
Adder
10.241
274761LEE CO EC;2U
Adder
4.765
274766LEE CO EC;7U
Adder
4.709
246936BC-WTG1
Solar/Wind Helper
11.036
270317AD1-130_GEN
Solar/Wind Helper
3.868
270485AE1-090_GEN
Solar/Wind Helper
0.304
270391AF1-285 GEN3
Solar/Wind Helper
0.541
270578AF1-285 GEN2
Solar/Wind Helper
0.541
960841AF2-375 GEN
Solar/Wind Helper
1.162
270286AF1-227 GEN2
Solar/Wind Helper
0.561
274674JOLIET 9 ;6U
Adder
8.521
276893AG1-478 C
Solar/Wind Harmer
0.243
270535AF1-215 GEN1
Solar/Wind Harmer
2.495
270536AF1-215 GEN2
Solar/Wind Harmer
2.495
958481AF2-142 GEN
Solar/Wind Harmer
8.14
970883AG2-550 GEN
Solar/Wind Harmer
5.424
970885AG2-551 GEN
Solar/Wind Harmer
1.261
274696ROCKY RD ;4P
Adder
6.146
274695ROCKY RD ;2P
Adder
6.005
274693ROCKY RD ;1P
Adder
5.946
274697ROCKY RD ;3P
Adder
1.631
274683WAUKEGAN ;8U
Adder
11.349
274683WAUKEGAN ;8U
Adder
9.567
958491AF2-143 GEN
Solar/Wind Harmer
8.029
962691AG1-118 GEN
Solar/Wind Harmer
16.041
24725505WLD G2 C
Solar/Wind Harmer
2.122
24699105WLD G1 C
Solar/Wind Harmer
2.097
960751AF2-366 GEN
Solar/Wind Harmer
1.53
276901AD2-066 C O1
Solar/Wind Harmer
1.868
926881AC1-175 GEN
Solar/Wind Harmer
2.968
972235AH1-702 GEN1
Adder
1.312
972236AH1-702 GEN2
Adder
1.141
274764LEE CO EC;5U
Adder
4.777
274765LEE CO EC;6U
Adder
4.777
274762LEE CO EC;3U
Adder
4.765
274763LEE CO EC;4U
Adder
4.721
246937BC-WTG2
Solar/Wind Helper
11.036
270462AD2-086
Solar/Wind Helper
3.497
247522W1-056 GEN
Solar/Wind Helper
1.143
253378AE2-206_GEN
Solar/Wind Helper
0.662
270240V3-007_GEN2
Solar/Wind Harmer
3.29
276868AE1-113 GEN
Solar/Wind Harmer
5.377
274879MINONK ;1U
Solar/Wind Harmer
3.585
276799AD1-013 GEN
Solar/Wind Harmer
1.164
946671AF1-331 GEN
Solar/Wind Harmer
0.221
274760LEE CO EC;1U
Adder
4.765
274767LEE CO EC;8U
Adder
4.709
246938BC-WTG3
Solar/Wind Helper
11.226
942871AE2-306 GEN
Solar/Wind Helper
0.406
270284AF1-227 GEN1
Solar/Wind Helper
1.528
270287AF1-227 GEN3
Solar/Wind Helper
0.561
276820AF1-078_GEN
Solar/Wind Helper
0.309
270541AE2-072 C
Solar/Wind Helper
0.974
24727205RPMNG3
50/50
3.23
959331AF2-224 GEN
Solar/Wind Harmer
18.598
963791AG1-232 GEN
Solar/Wind Harmer
15.623
965041AG1-368 GEN
Solar/Wind Harmer
11.086
970031AG2-029 GEN
Solar/Wind Harmer
26.405
247521TR3_G114
Solar/Wind Harmer
3.175
270191TR4_S_V150
Solar/Wind Harmer
2.833
965051AG1-369 GEN
Solar/Wind Harmer
4.718
270071AF1-092 GEN
Solar/Wind Harmer
13.713
24729505KEY G4
Adder
5.561
958711AF2-162 GEN
Solar/Wind Harmer
0.793
945581AF1-223 GEN
Solar/Wind Harmer
3.239
961761AG1-017 GEN
Solar/Wind Harmer
0.291
964611AG1-324 GEN
Solar/Wind Harmer
2.595
971771AH1-392 GEN
Solar/Wind Harmer
5.962
270526AF1-158 GEN
Solar/Wind Harmer
2.882
944161AF1-084 GEN
Solar/Wind Harmer
1.401
960681AF2-359 GEN
Solar/Wind Harmer
2.303
247536S-71 GEN
Solar/Wind Harmer
2.449
274775LINCOLN ;6U
Adder
3.515
274776LINCOLN ;7U
Adder
3.515
274777LINCOLN ;8U
Adder
3.515
972037AH1-567 GEN1
Adder
0.103
274827FISK ;RP
Adder
4.374
274800UNIV PARK;3U
Adder
3.279
274801UNIV PARK;4U
Adder
3.279
960591AF2-350 GEN
Solar/Wind Harmer
5.615
970289AG2-191 GEN
Solar/Wind Harmer
1.064
972228AH1-698 GEN2
Adder
2.072
972227AH1-698 GEN1
Adder
1.459
274687WILL CNTY;4U
Adder
15.547
274687WILL CNTY;4U
Adder
15.547
274675JOLIET 29;7U
Adder
17.026
274675JOLIET 29;7U
Adder
16.418
276893AG1-478 C
Solar/Wind Harmer
0.304
274728ELWOOD EC;5P
Adder
9.094
274731ELWOOD EC;2P
Adder
9.094
274733ELWOOD EC;3P
Adder
9.094
274735ELWOOD EC;4P
Adder
9.094
970833AG2-524 GEN
Solar/Wind Harmer
4.8
970833AG2-524 GEN
Solar/Wind Harmer
2.233
274744AC1-111 GEN8
Adder
3.049
274746AC1-111 G10
Adder
3.049
270543AE2-219 C
Solar/Wind Harmer
5.424
970073AG2-061 GEN
Solar/Wind Harmer
1.245
971549AH1-272 GEN
Solar/Wind Harmer
9.762
971411AH1-196 GEN
Solar/Wind Harmer
7.911
274823ROCKFORD ;21
Adder
10.167
972267AH1-718 GEN
Adder
2.11
957201AF2-014 GEN
Solar/Wind Helper
8.718
270223U2-072_GEN1
Solar/Wind Helper
0.8
270224U2-072_GEN2
Solar/Wind Helper
0.8
270227U2-072_GEN3
Solar/Wind Helper
0.8
270228U2-072_GEN4
Solar/Wind Helper
0.8
270231U2-072_GEN5
Solar/Wind Helper
0.8
966831AG1-554 GEN
Solar/Wind Helper
0.85
270499AE1-146 GEN
Solar/Wind Helper
1.94
945641AF1-229 GEN
Solar/Wind Helper
0.909
971675AH1-338 GEN
Solar/Wind Harmer
1.224
990497J1323
External Queue
1.5405974388122559
990792J1392
External Queue
5.299654960632324
LAGNLTFEXP_LAGN->PJM
CLTF
4.166
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.237
TVALTFEXP_TVA->PJM
CLTF
1.641
NYPJM->LTFIMP_NY
CLTF
0.907
LGEELTFEXP_LGEE->PJM
CLTF
1.248
WECLTFEXP_WEC->PJM
CLTF
1.986
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.192
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.107
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.281
MECLTFEXP_MEC->PJM
CLTF
7.242
SIGELTFEXP_SIGE->PJM
CLTF
0.143
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.662
CONTINGENCY 'ATSI_P2-3_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238607 CKT 1   /*02BEAVER     345.0 - 02CARLIL     345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 1           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 2           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AEP_P4_#2979_05DUMONT 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290597 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290597 CKT 1    /*05GRNTWN     765.0 - 05DUMONT_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-030_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'AEP_P4_#ADKINS AG1125_SRT-A_SENS'
 OPEN BRANCH FROM BUS 962760 TO BUS 248125 CKT 1   /*AG1-125 TP   765.0 - 05ADKINS     765.0
END
CONTINGENCY 'AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS'
 OPEN BRANCH FROM BUS 962760 TO BUS 248125 CKT 1   /*AG1-125 TP   765.0 - 05ADKINS     765.0
END
CONTINGENCY 'AEP_P4_#707_05MARYSV 765_B1_SRT-A_SENS'
 OPEN BRANCH FROM BUS 242928 TO BUS 248115 CKT 1    /*05MARYSV     765.0 - MARYSTAT     765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 243207 TO BUS 248105 CKT 1   /*05GRNTWN     765.0 - 05GREENTW_RM 765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248102 CKT 1   /*05TEDDY_RG   765.0 - 05TEDDY      765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248105 CKT 1   /*05TEDDY_RG   765.0 - 05GREENTW_RM 765.0
END
CONTINGENCY 'AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 243207 TO BUS 248105 CKT 1   /*05GRNTWN     765.0 - 05GREENTW_RM 765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248102 CKT 1   /*05TEDDY_RG   765.0 - 05TEDDY      765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248105 CKT 1   /*05TEDDY_RG   765.0 - 05GREENTW_RM 765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#TEDDY MARY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 242928 TO BUS 248102 CKT 1   /*05MARYSV     765.0 - 05TEDDY      765.0
END
CONTINGENCY 'AEP_P4_05MARYSV 765_C2_SRT-A_SENS'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2   /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 248102 CKT 1   /*05MARYSV     765.0 - 05TEDDY      765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#2995_05E LIMA 345_M_SRT-A'
 OPEN BRANCH FROM BUS 242935 TO BUS 245128 CKT 2   /*05E LIMA     345.0 - 05E.LIMA 2EQ   1.0
 OPEN BRANCH FROM BUS 242935 TO BUS 246929 CKT 1   /*05E LIMA     345.0 - 05MADDOX     345.0
 OPEN BRANCH FROM BUS 242989 TO BUS 245128 CKT 2   /*05E LIMA     138.0 - 05E.LIMA 2EQ   1.0
 OPEN BRANCH FROM BUS 245128 TO BUS 245148 CKT 2   /*05E.LIMA 2EQ   1.0 - 05E.LIMA T2   13.8
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P7-1_#11010___SRT-A'
 OPEN BRANCH FROM BUS 242933 TO BUS 243211 CKT 1   /*05RPMONE     345.0 - 05ALLEN      345.0
 OPEN BRANCH FROM BUS 243211 TO BUS 243232 CKT 1   /*05ALLEN      345.0 - 05SORENS     345.0
END
CONTINGENCY 'AEP_P1-2_#9287_1679_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290597 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290597 CKT 1    /*05GRNTWN     765.0 - 05DUMONT_RG  765.0
END
CONTINGENCY 'AEP_P7-1_#11087___SRT-A-1'
 OPEN BRANCH FROM BUS 243218 TO BUS 288691 CKT 1   /*05DESOTO     345.0 - 05WHIPPLEDTC 345.0
 OPEN BRANCH FROM BUS 243218 TO BUS 958860 CKT 2   /*05DESOTO     345.0 - AF2-177 TP   345.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-022T_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 264594 CKT 1   /*02LEMOYN     345.0 - 19LULU       345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
END
CONTINGENCY 'AEP_P4_05MARYSV 765_A_SRT-A_SENS'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
238569 to 239725 ckt 2
290614 to 242515 ckt 1
243206 to 290606 ckt Z1
290623 to 242925 ckt Z1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
256583 to 238530 ckt 1
965420 to 246929 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.87 %3729.0B4917.49
14.79
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.24 %3729.0B4632.89
14.3
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-008B_SRT-SL
BreakerAC139.03 %1683.0B2339.9
14.99
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-013_SRT-SL
BreakerAC118.03 %1683.0B1986.46
15.4
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-014_SRT-A
BreakerAC118.03 %1683.0B1986.44
15.4
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-009_SRT-A
BreakerAC117.85 %1683.0B1983.38
15.38
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC113.4 %1683.0B1908.5
11.98
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-005_SRT-A
BreakerAC130.04 %1892.0B2460.31
13.41
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-006_SRT-SL
BreakerAC127.41 %1892.0B2410.66
13.49
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010A_SRT-SL
BreakerAC125.51 %1892.0B2374.58
13.49
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC116.27 %1892.0B2199.92
10.49
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC115.8 %1892.0B2190.94
10.51
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-F1_SRT-A
BreakerAC134.38 %1646.0B2211.96
13.0
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-12_SRT-A
BreakerAC134.38 %1646.0B2211.96
13.0
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC131.38 %1646.0B2162.49
12.83
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B2_SRT-SL
BreakerAC129.53 %1646.0B2132.01
12.85
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B1_SRT-SL
BreakerAC129.53 %1646.0B2132.01
12.85
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC115.5 %1646.0B1901.19
10.01
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC108.41 %1646.0B1784.35
9.84
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-005_SRT-A
BreakerAC128.38 %1878.0B2410.9
13.43
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-006_SRT-SL
BreakerAC125.55 %1878.0B2357.8
13.57
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010A_SRT-SL
BreakerAC123.72 %1878.0B2323.45
13.52
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC115.9 %1878.0B2176.69
10.51
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC115.49 %1878.0B2168.95
10.53
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-007_SRT-SL
BreakerAC122.37 %1878.0B2298.14
14.84
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-004_SRT-A
BreakerAC103.09 %1878.0B1936.08
15.24
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-005_SRT-SL
BreakerAC103.09 %1878.0B1936.02
15.24
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-006_SRT-SL
BreakerAC103.09 %1878.0B1936.02
15.24
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC110.65 %1737.0B1922.03
10.21
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC107.15 %1302.0B1395.07
8.29
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC116.82 %1409.0B1646.06
8.1
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC110.97 %1409.0B1563.59
8.08
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC110.88 %1409.0B1562.23
8.08
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC105.36 %1409.0B1484.58
8.05
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC105.35 %1409.0B1484.33
8.05
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC105.58 %3039.0B3208.68
10.2
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC113.16 %2826.0B3197.84
10.2
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC133.22 %3792.0B5051.83
14.79
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.57 %3792.0B4761.71
14.3
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC111.91 %2246.0B2513.45
9.79
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC127.9 %4142.0B5297.56
16.35
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC108.0 %4142.0B4473.55
19.17
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC106.18 %4142.0B4397.83
19.7
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC105.96 %4142.0B4388.88
19.65
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.31 %4571.0B5773.71
16.37
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
SingleAC111.01 %4571.0B5074.41
13.51
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Base Case
SingleAC110.62 %4047.0A4476.89
14.07
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC108.08 %4571.0B4940.32
19.63
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC107.85 %4571.0B4929.67
19.56
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P2-2_#5063_05SBERWI 345_1_SRT-A
BusAC104.09 %4571.0B4757.98
18.91
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.34 %4571.0B5774.92
16.37
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
SingleAC111.24 %4571.0B5084.88
13.51
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Base Case
SingleAC110.76 %4047.0A4482.29
14.07
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC108.18 %4571.0B4944.72
19.63
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC107.94 %4571.0B4934.14
19.56
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P2-2_#5063_05SBERWI 345_1_SRT-A
BusAC104.2 %4571.0B4763.16
18.91
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Base Case
SingleAC120.76 %4047.0A4887.22
24.05
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC122.25 %1868.0B2283.58
9.9
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7443_05DUMONT 765_A_SRT-A
BreakerAC111.31 %3097.0B3447.28
22.04
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7442_05SORENS 765_K2_SRT-A
BreakerAC111.22 %3097.0B3444.48
21.89
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7444_05DUMONT 765_A2_SRT-A
BreakerAC111.06 %3097.0B3439.41
22.07
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC103.01 %3097.0B3190.2
17.04
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC110.78 %5523.0B6118.43
34.29
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC110.38 %5523.0B6096.34
36.89
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC109.5 %5523.0B6047.92
34.38
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#2995_05E LIMA 345_M_SRT-A
BreakerAC104.99 %5523.0B5798.45
33.08
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.53 %5523.0B5607.44
26.77
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P7-1_#11010___SRT-A
TowerAC101.49 %5523.0B5605.23
33.14
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P7-1_#17567_SRT-SL
TowerAC100.76 %5523.0B5565.17
32.99
GD2AEP
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC100.98 %6066.0B6125.38
34.29
GD2AEP
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC100.82 %6066.0B6115.5
36.89
GD2AEP
05TWIN B-05MERIDN 345.0 kV Ckt 1 line
AEP_P4_#7442_05SORENS 765_K2_SRT-A
BreakerAC100.24 %897.0B899.13
11.69
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC141.94 %1540.0B2185.8
6.25
GD2ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-022T_SRT-A
TowerAC134.03 %1793.0B2403.22
26.31
GD2ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-034T_SRT-A
BreakerAC108.4 %1793.0B1943.59
20.23
GD2ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-033T_SRT-A
BreakerAC108.18 %1793.0B1939.73
20.2
GD2ATSI/ITCT
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-025T_SRT-A
TowerAC122.24 %1660.0B2029.25
22.65
GD2ATSI/ITCT
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-023T_SRT-SL
BreakerAC116.94 %1660.0B1941.12
20.77
GD2ATSI/ITCT
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-022T_SRT-A
BreakerAC116.81 %1660.0B1939.0
20.77
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-009_SRT-SL
BreakerAC140.39 %1499.0B2104.51
12.68
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-F1_SRT-A
BreakerAC126.45 %1798.0B2273.56
12.97
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-12_SRT-A
BreakerAC126.45 %1798.0B2273.56
12.97
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC122.38 %1798.0B2200.39
12.79
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B2_SRT-SL
BreakerAC119.29 %1798.0B2144.77
12.82
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC103.63 %1798.0B1863.35
9.98
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC128.82 %1868.0B2406.35
9.9
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-032T_SRT-A
TowerAC102.98 %1868.0B1923.66
9.61
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-022T_SRT-A
TowerAC101.28 %1868.0B1891.93
9.45

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4917.49
MW Contribution:
14.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.069
270120AB2-067 GEN2
50/50
7.069
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.31
938701AE1-092 GEN
Solar/Wind Harmer
12.867
971655AH1-328 GEN
Solar/Wind Harmer
2.843
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
25326509SID D
Adder
1.446
971073AG2-665 GEN
Solar/Wind Harmer
5.597
970879AG2-548 GEN
Solar/Wind Harmer
1.272
25326109MON D
Adder
1.437
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
246937BC-WTG2
Solar/Wind Harmer
0.302
270246TR4_N_V150
Solar/Wind Harmer
0.048
270247TR4_N_V136
Solar/Wind Harmer
0.048
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.351
944541AF1-119 GEN
Solar/Wind Harmer
0.492
960971AF2-388 GEN
Solar/Wind Harmer
4.326
942221AE2-234 GEN
Solar/Wind Harmer
2.958
25194408D.CRK1
Adder
7.968
25194508D.CRK3
Adder
1.49
970621AG2-405 GEN
Solar/Wind Harmer
1.345
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970885AG2-551 GEN
Solar/Wind Harmer
2.446
247621Y3-024
Adder
0.253
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270031AE2-169
Solar/Wind Harmer
4.021
270599AE1-208 GEN
Solar/Wind Harmer
6.701
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728805RICHG1
Adder
3.944
24728905RICHG2
Adder
3.944
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.052
965791AG1-447 GEN
Solar/Wind Harmer
6.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274805UNIV PK N;1U
Adder
5.126
274808UNIV PK N;4U
Adder
5.092
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
276776AD2-060 GEN
Solar/Wind Harmer
0.758
958011AF2-095 GEN
Solar/Wind Harmer
10.234
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
274674JOLIET 9 ;6U
Adder
15.628
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274696ROCKY RD ;4P
Adder
11.481
274695ROCKY RD ;2P
Adder
11.216
274693ROCKY RD ;1P
Adder
11.106
274697ROCKY RD ;3P
Adder
3.047
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276901AD2-066 C O1
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
962691AG1-118 GEN
Solar/Wind Harmer
21.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
942111AE2-223 GEN
Solar/Wind Harmer
2.266
316097T157 G90
Solar/Wind Helper
1.51
235054AD2-180 GEN
Solar/Wind Helper
2.04
23585401KL_K28_T16
Solar/Wind Helper
1.489
235531U2-073 GEN
Solar/Wind Helper
3.327
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.344
235062AE1-101 C1
Solar/Wind Helper
1.672
316411AF1-147_GEN1
Solar/Wind Helper
0.895
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.17
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
972239AH1-704 GEN
Adder
2.678
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270291AC1-194 GEN
Solar/Wind Harmer
0
970179AG2-119 GEN
Solar/Wind Harmer
6.854
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
253406AD2-031_GEN
Solar/Wind Harmer
0.559
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270377AD1-106 GEN
Solar/Wind Harmer
2.842
247521TR3_G114
Solar/Wind Harmer
0.27
965051AG1-369 GEN
Solar/Wind Harmer
3.723
959331AF2-224 GEN
Solar/Wind Harmer
5.217
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.438
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
963791AG1-232 GEN
Solar/Wind Harmer
9.987
270071AF1-092 GEN
Solar/Wind Harmer
14.177
971985AH1-537 GEN
Solar/Wind Harmer
2.196
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
25196508WSDLE4
Adder
8.944
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
270543AE2-219 C
Solar/Wind Harmer
5.137
247536S-71 GEN
Solar/Wind Harmer
0.293
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
970289AG2-191 GEN
Solar/Wind Harmer
1.382
971771AH1-392 GEN
Solar/Wind Harmer
7.271
270526AF1-158 GEN
Solar/Wind Harmer
0
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
971549AH1-272 GEN
Solar/Wind Harmer
14.794
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.634
274776LINCOLN ;7U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972228AH1-698 GEN2
Adder
3.772
972227AH1-698 GEN1
Adder
2.656
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
274728ELWOOD EC;5P
Adder
16.687
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274735ELWOOD EC;4P
Adder
16.687
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
274744AC1-111 GEN8
Adder
5.652
274746AC1-111 G10
Adder
5.652
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
970169AG2-114 GEN
Solar/Wind Harmer
7.011
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
971411AH1-196 GEN
Solar/Wind Harmer
10.47
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.32
23750701CROSSCHOOL
Solar/Wind Helper
1.509
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.512
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.062
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
24318805MLG1
50/50
10.065
23559001PLEAS1
50/50
6.097
270051AF1-062 GEN
50/50
11.777
270475AD2-096_GEN
50/50
7.114
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
961921AG1-034 GEN
Solar/Wind Harmer
7.586
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
970191AG2-125 GEN
Solar/Wind Harmer
1.937
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
971191AH1-055 GEN
Solar/Wind Harmer
19.175
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
944531AF1-118 GEN
Solar/Wind Harmer
33.233
270043AE2-236 GEN
Solar/Wind Harmer
4.754
252519AF1-045_GEN
Solar/Wind Harmer
3.844
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
9.036
25194608D.CRK4
Adder
1.732
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
971347AH1-153 GEN
Solar/Wind Harmer
3.658
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.95
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
970289AG2-191 GEN
Solar/Wind Harmer
0.8
945111AF1-176 GEN
Solar/Wind Harmer
5.891
247642Z2-115 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
274753CRETE EC ;3U
Adder
8.436
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274811UNIV PK N;7U
Adder
5.114
972167AH1-666 GEN
Solar/Wind Harmer
5.69
274803UNIV PARK;6U
Adder
5.941
24728705AND G3
Adder
8.173
24728505AND G1
Adder
3.908
274887GEN-1.85
Solar/Wind Harmer
0.185
276843GEN-1.7
Solar/Wind Harmer
0.23
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274826FISK ;BP
Adder
11.151
972038AH1-567 GEN2
Adder
0.372
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
972259AH1-714 GEN
Adder
19.413
274676JOLIET 29;8U
Adder
30.039
274729ELWOOD EC;1P
Adder
16.687
274730ELWOOD EC;6P
Adder
16.687
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
274682WAUKEGAN ;7U
Adder
18.096
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970193AG2-126 GEN
Solar/Wind Harmer
10.468
970571AG2-364 GEN
Solar/Wind Harmer
13.944
964991AG1-363 GEN
Solar/Wind Helper
5.155
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.831
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
23562501BACKB
Solar/Wind Helper
1.012
235063AE1-101 C2
Solar/Wind Helper
1.672
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.512
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.594
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.868
316044AC1-158 PL1
Solar/Wind Helper
1.303
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.516
270166AC1-044 GEN3
50/50
7.069
23559101PLEAS2
50/50
6.097
962761AG1-125 GEN
Solar/Wind Harmer
34.394
970149AG2-104 GEN
Solar/Wind Harmer
18.573
970155AG2-107 GEN
Solar/Wind Harmer
21.963
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.894
270273AD2-016 GEN
Solar/Wind Harmer
0.807
972269AH1-719 GEN
Adder
2.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965421AG1-410 GEN
Solar/Wind Harmer
22.47
960001AF2-291 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965011AG1-365 GEN
Solar/Wind Harmer
7.453
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
958861AF2-177 GEN
Solar/Wind Harmer
3.191
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.732
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.351
970825AG2-519 GEN
Solar/Wind Harmer
2.589
24639705ELKHART HY
Adder
0.16
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
276903AD2-071 C
Solar/Wind Harmer
8.095
25196008MFTGT1
Adder
1.443
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.365
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274754CRETE EC ;4U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
274802UNIV PARK;5U
Adder
5.941
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
31.151
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
939401AE1-172 GEN
Solar/Wind Harmer
5.275
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
274682WAUKEGAN ;7U
Adder
18.096
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.818
971997AH1-543 GEN
Solar/Wind Harmer
3.68
962781AG1-127 GEN
Solar/Wind Harmer
6.668
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
316095T157 G97
Solar/Wind Helper
1.51
23583801GRNGAP
Solar/Wind Helper
5.626
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
238126S14_GEN_1
Solar/Wind Helper
0.831
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.661
237038AE2-054 C
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.58
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
202652Y1-033 WT C
Solar/Wind Helper
0.5
959091AF2-200 GEN
Solar/Wind Harmer
9.057
20715028HAN_X4-015
Solar/Wind Helper
0.057
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.031
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.792
211065PSPA IPP
Solar/Wind Helper
0.152
963161AG1-165 GEN
Solar/Wind Helper
0.441
957471AF2-041 GEN
Solar/Wind Harmer
13.586
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4632.89
MW Contribution:
14.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-008B_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-008B_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.03 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2339.9
MW Contribution:
14.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.743
241832AE2-181_GEN
Solar/Wind Harmer
1.961
958321AF2-126 GEN
Solar/Wind Harmer
1.441
23906402RICHG1
Adder
1.32
23906502RICHG2&3
Adder
1.317
270541AE2-072 C
Solar/Wind Harmer
4.329
270044AE2-322 C
Solar/Wind Harmer
0.914
246938BC-WTG3
Solar/Wind Harmer
2.562
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
270505AE1-170 C O1
Solar/Wind Harmer
9.622
945111AF1-176 GEN
Solar/Wind Harmer
3.627
958091AF2-103 GEN
Solar/Wind Harmer
0.103
270588AE1-091_GEN
Solar/Wind Harmer
7.015
24695305TIMB G C
Solar/Wind Harmer
2.067
247643Z2-116 C
Solar/Wind Harmer
0.043
270063AE2-323 C
Solar/Wind Harmer
1.342
24441505OLIV SLR
Solar/Wind Harmer
0.079
965021AG1-366 GEN
Solar/Wind Harmer
1.368
971347AH1-153 GEN
Solar/Wind Harmer
2.83
270043AE2-236 GEN
Solar/Wind Harmer
3.087
942871AE2-306 GEN
Solar/Wind Harmer
0.48
270391AF1-285 GEN3
Solar/Wind Harmer
0.246
972231SS25-0005
Solar/Wind Harmer
5.017
972181SS23-001
Solar/Wind Harmer
3.136
274752CRETE EC ;2U
Adder
2.584
274753CRETE EC ;3U
Adder
2.584
964401AG1-302 GEN
Solar/Wind Harmer
4.778
274724RIVER EC ;11
Adder
9.287
274814UNIV PK N;0U
Adder
2.638
274807UNIV PK N;3U
Adder
2.632
274811UNIV PK N;7U
Adder
2.615
276164X3-005 C
Solar/Wind Harmer
0.365
274803UNIV PARK;6U
Adder
3.011
274826FISK ;BP
Adder
5.643
972038AH1-567 GEN2
Adder
0.188
274887GEN-1.85
Solar/Wind Harmer
2.738
276772AC2-154 GEN
Solar/Wind Harmer
1.434
276843GEN-1.7
Solar/Wind Harmer
0.295
276806AD2-047 C O1
Solar/Wind Harmer
5.497
24189902OREGON_CT2
50/50
4.089
23856402BAYSG1
50/50
1.557
23888702TROY G3
50/50
1.501
972253AH1-711 GEN
50/50
45.89
23920202STRYCT
50/50
1.897
241858AF1-205_GEN
Solar/Wind Harmer
5.334
241840AF1-064_GEN
Solar/Wind Harmer
1.34
23906502RICHG2&3
Adder
1.317
960841AF2-375 GEN
Solar/Wind Harmer
3.591
270297AD1-101 GEN
Solar/Wind Harmer
1.459
24441205WTRV SLR C
Solar/Wind Harmer
0.093
270258AD1-119 GEN
Solar/Wind Harmer
1.367
270449AD2-020 GEN
Solar/Wind Harmer
1.841
943021AE2-325 GEN
Solar/Wind Harmer
2.392
246936BC-WTG1
Solar/Wind Harmer
2.519
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
945111AF1-176 GEN
Solar/Wind Harmer
11.445
957891AF2-083 GEN
Solar/Wind Harmer
9.587
965421AG1-410 GEN
Solar/Wind Harmer
19.157
24639705ELKHART HY
Adder
0.095
270216AD2-079_GEN
Solar/Wind Harmer
0.372
965011AG1-365 GEN
Solar/Wind Harmer
5.881
270317AD1-130_GEN
Solar/Wind Harmer
1.825
270485AE1-090_GEN
Solar/Wind Harmer
0.345
970373AG2-245 GEN
Solar/Wind Harmer
11.453
270055AF2-134 C O1
Solar/Wind Harmer
1.621
270391AF1-285 GEN3
Solar/Wind Harmer
0.641
270578AF1-285 GEN2
Solar/Wind Harmer
0.641
274751CRETE EC ;1U
Adder
2.584
274754CRETE EC ;4U
Adder
2.584
958381AF2-132 GEN
Solar/Wind Harmer
4.778
964861AG1-349 GEN
Solar/Wind Harmer
4.133
971917AH1-482 GEN
Solar/Wind Harmer
4.768
274723RIVER EC ;12
Adder
9.399
274812UNIV PK N;8U
Adder
2.615
274802UNIV PARK;5U
Adder
3.011
972207SS24-0001
Solar/Wind Harmer
11.321
23888502TROY G1
50/50
1.501
23888602TROY G2
50/50
1.501
945411AF1-206 GEN
Solar/Wind Harmer
8.227
945641AF1-229 GEN
Solar/Wind Harmer
3.751
270361_3
Solar/Wind Harmer
8.067
270575GUS2 35KV
Solar/Wind Harmer
9.503
270499AE1-146 GEN
Solar/Wind Harmer
2.264
971549AH1-272 GEN
Solar/Wind Harmer
14.988
270404AC1-167 GEN
Solar/Wind Harmer
0.754
944161AF1-084 GEN
Solar/Wind Harmer
1.472
957201AF2-014 GEN
Solar/Wind Harmer
2.92
270435AC2-044 GEN
Solar/Wind Harmer
1.288
270007AE1-245 C
Solar/Wind Harmer
3.452
970031AG2-029 GEN
Solar/Wind Harmer
15.263
971771AH1-392 GEN
Solar/Wind Harmer
5.464
965041AG1-368 GEN
Solar/Wind Harmer
6.054
247521TR3_G114
Solar/Wind Harmer
2.02
270191TR4_S_V150
Solar/Wind Harmer
1.802
965051AG1-369 GEN
Solar/Wind Harmer
3.001
966831AG1-554 GEN
Solar/Wind Harmer
0.715
270526AF1-158 GEN
Solar/Wind Harmer
2.699
959331AF2-224 GEN
Solar/Wind Harmer
5.881
270302AB2-170 GEN
Solar/Wind Harmer
4.774
960681AF2-359 GEN
Solar/Wind Harmer
2.151
963791AG1-232 GEN
Solar/Wind Harmer
7.333
971567AH1-282 GEN
Solar/Wind Harmer
2.703
270223U2-072_GEN1
Solar/Wind Harmer
1.046
270224U2-072_GEN2
Solar/Wind Harmer
1.046
270227U2-072_GEN3
Solar/Wind Harmer
1.046
270228U2-072_GEN4
Solar/Wind Harmer
1.046
270231U2-072_GEN5
Solar/Wind Harmer
1.046
270578AF1-285 GEN2
Solar/Wind Harmer
0.246
270071AF1-092 GEN
Solar/Wind Harmer
7.829
958391AF2-133 GEN
Solar/Wind Harmer
4.733
959141AF2-205 GEN
Solar/Wind Harmer
3.133
972037AH1-567 GEN1
Adder
0.095
274827FISK ;RP
Adder
3.999
274800UNIV PARK;3U
Adder
3.001
274801UNIV PARK;4U
Adder
3.001
960591AF2-350 GEN
Solar/Wind Harmer
5.139
24190002OREGON_ST1
50/50
5.502
24189802OREGON_CT1
50/50
4.176
23888802TROY G4
50/50
1.501
241996AE2-282_GEN
Solar/Wind Harmer
2.197
241808AF1-120 C
Solar/Wind Harmer
1.225
944231AF1-091 GEN
Solar/Wind Harmer
12.691
247522W1-056 GEN
Solar/Wind Harmer
1.562
961051AF2-396 GEN
Solar/Wind Harmer
10.336
961051AF2-396 GEN
Solar/Wind Harmer
4.807
246937BC-WTG2
Solar/Wind Harmer
2.519
247607V1-011 GEN
Solar/Wind Harmer
2.527
942801AE2-298 GEN
Solar/Wind Harmer
0.959
247620Y3-023
Adder
0.286
270246TR4_N_V150
Solar/Wind Harmer
0.511
270247TR4_N_V136
Solar/Wind Harmer
0.511
270462AD2-086
Solar/Wind Harmer
3.965
965681AG1-436 GEN
Solar/Wind Harmer
7.116
965791AG1-447 GEN
Solar/Wind Harmer
3.641
970349AG2-230 GEN
Solar/Wind Harmer
8.491
270535AF1-215 GEN1
Solar/Wind Harmer
2.432
270536AF1-215 GEN2
Solar/Wind Harmer
2.432
274805UNIV PK N;1U
Adder
2.621
274808UNIV PK N;4U
Adder
2.603
274888KELLY CRK;1U
Solar/Wind Harmer
3.032
276776AD2-060 GEN
Solar/Wind Harmer
0.215
958011AF2-095 GEN
Solar/Wind Harmer
7.4
970941AG2-585 GEN
Solar/Wind Harmer
2.826
274772LINCOLN ;3U
Adder
3.184
972259AH1-714 GEN
Adder
9.73
274676JOLIET 29;8U
Adder
15.077
939351AE1-166 GEN
Solar/Wind Harmer
3.019
274729ELWOOD EC;1P
Adder
8.362
274730ELWOOD EC;6P
Adder
8.362
274734ELWOOD EC;8P
Adder
8.362
274736ELWOOD EC;9P
Adder
8.362
970707AG2-453 GEN
Solar/Wind Harmer
14.241
943121AE2-341 GEN
Solar/Wind Harmer
7.542
943591AF1-030 GEN
Solar/Wind Harmer
5.028
274862TOP CROP ;2U
Solar/Wind Harmer
2.543
274682WAUKEGAN ;7U
Adder
8.979
276868AE1-113 GEN
Solar/Wind Harmer
5.016
274879MINONK ;1U
Solar/Wind Harmer
3.344
24690905MDL-1G C
Solar/Wind Harmer
3.969
274760LEE CO EC;1U
Adder
4.494
274767LEE CO EC;8U
Adder
4.442
962511AG1-100 GEN
Solar/Wind Helper
0.361
274775LINCOLN ;6U
Adder
3.184
274776LINCOLN ;7U
Adder
3.184
274777LINCOLN ;8U
Adder
3.184
972228AH1-698 GEN2
Adder
1.898
972227AH1-698 GEN1
Adder
1.336
274687WILL CNTY;4U
Adder
14.27
274687WILL CNTY;4U
Adder
14.27
274675JOLIET 29;7U
Adder
15.636
274675JOLIET 29;7U
Adder
15.077
276893AG1-478 C
Solar/Wind Harmer
0.28
274728ELWOOD EC;5P
Adder
8.362
274731ELWOOD EC;2P
Adder
8.362
274733ELWOOD EC;3P
Adder
8.362
274735ELWOOD EC;4P
Adder
8.362
970833AG2-524 GEN
Solar/Wind Harmer
4.419
970833AG2-524 GEN
Solar/Wind Harmer
2.055
274744AC1-111 GEN8
Adder
2.812
274746AC1-111 G10
Adder
2.812
970073AG2-061 GEN
Solar/Wind Harmer
1.159
946581AF1-322 GEN
Solar/Wind Harmer
5.059
274823ROCKFORD ;21
Adder
9.524
24729505KEY G4
Adder
3.154
972267AH1-718 GEN
Adder
1.998
241886AC2-103 GEN2
Solar/Wind Helper
6.895
241985AE1-237 GEN
Solar/Wind Helper
0.139
241982AE2-343 S C
Solar/Wind Helper
0.125
203846AF2-130 C
Solar/Wind Helper
0.261
241997AF1-093 GEN
Solar/Wind Helper
0.138
20334926Z1-069 C
Solar/Wind Helper
0.677
24691005MDL-2G C
Solar/Wind Harmer
0.649
274773LINCOLN ;4U
Adder
3.184
274774LINCOLN ;5U
Adder
3.184
940581AE2-045 GEN
Solar/Wind Harmer
5.237
971605AH1-302 GEN
Solar/Wind Harmer
4.478
274676JOLIET 29;8U
Adder
15.636
941551AE2-152 GEN
Solar/Wind Harmer
2.309
274732ELWOOD EC;7P
Adder
8.362
274674JOLIET 9 ;6U
Adder
7.832
274871GR RIDGE ;2U
Solar/Wind Harmer
3.89
274847GR RIDGE ;BU
Solar/Wind Harmer
2.558
274745AC1-111 GEN9
Adder
2.812
276694AA1-018 GEN2
Solar/Wind Harmer
3.172
276691AA1-018 GEN1
Solar/Wind Harmer
0.379
274861TOP CROP ;1U
Solar/Wind Harmer
3.045
274682WAUKEGAN ;7U
Adder
8.979
274828WAUKEGAN ;BP
Adder
5.513
276805AD2-038 GEN
Solar/Wind Harmer
2.555
939401AE1-172 GEN
Solar/Wind Harmer
6.92
276882AE2-255 GEN
Solar/Wind Harmer
1.672
962781AG1-127 GEN
Solar/Wind Harmer
4.714
274872LEEDK;1U
Solar/Wind Harmer
4.063
274822ROCKFORD ;11
Adder
9.594
274761LEE CO EC;2U
Adder
4.494
274766LEE CO EC;7U
Adder
4.442
241885AC2-103 GEN1
Solar/Wind Helper
6.895
241807AE2-176_GEN
Solar/Wind Helper
1.68
203947AF1-006 C
Solar/Wind Helper
0.403
961971AG1-040 GEN
Solar/Wind Helper
0.353
203830AF1-094 GEN
Solar/Wind Helper
0.342
203979AG1-198 GEN
Solar/Wind Helper
0.205
241966AE1-183 GEN
Solar/Wind Helper
0.138
254303AC2-168 GEN
Solar/Wind Helper
0.08
274770LINCOLN ;1U
Adder
3.184
274771LINCOLN ;2U
Adder
3.184
276897AD1-100 C
Solar/Wind Harmer
23.646
276893AG1-478 C
Solar/Wind Harmer
0.223
274674JOLIET 9 ;6U
Adder
7.832
958481AF2-142 GEN
Solar/Wind Harmer
7.541
945421AF1-207 GEN
Solar/Wind Harmer
7.034
957841AF2-078 GEN
Solar/Wind Harmer
3.028
942221AE2-234 GEN
Solar/Wind Harmer
1.751
274696ROCKY RD ;4P
Adder
5.692
274695ROCKY RD ;2P
Adder
5.561
274693ROCKY RD ;1P
Adder
5.506
274697ROCKY RD ;3P
Adder
1.511
274683WAUKEGAN ;8U
Adder
10.518
274683WAUKEGAN ;8U
Adder
8.866
958491AF2-143 GEN
Solar/Wind Harmer
7.474
276901AD2-066 C O1
Solar/Wind Harmer
1.742
962691AG1-118 GEN
Solar/Wind Harmer
14.897
960751AF2-366 GEN
Solar/Wind Harmer
1.422
270180AB1-006 GEN1
Solar/Wind Harmer
3.556
972235AH1-702 GEN1
Adder
1.23
972236AH1-702 GEN2
Adder
1.07
274764LEE CO EC;5U
Adder
4.505
274765LEE CO EC;6U
Adder
4.505
274762LEE CO EC;3U
Adder
4.494
274763LEE CO EC;4U
Adder
4.452
247621Y3-024
Adder
0.11
25326509SID D
Adder
0.588
203835AF1-098 GEN
Solar/Wind Helper
1.395
241967AE2-285_GEN
Solar/Wind Helper
0.358
241801AE1-079 GEN
Solar/Wind Helper
0.14
254304AE2-114 C
Solar/Wind Helper
0.119
254305AE2-115 C
Solar/Wind Helper
0.119
962101AG1-054 GEN
Solar/Wind Helper
0.345
203804AE2-113_GEN
Solar/Wind Helper
0.91
940863AE2-074 GEN
Solar/Wind Helper
0.236
946381AF1-302 GEN
Solar/Wind Helper
0.11
203954AE2-126 C
Solar/Wind Helper
0.229
24697605MDL-3G C
Solar/Wind Harmer
0.647
990142J1224
External Queue
14.793254852294922
990527J1329
External Queue
2.0237011909484863
991182J1586 G
External Queue
28.12165069580078
991177J1571 G
External Queue
15.794994354248047
LAGNLTFEXP_LAGN->PJM
CLTF
5.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.754
TVALTFEXP_TVA->PJM
CLTF
2.558
NYPJM->LTFIMP_NY
CLTF
2.102
LGEELTFEXP_LGEE->PJM
CLTF
2.253
WECLTFEXP_WEC->PJM
CLTF
1.864
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
109.736
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.094
MECLTFEXP_MEC->PJM
CLTF
7.273
SIGELTFEXP_SIGE->PJM
CLTF
0.188
CPLELTFEXP_CPLE->PJM
CLTF
0.497
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.653

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-013_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.03 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:1986.46
MW Contribution:
15.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.766
241832AE2-181_GEN
Solar/Wind Harmer
1.991
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.342
270541AE2-072 C
Solar/Wind Harmer
4.424
270044AE2-322 C
Solar/Wind Harmer
0.943
246938BC-WTG3
Solar/Wind Harmer
2.65
270491AE1-102 GEN2
Solar/Wind Harmer
0.866
270505AE1-170 C O1
Solar/Wind Harmer
9.953
945111AF1-176 GEN
Solar/Wind Harmer
3.752
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.254
24695305TIMB G C
Solar/Wind Harmer
2.14
247643Z2-116 C
Solar/Wind Harmer
0.044
270063AE2-323 C
Solar/Wind Harmer
1.39
23888502TROY G1
50/50
1.535
23888602TROY G2
50/50
1.535
945411AF1-206 GEN
Solar/Wind Harmer
8.35
945641AF1-229 GEN
Solar/Wind Harmer
3.836
270361_3
Solar/Wind Harmer
8.243
270575GUS2 35KV
Solar/Wind Harmer
9.711
270499AE1-146 GEN
Solar/Wind Harmer
2.316
971549AH1-272 GEN
Solar/Wind Harmer
15.401
270404AC1-167 GEN
Solar/Wind Harmer
0.777
944161AF1-084 GEN
Solar/Wind Harmer
1.521
957201AF2-014 GEN
Solar/Wind Harmer
3.021
270435AC2-044 GEN
Solar/Wind Harmer
1.332
270007AE1-245 C
Solar/Wind Harmer
3.57
970031AG2-029 GEN
Solar/Wind Harmer
15.814
971771AH1-392 GEN
Solar/Wind Harmer
5.662
965041AG1-368 GEN
Solar/Wind Harmer
6.273
247521TR3_G114
Solar/Wind Harmer
2.094
270191TR4_S_V150
Solar/Wind Harmer
1.868
965051AG1-369 GEN
Solar/Wind Harmer
3.111
966831AG1-554 GEN
Solar/Wind Harmer
0.741
270526AF1-158 GEN
Solar/Wind Harmer
2.799
959331AF2-224 GEN
Solar/Wind Harmer
6.101
270302AB2-170 GEN
Solar/Wind Harmer
4.959
960681AF2-359 GEN
Solar/Wind Harmer
2.234
963791AG1-232 GEN
Solar/Wind Harmer
7.629
971567AH1-282 GEN
Solar/Wind Harmer
2.814
270223U2-072_GEN1
Solar/Wind Harmer
1.089
270224U2-072_GEN2
Solar/Wind Harmer
1.089
270227U2-072_GEN3
Solar/Wind Harmer
1.089
270228U2-072_GEN4
Solar/Wind Harmer
1.089
270231U2-072_GEN5
Solar/Wind Harmer
1.089
270578AF1-285 GEN2
Solar/Wind Harmer
0.257
270071AF1-092 GEN
Solar/Wind Harmer
8.159
958391AF2-133 GEN
Solar/Wind Harmer
4.932
959141AF2-205 GEN
Solar/Wind Harmer
3.266
972037AH1-567 GEN1
Adder
0.099
274827FISK ;RP
Adder
4.17
274800UNIV PARK;3U
Adder
3.129
274801UNIV PARK;4U
Adder
3.129
960591AF2-350 GEN
Solar/Wind Harmer
5.358
274775LINCOLN ;6U
Adder
3.32
274776LINCOLN ;7U
Adder
3.32
274777LINCOLN ;8U
Adder
3.32
972228AH1-698 GEN2
Adder
1.979
972227AH1-698 GEN1
Adder
1.393
274687WILL CNTY;4U
Adder
14.883
274687WILL CNTY;4U
Adder
14.883
274675JOLIET 29;7U
Adder
16.309
274675JOLIET 29;7U
Adder
15.727
276893AG1-478 C
Solar/Wind Harmer
0.292
274728ELWOOD EC;5P
Adder
8.723
274731ELWOOD EC;2P
Adder
8.723
274733ELWOOD EC;3P
Adder
8.723
274735ELWOOD EC;4P
Adder
8.723
970833AG2-524 GEN
Solar/Wind Harmer
4.611
970833AG2-524 GEN
Solar/Wind Harmer
2.144
274744AC1-111 GEN8
Adder
2.934
274746AC1-111 G10
Adder
2.934
970073AG2-061 GEN
Solar/Wind Harmer
1.21
946581AF1-322 GEN
Solar/Wind Harmer
5.283
274823ROCKFORD ;21
Adder
9.952
24729505KEY G4
Adder
3.296
972267AH1-718 GEN
Adder
2.089
241886AC2-103 GEN2
Solar/Wind Helper
6.851
24441505OLIV SLR
Solar/Wind Harmer
0.082
965021AG1-366 GEN
Solar/Wind Harmer
1.419
971347AH1-153 GEN
Solar/Wind Harmer
2.94
270043AE2-236 GEN
Solar/Wind Harmer
3.208
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.257
972231SS25-0005
Solar/Wind Harmer
5.226
972181SS23-001
Solar/Wind Harmer
3.266
274752CRETE EC ;2U
Adder
2.692
274753CRETE EC ;3U
Adder
2.692
964401AG1-302 GEN
Solar/Wind Harmer
4.977
274724RIVER EC ;11
Adder
9.676
274814UNIV PK N;0U
Adder
2.749
274807UNIV PK N;3U
Adder
2.743
274811UNIV PK N;7U
Adder
2.725
276164X3-005 C
Solar/Wind Harmer
0.381
274803UNIV PARK;6U
Adder
3.139
274826FISK ;BP
Adder
5.884
972038AH1-567 GEN2
Adder
0.196
274887GEN-1.85
Solar/Wind Harmer
2.855
276772AC2-154 GEN
Solar/Wind Harmer
1.495
276843GEN-1.7
Solar/Wind Harmer
0.307
276806AD2-047 C O1
Solar/Wind Harmer
5.732
274772LINCOLN ;3U
Adder
3.32
972259AH1-714 GEN
Adder
10.149
274676JOLIET 29;8U
Adder
15.727
939351AE1-166 GEN
Solar/Wind Harmer
3.149
274729ELWOOD EC;1P
Adder
8.723
274730ELWOOD EC;6P
Adder
8.723
274734ELWOOD EC;8P
Adder
8.723
274736ELWOOD EC;9P
Adder
8.723
970707AG2-453 GEN
Solar/Wind Harmer
14.856
943121AE2-341 GEN
Solar/Wind Harmer
7.872
943591AF1-030 GEN
Solar/Wind Harmer
5.248
274862TOP CROP ;2U
Solar/Wind Harmer
2.654
274682WAUKEGAN ;7U
Adder
9.373
276868AE1-113 GEN
Solar/Wind Harmer
5.238
274879MINONK ;1U
Solar/Wind Harmer
3.492
24690905MDL-1G C
Solar/Wind Harmer
4.145
274760LEE CO EC;1U
Adder
4.698
274767LEE CO EC;8U
Adder
4.643
24728705AND G3
Adder
3.479
24728505AND G1
Adder
1.663
962511AG1-100 GEN
Solar/Wind Helper
0.351
241985AE1-237 GEN
Solar/Wind Helper
0.134
241982AE2-343 S C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
20334926Z1-069 C
Solar/Wind Helper
0.647
24691005MDL-2G C
Solar/Wind Harmer
0.678
24190002OREGON_ST1
50/50
5.544
24189802OREGON_CT1
50/50
4.207
23888802TROY G4
50/50
1.535
241996AE2-282_GEN
Solar/Wind Harmer
2.23
241808AF1-120 C
Solar/Wind Harmer
1.243
944231AF1-091 GEN
Solar/Wind Harmer
13.082
247522W1-056 GEN
Solar/Wind Harmer
1.61
961051AF2-396 GEN
Solar/Wind Harmer
10.687
961051AF2-396 GEN
Solar/Wind Harmer
4.971
246937BC-WTG2
Solar/Wind Harmer
2.605
247607V1-011 GEN
Solar/Wind Harmer
2.613
942801AE2-298 GEN
Solar/Wind Harmer
0.992
247620Y3-023
Adder
0.296
270246TR4_N_V150
Solar/Wind Harmer
0.53
24189902OREGON_CT2
50/50
4.12
23856402BAYSG1
50/50
1.57
23888702TROY G3
50/50
1.535
972253AH1-711 GEN
50/50
46.93
23920202STRYCT
50/50
1.926
241858AF1-205_GEN
Solar/Wind Harmer
5.41
241840AF1-064_GEN
Solar/Wind Harmer
1.357
23906502RICHG2&3
Adder
1.342
960841AF2-375 GEN
Solar/Wind Harmer
3.671
270297AD1-101 GEN
Solar/Wind Harmer
1.503
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.411
270449AD2-020 GEN
Solar/Wind Harmer
1.903
943021AE2-325 GEN
Solar/Wind Harmer
2.473
246936BC-WTG1
Solar/Wind Harmer
2.605
270489AE1-102 GEN1
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
11.839
957891AF2-083 GEN
Solar/Wind Harmer
9.919
965421AG1-410 GEN
Solar/Wind Harmer
19.821
24639705ELKHART HY
Adder
0.099
270216AD2-079_GEN
Solar/Wind Harmer
0.386
965011AG1-365 GEN
Solar/Wind Harmer
6.101
270317AD1-130_GEN
Solar/Wind Harmer
1.896
270485AE1-090_GEN
Solar/Wind Harmer
0.358
970373AG2-245 GEN
Solar/Wind Harmer
11.915
270055AF2-134 C O1
Solar/Wind Harmer
1.688
270391AF1-285 GEN3
Solar/Wind Harmer
0.667
270578AF1-285 GEN2
Solar/Wind Harmer
0.667
274751CRETE EC ;1U
Adder
2.692
274754CRETE EC ;4U
Adder
2.692
958381AF2-132 GEN
Solar/Wind Harmer
4.977
964861AG1-349 GEN
Solar/Wind Harmer
4.306
971917AH1-482 GEN
Solar/Wind Harmer
4.967
274723RIVER EC ;12
Adder
9.793
274812UNIV PK N;8U
Adder
2.725
274802UNIV PARK;5U
Adder
3.139
972207SS24-0001
Solar/Wind Harmer
11.805
274773LINCOLN ;4U
Adder
3.32
274774LINCOLN ;5U
Adder
3.32
940581AE2-045 GEN
Solar/Wind Harmer
5.461
971605AH1-302 GEN
Solar/Wind Harmer
4.669
274676JOLIET 29;8U
Adder
16.309
941551AE2-152 GEN
Solar/Wind Harmer
2.408
274732ELWOOD EC;7P
Adder
8.723
274674JOLIET 9 ;6U
Adder
8.17
274871GR RIDGE ;2U
Solar/Wind Harmer
4.058
274847GR RIDGE ;BU
Solar/Wind Harmer
2.669
274745AC1-111 GEN9
Adder
2.934
276694AA1-018 GEN2
Solar/Wind Harmer
3.311
276691AA1-018 GEN1
Solar/Wind Harmer
0.396
274861TOP CROP ;1U
Solar/Wind Harmer
3.178
274682WAUKEGAN ;7U
Adder
9.373
274828WAUKEGAN ;BP
Adder
5.756
276805AD2-038 GEN
Solar/Wind Harmer
2.668
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276882AE2-255 GEN
Solar/Wind Harmer
1.746
962781AG1-127 GEN
Solar/Wind Harmer
4.923
274872LEEDK;1U
Solar/Wind Harmer
4.243
274822ROCKFORD ;11
Adder
10.024
274761LEE CO EC;2U
Adder
4.698
274766LEE CO EC;7U
Adder
4.643
24728605AND G2
Adder
1.663
241885AC2-103 GEN1
Solar/Wind Helper
6.851
241807AE2-176_GEN
Solar/Wind Helper
1.655
203947AF1-006 C
Solar/Wind Helper
0.392
961971AG1-040 GEN
Solar/Wind Helper
0.343
203830AF1-094 GEN
Solar/Wind Helper
0.332
203979AG1-198 GEN
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
270247TR4_N_V136
Solar/Wind Harmer
0.53
270462AD2-086
Solar/Wind Harmer
4.119
965681AG1-436 GEN
Solar/Wind Harmer
7.392
965791AG1-447 GEN
Solar/Wind Harmer
3.782
970349AG2-230 GEN
Solar/Wind Harmer
8.821
270535AF1-215 GEN1
Solar/Wind Harmer
2.532
270536AF1-215 GEN2
Solar/Wind Harmer
2.532
274805UNIV PK N;1U
Adder
2.731
274808UNIV PK N;4U
Adder
2.713
274888KELLY CRK;1U
Solar/Wind Harmer
3.162
276776AD2-060 GEN
Solar/Wind Harmer
0.224
958011AF2-095 GEN
Solar/Wind Harmer
7.716
970941AG2-585 GEN
Solar/Wind Harmer
2.947
274770LINCOLN ;1U
Adder
3.32
274771LINCOLN ;2U
Adder
3.32
276897AD1-100 C
Solar/Wind Harmer
24.666
276893AG1-478 C
Solar/Wind Harmer
0.233
274674JOLIET 9 ;6U
Adder
8.17
958481AF2-142 GEN
Solar/Wind Harmer
7.87
945421AF1-207 GEN
Solar/Wind Harmer
7.342
957841AF2-078 GEN
Solar/Wind Harmer
3.161
942221AE2-234 GEN
Solar/Wind Harmer
1.828
274696ROCKY RD ;4P
Adder
5.942
274695ROCKY RD ;2P
Adder
5.805
274693ROCKY RD ;1P
Adder
5.748
274697ROCKY RD ;3P
Adder
1.577
274683WAUKEGAN ;8U
Adder
10.981
274683WAUKEGAN ;8U
Adder
9.256
958491AF2-143 GEN
Solar/Wind Harmer
7.804
276901AD2-066 C O1
Solar/Wind Harmer
1.819
962691AG1-118 GEN
Solar/Wind Harmer
15.555
960751AF2-366 GEN
Solar/Wind Harmer
1.485
270180AB1-006 GEN1
Solar/Wind Harmer
3.714
972235AH1-702 GEN1
Adder
1.285
972236AH1-702 GEN2
Adder
1.118
274764LEE CO EC;5U
Adder
4.71
274765LEE CO EC;6U
Adder
4.71
274762LEE CO EC;3U
Adder
4.698
274763LEE CO EC;4U
Adder
4.654
247621Y3-024
Adder
0.115
25326509SID D
Adder
0.617
203835AF1-098 GEN
Solar/Wind Helper
1.352
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.135
254304AE2-114 C
Solar/Wind Helper
0.115
254305AE2-115 C
Solar/Wind Helper
0.115
962101AG1-054 GEN
Solar/Wind Helper
0.332
203804AE2-113_GEN
Solar/Wind Helper
0.871
940863AE2-074 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Helper
0.105
24697605MDL-3G C
Solar/Wind Harmer
0.676
990142J1224
External Queue
14.817167282104492
990527J1329
External Queue
2.0269722938537598
991182J1586 G
External Queue
28.167613983154297
991177J1571 G
External Queue
15.820918083190918
LAGNLTFEXP_LAGN->PJM
CLTF
6.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.406
TVALTFEXP_TVA->PJM
CLTF
2.778
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
2.403
WECLTFEXP_WEC->PJM
CLTF
1.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.976
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.92
MECLTFEXP_MEC->PJM
CLTF
7.641
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CPLELTFEXP_CPLE->PJM
CLTF
0.733
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.592

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.03 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:1986.44
MW Contribution:
15.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
4.12
23856402BAYSG1
50/50
1.57
23888702TROY G3
50/50
1.535
972253AH1-711 GEN
50/50
46.927
23920202STRYCT
50/50
1.926
23929302BS-PKR
50/50
2.766
241832AE2-181_GEN
Solar/Wind Harmer
1.991
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.342
270541AE2-072 C
Solar/Wind Harmer
4.424
270044AE2-322 C
Solar/Wind Harmer
0.943
246938BC-WTG3
Solar/Wind Harmer
2.65
270491AE1-102 GEN2
Solar/Wind Harmer
0.866
270505AE1-170 C O1
Solar/Wind Harmer
9.953
945111AF1-176 GEN
Solar/Wind Harmer
3.752
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.254
24695305TIMB G C
Solar/Wind Harmer
2.14
247643Z2-116 C
Solar/Wind Harmer
0.044
270063AE2-323 C
Solar/Wind Harmer
1.39
24441505OLIV SLR
Solar/Wind Harmer
0.082
965021AG1-366 GEN
Solar/Wind Harmer
1.419
971347AH1-153 GEN
Solar/Wind Harmer
2.94
270043AE2-236 GEN
Solar/Wind Harmer
3.208
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.257
972231SS25-0005
Solar/Wind Harmer
5.226
972181SS23-001
Solar/Wind Harmer
3.266
274752CRETE EC ;2U
Adder
2.691
274753CRETE EC ;3U
Adder
2.691
964401AG1-302 GEN
Solar/Wind Harmer
4.977
274724RIVER EC ;11
Adder
9.676
274814UNIV PK N;0U
Adder
2.749
274807UNIV PK N;3U
Adder
2.743
274811UNIV PK N;7U
Adder
2.725
276164X3-005 C
Solar/Wind Harmer
0.381
274803UNIV PARK;6U
Adder
3.139
274826FISK ;BP
Adder
5.884
972038AH1-567 GEN2
Adder
0.196
274887GEN-1.85
Solar/Wind Harmer
2.855
276772AC2-154 GEN
Solar/Wind Harmer
1.495
276843GEN-1.7
Solar/Wind Harmer
0.307
276806AD2-047 C O1
Solar/Wind Harmer
5.732
274772LINCOLN ;3U
Adder
3.32
972259AH1-714 GEN
Adder
10.149
274676JOLIET 29;8U
Adder
15.727
939351AE1-166 GEN
Solar/Wind Harmer
3.149
274729ELWOOD EC;1P
Adder
8.723
274730ELWOOD EC;6P
Adder
8.723
274734ELWOOD EC;8P
Adder
8.723
274736ELWOOD EC;9P
Adder
8.723
970707AG2-453 GEN
Solar/Wind Harmer
14.856
943121AE2-341 GEN
Solar/Wind Harmer
7.872
943591AF1-030 GEN
Solar/Wind Harmer
5.248
274862TOP CROP ;2U
Solar/Wind Harmer
2.653
274682WAUKEGAN ;7U
Adder
9.373
276868AE1-113 GEN
Solar/Wind Harmer
5.238
274879MINONK ;1U
Solar/Wind Harmer
3.492
24690905MDL-1G C
Solar/Wind Harmer
4.145
274760LEE CO EC;1U
Adder
4.698
274767LEE CO EC;8U
Adder
4.643
24728705AND G3
Adder
3.479
24728505AND G1
Adder
1.663
962511AG1-100 GEN
Solar/Wind Helper
0.351
24190002OREGON_ST1
50/50
5.544
24189802OREGON_CT1
50/50
4.207
23888802TROY G4
50/50
1.535
241996AE2-282_GEN
Solar/Wind Harmer
2.23
241808AF1-120 C
Solar/Wind Harmer
1.243
944231AF1-091 GEN
Solar/Wind Harmer
13.082
247522W1-056 GEN
Solar/Wind Harmer
1.61
961051AF2-396 GEN
Solar/Wind Harmer
10.687
961051AF2-396 GEN
Solar/Wind Harmer
4.971
246937BC-WTG2
Solar/Wind Harmer
2.605
247607V1-011 GEN
Solar/Wind Harmer
2.613
942801AE2-298 GEN
Solar/Wind Harmer
0.992
247620Y3-023
Adder
0.296
270246TR4_N_V150
Solar/Wind Harmer
0.53
270247TR4_N_V136
Solar/Wind Harmer
0.53
270462AD2-086
Solar/Wind Harmer
4.119
965681AG1-436 GEN
Solar/Wind Harmer
7.392
965791AG1-447 GEN
Solar/Wind Harmer
3.782
970349AG2-230 GEN
Solar/Wind Harmer
8.821
270535AF1-215 GEN1
Solar/Wind Harmer
2.532
270536AF1-215 GEN2
Solar/Wind Harmer
2.532
274805UNIV PK N;1U
Adder
2.731
274808UNIV PK N;4U
Adder
2.713
274888KELLY CRK;1U
Solar/Wind Harmer
3.162
276776AD2-060 GEN
Solar/Wind Harmer
0.224
958011AF2-095 GEN
Solar/Wind Harmer
7.716
970941AG2-585 GEN
Solar/Wind Harmer
2.947
274770LINCOLN ;1U
Adder
3.32
274771LINCOLN ;2U
Adder
3.32
276897AD1-100 C
Solar/Wind Harmer
24.666
276893AG1-478 C
Solar/Wind Harmer
0.233
274674JOLIET 9 ;6U
Adder
8.17
958481AF2-142 GEN
Solar/Wind Harmer
7.87
945421AF1-207 GEN
Solar/Wind Harmer
7.342
957841AF2-078 GEN
Solar/Wind Harmer
3.161
942221AE2-234 GEN
Solar/Wind Harmer
1.828
274696ROCKY RD ;4P
Adder
5.942
274695ROCKY RD ;2P
Adder
5.805
274693ROCKY RD ;1P
Adder
5.748
274697ROCKY RD ;3P
Adder
1.577
274683WAUKEGAN ;8U
Adder
10.981
274683WAUKEGAN ;8U
Adder
9.256
958491AF2-143 GEN
Solar/Wind Harmer
7.804
276901AD2-066 C O1
Solar/Wind Harmer
1.819
962691AG1-118 GEN
Solar/Wind Harmer
15.555
960751AF2-366 GEN
Solar/Wind Harmer
1.485
270180AB1-006 GEN1
Solar/Wind Harmer
3.713
972235AH1-702 GEN1
Adder
1.285
972236AH1-702 GEN2
Adder
1.118
274764LEE CO EC;5U
Adder
4.709
274765LEE CO EC;6U
Adder
4.709
274762LEE CO EC;3U
Adder
4.698
274763LEE CO EC;4U
Adder
4.654
247621Y3-024
Adder
0.115
25326509SID D
Adder
0.617
203835AF1-098 GEN
Solar/Wind Helper
1.352
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.135
254304AE2-114 C
Solar/Wind Helper
0.115
254305AE2-115 C
Solar/Wind Helper
0.115
962101AG1-054 GEN
Solar/Wind Helper
0.332
203804AE2-113_GEN
Solar/Wind Helper
0.871
940863AE2-074 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Helper
0.105
24697605MDL-3G C
Solar/Wind Harmer
0.676
23888502TROY G1
50/50
1.535
23888602TROY G2
50/50
1.535
945411AF1-206 GEN
Solar/Wind Harmer
8.35
945641AF1-229 GEN
Solar/Wind Harmer
3.836
270361_3
Solar/Wind Harmer
8.243
270575GUS2 35KV
Solar/Wind Harmer
9.711
270499AE1-146 GEN
Solar/Wind Harmer
2.316
971549AH1-272 GEN
Solar/Wind Harmer
15.401
270404AC1-167 GEN
Solar/Wind Harmer
0.777
944161AF1-084 GEN
Solar/Wind Harmer
1.521
957201AF2-014 GEN
Solar/Wind Harmer
3.021
270435AC2-044 GEN
Solar/Wind Harmer
1.332
270007AE1-245 C
Solar/Wind Harmer
3.57
970031AG2-029 GEN
Solar/Wind Harmer
15.814
971771AH1-392 GEN
Solar/Wind Harmer
5.662
965041AG1-368 GEN
Solar/Wind Harmer
6.273
247521TR3_G114
Solar/Wind Harmer
2.094
270191TR4_S_V150
Solar/Wind Harmer
1.868
965051AG1-369 GEN
Solar/Wind Harmer
3.111
966831AG1-554 GEN
Solar/Wind Harmer
0.741
270526AF1-158 GEN
Solar/Wind Harmer
2.799
959331AF2-224 GEN
Solar/Wind Harmer
6.101
270302AB2-170 GEN
Solar/Wind Harmer
4.959
960681AF2-359 GEN
Solar/Wind Harmer
2.234
963791AG1-232 GEN
Solar/Wind Harmer
7.629
971567AH1-282 GEN
Solar/Wind Harmer
2.814
270223U2-072_GEN1
Solar/Wind Harmer
1.089
270224U2-072_GEN2
Solar/Wind Harmer
1.089
270227U2-072_GEN3
Solar/Wind Harmer
1.089
270228U2-072_GEN4
Solar/Wind Harmer
1.089
270231U2-072_GEN5
Solar/Wind Harmer
1.089
270578AF1-285 GEN2
Solar/Wind Harmer
0.257
270071AF1-092 GEN
Solar/Wind Harmer
8.159
958391AF2-133 GEN
Solar/Wind Harmer
4.932
959141AF2-205 GEN
Solar/Wind Harmer
3.266
972037AH1-567 GEN1
Adder
0.099
274827FISK ;RP
Adder
4.17
274800UNIV PARK;3U
Adder
3.129
274801UNIV PARK;4U
Adder
3.129
960591AF2-350 GEN
Solar/Wind Harmer
5.358
274775LINCOLN ;6U
Adder
3.32
274776LINCOLN ;7U
Adder
3.32
274777LINCOLN ;8U
Adder
3.32
972228AH1-698 GEN2
Adder
1.979
972227AH1-698 GEN1
Adder
1.393
274687WILL CNTY;4U
Adder
14.883
274687WILL CNTY;4U
Adder
14.883
274675JOLIET 29;7U
Adder
16.309
274675JOLIET 29;7U
Adder
15.727
276893AG1-478 C
Solar/Wind Harmer
0.292
274728ELWOOD EC;5P
Adder
8.723
274731ELWOOD EC;2P
Adder
8.723
274733ELWOOD EC;3P
Adder
8.723
274735ELWOOD EC;4P
Adder
8.723
970833AG2-524 GEN
Solar/Wind Harmer
4.611
970833AG2-524 GEN
Solar/Wind Harmer
2.144
274744AC1-111 GEN8
Adder
2.934
274746AC1-111 G10
Adder
2.934
970073AG2-061 GEN
Solar/Wind Harmer
1.21
946581AF1-322 GEN
Solar/Wind Harmer
5.283
274823ROCKFORD ;21
Adder
9.951
24729505KEY G4
Adder
3.296
972267AH1-718 GEN
Adder
2.089
241886AC2-103 GEN2
Solar/Wind Helper
6.851
241985AE1-237 GEN
Solar/Wind Helper
0.134
241982AE2-343 S C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
20334926Z1-069 C
Solar/Wind Helper
0.647
24691005MDL-2G C
Solar/Wind Harmer
0.678
241858AF1-205_GEN
Solar/Wind Harmer
5.41
241840AF1-064_GEN
Solar/Wind Harmer
1.357
23906502RICHG2&3
Adder
1.342
960841AF2-375 GEN
Solar/Wind Harmer
3.671
270297AD1-101 GEN
Solar/Wind Harmer
1.503
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.411
270449AD2-020 GEN
Solar/Wind Harmer
1.903
943021AE2-325 GEN
Solar/Wind Harmer
2.473
246936BC-WTG1
Solar/Wind Harmer
2.605
270489AE1-102 GEN1
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
11.839
957891AF2-083 GEN
Solar/Wind Harmer
9.919
965421AG1-410 GEN
Solar/Wind Harmer
19.821
24639705ELKHART HY
Adder
0.099
270216AD2-079_GEN
Solar/Wind Harmer
0.386
965011AG1-365 GEN
Solar/Wind Harmer
6.101
270317AD1-130_GEN
Solar/Wind Harmer
1.896
270485AE1-090_GEN
Solar/Wind Harmer
0.358
970373AG2-245 GEN
Solar/Wind Harmer
11.915
270055AF2-134 C O1
Solar/Wind Harmer
1.688
270391AF1-285 GEN3
Solar/Wind Harmer
0.667
270578AF1-285 GEN2
Solar/Wind Harmer
0.667
274751CRETE EC ;1U
Adder
2.691
274754CRETE EC ;4U
Adder
2.691
958381AF2-132 GEN
Solar/Wind Harmer
4.977
964861AG1-349 GEN
Solar/Wind Harmer
4.305
971917AH1-482 GEN
Solar/Wind Harmer
4.967
274723RIVER EC ;12
Adder
9.793
274812UNIV PK N;8U
Adder
2.725
274802UNIV PARK;5U
Adder
3.139
972207SS24-0001
Solar/Wind Harmer
11.805
274773LINCOLN ;4U
Adder
3.32
274774LINCOLN ;5U
Adder
3.32
940581AE2-045 GEN
Solar/Wind Harmer
5.461
971605AH1-302 GEN
Solar/Wind Harmer
4.669
274676JOLIET 29;8U
Adder
16.309
941551AE2-152 GEN
Solar/Wind Harmer
2.408
274732ELWOOD EC;7P
Adder
8.723
274674JOLIET 9 ;6U
Adder
8.17
274871GR RIDGE ;2U
Solar/Wind Harmer
4.058
274847GR RIDGE ;BU
Solar/Wind Harmer
2.669
274745AC1-111 GEN9
Adder
2.934
276694AA1-018 GEN2
Solar/Wind Harmer
3.311
276691AA1-018 GEN1
Solar/Wind Harmer
0.396
274861TOP CROP ;1U
Solar/Wind Harmer
3.178
274682WAUKEGAN ;7U
Adder
9.373
274828WAUKEGAN ;BP
Adder
5.756
276805AD2-038 GEN
Solar/Wind Harmer
2.668
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276882AE2-255 GEN
Solar/Wind Harmer
1.746
962781AG1-127 GEN
Solar/Wind Harmer
4.923
274872LEEDK;1U
Solar/Wind Harmer
4.243
274822ROCKFORD ;11
Adder
10.024
274761LEE CO EC;2U
Adder
4.698
274766LEE CO EC;7U
Adder
4.643
24728605AND G2
Adder
1.663
241885AC2-103 GEN1
Solar/Wind Helper
6.851
241807AE2-176_GEN
Solar/Wind Helper
1.655
203947AF1-006 C
Solar/Wind Helper
0.392
961971AG1-040 GEN
Solar/Wind Helper
0.343
203830AF1-094 GEN
Solar/Wind Helper
0.332
203979AG1-198 GEN
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
990142J1224
External Queue
14.817001342773438
990527J1329
External Queue
2.026949882507324
991182J1586 G
External Queue
28.16729736328125
991177J1571 G
External Queue
15.82073974609375
LAGNLTFEXP_LAGN->PJM
CLTF
6.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.406
TVALTFEXP_TVA->PJM
CLTF
2.778
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
2.403
WECLTFEXP_WEC->PJM
CLTF
1.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.975
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.92
MECLTFEXP_MEC->PJM
CLTF
7.641
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CPLELTFEXP_CPLE->PJM
CLTF
0.733
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.591

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-009_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-009_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.85 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:1983.38
MW Contribution:
15.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.775
241832AE2-181_GEN
Solar/Wind Harmer
1.992
958321AF2-126 GEN
Solar/Wind Harmer
1.466
23906402RICHG1
Adder
1.346
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
4.426
270044AE2-322 C
Solar/Wind Harmer
0.942
246938BC-WTG3
Solar/Wind Harmer
2.647
270491AE1-102 GEN2
Solar/Wind Harmer
0.865
270505AE1-170 C O1
Solar/Wind Harmer
9.942
945111AF1-176 GEN
Solar/Wind Harmer
3.748
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.25
24695305TIMB G C
Solar/Wind Harmer
2.138
247643Z2-116 C
Solar/Wind Harmer
0.044
270063AE2-323 C
Solar/Wind Harmer
1.389
24441505OLIV SLR
Solar/Wind Harmer
0.082
965021AG1-366 GEN
Solar/Wind Harmer
1.417
971347AH1-153 GEN
Solar/Wind Harmer
2.937
270043AE2-236 GEN
Solar/Wind Harmer
3.204
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
972231SS25-0005
Solar/Wind Harmer
5.22
972181SS23-001
Solar/Wind Harmer
3.262
274752CRETE EC ;2U
Adder
2.688
274753CRETE EC ;3U
Adder
2.688
964401AG1-302 GEN
Solar/Wind Harmer
4.971
274724RIVER EC ;11
Adder
9.665
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274811UNIV PK N;7U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0.38
274803UNIV PARK;6U
Adder
3.135
274826FISK ;BP
Adder
5.877
972038AH1-567 GEN2
Adder
0.196
274887GEN-1.85
Solar/Wind Harmer
2.851
276772AC2-154 GEN
Solar/Wind Harmer
1.494
276843GEN-1.7
Solar/Wind Harmer
0.307
276806AD2-047 C O1
Solar/Wind Harmer
5.725
274772LINCOLN ;3U
Adder
3.316
972259AH1-714 GEN
Adder
10.137
274676JOLIET 29;8U
Adder
15.708
939351AE1-166 GEN
Solar/Wind Harmer
3.145
274729ELWOOD EC;1P
Adder
8.712
274730ELWOOD EC;6P
Adder
8.713
274734ELWOOD EC;8P
Adder
8.713
274736ELWOOD EC;9P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
14.838
943121AE2-341 GEN
Solar/Wind Harmer
7.862
943591AF1-030 GEN
Solar/Wind Harmer
5.242
274862TOP CROP ;2U
Solar/Wind Harmer
2.65
274682WAUKEGAN ;7U
Adder
9.362
276868AE1-113 GEN
Solar/Wind Harmer
5.232
274879MINONK ;1U
Solar/Wind Harmer
3.488
24690905MDL-1G C
Solar/Wind Harmer
4.14
24190002OREGON_ST1
50/50
5.546
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.525
241996AE2-282_GEN
Solar/Wind Harmer
2.231
241808AF1-120 C
Solar/Wind Harmer
1.244
944231AF1-091 GEN
Solar/Wind Harmer
13.075
247522W1-056 GEN
Solar/Wind Harmer
1.61
961051AF2-396 GEN
Solar/Wind Harmer
10.674
961051AF2-396 GEN
Solar/Wind Harmer
4.965
246937BC-WTG2
Solar/Wind Harmer
2.602
247607V1-011 GEN
Solar/Wind Harmer
2.611
942801AE2-298 GEN
Solar/Wind Harmer
0.991
247620Y3-023
Adder
0.296
270246TR4_N_V150
Solar/Wind Harmer
0.529
270247TR4_N_V136
Solar/Wind Harmer
0.529
270462AD2-086
Solar/Wind Harmer
4.113
965681AG1-436 GEN
Solar/Wind Harmer
7.383
965791AG1-447 GEN
Solar/Wind Harmer
3.777
970349AG2-230 GEN
Solar/Wind Harmer
8.81
270535AF1-215 GEN1
Solar/Wind Harmer
2.529
270536AF1-215 GEN2
Solar/Wind Harmer
2.529
274805UNIV PK N;1U
Adder
2.728
274808UNIV PK N;4U
Adder
2.71
274888KELLY CRK;1U
Solar/Wind Harmer
3.158
276776AD2-060 GEN
Solar/Wind Harmer
0.224
958011AF2-095 GEN
Solar/Wind Harmer
7.707
970941AG2-585 GEN
Solar/Wind Harmer
2.944
274770LINCOLN ;1U
Adder
3.316
274771LINCOLN ;2U
Adder
3.316
276897AD1-100 C
Solar/Wind Harmer
24.637
276893AG1-478 C
Solar/Wind Harmer
0.232
274674JOLIET 9 ;6U
Adder
8.16
958481AF2-142 GEN
Solar/Wind Harmer
7.861
945421AF1-207 GEN
Solar/Wind Harmer
7.333
957841AF2-078 GEN
Solar/Wind Harmer
3.157
942221AE2-234 GEN
Solar/Wind Harmer
1.826
274696ROCKY RD ;4P
Adder
5.935
274695ROCKY RD ;2P
Adder
5.798
274693ROCKY RD ;1P
Adder
5.741
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.968
274683WAUKEGAN ;8U
Adder
9.245
958491AF2-143 GEN
Solar/Wind Harmer
7.794
276901AD2-066 C O1
Solar/Wind Harmer
1.817
962691AG1-118 GEN
Solar/Wind Harmer
15.536
960751AF2-366 GEN
Solar/Wind Harmer
1.483
270180AB1-006 GEN1
Solar/Wind Harmer
3.709
972235AH1-702 GEN1
Adder
1.284
972236AH1-702 GEN2
Adder
1.116
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
247621Y3-024
Adder
0.115
25326509SID D
Adder
0.616
203835AF1-098 GEN
Solar/Wind Helper
1.351
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.135
254304AE2-114 C
Solar/Wind Helper
0.114
254305AE2-115 C
Solar/Wind Helper
0.114
962101AG1-054 GEN
Solar/Wind Helper
0.331
203804AE2-113_GEN
Solar/Wind Helper
0.87
940863AE2-074 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Helper
0.105
24697605MDL-3G C
Solar/Wind Harmer
0.675
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
4.638
24728705AND G3
Adder
3.474
24728505AND G1
Adder
1.661
962511AG1-100 GEN
Solar/Wind Helper
0.35
23888502TROY G1
50/50
1.525
23888602TROY G2
50/50
1.525
945411AF1-206 GEN
Solar/Wind Harmer
8.355
945641AF1-229 GEN
Solar/Wind Harmer
3.829
270361_3
Solar/Wind Harmer
8.252
270575GUS2 35KV
Solar/Wind Harmer
9.722
270499AE1-146 GEN
Solar/Wind Harmer
2.318
971549AH1-272 GEN
Solar/Wind Harmer
15.383
270404AC1-167 GEN
Solar/Wind Harmer
0.777
944161AF1-084 GEN
Solar/Wind Harmer
1.52
957201AF2-014 GEN
Solar/Wind Harmer
3.017
270435AC2-044 GEN
Solar/Wind Harmer
1.33
270007AE1-245 C
Solar/Wind Harmer
3.567
970031AG2-029 GEN
Solar/Wind Harmer
15.796
971771AH1-392 GEN
Solar/Wind Harmer
5.656
965041AG1-368 GEN
Solar/Wind Harmer
6.267
247521TR3_G114
Solar/Wind Harmer
2.092
270191TR4_S_V150
Solar/Wind Harmer
1.866
965051AG1-369 GEN
Solar/Wind Harmer
3.108
966831AG1-554 GEN
Solar/Wind Harmer
0.741
270526AF1-158 GEN
Solar/Wind Harmer
2.796
959331AF2-224 GEN
Solar/Wind Harmer
6.094
270302AB2-170 GEN
Solar/Wind Harmer
4.953
960681AF2-359 GEN
Solar/Wind Harmer
2.232
963791AG1-232 GEN
Solar/Wind Harmer
7.621
971567AH1-282 GEN
Solar/Wind Harmer
2.809
270223U2-072_GEN1
Solar/Wind Harmer
1.088
270224U2-072_GEN2
Solar/Wind Harmer
1.088
270227U2-072_GEN3
Solar/Wind Harmer
1.088
270228U2-072_GEN4
Solar/Wind Harmer
1.088
270231U2-072_GEN5
Solar/Wind Harmer
1.088
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
270071AF1-092 GEN
Solar/Wind Harmer
8.149
958391AF2-133 GEN
Solar/Wind Harmer
4.926
959141AF2-205 GEN
Solar/Wind Harmer
3.262
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
274800UNIV PARK;3U
Adder
3.125
274801UNIV PARK;4U
Adder
3.125
960591AF2-350 GEN
Solar/Wind Harmer
5.352
274775LINCOLN ;6U
Adder
3.316
274776LINCOLN ;7U
Adder
3.316
274777LINCOLN ;8U
Adder
3.316
972228AH1-698 GEN2
Adder
1.977
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.866
274687WILL CNTY;4U
Adder
14.866
274675JOLIET 29;7U
Adder
16.29
274675JOLIET 29;7U
Adder
15.708
276893AG1-478 C
Solar/Wind Harmer
0.292
274728ELWOOD EC;5P
Adder
8.713
274731ELWOOD EC;2P
Adder
8.712
274733ELWOOD EC;3P
Adder
8.712
274735ELWOOD EC;4P
Adder
8.712
970833AG2-524 GEN
Solar/Wind Harmer
4.605
970833AG2-524 GEN
Solar/Wind Harmer
2.142
274744AC1-111 GEN8
Adder
2.931
274746AC1-111 G10
Adder
2.931
970073AG2-061 GEN
Solar/Wind Harmer
1.208
946581AF1-322 GEN
Solar/Wind Harmer
5.277
274823ROCKFORD ;21
Adder
9.94
24729505KEY G4
Adder
3.292
972267AH1-718 GEN
Adder
2.087
241886AC2-103 GEN2
Solar/Wind Helper
6.847
241985AE1-237 GEN
Solar/Wind Helper
0.134
241982AE2-343 S C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
20334926Z1-069 C
Solar/Wind Helper
0.646
24691005MDL-2G C
Solar/Wind Harmer
0.677
24189902OREGON_CT2
50/50
4.122
23856402BAYSG1
50/50
1.575
23888702TROY G3
50/50
1.525
972253AH1-711 GEN
50/50
46.615
23920202STRYCT
50/50
1.928
241858AF1-205_GEN
Solar/Wind Harmer
5.419
241840AF1-064_GEN
Solar/Wind Harmer
1.364
23906502RICHG2&3
Adder
1.343
960841AF2-375 GEN
Solar/Wind Harmer
3.674
270297AD1-101 GEN
Solar/Wind Harmer
1.503
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.41
270449AD2-020 GEN
Solar/Wind Harmer
1.901
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
2.602
270489AE1-102 GEN1
Solar/Wind Harmer
0.865
945111AF1-176 GEN
Solar/Wind Harmer
11.825
957891AF2-083 GEN
Solar/Wind Harmer
9.907
965421AG1-410 GEN
Solar/Wind Harmer
19.797
24639705ELKHART HY
Adder
0.098
270216AD2-079_GEN
Solar/Wind Harmer
0.385
965011AG1-365 GEN
Solar/Wind Harmer
6.094
270317AD1-130_GEN
Solar/Wind Harmer
1.893
270485AE1-090_GEN
Solar/Wind Harmer
0.358
970373AG2-245 GEN
Solar/Wind Harmer
11.901
270055AF2-134 C O1
Solar/Wind Harmer
1.686
270391AF1-285 GEN3
Solar/Wind Harmer
0.666
270578AF1-285 GEN2
Solar/Wind Harmer
0.666
274751CRETE EC ;1U
Adder
2.688
274754CRETE EC ;4U
Adder
2.688
958381AF2-132 GEN
Solar/Wind Harmer
4.971
964861AG1-349 GEN
Solar/Wind Harmer
4.3
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.781
274812UNIV PK N;8U
Adder
2.722
274802UNIV PARK;5U
Adder
3.135
972207SS24-0001
Solar/Wind Harmer
11.791
274773LINCOLN ;4U
Adder
3.316
274774LINCOLN ;5U
Adder
3.316
940581AE2-045 GEN
Solar/Wind Harmer
5.455
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.29
941551AE2-152 GEN
Solar/Wind Harmer
2.405
274732ELWOOD EC;7P
Adder
8.713
274674JOLIET 9 ;6U
Adder
8.16
274871GR RIDGE ;2U
Solar/Wind Harmer
4.053
274847GR RIDGE ;BU
Solar/Wind Harmer
2.665
274745AC1-111 GEN9
Adder
2.931
276694AA1-018 GEN2
Solar/Wind Harmer
3.307
276691AA1-018 GEN1
Solar/Wind Harmer
0.395
274861TOP CROP ;1U
Solar/Wind Harmer
3.174
274682WAUKEGAN ;7U
Adder
9.362
274828WAUKEGAN ;BP
Adder
5.749
276805AD2-038 GEN
Solar/Wind Harmer
2.665
939401AE1-172 GEN
Solar/Wind Harmer
7.217
276882AE2-255 GEN
Solar/Wind Harmer
1.744
962781AG1-127 GEN
Solar/Wind Harmer
4.917
274872LEEDK;1U
Solar/Wind Harmer
4.238
274822ROCKFORD ;11
Adder
10.012
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24728605AND G2
Adder
1.661
241885AC2-103 GEN1
Solar/Wind Helper
6.847
241807AE2-176_GEN
Solar/Wind Helper
1.645
203947AF1-006 C
Solar/Wind Helper
0.391
961971AG1-040 GEN
Solar/Wind Helper
0.342
203830AF1-094 GEN
Solar/Wind Helper
0.331
203979AG1-198 GEN
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
990142J1224
External Queue
14.793254852294922
990527J1329
External Queue
2.0237011909484863
991182J1586 G
External Queue
28.12165069580078
991177J1571 G
External Queue
15.794994354248047
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.401
TVALTFEXP_TVA->PJM
CLTF
2.775
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.945
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.534

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.4 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:1908.5
MW Contribution:
11.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.775
958321AF2-126 GEN
Solar/Wind Harmer
1.137
23906402RICHG1
Adder
1.346
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.167
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
270505AE1-170 C O1
Solar/Wind Harmer
4.855
945111AF1-176 GEN
Solar/Wind Harmer
3.748
270588AE1-091_GEN
Solar/Wind Harmer
3.596
24695305TIMB G C
Solar/Wind Harmer
0.378
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.417
971347AH1-153 GEN
Solar/Wind Harmer
2.049
270043AE2-236 GEN
Solar/Wind Harmer
2.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
9.665
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274811UNIV PK N;7U
Adder
2.722
274803UNIV PARK;6U
Adder
3.135
274826FISK ;BP
Adder
5.877
972038AH1-567 GEN2
Adder
0.196
274887GEN-1.85
Solar/Wind Harmer
0.097
276843GEN-1.7
Solar/Wind Harmer
0.121
276806AD2-047 C O1
Solar/Wind Harmer
2.116
274772LINCOLN ;3U
Adder
4.514
972259AH1-714 GEN
Adder
10.137
274676JOLIET 29;8U
Adder
15.708
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
8.712
274730ELWOOD EC;6P
Adder
8.713
274734ELWOOD EC;8P
Adder
8.713
274736ELWOOD EC;9P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.078
943121AE2-341 GEN
Solar/Wind Harmer
6.131
943591AF1-030 GEN
Solar/Wind Harmer
4.077
274862TOP CROP ;2U
Solar/Wind Harmer
0.494
274682WAUKEGAN ;7U
Adder
9.362
276868AE1-113 GEN
Solar/Wind Harmer
0.722
274879MINONK ;1U
Solar/Wind Harmer
0.151
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.598
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
944531AF1-118 GEN
Solar/Wind Harmer
16.015
959091AF2-200 GEN
Solar/Wind Harmer
7.132
970571AG2-364 GEN
Solar/Wind Harmer
7.106
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
4.638
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.116
965091AG1-374 GEN
Solar/Wind Harmer
10.297
959611AF2-252 GEN
Solar/Wind Harmer
1.144
965931AG1-462 GEN
Solar/Wind Harmer
8.718
971087AG2-675 GEN
Solar/Wind Harmer
1.823
247642Z2-115 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.032
970289AG2-191 GEN
Solar/Wind Harmer
0.367
971993AH1-541 GEN
Solar/Wind Harmer
1.533
946031AF1-268 GEN
Solar/Wind Harmer
3.094
970825AG2-519 GEN
Solar/Wind Harmer
2.443
270004AE1-209 GEN
Solar/Wind Harmer
0.699
957381AF2-032 GEN
Solar/Wind Harmer
0.73
942481AE2-261 GEN
Solar/Wind Harmer
9.607
970193AG2-126 GEN
Solar/Wind Harmer
4.752
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
3.474
24728505AND G1
Adder
1.661
962511AG1-100 GEN
Solar/Wind Helper
0.35
24189902OREGON_CT2
50/50
4.122
23856402BAYSG1
50/50
1.575
23888702TROY G3
50/50
1.525
972253AH1-711 GEN
50/50
46.615
23920202STRYCT
50/50
1.928
241858AF1-205_GEN
Solar/Wind Harmer
3.781
23906502RICHG2&3
Adder
1.343
960841AF2-375 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
0.187
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.25
957891AF2-083 GEN
Solar/Wind Harmer
7.68
965421AG1-410 GEN
Solar/Wind Harmer
13.812
24639705ELKHART HY
Adder
0.098
965011AG1-365 GEN
Solar/Wind Harmer
4.252
270317AD1-130_GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.303
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.532
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.781
274812UNIV PK N;8U
Adder
2.722
274802UNIV PARK;5U
Adder
3.135
274773LINCOLN ;4U
Adder
4.514
274774LINCOLN ;5U
Adder
4.514
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.29
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.713
274674JOLIET 9 ;6U
Adder
8.16
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.594
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.362
274828WAUKEGAN ;BP
Adder
5.749
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.702
276882AE2-255 GEN
Solar/Wind Harmer
0.421
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.886
270024AE2-089 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
10.699
959081AF2-199 GEN
Solar/Wind Harmer
3.566
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.012
970569AG2-363 GEN
Solar/Wind Harmer
10.659
970819AG2-516 GEN
Solar/Wind Harmer
4.255
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276708O09 GEN2
Solar/Wind Harmer
0.123
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.858
965651AG1-433 GEN
Solar/Wind Harmer
1.011
958861AF2-177 GEN
Solar/Wind Harmer
1.481
963741AG1-226 GEN
Solar/Wind Harmer
7.998
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
3.712
270032AE2-172
Solar/Wind Harmer
2.209
276621W2-048 GEN
Solar/Wind Harmer
0.164
276903AD2-071 C
Solar/Wind Harmer
3.645
970825AG2-519 GEN
Solar/Wind Harmer
1.151
270005AE1-210 C O1
Solar/Wind Harmer
0.699
965911AG1-460 GEN
Solar/Wind Harmer
0.643
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.285
24728605AND G2
Adder
1.661
241885AC2-103 GEN1
Solar/Wind Helper
6.847
241807AE2-176_GEN
Solar/Wind Helper
1.645
203947AF1-006 C
Solar/Wind Helper
0.391
961971AG1-040 GEN
Solar/Wind Helper
0.342
203830AF1-094 GEN
Solar/Wind Helper
0.331
203979AG1-198 GEN
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
23888502TROY G1
50/50
1.525
23888602TROY G2
50/50
1.525
945411AF1-206 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.522
270575GUS2 35KV
Solar/Wind Harmer
4.522
270499AE1-146 GEN
Solar/Wind Harmer
0.021
971549AH1-272 GEN
Solar/Wind Harmer
11.979
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.588
270007AE1-245 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.388
971771AH1-392 GEN
Solar/Wind Harmer
4.384
965041AG1-368 GEN
Solar/Wind Harmer
4.372
247521TR3_G114
Solar/Wind Harmer
0.157
965051AG1-369 GEN
Solar/Wind Harmer
2.168
270526AF1-158 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.976
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.581
960681AF2-359 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.317
971567AH1-282 GEN
Solar/Wind Harmer
3.005
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
270071AF1-092 GEN
Solar/Wind Harmer
7.265
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
274800UNIV PARK;3U
Adder
3.125
274801UNIV PARK;4U
Adder
3.125
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.514
274776LINCOLN ;7U
Adder
4.514
274777LINCOLN ;8U
Adder
4.514
971611AH1-305 GEN
Solar/Wind Harmer
2.221
24190002OREGON_ST1
50/50
5.546
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.525
970621AG2-405 GEN
Solar/Wind Harmer
0.945
944231AF1-091 GEN
Solar/Wind Harmer
11.69
970623AG2-406 GEN
Solar/Wind Harmer
0.886
961051AF2-396 GEN
Solar/Wind Harmer
9.383
961051AF2-396 GEN
Solar/Wind Harmer
6.256
246937BC-WTG2
Solar/Wind Harmer
0.187
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.296
270246TR4_N_V150
Solar/Wind Harmer
0.028
270247TR4_N_V136
Solar/Wind Harmer
0.028
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.151
965791AG1-447 GEN
Solar/Wind Harmer
3.777
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.728
274808UNIV PK N;4U
Adder
2.71
274888KELLY CRK;1U
Solar/Wind Harmer
0.218
276776AD2-060 GEN
Solar/Wind Harmer
0.398
958011AF2-095 GEN
Solar/Wind Harmer
5.377
970941AG2-585 GEN
Solar/Wind Harmer
2.054
274770LINCOLN ;1U
Adder
4.514
274771LINCOLN ;2U
Adder
4.514
276897AD1-100 C
Solar/Wind Harmer
9.25
276893AG1-478 C
Solar/Wind Harmer
0.247
274674JOLIET 9 ;6U
Adder
8.16
958481AF2-142 GEN
Solar/Wind Harmer
5.484
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
1.462
274696ROCKY RD ;4P
Adder
5.935
274695ROCKY RD ;2P
Adder
5.798
274693ROCKY RD ;1P
Adder
5.741
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.968
274683WAUKEGAN ;8U
Adder
9.245
958491AF2-143 GEN
Solar/Wind Harmer
5.438
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
10.839
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
7.132
971343AH1-151 GEN
Solar/Wind Harmer
7.132
972235AH1-702 GEN1
Adder
1.284
972236AH1-702 GEN2
Adder
1.116
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.397
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.564
942111AE2-223 GEN
Solar/Wind Harmer
1.128
944541AF1-119 GEN
Solar/Wind Harmer
0.23
960971AF2-388 GEN
Solar/Wind Harmer
2.023
960611AF2-352 GEN
Solar/Wind Harmer
1.144
970241AG2-163 GEN
Solar/Wind Harmer
1.971
270031AE2-169
Solar/Wind Harmer
1.849
270599AE1-208 GEN
Solar/Wind Harmer
3.081
270201AC2-176 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.434
970291AG2-192 GEN
Solar/Wind Harmer
0.2
964611AG1-324 GEN
Solar/Wind Harmer
0.25
247621Y3-024
Adder
0.115
971613AH1-306 GEN
Solar/Wind Harmer
1.591
276615X2-022 GEN
Solar/Wind Harmer
0.034
276838X2-022 GEN2
Solar/Wind Harmer
0.185
25326509SID D
Adder
0.616
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
1.397
276916AD2-100_GEN
Solar/Wind Harmer
6.713
276911AD2-131_GEN
Solar/Wind Harmer
0.442
970883AG2-550 GEN
Solar/Wind Harmer
3.196
970885AG2-551 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
3.366
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
203835AF1-098 GEN
Solar/Wind Helper
1.351
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.135
254304AE2-114 C
Solar/Wind Helper
0.114
254305AE2-115 C
Solar/Wind Helper
0.114
962101AG1-054 GEN
Solar/Wind Helper
0.331
203804AE2-113_GEN
Solar/Wind Helper
0.87
940863AE2-074 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Helper
0.105
972228AH1-698 GEN2
Adder
1.977
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.866
274687WILL CNTY;4U
Adder
14.866
274675JOLIET 29;7U
Adder
16.29
274675JOLIET 29;7U
Adder
15.708
274728ELWOOD EC;5P
Adder
8.713
274731ELWOOD EC;2P
Adder
8.712
274733ELWOOD EC;3P
Adder
8.712
274735ELWOOD EC;4P
Adder
8.712
970833AG2-524 GEN
Solar/Wind Harmer
4.048
970833AG2-524 GEN
Solar/Wind Harmer
2.699
274744AC1-111 GEN8
Adder
2.931
274746AC1-111 G10
Adder
2.931
970073AG2-061 GEN
Solar/Wind Harmer
1.208
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
5.374
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.396
276861AD2-134 GEN
Solar/Wind Harmer
0.064
276863AD2-134 GEN
Solar/Wind Harmer
0.064
971171AH1-044 GEN
Solar/Wind Harmer
7.132
274823ROCKFORD ;21
Adder
9.94
926823AC1-168 GEN
Solar/Wind Harmer
0.603
970169AG2-114 GEN
Solar/Wind Harmer
3.545
274856ECOGROVE ;U1
Solar/Wind Harmer
0.083
24729505KEY G4
Adder
3.292
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
2.087
276741O09 GEN1
Solar/Wind Harmer
0.123
274877BISHOP HL;1U
Solar/Wind Harmer
0.116
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.643
963841AG1-237 GEN
Solar/Wind Harmer
1.491
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.921
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.549
970289AG2-191 GEN
Solar/Wind Harmer
0.635
964611AG1-324 GEN
Solar/Wind Harmer
1.3
276668AB2-070 GEN1
Solar/Wind Harmer
0.13
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.13
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
1.251
247536S-71 GEN
Solar/Wind Harmer
0.131
270543AE2-219 C
Solar/Wind Harmer
2.237
944221AF1-090 GEN
Solar/Wind Harmer
1.843
971029AG2-637 GEN
Solar/Wind Harmer
4.677
241886AC2-103 GEN2
Solar/Wind Helper
6.847
241985AE1-237 GEN
Solar/Wind Helper
0.134
241982AE2-343 S C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
20334926Z1-069 C
Solar/Wind Helper
0.646
990142J1224
External Queue
14.793254852294922
990527J1329
External Queue
2.0237011909484863
991182J1586 G
External Queue
28.12165069580078
991177J1571 G
External Queue
15.794994354248047
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.401
TVALTFEXP_TVA->PJM
CLTF
2.775
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.945
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.534

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-005_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-005_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.04 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2460.31
MW Contribution:
13.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.123
241832AE2-181_GEN
Solar/Wind Harmer
1.977
958321AF2-126 GEN
Solar/Wind Harmer
1.453
23906402RICHG1
Adder
1.328
23906502RICHG2&3
Adder
1.324
270541AE2-072 C
Solar/Wind Harmer
4.218
270044AE2-322 C
Solar/Wind Harmer
0.857
246938BC-WTG3
Solar/Wind Harmer
2.348
270491AE1-102 GEN2
Solar/Wind Harmer
0.767
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270588AE1-091_GEN
Solar/Wind Harmer
6.434
945111AF1-176 GEN
Solar/Wind Harmer
3.247
270505AE1-170 C O1
Solar/Wind Harmer
8.609
24695305TIMB G C
Solar/Wind Harmer
1.894
270063AE2-323 C
Solar/Wind Harmer
1.211
247643Z2-116 C
Solar/Wind Harmer
0.038
965021AG1-366 GEN
Solar/Wind Harmer
1.242
24441505OLIV SLR
Solar/Wind Harmer
0.071
270043AE2-236 GEN
Solar/Wind Harmer
2.785
971347AH1-153 GEN
Solar/Wind Harmer
2.53
942871AE2-306 GEN
Solar/Wind Harmer
0.44
270391AF1-285 GEN3
Solar/Wind Harmer
0.226
972231SS25-0005
Solar/Wind Harmer
4.48
972181SS23-001
Solar/Wind Harmer
2.8
274752CRETE EC ;2U
Adder
2.307
274753CRETE EC ;3U
Adder
2.307
964401AG1-302 GEN
Solar/Wind Harmer
4.266
274724RIVER EC ;11
Adder
8.291
274814UNIV PK N;0U
Adder
2.355
274807UNIV PK N;3U
Adder
2.349
274811UNIV PK N;7U
Adder
2.334
276164X3-005 C
Solar/Wind Harmer
0.326
274803UNIV PARK;6U
Adder
2.687
274826FISK ;BP
Adder
5.036
972038AH1-567 GEN2
Adder
0.168
274887GEN-1.85
Solar/Wind Harmer
2.443
23888502TROY G1
50/50
1.899
23888602TROY G2
50/50
1.899
241886AC2-103 GEN2
Solar/Wind Harmer
15.654
945411AF1-206 GEN
Solar/Wind Harmer
8.156
945641AF1-229 GEN
Solar/Wind Harmer
3.506
270361_3
Solar/Wind Harmer
7.383
270575GUS2 35KV
Solar/Wind Harmer
8.698
270499AE1-146 GEN
Solar/Wind Harmer
2.08
971549AH1-272 GEN
Solar/Wind Harmer
13.415
270404AC1-167 GEN
Solar/Wind Harmer
0.706
944161AF1-084 GEN
Solar/Wind Harmer
1.317
957201AF2-014 GEN
Solar/Wind Harmer
2.676
270435AC2-044 GEN
Solar/Wind Harmer
1.18
270007AE1-245 C
Solar/Wind Harmer
3.178
965041AG1-368 GEN
Solar/Wind Harmer
5.531
970031AG2-029 GEN
Solar/Wind Harmer
13.751
247521TR3_G114
Solar/Wind Harmer
1.846
270191TR4_S_V150
Solar/Wind Harmer
1.647
965051AG1-369 GEN
Solar/Wind Harmer
2.742
966831AG1-554 GEN
Solar/Wind Harmer
0.652
971771AH1-392 GEN
Solar/Wind Harmer
4.89
959331AF2-224 GEN
Solar/Wind Harmer
5.34
270526AF1-158 GEN
Solar/Wind Harmer
2.414
270302AB2-170 GEN
Solar/Wind Harmer
4.384
960681AF2-359 GEN
Solar/Wind Harmer
1.922
971567AH1-282 GEN
Solar/Wind Harmer
2.477
963791AG1-232 GEN
Solar/Wind Harmer
6.647
270223U2-072_GEN1
Solar/Wind Harmer
0.958
270224U2-072_GEN2
Solar/Wind Harmer
0.958
270227U2-072_GEN3
Solar/Wind Harmer
0.958
270228U2-072_GEN4
Solar/Wind Harmer
0.958
270231U2-072_GEN5
Solar/Wind Harmer
0.958
270578AF1-285 GEN2
Solar/Wind Harmer
0.226
270071AF1-092 GEN
Solar/Wind Harmer
7.048
958391AF2-133 GEN
Solar/Wind Harmer
4.225
959141AF2-205 GEN
Solar/Wind Harmer
2.797
972037AH1-567 GEN1
Adder
0.084
274827FISK ;RP
Adder
3.569
274800UNIV PARK;3U
Adder
2.678
274801UNIV PARK;4U
Adder
2.678
960591AF2-350 GEN
Solar/Wind Harmer
4.585
274775LINCOLN ;6U
Adder
2.841
274776LINCOLN ;7U
Adder
2.841
274777LINCOLN ;8U
Adder
2.841
972228AH1-698 GEN2
Adder
1.693
972227AH1-698 GEN1
Adder
1.192
274687WILL CNTY;4U
Adder
12.731
274687WILL CNTY;4U
Adder
12.731
274675JOLIET 29;7U
Adder
13.949
274675JOLIET 29;7U
Adder
13.451
276893AG1-478 C
Solar/Wind Harmer
0.25
274728ELWOOD EC;5P
Adder
7.46
274731ELWOOD EC;2P
Adder
7.46
274733ELWOOD EC;3P
Adder
7.46
274735ELWOOD EC;4P
Adder
7.46
970833AG2-524 GEN
Solar/Wind Harmer
3.942
970833AG2-524 GEN
Solar/Wind Harmer
1.833
274744AC1-111 GEN8
Adder
2.508
274746AC1-111 G10
Adder
2.508
970073AG2-061 GEN
Solar/Wind Harmer
1.033
24729505KEY G4
Adder
2.832
274823ROCKFORD ;21
Adder
8.487
241985AE1-237 GEN
Solar/Wind Helper
0.133
241982AE2-343 S C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.25
241997AF1-093 GEN
Solar/Wind Helper
0.132
24189902OREGON_CT2
50/50
2.84
23888702TROY G3
50/50
1.899
972253AH1-711 GEN
50/50
58.052
23856402BAYSG1
50/50
1.205
23920202STRYCT
50/50
1.925
241885AC2-103 GEN1
Solar/Wind Harmer
15.654
241858AF1-205_GEN
Solar/Wind Harmer
5.547
241840AF1-064_GEN
Solar/Wind Harmer
1.352
23906502RICHG2&3
Adder
1.324
960841AF2-375 GEN
Solar/Wind Harmer
3.292
23867002DVBSG1
50/50
15.336
24190002OREGON_ST1
50/50
3.822
24189802OREGON_CT1
50/50
2.901
23888802TROY G4
50/50
1.899
241996AE2-282_GEN
Solar/Wind Harmer
2.178
241808AF1-120 C
Solar/Wind Harmer
1.214
944231AF1-091 GEN
Solar/Wind Harmer
11.933
247522W1-056 GEN
Solar/Wind Harmer
1.426
246937BC-WTG2
Solar/Wind Harmer
2.308
247607V1-011 GEN
Solar/Wind Harmer
2.326
942801AE2-298 GEN
Solar/Wind Harmer
0.885
961051AF2-396 GEN
Solar/Wind Harmer
9.248
961051AF2-396 GEN
Solar/Wind Harmer
4.302
247620Y3-023
Adder
0.257
270246TR4_N_V150
Solar/Wind Harmer
0.467
270247TR4_N_V136
Solar/Wind Harmer
0.467
270462AD2-086
Solar/Wind Harmer
3.641
965681AG1-436 GEN
Solar/Wind Harmer
6.359
965791AG1-447 GEN
Solar/Wind Harmer
3.254
970349AG2-230 GEN
Solar/Wind Harmer
7.591
270535AF1-215 GEN1
Solar/Wind Harmer
2.172
270536AF1-215 GEN2
Solar/Wind Harmer
2.172
274805UNIV PK N;1U
Adder
2.339
274808UNIV PK N;4U
Adder
2.324
274888KELLY CRK;1U
Solar/Wind Harmer
2.706
276776AD2-060 GEN
Solar/Wind Harmer
0.192
958011AF2-095 GEN
Solar/Wind Harmer
6.603
970941AG2-585 GEN
Solar/Wind Harmer
2.522
274770LINCOLN ;1U
Adder
2.841
274771LINCOLN ;2U
Adder
2.841
276897AD1-100 C
Solar/Wind Harmer
21.096
276893AG1-478 C
Solar/Wind Harmer
0.199
274674JOLIET 9 ;6U
Adder
6.987
942221AE2-234 GEN
Solar/Wind Harmer
1.578
958481AF2-142 GEN
Solar/Wind Harmer
6.725
945421AF1-207 GEN
Solar/Wind Harmer
6.277
957841AF2-078 GEN
Solar/Wind Harmer
2.702
274696ROCKY RD ;4P
Adder
5.075
274695ROCKY RD ;2P
Adder
4.958
274693ROCKY RD ;1P
Adder
4.91
274697ROCKY RD ;3P
Adder
1.347
274683WAUKEGAN ;8U
Adder
9.379
274683WAUKEGAN ;8U
Adder
7.906
958491AF2-143 GEN
Solar/Wind Harmer
6.664
276901AD2-066 C O1
Solar/Wind Harmer
1.553
962691AG1-118 GEN
Solar/Wind Harmer
13.281
960751AF2-366 GEN
Solar/Wind Harmer
1.268
972235AH1-702 GEN1
Adder
1.096
972236AH1-702 GEN2
Adder
0.953
274764LEE CO EC;5U
Adder
4.013
274765LEE CO EC;6U
Adder
4.013
274762LEE CO EC;3U
Adder
4.004
274763LEE CO EC;4U
Adder
3.966
203835AF1-098 GEN
Solar/Wind Helper
1.327
241967AE2-285_GEN
Solar/Wind Helper
0.343
241801AE1-079 GEN
Solar/Wind Helper
0.134
254304AE2-114 C
Solar/Wind Helper
0.114
254305AE2-115 C
Solar/Wind Helper
0.114
962101AG1-054 GEN
Solar/Wind Helper
0.331
203804AE2-113_GEN
Solar/Wind Helper
0.875
276772AC2-154 GEN
Solar/Wind Harmer
1.28
276843GEN-1.7
Solar/Wind Harmer
0.263
276806AD2-047 C O1
Solar/Wind Harmer
4.905
274772LINCOLN ;3U
Adder
2.841
972259AH1-714 GEN
Adder
8.681
274676JOLIET 29;8U
Adder
13.451
939351AE1-166 GEN
Solar/Wind Harmer
2.693
274729ELWOOD EC;1P
Adder
7.46
274730ELWOOD EC;6P
Adder
7.46
274734ELWOOD EC;8P
Adder
7.46
274736ELWOOD EC;9P
Adder
7.46
970707AG2-453 GEN
Solar/Wind Harmer
12.705
943121AE2-341 GEN
Solar/Wind Harmer
6.727
943591AF1-030 GEN
Solar/Wind Harmer
4.484
274862TOP CROP ;2U
Solar/Wind Harmer
2.267
274682WAUKEGAN ;7U
Adder
8.006
276868AE1-113 GEN
Solar/Wind Harmer
4.472
274879MINONK ;1U
Solar/Wind Harmer
2.981
24690905MDL-1G C
Solar/Wind Harmer
3.541
274760LEE CO EC;1U
Adder
4.004
274767LEE CO EC;8U
Adder
3.957
962511AG1-100 GEN
Solar/Wind Helper
0.343
270297AD1-101 GEN
Solar/Wind Harmer
1.367
270258AD1-119 GEN
Solar/Wind Harmer
1.275
24441205WTRV SLR C
Solar/Wind Harmer
0.083
246936BC-WTG1
Solar/Wind Harmer
2.308
270489AE1-102 GEN1
Solar/Wind Harmer
0.767
270449AD2-020 GEN
Solar/Wind Harmer
1.647
943021AE2-325 GEN
Solar/Wind Harmer
2.14
965421AG1-410 GEN
Solar/Wind Harmer
17.539
945111AF1-176 GEN
Solar/Wind Harmer
10.246
957891AF2-083 GEN
Solar/Wind Harmer
8.579
24639705ELKHART HY
Adder
0.085
270216AD2-079_GEN
Solar/Wind Harmer
0.334
965011AG1-365 GEN
Solar/Wind Harmer
5.34
270317AD1-130_GEN
Solar/Wind Harmer
1.676
270485AE1-090_GEN
Solar/Wind Harmer
0.317
970373AG2-245 GEN
Solar/Wind Harmer
10.23
270391AF1-285 GEN3
Solar/Wind Harmer
0.587
270578AF1-285 GEN2
Solar/Wind Harmer
0.587
270055AF2-134 C O1
Solar/Wind Harmer
1.448
274751CRETE EC ;1U
Adder
2.307
274754CRETE EC ;4U
Adder
2.307
958381AF2-132 GEN
Solar/Wind Harmer
4.266
964861AG1-349 GEN
Solar/Wind Harmer
3.69
971917AH1-482 GEN
Solar/Wind Harmer
4.257
274723RIVER EC ;12
Adder
8.391
274812UNIV PK N;8U
Adder
2.334
274802UNIV PARK;5U
Adder
2.687
940581AE2-045 GEN
Solar/Wind Harmer
4.675
972207SS24-0001
Solar/Wind Harmer
10.102
274773LINCOLN ;4U
Adder
2.841
274774LINCOLN ;5U
Adder
2.841
971605AH1-302 GEN
Solar/Wind Harmer
3.997
274676JOLIET 29;8U
Adder
13.949
941551AE2-152 GEN
Solar/Wind Harmer
2.06
274732ELWOOD EC;7P
Adder
7.46
274674JOLIET 9 ;6U
Adder
6.987
274871GR RIDGE ;2U
Solar/Wind Harmer
3.469
274847GR RIDGE ;BU
Solar/Wind Harmer
2.281
274745AC1-111 GEN9
Adder
2.508
276694AA1-018 GEN2
Solar/Wind Harmer
2.829
276691AA1-018 GEN1
Solar/Wind Harmer
0.338
274861TOP CROP ;1U
Solar/Wind Harmer
2.716
274682WAUKEGAN ;7U
Adder
8.006
274828WAUKEGAN ;BP
Adder
4.916
276805AD2-038 GEN
Solar/Wind Harmer
2.278
270024AE2-089 GEN
Solar/Wind Harmer
2.077
939401AE1-172 GEN
Solar/Wind Harmer
6.17
276882AE2-255 GEN
Solar/Wind Harmer
1.491
962781AG1-127 GEN
Solar/Wind Harmer
4.203
274872LEEDK;1U
Solar/Wind Harmer
3.622
274822ROCKFORD ;11
Adder
8.549
274761LEE CO EC;2U
Adder
4.004
274766LEE CO EC;7U
Adder
3.957
241807AE2-176_GEN
Solar/Wind Helper
2.25
203947AF1-006 C
Solar/Wind Helper
0.383
961971AG1-040 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.326
203979AG1-198 GEN
Solar/Wind Helper
0.196
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
20334926Z1-069 C
Solar/Wind Helper
0.652
940863AE2-074 GEN
Solar/Wind Helper
0.227
946381AF1-302 GEN
Solar/Wind Helper
0.106
203954AE2-126 C
Solar/Wind Helper
0.221
270180AB1-006 GEN1
Solar/Wind Harmer
1.44
270181AB1-006 GEN2
Solar/Wind Harmer
0.143
990142J1224
External Queue
13.943214416503906
990527J1329
External Queue
1.907416582107544
991182J1586 G
External Queue
26.14141845703125
991177J1571 G
External Queue
15.850347518920898
LAGNLTFEXP_LAGN->PJM
CLTF
4.895
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.09
TVALTFEXP_TVA->PJM
CLTF
2.213
NYPJM->LTFIMP_NY
CLTF
2.051
LGEELTFEXP_LGEE->PJM
CLTF
1.985
WECLTFEXP_WEC->PJM
CLTF
1.661
AG2-052LTFEXP_AG2-052->PJM
LTF
0.107
AH1-155LTFEXP_AH1-155->PJM
LTF
0.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.862
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.77
MECLTFEXP_MEC->PJM
CLTF
6.457
SIGELTFEXP_SIGE->PJM
CLTF
0.166
CPLELTFEXP_CPLE->PJM
CLTF
0.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.25

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-006_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.41 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2410.66
MW Contribution:
13.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.132
241832AE2-181_GEN
Solar/Wind Harmer
1.985
958321AF2-126 GEN
Solar/Wind Harmer
1.46
23906402RICHG1
Adder
1.333
23906502RICHG2&3
Adder
1.33
270541AE2-072 C
Solar/Wind Harmer
4.241
270044AE2-322 C
Solar/Wind Harmer
0.863
246938BC-WTG3
Solar/Wind Harmer
2.366
270491AE1-102 GEN2
Solar/Wind Harmer
0.773
958091AF2-103 GEN
Solar/Wind Harmer
0.096
270588AE1-091_GEN
Solar/Wind Harmer
6.492
945111AF1-176 GEN
Solar/Wind Harmer
3.271
270505AE1-170 C O1
Solar/Wind Harmer
8.672
24695305TIMB G C
Solar/Wind Harmer
1.909
270063AE2-323 C
Solar/Wind Harmer
1.221
247643Z2-116 C
Solar/Wind Harmer
0.039
965021AG1-366 GEN
Solar/Wind Harmer
1.252
24441505OLIV SLR
Solar/Wind Harmer
0.071
270043AE2-236 GEN
Solar/Wind Harmer
2.809
971347AH1-153 GEN
Solar/Wind Harmer
2.551
942871AE2-306 GEN
Solar/Wind Harmer
0.444
270391AF1-285 GEN3
Solar/Wind Harmer
0.228
972231SS25-0005
Solar/Wind Harmer
4.519
972181SS23-001
Solar/Wind Harmer
2.824
274752CRETE EC ;2U
Adder
2.327
274753CRETE EC ;3U
Adder
2.327
964401AG1-302 GEN
Solar/Wind Harmer
4.303
274724RIVER EC ;11
Adder
8.364
274814UNIV PK N;0U
Adder
2.375
274807UNIV PK N;3U
Adder
2.37
274811UNIV PK N;7U
Adder
2.355
276164X3-005 C
Solar/Wind Harmer
0.329
274803UNIV PARK;6U
Adder
2.711
274826FISK ;BP
Adder
5.081
972038AH1-567 GEN2
Adder
0.169
274887GEN-1.85
Solar/Wind Harmer
2.465
276772AC2-154 GEN
Solar/Wind Harmer
1.291
276843GEN-1.7
Solar/Wind Harmer
0.265
276806AD2-047 C O1
Solar/Wind Harmer
4.949
274772LINCOLN ;3U
Adder
2.867
972259AH1-714 GEN
Adder
8.759
274676JOLIET 29;8U
Adder
13.572
939351AE1-166 GEN
Solar/Wind Harmer
2.718
274729ELWOOD EC;1P
Adder
7.527
274730ELWOOD EC;6P
Adder
7.527
274734ELWOOD EC;8P
Adder
7.527
274736ELWOOD EC;9P
Adder
7.527
970707AG2-453 GEN
Solar/Wind Harmer
12.82
943121AE2-341 GEN
Solar/Wind Harmer
6.788
943591AF1-030 GEN
Solar/Wind Harmer
4.525
274862TOP CROP ;2U
Solar/Wind Harmer
2.288
274682WAUKEGAN ;7U
Adder
8.08
276868AE1-113 GEN
Solar/Wind Harmer
4.513
274879MINONK ;1U
Solar/Wind Harmer
3.009
24690905MDL-1G C
Solar/Wind Harmer
3.574
274760LEE CO EC;1U
Adder
4.042
274767LEE CO EC;8U
Adder
3.994
962511AG1-100 GEN
Solar/Wind Helper
0.343
23888502TROY G1
50/50
1.904
23888602TROY G2
50/50
1.904
241886AC2-103 GEN2
Solar/Wind Harmer
15.673
945411AF1-206 GEN
Solar/Wind Harmer
8.186
945641AF1-229 GEN
Solar/Wind Harmer
3.528
270361_3
Solar/Wind Harmer
7.438
270575GUS2 35KV
Solar/Wind Harmer
8.763
270499AE1-146 GEN
Solar/Wind Harmer
2.096
971549AH1-272 GEN
Solar/Wind Harmer
13.493
270404AC1-167 GEN
Solar/Wind Harmer
0.711
944161AF1-084 GEN
Solar/Wind Harmer
1.326
957201AF2-014 GEN
Solar/Wind Harmer
2.696
270435AC2-044 GEN
Solar/Wind Harmer
1.189
270007AE1-245 C
Solar/Wind Harmer
3.202
965041AG1-368 GEN
Solar/Wind Harmer
5.575
970031AG2-029 GEN
Solar/Wind Harmer
13.857
247521TR3_G114
Solar/Wind Harmer
1.86
270191TR4_S_V150
Solar/Wind Harmer
1.66
965051AG1-369 GEN
Solar/Wind Harmer
2.764
966831AG1-554 GEN
Solar/Wind Harmer
0.659
971771AH1-392 GEN
Solar/Wind Harmer
4.927
959331AF2-224 GEN
Solar/Wind Harmer
5.383
270526AF1-158 GEN
Solar/Wind Harmer
2.433
270302AB2-170 GEN
Solar/Wind Harmer
4.422
960681AF2-359 GEN
Solar/Wind Harmer
1.938
971567AH1-282 GEN
Solar/Wind Harmer
2.509
963791AG1-232 GEN
Solar/Wind Harmer
6.704
270223U2-072_GEN1
Solar/Wind Harmer
0.967
270224U2-072_GEN2
Solar/Wind Harmer
0.967
270227U2-072_GEN3
Solar/Wind Harmer
0.967
270228U2-072_GEN4
Solar/Wind Harmer
0.967
270231U2-072_GEN5
Solar/Wind Harmer
0.967
270578AF1-285 GEN2
Solar/Wind Harmer
0.228
270071AF1-092 GEN
Solar/Wind Harmer
7.111
958391AF2-133 GEN
Solar/Wind Harmer
4.263
959141AF2-205 GEN
Solar/Wind Harmer
2.822
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.601
274800UNIV PARK;3U
Adder
2.701
274801UNIV PARK;4U
Adder
2.701
960591AF2-350 GEN
Solar/Wind Harmer
4.626
274775LINCOLN ;6U
Adder
2.867
274776LINCOLN ;7U
Adder
2.867
274777LINCOLN ;8U
Adder
2.867
972228AH1-698 GEN2
Adder
1.708
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.846
274687WILL CNTY;4U
Adder
12.846
274675JOLIET 29;7U
Adder
14.075
274675JOLIET 29;7U
Adder
13.572
276893AG1-478 C
Solar/Wind Harmer
0.252
274728ELWOOD EC;5P
Adder
7.527
274731ELWOOD EC;2P
Adder
7.527
274733ELWOOD EC;3P
Adder
7.527
274735ELWOOD EC;4P
Adder
7.527
970833AG2-524 GEN
Solar/Wind Harmer
3.977
970833AG2-524 GEN
Solar/Wind Harmer
1.85
274744AC1-111 GEN8
Adder
2.531
274746AC1-111 G10
Adder
2.531
970073AG2-061 GEN
Solar/Wind Harmer
1.043
24729505KEY G4
Adder
2.859
274823ROCKFORD ;21
Adder
8.567
972267AH1-718 GEN
Adder
1.797
241985AE1-237 GEN
Solar/Wind Helper
0.133
241982AE2-343 S C
Solar/Wind Helper
0.119
203846AF2-130 C
Solar/Wind Helper
0.249
241997AF1-093 GEN
Solar/Wind Helper
0.131
20334926Z1-069 C
Solar/Wind Helper
0.649
23867002DVBSG1
50/50
15.354
24190002OREGON_ST1
50/50
3.831
24189802OREGON_CT1
50/50
2.908
23888802TROY G4
50/50
1.904
241996AE2-282_GEN
Solar/Wind Harmer
2.186
241808AF1-120 C
Solar/Wind Harmer
1.219
944231AF1-091 GEN
Solar/Wind Harmer
12.013
247522W1-056 GEN
Solar/Wind Harmer
1.44
246937BC-WTG2
Solar/Wind Harmer
2.325
247607V1-011 GEN
Solar/Wind Harmer
2.344
942801AE2-298 GEN
Solar/Wind Harmer
0.892
961051AF2-396 GEN
Solar/Wind Harmer
9.315
961051AF2-396 GEN
Solar/Wind Harmer
4.333
247620Y3-023
Adder
0.259
270246TR4_N_V150
Solar/Wind Harmer
0.471
270247TR4_N_V136
Solar/Wind Harmer
0.471
270462AD2-086
Solar/Wind Harmer
3.672
965681AG1-436 GEN
Solar/Wind Harmer
6.411
965791AG1-447 GEN
Solar/Wind Harmer
3.28
970349AG2-230 GEN
Solar/Wind Harmer
7.653
270535AF1-215 GEN1
Solar/Wind Harmer
2.191
270536AF1-215 GEN2
Solar/Wind Harmer
2.191
274805UNIV PK N;1U
Adder
2.36
274808UNIV PK N;4U
Adder
2.344
274888KELLY CRK;1U
Solar/Wind Harmer
2.73
276776AD2-060 GEN
Solar/Wind Harmer
0.194
958011AF2-095 GEN
Solar/Wind Harmer
6.662
970941AG2-585 GEN
Solar/Wind Harmer
2.544
274770LINCOLN ;1U
Adder
2.867
274771LINCOLN ;2U
Adder
2.867
276897AD1-100 C
Solar/Wind Harmer
21.286
276893AG1-478 C
Solar/Wind Harmer
0.201
274674JOLIET 9 ;6U
Adder
7.05
942221AE2-234 GEN
Solar/Wind Harmer
1.593
958481AF2-142 GEN
Solar/Wind Harmer
6.786
945421AF1-207 GEN
Solar/Wind Harmer
6.334
957841AF2-078 GEN
Solar/Wind Harmer
2.727
274695ROCKY RD ;2P
Adder
5.004
274693ROCKY RD ;1P
Adder
4.955
274697ROCKY RD ;3P
Adder
1.359
274696ROCKY RD ;4P
Adder
5.122
274683WAUKEGAN ;8U
Adder
9.465
274683WAUKEGAN ;8U
Adder
7.978
958491AF2-143 GEN
Solar/Wind Harmer
6.726
276901AD2-066 C O1
Solar/Wind Harmer
1.567
962691AG1-118 GEN
Solar/Wind Harmer
13.403
960751AF2-366 GEN
Solar/Wind Harmer
1.28
972235AH1-702 GEN1
Adder
1.106
972236AH1-702 GEN2
Adder
0.962
274764LEE CO EC;5U
Adder
4.051
274765LEE CO EC;6U
Adder
4.051
274762LEE CO EC;3U
Adder
4.042
274763LEE CO EC;4U
Adder
4.004
203835AF1-098 GEN
Solar/Wind Helper
1.324
241967AE2-285_GEN
Solar/Wind Helper
0.342
241801AE1-079 GEN
Solar/Wind Helper
0.133
254304AE2-114 C
Solar/Wind Helper
0.114
254305AE2-115 C
Solar/Wind Helper
0.114
962101AG1-054 GEN
Solar/Wind Helper
0.33
203804AE2-113_GEN
Solar/Wind Helper
0.871
940863AE2-074 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Helper
0.106
270180AB1-006 GEN1
Solar/Wind Harmer
1.454
270181AB1-006 GEN2
Solar/Wind Harmer
0.145
24189902OREGON_CT2
50/50
2.847
23888702TROY G3
50/50
1.904
972253AH1-711 GEN
50/50
58.21
23856402BAYSG1
50/50
1.21
23920202STRYCT
50/50
1.932
241885AC2-103 GEN1
Solar/Wind Harmer
15.673
241858AF1-205_GEN
Solar/Wind Harmer
5.567
241840AF1-064_GEN
Solar/Wind Harmer
1.358
23906502RICHG2&3
Adder
1.33
960841AF2-375 GEN
Solar/Wind Harmer
3.316
270297AD1-101 GEN
Solar/Wind Harmer
1.377
270258AD1-119 GEN
Solar/Wind Harmer
1.284
24441205WTRV SLR C
Solar/Wind Harmer
0.084
246936BC-WTG1
Solar/Wind Harmer
2.325
270489AE1-102 GEN1
Solar/Wind Harmer
0.773
270449AD2-020 GEN
Solar/Wind Harmer
1.658
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
17.673
945111AF1-176 GEN
Solar/Wind Harmer
10.321
957891AF2-083 GEN
Solar/Wind Harmer
8.642
24639705ELKHART HY
Adder
0.086
270216AD2-079_GEN
Solar/Wind Harmer
0.336
965011AG1-365 GEN
Solar/Wind Harmer
5.383
270317AD1-130_GEN
Solar/Wind Harmer
1.69
270485AE1-090_GEN
Solar/Wind Harmer
0.319
970373AG2-245 GEN
Solar/Wind Harmer
10.317
270391AF1-285 GEN3
Solar/Wind Harmer
0.592
270578AF1-285 GEN2
Solar/Wind Harmer
0.592
270055AF2-134 C O1
Solar/Wind Harmer
1.46
274751CRETE EC ;1U
Adder
2.327
274754CRETE EC ;4U
Adder
2.327
958381AF2-132 GEN
Solar/Wind Harmer
4.303
964861AG1-349 GEN
Solar/Wind Harmer
3.722
971917AH1-482 GEN
Solar/Wind Harmer
4.295
274723RIVER EC ;12
Adder
8.465
274812UNIV PK N;8U
Adder
2.355
274802UNIV PARK;5U
Adder
2.711
940581AE2-045 GEN
Solar/Wind Harmer
4.717
972207SS24-0001
Solar/Wind Harmer
10.192
274773LINCOLN ;4U
Adder
2.867
274774LINCOLN ;5U
Adder
2.867
971605AH1-302 GEN
Solar/Wind Harmer
4.033
274676JOLIET 29;8U
Adder
14.075
941551AE2-152 GEN
Solar/Wind Harmer
2.078
274732ELWOOD EC;7P
Adder
7.527
274674JOLIET 9 ;6U
Adder
7.05
274871GR RIDGE ;2U
Solar/Wind Harmer
3.501
274847GR RIDGE ;BU
Solar/Wind Harmer
2.302
274745AC1-111 GEN9
Adder
2.531
276694AA1-018 GEN2
Solar/Wind Harmer
2.855
276691AA1-018 GEN1
Solar/Wind Harmer
0.341
274861TOP CROP ;1U
Solar/Wind Harmer
2.74
274682WAUKEGAN ;7U
Adder
8.08
274828WAUKEGAN ;BP
Adder
4.961
276805AD2-038 GEN
Solar/Wind Harmer
2.299
270024AE2-089 GEN
Solar/Wind Harmer
2.097
939401AE1-172 GEN
Solar/Wind Harmer
6.227
276882AE2-255 GEN
Solar/Wind Harmer
1.504
962781AG1-127 GEN
Solar/Wind Harmer
4.242
274872LEEDK;1U
Solar/Wind Harmer
3.655
274822ROCKFORD ;11
Adder
8.629
274761LEE CO EC;2U
Adder
4.042
274766LEE CO EC;7U
Adder
3.994
241807AE2-176_GEN
Solar/Wind Helper
2.231
203947AF1-006 C
Solar/Wind Helper
0.382
961971AG1-040 GEN
Solar/Wind Helper
0.335
203830AF1-094 GEN
Solar/Wind Helper
0.325
203979AG1-198 GEN
Solar/Wind Helper
0.195
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.077
990142J1224
External Queue
13.951210975646973
990527J1329
External Queue
1.908510684967041
991182J1586 G
External Queue
26.15701675415039
991177J1571 G
External Queue
15.860834121704102
LAGNLTFEXP_LAGN->PJM
CLTF
4.973
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.195
TVALTFEXP_TVA->PJM
CLTF
2.252
NYPJM->LTFIMP_NY
CLTF
2.036
LGEELTFEXP_LGEE->PJM
CLTF
2.013
WECLTFEXP_WEC->PJM
CLTF
1.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.473
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.915
MECLTFEXP_MEC->PJM
CLTF
6.524
SIGELTFEXP_SIGE->PJM
CLTF
0.169
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.776

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.51 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2374.58
MW Contribution:
13.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
15.36
24190002OREGON_ST1
50/50
3.83
24189802OREGON_CT1
50/50
2.907
23888802TROY G4
50/50
1.904
241996AE2-282_GEN
Solar/Wind Harmer
2.185
241808AF1-120 C
Solar/Wind Harmer
1.218
944231AF1-091 GEN
Solar/Wind Harmer
12.009
247522W1-056 GEN
Solar/Wind Harmer
1.436
246937BC-WTG2
Solar/Wind Harmer
2.324
247607V1-011 GEN
Solar/Wind Harmer
2.343
942801AE2-298 GEN
Solar/Wind Harmer
0.892
961051AF2-396 GEN
Solar/Wind Harmer
9.315
961051AF2-396 GEN
Solar/Wind Harmer
4.333
247620Y3-023
Adder
0.259
270246TR4_N_V150
Solar/Wind Harmer
0.471
270247TR4_N_V136
Solar/Wind Harmer
0.471
270462AD2-086
Solar/Wind Harmer
3.67
965681AG1-436 GEN
Solar/Wind Harmer
6.412
965791AG1-447 GEN
Solar/Wind Harmer
3.281
970349AG2-230 GEN
Solar/Wind Harmer
7.655
270535AF1-215 GEN1
Solar/Wind Harmer
2.191
270536AF1-215 GEN2
Solar/Wind Harmer
2.191
274805UNIV PK N;1U
Adder
2.36
274808UNIV PK N;4U
Adder
2.345
274888KELLY CRK;1U
Solar/Wind Harmer
2.731
276776AD2-060 GEN
Solar/Wind Harmer
0.194
958011AF2-095 GEN
Solar/Wind Harmer
6.664
970941AG2-585 GEN
Solar/Wind Harmer
2.545
274770LINCOLN ;1U
Adder
2.867
274771LINCOLN ;2U
Adder
2.867
276897AD1-100 C
Solar/Wind Harmer
21.292
276893AG1-478 C
Solar/Wind Harmer
0.201
274674JOLIET 9 ;6U
Adder
7.052
942221AE2-234 GEN
Solar/Wind Harmer
1.593
958481AF2-142 GEN
Solar/Wind Harmer
6.788
945421AF1-207 GEN
Solar/Wind Harmer
6.336
957841AF2-078 GEN
Solar/Wind Harmer
2.728
274696ROCKY RD ;4P
Adder
5.123
274695ROCKY RD ;2P
Adder
5.005
274693ROCKY RD ;1P
Adder
4.956
274697ROCKY RD ;3P
Adder
1.36
274683WAUKEGAN ;8U
Adder
9.467
274683WAUKEGAN ;8U
Adder
7.981
958491AF2-143 GEN
Solar/Wind Harmer
6.728
276901AD2-066 C O1
Solar/Wind Harmer
1.568
962691AG1-118 GEN
Solar/Wind Harmer
13.407
960751AF2-366 GEN
Solar/Wind Harmer
1.28
270180AB1-006 GEN1
Solar/Wind Harmer
3.203
972235AH1-702 GEN1
Adder
1.107
972236AH1-702 GEN2
Adder
0.962
274764LEE CO EC;5U
Adder
4.053
274765LEE CO EC;6U
Adder
4.053
274762LEE CO EC;3U
Adder
4.043
274763LEE CO EC;4U
Adder
4.005
203835AF1-098 GEN
Solar/Wind Helper
1.318
241967AE2-285_GEN
Solar/Wind Helper
0.34
241801AE1-079 GEN
Solar/Wind Helper
0.133
254304AE2-114 C
Solar/Wind Helper
0.113
254305AE2-115 C
Solar/Wind Helper
0.113
962101AG1-054 GEN
Solar/Wind Helper
0.328
203804AE2-113_GEN
Solar/Wind Helper
0.867
940863AE2-074 GEN
Solar/Wind Helper
0.225
946381AF1-302 GEN
Solar/Wind Helper
0.105
23929302BS-PKR
50/50
2.13
241832AE2-181_GEN
Solar/Wind Harmer
1.983
958321AF2-126 GEN
Solar/Wind Harmer
1.458
23906402RICHG1
Adder
1.333
23906502RICHG2&3
Adder
1.329
270541AE2-072 C
Solar/Wind Harmer
4.237
270044AE2-322 C
Solar/Wind Harmer
0.862
246938BC-WTG3
Solar/Wind Harmer
2.364
270491AE1-102 GEN2
Solar/Wind Harmer
0.772
958091AF2-103 GEN
Solar/Wind Harmer
0.096
270588AE1-091_GEN
Solar/Wind Harmer
6.48
945111AF1-176 GEN
Solar/Wind Harmer
3.271
270505AE1-170 C O1
Solar/Wind Harmer
8.672
24695305TIMB G C
Solar/Wind Harmer
1.909
270063AE2-323 C
Solar/Wind Harmer
1.221
247643Z2-116 C
Solar/Wind Harmer
0.039
965021AG1-366 GEN
Solar/Wind Harmer
1.252
24441505OLIV SLR
Solar/Wind Harmer
0.071
270043AE2-236 GEN
Solar/Wind Harmer
2.809
971347AH1-153 GEN
Solar/Wind Harmer
2.552
942871AE2-306 GEN
Solar/Wind Harmer
0.444
270391AF1-285 GEN3
Solar/Wind Harmer
0.228
972231SS25-0005
Solar/Wind Harmer
4.52
972181SS23-001
Solar/Wind Harmer
2.825
274752CRETE EC ;2U
Adder
2.328
274753CRETE EC ;3U
Adder
2.328
964401AG1-302 GEN
Solar/Wind Harmer
4.304
274724RIVER EC ;11
Adder
8.366
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274811UNIV PK N;7U
Adder
2.355
276164X3-005 C
Solar/Wind Harmer
0.329
274803UNIV PARK;6U
Adder
2.711
274826FISK ;BP
Adder
5.082
972038AH1-567 GEN2
Adder
0.169
274887GEN-1.85
Solar/Wind Harmer
2.465
276772AC2-154 GEN
Solar/Wind Harmer
1.291
276843GEN-1.7
Solar/Wind Harmer
0.265
276806AD2-047 C O1
Solar/Wind Harmer
4.95
274772LINCOLN ;3U
Adder
2.867
972259AH1-714 GEN
Adder
8.761
274676JOLIET 29;8U
Adder
13.576
939351AE1-166 GEN
Solar/Wind Harmer
2.718
274729ELWOOD EC;1P
Adder
7.529
274730ELWOOD EC;6P
Adder
7.529
274734ELWOOD EC;8P
Adder
7.529
274736ELWOOD EC;9P
Adder
7.529
970707AG2-453 GEN
Solar/Wind Harmer
12.823
943121AE2-341 GEN
Solar/Wind Harmer
6.79
943591AF1-030 GEN
Solar/Wind Harmer
4.527
274862TOP CROP ;2U
Solar/Wind Harmer
2.289
274682WAUKEGAN ;7U
Adder
8.082
276868AE1-113 GEN
Solar/Wind Harmer
4.515
274879MINONK ;1U
Solar/Wind Harmer
3.01
24690905MDL-1G C
Solar/Wind Harmer
3.575
274760LEE CO EC;1U
Adder
4.043
274767LEE CO EC;8U
Adder
3.996
962511AG1-100 GEN
Solar/Wind Helper
0.341
23888502TROY G1
50/50
1.904
23888602TROY G2
50/50
1.904
945411AF1-206 GEN
Solar/Wind Harmer
8.181
945641AF1-229 GEN
Solar/Wind Harmer
3.522
270361_3
Solar/Wind Harmer
7.42
270575GUS2 35KV
Solar/Wind Harmer
8.741
270499AE1-146 GEN
Solar/Wind Harmer
2.091
971549AH1-272 GEN
Solar/Wind Harmer
13.493
270404AC1-167 GEN
Solar/Wind Harmer
0.711
944161AF1-084 GEN
Solar/Wind Harmer
1.326
957201AF2-014 GEN
Solar/Wind Harmer
2.695
270435AC2-044 GEN
Solar/Wind Harmer
1.188
270007AE1-245 C
Solar/Wind Harmer
3.201
965041AG1-368 GEN
Solar/Wind Harmer
5.574
970031AG2-029 GEN
Solar/Wind Harmer
13.857
247521TR3_G114
Solar/Wind Harmer
1.86
270191TR4_S_V150
Solar/Wind Harmer
1.659
965051AG1-369 GEN
Solar/Wind Harmer
2.763
966831AG1-554 GEN
Solar/Wind Harmer
0.657
971771AH1-392 GEN
Solar/Wind Harmer
4.928
959331AF2-224 GEN
Solar/Wind Harmer
5.382
270526AF1-158 GEN
Solar/Wind Harmer
2.433
270302AB2-170 GEN
Solar/Wind Harmer
4.419
960681AF2-359 GEN
Solar/Wind Harmer
1.938
971567AH1-282 GEN
Solar/Wind Harmer
2.498
963791AG1-232 GEN
Solar/Wind Harmer
6.704
270223U2-072_GEN1
Solar/Wind Harmer
0.966
270224U2-072_GEN2
Solar/Wind Harmer
0.966
270227U2-072_GEN3
Solar/Wind Harmer
0.966
270228U2-072_GEN4
Solar/Wind Harmer
0.966
270231U2-072_GEN5
Solar/Wind Harmer
0.966
270578AF1-285 GEN2
Solar/Wind Harmer
0.228
270071AF1-092 GEN
Solar/Wind Harmer
7.112
958391AF2-133 GEN
Solar/Wind Harmer
4.264
959141AF2-205 GEN
Solar/Wind Harmer
2.822
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
274800UNIV PARK;3U
Adder
2.702
274801UNIV PARK;4U
Adder
2.702
960591AF2-350 GEN
Solar/Wind Harmer
4.627
274775LINCOLN ;6U
Adder
2.867
274776LINCOLN ;7U
Adder
2.867
274777LINCOLN ;8U
Adder
2.867
972228AH1-698 GEN2
Adder
1.709
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.849
274687WILL CNTY;4U
Adder
12.849
274675JOLIET 29;7U
Adder
14.079
274675JOLIET 29;7U
Adder
13.576
276893AG1-478 C
Solar/Wind Harmer
0.252
274728ELWOOD EC;5P
Adder
7.529
274731ELWOOD EC;2P
Adder
7.529
274733ELWOOD EC;3P
Adder
7.529
274735ELWOOD EC;4P
Adder
7.529
970833AG2-524 GEN
Solar/Wind Harmer
3.979
970833AG2-524 GEN
Solar/Wind Harmer
1.85
274744AC1-111 GEN8
Adder
2.531
274746AC1-111 G10
Adder
2.531
970073AG2-061 GEN
Solar/Wind Harmer
1.043
24729505KEY G4
Adder
2.859
274823ROCKFORD ;21
Adder
8.57
972267AH1-718 GEN
Adder
1.797
241886AC2-103 GEN2
Solar/Wind Helper
3.957
241985AE1-237 GEN
Solar/Wind Helper
0.132
241982AE2-343 S C
Solar/Wind Helper
0.119
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
20334926Z1-069 C
Solar/Wind Helper
0.645
946581AF1-322 GEN
Solar/Wind Harmer
3.636
24189902OREGON_CT2
50/50
2.847
23888702TROY G3
50/50
1.904
972253AH1-711 GEN
50/50
58.195
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.931
241858AF1-205_GEN
Solar/Wind Harmer
5.564
241840AF1-064_GEN
Solar/Wind Harmer
1.357
23906502RICHG2&3
Adder
1.329
960841AF2-375 GEN
Solar/Wind Harmer
3.308
270297AD1-101 GEN
Solar/Wind Harmer
1.376
270258AD1-119 GEN
Solar/Wind Harmer
1.283
24441205WTRV SLR C
Solar/Wind Harmer
0.084
246936BC-WTG1
Solar/Wind Harmer
2.324
270489AE1-102 GEN1
Solar/Wind Harmer
0.772
270449AD2-020 GEN
Solar/Wind Harmer
1.658
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
17.666
945111AF1-176 GEN
Solar/Wind Harmer
10.322
957891AF2-083 GEN
Solar/Wind Harmer
8.643
24639705ELKHART HY
Adder
0.086
270216AD2-079_GEN
Solar/Wind Harmer
0.336
965011AG1-365 GEN
Solar/Wind Harmer
5.382
270317AD1-130_GEN
Solar/Wind Harmer
1.689
270485AE1-090_GEN
Solar/Wind Harmer
0.319
970373AG2-245 GEN
Solar/Wind Harmer
10.318
270391AF1-285 GEN3
Solar/Wind Harmer
0.592
270578AF1-285 GEN2
Solar/Wind Harmer
0.592
270055AF2-134 C O1
Solar/Wind Harmer
1.461
274751CRETE EC ;1U
Adder
2.328
274754CRETE EC ;4U
Adder
2.328
958381AF2-132 GEN
Solar/Wind Harmer
4.304
964861AG1-349 GEN
Solar/Wind Harmer
3.723
971917AH1-482 GEN
Solar/Wind Harmer
4.296
274723RIVER EC ;12
Adder
8.466
274812UNIV PK N;8U
Adder
2.355
274802UNIV PARK;5U
Adder
2.711
940581AE2-045 GEN
Solar/Wind Harmer
4.718
972207SS24-0001
Solar/Wind Harmer
10.195
274773LINCOLN ;4U
Adder
2.867
274774LINCOLN ;5U
Adder
2.867
971605AH1-302 GEN
Solar/Wind Harmer
4.034
274676JOLIET 29;8U
Adder
14.079
941551AE2-152 GEN
Solar/Wind Harmer
2.079
274732ELWOOD EC;7P
Adder
7.529
274674JOLIET 9 ;6U
Adder
7.052
274871GR RIDGE ;2U
Solar/Wind Harmer
3.502
274847GR RIDGE ;BU
Solar/Wind Harmer
2.303
274745AC1-111 GEN9
Adder
2.531
276694AA1-018 GEN2
Solar/Wind Harmer
2.856
276691AA1-018 GEN1
Solar/Wind Harmer
0.341
274861TOP CROP ;1U
Solar/Wind Harmer
2.741
274682WAUKEGAN ;7U
Adder
8.082
274828WAUKEGAN ;BP
Adder
4.963
276805AD2-038 GEN
Solar/Wind Harmer
2.3
270024AE2-089 GEN
Solar/Wind Harmer
2.097
939401AE1-172 GEN
Solar/Wind Harmer
6.229
276882AE2-255 GEN
Solar/Wind Harmer
1.505
962781AG1-127 GEN
Solar/Wind Harmer
4.243
274872LEEDK;1U
Solar/Wind Harmer
3.657
274822ROCKFORD ;11
Adder
8.632
274761LEE CO EC;2U
Adder
4.043
274766LEE CO EC;7U
Adder
3.996
241885AC2-103 GEN1
Solar/Wind Helper
3.957
241807AE2-176_GEN
Solar/Wind Helper
2.243
203947AF1-006 C
Solar/Wind Helper
0.381
961971AG1-040 GEN
Solar/Wind Helper
0.334
203830AF1-094 GEN
Solar/Wind Helper
0.324
203979AG1-198 GEN
Solar/Wind Helper
0.194
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
990142J1224
External Queue
13.943214416503906
990527J1329
External Queue
1.907416582107544
991182J1586 G
External Queue
26.14141845703125
991177J1571 G
External Queue
15.850347518920898
LAGNLTFEXP_LAGN->PJM
CLTF
4.981
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.218
TVALTFEXP_TVA->PJM
CLTF
2.256
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.48
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.931
MECLTFEXP_MEC->PJM
CLTF
6.528
SIGELTFEXP_SIGE->PJM
CLTF
0.169
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.82

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.27 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2199.92
MW Contribution:
10.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
1.902
23888602TROY G2
50/50
1.902
241886AC2-103 GEN2
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.061
270575GUS2 35KV
Solar/Wind Harmer
4.061
270499AE1-146 GEN
Solar/Wind Harmer
0.019
23929302BS-PKR
50/50
2.128
958321AF2-126 GEN
Solar/Wind Harmer
1.129
23906402RICHG1
Adder
1.331
23906502RICHG2&3
Adder
1.328
270541AE2-072 C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.149
270491AE1-102 GEN2
Solar/Wind Harmer
0.538
270588AE1-091_GEN
Solar/Wind Harmer
3.209
945111AF1-176 GEN
Solar/Wind Harmer
3.265
270505AE1-170 C O1
Solar/Wind Harmer
4.228
24189902OREGON_CT2
50/50
2.845
23888702TROY G3
50/50
1.902
972253AH1-711 GEN
50/50
58.161
23856402BAYSG1
50/50
1.208
23920202STRYCT
50/50
1.93
241885AC2-103 GEN1
Solar/Wind Harmer
0
241858AF1-205_GEN
Solar/Wind Harmer
3.879
23906502RICHG2&3
Adder
1.328
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.167
270489AE1-102 GEN1
Solar/Wind Harmer
0.538
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.151
965421AG1-410 GEN
Solar/Wind Harmer
12.304
945111AF1-176 GEN
Solar/Wind Harmer
7.189
957891AF2-083 GEN
Solar/Wind Harmer
6.688
24639705ELKHART HY
Adder
0.086
965011AG1-365 GEN
Solar/Wind Harmer
3.748
270317AD1-130_GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.184
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
3.916
274754CRETE EC ;4U
Adder
3.916
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.286
274723RIVER EC ;12
Adder
8.448
274812UNIV PK N;8U
Adder
2.35
274802UNIV PARK;5U
Adder
2.705
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.025
274676JOLIET 29;8U
Adder
14.047
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.513
274674JOLIET 9 ;6U
Adder
7.036
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.526
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.512
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.064
274828WAUKEGAN ;BP
Adder
4.951
276805AD2-038 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.327
276882AE2-255 GEN
Solar/Wind Harmer
0.362
962781AG1-127 GEN
Solar/Wind Harmer
2.955
274872LEEDK;1U
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.337
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.249
270043AE2-236 GEN
Solar/Wind Harmer
2.282
971347AH1-153 GEN
Solar/Wind Harmer
1.777
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
274752CRETE EC ;2U
Adder
3.916
274753CRETE EC ;3U
Adder
3.916
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.348
274814UNIV PK N;0U
Adder
2.371
274807UNIV PK N;3U
Adder
2.366
274811UNIV PK N;7U
Adder
2.35
274803UNIV PARK;6U
Adder
2.705
274826FISK ;BP
Adder
5.071
972038AH1-567 GEN2
Adder
0.169
274887GEN-1.85
Solar/Wind Harmer
0.084
276843GEN-1.7
Solar/Wind Harmer
0.104
276806AD2-047 C O1
Solar/Wind Harmer
1.825
274772LINCOLN ;3U
Adder
3.895
972259AH1-714 GEN
Adder
8.742
274676JOLIET 29;8U
Adder
13.546
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
7.512
274730ELWOOD EC;6P
Adder
7.513
274734ELWOOD EC;8P
Adder
7.513
274736ELWOOD EC;9P
Adder
7.513
970707AG2-453 GEN
Solar/Wind Harmer
10.414
943121AE2-341 GEN
Solar/Wind Harmer
5.283
943591AF1-030 GEN
Solar/Wind Harmer
3.513
274862TOP CROP ;2U
Solar/Wind Harmer
0.425
274682WAUKEGAN ;7U
Adder
8.064
276868AE1-113 GEN
Solar/Wind Harmer
0.621
274879MINONK ;1U
Solar/Wind Harmer
0.13
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.1
944531AF1-118 GEN
Solar/Wind Harmer
13.889
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
0.112
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
959091AF2-200 GEN
Solar/Wind Harmer
6.136
970571AG2-364 GEN
Solar/Wind Harmer
6.112
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.034
274767LEE CO EC;8U
Adder
3.986
24386205FR-12G C
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.342
971997AH1-543 GEN
Solar/Wind Harmer
1.624
957471AF2-041 GEN
Solar/Wind Harmer
9.204
959081AF2-199 GEN
Solar/Wind Harmer
3.068
971067AG2-660 GEN
Solar/Wind Harmer
1.023
274822ROCKFORD ;11
Adder
8.612
970569AG2-363 GEN
Solar/Wind Harmer
9.168
970819AG2-516 GEN
Solar/Wind Harmer
3.659
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.034
274766LEE CO EC;7U
Adder
3.986
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276708O09 GEN2
Solar/Wind Harmer
0.106
241807AE2-176_GEN
Solar/Wind Helper
2.245
203947AF1-006 C
Solar/Wind Helper
0.381
961971AG1-040 GEN
Solar/Wind Helper
0.334
203830AF1-094 GEN
Solar/Wind Helper
0.324
203979AG1-198 GEN
Solar/Wind Helper
0.195
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.077
23867002DVBSG1
50/50
15.354
24190002OREGON_ST1
50/50
3.828
24189802OREGON_CT1
50/50
2.906
23888802TROY G4
50/50
1.902
970621AG2-405 GEN
Solar/Wind Harmer
0.863
944231AF1-091 GEN
Solar/Wind Harmer
10.721
970623AG2-406 GEN
Solar/Wind Harmer
0.805
246937BC-WTG2
Solar/Wind Harmer
0.167
247607V1-011 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
8.175
961051AF2-396 GEN
Solar/Wind Harmer
5.45
247620Y3-023
Adder
0.259
270246TR4_N_V150
Solar/Wind Harmer
0.025
270247TR4_N_V136
Solar/Wind Harmer
0.025
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.465
965791AG1-447 GEN
Solar/Wind Harmer
3.274
970349AG2-230 GEN
Solar/Wind Harmer
5.33
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.355
274808UNIV PK N;4U
Adder
2.34
274888KELLY CRK;1U
Solar/Wind Harmer
0.188
276776AD2-060 GEN
Solar/Wind Harmer
0.344
958011AF2-095 GEN
Solar/Wind Harmer
4.639
970941AG2-585 GEN
Solar/Wind Harmer
1.772
274770LINCOLN ;1U
Adder
3.895
274771LINCOLN ;2U
Adder
3.895
276897AD1-100 C
Solar/Wind Harmer
7.977
276893AG1-478 C
Solar/Wind Harmer
0.213
274674JOLIET 9 ;6U
Adder
7.036
942221AE2-234 GEN
Solar/Wind Harmer
1.273
958481AF2-142 GEN
Solar/Wind Harmer
4.726
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.112
274695ROCKY RD ;2P
Adder
4.994
274693ROCKY RD ;1P
Adder
4.945
274697ROCKY RD ;3P
Adder
1.357
274683WAUKEGAN ;8U
Adder
9.446
274683WAUKEGAN ;8U
Adder
7.963
958491AF2-143 GEN
Solar/Wind Harmer
4.683
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.333
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.136
971343AH1-151 GEN
Solar/Wind Harmer
6.136
972235AH1-702 GEN1
Adder
1.104
972236AH1-702 GEN2
Adder
0.96
938861AE1-114 GEN
Solar/Wind Harmer
1.719
274764LEE CO EC;5U
Adder
4.043
274765LEE CO EC;6U
Adder
4.043
274762LEE CO EC;3U
Adder
4.034
274763LEE CO EC;4U
Adder
3.996
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.484
203835AF1-098 GEN
Solar/Wind Helper
1.32
241967AE2-285_GEN
Solar/Wind Helper
0.341
241801AE1-079 GEN
Solar/Wind Helper
0.133
254304AE2-114 C
Solar/Wind Helper
0.113
254305AE2-115 C
Solar/Wind Helper
0.113
962101AG1-054 GEN
Solar/Wind Helper
0.329
203804AE2-113_GEN
Solar/Wind Helper
0.869
940863AE2-074 GEN
Solar/Wind Helper
0.225
946381AF1-302 GEN
Solar/Wind Helper
0.105
971549AH1-272 GEN
Solar/Wind Harmer
10.493
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.524
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
3.882
970031AG2-029 GEN
Solar/Wind Harmer
2.091
247521TR3_G114
Solar/Wind Harmer
0.14
965051AG1-369 GEN
Solar/Wind Harmer
1.924
971771AH1-392 GEN
Solar/Wind Harmer
3.813
959331AF2-224 GEN
Solar/Wind Harmer
2.624
270526AF1-158 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.517
960681AF2-359 GEN
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
2.667
963791AG1-232 GEN
Solar/Wind Harmer
4.667
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270071AF1-092 GEN
Solar/Wind Harmer
6.326
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.594
274800UNIV PARK;3U
Adder
2.696
274801UNIV PARK;4U
Adder
2.696
960591AF2-350 GEN
Solar/Wind Harmer
3.221
274775LINCOLN ;6U
Adder
3.895
274776LINCOLN ;7U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
971611AH1-305 GEN
Solar/Wind Harmer
1.917
972228AH1-698 GEN2
Adder
1.705
972227AH1-698 GEN1
Adder
1.201
274687WILL CNTY;4U
Adder
12.821
274687WILL CNTY;4U
Adder
12.821
274675JOLIET 29;7U
Adder
14.048
274675JOLIET 29;7U
Adder
13.546
274728ELWOOD EC;5P
Adder
7.513
274731ELWOOD EC;2P
Adder
7.512
274733ELWOOD EC;3P
Adder
7.512
274735ELWOOD EC;4P
Adder
7.512
970833AG2-524 GEN
Solar/Wind Harmer
3.49
970833AG2-524 GEN
Solar/Wind Harmer
2.326
274744AC1-111 GEN8
Adder
2.526
274746AC1-111 G10
Adder
2.526
970073AG2-061 GEN
Solar/Wind Harmer
1.041
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.625
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.201
276861AD2-134 GEN
Solar/Wind Harmer
0.055
276863AD2-134 GEN
Solar/Wind Harmer
0.055
971171AH1-044 GEN
Solar/Wind Harmer
6.136
24729505KEY G4
Adder
2.853
274823ROCKFORD ;21
Adder
8.55
926823AC1-168 GEN
Solar/Wind Harmer
0.519
970169AG2-114 GEN
Solar/Wind Harmer
3.049
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971681AH1-341 GEN
Solar/Wind Harmer
4.884
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.793
276741O09 GEN1
Solar/Wind Harmer
0.106
241985AE1-237 GEN
Solar/Wind Helper
0.133
241982AE2-343 S C
Solar/Wind Helper
0.119
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
20334926Z1-069 C
Solar/Wind Helper
0.647
990142J1224
External Queue
13.943214416503906
990527J1329
External Queue
1.907416582107544
991182J1586 G
External Queue
26.14141845703125
991177J1571 G
External Queue
15.850347518920898
LAGNLTFEXP_LAGN->PJM
CLTF
4.961
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.187
TVALTFEXP_TVA->PJM
CLTF
2.246
NYPJM->LTFIMP_NY
CLTF
2.03
LGEELTFEXP_LGEE->PJM
CLTF
2.008
WECLTFEXP_WEC->PJM
CLTF
1.673
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.332
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.892
MECLTFEXP_MEC->PJM
CLTF
6.511
SIGELTFEXP_SIGE->PJM
CLTF
0.168
CPLELTFEXP_CPLE->PJM
CLTF
0.328
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.683

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.8 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2190.94
MW Contribution:
10.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.847
23888702TROY G3
50/50
1.904
972253AH1-711 GEN
50/50
58.195
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.931
241858AF1-205_GEN
Solar/Wind Harmer
3.882
23906502RICHG2&3
Adder
1.329
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.167
270489AE1-102 GEN1
Solar/Wind Harmer
0.539
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
12.325
945111AF1-176 GEN
Solar/Wind Harmer
7.201
957891AF2-083 GEN
Solar/Wind Harmer
6.7
24639705ELKHART HY
Adder
0.086
965011AG1-365 GEN
Solar/Wind Harmer
3.755
270317AD1-130_GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.199
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
3.924
274754CRETE EC ;4U
Adder
3.924
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.296
274723RIVER EC ;12
Adder
8.466
274812UNIV PK N;8U
Adder
2.355
274802UNIV PARK;5U
Adder
2.711
940581AE2-045 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.903
274774LINCOLN ;5U
Adder
3.903
971605AH1-302 GEN
Solar/Wind Harmer
4.034
274676JOLIET 29;8U
Adder
14.079
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.529
274674JOLIET 9 ;6U
Adder
7.052
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.531
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.513
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.082
274828WAUKEGAN ;BP
Adder
4.963
276805AD2-038 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.332
276882AE2-255 GEN
Solar/Wind Harmer
0.363
962781AG1-127 GEN
Solar/Wind Harmer
2.962
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.628
957471AF2-041 GEN
Solar/Wind Harmer
9.225
959081AF2-199 GEN
Solar/Wind Harmer
3.075
971067AG2-660 GEN
Solar/Wind Harmer
1.025
274822ROCKFORD ;11
Adder
8.632
970569AG2-363 GEN
Solar/Wind Harmer
9.19
970819AG2-516 GEN
Solar/Wind Harmer
3.668
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.043
274766LEE CO EC;7U
Adder
3.996
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276708O09 GEN2
Solar/Wind Harmer
0.106
241885AC2-103 GEN1
Solar/Wind Helper
3.957
241807AE2-176_GEN
Solar/Wind Helper
2.243
203947AF1-006 C
Solar/Wind Helper
0.381
961971AG1-040 GEN
Solar/Wind Helper
0.334
203830AF1-094 GEN
Solar/Wind Helper
0.324
203979AG1-198 GEN
Solar/Wind Helper
0.194
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
23929302BS-PKR
50/50
2.13
958321AF2-126 GEN
Solar/Wind Harmer
1.13
23906402RICHG1
Adder
1.333
23906502RICHG2&3
Adder
1.329
270541AE2-072 C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.149
270491AE1-102 GEN2
Solar/Wind Harmer
0.539
270588AE1-091_GEN
Solar/Wind Harmer
3.215
945111AF1-176 GEN
Solar/Wind Harmer
3.271
270505AE1-170 C O1
Solar/Wind Harmer
4.235
24695305TIMB G C
Solar/Wind Harmer
0.338
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270043AE2-236 GEN
Solar/Wind Harmer
2.286
971347AH1-153 GEN
Solar/Wind Harmer
1.78
270391AF1-285 GEN3
Solar/Wind Harmer
0.228
274752CRETE EC ;2U
Adder
3.924
274753CRETE EC ;3U
Adder
3.924
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.366
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274811UNIV PK N;7U
Adder
2.355
274803UNIV PARK;6U
Adder
2.711
274826FISK ;BP
Adder
5.082
972038AH1-567 GEN2
Adder
0.169
274887GEN-1.85
Solar/Wind Harmer
0.084
276843GEN-1.7
Solar/Wind Harmer
0.104
276806AD2-047 C O1
Solar/Wind Harmer
1.829
274772LINCOLN ;3U
Adder
3.903
972259AH1-714 GEN
Adder
8.761
274676JOLIET 29;8U
Adder
13.576
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
7.529
274730ELWOOD EC;6P
Adder
7.529
274734ELWOOD EC;8P
Adder
7.529
274736ELWOOD EC;9P
Adder
7.529
970707AG2-453 GEN
Solar/Wind Harmer
10.437
943121AE2-341 GEN
Solar/Wind Harmer
5.295
943591AF1-030 GEN
Solar/Wind Harmer
3.521
274862TOP CROP ;2U
Solar/Wind Harmer
0.426
274682WAUKEGAN ;7U
Adder
8.082
276868AE1-113 GEN
Solar/Wind Harmer
0.623
274879MINONK ;1U
Solar/Wind Harmer
0.13
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.107
944531AF1-118 GEN
Solar/Wind Harmer
13.92
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
959091AF2-200 GEN
Solar/Wind Harmer
6.15
970571AG2-364 GEN
Solar/Wind Harmer
6.126
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.043
274767LEE CO EC;8U
Adder
3.996
24386205FR-12G C
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.341
23867002DVBSG1
50/50
15.36
24190002OREGON_ST1
50/50
3.83
24189802OREGON_CT1
50/50
2.907
23888802TROY G4
50/50
1.904
970621AG2-405 GEN
Solar/Wind Harmer
0.865
944231AF1-091 GEN
Solar/Wind Harmer
10.737
970623AG2-406 GEN
Solar/Wind Harmer
0.807
246937BC-WTG2
Solar/Wind Harmer
0.167
247607V1-011 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
8.189
961051AF2-396 GEN
Solar/Wind Harmer
5.459
247620Y3-023
Adder
0.259
270246TR4_N_V150
Solar/Wind Harmer
0.025
270247TR4_N_V136
Solar/Wind Harmer
0.025
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.474
965791AG1-447 GEN
Solar/Wind Harmer
3.281
970349AG2-230 GEN
Solar/Wind Harmer
5.34
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.36
274808UNIV PK N;4U
Adder
2.345
274888KELLY CRK;1U
Solar/Wind Harmer
0.188
276776AD2-060 GEN
Solar/Wind Harmer
0.344
958011AF2-095 GEN
Solar/Wind Harmer
4.649
970941AG2-585 GEN
Solar/Wind Harmer
1.776
274770LINCOLN ;1U
Adder
3.903
274771LINCOLN ;2U
Adder
3.903
276897AD1-100 C
Solar/Wind Harmer
7.994
276893AG1-478 C
Solar/Wind Harmer
0.213
274674JOLIET 9 ;6U
Adder
7.052
942221AE2-234 GEN
Solar/Wind Harmer
1.276
958481AF2-142 GEN
Solar/Wind Harmer
4.736
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.123
274695ROCKY RD ;2P
Adder
5.005
274693ROCKY RD ;1P
Adder
4.956
274697ROCKY RD ;3P
Adder
1.36
274683WAUKEGAN ;8U
Adder
9.467
274683WAUKEGAN ;8U
Adder
7.981
958491AF2-143 GEN
Solar/Wind Harmer
4.694
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.354
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.15
971343AH1-151 GEN
Solar/Wind Harmer
6.15
972235AH1-702 GEN1
Adder
1.107
972236AH1-702 GEN2
Adder
0.962
938861AE1-114 GEN
Solar/Wind Harmer
1.723
274764LEE CO EC;5U
Adder
4.053
274765LEE CO EC;6U
Adder
4.053
274762LEE CO EC;3U
Adder
4.043
274763LEE CO EC;4U
Adder
4.005
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.343
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.485
203835AF1-098 GEN
Solar/Wind Helper
1.318
241967AE2-285_GEN
Solar/Wind Helper
0.34
241801AE1-079 GEN
Solar/Wind Helper
0.133
254304AE2-114 C
Solar/Wind Helper
0.113
254305AE2-115 C
Solar/Wind Helper
0.113
962101AG1-054 GEN
Solar/Wind Helper
0.328
203804AE2-113_GEN
Solar/Wind Helper
0.867
940863AE2-074 GEN
Solar/Wind Helper
0.225
946381AF1-302 GEN
Solar/Wind Helper
0.105
23888502TROY G1
50/50
1.904
23888602TROY G2
50/50
1.904
945411AF1-206 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.066
270575GUS2 35KV
Solar/Wind Harmer
4.066
270499AE1-146 GEN
Solar/Wind Harmer
0.019
971549AH1-272 GEN
Solar/Wind Harmer
10.508
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.525
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
3.889
970031AG2-029 GEN
Solar/Wind Harmer
2.095
247521TR3_G114
Solar/Wind Harmer
0.14
965051AG1-369 GEN
Solar/Wind Harmer
1.928
971771AH1-392 GEN
Solar/Wind Harmer
3.82
959331AF2-224 GEN
Solar/Wind Harmer
2.629
270526AF1-158 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.518
960681AF2-359 GEN
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
2.672
963791AG1-232 GEN
Solar/Wind Harmer
4.677
270578AF1-285 GEN2
Solar/Wind Harmer
0.228
270071AF1-092 GEN
Solar/Wind Harmer
6.34
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
274800UNIV PARK;3U
Adder
2.702
274801UNIV PARK;4U
Adder
2.702
960591AF2-350 GEN
Solar/Wind Harmer
3.228
274775LINCOLN ;6U
Adder
3.903
274776LINCOLN ;7U
Adder
3.903
274777LINCOLN ;8U
Adder
3.903
971611AH1-305 GEN
Solar/Wind Harmer
1.921
972228AH1-698 GEN2
Adder
1.709
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.849
274687WILL CNTY;4U
Adder
12.849
274675JOLIET 29;7U
Adder
14.079
274675JOLIET 29;7U
Adder
13.576
274728ELWOOD EC;5P
Adder
7.529
274731ELWOOD EC;2P
Adder
7.529
274733ELWOOD EC;3P
Adder
7.529
274735ELWOOD EC;4P
Adder
7.529
970833AG2-524 GEN
Solar/Wind Harmer
3.497
970833AG2-524 GEN
Solar/Wind Harmer
2.332
274744AC1-111 GEN8
Adder
2.531
274746AC1-111 G10
Adder
2.531
970073AG2-061 GEN
Solar/Wind Harmer
1.043
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.636
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.204
276861AD2-134 GEN
Solar/Wind Harmer
0.055
276863AD2-134 GEN
Solar/Wind Harmer
0.055
971171AH1-044 GEN
Solar/Wind Harmer
6.15
24729505KEY G4
Adder
2.859
274823ROCKFORD ;21
Adder
8.57
926823AC1-168 GEN
Solar/Wind Harmer
0.52
970169AG2-114 GEN
Solar/Wind Harmer
3.057
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971681AH1-341 GEN
Solar/Wind Harmer
4.896
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.797
276741O09 GEN1
Solar/Wind Harmer
0.106
241886AC2-103 GEN2
Solar/Wind Helper
3.957
241985AE1-237 GEN
Solar/Wind Helper
0.132
241982AE2-343 S C
Solar/Wind Helper
0.119
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
20334926Z1-069 C
Solar/Wind Helper
0.645
990142J1224
External Queue
13.943214416503906
990527J1329
External Queue
1.907416582107544
991182J1586 G
External Queue
26.14141845703125
991177J1571 G
External Queue
15.850347518920898
LAGNLTFEXP_LAGN->PJM
CLTF
4.981
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.218
TVALTFEXP_TVA->PJM
CLTF
2.256
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.48
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.931
MECLTFEXP_MEC->PJM
CLTF
6.528
SIGELTFEXP_SIGE->PJM
CLTF
0.169
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.82

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-F1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.38 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2211.96
MW Contribution:
13.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
1.812
23888602TROY G2
50/50
1.812
945411AF1-206 GEN
Solar/Wind Harmer
8.027
945641AF1-229 GEN
Solar/Wind Harmer
3.439
270361_3
Solar/Wind Harmer
7.851
270575GUS2 35KV
Solar/Wind Harmer
9.25
270499AE1-146 GEN
Solar/Wind Harmer
2.194
971549AH1-272 GEN
Solar/Wind Harmer
13.002
270404AC1-167 GEN
Solar/Wind Harmer
0.699
270007AE1-245 C
Solar/Wind Harmer
3.149
957201AF2-014 GEN
Solar/Wind Harmer
2.636
270435AC2-044 GEN
Solar/Wind Harmer
1.162
944161AF1-084 GEN
Solar/Wind Harmer
1.282
966831AG1-554 GEN
Solar/Wind Harmer
0.674
965041AG1-368 GEN
Solar/Wind Harmer
5.454
247521TR3_G114
Solar/Wind Harmer
1.821
270191TR4_S_V150
Solar/Wind Harmer
1.625
965051AG1-369 GEN
Solar/Wind Harmer
2.706
970031AG2-029 GEN
Solar/Wind Harmer
13.45
971771AH1-392 GEN
Solar/Wind Harmer
4.772
959331AF2-224 GEN
Solar/Wind Harmer
5.247
24189902OREGON_CT2
50/50
2.69
23888702TROY G3
50/50
1.812
972253AH1-711 GEN
50/50
55.394
23856402BAYSG1
50/50
1.231
23920202STRYCT
50/50
1.896
241858AF1-205_GEN
Solar/Wind Harmer
5.467
241840AF1-064_GEN
Solar/Wind Harmer
1.356
23906502RICHG2&3
Adder
1.308
960841AF2-375 GEN
Solar/Wind Harmer
3.489
270297AD1-101 GEN
Solar/Wind Harmer
1.367
270258AD1-119 GEN
Solar/Wind Harmer
1.261
24441205WTRV SLR C
Solar/Wind Harmer
0.081
246936BC-WTG1
Solar/Wind Harmer
2.273
270489AE1-102 GEN1
Solar/Wind Harmer
0.756
965421AG1-410 GEN
Solar/Wind Harmer
17.273
270449AD2-020 GEN
Solar/Wind Harmer
1.604
943021AE2-325 GEN
Solar/Wind Harmer
2.084
945111AF1-176 GEN
Solar/Wind Harmer
9.987
957891AF2-083 GEN
Solar/Wind Harmer
8.362
24639705ELKHART HY
Adder
0.083
270216AD2-079_GEN
Solar/Wind Harmer
0.326
965011AG1-365 GEN
Solar/Wind Harmer
5.247
270317AD1-130_GEN
Solar/Wind Harmer
1.66
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270391AF1-285 GEN3
Solar/Wind Harmer
0.582
270578AF1-285 GEN2
Solar/Wind Harmer
0.582
970373AG2-245 GEN
Solar/Wind Harmer
10.003
270055AF2-134 C O1
Solar/Wind Harmer
1.416
274751CRETE EC ;1U
Adder
2.258
274754CRETE EC ;4U
Adder
2.258
958381AF2-132 GEN
Solar/Wind Harmer
4.175
964861AG1-349 GEN
Solar/Wind Harmer
3.611
971917AH1-482 GEN
Solar/Wind Harmer
4.167
274723RIVER EC ;12
Adder
8.212
274812UNIV PK N;8U
Adder
2.284
274802UNIV PARK;5U
Adder
2.63
940581AE2-045 GEN
Solar/Wind Harmer
4.578
972207SS24-0001
Solar/Wind Harmer
9.891
274773LINCOLN ;4U
Adder
2.782
274774LINCOLN ;5U
Adder
2.782
971605AH1-302 GEN
Solar/Wind Harmer
3.914
274676JOLIET 29;8U
Adder
13.659
941551AE2-152 GEN
Solar/Wind Harmer
2.017
274732ELWOOD EC;7P
Adder
7.305
274674JOLIET 9 ;6U
Adder
6.842
274871GR RIDGE ;2U
Solar/Wind Harmer
3.398
274847GR RIDGE ;BU
Solar/Wind Harmer
2.234
274745AC1-111 GEN9
Adder
2.456
274861TOP CROP ;1U
Solar/Wind Harmer
2.66
276694AA1-018 GEN2
Solar/Wind Harmer
2.771
276691AA1-018 GEN1
Solar/Wind Harmer
0.331
270024AE2-089 GEN
Solar/Wind Harmer
2.046
274682WAUKEGAN ;7U
Adder
7.842
274828WAUKEGAN ;BP
Adder
4.815
276805AD2-038 GEN
Solar/Wind Harmer
2.232
939401AE1-172 GEN
Solar/Wind Harmer
6.045
276882AE2-255 GEN
Solar/Wind Harmer
1.46
241885AC2-103 GEN1
Solar/Wind Helper
9.15
203947AF1-006 C
Solar/Wind Helper
0.375
961971AG1-040 GEN
Solar/Wind Helper
0.328
203830AF1-094 GEN
Solar/Wind Helper
0.318
203979AG1-198 GEN
Solar/Wind Helper
0.191
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
962781AG1-127 GEN
Solar/Wind Harmer
2.985
23929302BS-PKR
50/50
2.17
241832AE2-181_GEN
Solar/Wind Harmer
1.945
958321AF2-126 GEN
Solar/Wind Harmer
1.457
23906402RICHG1
Adder
1.311
23906502RICHG2&3
Adder
1.308
270541AE2-072 C
Solar/Wind Harmer
4.226
270044AE2-322 C
Solar/Wind Harmer
0.848
270588AE1-091_GEN
Solar/Wind Harmer
6.563
958091AF2-103 GEN
Solar/Wind Harmer
0.094
246938BC-WTG3
Solar/Wind Harmer
2.313
270491AE1-102 GEN2
Solar/Wind Harmer
0.756
24695305TIMB G C
Solar/Wind Harmer
1.872
945111AF1-176 GEN
Solar/Wind Harmer
3.165
270505AE1-170 C O1
Solar/Wind Harmer
8.39
270063AE2-323 C
Solar/Wind Harmer
1.185
247643Z2-116 C
Solar/Wind Harmer
0.037
965021AG1-366 GEN
Solar/Wind Harmer
1.22
24441505OLIV SLR
Solar/Wind Harmer
0.069
270043AE2-236 GEN
Solar/Wind Harmer
2.732
971347AH1-153 GEN
Solar/Wind Harmer
2.473
942871AE2-306 GEN
Solar/Wind Harmer
0.436
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
972231SS25-0005
Solar/Wind Harmer
4.383
972181SS23-001
Solar/Wind Harmer
2.74
274752CRETE EC ;2U
Adder
2.258
274753CRETE EC ;3U
Adder
2.258
964401AG1-302 GEN
Solar/Wind Harmer
4.175
274724RIVER EC ;11
Adder
8.114
274814UNIV PK N;0U
Adder
2.304
274807UNIV PK N;3U
Adder
2.299
274811UNIV PK N;7U
Adder
2.284
276164X3-005 C
Solar/Wind Harmer
0.319
274803UNIV PARK;6U
Adder
2.63
274826FISK ;BP
Adder
4.93
972038AH1-567 GEN2
Adder
0.164
274887GEN-1.85
Solar/Wind Harmer
2.392
276772AC2-154 GEN
Solar/Wind Harmer
1.253
276843GEN-1.7
Solar/Wind Harmer
0.257
276806AD2-047 C O1
Solar/Wind Harmer
4.802
274772LINCOLN ;3U
Adder
2.782
972259AH1-714 GEN
Adder
8.5
274676JOLIET 29;8U
Adder
13.171
939351AE1-166 GEN
Solar/Wind Harmer
2.637
274729ELWOOD EC;1P
Adder
7.305
274730ELWOOD EC;6P
Adder
7.305
274734ELWOOD EC;8P
Adder
7.305
274736ELWOOD EC;9P
Adder
7.305
970707AG2-453 GEN
Solar/Wind Harmer
12.441
943121AE2-341 GEN
Solar/Wind Harmer
6.588
943591AF1-030 GEN
Solar/Wind Harmer
4.392
274862TOP CROP ;2U
Solar/Wind Harmer
2.221
274682WAUKEGAN ;7U
Adder
7.842
944531AF1-118 GEN
Solar/Wind Harmer
15.178
276868AE1-113 GEN
Solar/Wind Harmer
4.381
274879MINONK ;1U
Solar/Wind Harmer
2.921
962511AG1-100 GEN
Solar/Wind Helper
0.336
270526AF1-158 GEN
Solar/Wind Harmer
2.356
270302AB2-170 GEN
Solar/Wind Harmer
4.342
971567AH1-282 GEN
Solar/Wind Harmer
2.483
960681AF2-359 GEN
Solar/Wind Harmer
1.878
963791AG1-232 GEN
Solar/Wind Harmer
6.54
270223U2-072_GEN1
Solar/Wind Harmer
0.95
270224U2-072_GEN2
Solar/Wind Harmer
0.95
270227U2-072_GEN3
Solar/Wind Harmer
0.95
270228U2-072_GEN4
Solar/Wind Harmer
0.95
270231U2-072_GEN5
Solar/Wind Harmer
0.95
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270071AF1-092 GEN
Solar/Wind Harmer
6.922
958391AF2-133 GEN
Solar/Wind Harmer
4.136
959141AF2-205 GEN
Solar/Wind Harmer
2.738
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.494
274800UNIV PARK;3U
Adder
2.621
274801UNIV PARK;4U
Adder
2.621
960591AF2-350 GEN
Solar/Wind Harmer
4.489
274775LINCOLN ;6U
Adder
2.782
274776LINCOLN ;7U
Adder
2.782
274777LINCOLN ;8U
Adder
2.782
972228AH1-698 GEN2
Adder
1.658
972227AH1-698 GEN1
Adder
1.167
274687WILL CNTY;4U
Adder
12.465
274687WILL CNTY;4U
Adder
12.465
274675JOLIET 29;7U
Adder
13.659
274675JOLIET 29;7U
Adder
13.171
276893AG1-478 C
Solar/Wind Harmer
0.244
274728ELWOOD EC;5P
Adder
7.305
274731ELWOOD EC;2P
Adder
7.305
274733ELWOOD EC;3P
Adder
7.305
274735ELWOOD EC;4P
Adder
7.305
970833AG2-524 GEN
Solar/Wind Harmer
3.86
970833AG2-524 GEN
Solar/Wind Harmer
1.795
274744AC1-111 GEN8
Adder
2.456
274746AC1-111 G10
Adder
2.456
970073AG2-061 GEN
Solar/Wind Harmer
1.012
241886AC2-103 GEN2
Solar/Wind Helper
9.15
241985AE1-237 GEN
Solar/Wind Helper
0.13
241982AE2-343 S C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
20334926Z1-069 C
Solar/Wind Helper
0.634
23867002DVBSG1
50/50
13.97
24190002OREGON_ST1
50/50
3.619
24189802OREGON_CT1
50/50
2.747
23888802TROY G4
50/50
1.812
241996AE2-282_GEN
Solar/Wind Harmer
2.143
241808AF1-120 C
Solar/Wind Harmer
1.195
247522W1-056 GEN
Solar/Wind Harmer
1.487
944231AF1-091 GEN
Solar/Wind Harmer
11.742
247607V1-011 GEN
Solar/Wind Harmer
2.305
246937BC-WTG2
Solar/Wind Harmer
2.273
942801AE2-298 GEN
Solar/Wind Harmer
0.878
961051AF2-396 GEN
Solar/Wind Harmer
9.01
961051AF2-396 GEN
Solar/Wind Harmer
4.191
247620Y3-023
Adder
0.251
270246TR4_N_V150
Solar/Wind Harmer
0.461
270247TR4_N_V136
Solar/Wind Harmer
0.461
270462AD2-086
Solar/Wind Harmer
3.606
965681AG1-436 GEN
Solar/Wind Harmer
6.213
965791AG1-447 GEN
Solar/Wind Harmer
3.179
970349AG2-230 GEN
Solar/Wind Harmer
7.419
270535AF1-215 GEN1
Solar/Wind Harmer
2.125
270536AF1-215 GEN2
Solar/Wind Harmer
2.125
274805UNIV PK N;1U
Adder
2.289
274808UNIV PK N;4U
Adder
2.274
274888KELLY CRK;1U
Solar/Wind Harmer
2.649
276776AD2-060 GEN
Solar/Wind Harmer
0.188
958011AF2-095 GEN
Solar/Wind Harmer
6.464
970941AG2-585 GEN
Solar/Wind Harmer
2.469
274770LINCOLN ;1U
Adder
2.782
274771LINCOLN ;2U
Adder
2.782
276897AD1-100 C
Solar/Wind Harmer
20.657
276893AG1-478 C
Solar/Wind Harmer
0.195
274674JOLIET 9 ;6U
Adder
6.842
942221AE2-234 GEN
Solar/Wind Harmer
1.553
958481AF2-142 GEN
Solar/Wind Harmer
6.587
945421AF1-207 GEN
Solar/Wind Harmer
6.15
957841AF2-078 GEN
Solar/Wind Harmer
2.648
274696ROCKY RD ;4P
Adder
4.971
274695ROCKY RD ;2P
Adder
4.857
274693ROCKY RD ;1P
Adder
4.809
274697ROCKY RD ;3P
Adder
1.319
274683WAUKEGAN ;8U
Adder
9.186
274683WAUKEGAN ;8U
Adder
7.744
958491AF2-143 GEN
Solar/Wind Harmer
6.528
276901AD2-066 C O1
Solar/Wind Harmer
1.521
962691AG1-118 GEN
Solar/Wind Harmer
13.01
203835AF1-098 GEN
Solar/Wind Helper
1.297
241967AE2-285_GEN
Solar/Wind Helper
0.334
241801AE1-079 GEN
Solar/Wind Helper
0.13
254304AE2-114 C
Solar/Wind Helper
0.111
254305AE2-115 C
Solar/Wind Helper
0.111
962101AG1-054 GEN
Solar/Wind Helper
0.322
203804AE2-113_GEN
Solar/Wind Helper
0.851
940863AE2-074 GEN
Solar/Wind Helper
0.221
946381AF1-302 GEN
Solar/Wind Helper
0.103
960751AF2-366 GEN
Solar/Wind Harmer
0.9
990142J1224
External Queue
13.296195983886719
990527J1329
External Queue
1.8189051151275635
991182J1586 G
External Queue
24.904010772705078
991177J1571 G
External Queue
15.21457576751709
LAGNLTFEXP_LAGN->PJM
CLTF
4.852
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.173
TVALTFEXP_TVA->PJM
CLTF
2.201
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.968
WECLTFEXP_WEC->PJM
CLTF
1.627
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.908
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.714
MECLTFEXP_MEC->PJM
CLTF
6.341
SIGELTFEXP_SIGE->PJM
CLTF
0.164
CPLELTFEXP_CPLE->PJM
CLTF
0.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.77

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-12_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-12_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.38 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2211.96
MW Contribution:
13.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.69
23888702TROY G3
50/50
1.812
972253AH1-711 GEN
50/50
55.394
23856402BAYSG1
50/50
1.231
23920202STRYCT
50/50
1.896
241858AF1-205_GEN
Solar/Wind Harmer
5.467
241840AF1-064_GEN
Solar/Wind Harmer
1.356
23906502RICHG2&3
Adder
1.308
960841AF2-375 GEN
Solar/Wind Harmer
3.489
270297AD1-101 GEN
Solar/Wind Harmer
1.367
270258AD1-119 GEN
Solar/Wind Harmer
1.261
24441205WTRV SLR C
Solar/Wind Harmer
0.081
246936BC-WTG1
Solar/Wind Harmer
2.273
270489AE1-102 GEN1
Solar/Wind Harmer
0.756
965421AG1-410 GEN
Solar/Wind Harmer
17.273
270449AD2-020 GEN
Solar/Wind Harmer
1.604
943021AE2-325 GEN
Solar/Wind Harmer
2.084
945111AF1-176 GEN
Solar/Wind Harmer
9.987
957891AF2-083 GEN
Solar/Wind Harmer
8.362
24639705ELKHART HY
Adder
0.083
270216AD2-079_GEN
Solar/Wind Harmer
0.326
965011AG1-365 GEN
Solar/Wind Harmer
5.247
270317AD1-130_GEN
Solar/Wind Harmer
1.66
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270391AF1-285 GEN3
Solar/Wind Harmer
0.582
270578AF1-285 GEN2
Solar/Wind Harmer
0.582
970373AG2-245 GEN
Solar/Wind Harmer
10.003
270055AF2-134 C O1
Solar/Wind Harmer
1.416
274751CRETE EC ;1U
Adder
2.258
274754CRETE EC ;4U
Adder
2.258
958381AF2-132 GEN
Solar/Wind Harmer
4.175
964861AG1-349 GEN
Solar/Wind Harmer
3.611
971917AH1-482 GEN
Solar/Wind Harmer
4.167
274723RIVER EC ;12
Adder
8.212
274812UNIV PK N;8U
Adder
2.284
274802UNIV PARK;5U
Adder
2.63
940581AE2-045 GEN
Solar/Wind Harmer
4.578
972207SS24-0001
Solar/Wind Harmer
9.891
274773LINCOLN ;4U
Adder
2.782
274774LINCOLN ;5U
Adder
2.782
971605AH1-302 GEN
Solar/Wind Harmer
3.914
23929302BS-PKR
50/50
2.17
241832AE2-181_GEN
Solar/Wind Harmer
1.945
958321AF2-126 GEN
Solar/Wind Harmer
1.457
23906402RICHG1
Adder
1.311
23906502RICHG2&3
Adder
1.308
270541AE2-072 C
Solar/Wind Harmer
4.226
270044AE2-322 C
Solar/Wind Harmer
0.848
270588AE1-091_GEN
Solar/Wind Harmer
6.563
958091AF2-103 GEN
Solar/Wind Harmer
0.094
246938BC-WTG3
Solar/Wind Harmer
2.313
270491AE1-102 GEN2
Solar/Wind Harmer
0.756
24695305TIMB G C
Solar/Wind Harmer
1.872
945111AF1-176 GEN
Solar/Wind Harmer
3.165
270505AE1-170 C O1
Solar/Wind Harmer
8.39
270063AE2-323 C
Solar/Wind Harmer
1.185
247643Z2-116 C
Solar/Wind Harmer
0.037
965021AG1-366 GEN
Solar/Wind Harmer
1.22
24441505OLIV SLR
Solar/Wind Harmer
0.069
270043AE2-236 GEN
Solar/Wind Harmer
2.732
971347AH1-153 GEN
Solar/Wind Harmer
2.473
942871AE2-306 GEN
Solar/Wind Harmer
0.436
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
972231SS25-0005
Solar/Wind Harmer
4.383
972181SS23-001
Solar/Wind Harmer
2.74
274752CRETE EC ;2U
Adder
2.258
274753CRETE EC ;3U
Adder
2.258
964401AG1-302 GEN
Solar/Wind Harmer
4.175
274724RIVER EC ;11
Adder
8.114
274814UNIV PK N;0U
Adder
2.304
274807UNIV PK N;3U
Adder
2.299
274811UNIV PK N;7U
Adder
2.284
276164X3-005 C
Solar/Wind Harmer
0.319
274803UNIV PARK;6U
Adder
2.63
274826FISK ;BP
Adder
4.93
972038AH1-567 GEN2
Adder
0.164
274887GEN-1.85
Solar/Wind Harmer
2.392
276772AC2-154 GEN
Solar/Wind Harmer
1.253
276843GEN-1.7
Solar/Wind Harmer
0.257
276806AD2-047 C O1
Solar/Wind Harmer
4.802
274772LINCOLN ;3U
Adder
2.782
23888502TROY G1
50/50
1.812
23888602TROY G2
50/50
1.812
945411AF1-206 GEN
Solar/Wind Harmer
8.027
945641AF1-229 GEN
Solar/Wind Harmer
3.439
270361_3
Solar/Wind Harmer
7.851
270575GUS2 35KV
Solar/Wind Harmer
9.25
270499AE1-146 GEN
Solar/Wind Harmer
2.194
971549AH1-272 GEN
Solar/Wind Harmer
13.002
270404AC1-167 GEN
Solar/Wind Harmer
0.699
270007AE1-245 C
Solar/Wind Harmer
3.149
957201AF2-014 GEN
Solar/Wind Harmer
2.636
270435AC2-044 GEN
Solar/Wind Harmer
1.162
944161AF1-084 GEN
Solar/Wind Harmer
1.282
966831AG1-554 GEN
Solar/Wind Harmer
0.674
965041AG1-368 GEN
Solar/Wind Harmer
5.454
247521TR3_G114
Solar/Wind Harmer
1.821
270191TR4_S_V150
Solar/Wind Harmer
1.625
965051AG1-369 GEN
Solar/Wind Harmer
2.706
970031AG2-029 GEN
Solar/Wind Harmer
13.45
971771AH1-392 GEN
Solar/Wind Harmer
4.772
959331AF2-224 GEN
Solar/Wind Harmer
5.247
270526AF1-158 GEN
Solar/Wind Harmer
2.356
270302AB2-170 GEN
Solar/Wind Harmer
4.342
971567AH1-282 GEN
Solar/Wind Harmer
2.483
960681AF2-359 GEN
Solar/Wind Harmer
1.878
963791AG1-232 GEN
Solar/Wind Harmer
6.54
270223U2-072_GEN1
Solar/Wind Harmer
0.95
270224U2-072_GEN2
Solar/Wind Harmer
0.95
270227U2-072_GEN3
Solar/Wind Harmer
0.95
270228U2-072_GEN4
Solar/Wind Harmer
0.95
270231U2-072_GEN5
Solar/Wind Harmer
0.95
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270071AF1-092 GEN
Solar/Wind Harmer
6.922
958391AF2-133 GEN
Solar/Wind Harmer
4.136
959141AF2-205 GEN
Solar/Wind Harmer
2.738
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.494
274800UNIV PARK;3U
Adder
2.621
274801UNIV PARK;4U
Adder
2.621
960591AF2-350 GEN
Solar/Wind Harmer
4.489
274775LINCOLN ;6U
Adder
2.782
274776LINCOLN ;7U
Adder
2.782
274777LINCOLN ;8U
Adder
2.782
972228AH1-698 GEN2
Adder
1.658
972227AH1-698 GEN1
Adder
1.167
23867002DVBSG1
50/50
13.97
24190002OREGON_ST1
50/50
3.619
24189802OREGON_CT1
50/50
2.747
23888802TROY G4
50/50
1.812
241996AE2-282_GEN
Solar/Wind Harmer
2.143
241808AF1-120 C
Solar/Wind Harmer
1.195
247522W1-056 GEN
Solar/Wind Harmer
1.487
944231AF1-091 GEN
Solar/Wind Harmer
11.742
247607V1-011 GEN
Solar/Wind Harmer
2.305
246937BC-WTG2
Solar/Wind Harmer
2.273
942801AE2-298 GEN
Solar/Wind Harmer
0.878
961051AF2-396 GEN
Solar/Wind Harmer
9.01
961051AF2-396 GEN
Solar/Wind Harmer
4.191
247620Y3-023
Adder
0.251
270246TR4_N_V150
Solar/Wind Harmer
0.461
270247TR4_N_V136
Solar/Wind Harmer
0.461
270462AD2-086
Solar/Wind Harmer
3.606
965681AG1-436 GEN
Solar/Wind Harmer
6.213
965791AG1-447 GEN
Solar/Wind Harmer
3.179
970349AG2-230 GEN
Solar/Wind Harmer
7.419
270535AF1-215 GEN1
Solar/Wind Harmer
2.125
270536AF1-215 GEN2
Solar/Wind Harmer
2.125
274805UNIV PK N;1U
Adder
2.289
274808UNIV PK N;4U
Adder
2.274
274888KELLY CRK;1U
Solar/Wind Harmer
2.649
276776AD2-060 GEN
Solar/Wind Harmer
0.188
958011AF2-095 GEN
Solar/Wind Harmer
6.464
970941AG2-585 GEN
Solar/Wind Harmer
2.469
274770LINCOLN ;1U
Adder
2.782
274771LINCOLN ;2U
Adder
2.782
972259AH1-714 GEN
Adder
8.5
274676JOLIET 29;8U
Adder
13.171
939351AE1-166 GEN
Solar/Wind Harmer
2.637
274729ELWOOD EC;1P
Adder
7.305
274730ELWOOD EC;6P
Adder
7.305
274734ELWOOD EC;8P
Adder
7.305
274736ELWOOD EC;9P
Adder
7.305
970707AG2-453 GEN
Solar/Wind Harmer
12.441
943121AE2-341 GEN
Solar/Wind Harmer
6.588
943591AF1-030 GEN
Solar/Wind Harmer
4.392
274862TOP CROP ;2U
Solar/Wind Harmer
2.221
274682WAUKEGAN ;7U
Adder
7.842
944531AF1-118 GEN
Solar/Wind Harmer
15.178
276868AE1-113 GEN
Solar/Wind Harmer
4.381
274879MINONK ;1U
Solar/Wind Harmer
2.921
962511AG1-100 GEN
Solar/Wind Helper
0.336
274687WILL CNTY;4U
Adder
12.465
274687WILL CNTY;4U
Adder
12.465
274675JOLIET 29;7U
Adder
13.659
274675JOLIET 29;7U
Adder
13.171
276893AG1-478 C
Solar/Wind Harmer
0.244
274728ELWOOD EC;5P
Adder
7.305
274731ELWOOD EC;2P
Adder
7.305
274733ELWOOD EC;3P
Adder
7.305
274735ELWOOD EC;4P
Adder
7.305
970833AG2-524 GEN
Solar/Wind Harmer
3.86
970833AG2-524 GEN
Solar/Wind Harmer
1.795
274744AC1-111 GEN8
Adder
2.456
274746AC1-111 G10
Adder
2.456
970073AG2-061 GEN
Solar/Wind Harmer
1.012
241886AC2-103 GEN2
Solar/Wind Helper
9.15
241985AE1-237 GEN
Solar/Wind Helper
0.13
241982AE2-343 S C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
20334926Z1-069 C
Solar/Wind Helper
0.634
274676JOLIET 29;8U
Adder
13.659
941551AE2-152 GEN
Solar/Wind Harmer
2.017
274732ELWOOD EC;7P
Adder
7.305
274674JOLIET 9 ;6U
Adder
6.842
274871GR RIDGE ;2U
Solar/Wind Harmer
3.398
274847GR RIDGE ;BU
Solar/Wind Harmer
2.234
274745AC1-111 GEN9
Adder
2.456
274861TOP CROP ;1U
Solar/Wind Harmer
2.66
276694AA1-018 GEN2
Solar/Wind Harmer
2.771
276691AA1-018 GEN1
Solar/Wind Harmer
0.331
270024AE2-089 GEN
Solar/Wind Harmer
2.046
274682WAUKEGAN ;7U
Adder
7.842
274828WAUKEGAN ;BP
Adder
4.815
276805AD2-038 GEN
Solar/Wind Harmer
2.232
939401AE1-172 GEN
Solar/Wind Harmer
6.045
276882AE2-255 GEN
Solar/Wind Harmer
1.46
241885AC2-103 GEN1
Solar/Wind Helper
9.15
203947AF1-006 C
Solar/Wind Helper
0.375
961971AG1-040 GEN
Solar/Wind Helper
0.328
203830AF1-094 GEN
Solar/Wind Helper
0.318
203979AG1-198 GEN
Solar/Wind Helper
0.191
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
962781AG1-127 GEN
Solar/Wind Harmer
2.985
276897AD1-100 C
Solar/Wind Harmer
20.657
276893AG1-478 C
Solar/Wind Harmer
0.195
274674JOLIET 9 ;6U
Adder
6.842
942221AE2-234 GEN
Solar/Wind Harmer
1.553
958481AF2-142 GEN
Solar/Wind Harmer
6.587
945421AF1-207 GEN
Solar/Wind Harmer
6.15
957841AF2-078 GEN
Solar/Wind Harmer
2.648
274696ROCKY RD ;4P
Adder
4.971
274695ROCKY RD ;2P
Adder
4.857
274693ROCKY RD ;1P
Adder
4.809
274697ROCKY RD ;3P
Adder
1.319
274683WAUKEGAN ;8U
Adder
9.186
274683WAUKEGAN ;8U
Adder
7.744
958491AF2-143 GEN
Solar/Wind Harmer
6.528
276901AD2-066 C O1
Solar/Wind Harmer
1.521
962691AG1-118 GEN
Solar/Wind Harmer
13.01
203835AF1-098 GEN
Solar/Wind Helper
1.297
241967AE2-285_GEN
Solar/Wind Helper
0.334
241801AE1-079 GEN
Solar/Wind Helper
0.13
254304AE2-114 C
Solar/Wind Helper
0.111
254305AE2-115 C
Solar/Wind Helper
0.111
962101AG1-054 GEN
Solar/Wind Helper
0.322
203804AE2-113_GEN
Solar/Wind Helper
0.851
940863AE2-074 GEN
Solar/Wind Helper
0.221
946381AF1-302 GEN
Solar/Wind Helper
0.103
960751AF2-366 GEN
Solar/Wind Harmer
0.9
990142J1224
External Queue
13.296195983886719
990527J1329
External Queue
1.8189051151275635
991182J1586 G
External Queue
24.904010772705078
991177J1571 G
External Queue
15.21457576751709
LAGNLTFEXP_LAGN->PJM
CLTF
4.852
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.173
TVALTFEXP_TVA->PJM
CLTF
2.201
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.968
WECLTFEXP_WEC->PJM
CLTF
1.627
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.908
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.714
MECLTFEXP_MEC->PJM
CLTF
6.341
SIGELTFEXP_SIGE->PJM
CLTF
0.164
CPLELTFEXP_CPLE->PJM
CLTF
0.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.77

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.38 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2162.49
MW Contribution:
12.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.267
241832AE2-181_GEN
Solar/Wind Harmer
1.956
958321AF2-126 GEN
Solar/Wind Harmer
1.494
23906402RICHG1
Adder
1.323
23906502RICHG2&3
Adder
1.32
270541AE2-072 C
Solar/Wind Harmer
4.323
270044AE2-322 C
Solar/Wind Harmer
0.855
270588AE1-091_GEN
Solar/Wind Harmer
6.816
958091AF2-103 GEN
Solar/Wind Harmer
0.095
246938BC-WTG3
Solar/Wind Harmer
2.317
270491AE1-102 GEN2
Solar/Wind Harmer
0.757
23888502TROY G1
50/50
1.764
23888602TROY G2
50/50
1.764
945411AF1-206 GEN
Solar/Wind Harmer
8.075
270361_3
Solar/Wind Harmer
8.499
270575GUS2 35KV
Solar/Wind Harmer
10.012
945641AF1-229 GEN
Solar/Wind Harmer
3.441
270499AE1-146 GEN
Solar/Wind Harmer
2.357
971549AH1-272 GEN
Solar/Wind Harmer
12.828
270404AC1-167 GEN
Solar/Wind Harmer
0.705
966831AG1-554 GEN
Solar/Wind Harmer
0.708
270007AE1-245 C
Solar/Wind Harmer
3.175
957201AF2-014 GEN
Solar/Wind Harmer
2.641
270435AC2-044 GEN
Solar/Wind Harmer
1.165
24189902OREGON_CT2
50/50
2.597
23888702TROY G3
50/50
1.764
972253AH1-711 GEN
50/50
53.94
23856402BAYSG1
50/50
1.286
23920202STRYCT
50/50
1.908
241858AF1-205_GEN
Solar/Wind Harmer
5.508
241840AF1-064_GEN
Solar/Wind Harmer
1.39
23906502RICHG2&3
Adder
1.32
960841AF2-375 GEN
Solar/Wind Harmer
3.764
23867002DVBSG1
50/50
12.9
24190002OREGON_ST1
50/50
3.495
24189802OREGON_CT1
50/50
2.652
23888802TROY G4
50/50
1.764
241996AE2-282_GEN
Solar/Wind Harmer
2.156
241808AF1-120 C
Solar/Wind Harmer
1.202
247522W1-056 GEN
Solar/Wind Harmer
1.577
944231AF1-091 GEN
Solar/Wind Harmer
11.764
247607V1-011 GEN
Solar/Wind Harmer
2.324
942801AE2-298 GEN
Solar/Wind Harmer
0.885
246937BC-WTG2
Solar/Wind Harmer
2.278
961051AF2-396 GEN
Solar/Wind Harmer
8.923
961051AF2-396 GEN
Solar/Wind Harmer
4.15
270246TR4_N_V150
Solar/Wind Harmer
0.462
270247TR4_N_V136
Solar/Wind Harmer
0.462
247620Y3-023
Adder
0.249
270462AD2-086
Solar/Wind Harmer
3.631
965681AG1-436 GEN
Solar/Wind Harmer
6.163
965791AG1-447 GEN
Solar/Wind Harmer
3.153
970349AG2-230 GEN
Solar/Wind Harmer
7.362
270535AF1-215 GEN1
Solar/Wind Harmer
2.109
270536AF1-215 GEN2
Solar/Wind Harmer
2.109
274805UNIV PK N;1U
Adder
2.274
274808UNIV PK N;4U
Adder
2.259
274888KELLY CRK;1U
Solar/Wind Harmer
2.631
276776AD2-060 GEN
Solar/Wind Harmer
0.187
958011AF2-095 GEN
Solar/Wind Harmer
6.421
970941AG2-585 GEN
Solar/Wind Harmer
2.452
274770LINCOLN ;1U
Adder
2.763
274771LINCOLN ;2U
Adder
2.763
942221AE2-234 GEN
Solar/Wind Harmer
1.551
276897AD1-100 C
Solar/Wind Harmer
20.52
276893AG1-478 C
Solar/Wind Harmer
0.194
274674JOLIET 9 ;6U
Adder
6.796
958481AF2-142 GEN
Solar/Wind Harmer
6.543
945421AF1-207 GEN
Solar/Wind Harmer
6.113
957841AF2-078 GEN
Solar/Wind Harmer
2.631
274696ROCKY RD ;4P
Adder
4.939
274695ROCKY RD ;2P
Adder
4.825
274693ROCKY RD ;1P
Adder
4.778
274697ROCKY RD ;3P
Adder
1.311
274683WAUKEGAN ;8U
Adder
9.126
274683WAUKEGAN ;8U
Adder
7.693
958491AF2-143 GEN
Solar/Wind Harmer
6.486
276901AD2-066 C O1
Solar/Wind Harmer
1.512
962691AG1-118 GEN
Solar/Wind Harmer
12.926
24695305TIMB G C
Solar/Wind Harmer
1.881
945111AF1-176 GEN
Solar/Wind Harmer
3.136
270505AE1-170 C O1
Solar/Wind Harmer
8.31
270063AE2-323 C
Solar/Wind Harmer
1.179
247643Z2-116 C
Solar/Wind Harmer
0.037
965021AG1-366 GEN
Solar/Wind Harmer
1.219
24441505OLIV SLR
Solar/Wind Harmer
0.069
270043AE2-236 GEN
Solar/Wind Harmer
2.721
971347AH1-153 GEN
Solar/Wind Harmer
2.454
942871AE2-306 GEN
Solar/Wind Harmer
0.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.225
972231SS25-0005
Solar/Wind Harmer
4.352
972181SS23-001
Solar/Wind Harmer
2.72
274752CRETE EC ;2U
Adder
2.242
274753CRETE EC ;3U
Adder
2.242
964401AG1-302 GEN
Solar/Wind Harmer
4.146
274724RIVER EC ;11
Adder
8.057
274814UNIV PK N;0U
Adder
2.288
274807UNIV PK N;3U
Adder
2.284
274811UNIV PK N;7U
Adder
2.269
276164X3-005 C
Solar/Wind Harmer
0.317
274803UNIV PARK;6U
Adder
2.612
274826FISK ;BP
Adder
4.897
972038AH1-567 GEN2
Adder
0.163
274887GEN-1.85
Solar/Wind Harmer
2.376
276772AC2-154 GEN
Solar/Wind Harmer
1.244
276843GEN-1.7
Solar/Wind Harmer
0.256
276806AD2-047 C O1
Solar/Wind Harmer
4.77
274772LINCOLN ;3U
Adder
2.763
972259AH1-714 GEN
Adder
8.443
274676JOLIET 29;8U
Adder
13.083
939351AE1-166 GEN
Solar/Wind Harmer
2.62
274730ELWOOD EC;6P
Adder
7.256
274734ELWOOD EC;8P
Adder
7.256
274736ELWOOD EC;9P
Adder
7.256
970707AG2-453 GEN
Solar/Wind Harmer
12.358
274729ELWOOD EC;1P
Adder
7.256
943121AE2-341 GEN
Solar/Wind Harmer
6.545
943591AF1-030 GEN
Solar/Wind Harmer
4.363
274862TOP CROP ;2U
Solar/Wind Harmer
2.206
274682WAUKEGAN ;7U
Adder
7.791
944531AF1-118 GEN
Solar/Wind Harmer
15.14
276868AE1-113 GEN
Solar/Wind Harmer
4.353
944161AF1-084 GEN
Solar/Wind Harmer
1.269
270428AC2-015 C
Solar/Wind Harmer
3.097
965041AG1-368 GEN
Solar/Wind Harmer
5.468
247521TR3_G114
Solar/Wind Harmer
1.828
270191TR4_S_V150
Solar/Wind Harmer
1.631
965051AG1-369 GEN
Solar/Wind Harmer
2.716
970031AG2-029 GEN
Solar/Wind Harmer
13.369
971771AH1-392 GEN
Solar/Wind Harmer
4.731
959331AF2-224 GEN
Solar/Wind Harmer
5.241
270302AB2-170 GEN
Solar/Wind Harmer
4.372
270526AF1-158 GEN
Solar/Wind Harmer
2.336
971567AH1-282 GEN
Solar/Wind Harmer
2.531
960681AF2-359 GEN
Solar/Wind Harmer
1.863
270223U2-072_GEN1
Solar/Wind Harmer
0.957
270224U2-072_GEN2
Solar/Wind Harmer
0.957
270227U2-072_GEN3
Solar/Wind Harmer
0.957
270228U2-072_GEN4
Solar/Wind Harmer
0.957
270231U2-072_GEN5
Solar/Wind Harmer
0.957
270578AF1-285 GEN2
Solar/Wind Harmer
0.225
963791AG1-232 GEN
Solar/Wind Harmer
6.536
270377AD1-106 GEN
Solar/Wind Harmer
2.448
270071AF1-092 GEN
Solar/Wind Harmer
6.899
958391AF2-133 GEN
Solar/Wind Harmer
4.108
959141AF2-205 GEN
Solar/Wind Harmer
2.72
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.47
274800UNIV PARK;3U
Adder
2.604
274801UNIV PARK;4U
Adder
2.604
960591AF2-350 GEN
Solar/Wind Harmer
4.459
274775LINCOLN ;6U
Adder
2.763
274776LINCOLN ;7U
Adder
2.763
274777LINCOLN ;8U
Adder
2.763
972228AH1-698 GEN2
Adder
1.647
972227AH1-698 GEN1
Adder
1.159
274687WILL CNTY;4U
Adder
12.382
274687WILL CNTY;4U
Adder
12.382
274675JOLIET 29;7U
Adder
13.567
274675JOLIET 29;7U
Adder
13.083
276893AG1-478 C
Solar/Wind Harmer
0.243
274728ELWOOD EC;5P
Adder
7.256
274731ELWOOD EC;2P
Adder
7.256
274733ELWOOD EC;3P
Adder
7.256
274735ELWOOD EC;4P
Adder
7.256
970833AG2-524 GEN
Solar/Wind Harmer
3.835
970833AG2-524 GEN
Solar/Wind Harmer
1.784
274744AC1-111 GEN8
Adder
2.44
274746AC1-111 G10
Adder
2.44
970073AG2-061 GEN
Solar/Wind Harmer
1.006
241886AC2-103 GEN2
Solar/Wind Helper
9.445
241807AE2-176_GEN
Solar/Wind Harmer
2.786
270297AD1-101 GEN
Solar/Wind Harmer
1.392
270258AD1-119 GEN
Solar/Wind Harmer
1.27
24441205WTRV SLR C
Solar/Wind Harmer
0.08
246936BC-WTG1
Solar/Wind Harmer
2.278
270489AE1-102 GEN1
Solar/Wind Harmer
0.757
965421AG1-410 GEN
Solar/Wind Harmer
17.304
270449AD2-020 GEN
Solar/Wind Harmer
1.588
943021AE2-325 GEN
Solar/Wind Harmer
2.063
945111AF1-176 GEN
Solar/Wind Harmer
9.895
957891AF2-083 GEN
Solar/Wind Harmer
8.284
24639705ELKHART HY
Adder
0.083
270216AD2-079_GEN
Solar/Wind Harmer
0.323
965011AG1-365 GEN
Solar/Wind Harmer
5.241
270317AD1-130_GEN
Solar/Wind Harmer
1.672
270485AE1-090_GEN
Solar/Wind Harmer
0.316
270391AF1-285 GEN3
Solar/Wind Harmer
0.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.586
970373AG2-245 GEN
Solar/Wind Harmer
9.93
270055AF2-134 C O1
Solar/Wind Harmer
1.406
274751CRETE EC ;1U
Adder
2.242
274754CRETE EC ;4U
Adder
2.242
958381AF2-132 GEN
Solar/Wind Harmer
4.146
964861AG1-349 GEN
Solar/Wind Harmer
3.587
971917AH1-482 GEN
Solar/Wind Harmer
4.138
274723RIVER EC ;12
Adder
8.155
274812UNIV PK N;8U
Adder
2.269
274802UNIV PARK;5U
Adder
2.612
940581AE2-045 GEN
Solar/Wind Harmer
4.548
971605AH1-302 GEN
Solar/Wind Harmer
3.889
972207SS24-0001
Solar/Wind Harmer
9.825
274773LINCOLN ;4U
Adder
2.763
274774LINCOLN ;5U
Adder
2.763
274676JOLIET 29;8U
Adder
13.567
941551AE2-152 GEN
Solar/Wind Harmer
2.003
274732ELWOOD EC;7P
Adder
7.256
274674JOLIET 9 ;6U
Adder
6.796
274871GR RIDGE ;2U
Solar/Wind Harmer
3.375
274847GR RIDGE ;BU
Solar/Wind Harmer
2.219
274745AC1-111 GEN9
Adder
2.44
276694AA1-018 GEN2
Solar/Wind Harmer
2.752
276691AA1-018 GEN1
Solar/Wind Harmer
0.329
274861TOP CROP ;1U
Solar/Wind Harmer
2.642
270024AE2-089 GEN
Solar/Wind Harmer
2.044
274682WAUKEGAN ;7U
Adder
7.791
274828WAUKEGAN ;BP
Adder
4.784
276805AD2-038 GEN
Solar/Wind Harmer
2.217
939401AE1-172 GEN
Solar/Wind Harmer
6.006
241885AC2-103 GEN1
Solar/Wind Helper
9.445
962511AG1-100 GEN
Solar/Wind Helper
0.339
274879MINONK ;1U
Solar/Wind Harmer
1.978
203947AF1-006 C
Solar/Wind Helper
0.378
961971AG1-040 GEN
Solar/Wind Helper
0.332
203830AF1-094 GEN
Solar/Wind Helper
0.322
203979AG1-198 GEN
Solar/Wind Helper
0.193
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
241985AE1-237 GEN
Solar/Wind Helper
0.131
241982AE2-343 S C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.129
20334926Z1-069 C
Solar/Wind Helper
0.639
203835AF1-098 GEN
Solar/Wind Helper
1.31
241967AE2-285_GEN
Solar/Wind Helper
0.336
241801AE1-079 GEN
Solar/Wind Helper
0.131
254304AE2-114 C
Solar/Wind Helper
0.112
254305AE2-115 C
Solar/Wind Helper
0.112
962101AG1-054 GEN
Solar/Wind Helper
0.324
203804AE2-113_GEN
Solar/Wind Helper
0.859
940863AE2-074 GEN
Solar/Wind Helper
0.223
946381AF1-302 GEN
Solar/Wind Helper
0.104
990142J1224
External Queue
12.977669715881348
990527J1329
External Queue
1.7753312587738037
991182J1586 G
External Queue
24.28106117248535
991177J1571 G
External Queue
14.958016395568848
LAGNLTFEXP_LAGN->PJM
CLTF
4.836
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.166
TVALTFEXP_TVA->PJM
CLTF
2.195
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
1.968
WECLTFEXP_WEC->PJM
CLTF
1.617
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.583
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.697
MECLTFEXP_MEC->PJM
CLTF
6.305
SIGELTFEXP_SIGE->PJM
CLTF
0.164
CPLELTFEXP_CPLE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.632

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B2_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B2_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.53 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2132.01
MW Contribution:
12.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
1.918
958321AF2-126 GEN
Solar/Wind Harmer
1.434
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.29
270541AE2-072 C
Solar/Wind Harmer
4.158
270044AE2-322 C
Solar/Wind Harmer
0.836
270588AE1-091_GEN
Solar/Wind Harmer
6.445
958091AF2-103 GEN
Solar/Wind Harmer
0.093
246938BC-WTG3
Solar/Wind Harmer
2.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.745
945111AF1-176 GEN
Solar/Wind Harmer
3.127
24695305TIMB G C
Solar/Wind Harmer
1.846
270505AE1-170 C O1
Solar/Wind Harmer
8.289
270063AE2-323 C
Solar/Wind Harmer
1.171
247643Z2-116 C
Solar/Wind Harmer
0.037
965021AG1-366 GEN
Solar/Wind Harmer
1.204
24441505OLIV SLR
Solar/Wind Harmer
0.068
270043AE2-236 GEN
Solar/Wind Harmer
2.697
971347AH1-153 GEN
Solar/Wind Harmer
2.443
942871AE2-306 GEN
Solar/Wind Harmer
0.43
270391AF1-285 GEN3
Solar/Wind Harmer
0.221
972231SS25-0005
Solar/Wind Harmer
4.33
972181SS23-001
Solar/Wind Harmer
2.706
274752CRETE EC ;2U
Adder
2.23
274753CRETE EC ;3U
Adder
2.23
964401AG1-302 GEN
Solar/Wind Harmer
4.124
274724RIVER EC ;11
Adder
8.014
274814UNIV PK N;0U
Adder
2.276
274807UNIV PK N;3U
Adder
2.271
274811UNIV PK N;7U
Adder
2.256
276164X3-005 C
Solar/Wind Harmer
0.315
274803UNIV PARK;6U
Adder
2.598
274826FISK ;BP
Adder
4.869
972038AH1-567 GEN2
Adder
0.162
274887GEN-1.85
Solar/Wind Harmer
2.362
276772AC2-154 GEN
Solar/Wind Harmer
1.237
276843GEN-1.7
Solar/Wind Harmer
0.254
276806AD2-047 C O1
Solar/Wind Harmer
4.743
274772LINCOLN ;3U
Adder
2.748
972259AH1-714 GEN
Adder
8.395
274676JOLIET 29;8U
Adder
13.009
939351AE1-166 GEN
Solar/Wind Harmer
2.605
970707AG2-453 GEN
Solar/Wind Harmer
12.288
23888502TROY G1
50/50
1.794
23888602TROY G2
50/50
1.794
945411AF1-206 GEN
Solar/Wind Harmer
7.915
945641AF1-229 GEN
Solar/Wind Harmer
3.393
270361_3
Solar/Wind Harmer
7.665
270575GUS2 35KV
Solar/Wind Harmer
9.03
270499AE1-146 GEN
Solar/Wind Harmer
2.144
971549AH1-272 GEN
Solar/Wind Harmer
12.854
270404AC1-167 GEN
Solar/Wind Harmer
0.689
270007AE1-245 C
Solar/Wind Harmer
3.104
944161AF1-084 GEN
Solar/Wind Harmer
1.267
957201AF2-014 GEN
Solar/Wind Harmer
2.6
270435AC2-044 GEN
Solar/Wind Harmer
1.147
966831AG1-554 GEN
Solar/Wind Harmer
0.661
965041AG1-368 GEN
Solar/Wind Harmer
5.38
247521TR3_G114
Solar/Wind Harmer
1.797
270191TR4_S_V150
Solar/Wind Harmer
1.603
965051AG1-369 GEN
Solar/Wind Harmer
2.669
970031AG2-029 GEN
Solar/Wind Harmer
13.283
971771AH1-392 GEN
Solar/Wind Harmer
4.714
959331AF2-224 GEN
Solar/Wind Harmer
5.179
270526AF1-158 GEN
Solar/Wind Harmer
2.328
270302AB2-170 GEN
Solar/Wind Harmer
4.281
960681AF2-359 GEN
Solar/Wind Harmer
1.855
971567AH1-282 GEN
Solar/Wind Harmer
2.445
963791AG1-232 GEN
Solar/Wind Harmer
6.455
270223U2-072_GEN1
Solar/Wind Harmer
0.936
270224U2-072_GEN2
Solar/Wind Harmer
0.936
270227U2-072_GEN3
Solar/Wind Harmer
0.936
270228U2-072_GEN4
Solar/Wind Harmer
0.936
270231U2-072_GEN5
Solar/Wind Harmer
0.936
270578AF1-285 GEN2
Solar/Wind Harmer
0.221
270071AF1-092 GEN
Solar/Wind Harmer
6.833
958391AF2-133 GEN
Solar/Wind Harmer
4.085
959141AF2-205 GEN
Solar/Wind Harmer
2.704
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.451
274800UNIV PARK;3U
Adder
2.589
274801UNIV PARK;4U
Adder
2.589
960591AF2-350 GEN
Solar/Wind Harmer
4.434
274775LINCOLN ;6U
Adder
2.748
274776LINCOLN ;7U
Adder
2.748
274777LINCOLN ;8U
Adder
2.748
972228AH1-698 GEN2
Adder
1.637
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.312
274687WILL CNTY;4U
Adder
12.312
274675JOLIET 29;7U
Adder
13.491
274675JOLIET 29;7U
Adder
13.009
276893AG1-478 C
Solar/Wind Harmer
0.241
274728ELWOOD EC;5P
Adder
7.215
274731ELWOOD EC;2P
Adder
7.215
274733ELWOOD EC;3P
Adder
7.215
274735ELWOOD EC;4P
Adder
7.215
970833AG2-524 GEN
Solar/Wind Harmer
3.813
970833AG2-524 GEN
Solar/Wind Harmer
1.773
274744AC1-111 GEN8
Adder
2.426
274746AC1-111 G10
Adder
2.426
241886AC2-103 GEN2
Solar/Wind Helper
9.125
241985AE1-237 GEN
Solar/Wind Helper
0.128
241982AE2-343 S C
Solar/Wind Helper
0.115
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
274729ELWOOD EC;1P
Adder
7.215
274730ELWOOD EC;6P
Adder
7.215
274734ELWOOD EC;8P
Adder
7.215
274736ELWOOD EC;9P
Adder
7.215
943121AE2-341 GEN
Solar/Wind Harmer
6.507
943591AF1-030 GEN
Solar/Wind Harmer
4.338
274862TOP CROP ;2U
Solar/Wind Harmer
2.193
274682WAUKEGAN ;7U
Adder
7.745
962511AG1-100 GEN
Solar/Wind Helper
0.331
23867002DVBSG1
50/50
13.924
24190002OREGON_ST1
50/50
3.587
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.794
241996AE2-282_GEN
Solar/Wind Harmer
2.114
241808AF1-120 C
Solar/Wind Harmer
1.179
247522W1-056 GEN
Solar/Wind Harmer
1.455
944231AF1-091 GEN
Solar/Wind Harmer
11.584
247607V1-011 GEN
Solar/Wind Harmer
2.272
246937BC-WTG2
Solar/Wind Harmer
2.243
942801AE2-298 GEN
Solar/Wind Harmer
0.865
961051AF2-396 GEN
Solar/Wind Harmer
8.902
961051AF2-396 GEN
Solar/Wind Harmer
4.141
247620Y3-023
Adder
0.248
270246TR4_N_V150
Solar/Wind Harmer
0.455
270247TR4_N_V136
Solar/Wind Harmer
0.455
270462AD2-086
Solar/Wind Harmer
3.556
965681AG1-436 GEN
Solar/Wind Harmer
6.137
965791AG1-447 GEN
Solar/Wind Harmer
3.14
970349AG2-230 GEN
Solar/Wind Harmer
7.328
270535AF1-215 GEN1
Solar/Wind Harmer
2.099
270536AF1-215 GEN2
Solar/Wind Harmer
2.099
274805UNIV PK N;1U
Adder
2.261
274808UNIV PK N;4U
Adder
2.247
274888KELLY CRK;1U
Solar/Wind Harmer
2.617
276776AD2-060 GEN
Solar/Wind Harmer
0.186
958011AF2-095 GEN
Solar/Wind Harmer
6.385
970941AG2-585 GEN
Solar/Wind Harmer
2.439
274770LINCOLN ;1U
Adder
2.748
274771LINCOLN ;2U
Adder
2.748
276897AD1-100 C
Solar/Wind Harmer
20.403
276893AG1-478 C
Solar/Wind Harmer
0.192
274674JOLIET 9 ;6U
Adder
6.758
942221AE2-234 GEN
Solar/Wind Harmer
1.533
958481AF2-142 GEN
Solar/Wind Harmer
6.506
945421AF1-207 GEN
Solar/Wind Harmer
6.074
24189902OREGON_CT2
50/50
2.666
23888702TROY G3
50/50
1.794
972253AH1-711 GEN
50/50
54.851
23856402BAYSG1
50/50
1.208
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
5.389
241840AF1-064_GEN
Solar/Wind Harmer
1.334
23906502RICHG2&3
Adder
1.29
960841AF2-375 GEN
Solar/Wind Harmer
3.407
270297AD1-101 GEN
Solar/Wind Harmer
1.345
270258AD1-119 GEN
Solar/Wind Harmer
1.243
24441205WTRV SLR C
Solar/Wind Harmer
0.08
246936BC-WTG1
Solar/Wind Harmer
2.243
270489AE1-102 GEN1
Solar/Wind Harmer
0.745
965421AG1-410 GEN
Solar/Wind Harmer
17.041
270449AD2-020 GEN
Solar/Wind Harmer
1.585
943021AE2-325 GEN
Solar/Wind Harmer
2.059
945111AF1-176 GEN
Solar/Wind Harmer
9.868
957891AF2-083 GEN
Solar/Wind Harmer
8.262
24639705ELKHART HY
Adder
0.082
270216AD2-079_GEN
Solar/Wind Harmer
0.322
965011AG1-365 GEN
Solar/Wind Harmer
5.179
270317AD1-130_GEN
Solar/Wind Harmer
1.637
270485AE1-090_GEN
Solar/Wind Harmer
0.309
270391AF1-285 GEN3
Solar/Wind Harmer
0.573
270578AF1-285 GEN2
Solar/Wind Harmer
0.573
970373AG2-245 GEN
Solar/Wind Harmer
9.881
270055AF2-134 C O1
Solar/Wind Harmer
1.399
274751CRETE EC ;1U
Adder
2.23
274754CRETE EC ;4U
Adder
2.23
958381AF2-132 GEN
Solar/Wind Harmer
4.124
964861AG1-349 GEN
Solar/Wind Harmer
3.567
971917AH1-482 GEN
Solar/Wind Harmer
4.115
274723RIVER EC ;12
Adder
8.111
274812UNIV PK N;8U
Adder
2.256
274802UNIV PARK;5U
Adder
2.598
940581AE2-045 GEN
Solar/Wind Harmer
4.521
972207SS24-0001
Solar/Wind Harmer
9.769
274773LINCOLN ;4U
Adder
2.748
274774LINCOLN ;5U
Adder
2.748
971605AH1-302 GEN
Solar/Wind Harmer
3.866
274676JOLIET 29;8U
Adder
13.491
941551AE2-152 GEN
Solar/Wind Harmer
1.992
957841AF2-078 GEN
Solar/Wind Harmer
2.615
274695ROCKY RD ;2P
Adder
4.797
274693ROCKY RD ;1P
Adder
4.75
274697ROCKY RD ;3P
Adder
1.303
274696ROCKY RD ;4P
Adder
4.91
274683WAUKEGAN ;8U
Adder
9.073
274683WAUKEGAN ;8U
Adder
7.648
203835AF1-098 GEN
Solar/Wind Helper
1.278
241967AE2-285_GEN
Solar/Wind Helper
0.329
241801AE1-079 GEN
Solar/Wind Helper
0.129
254304AE2-114 C
Solar/Wind Helper
0.109
254305AE2-115 C
Solar/Wind Helper
0.109
962101AG1-054 GEN
Solar/Wind Helper
0.317
203804AE2-113_GEN
Solar/Wind Helper
0.839
940863AE2-074 GEN
Solar/Wind Helper
0.218
274732ELWOOD EC;7P
Adder
7.215
274674JOLIET 9 ;6U
Adder
6.758
274871GR RIDGE ;2U
Solar/Wind Harmer
3.356
274847GR RIDGE ;BU
Solar/Wind Harmer
2.207
274745AC1-111 GEN9
Adder
2.426
276694AA1-018 GEN2
Solar/Wind Harmer
2.737
276691AA1-018 GEN1
Solar/Wind Harmer
0.327
274861TOP CROP ;1U
Solar/Wind Harmer
2.627
274682WAUKEGAN ;7U
Adder
7.745
270024AE2-089 GEN
Solar/Wind Harmer
2.019
274828WAUKEGAN ;BP
Adder
4.756
241885AC2-103 GEN1
Solar/Wind Helper
9.125
203947AF1-006 C
Solar/Wind Helper
0.369
961971AG1-040 GEN
Solar/Wind Helper
0.324
203830AF1-094 GEN
Solar/Wind Helper
0.314
203979AG1-198 GEN
Solar/Wind Helper
0.188
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.767
254303AC2-168 GEN
Solar/Wind Helper
0.074
990142J1224
External Queue
13.161874771118164
990527J1329
External Queue
1.8005300760269165
991182J1586 G
External Queue
24.65581703186035
991177J1571 G
External Queue
15.046978950500488
LAGNLTFEXP_LAGN->PJM
CLTF
4.791
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.172
NYPJM->LTFIMP_NY
CLTF
1.956
LGEELTFEXP_LGEE->PJM
CLTF
1.942
WECLTFEXP_WEC->PJM
CLTF
1.607
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.855
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.601
MECLTFEXP_MEC->PJM
CLTF
6.262
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.279

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B1_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B1_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.53 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2132.01
MW Contribution:
12.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.666
23888702TROY G3
50/50
1.794
972253AH1-711 GEN
50/50
54.851
23856402BAYSG1
50/50
1.208
23867002DVBSG1
50/50
13.924
24190002OREGON_ST1
50/50
3.587
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.794
241996AE2-282_GEN
Solar/Wind Harmer
2.114
241808AF1-120 C
Solar/Wind Harmer
1.179
23888502TROY G1
50/50
1.794
23888602TROY G2
50/50
1.794
945411AF1-206 GEN
Solar/Wind Harmer
7.915
945641AF1-229 GEN
Solar/Wind Harmer
3.393
270361_3
Solar/Wind Harmer
7.665
270575GUS2 35KV
Solar/Wind Harmer
9.03
270499AE1-146 GEN
Solar/Wind Harmer
2.144
971549AH1-272 GEN
Solar/Wind Harmer
12.854
270404AC1-167 GEN
Solar/Wind Harmer
0.689
270007AE1-245 C
Solar/Wind Harmer
3.104
944161AF1-084 GEN
Solar/Wind Harmer
1.267
957201AF2-014 GEN
Solar/Wind Harmer
2.6
270435AC2-044 GEN
Solar/Wind Harmer
1.147
966831AG1-554 GEN
Solar/Wind Harmer
0.661
965041AG1-368 GEN
Solar/Wind Harmer
5.38
247521TR3_G114
Solar/Wind Harmer
1.797
270191TR4_S_V150
Solar/Wind Harmer
1.603
965051AG1-369 GEN
Solar/Wind Harmer
2.669
970031AG2-029 GEN
Solar/Wind Harmer
13.283
971771AH1-392 GEN
Solar/Wind Harmer
4.714
959331AF2-224 GEN
Solar/Wind Harmer
5.179
270526AF1-158 GEN
Solar/Wind Harmer
2.328
270302AB2-170 GEN
Solar/Wind Harmer
4.281
960681AF2-359 GEN
Solar/Wind Harmer
1.855
971567AH1-282 GEN
Solar/Wind Harmer
2.445
963791AG1-232 GEN
Solar/Wind Harmer
6.455
270223U2-072_GEN1
Solar/Wind Harmer
0.936
270224U2-072_GEN2
Solar/Wind Harmer
0.936
270227U2-072_GEN3
Solar/Wind Harmer
0.936
270228U2-072_GEN4
Solar/Wind Harmer
0.936
270231U2-072_GEN5
Solar/Wind Harmer
0.936
270578AF1-285 GEN2
Solar/Wind Harmer
0.221
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
1.918
958321AF2-126 GEN
Solar/Wind Harmer
1.434
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.29
270541AE2-072 C
Solar/Wind Harmer
4.158
270044AE2-322 C
Solar/Wind Harmer
0.836
270588AE1-091_GEN
Solar/Wind Harmer
6.445
958091AF2-103 GEN
Solar/Wind Harmer
0.093
246938BC-WTG3
Solar/Wind Harmer
2.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.745
945111AF1-176 GEN
Solar/Wind Harmer
3.127
24695305TIMB G C
Solar/Wind Harmer
1.846
270505AE1-170 C O1
Solar/Wind Harmer
8.289
270063AE2-323 C
Solar/Wind Harmer
1.171
247643Z2-116 C
Solar/Wind Harmer
0.037
965021AG1-366 GEN
Solar/Wind Harmer
1.204
24441505OLIV SLR
Solar/Wind Harmer
0.068
270043AE2-236 GEN
Solar/Wind Harmer
2.697
971347AH1-153 GEN
Solar/Wind Harmer
2.443
942871AE2-306 GEN
Solar/Wind Harmer
0.43
270391AF1-285 GEN3
Solar/Wind Harmer
0.221
972231SS25-0005
Solar/Wind Harmer
4.33
972181SS23-001
Solar/Wind Harmer
2.706
274752CRETE EC ;2U
Adder
2.23
274753CRETE EC ;3U
Adder
2.23
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
5.389
241840AF1-064_GEN
Solar/Wind Harmer
1.334
23906502RICHG2&3
Adder
1.29
960841AF2-375 GEN
Solar/Wind Harmer
3.407
270297AD1-101 GEN
Solar/Wind Harmer
1.345
270258AD1-119 GEN
Solar/Wind Harmer
1.243
24441205WTRV SLR C
Solar/Wind Harmer
0.08
246936BC-WTG1
Solar/Wind Harmer
2.243
270489AE1-102 GEN1
Solar/Wind Harmer
0.745
965421AG1-410 GEN
Solar/Wind Harmer
17.041
270449AD2-020 GEN
Solar/Wind Harmer
1.585
943021AE2-325 GEN
Solar/Wind Harmer
2.059
945111AF1-176 GEN
Solar/Wind Harmer
9.868
957891AF2-083 GEN
Solar/Wind Harmer
8.262
24639705ELKHART HY
Adder
0.082
270216AD2-079_GEN
Solar/Wind Harmer
0.322
965011AG1-365 GEN
Solar/Wind Harmer
5.179
270317AD1-130_GEN
Solar/Wind Harmer
1.637
270485AE1-090_GEN
Solar/Wind Harmer
0.309
270391AF1-285 GEN3
Solar/Wind Harmer
0.573
270578AF1-285 GEN2
Solar/Wind Harmer
0.573
970373AG2-245 GEN
Solar/Wind Harmer
9.881
270055AF2-134 C O1
Solar/Wind Harmer
1.399
274751CRETE EC ;1U
Adder
2.23
274754CRETE EC ;4U
Adder
2.23
247522W1-056 GEN
Solar/Wind Harmer
1.455
944231AF1-091 GEN
Solar/Wind Harmer
11.584
247607V1-011 GEN
Solar/Wind Harmer
2.272
246937BC-WTG2
Solar/Wind Harmer
2.243
942801AE2-298 GEN
Solar/Wind Harmer
0.865
961051AF2-396 GEN
Solar/Wind Harmer
8.902
961051AF2-396 GEN
Solar/Wind Harmer
4.141
247620Y3-023
Adder
0.248
270246TR4_N_V150
Solar/Wind Harmer
0.455
270247TR4_N_V136
Solar/Wind Harmer
0.455
270462AD2-086
Solar/Wind Harmer
3.556
965681AG1-436 GEN
Solar/Wind Harmer
6.137
965791AG1-447 GEN
Solar/Wind Harmer
3.14
970349AG2-230 GEN
Solar/Wind Harmer
7.328
270535AF1-215 GEN1
Solar/Wind Harmer
2.099
270536AF1-215 GEN2
Solar/Wind Harmer
2.099
274805UNIV PK N;1U
Adder
2.261
274808UNIV PK N;4U
Adder
2.247
274888KELLY CRK;1U
Solar/Wind Harmer
2.617
276776AD2-060 GEN
Solar/Wind Harmer
0.186
958011AF2-095 GEN
Solar/Wind Harmer
6.385
970941AG2-585 GEN
Solar/Wind Harmer
2.439
274770LINCOLN ;1U
Adder
2.748
274771LINCOLN ;2U
Adder
2.748
276897AD1-100 C
Solar/Wind Harmer
20.403
276893AG1-478 C
Solar/Wind Harmer
0.192
274674JOLIET 9 ;6U
Adder
6.758
942221AE2-234 GEN
Solar/Wind Harmer
1.533
958481AF2-142 GEN
Solar/Wind Harmer
6.506
945421AF1-207 GEN
Solar/Wind Harmer
6.074
957841AF2-078 GEN
Solar/Wind Harmer
2.615
274695ROCKY RD ;2P
Adder
4.797
274693ROCKY RD ;1P
Adder
4.75
274697ROCKY RD ;3P
Adder
1.303
274696ROCKY RD ;4P
Adder
4.91
274683WAUKEGAN ;8U
Adder
9.073
274683WAUKEGAN ;8U
Adder
7.648
203835AF1-098 GEN
Solar/Wind Helper
1.278
241967AE2-285_GEN
Solar/Wind Helper
0.329
241801AE1-079 GEN
Solar/Wind Helper
0.129
254304AE2-114 C
Solar/Wind Helper
0.109
254305AE2-115 C
Solar/Wind Helper
0.109
962101AG1-054 GEN
Solar/Wind Helper
0.317
203804AE2-113_GEN
Solar/Wind Helper
0.839
940863AE2-074 GEN
Solar/Wind Helper
0.218
964401AG1-302 GEN
Solar/Wind Harmer
4.124
274724RIVER EC ;11
Adder
8.014
274814UNIV PK N;0U
Adder
2.276
274807UNIV PK N;3U
Adder
2.271
274811UNIV PK N;7U
Adder
2.256
276164X3-005 C
Solar/Wind Harmer
0.315
274803UNIV PARK;6U
Adder
2.598
274826FISK ;BP
Adder
4.869
972038AH1-567 GEN2
Adder
0.162
274887GEN-1.85
Solar/Wind Harmer
2.362
276772AC2-154 GEN
Solar/Wind Harmer
1.237
276843GEN-1.7
Solar/Wind Harmer
0.254
276806AD2-047 C O1
Solar/Wind Harmer
4.743
274772LINCOLN ;3U
Adder
2.748
972259AH1-714 GEN
Adder
8.395
274676JOLIET 29;8U
Adder
13.009
939351AE1-166 GEN
Solar/Wind Harmer
2.605
970707AG2-453 GEN
Solar/Wind Harmer
12.288
274729ELWOOD EC;1P
Adder
7.215
274730ELWOOD EC;6P
Adder
7.215
274734ELWOOD EC;8P
Adder
7.215
274736ELWOOD EC;9P
Adder
7.215
943121AE2-341 GEN
Solar/Wind Harmer
6.507
943591AF1-030 GEN
Solar/Wind Harmer
4.338
274862TOP CROP ;2U
Solar/Wind Harmer
2.193
274682WAUKEGAN ;7U
Adder
7.745
962511AG1-100 GEN
Solar/Wind Helper
0.331
270071AF1-092 GEN
Solar/Wind Harmer
6.833
958391AF2-133 GEN
Solar/Wind Harmer
4.085
959141AF2-205 GEN
Solar/Wind Harmer
2.704
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.451
274800UNIV PARK;3U
Adder
2.589
274801UNIV PARK;4U
Adder
2.589
960591AF2-350 GEN
Solar/Wind Harmer
4.434
274775LINCOLN ;6U
Adder
2.748
274776LINCOLN ;7U
Adder
2.748
274777LINCOLN ;8U
Adder
2.748
972228AH1-698 GEN2
Adder
1.637
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.312
274687WILL CNTY;4U
Adder
12.312
274675JOLIET 29;7U
Adder
13.491
274675JOLIET 29;7U
Adder
13.009
276893AG1-478 C
Solar/Wind Harmer
0.241
274728ELWOOD EC;5P
Adder
7.215
274731ELWOOD EC;2P
Adder
7.215
274733ELWOOD EC;3P
Adder
7.215
274735ELWOOD EC;4P
Adder
7.215
970833AG2-524 GEN
Solar/Wind Harmer
3.813
970833AG2-524 GEN
Solar/Wind Harmer
1.773
274744AC1-111 GEN8
Adder
2.426
274746AC1-111 G10
Adder
2.426
241886AC2-103 GEN2
Solar/Wind Helper
9.125
241985AE1-237 GEN
Solar/Wind Helper
0.128
241982AE2-343 S C
Solar/Wind Helper
0.115
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
958381AF2-132 GEN
Solar/Wind Harmer
4.124
964861AG1-349 GEN
Solar/Wind Harmer
3.567
971917AH1-482 GEN
Solar/Wind Harmer
4.115
274723RIVER EC ;12
Adder
8.111
274812UNIV PK N;8U
Adder
2.256
274802UNIV PARK;5U
Adder
2.598
940581AE2-045 GEN
Solar/Wind Harmer
4.521
972207SS24-0001
Solar/Wind Harmer
9.769
274773LINCOLN ;4U
Adder
2.748
274774LINCOLN ;5U
Adder
2.748
971605AH1-302 GEN
Solar/Wind Harmer
3.866
274676JOLIET 29;8U
Adder
13.491
941551AE2-152 GEN
Solar/Wind Harmer
1.992
274732ELWOOD EC;7P
Adder
7.215
274674JOLIET 9 ;6U
Adder
6.758
274871GR RIDGE ;2U
Solar/Wind Harmer
3.356
274847GR RIDGE ;BU
Solar/Wind Harmer
2.207
274745AC1-111 GEN9
Adder
2.426
276694AA1-018 GEN2
Solar/Wind Harmer
2.737
276691AA1-018 GEN1
Solar/Wind Harmer
0.327
274861TOP CROP ;1U
Solar/Wind Harmer
2.627
274682WAUKEGAN ;7U
Adder
7.745
270024AE2-089 GEN
Solar/Wind Harmer
2.019
274828WAUKEGAN ;BP
Adder
4.756
241885AC2-103 GEN1
Solar/Wind Helper
9.125
203947AF1-006 C
Solar/Wind Helper
0.369
961971AG1-040 GEN
Solar/Wind Helper
0.324
203830AF1-094 GEN
Solar/Wind Helper
0.314
203979AG1-198 GEN
Solar/Wind Helper
0.188
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.767
254303AC2-168 GEN
Solar/Wind Helper
0.074
990142J1224
External Queue
13.161874771118164
990527J1329
External Queue
1.8005300760269165
991182J1586 G
External Queue
24.65581703186035
991177J1571 G
External Queue
15.046978950500488
LAGNLTFEXP_LAGN->PJM
CLTF
4.791
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.172
NYPJM->LTFIMP_NY
CLTF
1.956
LGEELTFEXP_LGEE->PJM
CLTF
1.942
WECLTFEXP_WEC->PJM
CLTF
1.607
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.855
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.601
MECLTFEXP_MEC->PJM
CLTF
6.262
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.279

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.5 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:1901.19
MW Contribution:
10.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.666
23888702TROY G3
50/50
1.794
972253AH1-711 GEN
50/50
54.851
23856402BAYSG1
50/50
1.208
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
3.76
23906502RICHG2&3
Adder
1.29
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.161
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
965421AG1-410 GEN
Solar/Wind Harmer
11.889
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.059
945111AF1-176 GEN
Solar/Wind Harmer
6.884
957891AF2-083 GEN
Solar/Wind Harmer
6.405
24639705ELKHART HY
Adder
0.082
965011AG1-365 GEN
Solar/Wind Harmer
3.613
270317AD1-130_GEN
Solar/Wind Harmer
0
23929302BS-PKR
50/50
2.128
958321AF2-126 GEN
Solar/Wind Harmer
1.111
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.29
270541AE2-072 C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.197
246938BC-WTG3
Solar/Wind Harmer
0.144
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
3.127
24695305TIMB G C
Solar/Wind Harmer
0.327
270505AE1-170 C O1
Solar/Wind Harmer
4.048
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.204
270043AE2-236 GEN
Solar/Wind Harmer
2.195
971347AH1-153 GEN
Solar/Wind Harmer
1.704
270391AF1-285 GEN3
Solar/Wind Harmer
0.221
274752CRETE EC ;2U
Adder
3.759
274753CRETE EC ;3U
Adder
3.759
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.014
274814UNIV PK N;0U
Adder
2.276
274807UNIV PK N;3U
Adder
2.271
274811UNIV PK N;7U
Adder
2.256
274803UNIV PARK;6U
Adder
2.598
274826FISK ;BP
Adder
4.869
972038AH1-567 GEN2
Adder
0.162
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.1
276806AD2-047 C O1
Solar/Wind Harmer
1.753
274772LINCOLN ;3U
Adder
3.74
972259AH1-714 GEN
Adder
8.395
274676JOLIET 29;8U
Adder
13.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.002
274729ELWOOD EC;1P
Adder
7.215
274730ELWOOD EC;6P
Adder
7.215
274734ELWOOD EC;8P
Adder
7.215
274736ELWOOD EC;9P
Adder
7.215
943121AE2-341 GEN
Solar/Wind Harmer
5.074
23867002DVBSG1
50/50
13.924
24190002OREGON_ST1
50/50
3.587
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.794
970621AG2-405 GEN
Solar/Wind Harmer
0.846
944231AF1-091 GEN
Solar/Wind Harmer
10.357
970623AG2-406 GEN
Solar/Wind Harmer
0.781
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.161
961051AF2-396 GEN
Solar/Wind Harmer
7.826
961051AF2-396 GEN
Solar/Wind Harmer
5.217
247620Y3-023
Adder
0.248
270246TR4_N_V150
Solar/Wind Harmer
0.024
270247TR4_N_V136
Solar/Wind Harmer
0.024
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.282
965791AG1-447 GEN
Solar/Wind Harmer
3.14
970349AG2-230 GEN
Solar/Wind Harmer
5.113
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.261
274808UNIV PK N;4U
Adder
2.247
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
276776AD2-060 GEN
Solar/Wind Harmer
0.33
958011AF2-095 GEN
Solar/Wind Harmer
4.455
970941AG2-585 GEN
Solar/Wind Harmer
1.701
274770LINCOLN ;1U
Adder
3.74
274771LINCOLN ;2U
Adder
3.74
276897AD1-100 C
Solar/Wind Harmer
7.661
276893AG1-478 C
Solar/Wind Harmer
0.204
274674JOLIET 9 ;6U
Adder
6.758
942221AE2-234 GEN
Solar/Wind Harmer
1.227
958481AF2-142 GEN
Solar/Wind Harmer
4.539
23888502TROY G1
50/50
1.794
23888602TROY G2
50/50
1.794
945411AF1-206 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.2
270575GUS2 35KV
Solar/Wind Harmer
4.2
270499AE1-146 GEN
Solar/Wind Harmer
0.019
970373AG2-245 GEN
Solar/Wind Harmer
6.894
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
3.759
274754CRETE EC ;4U
Adder
3.759
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.115
274723RIVER EC ;12
Adder
8.111
274812UNIV PK N;8U
Adder
2.256
274802UNIV PARK;5U
Adder
2.598
940581AE2-045 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.74
274774LINCOLN ;5U
Adder
3.74
971605AH1-302 GEN
Solar/Wind Harmer
3.866
274676JOLIET 29;8U
Adder
13.491
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.215
274674JOLIET 9 ;6U
Adder
6.758
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.426
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.492
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
7.745
270024AE2-089 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
4.756
241885AC2-103 GEN1
Solar/Wind Helper
9.125
203947AF1-006 C
Solar/Wind Helper
0.369
961971AG1-040 GEN
Solar/Wind Helper
0.324
203830AF1-094 GEN
Solar/Wind Helper
0.314
203979AG1-198 GEN
Solar/Wind Helper
0.188
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.767
254303AC2-168 GEN
Solar/Wind Helper
0.074
943591AF1-030 GEN
Solar/Wind Harmer
3.375
274862TOP CROP ;2U
Solar/Wind Harmer
0.408
274682WAUKEGAN ;7U
Adder
7.745
962511AG1-100 GEN
Solar/Wind Helper
0.331
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
4.797
274693ROCKY RD ;1P
Adder
4.75
274697ROCKY RD ;3P
Adder
1.303
274696ROCKY RD ;4P
Adder
4.91
274683WAUKEGAN ;8U
Adder
9.073
274683WAUKEGAN ;8U
Adder
7.648
203835AF1-098 GEN
Solar/Wind Helper
1.278
241967AE2-285_GEN
Solar/Wind Helper
0.329
241801AE1-079 GEN
Solar/Wind Helper
0.129
254304AE2-114 C
Solar/Wind Helper
0.109
254305AE2-115 C
Solar/Wind Helper
0.109
962101AG1-054 GEN
Solar/Wind Helper
0.317
203804AE2-113_GEN
Solar/Wind Helper
0.839
940863AE2-074 GEN
Solar/Wind Helper
0.218
971549AH1-272 GEN
Solar/Wind Harmer
10.01
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.507
965041AG1-368 GEN
Solar/Wind Harmer
3.754
247521TR3_G114
Solar/Wind Harmer
0.135
965051AG1-369 GEN
Solar/Wind Harmer
1.862
970031AG2-029 GEN
Solar/Wind Harmer
2.008
971771AH1-392 GEN
Solar/Wind Harmer
3.654
959331AF2-224 GEN
Solar/Wind Harmer
2.529
270526AF1-158 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.502
960681AF2-359 GEN
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
2.615
963791AG1-232 GEN
Solar/Wind Harmer
4.503
270578AF1-285 GEN2
Solar/Wind Harmer
0.221
270071AF1-092 GEN
Solar/Wind Harmer
6.092
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.451
274800UNIV PARK;3U
Adder
2.589
274801UNIV PARK;4U
Adder
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.093
274775LINCOLN ;6U
Adder
3.74
274776LINCOLN ;7U
Adder
3.74
274777LINCOLN ;8U
Adder
3.74
971611AH1-305 GEN
Solar/Wind Harmer
1.841
972228AH1-698 GEN2
Adder
1.637
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.312
274687WILL CNTY;4U
Adder
12.312
274675JOLIET 29;7U
Adder
13.491
274675JOLIET 29;7U
Adder
13.009
274728ELWOOD EC;5P
Adder
7.215
274731ELWOOD EC;2P
Adder
7.215
274733ELWOOD EC;3P
Adder
7.215
274735ELWOOD EC;4P
Adder
7.215
970833AG2-524 GEN
Solar/Wind Harmer
3.352
970833AG2-524 GEN
Solar/Wind Harmer
2.234
274744AC1-111 GEN8
Adder
2.426
274746AC1-111 G10
Adder
2.426
241886AC2-103 GEN2
Solar/Wind Helper
9.125
241985AE1-237 GEN
Solar/Wind Helper
0.128
241982AE2-343 S C
Solar/Wind Helper
0.115
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
990142J1224
External Queue
13.161874771118164
990527J1329
External Queue
1.8005300760269165
991182J1586 G
External Queue
24.65581703186035
991177J1571 G
External Queue
15.046978950500488
LAGNLTFEXP_LAGN->PJM
CLTF
4.791
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.172
NYPJM->LTFIMP_NY
CLTF
1.956
LGEELTFEXP_LGEE->PJM
CLTF
1.942
WECLTFEXP_WEC->PJM
CLTF
1.607
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.855
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.601
MECLTFEXP_MEC->PJM
CLTF
6.262
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.279

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.41 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:1784.35
MW Contribution:
9.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.549
23888702TROY G3
50/50
1.734
972253AH1-711 GEN
50/50
53.016
23856402BAYSG1
50/50
1.279
23920202STRYCT
50/50
1.886
241858AF1-205_GEN
Solar/Wind Harmer
3.799
23906502RICHG2&3
Adder
1.305
960841AF2-375 GEN
Solar/Wind Harmer
0
241807AE2-176_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.522
965421AG1-410 GEN
Solar/Wind Harmer
11.924
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.034
945111AF1-176 GEN
Solar/Wind Harmer
6.805
957891AF2-083 GEN
Solar/Wind Harmer
6.33
24639705ELKHART HY
Adder
0.082
965011AG1-365 GEN
Solar/Wind Harmer
3.609
270317AD1-130_GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.831
270055AF2-134 C O1
Solar/Wind Harmer
0
23929302BS-PKR
50/50
2.254
958321AF2-126 GEN
Solar/Wind Harmer
1.148
23906402RICHG1
Adder
1.308
23906502RICHG2&3
Adder
1.305
270541AE2-072 C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.359
246938BC-WTG3
Solar/Wind Harmer
0.145
270491AE1-102 GEN2
Solar/Wind Harmer
0.522
24695305TIMB G C
Solar/Wind Harmer
0.329
945111AF1-176 GEN
Solar/Wind Harmer
3.091
270505AE1-170 C O1
Solar/Wind Harmer
4.001
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.203
270043AE2-236 GEN
Solar/Wind Harmer
2.185
971347AH1-153 GEN
Solar/Wind Harmer
1.688
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
23867002DVBSG1
50/50
12.56
24190002OREGON_ST1
50/50
3.43
24189802OREGON_CT1
50/50
2.603
23888802TROY G4
50/50
1.734
970621AG2-405 GEN
Solar/Wind Harmer
0.867
944231AF1-091 GEN
Solar/Wind Harmer
10.388
970623AG2-406 GEN
Solar/Wind Harmer
0.789
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.732
961051AF2-396 GEN
Solar/Wind Harmer
5.155
270246TR4_N_V150
Solar/Wind Harmer
0.024
270247TR4_N_V136
Solar/Wind Harmer
0.024
247620Y3-023
Adder
0.246
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.24
965791AG1-447 GEN
Solar/Wind Harmer
3.109
970349AG2-230 GEN
Solar/Wind Harmer
5.065
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
23888502TROY G1
50/50
1.734
23888602TROY G2
50/50
1.734
945411AF1-206 GEN
Solar/Wind Harmer
0
270361_3
Solar/Wind Harmer
4.656
270575GUS2 35KV
Solar/Wind Harmer
4.656
270499AE1-146 GEN
Solar/Wind Harmer
0.021
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.841
270428AC2-015 C
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.508
965041AG1-368 GEN
Solar/Wind Harmer
3.768
247521TR3_G114
Solar/Wind Harmer
0.136
965051AG1-369 GEN
Solar/Wind Harmer
1.872
970031AG2-029 GEN
Solar/Wind Harmer
1.993
971771AH1-392 GEN
Solar/Wind Harmer
3.616
959331AF2-224 GEN
Solar/Wind Harmer
2.526
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.507
24191202EL_AA1-006
Adder
0.112
270526AF1-158 GEN
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
2.681
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
963791AG1-232 GEN
Solar/Wind Harmer
4.502
270377AD1-106 GEN
Solar/Wind Harmer
1.238
270071AF1-092 GEN
Solar/Wind Harmer
6.069
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.422
274800UNIV PARK;3U
Adder
2.568
274801UNIV PARK;4U
Adder
2.568
960591AF2-350 GEN
Solar/Wind Harmer
3.068
971611AH1-305 GEN
Solar/Wind Harmer
1.827
274775LINCOLN ;6U
Adder
3.71
274751CRETE EC ;1U
Adder
3.727
274754CRETE EC ;4U
Adder
3.727
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.081
274723RIVER EC ;12
Adder
8.042
274812UNIV PK N;8U
Adder
2.237
274802UNIV PARK;5U
Adder
2.576
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.835
274773LINCOLN ;4U
Adder
3.71
274774LINCOLN ;5U
Adder
3.71
274676JOLIET 29;8U
Adder
13.38
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.156
274674JOLIET 9 ;6U
Adder
6.703
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.406
270024AE2-089 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.488
274861TOP CROP ;1U
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
9.501
203947AF1-006 C
Solar/Wind Helper
0.374
961971AG1-040 GEN
Solar/Wind Helper
0.328
203830AF1-094 GEN
Solar/Wind Helper
0.318
203979AG1-198 GEN
Solar/Wind Helper
0.191
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
274752CRETE EC ;2U
Adder
3.727
274753CRETE EC ;3U
Adder
3.727
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.946
274814UNIV PK N;0U
Adder
2.257
274807UNIV PK N;3U
Adder
2.252
274811UNIV PK N;7U
Adder
2.237
274803UNIV PARK;6U
Adder
2.576
274826FISK ;BP
Adder
4.829
972038AH1-567 GEN2
Adder
0.161
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.099
276806AD2-047 C O1
Solar/Wind Harmer
1.739
274772LINCOLN ;3U
Adder
3.71
972259AH1-714 GEN
Adder
8.327
274676JOLIET 29;8U
Adder
12.903
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
7.156
274730ELWOOD EC;6P
Adder
7.156
274734ELWOOD EC;8P
Adder
7.156
274736ELWOOD EC;9P
Adder
7.156
970707AG2-453 GEN
Solar/Wind Harmer
9.921
943121AE2-341 GEN
Solar/Wind Harmer
5.034
943591AF1-030 GEN
Solar/Wind Harmer
3.348
274862TOP CROP ;2U
Solar/Wind Harmer
0.405
962511AG1-100 GEN
Solar/Wind Helper
0.335
274805UNIV PK N;1U
Adder
2.242
274808UNIV PK N;4U
Adder
2.228
274888KELLY CRK;1U
Solar/Wind Harmer
0.179
276776AD2-060 GEN
Solar/Wind Harmer
0.327
958011AF2-095 GEN
Solar/Wind Harmer
4.418
970941AG2-585 GEN
Solar/Wind Harmer
1.687
274770LINCOLN ;1U
Adder
3.71
274771LINCOLN ;2U
Adder
3.71
942221AE2-234 GEN
Solar/Wind Harmer
1.226
276897AD1-100 C
Solar/Wind Harmer
7.599
276893AG1-478 C
Solar/Wind Harmer
0.203
274674JOLIET 9 ;6U
Adder
6.703
958481AF2-142 GEN
Solar/Wind Harmer
4.502
203835AF1-098 GEN
Solar/Wind Helper
1.295
241967AE2-285_GEN
Solar/Wind Helper
0.332
241801AE1-079 GEN
Solar/Wind Helper
0.13
254304AE2-114 C
Solar/Wind Helper
0.111
254305AE2-115 C
Solar/Wind Helper
0.111
962101AG1-054 GEN
Solar/Wind Helper
0.321
203804AE2-113_GEN
Solar/Wind Helper
0.849
940863AE2-074 GEN
Solar/Wind Helper
0.22
946381AF1-302 GEN
Solar/Wind Helper
0.103
274776LINCOLN ;7U
Adder
3.71
274777LINCOLN ;8U
Adder
3.71
972228AH1-698 GEN2
Adder
1.624
972227AH1-698 GEN1
Adder
1.144
274687WILL CNTY;4U
Adder
12.211
274687WILL CNTY;4U
Adder
12.211
274675JOLIET 29;7U
Adder
13.381
274675JOLIET 29;7U
Adder
12.903
274728ELWOOD EC;5P
Adder
7.156
274731ELWOOD EC;2P
Adder
7.156
274733ELWOOD EC;3P
Adder
7.156
274735ELWOOD EC;4P
Adder
7.156
970833AG2-524 GEN
Solar/Wind Harmer
3.325
970833AG2-524 GEN
Solar/Wind Harmer
2.216
274744AC1-111 GEN8
Adder
2.406
274746AC1-111 G10
Adder
2.406
241886AC2-103 GEN2
Solar/Wind Helper
9.501
241985AE1-237 GEN
Solar/Wind Helper
0.129
241982AE2-343 S C
Solar/Wind Helper
0.116
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
20334926Z1-069 C
Solar/Wind Helper
0.632
990142J1224
External Queue
12.760451316833496
990527J1329
External Queue
1.7456159591674805
991182J1586 G
External Queue
23.870176315307617
991177J1571 G
External Queue
14.7259521484375
LAGNLTFEXP_LAGN->PJM
CLTF
4.772
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.138
TVALTFEXP_TVA->PJM
CLTF
2.167
NYPJM->LTFIMP_NY
CLTF
1.977
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.595
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.204
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.585
MECLTFEXP_MEC->PJM
CLTF
6.22
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.122

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-005_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-005_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.38 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2410.9
MW Contribution:
13.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
1.83
23888602TROY G2
50/50
1.83
23860102FRMENG 1
50/50
1.732
23860202FRMENG 2
50/50
1.732
24191202EL_AA1-006
50/50
0.333
241886AC2-103 GEN2
Solar/Wind Harmer
12.859
945411AF1-206 GEN
Solar/Wind Harmer
8.65
270361_3
Solar/Wind Harmer
9.718
270575GUS2 35KV
Solar/Wind Harmer
11.449
270499AE1-146 GEN
Solar/Wind Harmer
2.678
945641AF1-229 GEN
Solar/Wind Harmer
3.662
270428AC2-015 C
Solar/Wind Harmer
4.139
971549AH1-272 GEN
Solar/Wind Harmer
13.429
270404AC1-167 GEN
Solar/Wind Harmer
0.753
966831AG1-554 GEN
Solar/Wind Harmer
0.787
270007AE1-245 C
Solar/Wind Harmer
3.393
957201AF2-014 GEN
Solar/Wind Harmer
2.805
270435AC2-044 GEN
Solar/Wind Harmer
1.237
944161AF1-084 GEN
Solar/Wind Harmer
1.331
965041AG1-368 GEN
Solar/Wind Harmer
5.807
247521TR3_G114
Solar/Wind Harmer
1.943
270191TR4_S_V150
Solar/Wind Harmer
1.734
965051AG1-369 GEN
Solar/Wind Harmer
2.886
970031AG2-029 GEN
Solar/Wind Harmer
14.072
270302AB2-170 GEN
Solar/Wind Harmer
4.661
959331AF2-224 GEN
Solar/Wind Harmer
5.541
971771AH1-392 GEN
Solar/Wind Harmer
4.966
971567AH1-282 GEN
Solar/Wind Harmer
2.728
270526AF1-158 GEN
Solar/Wind Harmer
2.452
270377AD1-106 GEN
Solar/Wind Harmer
2.789
960681AF2-359 GEN
Solar/Wind Harmer
1.955
270223U2-072_GEN1
Solar/Wind Harmer
1.02
270224U2-072_GEN2
Solar/Wind Harmer
1.02
270227U2-072_GEN3
Solar/Wind Harmer
1.02
270228U2-072_GEN4
Solar/Wind Harmer
1.02
270231U2-072_GEN5
Solar/Wind Harmer
1.02
270578AF1-285 GEN2
Solar/Wind Harmer
0.24
963791AG1-232 GEN
Solar/Wind Harmer
6.91
23929302BS-PKR
50/50
2.517
241832AE2-181_GEN
Solar/Wind Harmer
2.094
958321AF2-126 GEN
Solar/Wind Harmer
1.629
23906402RICHG1
Adder
1.419
23906502RICHG2&3
Adder
1.417
270541AE2-072 C
Solar/Wind Harmer
4.698
270044AE2-322 C
Solar/Wind Harmer
0.914
270588AE1-091_GEN
Solar/Wind Harmer
7.492
958091AF2-103 GEN
Solar/Wind Harmer
0.101
246938BC-WTG3
Solar/Wind Harmer
2.461
270491AE1-102 GEN2
Solar/Wind Harmer
0.804
24695305TIMB G C
Solar/Wind Harmer
2.003
945111AF1-176 GEN
Solar/Wind Harmer
3.291
270505AE1-170 C O1
Solar/Wind Harmer
8.719
270063AE2-323 C
Solar/Wind Harmer
1.241
247643Z2-116 C
Solar/Wind Harmer
0.039
965021AG1-366 GEN
Solar/Wind Harmer
1.289
24441505OLIV SLR
Solar/Wind Harmer
0.072
270043AE2-236 GEN
Solar/Wind Harmer
2.868
942871AE2-306 GEN
Solar/Wind Harmer
0.468
270391AF1-285 GEN3
Solar/Wind Harmer
0.24
971347AH1-153 GEN
Solar/Wind Harmer
2.577
23867002DVBSG1
50/50
12.63
24190002OREGON_ST1
50/50
3.593
24189802OREGON_CT1
50/50
2.727
23888802TROY G4
50/50
1.83
241996AE2-282_GEN
Solar/Wind Harmer
2.31
241808AF1-120 C
Solar/Wind Harmer
1.288
247522W1-056 GEN
Solar/Wind Harmer
1.769
944231AF1-091 GEN
Solar/Wind Harmer
12.502
247607V1-011 GEN
Solar/Wind Harmer
2.484
942801AE2-298 GEN
Solar/Wind Harmer
0.946
246937BC-WTG2
Solar/Wind Harmer
2.419
961051AF2-396 GEN
Solar/Wind Harmer
9.361
961051AF2-396 GEN
Solar/Wind Harmer
4.354
270246TR4_N_V150
Solar/Wind Harmer
0.492
270247TR4_N_V136
Solar/Wind Harmer
0.492
247620Y3-023
Adder
0.262
270462AD2-086
Solar/Wind Harmer
3.871
965681AG1-436 GEN
Solar/Wind Harmer
6.469
965791AG1-447 GEN
Solar/Wind Harmer
3.31
970349AG2-230 GEN
Solar/Wind Harmer
7.73
24189902OREGON_CT2
50/50
2.67
23856402BAYSG1
50/50
1.428
23888702TROY G3
50/50
1.83
972253AH1-711 GEN
50/50
55.937
23860302FRMENG 3
50/50
3.514
23920202STRYCT
50/50
2.045
241885AC2-103 GEN1
Solar/Wind Harmer
12.859
241807AE2-176_GEN
Solar/Wind Harmer
7.263
241858AF1-205_GEN
Solar/Wind Harmer
5.91
241840AF1-064_GEN
Solar/Wind Harmer
1.516
23906502RICHG2&3
Adder
1.417
960841AF2-375 GEN
Solar/Wind Harmer
4.293
270297AD1-101 GEN
Solar/Wind Harmer
1.505
270258AD1-119 GEN
Solar/Wind Harmer
1.356
24441205WTRV SLR C
Solar/Wind Harmer
0.084
246936BC-WTG1
Solar/Wind Harmer
2.419
270489AE1-102 GEN1
Solar/Wind Harmer
0.804
965421AG1-410 GEN
Solar/Wind Harmer
18.369
270449AD2-020 GEN
Solar/Wind Harmer
1.666
943021AE2-325 GEN
Solar/Wind Harmer
2.164
945111AF1-176 GEN
Solar/Wind Harmer
10.383
957891AF2-083 GEN
Solar/Wind Harmer
8.692
24639705ELKHART HY
Adder
0.087
270216AD2-079_GEN
Solar/Wind Harmer
0.339
270317AD1-130_GEN
Solar/Wind Harmer
1.782
270485AE1-090_GEN
Solar/Wind Harmer
0.337
965011AG1-365 GEN
Solar/Wind Harmer
5.541
270391AF1-285 GEN3
Solar/Wind Harmer
0.624
270578AF1-285 GEN2
Solar/Wind Harmer
0.624
970373AG2-245 GEN
Solar/Wind Harmer
10.424
972231SS25-0005
Solar/Wind Harmer
4.569
972181SS23-001
Solar/Wind Harmer
2.856
274752CRETE EC ;2U
Adder
2.353
274753CRETE EC ;3U
Adder
2.353
964401AG1-302 GEN
Solar/Wind Harmer
4.353
274724RIVER EC ;11
Adder
8.459
274814UNIV PK N;0U
Adder
2.402
274807UNIV PK N;3U
Adder
2.397
274811UNIV PK N;7U
Adder
2.382
276164X3-005 C
Solar/Wind Harmer
0.333
961961AG1-039 GEN
Solar/Wind Harmer
1.348
274803UNIV PARK;6U
Adder
2.742
274826FISK ;BP
Adder
5.14
972038AH1-567 GEN2
Adder
0.171
274887GEN-1.85
Solar/Wind Harmer
2.494
276772AC2-154 GEN
Solar/Wind Harmer
1.306
276843GEN-1.7
Solar/Wind Harmer
0.268
276806AD2-047 C O1
Solar/Wind Harmer
5.007
274772LINCOLN ;3U
Adder
2.901
972259AH1-714 GEN
Adder
8.863
274676JOLIET 29;8U
Adder
13.734
939351AE1-166 GEN
Solar/Wind Harmer
2.75
274729ELWOOD EC;1P
Adder
7.617
274730ELWOOD EC;6P
Adder
7.617
274734ELWOOD EC;8P
Adder
7.617
274736ELWOOD EC;9P
Adder
7.617
970707AG2-453 GEN
Solar/Wind Harmer
12.974
943121AE2-341 GEN
Solar/Wind Harmer
6.87
943591AF1-030 GEN
Solar/Wind Harmer
4.58
274862TOP CROP ;2U
Solar/Wind Harmer
2.316
944531AF1-118 GEN
Solar/Wind Harmer
15.957
274682WAUKEGAN ;7U
Adder
8.178
274760LEE CO EC;1U
Adder
4.092
274767LEE CO EC;8U
Adder
4.044
962511AG1-100 GEN
Solar/Wind Helper
0.369
203854AF2-039 C
Solar/Wind Helper
0.151
20398826ARMNA MT
Solar/Wind Helper
0.712
270071AF1-092 GEN
Solar/Wind Harmer
7.271
958391AF2-133 GEN
Solar/Wind Harmer
4.314
959141AF2-205 GEN
Solar/Wind Harmer
2.856
972037AH1-567 GEN1
Adder
0.086
274827FISK ;RP
Adder
3.643
274800UNIV PARK;3U
Adder
2.733
274801UNIV PARK;4U
Adder
2.733
960591AF2-350 GEN
Solar/Wind Harmer
4.681
274775LINCOLN ;6U
Adder
2.901
274776LINCOLN ;7U
Adder
2.901
274777LINCOLN ;8U
Adder
2.901
972228AH1-698 GEN2
Adder
1.729
972227AH1-698 GEN1
Adder
1.217
274687WILL CNTY;4U
Adder
12.998
274687WILL CNTY;4U
Adder
12.998
274675JOLIET 29;7U
Adder
14.242
274675JOLIET 29;7U
Adder
13.734
276893AG1-478 C
Solar/Wind Harmer
0.255
274728ELWOOD EC;5P
Adder
7.617
274731ELWOOD EC;2P
Adder
7.617
274733ELWOOD EC;3P
Adder
7.617
274735ELWOOD EC;4P
Adder
7.617
970833AG2-524 GEN
Solar/Wind Harmer
4.025
970833AG2-524 GEN
Solar/Wind Harmer
1.872
274744AC1-111 GEN8
Adder
2.561
274746AC1-111 G10
Adder
2.561
970073AG2-061 GEN
Solar/Wind Harmer
1.056
24729505KEY G4
Adder
2.929
274823ROCKFORD ;21
Adder
8.673
972267AH1-718 GEN
Adder
1.819
241985AE1-237 GEN
Solar/Wind Helper
0.142
241982AE2-343 S C
Solar/Wind Helper
0.128
203846AF2-130 C
Solar/Wind Helper
0.267
241997AF1-093 GEN
Solar/Wind Helper
0.14
20334926Z1-069 C
Solar/Wind Helper
0.697
270055AF2-134 C O1
Solar/Wind Harmer
1.476
274751CRETE EC ;1U
Adder
2.353
274754CRETE EC ;4U
Adder
2.353
958381AF2-132 GEN
Solar/Wind Harmer
4.353
964861AG1-349 GEN
Solar/Wind Harmer
3.766
971917AH1-482 GEN
Solar/Wind Harmer
4.345
274723RIVER EC ;12
Adder
8.561
274812UNIV PK N;8U
Adder
2.382
241847AF2-150_GEN
Solar/Wind Harmer
1.955
274802UNIV PARK;5U
Adder
2.742
940581AE2-045 GEN
Solar/Wind Harmer
4.776
971605AH1-302 GEN
Solar/Wind Harmer
4.083
972207SS24-0001
Solar/Wind Harmer
10.314
274773LINCOLN ;4U
Adder
2.901
274774LINCOLN ;5U
Adder
2.901
274676JOLIET 29;8U
Adder
14.242
941551AE2-152 GEN
Solar/Wind Harmer
2.103
274732ELWOOD EC;7P
Adder
7.617
274674JOLIET 9 ;6U
Adder
7.134
274871GR RIDGE ;2U
Solar/Wind Harmer
3.543
274847GR RIDGE ;BU
Solar/Wind Harmer
2.33
270024AE2-089 GEN
Solar/Wind Harmer
2.158
274745AC1-111 GEN9
Adder
2.561
276694AA1-018 GEN2
Solar/Wind Harmer
2.889
276691AA1-018 GEN1
Solar/Wind Harmer
0.345
274861TOP CROP ;1U
Solar/Wind Harmer
2.774
274682WAUKEGAN ;7U
Adder
8.178
274828WAUKEGAN ;BP
Adder
5.021
276805AD2-038 GEN
Solar/Wind Harmer
2.327
939401AE1-172 GEN
Solar/Wind Harmer
6.305
274822ROCKFORD ;11
Adder
8.736
274761LEE CO EC;2U
Adder
4.092
274766LEE CO EC;7U
Adder
4.044
203947AF1-006 C
Solar/Wind Helper
0.411
961971AG1-040 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.35
203979AG1-198 GEN
Solar/Wind Helper
0.21
241966AE1-183 GEN
Solar/Wind Helper
0.14
254303AC2-168 GEN
Solar/Wind Helper
0.082
203855AF2-088 C
Solar/Wind Helper
0.073
270535AF1-215 GEN1
Solar/Wind Harmer
2.215
270536AF1-215 GEN2
Solar/Wind Harmer
2.215
274805UNIV PK N;1U
Adder
2.387
274808UNIV PK N;4U
Adder
2.371
274888KELLY CRK;1U
Solar/Wind Harmer
2.762
276776AD2-060 GEN
Solar/Wind Harmer
0.196
958011AF2-095 GEN
Solar/Wind Harmer
6.74
970941AG2-585 GEN
Solar/Wind Harmer
2.574
274770LINCOLN ;1U
Adder
2.901
274771LINCOLN ;2U
Adder
2.901
942221AE2-234 GEN
Solar/Wind Harmer
1.636
276897AD1-100 C
Solar/Wind Harmer
21.542
276893AG1-478 C
Solar/Wind Harmer
0.203
274674JOLIET 9 ;6U
Adder
7.134
958481AF2-142 GEN
Solar/Wind Harmer
6.869
945421AF1-207 GEN
Solar/Wind Harmer
6.419
957841AF2-078 GEN
Solar/Wind Harmer
2.763
274696ROCKY RD ;4P
Adder
5.184
274695ROCKY RD ;2P
Adder
5.065
274693ROCKY RD ;1P
Adder
5.015
274697ROCKY RD ;3P
Adder
1.376
274683WAUKEGAN ;8U
Adder
9.58
274683WAUKEGAN ;8U
Adder
8.075
958491AF2-143 GEN
Solar/Wind Harmer
6.808
276901AD2-066 C O1
Solar/Wind Harmer
1.587
972235AH1-702 GEN1
Adder
1.12
972236AH1-702 GEN2
Adder
0.974
274764LEE CO EC;5U
Adder
4.102
274765LEE CO EC;6U
Adder
4.102
274762LEE CO EC;3U
Adder
4.092
274763LEE CO EC;4U
Adder
4.054
25326509SID D
Adder
0.573
203835AF1-098 GEN
Solar/Wind Helper
1.424
241967AE2-285_GEN
Solar/Wind Helper
0.365
241801AE1-079 GEN
Solar/Wind Helper
0.143
254304AE2-114 C
Solar/Wind Helper
0.122
254305AE2-115 C
Solar/Wind Helper
0.122
962101AG1-054 GEN
Solar/Wind Helper
0.353
203804AE2-113_GEN
Solar/Wind Helper
0.936
940863AE2-074 GEN
Solar/Wind Helper
0.243
946381AF1-302 GEN
Solar/Wind Helper
0.113
203954AE2-126 C
Solar/Wind Helper
0.236
203853AF1-134 C O1
Solar/Wind Helper
0.222
203818AF1-086 GEN
Solar/Wind Helper
0.773
962691AG1-118 GEN
Solar/Wind Harmer
11.726
990142J1224
External Queue
13.534384727478027
990527J1329
External Queue
1.8514890670776367
991182J1586 G
External Queue
25.29424285888672
991177J1571 G
External Queue
15.716124534606934
LAGNLTFEXP_LAGN->PJM
CLTF
5.044
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.149
TVALTFEXP_TVA->PJM
CLTF
2.287
NYPJM->LTFIMP_NY
CLTF
2.187
LGEELTFEXP_LGEE->PJM
CLTF
2.067
WECLTFEXP_WEC->PJM
CLTF
1.697
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.712
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.078
MECLTFEXP_MEC->PJM
CLTF
6.613
SIGELTFEXP_SIGE->PJM
CLTF
0.172
CPLELTFEXP_CPLE->PJM
CLTF
0.292
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.432

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-006_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.55 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2357.8
MW Contribution:
13.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.536
241832AE2-181_GEN
Solar/Wind Harmer
2.11
958321AF2-126 GEN
Solar/Wind Harmer
1.643
23906402RICHG1
Adder
1.432
23906502RICHG2&3
Adder
1.43
270541AE2-072 C
Solar/Wind Harmer
4.748
270044AE2-322 C
Solar/Wind Harmer
0.926
270588AE1-091_GEN
Solar/Wind Harmer
7.621
958091AF2-103 GEN
Solar/Wind Harmer
0.103
246938BC-WTG3
Solar/Wind Harmer
2.495
270491AE1-102 GEN2
Solar/Wind Harmer
0.815
24695305TIMB G C
Solar/Wind Harmer
2.031
945111AF1-176 GEN
Solar/Wind Harmer
3.333
270505AE1-170 C O1
Solar/Wind Harmer
8.831
270063AE2-323 C
Solar/Wind Harmer
1.258
247643Z2-116 C
Solar/Wind Harmer
0.039
965021AG1-366 GEN
Solar/Wind Harmer
1.307
24441505OLIV SLR
Solar/Wind Harmer
0.073
270043AE2-236 GEN
Solar/Wind Harmer
2.909
942871AE2-306 GEN
Solar/Wind Harmer
0.476
270391AF1-285 GEN3
Solar/Wind Harmer
0.244
971347AH1-153 GEN
Solar/Wind Harmer
2.613
961961AG1-039 GEN
Solar/Wind Harmer
1.416
972231SS25-0005
Solar/Wind Harmer
4.637
972181SS23-001
Solar/Wind Harmer
2.898
274752CRETE EC ;2U
Adder
2.388
274753CRETE EC ;3U
Adder
2.388
964401AG1-302 GEN
Solar/Wind Harmer
4.418
274724RIVER EC ;11
Adder
8.585
274814UNIV PK N;0U
Adder
2.438
274807UNIV PK N;3U
Adder
2.433
274811UNIV PK N;7U
Adder
2.417
276164X3-005 C
Solar/Wind Harmer
0.338
274803UNIV PARK;6U
Adder
2.784
274826FISK ;BP
Adder
5.218
972038AH1-567 GEN2
Adder
0.174
274887GEN-1.85
Solar/Wind Harmer
2.532
276772AC2-154 GEN
Solar/Wind Harmer
1.326
276843GEN-1.7
Solar/Wind Harmer
0.272
276806AD2-047 C O1
Solar/Wind Harmer
5.083
274772LINCOLN ;3U
Adder
2.945
972259AH1-714 GEN
Adder
8.999
274676JOLIET 29;8U
Adder
13.943
939351AE1-166 GEN
Solar/Wind Harmer
2.792
970707AG2-453 GEN
Solar/Wind Harmer
13.172
274729ELWOOD EC;1P
Adder
7.733
274730ELWOOD EC;6P
Adder
7.734
274734ELWOOD EC;8P
Adder
7.734
274736ELWOOD EC;9P
Adder
7.734
943121AE2-341 GEN
Solar/Wind Harmer
6.976
943591AF1-030 GEN
Solar/Wind Harmer
4.651
274862TOP CROP ;2U
Solar/Wind Harmer
2.351
944531AF1-118 GEN
Solar/Wind Harmer
16.213
274682WAUKEGAN ;7U
Adder
8.304
274760LEE CO EC;1U
Adder
4.157
274767LEE CO EC;8U
Adder
4.108
962511AG1-100 GEN
Solar/Wind Helper
0.371
203854AF2-039 C
Solar/Wind Helper
0.152
20398826ARMNA MT
Solar/Wind Helper
0.713
23888502TROY G1
50/50
1.84
23888602TROY G2
50/50
1.84
23860102FRMENG 1
50/50
1.762
23860202FRMENG 2
50/50
1.762
24191202EL_AA1-006
50/50
0.345
241886AC2-103 GEN2
Solar/Wind Harmer
12.88
945411AF1-206 GEN
Solar/Wind Harmer
8.713
270361_3
Solar/Wind Harmer
9.854
270575GUS2 35KV
Solar/Wind Harmer
11.609
270499AE1-146 GEN
Solar/Wind Harmer
2.715
945641AF1-229 GEN
Solar/Wind Harmer
3.712
270428AC2-015 C
Solar/Wind Harmer
4.298
971549AH1-272 GEN
Solar/Wind Harmer
13.571
270404AC1-167 GEN
Solar/Wind Harmer
0.763
966831AG1-554 GEN
Solar/Wind Harmer
0.802
270007AE1-245 C
Solar/Wind Harmer
3.44
957201AF2-014 GEN
Solar/Wind Harmer
2.844
270435AC2-044 GEN
Solar/Wind Harmer
1.254
944161AF1-084 GEN
Solar/Wind Harmer
1.347
965041AG1-368 GEN
Solar/Wind Harmer
5.888
247521TR3_G114
Solar/Wind Harmer
1.97
270191TR4_S_V150
Solar/Wind Harmer
1.758
965051AG1-369 GEN
Solar/Wind Harmer
2.928
970031AG2-029 GEN
Solar/Wind Harmer
14.262
270302AB2-170 GEN
Solar/Wind Harmer
4.734
971567AH1-282 GEN
Solar/Wind Harmer
2.806
959331AF2-224 GEN
Solar/Wind Harmer
5.62
971771AH1-392 GEN
Solar/Wind Harmer
5.033
270526AF1-158 GEN
Solar/Wind Harmer
2.485
270377AD1-106 GEN
Solar/Wind Harmer
2.862
270223U2-072_GEN1
Solar/Wind Harmer
1.036
270224U2-072_GEN2
Solar/Wind Harmer
1.036
270227U2-072_GEN3
Solar/Wind Harmer
1.036
270228U2-072_GEN4
Solar/Wind Harmer
1.036
270231U2-072_GEN5
Solar/Wind Harmer
1.036
270578AF1-285 GEN2
Solar/Wind Harmer
0.244
960681AF2-359 GEN
Solar/Wind Harmer
1.983
963791AG1-232 GEN
Solar/Wind Harmer
7.014
270071AF1-092 GEN
Solar/Wind Harmer
7.381
958391AF2-133 GEN
Solar/Wind Harmer
4.378
959141AF2-205 GEN
Solar/Wind Harmer
2.899
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.698
274800UNIV PARK;3U
Adder
2.775
274801UNIV PARK;4U
Adder
2.775
960591AF2-350 GEN
Solar/Wind Harmer
4.752
274775LINCOLN ;6U
Adder
2.945
274776LINCOLN ;7U
Adder
2.945
274777LINCOLN ;8U
Adder
2.945
972228AH1-698 GEN2
Adder
1.755
972227AH1-698 GEN1
Adder
1.236
274687WILL CNTY;4U
Adder
13.196
274687WILL CNTY;4U
Adder
13.196
274675JOLIET 29;7U
Adder
14.46
274675JOLIET 29;7U
Adder
13.943
276893AG1-478 C
Solar/Wind Harmer
0.259
274728ELWOOD EC;5P
Adder
7.734
274731ELWOOD EC;2P
Adder
7.733
274733ELWOOD EC;3P
Adder
7.733
274735ELWOOD EC;4P
Adder
7.733
970833AG2-524 GEN
Solar/Wind Harmer
4.087
970833AG2-524 GEN
Solar/Wind Harmer
1.901
274744AC1-111 GEN8
Adder
2.601
274746AC1-111 G10
Adder
2.601
970073AG2-061 GEN
Solar/Wind Harmer
1.072
24729505KEY G4
Adder
2.976
274823ROCKFORD ;21
Adder
8.809
972267AH1-718 GEN
Adder
1.848
241985AE1-237 GEN
Solar/Wind Helper
0.143
241982AE2-343 S C
Solar/Wind Helper
0.128
203846AF2-130 C
Solar/Wind Helper
0.268
241997AF1-093 GEN
Solar/Wind Helper
0.141
20334926Z1-069 C
Solar/Wind Helper
0.698
24189902OREGON_CT2
50/50
2.684
23856402BAYSG1
50/50
1.439
23888702TROY G3
50/50
1.84
972253AH1-711 GEN
50/50
56.25
23860302FRMENG 3
50/50
3.574
23920202STRYCT
50/50
2.06
241885AC2-103 GEN1
Solar/Wind Harmer
12.88
241807AE2-176_GEN
Solar/Wind Harmer
7.406
241858AF1-205_GEN
Solar/Wind Harmer
5.952
241840AF1-064_GEN
Solar/Wind Harmer
1.529
23906502RICHG2&3
Adder
1.43
960841AF2-375 GEN
Solar/Wind Harmer
4.353
270297AD1-101 GEN
Solar/Wind Harmer
1.524
270258AD1-119 GEN
Solar/Wind Harmer
1.373
24441205WTRV SLR C
Solar/Wind Harmer
0.085
246936BC-WTG1
Solar/Wind Harmer
2.453
270489AE1-102 GEN1
Solar/Wind Harmer
0.815
965421AG1-410 GEN
Solar/Wind Harmer
18.623
270449AD2-020 GEN
Solar/Wind Harmer
1.686
943021AE2-325 GEN
Solar/Wind Harmer
2.192
945111AF1-176 GEN
Solar/Wind Harmer
10.516
957891AF2-083 GEN
Solar/Wind Harmer
8.804
24639705ELKHART HY
Adder
0.088
270216AD2-079_GEN
Solar/Wind Harmer
0.344
270317AD1-130_GEN
Solar/Wind Harmer
1.81
270485AE1-090_GEN
Solar/Wind Harmer
0.342
965011AG1-365 GEN
Solar/Wind Harmer
5.62
270391AF1-285 GEN3
Solar/Wind Harmer
0.635
270578AF1-285 GEN2
Solar/Wind Harmer
0.635
970373AG2-245 GEN
Solar/Wind Harmer
10.575
270055AF2-134 C O1
Solar/Wind Harmer
1.498
241847AF2-150_GEN
Solar/Wind Harmer
2.052
274751CRETE EC ;1U
Adder
2.388
274754CRETE EC ;4U
Adder
2.388
958381AF2-132 GEN
Solar/Wind Harmer
4.418
964861AG1-349 GEN
Solar/Wind Harmer
3.822
971917AH1-482 GEN
Solar/Wind Harmer
4.41
274723RIVER EC ;12
Adder
8.689
274812UNIV PK N;8U
Adder
2.417
274802UNIV PARK;5U
Adder
2.784
940581AE2-045 GEN
Solar/Wind Harmer
4.848
971605AH1-302 GEN
Solar/Wind Harmer
4.145
972207SS24-0001
Solar/Wind Harmer
10.471
274773LINCOLN ;4U
Adder
2.945
274774LINCOLN ;5U
Adder
2.945
274676JOLIET 29;8U
Adder
14.459
941551AE2-152 GEN
Solar/Wind Harmer
2.135
274732ELWOOD EC;7P
Adder
7.734
274674JOLIET 9 ;6U
Adder
7.243
274871GR RIDGE ;2U
Solar/Wind Harmer
3.598
274847GR RIDGE ;BU
Solar/Wind Harmer
2.366
270024AE2-089 GEN
Solar/Wind Harmer
2.193
274745AC1-111 GEN9
Adder
2.601
276694AA1-018 GEN2
Solar/Wind Harmer
2.934
276691AA1-018 GEN1
Solar/Wind Harmer
0.351
274861TOP CROP ;1U
Solar/Wind Harmer
2.816
274682WAUKEGAN ;7U
Adder
8.304
274828WAUKEGAN ;BP
Adder
5.099
276805AD2-038 GEN
Solar/Wind Harmer
2.364
939401AE1-172 GEN
Solar/Wind Harmer
6.403
274822ROCKFORD ;11
Adder
8.874
274761LEE CO EC;2U
Adder
4.157
274766LEE CO EC;7U
Adder
4.108
203947AF1-006 C
Solar/Wind Helper
0.414
961971AG1-040 GEN
Solar/Wind Helper
0.362
203830AF1-094 GEN
Solar/Wind Helper
0.351
203979AG1-198 GEN
Solar/Wind Helper
0.211
241966AE1-183 GEN
Solar/Wind Helper
0.141
254303AC2-168 GEN
Solar/Wind Helper
0.082
203855AF2-088 C
Solar/Wind Helper
0.073
23867002DVBSG1
50/50
12.652
24190002OREGON_ST1
50/50
3.611
24189802OREGON_CT1
50/50
2.74
23888802TROY G4
50/50
1.84
241996AE2-282_GEN
Solar/Wind Harmer
2.327
241808AF1-120 C
Solar/Wind Harmer
1.297
247522W1-056 GEN
Solar/Wind Harmer
1.802
944231AF1-091 GEN
Solar/Wind Harmer
12.652
247607V1-011 GEN
Solar/Wind Harmer
2.518
942801AE2-298 GEN
Solar/Wind Harmer
0.96
246937BC-WTG2
Solar/Wind Harmer
2.453
961051AF2-396 GEN
Solar/Wind Harmer
9.479
961051AF2-396 GEN
Solar/Wind Harmer
4.409
270246TR4_N_V150
Solar/Wind Harmer
0.499
270247TR4_N_V136
Solar/Wind Harmer
0.499
247620Y3-023
Adder
0.266
270462AD2-086
Solar/Wind Harmer
3.932
965681AG1-436 GEN
Solar/Wind Harmer
6.56
965791AG1-447 GEN
Solar/Wind Harmer
3.356
970349AG2-230 GEN
Solar/Wind Harmer
7.839
270535AF1-215 GEN1
Solar/Wind Harmer
2.247
270536AF1-215 GEN2
Solar/Wind Harmer
2.247
274805UNIV PK N;1U
Adder
2.423
274808UNIV PK N;4U
Adder
2.407
274888KELLY CRK;1U
Solar/Wind Harmer
2.804
276776AD2-060 GEN
Solar/Wind Harmer
0.199
958011AF2-095 GEN
Solar/Wind Harmer
6.843
970941AG2-585 GEN
Solar/Wind Harmer
2.614
274770LINCOLN ;1U
Adder
2.945
274771LINCOLN ;2U
Adder
2.945
942221AE2-234 GEN
Solar/Wind Harmer
1.662
276897AD1-100 C
Solar/Wind Harmer
21.871
276893AG1-478 C
Solar/Wind Harmer
0.206
274674JOLIET 9 ;6U
Adder
7.243
958481AF2-142 GEN
Solar/Wind Harmer
6.974
945421AF1-207 GEN
Solar/Wind Harmer
6.519
957841AF2-078 GEN
Solar/Wind Harmer
2.806
274696ROCKY RD ;4P
Adder
5.264
274695ROCKY RD ;2P
Adder
5.143
274693ROCKY RD ;1P
Adder
5.093
274697ROCKY RD ;3P
Adder
1.397
274683WAUKEGAN ;8U
Adder
9.728
274683WAUKEGAN ;8U
Adder
8.2
958491AF2-143 GEN
Solar/Wind Harmer
6.914
276901AD2-066 C O1
Solar/Wind Harmer
1.611
972235AH1-702 GEN1
Adder
1.138
972236AH1-702 GEN2
Adder
0.989
274764LEE CO EC;5U
Adder
4.167
274765LEE CO EC;6U
Adder
4.167
274762LEE CO EC;3U
Adder
4.157
274763LEE CO EC;4U
Adder
4.118
25326509SID D
Adder
0.583
247621Y3-024
Adder
0.104
203835AF1-098 GEN
Solar/Wind Helper
1.432
241967AE2-285_GEN
Solar/Wind Helper
0.366
241801AE1-079 GEN
Solar/Wind Helper
0.143
254304AE2-114 C
Solar/Wind Helper
0.122
254305AE2-115 C
Solar/Wind Helper
0.122
962101AG1-054 GEN
Solar/Wind Helper
0.353
203804AE2-113_GEN
Solar/Wind Helper
0.938
940863AE2-074 GEN
Solar/Wind Helper
0.243
946381AF1-302 GEN
Solar/Wind Helper
0.114
203954AE2-126 C
Solar/Wind Helper
0.236
203853AF1-134 C O1
Solar/Wind Helper
0.223
203818AF1-086 GEN
Solar/Wind Helper
0.773
962691AG1-118 GEN
Solar/Wind Harmer
11.908
990142J1224
External Queue
13.564727783203125
990527J1329
External Queue
1.855639934539795
991182J1586 G
External Queue
25.35342025756836
991177J1571 G
External Queue
15.755910873413086
LAGNLTFEXP_LAGN->PJM
CLTF
5.165
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.347
NYPJM->LTFIMP_NY
CLTF
2.183
LGEELTFEXP_LGEE->PJM
CLTF
2.113
WECLTFEXP_WEC->PJM
CLTF
1.724
AG2-052LTFEXP_AG2-052->PJM
LTF
0.111
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.789
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.306
MECLTFEXP_MEC->PJM
CLTF
6.726
SIGELTFEXP_SIGE->PJM
CLTF
0.176
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.283

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.72 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2323.45
MW Contribution:
13.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.524
241832AE2-181_GEN
Solar/Wind Harmer
2.101
958321AF2-126 GEN
Solar/Wind Harmer
1.635
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270541AE2-072 C
Solar/Wind Harmer
4.719
270044AE2-322 C
Solar/Wind Harmer
0.92
270588AE1-091_GEN
Solar/Wind Harmer
7.544
958091AF2-103 GEN
Solar/Wind Harmer
0.102
246938BC-WTG3
Solar/Wind Harmer
2.48
270491AE1-102 GEN2
Solar/Wind Harmer
0.81
24695305TIMB G C
Solar/Wind Harmer
2.018
945111AF1-176 GEN
Solar/Wind Harmer
3.317
270505AE1-170 C O1
Solar/Wind Harmer
8.789
270063AE2-323 C
Solar/Wind Harmer
1.252
247643Z2-116 C
Solar/Wind Harmer
0.039
965021AG1-366 GEN
Solar/Wind Harmer
1.3
24441505OLIV SLR
Solar/Wind Harmer
0.073
270043AE2-236 GEN
Solar/Wind Harmer
2.894
942871AE2-306 GEN
Solar/Wind Harmer
0.473
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
2.6
972231SS25-0005
Solar/Wind Harmer
4.614
972181SS23-001
Solar/Wind Harmer
2.883
274752CRETE EC ;2U
Adder
2.376
274753CRETE EC ;3U
Adder
2.376
964401AG1-302 GEN
Solar/Wind Harmer
4.396
274724RIVER EC ;11
Adder
8.542
274814UNIV PK N;0U
Adder
2.426
274807UNIV PK N;3U
Adder
2.421
274811UNIV PK N;7U
Adder
2.405
276164X3-005 C
Solar/Wind Harmer
0.336
961961AG1-039 GEN
Solar/Wind Harmer
1.362
274803UNIV PARK;6U
Adder
2.77
274826FISK ;BP
Adder
5.192
972038AH1-567 GEN2
Adder
0.173
274887GEN-1.85
Solar/Wind Harmer
2.519
276772AC2-154 GEN
Solar/Wind Harmer
1.319
276843GEN-1.7
Solar/Wind Harmer
0.271
276806AD2-047 C O1
Solar/Wind Harmer
5.057
274772LINCOLN ;3U
Adder
2.93
972259AH1-714 GEN
Adder
8.953
274676JOLIET 29;8U
Adder
13.872
939351AE1-166 GEN
Solar/Wind Harmer
2.778
970707AG2-453 GEN
Solar/Wind Harmer
13.105
274729ELWOOD EC;1P
Adder
7.694
274730ELWOOD EC;6P
Adder
7.694
274734ELWOOD EC;8P
Adder
7.694
274736ELWOOD EC;9P
Adder
7.694
943121AE2-341 GEN
Solar/Wind Harmer
6.94
943591AF1-030 GEN
Solar/Wind Harmer
4.627
274862TOP CROP ;2U
Solar/Wind Harmer
2.339
944531AF1-118 GEN
Solar/Wind Harmer
16.12
274682WAUKEGAN ;7U
Adder
8.262
274760LEE CO EC;1U
Adder
4.136
274767LEE CO EC;8U
Adder
4.087
962511AG1-100 GEN
Solar/Wind Helper
0.366
203854AF2-039 C
Solar/Wind Helper
0.15
20398826ARMNA MT
Solar/Wind Helper
0.705
276868AE1-113 GEN
Solar/Wind Harmer
2.634
23888502TROY G1
50/50
1.835
23888602TROY G2
50/50
1.835
23860102FRMENG 1
50/50
1.737
23860202FRMENG 2
50/50
1.737
24191202EL_AA1-006
50/50
0.334
945411AF1-206 GEN
Solar/Wind Harmer
8.678
270361_3
Solar/Wind Harmer
9.759
270575GUS2 35KV
Solar/Wind Harmer
11.497
270499AE1-146 GEN
Solar/Wind Harmer
2.689
945641AF1-229 GEN
Solar/Wind Harmer
3.679
270428AC2-015 C
Solar/Wind Harmer
4.165
971549AH1-272 GEN
Solar/Wind Harmer
13.515
270404AC1-167 GEN
Solar/Wind Harmer
0.758
966831AG1-554 GEN
Solar/Wind Harmer
0.792
270007AE1-245 C
Solar/Wind Harmer
3.418
957201AF2-014 GEN
Solar/Wind Harmer
2.826
270435AC2-044 GEN
Solar/Wind Harmer
1.246
944161AF1-084 GEN
Solar/Wind Harmer
1.341
965041AG1-368 GEN
Solar/Wind Harmer
5.853
247521TR3_G114
Solar/Wind Harmer
1.958
270191TR4_S_V150
Solar/Wind Harmer
1.748
965051AG1-369 GEN
Solar/Wind Harmer
2.91
970031AG2-029 GEN
Solar/Wind Harmer
14.189
270302AB2-170 GEN
Solar/Wind Harmer
4.7
959331AF2-224 GEN
Solar/Wind Harmer
5.588
971771AH1-392 GEN
Solar/Wind Harmer
5.008
971567AH1-282 GEN
Solar/Wind Harmer
2.752
270526AF1-158 GEN
Solar/Wind Harmer
2.473
270377AD1-106 GEN
Solar/Wind Harmer
2.813
960681AF2-359 GEN
Solar/Wind Harmer
1.973
270223U2-072_GEN1
Solar/Wind Harmer
1.029
270224U2-072_GEN2
Solar/Wind Harmer
1.029
270227U2-072_GEN3
Solar/Wind Harmer
1.029
270228U2-072_GEN4
Solar/Wind Harmer
1.029
270231U2-072_GEN5
Solar/Wind Harmer
1.029
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
963791AG1-232 GEN
Solar/Wind Harmer
6.973
270071AF1-092 GEN
Solar/Wind Harmer
7.341
958391AF2-133 GEN
Solar/Wind Harmer
4.356
959141AF2-205 GEN
Solar/Wind Harmer
2.884
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.679
274800UNIV PARK;3U
Adder
2.76
274801UNIV PARK;4U
Adder
2.76
960591AF2-350 GEN
Solar/Wind Harmer
4.728
274775LINCOLN ;6U
Adder
2.93
274776LINCOLN ;7U
Adder
2.93
274777LINCOLN ;8U
Adder
2.93
972228AH1-698 GEN2
Adder
1.746
972227AH1-698 GEN1
Adder
1.229
274687WILL CNTY;4U
Adder
13.128
274687WILL CNTY;4U
Adder
13.128
274675JOLIET 29;7U
Adder
14.386
274675JOLIET 29;7U
Adder
13.872
276893AG1-478 C
Solar/Wind Harmer
0.258
274728ELWOOD EC;5P
Adder
7.694
274731ELWOOD EC;2P
Adder
7.694
274733ELWOOD EC;3P
Adder
7.694
274735ELWOOD EC;4P
Adder
7.694
970833AG2-524 GEN
Solar/Wind Harmer
4.066
970833AG2-524 GEN
Solar/Wind Harmer
1.891
274744AC1-111 GEN8
Adder
2.587
274746AC1-111 G10
Adder
2.587
970073AG2-061 GEN
Solar/Wind Harmer
1.066
24729505KEY G4
Adder
2.959
274823ROCKFORD ;21
Adder
8.764
972267AH1-718 GEN
Adder
1.839
241886AC2-103 GEN2
Solar/Wind Helper
4.613
241985AE1-237 GEN
Solar/Wind Helper
0.141
241982AE2-343 S C
Solar/Wind Helper
0.127
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
20334926Z1-069 C
Solar/Wind Helper
0.69
24189902OREGON_CT2
50/50
2.678
23856402BAYSG1
50/50
1.432
23888702TROY G3
50/50
1.835
972253AH1-711 GEN
50/50
56.096
23867002DVBSG1
50/50
12.657
24190002OREGON_ST1
50/50
3.603
24189802OREGON_CT1
50/50
2.734
23888802TROY G4
50/50
1.835
241996AE2-282_GEN
Solar/Wind Harmer
2.317
241808AF1-120 C
Solar/Wind Harmer
1.292
247522W1-056 GEN
Solar/Wind Harmer
1.78
944231AF1-091 GEN
Solar/Wind Harmer
12.586
247607V1-011 GEN
Solar/Wind Harmer
2.502
942801AE2-298 GEN
Solar/Wind Harmer
0.953
246937BC-WTG2
Solar/Wind Harmer
2.437
961051AF2-396 GEN
Solar/Wind Harmer
9.435
961051AF2-396 GEN
Solar/Wind Harmer
4.388
270246TR4_N_V150
Solar/Wind Harmer
0.496
270247TR4_N_V136
Solar/Wind Harmer
0.496
247620Y3-023
Adder
0.264
270462AD2-086
Solar/Wind Harmer
3.903
965681AG1-436 GEN
Solar/Wind Harmer
6.527
965791AG1-447 GEN
Solar/Wind Harmer
3.34
970349AG2-230 GEN
Solar/Wind Harmer
7.8
270535AF1-215 GEN1
Solar/Wind Harmer
2.236
270536AF1-215 GEN2
Solar/Wind Harmer
2.236
274805UNIV PK N;1U
Adder
2.41
274808UNIV PK N;4U
Adder
2.394
274888KELLY CRK;1U
Solar/Wind Harmer
2.79
276776AD2-060 GEN
Solar/Wind Harmer
0.198
958011AF2-095 GEN
Solar/Wind Harmer
6.808
970941AG2-585 GEN
Solar/Wind Harmer
2.6
274770LINCOLN ;1U
Adder
2.93
274771LINCOLN ;2U
Adder
2.93
942221AE2-234 GEN
Solar/Wind Harmer
1.653
276897AD1-100 C
Solar/Wind Harmer
21.759
276893AG1-478 C
Solar/Wind Harmer
0.205
274674JOLIET 9 ;6U
Adder
7.206
958481AF2-142 GEN
Solar/Wind Harmer
6.939
945421AF1-207 GEN
Solar/Wind Harmer
6.485
957841AF2-078 GEN
Solar/Wind Harmer
2.792
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.066
274697ROCKY RD ;3P
Adder
1.39
274696ROCKY RD ;4P
Adder
5.238
274683WAUKEGAN ;8U
Adder
9.678
274683WAUKEGAN ;8U
Adder
8.158
958491AF2-143 GEN
Solar/Wind Harmer
6.878
276901AD2-066 C O1
Solar/Wind Harmer
1.603
962691AG1-118 GEN
Solar/Wind Harmer
13.707
972235AH1-702 GEN1
Adder
1.132
972236AH1-702 GEN2
Adder
0.984
274764LEE CO EC;5U
Adder
4.146
274765LEE CO EC;6U
Adder
4.146
274762LEE CO EC;3U
Adder
4.136
274763LEE CO EC;4U
Adder
4.097
25326509SID D
Adder
0.579
203835AF1-098 GEN
Solar/Wind Helper
1.415
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.142
254304AE2-114 C
Solar/Wind Helper
0.12
254305AE2-115 C
Solar/Wind Helper
0.12
962101AG1-054 GEN
Solar/Wind Helper
0.349
203804AE2-113_GEN
Solar/Wind Helper
0.927
940863AE2-074 GEN
Solar/Wind Helper
0.24
946381AF1-302 GEN
Solar/Wind Helper
0.112
203954AE2-126 C
Solar/Wind Helper
0.233
23860302FRMENG 3
50/50
3.525
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
7.281
241858AF1-205_GEN
Solar/Wind Harmer
5.928
241840AF1-064_GEN
Solar/Wind Harmer
1.521
23906502RICHG2&3
Adder
1.423
960841AF2-375 GEN
Solar/Wind Harmer
4.311
270297AD1-101 GEN
Solar/Wind Harmer
1.514
270258AD1-119 GEN
Solar/Wind Harmer
1.365
24441205WTRV SLR C
Solar/Wind Harmer
0.084
246936BC-WTG1
Solar/Wind Harmer
2.437
270489AE1-102 GEN1
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.51
270449AD2-020 GEN
Solar/Wind Harmer
1.679
943021AE2-325 GEN
Solar/Wind Harmer
2.181
945111AF1-176 GEN
Solar/Wind Harmer
10.467
957891AF2-083 GEN
Solar/Wind Harmer
8.762
24639705ELKHART HY
Adder
0.088
270216AD2-079_GEN
Solar/Wind Harmer
0.342
270317AD1-130_GEN
Solar/Wind Harmer
1.797
270485AE1-090_GEN
Solar/Wind Harmer
0.339
965011AG1-365 GEN
Solar/Wind Harmer
5.588
270391AF1-285 GEN3
Solar/Wind Harmer
0.63
270578AF1-285 GEN2
Solar/Wind Harmer
0.63
970373AG2-245 GEN
Solar/Wind Harmer
10.522
270055AF2-134 C O1
Solar/Wind Harmer
1.491
274751CRETE EC ;1U
Adder
2.376
274754CRETE EC ;4U
Adder
2.376
958381AF2-132 GEN
Solar/Wind Harmer
4.396
964861AG1-349 GEN
Solar/Wind Harmer
3.802
971917AH1-482 GEN
Solar/Wind Harmer
4.387
274723RIVER EC ;12
Adder
8.645
274812UNIV PK N;8U
Adder
2.405
241847AF2-150_GEN
Solar/Wind Harmer
1.974
274802UNIV PARK;5U
Adder
2.77
940581AE2-045 GEN
Solar/Wind Harmer
4.823
971605AH1-302 GEN
Solar/Wind Harmer
4.124
972207SS24-0001
Solar/Wind Harmer
10.417
274773LINCOLN ;4U
Adder
2.93
274774LINCOLN ;5U
Adder
2.93
274676JOLIET 29;8U
Adder
14.386
941551AE2-152 GEN
Solar/Wind Harmer
2.124
274732ELWOOD EC;7P
Adder
7.694
274674JOLIET 9 ;6U
Adder
7.206
274871GR RIDGE ;2U
Solar/Wind Harmer
3.579
274847GR RIDGE ;BU
Solar/Wind Harmer
2.353
270024AE2-089 GEN
Solar/Wind Harmer
2.18
274745AC1-111 GEN9
Adder
2.587
276694AA1-018 GEN2
Solar/Wind Harmer
2.919
276691AA1-018 GEN1
Solar/Wind Harmer
0.349
274861TOP CROP ;1U
Solar/Wind Harmer
2.802
274682WAUKEGAN ;7U
Adder
8.262
274828WAUKEGAN ;BP
Adder
5.073
276805AD2-038 GEN
Solar/Wind Harmer
2.351
939401AE1-172 GEN
Solar/Wind Harmer
6.37
274822ROCKFORD ;11
Adder
8.828
274761LEE CO EC;2U
Adder
4.136
274766LEE CO EC;7U
Adder
4.087
241885AC2-103 GEN1
Solar/Wind Helper
4.613
203947AF1-006 C
Solar/Wind Helper
0.409
961971AG1-040 GEN
Solar/Wind Helper
0.358
203830AF1-094 GEN
Solar/Wind Helper
0.347
203979AG1-198 GEN
Solar/Wind Helper
0.208
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203855AF2-088 C
Solar/Wind Helper
0.072
276882AE2-255 GEN
Solar/Wind Harmer
0.878
990142J1224
External Queue
13.534384727478027
990527J1329
External Queue
1.8514890670776367
991182J1586 G
External Queue
25.29424285888672
991177J1571 G
External Queue
15.716124534606934
LAGNLTFEXP_LAGN->PJM
CLTF
5.139
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.291
TVALTFEXP_TVA->PJM
CLTF
2.335
NYPJM->LTFIMP_NY
CLTF
2.157
LGEELTFEXP_LGEE->PJM
CLTF
2.099
WECLTFEXP_WEC->PJM
CLTF
1.715
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.256
MECLTFEXP_MEC->PJM
CLTF
6.691
SIGELTFEXP_SIGE->PJM
CLTF
0.175
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.063

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.9 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2176.69
MW Contribution:
10.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
1.834
23888602TROY G2
50/50
1.834
23860102FRMENG 1
50/50
1.736
23860202FRMENG 2
50/50
1.736
24191202EL_AA1-006
50/50
0.334
241886AC2-103 GEN2
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
270361_3
Solar/Wind Harmer
5.343
270575GUS2 35KV
Solar/Wind Harmer
5.343
270499AE1-146 GEN
Solar/Wind Harmer
0.024
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
10.511
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.55
965041AG1-368 GEN
Solar/Wind Harmer
4.077
247521TR3_G114
Solar/Wind Harmer
0.147
965051AG1-369 GEN
Solar/Wind Harmer
2.027
970031AG2-029 GEN
Solar/Wind Harmer
2.141
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.55
959331AF2-224 GEN
Solar/Wind Harmer
2.724
971771AH1-392 GEN
Solar/Wind Harmer
3.876
971567AH1-282 GEN
Solar/Wind Harmer
2.938
270526AF1-158 GEN
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
1.42
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
963791AG1-232 GEN
Solar/Wind Harmer
4.856
270071AF1-092 GEN
Solar/Wind Harmer
6.531
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.672
274800UNIV PARK;3U
Adder
2.755
274801UNIV PARK;4U
Adder
2.755
971611AH1-305 GEN
Solar/Wind Harmer
1.96
960591AF2-350 GEN
Solar/Wind Harmer
3.292
274775LINCOLN ;6U
Adder
3.98
274776LINCOLN ;7U
Adder
3.98
274777LINCOLN ;8U
Adder
3.98
972228AH1-698 GEN2
Adder
1.742
972227AH1-698 GEN1
Adder
1.227
274687WILL CNTY;4U
Adder
13.101
274687WILL CNTY;4U
Adder
13.101
274675JOLIET 29;7U
Adder
14.356
274675JOLIET 29;7U
Adder
13.843
23929302BS-PKR
50/50
2.522
958321AF2-126 GEN
Solar/Wind Harmer
1.267
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270541AE2-072 C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.737
246938BC-WTG3
Solar/Wind Harmer
0.156
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
24695305TIMB G C
Solar/Wind Harmer
0.357
945111AF1-176 GEN
Solar/Wind Harmer
3.312
270505AE1-170 C O1
Solar/Wind Harmer
4.285
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.297
270043AE2-236 GEN
Solar/Wind Harmer
2.351
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
1.811
274752CRETE EC ;2U
Adder
3.998
274753CRETE EC ;3U
Adder
3.998
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.524
274814UNIV PK N;0U
Adder
2.421
274807UNIV PK N;3U
Adder
2.416
274811UNIV PK N;7U
Adder
2.4
274803UNIV PARK;6U
Adder
2.764
274826FISK ;BP
Adder
5.181
972038AH1-567 GEN2
Adder
0.172
274887GEN-1.85
Solar/Wind Harmer
0.086
276843GEN-1.7
Solar/Wind Harmer
0.106
276806AD2-047 C O1
Solar/Wind Harmer
1.865
274772LINCOLN ;3U
Adder
3.98
972259AH1-714 GEN
Adder
8.934
274676JOLIET 29;8U
Adder
13.843
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
7.678
274730ELWOOD EC;6P
Adder
7.678
274734ELWOOD EC;8P
Adder
7.678
274736ELWOOD EC;9P
Adder
7.678
970707AG2-453 GEN
Solar/Wind Harmer
10.644
943121AE2-341 GEN
Solar/Wind Harmer
5.401
24189902OREGON_CT2
50/50
2.676
23856402BAYSG1
50/50
1.431
23888702TROY G3
50/50
1.834
972253AH1-711 GEN
50/50
56.063
23860302FRMENG 3
50/50
3.522
23920202STRYCT
50/50
2.05
241885AC2-103 GEN1
Solar/Wind Harmer
0
241807AE2-176_GEN
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
4.133
23906502RICHG2&3
Adder
1.422
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.175
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
965421AG1-410 GEN
Solar/Wind Harmer
12.893
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.178
945111AF1-176 GEN
Solar/Wind Harmer
7.29
957891AF2-083 GEN
Solar/Wind Harmer
6.781
24639705ELKHART HY
Adder
0.087
270317AD1-130_GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
3.892
970373AG2-245 GEN
Solar/Wind Harmer
7.327
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
3.998
274754CRETE EC ;4U
Adder
3.998
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.378
274723RIVER EC ;12
Adder
8.627
274812UNIV PK N;8U
Adder
2.4
274802UNIV PARK;5U
Adder
2.764
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.116
274773LINCOLN ;4U
Adder
3.98
274774LINCOLN ;5U
Adder
3.98
274676JOLIET 29;8U
Adder
14.356
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.678
274674JOLIET 9 ;6U
Adder
7.191
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
2.582
274728ELWOOD EC;5P
Adder
7.678
274731ELWOOD EC;2P
Adder
7.678
274733ELWOOD EC;3P
Adder
7.678
274735ELWOOD EC;4P
Adder
7.678
970833AG2-524 GEN
Solar/Wind Harmer
3.567
970833AG2-524 GEN
Solar/Wind Harmer
2.378
274744AC1-111 GEN8
Adder
2.582
274746AC1-111 G10
Adder
2.582
943591AF1-030 GEN
Solar/Wind Harmer
3.592
274862TOP CROP ;2U
Solar/Wind Harmer
0.435
944531AF1-118 GEN
Solar/Wind Harmer
14.371
274682WAUKEGAN ;7U
Adder
8.244
276868AE1-113 GEN
Solar/Wind Harmer
0.635
274879MINONK ;1U
Solar/Wind Harmer
0.133
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.174
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
959091AF2-200 GEN
Solar/Wind Harmer
6.276
970571AG2-364 GEN
Solar/Wind Harmer
6.253
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.127
274767LEE CO EC;8U
Adder
4.078
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.102
965091AG1-374 GEN
Solar/Wind Harmer
9.056
959611AF2-252 GEN
Solar/Wind Harmer
1.006
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.524
965931AG1-462 GEN
Solar/Wind Harmer
7.656
971087AG2-675 GEN
Solar/Wind Harmer
1.601
962511AG1-100 GEN
Solar/Wind Helper
0.367
203854AF2-039 C
Solar/Wind Helper
0.15
23867002DVBSG1
50/50
12.651
24190002OREGON_ST1
50/50
3.601
24189802OREGON_CT1
50/50
2.733
23888802TROY G4
50/50
1.834
970621AG2-405 GEN
Solar/Wind Harmer
0.951
944231AF1-091 GEN
Solar/Wind Harmer
11.237
970623AG2-406 GEN
Solar/Wind Harmer
0.857
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.175
961051AF2-396 GEN
Solar/Wind Harmer
8.281
961051AF2-396 GEN
Solar/Wind Harmer
5.52
270246TR4_N_V150
Solar/Wind Harmer
0.026
270247TR4_N_V136
Solar/Wind Harmer
0.026
247620Y3-023
Adder
0.264
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.545
965791AG1-447 GEN
Solar/Wind Harmer
3.333
970349AG2-230 GEN
Solar/Wind Harmer
5.432
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.405
274808UNIV PK N;4U
Adder
2.39
274888KELLY CRK;1U
Solar/Wind Harmer
0.192
276776AD2-060 GEN
Solar/Wind Harmer
0.351
958011AF2-095 GEN
Solar/Wind Harmer
4.74
970941AG2-585 GEN
Solar/Wind Harmer
1.81
274770LINCOLN ;1U
Adder
3.98
274771LINCOLN ;2U
Adder
3.98
942221AE2-234 GEN
Solar/Wind Harmer
1.321
276897AD1-100 C
Solar/Wind Harmer
8.153
276893AG1-478 C
Solar/Wind Harmer
0.217
274674JOLIET 9 ;6U
Adder
7.191
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.523
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.244
274828WAUKEGAN ;BP
Adder
5.062
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.38
276882AE2-255 GEN
Solar/Wind Harmer
0.371
962781AG1-127 GEN
Solar/Wind Harmer
3.022
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.661
957471AF2-041 GEN
Solar/Wind Harmer
9.414
959081AF2-199 GEN
Solar/Wind Harmer
3.138
971067AG2-660 GEN
Solar/Wind Harmer
1.046
274822ROCKFORD ;11
Adder
8.809
970569AG2-363 GEN
Solar/Wind Harmer
9.379
970819AG2-516 GEN
Solar/Wind Harmer
3.743
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.127
274766LEE CO EC;7U
Adder
4.078
958481AF2-142 GEN
Solar/Wind Harmer
4.831
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.226
274695ROCKY RD ;2P
Adder
5.106
274693ROCKY RD ;1P
Adder
5.056
274697ROCKY RD ;3P
Adder
1.387
274683WAUKEGAN ;8U
Adder
9.658
274683WAUKEGAN ;8U
Adder
8.141
958491AF2-143 GEN
Solar/Wind Harmer
4.789
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.543
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.276
971343AH1-151 GEN
Solar/Wind Harmer
6.276
972235AH1-702 GEN1
Adder
1.129
972236AH1-702 GEN2
Adder
0.982
938861AE1-114 GEN
Solar/Wind Harmer
1.758
274764LEE CO EC;5U
Adder
4.137
274765LEE CO EC;6U
Adder
4.137
970073AG2-061 GEN
Solar/Wind Harmer
1.064
24729505KEY G4
Adder
2.953
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.73
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.229
276861AD2-134 GEN
Solar/Wind Harmer
0.056
276863AD2-134 GEN
Solar/Wind Harmer
0.056
971171AH1-044 GEN
Solar/Wind Harmer
6.276
274823ROCKFORD ;21
Adder
8.745
970169AG2-114 GEN
Solar/Wind Harmer
3.121
926823AC1-168 GEN
Solar/Wind Harmer
0.531
274856ECOGROVE ;U1
Solar/Wind Harmer
0.073
971681AH1-341 GEN
Solar/Wind Harmer
4.997
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.835
276741O09 GEN1
Solar/Wind Harmer
0.109
274877BISHOP HL;1U
Solar/Wind Harmer
0.102
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.205
963841AG1-237 GEN
Solar/Wind Harmer
1.314
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.688
971609AH1-304 GEN
Solar/Wind Harmer
0.492
945581AF1-223 GEN
Solar/Wind Harmer
0
241985AE1-237 GEN
Solar/Wind Helper
0.141
241982AE2-343 S C
Solar/Wind Helper
0.127
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
20334926Z1-069 C
Solar/Wind Helper
0.691
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.906
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276708O09 GEN2
Solar/Wind Harmer
0.109
958861AF2-177 GEN
Solar/Wind Harmer
1.326
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.273
945371AF1-202 GEN
Solar/Wind Harmer
0
203947AF1-006 C
Solar/Wind Helper
0.409
961971AG1-040 GEN
Solar/Wind Helper
0.359
203830AF1-094 GEN
Solar/Wind Helper
0.348
203979AG1-198 GEN
Solar/Wind Helper
0.209
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203855AF2-088 C
Solar/Wind Helper
0.072
20398826ARMNA MT
Solar/Wind Helper
0.706
274762LEE CO EC;3U
Adder
4.127
274763LEE CO EC;4U
Adder
4.088
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.35
944541AF1-119 GEN
Solar/Wind Harmer
0.206
960971AF2-388 GEN
Solar/Wind Harmer
1.812
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.496
25326509SID D
Adder
0.577
942111AE2-223 GEN
Solar/Wind Harmer
0.992
970329AG2-216 GEN
Solar/Wind Harmer
1.308
960611AF2-352 GEN
Solar/Wind Harmer
1.006
270201AC2-176 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.655
270599AE1-208 GEN
Solar/Wind Harmer
2.759
203835AF1-098 GEN
Solar/Wind Helper
1.417
241967AE2-285_GEN
Solar/Wind Helper
0.363
241801AE1-079 GEN
Solar/Wind Helper
0.142
254304AE2-114 C
Solar/Wind Helper
0.121
254305AE2-115 C
Solar/Wind Helper
0.121
962101AG1-054 GEN
Solar/Wind Helper
0.35
203804AE2-113_GEN
Solar/Wind Helper
0.929
940863AE2-074 GEN
Solar/Wind Helper
0.241
946381AF1-302 GEN
Solar/Wind Helper
0.113
203954AE2-126 C
Solar/Wind Helper
0.234
203853AF1-134 C O1
Solar/Wind Helper
0.22
990142J1224
External Queue
13.534384727478027
990527J1329
External Queue
1.8514890670776367
991182J1586 G
External Queue
25.29424285888672
991177J1571 G
External Queue
15.716124534606934
LAGNLTFEXP_LAGN->PJM
CLTF
5.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.261
TVALTFEXP_TVA->PJM
CLTF
2.325
NYPJM->LTFIMP_NY
CLTF
2.163
LGEELTFEXP_LGEE->PJM
CLTF
2.093
WECLTFEXP_WEC->PJM
CLTF
1.711
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.219
MECLTFEXP_MEC->PJM
CLTF
6.675
SIGELTFEXP_SIGE->PJM
CLTF
0.174
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.932

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.49 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2168.95
MW Contribution:
10.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.524
958321AF2-126 GEN
Solar/Wind Harmer
1.268
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270541AE2-072 C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.742
246938BC-WTG3
Solar/Wind Harmer
0.157
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
24695305TIMB G C
Solar/Wind Harmer
0.357
945111AF1-176 GEN
Solar/Wind Harmer
3.317
270505AE1-170 C O1
Solar/Wind Harmer
4.292
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270043AE2-236 GEN
Solar/Wind Harmer
2.355
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
1.814
274752CRETE EC ;2U
Adder
4.006
274753CRETE EC ;3U
Adder
4.006
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.542
274814UNIV PK N;0U
Adder
2.426
274807UNIV PK N;3U
Adder
2.421
274811UNIV PK N;7U
Adder
2.405
274803UNIV PARK;6U
Adder
2.77
274826FISK ;BP
Adder
5.192
972038AH1-567 GEN2
Adder
0.173
274887GEN-1.85
Solar/Wind Harmer
0.086
276843GEN-1.7
Solar/Wind Harmer
0.107
276806AD2-047 C O1
Solar/Wind Harmer
1.869
274772LINCOLN ;3U
Adder
3.988
972259AH1-714 GEN
Adder
8.953
274676JOLIET 29;8U
Adder
13.872
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.667
274729ELWOOD EC;1P
Adder
7.694
274730ELWOOD EC;6P
Adder
7.694
274734ELWOOD EC;8P
Adder
7.694
274736ELWOOD EC;9P
Adder
7.694
943121AE2-341 GEN
Solar/Wind Harmer
5.412
943591AF1-030 GEN
Solar/Wind Harmer
3.599
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
944531AF1-118 GEN
Solar/Wind Harmer
14.401
274682WAUKEGAN ;7U
Adder
8.262
276868AE1-113 GEN
Solar/Wind Harmer
0.637
274879MINONK ;1U
Solar/Wind Harmer
0.133
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.181
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
959091AF2-200 GEN
Solar/Wind Harmer
6.289
970571AG2-364 GEN
Solar/Wind Harmer
6.267
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.136
274767LEE CO EC;8U
Adder
4.087
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.102
965091AG1-374 GEN
Solar/Wind Harmer
9.076
959611AF2-252 GEN
Solar/Wind Harmer
1.008
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.534
965931AG1-462 GEN
Solar/Wind Harmer
7.674
971087AG2-675 GEN
Solar/Wind Harmer
1.605
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.366
203854AF2-039 C
Solar/Wind Helper
0.15
20398826ARMNA MT
Solar/Wind Helper
0.705
24189902OREGON_CT2
50/50
2.678
23856402BAYSG1
50/50
1.432
23888702TROY G3
50/50
1.835
972253AH1-711 GEN
50/50
56.096
23860302FRMENG 3
50/50
3.525
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
4.136
23906502RICHG2&3
Adder
1.423
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.175
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
965421AG1-410 GEN
Solar/Wind Harmer
12.914
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.181
945111AF1-176 GEN
Solar/Wind Harmer
7.302
957891AF2-083 GEN
Solar/Wind Harmer
6.792
24639705ELKHART HY
Adder
0.088
270317AD1-130_GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
3.899
970373AG2-245 GEN
Solar/Wind Harmer
7.341
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.006
274754CRETE EC ;4U
Adder
4.006
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.387
274723RIVER EC ;12
Adder
8.645
274812UNIV PK N;8U
Adder
2.405
274802UNIV PARK;5U
Adder
2.77
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.124
274773LINCOLN ;4U
Adder
3.988
274774LINCOLN ;5U
Adder
3.988
274676JOLIET 29;8U
Adder
14.386
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.694
274674JOLIET 9 ;6U
Adder
7.206
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
2.587
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.524
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.262
274828WAUKEGAN ;BP
Adder
5.073
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.385
276882AE2-255 GEN
Solar/Wind Harmer
0.371
962781AG1-127 GEN
Solar/Wind Harmer
3.029
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.664
957471AF2-041 GEN
Solar/Wind Harmer
9.434
959081AF2-199 GEN
Solar/Wind Harmer
3.145
971067AG2-660 GEN
Solar/Wind Harmer
1.048
274822ROCKFORD ;11
Adder
8.828
970569AG2-363 GEN
Solar/Wind Harmer
9.4
970819AG2-516 GEN
Solar/Wind Harmer
3.751
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.136
274766LEE CO EC;7U
Adder
4.087
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.908
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276708O09 GEN2
Solar/Wind Harmer
0.109
23867002DVBSG1
50/50
12.657
24190002OREGON_ST1
50/50
3.603
24189802OREGON_CT1
50/50
2.734
23888802TROY G4
50/50
1.835
970621AG2-405 GEN
Solar/Wind Harmer
0.952
944231AF1-091 GEN
Solar/Wind Harmer
11.253
970623AG2-406 GEN
Solar/Wind Harmer
0.858
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.175
961051AF2-396 GEN
Solar/Wind Harmer
8.294
961051AF2-396 GEN
Solar/Wind Harmer
5.529
270246TR4_N_V150
Solar/Wind Harmer
0.026
270247TR4_N_V136
Solar/Wind Harmer
0.026
247620Y3-023
Adder
0.264
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.554
965791AG1-447 GEN
Solar/Wind Harmer
3.34
970349AG2-230 GEN
Solar/Wind Harmer
5.442
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.41
274808UNIV PK N;4U
Adder
2.394
274888KELLY CRK;1U
Solar/Wind Harmer
0.192
276776AD2-060 GEN
Solar/Wind Harmer
0.352
958011AF2-095 GEN
Solar/Wind Harmer
4.75
970941AG2-585 GEN
Solar/Wind Harmer
1.814
274770LINCOLN ;1U
Adder
3.988
274771LINCOLN ;2U
Adder
3.988
942221AE2-234 GEN
Solar/Wind Harmer
1.323
276897AD1-100 C
Solar/Wind Harmer
8.17
276893AG1-478 C
Solar/Wind Harmer
0.218
274674JOLIET 9 ;6U
Adder
7.206
958481AF2-142 GEN
Solar/Wind Harmer
4.841
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.066
274697ROCKY RD ;3P
Adder
1.39
274696ROCKY RD ;4P
Adder
5.238
274683WAUKEGAN ;8U
Adder
9.678
274683WAUKEGAN ;8U
Adder
8.158
958491AF2-143 GEN
Solar/Wind Harmer
4.799
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.563
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.289
971343AH1-151 GEN
Solar/Wind Harmer
6.289
972235AH1-702 GEN1
Adder
1.132
972236AH1-702 GEN2
Adder
0.984
938861AE1-114 GEN
Solar/Wind Harmer
1.762
274764LEE CO EC;5U
Adder
4.146
274765LEE CO EC;6U
Adder
4.146
274762LEE CO EC;3U
Adder
4.136
274763LEE CO EC;4U
Adder
4.097
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.351
944541AF1-119 GEN
Solar/Wind Harmer
0.207
960971AF2-388 GEN
Solar/Wind Harmer
1.816
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
958861AF2-177 GEN
Solar/Wind Harmer
1.329
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.283
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.613
203947AF1-006 C
Solar/Wind Helper
0.409
961971AG1-040 GEN
Solar/Wind Helper
0.358
203830AF1-094 GEN
Solar/Wind Helper
0.347
203979AG1-198 GEN
Solar/Wind Helper
0.208
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203855AF2-088 C
Solar/Wind Helper
0.072
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.497
25326509SID D
Adder
0.579
942111AE2-223 GEN
Solar/Wind Harmer
0.994
970329AG2-216 GEN
Solar/Wind Harmer
1.311
960611AF2-352 GEN
Solar/Wind Harmer
1.008
270201AC2-176 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.659
270599AE1-208 GEN
Solar/Wind Harmer
2.765
203835AF1-098 GEN
Solar/Wind Helper
1.415
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.142
254304AE2-114 C
Solar/Wind Helper
0.12
254305AE2-115 C
Solar/Wind Helper
0.12
962101AG1-054 GEN
Solar/Wind Helper
0.349
203804AE2-113_GEN
Solar/Wind Helper
0.927
940863AE2-074 GEN
Solar/Wind Helper
0.24
946381AF1-302 GEN
Solar/Wind Helper
0.112
203954AE2-126 C
Solar/Wind Helper
0.233
23888502TROY G1
50/50
1.835
23888602TROY G2
50/50
1.835
23860102FRMENG 1
50/50
1.737
23860202FRMENG 2
50/50
1.737
24191202EL_AA1-006
50/50
0.334
945411AF1-206 GEN
Solar/Wind Harmer
0
270361_3
Solar/Wind Harmer
5.347
270575GUS2 35KV
Solar/Wind Harmer
5.347
270499AE1-146 GEN
Solar/Wind Harmer
0.024
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
10.525
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.551
965041AG1-368 GEN
Solar/Wind Harmer
4.084
247521TR3_G114
Solar/Wind Harmer
0.147
965051AG1-369 GEN
Solar/Wind Harmer
2.03
970031AG2-029 GEN
Solar/Wind Harmer
2.145
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.551
959331AF2-224 GEN
Solar/Wind Harmer
2.729
971771AH1-392 GEN
Solar/Wind Harmer
3.882
971567AH1-282 GEN
Solar/Wind Harmer
2.943
270526AF1-158 GEN
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
1.423
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
963791AG1-232 GEN
Solar/Wind Harmer
4.865
270071AF1-092 GEN
Solar/Wind Harmer
6.544
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.679
274800UNIV PARK;3U
Adder
2.76
274801UNIV PARK;4U
Adder
2.76
971611AH1-305 GEN
Solar/Wind Harmer
1.964
960591AF2-350 GEN
Solar/Wind Harmer
3.298
274775LINCOLN ;6U
Adder
3.988
274776LINCOLN ;7U
Adder
3.988
274777LINCOLN ;8U
Adder
3.988
972228AH1-698 GEN2
Adder
1.746
972227AH1-698 GEN1
Adder
1.229
274687WILL CNTY;4U
Adder
13.128
274687WILL CNTY;4U
Adder
13.128
274675JOLIET 29;7U
Adder
14.386
274675JOLIET 29;7U
Adder
13.872
274728ELWOOD EC;5P
Adder
7.694
274731ELWOOD EC;2P
Adder
7.694
274733ELWOOD EC;3P
Adder
7.694
274735ELWOOD EC;4P
Adder
7.694
970833AG2-524 GEN
Solar/Wind Harmer
3.575
970833AG2-524 GEN
Solar/Wind Harmer
2.383
274744AC1-111 GEN8
Adder
2.587
274746AC1-111 G10
Adder
2.587
970073AG2-061 GEN
Solar/Wind Harmer
1.066
24729505KEY G4
Adder
2.959
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.74
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.231
276861AD2-134 GEN
Solar/Wind Harmer
0.056
276863AD2-134 GEN
Solar/Wind Harmer
0.056
971171AH1-044 GEN
Solar/Wind Harmer
6.289
274823ROCKFORD ;21
Adder
8.764
970169AG2-114 GEN
Solar/Wind Harmer
3.128
926823AC1-168 GEN
Solar/Wind Harmer
0.532
274856ECOGROVE ;U1
Solar/Wind Harmer
0.073
971681AH1-341 GEN
Solar/Wind Harmer
5.008
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.839
276741O09 GEN1
Solar/Wind Harmer
0.109
274877BISHOP HL;1U
Solar/Wind Harmer
0.102
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.212
963841AG1-237 GEN
Solar/Wind Harmer
1.317
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.692
971609AH1-304 GEN
Solar/Wind Harmer
0.493
945581AF1-223 GEN
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
4.613
241985AE1-237 GEN
Solar/Wind Helper
0.141
241982AE2-343 S C
Solar/Wind Helper
0.127
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
20334926Z1-069 C
Solar/Wind Helper
0.69
990142J1224
External Queue
13.534384727478027
990527J1329
External Queue
1.8514890670776367
991182J1586 G
External Queue
25.29424285888672
991177J1571 G
External Queue
15.716124534606934
LAGNLTFEXP_LAGN->PJM
CLTF
5.139
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.291
TVALTFEXP_TVA->PJM
CLTF
2.335
NYPJM->LTFIMP_NY
CLTF
2.157
LGEELTFEXP_LGEE->PJM
CLTF
2.099
WECLTFEXP_WEC->PJM
CLTF
1.715
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.256
MECLTFEXP_MEC->PJM
CLTF
6.691
SIGELTFEXP_SIGE->PJM
CLTF
0.175
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.063

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-007_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-007_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.37 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2298.14
MW Contribution:
14.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
2.617
972253AH1-711 GEN
50/50
80.001
23920202STRYCT
50/50
2.358
24189902OREGON_CT2
50/50
2.141
23906802RICHG5
50/50
1.013
23906502RICHG2&3
50/50
1.719
241858AF1-205_GEN
Solar/Wind Harmer
6.914
241840AF1-064_GEN
Solar/Wind Harmer
1.672
960841AF2-375 GEN
Solar/Wind Harmer
3.957
270297AD1-101 GEN
Solar/Wind Harmer
1.617
270258AD1-119 GEN
Solar/Wind Harmer
1.495
24441205WTRV SLR C
Solar/Wind Harmer
0.093
246936BC-WTG1
Solar/Wind Harmer
2.664
270489AE1-102 GEN1
Solar/Wind Harmer
0.885
965421AG1-410 GEN
Solar/Wind Harmer
20.235
270449AD2-020 GEN
Solar/Wind Harmer
1.844
943021AE2-325 GEN
Solar/Wind Harmer
2.396
945111AF1-176 GEN
Solar/Wind Harmer
11.502
957891AF2-083 GEN
Solar/Wind Harmer
9.629
24639705ELKHART HY
Adder
0.096
270216AD2-079_GEN
Solar/Wind Harmer
0.376
965011AG1-365 GEN
Solar/Wind Harmer
6.134
270317AD1-130_GEN
Solar/Wind Harmer
1.957
270485AE1-090_GEN
Solar/Wind Harmer
0.37
270391AF1-285 GEN3
Solar/Wind Harmer
0.687
270578AF1-285 GEN2
Solar/Wind Harmer
0.687
970373AG2-245 GEN
Solar/Wind Harmer
11.59
270055AF2-134 C O1
Solar/Wind Harmer
1.642
274751CRETE EC ;1U
Adder
2.619
274754CRETE EC ;4U
Adder
2.619
958381AF2-132 GEN
Solar/Wind Harmer
4.844
964861AG1-349 GEN
Solar/Wind Harmer
4.191
971917AH1-482 GEN
Solar/Wind Harmer
4.835
274723RIVER EC ;12
Adder
9.529
274812UNIV PK N;8U
Adder
2.651
274802UNIV PARK;5U
Adder
3.054
940581AE2-045 GEN
Solar/Wind Harmer
5.318
971605AH1-302 GEN
Solar/Wind Harmer
4.547
972207SS24-0001
Solar/Wind Harmer
11.487
274773LINCOLN ;4U
Adder
3.231
274774LINCOLN ;5U
Adder
3.231
274676JOLIET 29;8U
Adder
15.867
941551AE2-152 GEN
Solar/Wind Harmer
2.343
274732ELWOOD EC;7P
Adder
8.486
274674JOLIET 9 ;6U
Adder
7.948
274871GR RIDGE ;2U
Solar/Wind Harmer
3.948
274847GR RIDGE ;BU
Solar/Wind Harmer
2.596
270024AE2-089 GEN
Solar/Wind Harmer
2.4
274745AC1-111 GEN9
Adder
2.854
276694AA1-018 GEN2
Solar/Wind Harmer
3.22
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274861TOP CROP ;1U
Solar/Wind Harmer
3.091
274682WAUKEGAN ;7U
Adder
9.116
274828WAUKEGAN ;BP
Adder
5.598
276805AD2-038 GEN
Solar/Wind Harmer
2.595
939401AE1-172 GEN
Solar/Wind Harmer
7.029
276882AE2-255 GEN
Solar/Wind Harmer
1.698
274822ROCKFORD ;11
Adder
9.746
274761LEE CO EC;2U
Adder
4.567
274766LEE CO EC;7U
Adder
4.514
241885AC2-103 GEN1
Solar/Wind Helper
7.131
241807AE2-176_GEN
Solar/Wind Helper
1.742
203947AF1-006 C
Solar/Wind Helper
0.415
961971AG1-040 GEN
Solar/Wind Helper
0.363
203830AF1-094 GEN
Solar/Wind Helper
0.352
203979AG1-198 GEN
Solar/Wind Helper
0.211
241966AE1-183 GEN
Solar/Wind Helper
0.141
254303AC2-168 GEN
Solar/Wind Helper
0.082
203855AF2-088 C
Solar/Wind Helper
0.072
23906402RICHG1
50/50
1.723
23906502RICHG2&3
50/50
1.719
241832AE2-181_GEN
Solar/Wind Harmer
2.407
958321AF2-126 GEN
Solar/Wind Harmer
1.797
23929302BS-PKR
Adder
1.928
270541AE2-072 C
Solar/Wind Harmer
5.105
270044AE2-322 C
Solar/Wind Harmer
1.008
270588AE1-091_GEN
Solar/Wind Harmer
7.628
958091AF2-103 GEN
Solar/Wind Harmer
0.111
246938BC-WTG3
Solar/Wind Harmer
2.71
270491AE1-102 GEN2
Solar/Wind Harmer
0.885
24695305TIMB G C
Solar/Wind Harmer
2.196
945111AF1-176 GEN
Solar/Wind Harmer
3.645
270505AE1-170 C O1
Solar/Wind Harmer
9.658
270063AE2-323 C
Solar/Wind Harmer
1.378
247643Z2-116 C
Solar/Wind Harmer
0.043
965021AG1-366 GEN
Solar/Wind Harmer
1.426
24441505OLIV SLR
Solar/Wind Harmer
0.08
270043AE2-236 GEN
Solar/Wind Harmer
3.185
971347AH1-153 GEN
Solar/Wind Harmer
2.862
942871AE2-306 GEN
Solar/Wind Harmer
0.515
270391AF1-285 GEN3
Solar/Wind Harmer
0.264
972231SS25-0005
Solar/Wind Harmer
5.085
972181SS23-001
Solar/Wind Harmer
3.178
274752CRETE EC ;2U
Adder
2.619
274753CRETE EC ;3U
Adder
2.619
964401AG1-302 GEN
Solar/Wind Harmer
4.844
274724RIVER EC ;11
Adder
9.416
274814UNIV PK N;0U
Adder
2.675
274807UNIV PK N;3U
Adder
2.669
274811UNIV PK N;7U
Adder
2.651
276164X3-005 C
Solar/Wind Harmer
0.37
274803UNIV PARK;6U
Adder
3.054
274826FISK ;BP
Adder
5.725
972038AH1-567 GEN2
Adder
0.191
274887GEN-1.85
Solar/Wind Harmer
2.778
276772AC2-154 GEN
Solar/Wind Harmer
1.455
276843GEN-1.7
Solar/Wind Harmer
0.299
276806AD2-047 C O1
Solar/Wind Harmer
5.577
274772LINCOLN ;3U
Adder
3.231
972259AH1-714 GEN
Adder
9.874
274676JOLIET 29;8U
Adder
15.3
939351AE1-166 GEN
Solar/Wind Harmer
3.064
274729ELWOOD EC;1P
Adder
8.486
274730ELWOOD EC;6P
Adder
8.486
274734ELWOOD EC;8P
Adder
8.486
274736ELWOOD EC;9P
Adder
8.486
970707AG2-453 GEN
Solar/Wind Harmer
14.454
943121AE2-341 GEN
Solar/Wind Harmer
7.657
943591AF1-030 GEN
Solar/Wind Harmer
5.105
274862TOP CROP ;2U
Solar/Wind Harmer
2.581
944531AF1-118 GEN
Solar/Wind Harmer
17.76
274682WAUKEGAN ;7U
Adder
9.116
276868AE1-113 GEN
Solar/Wind Harmer
5.094
274879MINONK ;1U
Solar/Wind Harmer
3.396
274760LEE CO EC;1U
Adder
4.567
274767LEE CO EC;8U
Adder
4.514
962511AG1-100 GEN
Solar/Wind Helper
0.372
203854AF2-039 C
Solar/Wind Helper
0.15
23888502TROY G1
50/50
2.617
23888602TROY G2
50/50
2.617
23906902RICHG6
50/50
1.025
23906702RICHG4
50/50
1.02
945411AF1-206 GEN
Solar/Wind Harmer
9.797
945641AF1-229 GEN
Solar/Wind Harmer
4.031
270361_3
Solar/Wind Harmer
8.883
270575GUS2 35KV
Solar/Wind Harmer
10.465
270499AE1-146 GEN
Solar/Wind Harmer
2.498
971549AH1-272 GEN
Solar/Wind Harmer
14.836
270404AC1-167 GEN
Solar/Wind Harmer
0.831
270007AE1-245 C
Solar/Wind Harmer
3.7
957201AF2-014 GEN
Solar/Wind Harmer
3.088
270435AC2-044 GEN
Solar/Wind Harmer
1.362
944161AF1-084 GEN
Solar/Wind Harmer
1.473
966831AG1-554 GEN
Solar/Wind Harmer
0.779
965041AG1-368 GEN
Solar/Wind Harmer
6.393
247521TR3_G114
Solar/Wind Harmer
2.135
270191TR4_S_V150
Solar/Wind Harmer
1.905
965051AG1-369 GEN
Solar/Wind Harmer
3.172
970031AG2-029 GEN
Solar/Wind Harmer
15.603
959331AF2-224 GEN
Solar/Wind Harmer
6.134
971771AH1-392 GEN
Solar/Wind Harmer
5.508
270302AB2-170 GEN
Solar/Wind Harmer
5.12
270526AF1-158 GEN
Solar/Wind Harmer
2.72
971567AH1-282 GEN
Solar/Wind Harmer
2.923
960681AF2-359 GEN
Solar/Wind Harmer
2.172
270223U2-072_GEN1
Solar/Wind Harmer
1.121
270224U2-072_GEN2
Solar/Wind Harmer
1.121
270227U2-072_GEN3
Solar/Wind Harmer
1.121
270228U2-072_GEN4
Solar/Wind Harmer
1.121
270231U2-072_GEN5
Solar/Wind Harmer
1.121
270578AF1-285 GEN2
Solar/Wind Harmer
0.264
963791AG1-232 GEN
Solar/Wind Harmer
7.663
270071AF1-092 GEN
Solar/Wind Harmer
8.086
958391AF2-133 GEN
Solar/Wind Harmer
4.801
959141AF2-205 GEN
Solar/Wind Harmer
3.18
972037AH1-567 GEN1
Adder
0.096
274827FISK ;RP
Adder
4.057
274800UNIV PARK;3U
Adder
3.044
274801UNIV PARK;4U
Adder
3.044
960591AF2-350 GEN
Solar/Wind Harmer
5.213
274775LINCOLN ;6U
Adder
3.231
274776LINCOLN ;7U
Adder
3.231
274777LINCOLN ;8U
Adder
3.231
972228AH1-698 GEN2
Adder
1.926
972227AH1-698 GEN1
Adder
1.356
274687WILL CNTY;4U
Adder
14.48
274687WILL CNTY;4U
Adder
14.48
274675JOLIET 29;7U
Adder
15.867
274675JOLIET 29;7U
Adder
15.3
276893AG1-478 C
Solar/Wind Harmer
0.284
274728ELWOOD EC;5P
Adder
8.486
274731ELWOOD EC;2P
Adder
8.486
274733ELWOOD EC;3P
Adder
8.486
274735ELWOOD EC;4P
Adder
8.486
970833AG2-524 GEN
Solar/Wind Harmer
4.485
970833AG2-524 GEN
Solar/Wind Harmer
2.086
274744AC1-111 GEN8
Adder
2.854
274746AC1-111 G10
Adder
2.854
970073AG2-061 GEN
Solar/Wind Harmer
1.177
24729505KEY G4
Adder
3.26
274823ROCKFORD ;21
Adder
9.676
972267AH1-718 GEN
Adder
2.031
241886AC2-103 GEN2
Solar/Wind Helper
7.131
241985AE1-237 GEN
Solar/Wind Helper
0.143
241982AE2-343 S C
Solar/Wind Helper
0.128
203846AF2-130 C
Solar/Wind Helper
0.268
241997AF1-093 GEN
Solar/Wind Helper
0.141
20334926Z1-069 C
Solar/Wind Helper
0.694
23888802TROY G4
50/50
2.617
24190002OREGON_ST1
50/50
2.881
24189802OREGON_CT1
50/50
2.186
241996AE2-282_GEN
Solar/Wind Harmer
2.616
241808AF1-120 C
Solar/Wind Harmer
1.459
944231AF1-091 GEN
Solar/Wind Harmer
14.007
247522W1-056 GEN
Solar/Wind Harmer
1.705
247607V1-011 GEN
Solar/Wind Harmer
2.709
942801AE2-298 GEN
Solar/Wind Harmer
1.034
246937BC-WTG2
Solar/Wind Harmer
2.664
961051AF2-396 GEN
Solar/Wind Harmer
10.366
961051AF2-396 GEN
Solar/Wind Harmer
4.821
270246TR4_N_V150
Solar/Wind Harmer
0.54
270247TR4_N_V136
Solar/Wind Harmer
0.54
247620Y3-023
Adder
0.291
270462AD2-086
Solar/Wind Harmer
4.252
965681AG1-436 GEN
Solar/Wind Harmer
7.185
965791AG1-447 GEN
Solar/Wind Harmer
3.676
970349AG2-230 GEN
Solar/Wind Harmer
8.585
270535AF1-215 GEN1
Solar/Wind Harmer
2.463
270536AF1-215 GEN2
Solar/Wind Harmer
2.463
274805UNIV PK N;1U
Adder
2.657
274808UNIV PK N;4U
Adder
2.64
274888KELLY CRK;1U
Solar/Wind Harmer
3.076
276776AD2-060 GEN
Solar/Wind Harmer
0.218
958011AF2-095 GEN
Solar/Wind Harmer
7.507
970941AG2-585 GEN
Solar/Wind Harmer
2.867
274770LINCOLN ;1U
Adder
3.231
274771LINCOLN ;2U
Adder
3.231
942221AE2-234 GEN
Solar/Wind Harmer
1.82
276897AD1-100 C
Solar/Wind Harmer
23.999
276893AG1-478 C
Solar/Wind Harmer
0.226
274674JOLIET 9 ;6U
Adder
7.948
958481AF2-142 GEN
Solar/Wind Harmer
7.655
945421AF1-207 GEN
Solar/Wind Harmer
7.153
957841AF2-078 GEN
Solar/Wind Harmer
3.079
274696ROCKY RD ;4P
Adder
5.779
274695ROCKY RD ;2P
Adder
5.646
274693ROCKY RD ;1P
Adder
5.591
274697ROCKY RD ;3P
Adder
1.534
274683WAUKEGAN ;8U
Adder
10.68
274683WAUKEGAN ;8U
Adder
9.002
958491AF2-143 GEN
Solar/Wind Harmer
7.59
276901AD2-066 C O1
Solar/Wind Harmer
1.769
962691AG1-118 GEN
Solar/Wind Harmer
15.128
972235AH1-702 GEN1
Adder
1.25
972236AH1-702 GEN2
Adder
1.087
274764LEE CO EC;5U
Adder
4.578
274765LEE CO EC;6U
Adder
4.578
274762LEE CO EC;3U
Adder
4.567
274763LEE CO EC;4U
Adder
4.524
25326509SID D
Adder
0.629
247621Y3-024
Adder
0.114
203835AF1-098 GEN
Solar/Wind Helper
1.435
241801AE1-079 GEN
Solar/Wind Helper
0.144
241967AE2-285_GEN
Solar/Wind Helper
0.368
254304AE2-114 C
Solar/Wind Helper
0.122
254305AE2-115 C
Solar/Wind Helper
0.122
962101AG1-054 GEN
Solar/Wind Helper
0.354
203804AE2-113_GEN
Solar/Wind Helper
0.934
940863AE2-074 GEN
Solar/Wind Helper
0.242
946381AF1-302 GEN
Solar/Wind Helper
0.113
203954AE2-126 C
Solar/Wind Helper
0.235
20398826ARMNA MT
Solar/Wind Helper
0.708
203853AF1-134 C O1
Solar/Wind Helper
0.221
960751AF2-366 GEN
Solar/Wind Harmer
1.047
962781AG1-127 GEN
Solar/Wind Harmer
3.471
990142J1224
External Queue
15.359794616699219
990527J1329
External Queue
2.101203441619873
991182J1586 G
External Queue
28.409210205078125
991177J1571 G
External Queue
18.516592025756836
LAGNLTFEXP_LAGN->PJM
CLTF
5.796
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.926
TVALTFEXP_TVA->PJM
CLTF
2.644
NYPJM->LTFIMP_NY
CLTF
2.146
LGEELTFEXP_LGEE->PJM
CLTF
2.335
WECLTFEXP_WEC->PJM
CLTF
1.893
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
103.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.442
MECLTFEXP_MEC->PJM
CLTF
7.412
SIGELTFEXP_SIGE->PJM
CLTF
0.194
CPLELTFEXP_CPLE->PJM
CLTF
0.547
CBM West 2LTFEXP_CBM-W2->PJM
CBM
45.886

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-004_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.09 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1936.08
MW Contribution:
15.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
2.641
23888602TROY G2
50/50
2.641
23906902RICHG6
50/50
1.041
23906702RICHG4
50/50
1.037
945411AF1-206 GEN
Solar/Wind Harmer
9.928
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270361_3
Solar/Wind Harmer
9.074
270575GUS2 35KV
Solar/Wind Harmer
10.69
270499AE1-146 GEN
Solar/Wind Harmer
2.553
971549AH1-272 GEN
Solar/Wind Harmer
15.242
270404AC1-167 GEN
Solar/Wind Harmer
0.855
270007AE1-245 C
Solar/Wind Harmer
3.819
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
965041AG1-368 GEN
Solar/Wind Harmer
6.613
247521TR3_G114
Solar/Wind Harmer
2.209
270191TR4_S_V150
Solar/Wind Harmer
1.971
965051AG1-369 GEN
Solar/Wind Harmer
3.282
970031AG2-029 GEN
Solar/Wind Harmer
16.152
959331AF2-224 GEN
Solar/Wind Harmer
6.353
971771AH1-392 GEN
Solar/Wind Harmer
5.706
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270526AF1-158 GEN
Solar/Wind Harmer
2.82
971567AH1-282 GEN
Solar/Wind Harmer
3.032
960681AF2-359 GEN
Solar/Wind Harmer
2.255
270223U2-072_GEN1
Solar/Wind Harmer
1.165
270224U2-072_GEN2
Solar/Wind Harmer
1.165
270227U2-072_GEN3
Solar/Wind Harmer
1.165
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.439
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
5.204
270044AE2-322 C
Solar/Wind Harmer
1.037
270588AE1-091_GEN
Solar/Wind Harmer
7.869
958091AF2-103 GEN
Solar/Wind Harmer
0.114
246938BC-WTG3
Solar/Wind Harmer
2.797
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
23888702TROY G3
50/50
2.641
972253AH1-711 GEN
50/50
80.746
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.175
23906802RICHG5
50/50
1.03
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.002
241840AF1-064_GEN
Solar/Wind Harmer
1.696
960841AF2-375 GEN
Solar/Wind Harmer
4.043
270297AD1-101 GEN
Solar/Wind Harmer
1.661
270258AD1-119 GEN
Solar/Wind Harmer
1.539
24441205WTRV SLR C
Solar/Wind Harmer
0.095
246936BC-WTG1
Solar/Wind Harmer
2.75
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.894
270449AD2-020 GEN
Solar/Wind Harmer
1.905
943021AE2-325 GEN
Solar/Wind Harmer
2.476
945111AF1-176 GEN
Solar/Wind Harmer
11.894
957891AF2-083 GEN
Solar/Wind Harmer
9.958
24639705ELKHART HY
Adder
0.1
270216AD2-079_GEN
Solar/Wind Harmer
0.389
965011AG1-365 GEN
Solar/Wind Harmer
6.353
270317AD1-130_GEN
Solar/Wind Harmer
2.028
270485AE1-090_GEN
Solar/Wind Harmer
0.383
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.05
270055AF2-134 C O1
Solar/Wind Harmer
1.709
274751CRETE EC ;1U
Adder
2.726
274754CRETE EC ;4U
Adder
2.726
958381AF2-132 GEN
Solar/Wind Harmer
5.043
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.034
274723RIVER EC ;12
Adder
9.923
274812UNIV PK N;8U
Adder
2.761
274802UNIV PARK;5U
Adder
3.182
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.738
972207SS24-0001
Solar/Wind Harmer
11.971
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.54
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.847
274674JOLIET 9 ;6U
Adder
8.286
274871GR RIDGE ;2U
Solar/Wind Harmer
4.117
274847GR RIDGE ;BU
Solar/Wind Harmer
2.707
270024AE2-089 GEN
Solar/Wind Harmer
2.502
274745AC1-111 GEN9
Adder
2.977
276694AA1-018 GEN2
Solar/Wind Harmer
3.359
276691AA1-018 GEN1
Solar/Wind Harmer
0.401
274861TOP CROP ;1U
Solar/Wind Harmer
3.224
274682WAUKEGAN ;7U
Adder
9.511
274828WAUKEGAN ;BP
Adder
5.84
276805AD2-038 GEN
Solar/Wind Harmer
2.707
939401AE1-172 GEN
Solar/Wind Harmer
7.335
276882AE2-255 GEN
Solar/Wind Harmer
1.772
274822ROCKFORD ;11
Adder
10.177
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.715
24728605AND G2
Adder
1.714
241885AC2-103 GEN1
Solar/Wind Helper
7.081
241807AE2-176_GEN
Solar/Wind Helper
1.707
203947AF1-006 C
Solar/Wind Helper
0.403
961971AG1-040 GEN
Solar/Wind Helper
0.352
203830AF1-094 GEN
Solar/Wind Helper
0.341
203979AG1-198 GEN
Solar/Wind Helper
0.205
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
962781AG1-127 GEN
Solar/Wind Harmer
3.622
23888802TROY G4
50/50
2.641
24190002OREGON_ST1
50/50
2.927
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.651
241808AF1-120 C
Solar/Wind Harmer
1.478
944231AF1-091 GEN
Solar/Wind Harmer
14.402
247522W1-056 GEN
Solar/Wind Harmer
1.754
247607V1-011 GEN
Solar/Wind Harmer
2.795
942801AE2-298 GEN
Solar/Wind Harmer
1.067
246937BC-WTG2
Solar/Wind Harmer
2.75
961051AF2-396 GEN
Solar/Wind Harmer
10.714
961051AF2-396 GEN
Solar/Wind Harmer
4.983
270246TR4_N_V150
Solar/Wind Harmer
0.559
270247TR4_N_V136
Solar/Wind Harmer
0.559
247620Y3-023
Adder
0.301
270462AD2-086
Solar/Wind Harmer
4.405
965681AG1-436 GEN
Solar/Wind Harmer
7.459
965791AG1-447 GEN
Solar/Wind Harmer
3.816
970349AG2-230 GEN
Solar/Wind Harmer
8.915
270535AF1-215 GEN1
Solar/Wind Harmer
2.563
270536AF1-215 GEN2
Solar/Wind Harmer
2.563
274805UNIV PK N;1U
Adder
2.767
274808UNIV PK N;4U
Adder
2.749
274888KELLY CRK;1U
Solar/Wind Harmer
3.206
276776AD2-060 GEN
Solar/Wind Harmer
0.227
958011AF2-095 GEN
Solar/Wind Harmer
7.823
970941AG2-585 GEN
Solar/Wind Harmer
2.988
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
942221AE2-234 GEN
Solar/Wind Harmer
1.897
24695305TIMB G C
Solar/Wind Harmer
2.27
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270505AE1-170 C O1
Solar/Wind Harmer
9.987
270063AE2-323 C
Solar/Wind Harmer
1.426
247643Z2-116 C
Solar/Wind Harmer
0.045
965021AG1-366 GEN
Solar/Wind Harmer
1.477
24441505OLIV SLR
Solar/Wind Harmer
0.083
270043AE2-236 GEN
Solar/Wind Harmer
3.306
971347AH1-153 GEN
Solar/Wind Harmer
2.972
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
972231SS25-0005
Solar/Wind Harmer
5.293
972181SS23-001
Solar/Wind Harmer
3.308
274752CRETE EC ;2U
Adder
2.726
274753CRETE EC ;3U
Adder
2.726
964401AG1-302 GEN
Solar/Wind Harmer
5.043
274724RIVER EC ;11
Adder
9.804
274814UNIV PK N;0U
Adder
2.785
274807UNIV PK N;3U
Adder
2.779
276897AD1-100 C
Solar/Wind Harmer
25.018
276893AG1-478 C
Solar/Wind Harmer
0.236
274674JOLIET 9 ;6U
Adder
8.286
958481AF2-142 GEN
Solar/Wind Harmer
7.985
945421AF1-207 GEN
Solar/Wind Harmer
7.461
957841AF2-078 GEN
Solar/Wind Harmer
3.212
274695ROCKY RD ;2P
Adder
5.89
274693ROCKY RD ;1P
Adder
5.832
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.029
274683WAUKEGAN ;8U
Adder
11.142
274683WAUKEGAN ;8U
Adder
9.392
958491AF2-143 GEN
Solar/Wind Harmer
7.919
276901AD2-066 C O1
Solar/Wind Harmer
1.846
962691AG1-118 GEN
Solar/Wind Harmer
15.786
972235AH1-702 GEN1
Adder
1.305
972236AH1-702 GEN2
Adder
1.135
274764LEE CO EC;5U
Adder
4.783
274765LEE CO EC;6U
Adder
4.783
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
25326509SID D
Adder
0.657
247621Y3-024
Adder
0.119
203835AF1-098 GEN
Solar/Wind Helper
1.39
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
254304AE2-114 C
Solar/Wind Helper
0.117
254305AE2-115 C
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.34
203804AE2-113_GEN
Solar/Wind Helper
0.892
940863AE2-074 GEN
Solar/Wind Helper
0.231
946381AF1-302 GEN
Solar/Wind Helper
0.108
203954AE2-126 C
Solar/Wind Helper
0.224
960751AF2-366 GEN
Solar/Wind Harmer
1.093
274811UNIV PK N;7U
Adder
2.761
276164X3-005 C
Solar/Wind Harmer
0.386
274803UNIV PARK;6U
Adder
3.182
274826FISK ;BP
Adder
5.965
972038AH1-567 GEN2
Adder
0.199
274887GEN-1.85
Solar/Wind Harmer
2.895
276772AC2-154 GEN
Solar/Wind Harmer
1.516
276843GEN-1.7
Solar/Wind Harmer
0.311
276806AD2-047 C O1
Solar/Wind Harmer
5.812
274772LINCOLN ;3U
Adder
3.367
972259AH1-714 GEN
Adder
10.293
274676JOLIET 29;8U
Adder
15.949
939351AE1-166 GEN
Solar/Wind Harmer
3.194
274729ELWOOD EC;1P
Adder
8.847
274730ELWOOD EC;6P
Adder
8.847
274734ELWOOD EC;8P
Adder
8.847
274736ELWOOD EC;9P
Adder
8.847
970707AG2-453 GEN
Solar/Wind Harmer
15.068
943121AE2-341 GEN
Solar/Wind Harmer
7.986
943591AF1-030 GEN
Solar/Wind Harmer
5.324
274862TOP CROP ;2U
Solar/Wind Harmer
2.692
944531AF1-118 GEN
Solar/Wind Harmer
18.528
274682WAUKEGAN ;7U
Adder
9.511
276868AE1-113 GEN
Solar/Wind Harmer
5.316
274879MINONK ;1U
Solar/Wind Harmer
3.544
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
4.715
24728705AND G3
Adder
3.585
24728505AND G1
Adder
1.714
962511AG1-100 GEN
Solar/Wind Helper
0.36
270228U2-072_GEN4
Solar/Wind Harmer
1.165
270231U2-072_GEN5
Solar/Wind Harmer
1.165
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
963791AG1-232 GEN
Solar/Wind Harmer
7.96
270071AF1-092 GEN
Solar/Wind Harmer
8.415
958391AF2-133 GEN
Solar/Wind Harmer
5
959141AF2-205 GEN
Solar/Wind Harmer
3.312
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.227
274800UNIV PARK;3U
Adder
3.172
274801UNIV PARK;4U
Adder
3.172
960591AF2-350 GEN
Solar/Wind Harmer
5.433
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.093
274687WILL CNTY;4U
Adder
15.093
274675JOLIET 29;7U
Adder
16.54
274675JOLIET 29;7U
Adder
15.949
276893AG1-478 C
Solar/Wind Harmer
0.296
274728ELWOOD EC;5P
Adder
8.847
274731ELWOOD EC;2P
Adder
8.847
274733ELWOOD EC;3P
Adder
8.847
274735ELWOOD EC;4P
Adder
8.847
970833AG2-524 GEN
Solar/Wind Harmer
4.677
970833AG2-524 GEN
Solar/Wind Harmer
2.175
274744AC1-111 GEN8
Adder
2.977
274746AC1-111 G10
Adder
2.977
970073AG2-061 GEN
Solar/Wind Harmer
1.228
24729505KEY G4
Adder
3.403
274823ROCKFORD ;21
Adder
10.103
972267AH1-718 GEN
Adder
2.122
241886AC2-103 GEN2
Solar/Wind Helper
7.081
241985AE1-237 GEN
Solar/Wind Helper
0.138
241982AE2-343 S C
Solar/Wind Helper
0.124
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
20334926Z1-069 C
Solar/Wind Helper
0.662
990142J1224
External Queue
15.359953880310059
990527J1329
External Queue
2.1012251377105713
991182J1586 G
External Queue
28.409770965576172
991177J1571 G
External Queue
18.516189575195312
LAGNLTFEXP_LAGN->PJM
CLTF
6.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.592
TVALTFEXP_TVA->PJM
CLTF
2.868
NYPJM->LTFIMP_NY
CLTF
2.005
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.188
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.279
MECLTFEXP_MEC->PJM
CLTF
7.782
SIGELTFEXP_SIGE->PJM
CLTF
0.206
CPLELTFEXP_CPLE->PJM
CLTF
0.788
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.851

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-005_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-005_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.09 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1936.02
MW Contribution:
15.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
2.641
972253AH1-711 GEN
50/50
80.747
23920202STRYCT
50/50
2.391
24189902OREGON_CT2
50/50
2.175
23906802RICHG5
50/50
1.03
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.002
241840AF1-064_GEN
Solar/Wind Harmer
1.696
960841AF2-375 GEN
Solar/Wind Harmer
4.043
270297AD1-101 GEN
Solar/Wind Harmer
1.661
270258AD1-119 GEN
Solar/Wind Harmer
1.539
24441205WTRV SLR C
Solar/Wind Harmer
0.095
23888802TROY G4
50/50
2.641
24190002OREGON_ST1
50/50
2.926
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.651
241808AF1-120 C
Solar/Wind Harmer
1.478
944231AF1-091 GEN
Solar/Wind Harmer
14.402
247522W1-056 GEN
Solar/Wind Harmer
1.754
247607V1-011 GEN
Solar/Wind Harmer
2.795
942801AE2-298 GEN
Solar/Wind Harmer
1.067
246937BC-WTG2
Solar/Wind Harmer
2.749
961051AF2-396 GEN
Solar/Wind Harmer
10.714
961051AF2-396 GEN
Solar/Wind Harmer
4.983
270246TR4_N_V150
Solar/Wind Harmer
0.559
270247TR4_N_V136
Solar/Wind Harmer
0.559
247620Y3-023
Adder
0.301
270462AD2-086
Solar/Wind Harmer
4.405
965681AG1-436 GEN
Solar/Wind Harmer
7.459
965791AG1-447 GEN
Solar/Wind Harmer
3.816
970349AG2-230 GEN
Solar/Wind Harmer
8.914
270535AF1-215 GEN1
Solar/Wind Harmer
2.563
270536AF1-215 GEN2
Solar/Wind Harmer
2.563
274805UNIV PK N;1U
Adder
2.767
274808UNIV PK N;4U
Adder
2.749
274888KELLY CRK;1U
Solar/Wind Harmer
3.206
276776AD2-060 GEN
Solar/Wind Harmer
0.227
958011AF2-095 GEN
Solar/Wind Harmer
7.823
970941AG2-585 GEN
Solar/Wind Harmer
2.988
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
942221AE2-234 GEN
Solar/Wind Harmer
1.897
276897AD1-100 C
Solar/Wind Harmer
25.018
276893AG1-478 C
Solar/Wind Harmer
0.236
274674JOLIET 9 ;6U
Adder
8.286
958481AF2-142 GEN
Solar/Wind Harmer
7.984
945421AF1-207 GEN
Solar/Wind Harmer
7.461
957841AF2-078 GEN
Solar/Wind Harmer
3.212
274696ROCKY RD ;4P
Adder
6.029
274695ROCKY RD ;2P
Adder
5.89
274693ROCKY RD ;1P
Adder
5.832
274697ROCKY RD ;3P
Adder
1.6
274683WAUKEGAN ;8U
Adder
11.142
274683WAUKEGAN ;8U
Adder
9.392
958491AF2-143 GEN
Solar/Wind Harmer
7.919
276901AD2-066 C O1
Solar/Wind Harmer
1.846
962691AG1-118 GEN
Solar/Wind Harmer
15.786
972235AH1-702 GEN1
Adder
1.305
972236AH1-702 GEN2
Adder
1.135
274764LEE CO EC;5U
Adder
4.783
274765LEE CO EC;6U
Adder
4.783
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
25326509SID D
Adder
0.657
247621Y3-024
Adder
0.119
203835AF1-098 GEN
Solar/Wind Helper
1.39
241801AE1-079 GEN
Solar/Wind Helper
0.138
241967AE2-285_GEN
Solar/Wind Helper
0.354
254304AE2-114 C
Solar/Wind Helper
0.117
254305AE2-115 C
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.34
203804AE2-113_GEN
Solar/Wind Helper
0.892
940863AE2-074 GEN
Solar/Wind Helper
0.231
946381AF1-302 GEN
Solar/Wind Helper
0.108
203954AE2-126 C
Solar/Wind Helper
0.224
960751AF2-366 GEN
Solar/Wind Harmer
1.093
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.439
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.96
270541AE2-072 C
Solar/Wind Harmer
5.205
270044AE2-322 C
Solar/Wind Harmer
1.037
270588AE1-091_GEN
Solar/Wind Harmer
7.869
958091AF2-103 GEN
Solar/Wind Harmer
0.114
246938BC-WTG3
Solar/Wind Harmer
2.797
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
24695305TIMB G C
Solar/Wind Harmer
2.27
945111AF1-176 GEN
Solar/Wind Harmer
3.769
270505AE1-170 C O1
Solar/Wind Harmer
9.987
270063AE2-323 C
Solar/Wind Harmer
1.426
247643Z2-116 C
Solar/Wind Harmer
0.045
965021AG1-366 GEN
Solar/Wind Harmer
1.477
24441505OLIV SLR
Solar/Wind Harmer
0.083
270043AE2-236 GEN
Solar/Wind Harmer
3.306
971347AH1-153 GEN
Solar/Wind Harmer
2.971
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
972231SS25-0005
Solar/Wind Harmer
5.293
972181SS23-001
Solar/Wind Harmer
3.308
274752CRETE EC ;2U
Adder
2.726
274753CRETE EC ;3U
Adder
2.726
964401AG1-302 GEN
Solar/Wind Harmer
5.043
274724RIVER EC ;11
Adder
9.804
274814UNIV PK N;0U
Adder
2.785
274807UNIV PK N;3U
Adder
2.779
274811UNIV PK N;7U
Adder
2.761
276164X3-005 C
Solar/Wind Harmer
0.386
274803UNIV PARK;6U
Adder
3.182
274826FISK ;BP
Adder
5.965
972038AH1-567 GEN2
Adder
0.199
274887GEN-1.85
Solar/Wind Harmer
2.894
276772AC2-154 GEN
Solar/Wind Harmer
1.516
276843GEN-1.7
Solar/Wind Harmer
0.311
276806AD2-047 C O1
Solar/Wind Harmer
5.812
274772LINCOLN ;3U
Adder
3.367
972259AH1-714 GEN
Adder
10.292
274676JOLIET 29;8U
Adder
15.949
939351AE1-166 GEN
Solar/Wind Harmer
3.194
274729ELWOOD EC;1P
Adder
8.847
274730ELWOOD EC;6P
Adder
8.847
274734ELWOOD EC;8P
Adder
8.847
274736ELWOOD EC;9P
Adder
8.847
970707AG2-453 GEN
Solar/Wind Harmer
15.068
943121AE2-341 GEN
Solar/Wind Harmer
7.986
943591AF1-030 GEN
Solar/Wind Harmer
5.324
274862TOP CROP ;2U
Solar/Wind Harmer
2.692
944531AF1-118 GEN
Solar/Wind Harmer
18.528
274682WAUKEGAN ;7U
Adder
9.51
276868AE1-113 GEN
Solar/Wind Harmer
5.316
274879MINONK ;1U
Solar/Wind Harmer
3.544
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
4.715
24728705AND G3
Adder
3.585
24728505AND G1
Adder
1.714
962511AG1-100 GEN
Solar/Wind Helper
0.36
23888502TROY G1
50/50
2.641
23888602TROY G2
50/50
2.641
23906902RICHG6
50/50
1.041
23906702RICHG4
50/50
1.037
945411AF1-206 GEN
Solar/Wind Harmer
9.928
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270361_3
Solar/Wind Harmer
9.074
270575GUS2 35KV
Solar/Wind Harmer
10.69
270499AE1-146 GEN
Solar/Wind Harmer
2.553
971549AH1-272 GEN
Solar/Wind Harmer
15.242
270404AC1-167 GEN
Solar/Wind Harmer
0.855
270007AE1-245 C
Solar/Wind Harmer
3.819
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
965041AG1-368 GEN
Solar/Wind Harmer
6.613
247521TR3_G114
Solar/Wind Harmer
2.209
270191TR4_S_V150
Solar/Wind Harmer
1.971
965051AG1-369 GEN
Solar/Wind Harmer
3.282
970031AG2-029 GEN
Solar/Wind Harmer
16.152
959331AF2-224 GEN
Solar/Wind Harmer
6.353
971771AH1-392 GEN
Solar/Wind Harmer
5.706
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270526AF1-158 GEN
Solar/Wind Harmer
2.82
971567AH1-282 GEN
Solar/Wind Harmer
3.032
960681AF2-359 GEN
Solar/Wind Harmer
2.255
270223U2-072_GEN1
Solar/Wind Harmer
1.165
270224U2-072_GEN2
Solar/Wind Harmer
1.165
270227U2-072_GEN3
Solar/Wind Harmer
1.165
270228U2-072_GEN4
Solar/Wind Harmer
1.165
270231U2-072_GEN5
Solar/Wind Harmer
1.165
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
963791AG1-232 GEN
Solar/Wind Harmer
7.959
270071AF1-092 GEN
Solar/Wind Harmer
8.415
958391AF2-133 GEN
Solar/Wind Harmer
5
959141AF2-205 GEN
Solar/Wind Harmer
3.312
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.227
274800UNIV PARK;3U
Adder
3.172
274801UNIV PARK;4U
Adder
3.172
960591AF2-350 GEN
Solar/Wind Harmer
5.433
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.092
274687WILL CNTY;4U
Adder
15.092
274675JOLIET 29;7U
Adder
16.54
274675JOLIET 29;7U
Adder
15.949
276893AG1-478 C
Solar/Wind Harmer
0.296
274728ELWOOD EC;5P
Adder
8.847
274731ELWOOD EC;2P
Adder
8.847
274733ELWOOD EC;3P
Adder
8.847
274735ELWOOD EC;4P
Adder
8.847
970833AG2-524 GEN
Solar/Wind Harmer
4.677
970833AG2-524 GEN
Solar/Wind Harmer
2.175
274744AC1-111 GEN8
Adder
2.977
274746AC1-111 G10
Adder
2.977
970073AG2-061 GEN
Solar/Wind Harmer
1.228
24729505KEY G4
Adder
3.403
274823ROCKFORD ;21
Adder
10.103
972267AH1-718 GEN
Adder
2.122
241886AC2-103 GEN2
Solar/Wind Helper
7.081
241985AE1-237 GEN
Solar/Wind Helper
0.138
241982AE2-343 S C
Solar/Wind Helper
0.124
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
20334926Z1-069 C
Solar/Wind Helper
0.662
246936BC-WTG1
Solar/Wind Harmer
2.749
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.893
270449AD2-020 GEN
Solar/Wind Harmer
1.905
943021AE2-325 GEN
Solar/Wind Harmer
2.476
945111AF1-176 GEN
Solar/Wind Harmer
11.894
957891AF2-083 GEN
Solar/Wind Harmer
9.958
24639705ELKHART HY
Adder
0.1
270216AD2-079_GEN
Solar/Wind Harmer
0.389
965011AG1-365 GEN
Solar/Wind Harmer
6.353
270317AD1-130_GEN
Solar/Wind Harmer
2.028
270485AE1-090_GEN
Solar/Wind Harmer
0.383
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.05
270055AF2-134 C O1
Solar/Wind Harmer
1.709
274751CRETE EC ;1U
Adder
2.726
274754CRETE EC ;4U
Adder
2.726
958381AF2-132 GEN
Solar/Wind Harmer
5.043
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.034
274723RIVER EC ;12
Adder
9.922
274812UNIV PK N;8U
Adder
2.761
274802UNIV PARK;5U
Adder
3.182
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.738
972207SS24-0001
Solar/Wind Harmer
11.97
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.54
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.847
274674JOLIET 9 ;6U
Adder
8.286
274871GR RIDGE ;2U
Solar/Wind Harmer
4.117
274847GR RIDGE ;BU
Solar/Wind Harmer
2.707
270024AE2-089 GEN
Solar/Wind Harmer
2.502
274745AC1-111 GEN9
Adder
2.977
276694AA1-018 GEN2
Solar/Wind Harmer
3.359
276691AA1-018 GEN1
Solar/Wind Harmer
0.401
274861TOP CROP ;1U
Solar/Wind Harmer
3.224
274682WAUKEGAN ;7U
Adder
9.51
274828WAUKEGAN ;BP
Adder
5.84
276805AD2-038 GEN
Solar/Wind Harmer
2.707
939401AE1-172 GEN
Solar/Wind Harmer
7.335
276882AE2-255 GEN
Solar/Wind Harmer
1.772
274822ROCKFORD ;11
Adder
10.177
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.715
24728605AND G2
Adder
1.714
241885AC2-103 GEN1
Solar/Wind Helper
7.081
241807AE2-176_GEN
Solar/Wind Helper
1.707
203947AF1-006 C
Solar/Wind Helper
0.403
961971AG1-040 GEN
Solar/Wind Helper
0.352
203830AF1-094 GEN
Solar/Wind Helper
0.341
203979AG1-198 GEN
Solar/Wind Helper
0.205
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
962781AG1-127 GEN
Solar/Wind Harmer
3.622
990142J1224
External Queue
15.359794616699219
990527J1329
External Queue
2.101203441619873
991182J1586 G
External Queue
28.409210205078125
991177J1571 G
External Queue
18.516592025756836
LAGNLTFEXP_LAGN->PJM
CLTF
6.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.592
TVALTFEXP_TVA->PJM
CLTF
2.868
NYPJM->LTFIMP_NY
CLTF
2.005
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.185
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.279
MECLTFEXP_MEC->PJM
CLTF
7.782
SIGELTFEXP_SIGE->PJM
CLTF
0.206
CPLELTFEXP_CPLE->PJM
CLTF
0.788
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.85

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-006_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.09 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1936.02
MW Contribution:
15.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
2.641
23888602TROY G2
50/50
2.641
23906902RICHG6
50/50
1.041
23906702RICHG4
50/50
1.037
945411AF1-206 GEN
Solar/Wind Harmer
9.928
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270361_3
Solar/Wind Harmer
9.074
270575GUS2 35KV
Solar/Wind Harmer
10.69
270499AE1-146 GEN
Solar/Wind Harmer
2.553
971549AH1-272 GEN
Solar/Wind Harmer
15.242
270404AC1-167 GEN
Solar/Wind Harmer
0.855
270007AE1-245 C
Solar/Wind Harmer
3.819
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
965041AG1-368 GEN
Solar/Wind Harmer
6.613
247521TR3_G114
Solar/Wind Harmer
2.209
270191TR4_S_V150
Solar/Wind Harmer
1.971
965051AG1-369 GEN
Solar/Wind Harmer
3.282
970031AG2-029 GEN
Solar/Wind Harmer
16.152
959331AF2-224 GEN
Solar/Wind Harmer
6.353
971771AH1-392 GEN
Solar/Wind Harmer
5.706
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270526AF1-158 GEN
Solar/Wind Harmer
2.82
971567AH1-282 GEN
Solar/Wind Harmer
3.032
960681AF2-359 GEN
Solar/Wind Harmer
2.255
270223U2-072_GEN1
Solar/Wind Harmer
1.165
270224U2-072_GEN2
Solar/Wind Harmer
1.165
270227U2-072_GEN3
Solar/Wind Harmer
1.165
270228U2-072_GEN4
Solar/Wind Harmer
1.165
270231U2-072_GEN5
Solar/Wind Harmer
1.165
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.439
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.96
270541AE2-072 C
Solar/Wind Harmer
5.205
270044AE2-322 C
Solar/Wind Harmer
1.037
270588AE1-091_GEN
Solar/Wind Harmer
7.869
958091AF2-103 GEN
Solar/Wind Harmer
0.114
246938BC-WTG3
Solar/Wind Harmer
2.797
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
24695305TIMB G C
Solar/Wind Harmer
2.27
945111AF1-176 GEN
Solar/Wind Harmer
3.769
270505AE1-170 C O1
Solar/Wind Harmer
9.987
270063AE2-323 C
Solar/Wind Harmer
1.426
247643Z2-116 C
Solar/Wind Harmer
0.045
965021AG1-366 GEN
Solar/Wind Harmer
1.477
24441505OLIV SLR
Solar/Wind Harmer
0.083
270043AE2-236 GEN
Solar/Wind Harmer
3.306
971347AH1-153 GEN
Solar/Wind Harmer
2.971
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
972231SS25-0005
Solar/Wind Harmer
5.293
972181SS23-001
Solar/Wind Harmer
3.308
274752CRETE EC ;2U
Adder
2.726
274753CRETE EC ;3U
Adder
2.726
964401AG1-302 GEN
Solar/Wind Harmer
5.043
274724RIVER EC ;11
Adder
9.804
274814UNIV PK N;0U
Adder
2.785
274807UNIV PK N;3U
Adder
2.779
274811UNIV PK N;7U
Adder
2.761
276164X3-005 C
Solar/Wind Harmer
0.386
274803UNIV PARK;6U
Adder
3.182
274826FISK ;BP
Adder
5.965
972038AH1-567 GEN2
Adder
0.199
274887GEN-1.85
Solar/Wind Harmer
2.894
276772AC2-154 GEN
Solar/Wind Harmer
1.516
276843GEN-1.7
Solar/Wind Harmer
0.311
276806AD2-047 C O1
Solar/Wind Harmer
5.812
274772LINCOLN ;3U
Adder
3.367
972259AH1-714 GEN
Adder
10.292
274676JOLIET 29;8U
Adder
15.949
939351AE1-166 GEN
Solar/Wind Harmer
3.194
963791AG1-232 GEN
Solar/Wind Harmer
7.959
270071AF1-092 GEN
Solar/Wind Harmer
8.415
958391AF2-133 GEN
Solar/Wind Harmer
5
959141AF2-205 GEN
Solar/Wind Harmer
3.312
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.227
274800UNIV PARK;3U
Adder
3.172
274801UNIV PARK;4U
Adder
3.172
960591AF2-350 GEN
Solar/Wind Harmer
5.433
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.092
274687WILL CNTY;4U
Adder
15.092
274675JOLIET 29;7U
Adder
16.54
274675JOLIET 29;7U
Adder
15.949
23888702TROY G3
50/50
2.641
972253AH1-711 GEN
50/50
80.747
23920202STRYCT
50/50
2.391
24189902OREGON_CT2
50/50
2.175
23906802RICHG5
50/50
1.03
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.002
241840AF1-064_GEN
Solar/Wind Harmer
1.696
960841AF2-375 GEN
Solar/Wind Harmer
4.043
270297AD1-101 GEN
Solar/Wind Harmer
1.661
270258AD1-119 GEN
Solar/Wind Harmer
1.539
24441205WTRV SLR C
Solar/Wind Harmer
0.095
246936BC-WTG1
Solar/Wind Harmer
2.749
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.893
270449AD2-020 GEN
Solar/Wind Harmer
1.905
943021AE2-325 GEN
Solar/Wind Harmer
2.476
945111AF1-176 GEN
Solar/Wind Harmer
11.894
957891AF2-083 GEN
Solar/Wind Harmer
9.958
24639705ELKHART HY
Adder
0.1
270216AD2-079_GEN
Solar/Wind Harmer
0.389
965011AG1-365 GEN
Solar/Wind Harmer
6.353
270317AD1-130_GEN
Solar/Wind Harmer
2.028
270485AE1-090_GEN
Solar/Wind Harmer
0.383
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.05
270055AF2-134 C O1
Solar/Wind Harmer
1.709
274751CRETE EC ;1U
Adder
2.726
274754CRETE EC ;4U
Adder
2.726
958381AF2-132 GEN
Solar/Wind Harmer
5.043
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.034
274723RIVER EC ;12
Adder
9.922
274812UNIV PK N;8U
Adder
2.761
274802UNIV PARK;5U
Adder
3.182
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.738
972207SS24-0001
Solar/Wind Harmer
11.97
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.54
941551AE2-152 GEN
Solar/Wind Harmer
2.443
23888802TROY G4
50/50
2.641
24190002OREGON_ST1
50/50
2.926
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.651
241808AF1-120 C
Solar/Wind Harmer
1.478
944231AF1-091 GEN
Solar/Wind Harmer
14.402
247522W1-056 GEN
Solar/Wind Harmer
1.754
247607V1-011 GEN
Solar/Wind Harmer
2.795
942801AE2-298 GEN
Solar/Wind Harmer
1.067
246937BC-WTG2
Solar/Wind Harmer
2.749
961051AF2-396 GEN
Solar/Wind Harmer
10.714
961051AF2-396 GEN
Solar/Wind Harmer
4.983
270246TR4_N_V150
Solar/Wind Harmer
0.559
270247TR4_N_V136
Solar/Wind Harmer
0.559
247620Y3-023
Adder
0.301
270462AD2-086
Solar/Wind Harmer
4.405
965681AG1-436 GEN
Solar/Wind Harmer
7.459
965791AG1-447 GEN
Solar/Wind Harmer
3.816
970349AG2-230 GEN
Solar/Wind Harmer
8.914
270535AF1-215 GEN1
Solar/Wind Harmer
2.563
270536AF1-215 GEN2
Solar/Wind Harmer
2.563
274805UNIV PK N;1U
Adder
2.767
274808UNIV PK N;4U
Adder
2.749
274888KELLY CRK;1U
Solar/Wind Harmer
3.206
276776AD2-060 GEN
Solar/Wind Harmer
0.227
958011AF2-095 GEN
Solar/Wind Harmer
7.823
970941AG2-585 GEN
Solar/Wind Harmer
2.988
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
942221AE2-234 GEN
Solar/Wind Harmer
1.897
276897AD1-100 C
Solar/Wind Harmer
25.018
276893AG1-478 C
Solar/Wind Harmer
0.236
274674JOLIET 9 ;6U
Adder
8.286
958481AF2-142 GEN
Solar/Wind Harmer
7.984
945421AF1-207 GEN
Solar/Wind Harmer
7.461
957841AF2-078 GEN
Solar/Wind Harmer
3.212
274696ROCKY RD ;4P
Adder
6.029
274695ROCKY RD ;2P
Adder
5.89
274693ROCKY RD ;1P
Adder
5.832
274697ROCKY RD ;3P
Adder
1.6
274683WAUKEGAN ;8U
Adder
11.142
274683WAUKEGAN ;8U
Adder
9.392
958491AF2-143 GEN
Solar/Wind Harmer
7.919
276901AD2-066 C O1
Solar/Wind Harmer
1.846
962691AG1-118 GEN
Solar/Wind Harmer
15.786
972235AH1-702 GEN1
Adder
1.305
972236AH1-702 GEN2
Adder
1.135
274764LEE CO EC;5U
Adder
4.783
274765LEE CO EC;6U
Adder
4.783
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
25326509SID D
Adder
0.657
247621Y3-024
Adder
0.119
203835AF1-098 GEN
Solar/Wind Helper
1.39
241801AE1-079 GEN
Solar/Wind Helper
0.138
241967AE2-285_GEN
Solar/Wind Helper
0.354
254304AE2-114 C
Solar/Wind Helper
0.117
254305AE2-115 C
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.34
203804AE2-113_GEN
Solar/Wind Helper
0.892
940863AE2-074 GEN
Solar/Wind Helper
0.231
946381AF1-302 GEN
Solar/Wind Helper
0.108
203954AE2-126 C
Solar/Wind Helper
0.224
960751AF2-366 GEN
Solar/Wind Harmer
1.093
276893AG1-478 C
Solar/Wind Harmer
0.296
274728ELWOOD EC;5P
Adder
8.847
274731ELWOOD EC;2P
Adder
8.847
274733ELWOOD EC;3P
Adder
8.847
274735ELWOOD EC;4P
Adder
8.847
970833AG2-524 GEN
Solar/Wind Harmer
4.677
970833AG2-524 GEN
Solar/Wind Harmer
2.175
274744AC1-111 GEN8
Adder
2.977
274746AC1-111 G10
Adder
2.977
970073AG2-061 GEN
Solar/Wind Harmer
1.228
24729505KEY G4
Adder
3.403
274823ROCKFORD ;21
Adder
10.103
972267AH1-718 GEN
Adder
2.122
274729ELWOOD EC;1P
Adder
8.847
274730ELWOOD EC;6P
Adder
8.847
274734ELWOOD EC;8P
Adder
8.847
274736ELWOOD EC;9P
Adder
8.847
970707AG2-453 GEN
Solar/Wind Harmer
15.068
943121AE2-341 GEN
Solar/Wind Harmer
7.986
943591AF1-030 GEN
Solar/Wind Harmer
5.324
274862TOP CROP ;2U
Solar/Wind Harmer
2.692
944531AF1-118 GEN
Solar/Wind Harmer
18.528
274682WAUKEGAN ;7U
Adder
9.51
276868AE1-113 GEN
Solar/Wind Harmer
5.316
274879MINONK ;1U
Solar/Wind Harmer
3.544
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
4.715
24728705AND G3
Adder
3.585
24728505AND G1
Adder
1.714
962511AG1-100 GEN
Solar/Wind Helper
0.36
274732ELWOOD EC;7P
Adder
8.847
274674JOLIET 9 ;6U
Adder
8.286
274871GR RIDGE ;2U
Solar/Wind Harmer
4.117
274847GR RIDGE ;BU
Solar/Wind Harmer
2.707
270024AE2-089 GEN
Solar/Wind Harmer
2.502
274745AC1-111 GEN9
Adder
2.977
276694AA1-018 GEN2
Solar/Wind Harmer
3.359
276691AA1-018 GEN1
Solar/Wind Harmer
0.401
274861TOP CROP ;1U
Solar/Wind Harmer
3.224
274682WAUKEGAN ;7U
Adder
9.51
274828WAUKEGAN ;BP
Adder
5.84
276805AD2-038 GEN
Solar/Wind Harmer
2.707
939401AE1-172 GEN
Solar/Wind Harmer
7.335
276882AE2-255 GEN
Solar/Wind Harmer
1.772
274822ROCKFORD ;11
Adder
10.177
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.715
24728605AND G2
Adder
1.714
241885AC2-103 GEN1
Solar/Wind Helper
7.081
241807AE2-176_GEN
Solar/Wind Helper
1.707
203947AF1-006 C
Solar/Wind Helper
0.403
961971AG1-040 GEN
Solar/Wind Helper
0.352
203830AF1-094 GEN
Solar/Wind Helper
0.341
203979AG1-198 GEN
Solar/Wind Helper
0.205
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
962781AG1-127 GEN
Solar/Wind Harmer
3.622
241886AC2-103 GEN2
Solar/Wind Helper
7.081
241985AE1-237 GEN
Solar/Wind Helper
0.138
241982AE2-343 S C
Solar/Wind Helper
0.124
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
20334926Z1-069 C
Solar/Wind Helper
0.662
990142J1224
External Queue
15.359794616699219
990527J1329
External Queue
2.101203441619873
991182J1586 G
External Queue
28.409210205078125
991177J1571 G
External Queue
18.516592025756836
LAGNLTFEXP_LAGN->PJM
CLTF
6.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.592
TVALTFEXP_TVA->PJM
CLTF
2.868
NYPJM->LTFIMP_NY
CLTF
2.005
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.185
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.279
MECLTFEXP_MEC->PJM
CLTF
7.782
SIGELTFEXP_SIGE->PJM
CLTF
0.206
CPLELTFEXP_CPLE->PJM
CLTF
0.788
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.85

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.65 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:1922.03
MW Contribution:
10.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
2.865
270142AC1-141 CT1_
50/50
2.081
24642205MAYFLWER
50/50
0.032
944961AF1-161 GEN
50/50
2.458
962601AG1-109 GEN
50/50
2.458
965021AG1-366 GEN
Solar/Wind Harmer
4.658
270043AE2-236 GEN
Solar/Wind Harmer
5.337
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
32.656
24695305TIMB G C
Solar/Wind Harmer
0.545
945111AF1-176 GEN
Solar/Wind Harmer
4.975
971347AH1-153 GEN
Solar/Wind Harmer
3.002
270505AE1-170 C O1
Solar/Wind Harmer
6.29
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.571
274752CRETE EC ;2U
Adder
6.49
274753CRETE EC ;3U
Adder
6.49
274724RIVER EC ;11
Adder
13.897
274814UNIV PK N;0U
Adder
3.935
274807UNIV PK N;3U
Adder
3.926
274811UNIV PK N;7U
Adder
3.9
274772LINCOLN ;3U
Adder
6.547
274803UNIV PARK;6U
Adder
4.495
274826FISK ;BP
Adder
8.431
972038AH1-567 GEN2
Adder
0.281
274887GEN-1.85
Solar/Wind Harmer
0.139
276843GEN-1.7
Solar/Wind Harmer
0.173
276806AD2-047 C O1
Solar/Wind Harmer
3.036
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.564
970707AG2-453 GEN
Solar/Wind Harmer
17.395
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.491
274729ELWOOD EC;1P
Adder
12.464
274730ELWOOD EC;6P
Adder
12.465
274734ELWOOD EC;8P
Adder
12.465
274736ELWOOD EC;9P
Adder
12.465
970289AG2-191 GEN
Solar/Wind Harmer
0.58
946031AF1-268 GEN
Solar/Wind Harmer
4.982
943121AE2-341 GEN
Solar/Wind Harmer
8.771
943591AF1-030 GEN
Solar/Wind Harmer
5.832
270004AE1-209 GEN
Solar/Wind Harmer
1.133
274862TOP CROP ;2U
Solar/Wind Harmer
0.701
970825AG2-519 GEN
Solar/Wind Harmer
3.908
274682WAUKEGAN ;7U
Adder
13.321
276868AE1-113 GEN
Solar/Wind Harmer
1.021
274879MINONK ;1U
Solar/Wind Harmer
0.213
946671AF1-331 GEN
Solar/Wind Harmer
0.54
274855GSG-6 ;RU
Solar/Wind Harmer
0.185
274850MENDOTA H;RU
Solar/Wind Harmer
0.059
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
5.046
959091AF2-200 GEN
Solar/Wind Harmer
10.069
970571AG2-364 GEN
Solar/Wind Harmer
9.976
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.581
274767LEE CO EC;8U
Adder
6.504
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
960861AF2-377 GEN
50/50
2.456
970521AG2-332 GEN
50/50
11.157
24639705ELKHART HY
50/50
0.154
270143AC1-141 CT2_
50/50
2.081
24344105CKG2
50/50
6.284
24307105BERRINSP G
50/50
0.018
965011AG1-365 GEN
Solar/Wind Harmer
13.973
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.92
958861AF2-177 GEN
Solar/Wind Harmer
2.759
945111AF1-176 GEN
Solar/Wind Harmer
10.951
957891AF2-083 GEN
Solar/Wind Harmer
10.053
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.079
970373AG2-245 GEN
Solar/Wind Harmer
11.559
274751CRETE EC ;1U
Adder
6.49
274754CRETE EC ;4U
Adder
6.49
274723RIVER EC ;12
Adder
14.067
274812UNIV PK N;8U
Adder
3.9
270055AF2-134 C O1
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.162
965091AG1-374 GEN
Solar/Wind Harmer
14.177
959611AF2-252 GEN
Solar/Wind Harmer
1.575
965931AG1-462 GEN
Solar/Wind Harmer
12.05
971087AG2-675 GEN
Solar/Wind Harmer
2.52
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.067
957381AF2-032 GEN
Solar/Wind Harmer
0.966
942481AE2-261 GEN
Solar/Wind Harmer
12.705
970193AG2-126 GEN
Solar/Wind Harmer
6.182
24728705AND G3
Adder
4.563
24728505AND G1
Adder
2.182
246938BC-WTG3
Solar/Wind Helper
11.03
942871AE2-306 GEN
Solar/Wind Helper
0.436
270284AF1-227 GEN1
Solar/Wind Helper
1.841
270287AF1-227 GEN3
Solar/Wind Helper
0.675
276820AF1-078_GEN
Solar/Wind Helper
0.321
270541AE2-072 C
Solar/Wind Helper
0.902
24729405KEY G3
50/50
0.382
24729305KEY G2
50/50
0.375
24729205KEY G1
50/50
0.374
247620Y3-023
50/50
0.478
960851AF2-376 GEN
50/50
2.145
24643105BUCHANAN
50/50
0.011
270102X2-052 ST
50/50
1.316
270100X2-052 CT1
50/50
1.216
270101X2-052 CT2
50/50
1.216
270246TR4_N_V150
Solar/Wind Harmer
0.047
270247TR4_N_V136
Solar/Wind Harmer
0.047
942221AE2-234 GEN
Solar/Wind Harmer
2.915
944231AF1-091 GEN
Solar/Wind Harmer
16.486
944541AF1-119 GEN
Solar/Wind Harmer
0.437
960971AF2-388 GEN
Solar/Wind Harmer
3.84
970349AG2-230 GEN
Solar/Wind Harmer
9.006
961051AF2-396 GEN
Solar/Wind Harmer
11.975
961051AF2-396 GEN
Solar/Wind Harmer
7.983
270031AE2-169
Solar/Wind Harmer
3.187
270599AE1-208 GEN
Solar/Wind Harmer
5.311
965681AG1-436 GEN
Solar/Wind Harmer
7.151
965791AG1-447 GEN
Solar/Wind Harmer
5.244
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.421
247621Y3-024
Adder
0.188
274805UNIV PK N;1U
Adder
3.909
274808UNIV PK N;4U
Adder
3.883
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.547
274771LINCOLN ;2U
Adder
6.547
274888KELLY CRK;1U
Solar/Wind Harmer
0.312
276776AD2-060 GEN
Solar/Wind Harmer
0.571
958011AF2-095 GEN
Solar/Wind Harmer
7.714
970941AG2-585 GEN
Solar/Wind Harmer
2.946
276897AD1-100 C
Solar/Wind Harmer
13.263
274674JOLIET 9 ;6U
Adder
11.68
276893AG1-478 C
Solar/Wind Harmer
0.353
970291AG2-192 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.317
971613AH1-306 GEN
Solar/Wind Harmer
2.514
958481AF2-142 GEN
Solar/Wind Harmer
7.796
274696ROCKY RD ;4P
Adder
8.451
274695ROCKY RD ;2P
Adder
8.256
274773LINCOLN ;4U
Adder
6.547
274774LINCOLN ;5U
Adder
6.547
274802UNIV PARK;5U
Adder
4.495
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.946
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
23.324
274674JOLIET 9 ;6U
Adder
11.68
274732ELWOOD EC;7P
Adder
12.465
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.552
270594AE1-207 GEN
Solar/Wind Harmer
5.867
270032AE2-172
Solar/Wind Harmer
3.492
270005AE1-210 C O1
Solar/Wind Harmer
1.133
274745AC1-111 GEN9
Adder
4.189
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.845
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.842
274682WAUKEGAN ;7U
Adder
13.321
274828WAUKEGAN ;BP
Adder
8.177
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.874
939401AE1-172 GEN
Solar/Wind Harmer
3.83
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.596
971997AH1-543 GEN
Solar/Wind Harmer
2.669
957471AF2-041 GEN
Solar/Wind Harmer
15.103
959081AF2-199 GEN
Solar/Wind Harmer
5.034
971067AG2-660 GEN
Solar/Wind Harmer
1.678
274822ROCKFORD ;11
Adder
14.119
276903AD2-071 C
Solar/Wind Harmer
5.594
970819AG2-516 GEN
Solar/Wind Harmer
5.99
970569AG2-363 GEN
Solar/Wind Harmer
14.964
274858EASY ROAD;U2
Solar/Wind Harmer
0
274693ROCKY RD ;1P
Adder
8.175
274697ROCKY RD ;3P
Adder
2.243
274683WAUKEGAN ;8U
Adder
15.599
274683WAUKEGAN ;8U
Adder
13.149
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
15.403
958491AF2-143 GEN
Solar/Wind Harmer
7.702
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
10.069
971343AH1-151 GEN
Solar/Wind Harmer
10.069
972235AH1-702 GEN1
Adder
1.809
972236AH1-702 GEN2
Adder
1.573
938861AE1-114 GEN
Solar/Wind Harmer
2.807
274764LEE CO EC;5U
Adder
6.597
274765LEE CO EC;6U
Adder
6.597
274762LEE CO EC;3U
Adder
6.581
274763LEE CO EC;4U
Adder
6.519
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.787
276645AC1-214 GEN1
Solar/Wind Harmer
0.191
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.55
942111AE2-223 GEN
Solar/Wind Harmer
1.562
960611AF2-352 GEN
Solar/Wind Harmer
1.575
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.631
970885AG2-551 GEN
Solar/Wind Harmer
1.544
970241AG2-163 GEN
Solar/Wind Harmer
2.669
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.046
276838X2-022 GEN2
Solar/Wind Harmer
0.248
276916AD2-100_GEN
Solar/Wind Harmer
8.848
276911AD2-131_GEN
Solar/Wind Harmer
0.583
945391AF1-204 GEN
Solar/Wind Harmer
4.379
970623AG2-406 GEN
Solar/Wind Harmer
0.684
971587AH1-292 GEN
Solar/Wind Harmer
2.578
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.844
270462AD2-086
Solar/Wind Helper
3.683
247522W1-056 GEN
Solar/Wind Helper
1.146
253378AE2-206_GEN
Solar/Wind Helper
0.688
270349AD2-093_GEN
Solar/Wind Helper
0.824
270471AD2-092_GEN
Solar/Wind Helper
0.824
241960AC2-195 GEN
Solar/Wind Helper
0.664
24729505KEY G4
50/50
6.995
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.016
270144AC1-141 ST1_
50/50
1.838
24344005CKG1
50/50
5.28
959331AF2-224 GEN
Solar/Wind Harmer
9.781
963791AG1-232 GEN
Solar/Wind Harmer
12.238
970031AG2-029 GEN
Solar/Wind Harmer
4.668
965041AG1-368 GEN
Solar/Wind Harmer
8.594
270071AF1-092 GEN
Solar/Wind Harmer
14.854
247521TR3_G114
Solar/Wind Harmer
0.267
965051AG1-369 GEN
Solar/Wind Harmer
3.677
971771AH1-392 GEN
Solar/Wind Harmer
6.058
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.946
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.189
274775LINCOLN ;6U
Adder
6.547
274776LINCOLN ;7U
Adder
6.547
274777LINCOLN ;8U
Adder
6.547
972037AH1-567 GEN1
Adder
0.141
274827FISK ;RP
Adder
5.975
274800UNIV PARK;3U
Adder
4.482
274801UNIV PARK;4U
Adder
4.482
960591AF2-350 GEN
Solar/Wind Harmer
5.357
972228AH1-698 GEN2
Adder
2.836
972227AH1-698 GEN1
Adder
1.997
274687WILL CNTY;4U
Adder
21.288
274687WILL CNTY;4U
Adder
21.288
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
23.324
274675JOLIET 29;7U
Adder
22.491
274728ELWOOD EC;5P
Adder
12.465
274731ELWOOD EC;2P
Adder
12.464
274733ELWOOD EC;3P
Adder
12.464
274735ELWOOD EC;4P
Adder
12.464
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.003
970833AG2-524 GEN
Solar/Wind Harmer
5.794
970833AG2-524 GEN
Solar/Wind Harmer
3.862
971611AH1-305 GEN
Solar/Wind Harmer
3.121
274744AC1-111 GEN8
Adder
4.189
274746AC1-111 G10
Adder
4.189
970073AG2-061 GEN
Solar/Wind Harmer
1.711
247536S-71 GEN
Solar/Wind Harmer
0.205
971411AH1-196 GEN
Solar/Wind Harmer
7.602
971675AH1-338 GEN
Solar/Wind Harmer
1.975
276861AD2-134 GEN
Solar/Wind Harmer
0.09
276863AD2-134 GEN
Solar/Wind Harmer
0.09
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
10.069
274823ROCKFORD ;21
Adder
14.017
274856ECOGROVE ;U1
Solar/Wind Harmer
0.116
926823AC1-168 GEN
Solar/Wind Harmer
0.847
970169AG2-114 GEN
Solar/Wind Harmer
4.974
971681AH1-341 GEN
Solar/Wind Harmer
7.978
971549AH1-272 GEN
Solar/Wind Harmer
10.208
972267AH1-718 GEN
Adder
2.917
276741O09 GEN1
Solar/Wind Harmer
0.172
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.162
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
5.047
946321AF1-296 GEN
Solar/Wind Harmer
2.661
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.041
270543AE2-219 C
Solar/Wind Harmer
3.242
276668AB2-070 GEN1
Solar/Wind Harmer
0.176
276848AB2-070 GEN3
Solar/Wind Harmer
0.175
276849AB2-070 GEN2
Solar/Wind Harmer
0.176
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
6.154
944221AF1-090 GEN
Solar/Wind Harmer
2.4
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.567
270223U2-072_GEN1
Solar/Wind Helper
0.859
270224U2-072_GEN2
Solar/Wind Helper
0.859
270227U2-072_GEN3
Solar/Wind Helper
0.859
270228U2-072_GEN4
Solar/Wind Helper
0.859
270231U2-072_GEN5
Solar/Wind Helper
0.859
966831AG1-554 GEN
Solar/Wind Helper
0.861
270499AE1-146 GEN
Solar/Wind Helper
1.911
945641AF1-229 GEN
Solar/Wind Helper
0.907
274761LEE CO EC;2U
Adder
6.581
274766LEE CO EC;7U
Adder
6.504
276708O09 GEN2
Solar/Wind Harmer
0.172
276646AC1-214 GEN2
Solar/Wind Harmer
0.191
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.73
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.397
963741AG1-226 GEN
Solar/Wind Harmer
10.829
276621W2-048 GEN
Solar/Wind Harmer
0.22
965911AG1-460 GEN
Solar/Wind Harmer
0.85
24728605AND G2
Adder
2.182
970773AG2-487 GEN
Solar/Wind Harmer
0.657
246936BC-WTG1
Solar/Wind Helper
10.844
270317AD1-130_GEN
Solar/Wind Helper
4.072
270485AE1-090_GEN
Solar/Wind Helper
0.32
270391AF1-285 GEN3
Solar/Wind Helper
0.582
270578AF1-285 GEN2
Solar/Wind Helper
0.582
270286AF1-227 GEN2
Solar/Wind Helper
0.675
960841AF2-375 GEN
Solar/Wind Helper
1.143
990497J1323
External Queue
1.5952997207641602
990792J1392
External Queue
5.487830638885498
LAGNLTFEXP_LAGN->PJM
CLTF
6.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.165
TVALTFEXP_TVA->PJM
CLTF
2.538
NYPJM->LTFIMP_NY
CLTF
1.125
LGEELTFEXP_LGEE->PJM
CLTF
1.97
WECLTFEXP_WEC->PJM
CLTF
2.738
AG2-052LTFEXP_AG2-052->PJM
LTF
0.177
AH1-155LTFEXP_AH1-155->PJM
LTF
0.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.755
MECLTFEXP_MEC->PJM
CLTF
10.148
SIGELTFEXP_SIGE->PJM
CLTF
0.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.75

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.15 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1395.07
MW Contribution:
8.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
22.128
270462AD2-086
Solar/Wind Harmer
26.464
246937BC-WTG2
Solar/Wind Harmer
4.399
247607V1-011 GEN
Solar/Wind Harmer
3.339
247522W1-056 GEN
Solar/Wind Harmer
1.847
942801AE2-298 GEN
Solar/Wind Harmer
1.189
270246TR4_N_V150
Solar/Wind Harmer
0.61
270247TR4_N_V136
Solar/Wind Harmer
0.61
944231AF1-091 GEN
Solar/Wind Harmer
11.024
965431AG1-411 GEN
50/50
12.595
24727105RPMNG2
50/50
0.95
270284AF1-227 GEN1
Solar/Wind Harmer
35.351
270287AF1-227 GEN3
Solar/Wind Harmer
13.078
942871AE2-306 GEN
Solar/Wind Harmer
3.981
270391AF1-285 GEN3
Solar/Wind Harmer
2.042
246938BC-WTG3
Solar/Wind Harmer
4.475
270491AE1-102 GEN2
Solar/Wind Harmer
1.462
270588AE1-091_GEN
Solar/Wind Harmer
10.972
270541AE2-072 C
Solar/Wind Harmer
3.906
958091AF2-103 GEN
Solar/Wind Harmer
0.136
24695305TIMB G C
Solar/Wind Harmer
2.566
270044AE2-322 C
Solar/Wind Harmer
0.961
965021AG1-366 GEN
Solar/Wind Harmer
1.611
23906502RICHG2&3
Adder
0.824
23906402RICHG1
Adder
0.82
958321AF2-126 GEN
Solar/Wind Harmer
0.808
241832AE2-181_GEN
Solar/Wind Harmer
0.903
23929302BS-PKR
Adder
0.785
270043AE2-236 GEN
Solar/Wind Harmer
2.74
270063AE2-323 C
Solar/Wind Harmer
1.089
945111AF1-176 GEN
Solar/Wind Harmer
2.446
247643Z2-116 C
Solar/Wind Harmer
0.03
270036AE2-216 BAT
50/50
24.341
24727205RPMNG3
50/50
0.944
270223U2-072_GEN1
Solar/Wind Harmer
8.667
270224U2-072_GEN2
Solar/Wind Harmer
8.667
270227U2-072_GEN3
Solar/Wind Harmer
8.667
270228U2-072_GEN4
Solar/Wind Harmer
8.667
270231U2-072_GEN5
Solar/Wind Harmer
8.667
270578AF1-285 GEN2
Solar/Wind Harmer
2.042
270302AB2-170 GEN
Solar/Wind Harmer
31.864
957201AF2-014 GEN
Solar/Wind Harmer
5.1
270435AC2-044 GEN
Solar/Wind Harmer
2.249
270007AE1-245 C
Solar/Wind Harmer
4.562
966831AG1-554 GEN
Solar/Wind Harmer
1
270499AE1-146 GEN
Solar/Wind Harmer
2.038
270361_3
Solar/Wind Harmer
6.464
270575GUS2 35KV
Solar/Wind Harmer
7.615
270404AC1-167 GEN
Solar/Wind Harmer
0.792
247521TR3_G114
Solar/Wind Harmer
2.411
270191TR4_S_V150
Solar/Wind Harmer
2.151
965051AG1-369 GEN
Solar/Wind Harmer
3.582
965041AG1-368 GEN
Solar/Wind Harmer
7.168
959331AF2-224 GEN
Solar/Wind Harmer
6.929
945411AF1-206 GEN
Solar/Wind Harmer
3.609
963791AG1-232 GEN
Solar/Wind Harmer
7.328
945641AF1-229 GEN
Solar/Wind Harmer
1.915
970031AG2-029 GEN
Solar/Wind Harmer
12.871
270071AF1-092 GEN
Solar/Wind Harmer
6.824
971549AH1-272 GEN
Solar/Wind Harmer
8.295
270377AD1-106 GEN
Solar/Wind Harmer
2.318
24727005RPMNG1
50/50
0.949
270286AF1-227 GEN2
Solar/Wind Harmer
13.078
270391AF1-285 GEN3
Solar/Wind Harmer
5.308
270578AF1-285 GEN2
Solar/Wind Harmer
5.308
270317AD1-130_GEN
Solar/Wind Harmer
12.182
270485AE1-090_GEN
Solar/Wind Harmer
2.301
246936BC-WTG1
Solar/Wind Harmer
4.399
270489AE1-102 GEN1
Solar/Wind Harmer
1.462
965421AG1-410 GEN
Solar/Wind Harmer
32.496
270297AD1-101 GEN
Solar/Wind Harmer
1.723
960841AF2-375 GEN
Solar/Wind Harmer
3.024
270258AD1-119 GEN
Solar/Wind Harmer
1.505
965011AG1-365 GEN
Solar/Wind Harmer
6.929
23906502RICHG2&3
Adder
0.824
241840AF1-064_GEN
Solar/Wind Harmer
0.752
23920202STRYCT
Adder
0.862
241858AF1-205_GEN
Solar/Wind Harmer
2.39
972253AH1-711 GEN
Adder
18.601
24639705ELKHART HY
Adder
0.068
270216AD2-079_GEN
Solar/Wind Harmer
0.262
945111AF1-176 GEN
Solar/Wind Harmer
7.718
270520AE2-214 GEN
Solar/Wind Helper
1.267
241996AE2-282_GEN
Solar/Wind Harmer
0.964
241808AF1-120 C
Solar/Wind Harmer
0.537
247620Y3-023
Adder
0.211
942221AE2-234 GEN
Solar/Wind Harmer
1.516
961051AF2-396 GEN
Solar/Wind Harmer
6.826
961051AF2-396 GEN
Solar/Wind Harmer
3.175
270349AD2-093_GEN
Solar/Wind Helper
1.799
270471AD2-092_GEN
Solar/Wind Helper
1.799
946101AF1-275 GEN
Solar/Wind Helper
0.317
270054AF2-122 C O1
Solar/Wind Helper
0.659
LAGNLTFEXP_LAGN->PJM
CLTF
2.134
TVALTFEXP_TVA->PJM
CLTF
0.764
NYPJM->LTFIMP_NY
CLTF
0.788
LGEELTFEXP_LGEE->PJM
CLTF
0.75
WECLTFEXP_WEC->PJM
CLTF
1.225
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.36
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.172
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.333
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.091
MECLTFEXP_MEC->PJM
CLTF
4.396
SIGELTFEXP_SIGE->PJM
CLTF
0.086
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.839

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.82 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1646.06
MW Contribution:
8.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
7.81
270284AF1-227 GEN1
Solar/Wind Harmer
6.84
270287AF1-227 GEN3
Solar/Wind Harmer
2.53
942871AE2-306 GEN
Solar/Wind Harmer
0.907
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
942051AE2-217 GEN
Solar/Wind Harmer
13.98
970065AG2-057 GEN
Solar/Wind Harmer
0.651
276820AF1-078_GEN
Solar/Wind Harmer
1.068
962771AG1-126 GEN
Solar/Wind Harmer
20.895
270036AE2-216 BAT
50/50
5.971
270223U2-072_GEN1
Solar/Wind Harmer
1.974
270224U2-072_GEN2
Solar/Wind Harmer
1.974
270227U2-072_GEN3
Solar/Wind Harmer
1.974
270228U2-072_GEN4
Solar/Wind Harmer
1.974
270231U2-072_GEN5
Solar/Wind Harmer
1.974
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
241973AD2-163_GEN1
Solar/Wind Harmer
1.951
241974AD2-163_GEN2
Solar/Wind Harmer
1.951
270302AB2-170 GEN
Solar/Wind Harmer
7.816
970179AG2-119 GEN
Solar/Wind Harmer
6.791
241955AC1-078 GEN
Solar/Wind Harmer
4.994
957201AF2-014 GEN
Solar/Wind Harmer
2.726
270435AC2-044 GEN
Solar/Wind Harmer
1.202
241972AD1-140 GEN
Solar/Wind Harmer
2.573
270007AE1-245 C
Solar/Wind Harmer
3.051
247521TR3_G114
Solar/Wind Harmer
1.861
270191TR4_S_V150
Solar/Wind Harmer
1.66
965051AG1-369 GEN
Solar/Wind Harmer
2.764
965041AG1-368 GEN
Solar/Wind Harmer
5.371
945631AF1-228 GEN
Solar/Wind Harmer
2.514
959331AF2-224 GEN
Solar/Wind Harmer
5.3
270404AC1-167 GEN
Solar/Wind Harmer
0.571
943861AF1-054 GEN
Solar/Wind Harmer
1.939
943851AF1-053 GEN
Solar/Wind Harmer
0.937
963791AG1-232 GEN
Solar/Wind Harmer
6.712
253338AC1-165 GEN
Solar/Wind Harmer
0.524
253343AC1-166 GEN
Solar/Wind Harmer
0.524
970031AG2-029 GEN
Solar/Wind Harmer
12.056
270071AF1-092 GEN
Solar/Wind Harmer
7.206
24729505KEY G4
Adder
3.077
25306009OHH W.
Adder
1.341
253372AE2-315 SEC3
Adder
0.879
270286AF1-227 GEN2
Solar/Wind Harmer
2.53
971995AH1-542 GEN
Solar/Wind Harmer
11.797
270391AF1-285 GEN3
Solar/Wind Harmer
1.209
270578AF1-285 GEN2
Solar/Wind Harmer
1.209
270317AD1-130_GEN
Solar/Wind Harmer
2.988
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270520AE2-214 GEN
Solar/Wind Harmer
5.389
241813AF1-122_GEN
Solar/Wind Harmer
4.164
971201AH1-060 GEN
Solar/Wind Harmer
1.301
962761AG1-125 GEN
Solar/Wind Harmer
20.895
970149AG2-104 GEN
Solar/Wind Harmer
12.903
970155AG2-107 GEN
Solar/Wind Harmer
9.111
246936BC-WTG1
Solar/Wind Harmer
2.351
270489AE1-102 GEN1
Solar/Wind Harmer
0.781
965421AG1-410 GEN
Solar/Wind Harmer
17.827
970153AG2-106 GEN
Solar/Wind Harmer
9.111
246938BC-WTG3
Solar/Wind Harmer
2.392
270491AE1-102 GEN2
Solar/Wind Harmer
0.781
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.831
965021AG1-366 GEN
Solar/Wind Harmer
1.232
270044AE2-322 C
Solar/Wind Harmer
0.692
270518AE2-148 GEN
Solar/Wind Harmer
6.261
270588AE1-091_GEN
Solar/Wind Harmer
5.505
270043AE2-236 GEN
Solar/Wind Harmer
2.704
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
0.73
270063AE2-323 C
Solar/Wind Harmer
1.052
944531AF1-118 GEN
Solar/Wind Harmer
16.732
270541AE2-072 C
Solar/Wind Harmer
2.158
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
971347AH1-153 GEN
Solar/Wind Harmer
2.305
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.583
270505AE1-170 C O1
Solar/Wind Harmer
6.831
962031AG1-047 GEN
Solar/Wind Harmer
1.364
957741AF2-068 GEN
Solar/Wind Harmer
6.767
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.655
270004AE1-209 GEN
Solar/Wind Harmer
2.395
970825AG2-519 GEN
Solar/Wind Harmer
2.467
972231SS25-0005
Solar/Wind Harmer
4.147
972181SS23-001
Solar/Wind Harmer
2.592
274752CRETE EC ;2U
Adder
2.136
274753CRETE EC ;3U
Adder
2.136
274772LINCOLN ;3U
Adder
2.707
274724RIVER EC ;11
Adder
7.731
276164X3-005 C
Solar/Wind Harmer
0.306
274814UNIV PK N;0U
Adder
2.197
274807UNIV PK N;3U
Adder
2.192
274811UNIV PK N;7U
Adder
2.178
965461AG1-414 GEN
Solar/Wind Harmer
0.984
970289AG2-191 GEN
Solar/Wind Harmer
0.333
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.524
274826FISK ;BP
Adder
4.738
274887GEN-1.85
Solar/Wind Harmer
2.304
276772AC2-154 GEN
Solar/Wind Harmer
1.207
276843GEN-1.7
Solar/Wind Harmer
0.248
276806AD2-047 C O1
Solar/Wind Harmer
4.627
972038AH1-567 GEN2
Adder
0.158
964401AG1-302 GEN
Solar/Wind Harmer
3.921
972259AH1-714 GEN
Adder
8.237
274676JOLIET 29;8U
Adder
12.724
970707AG2-453 GEN
Solar/Wind Harmer
11.087
253372AE2-315 SEC3
Adder
0.879
958711AF2-162 GEN
Solar/Wind Harmer
0.469
971771AH1-392 GEN
Solar/Wind Harmer
4.103
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.999
270526AF1-158 GEN
Solar/Wind Harmer
2.05
961761AG1-017 GEN
Solar/Wind Harmer
0.193
964611AG1-324 GEN
Solar/Wind Harmer
1.75
247536S-71 GEN
Solar/Wind Harmer
1.815
960681AF2-359 GEN
Solar/Wind Harmer
1.694
270543AE2-219 C
Solar/Wind Harmer
4.458
971029AG2-637 GEN
Solar/Wind Harmer
6.646
971549AH1-272 GEN
Solar/Wind Harmer
8.101
274775LINCOLN ;6U
Adder
2.707
274776LINCOLN ;7U
Adder
2.707
274777LINCOLN ;8U
Adder
2.707
970289AG2-191 GEN
Solar/Wind Harmer
0.824
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.358
960591AF2-350 GEN
Solar/Wind Harmer
4.325
274800UNIV PARK;3U
Adder
2.522
274801UNIV PARK;4U
Adder
2.522
972228AH1-698 GEN2
Adder
1.601
972227AH1-698 GEN1
Adder
1.127
274687WILL CNTY;4U
Adder
12.029
274687WILL CNTY;4U
Adder
12.029
274675JOLIET 29;7U
Adder
13.196
274675JOLIET 29;7U
Adder
12.725
270297AD1-101 GEN
Solar/Wind Harmer
1.129
270258AD1-119 GEN
Solar/Wind Harmer
1.095
965011AG1-365 GEN
Solar/Wind Harmer
5.3
253333AC1-068 GEN
Solar/Wind Harmer
0.505
25326309TAIT D
Adder
0.527
270024AE2-089 GEN
Solar/Wind Harmer
2.197
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
965651AG1-433 GEN
Solar/Wind Harmer
2.534
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.279
958861AF2-177 GEN
Solar/Wind Harmer
5.03
945111AF1-176 GEN
Solar/Wind Harmer
8.149
957891AF2-083 GEN
Solar/Wind Harmer
6.834
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.271
943021AE2-325 GEN
Solar/Wind Harmer
1.652
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.221
270005AE1-210 C O1
Solar/Wind Harmer
2.395
970825AG2-519 GEN
Solar/Wind Harmer
0.919
274751CRETE EC ;1U
Adder
2.136
274754CRETE EC ;4U
Adder
2.136
972207SS24-0001
Solar/Wind Harmer
9.624
274773LINCOLN ;4U
Adder
2.707
274774LINCOLN ;5U
Adder
2.707
274723RIVER EC ;12
Adder
7.823
270055AF2-134 C O1
Solar/Wind Harmer
1.317
274812UNIV PK N;8U
Adder
2.178
270594AE1-207 GEN
Solar/Wind Harmer
5.904
270032AE2-172
Solar/Wind Harmer
2.022
274802UNIV PARK;5U
Adder
2.524
958381AF2-132 GEN
Solar/Wind Harmer
3.921
274676JOLIET 29;8U
Adder
13.196
270466AD2-091
50/50
5.428
270349AD2-093_GEN
Solar/Wind Harmer
4.875
270471AD2-092_GEN
Solar/Wind Harmer
4.875
938701AE1-092 GEN
Solar/Wind Harmer
21.99
270462AD2-086
Solar/Wind Harmer
6.492
946101AF1-275 GEN
Solar/Wind Harmer
1.347
241960AC2-195 GEN
Solar/Wind Harmer
2.356
253378AE2-206_GEN
Solar/Wind Harmer
2.404
25326509SID D
Adder
0.839
246937BC-WTG2
Solar/Wind Harmer
2.351
942801AE2-298 GEN
Solar/Wind Harmer
0.86
247607V1-011 GEN
Solar/Wind Harmer
2.234
270246TR4_N_V150
Solar/Wind Harmer
0.471
270247TR4_N_V136
Solar/Wind Harmer
0.471
942861AE2-305 GEN
Solar/Wind Harmer
3.928
25326109MON D
Adder
0.654
944231AF1-091 GEN
Solar/Wind Harmer
8.795
25322209TAIT E
Adder
4.684
25322209TAIT E
Adder
4.578
942221AE2-234 GEN
Solar/Wind Harmer
1.652
253349AC2-067 GEN
Solar/Wind Harmer
0.96
253400AC2-068 GEN
Solar/Wind Harmer
0.386
247620Y3-023
Adder
0.214
253370AE2-315 SEC1
Adder
0.929
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.068
970349AG2-230 GEN
Solar/Wind Harmer
6.915
961051AF2-396 GEN
Solar/Wind Harmer
7.218
961051AF2-396 GEN
Solar/Wind Harmer
3.357
247621Y3-024
Adder
0.109
270201AC2-176 GEN
Solar/Wind Harmer
2.319
253383AE2-342_GEN
Solar/Wind Harmer
0.398
964611AG1-324 GEN
Solar/Wind Harmer
0.235
965681AG1-436 GEN
Solar/Wind Harmer
5.605
965791AG1-447 GEN
Solar/Wind Harmer
2.868
270031AE2-169
Solar/Wind Harmer
3.645
270599AE1-208 GEN
Solar/Wind Harmer
3.645
970883AG2-550 GEN
Solar/Wind Harmer
4.458
970885AG2-551 GEN
Solar/Wind Harmer
1.037
274770LINCOLN ;1U
Adder
2.707
274771LINCOLN ;2U
Adder
2.707
270535AF1-215 GEN1
Solar/Wind Harmer
1.976
270536AF1-215 GEN2
Solar/Wind Harmer
1.976
274805UNIV PK N;1U
Adder
2.183
274808UNIV PK N;4U
Adder
2.168
970291AG2-192 GEN
Solar/Wind Harmer
0.564
970291AG2-192 GEN
Solar/Wind Harmer
0.182
270383AD1-128 GEN
Solar/Wind Harmer
2.644
274888KELLY CRK;1U
Solar/Wind Harmer
2.552
276776AD2-060 GEN
Solar/Wind Harmer
0.181
958011AF2-095 GEN
Solar/Wind Harmer
6.228
970941AG2-585 GEN
Solar/Wind Harmer
2.379
270054AF2-122 C O1
Solar/Wind Helper
0.827
LAGNLTFEXP_LAGN->PJM
CLTF
5.1
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.32
TVALTFEXP_TVA->PJM
CLTF
2.365
NYPJM->LTFIMP_NY
CLTF
1.312
LGEELTFEXP_LGEE->PJM
CLTF
2.29
WECLTFEXP_WEC->PJM
CLTF
1.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.311
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.538
MECLTFEXP_MEC->PJM
CLTF
6.315
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.726

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.97 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1563.59
MW Contribution:
8.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270286AF1-227 GEN2
Solar/Wind Harmer
2.524
971995AH1-542 GEN
Solar/Wind Harmer
11.77
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270317AD1-130_GEN
Solar/Wind Harmer
2.981
270485AE1-090_GEN
Solar/Wind Harmer
0.563
270520AE2-214 GEN
Solar/Wind Harmer
5.374
241813AF1-122_GEN
Solar/Wind Harmer
4.155
971201AH1-060 GEN
Solar/Wind Harmer
1.298
962761AG1-125 GEN
Solar/Wind Harmer
20.847
970149AG2-104 GEN
Solar/Wind Harmer
12.873
970155AG2-107 GEN
Solar/Wind Harmer
9.09
246936BC-WTG1
Solar/Wind Harmer
2.346
270489AE1-102 GEN1
Solar/Wind Harmer
0.78
965421AG1-410 GEN
Solar/Wind Harmer
17.787
270297AD1-101 GEN
Solar/Wind Harmer
1.127
270258AD1-119 GEN
Solar/Wind Harmer
1.093
965011AG1-365 GEN
Solar/Wind Harmer
5.288
270036AE2-216 BAT
50/50
5.957
270223U2-072_GEN1
Solar/Wind Harmer
1.969
270224U2-072_GEN2
Solar/Wind Harmer
1.969
270227U2-072_GEN3
Solar/Wind Harmer
1.969
270228U2-072_GEN4
Solar/Wind Harmer
1.969
270231U2-072_GEN5
Solar/Wind Harmer
1.969
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.945
241974AD2-163_GEN2
Solar/Wind Harmer
1.945
270302AB2-170 GEN
Solar/Wind Harmer
7.798
970179AG2-119 GEN
Solar/Wind Harmer
6.776
241955AC1-078 GEN
Solar/Wind Harmer
4.984
957201AF2-014 GEN
Solar/Wind Harmer
2.72
270435AC2-044 GEN
Solar/Wind Harmer
1.199
241972AD1-140 GEN
Solar/Wind Harmer
2.566
270007AE1-245 C
Solar/Wind Harmer
3.044
247521TR3_G114
Solar/Wind Harmer
1.857
270191TR4_S_V150
Solar/Wind Harmer
1.657
965051AG1-369 GEN
Solar/Wind Harmer
2.758
965041AG1-368 GEN
Solar/Wind Harmer
5.359
945631AF1-228 GEN
Solar/Wind Harmer
2.509
959331AF2-224 GEN
Solar/Wind Harmer
5.288
270404AC1-167 GEN
Solar/Wind Harmer
0.569
270466AD2-091
50/50
5.415
270349AD2-093_GEN
Solar/Wind Harmer
4.863
270471AD2-092_GEN
Solar/Wind Harmer
4.863
938701AE1-092 GEN
Solar/Wind Harmer
21.934
270462AD2-086
Solar/Wind Harmer
6.477
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.35
253378AE2-206_GEN
Solar/Wind Harmer
2.398
25326509SID D
Adder
0.837
246937BC-WTG2
Solar/Wind Harmer
2.346
942801AE2-298 GEN
Solar/Wind Harmer
0.858
247607V1-011 GEN
Solar/Wind Harmer
2.229
270246TR4_N_V150
Solar/Wind Harmer
0.47
270247TR4_N_V136
Solar/Wind Harmer
0.47
270475AD2-096_GEN
50/50
7.792
270284AF1-227 GEN1
Solar/Wind Harmer
6.824
270287AF1-227 GEN3
Solar/Wind Harmer
2.524
942871AE2-306 GEN
Solar/Wind Harmer
0.905
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
942051AE2-217 GEN
Solar/Wind Harmer
13.942
970065AG2-057 GEN
Solar/Wind Harmer
0.649
276820AF1-078_GEN
Solar/Wind Harmer
1.065
962771AG1-126 GEN
Solar/Wind Harmer
20.847
970153AG2-106 GEN
Solar/Wind Harmer
9.09
246938BC-WTG3
Solar/Wind Harmer
2.386
270491AE1-102 GEN2
Solar/Wind Harmer
0.78
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.827
965021AG1-366 GEN
Solar/Wind Harmer
1.23
270044AE2-322 C
Solar/Wind Harmer
0.691
943861AF1-054 GEN
Solar/Wind Harmer
1.926
943851AF1-053 GEN
Solar/Wind Harmer
0.931
963791AG1-232 GEN
Solar/Wind Harmer
6.697
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253343AC1-166 GEN
Solar/Wind Harmer
0.523
970031AG2-029 GEN
Solar/Wind Harmer
12.029
270071AF1-092 GEN
Solar/Wind Harmer
7.19
24729505KEY G4
Adder
3.07
25306009OHH W.
Adder
1.338
958711AF2-162 GEN
Solar/Wind Harmer
0.468
253372AE2-315 SEC3
Adder
0.877
253372AE2-315 SEC3
Adder
0.877
971771AH1-392 GEN
Solar/Wind Harmer
4.095
945581AF1-223 GEN
Solar/Wind Harmer
2.053
944161AF1-084 GEN
Solar/Wind Harmer
0.997
270526AF1-158 GEN
Solar/Wind Harmer
2.045
961761AG1-017 GEN
Solar/Wind Harmer
0.193
964611AG1-324 GEN
Solar/Wind Harmer
1.747
247536S-71 GEN
Solar/Wind Harmer
1.811
960681AF2-359 GEN
Solar/Wind Harmer
1.691
270543AE2-219 C
Solar/Wind Harmer
4.448
971029AG2-637 GEN
Solar/Wind Harmer
6.632
971549AH1-272 GEN
Solar/Wind Harmer
8.084
274775LINCOLN ;6U
Adder
2.701
274776LINCOLN ;7U
Adder
2.701
274777LINCOLN ;8U
Adder
2.701
970289AG2-191 GEN
Solar/Wind Harmer
0.823
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.351
960591AF2-350 GEN
Solar/Wind Harmer
4.316
274800UNIV PARK;3U
Adder
2.516
274801UNIV PARK;4U
Adder
2.516
972228AH1-698 GEN2
Adder
1.597
972227AH1-698 GEN1
Adder
1.125
253333AC1-068 GEN
Solar/Wind Harmer
0.504
25326309TAIT D
Adder
0.526
270024AE2-089 GEN
Solar/Wind Harmer
2.192
965651AG1-433 GEN
Solar/Wind Harmer
2.529
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.278
958861AF2-177 GEN
Solar/Wind Harmer
5.02
945111AF1-176 GEN
Solar/Wind Harmer
8.131
957891AF2-083 GEN
Solar/Wind Harmer
6.82
945371AF1-202 GEN
Solar/Wind Harmer
3.158
270449AD2-020 GEN
Solar/Wind Harmer
1.268
943021AE2-325 GEN
Solar/Wind Harmer
1.648
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.201
270005AE1-210 C O1
Solar/Wind Harmer
2.39
970825AG2-519 GEN
Solar/Wind Harmer
0.917
274751CRETE EC ;1U
Adder
2.131
274754CRETE EC ;4U
Adder
2.131
972207SS24-0001
Solar/Wind Harmer
9.604
274773LINCOLN ;4U
Adder
2.701
274774LINCOLN ;5U
Adder
2.701
274723RIVER EC ;12
Adder
7.806
270055AF2-134 C O1
Solar/Wind Harmer
1.315
274812UNIV PK N;8U
Adder
2.173
270594AE1-207 GEN
Solar/Wind Harmer
5.891
270032AE2-172
Solar/Wind Harmer
2.018
274802UNIV PARK;5U
Adder
2.519
958381AF2-132 GEN
Solar/Wind Harmer
3.912
270518AE2-148 GEN
Solar/Wind Harmer
6.249
270588AE1-091_GEN
Solar/Wind Harmer
5.494
270043AE2-236 GEN
Solar/Wind Harmer
2.698
253325AC1-069 GEN
Solar/Wind Harmer
0.504
960071AF2-298 GEN
Solar/Wind Harmer
0.728
270063AE2-323 C
Solar/Wind Harmer
1.049
944531AF1-118 GEN
Solar/Wind Harmer
16.696
270541AE2-072 C
Solar/Wind Harmer
2.153
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
971347AH1-153 GEN
Solar/Wind Harmer
2.3
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.577
270505AE1-170 C O1
Solar/Wind Harmer
6.816
962031AG1-047 GEN
Solar/Wind Harmer
1.361
957741AF2-068 GEN
Solar/Wind Harmer
6.753
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.647
270004AE1-209 GEN
Solar/Wind Harmer
2.39
970825AG2-519 GEN
Solar/Wind Harmer
2.462
972231SS25-0005
Solar/Wind Harmer
4.138
972181SS23-001
Solar/Wind Harmer
2.586
274752CRETE EC ;2U
Adder
2.131
274753CRETE EC ;3U
Adder
2.131
274772LINCOLN ;3U
Adder
2.701
274724RIVER EC ;11
Adder
7.714
276164X3-005 C
Solar/Wind Harmer
0.305
274814UNIV PK N;0U
Adder
2.192
274807UNIV PK N;3U
Adder
2.187
274811UNIV PK N;7U
Adder
2.173
965461AG1-414 GEN
Solar/Wind Harmer
0.982
970289AG2-191 GEN
Solar/Wind Harmer
0.332
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.519
274826FISK ;BP
Adder
4.728
274887GEN-1.85
Solar/Wind Harmer
2.299
276772AC2-154 GEN
Solar/Wind Harmer
1.204
276843GEN-1.7
Solar/Wind Harmer
0.247
276806AD2-047 C O1
Solar/Wind Harmer
4.617
972038AH1-567 GEN2
Adder
0.157
964401AG1-302 GEN
Solar/Wind Harmer
3.912
972259AH1-714 GEN
Adder
8.22
970707AG2-453 GEN
Solar/Wind Harmer
11.064
942861AE2-305 GEN
Solar/Wind Harmer
3.903
25326109MON D
Adder
0.652
944231AF1-091 GEN
Solar/Wind Harmer
8.776
25322209TAIT E
Adder
4.673
25322209TAIT E
Adder
4.568
942221AE2-234 GEN
Solar/Wind Harmer
1.648
253349AC2-067 GEN
Solar/Wind Harmer
0.958
253400AC2-068 GEN
Solar/Wind Harmer
0.385
247620Y3-023
Adder
0.214
944541AF1-119 GEN
Solar/Wind Harmer
1.937
960971AF2-388 GEN
Solar/Wind Harmer
5.057
253370AE2-315 SEC1
Adder
0.927
970349AG2-230 GEN
Solar/Wind Harmer
6.9
961051AF2-396 GEN
Solar/Wind Harmer
7.203
961051AF2-396 GEN
Solar/Wind Harmer
3.35
247621Y3-024
Adder
0.109
270201AC2-176 GEN
Solar/Wind Harmer
2.314
964611AG1-324 GEN
Solar/Wind Harmer
0.234
965681AG1-436 GEN
Solar/Wind Harmer
5.593
965791AG1-447 GEN
Solar/Wind Harmer
2.861
253383AE2-342_GEN
Solar/Wind Harmer
0.395
270031AE2-169
Solar/Wind Harmer
3.637
270599AE1-208 GEN
Solar/Wind Harmer
3.637
970883AG2-550 GEN
Solar/Wind Harmer
4.448
970885AG2-551 GEN
Solar/Wind Harmer
1.034
274770LINCOLN ;1U
Adder
2.701
274771LINCOLN ;2U
Adder
2.701
270535AF1-215 GEN1
Solar/Wind Harmer
1.972
270536AF1-215 GEN2
Solar/Wind Harmer
1.972
274805UNIV PK N;1U
Adder
2.178
274808UNIV PK N;4U
Adder
2.164
970291AG2-192 GEN
Solar/Wind Harmer
0.563
970291AG2-192 GEN
Solar/Wind Harmer
0.181
270383AD1-128 GEN
Solar/Wind Harmer
2.638
274888KELLY CRK;1U
Solar/Wind Harmer
2.547
276776AD2-060 GEN
Solar/Wind Harmer
0.181
958011AF2-095 GEN
Solar/Wind Harmer
6.215
970941AG2-585 GEN
Solar/Wind Harmer
2.374
270054AF2-122 C O1
Solar/Wind Helper
0.821
LAGNLTFEXP_LAGN->PJM
CLTF
5.09
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.316
TVALTFEXP_TVA->PJM
CLTF
2.361
NYPJM->LTFIMP_NY
CLTF
1.31
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.584
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.519
MECLTFEXP_MEC->PJM
CLTF
6.302
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.643

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.88 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1562.23
MW Contribution:
8.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
5.413
270349AD2-093_GEN
Solar/Wind Harmer
4.86
270471AD2-092_GEN
Solar/Wind Harmer
4.86
938701AE1-092 GEN
Solar/Wind Harmer
21.921
270462AD2-086
Solar/Wind Harmer
6.473
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.349
253378AE2-206_GEN
Solar/Wind Harmer
2.397
25326509SID D
Adder
0.837
246937BC-WTG2
Solar/Wind Harmer
2.344
942801AE2-298 GEN
Solar/Wind Harmer
0.858
247607V1-011 GEN
Solar/Wind Harmer
2.227
270246TR4_N_V150
Solar/Wind Harmer
0.469
270247TR4_N_V136
Solar/Wind Harmer
0.469
942861AE2-305 GEN
Solar/Wind Harmer
3.897
25326109MON D
Adder
0.652
944231AF1-091 GEN
Solar/Wind Harmer
8.771
25322209TAIT E
Adder
4.67
25322209TAIT E
Adder
4.565
942221AE2-234 GEN
Solar/Wind Harmer
1.648
253349AC2-067 GEN
Solar/Wind Harmer
0.957
253400AC2-068 GEN
Solar/Wind Harmer
0.385
247620Y3-023
Adder
0.214
944541AF1-119 GEN
Solar/Wind Harmer
1.936
960971AF2-388 GEN
Solar/Wind Harmer
5.055
253370AE2-315 SEC1
Adder
0.926
970349AG2-230 GEN
Solar/Wind Harmer
6.897
961051AF2-396 GEN
Solar/Wind Harmer
7.199
961051AF2-396 GEN
Solar/Wind Harmer
3.348
247621Y3-024
Adder
0.109
270201AC2-176 GEN
Solar/Wind Harmer
2.313
964611AG1-324 GEN
Solar/Wind Harmer
0.234
965681AG1-436 GEN
Solar/Wind Harmer
5.59
965791AG1-447 GEN
Solar/Wind Harmer
2.86
270031AE2-169
Solar/Wind Harmer
3.636
270599AE1-208 GEN
Solar/Wind Harmer
3.636
253383AE2-342_GEN
Solar/Wind Harmer
0.394
970883AG2-550 GEN
Solar/Wind Harmer
4.446
970885AG2-551 GEN
Solar/Wind Harmer
1.034
274770LINCOLN ;1U
Adder
2.7
274771LINCOLN ;2U
Adder
2.7
270475AD2-096_GEN
50/50
7.787
270284AF1-227 GEN1
Solar/Wind Harmer
6.82
270287AF1-227 GEN3
Solar/Wind Harmer
2.523
942871AE2-306 GEN
Solar/Wind Harmer
0.904
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
942051AE2-217 GEN
Solar/Wind Harmer
13.933
970065AG2-057 GEN
Solar/Wind Harmer
0.649
276820AF1-078_GEN
Solar/Wind Harmer
1.065
962771AG1-126 GEN
Solar/Wind Harmer
20.836
970153AG2-106 GEN
Solar/Wind Harmer
9.086
246938BC-WTG3
Solar/Wind Harmer
2.385
270491AE1-102 GEN2
Solar/Wind Harmer
0.779
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.826
965021AG1-366 GEN
Solar/Wind Harmer
1.229
270044AE2-322 C
Solar/Wind Harmer
0.691
270518AE2-148 GEN
Solar/Wind Harmer
6.247
270588AE1-091_GEN
Solar/Wind Harmer
5.492
270043AE2-236 GEN
Solar/Wind Harmer
2.697
253325AC1-069 GEN
Solar/Wind Harmer
0.504
960071AF2-298 GEN
Solar/Wind Harmer
0.728
270063AE2-323 C
Solar/Wind Harmer
1.049
944531AF1-118 GEN
Solar/Wind Harmer
16.688
270541AE2-072 C
Solar/Wind Harmer
2.152
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
971347AH1-153 GEN
Solar/Wind Harmer
2.299
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.576
270505AE1-170 C O1
Solar/Wind Harmer
6.813
962031AG1-047 GEN
Solar/Wind Harmer
1.36
957741AF2-068 GEN
Solar/Wind Harmer
6.749
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.645
270004AE1-209 GEN
Solar/Wind Harmer
2.388
970825AG2-519 GEN
Solar/Wind Harmer
2.461
972231SS25-0005
Solar/Wind Harmer
4.136
972181SS23-001
Solar/Wind Harmer
2.585
274752CRETE EC ;2U
Adder
2.13
274753CRETE EC ;3U
Adder
2.13
274772LINCOLN ;3U
Adder
2.7
270036AE2-216 BAT
50/50
5.954
270223U2-072_GEN1
Solar/Wind Harmer
1.968
270224U2-072_GEN2
Solar/Wind Harmer
1.968
270227U2-072_GEN3
Solar/Wind Harmer
1.968
270228U2-072_GEN4
Solar/Wind Harmer
1.968
270231U2-072_GEN5
Solar/Wind Harmer
1.968
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
270302AB2-170 GEN
Solar/Wind Harmer
7.794
970179AG2-119 GEN
Solar/Wind Harmer
6.772
241955AC1-078 GEN
Solar/Wind Harmer
4.982
957201AF2-014 GEN
Solar/Wind Harmer
2.718
270435AC2-044 GEN
Solar/Wind Harmer
1.199
241972AD1-140 GEN
Solar/Wind Harmer
2.564
270007AE1-245 C
Solar/Wind Harmer
3.043
247521TR3_G114
Solar/Wind Harmer
1.856
270191TR4_S_V150
Solar/Wind Harmer
1.656
965051AG1-369 GEN
Solar/Wind Harmer
2.757
965041AG1-368 GEN
Solar/Wind Harmer
5.357
945631AF1-228 GEN
Solar/Wind Harmer
2.508
959331AF2-224 GEN
Solar/Wind Harmer
5.285
270404AC1-167 GEN
Solar/Wind Harmer
0.569
943861AF1-054 GEN
Solar/Wind Harmer
1.923
943851AF1-053 GEN
Solar/Wind Harmer
0.929
963791AG1-232 GEN
Solar/Wind Harmer
6.694
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253343AC1-166 GEN
Solar/Wind Harmer
0.523
970031AG2-029 GEN
Solar/Wind Harmer
12.023
270071AF1-092 GEN
Solar/Wind Harmer
7.187
24729505KEY G4
Adder
3.068
25306009OHH W.
Adder
1.337
958711AF2-162 GEN
Solar/Wind Harmer
0.468
253372AE2-315 SEC3
Adder
0.876
253372AE2-315 SEC3
Adder
0.876
971771AH1-392 GEN
Solar/Wind Harmer
4.093
945581AF1-223 GEN
Solar/Wind Harmer
2.052
944161AF1-084 GEN
Solar/Wind Harmer
0.996
270526AF1-158 GEN
Solar/Wind Harmer
2.044
961761AG1-017 GEN
Solar/Wind Harmer
0.193
964611AG1-324 GEN
Solar/Wind Harmer
1.746
247536S-71 GEN
Solar/Wind Harmer
1.81
960681AF2-359 GEN
Solar/Wind Harmer
1.69
270543AE2-219 C
Solar/Wind Harmer
4.446
971029AG2-637 GEN
Solar/Wind Harmer
6.628
971549AH1-272 GEN
Solar/Wind Harmer
8.08
270286AF1-227 GEN2
Solar/Wind Harmer
2.523
971995AH1-542 GEN
Solar/Wind Harmer
11.763
270391AF1-285 GEN3
Solar/Wind Harmer
1.205
270578AF1-285 GEN2
Solar/Wind Harmer
1.205
270317AD1-130_GEN
Solar/Wind Harmer
2.98
270485AE1-090_GEN
Solar/Wind Harmer
0.563
270520AE2-214 GEN
Solar/Wind Harmer
5.371
241813AF1-122_GEN
Solar/Wind Harmer
4.152
971201AH1-060 GEN
Solar/Wind Harmer
1.298
962761AG1-125 GEN
Solar/Wind Harmer
20.836
970149AG2-104 GEN
Solar/Wind Harmer
12.866
970155AG2-107 GEN
Solar/Wind Harmer
9.086
246936BC-WTG1
Solar/Wind Harmer
2.344
270489AE1-102 GEN1
Solar/Wind Harmer
0.779
965421AG1-410 GEN
Solar/Wind Harmer
17.778
270297AD1-101 GEN
Solar/Wind Harmer
1.126
270258AD1-119 GEN
Solar/Wind Harmer
1.092
965011AG1-365 GEN
Solar/Wind Harmer
5.285
253333AC1-068 GEN
Solar/Wind Harmer
0.504
25326309TAIT D
Adder
0.525
270024AE2-089 GEN
Solar/Wind Harmer
2.191
965651AG1-433 GEN
Solar/Wind Harmer
2.527
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.278
958861AF2-177 GEN
Solar/Wind Harmer
5.017
945111AF1-176 GEN
Solar/Wind Harmer
8.127
957891AF2-083 GEN
Solar/Wind Harmer
6.816
945371AF1-202 GEN
Solar/Wind Harmer
3.157
270449AD2-020 GEN
Solar/Wind Harmer
1.268
943021AE2-325 GEN
Solar/Wind Harmer
1.648
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.197
270005AE1-210 C O1
Solar/Wind Harmer
2.388
970825AG2-519 GEN
Solar/Wind Harmer
0.916
274751CRETE EC ;1U
Adder
2.13
274754CRETE EC ;4U
Adder
2.13
972207SS24-0001
Solar/Wind Harmer
9.599
274773LINCOLN ;4U
Adder
2.7
274774LINCOLN ;5U
Adder
2.7
274724RIVER EC ;11
Adder
7.711
276164X3-005 C
Solar/Wind Harmer
0.305
274814UNIV PK N;0U
Adder
2.191
274807UNIV PK N;3U
Adder
2.186
274811UNIV PK N;7U
Adder
2.172
965461AG1-414 GEN
Solar/Wind Harmer
0.981
970289AG2-191 GEN
Solar/Wind Harmer
0.332
274803UNIV PARK;6U
Adder
2.518
247642Z2-115 C
Solar/Wind Harmer
0.028
274826FISK ;BP
Adder
4.726
972038AH1-567 GEN2
Adder
0.157
274887GEN-1.85
Solar/Wind Harmer
2.298
276772AC2-154 GEN
Solar/Wind Harmer
1.204
276843GEN-1.7
Solar/Wind Harmer
0.247
276806AD2-047 C O1
Solar/Wind Harmer
4.615
964401AG1-302 GEN
Solar/Wind Harmer
3.91
972259AH1-714 GEN
Adder
8.216
970707AG2-453 GEN
Solar/Wind Harmer
11.058
274775LINCOLN ;6U
Adder
2.7
274776LINCOLN ;7U
Adder
2.7
274777LINCOLN ;8U
Adder
2.7
970289AG2-191 GEN
Solar/Wind Harmer
0.822
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.349
274800UNIV PARK;3U
Adder
2.515
274801UNIV PARK;4U
Adder
2.515
960591AF2-350 GEN
Solar/Wind Harmer
4.314
972228AH1-698 GEN2
Adder
1.596
972227AH1-698 GEN1
Adder
1.124
274723RIVER EC ;12
Adder
7.802
270055AF2-134 C O1
Solar/Wind Harmer
1.314
274812UNIV PK N;8U
Adder
2.172
270594AE1-207 GEN
Solar/Wind Harmer
5.888
270032AE2-172
Solar/Wind Harmer
2.017
274802UNIV PARK;5U
Adder
2.518
958381AF2-132 GEN
Solar/Wind Harmer
3.91
270535AF1-215 GEN1
Solar/Wind Harmer
1.971
270536AF1-215 GEN2
Solar/Wind Harmer
1.971
274805UNIV PK N;1U
Adder
2.177
274808UNIV PK N;4U
Adder
2.163
970291AG2-192 GEN
Solar/Wind Harmer
0.562
970291AG2-192 GEN
Solar/Wind Harmer
0.181
270383AD1-128 GEN
Solar/Wind Harmer
2.637
274888KELLY CRK;1U
Solar/Wind Harmer
2.545
276776AD2-060 GEN
Solar/Wind Harmer
0.181
958011AF2-095 GEN
Solar/Wind Harmer
6.212
970941AG2-585 GEN
Solar/Wind Harmer
2.372
270054AF2-122 C O1
Solar/Wind Helper
0.82
LAGNLTFEXP_LAGN->PJM
CLTF
5.087
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.315
TVALTFEXP_TVA->PJM
CLTF
2.36
NYPJM->LTFIMP_NY
CLTF
1.309
LGEELTFEXP_LGEE->PJM
CLTF
2.284
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.165
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.515
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.624

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1484.58
MW Contribution:
8.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
7.753
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
942051AE2-217 GEN
Solar/Wind Harmer
13.86
970065AG2-057 GEN
Solar/Wind Harmer
0.646
276820AF1-078_GEN
Solar/Wind Harmer
1.059
962771AG1-126 GEN
Solar/Wind Harmer
20.746
970153AG2-106 GEN
Solar/Wind Harmer
9.046
246938BC-WTG3
Solar/Wind Harmer
2.375
270491AE1-102 GEN2
Solar/Wind Harmer
0.776
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.818
965021AG1-366 GEN
Solar/Wind Harmer
1.224
270044AE2-322 C
Solar/Wind Harmer
0.688
270518AE2-148 GEN
Solar/Wind Harmer
6.224
270588AE1-091_GEN
Solar/Wind Harmer
5.471
270043AE2-236 GEN
Solar/Wind Harmer
2.686
253325AC1-069 GEN
Solar/Wind Harmer
0.503
960071AF2-298 GEN
Solar/Wind Harmer
0.725
270063AE2-323 C
Solar/Wind Harmer
1.045
944531AF1-118 GEN
Solar/Wind Harmer
16.62
270541AE2-072 C
Solar/Wind Harmer
2.143
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
971347AH1-153 GEN
Solar/Wind Harmer
2.29
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.565
270505AE1-170 C O1
Solar/Wind Harmer
6.785
962031AG1-047 GEN
Solar/Wind Harmer
1.355
957741AF2-068 GEN
Solar/Wind Harmer
6.722
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.631
270004AE1-209 GEN
Solar/Wind Harmer
2.379
270036AE2-216 BAT
50/50
5.928
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.959
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.933
241974AD2-163_GEN2
Solar/Wind Harmer
1.933
270302AB2-170 GEN
Solar/Wind Harmer
7.76
970179AG2-119 GEN
Solar/Wind Harmer
6.743
241955AC1-078 GEN
Solar/Wind Harmer
4.963
957201AF2-014 GEN
Solar/Wind Harmer
2.707
270435AC2-044 GEN
Solar/Wind Harmer
1.194
241972AD1-140 GEN
Solar/Wind Harmer
2.551
270007AE1-245 C
Solar/Wind Harmer
3.03
247521TR3_G114
Solar/Wind Harmer
1.848
270191TR4_S_V150
Solar/Wind Harmer
1.649
965051AG1-369 GEN
Solar/Wind Harmer
2.745
965041AG1-368 GEN
Solar/Wind Harmer
5.334
945631AF1-228 GEN
Solar/Wind Harmer
2.5
959331AF2-224 GEN
Solar/Wind Harmer
5.263
270404AC1-167 GEN
Solar/Wind Harmer
0.567
963791AG1-232 GEN
Solar/Wind Harmer
6.667
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
253338AC1-165 GEN
Solar/Wind Harmer
0.521
253343AC1-166 GEN
Solar/Wind Harmer
0.521
970031AG2-029 GEN
Solar/Wind Harmer
11.974
270071AF1-092 GEN
Solar/Wind Harmer
7.157
24729505KEY G4
Adder
3.056
25306009OHH W.
Adder
1.331
958711AF2-162 GEN
Solar/Wind Harmer
0.466
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
971771AH1-392 GEN
Solar/Wind Harmer
4.076
945581AF1-223 GEN
Solar/Wind Harmer
2.044
944161AF1-084 GEN
Solar/Wind Harmer
0.992
270526AF1-158 GEN
Solar/Wind Harmer
2.036
961761AG1-017 GEN
Solar/Wind Harmer
0.192
964611AG1-324 GEN
Solar/Wind Harmer
1.739
247536S-71 GEN
Solar/Wind Harmer
1.803
960681AF2-359 GEN
Solar/Wind Harmer
1.683
270543AE2-219 C
Solar/Wind Harmer
4.428
971029AG2-637 GEN
Solar/Wind Harmer
6.602
971549AH1-272 GEN
Solar/Wind Harmer
8.047
274775LINCOLN ;6U
Adder
2.689
274776LINCOLN ;7U
Adder
2.689
274777LINCOLN ;8U
Adder
2.689
970289AG2-191 GEN
Solar/Wind Harmer
0.819
972037AH1-567 GEN1
Adder
0.079
970825AG2-519 GEN
Solar/Wind Harmer
2.451
972231SS25-0005
Solar/Wind Harmer
4.119
972181SS23-001
Solar/Wind Harmer
2.574
274752CRETE EC ;2U
Adder
2.121
274753CRETE EC ;3U
Adder
2.121
274772LINCOLN ;3U
Adder
2.689
274724RIVER EC ;11
Adder
7.679
276164X3-005 C
Solar/Wind Harmer
0.304
274814UNIV PK N;0U
Adder
2.182
274807UNIV PK N;3U
Adder
2.178
274811UNIV PK N;7U
Adder
2.163
965461AG1-414 GEN
Solar/Wind Harmer
0.977
970289AG2-191 GEN
Solar/Wind Harmer
0.331
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.508
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
971995AH1-542 GEN
Solar/Wind Harmer
11.711
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270317AD1-130_GEN
Solar/Wind Harmer
2.967
270485AE1-090_GEN
Solar/Wind Harmer
0.56
270520AE2-214 GEN
Solar/Wind Harmer
5.342
241813AF1-122_GEN
Solar/Wind Harmer
4.135
971201AH1-060 GEN
Solar/Wind Harmer
1.292
962761AG1-125 GEN
Solar/Wind Harmer
20.746
970149AG2-104 GEN
Solar/Wind Harmer
12.811
970155AG2-107 GEN
Solar/Wind Harmer
9.046
246936BC-WTG1
Solar/Wind Harmer
2.335
270489AE1-102 GEN1
Solar/Wind Harmer
0.776
965421AG1-410 GEN
Solar/Wind Harmer
17.703
270297AD1-101 GEN
Solar/Wind Harmer
1.121
270258AD1-119 GEN
Solar/Wind Harmer
1.088
965011AG1-365 GEN
Solar/Wind Harmer
5.263
253333AC1-068 GEN
Solar/Wind Harmer
0.503
25326309TAIT D
Adder
0.523
270024AE2-089 GEN
Solar/Wind Harmer
2.182
965651AG1-433 GEN
Solar/Wind Harmer
2.517
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.277
958861AF2-177 GEN
Solar/Wind Harmer
4.997
945111AF1-176 GEN
Solar/Wind Harmer
8.094
957891AF2-083 GEN
Solar/Wind Harmer
6.788
945371AF1-202 GEN
Solar/Wind Harmer
3.144
270449AD2-020 GEN
Solar/Wind Harmer
1.263
943021AE2-325 GEN
Solar/Wind Harmer
1.641
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.16
270005AE1-210 C O1
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
0.913
274751CRETE EC ;1U
Adder
2.121
274754CRETE EC ;4U
Adder
2.121
972207SS24-0001
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
2.689
274774LINCOLN ;5U
Adder
2.689
274723RIVER EC ;12
Adder
7.77
270055AF2-134 C O1
Solar/Wind Harmer
1.309
274812UNIV PK N;8U
Adder
2.163
270594AE1-207 GEN
Solar/Wind Harmer
5.865
270032AE2-172
Solar/Wind Harmer
2.008
274802UNIV PARK;5U
Adder
2.508
270466AD2-091
50/50
5.389
270349AD2-093_GEN
Solar/Wind Harmer
4.839
270471AD2-092_GEN
Solar/Wind Harmer
4.839
938701AE1-092 GEN
Solar/Wind Harmer
21.815
270462AD2-086
Solar/Wind Harmer
6.445
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.339
253378AE2-206_GEN
Solar/Wind Harmer
2.385
25326509SID D
Adder
0.833
246937BC-WTG2
Solar/Wind Harmer
2.335
942801AE2-298 GEN
Solar/Wind Harmer
0.854
247607V1-011 GEN
Solar/Wind Harmer
2.218
270246TR4_N_V150
Solar/Wind Harmer
0.468
270247TR4_N_V136
Solar/Wind Harmer
0.468
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.649
944231AF1-091 GEN
Solar/Wind Harmer
8.735
25322209TAIT E
Adder
4.65
25322209TAIT E
Adder
4.546
942221AE2-234 GEN
Solar/Wind Harmer
1.641
253349AC2-067 GEN
Solar/Wind Harmer
0.953
253400AC2-068 GEN
Solar/Wind Harmer
0.383
247620Y3-023
Adder
0.213
944541AF1-119 GEN
Solar/Wind Harmer
1.928
960971AF2-388 GEN
Solar/Wind Harmer
5.034
253370AE2-315 SEC1
Adder
0.922
970349AG2-230 GEN
Solar/Wind Harmer
6.869
961051AF2-396 GEN
Solar/Wind Harmer
7.17
961051AF2-396 GEN
Solar/Wind Harmer
3.335
247621Y3-024
Adder
0.108
270201AC2-176 GEN
Solar/Wind Harmer
2.303
964611AG1-324 GEN
Solar/Wind Harmer
0.233
965681AG1-436 GEN
Solar/Wind Harmer
5.567
965791AG1-447 GEN
Solar/Wind Harmer
2.848
270031AE2-169
Solar/Wind Harmer
3.621
270599AE1-208 GEN
Solar/Wind Harmer
3.621
970883AG2-550 GEN
Solar/Wind Harmer
4.428
970885AG2-551 GEN
Solar/Wind Harmer
1.03
253383AE2-342_GEN
Solar/Wind Harmer
0.387
274770LINCOLN ;1U
Adder
2.689
274771LINCOLN ;2U
Adder
2.689
270535AF1-215 GEN1
Solar/Wind Harmer
1.963
270536AF1-215 GEN2
Solar/Wind Harmer
1.963
274805UNIV PK N;1U
Adder
2.168
274808UNIV PK N;4U
Adder
2.154
970291AG2-192 GEN
Solar/Wind Harmer
0.56
970291AG2-192 GEN
Solar/Wind Harmer
0.18
270383AD1-128 GEN
Solar/Wind Harmer
2.627
270054AF2-122 C O1
Solar/Wind Helper
0.81
LAGNLTFEXP_LAGN->PJM
CLTF
5.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.308
TVALTFEXP_TVA->PJM
CLTF
2.351
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.276
WECLTFEXP_WEC->PJM
CLTF
1.577
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.149
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.48
MECLTFEXP_MEC->PJM
CLTF
6.274
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.337
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.469

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.35 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1484.33
MW Contribution:
8.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
7.753
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
942051AE2-217 GEN
Solar/Wind Harmer
13.86
970065AG2-057 GEN
Solar/Wind Harmer
0.646
276820AF1-078_GEN
Solar/Wind Harmer
1.059
962771AG1-126 GEN
Solar/Wind Harmer
20.746
970153AG2-106 GEN
Solar/Wind Harmer
9.046
246938BC-WTG3
Solar/Wind Harmer
2.375
270491AE1-102 GEN2
Solar/Wind Harmer
0.776
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.818
965021AG1-366 GEN
Solar/Wind Harmer
1.224
270044AE2-322 C
Solar/Wind Harmer
0.688
270518AE2-148 GEN
Solar/Wind Harmer
6.224
270588AE1-091_GEN
Solar/Wind Harmer
5.471
270043AE2-236 GEN
Solar/Wind Harmer
2.686
253325AC1-069 GEN
Solar/Wind Harmer
0.503
960071AF2-298 GEN
Solar/Wind Harmer
0.725
270063AE2-323 C
Solar/Wind Harmer
1.045
944531AF1-118 GEN
Solar/Wind Harmer
16.62
270541AE2-072 C
Solar/Wind Harmer
2.143
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
971347AH1-153 GEN
Solar/Wind Harmer
2.29
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.565
270505AE1-170 C O1
Solar/Wind Harmer
6.785
962031AG1-047 GEN
Solar/Wind Harmer
1.355
270036AE2-216 BAT
50/50
5.928
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.959
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.933
241974AD2-163_GEN2
Solar/Wind Harmer
1.933
270302AB2-170 GEN
Solar/Wind Harmer
7.76
970179AG2-119 GEN
Solar/Wind Harmer
6.743
241955AC1-078 GEN
Solar/Wind Harmer
4.963
957201AF2-014 GEN
Solar/Wind Harmer
2.707
270435AC2-044 GEN
Solar/Wind Harmer
1.194
241972AD1-140 GEN
Solar/Wind Harmer
2.551
270007AE1-245 C
Solar/Wind Harmer
3.03
247521TR3_G114
Solar/Wind Harmer
1.848
270191TR4_S_V150
Solar/Wind Harmer
1.649
965051AG1-369 GEN
Solar/Wind Harmer
2.745
965041AG1-368 GEN
Solar/Wind Harmer
5.334
945631AF1-228 GEN
Solar/Wind Harmer
2.5
959331AF2-224 GEN
Solar/Wind Harmer
5.263
270404AC1-167 GEN
Solar/Wind Harmer
0.567
963791AG1-232 GEN
Solar/Wind Harmer
6.667
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
253338AC1-165 GEN
Solar/Wind Harmer
0.521
253343AC1-166 GEN
Solar/Wind Harmer
0.521
970031AG2-029 GEN
Solar/Wind Harmer
11.974
270071AF1-092 GEN
Solar/Wind Harmer
7.157
24729505KEY G4
Adder
3.056
25306009OHH W.
Adder
1.331
958711AF2-162 GEN
Solar/Wind Harmer
0.466
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
971771AH1-392 GEN
Solar/Wind Harmer
4.076
945581AF1-223 GEN
Solar/Wind Harmer
2.044
944161AF1-084 GEN
Solar/Wind Harmer
0.992
270526AF1-158 GEN
Solar/Wind Harmer
2.036
270466AD2-091
50/50
5.389
270349AD2-093_GEN
Solar/Wind Harmer
4.839
270471AD2-092_GEN
Solar/Wind Harmer
4.839
938701AE1-092 GEN
Solar/Wind Harmer
21.815
270462AD2-086
Solar/Wind Harmer
6.445
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.339
253378AE2-206_GEN
Solar/Wind Harmer
2.385
25326509SID D
Adder
0.833
246937BC-WTG2
Solar/Wind Harmer
2.335
942801AE2-298 GEN
Solar/Wind Harmer
0.854
247607V1-011 GEN
Solar/Wind Harmer
2.218
270246TR4_N_V150
Solar/Wind Harmer
0.468
270247TR4_N_V136
Solar/Wind Harmer
0.468
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.649
944231AF1-091 GEN
Solar/Wind Harmer
8.735
25322209TAIT E
Adder
4.65
25322209TAIT E
Adder
4.546
942221AE2-234 GEN
Solar/Wind Harmer
1.641
253349AC2-067 GEN
Solar/Wind Harmer
0.953
253400AC2-068 GEN
Solar/Wind Harmer
0.383
247620Y3-023
Adder
0.213
944541AF1-119 GEN
Solar/Wind Harmer
1.928
960971AF2-388 GEN
Solar/Wind Harmer
5.034
253370AE2-315 SEC1
Adder
0.922
970349AG2-230 GEN
Solar/Wind Harmer
6.869
961051AF2-396 GEN
Solar/Wind Harmer
7.17
961051AF2-396 GEN
Solar/Wind Harmer
3.335
247621Y3-024
Adder
0.108
270201AC2-176 GEN
Solar/Wind Harmer
2.303
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
971995AH1-542 GEN
Solar/Wind Harmer
11.711
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270317AD1-130_GEN
Solar/Wind Harmer
2.967
270485AE1-090_GEN
Solar/Wind Harmer
0.56
270520AE2-214 GEN
Solar/Wind Harmer
5.342
241813AF1-122_GEN
Solar/Wind Harmer
4.135
971201AH1-060 GEN
Solar/Wind Harmer
1.292
962761AG1-125 GEN
Solar/Wind Harmer
20.746
970149AG2-104 GEN
Solar/Wind Harmer
12.811
970155AG2-107 GEN
Solar/Wind Harmer
9.046
246936BC-WTG1
Solar/Wind Harmer
2.335
270489AE1-102 GEN1
Solar/Wind Harmer
0.776
965421AG1-410 GEN
Solar/Wind Harmer
17.703
270297AD1-101 GEN
Solar/Wind Harmer
1.121
270258AD1-119 GEN
Solar/Wind Harmer
1.088
965011AG1-365 GEN
Solar/Wind Harmer
5.263
253333AC1-068 GEN
Solar/Wind Harmer
0.503
25326309TAIT D
Adder
0.523
270024AE2-089 GEN
Solar/Wind Harmer
2.182
965651AG1-433 GEN
Solar/Wind Harmer
2.517
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.277
958861AF2-177 GEN
Solar/Wind Harmer
4.997
945111AF1-176 GEN
Solar/Wind Harmer
8.094
957891AF2-083 GEN
Solar/Wind Harmer
6.788
945371AF1-202 GEN
Solar/Wind Harmer
3.144
270449AD2-020 GEN
Solar/Wind Harmer
1.263
943021AE2-325 GEN
Solar/Wind Harmer
1.641
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.16
270005AE1-210 C O1
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
0.913
274751CRETE EC ;1U
Adder
2.121
274754CRETE EC ;4U
Adder
2.121
972207SS24-0001
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
2.689
274774LINCOLN ;5U
Adder
2.689
274723RIVER EC ;12
Adder
7.77
270055AF2-134 C O1
Solar/Wind Harmer
1.309
274812UNIV PK N;8U
Adder
2.163
270594AE1-207 GEN
Solar/Wind Harmer
5.865
270032AE2-172
Solar/Wind Harmer
2.008
274802UNIV PARK;5U
Adder
2.508
957741AF2-068 GEN
Solar/Wind Harmer
6.722
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.631
270004AE1-209 GEN
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
2.451
972231SS25-0005
Solar/Wind Harmer
4.119
972181SS23-001
Solar/Wind Harmer
2.574
274752CRETE EC ;2U
Adder
2.121
274753CRETE EC ;3U
Adder
2.121
274772LINCOLN ;3U
Adder
2.689
274724RIVER EC ;11
Adder
7.679
276164X3-005 C
Solar/Wind Harmer
0.304
274814UNIV PK N;0U
Adder
2.182
274807UNIV PK N;3U
Adder
2.178
274811UNIV PK N;7U
Adder
2.163
965461AG1-414 GEN
Solar/Wind Harmer
0.977
970289AG2-191 GEN
Solar/Wind Harmer
0.331
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.508
964611AG1-324 GEN
Solar/Wind Harmer
0.233
965681AG1-436 GEN
Solar/Wind Harmer
5.567
965791AG1-447 GEN
Solar/Wind Harmer
2.848
270031AE2-169
Solar/Wind Harmer
3.621
270599AE1-208 GEN
Solar/Wind Harmer
3.621
970883AG2-550 GEN
Solar/Wind Harmer
4.428
970885AG2-551 GEN
Solar/Wind Harmer
1.03
253383AE2-342_GEN
Solar/Wind Harmer
0.387
274770LINCOLN ;1U
Adder
2.689
274771LINCOLN ;2U
Adder
2.689
270535AF1-215 GEN1
Solar/Wind Harmer
1.963
270536AF1-215 GEN2
Solar/Wind Harmer
1.963
274805UNIV PK N;1U
Adder
2.168
274808UNIV PK N;4U
Adder
2.154
970291AG2-192 GEN
Solar/Wind Harmer
0.56
970291AG2-192 GEN
Solar/Wind Harmer
0.18
270383AD1-128 GEN
Solar/Wind Harmer
2.627
270054AF2-122 C O1
Solar/Wind Helper
0.81
961761AG1-017 GEN
Solar/Wind Harmer
0.192
964611AG1-324 GEN
Solar/Wind Harmer
1.739
247536S-71 GEN
Solar/Wind Harmer
1.803
960681AF2-359 GEN
Solar/Wind Harmer
1.683
270543AE2-219 C
Solar/Wind Harmer
4.428
971029AG2-637 GEN
Solar/Wind Harmer
6.602
971549AH1-272 GEN
Solar/Wind Harmer
8.047
274775LINCOLN ;6U
Adder
2.689
274776LINCOLN ;7U
Adder
2.689
274777LINCOLN ;8U
Adder
2.689
970289AG2-191 GEN
Solar/Wind Harmer
0.819
972037AH1-567 GEN1
Adder
0.079
LAGNLTFEXP_LAGN->PJM
CLTF
5.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.308
TVALTFEXP_TVA->PJM
CLTF
2.351
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.276
WECLTFEXP_WEC->PJM
CLTF
1.577
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.149
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.48
MECLTFEXP_MEC->PJM
CLTF
6.274
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.337
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.469

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.58 %
Rating:3039.0 MVA
Rating Type:B
MVA to Mitigate:3208.68
MW Contribution:
10.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344305RKG2
50/50
11.018
270406AB1-088 CT1
50/50
2.513
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.082
24386205FR-12G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970193AG2-126 GEN
Solar/Wind Harmer
9.249
971347AH1-153 GEN
Solar/Wind Harmer
3.046
274772LINCOLN ;3U
Adder
7.265
274752CRETE EC ;2U
Adder
7.074
274753CRETE EC ;3U
Adder
7.074
274724RIVER EC ;11
Adder
15.124
274814UNIV PK N;0U
Adder
4.311
274807UNIV PK N;3U
Adder
4.302
274811UNIV PK N;7U
Adder
4.274
970091AG2-072 GEN
50/50
218.725
270407AB1-088 ST1
50/50
2.513
970023AG2-014 GEN
50/50
2.694
970783AG2-492 GEN
50/50
2.694
24344105CKG2
50/50
6.799
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.786
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.763
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939351AE1-166 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
0.154
276843GEN-1.7
Solar/Wind Harmer
0.191
276806AD2-047 C O1
Solar/Wind Harmer
3.355
274803UNIV PARK;6U
Adder
4.947
972038AH1-567 GEN2
Adder
0.309
972259AH1-714 GEN
Adder
16.155
274826FISK ;BP
Adder
9.27
970707AG2-453 GEN
Solar/Wind Harmer
19.288
274729ELWOOD EC;1P
Adder
13.819
274730ELWOOD EC;6P
Adder
13.819
274734ELWOOD EC;8P
Adder
13.819
274736ELWOOD EC;9P
Adder
13.819
274676JOLIET 29;8U
Adder
24.844
943121AE2-341 GEN
Solar/Wind Harmer
9.707
943591AF1-030 GEN
Solar/Wind Harmer
6.455
274862TOP CROP ;2U
Solar/Wind Harmer
0.78
965091AG1-374 GEN
Solar/Wind Harmer
17.188
959611AF2-252 GEN
Solar/Wind Harmer
1.91
276868AE1-113 GEN
Solar/Wind Harmer
1.141
274879MINONK ;1U
Solar/Wind Harmer
0.238
274682WAUKEGAN ;7U
Adder
14.697
971993AH1-541 GEN
Solar/Wind Harmer
2.606
970571AG2-364 GEN
Solar/Wind Harmer
11.227
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.065
270505AE1-170 C O1
Solar/Wind Harmer
5.856
959091AF2-200 GEN
Solar/Wind Harmer
11.115
945111AF1-176 GEN
Solar/Wind Harmer
4.457
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
957381AF2-032 GEN
Solar/Wind Harmer
1.241
942481AE2-261 GEN
Solar/Wind Harmer
16.362
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
7.252
274767LEE CO EC;8U
Adder
7.166
965931AG1-462 GEN
Solar/Wind Harmer
13.235
971087AG2-675 GEN
Solar/Wind Harmer
2.768
270063AE2-323 C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.002
270043AE2-236 GEN
Solar/Wind Harmer
2.578
970289AG2-191 GEN
Solar/Wind Harmer
0.419
965021AG1-366 GEN
Solar/Wind Harmer
1.022
252507AC2-088 GEN
Solar/Wind Helper
1.471
252524AE2-267 GEN
Solar/Wind Helper
0.466
339243AC2-075 GEN1
Solar/Wind Helper
0.336
270186AC1-089 GEN
Solar/Wind Helper
0.822
270367AC2-061_GEN
Solar/Wind Helper
1.691
253394AE2-221_GEN
Solar/Wind Helper
1.24
339206AE1-143 GEN
Solar/Wind Helper
1.206
960071AF2-298 GEN
Solar/Wind Helper
0.355
339255AE2-071 GEN
Solar/Wind Helper
0.153
339250AF1-203 GEN
Solar/Wind Helper
0.118
270518AE2-148 GEN
Solar/Wind Helper
5.631
253325AC1-069 GEN
Solar/Wind Helper
0.484
24344205RKG1
50/50
11.252
24344205RKG1
50/50
11.252
24344305RKG2
50/50
11.213
270393AB1-087 CT1
50/50
2.513
270394AB1-087 ST1
50/50
2.513
970539AG2-343 GEN
50/50
9.396
970543AG2-345 GEN
50/50
4.698
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.661
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.267
960681AF2-359 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.265
274776LINCOLN ;7U
Adder
7.265
274777LINCOLN ;8U
Adder
7.265
270526AF1-158 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.144
972227AH1-698 GEN1
Adder
2.214
960591AF2-350 GEN
Solar/Wind Harmer
5.921
972037AH1-567 GEN1
Adder
0.155
274800UNIV PARK;3U
Adder
4.938
274801UNIV PARK;4U
Adder
4.938
274827FISK ;RP
Adder
6.57
274687WILL CNTY;4U
Adder
23.495
274687WILL CNTY;4U
Adder
23.495
274731ELWOOD EC;2P
Adder
13.819
274733ELWOOD EC;3P
Adder
13.819
274735ELWOOD EC;4P
Adder
13.819
274728ELWOOD EC;5P
Adder
13.819
970833AG2-524 GEN
Solar/Wind Harmer
6.449
970833AG2-524 GEN
Solar/Wind Harmer
4.299
274675JOLIET 29;7U
Adder
25.765
274675JOLIET 29;7U
Adder
24.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
5.808
274744AC1-111 GEN8
Adder
4.638
274746AC1-111 G10
Adder
4.638
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.06
971771AH1-392 GEN
Solar/Wind Harmer
5.748
274854TWINGROVE;U2
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.91
276668AB2-070 GEN1
Solar/Wind Harmer
0.222
276848AB2-070 GEN3
Solar/Wind Harmer
0.221
276849AB2-070 GEN2
Solar/Wind Harmer
0.222
926823AC1-168 GEN
Solar/Wind Harmer
0.958
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.182
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276863AD2-134 GEN
Solar/Wind Harmer
0.1
971411AH1-196 GEN
Solar/Wind Harmer
8.382
971171AH1-044 GEN
Solar/Wind Harmer
11.115
274823ROCKFORD ;21
Adder
15.441
274856ECOGROVE ;U1
Solar/Wind Harmer
0.128
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971681AH1-341 GEN
Solar/Wind Harmer
8.802
944221AF1-090 GEN
Solar/Wind Harmer
3.186
276741O09 GEN1
Solar/Wind Harmer
0.191
972267AH1-718 GEN
Adder
3.215
946321AF1-296 GEN
Solar/Wind Harmer
2.925
971549AH1-272 GEN
Solar/Wind Harmer
10.203
270071AF1-092 GEN
Solar/Wind Harmer
8.932
970031AG2-029 GEN
Solar/Wind Harmer
2.434
970289AG2-191 GEN
Solar/Wind Harmer
0.724
959331AF2-224 GEN
Solar/Wind Harmer
2.147
339216AC1-074 GEN
Solar/Wind Helper
1.461
253406AD2-031_GEN
Solar/Wind Helper
0.712
270340AC2-060 GEN
Solar/Wind Helper
1.095
241972AD1-140 GEN
Solar/Wind Helper
2.071
253338AC1-165 GEN
Solar/Wind Helper
0.467
253343AC1-166 GEN
Solar/Wind Helper
0.467
270055AF2-134 C O1
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
17.105
970373AG2-245 GEN
Solar/Wind Harmer
14.697
274773LINCOLN ;4U
Adder
7.265
274774LINCOLN ;5U
Adder
7.265
274751CRETE EC ;1U
Adder
7.074
274754CRETE EC ;4U
Adder
7.074
274723RIVER EC ;12
Adder
15.309
274812UNIV PK N;8U
Adder
4.274
941551AE2-152 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
4.947
939401AE1-172 GEN
Solar/Wind Harmer
4.39
274732ELWOOD EC;7P
Adder
13.819
274674JOLIET 9 ;6U
Adder
12.932
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
25.765
274745AC1-111 GEN9
Adder
4.638
276694AA1-018 GEN2
Solar/Wind Harmer
0
942601AE2-276 GEN
50/50
8.364
270102X2-052 ST
50/50
1.428
270100X2-052 CT1
50/50
1.319
270101X2-052 CT2
50/50
1.319
971587AH1-292 GEN
Solar/Wind Harmer
7.361
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.892
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.216
965681AG1-436 GEN
Solar/Wind Harmer
7.77
276691AA1-018 GEN1
Solar/Wind Harmer
0.939
274861TOP CROP ;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.081
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3
276882AE2-255 GEN
Solar/Wind Harmer
0.666
274682WAUKEGAN ;7U
Adder
14.697
274828WAUKEGAN ;BP
Adder
9.02
962781AG1-127 GEN
Solar/Wind Harmer
5.386
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
16.84
276621W2-048 GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
9.279
957471AF2-041 GEN
Solar/Wind Harmer
16.672
959081AF2-199 GEN
Solar/Wind Harmer
5.557
971067AG2-660 GEN
Solar/Wind Harmer
1.852
274822ROCKFORD ;11
Adder
15.554
276646AC1-214 GEN2
Solar/Wind Harmer
0.217
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.884
945111AF1-176 GEN
Solar/Wind Harmer
9.811
970819AG2-516 GEN
Solar/Wind Harmer
6.595
274848CAMPGROVE;RU
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.094
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.252
274766LEE CO EC;7U
Adder
7.166
276708O09 GEN2
Solar/Wind Harmer
0.191
24639705ELKHART HY
Adder
0.118
965011AG1-365 GEN
Solar/Wind Harmer
3.067
270594AE1-207 GEN
Solar/Wind Harmer
3.372
270032AE2-172
Solar/Wind Harmer
2.007
252510AF1-249 C
Solar/Wind Helper
0.376
339221AD2-048_GEN
Solar/Wind Helper
1.206
943111AE2-339 GEN
Solar/Wind Helper
0.641
339211AE2-254 GEN
Solar/Wind Helper
0.448
253398AE2-221_GEN2
Solar/Wind Helper
1.24
339241AF1-083 GEN
Solar/Wind Helper
0.404
253333AC1-068 GEN
Solar/Wind Helper
0.484
965791AG1-447 GEN
Solar/Wind Harmer
5.698
945391AF1-204 GEN
Solar/Wind Harmer
6.551
970349AG2-230 GEN
Solar/Wind Harmer
9.139
274770LINCOLN ;1U
Adder
7.265
274771LINCOLN ;2U
Adder
7.265
274805UNIV PK N;1U
Adder
4.283
274808UNIV PK N;4U
Adder
4.255
276897AD1-100 C
Solar/Wind Harmer
14.818
274888KELLY CRK;1U
Solar/Wind Harmer
0.345
276776AD2-060 GEN
Solar/Wind Harmer
0.632
958011AF2-095 GEN
Solar/Wind Harmer
8.526
970941AG2-585 GEN
Solar/Wind Harmer
3.257
276893AG1-478 C
Solar/Wind Harmer
0.391
274674JOLIET 9 ;6U
Adder
12.932
958481AF2-142 GEN
Solar/Wind Harmer
8.668
942111AE2-223 GEN
Solar/Wind Harmer
1.876
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
8.594
960611AF2-352 GEN
Solar/Wind Harmer
1.91
274695ROCKY RD ;2P
Adder
9.123
274693ROCKY RD ;1P
Adder
9.033
274697ROCKY RD ;3P
Adder
2.478
274696ROCKY RD ;4P
Adder
9.338
274683WAUKEGAN ;8U
Adder
17.208
274683WAUKEGAN ;8U
Adder
14.506
962691AG1-118 GEN
Solar/Wind Harmer
17.022
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.058
276838X2-022 GEN2
Solar/Wind Harmer
0.314
971341AH1-150 GEN
Solar/Wind Harmer
11.115
971343AH1-151 GEN
Solar/Wind Harmer
11.115
276645AC1-214 GEN1
Solar/Wind Harmer
0.217
972235AH1-702 GEN1
Adder
1.993
972236AH1-702 GEN2
Adder
1.733
961051AF2-396 GEN
Solar/Wind Harmer
11.03
961051AF2-396 GEN
Solar/Wind Harmer
7.353
276916AD2-100_GEN
Solar/Wind Harmer
11.472
276911AD2-131_GEN
Solar/Wind Harmer
0.756
938861AE1-114 GEN
Solar/Wind Harmer
3.095
274764LEE CO EC;5U
Adder
7.269
274765LEE CO EC;6U
Adder
7.269
274762LEE CO EC;3U
Adder
7.252
274763LEE CO EC;4U
Adder
7.183
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.873
247620Y3-023
Adder
0.342
970291AG2-192 GEN
Solar/Wind Harmer
0.495
970291AG2-192 GEN
Solar/Wind Harmer
0.229
944231AF1-091 GEN
Solar/Wind Harmer
7.025
971613AH1-306 GEN
Solar/Wind Harmer
1.445
252509AD1-136 GEN
Solar/Wind Helper
0.21
25183208HLCRTG
Solar/Wind Helper
2.03
962581AG1-107 GEN
Solar/Wind Helper
0.905
961491AF2-440 GEN
Solar/Wind Helper
0.037
253349AC2-067 GEN
Solar/Wind Helper
0.213
253400AC2-068 GEN
Solar/Wind Helper
0.086
339236AF1-050_GEN
Solar/Wind Helper
0.404
253415AE1-040 GEN
Solar/Wind Helper
0.484
339231AF1-038_GEN
Solar/Wind Helper
0.394
950011AG9-010
External Queue
6.200752258300781
991082J1475 G
External Queue
6.164829730987549
950051AG9-018
External Queue
4.865413665771484
955142J992
External Queue
11.419598579406738
990742J1381
External Queue
17.560279846191406
991312J1772
External Queue
12.36315631866455
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.962
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.555
LAGNLTFEXP_LAGN->PJM
CLTF
2.301
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
1.033
WECLTFEXP_WEC->PJM
CLTF
3.003
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.212
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.737
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.546
MECLTFEXP_MEC->PJM
CLTF
10.638
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.591
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.16 %
Rating:2826.0 MVA
Rating Type:B
MVA to Mitigate:3197.84
MW Contribution:
10.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344305RKG2
50/50
11.018
270406AB1-088 CT1
50/50
2.513
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.082
24386205FR-12G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970193AG2-126 GEN
Solar/Wind Harmer
9.249
971347AH1-153 GEN
Solar/Wind Harmer
3.046
274772LINCOLN ;3U
Adder
7.265
274752CRETE EC ;2U
Adder
7.074
274753CRETE EC ;3U
Adder
7.074
274724RIVER EC ;11
Adder
15.124
274814UNIV PK N;0U
Adder
4.311
274807UNIV PK N;3U
Adder
4.302
274811UNIV PK N;7U
Adder
4.274
939351AE1-166 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
0.154
276843GEN-1.7
Solar/Wind Harmer
0.191
276806AD2-047 C O1
Solar/Wind Harmer
3.355
274803UNIV PARK;6U
Adder
4.947
972038AH1-567 GEN2
Adder
0.309
972259AH1-714 GEN
Adder
16.155
274826FISK ;BP
Adder
9.27
970707AG2-453 GEN
Solar/Wind Harmer
19.288
274729ELWOOD EC;1P
Adder
13.819
274730ELWOOD EC;6P
Adder
13.819
274734ELWOOD EC;8P
Adder
13.819
274736ELWOOD EC;9P
Adder
13.819
274676JOLIET 29;8U
Adder
24.844
943121AE2-341 GEN
Solar/Wind Harmer
9.707
943591AF1-030 GEN
Solar/Wind Harmer
6.455
274862TOP CROP ;2U
Solar/Wind Harmer
0.78
965091AG1-374 GEN
Solar/Wind Harmer
17.188
959611AF2-252 GEN
Solar/Wind Harmer
1.91
276868AE1-113 GEN
Solar/Wind Harmer
1.141
274879MINONK ;1U
Solar/Wind Harmer
0.238
274682WAUKEGAN ;7U
Adder
14.697
971993AH1-541 GEN
Solar/Wind Harmer
2.606
970571AG2-364 GEN
Solar/Wind Harmer
11.227
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.065
270505AE1-170 C O1
Solar/Wind Harmer
5.856
959091AF2-200 GEN
Solar/Wind Harmer
11.115
945111AF1-176 GEN
Solar/Wind Harmer
4.457
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
957381AF2-032 GEN
Solar/Wind Harmer
1.241
942481AE2-261 GEN
Solar/Wind Harmer
16.362
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
7.252
274767LEE CO EC;8U
Adder
7.166
965931AG1-462 GEN
Solar/Wind Harmer
13.235
971087AG2-675 GEN
Solar/Wind Harmer
2.768
270063AE2-323 C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.002
270043AE2-236 GEN
Solar/Wind Harmer
2.578
970289AG2-191 GEN
Solar/Wind Harmer
0.419
965021AG1-366 GEN
Solar/Wind Harmer
1.022
252507AC2-088 GEN
Solar/Wind Helper
1.471
252524AE2-267 GEN
Solar/Wind Helper
0.466
339243AC2-075 GEN1
Solar/Wind Helper
0.336
270186AC1-089 GEN
Solar/Wind Helper
0.822
270367AC2-061_GEN
Solar/Wind Helper
1.691
253394AE2-221_GEN
Solar/Wind Helper
1.24
339206AE1-143 GEN
Solar/Wind Helper
1.206
960071AF2-298 GEN
Solar/Wind Helper
0.355
339255AE2-071 GEN
Solar/Wind Helper
0.153
339250AF1-203 GEN
Solar/Wind Helper
0.118
270518AE2-148 GEN
Solar/Wind Helper
5.631
253325AC1-069 GEN
Solar/Wind Helper
0.484
970091AG2-072 GEN
50/50
218.725
270407AB1-088 ST1
50/50
2.513
970023AG2-014 GEN
50/50
2.694
970783AG2-492 GEN
50/50
2.694
24344105CKG2
50/50
6.799
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.786
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.763
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
17.105
970373AG2-245 GEN
Solar/Wind Harmer
14.697
274773LINCOLN ;4U
Adder
7.265
274774LINCOLN ;5U
Adder
7.265
274751CRETE EC ;1U
Adder
7.074
274754CRETE EC ;4U
Adder
7.074
274723RIVER EC ;12
Adder
15.309
274812UNIV PK N;8U
Adder
4.274
941551AE2-152 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
4.947
939401AE1-172 GEN
Solar/Wind Harmer
4.39
274732ELWOOD EC;7P
Adder
13.819
274674JOLIET 9 ;6U
Adder
12.932
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
25.765
274745AC1-111 GEN9
Adder
4.638
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.939
274861TOP CROP ;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.081
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3
276882AE2-255 GEN
Solar/Wind Harmer
0.666
274682WAUKEGAN ;7U
Adder
14.697
274828WAUKEGAN ;BP
Adder
9.02
962781AG1-127 GEN
Solar/Wind Harmer
5.386
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
16.84
276621W2-048 GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
9.279
957471AF2-041 GEN
Solar/Wind Harmer
16.672
959081AF2-199 GEN
Solar/Wind Harmer
5.557
971067AG2-660 GEN
Solar/Wind Harmer
1.852
274822ROCKFORD ;11
Adder
15.554
276646AC1-214 GEN2
Solar/Wind Harmer
0.217
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.884
945111AF1-176 GEN
Solar/Wind Harmer
9.811
970819AG2-516 GEN
Solar/Wind Harmer
6.595
274848CAMPGROVE;RU
Solar/Wind Harmer
0
942601AE2-276 GEN
50/50
8.364
270102X2-052 ST
50/50
1.428
270100X2-052 CT1
50/50
1.319
270101X2-052 CT2
50/50
1.319
971587AH1-292 GEN
Solar/Wind Harmer
7.361
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.892
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.216
965681AG1-436 GEN
Solar/Wind Harmer
7.77
965791AG1-447 GEN
Solar/Wind Harmer
5.698
945391AF1-204 GEN
Solar/Wind Harmer
6.551
970349AG2-230 GEN
Solar/Wind Harmer
9.139
274770LINCOLN ;1U
Adder
7.265
274771LINCOLN ;2U
Adder
7.265
274805UNIV PK N;1U
Adder
4.283
274808UNIV PK N;4U
Adder
4.255
276897AD1-100 C
Solar/Wind Harmer
14.818
274888KELLY CRK;1U
Solar/Wind Harmer
0.345
276776AD2-060 GEN
Solar/Wind Harmer
0.632
958011AF2-095 GEN
Solar/Wind Harmer
8.526
970941AG2-585 GEN
Solar/Wind Harmer
3.257
276893AG1-478 C
Solar/Wind Harmer
0.391
274674JOLIET 9 ;6U
Adder
12.932
958481AF2-142 GEN
Solar/Wind Harmer
8.668
942111AE2-223 GEN
Solar/Wind Harmer
1.876
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
8.594
960611AF2-352 GEN
Solar/Wind Harmer
1.91
274695ROCKY RD ;2P
Adder
9.123
274693ROCKY RD ;1P
Adder
9.033
274697ROCKY RD ;3P
Adder
2.478
274696ROCKY RD ;4P
Adder
9.338
274683WAUKEGAN ;8U
Adder
17.208
274683WAUKEGAN ;8U
Adder
14.506
962691AG1-118 GEN
Solar/Wind Harmer
17.022
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.058
276838X2-022 GEN2
Solar/Wind Harmer
0.314
971341AH1-150 GEN
Solar/Wind Harmer
11.115
971343AH1-151 GEN
Solar/Wind Harmer
11.115
276645AC1-214 GEN1
Solar/Wind Harmer
0.217
972235AH1-702 GEN1
Adder
1.993
972236AH1-702 GEN2
Adder
1.733
961051AF2-396 GEN
Solar/Wind Harmer
11.03
961051AF2-396 GEN
Solar/Wind Harmer
7.353
276916AD2-100_GEN
Solar/Wind Harmer
11.472
276911AD2-131_GEN
Solar/Wind Harmer
0.756
938861AE1-114 GEN
Solar/Wind Harmer
3.095
274764LEE CO EC;5U
Adder
7.269
274765LEE CO EC;6U
Adder
7.269
274762LEE CO EC;3U
Adder
7.252
274763LEE CO EC;4U
Adder
7.183
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.873
247620Y3-023
Adder
0.342
970291AG2-192 GEN
Solar/Wind Harmer
0.495
970291AG2-192 GEN
Solar/Wind Harmer
0.229
944231AF1-091 GEN
Solar/Wind Harmer
7.025
971613AH1-306 GEN
Solar/Wind Harmer
1.445
252509AD1-136 GEN
Solar/Wind Helper
0.21
25183208HLCRTG
Solar/Wind Helper
2.03
962581AG1-107 GEN
Solar/Wind Helper
0.905
961491AF2-440 GEN
Solar/Wind Helper
0.037
253349AC2-067 GEN
Solar/Wind Helper
0.213
253400AC2-068 GEN
Solar/Wind Helper
0.086
339236AF1-050_GEN
Solar/Wind Helper
0.404
253415AE1-040 GEN
Solar/Wind Helper
0.484
339231AF1-038_GEN
Solar/Wind Helper
0.394
24344205RKG1
50/50
11.252
24344205RKG1
50/50
11.252
24344305RKG2
50/50
11.213
270393AB1-087 CT1
50/50
2.513
270394AB1-087 ST1
50/50
2.513
970539AG2-343 GEN
50/50
9.396
970543AG2-345 GEN
50/50
4.698
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.661
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.267
960681AF2-359 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.265
274776LINCOLN ;7U
Adder
7.265
274777LINCOLN ;8U
Adder
7.265
270526AF1-158 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.144
972227AH1-698 GEN1
Adder
2.214
965911AG1-460 GEN
Solar/Wind Harmer
1.094
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.252
274766LEE CO EC;7U
Adder
7.166
276708O09 GEN2
Solar/Wind Harmer
0.191
24639705ELKHART HY
Adder
0.118
965011AG1-365 GEN
Solar/Wind Harmer
3.067
270594AE1-207 GEN
Solar/Wind Harmer
3.372
270032AE2-172
Solar/Wind Harmer
2.007
252510AF1-249 C
Solar/Wind Helper
0.376
339221AD2-048_GEN
Solar/Wind Helper
1.206
943111AE2-339 GEN
Solar/Wind Helper
0.641
339211AE2-254 GEN
Solar/Wind Helper
0.448
253398AE2-221_GEN2
Solar/Wind Helper
1.24
339241AF1-083 GEN
Solar/Wind Helper
0.404
253333AC1-068 GEN
Solar/Wind Helper
0.484
960591AF2-350 GEN
Solar/Wind Harmer
5.921
972037AH1-567 GEN1
Adder
0.155
274800UNIV PARK;3U
Adder
4.938
274801UNIV PARK;4U
Adder
4.938
274827FISK ;RP
Adder
6.57
274687WILL CNTY;4U
Adder
23.495
274687WILL CNTY;4U
Adder
23.495
274731ELWOOD EC;2P
Adder
13.819
274733ELWOOD EC;3P
Adder
13.819
274735ELWOOD EC;4P
Adder
13.819
274728ELWOOD EC;5P
Adder
13.819
970833AG2-524 GEN
Solar/Wind Harmer
6.449
970833AG2-524 GEN
Solar/Wind Harmer
4.299
274675JOLIET 29;7U
Adder
25.765
274675JOLIET 29;7U
Adder
24.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
5.808
274744AC1-111 GEN8
Adder
4.638
274746AC1-111 G10
Adder
4.638
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.06
971771AH1-392 GEN
Solar/Wind Harmer
5.748
274854TWINGROVE;U2
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.91
276668AB2-070 GEN1
Solar/Wind Harmer
0.222
276848AB2-070 GEN3
Solar/Wind Harmer
0.221
276849AB2-070 GEN2
Solar/Wind Harmer
0.222
926823AC1-168 GEN
Solar/Wind Harmer
0.958
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.182
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276863AD2-134 GEN
Solar/Wind Harmer
0.1
971411AH1-196 GEN
Solar/Wind Harmer
8.382
971171AH1-044 GEN
Solar/Wind Harmer
11.115
274823ROCKFORD ;21
Adder
15.441
274856ECOGROVE ;U1
Solar/Wind Harmer
0.128
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971681AH1-341 GEN
Solar/Wind Harmer
8.802
944221AF1-090 GEN
Solar/Wind Harmer
3.186
276741O09 GEN1
Solar/Wind Harmer
0.191
972267AH1-718 GEN
Adder
3.215
946321AF1-296 GEN
Solar/Wind Harmer
2.925
971549AH1-272 GEN
Solar/Wind Harmer
10.203
270071AF1-092 GEN
Solar/Wind Harmer
8.932
970031AG2-029 GEN
Solar/Wind Harmer
2.434
970289AG2-191 GEN
Solar/Wind Harmer
0.724
959331AF2-224 GEN
Solar/Wind Harmer
2.147
339216AC1-074 GEN
Solar/Wind Helper
1.461
253406AD2-031_GEN
Solar/Wind Helper
0.712
270340AC2-060 GEN
Solar/Wind Helper
1.095
241972AD1-140 GEN
Solar/Wind Helper
2.071
253338AC1-165 GEN
Solar/Wind Helper
0.467
253343AC1-166 GEN
Solar/Wind Helper
0.467
950011AG9-010
External Queue
6.200752258300781
991082J1475 G
External Queue
6.164829730987549
950051AG9-018
External Queue
4.865413665771484
955142J992
External Queue
11.419598579406738
990742J1381
External Queue
17.560279846191406
991312J1772
External Queue
12.36315631866455
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.962
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.555
LAGNLTFEXP_LAGN->PJM
CLTF
2.301
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
1.033
WECLTFEXP_WEC->PJM
CLTF
3.003
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.212
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.737
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.546
MECLTFEXP_MEC->PJM
CLTF
10.638
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.591
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.83
MW Contribution:
14.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.065
23559001PLEAS1
50/50
6.097
270051AF1-062 GEN
50/50
11.777
270475AD2-096_GEN
50/50
7.114
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
961921AG1-034 GEN
Solar/Wind Harmer
7.586
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
970191AG2-125 GEN
Solar/Wind Harmer
1.937
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
971191AH1-055 GEN
Solar/Wind Harmer
19.175
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
944531AF1-118 GEN
Solar/Wind Harmer
33.233
270043AE2-236 GEN
Solar/Wind Harmer
4.754
252519AF1-045_GEN
Solar/Wind Harmer
3.844
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
9.036
25194608D.CRK4
Adder
1.732
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
971347AH1-153 GEN
Solar/Wind Harmer
3.658
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.95
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
970289AG2-191 GEN
Solar/Wind Harmer
0.8
945111AF1-176 GEN
Solar/Wind Harmer
5.891
247642Z2-115 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
274753CRETE EC ;3U
Adder
8.436
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274811UNIV PK N;7U
Adder
5.114
972167AH1-666 GEN
Solar/Wind Harmer
5.69
274803UNIV PARK;6U
Adder
5.941
24728705AND G3
Adder
8.173
24728505AND G1
Adder
3.908
274887GEN-1.85
Solar/Wind Harmer
0.185
276843GEN-1.7
Solar/Wind Harmer
0.23
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274826FISK ;BP
Adder
11.151
972038AH1-567 GEN2
Adder
0.372
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
972259AH1-714 GEN
Adder
19.413
274676JOLIET 29;8U
Adder
30.039
274729ELWOOD EC;1P
Adder
16.687
274730ELWOOD EC;6P
Adder
16.687
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
274682WAUKEGAN ;7U
Adder
18.096
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970193AG2-126 GEN
Solar/Wind Harmer
10.468
970571AG2-364 GEN
Solar/Wind Harmer
13.944
964991AG1-363 GEN
Solar/Wind Helper
5.155
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.831
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
23562501BACKB
Solar/Wind Helper
1.012
235063AE1-101 C2
Solar/Wind Helper
1.672
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
208835TUHI V3-051
Solar/Wind Helper
0.022
972239AH1-704 GEN
Adder
2.678
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270291AC1-194 GEN
Solar/Wind Harmer
0
970179AG2-119 GEN
Solar/Wind Harmer
6.854
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
253406AD2-031_GEN
Solar/Wind Harmer
0.559
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270377AD1-106 GEN
Solar/Wind Harmer
2.842
247521TR3_G114
Solar/Wind Harmer
0.27
965051AG1-369 GEN
Solar/Wind Harmer
3.723
959331AF2-224 GEN
Solar/Wind Harmer
5.217
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.438
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
963791AG1-232 GEN
Solar/Wind Harmer
9.987
270071AF1-092 GEN
Solar/Wind Harmer
14.177
971985AH1-537 GEN
Solar/Wind Harmer
2.196
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
25196508WSDLE4
Adder
8.944
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
270543AE2-219 C
Solar/Wind Harmer
5.137
247536S-71 GEN
Solar/Wind Harmer
0.293
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
970289AG2-191 GEN
Solar/Wind Harmer
1.382
971771AH1-392 GEN
Solar/Wind Harmer
7.271
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
971549AH1-272 GEN
Solar/Wind Harmer
14.794
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.634
274776LINCOLN ;7U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972228AH1-698 GEN2
Adder
3.772
972227AH1-698 GEN1
Adder
2.656
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
270119AB2-067 GEN1
50/50
7.069
270120AB2-067 GEN2
50/50
7.069
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.31
938701AE1-092 GEN
Solar/Wind Harmer
12.867
971655AH1-328 GEN
Solar/Wind Harmer
2.843
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
25326509SID D
Adder
1.446
971073AG2-665 GEN
Solar/Wind Harmer
5.597
970879AG2-548 GEN
Solar/Wind Harmer
1.272
25326109MON D
Adder
1.437
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
246937BC-WTG2
Solar/Wind Harmer
0.302
270246TR4_N_V150
Solar/Wind Harmer
0.048
270247TR4_N_V136
Solar/Wind Harmer
0.048
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.351
944541AF1-119 GEN
Solar/Wind Harmer
0.492
960971AF2-388 GEN
Solar/Wind Harmer
4.326
942221AE2-234 GEN
Solar/Wind Harmer
2.958
25194408D.CRK1
Adder
7.968
25194508D.CRK3
Adder
1.49
970621AG2-405 GEN
Solar/Wind Harmer
1.345
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970885AG2-551 GEN
Solar/Wind Harmer
2.446
247621Y3-024
Adder
0.253
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270031AE2-169
Solar/Wind Harmer
4.021
270599AE1-208 GEN
Solar/Wind Harmer
6.701
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728805RICHG1
Adder
3.944
24728905RICHG2
Adder
3.944
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.052
965791AG1-447 GEN
Solar/Wind Harmer
6.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274805UNIV PK N;1U
Adder
5.126
274808UNIV PK N;4U
Adder
5.092
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
276776AD2-060 GEN
Solar/Wind Harmer
0.758
958011AF2-095 GEN
Solar/Wind Harmer
10.234
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
274674JOLIET 9 ;6U
Adder
15.628
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274696ROCKY RD ;4P
Adder
11.481
274695ROCKY RD ;2P
Adder
11.216
274693ROCKY RD ;1P
Adder
11.106
274728ELWOOD EC;5P
Adder
16.687
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274735ELWOOD EC;4P
Adder
16.687
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
274744AC1-111 GEN8
Adder
5.652
274746AC1-111 G10
Adder
5.652
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
970169AG2-114 GEN
Solar/Wind Harmer
7.011
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
971411AH1-196 GEN
Solar/Wind Harmer
10.47
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.32
23750701CROSSCHOOL
Solar/Wind Helper
1.509
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.512
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.062
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
274697ROCKY RD ;3P
Adder
3.047
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276901AD2-066 C O1
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
962691AG1-118 GEN
Solar/Wind Harmer
21.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
942111AE2-223 GEN
Solar/Wind Harmer
2.266
316097T157 G90
Solar/Wind Helper
1.51
235054AD2-180 GEN
Solar/Wind Helper
2.04
23585401KL_K28_T16
Solar/Wind Helper
1.489
235531U2-073 GEN
Solar/Wind Helper
3.327
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.344
235062AE1-101 C1
Solar/Wind Helper
1.672
316411AF1-147_GEN1
Solar/Wind Helper
0.895
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.17
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
270166AC1-044 GEN3
50/50
7.069
23559101PLEAS2
50/50
6.097
962761AG1-125 GEN
Solar/Wind Harmer
34.394
970149AG2-104 GEN
Solar/Wind Harmer
18.573
970155AG2-107 GEN
Solar/Wind Harmer
21.963
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.894
270273AD2-016 GEN
Solar/Wind Harmer
0.807
972269AH1-719 GEN
Adder
2.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965421AG1-410 GEN
Solar/Wind Harmer
22.47
960001AF2-291 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965011AG1-365 GEN
Solar/Wind Harmer
7.453
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
958861AF2-177 GEN
Solar/Wind Harmer
3.191
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.732
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.351
970825AG2-519 GEN
Solar/Wind Harmer
2.589
24639705ELKHART HY
Adder
0.16
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
276903AD2-071 C
Solar/Wind Harmer
8.095
25196008MFTGT1
Adder
1.443
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.365
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274754CRETE EC ;4U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
274802UNIV PARK;5U
Adder
5.941
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
31.151
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
939401AE1-172 GEN
Solar/Wind Harmer
5.275
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
274682WAUKEGAN ;7U
Adder
18.096
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.818
971997AH1-543 GEN
Solar/Wind Harmer
3.68
962781AG1-127 GEN
Solar/Wind Harmer
6.668
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
316095T157 G97
Solar/Wind Helper
1.51
23583801GRNGAP
Solar/Wind Helper
5.626
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
238126S14_GEN_1
Solar/Wind Helper
0.831
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.661
237038AE2-054 C
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
205932AD2-116_GEN
Solar/Wind Helper
0.512
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.594
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.868
316044AC1-158 PL1
Solar/Wind Helper
1.303
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.516
20716028EGP_W2-019
Solar/Wind Helper
0.019
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20715028HAN_X4-015
Solar/Wind Helper
0.057
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.031
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.792
211065PSPA IPP
Solar/Wind Helper
0.152
963161AG1-165 GEN
Solar/Wind Helper
0.441
957471AF2-041 GEN
Solar/Wind Harmer
13.586
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.58
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
202652Y1-033 WT C
Solar/Wind Helper
0.5
959091AF2-200 GEN
Solar/Wind Harmer
9.057
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4761.71
MW Contribution:
14.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.91 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2513.45
MW Contribution:
9.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
45.352
24727105RPMNG2
50/50
3.311
970583AG2-370 GEN
50/50
2.796
270142AC1-141 CT1_
50/50
2.011
24642205MAYFLWER
50/50
0.03
246938BC-WTG3
Solar/Wind Harmer
1.031
270491AE1-102 GEN2
Solar/Wind Harmer
3.723
965021AG1-366 GEN
Solar/Wind Harmer
4.589
270043AE2-236 GEN
Solar/Wind Harmer
5.206
270063AE2-323 C
Solar/Wind Harmer
0
24727005RPMNG1
50/50
3.31
960861AF2-377 GEN
50/50
2.388
970521AG2-332 GEN
50/50
10.816
24639705ELKHART HY
50/50
0.149
270143AC1-141 CT2_
50/50
2.011
246936BC-WTG1
Solar/Wind Harmer
1.154
270489AE1-102 GEN1
Solar/Wind Harmer
3.723
965421AG1-410 GEN
Solar/Wind Harmer
81.634
965011AG1-365 GEN
Solar/Wind Harmer
13.768
270024AE2-089 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
31.738
24695305TIMB G C
Solar/Wind Harmer
0.527
945111AF1-176 GEN
Solar/Wind Harmer
4.809
971347AH1-153 GEN
Solar/Wind Harmer
2.9
270505AE1-170 C O1
Solar/Wind Harmer
6.075
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.264
274752CRETE EC ;2U
Adder
6.248
274753CRETE EC ;3U
Adder
6.248
274724RIVER EC ;11
Adder
13.377
274814UNIV PK N;0U
Adder
3.786
274807UNIV PK N;3U
Adder
3.778
274811UNIV PK N;7U
Adder
3.753
274772LINCOLN ;3U
Adder
6.299
274803UNIV PARK;6U
Adder
4.324
274826FISK ;BP
Adder
8.11
972038AH1-567 GEN2
Adder
0.27
274887GEN-1.85
Solar/Wind Harmer
0.134
276843GEN-1.7
Solar/Wind Harmer
0.167
276806AD2-047 C O1
Solar/Wind Harmer
2.92
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.004
970707AG2-453 GEN
Solar/Wind Harmer
16.726
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.622
274729ELWOOD EC;1P
Adder
11.982
274730ELWOOD EC;6P
Adder
11.982
274734ELWOOD EC;8P
Adder
11.982
274736ELWOOD EC;9P
Adder
11.982
970289AG2-191 GEN
Solar/Wind Harmer
0.558
946031AF1-268 GEN
Solar/Wind Harmer
4.787
943121AE2-341 GEN
Solar/Wind Harmer
8.427
943591AF1-030 GEN
Solar/Wind Harmer
5.604
270004AE1-209 GEN
Solar/Wind Harmer
1.089
274862TOP CROP ;2U
Solar/Wind Harmer
0.674
970825AG2-519 GEN
Solar/Wind Harmer
3.754
274682WAUKEGAN ;7U
Adder
12.793
276868AE1-113 GEN
Solar/Wind Harmer
0.98
274879MINONK ;1U
Solar/Wind Harmer
0.204
946671AF1-331 GEN
Solar/Wind Harmer
0.519
274855GSG-6 ;RU
Solar/Wind Harmer
0.177
274850MENDOTA H;RU
Solar/Wind Harmer
0.056
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.841
959091AF2-200 GEN
Solar/Wind Harmer
9.659
970571AG2-364 GEN
Solar/Wind Harmer
9.566
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.308
274767LEE CO EC;8U
Adder
6.234
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.155
965091AG1-374 GEN
Solar/Wind Harmer
13.563
965931AG1-462 GEN
Solar/Wind Harmer
11.528
971087AG2-675 GEN
Solar/Wind Harmer
2.411
959611AF2-252 GEN
Solar/Wind Harmer
1.507
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.973
957381AF2-032 GEN
Solar/Wind Harmer
0.92
942481AE2-261 GEN
Solar/Wind Harmer
12.093
970193AG2-126 GEN
Solar/Wind Harmer
5.875
24728705AND G3
Adder
4.327
24728505AND G1
Adder
2.069
942871AE2-306 GEN
Solar/Wind Helper
0.448
270284AF1-227 GEN1
Solar/Wind Helper
1.912
270287AF1-227 GEN3
Solar/Wind Helper
0.701
276820AF1-078_GEN
Solar/Wind Helper
0.338
270541AE2-072 C
Solar/Wind Helper
0.958
965651AG1-433 GEN
Solar/Wind Harmer
1.86
958861AF2-177 GEN
Solar/Wind Harmer
2.67
945111AF1-176 GEN
Solar/Wind Harmer
10.586
957891AF2-083 GEN
Solar/Wind Harmer
9.711
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.972
970373AG2-245 GEN
Solar/Wind Harmer
11.129
274751CRETE EC ;1U
Adder
6.248
274754CRETE EC ;4U
Adder
6.248
274723RIVER EC ;12
Adder
13.542
274812UNIV PK N;8U
Adder
3.753
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.299
274774LINCOLN ;5U
Adder
6.299
274802UNIV PARK;5U
Adder
4.324
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.679
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.423
274674JOLIET 9 ;6U
Adder
11.228
274732ELWOOD EC;7P
Adder
11.982
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.296
270594AE1-207 GEN
Solar/Wind Harmer
5.638
270032AE2-172
Solar/Wind Harmer
3.356
270005AE1-210 C O1
Solar/Wind Harmer
1.089
274745AC1-111 GEN9
Adder
4.025
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.811
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.769
274682WAUKEGAN ;7U
Adder
12.793
274828WAUKEGAN ;BP
Adder
7.853
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.68
939401AE1-172 GEN
Solar/Wind Harmer
3.677
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971997AH1-543 GEN
Solar/Wind Harmer
2.561
957471AF2-041 GEN
Solar/Wind Harmer
14.489
959081AF2-199 GEN
Solar/Wind Harmer
4.83
971067AG2-660 GEN
Solar/Wind Harmer
1.61
274822ROCKFORD ;11
Adder
13.543
276903AD2-071 C
Solar/Wind Harmer
5.365
970819AG2-516 GEN
Solar/Wind Harmer
5.744
970569AG2-363 GEN
Solar/Wind Harmer
14.349
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.308
274766LEE CO EC;7U
Adder
6.234
276708O09 GEN2
Solar/Wind Harmer
0.165
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.443
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.247
963741AG1-226 GEN
Solar/Wind Harmer
10.345
276621W2-048 GEN
Solar/Wind Harmer
0.21
965911AG1-460 GEN
Solar/Wind Harmer
0.809
24728605AND G2
Adder
2.069
970773AG2-487 GEN
Solar/Wind Harmer
0.62
270317AD1-130_GEN
Solar/Wind Helper
4.168
270485AE1-090_GEN
Solar/Wind Helper
0.328
270391AF1-285 GEN3
Solar/Wind Helper
0.597
270578AF1-285 GEN2
Solar/Wind Helper
0.597
270286AF1-227 GEN2
Solar/Wind Helper
0.701
960841AF2-375 GEN
Solar/Wind Helper
1.192
24729405KEY G3
50/50
0.371
24729305KEY G2
50/50
0.365
24729205KEY G1
50/50
0.363
247620Y3-023
50/50
0.463
960851AF2-376 GEN
50/50
2.077
24643105BUCHANAN
50/50
0.01
246937BC-WTG2
Solar/Wind Harmer
1.154
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.833
944231AF1-091 GEN
Solar/Wind Harmer
16.013
944541AF1-119 GEN
Solar/Wind Harmer
0.423
960971AF2-388 GEN
Solar/Wind Harmer
3.72
970349AG2-230 GEN
Solar/Wind Harmer
8.699
961051AF2-396 GEN
Solar/Wind Harmer
11.565
961051AF2-396 GEN
Solar/Wind Harmer
7.71
270031AE2-169
Solar/Wind Harmer
3.074
270599AE1-208 GEN
Solar/Wind Harmer
5.123
965681AG1-436 GEN
Solar/Wind Harmer
6.895
965791AG1-447 GEN
Solar/Wind Harmer
5.056
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.406
247621Y3-024
Adder
0.181
274805UNIV PK N;1U
Adder
3.762
274808UNIV PK N;4U
Adder
3.737
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.299
274771LINCOLN ;2U
Adder
6.299
274888KELLY CRK;1U
Solar/Wind Harmer
0.3
276776AD2-060 GEN
Solar/Wind Harmer
0.55
958011AF2-095 GEN
Solar/Wind Harmer
7.42
970941AG2-585 GEN
Solar/Wind Harmer
2.834
276897AD1-100 C
Solar/Wind Harmer
12.751
274674JOLIET 9 ;6U
Adder
11.228
276893AG1-478 C
Solar/Wind Harmer
0.339
970291AG2-192 GEN
Solar/Wind Harmer
0.659
970291AG2-192 GEN
Solar/Wind Harmer
0.304
971613AH1-306 GEN
Solar/Wind Harmer
2.416
958481AF2-142 GEN
Solar/Wind Harmer
7.489
274696ROCKY RD ;4P
Adder
8.116
274695ROCKY RD ;2P
Adder
7.929
274693ROCKY RD ;1P
Adder
7.851
274697ROCKY RD ;3P
Adder
2.154
274683WAUKEGAN ;8U
Adder
14.981
274683WAUKEGAN ;8U
Adder
12.628
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
7.394
962691AG1-118 GEN
Solar/Wind Harmer
14.789
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.659
971343AH1-151 GEN
Solar/Wind Harmer
9.659
972235AH1-702 GEN1
Adder
1.735
972236AH1-702 GEN2
Adder
1.509
938861AE1-114 GEN
Solar/Wind Harmer
2.691
274764LEE CO EC;5U
Adder
6.323
274765LEE CO EC;6U
Adder
6.323
274762LEE CO EC;3U
Adder
6.308
274763LEE CO EC;4U
Adder
6.249
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.754
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.527
942111AE2-223 GEN
Solar/Wind Harmer
1.496
960611AF2-352 GEN
Solar/Wind Harmer
1.507
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.427
970885AG2-551 GEN
Solar/Wind Harmer
1.476
970241AG2-163 GEN
Solar/Wind Harmer
2.55
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.043
276838X2-022 GEN2
Solar/Wind Harmer
0.236
276916AD2-100_GEN
Solar/Wind Harmer
8.418
276911AD2-131_GEN
Solar/Wind Harmer
0.555
945391AF1-204 GEN
Solar/Wind Harmer
4.161
970623AG2-406 GEN
Solar/Wind Harmer
0.646
971587AH1-292 GEN
Solar/Wind Harmer
2.428
247607V1-011 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
3.77
247522W1-056 GEN
Solar/Wind Helper
1.187
253378AE2-206_GEN
Solar/Wind Helper
0.725
270349AD2-093_GEN
Solar/Wind Helper
0.869
270471AD2-092_GEN
Solar/Wind Helper
0.869
241960AC2-195 GEN
Solar/Wind Helper
0.709
24727205RPMNG3
50/50
3.291
24729505KEY G4
50/50
6.793
24653605MOTTVILLE
50/50
0.003
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.776
957201AF2-014 GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
3.627
959331AF2-224 GEN
Solar/Wind Harmer
9.638
963791AG1-232 GEN
Solar/Wind Harmer
11.962
970031AG2-029 GEN
Solar/Wind Harmer
4.557
965041AG1-368 GEN
Solar/Wind Harmer
8.389
270071AF1-092 GEN
Solar/Wind Harmer
14.462
247521TR3_G114
Solar/Wind Harmer
0.259
965051AG1-369 GEN
Solar/Wind Harmer
3.575
971771AH1-392 GEN
Solar/Wind Harmer
5.853
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.913
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.109
274775LINCOLN ;6U
Adder
6.299
274776LINCOLN ;7U
Adder
6.299
274777LINCOLN ;8U
Adder
6.299
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.748
274800UNIV PARK;3U
Adder
4.311
274801UNIV PARK;4U
Adder
4.311
960591AF2-350 GEN
Solar/Wind Harmer
5.152
972228AH1-698 GEN2
Adder
2.728
972227AH1-698 GEN1
Adder
1.92
274687WILL CNTY;4U
Adder
20.467
274687WILL CNTY;4U
Adder
20.467
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.423
274675JOLIET 29;7U
Adder
21.622
274728ELWOOD EC;5P
Adder
11.982
274731ELWOOD EC;2P
Adder
11.982
274733ELWOOD EC;3P
Adder
11.982
274735ELWOOD EC;4P
Adder
11.982
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.964
970833AG2-524 GEN
Solar/Wind Harmer
5.568
970833AG2-524 GEN
Solar/Wind Harmer
3.712
971611AH1-305 GEN
Solar/Wind Harmer
2.999
274744AC1-111 GEN8
Adder
4.025
274746AC1-111 G10
Adder
4.025
970073AG2-061 GEN
Solar/Wind Harmer
1.643
247536S-71 GEN
Solar/Wind Harmer
0.197
971411AH1-196 GEN
Solar/Wind Harmer
7.295
971675AH1-338 GEN
Solar/Wind Harmer
1.895
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276863AD2-134 GEN
Solar/Wind Harmer
0.087
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.659
274823ROCKFORD ;21
Adder
13.445
274856ECOGROVE ;U1
Solar/Wind Harmer
0.112
926823AC1-168 GEN
Solar/Wind Harmer
0.812
970169AG2-114 GEN
Solar/Wind Harmer
4.769
971681AH1-341 GEN
Solar/Wind Harmer
7.649
971549AH1-272 GEN
Solar/Wind Harmer
9.785
972267AH1-718 GEN
Adder
2.795
276741O09 GEN1
Solar/Wind Harmer
0.165
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.155
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.832
946321AF1-296 GEN
Solar/Wind Harmer
2.546
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.952
270543AE2-219 C
Solar/Wind Harmer
3.099
276668AB2-070 GEN1
Solar/Wind Harmer
0.168
276848AB2-070 GEN3
Solar/Wind Harmer
0.167
276849AB2-070 GEN2
Solar/Wind Harmer
0.168
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.847
944221AF1-090 GEN
Solar/Wind Harmer
2.28
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
0.881
270224U2-072_GEN2
Solar/Wind Helper
0.881
270227U2-072_GEN3
Solar/Wind Helper
0.881
270228U2-072_GEN4
Solar/Wind Helper
0.881
270231U2-072_GEN5
Solar/Wind Helper
0.881
966831AG1-554 GEN
Solar/Wind Helper
0.889
270499AE1-146 GEN
Solar/Wind Helper
1.989
945641AF1-229 GEN
Solar/Wind Helper
0.952
990497J1323
External Queue
1.5952997207641602
990792J1392
External Queue
5.487830638885498
LAGNLTFEXP_LAGN->PJM
CLTF
5.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.274
TVALTFEXP_TVA->PJM
CLTF
2.24
NYPJM->LTFIMP_NY
CLTF
1.314
LGEELTFEXP_LGEE->PJM
CLTF
1.767
WECLTFEXP_WEC->PJM
CLTF
2.626
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.114
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.636
MECLTFEXP_MEC->PJM
CLTF
9.653
SIGELTFEXP_SIGE->PJM
CLTF
0.197
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.784

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.9 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5297.56
MW Contribution:
16.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.726
24344105CKG2
50/50
10.12
962761AG1-125 GEN
Solar/Wind Harmer
74.4
970149AG2-104 GEN
Solar/Wind Harmer
40.177
970155AG2-107 GEN
Solar/Wind Harmer
47.51
274773LINCOLN ;4U
Adder
10.701
274774LINCOLN ;5U
Adder
10.701
274723RIVER EC ;12
Adder
22.518
24639705ELKHART HY
Adder
0.193
274751CRETE EC ;1U
Adder
10.338
274754CRETE EC ;4U
Adder
10.338
274812UNIV PK N;8U
Adder
6.271
957891AF2-083 GEN
Solar/Wind Harmer
14.548
274802UNIV PARK;5U
Adder
7.287
945111AF1-176 GEN
Solar/Wind Harmer
15.539
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.275
274676JOLIET 29;8U
Adder
38.191
274674JOLIET 9 ;6U
Adder
19.151
274732ELWOOD EC;7P
Adder
20.437
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.515
274745AC1-111 GEN9
Adder
6.924
270055AF2-134 C O1
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.615
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.395
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.104
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
13.576
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.138
939401AE1-172 GEN
Solar/Wind Harmer
6.395
962781AG1-127 GEN
Solar/Wind Harmer
8.134
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.993
971997AH1-543 GEN
Solar/Wind Harmer
4.466
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.605
957471AF2-041 GEN
Solar/Wind Harmer
25.396
959081AF2-199 GEN
Solar/Wind Harmer
8.465
971067AG2-660 GEN
Solar/Wind Harmer
2.822
965651AG1-433 GEN
Solar/Wind Harmer
2.481
274822ROCKFORD ;11
Adder
23.769
970819AG2-516 GEN
Solar/Wind Harmer
10.109
970569AG2-363 GEN
Solar/Wind Harmer
25.234
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.167
274766LEE CO EC;7U
Adder
11.036
958861AF2-177 GEN
Solar/Wind Harmer
3.623
276708O09 GEN2
Solar/Wind Harmer
0.294
276646AC1-214 GEN2
Solar/Wind Harmer
0.326
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.579
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.871
276621W2-048 GEN
Solar/Wind Harmer
0.396
270594AE1-207 GEN
Solar/Wind Harmer
8.855
270032AE2-172
Solar/Wind Harmer
5.271
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.696
965911AG1-460 GEN
Solar/Wind Harmer
1.557
270005AE1-210 C O1
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
2.723
965421AG1-410 GEN
Solar/Wind Harmer
22.474
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.436
246936BC-WTG1
Solar/Wind Harmer
0.297
270489AE1-102 GEN1
Solar/Wind Harmer
0.958
24728605AND G2
Adder
3.974
970091AG2-072 GEN
Adder
78.436
970773AG2-487 GEN
Solar/Wind Harmer
1.228
270317AD1-130_GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.059
24723205RIVRG3
Adder
16.391
24721705FLATG2
50/50
25.639
270102X2-052 ST
50/50
2.04
270100X2-052 CT1
50/50
1.885
270101X2-052 CT2
50/50
1.885
970349AG2-230 GEN
Solar/Wind Harmer
13.856
965681AG1-436 GEN
Solar/Wind Harmer
11.105
965791AG1-447 GEN
Solar/Wind Harmer
8.144
274770LINCOLN ;1U
Adder
10.701
274771LINCOLN ;2U
Adder
10.701
274805UNIV PK N;1U
Adder
6.285
274808UNIV PK N;4U
Adder
6.243
247620Y3-023
Adder
0.576
274888KELLY CRK;1U
Solar/Wind Harmer
0.509
276776AD2-060 GEN
Solar/Wind Harmer
0.93
958011AF2-095 GEN
Solar/Wind Harmer
12.557
970941AG2-585 GEN
Solar/Wind Harmer
4.796
276897AD1-100 C
Solar/Wind Harmer
21.761
274674JOLIET 9 ;6U
Adder
19.151
961051AF2-396 GEN
Solar/Wind Harmer
17.344
961051AF2-396 GEN
Solar/Wind Harmer
11.563
276893AG1-478 C
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.031
274695ROCKY RD ;2P
Adder
13.708
274693ROCKY RD ;1P
Adder
13.573
274697ROCKY RD ;3P
Adder
3.724
958481AF2-142 GEN
Solar/Wind Harmer
12.877
274683WAUKEGAN ;8U
Adder
25.9
274683WAUKEGAN ;8U
Adder
21.833
962691AG1-118 GEN
Solar/Wind Harmer
25.676
958491AF2-143 GEN
Solar/Wind Harmer
12.799
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
16.931
971343AH1-151 GEN
Solar/Wind Harmer
16.931
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.565
960971AF2-388 GEN
Solar/Wind Harmer
4.962
972235AH1-702 GEN1
Adder
3.049
972236AH1-702 GEN2
Adder
2.651
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
4.755
274764LEE CO EC;5U
Adder
11.194
274765LEE CO EC;6U
Adder
11.194
274762LEE CO EC;3U
Adder
11.167
274763LEE CO EC;4U
Adder
11.062
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.343
276645AC1-214 GEN1
Solar/Wind Harmer
0.326
942111AE2-223 GEN
Solar/Wind Harmer
2.688
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
3.3
960611AF2-352 GEN
Solar/Wind Harmer
2.733
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.927
970291AG2-192 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.479
970241AG2-163 GEN
Solar/Wind Harmer
4.651
270031AE2-169
Solar/Wind Harmer
4.369
270599AE1-208 GEN
Solar/Wind Harmer
7.282
276615X2-022 GEN
Solar/Wind Harmer
0.082
276838X2-022 GEN2
Solar/Wind Harmer
0.445
971613AH1-306 GEN
Solar/Wind Harmer
3.795
270246TR4_N_V150
Solar/Wind Harmer
0.05
270247TR4_N_V136
Solar/Wind Harmer
0.05
276916AD2-100_GEN
Solar/Wind Harmer
16.28
276911AD2-131_GEN
Solar/Wind Harmer
1.072
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
17.757
945391AF1-204 GEN
Solar/Wind Harmer
8.104
964611AG1-324 GEN
Solar/Wind Harmer
0.571
270201AC2-176 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.257
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.297
971587AH1-292 GEN
Solar/Wind Harmer
5.361
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.112
970885AG2-551 GEN
Solar/Wind Harmer
2.371
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.29
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.474
24728905RICHG2
Adder
3.474
24723005RIVRG1
Adder
16.391
24723105RIVRG2
Adder
16.391
24722005FLATG5
50/50
1.726
24721905FLATG4
50/50
31.534
962771AG1-126 GEN
Solar/Wind Harmer
74.4
970153AG2-106 GEN
Solar/Wind Harmer
47.51
971347AH1-153 GEN
Solar/Wind Harmer
4.619
270043AE2-236 GEN
Solar/Wind Harmer
5.83
944531AF1-118 GEN
Solar/Wind Harmer
39.701
274772LINCOLN ;3U
Adder
10.701
274724RIVER EC ;11
Adder
22.258
274752CRETE EC ;2U
Adder
10.338
274753CRETE EC ;3U
Adder
10.338
970707AG2-453 GEN
Solar/Wind Harmer
28.587
274814UNIV PK N;0U
Adder
6.326
274807UNIV PK N;3U
Adder
6.312
274811UNIV PK N;7U
Adder
6.271
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
9.169
972259AH1-714 GEN
Adder
23.869
274826FISK ;BP
Adder
13.684
274803UNIV PARK;6U
Adder
7.287
274887GEN-1.85
Solar/Wind Harmer
0.227
276843GEN-1.7
Solar/Wind Harmer
0.282
276806AD2-047 C O1
Solar/Wind Harmer
4.941
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.059
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
36.827
274729ELWOOD EC;1P
Adder
20.436
274730ELWOOD EC;6P
Adder
20.437
274734ELWOOD EC;8P
Adder
20.437
274736ELWOOD EC;9P
Adder
20.437
943121AE2-341 GEN
Solar/Wind Harmer
14.508
943591AF1-030 GEN
Solar/Wind Harmer
9.648
965021AG1-366 GEN
Solar/Wind Harmer
2.872
274862TOP CROP ;2U
Solar/Wind Harmer
1.159
274682WAUKEGAN ;7U
Adder
22.104
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24721605FLATG1
50/50
1.726
270071AF1-092 GEN
Solar/Wind Harmer
17.295
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
10.701
274776LINCOLN ;7U
Adder
10.701
274777LINCOLN ;8U
Adder
10.701
971771AH1-392 GEN
Solar/Wind Harmer
8.847
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
8.138
274827FISK ;RP
Adder
9.698
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.72
972228AH1-698 GEN2
Adder
4.629
972227AH1-698 GEN1
Adder
3.26
274800UNIV PARK;3U
Adder
7.284
274801UNIV PARK;4U
Adder
7.284
970031AG2-029 GEN
Solar/Wind Harmer
4.711
274687WILL CNTY;4U
Adder
34.799
274687WILL CNTY;4U
Adder
34.799
274675JOLIET 29;7U
Adder
38.191
274675JOLIET 29;7U
Adder
36.827
274728ELWOOD EC;5P
Adder
20.437
274731ELWOOD EC;2P
Adder
20.436
274733ELWOOD EC;3P
Adder
20.436
274735ELWOOD EC;4P
Adder
20.436
970833AG2-524 GEN
Solar/Wind Harmer
9.54
970833AG2-524 GEN
Solar/Wind Harmer
6.36
274744AC1-111 GEN8
Adder
6.924
274746AC1-111 G10
Adder
6.924
959331AF2-224 GEN
Solar/Wind Harmer
6.031
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
2.844
959141AF2-205 GEN
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
3.313
971411AH1-196 GEN
Solar/Wind Harmer
12.74
276861AD2-134 GEN
Solar/Wind Harmer
0.151
276863AD2-134 GEN
Solar/Wind Harmer
0.151
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
5.051
971171AH1-044 GEN
Solar/Wind Harmer
16.931
274823ROCKFORD ;21
Adder
23.596
970169AG2-114 GEN
Solar/Wind Harmer
8.419
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.43
971681AH1-341 GEN
Solar/Wind Harmer
13.512
972267AH1-718 GEN
Adder
4.973
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.294
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.684
946321AF1-296 GEN
Solar/Wind Harmer
4.596
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
11.059
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.499
965041AG1-368 GEN
Solar/Wind Harmer
8.029
970289AG2-191 GEN
Solar/Wind Harmer
1.518
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.297
971549AH1-272 GEN
Solar/Wind Harmer
16.346
247521TR3_G114
Solar/Wind Harmer
0.284
965051AG1-369 GEN
Solar/Wind Harmer
3.91
944221AF1-090 GEN
Solar/Wind Harmer
4.487
964611AG1-324 GEN
Solar/Wind Harmer
2.967
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.934
247536S-71 GEN
Solar/Wind Harmer
0.293
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.979
270007AE1-245 C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
971029AG2-637 GEN
Solar/Wind Harmer
10.316
276868AE1-113 GEN
Solar/Wind Harmer
1.703
274879MINONK ;1U
Solar/Wind Harmer
0.355
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274855GSG-6 ;RU
Solar/Wind Harmer
0.31
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
16.931
970571AG2-364 GEN
Solar/Wind Harmer
16.823
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.167
274767LEE CO EC;8U
Adder
11.036
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.328
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
965091AG1-374 GEN
Solar/Wind Harmer
24.6
959611AF2-252 GEN
Solar/Wind Harmer
2.733
24386205FR-12G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
20.87
971087AG2-675 GEN
Solar/Wind Harmer
4.365
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.879
971993AH1-541 GEN
Solar/Wind Harmer
3.686
957381AF2-032 GEN
Solar/Wind Harmer
1.767
942481AE2-261 GEN
Solar/Wind Harmer
23.27
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
5.778
24695305TIMB G C
Solar/Wind Harmer
0.648
946031AF1-268 GEN
Solar/Wind Harmer
7.259
970193AG2-126 GEN
Solar/Wind Harmer
11.441
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.403
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.266
270491AE1-102 GEN2
Solar/Wind Harmer
0.958
24728705AND G3
Adder
8.312
24728505AND G1
Adder
3.974
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.938
LAGNLTFEXP_LAGN->PJM
CLTF
16.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.242
TVALTFEXP_TVA->PJM
CLTF
7.96
NYPJM->LTFIMP_NY
CLTF
3.901
LGEELTFEXP_LGEE->PJM
CLTF
5.998
WECLTFEXP_WEC->PJM
CLTF
4.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.416
MECLTFEXP_MEC->PJM
CLTF
18.61
SIGELTFEXP_SIGE->PJM
CLTF
0.498
CPLELTFEXP_CPLE->PJM
CLTF
3.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.551

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4473.55
MW Contribution:
19.17
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
69.962
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.277
270100X2-052 CT1
50/50
2.104
270101X2-052 CT2
50/50
2.104
24643105BUCHANAN
50/50
0.018
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
15.664
961051AF2-396 GEN
Solar/Wind Harmer
19.838
24721605FLATG1
50/50
4.711
270144AC1-141 ST1_
50/50
3.051
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.268
24653605MOTTVILLE
50/50
0.005
959331AF2-224 GEN
Solar/Wind Harmer
7.224
270578AF1-285 GEN2
Solar/Wind Harmer
0.682
270071AF1-092 GEN
Solar/Wind Harmer
19.599
970031AG2-029 GEN
Solar/Wind Harmer
5.461
971771AH1-392 GEN
Solar/Wind Harmer
10.022
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24722005FLATG5
50/50
4.711
24721905FLATG4
50/50
86.05
270475AD2-096_GEN
50/50
10.483
270142AC1-141 CT1_
50/50
3.456
24642205MAYFLWER
50/50
0.053
944961AF1-161 GEN
50/50
4.124
962601AG1-109 GEN
50/50
4.124
962771AG1-126 GEN
Solar/Wind Harmer
109.537
970153AG2-106 GEN
Solar/Wind Harmer
69.947
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270043AE2-236 GEN
Solar/Wind Harmer
6.765
971347AH1-153 GEN
Solar/Wind Harmer
5.221
24721805FLATG3
50/50
4.711
24344105CKG2
50/50
11.483
270143AC1-141 CT2_
50/50
3.456
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.675
24307105BERRINSP G
50/50
0.03
962761AG1-125 GEN
Solar/Wind Harmer
109.537
970149AG2-104 GEN
Solar/Wind Harmer
59.152
970155AG2-107 GEN
Solar/Wind Harmer
69.947
965011AG1-365 GEN
Solar/Wind Harmer
10.32
957891AF2-083 GEN
Solar/Wind Harmer
16.606
945111AF1-176 GEN
Solar/Wind Harmer
17.763
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
5.166
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
274773LINCOLN ;4U
Adder
11.612
274774LINCOLN ;5U
Adder
11.612
274723RIVER EC ;12
Adder
24.471
274751CRETE EC ;1U
Adder
11.245
274754CRETE EC ;4U
Adder
11.245
965421AG1-410 GEN
Solar/Wind Harmer
28.412
970373AG2-245 GEN
Solar/Wind Harmer
19.884
274812UNIV PK N;8U
Adder
6.795
274802UNIV PARK;5U
Adder
7.869
246936BC-WTG1
Solar/Wind Harmer
0.378
270489AE1-102 GEN1
Solar/Wind Harmer
1.219
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
41.04
270055AF2-134 C O1
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
20.564
274732ELWOOD EC;7P
Adder
21.94
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.726
274745AC1-111 GEN9
Adder
7.404
958381AF2-132 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
3.44
270391AF1-285 GEN3
Solar/Wind Harmer
0.682
270063AE2-323 C
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
10.472
944531AF1-118 GEN
Solar/Wind Harmer
44.69
945111AF1-176 GEN
Solar/Wind Harmer
8.069
274772LINCOLN ;3U
Adder
11.612
274724RIVER EC ;11
Adder
24.187
274752CRETE EC ;2U
Adder
11.245
274753CRETE EC ;3U
Adder
11.245
274814UNIV PK N;0U
Adder
6.855
274807UNIV PK N;3U
Adder
6.84
274811UNIV PK N;7U
Adder
6.795
970707AG2-453 GEN
Solar/Wind Harmer
30.807
24695305TIMB G C
Solar/Wind Harmer
0.797
274803UNIV PARK;6U
Adder
7.869
274826FISK ;BP
Adder
14.772
274887GEN-1.85
Solar/Wind Harmer
0.244
276843GEN-1.7
Solar/Wind Harmer
0.304
276806AD2-047 C O1
Solar/Wind Harmer
5.33
972038AH1-567 GEN2
Adder
0.492
972259AH1-714 GEN
Adder
25.709
246938BC-WTG3
Solar/Wind Harmer
0.338
270491AE1-102 GEN2
Solar/Wind Harmer
1.219
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
39.574
274729ELWOOD EC;1P
Adder
21.939
274730ELWOOD EC;6P
Adder
21.94
274734ELWOOD EC;8P
Adder
21.94
274736ELWOOD EC;9P
Adder
21.94
943121AE2-341 GEN
Solar/Wind Harmer
15.518
943591AF1-030 GEN
Solar/Wind Harmer
10.32
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
1.234
274682WAUKEGAN ;7U
Adder
23.522
276868AE1-113 GEN
Solar/Wind Harmer
1.802
274879MINONK ;1U
Solar/Wind Harmer
0.376
946671AF1-331 GEN
Solar/Wind Harmer
0.957
274855GSG-6 ;RU
Solar/Wind Harmer
0.327
274850MENDOTA H;RU
Solar/Wind Harmer
0.104
959091AF2-200 GEN
Solar/Wind Harmer
17.823
970571AG2-364 GEN
Solar/Wind Harmer
17.631
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.659
274767LEE CO EC;8U
Adder
11.522
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.625
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965091AG1-374 GEN
Solar/Wind Harmer
25.202
959611AF2-252 GEN
Solar/Wind Harmer
2.8
247642Z2-115 C
Solar/Wind Harmer
0.003
965931AG1-462 GEN
Solar/Wind Harmer
21.395
971087AG2-675 GEN
Solar/Wind Harmer
4.475
24386205FR-12G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.915
270004AE1-209 GEN
Solar/Wind Harmer
1.752
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.121
970825AG2-519 GEN
Solar/Wind Harmer
6.019
971993AH1-541 GEN
Solar/Wind Harmer
3.688
946031AF1-268 GEN
Solar/Wind Harmer
7.583
957381AF2-032 GEN
Solar/Wind Harmer
1.73
942481AE2-261 GEN
Solar/Wind Harmer
22.758
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.995
24728705AND G3
Adder
8.012
24728505AND G1
Adder
3.831
270541AE2-072 C
Solar/Wind Harmer
0
23906402RICHG1
Adder
1.111
23906502RICHG2&3
Adder
1.11
24729505KEY G4
Adder
9.105
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.376
965041AG1-368 GEN
Solar/Wind Harmer
9.736
274775LINCOLN ;6U
Adder
11.612
274776LINCOLN ;7U
Adder
11.612
274777LINCOLN ;8U
Adder
11.612
247521TR3_G114
Solar/Wind Harmer
0.347
965051AG1-369 GEN
Solar/Wind Harmer
4.782
963791AG1-232 GEN
Solar/Wind Harmer
12.72
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.469
960591AF2-350 GEN
Solar/Wind Harmer
9.405
274800UNIV PARK;3U
Adder
7.859
274801UNIV PARK;4U
Adder
7.859
972228AH1-698 GEN2
Adder
4.989
972227AH1-698 GEN1
Adder
3.513
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.188
274687WILL CNTY;4U
Adder
37.422
274687WILL CNTY;4U
Adder
37.422
274675JOLIET 29;7U
Adder
41.04
274675JOLIET 29;7U
Adder
39.575
274728ELWOOD EC;5P
Adder
21.94
274731ELWOOD EC;2P
Adder
21.939
274733ELWOOD EC;3P
Adder
21.939
274735ELWOOD EC;4P
Adder
21.939
970833AG2-524 GEN
Solar/Wind Harmer
10.228
970833AG2-524 GEN
Solar/Wind Harmer
6.819
971549AH1-272 GEN
Solar/Wind Harmer
19.166
274744AC1-111 GEN8
Adder
7.404
274746AC1-111 G10
Adder
7.404
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
3.016
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.448
971675AH1-338 GEN
Solar/Wind Harmer
3.496
276861AD2-134 GEN
Solar/Wind Harmer
0.16
276863AD2-134 GEN
Solar/Wind Harmer
0.16
971611AH1-305 GEN
Solar/Wind Harmer
5.334
270007AE1-245 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.823
274823ROCKFORD ;21
Adder
24.808
274856ECOGROVE ;U1
Solar/Wind Harmer
0.206
945581AF1-223 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.499
970169AG2-114 GEN
Solar/Wind Harmer
8.815
971681AH1-341 GEN
Solar/Wind Harmer
14.132
972267AH1-718 GEN
Adder
5.171
276741O09 GEN1
Solar/Wind Harmer
0.306
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.961
971609AH1-304 GEN
Solar/Wind Harmer
1.381
946321AF1-296 GEN
Solar/Wind Harmer
4.723
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.58
963841AG1-237 GEN
Solar/Wind Harmer
3.532
964611AG1-324 GEN
Solar/Wind Harmer
3.142
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.308
270543AE2-219 C
Solar/Wind Harmer
5.181
944221AF1-090 GEN
Solar/Wind Harmer
4.314
971029AG2-637 GEN
Solar/Wind Harmer
10.609
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.902
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.486
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
23.522
958861AF2-177 GEN
Solar/Wind Harmer
3.956
274828WAUKEGAN ;BP
Adder
14.44
962781AG1-127 GEN
Solar/Wind Harmer
8.625
939401AE1-172 GEN
Solar/Wind Harmer
6.778
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.051
971997AH1-543 GEN
Solar/Wind Harmer
4.72
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.201
957471AF2-041 GEN
Solar/Wind Harmer
26.735
959081AF2-199 GEN
Solar/Wind Harmer
8.912
971067AG2-660 GEN
Solar/Wind Harmer
2.971
274822ROCKFORD ;11
Adder
24.99
970819AG2-516 GEN
Solar/Wind Harmer
10.604
945371AF1-202 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
26.447
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.659
274766LEE CO EC;7U
Adder
11.522
276708O09 GEN2
Solar/Wind Harmer
0.306
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.948
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.214
270032AE2-172
Solar/Wind Harmer
5.485
270005AE1-210 C O1
Solar/Wind Harmer
1.752
276903AD2-071 C
Solar/Wind Harmer
8.936
970825AG2-519 GEN
Solar/Wind Harmer
2.836
963741AG1-226 GEN
Solar/Wind Harmer
18.848
276621W2-048 GEN
Solar/Wind Harmer
0.393
965911AG1-460 GEN
Solar/Wind Harmer
1.522
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.54
24728605AND G2
Adder
3.831
970773AG2-487 GEN
Solar/Wind Harmer
1.192
23906502RICHG2&3
Adder
1.11
961051AF2-396 GEN
Solar/Wind Harmer
13.225
965681AG1-436 GEN
Solar/Wind Harmer
12.356
965791AG1-447 GEN
Solar/Wind Harmer
9.061
270462AD2-086
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
11.612
274771LINCOLN ;2U
Adder
11.612
270246TR4_N_V150
Solar/Wind Harmer
0.061
270247TR4_N_V136
Solar/Wind Harmer
0.061
274805UNIV PK N;1U
Adder
6.81
274808UNIV PK N;4U
Adder
6.766
274888KELLY CRK;1U
Solar/Wind Harmer
0.548
276776AD2-060 GEN
Solar/Wind Harmer
1.003
958011AF2-095 GEN
Solar/Wind Harmer
13.543
970941AG2-585 GEN
Solar/Wind Harmer
5.173
246937BC-WTG2
Solar/Wind Harmer
0.378
276897AD1-100 C
Solar/Wind Harmer
23.396
944231AF1-091 GEN
Solar/Wind Harmer
21.57
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
20.564
276893AG1-478 C
Solar/Wind Harmer
0.621
944541AF1-119 GEN
Solar/Wind Harmer
0.62
960971AF2-388 GEN
Solar/Wind Harmer
5.451
958481AF2-142 GEN
Solar/Wind Harmer
13.721
274695ROCKY RD ;2P
Adder
14.592
274693ROCKY RD ;1P
Adder
14.449
274697ROCKY RD ;3P
Adder
3.964
274696ROCKY RD ;4P
Adder
14.936
942221AE2-234 GEN
Solar/Wind Harmer
3.664
274683WAUKEGAN ;8U
Adder
27.547
274683WAUKEGAN ;8U
Adder
23.221
962691AG1-118 GEN
Solar/Wind Harmer
27.25
958491AF2-143 GEN
Solar/Wind Harmer
13.572
276901AD2-066 C O1
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.823
971343AH1-151 GEN
Solar/Wind Harmer
17.823
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.202
972236AH1-702 GEN2
Adder
2.785
970623AG2-406 GEN
Solar/Wind Harmer
1.615
938861AE1-114 GEN
Solar/Wind Harmer
4.972
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274764LEE CO EC;5U
Adder
11.687
274765LEE CO EC;6U
Adder
11.687
274762LEE CO EC;3U
Adder
11.659
274763LEE CO EC;4U
Adder
11.55
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.395
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.774
270031AE2-169
Solar/Wind Harmer
4.65
270599AE1-208 GEN
Solar/Wind Harmer
7.749
960611AF2-352 GEN
Solar/Wind Harmer
2.8
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.946
970291AG2-192 GEN
Solar/Wind Harmer
1.081
970291AG2-192 GEN
Solar/Wind Harmer
0.499
971613AH1-306 GEN
Solar/Wind Harmer
3.949
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.604
970241AG2-163 GEN
Solar/Wind Harmer
4.646
970621AG2-405 GEN
Solar/Wind Harmer
1.449
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
247621Y3-024
Adder
0.272
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
926881AC1-175 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
15.862
276911AD2-131_GEN
Solar/Wind Harmer
1.045
970883AG2-550 GEN
Solar/Wind Harmer
7.401
970885AG2-551 GEN
Solar/Wind Harmer
2.467
270383AD1-128 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.788
971587AH1-292 GEN
Solar/Wind Harmer
4.757
24728805RICHG1
Adder
3.35
24728905RICHG2
Adder
3.35
970329AG2-216 GEN
Solar/Wind Harmer
2.663
25326509SID D
Adder
1.142
LAGNLTFEXP_LAGN->PJM
CLTF
11.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.981
TVALTFEXP_TVA->PJM
CLTF
4.815
NYPJM->LTFIMP_NY
CLTF
3.074
LGEELTFEXP_LGEE->PJM
CLTF
4.556
WECLTFEXP_WEC->PJM
CLTF
4.845
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.158
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.375
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.313
MECLTFEXP_MEC->PJM
CLTF
18.13
SIGELTFEXP_SIGE->PJM
CLTF
0.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.889

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.18 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4397.83
MW Contribution:
19.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.756
24642205MAYFLWER
50/50
0.042
944961AF1-161 GEN
50/50
3.292
962601AG1-109 GEN
50/50
3.292
274772LINCOLN ;3U
50/50
7.357
962771AG1-126 GEN
Solar/Wind Harmer
81.685
970153AG2-106 GEN
Solar/Wind Harmer
35.618
971347AH1-153 GEN
Solar/Wind Harmer
5.97
270043AE2-236 GEN
Solar/Wind Harmer
6.503
247643Z2-116 C
Solar/Wind Harmer
0.08
270063AE2-323 C
Solar/Wind Harmer
2.51
270505AE1-170 C O1
Solar/Wind Harmer
17.111
24441505OLIV SLR
Solar/Wind Harmer
0.152
945111AF1-176 GEN
Solar/Wind Harmer
6.435
965021AG1-366 GEN
Solar/Wind Harmer
2.637
944531AF1-118 GEN
Solar/Wind Harmer
39.408
274724RIVER EC ;11
Adder
19.656
972231SS25-0005
Solar/Wind Harmer
10.523
972181SS23-001
Solar/Wind Harmer
6.577
274752CRETE EC ;2U
Adder
5.419
274753CRETE EC ;3U
Adder
5.419
276164X3-005 C
Solar/Wind Harmer
0.777
274814UNIV PK N;0U
Adder
5.578
274807UNIV PK N;3U
Adder
5.566
274811UNIV PK N;7U
Adder
5.53
970707AG2-453 GEN
Solar/Wind Harmer
30.87
274803UNIV PARK;6U
Adder
6.413
274826FISK ;BP
Adder
12.041
972259AH1-714 GEN
Adder
20.975
274887GEN-1.85
Solar/Wind Harmer
5.856
276772AC2-154 GEN
Solar/Wind Harmer
3.068
276843GEN-1.7
Solar/Wind Harmer
0.63
276806AD2-047 C O1
Solar/Wind Harmer
11.759
972038AH1-567 GEN2
Adder
0.401
939351AE1-166 GEN
Solar/Wind Harmer
6.495
274676JOLIET 29;8U
Adder
32.328
274730ELWOOD EC;6P
Adder
17.93
274734ELWOOD EC;8P
Adder
17.93
274736ELWOOD EC;9P
Adder
17.93
274729ELWOOD EC;1P
Adder
17.93
943121AE2-341 GEN
Solar/Wind Harmer
16.292
943591AF1-030 GEN
Solar/Wind Harmer
10.861
964401AG1-302 GEN
Solar/Wind Harmer
9.763
274862TOP CROP ;2U
Solar/Wind Harmer
5.438
274682WAUKEGAN ;7U
Adder
19.309
276868AE1-113 GEN
Solar/Wind Harmer
10.751
274879MINONK ;1U
Solar/Wind Harmer
7.168
276799AD1-013 GEN
Solar/Wind Harmer
2.341
946671AF1-331 GEN
Solar/Wind Harmer
0.444
274855GSG-6 ;RU
Solar/Wind Harmer
3.91
274850MENDOTA H;RU
Solar/Wind Harmer
2.718
276602WESTBROOK C
Solar/Wind Harmer
2.251
274760LEE CO EC;1U
Adder
9.664
274767LEE CO EC;8U
Adder
9.55
24721905FLATG4
Adder
18.411
959091AF2-200 GEN
Solar/Wind Harmer
18.283
270102X2-052 ST
50/50
1.83
270100X2-052 CT1
50/50
1.691
270101X2-052 CT2
50/50
1.691
247620Y3-023
50/50
0.556
24643105BUCHANAN
50/50
0.014
274770LINCOLN ;1U
50/50
7.357
274771LINCOLN ;2U
50/50
7.357
970349AG2-230 GEN
Solar/Wind Harmer
17.91
965681AG1-436 GEN
Solar/Wind Harmer
14.253
965791AG1-447 GEN
Solar/Wind Harmer
7.292
961051AF2-396 GEN
Solar/Wind Harmer
18.009
961051AF2-396 GEN
Solar/Wind Harmer
8.376
270349AD2-093_GEN
Solar/Wind Harmer
4.039
270471AD2-092_GEN
Solar/Wind Harmer
4.039
274805UNIV PK N;1U
Adder
5.542
274808UNIV PK N;4U
Adder
5.506
274888KELLY CRK;1U
Solar/Wind Harmer
6.487
276776AD2-060 GEN
Solar/Wind Harmer
0.46
958011AF2-095 GEN
Solar/Wind Harmer
15.829
970941AG2-585 GEN
Solar/Wind Harmer
6.046
276897AD1-100 C
Solar/Wind Harmer
50.878
274674JOLIET 9 ;6U
Adder
16.804
276893AG1-478 C
Solar/Wind Harmer
0.478
270535AF1-215 GEN1
Solar/Wind Harmer
4.943
270536AF1-215 GEN2
Solar/Wind Harmer
4.943
274695ROCKY RD ;2P
Adder
11.976
274693ROCKY RD ;1P
Adder
11.858
274697ROCKY RD ;3P
Adder
3.253
274696ROCKY RD ;4P
Adder
12.259
958481AF2-142 GEN
Solar/Wind Harmer
16.133
274683WAUKEGAN ;8U
Adder
22.619
274683WAUKEGAN ;8U
Adder
19.067
962691AG1-118 GEN
Solar/Wind Harmer
32.105
960751AF2-366 GEN
Solar/Wind Harmer
3.065
958491AF2-143 GEN
Solar/Wind Harmer
15.995
276901AD2-066 C O1
Solar/Wind Harmer
3.736
944541AF1-119 GEN
Solar/Wind Harmer
4.432
960971AF2-388 GEN
Solar/Wind Harmer
11.571
972235AH1-702 GEN1
Adder
2.646
972236AH1-702 GEN2
Adder
2.301
274764LEE CO EC;5U
Adder
9.686
274765LEE CO EC;6U
Adder
9.686
274762LEE CO EC;3U
Adder
9.664
274763LEE CO EC;4U
Adder
9.573
247621Y3-024
Adder
0.218
971341AH1-150 GEN
Solar/Wind Harmer
18.283
971343AH1-151 GEN
Solar/Wind Harmer
18.283
270144AC1-141 ST1_
50/50
2.433
24641605TWIN BRNCH
50/50
0.02
24344005CKG1
50/50
7.405
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.357
274776LINCOLN ;7U
50/50
7.357
274777LINCOLN ;8U
50/50
7.357
270071AF1-092 GEN
Solar/Wind Harmer
17.36
971771AH1-392 GEN
Solar/Wind Harmer
10.331
270526AF1-158 GEN
Solar/Wind Harmer
5.178
960681AF2-359 GEN
Solar/Wind Harmer
4.309
970031AG2-029 GEN
Solar/Wind Harmer
28.41
959331AF2-224 GEN
Solar/Wind Harmer
11.337
944161AF1-084 GEN
Solar/Wind Harmer
2.492
24729505KEY G4
Adder
7.189
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.534
960591AF2-350 GEN
Solar/Wind Harmer
10.992
274800UNIV PARK;3U
Adder
6.408
274801UNIV PARK;4U
Adder
6.408
972228AH1-698 GEN2
Adder
4.07
972227AH1-698 GEN1
Adder
2.866
274687WILL CNTY;4U
Adder
30.56
274687WILL CNTY;4U
Adder
30.56
274675JOLIET 29;7U
Adder
33.526
274675JOLIET 29;7U
Adder
32.329
274728ELWOOD EC;5P
Adder
17.93
274731ELWOOD EC;2P
Adder
17.93
274733ELWOOD EC;3P
Adder
17.93
274735ELWOOD EC;4P
Adder
17.93
276893AG1-478 C
Solar/Wind Harmer
0.6
970833AG2-524 GEN
Solar/Wind Harmer
9.514
970833AG2-524 GEN
Solar/Wind Harmer
4.425
274744AC1-111 GEN8
Adder
6.063
274746AC1-111 G10
Adder
6.063
958391AF2-133 GEN
Solar/Wind Harmer
9.699
970073AG2-061 GEN
Solar/Wind Harmer
2.48
971549AH1-272 GEN
Solar/Wind Harmer
19.702
959141AF2-205 GEN
Solar/Wind Harmer
6.434
965041AG1-368 GEN
Solar/Wind Harmer
10.597
971675AH1-338 GEN
Solar/Wind Harmer
19.065
971411AH1-196 GEN
Solar/Wind Harmer
15.888
276861AD2-134 GEN
Solar/Wind Harmer
1.891
276863AD2-134 GEN
Solar/Wind Harmer
1.891
958711AF2-162 GEN
Solar/Wind Harmer
1.071
274863CRW1-WTG
Solar/Wind Harmer
5.896
274864CRW2-WTG
Solar/Wind Harmer
5.896
274823ROCKFORD ;21
Adder
20.49
972267AH1-718 GEN
Adder
4.295
971171AH1-044 GEN
Solar/Wind Harmer
18.283
24344105CKG2
50/50
9.143
270143AC1-141 CT2_
50/50
2.756
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.256
24307105BERRINSP G
50/50
0.024
274773LINCOLN ;4U
50/50
7.357
274774LINCOLN ;5U
50/50
7.357
962761AG1-125 GEN
Solar/Wind Harmer
81.685
970149AG2-104 GEN
Solar/Wind Harmer
50.44
970155AG2-107 GEN
Solar/Wind Harmer
35.618
270216AD2-079_GEN
Solar/Wind Harmer
0.695
957891AF2-083 GEN
Solar/Wind Harmer
17.095
945111AF1-176 GEN
Solar/Wind Harmer
20.303
965011AG1-365 GEN
Solar/Wind Harmer
11.337
270449AD2-020 GEN
Solar/Wind Harmer
3.174
943021AE2-325 GEN
Solar/Wind Harmer
4.125
972207SS24-0001
Solar/Wind Harmer
24.651
24441205WTRV SLR C
Solar/Wind Harmer
0.151
274723RIVER EC ;12
Adder
19.886
274751CRETE EC ;1U
Adder
5.419
274754CRETE EC ;4U
Adder
5.419
274812UNIV PK N;8U
Adder
5.53
970373AG2-245 GEN
Solar/Wind Harmer
23.162
274802UNIV PARK;5U
Adder
6.413
941551AE2-152 GEN
Solar/Wind Harmer
4.967
274676JOLIET 29;8U
Adder
33.526
274674JOLIET 9 ;6U
Adder
16.804
274732ELWOOD EC;7P
Adder
17.93
270055AF2-134 C O1
Solar/Wind Harmer
3.295
274871GR RIDGE ;2U
Solar/Wind Harmer
8.376
274847GR RIDGE ;BU
Solar/Wind Harmer
5.508
274745AC1-111 GEN9
Adder
6.063
958381AF2-132 GEN
Solar/Wind Harmer
9.763
276694AA1-018 GEN2
Solar/Wind Harmer
6.786
276691AA1-018 GEN1
Solar/Wind Harmer
0.811
274861TOP CROP ;1U
Solar/Wind Harmer
6.513
964861AG1-349 GEN
Solar/Wind Harmer
8.45
971917AH1-482 GEN
Solar/Wind Harmer
9.749
274682WAUKEGAN ;7U
Adder
19.309
274828WAUKEGAN ;BP
Adder
11.857
962781AG1-127 GEN
Solar/Wind Harmer
10.159
939401AE1-172 GEN
Solar/Wind Harmer
14.878
274872LEEDK;1U
Solar/Wind Harmer
8.755
276805AD2-038 GEN
Solar/Wind Harmer
5.468
276882AE2-255 GEN
Solar/Wind Harmer
3.584
971997AH1-543 GEN
Solar/Wind Harmer
16.713
965651AG1-433 GEN
Solar/Wind Harmer
5.786
940581AE2-045 GEN
Solar/Wind Harmer
10.785
971605AH1-302 GEN
Solar/Wind Harmer
9.222
274822ROCKFORD ;11
Adder
20.64
274761LEE CO EC;2U
Adder
9.664
274766LEE CO EC;7U
Adder
9.55
957471AF2-041 GEN
Solar/Wind Harmer
27.425
959081AF2-199 GEN
Solar/Wind Harmer
9.142
971067AG2-660 GEN
Solar/Wind Harmer
2.126
LAGNLTFEXP_LAGN->PJM
CLTF
12.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.04
TVALTFEXP_TVA->PJM
CLTF
5.56
NYPJM->LTFIMP_NY
CLTF
2.96
LGEELTFEXP_LGEE->PJM
CLTF
4.361
WECLTFEXP_WEC->PJM
CLTF
4.006
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.803
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.413
MECLTFEXP_MEC->PJM
CLTF
15.587
SIGELTFEXP_SIGE->PJM
CLTF
0.383
CPLELTFEXP_CPLE->PJM
CLTF
1.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.882

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.96 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4388.88
MW Contribution:
19.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.751
24642205MAYFLWER
50/50
0.042
944961AF1-161 GEN
50/50
3.287
962601AG1-109 GEN
50/50
3.287
274772LINCOLN ;3U
50/50
7.349
962771AG1-126 GEN
Solar/Wind Harmer
81.69
970153AG2-106 GEN
Solar/Wind Harmer
35.621
971347AH1-153 GEN
Solar/Wind Harmer
5.963
270043AE2-236 GEN
Solar/Wind Harmer
6.498
247643Z2-116 C
Solar/Wind Harmer
0.08
270063AE2-323 C
Solar/Wind Harmer
2.507
270505AE1-170 C O1
Solar/Wind Harmer
17.083
24441505OLIV SLR
Solar/Wind Harmer
0.152
945111AF1-176 GEN
Solar/Wind Harmer
6.424
965021AG1-366 GEN
Solar/Wind Harmer
2.635
944531AF1-118 GEN
Solar/Wind Harmer
39.384
274724RIVER EC ;11
Adder
19.633
972231SS25-0005
Solar/Wind Harmer
10.51
972181SS23-001
Solar/Wind Harmer
6.569
274752CRETE EC ;2U
Adder
5.413
274753CRETE EC ;3U
Adder
5.413
276164X3-005 C
Solar/Wind Harmer
0.776
274814UNIV PK N;0U
Adder
5.572
274807UNIV PK N;3U
Adder
5.56
274811UNIV PK N;7U
Adder
5.524
970707AG2-453 GEN
Solar/Wind Harmer
30.836
274803UNIV PARK;6U
Adder
6.406
274826FISK ;BP
Adder
12.028
972259AH1-714 GEN
Adder
20.952
274887GEN-1.85
Solar/Wind Harmer
5.85
276772AC2-154 GEN
Solar/Wind Harmer
3.064
276843GEN-1.7
Solar/Wind Harmer
0.629
276806AD2-047 C O1
Solar/Wind Harmer
11.746
972038AH1-567 GEN2
Adder
0.401
939351AE1-166 GEN
Solar/Wind Harmer
6.488
274676JOLIET 29;8U
Adder
32.293
274729ELWOOD EC;1P
Adder
17.91
274730ELWOOD EC;6P
Adder
17.911
274734ELWOOD EC;8P
Adder
17.911
274736ELWOOD EC;9P
Adder
17.911
943121AE2-341 GEN
Solar/Wind Harmer
16.274
943591AF1-030 GEN
Solar/Wind Harmer
10.849
964401AG1-302 GEN
Solar/Wind Harmer
9.752
274862TOP CROP ;2U
Solar/Wind Harmer
5.432
274682WAUKEGAN ;7U
Adder
19.288
276868AE1-113 GEN
Solar/Wind Harmer
10.74
274879MINONK ;1U
Solar/Wind Harmer
7.16
276799AD1-013 GEN
Solar/Wind Harmer
2.338
946671AF1-331 GEN
Solar/Wind Harmer
0.443
270102X2-052 ST
50/50
1.827
270100X2-052 CT1
50/50
1.688
270101X2-052 CT2
50/50
1.688
247620Y3-023
50/50
0.556
24643105BUCHANAN
50/50
0.014
274770LINCOLN ;1U
50/50
7.349
274771LINCOLN ;2U
50/50
7.349
970349AG2-230 GEN
Solar/Wind Harmer
17.888
965681AG1-436 GEN
Solar/Wind Harmer
14.235
965791AG1-447 GEN
Solar/Wind Harmer
7.283
961051AF2-396 GEN
Solar/Wind Harmer
17.978
961051AF2-396 GEN
Solar/Wind Harmer
8.362
270349AD2-093_GEN
Solar/Wind Harmer
4.041
270471AD2-092_GEN
Solar/Wind Harmer
4.041
274805UNIV PK N;1U
Adder
5.536
274808UNIV PK N;4U
Adder
5.499
274888KELLY CRK;1U
Solar/Wind Harmer
6.479
276776AD2-060 GEN
Solar/Wind Harmer
0.46
958011AF2-095 GEN
Solar/Wind Harmer
15.811
970941AG2-585 GEN
Solar/Wind Harmer
6.039
276897AD1-100 C
Solar/Wind Harmer
50.822
274674JOLIET 9 ;6U
Adder
16.786
276893AG1-478 C
Solar/Wind Harmer
0.477
270535AF1-215 GEN1
Solar/Wind Harmer
4.937
270536AF1-215 GEN2
Solar/Wind Harmer
4.937
274696ROCKY RD ;4P
Adder
12.245
274695ROCKY RD ;2P
Adder
11.963
274693ROCKY RD ;1P
Adder
11.846
274697ROCKY RD ;3P
Adder
3.25
958481AF2-142 GEN
Solar/Wind Harmer
16.115
274683WAUKEGAN ;8U
Adder
22.595
274683WAUKEGAN ;8U
Adder
19.046
962691AG1-118 GEN
Solar/Wind Harmer
32.07
960751AF2-366 GEN
Solar/Wind Harmer
3.062
24344105CKG2
50/50
9.132
270143AC1-141 CT2_
50/50
2.751
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.237
24307105BERRINSP G
50/50
0.024
274773LINCOLN ;4U
50/50
7.349
274774LINCOLN ;5U
50/50
7.349
962761AG1-125 GEN
Solar/Wind Harmer
81.69
970149AG2-104 GEN
Solar/Wind Harmer
50.443
970155AG2-107 GEN
Solar/Wind Harmer
35.621
270216AD2-079_GEN
Solar/Wind Harmer
0.694
957891AF2-083 GEN
Solar/Wind Harmer
17.068
945111AF1-176 GEN
Solar/Wind Harmer
20.27
965011AG1-365 GEN
Solar/Wind Harmer
11.331
270449AD2-020 GEN
Solar/Wind Harmer
3.169
943021AE2-325 GEN
Solar/Wind Harmer
4.118
972207SS24-0001
Solar/Wind Harmer
24.624
24441205WTRV SLR C
Solar/Wind Harmer
0.15
274723RIVER EC ;12
Adder
19.863
274751CRETE EC ;1U
Adder
5.413
274754CRETE EC ;4U
Adder
5.413
274812UNIV PK N;8U
Adder
5.524
970373AG2-245 GEN
Solar/Wind Harmer
23.133
274802UNIV PARK;5U
Adder
6.406
941551AE2-152 GEN
Solar/Wind Harmer
4.962
274676JOLIET 29;8U
Adder
33.489
274674JOLIET 9 ;6U
Adder
16.786
274732ELWOOD EC;7P
Adder
17.911
270055AF2-134 C O1
Solar/Wind Harmer
3.291
274871GR RIDGE ;2U
Solar/Wind Harmer
8.367
274847GR RIDGE ;BU
Solar/Wind Harmer
5.502
274745AC1-111 GEN9
Adder
6.056
958381AF2-132 GEN
Solar/Wind Harmer
9.752
276694AA1-018 GEN2
Solar/Wind Harmer
6.779
276691AA1-018 GEN1
Solar/Wind Harmer
0.81
274861TOP CROP ;1U
Solar/Wind Harmer
6.506
964861AG1-349 GEN
Solar/Wind Harmer
8.44
971917AH1-482 GEN
Solar/Wind Harmer
9.738
274682WAUKEGAN ;7U
Adder
19.288
274828WAUKEGAN ;BP
Adder
11.844
962781AG1-127 GEN
Solar/Wind Harmer
10.148
939401AE1-172 GEN
Solar/Wind Harmer
14.862
274872LEEDK;1U
Solar/Wind Harmer
8.746
276805AD2-038 GEN
Solar/Wind Harmer
5.462
276882AE2-255 GEN
Solar/Wind Harmer
3.58
971997AH1-543 GEN
Solar/Wind Harmer
16.695
965651AG1-433 GEN
Solar/Wind Harmer
5.782
940581AE2-045 GEN
Solar/Wind Harmer
10.773
971605AH1-302 GEN
Solar/Wind Harmer
9.211
274822ROCKFORD ;11
Adder
20.617
274761LEE CO EC;2U
Adder
9.653
274766LEE CO EC;7U
Adder
9.54
957471AF2-041 GEN
Solar/Wind Harmer
27.395
959081AF2-199 GEN
Solar/Wind Harmer
9.132
971067AG2-660 GEN
Solar/Wind Harmer
2.124
274855GSG-6 ;RU
Solar/Wind Harmer
3.906
274850MENDOTA H;RU
Solar/Wind Harmer
2.716
276602WESTBROOK C
Solar/Wind Harmer
2.248
274760LEE CO EC;1U
Adder
9.653
274767LEE CO EC;8U
Adder
9.54
24721905FLATG4
Adder
18.412
959091AF2-200 GEN
Solar/Wind Harmer
18.263
958491AF2-143 GEN
Solar/Wind Harmer
15.978
276901AD2-066 C O1
Solar/Wind Harmer
3.732
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.564
972235AH1-702 GEN1
Adder
2.643
972236AH1-702 GEN2
Adder
2.299
274764LEE CO EC;5U
Adder
9.676
274765LEE CO EC;6U
Adder
9.676
274762LEE CO EC;3U
Adder
9.653
274763LEE CO EC;4U
Adder
9.562
247621Y3-024
Adder
0.218
971341AH1-150 GEN
Solar/Wind Harmer
18.263
971343AH1-151 GEN
Solar/Wind Harmer
18.263
270144AC1-141 ST1_
50/50
2.429
24641605TWIN BRNCH
50/50
0.02
24344005CKG1
50/50
7.392
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.349
274776LINCOLN ;7U
50/50
7.349
274777LINCOLN ;8U
50/50
7.349
270071AF1-092 GEN
Solar/Wind Harmer
17.348
971771AH1-392 GEN
Solar/Wind Harmer
10.316
270526AF1-158 GEN
Solar/Wind Harmer
5.171
960681AF2-359 GEN
Solar/Wind Harmer
4.303
970031AG2-029 GEN
Solar/Wind Harmer
28.377
959331AF2-224 GEN
Solar/Wind Harmer
11.331
944161AF1-084 GEN
Solar/Wind Harmer
2.488
24729505KEY G4
Adder
7.184
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.524
960591AF2-350 GEN
Solar/Wind Harmer
10.98
274800UNIV PARK;3U
Adder
6.401
274801UNIV PARK;4U
Adder
6.401
972228AH1-698 GEN2
Adder
4.065
972227AH1-698 GEN1
Adder
2.862
274687WILL CNTY;4U
Adder
30.526
274687WILL CNTY;4U
Adder
30.526
274675JOLIET 29;7U
Adder
33.489
274675JOLIET 29;7U
Adder
32.293
274728ELWOOD EC;5P
Adder
17.911
274731ELWOOD EC;2P
Adder
17.91
274733ELWOOD EC;3P
Adder
17.91
274735ELWOOD EC;4P
Adder
17.91
276893AG1-478 C
Solar/Wind Harmer
0.599
970833AG2-524 GEN
Solar/Wind Harmer
9.504
970833AG2-524 GEN
Solar/Wind Harmer
4.42
274744AC1-111 GEN8
Adder
6.056
274746AC1-111 G10
Adder
6.056
958391AF2-133 GEN
Solar/Wind Harmer
9.688
970073AG2-061 GEN
Solar/Wind Harmer
2.477
959141AF2-205 GEN
Solar/Wind Harmer
6.427
971549AH1-272 GEN
Solar/Wind Harmer
19.646
965041AG1-368 GEN
Solar/Wind Harmer
10.596
958711AF2-162 GEN
Solar/Wind Harmer
1.07
971675AH1-338 GEN
Solar/Wind Harmer
19.045
971411AH1-196 GEN
Solar/Wind Harmer
15.871
276861AD2-134 GEN
Solar/Wind Harmer
1.889
276863AD2-134 GEN
Solar/Wind Harmer
1.889
274863CRW1-WTG
Solar/Wind Harmer
5.89
274864CRW2-WTG
Solar/Wind Harmer
5.89
274823ROCKFORD ;21
Adder
20.468
972267AH1-718 GEN
Adder
4.29
971171AH1-044 GEN
Solar/Wind Harmer
18.263
LAGNLTFEXP_LAGN->PJM
CLTF
12.197
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.031
TVALTFEXP_TVA->PJM
CLTF
5.555
NYPJM->LTFIMP_NY
CLTF
2.964
LGEELTFEXP_LGEE->PJM
CLTF
4.358
WECLTFEXP_WEC->PJM
CLTF
4.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.397
MECLTFEXP_MEC->PJM
CLTF
15.571
SIGELTFEXP_SIGE->PJM
CLTF
0.382
CPLELTFEXP_CPLE->PJM
CLTF
1.447
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.8

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.31 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5773.71
MW Contribution:
16.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
17.36
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274775LINCOLN ;6U
Adder
10.797
274776LINCOLN ;7U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
80.774
970149AG2-104 GEN
Solar/Wind Harmer
43.619
970155AG2-107 GEN
Solar/Wind Harmer
51.58
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
10.415
274754CRETE EC ;4U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
15.659
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
6.422
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
14.053
965681AG1-436 GEN
Solar/Wind Harmer
11.209
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
276776AD2-060 GEN
Solar/Wind Harmer
0.937
958011AF2-095 GEN
Solar/Wind Harmer
12.646
970941AG2-585 GEN
Solar/Wind Harmer
4.83
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
21.908
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.582
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
25.814
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.897
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.686
960611AF2-352 GEN
Solar/Wind Harmer
2.728
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.921
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
270031AE2-169
Solar/Wind Harmer
4.257
270599AE1-208 GEN
Solar/Wind Harmer
7.096
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
276911AD2-131_GEN
Solar/Wind Harmer
1.062
270246TR4_N_V150
Solar/Wind Harmer
0.049
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.284
270383AD1-128 GEN
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
970883AG2-550 GEN
Solar/Wind Harmer
6.689
970885AG2-551 GEN
Solar/Wind Harmer
2.23
270054AF2-122 C O1
Solar/Wind Helper
1.547
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
971347AH1-153 GEN
Solar/Wind Harmer
4.684
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274753CRETE EC ;3U
Adder
10.415
270505AE1-170 C O1
Solar/Wind Harmer
9.246
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
0.228
276843GEN-1.7
Solar/Wind Harmer
0.284
276806AD2-047 C O1
Solar/Wind Harmer
4.976
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
17.002
970571AG2-364 GEN
Solar/Wind Harmer
16.871
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
965931AG1-462 GEN
Solar/Wind Harmer
20.885
971087AG2-675 GEN
Solar/Wind Harmer
4.368
965091AG1-374 GEN
Solar/Wind Harmer
24.551
959611AF2-252 GEN
Solar/Wind Harmer
2.728
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.663
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
942481AE2-261 GEN
Solar/Wind Harmer
23.05
270004AE1-209 GEN
Solar/Wind Harmer
1.624
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24695305TIMB G C
Solar/Wind Harmer
0.627
970825AG2-519 GEN
Solar/Wind Harmer
5.579
946031AF1-268 GEN
Solar/Wind Harmer
6.994
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
5.989
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.434
970169AG2-114 GEN
Solar/Wind Harmer
8.435
971681AH1-341 GEN
Solar/Wind Harmer
13.557
972267AH1-718 GEN
Adder
4.986
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.677
946321AF1-296 GEN
Solar/Wind Harmer
4.601
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
10.858
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
971549AH1-272 GEN
Solar/Wind Harmer
16.367
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.859
970289AG2-191 GEN
Solar/Wind Harmer
1.486
971609AH1-304 GEN
Solar/Wind Harmer
1.264
247521TR3_G114
Solar/Wind Harmer
0.275
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.891
247536S-71 GEN
Solar/Wind Harmer
0.278
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971997AH1-543 GEN
Solar/Wind Harmer
4.485
957471AF2-041 GEN
Solar/Wind Harmer
25.504
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
965651AG1-433 GEN
Solar/Wind Harmer
2.449
276708O09 GEN2
Solar/Wind Harmer
0.295
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
965911AG1-460 GEN
Solar/Wind Harmer
1.542
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.459
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
965421AG1-410 GEN
Solar/Wind Harmer
21.55
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.196
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
972203AH1-686 GEN
Adder
1.998
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-3_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.01 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5074.41
MW Contribution:
13.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.482
24721905FLATG4
50/50
27.071
962771AG1-126 GEN
Solar/Wind Harmer
94.712
970153AG2-106 GEN
Solar/Wind Harmer
60.48
971347AH1-153 GEN
Solar/Wind Harmer
4.178
274772LINCOLN ;3U
Adder
9.435
270043AE2-236 GEN
Solar/Wind Harmer
4.934
274724RIVER EC ;11
Adder
19.46
970707AG2-453 GEN
Solar/Wind Harmer
25.034
274752CRETE EC ;2U
Adder
9.02
274753CRETE EC ;3U
Adder
9.02
972259AH1-714 GEN
Adder
20.849
274814UNIV PK N;0U
Adder
5.517
274807UNIV PK N;3U
Adder
5.505
274811UNIV PK N;7U
Adder
5.469
274826FISK ;BP
Adder
11.934
274887GEN-1.85
Solar/Wind Harmer
0.198
276843GEN-1.7
Solar/Wind Harmer
0.246
276806AD2-047 C O1
Solar/Wind Harmer
4.309
274803UNIV PARK;6U
Adder
6.353
24721705FLATG2
50/50
22.01
270102X2-052 ST
50/50
1.799
270100X2-052 CT1
50/50
1.662
270101X2-052 CT2
50/50
1.662
970349AG2-230 GEN
Solar/Wind Harmer
12.534
965681AG1-436 GEN
Solar/Wind Harmer
9.772
965791AG1-447 GEN
Solar/Wind Harmer
7.166
274770LINCOLN ;1U
Adder
9.435
274771LINCOLN ;2U
Adder
9.435
274805UNIV PK N;1U
Adder
5.481
274808UNIV PK N;4U
Adder
5.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.443
276776AD2-060 GEN
Solar/Wind Harmer
0.811
958011AF2-095 GEN
Solar/Wind Harmer
10.949
970941AG2-585 GEN
Solar/Wind Harmer
4.182
276897AD1-100 C
Solar/Wind Harmer
18.954
274674JOLIET 9 ;6U
Adder
16.661
276893AG1-478 C
Solar/Wind Harmer
0.502
961051AF2-396 GEN
Solar/Wind Harmer
14.985
961051AF2-396 GEN
Solar/Wind Harmer
9.99
274695ROCKY RD ;2P
Adder
11.868
274693ROCKY RD ;1P
Adder
11.751
274697ROCKY RD ;3P
Adder
3.224
274696ROCKY RD ;4P
Adder
12.148
274683WAUKEGAN ;8U
Adder
22.4
274683WAUKEGAN ;8U
Adder
18.882
958481AF2-142 GEN
Solar/Wind Harmer
11.121
247620Y3-023
Adder
0.489
962691AG1-118 GEN
Solar/Wind Harmer
22.185
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.011
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.533
971343AH1-151 GEN
Solar/Wind Harmer
14.533
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.613
972236AH1-702 GEN2
Adder
2.272
938861AE1-114 GEN
Solar/Wind Harmer
4.06
274764LEE CO EC;5U
Adder
9.547
24721805FLATG3
50/50
1.482
24344105CKG2
50/50
9.343
962761AG1-125 GEN
Solar/Wind Harmer
94.712
970149AG2-104 GEN
Solar/Wind Harmer
51.146
970155AG2-107 GEN
Solar/Wind Harmer
60.48
274773LINCOLN ;4U
Adder
9.435
274774LINCOLN ;5U
Adder
9.435
274723RIVER EC ;12
Adder
19.685
274751CRETE EC ;1U
Adder
9.02
274754CRETE EC ;4U
Adder
9.02
274812UNIV PK N;8U
Adder
5.469
274802UNIV PARK;5U
Adder
6.353
941551AE2-152 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
12.616
274676JOLIET 29;8U
Adder
33.244
274674JOLIET 9 ;6U
Adder
16.661
274732ELWOOD EC;7P
Adder
17.77
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
13.42
24639705ELKHART HY
Adder
0.165
274745AC1-111 GEN9
Adder
6.017
970373AG2-245 GEN
Solar/Wind Harmer
15.746
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.902
274682WAUKEGAN ;7U
Adder
19.124
274828WAUKEGAN ;BP
Adder
11.742
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.205
274861TOP CROP ;1U
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.023
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.495
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.854
971997AH1-543 GEN
Solar/Wind Harmer
3.836
958381AF2-132 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
21.8
959081AF2-199 GEN
Solar/Wind Harmer
7.267
971067AG2-660 GEN
Solar/Wind Harmer
2.422
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.444
274822ROCKFORD ;11
Adder
20.385
970819AG2-516 GEN
Solar/Wind Harmer
8.655
970569AG2-363 GEN
Solar/Wind Harmer
21.506
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.525
274766LEE CO EC;7U
Adder
9.413
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.899
972038AH1-567 GEN2
Adder
0.398
270505AE1-170 C O1
Solar/Wind Harmer
7.964
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.056
274729ELWOOD EC;1P
Adder
17.77
274730ELWOOD EC;6P
Adder
17.77
274734ELWOOD EC;8P
Adder
17.77
274736ELWOOD EC;9P
Adder
17.77
943121AE2-341 GEN
Solar/Wind Harmer
12.618
943591AF1-030 GEN
Solar/Wind Harmer
8.391
945111AF1-176 GEN
Solar/Wind Harmer
6.096
274682WAUKEGAN ;7U
Adder
19.124
274862TOP CROP ;2U
Solar/Wind Harmer
1
944531AF1-118 GEN
Solar/Wind Harmer
32.801
276868AE1-113 GEN
Solar/Wind Harmer
1.463
274879MINONK ;1U
Solar/Wind Harmer
0.305
946671AF1-331 GEN
Solar/Wind Harmer
0.78
274855GSG-6 ;RU
Solar/Wind Harmer
0.267
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959091AF2-200 GEN
Solar/Wind Harmer
14.533
270063AE2-323 C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
14.338
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.525
274767LEE CO EC;8U
Adder
9.413
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.234
965931AG1-462 GEN
Solar/Wind Harmer
17.553
971087AG2-675 GEN
Solar/Wind Harmer
3.671
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.861
965091AG1-374 GEN
Solar/Wind Harmer
20.448
959611AF2-252 GEN
Solar/Wind Harmer
2.272
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.994
965021AG1-366 GEN
Solar/Wind Harmer
2.095
957381AF2-032 GEN
Solar/Wind Harmer
1.409
942481AE2-261 GEN
Solar/Wind Harmer
18.543
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.665
270284AF1-227 GEN1
Solar/Wind Helper
2.373
270287AF1-227 GEN3
Solar/Wind Helper
0.87
960801AF2-371 GEN
Solar/Wind Helper
0.964
964871AG1-351 GEN
Solar/Wind Helper
0.665
24721605FLATG1
50/50
1.482
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
9.435
274776LINCOLN ;7U
Adder
9.435
274777LINCOLN ;8U
Adder
9.435
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
7.732
270071AF1-092 GEN
Solar/Wind Harmer
14.586
274827FISK ;RP
Adder
8.458
972228AH1-698 GEN2
Adder
4.038
972227AH1-698 GEN1
Adder
2.843
960591AF2-350 GEN
Solar/Wind Harmer
7.603
972037AH1-567 GEN1
Adder
0.199
274800UNIV PARK;3U
Adder
6.351
274801UNIV PARK;4U
Adder
6.351
274687WILL CNTY;4U
Adder
30.296
274687WILL CNTY;4U
Adder
30.296
274675JOLIET 29;7U
Adder
33.244
274675JOLIET 29;7U
Adder
32.057
970833AG2-524 GEN
Solar/Wind Harmer
8.297
970833AG2-524 GEN
Solar/Wind Harmer
5.531
274728ELWOOD EC;5P
Adder
17.77
274731ELWOOD EC;2P
Adder
17.77
274733ELWOOD EC;3P
Adder
17.77
274735ELWOOD EC;4P
Adder
17.77
274744AC1-111 GEN8
Adder
6.017
274746AC1-111 G10
Adder
6.017
970073AG2-061 GEN
Solar/Wind Harmer
2.447
971675AH1-338 GEN
Solar/Wind Harmer
2.85
971411AH1-196 GEN
Solar/Wind Harmer
10.959
276861AD2-134 GEN
Solar/Wind Harmer
0.13
276863AD2-134 GEN
Solar/Wind Harmer
0.13
971171AH1-044 GEN
Solar/Wind Harmer
14.533
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
20.237
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.168
959141AF2-205 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.219
971681AH1-341 GEN
Solar/Wind Harmer
11.539
24729505KEY G4
Adder
6.649
970169AG2-114 GEN
Solar/Wind Harmer
7.15
971611AH1-305 GEN
Solar/Wind Harmer
4.239
970031AG2-029 GEN
Solar/Wind Harmer
3.854
972267AH1-718 GEN
Adder
4.228
276741O09 GEN1
Solar/Wind Harmer
0.25
274877BISHOP HL;1U
Solar/Wind Harmer
0.234
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.266
946321AF1-296 GEN
Solar/Wind Harmer
3.872
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
13.514
276668AB2-070 GEN1
Solar/Wind Harmer
0.255
276848AB2-070 GEN3
Solar/Wind Harmer
0.254
276849AB2-070 GEN2
Solar/Wind Harmer
0.255
963841AG1-237 GEN
Solar/Wind Harmer
2.803
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.399
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.148
241955AC1-078 GEN
Solar/Wind Helper
2.298
241973AD2-163_GEN1
Solar/Wind Helper
1.862
241974AD2-163_GEN2
Solar/Wind Helper
1.862
945631AF1-228 GEN
Solar/Wind Helper
1.837
276708O09 GEN2
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.276
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.688
965651AG1-433 GEN
Solar/Wind Harmer
1.961
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.83
276621W2-048 GEN
Solar/Wind Harmer
0.32
963741AG1-226 GEN
Solar/Wind Harmer
14.933
965011AG1-365 GEN
Solar/Wind Harmer
6.284
945371AF1-202 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.24
270520AE2-214 GEN
Solar/Wind Helper
3.207
270286AF1-227 GEN2
Solar/Wind Helper
0.87
274765LEE CO EC;6U
Adder
9.547
274762LEE CO EC;3U
Adder
9.525
274763LEE CO EC;4U
Adder
9.435
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.14
276645AC1-214 GEN1
Solar/Wind Harmer
0.276
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.249
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.272
944541AF1-119 GEN
Solar/Wind Harmer
0.446
960971AF2-388 GEN
Solar/Wind Harmer
3.922
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.752
276615X2-022 GEN
Solar/Wind Harmer
0.066
276838X2-022 GEN2
Solar/Wind Harmer
0.36
970241AG2-163 GEN
Solar/Wind Harmer
3.681
276916AD2-100_GEN
Solar/Wind Harmer
12.928
276911AD2-131_GEN
Solar/Wind Harmer
0.852
942221AE2-234 GEN
Solar/Wind Harmer
2.468
970291AG2-192 GEN
Solar/Wind Harmer
0.785
970291AG2-192 GEN
Solar/Wind Harmer
0.362
270054AF2-122 C O1
Solar/Wind Helper
2.097
946101AF1-275 GEN
Solar/Wind Helper
0.802
270349AD2-093_GEN
Solar/Wind Helper
1.818
270471AD2-092_GEN
Solar/Wind Helper
1.818
253383AE2-342_GEN
Solar/Wind Helper
0.854
241960AC2-195 GEN
Solar/Wind Helper
1.419
LAGNLTFEXP_LAGN->PJM
CLTF
11.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.139
TVALTFEXP_TVA->PJM
CLTF
5.225
NYPJM->LTFIMP_NY
CLTF
2.454
LGEELTFEXP_LGEE->PJM
CLTF
3.221
WECLTFEXP_WEC->PJM
CLTF
3.955
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
114.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.259
MECLTFEXP_MEC->PJM
CLTF
15.133
SIGELTFEXP_SIGE->PJM
CLTF
0.321
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.92

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.62 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4476.89
MW Contribution:
14.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.617
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
9.616
944961AF1-161 GEN
50/50
3.109
962601AG1-109 GEN
50/50
3.109
962771AG1-126 GEN
Solar/Wind Harmer
74.627
970153AG2-106 GEN
Solar/Wind Harmer
47.655
971347AH1-153 GEN
Solar/Wind Harmer
4.014
270043AE2-236 GEN
Solar/Wind Harmer
5.048
270505AE1-170 C O1
Solar/Wind Harmer
7.914
270063AE2-323 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.088
944531AF1-118 GEN
Solar/Wind Harmer
33.371
274724RIVER EC ;11
Adder
18.817
274752CRETE EC ;2U
Adder
8.738
274753CRETE EC ;3U
Adder
8.738
965021AG1-366 GEN
Solar/Wind Harmer
2.462
970707AG2-453 GEN
Solar/Wind Harmer
24.09
270102X2-052 ST
50/50
1.749
270100X2-052 CT1
50/50
1.616
270101X2-052 CT2
50/50
1.616
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.526
274770LINCOLN ;1U
50/50
9.616
274771LINCOLN ;2U
50/50
9.616
970349AG2-230 GEN
Solar/Wind Harmer
12.041
965681AG1-436 GEN
Solar/Wind Harmer
9.504
965791AG1-447 GEN
Solar/Wind Harmer
6.97
961051AF2-396 GEN
Solar/Wind Harmer
14.959
961051AF2-396 GEN
Solar/Wind Harmer
9.973
274805UNIV PK N;1U
Adder
5.303
274808UNIV PK N;4U
Adder
5.268
274888KELLY CRK;1U
Solar/Wind Harmer
0.428
276776AD2-060 GEN
Solar/Wind Harmer
0.783
958011AF2-095 GEN
Solar/Wind Harmer
10.572
970941AG2-585 GEN
Solar/Wind Harmer
4.038
276897AD1-100 C
Solar/Wind Harmer
18.287
274674JOLIET 9 ;6U
Adder
16.082
276893AG1-478 C
Solar/Wind Harmer
0.485
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
11.454
274693ROCKY RD ;1P
Adder
11.341
274697ROCKY RD ;3P
Adder
3.111
274696ROCKY RD ;4P
Adder
11.724
958481AF2-142 GEN
Solar/Wind Harmer
10.754
274683WAUKEGAN ;8U
Adder
21.627
274683WAUKEGAN ;8U
Adder
18.23
962691AG1-118 GEN
Solar/Wind Harmer
21.414
958491AF2-143 GEN
Solar/Wind Harmer
10.655
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.045
971343AH1-151 GEN
Solar/Wind Harmer
14.045
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.526
972236AH1-702 GEN2
Adder
2.196
938861AE1-114 GEN
Solar/Wind Harmer
3.928
944541AF1-119 GEN
Solar/Wind Harmer
0.462
960971AF2-388 GEN
Solar/Wind Harmer
4.056
274764LEE CO EC;5U
Adder
9.237
274765LEE CO EC;6U
Adder
9.237
274762LEE CO EC;3U
Adder
9.215
274763LEE CO EC;4U
Adder
9.128
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.104
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.191
942221AE2-234 GEN
Solar/Wind Harmer
2.684
960611AF2-352 GEN
Solar/Wind Harmer
2.217
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.745
944231AF1-091 GEN
Solar/Wind Harmer
15.08
270246TR4_N_V150
Solar/Wind Harmer
0.042
270247TR4_N_V136
Solar/Wind Harmer
0.042
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.669
970291AG2-192 GEN
Solar/Wind Harmer
0.817
970291AG2-192 GEN
Solar/Wind Harmer
0.377
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.353
270031AE2-169
Solar/Wind Harmer
3.44
270599AE1-208 GEN
Solar/Wind Harmer
5.734
971613AH1-306 GEN
Solar/Wind Harmer
2.966
276916AD2-100_GEN
Solar/Wind Harmer
12.749
276911AD2-131_GEN
Solar/Wind Harmer
0.84
246937BC-WTG2
Solar/Wind Harmer
0.244
270054AF2-122 C O1
Solar/Wind Helper
1.656
270144AC1-141 ST1_
50/50
2.311
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.028
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.616
274776LINCOLN ;7U
50/50
9.616
274777LINCOLN ;8U
50/50
9.616
270071AF1-092 GEN
Solar/Wind Harmer
14.768
971771AH1-392 GEN
Solar/Wind Harmer
7.622
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
4.047
959331AF2-224 GEN
Solar/Wind Harmer
5.169
274827FISK ;RP
Adder
8.169
972037AH1-567 GEN1
Adder
0.193
960591AF2-350 GEN
Solar/Wind Harmer
7.341
274800UNIV PARK;3U
Adder
6.134
274801UNIV PARK;4U
Adder
6.134
972228AH1-698 GEN2
Adder
3.896
972227AH1-698 GEN1
Adder
2.744
24729505KEY G4
Adder
6.793
274687WILL CNTY;4U
Adder
29.249
274687WILL CNTY;4U
Adder
29.249
274675JOLIET 29;7U
Adder
32.088
274675JOLIET 29;7U
Adder
30.942
274728ELWOOD EC;5P
Adder
17.157
274731ELWOOD EC;2P
Adder
17.157
274733ELWOOD EC;3P
Adder
17.157
274735ELWOOD EC;4P
Adder
17.157
970833AG2-524 GEN
Solar/Wind Harmer
8.005
970833AG2-524 GEN
Solar/Wind Harmer
5.336
274744AC1-111 GEN8
Adder
5.803
274746AC1-111 G10
Adder
5.803
970073AG2-061 GEN
Solar/Wind Harmer
2.368
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.753
971411AH1-196 GEN
Solar/Wind Harmer
10.588
276861AD2-134 GEN
Solar/Wind Harmer
0.126
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
14.045
274823ROCKFORD ;21
Adder
19.56
971611AH1-305 GEN
Solar/Wind Harmer
4.163
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
926823AC1-168 GEN
Solar/Wind Harmer
1.181
970169AG2-114 GEN
Solar/Wind Harmer
6.939
971681AH1-341 GEN
Solar/Wind Harmer
11.162
972267AH1-718 GEN
Adder
4.093
276741O09 GEN1
Solar/Wind Harmer
0.242
971549AH1-272 GEN
Solar/Wind Harmer
14.066
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
9.126
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.079
965041AG1-368 GEN
Solar/Wind Harmer
6.739
946321AF1-296 GEN
Solar/Wind Harmer
3.754
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.235
965051AG1-369 GEN
Solar/Wind Harmer
3.245
963841AG1-237 GEN
Solar/Wind Harmer
2.784
276668AB2-070 GEN1
Solar/Wind Harmer
0.25
276848AB2-070 GEN3
Solar/Wind Harmer
0.249
276849AB2-070 GEN2
Solar/Wind Harmer
0.25
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.194
971609AH1-304 GEN
Solar/Wind Harmer
1.022
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.766
274814UNIV PK N;0U
Adder
5.338
274807UNIV PK N;3U
Adder
5.326
274811UNIV PK N;7U
Adder
5.291
972259AH1-714 GEN
Adder
20.093
274826FISK ;BP
Adder
11.527
274803UNIV PARK;6U
Adder
6.138
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.237
276806AD2-047 C O1
Solar/Wind Harmer
4.16
972038AH1-567 GEN2
Adder
0.384
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.942
274729ELWOOD EC;1P
Adder
17.157
274730ELWOOD EC;6P
Adder
17.157
274734ELWOOD EC;8P
Adder
17.157
274736ELWOOD EC;9P
Adder
17.157
943121AE2-341 GEN
Solar/Wind Harmer
12.163
943591AF1-030 GEN
Solar/Wind Harmer
8.088
274682WAUKEGAN ;7U
Adder
18.463
274862TOP CROP ;2U
Solar/Wind Harmer
0.968
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.416
274879MINONK ;1U
Solar/Wind Harmer
0.295
946671AF1-331 GEN
Solar/Wind Harmer
0.753
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
959091AF2-200 GEN
Solar/Wind Harmer
14.045
970571AG2-364 GEN
Solar/Wind Harmer
13.895
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.215
274767LEE CO EC;8U
Adder
9.107
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
24690905MDL-1G C
Solar/Wind Harmer
0
24721905FLATG4
Adder
19.661
970781AG2-491 GEN
Solar/Wind Harmer
6.766
965931AG1-462 GEN
Solar/Wind Harmer
17.022
971087AG2-675 GEN
Solar/Wind Harmer
3.56
965091AG1-374 GEN
Solar/Wind Harmer
19.952
959611AF2-252 GEN
Solar/Wind Harmer
2.217
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
971993AH1-541 GEN
Solar/Wind Harmer
2.938
24695305TIMB G C
Solar/Wind Harmer
0.537
970289AG2-191 GEN
Solar/Wind Harmer
0.691
957381AF2-032 GEN
Solar/Wind Harmer
1.388
942481AE2-261 GEN
Solar/Wind Harmer
18.271
246938BC-WTG3
Solar/Wind Harmer
0.218
270491AE1-102 GEN2
Solar/Wind Harmer
0.786
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24344105CKG2
50/50
8.859
270143AC1-141 CT2_
50/50
2.617
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.55
274773LINCOLN ;4U
50/50
9.616
274774LINCOLN ;5U
50/50
9.616
962761AG1-125 GEN
Solar/Wind Harmer
74.627
970149AG2-104 GEN
Solar/Wind Harmer
40.3
970155AG2-107 GEN
Solar/Wind Harmer
47.655
957891AF2-083 GEN
Solar/Wind Harmer
12.55
945111AF1-176 GEN
Solar/Wind Harmer
13.401
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.895
274723RIVER EC ;12
Adder
19.037
274751CRETE EC ;1U
Adder
8.738
274754CRETE EC ;4U
Adder
8.738
965011AG1-365 GEN
Solar/Wind Harmer
7.385
274812UNIV PK N;8U
Adder
5.291
274802UNIV PARK;5U
Adder
6.138
970373AG2-245 GEN
Solar/Wind Harmer
15.385
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.088
274674JOLIET 9 ;6U
Adder
16.082
274732ELWOOD EC;7P
Adder
17.157
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.803
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.165
274682WAUKEGAN ;7U
Adder
18.463
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
11.336
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.78
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.257
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.318
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.826
971997AH1-543 GEN
Solar/Wind Harmer
3.71
957471AF2-041 GEN
Solar/Wind Harmer
21.068
959081AF2-199 GEN
Solar/Wind Harmer
7.023
971067AG2-660 GEN
Solar/Wind Harmer
2.341
274822ROCKFORD ;11
Adder
19.703
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.741
970819AG2-516 GEN
Solar/Wind Harmer
8.368
970569AG2-363 GEN
Solar/Wind Harmer
20.843
965651AG1-433 GEN
Solar/Wind Harmer
2.028
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.215
274766LEE CO EC;7U
Adder
9.107
276708O09 GEN2
Solar/Wind Harmer
0.242
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
958861AF2-177 GEN
Solar/Wind Harmer
2.941
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.439
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
14.886
276621W2-048 GEN
Solar/Wind Harmer
0.314
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
6.922
270032AE2-172
Solar/Wind Harmer
4.12
965421AG1-410 GEN
Solar/Wind Harmer
18.52
965911AG1-460 GEN
Solar/Wind Harmer
1.222
246936BC-WTG1
Solar/Wind Harmer
0.244
270489AE1-102 GEN1
Solar/Wind Harmer
0.786
276903AD2-071 C
Solar/Wind Harmer
6.725
LAGNLTFEXP_LAGN->PJM
CLTF
11.281
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.712
TVALTFEXP_TVA->PJM
CLTF
5.082
NYPJM->LTFIMP_NY
CLTF
2.583
LGEELTFEXP_LGEE->PJM
CLTF
3.675
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.237
AH1-155LTFEXP_AH1-155->PJM
LTF
0.356
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.267
MECLTFEXP_MEC->PJM
CLTF
14.733
SIGELTFEXP_SIGE->PJM
CLTF
0.34
CPLELTFEXP_CPLE->PJM
CLTF
1.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.349

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.08 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4940.32
MW Contribution:
19.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.775
24642205MAYFLWER
50/50
0.042
944961AF1-161 GEN
50/50
3.309
962601AG1-109 GEN
50/50
3.309
274772LINCOLN ;3U
50/50
7.418
962771AG1-126 GEN
Solar/Wind Harmer
89.226
970153AG2-106 GEN
Solar/Wind Harmer
38.907
971347AH1-153 GEN
Solar/Wind Harmer
6.05
270043AE2-236 GEN
Solar/Wind Harmer
6.529
247643Z2-116 C
Solar/Wind Harmer
0.08
24441505OLIV SLR
Solar/Wind Harmer
0.154
270505AE1-170 C O1
Solar/Wind Harmer
17.214
945111AF1-176 GEN
Solar/Wind Harmer
6.468
270063AE2-323 C
Solar/Wind Harmer
2.513
965021AG1-366 GEN
Solar/Wind Harmer
2.608
944531AF1-118 GEN
Solar/Wind Harmer
39.173
274724RIVER EC ;11
Adder
19.791
972231SS25-0005
Solar/Wind Harmer
10.591
972181SS23-001
Solar/Wind Harmer
6.619
274752CRETE EC ;2U
Adder
5.455
274753CRETE EC ;3U
Adder
5.455
276164X3-005 C
Solar/Wind Harmer
0.782
274814UNIV PK N;0U
Adder
5.614
274807UNIV PK N;3U
Adder
5.602
274811UNIV PK N;7U
Adder
5.565
970707AG2-453 GEN
Solar/Wind Harmer
31.089
274803UNIV PARK;6U
Adder
6.454
274826FISK ;BP
Adder
12.118
972259AH1-714 GEN
Adder
21.114
274887GEN-1.85
Solar/Wind Harmer
5.893
276772AC2-154 GEN
Solar/Wind Harmer
3.087
276843GEN-1.7
Solar/Wind Harmer
0.634
276806AD2-047 C O1
Solar/Wind Harmer
11.833
972038AH1-567 GEN2
Adder
0.404
939351AE1-166 GEN
Solar/Wind Harmer
6.535
274676JOLIET 29;8U
Adder
32.523
274729ELWOOD EC;1P
Adder
18.034
274730ELWOOD EC;6P
Adder
18.034
274734ELWOOD EC;8P
Adder
18.034
274736ELWOOD EC;9P
Adder
18.034
943121AE2-341 GEN
Solar/Wind Harmer
16.387
943591AF1-030 GEN
Solar/Wind Harmer
10.925
274862TOP CROP ;2U
Solar/Wind Harmer
5.462
274682WAUKEGAN ;7U
Adder
19.404
964401AG1-302 GEN
Solar/Wind Harmer
9.773
276868AE1-113 GEN
Solar/Wind Harmer
10.789
274879MINONK ;1U
Solar/Wind Harmer
7.193
276799AD1-013 GEN
Solar/Wind Harmer
2.35
946671AF1-331 GEN
Solar/Wind Harmer
0.445
274855GSG-6 ;RU
Solar/Wind Harmer
3.925
274850MENDOTA H;RU
Solar/Wind Harmer
2.729
276602WESTBROOK C
Solar/Wind Harmer
2.259
959091AF2-200 GEN
Solar/Wind Harmer
21.158
274760LEE CO EC;1U
Adder
9.686
274767LEE CO EC;8U
Adder
9.572
24721905FLATG4
Adder
19.928
24344105CKG2
50/50
9.299
270143AC1-141 CT2_
50/50
2.775
24639705ELKHART HY
50/50
0.187
970521AG2-332 GEN
50/50
13.311
24307105BERRINSP G
50/50
0.024
274773LINCOLN ;4U
50/50
7.418
274774LINCOLN ;5U
50/50
7.418
962761AG1-125 GEN
Solar/Wind Harmer
89.226
970149AG2-104 GEN
Solar/Wind Harmer
55.097
970155AG2-107 GEN
Solar/Wind Harmer
38.907
270216AD2-079_GEN
Solar/Wind Harmer
0.699
957891AF2-083 GEN
Solar/Wind Harmer
17.194
945111AF1-176 GEN
Solar/Wind Harmer
20.409
270449AD2-020 GEN
Solar/Wind Harmer
3.19
943021AE2-325 GEN
Solar/Wind Harmer
4.145
972207SS24-0001
Solar/Wind Harmer
24.857
24441205WTRV SLR C
Solar/Wind Harmer
0.151
965011AG1-365 GEN
Solar/Wind Harmer
11.213
274723RIVER EC ;12
Adder
20.022
274751CRETE EC ;1U
Adder
5.455
274754CRETE EC ;4U
Adder
5.455
274812UNIV PK N;8U
Adder
5.565
970373AG2-245 GEN
Solar/Wind Harmer
23.253
274802UNIV PARK;5U
Adder
6.454
941551AE2-152 GEN
Solar/Wind Harmer
4.997
274676JOLIET 29;8U
Adder
33.727
274674JOLIET 9 ;6U
Adder
16.903
274732ELWOOD EC;7P
Adder
18.034
274871GR RIDGE ;2U
Solar/Wind Harmer
8.425
274847GR RIDGE ;BU
Solar/Wind Harmer
5.54
270055AF2-134 C O1
Solar/Wind Harmer
3.304
274745AC1-111 GEN9
Adder
6.097
276694AA1-018 GEN2
Solar/Wind Harmer
6.817
276691AA1-018 GEN1
Solar/Wind Harmer
0.815
274861TOP CROP ;1U
Solar/Wind Harmer
6.542
274682WAUKEGAN ;7U
Adder
19.404
274828WAUKEGAN ;BP
Adder
11.914
958381AF2-132 GEN
Solar/Wind Harmer
9.773
964861AG1-349 GEN
Solar/Wind Harmer
8.457
971917AH1-482 GEN
Solar/Wind Harmer
9.757
962781AG1-127 GEN
Solar/Wind Harmer
10.205
274872LEEDK;1U
Solar/Wind Harmer
8.794
939401AE1-172 GEN
Solar/Wind Harmer
14.927
276805AD2-038 GEN
Solar/Wind Harmer
5.489
276882AE2-255 GEN
Solar/Wind Harmer
3.596
971997AH1-543 GEN
Solar/Wind Harmer
16.77
957471AF2-041 GEN
Solar/Wind Harmer
31.738
959081AF2-199 GEN
Solar/Wind Harmer
10.579
971067AG2-660 GEN
Solar/Wind Harmer
2.46
940581AE2-045 GEN
Solar/Wind Harmer
10.772
971605AH1-302 GEN
Solar/Wind Harmer
9.211
274822ROCKFORD ;11
Adder
20.708
274761LEE CO EC;2U
Adder
9.686
274766LEE CO EC;7U
Adder
9.572
970819AG2-516 GEN
Solar/Wind Harmer
7.613
270144AC1-141 ST1_
50/50
2.451
24344005CKG1
50/50
7.462
24641605TWIN BRNCH
50/50
0.02
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.418
274776LINCOLN ;7U
50/50
7.418
274777LINCOLN ;8U
50/50
7.418
270071AF1-092 GEN
Solar/Wind Harmer
17.395
971771AH1-392 GEN
Solar/Wind Harmer
10.406
270526AF1-158 GEN
Solar/Wind Harmer
5.216
960681AF2-359 GEN
Solar/Wind Harmer
4.343
970031AG2-029 GEN
Solar/Wind Harmer
28.389
944161AF1-084 GEN
Solar/Wind Harmer
2.504
959331AF2-224 GEN
Solar/Wind Harmer
11.213
972037AH1-567 GEN1
Adder
0.203
274827FISK ;RP
Adder
8.588
960591AF2-350 GEN
Solar/Wind Harmer
11.061
274800UNIV PARK;3U
Adder
6.448
274801UNIV PARK;4U
Adder
6.448
972228AH1-698 GEN2
Adder
4.095
972227AH1-698 GEN1
Adder
2.884
274687WILL CNTY;4U
Adder
30.745
274687WILL CNTY;4U
Adder
30.745
274675JOLIET 29;7U
Adder
33.728
274675JOLIET 29;7U
Adder
32.523
24729505KEY G4
Adder
7.126
274728ELWOOD EC;5P
Adder
18.034
274731ELWOOD EC;2P
Adder
18.034
274733ELWOOD EC;3P
Adder
18.034
274735ELWOOD EC;4P
Adder
18.034
276893AG1-478 C
Solar/Wind Harmer
0.603
970833AG2-524 GEN
Solar/Wind Harmer
9.569
970833AG2-524 GEN
Solar/Wind Harmer
4.451
274744AC1-111 GEN8
Adder
6.097
274746AC1-111 G10
Adder
6.097
970073AG2-061 GEN
Solar/Wind Harmer
2.489
958391AF2-133 GEN
Solar/Wind Harmer
9.701
959141AF2-205 GEN
Solar/Wind Harmer
6.431
971675AH1-338 GEN
Solar/Wind Harmer
19.139
971411AH1-196 GEN
Solar/Wind Harmer
15.949
276861AD2-134 GEN
Solar/Wind Harmer
1.898
276863AD2-134 GEN
Solar/Wind Harmer
1.898
971549AH1-272 GEN
Solar/Wind Harmer
19.629
274863CRW1-WTG
Solar/Wind Harmer
5.908
274864CRW2-WTG
Solar/Wind Harmer
5.908
971171AH1-044 GEN
Solar/Wind Harmer
21.158
276889AE2-281 GEN
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
20.558
972267AH1-718 GEN
Adder
4.302
270102X2-052 ST
50/50
1.845
270100X2-052 CT1
50/50
1.705
270101X2-052 CT2
50/50
1.705
24643105BUCHANAN
50/50
0.015
247620Y3-023
50/50
0.558
274770LINCOLN ;1U
50/50
7.418
274771LINCOLN ;2U
50/50
7.418
970349AG2-230 GEN
Solar/Wind Harmer
18.149
965681AG1-436 GEN
Solar/Wind Harmer
14.368
965791AG1-447 GEN
Solar/Wind Harmer
7.351
961051AF2-396 GEN
Solar/Wind Harmer
18.101
961051AF2-396 GEN
Solar/Wind Harmer
8.419
274805UNIV PK N;1U
Adder
5.578
274808UNIV PK N;4U
Adder
5.541
274888KELLY CRK;1U
Solar/Wind Harmer
6.527
276776AD2-060 GEN
Solar/Wind Harmer
0.463
958011AF2-095 GEN
Solar/Wind Harmer
15.928
970941AG2-585 GEN
Solar/Wind Harmer
6.084
276897AD1-100 C
Solar/Wind Harmer
51.184
274674JOLIET 9 ;6U
Adder
16.903
276893AG1-478 C
Solar/Wind Harmer
0.481
270535AF1-215 GEN1
Solar/Wind Harmer
4.956
270536AF1-215 GEN2
Solar/Wind Harmer
4.956
274695ROCKY RD ;2P
Adder
12.037
274693ROCKY RD ;1P
Adder
11.918
274697ROCKY RD ;3P
Adder
3.27
274696ROCKY RD ;4P
Adder
12.321
958481AF2-142 GEN
Solar/Wind Harmer
16.205
274683WAUKEGAN ;8U
Adder
22.729
274683WAUKEGAN ;8U
Adder
19.16
962691AG1-118 GEN
Solar/Wind Harmer
32.255
960751AF2-366 GEN
Solar/Wind Harmer
3.079
958491AF2-143 GEN
Solar/Wind Harmer
16.055
276901AD2-066 C O1
Solar/Wind Harmer
3.749
971341AH1-150 GEN
Solar/Wind Harmer
21.158
971343AH1-151 GEN
Solar/Wind Harmer
21.158
276872AE1-163_GEN1
Solar/Wind Harmer
7.094
276876AE1-163_GEN2
Solar/Wind Harmer
7.094
972235AH1-702 GEN1
Adder
2.655
972236AH1-702 GEN2
Adder
2.308
274764LEE CO EC;5U
Adder
9.709
274765LEE CO EC;6U
Adder
9.709
274762LEE CO EC;3U
Adder
9.686
274763LEE CO EC;4U
Adder
9.595
270054AF2-122 C O1
Solar/Wind Helper
1.626
LAGNLTFEXP_LAGN->PJM
CLTF
11.862
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.972
TVALTFEXP_TVA->PJM
CLTF
5.346
NYPJM->LTFIMP_NY
CLTF
2.82
LGEELTFEXP_LGEE->PJM
CLTF
3.91
WECLTFEXP_WEC->PJM
CLTF
4.019
AG2-052LTFEXP_AG2-052->PJM
LTF
0.25
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.31
MECLTFEXP_MEC->PJM
CLTF
15.493
SIGELTFEXP_SIGE->PJM
CLTF
0.36
CPLELTFEXP_CPLE->PJM
CLTF
1.484
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.994

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-030_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.85 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4929.67
MW Contribution:
19.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.77
24642205MAYFLWER
50/50
0.042
944961AF1-161 GEN
50/50
3.302
962601AG1-109 GEN
50/50
3.302
274772LINCOLN ;3U
50/50
7.408
962771AG1-126 GEN
Solar/Wind Harmer
89.224
970153AG2-106 GEN
Solar/Wind Harmer
38.906
971347AH1-153 GEN
Solar/Wind Harmer
6.04
270043AE2-236 GEN
Solar/Wind Harmer
6.521
247643Z2-116 C
Solar/Wind Harmer
0.08
24441505OLIV SLR
Solar/Wind Harmer
0.153
270505AE1-170 C O1
Solar/Wind Harmer
17.179
945111AF1-176 GEN
Solar/Wind Harmer
6.455
270063AE2-323 C
Solar/Wind Harmer
2.509
965021AG1-366 GEN
Solar/Wind Harmer
2.605
944531AF1-118 GEN
Solar/Wind Harmer
39.134
274724RIVER EC ;11
Adder
19.762
972231SS25-0005
Solar/Wind Harmer
10.575
972181SS23-001
Solar/Wind Harmer
6.609
274752CRETE EC ;2U
Adder
5.447
274753CRETE EC ;3U
Adder
5.447
276164X3-005 C
Solar/Wind Harmer
0.781
274814UNIV PK N;0U
Adder
5.606
274807UNIV PK N;3U
Adder
5.594
274811UNIV PK N;7U
Adder
5.557
970707AG2-453 GEN
Solar/Wind Harmer
31.045
274803UNIV PARK;6U
Adder
6.445
274826FISK ;BP
Adder
12.101
972259AH1-714 GEN
Adder
21.083
274887GEN-1.85
Solar/Wind Harmer
5.885
276772AC2-154 GEN
Solar/Wind Harmer
3.082
276843GEN-1.7
Solar/Wind Harmer
0.633
24344105CKG2
50/50
9.285
270143AC1-141 CT2_
50/50
2.77
24639705ELKHART HY
50/50
0.187
970521AG2-332 GEN
50/50
13.287
24307105BERRINSP G
50/50
0.024
274773LINCOLN ;4U
50/50
7.408
274774LINCOLN ;5U
50/50
7.408
962761AG1-125 GEN
Solar/Wind Harmer
89.224
970149AG2-104 GEN
Solar/Wind Harmer
55.096
970155AG2-107 GEN
Solar/Wind Harmer
38.906
270216AD2-079_GEN
Solar/Wind Harmer
0.698
957891AF2-083 GEN
Solar/Wind Harmer
17.16
945111AF1-176 GEN
Solar/Wind Harmer
20.368
270449AD2-020 GEN
Solar/Wind Harmer
3.183
943021AE2-325 GEN
Solar/Wind Harmer
4.137
972207SS24-0001
Solar/Wind Harmer
24.822
965011AG1-365 GEN
Solar/Wind Harmer
11.202
24441205WTRV SLR C
Solar/Wind Harmer
0.151
274723RIVER EC ;12
Adder
19.993
274751CRETE EC ;1U
Adder
5.447
274754CRETE EC ;4U
Adder
5.447
274812UNIV PK N;8U
Adder
5.557
970373AG2-245 GEN
Solar/Wind Harmer
23.216
274802UNIV PARK;5U
Adder
6.445
941551AE2-152 GEN
Solar/Wind Harmer
4.99
274676JOLIET 29;8U
Adder
33.678
274674JOLIET 9 ;6U
Adder
16.879
274732ELWOOD EC;7P
Adder
18.008
274871GR RIDGE ;2U
Solar/Wind Harmer
8.413
274847GR RIDGE ;BU
Solar/Wind Harmer
5.532
270055AF2-134 C O1
Solar/Wind Harmer
3.298
274745AC1-111 GEN9
Adder
6.089
276694AA1-018 GEN2
Solar/Wind Harmer
6.807
276691AA1-018 GEN1
Solar/Wind Harmer
0.814
274861TOP CROP ;1U
Solar/Wind Harmer
6.532
274682WAUKEGAN ;7U
Adder
19.377
274828WAUKEGAN ;BP
Adder
11.897
958381AF2-132 GEN
Solar/Wind Harmer
9.758
964861AG1-349 GEN
Solar/Wind Harmer
8.444
971917AH1-482 GEN
Solar/Wind Harmer
9.742
962781AG1-127 GEN
Solar/Wind Harmer
10.19
274872LEEDK;1U
Solar/Wind Harmer
8.781
939401AE1-172 GEN
Solar/Wind Harmer
14.906
276805AD2-038 GEN
Solar/Wind Harmer
5.481
276882AE2-255 GEN
Solar/Wind Harmer
3.591
971997AH1-543 GEN
Solar/Wind Harmer
16.746
957471AF2-041 GEN
Solar/Wind Harmer
31.693
959081AF2-199 GEN
Solar/Wind Harmer
10.564
971067AG2-660 GEN
Solar/Wind Harmer
2.457
940581AE2-045 GEN
Solar/Wind Harmer
10.756
971605AH1-302 GEN
Solar/Wind Harmer
9.197
274822ROCKFORD ;11
Adder
20.679
274761LEE CO EC;2U
Adder
9.672
274766LEE CO EC;7U
Adder
9.558
970819AG2-516 GEN
Solar/Wind Harmer
7.602
270144AC1-141 ST1_
50/50
2.446
24344005CKG1
50/50
7.447
24641605TWIN BRNCH
50/50
0.02
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.408
274776LINCOLN ;7U
50/50
7.408
274777LINCOLN ;8U
50/50
7.408
270071AF1-092 GEN
Solar/Wind Harmer
17.376
971771AH1-392 GEN
Solar/Wind Harmer
10.387
270526AF1-158 GEN
Solar/Wind Harmer
5.207
960681AF2-359 GEN
Solar/Wind Harmer
4.336
970031AG2-029 GEN
Solar/Wind Harmer
28.344
944161AF1-084 GEN
Solar/Wind Harmer
2.498
959331AF2-224 GEN
Solar/Wind Harmer
11.202
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.576
960591AF2-350 GEN
Solar/Wind Harmer
11.045
274800UNIV PARK;3U
Adder
6.439
274801UNIV PARK;4U
Adder
6.439
972228AH1-698 GEN2
Adder
4.089
972227AH1-698 GEN1
Adder
2.879
274687WILL CNTY;4U
Adder
30.7
274687WILL CNTY;4U
Adder
30.7
274675JOLIET 29;7U
Adder
33.679
274675JOLIET 29;7U
Adder
32.476
24729505KEY G4
Adder
7.119
274728ELWOOD EC;5P
Adder
18.008
274731ELWOOD EC;2P
Adder
18.008
274733ELWOOD EC;3P
Adder
18.008
274735ELWOOD EC;4P
Adder
18.008
276893AG1-478 C
Solar/Wind Harmer
0.602
970833AG2-524 GEN
Solar/Wind Harmer
9.556
970833AG2-524 GEN
Solar/Wind Harmer
4.444
274744AC1-111 GEN8
Adder
6.089
274746AC1-111 G10
Adder
6.089
970073AG2-061 GEN
Solar/Wind Harmer
2.486
958391AF2-133 GEN
Solar/Wind Harmer
9.686
270102X2-052 ST
50/50
1.842
270100X2-052 CT1
50/50
1.702
270101X2-052 CT2
50/50
1.702
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.557
274770LINCOLN ;1U
50/50
7.408
274771LINCOLN ;2U
50/50
7.408
970349AG2-230 GEN
Solar/Wind Harmer
18.121
965681AG1-436 GEN
Solar/Wind Harmer
14.345
965791AG1-447 GEN
Solar/Wind Harmer
7.339
961051AF2-396 GEN
Solar/Wind Harmer
18.063
961051AF2-396 GEN
Solar/Wind Harmer
8.401
274805UNIV PK N;1U
Adder
5.569
274808UNIV PK N;4U
Adder
5.533
274888KELLY CRK;1U
Solar/Wind Harmer
6.518
276776AD2-060 GEN
Solar/Wind Harmer
0.462
958011AF2-095 GEN
Solar/Wind Harmer
15.905
970941AG2-585 GEN
Solar/Wind Harmer
6.075
276897AD1-100 C
Solar/Wind Harmer
51.111
274674JOLIET 9 ;6U
Adder
16.879
276893AG1-478 C
Solar/Wind Harmer
0.48
270535AF1-215 GEN1
Solar/Wind Harmer
4.948
270536AF1-215 GEN2
Solar/Wind Harmer
4.948
274695ROCKY RD ;2P
Adder
12.019
274693ROCKY RD ;1P
Adder
11.901
274697ROCKY RD ;3P
Adder
3.265
274696ROCKY RD ;4P
Adder
12.303
958481AF2-142 GEN
Solar/Wind Harmer
16.182
274683WAUKEGAN ;8U
Adder
22.697
274683WAUKEGAN ;8U
Adder
19.132
962691AG1-118 GEN
Solar/Wind Harmer
32.209
960751AF2-366 GEN
Solar/Wind Harmer
3.074
958491AF2-143 GEN
Solar/Wind Harmer
16.032
276901AD2-066 C O1
Solar/Wind Harmer
3.744
971341AH1-150 GEN
Solar/Wind Harmer
21.128
971343AH1-151 GEN
Solar/Wind Harmer
21.128
276872AE1-163_GEN1
Solar/Wind Harmer
7.084
276876AE1-163_GEN2
Solar/Wind Harmer
7.084
972235AH1-702 GEN1
Adder
2.651
972236AH1-702 GEN2
Adder
2.305
274764LEE CO EC;5U
Adder
9.695
274765LEE CO EC;6U
Adder
9.695
274762LEE CO EC;3U
Adder
9.672
274763LEE CO EC;4U
Adder
9.581
270054AF2-122 C O1
Solar/Wind Helper
1.625
276806AD2-047 C O1
Solar/Wind Harmer
11.816
972038AH1-567 GEN2
Adder
0.403
939351AE1-166 GEN
Solar/Wind Harmer
6.525
274676JOLIET 29;8U
Adder
32.476
274729ELWOOD EC;1P
Adder
18.008
274730ELWOOD EC;6P
Adder
18.008
274734ELWOOD EC;8P
Adder
18.008
274736ELWOOD EC;9P
Adder
18.008
943121AE2-341 GEN
Solar/Wind Harmer
16.364
943591AF1-030 GEN
Solar/Wind Harmer
10.909
274862TOP CROP ;2U
Solar/Wind Harmer
5.454
274682WAUKEGAN ;7U
Adder
19.377
964401AG1-302 GEN
Solar/Wind Harmer
9.758
276868AE1-113 GEN
Solar/Wind Harmer
10.774
274879MINONK ;1U
Solar/Wind Harmer
7.183
276799AD1-013 GEN
Solar/Wind Harmer
2.347
946671AF1-331 GEN
Solar/Wind Harmer
0.445
274855GSG-6 ;RU
Solar/Wind Harmer
3.919
274850MENDOTA H;RU
Solar/Wind Harmer
2.725
276602WESTBROOK C
Solar/Wind Harmer
2.256
959091AF2-200 GEN
Solar/Wind Harmer
21.128
274760LEE CO EC;1U
Adder
9.672
274767LEE CO EC;8U
Adder
9.558
24721905FLATG4
Adder
19.926
959141AF2-205 GEN
Solar/Wind Harmer
6.422
971411AH1-196 GEN
Solar/Wind Harmer
15.927
971675AH1-338 GEN
Solar/Wind Harmer
19.112
276861AD2-134 GEN
Solar/Wind Harmer
1.895
276863AD2-134 GEN
Solar/Wind Harmer
1.895
971549AH1-272 GEN
Solar/Wind Harmer
19.563
274863CRW1-WTG
Solar/Wind Harmer
5.9
274864CRW2-WTG
Solar/Wind Harmer
5.9
971171AH1-044 GEN
Solar/Wind Harmer
21.128
276889AE2-281 GEN
Solar/Wind Harmer
2.024
274823ROCKFORD ;21
Adder
20.529
972267AH1-718 GEN
Adder
4.296
LAGNLTFEXP_LAGN->PJM
CLTF
11.847
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.962
TVALTFEXP_TVA->PJM
CLTF
5.339
NYPJM->LTFIMP_NY
CLTF
2.822
LGEELTFEXP_LGEE->PJM
CLTF
3.906
WECLTFEXP_WEC->PJM
CLTF
4.013
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.285
MECLTFEXP_MEC->PJM
CLTF
15.472
SIGELTFEXP_SIGE->PJM
CLTF
0.359
CPLELTFEXP_CPLE->PJM
CLTF
1.481
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.877

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P2-2_#5063_05SBERWI 345_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#5063_05SBERWI 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.09 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4757.98
MW Contribution:
18.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.692
24642205MAYFLWER
50/50
0.041
944961AF1-161 GEN
50/50
3.206
962601AG1-109 GEN
50/50
3.206
274772LINCOLN ;3U
50/50
7.202
962771AG1-126 GEN
Solar/Wind Harmer
88.136
970153AG2-106 GEN
Solar/Wind Harmer
38.432
971347AH1-153 GEN
Solar/Wind Harmer
5.88
270043AE2-236 GEN
Solar/Wind Harmer
6.356
247643Z2-116 C
Solar/Wind Harmer
0.078
24441505OLIV SLR
Solar/Wind Harmer
0.149
270505AE1-170 C O1
Solar/Wind Harmer
16.687
270063AE2-323 C
Solar/Wind Harmer
2.441
945111AF1-176 GEN
Solar/Wind Harmer
6.27
965021AG1-366 GEN
Solar/Wind Harmer
2.544
944531AF1-118 GEN
Solar/Wind Harmer
38.069
274724RIVER EC ;11
Adder
19.208
972231SS25-0005
Solar/Wind Harmer
10.278
972181SS23-001
Solar/Wind Harmer
6.423
274752CRETE EC ;2U
Adder
5.293
274753CRETE EC ;3U
Adder
5.293
276164X3-005 C
Solar/Wind Harmer
0.759
274814UNIV PK N;0U
Adder
5.448
274807UNIV PK N;3U
Adder
5.436
274811UNIV PK N;7U
Adder
5.401
970707AG2-453 GEN
Solar/Wind Harmer
30.174
274803UNIV PARK;6U
Adder
6.263
274826FISK ;BP
Adder
11.759
972259AH1-714 GEN
Adder
20.49
274887GEN-1.85
Solar/Wind Harmer
5.719
276772AC2-154 GEN
Solar/Wind Harmer
2.995
276843GEN-1.7
Solar/Wind Harmer
0.615
276806AD2-047 C O1
Solar/Wind Harmer
11.483
972038AH1-567 GEN2
Adder
0.392
939351AE1-166 GEN
Solar/Wind Harmer
6.341
274676JOLIET 29;8U
Adder
31.556
274729ELWOOD EC;1P
Adder
17.497
274730ELWOOD EC;6P
Adder
17.497
274734ELWOOD EC;8P
Adder
17.497
274736ELWOOD EC;9P
Adder
17.497
943121AE2-341 GEN
Solar/Wind Harmer
15.9
943591AF1-030 GEN
Solar/Wind Harmer
10.6
274862TOP CROP ;2U
Solar/Wind Harmer
5.298
274682WAUKEGAN ;7U
Adder
18.822
964401AG1-302 GEN
Solar/Wind Harmer
9.472
276868AE1-113 GEN
Solar/Wind Harmer
10.462
274879MINONK ;1U
Solar/Wind Harmer
6.975
276799AD1-013 GEN
Solar/Wind Harmer
2.279
946671AF1-331 GEN
Solar/Wind Harmer
0.432
274855GSG-6 ;RU
Solar/Wind Harmer
3.806
274850MENDOTA H;RU
Solar/Wind Harmer
2.646
276602WESTBROOK C
Solar/Wind Harmer
2.191
959091AF2-200 GEN
Solar/Wind Harmer
20.516
274760LEE CO EC;1U
Adder
9.389
274767LEE CO EC;8U
Adder
9.278
24721905FLATG4
Adder
19.422
270102X2-052 ST
50/50
1.791
270100X2-052 CT1
50/50
1.655
270101X2-052 CT2
50/50
1.655
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.542
274770LINCOLN ;1U
50/50
7.202
274771LINCOLN ;2U
50/50
7.202
970349AG2-230 GEN
Solar/Wind Harmer
17.64
965681AG1-436 GEN
Solar/Wind Harmer
13.944
965791AG1-447 GEN
Solar/Wind Harmer
7.134
961051AF2-396 GEN
Solar/Wind Harmer
17.54
961051AF2-396 GEN
Solar/Wind Harmer
8.158
274805UNIV PK N;1U
Adder
5.412
274808UNIV PK N;4U
Adder
5.377
274888KELLY CRK;1U
Solar/Wind Harmer
6.334
276776AD2-060 GEN
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
15.457
970941AG2-585 GEN
Solar/Wind Harmer
5.904
276897AD1-100 C
Solar/Wind Harmer
49.665
274674JOLIET 9 ;6U
Adder
16.401
276893AG1-478 C
Solar/Wind Harmer
0.466
270535AF1-215 GEN1
Solar/Wind Harmer
4.804
270536AF1-215 GEN2
Solar/Wind Harmer
4.804
274696ROCKY RD ;4P
Adder
11.951
274695ROCKY RD ;2P
Adder
11.676
274693ROCKY RD ;1P
Adder
11.561
274697ROCKY RD ;3P
Adder
3.172
958481AF2-142 GEN
Solar/Wind Harmer
15.718
274683WAUKEGAN ;8U
Adder
22.047
274683WAUKEGAN ;8U
Adder
18.585
962691AG1-118 GEN
Solar/Wind Harmer
31.285
960751AF2-366 GEN
Solar/Wind Harmer
2.986
958491AF2-143 GEN
Solar/Wind Harmer
15.569
276901AD2-066 C O1
Solar/Wind Harmer
3.636
971341AH1-150 GEN
Solar/Wind Harmer
20.516
971343AH1-151 GEN
Solar/Wind Harmer
20.516
276872AE1-163_GEN1
Solar/Wind Harmer
6.878
276876AE1-163_GEN2
Solar/Wind Harmer
6.878
972235AH1-702 GEN1
Adder
2.574
972236AH1-702 GEN2
Adder
2.238
274764LEE CO EC;5U
Adder
9.411
274765LEE CO EC;6U
Adder
9.411
274762LEE CO EC;3U
Adder
9.389
274763LEE CO EC;4U
Adder
9.301
270054AF2-122 C O1
Solar/Wind Helper
1.705
24344105CKG2
50/50
9.043
270143AC1-141 CT2_
50/50
2.692
24639705ELKHART HY
50/50
0.181
970521AG2-332 GEN
50/50
12.915
274773LINCOLN ;4U
50/50
7.202
274774LINCOLN ;5U
50/50
7.202
24307105BERRINSP G
50/50
0.024
962761AG1-125 GEN
Solar/Wind Harmer
88.136
970149AG2-104 GEN
Solar/Wind Harmer
54.424
970155AG2-107 GEN
Solar/Wind Harmer
38.432
270216AD2-079_GEN
Solar/Wind Harmer
0.678
957891AF2-083 GEN
Solar/Wind Harmer
16.669
945111AF1-176 GEN
Solar/Wind Harmer
19.785
270449AD2-020 GEN
Solar/Wind Harmer
3.091
943021AE2-325 GEN
Solar/Wind Harmer
4.016
972207SS24-0001
Solar/Wind Harmer
24.133
965011AG1-365 GEN
Solar/Wind Harmer
10.941
24441205WTRV SLR C
Solar/Wind Harmer
0.146
274723RIVER EC ;12
Adder
19.432
274751CRETE EC ;1U
Adder
5.293
274754CRETE EC ;4U
Adder
5.293
274812UNIV PK N;8U
Adder
5.401
274802UNIV PARK;5U
Adder
6.263
970373AG2-245 GEN
Solar/Wind Harmer
22.549
941551AE2-152 GEN
Solar/Wind Harmer
4.849
274676JOLIET 29;8U
Adder
32.725
274674JOLIET 9 ;6U
Adder
16.401
274732ELWOOD EC;7P
Adder
17.497
274871GR RIDGE ;2U
Solar/Wind Harmer
8.174
274847GR RIDGE ;BU
Solar/Wind Harmer
5.375
270055AF2-134 C O1
Solar/Wind Harmer
3.203
274745AC1-111 GEN9
Adder
5.916
276694AA1-018 GEN2
Solar/Wind Harmer
6.612
276691AA1-018 GEN1
Solar/Wind Harmer
0.79
274861TOP CROP ;1U
Solar/Wind Harmer
6.345
274682WAUKEGAN ;7U
Adder
18.822
274828WAUKEGAN ;BP
Adder
11.557
958381AF2-132 GEN
Solar/Wind Harmer
9.472
964861AG1-349 GEN
Solar/Wind Harmer
8.196
971917AH1-482 GEN
Solar/Wind Harmer
9.456
962781AG1-127 GEN
Solar/Wind Harmer
9.898
274872LEEDK;1U
Solar/Wind Harmer
8.529
939401AE1-172 GEN
Solar/Wind Harmer
14.475
276805AD2-038 GEN
Solar/Wind Harmer
5.323
276882AE2-255 GEN
Solar/Wind Harmer
3.487
971997AH1-543 GEN
Solar/Wind Harmer
16.261
957471AF2-041 GEN
Solar/Wind Harmer
30.774
959081AF2-199 GEN
Solar/Wind Harmer
10.258
971067AG2-660 GEN
Solar/Wind Harmer
2.386
940581AE2-045 GEN
Solar/Wind Harmer
10.436
971605AH1-302 GEN
Solar/Wind Harmer
8.924
274822ROCKFORD ;11
Adder
20.078
274761LEE CO EC;2U
Adder
9.389
274766LEE CO EC;7U
Adder
9.278
970819AG2-516 GEN
Solar/Wind Harmer
7.381
270144AC1-141 ST1_
50/50
2.377
24344005CKG1
50/50
7.233
24641605TWIN BRNCH
50/50
0.019
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.202
274776LINCOLN ;7U
50/50
7.202
274777LINCOLN ;8U
50/50
7.202
270071AF1-092 GEN
Solar/Wind Harmer
16.926
971771AH1-392 GEN
Solar/Wind Harmer
10.096
270526AF1-158 GEN
Solar/Wind Harmer
5.06
960681AF2-359 GEN
Solar/Wind Harmer
4.215
970031AG2-029 GEN
Solar/Wind Harmer
27.586
944161AF1-084 GEN
Solar/Wind Harmer
2.425
959331AF2-224 GEN
Solar/Wind Harmer
10.941
972037AH1-567 GEN1
Adder
0.197
274827FISK ;RP
Adder
8.334
960591AF2-350 GEN
Solar/Wind Harmer
10.734
274800UNIV PARK;3U
Adder
6.257
274801UNIV PARK;4U
Adder
6.257
972228AH1-698 GEN2
Adder
3.974
972227AH1-698 GEN1
Adder
2.798
274687WILL CNTY;4U
Adder
29.832
274687WILL CNTY;4U
Adder
29.832
24729505KEY G4
Adder
6.921
274675JOLIET 29;7U
Adder
32.726
274675JOLIET 29;7U
Adder
31.557
274728ELWOOD EC;5P
Adder
17.497
274731ELWOOD EC;2P
Adder
17.497
274733ELWOOD EC;3P
Adder
17.497
274735ELWOOD EC;4P
Adder
17.497
276893AG1-478 C
Solar/Wind Harmer
0.585
970833AG2-524 GEN
Solar/Wind Harmer
9.285
970833AG2-524 GEN
Solar/Wind Harmer
4.318
274744AC1-111 GEN8
Adder
5.916
274746AC1-111 G10
Adder
5.916
970073AG2-061 GEN
Solar/Wind Harmer
2.414
958391AF2-133 GEN
Solar/Wind Harmer
9.401
971675AH1-338 GEN
Solar/Wind Harmer
18.559
971411AH1-196 GEN
Solar/Wind Harmer
15.466
276861AD2-134 GEN
Solar/Wind Harmer
1.84
276863AD2-134 GEN
Solar/Wind Harmer
1.84
959141AF2-205 GEN
Solar/Wind Harmer
6.232
274863CRW1-WTG
Solar/Wind Harmer
5.728
274864CRW2-WTG
Solar/Wind Harmer
5.728
971171AH1-044 GEN
Solar/Wind Harmer
20.516
276889AE2-281 GEN
Solar/Wind Harmer
1.965
274823ROCKFORD ;21
Adder
19.933
971549AH1-272 GEN
Solar/Wind Harmer
18.905
972267AH1-718 GEN
Adder
4.17
LAGNLTFEXP_LAGN->PJM
CLTF
11.364
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.562
TVALTFEXP_TVA->PJM
CLTF
5.102
NYPJM->LTFIMP_NY
CLTF
2.62
LGEELTFEXP_LGEE->PJM
CLTF
3.696
WECLTFEXP_WEC->PJM
CLTF
3.896
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.976
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.348
MECLTFEXP_MEC->PJM
CLTF
14.982
SIGELTFEXP_SIGE->PJM
CLTF
0.344
CPLELTFEXP_CPLE->PJM
CLTF
1.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
88.313

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5774.92
MW Contribution:
16.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
80.774
970149AG2-104 GEN
Solar/Wind Harmer
43.619
970155AG2-107 GEN
Solar/Wind Harmer
51.58
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
10.415
274754CRETE EC ;4U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
14.053
965681AG1-436 GEN
Solar/Wind Harmer
11.209
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
276776AD2-060 GEN
Solar/Wind Harmer
0.937
958011AF2-095 GEN
Solar/Wind Harmer
12.646
970941AG2-585 GEN
Solar/Wind Harmer
4.83
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
21.908
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.582
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
945111AF1-176 GEN
Solar/Wind Harmer
15.659
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
0
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
971347AH1-153 GEN
Solar/Wind Harmer
4.684
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274753CRETE EC ;3U
Adder
10.415
270505AE1-170 C O1
Solar/Wind Harmer
9.246
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
0.228
276843GEN-1.7
Solar/Wind Harmer
0.284
276806AD2-047 C O1
Solar/Wind Harmer
4.976
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
17.002
970571AG2-364 GEN
Solar/Wind Harmer
16.871
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
965931AG1-462 GEN
Solar/Wind Harmer
20.885
971087AG2-675 GEN
Solar/Wind Harmer
4.368
965091AG1-374 GEN
Solar/Wind Harmer
24.551
959611AF2-252 GEN
Solar/Wind Harmer
2.728
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.663
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
942481AE2-261 GEN
Solar/Wind Harmer
23.05
270004AE1-209 GEN
Solar/Wind Harmer
1.624
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24695305TIMB G C
Solar/Wind Harmer
0.627
970825AG2-519 GEN
Solar/Wind Harmer
5.579
946031AF1-268 GEN
Solar/Wind Harmer
6.994
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
17.36
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274775LINCOLN ;6U
Adder
10.797
274776LINCOLN ;7U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
5.989
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.434
970169AG2-114 GEN
Solar/Wind Harmer
8.435
971681AH1-341 GEN
Solar/Wind Harmer
13.557
972267AH1-718 GEN
Adder
4.986
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.677
946321AF1-296 GEN
Solar/Wind Harmer
4.601
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
10.858
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
971549AH1-272 GEN
Solar/Wind Harmer
16.367
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.859
970289AG2-191 GEN
Solar/Wind Harmer
1.486
971609AH1-304 GEN
Solar/Wind Harmer
1.264
247521TR3_G114
Solar/Wind Harmer
0.275
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.891
247536S-71 GEN
Solar/Wind Harmer
0.278
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
6.422
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971997AH1-543 GEN
Solar/Wind Harmer
4.485
957471AF2-041 GEN
Solar/Wind Harmer
25.504
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
965651AG1-433 GEN
Solar/Wind Harmer
2.449
276708O09 GEN2
Solar/Wind Harmer
0.295
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
965911AG1-460 GEN
Solar/Wind Harmer
1.542
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.459
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
965421AG1-410 GEN
Solar/Wind Harmer
21.55
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.196
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
972203AH1-686 GEN
Adder
1.998
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
25.814
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.897
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.686
960611AF2-352 GEN
Solar/Wind Harmer
2.728
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.921
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
270031AE2-169
Solar/Wind Harmer
4.257
270599AE1-208 GEN
Solar/Wind Harmer
7.096
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
276911AD2-131_GEN
Solar/Wind Harmer
1.062
270246TR4_N_V150
Solar/Wind Harmer
0.049
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.284
270383AD1-128 GEN
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
970883AG2-550 GEN
Solar/Wind Harmer
6.689
970885AG2-551 GEN
Solar/Wind Harmer
2.23
270054AF2-122 C O1
Solar/Wind Helper
1.547
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-3_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.24 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5084.88
MW Contribution:
13.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.482
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
9.435
274776LINCOLN ;7U
Adder
9.435
274777LINCOLN ;8U
Adder
9.435
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
7.732
270071AF1-092 GEN
Solar/Wind Harmer
14.586
274827FISK ;RP
Adder
8.458
972228AH1-698 GEN2
Adder
4.038
972227AH1-698 GEN1
Adder
2.843
960591AF2-350 GEN
Solar/Wind Harmer
7.603
972037AH1-567 GEN1
Adder
0.199
274800UNIV PARK;3U
Adder
6.351
274801UNIV PARK;4U
Adder
6.351
274687WILL CNTY;4U
Adder
30.296
274687WILL CNTY;4U
Adder
30.296
274675JOLIET 29;7U
Adder
33.244
274675JOLIET 29;7U
Adder
32.057
970833AG2-524 GEN
Solar/Wind Harmer
8.297
970833AG2-524 GEN
Solar/Wind Harmer
5.531
274728ELWOOD EC;5P
Adder
17.77
274731ELWOOD EC;2P
Adder
17.77
274733ELWOOD EC;3P
Adder
17.77
274735ELWOOD EC;4P
Adder
17.77
274744AC1-111 GEN8
Adder
6.017
274746AC1-111 G10
Adder
6.017
970073AG2-061 GEN
Solar/Wind Harmer
2.447
971675AH1-338 GEN
Solar/Wind Harmer
2.85
971411AH1-196 GEN
Solar/Wind Harmer
10.959
276861AD2-134 GEN
Solar/Wind Harmer
0.13
276863AD2-134 GEN
Solar/Wind Harmer
0.13
971171AH1-044 GEN
Solar/Wind Harmer
14.533
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
20.237
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.168
959141AF2-205 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.219
971681AH1-341 GEN
Solar/Wind Harmer
11.539
24729505KEY G4
Adder
6.649
970169AG2-114 GEN
Solar/Wind Harmer
7.15
971611AH1-305 GEN
Solar/Wind Harmer
4.239
970031AG2-029 GEN
Solar/Wind Harmer
3.854
972267AH1-718 GEN
Adder
4.228
276741O09 GEN1
Solar/Wind Harmer
0.25
24721805FLATG3
50/50
1.482
24344105CKG2
50/50
9.343
962761AG1-125 GEN
Solar/Wind Harmer
94.712
970149AG2-104 GEN
Solar/Wind Harmer
51.146
970155AG2-107 GEN
Solar/Wind Harmer
60.48
274773LINCOLN ;4U
Adder
9.435
274774LINCOLN ;5U
Adder
9.435
274723RIVER EC ;12
Adder
19.685
274751CRETE EC ;1U
Adder
9.02
274754CRETE EC ;4U
Adder
9.02
274812UNIV PK N;8U
Adder
5.469
274802UNIV PARK;5U
Adder
6.353
941551AE2-152 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
12.616
274676JOLIET 29;8U
Adder
33.244
274674JOLIET 9 ;6U
Adder
16.661
274732ELWOOD EC;7P
Adder
17.77
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
13.42
24639705ELKHART HY
Adder
0.165
274745AC1-111 GEN9
Adder
6.017
970373AG2-245 GEN
Solar/Wind Harmer
15.746
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.902
274682WAUKEGAN ;7U
Adder
19.124
274828WAUKEGAN ;BP
Adder
11.742
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.205
274861TOP CROP ;1U
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.023
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.495
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.854
971997AH1-543 GEN
Solar/Wind Harmer
3.836
958381AF2-132 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
21.8
959081AF2-199 GEN
Solar/Wind Harmer
7.267
971067AG2-660 GEN
Solar/Wind Harmer
2.422
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.444
274822ROCKFORD ;11
Adder
20.385
970819AG2-516 GEN
Solar/Wind Harmer
8.655
970569AG2-363 GEN
Solar/Wind Harmer
21.506
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.525
274766LEE CO EC;7U
Adder
9.413
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.899
276708O09 GEN2
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.276
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.688
965651AG1-433 GEN
Solar/Wind Harmer
1.961
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.83
276621W2-048 GEN
Solar/Wind Harmer
0.32
963741AG1-226 GEN
Solar/Wind Harmer
14.933
965011AG1-365 GEN
Solar/Wind Harmer
6.284
945371AF1-202 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.24
270520AE2-214 GEN
Solar/Wind Helper
3.207
270286AF1-227 GEN2
Solar/Wind Helper
0.87
24722005FLATG5
50/50
1.482
24721905FLATG4
50/50
27.071
962771AG1-126 GEN
Solar/Wind Harmer
94.712
970153AG2-106 GEN
Solar/Wind Harmer
60.48
971347AH1-153 GEN
Solar/Wind Harmer
4.178
274772LINCOLN ;3U
Adder
9.435
270043AE2-236 GEN
Solar/Wind Harmer
4.934
274724RIVER EC ;11
Adder
19.46
970707AG2-453 GEN
Solar/Wind Harmer
25.034
274752CRETE EC ;2U
Adder
9.02
274753CRETE EC ;3U
Adder
9.02
972259AH1-714 GEN
Adder
20.849
274814UNIV PK N;0U
Adder
5.517
274807UNIV PK N;3U
Adder
5.505
274811UNIV PK N;7U
Adder
5.469
274826FISK ;BP
Adder
11.934
274887GEN-1.85
Solar/Wind Harmer
0.198
276843GEN-1.7
Solar/Wind Harmer
0.246
276806AD2-047 C O1
Solar/Wind Harmer
4.309
274803UNIV PARK;6U
Adder
6.353
972038AH1-567 GEN2
Adder
0.398
270505AE1-170 C O1
Solar/Wind Harmer
7.964
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.056
274729ELWOOD EC;1P
Adder
17.77
274730ELWOOD EC;6P
Adder
17.77
274734ELWOOD EC;8P
Adder
17.77
274736ELWOOD EC;9P
Adder
17.77
943121AE2-341 GEN
Solar/Wind Harmer
12.618
943591AF1-030 GEN
Solar/Wind Harmer
8.391
945111AF1-176 GEN
Solar/Wind Harmer
6.096
274682WAUKEGAN ;7U
Adder
19.124
274862TOP CROP ;2U
Solar/Wind Harmer
1
944531AF1-118 GEN
Solar/Wind Harmer
32.801
276868AE1-113 GEN
Solar/Wind Harmer
1.463
274879MINONK ;1U
Solar/Wind Harmer
0.305
946671AF1-331 GEN
Solar/Wind Harmer
0.78
274855GSG-6 ;RU
Solar/Wind Harmer
0.267
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959091AF2-200 GEN
Solar/Wind Harmer
14.533
270063AE2-323 C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
14.338
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.525
274767LEE CO EC;8U
Adder
9.413
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.234
965931AG1-462 GEN
Solar/Wind Harmer
17.553
971087AG2-675 GEN
Solar/Wind Harmer
3.671
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.861
965091AG1-374 GEN
Solar/Wind Harmer
20.448
959611AF2-252 GEN
Solar/Wind Harmer
2.272
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.994
965021AG1-366 GEN
Solar/Wind Harmer
2.095
957381AF2-032 GEN
Solar/Wind Harmer
1.409
942481AE2-261 GEN
Solar/Wind Harmer
18.543
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.665
270284AF1-227 GEN1
Solar/Wind Helper
2.373
270287AF1-227 GEN3
Solar/Wind Helper
0.87
960801AF2-371 GEN
Solar/Wind Helper
0.964
964871AG1-351 GEN
Solar/Wind Helper
0.665
24721705FLATG2
50/50
22.01
270102X2-052 ST
50/50
1.799
270100X2-052 CT1
50/50
1.662
270101X2-052 CT2
50/50
1.662
970349AG2-230 GEN
Solar/Wind Harmer
12.534
965681AG1-436 GEN
Solar/Wind Harmer
9.772
965791AG1-447 GEN
Solar/Wind Harmer
7.166
274770LINCOLN ;1U
Adder
9.435
274771LINCOLN ;2U
Adder
9.435
274805UNIV PK N;1U
Adder
5.481
274808UNIV PK N;4U
Adder
5.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.443
276776AD2-060 GEN
Solar/Wind Harmer
0.811
958011AF2-095 GEN
Solar/Wind Harmer
10.949
970941AG2-585 GEN
Solar/Wind Harmer
4.182
276897AD1-100 C
Solar/Wind Harmer
18.954
274674JOLIET 9 ;6U
Adder
16.661
276893AG1-478 C
Solar/Wind Harmer
0.502
961051AF2-396 GEN
Solar/Wind Harmer
14.985
961051AF2-396 GEN
Solar/Wind Harmer
9.99
274695ROCKY RD ;2P
Adder
11.868
274693ROCKY RD ;1P
Adder
11.751
274697ROCKY RD ;3P
Adder
3.224
274696ROCKY RD ;4P
Adder
12.148
274683WAUKEGAN ;8U
Adder
22.4
274683WAUKEGAN ;8U
Adder
18.882
958481AF2-142 GEN
Solar/Wind Harmer
11.121
247620Y3-023
Adder
0.489
962691AG1-118 GEN
Solar/Wind Harmer
22.185
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.011
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.533
971343AH1-151 GEN
Solar/Wind Harmer
14.533
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.613
972236AH1-702 GEN2
Adder
2.272
938861AE1-114 GEN
Solar/Wind Harmer
4.06
274764LEE CO EC;5U
Adder
9.547
274765LEE CO EC;6U
Adder
9.547
274762LEE CO EC;3U
Adder
9.525
274763LEE CO EC;4U
Adder
9.435
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.14
276645AC1-214 GEN1
Solar/Wind Harmer
0.276
274877BISHOP HL;1U
Solar/Wind Harmer
0.234
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.266
946321AF1-296 GEN
Solar/Wind Harmer
3.872
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
13.514
276668AB2-070 GEN1
Solar/Wind Harmer
0.255
276848AB2-070 GEN3
Solar/Wind Harmer
0.254
276849AB2-070 GEN2
Solar/Wind Harmer
0.255
963841AG1-237 GEN
Solar/Wind Harmer
2.803
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.399
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.148
241955AC1-078 GEN
Solar/Wind Helper
2.298
241973AD2-163_GEN1
Solar/Wind Helper
1.862
241974AD2-163_GEN2
Solar/Wind Helper
1.862
945631AF1-228 GEN
Solar/Wind Helper
1.837
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.249
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.272
944541AF1-119 GEN
Solar/Wind Harmer
0.446
960971AF2-388 GEN
Solar/Wind Harmer
3.922
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.752
276615X2-022 GEN
Solar/Wind Harmer
0.066
276838X2-022 GEN2
Solar/Wind Harmer
0.36
970241AG2-163 GEN
Solar/Wind Harmer
3.681
276916AD2-100_GEN
Solar/Wind Harmer
12.928
276911AD2-131_GEN
Solar/Wind Harmer
0.852
942221AE2-234 GEN
Solar/Wind Harmer
2.468
970291AG2-192 GEN
Solar/Wind Harmer
0.785
970291AG2-192 GEN
Solar/Wind Harmer
0.362
270054AF2-122 C O1
Solar/Wind Helper
2.097
946101AF1-275 GEN
Solar/Wind Helper
0.802
270349AD2-093_GEN
Solar/Wind Helper
1.818
270471AD2-092_GEN
Solar/Wind Helper
1.818
253383AE2-342_GEN
Solar/Wind Helper
0.854
241960AC2-195 GEN
Solar/Wind Helper
1.419
LAGNLTFEXP_LAGN->PJM
CLTF
11.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.139
TVALTFEXP_TVA->PJM
CLTF
5.225
NYPJM->LTFIMP_NY
CLTF
2.454
LGEELTFEXP_LGEE->PJM
CLTF
3.221
WECLTFEXP_WEC->PJM
CLTF
3.955
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
114.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.259
MECLTFEXP_MEC->PJM
CLTF
15.133
SIGELTFEXP_SIGE->PJM
CLTF
0.321
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.92

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.76 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4482.29
MW Contribution:
14.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
8.859
270143AC1-141 CT2_
50/50
2.617
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.55
274773LINCOLN ;4U
50/50
9.616
270142AC1-141 CT1_
50/50
2.617
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
9.616
944961AF1-161 GEN
50/50
3.109
962601AG1-109 GEN
50/50
3.109
962771AG1-126 GEN
Solar/Wind Harmer
74.627
970153AG2-106 GEN
Solar/Wind Harmer
47.655
971347AH1-153 GEN
Solar/Wind Harmer
4.014
270043AE2-236 GEN
Solar/Wind Harmer
5.048
270505AE1-170 C O1
Solar/Wind Harmer
7.914
270063AE2-323 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.088
944531AF1-118 GEN
Solar/Wind Harmer
33.371
274724RIVER EC ;11
Adder
18.817
274752CRETE EC ;2U
Adder
8.738
274753CRETE EC ;3U
Adder
8.738
965021AG1-366 GEN
Solar/Wind Harmer
2.462
970707AG2-453 GEN
Solar/Wind Harmer
24.09
274814UNIV PK N;0U
Adder
5.338
274807UNIV PK N;3U
Adder
5.326
274811UNIV PK N;7U
Adder
5.291
972259AH1-714 GEN
Adder
20.093
274826FISK ;BP
Adder
11.527
274803UNIV PARK;6U
Adder
6.138
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.237
276806AD2-047 C O1
Solar/Wind Harmer
4.16
972038AH1-567 GEN2
Adder
0.384
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.942
274729ELWOOD EC;1P
Adder
17.157
274730ELWOOD EC;6P
Adder
17.157
274734ELWOOD EC;8P
Adder
17.157
274736ELWOOD EC;9P
Adder
17.157
943121AE2-341 GEN
Solar/Wind Harmer
12.163
943591AF1-030 GEN
Solar/Wind Harmer
8.088
274682WAUKEGAN ;7U
Adder
18.463
274862TOP CROP ;2U
Solar/Wind Harmer
0.968
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274774LINCOLN ;5U
50/50
9.616
962761AG1-125 GEN
Solar/Wind Harmer
74.627
970149AG2-104 GEN
Solar/Wind Harmer
40.3
970155AG2-107 GEN
Solar/Wind Harmer
47.655
957891AF2-083 GEN
Solar/Wind Harmer
12.55
945111AF1-176 GEN
Solar/Wind Harmer
13.401
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.895
274723RIVER EC ;12
Adder
19.037
274751CRETE EC ;1U
Adder
8.738
274754CRETE EC ;4U
Adder
8.738
965011AG1-365 GEN
Solar/Wind Harmer
7.385
274812UNIV PK N;8U
Adder
5.291
274802UNIV PARK;5U
Adder
6.138
970373AG2-245 GEN
Solar/Wind Harmer
15.385
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.088
274674JOLIET 9 ;6U
Adder
16.082
274732ELWOOD EC;7P
Adder
17.157
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.803
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.165
274682WAUKEGAN ;7U
Adder
18.463
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
11.336
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.78
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.257
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.318
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.826
971997AH1-543 GEN
Solar/Wind Harmer
3.71
957471AF2-041 GEN
Solar/Wind Harmer
21.068
959081AF2-199 GEN
Solar/Wind Harmer
7.023
971067AG2-660 GEN
Solar/Wind Harmer
2.341
274822ROCKFORD ;11
Adder
19.703
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.741
970819AG2-516 GEN
Solar/Wind Harmer
8.368
970569AG2-363 GEN
Solar/Wind Harmer
20.843
965651AG1-433 GEN
Solar/Wind Harmer
2.028
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.215
274766LEE CO EC;7U
Adder
9.107
276708O09 GEN2
Solar/Wind Harmer
0.242
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
958861AF2-177 GEN
Solar/Wind Harmer
2.941
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.439
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
14.886
276621W2-048 GEN
Solar/Wind Harmer
0.314
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
6.922
270032AE2-172
Solar/Wind Harmer
4.12
965421AG1-410 GEN
Solar/Wind Harmer
18.52
965911AG1-460 GEN
Solar/Wind Harmer
1.222
246936BC-WTG1
Solar/Wind Harmer
0.244
270489AE1-102 GEN1
Solar/Wind Harmer
0.786
276903AD2-071 C
Solar/Wind Harmer
6.725
270102X2-052 ST
50/50
1.749
270100X2-052 CT1
50/50
1.616
270101X2-052 CT2
50/50
1.616
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.526
274770LINCOLN ;1U
50/50
9.616
274771LINCOLN ;2U
50/50
9.616
970349AG2-230 GEN
Solar/Wind Harmer
12.041
276868AE1-113 GEN
Solar/Wind Harmer
1.416
274879MINONK ;1U
Solar/Wind Harmer
0.295
946671AF1-331 GEN
Solar/Wind Harmer
0.753
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
959091AF2-200 GEN
Solar/Wind Harmer
14.045
970571AG2-364 GEN
Solar/Wind Harmer
13.895
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.215
274767LEE CO EC;8U
Adder
9.107
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
24690905MDL-1G C
Solar/Wind Harmer
0
24721905FLATG4
Adder
19.661
970781AG2-491 GEN
Solar/Wind Harmer
6.766
965931AG1-462 GEN
Solar/Wind Harmer
17.022
971087AG2-675 GEN
Solar/Wind Harmer
3.56
965091AG1-374 GEN
Solar/Wind Harmer
19.952
959611AF2-252 GEN
Solar/Wind Harmer
2.217
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
971993AH1-541 GEN
Solar/Wind Harmer
2.938
24695305TIMB G C
Solar/Wind Harmer
0.537
970289AG2-191 GEN
Solar/Wind Harmer
0.691
957381AF2-032 GEN
Solar/Wind Harmer
1.388
942481AE2-261 GEN
Solar/Wind Harmer
18.271
246938BC-WTG3
Solar/Wind Harmer
0.218
270491AE1-102 GEN2
Solar/Wind Harmer
0.786
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.504
965791AG1-447 GEN
Solar/Wind Harmer
6.97
961051AF2-396 GEN
Solar/Wind Harmer
14.959
961051AF2-396 GEN
Solar/Wind Harmer
9.973
274805UNIV PK N;1U
Adder
5.303
274808UNIV PK N;4U
Adder
5.268
274888KELLY CRK;1U
Solar/Wind Harmer
0.428
276776AD2-060 GEN
Solar/Wind Harmer
0.783
958011AF2-095 GEN
Solar/Wind Harmer
10.572
970941AG2-585 GEN
Solar/Wind Harmer
4.038
276897AD1-100 C
Solar/Wind Harmer
18.287
274674JOLIET 9 ;6U
Adder
16.082
276893AG1-478 C
Solar/Wind Harmer
0.485
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
11.454
274693ROCKY RD ;1P
Adder
11.341
274697ROCKY RD ;3P
Adder
3.111
274696ROCKY RD ;4P
Adder
11.724
958481AF2-142 GEN
Solar/Wind Harmer
10.754
274683WAUKEGAN ;8U
Adder
21.627
274683WAUKEGAN ;8U
Adder
18.23
962691AG1-118 GEN
Solar/Wind Harmer
21.414
958491AF2-143 GEN
Solar/Wind Harmer
10.655
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.045
971343AH1-151 GEN
Solar/Wind Harmer
14.045
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.526
972236AH1-702 GEN2
Adder
2.196
938861AE1-114 GEN
Solar/Wind Harmer
3.928
944541AF1-119 GEN
Solar/Wind Harmer
0.462
960971AF2-388 GEN
Solar/Wind Harmer
4.056
274764LEE CO EC;5U
Adder
9.237
274765LEE CO EC;6U
Adder
9.237
274762LEE CO EC;3U
Adder
9.215
274763LEE CO EC;4U
Adder
9.128
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.104
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.191
942221AE2-234 GEN
Solar/Wind Harmer
2.684
960611AF2-352 GEN
Solar/Wind Harmer
2.217
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.745
944231AF1-091 GEN
Solar/Wind Harmer
15.08
270246TR4_N_V150
Solar/Wind Harmer
0.042
270247TR4_N_V136
Solar/Wind Harmer
0.042
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.669
970291AG2-192 GEN
Solar/Wind Harmer
0.817
970291AG2-192 GEN
Solar/Wind Harmer
0.377
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.353
270031AE2-169
Solar/Wind Harmer
3.44
270599AE1-208 GEN
Solar/Wind Harmer
5.734
971613AH1-306 GEN
Solar/Wind Harmer
2.966
276916AD2-100_GEN
Solar/Wind Harmer
12.749
276911AD2-131_GEN
Solar/Wind Harmer
0.84
246937BC-WTG2
Solar/Wind Harmer
0.244
270054AF2-122 C O1
Solar/Wind Helper
1.656
270144AC1-141 ST1_
50/50
2.311
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.028
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.616
274776LINCOLN ;7U
50/50
9.616
274777LINCOLN ;8U
50/50
9.616
270071AF1-092 GEN
Solar/Wind Harmer
14.768
971771AH1-392 GEN
Solar/Wind Harmer
7.622
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
4.047
959331AF2-224 GEN
Solar/Wind Harmer
5.169
274827FISK ;RP
Adder
8.169
972037AH1-567 GEN1
Adder
0.193
960591AF2-350 GEN
Solar/Wind Harmer
7.341
274800UNIV PARK;3U
Adder
6.134
274801UNIV PARK;4U
Adder
6.134
972228AH1-698 GEN2
Adder
3.896
972227AH1-698 GEN1
Adder
2.744
24729505KEY G4
Adder
6.793
274687WILL CNTY;4U
Adder
29.249
274687WILL CNTY;4U
Adder
29.249
274675JOLIET 29;7U
Adder
32.088
274675JOLIET 29;7U
Adder
30.942
274728ELWOOD EC;5P
Adder
17.157
274731ELWOOD EC;2P
Adder
17.157
274733ELWOOD EC;3P
Adder
17.157
274735ELWOOD EC;4P
Adder
17.157
970833AG2-524 GEN
Solar/Wind Harmer
8.005
970833AG2-524 GEN
Solar/Wind Harmer
5.336
274744AC1-111 GEN8
Adder
5.803
274746AC1-111 G10
Adder
5.803
970073AG2-061 GEN
Solar/Wind Harmer
2.368
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.753
971411AH1-196 GEN
Solar/Wind Harmer
10.588
276861AD2-134 GEN
Solar/Wind Harmer
0.126
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
14.045
274823ROCKFORD ;21
Adder
19.56
971611AH1-305 GEN
Solar/Wind Harmer
4.163
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
926823AC1-168 GEN
Solar/Wind Harmer
1.181
970169AG2-114 GEN
Solar/Wind Harmer
6.939
971681AH1-341 GEN
Solar/Wind Harmer
11.162
972267AH1-718 GEN
Adder
4.093
276741O09 GEN1
Solar/Wind Harmer
0.242
971549AH1-272 GEN
Solar/Wind Harmer
14.066
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
9.126
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.079
965041AG1-368 GEN
Solar/Wind Harmer
6.739
946321AF1-296 GEN
Solar/Wind Harmer
3.754
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.235
965051AG1-369 GEN
Solar/Wind Harmer
3.245
963841AG1-237 GEN
Solar/Wind Harmer
2.784
276668AB2-070 GEN1
Solar/Wind Harmer
0.25
276848AB2-070 GEN3
Solar/Wind Harmer
0.249
276849AB2-070 GEN2
Solar/Wind Harmer
0.25
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.194
971609AH1-304 GEN
Solar/Wind Harmer
1.022
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.766
LAGNLTFEXP_LAGN->PJM
CLTF
11.281
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.712
TVALTFEXP_TVA->PJM
CLTF
5.082
NYPJM->LTFIMP_NY
CLTF
2.583
LGEELTFEXP_LGEE->PJM
CLTF
3.675
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.237
AH1-155LTFEXP_AH1-155->PJM
LTF
0.356
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.267
MECLTFEXP_MEC->PJM
CLTF
14.733
SIGELTFEXP_SIGE->PJM
CLTF
0.34
CPLELTFEXP_CPLE->PJM
CLTF
1.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.349

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.18 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4944.72
MW Contribution:
19.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.775
24642205MAYFLWER
50/50
0.042
944961AF1-161 GEN
50/50
3.309
962601AG1-109 GEN
50/50
3.309
274772LINCOLN ;3U
50/50
7.418
962771AG1-126 GEN
Solar/Wind Harmer
89.226
970153AG2-106 GEN
Solar/Wind Harmer
38.907
971347AH1-153 GEN
Solar/Wind Harmer
6.05
270043AE2-236 GEN
Solar/Wind Harmer
6.529
247643Z2-116 C
Solar/Wind Harmer
0.08
24344105CKG2
50/50
9.299
270143AC1-141 CT2_
50/50
2.775
24639705ELKHART HY
50/50
0.187
970521AG2-332 GEN
50/50
13.311
24307105BERRINSP G
50/50
0.024
274773LINCOLN ;4U
50/50
7.418
274774LINCOLN ;5U
50/50
7.418
962761AG1-125 GEN
Solar/Wind Harmer
89.226
970149AG2-104 GEN
Solar/Wind Harmer
55.097
970155AG2-107 GEN
Solar/Wind Harmer
38.907
270216AD2-079_GEN
Solar/Wind Harmer
0.699
957891AF2-083 GEN
Solar/Wind Harmer
17.194
945111AF1-176 GEN
Solar/Wind Harmer
20.409
270449AD2-020 GEN
Solar/Wind Harmer
3.19
943021AE2-325 GEN
Solar/Wind Harmer
4.145
972207SS24-0001
Solar/Wind Harmer
24.857
24441205WTRV SLR C
Solar/Wind Harmer
0.151
965011AG1-365 GEN
Solar/Wind Harmer
11.213
274723RIVER EC ;12
Adder
20.022
274751CRETE EC ;1U
Adder
5.455
274754CRETE EC ;4U
Adder
5.455
274812UNIV PK N;8U
Adder
5.565
970373AG2-245 GEN
Solar/Wind Harmer
23.253
274802UNIV PARK;5U
Adder
6.454
941551AE2-152 GEN
Solar/Wind Harmer
4.997
274676JOLIET 29;8U
Adder
33.727
274674JOLIET 9 ;6U
Adder
16.903
274732ELWOOD EC;7P
Adder
18.034
274871GR RIDGE ;2U
Solar/Wind Harmer
8.425
274847GR RIDGE ;BU
Solar/Wind Harmer
5.54
270055AF2-134 C O1
Solar/Wind Harmer
3.304
274745AC1-111 GEN9
Adder
6.097
276694AA1-018 GEN2
Solar/Wind Harmer
6.817
276691AA1-018 GEN1
Solar/Wind Harmer
0.815
274861TOP CROP ;1U
Solar/Wind Harmer
6.542
274682WAUKEGAN ;7U
Adder
19.404
274828WAUKEGAN ;BP
Adder
11.914
958381AF2-132 GEN
Solar/Wind Harmer
9.773
964861AG1-349 GEN
Solar/Wind Harmer
8.457
971917AH1-482 GEN
Solar/Wind Harmer
9.757
962781AG1-127 GEN
Solar/Wind Harmer
10.205
274872LEEDK;1U
Solar/Wind Harmer
8.794
939401AE1-172 GEN
Solar/Wind Harmer
14.927
276805AD2-038 GEN
Solar/Wind Harmer
5.489
24441505OLIV SLR
Solar/Wind Harmer
0.154
270505AE1-170 C O1
Solar/Wind Harmer
17.214
945111AF1-176 GEN
Solar/Wind Harmer
6.468
270063AE2-323 C
Solar/Wind Harmer
2.513
965021AG1-366 GEN
Solar/Wind Harmer
2.608
944531AF1-118 GEN
Solar/Wind Harmer
39.173
274724RIVER EC ;11
Adder
19.791
972231SS25-0005
Solar/Wind Harmer
10.591
972181SS23-001
Solar/Wind Harmer
6.619
274752CRETE EC ;2U
Adder
5.455
274753CRETE EC ;3U
Adder
5.455
276164X3-005 C
Solar/Wind Harmer
0.782
274814UNIV PK N;0U
Adder
5.614
274807UNIV PK N;3U
Adder
5.602
274811UNIV PK N;7U
Adder
5.565
970707AG2-453 GEN
Solar/Wind Harmer
31.089
274803UNIV PARK;6U
Adder
6.454
274826FISK ;BP
Adder
12.118
972259AH1-714 GEN
Adder
21.114
274887GEN-1.85
Solar/Wind Harmer
5.893
276772AC2-154 GEN
Solar/Wind Harmer
3.087
276843GEN-1.7
Solar/Wind Harmer
0.634
276806AD2-047 C O1
Solar/Wind Harmer
11.833
972038AH1-567 GEN2
Adder
0.404
939351AE1-166 GEN
Solar/Wind Harmer
6.535
274676JOLIET 29;8U
Adder
32.523
274729ELWOOD EC;1P
Adder
18.034
274730ELWOOD EC;6P
Adder
18.034
274734ELWOOD EC;8P
Adder
18.034
274736ELWOOD EC;9P
Adder
18.034
943121AE2-341 GEN
Solar/Wind Harmer
16.387
943591AF1-030 GEN
Solar/Wind Harmer
10.925
274862TOP CROP ;2U
Solar/Wind Harmer
5.462
274682WAUKEGAN ;7U
Adder
19.404
964401AG1-302 GEN
Solar/Wind Harmer
9.773
276868AE1-113 GEN
Solar/Wind Harmer
10.789
274879MINONK ;1U
Solar/Wind Harmer
7.193
276799AD1-013 GEN
Solar/Wind Harmer
2.35
946671AF1-331 GEN
Solar/Wind Harmer
0.445
274855GSG-6 ;RU
Solar/Wind Harmer
3.925
274850MENDOTA H;RU
Solar/Wind Harmer
2.729
276602WESTBROOK C
Solar/Wind Harmer
2.259
959091AF2-200 GEN
Solar/Wind Harmer
21.158
274760LEE CO EC;1U
Adder
9.686
274767LEE CO EC;8U
Adder
9.572
24721905FLATG4
Adder
19.928
270102X2-052 ST
50/50
1.845
270100X2-052 CT1
50/50
1.705
270101X2-052 CT2
50/50
1.705
24643105BUCHANAN
50/50
0.015
247620Y3-023
50/50
0.558
274770LINCOLN ;1U
50/50
7.418
274771LINCOLN ;2U
50/50
7.418
970349AG2-230 GEN
Solar/Wind Harmer
18.149
965681AG1-436 GEN
Solar/Wind Harmer
14.368
965791AG1-447 GEN
Solar/Wind Harmer
7.351
961051AF2-396 GEN
Solar/Wind Harmer
18.101
961051AF2-396 GEN
Solar/Wind Harmer
8.419
274805UNIV PK N;1U
Adder
5.578
274808UNIV PK N;4U
Adder
5.541
274888KELLY CRK;1U
Solar/Wind Harmer
6.527
276776AD2-060 GEN
Solar/Wind Harmer
0.463
958011AF2-095 GEN
Solar/Wind Harmer
15.928
970941AG2-585 GEN
Solar/Wind Harmer
6.084
276897AD1-100 C
Solar/Wind Harmer
51.184
274674JOLIET 9 ;6U
Adder
16.903
276893AG1-478 C
Solar/Wind Harmer
0.481
270535AF1-215 GEN1
Solar/Wind Harmer
4.956
270536AF1-215 GEN2
Solar/Wind Harmer
4.956
274695ROCKY RD ;2P
Adder
12.037
274693ROCKY RD ;1P
Adder
11.918
274697ROCKY RD ;3P
Adder
3.27
274696ROCKY RD ;4P
Adder
12.321
958481AF2-142 GEN
Solar/Wind Harmer
16.205
274683WAUKEGAN ;8U
Adder
22.729
274683WAUKEGAN ;8U
Adder
19.16
962691AG1-118 GEN
Solar/Wind Harmer
32.255
960751AF2-366 GEN
Solar/Wind Harmer
3.079
958491AF2-143 GEN
Solar/Wind Harmer
16.055
276901AD2-066 C O1
Solar/Wind Harmer
3.749
971341AH1-150 GEN
Solar/Wind Harmer
21.158
971343AH1-151 GEN
Solar/Wind Harmer
21.158
276872AE1-163_GEN1
Solar/Wind Harmer
7.094
276876AE1-163_GEN2
Solar/Wind Harmer
7.094
972235AH1-702 GEN1
Adder
2.655
972236AH1-702 GEN2
Adder
2.308
274764LEE CO EC;5U
Adder
9.709
274765LEE CO EC;6U
Adder
9.709
274762LEE CO EC;3U
Adder
9.686
274763LEE CO EC;4U
Adder
9.595
270054AF2-122 C O1
Solar/Wind Helper
1.626
276882AE2-255 GEN
Solar/Wind Harmer
3.596
971997AH1-543 GEN
Solar/Wind Harmer
16.77
957471AF2-041 GEN
Solar/Wind Harmer
31.738
959081AF2-199 GEN
Solar/Wind Harmer
10.579
971067AG2-660 GEN
Solar/Wind Harmer
2.46
940581AE2-045 GEN
Solar/Wind Harmer
10.772
971605AH1-302 GEN
Solar/Wind Harmer
9.211
274822ROCKFORD ;11
Adder
20.708
274761LEE CO EC;2U
Adder
9.686
274766LEE CO EC;7U
Adder
9.572
970819AG2-516 GEN
Solar/Wind Harmer
7.613
270144AC1-141 ST1_
50/50
2.451
24344005CKG1
50/50
7.462
24641605TWIN BRNCH
50/50
0.02
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.418
274776LINCOLN ;7U
50/50
7.418
274777LINCOLN ;8U
50/50
7.418
270071AF1-092 GEN
Solar/Wind Harmer
17.395
971771AH1-392 GEN
Solar/Wind Harmer
10.406
270526AF1-158 GEN
Solar/Wind Harmer
5.216
960681AF2-359 GEN
Solar/Wind Harmer
4.343
970031AG2-029 GEN
Solar/Wind Harmer
28.389
944161AF1-084 GEN
Solar/Wind Harmer
2.504
959331AF2-224 GEN
Solar/Wind Harmer
11.213
972037AH1-567 GEN1
Adder
0.203
274827FISK ;RP
Adder
8.588
960591AF2-350 GEN
Solar/Wind Harmer
11.061
274800UNIV PARK;3U
Adder
6.448
274801UNIV PARK;4U
Adder
6.448
972228AH1-698 GEN2
Adder
4.095
972227AH1-698 GEN1
Adder
2.884
274687WILL CNTY;4U
Adder
30.745
274687WILL CNTY;4U
Adder
30.745
274675JOLIET 29;7U
Adder
33.728
274675JOLIET 29;7U
Adder
32.523
24729505KEY G4
Adder
7.126
274728ELWOOD EC;5P
Adder
18.034
274731ELWOOD EC;2P
Adder
18.034
274733ELWOOD EC;3P
Adder
18.034
274735ELWOOD EC;4P
Adder
18.034
276893AG1-478 C
Solar/Wind Harmer
0.603
970833AG2-524 GEN
Solar/Wind Harmer
9.569
970833AG2-524 GEN
Solar/Wind Harmer
4.451
274744AC1-111 GEN8
Adder
6.097
274746AC1-111 G10
Adder
6.097
970073AG2-061 GEN
Solar/Wind Harmer
2.489
958391AF2-133 GEN
Solar/Wind Harmer
9.701
959141AF2-205 GEN
Solar/Wind Harmer
6.431
971675AH1-338 GEN
Solar/Wind Harmer
19.139
971411AH1-196 GEN
Solar/Wind Harmer
15.949
276861AD2-134 GEN
Solar/Wind Harmer
1.898
276863AD2-134 GEN
Solar/Wind Harmer
1.898
971549AH1-272 GEN
Solar/Wind Harmer
19.629
274863CRW1-WTG
Solar/Wind Harmer
5.908
274864CRW2-WTG
Solar/Wind Harmer
5.908
971171AH1-044 GEN
Solar/Wind Harmer
21.158
276889AE2-281 GEN
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
20.558
972267AH1-718 GEN
Adder
4.302
LAGNLTFEXP_LAGN->PJM
CLTF
11.862
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.972
TVALTFEXP_TVA->PJM
CLTF
5.346
NYPJM->LTFIMP_NY
CLTF
2.82
LGEELTFEXP_LGEE->PJM
CLTF
3.91
WECLTFEXP_WEC->PJM
CLTF
4.019
AG2-052LTFEXP_AG2-052->PJM
LTF
0.25
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.31
MECLTFEXP_MEC->PJM
CLTF
15.493
SIGELTFEXP_SIGE->PJM
CLTF
0.36
CPLELTFEXP_CPLE->PJM
CLTF
1.484
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.994

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.94 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4934.14
MW Contribution:
19.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.77
24642205MAYFLWER
50/50
0.042
944961AF1-161 GEN
50/50
3.302
962601AG1-109 GEN
50/50
3.302
274772LINCOLN ;3U
50/50
7.408
962771AG1-126 GEN
Solar/Wind Harmer
89.224
970153AG2-106 GEN
Solar/Wind Harmer
38.906
971347AH1-153 GEN
Solar/Wind Harmer
6.04
270043AE2-236 GEN
Solar/Wind Harmer
6.521
247643Z2-116 C
Solar/Wind Harmer
0.08
24441505OLIV SLR
Solar/Wind Harmer
0.153
270505AE1-170 C O1
Solar/Wind Harmer
17.179
24344105CKG2
50/50
9.285
270143AC1-141 CT2_
50/50
2.77
24639705ELKHART HY
50/50
0.187
970521AG2-332 GEN
50/50
13.287
24307105BERRINSP G
50/50
0.024
274773LINCOLN ;4U
50/50
7.408
274774LINCOLN ;5U
50/50
7.408
962761AG1-125 GEN
Solar/Wind Harmer
89.224
970149AG2-104 GEN
Solar/Wind Harmer
55.096
970155AG2-107 GEN
Solar/Wind Harmer
38.906
270216AD2-079_GEN
Solar/Wind Harmer
0.698
957891AF2-083 GEN
Solar/Wind Harmer
17.16
945111AF1-176 GEN
Solar/Wind Harmer
20.368
270449AD2-020 GEN
Solar/Wind Harmer
3.183
943021AE2-325 GEN
Solar/Wind Harmer
4.137
972207SS24-0001
Solar/Wind Harmer
24.822
965011AG1-365 GEN
Solar/Wind Harmer
11.202
24441205WTRV SLR C
Solar/Wind Harmer
0.151
274723RIVER EC ;12
Adder
19.993
274751CRETE EC ;1U
Adder
5.447
274754CRETE EC ;4U
Adder
5.447
274812UNIV PK N;8U
Adder
5.557
970373AG2-245 GEN
Solar/Wind Harmer
23.216
274802UNIV PARK;5U
Adder
6.445
941551AE2-152 GEN
Solar/Wind Harmer
4.99
274676JOLIET 29;8U
Adder
33.678
274674JOLIET 9 ;6U
Adder
16.879
274732ELWOOD EC;7P
Adder
18.008
274871GR RIDGE ;2U
Solar/Wind Harmer
8.413
274847GR RIDGE ;BU
Solar/Wind Harmer
5.532
270055AF2-134 C O1
Solar/Wind Harmer
3.298
274745AC1-111 GEN9
Adder
6.089
276694AA1-018 GEN2
Solar/Wind Harmer
6.807
270144AC1-141 ST1_
50/50
2.446
24344005CKG1
50/50
7.447
24641605TWIN BRNCH
50/50
0.02
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.408
274776LINCOLN ;7U
50/50
7.408
274777LINCOLN ;8U
50/50
7.408
270071AF1-092 GEN
Solar/Wind Harmer
17.376
971771AH1-392 GEN
Solar/Wind Harmer
10.387
270526AF1-158 GEN
Solar/Wind Harmer
5.207
960681AF2-359 GEN
Solar/Wind Harmer
4.336
970031AG2-029 GEN
Solar/Wind Harmer
28.344
944161AF1-084 GEN
Solar/Wind Harmer
2.498
959331AF2-224 GEN
Solar/Wind Harmer
11.202
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.576
960591AF2-350 GEN
Solar/Wind Harmer
11.045
274800UNIV PARK;3U
Adder
6.439
274801UNIV PARK;4U
Adder
6.439
972228AH1-698 GEN2
Adder
4.089
972227AH1-698 GEN1
Adder
2.879
274687WILL CNTY;4U
Adder
30.7
274687WILL CNTY;4U
Adder
30.7
274675JOLIET 29;7U
Adder
33.679
274675JOLIET 29;7U
Adder
32.476
24729505KEY G4
Adder
7.119
274728ELWOOD EC;5P
Adder
18.008
274731ELWOOD EC;2P
Adder
18.008
274733ELWOOD EC;3P
Adder
18.008
274735ELWOOD EC;4P
Adder
18.008
276893AG1-478 C
Solar/Wind Harmer
0.602
970833AG2-524 GEN
Solar/Wind Harmer
9.556
970833AG2-524 GEN
Solar/Wind Harmer
4.444
945111AF1-176 GEN
Solar/Wind Harmer
6.455
270063AE2-323 C
Solar/Wind Harmer
2.509
965021AG1-366 GEN
Solar/Wind Harmer
2.605
944531AF1-118 GEN
Solar/Wind Harmer
39.134
274724RIVER EC ;11
Adder
19.762
972231SS25-0005
Solar/Wind Harmer
10.575
972181SS23-001
Solar/Wind Harmer
6.609
274752CRETE EC ;2U
Adder
5.447
274753CRETE EC ;3U
Adder
5.447
276164X3-005 C
Solar/Wind Harmer
0.781
274814UNIV PK N;0U
Adder
5.606
274807UNIV PK N;3U
Adder
5.594
274811UNIV PK N;7U
Adder
5.557
970707AG2-453 GEN
Solar/Wind Harmer
31.045
274803UNIV PARK;6U
Adder
6.445
274826FISK ;BP
Adder
12.101
972259AH1-714 GEN
Adder
21.083
274887GEN-1.85
Solar/Wind Harmer
5.885
276772AC2-154 GEN
Solar/Wind Harmer
3.082
276843GEN-1.7
Solar/Wind Harmer
0.633
276806AD2-047 C O1
Solar/Wind Harmer
11.816
972038AH1-567 GEN2
Adder
0.403
939351AE1-166 GEN
Solar/Wind Harmer
6.525
274676JOLIET 29;8U
Adder
32.476
274729ELWOOD EC;1P
Adder
18.008
274730ELWOOD EC;6P
Adder
18.008
274734ELWOOD EC;8P
Adder
18.008
274736ELWOOD EC;9P
Adder
18.008
943121AE2-341 GEN
Solar/Wind Harmer
16.364
943591AF1-030 GEN
Solar/Wind Harmer
10.909
274862TOP CROP ;2U
Solar/Wind Harmer
5.454
274682WAUKEGAN ;7U
Adder
19.377
964401AG1-302 GEN
Solar/Wind Harmer
9.758
276868AE1-113 GEN
Solar/Wind Harmer
10.774
274879MINONK ;1U
Solar/Wind Harmer
7.183
276799AD1-013 GEN
Solar/Wind Harmer
2.347
946671AF1-331 GEN
Solar/Wind Harmer
0.445
274855GSG-6 ;RU
Solar/Wind Harmer
3.919
274850MENDOTA H;RU
Solar/Wind Harmer
2.725
276602WESTBROOK C
Solar/Wind Harmer
2.256
959091AF2-200 GEN
Solar/Wind Harmer
21.128
274760LEE CO EC;1U
Adder
9.672
274767LEE CO EC;8U
Adder
9.558
24721905FLATG4
Adder
19.926
270102X2-052 ST
50/50
1.842
270100X2-052 CT1
50/50
1.702
270101X2-052 CT2
50/50
1.702
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.557
274770LINCOLN ;1U
50/50
7.408
274771LINCOLN ;2U
50/50
7.408
970349AG2-230 GEN
Solar/Wind Harmer
18.121
965681AG1-436 GEN
Solar/Wind Harmer
14.345
965791AG1-447 GEN
Solar/Wind Harmer
7.339
961051AF2-396 GEN
Solar/Wind Harmer
18.063
961051AF2-396 GEN
Solar/Wind Harmer
8.401
274805UNIV PK N;1U
Adder
5.569
274808UNIV PK N;4U
Adder
5.533
274888KELLY CRK;1U
Solar/Wind Harmer
6.518
276776AD2-060 GEN
Solar/Wind Harmer
0.462
958011AF2-095 GEN
Solar/Wind Harmer
15.905
970941AG2-585 GEN
Solar/Wind Harmer
6.075
276897AD1-100 C
Solar/Wind Harmer
51.111
274674JOLIET 9 ;6U
Adder
16.879
276893AG1-478 C
Solar/Wind Harmer
0.48
270535AF1-215 GEN1
Solar/Wind Harmer
4.948
270536AF1-215 GEN2
Solar/Wind Harmer
4.948
274695ROCKY RD ;2P
Adder
12.019
274693ROCKY RD ;1P
Adder
11.901
274697ROCKY RD ;3P
Adder
3.265
274696ROCKY RD ;4P
Adder
12.303
958481AF2-142 GEN
Solar/Wind Harmer
16.182
274683WAUKEGAN ;8U
Adder
22.697
274683WAUKEGAN ;8U
Adder
19.132
962691AG1-118 GEN
Solar/Wind Harmer
32.209
960751AF2-366 GEN
Solar/Wind Harmer
3.074
958491AF2-143 GEN
Solar/Wind Harmer
16.032
276901AD2-066 C O1
Solar/Wind Harmer
3.744
971341AH1-150 GEN
Solar/Wind Harmer
21.128
971343AH1-151 GEN
Solar/Wind Harmer
21.128
276872AE1-163_GEN1
Solar/Wind Harmer
7.084
276876AE1-163_GEN2
Solar/Wind Harmer
7.084
972235AH1-702 GEN1
Adder
2.651
972236AH1-702 GEN2
Adder
2.305
274764LEE CO EC;5U
Adder
9.695
274765LEE CO EC;6U
Adder
9.695
274762LEE CO EC;3U
Adder
9.672
274763LEE CO EC;4U
Adder
9.581
270054AF2-122 C O1
Solar/Wind Helper
1.625
274744AC1-111 GEN8
Adder
6.089
274746AC1-111 G10
Adder
6.089
970073AG2-061 GEN
Solar/Wind Harmer
2.486
958391AF2-133 GEN
Solar/Wind Harmer
9.686
959141AF2-205 GEN
Solar/Wind Harmer
6.422
971411AH1-196 GEN
Solar/Wind Harmer
15.927
971675AH1-338 GEN
Solar/Wind Harmer
19.112
276861AD2-134 GEN
Solar/Wind Harmer
1.895
276863AD2-134 GEN
Solar/Wind Harmer
1.895
971549AH1-272 GEN
Solar/Wind Harmer
19.563
274863CRW1-WTG
Solar/Wind Harmer
5.9
274864CRW2-WTG
Solar/Wind Harmer
5.9
971171AH1-044 GEN
Solar/Wind Harmer
21.128
276889AE2-281 GEN
Solar/Wind Harmer
2.024
274823ROCKFORD ;21
Adder
20.529
972267AH1-718 GEN
Adder
4.296
276691AA1-018 GEN1
Solar/Wind Harmer
0.814
274861TOP CROP ;1U
Solar/Wind Harmer
6.532
274682WAUKEGAN ;7U
Adder
19.377
274828WAUKEGAN ;BP
Adder
11.897
958381AF2-132 GEN
Solar/Wind Harmer
9.758
964861AG1-349 GEN
Solar/Wind Harmer
8.444
971917AH1-482 GEN
Solar/Wind Harmer
9.742
962781AG1-127 GEN
Solar/Wind Harmer
10.19
274872LEEDK;1U
Solar/Wind Harmer
8.781
939401AE1-172 GEN
Solar/Wind Harmer
14.906
276805AD2-038 GEN
Solar/Wind Harmer
5.481
276882AE2-255 GEN
Solar/Wind Harmer
3.591
971997AH1-543 GEN
Solar/Wind Harmer
16.746
957471AF2-041 GEN
Solar/Wind Harmer
31.693
959081AF2-199 GEN
Solar/Wind Harmer
10.564
971067AG2-660 GEN
Solar/Wind Harmer
2.457
940581AE2-045 GEN
Solar/Wind Harmer
10.756
971605AH1-302 GEN
Solar/Wind Harmer
9.197
274822ROCKFORD ;11
Adder
20.679
274761LEE CO EC;2U
Adder
9.672
274766LEE CO EC;7U
Adder
9.558
970819AG2-516 GEN
Solar/Wind Harmer
7.602
LAGNLTFEXP_LAGN->PJM
CLTF
11.847
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.962
TVALTFEXP_TVA->PJM
CLTF
5.339
NYPJM->LTFIMP_NY
CLTF
2.822
LGEELTFEXP_LGEE->PJM
CLTF
3.906
WECLTFEXP_WEC->PJM
CLTF
4.013
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.285
MECLTFEXP_MEC->PJM
CLTF
15.472
SIGELTFEXP_SIGE->PJM
CLTF
0.359
CPLELTFEXP_CPLE->PJM
CLTF
1.481
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.877

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P2-2_#5063_05SBERWI 345_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#5063_05SBERWI 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.2 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4763.16
MW Contribution:
18.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
9.043
270143AC1-141 CT2_
50/50
2.692
24639705ELKHART HY
50/50
0.181
970521AG2-332 GEN
50/50
12.915
274773LINCOLN ;4U
50/50
7.202
274774LINCOLN ;5U
50/50
7.202
24307105BERRINSP G
50/50
0.024
962761AG1-125 GEN
Solar/Wind Harmer
88.136
970149AG2-104 GEN
Solar/Wind Harmer
54.424
970155AG2-107 GEN
Solar/Wind Harmer
38.432
270216AD2-079_GEN
Solar/Wind Harmer
0.678
957891AF2-083 GEN
Solar/Wind Harmer
16.669
945111AF1-176 GEN
Solar/Wind Harmer
19.785
270449AD2-020 GEN
Solar/Wind Harmer
3.091
943021AE2-325 GEN
Solar/Wind Harmer
4.016
972207SS24-0001
Solar/Wind Harmer
24.133
965011AG1-365 GEN
Solar/Wind Harmer
10.941
24441205WTRV SLR C
Solar/Wind Harmer
0.146
274723RIVER EC ;12
Adder
19.432
274751CRETE EC ;1U
Adder
5.293
274754CRETE EC ;4U
Adder
5.293
274812UNIV PK N;8U
Adder
5.401
274802UNIV PARK;5U
Adder
6.263
970373AG2-245 GEN
Solar/Wind Harmer
22.549
941551AE2-152 GEN
Solar/Wind Harmer
4.849
274676JOLIET 29;8U
Adder
32.725
274674JOLIET 9 ;6U
Adder
16.401
274732ELWOOD EC;7P
Adder
17.497
274871GR RIDGE ;2U
Solar/Wind Harmer
8.174
274847GR RIDGE ;BU
Solar/Wind Harmer
5.375
270055AF2-134 C O1
Solar/Wind Harmer
3.203
274745AC1-111 GEN9
Adder
5.916
276694AA1-018 GEN2
Solar/Wind Harmer
6.612
276691AA1-018 GEN1
Solar/Wind Harmer
0.79
274861TOP CROP ;1U
Solar/Wind Harmer
6.345
274682WAUKEGAN ;7U
Adder
18.822
274828WAUKEGAN ;BP
Adder
11.557
958381AF2-132 GEN
Solar/Wind Harmer
9.472
964861AG1-349 GEN
Solar/Wind Harmer
8.196
971917AH1-482 GEN
Solar/Wind Harmer
9.456
962781AG1-127 GEN
Solar/Wind Harmer
9.898
274872LEEDK;1U
Solar/Wind Harmer
8.529
939401AE1-172 GEN
Solar/Wind Harmer
14.475
276805AD2-038 GEN
Solar/Wind Harmer
5.323
276882AE2-255 GEN
Solar/Wind Harmer
3.487
971997AH1-543 GEN
Solar/Wind Harmer
16.261
957471AF2-041 GEN
Solar/Wind Harmer
30.774
959081AF2-199 GEN
Solar/Wind Harmer
10.258
971067AG2-660 GEN
Solar/Wind Harmer
2.386
940581AE2-045 GEN
Solar/Wind Harmer
10.436
971605AH1-302 GEN
Solar/Wind Harmer
8.924
274822ROCKFORD ;11
Adder
20.078
274761LEE CO EC;2U
Adder
9.389
274766LEE CO EC;7U
Adder
9.278
970819AG2-516 GEN
Solar/Wind Harmer
7.381
270142AC1-141 CT1_
50/50
2.692
24642205MAYFLWER
50/50
0.041
944961AF1-161 GEN
50/50
3.206
962601AG1-109 GEN
50/50
3.206
274772LINCOLN ;3U
50/50
7.202
962771AG1-126 GEN
Solar/Wind Harmer
88.136
970153AG2-106 GEN
Solar/Wind Harmer
38.432
971347AH1-153 GEN
Solar/Wind Harmer
5.88
270043AE2-236 GEN
Solar/Wind Harmer
6.356
247643Z2-116 C
Solar/Wind Harmer
0.078
24441505OLIV SLR
Solar/Wind Harmer
0.149
270505AE1-170 C O1
Solar/Wind Harmer
16.687
270063AE2-323 C
Solar/Wind Harmer
2.441
945111AF1-176 GEN
Solar/Wind Harmer
6.27
965021AG1-366 GEN
Solar/Wind Harmer
2.544
944531AF1-118 GEN
Solar/Wind Harmer
38.069
274724RIVER EC ;11
Adder
19.208
972231SS25-0005
Solar/Wind Harmer
10.278
972181SS23-001
Solar/Wind Harmer
6.423
274752CRETE EC ;2U
Adder
5.293
274753CRETE EC ;3U
Adder
5.293
276164X3-005 C
Solar/Wind Harmer
0.759
274814UNIV PK N;0U
Adder
5.448
274807UNIV PK N;3U
Adder
5.436
274811UNIV PK N;7U
Adder
5.401
970707AG2-453 GEN
Solar/Wind Harmer
30.174
274803UNIV PARK;6U
Adder
6.263
274826FISK ;BP
Adder
11.759
972259AH1-714 GEN
Adder
20.49
274887GEN-1.85
Solar/Wind Harmer
5.719
276772AC2-154 GEN
Solar/Wind Harmer
2.995
276843GEN-1.7
Solar/Wind Harmer
0.615
276806AD2-047 C O1
Solar/Wind Harmer
11.483
972038AH1-567 GEN2
Adder
0.392
939351AE1-166 GEN
Solar/Wind Harmer
6.341
274676JOLIET 29;8U
Adder
31.556
274729ELWOOD EC;1P
Adder
17.497
274730ELWOOD EC;6P
Adder
17.497
274734ELWOOD EC;8P
Adder
17.497
274736ELWOOD EC;9P
Adder
17.497
943121AE2-341 GEN
Solar/Wind Harmer
15.9
943591AF1-030 GEN
Solar/Wind Harmer
10.6
274862TOP CROP ;2U
Solar/Wind Harmer
5.298
274682WAUKEGAN ;7U
Adder
18.822
964401AG1-302 GEN
Solar/Wind Harmer
9.472
276868AE1-113 GEN
Solar/Wind Harmer
10.462
274879MINONK ;1U
Solar/Wind Harmer
6.975
276799AD1-013 GEN
Solar/Wind Harmer
2.279
946671AF1-331 GEN
Solar/Wind Harmer
0.432
274855GSG-6 ;RU
Solar/Wind Harmer
3.806
274850MENDOTA H;RU
Solar/Wind Harmer
2.646
276602WESTBROOK C
Solar/Wind Harmer
2.191
959091AF2-200 GEN
Solar/Wind Harmer
20.516
274760LEE CO EC;1U
Adder
9.389
274767LEE CO EC;8U
Adder
9.278
24721905FLATG4
Adder
19.422
270102X2-052 ST
50/50
1.791
270100X2-052 CT1
50/50
1.655
270101X2-052 CT2
50/50
1.655
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.542
274770LINCOLN ;1U
50/50
7.202
274771LINCOLN ;2U
50/50
7.202
970349AG2-230 GEN
Solar/Wind Harmer
17.64
965681AG1-436 GEN
Solar/Wind Harmer
13.944
965791AG1-447 GEN
Solar/Wind Harmer
7.134
961051AF2-396 GEN
Solar/Wind Harmer
17.54
961051AF2-396 GEN
Solar/Wind Harmer
8.158
274805UNIV PK N;1U
Adder
5.412
274808UNIV PK N;4U
Adder
5.377
274888KELLY CRK;1U
Solar/Wind Harmer
6.334
276776AD2-060 GEN
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
15.457
970941AG2-585 GEN
Solar/Wind Harmer
5.904
276897AD1-100 C
Solar/Wind Harmer
49.665
274674JOLIET 9 ;6U
Adder
16.401
276893AG1-478 C
Solar/Wind Harmer
0.466
270535AF1-215 GEN1
Solar/Wind Harmer
4.804
270536AF1-215 GEN2
Solar/Wind Harmer
4.804
274696ROCKY RD ;4P
Adder
11.951
274695ROCKY RD ;2P
Adder
11.676
274693ROCKY RD ;1P
Adder
11.561
274697ROCKY RD ;3P
Adder
3.172
958481AF2-142 GEN
Solar/Wind Harmer
15.718
274683WAUKEGAN ;8U
Adder
22.047
274683WAUKEGAN ;8U
Adder
18.585
962691AG1-118 GEN
Solar/Wind Harmer
31.285
960751AF2-366 GEN
Solar/Wind Harmer
2.986
958491AF2-143 GEN
Solar/Wind Harmer
15.569
276901AD2-066 C O1
Solar/Wind Harmer
3.636
971341AH1-150 GEN
Solar/Wind Harmer
20.516
971343AH1-151 GEN
Solar/Wind Harmer
20.516
276872AE1-163_GEN1
Solar/Wind Harmer
6.878
276876AE1-163_GEN2
Solar/Wind Harmer
6.878
972235AH1-702 GEN1
Adder
2.574
972236AH1-702 GEN2
Adder
2.238
274764LEE CO EC;5U
Adder
9.411
274765LEE CO EC;6U
Adder
9.411
274762LEE CO EC;3U
Adder
9.389
274763LEE CO EC;4U
Adder
9.301
270054AF2-122 C O1
Solar/Wind Helper
1.705
270144AC1-141 ST1_
50/50
2.377
24344005CKG1
50/50
7.233
24641605TWIN BRNCH
50/50
0.019
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.202
274776LINCOLN ;7U
50/50
7.202
274777LINCOLN ;8U
50/50
7.202
270071AF1-092 GEN
Solar/Wind Harmer
16.926
971771AH1-392 GEN
Solar/Wind Harmer
10.096
270526AF1-158 GEN
Solar/Wind Harmer
5.06
960681AF2-359 GEN
Solar/Wind Harmer
4.215
970031AG2-029 GEN
Solar/Wind Harmer
27.586
944161AF1-084 GEN
Solar/Wind Harmer
2.425
959331AF2-224 GEN
Solar/Wind Harmer
10.941
972037AH1-567 GEN1
Adder
0.197
274827FISK ;RP
Adder
8.334
960591AF2-350 GEN
Solar/Wind Harmer
10.734
274800UNIV PARK;3U
Adder
6.257
274801UNIV PARK;4U
Adder
6.257
972228AH1-698 GEN2
Adder
3.974
972227AH1-698 GEN1
Adder
2.798
274687WILL CNTY;4U
Adder
29.832
274687WILL CNTY;4U
Adder
29.832
24729505KEY G4
Adder
6.921
274675JOLIET 29;7U
Adder
32.726
274675JOLIET 29;7U
Adder
31.557
274728ELWOOD EC;5P
Adder
17.497
274731ELWOOD EC;2P
Adder
17.497
274733ELWOOD EC;3P
Adder
17.497
274735ELWOOD EC;4P
Adder
17.497
276893AG1-478 C
Solar/Wind Harmer
0.585
970833AG2-524 GEN
Solar/Wind Harmer
9.285
970833AG2-524 GEN
Solar/Wind Harmer
4.318
274744AC1-111 GEN8
Adder
5.916
274746AC1-111 G10
Adder
5.916
970073AG2-061 GEN
Solar/Wind Harmer
2.414
958391AF2-133 GEN
Solar/Wind Harmer
9.401
971675AH1-338 GEN
Solar/Wind Harmer
18.559
971411AH1-196 GEN
Solar/Wind Harmer
15.466
276861AD2-134 GEN
Solar/Wind Harmer
1.84
276863AD2-134 GEN
Solar/Wind Harmer
1.84
959141AF2-205 GEN
Solar/Wind Harmer
6.232
274863CRW1-WTG
Solar/Wind Harmer
5.728
274864CRW2-WTG
Solar/Wind Harmer
5.728
971171AH1-044 GEN
Solar/Wind Harmer
20.516
276889AE2-281 GEN
Solar/Wind Harmer
1.965
274823ROCKFORD ;21
Adder
19.933
971549AH1-272 GEN
Solar/Wind Harmer
18.905
972267AH1-718 GEN
Adder
4.17
LAGNLTFEXP_LAGN->PJM
CLTF
11.364
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.562
TVALTFEXP_TVA->PJM
CLTF
5.102
NYPJM->LTFIMP_NY
CLTF
2.62
LGEELTFEXP_LGEE->PJM
CLTF
3.696
WECLTFEXP_WEC->PJM
CLTF
3.896
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.976
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.348
MECLTFEXP_MEC->PJM
CLTF
14.982
SIGELTFEXP_SIGE->PJM
CLTF
0.344
CPLELTFEXP_CPLE->PJM
CLTF
1.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
88.313

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.76 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4887.22
MW Contribution:
24.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3
270100X2-052 CT1
50/50
2.772
270101X2-052 CT2
50/50
2.772
24643105BUCHANAN
50/50
0.023
247620Y3-023
50/50
0.894
274770LINCOLN ;1U
50/50
16.29
274771LINCOLN ;2U
50/50
16.29
970349AG2-230 GEN
Solar/Wind Harmer
20.983
965681AG1-436 GEN
Solar/Wind Harmer
16.258
965791AG1-447 GEN
Solar/Wind Harmer
11.923
961051AF2-396 GEN
Solar/Wind Harmer
25.67
961051AF2-396 GEN
Solar/Wind Harmer
17.113
274805UNIV PK N;1U
Adder
8.931
274808UNIV PK N;4U
Adder
8.873
274888KELLY CRK;1U
Solar/Wind Harmer
0.72
276776AD2-060 GEN
Solar/Wind Harmer
1.316
958011AF2-095 GEN
Solar/Wind Harmer
17.77
970941AG2-585 GEN
Solar/Wind Harmer
6.787
276897AD1-100 C
Solar/Wind Harmer
30.687
274674JOLIET 9 ;6U
Adder
26.949
276893AG1-478 C
Solar/Wind Harmer
0.813
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274695ROCKY RD ;2P
Adder
19.071
274693ROCKY RD ;1P
Adder
18.884
274697ROCKY RD ;3P
Adder
5.181
274696ROCKY RD ;4P
Adder
19.521
958481AF2-142 GEN
Solar/Wind Harmer
17.9
274683WAUKEGAN ;8U
Adder
35.976
274683WAUKEGAN ;8U
Adder
30.326
962691AG1-118 GEN
Solar/Wind Harmer
35.572
958491AF2-143 GEN
Solar/Wind Harmer
17.663
276901AD2-066 C O1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
23.171
971343AH1-151 GEN
Solar/Wind Harmer
23.171
276872AE1-163_GEN1
Solar/Wind Harmer
0
270142AC1-141 CT1_
50/50
4.509
24642205MAYFLWER
50/50
0.068
944961AF1-161 GEN
50/50
5.338
962601AG1-109 GEN
50/50
5.338
274772LINCOLN ;3U
50/50
16.29
971347AH1-153 GEN
Solar/Wind Harmer
6.994
270043AE2-236 GEN
Solar/Wind Harmer
8.579
270505AE1-170 C O1
Solar/Wind Harmer
13.603
945111AF1-176 GEN
Solar/Wind Harmer
10.436
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
56.263
274724RIVER EC ;11
Adder
31.767
274752CRETE EC ;2U
Adder
14.744
274753CRETE EC ;3U
Adder
14.744
274814UNIV PK N;0U
Adder
8.99
274807UNIV PK N;3U
Adder
8.97
274811UNIV PK N;7U
Adder
8.912
970707AG2-453 GEN
Solar/Wind Harmer
40.554
972259AH1-714 GEN
Adder
33.781
274803UNIV PARK;6U
Adder
10.322
274826FISK ;BP
Adder
19.382
274887GEN-1.85
Solar/Wind Harmer
0.321
276843GEN-1.7
Solar/Wind Harmer
0.399
276806AD2-047 C O1
Solar/Wind Harmer
6.993
972038AH1-567 GEN2
Adder
0.645
939351AE1-166 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
51.877
274729ELWOOD EC;1P
Adder
28.741
274730ELWOOD EC;6P
Adder
28.742
274734ELWOOD EC;8P
Adder
28.742
274736ELWOOD EC;9P
Adder
28.742
943121AE2-341 GEN
Solar/Wind Harmer
20.341
943591AF1-030 GEN
Solar/Wind Harmer
13.527
274682WAUKEGAN ;7U
Adder
30.726
274862TOP CROP ;2U
Solar/Wind Harmer
1.61
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
2.344
274879MINONK ;1U
Solar/Wind Harmer
0.489
946671AF1-331 GEN
Solar/Wind Harmer
1.245
274855GSG-6 ;RU
Solar/Wind Harmer
0.426
274850MENDOTA H;RU
Solar/Wind Harmer
0.136
965021AG1-366 GEN
Solar/Wind Harmer
3.887
959091AF2-200 GEN
Solar/Wind Harmer
23.171
970571AG2-364 GEN
Solar/Wind Harmer
22.813
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
15.096
274767LEE CO EC;8U
Adder
14.918
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.369
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.899
965931AG1-462 GEN
Solar/Wind Harmer
27.452
971087AG2-675 GEN
Solar/Wind Harmer
5.742
965091AG1-374 GEN
Solar/Wind Harmer
32.089
959611AF2-252 GEN
Solar/Wind Harmer
3.565
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.004
971993AH1-541 GEN
Solar/Wind Harmer
4.623
970289AG2-191 GEN
Solar/Wind Harmer
1.091
24344005CKG1
50/50
12.151
270144AC1-141 ST1_
50/50
3.981
24641605TWIN BRNCH
50/50
0.032
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
16.29
274776LINCOLN ;7U
50/50
16.29
274777LINCOLN ;8U
50/50
16.29
971771AH1-392 GEN
Solar/Wind Harmer
13.087
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
24.893
970031AG2-029 GEN
Solar/Wind Harmer
6.756
972037AH1-567 GEN1
Adder
0.324
274827FISK ;RP
Adder
13.736
960591AF2-350 GEN
Solar/Wind Harmer
12.34
274800UNIV PARK;3U
Adder
10.31
274801UNIV PARK;4U
Adder
10.31
972228AH1-698 GEN2
Adder
6.548
972227AH1-698 GEN1
Adder
4.611
274687WILL CNTY;4U
Adder
49.058
274687WILL CNTY;4U
Adder
49.058
24729505KEY G4
Adder
11.387
274675JOLIET 29;7U
Adder
53.8
274675JOLIET 29;7U
Adder
51.878
274728ELWOOD EC;5P
Adder
28.742
274731ELWOOD EC;2P
Adder
28.741
274733ELWOOD EC;3P
Adder
28.741
274735ELWOOD EC;4P
Adder
28.741
970833AG2-524 GEN
Solar/Wind Harmer
13.404
970833AG2-524 GEN
Solar/Wind Harmer
8.936
274744AC1-111 GEN8
Adder
9.698
274746AC1-111 G10
Adder
9.698
970073AG2-061 GEN
Solar/Wind Harmer
3.925
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
4.551
971411AH1-196 GEN
Solar/Wind Harmer
17.505
276861AD2-134 GEN
Solar/Wind Harmer
0.208
276863AD2-134 GEN
Solar/Wind Harmer
0.208
959331AF2-224 GEN
Solar/Wind Harmer
8.163
971549AH1-272 GEN
Solar/Wind Harmer
24.049
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
23.171
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
32.233
971611AH1-305 GEN
Solar/Wind Harmer
6.82
274856ECOGROVE ;U1
Solar/Wind Harmer
0.267
926823AC1-168 GEN
Solar/Wind Harmer
1.939
970169AG2-114 GEN
Solar/Wind Harmer
11.381
971681AH1-341 GEN
Solar/Wind Harmer
18.311
972267AH1-718 GEN
Adder
6.682
276741O09 GEN1
Solar/Wind Harmer
0.394
274877BISHOP HL;1U
Solar/Wind Harmer
0.369
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
11.46
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.067
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
14.314
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.381
965041AG1-368 GEN
Solar/Wind Harmer
10.029
276668AB2-070 GEN1
Solar/Wind Harmer
0.393
276848AB2-070 GEN3
Solar/Wind Harmer
0.392
276849AB2-070 GEN2
Solar/Wind Harmer
0.393
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.884
971609AH1-304 GEN
Solar/Wind Harmer
1.618
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.159
972236AH1-702 GEN2
Adder
3.616
944541AF1-119 GEN
Solar/Wind Harmer
0.761
960971AF2-388 GEN
Solar/Wind Harmer
6.685
938861AE1-114 GEN
Solar/Wind Harmer
6.442
274764LEE CO EC;5U
Adder
15.132
274765LEE CO EC;6U
Adder
15.132
274762LEE CO EC;3U
Adder
15.096
274763LEE CO EC;4U
Adder
14.954
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.801
276645AC1-214 GEN1
Solar/Wind Harmer
0.437
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
3.547
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
4.299
960611AF2-352 GEN
Solar/Wind Harmer
3.565
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.183
944231AF1-091 GEN
Solar/Wind Harmer
23.934
970291AG2-192 GEN
Solar/Wind Harmer
1.289
970291AG2-192 GEN
Solar/Wind Harmer
0.595
270031AE2-169
Solar/Wind Harmer
5.447
270599AE1-208 GEN
Solar/Wind Harmer
9.078
276615X2-022 GEN
Solar/Wind Harmer
0.102
276838X2-022 GEN2
Solar/Wind Harmer
0.552
970241AG2-163 GEN
Solar/Wind Harmer
5.716
24344105CKG2
50/50
15.609
270143AC1-141 CT2_
50/50
4.509
24639705ELKHART HY
50/50
0.301
970521AG2-332 GEN
50/50
21.375
24307105BERRINSP G
50/50
0.039
274773LINCOLN ;4U
50/50
16.29
274774LINCOLN ;5U
50/50
16.29
957891AF2-083 GEN
Solar/Wind Harmer
21.547
945111AF1-176 GEN
Solar/Wind Harmer
22.973
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
6.687
274723RIVER EC ;12
Adder
32.136
274751CRETE EC ;1U
Adder
14.744
274754CRETE EC ;4U
Adder
14.744
274812UNIV PK N;8U
Adder
8.912
274802UNIV PARK;5U
Adder
10.322
970373AG2-245 GEN
Solar/Wind Harmer
25.838
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.799
274674JOLIET 9 ;6U
Adder
26.949
274732ELWOOD EC;7P
Adder
28.742
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.698
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.939
274682WAUKEGAN ;7U
Adder
30.726
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
18.858
962781AG1-127 GEN
Solar/Wind Harmer
11.253
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
8.816
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
15.316
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.367
971997AH1-543 GEN
Solar/Wind Harmer
6.138
965011AG1-365 GEN
Solar/Wind Harmer
11.662
957471AF2-041 GEN
Solar/Wind Harmer
34.756
959081AF2-199 GEN
Solar/Wind Harmer
11.585
971067AG2-660 GEN
Solar/Wind Harmer
3.862
274822ROCKFORD ;11
Adder
32.468
970819AG2-516 GEN
Solar/Wind Harmer
13.763
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
14.32
970569AG2-363 GEN
Solar/Wind Harmer
34.22
965651AG1-433 GEN
Solar/Wind Harmer
3.342
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
15.096
274766LEE CO EC;7U
Adder
14.918
276708O09 GEN2
Solar/Wind Harmer
0.394
276646AC1-214 GEN2
Solar/Wind Harmer
0.437
958861AF2-177 GEN
Solar/Wind Harmer
4.817
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
15.28
945371AF1-202 GEN
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.491
963741AG1-226 GEN
Solar/Wind Harmer
23.192
270594AE1-207 GEN
Solar/Wind Harmer
10.875
270032AE2-172
Solar/Wind Harmer
6.473
957381AF2-032 GEN
Solar/Wind Harmer
2.142
942481AE2-261 GEN
Solar/Wind Harmer
28.148
270004AE1-209 GEN
Solar/Wind Harmer
2.023
970825AG2-519 GEN
Solar/Wind Harmer
6.871
946031AF1-268 GEN
Solar/Wind Harmer
8.578
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.45
24695305TIMB G C
Solar/Wind Harmer
0.754
970193AG2-126 GEN
Solar/Wind Harmer
13.114
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
8.888
247521TR3_G114
Solar/Wind Harmer
0.333
965051AG1-369 GEN
Solar/Wind Harmer
4.586
944221AF1-090 GEN
Solar/Wind Harmer
5.276
964611AG1-324 GEN
Solar/Wind Harmer
3.501
247536S-71 GEN
Solar/Wind Harmer
0.329
270543AE2-219 C
Solar/Wind Harmer
5.36
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
24728505AND G1
Adder
4.25
246938BC-WTG3
Solar/Wind Harmer
0.259
270491AE1-102 GEN2
Solar/Wind Harmer
0.936
971613AH1-306 GEN
Solar/Wind Harmer
4.661
276916AD2-100_GEN
Solar/Wind Harmer
19.57
276911AD2-131_GEN
Solar/Wind Harmer
1.289
270246TR4_N_V150
Solar/Wind Harmer
0.059
270247TR4_N_V136
Solar/Wind Harmer
0.059
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.673
270201AC2-176 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
9.289
247621Y3-024
Adder
0.295
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.411
970883AG2-550 GEN
Solar/Wind Harmer
7.657
970885AG2-551 GEN
Solar/Wind Harmer
2.552
971587AH1-292 GEN
Solar/Wind Harmer
5.454
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.29
270349AD2-093_GEN
Solar/Wind Helper
1.569
270471AD2-092_GEN
Solar/Wind Helper
1.569
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.912
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.541
270024AE2-089 GEN
Solar/Wind Harmer
0.002
965911AG1-460 GEN
Solar/Wind Harmer
1.883
276903AD2-071 C
Solar/Wind Harmer
10.45
270005AE1-210 C O1
Solar/Wind Harmer
2.023
970825AG2-519 GEN
Solar/Wind Harmer
3.238
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.152
24728605AND G2
Adder
4.25
965421AG1-410 GEN
Solar/Wind Harmer
22.891
246936BC-WTG1
Solar/Wind Harmer
0.29
270489AE1-102 GEN1
Solar/Wind Harmer
0.936
970773AG2-487 GEN
Solar/Wind Harmer
1.245
970091AG2-072 GEN
Adder
68.038
LAGNLTFEXP_LAGN->PJM
CLTF
12.231
TVALTFEXP_TVA->PJM
CLTF
4.659
NYPJM->LTFIMP_NY
CLTF
2.94
LGEELTFEXP_LGEE->PJM
CLTF
4.042
WECLTFEXP_WEC->PJM
CLTF
6.289
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.78
AG2-052LTFEXP_AG2-052->PJM
LTF
0.393
AH1-155LTFEXP_AH1-155->PJM
LTF
0.59
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.285
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.325
MECLTFEXP_MEC->PJM
CLTF
22.729
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM West 2LTFEXP_CBM-W2->PJM
CBM
110.466

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.25 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2283.58
MW Contribution:
9.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727105RPMNG2
50/50
3.318
970583AG2-370 GEN
50/50
2.814
270142AC1-141 CT1_
50/50
2.029
24642205MAYFLWER
50/50
0.031
944961AF1-161 GEN
50/50
2.395
962601AG1-109 GEN
50/50
2.395
965021AG1-366 GEN
Solar/Wind Harmer
4.607
270043AE2-236 GEN
Solar/Wind Harmer
5.241
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.981
24695305TIMB G C
Solar/Wind Harmer
0.532
945111AF1-176 GEN
Solar/Wind Harmer
4.853
971347AH1-153 GEN
Solar/Wind Harmer
2.927
270505AE1-170 C O1
Solar/Wind Harmer
6.132
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.345
274752CRETE EC ;2U
Adder
6.312
274753CRETE EC ;3U
Adder
6.312
274724RIVER EC ;11
Adder
13.515
274814UNIV PK N;0U
Adder
3.826
274807UNIV PK N;3U
Adder
3.817
274811UNIV PK N;7U
Adder
3.792
274772LINCOLN ;3U
Adder
6.365
274803UNIV PARK;6U
Adder
4.369
274826FISK ;BP
Adder
8.195
972038AH1-567 GEN2
Adder
0.273
274887GEN-1.85
Solar/Wind Harmer
0.135
276843GEN-1.7
Solar/Wind Harmer
0.168
24727205RPMNG3
50/50
3.298
24729505KEY G4
50/50
6.847
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.792
959331AF2-224 GEN
Solar/Wind Harmer
9.676
963791AG1-232 GEN
Solar/Wind Harmer
12.035
970031AG2-029 GEN
Solar/Wind Harmer
4.587
965041AG1-368 GEN
Solar/Wind Harmer
8.443
270071AF1-092 GEN
Solar/Wind Harmer
14.566
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.602
971771AH1-392 GEN
Solar/Wind Harmer
5.907
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.922
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.13
274775LINCOLN ;6U
Adder
6.365
274776LINCOLN ;7U
Adder
6.365
274777LINCOLN ;8U
Adder
6.365
972037AH1-567 GEN1
Adder
0.137
274827FISK ;RP
Adder
5.808
274800UNIV PARK;3U
Adder
4.357
274801UNIV PARK;4U
Adder
4.357
960591AF2-350 GEN
Solar/Wind Harmer
5.207
972228AH1-698 GEN2
Adder
2.756
972227AH1-698 GEN1
Adder
1.941
274687WILL CNTY;4U
Adder
20.685
274687WILL CNTY;4U
Adder
20.685
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.662
274675JOLIET 29;7U
Adder
21.853
274728ELWOOD EC;5P
Adder
12.11
274731ELWOOD EC;2P
Adder
12.11
274733ELWOOD EC;3P
Adder
12.11
274735ELWOOD EC;4P
Adder
12.11
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.974
970833AG2-524 GEN
Solar/Wind Harmer
5.628
970833AG2-524 GEN
Solar/Wind Harmer
3.752
971611AH1-305 GEN
Solar/Wind Harmer
3.031
274744AC1-111 GEN8
Adder
4.068
274746AC1-111 G10
Adder
4.068
970073AG2-061 GEN
Solar/Wind Harmer
1.661
247536S-71 GEN
Solar/Wind Harmer
0.199
971411AH1-196 GEN
Solar/Wind Harmer
7.376
971675AH1-338 GEN
Solar/Wind Harmer
1.916
276861AD2-134 GEN
Solar/Wind Harmer
0.088
276863AD2-134 GEN
Solar/Wind Harmer
0.088
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.768
274823ROCKFORD ;21
Adder
13.596
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
926823AC1-168 GEN
Solar/Wind Harmer
0.821
970169AG2-114 GEN
Solar/Wind Harmer
4.823
971681AH1-341 GEN
Solar/Wind Harmer
7.736
971549AH1-272 GEN
Solar/Wind Harmer
9.898
972267AH1-718 GEN
Adder
2.828
276741O09 GEN1
Solar/Wind Harmer
0.167
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.157
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.889
946321AF1-296 GEN
Solar/Wind Harmer
2.577
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.976
270543AE2-219 C
Solar/Wind Harmer
3.137
276668AB2-070 GEN1
Solar/Wind Harmer
0.17
276848AB2-070 GEN3
Solar/Wind Harmer
0.169
276849AB2-070 GEN2
Solar/Wind Harmer
0.17
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.928
944221AF1-090 GEN
Solar/Wind Harmer
2.312
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.609
270223U2-072_GEN1
Solar/Wind Helper
0.876
270224U2-072_GEN2
Solar/Wind Helper
0.876
270227U2-072_GEN3
Solar/Wind Helper
0.876
270228U2-072_GEN4
Solar/Wind Helper
0.876
270231U2-072_GEN5
Solar/Wind Helper
0.876
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
1.968
945641AF1-229 GEN
Solar/Wind Helper
0.94
276806AD2-047 C O1
Solar/Wind Harmer
2.951
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.153
970707AG2-453 GEN
Solar/Wind Harmer
16.903
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.852
274729ELWOOD EC;1P
Adder
12.11
274730ELWOOD EC;6P
Adder
12.11
274734ELWOOD EC;8P
Adder
12.11
274736ELWOOD EC;9P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.564
946031AF1-268 GEN
Solar/Wind Harmer
4.838
943121AE2-341 GEN
Solar/Wind Harmer
8.518
943591AF1-030 GEN
Solar/Wind Harmer
5.665
270004AE1-209 GEN
Solar/Wind Harmer
1.101
274862TOP CROP ;2U
Solar/Wind Harmer
0.681
970825AG2-519 GEN
Solar/Wind Harmer
3.795
274682WAUKEGAN ;7U
Adder
12.933
276868AE1-113 GEN
Solar/Wind Harmer
0.991
274879MINONK ;1U
Solar/Wind Harmer
0.207
946671AF1-331 GEN
Solar/Wind Harmer
0.524
274855GSG-6 ;RU
Solar/Wind Harmer
0.179
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.895
959091AF2-200 GEN
Solar/Wind Harmer
9.768
970571AG2-364 GEN
Solar/Wind Harmer
9.675
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.381
274767LEE CO EC;8U
Adder
6.306
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.157
965091AG1-374 GEN
Solar/Wind Harmer
13.726
965931AG1-462 GEN
Solar/Wind Harmer
11.666
971087AG2-675 GEN
Solar/Wind Harmer
2.44
959611AF2-252 GEN
Solar/Wind Harmer
1.525
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.998
957381AF2-032 GEN
Solar/Wind Harmer
0.932
942481AE2-261 GEN
Solar/Wind Harmer
12.255
970193AG2-126 GEN
Solar/Wind Harmer
5.956
24728705AND G3
Adder
4.39
24728505AND G1
Adder
2.099
246938BC-WTG3
Solar/Wind Helper
11.083
942871AE2-306 GEN
Solar/Wind Helper
0.445
270284AF1-227 GEN1
Solar/Wind Helper
1.893
270287AF1-227 GEN3
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.334
270541AE2-072 C
Solar/Wind Helper
0.943
24727005RPMNG1
50/50
3.317
960861AF2-377 GEN
50/50
2.406
970521AG2-332 GEN
50/50
10.906
24639705ELKHART HY
50/50
0.151
270143AC1-141 CT2_
50/50
2.029
965011AG1-365 GEN
Solar/Wind Harmer
13.822
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.876
958861AF2-177 GEN
Solar/Wind Harmer
2.694
945111AF1-176 GEN
Solar/Wind Harmer
10.683
957891AF2-083 GEN
Solar/Wind Harmer
9.802
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3
970373AG2-245 GEN
Solar/Wind Harmer
11.243
274751CRETE EC ;1U
Adder
6.312
274754CRETE EC ;4U
Adder
6.312
274723RIVER EC ;12
Adder
13.681
274812UNIV PK N;8U
Adder
3.792
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.365
274774LINCOLN ;5U
Adder
6.365
274802UNIV PARK;5U
Adder
4.369
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.75
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.662
274674JOLIET 9 ;6U
Adder
11.348
274732ELWOOD EC;7P
Adder
12.11
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.364
270594AE1-207 GEN
Solar/Wind Harmer
5.699
270032AE2-172
Solar/Wind Harmer
3.392
270005AE1-210 C O1
Solar/Wind Harmer
1.101
274745AC1-111 GEN9
Adder
4.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.82
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.788
274682WAUKEGAN ;7U
Adder
12.933
274828WAUKEGAN ;BP
Adder
7.939
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.731
939401AE1-172 GEN
Solar/Wind Harmer
3.718
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.578
971997AH1-543 GEN
Solar/Wind Harmer
2.59
957471AF2-041 GEN
Solar/Wind Harmer
14.651
959081AF2-199 GEN
Solar/Wind Harmer
4.884
971067AG2-660 GEN
Solar/Wind Harmer
1.628
274822ROCKFORD ;11
Adder
13.696
276903AD2-071 C
Solar/Wind Harmer
5.426
970819AG2-516 GEN
Solar/Wind Harmer
5.809
970569AG2-363 GEN
Solar/Wind Harmer
14.512
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.381
274766LEE CO EC;7U
Adder
6.306
276708O09 GEN2
Solar/Wind Harmer
0.167
276646AC1-214 GEN2
Solar/Wind Harmer
0.185
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.519
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.287
963741AG1-226 GEN
Solar/Wind Harmer
10.473
276621W2-048 GEN
Solar/Wind Harmer
0.213
965911AG1-460 GEN
Solar/Wind Harmer
0.82
24728605AND G2
Adder
2.099
970773AG2-487 GEN
Solar/Wind Harmer
0.63
246936BC-WTG1
Solar/Wind Helper
10.897
270317AD1-130_GEN
Solar/Wind Helper
4.143
270485AE1-090_GEN
Solar/Wind Helper
0.326
270391AF1-285 GEN3
Solar/Wind Helper
0.593
270578AF1-285 GEN2
Solar/Wind Helper
0.593
270286AF1-227 GEN2
Solar/Wind Helper
0.694
960841AF2-375 GEN
Solar/Wind Helper
1.179
24729405KEY G3
50/50
0.374
24729305KEY G2
50/50
0.367
24729205KEY G1
50/50
0.366
247620Y3-023
50/50
0.467
960851AF2-376 GEN
50/50
2.095
24643105BUCHANAN
50/50
0.01
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.855
944231AF1-091 GEN
Solar/Wind Harmer
16.139
944541AF1-119 GEN
Solar/Wind Harmer
0.427
960971AF2-388 GEN
Solar/Wind Harmer
3.752
970349AG2-230 GEN
Solar/Wind Harmer
8.78
961051AF2-396 GEN
Solar/Wind Harmer
11.674
961051AF2-396 GEN
Solar/Wind Harmer
7.782
270031AE2-169
Solar/Wind Harmer
3.104
270599AE1-208 GEN
Solar/Wind Harmer
5.173
965681AG1-436 GEN
Solar/Wind Harmer
6.963
965791AG1-447 GEN
Solar/Wind Harmer
5.106
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.41
247621Y3-024
Adder
0.183
274805UNIV PK N;1U
Adder
3.801
274808UNIV PK N;4U
Adder
3.776
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.365
274771LINCOLN ;2U
Adder
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
0.304
276776AD2-060 GEN
Solar/Wind Harmer
0.555
958011AF2-095 GEN
Solar/Wind Harmer
7.498
970941AG2-585 GEN
Solar/Wind Harmer
2.864
276897AD1-100 C
Solar/Wind Harmer
12.887
274674JOLIET 9 ;6U
Adder
11.348
276893AG1-478 C
Solar/Wind Harmer
0.343
970291AG2-192 GEN
Solar/Wind Harmer
0.666
970291AG2-192 GEN
Solar/Wind Harmer
0.308
971613AH1-306 GEN
Solar/Wind Harmer
2.442
958481AF2-142 GEN
Solar/Wind Harmer
7.57
274695ROCKY RD ;2P
Adder
8.016
274693ROCKY RD ;1P
Adder
7.937
274697ROCKY RD ;3P
Adder
2.178
274696ROCKY RD ;4P
Adder
8.205
274683WAUKEGAN ;8U
Adder
15.145
274683WAUKEGAN ;8U
Adder
12.766
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
14.951
958491AF2-143 GEN
Solar/Wind Harmer
7.476
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.768
971343AH1-151 GEN
Solar/Wind Harmer
9.768
972235AH1-702 GEN1
Adder
1.755
972236AH1-702 GEN2
Adder
1.526
938861AE1-114 GEN
Solar/Wind Harmer
2.722
274764LEE CO EC;5U
Adder
6.396
274765LEE CO EC;6U
Adder
6.396
274762LEE CO EC;3U
Adder
6.381
274763LEE CO EC;4U
Adder
6.321
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.763
276645AC1-214 GEN1
Solar/Wind Harmer
0.185
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.533
942111AE2-223 GEN
Solar/Wind Harmer
1.513
960611AF2-352 GEN
Solar/Wind Harmer
1.525
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.481
970885AG2-551 GEN
Solar/Wind Harmer
1.494
970241AG2-163 GEN
Solar/Wind Harmer
2.581
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.044
276838X2-022 GEN2
Solar/Wind Harmer
0.239
276916AD2-100_GEN
Solar/Wind Harmer
8.532
276911AD2-131_GEN
Solar/Wind Harmer
0.562
945391AF1-204 GEN
Solar/Wind Harmer
4.219
970623AG2-406 GEN
Solar/Wind Harmer
0.656
971587AH1-292 GEN
Solar/Wind Harmer
2.468
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.897
270462AD2-086
Solar/Wind Helper
3.747
247522W1-056 GEN
Solar/Wind Helper
1.177
253378AE2-206_GEN
Solar/Wind Helper
0.715
270349AD2-093_GEN
Solar/Wind Helper
0.857
270471AD2-092_GEN
Solar/Wind Helper
0.857
241960AC2-195 GEN
Solar/Wind Helper
0.697
990497J1323
External Queue
1.5952997207641602
990792J1392
External Queue
5.487830638885498
LAGNLTFEXP_LAGN->PJM
CLTF
5.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.51
TVALTFEXP_TVA->PJM
CLTF
2.319
NYPJM->LTFIMP_NY
CLTF
1.264
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
AG2-052LTFEXP_AG2-052->PJM
LTF
0.172
AH1-155LTFEXP_AH1-155->PJM
LTF
0.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
70.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.933
MECLTFEXP_MEC->PJM
CLTF
9.784
SIGELTFEXP_SIGE->PJM
CLTF
0.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.835

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7443_05DUMONT 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7443_05DUMONT 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.31 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3447.28
MW Contribution:
22.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
3.387
970521AG2-332 GEN
50/50
16.25
24639705ELKHART HY
50/50
0.226
24727005RPMNG1
50/50
1.31
270143AC1-141 CT2_
50/50
3.129
965011AG1-365 GEN
Solar/Wind Harmer
18.284
965651AG1-433 GEN
Solar/Wind Harmer
9.79
958861AF2-177 GEN
Solar/Wind Harmer
19
945371AF1-202 GEN
Solar/Wind Harmer
11.421
270024AE2-089 GEN
Solar/Wind Harmer
6.78
270005AE1-210 C O1
Solar/Wind Harmer
7.652
270216AD2-079_GEN
Solar/Wind Harmer
0.82
970825AG2-519 GEN
Solar/Wind Harmer
2.798
945111AF1-176 GEN
Solar/Wind Harmer
23.522
957891AF2-083 GEN
Solar/Wind Harmer
19.527
270449AD2-020 GEN
Solar/Wind Harmer
3.602
943021AE2-325 GEN
Solar/Wind Harmer
4.68
270594AE1-207 GEN
Solar/Wind Harmer
17.413
270032AE2-172
Solar/Wind Harmer
5.963
970583AG2-370 GEN
50/50
3.658
24727105RPMNG2
50/50
1.311
270142AC1-141 CT1_
50/50
3.129
944961AF1-161 GEN
50/50
3.736
962601AG1-109 GEN
50/50
3.736
24642205MAYFLWER
50/50
0.047
944531AF1-118 GEN
Solar/Wind Harmer
70.411
270043AE2-236 GEN
Solar/Wind Harmer
10.84
965021AG1-366 GEN
Solar/Wind Harmer
4.252
270063AE2-323 C
Solar/Wind Harmer
3.377
24695305TIMB G C
Solar/Wind Harmer
4.71
270004AE1-209 GEN
Solar/Wind Harmer
7.652
247643Z2-116 C
Solar/Wind Harmer
0.094
970825AG2-519 GEN
Solar/Wind Harmer
7.511
962031AG1-047 GEN
Solar/Wind Harmer
4.022
957741AF2-068 GEN
Solar/Wind Harmer
19.956
946031AF1-268 GEN
Solar/Wind Harmer
11.028
945111AF1-176 GEN
Solar/Wind Harmer
7.455
270505AE1-170 C O1
Solar/Wind Harmer
19.458
965461AG1-414 GEN
Solar/Wind Harmer
2.876
970289AG2-191 GEN
Solar/Wind Harmer
0.973
971347AH1-153 GEN
Solar/Wind Harmer
6.284
247642Z2-115 C
Solar/Wind Harmer
0.08
24379505HDWTR1G C
Solar/Wind Harmer
9.909
270240V3-007_GEN2
Solar/Wind Harmer
7.753
24441505OLIV SLR
Solar/Wind Harmer
0.166
270044AE2-322 C
Solar/Wind Harmer
1.609
246938BC-WTG3
Solar/Wind Harmer
4.736
270491AE1-102 GEN2
Solar/Wind Harmer
1.547
958091AF2-103 GEN
Solar/Wind Harmer
0.19
972231SS25-0005
Solar/Wind Harmer
10.716
972181SS23-001
Solar/Wind Harmer
6.698
274752CRETE EC ;2U
Adder
5.519
274753CRETE EC ;3U
Adder
5.519
274724RIVER EC ;11
Adder
19.865
964401AG1-302 GEN
Solar/Wind Harmer
10.14
274814UNIV PK N;0U
Adder
5.624
274807UNIV PK N;3U
Adder
5.612
274811UNIV PK N;7U
Adder
5.575
276164X3-005 C
Solar/Wind Harmer
0.78
274803UNIV PARK;6U
Adder
6.408
274826FISK ;BP
Adder
12.013
972038AH1-567 GEN2
Adder
0.4
274772LINCOLN ;3U
Adder
6.788
274887GEN-1.85
Solar/Wind Harmer
5.824
276772AC2-154 GEN
Solar/Wind Harmer
3.051
276843GEN-1.7
Solar/Wind Harmer
0.627
276806AD2-047 C O1
Solar/Wind Harmer
11.694
972259AH1-714 GEN
Adder
20.661
274676JOLIET 29;8U
Adder
31.983
939351AE1-166 GEN
Solar/Wind Harmer
6.408
970707AG2-453 GEN
Solar/Wind Harmer
30.235
274730ELWOOD EC;6P
Adder
17.731
274734ELWOOD EC;8P
Adder
17.731
274736ELWOOD EC;9P
Adder
17.731
274729ELWOOD EC;1P
Adder
17.73
943121AE2-341 GEN
Solar/Wind Harmer
15.942
943591AF1-030 GEN
Solar/Wind Harmer
10.628
274862TOP CROP ;2U
Solar/Wind Harmer
5.367
274682WAUKEGAN ;7U
Adder
18.924
24690905MDL-1G C
Solar/Wind Harmer
8.429
970781AG2-491 GEN
Solar/Wind Harmer
10.499
274760LEE CO EC;1U
Adder
9.359
274767LEE CO EC;8U
Adder
9.249
24728705AND G3
Adder
7.821
24728505AND G1
Adder
3.739
23906402RICHG1
Adder
0.88
23906502RICHG2&3
Adder
0.873
270284AF1-227 GEN1
Solar/Wind Helper
1.173
270287AF1-227 GEN3
Solar/Wind Helper
0.43
942081AE2-220 GEN
Solar/Wind Harmer
8.015
270209AC1-174_GEN
Solar/Wind Harmer
5.1
270437AC2-090 C
Solar/Wind Harmer
6.995
270239V3-007_GEN1
Solar/Wind Harmer
2.156
965421AG1-410 GEN
Solar/Wind Harmer
37.54
24441205WTRV SLR C
Solar/Wind Harmer
0.168
276903AD2-071 C
Solar/Wind Harmer
12.221
270258AD1-119 GEN
Solar/Wind Harmer
2.454
246936BC-WTG1
Solar/Wind Harmer
4.655
270489AE1-102 GEN1
Solar/Wind Harmer
1.547
970373AG2-245 GEN
Solar/Wind Harmer
24.25
270055AF2-134 C O1
Solar/Wind Harmer
3.437
274751CRETE EC ;1U
Adder
5.519
274754CRETE EC ;4U
Adder
5.519
274723RIVER EC ;12
Adder
20.108
958381AF2-132 GEN
Solar/Wind Harmer
10.14
964861AG1-349 GEN
Solar/Wind Harmer
8.772
971917AH1-482 GEN
Solar/Wind Harmer
10.12
274812UNIV PK N;8U
Adder
5.575
274802UNIV PARK;5U
Adder
6.408
972207SS24-0001
Solar/Wind Harmer
24.135
274773LINCOLN ;4U
Adder
6.788
274774LINCOLN ;5U
Adder
6.788
940581AE2-045 GEN
Solar/Wind Harmer
11.134
971605AH1-302 GEN
Solar/Wind Harmer
9.52
274676JOLIET 29;8U
Adder
33.167
941551AE2-152 GEN
Solar/Wind Harmer
4.9
274674JOLIET 9 ;6U
Adder
16.609
274732ELWOOD EC;7P
Adder
17.731
274871GR RIDGE ;2U
Solar/Wind Harmer
8.237
274847GR RIDGE ;BU
Solar/Wind Harmer
5.417
274745AC1-111 GEN9
Adder
5.943
276694AA1-018 GEN2
Solar/Wind Harmer
6.698
276691AA1-018 GEN1
Solar/Wind Harmer
0.801
274861TOP CROP ;1U
Solar/Wind Harmer
6.429
274682WAUKEGAN ;7U
Adder
18.924
274828WAUKEGAN ;BP
Adder
11.616
24791305MDL-5G
Solar/Wind Harmer
2.531
276805AD2-038 GEN
Solar/Wind Harmer
5.38
274822ROCKFORD ;11
Adder
20.064
274761LEE CO EC;2U
Adder
9.359
274766LEE CO EC;7U
Adder
9.249
24728605AND G2
Adder
3.739
23906502RICHG2&3
Adder
0.873
970091AG2-072 GEN
Adder
47.041
23920202STRYCT
Adder
0.787
270286AF1-227 GEN2
Solar/Wind Helper
0.43
270520AE2-214 GEN
Solar/Wind Helper
1.202
24729505KEY G4
50/50
13.446
24727205RPMNG3
50/50
1.303
24653605MOTTVILLE
50/50
0.005
24641605TWIN BRNCH
50/50
0.023
270144AC1-141 ST1_
50/50
2.763
270071AF1-092 GEN
Solar/Wind Harmer
28.587
959331AF2-224 GEN
Solar/Wind Harmer
18.284
958711AF2-162 GEN
Solar/Wind Harmer
1.812
970031AG2-029 GEN
Solar/Wind Harmer
41.433
945581AF1-223 GEN
Solar/Wind Harmer
7.424
963791AG1-232 GEN
Solar/Wind Harmer
21.919
965041AG1-368 GEN
Solar/Wind Harmer
15.73
247521TR3_G114
Solar/Wind Harmer
4.891
270191TR4_S_V150
Solar/Wind Harmer
4.365
965051AG1-369 GEN
Solar/Wind Harmer
7.267
961761AG1-017 GEN
Solar/Wind Harmer
0.569
964611AG1-324 GEN
Solar/Wind Harmer
5.187
971771AH1-392 GEN
Solar/Wind Harmer
11.667
944161AF1-084 GEN
Solar/Wind Harmer
2.814
970289AG2-191 GEN
Solar/Wind Harmer
2.41
270526AF1-158 GEN
Solar/Wind Harmer
5.674
270404AC1-167 GEN
Solar/Wind Harmer
1.327
247536S-71 GEN
Solar/Wind Harmer
4.946
960681AF2-359 GEN
Solar/Wind Harmer
4.549
971549AH1-272 GEN
Solar/Wind Harmer
22.038
957201AF2-014 GEN
Solar/Wind Harmer
5.398
270435AC2-044 GEN
Solar/Wind Harmer
2.38
270007AE1-245 C
Solar/Wind Harmer
6.335
270543AE2-219 C
Solar/Wind Harmer
11.387
958391AF2-133 GEN
Solar/Wind Harmer
10.051
959141AF2-205 GEN
Solar/Wind Harmer
6.656
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.513
274800UNIV PARK;3U
Adder
6.385
274801UNIV PARK;4U
Adder
6.385
274775LINCOLN ;6U
Adder
6.788
274776LINCOLN ;7U
Adder
6.788
274777LINCOLN ;8U
Adder
6.788
960591AF2-350 GEN
Solar/Wind Harmer
10.932
972228AH1-698 GEN2
Adder
4.033
972227AH1-698 GEN1
Adder
2.84
274687WILL CNTY;4U
Adder
30.287
274687WILL CNTY;4U
Adder
30.287
274675JOLIET 29;7U
Adder
33.168
274675JOLIET 29;7U
Adder
31.983
276893AG1-478 C
Solar/Wind Harmer
0.594
274728ELWOOD EC;5P
Adder
17.731
274731ELWOOD EC;2P
Adder
17.73
274733ELWOOD EC;3P
Adder
17.73
274735ELWOOD EC;4P
Adder
17.73
970833AG2-524 GEN
Solar/Wind Harmer
9.36
970833AG2-524 GEN
Solar/Wind Harmer
4.354
274744AC1-111 GEN8
Adder
5.943
274746AC1-111 G10
Adder
5.943
946581AF1-322 GEN
Solar/Wind Harmer
10.743
24691005MDL-2G C
Solar/Wind Harmer
3.882
274823ROCKFORD ;21
Adder
19.918
972267AH1-718 GEN
Adder
4.15
970073AG2-061 GEN
Solar/Wind Harmer
0.945
24729405KEY G3
50/50
0.734
24729305KEY G2
50/50
0.722
24729205KEY G1
50/50
0.718
247620Y3-023
50/50
0.693
960851AF2-376 GEN
50/50
3.281
24643105BUCHANAN
50/50
0.016
247621Y3-024
50/50
0.324
944541AF1-119 GEN
Solar/Wind Harmer
7.5
960971AF2-388 GEN
Solar/Wind Harmer
19.579
942221AE2-234 GEN
Solar/Wind Harmer
5.649
944231AF1-091 GEN
Solar/Wind Harmer
27.774
270031AE2-169
Solar/Wind Harmer
11.918
270599AE1-208 GEN
Solar/Wind Harmer
11.918
270246TR4_N_V150
Solar/Wind Harmer
1.238
270247TR4_N_V136
Solar/Wind Harmer
1.238
270201AC2-176 GEN
Solar/Wind Harmer
6.838
964611AG1-324 GEN
Solar/Wind Harmer
0.696
961051AF2-396 GEN
Solar/Wind Harmer
20.595
961051AF2-396 GEN
Solar/Wind Harmer
9.579
970291AG2-192 GEN
Solar/Wind Harmer
1.649
970291AG2-192 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
18.853
926881AC1-175 GEN
Solar/Wind Harmer
6.995
24725505WLD G2 C
Solar/Wind Harmer
4.822
24699105WLD G1 C
Solar/Wind Harmer
4.765
965681AG1-436 GEN
Solar/Wind Harmer
15.047
965791AG1-447 GEN
Solar/Wind Harmer
7.699
246937BC-WTG2
Solar/Wind Harmer
4.655
247607V1-011 GEN
Solar/Wind Harmer
4.641
270383AD1-128 GEN
Solar/Wind Harmer
7.127
970883AG2-550 GEN
Solar/Wind Harmer
11.387
970885AG2-551 GEN
Solar/Wind Harmer
2.648
270535AF1-215 GEN1
Solar/Wind Harmer
5.155
270536AF1-215 GEN2
Solar/Wind Harmer
5.155
274805UNIV PK N;1U
Adder
5.587
274808UNIV PK N;4U
Adder
5.551
274770LINCOLN ;1U
Adder
6.788
274771LINCOLN ;2U
Adder
6.788
274888KELLY CRK;1U
Solar/Wind Harmer
6.451
276776AD2-060 GEN
Solar/Wind Harmer
0.458
958011AF2-095 GEN
Solar/Wind Harmer
15.741
970941AG2-585 GEN
Solar/Wind Harmer
6.012
276897AD1-100 C
Solar/Wind Harmer
50.193
276893AG1-478 C
Solar/Wind Harmer
0.473
274674JOLIET 9 ;6U
Adder
16.609
945421AF1-207 GEN
Solar/Wind Harmer
14.979
957841AF2-078 GEN
Solar/Wind Harmer
6.448
958481AF2-142 GEN
Solar/Wind Harmer
15.922
942801AE2-298 GEN
Solar/Wind Harmer
1.595
274695ROCKY RD ;2P
Adder
11.722
274693ROCKY RD ;1P
Adder
11.606
274697ROCKY RD ;3P
Adder
3.184
274696ROCKY RD ;4P
Adder
11.998
274683WAUKEGAN ;8U
Adder
22.161
274683WAUKEGAN ;8U
Adder
18.68
270180AB1-006 GEN1
Solar/Wind Harmer
7.551
24697605MDL-3G C
Solar/Wind Harmer
3.87
24755605MDL-5G
Solar/Wind Harmer
2.531
24697905MDL-4G C
Solar/Wind Harmer
2.409
270181AB1-006 GEN2
Solar/Wind Harmer
0.751
972235AH1-702 GEN1
Adder
2.571
972236AH1-702 GEN2
Adder
2.236
274764LEE CO EC;5U
Adder
9.381
274765LEE CO EC;6U
Adder
9.381
274762LEE CO EC;3U
Adder
9.359
274763LEE CO EC;4U
Adder
9.271
24728805RICHG1
Adder
3.096
24728905RICHG2
Adder
3.096
270349AD2-093_GEN
Solar/Wind Helper
1.08
270471AD2-092_GEN
Solar/Wind Helper
1.08
270054AF2-122 C O1
Solar/Wind Helper
0.78
946101AF1-275 GEN
Solar/Wind Helper
0.301
958491AF2-143 GEN
Solar/Wind Harmer
6.092
990497J1323
External Queue
1.9189454317092896
LAGNLTFEXP_LAGN->PJM
CLTF
8.355
TVALTFEXP_TVA->PJM
CLTF
3.311
NYPJM->LTFIMP_NY
CLTF
1.987
LGEELTFEXP_LGEE->PJM
CLTF
3.249
WECLTFEXP_WEC->PJM
CLTF
3.892
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.513
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.387
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.395
MECLTFEXP_MEC->PJM
CLTF
14.451
SIGELTFEXP_SIGE->PJM
CLTF
0.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.342

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7442_05SORENS 765_K2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7442_05SORENS 765_K2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.22 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3444.48
MW Contribution:
21.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
3.382
970521AG2-332 GEN
50/50
16.165
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.308
270143AC1-141 CT2_
50/50
3.096
965011AG1-365 GEN
Solar/Wind Harmer
18.262
965651AG1-433 GEN
Solar/Wind Harmer
9.789
958861AF2-177 GEN
Solar/Wind Harmer
18.999
945371AF1-202 GEN
Solar/Wind Harmer
11.422
270024AE2-089 GEN
Solar/Wind Harmer
6.779
270005AE1-210 C O1
Solar/Wind Harmer
7.655
270216AD2-079_GEN
Solar/Wind Harmer
0.816
970825AG2-519 GEN
Solar/Wind Harmer
2.799
945111AF1-176 GEN
Solar/Wind Harmer
23.333
957891AF2-083 GEN
Solar/Wind Harmer
19.366
270594AE1-207 GEN
Solar/Wind Harmer
17.44
270032AE2-172
Solar/Wind Harmer
5.973
270449AD2-020 GEN
Solar/Wind Harmer
3.568
943021AE2-325 GEN
Solar/Wind Harmer
4.637
942081AE2-220 GEN
Solar/Wind Harmer
8.019
270209AC1-174_GEN
Solar/Wind Harmer
5.103
270437AC2-090 C
Solar/Wind Harmer
6.998
270239V3-007_GEN1
Solar/Wind Harmer
2.158
965421AG1-410 GEN
Solar/Wind Harmer
37.481
24441205WTRV SLR C
Solar/Wind Harmer
0.166
276903AD2-071 C
Solar/Wind Harmer
12.241
270258AD1-119 GEN
Solar/Wind Harmer
2.449
246936BC-WTG1
Solar/Wind Harmer
4.648
270489AE1-102 GEN1
Solar/Wind Harmer
1.545
970373AG2-245 GEN
Solar/Wind Harmer
24.219
270055AF2-134 C O1
Solar/Wind Harmer
3.435
274751CRETE EC ;1U
Adder
5.533
274754CRETE EC ;4U
Adder
5.533
274723RIVER EC ;12
Adder
20.174
958381AF2-132 GEN
Solar/Wind Harmer
10.14
274812UNIV PK N;8U
Adder
5.593
964861AG1-349 GEN
Solar/Wind Harmer
8.773
971917AH1-482 GEN
Solar/Wind Harmer
10.122
274802UNIV PARK;5U
Adder
6.433
972207SS24-0001
Solar/Wind Harmer
24.27
274773LINCOLN ;4U
Adder
6.826
274774LINCOLN ;5U
Adder
6.826
970583AG2-370 GEN
50/50
3.653
24727105RPMNG2
50/50
1.309
270142AC1-141 CT1_
50/50
3.096
24642205MAYFLWER
50/50
0.047
944961AF1-161 GEN
50/50
3.701
962601AG1-109 GEN
50/50
3.701
944531AF1-118 GEN
Solar/Wind Harmer
70.391
270043AE2-236 GEN
Solar/Wind Harmer
10.829
965021AG1-366 GEN
Solar/Wind Harmer
4.247
270063AE2-323 C
Solar/Wind Harmer
3.366
24695305TIMB G C
Solar/Wind Harmer
4.703
270004AE1-209 GEN
Solar/Wind Harmer
7.655
247643Z2-116 C
Solar/Wind Harmer
0.094
970825AG2-519 GEN
Solar/Wind Harmer
7.516
962031AG1-047 GEN
Solar/Wind Harmer
4.023
957741AF2-068 GEN
Solar/Wind Harmer
19.961
946031AF1-268 GEN
Solar/Wind Harmer
11.033
945111AF1-176 GEN
Solar/Wind Harmer
7.395
270505AE1-170 C O1
Solar/Wind Harmer
19.285
965461AG1-414 GEN
Solar/Wind Harmer
2.881
970289AG2-191 GEN
Solar/Wind Harmer
0.975
971347AH1-153 GEN
Solar/Wind Harmer
6.301
247642Z2-115 C
Solar/Wind Harmer
0.08
24379505HDWTR1G C
Solar/Wind Harmer
9.914
270240V3-007_GEN2
Solar/Wind Harmer
7.757
24441505OLIV SLR
Solar/Wind Harmer
0.165
270044AE2-322 C
Solar/Wind Harmer
1.606
246938BC-WTG3
Solar/Wind Harmer
4.728
270491AE1-102 GEN2
Solar/Wind Harmer
1.545
958091AF2-103 GEN
Solar/Wind Harmer
0.189
972231SS25-0005
Solar/Wind Harmer
10.742
972181SS23-001
Solar/Wind Harmer
6.714
274752CRETE EC ;2U
Adder
5.533
274753CRETE EC ;3U
Adder
5.533
274724RIVER EC ;11
Adder
19.931
964401AG1-302 GEN
Solar/Wind Harmer
10.14
274814UNIV PK N;0U
Adder
5.641
274807UNIV PK N;3U
Adder
5.629
274811UNIV PK N;7U
Adder
5.593
276164X3-005 C
Solar/Wind Harmer
0.783
274803UNIV PARK;6U
Adder
6.433
274826FISK ;BP
Adder
12.06
274772LINCOLN ;3U
Adder
6.826
972038AH1-567 GEN2
Adder
0.401
274887GEN-1.85
Solar/Wind Harmer
5.848
276772AC2-154 GEN
Solar/Wind Harmer
3.063
276843GEN-1.7
Solar/Wind Harmer
0.629
24729405KEY G3
50/50
0.734
24729305KEY G2
50/50
0.721
24729205KEY G1
50/50
0.718
247620Y3-023
50/50
0.69
960851AF2-376 GEN
50/50
3.277
24643105BUCHANAN
50/50
0.016
247621Y3-024
50/50
0.324
944541AF1-119 GEN
Solar/Wind Harmer
7.499
960971AF2-388 GEN
Solar/Wind Harmer
19.578
942221AE2-234 GEN
Solar/Wind Harmer
5.648
944231AF1-091 GEN
Solar/Wind Harmer
27.723
270031AE2-169
Solar/Wind Harmer
11.922
270599AE1-208 GEN
Solar/Wind Harmer
11.922
270246TR4_N_V150
Solar/Wind Harmer
1.236
270247TR4_N_V136
Solar/Wind Harmer
1.236
270201AC2-176 GEN
Solar/Wind Harmer
6.839
964611AG1-324 GEN
Solar/Wind Harmer
0.696
961051AF2-396 GEN
Solar/Wind Harmer
20.413
961051AF2-396 GEN
Solar/Wind Harmer
9.495
970291AG2-192 GEN
Solar/Wind Harmer
1.652
970291AG2-192 GEN
Solar/Wind Harmer
0.532
970349AG2-230 GEN
Solar/Wind Harmer
18.902
926881AC1-175 GEN
Solar/Wind Harmer
6.998
24725505WLD G2 C
Solar/Wind Harmer
4.829
24699105WLD G1 C
Solar/Wind Harmer
4.772
965681AG1-436 GEN
Solar/Wind Harmer
15.008
965791AG1-447 GEN
Solar/Wind Harmer
7.678
246937BC-WTG2
Solar/Wind Harmer
4.648
247607V1-011 GEN
Solar/Wind Harmer
4.633
270383AD1-128 GEN
Solar/Wind Harmer
7.132
970883AG2-550 GEN
Solar/Wind Harmer
11.391
970885AG2-551 GEN
Solar/Wind Harmer
2.649
270535AF1-215 GEN1
Solar/Wind Harmer
5.152
270536AF1-215 GEN2
Solar/Wind Harmer
5.152
274805UNIV PK N;1U
Adder
5.605
274808UNIV PK N;4U
Adder
5.568
274770LINCOLN ;1U
Adder
6.826
274771LINCOLN ;2U
Adder
6.826
274888KELLY CRK;1U
Solar/Wind Harmer
6.478
276776AD2-060 GEN
Solar/Wind Harmer
0.46
958011AF2-095 GEN
Solar/Wind Harmer
15.807
276806AD2-047 C O1
Solar/Wind Harmer
11.743
24729505KEY G4
50/50
13.443
24727205RPMNG3
50/50
1.301
24653605MOTTVILLE
50/50
0.005
24641605TWIN BRNCH
50/50
0.023
270144AC1-141 ST1_
50/50
2.734
270071AF1-092 GEN
Solar/Wind Harmer
28.591
959331AF2-224 GEN
Solar/Wind Harmer
18.262
958711AF2-162 GEN
Solar/Wind Harmer
1.812
970031AG2-029 GEN
Solar/Wind Harmer
41.334
945581AF1-223 GEN
Solar/Wind Harmer
7.425
963791AG1-232 GEN
Solar/Wind Harmer
21.902
965041AG1-368 GEN
Solar/Wind Harmer
15.709
247521TR3_G114
Solar/Wind Harmer
4.885
270191TR4_S_V150
Solar/Wind Harmer
4.359
965051AG1-369 GEN
Solar/Wind Harmer
7.258
961761AG1-017 GEN
Solar/Wind Harmer
0.57
964611AG1-324 GEN
Solar/Wind Harmer
5.189
971771AH1-392 GEN
Solar/Wind Harmer
11.607
970289AG2-191 GEN
Solar/Wind Harmer
2.414
944161AF1-084 GEN
Solar/Wind Harmer
2.786
270526AF1-158 GEN
Solar/Wind Harmer
5.65
247536S-71 GEN
Solar/Wind Harmer
4.948
270404AC1-167 GEN
Solar/Wind Harmer
1.324
960681AF2-359 GEN
Solar/Wind Harmer
4.537
957201AF2-014 GEN
Solar/Wind Harmer
5.389
270435AC2-044 GEN
Solar/Wind Harmer
2.376
971549AH1-272 GEN
Solar/Wind Harmer
21.886
270007AE1-245 C
Solar/Wind Harmer
6.325
270543AE2-219 C
Solar/Wind Harmer
11.391
958391AF2-133 GEN
Solar/Wind Harmer
10.055
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.547
959141AF2-205 GEN
Solar/Wind Harmer
6.661
274775LINCOLN ;6U
Adder
6.826
274776LINCOLN ;7U
Adder
6.826
274777LINCOLN ;8U
Adder
6.826
274800UNIV PARK;3U
Adder
6.411
274801UNIV PARK;4U
Adder
6.411
940581AE2-045 GEN
Solar/Wind Harmer
11.146
971605AH1-302 GEN
Solar/Wind Harmer
9.53
274676JOLIET 29;8U
Adder
33.312
941551AE2-152 GEN
Solar/Wind Harmer
4.923
274674JOLIET 9 ;6U
Adder
16.683
274732ELWOOD EC;7P
Adder
17.809
274871GR RIDGE ;2U
Solar/Wind Harmer
8.276
274847GR RIDGE ;BU
Solar/Wind Harmer
5.442
274745AC1-111 GEN9
Adder
5.972
276694AA1-018 GEN2
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.804
274861TOP CROP ;1U
Solar/Wind Harmer
6.456
274682WAUKEGAN ;7U
Adder
19.011
274828WAUKEGAN ;BP
Adder
11.67
276805AD2-038 GEN
Solar/Wind Harmer
5.403
24791305MDL-5G
Solar/Wind Harmer
2.537
274822ROCKFORD ;11
Adder
20.159
274761LEE CO EC;2U
Adder
9.403
274766LEE CO EC;7U
Adder
9.292
24728605AND G2
Adder
3.747
23906502RICHG2&3
Adder
0.869
970091AG2-072 GEN
Adder
47.294
23920202STRYCT
Adder
0.781
270286AF1-227 GEN2
Solar/Wind Helper
0.431
270520AE2-214 GEN
Solar/Wind Helper
1.202
960591AF2-350 GEN
Solar/Wind Harmer
10.977
972228AH1-698 GEN2
Adder
4.051
972227AH1-698 GEN1
Adder
2.852
274687WILL CNTY;4U
Adder
30.416
274687WILL CNTY;4U
Adder
30.416
274675JOLIET 29;7U
Adder
33.312
274675JOLIET 29;7U
Adder
32.122
276893AG1-478 C
Solar/Wind Harmer
0.596
274728ELWOOD EC;5P
Adder
17.809
274731ELWOOD EC;2P
Adder
17.808
274733ELWOOD EC;3P
Adder
17.808
274735ELWOOD EC;4P
Adder
17.808
970833AG2-524 GEN
Solar/Wind Harmer
9.404
970833AG2-524 GEN
Solar/Wind Harmer
4.374
274744AC1-111 GEN8
Adder
5.972
274746AC1-111 G10
Adder
5.972
970073AG2-061 GEN
Solar/Wind Harmer
2.45
946581AF1-322 GEN
Solar/Wind Harmer
10.767
24691005MDL-2G C
Solar/Wind Harmer
3.891
274823ROCKFORD ;21
Adder
20.012
972267AH1-718 GEN
Adder
4.17
970941AG2-585 GEN
Solar/Wind Harmer
6.037
276897AD1-100 C
Solar/Wind Harmer
50.428
276893AG1-478 C
Solar/Wind Harmer
0.475
274674JOLIET 9 ;6U
Adder
16.683
945421AF1-207 GEN
Solar/Wind Harmer
15.011
957841AF2-078 GEN
Solar/Wind Harmer
6.462
958481AF2-142 GEN
Solar/Wind Harmer
15.989
274696ROCKY RD ;4P
Adder
12.055
274695ROCKY RD ;2P
Adder
11.777
274693ROCKY RD ;1P
Adder
11.662
274697ROCKY RD ;3P
Adder
3.199
274683WAUKEGAN ;8U
Adder
22.263
274683WAUKEGAN ;8U
Adder
18.767
958491AF2-143 GEN
Solar/Wind Harmer
15.803
270180AB1-006 GEN1
Solar/Wind Harmer
7.568
24697605MDL-3G C
Solar/Wind Harmer
3.879
24755605MDL-5G
Solar/Wind Harmer
2.537
24697905MDL-4G C
Solar/Wind Harmer
2.415
270181AB1-006 GEN2
Solar/Wind Harmer
0.753
972235AH1-702 GEN1
Adder
2.583
972236AH1-702 GEN2
Adder
2.246
274764LEE CO EC;5U
Adder
9.425
274765LEE CO EC;6U
Adder
9.425
274762LEE CO EC;3U
Adder
9.403
274763LEE CO EC;4U
Adder
9.314
24728805RICHG1
Adder
3.1
24728905RICHG2
Adder
3.1
270349AD2-093_GEN
Solar/Wind Helper
1.081
270471AD2-092_GEN
Solar/Wind Helper
1.081
270054AF2-122 C O1
Solar/Wind Helper
0.78
946101AF1-275 GEN
Solar/Wind Helper
0.301
972259AH1-714 GEN
Adder
20.761
274676JOLIET 29;8U
Adder
32.122
939351AE1-166 GEN
Solar/Wind Harmer
6.438
970707AG2-453 GEN
Solar/Wind Harmer
30.394
274730ELWOOD EC;6P
Adder
17.809
274734ELWOOD EC;8P
Adder
17.809
274736ELWOOD EC;9P
Adder
17.809
274729ELWOOD EC;1P
Adder
17.808
943121AE2-341 GEN
Solar/Wind Harmer
16.022
943591AF1-030 GEN
Solar/Wind Harmer
10.681
274862TOP CROP ;2U
Solar/Wind Harmer
5.39
274682WAUKEGAN ;7U
Adder
19.011
24690905MDL-1G C
Solar/Wind Harmer
8.448
274760LEE CO EC;1U
Adder
9.403
274767LEE CO EC;8U
Adder
9.292
24728705AND G3
Adder
7.836
24728505AND G1
Adder
3.747
23906402RICHG1
Adder
0.876
23906502RICHG2&3
Adder
0.869
270284AF1-227 GEN1
Solar/Wind Helper
1.175
270287AF1-227 GEN3
Solar/Wind Helper
0.431
970781AG2-491 GEN
Solar/Wind Harmer
0.942
990497J1323
External Queue
1.9028279781341553
LAGNLTFEXP_LAGN->PJM
CLTF
8.402
TVALTFEXP_TVA->PJM
CLTF
3.331
NYPJM->LTFIMP_NY
CLTF
1.989
LGEELTFEXP_LGEE->PJM
CLTF
3.263
WECLTFEXP_WEC->PJM
CLTF
3.91
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.333
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.471
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.688

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7444_05DUMONT 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7444_05DUMONT 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.06 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3439.41
MW Contribution:
22.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
3.663
24727105RPMNG2
50/50
1.313
270142AC1-141 CT1_
50/50
3.115
24642205MAYFLWER
50/50
0.047
944961AF1-161 GEN
50/50
3.724
962601AG1-109 GEN
50/50
3.724
944531AF1-118 GEN
Solar/Wind Harmer
70.518
270043AE2-236 GEN
Solar/Wind Harmer
10.858
965021AG1-366 GEN
Solar/Wind Harmer
4.258
270063AE2-323 C
Solar/Wind Harmer
3.386
24695305TIMB G C
Solar/Wind Harmer
4.717
270004AE1-209 GEN
Solar/Wind Harmer
7.662
247643Z2-116 C
Solar/Wind Harmer
0.094
970825AG2-519 GEN
Solar/Wind Harmer
7.521
962031AG1-047 GEN
Solar/Wind Harmer
4.028
957741AF2-068 GEN
Solar/Wind Harmer
19.982
946031AF1-268 GEN
Solar/Wind Harmer
11.042
945111AF1-176 GEN
Solar/Wind Harmer
7.443
270505AE1-170 C O1
Solar/Wind Harmer
19.413
960861AF2-377 GEN
50/50
3.392
970521AG2-332 GEN
50/50
16.268
24639705ELKHART HY
50/50
0.226
24727005RPMNG1
50/50
1.312
270143AC1-141 CT2_
50/50
3.115
965011AG1-365 GEN
Solar/Wind Harmer
18.309
965651AG1-433 GEN
Solar/Wind Harmer
9.804
958861AF2-177 GEN
Solar/Wind Harmer
19.027
945371AF1-202 GEN
Solar/Wind Harmer
11.437
270024AE2-089 GEN
Solar/Wind Harmer
6.789
270005AE1-210 C O1
Solar/Wind Harmer
7.662
270216AD2-079_GEN
Solar/Wind Harmer
0.823
970825AG2-519 GEN
Solar/Wind Harmer
2.801
945111AF1-176 GEN
Solar/Wind Harmer
23.483
957891AF2-083 GEN
Solar/Wind Harmer
19.496
971347AH1-153 GEN
Solar/Wind Harmer
6.431
965461AG1-414 GEN
Solar/Wind Harmer
2.877
970289AG2-191 GEN
Solar/Wind Harmer
0.974
247642Z2-115 C
Solar/Wind Harmer
0.08
24379505HDWTR1G C
Solar/Wind Harmer
9.923
270240V3-007_GEN2
Solar/Wind Harmer
7.763
24441505OLIV SLR
Solar/Wind Harmer
0.167
270044AE2-322 C
Solar/Wind Harmer
1.611
246938BC-WTG3
Solar/Wind Harmer
4.743
270491AE1-102 GEN2
Solar/Wind Harmer
1.55
958091AF2-103 GEN
Solar/Wind Harmer
0.19
972231SS25-0005
Solar/Wind Harmer
10.76
972181SS23-001
Solar/Wind Harmer
6.725
274752CRETE EC ;2U
Adder
5.542
274753CRETE EC ;3U
Adder
5.542
274724RIVER EC ;11
Adder
19.952
964401AG1-302 GEN
Solar/Wind Harmer
10.173
274814UNIV PK N;0U
Adder
5.643
274807UNIV PK N;3U
Adder
5.631
274811UNIV PK N;7U
Adder
5.594
276164X3-005 C
Solar/Wind Harmer
0.783
274803UNIV PARK;6U
Adder
6.428
274826FISK ;BP
Adder
12.049
972038AH1-567 GEN2
Adder
0.401
274887GEN-1.85
Solar/Wind Harmer
5.84
276772AC2-154 GEN
Solar/Wind Harmer
3.059
276843GEN-1.7
Solar/Wind Harmer
0.628
276806AD2-047 C O1
Solar/Wind Harmer
11.726
274772LINCOLN ;3U
Adder
6.795
972259AH1-714 GEN
Adder
20.698
274676JOLIET 29;8U
Adder
32.058
939351AE1-166 GEN
Solar/Wind Harmer
6.421
970707AG2-453 GEN
Solar/Wind Harmer
30.273
274730ELWOOD EC;6P
Adder
17.772
274734ELWOOD EC;8P
Adder
17.772
274736ELWOOD EC;9P
Adder
17.772
274729ELWOOD EC;1P
Adder
17.771
943121AE2-341 GEN
Solar/Wind Harmer
15.967
943591AF1-030 GEN
Solar/Wind Harmer
10.645
274862TOP CROP ;2U
Solar/Wind Harmer
5.381
274682WAUKEGAN ;7U
Adder
18.961
24690905MDL-1G C
Solar/Wind Harmer
8.44
24729505KEY G4
50/50
13.466
24727205RPMNG3
50/50
1.305
24653605MOTTVILLE
50/50
0.005
24641605TWIN BRNCH
50/50
0.023
270144AC1-141 ST1_
50/50
2.751
270071AF1-092 GEN
Solar/Wind Harmer
28.619
959331AF2-224 GEN
Solar/Wind Harmer
18.309
958711AF2-162 GEN
Solar/Wind Harmer
1.815
970031AG2-029 GEN
Solar/Wind Harmer
41.465
945581AF1-223 GEN
Solar/Wind Harmer
7.435
963791AG1-232 GEN
Solar/Wind Harmer
21.949
965041AG1-368 GEN
Solar/Wind Harmer
15.752
247521TR3_G114
Solar/Wind Harmer
4.899
270191TR4_S_V150
Solar/Wind Harmer
4.371
965051AG1-369 GEN
Solar/Wind Harmer
7.278
961761AG1-017 GEN
Solar/Wind Harmer
0.57
964611AG1-324 GEN
Solar/Wind Harmer
5.194
971771AH1-392 GEN
Solar/Wind Harmer
11.707
970289AG2-191 GEN
Solar/Wind Harmer
2.411
944161AF1-084 GEN
Solar/Wind Harmer
2.803
270526AF1-158 GEN
Solar/Wind Harmer
5.698
270404AC1-167 GEN
Solar/Wind Harmer
1.328
247536S-71 GEN
Solar/Wind Harmer
4.953
960681AF2-359 GEN
Solar/Wind Harmer
4.577
971549AH1-272 GEN
Solar/Wind Harmer
22.073
957201AF2-014 GEN
Solar/Wind Harmer
5.406
270435AC2-044 GEN
Solar/Wind Harmer
2.384
270007AE1-245 C
Solar/Wind Harmer
6.344
270543AE2-219 C
Solar/Wind Harmer
11.402
958391AF2-133 GEN
Solar/Wind Harmer
10.08
959141AF2-205 GEN
Solar/Wind Harmer
6.674
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.539
274800UNIV PARK;3U
Adder
6.404
274801UNIV PARK;4U
Adder
6.404
960591AF2-350 GEN
Solar/Wind Harmer
10.961
274775LINCOLN ;6U
Adder
6.795
274776LINCOLN ;7U
Adder
6.795
274777LINCOLN ;8U
Adder
6.795
972228AH1-698 GEN2
Adder
4.043
972227AH1-698 GEN1
Adder
2.846
274687WILL CNTY;4U
Adder
30.363
274687WILL CNTY;4U
Adder
30.363
274675JOLIET 29;7U
Adder
33.246
274675JOLIET 29;7U
Adder
32.058
276893AG1-478 C
Solar/Wind Harmer
0.595
274728ELWOOD EC;5P
Adder
17.772
274731ELWOOD EC;2P
Adder
17.771
274733ELWOOD EC;3P
Adder
17.771
274735ELWOOD EC;4P
Adder
17.771
970833AG2-524 GEN
Solar/Wind Harmer
9.378
970833AG2-524 GEN
Solar/Wind Harmer
4.362
274744AC1-111 GEN8
Adder
5.954
274746AC1-111 G10
Adder
5.954
970073AG2-061 GEN
Solar/Wind Harmer
2.445
946581AF1-322 GEN
Solar/Wind Harmer
10.756
24691005MDL-2G C
Solar/Wind Harmer
3.887
274823ROCKFORD ;21
Adder
19.955
270594AE1-207 GEN
Solar/Wind Harmer
17.423
270032AE2-172
Solar/Wind Harmer
5.967
270449AD2-020 GEN
Solar/Wind Harmer
3.59
943021AE2-325 GEN
Solar/Wind Harmer
4.666
942081AE2-220 GEN
Solar/Wind Harmer
8.026
270209AC1-174_GEN
Solar/Wind Harmer
5.107
270437AC2-090 C
Solar/Wind Harmer
7.004
270239V3-007_GEN1
Solar/Wind Harmer
2.159
965421AG1-410 GEN
Solar/Wind Harmer
37.596
24441205WTRV SLR C
Solar/Wind Harmer
0.167
276903AD2-071 C
Solar/Wind Harmer
12.228
270258AD1-119 GEN
Solar/Wind Harmer
2.457
246936BC-WTG1
Solar/Wind Harmer
4.662
270489AE1-102 GEN1
Solar/Wind Harmer
1.55
970373AG2-245 GEN
Solar/Wind Harmer
24.361
270055AF2-134 C O1
Solar/Wind Harmer
3.45
274751CRETE EC ;1U
Adder
5.542
274754CRETE EC ;4U
Adder
5.542
274723RIVER EC ;12
Adder
20.195
958381AF2-132 GEN
Solar/Wind Harmer
10.173
964861AG1-349 GEN
Solar/Wind Harmer
8.8
971917AH1-482 GEN
Solar/Wind Harmer
10.153
274812UNIV PK N;8U
Adder
5.594
274802UNIV PARK;5U
Adder
6.428
972207SS24-0001
Solar/Wind Harmer
24.158
274773LINCOLN ;4U
Adder
6.795
274774LINCOLN ;5U
Adder
6.795
940581AE2-045 GEN
Solar/Wind Harmer
11.159
971605AH1-302 GEN
Solar/Wind Harmer
9.542
274676JOLIET 29;8U
Adder
33.245
941551AE2-152 GEN
Solar/Wind Harmer
4.91
274674JOLIET 9 ;6U
Adder
16.648
274732ELWOOD EC;7P
Adder
17.772
274871GR RIDGE ;2U
Solar/Wind Harmer
8.252
274847GR RIDGE ;BU
Solar/Wind Harmer
5.426
274745AC1-111 GEN9
Adder
5.954
276694AA1-018 GEN2
Solar/Wind Harmer
6.714
276691AA1-018 GEN1
Solar/Wind Harmer
0.803
274861TOP CROP ;1U
Solar/Wind Harmer
6.444
274682WAUKEGAN ;7U
Adder
18.961
274828WAUKEGAN ;BP
Adder
11.639
276805AD2-038 GEN
Solar/Wind Harmer
5.392
24791305MDL-5G
Solar/Wind Harmer
2.534
274822ROCKFORD ;11
Adder
20.1
972267AH1-718 GEN
Adder
4.158
24729405KEY G3
50/50
0.735
24729305KEY G2
50/50
0.723
24729205KEY G1
50/50
0.719
247620Y3-023
50/50
0.695
960851AF2-376 GEN
50/50
3.286
24643105BUCHANAN
50/50
0.016
247621Y3-024
50/50
0.325
944541AF1-119 GEN
Solar/Wind Harmer
7.511
960971AF2-388 GEN
Solar/Wind Harmer
19.608
942221AE2-234 GEN
Solar/Wind Harmer
5.657
944231AF1-091 GEN
Solar/Wind Harmer
27.808
270031AE2-169
Solar/Wind Harmer
11.933
270599AE1-208 GEN
Solar/Wind Harmer
11.933
270246TR4_N_V150
Solar/Wind Harmer
1.239
270247TR4_N_V136
Solar/Wind Harmer
1.239
270201AC2-176 GEN
Solar/Wind Harmer
6.846
964611AG1-324 GEN
Solar/Wind Harmer
0.697
961051AF2-396 GEN
Solar/Wind Harmer
20.542
961051AF2-396 GEN
Solar/Wind Harmer
9.554
970349AG2-230 GEN
Solar/Wind Harmer
19.294
970291AG2-192 GEN
Solar/Wind Harmer
1.649
970291AG2-192 GEN
Solar/Wind Harmer
0.531
926881AC1-175 GEN
Solar/Wind Harmer
7.004
24725505WLD G2 C
Solar/Wind Harmer
4.825
24699105WLD G1 C
Solar/Wind Harmer
4.769
965681AG1-436 GEN
Solar/Wind Harmer
15.141
965791AG1-447 GEN
Solar/Wind Harmer
7.747
246937BC-WTG2
Solar/Wind Harmer
4.662
247607V1-011 GEN
Solar/Wind Harmer
4.647
270383AD1-128 GEN
Solar/Wind Harmer
7.136
270535AF1-215 GEN1
Solar/Wind Harmer
5.176
270536AF1-215 GEN2
Solar/Wind Harmer
5.176
970883AG2-550 GEN
Solar/Wind Harmer
11.402
970885AG2-551 GEN
Solar/Wind Harmer
2.652
274805UNIV PK N;1U
Adder
5.606
274808UNIV PK N;4U
Adder
5.57
274888KELLY CRK;1U
Solar/Wind Harmer
6.468
276776AD2-060 GEN
Solar/Wind Harmer
0.459
958011AF2-095 GEN
Solar/Wind Harmer
15.784
274770LINCOLN ;1U
Adder
6.795
274771LINCOLN ;2U
Adder
6.795
970941AG2-585 GEN
Solar/Wind Harmer
6.029
276897AD1-100 C
Solar/Wind Harmer
50.292
276893AG1-478 C
Solar/Wind Harmer
0.474
274674JOLIET 9 ;6U
Adder
16.648
945421AF1-207 GEN
Solar/Wind Harmer
14.999
957841AF2-078 GEN
Solar/Wind Harmer
6.457
958481AF2-142 GEN
Solar/Wind Harmer
15.961
942801AE2-298 GEN
Solar/Wind Harmer
1.597
274695ROCKY RD ;2P
Adder
11.743
274693ROCKY RD ;1P
Adder
11.627
274697ROCKY RD ;3P
Adder
3.19
274696ROCKY RD ;4P
Adder
12.02
274683WAUKEGAN ;8U
Adder
22.204
274683WAUKEGAN ;8U
Adder
18.717
958491AF2-143 GEN
Solar/Wind Harmer
15.773
24697605MDL-3G C
Solar/Wind Harmer
3.875
24755605MDL-5G
Solar/Wind Harmer
2.534
24697905MDL-4G C
Solar/Wind Harmer
2.412
972235AH1-702 GEN1
Adder
2.576
972236AH1-702 GEN2
Adder
2.24
274764LEE CO EC;5U
Adder
9.398
274765LEE CO EC;6U
Adder
9.398
274762LEE CO EC;3U
Adder
9.376
274763LEE CO EC;4U
Adder
9.287
24728805RICHG1
Adder
3.1
24728905RICHG2
Adder
3.1
270349AD2-093_GEN
Solar/Wind Helper
1.079
270471AD2-092_GEN
Solar/Wind Helper
1.079
270054AF2-122 C O1
Solar/Wind Helper
0.779
946101AF1-275 GEN
Solar/Wind Helper
0.3
270180AB1-006 GEN1
Solar/Wind Harmer
6.97
270181AB1-006 GEN2
Solar/Wind Harmer
0.693
274760LEE CO EC;1U
Adder
9.376
274767LEE CO EC;8U
Adder
9.265
24728705AND G3
Adder
7.828
24728505AND G1
Adder
3.743
23906402RICHG1
Adder
0.88
23906502RICHG2&3
Adder
0.873
270284AF1-227 GEN1
Solar/Wind Helper
1.171
270287AF1-227 GEN3
Solar/Wind Helper
0.429
274761LEE CO EC;2U
Adder
9.376
274766LEE CO EC;7U
Adder
9.265
24728605AND G2
Adder
3.743
23906502RICHG2&3
Adder
0.873
970091AG2-072 GEN
Adder
47.024
23920202STRYCT
Adder
0.786
270286AF1-227 GEN2
Solar/Wind Helper
0.429
270520AE2-214 GEN
Solar/Wind Helper
1.2
990497J1323
External Queue
1.920957326889038
LAGNLTFEXP_LAGN->PJM
CLTF
8.372
TVALTFEXP_TVA->PJM
CLTF
3.318
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
3.252
WECLTFEXP_WEC->PJM
CLTF
3.899
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.509
AG2-052LTFEXP_AG2-052->PJM
LTF
0.26
AH1-155LTFEXP_AH1-155->PJM
LTF
0.39
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.42
MECLTFEXP_MEC->PJM
CLTF
14.477
SIGELTFEXP_SIGE->PJM
CLTF
0.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.462

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.01 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3190.2
MW Contribution:
17.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.734
24729305KEY G2
50/50
0.721
24729205KEY G1
50/50
0.718
247620Y3-023
50/50
0.69
960851AF2-376 GEN
50/50
3.277
24643105BUCHANAN
50/50
0.016
247621Y3-024
50/50
0.324
944541AF1-119 GEN
Solar/Wind Harmer
0.834
960971AF2-388 GEN
Solar/Wind Harmer
7.331
942221AE2-234 GEN
Solar/Wind Harmer
4.522
944231AF1-091 GEN
Solar/Wind Harmer
24.786
270031AE2-169
Solar/Wind Harmer
5.613
270599AE1-208 GEN
Solar/Wind Harmer
9.355
270246TR4_N_V150
Solar/Wind Harmer
0.065
270247TR4_N_V136
Solar/Wind Harmer
0.065
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.696
961051AF2-396 GEN
Solar/Wind Harmer
17.945
961051AF2-396 GEN
Solar/Wind Harmer
11.963
971613AH1-306 GEN
Solar/Wind Harmer
4.3
970291AG2-192 GEN
Solar/Wind Harmer
1.152
970291AG2-192 GEN
Solar/Wind Harmer
0.532
970349AG2-230 GEN
Solar/Wind Harmer
13.187
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.54
965681AG1-436 GEN
Solar/Wind Harmer
10.47
965791AG1-447 GEN
Solar/Wind Harmer
7.678
246937BC-WTG2
Solar/Wind Harmer
0.334
247607V1-011 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.947
970885AG2-551 GEN
Solar/Wind Harmer
2.649
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.605
274808UNIV PK N;4U
Adder
5.568
274770LINCOLN ;1U
Adder
9.292
274771LINCOLN ;2U
Adder
9.292
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
276776AD2-060 GEN
Solar/Wind Harmer
0.817
958011AF2-095 GEN
Solar/Wind Harmer
11.028
970941AG2-585 GEN
Solar/Wind Harmer
4.212
276897AD1-100 C
Solar/Wind Harmer
18.934
276893AG1-478 C
Solar/Wind Harmer
0.504
274674JOLIET 9 ;6U
Adder
16.683
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
11.155
274696ROCKY RD ;4P
Adder
12.055
274695ROCKY RD ;2P
Adder
11.777
274693ROCKY RD ;1P
Adder
11.662
274697ROCKY RD ;3P
Adder
3.199
274683WAUKEGAN ;8U
Adder
22.263
274683WAUKEGAN ;8U
Adder
18.767
958491AF2-143 GEN
Solar/Wind Harmer
11.026
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
21.97
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.375
971343AH1-151 GEN
Solar/Wind Harmer
14.375
972235AH1-702 GEN1
Adder
2.583
972236AH1-702 GEN2
Adder
2.246
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.805
938861AE1-114 GEN
Solar/Wind Harmer
4.01
274764LEE CO EC;5U
Adder
9.425
274765LEE CO EC;6U
Adder
9.425
274762LEE CO EC;3U
Adder
9.403
274763LEE CO EC;4U
Adder
9.314
276645AC1-214 GEN1
Solar/Wind Harmer
0.274
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.126
942111AE2-223 GEN
Solar/Wind Harmer
2.254
960611AF2-352 GEN
Solar/Wind Harmer
2.276
970241AG2-163 GEN
Solar/Wind Harmer
3.954
276615X2-022 GEN
Solar/Wind Harmer
0.066
276838X2-022 GEN2
Solar/Wind Harmer
0.361
945391AF1-204 GEN
Solar/Wind Harmer
6.631
276916AD2-100_GEN
Solar/Wind Harmer
12.922
276911AD2-131_GEN
Solar/Wind Harmer
0.851
24728805RICHG1
Adder
3.1
24728905RICHG2
Adder
3.1
970621AG2-405 GEN
Solar/Wind Harmer
1.034
970583AG2-370 GEN
50/50
3.653
24727105RPMNG2
50/50
1.309
270142AC1-141 CT1_
50/50
3.096
24642205MAYFLWER
50/50
0.047
944961AF1-161 GEN
50/50
3.701
962601AG1-109 GEN
50/50
3.701
944531AF1-118 GEN
Solar/Wind Harmer
62.885
270043AE2-236 GEN
Solar/Wind Harmer
8.814
965021AG1-366 GEN
Solar/Wind Harmer
4.247
270063AE2-323 C
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.832
270004AE1-209 GEN
Solar/Wind Harmer
2.117
970825AG2-519 GEN
Solar/Wind Harmer
7.011
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.926
946031AF1-268 GEN
Solar/Wind Harmer
8.826
945111AF1-176 GEN
Solar/Wind Harmer
7.395
270505AE1-170 C O1
Solar/Wind Harmer
9.418
970289AG2-191 GEN
Solar/Wind Harmer
0.975
971347AH1-153 GEN
Solar/Wind Harmer
4.396
247642Z2-115 C
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.299
270491AE1-102 GEN2
Solar/Wind Harmer
1.078
274752CRETE EC ;2U
Adder
9.326
274753CRETE EC ;3U
Adder
9.326
274724RIVER EC ;11
Adder
19.931
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.641
274807UNIV PK N;3U
Adder
5.629
274811UNIV PK N;7U
Adder
5.593
274803UNIV PARK;6U
Adder
6.433
274826FISK ;BP
Adder
12.06
274772LINCOLN ;3U
Adder
9.292
972038AH1-567 GEN2
Adder
0.401
274887GEN-1.85
Solar/Wind Harmer
0.199
276843GEN-1.7
Solar/Wind Harmer
0.248
276806AD2-047 C O1
Solar/Wind Harmer
4.34
972259AH1-714 GEN
Adder
20.761
274676JOLIET 29;8U
Adder
32.122
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
24.739
274730ELWOOD EC;6P
Adder
17.809
274734ELWOOD EC;8P
Adder
17.809
274736ELWOOD EC;9P
Adder
17.809
274729ELWOOD EC;1P
Adder
17.808
943121AE2-341 GEN
Solar/Wind Harmer
12.495
943591AF1-030 GEN
Solar/Wind Harmer
8.309
274862TOP CROP ;2U
Solar/Wind Harmer
1.004
274682WAUKEGAN ;7U
Adder
19.011
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.342
276868AE1-113 GEN
Solar/Wind Harmer
1.461
274879MINONK ;1U
Solar/Wind Harmer
0.305
946671AF1-331 GEN
Solar/Wind Harmer
0.771
274855GSG-6 ;RU
Solar/Wind Harmer
0.264
274850MENDOTA H;RU
Solar/Wind Harmer
0.084
959091AF2-200 GEN
Solar/Wind Harmer
14.375
970571AG2-364 GEN
Solar/Wind Harmer
14.297
24386205FR-12G C
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.403
274767LEE CO EC;8U
Adder
9.292
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
965091AG1-374 GEN
Solar/Wind Harmer
20.486
959611AF2-252 GEN
Solar/Wind Harmer
2.276
24728705AND G3
Adder
7.836
24728505AND G1
Adder
3.747
965931AG1-462 GEN
Solar/Wind Harmer
17.242
971087AG2-675 GEN
Solar/Wind Harmer
3.606
971993AH1-541 GEN
Solar/Wind Harmer
3.006
970193AG2-126 GEN
Solar/Wind Harmer
9.362
957381AF2-032 GEN
Solar/Wind Harmer
1.409
942481AE2-261 GEN
Solar/Wind Harmer
18.539
23906402RICHG1
Adder
0.876
23906502RICHG2&3
Adder
0.869
270541AE2-072 C
Solar/Wind Harmer
0
958321AF2-126 GEN
Solar/Wind Harmer
0.443
270284AF1-227 GEN1
Solar/Wind Helper
1.175
270287AF1-227 GEN3
Solar/Wind Helper
0.431
960861AF2-377 GEN
50/50
3.382
970521AG2-332 GEN
50/50
16.165
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.308
270143AC1-141 CT2_
50/50
3.096
965011AG1-365 GEN
Solar/Wind Harmer
12.741
965651AG1-433 GEN
Solar/Wind Harmer
3.666
958861AF2-177 GEN
Solar/Wind Harmer
5.255
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.002
270005AE1-210 C O1
Solar/Wind Harmer
2.117
970825AG2-519 GEN
Solar/Wind Harmer
3.304
945111AF1-176 GEN
Solar/Wind Harmer
16.279
957891AF2-083 GEN
Solar/Wind Harmer
15.012
270594AE1-207 GEN
Solar/Wind Harmer
10.034
270032AE2-172
Solar/Wind Harmer
5.973
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.637
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.415
965421AG1-410 GEN
Solar/Wind Harmer
26.149
276903AD2-071 C
Solar/Wind Harmer
9.536
246936BC-WTG1
Solar/Wind Harmer
0.334
270489AE1-102 GEN1
Solar/Wind Harmer
1.078
970373AG2-245 GEN
Solar/Wind Harmer
16.897
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
9.326
274754CRETE EC ;4U
Adder
9.326
274723RIVER EC ;12
Adder
20.174
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
5.593
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
10.122
274802UNIV PARK;5U
Adder
6.433
274773LINCOLN ;4U
Adder
9.292
274774LINCOLN ;5U
Adder
9.292
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.53
274676JOLIET 29;8U
Adder
33.312
941551AE2-152 GEN
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
16.683
274732ELWOOD EC;7P
Adder
17.809
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.972
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.208
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
19.011
274828WAUKEGAN ;BP
Adder
11.67
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.485
962781AG1-127 GEN
Solar/Wind Harmer
6.953
276882AE2-255 GEN
Solar/Wind Harmer
0.852
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.817
957471AF2-041 GEN
Solar/Wind Harmer
21.562
959081AF2-199 GEN
Solar/Wind Harmer
7.187
971067AG2-660 GEN
Solar/Wind Harmer
2.396
274822ROCKFORD ;11
Adder
20.159
970569AG2-363 GEN
Solar/Wind Harmer
21.445
970819AG2-516 GEN
Solar/Wind Harmer
8.554
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.403
274766LEE CO EC;7U
Adder
9.292
276646AC1-214 GEN2
Solar/Wind Harmer
0.274
276708O09 GEN2
Solar/Wind Harmer
0.247
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.71
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
3.747
970773AG2-487 GEN
Solar/Wind Harmer
1.202
963741AG1-226 GEN
Solar/Wind Harmer
16.041
276621W2-048 GEN
Solar/Wind Harmer
0.32
965911AG1-460 GEN
Solar/Wind Harmer
1.24
23906502RICHG2&3
Adder
0.869
970091AG2-072 GEN
Adder
47.294
23920202STRYCT
Adder
0.781
241858AF1-205_GEN
Solar/Wind Harmer
1.344
270286AF1-227 GEN2
Solar/Wind Helper
0.431
270520AE2-214 GEN
Solar/Wind Helper
1.202
24729505KEY G4
50/50
13.443
24727205RPMNG3
50/50
1.301
24653605MOTTVILLE
50/50
0.005
24641605TWIN BRNCH
50/50
0.023
270144AC1-141 ST1_
50/50
2.734
270071AF1-092 GEN
Solar/Wind Harmer
25.488
959331AF2-224 GEN
Solar/Wind Harmer
8.919
970031AG2-029 GEN
Solar/Wind Harmer
6.248
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
15.281
965041AG1-368 GEN
Solar/Wind Harmer
10.96
971609AH1-304 GEN
Solar/Wind Harmer
1.667
247521TR3_G114
Solar/Wind Harmer
0.367
965051AG1-369 GEN
Solar/Wind Harmer
5.063
964611AG1-324 GEN
Solar/Wind Harmer
3.62
971771AH1-392 GEN
Solar/Wind Harmer
8.998
970289AG2-191 GEN
Solar/Wind Harmer
1.684
270526AF1-158 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.341
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.05
971549AH1-272 GEN
Solar/Wind Harmer
17.043
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.563
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.547
959141AF2-205 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
9.292
274776LINCOLN ;7U
Adder
9.292
274777LINCOLN ;8U
Adder
9.292
274800UNIV PARK;3U
Adder
6.411
274801UNIV PARK;4U
Adder
6.411
960591AF2-350 GEN
Solar/Wind Harmer
7.658
972228AH1-698 GEN2
Adder
4.051
972227AH1-698 GEN1
Adder
2.852
971611AH1-305 GEN
Solar/Wind Harmer
4.539
274687WILL CNTY;4U
Adder
30.416
274687WILL CNTY;4U
Adder
30.416
274675JOLIET 29;7U
Adder
33.312
274675JOLIET 29;7U
Adder
32.122
274728ELWOOD EC;5P
Adder
17.809
274731ELWOOD EC;2P
Adder
17.808
274733ELWOOD EC;3P
Adder
17.808
274735ELWOOD EC;4P
Adder
17.808
970833AG2-524 GEN
Solar/Wind Harmer
8.267
970833AG2-524 GEN
Solar/Wind Harmer
5.511
274744AC1-111 GEN8
Adder
5.972
274746AC1-111 G10
Adder
5.972
970073AG2-061 GEN
Solar/Wind Harmer
2.45
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.958
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
10.852
971675AH1-338 GEN
Solar/Wind Harmer
2.819
276861AD2-134 GEN
Solar/Wind Harmer
0.129
276863AD2-134 GEN
Solar/Wind Harmer
0.129
971171AH1-044 GEN
Solar/Wind Harmer
14.375
274823ROCKFORD ;21
Adder
20.012
970169AG2-114 GEN
Solar/Wind Harmer
7.144
926823AC1-168 GEN
Solar/Wind Harmer
1.213
274856ECOGROVE ;U1
Solar/Wind Harmer
0.166
24386405FR-21G C
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
11.398
972267AH1-718 GEN
Adder
4.17
276741O09 GEN1
Solar/Wind Harmer
0.247
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.282
963841AG1-237 GEN
Solar/Wind Harmer
3.005
274854TWINGROVE;U2
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
3.807
276668AB2-070 GEN1
Solar/Wind Harmer
0.256
276848AB2-070 GEN3
Solar/Wind Harmer
0.255
276849AB2-070 GEN2
Solar/Wind Harmer
0.256
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.516
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
971587AH1-292 GEN
Solar/Wind Harmer
3.867
964571AG1-320 GEN
Solar/Wind Harmer
2.864
270349AD2-093_GEN
Solar/Wind Helper
1.081
270471AD2-092_GEN
Solar/Wind Helper
1.081
270054AF2-122 C O1
Solar/Wind Helper
0.78
946101AF1-275 GEN
Solar/Wind Helper
0.301
990497J1323
External Queue
1.9028279781341553
991297J1743
External Queue
13.235071182250977
990792J1392
External Queue
6.545727729797363
LAGNLTFEXP_LAGN->PJM
CLTF
8.402
TVALTFEXP_TVA->PJM
CLTF
3.331
NYPJM->LTFIMP_NY
CLTF
1.989
LGEELTFEXP_LGEE->PJM
CLTF
3.263
WECLTFEXP_WEC->PJM
CLTF
3.91
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.333
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.471
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.688

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.78 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6118.43
MW Contribution:
34.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
13.488
270144AC1-141 ST1_
50/50
4.417
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
13.44
274776LINCOLN ;7U
50/50
13.44
274777LINCOLN ;8U
50/50
13.44
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
7.886
971771AH1-392 GEN
Solar/Wind Harmer
18.775
270526AF1-158 GEN
Solar/Wind Harmer
9.429
270071AF1-092 GEN
Solar/Wind Harmer
30.976
944161AF1-084 GEN
Solar/Wind Harmer
4.48
972037AH1-567 GEN1
Adder
0.365
274827FISK ;RP
Adder
15.465
960591AF2-350 GEN
Solar/Wind Harmer
19.923
972228AH1-698 GEN2
Adder
7.377
972227AH1-698 GEN1
Adder
5.194
274800UNIV PARK;3U
Adder
11.611
274801UNIV PARK;4U
Adder
11.611
274687WILL CNTY;4U
Adder
55.279
274687WILL CNTY;4U
Adder
55.279
274675JOLIET 29;7U
Adder
60.629
274675JOLIET 29;7U
Adder
58.463
970031AG2-029 GEN
Solar/Wind Harmer
49.365
274728ELWOOD EC;5P
Adder
32.411
274731ELWOOD EC;2P
Adder
32.41
274733ELWOOD EC;3P
Adder
32.41
274735ELWOOD EC;4P
Adder
32.41
276893AG1-478 C
Solar/Wind Harmer
1.084
970833AG2-524 GEN
Solar/Wind Harmer
17.199
970833AG2-524 GEN
Solar/Wind Harmer
7.999
274744AC1-111 GEN8
Adder
10.938
274746AC1-111 G10
Adder
10.938
270102X2-052 ST
50/50
3.355
270100X2-052 CT1
50/50
3.1
270101X2-052 CT2
50/50
3.1
24643105BUCHANAN
50/50
0.026
274770LINCOLN ;1U
50/50
13.44
274771LINCOLN ;2U
50/50
13.44
247620Y3-023
50/50
0.991
970349AG2-230 GEN
Solar/Wind Harmer
33.323
965681AG1-436 GEN
Solar/Wind Harmer
26.089
965791AG1-447 GEN
Solar/Wind Harmer
13.348
961051AF2-396 GEN
Solar/Wind Harmer
32.427
961051AF2-396 GEN
Solar/Wind Harmer
15.082
274805UNIV PK N;1U
Adder
10.052
274808UNIV PK N;4U
Adder
9.986
274888KELLY CRK;1U
Solar/Wind Harmer
11.757
276776AD2-060 GEN
Solar/Wind Harmer
0.834
958011AF2-095 GEN
Solar/Wind Harmer
28.69
970941AG2-585 GEN
Solar/Wind Harmer
10.958
276897AD1-100 C
Solar/Wind Harmer
92.171
270535AF1-215 GEN1
Solar/Wind Harmer
8.976
270536AF1-215 GEN2
Solar/Wind Harmer
8.976
274674JOLIET 9 ;6U
Adder
30.381
276893AG1-478 C
Solar/Wind Harmer
0.864
274695ROCKY RD ;2P
Adder
21.528
274693ROCKY RD ;1P
Adder
21.316
274697ROCKY RD ;3P
Adder
5.848
274696ROCKY RD ;4P
Adder
22.036
958481AF2-142 GEN
Solar/Wind Harmer
28.999
274683WAUKEGAN ;8U
Adder
40.618
274683WAUKEGAN ;8U
Adder
34.239
270142AC1-141 CT1_
50/50
5.002
24642205MAYFLWER
50/50
0.076
274772LINCOLN ;3U
50/50
13.44
944961AF1-161 GEN
50/50
5.928
962601AG1-109 GEN
50/50
5.928
971347AH1-153 GEN
Solar/Wind Harmer
11.108
270043AE2-236 GEN
Solar/Wind Harmer
11.544
247643Z2-116 C
Solar/Wind Harmer
0.145
24441505OLIV SLR
Solar/Wind Harmer
0.278
270505AE1-170 C O1
Solar/Wind Harmer
30.925
945111AF1-176 GEN
Solar/Wind Harmer
11.586
274724RIVER EC ;11
Adder
35.711
972231SS25-0005
Solar/Wind Harmer
19.1
972181SS23-001
Solar/Wind Harmer
11.937
274752CRETE EC ;2U
Adder
9.837
274753CRETE EC ;3U
Adder
9.837
276164X3-005 C
Solar/Wind Harmer
1.411
270063AE2-323 C
Solar/Wind Harmer
4.403
274814UNIV PK N;0U
Adder
10.117
274807UNIV PK N;3U
Adder
10.095
274811UNIV PK N;7U
Adder
10.03
970707AG2-453 GEN
Solar/Wind Harmer
56.064
972259AH1-714 GEN
Adder
38.042
274803UNIV PARK;6U
Adder
11.623
274826FISK ;BP
Adder
21.822
274887GEN-1.85
Solar/Wind Harmer
10.615
276772AC2-154 GEN
Solar/Wind Harmer
5.56
276843GEN-1.7
Solar/Wind Harmer
1.142
276806AD2-047 C O1
Solar/Wind Harmer
21.313
972038AH1-567 GEN2
Adder
0.727
939351AE1-166 GEN
Solar/Wind Harmer
11.767
944531AF1-118 GEN
Solar/Wind Harmer
69.202
274676JOLIET 29;8U
Adder
58.463
274729ELWOOD EC;1P
Adder
32.41
274730ELWOOD EC;6P
Adder
32.411
274734ELWOOD EC;8P
Adder
32.411
274736ELWOOD EC;9P
Adder
32.411
943121AE2-341 GEN
Solar/Wind Harmer
29.406
943591AF1-030 GEN
Solar/Wind Harmer
19.604
964401AG1-302 GEN
Solar/Wind Harmer
17.685
274862TOP CROP ;2U
Solar/Wind Harmer
9.773
274682WAUKEGAN ;7U
Adder
34.688
276868AE1-113 GEN
Solar/Wind Harmer
19.24
274879MINONK ;1U
Solar/Wind Harmer
12.827
276799AD1-013 GEN
Solar/Wind Harmer
4.182
946671AF1-331 GEN
Solar/Wind Harmer
0.792
274855GSG-6 ;RU
Solar/Wind Harmer
6.983
274850MENDOTA H;RU
Solar/Wind Harmer
4.855
276602WESTBROOK C
Solar/Wind Harmer
4.02
959091AF2-200 GEN
Solar/Wind Harmer
37.588
970571AG2-364 GEN
Solar/Wind Harmer
37.151
274857EASY ROAD;U1
Solar/Wind Harmer
8.815
274760LEE CO EC;1U
Adder
17.118
274767LEE CO EC;8U
Adder
16.916
24728705AND G3
Adder
10.665
24728505AND G1
Adder
5.1
24690905MDL-1G C
Solar/Wind Harmer
9.079
24344105CKG2
50/50
17.244
270143AC1-141 CT2_
50/50
5.002
24639705ELKHART HY
50/50
0.334
274773LINCOLN ;4U
50/50
13.44
274774LINCOLN ;5U
50/50
13.44
970521AG2-332 GEN
50/50
23.718
24307105BERRINSP G
50/50
0.044
270216AD2-079_GEN
Solar/Wind Harmer
1.255
957891AF2-083 GEN
Solar/Wind Harmer
30.868
945111AF1-176 GEN
Solar/Wind Harmer
36.559
972207SS24-0001
Solar/Wind Harmer
45.031
270449AD2-020 GEN
Solar/Wind Harmer
5.715
943021AE2-325 GEN
Solar/Wind Harmer
7.427
274723RIVER EC ;12
Adder
36.127
274751CRETE EC ;1U
Adder
9.837
274754CRETE EC ;4U
Adder
9.837
970373AG2-245 GEN
Solar/Wind Harmer
42.152
274812UNIV PK N;8U
Adder
10.03
24441205WTRV SLR C
Solar/Wind Harmer
0.27
274802UNIV PARK;5U
Adder
11.623
941551AE2-152 GEN
Solar/Wind Harmer
8.999
270055AF2-134 C O1
Solar/Wind Harmer
5.984
274676JOLIET 29;8U
Adder
60.628
274674JOLIET 9 ;6U
Adder
30.381
274732ELWOOD EC;7P
Adder
32.411
274871GR RIDGE ;2U
Solar/Wind Harmer
15.14
274847GR RIDGE ;BU
Solar/Wind Harmer
9.956
274745AC1-111 GEN9
Adder
10.938
958381AF2-132 GEN
Solar/Wind Harmer
17.685
964861AG1-349 GEN
Solar/Wind Harmer
15.303
971917AH1-482 GEN
Solar/Wind Harmer
17.655
276694AA1-018 GEN2
Solar/Wind Harmer
12.198
276691AA1-018 GEN1
Solar/Wind Harmer
1.458
274861TOP CROP ;1U
Solar/Wind Harmer
11.705
274682WAUKEGAN ;7U
Adder
34.688
274828WAUKEGAN ;BP
Adder
21.291
958391AF2-133 GEN
Solar/Wind Harmer
17.547
24729505KEY G4
Adder
12.548
959141AF2-205 GEN
Solar/Wind Harmer
11.629
970073AG2-061 GEN
Solar/Wind Harmer
4.443
971675AH1-338 GEN
Solar/Wind Harmer
34.055
971411AH1-196 GEN
Solar/Wind Harmer
28.375
276861AD2-134 GEN
Solar/Wind Harmer
3.377
276863AD2-134 GEN
Solar/Wind Harmer
3.377
274863CRW1-WTG
Solar/Wind Harmer
10.548
274864CRW2-WTG
Solar/Wind Harmer
10.548
971171AH1-044 GEN
Solar/Wind Harmer
37.588
276889AE2-281 GEN
Solar/Wind Harmer
3.605
274823ROCKFORD ;21
Adder
36.484
970169AG2-114 GEN
Solar/Wind Harmer
18.611
274856ECOGROVE ;U1
Solar/Wind Harmer
6.268
276611AD2-172 GEN
Solar/Wind Harmer
4.755
276612AE2-035 GEN
Solar/Wind Harmer
4.755
926823AC1-168 GEN
Solar/Wind Harmer
7.988
971549AH1-272 GEN
Solar/Wind Harmer
34.293
971681AH1-341 GEN
Solar/Wind Harmer
27.72
972267AH1-718 GEN
Adder
7.584
962691AG1-118 GEN
Solar/Wind Harmer
57.593
960751AF2-366 GEN
Solar/Wind Harmer
5.494
958491AF2-143 GEN
Solar/Wind Harmer
28.659
276901AD2-066 C O1
Solar/Wind Harmer
6.693
971341AH1-150 GEN
Solar/Wind Harmer
37.588
971343AH1-151 GEN
Solar/Wind Harmer
37.588
276872AE1-163_GEN1
Solar/Wind Harmer
12.619
276876AE1-163_GEN2
Solar/Wind Harmer
12.619
945421AF1-207 GEN
Solar/Wind Harmer
26.261
957841AF2-078 GEN
Solar/Wind Harmer
11.305
972235AH1-702 GEN1
Adder
4.708
972236AH1-702 GEN2
Adder
4.094
938861AE1-114 GEN
Solar/Wind Harmer
15.142
274764LEE CO EC;5U
Adder
17.158
274765LEE CO EC;6U
Adder
17.158
274762LEE CO EC;3U
Adder
17.118
274763LEE CO EC;4U
Adder
16.956
247621Y3-024
Adder
0.337
24728805RICHG1
Adder
3.728
24728905RICHG2
Adder
3.728
270349AD2-093_GEN
Solar/Wind Helper
1.56
270471AD2-092_GEN
Solar/Wind Helper
1.56
939401AE1-172 GEN
Solar/Wind Harmer
26.719
962781AG1-127 GEN
Solar/Wind Harmer
18.21
274872LEEDK;1U
Solar/Wind Harmer
15.683
276805AD2-038 GEN
Solar/Wind Harmer
9.797
940581AE2-045 GEN
Solar/Wind Harmer
19.469
971605AH1-302 GEN
Solar/Wind Harmer
16.647
276882AE2-255 GEN
Solar/Wind Harmer
6.414
971997AH1-543 GEN
Solar/Wind Harmer
29.912
957471AF2-041 GEN
Solar/Wind Harmer
56.382
959081AF2-199 GEN
Solar/Wind Harmer
18.794
971067AG2-660 GEN
Solar/Wind Harmer
4.371
274822ROCKFORD ;11
Adder
36.75
970819AG2-516 GEN
Solar/Wind Harmer
22.34
970569AG2-363 GEN
Solar/Wind Harmer
55.727
274858EASY ROAD;U2
Solar/Wind Harmer
8.815
274761LEE CO EC;2U
Adder
17.118
274766LEE CO EC;7U
Adder
16.916
970091AG2-072 GEN
Adder
105.385
24728605AND G2
Adder
5.1
LAGNLTFEXP_LAGN->PJM
CLTF
14.187
TVALTFEXP_TVA->PJM
CLTF
5.423
NYPJM->LTFIMP_NY
CLTF
3.401
LGEELTFEXP_LGEE->PJM
CLTF
5.607
WECLTFEXP_WEC->PJM
CLTF
7.118
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.195
AG2-052LTFEXP_AG2-052->PJM
LTF
0.448
AH1-155LTFEXP_AH1-155->PJM
LTF
0.672
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.218
MECLTFEXP_MEC->PJM
CLTF
26.088
SIGELTFEXP_SIGE->PJM
CLTF
0.553
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.543

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.38 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6096.34
MW Contribution:
36.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.376
24642205MAYFLWER
50/50
0.082
944961AF1-161 GEN
50/50
6.372
962601AG1-109 GEN
50/50
6.372
274772LINCOLN ;3U
50/50
14.328
971347AH1-153 GEN
Solar/Wind Harmer
11.95
24441505OLIV SLR
Solar/Wind Harmer
0.299
247643Z2-116 C
Solar/Wind Harmer
0.155
270043AE2-236 GEN
Solar/Wind Harmer
12.195
270505AE1-170 C O1
Solar/Wind Harmer
33.236
945111AF1-176 GEN
Solar/Wind Harmer
12.446
274724RIVER EC ;11
Adder
38.104
972231SS25-0005
Solar/Wind Harmer
20.399
972181SS23-001
Solar/Wind Harmer
12.75
274752CRETE EC ;2U
Adder
10.506
274753CRETE EC ;3U
Adder
10.506
276164X3-005 C
Solar/Wind Harmer
1.504
270063AE2-323 C
Solar/Wind Harmer
4.695
274814UNIV PK N;0U
Adder
10.79
274807UNIV PK N;3U
Adder
10.767
274811UNIV PK N;7U
Adder
10.696
970707AG2-453 GEN
Solar/Wind Harmer
59.66
964401AG1-302 GEN
Solar/Wind Harmer
19.303
274803UNIV PARK;6U
Adder
12.378
274826FISK ;BP
Adder
23.237
972259AH1-714 GEN
Adder
40.472
274887GEN-1.85
Solar/Wind Harmer
11.297
276772AC2-154 GEN
Solar/Wind Harmer
5.917
24344005CKG1
50/50
14.521
270144AC1-141 ST1_
50/50
4.747
24641605TWIN BRNCH
50/50
0.038
24653605MOTTVILLE
50/50
0.008
274775LINCOLN ;6U
50/50
14.328
274776LINCOLN ;7U
50/50
14.328
274777LINCOLN ;8U
50/50
14.328
960681AF2-359 GEN
Solar/Wind Harmer
8.491
971771AH1-392 GEN
Solar/Wind Harmer
20.176
270526AF1-158 GEN
Solar/Wind Harmer
10.14
270071AF1-092 GEN
Solar/Wind Harmer
33.089
944161AF1-084 GEN
Solar/Wind Harmer
4.817
972037AH1-567 GEN1
Adder
0.389
274827FISK ;RP
Adder
16.469
960591AF2-350 GEN
Solar/Wind Harmer
21.204
274800UNIV PARK;3U
Adder
12.36
274801UNIV PARK;4U
Adder
12.36
972228AH1-698 GEN2
Adder
7.849
972227AH1-698 GEN1
Adder
5.527
958391AF2-133 GEN
Solar/Wind Harmer
19.179
959141AF2-205 GEN
Solar/Wind Harmer
12.724
274687WILL CNTY;4U
Adder
58.796
274687WILL CNTY;4U
Adder
58.796
970031AG2-029 GEN
Solar/Wind Harmer
52.55
274675JOLIET 29;7U
Adder
64.472
274675JOLIET 29;7U
Adder
62.169
274728ELWOOD EC;5P
Adder
34.447
274731ELWOOD EC;2P
Adder
34.446
274733ELWOOD EC;3P
Adder
34.446
274735ELWOOD EC;4P
Adder
34.446
276893AG1-478 C
Solar/Wind Harmer
1.152
970833AG2-524 GEN
Solar/Wind Harmer
18.269
970833AG2-524 GEN
Solar/Wind Harmer
8.497
274744AC1-111 GEN8
Adder
11.614
274746AC1-111 G10
Adder
11.614
970073AG2-061 GEN
Solar/Wind Harmer
4.703
946581AF1-322 GEN
Solar/Wind Harmer
20.573
24691005MDL-2G C
Solar/Wind Harmer
7.435
971411AH1-196 GEN
Solar/Wind Harmer
30.031
971675AH1-338 GEN
Solar/Wind Harmer
36.035
276861AD2-134 GEN
Solar/Wind Harmer
3.573
276843GEN-1.7
Solar/Wind Harmer
1.216
276806AD2-047 C O1
Solar/Wind Harmer
22.684
972038AH1-567 GEN2
Adder
0.774
939351AE1-166 GEN
Solar/Wind Harmer
12.505
274676JOLIET 29;8U
Adder
62.168
274730ELWOOD EC;6P
Adder
34.447
274734ELWOOD EC;8P
Adder
34.447
274736ELWOOD EC;9P
Adder
34.447
274729ELWOOD EC;1P
Adder
34.446
943121AE2-341 GEN
Solar/Wind Harmer
31.23
943591AF1-030 GEN
Solar/Wind Harmer
20.82
274862TOP CROP ;2U
Solar/Wind Harmer
10.361
274682WAUKEGAN ;7U
Adder
36.793
944531AF1-118 GEN
Solar/Wind Harmer
71.497
276868AE1-113 GEN
Solar/Wind Harmer
20.352
274879MINONK ;1U
Solar/Wind Harmer
13.569
24690905MDL-1G C
Solar/Wind Harmer
16.141
970781AG2-491 GEN
Solar/Wind Harmer
20.107
276799AD1-013 GEN
Solar/Wind Harmer
4.425
946671AF1-331 GEN
Solar/Wind Harmer
0.838
274855GSG-6 ;RU
Solar/Wind Harmer
7.389
274850MENDOTA H;RU
Solar/Wind Harmer
5.137
276602WESTBROOK C
Solar/Wind Harmer
4.254
959091AF2-200 GEN
Solar/Wind Harmer
39.747
274760LEE CO EC;1U
Adder
18.06
274767LEE CO EC;8U
Adder
17.848
24728705AND G3
Adder
10.678
24728505AND G1
Adder
5.106
970571AG2-364 GEN
Solar/Wind Harmer
36.857
276863AD2-134 GEN
Solar/Wind Harmer
3.573
24729505KEY G4
Adder
12.942
971549AH1-272 GEN
Solar/Wind Harmer
36.893
274863CRW1-WTG
Solar/Wind Harmer
11.117
274864CRW2-WTG
Solar/Wind Harmer
11.117
971171AH1-044 GEN
Solar/Wind Harmer
39.747
276889AE2-281 GEN
Solar/Wind Harmer
3.808
274823ROCKFORD ;21
Adder
38.572
274856ECOGROVE ;U1
Solar/Wind Harmer
6.621
276611AD2-172 GEN
Solar/Wind Harmer
5.023
276612AE2-035 GEN
Solar/Wind Harmer
5.023
926823AC1-168 GEN
Solar/Wind Harmer
8.419
972267AH1-718 GEN
Adder
7.992
270102X2-052 ST
50/50
3.615
270100X2-052 CT1
50/50
3.34
270101X2-052 CT2
50/50
3.34
24643105BUCHANAN
50/50
0.028
274770LINCOLN ;1U
50/50
14.328
274771LINCOLN ;2U
50/50
14.328
247620Y3-023
50/50
1.061
970349AG2-230 GEN
Solar/Wind Harmer
35.85
965681AG1-436 GEN
Solar/Wind Harmer
28.089
965791AG1-447 GEN
Solar/Wind Harmer
14.371
961051AF2-396 GEN
Solar/Wind Harmer
34.847
961051AF2-396 GEN
Solar/Wind Harmer
16.208
270535AF1-215 GEN1
Solar/Wind Harmer
9.77
270536AF1-215 GEN2
Solar/Wind Harmer
9.77
274805UNIV PK N;1U
Adder
10.72
274808UNIV PK N;4U
Adder
10.65
274888KELLY CRK;1U
Solar/Wind Harmer
12.513
276776AD2-060 GEN
Solar/Wind Harmer
0.888
958011AF2-095 GEN
Solar/Wind Harmer
30.534
970941AG2-585 GEN
Solar/Wind Harmer
11.662
276897AD1-100 C
Solar/Wind Harmer
97.952
274674JOLIET 9 ;6U
Adder
32.294
276893AG1-478 C
Solar/Wind Harmer
0.918
945421AF1-207 GEN
Solar/Wind Harmer
28.884
957841AF2-078 GEN
Solar/Wind Harmer
12.434
274695ROCKY RD ;2P
Adder
22.835
274693ROCKY RD ;1P
Adder
22.61
274697ROCKY RD ;3P
Adder
6.203
274696ROCKY RD ;4P
Adder
23.374
958481AF2-142 GEN
Solar/Wind Harmer
30.747
274683WAUKEGAN ;8U
Adder
43.078
274683WAUKEGAN ;8U
Adder
36.313
962691AG1-118 GEN
Solar/Wind Harmer
61.037
960751AF2-366 GEN
Solar/Wind Harmer
5.821
958491AF2-143 GEN
Solar/Wind Harmer
30.337
276901AD2-066 C O1
Solar/Wind Harmer
7.081
270180AB1-006 GEN1
Solar/Wind Harmer
14.461
24697605MDL-3G C
Solar/Wind Harmer
7.411
24755605MDL-5G
Solar/Wind Harmer
4.847
24697905MDL-4G C
Solar/Wind Harmer
4.614
270181AB1-006 GEN2
Solar/Wind Harmer
1.438
24344105CKG2
50/50
18.6
270143AC1-141 CT2_
50/50
5.376
24639705ELKHART HY
50/50
0.358
970521AG2-332 GEN
50/50
25.433
24307105BERRINSP G
50/50
0.047
274773LINCOLN ;4U
50/50
14.328
274774LINCOLN ;5U
50/50
14.328
971341AH1-150 GEN
Solar/Wind Harmer
39.747
971343AH1-151 GEN
Solar/Wind Harmer
39.747
276872AE1-163_GEN1
Solar/Wind Harmer
13.326
276876AE1-163_GEN2
Solar/Wind Harmer
13.326
972235AH1-702 GEN1
Adder
4.977
972236AH1-702 GEN2
Adder
4.327
274764LEE CO EC;5U
Adder
18.103
274765LEE CO EC;6U
Adder
18.103
274762LEE CO EC;3U
Adder
18.06
274763LEE CO EC;4U
Adder
17.89
247621Y3-024
Adder
0.343
24728805RICHG1
Adder
3.596
24728905RICHG2
Adder
3.596
270349AD2-093_GEN
Solar/Wind Helper
1.535
270471AD2-092_GEN
Solar/Wind Helper
1.535
270216AD2-079_GEN
Solar/Wind Harmer
1.347
957891AF2-083 GEN
Solar/Wind Harmer
33.17
945111AF1-176 GEN
Solar/Wind Harmer
39.271
270449AD2-020 GEN
Solar/Wind Harmer
6.143
943021AE2-325 GEN
Solar/Wind Harmer
7.983
970373AG2-245 GEN
Solar/Wind Harmer
45.77
972207SS24-0001
Solar/Wind Harmer
48.008
270055AF2-134 C O1
Solar/Wind Harmer
6.513
24441205WTRV SLR C
Solar/Wind Harmer
0.29
274723RIVER EC ;12
Adder
38.551
274751CRETE EC ;1U
Adder
10.506
274754CRETE EC ;4U
Adder
10.506
274812UNIV PK N;8U
Adder
10.696
958381AF2-132 GEN
Solar/Wind Harmer
19.303
964861AG1-349 GEN
Solar/Wind Harmer
16.707
971917AH1-482 GEN
Solar/Wind Harmer
19.276
274802UNIV PARK;5U
Adder
12.378
941551AE2-152 GEN
Solar/Wind Harmer
9.563
274676JOLIET 29;8U
Adder
64.471
274674JOLIET 9 ;6U
Adder
32.294
274732ELWOOD EC;7P
Adder
34.447
274871GR RIDGE ;2U
Solar/Wind Harmer
16.081
274847GR RIDGE ;BU
Solar/Wind Harmer
10.574
940581AE2-045 GEN
Solar/Wind Harmer
21.331
971605AH1-302 GEN
Solar/Wind Harmer
18.239
274745AC1-111 GEN9
Adder
11.614
276694AA1-018 GEN2
Solar/Wind Harmer
12.934
276691AA1-018 GEN1
Solar/Wind Harmer
1.546
274861TOP CROP ;1U
Solar/Wind Harmer
12.41
274682WAUKEGAN ;7U
Adder
36.793
274828WAUKEGAN ;BP
Adder
22.581
962781AG1-127 GEN
Solar/Wind Harmer
19.295
939401AE1-172 GEN
Solar/Wind Harmer
28.229
274872LEEDK;1U
Solar/Wind Harmer
16.613
276805AD2-038 GEN
Solar/Wind Harmer
10.371
276882AE2-255 GEN
Solar/Wind Harmer
6.784
24791305MDL-5G
Solar/Wind Harmer
4.847
971997AH1-543 GEN
Solar/Wind Harmer
31.619
957471AF2-041 GEN
Solar/Wind Harmer
59.62
959081AF2-199 GEN
Solar/Wind Harmer
19.873
971067AG2-660 GEN
Solar/Wind Harmer
4.622
274822ROCKFORD ;11
Adder
38.853
970819AG2-516 GEN
Solar/Wind Harmer
23.604
274761LEE CO EC;2U
Adder
18.06
274766LEE CO EC;7U
Adder
17.848
24728605AND G2
Adder
5.106
970091AG2-072 GEN
Adder
76.464
970569AG2-363 GEN
Solar/Wind Harmer
55.286
LAGNLTFEXP_LAGN->PJM
CLTF
13.81
TVALTFEXP_TVA->PJM
CLTF
5.072
NYPJM->LTFIMP_NY
CLTF
3.41
LGEELTFEXP_LGEE->PJM
CLTF
4.521
WECLTFEXP_WEC->PJM
CLTF
7.524
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.341
AG2-052LTFEXP_AG2-052->PJM
LTF
0.477
AH1-155LTFEXP_AH1-155->PJM
LTF
0.716
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
229.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.07
MECLTFEXP_MEC->PJM
CLTF
27.061
SIGELTFEXP_SIGE->PJM
CLTF
0.509
CBM West 2LTFEXP_CBM-W2->PJM
CBM
128.929

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.5 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6047.92
MW Contribution:
34.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.013
24642205MAYFLWER
50/50
0.076
274772LINCOLN ;3U
50/50
13.47
944961AF1-161 GEN
50/50
5.942
962601AG1-109 GEN
50/50
5.942
971347AH1-153 GEN
Solar/Wind Harmer
11.131
270043AE2-236 GEN
Solar/Wind Harmer
11.57
247643Z2-116 C
Solar/Wind Harmer
0.145
24441505OLIV SLR
Solar/Wind Harmer
0.278
270505AE1-170 C O1
Solar/Wind Harmer
30.994
945111AF1-176 GEN
Solar/Wind Harmer
11.613
274724RIVER EC ;11
Adder
35.793
972231SS25-0005
Solar/Wind Harmer
19.144
972181SS23-001
Solar/Wind Harmer
11.965
274752CRETE EC ;2U
Adder
9.86
274753CRETE EC ;3U
Adder
9.86
276164X3-005 C
Solar/Wind Harmer
1.414
270063AE2-323 C
Solar/Wind Harmer
4.413
274814UNIV PK N;0U
Adder
10.141
274807UNIV PK N;3U
Adder
10.119
274811UNIV PK N;7U
Adder
10.053
970707AG2-453 GEN
Solar/Wind Harmer
56.193
972259AH1-714 GEN
Adder
38.13
274803UNIV PARK;6U
Adder
11.65
274826FISK ;BP
Adder
21.872
274887GEN-1.85
Solar/Wind Harmer
10.639
276772AC2-154 GEN
Solar/Wind Harmer
5.573
276843GEN-1.7
Solar/Wind Harmer
1.145
276806AD2-047 C O1
Solar/Wind Harmer
21.363
972038AH1-567 GEN2
Adder
0.728
939351AE1-166 GEN
Solar/Wind Harmer
11.795
944531AF1-118 GEN
Solar/Wind Harmer
69.364
274676JOLIET 29;8U
Adder
58.599
274729ELWOOD EC;1P
Adder
32.486
274730ELWOOD EC;6P
Adder
32.486
274734ELWOOD EC;8P
Adder
32.486
274736ELWOOD EC;9P
Adder
32.486
943121AE2-341 GEN
Solar/Wind Harmer
29.475
943591AF1-030 GEN
Solar/Wind Harmer
19.65
964401AG1-302 GEN
Solar/Wind Harmer
17.727
274862TOP CROP ;2U
Solar/Wind Harmer
9.796
274682WAUKEGAN ;7U
Adder
34.771
276868AE1-113 GEN
Solar/Wind Harmer
19.287
274879MINONK ;1U
Solar/Wind Harmer
12.858
276799AD1-013 GEN
Solar/Wind Harmer
4.192
946671AF1-331 GEN
Solar/Wind Harmer
0.794
274855GSG-6 ;RU
Solar/Wind Harmer
7
274850MENDOTA H;RU
Solar/Wind Harmer
4.867
276602WESTBROOK C
Solar/Wind Harmer
4.03
959091AF2-200 GEN
Solar/Wind Harmer
37.68
970571AG2-364 GEN
Solar/Wind Harmer
37.244
274857EASY ROAD;U1
Solar/Wind Harmer
8.837
274760LEE CO EC;1U
Adder
17.161
274767LEE CO EC;8U
Adder
16.958
24728705AND G3
Adder
10.702
24728505AND G1
Adder
5.117
24690905MDL-1G C
Solar/Wind Harmer
9.102
24344005CKG1
50/50
13.518
270144AC1-141 ST1_
50/50
4.427
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
13.47
274776LINCOLN ;7U
50/50
13.47
274777LINCOLN ;8U
50/50
13.47
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
7.904
971771AH1-392 GEN
Solar/Wind Harmer
18.817
270526AF1-158 GEN
Solar/Wind Harmer
9.45
270071AF1-092 GEN
Solar/Wind Harmer
31.045
944161AF1-084 GEN
Solar/Wind Harmer
4.491
972037AH1-567 GEN1
Adder
0.366
274827FISK ;RP
Adder
15.501
960591AF2-350 GEN
Solar/Wind Harmer
19.969
972228AH1-698 GEN2
Adder
7.394
972227AH1-698 GEN1
Adder
5.206
274800UNIV PARK;3U
Adder
11.637
274801UNIV PARK;4U
Adder
11.637
274687WILL CNTY;4U
Adder
55.408
274687WILL CNTY;4U
Adder
55.408
274675JOLIET 29;7U
Adder
60.77
274675JOLIET 29;7U
Adder
58.6
970031AG2-029 GEN
Solar/Wind Harmer
49.481
274728ELWOOD EC;5P
Adder
32.486
274731ELWOOD EC;2P
Adder
32.486
274733ELWOOD EC;3P
Adder
32.486
274735ELWOOD EC;4P
Adder
32.486
276893AG1-478 C
Solar/Wind Harmer
1.086
970833AG2-524 GEN
Solar/Wind Harmer
17.239
970833AG2-524 GEN
Solar/Wind Harmer
8.018
274744AC1-111 GEN8
Adder
10.963
274746AC1-111 G10
Adder
10.963
958391AF2-133 GEN
Solar/Wind Harmer
17.588
24729505KEY G4
Adder
12.577
959141AF2-205 GEN
Solar/Wind Harmer
11.657
970073AG2-061 GEN
Solar/Wind Harmer
4.454
971675AH1-338 GEN
Solar/Wind Harmer
34.138
971411AH1-196 GEN
Solar/Wind Harmer
28.444
276861AD2-134 GEN
Solar/Wind Harmer
3.385
276863AD2-134 GEN
Solar/Wind Harmer
3.385
274863CRW1-WTG
Solar/Wind Harmer
10.573
274864CRW2-WTG
Solar/Wind Harmer
10.573
971171AH1-044 GEN
Solar/Wind Harmer
37.68
276889AE2-281 GEN
Solar/Wind Harmer
3.614
274823ROCKFORD ;21
Adder
36.573
970169AG2-114 GEN
Solar/Wind Harmer
18.658
274856ECOGROVE ;U1
Solar/Wind Harmer
6.284
276611AD2-172 GEN
Solar/Wind Harmer
4.767
276612AE2-035 GEN
Solar/Wind Harmer
4.767
926823AC1-168 GEN
Solar/Wind Harmer
8.008
971549AH1-272 GEN
Solar/Wind Harmer
34.378
971681AH1-341 GEN
Solar/Wind Harmer
27.789
972267AH1-718 GEN
Adder
7.604
270102X2-052 ST
50/50
3.362
270100X2-052 CT1
50/50
3.107
270101X2-052 CT2
50/50
3.107
24643105BUCHANAN
50/50
0.026
274770LINCOLN ;1U
50/50
13.47
274771LINCOLN ;2U
50/50
13.47
247620Y3-023
50/50
0.993
970349AG2-230 GEN
Solar/Wind Harmer
33.392
965681AG1-436 GEN
Solar/Wind Harmer
26.146
965791AG1-447 GEN
Solar/Wind Harmer
13.377
961051AF2-396 GEN
Solar/Wind Harmer
32.5
961051AF2-396 GEN
Solar/Wind Harmer
15.116
274805UNIV PK N;1U
Adder
10.075
274808UNIV PK N;4U
Adder
10.009
274888KELLY CRK;1U
Solar/Wind Harmer
11.784
276776AD2-060 GEN
Solar/Wind Harmer
0.836
958011AF2-095 GEN
Solar/Wind Harmer
28.756
970941AG2-585 GEN
Solar/Wind Harmer
10.983
276897AD1-100 C
Solar/Wind Harmer
92.385
270535AF1-215 GEN1
Solar/Wind Harmer
8.997
270536AF1-215 GEN2
Solar/Wind Harmer
8.997
274674JOLIET 9 ;6U
Adder
30.452
276893AG1-478 C
Solar/Wind Harmer
0.866
274695ROCKY RD ;2P
Adder
21.58
274693ROCKY RD ;1P
Adder
21.367
274697ROCKY RD ;3P
Adder
5.862
274696ROCKY RD ;4P
Adder
22.088
958481AF2-142 GEN
Solar/Wind Harmer
29.068
274683WAUKEGAN ;8U
Adder
40.715
274683WAUKEGAN ;8U
Adder
34.321
962691AG1-118 GEN
Solar/Wind Harmer
57.731
960751AF2-366 GEN
Solar/Wind Harmer
5.507
958491AF2-143 GEN
Solar/Wind Harmer
28.728
276901AD2-066 C O1
Solar/Wind Harmer
6.709
971341AH1-150 GEN
Solar/Wind Harmer
37.68
971343AH1-151 GEN
Solar/Wind Harmer
37.68
276872AE1-163_GEN1
Solar/Wind Harmer
12.65
276876AE1-163_GEN2
Solar/Wind Harmer
12.65
945421AF1-207 GEN
Solar/Wind Harmer
26.326
957841AF2-078 GEN
Solar/Wind Harmer
11.333
972235AH1-702 GEN1
Adder
4.72
972236AH1-702 GEN2
Adder
4.104
938861AE1-114 GEN
Solar/Wind Harmer
15.18
274764LEE CO EC;5U
Adder
17.201
274765LEE CO EC;6U
Adder
17.201
274762LEE CO EC;3U
Adder
17.161
274763LEE CO EC;4U
Adder
16.999
247621Y3-024
Adder
0.338
24728805RICHG1
Adder
3.746
24728905RICHG2
Adder
3.746
270349AD2-093_GEN
Solar/Wind Helper
1.553
270471AD2-092_GEN
Solar/Wind Helper
1.553
24344105CKG2
50/50
17.278
270143AC1-141 CT2_
50/50
5.013
24639705ELKHART HY
50/50
0.334
274773LINCOLN ;4U
50/50
13.47
274774LINCOLN ;5U
50/50
13.47
970521AG2-332 GEN
50/50
23.772
24307105BERRINSP G
50/50
0.044
270216AD2-079_GEN
Solar/Wind Harmer
1.258
957891AF2-083 GEN
Solar/Wind Harmer
30.937
945111AF1-176 GEN
Solar/Wind Harmer
36.641
972207SS24-0001
Solar/Wind Harmer
45.133
270449AD2-020 GEN
Solar/Wind Harmer
5.728
943021AE2-325 GEN
Solar/Wind Harmer
7.444
274723RIVER EC ;12
Adder
36.21
274751CRETE EC ;1U
Adder
9.86
274754CRETE EC ;4U
Adder
9.86
970373AG2-245 GEN
Solar/Wind Harmer
42.249
274812UNIV PK N;8U
Adder
10.053
24441205WTRV SLR C
Solar/Wind Harmer
0.27
274802UNIV PARK;5U
Adder
11.65
941551AE2-152 GEN
Solar/Wind Harmer
9.02
270055AF2-134 C O1
Solar/Wind Harmer
5.998
274676JOLIET 29;8U
Adder
60.769
274674JOLIET 9 ;6U
Adder
30.452
274732ELWOOD EC;7P
Adder
32.486
274871GR RIDGE ;2U
Solar/Wind Harmer
15.176
274847GR RIDGE ;BU
Solar/Wind Harmer
9.979
274745AC1-111 GEN9
Adder
10.963
958381AF2-132 GEN
Solar/Wind Harmer
17.727
964861AG1-349 GEN
Solar/Wind Harmer
15.339
971917AH1-482 GEN
Solar/Wind Harmer
17.697
276694AA1-018 GEN2
Solar/Wind Harmer
12.227
276691AA1-018 GEN1
Solar/Wind Harmer
1.461
274861TOP CROP ;1U
Solar/Wind Harmer
11.733
274682WAUKEGAN ;7U
Adder
34.771
274828WAUKEGAN ;BP
Adder
21.342
939401AE1-172 GEN
Solar/Wind Harmer
26.783
962781AG1-127 GEN
Solar/Wind Harmer
18.254
276805AD2-038 GEN
Solar/Wind Harmer
9.821
274872LEEDK;1U
Solar/Wind Harmer
15.721
940581AE2-045 GEN
Solar/Wind Harmer
19.516
971605AH1-302 GEN
Solar/Wind Harmer
16.687
276882AE2-255 GEN
Solar/Wind Harmer
6.429
971997AH1-543 GEN
Solar/Wind Harmer
29.984
957471AF2-041 GEN
Solar/Wind Harmer
56.52
959081AF2-199 GEN
Solar/Wind Harmer
18.84
971067AG2-660 GEN
Solar/Wind Harmer
4.381
274822ROCKFORD ;11
Adder
36.841
970819AG2-516 GEN
Solar/Wind Harmer
22.395
970569AG2-363 GEN
Solar/Wind Harmer
55.866
274858EASY ROAD;U2
Solar/Wind Harmer
8.837
274761LEE CO EC;2U
Adder
17.161
274766LEE CO EC;7U
Adder
16.958
970091AG2-072 GEN
Adder
105.739
24728605AND G2
Adder
5.117
LAGNLTFEXP_LAGN->PJM
CLTF
14.281
TVALTFEXP_TVA->PJM
CLTF
5.469
NYPJM->LTFIMP_NY
CLTF
3.371
LGEELTFEXP_LGEE->PJM
CLTF
5.638
WECLTFEXP_WEC->PJM
CLTF
7.136
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.164
AG2-052LTFEXP_AG2-052->PJM
LTF
0.449
AH1-155LTFEXP_AH1-155->PJM
LTF
0.674
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5
CBM West 1LTFEXP_CBM-W1->PJM
CBM
218.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.394
MECLTFEXP_MEC->PJM
CLTF
26.166
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.166

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#2995_05E LIMA 345_M_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2995_05E LIMA 345_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.99 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5798.45
MW Contribution:
33.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727105RPMNG2
50/50
2.055
965431AG1-411 GEN
50/50
25.108
270142AC1-141 CT1_
50/50
4.881
24642205MAYFLWER
50/50
0.074
944961AF1-161 GEN
50/50
5.776
962601AG1-109 GEN
50/50
5.776
270043AE2-236 GEN
Solar/Wind Harmer
11.898
965021AG1-366 GEN
Solar/Wind Harmer
5.027
246938BC-WTG3
Solar/Wind Harmer
8.591
270491AE1-102 GEN2
Solar/Wind Harmer
2.807
971347AH1-153 GEN
Solar/Wind Harmer
10.76
247643Z2-116 C
Solar/Wind Harmer
0.142
270063AE2-323 C
Solar/Wind Harmer
4.479
270505AE1-170 C O1
Solar/Wind Harmer
30.155
944531AF1-118 GEN
Solar/Wind Harmer
70.306
24441505OLIV SLR
Solar/Wind Harmer
0.268
945111AF1-176 GEN
Solar/Wind Harmer
11.341
274772LINCOLN ;3U
Adder
12.091
274724RIVER EC ;11
Adder
34.157
972231SS25-0005
Solar/Wind Harmer
18.272
972181SS23-001
Solar/Wind Harmer
11.42
274752CRETE EC ;2U
Adder
9.411
274753CRETE EC ;3U
Adder
9.411
276164X3-005 C
Solar/Wind Harmer
1.348
274814UNIV PK N;0U
Adder
9.666
274807UNIV PK N;3U
Adder
9.645
274811UNIV PK N;7U
Adder
9.583
970707AG2-453 GEN
Solar/Wind Harmer
53.448
274803UNIV PARK;6U
Adder
11.092
274826FISK ;BP
Adder
20.825
972259AH1-714 GEN
Adder
36.259
972038AH1-567 GEN2
Adder
0.693
274887GEN-1.85
Solar/Wind Harmer
10.123
276772AC2-154 GEN
Solar/Wind Harmer
5.302
276843GEN-1.7
Solar/Wind Harmer
1.089
276806AD2-047 C O1
Solar/Wind Harmer
20.325
939351AE1-166 GEN
Solar/Wind Harmer
11.202
274676JOLIET 29;8U
Adder
55.716
274729ELWOOD EC;1P
Adder
30.869
274730ELWOOD EC;6P
Adder
30.869
274734ELWOOD EC;8P
Adder
30.869
274736ELWOOD EC;9P
Adder
30.869
943121AE2-341 GEN
Solar/Wind Harmer
27.994
943591AF1-030 GEN
Solar/Wind Harmer
18.663
274862TOP CROP ;2U
Solar/Wind Harmer
9.289
274682WAUKEGAN ;7U
Adder
32.996
964401AG1-302 GEN
Solar/Wind Harmer
16.573
276868AE1-113 GEN
Solar/Wind Harmer
18.252
274879MINONK ;1U
Solar/Wind Harmer
12.168
276799AD1-013 GEN
Solar/Wind Harmer
3.97
946671AF1-331 GEN
Solar/Wind Harmer
0.752
274855GSG-6 ;RU
Solar/Wind Harmer
6.63
274850MENDOTA H;RU
Solar/Wind Harmer
4.61
276602WESTBROOK C
Solar/Wind Harmer
3.817
959091AF2-200 GEN
Solar/Wind Harmer
35.67
274760LEE CO EC;1U
Adder
16.218
274767LEE CO EC;8U
Adder
16.027
24728705AND G3
Adder
9.725
24728505AND G1
Adder
4.65
270284AF1-227 GEN1
Solar/Wind Helper
2.338
270287AF1-227 GEN3
Solar/Wind Helper
0.857
970571AG2-364 GEN
Solar/Wind Harmer
1.982
24727205RPMNG3
50/50
2.043
24641605TWIN BRNCH
50/50
0.035
270144AC1-141 ST1_
50/50
4.31
24344005CKG1
50/50
13.058
24653605MOTTVILLE
50/50
0.008
24729505KEY G4
50/50
13.483
959331AF2-224 GEN
Solar/Wind Harmer
21.616
957201AF2-014 GEN
Solar/Wind Harmer
9.792
270435AC2-044 GEN
Solar/Wind Harmer
4.318
270071AF1-092 GEN
Solar/Wind Harmer
31.311
970031AG2-029 GEN
Solar/Wind Harmer
51.31
971771AH1-392 GEN
Solar/Wind Harmer
18.28
270526AF1-158 GEN
Solar/Wind Harmer
9.126
960681AF2-359 GEN
Solar/Wind Harmer
7.58
944161AF1-084 GEN
Solar/Wind Harmer
4.359
274775LINCOLN ;6U
Adder
12.091
274776LINCOLN ;7U
Adder
12.091
274777LINCOLN ;8U
Adder
12.091
972037AH1-567 GEN1
Adder
0.348
274827FISK ;RP
Adder
14.759
274800UNIV PARK;3U
Adder
11.077
274801UNIV PARK;4U
Adder
11.077
960591AF2-350 GEN
Solar/Wind Harmer
19
972228AH1-698 GEN2
Adder
7.032
972227AH1-698 GEN1
Adder
4.951
274687WILL CNTY;4U
Adder
52.694
274687WILL CNTY;4U
Adder
52.694
274675JOLIET 29;7U
Adder
57.78
274675JOLIET 29;7U
Adder
55.717
274728ELWOOD EC;5P
Adder
30.869
274731ELWOOD EC;2P
Adder
30.869
274733ELWOOD EC;3P
Adder
30.869
274735ELWOOD EC;4P
Adder
30.869
276893AG1-478 C
Solar/Wind Harmer
1.032
970833AG2-524 GEN
Solar/Wind Harmer
16.37
970833AG2-524 GEN
Solar/Wind Harmer
7.614
274744AC1-111 GEN8
Adder
10.411
274746AC1-111 G10
Adder
10.411
958711AF2-162 GEN
Solar/Wind Harmer
1.841
963791AG1-232 GEN
Solar/Wind Harmer
24.524
970073AG2-061 GEN
Solar/Wind Harmer
4.218
958391AF2-133 GEN
Solar/Wind Harmer
16.395
971411AH1-196 GEN
Solar/Wind Harmer
26.946
971675AH1-338 GEN
Solar/Wind Harmer
32.333
276861AD2-134 GEN
Solar/Wind Harmer
3.206
276863AD2-134 GEN
Solar/Wind Harmer
3.206
959141AF2-205 GEN
Solar/Wind Harmer
10.841
971549AH1-272 GEN
Solar/Wind Harmer
33.083
274863CRW1-WTG
Solar/Wind Harmer
9.959
274864CRW2-WTG
Solar/Wind Harmer
9.959
971171AH1-044 GEN
Solar/Wind Harmer
35.67
276889AE2-281 GEN
Solar/Wind Harmer
3.415
274823ROCKFORD ;21
Adder
34.62
274856ECOGROVE ;U1
Solar/Wind Harmer
5.944
276611AD2-172 GEN
Solar/Wind Harmer
4.509
276612AE2-035 GEN
Solar/Wind Harmer
4.509
972267AH1-718 GEN
Adder
7.179
270102X2-052 ST
50/50
3.227
270100X2-052 CT1
50/50
2.982
270101X2-052 CT2
50/50
2.982
247620Y3-023
50/50
0.986
24643105BUCHANAN
50/50
0.025
24729405KEY G3
50/50
0.736
24729305KEY G2
50/50
0.724
24729205KEY G1
50/50
0.72
246937BC-WTG2
Solar/Wind Harmer
8.445
970349AG2-230 GEN
Solar/Wind Harmer
32.281
965681AG1-436 GEN
Solar/Wind Harmer
25.077
965791AG1-447 GEN
Solar/Wind Harmer
12.83
961051AF2-396 GEN
Solar/Wind Harmer
31.647
961051AF2-396 GEN
Solar/Wind Harmer
14.72
274770LINCOLN ;1U
Adder
12.091
274771LINCOLN ;2U
Adder
12.091
274805UNIV PK N;1U
Adder
9.604
274808UNIV PK N;4U
Adder
9.541
274888KELLY CRK;1U
Solar/Wind Harmer
11.212
276776AD2-060 GEN
Solar/Wind Harmer
0.795
958011AF2-095 GEN
Solar/Wind Harmer
27.36
970941AG2-585 GEN
Solar/Wind Harmer
10.45
276897AD1-100 C
Solar/Wind Harmer
87.747
274674JOLIET 9 ;6U
Adder
28.942
276893AG1-478 C
Solar/Wind Harmer
0.823
270535AF1-215 GEN1
Solar/Wind Harmer
8.458
270536AF1-215 GEN2
Solar/Wind Harmer
8.458
274695ROCKY RD ;2P
Adder
20.477
274693ROCKY RD ;1P
Adder
20.275
274697ROCKY RD ;3P
Adder
5.563
274696ROCKY RD ;4P
Adder
20.96
958481AF2-142 GEN
Solar/Wind Harmer
27.566
274683WAUKEGAN ;8U
Adder
38.634
274683WAUKEGAN ;8U
Adder
32.567
962691AG1-118 GEN
Solar/Wind Harmer
54.744
960751AF2-366 GEN
Solar/Wind Harmer
5.221
944541AF1-119 GEN
Solar/Wind Harmer
7.618
960971AF2-388 GEN
Solar/Wind Harmer
19.889
958491AF2-143 GEN
Solar/Wind Harmer
27.204
276901AD2-066 C O1
Solar/Wind Harmer
6.348
971341AH1-150 GEN
Solar/Wind Harmer
35.67
971343AH1-151 GEN
Solar/Wind Harmer
35.67
276872AE1-163_GEN1
Solar/Wind Harmer
11.953
276876AE1-163_GEN2
Solar/Wind Harmer
11.953
972235AH1-702 GEN1
Adder
4.467
972236AH1-702 GEN2
Adder
3.884
274764LEE CO EC;5U
Adder
16.256
274765LEE CO EC;6U
Adder
16.256
274762LEE CO EC;3U
Adder
16.218
274763LEE CO EC;4U
Adder
16.065
247621Y3-024
Adder
0.333
24728805RICHG1
Adder
3.368
24728905RICHG2
Adder
3.368
270349AD2-093_GEN
Solar/Wind Helper
1.751
270471AD2-092_GEN
Solar/Wind Helper
1.751
270054AF2-122 C O1
Solar/Wind Helper
1.207
24344105CKG2
50/50
16.637
24727005RPMNG1
50/50
2.055
270143AC1-141 CT2_
50/50
4.881
24639705ELKHART HY
50/50
0.33
970521AG2-332 GEN
50/50
23.507
24307105BERRINSP G
50/50
0.042
965011AG1-365 GEN
Solar/Wind Harmer
21.616
965421AG1-410 GEN
Solar/Wind Harmer
64.779
246936BC-WTG1
Solar/Wind Harmer
8.445
270489AE1-102 GEN1
Solar/Wind Harmer
2.807
270216AD2-079_GEN
Solar/Wind Harmer
1.233
957891AF2-083 GEN
Solar/Wind Harmer
30.125
945111AF1-176 GEN
Solar/Wind Harmer
35.784
270449AD2-020 GEN
Solar/Wind Harmer
5.568
943021AE2-325 GEN
Solar/Wind Harmer
7.236
972207SS24-0001
Solar/Wind Harmer
42.99
274773LINCOLN ;4U
Adder
12.091
274774LINCOLN ;5U
Adder
12.091
24441205WTRV SLR C
Solar/Wind Harmer
0.261
274723RIVER EC ;12
Adder
34.556
274751CRETE EC ;1U
Adder
9.411
274754CRETE EC ;4U
Adder
9.411
274812UNIV PK N;8U
Adder
9.583
274802UNIV PARK;5U
Adder
11.092
970373AG2-245 GEN
Solar/Wind Harmer
39.924
941551AE2-152 GEN
Solar/Wind Harmer
8.567
274676JOLIET 29;8U
Adder
57.779
274674JOLIET 9 ;6U
Adder
28.942
274732ELWOOD EC;7P
Adder
30.869
274871GR RIDGE ;2U
Solar/Wind Harmer
14.41
274847GR RIDGE ;BU
Solar/Wind Harmer
9.475
270055AF2-134 C O1
Solar/Wind Harmer
5.638
274745AC1-111 GEN9
Adder
10.411
276694AA1-018 GEN2
Solar/Wind Harmer
11.596
276691AA1-018 GEN1
Solar/Wind Harmer
1.386
274861TOP CROP ;1U
Solar/Wind Harmer
11.126
274682WAUKEGAN ;7U
Adder
32.996
274828WAUKEGAN ;BP
Adder
20.251
958381AF2-132 GEN
Solar/Wind Harmer
16.573
964861AG1-349 GEN
Solar/Wind Harmer
14.332
971917AH1-482 GEN
Solar/Wind Harmer
16.535
962781AG1-127 GEN
Solar/Wind Harmer
17.307
965651AG1-433 GEN
Solar/Wind Harmer
9.945
274872LEEDK;1U
Solar/Wind Harmer
14.902
939401AE1-172 GEN
Solar/Wind Harmer
25.288
276805AD2-038 GEN
Solar/Wind Harmer
9.3
276882AE2-255 GEN
Solar/Wind Harmer
6.084
971997AH1-543 GEN
Solar/Wind Harmer
28.352
957471AF2-041 GEN
Solar/Wind Harmer
53.504
959081AF2-199 GEN
Solar/Wind Harmer
17.835
971067AG2-660 GEN
Solar/Wind Harmer
4.148
274822ROCKFORD ;11
Adder
34.873
940581AE2-045 GEN
Solar/Wind Harmer
18.098
971605AH1-302 GEN
Solar/Wind Harmer
15.474
958861AF2-177 GEN
Solar/Wind Harmer
19.392
970819AG2-516 GEN
Solar/Wind Harmer
21.19
274761LEE CO EC;2U
Adder
16.218
274766LEE CO EC;7U
Adder
16.027
24728605AND G2
Adder
4.65
970091AG2-072 GEN
Adder
73.567
270286AF1-227 GEN2
Solar/Wind Helper
0.857
970569AG2-363 GEN
Solar/Wind Harmer
2.973
LAGNLTFEXP_LAGN->PJM
CLTF
13.291
TVALTFEXP_TVA->PJM
CLTF
5.088
NYPJM->LTFIMP_NY
CLTF
3.183
LGEELTFEXP_LGEE->PJM
CLTF
4.365
WECLTFEXP_WEC->PJM
CLTF
6.755
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.773
AG2-052LTFEXP_AG2-052->PJM
LTF
0.424
AH1-155LTFEXP_AH1-155->PJM
LTF
0.636
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.264
CBM West 1LTFEXP_CBM-W1->PJM
CBM
202.656
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.966
MECLTFEXP_MEC->PJM
CLTF
24.462
SIGELTFEXP_SIGE->PJM
CLTF
0.472
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.711

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.53 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5607.44
MW Contribution:
26.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.013
24642205MAYFLWER
50/50
0.076
274772LINCOLN ;3U
50/50
18.336
944961AF1-161 GEN
50/50
5.942
962601AG1-109 GEN
50/50
5.942
971347AH1-153 GEN
Solar/Wind Harmer
7.766
270043AE2-236 GEN
Solar/Wind Harmer
9.417
270505AE1-170 C O1
Solar/Wind Harmer
15.137
945111AF1-176 GEN
Solar/Wind Harmer
11.613
274724RIVER EC ;11
Adder
35.793
274752CRETE EC ;2U
Adder
16.621
274753CRETE EC ;3U
Adder
16.621
270063AE2-323 C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
10.141
274807UNIV PK N;3U
Adder
10.119
274811UNIV PK N;7U
Adder
10.053
970707AG2-453 GEN
Solar/Wind Harmer
45.738
972259AH1-714 GEN
Adder
38.13
24344005CKG1
50/50
13.518
270144AC1-141 ST1_
50/50
4.427
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
18.336
274776LINCOLN ;7U
50/50
18.336
274777LINCOLN ;8U
50/50
18.336
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
14.587
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
27.676
972037AH1-567 GEN1
Adder
0.366
274827FISK ;RP
Adder
15.501
960591AF2-350 GEN
Solar/Wind Harmer
13.932
972228AH1-698 GEN2
Adder
7.394
972227AH1-698 GEN1
Adder
5.206
274800UNIV PARK;3U
Adder
11.637
274801UNIV PARK;4U
Adder
11.637
274803UNIV PARK;6U
Adder
11.65
274826FISK ;BP
Adder
21.872
274887GEN-1.85
Solar/Wind Harmer
0.362
276843GEN-1.7
Solar/Wind Harmer
0.45
276806AD2-047 C O1
Solar/Wind Harmer
7.895
972038AH1-567 GEN2
Adder
0.728
939351AE1-166 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
61.966
274676JOLIET 29;8U
Adder
58.599
274729ELWOOD EC;1P
Adder
32.486
274730ELWOOD EC;6P
Adder
32.486
274734ELWOOD EC;8P
Adder
32.486
274736ELWOOD EC;9P
Adder
32.486
943121AE2-341 GEN
Solar/Wind Harmer
22.986
943591AF1-030 GEN
Solar/Wind Harmer
15.286
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.824
274682WAUKEGAN ;7U
Adder
34.771
276868AE1-113 GEN
Solar/Wind Harmer
2.661
274879MINONK ;1U
Solar/Wind Harmer
0.555
946671AF1-331 GEN
Solar/Wind Harmer
1.412
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.154
959091AF2-200 GEN
Solar/Wind Harmer
26.289
970571AG2-364 GEN
Solar/Wind Harmer
25.984
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
17.161
274767LEE CO EC;8U
Adder
16.958
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
12.865
965021AG1-366 GEN
Solar/Wind Harmer
4.261
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.422
274687WILL CNTY;4U
Adder
55.408
274687WILL CNTY;4U
Adder
55.408
274675JOLIET 29;7U
Adder
60.77
274675JOLIET 29;7U
Adder
58.6
970031AG2-029 GEN
Solar/Wind Harmer
7.48
274728ELWOOD EC;5P
Adder
32.486
274731ELWOOD EC;2P
Adder
32.486
274733ELWOOD EC;3P
Adder
32.486
274735ELWOOD EC;4P
Adder
32.486
970833AG2-524 GEN
Solar/Wind Harmer
15.154
970833AG2-524 GEN
Solar/Wind Harmer
10.103
274744AC1-111 GEN8
Adder
10.963
274746AC1-111 G10
Adder
10.963
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.577
959141AF2-205 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
4.454
971611AH1-305 GEN
Solar/Wind Harmer
7.947
971675AH1-338 GEN
Solar/Wind Harmer
5.16
971411AH1-196 GEN
Solar/Wind Harmer
19.845
276861AD2-134 GEN
Solar/Wind Harmer
0.236
276863AD2-134 GEN
Solar/Wind Harmer
0.236
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
26.289
274823ROCKFORD ;21
Adder
36.573
970169AG2-114 GEN
Solar/Wind Harmer
13.017
274856ECOGROVE ;U1
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
2.21
971549AH1-272 GEN
Solar/Wind Harmer
26.772
971681AH1-341 GEN
Solar/Wind Harmer
20.809
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
8.949
24344105CKG2
50/50
17.278
270143AC1-141 CT2_
50/50
5.013
24639705ELKHART HY
50/50
0.334
274773LINCOLN ;4U
50/50
18.336
274774LINCOLN ;5U
50/50
18.336
970521AG2-332 GEN
50/50
23.772
24307105BERRINSP G
50/50
0.044
957891AF2-083 GEN
Solar/Wind Harmer
23.982
945111AF1-176 GEN
Solar/Wind Harmer
25.563
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
7.444
274723RIVER EC ;12
Adder
36.21
274751CRETE EC ;1U
Adder
16.621
274754CRETE EC ;4U
Adder
16.621
970373AG2-245 GEN
Solar/Wind Harmer
29.476
274812UNIV PK N;8U
Adder
10.053
274802UNIV PARK;5U
Adder
11.65
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
60.769
274674JOLIET 9 ;6U
Adder
30.452
274732ELWOOD EC;7P
Adder
32.486
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
10.963
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
17.697
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
2.197
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
34.771
274828WAUKEGAN ;BP
Adder
21.342
939401AE1-172 GEN
Solar/Wind Harmer
10.03
962781AG1-127 GEN
Solar/Wind Harmer
12.744
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
16.687
276882AE2-255 GEN
Solar/Wind Harmer
1.552
971997AH1-543 GEN
Solar/Wind Harmer
6.973
957471AF2-041 GEN
Solar/Wind Harmer
39.433
959081AF2-199 GEN
Solar/Wind Harmer
13.144
971067AG2-660 GEN
Solar/Wind Harmer
4.381
274822ROCKFORD ;11
Adder
36.841
970819AG2-516 GEN
Solar/Wind Harmer
15.625
970569AG2-363 GEN
Solar/Wind Harmer
38.976
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
17.161
274766LEE CO EC;7U
Adder
16.958
965011AG1-365 GEN
Solar/Wind Harmer
12.784
276708O09 GEN2
Solar/Wind Harmer
0.449
276646AC1-214 GEN2
Solar/Wind Harmer
0.499
965651AG1-433 GEN
Solar/Wind Harmer
3.724
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
270102X2-052 ST
50/50
3.362
270100X2-052 CT1
50/50
3.107
270101X2-052 CT2
50/50
3.107
24643105BUCHANAN
50/50
0.026
274770LINCOLN ;1U
50/50
18.336
274771LINCOLN ;2U
50/50
18.336
247620Y3-023
50/50
0.993
970349AG2-230 GEN
Solar/Wind Harmer
23.297
965681AG1-436 GEN
Solar/Wind Harmer
18.242
965791AG1-447 GEN
Solar/Wind Harmer
13.377
961051AF2-396 GEN
Solar/Wind Harmer
28.57
961051AF2-396 GEN
Solar/Wind Harmer
19.046
274805UNIV PK N;1U
Adder
10.075
274808UNIV PK N;4U
Adder
10.009
274888KELLY CRK;1U
Solar/Wind Harmer
0.813
276776AD2-060 GEN
Solar/Wind Harmer
1.486
958011AF2-095 GEN
Solar/Wind Harmer
20.062
970941AG2-585 GEN
Solar/Wind Harmer
7.663
276897AD1-100 C
Solar/Wind Harmer
34.688
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
30.452
276893AG1-478 C
Solar/Wind Harmer
0.919
274695ROCKY RD ;2P
Adder
21.58
274693ROCKY RD ;1P
Adder
21.367
274697ROCKY RD ;3P
Adder
5.862
274696ROCKY RD ;4P
Adder
22.088
958481AF2-142 GEN
Solar/Wind Harmer
20.28
274683WAUKEGAN ;8U
Adder
40.715
274683WAUKEGAN ;8U
Adder
34.321
962691AG1-118 GEN
Solar/Wind Harmer
40.277
958491AF2-143 GEN
Solar/Wind Harmer
20.043
276901AD2-066 C O1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
26.289
971343AH1-151 GEN
Solar/Wind Harmer
26.289
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
4.72
972236AH1-702 GEN2
Adder
4.104
938861AE1-114 GEN
Solar/Wind Harmer
7.321
274764LEE CO EC;5U
Adder
17.201
274765LEE CO EC;6U
Adder
17.201
274762LEE CO EC;3U
Adder
17.161
274763LEE CO EC;4U
Adder
16.999
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
2.052
276645AC1-214 GEN1
Solar/Wind Harmer
0.499
944541AF1-119 GEN
Solar/Wind Harmer
0.848
960971AF2-388 GEN
Solar/Wind Harmer
7.448
972267AH1-718 GEN
Adder
7.604
276741O09 GEN1
Solar/Wind Harmer
0.449
274877BISHOP HL;1U
Solar/Wind Harmer
0.422
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
13.203
24386405FR-21G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.924
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
5.236
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
15.924
276668AB2-070 GEN1
Solar/Wind Harmer
0.46
276848AB2-070 GEN3
Solar/Wind Harmer
0.458
276849AB2-070 GEN2
Solar/Wind Harmer
0.46
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
2.196
971609AH1-304 GEN
Solar/Wind Harmer
1.842
965041AG1-368 GEN
Solar/Wind Harmer
11.074
944221AF1-090 GEN
Solar/Wind Harmer
6.279
964611AG1-324 GEN
Solar/Wind Harmer
4.011
247521TR3_G114
Solar/Wind Harmer
0.369
965051AG1-369 GEN
Solar/Wind Harmer
5.084
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.379
270543AE2-219 C
Solar/Wind Harmer
6.219
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
12.334
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.021
939741AE1-205 GEN
Solar/Wind Harmer
17.604
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
5.383
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
27.848
276621W2-048 GEN
Solar/Wind Harmer
0.575
270594AE1-207 GEN
Solar/Wind Harmer
12.64
270032AE2-172
Solar/Wind Harmer
7.524
965911AG1-460 GEN
Solar/Wind Harmer
2.221
276903AD2-071 C
Solar/Wind Harmer
12.218
270024AE2-089 GEN
Solar/Wind Harmer
0.002
270005AE1-210 C O1
Solar/Wind Harmer
2.315
970825AG2-519 GEN
Solar/Wind Harmer
3.725
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.127
970091AG2-072 GEN
Adder
105.739
24728605AND G2
Adder
5.117
965421AG1-410 GEN
Solar/Wind Harmer
25.535
970773AG2-487 GEN
Solar/Wind Harmer
1.491
246936BC-WTG1
Solar/Wind Harmer
0.325
270489AE1-102 GEN1
Solar/Wind Harmer
1.048
24386205FR-12G C
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
37.086
959611AF2-252 GEN
Solar/Wind Harmer
4.121
965931AG1-462 GEN
Solar/Wind Harmer
31.345
971087AG2-675 GEN
Solar/Wind Harmer
6.556
247642Z2-115 C
Solar/Wind Harmer
0.005
971993AH1-541 GEN
Solar/Wind Harmer
5.405
970289AG2-191 GEN
Solar/Wind Harmer
1.271
957381AF2-032 GEN
Solar/Wind Harmer
2.525
942481AE2-261 GEN
Solar/Wind Harmer
33.208
270004AE1-209 GEN
Solar/Wind Harmer
2.315
970193AG2-126 GEN
Solar/Wind Harmer
16.03
970825AG2-519 GEN
Solar/Wind Harmer
7.905
946031AF1-268 GEN
Solar/Wind Harmer
9.859
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.395
24695305TIMB G C
Solar/Wind Harmer
0.837
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
10.702
24728505AND G1
Adder
5.117
246938BC-WTG3
Solar/Wind Harmer
0.29
270491AE1-102 GEN2
Solar/Wind Harmer
1.048
942111AE2-223 GEN
Solar/Wind Harmer
4.087
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.408
960611AF2-352 GEN
Solar/Wind Harmer
4.121
942221AE2-234 GEN
Solar/Wind Harmer
4.822
970241AG2-163 GEN
Solar/Wind Harmer
6.864
970291AG2-192 GEN
Solar/Wind Harmer
1.502
970291AG2-192 GEN
Solar/Wind Harmer
0.693
276615X2-022 GEN
Solar/Wind Harmer
0.119
276838X2-022 GEN2
Solar/Wind Harmer
0.647
944231AF1-091 GEN
Solar/Wind Harmer
26.413
971613AH1-306 GEN
Solar/Wind Harmer
5.417
270031AE2-169
Solar/Wind Harmer
6.202
270599AE1-208 GEN
Solar/Wind Harmer
10.337
276916AD2-100_GEN
Solar/Wind Harmer
23.132
276911AD2-131_GEN
Solar/Wind Harmer
1.524
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
11.354
964611AG1-324 GEN
Solar/Wind Harmer
0.771
270201AC2-176 GEN
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.065
270247TR4_N_V136
Solar/Wind Harmer
0.065
971587AH1-292 GEN
Solar/Wind Harmer
7.235
247621Y3-024
Adder
0.338
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
8.884
970885AG2-551 GEN
Solar/Wind Harmer
2.961
970623AG2-406 GEN
Solar/Wind Harmer
1.577
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.325
24728805RICHG1
Adder
3.746
24728905RICHG2
Adder
3.746
270349AD2-093_GEN
Solar/Wind Helper
1.553
270471AD2-092_GEN
Solar/Wind Helper
1.553
LAGNLTFEXP_LAGN->PJM
CLTF
14.281
TVALTFEXP_TVA->PJM
CLTF
5.469
NYPJM->LTFIMP_NY
CLTF
3.371
LGEELTFEXP_LGEE->PJM
CLTF
5.638
WECLTFEXP_WEC->PJM
CLTF
7.136
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.164
AG2-052LTFEXP_AG2-052->PJM
LTF
0.449
AH1-155LTFEXP_AH1-155->PJM
LTF
0.674
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5
CBM West 1LTFEXP_CBM-W1->PJM
CBM
218.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.394
MECLTFEXP_MEC->PJM
CLTF
26.166
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.166

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11010___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11010___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.49 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5605.23
MW Contribution:
33.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270144AC1-141 ST1_
50/50
4.316
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.088
24653605MOTTVILLE
50/50
0.008
24729505KEY G4
50/50
13.633
270071AF1-092 GEN
Solar/Wind Harmer
31.464
959331AF2-224 GEN
Solar/Wind Harmer
20.693
971771AH1-392 GEN
Solar/Wind Harmer
18.313
970031AG2-029 GEN
Solar/Wind Harmer
50.82
270526AF1-158 GEN
Solar/Wind Harmer
9.147
960681AF2-359 GEN
Solar/Wind Harmer
7.603
944161AF1-084 GEN
Solar/Wind Harmer
4.365
274775LINCOLN ;6U
Adder
12.135
274776LINCOLN ;7U
Adder
12.135
270142AC1-141 CT1_
50/50
4.888
24642205MAYFLWER
50/50
0.074
944961AF1-161 GEN
50/50
5.783
962601AG1-109 GEN
50/50
5.783
270043AE2-236 GEN
Solar/Wind Harmer
11.918
971347AH1-153 GEN
Solar/Wind Harmer
10.798
965021AG1-366 GEN
Solar/Wind Harmer
4.812
24344105CKG2
50/50
16.695
270143AC1-141 CT2_
50/50
4.888
24639705ELKHART HY
50/50
0.33
970521AG2-332 GEN
50/50
23.474
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
20.693
270216AD2-079_GEN
Solar/Wind Harmer
1.234
957891AF2-083 GEN
Solar/Wind Harmer
30.161
945111AF1-176 GEN
Solar/Wind Harmer
35.806
270449AD2-020 GEN
Solar/Wind Harmer
5.575
943021AE2-325 GEN
Solar/Wind Harmer
7.245
972207SS24-0001
Solar/Wind Harmer
43.146
274773LINCOLN ;4U
Adder
12.135
274774LINCOLN ;5U
Adder
12.135
24441205WTRV SLR C
Solar/Wind Harmer
0.262
274723RIVER EC ;12
Adder
34.669
274751CRETE EC ;1U
Adder
9.44
274754CRETE EC ;4U
Adder
9.44
274812UNIV PK N;8U
Adder
9.614
274802UNIV PARK;5U
Adder
11.13
970373AG2-245 GEN
Solar/Wind Harmer
40.045
941551AE2-152 GEN
Solar/Wind Harmer
8.598
274676JOLIET 29;8U
Adder
57.988
274674JOLIET 9 ;6U
Adder
29.047
274732ELWOOD EC;7P
Adder
30.981
274871GR RIDGE ;2U
Solar/Wind Harmer
14.463
274847GR RIDGE ;BU
Solar/Wind Harmer
9.51
270055AF2-134 C O1
Solar/Wind Harmer
5.656
274745AC1-111 GEN9
Adder
10.45
276694AA1-018 GEN2
Solar/Wind Harmer
11.639
276691AA1-018 GEN1
Solar/Wind Harmer
1.391
274861TOP CROP ;1U
Solar/Wind Harmer
11.167
274682WAUKEGAN ;7U
Adder
33.121
274828WAUKEGAN ;BP
Adder
20.328
965651AG1-433 GEN
Solar/Wind Harmer
10.053
958381AF2-132 GEN
Solar/Wind Harmer
16.624
964861AG1-349 GEN
Solar/Wind Harmer
14.376
971917AH1-482 GEN
Solar/Wind Harmer
16.586
962781AG1-127 GEN
Solar/Wind Harmer
17.374
274872LEEDK;1U
Solar/Wind Harmer
14.96
939401AE1-172 GEN
Solar/Wind Harmer
25.386
276805AD2-038 GEN
Solar/Wind Harmer
9.335
276882AE2-255 GEN
Solar/Wind Harmer
6.107
971997AH1-543 GEN
Solar/Wind Harmer
28.462
958861AF2-177 GEN
Solar/Wind Harmer
19.601
957471AF2-041 GEN
Solar/Wind Harmer
53.717
959081AF2-199 GEN
Solar/Wind Harmer
17.906
971067AG2-660 GEN
Solar/Wind Harmer
4.164
274822ROCKFORD ;11
Adder
35.012
940581AE2-045 GEN
Solar/Wind Harmer
18.155
971605AH1-302 GEN
Solar/Wind Harmer
15.523
247643Z2-116 C
Solar/Wind Harmer
0.142
944531AF1-118 GEN
Solar/Wind Harmer
71.099
270063AE2-323 C
Solar/Wind Harmer
4.452
270505AE1-170 C O1
Solar/Wind Harmer
30.196
24441505OLIV SLR
Solar/Wind Harmer
0.269
945111AF1-176 GEN
Solar/Wind Harmer
11.348
274772LINCOLN ;3U
Adder
12.135
274724RIVER EC ;11
Adder
34.269
972231SS25-0005
Solar/Wind Harmer
18.33
972181SS23-001
Solar/Wind Harmer
11.456
274752CRETE EC ;2U
Adder
9.44
274753CRETE EC ;3U
Adder
9.44
276164X3-005 C
Solar/Wind Harmer
1.353
274814UNIV PK N;0U
Adder
9.698
274807UNIV PK N;3U
Adder
9.677
274811UNIV PK N;7U
Adder
9.614
970707AG2-453 GEN
Solar/Wind Harmer
53.645
274803UNIV PARK;6U
Adder
11.13
274826FISK ;BP
Adder
20.897
972259AH1-714 GEN
Adder
36.391
274887GEN-1.85
Solar/Wind Harmer
10.158
276772AC2-154 GEN
Solar/Wind Harmer
5.321
276843GEN-1.7
Solar/Wind Harmer
1.093
276806AD2-047 C O1
Solar/Wind Harmer
20.397
972038AH1-567 GEN2
Adder
0.696
939351AE1-166 GEN
Solar/Wind Harmer
11.243
274676JOLIET 29;8U
Adder
55.917
274729ELWOOD EC;1P
Adder
30.981
274730ELWOOD EC;6P
Adder
30.981
274734ELWOOD EC;8P
Adder
30.981
274736ELWOOD EC;9P
Adder
30.981
943121AE2-341 GEN
Solar/Wind Harmer
28.099
943591AF1-030 GEN
Solar/Wind Harmer
18.733
274862TOP CROP ;2U
Solar/Wind Harmer
9.324
274682WAUKEGAN ;7U
Adder
33.121
964401AG1-302 GEN
Solar/Wind Harmer
16.624
276868AE1-113 GEN
Solar/Wind Harmer
18.322
274879MINONK ;1U
Solar/Wind Harmer
12.215
276799AD1-013 GEN
Solar/Wind Harmer
3.986
946671AF1-331 GEN
Solar/Wind Harmer
0.755
274855GSG-6 ;RU
Solar/Wind Harmer
6.656
274850MENDOTA H;RU
Solar/Wind Harmer
4.628
276602WESTBROOK C
Solar/Wind Harmer
3.832
959091AF2-200 GEN
Solar/Wind Harmer
35.811
970571AG2-364 GEN
Solar/Wind Harmer
35.283
274760LEE CO EC;1U
Adder
16.284
274767LEE CO EC;8U
Adder
16.092
24728705AND G3
Adder
9.807
24728505AND G1
Adder
4.689
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270102X2-052 ST
50/50
3.237
270100X2-052 CT1
50/50
2.991
270101X2-052 CT2
50/50
2.991
247620Y3-023
50/50
0.984
24643105BUCHANAN
50/50
0.025
24729405KEY G3
50/50
0.744
24729305KEY G2
50/50
0.732
24729205KEY G1
50/50
0.728
970349AG2-230 GEN
Solar/Wind Harmer
32.395
965681AG1-436 GEN
Solar/Wind Harmer
25.151
965791AG1-447 GEN
Solar/Wind Harmer
12.868
961051AF2-396 GEN
Solar/Wind Harmer
31.679
961051AF2-396 GEN
Solar/Wind Harmer
14.735
274770LINCOLN ;1U
Adder
12.135
274771LINCOLN ;2U
Adder
12.135
274805UNIV PK N;1U
Adder
9.635
274808UNIV PK N;4U
Adder
9.572
274888KELLY CRK;1U
Solar/Wind Harmer
11.251
276776AD2-060 GEN
Solar/Wind Harmer
0.798
958011AF2-095 GEN
Solar/Wind Harmer
27.456
970941AG2-585 GEN
Solar/Wind Harmer
10.487
276897AD1-100 C
Solar/Wind Harmer
88.066
274674JOLIET 9 ;6U
Adder
29.047
276893AG1-478 C
Solar/Wind Harmer
0.826
270535AF1-215 GEN1
Solar/Wind Harmer
8.484
270536AF1-215 GEN2
Solar/Wind Harmer
8.484
274695ROCKY RD ;2P
Adder
20.555
274693ROCKY RD ;1P
Adder
20.352
274697ROCKY RD ;3P
Adder
5.584
274696ROCKY RD ;4P
Adder
21.039
958481AF2-142 GEN
Solar/Wind Harmer
27.668
274683WAUKEGAN ;8U
Adder
38.781
274683WAUKEGAN ;8U
Adder
32.69
944541AF1-119 GEN
Solar/Wind Harmer
7.702
960971AF2-388 GEN
Solar/Wind Harmer
20.106
962691AG1-118 GEN
Solar/Wind Harmer
54.955
960751AF2-366 GEN
Solar/Wind Harmer
5.241
958491AF2-143 GEN
Solar/Wind Harmer
27.307
276901AD2-066 C O1
Solar/Wind Harmer
6.372
971341AH1-150 GEN
Solar/Wind Harmer
35.811
971343AH1-151 GEN
Solar/Wind Harmer
35.811
276872AE1-163_GEN1
Solar/Wind Harmer
12
276876AE1-163_GEN2
Solar/Wind Harmer
12
972235AH1-702 GEN1
Adder
4.485
972236AH1-702 GEN2
Adder
3.9
274764LEE CO EC;5U
Adder
16.323
274765LEE CO EC;6U
Adder
16.323
274762LEE CO EC;3U
Adder
16.284
274763LEE CO EC;4U
Adder
16.131
247621Y3-024
Adder
0.333
24728805RICHG1
Adder
3.403
24728905RICHG2
Adder
3.403
270349AD2-093_GEN
Solar/Wind Helper
1.732
270471AD2-092_GEN
Solar/Wind Helper
1.732
270054AF2-122 C O1
Solar/Wind Helper
1.194
970819AG2-516 GEN
Solar/Wind Harmer
21.275
970569AG2-363 GEN
Solar/Wind Harmer
52.924
274761LEE CO EC;2U
Adder
16.284
274766LEE CO EC;7U
Adder
16.092
24728605AND G2
Adder
4.689
970091AG2-072 GEN
Adder
74.214
270286AF1-227 GEN2
Solar/Wind Helper
0.844
274777LINCOLN ;8U
Adder
12.135
972037AH1-567 GEN1
Adder
0.349
274827FISK ;RP
Adder
14.81
960591AF2-350 GEN
Solar/Wind Harmer
19.067
274800UNIV PARK;3U
Adder
11.115
274801UNIV PARK;4U
Adder
11.115
972228AH1-698 GEN2
Adder
7.057
972227AH1-698 GEN1
Adder
4.969
274687WILL CNTY;4U
Adder
52.882
274687WILL CNTY;4U
Adder
52.882
274675JOLIET 29;7U
Adder
57.989
274675JOLIET 29;7U
Adder
55.918
274728ELWOOD EC;5P
Adder
30.981
274731ELWOOD EC;2P
Adder
30.981
274733ELWOOD EC;3P
Adder
30.981
274735ELWOOD EC;4P
Adder
30.981
276893AG1-478 C
Solar/Wind Harmer
1.036
970833AG2-524 GEN
Solar/Wind Harmer
16.431
970833AG2-524 GEN
Solar/Wind Harmer
7.642
274744AC1-111 GEN8
Adder
10.45
274746AC1-111 G10
Adder
10.45
958711AF2-162 GEN
Solar/Wind Harmer
1.861
970073AG2-061 GEN
Solar/Wind Harmer
4.234
958391AF2-133 GEN
Solar/Wind Harmer
16.445
971411AH1-196 GEN
Solar/Wind Harmer
27.052
971675AH1-338 GEN
Solar/Wind Harmer
32.46
276861AD2-134 GEN
Solar/Wind Harmer
3.219
276863AD2-134 GEN
Solar/Wind Harmer
3.219
959141AF2-205 GEN
Solar/Wind Harmer
10.874
274863CRW1-WTG
Solar/Wind Harmer
9.998
274864CRW2-WTG
Solar/Wind Harmer
9.998
971549AH1-272 GEN
Solar/Wind Harmer
33.14
971171AH1-044 GEN
Solar/Wind Harmer
35.811
276889AE2-281 GEN
Solar/Wind Harmer
3.429
274823ROCKFORD ;21
Adder
34.758
963791AG1-232 GEN
Solar/Wind Harmer
24.018
274856ECOGROVE ;U1
Solar/Wind Harmer
5.968
276611AD2-172 GEN
Solar/Wind Harmer
4.527
276612AE2-035 GEN
Solar/Wind Harmer
4.527
972267AH1-718 GEN
Adder
7.209
926823AC1-168 GEN
Solar/Wind Harmer
6.628
LAGNLTFEXP_LAGN->PJM
CLTF
13.466
TVALTFEXP_TVA->PJM
CLTF
5.178
NYPJM->LTFIMP_NY
CLTF
3.127
LGEELTFEXP_LGEE->PJM
CLTF
4.428
WECLTFEXP_WEC->PJM
CLTF
6.782
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.711
AG2-052LTFEXP_AG2-052->PJM
LTF
0.426
AH1-155LTFEXP_AH1-155->PJM
LTF
0.638
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
203.496
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.304
MECLTFEXP_MEC->PJM
CLTF
24.589
SIGELTFEXP_SIGE->PJM
CLTF
0.476
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.858

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P7-1_#17567_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#17567_SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5565.17
MW Contribution:
32.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
16.131
270143AC1-141 CT2_
50/50
4.734
24639705ELKHART HY
50/50
0.318
970521AG2-332 GEN
50/50
22.616
24307105BERRINSP G
50/50
0.041
274773LINCOLN ;4U
50/50
12.402
274774LINCOLN ;5U
50/50
12.402
247604X1-042
50/50
0.046
270216AD2-079_GEN
Solar/Wind Harmer
1.19
957891AF2-083 GEN
Solar/Wind Harmer
29.243
945111AF1-176 GEN
Solar/Wind Harmer
34.697
270449AD2-020 GEN
Solar/Wind Harmer
5.42
943021AE2-325 GEN
Solar/Wind Harmer
7.043
24441205WTRV SLR C
Solar/Wind Harmer
0.256
965011AG1-365 GEN
Solar/Wind Harmer
18.878
972207SS24-0001
Solar/Wind Harmer
41.556
274723RIVER EC ;12
Adder
33.394
274751CRETE EC ;1U
Adder
9.095
274754CRETE EC ;4U
Adder
9.095
274812UNIV PK N;8U
Adder
9.261
970373AG2-245 GEN
Solar/Wind Harmer
38.624
274802UNIV PARK;5U
Adder
10.719
941551AE2-152 GEN
Solar/Wind Harmer
8.28
274676JOLIET 29;8U
Adder
55.839
270102X2-052 ST
50/50
3.127
270100X2-052 CT1
50/50
2.889
270101X2-052 CT2
50/50
2.889
24643105BUCHANAN
50/50
0.025
247620Y3-023
50/50
0.948
274770LINCOLN ;1U
50/50
12.402
274771LINCOLN ;2U
50/50
12.402
970349AG2-230 GEN
Solar/Wind Harmer
31.229
965681AG1-436 GEN
Solar/Wind Harmer
24.288
965791AG1-447 GEN
Solar/Wind Harmer
12.427
961051AF2-396 GEN
Solar/Wind Harmer
30.761
961051AF2-396 GEN
Solar/Wind Harmer
14.308
274805UNIV PK N;1U
Adder
9.281
274808UNIV PK N;4U
Adder
9.22
274888KELLY CRK;1U
Solar/Wind Harmer
10.836
276776AD2-060 GEN
Solar/Wind Harmer
0.769
958011AF2-095 GEN
Solar/Wind Harmer
26.442
970941AG2-585 GEN
Solar/Wind Harmer
10.099
276897AD1-100 C
Solar/Wind Harmer
84.806
274674JOLIET 9 ;6U
Adder
27.97
276893AG1-478 C
Solar/Wind Harmer
0.795
270535AF1-215 GEN1
Solar/Wind Harmer
8.178
270536AF1-215 GEN2
Solar/Wind Harmer
8.178
274695ROCKY RD ;2P
Adder
19.787
274693ROCKY RD ;1P
Adder
19.592
274697ROCKY RD ;3P
Adder
5.375
274696ROCKY RD ;4P
Adder
20.253
958481AF2-142 GEN
Solar/Wind Harmer
26.637
274683WAUKEGAN ;8U
Adder
37.331
274683WAUKEGAN ;8U
Adder
31.468
962691AG1-118 GEN
Solar/Wind Harmer
52.897
960751AF2-366 GEN
Solar/Wind Harmer
5.045
958491AF2-143 GEN
Solar/Wind Harmer
26.286
276901AD2-066 C O1
Solar/Wind Harmer
6.134
944541AF1-119 GEN
Solar/Wind Harmer
7.242
960971AF2-388 GEN
Solar/Wind Harmer
18.905
971341AH1-150 GEN
Solar/Wind Harmer
34.462
971343AH1-151 GEN
Solar/Wind Harmer
34.462
276872AE1-163_GEN1
Solar/Wind Harmer
11.549
276876AE1-163_GEN2
Solar/Wind Harmer
11.549
972235AH1-702 GEN1
Adder
4.316
270142AC1-141 CT1_
50/50
4.734
24642205MAYFLWER
50/50
0.072
944961AF1-161 GEN
50/50
5.622
962601AG1-109 GEN
50/50
5.622
274772LINCOLN ;3U
50/50
12.402
971347AH1-153 GEN
Solar/Wind Harmer
10.41
270043AE2-236 GEN
Solar/Wind Harmer
11.231
247643Z2-116 C
Solar/Wind Harmer
0.137
270505AE1-170 C O1
Solar/Wind Harmer
29.293
24441505OLIV SLR
Solar/Wind Harmer
0.26
945111AF1-176 GEN
Solar/Wind Harmer
10.997
270063AE2-323 C
Solar/Wind Harmer
4.272
944531AF1-118 GEN
Solar/Wind Harmer
66.547
965021AG1-366 GEN
Solar/Wind Harmer
4.39
274724RIVER EC ;11
Adder
33.009
972231SS25-0005
Solar/Wind Harmer
17.659
972181SS23-001
Solar/Wind Harmer
11.037
274752CRETE EC ;2U
Adder
9.095
274753CRETE EC ;3U
Adder
9.095
276164X3-005 C
Solar/Wind Harmer
1.303
274814UNIV PK N;0U
Adder
9.342
274807UNIV PK N;3U
Adder
9.322
274811UNIV PK N;7U
Adder
9.261
970707AG2-453 GEN
Solar/Wind Harmer
51.659
274803UNIV PARK;6U
Adder
10.719
274826FISK ;BP
Adder
20.125
972259AH1-714 GEN
Adder
35.044
274887GEN-1.85
Solar/Wind Harmer
9.783
276772AC2-154 GEN
Solar/Wind Harmer
5.124
276843GEN-1.7
Solar/Wind Harmer
1.053
276806AD2-047 C O1
Solar/Wind Harmer
19.643
972038AH1-567 GEN2
Adder
0.67
939351AE1-166 GEN
Solar/Wind Harmer
10.827
274676JOLIET 29;8U
Adder
53.844
274730ELWOOD EC;6P
Adder
29.833
274734ELWOOD EC;8P
Adder
29.833
274736ELWOOD EC;9P
Adder
29.833
274729ELWOOD EC;1P
Adder
29.832
943121AE2-341 GEN
Solar/Wind Harmer
27.053
943591AF1-030 GEN
Solar/Wind Harmer
18.036
274862TOP CROP ;2U
Solar/Wind Harmer
8.977
274682WAUKEGAN ;7U
Adder
31.883
964401AG1-302 GEN
Solar/Wind Harmer
16.016
276868AE1-113 GEN
Solar/Wind Harmer
17.636
274879MINONK ;1U
Solar/Wind Harmer
11.758
276799AD1-013 GEN
Solar/Wind Harmer
3.836
946671AF1-331 GEN
Solar/Wind Harmer
0.727
274855GSG-6 ;RU
Solar/Wind Harmer
6.406
274850MENDOTA H;RU
Solar/Wind Harmer
4.454
276602WESTBROOK C
Solar/Wind Harmer
3.687
959091AF2-200 GEN
Solar/Wind Harmer
34.462
970571AG2-364 GEN
Solar/Wind Harmer
33.953
274760LEE CO EC;1U
Adder
15.666
274767LEE CO EC;8U
Adder
15.482
24728705AND G3
Adder
9.432
24728505AND G1
Adder
4.51
23906402RICHG1
Adder
1.168
23906502RICHG2&3
Adder
1.162
972236AH1-702 GEN2
Adder
3.753
274764LEE CO EC;5U
Adder
15.703
274765LEE CO EC;6U
Adder
15.703
270144AC1-141 ST1_
50/50
4.18
24344005CKG1
50/50
12.73
24641605TWIN BRNCH
50/50
0.034
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
12.402
274776LINCOLN ;7U
50/50
12.402
274777LINCOLN ;8U
50/50
12.402
270071AF1-092 GEN
Solar/Wind Harmer
29.586
971771AH1-392 GEN
Solar/Wind Harmer
17.7
270526AF1-158 GEN
Solar/Wind Harmer
8.843
960681AF2-359 GEN
Solar/Wind Harmer
7.342
970031AG2-029 GEN
Solar/Wind Harmer
48.12
944161AF1-084 GEN
Solar/Wind Harmer
4.251
959331AF2-224 GEN
Solar/Wind Harmer
18.878
24729505KEY G4
Adder
12.039
972037AH1-567 GEN1
Adder
0.336
274827FISK ;RP
Adder
14.263
960591AF2-350 GEN
Solar/Wind Harmer
18.362
274800UNIV PARK;3U
Adder
10.705
274801UNIV PARK;4U
Adder
10.705
972228AH1-698 GEN2
Adder
6.796
972227AH1-698 GEN1
Adder
4.785
274687WILL CNTY;4U
Adder
50.923
274687WILL CNTY;4U
Adder
50.923
274675JOLIET 29;7U
Adder
55.84
274675JOLIET 29;7U
Adder
53.845
274728ELWOOD EC;5P
Adder
29.833
274731ELWOOD EC;2P
Adder
29.832
274733ELWOOD EC;3P
Adder
29.832
274735ELWOOD EC;4P
Adder
29.832
276893AG1-478 C
Solar/Wind Harmer
0.998
970833AG2-524 GEN
Solar/Wind Harmer
15.821
970833AG2-524 GEN
Solar/Wind Harmer
7.359
274744AC1-111 GEN8
Adder
10.061
274746AC1-111 G10
Adder
10.061
971549AH1-272 GEN
Solar/Wind Harmer
32.99
970073AG2-061 GEN
Solar/Wind Harmer
4.075
958391AF2-133 GEN
Solar/Wind Harmer
15.839
971411AH1-196 GEN
Solar/Wind Harmer
26.035
971675AH1-338 GEN
Solar/Wind Harmer
31.239
276861AD2-134 GEN
Solar/Wind Harmer
3.098
276863AD2-134 GEN
Solar/Wind Harmer
3.098
959141AF2-205 GEN
Solar/Wind Harmer
10.471
958711AF2-162 GEN
Solar/Wind Harmer
1.75
274863CRW1-WTG
Solar/Wind Harmer
9.624
274864CRW2-WTG
Solar/Wind Harmer
9.624
971171AH1-044 GEN
Solar/Wind Harmer
34.462
276889AE2-281 GEN
Solar/Wind Harmer
3.3
274823ROCKFORD ;21
Adder
33.447
274856ECOGROVE ;U1
Solar/Wind Harmer
5.742
276611AD2-172 GEN
Solar/Wind Harmer
4.356
276612AE2-035 GEN
Solar/Wind Harmer
4.356
926823AC1-168 GEN
Solar/Wind Harmer
7.296
970169AG2-114 GEN
Solar/Wind Harmer
16.94
965041AG1-368 GEN
Solar/Wind Harmer
16.935
972267AH1-718 GEN
Adder
6.935
963791AG1-232 GEN
Solar/Wind Harmer
6.581
274674JOLIET 9 ;6U
Adder
27.97
274732ELWOOD EC;7P
Adder
29.833
274871GR RIDGE ;2U
Solar/Wind Harmer
13.927
274847GR RIDGE ;BU
Solar/Wind Harmer
9.157
270055AF2-134 C O1
Solar/Wind Harmer
5.452
274745AC1-111 GEN9
Adder
10.061
276694AA1-018 GEN2
Solar/Wind Harmer
11.205
276691AA1-018 GEN1
Solar/Wind Harmer
1.339
274861TOP CROP ;1U
Solar/Wind Harmer
10.751
274682WAUKEGAN ;7U
Adder
31.883
274828WAUKEGAN ;BP
Adder
19.568
958381AF2-132 GEN
Solar/Wind Harmer
16.016
964861AG1-349 GEN
Solar/Wind Harmer
13.849
971917AH1-482 GEN
Solar/Wind Harmer
15.978
962781AG1-127 GEN
Solar/Wind Harmer
16.722
274872LEEDK;1U
Solar/Wind Harmer
14.399
939401AE1-172 GEN
Solar/Wind Harmer
24.438
276805AD2-038 GEN
Solar/Wind Harmer
8.986
276882AE2-255 GEN
Solar/Wind Harmer
5.879
971997AH1-543 GEN
Solar/Wind Harmer
27.396
965651AG1-433 GEN
Solar/Wind Harmer
9.453
957471AF2-041 GEN
Solar/Wind Harmer
51.692
959081AF2-199 GEN
Solar/Wind Harmer
17.231
971067AG2-660 GEN
Solar/Wind Harmer
4.007
274822ROCKFORD ;11
Adder
33.691
940581AE2-045 GEN
Solar/Wind Harmer
17.476
971605AH1-302 GEN
Solar/Wind Harmer
14.942
970819AG2-516 GEN
Solar/Wind Harmer
20.47
970569AG2-363 GEN
Solar/Wind Harmer
50.929
274761LEE CO EC;2U
Adder
15.666
274766LEE CO EC;7U
Adder
15.482
24728605AND G2
Adder
4.51
23906502RICHG2&3
Adder
1.162
970091AG2-072 GEN
Adder
70.904
274762LEE CO EC;3U
Adder
15.666
274763LEE CO EC;4U
Adder
15.519
247621Y3-024
Adder
0.321
24728805RICHG1
Adder
3.401
24728905RICHG2
Adder
3.401
270349AD2-093_GEN
Solar/Wind Helper
2.217
270471AD2-092_GEN
Solar/Wind Helper
2.217
270054AF2-122 C O1
Solar/Wind Helper
1.301
LAGNLTFEXP_LAGN->PJM
CLTF
12.607
TVALTFEXP_TVA->PJM
CLTF
4.786
NYPJM->LTFIMP_NY
CLTF
3.126
LGEELTFEXP_LGEE->PJM
CLTF
4.296
WECLTFEXP_WEC->PJM
CLTF
6.526
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.933
AG2-052LTFEXP_AG2-052->PJM
LTF
0.41
AH1-155LTFEXP_AH1-155->PJM
LTF
0.615
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.368
CBM West 1LTFEXP_CBM-W1->PJM
CBM
204.826
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.965
MECLTFEXP_MEC->PJM
CLTF
23.595
SIGELTFEXP_SIGE->PJM
CLTF
0.458
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.861

Details for 05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.98 %
Rating:6066.0 MVA
Rating Type:B
MVA to Mitigate:6125.38
MW Contribution:
34.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.355
270100X2-052 CT1
50/50
3.1
270101X2-052 CT2
50/50
3.1
24643105BUCHANAN
50/50
0.026
274770LINCOLN ;1U
50/50
13.44
274771LINCOLN ;2U
50/50
13.44
247620Y3-023
50/50
0.991
970349AG2-230 GEN
Solar/Wind Harmer
33.323
965681AG1-436 GEN
Solar/Wind Harmer
26.089
965791AG1-447 GEN
Solar/Wind Harmer
13.348
961051AF2-396 GEN
Solar/Wind Harmer
32.427
270142AC1-141 CT1_
50/50
5.002
24642205MAYFLWER
50/50
0.076
274772LINCOLN ;3U
50/50
13.44
944961AF1-161 GEN
50/50
5.928
962601AG1-109 GEN
50/50
5.928
971347AH1-153 GEN
Solar/Wind Harmer
11.108
270043AE2-236 GEN
Solar/Wind Harmer
11.544
247643Z2-116 C
Solar/Wind Harmer
0.145
24441505OLIV SLR
Solar/Wind Harmer
0.278
270505AE1-170 C O1
Solar/Wind Harmer
30.925
945111AF1-176 GEN
Solar/Wind Harmer
11.586
274724RIVER EC ;11
Adder
35.711
972231SS25-0005
Solar/Wind Harmer
19.1
972181SS23-001
Solar/Wind Harmer
11.937
274752CRETE EC ;2U
Adder
9.837
274753CRETE EC ;3U
Adder
9.837
276164X3-005 C
Solar/Wind Harmer
1.411
270063AE2-323 C
Solar/Wind Harmer
4.403
274814UNIV PK N;0U
Adder
10.117
274807UNIV PK N;3U
Adder
10.095
274811UNIV PK N;7U
Adder
10.03
970707AG2-453 GEN
Solar/Wind Harmer
56.064
972259AH1-714 GEN
Adder
38.042
274803UNIV PARK;6U
Adder
11.623
274826FISK ;BP
Adder
21.822
274887GEN-1.85
Solar/Wind Harmer
10.615
276772AC2-154 GEN
Solar/Wind Harmer
5.56
276843GEN-1.7
Solar/Wind Harmer
1.142
276806AD2-047 C O1
Solar/Wind Harmer
21.313
972038AH1-567 GEN2
Adder
0.727
939351AE1-166 GEN
Solar/Wind Harmer
11.767
944531AF1-118 GEN
Solar/Wind Harmer
69.202
274676JOLIET 29;8U
Adder
58.463
274729ELWOOD EC;1P
Adder
32.41
274730ELWOOD EC;6P
Adder
32.411
274734ELWOOD EC;8P
Adder
32.411
274736ELWOOD EC;9P
Adder
32.411
943121AE2-341 GEN
Solar/Wind Harmer
29.406
943591AF1-030 GEN
Solar/Wind Harmer
19.604
964401AG1-302 GEN
Solar/Wind Harmer
17.685
274862TOP CROP ;2U
Solar/Wind Harmer
9.773
274682WAUKEGAN ;7U
Adder
34.688
276868AE1-113 GEN
Solar/Wind Harmer
19.24
274879MINONK ;1U
Solar/Wind Harmer
12.827
276799AD1-013 GEN
Solar/Wind Harmer
4.182
946671AF1-331 GEN
Solar/Wind Harmer
0.792
274855GSG-6 ;RU
Solar/Wind Harmer
6.983
274850MENDOTA H;RU
Solar/Wind Harmer
4.855
276602WESTBROOK C
Solar/Wind Harmer
4.02
959091AF2-200 GEN
Solar/Wind Harmer
37.588
970571AG2-364 GEN
Solar/Wind Harmer
37.151
274857EASY ROAD;U1
Solar/Wind Harmer
8.815
274760LEE CO EC;1U
Adder
17.118
274767LEE CO EC;8U
Adder
16.916
24728705AND G3
Adder
10.665
24728505AND G1
Adder
5.1
24690905MDL-1G C
Solar/Wind Harmer
9.079
24344005CKG1
50/50
13.488
270144AC1-141 ST1_
50/50
4.417
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
13.44
274776LINCOLN ;7U
50/50
13.44
274777LINCOLN ;8U
50/50
13.44
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
7.886
971771AH1-392 GEN
Solar/Wind Harmer
18.775
270526AF1-158 GEN
Solar/Wind Harmer
9.429
270071AF1-092 GEN
Solar/Wind Harmer
30.976
944161AF1-084 GEN
Solar/Wind Harmer
4.48
972037AH1-567 GEN1
Adder
0.365
274827FISK ;RP
Adder
15.465
24344105CKG2
50/50
17.244
270143AC1-141 CT2_
50/50
5.002
24639705ELKHART HY
50/50
0.334
274773LINCOLN ;4U
50/50
13.44
274774LINCOLN ;5U
50/50
13.44
970521AG2-332 GEN
50/50
23.718
24307105BERRINSP G
50/50
0.044
270216AD2-079_GEN
Solar/Wind Harmer
1.255
957891AF2-083 GEN
Solar/Wind Harmer
30.868
945111AF1-176 GEN
Solar/Wind Harmer
36.559
972207SS24-0001
Solar/Wind Harmer
45.031
270449AD2-020 GEN
Solar/Wind Harmer
5.715
943021AE2-325 GEN
Solar/Wind Harmer
7.427
274723RIVER EC ;12
Adder
36.127
274751CRETE EC ;1U
Adder
9.837
274754CRETE EC ;4U
Adder
9.837
970373AG2-245 GEN
Solar/Wind Harmer
42.152
274812UNIV PK N;8U
Adder
10.03
24441205WTRV SLR C
Solar/Wind Harmer
0.27
274802UNIV PARK;5U
Adder
11.623
941551AE2-152 GEN
Solar/Wind Harmer
8.999
270055AF2-134 C O1
Solar/Wind Harmer
5.984
274676JOLIET 29;8U
Adder
60.628
274674JOLIET 9 ;6U
Adder
30.381
274732ELWOOD EC;7P
Adder
32.411
274871GR RIDGE ;2U
Solar/Wind Harmer
15.14
274847GR RIDGE ;BU
Solar/Wind Harmer
9.956
274745AC1-111 GEN9
Adder
10.938
958381AF2-132 GEN
Solar/Wind Harmer
17.685
964861AG1-349 GEN
Solar/Wind Harmer
15.303
971917AH1-482 GEN
Solar/Wind Harmer
17.655
276694AA1-018 GEN2
Solar/Wind Harmer
12.198
276691AA1-018 GEN1
Solar/Wind Harmer
1.458
274861TOP CROP ;1U
Solar/Wind Harmer
11.705
274682WAUKEGAN ;7U
Adder
34.688
274828WAUKEGAN ;BP
Adder
21.291
939401AE1-172 GEN
Solar/Wind Harmer
26.719
962781AG1-127 GEN
Solar/Wind Harmer
18.21
274872LEEDK;1U
Solar/Wind Harmer
15.683
276805AD2-038 GEN
Solar/Wind Harmer
9.797
940581AE2-045 GEN
Solar/Wind Harmer
19.469
971605AH1-302 GEN
Solar/Wind Harmer
16.647
276882AE2-255 GEN
Solar/Wind Harmer
6.414
971997AH1-543 GEN
Solar/Wind Harmer
29.912
957471AF2-041 GEN
Solar/Wind Harmer
56.382
959081AF2-199 GEN
Solar/Wind Harmer
18.794
971067AG2-660 GEN
Solar/Wind Harmer
4.371
274822ROCKFORD ;11
Adder
36.75
970819AG2-516 GEN
Solar/Wind Harmer
22.34
970569AG2-363 GEN
Solar/Wind Harmer
55.727
274858EASY ROAD;U2
Solar/Wind Harmer
8.815
274761LEE CO EC;2U
Adder
17.118
274766LEE CO EC;7U
Adder
16.916
970091AG2-072 GEN
Adder
105.385
24728605AND G2
Adder
5.1
961051AF2-396 GEN
Solar/Wind Harmer
15.082
274805UNIV PK N;1U
Adder
10.052
274808UNIV PK N;4U
Adder
9.986
274888KELLY CRK;1U
Solar/Wind Harmer
11.757
276776AD2-060 GEN
Solar/Wind Harmer
0.834
960591AF2-350 GEN
Solar/Wind Harmer
19.923
972228AH1-698 GEN2
Adder
7.377
972227AH1-698 GEN1
Adder
5.194
274800UNIV PARK;3U
Adder
11.611
274801UNIV PARK;4U
Adder
11.611
274687WILL CNTY;4U
Adder
55.279
274687WILL CNTY;4U
Adder
55.279
274675JOLIET 29;7U
Adder
60.629
274675JOLIET 29;7U
Adder
58.463
970031AG2-029 GEN
Solar/Wind Harmer
49.365
274728ELWOOD EC;5P
Adder
32.411
274731ELWOOD EC;2P
Adder
32.41
274733ELWOOD EC;3P
Adder
32.41
274735ELWOOD EC;4P
Adder
32.41
276893AG1-478 C
Solar/Wind Harmer
1.084
970833AG2-524 GEN
Solar/Wind Harmer
17.199
970833AG2-524 GEN
Solar/Wind Harmer
7.999
274744AC1-111 GEN8
Adder
10.938
274746AC1-111 G10
Adder
10.938
958391AF2-133 GEN
Solar/Wind Harmer
17.547
24729505KEY G4
Adder
12.548
959141AF2-205 GEN
Solar/Wind Harmer
11.629
970073AG2-061 GEN
Solar/Wind Harmer
4.443
971675AH1-338 GEN
Solar/Wind Harmer
34.055
971411AH1-196 GEN
Solar/Wind Harmer
28.375
276861AD2-134 GEN
Solar/Wind Harmer
3.377
276863AD2-134 GEN
Solar/Wind Harmer
3.377
274863CRW1-WTG
Solar/Wind Harmer
10.548
274864CRW2-WTG
Solar/Wind Harmer
10.548
971171AH1-044 GEN
Solar/Wind Harmer
37.588
276889AE2-281 GEN
Solar/Wind Harmer
3.605
274823ROCKFORD ;21
Adder
36.484
970169AG2-114 GEN
Solar/Wind Harmer
18.611
274856ECOGROVE ;U1
Solar/Wind Harmer
6.268
276611AD2-172 GEN
Solar/Wind Harmer
4.755
276612AE2-035 GEN
Solar/Wind Harmer
4.755
926823AC1-168 GEN
Solar/Wind Harmer
7.988
971549AH1-272 GEN
Solar/Wind Harmer
34.293
971681AH1-341 GEN
Solar/Wind Harmer
27.72
972267AH1-718 GEN
Adder
7.584
958011AF2-095 GEN
Solar/Wind Harmer
28.69
970941AG2-585 GEN
Solar/Wind Harmer
10.958
276897AD1-100 C
Solar/Wind Harmer
92.171
270535AF1-215 GEN1
Solar/Wind Harmer
8.976
270536AF1-215 GEN2
Solar/Wind Harmer
8.976
274674JOLIET 9 ;6U
Adder
30.381
276893AG1-478 C
Solar/Wind Harmer
0.864
274695ROCKY RD ;2P
Adder
21.528
274693ROCKY RD ;1P
Adder
21.316
274697ROCKY RD ;3P
Adder
5.848
274696ROCKY RD ;4P
Adder
22.036
958481AF2-142 GEN
Solar/Wind Harmer
28.999
274683WAUKEGAN ;8U
Adder
40.618
274683WAUKEGAN ;8U
Adder
34.239
962691AG1-118 GEN
Solar/Wind Harmer
57.593
960751AF2-366 GEN
Solar/Wind Harmer
5.494
958491AF2-143 GEN
Solar/Wind Harmer
28.659
276901AD2-066 C O1
Solar/Wind Harmer
6.693
971341AH1-150 GEN
Solar/Wind Harmer
37.588
971343AH1-151 GEN
Solar/Wind Harmer
37.588
276872AE1-163_GEN1
Solar/Wind Harmer
12.619
276876AE1-163_GEN2
Solar/Wind Harmer
12.619
945421AF1-207 GEN
Solar/Wind Harmer
26.261
957841AF2-078 GEN
Solar/Wind Harmer
11.305
972235AH1-702 GEN1
Adder
4.708
972236AH1-702 GEN2
Adder
4.094
938861AE1-114 GEN
Solar/Wind Harmer
15.142
274764LEE CO EC;5U
Adder
17.158
274765LEE CO EC;6U
Adder
17.158
274762LEE CO EC;3U
Adder
17.118
274763LEE CO EC;4U
Adder
16.956
247621Y3-024
Adder
0.337
24728805RICHG1
Adder
3.728
24728905RICHG2
Adder
3.728
270349AD2-093_GEN
Solar/Wind Helper
1.56
270471AD2-092_GEN
Solar/Wind Helper
1.56
LAGNLTFEXP_LAGN->PJM
CLTF
14.187
TVALTFEXP_TVA->PJM
CLTF
5.423
NYPJM->LTFIMP_NY
CLTF
3.401
LGEELTFEXP_LGEE->PJM
CLTF
5.607
WECLTFEXP_WEC->PJM
CLTF
7.118
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.195
AG2-052LTFEXP_AG2-052->PJM
LTF
0.448
AH1-155LTFEXP_AH1-155->PJM
LTF
0.672
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.218
MECLTFEXP_MEC->PJM
CLTF
26.088
SIGELTFEXP_SIGE->PJM
CLTF
0.553
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.543

Details for 05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.82 %
Rating:6066.0 MVA
Rating Type:B
MVA to Mitigate:6115.5
MW Contribution:
36.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.376
24642205MAYFLWER
50/50
0.082
944961AF1-161 GEN
50/50
6.372
962601AG1-109 GEN
50/50
6.372
274772LINCOLN ;3U
50/50
14.328
971347AH1-153 GEN
Solar/Wind Harmer
11.95
24441505OLIV SLR
Solar/Wind Harmer
0.299
247643Z2-116 C
Solar/Wind Harmer
0.155
270043AE2-236 GEN
Solar/Wind Harmer
12.195
270505AE1-170 C O1
Solar/Wind Harmer
33.236
945111AF1-176 GEN
Solar/Wind Harmer
12.446
274724RIVER EC ;11
Adder
38.104
972231SS25-0005
Solar/Wind Harmer
20.399
972181SS23-001
Solar/Wind Harmer
12.75
274752CRETE EC ;2U
Adder
10.506
274753CRETE EC ;3U
Adder
10.506
276164X3-005 C
Solar/Wind Harmer
1.504
270063AE2-323 C
Solar/Wind Harmer
4.695
274814UNIV PK N;0U
Adder
10.79
274807UNIV PK N;3U
Adder
10.767
274811UNIV PK N;7U
Adder
10.696
970707AG2-453 GEN
Solar/Wind Harmer
59.66
964401AG1-302 GEN
Solar/Wind Harmer
19.303
274803UNIV PARK;6U
Adder
12.378
274826FISK ;BP
Adder
23.237
972259AH1-714 GEN
Adder
40.472
274887GEN-1.85
Solar/Wind Harmer
11.297
276772AC2-154 GEN
Solar/Wind Harmer
5.917
276843GEN-1.7
Solar/Wind Harmer
1.216
276806AD2-047 C O1
Solar/Wind Harmer
22.684
972038AH1-567 GEN2
Adder
0.774
939351AE1-166 GEN
Solar/Wind Harmer
12.505
274676JOLIET 29;8U
Adder
62.168
274730ELWOOD EC;6P
Adder
34.447
274734ELWOOD EC;8P
Adder
34.447
274736ELWOOD EC;9P
Adder
34.447
274729ELWOOD EC;1P
Adder
34.446
943121AE2-341 GEN
Solar/Wind Harmer
31.23
943591AF1-030 GEN
Solar/Wind Harmer
20.82
274862TOP CROP ;2U
Solar/Wind Harmer
10.361
274682WAUKEGAN ;7U
Adder
36.793
944531AF1-118 GEN
Solar/Wind Harmer
71.497
276868AE1-113 GEN
Solar/Wind Harmer
20.352
274879MINONK ;1U
Solar/Wind Harmer
13.569
24690905MDL-1G C
Solar/Wind Harmer
16.141
970781AG2-491 GEN
Solar/Wind Harmer
20.107
276799AD1-013 GEN
Solar/Wind Harmer
4.425
946671AF1-331 GEN
Solar/Wind Harmer
0.838
274855GSG-6 ;RU
Solar/Wind Harmer
7.389
274850MENDOTA H;RU
Solar/Wind Harmer
5.137
276602WESTBROOK C
Solar/Wind Harmer
4.254
959091AF2-200 GEN
Solar/Wind Harmer
39.747
274760LEE CO EC;1U
Adder
18.06
274767LEE CO EC;8U
Adder
17.848
24728705AND G3
Adder
10.678
24728505AND G1
Adder
5.106
970571AG2-364 GEN
Solar/Wind Harmer
36.857
24344005CKG1
50/50
14.521
270144AC1-141 ST1_
50/50
4.747
24641605TWIN BRNCH
50/50
0.038
24653605MOTTVILLE
50/50
0.008
274775LINCOLN ;6U
50/50
14.328
274776LINCOLN ;7U
50/50
14.328
274777LINCOLN ;8U
50/50
14.328
960681AF2-359 GEN
Solar/Wind Harmer
8.491
971771AH1-392 GEN
Solar/Wind Harmer
20.176
270526AF1-158 GEN
Solar/Wind Harmer
10.14
270071AF1-092 GEN
Solar/Wind Harmer
33.089
944161AF1-084 GEN
Solar/Wind Harmer
4.817
972037AH1-567 GEN1
Adder
0.389
274827FISK ;RP
Adder
16.469
960591AF2-350 GEN
Solar/Wind Harmer
21.204
274800UNIV PARK;3U
Adder
12.36
274801UNIV PARK;4U
Adder
12.36
972228AH1-698 GEN2
Adder
7.849
972227AH1-698 GEN1
Adder
5.527
958391AF2-133 GEN
Solar/Wind Harmer
19.179
959141AF2-205 GEN
Solar/Wind Harmer
12.724
274687WILL CNTY;4U
Adder
58.796
274687WILL CNTY;4U
Adder
58.796
970031AG2-029 GEN
Solar/Wind Harmer
52.55
274675JOLIET 29;7U
Adder
64.472
274675JOLIET 29;7U
Adder
62.169
274728ELWOOD EC;5P
Adder
34.447
274731ELWOOD EC;2P
Adder
34.446
274733ELWOOD EC;3P
Adder
34.446
274735ELWOOD EC;4P
Adder
34.446
276893AG1-478 C
Solar/Wind Harmer
1.152
970833AG2-524 GEN
Solar/Wind Harmer
18.269
970833AG2-524 GEN
Solar/Wind Harmer
8.497
274744AC1-111 GEN8
Adder
11.614
274746AC1-111 G10
Adder
11.614
970073AG2-061 GEN
Solar/Wind Harmer
4.703
946581AF1-322 GEN
Solar/Wind Harmer
20.573
24691005MDL-2G C
Solar/Wind Harmer
7.435
971411AH1-196 GEN
Solar/Wind Harmer
30.031
971675AH1-338 GEN
Solar/Wind Harmer
36.035
276861AD2-134 GEN
Solar/Wind Harmer
3.573
276863AD2-134 GEN
Solar/Wind Harmer
3.573
24729505KEY G4
Adder
12.942
971549AH1-272 GEN
Solar/Wind Harmer
36.893
274863CRW1-WTG
Solar/Wind Harmer
11.117
274864CRW2-WTG
Solar/Wind Harmer
11.117
971171AH1-044 GEN
Solar/Wind Harmer
39.747
276889AE2-281 GEN
Solar/Wind Harmer
3.808
274823ROCKFORD ;21
Adder
38.572
274856ECOGROVE ;U1
Solar/Wind Harmer
6.621
276611AD2-172 GEN
Solar/Wind Harmer
5.023
276612AE2-035 GEN
Solar/Wind Harmer
5.023
926823AC1-168 GEN
Solar/Wind Harmer
8.419
972267AH1-718 GEN
Adder
7.992
270102X2-052 ST
50/50
3.615
270100X2-052 CT1
50/50
3.34
270101X2-052 CT2
50/50
3.34
24643105BUCHANAN
50/50
0.028
274770LINCOLN ;1U
50/50
14.328
274771LINCOLN ;2U
50/50
14.328
247620Y3-023
50/50
1.061
970349AG2-230 GEN
Solar/Wind Harmer
35.85
965681AG1-436 GEN
Solar/Wind Harmer
28.089
965791AG1-447 GEN
Solar/Wind Harmer
14.371
961051AF2-396 GEN
Solar/Wind Harmer
34.847
961051AF2-396 GEN
Solar/Wind Harmer
16.208
270535AF1-215 GEN1
Solar/Wind Harmer
9.77
270536AF1-215 GEN2
Solar/Wind Harmer
9.77
274805UNIV PK N;1U
Adder
10.72
274808UNIV PK N;4U
Adder
10.65
274888KELLY CRK;1U
Solar/Wind Harmer
12.513
276776AD2-060 GEN
Solar/Wind Harmer
0.888
958011AF2-095 GEN
Solar/Wind Harmer
30.534
970941AG2-585 GEN
Solar/Wind Harmer
11.662
276897AD1-100 C
Solar/Wind Harmer
97.952
274674JOLIET 9 ;6U
Adder
32.294
276893AG1-478 C
Solar/Wind Harmer
0.918
945421AF1-207 GEN
Solar/Wind Harmer
28.884
957841AF2-078 GEN
Solar/Wind Harmer
12.434
274695ROCKY RD ;2P
Adder
22.835
274693ROCKY RD ;1P
Adder
22.61
274697ROCKY RD ;3P
Adder
6.203
274696ROCKY RD ;4P
Adder
23.374
958481AF2-142 GEN
Solar/Wind Harmer
30.747
274683WAUKEGAN ;8U
Adder
43.078
274683WAUKEGAN ;8U
Adder
36.313
962691AG1-118 GEN
Solar/Wind Harmer
61.037
960751AF2-366 GEN
Solar/Wind Harmer
5.821
958491AF2-143 GEN
Solar/Wind Harmer
30.337
276901AD2-066 C O1
Solar/Wind Harmer
7.081
270180AB1-006 GEN1
Solar/Wind Harmer
14.461
24697605MDL-3G C
Solar/Wind Harmer
7.411
24755605MDL-5G
Solar/Wind Harmer
4.847
24697905MDL-4G C
Solar/Wind Harmer
4.614
270181AB1-006 GEN2
Solar/Wind Harmer
1.438
971341AH1-150 GEN
Solar/Wind Harmer
39.747
971343AH1-151 GEN
Solar/Wind Harmer
39.747
276872AE1-163_GEN1
Solar/Wind Harmer
13.326
276876AE1-163_GEN2
Solar/Wind Harmer
13.326
972235AH1-702 GEN1
Adder
4.977
972236AH1-702 GEN2
Adder
4.327
274764LEE CO EC;5U
Adder
18.103
274765LEE CO EC;6U
Adder
18.103
274762LEE CO EC;3U
Adder
18.06
274763LEE CO EC;4U
Adder
17.89
247621Y3-024
Adder
0.343
24728805RICHG1
Adder
3.596
24728905RICHG2
Adder
3.596
270349AD2-093_GEN
Solar/Wind Helper
1.535
270471AD2-092_GEN
Solar/Wind Helper
1.535
24344105CKG2
50/50
18.6
270143AC1-141 CT2_
50/50
5.376
24639705ELKHART HY
50/50
0.358
970521AG2-332 GEN
50/50
25.433
24307105BERRINSP G
50/50
0.047
274773LINCOLN ;4U
50/50
14.328
274774LINCOLN ;5U
50/50
14.328
270216AD2-079_GEN
Solar/Wind Harmer
1.347
957891AF2-083 GEN
Solar/Wind Harmer
33.17
945111AF1-176 GEN
Solar/Wind Harmer
39.271
270449AD2-020 GEN
Solar/Wind Harmer
6.143
943021AE2-325 GEN
Solar/Wind Harmer
7.983
970373AG2-245 GEN
Solar/Wind Harmer
45.77
972207SS24-0001
Solar/Wind Harmer
48.008
270055AF2-134 C O1
Solar/Wind Harmer
6.513
24441205WTRV SLR C
Solar/Wind Harmer
0.29
274723RIVER EC ;12
Adder
38.551
274751CRETE EC ;1U
Adder
10.506
274754CRETE EC ;4U
Adder
10.506
274812UNIV PK N;8U
Adder
10.696
958381AF2-132 GEN
Solar/Wind Harmer
19.303
964861AG1-349 GEN
Solar/Wind Harmer
16.707
971917AH1-482 GEN
Solar/Wind Harmer
19.276
274802UNIV PARK;5U
Adder
12.378
941551AE2-152 GEN
Solar/Wind Harmer
9.563
274676JOLIET 29;8U
Adder
64.471
274674JOLIET 9 ;6U
Adder
32.294
274732ELWOOD EC;7P
Adder
34.447
274871GR RIDGE ;2U
Solar/Wind Harmer
16.081
274847GR RIDGE ;BU
Solar/Wind Harmer
10.574
940581AE2-045 GEN
Solar/Wind Harmer
21.331
971605AH1-302 GEN
Solar/Wind Harmer
18.239
274745AC1-111 GEN9
Adder
11.614
276694AA1-018 GEN2
Solar/Wind Harmer
12.934
276691AA1-018 GEN1
Solar/Wind Harmer
1.546
274861TOP CROP ;1U
Solar/Wind Harmer
12.41
274682WAUKEGAN ;7U
Adder
36.793
274828WAUKEGAN ;BP
Adder
22.581
962781AG1-127 GEN
Solar/Wind Harmer
19.295
939401AE1-172 GEN
Solar/Wind Harmer
28.229
274872LEEDK;1U
Solar/Wind Harmer
16.613
276805AD2-038 GEN
Solar/Wind Harmer
10.371
276882AE2-255 GEN
Solar/Wind Harmer
6.784
24791305MDL-5G
Solar/Wind Harmer
4.847
971997AH1-543 GEN
Solar/Wind Harmer
31.619
957471AF2-041 GEN
Solar/Wind Harmer
59.62
959081AF2-199 GEN
Solar/Wind Harmer
19.873
971067AG2-660 GEN
Solar/Wind Harmer
4.622
274822ROCKFORD ;11
Adder
38.853
970819AG2-516 GEN
Solar/Wind Harmer
23.604
274761LEE CO EC;2U
Adder
18.06
274766LEE CO EC;7U
Adder
17.848
24728605AND G2
Adder
5.106
970091AG2-072 GEN
Adder
76.464
970569AG2-363 GEN
Solar/Wind Harmer
55.286
LAGNLTFEXP_LAGN->PJM
CLTF
13.81
TVALTFEXP_TVA->PJM
CLTF
5.072
NYPJM->LTFIMP_NY
CLTF
3.41
LGEELTFEXP_LGEE->PJM
CLTF
4.521
WECLTFEXP_WEC->PJM
CLTF
7.524
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.341
AG2-052LTFEXP_AG2-052->PJM
LTF
0.477
AH1-155LTFEXP_AH1-155->PJM
LTF
0.716
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
229.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.07
MECLTFEXP_MEC->PJM
CLTF
27.061
SIGELTFEXP_SIGE->PJM
CLTF
0.509
CBM West 2LTFEXP_CBM-W2->PJM
CBM
128.929

Details for 05TWIN B-05MERIDN 345.0 kV Ckt 1 line l/o AEP_P4_#7442_05SORENS 765_K2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05TWIN B-05MERIDN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7442_05SORENS 765_K2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.24 %
Rating:897.0 MVA
Rating Type:B
MVA to Mitigate:899.13
MW Contribution:
11.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247643Z2-116 C
Solar/Wind Harmer
0.045
971347AH1-153 GEN
Solar/Wind Harmer
3.153
270505AE1-170 C O1
Solar/Wind Harmer
9.393
945111AF1-176 GEN
Solar/Wind Harmer
3.274
24441505OLIV SLR
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
7.811
972231SS25-0005
Solar/Wind Harmer
4.183
972181SS23-001
Solar/Wind Harmer
2.614
274752CRETE EC ;2U
Adder
2.154
274753CRETE EC ;3U
Adder
2.154
276164X3-005 C
Solar/Wind Harmer
0.305
274814UNIV PK N;0U
Adder
2.185
274807UNIV PK N;3U
Adder
2.18
274811UNIV PK N;7U
Adder
2.166
274772LINCOLN ;3U
Adder
2.675
274676JOLIET 29;8U
Adder
12.312
274729ELWOOD EC;1P
Adder
6.8
274730ELWOOD EC;6P
Adder
6.8
274734ELWOOD EC;8P
Adder
6.8
274736ELWOOD EC;9P
Adder
6.8
959091AF2-200 GEN
Solar/Wind Harmer
7.641
970349AG2-230 GEN
Solar/Wind Harmer
9.459
961051AF2-396 GEN
Solar/Wind Harmer
9.357
961051AF2-396 GEN
Solar/Wind Harmer
4.352
965681AG1-436 GEN
Solar/Wind Harmer
6.639
965791AG1-447 GEN
Solar/Wind Harmer
3.397
247620Y3-023
Adder
0.207
274805UNIV PK N;1U
Adder
2.171
274808UNIV PK N;4U
Adder
2.157
274770LINCOLN ;1U
Adder
2.675
274771LINCOLN ;2U
Adder
2.675
971341AH1-150 GEN
Solar/Wind Harmer
7.641
971343AH1-151 GEN
Solar/Wind Harmer
7.641
944541AF1-119 GEN
Solar/Wind Helper
1.953
971771AH1-392 GEN
Solar/Wind Harmer
5.868
971549AH1-272 GEN
Solar/Wind Harmer
11.687
944161AF1-084 GEN
Solar/Wind Harmer
1.295
270526AF1-158 GEN
Solar/Wind Harmer
2.648
960681AF2-359 GEN
Solar/Wind Harmer
2.007
274775LINCOLN ;6U
Adder
2.675
274776LINCOLN ;7U
Adder
2.675
274777LINCOLN ;8U
Adder
2.675
274675JOLIET 29;7U
Adder
12.769
274675JOLIET 29;7U
Adder
12.313
274728ELWOOD EC;5P
Adder
6.8
270216AD2-079_GEN
Solar/Wind Harmer
0.384
957891AF2-083 GEN
Solar/Wind Harmer
9.145
270449AD2-020 GEN
Solar/Wind Harmer
1.67
943021AE2-325 GEN
Solar/Wind Harmer
2.17
945111AF1-176 GEN
Solar/Wind Harmer
10.331
24441205WTRV SLR C
Solar/Wind Harmer
0.077
24639705ELKHART HY
Adder
0.081
970373AG2-245 GEN
Solar/Wind Harmer
9.51
274751CRETE EC ;1U
Adder
2.154
274754CRETE EC ;4U
Adder
2.154
274723RIVER EC ;12
Adder
7.89
274812UNIV PK N;8U
Adder
2.166
972207SS24-0001
Solar/Wind Harmer
9.511
274773LINCOLN ;4U
Adder
2.675
274774LINCOLN ;5U
Adder
2.675
274676JOLIET 29;8U
Adder
12.768
274732ELWOOD EC;7P
Adder
6.8
957471AF2-041 GEN
Solar/Wind Harmer
11.461
959081AF2-199 GEN
Solar/Wind Harmer
3.82
971067AG2-660 GEN
Solar/Wind Harmer
0.888
274731ELWOOD EC;2P
Adder
6.8
274733ELWOOD EC;3P
Adder
6.8
274735ELWOOD EC;4P
Adder
6.8
971171AH1-044 GEN
Solar/Wind Harmer
7.641
958711AF2-162 GEN
Solar/Wind Helper
0.409
LAGNLTFEXP_LAGN->PJM
CLTF
1.774
TVALTFEXP_TVA->PJM
CLTF
0.499
NYPJM->LTFIMP_NY
CLTF
0.533
LGEELTFEXP_LGEE->PJM
CLTF
0.029
WECLTFEXP_WEC->PJM
CLTF
1.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.241
AG2-052LTFEXP_AG2-052->PJM
LTF
0.093
AH1-155LTFEXP_AH1-155->PJM
LTF
0.14
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.529
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.565
MECLTFEXP_MEC->PJM
CLTF
4.764
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.763

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2185.8
MW Contribution:
6.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.156
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
971985AH1-537 GEN
Solar/Wind Harmer
5.763
25196408WSDLE3
Adder
9.057
25196308WSDLE2
Adder
8.978
25196208WSDLE1
Adder
8.956
25196708WSDLE6
Adder
8.933
25196508WSDLE4
Adder
8.708
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.401
972163AH1-664 GEN
Solar/Wind Harmer
7.027
972165AH1-665 GEN
Solar/Wind Harmer
5.628
253406AD2-031_GEN
Solar/Wind Harmer
0.458
339216AC1-074 GEN
Solar/Wind Harmer
0.162
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.58
253372AE2-315 SEC3
Adder
1.514
253372AE2-315 SEC3
Adder
1.514
25306009OHH W.
Adder
2.27
270356AE2-297 GEN
Solar/Wind Harmer
0
3429211JKCT 2G
Adder
8.721
971029AG2-637 GEN
Solar/Wind Harmer
7.57
270543AE2-219 C
Solar/Wind Harmer
3.433
247536S-71 GEN
Solar/Wind Harmer
0.191
964611AG1-324 GEN
Solar/Wind Harmer
1.811
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.738
270432AC2-029 GEN
Solar/Wind Harmer
2.001
241972AD1-140 GEN
Solar/Wind Harmer
0.484
970289AG2-191 GEN
Solar/Wind Harmer
0.834
24729505KEY G4
Adder
3.899
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.68
24386405FR-21G C
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.053
270071AF1-092 GEN
Solar/Wind Harmer
7.11
971611AH1-305 GEN
Solar/Wind Harmer
2.204
959141AF2-205 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.16
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.144
276848AB2-070 GEN3
Solar/Wind Harmer
0.143
276849AB2-070 GEN2
Solar/Wind Harmer
0.144
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.806
970169AG2-114 GEN
Solar/Wind Harmer
3.591
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
4.277
274776LINCOLN ;7U
Adder
4.277
274777LINCOLN ;8U
Adder
4.277
926823AC1-168 GEN
Solar/Wind Harmer
0.6
972228AH1-698 GEN2
Adder
1.875
972227AH1-698 GEN1
Adder
1.321
970833AG2-524 GEN
Solar/Wind Harmer
3.884
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.53
274728ELWOOD EC;5P
Adder
8.311
274731ELWOOD EC;2P
Adder
8.311
274733ELWOOD EC;3P
Adder
8.311
274735ELWOOD EC;4P
Adder
8.311
274800UNIV PARK;3U
Adder
2.946
274801UNIV PARK;4U
Adder
2.946
970073AG2-061 GEN
Solar/Wind Harmer
1.175
972037AH1-567 GEN1
Adder
0.092
274827FISK ;RP
Adder
3.918
274675JOLIET 29;7U
Adder
15.488
274675JOLIET 29;7U
Adder
14.935
274687WILL CNTY;4U
Adder
14.106
274687WILL CNTY;4U
Adder
14.106
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
274744AC1-111 GEN8
Adder
2.817
274746AC1-111 G10
Adder
2.817
276861AD2-134 GEN
Solar/Wind Harmer
0.062
276863AD2-134 GEN
Solar/Wind Harmer
0.062
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.237
971171AH1-044 GEN
Solar/Wind Harmer
6.982
960681AF2-359 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.123
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
971681AH1-341 GEN
Solar/Wind Harmer
5.605
24803006KYGER 3HP
50/50
4.127
24802806KYGER 2HP
50/50
4.111
24802906KYGER 2LP
50/50
2.413
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.768
25194508D.CRK3
Adder
1.452
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.516
972045AH1-571 GEN
Solar/Wind Harmer
1.214
270269AC2-059
Solar/Wind Harmer
0
971125AH1-004 GEN
Solar/Wind Harmer
2.245
970107AG2-081 GEN
Solar/Wind Harmer
1.684
253370AE2-315 SEC1
Adder
1.601
24728805RICHG1
Adder
2.955
24728905RICHG2
Adder
2.955
25322209TAIT E
Adder
7.522
25322209TAIT E
Adder
7.353
25326109MON D
Adder
0.984
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.111
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.905
970885AG2-551 GEN
Solar/Wind Harmer
1.635
247621Y3-024
Adder
0.162
964611AG1-324 GEN
Solar/Wind Harmer
0.348
270201AC2-176 GEN
Solar/Wind Harmer
0
24803106KYGER 3LP
50/50
2.43
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
68.684
252507AC2-088 GEN
Solar/Wind Harmer
0.357
252519AF1-045_GEN
Solar/Wind Harmer
3.858
25194608D.CRK4
Adder
1.689
25196608WSDLE5
Adder
8.798
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.081
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
17.024
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.127
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
970191AG2-125 GEN
Solar/Wind Harmer
1.385
3429391JKCT 9G
Adder
6.396
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.143
270004AE1-209 GEN
Solar/Wind Harmer
1.04
24728705AND G3
Adder
5.496
24728505AND G1
Adder
2.628
946031AF1-268 GEN
Solar/Wind Harmer
4.524
970825AG2-519 GEN
Solar/Wind Harmer
3.571
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.92
970455AG2-298 GEN
Solar/Wind Harmer
1.776
970289AG2-191 GEN
Solar/Wind Harmer
0.483
247642Z2-115 C
Solar/Wind Harmer
0.002
970653AG2-424 GEN
Solar/Wind Harmer
0.428
944531AF1-118 GEN
Solar/Wind Harmer
18.504
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970193AG2-126 GEN
Solar/Wind Harmer
6.094
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.775
270518AE2-148 GEN
Solar/Wind Harmer
0.304
971993AH1-541 GEN
Solar/Wind Harmer
1.694
942481AE2-261 GEN
Solar/Wind Harmer
10.95
957381AF2-032 GEN
Solar/Wind Harmer
0.83
964401AG1-302 GEN
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
43.369
965091AG1-374 GEN
Solar/Wind Harmer
10.891
959611AF2-252 GEN
Solar/Wind Harmer
1.21
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
4.277
274887GEN-1.85
Solar/Wind Harmer
0.092
276843GEN-1.7
Solar/Wind Harmer
0.114
276806AD2-047 C O1
Solar/Wind Harmer
2.001
972259AH1-714 GEN
Adder
9.653
274729ELWOOD EC;1P
Adder
8.311
274730ELWOOD EC;6P
Adder
8.311
274734ELWOOD EC;8P
Adder
8.311
274736ELWOOD EC;9P
Adder
8.311
970707AG2-453 GEN
Solar/Wind Harmer
11.521
270043AE2-236 GEN
Solar/Wind Harmer
2.263
972038AH1-567 GEN2
Adder
0.184
970571AG2-364 GEN
Solar/Wind Harmer
7.05
274803UNIV PARK;6U
Adder
2.945
276868AE1-113 GEN
Solar/Wind Harmer
0.705
274879MINONK ;1U
Solar/Wind Harmer
0.147
274862TOP CROP ;2U
Solar/Wind Harmer
0.476
274826FISK ;BP
Adder
5.528
274676JOLIET 29;8U
Adder
14.935
274814UNIV PK N;0U
Adder
2.55
274807UNIV PK N;3U
Adder
2.544
274811UNIV PK N;7U
Adder
2.528
274724RIVER EC ;11
Adder
8.935
274752CRETE EC ;2U
Adder
4.155
274753CRETE EC ;3U
Adder
4.155
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
943121AE2-341 GEN
Solar/Wind Harmer
5.893
943591AF1-030 GEN
Solar/Wind Harmer
3.919
274682WAUKEGAN ;7U
Adder
5.301
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
959091AF2-200 GEN
Solar/Wind Harmer
6.982
971347AH1-153 GEN
Solar/Wind Harmer
1.745
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.079
252516AE2-318_GEN
Solar/Wind Harmer
8.283
25196808ZIMRHP
Adder
79.38
25194608D.CRK4
Adder
1.689
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.986
25196008MFTGT1
Adder
1.369
253398AE2-221_GEN2
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.031
270273AD2-016 GEN
Solar/Wind Harmer
0.594
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
25326309TAIT D
Adder
0.844
3429421JKCT 10G
Adder
6.396
970773AG2-487 GEN
Solar/Wind Harmer
0.939
3429241JKCT 3G
Adder
8.835
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.76
270005AE1-210 C O1
Solar/Wind Harmer
1.04
24728605AND G2
Adder
2.628
970825AG2-519 GEN
Solar/Wind Harmer
1.683
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.07
270594AE1-207 GEN
Solar/Wind Harmer
5.019
270032AE2-172
Solar/Wind Harmer
2.988
958861AF2-177 GEN
Solar/Wind Harmer
1.919
965651AG1-433 GEN
Solar/Wind Harmer
1.282
270024AE2-089 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.063
970091AG2-072 GEN
Adder
45.503
253333AC1-068 GEN
Solar/Wind Harmer
0.005
963741AG1-226 GEN
Solar/Wind Harmer
9.274
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
964901AG1-354 GEN
Solar/Wind Harmer
5.594
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.628
276621W2-048 GEN
Solar/Wind Harmer
0.183
965911AG1-460 GEN
Solar/Wind Harmer
0.732
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.756
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
5.074
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.536
939401AE1-172 GEN
Solar/Wind Harmer
2.672
941551AE2-152 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
4.277
274774LINCOLN ;5U
Adder
4.277
971997AH1-543 GEN
Solar/Wind Harmer
1.853
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.311
274674JOLIET 9 ;6U
Adder
7.779
276694AA1-018 GEN2
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
10.575
274802UNIV PARK;5U
Adder
2.945
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.411
276646AC1-214 GEN2
Solar/Wind Harmer
0.138
274848CAMPGROVE;RU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.488
274812UNIV PK N;8U
Adder
2.528
274723RIVER EC ;12
Adder
9.04
274751CRETE EC ;1U
Adder
4.155
274754CRETE EC ;4U
Adder
4.155
274745AC1-111 GEN9
Adder
2.817
962781AG1-127 GEN
Solar/Wind Harmer
3.332
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
10.473
959081AF2-199 GEN
Solar/Wind Harmer
3.491
971067AG2-660 GEN
Solar/Wind Harmer
1.164
276708O09 GEN2
Solar/Wind Harmer
0.123
970819AG2-516 GEN
Solar/Wind Harmer
4.177
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
2.485
270599AE1-208 GEN
Solar/Wind Harmer
4.141
971613AH1-306 GEN
Solar/Wind Harmer
2.151
964571AG1-320 GEN
Solar/Wind Harmer
4.079
970291AG2-192 GEN
Solar/Wind Harmer
0.57
970291AG2-192 GEN
Solar/Wind Harmer
0.263
944541AF1-119 GEN
Solar/Wind Harmer
0.292
960971AF2-388 GEN
Solar/Wind Harmer
2.564
942221AE2-234 GEN
Solar/Wind Harmer
1.655
971587AH1-292 GEN
Solar/Wind Harmer
2.993
945391AF1-204 GEN
Solar/Wind Harmer
4.316
970241AG2-163 GEN
Solar/Wind Harmer
2.286
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.434
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.7
276911AD2-131_GEN
Solar/Wind Harmer
0.507
276615X2-022 GEN
Solar/Wind Harmer
0.038
276838X2-022 GEN2
Solar/Wind Harmer
0.206
25326509SID D
Adder
0.689
960611AF2-352 GEN
Solar/Wind Harmer
1.21
942111AE2-223 GEN
Solar/Wind Harmer
1.178
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
8.857
274770LINCOLN ;1U
Adder
4.277
274771LINCOLN ;2U
Adder
4.277
276901AD2-066 C O1
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.206
276776AD2-060 GEN
Solar/Wind Harmer
0.377
958011AF2-095 GEN
Solar/Wind Harmer
5.084
970941AG2-585 GEN
Solar/Wind Harmer
1.942
276893AG1-478 C
Solar/Wind Harmer
0.235
274674JOLIET 9 ;6U
Adder
7.779
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.287
958491AF2-143 GEN
Solar/Wind Harmer
5.287
276645AC1-214 GEN1
Solar/Wind Harmer
0.138
274805UNIV PK N;1U
Adder
2.533
274808UNIV PK N;4U
Adder
2.517
274696ROCKY RD ;4P
Adder
5.728
274695ROCKY RD ;2P
Adder
5.596
274693ROCKY RD ;1P
Adder
5.541
274697ROCKY RD ;3P
Adder
1.52
962691AG1-118 GEN
Solar/Wind Harmer
10.508
964781AG1-341 GEN
Solar/Wind Harmer
3.705
971341AH1-150 GEN
Solar/Wind Harmer
6.982
971343AH1-151 GEN
Solar/Wind Harmer
6.982
970349AG2-230 GEN
Solar/Wind Harmer
5.234
965681AG1-436 GEN
Solar/Wind Harmer
4.361
965791AG1-447 GEN
Solar/Wind Harmer
3.198
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.562
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
8.801
971087AG2-675 GEN
Solar/Wind Harmer
1.841
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
3.511
945111AF1-176 GEN
Solar/Wind Harmer
2.708
965021AG1-366 GEN
Solar/Wind Harmer
1.077
270330AC1-082 GEN2
Solar/Wind Helper
0.194
270329AC1-082 GEN1
Solar/Wind Helper
0.194
274858EASY ROAD;U2
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
5.58
945111AF1-176 GEN
Solar/Wind Harmer
5.962
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.73
965011AG1-365 GEN
Solar/Wind Harmer
3.232
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.193
235780M24_1
Solar/Wind Helper
0.496
946321AF1-296 GEN
Solar/Wind Harmer
1.935
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.411
970031AG2-029 GEN
Solar/Wind Harmer
1.822
959331AF2-224 GEN
Solar/Wind Harmer
2.262
965041AG1-368 GEN
Solar/Wind Harmer
3.099
247521TR3_G114
Solar/Wind Harmer
0.11
965051AG1-369 GEN
Solar/Wind Harmer
1.514
945631AF1-228 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
6.245
938861AE1-114 GEN
Solar/Wind Harmer
1.972
970329AG2-216 GEN
Solar/Wind Harmer
1.444
961051AF2-396 GEN
Solar/Wind Harmer
6.65
961051AF2-396 GEN
Solar/Wind Harmer
4.433
971485AH1-239 GEN
Solar/Wind Harmer
2.603
966021AG1-471 GEN
Solar/Wind Harmer
1.739
270246TR4_N_V150
Solar/Wind Harmer
0.019
270247TR4_N_V136
Solar/Wind Harmer
0.019
237033AB1-150 GEN
Solar/Wind Helper
0.401
LAGNLTFEXP_LAGN->PJM
CLTF
6.552
TVALTFEXP_TVA->PJM
CLTF
3.106
NYPJM->LTFIMP_NY
CLTF
1.666
LGEELTFEXP_LGEE->PJM
CLTF
5.14
WECLTFEXP_WEC->PJM
CLTF
1.904
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.289
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.044
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.317
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.627
MECLTFEXP_MEC->PJM
CLTF
8.009
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.393

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-022T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-022T_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:134.03 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:2403.22
MW Contribution:
26.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24643105BUCHANAN
50/50
0.011
961051AF2-396 GEN
Solar/Wind Harmer
14.843
961051AF2-396 GEN
Solar/Wind Harmer
6.904
247620Y3-023
Adder
0.355
965681AG1-436 GEN
Solar/Wind Harmer
9.316
965791AG1-447 GEN
Solar/Wind Harmer
4.766
970349AG2-230 GEN
Solar/Wind Harmer
10.88
270535AF1-215 GEN1
Solar/Wind Harmer
3.034
270536AF1-215 GEN2
Solar/Wind Harmer
3.034
274805UNIV PK N;1U
Adder
3.222
274808UNIV PK N;4U
Adder
3.201
274888KELLY CRK;1U
Solar/Wind Harmer
3.691
276776AD2-060 GEN
Solar/Wind Harmer
0.262
958011AF2-095 GEN
Solar/Wind Harmer
9.007
970941AG2-585 GEN
Solar/Wind Harmer
3.44
274770LINCOLN ;1U
Adder
3.864
274771LINCOLN ;2U
Adder
3.864
276893AG1-478 C
Solar/Wind Harmer
0.27
274674JOLIET 9 ;6U
Adder
9.491
276897AD1-100 C
Solar/Wind Harmer
28.609
958481AF2-142 GEN
Solar/Wind Harmer
9.093
274696ROCKY RD ;4P
Adder
6.847
274695ROCKY RD ;2P
Adder
6.69
274693ROCKY RD ;1P
Adder
6.624
274697ROCKY RD ;3P
Adder
1.817
274683WAUKEGAN ;8U
Adder
12.656
274683WAUKEGAN ;8U
Adder
10.669
958491AF2-143 GEN
Solar/Wind Harmer
8.975
962691AG1-118 GEN
Solar/Wind Harmer
17.876
276901AD2-066 C O1
Solar/Wind Harmer
2.086
960751AF2-366 GEN
Solar/Wind Harmer
1.706
276872AE1-163_GEN1
Solar/Wind Harmer
3.945
276876AE1-163_GEN2
Solar/Wind Harmer
3.945
945421AF1-207 GEN
Solar/Wind Harmer
8.246
957841AF2-078 GEN
Solar/Wind Harmer
3.55
971341AH1-150 GEN
Solar/Wind Harmer
11.695
971343AH1-151 GEN
Solar/Wind Harmer
11.695
972235AH1-702 GEN1
Adder
1.467
972236AH1-702 GEN2
Adder
1.275
274764LEE CO EC;5U
Adder
5.349
274765LEE CO EC;6U
Adder
5.349
274762LEE CO EC;3U
Adder
5.337
274763LEE CO EC;4U
Adder
5.286
241996AE2-282_GEN
Solar/Wind Helper
2.648
944961AF1-161 GEN
50/50
2.78
962601AG1-109 GEN
50/50
2.78
270142AC1-141 CT1_
50/50
2.114
24642205MAYFLWER
50/50
0.032
270505AE1-170 C O1
Solar/Wind Harmer
13.67
945111AF1-176 GEN
Solar/Wind Harmer
5.085
247643Z2-116 C
Solar/Wind Harmer
0.057
24441505OLIV SLR
Solar/Wind Harmer
0.106
971347AH1-153 GEN
Solar/Wind Harmer
3.627
972231SS25-0005
Solar/Wind Harmer
6.213
972181SS23-001
Solar/Wind Harmer
3.883
274752CRETE EC ;2U
Adder
3.2
274753CRETE EC ;3U
Adder
3.2
964401AG1-302 GEN
Solar/Wind Harmer
5.869
274724RIVER EC ;11
Adder
11.432
270063AE2-323 C
Solar/Wind Harmer
1.412
274814UNIV PK N;0U
Adder
3.243
274807UNIV PK N;3U
Adder
3.236
274811UNIV PK N;7U
Adder
3.215
276164X3-005 C
Solar/Wind Harmer
0.448
274803UNIV PARK;6U
Adder
3.678
274826FISK ;BP
Adder
6.886
972038AH1-567 GEN2
Adder
0.229
274887GEN-1.85
Solar/Wind Harmer
3.333
276772AC2-154 GEN
Solar/Wind Harmer
1.746
276843GEN-1.7
Solar/Wind Harmer
0.359
276806AD2-047 C O1
Solar/Wind Harmer
6.692
274772LINCOLN ;3U
Adder
3.864
274676JOLIET 29;8U
Adder
18.294
972259AH1-714 GEN
Adder
11.793
274729ELWOOD EC;1P
Adder
10.133
274730ELWOOD EC;6P
Adder
10.134
274734ELWOOD EC;8P
Adder
10.134
274736ELWOOD EC;9P
Adder
10.134
939351AE1-166 GEN
Solar/Wind Harmer
3.652
970707AG2-453 GEN
Solar/Wind Harmer
17.232
274862TOP CROP ;2U
Solar/Wind Harmer
3.066
943121AE2-341 GEN
Solar/Wind Harmer
9.092
943591AF1-030 GEN
Solar/Wind Harmer
6.061
274682WAUKEGAN ;7U
Adder
10.808
276868AE1-113 GEN
Solar/Wind Harmer
6.008
274879MINONK ;1U
Solar/Wind Harmer
4.005
276799AD1-013 GEN
Solar/Wind Harmer
1.3
946671AF1-331 GEN
Solar/Wind Harmer
0.246
274855GSG-6 ;RU
Solar/Wind Harmer
2.17
274850MENDOTA H;RU
Solar/Wind Harmer
1.509
276602WESTBROOK C
Solar/Wind Harmer
1.249
959091AF2-200 GEN
Solar/Wind Harmer
11.695
970571AG2-364 GEN
Solar/Wind Harmer
11.6
274760LEE CO EC;1U
Adder
5.337
274767LEE CO EC;8U
Adder
5.274
241832AE2-181_GEN
Solar/Wind Helper
1.154
270541AE2-072 C
Solar/Wind Helper
1.714
247604X1-042
50/50
0.027
24307105BERRINSP G
50/50
0.021
270143AC1-141 CT2_
50/50
2.114
24441205WTRV SLR C
Solar/Wind Harmer
0.143
270449AD2-020 GEN
Solar/Wind Harmer
2.68
943021AE2-325 GEN
Solar/Wind Harmer
3.483
957891AF2-083 GEN
Solar/Wind Harmer
13.525
945111AF1-176 GEN
Solar/Wind Harmer
16.045
270216AD2-079_GEN
Solar/Wind Harmer
0.491
24639705ELKHART HY
Adder
0.123
970373AG2-245 GEN
Solar/Wind Harmer
14.49
270055AF2-134 C O1
Solar/Wind Harmer
2.023
274751CRETE EC ;1U
Adder
3.2
274754CRETE EC ;4U
Adder
3.2
958381AF2-132 GEN
Solar/Wind Harmer
5.869
274723RIVER EC ;12
Adder
11.57
964861AG1-349 GEN
Solar/Wind Harmer
5.068
971917AH1-482 GEN
Solar/Wind Harmer
5.847
274812UNIV PK N;8U
Adder
3.215
274802UNIV PARK;5U
Adder
3.678
972207SS24-0001
Solar/Wind Harmer
13.738
274773LINCOLN ;4U
Adder
3.864
274774LINCOLN ;5U
Adder
3.864
274676JOLIET 29;8U
Adder
18.972
274732ELWOOD EC;7P
Adder
10.134
274674JOLIET 9 ;6U
Adder
9.491
940581AE2-045 GEN
Solar/Wind Harmer
6.287
971605AH1-302 GEN
Solar/Wind Harmer
5.376
941551AE2-152 GEN
Solar/Wind Harmer
2.793
274871GR RIDGE ;2U
Solar/Wind Harmer
4.697
274847GR RIDGE ;BU
Solar/Wind Harmer
3.089
274745AC1-111 GEN9
Adder
3.391
274861TOP CROP ;1U
Solar/Wind Harmer
3.672
276694AA1-018 GEN2
Solar/Wind Harmer
3.825
276691AA1-018 GEN1
Solar/Wind Harmer
0.457
274682WAUKEGAN ;7U
Adder
10.808
274828WAUKEGAN ;BP
Adder
6.634
276805AD2-038 GEN
Solar/Wind Harmer
3.068
962781AG1-127 GEN
Solar/Wind Harmer
5.653
276882AE2-255 GEN
Solar/Wind Harmer
2.003
274872LEEDK;1U
Solar/Wind Harmer
4.869
939401AE1-172 GEN
Solar/Wind Harmer
8.253
971997AH1-543 GEN
Solar/Wind Harmer
9.288
957471AF2-041 GEN
Solar/Wind Harmer
17.542
959081AF2-199 GEN
Solar/Wind Harmer
5.847
971067AG2-660 GEN
Solar/Wind Harmer
1.36
274822ROCKFORD ;11
Adder
11.448
970819AG2-516 GEN
Solar/Wind Harmer
6.962
970569AG2-363 GEN
Solar/Wind Harmer
17.4
274761LEE CO EC;2U
Adder
5.337
274766LEE CO EC;7U
Adder
5.274
241840AF1-064_GEN
Solar/Wind Helper
1.493
241807AE2-176_GEN
Solar/Wind Helper
1.736
241885AC2-103 GEN1
Solar/Wind Helper
2.327
960841AF2-375 GEN
Solar/Wind Helper
1.443
958961AF2-187 GEN
Solar/Wind Helper
1.026
24344005CKG1
50/50
6.047
270144AC1-141 ST1_
50/50
1.867
971549AH1-272 GEN
Solar/Wind Harmer
26.308
944161AF1-084 GEN
Solar/Wind Harmer
2.18
971771AH1-392 GEN
Solar/Wind Harmer
7.351
270526AF1-158 GEN
Solar/Wind Harmer
3.624
960681AF2-359 GEN
Solar/Wind Harmer
2.816
970031AG2-029 GEN
Solar/Wind Harmer
16.718
958391AF2-133 GEN
Solar/Wind Harmer
5.765
972037AH1-567 GEN1
Adder
0.115
274827FISK ;RP
Adder
4.88
274800UNIV PARK;3U
Adder
3.658
274801UNIV PARK;4U
Adder
3.658
959141AF2-205 GEN
Solar/Wind Harmer
3.792
960591AF2-350 GEN
Solar/Wind Harmer
6.255
274775LINCOLN ;6U
Adder
3.864
274776LINCOLN ;7U
Adder
3.864
274777LINCOLN ;8U
Adder
3.864
972228AH1-698 GEN2
Adder
2.306
972227AH1-698 GEN1
Adder
1.624
274687WILL CNTY;4U
Adder
17.333
274687WILL CNTY;4U
Adder
17.333
274675JOLIET 29;7U
Adder
18.972
274675JOLIET 29;7U
Adder
18.294
276893AG1-478 C
Solar/Wind Harmer
0.339
274728ELWOOD EC;5P
Adder
10.134
274731ELWOOD EC;2P
Adder
10.133
274733ELWOOD EC;3P
Adder
10.133
274735ELWOOD EC;4P
Adder
10.133
970833AG2-524 GEN
Solar/Wind Harmer
5.338
970833AG2-524 GEN
Solar/Wind Harmer
2.483
274744AC1-111 GEN8
Adder
3.391
274746AC1-111 G10
Adder
3.391
970073AG2-061 GEN
Solar/Wind Harmer
1.392
971411AH1-196 GEN
Solar/Wind Harmer
8.834
971675AH1-338 GEN
Solar/Wind Harmer
10.583
276861AD2-134 GEN
Solar/Wind Harmer
1.049
276863AD2-134 GEN
Solar/Wind Harmer
1.049
276889AE2-281 GEN
Solar/Wind Harmer
1.127
971171AH1-044 GEN
Solar/Wind Harmer
11.695
274863CRW1-WTG
Solar/Wind Harmer
3.256
274864CRW2-WTG
Solar/Wind Harmer
3.256
274823ROCKFORD ;21
Adder
11.365
274856ECOGROVE ;U1
Solar/Wind Harmer
1.953
276611AD2-172 GEN
Solar/Wind Harmer
1.482
276612AE2-035 GEN
Solar/Wind Harmer
1.482
972267AH1-718 GEN
Adder
2.366
945411AF1-206 GEN
Solar/Wind Helper
5
241886AC2-103 GEN2
Solar/Wind Helper
2.327
945641AF1-229 GEN
Solar/Wind Helper
1.306
270499AE1-146 GEN
Solar/Wind Helper
2.205
926823AC1-168 GEN
Solar/Wind Harmer
0.354
241808AF1-120 C
Solar/Wind Helper
1.48
247522W1-056 GEN
Solar/Wind Helper
0.764
990142J1224
External Queue
48.28803634643555
990527J1329
External Queue
6.605751037597656
991182J1586 G
External Queue
80.72422790527344
991227J1663 G
External Queue
17.147865295410156
991177J1571 G
External Queue
66.31126403808594
LAGNLTFEXP_LAGN->PJM
CLTF
5.528
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.322
TVALTFEXP_TVA->PJM
CLTF
2.349
NYPJM->LTFIMP_NY
CLTF
1.153
LGEELTFEXP_LGEE->PJM
CLTF
1.731
WECLTFEXP_WEC->PJM
CLTF
2.223
AG2-052LTFEXP_AG2-052->PJM
LTF
0.145
AH1-155LTFEXP_AH1-155->PJM
LTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
189.521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.936
MECLTFEXP_MEC->PJM
CLTF
8.28
SIGELTFEXP_SIGE->PJM
CLTF
0.168
CPLELTFEXP_CPLE->PJM
CLTF
0.455
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.425

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-034T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-034T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.4 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:1943.59
MW Contribution:
20.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
Solar/Wind Harmer
20.226
944161AF1-084 GEN
Solar/Wind Harmer
1.685
971771AH1-392 GEN
Solar/Wind Harmer
5.695
270526AF1-158 GEN
Solar/Wind Harmer
2.809
960681AF2-359 GEN
Solar/Wind Harmer
2.185
970031AG2-029 GEN
Solar/Wind Harmer
12.992
958391AF2-133 GEN
Solar/Wind Harmer
4.486
972037AH1-567 GEN1
Adder
0.09
274827FISK ;RP
Adder
3.798
270505AE1-170 C O1
Solar/Wind Harmer
10.576
945111AF1-176 GEN
Solar/Wind Harmer
3.935
247643Z2-116 C
Solar/Wind Harmer
0.044
24441505OLIV SLR
Solar/Wind Harmer
0.082
971347AH1-153 GEN
Solar/Wind Harmer
2.815
972231SS25-0005
Solar/Wind Harmer
4.832
972181SS23-001
Solar/Wind Harmer
3.02
274752CRETE EC ;2U
Adder
2.488
274753CRETE EC ;3U
Adder
2.488
964401AG1-302 GEN
Solar/Wind Harmer
4.565
274724RIVER EC ;11
Adder
8.893
274814UNIV PK N;0U
Adder
2.523
274807UNIV PK N;3U
Adder
2.517
274811UNIV PK N;7U
Adder
2.501
270063AE2-323 C
Solar/Wind Harmer
1.09
276164X3-005 C
Solar/Wind Harmer
0.348
274803UNIV PARK;6U
Adder
2.862
274826FISK ;BP
Adder
5.359
972038AH1-567 GEN2
Adder
0.178
274887GEN-1.85
Solar/Wind Harmer
2.594
276772AC2-154 GEN
Solar/Wind Harmer
1.359
276843GEN-1.7
Solar/Wind Harmer
0.279
276806AD2-047 C O1
Solar/Wind Harmer
5.208
274772LINCOLN ;3U
Adder
3.008
274676JOLIET 29;8U
Adder
14.241
972259AH1-714 GEN
Adder
9.18
274729ELWOOD EC;1P
Adder
7.888
274730ELWOOD EC;6P
Adder
7.889
274734ELWOOD EC;8P
Adder
7.889
274736ELWOOD EC;9P
Adder
7.889
939351AE1-166 GEN
Solar/Wind Harmer
2.844
970707AG2-453 GEN
Solar/Wind Harmer
13.415
274800UNIV PARK;3U
Adder
2.846
274801UNIV PARK;4U
Adder
2.846
959141AF2-205 GEN
Solar/Wind Harmer
2.951
960591AF2-350 GEN
Solar/Wind Harmer
4.868
274775LINCOLN ;6U
Adder
3.008
274776LINCOLN ;7U
Adder
3.008
274777LINCOLN ;8U
Adder
3.008
972228AH1-698 GEN2
Adder
1.795
972227AH1-698 GEN1
Adder
1.264
274687WILL CNTY;4U
Adder
13.492
274687WILL CNTY;4U
Adder
13.492
274675JOLIET 29;7U
Adder
14.768
274675JOLIET 29;7U
Adder
14.241
276893AG1-478 C
Solar/Wind Harmer
0.264
274728ELWOOD EC;5P
Adder
7.889
274731ELWOOD EC;2P
Adder
7.888
274733ELWOOD EC;3P
Adder
7.888
274735ELWOOD EC;4P
Adder
7.888
970833AG2-524 GEN
Solar/Wind Harmer
4.156
970833AG2-524 GEN
Solar/Wind Harmer
1.933
247604X1-042
50/50
0.021
24441205WTRV SLR C
Solar/Wind Harmer
0.11
270449AD2-020 GEN
Solar/Wind Harmer
2.072
943021AE2-325 GEN
Solar/Wind Harmer
2.693
957891AF2-083 GEN
Solar/Wind Harmer
10.465
945111AF1-176 GEN
Solar/Wind Harmer
12.415
270216AD2-079_GEN
Solar/Wind Harmer
0.38
24639705ELKHART HY
Adder
0.095
970373AG2-245 GEN
Solar/Wind Harmer
11.259
270055AF2-134 C O1
Solar/Wind Harmer
1.572
274751CRETE EC ;1U
Adder
2.488
274754CRETE EC ;4U
Adder
2.488
958381AF2-132 GEN
Solar/Wind Harmer
4.565
274723RIVER EC ;12
Adder
9
964861AG1-349 GEN
Solar/Wind Harmer
3.943
971917AH1-482 GEN
Solar/Wind Harmer
4.549
274812UNIV PK N;8U
Adder
2.501
274802UNIV PARK;5U
Adder
2.862
972207SS24-0001
Solar/Wind Harmer
10.693
274773LINCOLN ;4U
Adder
3.008
274774LINCOLN ;5U
Adder
3.008
274676JOLIET 29;8U
Adder
14.768
940581AE2-045 GEN
Solar/Wind Harmer
4.895
274732ELWOOD EC;7P
Adder
7.889
274674JOLIET 9 ;6U
Adder
7.389
971605AH1-302 GEN
Solar/Wind Harmer
4.186
941551AE2-152 GEN
Solar/Wind Harmer
2.175
274871GR RIDGE ;2U
Solar/Wind Harmer
3.657
274847GR RIDGE ;BU
Solar/Wind Harmer
2.405
961051AF2-396 GEN
Solar/Wind Harmer
11.48
961051AF2-396 GEN
Solar/Wind Harmer
5.34
247620Y3-023
Adder
0.275
965681AG1-436 GEN
Solar/Wind Harmer
7.229
965791AG1-447 GEN
Solar/Wind Harmer
3.699
970349AG2-230 GEN
Solar/Wind Harmer
8.446
270535AF1-215 GEN1
Solar/Wind Harmer
2.359
270536AF1-215 GEN2
Solar/Wind Harmer
2.359
274805UNIV PK N;1U
Adder
2.506
274808UNIV PK N;4U
Adder
2.49
274888KELLY CRK;1U
Solar/Wind Harmer
2.873
276776AD2-060 GEN
Solar/Wind Harmer
0.204
958011AF2-095 GEN
Solar/Wind Harmer
7.01
970941AG2-585 GEN
Solar/Wind Harmer
2.678
274770LINCOLN ;1U
Adder
3.008
274771LINCOLN ;2U
Adder
3.008
276893AG1-478 C
Solar/Wind Harmer
0.21
274674JOLIET 9 ;6U
Adder
7.389
276897AD1-100 C
Solar/Wind Harmer
22.273
958481AF2-142 GEN
Solar/Wind Harmer
7.081
274696ROCKY RD ;4P
Adder
5.333
274695ROCKY RD ;2P
Adder
5.21
274693ROCKY RD ;1P
Adder
5.159
274862TOP CROP ;2U
Solar/Wind Harmer
2.388
943121AE2-341 GEN
Solar/Wind Harmer
7.08
943591AF1-030 GEN
Solar/Wind Harmer
4.72
274682WAUKEGAN ;7U
Adder
8.417
276868AE1-113 GEN
Solar/Wind Harmer
4.68
274879MINONK ;1U
Solar/Wind Harmer
3.12
276799AD1-013 GEN
Solar/Wind Harmer
1.012
946671AF1-331 GEN
Solar/Wind Harmer
0.192
274855GSG-6 ;RU
Solar/Wind Harmer
1.691
274850MENDOTA H;RU
Solar/Wind Harmer
1.176
276602WESTBROOK C
Solar/Wind Harmer
0.973
959091AF2-200 GEN
Solar/Wind Harmer
9.112
970571AG2-364 GEN
Solar/Wind Harmer
9.04
274760LEE CO EC;1U
Adder
4.16
274767LEE CO EC;8U
Adder
4.111
241832AE2-181_GEN
Solar/Wind Helper
1.101
270541AE2-072 C
Solar/Wind Helper
1.493
274745AC1-111 GEN9
Adder
2.64
276694AA1-018 GEN2
Solar/Wind Harmer
2.979
276691AA1-018 GEN1
Solar/Wind Harmer
0.356
274744AC1-111 GEN8
Adder
2.64
274746AC1-111 G10
Adder
2.64
970073AG2-061 GEN
Solar/Wind Harmer
1.084
971411AH1-196 GEN
Solar/Wind Harmer
6.883
971675AH1-338 GEN
Solar/Wind Harmer
8.246
276861AD2-134 GEN
Solar/Wind Harmer
0.818
276863AD2-134 GEN
Solar/Wind Harmer
0.818
276889AE2-281 GEN
Solar/Wind Harmer
0.878
971171AH1-044 GEN
Solar/Wind Harmer
9.112
274863CRW1-WTG
Solar/Wind Harmer
2.538
274864CRW2-WTG
Solar/Wind Harmer
2.538
274823ROCKFORD ;21
Adder
8.856
274856ECOGROVE ;U1
Solar/Wind Harmer
1.522
276611AD2-172 GEN
Solar/Wind Harmer
1.155
276612AE2-035 GEN
Solar/Wind Harmer
1.155
972267AH1-718 GEN
Adder
1.844
945411AF1-206 GEN
Solar/Wind Helper
4.842
241886AC2-103 GEN2
Solar/Wind Helper
1.906
270499AE1-146 GEN
Solar/Wind Helper
1.607
945641AF1-229 GEN
Solar/Wind Helper
0.874
926823AC1-168 GEN
Solar/Wind Harmer
0.276
274697ROCKY RD ;3P
Adder
1.415
274683WAUKEGAN ;8U
Adder
9.857
274683WAUKEGAN ;8U
Adder
8.309
958491AF2-143 GEN
Solar/Wind Harmer
6.991
962691AG1-118 GEN
Solar/Wind Harmer
13.924
276901AD2-066 C O1
Solar/Wind Harmer
1.625
960751AF2-366 GEN
Solar/Wind Harmer
1.329
276872AE1-163_GEN1
Solar/Wind Harmer
3.074
276876AE1-163_GEN2
Solar/Wind Harmer
3.074
945421AF1-207 GEN
Solar/Wind Harmer
6.427
957841AF2-078 GEN
Solar/Wind Harmer
2.767
971341AH1-150 GEN
Solar/Wind Harmer
9.112
971343AH1-151 GEN
Solar/Wind Harmer
9.112
972235AH1-702 GEN1
Adder
1.143
972236AH1-702 GEN2
Adder
0.994
274764LEE CO EC;5U
Adder
4.169
274765LEE CO EC;6U
Adder
4.169
274762LEE CO EC;3U
Adder
4.16
274763LEE CO EC;4U
Adder
4.12
241996AE2-282_GEN
Solar/Wind Helper
2.564
241808AF1-120 C
Solar/Wind Helper
1.433
274861TOP CROP ;1U
Solar/Wind Harmer
2.86
274682WAUKEGAN ;7U
Adder
8.417
274828WAUKEGAN ;BP
Adder
5.167
276805AD2-038 GEN
Solar/Wind Harmer
2.39
962781AG1-127 GEN
Solar/Wind Harmer
4.404
276882AE2-255 GEN
Solar/Wind Harmer
1.56
274872LEEDK;1U
Solar/Wind Harmer
3.793
939401AE1-172 GEN
Solar/Wind Harmer
6.43
971997AH1-543 GEN
Solar/Wind Harmer
7.236
957471AF2-041 GEN
Solar/Wind Harmer
13.669
959081AF2-199 GEN
Solar/Wind Harmer
4.556
971067AG2-660 GEN
Solar/Wind Harmer
1.06
274822ROCKFORD ;11
Adder
8.92
970819AG2-516 GEN
Solar/Wind Harmer
5.425
970569AG2-363 GEN
Solar/Wind Harmer
13.561
274761LEE CO EC;2U
Adder
4.16
274766LEE CO EC;7U
Adder
4.111
241840AF1-064_GEN
Solar/Wind Helper
1.326
241807AE2-176_GEN
Solar/Wind Helper
1.442
241885AC2-103 GEN1
Solar/Wind Helper
1.906
960841AF2-375 GEN
Solar/Wind Helper
1.048
990142J1224
External Queue
38.63399124145508
990527J1329
External Queue
5.285087585449219
991182J1586 G
External Queue
59.15724563598633
991227J1663 G
External Queue
12.725373268127441
991177J1571 G
External Queue
62.38090515136719
LAGNLTFEXP_LAGN->PJM
CLTF
4.382
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.944
TVALTFEXP_TVA->PJM
CLTF
1.873
NYPJM->LTFIMP_NY
CLTF
0.9
LGEELTFEXP_LGEE->PJM
CLTF
1.388
WECLTFEXP_WEC->PJM
CLTF
1.732
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
AH1-155LTFEXP_AH1-155->PJM
LTF
0.169
CBM West 1LTFEXP_CBM-W1->PJM
CBM
150.114
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.134
MECLTFEXP_MEC->PJM
CLTF
6.472
SIGELTFEXP_SIGE->PJM
CLTF
0.133
CPLELTFEXP_CPLE->PJM
CLTF
0.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.066

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-033T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-033T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.18 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:1939.73
MW Contribution:
20.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
961051AF2-396 GEN
Solar/Wind Harmer
11.396
961051AF2-396 GEN
Solar/Wind Harmer
5.3
247620Y3-023
Adder
0.271
965681AG1-436 GEN
Solar/Wind Harmer
7.149
965791AG1-447 GEN
Solar/Wind Harmer
3.657
970349AG2-230 GEN
Solar/Wind Harmer
8.346
270535AF1-215 GEN1
Solar/Wind Harmer
2.328
270536AF1-215 GEN2
Solar/Wind Harmer
2.328
274805UNIV PK N;1U
Adder
2.472
274808UNIV PK N;4U
Adder
2.455
274888KELLY CRK;1U
Solar/Wind Harmer
2.832
276776AD2-060 GEN
Solar/Wind Harmer
0.201
958011AF2-095 GEN
Solar/Wind Harmer
6.91
970941AG2-585 GEN
Solar/Wind Harmer
2.639
274770LINCOLN ;1U
Adder
2.964
274771LINCOLN ;2U
Adder
2.964
276893AG1-478 C
Solar/Wind Harmer
0.207
274674JOLIET 9 ;6U
Adder
7.281
276897AD1-100 C
Solar/Wind Harmer
21.946
958481AF2-142 GEN
Solar/Wind Harmer
6.976
274696ROCKY RD ;4P
Adder
5.253
274695ROCKY RD ;2P
Adder
5.132
274693ROCKY RD ;1P
Adder
5.081
274697ROCKY RD ;3P
Adder
1.394
274683WAUKEGAN ;8U
Adder
9.709
274683WAUKEGAN ;8U
Adder
8.184
958491AF2-143 GEN
Solar/Wind Harmer
6.885
962691AG1-118 GEN
Solar/Wind Harmer
13.713
276901AD2-066 C O1
Solar/Wind Harmer
1.6
960751AF2-366 GEN
Solar/Wind Harmer
1.308
276872AE1-163_GEN1
Solar/Wind Harmer
3.026
276876AE1-163_GEN2
Solar/Wind Harmer
3.026
945421AF1-207 GEN
Solar/Wind Harmer
6.324
957841AF2-078 GEN
Solar/Wind Harmer
2.723
971341AH1-150 GEN
Solar/Wind Harmer
8.972
971343AH1-151 GEN
Solar/Wind Harmer
8.972
972235AH1-702 GEN1
Adder
1.125
972236AH1-702 GEN2
Adder
0.978
274764LEE CO EC;5U
Adder
4.104
274765LEE CO EC;6U
Adder
4.104
274762LEE CO EC;3U
Adder
4.094
274763LEE CO EC;4U
Adder
4.055
241996AE2-282_GEN
Solar/Wind Helper
2.521
241808AF1-120 C
Solar/Wind Helper
1.409
270505AE1-170 C O1
Solar/Wind Harmer
10.494
945111AF1-176 GEN
Solar/Wind Harmer
3.903
247643Z2-116 C
Solar/Wind Harmer
0.043
24441505OLIV SLR
Solar/Wind Harmer
0.082
971347AH1-153 GEN
Solar/Wind Harmer
2.782
972231SS25-0005
Solar/Wind Harmer
4.766
972181SS23-001
Solar/Wind Harmer
2.979
274752CRETE EC ;2U
Adder
2.455
274753CRETE EC ;3U
Adder
2.455
964401AG1-302 GEN
Solar/Wind Harmer
4.502
274724RIVER EC ;11
Adder
8.77
274814UNIV PK N;0U
Adder
2.488
274807UNIV PK N;3U
Adder
2.482
274811UNIV PK N;7U
Adder
2.466
276164X3-005 C
Solar/Wind Harmer
0.343
270063AE2-323 C
Solar/Wind Harmer
1.073
274803UNIV PARK;6U
Adder
2.821
274826FISK ;BP
Adder
5.282
972038AH1-567 GEN2
Adder
0.176
274887GEN-1.85
Solar/Wind Harmer
2.556
276772AC2-154 GEN
Solar/Wind Harmer
1.339
276843GEN-1.7
Solar/Wind Harmer
0.275
276806AD2-047 C O1
Solar/Wind Harmer
5.133
274772LINCOLN ;3U
Adder
2.964
274676JOLIET 29;8U
Adder
14.034
972259AH1-714 GEN
Adder
9.047
274730ELWOOD EC;6P
Adder
7.774
274734ELWOOD EC;8P
Adder
7.774
274736ELWOOD EC;9P
Adder
7.774
274729ELWOOD EC;1P
Adder
7.773
939351AE1-166 GEN
Solar/Wind Harmer
2.802
970707AG2-453 GEN
Solar/Wind Harmer
13.219
274862TOP CROP ;2U
Solar/Wind Harmer
2.352
943121AE2-341 GEN
Solar/Wind Harmer
6.974
943591AF1-030 GEN
Solar/Wind Harmer
4.65
274682WAUKEGAN ;7U
Adder
8.291
276868AE1-113 GEN
Solar/Wind Harmer
4.609
274879MINONK ;1U
Solar/Wind Harmer
3.073
276799AD1-013 GEN
Solar/Wind Harmer
0.997
946671AF1-331 GEN
Solar/Wind Harmer
0.189
274855GSG-6 ;RU
Solar/Wind Harmer
1.665
274850MENDOTA H;RU
Solar/Wind Harmer
1.158
276602WESTBROOK C
Solar/Wind Harmer
0.958
959091AF2-200 GEN
Solar/Wind Harmer
8.972
970571AG2-364 GEN
Solar/Wind Harmer
8.899
274760LEE CO EC;1U
Adder
4.094
274767LEE CO EC;8U
Adder
4.046
241832AE2-181_GEN
Solar/Wind Helper
1.084
270541AE2-072 C
Solar/Wind Helper
1.511
971549AH1-272 GEN
Solar/Wind Harmer
20.195
944161AF1-084 GEN
Solar/Wind Harmer
1.674
971771AH1-392 GEN
Solar/Wind Harmer
5.639
270526AF1-158 GEN
Solar/Wind Harmer
2.781
960681AF2-359 GEN
Solar/Wind Harmer
2.161
970031AG2-029 GEN
Solar/Wind Harmer
12.78
958391AF2-133 GEN
Solar/Wind Harmer
4.423
972037AH1-567 GEN1
Adder
0.089
274827FISK ;RP
Adder
3.744
274800UNIV PARK;3U
Adder
2.806
274801UNIV PARK;4U
Adder
2.806
959141AF2-205 GEN
Solar/Wind Harmer
2.909
960591AF2-350 GEN
Solar/Wind Harmer
4.798
274775LINCOLN ;6U
Adder
2.964
274776LINCOLN ;7U
Adder
2.964
274777LINCOLN ;8U
Adder
2.964
972228AH1-698 GEN2
Adder
1.769
972227AH1-698 GEN1
Adder
1.246
274687WILL CNTY;4U
Adder
13.297
274687WILL CNTY;4U
Adder
13.297
274675JOLIET 29;7U
Adder
14.554
274675JOLIET 29;7U
Adder
14.034
276893AG1-478 C
Solar/Wind Harmer
0.26
274728ELWOOD EC;5P
Adder
7.774
274731ELWOOD EC;2P
Adder
7.773
274733ELWOOD EC;3P
Adder
7.773
274735ELWOOD EC;4P
Adder
7.773
970833AG2-524 GEN
Solar/Wind Harmer
4.095
970833AG2-524 GEN
Solar/Wind Harmer
1.905
274744AC1-111 GEN8
Adder
2.601
274746AC1-111 G10
Adder
2.601
970073AG2-061 GEN
Solar/Wind Harmer
1.067
971411AH1-196 GEN
Solar/Wind Harmer
6.777
971675AH1-338 GEN
Solar/Wind Harmer
8.119
276861AD2-134 GEN
Solar/Wind Harmer
0.805
276863AD2-134 GEN
Solar/Wind Harmer
0.805
276889AE2-281 GEN
Solar/Wind Harmer
0.865
971171AH1-044 GEN
Solar/Wind Harmer
8.972
274863CRW1-WTG
Solar/Wind Harmer
2.498
274864CRW2-WTG
Solar/Wind Harmer
2.498
274823ROCKFORD ;21
Adder
8.718
274856ECOGROVE ;U1
Solar/Wind Harmer
1.498
276611AD2-172 GEN
Solar/Wind Harmer
1.137
276612AE2-035 GEN
Solar/Wind Harmer
1.137
972267AH1-718 GEN
Adder
1.815
945411AF1-206 GEN
Solar/Wind Helper
4.761
241886AC2-103 GEN2
Solar/Wind Helper
1.763
270499AE1-146 GEN
Solar/Wind Helper
1.709
945641AF1-229 GEN
Solar/Wind Helper
0.975
926823AC1-168 GEN
Solar/Wind Harmer
0.272
24441205WTRV SLR C
Solar/Wind Harmer
0.11
270449AD2-020 GEN
Solar/Wind Harmer
2.058
943021AE2-325 GEN
Solar/Wind Harmer
2.674
957891AF2-083 GEN
Solar/Wind Harmer
10.382
945111AF1-176 GEN
Solar/Wind Harmer
12.314
270216AD2-079_GEN
Solar/Wind Harmer
0.376
24639705ELKHART HY
Adder
0.094
970373AG2-245 GEN
Solar/Wind Harmer
11.118
270055AF2-134 C O1
Solar/Wind Harmer
1.552
274751CRETE EC ;1U
Adder
2.455
274754CRETE EC ;4U
Adder
2.455
958381AF2-132 GEN
Solar/Wind Harmer
4.502
274723RIVER EC ;12
Adder
8.875
964861AG1-349 GEN
Solar/Wind Harmer
3.888
971917AH1-482 GEN
Solar/Wind Harmer
4.485
274812UNIV PK N;8U
Adder
2.466
274802UNIV PARK;5U
Adder
2.821
972207SS24-0001
Solar/Wind Harmer
10.538
274773LINCOLN ;4U
Adder
2.964
274774LINCOLN ;5U
Adder
2.964
274676JOLIET 29;8U
Adder
14.554
274732ELWOOD EC;7P
Adder
7.774
274674JOLIET 9 ;6U
Adder
7.281
940581AE2-045 GEN
Solar/Wind Harmer
4.823
971605AH1-302 GEN
Solar/Wind Harmer
4.123
941551AE2-152 GEN
Solar/Wind Harmer
2.143
274871GR RIDGE ;2U
Solar/Wind Harmer
3.603
274847GR RIDGE ;BU
Solar/Wind Harmer
2.369
274745AC1-111 GEN9
Adder
2.601
276694AA1-018 GEN2
Solar/Wind Harmer
2.934
276691AA1-018 GEN1
Solar/Wind Harmer
0.351
274861TOP CROP ;1U
Solar/Wind Harmer
2.817
274682WAUKEGAN ;7U
Adder
8.291
274828WAUKEGAN ;BP
Adder
5.089
276805AD2-038 GEN
Solar/Wind Harmer
2.354
962781AG1-127 GEN
Solar/Wind Harmer
4.337
276882AE2-255 GEN
Solar/Wind Harmer
1.536
274872LEEDK;1U
Solar/Wind Harmer
3.735
939401AE1-172 GEN
Solar/Wind Harmer
6.331
971997AH1-543 GEN
Solar/Wind Harmer
7.125
957471AF2-041 GEN
Solar/Wind Harmer
13.457
959081AF2-199 GEN
Solar/Wind Harmer
4.486
971067AG2-660 GEN
Solar/Wind Harmer
1.043
274822ROCKFORD ;11
Adder
8.782
970819AG2-516 GEN
Solar/Wind Harmer
5.341
970569AG2-363 GEN
Solar/Wind Harmer
13.348
274761LEE CO EC;2U
Adder
4.094
274766LEE CO EC;7U
Adder
4.046
241840AF1-064_GEN
Solar/Wind Helper
1.304
241807AE2-176_GEN
Solar/Wind Helper
1.365
241885AC2-103 GEN1
Solar/Wind Helper
1.763
960841AF2-375 GEN
Solar/Wind Helper
1.115
990142J1224
External Queue
38.97322463989258
990527J1329
External Queue
5.3314948081970215
991182J1586 G
External Queue
59.70839309692383
991227J1663 G
External Queue
12.830781936645508
991177J1571 G
External Queue
62.831573486328125
LAGNLTFEXP_LAGN->PJM
CLTF
4.248
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.805
TVALTFEXP_TVA->PJM
CLTF
1.806
NYPJM->LTFIMP_NY
CLTF
0.875
LGEELTFEXP_LGEE->PJM
CLTF
1.329
WECLTFEXP_WEC->PJM
CLTF
1.705
AG2-052LTFEXP_AG2-052->PJM
LTF
0.111
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.863
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.869
MECLTFEXP_MEC->PJM
CLTF
6.353
SIGELTFEXP_SIGE->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
0.358
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.106

Details for 19MON12-02LALLENDORF 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-025T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/ITCT
Facility Description:
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-025T_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:122.24 %
Rating:1660.0 MVA
Rating Type:B
MVA to Mitigate:2029.25
MW Contribution:
22.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270505AE1-170 C O1
Solar/Wind Harmer
11.986
945111AF1-176 GEN
Solar/Wind Harmer
4.46
247643Z2-116 C
Solar/Wind Harmer
0.05
24441505OLIV SLR
Solar/Wind Harmer
0.093
971347AH1-153 GEN
Solar/Wind Harmer
3.191
270063AE2-323 C
Solar/Wind Harmer
1.278
972231SS25-0005
Solar/Wind Harmer
5.475
972181SS23-001
Solar/Wind Harmer
3.422
274752CRETE EC ;2U
Adder
2.82
274753CRETE EC ;3U
Adder
2.82
964401AG1-302 GEN
Solar/Wind Harmer
5.173
274724RIVER EC ;11
Adder
10.076
274814UNIV PK N;0U
Adder
2.859
274807UNIV PK N;3U
Adder
2.852
274811UNIV PK N;7U
Adder
2.834
276164X3-005 C
Solar/Wind Harmer
0.395
274803UNIV PARK;6U
Adder
3.243
274826FISK ;BP
Adder
6.072
972038AH1-567 GEN2
Adder
0.202
274887GEN-1.85
Solar/Wind Harmer
2.939
276772AC2-154 GEN
Solar/Wind Harmer
1.539
276843GEN-1.7
Solar/Wind Harmer
0.316
276806AD2-047 C O1
Solar/Wind Harmer
5.901
274772LINCOLN ;3U
Adder
3.408
274676JOLIET 29;8U
Adder
16.135
972259AH1-714 GEN
Adder
10.402
274729ELWOOD EC;1P
Adder
8.938
274730ELWOOD EC;6P
Adder
8.938
274734ELWOOD EC;8P
Adder
8.938
274736ELWOOD EC;9P
Adder
8.938
939351AE1-166 GEN
Solar/Wind Harmer
3.222
970707AG2-453 GEN
Solar/Wind Harmer
15.201
943121AE2-341 GEN
Solar/Wind Harmer
8.021
943591AF1-030 GEN
Solar/Wind Harmer
5.348
274862TOP CROP ;2U
Solar/Wind Harmer
2.705
274682WAUKEGAN ;7U
Adder
9.536
276868AE1-113 GEN
Solar/Wind Harmer
5.302
274879MINONK ;1U
Solar/Wind Harmer
3.535
276799AD1-013 GEN
Solar/Wind Harmer
1.147
946671AF1-331 GEN
Solar/Wind Harmer
0.217
274855GSG-6 ;RU
Solar/Wind Harmer
1.915
274850MENDOTA H;RU
Solar/Wind Harmer
1.332
276602WESTBROOK C
Solar/Wind Harmer
1.103
959091AF2-200 GEN
Solar/Wind Harmer
10.322
970571AG2-364 GEN
Solar/Wind Harmer
10.24
274760LEE CO EC;1U
Adder
4.711
274767LEE CO EC;8U
Adder
4.656
241832AE2-181_GEN
Solar/Wind Helper
0.386
961051AF2-396 GEN
Solar/Wind Harmer
13.012
961051AF2-396 GEN
Solar/Wind Harmer
6.052
247620Y3-023
Adder
0.313
965681AG1-436 GEN
Solar/Wind Harmer
8.192
965791AG1-447 GEN
Solar/Wind Harmer
4.191
970349AG2-230 GEN
Solar/Wind Harmer
9.573
270535AF1-215 GEN1
Solar/Wind Harmer
2.673
270536AF1-215 GEN2
Solar/Wind Harmer
2.673
247604X1-042
50/50
0.024
24441205WTRV SLR C
Solar/Wind Harmer
0.125
270449AD2-020 GEN
Solar/Wind Harmer
2.349
943021AE2-325 GEN
Solar/Wind Harmer
3.052
957891AF2-083 GEN
Solar/Wind Harmer
11.862
945111AF1-176 GEN
Solar/Wind Harmer
14.073
270216AD2-079_GEN
Solar/Wind Harmer
0.431
24639705ELKHART HY
Adder
0.108
970373AG2-245 GEN
Solar/Wind Harmer
12.759
270055AF2-134 C O1
Solar/Wind Harmer
1.782
274751CRETE EC ;1U
Adder
2.82
274754CRETE EC ;4U
Adder
2.82
958381AF2-132 GEN
Solar/Wind Harmer
5.173
274723RIVER EC ;12
Adder
10.198
964861AG1-349 GEN
Solar/Wind Harmer
4.467
971917AH1-482 GEN
Solar/Wind Harmer
5.154
274812UNIV PK N;8U
Adder
2.834
274802UNIV PARK;5U
Adder
3.243
972207SS24-0001
Solar/Wind Harmer
12.118
274773LINCOLN ;4U
Adder
3.408
274774LINCOLN ;5U
Adder
3.408
274676JOLIET 29;8U
Adder
16.733
940581AE2-045 GEN
Solar/Wind Harmer
5.547
971605AH1-302 GEN
Solar/Wind Harmer
4.743
274732ELWOOD EC;7P
Adder
8.938
274674JOLIET 9 ;6U
Adder
8.372
941551AE2-152 GEN
Solar/Wind Harmer
2.464
274871GR RIDGE ;2U
Solar/Wind Harmer
4.144
274847GR RIDGE ;BU
Solar/Wind Harmer
2.725
274745AC1-111 GEN9
Adder
2.992
276694AA1-018 GEN2
Solar/Wind Harmer
3.375
276691AA1-018 GEN1
Solar/Wind Harmer
0.403
274861TOP CROP ;1U
Solar/Wind Harmer
3.24
274682WAUKEGAN ;7U
Adder
9.536
274828WAUKEGAN ;BP
Adder
5.853
276805AD2-038 GEN
Solar/Wind Harmer
2.707
962781AG1-127 GEN
Solar/Wind Harmer
4.989
276882AE2-255 GEN
Solar/Wind Harmer
1.767
274872LEEDK;1U
Solar/Wind Harmer
4.297
939401AE1-172 GEN
Solar/Wind Harmer
7.285
971997AH1-543 GEN
Solar/Wind Harmer
8.198
957471AF2-041 GEN
Solar/Wind Harmer
15.483
959081AF2-199 GEN
Solar/Wind Harmer
5.161
971067AG2-660 GEN
Solar/Wind Harmer
1.2
274822ROCKFORD ;11
Adder
10.104
970819AG2-516 GEN
Solar/Wind Harmer
6.145
970569AG2-363 GEN
Solar/Wind Harmer
15.36
274761LEE CO EC;2U
Adder
4.711
274766LEE CO EC;7U
Adder
4.656
241885AC2-103 GEN1
Solar/Wind Helper
2.234
241807AE2-176_GEN
Solar/Wind Helper
1.462
960841AF2-375 GEN
Solar/Wind Helper
1.14
241840AF1-064_GEN
Solar/Wind Helper
0.697
274805UNIV PK N;1U
Adder
2.84
274808UNIV PK N;4U
Adder
2.821
274888KELLY CRK;1U
Solar/Wind Harmer
3.255
276776AD2-060 GEN
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
7.943
970941AG2-585 GEN
Solar/Wind Harmer
3.034
274770LINCOLN ;1U
Adder
3.408
274771LINCOLN ;2U
Adder
3.408
276893AG1-478 C
Solar/Wind Harmer
0.238
274674JOLIET 9 ;6U
Adder
8.372
276897AD1-100 C
Solar/Wind Harmer
25.237
958481AF2-142 GEN
Solar/Wind Harmer
8.022
274696ROCKY RD ;4P
Adder
6.042
274695ROCKY RD ;2P
Adder
5.902
274693ROCKY RD ;1P
Adder
5.844
274697ROCKY RD ;3P
Adder
1.603
274683WAUKEGAN ;8U
Adder
11.167
274683WAUKEGAN ;8U
Adder
9.413
958491AF2-143 GEN
Solar/Wind Harmer
7.92
962691AG1-118 GEN
Solar/Wind Harmer
15.774
276901AD2-066 C O1
Solar/Wind Harmer
1.841
960751AF2-366 GEN
Solar/Wind Harmer
1.505
276872AE1-163_GEN1
Solar/Wind Harmer
3.482
276876AE1-163_GEN2
Solar/Wind Harmer
3.482
945421AF1-207 GEN
Solar/Wind Harmer
7.282
957841AF2-078 GEN
Solar/Wind Harmer
3.135
971341AH1-150 GEN
Solar/Wind Harmer
10.322
971343AH1-151 GEN
Solar/Wind Harmer
10.322
972235AH1-702 GEN1
Adder
1.295
972236AH1-702 GEN2
Adder
1.126
274764LEE CO EC;5U
Adder
4.722
274765LEE CO EC;6U
Adder
4.722
274762LEE CO EC;3U
Adder
4.711
274763LEE CO EC;4U
Adder
4.667
241996AE2-282_GEN
Solar/Wind Helper
0.855
241808AF1-120 C
Solar/Wind Helper
0.478
938861AE1-114 GEN
Solar/Wind Harmer
0.668
971549AH1-272 GEN
Solar/Wind Harmer
22.651
944161AF1-084 GEN
Solar/Wind Harmer
1.91
971771AH1-392 GEN
Solar/Wind Harmer
6.457
270526AF1-158 GEN
Solar/Wind Harmer
3.184
960681AF2-359 GEN
Solar/Wind Harmer
2.476
970031AG2-029 GEN
Solar/Wind Harmer
14.816
958391AF2-133 GEN
Solar/Wind Harmer
5.083
972037AH1-567 GEN1
Adder
0.102
274827FISK ;RP
Adder
4.303
274800UNIV PARK;3U
Adder
3.225
274801UNIV PARK;4U
Adder
3.225
959141AF2-205 GEN
Solar/Wind Harmer
3.344
960591AF2-350 GEN
Solar/Wind Harmer
5.516
274775LINCOLN ;6U
Adder
3.408
274776LINCOLN ;7U
Adder
3.408
274777LINCOLN ;8U
Adder
3.408
972228AH1-698 GEN2
Adder
2.034
972227AH1-698 GEN1
Adder
1.432
274687WILL CNTY;4U
Adder
15.287
274687WILL CNTY;4U
Adder
15.287
274675JOLIET 29;7U
Adder
16.733
274675JOLIET 29;7U
Adder
16.135
276893AG1-478 C
Solar/Wind Harmer
0.299
274728ELWOOD EC;5P
Adder
8.938
274731ELWOOD EC;2P
Adder
8.938
274733ELWOOD EC;3P
Adder
8.938
274735ELWOOD EC;4P
Adder
8.938
970833AG2-524 GEN
Solar/Wind Harmer
4.709
970833AG2-524 GEN
Solar/Wind Harmer
2.19
274744AC1-111 GEN8
Adder
2.992
274746AC1-111 G10
Adder
2.992
970073AG2-061 GEN
Solar/Wind Harmer
1.228
971411AH1-196 GEN
Solar/Wind Harmer
7.796
971675AH1-338 GEN
Solar/Wind Harmer
9.341
276861AD2-134 GEN
Solar/Wind Harmer
0.926
276863AD2-134 GEN
Solar/Wind Harmer
0.926
276889AE2-281 GEN
Solar/Wind Harmer
0.995
971171AH1-044 GEN
Solar/Wind Harmer
10.322
274863CRW1-WTG
Solar/Wind Harmer
2.875
274864CRW2-WTG
Solar/Wind Harmer
2.875
274823ROCKFORD ;21
Adder
10.031
274856ECOGROVE ;U1
Solar/Wind Harmer
1.724
276611AD2-172 GEN
Solar/Wind Harmer
1.308
276612AE2-035 GEN
Solar/Wind Harmer
1.308
926823AC1-168 GEN
Solar/Wind Harmer
2.192
971681AH1-341 GEN
Solar/Wind Harmer
7.625
972267AH1-718 GEN
Adder
2.089
241886AC2-103 GEN2
Solar/Wind Helper
2.234
945641AF1-229 GEN
Solar/Wind Helper
1.133
270499AE1-146 GEN
Solar/Wind Helper
1.718
945411AF1-206 GEN
Solar/Wind Helper
1.615
990142J1224
External Queue
36.94019317626953
990527J1329
External Queue
5.053378105163574
991182J1586 G
External Queue
63.8489990234375
991227J1663 G
External Queue
13.66822624206543
LAGNLTFEXP_LAGN->PJM
CLTF
4.922
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.087
TVALTFEXP_TVA->PJM
CLTF
2.098
NYPJM->LTFIMP_NY
CLTF
1.052
LGEELTFEXP_LGEE->PJM
CLTF
1.561
WECLTFEXP_WEC->PJM
CLTF
1.962
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.191
CBM West 1LTFEXP_CBM-W1->PJM
CBM
176.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.998
MECLTFEXP_MEC->PJM
CLTF
7.323
SIGELTFEXP_SIGE->PJM
CLTF
0.15
CPLELTFEXP_CPLE->PJM
CLTF
0.409
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.541

Details for 19MON12-02LALLENDORF 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-023T_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/ITCT
Facility Description:
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-023T_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.94 %
Rating:1660.0 MVA
Rating Type:B
MVA to Mitigate:1941.12
MW Contribution:
20.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270505AE1-170 C O1
Solar/Wind Harmer
11.023
945111AF1-176 GEN
Solar/Wind Harmer
4.104
247643Z2-116 C
Solar/Wind Harmer
0.046
24441505OLIV SLR
Solar/Wind Harmer
0.086
971347AH1-153 GEN
Solar/Wind Harmer
2.938
270063AE2-323 C
Solar/Wind Harmer
1.178
972231SS25-0005
Solar/Wind Harmer
5.044
972181SS23-001
Solar/Wind Harmer
3.153
274752CRETE EC ;2U
Adder
2.598
274753CRETE EC ;3U
Adder
2.598
964401AG1-302 GEN
Solar/Wind Harmer
4.767
274724RIVER EC ;11
Adder
9.284
274814UNIV PK N;0U
Adder
2.634
274807UNIV PK N;3U
Adder
2.628
274811UNIV PK N;7U
Adder
2.611
276164X3-005 C
Solar/Wind Harmer
0.364
274803UNIV PARK;6U
Adder
2.988
274826FISK ;BP
Adder
5.595
972038AH1-567 GEN2
Adder
0.186
274887GEN-1.85
Solar/Wind Harmer
2.708
276772AC2-154 GEN
Solar/Wind Harmer
1.419
276843GEN-1.7
Solar/Wind Harmer
0.291
276806AD2-047 C O1
Solar/Wind Harmer
5.438
274772LINCOLN ;3U
Adder
3.141
274676JOLIET 29;8U
Adder
14.869
972259AH1-714 GEN
Adder
9.586
274729ELWOOD EC;1P
Adder
8.236
274730ELWOOD EC;6P
Adder
8.237
274734ELWOOD EC;8P
Adder
8.237
274736ELWOOD EC;9P
Adder
8.237
939351AE1-166 GEN
Solar/Wind Harmer
2.969
970707AG2-453 GEN
Solar/Wind Harmer
14.008
274862TOP CROP ;2U
Solar/Wind Harmer
2.493
943121AE2-341 GEN
Solar/Wind Harmer
7.392
943591AF1-030 GEN
Solar/Wind Harmer
4.928
274682WAUKEGAN ;7U
Adder
8.788
276868AE1-113 GEN
Solar/Wind Harmer
4.887
274879MINONK ;1U
Solar/Wind Harmer
3.258
276799AD1-013 GEN
Solar/Wind Harmer
1.057
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274855GSG-6 ;RU
Solar/Wind Harmer
1.765
274850MENDOTA H;RU
Solar/Wind Harmer
1.227
276602WESTBROOK C
Solar/Wind Harmer
1.016
959091AF2-200 GEN
Solar/Wind Harmer
9.514
970571AG2-364 GEN
Solar/Wind Harmer
9.439
274760LEE CO EC;1U
Adder
4.343
274767LEE CO EC;8U
Adder
4.292
241832AE2-181_GEN
Solar/Wind Helper
0.431
247604X1-042
50/50
0.022
24441205WTRV SLR C
Solar/Wind Harmer
0.115
270449AD2-020 GEN
Solar/Wind Harmer
2.159
943021AE2-325 GEN
Solar/Wind Harmer
2.806
957891AF2-083 GEN
Solar/Wind Harmer
10.911
945111AF1-176 GEN
Solar/Wind Harmer
12.95
270216AD2-079_GEN
Solar/Wind Harmer
0.398
24639705ELKHART HY
Adder
0.1
970373AG2-245 GEN
Solar/Wind Harmer
11.751
270055AF2-134 C O1
Solar/Wind Harmer
1.641
274751CRETE EC ;1U
Adder
2.598
274754CRETE EC ;4U
Adder
2.598
958381AF2-132 GEN
Solar/Wind Harmer
4.767
274723RIVER EC ;12
Adder
9.396
964861AG1-349 GEN
Solar/Wind Harmer
4.117
971917AH1-482 GEN
Solar/Wind Harmer
4.75
274812UNIV PK N;8U
Adder
2.611
274802UNIV PARK;5U
Adder
2.988
972207SS24-0001
Solar/Wind Harmer
11.166
274773LINCOLN ;4U
Adder
3.141
274774LINCOLN ;5U
Adder
3.141
274676JOLIET 29;8U
Adder
15.42
940581AE2-045 GEN
Solar/Wind Harmer
5.113
971605AH1-302 GEN
Solar/Wind Harmer
4.372
274732ELWOOD EC;7P
Adder
8.237
274674JOLIET 9 ;6U
Adder
7.715
941551AE2-152 GEN
Solar/Wind Harmer
2.271
274871GR RIDGE ;2U
Solar/Wind Harmer
3.819
274847GR RIDGE ;BU
Solar/Wind Harmer
2.511
274745AC1-111 GEN9
Adder
2.757
276694AA1-018 GEN2
Solar/Wind Harmer
3.11
276691AA1-018 GEN1
Solar/Wind Harmer
0.372
274861TOP CROP ;1U
Solar/Wind Harmer
2.986
274682WAUKEGAN ;7U
Adder
8.788
274828WAUKEGAN ;BP
Adder
5.395
276805AD2-038 GEN
Solar/Wind Harmer
2.495
962781AG1-127 GEN
Solar/Wind Harmer
4.598
276882AE2-255 GEN
Solar/Wind Harmer
1.629
274872LEEDK;1U
Solar/Wind Harmer
3.96
939401AE1-172 GEN
Solar/Wind Harmer
6.715
971997AH1-543 GEN
Solar/Wind Harmer
7.556
957471AF2-041 GEN
Solar/Wind Harmer
14.271
959081AF2-199 GEN
Solar/Wind Harmer
4.757
971067AG2-660 GEN
Solar/Wind Harmer
1.106
274822ROCKFORD ;11
Adder
9.313
970819AG2-516 GEN
Solar/Wind Harmer
5.664
970569AG2-363 GEN
Solar/Wind Harmer
14.159
274761LEE CO EC;2U
Adder
4.343
274766LEE CO EC;7U
Adder
4.292
241885AC2-103 GEN1
Solar/Wind Helper
2.07
241807AE2-176_GEN
Solar/Wind Helper
1.368
241840AF1-064_GEN
Solar/Wind Helper
0.676
960841AF2-375 GEN
Solar/Wind Helper
1.036
961051AF2-396 GEN
Solar/Wind Harmer
11.966
961051AF2-396 GEN
Solar/Wind Harmer
5.566
247620Y3-023
Adder
0.289
965681AG1-436 GEN
Solar/Wind Harmer
7.541
965791AG1-447 GEN
Solar/Wind Harmer
3.858
970349AG2-230 GEN
Solar/Wind Harmer
8.814
270535AF1-215 GEN1
Solar/Wind Harmer
2.462
270536AF1-215 GEN2
Solar/Wind Harmer
2.462
274805UNIV PK N;1U
Adder
2.617
274808UNIV PK N;4U
Adder
2.6
274888KELLY CRK;1U
Solar/Wind Harmer
3
276776AD2-060 GEN
Solar/Wind Harmer
0.213
958011AF2-095 GEN
Solar/Wind Harmer
7.32
970941AG2-585 GEN
Solar/Wind Harmer
2.796
274770LINCOLN ;1U
Adder
3.141
274771LINCOLN ;2U
Adder
3.141
276893AG1-478 C
Solar/Wind Harmer
0.22
274674JOLIET 9 ;6U
Adder
7.715
276897AD1-100 C
Solar/Wind Harmer
23.257
958481AF2-142 GEN
Solar/Wind Harmer
7.393
274696ROCKY RD ;4P
Adder
5.568
274695ROCKY RD ;2P
Adder
5.44
274693ROCKY RD ;1P
Adder
5.386
274697ROCKY RD ;3P
Adder
1.478
274683WAUKEGAN ;8U
Adder
10.292
274683WAUKEGAN ;8U
Adder
8.675
958491AF2-143 GEN
Solar/Wind Harmer
7.299
962691AG1-118 GEN
Solar/Wind Harmer
14.538
276901AD2-066 C O1
Solar/Wind Harmer
1.697
960751AF2-366 GEN
Solar/Wind Harmer
1.387
945421AF1-207 GEN
Solar/Wind Harmer
6.715
957841AF2-078 GEN
Solar/Wind Harmer
2.891
276872AE1-163_GEN1
Solar/Wind Harmer
3.209
276876AE1-163_GEN2
Solar/Wind Harmer
3.209
971341AH1-150 GEN
Solar/Wind Harmer
9.514
971343AH1-151 GEN
Solar/Wind Harmer
9.514
972235AH1-702 GEN1
Adder
1.193
972236AH1-702 GEN2
Adder
1.038
274764LEE CO EC;5U
Adder
4.353
274765LEE CO EC;6U
Adder
4.353
971549AH1-272 GEN
Solar/Wind Harmer
20.774
944161AF1-084 GEN
Solar/Wind Harmer
1.755
971771AH1-392 GEN
Solar/Wind Harmer
5.944
270526AF1-158 GEN
Solar/Wind Harmer
2.931
960681AF2-359 GEN
Solar/Wind Harmer
2.279
970031AG2-029 GEN
Solar/Wind Harmer
13.705
958391AF2-133 GEN
Solar/Wind Harmer
4.685
972037AH1-567 GEN1
Adder
0.094
274827FISK ;RP
Adder
3.965
959141AF2-205 GEN
Solar/Wind Harmer
3.082
274800UNIV PARK;3U
Adder
2.972
274801UNIV PARK;4U
Adder
2.972
960591AF2-350 GEN
Solar/Wind Harmer
5.083
274775LINCOLN ;6U
Adder
3.141
274776LINCOLN ;7U
Adder
3.141
274777LINCOLN ;8U
Adder
3.141
972228AH1-698 GEN2
Adder
1.874
972227AH1-698 GEN1
Adder
1.32
274687WILL CNTY;4U
Adder
14.087
274687WILL CNTY;4U
Adder
14.087
274675JOLIET 29;7U
Adder
15.42
274675JOLIET 29;7U
Adder
14.869
276893AG1-478 C
Solar/Wind Harmer
0.276
274728ELWOOD EC;5P
Adder
8.237
274731ELWOOD EC;2P
Adder
8.236
274733ELWOOD EC;3P
Adder
8.236
274735ELWOOD EC;4P
Adder
8.236
970833AG2-524 GEN
Solar/Wind Harmer
4.34
970833AG2-524 GEN
Solar/Wind Harmer
2.018
274744AC1-111 GEN8
Adder
2.757
274746AC1-111 G10
Adder
2.757
970073AG2-061 GEN
Solar/Wind Harmer
1.132
971411AH1-196 GEN
Solar/Wind Harmer
7.186
971675AH1-338 GEN
Solar/Wind Harmer
8.609
276861AD2-134 GEN
Solar/Wind Harmer
0.854
276863AD2-134 GEN
Solar/Wind Harmer
0.854
276889AE2-281 GEN
Solar/Wind Harmer
0.917
971171AH1-044 GEN
Solar/Wind Harmer
9.514
274863CRW1-WTG
Solar/Wind Harmer
2.65
274864CRW2-WTG
Solar/Wind Harmer
2.65
274823ROCKFORD ;21
Adder
9.246
274856ECOGROVE ;U1
Solar/Wind Harmer
1.589
276611AD2-172 GEN
Solar/Wind Harmer
1.206
276612AE2-035 GEN
Solar/Wind Harmer
1.206
972267AH1-718 GEN
Adder
1.926
241886AC2-103 GEN2
Solar/Wind Helper
2.07
945411AF1-206 GEN
Solar/Wind Helper
1.883
945641AF1-229 GEN
Solar/Wind Helper
1.019
270499AE1-146 GEN
Solar/Wind Helper
1.563
926823AC1-168 GEN
Solar/Wind Harmer
0.288
274762LEE CO EC;3U
Adder
4.343
274763LEE CO EC;4U
Adder
4.302
241996AE2-282_GEN
Solar/Wind Helper
0.997
241808AF1-120 C
Solar/Wind Helper
0.557
990142J1224
External Queue
31.628137588500977
990527J1329
External Queue
4.326694965362549
991182J1586 G
External Queue
55.93790054321289
991227J1663 G
External Queue
12.273685455322266
991177J1571 G
External Queue
36.189971923828125
LAGNLTFEXP_LAGN->PJM
CLTF
4.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.956
TVALTFEXP_TVA->PJM
CLTF
1.944
NYPJM->LTFIMP_NY
CLTF
0.968
LGEELTFEXP_LGEE->PJM
CLTF
1.448
WECLTFEXP_WEC->PJM
CLTF
1.808
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
164.251
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.411
MECLTFEXP_MEC->PJM
CLTF
6.755
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CPLELTFEXP_CPLE->PJM
CLTF
0.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.556

Details for 19MON12-02LALLENDORF 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-022T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/ITCT
Facility Description:
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-022T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.81 %
Rating:1660.0 MVA
Rating Type:B
MVA to Mitigate:1939.0
MW Contribution:
20.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270505AE1-170 C O1
Solar/Wind Harmer
11.025
945111AF1-176 GEN
Solar/Wind Harmer
4.105
247643Z2-116 C
Solar/Wind Harmer
0.046
24441505OLIV SLR
Solar/Wind Harmer
0.086
971347AH1-153 GEN
Solar/Wind Harmer
2.938
270063AE2-323 C
Solar/Wind Harmer
1.179
972231SS25-0005
Solar/Wind Harmer
5.045
972181SS23-001
Solar/Wind Harmer
3.153
274752CRETE EC ;2U
Adder
2.598
274753CRETE EC ;3U
Adder
2.598
964401AG1-302 GEN
Solar/Wind Harmer
4.767
274724RIVER EC ;11
Adder
9.285
274814UNIV PK N;0U
Adder
2.634
274807UNIV PK N;3U
Adder
2.629
274811UNIV PK N;7U
Adder
2.611
276164X3-005 C
Solar/Wind Harmer
0.364
274803UNIV PARK;6U
Adder
2.988
274826FISK ;BP
Adder
5.596
972038AH1-567 GEN2
Adder
0.186
274887GEN-1.85
Solar/Wind Harmer
2.709
276772AC2-154 GEN
Solar/Wind Harmer
1.419
276843GEN-1.7
Solar/Wind Harmer
0.291
276806AD2-047 C O1
Solar/Wind Harmer
5.438
274772LINCOLN ;3U
Adder
3.141
274676JOLIET 29;8U
Adder
14.871
972259AH1-714 GEN
Adder
9.587
274729ELWOOD EC;1P
Adder
8.237
274730ELWOOD EC;6P
Adder
8.238
274734ELWOOD EC;8P
Adder
8.238
274736ELWOOD EC;9P
Adder
8.238
939351AE1-166 GEN
Solar/Wind Harmer
2.969
970707AG2-453 GEN
Solar/Wind Harmer
14.01
274862TOP CROP ;2U
Solar/Wind Harmer
2.493
943121AE2-341 GEN
Solar/Wind Harmer
7.393
943591AF1-030 GEN
Solar/Wind Harmer
4.929
274682WAUKEGAN ;7U
Adder
8.789
276868AE1-113 GEN
Solar/Wind Harmer
4.887
274879MINONK ;1U
Solar/Wind Harmer
3.258
276799AD1-013 GEN
Solar/Wind Harmer
1.057
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274855GSG-6 ;RU
Solar/Wind Harmer
1.766
274850MENDOTA H;RU
Solar/Wind Harmer
1.228
276602WESTBROOK C
Solar/Wind Harmer
1.016
959091AF2-200 GEN
Solar/Wind Harmer
9.515
970571AG2-364 GEN
Solar/Wind Harmer
9.44
274760LEE CO EC;1U
Adder
4.343
274767LEE CO EC;8U
Adder
4.292
241832AE2-181_GEN
Solar/Wind Helper
0.423
971549AH1-272 GEN
Solar/Wind Harmer
20.774
944161AF1-084 GEN
Solar/Wind Harmer
1.755
971771AH1-392 GEN
Solar/Wind Harmer
5.944
270526AF1-158 GEN
Solar/Wind Harmer
2.931
960681AF2-359 GEN
Solar/Wind Harmer
2.28
970031AG2-029 GEN
Solar/Wind Harmer
13.708
958391AF2-133 GEN
Solar/Wind Harmer
4.685
972037AH1-567 GEN1
Adder
0.094
274827FISK ;RP
Adder
3.966
959141AF2-205 GEN
Solar/Wind Harmer
3.083
274800UNIV PARK;3U
Adder
2.972
274801UNIV PARK;4U
Adder
2.972
960591AF2-350 GEN
Solar/Wind Harmer
5.084
274775LINCOLN ;6U
Adder
3.141
274776LINCOLN ;7U
Adder
3.141
274777LINCOLN ;8U
Adder
3.141
972228AH1-698 GEN2
Adder
1.874
972227AH1-698 GEN1
Adder
1.32
274687WILL CNTY;4U
Adder
14.089
274687WILL CNTY;4U
Adder
14.089
274675JOLIET 29;7U
Adder
15.422
274675JOLIET 29;7U
Adder
14.871
276893AG1-478 C
Solar/Wind Harmer
0.276
274728ELWOOD EC;5P
Adder
8.238
274731ELWOOD EC;2P
Adder
8.237
274733ELWOOD EC;3P
Adder
8.237
274735ELWOOD EC;4P
Adder
8.237
970833AG2-524 GEN
Solar/Wind Harmer
4.34
970833AG2-524 GEN
Solar/Wind Harmer
2.019
274744AC1-111 GEN8
Adder
2.757
274746AC1-111 G10
Adder
2.757
970073AG2-061 GEN
Solar/Wind Harmer
1.132
971411AH1-196 GEN
Solar/Wind Harmer
7.187
971675AH1-338 GEN
Solar/Wind Harmer
8.61
276861AD2-134 GEN
Solar/Wind Harmer
0.854
276863AD2-134 GEN
Solar/Wind Harmer
0.854
276889AE2-281 GEN
Solar/Wind Harmer
0.917
971171AH1-044 GEN
Solar/Wind Harmer
9.515
274863CRW1-WTG
Solar/Wind Harmer
2.65
274864CRW2-WTG
Solar/Wind Harmer
2.65
274823ROCKFORD ;21
Adder
9.247
274856ECOGROVE ;U1
Solar/Wind Harmer
1.589
276611AD2-172 GEN
Solar/Wind Harmer
1.206
276612AE2-035 GEN
Solar/Wind Harmer
1.206
972267AH1-718 GEN
Adder
1.926
241886AC2-103 GEN2
Solar/Wind Helper
2.071
945411AF1-206 GEN
Solar/Wind Helper
1.845
945641AF1-229 GEN
Solar/Wind Helper
1.02
270499AE1-146 GEN
Solar/Wind Helper
1.563
926823AC1-168 GEN
Solar/Wind Harmer
0.288
961051AF2-396 GEN
Solar/Wind Harmer
11.967
961051AF2-396 GEN
Solar/Wind Harmer
5.566
247620Y3-023
Adder
0.289
965681AG1-436 GEN
Solar/Wind Harmer
7.542
965791AG1-447 GEN
Solar/Wind Harmer
3.859
970349AG2-230 GEN
Solar/Wind Harmer
8.815
270535AF1-215 GEN1
Solar/Wind Harmer
2.462
270536AF1-215 GEN2
Solar/Wind Harmer
2.462
274805UNIV PK N;1U
Adder
2.617
274808UNIV PK N;4U
Adder
2.6
274888KELLY CRK;1U
Solar/Wind Harmer
3
276776AD2-060 GEN
Solar/Wind Harmer
0.213
958011AF2-095 GEN
Solar/Wind Harmer
7.321
970941AG2-585 GEN
Solar/Wind Harmer
2.796
274770LINCOLN ;1U
Adder
3.141
274771LINCOLN ;2U
Adder
3.141
276893AG1-478 C
Solar/Wind Harmer
0.22
274674JOLIET 9 ;6U
Adder
7.716
276897AD1-100 C
Solar/Wind Harmer
23.26
958481AF2-142 GEN
Solar/Wind Harmer
7.394
274695ROCKY RD ;2P
Adder
5.44
274693ROCKY RD ;1P
Adder
5.387
274697ROCKY RD ;3P
Adder
1.478
274696ROCKY RD ;4P
Adder
5.569
274683WAUKEGAN ;8U
Adder
10.293
274683WAUKEGAN ;8U
Adder
8.676
958491AF2-143 GEN
Solar/Wind Harmer
7.3
962691AG1-118 GEN
Solar/Wind Harmer
14.54
276901AD2-066 C O1
Solar/Wind Harmer
1.697
960751AF2-366 GEN
Solar/Wind Harmer
1.387
945421AF1-207 GEN
Solar/Wind Harmer
6.716
957841AF2-078 GEN
Solar/Wind Harmer
2.891
276872AE1-163_GEN1
Solar/Wind Harmer
3.21
276876AE1-163_GEN2
Solar/Wind Harmer
3.21
971341AH1-150 GEN
Solar/Wind Harmer
9.515
971343AH1-151 GEN
Solar/Wind Harmer
9.515
972235AH1-702 GEN1
Adder
1.193
972236AH1-702 GEN2
Adder
1.038
274764LEE CO EC;5U
Adder
4.354
274765LEE CO EC;6U
Adder
4.354
274762LEE CO EC;3U
Adder
4.343
274763LEE CO EC;4U
Adder
4.302
241996AE2-282_GEN
Solar/Wind Helper
0.977
241808AF1-120 C
Solar/Wind Helper
0.546
247604X1-042
50/50
0.022
24441205WTRV SLR C
Solar/Wind Harmer
0.115
270449AD2-020 GEN
Solar/Wind Harmer
2.159
943021AE2-325 GEN
Solar/Wind Harmer
2.806
957891AF2-083 GEN
Solar/Wind Harmer
10.912
945111AF1-176 GEN
Solar/Wind Harmer
12.951
270216AD2-079_GEN
Solar/Wind Harmer
0.398
24639705ELKHART HY
Adder
0.1
970373AG2-245 GEN
Solar/Wind Harmer
11.752
270055AF2-134 C O1
Solar/Wind Harmer
1.642
274751CRETE EC ;1U
Adder
2.598
274754CRETE EC ;4U
Adder
2.598
958381AF2-132 GEN
Solar/Wind Harmer
4.767
274723RIVER EC ;12
Adder
9.397
964861AG1-349 GEN
Solar/Wind Harmer
4.117
971917AH1-482 GEN
Solar/Wind Harmer
4.75
274812UNIV PK N;8U
Adder
2.611
274802UNIV PARK;5U
Adder
2.988
972207SS24-0001
Solar/Wind Harmer
11.168
274773LINCOLN ;4U
Adder
3.141
274774LINCOLN ;5U
Adder
3.141
274676JOLIET 29;8U
Adder
15.422
940581AE2-045 GEN
Solar/Wind Harmer
5.114
971605AH1-302 GEN
Solar/Wind Harmer
4.372
274732ELWOOD EC;7P
Adder
8.238
274674JOLIET 9 ;6U
Adder
7.716
941551AE2-152 GEN
Solar/Wind Harmer
2.271
274871GR RIDGE ;2U
Solar/Wind Harmer
3.819
274847GR RIDGE ;BU
Solar/Wind Harmer
2.511
274745AC1-111 GEN9
Adder
2.757
274861TOP CROP ;1U
Solar/Wind Harmer
2.986
276694AA1-018 GEN2
Solar/Wind Harmer
3.11
276691AA1-018 GEN1
Solar/Wind Harmer
0.372
274682WAUKEGAN ;7U
Adder
8.789
274828WAUKEGAN ;BP
Adder
5.395
276805AD2-038 GEN
Solar/Wind Harmer
2.496
962781AG1-127 GEN
Solar/Wind Harmer
4.599
276882AE2-255 GEN
Solar/Wind Harmer
1.629
274872LEEDK;1U
Solar/Wind Harmer
3.961
939401AE1-172 GEN
Solar/Wind Harmer
6.715
971997AH1-543 GEN
Solar/Wind Harmer
7.557
957471AF2-041 GEN
Solar/Wind Harmer
14.273
959081AF2-199 GEN
Solar/Wind Harmer
4.758
971067AG2-660 GEN
Solar/Wind Harmer
1.106
274822ROCKFORD ;11
Adder
9.314
970819AG2-516 GEN
Solar/Wind Harmer
5.665
970569AG2-363 GEN
Solar/Wind Harmer
14.161
274761LEE CO EC;2U
Adder
4.343
274766LEE CO EC;7U
Adder
4.292
241885AC2-103 GEN1
Solar/Wind Helper
2.071
241807AE2-176_GEN
Solar/Wind Helper
1.367
241840AF1-064_GEN
Solar/Wind Helper
0.675
960841AF2-375 GEN
Solar/Wind Helper
1.036
990142J1224
External Queue
31.623668670654297
990527J1329
External Queue
4.326083183288574
991182J1586 G
External Queue
55.92937088012695
991227J1663 G
External Queue
12.272621154785156
991177J1571 G
External Queue
36.18729019165039
LAGNLTFEXP_LAGN->PJM
CLTF
4.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.955
TVALTFEXP_TVA->PJM
CLTF
1.944
NYPJM->LTFIMP_NY
CLTF
0.968
LGEELTFEXP_LGEE->PJM
CLTF
1.448
WECLTFEXP_WEC->PJM
CLTF
1.809
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
164.256
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.412
MECLTFEXP_MEC->PJM
CLTF
6.755
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CPLELTFEXP_CPLE->PJM
CLTF
0.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.559

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-009_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-009_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.39 %
Rating:1499.0 MVA
Rating Type:B
MVA to Mitigate:2104.51
MW Contribution:
12.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.557
23888702TROY G3
50/50
1.74
972253AH1-711 GEN
50/50
53.199
23856402BAYSG1
50/50
1.287
23920202STRYCT
50/50
1.895
23860302FRMENG 3
50/50
2.415
241885AC2-103 GEN1
Solar/Wind Harmer
25.598
241858AF1-205_GEN
Solar/Wind Harmer
5.472
241840AF1-064_GEN
Solar/Wind Harmer
1.386
23906502RICHG2&3
Adder
1.312
960841AF2-375 GEN
Solar/Wind Harmer
3.801
241807AE2-176_GEN
Solar/Wind Harmer
3.573
270297AD1-101 GEN
Solar/Wind Harmer
1.388
270258AD1-119 GEN
Solar/Wind Harmer
1.262
24441205WTRV SLR C
Solar/Wind Harmer
0.079
246936BC-WTG1
Solar/Wind Harmer
2.262
270489AE1-102 GEN1
Solar/Wind Harmer
0.752
965421AG1-410 GEN
Solar/Wind Harmer
17.18
270449AD2-020 GEN
Solar/Wind Harmer
1.571
943021AE2-325 GEN
Solar/Wind Harmer
2.042
945111AF1-176 GEN
Solar/Wind Harmer
9.791
957891AF2-083 GEN
Solar/Wind Harmer
8.197
24639705ELKHART HY
Adder
0.082
270216AD2-079_GEN
Solar/Wind Harmer
0.32
965011AG1-365 GEN
Solar/Wind Harmer
5.197
270317AD1-130_GEN
Solar/Wind Harmer
1.662
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270391AF1-285 GEN3
Solar/Wind Harmer
0.583
270578AF1-285 GEN2
Solar/Wind Harmer
0.583
970373AG2-245 GEN
Solar/Wind Harmer
9.828
270055AF2-134 C O1
Solar/Wind Harmer
1.392
274751CRETE EC ;1U
Adder
2.219
274754CRETE EC ;4U
Adder
2.219
958381AF2-132 GEN
Solar/Wind Harmer
4.104
964861AG1-349 GEN
Solar/Wind Harmer
3.55
971917AH1-482 GEN
Solar/Wind Harmer
4.096
274723RIVER EC ;12
Adder
8.071
274812UNIV PK N;8U
Adder
2.245
274802UNIV PARK;5U
Adder
2.586
940581AE2-045 GEN
Solar/Wind Harmer
4.502
971605AH1-302 GEN
Solar/Wind Harmer
3.849
972207SS24-0001
Solar/Wind Harmer
9.724
274773LINCOLN ;4U
Adder
2.735
274774LINCOLN ;5U
Adder
2.735
241847AF2-150_GEN
Solar/Wind Harmer
1.822
23929302BS-PKR
50/50
2.268
241832AE2-181_GEN
Solar/Wind Harmer
1.943
958321AF2-126 GEN
Solar/Wind Harmer
1.49
23906402RICHG1
Adder
1.314
23906502RICHG2&3
Adder
1.312
270541AE2-072 C
Solar/Wind Harmer
4.312
270044AE2-322 C
Solar/Wind Harmer
0.85
270588AE1-091_GEN
Solar/Wind Harmer
6.835
958091AF2-103 GEN
Solar/Wind Harmer
0.094
246938BC-WTG3
Solar/Wind Harmer
2.301
270491AE1-102 GEN2
Solar/Wind Harmer
0.752
24695305TIMB G C
Solar/Wind Harmer
1.869
945111AF1-176 GEN
Solar/Wind Harmer
3.103
270505AE1-170 C O1
Solar/Wind Harmer
8.223
270063AE2-323 C
Solar/Wind Harmer
1.168
247643Z2-116 C
Solar/Wind Harmer
0.037
965021AG1-366 GEN
Solar/Wind Harmer
1.209
24441505OLIV SLR
Solar/Wind Harmer
0.068
270043AE2-236 GEN
Solar/Wind Harmer
2.696
971347AH1-153 GEN
Solar/Wind Harmer
2.429
942871AE2-306 GEN
Solar/Wind Harmer
0.437
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
972231SS25-0005
Solar/Wind Harmer
4.308
972181SS23-001
Solar/Wind Harmer
2.692
274752CRETE EC ;2U
Adder
2.219
274753CRETE EC ;3U
Adder
2.219
964401AG1-302 GEN
Solar/Wind Harmer
4.104
274724RIVER EC ;11
Adder
7.975
274814UNIV PK N;0U
Adder
2.265
274807UNIV PK N;3U
Adder
2.26
274811UNIV PK N;7U
Adder
2.245
276164X3-005 C
Solar/Wind Harmer
0.314
274803UNIV PARK;6U
Adder
2.586
274826FISK ;BP
Adder
4.847
972038AH1-567 GEN2
Adder
0.161
274887GEN-1.85
Solar/Wind Harmer
2.351
276772AC2-154 GEN
Solar/Wind Harmer
1.232
276843GEN-1.7
Solar/Wind Harmer
0.253
276806AD2-047 C O1
Solar/Wind Harmer
4.721
274772LINCOLN ;3U
Adder
2.735
961961AG1-039 GEN
Solar/Wind Harmer
1.257
23867002DVBSG1
50/50
12.566
24190002OREGON_ST1
50/50
3.44
24189802OREGON_CT1
50/50
2.611
23888802TROY G4
50/50
1.74
241996AE2-282_GEN
Solar/Wind Harmer
2.142
241808AF1-120 C
Solar/Wind Harmer
1.194
247522W1-056 GEN
Solar/Wind Harmer
1.591
944231AF1-091 GEN
Solar/Wind Harmer
11.674
247607V1-011 GEN
Solar/Wind Harmer
2.311
942801AE2-298 GEN
Solar/Wind Harmer
0.88
246937BC-WTG2
Solar/Wind Harmer
2.262
961051AF2-396 GEN
Solar/Wind Harmer
8.829
961051AF2-396 GEN
Solar/Wind Harmer
4.106
270246TR4_N_V150
Solar/Wind Harmer
0.459
270247TR4_N_V136
Solar/Wind Harmer
0.459
247620Y3-023
Adder
0.247
270462AD2-086
Solar/Wind Harmer
3.611
965681AG1-436 GEN
Solar/Wind Harmer
6.1
965791AG1-447 GEN
Solar/Wind Harmer
3.121
970349AG2-230 GEN
Solar/Wind Harmer
7.287
270535AF1-215 GEN1
Solar/Wind Harmer
2.088
270536AF1-215 GEN2
Solar/Wind Harmer
2.088
274805UNIV PK N;1U
Adder
2.25
274808UNIV PK N;4U
Adder
2.236
274888KELLY CRK;1U
Solar/Wind Harmer
2.604
276776AD2-060 GEN
Solar/Wind Harmer
0.185
958011AF2-095 GEN
Solar/Wind Harmer
6.355
970941AG2-585 GEN
Solar/Wind Harmer
2.427
274770LINCOLN ;1U
Adder
2.735
274771LINCOLN ;2U
Adder
2.735
942221AE2-234 GEN
Solar/Wind Harmer
1.537
23888502TROY G1
50/50
1.74
23888602TROY G2
50/50
1.74
23860102FRMENG 1
50/50
1.191
23860202FRMENG 2
50/50
1.191
241886AC2-103 GEN2
Solar/Wind Harmer
25.598
945411AF1-206 GEN
Solar/Wind Harmer
8.02
270361_3
Solar/Wind Harmer
8.586
270575GUS2 35KV
Solar/Wind Harmer
10.115
270499AE1-146 GEN
Solar/Wind Harmer
2.378
945641AF1-229 GEN
Solar/Wind Harmer
3.427
971549AH1-272 GEN
Solar/Wind Harmer
12.684
270404AC1-167 GEN
Solar/Wind Harmer
0.7
270428AC2-015 C
Solar/Wind Harmer
3.302
966831AG1-554 GEN
Solar/Wind Harmer
0.713
270007AE1-245 C
Solar/Wind Harmer
3.157
957201AF2-014 GEN
Solar/Wind Harmer
2.623
270435AC2-044 GEN
Solar/Wind Harmer
1.157
944161AF1-084 GEN
Solar/Wind Harmer
1.255
24191202EL_AA1-006
Adder
0.123
965041AG1-368 GEN
Solar/Wind Harmer
5.428
247521TR3_G114
Solar/Wind Harmer
1.815
270191TR4_S_V150
Solar/Wind Harmer
1.62
965051AG1-369 GEN
Solar/Wind Harmer
2.697
970031AG2-029 GEN
Solar/Wind Harmer
13.241
971771AH1-392 GEN
Solar/Wind Harmer
4.682
959331AF2-224 GEN
Solar/Wind Harmer
5.197
270302AB2-170 GEN
Solar/Wind Harmer
4.348
971567AH1-282 GEN
Solar/Wind Harmer
2.548
270526AF1-158 GEN
Solar/Wind Harmer
2.312
960681AF2-359 GEN
Solar/Wind Harmer
1.844
270223U2-072_GEN1
Solar/Wind Harmer
0.951
270224U2-072_GEN2
Solar/Wind Harmer
0.951
270227U2-072_GEN3
Solar/Wind Harmer
0.951
270228U2-072_GEN4
Solar/Wind Harmer
0.951
270231U2-072_GEN5
Solar/Wind Harmer
0.951
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
963791AG1-232 GEN
Solar/Wind Harmer
6.482
270377AD1-106 GEN
Solar/Wind Harmer
2.487
270071AF1-092 GEN
Solar/Wind Harmer
6.836
958391AF2-133 GEN
Solar/Wind Harmer
4.066
959141AF2-205 GEN
Solar/Wind Harmer
2.692
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.435
274800UNIV PARK;3U
Adder
2.577
274801UNIV PARK;4U
Adder
2.577
960591AF2-350 GEN
Solar/Wind Harmer
4.413
274775LINCOLN ;6U
Adder
2.735
274776LINCOLN ;7U
Adder
2.735
274777LINCOLN ;8U
Adder
2.735
972228AH1-698 GEN2
Adder
1.63
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.255
274687WILL CNTY;4U
Adder
12.255
274675JOLIET 29;7U
Adder
13.428
274675JOLIET 29;7U
Adder
12.949
276893AG1-478 C
Solar/Wind Harmer
0.24
274728ELWOOD EC;5P
Adder
7.182
274731ELWOOD EC;2P
Adder
7.182
274733ELWOOD EC;3P
Adder
7.182
274735ELWOOD EC;4P
Adder
7.182
970833AG2-524 GEN
Solar/Wind Harmer
3.795
970833AG2-524 GEN
Solar/Wind Harmer
1.765
274676JOLIET 29;8U
Adder
13.428
941551AE2-152 GEN
Solar/Wind Harmer
1.983
274732ELWOOD EC;7P
Adder
7.182
274674JOLIET 9 ;6U
Adder
6.727
274871GR RIDGE ;2U
Solar/Wind Harmer
3.341
274847GR RIDGE ;BU
Solar/Wind Harmer
2.197
270024AE2-089 GEN
Solar/Wind Harmer
2.026
274745AC1-111 GEN9
Adder
2.415
276694AA1-018 GEN2
Solar/Wind Harmer
2.724
276691AA1-018 GEN1
Solar/Wind Harmer
0.326
274861TOP CROP ;1U
Solar/Wind Harmer
2.615
203947AF1-006 C
Solar/Wind Helper
0.38
961971AG1-040 GEN
Solar/Wind Helper
0.333
203830AF1-094 GEN
Solar/Wind Helper
0.323
203979AG1-198 GEN
Solar/Wind Helper
0.194
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.076
276897AD1-100 C
Solar/Wind Harmer
20.311
276893AG1-478 C
Solar/Wind Harmer
0.192
274674JOLIET 9 ;6U
Adder
6.727
958481AF2-142 GEN
Solar/Wind Harmer
6.476
945421AF1-207 GEN
Solar/Wind Harmer
6.051
957841AF2-078 GEN
Solar/Wind Harmer
2.605
203835AF1-098 GEN
Solar/Wind Helper
1.314
241967AE2-285_GEN
Solar/Wind Helper
0.337
241801AE1-079 GEN
Solar/Wind Helper
0.132
254304AE2-114 C
Solar/Wind Helper
0.112
254305AE2-115 C
Solar/Wind Helper
0.112
962101AG1-054 GEN
Solar/Wind Helper
0.325
203804AE2-113_GEN
Solar/Wind Helper
0.862
940863AE2-074 GEN
Solar/Wind Helper
0.224
946381AF1-302 GEN
Solar/Wind Helper
0.105
274744AC1-111 GEN8
Adder
2.415
274746AC1-111 G10
Adder
2.415
241985AE1-237 GEN
Solar/Wind Helper
0.131
241982AE2-343 S C
Solar/Wind Helper
0.118
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.129
20334926Z1-069 C
Solar/Wind Helper
0.642
972259AH1-714 GEN
Adder
8.357
274676JOLIET 29;8U
Adder
12.949
939351AE1-166 GEN
Solar/Wind Harmer
2.593
274729ELWOOD EC;1P
Adder
7.182
274730ELWOOD EC;6P
Adder
7.182
274734ELWOOD EC;8P
Adder
7.182
274736ELWOOD EC;9P
Adder
7.182
970707AG2-453 GEN
Solar/Wind Harmer
12.232
943121AE2-341 GEN
Solar/Wind Harmer
6.478
943591AF1-030 GEN
Solar/Wind Harmer
4.319
274862TOP CROP ;2U
Solar/Wind Harmer
2.184
962511AG1-100 GEN
Solar/Wind Helper
0.34
990142J1224
External Queue
12.810073852539062
990527J1329
External Queue
1.7524040937423706
991182J1586 G
External Queue
23.964468002319336
991177J1571 G
External Queue
14.788094520568848
LAGNLTFEXP_LAGN->PJM
CLTF
4.778
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
TVALTFEXP_TVA->PJM
CLTF
2.168
NYPJM->LTFIMP_NY
CLTF
2.009
LGEELTFEXP_LGEE->PJM
CLTF
1.949
WECLTFEXP_WEC->PJM
CLTF
1.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.595
MECLTFEXP_MEC->PJM
CLTF
6.239
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
0.311
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.207

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-F1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.45 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2273.56
MW Contribution:
12.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.167
241832AE2-181_GEN
Solar/Wind Harmer
1.942
958321AF2-126 GEN
Solar/Wind Harmer
1.455
23906402RICHG1
Adder
1.309
23906502RICHG2&3
Adder
1.306
270541AE2-072 C
Solar/Wind Harmer
4.217
270044AE2-322 C
Solar/Wind Harmer
0.846
270588AE1-091_GEN
Solar/Wind Harmer
6.542
958091AF2-103 GEN
Solar/Wind Harmer
0.094
246938BC-WTG3
Solar/Wind Harmer
2.305
270491AE1-102 GEN2
Solar/Wind Harmer
0.753
24695305TIMB G C
Solar/Wind Harmer
1.865
945111AF1-176 GEN
Solar/Wind Harmer
3.154
270505AE1-170 C O1
Solar/Wind Harmer
8.36
270063AE2-323 C
Solar/Wind Harmer
1.181
247643Z2-116 C
Solar/Wind Harmer
0.037
965021AG1-366 GEN
Solar/Wind Harmer
1.216
24441505OLIV SLR
Solar/Wind Harmer
0.069
270043AE2-236 GEN
Solar/Wind Harmer
2.721
971347AH1-153 GEN
Solar/Wind Harmer
2.463
942871AE2-306 GEN
Solar/Wind Harmer
0.434
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
972231SS25-0005
Solar/Wind Harmer
4.365
972181SS23-001
Solar/Wind Harmer
2.728
274752CRETE EC ;2U
Adder
2.248
274753CRETE EC ;3U
Adder
2.248
964401AG1-302 GEN
Solar/Wind Harmer
4.157
274724RIVER EC ;11
Adder
8.079
274814UNIV PK N;0U
Adder
2.294
274807UNIV PK N;3U
Adder
2.289
274811UNIV PK N;7U
Adder
2.275
276164X3-005 C
Solar/Wind Harmer
0.318
274803UNIV PARK;6U
Adder
2.619
274826FISK ;BP
Adder
4.908
972038AH1-567 GEN2
Adder
0.163
274887GEN-1.85
Solar/Wind Harmer
2.381
276772AC2-154 GEN
Solar/Wind Harmer
1.247
276843GEN-1.7
Solar/Wind Harmer
0.256
276806AD2-047 C O1
Solar/Wind Harmer
4.781
274772LINCOLN ;3U
Adder
2.77
972259AH1-714 GEN
Adder
8.462
274676JOLIET 29;8U
Adder
13.112
939351AE1-166 GEN
Solar/Wind Harmer
2.626
274729ELWOOD EC;1P
Adder
7.272
274730ELWOOD EC;6P
Adder
7.272
274734ELWOOD EC;8P
Adder
7.272
274736ELWOOD EC;9P
Adder
7.272
970707AG2-453 GEN
Solar/Wind Harmer
12.386
23888502TROY G1
50/50
1.81
23888602TROY G2
50/50
1.81
241886AC2-103 GEN2
Solar/Wind Harmer
26.66
945411AF1-206 GEN
Solar/Wind Harmer
8.015
945641AF1-229 GEN
Solar/Wind Harmer
3.432
270361_3
Solar/Wind Harmer
7.834
270575GUS2 35KV
Solar/Wind Harmer
9.229
270499AE1-146 GEN
Solar/Wind Harmer
2.189
971549AH1-272 GEN
Solar/Wind Harmer
12.966
270404AC1-167 GEN
Solar/Wind Harmer
0.697
270007AE1-245 C
Solar/Wind Harmer
3.138
957201AF2-014 GEN
Solar/Wind Harmer
2.627
270435AC2-044 GEN
Solar/Wind Harmer
1.158
944161AF1-084 GEN
Solar/Wind Harmer
1.278
966831AG1-554 GEN
Solar/Wind Harmer
0.672
965041AG1-368 GEN
Solar/Wind Harmer
5.434
247521TR3_G114
Solar/Wind Harmer
1.815
270191TR4_S_V150
Solar/Wind Harmer
1.619
965051AG1-369 GEN
Solar/Wind Harmer
2.696
970031AG2-029 GEN
Solar/Wind Harmer
13.401
971771AH1-392 GEN
Solar/Wind Harmer
4.754
959331AF2-224 GEN
Solar/Wind Harmer
5.228
270526AF1-158 GEN
Solar/Wind Harmer
2.347
270302AB2-170 GEN
Solar/Wind Harmer
4.326
971567AH1-282 GEN
Solar/Wind Harmer
2.474
960681AF2-359 GEN
Solar/Wind Harmer
1.871
963791AG1-232 GEN
Solar/Wind Harmer
6.514
270223U2-072_GEN1
Solar/Wind Harmer
0.946
270224U2-072_GEN2
Solar/Wind Harmer
0.946
270227U2-072_GEN3
Solar/Wind Harmer
0.946
270228U2-072_GEN4
Solar/Wind Harmer
0.946
270231U2-072_GEN5
Solar/Wind Harmer
0.946
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270071AF1-092 GEN
Solar/Wind Harmer
6.892
958391AF2-133 GEN
Solar/Wind Harmer
4.118
959141AF2-205 GEN
Solar/Wind Harmer
2.726
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.479
274800UNIV PARK;3U
Adder
2.61
274801UNIV PARK;4U
Adder
2.61
960591AF2-350 GEN
Solar/Wind Harmer
4.469
274775LINCOLN ;6U
Adder
2.77
274776LINCOLN ;7U
Adder
2.77
274777LINCOLN ;8U
Adder
2.77
972228AH1-698 GEN2
Adder
1.651
972227AH1-698 GEN1
Adder
1.162
274687WILL CNTY;4U
Adder
12.41
274687WILL CNTY;4U
Adder
12.41
274675JOLIET 29;7U
Adder
13.598
274675JOLIET 29;7U
Adder
13.113
276893AG1-478 C
Solar/Wind Harmer
0.243
274728ELWOOD EC;5P
Adder
7.272
274731ELWOOD EC;2P
Adder
7.272
274733ELWOOD EC;3P
Adder
7.272
274735ELWOOD EC;4P
Adder
7.272
970833AG2-524 GEN
Solar/Wind Harmer
3.843
970833AG2-524 GEN
Solar/Wind Harmer
1.787
274744AC1-111 GEN8
Adder
2.445
274746AC1-111 G10
Adder
2.445
970073AG2-061 GEN
Solar/Wind Harmer
1.008
241985AE1-237 GEN
Solar/Wind Helper
0.13
241982AE2-343 S C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.129
20334926Z1-069 C
Solar/Wind Helper
0.637
23867002DVBSG1
50/50
13.959
24190002OREGON_ST1
50/50
3.615
24189802OREGON_CT1
50/50
2.744
23888802TROY G4
50/50
1.81
241996AE2-282_GEN
Solar/Wind Harmer
2.14
241808AF1-120 C
Solar/Wind Harmer
1.193
247522W1-056 GEN
Solar/Wind Harmer
1.482
944231AF1-091 GEN
Solar/Wind Harmer
11.706
247607V1-011 GEN
Solar/Wind Harmer
2.297
246937BC-WTG2
Solar/Wind Harmer
2.265
942801AE2-298 GEN
Solar/Wind Harmer
0.875
961051AF2-396 GEN
Solar/Wind Harmer
8.979
961051AF2-396 GEN
Solar/Wind Harmer
4.176
247620Y3-023
Adder
0.25
270246TR4_N_V150
Solar/Wind Harmer
0.459
270247TR4_N_V136
Solar/Wind Harmer
0.459
270462AD2-086
Solar/Wind Harmer
3.593
965681AG1-436 GEN
Solar/Wind Harmer
6.188
965791AG1-447 GEN
Solar/Wind Harmer
3.166
970349AG2-230 GEN
Solar/Wind Harmer
7.389
270535AF1-215 GEN1
Solar/Wind Harmer
2.116
270536AF1-215 GEN2
Solar/Wind Harmer
2.116
274805UNIV PK N;1U
Adder
2.28
274808UNIV PK N;4U
Adder
2.265
274888KELLY CRK;1U
Solar/Wind Harmer
2.637
276776AD2-060 GEN
Solar/Wind Harmer
0.187
958011AF2-095 GEN
Solar/Wind Harmer
6.436
970941AG2-585 GEN
Solar/Wind Harmer
2.458
274770LINCOLN ;1U
Adder
2.77
274771LINCOLN ;2U
Adder
2.77
276897AD1-100 C
Solar/Wind Harmer
20.566
276893AG1-478 C
Solar/Wind Harmer
0.194
274674JOLIET 9 ;6U
Adder
6.811
942221AE2-234 GEN
Solar/Wind Harmer
1.546
958481AF2-142 GEN
Solar/Wind Harmer
6.557
945421AF1-207 GEN
Solar/Wind Harmer
6.123
957841AF2-078 GEN
Solar/Wind Harmer
2.636
274696ROCKY RD ;4P
Adder
4.949
274695ROCKY RD ;2P
Adder
4.835
274693ROCKY RD ;1P
Adder
4.787
274697ROCKY RD ;3P
Adder
1.313
274683WAUKEGAN ;8U
Adder
9.145
274683WAUKEGAN ;8U
Adder
7.709
958491AF2-143 GEN
Solar/Wind Harmer
6.499
276901AD2-066 C O1
Solar/Wind Harmer
1.515
962691AG1-118 GEN
Solar/Wind Harmer
12.951
203835AF1-098 GEN
Solar/Wind Helper
1.301
241967AE2-285_GEN
Solar/Wind Helper
0.335
241801AE1-079 GEN
Solar/Wind Helper
0.131
254304AE2-114 C
Solar/Wind Helper
0.111
254305AE2-115 C
Solar/Wind Helper
0.111
962101AG1-054 GEN
Solar/Wind Helper
0.323
203804AE2-113_GEN
Solar/Wind Helper
0.855
940863AE2-074 GEN
Solar/Wind Helper
0.222
946381AF1-302 GEN
Solar/Wind Helper
0.104
24189902OREGON_CT2
50/50
2.687
23888702TROY G3
50/50
1.81
972253AH1-711 GEN
50/50
55.327
23856402BAYSG1
50/50
1.23
23920202STRYCT
50/50
1.893
241885AC2-103 GEN1
Solar/Wind Harmer
26.66
241858AF1-205_GEN
Solar/Wind Harmer
5.459
241840AF1-064_GEN
Solar/Wind Harmer
1.354
23906502RICHG2&3
Adder
1.306
960841AF2-375 GEN
Solar/Wind Harmer
3.481
270297AD1-101 GEN
Solar/Wind Harmer
1.363
270258AD1-119 GEN
Solar/Wind Harmer
1.257
24441205WTRV SLR C
Solar/Wind Harmer
0.08
246936BC-WTG1
Solar/Wind Harmer
2.265
270489AE1-102 GEN1
Solar/Wind Harmer
0.753
965421AG1-410 GEN
Solar/Wind Harmer
17.214
270449AD2-020 GEN
Solar/Wind Harmer
1.598
943021AE2-325 GEN
Solar/Wind Harmer
2.077
945111AF1-176 GEN
Solar/Wind Harmer
9.952
957891AF2-083 GEN
Solar/Wind Harmer
8.333
24639705ELKHART HY
Adder
0.083
270216AD2-079_GEN
Solar/Wind Harmer
0.324
965011AG1-365 GEN
Solar/Wind Harmer
5.228
270317AD1-130_GEN
Solar/Wind Harmer
1.654
270485AE1-090_GEN
Solar/Wind Harmer
0.312
270391AF1-285 GEN3
Solar/Wind Harmer
0.579
270578AF1-285 GEN2
Solar/Wind Harmer
0.579
970373AG2-245 GEN
Solar/Wind Harmer
9.962
270055AF2-134 C O1
Solar/Wind Harmer
1.41
274751CRETE EC ;1U
Adder
2.248
274754CRETE EC ;4U
Adder
2.248
958381AF2-132 GEN
Solar/Wind Harmer
4.157
964861AG1-349 GEN
Solar/Wind Harmer
3.596
971917AH1-482 GEN
Solar/Wind Harmer
4.149
274723RIVER EC ;12
Adder
8.176
274812UNIV PK N;8U
Adder
2.275
274802UNIV PARK;5U
Adder
2.619
940581AE2-045 GEN
Solar/Wind Harmer
4.558
971605AH1-302 GEN
Solar/Wind Harmer
3.897
972207SS24-0001
Solar/Wind Harmer
9.847
274773LINCOLN ;4U
Adder
2.77
274774LINCOLN ;5U
Adder
2.77
274676JOLIET 29;8U
Adder
13.598
941551AE2-152 GEN
Solar/Wind Harmer
2.008
274732ELWOOD EC;7P
Adder
7.272
274674JOLIET 9 ;6U
Adder
6.811
274871GR RIDGE ;2U
Solar/Wind Harmer
3.383
274847GR RIDGE ;BU
Solar/Wind Harmer
2.224
274745AC1-111 GEN9
Adder
2.445
276694AA1-018 GEN2
Solar/Wind Harmer
2.758
276691AA1-018 GEN1
Solar/Wind Harmer
0.33
274861TOP CROP ;1U
Solar/Wind Harmer
2.648
270024AE2-089 GEN
Solar/Wind Harmer
2.036
274682WAUKEGAN ;7U
Adder
7.807
274828WAUKEGAN ;BP
Adder
4.794
276805AD2-038 GEN
Solar/Wind Harmer
2.222
939401AE1-172 GEN
Solar/Wind Harmer
6.017
203947AF1-006 C
Solar/Wind Helper
0.376
961971AG1-040 GEN
Solar/Wind Helper
0.329
203830AF1-094 GEN
Solar/Wind Helper
0.319
203979AG1-198 GEN
Solar/Wind Helper
0.192
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
276882AE2-255 GEN
Solar/Wind Harmer
1.153
943121AE2-341 GEN
Solar/Wind Harmer
6.559
943591AF1-030 GEN
Solar/Wind Harmer
4.372
274862TOP CROP ;2U
Solar/Wind Harmer
2.211
274682WAUKEGAN ;7U
Adder
7.807
944531AF1-118 GEN
Solar/Wind Harmer
15.109
274879MINONK ;1U
Solar/Wind Harmer
2.907
962511AG1-100 GEN
Solar/Wind Helper
0.337
276868AE1-113 GEN
Solar/Wind Harmer
3.458
990142J1224
External Queue
13.296195983886719
990527J1329
External Queue
1.8189051151275635
991182J1586 G
External Queue
24.904010772705078
991177J1571 G
External Queue
15.21457576751709
LAGNLTFEXP_LAGN->PJM
CLTF
4.812
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.113
TVALTFEXP_TVA->PJM
CLTF
2.18
NYPJM->LTFIMP_NY
CLTF
1.997
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.62
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.638
MECLTFEXP_MEC->PJM
CLTF
6.308
SIGELTFEXP_SIGE->PJM
CLTF
0.163
CPLELTFEXP_CPLE->PJM
CLTF
0.312
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.504

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-12_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-12_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.45 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2273.56
MW Contribution:
12.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
1.81
23888602TROY G2
50/50
1.81
241886AC2-103 GEN2
Solar/Wind Harmer
26.66
945411AF1-206 GEN
Solar/Wind Harmer
8.015
945641AF1-229 GEN
Solar/Wind Harmer
3.432
270361_3
Solar/Wind Harmer
7.834
270575GUS2 35KV
Solar/Wind Harmer
9.229
270499AE1-146 GEN
Solar/Wind Harmer
2.189
971549AH1-272 GEN
Solar/Wind Harmer
12.966
270404AC1-167 GEN
Solar/Wind Harmer
0.697
270007AE1-245 C
Solar/Wind Harmer
3.138
957201AF2-014 GEN
Solar/Wind Harmer
2.627
270435AC2-044 GEN
Solar/Wind Harmer
1.158
944161AF1-084 GEN
Solar/Wind Harmer
1.278
966831AG1-554 GEN
Solar/Wind Harmer
0.672
965041AG1-368 GEN
Solar/Wind Harmer
5.434
247521TR3_G114
Solar/Wind Harmer
1.815
270191TR4_S_V150
Solar/Wind Harmer
1.619
965051AG1-369 GEN
Solar/Wind Harmer
2.696
970031AG2-029 GEN
Solar/Wind Harmer
13.401
971771AH1-392 GEN
Solar/Wind Harmer
4.754
959331AF2-224 GEN
Solar/Wind Harmer
5.228
270526AF1-158 GEN
Solar/Wind Harmer
2.347
270302AB2-170 GEN
Solar/Wind Harmer
4.326
971567AH1-282 GEN
Solar/Wind Harmer
2.474
960681AF2-359 GEN
Solar/Wind Harmer
1.871
963791AG1-232 GEN
Solar/Wind Harmer
6.514
270223U2-072_GEN1
Solar/Wind Harmer
0.946
270224U2-072_GEN2
Solar/Wind Harmer
0.946
270227U2-072_GEN3
Solar/Wind Harmer
0.946
23867002DVBSG1
50/50
13.959
24190002OREGON_ST1
50/50
3.615
24189802OREGON_CT1
50/50
2.744
23888802TROY G4
50/50
1.81
241996AE2-282_GEN
Solar/Wind Harmer
2.14
241808AF1-120 C
Solar/Wind Harmer
1.193
247522W1-056 GEN
Solar/Wind Harmer
1.482
944231AF1-091 GEN
Solar/Wind Harmer
11.706
247607V1-011 GEN
Solar/Wind Harmer
2.297
246937BC-WTG2
Solar/Wind Harmer
2.265
942801AE2-298 GEN
Solar/Wind Harmer
0.875
961051AF2-396 GEN
Solar/Wind Harmer
8.979
961051AF2-396 GEN
Solar/Wind Harmer
4.176
247620Y3-023
Adder
0.25
270246TR4_N_V150
Solar/Wind Harmer
0.459
270247TR4_N_V136
Solar/Wind Harmer
0.459
270462AD2-086
Solar/Wind Harmer
3.593
965681AG1-436 GEN
Solar/Wind Harmer
6.188
965791AG1-447 GEN
Solar/Wind Harmer
3.166
970349AG2-230 GEN
Solar/Wind Harmer
7.389
270535AF1-215 GEN1
Solar/Wind Harmer
2.116
270536AF1-215 GEN2
Solar/Wind Harmer
2.116
274805UNIV PK N;1U
Adder
2.28
274808UNIV PK N;4U
Adder
2.265
274888KELLY CRK;1U
Solar/Wind Harmer
2.637
276776AD2-060 GEN
Solar/Wind Harmer
0.187
958011AF2-095 GEN
Solar/Wind Harmer
6.436
970941AG2-585 GEN
Solar/Wind Harmer
2.458
274770LINCOLN ;1U
Adder
2.77
274771LINCOLN ;2U
Adder
2.77
276897AD1-100 C
Solar/Wind Harmer
20.566
276893AG1-478 C
Solar/Wind Harmer
0.194
274674JOLIET 9 ;6U
Adder
6.811
942221AE2-234 GEN
Solar/Wind Harmer
1.546
958481AF2-142 GEN
Solar/Wind Harmer
6.557
945421AF1-207 GEN
Solar/Wind Harmer
6.123
957841AF2-078 GEN
Solar/Wind Harmer
2.636
274696ROCKY RD ;4P
Adder
4.949
274695ROCKY RD ;2P
Adder
4.835
274693ROCKY RD ;1P
Adder
4.787
274697ROCKY RD ;3P
Adder
1.313
274683WAUKEGAN ;8U
Adder
9.145
274683WAUKEGAN ;8U
Adder
7.709
958491AF2-143 GEN
Solar/Wind Harmer
6.499
276901AD2-066 C O1
Solar/Wind Harmer
1.515
962691AG1-118 GEN
Solar/Wind Harmer
12.951
203835AF1-098 GEN
Solar/Wind Helper
1.301
241967AE2-285_GEN
Solar/Wind Helper
0.335
241801AE1-079 GEN
Solar/Wind Helper
0.131
254304AE2-114 C
Solar/Wind Helper
0.111
254305AE2-115 C
Solar/Wind Helper
0.111
962101AG1-054 GEN
Solar/Wind Helper
0.323
203804AE2-113_GEN
Solar/Wind Helper
0.855
24189902OREGON_CT2
50/50
2.687
23888702TROY G3
50/50
1.81
972253AH1-711 GEN
50/50
55.327
23856402BAYSG1
50/50
1.23
23920202STRYCT
50/50
1.893
241885AC2-103 GEN1
Solar/Wind Harmer
26.66
241858AF1-205_GEN
Solar/Wind Harmer
5.459
241840AF1-064_GEN
Solar/Wind Harmer
1.354
23906502RICHG2&3
Adder
1.306
960841AF2-375 GEN
Solar/Wind Harmer
3.481
270297AD1-101 GEN
Solar/Wind Harmer
1.363
270258AD1-119 GEN
Solar/Wind Harmer
1.257
24441205WTRV SLR C
Solar/Wind Harmer
0.08
246936BC-WTG1
Solar/Wind Harmer
2.265
270489AE1-102 GEN1
Solar/Wind Harmer
0.753
965421AG1-410 GEN
Solar/Wind Harmer
17.214
270449AD2-020 GEN
Solar/Wind Harmer
1.598
943021AE2-325 GEN
Solar/Wind Harmer
2.077
945111AF1-176 GEN
Solar/Wind Harmer
9.952
957891AF2-083 GEN
Solar/Wind Harmer
8.333
24639705ELKHART HY
Adder
0.083
270216AD2-079_GEN
Solar/Wind Harmer
0.324
965011AG1-365 GEN
Solar/Wind Harmer
5.228
270317AD1-130_GEN
Solar/Wind Harmer
1.654
270485AE1-090_GEN
Solar/Wind Harmer
0.312
270391AF1-285 GEN3
Solar/Wind Harmer
0.579
270578AF1-285 GEN2
Solar/Wind Harmer
0.579
23929302BS-PKR
50/50
2.167
241832AE2-181_GEN
Solar/Wind Harmer
1.942
958321AF2-126 GEN
Solar/Wind Harmer
1.455
23906402RICHG1
Adder
1.309
23906502RICHG2&3
Adder
1.306
270541AE2-072 C
Solar/Wind Harmer
4.217
270044AE2-322 C
Solar/Wind Harmer
0.846
270588AE1-091_GEN
Solar/Wind Harmer
6.542
958091AF2-103 GEN
Solar/Wind Harmer
0.094
246938BC-WTG3
Solar/Wind Harmer
2.305
270491AE1-102 GEN2
Solar/Wind Harmer
0.753
24695305TIMB G C
Solar/Wind Harmer
1.865
945111AF1-176 GEN
Solar/Wind Harmer
3.154
270505AE1-170 C O1
Solar/Wind Harmer
8.36
270063AE2-323 C
Solar/Wind Harmer
1.181
247643Z2-116 C
Solar/Wind Harmer
0.037
965021AG1-366 GEN
Solar/Wind Harmer
1.216
24441505OLIV SLR
Solar/Wind Harmer
0.069
270043AE2-236 GEN
Solar/Wind Harmer
2.721
971347AH1-153 GEN
Solar/Wind Harmer
2.463
942871AE2-306 GEN
Solar/Wind Harmer
0.434
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
972231SS25-0005
Solar/Wind Harmer
4.365
972181SS23-001
Solar/Wind Harmer
2.728
274752CRETE EC ;2U
Adder
2.248
274753CRETE EC ;3U
Adder
2.248
964401AG1-302 GEN
Solar/Wind Harmer
4.157
274724RIVER EC ;11
Adder
8.079
274814UNIV PK N;0U
Adder
2.294
274807UNIV PK N;3U
Adder
2.289
274811UNIV PK N;7U
Adder
2.275
276164X3-005 C
Solar/Wind Harmer
0.318
274803UNIV PARK;6U
Adder
2.619
274826FISK ;BP
Adder
4.908
970373AG2-245 GEN
Solar/Wind Harmer
9.962
270055AF2-134 C O1
Solar/Wind Harmer
1.41
274751CRETE EC ;1U
Adder
2.248
274754CRETE EC ;4U
Adder
2.248
958381AF2-132 GEN
Solar/Wind Harmer
4.157
964861AG1-349 GEN
Solar/Wind Harmer
3.596
971917AH1-482 GEN
Solar/Wind Harmer
4.149
274723RIVER EC ;12
Adder
8.176
274812UNIV PK N;8U
Adder
2.275
274802UNIV PARK;5U
Adder
2.619
940581AE2-045 GEN
Solar/Wind Harmer
4.558
971605AH1-302 GEN
Solar/Wind Harmer
3.897
972207SS24-0001
Solar/Wind Harmer
9.847
274773LINCOLN ;4U
Adder
2.77
274774LINCOLN ;5U
Adder
2.77
274676JOLIET 29;8U
Adder
13.598
941551AE2-152 GEN
Solar/Wind Harmer
2.008
274732ELWOOD EC;7P
Adder
7.272
274674JOLIET 9 ;6U
Adder
6.811
274871GR RIDGE ;2U
Solar/Wind Harmer
3.383
274847GR RIDGE ;BU
Solar/Wind Harmer
2.224
274745AC1-111 GEN9
Adder
2.445
276694AA1-018 GEN2
Solar/Wind Harmer
2.758
276691AA1-018 GEN1
Solar/Wind Harmer
0.33
274861TOP CROP ;1U
Solar/Wind Harmer
2.648
270024AE2-089 GEN
Solar/Wind Harmer
2.036
274682WAUKEGAN ;7U
Adder
7.807
274828WAUKEGAN ;BP
Adder
4.794
276805AD2-038 GEN
Solar/Wind Harmer
2.222
939401AE1-172 GEN
Solar/Wind Harmer
6.017
203947AF1-006 C
Solar/Wind Helper
0.376
961971AG1-040 GEN
Solar/Wind Helper
0.329
203830AF1-094 GEN
Solar/Wind Helper
0.319
203979AG1-198 GEN
Solar/Wind Helper
0.192
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
276882AE2-255 GEN
Solar/Wind Harmer
1.153
972038AH1-567 GEN2
Adder
0.163
274887GEN-1.85
Solar/Wind Harmer
2.381
276772AC2-154 GEN
Solar/Wind Harmer
1.247
276843GEN-1.7
Solar/Wind Harmer
0.256
276806AD2-047 C O1
Solar/Wind Harmer
4.781
274772LINCOLN ;3U
Adder
2.77
972259AH1-714 GEN
Adder
8.462
274676JOLIET 29;8U
Adder
13.112
939351AE1-166 GEN
Solar/Wind Harmer
2.626
274729ELWOOD EC;1P
Adder
7.272
274730ELWOOD EC;6P
Adder
7.272
274734ELWOOD EC;8P
Adder
7.272
274736ELWOOD EC;9P
Adder
7.272
970707AG2-453 GEN
Solar/Wind Harmer
12.386
943121AE2-341 GEN
Solar/Wind Harmer
6.559
943591AF1-030 GEN
Solar/Wind Harmer
4.372
274862TOP CROP ;2U
Solar/Wind Harmer
2.211
274682WAUKEGAN ;7U
Adder
7.807
944531AF1-118 GEN
Solar/Wind Harmer
15.109
274879MINONK ;1U
Solar/Wind Harmer
2.907
962511AG1-100 GEN
Solar/Wind Helper
0.337
276868AE1-113 GEN
Solar/Wind Harmer
3.458
940863AE2-074 GEN
Solar/Wind Helper
0.222
946381AF1-302 GEN
Solar/Wind Helper
0.104
270228U2-072_GEN4
Solar/Wind Harmer
0.946
270231U2-072_GEN5
Solar/Wind Harmer
0.946
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270071AF1-092 GEN
Solar/Wind Harmer
6.892
958391AF2-133 GEN
Solar/Wind Harmer
4.118
959141AF2-205 GEN
Solar/Wind Harmer
2.726
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.479
274800UNIV PARK;3U
Adder
2.61
274801UNIV PARK;4U
Adder
2.61
960591AF2-350 GEN
Solar/Wind Harmer
4.469
274775LINCOLN ;6U
Adder
2.77
274776LINCOLN ;7U
Adder
2.77
274777LINCOLN ;8U
Adder
2.77
972228AH1-698 GEN2
Adder
1.651
972227AH1-698 GEN1
Adder
1.162
274687WILL CNTY;4U
Adder
12.41
274687WILL CNTY;4U
Adder
12.41
274675JOLIET 29;7U
Adder
13.598
274675JOLIET 29;7U
Adder
13.113
276893AG1-478 C
Solar/Wind Harmer
0.243
274728ELWOOD EC;5P
Adder
7.272
274731ELWOOD EC;2P
Adder
7.272
274733ELWOOD EC;3P
Adder
7.272
274735ELWOOD EC;4P
Adder
7.272
970833AG2-524 GEN
Solar/Wind Harmer
3.843
970833AG2-524 GEN
Solar/Wind Harmer
1.787
274744AC1-111 GEN8
Adder
2.445
274746AC1-111 G10
Adder
2.445
970073AG2-061 GEN
Solar/Wind Harmer
1.008
241985AE1-237 GEN
Solar/Wind Helper
0.13
241982AE2-343 S C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.129
20334926Z1-069 C
Solar/Wind Helper
0.637
990142J1224
External Queue
13.296195983886719
990527J1329
External Queue
1.8189051151275635
991182J1586 G
External Queue
24.904010772705078
991177J1571 G
External Queue
15.21457576751709
LAGNLTFEXP_LAGN->PJM
CLTF
4.812
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.113
TVALTFEXP_TVA->PJM
CLTF
2.18
NYPJM->LTFIMP_NY
CLTF
1.997
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.62
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.638
MECLTFEXP_MEC->PJM
CLTF
6.308
SIGELTFEXP_SIGE->PJM
CLTF
0.163
CPLELTFEXP_CPLE->PJM
CLTF
0.312
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.504

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.38 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2200.39
MW Contribution:
12.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.264
241832AE2-181_GEN
Solar/Wind Harmer
1.953
958321AF2-126 GEN
Solar/Wind Harmer
1.492
23906402RICHG1
Adder
1.32
23906502RICHG2&3
Adder
1.318
270541AE2-072 C
Solar/Wind Harmer
4.314
270044AE2-322 C
Solar/Wind Harmer
0.852
270588AE1-091_GEN
Solar/Wind Harmer
6.794
958091AF2-103 GEN
Solar/Wind Harmer
0.095
246938BC-WTG3
Solar/Wind Harmer
2.31
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
24695305TIMB G C
Solar/Wind Harmer
1.875
945111AF1-176 GEN
Solar/Wind Harmer
3.125
270505AE1-170 C O1
Solar/Wind Harmer
8.281
270063AE2-323 C
Solar/Wind Harmer
1.174
247643Z2-116 C
Solar/Wind Harmer
0.037
965021AG1-366 GEN
Solar/Wind Harmer
1.214
24441505OLIV SLR
Solar/Wind Harmer
0.068
270043AE2-236 GEN
Solar/Wind Harmer
2.71
23888502TROY G1
50/50
1.762
23888602TROY G2
50/50
1.762
241886AC2-103 GEN2
Solar/Wind Harmer
25.89
945411AF1-206 GEN
Solar/Wind Harmer
8.063
270361_3
Solar/Wind Harmer
8.481
270575GUS2 35KV
Solar/Wind Harmer
9.992
945641AF1-229 GEN
Solar/Wind Harmer
3.434
270499AE1-146 GEN
Solar/Wind Harmer
2.352
971549AH1-272 GEN
Solar/Wind Harmer
12.792
270404AC1-167 GEN
Solar/Wind Harmer
0.703
966831AG1-554 GEN
Solar/Wind Harmer
0.706
270007AE1-245 C
Solar/Wind Harmer
3.165
957201AF2-014 GEN
Solar/Wind Harmer
2.632
270435AC2-044 GEN
Solar/Wind Harmer
1.161
944161AF1-084 GEN
Solar/Wind Harmer
1.265
270428AC2-015 C
Solar/Wind Harmer
3.087
965041AG1-368 GEN
Solar/Wind Harmer
5.449
247521TR3_G114
Solar/Wind Harmer
1.821
270191TR4_S_V150
Solar/Wind Harmer
1.625
965051AG1-369 GEN
Solar/Wind Harmer
2.706
970031AG2-029 GEN
Solar/Wind Harmer
13.32
971771AH1-392 GEN
Solar/Wind Harmer
4.713
959331AF2-224 GEN
Solar/Wind Harmer
5.221
270302AB2-170 GEN
Solar/Wind Harmer
4.356
270526AF1-158 GEN
Solar/Wind Harmer
2.327
971567AH1-282 GEN
Solar/Wind Harmer
2.521
960681AF2-359 GEN
Solar/Wind Harmer
1.856
270223U2-072_GEN1
Solar/Wind Harmer
0.953
270224U2-072_GEN2
Solar/Wind Harmer
0.953
270227U2-072_GEN3
Solar/Wind Harmer
0.953
270228U2-072_GEN4
Solar/Wind Harmer
0.953
270231U2-072_GEN5
Solar/Wind Harmer
0.953
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
963791AG1-232 GEN
Solar/Wind Harmer
6.51
270377AD1-106 GEN
Solar/Wind Harmer
2.438
270071AF1-092 GEN
Solar/Wind Harmer
6.869
958391AF2-133 GEN
Solar/Wind Harmer
4.09
959141AF2-205 GEN
Solar/Wind Harmer
2.708
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.455
274800UNIV PARK;3U
Adder
2.592
274801UNIV PARK;4U
Adder
2.592
960591AF2-350 GEN
Solar/Wind Harmer
4.439
274775LINCOLN ;6U
Adder
2.751
274776LINCOLN ;7U
Adder
2.751
274777LINCOLN ;8U
Adder
2.751
972228AH1-698 GEN2
Adder
1.639
972227AH1-698 GEN1
Adder
1.154
274687WILL CNTY;4U
Adder
12.327
274687WILL CNTY;4U
Adder
12.327
274675JOLIET 29;7U
Adder
13.507
274675JOLIET 29;7U
Adder
13.024
276893AG1-478 C
Solar/Wind Harmer
0.242
274728ELWOOD EC;5P
Adder
7.224
274731ELWOOD EC;2P
Adder
7.224
274733ELWOOD EC;3P
Adder
7.224
274735ELWOOD EC;4P
Adder
7.224
970833AG2-524 GEN
Solar/Wind Harmer
3.817
970833AG2-524 GEN
Solar/Wind Harmer
1.776
274744AC1-111 GEN8
Adder
2.429
274746AC1-111 G10
Adder
2.429
24189902OREGON_CT2
50/50
2.594
23888702TROY G3
50/50
1.762
972253AH1-711 GEN
50/50
53.873
23856402BAYSG1
50/50
1.285
23920202STRYCT
50/50
1.905
241885AC2-103 GEN1
Solar/Wind Harmer
25.89
241858AF1-205_GEN
Solar/Wind Harmer
5.5
241840AF1-064_GEN
Solar/Wind Harmer
1.388
23906502RICHG2&3
Adder
1.318
960841AF2-375 GEN
Solar/Wind Harmer
3.757
241807AE2-176_GEN
Solar/Wind Harmer
2.779
270297AD1-101 GEN
Solar/Wind Harmer
1.388
270258AD1-119 GEN
Solar/Wind Harmer
1.266
24441205WTRV SLR C
Solar/Wind Harmer
0.08
246936BC-WTG1
Solar/Wind Harmer
2.27
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.245
270449AD2-020 GEN
Solar/Wind Harmer
1.582
943021AE2-325 GEN
Solar/Wind Harmer
2.056
945111AF1-176 GEN
Solar/Wind Harmer
9.859
957891AF2-083 GEN
Solar/Wind Harmer
8.254
24639705ELKHART HY
Adder
0.082
270216AD2-079_GEN
Solar/Wind Harmer
0.322
965011AG1-365 GEN
Solar/Wind Harmer
5.221
270317AD1-130_GEN
Solar/Wind Harmer
1.665
270485AE1-090_GEN
Solar/Wind Harmer
0.315
270391AF1-285 GEN3
Solar/Wind Harmer
0.584
270578AF1-285 GEN2
Solar/Wind Harmer
0.584
970373AG2-245 GEN
Solar/Wind Harmer
9.888
270055AF2-134 C O1
Solar/Wind Harmer
1.4
274751CRETE EC ;1U
Adder
2.232
274754CRETE EC ;4U
Adder
2.232
958381AF2-132 GEN
Solar/Wind Harmer
4.128
964861AG1-349 GEN
Solar/Wind Harmer
3.571
971917AH1-482 GEN
Solar/Wind Harmer
4.12
274723RIVER EC ;12
Adder
8.119
274812UNIV PK N;8U
Adder
2.259
274802UNIV PARK;5U
Adder
2.601
940581AE2-045 GEN
Solar/Wind Harmer
4.528
971605AH1-302 GEN
Solar/Wind Harmer
3.872
972207SS24-0001
Solar/Wind Harmer
9.781
274773LINCOLN ;4U
Adder
2.751
274774LINCOLN ;5U
Adder
2.751
274676JOLIET 29;8U
Adder
13.507
941551AE2-152 GEN
Solar/Wind Harmer
1.994
274732ELWOOD EC;7P
Adder
7.224
274674JOLIET 9 ;6U
Adder
6.766
274871GR RIDGE ;2U
Solar/Wind Harmer
3.36
274847GR RIDGE ;BU
Solar/Wind Harmer
2.209
274745AC1-111 GEN9
Adder
2.429
276694AA1-018 GEN2
Solar/Wind Harmer
2.74
276691AA1-018 GEN1
Solar/Wind Harmer
0.328
274861TOP CROP ;1U
Solar/Wind Harmer
2.63
270024AE2-089 GEN
Solar/Wind Harmer
2.035
23867002DVBSG1
50/50
12.889
24190002OREGON_ST1
50/50
3.49
24189802OREGON_CT1
50/50
2.649
23888802TROY G4
50/50
1.762
241996AE2-282_GEN
Solar/Wind Harmer
2.153
241808AF1-120 C
Solar/Wind Harmer
1.201
247522W1-056 GEN
Solar/Wind Harmer
1.573
944231AF1-091 GEN
Solar/Wind Harmer
11.729
247607V1-011 GEN
Solar/Wind Harmer
2.317
942801AE2-298 GEN
Solar/Wind Harmer
0.882
246937BC-WTG2
Solar/Wind Harmer
2.27
961051AF2-396 GEN
Solar/Wind Harmer
8.892
961051AF2-396 GEN
Solar/Wind Harmer
4.136
270246TR4_N_V150
Solar/Wind Harmer
0.461
270247TR4_N_V136
Solar/Wind Harmer
0.461
247620Y3-023
Adder
0.249
270462AD2-086
Solar/Wind Harmer
3.618
965681AG1-436 GEN
Solar/Wind Harmer
6.138
965791AG1-447 GEN
Solar/Wind Harmer
3.141
970349AG2-230 GEN
Solar/Wind Harmer
7.333
270535AF1-215 GEN1
Solar/Wind Harmer
2.101
270536AF1-215 GEN2
Solar/Wind Harmer
2.101
274805UNIV PK N;1U
Adder
2.264
274808UNIV PK N;4U
Adder
2.249
274888KELLY CRK;1U
Solar/Wind Harmer
2.62
276776AD2-060 GEN
Solar/Wind Harmer
0.186
958011AF2-095 GEN
Solar/Wind Harmer
6.392
970941AG2-585 GEN
Solar/Wind Harmer
2.442
274770LINCOLN ;1U
Adder
2.751
274771LINCOLN ;2U
Adder
2.751
942221AE2-234 GEN
Solar/Wind Harmer
1.544
276897AD1-100 C
Solar/Wind Harmer
20.429
276893AG1-478 C
Solar/Wind Harmer
0.193
274674JOLIET 9 ;6U
Adder
6.766
958481AF2-142 GEN
Solar/Wind Harmer
6.514
971347AH1-153 GEN
Solar/Wind Harmer
2.444
942871AE2-306 GEN
Solar/Wind Harmer
0.438
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
972231SS25-0005
Solar/Wind Harmer
4.334
972181SS23-001
Solar/Wind Harmer
2.709
274752CRETE EC ;2U
Adder
2.232
274753CRETE EC ;3U
Adder
2.232
964401AG1-302 GEN
Solar/Wind Harmer
4.128
274724RIVER EC ;11
Adder
8.023
274814UNIV PK N;0U
Adder
2.279
274807UNIV PK N;3U
Adder
2.274
274811UNIV PK N;7U
Adder
2.259
276164X3-005 C
Solar/Wind Harmer
0.316
274803UNIV PARK;6U
Adder
2.601
274826FISK ;BP
Adder
4.875
972038AH1-567 GEN2
Adder
0.162
274887GEN-1.85
Solar/Wind Harmer
2.365
276772AC2-154 GEN
Solar/Wind Harmer
1.239
276843GEN-1.7
Solar/Wind Harmer
0.254
276806AD2-047 C O1
Solar/Wind Harmer
4.749
274772LINCOLN ;3U
Adder
2.751
972259AH1-714 GEN
Adder
8.406
274676JOLIET 29;8U
Adder
13.024
939351AE1-166 GEN
Solar/Wind Harmer
2.608
274729ELWOOD EC;1P
Adder
7.224
274730ELWOOD EC;6P
Adder
7.224
274734ELWOOD EC;8P
Adder
7.224
274736ELWOOD EC;9P
Adder
7.224
970707AG2-453 GEN
Solar/Wind Harmer
12.303
943121AE2-341 GEN
Solar/Wind Harmer
6.515
943591AF1-030 GEN
Solar/Wind Harmer
4.344
274862TOP CROP ;2U
Solar/Wind Harmer
2.196
274682WAUKEGAN ;7U
Adder
7.755
944531AF1-118 GEN
Solar/Wind Harmer
15.071
962511AG1-100 GEN
Solar/Wind Helper
0.34
970073AG2-061 GEN
Solar/Wind Harmer
1.001
241985AE1-237 GEN
Solar/Wind Helper
0.131
241982AE2-343 S C
Solar/Wind Helper
0.118
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.13
20334926Z1-069 C
Solar/Wind Helper
0.642
945421AF1-207 GEN
Solar/Wind Harmer
6.085
957841AF2-078 GEN
Solar/Wind Harmer
2.619
274696ROCKY RD ;4P
Adder
4.916
274695ROCKY RD ;2P
Adder
4.803
274693ROCKY RD ;1P
Adder
4.756
274697ROCKY RD ;3P
Adder
1.305
274683WAUKEGAN ;8U
Adder
9.085
274683WAUKEGAN ;8U
Adder
7.658
958491AF2-143 GEN
Solar/Wind Harmer
6.456
203835AF1-098 GEN
Solar/Wind Helper
1.314
241967AE2-285_GEN
Solar/Wind Helper
0.337
241801AE1-079 GEN
Solar/Wind Helper
0.132
254304AE2-114 C
Solar/Wind Helper
0.112
254305AE2-115 C
Solar/Wind Helper
0.112
962101AG1-054 GEN
Solar/Wind Helper
0.326
203804AE2-113_GEN
Solar/Wind Helper
0.862
940863AE2-074 GEN
Solar/Wind Helper
0.224
946381AF1-302 GEN
Solar/Wind Helper
0.105
274682WAUKEGAN ;7U
Adder
7.755
274828WAUKEGAN ;BP
Adder
4.762
276805AD2-038 GEN
Solar/Wind Harmer
2.207
203947AF1-006 C
Solar/Wind Helper
0.379
961971AG1-040 GEN
Solar/Wind Helper
0.333
203830AF1-094 GEN
Solar/Wind Helper
0.323
203979AG1-198 GEN
Solar/Wind Helper
0.194
241966AE1-183 GEN
Solar/Wind Helper
0.13
254303AC2-168 GEN
Solar/Wind Helper
0.076
990142J1224
External Queue
12.977669715881348
990527J1329
External Queue
1.7753312587738037
991182J1586 G
External Queue
24.28106117248535
991177J1571 G
External Queue
14.958016395568848
LAGNLTFEXP_LAGN->PJM
CLTF
4.796
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
TVALTFEXP_TVA->PJM
CLTF
2.175
NYPJM->LTFIMP_NY
CLTF
2.012
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.294
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.622
MECLTFEXP_MEC->PJM
CLTF
6.272
SIGELTFEXP_SIGE->PJM
CLTF
0.163
CPLELTFEXP_CPLE->PJM
CLTF
0.309
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.366

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B2_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B2_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.29 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2144.77
MW Contribution:
12.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.125
241832AE2-181_GEN
Solar/Wind Harmer
1.915
958321AF2-126 GEN
Solar/Wind Harmer
1.431
23906402RICHG1
Adder
1.29
23906502RICHG2&3
Adder
1.287
270541AE2-072 C
Solar/Wind Harmer
4.149
270044AE2-322 C
Solar/Wind Harmer
0.834
270588AE1-091_GEN
Solar/Wind Harmer
6.423
958091AF2-103 GEN
Solar/Wind Harmer
0.093
246938BC-WTG3
Solar/Wind Harmer
2.274
270491AE1-102 GEN2
Solar/Wind Harmer
0.743
945111AF1-176 GEN
Solar/Wind Harmer
3.116
24695305TIMB G C
Solar/Wind Harmer
1.839
270505AE1-170 C O1
Solar/Wind Harmer
8.26
270063AE2-323 C
Solar/Wind Harmer
1.166
247643Z2-116 C
Solar/Wind Harmer
0.037
965021AG1-366 GEN
Solar/Wind Harmer
1.2
24441505OLIV SLR
Solar/Wind Harmer
0.068
270043AE2-236 GEN
Solar/Wind Harmer
2.686
971347AH1-153 GEN
Solar/Wind Harmer
2.433
942871AE2-306 GEN
Solar/Wind Harmer
0.428
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
972231SS25-0005
Solar/Wind Harmer
4.311
972181SS23-001
Solar/Wind Harmer
2.694
274752CRETE EC ;2U
Adder
2.22
274753CRETE EC ;3U
Adder
2.22
964401AG1-302 GEN
Solar/Wind Harmer
4.106
274724RIVER EC ;11
Adder
7.979
274814UNIV PK N;0U
Adder
2.266
274807UNIV PK N;3U
Adder
2.261
274811UNIV PK N;7U
Adder
2.247
276164X3-005 C
Solar/Wind Harmer
0.314
23888502TROY G1
50/50
1.792
23888602TROY G2
50/50
1.792
241886AC2-103 GEN2
Solar/Wind Harmer
26.727
945411AF1-206 GEN
Solar/Wind Harmer
7.903
945641AF1-229 GEN
Solar/Wind Harmer
3.386
270361_3
Solar/Wind Harmer
7.648
270575GUS2 35KV
Solar/Wind Harmer
9.01
270499AE1-146 GEN
Solar/Wind Harmer
2.139
971549AH1-272 GEN
Solar/Wind Harmer
12.817
270404AC1-167 GEN
Solar/Wind Harmer
0.687
270007AE1-245 C
Solar/Wind Harmer
3.093
944161AF1-084 GEN
Solar/Wind Harmer
1.262
957201AF2-014 GEN
Solar/Wind Harmer
2.591
270435AC2-044 GEN
Solar/Wind Harmer
1.143
966831AG1-554 GEN
Solar/Wind Harmer
0.658
965041AG1-368 GEN
Solar/Wind Harmer
5.361
247521TR3_G114
Solar/Wind Harmer
1.79
270191TR4_S_V150
Solar/Wind Harmer
1.597
965051AG1-369 GEN
Solar/Wind Harmer
2.66
970031AG2-029 GEN
Solar/Wind Harmer
13.234
971771AH1-392 GEN
Solar/Wind Harmer
4.696
959331AF2-224 GEN
Solar/Wind Harmer
5.16
270526AF1-158 GEN
Solar/Wind Harmer
2.319
270302AB2-170 GEN
Solar/Wind Harmer
4.265
960681AF2-359 GEN
Solar/Wind Harmer
1.848
971567AH1-282 GEN
Solar/Wind Harmer
2.435
963791AG1-232 GEN
Solar/Wind Harmer
6.428
270223U2-072_GEN1
Solar/Wind Harmer
0.932
270224U2-072_GEN2
Solar/Wind Harmer
0.932
270227U2-072_GEN3
Solar/Wind Harmer
0.932
270228U2-072_GEN4
Solar/Wind Harmer
0.932
270231U2-072_GEN5
Solar/Wind Harmer
0.932
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270071AF1-092 GEN
Solar/Wind Harmer
6.804
958391AF2-133 GEN
Solar/Wind Harmer
4.068
959141AF2-205 GEN
Solar/Wind Harmer
2.693
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.436
274800UNIV PARK;3U
Adder
2.578
274801UNIV PARK;4U
Adder
2.578
960591AF2-350 GEN
Solar/Wind Harmer
4.414
274775LINCOLN ;6U
Adder
2.735
274776LINCOLN ;7U
Adder
2.735
274777LINCOLN ;8U
Adder
2.735
972228AH1-698 GEN2
Adder
1.63
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.257
274687WILL CNTY;4U
Adder
12.257
274675JOLIET 29;7U
Adder
13.43
274675JOLIET 29;7U
Adder
12.951
276893AG1-478 C
Solar/Wind Harmer
0.24
23867002DVBSG1
50/50
13.913
24190002OREGON_ST1
50/50
3.583
24189802OREGON_CT1
50/50
2.72
23888802TROY G4
50/50
1.792
241996AE2-282_GEN
Solar/Wind Harmer
2.11
241808AF1-120 C
Solar/Wind Harmer
1.177
247522W1-056 GEN
Solar/Wind Harmer
1.451
944231AF1-091 GEN
Solar/Wind Harmer
11.549
247607V1-011 GEN
Solar/Wind Harmer
2.265
246937BC-WTG2
Solar/Wind Harmer
2.235
942801AE2-298 GEN
Solar/Wind Harmer
0.862
961051AF2-396 GEN
Solar/Wind Harmer
8.871
961051AF2-396 GEN
Solar/Wind Harmer
4.126
247620Y3-023
Adder
0.247
270246TR4_N_V150
Solar/Wind Harmer
0.453
270247TR4_N_V136
Solar/Wind Harmer
0.453
270462AD2-086
Solar/Wind Harmer
3.542
965681AG1-436 GEN
Solar/Wind Harmer
6.113
965791AG1-447 GEN
Solar/Wind Harmer
3.127
970349AG2-230 GEN
Solar/Wind Harmer
7.299
270535AF1-215 GEN1
Solar/Wind Harmer
2.09
270536AF1-215 GEN2
Solar/Wind Harmer
2.09
274805UNIV PK N;1U
Adder
2.251
274808UNIV PK N;4U
Adder
2.237
274888KELLY CRK;1U
Solar/Wind Harmer
2.605
276776AD2-060 GEN
Solar/Wind Harmer
0.185
958011AF2-095 GEN
Solar/Wind Harmer
6.357
970941AG2-585 GEN
Solar/Wind Harmer
2.428
274770LINCOLN ;1U
Adder
2.735
274771LINCOLN ;2U
Adder
2.735
276897AD1-100 C
Solar/Wind Harmer
20.312
274803UNIV PARK;6U
Adder
2.586
274826FISK ;BP
Adder
4.848
972038AH1-567 GEN2
Adder
0.161
274887GEN-1.85
Solar/Wind Harmer
2.352
276772AC2-154 GEN
Solar/Wind Harmer
1.232
276843GEN-1.7
Solar/Wind Harmer
0.253
276806AD2-047 C O1
Solar/Wind Harmer
4.722
274772LINCOLN ;3U
Adder
2.735
972259AH1-714 GEN
Adder
8.358
274676JOLIET 29;8U
Adder
12.951
939351AE1-166 GEN
Solar/Wind Harmer
2.593
24189902OREGON_CT2
50/50
2.663
23888702TROY G3
50/50
1.792
972253AH1-711 GEN
50/50
54.784
23856402BAYSG1
50/50
1.206
23920202STRYCT
50/50
1.866
241885AC2-103 GEN1
Solar/Wind Harmer
26.727
241858AF1-205_GEN
Solar/Wind Harmer
5.382
241840AF1-064_GEN
Solar/Wind Harmer
1.331
23906502RICHG2&3
Adder
1.287
960841AF2-375 GEN
Solar/Wind Harmer
3.4
270297AD1-101 GEN
Solar/Wind Harmer
1.341
270258AD1-119 GEN
Solar/Wind Harmer
1.239
24441205WTRV SLR C
Solar/Wind Harmer
0.079
246936BC-WTG1
Solar/Wind Harmer
2.235
270489AE1-102 GEN1
Solar/Wind Harmer
0.743
965421AG1-410 GEN
Solar/Wind Harmer
16.982
270449AD2-020 GEN
Solar/Wind Harmer
1.579
943021AE2-325 GEN
Solar/Wind Harmer
2.052
945111AF1-176 GEN
Solar/Wind Harmer
9.832
957891AF2-083 GEN
Solar/Wind Harmer
8.233
24639705ELKHART HY
Adder
0.082
270216AD2-079_GEN
Solar/Wind Harmer
0.32
965011AG1-365 GEN
Solar/Wind Harmer
5.16
270317AD1-130_GEN
Solar/Wind Harmer
1.63
270485AE1-090_GEN
Solar/Wind Harmer
0.308
270391AF1-285 GEN3
Solar/Wind Harmer
0.571
270578AF1-285 GEN2
Solar/Wind Harmer
0.571
970373AG2-245 GEN
Solar/Wind Harmer
9.84
270055AF2-134 C O1
Solar/Wind Harmer
1.393
274751CRETE EC ;1U
Adder
2.22
274754CRETE EC ;4U
Adder
2.22
958381AF2-132 GEN
Solar/Wind Harmer
4.106
964861AG1-349 GEN
Solar/Wind Harmer
3.552
971917AH1-482 GEN
Solar/Wind Harmer
4.098
274723RIVER EC ;12
Adder
8.076
274812UNIV PK N;8U
Adder
2.247
274802UNIV PARK;5U
Adder
2.586
940581AE2-045 GEN
Solar/Wind Harmer
4.501
972207SS24-0001
Solar/Wind Harmer
9.726
274773LINCOLN ;4U
Adder
2.735
274774LINCOLN ;5U
Adder
2.735
971605AH1-302 GEN
Solar/Wind Harmer
3.849
274676JOLIET 29;8U
Adder
13.43
941551AE2-152 GEN
Solar/Wind Harmer
1.983
274730ELWOOD EC;6P
Adder
7.183
274734ELWOOD EC;8P
Adder
7.183
274736ELWOOD EC;9P
Adder
7.183
970707AG2-453 GEN
Solar/Wind Harmer
12.233
274729ELWOOD EC;1P
Adder
7.182
943121AE2-341 GEN
Solar/Wind Harmer
6.477
943591AF1-030 GEN
Solar/Wind Harmer
4.318
274862TOP CROP ;2U
Solar/Wind Harmer
2.183
962511AG1-100 GEN
Solar/Wind Helper
0.332
274728ELWOOD EC;5P
Adder
7.183
274731ELWOOD EC;2P
Adder
7.182
274733ELWOOD EC;3P
Adder
7.182
274735ELWOOD EC;4P
Adder
7.182
970833AG2-524 GEN
Solar/Wind Harmer
3.795
970833AG2-524 GEN
Solar/Wind Harmer
1.765
274744AC1-111 GEN8
Adder
2.415
274746AC1-111 G10
Adder
2.415
241985AE1-237 GEN
Solar/Wind Helper
0.129
241982AE2-343 S C
Solar/Wind Helper
0.115
274732ELWOOD EC;7P
Adder
7.183
274674JOLIET 9 ;6U
Adder
6.727
274871GR RIDGE ;2U
Solar/Wind Harmer
3.341
274847GR RIDGE ;BU
Solar/Wind Harmer
2.197
274745AC1-111 GEN9
Adder
2.415
276694AA1-018 GEN2
Solar/Wind Harmer
2.724
276691AA1-018 GEN1
Solar/Wind Harmer
0.326
274861TOP CROP ;1U
Solar/Wind Harmer
2.615
203947AF1-006 C
Solar/Wind Helper
0.37
961971AG1-040 GEN
Solar/Wind Helper
0.325
203830AF1-094 GEN
Solar/Wind Helper
0.315
203979AG1-198 GEN
Solar/Wind Helper
0.189
241966AE1-183 GEN
Solar/Wind Helper
0.127
241807AE2-176_GEN
Solar/Wind Helper
0.77
254303AC2-168 GEN
Solar/Wind Helper
0.074
276893AG1-478 C
Solar/Wind Harmer
0.192
274674JOLIET 9 ;6U
Adder
6.727
942221AE2-234 GEN
Solar/Wind Harmer
1.526
958481AF2-142 GEN
Solar/Wind Harmer
6.476
945421AF1-207 GEN
Solar/Wind Harmer
6.047
957841AF2-078 GEN
Solar/Wind Harmer
2.603
203835AF1-098 GEN
Solar/Wind Helper
1.282
241967AE2-285_GEN
Solar/Wind Helper
0.33
241801AE1-079 GEN
Solar/Wind Helper
0.129
254304AE2-114 C
Solar/Wind Helper
0.11
254305AE2-115 C
Solar/Wind Helper
0.11
962101AG1-054 GEN
Solar/Wind Helper
0.319
203804AE2-113_GEN
Solar/Wind Helper
0.843
940863AE2-074 GEN
Solar/Wind Helper
0.219
946381AF1-302 GEN
Solar/Wind Helper
0.102
203846AF2-130 C
Solar/Wind Helper
0.241
241997AF1-093 GEN
Solar/Wind Helper
0.127
990142J1224
External Queue
13.161874771118164
990527J1329
External Queue
1.8005300760269165
991182J1586 G
External Queue
24.65581703186035
991177J1571 G
External Queue
15.046978950500488
LAGNLTFEXP_LAGN->PJM
CLTF
4.751
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.085
TVALTFEXP_TVA->PJM
CLTF
2.152
NYPJM->LTFIMP_NY
CLTF
1.969
LGEELTFEXP_LGEE->PJM
CLTF
1.929
WECLTFEXP_WEC->PJM
CLTF
1.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.567
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.526
MECLTFEXP_MEC->PJM
CLTF
6.229
SIGELTFEXP_SIGE->PJM
CLTF
0.161
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.013

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.63 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:1863.35
MW Contribution:
9.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
13.913
24190002OREGON_ST1
50/50
3.583
24189802OREGON_CT1
50/50
2.72
23888802TROY G4
50/50
1.792
970621AG2-405 GEN
Solar/Wind Harmer
0.843
944231AF1-091 GEN
Solar/Wind Harmer
10.325
970623AG2-406 GEN
Solar/Wind Harmer
0.779
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.161
961051AF2-396 GEN
Solar/Wind Harmer
7.798
961051AF2-396 GEN
Solar/Wind Harmer
5.199
247620Y3-023
Adder
0.247
270246TR4_N_V150
Solar/Wind Harmer
0.024
270247TR4_N_V136
Solar/Wind Harmer
0.024
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.265
965791AG1-447 GEN
Solar/Wind Harmer
3.127
970349AG2-230 GEN
Solar/Wind Harmer
5.092
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.251
274808UNIV PK N;4U
Adder
2.237
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
276776AD2-060 GEN
Solar/Wind Harmer
0.329
958011AF2-095 GEN
Solar/Wind Harmer
4.435
970941AG2-585 GEN
Solar/Wind Harmer
1.694
274770LINCOLN ;1U
Adder
3.724
274771LINCOLN ;2U
Adder
3.724
276897AD1-100 C
Solar/Wind Harmer
7.627
276893AG1-478 C
Solar/Wind Harmer
0.203
274674JOLIET 9 ;6U
Adder
6.727
942221AE2-234 GEN
Solar/Wind Harmer
1.222
958481AF2-142 GEN
Solar/Wind Harmer
4.518
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
203835AF1-098 GEN
Solar/Wind Helper
1.282
241967AE2-285_GEN
Solar/Wind Helper
0.33
241801AE1-079 GEN
Solar/Wind Helper
0.129
254304AE2-114 C
Solar/Wind Helper
0.11
254305AE2-115 C
Solar/Wind Helper
0.11
962101AG1-054 GEN
Solar/Wind Helper
0.319
203804AE2-113_GEN
Solar/Wind Helper
0.843
940863AE2-074 GEN
Solar/Wind Helper
0.219
946381AF1-302 GEN
Solar/Wind Helper
0.102
23888502TROY G1
50/50
1.792
23888602TROY G2
50/50
1.792
241886AC2-103 GEN2
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.19
270575GUS2 35KV
Solar/Wind Harmer
4.19
270499AE1-146 GEN
Solar/Wind Harmer
0.019
971549AH1-272 GEN
Solar/Wind Harmer
9.982
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.505
965041AG1-368 GEN
Solar/Wind Harmer
3.74
247521TR3_G114
Solar/Wind Harmer
0.135
965051AG1-369 GEN
Solar/Wind Harmer
1.855
970031AG2-029 GEN
Solar/Wind Harmer
2
971771AH1-392 GEN
Solar/Wind Harmer
3.641
959331AF2-224 GEN
Solar/Wind Harmer
2.52
270526AF1-158 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.5
960681AF2-359 GEN
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
2.604
963791AG1-232 GEN
Solar/Wind Harmer
4.485
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270071AF1-092 GEN
Solar/Wind Harmer
6.065
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.436
274800UNIV PARK;3U
Adder
2.578
23929302BS-PKR
50/50
2.125
958321AF2-126 GEN
Solar/Wind Harmer
1.109
23906402RICHG1
Adder
1.29
23906502RICHG2&3
Adder
1.287
270541AE2-072 C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.186
246938BC-WTG3
Solar/Wind Harmer
0.144
270491AE1-102 GEN2
Solar/Wind Harmer
0.518
945111AF1-176 GEN
Solar/Wind Harmer
3.116
24695305TIMB G C
Solar/Wind Harmer
0.325
270505AE1-170 C O1
Solar/Wind Harmer
4.034
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.2
270043AE2-236 GEN
Solar/Wind Harmer
2.186
971347AH1-153 GEN
Solar/Wind Harmer
1.697
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
274752CRETE EC ;2U
Adder
3.743
274753CRETE EC ;3U
Adder
3.743
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.979
274814UNIV PK N;0U
Adder
2.266
274807UNIV PK N;3U
Adder
2.261
274811UNIV PK N;7U
Adder
2.247
274803UNIV PARK;6U
Adder
2.586
274826FISK ;BP
Adder
4.848
972038AH1-567 GEN2
Adder
0.161
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.1
276806AD2-047 C O1
Solar/Wind Harmer
1.745
274772LINCOLN ;3U
Adder
3.724
972259AH1-714 GEN
Adder
8.358
274676JOLIET 29;8U
Adder
12.951
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.183
274734ELWOOD EC;8P
Adder
7.183
274736ELWOOD EC;9P
Adder
7.183
970707AG2-453 GEN
Solar/Wind Harmer
9.957
274729ELWOOD EC;1P
Adder
7.182
943121AE2-341 GEN
Solar/Wind Harmer
5.051
943591AF1-030 GEN
Solar/Wind Harmer
3.359
274862TOP CROP ;2U
Solar/Wind Harmer
0.407
962511AG1-100 GEN
Solar/Wind Helper
0.332
24189902OREGON_CT2
50/50
2.663
23888702TROY G3
50/50
1.792
972253AH1-711 GEN
50/50
54.784
23856402BAYSG1
50/50
1.206
23920202STRYCT
50/50
1.866
241885AC2-103 GEN1
Solar/Wind Harmer
0
241858AF1-205_GEN
Solar/Wind Harmer
3.755
23906502RICHG2&3
Adder
1.287
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.161
270489AE1-102 GEN1
Solar/Wind Harmer
0.518
965421AG1-410 GEN
Solar/Wind Harmer
11.848
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.052
945111AF1-176 GEN
Solar/Wind Harmer
6.86
957891AF2-083 GEN
Solar/Wind Harmer
6.382
24639705ELKHART HY
Adder
0.082
965011AG1-365 GEN
Solar/Wind Harmer
3.6
270317AD1-130_GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.865
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
3.743
274754CRETE EC ;4U
Adder
3.743
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.098
274723RIVER EC ;12
Adder
8.076
274812UNIV PK N;8U
Adder
2.247
274802UNIV PARK;5U
Adder
2.586
940581AE2-045 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.724
274774LINCOLN ;5U
Adder
3.724
971605AH1-302 GEN
Solar/Wind Harmer
3.849
274676JOLIET 29;8U
Adder
13.43
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.183
274674JOLIET 9 ;6U
Adder
6.727
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.415
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.489
274861TOP CROP ;1U
Solar/Wind Harmer
0
203947AF1-006 C
Solar/Wind Helper
0.37
961971AG1-040 GEN
Solar/Wind Helper
0.325
203830AF1-094 GEN
Solar/Wind Helper
0.315
203979AG1-198 GEN
Solar/Wind Helper
0.189
241966AE1-183 GEN
Solar/Wind Helper
0.127
241807AE2-176_GEN
Solar/Wind Helper
0.77
254303AC2-168 GEN
Solar/Wind Helper
0.074
274801UNIV PARK;4U
Adder
2.578
960591AF2-350 GEN
Solar/Wind Harmer
3.08
274775LINCOLN ;6U
Adder
3.724
274776LINCOLN ;7U
Adder
3.724
274777LINCOLN ;8U
Adder
3.724
971611AH1-305 GEN
Solar/Wind Harmer
1.833
972228AH1-698 GEN2
Adder
1.63
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.257
274687WILL CNTY;4U
Adder
12.257
274675JOLIET 29;7U
Adder
13.43
274675JOLIET 29;7U
Adder
12.951
274728ELWOOD EC;5P
Adder
7.183
274731ELWOOD EC;2P
Adder
7.182
274733ELWOOD EC;3P
Adder
7.182
274735ELWOOD EC;4P
Adder
7.182
970833AG2-524 GEN
Solar/Wind Harmer
3.336
970833AG2-524 GEN
Solar/Wind Harmer
2.224
274744AC1-111 GEN8
Adder
2.415
274746AC1-111 G10
Adder
2.415
241985AE1-237 GEN
Solar/Wind Helper
0.129
241982AE2-343 S C
Solar/Wind Helper
0.115
203846AF2-130 C
Solar/Wind Helper
0.241
241997AF1-093 GEN
Solar/Wind Helper
0.127
990142J1224
External Queue
13.161874771118164
990527J1329
External Queue
1.8005300760269165
991182J1586 G
External Queue
24.65581703186035
991177J1571 G
External Queue
15.046978950500488
LAGNLTFEXP_LAGN->PJM
CLTF
4.751
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.085
TVALTFEXP_TVA->PJM
CLTF
2.152
NYPJM->LTFIMP_NY
CLTF
1.969
LGEELTFEXP_LGEE->PJM
CLTF
1.929
WECLTFEXP_WEC->PJM
CLTF
1.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.567
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.526
MECLTFEXP_MEC->PJM
CLTF
6.229
SIGELTFEXP_SIGE->PJM
CLTF
0.161
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.013

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.82 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2406.35
MW Contribution:
9.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
45.443
24727105RPMNG2
50/50
3.318
970583AG2-370 GEN
50/50
2.814
270142AC1-141 CT1_
50/50
2.029
24642205MAYFLWER
50/50
0.031
965021AG1-366 GEN
Solar/Wind Harmer
4.607
270043AE2-236 GEN
Solar/Wind Harmer
5.241
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.981
24695305TIMB G C
Solar/Wind Harmer
0.532
945111AF1-176 GEN
Solar/Wind Harmer
4.853
971347AH1-153 GEN
Solar/Wind Harmer
2.927
270505AE1-170 C O1
Solar/Wind Harmer
6.132
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.345
274752CRETE EC ;2U
Adder
6.312
274753CRETE EC ;3U
Adder
6.312
274724RIVER EC ;11
Adder
13.515
274814UNIV PK N;0U
Adder
3.826
24727205RPMNG3
50/50
3.298
24729505KEY G4
50/50
6.847
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.792
959331AF2-224 GEN
Solar/Wind Harmer
9.676
963791AG1-232 GEN
Solar/Wind Harmer
12.035
970031AG2-029 GEN
Solar/Wind Harmer
4.587
965041AG1-368 GEN
Solar/Wind Harmer
8.443
270071AF1-092 GEN
Solar/Wind Harmer
14.566
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.602
971771AH1-392 GEN
Solar/Wind Harmer
5.907
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.922
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.13
274775LINCOLN ;6U
Adder
6.365
274776LINCOLN ;7U
Adder
6.365
274777LINCOLN ;8U
Adder
6.365
972037AH1-567 GEN1
Adder
0.137
274827FISK ;RP
Adder
5.808
274800UNIV PARK;3U
Adder
4.357
274801UNIV PARK;4U
Adder
4.357
960591AF2-350 GEN
Solar/Wind Harmer
5.207
972228AH1-698 GEN2
Adder
2.756
972227AH1-698 GEN1
Adder
1.941
274687WILL CNTY;4U
Adder
20.685
274687WILL CNTY;4U
Adder
20.685
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.662
274675JOLIET 29;7U
Adder
21.853
274728ELWOOD EC;5P
Adder
12.11
274731ELWOOD EC;2P
Adder
12.11
274733ELWOOD EC;3P
Adder
12.11
274735ELWOOD EC;4P
Adder
12.11
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.974
970833AG2-524 GEN
Solar/Wind Harmer
5.628
970833AG2-524 GEN
Solar/Wind Harmer
3.752
971611AH1-305 GEN
Solar/Wind Harmer
3.031
274744AC1-111 GEN8
Adder
4.068
274746AC1-111 G10
Adder
4.068
970073AG2-061 GEN
Solar/Wind Harmer
1.661
247536S-71 GEN
Solar/Wind Harmer
0.199
971411AH1-196 GEN
Solar/Wind Harmer
7.376
971675AH1-338 GEN
Solar/Wind Harmer
1.916
276861AD2-134 GEN
Solar/Wind Harmer
0.088
276863AD2-134 GEN
Solar/Wind Harmer
0.088
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24727005RPMNG1
50/50
3.317
960861AF2-377 GEN
50/50
2.406
970521AG2-332 GEN
50/50
10.906
24639705ELKHART HY
50/50
0.151
270143AC1-141 CT2_
50/50
2.029
965421AG1-410 GEN
Solar/Wind Harmer
81.797
965011AG1-365 GEN
Solar/Wind Harmer
13.822
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.876
958861AF2-177 GEN
Solar/Wind Harmer
2.694
945111AF1-176 GEN
Solar/Wind Harmer
10.683
957891AF2-083 GEN
Solar/Wind Harmer
9.802
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3
970373AG2-245 GEN
Solar/Wind Harmer
11.243
274751CRETE EC ;1U
Adder
6.312
274754CRETE EC ;4U
Adder
6.312
274723RIVER EC ;12
Adder
13.681
24729405KEY G3
50/50
0.374
24729305KEY G2
50/50
0.367
24729205KEY G1
50/50
0.366
247620Y3-023
50/50
0.467
960851AF2-376 GEN
50/50
2.095
24643105BUCHANAN
50/50
0.01
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.855
944231AF1-091 GEN
Solar/Wind Harmer
16.139
944541AF1-119 GEN
Solar/Wind Harmer
0.427
960971AF2-388 GEN
Solar/Wind Harmer
3.752
970349AG2-230 GEN
Solar/Wind Harmer
8.78
961051AF2-396 GEN
Solar/Wind Harmer
11.674
961051AF2-396 GEN
Solar/Wind Harmer
7.782
270031AE2-169
Solar/Wind Harmer
3.104
270599AE1-208 GEN
Solar/Wind Harmer
5.173
965681AG1-436 GEN
Solar/Wind Harmer
6.963
965791AG1-447 GEN
Solar/Wind Harmer
5.106
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.41
247621Y3-024
Adder
0.183
274805UNIV PK N;1U
Adder
3.801
274808UNIV PK N;4U
Adder
3.776
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.365
274771LINCOLN ;2U
Adder
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
0.304
276776AD2-060 GEN
Solar/Wind Harmer
0.555
958011AF2-095 GEN
Solar/Wind Harmer
7.498
970941AG2-585 GEN
Solar/Wind Harmer
2.864
276897AD1-100 C
Solar/Wind Harmer
12.887
274674JOLIET 9 ;6U
Adder
11.348
276893AG1-478 C
Solar/Wind Harmer
0.343
970291AG2-192 GEN
Solar/Wind Harmer
0.666
970291AG2-192 GEN
Solar/Wind Harmer
0.308
971613AH1-306 GEN
Solar/Wind Harmer
2.442
958481AF2-142 GEN
Solar/Wind Harmer
7.57
274695ROCKY RD ;2P
Adder
8.016
274693ROCKY RD ;1P
Adder
7.937
274697ROCKY RD ;3P
Adder
2.178
274696ROCKY RD ;4P
Adder
8.205
274683WAUKEGAN ;8U
Adder
15.145
274683WAUKEGAN ;8U
Adder
12.766
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
14.951
958491AF2-143 GEN
Solar/Wind Harmer
7.476
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.768
971343AH1-151 GEN
Solar/Wind Harmer
9.768
972235AH1-702 GEN1
Adder
1.755
972236AH1-702 GEN2
Adder
1.526
938861AE1-114 GEN
Solar/Wind Harmer
2.722
274764LEE CO EC;5U
Adder
6.396
274765LEE CO EC;6U
Adder
6.396
274762LEE CO EC;3U
Adder
6.381
274763LEE CO EC;4U
Adder
6.321
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.763
276645AC1-214 GEN1
Solar/Wind Harmer
0.185
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.533
942111AE2-223 GEN
Solar/Wind Harmer
1.513
960611AF2-352 GEN
Solar/Wind Harmer
1.525
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.481
970885AG2-551 GEN
Solar/Wind Harmer
1.494
970241AG2-163 GEN
Solar/Wind Harmer
2.581
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.044
276838X2-022 GEN2
Solar/Wind Harmer
0.239
276916AD2-100_GEN
Solar/Wind Harmer
8.532
276911AD2-131_GEN
Solar/Wind Harmer
0.562
945391AF1-204 GEN
Solar/Wind Harmer
4.219
970623AG2-406 GEN
Solar/Wind Harmer
0.656
971587AH1-292 GEN
Solar/Wind Harmer
2.468
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.897
270462AD2-086
Solar/Wind Helper
3.747
247522W1-056 GEN
Solar/Wind Helper
1.177
253378AE2-206_GEN
Solar/Wind Helper
0.715
270349AD2-093_GEN
Solar/Wind Helper
0.857
270471AD2-092_GEN
Solar/Wind Helper
0.857
241960AC2-195 GEN
Solar/Wind Helper
0.697
274807UNIV PK N;3U
Adder
3.817
274811UNIV PK N;7U
Adder
3.792
274772LINCOLN ;3U
Adder
6.365
274803UNIV PARK;6U
Adder
4.369
274826FISK ;BP
Adder
8.195
972038AH1-567 GEN2
Adder
0.273
274887GEN-1.85
Solar/Wind Harmer
0.135
276843GEN-1.7
Solar/Wind Harmer
0.168
276806AD2-047 C O1
Solar/Wind Harmer
2.951
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.153
970707AG2-453 GEN
Solar/Wind Harmer
16.903
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.852
274729ELWOOD EC;1P
Adder
12.11
274730ELWOOD EC;6P
Adder
12.11
274734ELWOOD EC;8P
Adder
12.11
274736ELWOOD EC;9P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.564
946031AF1-268 GEN
Solar/Wind Harmer
4.838
943121AE2-341 GEN
Solar/Wind Harmer
8.518
943591AF1-030 GEN
Solar/Wind Harmer
5.665
270004AE1-209 GEN
Solar/Wind Harmer
1.101
274862TOP CROP ;2U
Solar/Wind Harmer
0.681
970825AG2-519 GEN
Solar/Wind Harmer
3.795
274682WAUKEGAN ;7U
Adder
12.933
276868AE1-113 GEN
Solar/Wind Harmer
0.991
274879MINONK ;1U
Solar/Wind Harmer
0.207
946671AF1-331 GEN
Solar/Wind Harmer
0.524
274855GSG-6 ;RU
Solar/Wind Harmer
0.179
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.895
959091AF2-200 GEN
Solar/Wind Harmer
9.768
970571AG2-364 GEN
Solar/Wind Harmer
9.675
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.381
274767LEE CO EC;8U
Adder
6.306
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.157
965091AG1-374 GEN
Solar/Wind Harmer
13.726
965931AG1-462 GEN
Solar/Wind Harmer
11.666
971087AG2-675 GEN
Solar/Wind Harmer
2.44
959611AF2-252 GEN
Solar/Wind Harmer
1.525
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.998
957381AF2-032 GEN
Solar/Wind Harmer
0.932
942481AE2-261 GEN
Solar/Wind Harmer
12.255
970193AG2-126 GEN
Solar/Wind Harmer
5.956
24728705AND G3
Adder
4.39
24728505AND G1
Adder
2.099
246938BC-WTG3
Solar/Wind Helper
11.083
942871AE2-306 GEN
Solar/Wind Helper
0.445
270284AF1-227 GEN1
Solar/Wind Helper
1.893
270287AF1-227 GEN3
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.334
270541AE2-072 C
Solar/Wind Helper
0.943
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.768
274823ROCKFORD ;21
Adder
13.596
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
926823AC1-168 GEN
Solar/Wind Harmer
0.821
970169AG2-114 GEN
Solar/Wind Harmer
4.823
971681AH1-341 GEN
Solar/Wind Harmer
7.736
971549AH1-272 GEN
Solar/Wind Harmer
9.898
972267AH1-718 GEN
Adder
2.828
276741O09 GEN1
Solar/Wind Harmer
0.167
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.157
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.889
946321AF1-296 GEN
Solar/Wind Harmer
2.577
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.976
270543AE2-219 C
Solar/Wind Harmer
3.137
276668AB2-070 GEN1
Solar/Wind Harmer
0.17
276848AB2-070 GEN3
Solar/Wind Harmer
0.169
276849AB2-070 GEN2
Solar/Wind Harmer
0.17
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.928
944221AF1-090 GEN
Solar/Wind Harmer
2.312
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.609
270223U2-072_GEN1
Solar/Wind Helper
0.876
270224U2-072_GEN2
Solar/Wind Helper
0.876
270227U2-072_GEN3
Solar/Wind Helper
0.876
270228U2-072_GEN4
Solar/Wind Helper
0.876
270231U2-072_GEN5
Solar/Wind Helper
0.876
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
1.968
945641AF1-229 GEN
Solar/Wind Helper
0.94
274812UNIV PK N;8U
Adder
3.792
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.365
274774LINCOLN ;5U
Adder
6.365
274802UNIV PARK;5U
Adder
4.369
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.75
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.662
274674JOLIET 9 ;6U
Adder
11.348
274732ELWOOD EC;7P
Adder
12.11
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.364
270594AE1-207 GEN
Solar/Wind Harmer
5.699
270032AE2-172
Solar/Wind Harmer
3.392
270005AE1-210 C O1
Solar/Wind Harmer
1.101
274745AC1-111 GEN9
Adder
4.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.82
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.788
274682WAUKEGAN ;7U
Adder
12.933
274828WAUKEGAN ;BP
Adder
7.939
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.731
939401AE1-172 GEN
Solar/Wind Harmer
3.718
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.578
971997AH1-543 GEN
Solar/Wind Harmer
2.59
957471AF2-041 GEN
Solar/Wind Harmer
14.651
959081AF2-199 GEN
Solar/Wind Harmer
4.884
971067AG2-660 GEN
Solar/Wind Harmer
1.628
274822ROCKFORD ;11
Adder
13.696
276903AD2-071 C
Solar/Wind Harmer
5.426
970819AG2-516 GEN
Solar/Wind Harmer
5.809
970569AG2-363 GEN
Solar/Wind Harmer
14.512
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.381
274766LEE CO EC;7U
Adder
6.306
276708O09 GEN2
Solar/Wind Harmer
0.167
276646AC1-214 GEN2
Solar/Wind Harmer
0.185
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.519
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.287
963741AG1-226 GEN
Solar/Wind Harmer
10.473
276621W2-048 GEN
Solar/Wind Harmer
0.213
965911AG1-460 GEN
Solar/Wind Harmer
0.82
24728605AND G2
Adder
2.099
970773AG2-487 GEN
Solar/Wind Harmer
0.63
246936BC-WTG1
Solar/Wind Helper
10.897
270317AD1-130_GEN
Solar/Wind Helper
4.143
270485AE1-090_GEN
Solar/Wind Helper
0.326
270391AF1-285 GEN3
Solar/Wind Helper
0.593
270578AF1-285 GEN2
Solar/Wind Helper
0.593
270286AF1-227 GEN2
Solar/Wind Helper
0.694
960841AF2-375 GEN
Solar/Wind Helper
1.179
990497J1323
External Queue
1.5952997207641602
990792J1392
External Queue
5.487830638885498
LAGNLTFEXP_LAGN->PJM
CLTF
5.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.51
TVALTFEXP_TVA->PJM
CLTF
2.319
NYPJM->LTFIMP_NY
CLTF
1.264
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
AG2-052LTFEXP_AG2-052->PJM
LTF
0.172
AH1-155LTFEXP_AH1-155->PJM
LTF
0.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
70.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.933
MECLTFEXP_MEC->PJM
CLTF
9.784
SIGELTFEXP_SIGE->PJM
CLTF
0.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.835

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-032T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-032T_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.98 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1923.66
MW Contribution:
9.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.145
965421AG1-410 GEN
Solar/Wind Harmer
112.286
965011AG1-365 GEN
Solar/Wind Harmer
17.416
270024AE2-089 GEN
Solar/Wind Harmer
3.678
24639705ELKHART HY
Adder
0.105
965651AG1-433 GEN
Solar/Wind Harmer
3.74
958861AF2-177 GEN
Solar/Wind Harmer
7.267
270216AD2-079_GEN
Solar/Wind Harmer
0.394
945371AF1-202 GEN
Solar/Wind Harmer
4.378
945111AF1-176 GEN
Solar/Wind Harmer
11.193
957891AF2-083 GEN
Solar/Wind Harmer
9.167
270449AD2-020 GEN
Solar/Wind Harmer
1.677
943021AE2-325 GEN
Solar/Wind Harmer
2.18
24441205WTRV SLR C
Solar/Wind Harmer
0.077
270005AE1-210 C O1
Solar/Wind Harmer
2.952
970825AG2-519 GEN
Solar/Wind Harmer
1.131
270594AE1-207 GEN
Solar/Wind Harmer
7.28
270032AE2-172
Solar/Wind Harmer
2.493
970373AG2-245 GEN
Solar/Wind Harmer
11.236
270055AF2-134 C O1
Solar/Wind Harmer
1.597
274751CRETE EC ;1U
Adder
2.576
274754CRETE EC ;4U
Adder
2.576
274723RIVER EC ;12
Adder
9.377
958381AF2-132 GEN
Solar/Wind Harmer
4.729
964861AG1-349 GEN
Solar/Wind Harmer
4.093
971917AH1-482 GEN
Solar/Wind Harmer
4.722
274812UNIV PK N;8U
Adder
2.599
274802UNIV PARK;5U
Adder
2.984
940581AE2-045 GEN
Solar/Wind Harmer
5.219
971605AH1-302 GEN
Solar/Wind Harmer
4.462
276903AD2-071 C
Solar/Wind Harmer
5.107
972207SS24-0001
Solar/Wind Harmer
11.205
274773LINCOLN ;4U
Adder
3.152
274774LINCOLN ;5U
Adder
3.152
274676JOLIET 29;8U
Adder
15.429
941551AE2-152 GEN
Solar/Wind Harmer
2.277
274732ELWOOD EC;7P
Adder
8.246
274674JOLIET 9 ;6U
Adder
7.724
274871GR RIDGE ;2U
Solar/Wind Harmer
3.828
274847GR RIDGE ;BU
Solar/Wind Harmer
2.517
274745AC1-111 GEN9
Adder
2.763
965431AG1-411 GEN
50/50
43.522
24727105RPMNG2
50/50
3.146
970583AG2-370 GEN
50/50
2.327
965021AG1-366 GEN
Solar/Wind Harmer
4.05
270043AE2-236 GEN
Solar/Wind Harmer
4.963
270063AE2-323 C
Solar/Wind Harmer
1.824
944531AF1-118 GEN
Solar/Wind Harmer
26.796
24695305TIMB G C
Solar/Wind Harmer
2.376
247643Z2-116 C
Solar/Wind Harmer
0.045
945111AF1-176 GEN
Solar/Wind Harmer
3.547
962031AG1-047 GEN
Solar/Wind Harmer
1.866
957741AF2-068 GEN
Solar/Wind Harmer
9.255
270505AE1-170 C O1
Solar/Wind Harmer
9.079
24441505OLIV SLR
Solar/Wind Harmer
0.077
971347AH1-153 GEN
Solar/Wind Harmer
2.853
946031AF1-268 GEN
Solar/Wind Harmer
4.547
270004AE1-209 GEN
Solar/Wind Harmer
2.952
247642Z2-115 C
Solar/Wind Harmer
0.035
970825AG2-519 GEN
Solar/Wind Harmer
3.037
965461AG1-414 GEN
Solar/Wind Harmer
1.219
970289AG2-191 GEN
Solar/Wind Harmer
0.413
972231SS25-0005
Solar/Wind Harmer
5.002
972181SS23-001
Solar/Wind Harmer
3.126
274752CRETE EC ;2U
Adder
2.576
274753CRETE EC ;3U
Adder
2.576
274724RIVER EC ;11
Adder
9.26
964401AG1-302 GEN
Solar/Wind Harmer
4.729
274814UNIV PK N;0U
Adder
2.622
274807UNIV PK N;3U
Adder
2.616
274811UNIV PK N;7U
Adder
2.599
276164X3-005 C
Solar/Wind Harmer
0.363
274803UNIV PARK;6U
Adder
2.984
274826FISK ;BP
Adder
5.593
972038AH1-567 GEN2
Adder
0.186
274887GEN-1.85
Solar/Wind Harmer
2.71
270246TR4_N_V150
Solar/Wind Harmer
0.715
270247TR4_N_V136
Solar/Wind Harmer
0.715
942221AE2-234 GEN
Solar/Wind Harmer
2.805
944231AF1-091 GEN
Solar/Wind Harmer
14.059
247620Y3-023
Adder
0.331
944541AF1-119 GEN
Solar/Wind Harmer
2.865
960971AF2-388 GEN
Solar/Wind Harmer
7.48
270201AC2-176 GEN
Solar/Wind Harmer
3.171
270031AE2-169
Solar/Wind Harmer
4.967
270599AE1-208 GEN
Solar/Wind Harmer
4.967
24727205RPMNG3
50/50
3.127
959331AF2-224 GEN
Solar/Wind Harmer
17.416
963791AG1-232 GEN
Solar/Wind Harmer
14.325
965041AG1-368 GEN
Solar/Wind Harmer
10.007
970031AG2-029 GEN
Solar/Wind Harmer
24.399
247521TR3_G114
Solar/Wind Harmer
2.827
270191TR4_S_V150
Solar/Wind Harmer
2.523
965051AG1-369 GEN
Solar/Wind Harmer
4.201
270071AF1-092 GEN
Solar/Wind Harmer
12.386
24729505KEY G4
Adder
4.827
958711AF2-162 GEN
Solar/Wind Harmer
0.692
945581AF1-223 GEN
Solar/Wind Harmer
2.846
961761AG1-017 GEN
Solar/Wind Harmer
0.264
971771AH1-392 GEN
Solar/Wind Harmer
5.448
964611AG1-324 GEN
Solar/Wind Harmer
2.349
944161AF1-084 GEN
Solar/Wind Harmer
1.304
270526AF1-158 GEN
Solar/Wind Harmer
2.633
960681AF2-359 GEN
Solar/Wind Harmer
2.093
247536S-71 GEN
Solar/Wind Harmer
2.215
970289AG2-191 GEN
Solar/Wind Harmer
1.022
971549AH1-272 GEN
Solar/Wind Harmer
9.608
958391AF2-133 GEN
Solar/Wind Harmer
4.696
959141AF2-205 GEN
Solar/Wind Harmer
3.114
972037AH1-567 GEN1
Adder
0.094
274827FISK ;RP
Adder
3.964
274800UNIV PARK;3U
Adder
2.972
274801UNIV PARK;4U
Adder
2.972
960591AF2-350 GEN
Solar/Wind Harmer
5.086
274775LINCOLN ;6U
Adder
3.152
274776LINCOLN ;7U
Adder
3.152
274777LINCOLN ;8U
Adder
3.152
972228AH1-698 GEN2
Adder
1.876
972227AH1-698 GEN1
Adder
1.321
274687WILL CNTY;4U
Adder
14.092
274687WILL CNTY;4U
Adder
14.092
274675JOLIET 29;7U
Adder
15.429
274675JOLIET 29;7U
Adder
14.878
276893AG1-478 C
Solar/Wind Harmer
0.276
274728ELWOOD EC;5P
Adder
8.246
274731ELWOOD EC;2P
Adder
8.246
274733ELWOOD EC;3P
Adder
8.246
274735ELWOOD EC;4P
Adder
8.246
970833AG2-524 GEN
Solar/Wind Harmer
4.35
970833AG2-524 GEN
Solar/Wind Harmer
2.023
274744AC1-111 GEN8
Adder
2.763
274746AC1-111 G10
Adder
2.763
946581AF1-322 GEN
Solar/Wind Harmer
5.048
24691005MDL-2G C
Solar/Wind Harmer
1.824
270543AE2-219 C
Solar/Wind Harmer
4.891
970073AG2-061 GEN
Solar/Wind Harmer
1.134
274823ROCKFORD ;21
Adder
9.263
972267AH1-718 GEN
Adder
1.93
957201AF2-014 GEN
Solar/Wind Helper
8.91
270223U2-072_GEN1
Solar/Wind Helper
0.838
270224U2-072_GEN2
Solar/Wind Helper
0.838
270227U2-072_GEN3
Solar/Wind Helper
0.838
270228U2-072_GEN4
Solar/Wind Helper
0.838
270231U2-072_GEN5
Solar/Wind Helper
0.838
966831AG1-554 GEN
Solar/Wind Helper
0.91
270499AE1-146 GEN
Solar/Wind Helper
2.194
945641AF1-229 GEN
Solar/Wind Helper
1.04
276772AC2-154 GEN
Solar/Wind Harmer
1.419
276843GEN-1.7
Solar/Wind Harmer
0.292
276806AD2-047 C O1
Solar/Wind Harmer
5.441
274772LINCOLN ;3U
Adder
3.152
972259AH1-714 GEN
Adder
9.603
274676JOLIET 29;8U
Adder
14.878
939351AE1-166 GEN
Solar/Wind Harmer
2.977
274729ELWOOD EC;1P
Adder
8.246
274730ELWOOD EC;6P
Adder
8.246
274734ELWOOD EC;8P
Adder
8.246
274736ELWOOD EC;9P
Adder
8.246
970707AG2-453 GEN
Solar/Wind Harmer
14.045
943121AE2-341 GEN
Solar/Wind Harmer
7.409
943591AF1-030 GEN
Solar/Wind Harmer
4.939
274862TOP CROP ;2U
Solar/Wind Harmer
2.496
24690905MDL-1G C
Solar/Wind Harmer
3.961
970781AG2-491 GEN
Solar/Wind Harmer
4.933
274682WAUKEGAN ;7U
Adder
8.801
274760LEE CO EC;1U
Adder
4.352
274767LEE CO EC;8U
Adder
4.301
246938BC-WTG3
Solar/Wind Helper
11.472
942871AE2-306 GEN
Solar/Wind Helper
0.426
270284AF1-227 GEN1
Solar/Wind Helper
1.61
270287AF1-227 GEN3
Solar/Wind Helper
0.59
270541AE2-072 C
Solar/Wind Helper
1.17
276820AF1-078_GEN
Solar/Wind Helper
0.329
276868AE1-113 GEN
Solar/Wind Harmer
3.451
961051AF2-396 GEN
Solar/Wind Harmer
9.671
961051AF2-396 GEN
Solar/Wind Harmer
4.498
964611AG1-324 GEN
Solar/Wind Harmer
0.315
247621Y3-024
Adder
0.141
970349AG2-230 GEN
Solar/Wind Harmer
8.559
965681AG1-436 GEN
Solar/Wind Harmer
6.923
965791AG1-447 GEN
Solar/Wind Harmer
3.542
970291AG2-192 GEN
Solar/Wind Harmer
0.699
970291AG2-192 GEN
Solar/Wind Harmer
0.225
270535AF1-215 GEN1
Solar/Wind Harmer
2.396
270536AF1-215 GEN2
Solar/Wind Harmer
2.396
274805UNIV PK N;1U
Adder
2.605
274808UNIV PK N;4U
Adder
2.588
274888KELLY CRK;1U
Solar/Wind Harmer
3.002
276776AD2-060 GEN
Solar/Wind Harmer
0.213
958011AF2-095 GEN
Solar/Wind Harmer
7.324
970941AG2-585 GEN
Solar/Wind Harmer
2.798
274770LINCOLN ;1U
Adder
3.152
274771LINCOLN ;2U
Adder
3.152
24725505WLD G2 C
Solar/Wind Harmer
1.998
24699105WLD G1 C
Solar/Wind Harmer
1.974
945421AF1-207 GEN
Solar/Wind Harmer
7.056
957841AF2-078 GEN
Solar/Wind Harmer
3.037
276897AD1-100 C
Solar/Wind Harmer
23.32
276893AG1-478 C
Solar/Wind Harmer
0.22
274674JOLIET 9 ;6U
Adder
7.724
958481AF2-142 GEN
Solar/Wind Harmer
7.404
270180AB1-006 GEN1
Solar/Wind Harmer
3.548
24697605MDL-3G C
Solar/Wind Harmer
1.818
24755605MDL-5G
Solar/Wind Harmer
1.189
24697905MDL-4G C
Solar/Wind Harmer
1.132
270181AB1-006 GEN2
Solar/Wind Harmer
0.353
274696ROCKY RD ;4P
Adder
5.578
274695ROCKY RD ;2P
Adder
5.45
274693ROCKY RD ;1P
Adder
5.396
274697ROCKY RD ;3P
Adder
1.48
274683WAUKEGAN ;8U
Adder
10.306
274683WAUKEGAN ;8U
Adder
8.688
970883AG2-550 GEN
Solar/Wind Harmer
4.891
970885AG2-551 GEN
Solar/Wind Harmer
1.137
958491AF2-143 GEN
Solar/Wind Harmer
7.315
962691AG1-118 GEN
Solar/Wind Harmer
14.569
276901AD2-066 C O1
Solar/Wind Harmer
1.703
960751AF2-366 GEN
Solar/Wind Harmer
1.39
972235AH1-702 GEN1
Adder
1.196
972236AH1-702 GEN2
Adder
1.04
274764LEE CO EC;5U
Adder
4.363
274765LEE CO EC;6U
Adder
4.363
274762LEE CO EC;3U
Adder
4.352
274763LEE CO EC;4U
Adder
4.311
276694AA1-018 GEN2
Solar/Wind Harmer
3.115
276691AA1-018 GEN1
Solar/Wind Harmer
0.372
274861TOP CROP ;1U
Solar/Wind Harmer
2.99
24791305MDL-5G
Solar/Wind Harmer
1.189
274682WAUKEGAN ;7U
Adder
8.801
274828WAUKEGAN ;BP
Adder
5.402
276805AD2-038 GEN
Solar/Wind Harmer
2.501
939401AE1-172 GEN
Solar/Wind Harmer
6.76
962781AG1-127 GEN
Solar/Wind Harmer
4.608
274822ROCKFORD ;11
Adder
9.331
274761LEE CO EC;2U
Adder
4.352
274766LEE CO EC;7U
Adder
4.301
246936BC-WTG1
Solar/Wind Helper
11.279
270317AD1-130_GEN
Solar/Wind Helper
4.051
270485AE1-090_GEN
Solar/Wind Helper
0.319
270391AF1-285 GEN3
Solar/Wind Helper
0.567
270578AF1-285 GEN2
Solar/Wind Helper
0.567
960841AF2-375 GEN
Solar/Wind Helper
1.323
270286AF1-227 GEN2
Solar/Wind Helper
0.59
241840AF1-064_GEN
Solar/Wind Helper
0.505
241807AE2-176_GEN
Solar/Wind Helper
0.732
276882AE2-255 GEN
Solar/Wind Harmer
1.15
246937BC-WTG2
Solar/Wind Helper
11.279
270462AD2-086
Solar/Wind Helper
3.664
247522W1-056 GEN
Solar/Wind Helper
1.247
253378AE2-206_GEN
Solar/Wind Helper
0.704
990497J1323
External Queue
1.3108574151992798
LAGNLTFEXP_LAGN->PJM
CLTF
4.246
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
1.745
NYPJM->LTFIMP_NY
CLTF
0.879
LGEELTFEXP_LGEE->PJM
CLTF
1.302
WECLTFEXP_WEC->PJM
CLTF
1.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.654
MECLTFEXP_MEC->PJM
CLTF
6.749
SIGELTFEXP_SIGE->PJM
CLTF
0.143
CPLELTFEXP_CPLE->PJM
CLTF
0.049
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.399

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-022T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-022T_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.28 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1891.93
MW Contribution:
9.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
43.52
24727105RPMNG2
50/50
3.145
970583AG2-370 GEN
50/50
2.328
965021AG1-366 GEN
Solar/Wind Harmer
4.047
270043AE2-236 GEN
Solar/Wind Harmer
4.951
270063AE2-323 C
Solar/Wind Harmer
1.818
944531AF1-118 GEN
Solar/Wind Harmer
26.732
24695305TIMB G C
Solar/Wind Harmer
2.379
247643Z2-116 C
Solar/Wind Harmer
0.045
945111AF1-176 GEN
Solar/Wind Harmer
3.517
962031AG1-047 GEN
Solar/Wind Harmer
1.861
957741AF2-068 GEN
Solar/Wind Harmer
9.234
270505AE1-170 C O1
Solar/Wind Harmer
8.996
24441505OLIV SLR
Solar/Wind Harmer
0.076
971347AH1-153 GEN
Solar/Wind Harmer
2.832
946031AF1-268 GEN
Solar/Wind Harmer
4.533
270004AE1-209 GEN
Solar/Wind Harmer
2.943
247642Z2-115 C
Solar/Wind Harmer
0.034
970825AG2-519 GEN
Solar/Wind Harmer
3.028
965461AG1-414 GEN
Solar/Wind Harmer
1.215
970289AG2-191 GEN
Solar/Wind Harmer
0.411
972231SS25-0005
Solar/Wind Harmer
4.966
972181SS23-001
Solar/Wind Harmer
3.104
274752CRETE EC ;2U
Adder
2.558
274753CRETE EC ;3U
Adder
2.558
274724RIVER EC ;11
Adder
9.194
964401AG1-302 GEN
Solar/Wind Harmer
4.695
274814UNIV PK N;0U
Adder
2.603
274807UNIV PK N;3U
Adder
2.598
274811UNIV PK N;7U
Adder
2.581
276164X3-005 C
Solar/Wind Harmer
0.361
274803UNIV PARK;6U
Adder
2.963
274826FISK ;BP
Adder
5.553
972038AH1-567 GEN2
Adder
0.185
274887GEN-1.85
Solar/Wind Harmer
2.691
276772AC2-154 GEN
Solar/Wind Harmer
1.409
276843GEN-1.7
Solar/Wind Harmer
0.29
276806AD2-047 C O1
Solar/Wind Harmer
5.403
274772LINCOLN ;3U
Adder
3.129
972259AH1-714 GEN
Adder
9.535
274676JOLIET 29;8U
Adder
14.772
939351AE1-166 GEN
Solar/Wind Harmer
2.956
970707AG2-453 GEN
Solar/Wind Harmer
13.945
274729ELWOOD EC;1P
Adder
8.187
274730ELWOOD EC;6P
Adder
8.187
274734ELWOOD EC;8P
Adder
8.187
274736ELWOOD EC;9P
Adder
8.187
943121AE2-341 GEN
Solar/Wind Harmer
7.357
943591AF1-030 GEN
Solar/Wind Harmer
4.904
24690905MDL-1G C
Solar/Wind Harmer
3.934
970781AG2-491 GEN
Solar/Wind Harmer
4.901
274862TOP CROP ;2U
Solar/Wind Harmer
2.478
274682WAUKEGAN ;7U
Adder
8.738
274760LEE CO EC;1U
Adder
4.322
274767LEE CO EC;8U
Adder
4.271
246938BC-WTG3
Solar/Wind Helper
11.472
942871AE2-306 GEN
Solar/Wind Helper
0.425
270284AF1-227 GEN1
Solar/Wind Helper
1.609
270287AF1-227 GEN3
Solar/Wind Helper
0.59
270541AE2-072 C
Solar/Wind Helper
1.125
276820AF1-078_GEN
Solar/Wind Helper
0.329
276868AE1-113 GEN
Solar/Wind Harmer
3.427
270246TR4_N_V150
Solar/Wind Harmer
0.716
270247TR4_N_V136
Solar/Wind Harmer
0.716
942221AE2-234 GEN
Solar/Wind Harmer
2.801
944231AF1-091 GEN
Solar/Wind Harmer
14.2
247620Y3-023
Adder
0.329
944541AF1-119 GEN
Solar/Wind Harmer
2.858
960971AF2-388 GEN
Solar/Wind Harmer
7.461
270201AC2-176 GEN
Solar/Wind Harmer
3.164
270031AE2-169
Solar/Wind Harmer
4.953
270599AE1-208 GEN
Solar/Wind Harmer
4.953
961051AF2-396 GEN
Solar/Wind Harmer
9.581
961051AF2-396 GEN
Solar/Wind Harmer
4.456
964611AG1-324 GEN
Solar/Wind Harmer
0.314
247621Y3-024
Adder
0.141
970349AG2-230 GEN
Solar/Wind Harmer
8.496
965681AG1-436 GEN
Solar/Wind Harmer
6.868
965791AG1-447 GEN
Solar/Wind Harmer
3.514
970291AG2-192 GEN
Solar/Wind Harmer
0.696
970291AG2-192 GEN
Solar/Wind Harmer
0.224
270535AF1-215 GEN1
Solar/Wind Harmer
2.379
270536AF1-215 GEN2
Solar/Wind Harmer
2.379
274805UNIV PK N;1U
Adder
2.586
274808UNIV PK N;4U
Adder
2.569
274888KELLY CRK;1U
Solar/Wind Harmer
2.98
276776AD2-060 GEN
Solar/Wind Harmer
0.211
958011AF2-095 GEN
Solar/Wind Harmer
7.272
970941AG2-585 GEN
Solar/Wind Harmer
2.778
274770LINCOLN ;1U
Adder
3.129
274771LINCOLN ;2U
Adder
3.129
24725505WLD G2 C
Solar/Wind Harmer
1.99
24699105WLD G1 C
Solar/Wind Harmer
1.967
945421AF1-207 GEN
Solar/Wind Harmer
7.009
957841AF2-078 GEN
Solar/Wind Harmer
3.017
276897AD1-100 C
Solar/Wind Harmer
23.155
276893AG1-478 C
Solar/Wind Harmer
0.218
274674JOLIET 9 ;6U
Adder
7.67
958481AF2-142 GEN
Solar/Wind Harmer
7.352
270180AB1-006 GEN1
Solar/Wind Harmer
3.525
24697605MDL-3G C
Solar/Wind Harmer
1.807
24755605MDL-5G
Solar/Wind Harmer
1.182
24697905MDL-4G C
Solar/Wind Harmer
1.125
270181AB1-006 GEN2
Solar/Wind Harmer
0.35
970883AG2-550 GEN
Solar/Wind Harmer
4.878
970885AG2-551 GEN
Solar/Wind Harmer
1.135
274696ROCKY RD ;4P
Adder
5.539
274695ROCKY RD ;2P
Adder
5.411
274693ROCKY RD ;1P
Adder
5.358
274697ROCKY RD ;3P
Adder
1.47
274683WAUKEGAN ;8U
Adder
10.233
274683WAUKEGAN ;8U
Adder
8.626
958491AF2-143 GEN
Solar/Wind Harmer
7.264
962691AG1-118 GEN
Solar/Wind Harmer
14.466
276901AD2-066 C O1
Solar/Wind Harmer
1.691
960751AF2-366 GEN
Solar/Wind Harmer
1.38
972235AH1-702 GEN1
Adder
1.187
972236AH1-702 GEN2
Adder
1.032
274764LEE CO EC;5U
Adder
4.332
274765LEE CO EC;6U
Adder
4.332
274762LEE CO EC;3U
Adder
4.322
274763LEE CO EC;4U
Adder
4.281
246937BC-WTG2
Solar/Wind Helper
11.279
270462AD2-086
Solar/Wind Helper
3.661
247522W1-056 GEN
Solar/Wind Helper
1.241
253378AE2-206_GEN
Solar/Wind Helper
0.703
24727205RPMNG3
50/50
3.126
959331AF2-224 GEN
Solar/Wind Harmer
17.404
963791AG1-232 GEN
Solar/Wind Harmer
14.314
965041AG1-368 GEN
Solar/Wind Harmer
10.01
970031AG2-029 GEN
Solar/Wind Harmer
24.321
247521TR3_G114
Solar/Wind Harmer
2.828
270191TR4_S_V150
Solar/Wind Harmer
2.524
965051AG1-369 GEN
Solar/Wind Harmer
4.202
270071AF1-092 GEN
Solar/Wind Harmer
12.357
24729505KEY G4
Adder
4.815
958711AF2-162 GEN
Solar/Wind Harmer
0.691
945581AF1-223 GEN
Solar/Wind Harmer
2.838
961761AG1-017 GEN
Solar/Wind Harmer
0.263
964611AG1-324 GEN
Solar/Wind Harmer
2.343
971771AH1-392 GEN
Solar/Wind Harmer
5.405
944161AF1-084 GEN
Solar/Wind Harmer
1.29
270526AF1-158 GEN
Solar/Wind Harmer
2.612
960681AF2-359 GEN
Solar/Wind Harmer
2.076
247536S-71 GEN
Solar/Wind Harmer
2.209
970289AG2-191 GEN
Solar/Wind Harmer
1.018
958391AF2-133 GEN
Solar/Wind Harmer
4.663
959141AF2-205 GEN
Solar/Wind Harmer
3.093
971549AH1-272 GEN
Solar/Wind Harmer
9.449
972037AH1-567 GEN1
Adder
0.093
274827FISK ;RP
Adder
3.936
274800UNIV PARK;3U
Adder
2.951
274801UNIV PARK;4U
Adder
2.951
960591AF2-350 GEN
Solar/Wind Harmer
5.05
274775LINCOLN ;6U
Adder
3.129
274776LINCOLN ;7U
Adder
3.129
274777LINCOLN ;8U
Adder
3.129
972228AH1-698 GEN2
Adder
1.862
972227AH1-698 GEN1
Adder
1.311
274687WILL CNTY;4U
Adder
13.992
274687WILL CNTY;4U
Adder
13.992
274675JOLIET 29;7U
Adder
15.32
274675JOLIET 29;7U
Adder
14.772
276893AG1-478 C
Solar/Wind Harmer
0.274
274728ELWOOD EC;5P
Adder
8.187
274731ELWOOD EC;2P
Adder
8.187
274733ELWOOD EC;3P
Adder
8.187
274735ELWOOD EC;4P
Adder
8.187
970833AG2-524 GEN
Solar/Wind Harmer
4.319
970833AG2-524 GEN
Solar/Wind Harmer
2.009
274744AC1-111 GEN8
Adder
2.743
274746AC1-111 G10
Adder
2.743
946581AF1-322 GEN
Solar/Wind Harmer
5.015
24691005MDL-2G C
Solar/Wind Harmer
1.812
270543AE2-219 C
Solar/Wind Harmer
4.878
970073AG2-061 GEN
Solar/Wind Harmer
1.126
274823ROCKFORD ;21
Adder
9.198
972267AH1-718 GEN
Adder
1.916
957201AF2-014 GEN
Solar/Wind Helper
8.91
270223U2-072_GEN1
Solar/Wind Helper
0.838
270224U2-072_GEN2
Solar/Wind Helper
0.838
270227U2-072_GEN3
Solar/Wind Helper
0.838
270228U2-072_GEN4
Solar/Wind Helper
0.838
270231U2-072_GEN5
Solar/Wind Helper
0.838
966831AG1-554 GEN
Solar/Wind Helper
0.907
270499AE1-146 GEN
Solar/Wind Helper
2.178
945641AF1-229 GEN
Solar/Wind Helper
1.037
24727005RPMNG1
50/50
3.145
965421AG1-410 GEN
Solar/Wind Harmer
112.283
965011AG1-365 GEN
Solar/Wind Harmer
17.404
270024AE2-089 GEN
Solar/Wind Harmer
3.673
24639705ELKHART HY
Adder
0.105
965651AG1-433 GEN
Solar/Wind Harmer
3.73
958861AF2-177 GEN
Solar/Wind Harmer
7.247
270216AD2-079_GEN
Solar/Wind Harmer
0.391
945371AF1-202 GEN
Solar/Wind Harmer
4.366
945111AF1-176 GEN
Solar/Wind Harmer
11.098
957891AF2-083 GEN
Solar/Wind Harmer
9.086
270449AD2-020 GEN
Solar/Wind Harmer
1.661
943021AE2-325 GEN
Solar/Wind Harmer
2.158
24441205WTRV SLR C
Solar/Wind Harmer
0.076
270005AE1-210 C O1
Solar/Wind Harmer
2.943
970825AG2-519 GEN
Solar/Wind Harmer
1.128
270594AE1-207 GEN
Solar/Wind Harmer
7.253
270032AE2-172
Solar/Wind Harmer
2.484
970373AG2-245 GEN
Solar/Wind Harmer
11.152
270055AF2-134 C O1
Solar/Wind Harmer
1.586
274751CRETE EC ;1U
Adder
2.558
274754CRETE EC ;4U
Adder
2.558
274723RIVER EC ;12
Adder
9.31
958381AF2-132 GEN
Solar/Wind Harmer
4.695
964861AG1-349 GEN
Solar/Wind Harmer
4.064
971917AH1-482 GEN
Solar/Wind Harmer
4.688
274812UNIV PK N;8U
Adder
2.581
276903AD2-071 C
Solar/Wind Harmer
5.088
274802UNIV PARK;5U
Adder
2.963
940581AE2-045 GEN
Solar/Wind Harmer
5.183
971605AH1-302 GEN
Solar/Wind Harmer
4.431
972207SS24-0001
Solar/Wind Harmer
11.126
274773LINCOLN ;4U
Adder
3.129
274774LINCOLN ;5U
Adder
3.129
274676JOLIET 29;8U
Adder
15.32
941551AE2-152 GEN
Solar/Wind Harmer
2.261
274674JOLIET 9 ;6U
Adder
7.67
274732ELWOOD EC;7P
Adder
8.187
274871GR RIDGE ;2U
Solar/Wind Harmer
3.801
274847GR RIDGE ;BU
Solar/Wind Harmer
2.499
274745AC1-111 GEN9
Adder
2.743
276694AA1-018 GEN2
Solar/Wind Harmer
3.093
276691AA1-018 GEN1
Solar/Wind Harmer
0.37
24791305MDL-5G
Solar/Wind Harmer
1.182
274861TOP CROP ;1U
Solar/Wind Harmer
2.968
274682WAUKEGAN ;7U
Adder
8.738
274828WAUKEGAN ;BP
Adder
5.364
276805AD2-038 GEN
Solar/Wind Harmer
2.483
939401AE1-172 GEN
Solar/Wind Harmer
6.713
962781AG1-127 GEN
Solar/Wind Harmer
4.575
274822ROCKFORD ;11
Adder
9.265
274761LEE CO EC;2U
Adder
4.322
274766LEE CO EC;7U
Adder
4.271
246936BC-WTG1
Solar/Wind Helper
11.279
270317AD1-130_GEN
Solar/Wind Helper
4.048
270485AE1-090_GEN
Solar/Wind Helper
0.318
270391AF1-285 GEN3
Solar/Wind Helper
0.567
270578AF1-285 GEN2
Solar/Wind Helper
0.567
960841AF2-375 GEN
Solar/Wind Helper
1.313
270286AF1-227 GEN2
Solar/Wind Helper
0.59
241840AF1-064_GEN
Solar/Wind Helper
0.468
241807AE2-176_GEN
Solar/Wind Helper
0.716
276882AE2-255 GEN
Solar/Wind Harmer
1.142
990497J1323
External Queue
1.3385206460952759
LAGNLTFEXP_LAGN->PJM
CLTF
4.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.965
TVALTFEXP_TVA->PJM
CLTF
1.731
NYPJM->LTFIMP_NY
CLTF
0.874
LGEELTFEXP_LGEE->PJM
CLTF
1.292
WECLTFEXP_WEC->PJM
CLTF
1.798
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.065
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.601
MECLTFEXP_MEC->PJM
CLTF
6.701
SIGELTFEXP_SIGE->PJM
CLTF
0.142
CPLELTFEXP_CPLE->PJM
CLTF
0.045
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.143
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-008B_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1          /*02DAV-BE     345.0 - 02LEMOYN     345.0
 DISCONNECT BUS 238670                                          /*02DVBSG1      25.0
 REMOVE MACHINE 1 FROM BUS 238670                               /*02DVBSG1      25.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-013_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238654 CKT 1          /*02LEMOYN     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238890 CKT 2          /*02LEMOYN     345.0 - 02LEMOYN     138.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238889 TO BUS 238961 CKT 1 /*02LEMOYN     345.0 - 02MIDWAY     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238889 TO BUS 238961 CKT 1 /*02LEMOYN     345.0 - 02MIDWAY     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238654 CKT 1   /*02LEMOYN     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238890 CKT 1   /*02LEMOYN     345.0 - 02LEMOYN     138.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-009_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-005_SRT-A'
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239171 CKT 2   /*02WLORAIN    345.0 - 02WLORG-2     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239172 CKT 3   /*02WLORAIN    345.0 - 02WLORG-3     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239173 CKT 4   /*02WLORAIN    345.0 - 02WLORG-4     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239174 CKT 5   /*02WLORAIN    345.0 - 02WLORG-5     13.8
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238566 CKT 1   /*02BEAVER     345.0 - 02WLORAIN    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1   /*02BEAVER     345.0 - AC2-103 TAP  345.0
 DISCONNECT BUS 239171                                   /*02WLORG-2     13.8
 DISCONNECT BUS 239172                                   /*02WLORG-3     13.8
 DISCONNECT BUS 239173                                   /*02WLORG-4     13.8
 DISCONNECT BUS 239174                                   /*02WLORG-5     13.8
 REMOVE MACHINE 2 FROM BUS 239171                        /*02WLORG-2     13.8
 REMOVE MACHINE 3 FROM BUS 239172                        /*02WLORG-3     13.8
 REMOVE MACHINE 4 FROM BUS 239173                        /*02WLORG-4     13.8
 REMOVE MACHINE 5 FROM BUS 239174                        /*02WLORG-5     13.8
END
CONTINGENCY 'ATSI_P2-3_OEC-345-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1          /*02BEAVER     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1          /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1878 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET POSTCONTRATING 1892 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1542 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET PRECONTRATING 1555 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-F1_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 2   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-12_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 1   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-3_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 1   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010B2_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1          /*02DAV-BE     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1878 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1542 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010B1_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1          /*02DAV-BE     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-810_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-809_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-007_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1          /*02DAV-BE     345.0 - 02BAY SH     345.0
 DISCONNECT BUS 238670                                          /*02DVBSG1      25.0
 REMOVE MACHINE 1 FROM BUS 238670                               /*02DVBSG1      25.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 241901 CKT 2 /*02BAY SH     345.0 - 02LALLENDORF 345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 241901 CKT 2 /*02BAY SH     345.0 - 02LALLENDORF 345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-004_SRT-A'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 238654 CKT 1   /*02BAY SH     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 241901 CKT 2   /*02BAY SH     345.0 - 02LALLENDORF 345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-005_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 238654 CKT 1          /*02BAY SH     345.0 - 02DAV-BE     345.0
 REDUCE BUS 238563 SHUNT BY 100 PERCENT                         /*02BAY SH     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 241901 CKT 2 /*02BAY SH     345.0 - 02LALLENDORF 345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 241901 CKT 2 /*02BAY SH     345.0 - 02LALLENDORF 345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1          /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 241901 CKT 2 /*02BAY SH     345.0 - 02LALLENDORF 345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 241901 CKT 2 /*02BAY SH     345.0 - 02LALLENDORF 345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1   /*02DAV-BE     345.0 - 02HAYES      345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-030_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'AEP_P1-3_#8072_05MARYSV 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2   /*05MARYSV     765.0 - 05MARYSV     345.0
END
CONTINGENCY 'AEP_P2-2_#5063_05SBERWI 345_1_SRT-A'
 OPEN BRANCH FROM BUS 242917 TO BUS 242942 CKT 1   /*05SBERW EQ     1.0 - 05SBERWI     345.0
 OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1   /*05SBERW EQ     1.0 - 05SBERWICK    69.0
 OPEN BRANCH FROM BUS 242917 TO BUS 243199 CKT 1   /*05SBERW EQ     1.0 - 05SBERW1-L    12.0
 OPEN BRANCH FROM BUS 242936 TO BUS 242942 CKT 1   /*05FOSTOR     345.0 - 05SBERWI     345.0
 OPEN BRANCH FROM BUS 945640 TO BUS 242942 CKT 1   /*AF1-229 TP   345.0 - 05SBERWI     345.0
END
CONTINGENCY 'AEP_P4_#7443_05DUMONT 765_A_SRT-A'
 OPEN BRANCH FROM BUS 243205 TO BUS 243206 CKT 1    /*05COOK       765.0 - 05DUMONT     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#7442_05SORENS 765_K2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#7444_05DUMONT 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243641 CKT 2    /*05DUMONT     765.0 - 05DUMONT 2EQ   1.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 243219 TO BUS 243641 CKT 2    /*05DUMONT     345.0 - 05DUMONT 2EQ   1.0
 OPEN BRANCH FROM BUS 243641 TO BUS 243642 CKT 2    /*05DUMONT 2EQ   1.0 - 05DUMONT T2   34.5
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#2995_05E LIMA 345_M_SRT-A'
 OPEN BRANCH FROM BUS 242935 TO BUS 245128 CKT 2   /*05E LIMA     345.0 - 05E.LIMA 2EQ   1.0
 OPEN BRANCH FROM BUS 242935 TO BUS 246929 CKT 1   /*05E LIMA     345.0 - 05MADDOX     345.0
 OPEN BRANCH FROM BUS 242989 TO BUS 245128 CKT 2   /*05E LIMA     138.0 - 05E.LIMA 2EQ   1.0
 OPEN BRANCH FROM BUS 245128 TO BUS 245148 CKT 2   /*05E.LIMA 2EQ   1.0 - 05E.LIMA T2   13.8
END
CONTINGENCY 'AEP_P7-1_#11010___SRT-A'
 OPEN BRANCH FROM BUS 242933 TO BUS 243211 CKT 1   /*05RPMONE     345.0 - 05ALLEN      345.0
 OPEN BRANCH FROM BUS 243211 TO BUS 243232 CKT 1   /*05ALLEN      345.0 - 05SORENS     345.0
END
CONTINGENCY 'AEP_P7-1_#17567_SRT-SL'
 OPEN BRANCH FROM BUS 242939 TO BUS 242945 CKT 1   /*05MARYSV     345.0 - 05SW LIM     345.0
 OPEN BRANCH FROM BUS 242939 TO BUS 290984 CKT 1   /*05MARYSV     345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-022T_SRT-A'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 265709 CKT 1   /*02LEMOYN     345.0 - 19MAPLE      345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-034T_SRT-A'
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 242936 CKT 1   /*02LALLENDORF 345.0 - 05FOSTOR     345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-033T_SRT-A'
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 238563 CKT 1   /*02LALLENDORF 345.0 - 02BAY SH     345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-025T_SRT-A'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 265709 CKT 1   /*02LEMOYN     345.0 - 19MAPLE      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 256583 CKT 1   /*19LULU       345.0 - 18MOROCCO    345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264613 CKT 1   /*19LULU       345.0 - 19MON34      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264839 CKT 1   /*19LULU       345.0 - 19MILAN      345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-023T_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 239344 CKT 3          /*02ALLEN      345.0 - 02ALLEN-2    138.0
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 256583 CKT 1          /*02ALLEN      345.0 - 18MOROCCO    345.0
 SET POSTCONTRATING 1394 BRANCH FROM BUS 238530 TO BUS 238961 CKT 1 /*02ALLEN      345.0 - 02MIDWAY     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 238530 TO BUS 238961 CKT 1 /*02ALLEN      345.0 - 02MIDWAY     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-022T_SRT-A'
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 239018 CKT 1   /*02ALLEN      345.0 - 02FULTON     345.0
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 256583 CKT 1   /*02ALLEN      345.0 - 18MOROCCO    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-009_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239289 CKT 1          /*02BEAVER     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-032T_SRT-A'
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 256583 CKT 1   /*19LULU       345.0 - 18MOROCCO    345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264613 CKT 1   /*19LULU       345.0 - 19MON34      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264839 CKT 1   /*19LULU       345.0 - 19MILAN      345.0
END
235117 to 235111 ckt 1
238563 to 238654 ckt 1
238654 to 239289 ckt 1
238654 to 241877 ckt 1
239289 to 238569 ckt 1
238889 to 238654 ckt 1
243211 to 242933 ckt 1
290984 to 242939 ckt 1
243458 to 246752 ckt 1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
242925 to 235117 ckt 1
246929 to 242935 ckt 1
242926 to 246751 ckt 1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
242933 to 965420 ckt 1
243232 to 246999 ckt 3
246999 to 290607 ckt Z1
290607 to 290608 ckt 1
243234 to 243228 ckt 1
248005 to 242528 ckt 1
256583 to 238530 ckt 1
264612 to 241901 ckt 1
241877 to 238569 ckt 1
965420 to 246929 ckt 1

Winter Peak Analysis

The New Service Request AH1-272 was evaluated as a 185.0 MW (123.9 MW Capacity) injection in the AEP area.

AH1-272 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 185.0 MW (185.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC179.81 %1180.0B2121.76
13.28
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-W_SENS
BreakerAC179.81 %1180.0B2121.75
13.28
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-W_SENS
BreakerAC179.81 %1180.0B2121.75
13.28
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC179.81 %1180.0B2121.75
13.28

Details for [AH1-272] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.81 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2121.76
MW Contribution:
13.28
IPD Plant:AH1-272
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
PJM_IPD
13.279

Details for [AH1-272] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.81 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2121.75
MW Contribution:
13.28
IPD Plant:AH1-272
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
PJM_IPD
13.279

Details for [AH1-272] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.81 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2121.75
MW Contribution:
13.28
IPD Plant:AH1-272
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
PJM_IPD
13.279

Details for [AH1-272] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.81 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2121.75
MW Contribution:
13.28
IPD Plant:AH1-272
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
PJM_IPD
13.279
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-W_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                   /*01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-W_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                   /*01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC120.49 %1737.0B2092.95
0.72
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC118.4 %1737.0B2056.53
0.73
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC116.41 %1737.0B2022.06
0.73
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC115.97 %1737.0B2014.34
0.7
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC108.18 %5133.0B5552.88
1.61
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC103.35 %3276.0B3385.78
0.74
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC101.76 %3276.0B3333.77
0.74
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC101.76 %3276.0B3333.74
0.74
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC111.9 %2991.0B3346.96
0.74
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC110.0 %2991.0B3290.17
0.74
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC110.0 %2991.0B3290.12
0.74
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC113.19 %4961.0B5615.13
2.12
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC103.69 %4961.0B5144.06
1.98
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC103.1 %4961.0B5114.58
2.13
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC102.1 %4961.0B5065.25
1.98
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC102.1 %4961.0B5065.17
1.98
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC103.66 %2219.0B2300.12
0.72
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC101.06 %2219.0B2242.58
0.73
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC100.53 %2219.0B2230.82
0.73
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC100.04 %2219.0B2219.82
0.7
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC106.03 %2219.0B2352.88
0.72
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC103.21 %2219.0B2290.26
0.73
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC102.89 %2219.0B2283.06
0.73
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC102.36 %2219.0B2271.47
0.7

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.49 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2092.95
MW Contribution:
0.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270191TR4_S_V150
Solar/Wind Harmer
3.471
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.032
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.18
270180AB1-006 GEN1
Solar/Wind Harmer
5.658
24791305MDL-5G
Solar/Wind Harmer
2.096
276741O09 GEN1
Solar/Wind Harmer
3.218
276726Z2-087_GEN
Solar/Wind Harmer
5.982
944221AF1-090 GEN
Solar/Wind Harmer
10.146
966831AG1-554 GEN
Solar/Wind Helper
0.281
24639705ELKHART HY
50/50
0.148
963791AG1-232 GEN
Solar/Wind Harmer
0.988
247521TR3_G114
Solar/Wind Harmer
4.555
24695305TIMB G C
Solar/Wind Harmer
3.924
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.418
276694AA1-018 GEN2
Solar/Wind Harmer
4.411
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.096
971343AH1-151 GEN
Solar/Wind Harmer
0.804
970169AG2-114 GEN
Solar/Wind Harmer
0.397
959341AF2-225 GEN
Solar/Wind Harmer
0.575
971087AG2-675 GEN
Solar/Wind Harmer
2.412
270445AC2-157 GEN2
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.152
944531AF1-118 GEN
Solar/Wind Harmer
2.052
970707AG2-453 GEN
Solar/Wind Harmer
1.192
970833AG2-524 GEN
Solar/Wind Harmer
3.705
958481AF2-142 GEN
Solar/Wind Harmer
0.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.856
274879MINONK ;1U
Solar/Wind Harmer
6.36
971675AH1-338 GEN
Solar/Wind Harmer
0.728
970781AG2-491 GEN
Solar/Wind Harmer
0.403
276903AD2-071 C
Solar/Wind Harmer
0.399
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.811
945391AF1-204 GEN
Solar/Wind Harmer
13.018
270391AF1-285 GEN3
Solar/Wind Helper
0.285
241847AF2-150_GEN
Solar/Wind Helper
0.265
965011AG1-365 GEN
Solar/Wind Harmer
1.139
945111AF1-176 GEN
Solar/Wind Harmer
0.876
945111AF1-176 GEN
Solar/Wind Harmer
4.774
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.668
970073AG2-061 GEN
Solar/Wind Harmer
1.641
274850MENDOTA H;RU
Solar/Wind Harmer
2.401
276863AD2-134 GEN
Solar/Wind Harmer
1.67
276861AD2-134 GEN
Solar/Wind Harmer
1.67
970571AG2-364 GEN
Solar/Wind Harmer
0.796
274856ECOGROVE ;U1
Solar/Wind Harmer
3.104
971681AH1-341 GEN
Solar/Wind Harmer
0.593
938861AE1-114 GEN
Solar/Wind Harmer
9.255
274858EASY ROAD;U2
Solar/Wind Harmer
3.688
270240V3-007_GEN2
Solar/Wind Harmer
4.477
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.353
965651AG1-433 GEN
Solar/Wind Harmer
8.19
972181SS23-001
Solar/Wind Harmer
0.439
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.299
970289AG2-191 GEN
Solar/Wind Harmer
0.08
274847GR RIDGE ;BU
Solar/Wind Harmer
4.836
946031AF1-268 GEN
Solar/Wind Harmer
0.346
959091AF2-200 GEN
Solar/Wind Harmer
0.804
274849CRESCENT ;1U
Solar/Wind Harmer
1.651
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.704
270227U2-072_GEN3
Solar/Wind Helper
1.995
270228U2-072_GEN4
Solar/Wind Helper
1.995
270231U2-072_GEN5
Solar/Wind Helper
1.995
270349AD2-093_GEN
Solar/Wind Helper
0.454
970031AG2-029 GEN
Solar/Wind Harmer
1.74
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.381
945581AF1-223 GEN
Solar/Wind Harmer
0
247620Y3-023
50/50
0.46
959331AF2-224 GEN
Solar/Wind Harmer
1.139
965041AG1-368 GEN
Solar/Wind Harmer
0.69
270031AE2-169
Solar/Wind Harmer
0.377
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.661
274861TOP CROP ;1U
Solar/Wind Harmer
4.856
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.349
971067AG2-660 GEN
Solar/Wind Harmer
1.608
24699105WLD G1 C
Solar/Wind Harmer
3.052
276655WTG1_EQ
Solar/Wind Harmer
6.603
963841AG1-237 GEN
Solar/Wind Harmer
11.714
270246TR4_N_V150
Solar/Wind Harmer
1.152
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.556
970291AG2-192 GEN
Solar/Wind Harmer
0.303
274871GR RIDGE ;2U
Solar/Wind Harmer
5.335
943121AE2-341 GEN
Solar/Wind Harmer
0.627
957471AF2-041 GEN
Solar/Wind Harmer
1.206
274848CAMPGROVE;RU
Solar/Wind Harmer
4.509
276785W4-005 GEN1
Solar/Wind Harmer
2.126
276849AB2-070 GEN2
Solar/Wind Harmer
1.825
957201AF2-014 GEN
Solar/Wind Helper
3.942
270284AF1-227 GEN1
Solar/Wind Helper
0.948
270428AC2-015 C
Solar/Wind Helper
0.374
253383AE2-342_GEN
Solar/Wind Helper
0.103
24729205KEY G1
50/50
6.727
270201AC2-176 GEN
Solar/Wind Harmer
4.618
970373AG2-245 GEN
Solar/Wind Harmer
0.924
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.493
274872LEEDK;1U
Solar/Wind Harmer
7.643
276872AE1-163_GEN1
Solar/Wind Harmer
5.502
959081AF2-199 GEN
Solar/Wind Harmer
0.402
274851PROVIDENC;RU
Solar/Wind Harmer
2.244
24386205FR-12G C
Solar/Wind Harmer
3.154
24379505HDWTR1G C
Solar/Wind Harmer
5.718
970885AG2-551 GEN
Solar/Wind Harmer
1.46
963741AG1-226 GEN
Solar/Wind Harmer
1.64
276686W4-005 GEN3
Solar/Wind Harmer
2.126
276764AC1-053 GEN2
Solar/Wind Harmer
2.764
276911AD2-131_GEN
Solar/Wind Harmer
0.168
943021AE2-325 GEN
Solar/Wind Harmer
2.95
964611AG1-324 GEN
Solar/Wind Harmer
0.402
276843GEN-1.7
Solar/Wind Harmer
0.568
958011AF2-095 GEN
Solar/Wind Harmer
0.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.447
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.615
24697905MDL-4G C
Solar/Wind Harmer
2.096
970819AG2-516 GEN
Solar/Wind Harmer
0.478
276646AC1-214 GEN2
Solar/Wind Harmer
1.204
274878BISHOP HL;2U
Solar/Wind Harmer
3.016
274854TWINGROVE;U2
Solar/Wind Harmer
5.82
965091AG1-374 GEN
Solar/Wind Harmer
1.13
965931AG1-462 GEN
Solar/Wind Harmer
0.961
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.995
270499AE1-146 GEN
Solar/Wind Helper
0.544
961051AF2-396 GEN
Solar/Wind Harmer
0.957
961051AF2-396 GEN
Solar/Wind Harmer
7.653
270599AE1-208 GEN
Solar/Wind Harmer
0.377
972231SS25-0005
Solar/Wind Harmer
0.703
971411AH1-196 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
3.454
276876AE1-163_GEN2
Solar/Wind Harmer
5.502
24386405FR-21G C
Solar/Wind Harmer
3.021
276782AC1-033 GEN
Solar/Wind Harmer
3.04
276763AC1-053 GEN1
Solar/Wind Harmer
2.764
971029AG2-637 GEN
Solar/Wind Harmer
0.481
270224U2-072_GEN2
Solar/Wind Helper
1.995
942871AE2-306 GEN
Solar/Wind Helper
0.214
945641AF1-229 GEN
Solar/Wind Helper
0.454
270541AE2-072 C
Solar/Wind Helper
0.459
970583AG2-370 GEN
50/50
2.758
965051AG1-369 GEN
Solar/Wind Harmer
0.293
970349AG2-230 GEN
Solar/Wind Harmer
0.721
971347AH1-153 GEN
Solar/Wind Harmer
0.24
961761AG1-017 GEN
Solar/Wind Harmer
0.449
960591AF2-350 GEN
Solar/Wind Harmer
0.428
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
16.272
247536S-71 GEN
Solar/Wind Harmer
3.798
926823AC1-168 GEN
Solar/Wind Harmer
4.874
274857EASY ROAD;U1
Solar/Wind Harmer
3.688
24725505WLD G2 C
Solar/Wind Harmer
3.052
276656WTG2_EQ
Solar/Wind Harmer
0.874
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.587
270462AD2-086
Solar/Wind Helper
1.788
270317AD1-130_GEN
Solar/Wind Helper
1.166
270287AF1-227 GEN3
Solar/Wind Helper
0.35
274887GEN-1.85
Solar/Wind Harmer
5.278
970833AG2-524 GEN
Solar/Wind Harmer
0.463
962781AG1-127 GEN
Solar/Wind Harmer
0.389
276868AE1-113 GEN
Solar/Wind Harmer
9.54
24697605MDL-3G C
Solar/Wind Harmer
3.143
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.804
24385905FR-11G C
Solar/Wind Harmer
5.939
946321AF1-296 GEN
Solar/Wind Harmer
11.289
274853TWINGROVE;U1
Solar/Wind Harmer
5.82
959611AF2-252 GEN
Solar/Wind Harmer
1.507
960611AF2-352 GEN
Solar/Wind Harmer
1.507
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.365
970193AG2-126 GEN
Solar/Wind Harmer
0.491
958581AF2-149 GEN
Solar/Wind Helper
0.222
24729405KEY G3
50/50
6.841
24729505KEY G4
50/50
6.727
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.436
970941AG2-585 GEN
Solar/Wind Harmer
0.236
276897AD1-100 C
Solar/Wind Harmer
56.232
971605AH1-302 GEN
Solar/Wind Harmer
6.283
970825AG2-519 GEN
Solar/Wind Harmer
0.274
276805AD2-038 GEN
Solar/Wind Harmer
4.799
970569AG2-363 GEN
Solar/Wind Harmer
1.195
276157O29GEN1
Solar/Wind Harmer
3.427
276645AC1-214 GEN1
Solar/Wind Harmer
1.204
939741AE1-205 GEN
Solar/Wind Harmer
0.767
960861AF2-377 GEN
50/50
2.345
24729305KEY G2
50/50
6.841
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.937
957891AF2-083 GEN
Solar/Wind Harmer
0.723
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.683
274888KELLY CRK;1U
Solar/Wind Harmer
5.846
276893AG1-478 C
Solar/Wind Harmer
0.338
270005AE1-210 C O1
Solar/Wind Harmer
6.493
276602WESTBROOK C
Solar/Wind Harmer
1.703
274863CRW1-WTG
Solar/Wind Harmer
4.717
274864CRW2-WTG
Solar/Wind Harmer
4.717
276603SUBLETTE C
Solar/Wind Harmer
0.798
24387305FR-4G C
Solar/Wind Harmer
4.532
24386605FR-22G C
Solar/Wind Harmer
3.021
24387005FR-3G C
Solar/Wind Harmer
2.991
274880W4-005 GEN4
Solar/Wind Harmer
2.126
246936BC-WTG1
Solar/Wind Helper
17.073
246937BC-WTG2
Solar/Wind Helper
17.073
960841AF2-375 GEN
Solar/Wind Helper
0.563
960851AF2-376 GEN
50/50
2.033
965021AG1-366 GEN
Solar/Wind Harmer
4.557
942221AE2-234 GEN
Solar/Wind Harmer
0.204
958861AF2-177 GEN
Solar/Wind Harmer
15.92
945371AF1-202 GEN
Solar/Wind Harmer
7.521
270505AE1-170 C O1
Solar/Wind Harmer
0.718
270032AE2-172
Solar/Wind Harmer
3.34
970825AG2-519 GEN
Solar/Wind Harmer
1.758
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.231
971997AH1-543 GEN
Solar/Wind Harmer
0.639
276889AE2-281 GEN
Solar/Wind Harmer
1.572
24691005MDL-2G C
Solar/Wind Harmer
3.143
971549AH1-272 GEN
Solar/Wind Harmer
0.722
276158O29GEN2
Solar/Wind Harmer
3.427
276708O09 GEN2
Solar/Wind Harmer
3.218
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.241
270543AE2-219 C
Solar/Wind Harmer
0.365
971993AH1-541 GEN
Solar/Wind Harmer
0.329
276621W2-048 GEN
Solar/Wind Harmer
5.054
942481AE2-261 GEN
Solar/Wind Harmer
1.011
270485AE1-090_GEN
Solar/Wind Helper
0.155
942111AE2-223 GEN
Solar/Wind Harmer
8.972
970241AG2-163 GEN
Solar/Wind Harmer
0.911
276174W4-005 GEN2
Solar/Wind Harmer
2.126
276668AB2-070 GEN1
Solar/Wind Harmer
1.825
970521AG2-332 GEN
50/50
10.74
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.192
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.016
276848AB2-070 GEN3
Solar/Wind Harmer
1.825
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.166
270471AD2-092_GEN
Solar/Wind Helper
0.454
276820AF1-078_GEN
Solar/Wind Helper
0.159
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.285
247522W1-056 GEN
Solar/Wind Helper
1.919
270286AF1-227 GEN2
Solar/Wind Helper
0.35
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.296
276838X2-022 GEN2
Solar/Wind Harmer
0.188
246938BC-WTG3
Solar/Wind Helper
17.366
990792J1392
External Queue
0.3027859032154083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.873
TVALTFEXP_TVA->PJM
CLTF
2.36
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.443
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.204
NYPJM->LTFIMP_NY
CLTF
1.303
MECLTFEXP_MEC->PJM
CLTF
9.641
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.255
LGEELTFEXP_LGEE->PJM
CLTF
1.795
LAGNLTFEXP_LAGN->PJM
CLTF
5.817
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.032
WECLTFEXP_WEC->PJM
CLTF
2.627
SIGELTFEXP_SIGE->PJM
CLTF
0.199

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.4 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2056.53
MW Contribution:
0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.018
270143AC1-141 CT2_
50/50
2.018
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24344105CKG2
50/50
6.328
270101X2-052 CT2
50/50
1.179
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.787
24642205MAYFLWER
50/50
0.618
962601AG1-109 GEN
50/50
2.385
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
24643105BUCHANAN
50/50
0.01
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
270100X2-052 CT1
50/50
1.179
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
944961AF1-161 GEN
50/50
2.385
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
270102X2-052 ST
50/50
1.276
970901AG2-562 GEN
50/50
4.835
24344005CKG1
50/50
5.553
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
960851AF2-376 GEN
50/50
2.087
24307105BERRINSP G
50/50
0.017
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
990792J1392
External Queue
0.30737584829330444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.41 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2022.06
MW Contribution:
0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
247620Y3-023
50/50
0.466
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
990792J1392
External Queue
0.30737584829330444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.97 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2014.34
MW Contribution:
0.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270191TR4_S_V150
Solar/Wind Harmer
3.383
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.91
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.095
270180AB1-006 GEN1
Solar/Wind Harmer
5.504
24791305MDL-5G
Solar/Wind Harmer
2.038
276741O09 GEN1
Solar/Wind Harmer
3.129
276726Z2-087_GEN
Solar/Wind Harmer
5.813
944221AF1-090 GEN
Solar/Wind Harmer
9.816
966831AG1-554 GEN
Solar/Wind Helper
0.286
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.971
247521TR3_G114
Solar/Wind Harmer
4.44
24695305TIMB G C
Solar/Wind Harmer
3.811
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.053
943591AF1-030 GEN
Solar/Wind Harmer
0.407
276694AA1-018 GEN2
Solar/Wind Harmer
4.296
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.038
971343AH1-151 GEN
Solar/Wind Harmer
0.782
970169AG2-114 GEN
Solar/Wind Harmer
0.386
959341AF2-225 GEN
Solar/Wind Harmer
0.559
971087AG2-675 GEN
Solar/Wind Harmer
2.343
270445AC2-157 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
2.012
270247TR4_N_V136
Solar/Wind Harmer
1.123
970707AG2-453 GEN
Solar/Wind Harmer
1.161
970833AG2-524 GEN
Solar/Wind Harmer
3.609
958481AF2-142 GEN
Solar/Wind Harmer
0.607
274862TOP CROP ;2U
Solar/Wind Harmer
4.729
274879MINONK ;1U
Solar/Wind Harmer
6.19
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
276903AD2-071 C
Solar/Wind Harmer
0.388
965651AG1-433 GEN
Solar/Wind Harmer
8.016
972181SS23-001
Solar/Wind Harmer
0.428
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.266
970289AG2-191 GEN
Solar/Wind Harmer
0.078
274847GR RIDGE ;BU
Solar/Wind Harmer
4.711
946031AF1-268 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
0.782
274849CRESCENT ;1U
Solar/Wind Harmer
1.605
957381AF2-032 GEN
Solar/Wind Harmer
0.066
276916AD2-100_GEN
Solar/Wind Harmer
0.681
270227U2-072_GEN3
Solar/Wind Helper
2.097
270228U2-072_GEN4
Solar/Wind Helper
2.097
270231U2-072_GEN5
Solar/Wind Helper
2.097
270349AD2-093_GEN
Solar/Wind Helper
0.517
270246TR4_N_V150
Solar/Wind Harmer
1.123
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.295
274871GR RIDGE ;2U
Solar/Wind Harmer
5.196
943121AE2-341 GEN
Solar/Wind Harmer
0.611
957471AF2-041 GEN
Solar/Wind Harmer
1.174
274848CAMPGROVE;RU
Solar/Wind Harmer
4.383
276785W4-005 GEN1
Solar/Wind Harmer
2.063
276849AB2-070 GEN2
Solar/Wind Harmer
1.771
957201AF2-014 GEN
Solar/Wind Helper
3.968
270284AF1-227 GEN1
Solar/Wind Helper
1.035
270428AC2-015 C
Solar/Wind Helper
0.376
253383AE2-342_GEN
Solar/Wind Helper
0.105
24729205KEY G1
50/50
6.593
270201AC2-176 GEN
Solar/Wind Harmer
4.506
970373AG2-245 GEN
Solar/Wind Harmer
0.901
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.326
274872LEEDK;1U
Solar/Wind Harmer
7.44
276872AE1-163_GEN1
Solar/Wind Harmer
5.354
959081AF2-199 GEN
Solar/Wind Harmer
0.391
274851PROVIDENC;RU
Solar/Wind Harmer
2.181
24386205FR-12G C
Solar/Wind Harmer
3.065
24379505HDWTR1G C
Solar/Wind Harmer
5.555
970885AG2-551 GEN
Solar/Wind Harmer
1.417
963741AG1-226 GEN
Solar/Wind Harmer
1.592
276686W4-005 GEN3
Solar/Wind Harmer
2.063
276764AC1-053 GEN2
Solar/Wind Harmer
2.681
276911AD2-131_GEN
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
0.935
961051AF2-396 GEN
Solar/Wind Harmer
7.477
270599AE1-208 GEN
Solar/Wind Harmer
0.368
972231SS25-0005
Solar/Wind Harmer
0.685
971411AH1-196 GEN
Solar/Wind Harmer
0.591
274855GSG-6 ;RU
Solar/Wind Harmer
3.361
276876AE1-163_GEN2
Solar/Wind Harmer
5.354
24386405FR-21G C
Solar/Wind Harmer
2.936
276782AC1-033 GEN
Solar/Wind Harmer
2.956
276763AC1-053 GEN1
Solar/Wind Harmer
2.681
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.786
945391AF1-204 GEN
Solar/Wind Harmer
12.593
270391AF1-285 GEN3
Solar/Wind Helper
0.3
241847AF2-150_GEN
Solar/Wind Helper
0.265
971029AG2-637 GEN
Solar/Wind Harmer
0.465
270224U2-072_GEN2
Solar/Wind Helper
2.097
942871AE2-306 GEN
Solar/Wind Helper
0.225
945641AF1-229 GEN
Solar/Wind Helper
0.46
270541AE2-072 C
Solar/Wind Helper
0.478
970031AG2-029 GEN
Solar/Wind Harmer
1.71
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.032
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.144
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
276868AE1-113 GEN
Solar/Wind Harmer
9.286
24697605MDL-3G C
Solar/Wind Harmer
3.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.782
24385905FR-11G C
Solar/Wind Harmer
5.772
946321AF1-296 GEN
Solar/Wind Harmer
10.97
274853TWINGROVE;U1
Solar/Wind Harmer
5.654
959611AF2-252 GEN
Solar/Wind Harmer
1.464
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.856
945111AF1-176 GEN
Solar/Wind Harmer
4.667
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.651
970073AG2-061 GEN
Solar/Wind Harmer
1.597
274850MENDOTA H;RU
Solar/Wind Harmer
2.337
276863AD2-134 GEN
Solar/Wind Harmer
1.625
276861AD2-134 GEN
Solar/Wind Harmer
1.625
970571AG2-364 GEN
Solar/Wind Harmer
0.775
274856ECOGROVE ;U1
Solar/Wind Harmer
3.02
971681AH1-341 GEN
Solar/Wind Harmer
0.577
938861AE1-114 GEN
Solar/Wind Harmer
9.003
274858EASY ROAD;U2
Solar/Wind Harmer
3.587
270240V3-007_GEN2
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.369
943021AE2-325 GEN
Solar/Wind Harmer
2.881
964611AG1-324 GEN
Solar/Wind Harmer
0.393
276843GEN-1.7
Solar/Wind Harmer
0.553
958011AF2-095 GEN
Solar/Wind Harmer
0.601
276691AA1-018 GEN1
Solar/Wind Harmer
0.435
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
24697905MDL-4G C
Solar/Wind Harmer
2.038
970819AG2-516 GEN
Solar/Wind Harmer
0.465
276646AC1-214 GEN2
Solar/Wind Harmer
1.17
274878BISHOP HL;2U
Solar/Wind Harmer
2.932
965931AG1-462 GEN
Solar/Wind Harmer
0.934
274854TWINGROVE;U2
Solar/Wind Harmer
5.654
965091AG1-374 GEN
Solar/Wind Harmer
1.098
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
2.097
270499AE1-146 GEN
Solar/Wind Helper
0.556
960611AF2-352 GEN
Solar/Wind Harmer
1.464
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.354
970193AG2-126 GEN
Solar/Wind Harmer
0.475
958581AF2-149 GEN
Solar/Wind Helper
0.216
970583AG2-370 GEN
50/50
2.702
965051AG1-369 GEN
Solar/Wind Harmer
0.285
970349AG2-230 GEN
Solar/Wind Harmer
0.704
971347AH1-153 GEN
Solar/Wind Harmer
0.235
961761AG1-017 GEN
Solar/Wind Harmer
0.438
960591AF2-350 GEN
Solar/Wind Harmer
0.417
958381AF2-132 GEN
Solar/Wind Harmer
0
960861AF2-377 GEN
50/50
2.286
24729305KEY G2
50/50
6.704
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.92
957891AF2-083 GEN
Solar/Wind Harmer
0.707
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.667
274888KELLY CRK;1U
Solar/Wind Harmer
5.697
276893AG1-478 C
Solar/Wind Harmer
0.33
270005AE1-210 C O1
Solar/Wind Harmer
6.326
276602WESTBROOK C
Solar/Wind Harmer
1.658
274863CRW1-WTG
Solar/Wind Harmer
4.59
274864CRW2-WTG
Solar/Wind Harmer
4.59
276603SUBLETTE C
Solar/Wind Harmer
0.776
24387305FR-4G C
Solar/Wind Harmer
4.404
24386605FR-22G C
Solar/Wind Harmer
2.936
24387005FR-3G C
Solar/Wind Harmer
2.906
274880W4-005 GEN4
Solar/Wind Harmer
2.063
246936BC-WTG1
Solar/Wind Helper
17.184
246937BC-WTG2
Solar/Wind Helper
17.184
960841AF2-375 GEN
Solar/Wind Helper
0.576
965021AG1-366 GEN
Solar/Wind Harmer
4.503
942221AE2-234 GEN
Solar/Wind Harmer
0.2
958861AF2-177 GEN
Solar/Wind Harmer
15.573
945371AF1-202 GEN
Solar/Wind Harmer
7.349
270505AE1-170 C O1
Solar/Wind Harmer
0.702
270032AE2-172
Solar/Wind Harmer
3.253
970825AG2-519 GEN
Solar/Wind Harmer
1.712
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.198
971997AH1-543 GEN
Solar/Wind Harmer
0.622
276889AE2-281 GEN
Solar/Wind Harmer
1.53
24691005MDL-2G C
Solar/Wind Harmer
3.058
971549AH1-272 GEN
Solar/Wind Harmer
0.702
276158O29GEN2
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
3.129
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.205
270543AE2-219 C
Solar/Wind Harmer
0.354
971993AH1-541 GEN
Solar/Wind Harmer
0.319
276621W2-048 GEN
Solar/Wind Harmer
4.9
942481AE2-261 GEN
Solar/Wind Harmer
0.979
270485AE1-090_GEN
Solar/Wind Helper
0.162
970521AG2-332 GEN
50/50
10.514
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
12.855
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.782
274877BISHOP HL;1U
Solar/Wind Harmer
2.932
276848AB2-070 GEN3
Solar/Wind Harmer
1.771
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.216
270471AD2-092_GEN
Solar/Wind Helper
0.517
276820AF1-078_GEN
Solar/Wind Helper
0.166
247620Y3-023
50/50
0.45
959331AF2-224 GEN
Solar/Wind Harmer
1.126
965041AG1-368 GEN
Solar/Wind Harmer
0.675
270031AE2-169
Solar/Wind Harmer
0.368
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.489
274861TOP CROP ;1U
Solar/Wind Harmer
4.729
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
15.839
247536S-71 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
4.742
274857EASY ROAD;U1
Solar/Wind Harmer
3.587
24725505WLD G2 C
Solar/Wind Harmer
2.968
276656WTG2_EQ
Solar/Wind Harmer
0.85
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.539
270462AD2-086
Solar/Wind Helper
1.865
270317AD1-130_GEN
Solar/Wind Helper
1.216
270287AF1-227 GEN3
Solar/Wind Helper
0.382
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.176
971067AG2-660 GEN
Solar/Wind Harmer
1.565
24699105WLD G1 C
Solar/Wind Harmer
2.968
276655WTG1_EQ
Solar/Wind Harmer
6.417
963841AG1-237 GEN
Solar/Wind Harmer
11.375
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.3
270286AF1-227 GEN2
Solar/Wind Helper
0.382
247522W1-056 GEN
Solar/Wind Helper
1.958
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.299
24729405KEY G3
50/50
6.704
24729505KEY G4
50/50
6.593
270043AE2-236 GEN
Solar/Wind Harmer
0.363
971771AH1-392 GEN
Solar/Wind Harmer
0.426
970941AG2-585 GEN
Solar/Wind Harmer
0.23
276897AD1-100 C
Solar/Wind Harmer
54.783
971605AH1-302 GEN
Solar/Wind Harmer
6.118
970825AG2-519 GEN
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
4.671
970569AG2-363 GEN
Solar/Wind Harmer
1.162
276157O29GEN1
Solar/Wind Harmer
3.332
276645AC1-214 GEN1
Solar/Wind Harmer
1.17
939741AE1-205 GEN
Solar/Wind Harmer
0.745
942111AE2-223 GEN
Solar/Wind Harmer
8.72
970241AG2-163 GEN
Solar/Wind Harmer
0.884
276174W4-005 GEN2
Solar/Wind Harmer
2.063
276668AB2-070 GEN1
Solar/Wind Harmer
1.771
276838X2-022 GEN2
Solar/Wind Harmer
0.183
246938BC-WTG3
Solar/Wind Helper
17.48
990792J1392
External Queue
0.3014104962348938
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.406
WECLTFEXP_WEC->PJM
CLTF
2.556
LAGNLTFEXP_LAGN->PJM
CLTF
5.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
SIGELTFEXP_SIGE->PJM
CLTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.67
NYPJM->LTFIMP_NY
CLTF
1.235
TVALTFEXP_TVA->PJM
CLTF
2.193
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.955
LGEELTFEXP_LGEE->PJM
CLTF
1.68
MECLTFEXP_MEC->PJM
CLTF
9.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.18 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5552.88
MW Contribution:
1.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
943591AF1-030 GEN
Solar/Wind Harmer
1.175
965681AG1-436 GEN
Solar/Wind Harmer
1.466
276694AA1-018 GEN2
Solar/Wind Harmer
12.077
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.221
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
1.086
959341AF2-225 GEN
Solar/Wind Harmer
1.549
971087AG2-675 GEN
Solar/Wind Harmer
6.516
24755605MDL-5G
Solar/Wind Harmer
5.234
270445AC2-157 GEN2
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
3.749
274847GR RIDGE ;BU
Solar/Wind Harmer
13.509
972181SS23-001
Solar/Wind Harmer
1.16
959091AF2-200 GEN
Solar/Wind Harmer
2.221
270055AF2-134 C O1
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
4.479
957381AF2-032 GEN
Solar/Wind Harmer
0.174
276916AD2-100_GEN
Solar/Wind Harmer
1.803
274776LINCOLN ;7U
50/50
19.245
274872LEEDK;1U
Solar/Wind Harmer
21.244
970373AG2-245 GEN
Solar/Wind Harmer
2.349
959081AF2-199 GEN
Solar/Wind Harmer
1.11
276872AE1-163_GEN1
Solar/Wind Harmer
14.997
964401AG1-302 GEN
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
6.088
24386205FR-12G C
Solar/Wind Harmer
7.802
276686W4-005 GEN3
Solar/Wind Harmer
5.559
276764AC1-053 GEN2
Solar/Wind Harmer
7.21
963741AG1-226 GEN
Solar/Wind Harmer
3.953
276911AD2-131_GEN
Solar/Wind Harmer
0.429
24344105CKG2
50/50
20.456
274661LASCO STA;2U
50/50
15.572
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
12.903
276882AE2-255 GEN
Solar/Wind Harmer
8.717
270526AF1-158 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
8.778
276726Z2-087_GEN
Solar/Wind Harmer
16.111
270180AB1-006 GEN1
Solar/Wind Harmer
14.131
24791305MDL-5G
Solar/Wind Harmer
5.234
944221AF1-090 GEN
Solar/Wind Harmer
25.717
970707AG2-453 GEN
Solar/Wind Harmer
3.393
970833AG2-524 GEN
Solar/Wind Harmer
10.343
958481AF2-142 GEN
Solar/Wind Harmer
1.705
274862TOP CROP ;2U
Solar/Wind Harmer
13.286
971675AH1-338 GEN
Solar/Wind Harmer
2.017
274879MINONK ;1U
Solar/Wind Harmer
17.434
970781AG2-491 GEN
Solar/Wind Harmer
1.006
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.085
945391AF1-204 GEN
Solar/Wind Harmer
29.773
274777LINCOLN ;8U
50/50
19.245
972231SS25-0005
Solar/Wind Harmer
1.856
274855GSG-6 ;RU
Solar/Wind Harmer
9.565
971411AH1-196 GEN
Solar/Wind Harmer
1.679
276876AE1-163_GEN2
Solar/Wind Harmer
14.997
276782AC1-033 GEN
Solar/Wind Harmer
8.241
961051AF2-396 GEN
Solar/Wind Harmer
1.98
961051AF2-396 GEN
Solar/Wind Harmer
15.837
24386405FR-21G C
Solar/Wind Harmer
7.474
276763AC1-053 GEN1
Solar/Wind Harmer
7.21
274770LINCOLN ;1U
50/50
19.245
274771LINCOLN ;2U
50/50
19.245
970073AG2-061 GEN
Solar/Wind Harmer
4.483
274850MENDOTA H;RU
Solar/Wind Harmer
6.65
276863AD2-134 GEN
Solar/Wind Harmer
4.625
276861AD2-134 GEN
Solar/Wind Harmer
4.625
274856ECOGROVE ;U1
Solar/Wind Harmer
8.538
971681AH1-341 GEN
Solar/Wind Harmer
1.629
938861AE1-114 GEN
Solar/Wind Harmer
25.406
970571AG2-364 GEN
Solar/Wind Harmer
2.167
274858EASY ROAD;U2
Solar/Wind Harmer
10.112
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
1.724
945111AF1-176 GEN
Solar/Wind Harmer
9.399
274887GEN-1.85
Solar/Wind Harmer
14.528
970833AG2-524 GEN
Solar/Wind Harmer
1.293
962781AG1-127 GEN
Solar/Wind Harmer
1.082
276868AE1-113 GEN
Solar/Wind Harmer
26.15
971171AH1-044 GEN
Solar/Wind Harmer
2.221
946321AF1-296 GEN
Solar/Wind Harmer
30.561
274853TWINGROVE;U1
Solar/Wind Harmer
15.584
959611AF2-252 GEN
Solar/Wind Harmer
4.036
960611AF2-352 GEN
Solar/Wind Harmer
4.036
24697605MDL-3G C
Solar/Wind Harmer
7.851
270181AB1-006 GEN2
Solar/Wind Harmer
1.57
24385905FR-11G C
Solar/Wind Harmer
14.693
970193AG2-126 GEN
Solar/Wind Harmer
1.123
274888KELLY CRK;1U
Solar/Wind Harmer
16.092
276893AG1-478 C
Solar/Wind Harmer
0.934
276602WESTBROOK C
Solar/Wind Harmer
4.717
274863CRW1-WTG
Solar/Wind Harmer
12.978
274864CRW2-WTG
Solar/Wind Harmer
12.978
276603SUBLETTE C
Solar/Wind Harmer
2.187
957891AF2-083 GEN
Solar/Wind Harmer
1.506
24387305FR-4G C
Solar/Wind Harmer
11.211
24386605FR-22G C
Solar/Wind Harmer
7.474
24387005FR-3G C
Solar/Wind Harmer
7.399
274880W4-005 GEN4
Solar/Wind Harmer
5.559
274773LINCOLN ;4U
50/50
19.245
972259AH1-714 GEN
50/50
40.401
962691AG1-118 GEN
Solar/Wind Harmer
3.425
971997AH1-543 GEN
Solar/Wind Harmer
1.764
276889AE2-281 GEN
Solar/Wind Harmer
4.285
276158O29GEN2
Solar/Wind Harmer
9.347
276708O09 GEN2
Solar/Wind Harmer
8.778
957841AF2-078 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
36.31
971341AH1-150 GEN
Solar/Wind Harmer
2.221
958391AF2-133 GEN
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
8.175
276843GEN-1.7
Solar/Wind Harmer
1.563
958011AF2-095 GEN
Solar/Wind Harmer
1.698
276691AA1-018 GEN1
Solar/Wind Harmer
1.224
958491AF2-143 GEN
Solar/Wind Harmer
1.681
970819AG2-516 GEN
Solar/Wind Harmer
1.316
276646AC1-214 GEN2
Solar/Wind Harmer
3.266
274878BISHOP HL;2U
Solar/Wind Harmer
8.175
945421AF1-207 GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
2.596
274854TWINGROVE;U2
Solar/Wind Harmer
15.584
965091AG1-374 GEN
Solar/Wind Harmer
3.027
24697905MDL-4G C
Solar/Wind Harmer
5.234
943021AE2-325 GEN
Solar/Wind Harmer
6.288
943121AE2-341 GEN
Solar/Wind Harmer
1.763
274871GR RIDGE ;2U
Solar/Wind Harmer
14.901
957471AF2-041 GEN
Solar/Wind Harmer
3.331
274848CAMPGROVE;RU
Solar/Wind Harmer
12.201
270449AD2-020 GEN
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
5.559
276849AB2-070 GEN2
Solar/Wind Harmer
4.769
274775LINCOLN ;6U
50/50
19.245
970349AG2-230 GEN
Solar/Wind Harmer
1.931
971347AH1-153 GEN
Solar/Wind Harmer
0.644
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.179
939401AE1-172 GEN
Solar/Wind Harmer
45.023
926823AC1-168 GEN
Solar/Wind Harmer
13.325
958381AF2-132 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
10.112
959141AF2-205 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
2.355
276615X2-022 GEN
Solar/Wind Harmer
4.125
270063AE2-323 C
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
13.286
971067AG2-660 GEN
Solar/Wind Harmer
4.441
971917AH1-482 GEN
Solar/Wind Harmer
16.838
276655WTG1_EQ
Solar/Wind Harmer
17.784
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
15.858
963841AG1-237 GEN
Solar/Wind Harmer
28.603
274772LINCOLN ;3U
50/50
19.245
274774LINCOLN ;5U
50/50
19.245
274660LASCO STA;1U
50/50
15.532
276897AD1-100 C
Solar/Wind Harmer
156.947
970941AG2-585 GEN
Solar/Wind Harmer
0.648
276805AD2-038 GEN
Solar/Wind Harmer
13.114
970569AG2-363 GEN
Solar/Wind Harmer
3.25
276157O29GEN1
Solar/Wind Harmer
9.347
971605AH1-302 GEN
Solar/Wind Harmer
15.823
276645AC1-214 GEN1
Solar/Wind Harmer
3.266
971771AH1-392 GEN
Solar/Wind Harmer
0.941
939741AE1-205 GEN
Solar/Wind Harmer
2.066
942111AE2-223 GEN
Solar/Wind Harmer
24.167
276174W4-005 GEN2
Solar/Wind Harmer
5.559
276668AB2-070 GEN1
Solar/Wind Harmer
4.769
276838X2-022 GEN2
Solar/Wind Harmer
0.49
970241AG2-163 GEN
Solar/Wind Harmer
2.196
270505AE1-170 C O1
Solar/Wind Harmer
1.526
24691005MDL-2G C
Solar/Wind Harmer
7.851
971993AH1-541 GEN
Solar/Wind Harmer
0.861
276621W2-048 GEN
Solar/Wind Harmer
13.134
971549AH1-272 GEN
Solar/Wind Harmer
1.613
942481AE2-261 GEN
Solar/Wind Harmer
2.597
276848AB2-070 GEN3
Solar/Wind Harmer
4.769
270444AC2-157 GEN1
Solar/Wind Harmer
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.121
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.48
LAGNLTFEXP_LAGN->PJM
CLTF
10.935
AH1-155LTFEXP_AH1-155->PJM
LTF
0.619
NYPJM->LTFIMP_NY
CLTF
3.181
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.742
SIGELTFEXP_SIGE->PJM
CLTF
0.318
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.453
LGEELTFEXP_LGEE->PJM
CLTF
1.229
TVALTFEXP_TVA->PJM
CLTF
3.54
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
80.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.429
WECLTFEXP_WEC->PJM
CLTF
7.219
MECLTFEXP_MEC->PJM
CLTF
25.034
AG2-052LTFEXP_AG2-052->PJM
LTF
0.413

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.35 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3385.78
MW Contribution:
0.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344305RKG2
50/50
11.11
24344305RKG2
50/50
11.015
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.462
972181SS23-001
Solar/Wind Harmer
0.486
274847GR RIDGE ;BU
Solar/Wind Harmer
5.462
959091AF2-200 GEN
Solar/Wind Harmer
0.9
274849CRESCENT ;1U
Solar/Wind Harmer
1.898
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.928
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.183
339241AF1-083 GEN
Solar/Wind Helper
0.191
253333AC1-068 GEN
Solar/Wind Helper
0.134
962211AG1-066 GEN
Solar/Wind Helper
0.209
970543AG2-345 GEN
50/50
4.595
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.434
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.631
970169AG2-114 GEN
Solar/Wind Harmer
0.471
943591AF1-030 GEN
Solar/Wind Harmer
0.469
276694AA1-018 GEN2
Solar/Wind Harmer
4.975
959341AF2-225 GEN
Solar/Wind Harmer
0.702
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.9
971087AG2-675 GEN
Solar/Wind Harmer
2.681
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.169
253338AC1-165 GEN
Solar/Wind Helper
0.134
24386205FR-12G C
Solar/Wind Harmer
5.238
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.651
970373AG2-245 GEN
Solar/Wind Harmer
1.197
276872AE1-163_GEN1
Solar/Wind Harmer
6.257
274872LEEDK;1U
Solar/Wind Harmer
8.563
276686W4-005 GEN3
Solar/Wind Harmer
2.725
276764AC1-053 GEN2
Solar/Wind Harmer
3.546
959081AF2-199 GEN
Solar/Wind Harmer
0.45
274851PROVIDENC;RU
Solar/Wind Harmer
2.579
276911AD2-131_GEN
Solar/Wind Harmer
0.221
25183208HLCRTG
Solar/Wind Helper
0.95
253325AC1-069 GEN
Solar/Wind Helper
0.134
970781AG2-491 GEN
Solar/Wind Harmer
0.66
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.916
970707AG2-453 GEN
Solar/Wind Harmer
1.341
970833AG2-524 GEN
Solar/Wind Harmer
4.183
958481AF2-142 GEN
Solar/Wind Harmer
0.702
274862TOP CROP ;2U
Solar/Wind Harmer
5.476
274879MINONK ;1U
Solar/Wind Harmer
7.21
971675AH1-338 GEN
Solar/Wind Harmer
0.815
965911AG1-460 GEN
Solar/Wind Harmer
1.062
339211AE2-254 GEN
Solar/Wind Helper
0.21
253406AD2-031_GEN
Solar/Wind Helper
0.185
24344205RKG1
50/50
11.484
270102X2-052 ST
50/50
1.391
970901AG2-562 GEN
50/50
5.27
24386405FR-21G C
Solar/Wind Harmer
5.018
972231SS25-0005
Solar/Wind Harmer
0.777
276876AE1-163_GEN2
Solar/Wind Harmer
6.257
276763AC1-053 GEN1
Solar/Wind Harmer
3.546
274855GSG-6 ;RU
Solar/Wind Harmer
3.867
971411AH1-196 GEN
Solar/Wind Harmer
0.679
961051AF2-396 GEN
Solar/Wind Harmer
0.893
961051AF2-396 GEN
Solar/Wind Harmer
7.143
276782AC1-033 GEN
Solar/Wind Harmer
3.483
944031AF1-071 GEN
Solar/Wind Helper
0.053
270407AB1-088 ST1
50/50
2.588
970023AG2-014 GEN
50/50
2.641
24344105CKG2
50/50
6.882
270101X2-052 CT2
50/50
1.285
270180AB1-006 GEN1
Solar/Wind Harmer
9.271
24791305MDL-5G
Solar/Wind Harmer
3.434
965791AG1-447 GEN
Solar/Wind Harmer
5.553
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.297
276882AE2-255 GEN
Solar/Wind Harmer
3.605
944221AF1-090 GEN
Solar/Wind Harmer
13.705
276741O09 GEN1
Solar/Wind Harmer
3.619
339221AD2-048_GEN
Solar/Wind Helper
0.342
270340AC2-060 GEN
Solar/Wind Helper
0.373
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.557
270100X2-052 CT1
50/50
1.285
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.856
970571AG2-364 GEN
Solar/Wind Harmer
0.909
274850MENDOTA H;RU
Solar/Wind Harmer
2.689
276863AD2-134 GEN
Solar/Wind Harmer
1.87
276861AD2-134 GEN
Solar/Wind Harmer
1.87
945111AF1-176 GEN
Solar/Wind Harmer
0.794
945111AF1-176 GEN
Solar/Wind Harmer
4.329
274856ECOGROVE ;U1
Solar/Wind Harmer
3.466
971681AH1-341 GEN
Solar/Wind Harmer
0.663
938861AE1-114 GEN
Solar/Wind Harmer
10.341
274858EASY ROAD;U2
Solar/Wind Harmer
4.117
970539AG2-343 GEN
50/50
9.19
274871GR RIDGE ;2U
Solar/Wind Harmer
6.025
943121AE2-341 GEN
Solar/Wind Harmer
0.704
276785W4-005 GEN1
Solar/Wind Harmer
2.725
276849AB2-070 GEN2
Solar/Wind Harmer
2.337
957471AF2-041 GEN
Solar/Wind Harmer
1.349
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.191
970289AG2-191 GEN
Solar/Wind Harmer
0.402
970291AG2-192 GEN
Solar/Wind Harmer
0.219
252524AE2-267 GEN
Solar/Wind Helper
0.255
253317AC1-085 GEN4
Solar/Wind Helper
0.596
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.065
270393AB1-087 CT1
50/50
2.588
270406AB1-088 CT1
50/50
2.588
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.742
971347AH1-153 GEN
Solar/Wind Harmer
0.247
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.48
939401AE1-172 GEN
Solar/Wind Harmer
18.931
276656WTG2_EQ
Solar/Wind Harmer
1.066
926823AC1-168 GEN
Solar/Wind Harmer
5.594
276615X2-022 GEN
Solar/Wind Harmer
2.045
274857EASY ROAD;U1
Solar/Wind Harmer
4.117
252507AC2-088 GEN
Solar/Wind Helper
0.377
24344205RKG1
50/50
11.484
24697605MDL-3G C
Solar/Wind Harmer
5.151
270181AB1-006 GEN2
Solar/Wind Harmer
1.03
24385905FR-11G C
Solar/Wind Harmer
9.864
970193AG2-126 GEN
Solar/Wind Harmer
0.751
274887GEN-1.85
Solar/Wind Harmer
5.918
970833AG2-524 GEN
Solar/Wind Harmer
0.523
274853TWINGROVE;U1
Solar/Wind Harmer
7.169
959611AF2-252 GEN
Solar/Wind Harmer
1.857
960611AF2-352 GEN
Solar/Wind Harmer
1.857
276868AE1-113 GEN
Solar/Wind Harmer
10.815
962781AG1-127 GEN
Solar/Wind Harmer
0.436
971171AH1-044 GEN
Solar/Wind Harmer
0.9
946321AF1-296 GEN
Solar/Wind Harmer
12.566
270063AE2-323 C
Solar/Wind Harmer
0
970091AG2-072 GEN
50/50
216.879
270394AB1-087 ST1
50/50
2.588
970783AG2-492 GEN
50/50
2.641
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.404
963841AG1-237 GEN
Solar/Wind Harmer
19.192
971917AH1-482 GEN
Solar/Wind Harmer
9.558
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.476
276655WTG1_EQ
Solar/Wind Harmer
8.054
971067AG2-660 GEN
Solar/Wind Harmer
1.799
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.099
270186AC1-089 GEN
Solar/Wind Helper
0.607
339231AF1-038_GEN
Solar/Wind Helper
0.187
270222AC2-111 GEN
Solar/Wind Helper
0.234
339250AF1-203 GEN
Solar/Wind Helper
0.056
24387305FR-4G C
Solar/Wind Harmer
7.526
24386605FR-22G C
Solar/Wind Harmer
5.018
24387005FR-3G C
Solar/Wind Harmer
4.967
274888KELLY CRK;1U
Solar/Wind Harmer
6.555
276893AG1-478 C
Solar/Wind Harmer
0.38
274863CRW1-WTG
Solar/Wind Harmer
5.543
274864CRW2-WTG
Solar/Wind Harmer
5.543
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276602WESTBROOK C
Solar/Wind Harmer
1.907
957891AF2-083 GEN
Solar/Wind Harmer
0.676
276603SUBLETTE C
Solar/Wind Harmer
0.892
270071AF1-092 GEN
Solar/Wind Harmer
0.563
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.583
253398AE2-221_GEN2
Solar/Wind Helper
0.583
339236AF1-050_GEN
Solar/Wind Helper
0.191
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.151
971997AH1-543 GEN
Solar/Wind Harmer
0.729
962691AG1-118 GEN
Solar/Wind Harmer
1.379
276889AE2-281 GEN
Solar/Wind Harmer
1.788
971993AH1-541 GEN
Solar/Wind Harmer
0.422
270505AE1-170 C O1
Solar/Wind Harmer
0.677
276621W2-048 GEN
Solar/Wind Harmer
6.511
942481AE2-261 GEN
Solar/Wind Harmer
1.324
276158O29GEN2
Solar/Wind Harmer
3.853
276708O09 GEN2
Solar/Wind Harmer
3.619
971549AH1-272 GEN
Solar/Wind Harmer
0.737
270367AC2-061_GEN
Solar/Wind Helper
0.469
962581AG1-107 GEN
Solar/Wind Helper
0.576
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.434
276843GEN-1.7
Solar/Wind Harmer
0.637
958011AF2-095 GEN
Solar/Wind Harmer
0.692
276691AA1-018 GEN1
Solar/Wind Harmer
0.504
274854TWINGROVE;U2
Solar/Wind Harmer
7.169
965091AG1-374 GEN
Solar/Wind Harmer
1.392
958491AF2-143 GEN
Solar/Wind Harmer
0.696
943021AE2-325 GEN
Solar/Wind Harmer
2.802
276646AC1-214 GEN2
Solar/Wind Harmer
1.384
970819AG2-516 GEN
Solar/Wind Harmer
0.534
274878BISHOP HL;2U
Solar/Wind Harmer
3.456
965931AG1-462 GEN
Solar/Wind Harmer
1.068
339206AE1-143 GEN
Solar/Wind Helper
0.35
241972AD1-140 GEN
Solar/Wind Helper
0.541
942601AE2-276 GEN
50/50
8.233
971605AH1-302 GEN
Solar/Wind Harmer
9.589
970241AG2-163 GEN
Solar/Wind Harmer
1.473
276897AD1-100 C
Solar/Wind Harmer
63.744
970941AG2-585 GEN
Solar/Wind Harmer
0.264
939741AE1-205 GEN
Solar/Wind Harmer
0.935
942111AE2-223 GEN
Solar/Wind Harmer
10.945
971771AH1-392 GEN
Solar/Wind Harmer
0.419
276805AD2-038 GEN
Solar/Wind Harmer
5.43
276174W4-005 GEN2
Solar/Wind Harmer
2.725
276668AB2-070 GEN1
Solar/Wind Harmer
2.337
970569AG2-363 GEN
Solar/Wind Harmer
1.363
276838X2-022 GEN2
Solar/Wind Harmer
0.243
276645AC1-214 GEN1
Solar/Wind Harmer
1.384
276157O29GEN1
Solar/Wind Harmer
3.853
270043AE2-236 GEN
Solar/Wind Harmer
0.177
961491AF2-440 GEN
Solar/Wind Helper
0.192
970031AG2-029 GEN
Solar/Wind Harmer
0.903
339216AC1-074 GEN
Solar/Wind Helper
0.395
253415AE1-040 GEN
Solar/Wind Helper
0.15
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.792
276848AB2-070 GEN3
Solar/Wind Harmer
2.337
971341AH1-150 GEN
Solar/Wind Harmer
0.9
274877BISHOP HL;1U
Solar/Wind Harmer
3.456
253316AC1-085 GEN3
Solar/Wind Helper
0.596
253433AC1-085 GEN1
Solar/Wind Helper
0.378
253349AC2-067 GEN
Solar/Wind Helper
0.161
253343AC1-166 GEN
Solar/Wind Helper
0.134
955142J992
External Queue
0.6478373408317566
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
991112J1481
External Queue
1.0048468112945557
990742J1381
External Queue
1.0048468112945557
950051AG9-018
External Queue
0.31534820795059204
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.815
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.362
MECLTFEXP_MEC->PJM
CLTF
10.182
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.557
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.828
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.205
NYPJM->LTFIMP_NY
CLTF
1.178
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
29.011
AH1-155LTFEXP_AH1-155->PJM
LTF
0.307
WECLTFEXP_WEC->PJM
CLTF
2.921
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.728

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.76 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3333.77
MW Contribution:
0.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970543AG2-345 GEN
50/50
4.61
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.444
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.633
970169AG2-114 GEN
Solar/Wind Harmer
0.473
943591AF1-030 GEN
Solar/Wind Harmer
0.471
276694AA1-018 GEN2
Solar/Wind Harmer
4.996
959341AF2-225 GEN
Solar/Wind Harmer
0.705
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.904
971087AG2-675 GEN
Solar/Wind Harmer
2.693
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.168
253338AC1-165 GEN
Solar/Wind Helper
0.133
270407AB1-088 ST1
50/50
2.594
970023AG2-014 GEN
50/50
2.649
24344105CKG2
50/50
6.908
270101X2-052 CT2
50/50
1.29
270180AB1-006 GEN1
Solar/Wind Harmer
9.298
24791305MDL-5G
Solar/Wind Harmer
3.444
965791AG1-447 GEN
Solar/Wind Harmer
5.575
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.327
276882AE2-255 GEN
Solar/Wind Harmer
3.62
944221AF1-090 GEN
Solar/Wind Harmer
13.766
276741O09 GEN1
Solar/Wind Harmer
3.635
339221AD2-048_GEN
Solar/Wind Helper
0.34
270340AC2-060 GEN
Solar/Wind Helper
0.37
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.545
970091AG2-072 GEN
50/50
217.153
270394AB1-087 ST1
50/50
2.594
970783AG2-492 GEN
50/50
2.649
970781AG2-491 GEN
Solar/Wind Harmer
0.662
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.994
970707AG2-453 GEN
Solar/Wind Harmer
1.346
970833AG2-524 GEN
Solar/Wind Harmer
4.2
958481AF2-142 GEN
Solar/Wind Harmer
0.705
274862TOP CROP ;2U
Solar/Wind Harmer
5.499
274879MINONK ;1U
Solar/Wind Harmer
7.24
971675AH1-338 GEN
Solar/Wind Harmer
0.819
965911AG1-460 GEN
Solar/Wind Harmer
1.067
339211AE2-254 GEN
Solar/Wind Helper
0.209
253406AD2-031_GEN
Solar/Wind Helper
0.184
270100X2-052 CT1
50/50
1.29
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.864
970571AG2-364 GEN
Solar/Wind Harmer
0.913
274850MENDOTA H;RU
Solar/Wind Harmer
2.7
276863AD2-134 GEN
Solar/Wind Harmer
1.878
276861AD2-134 GEN
Solar/Wind Harmer
1.878
945111AF1-176 GEN
Solar/Wind Harmer
0.798
945111AF1-176 GEN
Solar/Wind Harmer
4.348
274856ECOGROVE ;U1
Solar/Wind Harmer
3.482
971681AH1-341 GEN
Solar/Wind Harmer
0.666
938861AE1-114 GEN
Solar/Wind Harmer
10.387
274858EASY ROAD;U2
Solar/Wind Harmer
4.136
24344305RKG2
50/50
11.124
24344305RKG2
50/50
11.029
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.468
972181SS23-001
Solar/Wind Harmer
0.488
274847GR RIDGE ;BU
Solar/Wind Harmer
5.484
959091AF2-200 GEN
Solar/Wind Harmer
0.904
274849CRESCENT ;1U
Solar/Wind Harmer
1.906
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.932
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.182
339241AF1-083 GEN
Solar/Wind Helper
0.19
253333AC1-068 GEN
Solar/Wind Helper
0.133
962211AG1-066 GEN
Solar/Wind Helper
0.207
24344205RKG1
50/50
11.499
24697605MDL-3G C
Solar/Wind Harmer
5.166
270181AB1-006 GEN2
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
9.894
970193AG2-126 GEN
Solar/Wind Harmer
0.754
274887GEN-1.85
Solar/Wind Harmer
5.943
970833AG2-524 GEN
Solar/Wind Harmer
0.525
274853TWINGROVE;U1
Solar/Wind Harmer
7.199
959611AF2-252 GEN
Solar/Wind Harmer
1.864
960611AF2-352 GEN
Solar/Wind Harmer
1.864
276868AE1-113 GEN
Solar/Wind Harmer
10.861
962781AG1-127 GEN
Solar/Wind Harmer
0.438
971171AH1-044 GEN
Solar/Wind Harmer
0.904
946321AF1-296 GEN
Solar/Wind Harmer
12.624
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.908
339216AC1-074 GEN
Solar/Wind Helper
0.394
253415AE1-040 GEN
Solar/Wind Helper
0.149
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.435
963841AG1-237 GEN
Solar/Wind Harmer
19.253
971917AH1-482 GEN
Solar/Wind Harmer
9.588
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.499
276655WTG1_EQ
Solar/Wind Harmer
8.088
971067AG2-660 GEN
Solar/Wind Harmer
1.807
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.098
270186AC1-089 GEN
Solar/Wind Helper
0.604
339231AF1-038_GEN
Solar/Wind Helper
0.186
270222AC2-111 GEN
Solar/Wind Helper
0.233
339250AF1-203 GEN
Solar/Wind Helper
0.056
970539AG2-343 GEN
50/50
9.221
274871GR RIDGE ;2U
Solar/Wind Harmer
6.05
943121AE2-341 GEN
Solar/Wind Harmer
0.707
276785W4-005 GEN1
Solar/Wind Harmer
2.737
276849AB2-070 GEN2
Solar/Wind Harmer
2.347
957471AF2-041 GEN
Solar/Wind Harmer
1.355
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.214
970289AG2-191 GEN
Solar/Wind Harmer
0.404
970291AG2-192 GEN
Solar/Wind Harmer
0.22
252524AE2-267 GEN
Solar/Wind Helper
0.254
253317AC1-085 GEN4
Solar/Wind Helper
0.593
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.064
24386205FR-12G C
Solar/Wind Harmer
5.254
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.66
970373AG2-245 GEN
Solar/Wind Harmer
1.201
276872AE1-163_GEN1
Solar/Wind Harmer
6.283
274872LEEDK;1U
Solar/Wind Harmer
8.599
276686W4-005 GEN3
Solar/Wind Harmer
2.737
276764AC1-053 GEN2
Solar/Wind Harmer
3.562
959081AF2-199 GEN
Solar/Wind Harmer
0.452
274851PROVIDENC;RU
Solar/Wind Harmer
2.59
276911AD2-131_GEN
Solar/Wind Harmer
0.222
25183208HLCRTG
Solar/Wind Helper
0.946
253325AC1-069 GEN
Solar/Wind Helper
0.133
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.444
276843GEN-1.7
Solar/Wind Harmer
0.639
958011AF2-095 GEN
Solar/Wind Harmer
0.694
276691AA1-018 GEN1
Solar/Wind Harmer
0.506
274854TWINGROVE;U2
Solar/Wind Harmer
7.199
965091AG1-374 GEN
Solar/Wind Harmer
1.398
958491AF2-143 GEN
Solar/Wind Harmer
0.699
943021AE2-325 GEN
Solar/Wind Harmer
2.814
276646AC1-214 GEN2
Solar/Wind Harmer
1.39
970819AG2-516 GEN
Solar/Wind Harmer
0.536
274878BISHOP HL;2U
Solar/Wind Harmer
3.471
965931AG1-462 GEN
Solar/Wind Harmer
1.073
339206AE1-143 GEN
Solar/Wind Helper
0.348
241972AD1-140 GEN
Solar/Wind Helper
0.537
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.852
276848AB2-070 GEN3
Solar/Wind Harmer
2.347
971341AH1-150 GEN
Solar/Wind Harmer
0.904
274877BISHOP HL;1U
Solar/Wind Harmer
3.471
253316AC1-085 GEN3
Solar/Wind Helper
0.593
253433AC1-085 GEN1
Solar/Wind Helper
0.376
253349AC2-067 GEN
Solar/Wind Helper
0.16
253343AC1-166 GEN
Solar/Wind Helper
0.133
24344205RKG1
50/50
11.499
270102X2-052 ST
50/50
1.396
970901AG2-562 GEN
50/50
5.29
24386405FR-21G C
Solar/Wind Harmer
5.033
972231SS25-0005
Solar/Wind Harmer
0.781
276876AE1-163_GEN2
Solar/Wind Harmer
6.283
276763AC1-053 GEN1
Solar/Wind Harmer
3.562
274855GSG-6 ;RU
Solar/Wind Harmer
3.884
971411AH1-196 GEN
Solar/Wind Harmer
0.682
961051AF2-396 GEN
Solar/Wind Harmer
0.897
961051AF2-396 GEN
Solar/Wind Harmer
7.174
276782AC1-033 GEN
Solar/Wind Harmer
3.499
944031AF1-071 GEN
Solar/Wind Helper
0.052
270393AB1-087 CT1
50/50
2.594
270406AB1-088 CT1
50/50
2.594
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.745
971347AH1-153 GEN
Solar/Wind Harmer
0.248
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.482
939401AE1-172 GEN
Solar/Wind Harmer
19.009
276656WTG2_EQ
Solar/Wind Harmer
1.071
926823AC1-168 GEN
Solar/Wind Harmer
5.618
276615X2-022 GEN
Solar/Wind Harmer
2.054
274857EASY ROAD;U1
Solar/Wind Harmer
4.136
252507AC2-088 GEN
Solar/Wind Helper
0.376
942601AE2-276 GEN
50/50
8.252
971605AH1-302 GEN
Solar/Wind Harmer
9.618
970241AG2-163 GEN
Solar/Wind Harmer
1.478
276897AD1-100 C
Solar/Wind Harmer
64.004
970941AG2-585 GEN
Solar/Wind Harmer
0.265
939741AE1-205 GEN
Solar/Wind Harmer
0.939
942111AE2-223 GEN
Solar/Wind Harmer
10.99
971771AH1-392 GEN
Solar/Wind Harmer
0.421
276805AD2-038 GEN
Solar/Wind Harmer
5.453
276174W4-005 GEN2
Solar/Wind Harmer
2.737
276668AB2-070 GEN1
Solar/Wind Harmer
2.347
970569AG2-363 GEN
Solar/Wind Harmer
1.369
276838X2-022 GEN2
Solar/Wind Harmer
0.244
276645AC1-214 GEN1
Solar/Wind Harmer
1.39
276157O29GEN1
Solar/Wind Harmer
3.871
270043AE2-236 GEN
Solar/Wind Harmer
0.178
961491AF2-440 GEN
Solar/Wind Helper
0.191
24387305FR-4G C
Solar/Wind Harmer
7.549
24386605FR-22G C
Solar/Wind Harmer
5.033
24387005FR-3G C
Solar/Wind Harmer
4.983
274888KELLY CRK;1U
Solar/Wind Harmer
6.582
276893AG1-478 C
Solar/Wind Harmer
0.382
274863CRW1-WTG
Solar/Wind Harmer
5.566
274864CRW2-WTG
Solar/Wind Harmer
5.566
274880W4-005 GEN4
Solar/Wind Harmer
2.737
276602WESTBROOK C
Solar/Wind Harmer
1.915
957891AF2-083 GEN
Solar/Wind Harmer
0.679
276603SUBLETTE C
Solar/Wind Harmer
0.896
270071AF1-092 GEN
Solar/Wind Harmer
0.566
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.581
253398AE2-221_GEN2
Solar/Wind Helper
0.581
339236AF1-050_GEN
Solar/Wind Helper
0.19
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.166
971997AH1-543 GEN
Solar/Wind Harmer
0.732
962691AG1-118 GEN
Solar/Wind Harmer
1.385
276889AE2-281 GEN
Solar/Wind Harmer
1.795
971993AH1-541 GEN
Solar/Wind Harmer
0.424
270505AE1-170 C O1
Solar/Wind Harmer
0.68
276621W2-048 GEN
Solar/Wind Harmer
6.539
942481AE2-261 GEN
Solar/Wind Harmer
1.329
276158O29GEN2
Solar/Wind Harmer
3.871
276708O09 GEN2
Solar/Wind Harmer
3.635
971549AH1-272 GEN
Solar/Wind Harmer
0.741
270367AC2-061_GEN
Solar/Wind Helper
0.466
962581AG1-107 GEN
Solar/Wind Helper
0.573
955142J992
External Queue
0.6478373408317566
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
991112J1481
External Queue
1.0048468112945557
990742J1381
External Queue
1.0048468112945557
950051AG9-018
External Queue
0.31534820795059204
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.814
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
NYPJM->LTFIMP_NY
CLTF
1.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.087
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.943
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
WECLTFEXP_WEC->PJM
CLTF
2.934
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.797
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.308
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.34
MECLTFEXP_MEC->PJM
CLTF
10.238
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.76 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3333.74
MW Contribution:
0.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970543AG2-345 GEN
50/50
4.61
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.444
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.633
970169AG2-114 GEN
Solar/Wind Harmer
0.473
943591AF1-030 GEN
Solar/Wind Harmer
0.471
276694AA1-018 GEN2
Solar/Wind Harmer
4.996
959341AF2-225 GEN
Solar/Wind Harmer
0.705
276901AD2-066 C O1
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
1.29
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.864
970571AG2-364 GEN
Solar/Wind Harmer
0.913
274850MENDOTA H;RU
Solar/Wind Harmer
2.7
276863AD2-134 GEN
Solar/Wind Harmer
1.878
276861AD2-134 GEN
Solar/Wind Harmer
1.878
945111AF1-176 GEN
Solar/Wind Harmer
0.798
945111AF1-176 GEN
Solar/Wind Harmer
4.348
274856ECOGROVE ;U1
Solar/Wind Harmer
3.482
971681AH1-341 GEN
Solar/Wind Harmer
0.666
938861AE1-114 GEN
Solar/Wind Harmer
10.387
274858EASY ROAD;U2
Solar/Wind Harmer
4.136
270393AB1-087 CT1
50/50
2.594
270406AB1-088 CT1
50/50
2.594
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.745
971347AH1-153 GEN
Solar/Wind Harmer
0.248
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.482
939401AE1-172 GEN
Solar/Wind Harmer
19.009
276656WTG2_EQ
Solar/Wind Harmer
1.071
970091AG2-072 GEN
50/50
217.153
270394AB1-087 ST1
50/50
2.594
970783AG2-492 GEN
50/50
2.649
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.435
963841AG1-237 GEN
Solar/Wind Harmer
19.253
971917AH1-482 GEN
Solar/Wind Harmer
9.588
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.499
276655WTG1_EQ
Solar/Wind Harmer
8.088
971067AG2-660 GEN
Solar/Wind Harmer
1.807
971343AH1-151 GEN
Solar/Wind Harmer
0.904
971087AG2-675 GEN
Solar/Wind Harmer
2.693
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.168
253338AC1-165 GEN
Solar/Wind Helper
0.133
970539AG2-343 GEN
50/50
9.221
274871GR RIDGE ;2U
Solar/Wind Harmer
6.05
943121AE2-341 GEN
Solar/Wind Harmer
0.707
276785W4-005 GEN1
Solar/Wind Harmer
2.737
276849AB2-070 GEN2
Solar/Wind Harmer
2.347
957471AF2-041 GEN
Solar/Wind Harmer
1.355
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.214
970289AG2-191 GEN
Solar/Wind Harmer
0.404
970291AG2-192 GEN
Solar/Wind Harmer
0.22
252524AE2-267 GEN
Solar/Wind Helper
0.254
253317AC1-085 GEN4
Solar/Wind Helper
0.593
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.064
970781AG2-491 GEN
Solar/Wind Harmer
0.662
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.994
970707AG2-453 GEN
Solar/Wind Harmer
1.346
970833AG2-524 GEN
Solar/Wind Harmer
4.2
958481AF2-142 GEN
Solar/Wind Harmer
0.705
274862TOP CROP ;2U
Solar/Wind Harmer
5.499
274879MINONK ;1U
Solar/Wind Harmer
7.24
971675AH1-338 GEN
Solar/Wind Harmer
0.819
965911AG1-460 GEN
Solar/Wind Harmer
1.067
339211AE2-254 GEN
Solar/Wind Helper
0.209
253406AD2-031_GEN
Solar/Wind Helper
0.184
926823AC1-168 GEN
Solar/Wind Harmer
5.618
276615X2-022 GEN
Solar/Wind Harmer
2.054
274857EASY ROAD;U1
Solar/Wind Harmer
4.136
252507AC2-088 GEN
Solar/Wind Helper
0.376
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.166
971997AH1-543 GEN
Solar/Wind Harmer
0.732
962691AG1-118 GEN
Solar/Wind Harmer
1.385
276889AE2-281 GEN
Solar/Wind Harmer
1.795
971993AH1-541 GEN
Solar/Wind Harmer
0.424
270505AE1-170 C O1
Solar/Wind Harmer
0.68
276621W2-048 GEN
Solar/Wind Harmer
6.539
942481AE2-261 GEN
Solar/Wind Harmer
1.329
276158O29GEN2
Solar/Wind Harmer
3.871
276708O09 GEN2
Solar/Wind Harmer
3.635
971549AH1-272 GEN
Solar/Wind Harmer
0.741
270367AC2-061_GEN
Solar/Wind Helper
0.466
962581AG1-107 GEN
Solar/Wind Helper
0.573
24387305FR-4G C
Solar/Wind Harmer
7.549
24386605FR-22G C
Solar/Wind Harmer
5.033
24387005FR-3G C
Solar/Wind Harmer
4.983
274888KELLY CRK;1U
Solar/Wind Harmer
6.582
276893AG1-478 C
Solar/Wind Harmer
0.382
274863CRW1-WTG
Solar/Wind Harmer
5.566
274864CRW2-WTG
Solar/Wind Harmer
5.566
274880W4-005 GEN4
Solar/Wind Harmer
2.737
276602WESTBROOK C
Solar/Wind Harmer
1.915
957891AF2-083 GEN
Solar/Wind Harmer
0.679
276603SUBLETTE C
Solar/Wind Harmer
0.896
270071AF1-092 GEN
Solar/Wind Harmer
0.566
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.581
253398AE2-221_GEN2
Solar/Wind Helper
0.581
339236AF1-050_GEN
Solar/Wind Helper
0.19
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.444
276843GEN-1.7
Solar/Wind Harmer
0.639
958011AF2-095 GEN
Solar/Wind Harmer
0.694
276691AA1-018 GEN1
Solar/Wind Harmer
0.506
274854TWINGROVE;U2
Solar/Wind Harmer
7.199
965091AG1-374 GEN
Solar/Wind Harmer
1.398
958491AF2-143 GEN
Solar/Wind Harmer
0.699
943021AE2-325 GEN
Solar/Wind Harmer
2.814
276646AC1-214 GEN2
Solar/Wind Harmer
1.39
970819AG2-516 GEN
Solar/Wind Harmer
0.536
274878BISHOP HL;2U
Solar/Wind Harmer
3.471
965931AG1-462 GEN
Solar/Wind Harmer
1.073
339206AE1-143 GEN
Solar/Wind Helper
0.348
241972AD1-140 GEN
Solar/Wind Helper
0.537
270407AB1-088 ST1
50/50
2.594
970023AG2-014 GEN
50/50
2.649
24344105CKG2
50/50
6.908
270101X2-052 CT2
50/50
1.29
270180AB1-006 GEN1
Solar/Wind Harmer
9.298
24791305MDL-5G
Solar/Wind Harmer
3.444
965791AG1-447 GEN
Solar/Wind Harmer
5.575
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.327
276882AE2-255 GEN
Solar/Wind Harmer
3.62
944221AF1-090 GEN
Solar/Wind Harmer
13.766
276741O09 GEN1
Solar/Wind Harmer
3.635
339221AD2-048_GEN
Solar/Wind Helper
0.34
270340AC2-060 GEN
Solar/Wind Helper
0.37
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.545
24386205FR-12G C
Solar/Wind Harmer
5.254
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.66
970373AG2-245 GEN
Solar/Wind Harmer
1.201
276872AE1-163_GEN1
Solar/Wind Harmer
6.283
274872LEEDK;1U
Solar/Wind Harmer
8.599
276686W4-005 GEN3
Solar/Wind Harmer
2.737
276764AC1-053 GEN2
Solar/Wind Harmer
3.562
959081AF2-199 GEN
Solar/Wind Harmer
0.452
274851PROVIDENC;RU
Solar/Wind Harmer
2.59
276911AD2-131_GEN
Solar/Wind Harmer
0.222
25183208HLCRTG
Solar/Wind Helper
0.946
253325AC1-069 GEN
Solar/Wind Helper
0.133
24344305RKG2
50/50
11.124
24344305RKG2
50/50
11.029
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.468
972181SS23-001
Solar/Wind Harmer
0.488
274847GR RIDGE ;BU
Solar/Wind Harmer
5.484
959091AF2-200 GEN
Solar/Wind Harmer
0.904
274849CRESCENT ;1U
Solar/Wind Harmer
1.906
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.932
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.182
339241AF1-083 GEN
Solar/Wind Helper
0.19
253333AC1-068 GEN
Solar/Wind Helper
0.133
962211AG1-066 GEN
Solar/Wind Helper
0.207
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.852
276848AB2-070 GEN3
Solar/Wind Harmer
2.347
971341AH1-150 GEN
Solar/Wind Harmer
0.904
274877BISHOP HL;1U
Solar/Wind Harmer
3.471
253316AC1-085 GEN3
Solar/Wind Helper
0.593
253433AC1-085 GEN1
Solar/Wind Helper
0.376
253349AC2-067 GEN
Solar/Wind Helper
0.16
253343AC1-166 GEN
Solar/Wind Helper
0.133
24344205RKG1
50/50
11.499
270102X2-052 ST
50/50
1.396
970901AG2-562 GEN
50/50
5.29
24386405FR-21G C
Solar/Wind Harmer
5.033
972231SS25-0005
Solar/Wind Harmer
0.781
276876AE1-163_GEN2
Solar/Wind Harmer
6.283
276763AC1-053 GEN1
Solar/Wind Harmer
3.562
274855GSG-6 ;RU
Solar/Wind Harmer
3.884
971411AH1-196 GEN
Solar/Wind Harmer
0.682
961051AF2-396 GEN
Solar/Wind Harmer
0.897
961051AF2-396 GEN
Solar/Wind Harmer
7.174
276782AC1-033 GEN
Solar/Wind Harmer
3.499
944031AF1-071 GEN
Solar/Wind Helper
0.052
24344205RKG1
50/50
11.499
24697605MDL-3G C
Solar/Wind Harmer
5.166
270181AB1-006 GEN2
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
9.894
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.098
270186AC1-089 GEN
Solar/Wind Helper
0.604
339231AF1-038_GEN
Solar/Wind Helper
0.186
270222AC2-111 GEN
Solar/Wind Helper
0.233
339250AF1-203 GEN
Solar/Wind Helper
0.056
970193AG2-126 GEN
Solar/Wind Harmer
0.754
274887GEN-1.85
Solar/Wind Harmer
5.943
970833AG2-524 GEN
Solar/Wind Harmer
0.525
274853TWINGROVE;U1
Solar/Wind Harmer
7.199
959611AF2-252 GEN
Solar/Wind Harmer
1.864
960611AF2-352 GEN
Solar/Wind Harmer
1.864
276868AE1-113 GEN
Solar/Wind Harmer
10.861
962781AG1-127 GEN
Solar/Wind Harmer
0.438
971171AH1-044 GEN
Solar/Wind Harmer
0.904
946321AF1-296 GEN
Solar/Wind Harmer
12.624
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.908
339216AC1-074 GEN
Solar/Wind Helper
0.394
253415AE1-040 GEN
Solar/Wind Helper
0.149
942601AE2-276 GEN
50/50
8.252
971605AH1-302 GEN
Solar/Wind Harmer
9.618
970241AG2-163 GEN
Solar/Wind Harmer
1.478
276897AD1-100 C
Solar/Wind Harmer
64.004
970941AG2-585 GEN
Solar/Wind Harmer
0.265
939741AE1-205 GEN
Solar/Wind Harmer
0.939
942111AE2-223 GEN
Solar/Wind Harmer
10.99
971771AH1-392 GEN
Solar/Wind Harmer
0.421
276805AD2-038 GEN
Solar/Wind Harmer
5.453
276174W4-005 GEN2
Solar/Wind Harmer
2.737
276668AB2-070 GEN1
Solar/Wind Harmer
2.347
970569AG2-363 GEN
Solar/Wind Harmer
1.369
276838X2-022 GEN2
Solar/Wind Harmer
0.244
276645AC1-214 GEN1
Solar/Wind Harmer
1.39
276157O29GEN1
Solar/Wind Harmer
3.871
270043AE2-236 GEN
Solar/Wind Harmer
0.178
961491AF2-440 GEN
Solar/Wind Helper
0.191
955142J992
External Queue
0.6478373408317566
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
991112J1481
External Queue
1.0048468112945557
990742J1381
External Queue
1.0048468112945557
950051AG9-018
External Queue
0.31534820795059204
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.814
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
NYPJM->LTFIMP_NY
CLTF
1.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.087
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.943
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
WECLTFEXP_WEC->PJM
CLTF
2.934
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.797
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.308
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.34
MECLTFEXP_MEC->PJM
CLTF
10.238
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.9 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3346.96
MW Contribution:
0.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970543AG2-345 GEN
50/50
4.595
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.434
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.631
970169AG2-114 GEN
Solar/Wind Harmer
0.471
943591AF1-030 GEN
Solar/Wind Harmer
0.469
276694AA1-018 GEN2
Solar/Wind Harmer
4.975
959341AF2-225 GEN
Solar/Wind Harmer
0.702
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.9
971087AG2-675 GEN
Solar/Wind Harmer
2.681
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.169
253338AC1-165 GEN
Solar/Wind Helper
0.134
24344305RKG2
50/50
11.11
24344305RKG2
50/50
11.015
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.462
972181SS23-001
Solar/Wind Harmer
0.486
274847GR RIDGE ;BU
Solar/Wind Harmer
5.462
959091AF2-200 GEN
Solar/Wind Harmer
0.9
274849CRESCENT ;1U
Solar/Wind Harmer
1.898
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.928
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.183
339241AF1-083 GEN
Solar/Wind Helper
0.191
253333AC1-068 GEN
Solar/Wind Helper
0.134
962211AG1-066 GEN
Solar/Wind Helper
0.209
24386205FR-12G C
Solar/Wind Harmer
5.238
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.651
970373AG2-245 GEN
Solar/Wind Harmer
1.197
276872AE1-163_GEN1
Solar/Wind Harmer
6.257
274872LEEDK;1U
Solar/Wind Harmer
8.563
276686W4-005 GEN3
Solar/Wind Harmer
2.725
276764AC1-053 GEN2
Solar/Wind Harmer
3.546
959081AF2-199 GEN
Solar/Wind Harmer
0.45
274851PROVIDENC;RU
Solar/Wind Harmer
2.579
276911AD2-131_GEN
Solar/Wind Harmer
0.221
25183208HLCRTG
Solar/Wind Helper
0.95
253325AC1-069 GEN
Solar/Wind Helper
0.134
270407AB1-088 ST1
50/50
2.588
970023AG2-014 GEN
50/50
2.641
24344105CKG2
50/50
6.882
270101X2-052 CT2
50/50
1.285
270180AB1-006 GEN1
Solar/Wind Harmer
9.271
24791305MDL-5G
Solar/Wind Harmer
3.434
965791AG1-447 GEN
Solar/Wind Harmer
5.553
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.297
276882AE2-255 GEN
Solar/Wind Harmer
3.605
944221AF1-090 GEN
Solar/Wind Harmer
13.705
276741O09 GEN1
Solar/Wind Harmer
3.619
339221AD2-048_GEN
Solar/Wind Helper
0.342
270340AC2-060 GEN
Solar/Wind Helper
0.373
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.557
970781AG2-491 GEN
Solar/Wind Harmer
0.66
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.916
970707AG2-453 GEN
Solar/Wind Harmer
1.341
970833AG2-524 GEN
Solar/Wind Harmer
4.183
958481AF2-142 GEN
Solar/Wind Harmer
0.702
274862TOP CROP ;2U
Solar/Wind Harmer
5.476
274879MINONK ;1U
Solar/Wind Harmer
7.21
971675AH1-338 GEN
Solar/Wind Harmer
0.815
965911AG1-460 GEN
Solar/Wind Harmer
1.062
339211AE2-254 GEN
Solar/Wind Helper
0.21
253406AD2-031_GEN
Solar/Wind Helper
0.185
24344205RKG1
50/50
11.484
270102X2-052 ST
50/50
1.391
970901AG2-562 GEN
50/50
5.27
24386405FR-21G C
Solar/Wind Harmer
5.018
972231SS25-0005
Solar/Wind Harmer
0.777
276876AE1-163_GEN2
Solar/Wind Harmer
6.257
276763AC1-053 GEN1
Solar/Wind Harmer
3.546
274855GSG-6 ;RU
Solar/Wind Harmer
3.867
971411AH1-196 GEN
Solar/Wind Harmer
0.679
961051AF2-396 GEN
Solar/Wind Harmer
0.893
961051AF2-396 GEN
Solar/Wind Harmer
7.143
276782AC1-033 GEN
Solar/Wind Harmer
3.483
944031AF1-071 GEN
Solar/Wind Helper
0.053
270100X2-052 CT1
50/50
1.285
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.856
970571AG2-364 GEN
Solar/Wind Harmer
0.909
274850MENDOTA H;RU
Solar/Wind Harmer
2.689
276863AD2-134 GEN
Solar/Wind Harmer
1.87
276861AD2-134 GEN
Solar/Wind Harmer
1.87
945111AF1-176 GEN
Solar/Wind Harmer
0.794
945111AF1-176 GEN
Solar/Wind Harmer
4.329
274856ECOGROVE ;U1
Solar/Wind Harmer
3.466
971681AH1-341 GEN
Solar/Wind Harmer
0.663
938861AE1-114 GEN
Solar/Wind Harmer
10.341
274858EASY ROAD;U2
Solar/Wind Harmer
4.117
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.434
276843GEN-1.7
Solar/Wind Harmer
0.637
958011AF2-095 GEN
Solar/Wind Harmer
0.692
276691AA1-018 GEN1
Solar/Wind Harmer
0.504
274854TWINGROVE;U2
Solar/Wind Harmer
7.169
965091AG1-374 GEN
Solar/Wind Harmer
1.392
958491AF2-143 GEN
Solar/Wind Harmer
0.696
943021AE2-325 GEN
Solar/Wind Harmer
2.802
276646AC1-214 GEN2
Solar/Wind Harmer
1.384
970819AG2-516 GEN
Solar/Wind Harmer
0.534
274878BISHOP HL;2U
Solar/Wind Harmer
3.456
965931AG1-462 GEN
Solar/Wind Harmer
1.068
339206AE1-143 GEN
Solar/Wind Helper
0.35
241972AD1-140 GEN
Solar/Wind Helper
0.541
24344205RKG1
50/50
11.484
24697605MDL-3G C
Solar/Wind Harmer
5.151
270181AB1-006 GEN2
Solar/Wind Harmer
1.03
24385905FR-11G C
Solar/Wind Harmer
9.864
970193AG2-126 GEN
Solar/Wind Harmer
0.751
274887GEN-1.85
Solar/Wind Harmer
5.918
970833AG2-524 GEN
Solar/Wind Harmer
0.523
274853TWINGROVE;U1
Solar/Wind Harmer
7.169
959611AF2-252 GEN
Solar/Wind Harmer
1.857
960611AF2-352 GEN
Solar/Wind Harmer
1.857
276868AE1-113 GEN
Solar/Wind Harmer
10.815
962781AG1-127 GEN
Solar/Wind Harmer
0.436
971171AH1-044 GEN
Solar/Wind Harmer
0.9
946321AF1-296 GEN
Solar/Wind Harmer
12.566
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.903
339216AC1-074 GEN
Solar/Wind Helper
0.395
253415AE1-040 GEN
Solar/Wind Helper
0.15
24387305FR-4G C
Solar/Wind Harmer
7.526
24386605FR-22G C
Solar/Wind Harmer
5.018
24387005FR-3G C
Solar/Wind Harmer
4.967
274888KELLY CRK;1U
Solar/Wind Harmer
6.555
276893AG1-478 C
Solar/Wind Harmer
0.38
274863CRW1-WTG
Solar/Wind Harmer
5.543
274864CRW2-WTG
Solar/Wind Harmer
5.543
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276602WESTBROOK C
Solar/Wind Harmer
1.907
957891AF2-083 GEN
Solar/Wind Harmer
0.676
276603SUBLETTE C
Solar/Wind Harmer
0.892
270071AF1-092 GEN
Solar/Wind Harmer
0.563
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.583
253398AE2-221_GEN2
Solar/Wind Helper
0.583
339236AF1-050_GEN
Solar/Wind Helper
0.191
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.151
971997AH1-543 GEN
Solar/Wind Harmer
0.729
962691AG1-118 GEN
Solar/Wind Harmer
1.379
276889AE2-281 GEN
Solar/Wind Harmer
1.788
971993AH1-541 GEN
Solar/Wind Harmer
0.422
270505AE1-170 C O1
Solar/Wind Harmer
0.677
276621W2-048 GEN
Solar/Wind Harmer
6.511
942481AE2-261 GEN
Solar/Wind Harmer
1.324
276158O29GEN2
Solar/Wind Harmer
3.853
276708O09 GEN2
Solar/Wind Harmer
3.619
971549AH1-272 GEN
Solar/Wind Harmer
0.737
270367AC2-061_GEN
Solar/Wind Helper
0.469
962581AG1-107 GEN
Solar/Wind Helper
0.576
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.792
276848AB2-070 GEN3
Solar/Wind Harmer
2.337
971341AH1-150 GEN
Solar/Wind Harmer
0.9
274877BISHOP HL;1U
Solar/Wind Harmer
3.456
253316AC1-085 GEN3
Solar/Wind Helper
0.596
253433AC1-085 GEN1
Solar/Wind Helper
0.378
253349AC2-067 GEN
Solar/Wind Helper
0.161
253343AC1-166 GEN
Solar/Wind Helper
0.134
970539AG2-343 GEN
50/50
9.19
274871GR RIDGE ;2U
Solar/Wind Harmer
6.025
943121AE2-341 GEN
Solar/Wind Harmer
0.704
276785W4-005 GEN1
Solar/Wind Harmer
2.725
276849AB2-070 GEN2
Solar/Wind Harmer
2.337
957471AF2-041 GEN
Solar/Wind Harmer
1.349
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.191
970289AG2-191 GEN
Solar/Wind Harmer
0.402
970291AG2-192 GEN
Solar/Wind Harmer
0.219
252524AE2-267 GEN
Solar/Wind Helper
0.255
253317AC1-085 GEN4
Solar/Wind Helper
0.596
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.065
270393AB1-087 CT1
50/50
2.588
270406AB1-088 CT1
50/50
2.588
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.742
971347AH1-153 GEN
Solar/Wind Harmer
0.247
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.48
939401AE1-172 GEN
Solar/Wind Harmer
18.931
276656WTG2_EQ
Solar/Wind Harmer
1.066
926823AC1-168 GEN
Solar/Wind Harmer
5.594
276615X2-022 GEN
Solar/Wind Harmer
2.045
274857EASY ROAD;U1
Solar/Wind Harmer
4.117
252507AC2-088 GEN
Solar/Wind Helper
0.377
970091AG2-072 GEN
50/50
216.879
270394AB1-087 ST1
50/50
2.588
970783AG2-492 GEN
50/50
2.641
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.404
963841AG1-237 GEN
Solar/Wind Harmer
19.192
971917AH1-482 GEN
Solar/Wind Harmer
9.558
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.476
276655WTG1_EQ
Solar/Wind Harmer
8.054
971067AG2-660 GEN
Solar/Wind Harmer
1.799
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.099
270186AC1-089 GEN
Solar/Wind Helper
0.607
339231AF1-038_GEN
Solar/Wind Helper
0.187
270222AC2-111 GEN
Solar/Wind Helper
0.234
339250AF1-203 GEN
Solar/Wind Helper
0.056
942601AE2-276 GEN
50/50
8.233
971605AH1-302 GEN
Solar/Wind Harmer
9.589
970241AG2-163 GEN
Solar/Wind Harmer
1.473
276897AD1-100 C
Solar/Wind Harmer
63.744
970941AG2-585 GEN
Solar/Wind Harmer
0.264
939741AE1-205 GEN
Solar/Wind Harmer
0.935
942111AE2-223 GEN
Solar/Wind Harmer
10.945
971771AH1-392 GEN
Solar/Wind Harmer
0.419
276805AD2-038 GEN
Solar/Wind Harmer
5.43
276174W4-005 GEN2
Solar/Wind Harmer
2.725
276668AB2-070 GEN1
Solar/Wind Harmer
2.337
970569AG2-363 GEN
Solar/Wind Harmer
1.363
276838X2-022 GEN2
Solar/Wind Harmer
0.243
276645AC1-214 GEN1
Solar/Wind Harmer
1.384
276157O29GEN1
Solar/Wind Harmer
3.853
270043AE2-236 GEN
Solar/Wind Harmer
0.177
961491AF2-440 GEN
Solar/Wind Helper
0.192
955142J992
External Queue
0.6478373408317566
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
991112J1481
External Queue
1.0048468112945557
990742J1381
External Queue
1.0048468112945557
950051AG9-018
External Queue
0.31534820795059204
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.815
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.362
MECLTFEXP_MEC->PJM
CLTF
10.182
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.557
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.828
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.205
NYPJM->LTFIMP_NY
CLTF
1.178
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
29.011
AH1-155LTFEXP_AH1-155->PJM
LTF
0.307
WECLTFEXP_WEC->PJM
CLTF
2.921
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.728

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.0 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3290.17
MW Contribution:
0.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970543AG2-345 GEN
50/50
4.61
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.444
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.633
970169AG2-114 GEN
Solar/Wind Harmer
0.473
943591AF1-030 GEN
Solar/Wind Harmer
0.471
276694AA1-018 GEN2
Solar/Wind Harmer
4.996
959341AF2-225 GEN
Solar/Wind Harmer
0.705
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.904
971087AG2-675 GEN
Solar/Wind Harmer
2.693
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.168
253338AC1-165 GEN
Solar/Wind Helper
0.133
270407AB1-088 ST1
50/50
2.594
970023AG2-014 GEN
50/50
2.649
24344105CKG2
50/50
6.908
270101X2-052 CT2
50/50
1.29
270180AB1-006 GEN1
Solar/Wind Harmer
9.298
24791305MDL-5G
Solar/Wind Harmer
3.444
965791AG1-447 GEN
Solar/Wind Harmer
5.575
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.327
276882AE2-255 GEN
Solar/Wind Harmer
3.62
944221AF1-090 GEN
Solar/Wind Harmer
13.766
276741O09 GEN1
Solar/Wind Harmer
3.635
339221AD2-048_GEN
Solar/Wind Helper
0.34
270340AC2-060 GEN
Solar/Wind Helper
0.37
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.545
970091AG2-072 GEN
50/50
217.153
270394AB1-087 ST1
50/50
2.594
970783AG2-492 GEN
50/50
2.649
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.435
963841AG1-237 GEN
Solar/Wind Harmer
19.253
971917AH1-482 GEN
Solar/Wind Harmer
9.588
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.499
276655WTG1_EQ
Solar/Wind Harmer
8.088
971067AG2-660 GEN
Solar/Wind Harmer
1.807
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.098
270186AC1-089 GEN
Solar/Wind Helper
0.604
339231AF1-038_GEN
Solar/Wind Helper
0.186
270222AC2-111 GEN
Solar/Wind Helper
0.233
339250AF1-203 GEN
Solar/Wind Helper
0.056
970781AG2-491 GEN
Solar/Wind Harmer
0.662
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.994
970707AG2-453 GEN
Solar/Wind Harmer
1.346
970833AG2-524 GEN
Solar/Wind Harmer
4.2
958481AF2-142 GEN
Solar/Wind Harmer
0.705
274862TOP CROP ;2U
Solar/Wind Harmer
5.499
274879MINONK ;1U
Solar/Wind Harmer
7.24
971675AH1-338 GEN
Solar/Wind Harmer
0.819
965911AG1-460 GEN
Solar/Wind Harmer
1.067
339211AE2-254 GEN
Solar/Wind Helper
0.209
253406AD2-031_GEN
Solar/Wind Helper
0.184
24344205RKG1
50/50
11.499
24697605MDL-3G C
Solar/Wind Harmer
5.166
270181AB1-006 GEN2
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
9.894
970193AG2-126 GEN
Solar/Wind Harmer
0.754
274887GEN-1.85
Solar/Wind Harmer
5.943
970833AG2-524 GEN
Solar/Wind Harmer
0.525
274853TWINGROVE;U1
Solar/Wind Harmer
7.199
959611AF2-252 GEN
Solar/Wind Harmer
1.864
960611AF2-352 GEN
Solar/Wind Harmer
1.864
276868AE1-113 GEN
Solar/Wind Harmer
10.861
962781AG1-127 GEN
Solar/Wind Harmer
0.438
971171AH1-044 GEN
Solar/Wind Harmer
0.904
946321AF1-296 GEN
Solar/Wind Harmer
12.624
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.908
339216AC1-074 GEN
Solar/Wind Helper
0.394
253415AE1-040 GEN
Solar/Wind Helper
0.149
24344305RKG2
50/50
11.124
24344305RKG2
50/50
11.029
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.468
972181SS23-001
Solar/Wind Harmer
0.488
274847GR RIDGE ;BU
Solar/Wind Harmer
5.484
959091AF2-200 GEN
Solar/Wind Harmer
0.904
274849CRESCENT ;1U
Solar/Wind Harmer
1.906
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.932
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.182
339241AF1-083 GEN
Solar/Wind Helper
0.19
253333AC1-068 GEN
Solar/Wind Helper
0.133
962211AG1-066 GEN
Solar/Wind Helper
0.207
270100X2-052 CT1
50/50
1.29
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.864
970571AG2-364 GEN
Solar/Wind Harmer
0.913
274850MENDOTA H;RU
Solar/Wind Harmer
2.7
276863AD2-134 GEN
Solar/Wind Harmer
1.878
276861AD2-134 GEN
Solar/Wind Harmer
1.878
945111AF1-176 GEN
Solar/Wind Harmer
0.798
945111AF1-176 GEN
Solar/Wind Harmer
4.348
274856ECOGROVE ;U1
Solar/Wind Harmer
3.482
971681AH1-341 GEN
Solar/Wind Harmer
0.666
938861AE1-114 GEN
Solar/Wind Harmer
10.387
274858EASY ROAD;U2
Solar/Wind Harmer
4.136
942601AE2-276 GEN
50/50
8.252
971605AH1-302 GEN
Solar/Wind Harmer
9.618
970241AG2-163 GEN
Solar/Wind Harmer
1.478
276897AD1-100 C
Solar/Wind Harmer
64.004
970941AG2-585 GEN
Solar/Wind Harmer
0.265
939741AE1-205 GEN
Solar/Wind Harmer
0.939
942111AE2-223 GEN
Solar/Wind Harmer
10.99
971771AH1-392 GEN
Solar/Wind Harmer
0.421
276805AD2-038 GEN
Solar/Wind Harmer
5.453
276174W4-005 GEN2
Solar/Wind Harmer
2.737
276668AB2-070 GEN1
Solar/Wind Harmer
2.347
970569AG2-363 GEN
Solar/Wind Harmer
1.369
276838X2-022 GEN2
Solar/Wind Harmer
0.244
276645AC1-214 GEN1
Solar/Wind Harmer
1.39
276157O29GEN1
Solar/Wind Harmer
3.871
270043AE2-236 GEN
Solar/Wind Harmer
0.178
961491AF2-440 GEN
Solar/Wind Helper
0.191
24344205RKG1
50/50
11.499
270102X2-052 ST
50/50
1.396
970901AG2-562 GEN
50/50
5.29
24386405FR-21G C
Solar/Wind Harmer
5.033
972231SS25-0005
Solar/Wind Harmer
0.781
276876AE1-163_GEN2
Solar/Wind Harmer
6.283
276763AC1-053 GEN1
Solar/Wind Harmer
3.562
274855GSG-6 ;RU
Solar/Wind Harmer
3.884
971411AH1-196 GEN
Solar/Wind Harmer
0.682
961051AF2-396 GEN
Solar/Wind Harmer
0.897
961051AF2-396 GEN
Solar/Wind Harmer
7.174
276782AC1-033 GEN
Solar/Wind Harmer
3.499
944031AF1-071 GEN
Solar/Wind Helper
0.052
24386205FR-12G C
Solar/Wind Harmer
5.254
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.66
970373AG2-245 GEN
Solar/Wind Harmer
1.201
276872AE1-163_GEN1
Solar/Wind Harmer
6.283
274872LEEDK;1U
Solar/Wind Harmer
8.599
276686W4-005 GEN3
Solar/Wind Harmer
2.737
276764AC1-053 GEN2
Solar/Wind Harmer
3.562
959081AF2-199 GEN
Solar/Wind Harmer
0.452
274851PROVIDENC;RU
Solar/Wind Harmer
2.59
276911AD2-131_GEN
Solar/Wind Harmer
0.222
25183208HLCRTG
Solar/Wind Helper
0.946
253325AC1-069 GEN
Solar/Wind Helper
0.133
970539AG2-343 GEN
50/50
9.221
274871GR RIDGE ;2U
Solar/Wind Harmer
6.05
943121AE2-341 GEN
Solar/Wind Harmer
0.707
276785W4-005 GEN1
Solar/Wind Harmer
2.737
276849AB2-070 GEN2
Solar/Wind Harmer
2.347
957471AF2-041 GEN
Solar/Wind Harmer
1.355
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.214
970289AG2-191 GEN
Solar/Wind Harmer
0.404
970291AG2-192 GEN
Solar/Wind Harmer
0.22
252524AE2-267 GEN
Solar/Wind Helper
0.254
253317AC1-085 GEN4
Solar/Wind Helper
0.593
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.064
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.444
276843GEN-1.7
Solar/Wind Harmer
0.639
958011AF2-095 GEN
Solar/Wind Harmer
0.694
276691AA1-018 GEN1
Solar/Wind Harmer
0.506
274854TWINGROVE;U2
Solar/Wind Harmer
7.199
965091AG1-374 GEN
Solar/Wind Harmer
1.398
958491AF2-143 GEN
Solar/Wind Harmer
0.699
943021AE2-325 GEN
Solar/Wind Harmer
2.814
276646AC1-214 GEN2
Solar/Wind Harmer
1.39
970819AG2-516 GEN
Solar/Wind Harmer
0.536
274878BISHOP HL;2U
Solar/Wind Harmer
3.471
965931AG1-462 GEN
Solar/Wind Harmer
1.073
339206AE1-143 GEN
Solar/Wind Helper
0.348
241972AD1-140 GEN
Solar/Wind Helper
0.537
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.852
276848AB2-070 GEN3
Solar/Wind Harmer
2.347
971341AH1-150 GEN
Solar/Wind Harmer
0.904
274877BISHOP HL;1U
Solar/Wind Harmer
3.471
253316AC1-085 GEN3
Solar/Wind Helper
0.593
253433AC1-085 GEN1
Solar/Wind Helper
0.376
253349AC2-067 GEN
Solar/Wind Helper
0.16
253343AC1-166 GEN
Solar/Wind Helper
0.133
270393AB1-087 CT1
50/50
2.594
270406AB1-088 CT1
50/50
2.594
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.745
971347AH1-153 GEN
Solar/Wind Harmer
0.248
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.482
939401AE1-172 GEN
Solar/Wind Harmer
19.009
276656WTG2_EQ
Solar/Wind Harmer
1.071
926823AC1-168 GEN
Solar/Wind Harmer
5.618
276615X2-022 GEN
Solar/Wind Harmer
2.054
274857EASY ROAD;U1
Solar/Wind Harmer
4.136
252507AC2-088 GEN
Solar/Wind Helper
0.376
24387305FR-4G C
Solar/Wind Harmer
7.549
24386605FR-22G C
Solar/Wind Harmer
5.033
24387005FR-3G C
Solar/Wind Harmer
4.983
274888KELLY CRK;1U
Solar/Wind Harmer
6.582
276893AG1-478 C
Solar/Wind Harmer
0.382
274863CRW1-WTG
Solar/Wind Harmer
5.566
274864CRW2-WTG
Solar/Wind Harmer
5.566
274880W4-005 GEN4
Solar/Wind Harmer
2.737
276602WESTBROOK C
Solar/Wind Harmer
1.915
957891AF2-083 GEN
Solar/Wind Harmer
0.679
276603SUBLETTE C
Solar/Wind Harmer
0.896
270071AF1-092 GEN
Solar/Wind Harmer
0.566
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.581
253398AE2-221_GEN2
Solar/Wind Helper
0.581
339236AF1-050_GEN
Solar/Wind Helper
0.19
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.166
971997AH1-543 GEN
Solar/Wind Harmer
0.732
962691AG1-118 GEN
Solar/Wind Harmer
1.385
276889AE2-281 GEN
Solar/Wind Harmer
1.795
971993AH1-541 GEN
Solar/Wind Harmer
0.424
270505AE1-170 C O1
Solar/Wind Harmer
0.68
276621W2-048 GEN
Solar/Wind Harmer
6.539
942481AE2-261 GEN
Solar/Wind Harmer
1.329
276158O29GEN2
Solar/Wind Harmer
3.871
276708O09 GEN2
Solar/Wind Harmer
3.635
971549AH1-272 GEN
Solar/Wind Harmer
0.741
270367AC2-061_GEN
Solar/Wind Helper
0.466
962581AG1-107 GEN
Solar/Wind Helper
0.573
955142J992
External Queue
0.6478373408317566
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
991112J1481
External Queue
1.0048468112945557
990742J1381
External Queue
1.0048468112945557
950051AG9-018
External Queue
0.31534820795059204
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
NYPJM->LTFIMP_NY
CLTF
1.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.087
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.943
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
WECLTFEXP_WEC->PJM
CLTF
2.934
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.797
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.308
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.34
MECLTFEXP_MEC->PJM
CLTF
10.238
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.814
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.0 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3290.12
MW Contribution:
0.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970543AG2-345 GEN
50/50
4.61
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.444
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.633
970169AG2-114 GEN
Solar/Wind Harmer
0.473
943591AF1-030 GEN
Solar/Wind Harmer
0.471
276694AA1-018 GEN2
Solar/Wind Harmer
4.996
959341AF2-225 GEN
Solar/Wind Harmer
0.705
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.904
971087AG2-675 GEN
Solar/Wind Harmer
2.693
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.168
253338AC1-165 GEN
Solar/Wind Helper
0.133
24344305RKG2
50/50
11.124
24344305RKG2
50/50
11.029
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.468
972181SS23-001
Solar/Wind Harmer
0.488
274847GR RIDGE ;BU
Solar/Wind Harmer
5.484
959091AF2-200 GEN
Solar/Wind Harmer
0.904
274849CRESCENT ;1U
Solar/Wind Harmer
1.906
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.932
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.182
339241AF1-083 GEN
Solar/Wind Helper
0.19
253333AC1-068 GEN
Solar/Wind Helper
0.133
962211AG1-066 GEN
Solar/Wind Helper
0.207
24386205FR-12G C
Solar/Wind Harmer
5.254
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.66
970373AG2-245 GEN
Solar/Wind Harmer
1.201
276872AE1-163_GEN1
Solar/Wind Harmer
6.283
274872LEEDK;1U
Solar/Wind Harmer
8.599
276686W4-005 GEN3
Solar/Wind Harmer
2.737
276764AC1-053 GEN2
Solar/Wind Harmer
3.562
959081AF2-199 GEN
Solar/Wind Harmer
0.452
274851PROVIDENC;RU
Solar/Wind Harmer
2.59
276911AD2-131_GEN
Solar/Wind Harmer
0.222
25183208HLCRTG
Solar/Wind Helper
0.946
253325AC1-069 GEN
Solar/Wind Helper
0.133
270407AB1-088 ST1
50/50
2.594
970023AG2-014 GEN
50/50
2.649
24344105CKG2
50/50
6.908
270101X2-052 CT2
50/50
1.29
270180AB1-006 GEN1
Solar/Wind Harmer
9.298
24791305MDL-5G
Solar/Wind Harmer
3.444
965791AG1-447 GEN
Solar/Wind Harmer
5.575
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.327
276882AE2-255 GEN
Solar/Wind Harmer
3.62
944221AF1-090 GEN
Solar/Wind Harmer
13.766
276741O09 GEN1
Solar/Wind Harmer
3.635
339221AD2-048_GEN
Solar/Wind Helper
0.34
270340AC2-060 GEN
Solar/Wind Helper
0.37
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.545
970781AG2-491 GEN
Solar/Wind Harmer
0.662
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.994
970707AG2-453 GEN
Solar/Wind Harmer
1.346
970833AG2-524 GEN
Solar/Wind Harmer
4.2
958481AF2-142 GEN
Solar/Wind Harmer
0.705
274862TOP CROP ;2U
Solar/Wind Harmer
5.499
274879MINONK ;1U
Solar/Wind Harmer
7.24
971675AH1-338 GEN
Solar/Wind Harmer
0.819
965911AG1-460 GEN
Solar/Wind Harmer
1.067
339211AE2-254 GEN
Solar/Wind Helper
0.209
253406AD2-031_GEN
Solar/Wind Helper
0.184
24344205RKG1
50/50
11.499
270102X2-052 ST
50/50
1.396
970901AG2-562 GEN
50/50
5.29
24386405FR-21G C
Solar/Wind Harmer
5.033
972231SS25-0005
Solar/Wind Harmer
0.781
276876AE1-163_GEN2
Solar/Wind Harmer
6.283
276763AC1-053 GEN1
Solar/Wind Harmer
3.562
274855GSG-6 ;RU
Solar/Wind Harmer
3.884
971411AH1-196 GEN
Solar/Wind Harmer
0.682
961051AF2-396 GEN
Solar/Wind Harmer
0.897
961051AF2-396 GEN
Solar/Wind Harmer
7.174
276782AC1-033 GEN
Solar/Wind Harmer
3.499
944031AF1-071 GEN
Solar/Wind Helper
0.052
270100X2-052 CT1
50/50
1.29
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.864
970571AG2-364 GEN
Solar/Wind Harmer
0.913
274850MENDOTA H;RU
Solar/Wind Harmer
2.7
276863AD2-134 GEN
Solar/Wind Harmer
1.878
276861AD2-134 GEN
Solar/Wind Harmer
1.878
945111AF1-176 GEN
Solar/Wind Harmer
0.798
945111AF1-176 GEN
Solar/Wind Harmer
4.348
274856ECOGROVE ;U1
Solar/Wind Harmer
3.482
971681AH1-341 GEN
Solar/Wind Harmer
0.666
938861AE1-114 GEN
Solar/Wind Harmer
10.387
274858EASY ROAD;U2
Solar/Wind Harmer
4.136
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.444
276843GEN-1.7
Solar/Wind Harmer
0.639
958011AF2-095 GEN
Solar/Wind Harmer
0.694
276691AA1-018 GEN1
Solar/Wind Harmer
0.506
24344205RKG1
50/50
11.499
24697605MDL-3G C
Solar/Wind Harmer
5.166
270181AB1-006 GEN2
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
9.894
970193AG2-126 GEN
Solar/Wind Harmer
0.754
274887GEN-1.85
Solar/Wind Harmer
5.943
970833AG2-524 GEN
Solar/Wind Harmer
0.525
274853TWINGROVE;U1
Solar/Wind Harmer
7.199
959611AF2-252 GEN
Solar/Wind Harmer
1.864
960611AF2-352 GEN
Solar/Wind Harmer
1.864
276868AE1-113 GEN
Solar/Wind Harmer
10.861
962781AG1-127 GEN
Solar/Wind Harmer
0.438
971171AH1-044 GEN
Solar/Wind Harmer
0.904
946321AF1-296 GEN
Solar/Wind Harmer
12.624
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.908
339216AC1-074 GEN
Solar/Wind Helper
0.394
253415AE1-040 GEN
Solar/Wind Helper
0.149
24387305FR-4G C
Solar/Wind Harmer
7.549
24386605FR-22G C
Solar/Wind Harmer
5.033
24387005FR-3G C
Solar/Wind Harmer
4.983
274888KELLY CRK;1U
Solar/Wind Harmer
6.582
276893AG1-478 C
Solar/Wind Harmer
0.382
274863CRW1-WTG
Solar/Wind Harmer
5.566
274864CRW2-WTG
Solar/Wind Harmer
5.566
274880W4-005 GEN4
Solar/Wind Harmer
2.737
276602WESTBROOK C
Solar/Wind Harmer
1.915
957891AF2-083 GEN
Solar/Wind Harmer
0.679
276603SUBLETTE C
Solar/Wind Harmer
0.896
270071AF1-092 GEN
Solar/Wind Harmer
0.566
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.581
253398AE2-221_GEN2
Solar/Wind Helper
0.581
339236AF1-050_GEN
Solar/Wind Helper
0.19
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.166
971997AH1-543 GEN
Solar/Wind Harmer
0.732
962691AG1-118 GEN
Solar/Wind Harmer
1.385
276889AE2-281 GEN
Solar/Wind Harmer
1.795
971993AH1-541 GEN
Solar/Wind Harmer
0.424
270505AE1-170 C O1
Solar/Wind Harmer
0.68
276621W2-048 GEN
Solar/Wind Harmer
6.539
942481AE2-261 GEN
Solar/Wind Harmer
1.329
276158O29GEN2
Solar/Wind Harmer
3.871
276708O09 GEN2
Solar/Wind Harmer
3.635
971549AH1-272 GEN
Solar/Wind Harmer
0.741
270367AC2-061_GEN
Solar/Wind Helper
0.466
962581AG1-107 GEN
Solar/Wind Helper
0.573
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.852
276848AB2-070 GEN3
Solar/Wind Harmer
2.347
971341AH1-150 GEN
Solar/Wind Harmer
0.904
274877BISHOP HL;1U
Solar/Wind Harmer
3.471
253316AC1-085 GEN3
Solar/Wind Helper
0.593
253433AC1-085 GEN1
Solar/Wind Helper
0.376
253349AC2-067 GEN
Solar/Wind Helper
0.16
253343AC1-166 GEN
Solar/Wind Helper
0.133
970539AG2-343 GEN
50/50
9.221
274871GR RIDGE ;2U
Solar/Wind Harmer
6.05
943121AE2-341 GEN
Solar/Wind Harmer
0.707
276785W4-005 GEN1
Solar/Wind Harmer
2.737
276849AB2-070 GEN2
Solar/Wind Harmer
2.347
957471AF2-041 GEN
Solar/Wind Harmer
1.355
270449AD2-020 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
7.199
965091AG1-374 GEN
Solar/Wind Harmer
1.398
958491AF2-143 GEN
Solar/Wind Harmer
0.699
943021AE2-325 GEN
Solar/Wind Harmer
2.814
276646AC1-214 GEN2
Solar/Wind Harmer
1.39
970819AG2-516 GEN
Solar/Wind Harmer
0.536
274878BISHOP HL;2U
Solar/Wind Harmer
3.471
965931AG1-462 GEN
Solar/Wind Harmer
1.073
339206AE1-143 GEN
Solar/Wind Helper
0.348
241972AD1-140 GEN
Solar/Wind Helper
0.537
274848CAMPGROVE;RU
Solar/Wind Harmer
5.214
970289AG2-191 GEN
Solar/Wind Harmer
0.404
970291AG2-192 GEN
Solar/Wind Harmer
0.22
252524AE2-267 GEN
Solar/Wind Helper
0.254
253317AC1-085 GEN4
Solar/Wind Helper
0.593
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.064
270393AB1-087 CT1
50/50
2.594
270406AB1-088 CT1
50/50
2.594
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.745
971347AH1-153 GEN
Solar/Wind Harmer
0.248
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.482
939401AE1-172 GEN
Solar/Wind Harmer
19.009
276656WTG2_EQ
Solar/Wind Harmer
1.071
926823AC1-168 GEN
Solar/Wind Harmer
5.618
276615X2-022 GEN
Solar/Wind Harmer
2.054
274857EASY ROAD;U1
Solar/Wind Harmer
4.136
252507AC2-088 GEN
Solar/Wind Helper
0.376
970091AG2-072 GEN
50/50
217.153
270394AB1-087 ST1
50/50
2.594
970783AG2-492 GEN
50/50
2.649
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.435
963841AG1-237 GEN
Solar/Wind Harmer
19.253
971917AH1-482 GEN
Solar/Wind Harmer
9.588
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.499
276655WTG1_EQ
Solar/Wind Harmer
8.088
971067AG2-660 GEN
Solar/Wind Harmer
1.807
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.098
270186AC1-089 GEN
Solar/Wind Helper
0.604
339231AF1-038_GEN
Solar/Wind Helper
0.186
270222AC2-111 GEN
Solar/Wind Helper
0.233
339250AF1-203 GEN
Solar/Wind Helper
0.056
942601AE2-276 GEN
50/50
8.252
971605AH1-302 GEN
Solar/Wind Harmer
9.618
970241AG2-163 GEN
Solar/Wind Harmer
1.478
276897AD1-100 C
Solar/Wind Harmer
64.004
970941AG2-585 GEN
Solar/Wind Harmer
0.265
939741AE1-205 GEN
Solar/Wind Harmer
0.939
942111AE2-223 GEN
Solar/Wind Harmer
10.99
971771AH1-392 GEN
Solar/Wind Harmer
0.421
276805AD2-038 GEN
Solar/Wind Harmer
5.453
276174W4-005 GEN2
Solar/Wind Harmer
2.737
276668AB2-070 GEN1
Solar/Wind Harmer
2.347
970569AG2-363 GEN
Solar/Wind Harmer
1.369
276838X2-022 GEN2
Solar/Wind Harmer
0.244
276645AC1-214 GEN1
Solar/Wind Harmer
1.39
276157O29GEN1
Solar/Wind Harmer
3.871
270043AE2-236 GEN
Solar/Wind Harmer
0.178
961491AF2-440 GEN
Solar/Wind Helper
0.191
955142J992
External Queue
0.6478373408317566
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
991112J1481
External Queue
1.0048468112945557
990742J1381
External Queue
1.0048468112945557
950051AG9-018
External Queue
0.31534820795059204
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.814
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
NYPJM->LTFIMP_NY
CLTF
1.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.087
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.943
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
WECLTFEXP_WEC->PJM
CLTF
2.934
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.797
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.308
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.34
MECLTFEXP_MEC->PJM
CLTF
10.238
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.19 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5615.13
MW Contribution:
2.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
19.094
270101X2-052 CT2
50/50
3.322
965791AG1-447 GEN
Solar/Wind Harmer
14.312
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
16.653
24791305MDL-5G
Solar/Wind Harmer
6.168
276882AE2-255 GEN
Solar/Wind Harmer
9.245
276741O09 GEN1
Solar/Wind Harmer
9.356
270142AC1-141 CT1_
50/50
5.318
270143AC1-141 CT2_
50/50
5.318
24639705ELKHART HY
50/50
0.355
965681AG1-436 GEN
Solar/Wind Harmer
1.626
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.221
276694AA1-018 GEN2
Solar/Wind Harmer
12.798
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
6.168
971343AH1-151 GEN
Solar/Wind Harmer
2.34
970169AG2-114 GEN
Solar/Wind Harmer
1.163
959341AF2-225 GEN
Solar/Wind Harmer
1.689
971087AG2-675 GEN
Solar/Wind Harmer
6.993
970291AG2-192 GEN
Solar/Wind Harmer
0.131
963791AG1-232 GEN
Solar/Wind Harmer
1.357
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
6.782
24695305TIMB G C
Solar/Wind Harmer
6.541
972207SS24-0001
Solar/Wind Harmer
3.817
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
1.254
274847GR RIDGE ;BU
Solar/Wind Harmer
14.105
959091AF2-200 GEN
Solar/Wind Harmer
2.34
274849CRESCENT ;1U
Solar/Wind Harmer
4.808
965651AG1-433 GEN
Solar/Wind Harmer
16.648
970289AG2-191 GEN
Solar/Wind Harmer
0.192
957381AF2-032 GEN
Solar/Wind Harmer
0.2
276916AD2-100_GEN
Solar/Wind Harmer
2.081
946031AF1-268 GEN
Solar/Wind Harmer
0.712
965421AG1-410 GEN
Solar/Wind Harmer
2.186
270349AD2-093_GEN
Solar/Wind Helper
0.732
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
15.559
943121AE2-341 GEN
Solar/Wind Harmer
1.831
957471AF2-041 GEN
Solar/Wind Harmer
3.51
274848CAMPGROVE;RU
Solar/Wind Harmer
13.133
276785W4-005 GEN1
Solar/Wind Harmer
6.269
276849AB2-070 GEN2
Solar/Wind Harmer
5.38
274776LINCOLN ;7U
50/50
19.594
970373AG2-245 GEN
Solar/Wind Harmer
2.66
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
22.268
276872AE1-163_GEN1
Solar/Wind Harmer
15.988
959081AF2-199 GEN
Solar/Wind Harmer
1.17
24386205FR-12G C
Solar/Wind Harmer
9.336
274851PROVIDENC;RU
Solar/Wind Harmer
6.535
963741AG1-226 GEN
Solar/Wind Harmer
4.866
276686W4-005 GEN3
Solar/Wind Harmer
6.269
276764AC1-053 GEN2
Solar/Wind Harmer
8.149
276911AD2-131_GEN
Solar/Wind Harmer
0.495
270004AE1-209 GEN
Solar/Wind Harmer
13.761
270201AC2-176 GEN
Solar/Wind Harmer
8.644
24379505HDWTR1G C
Solar/Wind Harmer
12.238
970885AG2-551 GEN
Solar/Wind Harmer
2.885
276726Z2-087_GEN
Solar/Wind Harmer
17.562
944541AF1-119 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
30.092
270191TR4_S_V150
Solar/Wind Harmer
5.168
24641605TWIN BRNCH
50/50
0.038
970707AG2-453 GEN
Solar/Wind Harmer
3.491
970833AG2-524 GEN
Solar/Wind Harmer
10.802
958481AF2-142 GEN
Solar/Wind Harmer
1.807
274862TOP CROP ;2U
Solar/Wind Harmer
14.086
970781AG2-491 GEN
Solar/Wind Harmer
1.186
274879MINONK ;1U
Solar/Wind Harmer
18.49
971675AH1-338 GEN
Solar/Wind Harmer
2.12
944531AF1-118 GEN
Solar/Wind Harmer
4.1
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.397
945391AF1-204 GEN
Solar/Wind Harmer
38.775
276903AD2-071 C
Solar/Wind Harmer
0.942
270247TR4_N_V136
Solar/Wind Harmer
1.716
270102X2-052 ST
50/50
3.595
970901AG2-562 GEN
50/50
13.622
24344005CKG1
50/50
15.603
274777LINCOLN ;8U
50/50
19.594
961051AF2-396 GEN
Solar/Wind Harmer
2.529
961051AF2-396 GEN
Solar/Wind Harmer
20.232
972231SS25-0005
Solar/Wind Harmer
2.007
971411AH1-196 GEN
Solar/Wind Harmer
1.767
274855GSG-6 ;RU
Solar/Wind Harmer
10.056
276876AE1-163_GEN2
Solar/Wind Harmer
15.988
24386405FR-21G C
Solar/Wind Harmer
8.942
276782AC1-033 GEN
Solar/Wind Harmer
8.851
276763AC1-053 GEN1
Solar/Wind Harmer
8.149
270599AE1-208 GEN
Solar/Wind Harmer
0.772
971029AG2-637 GEN
Solar/Wind Harmer
0.988
270054AF2-122 C O1
Solar/Wind Helper
0.559
270100X2-052 CT1
50/50
3.322
274770LINCOLN ;1U
50/50
19.594
274771LINCOLN ;2U
50/50
19.594
945111AF1-176 GEN
Solar/Wind Harmer
2.262
945111AF1-176 GEN
Solar/Wind Harmer
12.331
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.763
274850MENDOTA H;RU
Solar/Wind Harmer
6.991
276863AD2-134 GEN
Solar/Wind Harmer
4.863
276861AD2-134 GEN
Solar/Wind Harmer
4.863
970571AG2-364 GEN
Solar/Wind Harmer
2.316
274856ECOGROVE ;U1
Solar/Wind Harmer
9.025
971681AH1-341 GEN
Solar/Wind Harmer
1.725
938861AE1-114 GEN
Solar/Wind Harmer
26.903
274858EASY ROAD;U2
Solar/Wind Harmer
10.718
965011AG1-365 GEN
Solar/Wind Harmer
1.101
270594AE1-207 GEN
Solar/Wind Harmer
1.561
270240V3-007_GEN2
Solar/Wind Harmer
9.582
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.09
943021AE2-325 GEN
Solar/Wind Harmer
7.909
276843GEN-1.7
Solar/Wind Harmer
1.646
958011AF2-095 GEN
Solar/Wind Harmer
1.788
945421AF1-207 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.297
958491AF2-143 GEN
Solar/Wind Harmer
1.786
24697905MDL-4G C
Solar/Wind Harmer
6.168
970819AG2-516 GEN
Solar/Wind Harmer
1.391
276646AC1-214 GEN2
Solar/Wind Harmer
3.506
274878BISHOP HL;2U
Solar/Wind Harmer
8.781
274854TWINGROVE;U2
Solar/Wind Harmer
17.103
965091AG1-374 GEN
Solar/Wind Harmer
3.322
965931AG1-462 GEN
Solar/Wind Harmer
2.786
964611AG1-324 GEN
Solar/Wind Harmer
0.768
270491AE1-102 GEN2
Solar/Wind Harmer
0.09
270356AE2-297 GEN
Solar/Wind Harmer
0
24643105BUCHANAN
50/50
0.028
274887GEN-1.85
Solar/Wind Harmer
15.299
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.35
970031AG2-029 GEN
Solar/Wind Harmer
3.022
962781AG1-127 GEN
Solar/Wind Harmer
1.134
24697605MDL-3G C
Solar/Wind Harmer
9.252
270181AB1-006 GEN2
Solar/Wind Harmer
1.85
276868AE1-113 GEN
Solar/Wind Harmer
27.735
971171AH1-044 GEN
Solar/Wind Harmer
2.34
24385905FR-11G C
Solar/Wind Harmer
17.58
274853TWINGROVE;U1
Solar/Wind Harmer
17.103
959611AF2-252 GEN
Solar/Wind Harmer
4.43
960611AF2-352 GEN
Solar/Wind Harmer
4.43
946321AF1-296 GEN
Solar/Wind Harmer
32.747
960971AF2-388 GEN
Solar/Wind Harmer
33.297
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.462
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.721
24653605MOTTVILLE
50/50
0.008
957891AF2-083 GEN
Solar/Wind Harmer
1.911
270071AF1-092 GEN
Solar/Wind Harmer
1.896
274888KELLY CRK;1U
Solar/Wind Harmer
16.946
276893AG1-478 C
Solar/Wind Harmer
0.983
274863CRW1-WTG
Solar/Wind Harmer
13.812
274864CRW2-WTG
Solar/Wind Harmer
13.812
276602WESTBROOK C
Solar/Wind Harmer
4.959
24387305FR-4G C
Solar/Wind Harmer
13.414
24386605FR-22G C
Solar/Wind Harmer
8.942
24387005FR-3G C
Solar/Wind Harmer
8.853
276603SUBLETTE C
Solar/Wind Harmer
2.319
274880W4-005 GEN4
Solar/Wind Harmer
6.269
270005AE1-210 C O1
Solar/Wind Harmer
13.761
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.279
246936BC-WTG1
Solar/Wind Harmer
6.236
246937BC-WTG2
Solar/Wind Harmer
6.236
270459AD2-067 GEN
Solar/Wind Helper
0.77
274773LINCOLN ;4U
50/50
19.594
24307105BERRINSP G
50/50
0.047
270505AE1-170 C O1
Solar/Wind Harmer
1.915
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.586
24691005MDL-2G C
Solar/Wind Harmer
9.252
971997AH1-543 GEN
Solar/Wind Harmer
1.864
276889AE2-281 GEN
Solar/Wind Harmer
4.568
971549AH1-272 GEN
Solar/Wind Harmer
2.119
276158O29GEN2
Solar/Wind Harmer
9.962
276708O09 GEN2
Solar/Wind Harmer
9.356
965021AG1-366 GEN
Solar/Wind Harmer
4.406
971993AH1-541 GEN
Solar/Wind Harmer
0.971
958861AF2-177 GEN
Solar/Wind Harmer
32.514
276621W2-048 GEN
Solar/Wind Harmer
14.904
942221AE2-234 GEN
Solar/Wind Harmer
0.357
942481AE2-261 GEN
Solar/Wind Harmer
2.986
945371AF1-202 GEN
Solar/Wind Harmer
15.509
270032AE2-172
Solar/Wind Harmer
7.806
970825AG2-519 GEN
Solar/Wind Harmer
3.715
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.656
270543AE2-219 C
Solar/Wind Harmer
0.721
247607V1-011 GEN
Solar/Wind Harmer
5.418
270435AC2-044 GEN
Solar/Wind Harmer
0.138
970521AG2-332 GEN
50/50
25.194
276806AD2-047 C O1
Solar/Wind Harmer
38.236
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.34
274877BISHOP HL;1U
Solar/Wind Harmer
8.781
276848AB2-070 GEN3
Solar/Wind Harmer
5.38
270444AC2-157 GEN1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.732
970289AG2-191 GEN
Solar/Wind Harmer
1.334
970291AG2-192 GEN
Solar/Wind Harmer
0.728
270246TR4_N_V150
Solar/Wind Harmer
1.716
957201AF2-014 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
50/50
19.594
970349AG2-230 GEN
Solar/Wind Harmer
2.066
971347AH1-153 GEN
Solar/Wind Harmer
0.689
960591AF2-350 GEN
Solar/Wind Harmer
1.241
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
47.612
926823AC1-168 GEN
Solar/Wind Harmer
14.207
274857EASY ROAD;U1
Solar/Wind Harmer
10.718
276656WTG2_EQ
Solar/Wind Harmer
2.567
276615X2-022 GEN
Solar/Wind Harmer
4.681
24725505WLD G2 C
Solar/Wind Harmer
7.118
965051AG1-369 GEN
Solar/Wind Harmer
0.436
961761AG1-017 GEN
Solar/Wind Harmer
0.84
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.286
958091AF2-103 GEN
Solar/Wind Harmer
0
270144AC1-141 ST1_
50/50
4.707
24642205MAYFLWER
50/50
1.638
962601AG1-109 GEN
50/50
6.313
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.337
274861TOP CROP ;1U
Solar/Wind Harmer
14.086
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
18.688
971067AG2-660 GEN
Solar/Wind Harmer
4.679
276655WTG1_EQ
Solar/Wind Harmer
19.386
963841AG1-237 GEN
Solar/Wind Harmer
34.712
959331AF2-224 GEN
Solar/Wind Harmer
1.101
965041AG1-368 GEN
Solar/Wind Harmer
0.951
270031AE2-169
Solar/Wind Harmer
0.772
24699105WLD G1 C
Solar/Wind Harmer
7.118
270383AD1-128 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
50/50
19.594
274774LINCOLN ;5U
50/50
19.594
944961AF1-161 GEN
50/50
6.313
971771AH1-392 GEN
Solar/Wind Harmer
1.164
270043AE2-236 GEN
Solar/Wind Harmer
0.701
970941AG2-585 GEN
Solar/Wind Harmer
0.683
276897AD1-100 C
Solar/Wind Harmer
163.988
971605AH1-302 GEN
Solar/Wind Harmer
18.338
276805AD2-038 GEN
Solar/Wind Harmer
13.931
970569AG2-363 GEN
Solar/Wind Harmer
3.474
276645AC1-214 GEN1
Solar/Wind Harmer
3.506
276157O29GEN1
Solar/Wind Harmer
9.962
939741AE1-205 GEN
Solar/Wind Harmer
2.252
942111AE2-223 GEN
Solar/Wind Harmer
26.343
970241AG2-163 GEN
Solar/Wind Harmer
2.703
276174W4-005 GEN2
Solar/Wind Harmer
6.269
276668AB2-070 GEN1
Solar/Wind Harmer
5.38
276838X2-022 GEN2
Solar/Wind Harmer
0.556
970825AG2-519 GEN
Solar/Wind Harmer
0.58
270007AE1-245 C
Solar/Wind Harmer
7.597
246938BC-WTG3
Solar/Wind Harmer
6.344
NYPJM->LTFIMP_NY
CLTF
3.691
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.533
CBM West 1LTFEXP_CBM-W1->PJM
CBM
234.012
LGEELTFEXP_LGEE->PJM
CLTF
3.98
TVALTFEXP_TVA->PJM
CLTF
5.131
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
50.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
137.069
WECLTFEXP_WEC->PJM
CLTF
7.629
MECLTFEXP_MEC->PJM
CLTF
27.64
AG2-052LTFEXP_AG2-052->PJM
LTF
0.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.712
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.521
LAGNLTFEXP_LAGN->PJM
CLTF
14.07
AH1-155LTFEXP_AH1-155->PJM
LTF
0.713

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.69 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5144.06
MW Contribution:
1.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.953
270143AC1-141 CT2_
50/50
4.953
24639705ELKHART HY
50/50
0.331
965681AG1-436 GEN
Solar/Wind Harmer
1.504
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.13
276694AA1-018 GEN2
Solar/Wind Harmer
11.833
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.165
970169AG2-114 GEN
Solar/Wind Harmer
1.072
972207SS24-0001
Solar/Wind Harmer
3.534
972181SS23-001
Solar/Wind Harmer
1.16
270055AF2-134 C O1
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
13.046
959091AF2-200 GEN
Solar/Wind Harmer
2.165
274849CRESCENT ;1U
Solar/Wind Harmer
4.44
965651AG1-433 GEN
Solar/Wind Harmer
16.307
970289AG2-191 GEN
Solar/Wind Harmer
0.181
957381AF2-032 GEN
Solar/Wind Harmer
0.183
276916AD2-100_GEN
Solar/Wind Harmer
1.901
946031AF1-268 GEN
Solar/Wind Harmer
0.706
965421AG1-410 GEN
Solar/Wind Harmer
2.09
270349AD2-093_GEN
Solar/Wind Helper
0.722
24755605MDL-5G
Solar/Wind Harmer
5.509
959341AF2-225 GEN
Solar/Wind Harmer
1.553
971087AG2-675 GEN
Solar/Wind Harmer
6.471
963791AG1-232 GEN
Solar/Wind Harmer
1.31
970291AG2-192 GEN
Solar/Wind Harmer
0.124
247521TR3_G114
Solar/Wind Harmer
6.497
24695305TIMB G C
Solar/Wind Harmer
6.263
270445AC2-157 GEN2
Solar/Wind Harmer
0
274776LINCOLN ;7U
50/50
18.14
970373AG2-245 GEN
Solar/Wind Harmer
2.43
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
20.606
959081AF2-199 GEN
Solar/Wind Harmer
1.082
276872AE1-163_GEN1
Solar/Wind Harmer
14.773
274851PROVIDENC;RU
Solar/Wind Harmer
6.034
24386205FR-12G C
Solar/Wind Harmer
8.33
963741AG1-226 GEN
Solar/Wind Harmer
4.356
276686W4-005 GEN3
Solar/Wind Harmer
5.74
276764AC1-053 GEN2
Solar/Wind Harmer
7.46
276911AD2-131_GEN
Solar/Wind Harmer
0.453
270004AE1-209 GEN
Solar/Wind Harmer
13.697
270201AC2-176 GEN
Solar/Wind Harmer
8.545
24379505HDWTR1G C
Solar/Wind Harmer
12.438
970885AG2-551 GEN
Solar/Wind Harmer
2.911
24344105CKG2
50/50
17.764
270101X2-052 CT2
50/50
3.074
965791AG1-447 GEN
Solar/Wind Harmer
13.238
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
8.546
270180AB1-006 GEN1
Solar/Wind Harmer
14.875
24791305MDL-5G
Solar/Wind Harmer
5.509
276741O09 GEN1
Solar/Wind Harmer
8.652
944541AF1-119 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
16.147
944221AF1-090 GEN
Solar/Wind Harmer
27.427
270191TR4_S_V150
Solar/Wind Harmer
4.951
24641605TWIN BRNCH
50/50
0.035
970707AG2-453 GEN
Solar/Wind Harmer
3.232
944531AF1-118 GEN
Solar/Wind Harmer
3.989
970833AG2-524 GEN
Solar/Wind Harmer
9.992
958481AF2-142 GEN
Solar/Wind Harmer
1.671
274862TOP CROP ;2U
Solar/Wind Harmer
13.024
274879MINONK ;1U
Solar/Wind Harmer
17.091
971675AH1-338 GEN
Solar/Wind Harmer
1.962
970781AG2-491 GEN
Solar/Wind Harmer
1.059
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.19
276903AD2-071 C
Solar/Wind Harmer
0.899
945391AF1-204 GEN
Solar/Wind Harmer
34.921
270247TR4_N_V136
Solar/Wind Harmer
1.644
270102X2-052 ST
50/50
3.326
970901AG2-562 GEN
50/50
12.603
24344005CKG1
50/50
14.512
274777LINCOLN ;8U
50/50
18.14
961051AF2-396 GEN
Solar/Wind Harmer
2.356
961051AF2-396 GEN
Solar/Wind Harmer
18.844
972231SS25-0005
Solar/Wind Harmer
1.856
971411AH1-196 GEN
Solar/Wind Harmer
1.635
274855GSG-6 ;RU
Solar/Wind Harmer
9.305
276876AE1-163_GEN2
Solar/Wind Harmer
14.773
276782AC1-033 GEN
Solar/Wind Harmer
8.174
24386405FR-21G C
Solar/Wind Harmer
7.979
276763AC1-053 GEN1
Solar/Wind Harmer
7.46
270599AE1-208 GEN
Solar/Wind Harmer
0.756
971029AG2-637 GEN
Solar/Wind Harmer
1.009
270100X2-052 CT1
50/50
3.074
274770LINCOLN ;1U
50/50
18.14
274771LINCOLN ;2U
50/50
18.14
945111AF1-176 GEN
Solar/Wind Harmer
2.108
945111AF1-176 GEN
Solar/Wind Harmer
11.49
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.402
940581AE2-045 GEN
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
6.469
276863AD2-134 GEN
Solar/Wind Harmer
4.499
276861AD2-134 GEN
Solar/Wind Harmer
4.499
274856ECOGROVE ;U1
Solar/Wind Harmer
8.351
970571AG2-364 GEN
Solar/Wind Harmer
2.139
971681AH1-341 GEN
Solar/Wind Harmer
1.596
938861AE1-114 GEN
Solar/Wind Harmer
24.893
274858EASY ROAD;U2
Solar/Wind Harmer
9.917
965011AG1-365 GEN
Solar/Wind Harmer
1.053
270594AE1-207 GEN
Solar/Wind Harmer
1.485
270240V3-007_GEN2
Solar/Wind Harmer
9.739
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.086
943021AE2-325 GEN
Solar/Wind Harmer
7.365
276843GEN-1.7
Solar/Wind Harmer
1.523
958011AF2-095 GEN
Solar/Wind Harmer
1.654
276691AA1-018 GEN1
Solar/Wind Harmer
1.199
958491AF2-143 GEN
Solar/Wind Harmer
1.651
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.287
24697905MDL-4G C
Solar/Wind Harmer
5.509
276646AC1-214 GEN2
Solar/Wind Harmer
3.237
274878BISHOP HL;2U
Solar/Wind Harmer
8.109
274854TWINGROVE;U2
Solar/Wind Harmer
15.712
965091AG1-374 GEN
Solar/Wind Harmer
3.052
965931AG1-462 GEN
Solar/Wind Harmer
2.578
964611AG1-324 GEN
Solar/Wind Harmer
0.76
270356AE2-297 GEN
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.086
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
14.391
943121AE2-341 GEN
Solar/Wind Harmer
1.695
957471AF2-041 GEN
Solar/Wind Harmer
3.247
274848CAMPGROVE;RU
Solar/Wind Harmer
12.124
276785W4-005 GEN1
Solar/Wind Harmer
5.74
276849AB2-070 GEN2
Solar/Wind Harmer
4.926
970289AG2-191 GEN
Solar/Wind Harmer
1.255
970291AG2-192 GEN
Solar/Wind Harmer
0.684
270246TR4_N_V150
Solar/Wind Harmer
1.644
957201AF2-014 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
50/50
18.14
970349AG2-230 GEN
Solar/Wind Harmer
1.922
971347AH1-153 GEN
Solar/Wind Harmer
0.641
960591AF2-350 GEN
Solar/Wind Harmer
1.148
939351AE1-166 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
43.942
926823AC1-168 GEN
Solar/Wind Harmer
13.12
274857EASY ROAD;U1
Solar/Wind Harmer
9.917
276656WTG2_EQ
Solar/Wind Harmer
2.36
276615X2-022 GEN
Solar/Wind Harmer
4.283
24725505WLD G2 C
Solar/Wind Harmer
6.849
961761AG1-017 GEN
Solar/Wind Harmer
0.831
965051AG1-369 GEN
Solar/Wind Harmer
0.417
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.279
958091AF2-103 GEN
Solar/Wind Harmer
0
24643105BUCHANAN
50/50
0.026
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
14.152
970031AG2-029 GEN
Solar/Wind Harmer
2.845
970833AG2-524 GEN
Solar/Wind Harmer
1.249
962781AG1-127 GEN
Solar/Wind Harmer
1.049
276868AE1-113 GEN
Solar/Wind Harmer
25.637
971171AH1-044 GEN
Solar/Wind Harmer
2.165
24697605MDL-3G C
Solar/Wind Harmer
8.264
270181AB1-006 GEN2
Solar/Wind Harmer
1.653
960971AF2-388 GEN
Solar/Wind Harmer
32.614
24385905FR-11G C
Solar/Wind Harmer
15.687
946321AF1-296 GEN
Solar/Wind Harmer
30.3
274853TWINGROVE;U1
Solar/Wind Harmer
15.712
959611AF2-252 GEN
Solar/Wind Harmer
4.069
960611AF2-352 GEN
Solar/Wind Harmer
4.069
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.317
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.728
270144AC1-141 ST1_
50/50
4.385
24642205MAYFLWER
50/50
1.524
962601AG1-109 GEN
50/50
5.878
247620Y3-023
50/50
0.982
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.5
274861TOP CROP ;1U
Solar/Wind Harmer
13.024
971067AG2-660 GEN
Solar/Wind Harmer
4.33
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
16.693
959331AF2-224 GEN
Solar/Wind Harmer
1.053
276655WTG1_EQ
Solar/Wind Harmer
17.823
963841AG1-237 GEN
Solar/Wind Harmer
31.024
270031AE2-169
Solar/Wind Harmer
0.756
965041AG1-368 GEN
Solar/Wind Harmer
0.91
24699105WLD G1 C
Solar/Wind Harmer
6.849
270383AD1-128 GEN
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.008
270071AF1-092 GEN
Solar/Wind Harmer
1.786
957891AF2-083 GEN
Solar/Wind Harmer
1.78
274888KELLY CRK;1U
Solar/Wind Harmer
15.676
276893AG1-478 C
Solar/Wind Harmer
0.909
276602WESTBROOK C
Solar/Wind Harmer
4.589
274863CRW1-WTG
Solar/Wind Harmer
12.737
274864CRW2-WTG
Solar/Wind Harmer
12.737
276603SUBLETTE C
Solar/Wind Harmer
2.146
24387305FR-4G C
Solar/Wind Harmer
11.969
24386605FR-22G C
Solar/Wind Harmer
7.979
24387005FR-3G C
Solar/Wind Harmer
7.9
274880W4-005 GEN4
Solar/Wind Harmer
5.74
270005AE1-210 C O1
Solar/Wind Harmer
13.697
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.264
246936BC-WTG1
Solar/Wind Harmer
5.962
246937BC-WTG2
Solar/Wind Harmer
5.962
274773LINCOLN ;4U
50/50
18.14
24307105BERRINSP G
50/50
0.043
270505AE1-170 C O1
Solar/Wind Harmer
1.783
962691AG1-118 GEN
Solar/Wind Harmer
3.318
971997AH1-543 GEN
Solar/Wind Harmer
1.723
276889AE2-281 GEN
Solar/Wind Harmer
4.221
957841AF2-078 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
1.975
24691005MDL-2G C
Solar/Wind Harmer
8.264
965021AG1-366 GEN
Solar/Wind Harmer
4.211
276158O29GEN2
Solar/Wind Harmer
9.213
276708O09 GEN2
Solar/Wind Harmer
8.652
958861AF2-177 GEN
Solar/Wind Harmer
31.906
942221AE2-234 GEN
Solar/Wind Harmer
0.346
945371AF1-202 GEN
Solar/Wind Harmer
15.277
971993AH1-541 GEN
Solar/Wind Harmer
0.889
276621W2-048 GEN
Solar/Wind Harmer
13.64
270032AE2-172
Solar/Wind Harmer
7.423
942481AE2-261 GEN
Solar/Wind Harmer
2.729
970825AG2-519 GEN
Solar/Wind Harmer
3.672
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.699
270543AE2-219 C
Solar/Wind Harmer
0.728
247607V1-011 GEN
Solar/Wind Harmer
5.196
270435AC2-044 GEN
Solar/Wind Harmer
0.132
274772LINCOLN ;3U
50/50
18.14
274774LINCOLN ;5U
50/50
18.14
944961AF1-161 GEN
50/50
5.878
270043AE2-236 GEN
Solar/Wind Harmer
0.666
971771AH1-392 GEN
Solar/Wind Harmer
1.083
970941AG2-585 GEN
Solar/Wind Harmer
0.632
276897AD1-100 C
Solar/Wind Harmer
151.637
276805AD2-038 GEN
Solar/Wind Harmer
12.877
971605AH1-302 GEN
Solar/Wind Harmer
16.497
970569AG2-363 GEN
Solar/Wind Harmer
3.209
276157O29GEN1
Solar/Wind Harmer
9.213
276645AC1-214 GEN1
Solar/Wind Harmer
3.237
939741AE1-205 GEN
Solar/Wind Harmer
2.07
942111AE2-223 GEN
Solar/Wind Harmer
24.22
970241AG2-163 GEN
Solar/Wind Harmer
2.42
276174W4-005 GEN2
Solar/Wind Harmer
5.74
276668AB2-070 GEN1
Solar/Wind Harmer
4.926
276838X2-022 GEN2
Solar/Wind Harmer
0.509
970825AG2-519 GEN
Solar/Wind Harmer
0.573
270007AE1-245 C
Solar/Wind Harmer
7.285
246938BC-WTG3
Solar/Wind Harmer
6.065
970521AG2-332 GEN
50/50
23.519
276806AD2-047 C O1
Solar/Wind Harmer
35.37
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.165
274877BISHOP HL;1U
Solar/Wind Harmer
8.109
276848AB2-070 GEN3
Solar/Wind Harmer
4.926
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.722
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.183
WECLTFEXP_WEC->PJM
CLTF
7.061
MECLTFEXP_MEC->PJM
CLTF
25.64
AG2-052LTFEXP_AG2-052->PJM
LTF
0.436
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.307
LAGNLTFEXP_LAGN->PJM
CLTF
13.625
AH1-155LTFEXP_AH1-155->PJM
LTF
0.653
NYPJM->LTFIMP_NY
CLTF
3.51
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.586
SIGELTFEXP_SIGE->PJM
CLTF
0.545
CBM West 1LTFEXP_CBM-W1->PJM
CBM
218.246
LGEELTFEXP_LGEE->PJM
CLTF
5.512
TVALTFEXP_TVA->PJM
CLTF
5.176
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.752

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.1 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5114.58
MW Contribution:
2.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972207SS24-0001
Solar/Wind Harmer
3.771
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
1.24
274847GR RIDGE ;BU
Solar/Wind Harmer
13.871
959091AF2-200 GEN
Solar/Wind Harmer
2.292
274849CRESCENT ;1U
Solar/Wind Harmer
4.671
965651AG1-433 GEN
Solar/Wind Harmer
16.751
970289AG2-191 GEN
Solar/Wind Harmer
0.194
957381AF2-032 GEN
Solar/Wind Harmer
0.187
276916AD2-100_GEN
Solar/Wind Harmer
1.936
946031AF1-268 GEN
Solar/Wind Harmer
0.718
965421AG1-410 GEN
Solar/Wind Harmer
2.22
270142AC1-141 CT1_
50/50
5.33
270143AC1-141 CT2_
50/50
5.33
24639705ELKHART HY
50/50
0.355
965681AG1-436 GEN
Solar/Wind Harmer
1.621
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.201
276694AA1-018 GEN2
Solar/Wind Harmer
12.56
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
6.03
971343AH1-151 GEN
Solar/Wind Harmer
2.292
970169AG2-114 GEN
Solar/Wind Harmer
1.128
959341AF2-225 GEN
Solar/Wind Harmer
1.624
971087AG2-675 GEN
Solar/Wind Harmer
6.799
970291AG2-192 GEN
Solar/Wind Harmer
0.133
963791AG1-232 GEN
Solar/Wind Harmer
1.369
247521TR3_G114
Solar/Wind Harmer
6.863
24695305TIMB G C
Solar/Wind Harmer
6.622
270445AC2-157 GEN2
Solar/Wind Harmer
0
274776LINCOLN ;7U
50/50
19.36
970373AG2-245 GEN
Solar/Wind Harmer
2.641
964401AG1-302 GEN
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.038
970707AG2-453 GEN
Solar/Wind Harmer
3.442
970833AG2-524 GEN
Solar/Wind Harmer
10.625
958481AF2-142 GEN
Solar/Wind Harmer
1.773
274862TOP CROP ;2U
Solar/Wind Harmer
13.823
944531AF1-118 GEN
Solar/Wind Harmer
4.124
274879MINONK ;1U
Solar/Wind Harmer
18.098
970781AG2-491 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
2.078
966841AG1-555 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.948
965911AG1-460 GEN
Solar/Wind Harmer
2.235
945391AF1-204 GEN
Solar/Wind Harmer
35.346
270247TR4_N_V136
Solar/Wind Harmer
1.736
270102X2-052 ST
50/50
3.588
970901AG2-562 GEN
50/50
13.596
24344005CKG1
50/50
15.641
274777LINCOLN ;8U
50/50
19.36
961051AF2-396 GEN
Solar/Wind Harmer
2.534
961051AF2-396 GEN
Solar/Wind Harmer
20.273
972231SS25-0005
Solar/Wind Harmer
1.984
971411AH1-196 GEN
Solar/Wind Harmer
1.732
274855GSG-6 ;RU
Solar/Wind Harmer
9.856
276876AE1-163_GEN2
Solar/Wind Harmer
15.618
24386405FR-21G C
Solar/Wind Harmer
8.604
276782AC1-033 GEN
Solar/Wind Harmer
8.596
276763AC1-053 GEN1
Solar/Wind Harmer
7.686
270599AE1-208 GEN
Solar/Wind Harmer
0.777
971029AG2-637 GEN
Solar/Wind Harmer
1.009
24344105CKG2
50/50
19.181
270101X2-052 CT2
50/50
3.316
965791AG1-447 GEN
Solar/Wind Harmer
14.269
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
9.049
270180AB1-006 GEN1
Solar/Wind Harmer
16.282
24791305MDL-5G
Solar/Wind Harmer
6.03
276741O09 GEN1
Solar/Wind Harmer
9.119
276726Z2-087_GEN
Solar/Wind Harmer
16.885
944541AF1-119 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
27.731
270191TR4_S_V150
Solar/Wind Harmer
5.23
270100X2-052 CT1
50/50
3.316
274770LINCOLN ;1U
50/50
19.36
274771LINCOLN ;2U
50/50
19.36
945111AF1-176 GEN
Solar/Wind Harmer
2.267
945111AF1-176 GEN
Solar/Wind Harmer
12.356
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.665
274850MENDOTA H;RU
Solar/Wind Harmer
6.853
276863AD2-134 GEN
Solar/Wind Harmer
4.766
276861AD2-134 GEN
Solar/Wind Harmer
4.766
274856ECOGROVE ;U1
Solar/Wind Harmer
8.831
970571AG2-364 GEN
Solar/Wind Harmer
2.258
971681AH1-341 GEN
Solar/Wind Harmer
1.687
938861AE1-114 GEN
Solar/Wind Harmer
26.302
274858EASY ROAD;U2
Solar/Wind Harmer
10.475
965011AG1-365 GEN
Solar/Wind Harmer
1.11
270594AE1-207 GEN
Solar/Wind Harmer
1.575
270240V3-007_GEN2
Solar/Wind Harmer
9.719
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.091
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
15.301
943121AE2-341 GEN
Solar/Wind Harmer
1.802
957471AF2-041 GEN
Solar/Wind Harmer
3.438
274848CAMPGROVE;RU
Solar/Wind Harmer
12.74
970289AG2-191 GEN
Solar/Wind Harmer
1.347
970291AG2-192 GEN
Solar/Wind Harmer
0.735
276785W4-005 GEN1
Solar/Wind Harmer
5.919
276849AB2-070 GEN2
Solar/Wind Harmer
5.081
270246TR4_N_V150
Solar/Wind Harmer
1.736
957201AF2-014 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
50/50
19.36
970349AG2-230 GEN
Solar/Wind Harmer
2.07
971347AH1-153 GEN
Solar/Wind Harmer
0.69
958381AF2-132 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.224
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
46.474
926823AC1-168 GEN
Solar/Wind Harmer
13.842
274857EASY ROAD;U1
Solar/Wind Harmer
10.475
276656WTG2_EQ
Solar/Wind Harmer
2.468
276615X2-022 GEN
Solar/Wind Harmer
4.403
24725505WLD G2 C
Solar/Wind Harmer
7.152
965051AG1-369 GEN
Solar/Wind Harmer
0.441
961761AG1-017 GEN
Solar/Wind Harmer
0.849
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.391
958091AF2-103 GEN
Solar/Wind Harmer
0
270144AC1-141 ST1_
50/50
4.718
24642205MAYFLWER
50/50
1.639
962601AG1-109 GEN
50/50
6.326
247620Y3-023
50/50
1.053
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.13
274861TOP CROP ;1U
Solar/Wind Harmer
13.823
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
18.272
971067AG2-660 GEN
Solar/Wind Harmer
4.584
959331AF2-224 GEN
Solar/Wind Harmer
1.11
276655WTG1_EQ
Solar/Wind Harmer
18.638
963841AG1-237 GEN
Solar/Wind Harmer
33.096
965041AG1-368 GEN
Solar/Wind Harmer
0.961
270031AE2-169
Solar/Wind Harmer
0.777
24699105WLD G1 C
Solar/Wind Harmer
7.152
270383AD1-128 GEN
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.008
957891AF2-083 GEN
Solar/Wind Harmer
1.915
270071AF1-092 GEN
Solar/Wind Harmer
1.91
274888KELLY CRK;1U
Solar/Wind Harmer
16.701
276893AG1-478 C
Solar/Wind Harmer
0.967
276602WESTBROOK C
Solar/Wind Harmer
4.861
274863CRW1-WTG
Solar/Wind Harmer
13.439
274864CRW2-WTG
Solar/Wind Harmer
13.439
276603SUBLETTE C
Solar/Wind Harmer
2.266
24387305FR-4G C
Solar/Wind Harmer
12.907
24386605FR-22G C
Solar/Wind Harmer
8.604
24387005FR-3G C
Solar/Wind Harmer
8.518
274880W4-005 GEN4
Solar/Wind Harmer
5.919
270005AE1-210 C O1
Solar/Wind Harmer
13.854
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.292
246936BC-WTG1
Solar/Wind Harmer
6.341
246937BC-WTG2
Solar/Wind Harmer
6.341
24307105BERRINSP G
50/50
0.047
274773LINCOLN ;4U
50/50
19.36
270505AE1-170 C O1
Solar/Wind Harmer
1.918
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.521
24691005MDL-2G C
Solar/Wind Harmer
9.046
971997AH1-543 GEN
Solar/Wind Harmer
1.823
971549AH1-272 GEN
Solar/Wind Harmer
2.128
276889AE2-281 GEN
Solar/Wind Harmer
4.462
965021AG1-366 GEN
Solar/Wind Harmer
4.438
276158O29GEN2
Solar/Wind Harmer
9.711
276708O09 GEN2
Solar/Wind Harmer
9.119
958861AF2-177 GEN
Solar/Wind Harmer
32.716
942221AE2-234 GEN
Solar/Wind Harmer
0.36
945371AF1-202 GEN
Solar/Wind Harmer
15.608
971993AH1-541 GEN
Solar/Wind Harmer
0.917
270032AE2-172
Solar/Wind Harmer
7.876
276621W2-048 GEN
Solar/Wind Harmer
14.021
942481AE2-261 GEN
Solar/Wind Harmer
2.785
970825AG2-519 GEN
Solar/Wind Harmer
3.741
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.694
270543AE2-219 C
Solar/Wind Harmer
0.734
247607V1-011 GEN
Solar/Wind Harmer
5.511
270435AC2-044 GEN
Solar/Wind Harmer
0.14
943021AE2-325 GEN
Solar/Wind Harmer
7.925
276843GEN-1.7
Solar/Wind Harmer
1.622
958011AF2-095 GEN
Solar/Wind Harmer
1.762
945421AF1-207 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.273
958491AF2-143 GEN
Solar/Wind Harmer
1.749
24697905MDL-4G C
Solar/Wind Harmer
6.03
970819AG2-516 GEN
Solar/Wind Harmer
1.361
276646AC1-214 GEN2
Solar/Wind Harmer
3.406
274878BISHOP HL;2U
Solar/Wind Harmer
8.527
965931AG1-462 GEN
Solar/Wind Harmer
2.709
274854TWINGROVE;U2
Solar/Wind Harmer
16.378
965091AG1-374 GEN
Solar/Wind Harmer
3.181
964611AG1-324 GEN
Solar/Wind Harmer
0.776
270491AE1-102 GEN2
Solar/Wind Harmer
0.091
270356AE2-297 GEN
Solar/Wind Harmer
0
944961AF1-161 GEN
50/50
6.326
274772LINCOLN ;3U
50/50
19.36
274774LINCOLN ;5U
50/50
19.36
971771AH1-392 GEN
Solar/Wind Harmer
1.165
270043AE2-236 GEN
Solar/Wind Harmer
0.704
970941AG2-585 GEN
Solar/Wind Harmer
0.673
276897AD1-100 C
Solar/Wind Harmer
161.319
971605AH1-302 GEN
Solar/Wind Harmer
18.099
276805AD2-038 GEN
Solar/Wind Harmer
13.646
970569AG2-363 GEN
Solar/Wind Harmer
3.387
276157O29GEN1
Solar/Wind Harmer
9.711
276645AC1-214 GEN1
Solar/Wind Harmer
3.406
939741AE1-205 GEN
Solar/Wind Harmer
2.165
942111AE2-223 GEN
Solar/Wind Harmer
25.328
970241AG2-163 GEN
Solar/Wind Harmer
2.554
276174W4-005 GEN2
Solar/Wind Harmer
5.919
276668AB2-070 GEN1
Solar/Wind Harmer
5.081
276838X2-022 GEN2
Solar/Wind Harmer
0.523
970825AG2-519 GEN
Solar/Wind Harmer
0.584
270007AE1-245 C
Solar/Wind Harmer
7.728
246938BC-WTG3
Solar/Wind Harmer
6.451
24643105BUCHANAN
50/50
0.028
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
15.078
970031AG2-029 GEN
Solar/Wind Harmer
3.032
970833AG2-524 GEN
Solar/Wind Harmer
1.328
962781AG1-127 GEN
Solar/Wind Harmer
1.113
276868AE1-113 GEN
Solar/Wind Harmer
27.147
24697605MDL-3G C
Solar/Wind Harmer
9.046
270181AB1-006 GEN2
Solar/Wind Harmer
1.809
971171AH1-044 GEN
Solar/Wind Harmer
2.292
24385905FR-11G C
Solar/Wind Harmer
16.916
960971AF2-388 GEN
Solar/Wind Harmer
33.501
946321AF1-296 GEN
Solar/Wind Harmer
31.858
274853TWINGROVE;U1
Solar/Wind Harmer
16.378
959611AF2-252 GEN
Solar/Wind Harmer
4.242
960611AF2-352 GEN
Solar/Wind Harmer
4.242
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.333
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.734
274872LEEDK;1U
Solar/Wind Harmer
21.85
959081AF2-199 GEN
Solar/Wind Harmer
1.146
276872AE1-163_GEN1
Solar/Wind Harmer
15.618
24386205FR-12G C
Solar/Wind Harmer
8.983
274851PROVIDENC;RU
Solar/Wind Harmer
6.348
963741AG1-226 GEN
Solar/Wind Harmer
4.597
276686W4-005 GEN3
Solar/Wind Harmer
5.919
276764AC1-053 GEN2
Solar/Wind Harmer
7.686
276911AD2-131_GEN
Solar/Wind Harmer
0.461
270004AE1-209 GEN
Solar/Wind Harmer
13.854
270201AC2-176 GEN
Solar/Wind Harmer
8.734
24379505HDWTR1G C
Solar/Wind Harmer
12.413
970885AG2-551 GEN
Solar/Wind Harmer
2.937
270349AD2-093_GEN
Solar/Wind Helper
0.709
970521AG2-332 GEN
50/50
25.247
276806AD2-047 C O1
Solar/Wind Harmer
37.684
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.292
274877BISHOP HL;1U
Solar/Wind Harmer
8.527
276848AB2-070 GEN3
Solar/Wind Harmer
5.081
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.709
CBM West 2LTFEXP_CBM-W2->PJM
CBM
127.984
WECLTFEXP_WEC->PJM
CLTF
7.473
MECLTFEXP_MEC->PJM
CLTF
26.605
AG2-052LTFEXP_AG2-052->PJM
LTF
0.465
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.218
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.445
LAGNLTFEXP_LAGN->PJM
CLTF
13.263
AH1-155LTFEXP_AH1-155->PJM
LTF
0.698
NYPJM->LTFIMP_NY
CLTF
3.513
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.679
SIGELTFEXP_SIGE->PJM
CLTF
0.501
CBM West 1LTFEXP_CBM-W1->PJM
CBM
229.695
LGEELTFEXP_LGEE->PJM
CLTF
4.399
TVALTFEXP_TVA->PJM
CLTF
4.838
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
52.01

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5065.25
MW Contribution:
1.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.966
270143AC1-141 CT2_
50/50
4.966
24639705ELKHART HY
50/50
0.332
965681AG1-436 GEN
Solar/Wind Harmer
1.508
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.133
276694AA1-018 GEN2
Solar/Wind Harmer
11.866
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.171
970169AG2-114 GEN
Solar/Wind Harmer
1.075
24755605MDL-5G
Solar/Wind Harmer
5.525
959341AF2-225 GEN
Solar/Wind Harmer
1.557
971087AG2-675 GEN
Solar/Wind Harmer
6.491
963791AG1-232 GEN
Solar/Wind Harmer
1.314
970291AG2-192 GEN
Solar/Wind Harmer
0.124
247521TR3_G114
Solar/Wind Harmer
6.522
24695305TIMB G C
Solar/Wind Harmer
6.288
270445AC2-157 GEN2
Solar/Wind Harmer
0
24344105CKG2
50/50
17.806
270101X2-052 CT2
50/50
3.082
965791AG1-447 GEN
Solar/Wind Harmer
13.273
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
8.57
270180AB1-006 GEN1
Solar/Wind Harmer
14.919
24791305MDL-5G
Solar/Wind Harmer
5.525
276741O09 GEN1
Solar/Wind Harmer
8.678
944541AF1-119 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
16.196
944221AF1-090 GEN
Solar/Wind Harmer
27.525
270191TR4_S_V150
Solar/Wind Harmer
4.97
270144AC1-141 ST1_
50/50
4.396
24642205MAYFLWER
50/50
1.528
962601AG1-109 GEN
50/50
5.894
247620Y3-023
50/50
0.985
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.549
274861TOP CROP ;1U
Solar/Wind Harmer
13.061
971067AG2-660 GEN
Solar/Wind Harmer
4.343
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
16.742
959331AF2-224 GEN
Solar/Wind Harmer
1.056
276655WTG1_EQ
Solar/Wind Harmer
17.878
963841AG1-237 GEN
Solar/Wind Harmer
31.122
270031AE2-169
Solar/Wind Harmer
0.758
965041AG1-368 GEN
Solar/Wind Harmer
0.913
24699105WLD G1 C
Solar/Wind Harmer
6.873
270383AD1-128 GEN
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.036
970707AG2-453 GEN
Solar/Wind Harmer
3.24
944531AF1-118 GEN
Solar/Wind Harmer
4
970833AG2-524 GEN
Solar/Wind Harmer
10.019
958481AF2-142 GEN
Solar/Wind Harmer
1.675
274862TOP CROP ;2U
Solar/Wind Harmer
13.061
274879MINONK ;1U
Solar/Wind Harmer
17.14
971675AH1-338 GEN
Solar/Wind Harmer
1.967
970781AG2-491 GEN
Solar/Wind Harmer
1.063
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.198
276903AD2-071 C
Solar/Wind Harmer
0.902
945391AF1-204 GEN
Solar/Wind Harmer
35.046
270247TR4_N_V136
Solar/Wind Harmer
1.65
24643105BUCHANAN
50/50
0.026
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
14.191
970031AG2-029 GEN
Solar/Wind Harmer
2.853
970833AG2-524 GEN
Solar/Wind Harmer
1.252
962781AG1-127 GEN
Solar/Wind Harmer
1.052
276868AE1-113 GEN
Solar/Wind Harmer
25.71
971171AH1-044 GEN
Solar/Wind Harmer
2.171
24697605MDL-3G C
Solar/Wind Harmer
8.288
270181AB1-006 GEN2
Solar/Wind Harmer
1.658
960971AF2-388 GEN
Solar/Wind Harmer
32.712
24385905FR-11G C
Solar/Wind Harmer
15.735
946321AF1-296 GEN
Solar/Wind Harmer
30.393
274853TWINGROVE;U1
Solar/Wind Harmer
15.76
959611AF2-252 GEN
Solar/Wind Harmer
4.082
972207SS24-0001
Solar/Wind Harmer
3.543
972181SS23-001
Solar/Wind Harmer
1.163
270055AF2-134 C O1
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
13.082
959091AF2-200 GEN
Solar/Wind Harmer
2.171
270100X2-052 CT1
50/50
3.082
274770LINCOLN ;1U
50/50
18.189
274771LINCOLN ;2U
50/50
18.189
945111AF1-176 GEN
Solar/Wind Harmer
2.113
945111AF1-176 GEN
Solar/Wind Harmer
11.52
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.415
940581AE2-045 GEN
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
6.488
276863AD2-134 GEN
Solar/Wind Harmer
4.512
276861AD2-134 GEN
Solar/Wind Harmer
4.512
274856ECOGROVE ;U1
Solar/Wind Harmer
8.375
970571AG2-364 GEN
Solar/Wind Harmer
2.146
971681AH1-341 GEN
Solar/Wind Harmer
1.601
938861AE1-114 GEN
Solar/Wind Harmer
24.967
274858EASY ROAD;U2
Solar/Wind Harmer
9.947
965011AG1-365 GEN
Solar/Wind Harmer
1.056
270594AE1-207 GEN
Solar/Wind Harmer
1.49
270240V3-007_GEN2
Solar/Wind Harmer
9.777
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.086
274772LINCOLN ;3U
50/50
18.189
274774LINCOLN ;5U
50/50
18.189
944961AF1-161 GEN
50/50
5.894
270043AE2-236 GEN
Solar/Wind Harmer
0.667
971771AH1-392 GEN
Solar/Wind Harmer
1.085
970941AG2-585 GEN
Solar/Wind Harmer
0.633
276897AD1-100 C
Solar/Wind Harmer
152.054
276805AD2-038 GEN
Solar/Wind Harmer
12.914
971605AH1-302 GEN
Solar/Wind Harmer
16.544
970569AG2-363 GEN
Solar/Wind Harmer
3.218
276157O29GEN1
Solar/Wind Harmer
9.24
276645AC1-214 GEN1
Solar/Wind Harmer
3.247
939741AE1-205 GEN
Solar/Wind Harmer
2.076
942111AE2-223 GEN
Solar/Wind Harmer
24.294
970241AG2-163 GEN
Solar/Wind Harmer
2.428
276174W4-005 GEN2
Solar/Wind Harmer
5.759
276668AB2-070 GEN1
Solar/Wind Harmer
4.942
276838X2-022 GEN2
Solar/Wind Harmer
0.51
970825AG2-519 GEN
Solar/Wind Harmer
0.575
274849CRESCENT ;1U
Solar/Wind Harmer
4.453
965651AG1-433 GEN
Solar/Wind Harmer
16.356
970289AG2-191 GEN
Solar/Wind Harmer
0.181
957381AF2-032 GEN
Solar/Wind Harmer
0.184
276916AD2-100_GEN
Solar/Wind Harmer
1.907
946031AF1-268 GEN
Solar/Wind Harmer
0.709
965421AG1-410 GEN
Solar/Wind Harmer
2.099
270349AD2-093_GEN
Solar/Wind Helper
0.718
960611AF2-352 GEN
Solar/Wind Harmer
4.082
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.322
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.731
270102X2-052 ST
50/50
3.334
970901AG2-562 GEN
50/50
12.636
24344005CKG1
50/50
14.55
274777LINCOLN ;8U
50/50
18.189
961051AF2-396 GEN
Solar/Wind Harmer
2.362
961051AF2-396 GEN
Solar/Wind Harmer
18.894
972231SS25-0005
Solar/Wind Harmer
1.861
274776LINCOLN ;7U
50/50
18.189
970373AG2-245 GEN
Solar/Wind Harmer
2.436
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
20.665
959081AF2-199 GEN
Solar/Wind Harmer
1.086
276872AE1-163_GEN1
Solar/Wind Harmer
14.816
274851PROVIDENC;RU
Solar/Wind Harmer
6.052
24386205FR-12G C
Solar/Wind Harmer
8.356
963741AG1-226 GEN
Solar/Wind Harmer
4.37
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
14.431
943121AE2-341 GEN
Solar/Wind Harmer
1.699
957471AF2-041 GEN
Solar/Wind Harmer
3.257
274848CAMPGROVE;RU
Solar/Wind Harmer
12.161
276785W4-005 GEN1
Solar/Wind Harmer
5.759
276849AB2-070 GEN2
Solar/Wind Harmer
4.942
970289AG2-191 GEN
Solar/Wind Harmer
1.259
970291AG2-192 GEN
Solar/Wind Harmer
0.687
270246TR4_N_V150
Solar/Wind Harmer
1.65
957201AF2-014 GEN
Solar/Wind Harmer
0
276686W4-005 GEN3
Solar/Wind Harmer
5.759
276764AC1-053 GEN2
Solar/Wind Harmer
7.485
276911AD2-131_GEN
Solar/Wind Harmer
0.454
270004AE1-209 GEN
Solar/Wind Harmer
13.746
270201AC2-176 GEN
Solar/Wind Harmer
8.576
24379505HDWTR1G C
Solar/Wind Harmer
12.487
970885AG2-551 GEN
Solar/Wind Harmer
2.924
943021AE2-325 GEN
Solar/Wind Harmer
7.384
276843GEN-1.7
Solar/Wind Harmer
1.527
958011AF2-095 GEN
Solar/Wind Harmer
1.658
276691AA1-018 GEN1
Solar/Wind Harmer
1.202
958491AF2-143 GEN
Solar/Wind Harmer
1.656
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.291
24697905MDL-4G C
Solar/Wind Harmer
5.525
276646AC1-214 GEN2
Solar/Wind Harmer
3.247
274878BISHOP HL;2U
Solar/Wind Harmer
8.133
274854TWINGROVE;U2
Solar/Wind Harmer
15.76
965091AG1-374 GEN
Solar/Wind Harmer
3.061
965931AG1-462 GEN
Solar/Wind Harmer
2.586
964611AG1-324 GEN
Solar/Wind Harmer
0.763
270356AE2-297 GEN
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.086
970521AG2-332 GEN
50/50
23.582
276806AD2-047 C O1
Solar/Wind Harmer
35.467
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.171
274877BISHOP HL;1U
Solar/Wind Harmer
8.133
276848AB2-070 GEN3
Solar/Wind Harmer
4.942
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.718
971411AH1-196 GEN
Solar/Wind Harmer
1.64
274855GSG-6 ;RU
Solar/Wind Harmer
9.332
276876AE1-163_GEN2
Solar/Wind Harmer
14.816
276782AC1-033 GEN
Solar/Wind Harmer
8.199
24386405FR-21G C
Solar/Wind Harmer
8.004
276763AC1-053 GEN1
Solar/Wind Harmer
7.485
270599AE1-208 GEN
Solar/Wind Harmer
0.758
971029AG2-637 GEN
Solar/Wind Harmer
1.014
274775LINCOLN ;6U
50/50
18.189
970349AG2-230 GEN
Solar/Wind Harmer
1.927
971347AH1-153 GEN
Solar/Wind Harmer
0.642
960591AF2-350 GEN
Solar/Wind Harmer
1.152
939351AE1-166 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
44.067
926823AC1-168 GEN
Solar/Wind Harmer
13.159
274857EASY ROAD;U1
Solar/Wind Harmer
9.947
276656WTG2_EQ
Solar/Wind Harmer
2.367
276615X2-022 GEN
Solar/Wind Harmer
4.298
24725505WLD G2 C
Solar/Wind Harmer
6.873
961761AG1-017 GEN
Solar/Wind Harmer
0.834
965051AG1-369 GEN
Solar/Wind Harmer
0.419
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.309
958091AF2-103 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
7.32
246938BC-WTG3
Solar/Wind Harmer
6.094
24653605MOTTVILLE
50/50
0.008
270071AF1-092 GEN
Solar/Wind Harmer
1.791
957891AF2-083 GEN
Solar/Wind Harmer
1.784
274888KELLY CRK;1U
Solar/Wind Harmer
15.718
276893AG1-478 C
Solar/Wind Harmer
0.911
276602WESTBROOK C
Solar/Wind Harmer
4.602
274863CRW1-WTG
Solar/Wind Harmer
12.774
274864CRW2-WTG
Solar/Wind Harmer
12.774
276603SUBLETTE C
Solar/Wind Harmer
2.152
24387305FR-4G C
Solar/Wind Harmer
12.006
24386605FR-22G C
Solar/Wind Harmer
8.004
24387005FR-3G C
Solar/Wind Harmer
7.924
274880W4-005 GEN4
Solar/Wind Harmer
5.759
270005AE1-210 C O1
Solar/Wind Harmer
13.746
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.269
246936BC-WTG1
Solar/Wind Harmer
5.99
246937BC-WTG2
Solar/Wind Harmer
5.99
274773LINCOLN ;4U
50/50
18.189
24307105BERRINSP G
50/50
0.044
270505AE1-170 C O1
Solar/Wind Harmer
1.788
962691AG1-118 GEN
Solar/Wind Harmer
3.328
971997AH1-543 GEN
Solar/Wind Harmer
1.728
276889AE2-281 GEN
Solar/Wind Harmer
4.233
957841AF2-078 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
1.981
24691005MDL-2G C
Solar/Wind Harmer
8.288
965021AG1-366 GEN
Solar/Wind Harmer
4.223
276158O29GEN2
Solar/Wind Harmer
9.24
276708O09 GEN2
Solar/Wind Harmer
8.678
958861AF2-177 GEN
Solar/Wind Harmer
32.004
942221AE2-234 GEN
Solar/Wind Harmer
0.347
945371AF1-202 GEN
Solar/Wind Harmer
15.326
971993AH1-541 GEN
Solar/Wind Harmer
0.892
276621W2-048 GEN
Solar/Wind Harmer
13.685
270032AE2-172
Solar/Wind Harmer
7.448
942481AE2-261 GEN
Solar/Wind Harmer
2.738
970825AG2-519 GEN
Solar/Wind Harmer
3.685
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.71
270543AE2-219 C
Solar/Wind Harmer
0.731
247607V1-011 GEN
Solar/Wind Harmer
5.22
270435AC2-044 GEN
Solar/Wind Harmer
0.132
CBM West 1LTFEXP_CBM-W1->PJM
CBM
219.037
LGEELTFEXP_LGEE->PJM
CLTF
5.55
TVALTFEXP_TVA->PJM
CLTF
5.231
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.752
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.913
WECLTFEXP_WEC->PJM
CLTF
7.082
MECLTFEXP_MEC->PJM
CLTF
25.731
AG2-052LTFEXP_AG2-052->PJM
LTF
0.437
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.553
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.271
LAGNLTFEXP_LAGN->PJM
CLTF
13.735
AH1-155LTFEXP_AH1-155->PJM
LTF
0.655
NYPJM->LTFIMP_NY
CLTF
3.476
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.564
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5065.17
MW Contribution:
1.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.966
270143AC1-141 CT2_
50/50
4.966
24639705ELKHART HY
50/50
0.332
965681AG1-436 GEN
Solar/Wind Harmer
1.508
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.133
276694AA1-018 GEN2
Solar/Wind Harmer
11.866
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.171
970169AG2-114 GEN
Solar/Wind Harmer
1.075
24755605MDL-5G
Solar/Wind Harmer
5.525
959341AF2-225 GEN
Solar/Wind Harmer
1.557
971087AG2-675 GEN
Solar/Wind Harmer
6.491
963791AG1-232 GEN
Solar/Wind Harmer
1.314
970291AG2-192 GEN
Solar/Wind Harmer
0.124
247521TR3_G114
Solar/Wind Harmer
6.522
24695305TIMB G C
Solar/Wind Harmer
6.288
270445AC2-157 GEN2
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
3.082
274770LINCOLN ;1U
50/50
18.189
274771LINCOLN ;2U
50/50
18.189
945111AF1-176 GEN
Solar/Wind Harmer
2.113
945111AF1-176 GEN
Solar/Wind Harmer
11.52
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.415
940581AE2-045 GEN
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
6.488
276863AD2-134 GEN
Solar/Wind Harmer
4.512
276861AD2-134 GEN
Solar/Wind Harmer
4.512
274856ECOGROVE ;U1
Solar/Wind Harmer
8.375
970571AG2-364 GEN
Solar/Wind Harmer
2.146
971681AH1-341 GEN
Solar/Wind Harmer
1.601
938861AE1-114 GEN
Solar/Wind Harmer
24.967
274858EASY ROAD;U2
Solar/Wind Harmer
9.947
965011AG1-365 GEN
Solar/Wind Harmer
1.056
270594AE1-207 GEN
Solar/Wind Harmer
1.49
270240V3-007_GEN2
Solar/Wind Harmer
9.777
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.086
274775LINCOLN ;6U
50/50
18.189
970349AG2-230 GEN
Solar/Wind Harmer
1.927
971347AH1-153 GEN
Solar/Wind Harmer
0.642
960591AF2-350 GEN
Solar/Wind Harmer
1.152
939351AE1-166 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
44.067
926823AC1-168 GEN
Solar/Wind Harmer
13.159
274857EASY ROAD;U1
Solar/Wind Harmer
9.947
276656WTG2_EQ
Solar/Wind Harmer
2.367
276615X2-022 GEN
Solar/Wind Harmer
4.298
24725505WLD G2 C
Solar/Wind Harmer
6.873
961761AG1-017 GEN
Solar/Wind Harmer
0.834
965051AG1-369 GEN
Solar/Wind Harmer
0.419
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.309
958091AF2-103 GEN
Solar/Wind Harmer
0
270144AC1-141 ST1_
50/50
4.396
24642205MAYFLWER
50/50
1.528
962601AG1-109 GEN
50/50
5.894
247620Y3-023
50/50
0.985
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.549
274861TOP CROP ;1U
Solar/Wind Harmer
13.061
971067AG2-660 GEN
Solar/Wind Harmer
4.343
946581AF1-322 GEN
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.008
270071AF1-092 GEN
Solar/Wind Harmer
1.791
957891AF2-083 GEN
Solar/Wind Harmer
1.784
274888KELLY CRK;1U
Solar/Wind Harmer
15.718
276893AG1-478 C
Solar/Wind Harmer
0.911
276602WESTBROOK C
Solar/Wind Harmer
4.602
274863CRW1-WTG
Solar/Wind Harmer
12.774
274864CRW2-WTG
Solar/Wind Harmer
12.774
276603SUBLETTE C
Solar/Wind Harmer
2.152
24387305FR-4G C
Solar/Wind Harmer
12.006
24386605FR-22G C
Solar/Wind Harmer
8.004
24387005FR-3G C
Solar/Wind Harmer
7.924
274880W4-005 GEN4
Solar/Wind Harmer
5.759
24690905MDL-1G C
Solar/Wind Harmer
16.742
959331AF2-224 GEN
Solar/Wind Harmer
1.056
276655WTG1_EQ
Solar/Wind Harmer
17.878
963841AG1-237 GEN
Solar/Wind Harmer
31.122
270031AE2-169
Solar/Wind Harmer
0.758
965041AG1-368 GEN
Solar/Wind Harmer
0.913
24699105WLD G1 C
Solar/Wind Harmer
6.873
270383AD1-128 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
7.384
276843GEN-1.7
Solar/Wind Harmer
1.527
958011AF2-095 GEN
Solar/Wind Harmer
1.658
276691AA1-018 GEN1
Solar/Wind Harmer
1.202
958491AF2-143 GEN
Solar/Wind Harmer
1.656
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.291
24697905MDL-4G C
Solar/Wind Harmer
5.525
276646AC1-214 GEN2
Solar/Wind Harmer
3.247
274878BISHOP HL;2U
Solar/Wind Harmer
8.133
274854TWINGROVE;U2
Solar/Wind Harmer
15.76
965091AG1-374 GEN
Solar/Wind Harmer
3.061
965931AG1-462 GEN
Solar/Wind Harmer
2.586
964611AG1-324 GEN
Solar/Wind Harmer
0.763
270356AE2-297 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
50/50
18.189
274774LINCOLN ;5U
50/50
18.189
944961AF1-161 GEN
50/50
5.894
270043AE2-236 GEN
Solar/Wind Harmer
0.667
971771AH1-392 GEN
Solar/Wind Harmer
1.085
970941AG2-585 GEN
Solar/Wind Harmer
0.633
276897AD1-100 C
Solar/Wind Harmer
152.054
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
14.431
943121AE2-341 GEN
Solar/Wind Harmer
1.699
957471AF2-041 GEN
Solar/Wind Harmer
3.257
274848CAMPGROVE;RU
Solar/Wind Harmer
12.161
276785W4-005 GEN1
Solar/Wind Harmer
5.759
276849AB2-070 GEN2
Solar/Wind Harmer
4.942
970289AG2-191 GEN
Solar/Wind Harmer
1.259
970291AG2-192 GEN
Solar/Wind Harmer
0.687
270246TR4_N_V150
Solar/Wind Harmer
1.65
957201AF2-014 GEN
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.036
970707AG2-453 GEN
Solar/Wind Harmer
3.24
944531AF1-118 GEN
Solar/Wind Harmer
4
970833AG2-524 GEN
Solar/Wind Harmer
10.019
958481AF2-142 GEN
Solar/Wind Harmer
1.675
274862TOP CROP ;2U
Solar/Wind Harmer
13.061
274879MINONK ;1U
Solar/Wind Harmer
17.14
971675AH1-338 GEN
Solar/Wind Harmer
1.967
970781AG2-491 GEN
Solar/Wind Harmer
1.063
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.198
276903AD2-071 C
Solar/Wind Harmer
0.902
945391AF1-204 GEN
Solar/Wind Harmer
35.046
270247TR4_N_V136
Solar/Wind Harmer
1.65
274773LINCOLN ;4U
50/50
18.189
24307105BERRINSP G
50/50
0.044
270505AE1-170 C O1
Solar/Wind Harmer
1.788
962691AG1-118 GEN
Solar/Wind Harmer
3.328
971997AH1-543 GEN
Solar/Wind Harmer
1.728
276889AE2-281 GEN
Solar/Wind Harmer
4.233
957841AF2-078 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
1.981
24691005MDL-2G C
Solar/Wind Harmer
8.288
965021AG1-366 GEN
Solar/Wind Harmer
4.223
276158O29GEN2
Solar/Wind Harmer
9.24
276708O09 GEN2
Solar/Wind Harmer
8.678
958861AF2-177 GEN
Solar/Wind Harmer
32.004
942221AE2-234 GEN
Solar/Wind Harmer
0.347
945371AF1-202 GEN
Solar/Wind Harmer
15.326
971993AH1-541 GEN
Solar/Wind Harmer
0.892
276621W2-048 GEN
Solar/Wind Harmer
13.685
270032AE2-172
Solar/Wind Harmer
7.448
942481AE2-261 GEN
Solar/Wind Harmer
2.738
970825AG2-519 GEN
Solar/Wind Harmer
3.685
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.71
270543AE2-219 C
Solar/Wind Harmer
0.731
247607V1-011 GEN
Solar/Wind Harmer
5.22
270435AC2-044 GEN
Solar/Wind Harmer
0.132
270005AE1-210 C O1
Solar/Wind Harmer
13.746
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.269
246936BC-WTG1
Solar/Wind Harmer
5.99
246937BC-WTG2
Solar/Wind Harmer
5.99
270491AE1-102 GEN2
Solar/Wind Harmer
0.086
24344105CKG2
50/50
17.806
270101X2-052 CT2
50/50
3.082
965791AG1-447 GEN
Solar/Wind Harmer
13.273
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
8.57
270180AB1-006 GEN1
Solar/Wind Harmer
14.919
24791305MDL-5G
Solar/Wind Harmer
5.525
276741O09 GEN1
Solar/Wind Harmer
8.678
944541AF1-119 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
16.196
944221AF1-090 GEN
Solar/Wind Harmer
27.525
270191TR4_S_V150
Solar/Wind Harmer
4.97
274776LINCOLN ;7U
50/50
18.189
970373AG2-245 GEN
Solar/Wind Harmer
2.436
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
20.665
959081AF2-199 GEN
Solar/Wind Harmer
1.086
276872AE1-163_GEN1
Solar/Wind Harmer
14.816
274851PROVIDENC;RU
Solar/Wind Harmer
6.052
24386205FR-12G C
Solar/Wind Harmer
8.356
963741AG1-226 GEN
Solar/Wind Harmer
4.37
276686W4-005 GEN3
Solar/Wind Harmer
5.759
276764AC1-053 GEN2
Solar/Wind Harmer
7.485
276911AD2-131_GEN
Solar/Wind Harmer
0.454
270004AE1-209 GEN
Solar/Wind Harmer
13.746
270201AC2-176 GEN
Solar/Wind Harmer
8.576
24379505HDWTR1G C
Solar/Wind Harmer
12.487
970885AG2-551 GEN
Solar/Wind Harmer
2.924
972207SS24-0001
Solar/Wind Harmer
3.543
972181SS23-001
Solar/Wind Harmer
1.163
270055AF2-134 C O1
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
13.082
959091AF2-200 GEN
Solar/Wind Harmer
2.171
274849CRESCENT ;1U
Solar/Wind Harmer
4.453
965651AG1-433 GEN
Solar/Wind Harmer
16.356
970289AG2-191 GEN
Solar/Wind Harmer
0.181
957381AF2-032 GEN
Solar/Wind Harmer
0.184
276916AD2-100_GEN
Solar/Wind Harmer
1.907
946031AF1-268 GEN
Solar/Wind Harmer
0.709
965421AG1-410 GEN
Solar/Wind Harmer
2.099
270349AD2-093_GEN
Solar/Wind Helper
0.718
970521AG2-332 GEN
50/50
23.582
276806AD2-047 C O1
Solar/Wind Harmer
35.467
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.171
274877BISHOP HL;1U
Solar/Wind Harmer
8.133
276848AB2-070 GEN3
Solar/Wind Harmer
4.942
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.718
270102X2-052 ST
50/50
3.334
970901AG2-562 GEN
50/50
12.636
24344005CKG1
50/50
14.55
274777LINCOLN ;8U
50/50
18.189
961051AF2-396 GEN
Solar/Wind Harmer
2.362
961051AF2-396 GEN
Solar/Wind Harmer
18.894
972231SS25-0005
Solar/Wind Harmer
1.861
971411AH1-196 GEN
Solar/Wind Harmer
1.64
274855GSG-6 ;RU
Solar/Wind Harmer
9.332
276876AE1-163_GEN2
Solar/Wind Harmer
14.816
276782AC1-033 GEN
Solar/Wind Harmer
8.199
24386405FR-21G C
Solar/Wind Harmer
8.004
276763AC1-053 GEN1
Solar/Wind Harmer
7.485
270599AE1-208 GEN
Solar/Wind Harmer
0.758
971029AG2-637 GEN
Solar/Wind Harmer
1.014
24643105BUCHANAN
50/50
0.026
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
14.191
970031AG2-029 GEN
Solar/Wind Harmer
2.853
970833AG2-524 GEN
Solar/Wind Harmer
1.252
962781AG1-127 GEN
Solar/Wind Harmer
1.052
276868AE1-113 GEN
Solar/Wind Harmer
25.71
971171AH1-044 GEN
Solar/Wind Harmer
2.171
24697605MDL-3G C
Solar/Wind Harmer
8.288
270181AB1-006 GEN2
Solar/Wind Harmer
1.658
960971AF2-388 GEN
Solar/Wind Harmer
32.712
24385905FR-11G C
Solar/Wind Harmer
15.735
946321AF1-296 GEN
Solar/Wind Harmer
30.393
274853TWINGROVE;U1
Solar/Wind Harmer
15.76
959611AF2-252 GEN
Solar/Wind Harmer
4.082
960611AF2-352 GEN
Solar/Wind Harmer
4.082
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.322
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.731
276805AD2-038 GEN
Solar/Wind Harmer
12.914
971605AH1-302 GEN
Solar/Wind Harmer
16.544
970569AG2-363 GEN
Solar/Wind Harmer
3.218
276157O29GEN1
Solar/Wind Harmer
9.24
276645AC1-214 GEN1
Solar/Wind Harmer
3.247
939741AE1-205 GEN
Solar/Wind Harmer
2.076
942111AE2-223 GEN
Solar/Wind Harmer
24.294
970241AG2-163 GEN
Solar/Wind Harmer
2.428
276174W4-005 GEN2
Solar/Wind Harmer
5.759
276668AB2-070 GEN1
Solar/Wind Harmer
4.942
276838X2-022 GEN2
Solar/Wind Harmer
0.51
970825AG2-519 GEN
Solar/Wind Harmer
0.575
270007AE1-245 C
Solar/Wind Harmer
7.32
246938BC-WTG3
Solar/Wind Harmer
6.094
CBM West 1LTFEXP_CBM-W1->PJM
CBM
219.037
LGEELTFEXP_LGEE->PJM
CLTF
5.55
TVALTFEXP_TVA->PJM
CLTF
5.231
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.752
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.913
WECLTFEXP_WEC->PJM
CLTF
7.082
MECLTFEXP_MEC->PJM
CLTF
25.731
AG2-052LTFEXP_AG2-052->PJM
LTF
0.437
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.553
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.271
LAGNLTFEXP_LAGN->PJM
CLTF
13.735
AH1-155LTFEXP_AH1-155->PJM
LTF
0.655
NYPJM->LTFIMP_NY
CLTF
3.476
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.564
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.66 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2300.12
MW Contribution:
0.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965651AG1-433 GEN
Solar/Wind Harmer
8.19
972181SS23-001
Solar/Wind Harmer
0.439
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.299
970289AG2-191 GEN
Solar/Wind Harmer
0.08
274847GR RIDGE ;BU
Solar/Wind Harmer
4.836
946031AF1-268 GEN
Solar/Wind Harmer
0.346
959091AF2-200 GEN
Solar/Wind Harmer
0.804
274849CRESCENT ;1U
Solar/Wind Harmer
1.651
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.704
270227U2-072_GEN3
Solar/Wind Helper
1.995
270228U2-072_GEN4
Solar/Wind Helper
1.995
270231U2-072_GEN5
Solar/Wind Helper
1.995
270349AD2-093_GEN
Solar/Wind Helper
0.454
24727205RPMNG3
50/50
68.356
24639705ELKHART HY
50/50
0.148
963791AG1-232 GEN
Solar/Wind Harmer
0.988
247521TR3_G114
Solar/Wind Harmer
4.555
24695305TIMB G C
Solar/Wind Harmer
3.924
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.418
276694AA1-018 GEN2
Solar/Wind Harmer
4.411
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.096
971343AH1-151 GEN
Solar/Wind Harmer
0.804
970169AG2-114 GEN
Solar/Wind Harmer
0.397
959341AF2-225 GEN
Solar/Wind Harmer
0.575
971087AG2-675 GEN
Solar/Wind Harmer
2.412
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729205KEY G1
50/50
6.727
270201AC2-176 GEN
Solar/Wind Harmer
4.618
970373AG2-245 GEN
Solar/Wind Harmer
0.924
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.493
274872LEEDK;1U
Solar/Wind Harmer
7.643
276872AE1-163_GEN1
Solar/Wind Harmer
5.502
959081AF2-199 GEN
Solar/Wind Harmer
0.402
274851PROVIDENC;RU
Solar/Wind Harmer
2.244
24386205FR-12G C
Solar/Wind Harmer
3.154
24379505HDWTR1G C
Solar/Wind Harmer
5.718
970885AG2-551 GEN
Solar/Wind Harmer
1.46
963741AG1-226 GEN
Solar/Wind Harmer
1.64
276686W4-005 GEN3
Solar/Wind Harmer
2.126
276764AC1-053 GEN2
Solar/Wind Harmer
2.764
276911AD2-131_GEN
Solar/Wind Harmer
0.168
270191TR4_S_V150
Solar/Wind Harmer
3.471
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.032
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.18
270180AB1-006 GEN1
Solar/Wind Harmer
5.658
24791305MDL-5G
Solar/Wind Harmer
2.096
276741O09 GEN1
Solar/Wind Harmer
3.218
276726Z2-087_GEN
Solar/Wind Harmer
5.982
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.152
944531AF1-118 GEN
Solar/Wind Harmer
2.052
970707AG2-453 GEN
Solar/Wind Harmer
1.192
970833AG2-524 GEN
Solar/Wind Harmer
3.705
958481AF2-142 GEN
Solar/Wind Harmer
0.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.856
274879MINONK ;1U
Solar/Wind Harmer
6.36
971675AH1-338 GEN
Solar/Wind Harmer
0.728
970781AG2-491 GEN
Solar/Wind Harmer
0.403
276903AD2-071 C
Solar/Wind Harmer
0.399
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.811
945391AF1-204 GEN
Solar/Wind Harmer
13.018
270391AF1-285 GEN3
Solar/Wind Helper
0.285
241847AF2-150_GEN
Solar/Wind Helper
0.265
961051AF2-396 GEN
Solar/Wind Harmer
0.957
961051AF2-396 GEN
Solar/Wind Harmer
7.653
270599AE1-208 GEN
Solar/Wind Harmer
0.377
972231SS25-0005
Solar/Wind Harmer
0.703
971411AH1-196 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
3.454
276876AE1-163_GEN2
Solar/Wind Harmer
5.502
24386405FR-21G C
Solar/Wind Harmer
3.021
276782AC1-033 GEN
Solar/Wind Harmer
3.04
276763AC1-053 GEN1
Solar/Wind Harmer
2.764
971029AG2-637 GEN
Solar/Wind Harmer
0.481
270224U2-072_GEN2
Solar/Wind Helper
1.995
942871AE2-306 GEN
Solar/Wind Helper
0.214
945641AF1-229 GEN
Solar/Wind Helper
0.454
270541AE2-072 C
Solar/Wind Helper
0.459
944221AF1-090 GEN
Solar/Wind Harmer
10.146
966831AG1-554 GEN
Solar/Wind Helper
0.281
965011AG1-365 GEN
Solar/Wind Harmer
1.139
945111AF1-176 GEN
Solar/Wind Harmer
0.876
945111AF1-176 GEN
Solar/Wind Harmer
4.774
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.668
970073AG2-061 GEN
Solar/Wind Harmer
1.641
274850MENDOTA H;RU
Solar/Wind Harmer
2.401
276863AD2-134 GEN
Solar/Wind Harmer
1.67
276861AD2-134 GEN
Solar/Wind Harmer
1.67
970571AG2-364 GEN
Solar/Wind Harmer
0.796
274856ECOGROVE ;U1
Solar/Wind Harmer
3.104
971681AH1-341 GEN
Solar/Wind Harmer
0.593
938861AE1-114 GEN
Solar/Wind Harmer
9.255
274858EASY ROAD;U2
Solar/Wind Harmer
3.688
270240V3-007_GEN2
Solar/Wind Harmer
4.477
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.353
943021AE2-325 GEN
Solar/Wind Harmer
2.95
964611AG1-324 GEN
Solar/Wind Harmer
0.402
276843GEN-1.7
Solar/Wind Harmer
0.568
958011AF2-095 GEN
Solar/Wind Harmer
0.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.447
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.615
24697905MDL-4G C
Solar/Wind Harmer
2.096
970819AG2-516 GEN
Solar/Wind Harmer
0.478
276646AC1-214 GEN2
Solar/Wind Harmer
1.204
274878BISHOP HL;2U
Solar/Wind Harmer
3.016
274854TWINGROVE;U2
Solar/Wind Harmer
5.82
965091AG1-374 GEN
Solar/Wind Harmer
1.13
965931AG1-462 GEN
Solar/Wind Harmer
0.961
24727105RPMNG2
50/50
68.356
270246TR4_N_V150
Solar/Wind Harmer
1.152
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.556
970291AG2-192 GEN
Solar/Wind Harmer
0.303
274871GR RIDGE ;2U
Solar/Wind Harmer
5.335
943121AE2-341 GEN
Solar/Wind Harmer
0.627
957471AF2-041 GEN
Solar/Wind Harmer
1.206
274848CAMPGROVE;RU
Solar/Wind Harmer
4.509
276785W4-005 GEN1
Solar/Wind Harmer
2.126
276849AB2-070 GEN2
Solar/Wind Harmer
1.825
957201AF2-014 GEN
Solar/Wind Helper
3.942
270284AF1-227 GEN1
Solar/Wind Helper
0.948
270428AC2-015 C
Solar/Wind Helper
0.374
253383AE2-342_GEN
Solar/Wind Helper
0.103
970583AG2-370 GEN
50/50
2.758
965051AG1-369 GEN
Solar/Wind Harmer
0.293
970349AG2-230 GEN
Solar/Wind Harmer
0.721
971347AH1-153 GEN
Solar/Wind Harmer
0.24
961761AG1-017 GEN
Solar/Wind Harmer
0.449
960591AF2-350 GEN
Solar/Wind Harmer
0.428
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
16.272
247536S-71 GEN
Solar/Wind Harmer
3.798
926823AC1-168 GEN
Solar/Wind Harmer
4.874
274857EASY ROAD;U1
Solar/Wind Harmer
3.688
24725505WLD G2 C
Solar/Wind Harmer
3.052
276656WTG2_EQ
Solar/Wind Harmer
0.874
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.587
270462AD2-086
Solar/Wind Helper
1.788
270317AD1-130_GEN
Solar/Wind Helper
1.166
270287AF1-227 GEN3
Solar/Wind Helper
0.35
970031AG2-029 GEN
Solar/Wind Harmer
1.74
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.381
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.278
970833AG2-524 GEN
Solar/Wind Harmer
0.463
962781AG1-127 GEN
Solar/Wind Harmer
0.389
276868AE1-113 GEN
Solar/Wind Harmer
9.54
24697605MDL-3G C
Solar/Wind Harmer
3.143
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.804
24385905FR-11G C
Solar/Wind Harmer
5.939
946321AF1-296 GEN
Solar/Wind Harmer
11.289
274853TWINGROVE;U1
Solar/Wind Harmer
5.82
959611AF2-252 GEN
Solar/Wind Harmer
1.507
960611AF2-352 GEN
Solar/Wind Harmer
1.507
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.365
970193AG2-126 GEN
Solar/Wind Harmer
0.491
958581AF2-149 GEN
Solar/Wind Helper
0.222
24727005RPMNG1
50/50
68.356
247620Y3-023
50/50
0.46
959331AF2-224 GEN
Solar/Wind Harmer
1.139
965041AG1-368 GEN
Solar/Wind Harmer
0.69
270031AE2-169
Solar/Wind Harmer
0.377
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.661
274861TOP CROP ;1U
Solar/Wind Harmer
4.856
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.349
971067AG2-660 GEN
Solar/Wind Harmer
1.608
24699105WLD G1 C
Solar/Wind Harmer
3.052
276655WTG1_EQ
Solar/Wind Harmer
6.603
963841AG1-237 GEN
Solar/Wind Harmer
11.714
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.285
247522W1-056 GEN
Solar/Wind Helper
1.919
270286AF1-227 GEN2
Solar/Wind Helper
0.35
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.296
960861AF2-377 GEN
50/50
2.345
24729305KEY G2
50/50
6.841
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.937
957891AF2-083 GEN
Solar/Wind Harmer
0.723
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.683
274888KELLY CRK;1U
Solar/Wind Harmer
5.846
276893AG1-478 C
Solar/Wind Harmer
0.338
270005AE1-210 C O1
Solar/Wind Harmer
6.493
276602WESTBROOK C
Solar/Wind Harmer
1.703
274863CRW1-WTG
Solar/Wind Harmer
4.717
274864CRW2-WTG
Solar/Wind Harmer
4.717
276603SUBLETTE C
Solar/Wind Harmer
0.798
24387305FR-4G C
Solar/Wind Harmer
4.532
24386605FR-22G C
Solar/Wind Harmer
3.021
24387005FR-3G C
Solar/Wind Harmer
2.991
274880W4-005 GEN4
Solar/Wind Harmer
2.126
246936BC-WTG1
Solar/Wind Helper
17.073
246937BC-WTG2
Solar/Wind Helper
17.073
960841AF2-375 GEN
Solar/Wind Helper
0.563
960851AF2-376 GEN
50/50
2.033
965021AG1-366 GEN
Solar/Wind Harmer
4.557
942221AE2-234 GEN
Solar/Wind Harmer
0.204
958861AF2-177 GEN
Solar/Wind Harmer
15.92
945371AF1-202 GEN
Solar/Wind Harmer
7.521
270505AE1-170 C O1
Solar/Wind Harmer
0.718
270032AE2-172
Solar/Wind Harmer
3.34
970825AG2-519 GEN
Solar/Wind Harmer
1.758
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.231
971997AH1-543 GEN
Solar/Wind Harmer
0.639
276889AE2-281 GEN
Solar/Wind Harmer
1.572
24691005MDL-2G C
Solar/Wind Harmer
3.143
971549AH1-272 GEN
Solar/Wind Harmer
0.722
276158O29GEN2
Solar/Wind Harmer
3.427
276708O09 GEN2
Solar/Wind Harmer
3.218
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.241
270543AE2-219 C
Solar/Wind Harmer
0.365
971993AH1-541 GEN
Solar/Wind Harmer
0.329
276621W2-048 GEN
Solar/Wind Harmer
5.054
942481AE2-261 GEN
Solar/Wind Harmer
1.011
270485AE1-090_GEN
Solar/Wind Helper
0.155
24729405KEY G3
50/50
6.841
24729505KEY G4
50/50
6.727
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.436
970941AG2-585 GEN
Solar/Wind Harmer
0.236
276897AD1-100 C
Solar/Wind Harmer
56.232
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.995
270499AE1-146 GEN
Solar/Wind Helper
0.544
971605AH1-302 GEN
Solar/Wind Harmer
6.283
970825AG2-519 GEN
Solar/Wind Harmer
0.274
276805AD2-038 GEN
Solar/Wind Harmer
4.799
970569AG2-363 GEN
Solar/Wind Harmer
1.195
276157O29GEN1
Solar/Wind Harmer
3.427
276645AC1-214 GEN1
Solar/Wind Harmer
1.204
939741AE1-205 GEN
Solar/Wind Harmer
0.767
942111AE2-223 GEN
Solar/Wind Harmer
8.972
970241AG2-163 GEN
Solar/Wind Harmer
0.911
276174W4-005 GEN2
Solar/Wind Harmer
2.126
276668AB2-070 GEN1
Solar/Wind Harmer
1.825
276838X2-022 GEN2
Solar/Wind Harmer
0.188
246938BC-WTG3
Solar/Wind Helper
17.366
970521AG2-332 GEN
50/50
10.74
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.192
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.016
276848AB2-070 GEN3
Solar/Wind Harmer
1.825
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.166
270471AD2-092_GEN
Solar/Wind Helper
0.454
276820AF1-078_GEN
Solar/Wind Helper
0.159
990792J1392
External Queue
0.3027859032154083
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.032
WECLTFEXP_WEC->PJM
CLTF
2.627
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.873
TVALTFEXP_TVA->PJM
CLTF
2.36
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.443
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.204
NYPJM->LTFIMP_NY
CLTF
1.303
MECLTFEXP_MEC->PJM
CLTF
9.641
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.255
LGEELTFEXP_LGEE->PJM
CLTF
1.795
LAGNLTFEXP_LAGN->PJM
CLTF
5.817
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.06 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2242.58
MW Contribution:
0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.018
270143AC1-141 CT2_
50/50
2.018
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
24643105BUCHANAN
50/50
0.01
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.787
24642205MAYFLWER
50/50
0.618
962601AG1-109 GEN
50/50
2.385
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
944961AF1-161 GEN
50/50
2.385
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
990792J1392
External Queue
0.30737584829330444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.53 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2230.82
MW Contribution:
0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
990792J1392
External Queue
0.30737584829330444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.04 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2219.82
MW Contribution:
0.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
67.807
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.971
247521TR3_G114
Solar/Wind Harmer
4.44
24695305TIMB G C
Solar/Wind Harmer
3.811
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.053
943591AF1-030 GEN
Solar/Wind Harmer
0.407
276694AA1-018 GEN2
Solar/Wind Harmer
4.296
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.038
971343AH1-151 GEN
Solar/Wind Harmer
0.782
970169AG2-114 GEN
Solar/Wind Harmer
0.386
959341AF2-225 GEN
Solar/Wind Harmer
0.559
971087AG2-675 GEN
Solar/Wind Harmer
2.343
270445AC2-157 GEN2
Solar/Wind Harmer
0
24727105RPMNG2
50/50
67.807
270246TR4_N_V150
Solar/Wind Harmer
1.123
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.295
274871GR RIDGE ;2U
Solar/Wind Harmer
5.196
943121AE2-341 GEN
Solar/Wind Harmer
0.611
957471AF2-041 GEN
Solar/Wind Harmer
1.174
274848CAMPGROVE;RU
Solar/Wind Harmer
4.383
276785W4-005 GEN1
Solar/Wind Harmer
2.063
276849AB2-070 GEN2
Solar/Wind Harmer
1.771
957201AF2-014 GEN
Solar/Wind Helper
3.968
270284AF1-227 GEN1
Solar/Wind Helper
1.035
270428AC2-015 C
Solar/Wind Helper
0.376
253383AE2-342_GEN
Solar/Wind Helper
0.105
944531AF1-118 GEN
Solar/Wind Harmer
2.012
270247TR4_N_V136
Solar/Wind Harmer
1.123
970707AG2-453 GEN
Solar/Wind Harmer
1.161
970833AG2-524 GEN
Solar/Wind Harmer
3.609
958481AF2-142 GEN
Solar/Wind Harmer
0.607
274862TOP CROP ;2U
Solar/Wind Harmer
4.729
274879MINONK ;1U
Solar/Wind Harmer
6.19
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
276903AD2-071 C
Solar/Wind Harmer
0.388
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.786
945391AF1-204 GEN
Solar/Wind Harmer
12.593
270391AF1-285 GEN3
Solar/Wind Helper
0.3
241847AF2-150_GEN
Solar/Wind Helper
0.265
970583AG2-370 GEN
50/50
2.702
965051AG1-369 GEN
Solar/Wind Harmer
0.285
970349AG2-230 GEN
Solar/Wind Harmer
0.704
971347AH1-153 GEN
Solar/Wind Harmer
0.235
961761AG1-017 GEN
Solar/Wind Harmer
0.438
960591AF2-350 GEN
Solar/Wind Harmer
0.417
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
15.839
247536S-71 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
4.742
274857EASY ROAD;U1
Solar/Wind Harmer
3.587
24725505WLD G2 C
Solar/Wind Harmer
2.968
276656WTG2_EQ
Solar/Wind Harmer
0.85
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.539
270462AD2-086
Solar/Wind Helper
1.865
270317AD1-130_GEN
Solar/Wind Helper
1.216
270287AF1-227 GEN3
Solar/Wind Helper
0.382
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.856
945111AF1-176 GEN
Solar/Wind Harmer
4.667
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.651
970073AG2-061 GEN
Solar/Wind Harmer
1.597
274850MENDOTA H;RU
Solar/Wind Harmer
2.337
276863AD2-134 GEN
Solar/Wind Harmer
1.625
276861AD2-134 GEN
Solar/Wind Harmer
1.625
970571AG2-364 GEN
Solar/Wind Harmer
0.775
274856ECOGROVE ;U1
Solar/Wind Harmer
3.02
971681AH1-341 GEN
Solar/Wind Harmer
0.577
938861AE1-114 GEN
Solar/Wind Harmer
9.003
274858EASY ROAD;U2
Solar/Wind Harmer
3.587
270240V3-007_GEN2
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.369
965021AG1-366 GEN
Solar/Wind Harmer
4.503
942221AE2-234 GEN
Solar/Wind Harmer
0.2
958861AF2-177 GEN
Solar/Wind Harmer
15.573
945371AF1-202 GEN
Solar/Wind Harmer
7.349
270505AE1-170 C O1
Solar/Wind Harmer
0.702
270032AE2-172
Solar/Wind Harmer
3.253
970825AG2-519 GEN
Solar/Wind Harmer
1.712
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.198
971997AH1-543 GEN
Solar/Wind Harmer
0.622
276889AE2-281 GEN
Solar/Wind Harmer
1.53
24691005MDL-2G C
Solar/Wind Harmer
3.058
971549AH1-272 GEN
Solar/Wind Harmer
0.702
276158O29GEN2
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
3.129
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.205
270543AE2-219 C
Solar/Wind Harmer
0.354
971993AH1-541 GEN
Solar/Wind Harmer
0.319
276621W2-048 GEN
Solar/Wind Harmer
4.9
942481AE2-261 GEN
Solar/Wind Harmer
0.979
270485AE1-090_GEN
Solar/Wind Helper
0.162
960861AF2-377 GEN
50/50
2.286
24729305KEY G2
50/50
6.704
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.92
957891AF2-083 GEN
Solar/Wind Harmer
0.707
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.667
274888KELLY CRK;1U
Solar/Wind Harmer
5.697
276893AG1-478 C
Solar/Wind Harmer
0.33
270005AE1-210 C O1
Solar/Wind Harmer
6.326
276602WESTBROOK C
Solar/Wind Harmer
1.658
274863CRW1-WTG
Solar/Wind Harmer
4.59
274864CRW2-WTG
Solar/Wind Harmer
4.59
276603SUBLETTE C
Solar/Wind Harmer
0.776
24387305FR-4G C
Solar/Wind Harmer
4.404
24386605FR-22G C
Solar/Wind Harmer
2.936
943021AE2-325 GEN
Solar/Wind Harmer
2.881
964611AG1-324 GEN
Solar/Wind Harmer
0.393
276843GEN-1.7
Solar/Wind Harmer
0.553
958011AF2-095 GEN
Solar/Wind Harmer
0.601
276691AA1-018 GEN1
Solar/Wind Harmer
0.435
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
24697905MDL-4G C
Solar/Wind Harmer
2.038
970819AG2-516 GEN
Solar/Wind Harmer
0.465
276646AC1-214 GEN2
Solar/Wind Harmer
1.17
274878BISHOP HL;2U
Solar/Wind Harmer
2.932
270191TR4_S_V150
Solar/Wind Harmer
3.383
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.91
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.095
270180AB1-006 GEN1
Solar/Wind Harmer
5.504
24791305MDL-5G
Solar/Wind Harmer
2.038
276741O09 GEN1
Solar/Wind Harmer
3.129
276726Z2-087_GEN
Solar/Wind Harmer
5.813
944221AF1-090 GEN
Solar/Wind Harmer
9.816
966831AG1-554 GEN
Solar/Wind Helper
0.286
965931AG1-462 GEN
Solar/Wind Harmer
0.934
274854TWINGROVE;U2
Solar/Wind Harmer
5.654
965091AG1-374 GEN
Solar/Wind Harmer
1.098
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
2.097
270499AE1-146 GEN
Solar/Wind Helper
0.556
24729205KEY G1
50/50
6.593
270201AC2-176 GEN
Solar/Wind Harmer
4.506
965651AG1-433 GEN
Solar/Wind Harmer
8.016
972181SS23-001
Solar/Wind Harmer
0.428
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.266
970289AG2-191 GEN
Solar/Wind Harmer
0.078
274847GR RIDGE ;BU
Solar/Wind Harmer
4.711
946031AF1-268 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
0.782
274849CRESCENT ;1U
Solar/Wind Harmer
1.605
957381AF2-032 GEN
Solar/Wind Harmer
0.066
276916AD2-100_GEN
Solar/Wind Harmer
0.681
270227U2-072_GEN3
Solar/Wind Helper
2.097
270228U2-072_GEN4
Solar/Wind Helper
2.097
270231U2-072_GEN5
Solar/Wind Helper
2.097
270349AD2-093_GEN
Solar/Wind Helper
0.517
970521AG2-332 GEN
50/50
10.514
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
12.855
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.782
274877BISHOP HL;1U
Solar/Wind Harmer
2.932
276848AB2-070 GEN3
Solar/Wind Harmer
1.771
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.216
270471AD2-092_GEN
Solar/Wind Helper
0.517
276820AF1-078_GEN
Solar/Wind Helper
0.166
961051AF2-396 GEN
Solar/Wind Harmer
0.935
961051AF2-396 GEN
Solar/Wind Harmer
7.477
270599AE1-208 GEN
Solar/Wind Harmer
0.368
972231SS25-0005
Solar/Wind Harmer
0.685
971411AH1-196 GEN
Solar/Wind Harmer
0.591
274855GSG-6 ;RU
Solar/Wind Harmer
3.361
276876AE1-163_GEN2
Solar/Wind Harmer
5.354
24386405FR-21G C
Solar/Wind Harmer
2.936
276782AC1-033 GEN
Solar/Wind Harmer
2.956
276763AC1-053 GEN1
Solar/Wind Harmer
2.681
971029AG2-637 GEN
Solar/Wind Harmer
0.465
270224U2-072_GEN2
Solar/Wind Helper
2.097
942871AE2-306 GEN
Solar/Wind Helper
0.225
945641AF1-229 GEN
Solar/Wind Helper
0.46
270541AE2-072 C
Solar/Wind Helper
0.478
970373AG2-245 GEN
Solar/Wind Harmer
0.901
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.326
274872LEEDK;1U
Solar/Wind Harmer
7.44
276872AE1-163_GEN1
Solar/Wind Harmer
5.354
959081AF2-199 GEN
Solar/Wind Harmer
0.391
274851PROVIDENC;RU
Solar/Wind Harmer
2.181
24386205FR-12G C
Solar/Wind Harmer
3.065
24379505HDWTR1G C
Solar/Wind Harmer
5.555
970885AG2-551 GEN
Solar/Wind Harmer
1.417
963741AG1-226 GEN
Solar/Wind Harmer
1.592
276686W4-005 GEN3
Solar/Wind Harmer
2.063
276764AC1-053 GEN2
Solar/Wind Harmer
2.681
276911AD2-131_GEN
Solar/Wind Harmer
0.162
24727005RPMNG1
50/50
67.807
247620Y3-023
50/50
0.45
959331AF2-224 GEN
Solar/Wind Harmer
1.126
965041AG1-368 GEN
Solar/Wind Harmer
0.675
270031AE2-169
Solar/Wind Harmer
0.368
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.489
274861TOP CROP ;1U
Solar/Wind Harmer
4.729
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.176
971067AG2-660 GEN
Solar/Wind Harmer
1.565
24699105WLD G1 C
Solar/Wind Harmer
2.968
276655WTG1_EQ
Solar/Wind Harmer
6.417
963841AG1-237 GEN
Solar/Wind Harmer
11.375
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.3
270286AF1-227 GEN2
Solar/Wind Helper
0.382
247522W1-056 GEN
Solar/Wind Helper
1.958
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.299
970031AG2-029 GEN
Solar/Wind Harmer
1.71
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.032
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.144
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
276868AE1-113 GEN
Solar/Wind Harmer
9.286
24697605MDL-3G C
Solar/Wind Harmer
3.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.782
24385905FR-11G C
Solar/Wind Harmer
5.772
946321AF1-296 GEN
Solar/Wind Harmer
10.97
274853TWINGROVE;U1
Solar/Wind Harmer
5.654
959611AF2-252 GEN
Solar/Wind Harmer
1.464
960611AF2-352 GEN
Solar/Wind Harmer
1.464
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.354
970193AG2-126 GEN
Solar/Wind Harmer
0.475
958581AF2-149 GEN
Solar/Wind Helper
0.216
24387005FR-3G C
Solar/Wind Harmer
2.906
274880W4-005 GEN4
Solar/Wind Harmer
2.063
246936BC-WTG1
Solar/Wind Helper
17.184
246937BC-WTG2
Solar/Wind Helper
17.184
960841AF2-375 GEN
Solar/Wind Helper
0.576
24729405KEY G3
50/50
6.704
24729505KEY G4
50/50
6.593
270043AE2-236 GEN
Solar/Wind Harmer
0.363
971771AH1-392 GEN
Solar/Wind Harmer
0.426
970941AG2-585 GEN
Solar/Wind Harmer
0.23
276897AD1-100 C
Solar/Wind Harmer
54.783
971605AH1-302 GEN
Solar/Wind Harmer
6.118
970825AG2-519 GEN
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
4.671
970569AG2-363 GEN
Solar/Wind Harmer
1.162
276157O29GEN1
Solar/Wind Harmer
3.332
276645AC1-214 GEN1
Solar/Wind Harmer
1.17
939741AE1-205 GEN
Solar/Wind Harmer
0.745
942111AE2-223 GEN
Solar/Wind Harmer
8.72
970241AG2-163 GEN
Solar/Wind Harmer
0.884
276174W4-005 GEN2
Solar/Wind Harmer
2.063
276668AB2-070 GEN1
Solar/Wind Harmer
1.771
276838X2-022 GEN2
Solar/Wind Harmer
0.183
246938BC-WTG3
Solar/Wind Helper
17.48
990792J1392
External Queue
0.3014104962348938
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
SIGELTFEXP_SIGE->PJM
CLTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.67
NYPJM->LTFIMP_NY
CLTF
1.235
TVALTFEXP_TVA->PJM
CLTF
2.193
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.955
LGEELTFEXP_LGEE->PJM
CLTF
1.68
MECLTFEXP_MEC->PJM
CLTF
9.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.406
WECLTFEXP_WEC->PJM
CLTF
2.556
LAGNLTFEXP_LAGN->PJM
CLTF
5.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.03 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2352.88
MW Contribution:
0.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
45.078
24727205RPMNG3
50/50
68.356
24639705ELKHART HY
50/50
0.148
963791AG1-232 GEN
Solar/Wind Harmer
0.988
247521TR3_G114
Solar/Wind Harmer
4.555
24695305TIMB G C
Solar/Wind Harmer
3.924
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.418
276694AA1-018 GEN2
Solar/Wind Harmer
4.411
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.096
971343AH1-151 GEN
Solar/Wind Harmer
0.804
970169AG2-114 GEN
Solar/Wind Harmer
0.397
959341AF2-225 GEN
Solar/Wind Harmer
0.575
971087AG2-675 GEN
Solar/Wind Harmer
2.412
270445AC2-157 GEN2
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
6.762
965651AG1-433 GEN
Solar/Wind Harmer
8.19
972181SS23-001
Solar/Wind Harmer
0.439
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.299
970289AG2-191 GEN
Solar/Wind Harmer
0.08
274847GR RIDGE ;BU
Solar/Wind Harmer
4.836
946031AF1-268 GEN
Solar/Wind Harmer
0.346
959091AF2-200 GEN
Solar/Wind Harmer
0.804
274849CRESCENT ;1U
Solar/Wind Harmer
1.651
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.704
270227U2-072_GEN3
Solar/Wind Helper
1.995
270228U2-072_GEN4
Solar/Wind Helper
1.995
270231U2-072_GEN5
Solar/Wind Helper
1.995
270349AD2-093_GEN
Solar/Wind Helper
0.454
24729205KEY G1
50/50
6.727
270201AC2-176 GEN
Solar/Wind Harmer
4.618
970373AG2-245 GEN
Solar/Wind Harmer
0.924
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.493
274872LEEDK;1U
Solar/Wind Harmer
7.643
276872AE1-163_GEN1
Solar/Wind Harmer
5.502
959081AF2-199 GEN
Solar/Wind Harmer
0.402
274851PROVIDENC;RU
Solar/Wind Harmer
2.244
24386205FR-12G C
Solar/Wind Harmer
3.154
24379505HDWTR1G C
Solar/Wind Harmer
5.718
970885AG2-551 GEN
Solar/Wind Harmer
1.46
963741AG1-226 GEN
Solar/Wind Harmer
1.64
276686W4-005 GEN3
Solar/Wind Harmer
2.126
276764AC1-053 GEN2
Solar/Wind Harmer
2.764
276911AD2-131_GEN
Solar/Wind Harmer
0.168
270191TR4_S_V150
Solar/Wind Harmer
3.471
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.032
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.18
270180AB1-006 GEN1
Solar/Wind Harmer
5.658
24791305MDL-5G
Solar/Wind Harmer
2.096
276741O09 GEN1
Solar/Wind Harmer
3.218
276726Z2-087_GEN
Solar/Wind Harmer
5.982
944221AF1-090 GEN
Solar/Wind Harmer
10.146
966831AG1-554 GEN
Solar/Wind Helper
0.281
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.152
944531AF1-118 GEN
Solar/Wind Harmer
2.052
970707AG2-453 GEN
Solar/Wind Harmer
1.192
970833AG2-524 GEN
Solar/Wind Harmer
3.705
958481AF2-142 GEN
Solar/Wind Harmer
0.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.856
274879MINONK ;1U
Solar/Wind Harmer
6.36
971675AH1-338 GEN
Solar/Wind Harmer
0.728
970781AG2-491 GEN
Solar/Wind Harmer
0.403
276903AD2-071 C
Solar/Wind Harmer
0.399
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.811
945391AF1-204 GEN
Solar/Wind Harmer
13.018
270391AF1-285 GEN3
Solar/Wind Helper
0.285
241847AF2-150_GEN
Solar/Wind Helper
0.265
961051AF2-396 GEN
Solar/Wind Harmer
0.957
961051AF2-396 GEN
Solar/Wind Harmer
7.653
270599AE1-208 GEN
Solar/Wind Harmer
0.377
972231SS25-0005
Solar/Wind Harmer
0.703
971411AH1-196 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
3.454
276876AE1-163_GEN2
Solar/Wind Harmer
5.502
24386405FR-21G C
Solar/Wind Harmer
3.021
276782AC1-033 GEN
Solar/Wind Harmer
3.04
276763AC1-053 GEN1
Solar/Wind Harmer
2.764
971029AG2-637 GEN
Solar/Wind Harmer
0.481
270224U2-072_GEN2
Solar/Wind Helper
1.995
942871AE2-306 GEN
Solar/Wind Helper
0.214
945641AF1-229 GEN
Solar/Wind Helper
0.454
270541AE2-072 C
Solar/Wind Helper
0.459
965011AG1-365 GEN
Solar/Wind Harmer
1.139
945111AF1-176 GEN
Solar/Wind Harmer
0.876
945111AF1-176 GEN
Solar/Wind Harmer
4.774
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.668
970073AG2-061 GEN
Solar/Wind Harmer
1.641
274850MENDOTA H;RU
Solar/Wind Harmer
2.401
276863AD2-134 GEN
Solar/Wind Harmer
1.67
276861AD2-134 GEN
Solar/Wind Harmer
1.67
970571AG2-364 GEN
Solar/Wind Harmer
0.796
274856ECOGROVE ;U1
Solar/Wind Harmer
3.104
971681AH1-341 GEN
Solar/Wind Harmer
0.593
938861AE1-114 GEN
Solar/Wind Harmer
9.255
274858EASY ROAD;U2
Solar/Wind Harmer
3.688
270240V3-007_GEN2
Solar/Wind Harmer
4.477
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.353
960861AF2-377 GEN
50/50
2.345
24729305KEY G2
50/50
6.841
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.937
957891AF2-083 GEN
Solar/Wind Harmer
0.723
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.683
274888KELLY CRK;1U
Solar/Wind Harmer
5.846
276893AG1-478 C
Solar/Wind Harmer
0.338
270005AE1-210 C O1
Solar/Wind Harmer
6.493
276602WESTBROOK C
Solar/Wind Harmer
1.703
274863CRW1-WTG
Solar/Wind Harmer
4.717
274864CRW2-WTG
Solar/Wind Harmer
4.717
276603SUBLETTE C
Solar/Wind Harmer
0.798
24387305FR-4G C
Solar/Wind Harmer
4.532
24386605FR-22G C
Solar/Wind Harmer
3.021
24387005FR-3G C
Solar/Wind Harmer
2.991
274880W4-005 GEN4
Solar/Wind Harmer
2.126
246936BC-WTG1
Solar/Wind Helper
17.073
246937BC-WTG2
Solar/Wind Helper
17.073
943021AE2-325 GEN
Solar/Wind Harmer
2.95
964611AG1-324 GEN
Solar/Wind Harmer
0.402
276843GEN-1.7
Solar/Wind Harmer
0.568
958011AF2-095 GEN
Solar/Wind Harmer
0.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.447
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.615
24697905MDL-4G C
Solar/Wind Harmer
2.096
970819AG2-516 GEN
Solar/Wind Harmer
0.478
276646AC1-214 GEN2
Solar/Wind Harmer
1.204
274878BISHOP HL;2U
Solar/Wind Harmer
3.016
274854TWINGROVE;U2
Solar/Wind Harmer
5.82
965091AG1-374 GEN
Solar/Wind Harmer
1.13
965931AG1-462 GEN
Solar/Wind Harmer
0.961
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.995
270499AE1-146 GEN
Solar/Wind Helper
0.544
24727105RPMNG2
50/50
68.356
270246TR4_N_V150
Solar/Wind Harmer
1.152
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.556
970291AG2-192 GEN
Solar/Wind Harmer
0.303
274871GR RIDGE ;2U
Solar/Wind Harmer
5.335
943121AE2-341 GEN
Solar/Wind Harmer
0.627
957471AF2-041 GEN
Solar/Wind Harmer
1.206
274848CAMPGROVE;RU
Solar/Wind Harmer
4.509
276785W4-005 GEN1
Solar/Wind Harmer
2.126
276849AB2-070 GEN2
Solar/Wind Harmer
1.825
957201AF2-014 GEN
Solar/Wind Helper
3.942
270284AF1-227 GEN1
Solar/Wind Helper
0.948
270428AC2-015 C
Solar/Wind Helper
0.374
253383AE2-342_GEN
Solar/Wind Helper
0.103
970583AG2-370 GEN
50/50
2.758
965051AG1-369 GEN
Solar/Wind Harmer
0.293
970349AG2-230 GEN
Solar/Wind Harmer
0.721
971347AH1-153 GEN
Solar/Wind Harmer
0.24
961761AG1-017 GEN
Solar/Wind Harmer
0.449
960591AF2-350 GEN
Solar/Wind Harmer
0.428
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
16.272
247536S-71 GEN
Solar/Wind Harmer
3.798
926823AC1-168 GEN
Solar/Wind Harmer
4.874
274857EASY ROAD;U1
Solar/Wind Harmer
3.688
24725505WLD G2 C
Solar/Wind Harmer
3.052
276656WTG2_EQ
Solar/Wind Harmer
0.874
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.587
270462AD2-086
Solar/Wind Helper
1.788
270317AD1-130_GEN
Solar/Wind Helper
1.166
270287AF1-227 GEN3
Solar/Wind Helper
0.35
970031AG2-029 GEN
Solar/Wind Harmer
1.74
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.381
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.278
970833AG2-524 GEN
Solar/Wind Harmer
0.463
962781AG1-127 GEN
Solar/Wind Harmer
0.389
276868AE1-113 GEN
Solar/Wind Harmer
9.54
24697605MDL-3G C
Solar/Wind Harmer
3.143
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.804
24385905FR-11G C
Solar/Wind Harmer
5.939
946321AF1-296 GEN
Solar/Wind Harmer
11.289
274853TWINGROVE;U1
Solar/Wind Harmer
5.82
959611AF2-252 GEN
Solar/Wind Harmer
1.507
960611AF2-352 GEN
Solar/Wind Harmer
1.507
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.365
970193AG2-126 GEN
Solar/Wind Harmer
0.491
958581AF2-149 GEN
Solar/Wind Helper
0.222
24727005RPMNG1
50/50
68.356
247620Y3-023
50/50
0.46
959331AF2-224 GEN
Solar/Wind Harmer
1.139
965041AG1-368 GEN
Solar/Wind Harmer
0.69
270031AE2-169
Solar/Wind Harmer
0.377
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.661
274861TOP CROP ;1U
Solar/Wind Harmer
4.856
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.349
971067AG2-660 GEN
Solar/Wind Harmer
1.608
24699105WLD G1 C
Solar/Wind Harmer
3.052
276655WTG1_EQ
Solar/Wind Harmer
6.603
963841AG1-237 GEN
Solar/Wind Harmer
11.714
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.285
247522W1-056 GEN
Solar/Wind Helper
1.919
270286AF1-227 GEN2
Solar/Wind Helper
0.35
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.296
24729405KEY G3
50/50
6.841
24729505KEY G4
50/50
6.727
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.436
970941AG2-585 GEN
Solar/Wind Harmer
0.236
276897AD1-100 C
Solar/Wind Harmer
56.232
971605AH1-302 GEN
Solar/Wind Harmer
6.283
970825AG2-519 GEN
Solar/Wind Harmer
0.274
276805AD2-038 GEN
Solar/Wind Harmer
4.799
970569AG2-363 GEN
Solar/Wind Harmer
1.195
276157O29GEN1
Solar/Wind Harmer
3.427
276645AC1-214 GEN1
Solar/Wind Harmer
1.204
939741AE1-205 GEN
Solar/Wind Harmer
0.767
960841AF2-375 GEN
Solar/Wind Helper
0.563
960851AF2-376 GEN
50/50
2.033
965021AG1-366 GEN
Solar/Wind Harmer
4.557
942221AE2-234 GEN
Solar/Wind Harmer
0.204
958861AF2-177 GEN
Solar/Wind Harmer
15.92
945371AF1-202 GEN
Solar/Wind Harmer
7.521
270505AE1-170 C O1
Solar/Wind Harmer
0.718
270032AE2-172
Solar/Wind Harmer
3.34
970825AG2-519 GEN
Solar/Wind Harmer
1.758
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.231
971997AH1-543 GEN
Solar/Wind Harmer
0.639
276889AE2-281 GEN
Solar/Wind Harmer
1.572
24691005MDL-2G C
Solar/Wind Harmer
3.143
971549AH1-272 GEN
Solar/Wind Harmer
0.722
276158O29GEN2
Solar/Wind Harmer
3.427
276708O09 GEN2
Solar/Wind Harmer
3.218
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.241
270543AE2-219 C
Solar/Wind Harmer
0.365
971993AH1-541 GEN
Solar/Wind Harmer
0.329
276621W2-048 GEN
Solar/Wind Harmer
5.054
942481AE2-261 GEN
Solar/Wind Harmer
1.011
270485AE1-090_GEN
Solar/Wind Helper
0.155
942111AE2-223 GEN
Solar/Wind Harmer
8.972
970241AG2-163 GEN
Solar/Wind Harmer
0.911
276174W4-005 GEN2
Solar/Wind Harmer
2.126
276668AB2-070 GEN1
Solar/Wind Harmer
1.825
276838X2-022 GEN2
Solar/Wind Harmer
0.188
246938BC-WTG3
Solar/Wind Helper
17.366
970521AG2-332 GEN
50/50
10.74
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.192
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.016
276848AB2-070 GEN3
Solar/Wind Harmer
1.825
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.166
270471AD2-092_GEN
Solar/Wind Helper
0.454
276820AF1-078_GEN
Solar/Wind Helper
0.159
990792J1392
External Queue
0.3027859032154083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.873
TVALTFEXP_TVA->PJM
CLTF
2.36
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.443
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.204
NYPJM->LTFIMP_NY
CLTF
1.303
MECLTFEXP_MEC->PJM
CLTF
9.641
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.255
LGEELTFEXP_LGEE->PJM
CLTF
1.795
LAGNLTFEXP_LAGN->PJM
CLTF
5.817
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.032
WECLTFEXP_WEC->PJM
CLTF
2.627
SIGELTFEXP_SIGE->PJM
CLTF
0.199

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.21 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2290.26
MW Contribution:
0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
45.403
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.018
270143AC1-141 CT2_
50/50
2.018
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.787
24642205MAYFLWER
50/50
0.618
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
24643105BUCHANAN
50/50
0.01
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
965421AG1-410 GEN
Solar/Wind Harmer
6.81
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
990792J1392
External Queue
0.30737584829330444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.89 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2283.06
MW Contribution:
0.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
45.403
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
961051AF2-396 GEN
Solar/Wind Harmer
0.969
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
965421AG1-410 GEN
Solar/Wind Harmer
6.81
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
990792J1392
External Queue
0.30737584829330444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.36 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2271.47
MW Contribution:
0.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
44.74
24727205RPMNG3
50/50
67.807
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.971
247521TR3_G114
Solar/Wind Harmer
4.44
24695305TIMB G C
Solar/Wind Harmer
3.811
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.053
943591AF1-030 GEN
Solar/Wind Harmer
0.407
276694AA1-018 GEN2
Solar/Wind Harmer
4.296
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.038
971343AH1-151 GEN
Solar/Wind Harmer
0.782
970169AG2-114 GEN
Solar/Wind Harmer
0.386
959341AF2-225 GEN
Solar/Wind Harmer
0.559
971087AG2-675 GEN
Solar/Wind Harmer
2.343
270445AC2-157 GEN2
Solar/Wind Harmer
0
270191TR4_S_V150
Solar/Wind Harmer
3.383
944541AF1-119 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.856
945111AF1-176 GEN
Solar/Wind Harmer
4.667
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.651
970073AG2-061 GEN
Solar/Wind Harmer
1.597
274850MENDOTA H;RU
Solar/Wind Harmer
2.337
276863AD2-134 GEN
Solar/Wind Harmer
1.625
276861AD2-134 GEN
Solar/Wind Harmer
1.625
970571AG2-364 GEN
Solar/Wind Harmer
0.775
274856ECOGROVE ;U1
Solar/Wind Harmer
3.02
971681AH1-341 GEN
Solar/Wind Harmer
0.577
938861AE1-114 GEN
Solar/Wind Harmer
9.003
274858EASY ROAD;U2
Solar/Wind Harmer
3.587
270240V3-007_GEN2
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.369
24727105RPMNG2
50/50
67.807
270246TR4_N_V150
Solar/Wind Harmer
1.123
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.295
274871GR RIDGE ;2U
Solar/Wind Harmer
5.196
943121AE2-341 GEN
Solar/Wind Harmer
0.611
957471AF2-041 GEN
Solar/Wind Harmer
1.174
970583AG2-370 GEN
50/50
2.702
965051AG1-369 GEN
Solar/Wind Harmer
0.285
970349AG2-230 GEN
Solar/Wind Harmer
0.704
971347AH1-153 GEN
Solar/Wind Harmer
0.235
961761AG1-017 GEN
Solar/Wind Harmer
0.438
960591AF2-350 GEN
Solar/Wind Harmer
0.417
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
15.839
247536S-71 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
4.742
274857EASY ROAD;U1
Solar/Wind Harmer
3.587
24725505WLD G2 C
Solar/Wind Harmer
2.968
276656WTG2_EQ
Solar/Wind Harmer
0.85
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.539
270462AD2-086
Solar/Wind Helper
1.865
270317AD1-130_GEN
Solar/Wind Helper
1.216
270287AF1-227 GEN3
Solar/Wind Helper
0.382
24727005RPMNG1
50/50
67.807
247620Y3-023
50/50
0.45
959331AF2-224 GEN
Solar/Wind Harmer
1.126
965041AG1-368 GEN
Solar/Wind Harmer
0.675
270031AE2-169
Solar/Wind Harmer
0.368
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.489
274861TOP CROP ;1U
Solar/Wind Harmer
4.729
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.176
971067AG2-660 GEN
Solar/Wind Harmer
1.565
24699105WLD G1 C
Solar/Wind Harmer
2.968
276655WTG1_EQ
Solar/Wind Harmer
6.417
963841AG1-237 GEN
Solar/Wind Harmer
11.375
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.3
270286AF1-227 GEN2
Solar/Wind Helper
0.382
247522W1-056 GEN
Solar/Wind Helper
1.958
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.299
960861AF2-377 GEN
50/50
2.286
24729305KEY G2
50/50
6.704
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.92
957891AF2-083 GEN
Solar/Wind Harmer
0.707
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.667
274888KELLY CRK;1U
Solar/Wind Harmer
5.697
276893AG1-478 C
Solar/Wind Harmer
0.33
270005AE1-210 C O1
Solar/Wind Harmer
6.326
276602WESTBROOK C
Solar/Wind Harmer
1.658
274863CRW1-WTG
Solar/Wind Harmer
4.59
274864CRW2-WTG
Solar/Wind Harmer
4.59
276603SUBLETTE C
Solar/Wind Harmer
0.776
24387305FR-4G C
Solar/Wind Harmer
4.404
24386605FR-22G C
Solar/Wind Harmer
2.936
24387005FR-3G C
Solar/Wind Harmer
2.906
274880W4-005 GEN4
Solar/Wind Harmer
2.063
246936BC-WTG1
Solar/Wind Helper
17.184
246937BC-WTG2
Solar/Wind Helper
17.184
960841AF2-375 GEN
Solar/Wind Helper
0.576
943021AE2-325 GEN
Solar/Wind Harmer
2.881
964611AG1-324 GEN
Solar/Wind Harmer
0.393
276843GEN-1.7
Solar/Wind Harmer
0.553
958011AF2-095 GEN
Solar/Wind Harmer
0.601
276691AA1-018 GEN1
Solar/Wind Harmer
0.435
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
24697905MDL-4G C
Solar/Wind Harmer
2.038
970819AG2-516 GEN
Solar/Wind Harmer
0.465
276646AC1-214 GEN2
Solar/Wind Harmer
1.17
274878BISHOP HL;2U
Solar/Wind Harmer
2.932
965931AG1-462 GEN
Solar/Wind Harmer
0.934
274854TWINGROVE;U2
Solar/Wind Harmer
5.654
965091AG1-374 GEN
Solar/Wind Harmer
1.098
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
2.097
270499AE1-146 GEN
Solar/Wind Helper
0.556
24729405KEY G3
50/50
6.704
24729505KEY G4
50/50
6.593
270043AE2-236 GEN
Solar/Wind Harmer
0.363
971771AH1-392 GEN
Solar/Wind Harmer
0.426
970941AG2-585 GEN
Solar/Wind Harmer
0.23
276897AD1-100 C
Solar/Wind Harmer
54.783
971605AH1-302 GEN
Solar/Wind Harmer
6.118
970825AG2-519 GEN
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
4.671
970569AG2-363 GEN
Solar/Wind Harmer
1.162
276157O29GEN1
Solar/Wind Harmer
3.332
276645AC1-214 GEN1
Solar/Wind Harmer
1.17
939741AE1-205 GEN
Solar/Wind Harmer
0.745
942111AE2-223 GEN
Solar/Wind Harmer
8.72
970241AG2-163 GEN
Solar/Wind Harmer
0.884
276174W4-005 GEN2
Solar/Wind Harmer
2.063
276668AB2-070 GEN1
Solar/Wind Harmer
1.771
276838X2-022 GEN2
Solar/Wind Harmer
0.183
246938BC-WTG3
Solar/Wind Helper
17.48
274848CAMPGROVE;RU
Solar/Wind Harmer
4.383
276785W4-005 GEN1
Solar/Wind Harmer
2.063
276849AB2-070 GEN2
Solar/Wind Harmer
1.771
957201AF2-014 GEN
Solar/Wind Helper
3.968
270284AF1-227 GEN1
Solar/Wind Helper
1.035
270428AC2-015 C
Solar/Wind Helper
0.376
253383AE2-342_GEN
Solar/Wind Helper
0.105
970031AG2-029 GEN
Solar/Wind Harmer
1.71
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.032
944531AF1-118 GEN
Solar/Wind Harmer
2.012
270247TR4_N_V136
Solar/Wind Harmer
1.123
970707AG2-453 GEN
Solar/Wind Harmer
1.161
970833AG2-524 GEN
Solar/Wind Harmer
3.609
958481AF2-142 GEN
Solar/Wind Harmer
0.607
274862TOP CROP ;2U
Solar/Wind Harmer
4.729
274879MINONK ;1U
Solar/Wind Harmer
6.19
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
276903AD2-071 C
Solar/Wind Harmer
0.388
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.786
945391AF1-204 GEN
Solar/Wind Harmer
12.593
270391AF1-285 GEN3
Solar/Wind Helper
0.3
241847AF2-150_GEN
Solar/Wind Helper
0.265
961051AF2-396 GEN
Solar/Wind Harmer
0.935
961051AF2-396 GEN
Solar/Wind Harmer
7.477
270599AE1-208 GEN
Solar/Wind Harmer
0.368
972231SS25-0005
Solar/Wind Harmer
0.685
971411AH1-196 GEN
Solar/Wind Harmer
0.591
274855GSG-6 ;RU
Solar/Wind Harmer
3.361
276876AE1-163_GEN2
Solar/Wind Harmer
5.354
24386405FR-21G C
Solar/Wind Harmer
2.936
276782AC1-033 GEN
Solar/Wind Harmer
2.956
276763AC1-053 GEN1
Solar/Wind Harmer
2.681
971029AG2-637 GEN
Solar/Wind Harmer
0.465
965021AG1-366 GEN
Solar/Wind Harmer
4.503
942221AE2-234 GEN
Solar/Wind Harmer
0.2
958861AF2-177 GEN
Solar/Wind Harmer
15.573
945371AF1-202 GEN
Solar/Wind Harmer
7.349
270505AE1-170 C O1
Solar/Wind Harmer
0.702
270032AE2-172
Solar/Wind Harmer
3.253
970825AG2-519 GEN
Solar/Wind Harmer
1.712
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.198
971997AH1-543 GEN
Solar/Wind Harmer
0.622
276889AE2-281 GEN
Solar/Wind Harmer
1.53
24691005MDL-2G C
Solar/Wind Harmer
3.058
971549AH1-272 GEN
Solar/Wind Harmer
0.702
276158O29GEN2
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
3.129
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.205
270543AE2-219 C
Solar/Wind Harmer
0.354
971993AH1-541 GEN
Solar/Wind Harmer
0.319
276621W2-048 GEN
Solar/Wind Harmer
4.9
942481AE2-261 GEN
Solar/Wind Harmer
0.979
270485AE1-090_GEN
Solar/Wind Helper
0.162
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.91
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.095
270180AB1-006 GEN1
Solar/Wind Harmer
5.504
24791305MDL-5G
Solar/Wind Harmer
2.038
276741O09 GEN1
Solar/Wind Harmer
3.129
276726Z2-087_GEN
Solar/Wind Harmer
5.813
944221AF1-090 GEN
Solar/Wind Harmer
9.816
966831AG1-554 GEN
Solar/Wind Helper
0.286
24729205KEY G1
50/50
6.593
270201AC2-176 GEN
Solar/Wind Harmer
4.506
970373AG2-245 GEN
Solar/Wind Harmer
0.901
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.326
274872LEEDK;1U
Solar/Wind Harmer
7.44
276872AE1-163_GEN1
Solar/Wind Harmer
5.354
959081AF2-199 GEN
Solar/Wind Harmer
0.391
274851PROVIDENC;RU
Solar/Wind Harmer
2.181
24386205FR-12G C
Solar/Wind Harmer
3.065
24379505HDWTR1G C
Solar/Wind Harmer
5.555
970885AG2-551 GEN
Solar/Wind Harmer
1.417
963741AG1-226 GEN
Solar/Wind Harmer
1.592
276686W4-005 GEN3
Solar/Wind Harmer
2.063
276764AC1-053 GEN2
Solar/Wind Harmer
2.681
276911AD2-131_GEN
Solar/Wind Harmer
0.162
965421AG1-410 GEN
Solar/Wind Harmer
6.711
965651AG1-433 GEN
Solar/Wind Harmer
8.016
972181SS23-001
Solar/Wind Harmer
0.428
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.266
970289AG2-191 GEN
Solar/Wind Harmer
0.078
274847GR RIDGE ;BU
Solar/Wind Harmer
4.711
946031AF1-268 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
0.782
274849CRESCENT ;1U
Solar/Wind Harmer
1.605
957381AF2-032 GEN
Solar/Wind Harmer
0.066
276916AD2-100_GEN
Solar/Wind Harmer
0.681
270227U2-072_GEN3
Solar/Wind Helper
2.097
270228U2-072_GEN4
Solar/Wind Helper
2.097
270231U2-072_GEN5
Solar/Wind Helper
2.097
270349AD2-093_GEN
Solar/Wind Helper
0.517
970521AG2-332 GEN
50/50
10.514
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
12.855
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.782
274877BISHOP HL;1U
Solar/Wind Harmer
2.932
276848AB2-070 GEN3
Solar/Wind Harmer
1.771
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.216
270471AD2-092_GEN
Solar/Wind Helper
0.517
276820AF1-078_GEN
Solar/Wind Helper
0.166
270224U2-072_GEN2
Solar/Wind Helper
2.097
942871AE2-306 GEN
Solar/Wind Helper
0.225
945641AF1-229 GEN
Solar/Wind Helper
0.46
270541AE2-072 C
Solar/Wind Helper
0.478
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.144
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
276868AE1-113 GEN
Solar/Wind Harmer
9.286
24697605MDL-3G C
Solar/Wind Harmer
3.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.782
24385905FR-11G C
Solar/Wind Harmer
5.772
946321AF1-296 GEN
Solar/Wind Harmer
10.97
274853TWINGROVE;U1
Solar/Wind Harmer
5.654
959611AF2-252 GEN
Solar/Wind Harmer
1.464
960611AF2-352 GEN
Solar/Wind Harmer
1.464
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.354
970193AG2-126 GEN
Solar/Wind Harmer
0.475
958581AF2-149 GEN
Solar/Wind Helper
0.216
990792J1392
External Queue
0.3014104962348938
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
SIGELTFEXP_SIGE->PJM
CLTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.67
NYPJM->LTFIMP_NY
CLTF
1.235
TVALTFEXP_TVA->PJM
CLTF
2.193
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.955
LGEELTFEXP_LGEE->PJM
CLTF
1.68
MECLTFEXP_MEC->PJM
CLTF
9.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.406
WECLTFEXP_WEC->PJM
CLTF
2.556
LAGNLTFEXP_LAGN->PJM
CLTF
5.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
243211 to 242933 ckt 1
243206 to 290606 ckt Z1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
290608 to 242928 ckt Z1
242933 to 965420 ckt 1
965420 to 246929 ckt 1

Light Load Analysis

The New Service Request AH1-272 was evaluated as a 185.0 MW injection

AH1-272 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 185.0 MW (185.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2ATSI/ITCT
19MAPLE-02LEMOYN 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-032T_SRT-A
TowerAC100.69 %852.0B857.91
9.62

Details for 19MAPLE-02LEMOYN 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-032T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/ITCT
Facility Description:
19MAPLE-02LEMOYN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-032T_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.69 %
Rating:852.0 MVA
Rating Type:B
MVA to Mitigate:857.91
MW Contribution:
9.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241886AC2-103 GEN2
Solar/Wind Helper
2.998
241885AC2-103 GEN1
Solar/Wind Helper
2.998
270428AC2-015 C
Solar/Wind Helper
1.659
241808AF1-120 C
Solar/Wind Helper
0.757
241996AE2-282_GEN
Solar/Wind Helper
1.357
241832AE2-181_GEN
Solar/Wind Helper
0.965
241807AE2-176_GEN
Solar/Wind Helper
2.452
241840AF1-064_GEN
Solar/Wind Helper
1
270449AD2-020 GEN
Solar/Wind Harmer
0
270499AE1-146 GEN
Solar/Wind Helper
1.869
270505AE1-170 C O1
Solar/Wind Harmer
4.929
943021AE2-325 GEN
Solar/Wind Harmer
3.278
945111AF1-176 GEN
Solar/Wind Harmer
3.592
945111AF1-176 GEN
Solar/Wind Harmer
4.451
945641AF1-229 GEN
Solar/Wind Helper
2.045
960841AF2-375 GEN
Solar/Wind Helper
2.126
961051AF2-396 GEN
Solar/Wind Harmer
6.749
961051AF2-396 GEN
Solar/Wind Harmer
4.908
971549AH1-272 GEN
Solar/Wind Harmer
9.619
957891AF2-083 GEN
Solar/Wind Harmer
4.875
990142J1224
External Queue
18.80097770690918
990527J1329
External Queue
4.021599292755127
991182J1586 G
External Queue
32.84828567504883
991227J1663 G
External Queue
6.8025898933410645
CBM West 1LTFEXP_CBM-W1->PJM
CBM
104.451
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.038
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.383
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.888
NYPJM->LTFIMP_NY
CLTF
0.818
LGEELTFEXP_LGEE->PJM
CLTF
0.904
WECLTFEXP_WEC->PJM
CLTF
1.221
CPLELTFEXP_CPLE->PJM
CLTF
0.087
TVALTFEXP_TVA->PJM
CLTF
1.136
MECLTFEXP_MEC->PJM
CLTF
4.477
LAGNLTFEXP_LAGN->PJM
CLTF
2.818
SIGELTFEXP_SIGE->PJM
CLTF
0.088
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CONTINGENCY 'ATSI_P7-1_TE-345-032T_SRT-A'
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 256583 CKT 1   /*19LULU       345.0 - 18MOROCCO    345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264613 CKT 1   /*19LULU       345.0 - 19MON34      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264839 CKT 1   /*19LULU       345.0 - 19MILAN      345.0
END
265709 to 238889 ckt 1

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-230, AG2-562, AH1-153 and AH1-272 in PJM Transition Cycle 2 Cluster 40 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 40 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 40 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 40 projects have been dispatched online at maximum power output, with 1.0 voltage at the terminal bus.

 

Transition Cycle 2 Cluster 40 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Three-phase faults with loss of multiple-Circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 40 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 Summer Peak case:

       a)       Cluster 40 projects were able to ride through the faults (except for faults where protective action trips a generator(s)).

       b)       The system with Cluster 40 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

In several contingencies, AH1-153 active power failed to recover to the pre fault level. Although this issue did not cause instability in the system, the model was tuned to achieve satisfactory active power recovery. This was accomplished by adjusting the Kp, Ki, and Kc in the plant controller model (REPCA1) by setting Kp from 3 to 5, Ki from 5 to 3, and Kc from 0 to 0.065. The parameters modification is pending developer’s confirmation.

 

The IPCMD and IQCMD states in the REGCA1 models of AG2-230 showed erratic behavior for some contingencies in which AG2-230 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

The IPCMD and IQCMD states in the REGCA1 models of AH1-153 showed erratic behavior for some contingencies in which AH1-153 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

The IPCMD and IQCMD states in the REGCA1 models of AH1-272 showed erratic behavior for some contingencies in which AH1-272 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 40 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-230

Solar

AEP

150

Dumont substation 345 kV

AH1-153

Solar

AEP

50

Dumont substation 345 kV

AG2-562

Natural Gas

AEP

52

Elderberry station 345 kV

AH1-272

Solar

AEP

185

Twin Branch – Argenta 345 kV

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AH1-272 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AB1-006Meadow Lake 345kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-170East Lima-Marysville 345kVIn Service
AC1-001Delano 138kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-078Beatty-London 138kVIn Service
AC1-085Stuart-Clinton 345kVIn Service
AC1-111Aurora 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Platter Creek 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-214Crescent RidgeIn Service
AC2-015Chatfield-Howard 138kVPartially in Service - Under Construction
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-090Losantville 345kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-195Galion-Roberts South 138 kVPartially in Service - Under Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVWithdrawn
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVWithdrawn
AD2-093Marysville 345kVPartially in Service - Under Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVEngineering & Procurement
AE1-102Maddox Creek 345 kVSuspended
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-183Maysville-McDowell 69 kVUnder Construction
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVPartially in Service - Under Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-089Pennville-Adams 138 kVSuspended
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVIn Service
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVUnder Construction
AE2-216Hardin Switch 345 kVSuspended
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVUnder Construction
AE2-282East Fayette 138 kVIn Service
AE2-285Maysville 69 kVUnder Construction
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVWithdrawn
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-322Platter Creek 69kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVWithdrawn
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-342Woodstock 69 kVSuspended
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-084Hartford-Almena 69 kVUnder Construction
AF1-086Madera-Westover South 115 kVPartially in Service - Under Construction
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-093Henderson-Stoneboro 69 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVSuspended
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-122Cardington-Liberty 69 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVUnder Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-204Eugene 345 kVEngineering & Procurement
AF1-205Napoleon Muni 138 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-229Galion-South Berwick 345 kVUnder Construction
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVUnder Construction
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-302Brookville-Squab Hollow 138 kVUnder Construction
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-004Beaver 345 kVEngineering & Procurement
AF2-005Beaver 138 kVEngineering & Procurement
AF2-014Maddox Creek 345 kVUnder Construction
AF2-032Kincaid 345 kVWithdrawn
AF2-039Shawville-Clearfield 34.5 kVUnder Construction
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-068Jay 138 kVEngineering & Procurement
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-103Haviland 138 kVIn Service
AF2-122Kirk 138 kVPartially in Service - Under Construction
AF2-126Weston 69 kV IIUnder Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-187Brookside-Cloverdale 138 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVPartially in Service - Under Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-377Logtown 138 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AG1-017Jay 138 kVIn Service
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-109Valley 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-198Union City 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-411Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-500Beaver 345 kVEngineering & Procurement
AG1-501Beaver 138 kVEngineering & Procurement
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG2-029Forest G. Hipple-Dunton Lake 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-109Fitchville-New London 69 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-332East Elkhart - Elcona Tap 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-370Tillman 138 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-675Cordova 345 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Delaware Business Park 138kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-073Yankee 12.5kVIn Service
W1-056Ada-Dunkirk 69kVIn Service
W2-048Brokaw-LanesvilleIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts
AH1-272 System Reinforcements:
TOTrans Owner IDTitleAllocated Cost ($USD)
METCMETC_TC2_19125Reconductor Allen Junction - Morocco to 2-1431 ACSS and replace 13 trainers$4,880,003
Grand Total:$4,880,003

System Reinforcement
Type
Load Flow
TO
METC
RTEP ID / TO ID
(Pending) / METC_TC2_19125
Title
Reconductor Allen Junction - Morocco to 2-1431 ACSS and replace 13 trainers
Description
Reconductor Allen Junction - Morocco to 2-1431 ACSS and replace 13 trainers. New ratings for METC/MISO facilities will be 2094/2390 MVA SN/SE.
Total Cost ($USD)
$17,019,725
Allocated Cost ($USD)
$4,880,003
Time Estimate
18 Months

Contributor

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-363
17.4 MW19.0%$3,227,613
AG2-364
11.6 MW12.6%$2,151,742
AG2-660
1.4 MW1.5%$252,273
AH1-044
11.7 MW12.7%$2,169,364
AH1-150
11.7 MW12.7%$2,169,364
AH1-151
11.7 MW12.7%$2,169,364
AH1-272
26.3 MW28.7%$4,880,003

System Reinforcement
Type
Load Flow
TO
ITCT
RTEP ID / TO ID
(Pending) / ITCT_TC1_13866
Title
MTEP #25223/#25224 - Lulu Sub. Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station (Projected ISD 6/11/2027)
Description
Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station. This project is a DPP 2020 Network Upgrade associated with the J1516, J1525, J1526, J1527, J1550, J1553, J1557, J1571, J1586, J1587, J1603, J1614, J1635, J1658, J1659, J1663, and J1664 projects. Projected In-Service 6/1/2027
Total Cost ($USD)
$29,916,928
Allocated Cost ($USD)
$0
Time Estimate
TBD

ContingentTopology Changing

Note 1: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
02LEMOYN-19MAPLE 345.0 kV Ckt 1 line(Any)

New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact
          Powerton ;B 345 kV  (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-363, AG2-364
        
          Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-660, AH1-044, AH1-150, AH1-151
        

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Impacted FacilityTransmission OwnerReinforcementCostCost Allocated to AH1-272Scenarios
  • Wvrich 69.0 - Rochester TP 69.0 CKT 1
NIPS Wvrich - Rochester TP 69 kV
DEI: Rebuild 1 mile of 69kV with 477ACSR/VR2 @
100/120C the ratings assume that NIPSCO terminal
upgrades would not limit our T-Line rating. $1.5M

NIPSCO: DEI mitigations acceptable to remove
constraint. $0
$1,500,000$49,531
  • NIPSCO
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AH1-272 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
APSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationContingent$0N/A
APSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Contingent$0N/A
APSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardContingent$0N/A
APSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Contingent$0N/A
APSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Contingent$0N/A
ATSINoneLallendorf & Allen Jct Substation Upgrades (Projected ISD 6/1/2032) - s3845.1Contingent$0N/A
AEPb4068.1b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570Contingent$0N/A
AEPb3919.1Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yardContingent$0N/A
AEPb4000.251Replace the wave trap and upgrade the relay at Cloverdale 765kV substationContingent$0N/A
AEPb4000.252Replace the wave trap and upgrade the relay at Joshua Falls 765kV substationContingent$0N/A
Grand Total:$0

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / ATSI-2025-005 (Supplemental)
Title
Lallendorf & Allen Jct Substation Upgrades (Projected ISD 6/1/2032) - s3845.1
Description
1) At Lallendorf Substation: Substation: Replace line relaying. Install new seven-mile ADSS fiber line from Lallendorf Substation to Toledo Edison regional services territory boundary. 2) At Allen Junction Substation: replace disconnect switches, breaker leads, metering, and transmission line drops. Cost Est: $7.21 mil Allen Junction – Morocco 345 kV Line ratings: - Before Proposed Solution: 1517 / 1793 / 1759 / 1793 MVA (SN/SE/WN/WE) - After Proposed Solution: 1868 / 2249 / 2340 / 2535 MVA (SN/SE/WN/WE) Laplaissance Creek 345kV sub involves tapping the Lemoyne-Maple (J1062 POI) 345kV line & Lallendorf-Monroe 345kV line https://www.pjm.com/-/media/DotCom/committees-groups/committees/teac/2025/20251208/20251208-item-04---atsi-supplemental-projects.pdf
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Contingent

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1868.0 MVA
(All)B2249.0 MVA
WINA2340.0 MVA
WINB2535.0 MVA

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
05MARYSV-05BOKESCRK 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5395.0 MVA
(All)B5523.0 MVA
05MERIDN-05TWIN B 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
05MARYSV-05BOKESCRK 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MERIDN-05TWIN B 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: n9227.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9227.0 / TC1-ATSI-001.b
Title
Beaver-Lake Ave Ckt #2 345kV: Upgrade T-line drops, overhead substation conductor and TL reconductor
Description
Reconductor (possible rebuild) of 8.12 miles of dual transmission line and (2) single conductor line drops at Beaver on the Beaver-Lake Ave Ckt #2 345 kV line using triple (3) 1113 54/19 ""Finch"" ACSS"
Total Cost ($USD)
$48,873,856
Discounted Total Cost ($USD)
$48,873,856
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Rating SetRating TypeRating Value
(All)A1868.0 MVA
(All)B2249.0 MVA
(All)C2375.0 MVA

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: s3442.26
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s3442.26
Title
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont
Description
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont to address a generation deliverability violation on the Dumont – Sorenson 765 kV branch related to the new customer interconnections in the area. Projected in service date 3/5/2027
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-272 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5395.0 MVA
(All)B5523.0 MVA
(All)C5523.0 MVA

System Reinforcement: n9767.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9767.0 / AEP-TC2-19068
Title
05KAMMER_RG 765.0 kV to 05KAMMER 765.0 kV ckt Z1 - Replace Wavetraps
Description
Replace the existing 3000A wave trap at Kammer 765 station towards Guernsey with a 5000A wave trap. Additionally, replace the 3000A circuit breaker QQ1 with a 5000A circuit breaker. Disconnect switches and a relays will be upgraded as well.
Total Cost ($USD)
$4,500,000
Discounted Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3851.2
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.2
Title
Rebuild R.P. Mone – Maddox Creek 345kV line (9.4 miles).
Description
Rebuild R.P. Mone – Maddox Creek 345kV line (9.4 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA
(All)C3774.0 MVA
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA
(All)C3774.0 MVA

System Reinforcement: n9786.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9786.0 / AEP-TC2-19161
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Wave Traps
Description
Replace wave tap at Maliszewski towards Marysville
Total Cost ($USD)
$3,000,000
Discounted Total Cost ($USD)
$3,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3919.5
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.5 / (Pending)
Title
Reconductor 4.75-miles of the existing Bokes Creek-Marysville 345 kV circuit.
Description
Reconductor 4.75-miles of the existing Bokes Creek-Marysville 345 kV circuit. Update the associated relay settings.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05BOKESCRK 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1740.0 MVA
(All)B1868.0 MVA
(All)C1925.0 MVA

System Reinforcement: n9766.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9766.0 / AEP-TC2_19067
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Wavetrap
Description
Replace 4000A Wavetrap towards Maliszewski with 5000A equivalent
Total Cost ($USD)
$1,100,000
Discounted Total Cost ($USD)
$1,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Nov 12 2027

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B6667.0 MVA
(All)C6868.0 MVA

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-272


AH1-272 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowAPSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationTopology-0.0%Contingent$0
Load FlowAPSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Topology-0.0%Contingent$0
Load FlowAPSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardTopology-0.0%Contingent$0
Load FlowAPSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Topology-0.0%Contingent$0
Load FlowAPSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowITCT(Pending) / ITCT_TC1_13866MTEP #25223/#25224 - Lulu Sub. Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station (Projected ISD 6/11/2027)Topology-0.0%Contingent$0
Load FlowAEPb4068.1 / AEP-TC2-18693b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570Topology-0.0%Contingent$0
Load FlowAEPb3919.1Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yardTopology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-272 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-272 One Line Diagram

AH1-272 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.