AH1-292 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:29

Sullivan 345 kV

44.0 MW Capacity / 0.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Trade Post Solar LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $0 $0 = ∞ AND ( $0 - $0 ) 44.0 = $0 per MW

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the American Electric Power zone — Sullivan County, Indiana. This project is an increase to the developer’s AC2-157 project(s), which will share the same Point of Interconnection. The AH1-292 project is a 44.0 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 200.0 MW with 120.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-292
Project Name:
Sullivan 345 kV
Project Developer Name:
Trade Post Solar LLC
State:
Indiana
County:
Sullivan
Transmission Owner:
American Electric Power
MFO:
200.0
MWE:
0.0
MWC:
44.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Not Required

A Physical Interconnection Facilities Study is not required for this project.

Point of Interconnection

AH1-292 will interconnect on the American Electric Power transmission system at the Sullivan 345 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-292 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-292Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$0$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$0$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$0$0$0

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-292

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-292
Project ID: AH1-292
20% of cost allocation for Phase II Network Upgrades:(A) $0
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $176,000
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

no interconnections facilities required to support the interconnection

(Pending Facilities Study)$0$0
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$0$0
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 0 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-292 was evaluated as a 0.0 MW (44.0 MW Capacity) injection in the AEP area.

AH1-292 was evaluated as part of a plant. The plant consists of AH1-292. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC102.09 %5523.0B5638.63
5.17
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC102.08 %5523.0B5637.94
5.17
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC123.36 %4571.0B5638.63
5.17
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC123.34 %4571.0B5637.94
5.17
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC104.85 %4142.0B4342.78
6.13
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.48 %4571.0B4638.62
5.2
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.94 %4571.0B4659.48
5.2
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS
SingleAC120.92 %4142.0B5008.41
5.41
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#XXXX_MARYSVILLE_TEDDY_SRT-A_SENS
SingleAC102.05 %4142.0B4227.07
4.56
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC107.72 %1189.0A1280.85
2.38

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
5.17
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
5.17
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.36 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
5.17
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
5.17
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4342.78
MW Contribution:
6.13
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.43 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4946.71
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
270120AB2-067 GEN2
50/50
13.691
270160DARBY CT5
50/50
0.825
270466AD2-091
50/50
8.422
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
16.303
270462AD2-086
Solar/Wind Harmer
0.001
970349AG2-230 GEN
Solar/Wind Harmer
13.735
960971AF2-388 GEN
Solar/Wind Harmer
5.346
24697605MDL-3G C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
8.243
966841AG1-555 GEN
Solar/Wind Harmer
1.019
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.057
970883AG2-550 GEN
Solar/Wind Harmer
8.946
274808UNIV PK N;4U
Adder
6.368
926881AC1-175 GEN
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
19.549
958481AF2-142 GEN
Solar/Wind Harmer
13.2
961051AF2-396 GEN
Solar/Wind Harmer
17.567
961051AF2-396 GEN
Solar/Wind Harmer
11.711
962761AG1-125 GEN
Solar/Wind Harmer
51.21
270520AE2-214 GEN
Solar/Wind Harmer
0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
270273AD2-016 GEN
Solar/Wind Harmer
1.001
25326309TAIT D
Adder
1.474
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
10.066
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
10.545
274802UNIV PARK;5U
Adder
7.433
270437AC2-090 C
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
20.872
274674JOLIET 9 ;6U
Adder
19.549
939401AE1-172 GEN
Solar/Wind Harmer
6.59
962781AG1-127 GEN
Solar/Wind Harmer
8.326
274766LEE CO EC;7U
Adder
11.361
276708O09 GEN2
Solar/Wind Harmer
0.303
965911AG1-460 GEN
Solar/Wind Harmer
1.674
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.485
203855AF2-088 C
Solar/Wind Helper
0.158
970155AG2-107 GEN
Solar/Wind Harmer
32.701
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
965651AG1-433 GEN
Solar/Wind Harmer
2.673
971995AH1-542 GEN
Solar/Wind Harmer
3.337
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.955
274812UNIV PK N;8U
Adder
6.396
24639705ELKHART HY
Adder
0.196
965421AG1-410 GEN
Solar/Wind Harmer
26.684
970613AG2-401 GEN
Solar/Wind Harmer
6.512
274676JOLIET 29;8U
Adder
38.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.607
274828WAUKEGAN ;BP
Adder
13.888
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
957471AF2-041 GEN
Solar/Wind Harmer
26.068
24728605AND G2
Adder
4.768
25194608D.CRK4
Adder
2.043
252516AE2-318_GEN
Solar/Wind Harmer
9.707
274848CAMPGROVE;RU
Solar/Wind Harmer
0
241966AE1-183 GEN
Solar/Wind Helper
0.312
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
964201AG1-281 GEN
Solar/Wind Helper
0.498
238185AF2-356 C
Solar/Wind Helper
2.178
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.055
203952AE2-129 C
Solar/Wind Helper
0.488
238120AE2-309 GEN
Solar/Wind Helper
0.416
23751101LEADS_P59
Solar/Wind Helper
1.832
270051AF1-062 GEN
50/50
18.043
270043AE2-236 GEN
Solar/Wind Harmer
5.885
253394AE2-221_GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
3.029
274772LINCOLN ;3U
Adder
10.86
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.441
970825AG2-519 GEN
Solar/Wind Harmer
6.737
274724RIVER EC ;11
Adder
22.661
972259AH1-714 GEN
Adder
24.311
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.319
274729ELWOOD EC;1P
Adder
20.872
270505AE1-170 C O1
Solar/Wind Harmer
9.267
945111AF1-176 GEN
Solar/Wind Harmer
7.15
946671AF1-331 GEN
Solar/Wind Harmer
0.929
274850MENDOTA H;RU
Solar/Wind Harmer
0.101
970571AG2-364 GEN
Solar/Wind Harmer
17.368
971993AH1-541 GEN
Solar/Wind Harmer
3.929
25196008MFTGT1
Adder
1.643
942481AE2-261 GEN
Solar/Wind Harmer
25.023
270367AC2-061_GEN
Solar/Wind Harmer
-0.001
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
961921AG1-034 GEN
Solar/Wind Harmer
11.241
942051AE2-217 GEN
Solar/Wind Harmer
20.261
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
944531AF1-118 GEN
Solar/Wind Harmer
41.277
971347AH1-153 GEN
Solar/Wind Harmer
4.578
970781AG2-491 GEN
Solar/Wind Harmer
9.079
270063AE2-323 C
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
10.545
274887GEN-1.85
Solar/Wind Harmer
0.231
970707AG2-453 GEN
Solar/Wind Harmer
29.056
274826FISK ;BP
Adder
13.952
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
20.872
274862TOP CROP ;2U
Solar/Wind Harmer
1.188
276868AE1-113 GEN
Solar/Wind Harmer
1.751
274879MINONK ;1U
Solar/Wind Harmer
0.365
274855GSG-6 ;RU
Solar/Wind Harmer
0.318
25196608WSDLE5
Adder
10.674
959611AF2-252 GEN
Solar/Wind Harmer
2.874
274857EASY ROAD;U1
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
12.901
276782AC1-033 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.384
202652Y1-033 WT C
Solar/Wind Helper
0.576
20092526R32
Solar/Wind Helper
1.21
20398826ARMNA MT
Solar/Wind Helper
1.511
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.259
958171AF2-111 GEN
Solar/Wind Harmer
13.887
970149AG2-104 GEN
Solar/Wind Harmer
27.654
971917AH1-482 GEN
Solar/Wind Harmer
11.826
970373AG2-245 GEN
Solar/Wind Harmer
19.061
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
20.916
276691AA1-018 GEN1
Solar/Wind Harmer
1.43
274861TOP CROP ;1U
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
1.548
943021AE2-325 GEN
Solar/Wind Harmer
4.573
276882AE2-255 GEN
Solar/Wind Harmer
1.021
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
8.689
971067AG2-660 GEN
Solar/Wind Harmer
2.896
274822ROCKFORD ;11
Adder
24.404
276655WTG1_EQ
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
10.388
276646AC1-214 GEN2
Solar/Wind Harmer
0.338
970091AG2-072 GEN
Adder
16.07
270161DARBY CT6
50/50
0.813
25326109MON D
50/50
1.903
942861AE2-305 GEN
Solar/Wind Harmer
8.674
270269AC2-059
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
4.181
945421AF1-207 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.609
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
8.281
270031AE2-169
Solar/Wind Harmer
4.946
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.672
970885AG2-551 GEN
Solar/Wind Harmer
2.982
270383AD1-128 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
12.809
247620Y3-023
Adder
0.586
274695ROCKY RD ;2P
Adder
14.015
958491AF2-143 GEN
Solar/Wind Harmer
13.148
276872AE1-163_GEN1
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.757
972236AH1-702 GEN2
Adder
2.723
274765LEE CO EC;6U
Adder
11.523
274763LEE CO EC;4U
Adder
11.388
252509AD1-136 GEN
Solar/Wind Harmer
0.043
276911AD2-131_GEN
Solar/Wind Harmer
1.155
254304AE2-114 C
Solar/Wind Helper
0.274
946381AF1-302 GEN
Solar/Wind Helper
0.237
203961AE2-224 GEN
Solar/Wind Helper
2.479
940863AE2-074 GEN
Solar/Wind Helper
0.479
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.672
203946AE2-131 C
Solar/Wind Helper
0.488
235531U2-073 GEN
Solar/Wind Helper
2.67
270475AD2-096_GEN
50/50
10.581
270518AE2-148 GEN
Solar/Wind Harmer
0.888
253325AC1-069 GEN
Solar/Wind Harmer
0.012
970191AG2-125 GEN
Solar/Wind Harmer
2.379
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.936
274753CRETE EC ;3U
Adder
10.545
274814UNIV PK N;0U
Adder
6.452
274807UNIV PK N;3U
Adder
6.438
276843GEN-1.7
Solar/Wind Harmer
0.288
274803UNIV PARK;6U
Adder
7.433
972038AH1-567 GEN2
Adder
0.465
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
1.154
965091AG1-374 GEN
Solar/Wind Harmer
25.867
274760LEE CO EC;1U
Adder
11.496
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965931AG1-462 GEN
Solar/Wind Harmer
21.621
962511AG1-100 GEN
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
0.893
203854AF2-039 C
Solar/Wind Helper
0.327
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.265
971611AH1-305 GEN
Solar/Wind Harmer
5.423
959141AF2-205 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.671
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
10.86
274777LINCOLN ;8U
Adder
10.86
247536S-71 GEN
Solar/Wind Harmer
0.358
965051AG1-369 GEN
Solar/Wind Harmer
4.466
970031AG2-029 GEN
Solar/Wind Harmer
4.844
971029AG2-637 GEN
Solar/Wind Harmer
13.408
960591AF2-350 GEN
Solar/Wind Harmer
8.895
972228AH1-698 GEN2
Adder
4.722
972037AH1-567 GEN1
Adder
0.233
274675JOLIET 29;7U
Adder
38.97
274675JOLIET 29;7U
Adder
37.578
970833AG2-524 GEN
Solar/Wind Harmer
9.741
970833AG2-524 GEN
Solar/Wind Harmer
6.494
971675AH1-338 GEN
Solar/Wind Harmer
3.397
971411AH1-196 GEN
Solar/Wind Harmer
13.063
971171AH1-044 GEN
Solar/Wind Harmer
17.379
274823ROCKFORD ;21
Adder
24.227
274853TWINGROVE;U1
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.127
946321AF1-296 GEN
Solar/Wind Harmer
4.758
23652301WDPWR_K20
Solar/Wind Helper
0.16
203846AF2-130 C
Solar/Wind Helper
0.498
203955AF1-039 C O1
Solar/Wind Helper
0.38
23750701CROSSCHOOL
Solar/Wind Helper
1.182
270159DARBY CT4
50/50
0.828
961821AG1-024 GEN
Solar/Wind Harmer
7.494
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
971655AH1-328 GEN
Solar/Wind Harmer
3.602
25322209TAIT E
Adder
13.115
25322209TAIT E
Adder
12.82
253370AE2-315 SEC1
Adder
2.679
970291AG2-192 GEN
Solar/Wind Harmer
1.186
970291AG2-192 GEN
Solar/Wind Harmer
0.547
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
4.358
965681AG1-436 GEN
Solar/Wind Harmer
11.293
247621Y3-024
Adder
0.31
270246TR4_N_V150
Solar/Wind Harmer
0.057
276776AD2-060 GEN
Solar/Wind Harmer
0.949
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.379
971343AH1-151 GEN
Solar/Wind Harmer
17.379
971587AH1-292 GEN
Solar/Wind Harmer
6.129
276916AD2-100_GEN
Solar/Wind Harmer
17.538
241801AE1-079 GEN
Solar/Wind Helper
0.309
203835AF1-098 GEN
Solar/Wind Helper
2.053
203818AF1-086 GEN
Solar/Wind Helper
1.772
203853AF1-134 C O1
Solar/Wind Helper
0.497
203804AE2-113_GEN
Solar/Wind Helper
1.84
962771AG1-126 GEN
Solar/Wind Harmer
51.21
970153AG2-106 GEN
Solar/Wind Harmer
32.701
270284AF1-227 GEN1
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.003
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.642
946031AF1-268 GEN
Solar/Wind Harmer
8.511
274811UNIV PK N;7U
Adder
6.396
276806AD2-047 C O1
Solar/Wind Harmer
5.041
274676JOLIET 29;8U
Adder
37.578
274734ELWOOD EC;8P
Adder
20.872
274736ELWOOD EC;9P
Adder
20.872
943121AE2-341 GEN
Solar/Wind Harmer
14.798
943591AF1-030 GEN
Solar/Wind Harmer
9.841
24695305TIMB G C
Solar/Wind Harmer
0.747
274682WAUKEGAN ;7U
Adder
22.607
959091AF2-200 GEN
Solar/Wind Harmer
17.379
24728505AND G1
Adder
4.768
25194608D.CRK4
Adder
2.043
252519AF1-045_GEN
Solar/Wind Harmer
4.521
274767LEE CO EC;8U
Adder
11.361
971087AG2-675 GEN
Solar/Wind Harmer
4.522
957381AF2-032 GEN
Solar/Wind Harmer
1.898
235058AG1-386 C
Solar/Wind Helper
0.575
964991AG1-363 GEN
Solar/Wind Helper
3.728
20303426NA_O38_P22
Solar/Wind Helper
1.017
203993AD2-133_GEN1
Solar/Wind Helper
1.055
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
4.282
943851AF1-053 GEN
Solar/Wind Harmer
2.966
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.422
253372AE2-315 SEC3
Adder
2.534
253372AE2-315 SEC3
Adder
2.534
25306009OHH W.
Adder
3.829
970289AG2-191 GEN
Solar/Wind Harmer
1.733
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
12.161
247521TR3_G114
Solar/Wind Harmer
0.324
972227AH1-698 GEN1
Adder
3.325
274827FISK ;RP
Adder
9.888
274800UNIV PARK;3U
Adder
7.429
274801UNIV PARK;4U
Adder
7.429
957201AF2-014 GEN
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
20.872
274744AC1-111 GEN8
Adder
7.068
970169AG2-114 GEN
Solar/Wind Harmer
8.736
959341AF2-225 GEN
Solar/Wind Harmer
9.098
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276741O09 GEN1
Solar/Wind Harmer
0.303
276668AB2-070 GEN1
Solar/Wind Harmer
0.334
276848AB2-070 GEN3
Solar/Wind Harmer
0.333
276849AB2-070 GEN2
Solar/Wind Harmer
0.334
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
241997AF1-093 GEN
Solar/Wind Helper
0.312
270166AC1-044 GEN3
50/50
13.691
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.387
964861AG1-349 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
9.088
270594AE1-207 GEN
Solar/Wind Harmer
10.169
270032AE2-172
Solar/Wind Harmer
6.053
945371AF1-202 GEN
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
10.86
274774LINCOLN ;5U
Adder
10.86
970825AG2-519 GEN
Solar/Wind Harmer
3.175
270005AE1-210 C O1
Solar/Wind Harmer
1.936
274723RIVER EC ;12
Adder
22.929
274751CRETE EC ;1U
Adder
10.545
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.358
270489AE1-102 GEN1
Solar/Wind Harmer
1.154
957891AF2-083 GEN
Solar/Wind Harmer
14.717
945111AF1-176 GEN
Solar/Wind Harmer
15.739
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.591
970569AG2-363 GEN
Solar/Wind Harmer
26.052
939741AE1-205 GEN
Solar/Wind Harmer
12.131
252510AF1-249 C
Solar/Wind Harmer
0.065
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.496
25196808ZIMRHP
Adder
93.029
25196008MFTGT1
Adder
1.696
276621W2-048 GEN
Solar/Wind Harmer
0.423
254303AC2-168 GEN
Solar/Wind Helper
0.198
961971AG1-040 GEN
Solar/Wind Helper
0.519
238126S14_GEN_1
Solar/Wind Helper
0.662
274693ROCKY RD ;1P
Adder
13.877
274683WAUKEGAN ;8U
Adder
26.494
274683WAUKEGAN ;8U
Adder
22.333
276876AE1-163_GEN2
Solar/Wind Harmer
0
25194408D.CRK1
Adder
9.396
972235AH1-702 GEN1
Adder
3.131
960611AF2-352 GEN
Solar/Wind Harmer
2.874
274764LEE CO EC;5U
Adder
11.523
945391AF1-204 GEN
Solar/Wind Harmer
9.138
276615X2-022 GEN
Solar/Wind Harmer
0.088
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
4.521
241972AD1-140 GEN
Solar/Wind Harmer
1.102
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.92
959331AF2-224 GEN
Solar/Wind Harmer
6.362
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.469
274776LINCOLN ;7U
Adder
10.86
270526AF1-158 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
3.493
965041AG1-368 GEN
Solar/Wind Harmer
8.914
963841AG1-237 GEN
Solar/Wind Harmer
3.86
274687WILL CNTY;4U
Adder
35.509
274687WILL CNTY;4U
Adder
35.509
274731ELWOOD EC;2P
Adder
20.872
274733ELWOOD EC;3P
Adder
20.872
274746AC1-111 G10
Adder
7.068
270356AE2-297 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.477
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.277
23750501ELLIOTTS
Solar/Wind Helper
0.695
20089126CSLMN_L13
Solar/Wind Helper
0.613
20088926STNY CRK
Solar/Wind Helper
0.849
20094526CT_V3-030
Solar/Wind Helper
0.494
20088626ARWF_N39
Solar/Wind Helper
1.24
20334926Z1-069 C
Solar/Wind Helper
1.403
238118U2-030_1
Solar/Wind Helper
0.283
946071AF1-272 GEN
Solar/Wind Helper
2.879
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
23585401KL_K28_T16
Solar/Wind Helper
1.267
238117U2-030
Solar/Wind Helper
0.283
270119AB2-067 GEN1
50/50
13.691
25326509SID D
50/50
1.895
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
3.637
24387305FR-4G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
10.86
274771LINCOLN ;2U
Adder
10.86
274805UNIV PK N;1U
Adder
6.41
274888KELLY CRK;1U
Solar/Wind Harmer
0.519
970941AG2-585 GEN
Solar/Wind Harmer
4.892
276897AD1-100 C
Solar/Wind Harmer
22.228
246937BC-WTG2
Solar/Wind Harmer
0.358
276893AG1-478 C
Solar/Wind Harmer
0.591
970241AG2-163 GEN
Solar/Wind Harmer
5.155
274697ROCKY RD ;3P
Adder
3.807
274696ROCKY RD ;4P
Adder
14.346
962691AG1-118 GEN
Solar/Wind Harmer
26.273
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.816
938861AE1-114 GEN
Solar/Wind Harmer
4.893
276645AC1-214 GEN1
Solar/Wind Harmer
0.338
274762LEE CO EC;3U
Adder
11.496
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.387
276838X2-022 GEN2
Solar/Wind Harmer
0.476
970623AG2-406 GEN
Solar/Wind Harmer
1.547
962581AG1-107 GEN
Solar/Wind Harmer
0.001
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
23751201ROTHROCK
Solar/Wind Helper
0.733
270156DARBY CT1
50/50
0.841
270157DARBY CT2
50/50
0.839
270459AD2-067 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
17.821
24729505KEY G4
Adder
8.54
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.262
971771AH1-392 GEN
Solar/Wind Harmer
8.94
270435AC2-044 GEN
Solar/Wind Harmer
1.124
274728ELWOOD EC;5P
Adder
20.872
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.922
276861AD2-134 GEN
Solar/Wind Harmer
0.155
276863AD2-134 GEN
Solar/Wind Harmer
0.155
25196408WSDLE3
Adder
10.988
270007AE1-245 C
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.202
971681AH1-341 GEN
Solar/Wind Harmer
13.904
25196108MFTGT2
Adder
1.87
25196108MFTGT2
Adder
1.736
241985AE1-237 GEN
Solar/Wind Helper
0.309
20089226LOOKOUT
Solar/Wind Helper
0.611
203940AF1-140 C
Solar/Wind Helper
0.411
NYPJM->LTFIMP_NY
CLTF
5.162
LGEELTFEXP_LGEE->PJM
CLTF
7.836
WECLTFEXP_WEC->PJM
CLTF
4.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.297
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446
CPLELTFEXP_CPLE->PJM
CLTF
2.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.765
MECLTFEXP_MEC->PJM
CLTF
19.491
SIGELTFEXP_SIGE->PJM
CLTF
0.599
LAGNLTFEXP_LAGN->PJM
CLTF
17.61
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.111
TVALTFEXP_TVA->PJM
CLTF
8.46

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.48 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4638.62
MW Contribution:
5.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
970155AG2-107 GEN
Solar/Wind Harmer
59.604
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.002
274827FISK ;RP
Adder
11.133
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972227AH1-698 GEN1
Adder
3.737
274735ELWOOD EC;4P
Adder
23.324
274744AC1-111 GEN8
Adder
7.861
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
963791AG1-232 GEN
Solar/Wind Harmer
12.673
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270063AE2-323 C
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
11.974
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
23.325
944531AF1-118 GEN
Solar/Wind Harmer
44.295
970781AG2-491 GEN
Solar/Wind Harmer
9.86
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
276868AE1-113 GEN
Solar/Wind Harmer
1.916
270142AC1-141 CT1_
50/50
3.606
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
274811UNIV PK N;7U
Adder
7.232
276806AD2-047 C O1
Solar/Wind Harmer
5.669
274676JOLIET 29;8U
Adder
42.062
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274682WAUKEGAN ;7U
Adder
24.977
959091AF2-200 GEN
Solar/Wind Harmer
18.917
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
970289AG2-191 GEN
Solar/Wind Harmer
0.995
971087AG2-675 GEN
Solar/Wind Harmer
4.746
957381AF2-032 GEN
Solar/Wind Harmer
1.851
946031AF1-268 GEN
Solar/Wind Harmer
7.675
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270102X2-052 ST
50/50
2.435
24643105BUCHANAN
50/50
0.019
970349AG2-230 GEN
Solar/Wind Harmer
16.401
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
274808UNIV PK N;4U
Adder
7.201
274674JOLIET 9 ;6U
Adder
21.855
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274693ROCKY RD ;1P
Adder
15.339
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.399
270247TR4_N_V136
Solar/Wind Harmer
0.06
274764LEE CO EC;5U
Adder
12.402
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
5.429
960611AF2-352 GEN
Solar/Wind Harmer
2.992
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
24725505WLD G2 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
8.566
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
274879MINONK ;1U
Solar/Wind Harmer
0.4
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.992
970193AG2-126 GEN
Solar/Wind Harmer
12.093
270541AE2-072 C
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
1.203
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
13.215
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276776AD2-060 GEN
Solar/Wind Harmer
1.067
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
270246TR4_N_V150
Solar/Wind Harmer
0.06
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
971613AH1-306 GEN
Solar/Wind Harmer
4.231
276916AD2-100_GEN
Solar/Wind Harmer
16.976
247621Y3-024
Adder
0.274
971587AH1-292 GEN
Solar/Wind Harmer
5.199
274812UNIV PK N;8U
Adder
7.232
274676JOLIET 29;8U
Adder
43.62
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
957471AF2-041 GEN
Solar/Wind Harmer
28.375
965651AG1-433 GEN
Solar/Wind Harmer
2.714
944961AF1-161 GEN
50/50
4.308
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274724RIVER EC ;11
Adder
25.717
972259AH1-714 GEN
Adder
27.313
274729ELWOOD EC;1P
Adder
23.324
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
970571AG2-364 GEN
Solar/Wind Harmer
18.75
246938BC-WTG3
Solar/Wind Harmer
0.328
971993AH1-541 GEN
Solar/Wind Harmer
3.947
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
970825AG2-519 GEN
Solar/Wind Harmer
6.118
270240V3-007_GEN2
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
2.25
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
276893AG1-478 C
Solar/Wind Harmer
0.66
274696ROCKY RD ;4P
Adder
15.857
274697ROCKY RD ;3P
Adder
4.208
962691AG1-118 GEN
Solar/Wind Harmer
28.923
24387305FR-4G C
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274762LEE CO EC;3U
Adder
12.373
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970241AG2-163 GEN
Solar/Wind Harmer
5.219
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
276838X2-022 GEN2
Solar/Wind Harmer
0.473
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270475AD2-096_GEN
50/50
9.997
24642205MAYFLWER
50/50
0.055
962601AG1-109 GEN
50/50
4.308
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274753CRETE EC ;3U
Adder
11.974
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274803UNIV PARK;6U
Adder
8.371
276843GEN-1.7
Solar/Wind Harmer
0.323
972038AH1-567 GEN2
Adder
0.523
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
965091AG1-374 GEN
Solar/Wind Harmer
26.927
965931AG1-462 GEN
Solar/Wind Harmer
22.694
270004AE1-209 GEN
Solar/Wind Harmer
1.763
24379505HDWTR1G C
Solar/Wind Harmer
0
270101X2-052 CT2
50/50
2.25
247620Y3-023
50/50
0.727
965791AG1-447 GEN
Solar/Wind Harmer
9.691
945421AF1-207 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
14.407
270180AB1-006 GEN1
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
15.492
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.955
274765LEE CO EC;6U
Adder
12.402
274763LEE CO EC;4U
Adder
12.256
944541AF1-119 GEN
Solar/Wind Harmer
0.618
270031AE2-169
Solar/Wind Harmer
4.725
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276911AD2-131_GEN
Solar/Wind Harmer
1.118
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.468
962761AG1-125 GEN
Solar/Wind Harmer
93.339
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
11.974
274802UNIV PARK;5U
Adder
8.371
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
939401AE1-172 GEN
Solar/Wind Harmer
7.225
962781AG1-127 GEN
Solar/Wind Harmer
9.154
24385905FR-11G C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
276708O09 GEN2
Solar/Wind Harmer
0.324
276903AD2-071 C
Solar/Wind Harmer
9.571
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270437AC2-090 C
Solar/Wind Harmer
0
24344005CKG1
50/50
9.721
24641605TWIN BRNCH
50/50
0.026
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
960591AF2-350 GEN
Solar/Wind Harmer
10.005
972228AH1-698 GEN2
Adder
5.307
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
965051AG1-369 GEN
Solar/Wind Harmer
4.689
972267AH1-718 GEN
Adder
5.487
274853TWINGROVE;U1
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.309
971029AG2-637 GEN
Solar/Wind Harmer
10.57
24344105CKG2
50/50
12.076
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970373AG2-245 GEN
Solar/Wind Harmer
21.825
943021AE2-325 GEN
Solar/Wind Harmer
5.398
971917AH1-482 GEN
Solar/Wind Harmer
13.304
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
21.176
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
270144AC1-141 ST1_
50/50
3.196
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
12.383
959331AF2-224 GEN
Solar/Wind Harmer
7.14
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274746AC1-111 G10
Adder
7.861
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
965041AG1-368 GEN
Solar/Wind Harmer
9.581
926823AC1-168 GEN
Solar/Wind Harmer
1.594
963841AG1-237 GEN
Solar/Wind Harmer
3.99
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
270356AE2-297 GEN
Solar/Wind Harmer
0
24307105BERRINSP G
50/50
0.032
957891AF2-083 GEN
Solar/Wind Harmer
17.358
945111AF1-176 GEN
Solar/Wind Harmer
18.541
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24386605FR-22G C
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
939741AE1-205 GEN
Solar/Wind Harmer
12.763
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.421
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
971771AH1-392 GEN
Solar/Wind Harmer
10.525
274728ELWOOD EC;5P
Adder
23.325
24691005MDL-2G C
Solar/Wind Harmer
0
24729505KEY G4
Adder
9.035
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270435AC2-044 GEN
Solar/Wind Harmer
1.153
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.183
965421AG1-410 GEN
Solar/Wind Harmer
27.632
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
23906502RICHG2&3
Adder
1.056
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.719
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4659.48
MW Contribution:
5.2
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
970155AG2-107 GEN
Solar/Wind Harmer
59.604
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.232
274676JOLIET 29;8U
Adder
43.62
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
957471AF2-041 GEN
Solar/Wind Harmer
28.375
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
23906502RICHG2&3
Adder
1.056
958391AF2-133 GEN
Solar/Wind Harmer
0.002
274827FISK ;RP
Adder
11.133
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972227AH1-698 GEN1
Adder
3.737
274735ELWOOD EC;4P
Adder
23.324
274744AC1-111 GEN8
Adder
7.861
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
963791AG1-232 GEN
Solar/Wind Harmer
12.673
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.719
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270063AE2-323 C
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
11.974
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
23.325
944531AF1-118 GEN
Solar/Wind Harmer
44.295
970781AG2-491 GEN
Solar/Wind Harmer
9.86
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.992
970193AG2-126 GEN
Solar/Wind Harmer
12.093
270541AE2-072 C
Solar/Wind Harmer
0
270142AC1-141 CT1_
50/50
3.606
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
274811UNIV PK N;7U
Adder
7.232
276806AD2-047 C O1
Solar/Wind Harmer
5.669
274676JOLIET 29;8U
Adder
42.062
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274682WAUKEGAN ;7U
Adder
24.977
959091AF2-200 GEN
Solar/Wind Harmer
18.917
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
970289AG2-191 GEN
Solar/Wind Harmer
0.995
971087AG2-675 GEN
Solar/Wind Harmer
4.746
957381AF2-032 GEN
Solar/Wind Harmer
1.851
946031AF1-268 GEN
Solar/Wind Harmer
7.675
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
944961AF1-161 GEN
50/50
4.308
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274724RIVER EC ;11
Adder
25.717
972259AH1-714 GEN
Adder
27.313
274729ELWOOD EC;1P
Adder
23.324
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
970571AG2-364 GEN
Solar/Wind Harmer
18.75
270102X2-052 ST
50/50
2.435
24643105BUCHANAN
50/50
0.019
970349AG2-230 GEN
Solar/Wind Harmer
16.401
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
274808UNIV PK N;4U
Adder
7.201
274674JOLIET 9 ;6U
Adder
21.855
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274693ROCKY RD ;1P
Adder
15.339
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.399
270247TR4_N_V136
Solar/Wind Harmer
0.06
274764LEE CO EC;5U
Adder
12.402
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
5.429
960611AF2-352 GEN
Solar/Wind Harmer
2.992
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
24725505WLD G2 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
8.566
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
270054AF2-122 C O1
Solar/Wind Helper
1.203
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
13.215
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276776AD2-060 GEN
Solar/Wind Harmer
1.067
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
270246TR4_N_V150
Solar/Wind Harmer
0.06
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
971613AH1-306 GEN
Solar/Wind Harmer
4.231
276916AD2-100_GEN
Solar/Wind Harmer
16.976
247621Y3-024
Adder
0.274
971587AH1-292 GEN
Solar/Wind Harmer
5.199
246938BC-WTG3
Solar/Wind Harmer
0.328
971993AH1-541 GEN
Solar/Wind Harmer
3.947
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
970825AG2-519 GEN
Solar/Wind Harmer
6.118
270240V3-007_GEN2
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
2.25
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
276893AG1-478 C
Solar/Wind Harmer
0.66
274696ROCKY RD ;4P
Adder
15.857
274697ROCKY RD ;3P
Adder
4.208
962691AG1-118 GEN
Solar/Wind Harmer
28.923
24387305FR-4G C
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274762LEE CO EC;3U
Adder
12.373
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970241AG2-163 GEN
Solar/Wind Harmer
5.219
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
276838X2-022 GEN2
Solar/Wind Harmer
0.473
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270475AD2-096_GEN
50/50
9.997
24642205MAYFLWER
50/50
0.055
962601AG1-109 GEN
50/50
4.308
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274753CRETE EC ;3U
Adder
11.974
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274803UNIV PARK;6U
Adder
8.371
276843GEN-1.7
Solar/Wind Harmer
0.323
972038AH1-567 GEN2
Adder
0.523
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
965091AG1-374 GEN
Solar/Wind Harmer
26.927
965931AG1-462 GEN
Solar/Wind Harmer
22.694
270004AE1-209 GEN
Solar/Wind Harmer
1.763
24379505HDWTR1G C
Solar/Wind Harmer
0
270101X2-052 CT2
50/50
2.25
247620Y3-023
50/50
0.727
965791AG1-447 GEN
Solar/Wind Harmer
9.691
945421AF1-207 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
14.407
270180AB1-006 GEN1
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
15.492
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.955
274765LEE CO EC;6U
Adder
12.402
274763LEE CO EC;4U
Adder
12.256
944541AF1-119 GEN
Solar/Wind Harmer
0.618
270031AE2-169
Solar/Wind Harmer
4.725
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276911AD2-131_GEN
Solar/Wind Harmer
1.118
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.468
24344105CKG2
50/50
12.076
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970373AG2-245 GEN
Solar/Wind Harmer
21.825
943021AE2-325 GEN
Solar/Wind Harmer
5.398
971917AH1-482 GEN
Solar/Wind Harmer
13.304
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
93.339
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
11.974
274802UNIV PARK;5U
Adder
8.371
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
939401AE1-172 GEN
Solar/Wind Harmer
7.225
962781AG1-127 GEN
Solar/Wind Harmer
9.154
24385905FR-11G C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
276708O09 GEN2
Solar/Wind Harmer
0.324
276903AD2-071 C
Solar/Wind Harmer
9.571
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270437AC2-090 C
Solar/Wind Harmer
0
24344005CKG1
50/50
9.721
24641605TWIN BRNCH
50/50
0.026
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
960591AF2-350 GEN
Solar/Wind Harmer
10.005
972228AH1-698 GEN2
Adder
5.307
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
965051AG1-369 GEN
Solar/Wind Harmer
4.689
972267AH1-718 GEN
Adder
5.487
274853TWINGROVE;U1
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.309
971029AG2-637 GEN
Solar/Wind Harmer
10.57
276882AE2-255 GEN
Solar/Wind Harmer
1.118
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
21.176
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
270144AC1-141 ST1_
50/50
3.196
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
12.383
959331AF2-224 GEN
Solar/Wind Harmer
7.14
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274746AC1-111 G10
Adder
7.861
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
965041AG1-368 GEN
Solar/Wind Harmer
9.581
926823AC1-168 GEN
Solar/Wind Harmer
1.594
963841AG1-237 GEN
Solar/Wind Harmer
3.99
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
270356AE2-297 GEN
Solar/Wind Harmer
0
24307105BERRINSP G
50/50
0.032
957891AF2-083 GEN
Solar/Wind Harmer
17.358
945111AF1-176 GEN
Solar/Wind Harmer
18.541
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24386605FR-22G C
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
939741AE1-205 GEN
Solar/Wind Harmer
12.763
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.421
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
971771AH1-392 GEN
Solar/Wind Harmer
10.525
274728ELWOOD EC;5P
Adder
23.325
24691005MDL-2G C
Solar/Wind Harmer
0
24729505KEY G4
Adder
9.035
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270435AC2-044 GEN
Solar/Wind Harmer
1.153
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.183
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.92 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5008.41
MW Contribution:
5.41
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24642205MAYFLWER
50/50
0.069
962601AG1-109 GEN
50/50
5.371
274753CRETE EC ;3U
Adder
14.913
274814UNIV PK N;0U
Adder
9.09
274807UNIV PK N;3U
Adder
9.07
274803UNIV PARK;6U
Adder
10.432
276843GEN-1.7
Solar/Wind Harmer
0.403
972038AH1-567 GEN2
Adder
0.652
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
15.212
274878BISHOP HL;2U
Solar/Wind Harmer
0.372
971347AH1-153 GEN
Solar/Wind Harmer
7.007
270063AE2-323 C
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
14.913
944531AF1-118 GEN
Solar/Wind Harmer
56.246
970707AG2-453 GEN
Solar/Wind Harmer
40.893
24690905MDL-1G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
27.64
965091AG1-374 GEN
Solar/Wind Harmer
32.301
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.995
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.903
965681AG1-436 GEN
Solar/Wind Harmer
16.554
276776AD2-060 GEN
Solar/Wind Harmer
1.331
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270142AC1-141 CT1_
50/50
4.53
274811UNIV PK N;7U
Adder
9.011
276806AD2-047 C O1
Solar/Wind Harmer
7.069
274676JOLIET 29;8U
Adder
52.392
274734ELWOOD EC;8P
Adder
29.026
274736ELWOOD EC;9P
Adder
29.026
943121AE2-341 GEN
Solar/Wind Harmer
20.51
943591AF1-030 GEN
Solar/Wind Harmer
13.64
274682WAUKEGAN ;7U
Adder
30.998
959091AF2-200 GEN
Solar/Wind Harmer
23.357
274827FISK ;RP
Adder
13.882
274800UNIV PARK;3U
Adder
10.418
274801UNIV PARK;4U
Adder
10.418
972227AH1-698 GEN1
Adder
4.661
274735ELWOOD EC;4P
Adder
29.025
24344005CKG1
50/50
12.247
24641605TWIN BRNCH
50/50
0.032
274775LINCOLN ;6U
50/50
16.554
274777LINCOLN ;8U
50/50
16.554
970031AG2-029 GEN
Solar/Wind Harmer
6.772
972037AH1-567 GEN1
Adder
0.327
960591AF2-350 GEN
Solar/Wind Harmer
12.474
972228AH1-698 GEN2
Adder
6.619
274675JOLIET 29;7U
Adder
54.333
274675JOLIET 29;7U
Adder
52.393
970833AG2-524 GEN
Solar/Wind Harmer
13.528
970833AG2-524 GEN
Solar/Wind Harmer
9.019
971411AH1-196 GEN
Solar/Wind Harmer
17.649
971675AH1-338 GEN
Solar/Wind Harmer
4.588
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
23.357
274823ROCKFORD ;21
Adder
32.492
971611AH1-305 GEN
Solar/Wind Harmer
6.874
972267AH1-718 GEN
Adder
6.732
946321AF1-296 GEN
Solar/Wind Harmer
6.109
274853TWINGROVE;U1
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
4.503
247536S-71 GEN
Solar/Wind Harmer
0.321
971029AG2-637 GEN
Solar/Wind Harmer
10.12
270102X2-052 ST
50/50
3.058
24643105BUCHANAN
50/50
0.024
970349AG2-230 GEN
Solar/Wind Harmer
21.02
961051AF2-396 GEN
Solar/Wind Harmer
25.827
961051AF2-396 GEN
Solar/Wind Harmer
17.218
274808UNIV PK N;4U
Adder
8.972
274674JOLIET 9 ;6U
Adder
27.209
274693ROCKY RD ;1P
Adder
19.046
958481AF2-142 GEN
Solar/Wind Harmer
18.073
274683WAUKEGAN ;8U
Adder
36.293
274683WAUKEGAN ;8U
Adder
30.593
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.192
274764LEE CO EC;5U
Adder
15.248
960971AF2-388 GEN
Solar/Wind Harmer
6.656
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
3.589
966841AG1-555 GEN
Solar/Wind Harmer
1.188
944231AF1-091 GEN
Solar/Wind Harmer
23.789
276615X2-022 GEN
Solar/Wind Harmer
0.102
270599AE1-208 GEN
Solar/Wind Harmer
8.982
270247TR4_N_V136
Solar/Wind Harmer
0.058
24725505WLD G2 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
9.248
926881AC1-175 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
50/50
16.554
944961AF1-161 GEN
50/50
5.371
270043AE2-236 GEN
Solar/Wind Harmer
8.609
270505AE1-170 C O1
Solar/Wind Harmer
13.688
945111AF1-176 GEN
Solar/Wind Harmer
10.497
274724RIVER EC ;11
Adder
32.107
972259AH1-714 GEN
Adder
34.103
274729ELWOOD EC;1P
Adder
29.025
946671AF1-331 GEN
Solar/Wind Harmer
1.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.137
965021AG1-366 GEN
Solar/Wind Harmer
3.873
970571AG2-364 GEN
Solar/Wind Harmer
23.003
971993AH1-541 GEN
Solar/Wind Harmer
4.642
942481AE2-261 GEN
Solar/Wind Harmer
28.217
970825AG2-519 GEN
Solar/Wind Harmer
6.765
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.208
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.25
24653605MOTTVILLE
50/50
0.007
971771AH1-392 GEN
Solar/Wind Harmer
13.194
270071AF1-092 GEN
Solar/Wind Harmer
24.953
274728ELWOOD EC;5P
Adder
29.026
24729505KEY G4
Adder
11.373
970073AG2-061 GEN
Solar/Wind Harmer
3.962
276861AD2-134 GEN
Solar/Wind Harmer
0.21
276863AD2-134 GEN
Solar/Wind Harmer
0.21
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
24.093
274856ECOGROVE ;U1
Solar/Wind Harmer
0.27
971681AH1-341 GEN
Solar/Wind Harmer
18.454
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.19
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.88
274773LINCOLN ;4U
50/50
16.554
274774LINCOLN ;5U
50/50
16.554
24307105BERRINSP G
50/50
0.04
957891AF2-083 GEN
Solar/Wind Harmer
21.685
945111AF1-176 GEN
Solar/Wind Harmer
23.109
274723RIVER EC ;12
Adder
32.481
274751CRETE EC ;1U
Adder
14.913
964861AG1-349 GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
6.189
965011AG1-365 GEN
Solar/Wind Harmer
11.618
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
14.433
970569AG2-363 GEN
Solar/Wind Harmer
34.504
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
15.212
958861AF2-177 GEN
Solar/Wind Harmer
4.79
939741AE1-205 GEN
Solar/Wind Harmer
15.389
945371AF1-202 GEN
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.492
270594AE1-207 GEN
Solar/Wind Harmer
10.763
270032AE2-172
Solar/Wind Harmer
6.407
270005AE1-210 C O1
Solar/Wind Harmer
1.995
970825AG2-519 GEN
Solar/Wind Harmer
3.188
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.28
270489AE1-102 GEN1
Solar/Wind Harmer
0.903
274744AC1-111 GEN8
Adder
9.782
958391AF2-133 GEN
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
11.475
270143AC1-141 CT2_
50/50
4.53
24639705ELKHART HY
50/50
0.302
970521AG2-332 GEN
50/50
21.475
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
274812UNIV PK N;8U
Adder
9.011
274676JOLIET 29;8U
Adder
54.332
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.782
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
30.998
274828WAUKEGAN ;BP
Adder
19.024
957471AF2-041 GEN
Solar/Wind Harmer
35.035
965651AG1-433 GEN
Solar/Wind Harmer
3.328
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.023
24728605AND G2
Adder
4.166
965421AG1-410 GEN
Solar/Wind Harmer
22.186
970883AG2-550 GEN
Solar/Wind Harmer
7.415
270054AF2-122 C O1
Solar/Wind Helper
1.32
274826FISK ;BP
Adder
19.587
274887GEN-1.85
Solar/Wind Harmer
0.324
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
29.026
274862TOP CROP ;2U
Solar/Wind Harmer
1.626
276868AE1-113 GEN
Solar/Wind Harmer
2.364
274879MINONK ;1U
Solar/Wind Harmer
0.493
274855GSG-6 ;RU
Solar/Wind Harmer
0.429
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.946
959611AF2-252 GEN
Solar/Wind Harmer
3.589
970193AG2-126 GEN
Solar/Wind Harmer
13.057
270287AF1-227 GEN3
Solar/Wind Helper
0.817
270100X2-052 CT1
50/50
2.825
274770LINCOLN ;1U
50/50
16.554
274771LINCOLN ;2U
50/50
16.554
274805UNIV PK N;1U
Adder
9.031
274888KELLY CRK;1U
Solar/Wind Harmer
0.727
970941AG2-585 GEN
Solar/Wind Harmer
6.861
276897AD1-100 C
Solar/Wind Harmer
31.049
276893AG1-478 C
Solar/Wind Harmer
0.821
274697ROCKY RD ;3P
Adder
5.225
274696ROCKY RD ;4P
Adder
19.689
962691AG1-118 GEN
Solar/Wind Harmer
35.867
938861AE1-114 GEN
Solar/Wind Harmer
6.492
274762LEE CO EC;3U
Adder
15.212
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.814
276645AC1-214 GEN1
Solar/Wind Harmer
0.44
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
3.572
942221AE2-234 GEN
Solar/Wind Harmer
4.268
24387305FR-4G C
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.554
970241AG2-163 GEN
Solar/Wind Harmer
5.718
970623AG2-406 GEN
Solar/Wind Harmer
1.371
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.28
270101X2-052 CT2
50/50
2.825
247620Y3-023
50/50
0.898
965791AG1-447 GEN
Solar/Wind Harmer
12.14
958011AF2-095 GEN
Solar/Wind Harmer
17.963
274695ROCKY RD ;2P
Adder
19.235
958491AF2-143 GEN
Solar/Wind Harmer
17.827
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
3.645
274765LEE CO EC;6U
Adder
15.248
274763LEE CO EC;4U
Adder
15.069
944541AF1-119 GEN
Solar/Wind Harmer
0.758
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
5.389
276911AD2-131_GEN
Solar/Wind Harmer
1.292
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.661
270201AC2-176 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.472
946101AF1-275 GEN
Solar/Wind Helper
0.65
24344105CKG2
50/50
15.733
943021AE2-325 GEN
Solar/Wind Harmer
6.729
970373AG2-245 GEN
Solar/Wind Harmer
26.204
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.958
274861TOP CROP ;1U
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
15.475
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.379
959081AF2-199 GEN
Solar/Wind Harmer
11.678
971067AG2-660 GEN
Solar/Wind Harmer
3.893
274822ROCKFORD ;11
Adder
32.73
970819AG2-516 GEN
Solar/Wind Harmer
13.872
276646AC1-214 GEN2
Solar/Wind Harmer
0.44
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
23.2
970773AG2-487 GEN
Solar/Wind Harmer
1.206
970091AG2-072 GEN
Adder
67.129
270286AF1-227 GEN2
Solar/Wind Helper
0.817
270144AC1-141 ST1_
50/50
4.015
274776LINCOLN ;7U
50/50
16.554
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
49.553
274687WILL CNTY;4U
Adder
49.553
274731ELWOOD EC;2P
Adder
29.025
274733ELWOOD EC;3P
Adder
29.025
274746AC1-111 G10
Adder
9.782
959331AF2-224 GEN
Solar/Wind Harmer
8.133
926823AC1-168 GEN
Solar/Wind Harmer
1.955
276726Z2-087_GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.388
965041AG1-368 GEN
Solar/Wind Harmer
9.911
971609AH1-304 GEN
Solar/Wind Harmer
1.601
944221AF1-090 GEN
Solar/Wind Harmer
5.281
964611AG1-324 GEN
Solar/Wind Harmer
3.439
270356AE2-297 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.397
274877BISHOP HL;1U
Solar/Wind Harmer
0.372
959341AF2-225 GEN
Solar/Wind Harmer
11.542
963791AG1-232 GEN
Solar/Wind Harmer
14.195
276668AB2-070 GEN1
Solar/Wind Harmer
0.395
276848AB2-070 GEN3
Solar/Wind Harmer
0.393
276849AB2-070 GEN2
Solar/Wind Harmer
0.395
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.868
247521TR3_G114
Solar/Wind Harmer
0.327
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0.001
274767LEE CO EC;8U
Adder
15.033
971087AG2-675 GEN
Solar/Wind Harmer
5.781
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.081
957381AF2-032 GEN
Solar/Wind Harmer
2.147
946031AF1-268 GEN
Solar/Wind Harmer
8.435
24695305TIMB G C
Solar/Wind Harmer
0.74
24728505AND G1
Adder
4.166
270284AF1-227 GEN1
Solar/Wind Helper
2.228
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
23.357
971343AH1-151 GEN
Solar/Wind Harmer
23.357
970291AG2-192 GEN
Solar/Wind Harmer
1.278
970291AG2-192 GEN
Solar/Wind Harmer
0.59
971613AH1-306 GEN
Solar/Wind Harmer
4.613
276916AD2-100_GEN
Solar/Wind Harmer
19.611
270246TR4_N_V150
Solar/Wind Harmer
0.058
247621Y3-024
Adder
0.288
971587AH1-292 GEN
Solar/Wind Harmer
5.408
274754CRETE EC ;4U
Adder
14.913
274802UNIV PARK;5U
Adder
10.432
274674JOLIET 9 ;6U
Adder
27.209
274732ELWOOD EC;7P
Adder
29.026
958381AF2-132 GEN
Solar/Wind Harmer
0.002
962781AG1-127 GEN
Solar/Wind Harmer
11.346
939401AE1-172 GEN
Solar/Wind Harmer
8.909
274766LEE CO EC;7U
Adder
15.033
276708O09 GEN2
Solar/Wind Harmer
0.397
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.887
276903AD2-071 C
Solar/Wind Harmer
10.328
270437AC2-090 C
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Helper
2.6
270349AD2-093_GEN
Solar/Wind Helper
1.835
270471AD2-092_GEN
Solar/Wind Helper
1.835
NYPJM->LTFIMP_NY
CLTF
2.831
LGEELTFEXP_LGEE->PJM
CLTF
3.802
WECLTFEXP_WEC->PJM
CLTF
6.34
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.778
AG2-052LTFEXP_AG2-052->PJM
LTF
0.395
AH1-155LTFEXP_AH1-155->PJM
LTF
0.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.518
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.577
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.817
MECLTFEXP_MEC->PJM
CLTF
22.833
SIGELTFEXP_SIGE->PJM
CLTF
0.424
LAGNLTFEXP_LAGN->PJM
CLTF
12.121
TVALTFEXP_TVA->PJM
CLTF
4.571

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#XXXX_MARYSVILLE_TEDDY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#XXXX_MARYSVILLE_TEDDY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4227.07
MW Contribution:
4.56
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270143AC1-141 CT2_
50/50
4.046
24639705ELKHART HY
50/50
0.271
970521AG2-332 GEN
50/50
19.228
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
274812UNIV PK N;8U
Adder
7.96
274676JOLIET 29;8U
Adder
47.996
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
8.641
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
27.371
274828WAUKEGAN ;BP
Adder
16.798
965651AG1-433 GEN
Solar/Wind Harmer
3.09
270055AF2-134 C O1
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
30.913
971347AH1-153 GEN
Solar/Wind Harmer
6.242
944531AF1-118 GEN
Solar/Wind Harmer
52.355
270063AE2-323 C
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
13.171
970707AG2-453 GEN
Solar/Wind Harmer
36.15
274826FISK ;BP
Adder
17.307
274887GEN-1.85
Solar/Wind Harmer
0.287
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
25.635
274862TOP CROP ;2U
Solar/Wind Harmer
1.435
276868AE1-113 GEN
Solar/Wind Harmer
2.085
24344105CKG2
50/50
14.029
943021AE2-325 GEN
Solar/Wind Harmer
6.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
22.649
276691AA1-018 GEN1
Solar/Wind Harmer
1.728
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.586
965421AG1-410 GEN
Solar/Wind Harmer
20.662
24728605AND G2
Adder
3.684
274827FISK ;RP
Adder
12.265
274800UNIV PARK;3U
Adder
9.204
274801UNIV PARK;4U
Adder
9.204
972227AH1-698 GEN1
Adder
4.117
274735ELWOOD EC;4P
Adder
25.635
274744AC1-111 GEN8
Adder
8.641
970169AG2-114 GEN
Solar/Wind Harmer
10.094
958391AF2-133 GEN
Solar/Wind Harmer
0.002
276741O09 GEN1
Solar/Wind Harmer
0.35
274877BISHOP HL;1U
Solar/Wind Harmer
0.327
963791AG1-232 GEN
Solar/Wind Harmer
13.114
959341AF2-225 GEN
Solar/Wind Harmer
10.125
276668AB2-070 GEN1
Solar/Wind Harmer
0.345
276848AB2-070 GEN3
Solar/Wind Harmer
0.343
276849AB2-070 GEN2
Solar/Wind Harmer
0.345
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.612
247521TR3_G114
Solar/Wind Harmer
0.304
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274879MINONK ;1U
Solar/Wind Harmer
0.435
274855GSG-6 ;RU
Solar/Wind Harmer
0.379
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
3.146
970781AG2-491 GEN
Solar/Wind Harmer
9.067
970193AG2-126 GEN
Solar/Wind Harmer
11.081
270287AF1-227 GEN3
Solar/Wind Helper
0.767
270102X2-052 ST
50/50
2.706
24643105BUCHANAN
50/50
0.021
970349AG2-230 GEN
Solar/Wind Harmer
18.725
961051AF2-396 GEN
Solar/Wind Harmer
23.062
961051AF2-396 GEN
Solar/Wind Harmer
15.375
274808UNIV PK N;4U
Adder
7.925
274674JOLIET 9 ;6U
Adder
24.034
274693ROCKY RD ;1P
Adder
16.818
958481AF2-142 GEN
Solar/Wind Harmer
15.95
274683WAUKEGAN ;8U
Adder
32.045
274683WAUKEGAN ;8U
Adder
27.013
270142AC1-141 CT1_
50/50
4.046
274811UNIV PK N;7U
Adder
7.96
276806AD2-047 C O1
Solar/Wind Harmer
6.245
274676JOLIET 29;8U
Adder
46.282
274734ELWOOD EC;8P
Adder
25.635
274736ELWOOD EC;9P
Adder
25.635
943121AE2-341 GEN
Solar/Wind Harmer
18.119
943591AF1-030 GEN
Solar/Wind Harmer
12.05
274682WAUKEGAN ;7U
Adder
27.371
959091AF2-200 GEN
Solar/Wind Harmer
20.608
274767LEE CO EC;8U
Adder
13.257
971087AG2-675 GEN
Solar/Wind Harmer
5.091
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.933
957381AF2-032 GEN
Solar/Wind Harmer
1.87
946031AF1-268 GEN
Solar/Wind Harmer
7.751
24695305TIMB G C
Solar/Wind Harmer
0.688
24728505AND G1
Adder
3.684
270284AF1-227 GEN1
Solar/Wind Helper
2.091
270100X2-052 CT1
50/50
2.499
274770LINCOLN ;1U
50/50
14.651
274771LINCOLN ;2U
50/50
14.651
274805UNIV PK N;1U
Adder
7.977
274888KELLY CRK;1U
Solar/Wind Harmer
0.643
970941AG2-585 GEN
Solar/Wind Harmer
6.061
276897AD1-100 C
Solar/Wind Harmer
27.426
276893AG1-478 C
Solar/Wind Harmer
0.725
274697ROCKY RD ;3P
Adder
4.614
274696ROCKY RD ;4P
Adder
17.386
962691AG1-118 GEN
Solar/Wind Harmer
31.666
938861AE1-114 GEN
Solar/Wind Harmer
5.726
274762LEE CO EC;3U
Adder
13.415
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.599
276645AC1-214 GEN1
Solar/Wind Harmer
0.387
942221AE2-234 GEN
Solar/Wind Harmer
3.917
944961AF1-161 GEN
50/50
4.795
274772LINCOLN ;3U
50/50
14.651
270043AE2-236 GEN
Solar/Wind Harmer
7.894
270505AE1-170 C O1
Solar/Wind Harmer
12.22
945111AF1-176 GEN
Solar/Wind Harmer
9.378
274724RIVER EC ;11
Adder
28.38
972259AH1-714 GEN
Adder
30.137
274729ELWOOD EC;1P
Adder
25.635
965021AG1-366 GEN
Solar/Wind Harmer
3.589
946671AF1-331 GEN
Solar/Wind Harmer
1.108
274850MENDOTA H;RU
Solar/Wind Harmer
0.121
970571AG2-364 GEN
Solar/Wind Harmer
20.267
971993AH1-541 GEN
Solar/Wind Harmer
4.053
970825AG2-519 GEN
Solar/Wind Harmer
6.192
942481AE2-261 GEN
Solar/Wind Harmer
24.574
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.174
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.233
960971AF2-388 GEN
Solar/Wind Harmer
6.18
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.698
274764LEE CO EC;5U
Adder
13.446
944231AF1-091 GEN
Solar/Wind Harmer
21.915
960611AF2-352 GEN
Solar/Wind Harmer
3.146
24697605MDL-3G C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
8.214
966841AG1-555 GEN
Solar/Wind Harmer
0.987
276615X2-022 GEN
Solar/Wind Harmer
0.089
270247TR4_N_V136
Solar/Wind Harmer
0.054
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.849
970883AG2-550 GEN
Solar/Wind Harmer
6.922
965681AG1-436 GEN
Solar/Wind Harmer
14.637
276776AD2-060 GEN
Solar/Wind Harmer
1.176
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
20.608
971343AH1-151 GEN
Solar/Wind Harmer
20.608
970291AG2-192 GEN
Solar/Wind Harmer
1.103
970291AG2-192 GEN
Solar/Wind Harmer
0.509
971613AH1-306 GEN
Solar/Wind Harmer
4.035
270246TR4_N_V150
Solar/Wind Harmer
0.054
276916AD2-100_GEN
Solar/Wind Harmer
17.071
247621Y3-024
Adder
0.267
971587AH1-292 GEN
Solar/Wind Harmer
4.56
270349AD2-093_GEN
Solar/Wind Helper
1.727
270471AD2-092_GEN
Solar/Wind Helper
1.727
942111AE2-223 GEN
Solar/Wind Harmer
3.134
957841AF2-078 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.483
970241AG2-163 GEN
Solar/Wind Harmer
4.786
970623AG2-406 GEN
Solar/Wind Harmer
1.277
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.261
270144AC1-141 ST1_
50/50
3.585
274776LINCOLN ;7U
50/50
14.651
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24642205MAYFLWER
50/50
0.061
962601AG1-109 GEN
50/50
4.795
274753CRETE EC ;3U
Adder
13.171
274814UNIV PK N;0U
Adder
8.029
274807UNIV PK N;3U
Adder
8.012
274803UNIV PARK;6U
Adder
9.216
276843GEN-1.7
Solar/Wind Harmer
0.356
972038AH1-567 GEN2
Adder
0.576
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
13.415
274878BISHOP HL;2U
Solar/Wind Harmer
0.327
965931AG1-462 GEN
Solar/Wind Harmer
24.341
965091AG1-374 GEN
Solar/Wind Harmer
28.311
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.841
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.842
270101X2-052 CT2
50/50
2.499
247620Y3-023
50/50
0.805
965791AG1-447 GEN
Solar/Wind Harmer
10.734
958011AF2-095 GEN
Solar/Wind Harmer
15.87
274695ROCKY RD ;2P
Adder
16.985
944541AF1-119 GEN
Solar/Wind Harmer
0.704
958491AF2-143 GEN
Solar/Wind Harmer
15.725
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
3.216
274765LEE CO EC;6U
Adder
13.446
274763LEE CO EC;4U
Adder
13.288
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.929
276911AD2-131_GEN
Solar/Wind Harmer
1.124
964611AG1-324 GEN
Solar/Wind Harmer
0.609
270201AC2-176 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.307
959081AF2-199 GEN
Solar/Wind Harmer
10.304
971067AG2-660 GEN
Solar/Wind Harmer
3.435
274822ROCKFORD ;11
Adder
28.877
970819AG2-516 GEN
Solar/Wind Harmer
12.238
971917AH1-482 GEN
Solar/Wind Harmer
13.141
276646AC1-214 GEN2
Solar/Wind Harmer
0.387
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
19.419
970773AG2-487 GEN
Solar/Wind Harmer
1.103
270286AF1-227 GEN2
Solar/Wind Helper
0.767
274754CRETE EC ;4U
Adder
13.171
274802UNIV PARK;5U
Adder
9.216
274674JOLIET 9 ;6U
Adder
24.034
274732ELWOOD EC;7P
Adder
25.635
962781AG1-127 GEN
Solar/Wind Harmer
10.016
939401AE1-172 GEN
Solar/Wind Harmer
7.852
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274766LEE CO EC;7U
Adder
13.257
276708O09 GEN2
Solar/Wind Harmer
0.35
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.644
276903AD2-071 C
Solar/Wind Harmer
9.03
270437AC2-090 C
Solar/Wind Harmer
0
24344005CKG1
50/50
10.917
24641605TWIN BRNCH
50/50
0.029
274775LINCOLN ;6U
50/50
14.651
274777LINCOLN ;8U
50/50
14.651
970031AG2-029 GEN
Solar/Wind Harmer
6.135
972037AH1-567 GEN1
Adder
0.289
960591AF2-350 GEN
Solar/Wind Harmer
11.021
972228AH1-698 GEN2
Adder
5.848
274675JOLIET 29;7U
Adder
47.997
274675JOLIET 29;7U
Adder
46.283
970833AG2-524 GEN
Solar/Wind Harmer
11.948
970833AG2-524 GEN
Solar/Wind Harmer
7.965
971411AH1-196 GEN
Solar/Wind Harmer
15.576
971675AH1-338 GEN
Solar/Wind Harmer
4.049
971171AH1-044 GEN
Solar/Wind Harmer
20.608
274823ROCKFORD ;21
Adder
28.668
972267AH1-718 GEN
Adder
5.934
959141AF2-205 GEN
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
5.767
946321AF1-296 GEN
Solar/Wind Harmer
5.381
274853TWINGROVE;U1
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
4.187
247536S-71 GEN
Solar/Wind Harmer
0.298
971029AG2-637 GEN
Solar/Wind Harmer
9.523
274687WILL CNTY;4U
Adder
43.775
274687WILL CNTY;4U
Adder
43.775
274731ELWOOD EC;2P
Adder
25.635
274733ELWOOD EC;3P
Adder
25.635
274746AC1-111 G10
Adder
8.641
959331AF2-224 GEN
Solar/Wind Harmer
7.537
926823AC1-168 GEN
Solar/Wind Harmer
1.722
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
9.194
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.464
963841AG1-237 GEN
Solar/Wind Harmer
3.66
964611AG1-324 GEN
Solar/Wind Harmer
3.168
944221AF1-090 GEN
Solar/Wind Harmer
4.588
270356AE2-297 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
50/50
14.651
274774LINCOLN ;5U
50/50
14.651
24307105BERRINSP G
50/50
0.035
957891AF2-083 GEN
Solar/Wind Harmer
19.358
945111AF1-176 GEN
Solar/Wind Harmer
20.644
274723RIVER EC ;12
Adder
28.708
274751CRETE EC ;1U
Adder
13.171
965011AG1-365 GEN
Solar/Wind Harmer
10.767
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.458
958861AF2-177 GEN
Solar/Wind Harmer
4.445
970569AG2-363 GEN
Solar/Wind Harmer
30.401
964861AG1-349 GEN
Solar/Wind Harmer
0.001
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
13.415
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.109
939741AE1-205 GEN
Solar/Wind Harmer
13.5
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.43
270005AE1-210 C O1
Solar/Wind Harmer
1.841
270594AE1-207 GEN
Solar/Wind Harmer
9.414
270032AE2-172
Solar/Wind Harmer
5.604
970825AG2-519 GEN
Solar/Wind Harmer
2.918
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.261
270489AE1-102 GEN1
Solar/Wind Harmer
0.842
24653605MOTTVILLE
50/50
0.006
971771AH1-392 GEN
Solar/Wind Harmer
11.755
270071AF1-092 GEN
Solar/Wind Harmer
22.438
24729505KEY G4
Adder
10.579
274728ELWOOD EC;5P
Adder
25.635
970073AG2-061 GEN
Solar/Wind Harmer
3.495
971549AH1-272 GEN
Solar/Wind Harmer
21.564
276861AD2-134 GEN
Solar/Wind Harmer
0.185
276863AD2-134 GEN
Solar/Wind Harmer
0.185
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.238
971681AH1-341 GEN
Solar/Wind Harmer
16.274
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.846
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.82
NYPJM->LTFIMP_NY
CLTF
2.548
LGEELTFEXP_LGEE->PJM
CLTF
3.406
WECLTFEXP_WEC->PJM
CLTF
5.594
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.738
AG2-052LTFEXP_AG2-052->PJM
LTF
0.346
AH1-155LTFEXP_AH1-155->PJM
LTF
0.518
CBM West 2LTFEXP_CBM-W2->PJM
CBM
95.278
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.604
MECLTFEXP_MEC->PJM
CLTF
20.061
SIGELTFEXP_SIGE->PJM
CLTF
0.371
LAGNLTFEXP_LAGN->PJM
CLTF
10.559
TVALTFEXP_TVA->PJM
CLTF
3.978

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1280.85
MW Contribution:
2.38
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.63 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1362.91
MW Contribution:
2.6
Bus #Bus NameTypeMW Contribution
270273AD2-016 GEN
Solar/Wind Harmer
0.596
25326309TAIT D
Adder
0.805
3429241JKCT 3G
Adder
8.287
270437AC2-090 C
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.004
276903AD2-071 C
Solar/Wind Harmer
3.979
252516AE2-318_GEN
Solar/Wind Harmer
7.932
25194608D.CRK4
Adder
1.604
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.761
945681AF1-233 GEN
Solar/Wind Harmer
11.543
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
970613AG2-401 GEN
Solar/Wind Harmer
3.158
24728605AND G2
Adder
2.173
270024AE2-089 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.985
964901AG1-354 GEN
Solar/Wind Harmer
4.987
971191AH1-055 GEN
Solar/Wind Harmer
68.884
25196008MFTGT1
Adder
1.242
253394AE2-221_GEN
Solar/Wind Harmer
0.001
972167AH1-666 GEN
Solar/Wind Harmer
4.919
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
3.867
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.902
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.389
252507AC2-088 GEN
Solar/Wind Harmer
0.343
25196608WSDLE5
Adder
8.356
958171AF2-111 GEN
Solar/Wind Harmer
16.332
3429391JKCT 9G
Adder
6.006
970193AG2-126 GEN
Solar/Wind Harmer
4.669
944531AF1-118 GEN
Solar/Wind Harmer
13.648
270330AC1-082 GEN2
Solar/Wind Helper
0.188
24803206KYGER 4HP
50/50
4.085
3429421JKCT 10G
Adder
6.006
970773AG2-487 GEN
Solar/Wind Harmer
0.807
970653AG2-424 GEN
Solar/Wind Harmer
1.845
970091AG2-072 GEN
Adder
37.335
960001AF2-291 GEN
Solar/Wind Helper
1.682
24803006KYGER 3HP
50/50
4.142
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.038
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.38
270269AC2-059
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.148
25326109MON D
Adder
0.942
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.377
964571AG1-320 GEN
Solar/Wind Harmer
3.631
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.967
944541AF1-119 GEN
Solar/Wind Harmer
0.224
970329AG2-216 GEN
Solar/Wind Harmer
1.4
970191AG2-125 GEN
Solar/Wind Harmer
1.303
24379505HDWTR1G C
Solar/Wind Harmer
0
970455AG2-298 GEN
Solar/Wind Harmer
1.6
253325AC1-069 GEN
Solar/Wind Harmer
0.004
270004AE1-209 GEN
Solar/Wind Harmer
0.848
970653AG2-424 GEN
Solar/Wind Harmer
0.382
270518AE2-148 GEN
Solar/Wind Harmer
0.289
270329AC1-082 GEN1
Solar/Wind Helper
0.188
971985AH1-537 GEN
Solar/Wind Harmer
5.716
972165AH1-665 GEN
Solar/Wind Harmer
5.396
253406AD2-031_GEN
Solar/Wind Harmer
0.443
339216AC1-074 GEN
Solar/Wind Harmer
0.154
971029AG2-637 GEN
Solar/Wind Harmer
6.48
247536S-71 GEN
Solar/Wind Harmer
0.158
945581AF1-223 GEN
Solar/Wind Harmer
0
24802806KYGER 2HP
50/50
4.127
24802906KYGER 2LP
50/50
2.422
253370AE2-315 SEC1
Adder
1.526
971125AH1-004 GEN
Solar/Wind Harmer
2.112
25322209TAIT E
Adder
7.169
25322209TAIT E
Adder
7.008
247621Y3-024
Adder
0.133
971613AH1-306 GEN
Solar/Wind Harmer
1.669
970291AG2-192 GEN
Solar/Wind Harmer
0.435
970291AG2-192 GEN
Solar/Wind Harmer
0.201
971587AH1-292 GEN
Solar/Wind Harmer
2.382
252519AF1-045_GEN
Solar/Wind Harmer
3.694
25194608D.CRK4
Adder
1.604
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.789
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
24728505AND G1
Adder
2.173
946031AF1-268 GEN
Solar/Wind Harmer
3.69
970289AG2-191 GEN
Solar/Wind Harmer
0.368
247642Z2-115 C
Solar/Wind Harmer
0.001
24802606KYGER 1HP
50/50
4.172
24802706KYGER 1LP
50/50
2.446
253372AE2-315 SEC3
Adder
1.444
253372AE2-315 SEC3
Adder
1.444
25306009OHH W.
Adder
2.154
970289AG2-191 GEN
Solar/Wind Harmer
0.636
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.618
972273AH1-721 GEN
Adder
39.663
24803406KYGER 5HP
50/50
4.094
25196808ZIMRHP
Adder
75.812
252510AF1-249 C
Solar/Wind Harmer
0.051
25196008MFTGT1
Adder
1.283
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
0.848
970825AG2-519 GEN
Solar/Wind Harmer
1.367
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
3.893
270032AE2-172
Solar/Wind Harmer
2.318
958861AF2-177 GEN
Solar/Wind Harmer
1.487
270331AC1-082 GEN3
Solar/Wind Helper
0.187
972163AH1-664 GEN
Solar/Wind Harmer
6.737
270263AC1-001 GEN
Solar/Wind Harmer
0.582
270340AC2-060 GEN
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
8.179
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.01
241972AD1-140 GEN
Solar/Wind Harmer
0.472
964611AG1-324 GEN
Solar/Wind Harmer
1.472
971609AH1-304 GEN
Solar/Wind Harmer
0.584
25194408D.CRK1
Adder
7.38
972043AH1-570 GEN
Solar/Wind Harmer
1.433
942891AE2-308 GEN
Solar/Wind Harmer
4.783
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.132
24725505WLD G2 C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
3.278
960971AF2-388 GEN
Solar/Wind Harmer
1.97
945391AF1-204 GEN
Solar/Wind Harmer
3.307
964781AG1-341 GEN
Solar/Wind Harmer
3.276
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970107AG2-081 GEN
Solar/Wind Harmer
1.584
25326509SID D
Adder
0.66
942221AE2-234 GEN
Solar/Wind Harmer
1.259
24803506KYGER 5LP
50/50
2.389
25196408WSDLE3
Adder
8.602
25196108MFTGT2
Adder
1.414
25196108MFTGT2
Adder
1.313
270543AE2-219 C
Solar/Wind Harmer
2.892
24729505KEY G4
Adder
2.909
NYPJM->LTFIMP_NY
CLTF
1.348
LGEELTFEXP_LGEE->PJM
CLTF
4.627
WECLTFEXP_WEC->PJM
CLTF
1.3
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.242
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.509
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.475
MECLTFEXP_MEC->PJM
CLTF
5.763
SIGELTFEXP_SIGE->PJM
CLTF
0.281
LAGNLTFEXP_LAGN->PJM
CLTF
5.22
TVALTFEXP_TVA->PJM
CLTF
2.571
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS'
 OPEN BRANCH FROM BUS 962760 TO BUS 248125 CKT 1   /*AG1-125 TP   765.0 - 05ADKINS     765.0
END
CONTINGENCY 'AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 243207 TO BUS 248105 CKT 1   /*05GRNTWN     765.0 - 05GREENTW_RM 765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248102 CKT 1   /*05TEDDY_RG   765.0 - 05TEDDY      765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248105 CKT 1   /*05TEDDY_RG   765.0 - 05GREENTW_RM 765.0
END
CONTINGENCY 'AEP_P1-2_#XXXX_MARYSVILLE_TEDDY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 242928 TO BUS 248102 CKT 1   /*05MARYSV     765.0 - 05TEDDY      765.0
END
290610 to 242512 ckt Z1
242514 to 290610 ckt 1
290623 to 242925 ckt Z1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
248005 to 242528 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC122.65 %3792.0B4650.99
4.66
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC122.64 %3792.0B4650.57
4.66
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC138.45 %3792.0B5250.02
4.57
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC138.41 %3792.0B5248.4
4.57
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC110.65 %1737.0B1922.03
2.58
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-2_MP-500-028_SRT-A
SingleAC100.79 %4000.0B4031.79
4.9
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-3_MP-765-502T_SRT-A
SingleAC100.79 %4000.0B4031.62
4.9
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC104.78 %2320.0B2430.97
2.5
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
4.8
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC105.58 %3039.0B3208.68
7.36
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC113.16 %2826.0B3197.84
7.36
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC111.91 %2246.0B2513.45
2.43
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC127.9 %4142.0B5297.56
5.36
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC108.0 %4142.0B4473.55
4.76
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.31 %4571.0B5773.71
5.22
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC110.01 %4571.0B5028.49
4.71
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.34 %4571.0B5774.92
5.22
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC110.28 %4571.0B5040.8
4.71
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Base Case
SingleAC120.76 %4047.0A4887.22
5.45
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC116.4 %5523.0B6428.58
7.16
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC109.18 %4558.0A4976.63
5.31
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.76 %5523.0B5896.19
6.36
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC122.25 %1868.0B2283.58
2.47
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC103.01 %3097.0B3190.2
3.87
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.53 %5523.0B5607.44
7.24
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC112.63 %2317.0B2609.67
2.74
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC141.94 %1540.0B2185.8
2.99
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC133.27 %1540.0B2052.4
3.03
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC128.82 %1868.0B2406.35
2.47

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.99
MW Contribution:
4.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962761AG1-125 GEN
Solar/Wind Harmer
30.328
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.726
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
23684201S70BUS2
50/50
0.3
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.051
25196808ZIMRHP
Adder
72.791
25196008MFTGT1
Adder
1.323
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
965011AG1-365 GEN
Solar/Wind Harmer
6.491
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
23684101S70BUS1
50/50
0.295
970879AG2-548 GEN
Solar/Wind Harmer
1.187
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.261
942221AE2-234 GEN
Solar/Wind Harmer
2.621
246937BC-WTG2
Solar/Wind Harmer
0.26
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.722
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
970941AG2-585 GEN
Solar/Wind Harmer
3.484
276897AD1-100 C
Solar/Wind Harmer
15.831
971073AG2-665 GEN
Solar/Wind Harmer
5.224
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
25326109MON D
Adder
1.28
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194508D.CRK3
Adder
1.361
24728805RICHG1
Adder
3.564
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247620Y3-023
Adder
0.422
972045AH1-571 GEN
Solar/Wind Harmer
1.333
958011AF2-095 GEN
Solar/Wind Harmer
9.122
274695ROCKY RD ;2P
Adder
10.024
958491AF2-143 GEN
Solar/Wind Harmer
9.422
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.948
235531U2-073 GEN
Solar/Wind Helper
3.079
238149AF1-291A_GEN
Solar/Wind Helper
0.123
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25196508WSDLE4
Adder
8.165
972163AH1-664 GEN
Solar/Wind Harmer
7.323
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.067
959331AF2-224 GEN
Solar/Wind Harmer
4.543
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
25306009OHH W.
Adder
2.794
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
247521TR3_G114
Solar/Wind Harmer
0.234
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274735ELWOOD EC;4P
Adder
14.887
274744AC1-111 GEN8
Adder
5.047
970169AG2-114 GEN
Solar/Wind Harmer
6.285
959341AF2-225 GEN
Solar/Wind Harmer
6.578
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
25326309TAIT D
Adder
1.064
270317AD1-130_GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.862
25194408D.CRK1
Adder
7.279
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.846
270599AE1-208 GEN
Solar/Wind Harmer
5.986
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
972043AH1-570 GEN
Solar/Wind Harmer
1.663
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274808UNIV PK N;4U
Adder
4.533
945391AF1-204 GEN
Solar/Wind Harmer
6.73
274674JOLIET 9 ;6U
Adder
13.943
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
274693ROCKY RD ;1P
Adder
9.926
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
23585401KL_K28_T16
Solar/Wind Helper
1.451
238117U2-030
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.432
235062AE1-101 C1
Solar/Wind Helper
1.447
970155AG2-107 GEN
Solar/Wind Harmer
19.366
972203AH1-686 GEN
Adder
2.339
24723205RIVRG3
Adder
18.772
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252516AE2-318_GEN
Solar/Wind Harmer
7.551
25194608D.CRK4
Adder
1.582
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
19.339
24728605AND G2
Adder
3.541
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.553
274676JOLIET 29;8U
Adder
27.787
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
237006AB1-125 GEN
Solar/Wind Helper
0.107
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.075
253406AD2-031_GEN
Solar/Wind Harmer
0.507
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972165AH1-665 GEN
Solar/Wind Harmer
5.865
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.226
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
274675JOLIET 29;7U
Adder
27.787
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
971675AH1-338 GEN
Solar/Wind Harmer
2.438
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
971171AH1-044 GEN
Solar/Wind Harmer
3.185
276893AG1-478 C
Solar/Wind Harmer
0.421
970107AG2-081 GEN
Solar/Wind Harmer
1.892
274696ROCKY RD ;4P
Adder
10.261
274697ROCKY RD ;3P
Adder
2.723
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
316411AF1-147_GEN1
Solar/Wind Helper
0.762
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
270071AF1-092 GEN
Solar/Wind Harmer
12.517
270435AC2-044 GEN
Solar/Wind Harmer
0.816
24691005MDL-2G C
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
274728ELWOOD EC;5P
Adder
14.887
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
965041AG1-368 GEN
Solar/Wind Harmer
6.455
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274776LINCOLN ;7U
Adder
7.689
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274746AC1-111 G10
Adder
5.047
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23779801AA1-109
Solar/Wind Helper
0.168
3138216PACIFIC
Solar/Wind Helper
0.038
23559101PLEAS2
50/50
11.898
23562301OGROV1
50/50
2.293
970149AG2-104 GEN
Solar/Wind Harmer
16.378
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
971073AG2-665 GEN
Solar/Wind Harmer
1.187
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970091AG2-072 GEN
Adder
71.643
971917AH1-482 GEN
Solar/Wind Harmer
8.351
970373AG2-245 GEN
Solar/Wind Harmer
13.48
963741AG1-226 GEN
Solar/Wind Harmer
15.1
943021AE2-325 GEN
Solar/Wind Harmer
3.32
941551AE2-152 GEN
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.303
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252519AF1-045_GEN
Solar/Wind Harmer
3.517
25194608D.CRK4
Adder
1.582
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
274811UNIV PK N;7U
Adder
4.553
276806AD2-047 C O1
Solar/Wind Harmer
3.589
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274682WAUKEGAN ;7U
Adder
16.174
270588AE1-091_GEN
Solar/Wind Harmer
4.882
964991AG1-363 GEN
Solar/Wind Helper
4.289
238110AE1-109 GEN3
Solar/Wind Helper
0.103
235063AE1-101 C2
Solar/Wind Helper
1.447
959091AF2-200 GEN
Solar/Wind Harmer
3.185
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
971655AH1-328 GEN
Solar/Wind Harmer
2.4
247621Y3-024
Adder
0.226
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
270246TR4_N_V150
Solar/Wind Harmer
0.041
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.006
971587AH1-292 GEN
Solar/Wind Harmer
4.656
276776AD2-060 GEN
Solar/Wind Harmer
0.676
971125AH1-004 GEN
Solar/Wind Harmer
2.523
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.331
238147AE2-230_GEN1
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.297
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
970825AG2-519 GEN
Solar/Wind Harmer
4.924
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
246938BC-WTG3
Solar/Wind Harmer
0.232
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274724RIVER EC ;11
Adder
16.119
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
946671AF1-331 GEN
Solar/Wind Harmer
0.667
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
237048AF1-022 C
Solar/Wind Helper
0.176
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.762
274723RIVER EC ;12
Adder
16.309
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.293
939741AE1-205 GEN
Solar/Wind Harmer
8.771
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23583801GRNGAP
Solar/Wind Helper
4.978
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.438
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.732
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.237
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
961921AG1-034 GEN
Solar/Wind Harmer
6.37
942051AE2-217 GEN
Solar/Wind Harmer
12.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
252507AC2-088 GEN
Solar/Wind Harmer
0.304
25196608WSDLE5
Adder
8.25
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
971347AH1-153 GEN
Solar/Wind Harmer
3.227
24728705AND G3
Adder
7.406
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.503
274887GEN-1.85
Solar/Wind Harmer
0.165
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
274730ELWOOD EC;6P
Adder
14.887
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
238127S14_GEN_2
Solar/Wind Helper
0.769
238152AF2-075_GEN
Solar/Wind Helper
0.617
23777901MDS_W4-102
Solar/Wind Helper
0.153
24318805MLG1
50/50
6.603
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
970191AG2-125 GEN
Solar/Wind Harmer
1.734
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.503
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274803UNIV PARK;6U
Adder
5.293
276843GEN-1.7
Solar/Wind Harmer
0.205
972038AH1-567 GEN2
Adder
0.331
965091AG1-374 GEN
Solar/Wind Harmer
18.751
23562501BACKB
Solar/Wind Helper
1.049
238108AE1-109 GEN1
Solar/Wind Helper
0.103
237001AB1-127_GEN
Solar/Wind Helper
0.384
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.272
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.503
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274674JOLIET 9 ;6U
Adder
13.943
939401AE1-172 GEN
Solar/Wind Harmer
4.718
962781AG1-127 GEN
Solar/Wind Harmer
5.964
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.57
MW Contribution:
4.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971073AG2-665 GEN
Solar/Wind Harmer
5.224
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
25326109MON D
Adder
1.28
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194508D.CRK3
Adder
1.361
24728805RICHG1
Adder
3.564
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247620Y3-023
Adder
0.422
972045AH1-571 GEN
Solar/Wind Harmer
1.333
958011AF2-095 GEN
Solar/Wind Harmer
9.122
274695ROCKY RD ;2P
Adder
10.024
958491AF2-143 GEN
Solar/Wind Harmer
9.422
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.948
235531U2-073 GEN
Solar/Wind Helper
3.079
238149AF1-291A_GEN
Solar/Wind Helper
0.123
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
25306009OHH W.
Adder
2.794
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
247521TR3_G114
Solar/Wind Harmer
0.234
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274735ELWOOD EC;4P
Adder
14.887
274744AC1-111 GEN8
Adder
5.047
970169AG2-114 GEN
Solar/Wind Harmer
6.285
959341AF2-225 GEN
Solar/Wind Harmer
6.578
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.862
25194408D.CRK1
Adder
7.279
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.846
270599AE1-208 GEN
Solar/Wind Harmer
5.986
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
972043AH1-570 GEN
Solar/Wind Harmer
1.663
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274808UNIV PK N;4U
Adder
4.533
945391AF1-204 GEN
Solar/Wind Harmer
6.73
274674JOLIET 9 ;6U
Adder
13.943
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
274693ROCKY RD ;1P
Adder
9.926
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
23585401KL_K28_T16
Solar/Wind Helper
1.451
238117U2-030
Solar/Wind Helper
0.32
970155AG2-107 GEN
Solar/Wind Harmer
19.366
972203AH1-686 GEN
Adder
2.339
24723205RIVRG3
Adder
18.772
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252516AE2-318_GEN
Solar/Wind Harmer
7.551
25194608D.CRK4
Adder
1.582
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
19.339
24728605AND G2
Adder
3.541
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.553
274676JOLIET 29;8U
Adder
27.787
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.075
253406AD2-031_GEN
Solar/Wind Harmer
0.507
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972165AH1-665 GEN
Solar/Wind Harmer
5.865
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.226
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
971675AH1-338 GEN
Solar/Wind Harmer
2.438
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
971171AH1-044 GEN
Solar/Wind Harmer
3.185
23684101S70BUS1
50/50
0.295
970879AG2-548 GEN
Solar/Wind Harmer
1.187
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.261
942221AE2-234 GEN
Solar/Wind Harmer
2.621
246937BC-WTG2
Solar/Wind Harmer
0.26
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.722
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
970941AG2-585 GEN
Solar/Wind Harmer
3.484
276897AD1-100 C
Solar/Wind Harmer
15.831
276893AG1-478 C
Solar/Wind Harmer
0.421
970107AG2-081 GEN
Solar/Wind Harmer
1.892
274696ROCKY RD ;4P
Adder
10.261
274697ROCKY RD ;3P
Adder
2.723
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
316411AF1-147_GEN1
Solar/Wind Helper
0.762
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
270071AF1-092 GEN
Solar/Wind Harmer
12.517
270435AC2-044 GEN
Solar/Wind Harmer
0.816
24691005MDL-2G C
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
274728ELWOOD EC;5P
Adder
14.887
274863CRW1-WTG
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25196508WSDLE4
Adder
8.165
972163AH1-664 GEN
Solar/Wind Harmer
7.323
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.067
959331AF2-224 GEN
Solar/Wind Harmer
4.543
965041AG1-368 GEN
Solar/Wind Harmer
6.455
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274776LINCOLN ;7U
Adder
7.689
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274746AC1-111 G10
Adder
5.047
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23779801AA1-109
Solar/Wind Helper
0.168
3138216PACIFIC
Solar/Wind Helper
0.038
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252519AF1-045_GEN
Solar/Wind Harmer
3.517
25194608D.CRK4
Adder
1.582
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
274811UNIV PK N;7U
Adder
4.553
276806AD2-047 C O1
Solar/Wind Harmer
3.589
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274682WAUKEGAN ;7U
Adder
16.174
270588AE1-091_GEN
Solar/Wind Harmer
4.882
964991AG1-363 GEN
Solar/Wind Helper
4.289
238110AE1-109 GEN3
Solar/Wind Helper
0.103
235063AE1-101 C2
Solar/Wind Helper
1.447
959091AF2-200 GEN
Solar/Wind Harmer
3.185
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
971655AH1-328 GEN
Solar/Wind Harmer
2.4
247621Y3-024
Adder
0.226
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
270246TR4_N_V150
Solar/Wind Harmer
0.041
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.006
971587AH1-292 GEN
Solar/Wind Harmer
4.656
276776AD2-060 GEN
Solar/Wind Harmer
0.676
971125AH1-004 GEN
Solar/Wind Harmer
2.523
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.331
238147AE2-230_GEN1
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.297
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
970825AG2-519 GEN
Solar/Wind Harmer
4.924
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
246938BC-WTG3
Solar/Wind Harmer
0.232
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274724RIVER EC ;11
Adder
16.119
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
946671AF1-331 GEN
Solar/Wind Harmer
0.667
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
237048AF1-022 C
Solar/Wind Helper
0.176
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.762
23684201S70BUS2
50/50
0.3
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.051
25196808ZIMRHP
Adder
72.791
25196008MFTGT1
Adder
1.323
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
965011AG1-365 GEN
Solar/Wind Harmer
6.491
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.293
939741AE1-205 GEN
Solar/Wind Harmer
8.771
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23583801GRNGAP
Solar/Wind Helper
4.978
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.438
23559101PLEAS2
50/50
11.898
23562301OGROV1
50/50
2.293
970149AG2-104 GEN
Solar/Wind Harmer
16.378
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
971073AG2-665 GEN
Solar/Wind Harmer
1.187
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970091AG2-072 GEN
Adder
71.643
971917AH1-482 GEN
Solar/Wind Harmer
8.351
970373AG2-245 GEN
Solar/Wind Harmer
13.48
963741AG1-226 GEN
Solar/Wind Harmer
15.1
943021AE2-325 GEN
Solar/Wind Harmer
3.32
941551AE2-152 GEN
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.303
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.732
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.237
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
961921AG1-034 GEN
Solar/Wind Harmer
6.37
942051AE2-217 GEN
Solar/Wind Harmer
12.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
252507AC2-088 GEN
Solar/Wind Harmer
0.304
25196608WSDLE5
Adder
8.25
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
971347AH1-153 GEN
Solar/Wind Harmer
3.227
24728705AND G3
Adder
7.406
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.503
274887GEN-1.85
Solar/Wind Harmer
0.165
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
274730ELWOOD EC;6P
Adder
14.887
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
238127S14_GEN_2
Solar/Wind Helper
0.769
238152AF2-075_GEN
Solar/Wind Helper
0.617
23777901MDS_W4-102
Solar/Wind Helper
0.153
238148AE2-230_GEN2
Solar/Wind Helper
0.432
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
24318805MLG1
50/50
6.603
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
970191AG2-125 GEN
Solar/Wind Harmer
1.734
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.503
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274803UNIV PARK;6U
Adder
5.293
276843GEN-1.7
Solar/Wind Harmer
0.205
972038AH1-567 GEN2
Adder
0.331
965091AG1-374 GEN
Solar/Wind Harmer
18.751
23562501BACKB
Solar/Wind Helper
1.049
238108AE1-109 GEN1
Solar/Wind Helper
0.103
237001AB1-127_GEN
Solar/Wind Helper
0.384
962761AG1-125 GEN
Solar/Wind Harmer
30.328
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.726
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.064
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.272
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.503
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274674JOLIET 9 ;6U
Adder
13.943
939401AE1-172 GEN
Solar/Wind Harmer
4.718
962781AG1-127 GEN
Solar/Wind Harmer
5.964
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5250.02
MW Contribution:
4.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970155AG2-107 GEN
Solar/Wind Harmer
18.85
972203AH1-686 GEN
Adder
2.3
24723205RIVRG3
Adder
18.491
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252516AE2-318_GEN
Solar/Wind Harmer
7.407
25194608D.CRK4
Adder
1.552
945681AF1-233 GEN
Solar/Wind Harmer
12.198
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.138
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.454
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.299
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
238120AE2-309 GEN
Solar/Wind Helper
0.408
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
961921AG1-034 GEN
Solar/Wind Harmer
6.223
942051AE2-217 GEN
Solar/Wind Harmer
12.329
252507AC2-088 GEN
Solar/Wind Harmer
0.298
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
25196608WSDLE5
Adder
8.09
958171AF2-111 GEN
Solar/Wind Harmer
16.173
944531AF1-118 GEN
Solar/Wind Harmer
28.761
24728705AND G3
Adder
7.256
971347AH1-153 GEN
Solar/Wind Harmer
3.154
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.339
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274887GEN-1.85
Solar/Wind Harmer
0.161
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
970707AG2-453 GEN
Solar/Wind Harmer
20.232
274730ELWOOD EC;6P
Adder
14.566
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
959611AF2-252 GEN
Solar/Wind Harmer
2.04
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
238152AF2-075_GEN
Solar/Wind Helper
0.595
23777901MDS_W4-102
Solar/Wind Helper
0.147
238127S14_GEN_2
Solar/Wind Helper
0.641
23684201S70BUS2
50/50
0.315
972269AH1-719 GEN
Adder
2.27
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.05
25196808ZIMRHP
Adder
71.417
25196008MFTGT1
Adder
1.297
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970825AG2-519 GEN
Solar/Wind Harmer
2.272
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
965011AG1-365 GEN
Solar/Wind Harmer
6.339
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
939741AE1-205 GEN
Solar/Wind Harmer
8.588
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
237085AD2-009_GEN
Solar/Wind Helper
1.37
238126S14_GEN_1
Solar/Wind Helper
0.641
23559101PLEAS2
50/50
11.247
23562301OGROV1
50/50
2.436
970149AG2-104 GEN
Solar/Wind Harmer
15.941
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970091AG2-072 GEN
Adder
70.262
971917AH1-482 GEN
Solar/Wind Harmer
8.17
970373AG2-245 GEN
Solar/Wind Harmer
13.183
944971AF1-162 GEN
Solar/Wind Harmer
6.272
963741AG1-226 GEN
Solar/Wind Harmer
14.786
943021AE2-325 GEN
Solar/Wind Harmer
3.244
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
23546401DTGZ2-030
Solar/Wind Helper
0.075
237038AE2-054 C
Solar/Wind Helper
0.227
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
246938BC-WTG3
Solar/Wind Harmer
0.226
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274724RIVER EC ;11
Adder
15.767
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
238175AF1-290_GEN
Solar/Wind Helper
0.13
24318805MLG1
50/50
6.319
24686405CER G5
Adder
8.185
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
970191AG2-125 GEN
Solar/Wind Harmer
1.699
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.388
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.339
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274803UNIV PARK;6U
Adder
5.179
276843GEN-1.7
Solar/Wind Harmer
0.2
972038AH1-567 GEN2
Adder
0.324
965091AG1-374 GEN
Solar/Wind Harmer
18.362
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237001AB1-127_GEN
Solar/Wind Helper
0.369
971073AG2-665 GEN
Solar/Wind Harmer
5.141
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.328
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
24728805RICHG1
Adder
3.492
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.309
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
958011AF2-095 GEN
Solar/Wind Harmer
8.924
958491AF2-143 GEN
Solar/Wind Harmer
9.221
23684101S70BUS1
50/50
0.309
970879AG2-548 GEN
Solar/Wind Harmer
1.168
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.233
942221AE2-234 GEN
Solar/Wind Harmer
2.563
957841AF2-078 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.119
235531U2-073 GEN
Solar/Wind Helper
2.544
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196508WSDLE4
Adder
8.008
972163AH1-664 GEN
Solar/Wind Harmer
7.194
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
959331AF2-224 GEN
Solar/Wind Harmer
4.437
965041AG1-368 GEN
Solar/Wind Harmer
6.303
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
270526AF1-158 GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
Adder
7.522
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252519AF1-045_GEN
Solar/Wind Harmer
3.45
25194608D.CRK4
Adder
1.552
946031AF1-268 GEN
Solar/Wind Harmer
6.094
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.47
24695305TIMB G C
Solar/Wind Harmer
0.532
274811UNIV PK N;7U
Adder
4.454
276806AD2-047 C O1
Solar/Wind Harmer
3.512
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
964991AG1-363 GEN
Solar/Wind Helper
4.131
238110AE1-109 GEN3
Solar/Wind Helper
0.088
235063AE1-101 C2
Solar/Wind Helper
1.383
959091AF2-200 GEN
Solar/Wind Harmer
2.06
970935AG2-582 GEN
50/50
1217.29
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
971655AH1-328 GEN
Solar/Wind Harmer
2.343
247621Y3-024
Adder
0.222
971613AH1-306 GEN
Solar/Wind Harmer
3.066
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
270246TR4_N_V150
Solar/Wind Harmer
0.04
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.827
971587AH1-292 GEN
Solar/Wind Harmer
4.565
971125AH1-004 GEN
Solar/Wind Harmer
2.48
276776AD2-060 GEN
Solar/Wind Harmer
0.661
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
237080AD1-060 GEN
Solar/Wind Helper
0.284
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
247521TR3_G114
Solar/Wind Harmer
0.229
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274735ELWOOD EC;4P
Adder
14.566
970179AG2-119 GEN
Solar/Wind Harmer
5.512
970169AG2-114 GEN
Solar/Wind Harmer
6.152
959341AF2-225 GEN
Solar/Wind Harmer
6.441
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.602
25194408D.CRK1
Adder
7.139
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.762
270599AE1-208 GEN
Solar/Wind Harmer
5.858
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
966841AG1-555 GEN
Solar/Wind Harmer
0.711
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274808UNIV PK N;4U
Adder
4.435
958481AF2-142 GEN
Solar/Wind Harmer
9.241
944231AF1-091 GEN
Solar/Wind Harmer
14.169
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
238148AE2-230_GEN2
Solar/Wind Helper
0.416
235062AE1-101 C1
Solar/Wind Helper
1.383
238117U2-030
Solar/Wind Helper
0.26
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.039
253406AD2-031_GEN
Solar/Wind Harmer
0.497
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
247536S-71 GEN
Solar/Wind Harmer
0.257
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.151
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
959141AF2-205 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
270399AC1-101 GEN
Solar/Wind Harmer
1.959
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
971171AH1-044 GEN
Solar/Wind Harmer
2.06
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270459AD2-067 GEN
Solar/Wind Harmer
0
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
962761AG1-125 GEN
Solar/Wind Harmer
29.52
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.043
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.119
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.339
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
939401AE1-172 GEN
Solar/Wind Harmer
4.617
962781AG1-127 GEN
Solar/Wind Harmer
5.837
235067AD1-061 GEN
Solar/Wind Helper
0.371
237002AB1-128_GEN
Solar/Wind Helper
0.369
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
270543AE2-219 C
Solar/Wind Harmer
4.502
24729505KEY G4
Adder
5.966
270071AF1-092 GEN
Solar/Wind Harmer
12.235
24691005MDL-2G C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270007AE1-245 C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.566
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.41 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5248.4
MW Contribution:
4.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970155AG2-107 GEN
Solar/Wind Harmer
18.85
972203AH1-686 GEN
Adder
2.3
24723205RIVRG3
Adder
18.491
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252516AE2-318_GEN
Solar/Wind Harmer
7.407
25194608D.CRK4
Adder
1.552
945681AF1-233 GEN
Solar/Wind Harmer
12.198
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.138
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.454
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.299
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
238120AE2-309 GEN
Solar/Wind Helper
0.408
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
961921AG1-034 GEN
Solar/Wind Harmer
6.223
942051AE2-217 GEN
Solar/Wind Harmer
12.329
252507AC2-088 GEN
Solar/Wind Harmer
0.298
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
25196608WSDLE5
Adder
8.09
958171AF2-111 GEN
Solar/Wind Harmer
16.173
944531AF1-118 GEN
Solar/Wind Harmer
28.761
24728705AND G3
Adder
7.256
971347AH1-153 GEN
Solar/Wind Harmer
3.154
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.339
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274887GEN-1.85
Solar/Wind Harmer
0.161
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
970707AG2-453 GEN
Solar/Wind Harmer
20.232
274730ELWOOD EC;6P
Adder
14.566
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
959611AF2-252 GEN
Solar/Wind Harmer
2.04
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
238152AF2-075_GEN
Solar/Wind Helper
0.595
23777901MDS_W4-102
Solar/Wind Helper
0.147
238127S14_GEN_2
Solar/Wind Helper
0.641
23684201S70BUS2
50/50
0.315
972269AH1-719 GEN
Adder
2.27
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.05
25196808ZIMRHP
Adder
71.417
25196008MFTGT1
Adder
1.297
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970825AG2-519 GEN
Solar/Wind Harmer
2.272
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
965011AG1-365 GEN
Solar/Wind Harmer
6.339
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
939741AE1-205 GEN
Solar/Wind Harmer
8.588
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
237085AD2-009_GEN
Solar/Wind Helper
1.37
238126S14_GEN_1
Solar/Wind Helper
0.641
23559101PLEAS2
50/50
11.247
23562301OGROV1
50/50
2.436
970149AG2-104 GEN
Solar/Wind Harmer
15.941
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970091AG2-072 GEN
Adder
70.262
971917AH1-482 GEN
Solar/Wind Harmer
8.17
970373AG2-245 GEN
Solar/Wind Harmer
13.183
944971AF1-162 GEN
Solar/Wind Harmer
6.272
963741AG1-226 GEN
Solar/Wind Harmer
14.786
943021AE2-325 GEN
Solar/Wind Harmer
3.244
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
23546401DTGZ2-030
Solar/Wind Helper
0.075
237038AE2-054 C
Solar/Wind Helper
0.227
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
246938BC-WTG3
Solar/Wind Harmer
0.226
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274724RIVER EC ;11
Adder
15.767
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
238175AF1-290_GEN
Solar/Wind Helper
0.13
24318805MLG1
50/50
6.319
24686405CER G5
Adder
8.185
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
970191AG2-125 GEN
Solar/Wind Harmer
1.699
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.388
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.339
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274803UNIV PARK;6U
Adder
5.179
276843GEN-1.7
Solar/Wind Harmer
0.2
972038AH1-567 GEN2
Adder
0.324
965091AG1-374 GEN
Solar/Wind Harmer
18.362
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237001AB1-127_GEN
Solar/Wind Helper
0.369
23684101S70BUS1
50/50
0.309
970879AG2-548 GEN
Solar/Wind Harmer
1.168
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.233
942221AE2-234 GEN
Solar/Wind Harmer
2.563
971073AG2-665 GEN
Solar/Wind Harmer
5.141
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.328
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
24728805RICHG1
Adder
3.492
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.309
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
958011AF2-095 GEN
Solar/Wind Harmer
8.924
958491AF2-143 GEN
Solar/Wind Harmer
9.221
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.119
235531U2-073 GEN
Solar/Wind Helper
2.544
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196508WSDLE4
Adder
8.008
972163AH1-664 GEN
Solar/Wind Harmer
7.194
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
959331AF2-224 GEN
Solar/Wind Harmer
4.437
965041AG1-368 GEN
Solar/Wind Harmer
6.303
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
270526AF1-158 GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
Adder
7.522
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252519AF1-045_GEN
Solar/Wind Harmer
3.45
25194608D.CRK4
Adder
1.552
946031AF1-268 GEN
Solar/Wind Harmer
6.094
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.47
24695305TIMB G C
Solar/Wind Harmer
0.532
274811UNIV PK N;7U
Adder
4.454
276806AD2-047 C O1
Solar/Wind Harmer
3.512
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
964991AG1-363 GEN
Solar/Wind Helper
4.131
238110AE1-109 GEN3
Solar/Wind Helper
0.088
235063AE1-101 C2
Solar/Wind Helper
1.383
959091AF2-200 GEN
Solar/Wind Harmer
2.06
970935AG2-582 GEN
50/50
1217.29
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
971655AH1-328 GEN
Solar/Wind Harmer
2.343
247621Y3-024
Adder
0.222
971613AH1-306 GEN
Solar/Wind Harmer
3.066
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
270246TR4_N_V150
Solar/Wind Harmer
0.04
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.827
971587AH1-292 GEN
Solar/Wind Harmer
4.565
971125AH1-004 GEN
Solar/Wind Harmer
2.48
276776AD2-060 GEN
Solar/Wind Harmer
0.661
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
237080AD1-060 GEN
Solar/Wind Helper
0.284
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
247521TR3_G114
Solar/Wind Harmer
0.229
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274735ELWOOD EC;4P
Adder
14.566
970179AG2-119 GEN
Solar/Wind Harmer
5.512
970169AG2-114 GEN
Solar/Wind Harmer
6.152
959341AF2-225 GEN
Solar/Wind Harmer
6.441
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.602
25194408D.CRK1
Adder
7.139
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.762
270599AE1-208 GEN
Solar/Wind Harmer
5.858
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
966841AG1-555 GEN
Solar/Wind Harmer
0.711
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274808UNIV PK N;4U
Adder
4.435
958481AF2-142 GEN
Solar/Wind Harmer
9.241
944231AF1-091 GEN
Solar/Wind Harmer
14.169
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
238148AE2-230_GEN2
Solar/Wind Helper
0.416
235062AE1-101 C1
Solar/Wind Helper
1.383
238117U2-030
Solar/Wind Helper
0.26
270291AC1-194 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
971985AH1-537 GEN
Solar/Wind Harmer
2.039
253406AD2-031_GEN
Solar/Wind Harmer
0.497
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
247536S-71 GEN
Solar/Wind Harmer
0.257
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.151
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
959141AF2-205 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
270399AC1-101 GEN
Solar/Wind Harmer
1.959
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
971171AH1-044 GEN
Solar/Wind Harmer
2.06
962761AG1-125 GEN
Solar/Wind Harmer
29.52
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.043
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.119
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.339
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
939401AE1-172 GEN
Solar/Wind Harmer
4.617
962781AG1-127 GEN
Solar/Wind Harmer
5.837
235067AD1-061 GEN
Solar/Wind Helper
0.371
237002AB1-128_GEN
Solar/Wind Helper
0.369
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270459AD2-067 GEN
Solar/Wind Harmer
0
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
270543AE2-219 C
Solar/Wind Harmer
4.502
24729505KEY G4
Adder
5.966
270071AF1-092 GEN
Solar/Wind Harmer
12.235
24691005MDL-2G C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270007AE1-245 C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.566
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.65 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:1922.03
MW Contribution:
2.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.081
24695305TIMB G C
Solar/Wind Harmer
0.545
274811UNIV PK N;7U
Adder
3.9
276806AD2-047 C O1
Solar/Wind Harmer
3.036
247642Z2-115 C
Solar/Wind Harmer
0.002
274676JOLIET 29;8U
Adder
22.491
274734ELWOOD EC;8P
Adder
12.465
960861AF2-377 GEN
50/50
2.456
24307105BERRINSP G
50/50
0.018
965011AG1-365 GEN
Solar/Wind Harmer
13.973
958861AF2-177 GEN
Solar/Wind Harmer
2.759
945111AF1-176 GEN
Solar/Wind Harmer
10.951
957891AF2-083 GEN
Solar/Wind Harmer
10.053
945371AF1-202 GEN
Solar/Wind Harmer
0
944961AF1-161 GEN
50/50
2.458
965021AG1-366 GEN
Solar/Wind Harmer
4.658
270043AE2-236 GEN
Solar/Wind Harmer
5.337
945111AF1-176 GEN
Solar/Wind Harmer
4.975
270505AE1-170 C O1
Solar/Wind Harmer
6.29
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.571
274724RIVER EC ;11
Adder
13.897
274772LINCOLN ;3U
Adder
6.547
972259AH1-714 GEN
Adder
14.564
274729ELWOOD EC;1P
Adder
12.464
970825AG2-519 GEN
Solar/Wind Harmer
3.908
946671AF1-331 GEN
Solar/Wind Harmer
0.54
274850MENDOTA H;RU
Solar/Wind Harmer
0.059
970571AG2-364 GEN
Solar/Wind Harmer
9.976
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.067
942481AE2-261 GEN
Solar/Wind Harmer
12.705
246938BC-WTG3
Solar/Wind Helper
11.03
24729405KEY G3
50/50
0.382
24729305KEY G2
50/50
0.375
960851AF2-376 GEN
50/50
2.145
270100X2-052 CT1
50/50
1.216
942221AE2-234 GEN
Solar/Wind Harmer
2.915
274805UNIV PK N;1U
Adder
3.909
274770LINCOLN ;1U
Adder
6.547
274771LINCOLN ;2U
Adder
6.547
274888KELLY CRK;1U
Solar/Wind Harmer
0.312
970941AG2-585 GEN
Solar/Wind Harmer
2.946
276897AD1-100 C
Solar/Wind Harmer
13.263
276893AG1-478 C
Solar/Wind Harmer
0.353
274696ROCKY RD ;4P
Adder
8.451
274697ROCKY RD ;3P
Adder
2.243
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
15.403
938861AE1-114 GEN
Solar/Wind Harmer
2.807
274762LEE CO EC;3U
Adder
6.581
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.787
276645AC1-214 GEN1
Solar/Wind Harmer
0.191
24387305FR-4G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
1.562
970241AG2-163 GEN
Solar/Wind Harmer
2.669
276838X2-022 GEN2
Solar/Wind Harmer
0.248
970623AG2-406 GEN
Solar/Wind Harmer
0.684
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.844
247522W1-056 GEN
Solar/Wind Helper
1.146
253378AE2-206_GEN
Solar/Wind Helper
0.688
270246TR4_N_V150
Solar/Wind Harmer
0.047
965681AG1-436 GEN
Solar/Wind Harmer
7.151
247621Y3-024
Adder
0.188
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.571
970291AG2-192 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.317
971613AH1-306 GEN
Solar/Wind Harmer
2.514
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
10.069
971343AH1-151 GEN
Solar/Wind Harmer
10.069
276916AD2-100_GEN
Solar/Wind Harmer
8.848
971587AH1-292 GEN
Solar/Wind Harmer
2.578
270349AD2-093_GEN
Solar/Wind Helper
0.824
270471AD2-092_GEN
Solar/Wind Helper
0.824
24344105CKG2
50/50
6.284
943021AE2-325 GEN
Solar/Wind Harmer
3.079
970373AG2-245 GEN
Solar/Wind Harmer
11.559
971917AH1-482 GEN
Solar/Wind Harmer
6.946
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.845
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.596
959081AF2-199 GEN
Solar/Wind Harmer
5.034
971067AG2-660 GEN
Solar/Wind Harmer
1.678
274822ROCKFORD ;11
Adder
14.119
970819AG2-516 GEN
Solar/Wind Harmer
5.99
276646AC1-214 GEN2
Solar/Wind Harmer
0.191
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
10.829
970773AG2-487 GEN
Solar/Wind Harmer
0.657
270578AF1-285 GEN2
Solar/Wind Helper
0.582
270286AF1-227 GEN2
Solar/Wind Helper
0.675
24729205KEY G1
50/50
0.374
247620Y3-023
50/50
0.478
270101X2-052 CT2
50/50
1.216
944541AF1-119 GEN
Solar/Wind Harmer
0.437
270031AE2-169
Solar/Wind Harmer
3.187
965791AG1-447 GEN
Solar/Wind Harmer
5.244
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.421
958011AF2-095 GEN
Solar/Wind Harmer
7.714
274695ROCKY RD ;2P
Adder
8.256
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
7.702
276872AE1-163_GEN1
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.573
274765LEE CO EC;6U
Adder
6.597
274763LEE CO EC;4U
Adder
6.519
24699105WLD G1 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.544
270383AD1-128 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
0.583
241960AC2-195 GEN
Solar/Wind Helper
0.664
270144AC1-141 ST1_
50/50
1.838
959331AF2-224 GEN
Solar/Wind Harmer
9.781
965041AG1-368 GEN
Solar/Wind Harmer
8.594
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.946
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.189
274776LINCOLN ;7U
Adder
6.547
274687WILL CNTY;4U
Adder
21.288
274687WILL CNTY;4U
Adder
21.288
274731ELWOOD EC;2P
Adder
12.464
274733ELWOOD EC;3P
Adder
12.464
274746AC1-111 G10
Adder
4.189
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.847
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.041
944221AF1-090 GEN
Solar/Wind Harmer
2.4
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
0.859
966831AG1-554 GEN
Solar/Wind Helper
0.861
270499AE1-146 GEN
Solar/Wind Helper
1.911
24643105BUCHANAN
50/50
0.011
270102X2-052 ST
50/50
1.316
270247TR4_N_V136
Solar/Wind Harmer
0.047
944231AF1-091 GEN
Solar/Wind Harmer
16.486
960971AF2-388 GEN
Solar/Wind Harmer
3.84
970349AG2-230 GEN
Solar/Wind Harmer
9.006
961051AF2-396 GEN
Solar/Wind Harmer
11.975
961051AF2-396 GEN
Solar/Wind Harmer
7.983
270599AE1-208 GEN
Solar/Wind Harmer
5.311
274808UNIV PK N;4U
Adder
3.883
274674JOLIET 9 ;6U
Adder
11.68
958481AF2-142 GEN
Solar/Wind Harmer
7.796
274693ROCKY RD ;1P
Adder
8.175
274683WAUKEGAN ;8U
Adder
15.599
274683WAUKEGAN ;8U
Adder
13.149
276876AE1-163_GEN2
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.809
274764LEE CO EC;5U
Adder
6.597
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.55
960611AF2-352 GEN
Solar/Wind Harmer
1.575
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.631
276615X2-022 GEN
Solar/Wind Harmer
0.046
945391AF1-204 GEN
Solar/Wind Harmer
4.379
270462AD2-086
Solar/Wind Helper
3.683
24641605TWIN BRNCH
50/50
0.016
24344005CKG1
50/50
5.28
970031AG2-029 GEN
Solar/Wind Harmer
4.668
965051AG1-369 GEN
Solar/Wind Harmer
3.677
945581AF1-223 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
6.547
274777LINCOLN ;8U
Adder
6.547
972037AH1-567 GEN1
Adder
0.141
960591AF2-350 GEN
Solar/Wind Harmer
5.357
972228AH1-698 GEN2
Adder
2.836
274675JOLIET 29;7U
Adder
23.324
274675JOLIET 29;7U
Adder
22.491
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
5.794
970833AG2-524 GEN
Solar/Wind Harmer
3.862
971611AH1-305 GEN
Solar/Wind Harmer
3.121
247536S-71 GEN
Solar/Wind Harmer
0.205
971411AH1-196 GEN
Solar/Wind Harmer
7.602
971675AH1-338 GEN
Solar/Wind Harmer
1.975
971171AH1-044 GEN
Solar/Wind Harmer
10.069
274823ROCKFORD ;21
Adder
14.017
972267AH1-718 GEN
Adder
2.917
24386405FR-21G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
2.661
971029AG2-637 GEN
Solar/Wind Harmer
6.154
270224U2-072_GEN2
Solar/Wind Helper
0.859
945641AF1-229 GEN
Solar/Wind Helper
0.907
970583AG2-370 GEN
50/50
2.865
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
32.656
971347AH1-153 GEN
Solar/Wind Harmer
3.002
274752CRETE EC ;2U
Adder
6.49
274826FISK ;BP
Adder
8.431
274887GEN-1.85
Solar/Wind Harmer
0.139
970707AG2-453 GEN
Solar/Wind Harmer
17.395
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
12.465
274862TOP CROP ;2U
Solar/Wind Harmer
0.701
276868AE1-113 GEN
Solar/Wind Harmer
1.021
274879MINONK ;1U
Solar/Wind Harmer
0.213
274855GSG-6 ;RU
Solar/Wind Harmer
0.185
970781AG2-491 GEN
Solar/Wind Harmer
5.046
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
1.575
970193AG2-126 GEN
Solar/Wind Harmer
6.182
24728705AND G3
Adder
4.563
942871AE2-306 GEN
Solar/Wind Helper
0.436
270287AF1-227 GEN3
Solar/Wind Helper
0.675
270541AE2-072 C
Solar/Wind Helper
0.902
24729505KEY G4
50/50
6.995
24653605MOTTVILLE
50/50
0.004
270071AF1-092 GEN
Solar/Wind Harmer
14.854
971771AH1-392 GEN
Solar/Wind Harmer
6.058
274728ELWOOD EC;5P
Adder
12.465
970073AG2-061 GEN
Solar/Wind Harmer
1.711
276861AD2-134 GEN
Solar/Wind Harmer
0.09
276863AD2-134 GEN
Solar/Wind Harmer
0.09
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.116
971681AH1-341 GEN
Solar/Wind Harmer
7.978
971549AH1-272 GEN
Solar/Wind Harmer
10.208
270543AE2-219 C
Solar/Wind Harmer
3.242
270007AE1-245 C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
12.238
247521TR3_G114
Solar/Wind Harmer
0.267
274827FISK ;RP
Adder
5.975
274800UNIV PARK;3U
Adder
4.482
274801UNIV PARK;4U
Adder
4.482
972227AH1-698 GEN1
Adder
1.997
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
12.464
970289AG2-191 GEN
Solar/Wind Harmer
1.003
274744AC1-111 GEN8
Adder
4.189
970169AG2-114 GEN
Solar/Wind Harmer
4.974
276741O09 GEN1
Solar/Wind Harmer
0.172
274877BISHOP HL;1U
Solar/Wind Harmer
0.162
959341AF2-225 GEN
Solar/Wind Harmer
5.047
276668AB2-070 GEN1
Solar/Wind Harmer
0.176
276848AB2-070 GEN3
Solar/Wind Harmer
0.175
276849AB2-070 GEN2
Solar/Wind Harmer
0.176
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.567
270227U2-072_GEN3
Solar/Wind Helper
0.859
270228U2-072_GEN4
Solar/Wind Helper
0.859
270231U2-072_GEN5
Solar/Wind Helper
0.859
24642205MAYFLWER
50/50
0.032
962601AG1-109 GEN
50/50
2.458
274753CRETE EC ;3U
Adder
6.49
274814UNIV PK N;0U
Adder
3.935
274807UNIV PK N;3U
Adder
3.926
274803UNIV PARK;6U
Adder
4.495
972038AH1-567 GEN2
Adder
0.281
276843GEN-1.7
Solar/Wind Harmer
0.173
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.133
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.581
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.162
965091AG1-374 GEN
Solar/Wind Harmer
14.177
965931AG1-462 GEN
Solar/Wind Harmer
12.05
274751CRETE EC ;1U
Adder
6.49
274723RIVER EC ;12
Adder
14.067
274773LINCOLN ;4U
Adder
6.547
274774LINCOLN ;5U
Adder
6.547
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.552
270594AE1-207 GEN
Solar/Wind Harmer
5.867
270032AE2-172
Solar/Wind Harmer
3.492
270005AE1-210 C O1
Solar/Wind Harmer
1.133
970825AG2-519 GEN
Solar/Wind Harmer
1.842
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
2.669
970569AG2-363 GEN
Solar/Wind Harmer
14.964
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.581
24386605FR-22G C
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.73
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.22
246936BC-WTG1
Solar/Wind Helper
10.844
270485AE1-090_GEN
Solar/Wind Helper
0.32
960841AF2-375 GEN
Solar/Wind Helper
1.143
274736ELWOOD EC;9P
Adder
12.465
970289AG2-191 GEN
Solar/Wind Harmer
0.58
946031AF1-268 GEN
Solar/Wind Harmer
4.982
943121AE2-341 GEN
Solar/Wind Harmer
8.771
943591AF1-030 GEN
Solar/Wind Harmer
5.832
274682WAUKEGAN ;7U
Adder
13.321
959091AF2-200 GEN
Solar/Wind Harmer
10.069
274767LEE CO EC;8U
Adder
6.504
971087AG2-675 GEN
Solar/Wind Harmer
2.52
957381AF2-032 GEN
Solar/Wind Harmer
0.966
24728505AND G1
Adder
2.182
270284AF1-227 GEN1
Solar/Wind Helper
1.841
276820AF1-078_GEN
Solar/Wind Helper
0.321
970521AG2-332 GEN
50/50
11.157
24639705ELKHART HY
50/50
0.154
270143AC1-141 CT2_
50/50
2.081
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.92
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
3.9
270055AF2-134 C O1
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
23.324
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.189
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
13.321
274828WAUKEGAN ;BP
Adder
8.177
957471AF2-041 GEN
Solar/Wind Harmer
15.103
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.397
24728605AND G2
Adder
2.182
24379505HDWTR1G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
6.49
274802UNIV PARK;5U
Adder
4.495
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
11.68
274732ELWOOD EC;7P
Adder
12.465
962781AG1-127 GEN
Solar/Wind Harmer
4.874
939401AE1-172 GEN
Solar/Wind Harmer
3.83
276903AD2-071 C
Solar/Wind Harmer
5.594
274766LEE CO EC;7U
Adder
6.504
276708O09 GEN2
Solar/Wind Harmer
0.172
24385905FR-11G C
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.85
270317AD1-130_GEN
Solar/Wind Helper
4.072
270391AF1-285 GEN3
Solar/Wind Helper
0.582
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
NYPJM->LTFIMP_NY
CLTF
1.125
LGEELTFEXP_LGEE->PJM
CLTF
1.97
WECLTFEXP_WEC->PJM
CLTF
2.738
AG2-052LTFEXP_AG2-052->PJM
LTF
0.177
AH1-155LTFEXP_AH1-155->PJM
LTF
0.266
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.75
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.755
MECLTFEXP_MEC->PJM
CLTF
10.148
SIGELTFEXP_SIGE->PJM
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
6.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.165
TVALTFEXP_TVA->PJM
CLTF
2.538

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.79
MW Contribution:
4.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252519AF1-045_GEN
Solar/Wind Harmer
3.611
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.696
274811UNIV PK N;7U
Adder
4.772
276806AD2-047 C O1
Solar/Wind Harmer
3.764
24695305TIMB G C
Solar/Wind Harmer
0.562
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274682WAUKEGAN ;7U
Adder
3.428
964991AG1-363 GEN
Solar/Wind Helper
3.896
238110AE1-109 GEN3
Solar/Wind Helper
0.096
959091AF2-200 GEN
Solar/Wind Harmer
11.056
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24686405CER G5
Adder
8.833
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.57
970191AG2-125 GEN
Solar/Wind Harmer
1.771
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.475
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.861
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
276843GEN-1.7
Solar/Wind Harmer
0.215
274803UNIV PARK;6U
Adder
5.55
972038AH1-567 GEN2
Adder
0.347
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
965091AG1-374 GEN
Solar/Wind Harmer
19.702
23562501BACKB
Solar/Wind Helper
1.069
238108AE1-109 GEN1
Solar/Wind Helper
0.096
243186AF1-051 GEN
50/50
6.83
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
252516AE2-318_GEN
Solar/Wind Harmer
7.753
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
965651AG1-433 GEN
Solar/Wind Harmer
2.002
970613AG2-401 GEN
Solar/Wind Harmer
5
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.147
274812UNIV PK N;8U
Adder
4.772
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274676JOLIET 29;8U
Adder
29.146
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238109AE1-109 GEN2
Solar/Wind Helper
0.096
942051AE2-217 GEN
Solar/Wind Harmer
12.564
252507AC2-088 GEN
Solar/Wind Harmer
0.312
961921AG1-034 GEN
Solar/Wind Harmer
6.169
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
944531AF1-118 GEN
Solar/Wind Harmer
30.627
958171AF2-111 GEN
Solar/Wind Harmer
16.988
971347AH1-153 GEN
Solar/Wind Harmer
3.374
970781AG2-491 GEN
Solar/Wind Harmer
6.73
24728705AND G3
Adder
7.73
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.861
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
970707AG2-453 GEN
Solar/Wind Harmer
21.689
274730ELWOOD EC;6P
Adder
15.615
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
959611AF2-252 GEN
Solar/Wind Harmer
2.189
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
238127S14_GEN_2
Solar/Wind Helper
0.726
270120AB2-067 GEN2
50/50
5.522
25194408D.CRK1
Adder
7.485
270054AF2-122 C O1
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
4.003
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
270462AD2-086
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
6.229
24725505WLD G2 C
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
10.122
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
966841AG1-555 GEN
Solar/Wind Harmer
0.761
270247TR4_N_V136
Solar/Wind Harmer
0.043
972043AH1-570 GEN
Solar/Wind Harmer
1.73
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
958481AF2-142 GEN
Solar/Wind Harmer
9.909
274693ROCKY RD ;1P
Adder
10.419
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23585401KL_K28_T16
Solar/Wind Helper
1.41
238117U2-030
Solar/Wind Helper
0.306
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25306009OHH W.
Adder
2.85
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
970289AG2-191 GEN
Solar/Wind Harmer
1.292
963791AG1-232 GEN
Solar/Wind Harmer
9.106
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
972227AH1-698 GEN1
Adder
2.483
274827FISK ;RP
Adder
7.384
957471AF2-041 GEN
Solar/Wind Harmer
16.585
962761AG1-125 GEN
Solar/Wind Harmer
32.401
24686505CER G6
Adder
8.903
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.084
270437AC2-090 C
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.58
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.861
274802UNIV PARK;5U
Adder
5.55
274732ELWOOD EC;7P
Adder
15.615
274674JOLIET 9 ;6U
Adder
14.625
939401AE1-172 GEN
Solar/Wind Harmer
4.951
962781AG1-127 GEN
Solar/Wind Harmer
6.263
270459AD2-067 GEN
Solar/Wind Harmer
0
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
24691005MDL-2G C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
274728ELWOOD EC;5P
Adder
15.615
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
270186AC1-089 GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.324
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
970825AG2-519 GEN
Solar/Wind Harmer
5.122
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
965021AG1-366 GEN
Solar/Wind Harmer
2.244
274772LINCOLN ;3U
Adder
8.061
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
972259AH1-714 GEN
Adder
18.154
274729ELWOOD EC;1P
Adder
15.615
246938BC-WTG3
Solar/Wind Harmer
0.239
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
237048AF1-022 C
Solar/Wind Helper
0.182
238175AF1-290_GEN
Solar/Wind Helper
0.12
24289405MTG1
50/50
6.078
970149AG2-104 GEN
Solar/Wind Harmer
17.497
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.164
970091AG2-072 GEN
Adder
75.485
970773AG2-487 GEN
Solar/Wind Harmer
1.2
944971AF1-162 GEN
Solar/Wind Harmer
6.766
971917AH1-482 GEN
Solar/Wind Harmer
8.743
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
941551AE2-152 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
9.18
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
971073AG2-665 GEN
Solar/Wind Harmer
5.121
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
944541AF1-119 GEN
Solar/Wind Harmer
0.456
970329AG2-216 GEN
Solar/Wind Harmer
2.946
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270031AE2-169
Solar/Wind Harmer
3.738
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.14
247620Y3-023
Adder
0.44
972045AH1-571 GEN
Solar/Wind Harmer
1.386
958011AF2-095 GEN
Solar/Wind Harmer
9.564
274695ROCKY RD ;2P
Adder
10.523
958491AF2-143 GEN
Solar/Wind Harmer
9.89
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.875
235531U2-073 GEN
Solar/Wind Helper
2.924
971985AH1-537 GEN
Solar/Wind Harmer
2.118
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270291AC1-194 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
247536S-71 GEN
Solar/Wind Harmer
0.272
972165AH1-665 GEN
Solar/Wind Harmer
6.065
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
965051AG1-369 GEN
Solar/Wind Harmer
3.331
270399AC1-101 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972037AH1-567 GEN1
Adder
0.174
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
971171AH1-044 GEN
Solar/Wind Harmer
11.056
270263AC1-001 GEN
Solar/Wind Harmer
0.702
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
945631AF1-228 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.757
961821AG1-024 GEN
Solar/Wind Harmer
4.113
25196508WSDLE4
Adder
8.396
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
972163AH1-664 GEN
Solar/Wind Harmer
7.573
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
959331AF2-224 GEN
Solar/Wind Harmer
4.711
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270400AC1-102 GEN
Solar/Wind Harmer
2.112
274776LINCOLN ;7U
Adder
8.061
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274746AC1-111 G10
Adder
5.296
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
1.983
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.373
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
276776AD2-060 GEN
Solar/Wind Harmer
0.708
276901AD2-066 C O1
Solar/Wind Harmer
0
971125AH1-004 GEN
Solar/Wind Harmer
2.63
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274735ELWOOD EC;4P
Adder
15.615
957201AF2-014 GEN
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
5.296
970169AG2-114 GEN
Solar/Wind Harmer
6.598
959341AF2-225 GEN
Solar/Wind Harmer
6.91
270166AC1-044 GEN3
50/50
5.522
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.052
25196808ZIMRHP
Adder
74.904
25196008MFTGT1
Adder
1.367
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
939741AE1-205 GEN
Solar/Wind Harmer
9.213
970569AG2-363 GEN
Solar/Wind Harmer
19.691
23583801GRNGAP
Solar/Wind Helper
4.45
238126S14_GEN_1
Solar/Wind Helper
0.726
270119AB2-067 GEN1
50/50
5.522
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
1.164
25326509SID D
Adder
1.282
942221AE2-234 GEN
Solar/Wind Harmer
2.725
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.903
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
4.783
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
274696ROCKY RD ;4P
Adder
10.771
274697ROCKY RD ;3P
Adder
2.859
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
970107AG2-081 GEN
Solar/Wind Harmer
1.973
23751201ROTHROCK
Solar/Wind Helper
0.867
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.62
MW Contribution:
4.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252519AF1-045_GEN
Solar/Wind Harmer
3.611
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
946031AF1-268 GEN
Solar/Wind Harmer
6.472
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24686405CER G5
Adder
8.833
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.57
970191AG2-125 GEN
Solar/Wind Harmer
1.771
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.475
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270120AB2-067 GEN2
50/50
5.522
25194408D.CRK1
Adder
7.485
270054AF2-122 C O1
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
4.003
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
270462AD2-086
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
6.229
24725505WLD G2 C
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
10.122
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
966841AG1-555 GEN
Solar/Wind Harmer
0.761
270247TR4_N_V136
Solar/Wind Harmer
0.043
972043AH1-570 GEN
Solar/Wind Harmer
1.73
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
958481AF2-142 GEN
Solar/Wind Harmer
9.909
274693ROCKY RD ;1P
Adder
10.419
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23585401KL_K28_T16
Solar/Wind Helper
1.41
238117U2-030
Solar/Wind Helper
0.306
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
32.401
24686505CER G6
Adder
8.903
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.084
270437AC2-090 C
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.58
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.861
274802UNIV PARK;5U
Adder
5.55
274732ELWOOD EC;7P
Adder
15.615
274674JOLIET 9 ;6U
Adder
14.625
939401AE1-172 GEN
Solar/Wind Harmer
4.951
962781AG1-127 GEN
Solar/Wind Harmer
6.263
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
252516AE2-318_GEN
Solar/Wind Harmer
7.753
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
965651AG1-433 GEN
Solar/Wind Harmer
2.002
970613AG2-401 GEN
Solar/Wind Harmer
5
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.147
274812UNIV PK N;8U
Adder
4.772
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274676JOLIET 29;8U
Adder
29.146
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
270459AD2-067 GEN
Solar/Wind Harmer
0
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
24691005MDL-2G C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
274728ELWOOD EC;5P
Adder
15.615
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
270186AC1-089 GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.324
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
970825AG2-519 GEN
Solar/Wind Harmer
5.122
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
965021AG1-366 GEN
Solar/Wind Harmer
2.244
274772LINCOLN ;3U
Adder
8.061
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
972259AH1-714 GEN
Adder
18.154
274729ELWOOD EC;1P
Adder
15.615
246938BC-WTG3
Solar/Wind Harmer
0.239
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
237048AF1-022 C
Solar/Wind Helper
0.182
238175AF1-290_GEN
Solar/Wind Helper
0.12
942051AE2-217 GEN
Solar/Wind Harmer
12.564
252507AC2-088 GEN
Solar/Wind Harmer
0.312
961921AG1-034 GEN
Solar/Wind Harmer
6.169
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
944531AF1-118 GEN
Solar/Wind Harmer
30.627
958171AF2-111 GEN
Solar/Wind Harmer
16.988
971347AH1-153 GEN
Solar/Wind Harmer
3.374
970781AG2-491 GEN
Solar/Wind Harmer
6.73
24728705AND G3
Adder
7.73
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.861
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
970707AG2-453 GEN
Solar/Wind Harmer
21.689
274730ELWOOD EC;6P
Adder
15.615
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
959611AF2-252 GEN
Solar/Wind Harmer
2.189
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
238127S14_GEN_2
Solar/Wind Helper
0.726
24289405MTG1
50/50
6.078
970149AG2-104 GEN
Solar/Wind Harmer
17.497
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.164
970091AG2-072 GEN
Adder
75.485
970773AG2-487 GEN
Solar/Wind Harmer
1.2
944971AF1-162 GEN
Solar/Wind Harmer
6.766
971917AH1-482 GEN
Solar/Wind Harmer
8.743
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
941551AE2-152 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
9.18
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
971073AG2-665 GEN
Solar/Wind Harmer
5.121
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
944541AF1-119 GEN
Solar/Wind Harmer
0.456
970329AG2-216 GEN
Solar/Wind Harmer
2.946
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270031AE2-169
Solar/Wind Harmer
3.738
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.14
247620Y3-023
Adder
0.44
972045AH1-571 GEN
Solar/Wind Harmer
1.386
958011AF2-095 GEN
Solar/Wind Harmer
9.564
274695ROCKY RD ;2P
Adder
10.523
958491AF2-143 GEN
Solar/Wind Harmer
9.89
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.875
235531U2-073 GEN
Solar/Wind Helper
2.924
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.861
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
276843GEN-1.7
Solar/Wind Harmer
0.215
274803UNIV PARK;6U
Adder
5.55
972038AH1-567 GEN2
Adder
0.347
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
965091AG1-374 GEN
Solar/Wind Harmer
19.702
23562501BACKB
Solar/Wind Helper
1.069
238108AE1-109 GEN1
Solar/Wind Helper
0.096
971985AH1-537 GEN
Solar/Wind Harmer
2.118
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270291AC1-194 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
247536S-71 GEN
Solar/Wind Harmer
0.272
972165AH1-665 GEN
Solar/Wind Harmer
6.065
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
965051AG1-369 GEN
Solar/Wind Harmer
3.331
270399AC1-101 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972037AH1-567 GEN1
Adder
0.174
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
971171AH1-044 GEN
Solar/Wind Harmer
11.056
270263AC1-001 GEN
Solar/Wind Harmer
0.702
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
945631AF1-228 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.757
961821AG1-024 GEN
Solar/Wind Harmer
4.113
25196508WSDLE4
Adder
8.396
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
972163AH1-664 GEN
Solar/Wind Harmer
7.573
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
959331AF2-224 GEN
Solar/Wind Harmer
4.711
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270400AC1-102 GEN
Solar/Wind Harmer
2.112
274776LINCOLN ;7U
Adder
8.061
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274746AC1-111 G10
Adder
5.296
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
1.983
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.373
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
276776AD2-060 GEN
Solar/Wind Harmer
0.708
276901AD2-066 C O1
Solar/Wind Harmer
0
971125AH1-004 GEN
Solar/Wind Harmer
2.63
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.696
274811UNIV PK N;7U
Adder
4.772
276806AD2-047 C O1
Solar/Wind Harmer
3.764
24695305TIMB G C
Solar/Wind Harmer
0.562
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274682WAUKEGAN ;7U
Adder
3.428
964991AG1-363 GEN
Solar/Wind Helper
3.896
238110AE1-109 GEN3
Solar/Wind Helper
0.096
959091AF2-200 GEN
Solar/Wind Harmer
11.056
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25306009OHH W.
Adder
2.85
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
970289AG2-191 GEN
Solar/Wind Harmer
1.292
963791AG1-232 GEN
Solar/Wind Harmer
9.106
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
972227AH1-698 GEN1
Adder
2.483
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274735ELWOOD EC;4P
Adder
15.615
957201AF2-014 GEN
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
5.296
970169AG2-114 GEN
Solar/Wind Harmer
6.598
959341AF2-225 GEN
Solar/Wind Harmer
6.91
270166AC1-044 GEN3
50/50
5.522
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.052
25196808ZIMRHP
Adder
74.904
25196008MFTGT1
Adder
1.367
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
939741AE1-205 GEN
Solar/Wind Harmer
9.213
970569AG2-363 GEN
Solar/Wind Harmer
19.691
23583801GRNGAP
Solar/Wind Helper
4.45
238126S14_GEN_1
Solar/Wind Helper
0.726
270119AB2-067 GEN1
50/50
5.522
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
1.164
25326509SID D
Adder
1.282
942221AE2-234 GEN
Solar/Wind Harmer
2.725
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.903
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
4.783
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
274696ROCKY RD ;4P
Adder
10.771
274697ROCKY RD ;3P
Adder
2.859
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
970107AG2-081 GEN
Solar/Wind Harmer
1.973
23751201ROTHROCK
Solar/Wind Helper
0.867
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2430.97
MW Contribution:
2.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
26.903
24689505VACITY
50/50
3.164
962751AG1-124 GEN
Solar/Wind Harmer
6.205
972273AH1-721 GEN
Adder
50.356
970093AG2-073 GEN
Solar/Wind Harmer
3.273
972167AH1-666 GEN
Solar/Wind Harmer
2.762
942481AE2-261 GEN
Solar/Wind Harmer
10.082
971993AH1-541 GEN
Solar/Wind Harmer
1.535
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
0.634
270367AC2-061_GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.482
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
946671AF1-331 GEN
Solar/Wind Harmer
0.345
274729ELWOOD EC;1P
Adder
7.484
270240V3-007_GEN2
Solar/Wind Harmer
0
970107AG2-081 GEN
Solar/Wind Harmer
1.103
276838X2-022 GEN2
Solar/Wind Harmer
0.188
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.528
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
942111AE2-223 GEN
Solar/Wind Harmer
1.06
24728305BUCHG2
Adder
3.63
24686505CER G6
Adder
4.748
3429241JKCT 3G
Adder
6.43
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276708O09 GEN2
Solar/Wind Harmer
0.116
274766LEE CO EC;7U
Adder
4.297
962781AG1-127 GEN
Solar/Wind Harmer
3.062
971485AH1-239 GEN
Solar/Wind Harmer
3.377
964781AG1-341 GEN
Solar/Wind Harmer
4.305
942891AE2-308 GEN
Solar/Wind Harmer
3.798
972043AH1-570 GEN
Solar/Wind Harmer
0.938
276615X2-022 GEN
Solar/Wind Harmer
0.035
945391AF1-204 GEN
Solar/Wind Harmer
3.538
960611AF2-352 GEN
Solar/Wind Harmer
1.092
274764LEE CO EC;5U
Adder
4.358
972235AH1-702 GEN1
Adder
1.172
276876AE1-163_GEN2
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.364
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
274693ROCKY RD ;1P
Adder
5.064
958481AF2-142 GEN
Solar/Wind Harmer
4.795
24728905RICHG2
Adder
1.729
24697605MDL-3G C
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.01
926881AC1-175 GEN
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
2.854
970883AG2-550 GEN
Solar/Wind Harmer
3.108
960971AF2-388 GEN
Solar/Wind Harmer
1.8
24734705WLF1G3
50/50
5.196
24734905WLF1G5
50/50
5.196
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.671
270399AC1-101 GEN
Solar/Wind Harmer
1.444
339216AC1-074 GEN
Solar/Wind Harmer
0.095
972165AH1-665 GEN
Solar/Wind Harmer
3.094
946321AF1-296 GEN
Solar/Wind Harmer
1.85
972267AH1-718 GEN
Adder
1.953
274823ROCKFORD ;21
Adder
9.053
971171AH1-044 GEN
Solar/Wind Harmer
6.475
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.845
24386405FR-21G C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.499
970833AG2-524 GEN
Solar/Wind Harmer
2.333
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
960591AF2-350 GEN
Solar/Wind Harmer
3.162
971611AH1-305 GEN
Solar/Wind Harmer
1.876
971985AH1-537 GEN
Solar/Wind Harmer
0.936
959141AF2-205 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
4.672
253406AD2-031_GEN
Solar/Wind Harmer
0.23
247536S-71 GEN
Solar/Wind Harmer
0.124
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
1.809
3148013FISHERV
Solar/Wind Helper
0.165
316405AF2-144 C
Solar/Wind Helper
0.151
3143873LANEXA
Solar/Wind Helper
0.067
971461AH1-227 GEN
Solar/Wind Harmer
2.687
3429391JKCT 9G
Adder
4.482
958171AF2-111 GEN
Solar/Wind Harmer
8.524
970193AG2-126 GEN
Solar/Wind Harmer
4.994
24728705AND G3
Adder
3.771
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.146
274855GSG-6 ;RU
Solar/Wind Harmer
0.118
276868AE1-113 GEN
Solar/Wind Harmer
0.643
274879MINONK ;1U
Solar/Wind Harmer
0.134
25196608WSDLE5
Adder
3.933
274862TOP CROP ;2U
Solar/Wind Harmer
0.432
970781AG2-491 GEN
Solar/Wind Harmer
3.187
274730ELWOOD EC;6P
Adder
7.484
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.354
274887GEN-1.85
Solar/Wind Harmer
0.082
944531AF1-118 GEN
Solar/Wind Harmer
13.572
971347AH1-153 GEN
Solar/Wind Harmer
1.512
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
238152AF2-075_GEN
Solar/Wind Helper
0.306
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
943031AE2-326 GEN
Solar/Wind Harmer
3.912
960911AF2-382 GEN
Solar/Wind Harmer
4.078
972103AH1-617 GEN
Solar/Wind Harmer
9.709
270030AE2-140 GEN
Solar/Wind Harmer
7.666
957381AF2-032 GEN
Solar/Wind Harmer
0.764
971087AG2-675 GEN
Solar/Wind Harmer
1.765
24728505AND G1
Adder
1.803
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
959091AF2-200 GEN
Solar/Wind Harmer
6.475
252519AF1-045_GEN
Solar/Wind Harmer
1.674
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
943121AE2-341 GEN
Solar/Wind Harmer
5.351
943591AF1-030 GEN
Solar/Wind Harmer
3.559
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
3.003
276806AD2-047 C O1
Solar/Wind Harmer
1.792
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
4.107
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
946031AF1-268 GEN
Solar/Wind Harmer
2.979
316192AB2-158 GEN
Solar/Wind Helper
0.989
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
971125AH1-004 GEN
Solar/Wind Harmer
1.471
971587AH1-292 GEN
Solar/Wind Harmer
2.505
276916AD2-100_GEN
Solar/Wind Harmer
7.095
971341AH1-150 GEN
Solar/Wind Harmer
6.475
971343AH1-151 GEN
Solar/Wind Harmer
6.475
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.337
970291AG2-192 GEN
Solar/Wind Harmer
0.41
970291AG2-192 GEN
Solar/Wind Harmer
0.189
971613AH1-306 GEN
Solar/Wind Harmer
1.512
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
3.818
238147AE2-230_GEN1
Solar/Wind Helper
0.214
316097T157 G90
Solar/Wind Helper
0.557
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
24735205WLF2G2
50/50
5.207
24723205RIVRG3
Adder
11.612
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
6.034
943811AF1-049 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
6.517
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
9.712
252516AE2-318_GEN
Solar/Wind Harmer
3.594
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.557
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
13.963
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.159
970613AG2-401 GEN
Solar/Wind Harmer
2.314
270055AF2-134 C O1
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
6.407
944971AF1-162 GEN
Solar/Wind Harmer
4.503
970653AG2-424 GEN
Solar/Wind Harmer
1.862
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.003
970091AG2-072 GEN
Adder
38.065
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
7.714
970819AG2-516 GEN
Solar/Wind Harmer
3.898
274822ROCKFORD ;11
Adder
9.119
959081AF2-199 GEN
Solar/Wind Harmer
3.237
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274872LEEDK;1U
Solar/Wind Harmer
0
24686405CER G5
Adder
4.71
970653AG2-424 GEN
Solar/Wind Harmer
0.386
970455AG2-298 GEN
Solar/Wind Harmer
1.477
965931AG1-462 GEN
Solar/Wind Harmer
8.44
965091AG1-374 GEN
Solar/Wind Harmer
9.832
274878BISHOP HL;2U
Solar/Wind Harmer
0.109
274760LEE CO EC;1U
Adder
4.348
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.102
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
0.68
964401AG1-302 GEN
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
0.781
3146776BUCKING
Solar/Wind Helper
0.05
316337AD2-073 GEN
Solar/Wind Helper
0.173
3141726DUNNSVL
Solar/Wind Helper
0.452
971277AH1-098 GEN
Solar/Wind Harmer
2.311
24728205BUCHG1
Adder
3.63
966021AG1-471 GEN
Solar/Wind Harmer
2.29
964571AG1-320 GEN
Solar/Wind Harmer
3.443
972045AH1-571 GEN
Solar/Wind Harmer
0.751
276911AD2-131_GEN
Solar/Wind Harmer
0.467
274765LEE CO EC;6U
Adder
4.358
274763LEE CO EC;4U
Adder
4.307
972236AH1-702 GEN2
Adder
1.019
252509AD1-136 GEN
Solar/Wind Harmer
0.016
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.815
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
0.65
274695ROCKY RD ;2P
Adder
5.115
24728805RICHG1
Adder
1.729
270180AB1-006 GEN1
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
4.553
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.712
970885AG2-551 GEN
Solar/Wind Harmer
1.036
964611AG1-324 GEN
Solar/Wind Harmer
0.233
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.205
965791AG1-447 GEN
Solar/Wind Harmer
2.8
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316045AC1-158 PL2
Solar/Wind Helper
2.117
24735105WLF2G1
50/50
5.207
274762LEE CO EC;3U
Adder
4.348
970241AG2-163 GEN
Solar/Wind Harmer
1.901
938861AE1-114 GEN
Solar/Wind Harmer
1.845
962581AG1-107 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.643
274696ROCKY RD ;4P
Adder
5.236
274697ROCKY RD ;3P
Adder
1.389
276893AG1-478 C
Solar/Wind Harmer
0.212
957841AF2-078 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
0.184
970941AG2-585 GEN
Solar/Wind Harmer
1.739
942221AE2-234 GEN
Solar/Wind Harmer
1.218
237061AD1-155 GEN
Solar/Wind Helper
0.84
316312AB1-027
Solar/Wind Helper
0.234
3143526WINTERP
Solar/Wind Helper
0.609
971687AH1-348 GEN
Solar/Wind Harmer
0.521
276621W2-048 GEN
Solar/Wind Harmer
0.167
25196008MFTGT1
Adder
0.654
25196808ZIMRHP
Adder
35.505
939741AE1-205 GEN
Solar/Wind Harmer
4.566
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.348
970569AG2-363 GEN
Solar/Wind Harmer
9.723
971997AH1-543 GEN
Solar/Wind Harmer
1.689
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.024
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.938
270594AE1-207 GEN
Solar/Wind Harmer
3.528
270032AE2-172
Solar/Wind Harmer
2.1
970825AG2-519 GEN
Solar/Wind Harmer
1.115
270005AE1-210 C O1
Solar/Wind Harmer
0.68
964861AG1-349 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.9
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
0.937
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
316095T157 G97
Solar/Wind Helper
0.557
3142946ENON
Solar/Wind Helper
0.038
253398AE2-221_GEN2
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.334
315821AE2-092 GEN
Solar/Wind Helper
1.831
23583801GRNGAP
Solar/Wind Helper
2.128
316075AC2-137 C
Solar/Wind Helper
0.18
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
971313AH1-133 GEN
Solar/Wind Harmer
2.637
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
971681AH1-341 GEN
Solar/Wind Harmer
5.242
274856ECOGROVE ;U1
Solar/Wind Harmer
0.076
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276863AD2-134 GEN
Solar/Wind Harmer
0.058
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
4.049
316404AE1-155 C
Solar/Wind Helper
0.959
970349AG2-230 GEN
Solar/Wind Harmer
4.536
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316450AC1-158 RIC
Solar/Wind Helper
0.176
316487AF1-042 GEN
Solar/Wind Helper
0.113
24385905FR-11G C
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.397
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
276903AD2-071 C
Solar/Wind Harmer
3.542
270437AC2-090 C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Helper
0.287
3147666LOUISA
Solar/Wind Helper
0.335
3141906WESTMOR
Solar/Wind Helper
0.046
970281AG2-184 GEN
Solar/Wind Harmer
10.194
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.131
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.131
274877BISHOP HL;1U
Solar/Wind Harmer
0.109
276741O09 GEN1
Solar/Wind Harmer
0.116
959341AF2-225 GEN
Solar/Wind Harmer
3.424
970169AG2-114 GEN
Solar/Wind Harmer
3.232
274744AC1-111 GEN8
Adder
2.557
274735ELWOOD EC;4P
Adder
7.484
970289AG2-191 GEN
Solar/Wind Harmer
0.599
958391AF2-133 GEN
Solar/Wind Harmer
0
3148463FAIRFLD
Solar/Wind Helper
0.399
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316059AD1-063 C
Solar/Wind Helper
0.113
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
7.484
270543AE2-219 C
Solar/Wind Harmer
2.176
270071AF1-092 GEN
Solar/Wind Harmer
5.772
3148133STUARTS
Solar/Wind Helper
0.172
316258AE1-075 C
Solar/Wind Helper
0.181
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
3141426STAFORD
Solar/Wind Helper
0.025
970825AG2-519 GEN
Solar/Wind Harmer
2.365
253394AE2-221_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
7.973
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.643
3147983MERCK5
Solar/Wind Helper
0.108
3143526WINTERP
Solar/Wind Helper
0.609
964211AG1-282 GEN
Solar/Wind Helper
0.152
24734805WLF1G4
50/50
5.196
270400AC1-102 GEN
Solar/Wind Harmer
1.444
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
10.049
3429211JKCT 2G
Adder
6.347
972163AH1-664 GEN
Solar/Wind Harmer
3.863
944221AF1-090 GEN
Solar/Wind Harmer
1.996
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
270356AE2-297 GEN
Solar/Wind Harmer
0
25196508WSDLE4
Adder
3.893
274746AC1-111 G10
Adder
2.557
946581AF1-322 GEN
Solar/Wind Harmer
0
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
971609AH1-304 GEN
Solar/Wind Harmer
0.508
964611AG1-324 GEN
Solar/Wind Harmer
1.21
960681AF2-359 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
316164AC1-076 GEN
Solar/Wind Helper
0.62
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141813NORNECK
Solar/Wind Helper
0.113
276882AE2-255 GEN
Solar/Wind Harmer
0.375
970773AG2-487 GEN
Solar/Wind Harmer
0.568
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
941551AE2-152 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.068
970373AG2-245 GEN
Solar/Wind Harmer
6.5
3132273ORANGE
Solar/Wind Helper
0.03
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
316223AC1-118
Solar/Wind Helper
0.174
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
4.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
971125AH1-004 GEN
Solar/Wind Harmer
2.78
971587AH1-292 GEN
Solar/Wind Harmer
4.796
276916AD2-100_GEN
Solar/Wind Harmer
13.351
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
5.363
971061AG2-657 GEN
Solar/Wind Harmer
5.362
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
24691005MDL-2G C
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.033
270543AE2-219 C
Solar/Wind Harmer
4.252
274728ELWOOD EC;5P
Adder
14.264
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.089
24684605SMG4
50/50
2.21
970563AG2-360 GEN
50/50
45.796
962751AG1-124 GEN
Solar/Wind Harmer
12.886
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
972273AH1-721 GEN
Adder
89.23
970093AG2-073 GEN
Solar/Wind Harmer
6.071
24684505SMG3
50/50
1.341
3147312GRETNA
Solar/Wind Harmer
0.047
971687AH1-348 GEN
Solar/Wind Harmer
0.947
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252510AF1-249 C
Solar/Wind Harmer
0.048
276621W2-048 GEN
Solar/Wind Harmer
0.315
253398AE2-221_GEN2
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24386605FR-22G C
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
970569AG2-363 GEN
Solar/Wind Harmer
18.425
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276805AD2-038 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
964861AG1-349 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
315821AE2-092 GEN
Solar/Wind Helper
3.23
23583801GRNGAP
Solar/Wind Helper
4.295
970107AG2-081 GEN
Solar/Wind Harmer
2.085
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
1.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
960201AF2-311 GEN
Solar/Wind Harmer
5.7
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
274762LEE CO EC;3U
Adder
8.213
938861AE1-114 GEN
Solar/Wind Harmer
3.487
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
274696ROCKY RD ;4P
Adder
9.947
274697ROCKY RD ;3P
Adder
2.64
276893AG1-478 C
Solar/Wind Harmer
0.404
276897AD1-100 C
Solar/Wind Harmer
15.124
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
970941AG2-585 GEN
Solar/Wind Harmer
3.319
237061AD1-155 GEN
Solar/Wind Helper
1.647
24290705CLAY-2
50/50
0.252
958131AF2-107 GEN
Solar/Wind Harmer
5.335
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
960001AF2-291 GEN
Solar/Wind Harmer
0
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
970091AG2-072 GEN
Adder
73.941
971073AG2-665 GEN
Solar/Wind Harmer
1.065
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
970819AG2-516 GEN
Solar/Wind Harmer
7.371
274822ROCKFORD ;11
Adder
17.258
24728205BUCHG1
50/50
7.157
971277AH1-098 GEN
Solar/Wind Harmer
5.174
970913AG2-568 GEN
Solar/Wind Harmer
7.67
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
964571AG1-320 GEN
Solar/Wind Harmer
6.355
972045AH1-571 GEN
Solar/Wind Harmer
1.437
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
276911AD2-131_GEN
Solar/Wind Harmer
0.879
24728805RICHG1
Adder
3.383
24699105WLD G1 C
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
8.233
274763LEE CO EC;4U
Adder
8.136
270383AD1-128 GEN
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274695ROCKY RD ;2P
Adder
9.717
970885AG2-551 GEN
Solar/Wind Harmer
2.025
270031AE2-169
Solar/Wind Harmer
3.328
964611AG1-324 GEN
Solar/Wind Harmer
0.453
958011AF2-095 GEN
Solar/Wind Harmer
8.691
270201AC2-176 GEN
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
24684305SMG1
50/50
0.795
971329AH1-144 GEN
Solar/Wind Harmer
6.744
24734805WLF1G4
Adder
8.187
24735105WLF2G1
Adder
8.017
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
3429211JKCT 2G
Adder
11.861
972163AH1-664 GEN
Solar/Wind Harmer
7.559
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196508WSDLE4
Adder
7.759
270356AE2-297 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.696
274854TWINGROVE;U2
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.044
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.61
274746AC1-111 G10
Adder
4.865
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
971609AH1-304 GEN
Solar/Wind Harmer
0.988
964611AG1-324 GEN
Solar/Wind Harmer
2.357
316164AC1-076 GEN
Solar/Wind Helper
1.176
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
5.792
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
972043AH1-570 GEN
Solar/Wind Harmer
1.794
25194408D.CRK1
Adder
6.93
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276615X2-022 GEN
Solar/Wind Harmer
0.065
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960611AF2-352 GEN
Solar/Wind Harmer
2.071
966841AG1-555 GEN
Solar/Wind Harmer
0.701
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
972235AH1-702 GEN1
Adder
2.217
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274693ROCKY RD ;1P
Adder
9.622
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
274674JOLIET 9 ;6U
Adder
13.36
270599AE1-208 GEN
Solar/Wind Harmer
5.547
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316450AC1-158 RIC
Solar/Wind Helper
0.337
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270069AE2-166 C O1
Solar/Wind Harmer
10.375
24734705WLF1G3
Adder
8.187
24734905WLF1G5
Adder
8.187
270399AC1-101 GEN
Solar/Wind Harmer
2.889
971981AH1-535 GEN
Solar/Wind Harmer
5.838
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
253406AD2-031_GEN
Solar/Wind Harmer
0.464
946321AF1-296 GEN
Solar/Wind Harmer
3.479
270291AC1-194 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
971029AG2-637 GEN
Solar/Wind Harmer
9.145
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.242
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148013FISHERV
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.267
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.731
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
9.535
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
3429391JKCT 9G
Adder
8.393
958171AF2-111 GEN
Solar/Wind Harmer
16.661
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
24728705AND G3
Adder
7.274
959611AF2-252 GEN
Solar/Wind Harmer
2.071
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
274730ELWOOD EC;6P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316044AC1-158 PL1
Solar/Wind Helper
1.262
971343AH1-151 GEN
Solar/Wind Harmer
12.26
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.644
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
970281AG2-184 GEN
Solar/Wind Harmer
18.909
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
959341AF2-225 GEN
Solar/Wind Harmer
6.498
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
970169AG2-114 GEN
Solar/Wind Harmer
6.143
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274744AC1-111 GEN8
Adder
4.865
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
958391AF2-133 GEN
Solar/Wind Harmer
0.001
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
971881AH1-461 GEN
50/50
14.967
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147123OTTER R
Solar/Wind Harmer
0.13
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24721905FLATG4
Adder
21.662
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971087AG2-675 GEN
Solar/Wind Harmer
3.318
274767LEE CO EC;8U
Adder
8.117
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
276806AD2-047 C O1
Solar/Wind Harmer
3.42
316192AB2-158 GEN
Solar/Wind Helper
1.845
316447AC1-158 HLD
Solar/Wind Helper
2.777
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
7.447
24686405CER G5
Adder
9.787
970653AG2-424 GEN
Solar/Wind Harmer
0.705
970455AG2-298 GEN
Solar/Wind Harmer
2.725
965931AG1-462 GEN
Solar/Wind Harmer
15.863
965091AG1-374 GEN
Solar/Wind Harmer
18.636
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
24690905MDL-1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276843GEN-1.7
Solar/Wind Harmer
0.195
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
941551AE2-152 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
7.838
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
24735205WLF2G2
Adder
8.017
24723205RIVRG3
Adder
22.932
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
945681AF1-233 GEN
Solar/Wind Harmer
12.766
252516AE2-318_GEN
Solar/Wind Harmer
7.186
25194608D.CRK4
Adder
1.506
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
957471AF2-041 GEN
Solar/Wind Harmer
18.391
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.865
274871GR RIDGE ;2U
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
18.034
972167AH1-666 GEN
Solar/Wind Harmer
5.413
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.251
970879AG2-548 GEN
Solar/Wind Harmer
4.688
942481AE2-261 GEN
Solar/Wind Harmer
18.979
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
12.283
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
946671AF1-331 GEN
Solar/Wind Harmer
0.653
970825AG2-519 GEN
Solar/Wind Harmer
4.603
274729ELWOOD EC;1P
Adder
14.264
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
3147983MERCK5
Solar/Wind Helper
0.198
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
26.611
316499AE2-029_GEN
Solar/Wind Helper
1.726
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.195
24728305BUCHG2
50/50
7.157
24686505CER G6
Adder
9.865
3429241JKCT 3G
Adder
12.016
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
270437AC2-090 C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.58 %
Rating:3039.0 MVA
Rating Type:B
MVA to Mitigate:3208.68
MW Contribution:
7.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274772LINCOLN ;3U
Adder
7.265
274724RIVER EC ;11
Adder
15.124
972259AH1-714 GEN
Adder
16.155
274729ELWOOD EC;1P
Adder
13.819
971993AH1-541 GEN
Solar/Wind Harmer
2.606
970571AG2-364 GEN
Solar/Wind Harmer
11.227
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274850MENDOTA H;RU
Solar/Wind Harmer
0.065
270505AE1-170 C O1
Solar/Wind Harmer
5.856
945111AF1-176 GEN
Solar/Wind Harmer
4.457
942481AE2-261 GEN
Solar/Wind Harmer
16.362
270043AE2-236 GEN
Solar/Wind Harmer
2.578
965021AG1-366 GEN
Solar/Wind Harmer
1.022
270186AC1-089 GEN
Solar/Wind Helper
0.822
270367AC2-061_GEN
Solar/Wind Helper
1.691
253394AE2-221_GEN
Solar/Wind Helper
1.24
942601AE2-276 GEN
50/50
8.364
270100X2-052 CT1
50/50
1.319
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.216
274770LINCOLN ;1U
Adder
7.265
274771LINCOLN ;2U
Adder
7.265
274805UNIV PK N;1U
Adder
4.283
276897AD1-100 C
Solar/Wind Harmer
14.818
274888KELLY CRK;1U
Solar/Wind Harmer
0.345
970941AG2-585 GEN
Solar/Wind Harmer
3.257
276893AG1-478 C
Solar/Wind Harmer
0.391
942111AE2-223 GEN
Solar/Wind Harmer
1.876
274697ROCKY RD ;3P
Adder
2.478
274696ROCKY RD ;4P
Adder
9.338
962691AG1-118 GEN
Solar/Wind Harmer
17.022
276838X2-022 GEN2
Solar/Wind Harmer
0.314
276645AC1-214 GEN1
Solar/Wind Harmer
0.217
938861AE1-114 GEN
Solar/Wind Harmer
3.095
274762LEE CO EC;3U
Adder
7.252
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.873
962581AG1-107 GEN
Solar/Wind Helper
0.905
961491AF2-440 GEN
Solar/Wind Helper
0.037
339236AF1-050_GEN
Solar/Wind Helper
0.404
24385905FR-11G C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
7.074
274802UNIV PARK;5U
Adder
4.947
939401AE1-172 GEN
Solar/Wind Harmer
4.39
274732ELWOOD EC;7P
Adder
13.819
274674JOLIET 9 ;6U
Adder
12.932
962781AG1-127 GEN
Solar/Wind Harmer
5.386
965911AG1-460 GEN
Solar/Wind Harmer
1.094
274766LEE CO EC;7U
Adder
7.166
276708O09 GEN2
Solar/Wind Harmer
0.191
339211AE2-254 GEN
Solar/Wind Helper
0.448
253333AC1-068 GEN
Solar/Wind Helper
0.484
270102X2-052 ST
50/50
1.428
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.892
945391AF1-204 GEN
Solar/Wind Harmer
6.551
970349AG2-230 GEN
Solar/Wind Harmer
9.139
274808UNIV PK N;4U
Adder
4.255
274674JOLIET 9 ;6U
Adder
12.932
958481AF2-142 GEN
Solar/Wind Harmer
8.668
960611AF2-352 GEN
Solar/Wind Harmer
1.91
274693ROCKY RD ;1P
Adder
9.033
274683WAUKEGAN ;8U
Adder
17.208
274683WAUKEGAN ;8U
Adder
14.506
276876AE1-163_GEN2
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.058
972235AH1-702 GEN1
Adder
1.993
961051AF2-396 GEN
Solar/Wind Harmer
11.03
961051AF2-396 GEN
Solar/Wind Harmer
7.353
274764LEE CO EC;5U
Adder
7.269
944231AF1-091 GEN
Solar/Wind Harmer
7.025
253349AC2-067 GEN
Solar/Wind Helper
0.213
253415AE1-040 GEN
Solar/Wind Helper
0.484
24344205RKG1
50/50
11.252
24344205RKG1
50/50
11.252
270393AB1-087 CT1
50/50
2.513
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.661
959141AF2-205 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.265
274777LINCOLN ;8U
Adder
7.265
972228AH1-698 GEN2
Adder
3.144
960591AF2-350 GEN
Solar/Wind Harmer
5.921
972037AH1-567 GEN1
Adder
0.155
970833AG2-524 GEN
Solar/Wind Harmer
6.449
970833AG2-524 GEN
Solar/Wind Harmer
4.299
274675JOLIET 29;7U
Adder
25.765
274675JOLIET 29;7U
Adder
24.845
971675AH1-338 GEN
Solar/Wind Harmer
2.182
971411AH1-196 GEN
Solar/Wind Harmer
8.382
971171AH1-044 GEN
Solar/Wind Harmer
11.115
274823ROCKFORD ;21
Adder
15.441
972267AH1-718 GEN
Adder
3.215
946321AF1-296 GEN
Solar/Wind Harmer
2.925
970031AG2-029 GEN
Solar/Wind Harmer
2.434
339216AC1-074 GEN
Solar/Wind Helper
1.461
253406AD2-031_GEN
Solar/Wind Helper
0.712
270406AB1-088 CT1
50/50
2.513
970781AG2-491 GEN
Solar/Wind Harmer
8.082
970193AG2-126 GEN
Solar/Wind Harmer
9.249
971347AH1-153 GEN
Solar/Wind Harmer
3.046
274752CRETE EC ;2U
Adder
7.074
939351AE1-166 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
0.154
274826FISK ;BP
Adder
9.27
970707AG2-453 GEN
Solar/Wind Harmer
19.288
274730ELWOOD EC;6P
Adder
13.819
274862TOP CROP ;2U
Solar/Wind Harmer
0.78
959611AF2-252 GEN
Solar/Wind Harmer
1.91
276868AE1-113 GEN
Solar/Wind Harmer
1.141
274879MINONK ;1U
Solar/Wind Harmer
0.238
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Helper
1.471
24344305RKG2
50/50
11.018
274811UNIV PK N;7U
Adder
4.274
276806AD2-047 C O1
Solar/Wind Harmer
3.355
274734ELWOOD EC;8P
Adder
13.819
274736ELWOOD EC;9P
Adder
13.819
274676JOLIET 29;8U
Adder
24.844
943121AE2-341 GEN
Solar/Wind Harmer
9.707
943591AF1-030 GEN
Solar/Wind Harmer
6.455
274682WAUKEGAN ;7U
Adder
14.697
959091AF2-200 GEN
Solar/Wind Harmer
11.115
957381AF2-032 GEN
Solar/Wind Harmer
1.241
274767LEE CO EC;8U
Adder
7.166
971087AG2-675 GEN
Solar/Wind Harmer
2.768
247642Z2-115 C
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
0.419
252524AE2-267 GEN
Solar/Wind Helper
0.466
960071AF2-298 GEN
Solar/Wind Helper
0.355
971587AH1-292 GEN
Solar/Wind Harmer
7.361
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.77
276776AD2-060 GEN
Solar/Wind Harmer
0.632
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
11.115
971343AH1-151 GEN
Solar/Wind Harmer
11.115
276916AD2-100_GEN
Solar/Wind Harmer
11.472
970291AG2-192 GEN
Solar/Wind Harmer
0.495
970291AG2-192 GEN
Solar/Wind Harmer
0.229
971613AH1-306 GEN
Solar/Wind Harmer
1.445
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.274
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
25.765
274745AC1-111 GEN9
Adder
4.638
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
14.697
274828WAUKEGAN ;BP
Adder
9.02
957471AF2-041 GEN
Solar/Wind Harmer
16.672
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.118
943111AE2-339 GEN
Solar/Wind Helper
0.641
339241AF1-083 GEN
Solar/Wind Helper
0.404
970091AG2-072 GEN
50/50
218.725
270407AB1-088 ST1
50/50
2.513
970023AG2-014 GEN
50/50
2.694
970783AG2-492 GEN
50/50
2.694
24344105CKG2
50/50
6.799
971917AH1-482 GEN
Solar/Wind Harmer
9.763
963741AG1-226 GEN
Solar/Wind Harmer
17.105
970373AG2-245 GEN
Solar/Wind Harmer
14.697
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.939
274861TOP CROP ;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.666
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
5.557
971067AG2-660 GEN
Solar/Wind Harmer
1.852
274822ROCKFORD ;11
Adder
15.554
276646AC1-214 GEN2
Solar/Wind Harmer
0.217
943021AE2-325 GEN
Solar/Wind Harmer
2.884
970819AG2-516 GEN
Solar/Wind Harmer
6.595
339221AD2-048_GEN
Solar/Wind Helper
1.206
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274753CRETE EC ;3U
Adder
7.074
274814UNIV PK N;0U
Adder
4.311
274807UNIV PK N;3U
Adder
4.302
276843GEN-1.7
Solar/Wind Harmer
0.191
274803UNIV PARK;6U
Adder
4.947
972038AH1-567 GEN2
Adder
0.309
965091AG1-374 GEN
Solar/Wind Harmer
17.188
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
274760LEE CO EC;1U
Adder
7.252
965931AG1-462 GEN
Solar/Wind Harmer
13.235
339243AC2-075 GEN1
Solar/Wind Helper
0.336
339206AE1-143 GEN
Solar/Wind Helper
1.206
339255AE2-071 GEN
Solar/Wind Helper
0.153
339250AF1-203 GEN
Solar/Wind Helper
0.118
270518AE2-148 GEN
Solar/Wind Helper
5.631
253325AC1-069 GEN
Solar/Wind Helper
0.484
270101X2-052 CT2
50/50
1.319
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.698
958011AF2-095 GEN
Solar/Wind Harmer
8.526
958491AF2-143 GEN
Solar/Wind Harmer
8.594
274695ROCKY RD ;2P
Adder
9.123
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.733
276911AD2-131_GEN
Solar/Wind Harmer
0.756
274765LEE CO EC;6U
Adder
7.269
274763LEE CO EC;4U
Adder
7.183
247620Y3-023
Adder
0.342
252509AD1-136 GEN
Solar/Wind Helper
0.21
25183208HLCRTG
Solar/Wind Helper
2.03
253400AC2-068 GEN
Solar/Wind Helper
0.086
339231AF1-038_GEN
Solar/Wind Helper
0.394
270394AB1-087 ST1
50/50
2.513
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.267
960681AF2-359 GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
Adder
7.265
270526AF1-158 GEN
Solar/Wind Harmer
0
274687WILL CNTY;4U
Adder
23.495
274687WILL CNTY;4U
Adder
23.495
274731ELWOOD EC;2P
Adder
13.819
274733ELWOOD EC;3P
Adder
13.819
274746AC1-111 G10
Adder
4.638
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.958
944221AF1-090 GEN
Solar/Wind Harmer
3.186
959331AF2-224 GEN
Solar/Wind Harmer
2.147
270340AC2-060 GEN
Solar/Wind Helper
1.095
241972AD1-140 GEN
Solar/Wind Helper
2.071
253338AC1-165 GEN
Solar/Wind Helper
0.467
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.786
964861AG1-349 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
7.265
274774LINCOLN ;5U
Adder
7.265
274751CRETE EC ;1U
Adder
7.074
274723RIVER EC ;12
Adder
15.309
939741AE1-205 GEN
Solar/Wind Harmer
8.081
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3
970569AG2-363 GEN
Solar/Wind Harmer
16.84
276621W2-048 GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
9.279
945111AF1-176 GEN
Solar/Wind Harmer
9.811
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.252
965011AG1-365 GEN
Solar/Wind Harmer
3.067
270594AE1-207 GEN
Solar/Wind Harmer
3.372
270032AE2-172
Solar/Wind Harmer
2.007
252510AF1-249 C
Solar/Wind Helper
0.376
253398AE2-221_GEN2
Solar/Wind Helper
1.24
24344305RKG2
50/50
11.213
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
13.819
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
5.748
970073AG2-061 GEN
Solar/Wind Harmer
1.91
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276863AD2-134 GEN
Solar/Wind Harmer
0.1
274856ECOGROVE ;U1
Solar/Wind Harmer
0.128
971681AH1-341 GEN
Solar/Wind Harmer
8.802
971549AH1-272 GEN
Solar/Wind Harmer
10.203
270071AF1-092 GEN
Solar/Wind Harmer
8.932
970539AG2-343 GEN
50/50
9.396
970543AG2-345 GEN
50/50
4.698
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972227AH1-698 GEN1
Adder
2.214
274800UNIV PARK;3U
Adder
4.938
274801UNIV PARK;4U
Adder
4.938
274827FISK ;RP
Adder
6.57
274735ELWOOD EC;4P
Adder
13.819
970169AG2-114 GEN
Solar/Wind Harmer
5.808
274744AC1-111 GEN8
Adder
4.638
959341AF2-225 GEN
Solar/Wind Harmer
6.06
276668AB2-070 GEN1
Solar/Wind Harmer
0.222
276848AB2-070 GEN3
Solar/Wind Harmer
0.221
276849AB2-070 GEN2
Solar/Wind Harmer
0.222
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
276741O09 GEN1
Solar/Wind Harmer
0.191
970289AG2-191 GEN
Solar/Wind Harmer
0.724
253343AC1-166 GEN
Solar/Wind Helper
0.467
955142J992
External Queue
11.419598579406738
990742J1381
External Queue
17.560279846191406
991312J1772
External Queue
12.36315631866455
950011AG9-010
External Queue
6.200752258300781
991082J1475 G
External Queue
6.164829730987549
950051AG9-018
External Queue
4.865413665771484
NYPJM->LTFIMP_NY
CLTF
1.033
WECLTFEXP_WEC->PJM
CLTF
3.003
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.212
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.591
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.737
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.546
MECLTFEXP_MEC->PJM
CLTF
10.638
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.962
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.555
LAGNLTFEXP_LAGN->PJM
CLTF
2.301
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.16 %
Rating:2826.0 MVA
Rating Type:B
MVA to Mitigate:3197.84
MW Contribution:
7.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270101X2-052 CT2
50/50
1.319
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.698
958011AF2-095 GEN
Solar/Wind Harmer
8.526
958491AF2-143 GEN
Solar/Wind Harmer
8.594
274695ROCKY RD ;2P
Adder
9.123
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.733
276911AD2-131_GEN
Solar/Wind Harmer
0.756
274765LEE CO EC;6U
Adder
7.269
274763LEE CO EC;4U
Adder
7.183
247620Y3-023
Adder
0.342
252509AD1-136 GEN
Solar/Wind Helper
0.21
25183208HLCRTG
Solar/Wind Helper
2.03
253400AC2-068 GEN
Solar/Wind Helper
0.086
339231AF1-038_GEN
Solar/Wind Helper
0.394
270102X2-052 ST
50/50
1.428
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.892
945391AF1-204 GEN
Solar/Wind Harmer
6.551
970349AG2-230 GEN
Solar/Wind Harmer
9.139
274808UNIV PK N;4U
Adder
4.255
274674JOLIET 9 ;6U
Adder
12.932
958481AF2-142 GEN
Solar/Wind Harmer
8.668
960611AF2-352 GEN
Solar/Wind Harmer
1.91
24344205RKG1
50/50
11.252
24344205RKG1
50/50
11.252
270393AB1-087 CT1
50/50
2.513
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.661
959141AF2-205 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.265
274777LINCOLN ;8U
Adder
7.265
972228AH1-698 GEN2
Adder
3.144
960591AF2-350 GEN
Solar/Wind Harmer
5.921
972037AH1-567 GEN1
Adder
0.155
970833AG2-524 GEN
Solar/Wind Harmer
6.449
970833AG2-524 GEN
Solar/Wind Harmer
4.299
274675JOLIET 29;7U
Adder
25.765
274675JOLIET 29;7U
Adder
24.845
971675AH1-338 GEN
Solar/Wind Harmer
2.182
971411AH1-196 GEN
Solar/Wind Harmer
8.382
971171AH1-044 GEN
Solar/Wind Harmer
11.115
274823ROCKFORD ;21
Adder
15.441
972267AH1-718 GEN
Adder
3.215
946321AF1-296 GEN
Solar/Wind Harmer
2.925
970031AG2-029 GEN
Solar/Wind Harmer
2.434
339216AC1-074 GEN
Solar/Wind Helper
1.461
253406AD2-031_GEN
Solar/Wind Helper
0.712
24344305RKG2
50/50
11.213
970539AG2-343 GEN
50/50
9.396
970543AG2-345 GEN
50/50
4.698
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972227AH1-698 GEN1
Adder
2.214
274800UNIV PARK;3U
Adder
4.938
274801UNIV PARK;4U
Adder
4.938
274827FISK ;RP
Adder
6.57
274735ELWOOD EC;4P
Adder
13.819
970169AG2-114 GEN
Solar/Wind Harmer
5.808
274744AC1-111 GEN8
Adder
4.638
959341AF2-225 GEN
Solar/Wind Harmer
6.06
276668AB2-070 GEN1
Solar/Wind Harmer
0.222
276848AB2-070 GEN3
Solar/Wind Harmer
0.221
276849AB2-070 GEN2
Solar/Wind Harmer
0.222
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
276741O09 GEN1
Solar/Wind Harmer
0.191
970289AG2-191 GEN
Solar/Wind Harmer
0.724
253343AC1-166 GEN
Solar/Wind Helper
0.467
270394AB1-087 ST1
50/50
2.513
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.267
960681AF2-359 GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
Adder
7.265
270526AF1-158 GEN
Solar/Wind Harmer
0
274687WILL CNTY;4U
Adder
23.495
274687WILL CNTY;4U
Adder
23.495
274731ELWOOD EC;2P
Adder
13.819
274733ELWOOD EC;3P
Adder
13.819
274746AC1-111 G10
Adder
4.638
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.958
944221AF1-090 GEN
Solar/Wind Harmer
3.186
959331AF2-224 GEN
Solar/Wind Harmer
2.147
270340AC2-060 GEN
Solar/Wind Helper
1.095
241972AD1-140 GEN
Solar/Wind Helper
2.071
253338AC1-165 GEN
Solar/Wind Helper
0.467
270406AB1-088 CT1
50/50
2.513
970781AG2-491 GEN
Solar/Wind Harmer
8.082
970193AG2-126 GEN
Solar/Wind Harmer
9.249
971347AH1-153 GEN
Solar/Wind Harmer
3.046
274752CRETE EC ;2U
Adder
7.074
939351AE1-166 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
0.154
274826FISK ;BP
Adder
9.27
970707AG2-453 GEN
Solar/Wind Harmer
19.288
274730ELWOOD EC;6P
Adder
13.819
274862TOP CROP ;2U
Solar/Wind Harmer
0.78
959611AF2-252 GEN
Solar/Wind Harmer
1.91
276868AE1-113 GEN
Solar/Wind Harmer
1.141
274879MINONK ;1U
Solar/Wind Harmer
0.238
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Helper
1.471
942601AE2-276 GEN
50/50
8.364
270100X2-052 CT1
50/50
1.319
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.216
274770LINCOLN ;1U
Adder
7.265
274771LINCOLN ;2U
Adder
7.265
274805UNIV PK N;1U
Adder
4.283
276897AD1-100 C
Solar/Wind Harmer
14.818
274888KELLY CRK;1U
Solar/Wind Harmer
0.345
970941AG2-585 GEN
Solar/Wind Harmer
3.257
276893AG1-478 C
Solar/Wind Harmer
0.391
942111AE2-223 GEN
Solar/Wind Harmer
1.876
274697ROCKY RD ;3P
Adder
2.478
274696ROCKY RD ;4P
Adder
9.338
962691AG1-118 GEN
Solar/Wind Harmer
17.022
276838X2-022 GEN2
Solar/Wind Harmer
0.314
276645AC1-214 GEN1
Solar/Wind Harmer
0.217
938861AE1-114 GEN
Solar/Wind Harmer
3.095
274762LEE CO EC;3U
Adder
7.252
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.873
962581AG1-107 GEN
Solar/Wind Helper
0.905
961491AF2-440 GEN
Solar/Wind Helper
0.037
339236AF1-050_GEN
Solar/Wind Helper
0.404
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.786
964861AG1-349 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
7.265
274774LINCOLN ;5U
Adder
7.265
274751CRETE EC ;1U
Adder
7.074
274723RIVER EC ;12
Adder
15.309
939741AE1-205 GEN
Solar/Wind Harmer
8.081
24344305RKG2
50/50
11.018
274811UNIV PK N;7U
Adder
4.274
276806AD2-047 C O1
Solar/Wind Harmer
3.355
274734ELWOOD EC;8P
Adder
13.819
274736ELWOOD EC;9P
Adder
13.819
274676JOLIET 29;8U
Adder
24.844
943121AE2-341 GEN
Solar/Wind Harmer
9.707
943591AF1-030 GEN
Solar/Wind Harmer
6.455
274682WAUKEGAN ;7U
Adder
14.697
959091AF2-200 GEN
Solar/Wind Harmer
11.115
957381AF2-032 GEN
Solar/Wind Harmer
1.241
274767LEE CO EC;8U
Adder
7.166
971087AG2-675 GEN
Solar/Wind Harmer
2.768
247642Z2-115 C
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
0.419
252524AE2-267 GEN
Solar/Wind Helper
0.466
960071AF2-298 GEN
Solar/Wind Helper
0.355
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3
970569AG2-363 GEN
Solar/Wind Harmer
16.84
276621W2-048 GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
9.279
945111AF1-176 GEN
Solar/Wind Harmer
9.811
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.252
965011AG1-365 GEN
Solar/Wind Harmer
3.067
270594AE1-207 GEN
Solar/Wind Harmer
3.372
270032AE2-172
Solar/Wind Harmer
2.007
252510AF1-249 C
Solar/Wind Helper
0.376
253398AE2-221_GEN2
Solar/Wind Helper
1.24
274772LINCOLN ;3U
Adder
7.265
274724RIVER EC ;11
Adder
15.124
972259AH1-714 GEN
Adder
16.155
274729ELWOOD EC;1P
Adder
13.819
971993AH1-541 GEN
Solar/Wind Harmer
2.606
970571AG2-364 GEN
Solar/Wind Harmer
11.227
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274850MENDOTA H;RU
Solar/Wind Harmer
0.065
270505AE1-170 C O1
Solar/Wind Harmer
5.856
945111AF1-176 GEN
Solar/Wind Harmer
4.457
942481AE2-261 GEN
Solar/Wind Harmer
16.362
270043AE2-236 GEN
Solar/Wind Harmer
2.578
965021AG1-366 GEN
Solar/Wind Harmer
1.022
270186AC1-089 GEN
Solar/Wind Helper
0.822
270367AC2-061_GEN
Solar/Wind Helper
1.691
253394AE2-221_GEN
Solar/Wind Helper
1.24
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.274
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
25.765
274745AC1-111 GEN9
Adder
4.638
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
14.697
274828WAUKEGAN ;BP
Adder
9.02
957471AF2-041 GEN
Solar/Wind Harmer
16.672
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.118
943111AE2-339 GEN
Solar/Wind Helper
0.641
339241AF1-083 GEN
Solar/Wind Helper
0.404
971587AH1-292 GEN
Solar/Wind Harmer
7.361
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.77
276776AD2-060 GEN
Solar/Wind Harmer
0.632
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
11.115
971343AH1-151 GEN
Solar/Wind Harmer
11.115
276916AD2-100_GEN
Solar/Wind Harmer
11.472
970291AG2-192 GEN
Solar/Wind Harmer
0.495
970291AG2-192 GEN
Solar/Wind Harmer
0.229
971613AH1-306 GEN
Solar/Wind Harmer
1.445
970091AG2-072 GEN
50/50
218.725
270407AB1-088 ST1
50/50
2.513
970023AG2-014 GEN
50/50
2.694
970783AG2-492 GEN
50/50
2.694
24344105CKG2
50/50
6.799
971917AH1-482 GEN
Solar/Wind Harmer
9.763
963741AG1-226 GEN
Solar/Wind Harmer
17.105
970373AG2-245 GEN
Solar/Wind Harmer
14.697
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.939
274861TOP CROP ;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.666
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
5.557
971067AG2-660 GEN
Solar/Wind Harmer
1.852
274822ROCKFORD ;11
Adder
15.554
276646AC1-214 GEN2
Solar/Wind Harmer
0.217
943021AE2-325 GEN
Solar/Wind Harmer
2.884
970819AG2-516 GEN
Solar/Wind Harmer
6.595
339221AD2-048_GEN
Solar/Wind Helper
1.206
24385905FR-11G C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
7.074
274802UNIV PARK;5U
Adder
4.947
939401AE1-172 GEN
Solar/Wind Harmer
4.39
274732ELWOOD EC;7P
Adder
13.819
274674JOLIET 9 ;6U
Adder
12.932
962781AG1-127 GEN
Solar/Wind Harmer
5.386
965911AG1-460 GEN
Solar/Wind Harmer
1.094
274766LEE CO EC;7U
Adder
7.166
276708O09 GEN2
Solar/Wind Harmer
0.191
339211AE2-254 GEN
Solar/Wind Helper
0.448
253333AC1-068 GEN
Solar/Wind Helper
0.484
274693ROCKY RD ;1P
Adder
9.033
274683WAUKEGAN ;8U
Adder
17.208
274683WAUKEGAN ;8U
Adder
14.506
276876AE1-163_GEN2
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.058
972235AH1-702 GEN1
Adder
1.993
961051AF2-396 GEN
Solar/Wind Harmer
11.03
961051AF2-396 GEN
Solar/Wind Harmer
7.353
274764LEE CO EC;5U
Adder
7.269
944231AF1-091 GEN
Solar/Wind Harmer
7.025
253349AC2-067 GEN
Solar/Wind Helper
0.213
253415AE1-040 GEN
Solar/Wind Helper
0.484
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
13.819
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
5.748
970073AG2-061 GEN
Solar/Wind Harmer
1.91
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276863AD2-134 GEN
Solar/Wind Harmer
0.1
274856ECOGROVE ;U1
Solar/Wind Harmer
0.128
971681AH1-341 GEN
Solar/Wind Harmer
8.802
971549AH1-272 GEN
Solar/Wind Harmer
10.203
270071AF1-092 GEN
Solar/Wind Harmer
8.932
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274753CRETE EC ;3U
Adder
7.074
274814UNIV PK N;0U
Adder
4.311
274807UNIV PK N;3U
Adder
4.302
276843GEN-1.7
Solar/Wind Harmer
0.191
274803UNIV PARK;6U
Adder
4.947
972038AH1-567 GEN2
Adder
0.309
965091AG1-374 GEN
Solar/Wind Harmer
17.188
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
274760LEE CO EC;1U
Adder
7.252
965931AG1-462 GEN
Solar/Wind Harmer
13.235
339243AC2-075 GEN1
Solar/Wind Helper
0.336
339206AE1-143 GEN
Solar/Wind Helper
1.206
339255AE2-071 GEN
Solar/Wind Helper
0.153
339250AF1-203 GEN
Solar/Wind Helper
0.118
270518AE2-148 GEN
Solar/Wind Helper
5.631
253325AC1-069 GEN
Solar/Wind Helper
0.484
955142J992
External Queue
11.419598579406738
990742J1381
External Queue
17.560279846191406
991312J1772
External Queue
12.36315631866455
950011AG9-010
External Queue
6.200752258300781
991082J1475 G
External Queue
6.164829730987549
950051AG9-018
External Queue
4.865413665771484
NYPJM->LTFIMP_NY
CLTF
1.033
WECLTFEXP_WEC->PJM
CLTF
3.003
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.212
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.591
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.737
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.546
MECLTFEXP_MEC->PJM
CLTF
10.638
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.962
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.555
LAGNLTFEXP_LAGN->PJM
CLTF
2.301
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.91 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2513.45
MW Contribution:
2.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
2.796
270063AE2-323 C
Solar/Wind Harmer
0
965431AG1-411 GEN
50/50
45.352
24727105RPMNG2
50/50
3.311
270142AC1-141 CT1_
50/50
2.011
24695305TIMB G C
Solar/Wind Harmer
0.527
274811UNIV PK N;7U
Adder
3.753
276806AD2-047 C O1
Solar/Wind Harmer
2.92
247642Z2-115 C
Solar/Wind Harmer
0.002
274676JOLIET 29;8U
Adder
21.622
274734ELWOOD EC;8P
Adder
11.982
274736ELWOOD EC;9P
Adder
11.982
970289AG2-191 GEN
Solar/Wind Harmer
0.558
946031AF1-268 GEN
Solar/Wind Harmer
4.787
943121AE2-341 GEN
Solar/Wind Harmer
8.427
943591AF1-030 GEN
Solar/Wind Harmer
5.604
274682WAUKEGAN ;7U
Adder
12.793
959091AF2-200 GEN
Solar/Wind Harmer
9.659
274767LEE CO EC;8U
Adder
6.234
971087AG2-675 GEN
Solar/Wind Harmer
2.411
957381AF2-032 GEN
Solar/Wind Harmer
0.92
24728505AND G1
Adder
2.069
270284AF1-227 GEN1
Solar/Wind Helper
1.912
276820AF1-078_GEN
Solar/Wind Helper
0.338
960861AF2-377 GEN
50/50
2.388
246936BC-WTG1
Solar/Wind Harmer
1.154
270489AE1-102 GEN1
Solar/Wind Harmer
3.723
965011AG1-365 GEN
Solar/Wind Harmer
13.768
958861AF2-177 GEN
Solar/Wind Harmer
2.67
945111AF1-176 GEN
Solar/Wind Harmer
10.586
957891AF2-083 GEN
Solar/Wind Harmer
9.711
945371AF1-202 GEN
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
6.248
274723RIVER EC ;12
Adder
13.542
274773LINCOLN ;4U
Adder
6.299
274774LINCOLN ;5U
Adder
6.299
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.296
270594AE1-207 GEN
Solar/Wind Harmer
5.638
270032AE2-172
Solar/Wind Harmer
3.356
270005AE1-210 C O1
Solar/Wind Harmer
1.089
970825AG2-519 GEN
Solar/Wind Harmer
1.769
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
2.561
970569AG2-363 GEN
Solar/Wind Harmer
14.349
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.308
24386605FR-22G C
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.443
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.21
270485AE1-090_GEN
Solar/Wind Helper
0.328
960841AF2-375 GEN
Solar/Wind Helper
1.192
246938BC-WTG3
Solar/Wind Harmer
1.031
965021AG1-366 GEN
Solar/Wind Harmer
4.589
270043AE2-236 GEN
Solar/Wind Harmer
5.206
945111AF1-176 GEN
Solar/Wind Harmer
4.809
270505AE1-170 C O1
Solar/Wind Harmer
6.075
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.264
274724RIVER EC ;11
Adder
13.377
274772LINCOLN ;3U
Adder
6.299
972259AH1-714 GEN
Adder
14.004
274729ELWOOD EC;1P
Adder
11.982
970825AG2-519 GEN
Solar/Wind Harmer
3.754
946671AF1-331 GEN
Solar/Wind Harmer
0.519
274850MENDOTA H;RU
Solar/Wind Harmer
0.056
970571AG2-364 GEN
Solar/Wind Harmer
9.566
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.973
942481AE2-261 GEN
Solar/Wind Harmer
12.093
24729405KEY G3
50/50
0.371
24729305KEY G2
50/50
0.365
960851AF2-376 GEN
50/50
2.077
246937BC-WTG2
Solar/Wind Harmer
1.154
942221AE2-234 GEN
Solar/Wind Harmer
2.833
274805UNIV PK N;1U
Adder
3.762
274770LINCOLN ;1U
Adder
6.299
274771LINCOLN ;2U
Adder
6.299
274888KELLY CRK;1U
Solar/Wind Harmer
0.3
970941AG2-585 GEN
Solar/Wind Harmer
2.834
276897AD1-100 C
Solar/Wind Harmer
12.751
276893AG1-478 C
Solar/Wind Harmer
0.339
274696ROCKY RD ;4P
Adder
8.116
274697ROCKY RD ;3P
Adder
2.154
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
14.789
938861AE1-114 GEN
Solar/Wind Harmer
2.691
274762LEE CO EC;3U
Adder
6.308
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.754
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
24387305FR-4G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
1.496
970241AG2-163 GEN
Solar/Wind Harmer
2.55
276838X2-022 GEN2
Solar/Wind Harmer
0.236
970623AG2-406 GEN
Solar/Wind Harmer
0.646
247607V1-011 GEN
Solar/Wind Harmer
0
247522W1-056 GEN
Solar/Wind Helper
1.187
253378AE2-206_GEN
Solar/Wind Helper
0.725
970521AG2-332 GEN
50/50
10.816
24639705ELKHART HY
50/50
0.149
270143AC1-141 CT2_
50/50
2.011
965421AG1-410 GEN
Solar/Wind Harmer
81.634
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.86
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
3.753
270246TR4_N_V150
Solar/Wind Harmer
0.046
965681AG1-436 GEN
Solar/Wind Harmer
6.895
247621Y3-024
Adder
0.181
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.55
970291AG2-192 GEN
Solar/Wind Harmer
0.659
970291AG2-192 GEN
Solar/Wind Harmer
0.304
971613AH1-306 GEN
Solar/Wind Harmer
2.416
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.659
971343AH1-151 GEN
Solar/Wind Harmer
9.659
276916AD2-100_GEN
Solar/Wind Harmer
8.418
971587AH1-292 GEN
Solar/Wind Harmer
2.428
270349AD2-093_GEN
Solar/Wind Helper
0.869
270471AD2-092_GEN
Solar/Wind Helper
0.869
24727005RPMNG1
50/50
3.31
943021AE2-325 GEN
Solar/Wind Harmer
2.972
970373AG2-245 GEN
Solar/Wind Harmer
11.129
971917AH1-482 GEN
Solar/Wind Harmer
6.679
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.811
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.572
959081AF2-199 GEN
Solar/Wind Harmer
4.83
971067AG2-660 GEN
Solar/Wind Harmer
1.61
274822ROCKFORD ;11
Adder
13.543
970819AG2-516 GEN
Solar/Wind Harmer
5.744
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
10.345
970773AG2-487 GEN
Solar/Wind Harmer
0.62
270578AF1-285 GEN2
Solar/Wind Helper
0.597
270286AF1-227 GEN2
Solar/Wind Helper
0.701
24729205KEY G1
50/50
0.363
247620Y3-023
50/50
0.463
944541AF1-119 GEN
Solar/Wind Harmer
0.423
270031AE2-169
Solar/Wind Harmer
3.074
965791AG1-447 GEN
Solar/Wind Harmer
5.056
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.406
958011AF2-095 GEN
Solar/Wind Harmer
7.42
274695ROCKY RD ;2P
Adder
7.929
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
7.394
276872AE1-163_GEN1
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.509
274765LEE CO EC;6U
Adder
6.323
274763LEE CO EC;4U
Adder
6.249
24699105WLD G1 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.476
270383AD1-128 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
0.555
241960AC2-195 GEN
Solar/Wind Helper
0.709
270144AC1-141 ST1_
50/50
1.776
959331AF2-224 GEN
Solar/Wind Harmer
9.638
965041AG1-368 GEN
Solar/Wind Harmer
8.389
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.913
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.109
274776LINCOLN ;7U
Adder
6.299
274687WILL CNTY;4U
Adder
20.467
274687WILL CNTY;4U
Adder
20.467
274731ELWOOD EC;2P
Adder
11.982
274733ELWOOD EC;3P
Adder
11.982
274746AC1-111 G10
Adder
4.025
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.812
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.952
944221AF1-090 GEN
Solar/Wind Harmer
2.28
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
0.881
966831AG1-554 GEN
Solar/Wind Helper
0.889
270499AE1-146 GEN
Solar/Wind Helper
1.989
24643105BUCHANAN
50/50
0.01
270247TR4_N_V136
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
16.013
960971AF2-388 GEN
Solar/Wind Harmer
3.72
970349AG2-230 GEN
Solar/Wind Harmer
8.699
961051AF2-396 GEN
Solar/Wind Harmer
11.565
961051AF2-396 GEN
Solar/Wind Harmer
7.71
270599AE1-208 GEN
Solar/Wind Harmer
5.123
274808UNIV PK N;4U
Adder
3.737
274674JOLIET 9 ;6U
Adder
11.228
958481AF2-142 GEN
Solar/Wind Harmer
7.489
274693ROCKY RD ;1P
Adder
7.851
274683WAUKEGAN ;8U
Adder
14.981
274683WAUKEGAN ;8U
Adder
12.628
276876AE1-163_GEN2
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.735
274764LEE CO EC;5U
Adder
6.323
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.527
960611AF2-352 GEN
Solar/Wind Harmer
1.507
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.427
276615X2-022 GEN
Solar/Wind Harmer
0.043
945391AF1-204 GEN
Solar/Wind Harmer
4.161
270462AD2-086
Solar/Wind Helper
3.77
24641605TWIN BRNCH
50/50
0.015
970031AG2-029 GEN
Solar/Wind Harmer
4.557
965051AG1-369 GEN
Solar/Wind Harmer
3.575
945581AF1-223 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
6.299
274777LINCOLN ;8U
Adder
6.299
972037AH1-567 GEN1
Adder
0.136
960591AF2-350 GEN
Solar/Wind Harmer
5.152
972228AH1-698 GEN2
Adder
2.728
274675JOLIET 29;7U
Adder
22.423
274675JOLIET 29;7U
Adder
21.622
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
5.568
970833AG2-524 GEN
Solar/Wind Harmer
3.712
971611AH1-305 GEN
Solar/Wind Harmer
2.999
247536S-71 GEN
Solar/Wind Harmer
0.197
971411AH1-196 GEN
Solar/Wind Harmer
7.295
971675AH1-338 GEN
Solar/Wind Harmer
1.895
971171AH1-044 GEN
Solar/Wind Harmer
9.659
274823ROCKFORD ;21
Adder
13.445
972267AH1-718 GEN
Adder
2.795
24386405FR-21G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
2.546
971029AG2-637 GEN
Solar/Wind Harmer
5.847
270224U2-072_GEN2
Solar/Wind Helper
0.881
945641AF1-229 GEN
Solar/Wind Helper
0.952
944531AF1-118 GEN
Solar/Wind Harmer
31.738
971347AH1-153 GEN
Solar/Wind Harmer
2.9
274752CRETE EC ;2U
Adder
6.248
274826FISK ;BP
Adder
8.11
274887GEN-1.85
Solar/Wind Harmer
0.134
970707AG2-453 GEN
Solar/Wind Harmer
16.726
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
11.982
274862TOP CROP ;2U
Solar/Wind Harmer
0.674
276868AE1-113 GEN
Solar/Wind Harmer
0.98
274879MINONK ;1U
Solar/Wind Harmer
0.204
274855GSG-6 ;RU
Solar/Wind Harmer
0.177
970781AG2-491 GEN
Solar/Wind Harmer
4.841
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
1.507
970193AG2-126 GEN
Solar/Wind Harmer
5.875
24728705AND G3
Adder
4.327
942871AE2-306 GEN
Solar/Wind Helper
0.448
270287AF1-227 GEN3
Solar/Wind Helper
0.701
270541AE2-072 C
Solar/Wind Helper
0.958
24729505KEY G4
50/50
6.793
24653605MOTTVILLE
50/50
0.003
270435AC2-044 GEN
Solar/Wind Harmer
3.627
270071AF1-092 GEN
Solar/Wind Harmer
14.462
971771AH1-392 GEN
Solar/Wind Harmer
5.853
274728ELWOOD EC;5P
Adder
11.982
970073AG2-061 GEN
Solar/Wind Harmer
1.643
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276863AD2-134 GEN
Solar/Wind Harmer
0.087
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.112
971681AH1-341 GEN
Solar/Wind Harmer
7.649
971549AH1-272 GEN
Solar/Wind Harmer
9.785
270543AE2-219 C
Solar/Wind Harmer
3.099
270007AE1-245 C
Solar/Wind Harmer
0
24727205RPMNG3
50/50
3.291
957201AF2-014 GEN
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
11.962
247521TR3_G114
Solar/Wind Harmer
0.259
274827FISK ;RP
Adder
5.748
274800UNIV PARK;3U
Adder
4.311
274801UNIV PARK;4U
Adder
4.311
972227AH1-698 GEN1
Adder
1.92
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
11.982
970289AG2-191 GEN
Solar/Wind Harmer
0.964
274744AC1-111 GEN8
Adder
4.025
970169AG2-114 GEN
Solar/Wind Harmer
4.769
276741O09 GEN1
Solar/Wind Harmer
0.165
274877BISHOP HL;1U
Solar/Wind Harmer
0.155
959341AF2-225 GEN
Solar/Wind Harmer
4.832
276668AB2-070 GEN1
Solar/Wind Harmer
0.168
276848AB2-070 GEN3
Solar/Wind Harmer
0.167
276849AB2-070 GEN2
Solar/Wind Harmer
0.168
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Helper
0.881
270228U2-072_GEN4
Solar/Wind Helper
0.881
270231U2-072_GEN5
Solar/Wind Helper
0.881
24642205MAYFLWER
50/50
0.03
270491AE1-102 GEN2
Solar/Wind Harmer
3.723
274753CRETE EC ;3U
Adder
6.248
274814UNIV PK N;0U
Adder
3.786
274807UNIV PK N;3U
Adder
3.778
274803UNIV PARK;6U
Adder
4.324
972038AH1-567 GEN2
Adder
0.27
276843GEN-1.7
Solar/Wind Harmer
0.167
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.089
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.308
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.155
965091AG1-374 GEN
Solar/Wind Harmer
13.563
965931AG1-462 GEN
Solar/Wind Harmer
11.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.423
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.025
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
12.793
274828WAUKEGAN ;BP
Adder
7.853
957471AF2-041 GEN
Solar/Wind Harmer
14.489
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.247
24728605AND G2
Adder
2.069
274754CRETE EC ;4U
Adder
6.248
274802UNIV PARK;5U
Adder
4.324
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
11.228
274732ELWOOD EC;7P
Adder
11.982
962781AG1-127 GEN
Solar/Wind Harmer
4.68
939401AE1-172 GEN
Solar/Wind Harmer
3.677
276903AD2-071 C
Solar/Wind Harmer
5.365
274766LEE CO EC;7U
Adder
6.234
276708O09 GEN2
Solar/Wind Harmer
0.165
24385905FR-11G C
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.809
270317AD1-130_GEN
Solar/Wind Helper
4.168
270391AF1-285 GEN3
Solar/Wind Helper
0.597
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
NYPJM->LTFIMP_NY
CLTF
1.314
LGEELTFEXP_LGEE->PJM
CLTF
1.767
WECLTFEXP_WEC->PJM
CLTF
2.626
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.784
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.114
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.636
MECLTFEXP_MEC->PJM
CLTF
9.653
SIGELTFEXP_SIGE->PJM
CLTF
0.197
LAGNLTFEXP_LAGN->PJM
CLTF
5.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.274
TVALTFEXP_TVA->PJM
CLTF
2.24

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.9 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5297.56
MW Contribution:
5.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
10.12
970149AG2-104 GEN
Solar/Wind Harmer
40.177
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.275
943021AE2-325 GEN
Solar/Wind Harmer
4.515
276691AA1-018 GEN1
Solar/Wind Harmer
1.395
274861TOP CROP ;1U
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
11.138
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.993
959081AF2-199 GEN
Solar/Wind Harmer
8.465
971067AG2-660 GEN
Solar/Wind Harmer
2.822
274822ROCKFORD ;11
Adder
23.769
970819AG2-516 GEN
Solar/Wind Harmer
10.109
276646AC1-214 GEN2
Solar/Wind Harmer
0.326
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.871
970091AG2-072 GEN
Adder
78.436
970773AG2-487 GEN
Solar/Wind Harmer
1.228
274753CRETE EC ;3U
Adder
10.338
274814UNIV PK N;0U
Adder
6.326
274807UNIV PK N;3U
Adder
6.312
274803UNIV PARK;6U
Adder
7.287
276843GEN-1.7
Solar/Wind Harmer
0.282
972038AH1-567 GEN2
Adder
0.456
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
11.167
24690905MDL-1G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
965091AG1-374 GEN
Solar/Wind Harmer
24.6
24386205FR-12G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
20.87
270004AE1-209 GEN
Solar/Wind Harmer
1.678
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.958
270043AE2-236 GEN
Solar/Wind Harmer
5.83
274772LINCOLN ;3U
Adder
10.701
274724RIVER EC ;11
Adder
22.258
270505AE1-170 C O1
Solar/Wind Harmer
9.169
972259AH1-714 GEN
Adder
23.869
945111AF1-176 GEN
Solar/Wind Harmer
7.059
274729ELWOOD EC;1P
Adder
20.436
965021AG1-366 GEN
Solar/Wind Harmer
2.872
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
970571AG2-364 GEN
Solar/Wind Harmer
16.823
971993AH1-541 GEN
Solar/Wind Harmer
3.686
942481AE2-261 GEN
Solar/Wind Harmer
23.27
970825AG2-519 GEN
Solar/Wind Harmer
5.778
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.403
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.266
270101X2-052 CT2
50/50
1.885
24721805FLATG3
50/50
1.726
970155AG2-107 GEN
Solar/Wind Harmer
47.51
24639705ELKHART HY
Adder
0.193
274812UNIV PK N;8U
Adder
6.271
274676JOLIET 29;8U
Adder
38.191
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
6.924
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.104
274828WAUKEGAN ;BP
Adder
13.576
24722005FLATG5
50/50
1.726
24721905FLATG4
50/50
31.534
962771AG1-126 GEN
Solar/Wind Harmer
74.4
970153AG2-106 GEN
Solar/Wind Harmer
47.51
274811UNIV PK N;7U
Adder
6.271
276806AD2-047 C O1
Solar/Wind Harmer
4.941
274676JOLIET 29;8U
Adder
36.827
274734ELWOOD EC;8P
Adder
20.437
274736ELWOOD EC;9P
Adder
20.437
943121AE2-341 GEN
Solar/Wind Harmer
14.508
943591AF1-030 GEN
Solar/Wind Harmer
9.648
274682WAUKEGAN ;7U
Adder
22.104
959091AF2-200 GEN
Solar/Wind Harmer
16.931
274767LEE CO EC;8U
Adder
11.036
971087AG2-675 GEN
Solar/Wind Harmer
4.365
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.879
957381AF2-032 GEN
Solar/Wind Harmer
1.767
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.648
946031AF1-268 GEN
Solar/Wind Harmer
7.259
24728505AND G1
Adder
3.974
24721705FLATG2
50/50
25.639
965681AG1-436 GEN
Solar/Wind Harmer
11.105
276776AD2-060 GEN
Solar/Wind Harmer
0.93
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
16.931
971343AH1-151 GEN
Solar/Wind Harmer
16.931
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.479
971613AH1-306 GEN
Solar/Wind Harmer
3.795
270246TR4_N_V150
Solar/Wind Harmer
0.05
276916AD2-100_GEN
Solar/Wind Harmer
16.28
247621Y3-024
Adder
0.257
971587AH1-292 GEN
Solar/Wind Harmer
5.361
24723005RIVRG1
Adder
16.391
24723105RIVRG2
Adder
16.391
274827FISK ;RP
Adder
9.698
972227AH1-698 GEN1
Adder
3.26
971347AH1-153 GEN
Solar/Wind Harmer
4.619
944531AF1-118 GEN
Solar/Wind Harmer
39.701
274752CRETE EC ;2U
Adder
10.338
970707AG2-453 GEN
Solar/Wind Harmer
28.587
270063AE2-323 C
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.04
970349AG2-230 GEN
Solar/Wind Harmer
13.856
274808UNIV PK N;4U
Adder
6.243
270100X2-052 CT1
50/50
1.885
274770LINCOLN ;1U
Adder
10.701
274771LINCOLN ;2U
Adder
10.701
274805UNIV PK N;1U
Adder
6.285
274888KELLY CRK;1U
Solar/Wind Harmer
0.509
970941AG2-585 GEN
Solar/Wind Harmer
4.796
276897AD1-100 C
Solar/Wind Harmer
21.761
276893AG1-478 C
Solar/Wind Harmer
0.578
274696ROCKY RD ;4P
Adder
14.031
274697ROCKY RD ;3P
Adder
3.724
962691AG1-118 GEN
Solar/Wind Harmer
25.676
957841AF2-078 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
4.755
274775LINCOLN ;6U
Adder
10.701
274777LINCOLN ;8U
Adder
10.701
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.72
972228AH1-698 GEN2
Adder
4.629
970031AG2-029 GEN
Solar/Wind Harmer
4.711
274675JOLIET 29;7U
Adder
38.191
274675JOLIET 29;7U
Adder
36.827
970833AG2-524 GEN
Solar/Wind Harmer
9.54
970833AG2-524 GEN
Solar/Wind Harmer
6.36
962761AG1-125 GEN
Solar/Wind Harmer
74.4
274754CRETE EC ;4U
Adder
10.338
274802UNIV PARK;5U
Adder
7.287
274674JOLIET 9 ;6U
Adder
19.151
274732ELWOOD EC;7P
Adder
20.437
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.395
962781AG1-127 GEN
Solar/Wind Harmer
8.134
274766LEE CO EC;7U
Adder
11.036
276708O09 GEN2
Solar/Wind Harmer
0.294
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.696
965911AG1-460 GEN
Solar/Wind Harmer
1.557
270437AC2-090 C
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
17.295
971771AH1-392 GEN
Solar/Wind Harmer
8.847
24729505KEY G4
Adder
8.138
274728ELWOOD EC;5P
Adder
20.437
970073AG2-061 GEN
Solar/Wind Harmer
2.844
276861AD2-134 GEN
Solar/Wind Harmer
0.151
276863AD2-134 GEN
Solar/Wind Harmer
0.151
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
971681AH1-341 GEN
Solar/Wind Harmer
13.512
24691005MDL-2G C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
16.346
270435AC2-044 GEN
Solar/Wind Harmer
0.934
270543AE2-219 C
Solar/Wind Harmer
4.979
270007AE1-245 C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
10.701
274774LINCOLN ;5U
Adder
10.701
274723RIVER EC ;12
Adder
22.518
274751CRETE EC ;1U
Adder
10.338
957891AF2-083 GEN
Solar/Wind Harmer
14.548
945111AF1-176 GEN
Solar/Wind Harmer
15.539
965011AG1-365 GEN
Solar/Wind Harmer
8.615
964861AG1-349 GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.466
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.605
970569AG2-363 GEN
Solar/Wind Harmer
25.234
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.167
958861AF2-177 GEN
Solar/Wind Harmer
3.623
939741AE1-205 GEN
Solar/Wind Harmer
11.579
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.396
270594AE1-207 GEN
Solar/Wind Harmer
8.855
270032AE2-172
Solar/Wind Harmer
5.271
270005AE1-210 C O1
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
2.723
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.297
270489AE1-102 GEN1
Solar/Wind Harmer
0.958
274762LEE CO EC;3U
Adder
11.167
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.343
276645AC1-214 GEN1
Solar/Wind Harmer
0.326
942111AE2-223 GEN
Solar/Wind Harmer
2.688
942221AE2-234 GEN
Solar/Wind Harmer
3.3
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.651
276838X2-022 GEN2
Solar/Wind Harmer
0.445
246937BC-WTG2
Solar/Wind Harmer
0.297
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.29
965791AG1-447 GEN
Solar/Wind Harmer
8.144
247620Y3-023
Adder
0.576
958011AF2-095 GEN
Solar/Wind Harmer
12.557
274695ROCKY RD ;2P
Adder
13.708
958491AF2-143 GEN
Solar/Wind Harmer
12.799
276872AE1-163_GEN1
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.565
972236AH1-702 GEN2
Adder
2.651
945421AF1-207 GEN
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
11.194
274763LEE CO EC;4U
Adder
11.062
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.369
276911AD2-131_GEN
Solar/Wind Harmer
1.072
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.571
270201AC2-176 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.371
24728805RICHG1
Adder
3.474
24721605FLATG1
50/50
1.726
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
10.701
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
34.799
274687WILL CNTY;4U
Adder
34.799
274731ELWOOD EC;2P
Adder
20.436
274733ELWOOD EC;3P
Adder
20.436
274746AC1-111 G10
Adder
6.924
959331AF2-224 GEN
Solar/Wind Harmer
6.031
926823AC1-168 GEN
Solar/Wind Harmer
1.43
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.499
965041AG1-368 GEN
Solar/Wind Harmer
8.029
971609AH1-304 GEN
Solar/Wind Harmer
1.297
944221AF1-090 GEN
Solar/Wind Harmer
4.487
964611AG1-324 GEN
Solar/Wind Harmer
2.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
274800UNIV PARK;3U
Adder
7.284
274801UNIV PARK;4U
Adder
7.284
274735ELWOOD EC;4P
Adder
20.436
274744AC1-111 GEN8
Adder
6.924
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
8.419
276741O09 GEN1
Solar/Wind Harmer
0.294
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
959341AF2-225 GEN
Solar/Wind Harmer
8.684
963791AG1-232 GEN
Solar/Wind Harmer
11.059
970289AG2-191 GEN
Solar/Wind Harmer
1.518
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.284
957201AF2-014 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.938
274674JOLIET 9 ;6U
Adder
19.151
961051AF2-396 GEN
Solar/Wind Harmer
17.344
961051AF2-396 GEN
Solar/Wind Harmer
11.563
274693ROCKY RD ;1P
Adder
13.573
958481AF2-142 GEN
Solar/Wind Harmer
12.877
274683WAUKEGAN ;8U
Adder
25.9
274683WAUKEGAN ;8U
Adder
21.833
276876AE1-163_GEN2
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
4.962
972235AH1-702 GEN1
Adder
3.049
274764LEE CO EC;5U
Adder
11.194
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.733
966841AG1-555 GEN
Solar/Wind Harmer
0.927
270599AE1-208 GEN
Solar/Wind Harmer
7.282
276615X2-022 GEN
Solar/Wind Harmer
0.082
270247TR4_N_V136
Solar/Wind Harmer
0.05
24725505WLD G2 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
17.757
945391AF1-204 GEN
Solar/Wind Harmer
8.104
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.112
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.474
957471AF2-041 GEN
Solar/Wind Harmer
25.396
965651AG1-433 GEN
Solar/Wind Harmer
2.481
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
22.474
970613AG2-401 GEN
Solar/Wind Harmer
5.436
24728605AND G2
Adder
3.974
972203AH1-686 GEN
Adder
2.059
24723205RIVRG3
Adder
16.391
959141AF2-205 GEN
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
3.313
971411AH1-196 GEN
Solar/Wind Harmer
12.74
971611AH1-305 GEN
Solar/Wind Harmer
5.051
971171AH1-044 GEN
Solar/Wind Harmer
16.931
274823ROCKFORD ;21
Adder
23.596
972267AH1-718 GEN
Adder
4.973
946321AF1-296 GEN
Solar/Wind Harmer
4.596
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.91
247536S-71 GEN
Solar/Wind Harmer
0.293
971029AG2-637 GEN
Solar/Wind Harmer
10.316
274826FISK ;BP
Adder
13.684
274887GEN-1.85
Solar/Wind Harmer
0.227
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
20.437
274862TOP CROP ;2U
Solar/Wind Harmer
1.159
276868AE1-113 GEN
Solar/Wind Harmer
1.703
274879MINONK ;1U
Solar/Wind Harmer
0.355
274855GSG-6 ;RU
Solar/Wind Harmer
0.31
274857EASY ROAD;U1
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.328
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.733
970193AG2-126 GEN
Solar/Wind Harmer
11.441
24728705AND G3
Adder
8.312
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
NYPJM->LTFIMP_NY
CLTF
3.901
LGEELTFEXP_LGEE->PJM
CLTF
5.998
WECLTFEXP_WEC->PJM
CLTF
4.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.551
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.416
MECLTFEXP_MEC->PJM
CLTF
18.61
SIGELTFEXP_SIGE->PJM
CLTF
0.498
LAGNLTFEXP_LAGN->PJM
CLTF
16.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.242
TVALTFEXP_TVA->PJM
CLTF
7.96

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4473.55
MW Contribution:
4.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247620Y3-023
50/50
0.701
270101X2-052 CT2
50/50
2.104
965791AG1-447 GEN
Solar/Wind Harmer
9.061
958011AF2-095 GEN
Solar/Wind Harmer
13.543
944541AF1-119 GEN
Solar/Wind Harmer
0.62
274695ROCKY RD ;2P
Adder
14.592
958491AF2-143 GEN
Solar/Wind Harmer
13.572
276872AE1-163_GEN1
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
19.599
971771AH1-392 GEN
Solar/Wind Harmer
10.022
24729505KEY G4
Adder
9.105
270435AC2-044 GEN
Solar/Wind Harmer
1.188
274728ELWOOD EC;5P
Adder
21.94
971549AH1-272 GEN
Solar/Wind Harmer
19.166
970073AG2-061 GEN
Solar/Wind Harmer
3.016
276861AD2-134 GEN
Solar/Wind Harmer
0.16
276863AD2-134 GEN
Solar/Wind Harmer
0.16
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.376
247521TR3_G114
Solar/Wind Harmer
0.347
963791AG1-232 GEN
Solar/Wind Harmer
12.72
274827FISK ;RP
Adder
10.469
274800UNIV PARK;3U
Adder
7.859
274801UNIV PARK;4U
Adder
7.859
972227AH1-698 GEN1
Adder
3.513
957201AF2-014 GEN
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
21.939
274744AC1-111 GEN8
Adder
7.404
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
8.815
276741O09 GEN1
Solar/Wind Harmer
0.306
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
959341AF2-225 GEN
Solar/Wind Harmer
8.961
24722005FLATG5
50/50
4.711
24721905FLATG4
50/50
86.05
270142AC1-141 CT1_
50/50
3.456
962771AG1-126 GEN
Solar/Wind Harmer
109.537
970153AG2-106 GEN
Solar/Wind Harmer
69.947
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
274811UNIV PK N;7U
Adder
6.795
24695305TIMB G C
Solar/Wind Harmer
0.797
276806AD2-047 C O1
Solar/Wind Harmer
5.33
274676JOLIET 29;8U
Adder
39.574
274734ELWOOD EC;8P
Adder
21.94
274736ELWOOD EC;9P
Adder
21.94
943121AE2-341 GEN
Solar/Wind Harmer
15.518
943591AF1-030 GEN
Solar/Wind Harmer
10.32
274682WAUKEGAN ;7U
Adder
23.522
959091AF2-200 GEN
Solar/Wind Harmer
17.823
274767LEE CO EC;8U
Adder
11.522
247642Z2-115 C
Solar/Wind Harmer
0.003
971087AG2-675 GEN
Solar/Wind Harmer
4.475
970289AG2-191 GEN
Solar/Wind Harmer
0.915
946031AF1-268 GEN
Solar/Wind Harmer
7.583
957381AF2-032 GEN
Solar/Wind Harmer
1.73
24728505AND G1
Adder
3.831
23906402RICHG1
Adder
1.111
23906502RICHG2&3
Adder
1.11
24307105BERRINSP G
50/50
0.03
965011AG1-365 GEN
Solar/Wind Harmer
10.32
957891AF2-083 GEN
Solar/Wind Harmer
16.606
945111AF1-176 GEN
Solar/Wind Harmer
17.763
274773LINCOLN ;4U
Adder
11.612
274774LINCOLN ;5U
Adder
11.612
274723RIVER EC ;12
Adder
24.471
274751CRETE EC ;1U
Adder
11.245
246936BC-WTG1
Solar/Wind Harmer
0.378
270489AE1-102 GEN1
Solar/Wind Harmer
1.219
964861AG1-349 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.956
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.72
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.201
945371AF1-202 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
26.447
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.659
939741AE1-205 GEN
Solar/Wind Harmer
11.948
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.214
270032AE2-172
Solar/Wind Harmer
5.485
270005AE1-210 C O1
Solar/Wind Harmer
1.752
944961AF1-161 GEN
50/50
4.124
270043AE2-236 GEN
Solar/Wind Harmer
6.765
965021AG1-366 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
10.472
945111AF1-176 GEN
Solar/Wind Harmer
8.069
274772LINCOLN ;3U
Adder
11.612
274724RIVER EC ;11
Adder
24.187
972259AH1-714 GEN
Adder
25.709
246938BC-WTG3
Solar/Wind Harmer
0.338
274729ELWOOD EC;1P
Adder
21.939
946671AF1-331 GEN
Solar/Wind Harmer
0.957
274850MENDOTA H;RU
Solar/Wind Harmer
0.104
970571AG2-364 GEN
Solar/Wind Harmer
17.631
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.121
970825AG2-519 GEN
Solar/Wind Harmer
6.019
971993AH1-541 GEN
Solar/Wind Harmer
3.688
942481AE2-261 GEN
Solar/Wind Harmer
22.758
270240V3-007_GEN2
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
2.104
274770LINCOLN ;1U
Adder
11.612
274771LINCOLN ;2U
Adder
11.612
274805UNIV PK N;1U
Adder
6.81
274888KELLY CRK;1U
Solar/Wind Harmer
0.548
970941AG2-585 GEN
Solar/Wind Harmer
5.173
246937BC-WTG2
Solar/Wind Harmer
0.378
276897AD1-100 C
Solar/Wind Harmer
23.396
276893AG1-478 C
Solar/Wind Harmer
0.621
274697ROCKY RD ;3P
Adder
3.964
274696ROCKY RD ;4P
Adder
14.936
942221AE2-234 GEN
Solar/Wind Harmer
3.664
962691AG1-118 GEN
Solar/Wind Harmer
27.25
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.615
938861AE1-114 GEN
Solar/Wind Harmer
4.972
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274762LEE CO EC;3U
Adder
11.659
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.395
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
942111AE2-223 GEN
Solar/Wind Harmer
2.774
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.646
970621AG2-405 GEN
Solar/Wind Harmer
1.449
276838X2-022 GEN2
Solar/Wind Harmer
0.442
25326509SID D
Adder
1.142
270475AD2-096_GEN
50/50
10.483
24642205MAYFLWER
50/50
0.053
962601AG1-109 GEN
50/50
4.124
274753CRETE EC ;3U
Adder
11.245
274814UNIV PK N;0U
Adder
6.855
274807UNIV PK N;3U
Adder
6.84
274803UNIV PARK;6U
Adder
7.869
971347AH1-153 GEN
Solar/Wind Harmer
5.221
270391AF1-285 GEN3
Solar/Wind Harmer
0.682
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
44.69
274752CRETE EC ;2U
Adder
11.245
970707AG2-453 GEN
Solar/Wind Harmer
30.807
274826FISK ;BP
Adder
14.772
274887GEN-1.85
Solar/Wind Harmer
0.244
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
21.94
274862TOP CROP ;2U
Solar/Wind Harmer
1.234
276868AE1-113 GEN
Solar/Wind Harmer
1.802
274879MINONK ;1U
Solar/Wind Harmer
0.376
274855GSG-6 ;RU
Solar/Wind Harmer
0.327
274857EASY ROAD;U1
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.625
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.8
970193AG2-126 GEN
Solar/Wind Harmer
10.995
24728705AND G3
Adder
8.012
270541AE2-072 C
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
109.537
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
274754CRETE EC ;4U
Adder
11.245
274802UNIV PARK;5U
Adder
7.869
274674JOLIET 9 ;6U
Adder
20.564
274732ELWOOD EC;7P
Adder
21.94
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.625
939401AE1-172 GEN
Solar/Wind Harmer
6.778
274766LEE CO EC;7U
Adder
11.522
276708O09 GEN2
Solar/Wind Harmer
0.306
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.936
965911AG1-460 GEN
Solar/Wind Harmer
1.522
270437AC2-090 C
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.277
24643105BUCHANAN
50/50
0.018
970349AG2-230 GEN
Solar/Wind Harmer
15.664
961051AF2-396 GEN
Solar/Wind Harmer
19.838
961051AF2-396 GEN
Solar/Wind Harmer
13.225
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.061
274808UNIV PK N;4U
Adder
6.766
944231AF1-091 GEN
Solar/Wind Harmer
21.57
274674JOLIET 9 ;6U
Adder
20.564
960971AF2-388 GEN
Solar/Wind Harmer
5.451
958481AF2-142 GEN
Solar/Wind Harmer
13.721
274693ROCKY RD ;1P
Adder
14.449
274683WAUKEGAN ;8U
Adder
27.547
274683WAUKEGAN ;8U
Adder
23.221
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.202
274764LEE CO EC;5U
Adder
11.687
24697605MDL-3G C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
7.749
960611AF2-352 GEN
Solar/Wind Harmer
2.8
966841AG1-555 GEN
Solar/Wind Harmer
0.946
24725505WLD G2 C
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.081
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.401
945391AF1-204 GEN
Solar/Wind Harmer
7.788
24728905RICHG2
Adder
3.35
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.268
970031AG2-029 GEN
Solar/Wind Harmer
5.461
274775LINCOLN ;6U
Adder
11.612
274777LINCOLN ;8U
Adder
11.612
965051AG1-369 GEN
Solar/Wind Harmer
4.782
972037AH1-567 GEN1
Adder
0.247
960591AF2-350 GEN
Solar/Wind Harmer
9.405
972228AH1-698 GEN2
Adder
4.989
274675JOLIET 29;7U
Adder
41.04
274675JOLIET 29;7U
Adder
39.575
970833AG2-524 GEN
Solar/Wind Harmer
10.228
970833AG2-524 GEN
Solar/Wind Harmer
6.819
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.448
971675AH1-338 GEN
Solar/Wind Harmer
3.496
971611AH1-305 GEN
Solar/Wind Harmer
5.334
971171AH1-044 GEN
Solar/Wind Harmer
17.823
274823ROCKFORD ;21
Adder
24.808
945581AF1-223 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.171
946321AF1-296 GEN
Solar/Wind Harmer
4.723
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.308
971029AG2-637 GEN
Solar/Wind Harmer
10.609
24721805FLATG3
50/50
4.711
270143AC1-141 CT2_
50/50
3.456
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.675
970155AG2-107 GEN
Solar/Wind Harmer
69.947
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
28.412
274812UNIV PK N;8U
Adder
6.795
274676JOLIET 29;8U
Adder
41.04
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.726
274745AC1-111 GEN9
Adder
7.404
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
23.522
274828WAUKEGAN ;BP
Adder
14.44
957471AF2-041 GEN
Solar/Wind Harmer
26.735
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.54
24728605AND G2
Adder
3.831
23906502RICHG2&3
Adder
1.11
24721705FLATG2
50/50
69.962
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
12.356
270246TR4_N_V150
Solar/Wind Harmer
0.061
276776AD2-060 GEN
Solar/Wind Harmer
1.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.823
971343AH1-151 GEN
Solar/Wind Harmer
17.823
970291AG2-192 GEN
Solar/Wind Harmer
1.081
970291AG2-192 GEN
Solar/Wind Harmer
0.499
971613AH1-306 GEN
Solar/Wind Harmer
3.949
247621Y3-024
Adder
0.272
276916AD2-100_GEN
Solar/Wind Harmer
15.862
971587AH1-292 GEN
Solar/Wind Harmer
4.757
24344105CKG2
50/50
11.483
970149AG2-104 GEN
Solar/Wind Harmer
59.152
943021AE2-325 GEN
Solar/Wind Harmer
5.166
970373AG2-245 GEN
Solar/Wind Harmer
19.884
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.902
276691AA1-018 GEN1
Solar/Wind Harmer
1.486
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.051
959081AF2-199 GEN
Solar/Wind Harmer
8.912
971067AG2-660 GEN
Solar/Wind Harmer
2.971
274822ROCKFORD ;11
Adder
24.99
970819AG2-516 GEN
Solar/Wind Harmer
10.604
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.848
970773AG2-487 GEN
Solar/Wind Harmer
1.192
276843GEN-1.7
Solar/Wind Harmer
0.304
972038AH1-567 GEN2
Adder
0.492
270491AE1-102 GEN2
Solar/Wind Harmer
1.219
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
11.659
24690905MDL-1G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965091AG1-374 GEN
Solar/Wind Harmer
25.202
965931AG1-462 GEN
Solar/Wind Harmer
21.395
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.752
24379505HDWTR1G C
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.785
945421AF1-207 GEN
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
11.687
274763LEE CO EC;4U
Adder
11.55
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.65
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.604
24699105WLD G1 C
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
1.045
970885AG2-551 GEN
Solar/Wind Harmer
2.467
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.35
970329AG2-216 GEN
Solar/Wind Harmer
2.663
24721605FLATG1
50/50
4.711
270144AC1-141 ST1_
50/50
3.051
959331AF2-224 GEN
Solar/Wind Harmer
7.224
270578AF1-285 GEN2
Solar/Wind Harmer
0.682
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
965041AG1-368 GEN
Solar/Wind Harmer
9.736
274776LINCOLN ;7U
Adder
11.612
274687WILL CNTY;4U
Adder
37.422
274687WILL CNTY;4U
Adder
37.422
274731ELWOOD EC;2P
Adder
21.939
274733ELWOOD EC;3P
Adder
21.939
274746AC1-111 G10
Adder
7.404
926823AC1-168 GEN
Solar/Wind Harmer
1.499
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.381
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.532
964611AG1-324 GEN
Solar/Wind Harmer
3.142
944221AF1-090 GEN
Solar/Wind Harmer
4.314
270356AE2-297 GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.836
276621W2-048 GEN
Solar/Wind Harmer
0.393
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.58
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.206
971681AH1-341 GEN
Solar/Wind Harmer
14.132
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.181
NYPJM->LTFIMP_NY
CLTF
3.074
LGEELTFEXP_LGEE->PJM
CLTF
4.556
WECLTFEXP_WEC->PJM
CLTF
4.845
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.158
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.889
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.375
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.313
MECLTFEXP_MEC->PJM
CLTF
18.13
SIGELTFEXP_SIGE->PJM
CLTF
0.416
LAGNLTFEXP_LAGN->PJM
CLTF
11.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.981
TVALTFEXP_TVA->PJM
CLTF
4.815

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.31 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5773.71
MW Contribution:
5.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274753CRETE EC ;3U
Adder
10.415
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274803UNIV PARK;6U
Adder
7.339
276843GEN-1.7
Solar/Wind Harmer
0.284
972038AH1-567 GEN2
Adder
0.459
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
11.202
962761AG1-125 GEN
Solar/Wind Harmer
80.774
274754CRETE EC ;4U
Adder
10.415
274802UNIV PARK;5U
Adder
7.339
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
939401AE1-172 GEN
Solar/Wind Harmer
6.422
274766LEE CO EC;7U
Adder
11.07
276708O09 GEN2
Solar/Wind Harmer
0.295
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.542
276903AD2-071 C
Solar/Wind Harmer
8.459
270437AC2-090 C
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
17.36
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274728ELWOOD EC;5P
Adder
20.57
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
274751CRETE EC ;1U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
945111AF1-176 GEN
Solar/Wind Harmer
15.659
964861AG1-349 GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
971997AH1-543 GEN
Solar/Wind Harmer
4.485
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
270100X2-052 CT1
50/50
1.903
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
970941AG2-585 GEN
Solar/Wind Harmer
4.83
276897AD1-100 C
Solar/Wind Harmer
21.908
276893AG1-478 C
Solar/Wind Harmer
0.582
274696ROCKY RD ;4P
Adder
14.112
274697ROCKY RD ;3P
Adder
3.745
962691AG1-118 GEN
Solar/Wind Harmer
25.814
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274762LEE CO EC;3U
Adder
11.202
957841AF2-078 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
942111AE2-223 GEN
Solar/Wind Harmer
2.686
24387305FR-4G C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276838X2-022 GEN2
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.284
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
270101X2-052 CT2
50/50
1.903
965791AG1-447 GEN
Solar/Wind Harmer
8.22
958011AF2-095 GEN
Solar/Wind Harmer
12.646
247620Y3-023
Adder
0.579
274695ROCKY RD ;2P
Adder
13.787
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.662
274765LEE CO EC;6U
Adder
11.229
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.257
276911AD2-131_GEN
Solar/Wind Harmer
1.062
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.23
24721605FLATG1
50/50
1.801
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274746AC1-111 G10
Adder
6.969
959331AF2-224 GEN
Solar/Wind Harmer
5.989
926823AC1-168 GEN
Solar/Wind Harmer
1.434
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
965041AG1-368 GEN
Solar/Wind Harmer
7.859
971609AH1-304 GEN
Solar/Wind Harmer
1.264
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270356AE2-297 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
274827FISK ;RP
Adder
9.767
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274735ELWOOD EC;4P
Adder
20.57
274744AC1-111 GEN8
Adder
6.969
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
8.435
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
959341AF2-225 GEN
Solar/Wind Harmer
8.677
963791AG1-232 GEN
Solar/Wind Harmer
10.858
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.486
247521TR3_G114
Solar/Wind Harmer
0.275
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.06
970349AG2-230 GEN
Solar/Wind Harmer
14.053
274808UNIV PK N;4U
Adder
6.289
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
274693ROCKY RD ;1P
Adder
13.651
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
274764LEE CO EC;5U
Adder
11.229
960971AF2-388 GEN
Solar/Wind Harmer
4.897
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.728
966841AG1-555 GEN
Solar/Wind Harmer
0.921
276615X2-022 GEN
Solar/Wind Harmer
0.081
270599AE1-208 GEN
Solar/Wind Harmer
7.096
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
6.689
270054AF2-122 C O1
Solar/Wind Helper
1.547
24721805FLATG3
50/50
1.801
970155AG2-107 GEN
Solar/Wind Harmer
51.58
24639705ELKHART HY
Adder
0.194
274812UNIV PK N;8U
Adder
6.317
274676JOLIET 29;8U
Adder
38.449
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.229
274828WAUKEGAN ;BP
Adder
13.652
957471AF2-041 GEN
Solar/Wind Harmer
25.504
965651AG1-433 GEN
Solar/Wind Harmer
2.449
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
21.55
970613AG2-401 GEN
Solar/Wind Harmer
5.196
24728605AND G2
Adder
3.809
972203AH1-686 GEN
Adder
1.998
274775LINCOLN ;6U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
959141AF2-205 GEN
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
972267AH1-718 GEN
Adder
4.986
946321AF1-296 GEN
Solar/Wind Harmer
4.601
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.795
247536S-71 GEN
Solar/Wind Harmer
0.278
971029AG2-637 GEN
Solar/Wind Harmer
9.586
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
274811UNIV PK N;7U
Adder
6.317
276806AD2-047 C O1
Solar/Wind Harmer
4.976
274676JOLIET 29;8U
Adder
37.076
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
959091AF2-200 GEN
Solar/Wind Harmer
17.002
274767LEE CO EC;8U
Adder
11.07
971087AG2-675 GEN
Solar/Wind Harmer
4.368
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
24695305TIMB G C
Solar/Wind Harmer
0.627
946031AF1-268 GEN
Solar/Wind Harmer
6.994
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
4.684
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274826FISK ;BP
Adder
13.782
274887GEN-1.85
Solar/Wind Harmer
0.228
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
20.57
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274857EASY ROAD;U1
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.09
970073AG2-061 GEN
Solar/Wind Harmer
2.857
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
971681AH1-341 GEN
Solar/Wind Harmer
13.557
24691005MDL-2G C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
16.367
270435AC2-044 GEN
Solar/Wind Harmer
0.891
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
24344105CKG2
50/50
10.297
970149AG2-104 GEN
Solar/Wind Harmer
43.619
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
943021AE2-325 GEN
Solar/Wind Harmer
4.55
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274861TOP CROP ;1U
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
11.164
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.998
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
24721705FLATG2
50/50
26.753
965681AG1-436 GEN
Solar/Wind Harmer
11.209
276776AD2-060 GEN
Solar/Wind Harmer
0.937
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
270246TR4_N_V150
Solar/Wind Harmer
0.049
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
270505AE1-170 C O1
Solar/Wind Harmer
9.246
972259AH1-714 GEN
Adder
24.043
945111AF1-176 GEN
Solar/Wind Harmer
7.113
274729ELWOOD EC;1P
Adder
20.57
965021AG1-366 GEN
Solar/Wind Harmer
2.852
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
970571AG2-364 GEN
Solar/Wind Harmer
16.871
971993AH1-541 GEN
Solar/Wind Harmer
3.663
942481AE2-261 GEN
Solar/Wind Harmer
23.05
970825AG2-519 GEN
Solar/Wind Harmer
5.579
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
276782AC1-033 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
959611AF2-252 GEN
Solar/Wind Harmer
2.728
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24728705AND G3
Adder
7.966
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
20.885
965091AG1-374 GEN
Solar/Wind Harmer
24.551
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.624
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.01 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5028.49
MW Contribution:
4.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
76.7
270349AD2-093_GEN
Solar/Wind Harmer
0.002
247620Y3-023
50/50
0.723
270101X2-052 CT2
50/50
2.175
965791AG1-447 GEN
Solar/Wind Harmer
9.363
958011AF2-095 GEN
Solar/Wind Harmer
13.957
944541AF1-119 GEN
Solar/Wind Harmer
0.629
274695ROCKY RD ;2P
Adder
15.016
958491AF2-143 GEN
Solar/Wind Harmer
13.95
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.86
274765LEE CO EC;6U
Adder
11.991
274763LEE CO EC;4U
Adder
11.851
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.656
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.598
24699105WLD G1 C
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
1.056
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.391
24721605FLATG1
50/50
5.165
270144AC1-141 ST1_
50/50
3.155
959331AF2-224 GEN
Solar/Wind Harmer
7.385
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
11.987
965041AG1-368 GEN
Solar/Wind Harmer
9.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274687WILL CNTY;4U
Adder
38.553
274687WILL CNTY;4U
Adder
38.553
274731ELWOOD EC;2P
Adder
22.596
274733ELWOOD EC;3P
Adder
22.596
274746AC1-111 G10
Adder
7.624
926823AC1-168 GEN
Solar/Wind Harmer
1.537
270102X2-052 ST
50/50
2.354
24643105BUCHANAN
50/50
0.019
970349AG2-230 GEN
Solar/Wind Harmer
16.255
961051AF2-396 GEN
Solar/Wind Harmer
20.485
961051AF2-396 GEN
Solar/Wind Harmer
13.656
274808UNIV PK N;4U
Adder
6.974
270247TR4_N_V136
Solar/Wind Harmer
0.062
274674JOLIET 9 ;6U
Adder
21.182
944231AF1-091 GEN
Solar/Wind Harmer
21.933
960971AF2-388 GEN
Solar/Wind Harmer
5.526
958481AF2-142 GEN
Solar/Wind Harmer
14.114
274693ROCKY RD ;1P
Adder
14.868
274683WAUKEGAN ;8U
Adder
28.341
274683WAUKEGAN ;8U
Adder
23.89
270462AD2-086
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.289
274764LEE CO EC;5U
Adder
11.991
24697605MDL-3G C
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.587
970031AG2-029 GEN
Solar/Wind Harmer
5.617
274775LINCOLN ;6U
Adder
11.987
274777LINCOLN ;8U
Adder
11.987
972037AH1-567 GEN1
Adder
0.255
960591AF2-350 GEN
Solar/Wind Harmer
9.692
972228AH1-698 GEN2
Adder
5.142
965051AG1-369 GEN
Solar/Wind Harmer
4.809
274675JOLIET 29;7U
Adder
42.278
274675JOLIET 29;7U
Adder
40.768
970833AG2-524 GEN
Solar/Wind Harmer
10.534
970833AG2-524 GEN
Solar/Wind Harmer
7.023
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.821
971675AH1-338 GEN
Solar/Wind Harmer
3.593
971611AH1-305 GEN
Solar/Wind Harmer
5.462
971171AH1-044 GEN
Solar/Wind Harmer
18.31
274823ROCKFORD ;21
Adder
25.482
972267AH1-718 GEN
Adder
5.303
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
4.834
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.301
971029AG2-637 GEN
Solar/Wind Harmer
10.16
971347AH1-153 GEN
Solar/Wind Harmer
5.418
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
45.71
274752CRETE EC ;2U
Adder
11.595
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
270100X2-052 CT1
50/50
2.175
274770LINCOLN ;1U
Adder
11.987
274771LINCOLN ;2U
Adder
11.987
274805UNIV PK N;1U
Adder
7.02
274888KELLY CRK;1U
Solar/Wind Harmer
0.565
970941AG2-585 GEN
Solar/Wind Harmer
5.331
276897AD1-100 C
Solar/Wind Harmer
24.102
276893AG1-478 C
Solar/Wind Harmer
0.639
274697ROCKY RD ;3P
Adder
4.079
274696ROCKY RD ;4P
Adder
15.37
962691AG1-118 GEN
Solar/Wind Harmer
28.03
246937BC-WTG2
Solar/Wind Harmer
0.377
942221AE2-234 GEN
Solar/Wind Harmer
3.701
938861AE1-114 GEN
Solar/Wind Harmer
5.103
274762LEE CO EC;3U
Adder
11.963
957841AF2-078 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.43
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.607
942111AE2-223 GEN
Solar/Wind Harmer
2.835
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.698
276838X2-022 GEN2
Solar/Wind Harmer
0.449
970621AG2-405 GEN
Solar/Wind Harmer
1.408
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
12.767
276776AD2-060 GEN
Solar/Wind Harmer
1.034
270246TR4_N_V150
Solar/Wind Harmer
0.062
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.31
971343AH1-151 GEN
Solar/Wind Harmer
18.31
970291AG2-192 GEN
Solar/Wind Harmer
1.085
970291AG2-192 GEN
Solar/Wind Harmer
0.501
971613AH1-306 GEN
Solar/Wind Harmer
3.953
247621Y3-024
Adder
0.268
276916AD2-100_GEN
Solar/Wind Harmer
16.036
274827FISK ;RP
Adder
10.79
274800UNIV PARK;3U
Adder
8.099
274801UNIV PARK;4U
Adder
8.099
972227AH1-698 GEN1
Adder
3.62
247521TR3_G114
Solar/Wind Harmer
0.349
274735ELWOOD EC;4P
Adder
22.596
963791AG1-232 GEN
Solar/Wind Harmer
12.868
274744AC1-111 GEN8
Adder
7.624
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.313
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
9.036
276741O09 GEN1
Solar/Wind Harmer
0.313
274877BISHOP HL;1U
Solar/Wind Harmer
0.294
959341AF2-225 GEN
Solar/Wind Harmer
9.159
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.383
963841AG1-237 GEN
Solar/Wind Harmer
3.581
964611AG1-324 GEN
Solar/Wind Harmer
3.111
944221AF1-090 GEN
Solar/Wind Harmer
4.35
270356AE2-297 GEN
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.17
971771AH1-392 GEN
Solar/Wind Harmer
10.358
24729505KEY G4
Adder
9.292
274728ELWOOD EC;5P
Adder
22.596
971549AH1-272 GEN
Solar/Wind Harmer
19.703
270435AC2-044 GEN
Solar/Wind Harmer
1.183
970073AG2-061 GEN
Solar/Wind Harmer
3.1
276861AD2-134 GEN
Solar/Wind Harmer
0.164
276863AD2-134 GEN
Solar/Wind Harmer
0.164
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
971681AH1-341 GEN
Solar/Wind Harmer
14.503
270007AE1-245 C
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.021
970289AG2-191 GEN
Solar/Wind Harmer
1.586
276668AB2-070 GEN1
Solar/Wind Harmer
0.319
276848AB2-070 GEN3
Solar/Wind Harmer
0.317
276849AB2-070 GEN2
Solar/Wind Harmer
0.319
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24722005FLATG5
50/50
5.165
24721905FLATG4
50/50
94.337
270142AC1-141 CT1_
50/50
3.573
962771AG1-126 GEN
Solar/Wind Harmer
120.056
970153AG2-106 GEN
Solar/Wind Harmer
76.664
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
274811UNIV PK N;7U
Adder
7.005
276806AD2-047 C O1
Solar/Wind Harmer
5.492
274676JOLIET 29;8U
Adder
40.767
274734ELWOOD EC;8P
Adder
22.596
274736ELWOOD EC;9P
Adder
22.596
943121AE2-341 GEN
Solar/Wind Harmer
15.981
943591AF1-030 GEN
Solar/Wind Harmer
10.628
24695305TIMB G C
Solar/Wind Harmer
0.801
274682WAUKEGAN ;7U
Adder
24.202
959091AF2-200 GEN
Solar/Wind Harmer
18.31
274767LEE CO EC;8U
Adder
11.822
971087AG2-675 GEN
Solar/Wind Harmer
4.579
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.918
946031AF1-268 GEN
Solar/Wind Harmer
7.51
957381AF2-032 GEN
Solar/Wind Harmer
1.751
24728505AND G1
Adder
3.753
23906402RICHG1
Adder
1.086
23906502RICHG2&3
Adder
1.085
24307105BERRINSP G
50/50
0.031
965011AG1-365 GEN
Solar/Wind Harmer
10.55
957891AF2-083 GEN
Solar/Wind Harmer
17.154
945111AF1-176 GEN
Solar/Wind Harmer
18.343
274773LINCOLN ;4U
Adder
11.987
274774LINCOLN ;5U
Adder
11.987
274723RIVER EC ;12
Adder
25.237
274751CRETE EC ;1U
Adder
11.595
964861AG1-349 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.377
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.85
958861AF2-177 GEN
Solar/Wind Harmer
4.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
27.133
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.963
945371AF1-202 GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.212
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.223
270032AE2-172
Solar/Wind Harmer
5.49
270005AE1-210 C O1
Solar/Wind Harmer
1.741
276621W2-048 GEN
Solar/Wind Harmer
0.399
970825AG2-519 GEN
Solar/Wind Harmer
2.813
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
944961AF1-161 GEN
50/50
4.258
270043AE2-236 GEN
Solar/Wind Harmer
6.98
965021AG1-366 GEN
Solar/Wind Harmer
3.517
270505AE1-170 C O1
Solar/Wind Harmer
10.819
945111AF1-176 GEN
Solar/Wind Harmer
8.333
274772LINCOLN ;3U
Adder
11.987
274724RIVER EC ;11
Adder
24.945
972259AH1-714 GEN
Adder
26.498
274729ELWOOD EC;1P
Adder
22.596
246938BC-WTG3
Solar/Wind Harmer
0.336
946671AF1-331 GEN
Solar/Wind Harmer
0.983
274850MENDOTA H;RU
Solar/Wind Harmer
0.107
970571AG2-364 GEN
Solar/Wind Harmer
18.089
971993AH1-541 GEN
Solar/Wind Harmer
3.746
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.999
970825AG2-519 GEN
Solar/Wind Harmer
5.97
942481AE2-261 GEN
Solar/Wind Harmer
23.025
270240V3-007_GEN2
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
10.024
24642205MAYFLWER
50/50
0.054
962601AG1-109 GEN
50/50
4.258
274753CRETE EC ;3U
Adder
11.595
274814UNIV PK N;0U
Adder
7.066
274807UNIV PK N;3U
Adder
7.051
274803UNIV PARK;6U
Adder
8.11
972038AH1-567 GEN2
Adder
0.507
276843GEN-1.7
Solar/Wind Harmer
0.313
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
274760LEE CO EC;1U
Adder
11.963
274878BISHOP HL;2U
Solar/Wind Harmer
0.294
24690905MDL-1G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
21.892
965091AG1-374 GEN
Solar/Wind Harmer
25.724
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.741
24379505HDWTR1G C
Solar/Wind Harmer
0
24344105CKG2
50/50
11.949
970149AG2-104 GEN
Solar/Wind Harmer
64.832
943021AE2-325 GEN
Solar/Wind Harmer
5.335
970373AG2-245 GEN
Solar/Wind Harmer
20.466
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.529
274861TOP CROP ;1U
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
12.213
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.08
959081AF2-199 GEN
Solar/Wind Harmer
9.155
971067AG2-660 GEN
Solar/Wind Harmer
3.052
274822ROCKFORD ;11
Adder
25.668
970819AG2-516 GEN
Solar/Wind Harmer
10.889
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
19.06
970773AG2-487 GEN
Solar/Wind Harmer
1.148
970707AG2-453 GEN
Solar/Wind Harmer
31.765
274826FISK ;BP
Adder
15.225
274887GEN-1.85
Solar/Wind Harmer
0.252
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
22.596
274862TOP CROP ;2U
Solar/Wind Harmer
1.27
276868AE1-113 GEN
Solar/Wind Harmer
1.852
274879MINONK ;1U
Solar/Wind Harmer
0.386
274855GSG-6 ;RU
Solar/Wind Harmer
0.336
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.799
959611AF2-252 GEN
Solar/Wind Harmer
2.858
970193AG2-126 GEN
Solar/Wind Harmer
11.007
24728705AND G3
Adder
7.849
270541AE2-072 C
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
120.056
274754CRETE EC ;4U
Adder
11.595
274802UNIV PARK;5U
Adder
8.11
274674JOLIET 9 ;6U
Adder
21.182
274732ELWOOD EC;7P
Adder
22.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.87
939401AE1-172 GEN
Solar/Wind Harmer
6.964
274766LEE CO EC;7U
Adder
11.822
276708O09 GEN2
Solar/Wind Harmer
0.313
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.916
965911AG1-460 GEN
Solar/Wind Harmer
1.54
270437AC2-090 C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.858
966841AG1-555 GEN
Solar/Wind Harmer
0.962
270599AE1-208 GEN
Solar/Wind Harmer
7.759
276615X2-022 GEN
Solar/Wind Harmer
0.083
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.796
970883AG2-550 GEN
Solar/Wind Harmer
7.172
24721805FLATG3
50/50
5.165
270143AC1-141 CT2_
50/50
3.573
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.205
970155AG2-107 GEN
Solar/Wind Harmer
76.664
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.005
274676JOLIET 29;8U
Adder
42.277
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.624
965421AG1-410 GEN
Solar/Wind Harmer
28.373
965651AG1-433 GEN
Solar/Wind Harmer
2.763
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.202
274828WAUKEGAN ;BP
Adder
14.856
957471AF2-041 GEN
Solar/Wind Harmer
27.465
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.437
24728605AND G2
Adder
3.753
23906502RICHG2&3
Adder
1.085
971587AH1-292 GEN
Solar/Wind Harmer
4.706
NYPJM->LTFIMP_NY
CLTF
2.987
LGEELTFEXP_LGEE->PJM
CLTF
4.166
WECLTFEXP_WEC->PJM
CLTF
4.975
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.28
AG2-052LTFEXP_AG2-052->PJM
LTF
0.313
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.612
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.183
MECLTFEXP_MEC->PJM
CLTF
18.423
SIGELTFEXP_SIGE->PJM
CLTF
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
11.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.355
TVALTFEXP_TVA->PJM
CLTF
4.573

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5774.92
MW Contribution:
5.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
10.297
970149AG2-104 GEN
Solar/Wind Harmer
43.619
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274753CRETE EC ;3U
Adder
10.415
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274803UNIV PARK;6U
Adder
7.339
276843GEN-1.7
Solar/Wind Harmer
0.284
972038AH1-567 GEN2
Adder
0.459
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
11.202
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
20.885
965091AG1-374 GEN
Solar/Wind Harmer
24.551
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.624
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
24722005FLATG5
50/50
1.801
24721705FLATG2
50/50
26.753
965681AG1-436 GEN
Solar/Wind Harmer
11.209
276776AD2-060 GEN
Solar/Wind Harmer
0.937
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
80.774
274754CRETE EC ;4U
Adder
10.415
274802UNIV PARK;5U
Adder
7.339
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
939401AE1-172 GEN
Solar/Wind Harmer
6.422
274766LEE CO EC;7U
Adder
11.07
276708O09 GEN2
Solar/Wind Harmer
0.295
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.542
276903AD2-071 C
Solar/Wind Harmer
8.459
270437AC2-090 C
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
17.36
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274728ELWOOD EC;5P
Adder
20.57
24729505KEY G4
Adder
8.09
970073AG2-061 GEN
Solar/Wind Harmer
2.857
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
971681AH1-341 GEN
Solar/Wind Harmer
13.557
24691005MDL-2G C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
16.367
270435AC2-044 GEN
Solar/Wind Harmer
0.891
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
274751CRETE EC ;1U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
945111AF1-176 GEN
Solar/Wind Harmer
15.659
964861AG1-349 GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
971997AH1-543 GEN
Solar/Wind Harmer
4.485
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
270100X2-052 CT1
50/50
1.903
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
970941AG2-585 GEN
Solar/Wind Harmer
4.83
276897AD1-100 C
Solar/Wind Harmer
21.908
276893AG1-478 C
Solar/Wind Harmer
0.582
274696ROCKY RD ;4P
Adder
14.112
274697ROCKY RD ;3P
Adder
3.745
962691AG1-118 GEN
Solar/Wind Harmer
25.814
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274762LEE CO EC;3U
Adder
11.202
957841AF2-078 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
942111AE2-223 GEN
Solar/Wind Harmer
2.686
24387305FR-4G C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276838X2-022 GEN2
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.284
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
270101X2-052 CT2
50/50
1.903
965791AG1-447 GEN
Solar/Wind Harmer
8.22
958011AF2-095 GEN
Solar/Wind Harmer
12.646
247620Y3-023
Adder
0.579
274695ROCKY RD ;2P
Adder
13.787
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.662
274765LEE CO EC;6U
Adder
11.229
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.257
276911AD2-131_GEN
Solar/Wind Harmer
1.062
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.23
24721605FLATG1
50/50
1.801
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274746AC1-111 G10
Adder
6.969
959331AF2-224 GEN
Solar/Wind Harmer
5.989
926823AC1-168 GEN
Solar/Wind Harmer
1.434
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
965041AG1-368 GEN
Solar/Wind Harmer
7.859
971609AH1-304 GEN
Solar/Wind Harmer
1.264
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270356AE2-297 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
274827FISK ;RP
Adder
9.767
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274735ELWOOD EC;4P
Adder
20.57
274744AC1-111 GEN8
Adder
6.969
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
8.435
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
959341AF2-225 GEN
Solar/Wind Harmer
8.677
963791AG1-232 GEN
Solar/Wind Harmer
10.858
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.486
247521TR3_G114
Solar/Wind Harmer
0.275
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.06
970349AG2-230 GEN
Solar/Wind Harmer
14.053
274808UNIV PK N;4U
Adder
6.289
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
274693ROCKY RD ;1P
Adder
13.651
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
274764LEE CO EC;5U
Adder
11.229
960971AF2-388 GEN
Solar/Wind Harmer
4.897
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.728
966841AG1-555 GEN
Solar/Wind Harmer
0.921
276615X2-022 GEN
Solar/Wind Harmer
0.081
270599AE1-208 GEN
Solar/Wind Harmer
7.096
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
6.689
270054AF2-122 C O1
Solar/Wind Helper
1.547
24721805FLATG3
50/50
1.801
970155AG2-107 GEN
Solar/Wind Harmer
51.58
24639705ELKHART HY
Adder
0.194
274812UNIV PK N;8U
Adder
6.317
274676JOLIET 29;8U
Adder
38.449
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.229
274828WAUKEGAN ;BP
Adder
13.652
957471AF2-041 GEN
Solar/Wind Harmer
25.504
965651AG1-433 GEN
Solar/Wind Harmer
2.449
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
21.55
970613AG2-401 GEN
Solar/Wind Harmer
5.196
24728605AND G2
Adder
3.809
972203AH1-686 GEN
Adder
1.998
274775LINCOLN ;6U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
959141AF2-205 GEN
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
972267AH1-718 GEN
Adder
4.986
946321AF1-296 GEN
Solar/Wind Harmer
4.601
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.795
247536S-71 GEN
Solar/Wind Harmer
0.278
971029AG2-637 GEN
Solar/Wind Harmer
9.586
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
274811UNIV PK N;7U
Adder
6.317
276806AD2-047 C O1
Solar/Wind Harmer
4.976
274676JOLIET 29;8U
Adder
37.076
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
959091AF2-200 GEN
Solar/Wind Harmer
17.002
274767LEE CO EC;8U
Adder
11.07
971087AG2-675 GEN
Solar/Wind Harmer
4.368
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
24695305TIMB G C
Solar/Wind Harmer
0.627
946031AF1-268 GEN
Solar/Wind Harmer
6.994
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
4.684
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274826FISK ;BP
Adder
13.782
274887GEN-1.85
Solar/Wind Harmer
0.228
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
20.57
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
959611AF2-252 GEN
Solar/Wind Harmer
2.728
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24728705AND G3
Adder
7.966
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274861TOP CROP ;1U
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
11.164
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.998
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
270246TR4_N_V150
Solar/Wind Harmer
0.049
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
274724RIVER EC ;11
Adder
22.43
270505AE1-170 C O1
Solar/Wind Harmer
9.246
972259AH1-714 GEN
Adder
24.043
945111AF1-176 GEN
Solar/Wind Harmer
7.113
274729ELWOOD EC;1P
Adder
20.57
965021AG1-366 GEN
Solar/Wind Harmer
2.852
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
970571AG2-364 GEN
Solar/Wind Harmer
16.871
971993AH1-541 GEN
Solar/Wind Harmer
3.663
942481AE2-261 GEN
Solar/Wind Harmer
23.05
970825AG2-519 GEN
Solar/Wind Harmer
5.579
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.28 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5040.8
MW Contribution:
4.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
944961AF1-161 GEN
50/50
4.258
270043AE2-236 GEN
Solar/Wind Harmer
6.98
965021AG1-366 GEN
Solar/Wind Harmer
3.517
270100X2-052 CT1
50/50
2.175
274770LINCOLN ;1U
Adder
11.987
274771LINCOLN ;2U
Adder
11.987
274805UNIV PK N;1U
Adder
7.02
274888KELLY CRK;1U
Solar/Wind Harmer
0.565
970941AG2-585 GEN
Solar/Wind Harmer
5.331
276897AD1-100 C
Solar/Wind Harmer
24.102
276893AG1-478 C
Solar/Wind Harmer
0.639
274697ROCKY RD ;3P
Adder
4.079
274696ROCKY RD ;4P
Adder
15.37
962691AG1-118 GEN
Solar/Wind Harmer
28.03
246937BC-WTG2
Solar/Wind Harmer
0.377
942221AE2-234 GEN
Solar/Wind Harmer
3.701
938861AE1-114 GEN
Solar/Wind Harmer
5.103
274762LEE CO EC;3U
Adder
11.963
957841AF2-078 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.43
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.607
942111AE2-223 GEN
Solar/Wind Harmer
2.835
24387305FR-4G C
Solar/Wind Harmer
0
24721705FLATG2
50/50
76.7
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
12.767
276776AD2-060 GEN
Solar/Wind Harmer
1.034
270246TR4_N_V150
Solar/Wind Harmer
0.062
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.31
971343AH1-151 GEN
Solar/Wind Harmer
18.31
970291AG2-192 GEN
Solar/Wind Harmer
1.085
970291AG2-192 GEN
Solar/Wind Harmer
0.501
971613AH1-306 GEN
Solar/Wind Harmer
3.953
247621Y3-024
Adder
0.268
276916AD2-100_GEN
Solar/Wind Harmer
16.036
971587AH1-292 GEN
Solar/Wind Harmer
4.706
24344105CKG2
50/50
11.949
970149AG2-104 GEN
Solar/Wind Harmer
64.832
943021AE2-325 GEN
Solar/Wind Harmer
5.335
970373AG2-245 GEN
Solar/Wind Harmer
20.466
941551AE2-152 GEN
Solar/Wind Harmer
0.001
247620Y3-023
50/50
0.723
270101X2-052 CT2
50/50
2.175
965791AG1-447 GEN
Solar/Wind Harmer
9.363
958011AF2-095 GEN
Solar/Wind Harmer
13.957
944541AF1-119 GEN
Solar/Wind Harmer
0.629
274695ROCKY RD ;2P
Adder
15.016
958491AF2-143 GEN
Solar/Wind Harmer
13.95
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.86
274765LEE CO EC;6U
Adder
11.991
274763LEE CO EC;4U
Adder
11.851
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.656
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.598
24699105WLD G1 C
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
1.056
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.391
24721605FLATG1
50/50
5.165
270144AC1-141 ST1_
50/50
3.155
959331AF2-224 GEN
Solar/Wind Harmer
7.385
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
11.987
965041AG1-368 GEN
Solar/Wind Harmer
9.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274687WILL CNTY;4U
Adder
38.553
274687WILL CNTY;4U
Adder
38.553
274731ELWOOD EC;2P
Adder
22.596
274733ELWOOD EC;3P
Adder
22.596
274746AC1-111 G10
Adder
7.624
926823AC1-168 GEN
Solar/Wind Harmer
1.537
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.383
963841AG1-237 GEN
Solar/Wind Harmer
3.581
964611AG1-324 GEN
Solar/Wind Harmer
3.111
944221AF1-090 GEN
Solar/Wind Harmer
4.35
270356AE2-297 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.354
24643105BUCHANAN
50/50
0.019
970349AG2-230 GEN
Solar/Wind Harmer
16.255
961051AF2-396 GEN
Solar/Wind Harmer
20.485
961051AF2-396 GEN
Solar/Wind Harmer
13.656
274808UNIV PK N;4U
Adder
6.974
270247TR4_N_V136
Solar/Wind Harmer
0.062
274674JOLIET 9 ;6U
Adder
21.182
944231AF1-091 GEN
Solar/Wind Harmer
21.933
960971AF2-388 GEN
Solar/Wind Harmer
5.526
958481AF2-142 GEN
Solar/Wind Harmer
14.114
274693ROCKY RD ;1P
Adder
14.868
274683WAUKEGAN ;8U
Adder
28.341
274683WAUKEGAN ;8U
Adder
23.89
270462AD2-086
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.289
274764LEE CO EC;5U
Adder
11.991
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.858
966841AG1-555 GEN
Solar/Wind Harmer
0.962
270599AE1-208 GEN
Solar/Wind Harmer
7.759
276615X2-022 GEN
Solar/Wind Harmer
0.083
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.796
970883AG2-550 GEN
Solar/Wind Harmer
7.172
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.587
970031AG2-029 GEN
Solar/Wind Harmer
5.617
274775LINCOLN ;6U
Adder
11.987
274777LINCOLN ;8U
Adder
11.987
972037AH1-567 GEN1
Adder
0.255
960591AF2-350 GEN
Solar/Wind Harmer
9.692
972228AH1-698 GEN2
Adder
5.142
965051AG1-369 GEN
Solar/Wind Harmer
4.809
274675JOLIET 29;7U
Adder
42.278
274675JOLIET 29;7U
Adder
40.768
970833AG2-524 GEN
Solar/Wind Harmer
10.534
970833AG2-524 GEN
Solar/Wind Harmer
7.023
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.821
971675AH1-338 GEN
Solar/Wind Harmer
3.593
971611AH1-305 GEN
Solar/Wind Harmer
5.462
971171AH1-044 GEN
Solar/Wind Harmer
18.31
274823ROCKFORD ;21
Adder
25.482
972267AH1-718 GEN
Adder
5.303
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
4.834
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.301
971029AG2-637 GEN
Solar/Wind Harmer
10.16
971347AH1-153 GEN
Solar/Wind Harmer
5.418
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
45.71
274752CRETE EC ;2U
Adder
11.595
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.765
274826FISK ;BP
Adder
15.225
274887GEN-1.85
Solar/Wind Harmer
0.252
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
22.596
274862TOP CROP ;2U
Solar/Wind Harmer
1.27
276868AE1-113 GEN
Solar/Wind Harmer
1.852
274879MINONK ;1U
Solar/Wind Harmer
0.386
274855GSG-6 ;RU
Solar/Wind Harmer
0.336
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.799
959611AF2-252 GEN
Solar/Wind Harmer
2.858
970193AG2-126 GEN
Solar/Wind Harmer
11.007
24728705AND G3
Adder
7.849
270541AE2-072 C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.698
276838X2-022 GEN2
Solar/Wind Harmer
0.449
970621AG2-405 GEN
Solar/Wind Harmer
1.408
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.17
971771AH1-392 GEN
Solar/Wind Harmer
10.358
24729505KEY G4
Adder
9.292
274728ELWOOD EC;5P
Adder
22.596
971549AH1-272 GEN
Solar/Wind Harmer
19.703
270435AC2-044 GEN
Solar/Wind Harmer
1.183
274827FISK ;RP
Adder
10.79
274800UNIV PARK;3U
Adder
8.099
274801UNIV PARK;4U
Adder
8.099
972227AH1-698 GEN1
Adder
3.62
247521TR3_G114
Solar/Wind Harmer
0.349
274735ELWOOD EC;4P
Adder
22.596
963791AG1-232 GEN
Solar/Wind Harmer
12.868
274744AC1-111 GEN8
Adder
7.624
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.313
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
9.036
276741O09 GEN1
Solar/Wind Harmer
0.313
274877BISHOP HL;1U
Solar/Wind Harmer
0.294
959341AF2-225 GEN
Solar/Wind Harmer
9.159
970289AG2-191 GEN
Solar/Wind Harmer
1.586
276668AB2-070 GEN1
Solar/Wind Harmer
0.319
276848AB2-070 GEN3
Solar/Wind Harmer
0.317
276849AB2-070 GEN2
Solar/Wind Harmer
0.319
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
3.1
276861AD2-134 GEN
Solar/Wind Harmer
0.164
276863AD2-134 GEN
Solar/Wind Harmer
0.164
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
971681AH1-341 GEN
Solar/Wind Harmer
14.503
270007AE1-245 C
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.021
24307105BERRINSP G
50/50
0.031
965011AG1-365 GEN
Solar/Wind Harmer
10.55
957891AF2-083 GEN
Solar/Wind Harmer
17.154
945111AF1-176 GEN
Solar/Wind Harmer
18.343
274773LINCOLN ;4U
Adder
11.987
274774LINCOLN ;5U
Adder
11.987
274723RIVER EC ;12
Adder
25.237
274751CRETE EC ;1U
Adder
11.595
964861AG1-349 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.377
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.85
958861AF2-177 GEN
Solar/Wind Harmer
4.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
27.133
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.963
945371AF1-202 GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.212
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.223
270032AE2-172
Solar/Wind Harmer
5.49
270005AE1-210 C O1
Solar/Wind Harmer
1.741
276621W2-048 GEN
Solar/Wind Harmer
0.399
970825AG2-519 GEN
Solar/Wind Harmer
2.813
24722005FLATG5
50/50
5.165
24721905FLATG4
50/50
94.337
270142AC1-141 CT1_
50/50
3.573
962771AG1-126 GEN
Solar/Wind Harmer
120.056
970153AG2-106 GEN
Solar/Wind Harmer
76.664
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
274811UNIV PK N;7U
Adder
7.005
276806AD2-047 C O1
Solar/Wind Harmer
5.492
274676JOLIET 29;8U
Adder
40.767
274734ELWOOD EC;8P
Adder
22.596
274736ELWOOD EC;9P
Adder
22.596
943121AE2-341 GEN
Solar/Wind Harmer
15.981
943591AF1-030 GEN
Solar/Wind Harmer
10.628
24695305TIMB G C
Solar/Wind Harmer
0.801
274682WAUKEGAN ;7U
Adder
24.202
959091AF2-200 GEN
Solar/Wind Harmer
18.31
274767LEE CO EC;8U
Adder
11.822
971087AG2-675 GEN
Solar/Wind Harmer
4.579
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.918
946031AF1-268 GEN
Solar/Wind Harmer
7.51
957381AF2-032 GEN
Solar/Wind Harmer
1.751
24728505AND G1
Adder
3.753
23906402RICHG1
Adder
1.086
23906502RICHG2&3
Adder
1.085
24721805FLATG3
50/50
5.165
270143AC1-141 CT2_
50/50
3.573
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.205
970155AG2-107 GEN
Solar/Wind Harmer
76.664
270449AD2-020 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
10.819
945111AF1-176 GEN
Solar/Wind Harmer
8.333
274772LINCOLN ;3U
Adder
11.987
274724RIVER EC ;11
Adder
24.945
972259AH1-714 GEN
Adder
26.498
274729ELWOOD EC;1P
Adder
22.596
246938BC-WTG3
Solar/Wind Harmer
0.336
946671AF1-331 GEN
Solar/Wind Harmer
0.983
274850MENDOTA H;RU
Solar/Wind Harmer
0.107
970571AG2-364 GEN
Solar/Wind Harmer
18.089
971993AH1-541 GEN
Solar/Wind Harmer
3.746
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.999
970825AG2-519 GEN
Solar/Wind Harmer
5.97
942481AE2-261 GEN
Solar/Wind Harmer
23.025
270240V3-007_GEN2
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
10.024
24642205MAYFLWER
50/50
0.054
962601AG1-109 GEN
50/50
4.258
274753CRETE EC ;3U
Adder
11.595
274814UNIV PK N;0U
Adder
7.066
274807UNIV PK N;3U
Adder
7.051
274803UNIV PARK;6U
Adder
8.11
972038AH1-567 GEN2
Adder
0.507
276843GEN-1.7
Solar/Wind Harmer
0.313
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
274760LEE CO EC;1U
Adder
11.963
274878BISHOP HL;2U
Solar/Wind Harmer
0.294
24690905MDL-1G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
21.892
965091AG1-374 GEN
Solar/Wind Harmer
25.724
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.741
24379505HDWTR1G C
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.529
274861TOP CROP ;1U
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
12.213
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.08
959081AF2-199 GEN
Solar/Wind Harmer
9.155
971067AG2-660 GEN
Solar/Wind Harmer
3.052
274822ROCKFORD ;11
Adder
25.668
970819AG2-516 GEN
Solar/Wind Harmer
10.889
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
19.06
970773AG2-487 GEN
Solar/Wind Harmer
1.148
962761AG1-125 GEN
Solar/Wind Harmer
120.056
274754CRETE EC ;4U
Adder
11.595
274802UNIV PARK;5U
Adder
8.11
274674JOLIET 9 ;6U
Adder
21.182
274732ELWOOD EC;7P
Adder
22.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.87
939401AE1-172 GEN
Solar/Wind Harmer
6.964
274766LEE CO EC;7U
Adder
11.822
276708O09 GEN2
Solar/Wind Harmer
0.313
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.916
965911AG1-460 GEN
Solar/Wind Harmer
1.54
270437AC2-090 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.005
274676JOLIET 29;8U
Adder
42.277
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.624
965421AG1-410 GEN
Solar/Wind Harmer
28.373
965651AG1-433 GEN
Solar/Wind Harmer
2.763
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.202
274828WAUKEGAN ;BP
Adder
14.856
957471AF2-041 GEN
Solar/Wind Harmer
27.465
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.437
24728605AND G2
Adder
3.753
23906502RICHG2&3
Adder
1.085
NYPJM->LTFIMP_NY
CLTF
2.987
LGEELTFEXP_LGEE->PJM
CLTF
4.166
WECLTFEXP_WEC->PJM
CLTF
4.975
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.28
AG2-052LTFEXP_AG2-052->PJM
LTF
0.313
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.612
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.183
MECLTFEXP_MEC->PJM
CLTF
18.423
SIGELTFEXP_SIGE->PJM
CLTF
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
11.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.355
TVALTFEXP_TVA->PJM
CLTF
4.573

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.76 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4887.22
MW Contribution:
5.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270143AC1-141 CT2_
50/50
4.509
270142AC1-141 CT1_
50/50
4.509
274811UNIV PK N;7U
Adder
8.912
276806AD2-047 C O1
Solar/Wind Harmer
6.993
274676JOLIET 29;8U
Adder
51.877
274734ELWOOD EC;8P
Adder
28.742
274736ELWOOD EC;9P
Adder
28.742
943121AE2-341 GEN
Solar/Wind Harmer
20.341
943591AF1-030 GEN
Solar/Wind Harmer
13.527
274682WAUKEGAN ;7U
Adder
30.726
959091AF2-200 GEN
Solar/Wind Harmer
23.171
274767LEE CO EC;8U
Adder
14.918
971087AG2-675 GEN
Solar/Wind Harmer
5.742
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.091
957381AF2-032 GEN
Solar/Wind Harmer
2.142
946031AF1-268 GEN
Solar/Wind Harmer
8.578
24695305TIMB G C
Solar/Wind Harmer
0.754
965681AG1-436 GEN
Solar/Wind Harmer
16.258
276776AD2-060 GEN
Solar/Wind Harmer
1.316
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
23.171
971343AH1-151 GEN
Solar/Wind Harmer
23.171
970291AG2-192 GEN
Solar/Wind Harmer
1.289
970291AG2-192 GEN
Solar/Wind Harmer
0.595
971613AH1-306 GEN
Solar/Wind Harmer
4.661
276916AD2-100_GEN
Solar/Wind Harmer
19.57
270246TR4_N_V150
Solar/Wind Harmer
0.059
247621Y3-024
Adder
0.295
971587AH1-292 GEN
Solar/Wind Harmer
5.454
270349AD2-093_GEN
Solar/Wind Helper
1.569
270471AD2-092_GEN
Solar/Wind Helper
1.569
24653605MOTTVILLE
50/50
0.007
971771AH1-392 GEN
Solar/Wind Harmer
13.087
270071AF1-092 GEN
Solar/Wind Harmer
24.893
24729505KEY G4
Adder
11.387
274728ELWOOD EC;5P
Adder
28.742
970073AG2-061 GEN
Solar/Wind Harmer
3.925
276861AD2-134 GEN
Solar/Wind Harmer
0.208
276863AD2-134 GEN
Solar/Wind Harmer
0.208
971549AH1-272 GEN
Solar/Wind Harmer
24.049
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.267
971681AH1-341 GEN
Solar/Wind Harmer
18.311
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.36
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.912
944961AF1-161 GEN
50/50
5.338
274772LINCOLN ;3U
50/50
16.29
270043AE2-236 GEN
Solar/Wind Harmer
8.579
270505AE1-170 C O1
Solar/Wind Harmer
13.603
945111AF1-176 GEN
Solar/Wind Harmer
10.436
274724RIVER EC ;11
Adder
31.767
972259AH1-714 GEN
Adder
33.781
274729ELWOOD EC;1P
Adder
28.741
946671AF1-331 GEN
Solar/Wind Harmer
1.245
274850MENDOTA H;RU
Solar/Wind Harmer
0.136
965021AG1-366 GEN
Solar/Wind Harmer
3.887
970571AG2-364 GEN
Solar/Wind Harmer
22.813
971993AH1-541 GEN
Solar/Wind Harmer
4.623
942481AE2-261 GEN
Solar/Wind Harmer
28.148
970825AG2-519 GEN
Solar/Wind Harmer
6.871
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.45
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.259
24307105BERRINSP G
50/50
0.039
274773LINCOLN ;4U
50/50
16.29
274774LINCOLN ;5U
50/50
16.29
957891AF2-083 GEN
Solar/Wind Harmer
21.547
945111AF1-176 GEN
Solar/Wind Harmer
22.973
274723RIVER EC ;12
Adder
32.136
274751CRETE EC ;1U
Adder
14.744
964861AG1-349 GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
6.138
965011AG1-365 GEN
Solar/Wind Harmer
11.662
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
14.32
970569AG2-363 GEN
Solar/Wind Harmer
34.22
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
15.096
958861AF2-177 GEN
Solar/Wind Harmer
4.817
939741AE1-205 GEN
Solar/Wind Harmer
15.28
945371AF1-202 GEN
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.491
270594AE1-207 GEN
Solar/Wind Harmer
10.875
270032AE2-172
Solar/Wind Harmer
6.473
270005AE1-210 C O1
Solar/Wind Harmer
2.023
970825AG2-519 GEN
Solar/Wind Harmer
3.238
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.29
270489AE1-102 GEN1
Solar/Wind Harmer
0.936
270100X2-052 CT1
50/50
2.772
274770LINCOLN ;1U
50/50
16.29
274771LINCOLN ;2U
50/50
16.29
274805UNIV PK N;1U
Adder
8.931
274888KELLY CRK;1U
Solar/Wind Harmer
0.72
970941AG2-585 GEN
Solar/Wind Harmer
6.787
276897AD1-100 C
Solar/Wind Harmer
30.687
276893AG1-478 C
Solar/Wind Harmer
0.813
274697ROCKY RD ;3P
Adder
5.181
274696ROCKY RD ;4P
Adder
19.521
962691AG1-118 GEN
Solar/Wind Harmer
35.572
938861AE1-114 GEN
Solar/Wind Harmer
6.442
274762LEE CO EC;3U
Adder
15.096
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.801
276645AC1-214 GEN1
Solar/Wind Harmer
0.437
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
3.547
942221AE2-234 GEN
Solar/Wind Harmer
4.299
24387305FR-4G C
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.552
970241AG2-163 GEN
Solar/Wind Harmer
5.716
970623AG2-406 GEN
Solar/Wind Harmer
1.411
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.29
24344105CKG2
50/50
15.609
943021AE2-325 GEN
Solar/Wind Harmer
6.687
970373AG2-245 GEN
Solar/Wind Harmer
25.838
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.939
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
15.316
276882AE2-255 GEN
Solar/Wind Harmer
1.367
959081AF2-199 GEN
Solar/Wind Harmer
11.585
971067AG2-660 GEN
Solar/Wind Harmer
3.862
274822ROCKFORD ;11
Adder
32.468
970819AG2-516 GEN
Solar/Wind Harmer
13.763
276646AC1-214 GEN2
Solar/Wind Harmer
0.437
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
23.192
970773AG2-487 GEN
Solar/Wind Harmer
1.245
970091AG2-072 GEN
Adder
68.038
270101X2-052 CT2
50/50
2.772
247620Y3-023
50/50
0.894
965791AG1-447 GEN
Solar/Wind Harmer
11.923
958011AF2-095 GEN
Solar/Wind Harmer
17.77
274695ROCKY RD ;2P
Adder
19.071
958491AF2-143 GEN
Solar/Wind Harmer
17.663
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
3.616
944541AF1-119 GEN
Solar/Wind Harmer
0.761
274765LEE CO EC;6U
Adder
15.132
274763LEE CO EC;4U
Adder
14.954
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
5.447
276911AD2-131_GEN
Solar/Wind Harmer
1.289
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.673
270201AC2-176 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.552
270144AC1-141 ST1_
50/50
3.981
274776LINCOLN ;7U
50/50
16.29
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
49.058
274687WILL CNTY;4U
Adder
49.058
274731ELWOOD EC;2P
Adder
28.741
274733ELWOOD EC;3P
Adder
28.741
274746AC1-111 G10
Adder
9.698
959331AF2-224 GEN
Solar/Wind Harmer
8.163
926823AC1-168 GEN
Solar/Wind Harmer
1.939
276726Z2-087_GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.381
965041AG1-368 GEN
Solar/Wind Harmer
10.029
971609AH1-304 GEN
Solar/Wind Harmer
1.618
944221AF1-090 GEN
Solar/Wind Harmer
5.276
964611AG1-324 GEN
Solar/Wind Harmer
3.501
270356AE2-297 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
3
24643105BUCHANAN
50/50
0.023
970349AG2-230 GEN
Solar/Wind Harmer
20.983
961051AF2-396 GEN
Solar/Wind Harmer
25.67
961051AF2-396 GEN
Solar/Wind Harmer
17.113
274808UNIV PK N;4U
Adder
8.873
274674JOLIET 9 ;6U
Adder
26.949
274693ROCKY RD ;1P
Adder
18.884
958481AF2-142 GEN
Solar/Wind Harmer
17.9
274683WAUKEGAN ;8U
Adder
35.976
274683WAUKEGAN ;8U
Adder
30.326
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.159
960971AF2-388 GEN
Solar/Wind Harmer
6.685
274764LEE CO EC;5U
Adder
15.132
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
3.565
966841AG1-555 GEN
Solar/Wind Harmer
1.183
944231AF1-091 GEN
Solar/Wind Harmer
23.934
270599AE1-208 GEN
Solar/Wind Harmer
9.078
276615X2-022 GEN
Solar/Wind Harmer
0.102
270247TR4_N_V136
Solar/Wind Harmer
0.059
24725505WLD G2 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
9.289
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.657
24344005CKG1
50/50
12.151
24641605TWIN BRNCH
50/50
0.032
274775LINCOLN ;6U
50/50
16.29
274777LINCOLN ;8U
50/50
16.29
970031AG2-029 GEN
Solar/Wind Harmer
6.756
972037AH1-567 GEN1
Adder
0.324
960591AF2-350 GEN
Solar/Wind Harmer
12.34
972228AH1-698 GEN2
Adder
6.548
274675JOLIET 29;7U
Adder
53.8
274675JOLIET 29;7U
Adder
51.878
970833AG2-524 GEN
Solar/Wind Harmer
13.404
970833AG2-524 GEN
Solar/Wind Harmer
8.936
971675AH1-338 GEN
Solar/Wind Harmer
4.551
971411AH1-196 GEN
Solar/Wind Harmer
17.505
971171AH1-044 GEN
Solar/Wind Harmer
23.171
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
32.233
971611AH1-305 GEN
Solar/Wind Harmer
6.82
972267AH1-718 GEN
Adder
6.682
946321AF1-296 GEN
Solar/Wind Harmer
6.067
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
4.586
247536S-71 GEN
Solar/Wind Harmer
0.329
971029AG2-637 GEN
Solar/Wind Harmer
10.541
971347AH1-153 GEN
Solar/Wind Harmer
6.994
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
56.263
274752CRETE EC ;2U
Adder
14.744
970707AG2-453 GEN
Solar/Wind Harmer
40.554
274826FISK ;BP
Adder
19.382
274887GEN-1.85
Solar/Wind Harmer
0.321
939351AE1-166 GEN
Solar/Wind Harmer
0.001
274730ELWOOD EC;6P
Adder
28.742
274862TOP CROP ;2U
Solar/Wind Harmer
1.61
276868AE1-113 GEN
Solar/Wind Harmer
2.344
274879MINONK ;1U
Solar/Wind Harmer
0.489
274855GSG-6 ;RU
Solar/Wind Harmer
0.426
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.899
959611AF2-252 GEN
Solar/Wind Harmer
3.565
970193AG2-126 GEN
Solar/Wind Harmer
13.114
24728705AND G3
Adder
8.888
274827FISK ;RP
Adder
13.736
274800UNIV PARK;3U
Adder
10.31
274801UNIV PARK;4U
Adder
10.31
972227AH1-698 GEN1
Adder
4.611
274735ELWOOD EC;4P
Adder
28.741
274744AC1-111 GEN8
Adder
9.698
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
11.381
276741O09 GEN1
Solar/Wind Harmer
0.394
274877BISHOP HL;1U
Solar/Wind Harmer
0.369
959341AF2-225 GEN
Solar/Wind Harmer
11.46
963791AG1-232 GEN
Solar/Wind Harmer
14.314
276668AB2-070 GEN1
Solar/Wind Harmer
0.393
276848AB2-070 GEN3
Solar/Wind Harmer
0.392
276849AB2-070 GEN2
Solar/Wind Harmer
0.393
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.884
247521TR3_G114
Solar/Wind Harmer
0.333
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
24728505AND G1
Adder
4.25
24642205MAYFLWER
50/50
0.068
962601AG1-109 GEN
50/50
5.338
274753CRETE EC ;3U
Adder
14.744
274814UNIV PK N;0U
Adder
8.99
274807UNIV PK N;3U
Adder
8.97
274803UNIV PARK;6U
Adder
10.322
276843GEN-1.7
Solar/Wind Harmer
0.399
972038AH1-567 GEN2
Adder
0.645
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
15.096
274878BISHOP HL;2U
Solar/Wind Harmer
0.369
24690905MDL-1G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
27.452
965091AG1-374 GEN
Solar/Wind Harmer
32.089
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
2.023
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.936
274754CRETE EC ;4U
Adder
14.744
24639705ELKHART HY
50/50
0.301
970521AG2-332 GEN
50/50
21.375
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
8.912
274676JOLIET 29;8U
Adder
53.799
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.698
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
30.726
274828WAUKEGAN ;BP
Adder
18.858
957471AF2-041 GEN
Solar/Wind Harmer
34.756
965651AG1-433 GEN
Solar/Wind Harmer
3.342
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.002
970613AG2-401 GEN
Solar/Wind Harmer
6.152
24728605AND G2
Adder
4.25
965421AG1-410 GEN
Solar/Wind Harmer
22.891
274802UNIV PARK;5U
Adder
10.322
274674JOLIET 9 ;6U
Adder
26.949
274732ELWOOD EC;7P
Adder
28.742
962781AG1-127 GEN
Solar/Wind Harmer
11.253
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
8.816
274766LEE CO EC;7U
Adder
14.918
276708O09 GEN2
Solar/Wind Harmer
0.394
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.883
276903AD2-071 C
Solar/Wind Harmer
10.45
270437AC2-090 C
Solar/Wind Harmer
0
NYPJM->LTFIMP_NY
CLTF
2.94
LGEELTFEXP_LGEE->PJM
CLTF
4.042
WECLTFEXP_WEC->PJM
CLTF
6.289
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.78
AG2-052LTFEXP_AG2-052->PJM
LTF
0.393
AH1-155LTFEXP_AH1-155->PJM
LTF
0.59
CBM West 2LTFEXP_CBM-W2->PJM
CBM
110.466
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.285
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.325
MECLTFEXP_MEC->PJM
CLTF
22.729
SIGELTFEXP_SIGE->PJM
CLTF
0.435
LAGNLTFEXP_LAGN->PJM
CLTF
12.231
TVALTFEXP_TVA->PJM
CLTF
4.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6428.58
MW Contribution:
7.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971313AH1-133 GEN
Solar/Wind Harmer
5.062
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
971061AG2-657 GEN
Solar/Wind Harmer
6.001
270543AE2-219 C
Solar/Wind Harmer
6.546
24691005MDL-2G C
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.55
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
3.032
276861AD2-134 GEN
Solar/Wind Harmer
0.162
276863AD2-134 GEN
Solar/Wind Harmer
0.162
971681AH1-341 GEN
Solar/Wind Harmer
14.63
274728ELWOOD EC;5P
Adder
21.404
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
20089226LOOKOUT
Solar/Wind Helper
0.686
241985AE1-237 GEN
Solar/Wind Helper
0.274
24318705GVG2
50/50
11.565
971687AH1-348 GEN
Solar/Wind Harmer
1.062
25196808ZIMRHP
Adder
108.598
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970879AG2-548 GEN
Solar/Wind Harmer
1.694
970107AG2-081 GEN
Solar/Wind Harmer
2.978
970241AG2-163 GEN
Solar/Wind Harmer
5.492
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.521
942111AE2-223 GEN
Solar/Wind Harmer
2.987
276645AC1-214 GEN1
Solar/Wind Harmer
0.358
276897AD1-100 C
Solar/Wind Harmer
22.743
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.467
962691AG1-118 GEN
Solar/Wind Harmer
27.261
970913AG2-568 GEN
Solar/Wind Harmer
8.731
24728205BUCHG1
Adder
6.8
971073AG2-665 GEN
Solar/Wind Harmer
7.453
252509AD1-136 GEN
Solar/Wind Harmer
0.05
972045AH1-571 GEN
Solar/Wind Harmer
2.084
25183208HLCRTG
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
2.009
964571AG1-320 GEN
Solar/Wind Harmer
8.813
270269AC2-059
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
5.185
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
0
966021AG1-471 GEN
Solar/Wind Harmer
5.029
270031AE2-169
Solar/Wind Harmer
5.121
945421AF1-207 GEN
Solar/Wind Harmer
0
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
270201AC2-176 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
1.282
944541AF1-119 GEN
Solar/Wind Harmer
0.618
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.642
274695ROCKY RD ;2P
Adder
14.499
274765LEE CO EC;6U
Adder
12.144
274763LEE CO EC;4U
Adder
12.001
972236AH1-702 GEN2
Adder
2.854
971277AH1-098 GEN
Solar/Wind Harmer
3.633
958011AF2-095 GEN
Solar/Wind Harmer
13.073
235054AD2-180 GEN
Solar/Wind Helper
2.046
235531U2-073 GEN
Solar/Wind Helper
3.281
254304AE2-114 C
Solar/Wind Helper
0.241
203961AE2-224 GEN
Solar/Wind Helper
2.731
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
946751AF1-339 GEN
Solar/Wind Helper
0.504
20674328GAR_V4-001
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219912AD2-042 GEN
Solar/Wind Helper
0.159
233994AC2-023 GEN
Solar/Wind Helper
1.001
234036AF2-325 C
Solar/Wind Helper
0.044
232436AB1-176 C
Solar/Wind Helper
0.046
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
27.062
270400AC1-102 GEN
Solar/Wind Harmer
3.79
941621AE2-160 GEN
Adder
5.034
972163AH1-664 GEN
Solar/Wind Harmer
11.291
3429211JKCT 2G
Adder
16.597
25196508WSDLE4
Adder
12.037
24734805WLF1G4
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.978
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
4.07
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.521
964611AG1-324 GEN
Solar/Wind Harmer
3.625
270432AC2-029 GEN
Solar/Wind Harmer
4.119
944221AF1-090 GEN
Solar/Wind Harmer
5.449
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
0.996
926823AC1-168 GEN
Solar/Wind Harmer
1.55
274776LINCOLN ;7U
Adder
11.001
274746AC1-111 G10
Adder
7.28
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
23750501ELLIOTTS
Solar/Wind Helper
0.793
238118U2-030_1
Solar/Wind Helper
0.345
20089126CSLMN_L13
Solar/Wind Helper
0.688
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
20334926Z1-069 C
Solar/Wind Helper
1.501
959421AF2-233 GEN
Solar/Wind Helper
0.504
209029WAYMART-WD
Solar/Wind Helper
0.944
20675128HRM_W1-127
Solar/Wind Helper
0.033
972043AH1-570 GEN
Solar/Wind Harmer
2.601
25194408D.CRK1
Adder
10.747
942891AE2-308 GEN
Solar/Wind Harmer
9.908
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
10.085
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.061
970883AG2-550 GEN
Solar/Wind Harmer
9.352
24697605MDL-3G C
Solar/Wind Harmer
0
971485AH1-239 GEN
Solar/Wind Harmer
7.452
964781AG1-341 GEN
Solar/Wind Harmer
9.873
270599AE1-208 GEN
Solar/Wind Harmer
8.535
960971AF2-388 GEN
Solar/Wind Harmer
5.431
276615X2-022 GEN
Solar/Wind Harmer
0.096
960611AF2-352 GEN
Solar/Wind Harmer
3.067
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
13.633
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
972235AH1-702 GEN1
Adder
3.282
274674JOLIET 9 ;6U
Adder
20.046
274683WAUKEGAN ;8U
Adder
27.432
23585401KL_K28_T16
Solar/Wind Helper
1.54
238117U2-030
Solar/Wind Helper
0.345
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
20675428EAM_W2-061
Solar/Wind Helper
0.017
207459AE1-142 C O1
Solar/Wind Helper
0.312
214067T20SOLAR
Solar/Wind Helper
0.012
230433AD2-135 GEN
Solar/Wind Helper
0.018
234015AF2-250 C
Solar/Wind Helper
0.04
232428Y3-058 C
Solar/Wind Helper
0.352
232424Y1-079 C
Solar/Wind Helper
0.121
235062AE1-101 C1
Solar/Wind Helper
1.478
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
270399AC1-101 GEN
Solar/Wind Harmer
3.79
971985AH1-537 GEN
Solar/Wind Harmer
3.231
972165AH1-665 GEN
Solar/Wind Harmer
9.043
339216AC1-074 GEN
Solar/Wind Harmer
0.266
24734705WLF1G3
Adder
8.159
24734905WLF1G5
Adder
8.159
253406AD2-031_GEN
Solar/Wind Harmer
0.728
270291AC1-194 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
14.087
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.372
971611AH1-305 GEN
Solar/Wind Harmer
5.499
959141AF2-205 GEN
Solar/Wind Harmer
0.001
966391AG1-508 GEN
Solar/Wind Harmer
1.42
274775LINCOLN ;6U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
970833AG2-524 GEN
Solar/Wind Harmer
10.003
970833AG2-524 GEN
Solar/Wind Harmer
6.669
971675AH1-338 GEN
Solar/Wind Harmer
3.544
971171AH1-044 GEN
Solar/Wind Harmer
18.173
972267AH1-718 GEN
Adder
5.423
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274823ROCKFORD ;21
Adder
25.367
971411AH1-196 GEN
Solar/Wind Harmer
13.626
972228AH1-698 GEN2
Adder
4.822
960591AF2-350 GEN
Solar/Wind Harmer
9.078
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
203955AF1-039 C O1
Solar/Wind Helper
0.435
203846AF2-130 C
Solar/Wind Helper
0.501
959431AF2-234 GEN
Solar/Wind Helper
1.007
212266LOR1
Solar/Wind Helper
0.342
961261AF2-417 GEN
Solar/Wind Helper
0.499
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
219620RIDERU C
Solar/Wind Helper
0.001
219615MILLCREEK C
Solar/Wind Helper
0.028
227927V4-067C
Solar/Wind Helper
0.011
228728W1-130C
Solar/Wind Helper
0.057
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
971461AH1-227 GEN
Solar/Wind Harmer
5.44
252507AC2-088 GEN
Solar/Wind Harmer
0.453
958171AF2-111 GEN
Solar/Wind Harmer
25.009
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
24728705AND G3
Adder
10.976
970193AG2-126 GEN
Solar/Wind Harmer
14.237
270346AE1-212 GEN
Solar/Wind Harmer
8.358
970781AG2-491 GEN
Solar/Wind Harmer
9.325
959611AF2-252 GEN
Solar/Wind Harmer
3.067
944531AF1-118 GEN
Solar/Wind Harmer
41.107
276782AC1-033 GEN
Solar/Wind Harmer
0
276868AE1-113 GEN
Solar/Wind Harmer
1.82
274879MINONK ;1U
Solar/Wind Harmer
0.38
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
29.702
274862TOP CROP ;2U
Solar/Wind Harmer
1.227
274855GSG-6 ;RU
Solar/Wind Harmer
0.332
274857EASY ROAD;U1
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
21.404
274887GEN-1.85
Solar/Wind Harmer
0.236
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
970281AG2-184 GEN
Solar/Wind Harmer
22.827
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
1.788
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.362
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
9.649
970169AG2-114 GEN
Solar/Wind Harmer
9.156
274877BISHOP HL;1U
Solar/Wind Harmer
0.304
276741O09 GEN1
Solar/Wind Harmer
0.321
274744AC1-111 GEN8
Adder
7.28
274735ELWOOD EC;4P
Adder
21.404
972227AH1-698 GEN1
Adder
3.396
241997AF1-093 GEN
Solar/Wind Helper
0.282
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
209054AE2-059 GEN
Solar/Wind Helper
0.091
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
230407AD2-065 C
Solar/Wind Helper
0.043
232432Z2-076 GEN
Solar/Wind Helper
0.07
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
962771AG1-126 GEN
Solar/Wind Harmer
46.005
970153AG2-106 GEN
Solar/Wind Harmer
29.378
972103AH1-617 GEN
Solar/Wind Harmer
21.74
960911AF2-382 GEN
Solar/Wind Harmer
7.999
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25194608D.CRK4
Adder
2.336
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
12.81
24728505AND G1
Adder
5.248
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.035
946031AF1-268 GEN
Solar/Wind Harmer
8.922
957381AF2-032 GEN
Solar/Wind Harmer
2.099
943031AE2-326 GEN
Solar/Wind Harmer
4.803
943121AE2-341 GEN
Solar/Wind Harmer
15.239
943591AF1-030 GEN
Solar/Wind Harmer
10.134
959091AF2-200 GEN
Solar/Wind Harmer
18.173
274767LEE CO EC;8U
Adder
11.973
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
971087AG2-675 GEN
Solar/Wind Harmer
4.845
274682WAUKEGAN ;7U
Adder
7.239
276806AD2-047 C O1
Solar/Wind Harmer
5.144
235058AG1-386 C
Solar/Wind Helper
0.518
964991AG1-363 GEN
Solar/Wind Helper
4.441
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203975AE1-071-GEN
Solar/Wind Helper
2.698
20674628WNG_W3-110
Solar/Wind Helper
0.098
217208PARK ELE C
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.018
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219766PARADISE C
Solar/Wind Helper
0.058
233996TM1833_GEN
Solar/Wind Helper
0.214
20676428JCR_X2-075
Solar/Wind Helper
0.074
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
233901CHERRYDALE C
Solar/Wind Helper
0.242
205956AE1-196_GEN
Solar/Wind Helper
0.528
205917AD1-020 ES
Solar/Wind Helper
0.371
23779801AA1-109
Solar/Wind Helper
0.169
24289405MTG1
50/50
11.336
24686405CER G5
Adder
15.429
970455AG2-298 GEN
Solar/Wind Harmer
3.77
970653AG2-424 GEN
Solar/Wind Harmer
0.96
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
2.038
970191AG2-125 GEN
Solar/Wind Harmer
2.419
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
27.602
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274878BISHOP HL;2U
Solar/Wind Harmer
0.304
253325AC1-069 GEN
Solar/Wind Harmer
0.01
274760LEE CO EC;1U
Adder
12.115
965931AG1-462 GEN
Solar/Wind Harmer
23.167
276843GEN-1.7
Solar/Wind Harmer
0.294
23562501BACKB
Solar/Wind Helper
1.078
238108AE1-109 GEN1
Solar/Wind Helper
0.103
203854AF2-039 C
Solar/Wind Helper
0.357
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
962511AG1-100 GEN
Solar/Wind Helper
0.492
24289405MTG1
50/50
11.336
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
16.719
970149AG2-104 GEN
Solar/Wind Harmer
24.844
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
3429421JKCT 10G
Adder
11.809
970653AG2-424 GEN
Solar/Wind Harmer
4.631
970773AG2-487 GEN
Solar/Wind Harmer
1.693
963741AG1-226 GEN
Solar/Wind Harmer
22.28
276655WTG1_EQ
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
11.925
276646AC1-214 GEN2
Solar/Wind Harmer
0.358
276882AE2-255 GEN
Solar/Wind Harmer
1.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.477
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
9.087
971067AG2-660 GEN
Solar/Wind Harmer
3.029
274822ROCKFORD ;11
Adder
25.553
970819AG2-516 GEN
Solar/Wind Harmer
10.9
957921AF2-086 GEN
Solar/Wind Helper
0.497
211065PSPA IPP
Solar/Wind Helper
0.169
20674128FR_U2-059
Solar/Wind Helper
0.004
207511W3-106 GEN
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
219249CENTRALDIV C
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
233935AB2-179 C
Solar/Wind Helper
1.32
237038AE2-054 C
Solar/Wind Helper
0.24
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
207518AF1-320_GEN
Solar/Wind Helper
1.73
20674928WA_W3-044
Solar/Wind Helper
0.108
20676328BVR_Y1-020
Solar/Wind Helper
0.03
20676728BRNX1-095
Solar/Wind Helper
0.032
219919AE1-041 FULL
Solar/Wind Helper
0.004
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
963711AG1-223 GEN
Solar/Wind Helper
0.069
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
938861AE1-114 GEN
Solar/Wind Harmer
5.149
274696ROCKY RD ;4P
Adder
14.841
274762LEE CO EC;3U
Adder
12.115
274697ROCKY RD ;3P
Adder
3.939
276893AG1-478 C
Solar/Wind Harmer
0.606
942221AE2-234 GEN
Solar/Wind Harmer
3.648
274888KELLY CRK;1U
Solar/Wind Harmer
0.529
970941AG2-585 GEN
Solar/Wind Harmer
4.993
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
962101AG1-054 GEN
Solar/Wind Helper
0.72
961431AF2-434 GEN
Solar/Wind Helper
0.502
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
217081WEATEXAS C
Solar/Wind Helper
0.014
219272CLEANLIGHT C
Solar/Wind Helper
0.027
228754AB1-001 C
Solar/Wind Helper
0.028
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
233946AB2-136 GEN
Solar/Wind Helper
0.592
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
223402AF1-300 C
Solar/Wind Helper
0.341
252510AF1-249 C
Solar/Wind Harmer
0.075
25196008MFTGT1
Adder
1.98
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
10.536
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
2.038
970825AG2-519 GEN
Solar/Wind Harmer
3.334
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.02
276621W2-048 GEN
Solar/Wind Harmer
0.463
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.546
939741AE1-205 GEN
Solar/Wind Harmer
12.866
964861AG1-349 GEN
Solar/Wind Harmer
0.001
970569AG2-363 GEN
Solar/Wind Harmer
27.326
971997AH1-543 GEN
Solar/Wind Harmer
4.779
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
276805AD2-038 GEN
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.115
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
23583801GRNGAP
Solar/Wind Helper
4.315
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
207437AD2-070 GEN
Solar/Wind Helper
0.152
207510AF2-138 C
Solar/Wind Helper
0.089
20673728F2S_V4-070
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
219623KINSLEYBEA C
Solar/Wind Helper
0.002
237085AD2-009_GEN
Solar/Wind Helper
1.463
233933AB2-153 GEN
Solar/Wind Helper
0.242
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
235063AE1-101 C2
Solar/Wind Helper
1.478
24318705GVG2
50/50
11.565
971191AH1-055 GEN
Solar/Wind Harmer
29.882
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
7.453
972167AH1-666 GEN
Solar/Wind Harmer
8.106
25196008MFTGT1
Adder
1.918
970093AG2-073 GEN
Solar/Wind Harmer
8.38
253394AE2-221_GEN
Solar/Wind Harmer
0.001
972273AH1-721 GEN
Adder
114.179
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
7.074
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.91
942481AE2-261 GEN
Solar/Wind Harmer
27.692
971993AH1-541 GEN
Solar/Wind Harmer
4.271
970571AG2-364 GEN
Solar/Wind Harmer
18.217
274772LINCOLN ;3U
Adder
11.001
972259AH1-714 GEN
Adder
24.853
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
946671AF1-331 GEN
Solar/Wind Harmer
0.969
274729ELWOOD EC;1P
Adder
21.404
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
946731AF1-337 GEN
Solar/Wind Helper
0.504
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
207484AF2-139 C O1
Solar/Wind Helper
0.093
20676228FRD_X1-012
Solar/Wind Helper
0.101
20673628F1S_V4-069
Solar/Wind Helper
0.032
219908AB1-139 C
Solar/Wind Helper
0.08
218428ETC SOLAR C
Solar/Wind Helper
0.005
20716028EGP_W2-019
Solar/Wind Helper
0.02
219907AC1-030 C
Solar/Wind Helper
0.036
232408W1-005 C
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
205916AD1-020 GEN
Solar/Wind Helper
1.727
238175AF1-290_GEN
Solar/Wind Helper
0.127
243186AF1-051 GEN
50/50
12.477
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
970155AG2-107 GEN
Solar/Wind Harmer
29.378
945681AF1-233 GEN
Solar/Wind Harmer
19.107
252516AE2-318_GEN
Solar/Wind Harmer
11.165
25194608D.CRK4
Adder
2.336
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.854
24735205WLF2G2
Adder
8.041
24728605AND G2
Adder
5.248
970613AG2-401 GEN
Solar/Wind Harmer
6.957
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
964901AG1-354 GEN
Solar/Wind Harmer
14.121
965651AG1-433 GEN
Solar/Wind Harmer
2.715
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.28
957471AF2-041 GEN
Solar/Wind Harmer
27.26
238185AF2-356 C
Solar/Wind Helper
2.64
238120AE2-309 GEN
Solar/Wind Helper
0.514
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
205941AD2-115 GEN
Solar/Wind Helper
0.536
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
230415AB2-049 C
Solar/Wind Helper
0.032
232406W1-004 FULL
Solar/Wind Helper
0.528
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.119
23777801MSM_W1-116
Solar/Wind Helper
0.101
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
971225AH1-072 GEN
Solar/Wind Harmer
2.121
971227AH1-073 GEN
Solar/Wind Harmer
2.121
971125AH1-004 GEN
Solar/Wind Harmer
3.97
971587AH1-292 GEN
Solar/Wind Harmer
7.164
253370AE2-315 SEC1
Adder
2.718
970291AG2-192 GEN
Solar/Wind Harmer
1.223
970291AG2-192 GEN
Solar/Wind Harmer
0.565
971613AH1-306 GEN
Solar/Wind Harmer
4.515
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
247621Y3-024
Adder
0.321
276916AD2-100_GEN
Solar/Wind Harmer
19.462
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.173
971343AH1-151 GEN
Solar/Wind Harmer
18.173
276776AD2-060 GEN
Solar/Wind Harmer
0.968
241801AE1-079 GEN
Solar/Wind Helper
0.274
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
203804AE2-113_GEN
Solar/Wind Helper
1.942
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
20720828JCB_W4-025
Solar/Wind Helper
0.068
219906AC1-017 C
Solar/Wind Helper
0.045
219904AC1-010 C
Solar/Wind Helper
0.064
237080AD1-060 GEN
Solar/Wind Helper
0.299
970373AG2-245 GEN
Solar/Wind Harmer
16.807
24686505CER G6
Adder
15.551
962761AG1-125 GEN
Solar/Wind Harmer
46.005
24728305BUCHG2
Adder
6.8
3429241JKCT 3G
Adder
16.815
270273AD2-016 GEN
Solar/Wind Harmer
0.98
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
10.535
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.852
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.831
253333AC1-068 GEN
Solar/Wind Harmer
0.01
276708O09 GEN2
Solar/Wind Harmer
0.321
962781AG1-127 GEN
Solar/Wind Harmer
8.648
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274674JOLIET 9 ;6U
Adder
20.046
20089026BF_G21_K23
Solar/Wind Helper
0.545
20084626FORWARD
Solar/Wind Helper
0.405
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
217169METRODIV C
Solar/Wind Helper
0.004
207454AA2-184 E
Solar/Wind Helper
0.335
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
233950AC2-186 GEN
Solar/Wind Helper
0.121
235067AD1-061 GEN
Solar/Wind Helper
0.394
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
203940AF1-140 C
Solar/Wind Helper
0.45
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
209027LOR2_Q27
Solar/Wind Helper
1.174
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
20390526W1-045 C
Solar/Wind Helper
0.36
219258KINSLEYDEP C
Solar/Wind Helper
0.081
230434AG1-499 GEN
Solar/Wind Helper
0.244
233940AF2-379 C
Solar/Wind Helper
0.065
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
228729W2-030 C
Solar/Wind Helper
0.117
233918AB1-142 GEN
Solar/Wind Helper
0.523
237001AB1-127_GEN
Solar/Wind Helper
0.391
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4976.63
MW Contribution:
5.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970913AG2-568 GEN
Solar/Wind Harmer
8.105
24728205BUCHG1
Adder
6.196
971277AH1-098 GEN
Solar/Wind Harmer
3.388
971073AG2-665 GEN
Solar/Wind Harmer
5.846
972045AH1-571 GEN
Solar/Wind Harmer
1.594
966021AG1-471 GEN
Solar/Wind Harmer
4.034
252509AD1-136 GEN
Solar/Wind Harmer
0.037
964571AG1-320 GEN
Solar/Wind Harmer
6.787
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.463
24728805RICHG1
Adder
3.656
276911AD2-131_GEN
Solar/Wind Harmer
0.919
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.135
270031AE2-169
Solar/Wind Harmer
3.483
964611AG1-324 GEN
Solar/Wind Harmer
0.475
270201AC2-176 GEN
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
8.405
274763LEE CO EC;4U
Adder
8.307
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.968
958491AF2-143 GEN
Solar/Wind Harmer
9.353
274695ROCKY RD ;2P
Adder
9.916
944541AF1-119 GEN
Solar/Wind Harmer
0.412
958011AF2-095 GEN
Solar/Wind Harmer
8.864
235054AD2-180 GEN
Solar/Wind Helper
1.531
270399AC1-101 GEN
Solar/Wind Harmer
3.431
24734705WLF1G3
Adder
7.275
24734905WLF1G5
Adder
7.275
971985AH1-537 GEN
Solar/Wind Harmer
2.606
966391AG1-508 GEN
Solar/Wind Harmer
1.323
971331AH1-145 GEN
Solar/Wind Harmer
10.902
971981AH1-535 GEN
Solar/Wind Harmer
5.247
972165AH1-665 GEN
Solar/Wind Harmer
6.87
339216AC1-074 GEN
Solar/Wind Harmer
0.202
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270069AE2-166 C O1
Solar/Wind Harmer
6.22
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.69
247536S-71 GEN
Solar/Wind Harmer
0.254
971611AH1-305 GEN
Solar/Wind Harmer
3.778
24721605FLATG1
50/50
2.475
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
24.531
270400AC1-102 GEN
Solar/Wind Harmer
3.431
941621AE2-160 GEN
Adder
4.685
24734805WLF1G4
Adder
7.275
24735105WLF2G1
Adder
7.131
971329AH1-144 GEN
Solar/Wind Harmer
4.007
972163AH1-664 GEN
Solar/Wind Harmer
8.578
3429211JKCT 2G
Adder
12.836
25196508WSDLE4
Adder
8.748
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.692
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.926
963841AG1-237 GEN
Solar/Wind Harmer
2.866
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
2.468
926823AC1-168 GEN
Solar/Wind Harmer
1.07
274746AC1-111 G10
Adder
4.965
274731ELWOOD EC;2P
Adder
14.558
274733ELWOOD EC;3P
Adder
14.558
971313AH1-133 GEN
Solar/Wind Harmer
4.633
971061AG2-657 GEN
Solar/Wind Harmer
5.63
25196108MFTGT2
Adder
1.606
25196108MFTGT2
Adder
1.492
25196408WSDLE3
Adder
9.098
25196308WSDLE2
Adder
9.019
25196208WSDLE1
Adder
8.997
25196708WSDLE6
Adder
8.974
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.484
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
10.116
274856ECOGROVE ;U1
Solar/Wind Harmer
0.147
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
970073AG2-061 GEN
Solar/Wind Harmer
2.078
274728ELWOOD EC;5P
Adder
14.558
970281AG2-184 GEN
Solar/Wind Harmer
20.069
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.257
276848AB2-070 GEN3
Solar/Wind Harmer
0.256
276849AB2-070 GEN2
Solar/Wind Harmer
0.257
970289AG2-191 GEN
Solar/Wind Harmer
1.233
25306009OHH W.
Adder
2.654
253372AE2-315 SEC3
Adder
1.743
253372AE2-315 SEC3
Adder
1.743
959341AF2-225 GEN
Solar/Wind Harmer
6.721
274877BISHOP HL;1U
Solar/Wind Harmer
0.211
970169AG2-114 GEN
Solar/Wind Harmer
6.325
276741O09 GEN1
Solar/Wind Harmer
0.223
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
4.965
274735ELWOOD EC;4P
Adder
14.558
24722005FLATG5
50/50
2.475
24721905FLATG4
50/50
45.211
960911AF2-382 GEN
Solar/Wind Harmer
7.256
972103AH1-617 GEN
Solar/Wind Harmer
19.113
943031AE2-326 GEN
Solar/Wind Harmer
4.478
252519AF1-045_GEN
Solar/Wind Harmer
3.801
25194608D.CRK4
Adder
1.702
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.158
962771AG1-126 GEN
Solar/Wind Harmer
27.311
970153AG2-106 GEN
Solar/Wind Harmer
17.44
24728505AND G1
Adder
3.745
270030AE2-140 GEN
Solar/Wind Harmer
13.518
957381AF2-032 GEN
Solar/Wind Harmer
1.5
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.714
946031AF1-268 GEN
Solar/Wind Harmer
6.123
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
971087AG2-675 GEN
Solar/Wind Harmer
3.389
274767LEE CO EC;8U
Adder
8.287
959091AF2-200 GEN
Solar/Wind Harmer
12.516
274682WAUKEGAN ;7U
Adder
16.004
943121AE2-341 GEN
Solar/Wind Harmer
10.39
943591AF1-030 GEN
Solar/Wind Harmer
6.91
274734ELWOOD EC;8P
Adder
14.558
274736ELWOOD EC;9P
Adder
14.558
276806AD2-047 C O1
Solar/Wind Harmer
3.488
235058AG1-386 C
Solar/Wind Helper
0.387
24318705GVG2
50/50
10.829
971687AH1-348 GEN
Solar/Wind Harmer
0.943
25196808ZIMRHP
Adder
79.991
25196008MFTGT1
Adder
1.457
252510AF1-249 C
Solar/Wind Harmer
0.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.329
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
7.264
270032AE2-172
Solar/Wind Harmer
4.324
270005AE1-210 C O1
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
2.292
939741AE1-205 GEN
Solar/Wind Harmer
8.961
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.933
970569AG2-363 GEN
Solar/Wind Harmer
18.869
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.386
945371AF1-202 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
3.283
276805AD2-038 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.692
24318705GVG2
50/50
10.829
971191AH1-055 GEN
Solar/Wind Harmer
25.524
970879AG2-548 GEN
Solar/Wind Harmer
5.846
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
6.527
972167AH1-666 GEN
Solar/Wind Harmer
6.143
972273AH1-721 GEN
Adder
91.222
25196008MFTGT1
Adder
1.411
253394AE2-221_GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
19.808
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.022
970825AG2-519 GEN
Solar/Wind Harmer
4.865
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.45
970571AG2-364 GEN
Solar/Wind Harmer
12.579
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
946671AF1-331 GEN
Solar/Wind Harmer
0.666
274729ELWOOD EC;1P
Adder
14.558
237048AF1-022 C
Solar/Wind Helper
0.175
237046AF1-021 C
Solar/Wind Helper
0.301
970879AG2-548 GEN
Solar/Wind Harmer
1.329
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970107AG2-081 GEN
Solar/Wind Harmer
2.281
970241AG2-163 GEN
Solar/Wind Harmer
3.886
276838X2-022 GEN2
Solar/Wind Harmer
0.37
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.08
276645AC1-214 GEN1
Solar/Wind Harmer
0.248
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.019
274762LEE CO EC;3U
Adder
8.386
938861AE1-114 GEN
Solar/Wind Harmer
3.56
962691AG1-118 GEN
Solar/Wind Harmer
18.68
274696ROCKY RD ;4P
Adder
10.15
274697ROCKY RD ;3P
Adder
2.694
276897AD1-100 C
Solar/Wind Harmer
15.453
276893AG1-478 C
Solar/Wind Harmer
0.412
274888KELLY CRK;1U
Solar/Wind Harmer
0.359
970941AG2-585 GEN
Solar/Wind Harmer
3.385
237043AE2-125 C
Solar/Wind Helper
0.157
23751201ROTHROCK
Solar/Wind Helper
0.666
24289405MTG1
50/50
10.896
24686405CER G5
Adder
13.963
970455AG2-298 GEN
Solar/Wind Harmer
2.913
970653AG2-424 GEN
Solar/Wind Harmer
0.745
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.4
965091AG1-374 GEN
Solar/Wind Harmer
19.301
970191AG2-125 GEN
Solar/Wind Harmer
1.638
965931AG1-462 GEN
Solar/Wind Harmer
16.203
274878BISHOP HL;2U
Solar/Wind Harmer
0.211
274760LEE CO EC;1U
Adder
8.386
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.199
23562501BACKB
Solar/Wind Helper
0.811
24289405MTG1
50/50
10.896
944971AF1-162 GEN
Solar/Wind Harmer
10.992
971403AH1-188 GEN
Solar/Wind Harmer
15.251
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.329
970091AG2-072 GEN
Adder
86.562
3429421JKCT 10G
Adder
9.095
970653AG2-424 GEN
Solar/Wind Harmer
3.596
970149AG2-104 GEN
Solar/Wind Harmer
14.748
970773AG2-487 GEN
Solar/Wind Harmer
1.199
963741AG1-226 GEN
Solar/Wind Harmer
15.765
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.248
970819AG2-516 GEN
Solar/Wind Harmer
7.523
971461AH1-227 GEN
Solar/Wind Harmer
4.836
270346AE1-212 GEN
Solar/Wind Harmer
7.826
958121AF2-106 GEN
Solar/Wind Harmer
0
3429391JKCT 9G
Adder
9.095
958171AF2-111 GEN
Solar/Wind Harmer
18.695
252507AC2-088 GEN
Solar/Wind Harmer
0.336
25196608WSDLE5
Adder
8.838
970193AG2-126 GEN
Solar/Wind Harmer
10.239
24728705AND G3
Adder
7.833
970781AG2-491 GEN
Solar/Wind Harmer
6.48
959611AF2-252 GEN
Solar/Wind Harmer
2.145
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
276868AE1-113 GEN
Solar/Wind Harmer
1.25
274879MINONK ;1U
Solar/Wind Harmer
0.261
274862TOP CROP ;2U
Solar/Wind Harmer
0.839
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
14.558
970707AG2-453 GEN
Solar/Wind Harmer
20.15
274887GEN-1.85
Solar/Wind Harmer
0.16
24686505CER G6
Adder
14.074
24728305BUCHG2
Adder
6.196
3429241JKCT 3G
Adder
13.004
962761AG1-125 GEN
Solar/Wind Harmer
27.311
965911AG1-460 GEN
Solar/Wind Harmer
1.325
270437AC2-090 C
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.31
270273AD2-016 GEN
Solar/Wind Harmer
0.662
276708O09 GEN2
Solar/Wind Harmer
0.223
274766LEE CO EC;7U
Adder
8.287
25326309TAIT D
Adder
0.988
939401AE1-172 GEN
Solar/Wind Harmer
4.684
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
5.929
274732ELWOOD EC;7P
Adder
14.558
274674JOLIET 9 ;6U
Adder
13.632
942891AE2-308 GEN
Solar/Wind Harmer
7.677
972043AH1-570 GEN
Solar/Wind Harmer
1.99
971485AH1-239 GEN
Solar/Wind Harmer
5.968
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25194408D.CRK1
Adder
7.827
945391AF1-204 GEN
Solar/Wind Harmer
7.253
24728905RICHG2
Adder
3.656
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.068
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.743
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.145
970883AG2-550 GEN
Solar/Wind Harmer
6.406
270599AE1-208 GEN
Solar/Wind Harmer
5.804
274764LEE CO EC;5U
Adder
8.405
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.263
274683WAUKEGAN ;8U
Adder
18.772
274683WAUKEGAN ;8U
Adder
15.824
274693ROCKY RD ;1P
Adder
9.818
958481AF2-142 GEN
Solar/Wind Harmer
9.318
274674JOLIET 9 ;6U
Adder
13.632
960971AF2-388 GEN
Solar/Wind Harmer
3.621
23585401KL_K28_T16
Solar/Wind Helper
1.157
946321AF1-296 GEN
Solar/Wind Harmer
3.554
959141AF2-205 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.763
945581AF1-223 GEN
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.485
971171AH1-044 GEN
Solar/Wind Harmer
12.516
971675AH1-338 GEN
Solar/Wind Harmer
2.437
971411AH1-196 GEN
Solar/Wind Harmer
9.369
970833AG2-524 GEN
Solar/Wind Harmer
6.809
970833AG2-524 GEN
Solar/Wind Harmer
4.54
274675JOLIET 29;7U
Adder
27.142
960591AF2-350 GEN
Solar/Wind Harmer
6.155
23652301WDPWR_K20
Solar/Wind Helper
0.127
243186AF1-051 GEN
50/50
11.683
24721805FLATG3
50/50
2.475
24723205RIVRG3
Adder
32.69
972203AH1-686 GEN
Adder
3.965
24735205WLF2G2
Adder
7.131
945681AF1-233 GEN
Solar/Wind Harmer
14.491
964901AG1-354 GEN
Solar/Wind Harmer
11.126
252516AE2-318_GEN
Solar/Wind Harmer
8.161
25194608D.CRK4
Adder
1.702
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.045
970155AG2-107 GEN
Solar/Wind Harmer
17.44
24728605AND G2
Adder
3.745
943811AF1-049 GEN
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.832
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
18.774
274828WAUKEGAN ;BP
Adder
9.84
274682WAUKEGAN ;7U
Adder
16.004
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.965
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
1.811
274676JOLIET 29;8U
Adder
9.572
238185AF2-356 C
Solar/Wind Helper
1.975
243186AF1-051 GEN
50/50
11.683
24721705FLATG2
50/50
36.759
24723005RIVRG1
Adder
32.69
24723105RIVRG2
Adder
32.69
971225AH1-072 GEN
Solar/Wind Harmer
1.885
971227AH1-073 GEN
Solar/Wind Harmer
1.885
270583AD2-179 GEN
Solar/Wind Harmer
7.872
971125AH1-004 GEN
Solar/Wind Harmer
3.042
971587AH1-292 GEN
Solar/Wind Harmer
5.311
276916AD2-100_GEN
Solar/Wind Harmer
13.944
970291AG2-192 GEN
Solar/Wind Harmer
0.844
970291AG2-192 GEN
Solar/Wind Harmer
0.389
971613AH1-306 GEN
Solar/Wind Harmer
3.113
253370AE2-315 SEC1
Adder
1.843
247621Y3-024
Adder
0.218
25322209TAIT E
Adder
8.794
25322209TAIT E
Adder
8.596
971341AH1-150 GEN
Solar/Wind Harmer
12.516
971343AH1-151 GEN
Solar/Wind Harmer
12.516
276901AD2-066 C O1
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.657
274822ROCKFORD ;11
Adder
17.613
959081AF2-199 GEN
Solar/Wind Harmer
6.258
971067AG2-660 GEN
Solar/Wind Harmer
2.086
971917AH1-482 GEN
Solar/Wind Harmer
8.135
276882AE2-255 GEN
Solar/Wind Harmer
0.729
274872LEEDK;1U
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.009
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
5.443
23750501ELLIOTTS
Solar/Wind Helper
0.598
NYPJM->LTFIMP_NY
CLTF
4.626
LGEELTFEXP_LGEE->PJM
CLTF
7.468
WECLTFEXP_WEC->PJM
CLTF
3.435
AG2-052LTFEXP_AG2-052->PJM
LTF
0.207
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
CPLELTFEXP_CPLE->PJM
CLTF
6.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.098
CBM West 1LTFEXP_CBM-W1->PJM
CBM
115.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.783
MECLTFEXP_MEC->PJM
CLTF
15.666
SIGELTFEXP_SIGE->PJM
CLTF
0.545
LAGNLTFEXP_LAGN->PJM
CLTF
19.698
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23
TVALTFEXP_TVA->PJM
CLTF
10.208

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5896.19
MW Contribution:
6.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
960911AF2-382 GEN
Solar/Wind Harmer
8.992
943031AE2-326 GEN
Solar/Wind Harmer
6.089
972103AH1-617 GEN
Solar/Wind Harmer
23.135
270030AE2-140 GEN
Solar/Wind Harmer
18.672
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
10.955
24728505AND G1
Adder
4.51
962771AG1-126 GEN
Solar/Wind Harmer
32.057
970153AG2-106 GEN
Solar/Wind Harmer
20.471
957381AF2-032 GEN
Solar/Wind Harmer
1.818
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.862
946031AF1-268 GEN
Solar/Wind Harmer
7.4
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
971087AG2-675 GEN
Solar/Wind Harmer
4.124
24318705GVG2
50/50
11.822
971191AH1-055 GEN
Solar/Wind Harmer
29.317
970879AG2-548 GEN
Solar/Wind Harmer
6.854
972273AH1-721 GEN
Adder
111.17
970093AG2-073 GEN
Solar/Wind Harmer
7.87
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
8.058
25196008MFTGT1
Adder
1.685
253394AE2-221_GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.122
3146802CHATHAM
Solar/Wind Harmer
0.115
942481AE2-261 GEN
Solar/Wind Harmer
24.006
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.664
970825AG2-519 GEN
Solar/Wind Harmer
5.878
970571AG2-364 GEN
Solar/Wind Harmer
15.299
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.443
274850MENDOTA H;RU
Solar/Wind Harmer
0.088
946671AF1-331 GEN
Solar/Wind Harmer
0.811
274729ELWOOD EC;1P
Adder
17.715
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
970879AG2-548 GEN
Solar/Wind Harmer
1.558
970107AG2-081 GEN
Solar/Wind Harmer
2.741
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
4.689
276838X2-022 GEN2
Solar/Wind Harmer
0.448
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.525
276645AC1-214 GEN1
Solar/Wind Harmer
0.302
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.239
274762LEE CO EC;3U
Adder
10.206
938861AE1-114 GEN
Solar/Wind Harmer
4.333
962691AG1-118 GEN
Solar/Wind Harmer
22.733
274696ROCKY RD ;4P
Adder
12.353
274697ROCKY RD ;3P
Adder
3.278
276897AD1-100 C
Solar/Wind Harmer
18.8
276893AG1-478 C
Solar/Wind Harmer
0.501
274888KELLY CRK;1U
Solar/Wind Harmer
0.437
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
970941AG2-585 GEN
Solar/Wind Harmer
2.017
971461AH1-227 GEN
Solar/Wind Harmer
5.939
270346AE1-212 GEN
Solar/Wind Harmer
10.045
958121AF2-106 GEN
Solar/Wind Harmer
0.001
3429391JKCT 9G
Adder
10.948
24686505CER G6
Adder
16.156
24728305BUCHG2
Adder
7.739
3429241JKCT 3G
Adder
15.659
962761AG1-125 GEN
Solar/Wind Harmer
32.057
965911AG1-460 GEN
Solar/Wind Harmer
1.606
270437AC2-090 C
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.823
270273AD2-016 GEN
Solar/Wind Harmer
0.795
276708O09 GEN2
Solar/Wind Harmer
0.271
274766LEE CO EC;7U
Adder
10.085
939401AE1-172 GEN
Solar/Wind Harmer
5.694
25326309TAIT D
Adder
1.195
962781AG1-127 GEN
Solar/Wind Harmer
7.216
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
942891AE2-308 GEN
Solar/Wind Harmer
9.244
972043AH1-570 GEN
Solar/Wind Harmer
2.384
971485AH1-239 GEN
Solar/Wind Harmer
7.296
964781AG1-341 GEN
Solar/Wind Harmer
9.518
25194408D.CRK1
Adder
9.34
945391AF1-204 GEN
Solar/Wind Harmer
8.741
942671AE2-283 GEN
Solar/Wind Harmer
3.812
24728905RICHG2
Adder
4.399
276615X2-022 GEN
Solar/Wind Harmer
0.083
926881AC1-175 GEN
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.897
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.602
970883AG2-550 GEN
Solar/Wind Harmer
7.744
270599AE1-208 GEN
Solar/Wind Harmer
7.027
274764LEE CO EC;5U
Adder
10.23
972235AH1-702 GEN1
Adder
2.754
276876AE1-163_GEN2
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274693ROCKY RD ;1P
Adder
11.949
958481AF2-142 GEN
Solar/Wind Harmer
11.337
274674JOLIET 9 ;6U
Adder
16.589
23585401KL_K28_T16
Solar/Wind Helper
1.275
238117U2-030
Solar/Wind Helper
0.29
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
270399AC1-101 GEN
Solar/Wind Harmer
4.065
966391AG1-508 GEN
Solar/Wind Harmer
1.796
971331AH1-145 GEN
Solar/Wind Harmer
15.307
24734705WLF1G3
Adder
9.154
24734905WLF1G5
Adder
9.154
971985AH1-537 GEN
Solar/Wind Harmer
3.035
971981AH1-535 GEN
Solar/Wind Harmer
6.584
270069AE2-166 C O1
Solar/Wind Harmer
8.709
972165AH1-665 GEN
Solar/Wind Harmer
8.194
339216AC1-074 GEN
Solar/Wind Harmer
0.242
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.618
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.702
946321AF1-296 GEN
Solar/Wind Harmer
4.325
247536S-71 GEN
Solar/Wind Harmer
0.307
971611AH1-305 GEN
Solar/Wind Harmer
4.575
972267AH1-718 GEN
Adder
4.579
959141AF2-205 GEN
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
21.28
971171AH1-044 GEN
Solar/Wind Harmer
15.232
945581AF1-223 GEN
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.966
971411AH1-196 GEN
Solar/Wind Harmer
11.402
970833AG2-524 GEN
Solar/Wind Harmer
8.285
970833AG2-524 GEN
Solar/Wind Harmer
5.523
274675JOLIET 29;7U
Adder
33.032
960591AF2-350 GEN
Solar/Wind Harmer
7.491
23750701CROSSCHOOL
Solar/Wind Helper
1.205
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
958171AF2-111 GEN
Solar/Wind Harmer
22.344
252507AC2-088 GEN
Solar/Wind Harmer
0.399
25196608WSDLE5
Adder
10.55
970193AG2-126 GEN
Solar/Wind Harmer
12.34
24728705AND G3
Adder
9.433
970781AG2-491 GEN
Solar/Wind Harmer
7.832
959611AF2-252 GEN
Solar/Wind Harmer
2.602
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
276868AE1-113 GEN
Solar/Wind Harmer
1.52
274879MINONK ;1U
Solar/Wind Harmer
0.317
274862TOP CROP ;2U
Solar/Wind Harmer
1.021
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
17.715
970707AG2-453 GEN
Solar/Wind Harmer
24.521
274887GEN-1.85
Solar/Wind Harmer
0.195
238127S14_GEN_2
Solar/Wind Helper
0.692
202652Y1-033 WT C
Solar/Wind Helper
0.538
20092526R32
Solar/Wind Helper
1.061
243186AF1-051 GEN
50/50
12.754
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24735205WLF2G2
Adder
8.97
945681AF1-233 GEN
Solar/Wind Harmer
17.283
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
964901AG1-354 GEN
Solar/Wind Harmer
13.534
252516AE2-318_GEN
Solar/Wind Harmer
9.728
25194608D.CRK4
Adder
2.03
3147123OTTER R
Solar/Wind Harmer
0.087
274767LEE CO EC;8U
Adder
10.085
959091AF2-200 GEN
Solar/Wind Harmer
15.232
274682WAUKEGAN ;7U
Adder
19.478
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.409
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
276806AD2-047 C O1
Solar/Wind Harmer
4.245
964991AG1-363 GEN
Solar/Wind Helper
3.731
238110AE1-109 GEN3
Solar/Wind Helper
0.089
235058AG1-386 C
Solar/Wind Helper
0.381
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
971225AH1-072 GEN
Solar/Wind Harmer
2.315
971227AH1-073 GEN
Solar/Wind Harmer
2.315
270583AD2-179 GEN
Solar/Wind Harmer
11.364
971125AH1-004 GEN
Solar/Wind Harmer
3.655
971587AH1-292 GEN
Solar/Wind Harmer
6.363
276916AD2-100_GEN
Solar/Wind Harmer
16.897
970291AG2-192 GEN
Solar/Wind Harmer
1.019
970291AG2-192 GEN
Solar/Wind Harmer
0.47
971613AH1-306 GEN
Solar/Wind Harmer
3.76
253370AE2-315 SEC1
Adder
2.225
247621Y3-024
Adder
0.264
971341AH1-150 GEN
Solar/Wind Harmer
15.232
971343AH1-151 GEN
Solar/Wind Harmer
15.232
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
276901AD2-066 C O1
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.799
316097T157 G90
Solar/Wind Helper
1.102
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.427
24728605AND G2
Adder
4.51
970155AG2-107 GEN
Solar/Wind Harmer
20.471
970613AG2-401 GEN
Solar/Wind Harmer
5.825
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
22.848
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
6.042
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
11.649
270055AF2-134 C O1
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
964201AG1-281 GEN
Solar/Wind Helper
0.442
24289405MTG1
50/50
11.78
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
18.148
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
3429421JKCT 10G
Adder
10.948
970653AG2-424 GEN
Solar/Wind Harmer
4.351
970149AG2-104 GEN
Solar/Wind Harmer
17.311
970773AG2-487 GEN
Solar/Wind Harmer
1.442
963741AG1-226 GEN
Solar/Wind Harmer
19.023
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.302
970819AG2-516 GEN
Solar/Wind Harmer
9.157
274822ROCKFORD ;11
Adder
21.436
959081AF2-199 GEN
Solar/Wind Harmer
7.616
971067AG2-660 GEN
Solar/Wind Harmer
2.539
276882AE2-255 GEN
Solar/Wind Harmer
0.887
971917AH1-482 GEN
Solar/Wind Harmer
9.865
274872LEEDK;1U
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.228
941551AE2-152 GEN
Solar/Wind Harmer
0
24289405MTG1
50/50
11.78
24686405CER G5
Adder
16.028
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970653AG2-424 GEN
Solar/Wind Harmer
0.902
941801AE2-185 GEN
Solar/Wind Harmer
4.901
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.692
965091AG1-374 GEN
Solar/Wind Harmer
23.422
965931AG1-462 GEN
Solar/Wind Harmer
19.72
274878BISHOP HL;2U
Solar/Wind Harmer
0.257
970191AG2-125 GEN
Solar/Wind Harmer
1.979
274760LEE CO EC;1U
Adder
10.206
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.242
23562501BACKB
Solar/Wind Helper
0.87
238108AE1-109 GEN1
Solar/Wind Helper
0.089
970913AG2-568 GEN
Solar/Wind Harmer
9.827
24728205BUCHG1
Adder
7.739
971277AH1-098 GEN
Solar/Wind Harmer
4.618
971073AG2-665 GEN
Solar/Wind Harmer
6.854
972045AH1-571 GEN
Solar/Wind Harmer
1.91
966021AG1-471 GEN
Solar/Wind Harmer
4.933
964571AG1-320 GEN
Solar/Wind Harmer
8.194
252509AD1-136 GEN
Solar/Wind Harmer
0.044
25183208HLCRTG
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.746
24728805RICHG1
Adder
4.399
276911AD2-131_GEN
Solar/Wind Harmer
1.113
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
970885AG2-551 GEN
Solar/Wind Harmer
2.581
270031AE2-169
Solar/Wind Harmer
4.216
964611AG1-324 GEN
Solar/Wind Harmer
0.575
274765LEE CO EC;6U
Adder
10.23
274763LEE CO EC;4U
Adder
10.109
270201AC2-176 GEN
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.395
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.378
274695ROCKY RD ;2P
Adder
12.068
958011AF2-095 GEN
Solar/Wind Harmer
10.787
235054AD2-180 GEN
Solar/Wind Helper
1.707
235531U2-073 GEN
Solar/Wind Helper
2.776
203961AE2-224 GEN
Solar/Wind Helper
2.204
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
28.948
270400AC1-102 GEN
Solar/Wind Harmer
4.065
941621AE2-160 GEN
Adder
5.641
971329AH1-144 GEN
Solar/Wind Harmer
5.625
24734805WLF1G4
Adder
9.154
24735105WLF2G1
Adder
8.97
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
10.231
25196508WSDLE4
Adder
10.442
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.825
270356AE2-297 GEN
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.756
963841AG1-237 GEN
Solar/Wind Harmer
3.459
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
2.987
926823AC1-168 GEN
Solar/Wind Harmer
1.302
274746AC1-111 G10
Adder
6.042
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
23750501ELLIOTTS
Solar/Wind Helper
0.639
238118U2-030_1
Solar/Wind Helper
0.29
20089126CSLMN_L13
Solar/Wind Helper
0.558
20088926STNY CRK
Solar/Wind Helper
0.752
24318705GVG2
50/50
11.822
971687AH1-348 GEN
Solar/Wind Harmer
1.157
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252510AF1-249 C
Solar/Wind Harmer
0.065
253398AE2-221_GEN2
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.031
276621W2-048 GEN
Solar/Wind Harmer
0.398
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
8.772
270032AE2-172
Solar/Wind Harmer
5.222
270005AE1-210 C O1
Solar/Wind Harmer
1.692
970825AG2-519 GEN
Solar/Wind Harmer
2.77
939741AE1-205 GEN
Solar/Wind Harmer
10.877
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.607
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.206
970569AG2-363 GEN
Solar/Wind Harmer
22.948
945371AF1-202 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.993
964861AG1-349 GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
3.264
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
970281AG2-184 GEN
Solar/Wind Harmer
24.292
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270197AD1-017 GEN1
Solar/Wind Harmer
1.008
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
970289AG2-191 GEN
Solar/Wind Harmer
1.489
959341AF2-225 GEN
Solar/Wind Harmer
8.158
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
274877BISHOP HL;1U
Solar/Wind Harmer
0.257
970169AG2-114 GEN
Solar/Wind Harmer
7.684
276741O09 GEN1
Solar/Wind Harmer
0.271
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
6.042
274735ELWOOD EC;4P
Adder
17.715
971313AH1-133 GEN
Solar/Wind Harmer
5.869
971061AG2-657 GEN
Solar/Wind Harmer
6.84
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.421
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
12.311
274856ECOGROVE ;U1
Solar/Wind Harmer
0.178
276861AD2-134 GEN
Solar/Wind Harmer
0.136
276863AD2-134 GEN
Solar/Wind Harmer
0.136
970073AG2-061 GEN
Solar/Wind Harmer
2.528
274728ELWOOD EC;5P
Adder
17.715
20089226LOOKOUT
Solar/Wind Helper
0.556
203940AF1-140 C
Solar/Wind Helper
0.362
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.25 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2283.58
MW Contribution:
2.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729205KEY G1
50/50
0.366
247620Y3-023
50/50
0.467
944541AF1-119 GEN
Solar/Wind Harmer
0.427
270031AE2-169
Solar/Wind Harmer
3.104
965791AG1-447 GEN
Solar/Wind Harmer
5.106
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.41
958011AF2-095 GEN
Solar/Wind Harmer
7.498
274695ROCKY RD ;2P
Adder
8.016
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
7.476
276872AE1-163_GEN1
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.526
274765LEE CO EC;6U
Adder
6.396
274763LEE CO EC;4U
Adder
6.321
24727205RPMNG3
50/50
3.298
963791AG1-232 GEN
Solar/Wind Harmer
12.035
247521TR3_G114
Solar/Wind Harmer
0.261
274827FISK ;RP
Adder
5.808
274800UNIV PARK;3U
Adder
4.357
274801UNIV PARK;4U
Adder
4.357
972227AH1-698 GEN1
Adder
1.941
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.974
274744AC1-111 GEN8
Adder
4.068
970169AG2-114 GEN
Solar/Wind Harmer
4.823
276741O09 GEN1
Solar/Wind Harmer
0.167
274877BISHOP HL;1U
Solar/Wind Harmer
0.157
959341AF2-225 GEN
Solar/Wind Harmer
4.889
276668AB2-070 GEN1
Solar/Wind Harmer
0.17
276848AB2-070 GEN3
Solar/Wind Harmer
0.169
276849AB2-070 GEN2
Solar/Wind Harmer
0.17
970521AG2-332 GEN
50/50
10.906
24639705ELKHART HY
50/50
0.151
270143AC1-141 CT2_
50/50
2.029
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.876
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
3.792
270055AF2-134 C O1
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.662
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
12.933
274828WAUKEGAN ;BP
Adder
7.939
957471AF2-041 GEN
Solar/Wind Harmer
14.651
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.287
24728605AND G2
Adder
2.099
24641605TWIN BRNCH
50/50
0.015
970031AG2-029 GEN
Solar/Wind Harmer
4.587
965051AG1-369 GEN
Solar/Wind Harmer
3.602
945581AF1-223 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
6.365
274777LINCOLN ;8U
Adder
6.365
972037AH1-567 GEN1
Adder
0.137
960591AF2-350 GEN
Solar/Wind Harmer
5.207
972228AH1-698 GEN2
Adder
2.756
274675JOLIET 29;7U
Adder
22.662
274675JOLIET 29;7U
Adder
21.853
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
5.628
970833AG2-524 GEN
Solar/Wind Harmer
3.752
971611AH1-305 GEN
Solar/Wind Harmer
3.031
247536S-71 GEN
Solar/Wind Harmer
0.199
971411AH1-196 GEN
Solar/Wind Harmer
7.376
971675AH1-338 GEN
Solar/Wind Harmer
1.916
971171AH1-044 GEN
Solar/Wind Harmer
9.768
274823ROCKFORD ;21
Adder
13.596
972267AH1-718 GEN
Adder
2.828
24386405FR-21G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
2.577
24729405KEY G3
50/50
0.374
24729305KEY G2
50/50
0.367
960851AF2-376 GEN
50/50
2.095
942221AE2-234 GEN
Solar/Wind Harmer
2.855
274805UNIV PK N;1U
Adder
3.801
274770LINCOLN ;1U
Adder
6.365
274771LINCOLN ;2U
Adder
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
0.304
970941AG2-585 GEN
Solar/Wind Harmer
2.864
276897AD1-100 C
Solar/Wind Harmer
12.887
276893AG1-478 C
Solar/Wind Harmer
0.343
274697ROCKY RD ;3P
Adder
2.178
274696ROCKY RD ;4P
Adder
8.205
957841AF2-078 GEN
Solar/Wind Harmer
0
270144AC1-141 ST1_
50/50
1.792
959331AF2-224 GEN
Solar/Wind Harmer
9.676
965041AG1-368 GEN
Solar/Wind Harmer
8.443
270526AF1-158 GEN
Solar/Wind Harmer
0
24727105RPMNG2
50/50
3.318
270142AC1-141 CT1_
50/50
2.029
24695305TIMB G C
Solar/Wind Harmer
0.532
274811UNIV PK N;7U
Adder
3.792
276806AD2-047 C O1
Solar/Wind Harmer
2.951
247642Z2-115 C
Solar/Wind Harmer
0.002
274676JOLIET 29;8U
Adder
21.852
274734ELWOOD EC;8P
Adder
12.11
274736ELWOOD EC;9P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.564
946031AF1-268 GEN
Solar/Wind Harmer
4.838
943121AE2-341 GEN
Solar/Wind Harmer
8.518
943591AF1-030 GEN
Solar/Wind Harmer
5.665
274682WAUKEGAN ;7U
Adder
12.933
959091AF2-200 GEN
Solar/Wind Harmer
9.768
274767LEE CO EC;8U
Adder
6.306
971087AG2-675 GEN
Solar/Wind Harmer
2.44
957381AF2-032 GEN
Solar/Wind Harmer
0.932
24728505AND G1
Adder
2.099
270284AF1-227 GEN1
Solar/Wind Helper
1.893
276820AF1-078_GEN
Solar/Wind Helper
0.334
270246TR4_N_V150
Solar/Wind Harmer
0.046
965681AG1-436 GEN
Solar/Wind Harmer
6.963
247621Y3-024
Adder
0.183
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.555
970291AG2-192 GEN
Solar/Wind Harmer
0.666
970291AG2-192 GEN
Solar/Wind Harmer
0.308
971613AH1-306 GEN
Solar/Wind Harmer
2.442
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.768
971343AH1-151 GEN
Solar/Wind Harmer
9.768
276916AD2-100_GEN
Solar/Wind Harmer
8.532
971587AH1-292 GEN
Solar/Wind Harmer
2.468
270349AD2-093_GEN
Solar/Wind Helper
0.857
270471AD2-092_GEN
Solar/Wind Helper
0.857
24729505KEY G4
50/50
6.847
24653605MOTTVILLE
50/50
0.004
270071AF1-092 GEN
Solar/Wind Harmer
14.566
971771AH1-392 GEN
Solar/Wind Harmer
5.907
274728ELWOOD EC;5P
Adder
12.11
970073AG2-061 GEN
Solar/Wind Harmer
1.661
276861AD2-134 GEN
Solar/Wind Harmer
0.088
276863AD2-134 GEN
Solar/Wind Harmer
0.088
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
971681AH1-341 GEN
Solar/Wind Harmer
7.736
971549AH1-272 GEN
Solar/Wind Harmer
9.898
270543AE2-219 C
Solar/Wind Harmer
3.137
270007AE1-245 C
Solar/Wind Harmer
0
944961AF1-161 GEN
50/50
2.395
965021AG1-366 GEN
Solar/Wind Harmer
4.607
270043AE2-236 GEN
Solar/Wind Harmer
5.241
945111AF1-176 GEN
Solar/Wind Harmer
4.853
270505AE1-170 C O1
Solar/Wind Harmer
6.132
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.345
274724RIVER EC ;11
Adder
13.515
274772LINCOLN ;3U
Adder
6.365
972259AH1-714 GEN
Adder
14.153
274729ELWOOD EC;1P
Adder
12.11
970825AG2-519 GEN
Solar/Wind Harmer
3.795
946671AF1-331 GEN
Solar/Wind Harmer
0.524
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
970571AG2-364 GEN
Solar/Wind Harmer
9.675
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.998
942481AE2-261 GEN
Solar/Wind Harmer
12.255
246938BC-WTG3
Solar/Wind Helper
11.083
960861AF2-377 GEN
50/50
2.406
965011AG1-365 GEN
Solar/Wind Harmer
13.822
958861AF2-177 GEN
Solar/Wind Harmer
2.694
945111AF1-176 GEN
Solar/Wind Harmer
10.683
957891AF2-083 GEN
Solar/Wind Harmer
9.802
945371AF1-202 GEN
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
6.312
274723RIVER EC ;12
Adder
13.681
274773LINCOLN ;4U
Adder
6.365
274774LINCOLN ;5U
Adder
6.365
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.364
270594AE1-207 GEN
Solar/Wind Harmer
5.699
270032AE2-172
Solar/Wind Harmer
3.392
270005AE1-210 C O1
Solar/Wind Harmer
1.101
970825AG2-519 GEN
Solar/Wind Harmer
1.788
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
2.59
970569AG2-363 GEN
Solar/Wind Harmer
14.512
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.381
24386605FR-22G C
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.519
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.213
246936BC-WTG1
Solar/Wind Helper
10.897
270485AE1-090_GEN
Solar/Wind Helper
0.326
960841AF2-375 GEN
Solar/Wind Helper
1.179
962691AG1-118 GEN
Solar/Wind Harmer
14.951
938861AE1-114 GEN
Solar/Wind Harmer
2.722
274762LEE CO EC;3U
Adder
6.381
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.763
276645AC1-214 GEN1
Solar/Wind Harmer
0.185
24387305FR-4G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
1.513
970241AG2-163 GEN
Solar/Wind Harmer
2.581
276838X2-022 GEN2
Solar/Wind Harmer
0.239
970623AG2-406 GEN
Solar/Wind Harmer
0.656
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.897
247522W1-056 GEN
Solar/Wind Helper
1.177
253378AE2-206_GEN
Solar/Wind Helper
0.715
24727005RPMNG1
50/50
3.317
943021AE2-325 GEN
Solar/Wind Harmer
3
970373AG2-245 GEN
Solar/Wind Harmer
11.243
971917AH1-482 GEN
Solar/Wind Harmer
6.75
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.82
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.578
959081AF2-199 GEN
Solar/Wind Harmer
4.884
971067AG2-660 GEN
Solar/Wind Harmer
1.628
274822ROCKFORD ;11
Adder
13.696
970819AG2-516 GEN
Solar/Wind Harmer
5.809
276646AC1-214 GEN2
Solar/Wind Harmer
0.185
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
10.473
970773AG2-487 GEN
Solar/Wind Harmer
0.63
270578AF1-285 GEN2
Solar/Wind Helper
0.593
270286AF1-227 GEN2
Solar/Wind Helper
0.694
24699105WLD G1 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.494
270383AD1-128 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
0.562
241960AC2-195 GEN
Solar/Wind Helper
0.697
971609AH1-304 GEN
Solar/Wind Harmer
0.922
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.13
274776LINCOLN ;7U
Adder
6.365
274687WILL CNTY;4U
Adder
20.685
274687WILL CNTY;4U
Adder
20.685
274731ELWOOD EC;2P
Adder
12.11
274733ELWOOD EC;3P
Adder
12.11
274746AC1-111 G10
Adder
4.068
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.821
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.976
944221AF1-090 GEN
Solar/Wind Harmer
2.312
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
0.876
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
1.968
970583AG2-370 GEN
50/50
2.814
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.981
971347AH1-153 GEN
Solar/Wind Harmer
2.927
274752CRETE EC ;2U
Adder
6.312
274826FISK ;BP
Adder
8.195
274887GEN-1.85
Solar/Wind Harmer
0.135
970707AG2-453 GEN
Solar/Wind Harmer
16.903
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
12.11
274862TOP CROP ;2U
Solar/Wind Harmer
0.681
276868AE1-113 GEN
Solar/Wind Harmer
0.991
274879MINONK ;1U
Solar/Wind Harmer
0.207
274855GSG-6 ;RU
Solar/Wind Harmer
0.179
970781AG2-491 GEN
Solar/Wind Harmer
4.895
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
1.525
970193AG2-126 GEN
Solar/Wind Harmer
5.956
24728705AND G3
Adder
4.39
942871AE2-306 GEN
Solar/Wind Helper
0.445
270287AF1-227 GEN3
Solar/Wind Helper
0.694
24643105BUCHANAN
50/50
0.01
270247TR4_N_V136
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
16.139
960971AF2-388 GEN
Solar/Wind Harmer
3.752
970349AG2-230 GEN
Solar/Wind Harmer
8.78
961051AF2-396 GEN
Solar/Wind Harmer
11.674
961051AF2-396 GEN
Solar/Wind Harmer
7.782
270599AE1-208 GEN
Solar/Wind Harmer
5.173
274808UNIV PK N;4U
Adder
3.776
274674JOLIET 9 ;6U
Adder
11.348
958481AF2-142 GEN
Solar/Wind Harmer
7.57
274693ROCKY RD ;1P
Adder
7.937
274683WAUKEGAN ;8U
Adder
15.145
274683WAUKEGAN ;8U
Adder
12.766
276876AE1-163_GEN2
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.755
274764LEE CO EC;5U
Adder
6.396
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.533
960611AF2-352 GEN
Solar/Wind Harmer
1.525
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.481
276615X2-022 GEN
Solar/Wind Harmer
0.044
945391AF1-204 GEN
Solar/Wind Harmer
4.219
270462AD2-086
Solar/Wind Helper
3.747
971029AG2-637 GEN
Solar/Wind Harmer
5.928
270224U2-072_GEN2
Solar/Wind Helper
0.876
945641AF1-229 GEN
Solar/Wind Helper
0.94
270541AE2-072 C
Solar/Wind Helper
0.943
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.609
270227U2-072_GEN3
Solar/Wind Helper
0.876
270228U2-072_GEN4
Solar/Wind Helper
0.876
270231U2-072_GEN5
Solar/Wind Helper
0.876
24642205MAYFLWER
50/50
0.031
962601AG1-109 GEN
50/50
2.395
274753CRETE EC ;3U
Adder
6.312
274814UNIV PK N;0U
Adder
3.826
274807UNIV PK N;3U
Adder
3.817
274803UNIV PARK;6U
Adder
4.369
972038AH1-567 GEN2
Adder
0.273
276843GEN-1.7
Solar/Wind Harmer
0.168
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.101
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.381
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.157
965091AG1-374 GEN
Solar/Wind Harmer
13.726
965931AG1-462 GEN
Solar/Wind Harmer
11.666
24379505HDWTR1G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
6.312
274802UNIV PARK;5U
Adder
4.369
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
11.348
274732ELWOOD EC;7P
Adder
12.11
962781AG1-127 GEN
Solar/Wind Harmer
4.731
939401AE1-172 GEN
Solar/Wind Harmer
3.718
276903AD2-071 C
Solar/Wind Harmer
5.426
274766LEE CO EC;7U
Adder
6.306
276708O09 GEN2
Solar/Wind Harmer
0.167
24385905FR-11G C
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.82
270317AD1-130_GEN
Solar/Wind Helper
4.143
270391AF1-285 GEN3
Solar/Wind Helper
0.593
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
NYPJM->LTFIMP_NY
CLTF
1.264
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
AG2-052LTFEXP_AG2-052->PJM
LTF
0.172
AH1-155LTFEXP_AH1-155->PJM
LTF
0.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.835
CBM West 1LTFEXP_CBM-W1->PJM
CBM
70.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.933
MECLTFEXP_MEC->PJM
CLTF
9.784
SIGELTFEXP_SIGE->PJM
CLTF
0.201
LAGNLTFEXP_LAGN->PJM
CLTF
5.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.51
TVALTFEXP_TVA->PJM
CLTF
2.319

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.01 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3190.2
MW Contribution:
3.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24641605TWIN BRNCH
50/50
0.023
970031AG2-029 GEN
Solar/Wind Harmer
6.248
945581AF1-223 GEN
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
5.063
247536S-71 GEN
Solar/Wind Harmer
0.341
972037AH1-567 GEN1
Adder
0.202
959141AF2-205 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
9.292
274777LINCOLN ;8U
Adder
9.292
960591AF2-350 GEN
Solar/Wind Harmer
7.658
972228AH1-698 GEN2
Adder
4.051
24727105RPMNG2
50/50
1.309
270142AC1-141 CT1_
50/50
3.096
24695305TIMB G C
Solar/Wind Harmer
0.832
946031AF1-268 GEN
Solar/Wind Harmer
8.826
970289AG2-191 GEN
Solar/Wind Harmer
0.975
247642Z2-115 C
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
5.593
276806AD2-047 C O1
Solar/Wind Harmer
4.34
274676JOLIET 29;8U
Adder
32.122
274734ELWOOD EC;8P
Adder
17.809
274736ELWOOD EC;9P
Adder
17.809
943121AE2-341 GEN
Solar/Wind Harmer
12.495
943591AF1-030 GEN
Solar/Wind Harmer
8.309
274682WAUKEGAN ;7U
Adder
19.011
959091AF2-200 GEN
Solar/Wind Harmer
14.375
274767LEE CO EC;8U
Adder
9.292
24728505AND G1
Adder
3.747
971087AG2-675 GEN
Solar/Wind Harmer
3.606
957381AF2-032 GEN
Solar/Wind Harmer
1.409
23906402RICHG1
Adder
0.876
23906502RICHG2&3
Adder
0.869
270284AF1-227 GEN1
Solar/Wind Helper
1.175
247621Y3-024
50/50
0.324
270246TR4_N_V150
Solar/Wind Harmer
0.065
971613AH1-306 GEN
Solar/Wind Harmer
4.3
970291AG2-192 GEN
Solar/Wind Harmer
1.152
970291AG2-192 GEN
Solar/Wind Harmer
0.532
965681AG1-436 GEN
Solar/Wind Harmer
10.47
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.817
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.375
971343AH1-151 GEN
Solar/Wind Harmer
14.375
276916AD2-100_GEN
Solar/Wind Harmer
12.922
971587AH1-292 GEN
Solar/Wind Harmer
3.867
270349AD2-093_GEN
Solar/Wind Helper
1.081
270471AD2-092_GEN
Solar/Wind Helper
1.081
24642205MAYFLWER
50/50
0.047
962601AG1-109 GEN
50/50
3.701
270004AE1-209 GEN
Solar/Wind Harmer
2.117
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
1.078
274753CRETE EC ;3U
Adder
9.326
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.641
274807UNIV PK N;3U
Adder
5.629
274803UNIV PARK;6U
Adder
6.433
972038AH1-567 GEN2
Adder
0.401
276843GEN-1.7
Solar/Wind Harmer
0.248
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.403
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
965091AG1-374 GEN
Solar/Wind Harmer
20.486
965931AG1-462 GEN
Solar/Wind Harmer
17.242
958321AF2-126 GEN
Solar/Wind Harmer
0.443
24729205KEY G1
50/50
0.718
247620Y3-023
50/50
0.69
944541AF1-119 GEN
Solar/Wind Harmer
0.834
270031AE2-169
Solar/Wind Harmer
5.613
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.696
24699105WLD G1 C
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
7.678
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.649
958011AF2-095 GEN
Solar/Wind Harmer
11.028
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
11.777
958491AF2-143 GEN
Solar/Wind Harmer
11.026
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.246
274765LEE CO EC;6U
Adder
9.425
274763LEE CO EC;4U
Adder
9.314
276911AD2-131_GEN
Solar/Wind Harmer
0.851
24728805RICHG1
Adder
3.1
964571AG1-320 GEN
Solar/Wind Harmer
2.864
946101AF1-275 GEN
Solar/Wind Helper
0.301
24729405KEY G3
50/50
0.734
24729305KEY G2
50/50
0.721
960851AF2-376 GEN
50/50
3.277
942221AE2-234 GEN
Solar/Wind Harmer
4.522
970623AG2-406 GEN
Solar/Wind Harmer
1.54
246937BC-WTG2
Solar/Wind Harmer
0.334
247607V1-011 GEN
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.605
274770LINCOLN ;1U
Adder
9.292
274771LINCOLN ;2U
Adder
9.292
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
970941AG2-585 GEN
Solar/Wind Harmer
4.212
276897AD1-100 C
Solar/Wind Harmer
18.934
276893AG1-478 C
Solar/Wind Harmer
0.504
970521AG2-332 GEN
50/50
16.165
24639705ELKHART HY
50/50
0.225
270143AC1-141 CT2_
50/50
3.096
965651AG1-433 GEN
Solar/Wind Harmer
3.666
270024AE2-089 GEN
Solar/Wind Harmer
0.002
270449AD2-020 GEN
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.415
965421AG1-410 GEN
Solar/Wind Harmer
26.149
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.593
274676JOLIET 29;8U
Adder
33.312
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.972
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
19.011
274828WAUKEGAN ;BP
Adder
11.67
957471AF2-041 GEN
Solar/Wind Harmer
21.562
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
3.747
23906502RICHG2&3
Adder
0.869
960861AF2-377 GEN
50/50
3.382
965011AG1-365 GEN
Solar/Wind Harmer
12.741
958861AF2-177 GEN
Solar/Wind Harmer
5.255
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
2.117
970825AG2-519 GEN
Solar/Wind Harmer
3.304
945111AF1-176 GEN
Solar/Wind Harmer
16.279
957891AF2-083 GEN
Solar/Wind Harmer
15.012
270594AE1-207 GEN
Solar/Wind Harmer
10.034
270032AE2-172
Solar/Wind Harmer
5.973
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.334
270489AE1-102 GEN1
Solar/Wind Harmer
1.078
274751CRETE EC ;1U
Adder
9.326
274723RIVER EC ;12
Adder
20.174
964861AG1-349 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
9.292
274774LINCOLN ;5U
Adder
9.292
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.53
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.817
970569AG2-363 GEN
Solar/Wind Harmer
21.445
24386605FR-22G C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.403
939741AE1-205 GEN
Solar/Wind Harmer
9.71
276621W2-048 GEN
Solar/Wind Harmer
0.32
970583AG2-370 GEN
50/50
3.653
944531AF1-118 GEN
Solar/Wind Harmer
62.885
270063AE2-323 C
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
4.396
274752CRETE EC ;2U
Adder
9.326
274826FISK ;BP
Adder
12.06
274887GEN-1.85
Solar/Wind Harmer
0.199
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
24.739
274730ELWOOD EC;6P
Adder
17.809
274862TOP CROP ;2U
Solar/Wind Harmer
1.004
970781AG2-491 GEN
Solar/Wind Harmer
7.342
276868AE1-113 GEN
Solar/Wind Harmer
1.461
274879MINONK ;1U
Solar/Wind Harmer
0.305
274855GSG-6 ;RU
Solar/Wind Harmer
0.264
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.276
24728705AND G3
Adder
7.836
970193AG2-126 GEN
Solar/Wind Harmer
9.362
270541AE2-072 C
Solar/Wind Harmer
0
270287AF1-227 GEN3
Solar/Wind Helper
0.431
24643105BUCHANAN
50/50
0.016
960971AF2-388 GEN
Solar/Wind Harmer
7.331
944231AF1-091 GEN
Solar/Wind Harmer
24.786
270599AE1-208 GEN
Solar/Wind Harmer
9.355
270247TR4_N_V136
Solar/Wind Harmer
0.065
961051AF2-396 GEN
Solar/Wind Harmer
17.945
961051AF2-396 GEN
Solar/Wind Harmer
11.963
970349AG2-230 GEN
Solar/Wind Harmer
13.187
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.947
274808UNIV PK N;4U
Adder
5.568
274674JOLIET 9 ;6U
Adder
16.683
958481AF2-142 GEN
Solar/Wind Harmer
11.155
274693ROCKY RD ;1P
Adder
11.662
274683WAUKEGAN ;8U
Adder
22.263
274683WAUKEGAN ;8U
Adder
18.767
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.583
966841AG1-555 GEN
Solar/Wind Harmer
0.805
274764LEE CO EC;5U
Adder
9.425
960611AF2-352 GEN
Solar/Wind Harmer
2.276
276615X2-022 GEN
Solar/Wind Harmer
0.066
945391AF1-204 GEN
Solar/Wind Harmer
6.631
24728905RICHG2
Adder
3.1
270054AF2-122 C O1
Solar/Wind Helper
0.78
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.536
24727205RPMNG3
50/50
1.301
963791AG1-232 GEN
Solar/Wind Harmer
15.281
247521TR3_G114
Solar/Wind Harmer
0.367
970289AG2-191 GEN
Solar/Wind Harmer
1.684
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
8.547
274800UNIV PARK;3U
Adder
6.411
274801UNIV PARK;4U
Adder
6.411
972227AH1-698 GEN1
Adder
2.852
274735ELWOOD EC;4P
Adder
17.808
274744AC1-111 GEN8
Adder
5.972
970169AG2-114 GEN
Solar/Wind Harmer
7.144
276741O09 GEN1
Solar/Wind Harmer
0.247
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
959341AF2-225 GEN
Solar/Wind Harmer
7.282
276668AB2-070 GEN1
Solar/Wind Harmer
0.256
276848AB2-070 GEN3
Solar/Wind Harmer
0.255
276849AB2-070 GEN2
Solar/Wind Harmer
0.256
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
9.326
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274802UNIV PARK;5U
Adder
6.433
274674JOLIET 9 ;6U
Adder
16.683
274732ELWOOD EC;7P
Adder
17.809
939401AE1-172 GEN
Solar/Wind Harmer
5.485
962781AG1-127 GEN
Solar/Wind Harmer
6.953
24385905FR-11G C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
9.292
276708O09 GEN2
Solar/Wind Harmer
0.247
965911AG1-460 GEN
Solar/Wind Harmer
1.24
241858AF1-205_GEN
Solar/Wind Harmer
1.344
270520AE2-214 GEN
Solar/Wind Helper
1.202
24729505KEY G4
50/50
13.443
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
25.488
971771AH1-392 GEN
Solar/Wind Harmer
8.998
270435AC2-044 GEN
Solar/Wind Harmer
1.05
971549AH1-272 GEN
Solar/Wind Harmer
17.043
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.563
274728ELWOOD EC;5P
Adder
17.809
970073AG2-061 GEN
Solar/Wind Harmer
2.45
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.129
276863AD2-134 GEN
Solar/Wind Harmer
0.129
274856ECOGROVE ;U1
Solar/Wind Harmer
0.166
971681AH1-341 GEN
Solar/Wind Harmer
11.398
944961AF1-161 GEN
50/50
3.701
270043AE2-236 GEN
Solar/Wind Harmer
8.814
965021AG1-366 GEN
Solar/Wind Harmer
4.247
970825AG2-519 GEN
Solar/Wind Harmer
7.011
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.926
945111AF1-176 GEN
Solar/Wind Harmer
7.395
270505AE1-170 C O1
Solar/Wind Harmer
9.418
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.299
274724RIVER EC ;11
Adder
19.931
274772LINCOLN ;3U
Adder
9.292
972259AH1-714 GEN
Adder
20.761
274729ELWOOD EC;1P
Adder
17.808
946671AF1-331 GEN
Solar/Wind Harmer
0.771
274850MENDOTA H;RU
Solar/Wind Harmer
0.084
970571AG2-364 GEN
Solar/Wind Harmer
14.297
971993AH1-541 GEN
Solar/Wind Harmer
3.006
942481AE2-261 GEN
Solar/Wind Harmer
18.539
270144AC1-141 ST1_
50/50
2.734
959331AF2-224 GEN
Solar/Wind Harmer
8.919
965041AG1-368 GEN
Solar/Wind Harmer
10.96
971609AH1-304 GEN
Solar/Wind Harmer
1.667
964611AG1-324 GEN
Solar/Wind Harmer
3.62
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
9.292
274687WILL CNTY;4U
Adder
30.416
274687WILL CNTY;4U
Adder
30.416
274731ELWOOD EC;2P
Adder
17.808
274733ELWOOD EC;3P
Adder
17.808
274746AC1-111 G10
Adder
5.972
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
926823AC1-168 GEN
Solar/Wind Harmer
1.213
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.005
274854TWINGROVE;U2
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.516
945411AF1-206 GEN
Solar/Wind Harmer
0
24727005RPMNG1
50/50
1.308
943021AE2-325 GEN
Solar/Wind Harmer
4.637
970373AG2-245 GEN
Solar/Wind Harmer
16.897
971917AH1-482 GEN
Solar/Wind Harmer
10.122
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.208
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.852
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
7.187
971067AG2-660 GEN
Solar/Wind Harmer
2.396
274822ROCKFORD ;11
Adder
20.159
970819AG2-516 GEN
Solar/Wind Harmer
8.554
276646AC1-214 GEN2
Solar/Wind Harmer
0.274
276655WTG1_EQ
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
1.202
963741AG1-226 GEN
Solar/Wind Harmer
16.041
970091AG2-072 GEN
Adder
47.294
23920202STRYCT
Adder
0.781
270286AF1-227 GEN2
Solar/Wind Helper
0.431
971611AH1-305 GEN
Solar/Wind Harmer
4.539
274675JOLIET 29;7U
Adder
33.312
274675JOLIET 29;7U
Adder
32.122
970833AG2-524 GEN
Solar/Wind Harmer
8.267
970833AG2-524 GEN
Solar/Wind Harmer
5.511
971029AG2-637 GEN
Solar/Wind Harmer
10.958
971411AH1-196 GEN
Solar/Wind Harmer
10.852
971675AH1-338 GEN
Solar/Wind Harmer
2.819
971171AH1-044 GEN
Solar/Wind Harmer
14.375
274823ROCKFORD ;21
Adder
20.012
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.17
946321AF1-296 GEN
Solar/Wind Harmer
3.807
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
12.055
274697ROCKY RD ;3P
Adder
3.199
962691AG1-118 GEN
Solar/Wind Harmer
21.97
24387305FR-4G C
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
4.01
274762LEE CO EC;3U
Adder
9.403
276645AC1-214 GEN1
Solar/Wind Harmer
0.274
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.126
942111AE2-223 GEN
Solar/Wind Harmer
2.254
970241AG2-163 GEN
Solar/Wind Harmer
3.954
276838X2-022 GEN2
Solar/Wind Harmer
0.361
970621AG2-405 GEN
Solar/Wind Harmer
1.034
990792J1392
External Queue
6.545727729797363
990497J1323
External Queue
1.9028279781341553
991297J1743
External Queue
13.235071182250977
NYPJM->LTFIMP_NY
CLTF
1.989
LGEELTFEXP_LGEE->PJM
CLTF
3.263
WECLTFEXP_WEC->PJM
CLTF
3.91
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.688
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.333
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.471
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.335
LAGNLTFEXP_LAGN->PJM
CLTF
8.402
TVALTFEXP_TVA->PJM
CLTF
3.331

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.53 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5607.44
MW Contribution:
7.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.013
274811UNIV PK N;7U
Adder
10.053
276806AD2-047 C O1
Solar/Wind Harmer
7.895
274676JOLIET 29;8U
Adder
58.599
274734ELWOOD EC;8P
Adder
32.486
274736ELWOOD EC;9P
Adder
32.486
943121AE2-341 GEN
Solar/Wind Harmer
22.986
943591AF1-030 GEN
Solar/Wind Harmer
15.286
274682WAUKEGAN ;7U
Adder
34.771
959091AF2-200 GEN
Solar/Wind Harmer
26.289
274767LEE CO EC;8U
Adder
16.958
971087AG2-675 GEN
Solar/Wind Harmer
6.556
247642Z2-115 C
Solar/Wind Harmer
0.005
970289AG2-191 GEN
Solar/Wind Harmer
1.271
957381AF2-032 GEN
Solar/Wind Harmer
2.525
946031AF1-268 GEN
Solar/Wind Harmer
9.859
24695305TIMB G C
Solar/Wind Harmer
0.837
24728505AND G1
Adder
5.117
965681AG1-436 GEN
Solar/Wind Harmer
18.242
276776AD2-060 GEN
Solar/Wind Harmer
1.486
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
26.289
971343AH1-151 GEN
Solar/Wind Harmer
26.289
970291AG2-192 GEN
Solar/Wind Harmer
1.502
970291AG2-192 GEN
Solar/Wind Harmer
0.693
971613AH1-306 GEN
Solar/Wind Harmer
5.417
276916AD2-100_GEN
Solar/Wind Harmer
23.132
270246TR4_N_V150
Solar/Wind Harmer
0.065
971587AH1-292 GEN
Solar/Wind Harmer
7.235
247621Y3-024
Adder
0.338
270349AD2-093_GEN
Solar/Wind Helper
1.553
270471AD2-092_GEN
Solar/Wind Helper
1.553
24642205MAYFLWER
50/50
0.076
962601AG1-109 GEN
50/50
5.942
274753CRETE EC ;3U
Adder
16.621
274814UNIV PK N;0U
Adder
10.141
274807UNIV PK N;3U
Adder
10.119
274803UNIV PARK;6U
Adder
11.65
276843GEN-1.7
Solar/Wind Harmer
0.45
972038AH1-567 GEN2
Adder
0.728
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
17.161
24690905MDL-1G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.422
24386205FR-12G C
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
37.086
965931AG1-462 GEN
Solar/Wind Harmer
31.345
270004AE1-209 GEN
Solar/Wind Harmer
2.315
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
1.048
270101X2-052 CT2
50/50
3.107
247620Y3-023
50/50
0.993
965791AG1-447 GEN
Solar/Wind Harmer
13.377
958011AF2-095 GEN
Solar/Wind Harmer
20.062
274695ROCKY RD ;2P
Adder
21.58
958491AF2-143 GEN
Solar/Wind Harmer
20.043
276872AE1-163_GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
4.104
274765LEE CO EC;6U
Adder
17.201
274763LEE CO EC;4U
Adder
16.999
270180AB1-006 GEN1
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.848
270031AE2-169
Solar/Wind Harmer
6.202
276911AD2-131_GEN
Solar/Wind Harmer
1.524
270143AC1-141 CT2_
50/50
5.013
24639705ELKHART HY
50/50
0.334
970521AG2-332 GEN
50/50
23.772
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
10.053
270055AF2-134 C O1
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
60.769
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
10.963
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
34.771
274828WAUKEGAN ;BP
Adder
21.342
957471AF2-041 GEN
Solar/Wind Harmer
39.433
965651AG1-433 GEN
Solar/Wind Harmer
3.724
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.002
970613AG2-401 GEN
Solar/Wind Harmer
7.127
24728605AND G2
Adder
5.117
965421AG1-410 GEN
Solar/Wind Harmer
25.535
274773LINCOLN ;4U
50/50
18.336
274774LINCOLN ;5U
50/50
18.336
24307105BERRINSP G
50/50
0.044
957891AF2-083 GEN
Solar/Wind Harmer
23.982
945111AF1-176 GEN
Solar/Wind Harmer
25.563
274723RIVER EC ;12
Adder
36.21
274751CRETE EC ;1U
Adder
16.621
964861AG1-349 GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
16.687
971997AH1-543 GEN
Solar/Wind Harmer
6.973
970569AG2-363 GEN
Solar/Wind Harmer
38.976
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
17.161
965011AG1-365 GEN
Solar/Wind Harmer
12.784
939741AE1-205 GEN
Solar/Wind Harmer
17.604
24386605FR-22G C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
7.766
274752CRETE EC ;2U
Adder
16.621
270063AE2-323 C
Solar/Wind Harmer
0.001
970707AG2-453 GEN
Solar/Wind Harmer
45.738
274826FISK ;BP
Adder
21.872
274887GEN-1.85
Solar/Wind Harmer
0.362
939351AE1-166 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
61.966
274730ELWOOD EC;6P
Adder
32.486
274862TOP CROP ;2U
Solar/Wind Harmer
1.824
276868AE1-113 GEN
Solar/Wind Harmer
2.661
274879MINONK ;1U
Solar/Wind Harmer
0.555
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274857EASY ROAD;U1
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
12.865
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
4.121
970193AG2-126 GEN
Solar/Wind Harmer
16.03
24728705AND G3
Adder
10.702
270102X2-052 ST
50/50
3.362
24643105BUCHANAN
50/50
0.026
970349AG2-230 GEN
Solar/Wind Harmer
23.297
961051AF2-396 GEN
Solar/Wind Harmer
28.57
961051AF2-396 GEN
Solar/Wind Harmer
19.046
274808UNIV PK N;4U
Adder
10.009
274674JOLIET 9 ;6U
Adder
30.452
274693ROCKY RD ;1P
Adder
21.367
958481AF2-142 GEN
Solar/Wind Harmer
20.28
274683WAUKEGAN ;8U
Adder
40.715
274683WAUKEGAN ;8U
Adder
34.321
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.72
274764LEE CO EC;5U
Adder
17.201
24697605MDL-3G C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
7.448
966841AG1-555 GEN
Solar/Wind Harmer
1.408
960611AF2-352 GEN
Solar/Wind Harmer
4.121
276615X2-022 GEN
Solar/Wind Harmer
0.119
944231AF1-091 GEN
Solar/Wind Harmer
26.413
270599AE1-208 GEN
Solar/Wind Harmer
10.337
24725505WLD G2 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
11.354
270247TR4_N_V136
Solar/Wind Harmer
0.065
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
8.884
24728905RICHG2
Adder
3.746
274827FISK ;RP
Adder
15.501
972227AH1-698 GEN1
Adder
5.206
274800UNIV PARK;3U
Adder
11.637
274801UNIV PARK;4U
Adder
11.637
274735ELWOOD EC;4P
Adder
32.486
274744AC1-111 GEN8
Adder
10.963
958391AF2-133 GEN
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
13.017
276741O09 GEN1
Solar/Wind Harmer
0.449
274877BISHOP HL;1U
Solar/Wind Harmer
0.422
959341AF2-225 GEN
Solar/Wind Harmer
13.203
963791AG1-232 GEN
Solar/Wind Harmer
15.924
276668AB2-070 GEN1
Solar/Wind Harmer
0.46
276848AB2-070 GEN3
Solar/Wind Harmer
0.458
276849AB2-070 GEN2
Solar/Wind Harmer
0.46
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
2.196
247521TR3_G114
Solar/Wind Harmer
0.369
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
16.621
274802UNIV PARK;5U
Adder
11.65
274674JOLIET 9 ;6U
Adder
30.452
274732ELWOOD EC;7P
Adder
32.486
958381AF2-132 GEN
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
10.03
962781AG1-127 GEN
Solar/Wind Harmer
12.744
274766LEE CO EC;7U
Adder
16.958
276708O09 GEN2
Solar/Wind Harmer
0.449
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.221
276903AD2-071 C
Solar/Wind Harmer
12.218
270437AC2-090 C
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.008
971771AH1-392 GEN
Solar/Wind Harmer
14.587
270071AF1-092 GEN
Solar/Wind Harmer
27.676
274728ELWOOD EC;5P
Adder
32.486
24729505KEY G4
Adder
12.577
970073AG2-061 GEN
Solar/Wind Harmer
4.454
276861AD2-134 GEN
Solar/Wind Harmer
0.236
276863AD2-134 GEN
Solar/Wind Harmer
0.236
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.304
971549AH1-272 GEN
Solar/Wind Harmer
26.772
971681AH1-341 GEN
Solar/Wind Harmer
20.809
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.219
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.021
274772LINCOLN ;3U
50/50
18.336
944961AF1-161 GEN
50/50
5.942
270043AE2-236 GEN
Solar/Wind Harmer
9.417
270505AE1-170 C O1
Solar/Wind Harmer
15.137
945111AF1-176 GEN
Solar/Wind Harmer
11.613
274724RIVER EC ;11
Adder
35.793
972259AH1-714 GEN
Adder
38.13
274729ELWOOD EC;1P
Adder
32.486
946671AF1-331 GEN
Solar/Wind Harmer
1.412
274850MENDOTA H;RU
Solar/Wind Harmer
0.154
970571AG2-364 GEN
Solar/Wind Harmer
25.984
965021AG1-366 GEN
Solar/Wind Harmer
4.261
971993AH1-541 GEN
Solar/Wind Harmer
5.405
942481AE2-261 GEN
Solar/Wind Harmer
33.208
970825AG2-519 GEN
Solar/Wind Harmer
7.905
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.395
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.29
270144AC1-141 ST1_
50/50
4.427
274776LINCOLN ;7U
50/50
18.336
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
55.408
274687WILL CNTY;4U
Adder
55.408
274731ELWOOD EC;2P
Adder
32.486
274733ELWOOD EC;3P
Adder
32.486
274746AC1-111 G10
Adder
10.963
926823AC1-168 GEN
Solar/Wind Harmer
2.21
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
959331AF2-224 GEN
Solar/Wind Harmer
8.949
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
5.236
971609AH1-304 GEN
Solar/Wind Harmer
1.842
965041AG1-368 GEN
Solar/Wind Harmer
11.074
24344105CKG2
50/50
17.278
943021AE2-325 GEN
Solar/Wind Harmer
7.444
970373AG2-245 GEN
Solar/Wind Harmer
29.476
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
17.697
276691AA1-018 GEN1
Solar/Wind Harmer
2.197
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
-0.001
276882AE2-255 GEN
Solar/Wind Harmer
1.552
959081AF2-199 GEN
Solar/Wind Harmer
13.144
971067AG2-660 GEN
Solar/Wind Harmer
4.381
274822ROCKFORD ;11
Adder
36.841
970819AG2-516 GEN
Solar/Wind Harmer
15.625
276646AC1-214 GEN2
Solar/Wind Harmer
0.499
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
27.848
970091AG2-072 GEN
Adder
105.739
970773AG2-487 GEN
Solar/Wind Harmer
1.491
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.771
270201AC2-176 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.961
24728805RICHG1
Adder
3.746
24344005CKG1
50/50
13.518
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
18.336
274777LINCOLN ;8U
50/50
18.336
972037AH1-567 GEN1
Adder
0.366
960591AF2-350 GEN
Solar/Wind Harmer
13.932
972228AH1-698 GEN2
Adder
7.394
274675JOLIET 29;7U
Adder
60.77
274675JOLIET 29;7U
Adder
58.6
970031AG2-029 GEN
Solar/Wind Harmer
7.48
970833AG2-524 GEN
Solar/Wind Harmer
15.154
970833AG2-524 GEN
Solar/Wind Harmer
10.103
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
7.947
971675AH1-338 GEN
Solar/Wind Harmer
5.16
971411AH1-196 GEN
Solar/Wind Harmer
19.845
971171AH1-044 GEN
Solar/Wind Harmer
26.289
274823ROCKFORD ;21
Adder
36.573
972267AH1-718 GEN
Adder
7.604
24386405FR-21G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.924
945581AF1-223 GEN
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
5.084
247536S-71 GEN
Solar/Wind Harmer
0.379
971029AG2-637 GEN
Solar/Wind Harmer
12.334
944221AF1-090 GEN
Solar/Wind Harmer
6.279
964611AG1-324 GEN
Solar/Wind Harmer
4.011
270356AE2-297 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
5.383
945371AF1-202 GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.575
270594AE1-207 GEN
Solar/Wind Harmer
12.64
270032AE2-172
Solar/Wind Harmer
7.524
270005AE1-210 C O1
Solar/Wind Harmer
2.315
970825AG2-519 GEN
Solar/Wind Harmer
3.725
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.325
270489AE1-102 GEN1
Solar/Wind Harmer
1.048
270100X2-052 CT1
50/50
3.107
274770LINCOLN ;1U
50/50
18.336
274771LINCOLN ;2U
50/50
18.336
274805UNIV PK N;1U
Adder
10.075
274888KELLY CRK;1U
Solar/Wind Harmer
0.813
970941AG2-585 GEN
Solar/Wind Harmer
7.663
276897AD1-100 C
Solar/Wind Harmer
34.688
276893AG1-478 C
Solar/Wind Harmer
0.919
274697ROCKY RD ;3P
Adder
5.862
274696ROCKY RD ;4P
Adder
22.088
962691AG1-118 GEN
Solar/Wind Harmer
40.277
957841AF2-078 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
7.321
274762LEE CO EC;3U
Adder
17.161
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
2.052
276645AC1-214 GEN1
Solar/Wind Harmer
0.499
942111AE2-223 GEN
Solar/Wind Harmer
4.087
24387305FR-4G C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
4.822
970241AG2-163 GEN
Solar/Wind Harmer
6.864
276838X2-022 GEN2
Solar/Wind Harmer
0.647
970623AG2-406 GEN
Solar/Wind Harmer
1.577
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.325
NYPJM->LTFIMP_NY
CLTF
3.371
LGEELTFEXP_LGEE->PJM
CLTF
5.638
WECLTFEXP_WEC->PJM
CLTF
7.136
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.164
AG2-052LTFEXP_AG2-052->PJM
LTF
0.449
AH1-155LTFEXP_AH1-155->PJM
LTF
0.674
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.166
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5
CBM West 1LTFEXP_CBM-W1->PJM
CBM
218.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.394
MECLTFEXP_MEC->PJM
CLTF
26.166
SIGELTFEXP_SIGE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
14.281
TVALTFEXP_TVA->PJM
CLTF
5.469

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.63 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2609.67
MW Contribution:
2.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
25194708EBND2
50/50
6.282
24729205KEY G1
50/50
0.332
944541AF1-119 GEN
Solar/Wind Harmer
0.465
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.665
270383AD1-128 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.476
270201AC2-176 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.651
270180AB1-006 GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
24726905LAWG2S
50/50
5.175
24726705LAWG2A
50/50
3.469
945581AF1-223 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.216
971029AG2-637 GEN
Solar/Wind Harmer
6.645
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.16
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.136
963791AG1-232 GEN
Solar/Wind Harmer
5.573
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.138
276848AB2-070 GEN3
Solar/Wind Harmer
0.137
276849AB2-070 GEN2
Solar/Wind Harmer
0.138
959341AF2-225 GEN
Solar/Wind Harmer
3.675
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
3.478
972227AH1-698 GEN1
Adder
1.29
274800UNIV PARK;3U
Adder
2.879
274801UNIV PARK;4U
Adder
2.879
274827FISK ;RP
Adder
3.829
274735ELWOOD EC;4P
Adder
8.1
274744AC1-111 GEN8
Adder
2.736
274877BISHOP HL;1U
Solar/Wind Harmer
0.112
276741O09 GEN1
Solar/Wind Harmer
0.118
253343AC1-166 GEN
Solar/Wind Helper
0.584
241973AD2-163_GEN1
Solar/Wind Helper
1.034
241974AD2-163_GEN2
Solar/Wind Helper
1.034
241955AC1-078 GEN
Solar/Wind Helper
0.981
24726805LAWG2B
50/50
3.43
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.089
961161AF2-407 GEN
50/50
36.206
24728705AND G3
50/50
7.209
944531AF1-118 GEN
Solar/Wind Harmer
27.23
970193AG2-126 GEN
Solar/Wind Harmer
6.211
970781AG2-491 GEN
Solar/Wind Harmer
3.696
971347AH1-153 GEN
Solar/Wind Harmer
1.751
959611AF2-252 GEN
Solar/Wind Harmer
1.165
939351AE1-166 GEN
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
4.076
274887GEN-1.85
Solar/Wind Harmer
0.09
274826FISK ;BP
Adder
5.402
970707AG2-453 GEN
Solar/Wind Harmer
11.245
274730ELWOOD EC;6P
Adder
8.1
274862TOP CROP ;2U
Solar/Wind Harmer
0.462
276868AE1-113 GEN
Solar/Wind Harmer
0.682
274879MINONK ;1U
Solar/Wind Harmer
0.142
274855GSG-6 ;RU
Solar/Wind Harmer
0.123
276782AC1-033 GEN
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Helper
1.361
24729405KEY G3
50/50
0.34
24729305KEY G2
50/50
0.334
942221AE2-234 GEN
Solar/Wind Harmer
2.113
24728505AND G1
50/50
3.447
946031AF1-268 GEN
Solar/Wind Harmer
6.921
970289AG2-191 GEN
Solar/Wind Harmer
0.658
247642Z2-115 C
Solar/Wind Harmer
0.002
957381AF2-032 GEN
Solar/Wind Harmer
0.783
276806AD2-047 C O1
Solar/Wind Harmer
1.955
274811UNIV PK N;7U
Adder
2.475
274734ELWOOD EC;8P
Adder
8.1
274736ELWOOD EC;9P
Adder
8.1
274676JOLIET 29;8U
Adder
14.556
943121AE2-341 GEN
Solar/Wind Harmer
5.725
943591AF1-030 GEN
Solar/Wind Harmer
3.807
274682WAUKEGAN ;7U
Adder
8.741
959091AF2-200 GEN
Solar/Wind Harmer
6.717
274767LEE CO EC;8U
Adder
4.387
971087AG2-675 GEN
Solar/Wind Harmer
1.743
252524AE2-267 GEN
Solar/Wind Helper
1.058
960071AF2-298 GEN
Solar/Wind Helper
0.562
276820AF1-078_GEN
Solar/Wind Helper
0.471
24726405LAWG1A
50/50
3.345
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.847
945371AF1-202 GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.617
958861AF2-177 GEN
Solar/Wind Harmer
3.107
270594AE1-207 GEN
Solar/Wind Harmer
7.11
270032AE2-172
Solar/Wind Harmer
4.232
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.534
964861AG1-349 GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.9
276621W2-048 GEN
Solar/Wind Harmer
0.174
274773LINCOLN ;4U
Adder
4.193
274774LINCOLN ;5U
Adder
4.193
274723RIVER EC ;12
Adder
8.866
274751CRETE EC ;1U
Adder
4.076
971997AH1-543 GEN
Solar/Wind Harmer
1.792
276805AD2-038 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
10.179
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.439
957891AF2-083 GEN
Solar/Wind Harmer
5.533
945111AF1-176 GEN
Solar/Wind Harmer
5.913
965011AG1-365 GEN
Solar/Wind Harmer
3.036
252510AF1-249 C
Solar/Wind Helper
0.649
253398AE2-221_GEN2
Solar/Wind Helper
1.605
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.553
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.138
270043AE2-236 GEN
Solar/Wind Harmer
2.461
971993AH1-541 GEN
Solar/Wind Harmer
1.619
274772LINCOLN ;3U
Adder
4.193
942481AE2-261 GEN
Solar/Wind Harmer
10.33
274724RIVER EC ;11
Adder
8.762
972259AH1-714 GEN
Adder
9.423
274729ELWOOD EC;1P
Adder
8.1
970571AG2-364 GEN
Solar/Wind Harmer
6.786
946671AF1-331 GEN
Solar/Wind Harmer
0.359
274850MENDOTA H;RU
Solar/Wind Harmer
0.039
270505AE1-170 C O1
Solar/Wind Harmer
3.482
945111AF1-176 GEN
Solar/Wind Harmer
2.686
965021AG1-366 GEN
Solar/Wind Harmer
1.012
253394AE2-221_GEN
Solar/Wind Helper
1.605
270367AC2-061_GEN
Solar/Wind Helper
1.959
270186AC1-089 GEN
Solar/Wind Helper
0.816
970241AG2-163 GEN
Solar/Wind Harmer
2.28
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
1.137
276838X2-022 GEN2
Solar/Wind Harmer
0.196
274770LINCOLN ;1U
Adder
4.193
274771LINCOLN ;2U
Adder
4.193
276897AD1-100 C
Solar/Wind Harmer
8.649
274888KELLY CRK;1U
Solar/Wind Harmer
0.201
970941AG2-585 GEN
Solar/Wind Harmer
1.898
274805UNIV PK N;1U
Adder
2.48
276893AG1-478 C
Solar/Wind Harmer
0.229
274696ROCKY RD ;4P
Adder
5.549
274697ROCKY RD ;3P
Adder
1.473
962691AG1-118 GEN
Solar/Wind Harmer
10.16
276645AC1-214 GEN1
Solar/Wind Harmer
0.133
938861AE1-114 GEN
Solar/Wind Harmer
1.89
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.537
274762LEE CO EC;3U
Adder
4.439
253378AE2-206_GEN
Solar/Wind Helper
1.008
962581AG1-107 GEN
Solar/Wind Helper
1.008
961491AF2-440 GEN
Solar/Wind Helper
0.041
961171AF2-408 GEN
50/50
9.629
24728605AND G2
50/50
3.447
970613AG2-401 GEN
Solar/Wind Harmer
7.823
965651AG1-433 GEN
Solar/Wind Harmer
2.041
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.475
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.736
274682WAUKEGAN ;7U
Adder
8.741
274828WAUKEGAN ;BP
Adder
5.369
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.074
957471AF2-041 GEN
Solar/Wind Harmer
10.076
270449AD2-020 GEN
Solar/Wind Harmer
0
247621Y3-024
50/50
0.2
971613AH1-306 GEN
Solar/Wind Harmer
3.047
970291AG2-192 GEN
Solar/Wind Harmer
0.777
970291AG2-192 GEN
Solar/Wind Harmer
0.359
971587AH1-292 GEN
Solar/Wind Harmer
2.74
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.321
276916AD2-100_GEN
Solar/Wind Harmer
7.252
276776AD2-060 GEN
Solar/Wind Harmer
0.368
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.717
971343AH1-151 GEN
Solar/Wind Harmer
6.717
253383AE2-342_GEN
Solar/Wind Helper
0.473
970773AG2-487 GEN
Solar/Wind Harmer
1.792
963741AG1-226 GEN
Solar/Wind Harmer
9.25
971917AH1-482 GEN
Solar/Wind Harmer
4.671
970373AG2-245 GEN
Solar/Wind Harmer
7.43
276655WTG1_EQ
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.556
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.398
274872LEEDK;1U
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.133
959081AF2-199 GEN
Solar/Wind Harmer
3.359
971067AG2-660 GEN
Solar/Wind Harmer
1.12
970091AG2-072 GEN
Adder
36.89
274822ROCKFORD ;11
Adder
9.422
970819AG2-516 GEN
Solar/Wind Harmer
4.01
943021AE2-325 GEN
Solar/Wind Harmer
1.71
24728805RICHG1
Adder
1.91
965791AG1-447 GEN
Solar/Wind Harmer
3.169
276911AD2-131_GEN
Solar/Wind Harmer
0.478
958011AF2-095 GEN
Solar/Wind Harmer
4.968
958491AF2-143 GEN
Solar/Wind Harmer
5.119
276872AE1-163_GEN1
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.421
972236AH1-702 GEN2
Adder
1.051
247620Y3-023
Adder
0.221
274765LEE CO EC;6U
Adder
4.449
274763LEE CO EC;4U
Adder
4.397
25183208HLCRTG
Solar/Wind Helper
2.475
252509AD1-136 GEN
Solar/Wind Helper
0.194
253400AC2-068 GEN
Solar/Wind Helper
0.107
964611AG1-324 GEN
Solar/Wind Harmer
2.474
963841AG1-237 GEN
Solar/Wind Harmer
1.664
946581AF1-322 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
274776LINCOLN ;7U
Adder
4.193
960681AF2-359 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.022
274731ELWOOD EC;2P
Adder
8.1
274733ELWOOD EC;3P
Adder
8.1
274687WILL CNTY;4U
Adder
13.754
274687WILL CNTY;4U
Adder
13.754
274746AC1-111 G10
Adder
2.736
270526AF1-158 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.579
959331AF2-224 GEN
Solar/Wind Harmer
2.126
241972AD1-140 GEN
Solar/Wind Helper
3.462
270340AC2-060 GEN
Solar/Wind Helper
1.186
253338AC1-165 GEN
Solar/Wind Helper
0.584
945631AF1-228 GEN
Solar/Wind Helper
1.084
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.229
24385905FR-11G C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.598
965911AG1-460 GEN
Solar/Wind Harmer
0.691
274754CRETE EC ;4U
Adder
4.076
274802UNIV PARK;5U
Adder
2.879
274732ELWOOD EC;7P
Adder
8.1
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
4.082
24725505WLD G2 C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
6.109
970883AG2-550 GEN
Solar/Wind Harmer
4.953
945391AF1-204 GEN
Solar/Wind Harmer
4.4
966841AG1-555 GEN
Solar/Wind Harmer
0.427
24697605MDL-3G C
Solar/Wind Harmer
0
24728905RICHG2
Adder
1.91
970349AG2-230 GEN
Solar/Wind Harmer
5.254
960611AF2-352 GEN
Solar/Wind Harmer
1.165
276615X2-022 GEN
Solar/Wind Harmer
0.036
274808UNIV PK N;4U
Adder
2.464
274674JOLIET 9 ;6U
Adder
7.581
958481AF2-142 GEN
Solar/Wind Harmer
5.132
276876AE1-163_GEN2
Solar/Wind Harmer
0
274693ROCKY RD ;1P
Adder
5.368
274683WAUKEGAN ;8U
Adder
10.242
274683WAUKEGAN ;8U
Adder
8.634
972235AH1-702 GEN1
Adder
1.209
274764LEE CO EC;5U
Adder
4.449
961051AF2-396 GEN
Solar/Wind Harmer
6.579
961051AF2-396 GEN
Solar/Wind Harmer
4.386
253349AC2-067 GEN
Solar/Wind Helper
0.267
253415AE1-040 GEN
Solar/Wind Helper
0.551
274775LINCOLN ;6U
Adder
4.193
274777LINCOLN ;8U
Adder
4.193
972228AH1-698 GEN2
Adder
1.832
960591AF2-350 GEN
Solar/Wind Harmer
3.45
972037AH1-567 GEN1
Adder
0.09
970833AG2-524 GEN
Solar/Wind Harmer
3.784
970833AG2-524 GEN
Solar/Wind Harmer
2.522
274675JOLIET 29;7U
Adder
15.095
274675JOLIET 29;7U
Adder
14.556
970031AG2-029 GEN
Solar/Wind Harmer
1.836
971675AH1-338 GEN
Solar/Wind Harmer
1.313
971411AH1-196 GEN
Solar/Wind Harmer
5.046
971171AH1-044 GEN
Solar/Wind Harmer
6.717
274823ROCKFORD ;21
Adder
9.354
972267AH1-718 GEN
Adder
1.98
946321AF1-296 GEN
Solar/Wind Harmer
1.835
253406AD2-031_GEN
Solar/Wind Helper
0.908
24726605LAWG1S
50/50
5.173
24726505LAWG1B
50/50
3.445
24729505KEY G4
50/50
6.226
270543AE2-219 C
Solar/Wind Harmer
3.467
270071AF1-092 GEN
Solar/Wind Harmer
8.015
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
8.1
970073AG2-061 GEN
Solar/Wind Harmer
1.138
971771AH1-392 GEN
Solar/Wind Harmer
3.397
276861AD2-134 GEN
Solar/Wind Harmer
0.06
276863AD2-134 GEN
Solar/Wind Harmer
0.06
274856ECOGROVE ;U1
Solar/Wind Harmer
0.078
971681AH1-341 GEN
Solar/Wind Harmer
5.372
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.847
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
10.482
274753CRETE EC ;3U
Adder
4.076
276843GEN-1.7
Solar/Wind Harmer
0.112
274814UNIV PK N;0U
Adder
2.497
274807UNIV PK N;3U
Adder
2.491
274803UNIV PARK;6U
Adder
2.879
972038AH1-567 GEN2
Adder
0.18
274878BISHOP HL;2U
Solar/Wind Harmer
0.112
274760LEE CO EC;1U
Adder
4.439
965931AG1-462 GEN
Solar/Wind Harmer
8.333
270518AE2-148 GEN
Solar/Wind Helper
8.492
253325AC1-069 GEN
Solar/Wind Helper
0.605
274674JOLIET 9 ;6U
Adder
7.581
962781AG1-127 GEN
Solar/Wind Harmer
3.219
276708O09 GEN2
Solar/Wind Harmer
0.118
274766LEE CO EC;7U
Adder
4.387
253333AC1-068 GEN
Solar/Wind Helper
0.605
NYPJM->LTFIMP_NY
CLTF
0.654
LGEELTFEXP_LGEE->PJM
CLTF
1.45
WECLTFEXP_WEC->PJM
CLTF
1.827
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.493
MECLTFEXP_MEC->PJM
CLTF
7.337
SIGELTFEXP_SIGE->PJM
CLTF
0.239
LAGNLTFEXP_LAGN->PJM
CLTF
4.89
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.583
TVALTFEXP_TVA->PJM
CLTF
1.97

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2185.8
MW Contribution:
2.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
252516AE2-318_GEN
Solar/Wind Harmer
8.283
25194608D.CRK4
Adder
1.689
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.986
945681AF1-233 GEN
Solar/Wind Harmer
12.031
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
970613AG2-401 GEN
Solar/Wind Harmer
3.76
24728605AND G2
Adder
2.628
965651AG1-433 GEN
Solar/Wind Harmer
1.282
270024AE2-089 GEN
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.594
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.488
274812UNIV PK N;8U
Adder
2.528
274745AC1-111 GEN9
Adder
2.817
957471AF2-041 GEN
Solar/Wind Harmer
10.473
270449AD2-020 GEN
Solar/Wind Harmer
0
24803106KYGER 3LP
50/50
2.43
24803306KYGER 4LP
50/50
2.38
252507AC2-088 GEN
Solar/Wind Harmer
0.357
25196608WSDLE5
Adder
8.798
958171AF2-111 GEN
Solar/Wind Harmer
17.024
3429391JKCT 9G
Adder
6.396
24728705AND G3
Adder
5.496
944531AF1-118 GEN
Solar/Wind Harmer
18.504
970193AG2-126 GEN
Solar/Wind Harmer
6.094
970781AG2-491 GEN
Solar/Wind Harmer
3.775
959611AF2-252 GEN
Solar/Wind Harmer
1.21
939351AE1-166 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
0.092
274730ELWOOD EC;6P
Adder
8.311
970707AG2-453 GEN
Solar/Wind Harmer
11.521
276868AE1-113 GEN
Solar/Wind Harmer
0.705
274879MINONK ;1U
Solar/Wind Harmer
0.147
274862TOP CROP ;2U
Solar/Wind Harmer
0.476
274826FISK ;BP
Adder
5.528
274752CRETE EC ;2U
Adder
4.155
276782AC1-033 GEN
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
971347AH1-153 GEN
Solar/Wind Harmer
1.745
274857EASY ROAD;U1
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
270330AC1-082 GEN2
Solar/Wind Helper
0.194
24803406KYGER 5HP
50/50
4.083
25196808ZIMRHP
Adder
79.38
252510AF1-249 C
Solar/Wind Harmer
0.054
25196008MFTGT1
Adder
1.369
253398AE2-221_GEN2
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.04
970825AG2-519 GEN
Solar/Wind Harmer
1.683
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
5.019
270032AE2-172
Solar/Wind Harmer
2.988
958861AF2-177 GEN
Solar/Wind Harmer
1.919
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.628
276621W2-048 GEN
Solar/Wind Harmer
0.183
964861AG1-349 GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
5.074
274773LINCOLN ;4U
Adder
4.277
274774LINCOLN ;5U
Adder
4.277
971997AH1-543 GEN
Solar/Wind Harmer
1.853
276805AD2-038 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
10.575
274723RIVER EC ;12
Adder
9.04
274751CRETE EC ;1U
Adder
4.155
274858EASY ROAD;U2
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
5.58
945111AF1-176 GEN
Solar/Wind Harmer
5.962
965011AG1-365 GEN
Solar/Wind Harmer
3.232
270331AC1-082 GEN3
Solar/Wind Helper
0.193
24803206KYGER 4HP
50/50
4.079
3429421JKCT 10G
Adder
6.396
970773AG2-487 GEN
Solar/Wind Harmer
0.939
970653AG2-424 GEN
Solar/Wind Harmer
2.063
970091AG2-072 GEN
Adder
45.503
963741AG1-226 GEN
Solar/Wind Harmer
9.274
971917AH1-482 GEN
Solar/Wind Harmer
4.756
276655WTG1_EQ
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.536
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.411
276646AC1-214 GEN2
Solar/Wind Harmer
0.138
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.491
971067AG2-660 GEN
Solar/Wind Harmer
1.164
970819AG2-516 GEN
Solar/Wind Harmer
4.177
943021AE2-325 GEN
Solar/Wind Harmer
1.73
960001AF2-291 GEN
Solar/Wind Helper
1.722
971191AH1-055 GEN
Solar/Wind Harmer
68.684
25196008MFTGT1
Adder
1.326
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.127
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.143
970825AG2-519 GEN
Solar/Wind Harmer
3.571
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.92
971993AH1-541 GEN
Solar/Wind Harmer
1.694
942481AE2-261 GEN
Solar/Wind Harmer
10.95
972273AH1-721 GEN
Adder
43.369
274772LINCOLN ;3U
Adder
4.277
972259AH1-714 GEN
Adder
9.653
274729ELWOOD EC;1P
Adder
8.311
270043AE2-236 GEN
Solar/Wind Harmer
2.263
970571AG2-364 GEN
Solar/Wind Harmer
7.05
274724RIVER EC ;11
Adder
8.935
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
270505AE1-170 C O1
Solar/Wind Harmer
3.511
945111AF1-176 GEN
Solar/Wind Harmer
2.708
965021AG1-366 GEN
Solar/Wind Harmer
1.077
970191AG2-125 GEN
Solar/Wind Harmer
1.385
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.04
970455AG2-298 GEN
Solar/Wind Harmer
1.776
970653AG2-424 GEN
Solar/Wind Harmer
0.428
253325AC1-069 GEN
Solar/Wind Harmer
0.005
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.304
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
10.891
276843GEN-1.7
Solar/Wind Harmer
0.114
972038AH1-567 GEN2
Adder
0.184
274803UNIV PARK;6U
Adder
2.945
274814UNIV PK N;0U
Adder
2.55
274807UNIV PK N;3U
Adder
2.544
274753CRETE EC ;3U
Adder
4.155
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
965931AG1-462 GEN
Solar/Wind Harmer
8.801
270329AC1-082 GEN1
Solar/Wind Helper
0.194
24803006KYGER 3HP
50/50
4.127
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.452
972045AH1-571 GEN
Solar/Wind Harmer
1.214
270269AC2-059
Solar/Wind Harmer
0
24728805RICHG1
Adder
2.955
25326109MON D
Adder
0.984
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.635
964611AG1-324 GEN
Solar/Wind Harmer
0.348
270201AC2-176 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
2.485
964571AG1-320 GEN
Solar/Wind Harmer
4.079
944541AF1-119 GEN
Solar/Wind Harmer
0.292
270180AB1-006 GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
0.507
958011AF2-095 GEN
Solar/Wind Harmer
5.084
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
5.287
274695ROCKY RD ;2P
Adder
5.596
965791AG1-447 GEN
Solar/Wind Harmer
3.198
970329AG2-216 GEN
Solar/Wind Harmer
1.444
966021AG1-471 GEN
Solar/Wind Harmer
1.739
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970107AG2-081 GEN
Solar/Wind Harmer
1.684
942221AE2-234 GEN
Solar/Wind Harmer
1.655
970241AG2-163 GEN
Solar/Wind Harmer
2.286
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.206
25326509SID D
Adder
0.689
942111AE2-223 GEN
Solar/Wind Harmer
1.178
276897AD1-100 C
Solar/Wind Harmer
8.857
274770LINCOLN ;1U
Adder
4.277
274771LINCOLN ;2U
Adder
4.277
274888KELLY CRK;1U
Solar/Wind Harmer
0.206
970941AG2-585 GEN
Solar/Wind Harmer
1.942
276893AG1-478 C
Solar/Wind Harmer
0.235
276645AC1-214 GEN1
Solar/Wind Harmer
0.138
274805UNIV PK N;1U
Adder
2.533
274696ROCKY RD ;4P
Adder
5.728
274697ROCKY RD ;3P
Adder
1.52
962691AG1-118 GEN
Solar/Wind Harmer
10.508
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.562
938861AE1-114 GEN
Solar/Wind Harmer
1.972
25196508WSDLE4
Adder
8.708
972163AH1-664 GEN
Solar/Wind Harmer
7.027
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.58
270356AE2-297 GEN
Solar/Wind Harmer
0
3429211JKCT 2G
Adder
8.721
964611AG1-324 GEN
Solar/Wind Harmer
1.811
971609AH1-304 GEN
Solar/Wind Harmer
0.738
270432AC2-029 GEN
Solar/Wind Harmer
2.001
241972AD1-140 GEN
Solar/Wind Harmer
0.484
963841AG1-237 GEN
Solar/Wind Harmer
1.68
946581AF1-322 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.16
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
Adder
4.277
926823AC1-168 GEN
Solar/Wind Harmer
0.6
274731ELWOOD EC;2P
Adder
8.311
274733ELWOOD EC;3P
Adder
8.311
274687WILL CNTY;4U
Adder
14.106
274687WILL CNTY;4U
Adder
14.106
274746AC1-111 G10
Adder
2.817
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.262
965041AG1-368 GEN
Solar/Wind Harmer
3.099
945631AF1-228 GEN
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
3.858
25194608D.CRK4
Adder
1.689
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.081
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
24728505AND G1
Adder
2.628
946031AF1-268 GEN
Solar/Wind Harmer
4.524
970289AG2-191 GEN
Solar/Wind Harmer
0.483
247642Z2-115 C
Solar/Wind Harmer
0.002
957381AF2-032 GEN
Solar/Wind Harmer
0.83
276806AD2-047 C O1
Solar/Wind Harmer
2.001
274734ELWOOD EC;8P
Adder
8.311
274736ELWOOD EC;9P
Adder
8.311
274676JOLIET 29;8U
Adder
14.935
274811UNIV PK N;7U
Adder
2.528
943121AE2-341 GEN
Solar/Wind Harmer
5.893
943591AF1-030 GEN
Solar/Wind Harmer
3.919
274682WAUKEGAN ;7U
Adder
5.301
959091AF2-200 GEN
Solar/Wind Harmer
6.982
971087AG2-675 GEN
Solar/Wind Harmer
1.841
24802806KYGER 2HP
50/50
4.111
24802906KYGER 2LP
50/50
2.413
971125AH1-004 GEN
Solar/Wind Harmer
2.245
253370AE2-315 SEC1
Adder
1.601
25322209TAIT E
Adder
7.522
25322209TAIT E
Adder
7.353
247621Y3-024
Adder
0.162
971613AH1-306 GEN
Solar/Wind Harmer
2.151
970291AG2-192 GEN
Solar/Wind Harmer
0.57
970291AG2-192 GEN
Solar/Wind Harmer
0.263
971587AH1-292 GEN
Solar/Wind Harmer
2.993
276916AD2-100_GEN
Solar/Wind Harmer
7.7
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.377
971341AH1-150 GEN
Solar/Wind Harmer
6.982
971343AH1-151 GEN
Solar/Wind Harmer
6.982
965681AG1-436 GEN
Solar/Wind Harmer
4.361
270246TR4_N_V150
Solar/Wind Harmer
0.019
24802606KYGER 1HP
50/50
4.156
24802706KYGER 1LP
50/50
2.437
253372AE2-315 SEC3
Adder
1.514
253372AE2-315 SEC3
Adder
1.514
25306009OHH W.
Adder
2.27
970289AG2-191 GEN
Solar/Wind Harmer
0.834
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.053
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.144
276848AB2-070 GEN3
Solar/Wind Harmer
0.143
276849AB2-070 GEN2
Solar/Wind Harmer
0.144
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.806
970169AG2-114 GEN
Solar/Wind Harmer
3.591
972227AH1-698 GEN1
Adder
1.321
274735ELWOOD EC;4P
Adder
8.311
274800UNIV PARK;3U
Adder
2.946
274801UNIV PARK;4U
Adder
2.946
274827FISK ;RP
Adder
3.918
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
274744AC1-111 GEN8
Adder
2.817
276741O09 GEN1
Solar/Wind Harmer
0.123
247521TR3_G114
Solar/Wind Harmer
0.11
25194408D.CRK1
Adder
7.768
972043AH1-570 GEN
Solar/Wind Harmer
1.516
24728905RICHG2
Adder
2.955
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.111
970883AG2-550 GEN
Solar/Wind Harmer
4.905
24725505WLD G2 C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
4.141
960971AF2-388 GEN
Solar/Wind Harmer
2.564
945391AF1-204 GEN
Solar/Wind Harmer
4.316
966841AG1-555 GEN
Solar/Wind Harmer
0.434
24697605MDL-3G C
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.038
960611AF2-352 GEN
Solar/Wind Harmer
1.21
274674JOLIET 9 ;6U
Adder
7.779
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.287
274808UNIV PK N;4U
Adder
2.517
274693ROCKY RD ;1P
Adder
5.541
964781AG1-341 GEN
Solar/Wind Harmer
3.705
970349AG2-230 GEN
Solar/Wind Harmer
5.234
961051AF2-396 GEN
Solar/Wind Harmer
6.65
961051AF2-396 GEN
Solar/Wind Harmer
4.433
971485AH1-239 GEN
Solar/Wind Harmer
2.603
270247TR4_N_V136
Solar/Wind Harmer
0.019
237033AB1-150 GEN
Solar/Wind Helper
0.401
971985AH1-537 GEN
Solar/Wind Harmer
5.763
972165AH1-665 GEN
Solar/Wind Harmer
5.628
253406AD2-031_GEN
Solar/Wind Harmer
0.458
339216AC1-074 GEN
Solar/Wind Harmer
0.162
971029AG2-637 GEN
Solar/Wind Harmer
7.57
247536S-71 GEN
Solar/Wind Harmer
0.191
945581AF1-223 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.204
959141AF2-205 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
4.277
274777LINCOLN ;8U
Adder
4.277
972228AH1-698 GEN2
Adder
1.875
970833AG2-524 GEN
Solar/Wind Harmer
3.884
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.53
972037AH1-567 GEN1
Adder
0.092
274675JOLIET 29;7U
Adder
15.488
274675JOLIET 29;7U
Adder
14.935
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.237
971171AH1-044 GEN
Solar/Wind Harmer
6.982
946321AF1-296 GEN
Solar/Wind Harmer
1.935
970031AG2-029 GEN
Solar/Wind Harmer
1.822
965051AG1-369 GEN
Solar/Wind Harmer
1.514
24803506KYGER 5LP
50/50
2.38
25196408WSDLE3
Adder
9.057
25196308WSDLE2
Adder
8.978
25196208WSDLE1
Adder
8.956
25196708WSDLE6
Adder
8.933
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.401
270543AE2-219 C
Solar/Wind Harmer
3.433
24729505KEY G4
Adder
3.899
24691005MDL-2G C
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
7.11
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
8.311
970073AG2-061 GEN
Solar/Wind Harmer
1.175
276861AD2-134 GEN
Solar/Wind Harmer
0.062
276863AD2-134 GEN
Solar/Wind Harmer
0.062
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
971681AH1-341 GEN
Solar/Wind Harmer
5.605
971771AH1-392 GEN
Solar/Wind Harmer
3.411
971549AH1-272 GEN
Solar/Wind Harmer
6.245
270273AD2-016 GEN
Solar/Wind Harmer
0.594
25326309TAIT D
Adder
0.844
3429241JKCT 3G
Adder
8.835
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.07
253333AC1-068 GEN
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.732
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.672
274732ELWOOD EC;7P
Adder
8.311
274674JOLIET 9 ;6U
Adder
7.779
274802UNIV PARK;5U
Adder
2.945
274754CRETE EC ;4U
Adder
4.155
962781AG1-127 GEN
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
0.123
235780M24_1
Solar/Wind Helper
0.496
NYPJM->LTFIMP_NY
CLTF
1.666
LGEELTFEXP_LGEE->PJM
CLTF
5.14
WECLTFEXP_WEC->PJM
CLTF
1.904
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.289
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.393
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.044
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.317
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.627
MECLTFEXP_MEC->PJM
CLTF
8.009
SIGELTFEXP_SIGE->PJM
CLTF
0.331
LAGNLTFEXP_LAGN->PJM
CLTF
6.552
TVALTFEXP_TVA->PJM
CLTF
3.106

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.27 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2052.4
MW Contribution:
3.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
252516AE2-318_GEN
Solar/Wind Harmer
8.746
25194608D.CRK4
Adder
1.776
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.475
945681AF1-233 GEN
Solar/Wind Harmer
12.627
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
970613AG2-401 GEN
Solar/Wind Harmer
3.658
24728605AND G2
Adder
2.584
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.166
972203AH1-686 GEN
Adder
1.223
964901AG1-354 GEN
Solar/Wind Harmer
5.49
270055AF2-134 C O1
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
13.407
274745AC1-111 GEN9
Adder
2.441
957471AF2-041 GEN
Solar/Wind Harmer
9.139
274682WAUKEGAN ;7U
Adder
7.839
274828WAUKEGAN ;BP
Adder
4.817
24803106KYGER 3LP
50/50
2.46
24803306KYGER 4LP
50/50
2.41
252507AC2-088 GEN
Solar/Wind Harmer
0.376
25196608WSDLE5
Adder
9.253
958171AF2-111 GEN
Solar/Wind Harmer
17.947
3429391JKCT 9G
Adder
6.589
24728705AND G3
Adder
5.404
970193AG2-126 GEN
Solar/Wind Harmer
5.894
944531AF1-118 GEN
Solar/Wind Harmer
16.286
970781AG2-491 GEN
Solar/Wind Harmer
3.495
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Harmer
5.57
276868AE1-113 GEN
Solar/Wind Harmer
0.616
274879MINONK ;1U
Solar/Wind Harmer
0.129
939351AE1-166 GEN
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.415
274730ELWOOD EC;6P
Adder
7.204
274887GEN-1.85
Solar/Wind Harmer
0.079
274855GSG-6 ;RU
Solar/Wind Harmer
0.111
274857EASY ROAD;U1
Solar/Wind Harmer
0
274826FISK ;BP
Adder
4.777
970707AG2-453 GEN
Solar/Wind Harmer
9.937
270330AC1-082 GEN2
Solar/Wind Helper
0.188
24803406KYGER 5HP
50/50
4.134
25196808ZIMRHP
Adder
83.622
252510AF1-249 C
Solar/Wind Harmer
0.057
25196008MFTGT1
Adder
1.43
253398AE2-221_GEN2
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
24803206KYGER 4HP
50/50
4.13
3429421JKCT 10G
Adder
6.589
970773AG2-487 GEN
Solar/Wind Harmer
0.935
970091AG2-072 GEN
Adder
49.338
970653AG2-424 GEN
Solar/Wind Harmer
2.069
963741AG1-226 GEN
Solar/Wind Harmer
8.794
971917AH1-482 GEN
Solar/Wind Harmer
4.274
276655WTG1_EQ
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.636
276646AC1-214 GEN2
Solar/Wind Harmer
0.122
276882AE2-255 GEN
Solar/Wind Harmer
0.36
941551AE2-152 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.499
959081AF2-199 GEN
Solar/Wind Harmer
3.046
971067AG2-660 GEN
Solar/Wind Harmer
1.015
274872LEEDK;1U
Solar/Wind Harmer
0
274822ROCKFORD ;11
Adder
2.437
970819AG2-516 GEN
Solar/Wind Harmer
3.649
960001AF2-291 GEN
Solar/Wind Helper
1.676
270005AE1-210 C O1
Solar/Wind Harmer
0.992
970825AG2-519 GEN
Solar/Wind Harmer
1.611
270594AE1-207 GEN
Solar/Wind Harmer
4.771
270032AE2-172
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.758
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.169
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.21
964861AG1-349 GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.558
970569AG2-363 GEN
Solar/Wind Harmer
9.303
971997AH1-543 GEN
Solar/Wind Harmer
1.622
276805AD2-038 GEN
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.061
270331AC1-082 GEN3
Solar/Wind Helper
0.186
971191AH1-055 GEN
Solar/Wind Harmer
70.432
25196008MFTGT1
Adder
1.385
253394AE2-221_GEN
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.47
24379505HDWTR1G C
Solar/Wind Harmer
0
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970455AG2-298 GEN
Solar/Wind Harmer
1.797
270004AE1-209 GEN
Solar/Wind Harmer
0.992
970653AG2-424 GEN
Solar/Wind Harmer
0.429
270518AE2-148 GEN
Solar/Wind Harmer
0.348
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
9.828
274878BISHOP HL;2U
Solar/Wind Harmer
0.104
276843GEN-1.7
Solar/Wind Harmer
0.099
972038AH1-567 GEN2
Adder
0.159
274803UNIV PARK;6U
Adder
2.546
965931AG1-462 GEN
Solar/Wind Harmer
7.765
274760LEE CO EC;1U
Adder
4.061
270329AC1-082 GEN1
Solar/Wind Helper
0.188
972167AH1-666 GEN
Solar/Wind Harmer
5.382
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.224
970825AG2-519 GEN
Solar/Wind Harmer
3.419
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.615
972273AH1-721 GEN
Adder
42.335
942481AE2-261 GEN
Solar/Wind Harmer
10.146
971993AH1-541 GEN
Solar/Wind Harmer
1.554
970571AG2-364 GEN
Solar/Wind Harmer
6.202
274729ELWOOD EC;1P
Adder
7.204
972259AH1-714 GEN
Adder
8.342
274850MENDOTA H;RU
Solar/Wind Harmer
0.035
946671AF1-331 GEN
Solar/Wind Harmer
0.325
24803006KYGER 3HP
50/50
4.179
25183008BIOENL
50/50
0.032
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.527
270269AC2-059
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.262
25326109MON D
Adder
1.062
24728805RICHG1
Adder
2.987
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.601
964571AG1-320 GEN
Solar/Wind Harmer
4.114
964611AG1-324 GEN
Solar/Wind Harmer
0.333
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
2.337
944541AF1-119 GEN
Solar/Wind Harmer
0.265
970329AG2-216 GEN
Solar/Wind Harmer
1.606
270180AB1-006 GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
0.471
942861AE2-305 GEN
Solar/Wind Harmer
2.579
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.619
966021AG1-471 GEN
Solar/Wind Harmer
1.662
958011AF2-095 GEN
Solar/Wind Harmer
4.397
274765LEE CO EC;6U
Adder
4.07
274763LEE CO EC;4U
Adder
4.023
274695ROCKY RD ;2P
Adder
4.859
972236AH1-702 GEN2
Adder
0.956
25196508WSDLE4
Adder
9.159
972163AH1-664 GEN
Solar/Wind Harmer
7.368
270263AC1-001 GEN
Solar/Wind Harmer
0.65
270340AC2-060 GEN
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
8.956
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.299
241972AD1-140 GEN
Solar/Wind Harmer
0.535
964611AG1-324 GEN
Solar/Wind Harmer
1.732
971609AH1-304 GEN
Solar/Wind Harmer
0.694
963841AG1-237 GEN
Solar/Wind Harmer
1.583
945631AF1-228 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.02
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.529
274731ELWOOD EC;2P
Adder
7.204
274733ELWOOD EC;3P
Adder
7.204
274687WILL CNTY;4U
Adder
12.208
274687WILL CNTY;4U
Adder
12.208
274746AC1-111 G10
Adder
2.441
252519AF1-045_GEN
Solar/Wind Harmer
4.074
25194608D.CRK4
Adder
1.776
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.717
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
24728505AND G1
Adder
2.584
946031AF1-268 GEN
Solar/Wind Harmer
4.337
970289AG2-191 GEN
Solar/Wind Harmer
0.457
247642Z2-115 C
Solar/Wind Harmer
0.002
957381AF2-032 GEN
Solar/Wind Harmer
0.768
274734ELWOOD EC;8P
Adder
7.204
274736ELWOOD EC;9P
Adder
7.204
276806AD2-047 C O1
Solar/Wind Harmer
1.73
274676JOLIET 29;8U
Adder
12.928
959091AF2-200 GEN
Solar/Wind Harmer
6.093
274767LEE CO EC;8U
Adder
4.013
971087AG2-675 GEN
Solar/Wind Harmer
1.624
943121AE2-341 GEN
Solar/Wind Harmer
5.104
943591AF1-030 GEN
Solar/Wind Harmer
3.394
274682WAUKEGAN ;7U
Adder
7.839
24802806KYGER 2HP
50/50
4.162
24802906KYGER 2LP
50/50
2.443
253370AE2-315 SEC1
Adder
1.716
971125AH1-004 GEN
Solar/Wind Harmer
2.323
25322209TAIT E
Adder
8.074
25322209TAIT E
Adder
7.893
247621Y3-024
Adder
0.156
971613AH1-306 GEN
Solar/Wind Harmer
2.045
970291AG2-192 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.25
971587AH1-292 GEN
Solar/Wind Harmer
3.03
276916AD2-100_GEN
Solar/Wind Harmer
7.149
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.326
971341AH1-150 GEN
Solar/Wind Harmer
6.093
971343AH1-151 GEN
Solar/Wind Harmer
6.093
24802606KYGER 1HP
50/50
4.207
24802706KYGER 1LP
50/50
2.467
253372AE2-315 SEC3
Adder
1.623
253372AE2-315 SEC3
Adder
1.623
25306009OHH W.
Adder
2.424
970289AG2-191 GEN
Solar/Wind Harmer
0.79
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
4.554
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.132
276848AB2-070 GEN3
Solar/Wind Harmer
0.132
276849AB2-070 GEN2
Solar/Wind Harmer
0.132
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.273
943851AF1-053 GEN
Solar/Wind Harmer
0.882
959341AF2-225 GEN
Solar/Wind Harmer
3.418
970169AG2-114 GEN
Solar/Wind Harmer
3.185
274877BISHOP HL;1U
Solar/Wind Harmer
0.104
276741O09 GEN1
Solar/Wind Harmer
0.108
274735ELWOOD EC;4P
Adder
7.204
972227AH1-698 GEN1
Adder
1.143
274800UNIV PARK;3U
Adder
2.547
274801UNIV PARK;4U
Adder
2.547
274744AC1-111 GEN8
Adder
2.441
274827FISK ;RP
Adder
3.386
25194408D.CRK1
Adder
8.168
972043AH1-570 GEN
Solar/Wind Harmer
1.575
24728905RICHG2
Adder
2.987
942891AE2-308 GEN
Solar/Wind Harmer
5.239
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.803
24725505WLD G2 C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
3.895
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.175
966841AG1-555 GEN
Solar/Wind Harmer
0.406
24697605MDL-3G C
Solar/Wind Harmer
0
964781AG1-341 GEN
Solar/Wind Harmer
3.596
276615X2-022 GEN
Solar/Wind Harmer
0.035
960611AF2-352 GEN
Solar/Wind Harmer
1.092
971485AH1-239 GEN
Solar/Wind Harmer
2.492
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
4.605
274674JOLIET 9 ;6U
Adder
6.739
274764LEE CO EC;5U
Adder
4.07
274693ROCKY RD ;1P
Adder
4.811
274683WAUKEGAN ;8U
Adder
9.19
274683WAUKEGAN ;8U
Adder
7.747
972235AH1-702 GEN1
Adder
1.099
237033AB1-150 GEN
Solar/Wind Helper
0.404
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970107AG2-081 GEN
Solar/Wind Harmer
1.743
25326509SID D
Adder
0.755
942221AE2-234 GEN
Solar/Wind Harmer
1.514
970241AG2-163 GEN
Solar/Wind Harmer
2.168
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.19
942111AE2-223 GEN
Solar/Wind Harmer
1.058
276645AC1-214 GEN1
Solar/Wind Harmer
0.122
276897AD1-100 C
Solar/Wind Harmer
7.68
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.494
276893AG1-478 C
Solar/Wind Harmer
0.204
274888KELLY CRK;1U
Solar/Wind Harmer
0.178
970941AG2-585 GEN
Solar/Wind Harmer
1.679
938861AE1-114 GEN
Solar/Wind Harmer
1.726
962691AG1-118 GEN
Solar/Wind Harmer
9.136
274762LEE CO EC;3U
Adder
4.061
274696ROCKY RD ;4P
Adder
4.974
274697ROCKY RD ;3P
Adder
1.32
971985AH1-537 GEN
Solar/Wind Harmer
5.9
253406AD2-031_GEN
Solar/Wind Harmer
0.493
972165AH1-665 GEN
Solar/Wind Harmer
5.901
339216AC1-074 GEN
Solar/Wind Harmer
0.169
971029AG2-637 GEN
Solar/Wind Harmer
7.492
247536S-71 GEN
Solar/Wind Harmer
0.185
945581AF1-223 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.005
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.368
970833AG2-524 GEN
Solar/Wind Harmer
2.246
972228AH1-698 GEN2
Adder
1.623
960591AF2-350 GEN
Solar/Wind Harmer
3.054
274675JOLIET 29;7U
Adder
13.407
274675JOLIET 29;7U
Adder
12.928
972267AH1-718 GEN
Adder
1.819
972037AH1-567 GEN1
Adder
0.08
971171AH1-044 GEN
Solar/Wind Harmer
6.093
971675AH1-338 GEN
Solar/Wind Harmer
1.188
946321AF1-296 GEN
Solar/Wind Harmer
1.706
971411AH1-196 GEN
Solar/Wind Harmer
4.564
270273AD2-016 GEN
Solar/Wind Harmer
0.667
25326309TAIT D
Adder
0.906
3429241JKCT 3G
Adder
9.074
270437AC2-090 C
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.005
276903AD2-071 C
Solar/Wind Harmer
4.853
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.679
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.347
276708O09 GEN2
Solar/Wind Harmer
0.108
274732ELWOOD EC;7P
Adder
7.204
274674JOLIET 9 ;6U
Adder
6.739
274802UNIV PARK;5U
Adder
2.546
274766LEE CO EC;7U
Adder
4.013
962781AG1-127 GEN
Solar/Wind Harmer
2.898
235780M24_1
Solar/Wind Helper
0.501
24803506KYGER 5LP
50/50
2.41
25196408WSDLE3
Adder
9.526
25196308WSDLE2
Adder
9.443
25196208WSDLE1
Adder
9.419
25196708WSDLE6
Adder
9.395
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
270543AE2-219 C
Solar/Wind Harmer
3.362
24729505KEY G4
Adder
3.463
24691005MDL-2G C
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
6.13
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.026
274728ELWOOD EC;5P
Adder
7.204
971681AH1-341 GEN
Solar/Wind Harmer
4.906
276861AD2-134 GEN
Solar/Wind Harmer
0.054
276863AD2-134 GEN
Solar/Wind Harmer
0.054
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
NYPJM->LTFIMP_NY
CLTF
1.597
LGEELTFEXP_LGEE->PJM
CLTF
5.305
WECLTFEXP_WEC->PJM
CLTF
1.662
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.865
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.274
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.431
MECLTFEXP_MEC->PJM
CLTF
7.137
SIGELTFEXP_SIGE->PJM
CLTF
0.33
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
TVALTFEXP_TVA->PJM
CLTF
2.665

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.82 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2406.35
MW Contribution:
2.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970521AG2-332 GEN
50/50
10.906
24639705ELKHART HY
50/50
0.151
270143AC1-141 CT2_
50/50
2.029
965421AG1-410 GEN
Solar/Wind Harmer
81.797
24727005RPMNG1
50/50
3.317
943021AE2-325 GEN
Solar/Wind Harmer
3
970373AG2-245 GEN
Solar/Wind Harmer
11.243
971917AH1-482 GEN
Solar/Wind Harmer
6.75
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.82
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.578
959081AF2-199 GEN
Solar/Wind Harmer
4.884
971067AG2-660 GEN
Solar/Wind Harmer
1.628
274822ROCKFORD ;11
Adder
13.696
970819AG2-516 GEN
Solar/Wind Harmer
5.809
276646AC1-214 GEN2
Solar/Wind Harmer
0.185
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
10.473
960861AF2-377 GEN
50/50
2.406
965011AG1-365 GEN
Solar/Wind Harmer
13.822
958861AF2-177 GEN
Solar/Wind Harmer
2.694
945111AF1-176 GEN
Solar/Wind Harmer
10.683
957891AF2-083 GEN
Solar/Wind Harmer
9.802
945371AF1-202 GEN
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
6.312
274723RIVER EC ;12
Adder
13.681
274773LINCOLN ;4U
Adder
6.365
970773AG2-487 GEN
Solar/Wind Harmer
0.63
270578AF1-285 GEN2
Solar/Wind Helper
0.593
270286AF1-227 GEN2
Solar/Wind Helper
0.694
24642205MAYFLWER
50/50
0.031
274753CRETE EC ;3U
Adder
6.312
274814UNIV PK N;0U
Adder
3.826
274807UNIV PK N;3U
Adder
3.817
274803UNIV PARK;6U
Adder
4.369
972038AH1-567 GEN2
Adder
0.273
276843GEN-1.7
Solar/Wind Harmer
0.168
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.101
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.381
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.157
965091AG1-374 GEN
Solar/Wind Harmer
13.726
965931AG1-462 GEN
Solar/Wind Harmer
11.666
24379505HDWTR1G C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
4.607
270043AE2-236 GEN
Solar/Wind Harmer
5.241
945111AF1-176 GEN
Solar/Wind Harmer
4.853
270505AE1-170 C O1
Solar/Wind Harmer
6.132
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.345
274724RIVER EC ;11
Adder
13.515
274772LINCOLN ;3U
Adder
6.365
972259AH1-714 GEN
Adder
14.153
274729ELWOOD EC;1P
Adder
12.11
970825AG2-519 GEN
Solar/Wind Harmer
3.795
946671AF1-331 GEN
Solar/Wind Harmer
0.524
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
970571AG2-364 GEN
Solar/Wind Harmer
9.675
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.998
942481AE2-261 GEN
Solar/Wind Harmer
12.255
246938BC-WTG3
Solar/Wind Helper
11.083
24729205KEY G1
50/50
0.366
247620Y3-023
50/50
0.467
944541AF1-119 GEN
Solar/Wind Harmer
0.427
270031AE2-169
Solar/Wind Harmer
3.104
965791AG1-447 GEN
Solar/Wind Harmer
5.106
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.41
958011AF2-095 GEN
Solar/Wind Harmer
7.498
274695ROCKY RD ;2P
Adder
8.016
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
7.476
276872AE1-163_GEN1
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.526
274765LEE CO EC;6U
Adder
6.396
274763LEE CO EC;4U
Adder
6.321
24699105WLD G1 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.494
270383AD1-128 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
0.562
241960AC2-195 GEN
Solar/Wind Helper
0.697
270144AC1-141 ST1_
50/50
1.792
959331AF2-224 GEN
Solar/Wind Harmer
9.676
965041AG1-368 GEN
Solar/Wind Harmer
8.443
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.922
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.13
274776LINCOLN ;7U
Adder
6.365
274687WILL CNTY;4U
Adder
20.685
274687WILL CNTY;4U
Adder
20.685
274731ELWOOD EC;2P
Adder
12.11
274733ELWOOD EC;3P
Adder
12.11
274746AC1-111 G10
Adder
4.068
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.821
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.976
944221AF1-090 GEN
Solar/Wind Harmer
2.312
270356AE2-297 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.876
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
3.792
270055AF2-134 C O1
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.662
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
12.933
274828WAUKEGAN ;BP
Adder
7.939
957471AF2-041 GEN
Solar/Wind Harmer
14.651
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.287
24728605AND G2
Adder
2.099
965431AG1-411 GEN
50/50
45.443
24727105RPMNG2
50/50
3.318
270142AC1-141 CT1_
50/50
2.029
24695305TIMB G C
Solar/Wind Harmer
0.532
274811UNIV PK N;7U
Adder
3.792
276806AD2-047 C O1
Solar/Wind Harmer
2.951
247642Z2-115 C
Solar/Wind Harmer
0.002
274676JOLIET 29;8U
Adder
21.852
274734ELWOOD EC;8P
Adder
12.11
274736ELWOOD EC;9P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.564
946031AF1-268 GEN
Solar/Wind Harmer
4.838
943121AE2-341 GEN
Solar/Wind Harmer
8.518
943591AF1-030 GEN
Solar/Wind Harmer
5.665
274682WAUKEGAN ;7U
Adder
12.933
959091AF2-200 GEN
Solar/Wind Harmer
9.768
274767LEE CO EC;8U
Adder
6.306
971087AG2-675 GEN
Solar/Wind Harmer
2.44
957381AF2-032 GEN
Solar/Wind Harmer
0.932
24728505AND G1
Adder
2.099
270284AF1-227 GEN1
Solar/Wind Helper
1.893
276820AF1-078_GEN
Solar/Wind Helper
0.334
270246TR4_N_V150
Solar/Wind Harmer
0.046
965681AG1-436 GEN
Solar/Wind Harmer
6.963
247621Y3-024
Adder
0.183
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.555
970291AG2-192 GEN
Solar/Wind Harmer
0.666
970291AG2-192 GEN
Solar/Wind Harmer
0.308
971613AH1-306 GEN
Solar/Wind Harmer
2.442
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.768
971343AH1-151 GEN
Solar/Wind Harmer
9.768
276916AD2-100_GEN
Solar/Wind Harmer
8.532
971587AH1-292 GEN
Solar/Wind Harmer
2.468
270349AD2-093_GEN
Solar/Wind Helper
0.857
270471AD2-092_GEN
Solar/Wind Helper
0.857
24727205RPMNG3
50/50
3.298
963791AG1-232 GEN
Solar/Wind Harmer
12.035
247521TR3_G114
Solar/Wind Harmer
0.261
274827FISK ;RP
Adder
5.808
274800UNIV PARK;3U
Adder
4.357
274801UNIV PARK;4U
Adder
4.357
972227AH1-698 GEN1
Adder
1.941
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.974
274744AC1-111 GEN8
Adder
4.068
970169AG2-114 GEN
Solar/Wind Harmer
4.823
276741O09 GEN1
Solar/Wind Harmer
0.167
274877BISHOP HL;1U
Solar/Wind Harmer
0.157
959341AF2-225 GEN
Solar/Wind Harmer
4.889
276668AB2-070 GEN1
Solar/Wind Harmer
0.17
276848AB2-070 GEN3
Solar/Wind Harmer
0.169
276849AB2-070 GEN2
Solar/Wind Harmer
0.17
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.609
270227U2-072_GEN3
Solar/Wind Helper
0.876
270228U2-072_GEN4
Solar/Wind Helper
0.876
270231U2-072_GEN5
Solar/Wind Helper
0.876
970583AG2-370 GEN
50/50
2.814
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.981
971347AH1-153 GEN
Solar/Wind Harmer
2.927
274752CRETE EC ;2U
Adder
6.312
274826FISK ;BP
Adder
8.195
274887GEN-1.85
Solar/Wind Harmer
0.135
970707AG2-453 GEN
Solar/Wind Harmer
16.903
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
12.11
274862TOP CROP ;2U
Solar/Wind Harmer
0.681
276868AE1-113 GEN
Solar/Wind Harmer
0.991
274879MINONK ;1U
Solar/Wind Harmer
0.207
274855GSG-6 ;RU
Solar/Wind Harmer
0.179
970781AG2-491 GEN
Solar/Wind Harmer
4.895
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
1.525
970193AG2-126 GEN
Solar/Wind Harmer
5.956
24728705AND G3
Adder
4.39
942871AE2-306 GEN
Solar/Wind Helper
0.445
270287AF1-227 GEN3
Solar/Wind Helper
0.694
270541AE2-072 C
Solar/Wind Helper
0.943
24643105BUCHANAN
50/50
0.01
270247TR4_N_V136
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
16.139
960971AF2-388 GEN
Solar/Wind Harmer
3.752
970349AG2-230 GEN
Solar/Wind Harmer
8.78
961051AF2-396 GEN
Solar/Wind Harmer
11.674
961051AF2-396 GEN
Solar/Wind Harmer
7.782
270599AE1-208 GEN
Solar/Wind Harmer
5.173
274808UNIV PK N;4U
Adder
3.776
274674JOLIET 9 ;6U
Adder
11.348
958481AF2-142 GEN
Solar/Wind Harmer
7.57
274693ROCKY RD ;1P
Adder
7.937
274683WAUKEGAN ;8U
Adder
15.145
274683WAUKEGAN ;8U
Adder
12.766
276876AE1-163_GEN2
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.755
274764LEE CO EC;5U
Adder
6.396
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.533
960611AF2-352 GEN
Solar/Wind Harmer
1.525
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.481
276615X2-022 GEN
Solar/Wind Harmer
0.044
945391AF1-204 GEN
Solar/Wind Harmer
4.219
270462AD2-086
Solar/Wind Helper
3.747
24729405KEY G3
50/50
0.374
24729305KEY G2
50/50
0.367
960851AF2-376 GEN
50/50
2.095
942221AE2-234 GEN
Solar/Wind Harmer
2.855
274805UNIV PK N;1U
Adder
3.801
274770LINCOLN ;1U
Adder
6.365
274771LINCOLN ;2U
Adder
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
0.304
970941AG2-585 GEN
Solar/Wind Harmer
2.864
276897AD1-100 C
Solar/Wind Harmer
12.887
276893AG1-478 C
Solar/Wind Harmer
0.343
274697ROCKY RD ;3P
Adder
2.178
274696ROCKY RD ;4P
Adder
8.205
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
14.951
938861AE1-114 GEN
Solar/Wind Harmer
2.722
274762LEE CO EC;3U
Adder
6.381
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.763
276645AC1-214 GEN1
Solar/Wind Harmer
0.185
24387305FR-4G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
1.513
970241AG2-163 GEN
Solar/Wind Harmer
2.581
276838X2-022 GEN2
Solar/Wind Harmer
0.239
970623AG2-406 GEN
Solar/Wind Harmer
0.656
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.897
247522W1-056 GEN
Solar/Wind Helper
1.177
253378AE2-206_GEN
Solar/Wind Helper
0.715
24641605TWIN BRNCH
50/50
0.015
970031AG2-029 GEN
Solar/Wind Harmer
4.587
965051AG1-369 GEN
Solar/Wind Harmer
3.602
945581AF1-223 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
6.365
274777LINCOLN ;8U
Adder
6.365
972037AH1-567 GEN1
Adder
0.137
960591AF2-350 GEN
Solar/Wind Harmer
5.207
972228AH1-698 GEN2
Adder
2.756
274675JOLIET 29;7U
Adder
22.662
274675JOLIET 29;7U
Adder
21.853
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
5.628
970833AG2-524 GEN
Solar/Wind Harmer
3.752
971611AH1-305 GEN
Solar/Wind Harmer
3.031
247536S-71 GEN
Solar/Wind Harmer
0.199
971411AH1-196 GEN
Solar/Wind Harmer
7.376
971675AH1-338 GEN
Solar/Wind Harmer
1.916
971171AH1-044 GEN
Solar/Wind Harmer
9.768
274823ROCKFORD ;21
Adder
13.596
972267AH1-718 GEN
Adder
2.828
24386405FR-21G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
2.577
971029AG2-637 GEN
Solar/Wind Harmer
5.928
270224U2-072_GEN2
Solar/Wind Helper
0.876
945641AF1-229 GEN
Solar/Wind Helper
0.94
274754CRETE EC ;4U
Adder
6.312
274802UNIV PARK;5U
Adder
4.369
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
11.348
274732ELWOOD EC;7P
Adder
12.11
962781AG1-127 GEN
Solar/Wind Harmer
4.731
939401AE1-172 GEN
Solar/Wind Harmer
3.718
276903AD2-071 C
Solar/Wind Harmer
5.426
274766LEE CO EC;7U
Adder
6.306
276708O09 GEN2
Solar/Wind Harmer
0.167
24385905FR-11G C
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.82
270317AD1-130_GEN
Solar/Wind Helper
4.143
270391AF1-285 GEN3
Solar/Wind Helper
0.593
24729505KEY G4
50/50
6.847
24653605MOTTVILLE
50/50
0.004
270071AF1-092 GEN
Solar/Wind Harmer
14.566
971771AH1-392 GEN
Solar/Wind Harmer
5.907
274728ELWOOD EC;5P
Adder
12.11
970073AG2-061 GEN
Solar/Wind Harmer
1.661
276861AD2-134 GEN
Solar/Wind Harmer
0.088
276863AD2-134 GEN
Solar/Wind Harmer
0.088
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
971681AH1-341 GEN
Solar/Wind Harmer
7.736
971549AH1-272 GEN
Solar/Wind Harmer
9.898
270543AE2-219 C
Solar/Wind Harmer
3.137
270007AE1-245 C
Solar/Wind Harmer
0
274774LINCOLN ;5U
Adder
6.365
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.364
270594AE1-207 GEN
Solar/Wind Harmer
5.699
270032AE2-172
Solar/Wind Harmer
3.392
270005AE1-210 C O1
Solar/Wind Harmer
1.101
970825AG2-519 GEN
Solar/Wind Harmer
1.788
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
2.59
970569AG2-363 GEN
Solar/Wind Harmer
14.512
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.381
24386605FR-22G C
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.519
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.213
246936BC-WTG1
Solar/Wind Helper
10.897
270485AE1-090_GEN
Solar/Wind Helper
0.326
960841AF2-375 GEN
Solar/Wind Helper
1.179
270223U2-072_GEN1
Solar/Wind Helper
0.876
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
1.968
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
NYPJM->LTFIMP_NY
CLTF
1.264
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
AG2-052LTFEXP_AG2-052->PJM
LTF
0.172
AH1-155LTFEXP_AH1-155->PJM
LTF
0.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.835
CBM West 1LTFEXP_CBM-W1->PJM
CBM
70.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.933
MECLTFEXP_MEC->PJM
CLTF
9.784
SIGELTFEXP_SIGE->PJM
CLTF
0.201
LAGNLTFEXP_LAGN->PJM
CLTF
5.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.51
TVALTFEXP_TVA->PJM
CLTF
2.319
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
243211 to 242933 ckt 1
242920 to 235102 ckt 5
247977 to 242524 ckt 17
242519 to 314912 ckt 1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
246929 to 242935 ckt 1
242926 to 246751 ckt 1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
242516 to 242920 ckt 1
242933 to 965420 ckt 1
243232 to 246999 ckt 3
246999 to 290607 ckt Z1
243233 to 249567 ckt 1
248005 to 242528 ckt 1
965420 to 246929 ckt 1

Winter Peak Analysis

The New Service Request AH1-292 was evaluated as a 0.0 MW (44.0 MW Capacity) injection in the AEP area.

AH1-292 was evaluated as part of a plant. The plant consists of AH1-292. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-292 was evaluated as a 0.0 MW injection

AH1-292 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

PJM has reviewed this project submission and determined that a stability study is not required as this is a CIR only increase with no changes to equipment/electrical parameters (no change to MFO).

Reactive Power Analysis

Not Required

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements based on the project Agreements per PJM’s Tariff, Part IX, Subpart B, App. 2, section 4.6.1.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVEngineering & Procurement
AC1-214Crescent RidgeIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-120Ripley 69kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVWithdrawn
AD2-093Marysville 345kVPartially in Service - Under Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-092Blue Jacket-Kirby 138 kVEngineering & Procurement
AE1-102Maddox Creek 345 kVSuspended
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-175Light Foot 34.5 kVIn Service
AE1-183Maysville-McDowell 69 kVUnder Construction
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVPartially in Service - Under Construction
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-089Pennville-Adams 138 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-214Cole 345 kVUnder Construction
AE2-216Hardin Switch 345 kVSuspended
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-285Maysville 69 kVUnder Construction
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVWithdrawn
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVPartially in Service - Under Construction
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-093Henderson-Stoneboro 69 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVSuspended
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVUnder Construction
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVEngineering & Procurement
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVUnder Construction
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-302Brookville-Squab Hollow 138 kVUnder Construction
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-014Maddox Creek 345 kVUnder Construction
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVWithdrawn
AF2-039Shawville-Clearfield 34.5 kVUnder Construction
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-122Kirk 138 kVPartially in Service - Under Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVPartially in Service - Under Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-109Valley 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-198Union City 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-471Up Church-Wayne County 69 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-508Point Lookout 69 kVWithdrawn
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-029Forest G. Hipple-Dunton Lake 345 kVActive
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-332East Elkhart - Elcona Tap 138 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-424Summersville - Magnolia 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-348Pound 34.5 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Delaware Business Park 138kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
W2-048Brokaw-LanesvilleIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9769.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9769.0 / AEP-TC2-19070
Title
05CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBs
Description
Upgrade/replace Cloverdale 765 kV, 4000 A CBs "CC" and "CC2" to 5000 A
Total Cost ($USD)
$25,000,000
Discounted Total Cost ($USD)
$25,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-292 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-292 could receive cost allocation. Although AH1-292 may not presently have cost responsibility for this upgrade, AH1-292 is a potential Aggregate Pool Contributor.

FacilityContingency
05CLOVRD-05CLOVRD_RJA 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: n9763.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9763.0 / AEP-TC2-19060
Title
05J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace Wavetraps
Description
Replace wave trap on 765 kV Cloverdale line. Replace/upgrade CB's B and B2 with 5000A CBs.
Total Cost ($USD)
$3,300,000
Discounted Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-292 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-292 could receive cost allocation. Although AH1-292 may not presently have cost responsibility for this upgrade, AH1-292 is a potential Aggregate Pool Contributor.

FacilityContingency
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: n9767.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9767.0 / AEP-TC2-19068
Title
05KAMMER_RG 765.0 kV to 05KAMMER 765.0 kV ckt Z1 - Replace Wavetraps
Description
Replace the existing 3000A wave trap at Kammer 765 station towards Guernsey with a 5000A wave trap. Additionally, replace the 3000A circuit breaker QQ1 with a 5000A circuit breaker. Disconnect switches and a relays will be upgraded as well.
Total Cost ($USD)
$4,500,000
Discounted Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-292 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-292 could receive cost allocation. Although AH1-292 may not presently have cost responsibility for this upgrade, AH1-292 is a potential Aggregate Pool Contributor.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3851.2
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.2
Title
Rebuild R.P. Mone – Maddox Creek 345kV line (9.4 miles).
Description
Rebuild R.P. Mone – Maddox Creek 345kV line (9.4 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA
(All)C3774.0 MVA
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA
(All)C3774.0 MVA

System Reinforcement: n9786.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9786.0 / AEP-TC2-19161
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Wave Traps
Description
Replace wave tap at Maliszewski towards Marysville
Total Cost ($USD)
$3,000,000
Discounted Total Cost ($USD)
$3,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-292 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-292 could receive cost allocation. Although AH1-292 may not presently have cost responsibility for this upgrade, AH1-292 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B5523.0 MVA

System Reinforcement: n9766.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9766.0 / AEP-TC2_19067
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Wavetrap
Description
Replace 4000A Wavetrap towards Maliszewski with 5000A equivalent
Total Cost ($USD)
$1,100,000
Discounted Total Cost ($USD)
$1,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-292 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-292 could receive cost allocation. Although AH1-292 may not presently have cost responsibility for this upgrade, AH1-292 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Nov 12 2027

Not Contingent

Note: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B6667.0 MVA
(All)C6868.0 MVA

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Apr 03 2028

Not Contingent

Note: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: n9759.0
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
n9759.0 / OVEC-TC2-19030
Title
06KYGER 345.0 kV to 05SPORN 345.0 kV ckt 1 - Replace Equipment
Description
Sag study Sporn - Kyger Creek line and replace section #25 OVEC element conductor 12.51 Miles At Sporn replace the following equipment: 2 - 2000 KCM AAC, 91-Str., AA1S1, AA1S2, AAS1, AAS2, KYGER CREEK #1 - PH A, KYGER CREEK #1 - PH B At Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB
Total Cost ($USD)
$38,180,000
Discounted Total Cost ($USD)
$38,180,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-292 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-292 could receive cost allocation. Although AH1-292 may not presently have cost responsibility for this upgrade, AH1-292 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1942.0 MVA
(All)B2837.0 MVA
LLA1942.0 MVA
LLB2837.0 MVA

System Reinforcement: n9753.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9753.0 / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Discounted Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-292 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-292 could receive cost allocation. Although AH1-292 may not presently have cost responsibility for this upgrade, AH1-292 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1944.0 MVA
(All)B2825.0 MVA
(All)C2468.0 MVA

System Reinforcement: b2831.2
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
b2831.2
Title
Rebuild the Tanner Creek – Miami Fort 345kV line (DEOK portion), Actual In-service date 5/14/2021
Description
Rebuild the Tanner Creek – Miami Fort 345kV line (DEOK portion) Actual In-service date 5/14/2021
Cost Information
Time Estimate
May 14 2021

Not Contingent

Note: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2390.0 MVA
(All)B2390.0 MVA
(All)C2390.0 MVA

System Reinforcement: s2019
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
s2019 / AEP Project Resolves Overload
Title
AEP Project s2019 Resolves DEOK Overload
Description
Install two (2) new 345 kV breakers and move the existing M2 breaker into the new N string at Tanners Creek station. Terminate the Dearborn line and the transformer into the new N string. Install a new 345 kV breaker “T” to complete the T string. Projected in-service date 5/23/2023.
Cost Information
Time Estimate
May 26 2021

Not Contingent

Note: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-292 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2403.0 MVA
(All)B2403.0 MVA

System Reinforcement: b2968
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b2968
Title
Upgrade existing 345kV terminal equipment at Tanners Creek station on Tanners Creek - Miami Fort 345kV line, Actual In-Service Date 12/22/2020
Description
Upgrade existing 345kV terminal equipment at Tanners Creek station on Tanners Creek - Miami Fort 345kV line, Actual In-Service Date 12/22/2020
Cost Information
Time Estimate
Dec 22 2020

Not Contingent

Note: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B2542.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-292 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-292 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-292


AH1-292 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-292 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-292 One Line Diagram

AH1-292 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.